Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:57:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 28214.83 | 609.12 | 609.12 |
Net Site Energy | 27613.55 | 596.14 | 596.14 |
Total Source Energy | 87852.91 | 1896.64 | 1896.64 |
Net Source Energy | 85948.67 | 1855.53 | 1855.53 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 74.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1812.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 264.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2640.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 547.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1144.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12806.86 |
Humidification | 1609.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.65 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 647.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27493.06 | 721.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15685.67 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 74.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1812.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 264.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2640.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 547.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1144.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12806.86 |
Humidification | General | 1609.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.65 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 647.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 74.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1812.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 264.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2640.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 547.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1144.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12806.86 |
Humidification | Unassigned | 1609.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.65 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 647.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 44.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 205.86 | 15.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 593.54 | 15.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 44.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 205.86 | 15.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 593.54 | 15.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 627.210 | 2.28 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -25.93 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 601.276 | 2.19 |
Electricity Coming From Utility | 26891.781 | 97.81 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26891.781 | 97.81 |
Total On-Site and Utility Electric Sources | 27493.058 | 100.00 |
Total Electricity End Uses | 27493.058 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 15685.67 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 15685.67 | 100.00 |
Total Water End Uses | 15685.67 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1137.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5743.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-AUG-15:09 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 27-JUN-11:00 |
Heating | 0.00 | 557558.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 403847.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 154688.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52594.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 236794.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38718.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 75058.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30039.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1840073.21 | 587597.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 557558.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 403847.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 154688.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3364.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 236794.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 38718.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 75058.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 30039.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 81.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11384.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5740.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 837.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8361.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1732.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3623.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5096.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 701.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 87070.51 | 782.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 245.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 123.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 110.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1879.75 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 245.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 123.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 110.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1879.75 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.45 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.505947 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.83 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.494424 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 23.38 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.87 | 0.323921 | 0.275000 | 1.61 | 0.863790 | 0.500000 | 0.001176 | 0.000323 | 1.61 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.33 | 0.343768 | 0.292000 | 16.16 | 0.916714 | 0.500000 | 0.001108 | 0.007628 | 16.16 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.59 | 0.340525 | 0.289000 | 1.61 | 0.908066 | 0.500000 | 0.001119 | 0.001528 | 2.29 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.15 | 0.207256 | 0.176000 | 0.202804 | 0.552683 | 0.500000 | 0.001838 | 0.000137 | 0.205410 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.15 | 0.133828 | 0.114000 | 0.131102 | 0.356876 | 0.500000 | 0.002847 | 0.000104 | 0.155265 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.30 | 0.184086 | 0.156000 | 0.202388 | 0.490896 | 0.500000 | 0.002070 | 0.000199 | 0.298428 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.49 | 0.103619 | 0.088000 | 0.130706 | 0.300000 | 0.500000 | 0.003677 | 0.000068 | 0.130706 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.40 | 0.209505 | 0.178000 | 2.03 | 0.558681 | 0.500000 | 0.001819 | 0.003718 | 5.58 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.22 | 0.335836 | 0.500000 | 0.003025 | 0.002491 | 3.74 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.82 | 0.186303 | 0.158000 | 2.03 | 0.496808 | 0.500000 | 0.002045 | 0.003748 | 5.63 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.30 | 0.115746 | 0.098000 | 1.30 | 0.308657 | 0.500000 | 0.003292 | 0.002280 | 3.42 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.31 | 0.181985 | 0.155000 | 0.203408 | 0.485292 | 0.500000 | 0.002094 | 0.000478 | 0.718683 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.26 | 0.122338 | 0.104000 | 0.130835 | 0.326235 | 0.500000 | 0.003114 | 0.000318 | 0.477475 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.44 | 0.165482 | 0.141000 | 0.203493 | 0.441286 | 0.500000 | 0.002302 | 0.000482 | 0.723597 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.44 | 0.106609 | 0.091000 | 0.131371 | 0.300000 | 0.500000 | 0.003574 | 0.000301 | 0.451934 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 14760.54 | 0.000323 | 411.97 |
CORE_MID VAV BOX REHEAT COIL | 348699.57 | 0.007628 | 11572.53 |
CORE_TOP VAV BOX REHEAT COIL | 69854.32 | 0.001528 | 2719.87 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6280.03 | 0.000137 | 244.76 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4743.01 | 0.000104 | 184.75 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9106.45 | 0.000199 | 354.47 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3123.82 | 0.000068 | 107.50 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 169975.23 | 0.003718 | 6607.44 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 113858.05 | 0.002491 | 4425.73 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 171359.31 | 0.003748 | 6661.15 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 104241.24 | 0.002280 | 4052.44 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21873.29 | 0.000478 | 849.99 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14531.20 | 0.000318 | 564.65 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22022.54 | 0.000482 | 855.78 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13755.20 | 0.000301 | 534.53 |
VAV_BOT WITH REHEAT HEATING COIL | 31616.04 | 0.000692 | 713.11 |
VAV_MID WITH REHEAT HEATING COIL | 222060.98 | 0.004858 | 5084.44 |
VAV_TOP WITH REHEAT HEATING COIL | 21365.15 | 0.000467 | 492.97 |
CAV_BAS HEATING COIL | 238797.33 | 0.005224 | 7693.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.48 | 2.28 | 10.96 | 2.28 | 9.76 | 9.76 | 0.300000 | 0.233773 | 9.76 |
VAV_MID WITH REHEAT | 52.53 | 22.82 | 105.07 | 29.15 | 91.85 | 91.85 | 0.300000 | 0.317376 | 91.85 |
VAV_TOP WITH REHEAT | 5.52 | 2.28 | 11.04 | 4.66 | 10.55 | 10.55 | 0.300000 | 0.441643 | 10.55 |
CAV_BAS | 5.45 | 5.45 | 5.45 | 5.45 | 5.45 | 5.45 | 1.00 | 1.00 | 5.45 |
AIRLOOP DATACENTER BASEMENT | 23.38 | 23.38 | 23.38 | 23.38 | 23.38 | 23.38 | 1.00 | 0.999989 | 23.38 |
AIRLOOP DATACENTER BOT | 0.505947 | 0.505947 | 0.505947 | 0.505947 | 0.505947 | 0.505947 | 1.00 | 1.00 | 0.505947 |
AIRLOOP DATACENTER MID | 4.83 | 4.83 | 4.83 | 4.83 | 4.83 | 4.83 | 1.00 | 1.00 | 4.83 |
AIRLOOP DATACENTER TOP | 0.494424 | 0.494424 | 0.494424 | 0.494424 | 0.494424 | 0.494424 | 1.00 | 1.00 | 0.494424 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.76 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 91.85 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.55 | |
CAV_BAS_OA_CONTROLLER | 5.45 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 23.38 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.505947 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.83 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.494424 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.55 | 6.67 | 10.86 | 0.008154 | 0.008154 | 181629.63 | 0.005195 | 9.76 |
VAV_MID WITH REHEAT COOLING COIL | 27.86 | 6.67 | 10.86 | 0.008087 | 0.008087 | 1740531.15 | 0.049779 | 91.85 |
VAV_TOP WITH REHEAT COOLING COIL | 27.25 | 6.67 | 10.87 | 0.008152 | 0.008152 | 192709.21 | 0.005511 | 10.55 |
CAV_BAS COOLING COIL | 28.03 | 6.67 | 11.28 | 0.008206 | 0.008206 | 101774.83 | 0.002911 | 5.45 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.76 |
VAV_MID WITH REHEAT FAN | 91.85 |
VAV_TOP WITH REHEAT FAN | 10.55 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005195 | 0.000092 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000692 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.049779 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004858 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005511 | 0.000086 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000467 | |
CAV_BAS_COOLC_CONTROLLER | 0.002911 | 0.000164 |
CAV_BAS_HEATC_CONTROLLER | 0.005224 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.45 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 23.38 | 440009.89 | 287929.32 | 0.010776 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.505947 | 9313.23 | 6159.32 | 0.000228 |
AIRLOOP DATACENTER MID COOLING COIL | 4.83 | 88983.63 | 58827.18 | 0.002179 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.494424 | 9104.23 | 6020.03 | 0.000223 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 23.38 | 23.38 | 23.38 | 23.38 | 440009.89 | 440009.89 | 14683.19 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.505947 | 0.505947 | 0.505947 | 0.505947 | 9313.23 | 9313.23 | 678.30 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.83 | 4.83 | 4.83 | 4.83 | 88983.63 | 88983.63 | 6783.03 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.494424 | 0.494424 | 0.494424 | 0.494424 | 9104.23 | 9104.23 | 678.30 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 23.38 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.505947 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.83 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.494424 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 23.38 | 440009.89 | 0.010776 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.505947 | 9313.23 | 0.000228 |
AIRLOOP DATACENTER MID HEATING COIL | 4.83 | 88983.63 | 0.002179 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.494424 | 9104.23 | 0.000223 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14683.19 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 678.30 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6783.03 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 678.30 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000103 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.063396 | 10248.11 | |
HEATSYS1 PUMP | 0.035044 | 10449.31 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.063396 | 7.61 |
HEATSYS1 | 0.035044 | 4.21 |
COOLSYS1_SUPPLY | 0.063396 | 7.61 |
SINGLE WATER PLANT LOOP | 0.013406 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.063396 | 0.063396 | 266103.82 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1602023.30 | 1602023.30 | 0.035044 |
CENTRAL BOILER | 552214.72 | 540430.36 | 0.013406 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.031698 | 3547.56 |
COOLSYS1 CHILLER2 PUMP | 0.031698 | 3547.56 |
PLANT CIRC PUMP | 0.013406 | 3385.36 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.063396 | 0.032088 | 1124719.08 | 1130053.16 | 0.055556 |
COOLSYS1 CHILLER2 | 0.063396 | 0.032088 | 1124719.08 | 1130053.16 | 0.055556 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013406 | 139666.47 | 58835.43 | 69833.23 | 7004.20 | 21371.46 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.111113 | 13.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.111113 | 27236.68 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 45.34 | 1341282.77 | 9.07 | 167660.35 |
TOWERWATERSYS COOLTOWER 2 | 45.34 | 1341282.77 | 9.07 | 167660.35 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.058085 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.452 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.400 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.662 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5215 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5467 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4343 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.81534556E-15 | 0.47534309E-16 | -0.12491808E-09 | -0.15651055E-17 |
51 | 8 | 0.18376575E-07 | 0.18892299E-12 | 0.33997552E-03 | -0.20894799E-09 |
52 | 7 | -0.11109444E-01 | 0.10222184E-07 | -0.21454547E-01 | 0.12631841E-03 |
53 | 6 | 0.37458360 | 0.36213810E-05 | 0.44579641 | -0.43850983E-02 |
54 | 5 | -4.8902522 | 0.13734403E-03 | -4.2389002 | 0.59460182E-01 |
55 | 4 | 31.674104 | 0.11393769E-02 | 20.648451 | -0.40448134 |
56 | 3 | -108.39803 | 0.25142476E-02 | -54.058051 | 1.4743366 |
57 | 2 | 194.32686 | 0.14299560E-02 | 76.440274 | -2.8561868 |
58 | 1 | -170.12819 | 0.15421596E-03 | -54.840647 | 2.7274244 |
59 | 0 | 57.057407 | 0.88766417E-06 | 15.629571 | |
60 | 9 | 0.15527634E-14 | 0.48972640E-16 | -0.12737755E-09 | -0.48559044E-17 |
61 | 8 | 0.18724477E-07 | 0.18300980E-12 | 0.34384059E-03 | -0.21290374E-09 |
62 | 7 | -0.11225506E-01 | 0.98577958E-08 | -0.21621905E-01 | 0.12763808E-03 |
63 | 6 | 0.37773826 | 0.34860306E-05 | 0.44850155 | -0.44222837E-02 |
64 | 5 | -4.9210508 | 0.13200769E-03 | -4.2597582 | 0.59842059E-01 |
65 | 4 | 31.810414 | 0.10936068E-02 | 20.730162 | -0.40629104 |
66 | 3 | -108.68827 | 0.24103335E-02 | -54.219675 | 1.4785295 |
67 | 2 | 194.61479 | 0.13693941E-02 | 76.588171 | -2.8607587 |
68 | 1 | -170.23464 | 0.14753937E-03 | -54.883028 | 2.7292902 |
69 | 0 | 57.057407 | 0.84836289E-06 | 15.622061 | |
70 | 9 | 0.10580992E-14 | 0.52916478E-16 | -0.11479962E-09 | -0.26242945E-17 |
71 | 8 | 0.16943687E-07 | 0.21219816E-12 | 0.32378363E-03 | -0.19265555E-09 |
72 | 7 | -0.10622292E-01 | 0.11706466E-07 | -0.20751735E-01 | 0.12077931E-03 |
73 | 6 | 0.36134106 | 0.41796623E-05 | 0.43441658 | -0.42290030E-02 |
74 | 5 | -4.7609497 | 0.15957712E-03 | -4.1510514 | 0.57856955E-01 |
75 | 4 | 31.101728 | 0.13316855E-02 | 20.304070 | -0.39688243 |
76 | 3 | -107.17897 | 0.29539374E-02 | -53.376774 | 1.4567269 |
77 | 2 | 193.11717 | 0.16877407E-02 | 75.817308 | -2.8369794 |
78 | 1 | -169.68078 | 0.18278585E-03 | -54.662957 | 2.7195831 |
79 | 0 | 57.057407 | 0.10570564E-05 | 15.661738 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1376E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1391E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4572E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4584E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1322E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1331E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7516E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1706E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2646E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4846E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5652E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1550E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2218E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7664E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1044 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5954E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1167 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0313E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7338E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9424E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1496E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0924E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1750E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2864E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4893E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5885E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1591E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2376E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7668E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8046E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1375E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1391E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4570E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4584E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1321E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1331E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7515E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8889E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0741E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7066E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9049E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5250E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6121E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9952E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0209E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3314E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0727E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0514E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8793E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1911E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7152E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2799E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2243E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8387E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9061E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6426E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6916E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4977E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5174E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9953E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0213E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7708E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7722E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5123E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5135E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3404E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3412E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7516E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7522E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8031E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8840E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5387E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6029E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3616E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4079E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7668E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8046E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7726E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4518E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1327E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1023E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9123E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4449E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1496E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0921E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8016E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8823E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5368E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5993E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3584E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3981E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7664E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7707E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7721E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5122E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5133E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3403E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3410E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7515E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7521E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4967E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5662E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2212E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2714E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2028E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2211E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9954E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0213E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7376E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8453E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3255E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6013E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6503E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5058E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2799E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2243E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5392E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6917E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2758E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4333E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2287E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3087E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9952E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0208E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1045 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5255E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1133 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.0913E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5061E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4104E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8633E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9092E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1664E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0021E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8539E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7668E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9793E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5498E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9603E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9312E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4692E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3039E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7423E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8249E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4975E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3745E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8633E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9088E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.4944E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6875E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0317E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3811E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3724E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2693E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9603E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9312E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1046 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5397E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1134 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1077E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5201E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4215E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8716E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9134E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1707E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0067E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8587E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7712E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.9874E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5552E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9686E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9354E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4696E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3065E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7429E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8270E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5015E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3770E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8716E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9131E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.4974E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6914E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0350E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3847E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3794E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2740E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9686E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9354E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 68720.28254 | 68720.28254 | 5.44960 | 5.44960 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 0.50000 | 4.31558E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 74044.57189 | 74044.57189 | 5.87193 | 5.87193 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 697876.28438 | 697876.28438 | 55.32931 | 55.32931 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 201017.79884 | 201017.79884 | 9.31992 | 10.77825 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 69792.35724 | 69792.35724 | 5.58563 | 5.58563 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 48938.09311 | 48938.09311 | 2.28820 | 2.28820 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14398.58603 | 14398.58603 | 1.15230 | 1.15230 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4404.86292 | 4404.86292 | 0.20541 | 0.20541 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14370.17622 | 14370.17622 | 1.15002 | 1.15002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 34.99233 | 5.62211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3325.32531 | 3325.32531 | 0.15526 | 0.15526 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16211.22770 | 16211.22770 | 1.29736 | 1.29736 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 40.57833 | 5.63076E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6380.69067 | 6380.69067 | 0.29843 | 0.29843 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18559.66998 | 18559.66998 | 1.48529 | 1.48529 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1931.56185 | 1931.56185 | 8.95945E-002 | 8.95945E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 142444.85452 | 142444.85452 | 11.39925 | 11.39925 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 118978.37238 | 118978.37238 | 5.58184 | 5.58184 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 152709.90546 | 152709.90546 | 12.22065 | 12.22065 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 35.36917 | 5.62269E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 79694.10005 | 79694.10005 | 3.73935 | 3.73935 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 160188.92072 | 160188.92072 | 12.81923 | 12.81923 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 40.68917 | 5.63093E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 119945.86499 | 119945.86499 | 5.62740 | 5.62740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 166156.59213 | 166156.59213 | 13.29674 | 13.29674 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 72971.49380 | 72971.49380 | 3.42283 | 3.42283 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 16398.87050 | 16398.87050 | 1.31231 | 1.31231 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15306.88182 | 15306.88182 | 0.71868 | 0.71868 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15720.62897 | 15720.62897 | 1.25803 | 1.25803 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 36.07850 | 5.62379E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10168.64893 | 10168.64893 | 0.47747 | 0.47747 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18034.61702 | 18034.61702 | 1.44321 | 1.44321 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15411.22240 | 15411.22240 | 0.72360 | 0.72360 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18040.01591 | 18040.01591 | 1.44364 | 1.44364 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9626.11889 | 9626.11889 | 0.45193 | 0.45193 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8015.15154 | 8015.15154 | 0.50595 | 0.50595 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76526.04646 | 76526.04646 | 4.83066 | 4.83066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7832.58613 | 7832.58613 | 0.49442 | 0.49442 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 36.27800 | 5.62409E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370327.23692 | 370327.23692 | 23.37598 | 23.37598 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 28.69700 | 5.61258E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 0.50000 | 4.31558E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 155649.44 | 9.76068 | 9.76068 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 24679.27 | 1.82652 | 1.82652 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1462093.46 | 91.84596 | 91.84596 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 272529.10 | 29.14968 | 29.14968 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 166497.52 | 10.55126 | 10.55126 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 27309.24 | 4.65989 | 4.65989 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
7 | CAV_BAS | Cooling | Sensible | 80420.63 | 5.44960 | 5.44960 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 52075.95 | 1.20016 | 1.20016 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369277.77 | 23.37625 | 23.37625 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14683.19 | 0.33839 | 0.33839 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8047.15 | 0.50595 | 0.50595 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76884.59 | 4.83066 | 4.83066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6783.03 | 0.15632 | 0.15632 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7870.82 | 0.49442 | 0.49442 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.44960 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.87193 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32392 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27500 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61478 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86379 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17621E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.22887E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61478 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14760.54215 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.22887E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 411.96821 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.32931 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34377 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29200 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.15616 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91671 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10831E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.62781E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.15616 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 348699.57097 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.62781E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11572.52840 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.58563 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34052 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61425 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90807 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11886E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52807E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.28820 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 69854.32448 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52807E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2719.86846 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15230 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20726 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17600 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20280 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55268 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83831E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37376E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20541 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6280.02816 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37376E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.75659 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15002 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13383 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11400 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13110 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35688 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84693E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03753E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15526 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4743.01109 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03753E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 184.75378 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29736 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18409 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15600 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20239 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49090 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06968E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99204E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29843 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9106.44661 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99204E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 354.47070 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48529 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10362 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.80000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13071 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67692E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.83336E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13071 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3123.81587 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.83336E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 107.49993 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.39925 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20951 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02907 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55868 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81857E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.71821E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.58184 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 169975.23064 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.71821E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6607.43520 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.22065 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33584 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02528E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.49065E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.73935 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 113858.04841 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.49065E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4425.72974 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.81923 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18630 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15800 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02544 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49681 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04506E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.74849E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.62740 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 171359.31312 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.74849E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6661.15436 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.29674 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11575 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.80000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30308 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30866 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29168E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28028E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.42283 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 104241.24200 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28028E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4052.44033 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31231 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18198 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15500 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20341 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48529 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09358E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.78479E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71868 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21873.29058 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.78479E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 849.98594 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25803 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12234 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13084 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32624 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11432E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.17870E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47747 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14531.19719 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.17870E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 564.65400 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44321 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16548 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14100 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20349 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44129 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30236E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.81744E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72360 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22022.54018 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.81744E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 855.77855 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44364 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10661 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.10000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13137 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57380E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.00895E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45193 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13755.20284 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00895E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 534.53278 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50595 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.83066 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49442 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 23.37598 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.47845 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28178 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.95690 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28178 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.76068 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.76068 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.23377 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.53259 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.82135 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 105.06517 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.14968 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 91.84596 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 91.84596 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31738 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.52141 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28335 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.04282 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.65989 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.55126 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.55126 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.44164 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.44960 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.44960 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.44960 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.44960 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.44960 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.44960 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 23.37598 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 23.37598 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.37598 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 23.37598 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.37625 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 23.37625 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50595 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50595 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50595 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50595 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50595 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50595 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.83066 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.83066 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.83066 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.83066 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.83066 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.83066 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49442 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49442 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49442 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49442 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49442 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49442 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.76068 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 91.84596 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.55126 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.44960 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 23.37625 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50595 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.83066 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49442 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.76068 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.55025 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86203 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.15378E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.15378E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 181629.62661 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.19458E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.76068 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 31616.03808 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.91602E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 713.10507 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.76068 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.19458E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.16706E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.91602E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 91.84596 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.85902 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86179 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.08700E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.08700E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1740531.15097 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.97790E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 91.84596 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 222060.98457 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.85759E-003 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5084.43672 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 91.84596 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.97790E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.56610E-006 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.85759E-003 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.55126 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.25192 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87232 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.15151E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.15151E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 192709.20605 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.51146E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.55126 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 21365.14803 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.67363E-004 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 492.97007 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.55126 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.51146E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.64001E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.67363E-004 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.44960 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.02650 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.27945 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.20592E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.20592E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 101774.83028 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.91075E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.44960 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 238797.32774 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22370E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7693.71577 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.44960 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.91075E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.63597E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.22370E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.37625 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 23.37625 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 440009.89216 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 287929.32378 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07758E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 23.37625 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 23.37625 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 23.37625 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 23.37625 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 440009.89216 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 440009.89216 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14683.19080 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 23.37625 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 23.37625 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 440009.89216 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07758E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14683.19080 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.02964E-004 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50595 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50595 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9313.22679 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6159.32401 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28080E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50595 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50595 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50595 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50595 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9313.22679 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9313.22679 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50595 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50595 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9313.22679 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28080E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.83066 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.83066 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 88983.62635 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58827.18235 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.17920E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.83066 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.83066 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.83066 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.83066 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 88983.62635 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 88983.62635 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6783.02586 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.83066 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.83066 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 88983.62635 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.17920E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6783.02586 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49442 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49442 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9104.22655 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6020.02697 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22962E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49442 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49442 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49442 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49442 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9104.22655 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9104.22655 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49442 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49442 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9104.22655 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22962E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.33958E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 10248.10953 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.33958E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.60749 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.33958E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.33958E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 266103.81920 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.50443E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.20532 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.50443E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 10449.31235 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1602023.30272 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1602023.30000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.50443E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.33958E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.60749 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.16979E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3547.55592 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.16979E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3547.55592 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.33958E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.20880E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1124719.07506 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1130053.16000 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.55564E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.33958E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.20880E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1124719.07506 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1130053.16000 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.55564E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34061E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.60873 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34061E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3385.36195 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34061E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58835.42730 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21371.46059 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 552214.71928 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 540430.36000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34061E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11111 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.33352 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11111 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 27236.68012 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 45.34406 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1341282.76846 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.06881 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 167660.34606 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 45.34406 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1341282.76846 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.06881 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 167660.34606 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.80850E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.80850E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20550.58 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 485810.76 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 97243.35 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8742.32 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6602.68 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12676.98 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4351.24 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 236621.62 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 158501.22 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 238548.40 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 145113.65 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30449.72 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20228.83 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30657.50 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19148.56 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 36442.02 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 267662.04 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 26328.80 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 262494.58 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 240480.53 | 160207.94 | 80272.59 | 0.67 | 54076.18 | 548.47 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2290752.60 | 1518446.65 | 772305.96 | 0.66 | 517179.10 | 5245.52 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 258020.26 | 172448.17 | 85572.09 | 0.67 | 59594.10 | 604.44 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 131839.99 | 88439.64 | 43400.35 | 0.67 | 26578.15 | 269.57 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.80 | 23.21 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.80 | 23.21 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3479693400 | 0.2682492895 | Pass | Pass | 1.4346693748 | 5.0631625536 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.9679020703E-002 | 0.1333388517 | Pass | Pass | 0.1188188081 | 0.3229146463 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.5890801344E-002 | 7.8979131285E-002 | Pass | Pass | 7.7453761784E-002 | 0.2666688545 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.9224056628E-002 | 3.5902099750E-002 | Pass | Pass | 0.1941490672 | 0.3922673230 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.3609168109E-002 | 8.6854539507E-002 | Pass | Pass | 0.1180101104 | 0.3211104400 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1045592569 | 0.1322936828 | Pass | Pass | 0.1192237112 | 0.3243074414 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1868166571 | 0.2912396013 | Pass | Pass | 0.1467718009 | 0.4017518642 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1219362108 | 0.2342596732 | Pass | Pass | 0.1290439584 | 0.3660879120 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.4290272729E-002 | 4.0015121535E-002 | Pass | Pass | 7.6110947016E-002 | 0.2637329300 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0653171050E-002 | 9.9271944267E-002 | Pass | Pass | 7.6994461621E-002 | 0.2663058615 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1901173049 | 0.2487474050 | Pass | Pass | 9.7689349232E-002 | 0.3175796370 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1028102786 | 0.1351006852 | Pass | Pass | 7.3506084816E-002 | 0.2531454706 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1226432165 | 0.1577911689 | Pass | Pass | 15.2827679312 | 57.0565420677 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.5483836404E-002 | 0.1170351268 | Pass | Pass | 14.0979467238 | 54.5073972040 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1552045341 | 0.1183525075 | Pass | Pass | 0.2005985286 | 0.4000975035 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1227094454 | 0.1178194360 | Pass | Pass | 2.1647229502 | 22.9492070162 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.5639103165E-002 | 2.4626814230E-002 | Pass | Pass | 7.7926162689 | 88.3126076488 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9597854863E-002 | 3.2953536575E-002 | Pass | Pass | 0.1234998924 | 0.3858436512 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8703465928E-002 | 6.0771737047E-002 | Pass | Pass | 0.1972976946 | 0.3893800252 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7035790112E-006 | 5.6869290999E-006 | Pass | Pass | 7.0490018036E-003 | 7.6473208244E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.6132680834E-003 | 1.3166857328E-002 | Pass | Pass | 0.1607222380 | 0.3833397242 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.4484355016E-002 | 3.5875625221E-002 | Pass | Pass | 9.9888510512E-002 | 0.3970712262 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7967107865E-005 | 2.5283160716E-005 | Pass | Pass | 7.8755207466E-005 | 1.0587210008E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5168.45 | 41.35 | 0.00 | 15390.73 | 24191.70 | 44792.25 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 1390.74 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.586 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 122.81 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 110.29 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 1102.91 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 110.29 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.36 | 0.0000 | Y | 7.94 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.06 | 0.0000 | Y | 5.05 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 22.99 | 0.0000 | Y | 7.81 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.23 | 0.0000 | Y | 5.09 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.30 | 0.0000 | Y | 79.21 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.04 | 0.0000 | Y | 50.46 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 22.97 | 0.0000 | Y | 78.06 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.19 | 0.0000 | Y | 50.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.30 | 0.0000 | Y | 7.92 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.04 | 0.0000 | Y | 5.05 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 22.96 | 0.0000 | Y | 7.81 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.19 | 0.0000 | Y | 5.08 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.96 | 0.0000 | Y | 34.81 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 37.39 | 168.00 | 36.42 | 0.0000 | Y | 1.78 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 37.39 | 168.00 | 36.42 | 0.0000 | Y | 17.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 37.39 | 168.00 | 36.42 | 0.0000 | Y | 1.78 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 571.42 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.79 | 41.79 | 101.60 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.79 | 62.79 | 10.84 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.79 | 47.06 | 152.09 | |
Exterior Lighting Total | 31088.59 | 264.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2209817.35 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1602023.30 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1130053.16 | 6.59 | 991314.38 | 5.87 | 6.80 | 23.21 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1130053.16 | 6.59 | 991314.38 | 5.87 | 6.80 | 23.21 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 540430.36 | 0.90 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1341282.77 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1341282.77 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 181629.63 | 240480.53 | 160207.94 | 80272.59 | 0.67 | - | 54076.18 | 548.47 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1740531.15 | 2290752.60 | 1518446.65 | 772305.96 | 0.66 | - | 517179.10 | 5245.52 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 192709.21 | 258020.26 | 172448.17 | 85572.09 | 0.67 | - | 59594.10 | 604.44 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 101774.83 | 131839.99 | 88439.64 | 43400.35 | 0.67 | - | 26578.15 | 269.57 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 440009.89 | 287929.32 | 152080.57 | 0.65 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9313.23 | 6159.32 | 3153.90 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 88983.63 | 58827.18 | 30156.44 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9104.23 | 6020.03 | 3084.20 | 0.66 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 14760.54 | 20550.58 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 348699.57 | 485810.76 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 69854.32 | 97243.35 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6280.03 | 8742.32 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4743.01 | 6602.68 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9106.45 | 12676.98 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3123.82 | 4351.24 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 169975.23 | 236621.62 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 113858.05 | 158501.22 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 171359.31 | 238548.40 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 104241.24 | 145113.65 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21873.29 | 30449.72 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14531.20 | 20228.83 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22022.54 | 30657.50 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13755.20 | 19148.56 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 31616.04 | 36442.02 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 222060.98 | 267662.04 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 21365.15 | 26328.80 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 238797.33 | 262494.58 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 440009.89 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9313.23 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 88983.63 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9104.23 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14683.19 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6783.03 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.76 | 21092.32 | 2160.95 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 91.85 | 198474.22 | 2160.95 | 1.00 | 1.08 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.55 | 22679.56 | 2149.46 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.45 | 9240.63 | 1695.65 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 23.38 | 38553.21 | 1649.25 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 566.72 | 1120.11 | 1.00 | 1.60 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.83 | 5410.86 | 1120.11 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 553.81 | 1120.11 | 1.00 | 1.61 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.063396 | 10248.11 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.035044 | 10449.31 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.031698 | 3547.56 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.031698 | 3547.56 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013406 | 3385.36 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.111113 | 27236.68 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 68720.28 | 68720.28 | 24.72 | 5.450 | 5.450 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00901 | 30.96 | 0.00562 | 1.200 | 0.00 |
CORE_BOTTOM | 74044.57 | 74044.57 | 29.66 | 5.872 | 5.872 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 30.96 | 0.00562 | 1.078 | 0.00 |
CORE_MID | 697876.28 | 697876.28 | 279.58 | 55.329 | 55.329 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 30.96 | 0.00562 | 10.778 | 0.00 |
CORE_TOP | 69792.36 | 69792.36 | 27.96 | 5.586 | 5.586 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00894 | 40.67 | 0.00563 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14398.59 | 14398.59 | 45.94 | 1.152 | 1.152 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00870 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14370.18 | 14370.18 | 71.15 | 1.150 | 1.150 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00862 | 34.99 | 0.00562 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16211.23 | 16211.23 | 51.72 | 1.297 | 1.297 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00867 | 40.58 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18559.67 | 18559.67 | 91.89 | 1.485 | 1.485 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00860 | 39.12 | 0.00563 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 142444.85 | 142444.85 | 454.50 | 11.399 | 11.399 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00861 | 40.80 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 152709.91 | 152709.91 | 756.08 | 12.221 | 12.221 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00856 | 35.37 | 0.00562 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 160188.92 | 160188.92 | 511.10 | 12.819 | 12.819 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00859 | 40.69 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 166156.59 | 166156.59 | 822.66 | 13.297 | 13.297 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00856 | 38.94 | 0.00563 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16398.87 | 16398.87 | 52.32 | 1.312 | 1.312 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00856 | 40.53 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15720.63 | 15720.63 | 77.83 | 1.258 | 1.258 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00854 | 36.08 | 0.00562 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18034.62 | 18034.62 | 57.54 | 1.443 | 1.443 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00856 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18040.02 | 18040.02 | 89.32 | 1.444 | 1.444 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00853 | 38.94 | 0.00563 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8015.15 | 8015.15 | 221.40 | 0.506 | 0.506 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76526.05 | 76526.05 | 2113.82 | 4.831 | 4.831 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7832.59 | 7832.59 | 216.35 | 0.494 | 0.494 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 36.28 | 0.00562 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370327.24 | 370327.24 | 472.55 | 23.376 | 23.376 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 28.70 | 0.00561 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.34 | 0.00432 | 0.50 | 0.00432 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.76 | 0.00432 | 0.50 | 0.00432 | 1.078 | 0.00 | |
CORE_MID | 201017.80 | 201017.80 | 80.53 | 9.320 | 10.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 10.778 | 0.00 |
CORE_TOP | 48938.09 | 48938.09 | 19.61 | 2.288 | 2.288 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4404.86 | 4404.86 | 14.05 | 0.205 | 0.205 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00735 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3325.33 | 3325.33 | 16.46 | 0.155 | 0.155 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6380.69 | 6380.69 | 20.36 | 0.298 | 0.298 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1931.56 | 1931.56 | 9.56 | 0.090 | 0.090 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00692 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 118978.37 | 118978.37 | 379.62 | 5.582 | 5.582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 79694.10 | 79694.10 | 394.57 | 3.739 | 3.739 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 119945.86 | 119945.86 | 382.70 | 5.627 | 5.627 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 72971.49 | 72971.49 | 361.29 | 3.423 | 3.423 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15306.88 | 15306.88 | 48.84 | 0.719 | 0.719 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10168.65 | 10168.65 | 50.35 | 0.477 | 0.477 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15411.22 | 15411.22 | 49.17 | 0.724 | 0.724 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9626.12 | 9626.12 | 47.66 | 0.452 | 0.452 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.65 | 0.00672 | 0.50 | 0.00432 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.63 | 0.00459 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.76 | 9.76 | 1.83 | 1.83 | 9.7607 | 2.2818 | 9.7607 | 0.2338 | 0.3000 |
VAV_MID WITH REHEAT | 91.85 | 91.85 | 29.15 | 29.15 | 91.8460 | 29.1497 | 91.8460 | 0.3174 | 0.3000 |
VAV_TOP WITH REHEAT | 10.55 | 10.55 | 4.66 | 4.66 | 10.5513 | 4.6599 | 10.5513 | 0.4416 | 0.3000 |
CAV_BAS | 5.45 | 5.45 | 1.20 | 1.20 | 5.4496 | 5.4496 | 5.4496 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.38 | 23.38 | 0.34 | 0.34 | 23.3762 | 23.3760 | 23.3762 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5059 | 0.5059 | 0.5059 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.83 | 4.83 | 0.16 | 0.16 | 4.8307 | 4.8307 | 4.8307 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4944 | 0.4944 | 0.4944 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 14760.542 | 14760.542 | 1.614782 | 0.00032289 | 411.968 | 12/21 00:10:00 | 12/21 00:10:00 | 14760.54 | 14760.54 | 1.614782 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 14785.88 | 14785.88 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 348699.571 | 348699.571 | 16.156159 | 0.00762781 | 11572.528 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 348699.57 | 348699.57 | 16.156159 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 201017.80 | 0.00 | 349562.83 | 349562.83 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 69854.324 | 69854.324 | 2.288205 | 0.00152807 | 2719.868 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 69854.32 | 69854.32 | 2.288205 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 48938.09 | 0.00 | 70003.04 | 70003.04 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6280.028 | 6280.028 | 0.205410 | 0.00013738 | 244.757 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6280.03 | 6280.03 | 0.205410 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00735091 | 43.1891 | 4404.86 | 0.00 | 6293.40 | 6293.40 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4743.011 | 4743.011 | 0.155265 | 0.00010375 | 184.754 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4743.01 | 4743.01 | 0.155265 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00746318 | 43.8409 | 3325.33 | 0.00 | 4753.11 | 4753.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9106.447 | 9106.447 | 0.298428 | 0.00019920 | 354.471 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9106.45 | 9106.45 | 0.298428 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00762684 | 44.7901 | 6380.69 | 0.00 | 9125.83 | 9125.83 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3123.816 | 3123.816 | 0.130706 | 0.00006833 | 107.500 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3123.82 | 3123.82 | 0.130706 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00691939 | 40.6817 | 1931.56 | 0.00 | 3131.26 | 3131.26 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 169975.231 | 169975.231 | 5.581843 | 0.00371821 | 6607.435 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 169975.23 | 169975.23 | 5.581843 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777456 | 45.6468 | 118978.37 | 0.00 | 170337.22 | 170337.22 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 113858.048 | 113858.048 | 3.739350 | 0.00249065 | 4425.730 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 113858.05 | 113858.05 | 3.739350 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778157 | 45.6875 | 79694.10 | 0.00 | 114100.53 | 114100.53 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 171359.313 | 171359.313 | 5.627405 | 0.00374849 | 6661.154 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 171359.31 | 171359.31 | 5.627405 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777757 | 45.6643 | 119945.86 | 0.00 | 171724.25 | 171724.25 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 104241.242 | 104241.242 | 3.422831 | 0.00228028 | 4052.440 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 104241.24 | 104241.24 | 3.422831 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00774593 | 45.4810 | 72971.49 | 0.00 | 104463.24 | 104463.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21873.291 | 21873.291 | 0.718683 | 0.00047848 | 849.986 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21873.29 | 21873.29 | 0.718683 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780558 | 45.8267 | 15306.88 | 0.00 | 21919.88 | 21919.88 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14531.197 | 14531.197 | 0.477475 | 0.00031787 | 564.654 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14531.20 | 14531.20 | 0.477475 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780574 | 45.8277 | 10168.65 | 0.00 | 14562.15 | 14562.15 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22022.540 | 22022.540 | 0.723597 | 0.00048174 | 855.779 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22022.54 | 22022.54 | 0.723597 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780701 | 45.8350 | 15411.22 | 0.00 | 22069.44 | 22069.44 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13755.203 | 13755.203 | 0.451934 | 0.00030090 | 534.533 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13755.20 | 13755.20 | 0.451934 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00779308 | 45.7543 | 9626.12 | 0.00 | 13784.50 | 13784.50 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 181629.627 | -999.000 | 9.760683 | 0.00519458 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 181629.63 | 181629.63 | 9.760683 | 27.55 | 16.32 | 0.00815378 | 10.86 | 10.09 | 0.00815378 | 40.80 | 0.00563111 | 18.58 | 20.8028 | 24.00 | 0.00882994 | 43.1322 | 120030.35 | 0.00 | 196261.78 | 186925.68 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 31616.038 | 31616.038 | 2.928205 | 0.00069160 | 713.105 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31616.04 | 31616.04 | 2.928205 | 2.97 | 2.38 | 0.00470728 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 69.3428 | 21.64 | 0.00625214 | 35.3732 | 16042.44 | 0.00 | 31753.50 | 31753.50 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1740531.151 | -999.000 | 91.845957 | 0.04977897 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1740531.15 | 1740531.13 | 91.845957 | 27.86 | 16.37 | 0.00808700 | 10.86 | 10.03 | 0.00808700 | 40.80 | 0.00563111 | 18.58 | 22.1088 | 24.00 | 0.00881952 | 43.0815 | 1104405.51 | 0.00 | 1879547.29 | 1798385.86 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 222060.985 | 222060.985 | 27.553787 | 0.00485759 | 5084.437 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 222060.98 | 222060.98 | 27.553787 | 5.46 | 4.30 | 0.00519407 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 73.6959 | 19.61 | 0.00732612 | 46.8939 | 249429.73 | 0.00 | 233257.76 | 233257.76 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 192709.206 | -999.000 | 10.551260 | 0.00551146 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 192709.21 | 192709.20 | 10.551260 | 27.25 | 16.22 | 0.00815151 | 10.87 | 10.10 | 0.00815151 | 40.80 | 0.00563111 | 18.58 | 19.2441 | 24.00 | 0.00875664 | 42.7784 | 131349.03 | 0.00 | 208484.86 | 198536.06 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 21365.148 | 21365.148 | 3.165378 | 0.00046736 | 492.970 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21365.15 | 21365.15 | 3.165378 | 6.66 | 5.30 | 0.00552939 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 64.1472 | 17.60 | 0.00746132 | 54.1694 | 28471.41 | 0.00 | 22946.02 | 22946.02 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 101774.830 | -999.000 | 5.449597 | 0.00291075 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 101774.83 | 101774.83 | 5.449597 | 28.03 | 16.52 | 0.00820592 | 11.28 | 10.32 | 0.00820592 | 40.13 | 0.00563007 | 18.37 | 22.0228 | 24.00 | 0.00906279 | 44.2540 | 60075.71 | 0.00 | 109793.81 | 105660.88 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 238797.328 | 238797.328 | 5.449597 | 0.00522370 | 7693.716 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 238797.33 | 238797.33 | 5.449597 | 0.11 | 0.11 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 22.0228 | 25.34 | 0.00431558 | 19.6025 | 0.00 | 0.00 | 188488.92 | 188488.92 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 440009.892 | 287929.324 | 23.376249 | 0.01077581 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 400147.82 | 400134.82 | -999.0 | 28.73 | 16.99 | 0.00850024 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | -999.0000 | 27.00 | 0.00854243 | 34.9371 | 369866.28 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9313.227 | 6159.324 | 0.505947 | 0.00022808 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8438.06 | 8438.06 | -999.0 | 28.33 | 16.85 | 0.00849865 | 12.80 | 11.23 | 0.00849865 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859034 | 35.1281 | 8011.69 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88983.626 | 58827.182 | 4.830660 | 0.00217920 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 80631.43 | 80631.43 | -999.0 | 28.34 | 16.86 | 0.00849841 | 12.80 | 11.23 | 0.00849841 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859460 | 35.1456 | 76473.57 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9104.227 | 6020.027 | 0.494424 | 0.00022296 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8249.19 | 8249.19 | -999.0 | 28.33 | 16.86 | 0.00849859 | 12.80 | 11.23 | 0.00849859 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859244 | 35.1367 | 7832.59 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 440009.892 | 440009.892 | 23.376249 | 0.01077581 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 440009.89 | 440009.89 | 23.376249 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.4476 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9313.227 | 9313.227 | 0.505947 | 0.00022808 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9313.23 | 9313.23 | 0.505947 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0897 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88983.626 | 88983.626 | 4.830660 | 0.00217920 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 88983.63 | 88983.63 | 4.830660 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.2361 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9104.227 | 9104.227 | 0.494424 | 0.00022296 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9104.23 | 9104.23 | 0.494424 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1617 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14683.19 | 14683.19 | 23.376249 | 0.01 | 0.01 | 0.00843943 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.4476 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.505947 | 0.02 | 0.02 | 0.00837071 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0897 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6783.03 | 6783.03 | 4.830660 | 0.02 | 0.02 | 0.00664225 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.2361 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.494424 | 0.02 | 0.02 | 0.00458029 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1617 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 14760.542 | 14760.542 | 1.614782 | 0.00032289 | 411.968 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 0.9032 | 0.921369 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 14760.54 | 14760.54 | 1.0000 | 1.76526982 | 1.614782 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.32285433 | 60.00 | 48.89 | 11.11 | 0.000 | 14760.54 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 14785.88 | 14785.88 | 1.76526982 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 348699.571 | 348699.571 | 16.156159 | 0.00762781 | 11572.528 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 21.3368 | 21.766198 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 348699.57 | 348699.57 | 1.0000 | 17.66181949 | 16.156159 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 7.62703469 | 60.00 | 48.89 | 11.11 | 0.000 | 348699.57 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 201017.80 | 0.00 | 349562.83 | 349562.83 | 17.66181949 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52851.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 69854.324 | 69854.324 | 2.288205 | 0.00152807 | 2719.868 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 4.2744 | 4.360381 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 69854.32 | 69854.32 | 1.0000 | 2.50145230 | 2.288205 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.52790941 | 60.00 | 48.89 | 11.11 | 0.000 | 69854.32 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 48938.09 | 0.00 | 70003.04 | 70003.04 | 2.50145230 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61044.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6280.028 | 6280.028 | 0.205410 | 0.00013738 | 244.757 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 0.3843 | 0.392006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6280.03 | 6280.03 | 1.0000 | 0.22455302 | 0.205410 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.13736178 | 60.00 | 48.89 | 11.11 | 0.000 | 6280.03 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00735091 | 21.00 | 0.00735091 | 43.1891 | 4404.86 | 0.00 | 6293.40 | 6293.40 | 0.22455302 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61086.2 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4743.011 | 4743.011 | 0.155265 | 0.00010375 | 184.754 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 0.2902 | 0.296064 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4743.01 | 4743.01 | 1.0000 | 0.16973429 | 0.155265 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.10374292 | 60.00 | 48.89 | 11.11 | 0.000 | 4743.01 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.86 | 0.00746318 | 21.00 | 0.00746318 | 43.8409 | 3325.33 | 0.00 | 4753.11 | 4753.11 | 0.16973429 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61063.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9106.447 | 9106.447 | 0.298428 | 0.00019920 | 354.471 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 0.5572 | 0.568434 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9106.45 | 9106.45 | 1.0000 | 0.32624010 | 0.298428 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.19918345 | 60.00 | 48.89 | 11.11 | 0.000 | 9106.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00762684 | 21.00 | 0.00762684 | 44.7901 | 6380.69 | 0.00 | 9125.83 | 9125.83 | 0.32624010 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61032.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3123.816 | 3123.816 | 0.130706 | 0.00006833 | 107.500 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 0.1911 | 0.194992 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3123.82 | 3123.82 | 1.0000 | 0.14288668 | 0.130706 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06832659 | 60.00 | 48.89 | 11.11 | 0.000 | 3123.82 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00691939 | 21.00 | 0.00691939 | 40.6817 | 1931.56 | 0.00 | 3131.26 | 3131.26 | 0.14288668 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.29 | 19.43 | 0.00800000 | 54974.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 169975.231 | 169975.231 | 5.581843 | 0.00371821 | 6607.435 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 10.4007 | 10.610035 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 169975.23 | 169975.23 | 1.0000 | 6.10203796 | 5.581843 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 3.71783360 | 60.00 | 48.89 | 11.11 | 0.000 | 169975.23 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00777456 | 21.00 | 0.00777456 | 45.6468 | 118978.37 | 0.00 | 170337.22 | 170337.22 | 6.10203796 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 113858.048 | 113858.048 | 3.739350 | 0.00249065 | 4425.730 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 6.9669 | 7.107141 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 113858.05 | 113858.05 | 1.0000 | 4.08783528 | 3.739350 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 2.49039390 | 60.00 | 48.89 | 11.11 | 0.000 | 113858.05 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778157 | 21.00 | 0.00778157 | 45.6875 | 79694.10 | 0.00 | 114100.53 | 114100.53 | 4.08783528 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 171359.313 | 171359.313 | 5.627405 | 0.00374849 | 6661.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 10.4854 | 10.696431 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 171359.31 | 171359.31 | 1.0000 | 6.15184613 | 5.627405 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 3.74810735 | 60.00 | 48.89 | 11.11 | 0.000 | 171359.31 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00777757 | 21.00 | 0.00777757 | 45.6643 | 119945.86 | 0.00 | 171724.25 | 171724.25 | 6.15184613 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 104241.242 | 104241.242 | 3.422831 | 0.00228028 | 4052.440 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 6.3785 | 6.506849 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 104241.24 | 104241.24 | 1.0000 | 3.74181930 | 3.422831 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 2.28004745 | 60.00 | 48.89 | 11.11 | 0.000 | 104241.24 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00774593 | 21.00 | 0.00774593 | 45.4810 | 72971.49 | 0.00 | 104463.24 | 104463.24 | 3.74181930 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21873.291 | 21873.291 | 0.718683 | 0.00047848 | 849.986 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 1.3384 | 1.365354 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21873.29 | 21873.29 | 1.0000 | 0.78566048 | 0.718683 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.47843003 | 60.00 | 48.89 | 11.11 | 0.000 | 21873.29 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780558 | 21.00 | 0.00780558 | 45.8267 | 15306.88 | 0.00 | 21919.88 | 21919.88 | 0.78566048 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60959.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14531.197 | 14531.197 | 0.477475 | 0.00031787 | 564.654 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 0.8892 | 0.907053 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14531.20 | 14531.20 | 1.0000 | 0.52197281 | 0.477475 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.31783792 | 60.00 | 48.89 | 11.11 | 0.000 | 14531.20 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780574 | 21.00 | 0.00780574 | 45.8277 | 10168.65 | 0.00 | 14562.15 | 14562.15 | 0.52197281 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60958.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22022.540 | 22022.540 | 0.723597 | 0.00048174 | 855.779 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 1.3476 | 1.374670 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22022.54 | 22022.54 | 1.0000 | 0.79103157 | 0.723597 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.48169454 | 60.00 | 48.89 | 11.11 | 0.000 | 22022.54 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780701 | 21.00 | 0.00780701 | 45.8350 | 15411.22 | 0.00 | 22069.44 | 22069.44 | 0.79103157 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60959.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13755.203 | 13755.203 | 0.451934 | 0.00030090 | 534.533 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 0.8417 | 0.858614 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13755.20 | 13755.20 | 1.0000 | 0.49405207 | 0.451934 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.30086475 | 60.00 | 48.89 | 11.11 | 0.000 | 13755.20 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00779308 | 21.00 | 0.00779308 | 45.7543 | 9626.12 | 0.00 | 13784.50 | 13784.50 | 0.49405207 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60960.7 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 181629.627 | -999.000 | 9.760683 | 0.00519458 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9975 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.760683 | 10.67032210 | 4197.9300 | 999.8980 | 63.38929406 | 15.00 | 6.67 | 8.33 | 2216644.81 | 8.1939 | 8.193899 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 181629.63 | 181629.63 | 1.0000 | 10.67032210 | 9.760683 | 27.55 | 16.32 | 0.00815378 | 48493.3 | 10.86 | 10.09 | 0.00815378 | 31471.4 | 5.19405443 | 6.67 | 15.00 | 8.33 | 21092.316 | 160537.31 | 40.80 | 0.00563111 | 18.58 | 2.03050000 | 20.8028 | 24.00 | 0.00882994 | 24.00 | 0.00882994 | 43.1322 | 120030.35 | 0.00 | 196261.78 | 186925.68 | 10.67032210 | 27.55 | 17.33 | 0.00815378 | 48493.3 | 10.38 | 10.35 | 0.00780661 | 30100.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 31616.038 | 31616.038 | 2.928205 | 0.00069160 | 713.105 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.760683 | 10.67032210 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 1.9346 | 1.973507 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31616.04 | 31616.04 | 1.0000 | 3.20109663 | 2.928205 | 2.97 | 2.38 | 0.00470728 | 14784.1 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.69153116 | 60.00 | 48.89 | 11.11 | 0.000 | 31616.04 | 0.50 | 0.00431558 | 0.50 | 2.03050000 | 69.3428 | 8.56 | 0.00559323 | 21.64 | 0.00625214 | 35.3732 | 16042.44 | 0.00 | 31753.50 | 31753.50 | 3.20109663 | 2.80 | 2.80 | 0.00470728 | 14610.7 | 12.59 | 7.91 | 0.00470728 | 24530.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1740531.151 | -999.000 | 91.845957 | 0.04977897 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8733 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 91.845957 | 100.40546870 | 4197.9300 | 999.8980 | 63.38929406 | 15.00 | 6.67 | 8.33 | 2216644.81 | 78.5210 | 78.520976 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1740531.15 | 1740531.13 | 1.0000 | 100.40546870 | 91.845957 | 27.86 | 16.37 | 0.00808700 | 48637.8 | 10.86 | 10.03 | 0.00808700 | 31302.7 | 49.77389262 | 6.67 | 15.00 | 8.33 | 198474.221 | 1542056.93 | 40.80 | 0.00563111 | 18.58 | 20.30600000 | 22.1088 | 24.00 | 0.00881952 | 24.00 | 0.00881952 | 43.0815 | 1104405.51 | 0.00 | 1879547.29 | 1798385.86 | 100.40546870 | 27.86 | 17.39 | 0.00808700 | 48637.8 | 10.30 | 10.28 | 0.00776624 | 29918.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 222060.985 | 222060.985 | 27.553787 | 0.00485759 | 5084.437 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 91.845957 | 100.40546870 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 13.5878 | 13.861283 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 222060.98 | 222060.98 | 1.0000 | 30.12164061 | 27.553787 | 5.46 | 4.30 | 0.00519407 | 18532.8 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 4.85709468 | 60.00 | 48.89 | 11.11 | 0.000 | 222060.98 | 0.50 | 0.00431558 | 0.50 | 20.30600000 | 73.6959 | 19.37 | 0.00765532 | 19.61 | 0.00732612 | 46.8939 | 249429.73 | 0.00 | 233257.76 | 233257.76 | 30.12164061 | 2.80 | 2.80 | 0.00519407 | 15830.7 | 10.43 | 7.46 | 0.00519407 | 23574.5 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 192709.206 | -999.000 | 10.551260 | 0.00551146 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9933 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.551260 | 11.53457676 | 4197.9300 | 999.8980 | 63.38929406 | 15.00 | 6.67 | 8.33 | 2216644.81 | 8.6937 | 8.693734 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 192709.21 | 192709.20 | 1.0000 | 11.53457676 | 10.551260 | 27.25 | 16.22 | 0.00815151 | 48183.2 | 10.87 | 10.10 | 0.00815151 | 31476.1 | 5.51089667 | 6.67 | 15.00 | 8.33 | 22679.560 | 170029.65 | 40.80 | 0.00563111 | 18.58 | 2.03050000 | 19.2441 | 24.00 | 0.00875664 | 24.00 | 0.00875664 | 42.7784 | 131349.03 | 0.00 | 208484.86 | 198536.06 | 11.53457676 | 27.25 | 17.23 | 0.00815151 | 48183.2 | 10.38 | 10.36 | 0.00780927 | 30108.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 21365.148 | 21365.148 | 3.165378 | 0.00046736 | 492.970 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.551260 | 11.53457676 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 1.3073 | 1.333635 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21365.15 | 21365.15 | 1.0000 | 3.46037303 | 3.165378 | 6.66 | 5.30 | 0.00552939 | 20584.9 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.46731553 | 60.00 | 48.89 | 11.11 | 0.000 | 21365.15 | 0.50 | 0.00431558 | 0.50 | 2.03050000 | 64.1472 | 17.67 | 0.00770111 | 17.60 | 0.00746132 | 54.1694 | 28471.41 | 0.00 | 22946.02 | 22946.02 | 3.46037303 | 2.80 | 2.80 | 0.00552939 | 16671.0 | 9.33 | 7.32 | 0.00552939 | 23302.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 101774.830 | -999.000 | 5.449597 | 0.00291075 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0944 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 5.449597 | 5.95746803 | 4197.9300 | 999.8980 | 63.38929406 | 15.00 | 6.67 | 8.33 | 2216644.81 | 4.5914 | 4.591391 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 101774.83 | 101774.83 | 1.0000 | 5.95746803 | 5.449597 | 28.03 | 16.52 | 0.00820592 | 49112.2 | 11.28 | 10.32 | 0.00820592 | 32028.6 | 2.91045034 | 6.67 | 15.00 | 8.33 | 9240.633 | 92534.20 | 40.13 | 0.00563007 | 18.37 | 1.20015641 | 22.0228 | 24.00 | 0.00906279 | 24.00 | 0.00906279 | 44.2540 | 60075.71 | 0.00 | 109793.81 | 105660.88 | 5.95746803 | 28.03 | 17.54 | 0.00820592 | 49112.2 | 10.64 | 10.60 | 0.00793071 | 30682.6 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 238797.328 | 238797.328 | 5.449597 | 0.00522370 | 7693.716 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 5.449597 | 5.95746803 | 4197.9300 | 999.8980 | 35.04072938 | 48.89 | 60.00 | 11.11 | 1634264.66 | 14.6119 | 14.905983 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 238797.33 | 238797.33 | 1.0000 | 5.95746803 | 5.449597 | 0.11 | 0.11 | 0.00431558 | 10904.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 5.22316531 | 60.00 | 48.89 | 11.11 | 0.000 | 238797.33 | 0.50 | 0.00431558 | 0.50 | 1.20015641 | 22.0228 | 0.00 | 0.00431558 | 25.34 | 0.00431558 | 19.6025 | 0.00 | 0.00 | 188488.92 | 188488.92 | 5.95746803 | 12.80 | 7.56 | 0.00431558 | 23757.7 | 44.04 | 19.66 | 0.00431558 | 55396.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 440009.892 | 287929.324 | 23.376249 | 0.01077581 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6415 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 400147.82 | 400134.82 | 0.9094 | -999.0 | -999.0 | 28.73 | 16.99 | 0.00850024 | 50584.1 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 400147.82 | 40.80 | 0.00563111 | 18.58 | 0.33839277 | -999.0000 | 27.00 | 0.00854243 | 27.00 | 0.00854243 | 34.9371 | 369866.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9313.227 | 6159.324 | 0.505947 | 0.00022808 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6386 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8438.06 | 8438.06 | 0.9060 | -999.0 | -999.0 | 28.33 | 16.85 | 0.00849865 | 50167.3 | 12.80 | 11.23 | 0.00849865 | 34318.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8438.06 | 36.28 | 0.00562409 | 17.15 | 0.01563234 | -999.0000 | 27.00 | 0.00859034 | 27.00 | 0.00859034 | 35.1281 | 8011.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 88983.626 | 58827.182 | 4.830660 | 0.00217920 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6381 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 80631.43 | 80631.43 | 0.9061 | -999.0 | -999.0 | 28.34 | 16.86 | 0.00849841 | 50180.5 | 12.80 | 11.23 | 0.00849841 | 34318.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80631.43 | 36.28 | 0.00562409 | 17.15 | 0.15632344 | -999.0000 | 27.00 | 0.00859460 | 27.00 | 0.00859460 | 35.1456 | 76473.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9104.227 | 6020.027 | 0.494424 | 0.00022296 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6385 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8249.19 | 8249.19 | 0.9061 | -999.0 | -999.0 | 28.33 | 16.86 | 0.00849859 | 50173.8 | 12.80 | 11.23 | 0.00849859 | 34318.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8249.19 | 36.28 | 0.00562409 | 17.15 | 0.01563234 | -999.0000 | 27.00 | 0.00859244 | 27.00 | 0.00859244 | 35.1367 | 7832.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 440009.892 | 440009.892 | 23.376249 | 0.01077581 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 440009.89 | 440009.89 | 1.0000 | 25.55477988 | 23.376249 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 440009.89 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.4476 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9313.227 | 9313.227 | 0.505947 | 0.00022808 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9313.23 | 9313.23 | 1.0000 | 0.55309824 | 0.505947 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9313.23 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0897 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88983.626 | 88983.626 | 4.830660 | 0.00217920 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 88983.63 | 88983.63 | 1.0000 | 5.28084944 | 4.830660 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88983.63 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.2361 | 0.00 | 0.00672007 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9104.227 | 9104.227 | 0.494424 | 0.00022296 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9104.23 | 9104.23 | 1.0000 | 0.54050183 | 0.494424 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9104.23 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.1617 | 0.00 | 0.00458893 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 23.376249 | 25.55477988 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14683.19 | 14683.19 | 1.0000 | 25.55477988 | 23.376249 | 0.01 | 0.01 | 0.00843943 | 21113.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14683.19 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.4476 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.505947 | 0.55309824 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.55309824 | 0.505947 | 0.02 | 0.02 | 0.00837071 | 20950.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0897 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.830660 | 5.28084944 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6783.03 | 6783.03 | 1.0000 | 5.28084944 | 4.830660 | 0.02 | 0.02 | 0.00664225 | 16628.3 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6783.03 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.2361 | 0.00 | 0.00672007 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.494424 | 0.54050183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.54050183 | 0.494424 | 0.02 | 0.02 | 0.00458029 | 11471.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.1617 | 0.00 | 0.00458893 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.76 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 91.85 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.55 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.45 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 23.38 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2380.33 | 1375.17 | 453.50 |
CORE_BOTTOM | 2182.00 | 792.83 | 30.67 |
CORE_MID | 1596.50 | 2207.00 | 170.17 |
CORE_TOP | 1627.33 | 2864.67 | 302.17 |
PERIMETER_BOT_ZN_3 | 2071.00 | 2327.33 | 125.67 |
PERIMETER_BOT_ZN_2 | 2772.00 | 1804.67 | 251.50 |
PERIMETER_BOT_ZN_1 | 3082.00 | 1368.83 | 247.50 |
PERIMETER_BOT_ZN_4 | 3730.83 | 963.17 | 444.00 |
PERIMETER_MID_ZN_3 | 2022.50 | 3064.67 | 396.67 |
PERIMETER_MID_ZN_2 | 2235.33 | 2067.00 | 381.33 |
PERIMETER_MID_ZN_1 | 2920.83 | 1755.17 | 333.33 |
PERIMETER_MID_ZN_4 | 2718.50 | 2283.33 | 365.00 |
PERIMETER_TOP_ZN_3 | 2557.00 | 3240.83 | 902.67 |
PERIMETER_TOP_ZN_2 | 2901.00 | 2604.00 | 641.00 |
PERIMETER_TOP_ZN_1 | 2998.50 | 2080.33 | 528.50 |
PERIMETER_TOP_ZN_4 | 2911.33 | 2580.17 | 656.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1176.17 | 1176.17 |
DATACENTER_MID_ZN_6 | 5938.50 | 461.67 | 461.67 |
DATACENTER_TOP_ZN_6 | 5764.00 | 549.50 | 537.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5706.00 | 5706.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5907.17 | 5743.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 75.33 | 0.00 | 8.00 |
CORE_BOTTOM | 0.00 | 5.50 | 0.00 | 0.33 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 42.67 | 0.00 | 23.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 92.33 | 0.00 | 75.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 132.17 | 0.00 | 105.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 323.50 | 0.00 | 122.67 |
PERIMETER_MID_ZN_3 | 0.33 | 33.50 | 0.00 | 20.67 |
PERIMETER_MID_ZN_2 | 0.33 | 100.83 | 0.00 | 77.33 |
PERIMETER_MID_ZN_1 | 0.00 | 163.83 | 0.00 | 147.00 |
PERIMETER_MID_ZN_4 | 0.00 | 126.33 | 0.00 | 54.00 |
PERIMETER_TOP_ZN_3 | 5.00 | 62.67 | 0.00 | 35.50 |
PERIMETER_TOP_ZN_2 | 3.50 | 120.67 | 0.00 | 78.33 |
PERIMETER_TOP_ZN_1 | 1.83 | 109.50 | 0.00 | 75.00 |
PERIMETER_TOP_ZN_4 | 1.83 | 140.67 | 0.00 | 56.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 736.17 | 0.00 | 593.17 |
DATACENTER_MID_ZN_6 | 0.00 | 624.50 | 0.00 | 508.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 522.00 | 0.00 | 422.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1032.50 | 0.00 | 795.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 5.33 | 1671.50 | 0.00 | 1137.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 1.215 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.844 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.619 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.576 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 0.806 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 1.210 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 1.409 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 1.765 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 0.684 | 0.081 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 1.086 | 0.091 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 1.265 | 0.082 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 1.088 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 0.668 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 1.083 | 0.105 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 1.288 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 1.067 | 0.105 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 26.987 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.91 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.93 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.46 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1026.00 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 51519973.11 | 0.00 | 51519973.11 | 0.00 | 51519973.11 | 37848132.68 | 3873.31 | 2333.26 | 2553.42 | 342.21 |
CORE_BOTTOM | 36996632.89 | 0.00 | 36996632.89 | 0.00 | 36996632.89 | 33990283.35 | 5580.24 | 13.49 | 3166.27 | 561.63 |
CORE_MID | 0.26E+09 | 0.00 | 0.26E+09 | 0.00 | 0.26E+09 | 0.34E+09 | 6168.67 | 127.16 | 2464.18 | 146.89 |
CORE_TOP | 23951981.43 | 0.00 | 23951981.43 | 0.00 | 23951981.43 | 33990283.35 | 6216.17 | 234.92 | 2308.91 | 183.42 |
PERIMETER_BOT_ZN_3 | 4435182.98 | 0.00 | 4435182.98 | 347995.63 | 4783178.61 | 4267819.30 | 3905.96 | 54.35 | 4799.69 | 561.63 |
PERIMETER_BOT_ZN_2 | 4163473.22 | 0.00 | 4163473.22 | 231996.93 | 4395470.14 | 2750345.05 | 3728.86 | 31.74 | 4999.39 | 561.63 |
PERIMETER_BOT_ZN_1 | 7462928.53 | 0.00 | 7462928.53 | 347995.63 | 7810924.16 | 4267912.63 | 3671.83 | 28.16 | 5060.01 | 561.63 |
PERIMETER_BOT_ZN_4 | 6115786.94 | 0.00 | 6115786.94 | 231996.93 | 6347783.87 | 2750345.05 | 3498.12 | 13.18 | 5248.71 | 561.63 |
PERIMETER_MID_ZN_3 | 35355676.63 | 0.00 | 35355676.63 | 816132.14 | 36171808.76 | 42678193.03 | 4533.98 | 128.81 | 4097.21 | 146.89 |
PERIMETER_MID_ZN_2 | 36266360.43 | 0.00 | 36266360.43 | 544087.72 | 36810448.15 | 27503450.52 | 4342.13 | 112.11 | 4305.76 | 993.81 |
PERIMETER_MID_ZN_1 | 64549106.41 | 0.00 | 64549106.41 | 816132.14 | 65365238.54 | 42679126.28 | 4043.31 | 140.18 | 4576.51 | 146.89 |
PERIMETER_MID_ZN_4 | 36018689.17 | 0.00 | 36018689.17 | 544087.72 | 36562776.89 | 27503450.52 | 4131.20 | 166.66 | 4462.14 | 146.89 |
PERIMETER_TOP_ZN_3 | 3472101.94 | 0.00 | 3472101.94 | 1013296.28 | 4485398.22 | 4267819.30 | 4263.94 | 163.31 | 4332.76 | 183.42 |
PERIMETER_TOP_ZN_2 | 3577013.51 | 0.00 | 3577013.51 | 675530.39 | 4252543.90 | 2750345.05 | 4053.27 | 185.50 | 4521.23 | 183.42 |
PERIMETER_TOP_ZN_1 | 6586122.67 | 0.00 | 6586122.67 | 1013296.28 | 7599418.95 | 4267912.63 | 4060.51 | 139.27 | 4560.22 | 183.42 |
PERIMETER_TOP_ZN_4 | 3548042.81 | 0.00 | 3548042.81 | 675530.39 | 4223573.20 | 2750345.05 | 4038.79 | 105.10 | 4616.11 | 183.42 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.46E+09 | 0.00 | 0.46E+09 | 0.00 | 0.46E+09 | 10671554.30 | 693.42 | 1549.75 | 6516.83 | 2480.71 |
Total Facility | 0.49E+10 | 0.00 | 0.49E+10 | 31742035.64 | 0.50E+10 | 0.50E+10 | 7251.94 | 4359.17 | 8063.98 | 3328.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.2421 | 0.0000 | 2.2421 | 0.0000 | 2.2421 | 1.2002 | 1307.71 | 2331.53 | 2303.75 |
CORE_BOTTOM | 1.5738 | 0.0000 | 1.5738 | 0.0000 | 1.5738 | 1.0778 | 3283.77 | 9.64 | 2649.60 |
CORE_MID | 11.5386 | 0.0000 | 11.5386 | 0.0000 | 11.5386 | 10.7782 | 3492.76 | 127.16 | 2323.09 |
CORE_TOP | 1.0748 | 0.0000 | 1.0748 | 0.0000 | 1.0748 | 1.0778 | 3540.55 | 234.71 | 2167.74 |
PERIMETER_BOT_ZN_3 | 0.1886 | 0.0000 | 0.1886 | 0.0081 | 0.1968 | 0.1353 | 1602.53 | 49.59 | 4290.87 |
PERIMETER_BOT_ZN_2 | 0.1826 | 0.0000 | 0.1826 | 0.0054 | 0.1880 | 0.0872 | 1425.73 | 27.32 | 4489.95 |
PERIMETER_BOT_ZN_1 | 0.3300 | 0.0000 | 0.3300 | 0.0081 | 0.3381 | 0.1353 | 1367.79 | 23.65 | 4551.56 |
PERIMETER_BOT_ZN_4 | 0.2662 | 0.0000 | 0.2662 | 0.0054 | 0.2716 | 0.0872 | 1196.41 | 9.07 | 4737.52 |
PERIMETER_MID_ZN_3 | 1.6008 | 0.0000 | 1.6008 | 0.0191 | 1.6198 | 1.3533 | 1858.37 | 128.81 | 3955.82 |
PERIMETER_MID_ZN_2 | 1.6375 | 0.0000 | 1.6375 | 0.0137 | 1.6512 | 0.8721 | 1445.30 | 109.03 | 3479.67 |
PERIMETER_MID_ZN_1 | 2.9635 | 0.0000 | 2.9635 | 0.0191 | 2.9826 | 1.3533 | 1367.40 | 140.18 | 4435.42 |
PERIMETER_MID_ZN_4 | 1.6407 | 0.0000 | 1.6407 | 0.0127 | 1.6534 | 0.8721 | 1455.33 | 166.66 | 4321.01 |
PERIMETER_TOP_ZN_3 | 0.1565 | 0.0000 | 0.1565 | 0.0237 | 0.1802 | 0.1353 | 1590.82 | 162.93 | 4189.24 |
PERIMETER_TOP_ZN_2 | 0.1633 | 0.0000 | 0.1633 | 0.0158 | 0.1791 | 0.0872 | 1379.53 | 185.21 | 4378.25 |
PERIMETER_TOP_ZN_1 | 0.3020 | 0.0000 | 0.3020 | 0.0237 | 0.3257 | 0.1353 | 1385.46 | 138.86 | 4418.67 |
PERIMETER_TOP_ZN_4 | 0.1610 | 0.0000 | 0.1610 | 0.0158 | 0.1768 | 0.0872 | 1363.93 | 104.74 | 4474.33 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.8583 | 0.0000 | 13.8583 | 0.0000 | 13.8583 | 0.3384 | 357.13 | 1549.75 | 4036.12 |
Total Facility | 215.4752 | 0.0000 | 215.4752 | 0.7512 | 216.2264 | 158.4706 | 4434.94 | 4351.58 | 5582.61 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 70717306.44 | 0.00 | 70717306.44 | 48026705.38 | 3364.39 | 4.65 | 5390.96 | 561.63 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 3922.66 | 4.94 | 4832.40 | 146.89 |
VAV_TOP WITH REHEAT | 49159668.77 | 0.00 | 49159668.77 | 48026705.38 | 4001.15 | 2.01 | 4756.84 | 183.42 |
CAV_BAS | 61570159.50 | 0.00 | 61570159.50 | 37848132.68 | 3852.36 | 2.82 | 4904.82 | 342.21 |
AIRLOOP DATACENTER BASEMENT | 0.55E+09 | 0.00 | 0.55E+09 | 10671554.30 | 693.42 | 0.00 | 8066.58 | 2480.71 |
AIRLOOP DATACENTER BOT | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2919517.21 | 0.00 | 2919517.21 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.0369 | 0.0000 | 3.0369 | 1.5229 | 1091.15 | 1.69 | 4850.15 |
VAV_MID WITH REHEAT | 23.1887 | 0.0000 | 23.1887 | 15.2292 | 1247.73 | 4.76 | 4690.51 |
VAV_TOP WITH REHEAT | 2.2200 | 0.0000 | 2.2200 | 1.5229 | 1325.87 | 2.01 | 4615.12 |
CAV_BAS | 2.6795 | 0.0000 | 2.6795 | 1.2002 | 1305.54 | 0.28 | 4637.18 |
AIRLOOP DATACENTER BASEMENT | 16.5617 | 0.0000 | 16.5617 | 0.3384 | 357.13 | 0.00 | 5585.87 |
AIRLOOP DATACENTER BOT | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1365 | 0.0000 | 0.1365 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 168.61 | 3053.10 | 0.00 | 0.00 | 0.00 | 2202.09 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 567.90 | 2192.32 | 0.00 | 0.00 | 0.00 | 2133.44 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 114.53 | 2407.53 | 0.00 | 0.00 | 0.00 | 2376.09 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2331.42 | 2655.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1549.75 | 6516.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.3967 | 5.3053 | 0.0000 | 0.0000 | 0.0000 | 1.9986 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 23.9678 | 39.4151 | 0.0000 | 0.0000 | 0.0000 | 20.4268 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.3275 | 3.6735 | 0.0000 | 0.0000 | 0.0000 | 1.9999 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.4345 | 5.4390 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4046 | 24.2318 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1869 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1187 |
Fields with Defaults | 3885 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27493.06 | 298210.93 | 21-JAN-04:00 | 1840073.21 | 25-AUG-15:10 |
Electricity:Building | 16489.09 | 215843.22 | 07-MAY-17:20 | 958209.73 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 547.21 | 14055.89 | 01-JAN-00:10 | 24238.09 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16489.09 | 215843.22 | 07-MAY-17:20 | 958209.73 | 01-DEC-16:30 |
InteriorLights:Electricity | 1812.70 | 8587.06 | 02-APR-17:20 | 179838.04 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 122.81 | 598.35 | 01-JAN-00:10 | 10780.55 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1812.70 | 8587.06 | 02-APR-17:20 | 179838.04 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity | 1812.70 | 8587.06 | 02-APR-17:20 | 179838.04 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.81 | 598.35 | 01-JAN-00:10 | 10780.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1812.70 | 8587.06 | 02-APR-17:20 | 179838.04 | 28-NOV-16:30 |
Electricity:Zone:CORE_BOTTOM | 399.91 | 4990.59 | 01-JAN-00:10 | 26888.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3999.04 | 49905.77 | 01-JAN-00:10 | 268882.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1102.91 | 5373.60 | 01-JAN-00:10 | 96816.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1102.91 | 5373.60 | 01-JAN-00:10 | 96816.88 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 399.90 | 4990.58 | 01-JAN-00:10 | 26888.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 44.31 | 591.30 | 02-APR-17:10 | 3376.18 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.94 | 32.13 | 01-JAN-09:30 | 1215.63 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.94 | 32.13 | 01-JAN-09:30 | 1215.63 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.49 | 381.06 | 02-APR-17:10 | 2175.74 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.05 | 20.71 | 01-JAN-07:50 | 783.40 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.05 | 20.71 | 01-JAN-07:50 | 783.40 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 44.18 | 591.31 | 12-MAR-17:10 | 3376.24 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.81 | 32.13 | 01-JAN-07:50 | 1215.66 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.81 | 32.13 | 01-JAN-07:50 | 1215.66 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.52 | 381.06 | 12-MAR-17:10 | 2175.73 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.09 | 20.71 | 01-JAN-09:30 | 783.40 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.09 | 20.71 | 01-JAN-09:30 | 783.40 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 442.87 | 5913.03 | 02-APR-17:10 | 33761.84 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 79.21 | 321.32 | 01-JAN-09:30 | 12156.33 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 79.21 | 321.32 | 01-JAN-09:30 | 12156.33 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 284.81 | 3810.58 | 02-APR-17:10 | 21757.42 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 50.46 | 207.07 | 01-JAN-07:50 | 7834.00 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 50.46 | 207.07 | 01-JAN-07:50 | 7834.00 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 441.72 | 5913.12 | 12-MAR-17:10 | 33762.44 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 78.06 | 321.33 | 01-JAN-07:50 | 12156.59 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 78.06 | 321.33 | 01-JAN-07:50 | 12156.59 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 285.14 | 3810.56 | 12-MAR-17:10 | 21757.33 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 50.79 | 207.07 | 01-JAN-09:20 | 7834.00 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 50.79 | 207.07 | 01-JAN-09:20 | 7834.00 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 44.29 | 591.30 | 02-APR-17:10 | 3376.18 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.92 | 32.13 | 01-JAN-09:30 | 1215.63 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.92 | 32.13 | 01-JAN-09:30 | 1215.63 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.48 | 381.06 | 02-APR-17:10 | 2175.74 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.05 | 20.71 | 01-JAN-07:50 | 783.40 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.05 | 20.71 | 01-JAN-07:50 | 783.40 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 44.17 | 591.31 | 12-MAR-17:10 | 3376.24 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.81 | 32.13 | 01-JAN-07:50 | 1215.66 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.81 | 32.13 | 01-JAN-07:50 | 1215.66 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.51 | 381.06 | 12-MAR-17:10 | 2175.73 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.08 | 20.71 | 01-JAN-09:20 | 783.40 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.08 | 20.71 | 01-JAN-09:20 | 783.40 | 28-NOV-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7529.67 | 95077.00 | 01-JAN-00:10 | 382672.17 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 34.81 | 168.86 | 01-JAN-00:10 | 3039.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 34.81 | 168.86 | 01-JAN-00:10 | 3039.65 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.66 | 1957.22 | 01-JAN-00:10 | 7949.46 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1556.56 | 19572.19 | 01-JAN-00:10 | 79494.63 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 17.76 | 86.14 | 01-JAN-00:10 | 1550.41 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 17.76 | 86.14 | 01-JAN-00:10 | 1550.41 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.66 | 1957.22 | 01-JAN-00:10 | 7949.46 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3366.99 | 3702.12 | 01-JAN-05:30 | 376138.21 | 05-SEP-07:40 |
HeatRejection:Electricity | 1144.14 | 288.14 | 01-JAN-08:00 | 75058.17 | 10-APR-14:20 |
General:HeatRejection:Electricity | 1144.14 | 288.14 | 01-JAN-08:00 | 75058.17 | 10-APR-14:20 |
ElectricityProduced:Facility | 601.28 | -0.00 | 22-JAN-17:40 | 88482.24 | 12-MAY-12:30 |
ElectricityProduced:Plant | 601.28 | -0.00 | 22-JAN-17:40 | 88482.24 | 12-MAY-12:30 |
Photovoltaic:ElectricityProduced | 627.21 | 0.00 | 01-JAN-00:10 | 92157.80 | 12-MAY-12:30 |
PowerConversion:ElectricityProduced | -25.93 | -3675.56 | 12-MAY-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 6223.11 | 50785.44 | 21-JAN-04:00 | 521922.36 | 25-AUG-15:10 |
ExteriorEquipment:Electricity | 1203.73 | 17814.45 | 01-JAN-00:10 | 73702.22 | 20-JAN-08:40 |
Transformer:ExteriorEquipment:Electricity | 54.39 | 979.82 | 01-JAN-00:10 | 3377.37 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
ElectricityPurchased:Plant | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
Cogeneration:ElectricityPurchased | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
ElectricityNet:Plant | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
Cogeneration:ElectricityNet | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
General:Cogeneration:ElectricityNet | 26891.78 | 278159.15 | 22-JAN-10:10 | 1784223.79 | 25-AUG-15:10 |
Fans:Electricity | 2640.26 | 45084.59 | 04-JAN-00:10 | 254980.94 | 19-JUN-15:00 |
General:Fans:Electricity | 2640.26 | 45084.59 | 04-JAN-00:10 | 254980.94 | 19-JUN-15:00 |
ExteriorLights:Electricity | 264.53 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 264.53 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 3594.84 | 2351.63 | 02-JAN-07:10 | 415440.83 | 11-AUG-15:50 |
General:Cooling:Electricity | 3594.84 | 2351.63 | 02-JAN-07:10 | 415440.83 | 11-AUG-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1609.27 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-13:30 |
General:Humidifier:Electricity | 1609.27 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-13:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 547.20 | 3385.36 | 01-JAN-00:10 | 46806.67 | 02-NOV-14:30 |
General:Pumps:Electricity | 547.20 | 3385.36 | 01-JAN-00:10 | 46806.67 | 02-NOV-14:30 |
WIRED_LTG_ELECTRICITY | 50.94 | 0.00 | 01-JAN-00:10 | 5053.45 | 28-NOV-16:40 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 721.77 | 7280.88 | 18-MAR-16:10 | 587597.26 | 06-DEC-07:10 |
NaturalGas:Plant | 721.77 | 7280.88 | 18-MAR-16:10 | 587597.26 | 06-DEC-07:10 |
Heating:NaturalGas | 74.72 | 0.00 | 01-JAN-00:10 | 557558.16 | 06-DEC-07:10 |
Boiler:Heating:NaturalGas | 74.72 | 0.00 | 01-JAN-00:10 | 557558.16 | 06-DEC-07:10 |
WaterSystems:NaturalGas | 647.05 | 7280.88 | 02-JAN-05:20 | 76828.17 | 23-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 647.05 | 7280.88 | 02-JAN-05:20 | 76828.17 | 23-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 20078.72 | 8203.95 | 02-JAN-07:10 | 2415494.92 | 28-AUG-12:10 |
PlantLoopCoolingDemand:HVAC | 20078.72 | 8203.95 | 02-JAN-07:10 | 2415494.92 | 28-AUG-12:10 |
CoolingCoils:PlantLoopCoolingDemand | 20078.72 | 8203.95 | 02-JAN-07:10 | 2415494.92 | 28-AUG-12:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 15685.67 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
Water:HVAC | 598.65 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
Humidifier:Water | 598.65 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
General:Humidifier:Water | 598.65 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
MainsWater:Facility | 15685.67 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
MainsWater:HVAC | 598.65 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
Humidifier:MainsWater | 598.65 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
General:Humidifier:MainsWater | 598.65 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
Water:Plant | 15087.03 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 15087.03 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 12806.86 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-15:20 |
General:HeatRejection:Water | 12806.86 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-15:20 |
HeatRejection:MainsWater | 12806.86 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-15:20 |
General:HeatRejection:MainsWater | 12806.86 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-15:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 77061.76 | 100326.80 | 01-JAN-05:30 | 9343296.04 | 28-AUG-12:30 |
EnergyTransfer:Building | 20448.37 | 90828.10 | 02-JAN-02:50 | 1602142.99 | 14-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 666.89 | 0.00 | 01-JAN-00:10 | 74353.63 | 26-DEC-06:10 |
Heating:EnergyTransfer | 43.26 | 0.00 | 01-JAN-17:10 | 271879.11 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.40 | 0.00 | 01-JAN-00:10 | 28152.16 | 26-AUG-16:10 |
General:Heating:EnergyTransfer | 43.26 | 0.00 | 01-JAN-17:10 | 271879.11 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.40 | 0.00 | 01-JAN-00:10 | 28152.16 | 26-AUG-16:10 |
Cooling:EnergyTransfer | 20405.12 | 89864.21 | 01-JAN-08:50 | 1602142.99 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 662.49 | 0.00 | 01-JAN-00:10 | 74353.63 | 26-DEC-06:10 |
General:Cooling:EnergyTransfer | 20405.12 | 89864.21 | 01-JAN-08:50 | 1602142.99 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 662.49 | 0.00 | 01-JAN-00:10 | 74353.63 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 650.30 | 0.00 | 01-JAN-00:10 | 59315.89 | 14-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 650.30 | 0.00 | 01-JAN-00:10 | 59315.89 | 14-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 650.30 | 0.00 | 01-JAN-00:10 | 59315.89 | 14-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 4700.06 | 0.00 | 01-JAN-00:10 | 399973.77 | 11-SEP-09:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4700.06 | 0.00 | 01-JAN-00:10 | 399973.77 | 11-SEP-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4700.06 | 0.00 | 01-JAN-00:10 | 399973.77 | 11-SEP-09:20 |
EnergyTransfer:Zone:CORE_TOP | 459.86 | 0.00 | 01-JAN-00:10 | 47585.47 | 28-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.41 | 0.00 | 01-JAN-00:10 | 41318.37 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.41 | 0.00 | 01-JAN-00:10 | 41318.37 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 459.44 | 0.00 | 01-JAN-00:10 | 47585.47 | 28-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 459.44 | 0.00 | 01-JAN-00:10 | 47585.47 | 28-AUG-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 94.71 | 0.00 | 01-JAN-00:10 | 11763.10 | 28-AUG-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 94.71 | 0.00 | 01-JAN-00:10 | 11763.10 | 28-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 94.71 | 0.00 | 01-JAN-00:10 | 11763.10 | 28-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 85.88 | 0.00 | 01-JAN-00:10 | 13561.33 | 19-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 196.44 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 196.44 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 85.88 | 0.00 | 01-JAN-00:10 | 13561.33 | 19-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 85.88 | 0.00 | 01-JAN-00:10 | 13561.33 | 19-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 141.81 | 0.00 | 01-JAN-00:10 | 17356.46 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 141.81 | 0.00 | 01-JAN-00:10 | 17356.46 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 141.81 | 0.00 | 01-JAN-00:10 | 17356.46 | 02-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 127.50 | 0.00 | 01-JAN-00:10 | 18597.91 | 25-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 127.50 | 0.00 | 01-JAN-00:10 | 18597.91 | 25-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 127.50 | 0.00 | 01-JAN-00:10 | 18597.91 | 25-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 755.05 | 0.00 | 01-JAN-00:10 | 111133.59 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.58 | 0.00 | 01-JAN-00:10 | 67985.08 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.58 | 0.00 | 01-JAN-00:10 | 67985.08 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 751.47 | 0.00 | 01-JAN-00:10 | 111133.59 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 751.47 | 0.00 | 01-JAN-00:10 | 111133.59 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 780.21 | 0.00 | 01-JAN-00:10 | 140181.11 | 19-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.28 | 0.00 | 01-JAN-00:10 | 40185.05 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.28 | 0.00 | 01-JAN-00:10 | 40185.05 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 778.93 | 0.00 | 01-JAN-00:10 | 140181.11 | 19-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 778.93 | 0.00 | 01-JAN-00:10 | 140181.11 | 19-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1274.57 | 0.00 | 01-JAN-00:10 | 174717.63 | 01-NOV-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.50 | 0.00 | 01-JAN-00:10 | 37493.65 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.50 | 0.00 | 01-JAN-00:10 | 37493.65 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1274.07 | 0.00 | 01-JAN-00:10 | 174717.63 | 01-NOV-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1274.07 | 0.00 | 01-JAN-00:10 | 174717.63 | 01-NOV-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 823.69 | 0.00 | 01-JAN-00:10 | 153096.17 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.64 | 0.00 | 01-JAN-00:10 | 26803.01 | 18-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.64 | 0.00 | 01-JAN-00:10 | 26803.01 | 18-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 823.05 | 0.00 | 01-JAN-00:10 | 153096.17 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 823.05 | 0.00 | 01-JAN-00:10 | 153096.17 | 29-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.11 | 0.00 | 01-JAN-00:10 | 13738.24 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.10 | 0.00 | 01-JAN-00:10 | 13738.24 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.10 | 0.00 | 01-JAN-00:10 | 13738.24 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 77.01 | 0.00 | 01-JAN-00:10 | 12581.96 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 77.01 | 0.00 | 01-JAN-00:10 | 12581.96 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 82.12 | 0.00 | 01-JAN-00:10 | 14268.08 | 19-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.23 | 0.00 | 01-JAN-00:10 | 8742.39 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.23 | 0.00 | 01-JAN-00:10 | 8742.39 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 80.89 | 0.00 | 01-JAN-00:10 | 14268.08 | 19-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 80.89 | 0.00 | 01-JAN-00:10 | 14268.08 | 19-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 126.88 | 0.00 | 01-JAN-00:10 | 19123.63 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.98 | 0.00 | 01-JAN-00:10 | 9354.25 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.98 | 0.00 | 01-JAN-00:10 | 9354.25 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 125.89 | 0.00 | 01-JAN-00:10 | 19123.63 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 125.89 | 0.00 | 01-JAN-00:10 | 19123.63 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 84.13 | 0.00 | 01-JAN-00:10 | 16274.45 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.74 | 0.00 | 01-JAN-00:10 | 6861.05 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.74 | 0.00 | 01-JAN-00:10 | 6861.05 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 83.39 | 0.00 | 01-JAN-00:10 | 16274.45 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 83.39 | 0.00 | 01-JAN-00:10 | 16274.45 | 29-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 88.84 | 0.00 | 01-JAN-00:10 | 14885.27 | 28-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.12 | 0.00 | 01-JAN-00:10 | 3260.65 | 17-DEC-10:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.12 | 0.00 | 01-JAN-00:10 | 3260.65 | 17-DEC-10:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 87.72 | 0.00 | 01-JAN-00:10 | 14885.27 | 28-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 87.72 | 0.00 | 01-JAN-00:10 | 14885.27 | 28-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 612.54 | 0.00 | 01-JAN-00:10 | 90379.78 | 19-JUN-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.17 | 0.00 | 01-JAN-00:10 | 41859.26 | 02-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.17 | 0.00 | 01-JAN-00:10 | 41859.26 | 02-JAN-11:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 597.37 | 0.00 | 01-JAN-00:10 | 90379.78 | 19-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 597.37 | 0.00 | 01-JAN-00:10 | 90379.78 | 19-JUN-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 116.75 | 0.00 | 01-JAN-00:10 | 23511.31 | 28-JUN-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.94 | 0.00 | 01-JAN-00:10 | 14312.50 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.94 | 0.00 | 01-JAN-00:10 | 14312.50 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 106.81 | 0.00 | 01-JAN-00:10 | 23511.31 | 28-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 106.81 | 0.00 | 01-JAN-00:10 | 23511.31 | 28-JUN-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.61 | 1164.82 | 21-JAN-08:00 | 7838.77 | 28-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.61 | 1164.82 | 21-JAN-08:00 | 7838.77 | 28-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.61 | 1164.82 | 21-JAN-08:00 | 7838.77 | 28-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1284.05 | 8.00 | 02-JAN-02:30 | 73747.11 | 28-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.08 | 0.00 | 01-JAN-00:10 | 2756.35 | 01-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.08 | 0.00 | 01-JAN-00:10 | 2756.35 | 01-JAN-08:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1283.97 | 0.00 | 01-JAN-02:10 | 73747.11 | 28-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1283.97 | 0.00 | 01-JAN-02:10 | 73747.11 | 28-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 123.79 | 5.20 | 22-JAN-04:30 | 7479.12 | 26-APR-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.08 | 0.00 | 01-JAN-16:40 | 572.62 | 01-JAN-01:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.08 | 0.00 | 01-JAN-16:40 | 572.62 | 01-JAN-01:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 123.71 | 0.00 | 01-JAN-00:10 | 7479.12 | 26-APR-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 123.71 | 0.00 | 01-JAN-00:10 | 7479.12 | 26-APR-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7148.03 | 87898.53 | 27-MAY-16:20 | 382716.69 | 27-AUG-02:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7148.03 | 87898.53 | 27-MAY-16:20 | 382716.69 | 27-AUG-02:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7148.03 | 87898.53 | 27-MAY-16:20 | 382716.69 | 27-AUG-02:30 |
PlantLoopHeatingDemand:Facility | 390.74 | 0.00 | 01-JAN-00:10 | 392734.43 | 06-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 323.62 | 0.00 | 01-JAN-00:10 | 42570.26 | 23-JAN-12:50 |
WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42570.26 | 23-JAN-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42570.26 | 23-JAN-12:50 |
EnergyTransfer:HVAC | 18226.65 | 7219.55 | 01-JAN-08:10 | 2245618.27 | 28-AUG-12:10 |
HeatingCoils:EnergyTransfer | 67.12 | 0.00 | 01-JAN-00:10 | 379342.40 | 06-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 67.12 | 0.00 | 01-JAN-00:10 | 379342.40 | 06-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 67.12 | 0.00 | 01-JAN-00:10 | 379342.40 | 06-DEC-07:10 |
CoolingCoils:EnergyTransfer | 18159.53 | 5852.32 | 02-JAN-07:10 | 2245618.27 | 28-AUG-12:10 |
EnergyTransfer:Plant | 38386.74 | 0.00 | 01-JAN-00:10 | 5993374.59 | 05-SEP-07:40 |
LoopToLoop:EnergyTransfer | 12209.73 | 0.00 | 01-JAN-00:10 | 1904010.02 | 05-SEP-07:40 |
WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42570.26 | 23-JAN-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42570.26 | 23-JAN-12:50 |
Boilers:EnergyTransfer | 66.41 | 0.00 | 01-JAN-00:10 | 482277.15 | 06-DEC-07:10 |
Chillers:EnergyTransfer | 12055.67 | 0.00 | 01-JAN-00:10 | 1905258.24 | 05-SEP-07:50 |
HeatRejection:EnergyTransfer | 13731.32 | 0.00 | 01-JAN-00:10 | 2165741.14 | 05-SEP-07:50 |
General:HeatRejection:EnergyTransfer | 13731.32 | 0.00 | 01-JAN-00:10 | 2165741.14 | 05-SEP-07:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.398 | -662.488 | 0.000 | 0.000 | 92.686 | 122.809 | 424.397 | 0.000 | 0.000 | 0.000 | 18.198 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -650.297 | 0.000 | 0.000 | 83.407 | 110.291 | 289.614 | 0.000 | 0.000 | 0.000 | 166.985 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4700.059 | 0.000 | 0.000 | 836.112 | 1102.914 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.010 | 0.000 | 0.000 | 0.000 | 0.000 | -135.094 |
CORE_TOP | 0.000 | 0.000 | 0.414 | -459.439 | 0.000 | 0.000 | 84.641 | 110.291 | 289.613 | 0.000 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -25.520 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -94.713 | 0.000 | 0.000 | 10.536 | 7.940 | 36.365 | 42.968 | 0.000 | 0.788 | 38.483 | 0.000 | -40.355 | 0.000 | -2.012 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -85.876 | 0.000 | 0.000 | 6.766 | 5.052 | 23.435 | 76.347 | 0.000 | 0.522 | 0.001 | 0.000 | -24.612 | 0.000 | -1.351 | -0.282 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -141.806 | 0.000 | 0.000 | 10.478 | 7.814 | 36.366 | 125.468 | 0.000 | 0.773 | 1.830 | 0.000 | -38.811 | 0.000 | -2.112 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -127.496 | 0.000 | 0.000 | 6.736 | 5.088 | 23.435 | 71.596 | 0.000 | 0.479 | 52.760 | 0.000 | -31.020 | 0.000 | -1.579 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.581 | -751.461 | 0.000 | 0.000 | 108.007 | 79.214 | 363.654 | 446.469 | 0.000 | 18.200 | 137.173 | 0.000 | -363.149 | 0.000 | -41.688 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.280 | -778.930 | 0.000 | 0.000 | 49.905 | 50.460 | 234.352 | 759.773 | 0.000 | 11.481 | 0.021 | 0.000 | -235.421 | 0.000 | -30.105 | -62.796 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.505 | -1274.049 | 0.000 | 0.000 | 105.127 | 78.063 | 363.660 | 1253.730 | 0.000 | 17.573 | 0.058 | 0.000 | -376.670 | 0.000 | -47.975 | -119.964 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.639 | -823.027 | 0.000 | 0.000 | 68.563 | 50.790 | 234.351 | 730.399 | 0.000 | 11.200 | 25.639 | 0.000 | -267.032 | 0.000 | -31.520 | -0.006 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.096 | -77.012 | 0.000 | 0.000 | 10.960 | 7.921 | 36.365 | 44.813 | 0.000 | 2.192 | 10.413 | 0.000 | -33.988 | 0.000 | -4.761 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.230 | -80.895 | 0.000 | 0.000 | 6.856 | 5.046 | 23.435 | 76.269 | 0.000 | 1.398 | 0.001 | 0.000 | -22.231 | 0.000 | -3.467 | -7.641 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.983 | -125.890 | 0.000 | 0.000 | 10.614 | 7.806 | 36.366 | 125.394 | 0.000 | 2.114 | 0.001 | 0.000 | -35.822 | 0.000 | -5.600 | -15.966 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.743 | -83.385 | 0.000 | 0.000 | 6.940 | 5.079 | 23.435 | 72.943 | 0.000 | 1.361 | 1.935 | 0.000 | -25.369 | 0.000 | -3.682 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.609 | 0.000 | 0.000 | 0.934 | 1.776 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.981 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.076 | -1283.973 | 0.000 | 0.000 | 9.372 | 17.757 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -282.037 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.078 | -123.712 | 0.000 | 0.000 | 0.939 | 1.776 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -32.962 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7148.037 | 0.000 | 0.000 | 19.189 | 34.812 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -400.822 |
GROUNDFLOOR_PLENUM | 1.124 | -87.719 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.482 | 89.569 | 0.000 | 0.000 | 0.000 | -4.456 | 0.000 |
MIDFLOOR_PLENUM | 15.166 | -597.368 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27.116 | 631.051 | 0.000 | 0.000 | 0.000 | -75.965 | -0.006 |
TOPFLOOR_PLENUM | 9.945 | -106.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.743 | 101.791 | 0.000 | 0.000 | 0.000 | -7.672 | -0.000 |
Total Facility | 26.235 | -791.893 | 17.022 | -19613.152 | 0.000 | 0.000 | 1528.767 | 1812.698 | 14676.396 | 3826.169 | 0.000 | 99.420 | 1275.924 | 0.000 | -1494.479 | 0.000 | -263.943 | -1099.084 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 16-OCT-04:11 | 0.00 | 0.00 | 0.00 | -102001.80 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 87945.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | -89457.19 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 82982.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 20-SEP-04:13 | 0.00 | 0.00 | 0.00 | -813569.16 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 748819.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-04:13 | 0.00 | 0.00 | 0.00 | -83227.22 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 76752.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUN-17:11 | 0.00 | 0.00 | 0.00 | -18647.20 | 0.00 | 0.00 | 0.00 | 32.13 | 559.17 | 6473.47 | 0.00 | 270.42 | 11312.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-09:31 | 0.00 | 0.00 | 0.00 | -20014.45 | 0.00 | 0.00 | 20.96 | 20.71 | 464.11 | 12849.77 | 0.00 | 0.00 | 6684.26 | 0.00 | -0.00 | 0.00 | -25.36 | 0.00 |
PERIMETER_BOT_ZN_1 | 25-DEC-13:41 | 0.00 | 0.00 | 0.00 | -23755.09 | 0.00 | 0.00 | 30.54 | 32.13 | 720.19 | 23603.37 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -54.30 | -576.84 |
PERIMETER_BOT_ZN_4 | 23-APR-16:21 | 0.00 | 0.00 | 0.00 | -28568.86 | 0.00 | 0.00 | 14.03 | 20.71 | 464.11 | 15506.77 | 0.00 | 62.97 | 12500.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 30-JUL-18:11 | 0.00 | 0.00 | 0.00 | -185969.53 | 0.00 | 0.00 | 0.00 | 321.32 | 5591.71 | 53307.75 | 0.00 | 10501.59 | 116247.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18-JUN-08:41 | 0.00 | 0.00 | 0.00 | -224229.73 | 0.00 | 0.00 | 182.75 | 207.07 | 4641.14 | 148614.81 | 0.00 | 996.53 | 69587.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 19-NOV-14:51 | 0.00 | 0.00 | 0.00 | -225940.72 | 0.00 | 0.00 | 332.79 | 321.33 | 7201.95 | 168513.09 | 0.00 | 0.00 | 51529.16 | 0.00 | -0.00 | 0.00 | -1957.60 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-17:31 | 0.00 | 0.00 | 0.00 | -256438.32 | 0.00 | 0.00 | 0.00 | 207.07 | 3603.49 | 153069.84 | 0.00 | 5409.22 | 94148.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-JUL-18:11 | 0.00 | 0.00 | 0.00 | -22295.47 | 0.00 | 0.00 | 0.00 | 32.13 | 559.17 | 5133.15 | 0.00 | 1218.04 | 15352.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-08:11 | 0.00 | 0.00 | 0.00 | -22852.66 | 0.00 | 0.00 | 18.63 | 20.71 | 464.11 | 15202.09 | 0.00 | 91.56 | 7055.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-13:21 | 0.00 | 0.00 | 0.00 | -26167.99 | 0.00 | 0.00 | 30.49 | 32.13 | 720.19 | 19494.67 | 0.00 | 72.64 | 5817.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-17:31 | 0.00 | 0.00 | 0.00 | -28558.75 | 0.00 | 0.00 | 0.00 | 20.71 | 360.35 | 15158.66 | 0.00 | 629.09 | 12389.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 28-DEC-17:00 | 0.00 | 0.00 | 0.00 | -7838.75 | 0.00 | 0.00 | 100.85 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -211.56 |
DATACENTER_MID_ZN_6 | 28-DEC-17:00 | 0.00 | 0.00 | 0.00 | -73746.92 | 0.00 | 0.00 | 1008.50 | 1550.41 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6756.22 |
DATACENTER_TOP_ZN_6 | 26-APR-18:30 | 0.00 | 0.00 | 0.00 | -7478.99 | 0.00 | 0.00 | 10.39 | 51.68 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -377.50 |
DATACENTER_BASEMENT_ZN_6 | 23-AUG-22:53 | 0.00 | 0.00 | 0.00 | -386154.60 | 0.00 | 0.00 | 105.81 | 168.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 6247.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-AUG-05:13 | 0.00 | -16583.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 16560.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 28-AUG-05:13 | 0.00 | -127268.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.40 | 126759.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:40 | 0.00 | -23512.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.36 | 22895.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-AUG-05:01 | 0.00 | -70506.56 | 0.00 | -2016860.45 | 0.00 | 0.00 | 15322.00 | 10253.98 | 616289.16 | 8288.09 | 0.00 | 2066.63 | 1435333.89 | 0.00 | -186.75 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-AUG-16:01 | 0.00 | 0.00 | 29878.29 | 0.00 | 0.00 | 0.00 | 520.13 | 598.90 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -44454.86 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 66060.77 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -72535.76 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 07-DEC-06:01 | 0.00 | 0.00 | 1375.05 | 0.00 | 0.00 | 0.00 | 90.33 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 1886.20 | 0.00 | -3937.46 | 0.00 | -76.43 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 136192.73 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39255.58 | 0.00 | -2766.94 | -102300.54 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 119205.92 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27323.07 | 0.00 | -1925.19 | -95197.14 |
PERIMETER_MID_ZN_1 | 07-DEC-06:01 | 0.00 | 0.00 | 136520.62 | 0.00 | 0.00 | 0.00 | 1460.99 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57552.68 | 0.00 | -2654.69 | -88051.57 |
PERIMETER_MID_ZN_4 | 07-DEC-06:01 | 0.00 | 0.00 | 104489.44 | 0.00 | 0.00 | 0.00 | 941.48 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37107.21 | 0.00 | -1777.53 | -73169.13 |
PERIMETER_TOP_ZN_3 | 18-DEC-05:11 | 0.00 | 0.00 | 17324.10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3385.81 | 0.00 | -522.92 | -14228.39 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 15678.19 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2249.71 | 0.00 | -198.68 | -13753.74 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 17784.40 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3809.87 | 0.00 | -330.86 | -14456.72 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 15415.41 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2450.86 | 0.00 | -218.51 | -13269.99 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-01:43 | 0.00 | 0.00 | 4002.82 | 0.00 | 0.00 | 0.00 | 0.00 | 86.14 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23575.01 |
DATACENTER_TOP_ZN_6 | 01-JAN-01:35 | 0.00 | 0.00 | 578.44 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2535.66 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 23-APR-15:41 | 10705.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11162.73 |
MIDFLOOR_PLENUM | 30-JUL-16:11 | 92650.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13329.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -105979.66 |
TOPFLOOR_PLENUM | 02-JAN-06:03 | 17339.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -159.35 | -17180.51 |
Total Facility | 07-DEC-06:01 | -782465.75 | 738995.20 | 589832.05 | -738995.20 | 0.00 | 0.00 | 18885.36 | 10253.98 | 616289.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -224093.20 | 0.00 | -15431.94 | -213269.66 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.9569 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.7607 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 105.0652 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 91.8460 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.0428 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4496 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4496 | 0.2202 | 1.0000 | Not calculated | 1.2002 | 0.2202 | ||
AIRLOOP DATACENTER BASEMENT | 23.3760 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 23.3762 | 0.0145 | 1.0000 | Not calculated | 0.3384 | 0.0145 | ||
AIRLOOP DATACENTER BOT | 0.5059 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5059 | 0.0309 | 1.0000 | Not calculated | 0.0156 | 0.0309 | ||
AIRLOOP DATACENTER MID | 4.8307 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8307 | 0.0324 | 1.0000 | Not calculated | 0.1563 | 0.0324 | ||
AIRLOOP DATACENTER TOP | 0.4944 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4944 | 0.0316 | 1.0000 | Not calculated | 0.0156 | 0.0316 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4784 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2818 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.5326 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8214 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5214 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2834 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4496 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4496 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2202 | ||
AIRLOOP DATACENTER BASEMENT | 23.3760 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 23.3760 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0145 | ||
AIRLOOP DATACENTER BOT | 0.5059 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5059 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0309 | ||
AIRLOOP DATACENTER MID | 4.8307 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8307 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0324 | ||
AIRLOOP DATACENTER TOP | 0.4944 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4944 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0316 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4496 | 5.4496 | 5.4496 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8719 | 5.8719 | 1.6148 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.3293 | 55.3293 | 16.1562 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5856 | 5.5856 | 1.6142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1523 | 1.1523 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1500 | 1.1500 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2974 | 1.2974 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4853 | 1.4853 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.3993 | 11.3993 | 2.0291 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.2206 | 12.2206 | 1.3076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.8192 | 12.8192 | 2.0254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2967 | 13.2967 | 1.3031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3123 | 1.3123 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2580 | 1.2580 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4432 | 1.4432 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4436 | 1.4436 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5059 | 0.5059 | 0.5059 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8307 | 4.8307 | 4.8307 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4944 | 0.4944 | 0.4944 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 23.3760 | 23.3760 | 23.3760 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.9569 | 9.7607 | 10.9569 | 2.2818 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 105.0652 | 91.8460 | 105.0652 | 22.8214 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.0428 | 10.5513 | 11.0428 | 2.2834 | 0.0000 | 1.0000 |
CAV_BAS | 5.4496 | 5.4496 | 5.4496 | 5.4496 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.3760 | 23.3762 | 23.3760 | 23.3760 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5059 | 0.5059 | 0.5059 | 0.5059 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8307 | 4.8307 | 4.8307 | 4.8307 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4944 | 0.4944 | 0.4944 | 0.4944 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4496 | 5.4496 | 5.4496 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9360 | 2.9360 | 1.6148 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.6647 | 27.6647 | 16.1562 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7928 | 2.7928 | 1.6142 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5761 | 0.5761 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5750 | 0.5750 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6487 | 0.6487 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7426 | 0.7426 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6996 | 5.6996 | 2.0291 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1103 | 6.1103 | 1.3076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4096 | 6.4096 | 2.0254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6484 | 6.6484 | 1.3031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6562 | 0.6562 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6290 | 0.6290 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7216 | 0.7216 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7218 | 0.7218 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5059 | 0.5059 | 0.5059 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8307 | 4.8307 | 4.8307 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4944 | 0.4944 | 0.4944 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 23.3760 | 23.3760 | 23.3760 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4784 | 2.2818 | 2.2818 | 2.2818 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.5326 | 22.8214 | 22.8214 | 22.8214 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5214 | 2.2834 | 2.2834 | 2.2834 | 0.0000 | 1.0000 |
CAV_BAS | 5.4496 | 5.4496 | 5.4496 | 5.4496 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.3760 | 23.3760 | 23.3760 | 23.3760 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5059 | 0.5059 | 0.5059 | 0.5059 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8307 | 4.8307 | 4.8307 | 4.8307 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4944 | 0.4944 | 0.4944 | 0.4944 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1137.33 |
Number of hours not met | 1137.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 74.72 | 557558.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3594.84 | 415440.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1812.70 | 179838.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 264.53 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.39 | 3377.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2640.26 | 254980.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 547.20 | 46806.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1144.14 | 75058.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1609.27 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 647.05 | 76828.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27493.06 |
Natural Gas | 0.00 | 721.77 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 28214.83 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 627.21 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 39.13 |
Space Heating | 0.00 |
Space Cooling | 77.61 |
Fans (All) | 57.00 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 593.54 |
Subtotal | 593.54 |
Natural Gas [MJ/m2] | |
Space Heating | 1.61 |
Service Water Heating | 13.97 |
Miscellaneous (All) | 15.58 |
Subtotal | 15.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.42 |
Space Heating | 0.26 |
Space Cooling | 12.74 |
Fans (All) | 9.36 |
Service Water Heating | 2.29 |
Receptacle Equipment | 52.02 |
Miscellaneous | 16.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2192. | 8760. |
LTG_SCH_DATACENTER | 1950. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 837. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8424.67 | 335.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8653.17 | 106.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8643.33 | 116.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8253.50 | 506.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8703.33 | 56.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8572.67 | 187.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8607.33 | 152.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8439.33 | 320.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8660.50 | 99.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8550.50 | 209.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8577.17 | 182.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8441.67 | 318.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7499.17 | 1260.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7607.67 | 1152.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7665.67 | 1094.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6634.00 | 2045.00 | 81.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8528.33 | 231.67 | 0.00 | 0.00 | 0.00 |
Min | 6634.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2045.00 | 81.00 | 0.00 | 0.00 |
Average | 8387.19 | 369.29 | 3.52 | 0.00 | 0.00 |
Sum | 192905.33 | 8493.67 | 81.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367545.00 | 1071.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330773.00 | 40.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330793.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1699.00 | 569.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1711.83 | 556.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1729.83 | 538.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 74203.83 | 27824.33 | 1366.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367545.00 | 27824.33 | 1366.83 | 0.00 | 0.00 |
Average | 78943.85 | 1331.64 | 59.43 | 0.00 | 0.00 |
Sum | 1815708.50 | 30627.67 | 1366.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8044.67 | 715.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8389.17 | 370.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8450.00 | 310.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8428.83 | 331.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8304.17 | 455.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8344.00 | 416.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8264.83 | 495.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8068.83 | 691.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8265.50 | 494.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8200.17 | 559.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8215.67 | 544.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8144.33 | 615.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8258.33 | 501.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8202.83 | 557.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8217.83 | 542.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8164.67 | 595.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8185.50 | 574.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8229.67 | 530.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8262.00 | 498.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7164.17 | 1591.50 | 4.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8200.83 | 559.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8213.17 | 546.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7790.33 | 969.67 | 0.00 | 0.00 | 0.00 |
Min | 7164.17 | 310.00 | 0.00 | 0.00 | 0.00 |
Max | 8450.00 | 1591.50 | 4.33 | 0.00 | 0.00 |
Average | 8174.33 | 585.49 | 0.19 | 0.00 | 0.00 |
Sum | 188009.50 | 13466.17 | 4.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 365790.83 | 2825.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329996.00 | 817.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330302.00 | 511.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329701.50 | 1111.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38914.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38903.33 | 21.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24895.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24903.83 | 5.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1927.67 | 340.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1928.83 | 339.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1948.00 | 320.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82922.83 | 20363.50 | 108.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365790.83 | 20363.50 | 108.67 | 0.00 | 0.00 |
Average | 79170.21 | 1159.98 | 4.72 | 0.00 | 0.00 |
Sum | 1820914.83 | 26679.50 | 108.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515175E+11 | 99296.39 | 09-JAN-05:12 | 9.33 | 9.33 | 0.566797E+10 | 7499.22 | 23-JAN-14:20 | 21.67 | 11.33 |
February | 0.425864E+11 | 97894.83 | 13-FEB-05:11 | 8.00 | 8.00 | 0.513765E+10 | 7499.27 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.500245E+11 | 98853.69 | 20-MAR-04:12 | 11.83 | 7.65 | 0.613135E+10 | 7499.23 | 10-MAR-14:20 | 11.83 | 7.65 |
April | 0.511759E+11 | 98295.82 | 24-APR-04:21 | 16.00 | 5.06 | 0.545053E+10 | 7499.23 | 04-APR-09:09 | 16.00 | 5.06 |
May | 0.514458E+11 | 98778.33 | 29-MAY-17:48 | 31.17 | 13.71 | 0.590073E+10 | 7499.18 | 11-MAY-09:20 | 31.17 | 13.71 |
June | 0.528108E+11 | 99411.04 | 19-JUN-04:12 | 22.67 | 10.74 | 0.588119E+10 | 7499.27 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.582079E+11 | 101046.20 | 03-JUL-04:11 | 20.67 | 7.71 | 0.547496E+10 | 7499.39 | 21-JUL-09:20 | 31.33 | 20.88 |
August | 0.673759E+11 | 99258.08 | 27-AUG-18:16 | 38.33 | 18.09 | 0.613890E+10 | 7499.26 | 18-AUG-09:09 | 38.33 | 18.09 |
September | 0.603118E+11 | 99376.82 | 18-SEP-03:02 | 26.00 | 12.63 | 0.545563E+10 | 7499.23 | 22-SEP-09:20 | 24.20 | 17.34 |
October | 0.617374E+11 | 102002.62 | 16-OCT-04:11 | 17.00 | 7.00 | 0.567324E+10 | 7711.74 | 10-OCT-09:09 | 17.00 | 7.00 |
November | 0.588034E+11 | 99392.91 | 24-NOV-05:11 | 3.67 | -1.5 | 0.561617E+10 | 7499.38 | 16-NOV-14:20 | 3.67 | -1.5 |
December | 0.564931E+11 | 99874.43 | 11-DEC-05:11 | 8.33 | 1.55 | 0.547300E+10 | 7499.11 | 21-DEC-14:20 | 25.33 | 10.67 |
Annual Sum or Average | 0.662490E+12 | 0.680013E+11 | ||||||||
Minimum of Months | 0.425864E+11 | 97894.83 | 3.67 | -1.5 | 0.513765E+10 | 7499.11 | 3.67 | -1.5 | ||
Maximum of Months | 0.673759E+11 | 102002.62 | 38.33 | 18.09 | 0.613890E+10 | 7711.74 | 38.33 | 20.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426652E+11 | 83541.58 | 17-JAN-05:12 | 11.33 | 3.83 | 0.507615E+10 | 6734.79 | 23-JAN-14:20 | 21.67 | 11.33 |
February | 0.378522E+11 | 83830.29 | 21-FEB-05:12 | 9.33 | 8.41 | 0.460547E+10 | 6735.01 | 15-FEB-14:00 | 9.33 | 8.41 |
March | 0.497062E+11 | 84774.67 | 20-MAR-04:12 | 11.83 | 7.65 | 0.549962E+10 | 6734.86 | 17-MAR-09:00 | 11.83 | 7.65 |
April | 0.617594E+11 | 81668.90 | 20-APR-04:13 | 13.00 | 5.28 | 0.487931E+10 | 6734.83 | 10-APR-09:09 | 13.00 | 5.28 |
May | 0.538402E+11 | 87903.26 | 30-MAY-04:13 | 18.00 | 9.08 | 0.528574E+10 | 6734.80 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.614740E+11 | 78733.34 | 19-JUN-05:04 | 22.17 | 10.17 | 0.526574E+10 | 6734.81 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.644398E+11 | 76743.63 | 17-JUL-05:05 | 26.85 | 19.48 | 0.489472E+10 | 6734.85 | 05-JUL-09:09 | 26.85 | 19.48 |
August | 0.736733E+11 | 81598.88 | 21-AUG-05:05 | 24.67 | 16.53 | 0.549825E+10 | 6770.75 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.542308E+11 | 86671.53 | 20-SEP-04:13 | 23.80 | 14.03 | 0.488316E+10 | 6734.79 | 15-SEP-09:20 | 23.80 | 14.03 |
October | 0.531160E+11 | 89458.10 | 16-OCT-04:12 | 17.00 | 7.00 | 0.507984E+10 | 6734.81 | 10-OCT-09:20 | 17.00 | 7.00 |
November | 0.495104E+11 | 85633.28 | 06-NOV-05:12 | 7.67 | 2.51 | 0.503057E+10 | 6734.97 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.480306E+11 | 86986.38 | 04-DEC-05:11 | 3.00 | 0.78 | 0.490307E+10 | 6734.75 | 19-DEC-10:20 | 13.00 | 5.14 |
Annual Sum or Average | 0.650298E+12 | 0.609016E+11 | ||||||||
Minimum of Months | 0.378522E+11 | 76743.63 | 3.00 | 0.78 | 0.460547E+10 | 6734.75 | 9.33 | 5.14 | ||
Maximum of Months | 0.736733E+11 | 89458.10 | 26.85 | 19.48 | 0.549962E+10 | 6770.75 | 33.33 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308634E+11 | 70927.54 | 09-JAN-06:03 | 9.83 | 9.83 | 0.502900E+10 | 6734.78 | 20-JAN-10:39 | 17.67 | 9.70 |
February | 0.263079E+11 | 70984.71 | 24-FEB-06:02 | 7.00 | 7.00 | 0.457199E+10 | 6734.86 | 15-FEB-14:00 | 7.00 | 7.00 |
March | 0.342384E+11 | 74099.85 | 18-MAR-05:02 | 11.78 | 9.21 | 0.548096E+10 | 6734.81 | 17-MAR-09:00 | 11.78 | 9.21 |
April | 0.409913E+11 | 74500.41 | 17-APR-04:12 | 14.67 | 9.77 | 0.487442E+10 | 6734.82 | 04-APR-09:09 | 14.67 | 9.77 |
May | 0.456767E+11 | 76195.13 | 12-MAY-05:03 | 18.67 | 8.63 | 0.528231E+10 | 6734.79 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.499044E+11 | 72940.64 | 13-JUN-04:12 | 19.67 | 7.92 | 0.526291E+10 | 6734.81 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.482410E+11 | 79999.52 | 03-JUL-04:13 | 20.67 | 7.71 | 0.489147E+10 | 6734.86 | 21-JUL-09:20 | 31.33 | 20.88 |
August | 0.497876E+11 | 73956.56 | 05-AUG-04:12 | 21.67 | 17.87 | 0.549294E+10 | 6734.88 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.439748E+11 | 81358.97 | 20-SEP-04:13 | 23.80 | 14.03 | 0.488062E+10 | 6734.79 | 15-SEP-09:20 | 23.80 | 14.03 |
October | 0.394526E+11 | 75539.53 | 11-OCT-04:12 | 18.00 | 10.82 | 0.506895E+10 | 6734.83 | 03-OCT-13:39 | 18.00 | 10.82 |
November | 0.324542E+11 | 74074.97 | 13-NOV-05:12 | 17.00 | 17.00 | 0.500979E+10 | 6734.91 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.281141E+11 | 69906.76 | 29-DEC-06:02 | 6.00 | 1.72 | 0.485194E+10 | 6734.78 | 13-DEC-10:20 | 6.00 | 1.72 |
Annual Sum or Average | 0.470006E+12 | 0.606973E+11 | ||||||||
Minimum of Months | 0.263079E+11 | 69906.76 | 6.00 | 1.72 | 0.457199E+10 | 6734.78 | 6.00 | 1.72 | ||
Maximum of Months | 0.499044E+11 | 81358.97 | 23.80 | 17.87 | 0.549294E+10 | 6734.91 | 33.33 | 20.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239113E+11 | 32482.62 | 27-JAN-17:00 | 26.00 | 9.22 | 0.484131E+10 | 6734.68 | 23-JAN-14:20 | 26.00 | 9.22 |
February | 0.200758E+11 | 30488.51 | 23-FEB-15:00 | 18.00 | 10.35 | 0.437612E+10 | 6734.69 | 15-FEB-14:00 | 18.00 | 10.35 |
March | 0.282308E+11 | 70100.43 | 17-MAR-05:03 | 13.48 | 9.60 | 0.536207E+10 | 6734.79 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.414807E+11 | 74509.55 | 26-APR-04:12 | 20.00 | 10.45 | 0.486468E+10 | 6734.80 | 03-APR-09:20 | 20.00 | 10.45 |
May | 0.486425E+11 | 75802.64 | 26-MAY-05:03 | 21.33 | 12.61 | 0.528312E+10 | 6734.78 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.573181E+11 | 83237.82 | 19-JUN-04:13 | 22.67 | 10.74 | 0.526691E+10 | 6734.81 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.553416E+11 | 83144.37 | 03-JUL-04:13 | 20.67 | 7.71 | 0.489695E+10 | 6734.85 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.556900E+11 | 77088.69 | 21-AUG-05:03 | 24.67 | 16.53 | 0.549591E+10 | 6734.89 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.472581E+11 | 82770.51 | 20-SEP-04:13 | 23.80 | 14.03 | 0.488299E+10 | 6734.76 | 28-SEP-09:20 | 28.30 | 15.58 |
October | 0.357806E+11 | 75152.46 | 05-OCT-04:12 | 19.67 | 13.65 | 0.502466E+10 | 6734.79 | 10-OCT-09:20 | 27.00 | 15.93 |
November | 0.257540E+11 | 70268.59 | 03-NOV-05:03 | 16.00 | 12.46 | 0.487238E+10 | 6734.83 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.199578E+11 | 29937.98 | 22-DEC-17:00 | 24.00 | 9.52 | 0.450044E+10 | 6734.63 | 22-DEC-14:20 | 24.00 | 9.52 |
Annual Sum or Average | 0.459441E+12 | 0.596676E+11 | ||||||||
Minimum of Months | 0.199578E+11 | 29937.98 | 13.48 | 7.71 | 0.437612E+10 | 6734.63 | 18.00 | 9.22 | ||
Maximum of Months | 0.573181E+11 | 83237.82 | 26.00 | 16.53 | 0.549591E+10 | 6734.89 | 33.33 | 20.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363731E+10 | 4996.18 | 31-JAN-16:30 | 29.00 | 10.73 | 0.621829E+09 | 845.63 | 23-JAN-14:20 | 29.00 | 10.73 |
February | 0.308449E+10 | 4987.72 | 22-FEB-14:00 | 21.00 | 12.01 | 0.563840E+09 | 845.65 | 15-FEB-14:00 | 21.00 | 12.01 |
March | 0.498392E+10 | 7172.66 | 20-MAR-14:00 | 27.70 | 14.42 | 0.681210E+09 | 845.64 | 17-MAR-09:00 | 27.70 | 14.42 |
April | 0.898800E+10 | 17701.59 | 30-APR-16:21 | 32.50 | 11.88 | 0.612508E+09 | 845.63 | 27-APR-13:30 | 32.50 | 11.88 |
May | 0.961716E+10 | 17760.37 | 07-MAY-17:01 | 35.83 | 14.32 | 0.664528E+09 | 845.63 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.135100E+11 | 18647.80 | 04-JUN-17:11 | 37.67 | 15.89 | 0.663063E+09 | 845.76 | 19-JUN-13:00 | 39.00 | 18.45 |
July | 0.130247E+11 | 18499.82 | 04-JUL-17:21 | 36.50 | 15.52 | 0.616640E+09 | 845.75 | 17-JUL-13:50 | 36.67 | 20.83 |
August | 0.136118E+11 | 18137.78 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691542E+09 | 851.37 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.964834E+10 | 17749.67 | 17-SEP-15:52 | 34.40 | 17.71 | 0.614073E+09 | 845.63 | 15-SEP-09:20 | 34.40 | 17.71 |
October | 0.653454E+10 | 13744.17 | 02-OCT-04:23 | 26.00 | 17.05 | 0.633969E+09 | 845.66 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.455815E+10 | 6786.98 | 02-NOV-13:30 | 26.50 | 15.49 | 0.623893E+09 | 845.65 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.351518E+10 | 5265.11 | 26-DEC-15:30 | 23.00 | 10.56 | 0.596721E+09 | 845.62 | 13-DEC-10:20 | 23.00 | 10.56 |
Annual Sum or Average | 0.947135E+11 | 0.758381E+10 | ||||||||
Minimum of Months | 0.308449E+10 | 4987.72 | 21.00 | 10.56 | 0.563840E+09 | 845.62 | 18.00 | 10.56 | ||
Maximum of Months | 0.136118E+11 | 18647.80 | 38.00 | 20.26 | 0.691542E+09 | 851.37 | 39.00 | 20.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377785E+10 | 7600.98 | 17-JAN-09:30 | 16.50 | 6.15 | 0.406655E+09 | 544.96 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.304241E+10 | 10866.68 | 20-FEB-09:43 | 13.67 | 12.07 | 0.367413E+09 | 544.97 | 15-FEB-14:00 | 13.67 | 12.07 |
March | 0.468242E+10 | 17036.41 | 19-MAR-09:32 | 21.80 | 12.11 | 0.441659E+09 | 544.97 | 14-MAR-09:00 | 21.80 | 12.11 |
April | 0.858391E+10 | 19346.77 | 23-APR-08:22 | 23.50 | 8.72 | 0.395329E+09 | 545.88 | 24-APR-09:50 | 26.83 | 10.74 |
May | 0.977950E+10 | 20014.64 | 29-MAY-09:31 | 27.33 | 12.10 | 0.428945E+09 | 545.73 | 11-MAY-09:00 | 27.33 | 12.10 |
June | 0.119971E+11 | 19188.78 | 04-JUN-09:11 | 31.37 | 16.06 | 0.427638E+09 | 545.62 | 09-JUN-09:00 | 31.00 | 15.04 |
July | 0.109438E+11 | 18798.54 | 04-JUL-08:41 | 29.67 | 12.78 | 0.397677E+09 | 545.56 | 05-JUL-09:00 | 33.00 | 15.71 |
August | 0.110687E+11 | 18791.03 | 13-AUG-09:02 | 32.17 | 20.93 | 0.445791E+09 | 550.84 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.846357E+10 | 19655.89 | 10-SEP-09:21 | 30.20 | 19.40 | 0.396001E+09 | 546.28 | 08-SEP-09:00 | 30.20 | 19.40 |
October | 0.643136E+10 | 18529.87 | 15-OCT-08:42 | 23.33 | 9.51 | 0.410077E+09 | 545.43 | 05-OCT-09:09 | 23.33 | 9.51 |
November | 0.408142E+10 | 8674.69 | 19-NOV-09:43 | 22.17 | 10.30 | 0.404017E+09 | 544.98 | 22-NOV-10:50 | 20.00 | 11.34 |
December | 0.302432E+10 | 6665.14 | 26-DEC-09:40 | 16.33 | 7.28 | 0.390040E+09 | 544.95 | 13-DEC-10:09 | 16.33 | 7.28 |
Annual Sum or Average | 0.858764E+11 | 0.491124E+10 | ||||||||
Minimum of Months | 0.302432E+10 | 6665.14 | 13.67 | 6.15 | 0.367413E+09 | 544.95 | 13.67 | 7.28 | ||
Maximum of Months | 0.119971E+11 | 20014.64 | 32.17 | 20.93 | 0.445791E+09 | 550.84 | 33.00 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121345E+11 | 22248.12 | 16-JAN-12:12 | 24.00 | 8.78 | 0.636822E+09 | 904.66 | 17-JAN-14:20 | 24.33 | 9.07 |
February | 0.713401E+10 | 20766.36 | 26-FEB-14:32 | 17.00 | 9.86 | 0.570655E+09 | 847.44 | 23-FEB-14:00 | 17.00 | 9.86 |
March | 0.852036E+10 | 14386.13 | 26-MAR-13:43 | 17.10 | 5.98 | 0.683240E+09 | 847.24 | 17-MAR-13:09 | 17.10 | 5.98 |
April | 0.123333E+11 | 20941.76 | 23-APR-15:41 | 33.25 | 12.77 | 0.613211E+09 | 847.00 | 25-APR-13:30 | 31.00 | 14.65 |
May | 0.104678E+11 | 20097.76 | 07-MAY-16:21 | 36.00 | 14.22 | 0.664673E+09 | 845.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.129896E+11 | 20728.61 | 04-JUN-15:51 | 38.00 | 16.06 | 0.662889E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.132410E+11 | 20589.13 | 04-JUL-16:41 | 37.00 | 16.02 | 0.616663E+09 | 846.04 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.155913E+11 | 20688.38 | 27-AUG-13:41 | 39.67 | 18.22 | 0.691828E+09 | 851.66 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.135280E+11 | 22319.99 | 10-SEP-12:41 | 34.22 | 18.96 | 0.615341E+09 | 902.51 | 28-SEP-13:39 | 36.47 | 16.05 |
October | 0.134306E+11 | 23084.37 | 15-OCT-13:21 | 30.50 | 12.34 | 0.640819E+09 | 905.43 | 02-OCT-13:09 | 30.50 | 12.34 |
November | 0.116782E+11 | 22519.26 | 19-NOV-13:42 | 26.00 | 11.10 | 0.634047E+09 | 915.19 | 20-NOV-14:20 | 27.00 | 11.68 |
December | 0.107588E+11 | 23755.69 | 25-DEC-13:41 | 25.83 | 11.94 | 0.612015E+09 | 895.39 | 26-DEC-14:09 | 23.00 | 10.20 |
Annual Sum or Average | 0.141807E+12 | 0.764220E+10 | ||||||||
Minimum of Months | 0.713401E+10 | 14386.13 | 17.00 | 5.98 | 0.570655E+09 | 845.65 | 17.00 | 5.98 | ||
Maximum of Months | 0.155913E+11 | 23755.69 | 39.67 | 18.96 | 0.691828E+09 | 915.19 | 38.17 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545190E+10 | 24097.84 | 29-JAN-16:22 | 24.50 | 9.40 | 0.409411E+09 | 544.98 | 30-JAN-14:00 | 25.00 | 9.66 |
February | 0.468130E+10 | 17932.12 | 20-FEB-16:22 | 17.50 | 9.63 | 0.372184E+09 | 545.00 | 15-FEB-14:00 | 17.50 | 9.63 |
March | 0.806155E+10 | 19346.91 | 26-MAR-15:42 | 18.12 | 6.11 | 0.445619E+09 | 544.97 | 09-MAR-14:00 | 18.12 | 6.11 |
April | 0.149059E+11 | 28568.79 | 23-APR-16:21 | 33.15 | 12.72 | 0.396883E+09 | 544.98 | 27-APR-13:30 | 25.00 | 11.82 |
May | 0.116413E+11 | 27179.08 | 28-MAY-17:01 | 32.83 | 12.78 | 0.429371E+09 | 544.96 | 12-MAY-09:09 | 32.83 | 12.78 |
June | 0.154239E+11 | 28334.49 | 04-JUN-16:31 | 38.00 | 16.06 | 0.428136E+09 | 544.96 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.148504E+11 | 27868.75 | 04-JUL-17:21 | 36.50 | 15.52 | 0.398454E+09 | 544.97 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.185588E+11 | 26792.23 | 13-AUG-16:21 | 38.00 | 20.26 | 0.446882E+09 | 550.47 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.102532E+11 | 24117.93 | 24-SEP-15:12 | 33.80 | 18.62 | 0.396617E+09 | 544.96 | 15-SEP-09:09 | 33.80 | 18.62 |
October | 0.900428E+10 | 24564.33 | 15-OCT-14:01 | 31.00 | 12.59 | 0.412115E+09 | 544.99 | 03-OCT-13:39 | 31.00 | 12.59 |
November | 0.776034E+10 | 24131.42 | 05-NOV-15:12 | 22.67 | 8.62 | 0.407716E+09 | 544.99 | 27-NOV-14:39 | 24.97 | 9.27 |
December | 0.690452E+10 | 25368.75 | 25-DEC-15:01 | 26.00 | 11.63 | 0.397131E+09 | 544.95 | 13-DEC-10:09 | 26.00 | 11.63 |
Annual Sum or Average | 0.127497E+12 | 0.494052E+10 | ||||||||
Minimum of Months | 0.468130E+10 | 17932.12 | 17.50 | 6.11 | 0.372184E+09 | 544.95 | 17.50 | 6.11 | ||
Maximum of Months | 0.185588E+11 | 28568.79 | 38.00 | 20.26 | 0.446882E+09 | 550.47 | 38.17 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253701E+10 | 3687.45 | 31-JAN-16:30 | 29.00 | 10.73 | 0.571594E+09 | 845.61 | 20-JAN-14:20 | 29.00 | 10.73 |
February | 0.200322E+10 | 2912.90 | 22-FEB-14:10 | 21.00 | 11.95 | 0.515743E+09 | 845.62 | 15-FEB-14:00 | 21.00 | 11.95 |
March | 0.316479E+10 | 5442.10 | 16-MAR-16:00 | 28.80 | 13.95 | 0.647202E+09 | 845.63 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.619416E+10 | 17104.78 | 30-APR-16:31 | 32.33 | 11.86 | 0.608365E+09 | 845.63 | 27-APR-13:30 | 32.33 | 11.86 |
May | 0.869333E+10 | 17695.63 | 07-MAY-17:01 | 35.83 | 14.32 | 0.664150E+09 | 845.63 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.125351E+11 | 18205.83 | 11-JUN-18:02 | 33.83 | 14.94 | 0.663216E+09 | 845.64 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.113320E+11 | 18598.17 | 30-JUL-18:11 | 37.33 | 18.54 | 0.616841E+09 | 845.65 | 21-JUL-09:20 | 37.33 | 18.54 |
August | 0.105586E+11 | 17820.25 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691259E+09 | 845.64 | 28-AUG-09:39 | 33.00 | 21.02 |
September | 0.846196E+10 | 17686.27 | 10-SEP-16:42 | 34.00 | 19.47 | 0.613819E+09 | 845.63 | 08-SEP-09:20 | 34.00 | 19.47 |
October | 0.486977E+10 | 11693.11 | 04-OCT-05:02 | 20.83 | 17.03 | 0.617827E+09 | 845.67 | 03-OCT-13:39 | 20.83 | 17.03 |
November | 0.279678E+10 | 5388.76 | 02-NOV-14:00 | 27.00 | 15.44 | 0.588498E+09 | 845.63 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.200011E+10 | 2506.86 | 22-DEC-16:30 | 24.50 | 9.81 | 0.520129E+09 | 833.39 | 22-DEC-14:00 | 24.50 | 9.81 |
Annual Sum or Average | 0.751469E+11 | 0.731864E+10 | ||||||||
Minimum of Months | 0.200011E+10 | 2506.86 | 20.83 | 9.81 | 0.515743E+09 | 833.39 | 18.00 | 9.81 | ||
Maximum of Months | 0.125351E+11 | 18598.17 | 38.00 | 20.26 | 0.691259E+09 | 845.67 | 38.17 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265089E+10 | 6903.86 | 27-JAN-11:05 | 22.33 | 7.96 | 0.293385E+09 | 548.50 | 26-JAN-13:09 | 22.33 | 7.96 |
February | 0.205746E+10 | 7043.09 | 23-FEB-11:05 | 15.83 | 10.67 | 0.264618E+09 | 548.50 | 21-FEB-13:09 | 15.83 | 10.67 |
March | 0.358227E+10 | 13826.69 | 19-MAR-09:23 | 21.35 | 11.96 | 0.320180E+09 | 548.51 | 16-MAR-10:09 | 21.35 | 11.96 |
April | 0.783640E+10 | 21241.30 | 30-APR-09:51 | 28.00 | 10.47 | 0.292176E+09 | 548.51 | 28-APR-10:09 | 28.00 | 10.47 |
May | 0.976221E+10 | 21529.70 | 07-MAY-09:01 | 27.17 | 11.80 | 0.317010E+09 | 548.53 | 22-MAY-10:09 | 25.33 | 9.96 |
June | 0.122238E+11 | 22424.40 | 18-JUN-08:41 | 31.67 | 17.41 | 0.315884E+09 | 548.51 | 29-JUN-10:09 | 34.33 | 18.62 |
July | 0.108932E+11 | 21924.75 | 04-JUL-09:31 | 31.33 | 14.72 | 0.294869E+09 | 548.51 | 03-JUL-14:09 | 31.33 | 14.72 |
August | 0.105411E+11 | 20272.05 | 13-AUG-09:02 | 32.17 | 20.93 | 0.329195E+09 | 548.51 | 22-AUG-10:09 | 32.17 | 19.35 |
September | 0.810945E+10 | 21320.11 | 10-SEP-10:01 | 31.88 | 19.21 | 0.292902E+09 | 548.51 | 22-SEP-10:09 | 25.37 | 17.42 |
October | 0.560338E+10 | 17292.18 | 09-OCT-09:02 | 22.50 | 13.48 | 0.301127E+09 | 548.50 | 18-OCT-10:09 | 26.33 | 11.01 |
November | 0.291168E+10 | 8443.52 | 01-NOV-10:05 | 23.33 | 16.05 | 0.293883E+09 | 548.52 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.172123E+10 | 5499.28 | 27-DEC-11:05 | 16.33 | 7.91 | 0.275960E+09 | 548.49 | 27-DEC-13:09 | 19.00 | 10.04 |
Annual Sum or Average | 0.778931E+11 | 0.359119E+10 | ||||||||
Minimum of Months | 0.172123E+10 | 5499.28 | 15.83 | 7.91 | 0.264618E+09 | 548.49 | 15.83 | 7.96 | ||
Maximum of Months | 0.122238E+11 | 22424.40 | 32.17 | 20.93 | 0.329195E+09 | 548.53 | 34.33 | 19.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119024E+11 | 21294.00 | 29-JAN-13:52 | 24.00 | 9.34 | 0.636380E+09 | 932.88 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.650064E+10 | 20457.83 | 26-FEB-12:23 | 16.00 | 10.19 | 0.561929E+09 | 864.12 | 28-FEB-14:20 | 18.33 | 7.88 |
March | 0.715732E+10 | 15206.72 | 26-MAR-14:13 | 17.20 | 5.88 | 0.671582E+09 | 846.71 | 17-MAR-13:09 | 17.20 | 5.88 |
April | 0.999353E+10 | 20779.59 | 30-APR-12:32 | 33.00 | 12.07 | 0.611183E+09 | 847.00 | 25-APR-13:20 | 33.00 | 12.07 |
May | 0.970622E+10 | 20063.52 | 07-MAY-16:21 | 36.00 | 14.22 | 0.664306E+09 | 845.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.119113E+11 | 19836.74 | 18-JUN-10:41 | 35.67 | 17.76 | 0.662994E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.115967E+11 | 21228.95 | 30-JUL-14:51 | 38.00 | 18.95 | 0.616847E+09 | 846.64 | 31-JUL-13:20 | 37.00 | 19.00 |
August | 0.128587E+11 | 20299.74 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691727E+09 | 847.00 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.128377E+11 | 22388.23 | 10-SEP-12:41 | 34.22 | 18.96 | 0.615946E+09 | 930.66 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.126389E+11 | 21411.22 | 09-OCT-13:42 | 31.83 | 17.27 | 0.640080E+09 | 931.25 | 31-OCT-13:00 | 27.00 | 12.18 |
November | 0.106906E+11 | 22595.67 | 19-NOV-14:51 | 27.00 | 11.47 | 0.631214E+09 | 928.15 | 20-NOV-14:20 | 27.00 | 11.68 |
December | 0.961289E+10 | 22471.42 | 03-DEC-13:12 | 20.33 | 10.37 | 0.602855E+09 | 907.80 | 28-DEC-14:09 | 19.47 | 8.47 |
Annual Sum or Average | 0.127407E+12 | 0.760704E+10 | ||||||||
Minimum of Months | 0.650064E+10 | 15206.72 | 16.00 | 5.88 | 0.561929E+09 | 845.65 | 17.20 | 5.88 | ||
Maximum of Months | 0.128587E+11 | 22595.67 | 38.00 | 20.26 | 0.691727E+09 | 932.88 | 38.17 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349049E+10 | 14292.44 | 29-JAN-16:32 | 24.33 | 9.38 | 0.388667E+09 | 544.95 | 23-JAN-14:20 | 24.33 | 9.38 |
February | 0.236949E+10 | 10554.32 | 22-FEB-16:30 | 20.50 | 11.47 | 0.348865E+09 | 544.96 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.397350E+10 | 15749.36 | 18-MAR-17:05 | 26.92 | 12.85 | 0.429005E+09 | 544.96 | 17-MAR-09:00 | 26.92 | 12.85 |
April | 0.852567E+10 | 24472.60 | 30-APR-16:31 | 32.33 | 11.86 | 0.395166E+09 | 544.96 | 27-APR-13:30 | 32.33 | 11.86 |
May | 0.992021E+10 | 24678.83 | 07-MAY-16:21 | 36.00 | 14.22 | 0.428954E+09 | 544.96 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.126166E+11 | 25134.18 | 11-JUN-17:21 | 34.00 | 15.03 | 0.427924E+09 | 544.96 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.105242E+11 | 25645.35 | 30-JUL-17:31 | 38.00 | 19.05 | 0.398113E+09 | 544.97 | 21-JUL-09:20 | 38.00 | 19.05 |
August | 0.106152E+11 | 24177.73 | 06-AUG-17:31 | 30.33 | 18.66 | 0.446150E+09 | 544.96 | 28-AUG-09:39 | 33.00 | 21.02 |
September | 0.814943E+10 | 21656.61 | 04-SEP-15:42 | 31.60 | 21.45 | 0.396229E+09 | 544.96 | 08-SEP-09:20 | 30.73 | 20.63 |
October | 0.581396E+10 | 20939.00 | 15-OCT-16:12 | 30.67 | 12.42 | 0.404853E+09 | 544.99 | 03-OCT-13:39 | 30.67 | 12.42 |
November | 0.380181E+10 | 20519.83 | 19-NOV-14:51 | 27.00 | 11.47 | 0.393871E+09 | 544.97 | 16-NOV-14:09 | 27.00 | 11.47 |
December | 0.250420E+10 | 14775.09 | 25-DEC-16:32 | 24.67 | 11.46 | 0.362741E+09 | 544.95 | 26-DEC-14:20 | 23.00 | 10.23 |
Annual Sum or Average | 0.823047E+11 | 0.482054E+10 | ||||||||
Minimum of Months | 0.236949E+10 | 10554.32 | 20.50 | 9.38 | 0.348865E+09 | 544.95 | 20.50 | 9.38 | ||
Maximum of Months | 0.126166E+11 | 25645.35 | 38.00 | 21.45 | 0.446150E+09 | 544.99 | 38.17 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200746E+10 | 3431.42 | 27-JAN-16:30 | 26.50 | 9.48 | 0.543325E+09 | 845.61 | 06-JAN-14:20 | 26.50 | 9.48 |
February | 0.152165E+10 | 2686.77 | 22-FEB-16:30 | 20.50 | 11.47 | 0.485897E+09 | 845.58 | 22-FEB-14:20 | 20.50 | 11.47 |
March | 0.274577E+10 | 5879.83 | 16-MAR-16:00 | 28.80 | 13.95 | 0.621073E+09 | 845.62 | 21-MAR-13:20 | 25.17 | 12.74 |
April | 0.638177E+10 | 17168.46 | 30-APR-16:01 | 32.83 | 11.93 | 0.603765E+09 | 845.63 | 27-APR-13:00 | 32.83 | 11.93 |
May | 0.919226E+10 | 20444.74 | 28-MAY-16:51 | 33.00 | 12.91 | 0.663777E+09 | 845.63 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.138154E+11 | 21098.56 | 25-JUN-18:01 | 37.67 | 14.86 | 0.663351E+09 | 845.64 | 19-JUN-13:09 | 37.67 | 14.86 |
July | 0.125856E+11 | 22297.02 | 30-JUL-18:11 | 37.33 | 18.54 | 0.617017E+09 | 845.64 | 05-JUL-09:09 | 37.33 | 18.54 |
August | 0.115129E+11 | 21073.88 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691357E+09 | 845.64 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.898137E+10 | 20551.00 | 24-SEP-14:21 | 33.55 | 18.95 | 0.613549E+09 | 845.63 | 19-SEP-13:20 | 33.55 | 18.95 |
October | 0.465948E+10 | 14385.04 | 02-OCT-03:02 | 25.17 | 16.69 | 0.602855E+09 | 845.66 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.228050E+10 | 5604.10 | 01-NOV-15:30 | 28.50 | 15.96 | 0.563668E+09 | 845.62 | 16-NOV-14:00 | 18.00 | 12.18 |
December | 0.132833E+10 | 2411.51 | 22-DEC-15:00 | 26.00 | 10.43 | 0.489374E+09 | 819.44 | 22-DEC-14:00 | 26.00 | 10.43 |
Annual Sum or Average | 0.770125E+11 | 0.715901E+10 | ||||||||
Minimum of Months | 0.132833E+10 | 2411.51 | 20.50 | 9.48 | 0.485897E+09 | 819.44 | 18.00 | 9.48 | ||
Maximum of Months | 0.138154E+11 | 22297.02 | 38.00 | 20.26 | 0.691357E+09 | 845.66 | 37.67 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222214E+10 | 4726.56 | 27-JAN-10:30 | 21.00 | 7.83 | 0.392386E+09 | 544.95 | 24-JAN-14:20 | 21.00 | 7.83 |
February | 0.166873E+10 | 5390.94 | 23-FEB-10:20 | 14.67 | 11.08 | 0.351868E+09 | 544.95 | 23-FEB-10:09 | 14.67 | 11.08 |
March | 0.329219E+10 | 7243.29 | 23-MAR-10:20 | 22.33 | 10.61 | 0.429819E+09 | 544.97 | 14-MAR-13:50 | 22.33 | 10.61 |
April | 0.818080E+10 | 19798.84 | 30-APR-10:02 | 28.50 | 10.63 | 0.394926E+09 | 544.99 | 11-APR-09:09 | 28.50 | 10.63 |
May | 0.103699E+11 | 21142.52 | 28-MAY-08:52 | 27.00 | 11.44 | 0.428978E+09 | 545.56 | 11-MAY-09:00 | 27.00 | 11.44 |
June | 0.133773E+11 | 22854.27 | 18-JUN-08:11 | 30.67 | 17.10 | 0.427945E+09 | 545.48 | 08-JUN-09:00 | 30.67 | 17.10 |
July | 0.120426E+11 | 22156.20 | 30-JUL-08:11 | 27.00 | 19.19 | 0.398157E+09 | 545.45 | 28-JUL-09:00 | 27.00 | 19.19 |
August | 0.115276E+11 | 20979.48 | 13-AUG-09:42 | 32.83 | 21.13 | 0.446143E+09 | 545.48 | 01-AUG-09:00 | 32.83 | 21.13 |
September | 0.871922E+10 | 20077.92 | 10-SEP-10:12 | 32.17 | 19.22 | 0.396121E+09 | 546.00 | 08-SEP-09:00 | 32.17 | 19.22 |
October | 0.554687E+10 | 19604.83 | 15-OCT-09:22 | 25.00 | 10.12 | 0.405475E+09 | 544.99 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.256008E+10 | 6316.77 | 01-NOV-10:00 | 23.00 | 16.02 | 0.392945E+09 | 544.98 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.138747E+10 | 2877.83 | 22-DEC-10:40 | 20.33 | 8.51 | 0.356279E+09 | 544.95 | 13-DEC-10:20 | 20.33 | 8.51 |
Annual Sum or Average | 0.808949E+11 | 0.482104E+10 | ||||||||
Minimum of Months | 0.138747E+10 | 2877.83 | 14.67 | 7.83 | 0.351868E+09 | 544.95 | 14.67 | 7.83 | ||
Maximum of Months | 0.133773E+11 | 22854.27 | 32.83 | 21.13 | 0.446143E+09 | 546.00 | 32.83 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106314E+11 | 25472.57 | 29-JAN-14:11 | 24.00 | 9.34 | 0.617877E+09 | 871.40 | 24-JAN-14:00 | 24.00 | 9.34 |
February | 0.542044E+10 | 16254.73 | 28-FEB-14:05 | 18.17 | 7.92 | 0.545483E+09 | 846.21 | 23-FEB-14:50 | 18.17 | 7.92 |
March | 0.634360E+10 | 14168.90 | 23-MAR-14:00 | 25.50 | 11.67 | 0.655414E+09 | 845.96 | 16-MAR-13:00 | 25.50 | 11.67 |
April | 0.102349E+11 | 23187.85 | 02-APR-16:21 | 31.00 | 12.54 | 0.607569E+09 | 846.63 | 25-APR-13:09 | 31.00 | 14.74 |
May | 0.102463E+11 | 22612.12 | 28-MAY-16:51 | 33.00 | 12.91 | 0.663529E+09 | 845.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.131605E+11 | 22630.94 | 18-JUN-17:32 | 38.00 | 19.14 | 0.663143E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.128582E+11 | 24816.15 | 30-JUL-14:51 | 38.00 | 18.95 | 0.616982E+09 | 846.01 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.138828E+11 | 23488.15 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691754E+09 | 847.28 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.134381E+11 | 25221.81 | 24-SEP-14:21 | 33.55 | 18.95 | 0.615187E+09 | 903.22 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.122918E+11 | 26168.01 | 15-OCT-13:21 | 30.50 | 12.34 | 0.629151E+09 | 891.74 | 02-OCT-13:09 | 30.50 | 12.34 |
November | 0.954251E+10 | 24420.95 | 05-NOV-13:42 | 22.00 | 8.01 | 0.616648E+09 | 885.71 | 01-NOV-13:00 | 22.00 | 8.01 |
December | 0.784208E+10 | 25544.93 | 25-DEC-14:11 | 26.00 | 11.85 | 0.583310E+09 | 855.30 | 22-DEC-14:09 | 26.00 | 11.85 |
Annual Sum or Average | 0.125893E+12 | 0.750605E+10 | ||||||||
Minimum of Months | 0.542044E+10 | 14168.90 | 18.17 | 7.92 | 0.545483E+09 | 845.65 | 18.17 | 7.92 | ||
Maximum of Months | 0.138828E+11 | 26168.01 | 38.00 | 20.26 | 0.691754E+09 | 903.22 | 38.17 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305628E+10 | 19837.88 | 29-JAN-16:12 | 24.67 | 9.41 | 0.373058E+09 | 544.95 | 23-JAN-14:20 | 24.67 | 9.41 |
February | 0.201103E+10 | 10489.05 | 22-FEB-16:30 | 20.50 | 11.47 | 0.332937E+09 | 544.96 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.361666E+10 | 17030.37 | 18-MAR-17:05 | 26.92 | 12.85 | 0.415332E+09 | 544.97 | 10-MAR-14:00 | 26.92 | 12.85 |
April | 0.868737E+10 | 26900.46 | 02-APR-16:21 | 31.00 | 12.54 | 0.393590E+09 | 544.97 | 27-APR-13:00 | 26.00 | 12.23 |
May | 0.102988E+11 | 27352.38 | 28-MAY-16:51 | 33.00 | 12.91 | 0.428813E+09 | 544.96 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.134919E+11 | 25540.57 | 25-JUN-17:21 | 38.00 | 15.15 | 0.427958E+09 | 544.96 | 19-JUN-13:09 | 38.00 | 15.15 |
July | 0.113984E+11 | 28560.55 | 30-JUL-17:31 | 38.00 | 19.05 | 0.398149E+09 | 544.97 | 05-JUL-09:09 | 38.00 | 19.05 |
August | 0.113009E+11 | 25786.80 | 13-AUG-16:21 | 38.00 | 20.26 | 0.446163E+09 | 544.97 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.851894E+10 | 24469.64 | 24-SEP-16:21 | 33.00 | 18.31 | 0.396181E+09 | 544.95 | 19-SEP-13:20 | 33.00 | 18.31 |
October | 0.566423E+10 | 23655.47 | 15-OCT-16:01 | 30.83 | 12.50 | 0.397308E+09 | 544.98 | 03-OCT-13:39 | 30.83 | 12.50 |
November | 0.335362E+10 | 12261.00 | 01-NOV-16:00 | 28.00 | 15.72 | 0.382099E+09 | 544.96 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.198864E+10 | 16487.91 | 25-DEC-16:11 | 25.33 | 11.74 | 0.345210E+09 | 544.95 | 22-DEC-14:20 | 25.33 | 11.74 |
Annual Sum or Average | 0.833867E+11 | 0.473680E+10 | ||||||||
Minimum of Months | 0.198864E+10 | 10489.05 | 20.50 | 9.41 | 0.332937E+09 | 544.95 | 18.00 | 9.41 | ||
Maximum of Months | 0.134919E+11 | 28560.55 | 38.00 | 20.26 | 0.446163E+09 | 544.98 | 38.00 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358907E+10 | 5736.86 | 17-JAN-17:00 | 24.00 | 9.10 | 0.00 | 0.00 | 01-JAN-00:10 | 24.00 | 9.10 |
February | 0.267328E+10 | 5125.39 | 21-FEB-06:15 | 9.67 | 8.23 | 0.00 | 0.00 | 01-FEB-00:10 | 9.67 | 8.23 |
March | 0.441877E+10 | 7110.31 | 20-MAR-05:15 | 11.27 | 7.51 | 0.00 | 0.00 | 01-MAR-00:10 | 11.27 | 7.51 |
April | 0.837651E+10 | 8952.37 | 24-APR-07:10 | 19.67 | 7.24 | 0.00 | 0.00 | 01-APR-00:10 | 19.67 | 7.24 |
May | 0.881721E+10 | 9497.32 | 30-MAY-05:10 | 18.00 | 8.75 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 8.75 |
June | 0.113626E+11 | 11953.90 | 05-JUN-05:10 | 23.33 | 12.92 | 0.00 | 0.00 | 01-JUN-00:10 | 23.33 | 12.92 |
July | 0.112847E+11 | 14565.63 | 17-JUL-05:15 | 26.70 | 19.47 | 0.00 | 0.00 | 01-JUL-00:10 | 26.70 | 19.47 |
August | 0.126438E+11 | 16583.80 | 28-AUG-05:13 | 28.67 | 19.85 | 0.00 | 0.00 | 01-AUG-00:10 | 28.67 | 19.85 |
September | 0.907660E+10 | 13447.49 | 05-SEP-05:15 | 21.63 | 18.84 | 0.00 | 0.00 | 01-SEP-00:10 | 21.63 | 18.84 |
October | 0.695062E+10 | 12966.15 | 02-OCT-05:15 | 25.67 | 16.91 | 0.00 | 0.00 | 01-OCT-00:10 | 25.67 | 16.91 |
November | 0.494292E+10 | 8717.67 | 13-NOV-06:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-NOV-00:10 | 16.67 | 16.67 |
December | 0.358335E+10 | 8466.17 | 26-DEC-06:15 | 8.67 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 3.13 |
Annual Sum or Average | 0.877196E+11 | 0.00 | ||||||||
Minimum of Months | 0.267328E+10 | 5125.39 | 8.67 | 3.13 | 0.00 | 0.00 | 8.67 | 3.13 | ||
Maximum of Months | 0.126438E+11 | 16583.80 | 28.67 | 19.85 | 0.00 | 0.00 | 28.67 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146389E+10 | 2861.65 | 27-JAN-17:00 | 26.00 | 9.22 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 9.22 |
February | 0.946099E+09 | 2769.67 | 01-FEB-06:10 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.187970E+10 | 4319.13 | 27-MAR-05:03 | 2.52 | -0.8 | 0.00 | 0.00 | 01-MAR-00:10 | 2.52 | -0.8 |
April | 0.553967E+10 | 6600.66 | 25-APR-15:20 | 33.00 | 15.00 | 0.00 | 0.00 | 01-APR-00:10 | 33.00 | 15.00 |
May | 0.730504E+10 | 7268.65 | 08-MAY-16:00 | 34.00 | 13.77 | 0.00 | 0.00 | 01-MAY-00:10 | 34.00 | 13.77 |
June | 0.970512E+10 | 9256.13 | 26-JUN-05:02 | 22.17 | 10.13 | 0.00 | 0.00 | 01-JUN-00:10 | 22.17 | 10.13 |
July | 0.893617E+10 | 9330.74 | 31-JUL-05:02 | 25.83 | 15.57 | 0.00 | 0.00 | 01-JUL-00:10 | 25.83 | 15.57 |
August | 0.897126E+10 | 12726.75 | 28-AUG-05:13 | 28.67 | 19.85 | 0.00 | 0.00 | 01-AUG-00:10 | 28.67 | 19.85 |
September | 0.745724E+10 | 11033.67 | 11-SEP-05:13 | 22.33 | 18.20 | 0.00 | 0.00 | 01-SEP-00:10 | 22.33 | 18.20 |
October | 0.459554E+10 | 8206.53 | 02-OCT-05:15 | 25.67 | 16.91 | 0.00 | 0.00 | 01-OCT-00:10 | 25.67 | 16.91 |
November | 0.206311E+10 | 4153.71 | 02-NOV-16:00 | 26.00 | 15.13 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 15.13 |
December | 0.874159E+09 | 6871.86 | 06-DEC-06:01 | 0.67 | -4.3 | 0.00 | 0.00 | 01-DEC-00:10 | 0.67 | -4.3 |
Annual Sum or Average | 0.597370E+11 | 0.00 | ||||||||
Minimum of Months | 0.874159E+09 | 2769.67 | 0.67 | -4.3 | 0.00 | 0.00 | 0.67 | -4.3 | ||
Maximum of Months | 0.970512E+10 | 12726.75 | 34.00 | 19.85 | 0.00 | 0.00 | 34.00 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215031E+10 | 7894.60 | 31-JAN-16:00 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.117331E+10 | 7028.59 | 23-FEB-14:50 | 18.00 | 10.42 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.42 |
March | 0.327178E+10 | 11427.64 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.105574E+11 | 18757.82 | 14-APR-15:10 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.137495E+11 | 19213.23 | 19-MAY-14:00 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.194628E+11 | 23511.31 | 28-JUN-14:40 | 41.67 | 19.29 | 0.00 | 0.00 | 01-JUN-00:10 | 41.67 | 19.29 |
July | 0.171804E+11 | 21963.61 | 20-JUL-14:20 | 39.33 | 20.22 | 0.00 | 0.00 | 01-JUL-00:10 | 39.33 | 20.22 |
August | 0.167195E+11 | 21600.07 | 15-AUG-15:10 | 39.00 | 18.89 | 0.00 | 0.00 | 01-AUG-00:10 | 39.00 | 18.89 |
September | 0.124500E+11 | 19151.64 | 07-SEP-15:20 | 37.37 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.37 | 19.77 |
October | 0.662898E+10 | 16743.72 | 02-OCT-14:30 | 35.00 | 19.50 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.50 |
November | 0.256405E+10 | 10483.54 | 01-NOV-15:20 | 28.67 | 16.04 | 0.00 | 0.00 | 01-NOV-00:10 | 28.67 | 16.04 |
December | 0.899862E+09 | 5812.52 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.106808E+12 | 0.00 | ||||||||
Minimum of Months | 0.899862E+09 | 5812.52 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.194628E+11 | 23511.31 | 41.67 | 20.22 | 0.00 | 0.00 | 41.67 | 20.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402345E+10 | 2251.76 | 29-JAN-17:15 | 23.00 | 8.84 | 95230212.02 | 126.83 | 09-JAN-10:00 | 23.00 | 8.84 |
February | 0.812628E+10 | 3998.12 | 27-FEB-17:40 | 15.67 | 8.53 | 86398612.04 | 126.84 | 16-FEB-10:00 | 15.67 | 8.53 |
March | 0.143101E+11 | 7130.65 | 31-MAR-24:00 | 15.30 | 7.49 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.30 | 7.49 |
April | 0.184512E+11 | 7727.90 | 26-APR-18:50 | 19.33 | 9.57 | 99038422.27 | 158.56 | 24-APR-13:00 | 19.33 | 9.57 |
May | 0.462078E+10 | 3479.52 | 31-MAY-24:00 | 26.00 | 10.61 | 99233117.00 | 126.82 | 01-MAY-13:50 | 26.00 | 10.61 |
June | 0.945930E+10 | 5411.70 | 30-JUN-23:55 | 28.10 | 15.37 | 98957378.90 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.148125E+11 | 7321.59 | 31-JUL-23:57 | 29.60 | 17.96 | 91884255.32 | 126.84 | 18-JUL-09:09 | 29.60 | 17.96 |
August | 0.195009E+11 | 7749.00 | 21-AUG-00:40 | 26.00 | 16.49 | 0.111834E+09 | 168.58 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.450136E+10 | 3486.33 | 30-SEP-23:40 | 25.30 | 15.38 | 91611992.29 | 126.85 | 01-SEP-09:00 | 25.30 | 15.38 |
October | 0.954668E+10 | 5301.77 | 31-OCT-24:00 | 17.10 | 9.96 | 95231163.09 | 126.84 | 03-OCT-09:00 | 17.10 | 9.96 |
November | 0.139845E+11 | 6242.48 | 26-NOV-16:57 | 18.00 | 8.58 | 94301936.18 | 126.84 | 13-NOV-10:09 | 18.00 | 8.58 |
December | 0.192719E+11 | 7838.77 | 28-DEC-17:00 | 18.60 | 7.88 | 92161169.16 | 135.00 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.140609E+12 | 0.115912E+10 | ||||||||
Minimum of Months | 0.402345E+10 | 2251.76 | 15.30 | 7.49 | 86398612.04 | 126.82 | 15.30 | 7.49 | ||
Maximum of Months | 0.195009E+11 | 7838.77 | 29.60 | 17.96 | 0.111834E+09 | 168.58 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288550E+10 | 1984.64 | 29-JAN-17:27 | 22.50 | 8.59 | 95230204.25 | 126.83 | 09-JAN-10:00 | 22.50 | 8.59 |
February | 0.682659E+10 | 3743.47 | 27-FEB-17:50 | 15.33 | 8.42 | 86398538.07 | 126.84 | 16-FEB-10:00 | 15.33 | 8.42 |
March | 0.129920E+11 | 6659.51 | 31-MAR-23:50 | 15.32 | 7.32 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.32 | 7.32 |
April | 0.174571E+11 | 7366.28 | 26-APR-18:50 | 19.33 | 9.57 | 97826778.45 | 154.48 | 24-APR-13:00 | 19.33 | 9.57 |
May | 0.425201E+10 | 3379.50 | 31-MAY-24:00 | 26.00 | 10.61 | 99233117.17 | 126.82 | 08-MAY-09:09 | 26.00 | 10.61 |
June | 0.899820E+10 | 5200.96 | 30-JUN-23:40 | 28.87 | 14.96 | 98957378.79 | 126.83 | 30-JUN-09:00 | 28.87 | 14.96 |
July | 0.140732E+11 | 6998.93 | 31-JUL-23:57 | 29.60 | 17.96 | 91883924.03 | 126.83 | 14-JUL-09:09 | 29.60 | 17.96 |
August | 0.183551E+11 | 7239.95 | 20-AUG-21:03 | 28.83 | 16.12 | 0.109898E+09 | 163.25 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.410244E+10 | 3396.86 | 30-SEP-24:00 | 25.20 | 15.49 | 91610940.24 | 126.85 | 11-SEP-13:00 | 25.20 | 15.49 |
October | 0.866021E+10 | 4898.82 | 31-OCT-24:00 | 17.10 | 9.96 | 95231127.10 | 126.84 | 03-OCT-09:00 | 17.10 | 9.96 |
November | 0.125816E+11 | 5730.83 | 14-NOV-17:00 | 19.00 | 14.11 | 94301841.24 | 126.84 | 13-NOV-14:00 | 19.00 | 14.11 |
December | 0.172135E+11 | 7374.71 | 28-DEC-17:00 | 18.60 | 7.88 | 92002083.34 | 132.59 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.128397E+12 | 0.115581E+10 | ||||||||
Minimum of Months | 0.288550E+10 | 1984.64 | 15.32 | 7.32 | 86398538.07 | 126.82 | 15.32 | 7.32 | ||
Maximum of Months | 0.183551E+11 | 7374.71 | 29.60 | 17.96 | 0.109898E+09 | 163.25 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197607E+10 | 1984.38 | 24-JAN-17:00 | 24.00 | 10.79 | 95081957.00 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.577232E+10 | 3707.52 | 27-FEB-17:50 | 15.33 | 8.42 | 86398533.98 | 126.84 | 16-FEB-10:00 | 15.33 | 8.42 |
March | 0.123013E+11 | 6482.20 | 31-MAR-23:20 | 15.37 | 6.81 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.37 | 6.81 |
April | 0.174926E+11 | 7479.12 | 26-APR-18:30 | 20.00 | 9.88 | 96889255.07 | 154.44 | 24-APR-13:00 | 20.00 | 9.88 |
May | 0.428889E+10 | 3391.62 | 31-MAY-24:00 | 26.00 | 10.61 | 99233117.32 | 126.82 | 10-MAY-09:09 | 26.00 | 10.61 |
June | 0.915712E+10 | 5258.28 | 30-JUN-23:40 | 28.87 | 14.96 | 98957380.94 | 126.83 | 30-JUN-09:00 | 28.87 | 14.96 |
July | 0.142506E+11 | 7046.17 | 31-JUL-23:57 | 29.60 | 17.96 | 91885189.05 | 126.84 | 14-JUL-09:00 | 29.60 | 17.96 |
August | 0.185356E+11 | 7432.76 | 20-AUG-21:03 | 28.83 | 16.12 | 0.108886E+09 | 163.57 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.417722E+10 | 3427.60 | 30-SEP-23:55 | 25.20 | 15.49 | 91611453.52 | 126.85 | 05-SEP-13:09 | 25.20 | 15.49 |
October | 0.827582E+10 | 4701.75 | 31-OCT-23:40 | 16.87 | 9.55 | 95231156.81 | 126.84 | 03-OCT-09:00 | 16.87 | 9.55 |
November | 0.116975E+11 | 5745.67 | 21-NOV-17:00 | 24.00 | 10.76 | 94301906.79 | 126.84 | 13-NOV-10:09 | 24.00 | 10.76 |
December | 0.157871E+11 | 7361.13 | 26-DEC-17:00 | 23.00 | 10.75 | 91917634.26 | 129.17 | 22-DEC-16:00 | 23.00 | 10.75 |
Annual Sum or Average | 0.123712E+12 | 0.115363E+10 | ||||||||
Minimum of Months | 0.197607E+10 | 1984.38 | 15.33 | 6.81 | 86398533.98 | 126.82 | 15.33 | 6.81 | ||
Maximum of Months | 0.185356E+11 | 7479.12 | 29.60 | 17.96 | 0.108886E+09 | 163.57 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239231E+12 | 91777.86 | 17-JAN-17:00 | 24.00 | 9.10 | 0.206145E+10 | 2745.41 | 02-JAN-14:09 | 24.00 | 9.10 |
February | 0.434388E+12 | 182324.46 | 21-FEB-17:00 | 19.00 | 10.37 | 0.187024E+10 | 2746.83 | 17-FEB-14:00 | 19.00 | 10.37 |
March | 0.726192E+12 | 357664.50 | 31-MAR-24:00 | 15.30 | 7.49 | 0.223501E+10 | 2748.84 | 16-MAR-13:00 | 15.30 | 7.49 |
April | 0.933773E+12 | 378773.76 | 03-APR-21:02 | 22.83 | 9.11 | 0.248213E+10 | 4976.80 | 14-APR-13:00 | 34.00 | 14.07 |
May | 0.239771E+12 | 175299.38 | 31-MAY-24:00 | 26.00 | 10.61 | 0.214826E+10 | 2747.13 | 15-MAY-13:00 | 26.00 | 10.61 |
June | 0.468447E+12 | 267153.91 | 30-JUN-24:00 | 28.10 | 15.37 | 0.214272E+10 | 2748.03 | 22-JUN-09:09 | 28.10 | 15.37 |
July | 0.731504E+12 | 356247.01 | 31-JUL-23:13 | 30.33 | 18.19 | 0.200132E+10 | 3309.84 | 14-JUL-09:00 | 30.33 | 18.19 |
August | 0.962478E+12 | 386151.65 | 23-AUG-22:53 | 24.00 | 10.56 | 0.309507E+10 | 5027.92 | 23-AUG-13:09 | 24.00 | 10.56 |
September | 0.237597E+12 | 177021.24 | 30-SEP-23:55 | 25.20 | 15.49 | 0.198321E+10 | 2746.81 | 15-SEP-09:09 | 25.20 | 15.49 |
October | 0.488490E+12 | 268682.19 | 31-OCT-24:00 | 17.10 | 9.96 | 0.206169E+10 | 2748.14 | 16-OCT-13:00 | 17.10 | 9.96 |
November | 0.709201E+12 | 276298.07 | 20-NOV-17:00 | 26.00 | 12.00 | 0.204173E+10 | 2751.10 | 13-NOV-10:09 | 26.00 | 12.00 |
December | 0.976961E+12 | 370243.00 | 25-DEC-16:32 | 24.67 | 11.46 | 0.199488E+10 | 3129.46 | 22-DEC-14:00 | 24.67 | 11.46 |
Annual Sum or Average | 0.714803E+13 | 0.261177E+11 | ||||||||
Minimum of Months | 0.237597E+12 | 91777.86 | 15.30 | 7.49 | 0.187024E+10 | 2745.41 | 15.30 | 7.49 | ||
Maximum of Months | 0.976961E+12 | 386151.65 | 30.33 | 18.19 | 0.309507E+10 | 5027.92 | 34.00 | 18.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328228E+09 | 11584.89 | 16-JAN-15:32 | 24.00 |
February | 0.158999E+09 | 10921.55 | 28-FEB-05:15 | 5.00 |
March | 0.126869E+09 | 12520.52 | 18-MAR-16:01 | 27.20 |
April | 0.356643E+09 | 19492.80 | 29-APR-16:01 | 32.67 |
May | 0.361294E+09 | 22365.86 | 20-MAY-16:01 | 34.83 |
June | 0.378758E+09 | 29309.62 | 17-JUN-16:02 | 40.50 |
July | 0.580139E+09 | 26462.75 | 22-JUL-16:01 | 38.00 |
August | 0.443088E+09 | 29878.36 | 26-AUG-16:01 | 40.83 |
September | 0.648975E+09 | 21644.12 | 23-SEP-16:01 | 34.30 |
October | 0.424998E+09 | 17254.72 | 14-OCT-16:01 | 31.00 |
November | 0.293623E+09 | 10939.72 | 18-NOV-05:17 | 6.67 |
December | 0.296409E+09 | 10823.32 | 26-DEC-05:16 | 8.33 |
Annual Sum or Average | 0.439802E+10 | |||
Minimum of Months | 0.126869E+09 | 10823.32 | 5.00 | |
Maximum of Months | 0.648975E+09 | 29878.36 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240570E+09 | 66061.06 | 02-JAN-05:11 | 4.00 |
February | 25937055.87 | 59030.10 | 13-FEB-06:03 | 8.00 |
March | 7237831.15 | 48252.21 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 7937100.03 | 57731.42 | 24-NOV-06:02 | 3.17 |
December | 0.132227E+09 | 61679.84 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.413909E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.240570E+09 | 66061.06 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 117861.27 | 1375.05 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 117861.27 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 117861.27 | 1375.05 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64549860.04 | 13619.30 | 02-JAN-05:11 | 4.00 |
February | 18896398.91 | 10369.81 | 03-FEB-06:02 | 6.83 |
March | 32561792.77 | 12734.55 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 19980397.22 | 12609.64 | 24-NOV-05:11 | 3.67 |
December | 0.222072E+09 | 13126.56 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.358061E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.222072E+09 | 13619.30 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24138268.55 | 11920.64 | 02-JAN-05:11 | 4.00 |
February | 3646590.20 | 6553.58 | 13-FEB-06:03 | 8.00 |
March | 8481903.53 | 8055.47 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 4966466.48 | 10710.39 | 24-NOV-06:02 | 3.17 |
December | 86808030.12 | 11562.95 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.128041E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 86808030.12 | 11920.64 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6761117.20 | 12365.75 | 02-JAN-06:03 | 4.33 |
February | 3735583.24 | 8727.38 | 13-FEB-06:03 | 8.00 |
March | 4824976.39 | 11021.51 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 35131992.31 | 13651.96 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 50453669.13 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 35131992.31 | 13651.96 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10180247.68 | 8368.03 | 02-JAN-06:03 | 4.33 |
February | 1023639.56 | 3329.10 | 13-FEB-06:03 | 8.00 |
March | 987140.81 | 5086.86 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 1426594.59 | 5296.40 | 24-NOV-06:02 | 3.17 |
December | 50240762.04 | 10448.83 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 63858384.68 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 50240762.04 | 10448.83 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.571047E+09 | 17301.19 | 02-JAN-05:11 | 4.00 |
February | 0.460498E+09 | 15854.58 | 13-FEB-05:11 | 8.00 |
March | 0.306323E+09 | 16352.48 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 51720536.86 | 14059.67 | 26-OCT-05:02 | 7.17 |
November | 0.347468E+09 | 16620.66 | 24-NOV-05:11 | 3.67 |
December | 0.135860E+10 | 17324.02 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.309566E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.135860E+10 | 17324.02 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217990E+09 | 15677.98 | 02-JAN-05:11 | 4.00 |
February | 0.184052E+09 | 14196.23 | 13-FEB-05:11 | 8.00 |
March | 0.124526E+09 | 14255.70 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 16036779.96 | 10216.96 | 26-OCT-05:02 | 7.17 |
November | 0.126090E+09 | 14731.95 | 24-NOV-05:11 | 3.67 |
December | 0.561211E+09 | 15436.87 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.122991E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.561211E+09 | 15677.98 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111013E+09 | 17784.25 | 02-JAN-05:11 | 4.00 |
February | 0.158806E+09 | 17319.79 | 13-FEB-05:11 | 8.00 |
March | 0.154884E+09 | 16743.30 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 7586806.25 | 10455.76 | 26-OCT-05:02 | 7.17 |
November | 76083468.47 | 16604.20 | 24-NOV-05:11 | 3.67 |
December | 0.474509E+09 | 17533.32 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.982883E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.474509E+09 | 17784.25 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105499E+09 | 15415.18 | 02-JAN-05:11 | 4.00 |
February | 0.104103E+09 | 13969.33 | 13-FEB-05:11 | 8.00 |
March | 59240339.91 | 13749.71 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 3462033.04 | 6809.62 | 26-OCT-05:02 | 7.17 |
November | 63391893.38 | 14283.03 | 24-NOV-05:11 | 3.67 |
December | 0.407170E+09 | 15212.41 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.742866E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.407170E+09 | 15415.18 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106667E+09 | 8337.25 | 29-JAN-16:22 | 24.50 |
February | 76045829.71 | 8980.49 | 13-FEB-05:11 | 8.00 |
March | 95228159.06 | 8750.78 | 27-MAR-04:11 | 2.37 |
April | 0.108724E+09 | 10705.99 | 23-APR-15:41 | 33.25 |
May | 66693398.33 | 8822.03 | 07-MAY-15:41 | 35.83 |
June | 49909561.46 | 8472.61 | 25-JUN-17:21 | 38.00 |
July | 75928250.95 | 9131.65 | 30-JUL-16:21 | 38.00 |
August | 94670295.89 | 9156.39 | 27-AUG-15:41 | 40.00 |
September | 57309452.53 | 7605.08 | 10-SEP-14:01 | 35.18 |
October | 91533007.04 | 8333.82 | 15-OCT-14:01 | 31.00 |
November | 0.134838E+09 | 8915.31 | 24-NOV-05:11 | 3.67 |
December | 0.166807E+09 | 10495.20 | 11-DEC-05:11 | 8.33 |
Annual Sum or Average | 0.112435E+10 | |||
Minimum of Months | 49909561.46 | 7605.08 | 2.37 | |
Maximum of Months | 0.166807E+09 | 10705.99 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351552E+09 | 7915.85 | 01-JAN-13:33 | 14.17 |
February | 0.181234E+09 | 5547.70 | 10-FEB-06:02 | 16.00 |
March | 77769427.52 | 5864.52 | 09-MAR-06:02 | 10.00 |
April | 63828385.84 | 9102.09 | 30-APR-15:51 | 33.00 |
May | 59582334.41 | 9254.21 | 07-MAY-15:41 | 35.83 |
June | 56628800.29 | 8776.70 | 25-JUN-17:21 | 38.00 |
July | 75093637.78 | 9264.94 | 30-JUL-16:11 | 38.00 |
August | 51440271.70 | 8975.61 | 27-AUG-15:41 | 40.00 |
September | 50352651.59 | 7880.74 | 10-SEP-14:01 | 35.18 |
October | 61904664.50 | 7568.00 | 15-OCT-15:32 | 31.00 |
November | 85443239.91 | 8877.20 | 19-NOV-14:51 | 27.00 |
December | 0.401724E+09 | 7532.26 | 25-DEC-16:32 | 24.67 |
Annual Sum or Average | 0.151655E+10 | |||
Minimum of Months | 50352651.59 | 5547.70 | 10.00 | |
Maximum of Months | 0.401724E+09 | 9264.94 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178739E+10 | 17339.91 | 02-JAN-06:03 | 4.33 |
February | 0.149069E+10 | 9025.43 | 13-FEB-06:03 | 8.00 |
March | 0.135415E+10 | 12353.64 | 18-MAR-05:02 | 11.78 |
April | 0.407584E+09 | 13262.62 | 27-APR-05:03 | 12.00 |
May | 0.172430E+09 | 11676.33 | 01-MAY-04:13 | 12.33 |
June | 40892009.70 | 11464.03 | 12-JUN-04:12 | 20.00 |
July | 30980446.96 | 12345.31 | 03-JUL-04:11 | 20.67 |
August | 30397253.94 | 8603.64 | 25-AUG-04:12 | 22.00 |
September | 49922668.26 | 10192.12 | 22-SEP-05:02 | 17.10 |
October | 0.738379E+09 | 12194.32 | 18-OCT-05:03 | 15.83 |
November | 0.121731E+10 | 12111.95 | 24-NOV-06:02 | 3.17 |
December | 0.262409E+10 | 15777.80 | 18-DEC-06:03 | 3.83 |
Annual Sum or Average | 0.994421E+10 | |||
Minimum of Months | 30397253.94 | 8603.64 | 3.17 | |
Maximum of Months | 0.262409E+10 | 17339.91 | 22.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7608069.16 | 400.28 | 01-JAN-01:43 | 4.77 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 7608069.16 | |||
Minimum of Months | 0.00 | 0.00 | 4.77 | |
Maximum of Months | 7608069.16 | 400.28 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78093589.79 | 578.44 | 01-JAN-01:35 | 4.93 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 78093589.79 | |||
Minimum of Months | 0.00 | 0.00 | 4.93 | |
Maximum of Months | 78093589.79 | 578.44 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102471E+11 | 10780.55 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.929489E+10 | 10780.55 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.110442E+11 | 10780.55 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.986550E+10 | 10780.55 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.106457E+11 | 10780.55 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.105939E+11 | 10780.55 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.991722E+10 | 10780.55 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.110442E+11 | 10780.55 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.986550E+10 | 10780.55 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.102471E+11 | 10780.55 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.101268E+11 | 10780.55 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.991722E+10 | 10780.55 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.122809E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.929489E+10 | 10780.55 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.110442E+11 | 10780.55 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.920263E+10 | 9681.69 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.834746E+10 | 9681.69 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.991846E+10 | 9681.69 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.885991E+10 | 9681.69 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.956054E+10 | 9681.69 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.951409E+10 | 9681.69 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.890636E+10 | 9681.69 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.991846E+10 | 9681.69 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.885991E+10 | 9681.69 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.920263E+10 | 9681.69 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.909454E+10 | 9681.69 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.890636E+10 | 9681.69 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.110291E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.834746E+10 | 9681.69 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.991846E+10 | 9681.69 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.920263E+10 | 9681.69 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.834746E+10 | 9681.69 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.991846E+10 | 9681.69 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.885991E+10 | 9681.69 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.956054E+10 | 9681.69 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.951409E+10 | 9681.69 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.890636E+10 | 9681.69 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.991846E+10 | 9681.69 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.885991E+10 | 9681.69 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.920263E+10 | 9681.69 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.909454E+10 | 9681.69 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.890636E+10 | 9681.69 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.110291E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.834746E+10 | 9681.69 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.991846E+10 | 9681.69 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.920263E+10 | 9681.69 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.834746E+10 | 9681.69 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.991846E+10 | 9681.69 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.885991E+10 | 9681.69 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.956054E+10 | 9681.69 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.951409E+10 | 9681.69 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.890636E+10 | 9681.69 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.991846E+10 | 9681.69 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.885991E+10 | 9681.69 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.920263E+10 | 9681.69 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.909454E+10 | 9681.69 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.890636E+10 | 9681.69 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.110291E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.834746E+10 | 9681.69 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.991846E+10 | 9681.69 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718133E+09 | 1085.02 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.636280E+09 | 1012.06 | 03-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.706290E+09 | 944.32 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.610911E+09 | 649.85 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.644503E+09 | 623.27 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.627659E+09 | 578.40 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.596494E+09 | 639.81 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.681215E+09 | 954.74 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.624091E+09 | 832.06 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.683706E+09 | 1041.68 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.700817E+09 | 1215.63 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.709588E+09 | 1215.63 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.793969E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.596494E+09 | 578.40 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.718133E+09 | 1215.63 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.446680E+09 | 692.60 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.400674E+09 | 626.74 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.451058E+09 | 430.89 | 08-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.391480E+09 | 372.74 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.416886E+09 | 372.74 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.406706E+09 | 372.74 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.387060E+09 | 418.26 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.438122E+09 | 596.81 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.400011E+09 | 415.88 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.428725E+09 | 501.29 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.440924E+09 | 783.40 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.443401E+09 | 783.40 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.505173E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.387060E+09 | 372.74 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.451058E+09 | 783.40 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681924E+09 | 1058.44 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.615179E+09 | 991.24 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.697427E+09 | 904.70 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.613245E+09 | 655.35 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.651201E+09 | 623.27 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.635967E+09 | 613.47 | 27-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.604684E+09 | 643.62 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.685097E+09 | 960.02 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.621981E+09 | 662.71 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.658365E+09 | 904.37 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.674161E+09 | 1215.66 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.675090E+09 | 1215.66 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.781432E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.604684E+09 | 613.47 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.697427E+09 | 1215.66 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.453678E+09 | 708.15 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.404858E+09 | 656.38 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.453323E+09 | 661.86 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.393924E+09 | 513.39 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.418283E+09 | 416.27 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.407663E+09 | 397.11 | 27-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.387863E+09 | 417.01 | 24-JUL-08:20 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.440417E+09 | 626.57 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.402208E+09 | 589.24 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.434227E+09 | 681.53 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.443601E+09 | 783.40 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.447735E+09 | 783.40 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.508778E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.387863E+09 | 397.11 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.453678E+09 | 783.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.715193E+09 | 1082.84 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.634075E+09 | 1008.68 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.704549E+09 | 940.42 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.610264E+09 | 643.13 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.644329E+09 | 616.10 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.627497E+09 | 578.40 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.596115E+09 | 633.58 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.680256E+09 | 951.76 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.623236E+09 | 826.51 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.681061E+09 | 1038.83 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.698260E+09 | 1215.63 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.706551E+09 | 1215.63 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.792139E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.596115E+09 | 578.40 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.715193E+09 | 1215.63 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.446165E+09 | 690.24 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.399907E+09 | 622.95 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.450668E+09 | 428.03 | 08-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.391372E+09 | 372.74 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.416693E+09 | 372.74 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.406440E+09 | 372.74 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.386589E+09 | 414.69 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.437569E+09 | 592.60 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.399738E+09 | 412.16 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.427995E+09 | 490.94 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.440269E+09 | 783.40 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.442577E+09 | 783.40 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.504598E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.386589E+09 | 372.74 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.450668E+09 | 783.40 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681766E+09 | 1056.79 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.614665E+09 | 988.71 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.696744E+09 | 900.51 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.612630E+09 | 649.13 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.650659E+09 | 616.10 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.635296E+09 | 578.41 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.603790E+09 | 636.46 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.684072E+09 | 957.08 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.621326E+09 | 657.78 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.656908E+09 | 864.70 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.673553E+09 | 1215.66 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.674874E+09 | 1215.66 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.780628E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.603790E+09 | 578.41 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.696744E+09 | 1215.66 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.452427E+09 | 706.42 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.403744E+09 | 653.07 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.452513E+09 | 658.50 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.393601E+09 | 507.43 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.417916E+09 | 412.61 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.407363E+09 | 372.74 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.387341E+09 | 413.23 | 24-JUL-08:20 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.439742E+09 | 622.46 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.401690E+09 | 583.99 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.433248E+09 | 679.43 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.442703E+09 | 783.40 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.446687E+09 | 783.40 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.507898E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.387341E+09 | 372.74 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.452513E+09 | 783.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.715162E+09 | 1082.67 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.634038E+09 | 1008.25 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.704461E+09 | 939.97 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.610256E+09 | 643.00 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.644325E+09 | 615.81 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.627496E+09 | 578.40 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.596099E+09 | 633.33 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.680238E+09 | 951.21 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.623188E+09 | 825.83 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.681013E+09 | 1038.74 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.698229E+09 | 1215.63 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.706494E+09 | 1215.63 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.792100E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.596099E+09 | 578.40 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.715162E+09 | 1215.63 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.446158E+09 | 690.05 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.399879E+09 | 622.65 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.450651E+09 | 427.93 | 08-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.391366E+09 | 372.74 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.416690E+09 | 372.74 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.406433E+09 | 372.74 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.386553E+09 | 414.55 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.437562E+09 | 592.23 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.399726E+09 | 412.04 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.427969E+09 | 490.88 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.440252E+09 | 783.40 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.442568E+09 | 783.40 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.504581E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.386553E+09 | 372.74 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.450651E+09 | 783.40 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681741E+09 | 1056.47 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.614649E+09 | 988.26 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.696722E+09 | 900.01 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.612602E+09 | 649.01 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.650649E+09 | 615.81 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.635287E+09 | 578.41 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.603772E+09 | 636.35 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.684046E+09 | 956.54 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.621313E+09 | 657.62 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.656903E+09 | 864.39 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.673546E+09 | 1215.66 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.674869E+09 | 1215.66 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.780610E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.603772E+09 | 578.41 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.696722E+09 | 1215.66 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.452380E+09 | 706.32 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.403727E+09 | 652.80 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.452501E+09 | 658.29 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.393597E+09 | 507.37 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.417899E+09 | 412.47 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.407364E+09 | 372.74 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.387339E+09 | 413.12 | 24-JUL-08:20 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.439728E+09 | 622.12 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.401667E+09 | 583.63 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.433240E+09 | 679.33 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.442693E+09 | 783.40 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.446640E+09 | 783.40 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.507877E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.387339E+09 | 372.74 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.452501E+09 | 783.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148158E+09 | 155.04 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.134390E+09 | 155.04 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.159693E+09 | 155.04 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.142638E+09 | 155.04 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.153925E+09 | 155.04 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.153181E+09 | 155.04 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.143382E+09 | 155.04 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.159693E+09 | 155.04 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.142638E+09 | 155.04 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.148158E+09 | 155.04 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.146421E+09 | 155.04 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.143382E+09 | 155.04 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.177566E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.134390E+09 | 155.04 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.159693E+09 | 155.04 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148158E+09 | 155.04 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.134390E+09 | 155.04 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.159693E+09 | 155.04 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.142638E+09 | 155.04 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.153925E+09 | 155.04 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.153181E+09 | 155.04 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.143382E+09 | 155.04 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.159693E+09 | 155.04 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.142638E+09 | 155.04 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.148158E+09 | 155.04 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.146421E+09 | 155.04 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.143382E+09 | 155.04 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.177566E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.134390E+09 | 155.04 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.159693E+09 | 155.04 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148158E+09 | 155.04 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.134390E+09 | 155.04 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.159693E+09 | 155.04 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.142638E+09 | 155.04 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.153925E+09 | 155.04 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.153181E+09 | 155.04 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.143382E+09 | 155.04 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.159693E+09 | 155.04 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.142638E+09 | 155.04 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.148158E+09 | 155.04 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.146421E+09 | 155.04 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.143382E+09 | 155.04 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.177566E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.134390E+09 | 155.04 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.159693E+09 | 155.04 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.290468E+10 | 3039.65 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.263476E+10 | 3039.65 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.313083E+10 | 3039.65 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.279647E+10 | 3039.65 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.301776E+10 | 3039.65 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.300317E+10 | 3039.65 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.281106E+10 | 3039.65 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.313083E+10 | 3039.65 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.279647E+10 | 3039.65 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.290468E+10 | 3039.65 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.287064E+10 | 3039.65 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.281106E+10 | 3039.65 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.348124E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.263476E+10 | 3039.65 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.313083E+10 | 3039.65 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.102471E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.929489E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.110442E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.986550E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.106457E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.105939E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.991722E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.110442E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.986550E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.102471E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.101268E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.991722E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.122809E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.929489E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.110442E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.920263E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.991846E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.885991E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.956054E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.951409E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.890636E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.991846E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.885991E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.920263E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.909454E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.890636E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.110291E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.991846E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.920263E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.885991E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.956054E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.951409E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.890636E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.885991E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.920263E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.909454E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.890636E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.110291E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.920263E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.885991E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.956054E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.951409E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.890636E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.885991E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.920263E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.909454E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.890636E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.110291E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.718133E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1035987.10 | 0.333847E+09 |
February | 0.136985E+10 | 0.636280E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266882E+09 |
March | 0.163685E+10 | 0.706290E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2865097.92 | 0.341098E+09 |
April | 0.145243E+10 | 0.610911E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51201616.08 | 0.105373E+09 |
May | 0.157338E+10 | 0.644503E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100486E+09 | 67980584.88 |
June | 0.156900E+10 | 0.627659E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185656E+09 | 15317072.71 |
July | 0.145680E+10 | 0.596494E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184277E+09 | 12436080.98 |
August | 0.163685E+10 | 0.681215E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128173E+09 | 19419555.39 |
September | 0.145243E+10 | 0.624091E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97174995.43 | 44007236.56 |
October | 0.150991E+10 | 0.683706E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34203461.23 | 0.172175E+09 |
November | 0.149516E+10 | 0.700817E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2706170.06 | 0.304884E+09 |
December | 0.145680E+10 | 0.709588E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 183235.25 | 0.328164E+09 |
Annual Sum or Average | 0.181194E+11 | 0.793969E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787963E+09 | 0.201158E+10 |
Minimum of Months | 0.136985E+10 | 0.596494E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12436080.98 |
Maximum of Months | 0.163685E+10 | 0.718133E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185656E+09 | 0.341098E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.446680E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644811.49 | 0.229026E+09 |
February | 0.882782E+09 | 0.400674E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178789E+09 |
March | 0.105485E+10 | 0.451058E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1846991.73 | 0.227626E+09 |
April | 0.936002E+09 | 0.391480E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33636849.50 | 70652939.65 |
May | 0.101394E+10 | 0.416886E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64816450.87 | 47139034.26 |
June | 0.101113E+10 | 0.406706E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123559E+09 | 10245154.01 |
July | 0.938820E+09 | 0.387060E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123382E+09 | 8005074.42 |
August | 0.105485E+10 | 0.438122E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86995183.24 | 11630509.13 |
September | 0.936002E+09 | 0.400011E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63526798.63 | 29827371.66 |
October | 0.973041E+09 | 0.428725E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21757141.88 | 0.116499E+09 |
November | 0.963541E+09 | 0.440924E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1441518.10 | 0.203765E+09 |
December | 0.938820E+09 | 0.443401E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85657.12 | 0.217660E+09 |
Annual Sum or Average | 0.116768E+11 | 0.505173E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521692E+09 | 0.135086E+10 |
Minimum of Months | 0.882782E+09 | 0.387060E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8005074.42 |
Maximum of Months | 0.105485E+10 | 0.451058E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123559E+09 | 0.229026E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.681924E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 870178.86 | 0.362572E+09 |
February | 0.136988E+10 | 0.615179E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273881E+09 |
March | 0.163688E+10 | 0.697427E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2622412.33 | 0.349154E+09 |
April | 0.145246E+10 | 0.613245E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48430319.06 | 0.109880E+09 |
May | 0.157341E+10 | 0.651201E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99063269.23 | 68245893.79 |
June | 0.156904E+10 | 0.635967E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187188E+09 | 14886364.30 |
July | 0.145684E+10 | 0.604684E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184175E+09 | 12259234.74 |
August | 0.163688E+10 | 0.685097E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126261E+09 | 20030767.48 |
September | 0.145246E+10 | 0.621981E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92145375.07 | 48209482.75 |
October | 0.150994E+10 | 0.658365E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30587029.73 | 0.185292E+09 |
November | 0.149520E+10 | 0.674161E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1562291.17 | 0.323602E+09 |
December | 0.145684E+10 | 0.675090E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72640.53 | 0.344153E+09 |
Annual Sum or Average | 0.181198E+11 | 0.781432E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772979E+09 | 0.211216E+10 |
Minimum of Months | 0.136988E+10 | 0.604684E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12259234.74 |
Maximum of Months | 0.163688E+10 | 0.697427E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187188E+09 | 0.362572E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.453678E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644138.52 | 0.248400E+09 |
February | 0.882782E+09 | 0.404858E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199376E+09 |
March | 0.105485E+10 | 0.453323E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1729589.00 | 0.262192E+09 |
April | 0.936002E+09 | 0.393924E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29811968.09 | 92985370.81 |
May | 0.101394E+10 | 0.418283E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61076442.89 | 56625509.09 |
June | 0.101113E+10 | 0.407663E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115850E+09 | 15159779.50 |
July | 0.938820E+09 | 0.387863E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112736E+09 | 14524262.90 |
August | 0.105485E+10 | 0.440417E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76994458.75 | 23586925.79 |
September | 0.936002E+09 | 0.402208E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58373920.77 | 39104345.82 |
October | 0.973041E+09 | 0.434227E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20095671.89 | 0.136352E+09 |
November | 0.963541E+09 | 0.443601E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1148690.25 | 0.237422E+09 |
December | 0.938820E+09 | 0.447735E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58656.15 | 0.252834E+09 |
Annual Sum or Average | 0.116768E+11 | 0.508778E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478519E+09 | 0.157856E+10 |
Minimum of Months | 0.882782E+09 | 0.387863E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14524262.90 |
Maximum of Months | 0.105485E+10 | 0.453678E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115850E+09 | 0.262192E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.715193E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5751616.61 | 0.665690E+09 |
February | 0.136985E+10 | 0.634075E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540786E+09 |
March | 0.163685E+10 | 0.704549E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6964450.65 | 0.708563E+09 |
April | 0.145243E+10 | 0.610264E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125341E+09 | 0.240643E+09 |
May | 0.157338E+10 | 0.644329E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230830E+09 | 0.155856E+09 |
June | 0.156900E+10 | 0.627497E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423199E+09 | 44259529.20 |
July | 0.145680E+10 | 0.596115E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417789E+09 | 38096716.63 |
August | 0.163685E+10 | 0.680256E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296424E+09 | 52939042.05 |
September | 0.145243E+10 | 0.623236E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216781E+09 | 0.103015E+09 |
October | 0.150991E+10 | 0.681061E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83750909.13 | 0.361922E+09 |
November | 0.149516E+10 | 0.698260E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10491443.70 | 0.611153E+09 |
December | 0.145680E+10 | 0.706551E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2644897.09 | 0.645846E+09 |
Annual Sum or Average | 0.181194E+11 | 0.792139E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181997E+10 | 0.416877E+10 |
Minimum of Months | 0.136985E+10 | 0.596115E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38096716.63 |
Maximum of Months | 0.163685E+10 | 0.715193E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423199E+09 | 0.708563E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.446165E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270960.35 | 0.483552E+09 |
February | 0.649041E+09 | 0.399907E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386444E+09 |
March | 0.773965E+09 | 0.450668E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3690198.38 | 0.506273E+09 |
April | 0.688021E+09 | 0.391372E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74106289.00 | 0.179252E+09 |
May | 0.744847E+09 | 0.416693E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144572E+09 | 0.113753E+09 |
June | 0.742030E+09 | 0.406440E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276241E+09 | 32091146.69 |
July | 0.690839E+09 | 0.386589E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270703E+09 | 28456220.63 |
August | 0.773965E+09 | 0.437569E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188433E+09 | 40540666.58 |
September | 0.688021E+09 | 0.399738E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137257E+09 | 75821432.57 |
October | 0.715730E+09 | 0.427995E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47876762.93 | 0.263822E+09 |
November | 0.708685E+09 | 0.440269E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3462785.48 | 0.439216E+09 |
December | 0.690839E+09 | 0.442577E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497637.08 | 0.461291E+09 |
Annual Sum or Average | 0.858171E+10 | 0.504598E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114811E+10 | 0.301051E+10 |
Minimum of Months | 0.649041E+09 | 0.386589E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28456220.63 |
Maximum of Months | 0.773965E+09 | 0.450668E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276241E+09 | 0.506273E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.681766E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1565016.62 | 0.820200E+09 |
February | 0.136988E+10 | 0.614665E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611480E+09 |
March | 0.163688E+10 | 0.696744E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5790403.35 | 0.777653E+09 |
April | 0.145246E+10 | 0.612630E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111913E+09 | 0.261269E+09 |
May | 0.157341E+10 | 0.650659E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226931E+09 | 0.158575E+09 |
June | 0.156904E+10 | 0.635296E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427715E+09 | 42552839.09 |
July | 0.145684E+10 | 0.603790E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417954E+09 | 37467614.65 |
August | 0.163688E+10 | 0.684072E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288919E+09 | 56930541.05 |
September | 0.145246E+10 | 0.621326E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204407E+09 | 0.117830E+09 |
October | 0.150994E+10 | 0.656908E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68745897.21 | 0.424818E+09 |
November | 0.149520E+10 | 0.673553E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3254936.23 | 0.723261E+09 |
December | 0.145684E+10 | 0.674874E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 133850.78 | 0.765437E+09 |
Annual Sum or Average | 0.181198E+11 | 0.780628E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175733E+10 | 0.479747E+10 |
Minimum of Months | 0.136988E+10 | 0.603790E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37467614.65 |
Maximum of Months | 0.163688E+10 | 0.696744E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427715E+09 | 0.820200E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.452427E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1645026.67 | 0.503901E+09 |
February | 0.882782E+09 | 0.403744E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395283E+09 |
March | 0.105485E+10 | 0.452513E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3828332.53 | 0.523194E+09 |
April | 0.936002E+09 | 0.393601E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70374488.40 | 0.195391E+09 |
May | 0.101394E+10 | 0.417916E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141679E+09 | 0.124156E+09 |
June | 0.101113E+10 | 0.407363E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269979E+09 | 37146169.13 |
July | 0.938820E+09 | 0.387341E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263226E+09 | 33214689.29 |
August | 0.105485E+10 | 0.439742E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183086E+09 | 45757634.88 |
September | 0.936002E+09 | 0.401690E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134317E+09 | 82593838.09 |
October | 0.973041E+09 | 0.433248E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48094321.48 | 0.275992E+09 |
November | 0.963541E+09 | 0.442703E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3529274.96 | 0.458746E+09 |
December | 0.938820E+09 | 0.446687E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229334.67 | 0.476587E+09 |
Annual Sum or Average | 0.116768E+11 | 0.507898E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111999E+10 | 0.315196E+10 |
Minimum of Months | 0.882782E+09 | 0.387341E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33214689.29 |
Maximum of Months | 0.105485E+10 | 0.452513E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269979E+09 | 0.523194E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.715162E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10427787.76 | 0.737090E+09 |
February | 0.136985E+10 | 0.634038E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599810E+09 |
March | 0.163685E+10 | 0.704461E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8160282.12 | 0.814435E+09 |
April | 0.145243E+10 | 0.610256E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145307E+09 | 0.293883E+09 |
May | 0.157338E+10 | 0.644325E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274450E+09 | 0.193931E+09 |
June | 0.156900E+10 | 0.627496E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512939E+09 | 56703140.90 |
July | 0.145680E+10 | 0.596099E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501647E+09 | 49874275.75 |
August | 0.163685E+10 | 0.680238E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356140E+09 | 67259732.00 |
September | 0.145243E+10 | 0.623188E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259252E+09 | 0.132546E+09 |
October | 0.150991E+10 | 0.681013E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100837E+09 | 0.420418E+09 |
November | 0.149516E+10 | 0.698229E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16357602.93 | 0.680436E+09 |
December | 0.145680E+10 | 0.706494E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6000478.62 | 0.714930E+09 |
Annual Sum or Average | 0.181194E+11 | 0.792100E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219152E+10 | 0.476132E+10 |
Minimum of Months | 0.136985E+10 | 0.596099E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49874275.75 |
Maximum of Months | 0.163685E+10 | 0.715162E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512939E+09 | 0.814435E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.446158E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2338104.65 | 0.540186E+09 |
February | 0.882782E+09 | 0.399879E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433827E+09 |
March | 0.105485E+10 | 0.450651E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4695755.01 | 0.588672E+09 |
April | 0.936002E+09 | 0.391366E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89242281.70 | 0.220914E+09 |
May | 0.101394E+10 | 0.416690E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175210E+09 | 0.141920E+09 |
June | 0.101113E+10 | 0.406433E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337254E+09 | 41002539.70 |
July | 0.938820E+09 | 0.386553E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328260E+09 | 37046962.03 |
August | 0.105485E+10 | 0.437562E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228996E+09 | 51366894.76 |
September | 0.936002E+09 | 0.399726E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166426E+09 | 97046919.60 |
October | 0.973041E+09 | 0.427969E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58338644.71 | 0.310588E+09 |
November | 0.963541E+09 | 0.440252E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5412249.41 | 0.493526E+09 |
December | 0.938820E+09 | 0.442568E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1330891.31 | 0.510935E+09 |
Annual Sum or Average | 0.116768E+11 | 0.504581E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139750E+10 | 0.346703E+10 |
Minimum of Months | 0.882782E+09 | 0.386553E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37046962.03 |
Maximum of Months | 0.105485E+10 | 0.450651E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337254E+09 | 0.588672E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.681741E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2303163.13 | 0.939580E+09 |
February | 0.136988E+10 | 0.614649E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694757E+09 |
March | 0.163688E+10 | 0.696722E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6742884.73 | 0.909884E+09 |
April | 0.145246E+10 | 0.612602E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132965E+09 | 0.320731E+09 |
May | 0.157341E+10 | 0.650649E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271153E+09 | 0.197081E+09 |
June | 0.156904E+10 | 0.635287E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517173E+09 | 54587389.48 |
July | 0.145684E+10 | 0.603772E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501855E+09 | 49078867.58 |
August | 0.163688E+10 | 0.684046E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348354E+09 | 72356027.04 |
September | 0.145246E+10 | 0.621313E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246157E+09 | 0.151102E+09 |
October | 0.150994E+10 | 0.656903E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83067761.80 | 0.504753E+09 |
November | 0.149520E+10 | 0.673546E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4222241.63 | 0.832699E+09 |
December | 0.145684E+10 | 0.674869E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 192774.39 | 0.872936E+09 |
Annual Sum or Average | 0.181198E+11 | 0.780610E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211419E+10 | 0.559954E+10 |
Minimum of Months | 0.136988E+10 | 0.603772E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49078867.58 |
Maximum of Months | 0.163688E+10 | 0.696722E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517173E+09 | 0.939580E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.452380E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2491989.24 | 0.573790E+09 |
February | 0.882782E+09 | 0.403727E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451254E+09 |
March | 0.105485E+10 | 0.452501E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4482864.71 | 0.614707E+09 |
April | 0.936002E+09 | 0.393597E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84828162.50 | 0.239387E+09 |
May | 0.101394E+10 | 0.417899E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171435E+09 | 0.154099E+09 |
June | 0.101113E+10 | 0.407364E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329175E+09 | 46679355.74 |
July | 0.938820E+09 | 0.387339E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319958E+09 | 42444117.44 |
August | 0.105485E+10 | 0.439728E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222257E+09 | 57465472.32 |
September | 0.936002E+09 | 0.401667E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162404E+09 | 0.105187E+09 |
October | 0.973041E+09 | 0.433240E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58012117.26 | 0.327385E+09 |
November | 0.963541E+09 | 0.442693E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5133818.67 | 0.527084E+09 |
December | 0.938820E+09 | 0.446640E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 562072.20 | 0.542155E+09 |
Annual Sum or Average | 0.116768E+11 | 0.507877E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136074E+10 | 0.368164E+10 |
Minimum of Months | 0.882782E+09 | 0.387339E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42444117.44 |
Maximum of Months | 0.105485E+10 | 0.452501E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329175E+09 | 0.614707E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.148158E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.134390E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.159693E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.142638E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.153925E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.153181E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.143382E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.159693E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.142638E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.148158E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.146421E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.143382E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.177566E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.134390E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.159693E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.148158E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.134390E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.159693E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.142638E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.153925E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.153181E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.143382E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.159693E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.142638E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.148158E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.146421E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.143382E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.177566E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.134390E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.159693E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.148158E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.134390E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.159693E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.142638E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.153925E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.153181E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.143382E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.159693E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.142638E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.148158E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.146421E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.143382E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.177566E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.134390E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.159693E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.290468E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.263476E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.313083E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.279647E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.301776E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.300317E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.281106E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.313083E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.279647E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.290468E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.287064E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.281106E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.348124E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.263476E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.313083E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1212506.63 | 0.748647E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582228E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4062877.38 | 0.742783E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94330078.87 | 0.241584E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189790E+09 | 0.148219E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356945E+09 | 37795197.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355091E+09 | 32273894.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238109E+09 | 51117229.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179329E+09 | 94288700.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60191271.00 | 0.382353E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3192536.98 | 0.672323E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84295.28 | 0.722388E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148234E+10 | 0.445600E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32273894.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356945E+09 | 0.748647E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2509642.43 | 0.125281E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990740E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8133874.24 | 0.127499E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178988E+09 | 0.423873E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345159E+09 | 0.261960E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642160E+09 | 70458306.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645677E+09 | 58839332.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443484E+09 | 89733305.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322516E+09 | 0.166904E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113299E+09 | 0.659190E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8666746.86 | 0.113775E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 978742.46 | 0.120925E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271157E+10 | 0.759649E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58839332.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645677E+09 | 0.127499E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2163159.69 | 0.122678E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993150E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4987618.62 | 0.132513E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155489E+09 | 0.457748E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329705E+09 | 0.271454E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683188E+09 | 75058633.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655698E+09 | 67219852.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463255E+09 | 96829750.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327702E+09 | 0.190563E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110961E+09 | 0.680150E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8274305.78 | 0.112463E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1089329.58 | 0.116345E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274251E+10 | 0.767216E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67219852.18 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683188E+09 | 0.132513E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10780.55 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10780.55 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10780.55 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10780.55 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10780.55 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10780.55 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10780.55 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10780.55 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10780.55 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10780.55 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10780.55 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10780.55 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10780.55 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10780.55 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9681.69 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9681.69 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9681.69 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9681.69 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9681.69 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9681.69 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9681.69 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9681.69 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9681.69 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9681.69 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9681.69 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9681.69 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9681.69 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9681.69 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9681.69 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9681.69 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9681.69 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9681.69 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9681.69 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9681.69 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9681.69 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9681.69 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9681.69 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9681.69 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9681.69 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9681.69 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9681.69 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9681.69 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9681.69 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9681.69 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9681.69 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9681.69 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9681.69 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9681.69 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9681.69 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9681.69 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9681.69 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9681.69 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1085.02 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 31-JAN-14:00 | 725.81 | 01-JAN-00:55 |
February | 2010.79 | 01-FEB-10:09 | 1012.06 | 03-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 758.22 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 944.32 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 | 18-MAR-17:10 | 660.91 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 649.85 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.31 | 30-APR-15:43 | 322.97 | 21-APR-04:53 |
May | 2010.79 | 01-MAY-09:09 | 623.27 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.90 | 20-MAY-17:30 | 251.49 | 23-MAY-04:53 |
June | 2010.79 | 01-JUN-09:09 | 578.40 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 571.47 | 17-JUN-17:10 | 118.02 | 13-JUN-04:20 |
July | 2010.79 | 03-JUL-09:09 | 639.81 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.29 | 22-JUL-18:00 | 181.04 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 954.74 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.76 | 13-AUG-16:00 | 301.83 | 05-AUG-17:45 |
September | 2010.79 | 01-SEP-09:09 | 832.06 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.14 | 17-SEP-11:58 | 231.49 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1041.68 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.99 | 01-OCT-14:40 | 646.90 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 1215.63 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 19-NOV-15:10 | 656.75 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1215.63 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 25-DEC-15:50 | 549.92 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.02 | |||||
Maximum of Months | 2010.79 | 1215.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 722.29 | 758.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 692.60 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 31-JAN-14:00 | 490.04 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 626.74 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 505.38 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 430.89 | 08-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.66 | 18-MAR-17:10 | 435.10 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 372.74 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.01 | 30-APR-15:43 | 310.69 | 16-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 372.74 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.86 | 20-MAY-17:30 | 167.36 | 23-MAY-04:53 |
June | 1295.83 | 01-JUN-09:09 | 372.74 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.18 | 17-JUN-17:10 | 92.38 | 11-JUN-06:50 |
July | 1295.83 | 03-JUL-09:09 | 418.26 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.72 | 22-JUL-18:00 | 116.06 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 596.81 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.56 | 13-AUG-15:55 | 194.89 | 05-AUG-17:45 |
September | 1295.83 | 01-SEP-09:09 | 415.88 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.20 | 17-SEP-11:58 | 149.46 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 501.29 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 01-OCT-14:40 | 451.82 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 | 19-NOV-15:10 | 429.82 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 25-DEC-15:50 | 360.47 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 490.72 | 505.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1058.44 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 31-JAN-15:00 | 732.95 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 991.24 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 807.10 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 904.70 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.11 | 15-MAR-13:00 | 658.03 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 655.35 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.55 | 30-APR-15:43 | 326.58 | 16-APR-09:00 |
May | 2010.83 | 01-MAY-09:09 | 623.27 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.54 | 20-MAY-17:30 | 250.25 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 613.47 | 27-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 571.88 | 17-JUN-17:10 | 116.87 | 13-JUN-04:20 |
July | 2010.83 | 03-JUL-09:09 | 643.62 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.48 | 22-JUL-18:00 | 181.34 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 960.02 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.75 | 13-AUG-16:00 | 311.46 | 05-AUG-17:45 |
September | 2010.83 | 01-SEP-09:09 | 662.71 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.94 | 17-SEP-11:55 | 237.77 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 904.37 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.54 | 01-OCT-14:25 | 720.43 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 1215.66 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 01-NOV-16:10 | 675.62 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1215.66 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 21-DEC-15:00 | 557.67 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 613.47 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.87 | |||||
Maximum of Months | 2010.83 | 1215.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 735.48 | 807.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 708.15 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 31-JAN-14:00 | 518.79 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 656.38 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 577.47 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 661.86 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 15-MAR-13:00 | 490.41 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 513.39 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.81 | 30-APR-15:04 | 276.16 | 16-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 416.27 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.03 | 20-MAY-17:45 | 187.55 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 397.11 | 27-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.75 | 17-JUN-17:10 | 102.41 | 13-JUN-03:45 |
July | 1295.83 | 03-JUL-09:09 | 417.01 | 24-JUL-08:20 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.98 | 22-JUL-18:00 | 170.43 | 26-JUL-23:50 |
August | 1295.83 | 01-AUG-09:09 | 626.57 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.73 | 13-AUG-16:00 | 268.33 | 05-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 589.24 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.84 | 17-SEP-11:58 | 184.14 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 681.53 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.18 | 01-OCT-14:25 | 501.45 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 01-NOV-16:00 | 497.21 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 21-DEC-15:00 | 407.30 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 397.11 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 478.98 | 577.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1082.84 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 144.60 | 16-JAN-11:53 | 1238.94 | 01-JAN-00:55 |
February | 2010.79 | 01-FEB-10:09 | 1008.68 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1540.86 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 940.42 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.93 | 18-MAR-17:02 | 1355.84 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 643.13 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 890.49 | 30-APR-15:53 | 707.77 | 21-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 616.10 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 839.92 | 20-MAY-17:01 | 583.26 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 578.40 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.76 | 17-JUN-17:10 | 309.54 | 13-JUN-03:55 |
July | 2010.79 | 03-JUL-09:09 | 633.58 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.69 | 22-JUL-18:00 | 478.40 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 951.76 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.13 | 13-AUG-16:00 | 691.63 | 05-AUG-17:45 |
September | 2010.79 | 01-SEP-09:09 | 826.51 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1094.53 | 17-SEP-11:58 | 499.62 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1038.83 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.89 | 01-OCT-14:40 | 1318.51 | 22-OCT-13:55 |
November | 2010.79 | 01-NOV-09:09 | 1215.63 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.29 | 19-NOV-14:32 | 1312.03 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1215.63 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.32 | 25-DEC-16:00 | 1134.36 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.54 | |||||
Maximum of Months | 2010.79 | 1215.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.69 | 1540.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 690.24 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 | 31-JAN-14:00 | 872.07 | 01-JAN-00:55 |
February | 1239.33 | 01-FEB-08:09 | 622.95 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1082.31 | 02-FEB-23:00 |
March | 1239.33 | 01-MAR-08:09 | 428.03 | 08-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.45 | 18-MAR-17:02 | 926.87 | 28-MAR-04:00 |
April | 1239.33 | 03-APR-07:10 | 372.74 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.79 | 30-APR-15:53 | 727.07 | 16-APR-08:50 |
May | 1239.33 | 01-MAY-07:10 | 372.74 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 521.29 | 20-MAY-17:01 | 396.34 | 23-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 372.74 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 889.28 | 17-JUN-17:10 | 228.53 | 11-JUN-06:00 |
July | 1239.33 | 03-JUL-07:10 | 414.69 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.62 | 22-JUL-17:43 | 330.86 | 26-JUL-24:00 |
August | 1239.33 | 01-AUG-07:10 | 592.60 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.63 | 13-AUG-15:55 | 483.88 | 05-AUG-17:45 |
September | 1239.33 | 01-SEP-07:10 | 412.16 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 737.36 | 17-SEP-11:55 | 340.81 | 03-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 490.94 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.95 | 01-OCT-14:25 | 1013.32 | 22-OCT-13:55 |
November | 1239.33 | 01-NOV-07:10 | 783.40 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.31 | 19-NOV-15:00 | 901.86 | 29-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 783.40 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.97 | 25-DEC-16:00 | 771.64 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.53 | |||||
Maximum of Months | 1239.33 | 783.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.62 | 1082.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1056.79 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 | 31-JAN-15:10 | 1551.74 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 988.71 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1771.35 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 900.51 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.39 | 15-MAR-13:00 | 1430.76 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 649.13 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 866.01 | 30-APR-15:53 | 723.84 | 21-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 616.10 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 821.54 | 20-MAY-17:01 | 585.25 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 578.41 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1328.65 | 17-JUN-17:10 | 304.96 | 13-JUN-03:55 |
July | 2010.83 | 03-JUL-09:09 | 636.46 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.86 | 22-JUL-18:00 | 476.78 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 957.08 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.08 | 13-AUG-16:00 | 726.30 | 05-AUG-17:45 |
September | 2010.83 | 01-SEP-09:09 | 657.78 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.83 | 17-SEP-11:55 | 521.36 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 864.70 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 665.01 | 01-OCT-14:25 | 1641.74 | 22-OCT-13:55 |
November | 2010.83 | 01-NOV-09:09 | 1215.66 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 | 01-NOV-16:10 | 1449.04 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1215.66 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 21-DEC-15:00 | 1228.88 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.96 | |||||
Maximum of Months | 2010.83 | 1215.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.86 | 1771.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 706.42 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 | 16-JAN-11:53 | 961.75 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 653.07 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1145.31 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 658.50 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 15-MAR-13:00 | 970.40 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 507.43 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 572.46 | 30-APR-15:13 | 510.07 | 26-APR-21:10 |
May | 1295.83 | 01-MAY-09:09 | 412.61 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.79 | 20-MAY-17:45 | 420.52 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 372.74 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 889.32 | 17-JUN-17:10 | 237.50 | 13-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 413.23 | 24-JUL-08:20 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.46 | 22-JUL-18:00 | 378.88 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 622.46 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1005.55 | 13-AUG-16:00 | 506.79 | 05-AUG-17:45 |
September | 1295.83 | 01-SEP-09:09 | 583.99 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.68 | 17-SEP-11:55 | 351.70 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 679.43 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.84 | 01-OCT-14:25 | 944.83 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.68 | 19-NOV-12:32 | 926.70 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 | 25-DEC-13:31 | 791.62 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.50 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.46 | 1145.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1082.67 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 297.14 | 16-JAN-11:53 | 1276.44 | 01-JAN-01:07 |
February | 2010.79 | 01-FEB-10:09 | 1008.25 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1750.79 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 939.97 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.22 | 18-MAR-17:02 | 1525.57 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 643.00 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.83 | 30-APR-15:25 | 835.94 | 26-APR-21:10 |
May | 2010.79 | 01-MAY-09:09 | 615.81 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 969.47 | 20-MAY-17:01 | 692.96 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 578.40 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.36 | 17-JUN-17:10 | 377.94 | 13-JUN-03:55 |
July | 2010.79 | 03-JUL-09:09 | 633.33 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.60 | 22-JUL-18:00 | 601.88 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 951.21 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.35 | 13-AUG-16:00 | 881.52 | 05-AUG-17:45 |
September | 2010.79 | 01-SEP-09:09 | 825.83 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1292.74 | 17-SEP-12:45 | 634.79 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1038.74 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 825.71 | 01-OCT-14:25 | 1570.43 | 22-OCT-13:55 |
November | 2010.79 | 01-NOV-09:09 | 1215.63 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 557.92 | 19-NOV-12:52 | 1478.61 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1215.63 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.15 | 25-DEC-15:52 | 1350.95 | 07-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.94 | |||||
Maximum of Months | 2010.79 | 1215.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.60 | 1750.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 690.05 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.10 | 16-JAN-12:30 | 861.80 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 622.65 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1231.61 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 427.93 | 08-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.40 | 18-MAR-17:02 | 1051.00 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 372.74 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.27 | 30-APR-15:23 | 849.87 | 16-APR-08:30 |
May | 1295.83 | 01-MAY-09:09 | 372.74 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 636.93 | 20-MAY-17:07 | 471.24 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 372.74 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.33 | 17-JUN-17:10 | 284.59 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 414.55 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.85 | 22-JUL-17:43 | 414.80 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 592.23 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.88 | 13-AUG-16:00 | 612.69 | 05-AUG-17:45 |
September | 1295.83 | 01-SEP-09:09 | 412.04 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 878.11 | 17-SEP-12:45 | 430.83 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 490.88 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.44 | 01-OCT-14:25 | 1215.14 | 22-OCT-13:55 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.92 | 19-NOV-15:00 | 1025.29 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.38 | 25-DEC-16:00 | 905.34 | 07-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.59 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.85 | 1231.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1056.47 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.78 | 31-JAN-14:10 | 1616.57 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 988.26 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2047.42 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 900.01 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.26 | 15-MAR-13:00 | 1630.18 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 649.01 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.79 | 30-APR-14:55 | 875.26 | 26-APR-21:10 |
May | 2010.83 | 01-MAY-09:09 | 615.81 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 950.92 | 20-MAY-17:47 | 695.24 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 578.41 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.30 | 17-JUN-17:10 | 372.06 | 13-JUN-03:55 |
July | 2010.83 | 03-JUL-09:09 | 636.35 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2054.47 | 22-JUL-17:43 | 599.83 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 956.54 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.27 | 13-AUG-16:00 | 925.10 | 05-AUG-17:45 |
September | 2010.83 | 01-SEP-09:09 | 657.62 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.43 | 17-SEP-12:07 | 661.63 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 864.39 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.73 | 01-OCT-14:25 | 1973.14 | 22-OCT-13:55 |
November | 2010.83 | 01-NOV-09:09 | 1215.66 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.63 | 01-NOV-16:00 | 1665.70 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1215.66 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 21-DEC-15:00 | 1390.87 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.06 | |||||
Maximum of Months | 2010.83 | 1215.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2054.47 | 2047.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 706.32 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 120.79 | 16-JAN-11:53 | 1008.68 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 652.80 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1320.68 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 658.29 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 | 15-MAR-13:00 | 1118.53 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 507.37 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.86 | 30-APR-15:00 | 631.79 | 26-APR-21:10 |
May | 1295.83 | 01-MAY-09:09 | 412.47 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 628.23 | 20-MAY-17:45 | 503.44 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 372.74 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.25 | 17-JUN-17:10 | 289.76 | 13-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 413.12 | 24-JUL-08:20 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.74 | 22-JUL-18:00 | 476.27 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 622.12 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.01 | 13-AUG-16:00 | 644.22 | 05-AUG-17:35 |
September | 1295.83 | 01-SEP-09:09 | 583.63 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 878.18 | 17-SEP-12:45 | 443.50 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 679.33 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 545.67 | 01-OCT-14:25 | 1134.90 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.08 | 19-NOV-12:12 | 1064.67 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.15 | 25-DEC-13:52 | 908.32 | 07-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.76 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.74 | 1320.68 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 155.04 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 155.04 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 155.04 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 155.04 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 155.04 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 155.04 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 155.04 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 155.04 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 155.04 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 155.04 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 155.04 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 155.04 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 155.04 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 155.04 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 155.04 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 155.04 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 155.04 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 155.04 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 155.04 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 155.04 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 155.04 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 155.04 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 155.04 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 155.04 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 155.04 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 155.04 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 155.04 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 155.04 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 155.04 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 155.04 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 155.04 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 155.04 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 155.04 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 155.04 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 155.04 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 155.04 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3039.65 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3039.65 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3039.65 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3039.65 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3039.65 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3039.65 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3039.65 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3039.65 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3039.65 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3039.65 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3039.65 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3039.65 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3039.65 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3039.65 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.76 | 31-JAN-14:00 | 1634.20 | 01-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1692.20 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.34 | 18-MAR-17:02 | 1448.67 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.37 | 30-APR-14:51 | 720.32 | 21-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.32 | 20-MAY-17:01 | 569.16 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.66 | 17-JUN-17:03 | 274.22 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1492.85 | 22-JUL-18:00 | 409.56 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1273.91 | 13-AUG-16:00 | 635.65 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.51 | 17-SEP-12:00 | 468.78 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.21 | 01-OCT-14:50 | 1277.81 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.19 | 19-NOV-15:00 | 1442.85 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 | 21-DEC-15:00 | 1214.74 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1492.85 | 1692.20 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 31-JAN-14:00 | 2418.03 | 01-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2941.64 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.34 | 18-MAR-17:02 | 2476.32 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.39 | 30-APR-15:00 | 1273.39 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1368.20 | 20-MAY-17:01 | 1016.60 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2193.45 | 17-JUN-17:03 | 496.02 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2698.99 | 22-JUL-18:00 | 750.71 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.52 | 13-AUG-16:00 | 1122.51 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1723.10 | 17-SEP-12:00 | 820.78 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.63 | 01-OCT-14:50 | 2172.28 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.56 | 19-NOV-14:51 | 2438.30 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.06 | 25-DEC-15:52 | 2097.13 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.02 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2698.99 | 2941.64 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 | 16-JAN-11:53 | 2100.18 | 01-JAN-01:20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2910.48 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.08 | 15-MAR-13:00 | 2442.63 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.73 | 30-APR-15:50 | 1286.83 | 26-APR-21:02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1311.10 | 20-MAY-17:01 | 1058.82 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2346.90 | 17-JUN-17:03 | 519.60 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2761.59 | 22-JUL-18:00 | 911.47 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2251.90 | 13-AUG-16:00 | 1398.63 | 05-AUG-17:45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1744.07 | 17-SEP-11:53 | 988.97 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.88 | 01-OCT-14:12 | 2779.69 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.58 | 19-NOV-15:00 | 2417.98 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.76 | 25-DEC-13:52 | 2018.48 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.60 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2761.59 | 2910.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 99296.39 | 09-JAN-05:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97894.83 | 13-FEB-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98853.69 | 20-MAR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98295.82 | 24-APR-04:21 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98778.33 | 29-MAY-17:48 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99411.04 | 19-JUN-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 101046.20 | 03-JUL-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99258.08 | 27-AUG-18:16 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99376.82 | 18-SEP-03:02 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 102002.62 | 16-OCT-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99392.91 | 24-NOV-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99874.43 | 11-DEC-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 97894.83 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102002.62 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 83541.58 | 17-JAN-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83830.29 | 21-FEB-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84774.67 | 20-MAR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81668.90 | 20-APR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87903.26 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78733.34 | 19-JUN-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76743.63 | 17-JUL-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81598.88 | 21-AUG-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86671.53 | 20-SEP-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89458.10 | 16-OCT-04:12 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85633.28 | 06-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86986.38 | 04-DEC-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 76743.63 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89458.10 | 9673.43 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 70927.54 | 09-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70984.71 | 24-FEB-06:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74099.85 | 18-MAR-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74500.41 | 17-APR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76195.13 | 12-MAY-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72940.64 | 13-JUN-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79999.52 | 03-JUL-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73956.56 | 05-AUG-04:12 | 0.00 | 3224.16 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81358.97 | 20-SEP-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75539.53 | 11-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74074.97 | 13-NOV-05:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69906.76 | 29-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 69906.76 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81358.97 | 9673.43 | 3761.52 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32482.62 | 27-JAN-17:00 | 15316.26 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30488.51 | 23-FEB-15:00 | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70100.43 | 17-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74509.55 | 26-APR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75802.64 | 26-MAY-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83237.82 | 19-JUN-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83144.37 | 03-JUL-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77088.69 | 21-AUG-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82770.51 | 20-SEP-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75152.46 | 05-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70268.59 | 03-NOV-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29937.98 | 22-DEC-17:00 | 15316.26 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 29937.98 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83237.82 | 16014.58 | 9681.69 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4996.18 | 31-JAN-16:30 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 |
February | 4987.72 | 22-FEB-14:00 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 |
March | 7172.66 | 20-MAR-14:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 0.00 |
April | 17701.59 | 30-APR-16:21 | 1012.16 | 321.32 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 293.68 | 0.00 |
May | 17760.37 | 07-MAY-17:01 | 0.00 | 321.32 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 235.15 | 0.00 |
June | 18647.80 | 04-JUN-17:11 | 0.00 | 321.32 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 270.42 | 0.00 |
July | 18499.82 | 04-JUL-17:21 | 0.00 | 321.32 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 324.12 | 0.00 |
August | 18137.78 | 13-AUG-16:21 | 809.73 | 257.06 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 569.74 | 0.00 |
September | 17749.67 | 17-SEP-15:52 | 607.30 | 192.79 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.13 | 0.00 |
October | 13744.17 | 02-OCT-04:23 | 0.00 | 269.88 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 | 0.00 |
November | 6786.98 | 02-NOV-13:30 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 |
December | 5265.11 | 26-DEC-15:30 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4987.72 | 0.00 | 192.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18647.80 | 2010.79 | 578.40 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 569.74 | 35.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7600.98 | 17-JAN-09:30 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.09 |
February | 10866.68 | 20-FEB-09:43 | 195.68 | 62.12 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.45 |
March | 17036.41 | 19-MAR-09:32 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.63 |
April | 19346.77 | 23-APR-08:22 | 391.37 | 124.24 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 |
May | 20014.64 | 29-MAY-09:31 | 456.59 | 144.95 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.36 |
June | 19188.78 | 04-JUN-09:11 | 587.05 | 186.37 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 0.00 |
July | 18798.54 | 04-JUL-08:41 | 521.82 | 165.66 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 0.00 |
August | 18791.03 | 13-AUG-09:02 | 391.37 | 124.24 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 0.00 |
September | 19655.89 | 10-SEP-09:21 | 456.59 | 144.95 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 0.00 |
October | 18529.87 | 15-OCT-08:42 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.47 |
November | 8674.69 | 19-NOV-09:43 | 195.68 | 62.12 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.45 |
December | 6665.14 | 26-DEC-09:40 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6665.14 | 195.68 | 62.12 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20014.64 | 1239.33 | 372.74 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 106.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22248.12 | 16-JAN-12:12 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.20 |
February | 20766.36 | 26-FEB-14:32 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.52 |
March | 14386.13 | 26-MAR-13:43 | 303.66 | 96.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.49 |
April | 20941.76 | 23-APR-15:41 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 176.02 | 0.00 |
May | 20097.76 | 07-MAY-16:21 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 236.99 | 0.00 |
June | 20728.61 | 04-JUN-15:51 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 327.61 | 0.00 |
July | 20589.13 | 04-JUL-16:41 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 352.50 | 0.00 |
August | 20688.38 | 27-AUG-13:41 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 318.95 | 0.00 |
September | 22319.99 | 10-SEP-12:41 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 165.30 | 0.00 |
October | 23084.37 | 15-OCT-13:21 | 809.75 | 257.06 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 0.00 |
November | 22519.26 | 19-NOV-13:42 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 |
December | 23755.69 | 25-DEC-13:41 | 809.75 | 257.06 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14386.13 | 303.66 | 96.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23755.69 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 352.50 | 266.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24097.84 | 29-JAN-16:22 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.24 |
February | 17932.12 | 20-FEB-16:22 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 |
March | 19346.91 | 26-MAR-15:42 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 |
April | 28568.79 | 23-APR-16:21 | 652.28 | 207.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 | 0.00 |
May | 27179.08 | 28-MAY-17:01 | 0.00 | 207.07 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 82.39 | 0.00 |
June | 28334.49 | 04-JUN-16:31 | 652.28 | 207.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 149.72 | 0.00 |
July | 27868.75 | 04-JUL-17:21 | 0.00 | 207.07 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 155.74 | 0.00 |
August | 26792.23 | 13-AUG-16:21 | 521.82 | 165.66 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 308.02 | 0.00 |
September | 24117.93 | 24-SEP-15:12 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 133.99 | 0.00 |
October | 24564.33 | 15-OCT-14:01 | 521.82 | 165.66 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 48.32 | 0.00 |
November | 24131.42 | 05-NOV-15:12 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.61 |
December | 25368.75 | 25-DEC-15:01 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17932.12 | 0.00 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28568.79 | 652.28 | 207.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 308.02 | 97.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3687.45 | 31-JAN-16:30 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 0.00 |
February | 2912.90 | 22-FEB-14:10 | 4021.58 | 1156.80 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.56 |
March | 5442.10 | 16-MAR-16:00 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 | 0.00 |
April | 17104.78 | 30-APR-16:31 | 1012.16 | 321.32 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 672.07 | 0.00 |
May | 17695.63 | 07-MAY-17:01 | 0.00 | 321.32 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 536.68 | 0.00 |
June | 18205.83 | 11-JUN-18:02 | 0.00 | 321.32 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 451.18 | 0.00 |
July | 18598.17 | 30-JUL-18:11 | 0.00 | 321.32 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.16 | 0.00 |
August | 17820.25 | 13-AUG-16:21 | 809.73 | 257.06 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.92 | 0.00 |
September | 17686.27 | 10-SEP-16:42 | 607.30 | 192.79 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 812.75 | 0.00 |
October | 11693.11 | 04-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 |
November | 5388.76 | 02-NOV-14:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.28 | 0.00 |
December | 2506.86 | 22-DEC-16:30 | 1923.11 | 642.49 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2506.86 | 0.00 | 192.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18598.17 | 4021.58 | 1156.80 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.92 | 82.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6903.86 | 27-JAN-11:05 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.75 |
February | 7043.09 | 23-FEB-11:05 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 |
March | 13826.69 | 19-MAR-09:23 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.46 |
April | 21241.30 | 30-APR-09:51 | 456.59 | 144.95 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 |
May | 21529.70 | 07-MAY-09:01 | 456.59 | 144.95 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 |
June | 22424.40 | 18-JUN-08:41 | 587.05 | 186.37 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.65 | 0.00 |
July | 21924.75 | 04-JUL-09:31 | 521.82 | 165.66 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 0.00 |
August | 20272.05 | 13-AUG-09:02 | 391.37 | 124.24 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 87.64 | 0.00 |
September | 21320.11 | 10-SEP-10:01 | 456.59 | 144.95 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 98.82 | 0.00 |
October | 17292.18 | 09-OCT-09:02 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.99 |
November | 8443.52 | 01-NOV-10:05 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
December | 5499.28 | 27-DEC-11:05 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5499.28 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22424.40 | 2478.65 | 745.48 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.65 | 188.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21294.00 | 29-JAN-13:52 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.30 |
February | 20457.83 | 26-FEB-12:23 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.66 |
March | 15206.72 | 26-MAR-14:13 | 303.66 | 96.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.05 |
April | 20779.59 | 30-APR-12:32 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 409.47 | 0.00 |
May | 20063.52 | 07-MAY-16:21 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 538.41 | 0.00 |
June | 19836.74 | 18-JUN-10:41 | 809.75 | 257.06 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 318.93 | 0.00 |
July | 21228.95 | 30-JUL-14:51 | 910.97 | 289.20 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 656.86 | 0.00 |
August | 20299.74 | 13-AUG-16:21 | 809.75 | 257.06 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.72 | 0.00 |
September | 22388.23 | 10-SEP-12:41 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 362.99 | 0.00 |
October | 21411.22 | 09-OCT-13:42 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 0.00 |
November | 22595.67 | 19-NOV-14:51 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.76 |
December | 22471.42 | 03-DEC-13:12 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15206.72 | 303.66 | 96.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22595.67 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.72 | 412.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14292.44 | 29-JAN-16:32 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.97 |
February | 10554.32 | 22-FEB-16:30 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 |
March | 15749.36 | 18-MAR-17:05 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
April | 24472.60 | 30-APR-16:31 | 652.28 | 207.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 189.09 | 0.00 |
May | 24678.83 | 07-MAY-16:21 | 652.28 | 207.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 247.47 | 0.00 |
June | 25134.18 | 11-JUN-17:21 | 0.00 | 207.07 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 151.45 | 0.00 |
July | 25645.35 | 30-JUL-17:31 | 0.00 | 207.07 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 540.92 | 0.00 |
August | 24177.73 | 06-AUG-17:31 | 0.00 | 165.66 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 29.56 | 0.00 |
September | 21656.61 | 04-SEP-15:42 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 122.48 | 0.00 |
October | 20939.00 | 15-OCT-16:12 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 116.08 | 0.00 |
November | 20519.83 | 19-NOV-14:51 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
December | 14775.09 | 25-DEC-16:32 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10554.32 | 0.00 | 103.54 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25645.35 | 1239.33 | 372.74 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 540.92 | 103.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3431.42 | 27-JAN-16:30 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 | 0.00 |
February | 2686.77 | 22-FEB-16:30 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 |
March | 5879.83 | 16-MAR-16:00 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 0.00 |
April | 17168.46 | 30-APR-16:01 | 708.51 | 224.93 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 976.63 | 0.00 |
May | 20444.74 | 28-MAY-16:51 | 1012.16 | 321.32 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 666.41 | 0.00 |
June | 21098.56 | 25-JUN-18:01 | 0.00 | 257.06 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.73 | 0.00 |
July | 22297.02 | 30-JUL-18:11 | 0.00 | 321.32 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1218.04 | 0.00 |
August | 21073.88 | 13-AUG-16:21 | 809.73 | 257.06 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1589.52 | 0.00 |
September | 20551.00 | 24-SEP-14:21 | 708.51 | 224.93 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 574.50 | 0.00 |
October | 14385.04 | 02-OCT-03:02 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.99 |
November | 5604.10 | 01-NOV-15:30 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 76.48 | 0.00 |
December | 2411.51 | 22-DEC-15:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2411.51 | 0.00 | 224.93 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22297.02 | 2010.79 | 578.40 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1589.52 | 90.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4726.56 | 27-JAN-10:30 | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 |
February | 5390.94 | 23-FEB-10:20 | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.58 |
March | 7243.29 | 23-MAR-10:20 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 |
April | 19798.84 | 30-APR-10:02 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
May | 21142.52 | 28-MAY-08:52 | 391.37 | 124.24 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 |
June | 22854.27 | 18-JUN-08:11 | 521.82 | 165.66 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 | 0.00 |
July | 22156.20 | 30-JUL-08:11 | 456.59 | 144.95 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 |
August | 20979.48 | 13-AUG-09:42 | 391.37 | 124.24 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 95.27 | 0.00 |
September | 20077.92 | 10-SEP-10:12 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 190.66 | 0.00 |
October | 19604.83 | 15-OCT-09:22 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.47 |
November | 6316.77 | 01-NOV-10:00 | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 |
December | 2877.83 | 22-DEC-10:40 | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2877.83 | 326.14 | 103.54 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22854.27 | 1295.83 | 372.74 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 190.66 | 104.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25472.57 | 29-JAN-14:11 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.95 |
February | 16254.73 | 28-FEB-14:05 | 4021.67 | 1156.82 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 |
March | 14168.90 | 23-MAR-14:00 | 2010.83 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 | 0.00 |
April | 23187.85 | 02-APR-16:21 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 137.09 | 0.00 |
May | 22612.12 | 28-MAY-16:51 | 1012.19 | 321.33 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 656.64 | 0.00 |
June | 22630.94 | 18-JUN-17:32 | 0.00 | 160.66 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 319.78 | 0.00 |
July | 24816.15 | 30-JUL-14:51 | 910.97 | 289.20 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 766.83 | 0.00 |
August | 23488.15 | 13-AUG-16:21 | 809.75 | 257.06 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.06 | 0.00 |
September | 25221.81 | 24-SEP-14:21 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 423.25 | 0.00 |
October | 26168.01 | 15-OCT-13:21 | 809.75 | 257.06 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 0.00 |
November | 24420.95 | 05-NOV-13:42 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.63 |
December | 25544.93 | 25-DEC-14:11 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14168.90 | 0.00 | 160.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26168.01 | 4021.67 | 1156.82 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.06 | 443.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19837.88 | 29-JAN-16:12 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.65 |
February | 10489.05 | 22-FEB-16:30 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.08 |
March | 17030.37 | 18-MAR-17:05 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 |
April | 26900.46 | 02-APR-16:21 | 652.28 | 207.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 0.00 |
May | 27352.38 | 28-MAY-16:51 | 652.28 | 207.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 196.35 | 0.00 |
June | 25540.57 | 25-JUN-17:21 | 0.00 | 165.66 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 591.15 | 0.00 |
July | 28560.55 | 30-JUL-17:31 | 0.00 | 207.07 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 629.09 | 0.00 |
August | 25786.80 | 13-AUG-16:21 | 521.82 | 165.66 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 895.62 | 0.00 |
September | 24469.64 | 24-SEP-16:21 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 275.01 | 0.00 |
October | 23655.47 | 15-OCT-16:01 | 521.82 | 165.66 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 114.86 | 0.00 |
November | 12261.00 | 01-NOV-16:00 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 0.00 |
December | 16487.91 | 25-DEC-16:11 | 521.82 | 165.66 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10489.05 | 0.00 | 124.24 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28560.55 | 1239.33 | 372.74 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 895.62 | 111.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5736.86 | 17-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
February | 5125.39 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.27 |
March | 7110.31 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.55 |
April | 8952.37 | 24-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 |
May | 9497.32 | 30-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
June | 11953.90 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
July | 14565.63 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 | 0.00 |
August | 16583.80 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 0.00 |
September | 13447.49 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
October | 12966.15 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 0.00 |
November | 8717.67 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 |
December | 8466.17 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5125.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16583.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 182.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2861.65 | 27-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 0.00 |
February | 2769.67 | 01-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.54 |
March | 4319.13 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.13 |
April | 6600.66 | 25-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.56 | 0.00 |
May | 7268.65 | 08-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.55 | 0.00 |
June | 9256.13 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.90 |
July | 9330.74 | 31-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | 0.00 |
August | 12726.75 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | 0.00 |
September | 11033.67 | 11-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.05 |
October | 8206.53 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 | 0.00 |
November | 4153.71 | 02-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.16 | 0.00 |
December | 6871.86 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2769.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12726.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.56 | 459.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7894.60 | 31-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.35 | 0.00 |
February | 7028.59 | 23-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.23 |
March | 11427.64 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 | 0.00 |
April | 18757.82 | 14-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.76 | 0.00 |
May | 19213.23 | 19-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.67 | 0.00 |
June | 23511.31 | 28-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.36 | 0.00 |
July | 21963.61 | 20-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.74 | 0.00 |
August | 21600.07 | 15-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.80 | 0.00 |
September | 19151.64 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.68 | 0.00 |
October | 16743.72 | 02-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.80 | 0.00 |
November | 10483.54 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.77 | 0.00 |
December | 5812.52 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5812.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23511.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.36 | 229.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2251.76 | 29-JAN-17:15 | 46.77 | 34.46 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3998.12 | 27-FEB-17:40 | 70.15 | 86.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7130.65 | 31-MAR-24:00 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7727.90 | 26-APR-18:50 | 23.38 | 51.68 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3479.52 | 31-MAY-24:00 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5411.70 | 30-JUN-23:55 | 0.00 | 17.23 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7321.59 | 31-JUL-23:57 | 0.00 | 25.84 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7749.00 | 21-AUG-00:40 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3486.33 | 30-SEP-23:40 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5301.77 | 31-OCT-24:00 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6242.48 | 26-NOV-16:57 | 35.07 | 25.84 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7838.77 | 28-DEC-17:00 | 222.14 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2251.76 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7838.77 | 222.14 | 155.04 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1984.64 | 29-JAN-17:27 | 35.07 | 25.84 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3743.47 | 27-FEB-17:50 | 70.15 | 86.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6659.51 | 31-MAR-23:50 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7366.28 | 26-APR-18:50 | 23.38 | 51.68 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3379.50 | 31-MAY-24:00 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5200.96 | 30-JUN-23:40 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6998.93 | 31-JUL-23:57 | 0.00 | 25.84 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7239.95 | 20-AUG-21:03 | 0.00 | 34.46 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3396.86 | 30-SEP-24:00 | 0.00 | 17.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4898.82 | 31-OCT-24:00 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5730.83 | 14-NOV-17:00 | 222.14 | 155.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7374.71 | 28-DEC-17:00 | 222.14 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1984.64 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7374.71 | 222.14 | 155.04 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1984.38 | 24-JAN-17:00 | 222.14 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3707.52 | 27-FEB-17:50 | 70.15 | 86.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6482.20 | 31-MAR-23:20 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7479.12 | 26-APR-18:30 | 23.38 | 51.68 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3391.62 | 31-MAY-24:00 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5258.28 | 30-JUN-23:40 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7046.17 | 31-JUL-23:57 | 0.00 | 25.84 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7432.76 | 20-AUG-21:03 | 0.00 | 34.46 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3427.60 | 30-SEP-23:55 | 0.00 | 17.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4701.75 | 31-OCT-23:40 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5745.67 | 21-NOV-17:00 | 222.14 | 155.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7361.13 | 26-DEC-17:00 | 222.14 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1984.38 | 0.00 | 8.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7479.12 | 222.14 | 155.04 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91777.86 | 17-JAN-17:00 | 4808.68 | 3039.65 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182324.46 | 21-FEB-17:00 | 4808.68 | 3039.65 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357664.50 | 31-MAR-24:00 | 0.00 | 168.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 378773.76 | 03-APR-21:02 | 1518.53 | 2026.38 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175299.38 | 31-MAY-24:00 | 0.00 | 168.86 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267153.91 | 30-JUN-24:00 | 0.00 | 337.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356247.01 | 31-JUL-23:13 | 0.00 | 506.59 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 386151.65 | 23-AUG-22:53 | 1012.35 | 675.46 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177021.24 | 30-SEP-23:55 | 0.00 | 337.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268682.19 | 31-OCT-24:00 | 0.00 | 168.86 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276298.07 | 20-NOV-17:00 | 4808.68 | 3039.65 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 370243.00 | 25-DEC-16:32 | 1265.44 | 844.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91777.86 | 0.00 | 168.86 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 386151.65 | 4808.68 | 3039.65 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.157666E+13 | 1151740.42 | 27-JAN-16:40 | 0.701220E+11 | 424652.64 | 02-JAN-06:10 |
February | 0.157458E+13 | 1155623.80 | 22-FEB-16:30 | 0.647980E+11 | 280673.84 | 13-FEB-06:10 |
March | 0.233490E+13 | 1465451.14 | 17-MAR-15:20 | 0.706447E+11 | 432320.65 | 27-MAR-06:10 |
April | 0.299475E+13 | 1751181.87 | 12-APR-15:50 | 0.536421E+11 | 71206.30 | 05-APR-11:09 |
May | 0.189338E+13 | 1209840.31 | 16-MAY-15:50 | 0.532347E+11 | 67761.52 | 04-MAY-11:30 |
June | 0.235816E+13 | 1443466.88 | 19-JUN-14:50 | 0.495259E+11 | 62657.72 | 05-JUN-11:20 |
July | 0.276500E+13 | 1605531.15 | 20-JUL-15:09 | 0.474712E+11 | 59343.43 | 03-JUL-11:50 |
August | 0.321840E+13 | 1840073.21 | 25-AUG-15:09 | 0.504409E+11 | 60847.90 | 30-AUG-11:30 |
September | 0.177953E+13 | 1236515.16 | 06-SEP-15:00 | 0.489694E+11 | 64697.30 | 25-SEP-11:30 |
October | 0.210025E+13 | 1351886.15 | 02-OCT-15:00 | 0.552463E+11 | 196117.28 | 25-OCT-06:10 |
November | 0.224530E+13 | 1473850.99 | 20-NOV-16:10 | 0.606160E+11 | 280641.36 | 24-NOV-06:10 |
December | 0.265213E+13 | 1538561.50 | 22-DEC-16:00 | 0.970571E+11 | 587597.26 | 06-DEC-07:10 |
Annual Sum or Average | 0.274931E+14 | 0.721768E+12 | ||||
Minimum of Months | 0.157458E+13 | 1151740.42 | 0.474712E+11 | 59343.43 | ||
Maximum of Months | 0.321840E+13 | 1840073.21 | 0.970571E+11 | 587597.26 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.355567E+11 | 59423.41 | 30-JAN-12:30 | 0.00 | 0.00 |
February | 0.318554E+11 | 74820.60 | 27-FEB-12:39 | 0.00 | 0.00 |
March | 0.466381E+11 | 86249.66 | 28-MAR-12:30 | 0.00 | 0.00 |
April | 0.663128E+11 | 87025.19 | 19-APR-12:30 | 0.00 | 0.00 |
May | 0.733372E+11 | 88482.24 | 12-MAY-12:30 | 0.00 | 0.00 |
June | 0.731278E+11 | 85921.72 | 10-JUN-12:30 | 0.00 | 0.00 |
July | 0.620817E+11 | 81582.34 | 21-JUL-12:30 | 0.00 | 0.00 |
August | 0.570455E+11 | 80074.66 | 05-AUG-12:30 | 0.00 | 0.00 |
September | 0.461525E+11 | 76519.03 | 09-SEP-12:30 | 0.00 | 0.00 |
October | 0.441772E+11 | 73306.93 | 12-OCT-12:30 | 0.00 | 0.00 |
November | 0.337460E+11 | 62875.00 | 04-NOV-11:00 | 0.00 | 0.00 |
December | 0.312457E+11 | 55021.61 | 14-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.601276E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.312457E+11 | 55021.61 | 0.00 | 0.00 | |
Maximum of Months | 0.733372E+11 | 88482.24 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.152913E+12 | 0.283343E+11 | 0.766053E+12 | 0.102198E+12 | 0.180915E+12 | 0.287449E+11 | 0.00 | 0.854405E+11 | 0.442303E+11 | 0.187836E+12 | 0.00 | 0.00 | 0.00 |
February | 0.138345E+12 | 0.234177E+11 | 0.978954E+12 | 0.923142E+11 | 0.159384E+12 | 0.209306E+11 | 0.00 | 0.493324E+11 | 0.194437E+11 | 0.924595E+11 | 0.00 | 0.00 | 0.00 |
March | 0.162770E+12 | 0.229510E+11 | 0.141687E+13 | 0.102366E+12 | 0.190620E+12 | 0.315831E+11 | 0.00 | 0.155994E+12 | 0.602935E+11 | 0.191451E+12 | 0.00 | 0.00 | 0.00 |
April | 0.144789E+12 | 0.193025E+11 | 0.165903E+13 | 0.988853E+11 | 0.229198E+12 | 0.520699E+11 | 0.00 | 0.427955E+12 | 0.108798E+12 | 0.254728E+12 | 0.00 | 0.00 | 0.00 |
May | 0.155793E+12 | 0.174241E+11 | 0.774844E+12 | 0.102281E+12 | 0.252007E+12 | 0.533019E+11 | 0.00 | 0.283968E+12 | 0.113948E+12 | 0.139815E+12 | 0.00 | 0.00 | 0.00 |
June | 0.154525E+12 | 0.159110E+11 | 0.106252E+13 | 0.990427E+11 | 0.276443E+12 | 0.679799E+11 | 0.00 | 0.479843E+12 | 0.135389E+12 | 0.665134E+11 | 0.00 | 0.00 | 0.00 |
July | 0.145013E+12 | 0.168782E+11 | 0.139340E+13 | 0.102123E+12 | 0.268339E+12 | 0.680226E+11 | 0.00 | 0.594397E+12 | 0.156704E+12 | 0.201208E+11 | 0.00 | 0.00 | 0.00 |
August | 0.162016E+12 | 0.188928E+11 | 0.173200E+13 | 0.102366E+12 | 0.275584E+12 | 0.688507E+11 | 0.00 | 0.657567E+12 | 0.158084E+12 | 0.430446E+11 | 0.00 | 0.00 | 0.00 |
September | 0.145247E+12 | 0.208186E+11 | 0.740713E+12 | 0.988845E+11 | 0.237625E+12 | 0.556191E+11 | 0.00 | 0.316386E+12 | 0.144843E+12 | 0.193905E+11 | 0.00 | 0.00 | 0.00 |
October | 0.151758E+12 | 0.246223E+11 | 0.108340E+13 | 0.102198E+12 | 0.210016E+12 | 0.429269E+11 | 0.00 | 0.235400E+12 | 0.930054E+11 | 0.156923E+12 | 0.00 | 0.00 | 0.00 |
November | 0.150951E+12 | 0.267265E+11 | 0.135889E+13 | 0.989491E+11 | 0.182963E+12 | 0.305295E+11 | 0.00 | 0.160428E+12 | 0.614561E+11 | 0.174409E+12 | 0.00 | 0.00 | 0.00 |
December | 0.148579E+12 | 0.292483E+11 | 0.170972E+13 | 0.102124E+12 | 0.177169E+12 | 0.266400E+11 | 0.00 | 0.148129E+12 | 0.479410E+11 | 0.262577E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181270E+13 | 0.264527E+12 | 0.146764E+14 | 0.120373E+13 | 0.264026E+13 | 0.547199E+12 | 0.00 | 0.359484E+13 | 0.114414E+13 | 0.160927E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138345E+12 | 0.159110E+11 | 0.740713E+12 | 0.923142E+11 | 0.159384E+12 | 0.209306E+11 | 0.00 | 0.493324E+11 | 0.194437E+11 | 0.193905E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162770E+12 | 0.292483E+11 | 0.173200E+13 | 0.102366E+12 | 0.276443E+12 | 0.688507E+11 | 0.00 | 0.657567E+12 | 0.158084E+12 | 0.262577E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.944818E+10 | 0.00 | 0.606739E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.101338E+11 | 0.00 | 0.546642E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.968841E+10 | 0.00 | 0.609563E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 19574882.32 | 0.00 | 0.536225E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.532347E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.495259E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.474712E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.504409E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1999.72 | 0.00 | 0.489694E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.167993E+10 | 0.00 | 0.535664E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.516739E+10 | 0.00 | 0.554486E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.385840E+11 | 0.00 | 0.584732E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.747212E+11 | 0.00 | 0.647047E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.474712E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.385840E+11 | 0.00 | 0.609563E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 173771.70 | 20-JAN-16:00 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73702.22 | 20-JAN-08:39 | 146887.39 | 31-JAN-16:00 | 38688.77 | 27-JAN-15:39 | 0.00 | 01-JAN-00:10 |
February | 171152.48 | 10-FEB-08:09 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73701.39 | 10-FEB-08:20 | 140384.76 | 22-FEB-16:30 | 22524.26 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 166675.44 | 21-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73699.04 | 21-MAR-07:19 | 172978.96 | 16-MAR-15:50 | 39912.22 | 20-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 157948.69 | 04-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73694.46 | 04-APR-07:19 | 222074.93 | 25-APR-15:20 | 38430.93 | 14-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 156033.92 | 26-MAY-08:30 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73693.22 | 26-MAY-07:19 | 222810.93 | 18-MAY-15:09 | 38406.83 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 154747.88 | 27-JUN-07:10 | 31088.59 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 73692.78 | 27-JUN-07:19 | 254980.94 | 19-JUN-14:00 | 43724.11 | 19-JUN-14:50 | 0.00 | 01-JUN-00:10 |
July | 156561.45 | 13-JUL-15:00 | 31088.59 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 73693.37 | 27-JUL-07:19 | 246336.75 | 21-JUL-15:39 | 40759.40 | 11-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 169360.07 | 04-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73700.45 | 04-AUG-07:19 | 242573.48 | 08-AUG-15:20 | 42181.03 | 23-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 161166.93 | 29-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73696.15 | 29-SEP-07:19 | 224304.04 | 05-SEP-15:00 | 42412.22 | 28-SEP-13:20 | 0.00 | 01-SEP-00:10 |
October | 167061.90 | 27-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73699.24 | 27-OCT-07:19 | 201406.46 | 02-OCT-15:00 | 42681.17 | 05-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 179838.04 | 28-NOV-16:30 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73699.50 | 01-NOV-07:19 | 160043.62 | 02-NOV-15:00 | 46806.67 | 02-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 179838.04 | 01-DEC-16:30 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73701.12 | 12-DEC-08:20 | 134263.13 | 22-DEC-16:00 | 22416.24 | 06-DEC-08:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 154747.88 | 31088.59 | 423497.50 | 73692.78 | 134263.13 | 22416.24 | 0.00 | |||||||
Maximum of Months | 179838.04 | 31088.59 | 778371.69 | 73702.22 | 254980.94 | 46806.67 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 224852.68 | 31-JAN-15:50 | 46107.13 | 31-JAN-14:50 | 100000.00 | 01-JAN-13:30 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 110294.18 | 22-FEB-14:09 | 44908.80 | 22-FEB-14:09 | 100000.00 | 01-FEB-22:10 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 300522.91 | 20-MAR-14:39 | 59417.20 | 16-MAR-15:09 | 100000.00 | 08-MAR-05:19 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 354530.38 | 14-APR-14:00 | 75058.17 | 10-APR-14:20 | 100000.00 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 258351.40 | 31-MAY-15:50 | 75058.17 | 04-MAY-14:50 | 100000.00 | 01-MAY-00:20 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 356240.89 | 28-JUN-14:00 | 75058.17 | 01-JUN-08:39 | 100000.00 | 02-JUN-02:49 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 399908.67 | 19-JUL-13:39 | 75058.17 | 01-JUL-13:00 | 100000.00 | 01-JUL-01:10 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 415440.83 | 11-AUG-15:50 | 75058.17 | 01-AUG-05:30 | 100000.00 | 22-AUG-20:49 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 309572.15 | 01-SEP-12:30 | 75058.17 | 01-SEP-06:10 | 100000.00 | 18-SEP-03:09 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 312590.33 | 02-OCT-14:09 | 75058.17 | 02-OCT-07:19 | 100000.00 | 06-OCT-01:19 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 304145.68 | 20-NOV-16:10 | 75058.17 | 01-NOV-12:50 | 100000.00 | 03-NOV-21:10 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 262877.10 | 22-DEC-15:30 | 45669.27 | 22-DEC-15:39 | 100000.00 | 01-DEC-05:00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 110294.18 | 44908.80 | 100000.00 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 415440.83 | 75058.17 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1151740.42 | 27-JAN-16:40 | 154688.45 | 423497.50 | 0.00 | 52594.17 | 122458.97 | 38162.82 | 0.00 | 214863.42 | 45475.09 |
February | 1155623.80 | 22-FEB-16:30 | 154688.45 | 541788.89 | 0.00 | 52594.17 | 140384.76 | 20687.37 | 0.00 | 100785.46 | 44694.70 |
March | 1465451.14 | 17-MAR-15:20 | 154688.45 | 660080.29 | 0.00 | 52594.17 | 164916.87 | 22444.03 | 0.00 | 256353.06 | 59417.20 |
April | 1751181.87 | 12-APR-15:50 | 154688.45 | 778371.69 | 0.00 | 52594.17 | 213372.86 | 38364.53 | 0.00 | 338732.02 | 75058.17 |
May | 1209840.31 | 16-MAY-15:50 | 154688.45 | 423497.50 | 0.00 | 52594.17 | 211359.71 | 38345.42 | 0.00 | 253339.81 | 75058.17 |
June | 1443466.88 | 19-JUN-14:50 | 154688.45 | 541788.89 | 0.00 | 24462.73 | 253903.01 | 43724.11 | 0.00 | 349841.52 | 75058.17 |
July | 1605531.15 | 20-JUL-15:09 | 154688.45 | 660080.29 | 0.00 | 52594.17 | 240623.59 | 40003.64 | 0.00 | 382482.84 | 75058.17 |
August | 1840073.21 | 25-AUG-15:09 | 154688.45 | 778371.69 | 0.00 | 52594.17 | 236794.68 | 38718.06 | 0.00 | 403847.99 | 75058.17 |
September | 1236515.16 | 06-SEP-15:00 | 154688.45 | 423497.50 | 0.00 | 52594.17 | 212950.69 | 39864.30 | 0.00 | 277861.88 | 75058.17 |
October | 1351886.15 | 02-OCT-15:00 | 154688.45 | 541788.89 | 0.00 | 52594.17 | 201406.46 | 39334.71 | 0.00 | 287015.30 | 75058.17 |
November | 1473850.99 | 20-NOV-16:10 | 155628.63 | 660080.29 | 0.00 | 52594.61 | 118135.98 | 38926.22 | 0.00 | 304145.68 | 44339.57 |
December | 1538561.50 | 22-DEC-16:00 | 162165.84 | 778371.69 | 0.00 | 52597.16 | 134263.13 | 20887.03 | 0.00 | 245066.32 | 45210.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1151740.42 | 154688.45 | 423497.50 | 0.00 | 24462.73 | 118135.98 | 20687.37 | 0.00 | 100785.46 | 44339.57 | |
Maximum of Months | 1840073.21 | 162165.84 | 778371.69 | 0.00 | 52597.16 | 253903.01 | 43724.11 | 0.00 | 403847.99 | 75058.17 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 411446.18 | 02-JAN-06:10 | 0.00 | 76828.17 | 23-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 273392.96 | 13-FEB-06:10 | 0.00 | 76763.55 | 01-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 402423.89 | 27-MAR-06:10 | 0.00 | 75563.90 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 14004.87 | 21-APR-06:10 | 0.00 | 71206.30 | 05-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 67761.52 | 04-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 62657.72 | 05-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 59343.43 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 60847.90 | 30-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 3.33 | 02-SEP-11:50 | 0.00 | 64697.30 | 25-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 166457.60 | 25-OCT-06:10 | 0.00 | 69387.71 | 24-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 273360.48 | 24-NOV-06:10 | 0.00 | 73015.56 | 20-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 557558.16 | 06-DEC-07:10 | 0.00 | 76246.22 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59343.43 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 557558.16 | 0.00 | 76828.17 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.26 | 1.83 | 27.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.45 | 0.00 | 26.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.82 | 0.00 | 25.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.73 | 0.00 | 26.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.48 | 0.00 | 26.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.23 | 0.00 | 26.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.40 | 0.33 | 26.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.05 | 0.67 | 26.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.87 | 1.67 | 26.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.03 | 1.00 | 27.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.03 | 1.67 | 27.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.05 | 0.83 | 27.09 |
Annual Sum or Average | 0.00 | 0.00 | 75.33 | 26.72 | 8.00 | 26.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.82 | 0.00 | 25.82 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.26 | 1.83 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.71 | 0.00 | 25.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.89 | 0.00 | 25.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.71 | 0.00 | 25.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.60 | 0.00 | 25.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.66 | 0.33 | 25.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.82 | 0.00 | 25.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 25.67 | 0.33 | 25.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.89 | 0.33 | 25.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.07 | 0.00 | 19.07 | 0.17 | 22.32 | 0.00 | 22.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.07 | 0.00 | 19.07 | 0.17 | 25.58 | 0.00 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.83 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.32 | 0.67 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.31 | 5.17 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.16 | 7.67 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.07 | 5.67 | 27.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.12 | 2.50 | 27.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.81 | 0.67 | 27.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 42.67 | 27.17 | 23.17 | 27.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.32 | 7.67 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 1.00 | 27.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.78 | 9.83 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.83 | 13.17 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.81 | 11.17 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.61 | 14.17 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.68 | 9.33 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.57 | 9.00 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.51 | 5.67 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Annual Sum or Average | 0.00 | 0.00 | 92.33 | 27.69 | 75.50 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.83 | 14.17 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.18 | 11.33 | 27.18 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.62 | 2.17 | 27.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.40 | 1.00 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.71 | 7.67 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.40 | 6.33 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.28 | 5.83 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.22 | 9.83 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.26 | 7.33 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.19 | 9.17 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 26.74 | 15.17 | 26.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 26.05 | 16.83 | 26.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.91 | 13.17 | 26.91 |
Annual Sum or Average | 0.00 | 0.00 | 132.17 | 27.03 | 105.83 | 27.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.05 | 1.00 | 26.05 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.71 | 16.83 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.86 | 3.83 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.85 | 1.17 | 27.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.70 | 3.67 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 27.76 | 17.50 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.91 | 8.33 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 27.58 | 16.50 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 | 27.67 | 22.33 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 27.86 | 21.17 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.32 | 9.33 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.60 | 7.67 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.72 | 5.33 | 27.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.89 | 5.83 | 27.94 |
Annual Sum or Average | 0.00 | 0.00 | 323.50 | 27.71 | 122.67 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.32 | 1.17 | 27.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 27.91 | 22.33 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.34 | 0.67 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.39 | 5.50 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.44 | 7.50 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.30 | 3.67 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.43 | 2.67 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 0.33 | 19.30 | 0.00 | 19.30 | 33.50 | 27.31 | 20.67 | 27.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.34 | 0.00 | 19.34 | 11.67 | 27.44 | 7.50 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.84 | 11.50 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.98 | 13.00 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.90 | 11.50 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.71 | 15.00 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.76 | 10.50 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.72 | 9.17 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.55 | 6.17 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Annual Sum or Average | 0.33 | 19.40 | 0.00 | 19.40 | 100.83 | 27.77 | 77.33 | 27.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.40 | 0.00 | 19.40 | 22.50 | 27.98 | 15.00 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 25.68 | 31.00 | 25.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.65 | 1.83 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.70 | 6.33 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.42 | 6.00 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.40 | 5.67 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.43 | 9.17 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.52 | 5.83 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.99 | 11.00 | 27.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 25.91 | 28.33 | 25.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 25.69 | 24.83 | 25.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 26.28 | 16.17 | 26.28 |
Annual Sum or Average | 0.00 | 0.00 | 163.83 | 26.43 | 147.00 | 26.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.68 | 0.83 | 25.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.70 | 31.00 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.64 | 1.83 | 27.64 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.67 | 0.17 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.50 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.27 | 5.17 | 28.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.34 | 6.17 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.65 | 8.17 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 27.60 | 11.33 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.55 | 6.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.56 | 6.17 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.84 | 4.83 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.64 | 1.83 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.78 | 1.00 | 27.78 |
Annual Sum or Average | 0.00 | 0.00 | 126.33 | 27.75 | 54.00 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.55 | 0.17 | 27.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 28.34 | 11.33 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 0.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.37 | 1.33 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.48 | 4.00 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.54 | 7.83 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.47 | 10.33 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.53 | 5.17 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.46 | 5.33 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.33 | 1.50 | 27.42 |
November | 0.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 2.83 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 5.00 | 18.88 | 0.00 | 18.88 | 62.67 | 26.85 | 35.50 | 27.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 0.00 | 18.66 |
Maximum of Months | 2.83 | 19.30 | 0.00 | 19.30 | 20.00 | 27.54 | 10.33 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
February | 0.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 0.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.85 | 11.83 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 28.05 | 13.00 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.96 | 11.67 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.77 | 15.50 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.78 | 10.67 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.78 | 9.50 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.50 | 6.17 | 27.55 |
November | 0.17 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
December | 2.67 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Annual Sum or Average | 3.50 | 18.81 | 0.00 | 18.81 | 120.67 | 27.59 | 78.33 | 27.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 0.00 | 18.33 |
Maximum of Months | 2.67 | 19.09 | 0.00 | 19.09 | 29.33 | 28.05 | 15.50 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.49 | 0.00 | 18.49 | 6.00 | 27.86 | 6.00 | 27.99 |
February | 0.17 | 19.14 | 0.00 | 19.14 | 1.17 | 26.39 | 1.17 | 26.87 |
March | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.79 | 7.17 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.61 | 6.83 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.52 | 7.17 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.49 | 10.67 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.66 | 6.83 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.43 | 9.50 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.74 | 9.33 | 27.79 |
November | 0.17 | 19.34 | 0.00 | 19.34 | 5.33 | 27.52 | 5.33 | 27.64 |
December | 1.17 | 18.98 | 0.00 | 18.98 | 5.00 | 26.36 | 5.00 | 27.13 |
Annual Sum or Average | 1.83 | 19.00 | 0.00 | 19.00 | 109.50 | 27.50 | 75.00 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 0.00 | 19.22 |
Maximum of Months | 1.17 | 19.34 | 0.00 | 19.34 | 20.50 | 27.86 | 10.67 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.33 | 0.00 | 18.33 | 1.00 | 26.20 | 1.00 | 26.81 |
February | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
March | 0.17 | 19.39 | 0.00 | 19.39 | 0.33 | 24.98 | 0.17 | 25.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.32 | 5.83 | 28.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.40 | 6.83 | 28.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 27.81 | 9.67 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 27.74 | 13.00 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.72 | 7.17 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.64 | 6.83 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.88 | 4.50 | 28.00 |
November | 0.17 | 19.26 | 0.00 | 19.26 | 0.83 | 26.24 | 0.83 | 26.87 |
December | 1.17 | 18.91 | 0.00 | 18.91 | 0.67 | 22.07 | 0.67 | 23.54 |
Annual Sum or Average | 1.83 | 18.98 | 0.00 | 18.98 | 140.67 | 27.75 | 56.50 | 27.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 0.00 | 19.42 |
Maximum of Months | 1.17 | 19.42 | 0.00 | 19.42 | 37.17 | 28.40 | 13.00 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 373.17 | 28.92 | 289.83 | 28.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.57 | 0.00 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 334.50 | 28.82 | 276.50 | 28.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 28.15 | 26.83 | 28.15 |
Annual Sum or Average | 0.00 | 0.00 | 736.17 | 28.85 | 593.17 | 28.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 373.17 | 28.92 | 289.83 | 28.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 339.83 | 28.73 | 267.67 | 28.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.56 | 0.00 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 278.17 | 28.62 | 235.00 | 28.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.98 | 6.17 | 27.98 |
Annual Sum or Average | 0.00 | 0.00 | 624.50 | 28.67 | 508.83 | 28.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 339.83 | 28.73 | 267.67 | 28.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 281.17 | 28.82 | 222.17 | 28.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.84 | 0.00 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 237.33 | 28.73 | 198.67 | 28.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.69 | 1.17 | 27.69 |
Annual Sum or Average | 0.00 | 0.00 | 522.00 | 28.77 | 422.00 | 28.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 281.17 | 28.82 | 222.17 | 28.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 311.50 | 31.45 | 278.50 | 31.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 | 28.31 | 20.67 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 667.50 | 31.05 | 486.83 | 31.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.12 | 9.33 | 28.12 |
Annual Sum or Average | 0.00 | 0.00 | 1032.50 | 31.03 | 795.33 | 31.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 667.50 | 31.45 | 486.83 | 31.52 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 124.33 | 24.00 | 108.67 | 25.05 | 0.00 | 25.05 |
February | 49.17 | 24.00 | 178.00 | 24.88 | 0.00 | 24.88 |
March | 106.67 | 24.01 | 91.17 | 24.80 | 0.00 | 24.80 |
April | 123.00 | 24.00 | 85.67 | 25.00 | 0.00 | 25.00 |
May | 159.17 | 24.00 | 70.83 | 24.76 | 0.00 | 24.76 |
June | 46.00 | 24.00 | 105.67 | 25.27 | 0.00 | 25.27 |
July | 162.67 | 24.38 | 408.83 | 24.64 | 150.00 | 24.59 |
August | 159.83 | 24.51 | 446.83 | 24.54 | 156.17 | 24.54 |
September | 113.17 | 24.85 | 386.33 | 24.75 | 113.17 | 24.77 |
October | 77.33 | 24.06 | 205.00 | 25.04 | 14.17 | 25.01 |
November | 79.83 | 24.49 | 194.83 | 25.18 | 20.00 | 25.23 |
December | 174.00 | 24.00 | 98.50 | 24.93 | 0.00 | 24.93 |
Annual Sum or Average | 1375.17 | 24.21 | 2380.33 | 24.83 | 453.50 | 24.81 |
Minimum of Months | 46.00 | 24.00 | 70.83 | 24.54 | 0.00 | 24.54 |
Maximum of Months | 174.00 | 24.85 | 446.83 | 25.27 | 156.17 | 25.27 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 129.67 | 23.99 | 67.17 | 24.52 | 0.00 | 24.52 |
February | 33.00 | 23.99 | 181.50 | 24.62 | 0.00 | 24.62 |
March | 74.83 | 24.01 | 97.17 | 24.64 | 0.00 | 24.64 |
April | 68.50 | 24.01 | 32.50 | 24.40 | 0.00 | 24.40 |
May | 100.00 | 24.01 | 31.83 | 24.46 | 0.00 | 24.46 |
June | 15.50 | 24.00 | 88.50 | 24.52 | 0.00 | 24.52 |
July | 11.83 | 24.01 | 396.00 | 24.25 | 0.33 | 24.25 |
August | 0.17 | 24.00 | 456.33 | 24.27 | 0.17 | 24.27 |
September | 20.83 | 25.41 | 387.83 | 24.45 | 20.83 | 24.50 |
October | 70.67 | 24.01 | 192.00 | 24.61 | 1.67 | 24.61 |
November | 83.83 | 24.17 | 174.50 | 24.64 | 7.67 | 24.68 |
December | 184.00 | 24.01 | 76.67 | 24.55 | 0.00 | 24.55 |
Annual Sum or Average | 792.83 | 24.06 | 2182.00 | 24.46 | 30.67 | 24.47 |
Minimum of Months | 0.17 | 23.99 | 31.83 | 24.25 | 0.00 | 24.25 |
Maximum of Months | 184.00 | 25.41 | 456.33 | 24.64 | 20.83 | 24.68 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 333.50 | 23.74 | 16.00 | 23.78 | 0.00 | 23.78 |
February | 172.83 | 23.69 | 53.33 | 23.87 | 0.00 | 23.87 |
March | 202.83 | 23.88 | 50.00 | 24.06 | 0.00 | 24.06 |
April | 210.33 | 24.01 | 13.33 | 24.10 | 0.00 | 24.10 |
May | 182.83 | 24.02 | 14.33 | 24.15 | 0.00 | 24.15 |
June | 58.50 | 24.00 | 42.83 | 24.19 | 0.00 | 24.19 |
July | 47.50 | 24.18 | 371.33 | 24.20 | 27.33 | 24.21 |
August | 78.17 | 24.30 | 416.83 | 24.20 | 60.17 | 24.22 |
September | 53.50 | 24.79 | 378.33 | 24.40 | 53.33 | 24.45 |
October | 173.83 | 23.95 | 129.83 | 24.21 | 4.00 | 24.21 |
November | 263.00 | 23.92 | 110.33 | 24.11 | 25.33 | 24.13 |
December | 430.17 | 23.81 | 0.00 | 23.81 | 0.00 | 23.81 |
Annual Sum or Average | 2207.00 | 23.91 | 1596.50 | 24.10 | 170.17 | 24.11 |
Minimum of Months | 47.50 | 23.69 | 0.00 | 23.78 | 0.00 | 23.78 |
Maximum of Months | 430.17 | 24.79 | 416.83 | 24.40 | 60.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.00 | 23.12 | 18.50 | 22.98 | 18.50 | 22.85 |
February | 374.67 | 22.93 | 6.33 | 22.91 | 3.83 | 22.89 |
March | 332.67 | 23.40 | 20.00 | 23.40 | 5.67 | 23.36 |
April | 198.00 | 23.92 | 15.00 | 24.01 | 0.00 | 24.01 |
May | 165.00 | 24.01 | 23.67 | 24.20 | 0.00 | 24.20 |
June | 34.83 | 23.99 | 95.50 | 24.47 | 0.00 | 24.47 |
July | 58.33 | 24.13 | 392.50 | 24.30 | 41.83 | 24.29 |
August | 92.83 | 24.23 | 437.50 | 24.23 | 82.17 | 24.23 |
September | 75.83 | 24.54 | 383.33 | 24.42 | 75.83 | 24.44 |
October | 235.33 | 23.69 | 113.00 | 23.92 | 7.17 | 23.93 |
November | 341.83 | 23.19 | 81.83 | 23.38 | 27.00 | 23.41 |
December | 493.33 | 22.69 | 40.17 | 22.55 | 40.17 | 22.43 |
Annual Sum or Average | 2864.67 | 23.32 | 1627.33 | 23.64 | 302.17 | 23.62 |
Minimum of Months | 34.83 | 22.69 | 6.33 | 22.55 | 0.00 | 22.43 |
Maximum of Months | 493.33 | 24.54 | 437.50 | 24.47 | 82.17 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 457.83 | 23.51 | 9.67 | 23.53 | 0.00 | 23.53 |
February | 314.83 | 23.31 | 12.67 | 23.34 | 0.00 | 23.34 |
March | 276.00 | 23.56 | 37.50 | 23.68 | 0.00 | 23.68 |
April | 128.50 | 23.96 | 68.50 | 24.45 | 0.00 | 24.45 |
May | 66.33 | 24.00 | 78.50 | 24.96 | 0.00 | 24.96 |
June | 15.50 | 26.40 | 272.67 | 24.85 | 12.50 | 24.94 |
July | 35.00 | 26.50 | 455.17 | 24.70 | 33.67 | 24.82 |
August | 25.83 | 26.67 | 478.50 | 24.53 | 25.00 | 24.63 |
September | 37.83 | 26.33 | 422.33 | 24.66 | 37.83 | 24.79 |
October | 200.33 | 23.84 | 147.33 | 24.18 | 1.83 | 24.19 |
November | 315.33 | 23.68 | 85.17 | 23.83 | 13.67 | 23.87 |
December | 454.00 | 23.43 | 3.00 | 23.43 | 1.17 | 23.43 |
Annual Sum or Average | 2327.33 | 23.71 | 2071.00 | 24.13 | 125.67 | 24.20 |
Minimum of Months | 15.50 | 23.31 | 3.00 | 23.34 | 0.00 | 23.34 |
Maximum of Months | 457.83 | 26.67 | 478.50 | 24.96 | 37.83 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 280.00 | 23.49 | 43.33 | 23.74 | 0.00 | 23.74 |
February | 246.67 | 23.26 | 75.50 | 23.58 | 2.67 | 23.61 |
March | 208.50 | 23.52 | 99.50 | 23.90 | 1.33 | 23.91 |
April | 82.17 | 24.43 | 184.50 | 24.74 | 13.83 | 24.86 |
May | 48.50 | 25.35 | 224.33 | 25.03 | 20.00 | 25.19 |
June | 39.50 | 26.90 | 376.17 | 24.82 | 36.83 | 25.00 |
July | 53.33 | 26.79 | 464.67 | 24.81 | 52.17 | 25.00 |
August | 43.33 | 26.75 | 486.83 | 24.60 | 40.83 | 24.77 |
September | 50.33 | 26.60 | 445.17 | 24.75 | 50.33 | 24.92 |
October | 147.33 | 24.08 | 219.67 | 24.49 | 14.67 | 24.59 |
November | 231.33 | 23.63 | 125.33 | 23.95 | 15.50 | 23.98 |
December | 373.67 | 23.36 | 27.00 | 23.49 | 3.33 | 23.47 |
Annual Sum or Average | 1804.67 | 23.93 | 2772.00 | 24.36 | 251.50 | 24.48 |
Minimum of Months | 39.50 | 23.26 | 27.00 | 23.49 | 0.00 | 23.47 |
Maximum of Months | 373.67 | 26.90 | 486.83 | 25.03 | 52.17 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.50 | 23.96 | 199.33 | 24.41 | 22.17 | 24.57 |
February | 190.67 | 23.31 | 144.83 | 23.80 | 5.00 | 23.85 |
March | 171.83 | 23.44 | 136.00 | 23.94 | 0.17 | 23.95 |
April | 91.67 | 24.20 | 177.17 | 24.63 | 7.00 | 24.70 |
May | 78.33 | 24.01 | 108.67 | 24.79 | 0.00 | 24.79 |
June | 24.67 | 25.71 | 258.17 | 24.82 | 14.17 | 24.92 |
July | 40.67 | 26.37 | 446.67 | 24.71 | 35.83 | 24.85 |
August | 32.33 | 26.78 | 485.50 | 24.58 | 31.00 | 24.71 |
September | 48.17 | 26.69 | 444.83 | 24.78 | 48.17 | 24.95 |
October | 116.83 | 24.64 | 279.17 | 24.75 | 31.67 | 24.92 |
November | 142.83 | 24.15 | 260.33 | 24.47 | 30.33 | 24.58 |
December | 242.33 | 23.75 | 141.33 | 24.23 | 22.00 | 24.36 |
Annual Sum or Average | 1368.83 | 24.13 | 3082.00 | 24.50 | 247.50 | 24.62 |
Minimum of Months | 24.67 | 23.31 | 108.67 | 23.80 | 0.00 | 23.85 |
Maximum of Months | 242.33 | 26.78 | 485.50 | 24.82 | 48.17 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 187.50 | 23.96 | 104.83 | 24.33 | 6.83 | 24.39 |
February | 62.83 | 24.00 | 208.67 | 24.44 | 3.00 | 24.47 |
March | 46.67 | 24.53 | 253.67 | 24.74 | 8.00 | 24.80 |
April | 40.17 | 27.01 | 341.67 | 25.15 | 37.00 | 25.33 |
May | 28.50 | 26.70 | 264.33 | 25.26 | 23.67 | 25.41 |
June | 40.00 | 27.11 | 418.67 | 24.89 | 40.00 | 25.07 |
July | 94.33 | 26.98 | 481.00 | 25.10 | 94.33 | 25.37 |
August | 107.67 | 26.60 | 509.67 | 24.95 | 107.67 | 25.19 |
September | 62.50 | 26.89 | 464.33 | 24.91 | 62.50 | 25.12 |
October | 73.17 | 25.10 | 299.17 | 24.98 | 26.17 | 25.12 |
November | 77.17 | 24.96 | 248.67 | 24.93 | 24.50 | 25.07 |
December | 142.67 | 24.25 | 136.17 | 24.86 | 10.33 | 24.95 |
Annual Sum or Average | 963.17 | 25.32 | 3730.83 | 24.91 | 444.00 | 25.08 |
Minimum of Months | 28.50 | 23.96 | 104.83 | 24.33 | 3.00 | 24.39 |
Maximum of Months | 187.50 | 27.11 | 509.67 | 25.26 | 107.67 | 25.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.44 | 35.33 | 22.28 | 35.33 | 22.14 |
February | 434.33 | 22.26 | 5.50 | 22.24 | 5.50 | 22.21 |
March | 419.83 | 22.82 | 22.83 | 22.75 | 16.67 | 22.68 |
April | 219.33 | 23.75 | 36.33 | 23.98 | 0.00 | 23.98 |
May | 109.67 | 23.96 | 57.67 | 24.70 | 0.00 | 24.70 |
June | 14.83 | 26.28 | 238.67 | 24.98 | 11.17 | 25.07 |
July | 48.67 | 25.96 | 446.00 | 24.73 | 46.00 | 24.85 |
August | 49.50 | 25.23 | 457.33 | 24.48 | 43.00 | 24.56 |
September | 52.50 | 25.59 | 401.67 | 24.65 | 47.67 | 24.75 |
October | 289.83 | 23.28 | 108.83 | 23.59 | 5.17 | 23.59 |
November | 427.17 | 22.67 | 84.33 | 22.71 | 58.17 | 22.67 |
December | 497.00 | 21.86 | 128.00 | 21.64 | 128.00 | 21.49 |
Annual Sum or Average | 3064.67 | 22.80 | 2022.50 | 23.35 | 396.67 | 23.32 |
Minimum of Months | 14.83 | 21.86 | 5.50 | 21.64 | 0.00 | 21.49 |
Maximum of Months | 502.00 | 26.28 | 457.33 | 24.98 | 128.00 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.83 | 22.91 | 30.00 | 22.93 | 12.50 | 22.84 |
February | 275.83 | 22.59 | 36.33 | 22.80 | 3.00 | 22.78 |
March | 244.50 | 23.06 | 64.33 | 23.38 | 7.83 | 23.32 |
April | 94.50 | 24.45 | 152.00 | 24.92 | 17.50 | 25.07 |
May | 58.17 | 25.43 | 195.00 | 25.26 | 25.67 | 25.45 |
June | 41.83 | 27.06 | 307.00 | 25.09 | 40.33 | 25.30 |
July | 71.17 | 26.65 | 393.33 | 25.09 | 70.33 | 25.29 |
August | 61.33 | 26.46 | 408.67 | 24.84 | 59.17 | 25.03 |
September | 58.17 | 26.53 | 364.50 | 24.95 | 57.33 | 25.14 |
October | 166.17 | 23.71 | 159.83 | 24.33 | 14.00 | 24.44 |
November | 277.17 | 23.09 | 77.00 | 23.31 | 28.17 | 23.31 |
December | 396.33 | 22.68 | 47.33 | 22.49 | 45.50 | 22.34 |
Annual Sum or Average | 2067.00 | 23.49 | 2235.33 | 24.11 | 381.33 | 24.22 |
Minimum of Months | 41.83 | 22.59 | 30.00 | 22.49 | 3.00 | 22.34 |
Maximum of Months | 396.33 | 27.06 | 408.67 | 25.26 | 70.33 | 25.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 224.67 | 23.62 | 206.33 | 24.17 | 29.50 | 24.28 |
February | 240.17 | 22.78 | 135.00 | 23.37 | 6.17 | 23.40 |
March | 237.83 | 23.02 | 117.17 | 23.47 | 6.67 | 23.42 |
April | 131.00 | 23.87 | 149.17 | 24.44 | 4.50 | 24.49 |
May | 103.83 | 23.93 | 91.00 | 24.69 | 0.00 | 24.69 |
June | 26.00 | 25.20 | 229.67 | 24.88 | 10.17 | 24.97 |
July | 61.00 | 25.81 | 439.33 | 24.74 | 54.67 | 24.87 |
August | 58.50 | 25.67 | 475.00 | 24.58 | 52.33 | 24.69 |
September | 56.67 | 26.46 | 437.00 | 24.81 | 56.67 | 24.98 |
October | 145.33 | 24.26 | 262.17 | 24.62 | 33.00 | 24.80 |
November | 194.17 | 23.64 | 235.83 | 24.17 | 42.00 | 24.26 |
December | 276.00 | 23.18 | 143.17 | 23.67 | 37.67 | 23.70 |
Annual Sum or Average | 1755.17 | 23.71 | 2920.83 | 24.30 | 333.33 | 24.40 |
Minimum of Months | 26.00 | 22.78 | 91.00 | 23.37 | 0.00 | 23.40 |
Maximum of Months | 276.00 | 26.46 | 475.00 | 24.88 | 56.67 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 365.33 | 22.96 | 67.67 | 23.11 | 14.00 | 23.04 |
February | 341.33 | 22.70 | 39.00 | 22.88 | 0.17 | 22.88 |
March | 278.67 | 23.11 | 87.67 | 23.40 | 7.00 | 23.38 |
April | 107.00 | 24.41 | 194.00 | 24.77 | 18.67 | 24.91 |
May | 74.83 | 24.92 | 217.17 | 25.07 | 21.00 | 25.22 |
June | 29.67 | 26.83 | 333.83 | 24.96 | 26.83 | 25.11 |
July | 73.00 | 26.59 | 464.17 | 24.96 | 71.17 | 25.16 |
August | 54.17 | 26.42 | 486.83 | 24.71 | 54.17 | 24.86 |
September | 57.33 | 26.43 | 436.17 | 24.82 | 57.33 | 24.99 |
October | 189.67 | 23.79 | 192.33 | 24.24 | 16.00 | 24.35 |
November | 290.83 | 23.18 | 132.33 | 23.54 | 31.33 | 23.56 |
December | 421.50 | 22.60 | 67.33 | 22.54 | 47.33 | 22.40 |
Annual Sum or Average | 2283.33 | 23.44 | 2718.50 | 24.07 | 365.00 | 24.16 |
Minimum of Months | 29.67 | 22.60 | 39.00 | 22.54 | 0.17 | 22.40 |
Maximum of Months | 421.50 | 26.83 | 486.83 | 25.07 | 71.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.84 | 115.50 | 21.52 | 115.50 | 21.31 |
February | 447.00 | 21.60 | 83.67 | 21.38 | 83.67 | 21.22 |
March | 443.17 | 22.35 | 56.83 | 22.16 | 52.17 | 21.99 |
April | 222.50 | 23.51 | 50.67 | 23.81 | 2.00 | 23.79 |
May | 111.50 | 23.88 | 81.50 | 24.62 | 0.33 | 24.62 |
June | 28.83 | 26.23 | 300.50 | 24.88 | 21.17 | 25.01 |
July | 67.83 | 25.93 | 450.00 | 24.78 | 63.17 | 24.92 |
August | 72.00 | 25.20 | 467.33 | 24.51 | 64.17 | 24.60 |
September | 89.17 | 25.17 | 409.50 | 24.64 | 72.17 | 24.76 |
October | 312.83 | 22.90 | 132.67 | 23.17 | 36.50 | 23.10 |
November | 447.00 | 22.11 | 142.33 | 21.94 | 125.33 | 21.79 |
December | 497.00 | 21.15 | 266.50 | 20.91 | 266.50 | 20.79 |
Annual Sum or Average | 3240.83 | 22.39 | 2557.00 | 22.89 | 902.67 | 22.75 |
Minimum of Months | 28.83 | 21.15 | 50.67 | 20.91 | 0.33 | 20.79 |
Maximum of Months | 502.00 | 26.23 | 467.33 | 24.88 | 266.50 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 445.67 | 22.76 | 55.67 | 22.48 | 53.17 | 22.24 |
February | 358.33 | 22.24 | 57.00 | 22.11 | 42.33 | 21.94 |
March | 307.00 | 22.83 | 66.33 | 22.94 | 19.00 | 22.83 |
April | 102.83 | 24.31 | 210.00 | 24.70 | 20.17 | 24.85 |
May | 67.50 | 25.47 | 272.00 | 25.00 | 31.83 | 25.19 |
June | 46.83 | 27.03 | 407.50 | 24.88 | 44.67 | 25.09 |
July | 79.50 | 26.64 | 468.67 | 24.97 | 78.33 | 25.18 |
August | 66.17 | 26.36 | 492.83 | 24.72 | 63.33 | 24.89 |
September | 69.00 | 26.26 | 441.17 | 24.81 | 63.50 | 25.00 |
October | 210.17 | 23.45 | 195.33 | 23.98 | 24.67 | 23.99 |
November | 355.33 | 22.72 | 99.17 | 22.69 | 64.67 | 22.58 |
December | 495.67 | 22.14 | 135.33 | 21.79 | 135.33 | 21.56 |
Annual Sum or Average | 2604.00 | 23.14 | 2901.00 | 23.70 | 641.00 | 23.70 |
Minimum of Months | 46.83 | 22.14 | 55.67 | 21.79 | 19.00 | 21.56 |
Maximum of Months | 495.67 | 27.03 | 492.83 | 25.00 | 135.33 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 252.17 | 22.93 | 189.67 | 23.43 | 42.67 | 23.37 |
February | 284.33 | 22.17 | 129.33 | 22.55 | 30.67 | 22.40 |
March | 280.00 | 22.64 | 110.33 | 22.91 | 25.83 | 22.76 |
April | 153.50 | 23.75 | 162.17 | 24.31 | 11.17 | 24.39 |
May | 113.67 | 23.92 | 123.00 | 24.60 | 3.50 | 24.64 |
June | 41.00 | 25.55 | 278.83 | 24.85 | 21.00 | 24.98 |
July | 73.67 | 25.82 | 442.83 | 24.78 | 67.00 | 24.92 |
August | 74.67 | 25.46 | 480.67 | 24.58 | 67.17 | 24.69 |
September | 75.33 | 25.92 | 434.50 | 24.80 | 70.00 | 24.96 |
October | 175.67 | 23.79 | 257.00 | 24.29 | 40.17 | 24.42 |
November | 237.33 | 22.97 | 220.67 | 23.46 | 59.00 | 23.38 |
December | 319.00 | 22.57 | 169.50 | 22.73 | 90.33 | 22.54 |
Annual Sum or Average | 2080.33 | 23.28 | 2998.50 | 23.93 | 528.50 | 23.94 |
Minimum of Months | 41.00 | 22.17 | 110.33 | 22.55 | 3.50 | 22.40 |
Maximum of Months | 319.00 | 25.92 | 480.67 | 24.85 | 90.33 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 387.67 | 22.37 | 90.67 | 22.30 | 55.33 | 22.08 |
February | 370.83 | 22.09 | 54.83 | 22.10 | 29.67 | 21.98 |
March | 325.67 | 22.68 | 98.00 | 22.86 | 28.33 | 22.73 |
April | 135.33 | 24.24 | 193.83 | 24.63 | 22.17 | 24.79 |
May | 94.00 | 24.80 | 226.67 | 24.96 | 24.00 | 25.12 |
June | 36.67 | 26.71 | 358.33 | 24.93 | 31.50 | 25.10 |
July | 86.50 | 26.39 | 464.17 | 24.97 | 83.00 | 25.17 |
August | 69.17 | 26.01 | 488.83 | 24.70 | 66.83 | 24.85 |
September | 74.33 | 25.98 | 433.83 | 24.81 | 72.17 | 24.97 |
October | 228.00 | 23.39 | 193.83 | 23.92 | 26.67 | 23.99 |
November | 328.33 | 22.64 | 146.17 | 22.83 | 66.33 | 22.71 |
December | 443.67 | 21.98 | 162.17 | 21.71 | 150.17 | 21.50 |
Annual Sum or Average | 2580.17 | 23.01 | 2911.33 | 23.66 | 656.17 | 23.65 |
Minimum of Months | 36.67 | 21.98 | 54.83 | 21.71 | 22.17 | 21.50 |
Maximum of Months | 443.67 | 26.71 | 488.83 | 24.97 | 150.17 | 25.17 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 27.00 | 502.00 | 27.00 | 1.50 | 27.00 |
February | 4.50 | 27.00 | 454.00 | 27.00 | 4.50 | 27.00 |
March | 7.17 | 27.00 | 514.00 | 27.00 | 7.17 | 27.00 |
April | 288.00 | 28.85 | 485.00 | 28.41 | 288.00 | 28.53 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 20.83 | 27.00 | 496.00 | 27.00 | 20.83 | 27.00 |
July | 231.50 | 27.00 | 497.00 | 27.00 | 231.50 | 27.00 |
August | 502.17 | 27.99 | 514.00 | 27.98 | 502.17 | 27.98 |
September | 25.00 | 27.00 | 485.00 | 27.00 | 25.00 | 27.00 |
October | 24.83 | 27.00 | 502.00 | 27.00 | 24.83 | 27.00 |
November | 41.67 | 27.00 | 489.00 | 27.00 | 41.67 | 27.00 |
December | 29.00 | 27.96 | 497.00 | 27.13 | 29.00 | 27.17 |
Annual Sum or Average | 1176.17 | 27.90 | 5943.00 | 27.30 | 1176.17 | 27.39 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 502.17 | 28.85 | 514.00 | 28.41 | 502.17 | 28.53 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 175.00 | 29.03 | 485.00 | 28.24 | 175.00 | 28.40 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 14.33 | 27.00 | 497.00 | 27.00 | 14.33 | 27.00 |
August | 258.17 | 28.42 | 514.00 | 27.97 | 258.17 | 28.08 |
September | 4.17 | 27.00 | 485.00 | 27.00 | 4.17 | 27.00 |
October | 2.00 | 27.00 | 502.00 | 27.00 | 2.00 | 27.00 |
November | 3.67 | 27.00 | 489.00 | 27.00 | 3.67 | 27.00 |
December | 4.33 | 28.06 | 492.50 | 27.03 | 4.33 | 27.04 |
Annual Sum or Average | 461.67 | 28.57 | 5938.50 | 27.25 | 461.67 | 27.34 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 258.17 | 29.03 | 514.00 | 28.24 | 258.17 | 28.40 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.00 | 24.59 | 460.17 | 26.94 | 0.00 | 26.94 |
February | 0.00 | 0.00 | 447.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 499.00 | 27.00 | 0.00 | 27.00 |
April | 163.17 | 29.01 | 485.00 | 28.13 | 163.17 | 28.30 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 20.50 | 27.00 | 496.00 | 27.00 | 20.50 | 27.00 |
July | 77.17 | 27.01 | 497.00 | 27.00 | 77.17 | 27.00 |
August | 245.17 | 28.35 | 514.00 | 27.89 | 245.17 | 28.00 |
September | 21.67 | 27.00 | 485.00 | 27.00 | 21.67 | 27.00 |
October | 5.00 | 27.00 | 502.00 | 27.00 | 5.00 | 27.00 |
November | 4.00 | 27.00 | 471.33 | 27.00 | 4.00 | 27.00 |
December | 0.83 | 27.74 | 399.33 | 27.01 | 0.83 | 27.01 |
Annual Sum or Average | 549.50 | 28.15 | 5764.00 | 27.22 | 537.50 | 27.30 |
Minimum of Months | 0.00 | 0.00 | 399.33 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 245.17 | 29.01 | 514.00 | 28.13 | 245.17 | 28.30 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 381.67 | 27.00 | 502.00 | 27.00 | 381.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.66 | 485.00 | 29.66 | 485.00 | 29.66 |
May | 391.33 | 27.00 | 508.00 | 27.00 | 391.33 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.07 | 497.00 | 27.07 | 497.00 | 27.07 |
August | 514.00 | 31.29 | 514.00 | 31.29 | 514.00 | 31.29 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.02 | 497.00 | 27.02 | 497.00 | 27.02 |
Annual Sum or Average | 5706.00 | 27.62 | 5943.00 | 27.61 | 5706.00 | 27.61 |
Minimum of Months | 381.67 | 27.00 | 454.00 | 27.00 | 381.67 | 27.00 |
Maximum of Months | 514.00 | 31.29 | 514.00 | 31.29 | 514.00 | 31.29 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.79763 | 0.80839 | 18.86366 |
February | 454.00000 | 27.00021 | 29.33818 | 0.88105 | 21.44477 |
March | 514.00000 | 27.00003 | 26.49449 | 0.90373 | 22.32639 |
April | 485.00000 | 28.14171 | 18.09549 | 1.10366 | 31.32393 |
May | 508.00000 | 27.00000 | 17.51796 | 0.13935 | 5.46246 |
June | 496.00000 | 27.00000 | 23.66617 | 0.25397 | 6.43636 |
July | 497.00000 | 27.00063 | 33.22978 | 0.37294 | 7.99221 |
August | 514.00000 | 27.97057 | 33.72118 | 0.68471 | 16.33967 |
September | 485.00000 | 27.00064 | 34.59371 | 0.28580 | 6.77145 |
October | 502.00000 | 27.00010 | 25.22024 | 0.88944 | 21.84101 |
November | 489.00000 | 27.00013 | 24.63595 | 0.90256 | 22.32314 |
December | 497.00000 | 27.07856 | 17.31958 | 0.86787 | 21.06137 |
Annual Sum or Average | 5943.00000 | 27.18383 | 25.53208 | 0.67263 | 16.80015 |
Minimum of Months | 454.00000 | 27.00000 | 17.31958 | 0.13935 | 5.46246 |
Maximum of Months | 514.00000 | 28.14171 | 34.59371 | 1.10366 | 31.32393 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.78128 | 0.73462 | 16.48102 |
February | 454.00000 | 27.00021 | 29.35867 | 0.78702 | 18.14392 |
March | 514.00000 | 27.00003 | 26.46557 | 0.80703 | 18.85612 |
April | 485.00000 | 27.95223 | 18.16331 | 0.97746 | 25.84935 |
May | 508.00000 | 27.00000 | 17.49183 | 0.08979 | 5.23965 |
June | 496.00000 | 27.00000 | 23.64539 | 0.18881 | 5.84223 |
July | 497.00000 | 27.00036 | 33.23913 | 0.27672 | 6.68583 |
August | 514.00000 | 27.74723 | 33.92267 | 0.48100 | 11.02063 |
September | 485.00000 | 27.00054 | 34.66601 | 0.23029 | 6.17839 |
October | 502.00000 | 27.00009 | 25.19890 | 0.81820 | 19.28903 |
November | 489.00000 | 27.00013 | 24.62198 | 0.79668 | 18.55791 |
December | 497.00000 | 27.01866 | 17.33401 | 0.71099 | 15.81487 |
Annual Sum or Average | 5943.00000 | 27.14401 | 25.55370 | 0.57284 | 13.94938 |
Minimum of Months | 454.00000 | 27.00000 | 17.33401 | 0.08979 | 5.23965 |
Maximum of Months | 514.00000 | 27.95223 | 34.66601 | 0.97746 | 25.84935 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94007 | 22.94978 | 0.67518 | 15.01360 |
February | 454.00000 | 27.00021 | 29.40666 | 0.73282 | 16.49821 |
March | 514.00000 | 27.00003 | 26.48751 | 0.77356 | 17.83998 |
April | 485.00000 | 27.82866 | 18.24519 | 0.95575 | 25.14021 |
May | 508.00000 | 27.00000 | 17.50344 | 0.10218 | 5.36178 |
June | 496.00000 | 27.00000 | 23.65611 | 0.21695 | 6.14648 |
July | 497.00000 | 27.00156 | 33.24293 | 0.30442 | 7.08254 |
August | 514.00000 | 27.66581 | 33.99483 | 0.48100 | 11.26453 |
September | 485.00000 | 27.00059 | 34.65770 | 0.24418 | 6.36855 |
October | 502.00000 | 27.00010 | 25.21518 | 0.80046 | 18.77754 |
November | 489.00000 | 27.00013 | 24.64349 | 0.75194 | 17.22103 |
December | 497.00000 | 27.00434 | 17.35332 | 0.63758 | 13.83387 |
Annual Sum or Average | 5943.00000 | 27.12073 | 25.59270 | 0.55455 | 13.34070 |
Minimum of Months | 454.00000 | 26.94007 | 17.35332 | 0.10218 | 5.36178 |
Maximum of Months | 514.00000 | 27.82866 | 34.65770 | 0.95575 | 25.14021 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99995 | 25.63290 | 1.02845 | 27.37773 |
February | 454.00000 | 27.00014 | 31.02351 | 1.20451 | 35.48904 |
March | 514.00000 | 27.00147 | 25.77504 | 1.30173 | 40.38819 |
April | 485.00000 | 29.65782 | 16.73832 | 1.87188 | 67.43427 |
May | 508.00000 | 27.00051 | 26.51011 | 0.43696 | 9.07976 |
June | 496.00000 | 27.00302 | 29.57393 | 0.68783 | 14.97267 |
July | 497.00000 | 27.07307 | 36.03167 | 0.99331 | 26.04826 |
August | 514.00000 | 31.29276 | 32.12628 | 2.35988 | 83.97160 |
September | 485.00000 | 27.00127 | 38.34159 | 0.62526 | 13.34919 |
October | 502.00000 | 27.00117 | 27.41990 | 1.23857 | 37.21223 |
November | 489.00000 | 27.00251 | 25.50669 | 1.35492 | 43.17895 |
December | 497.00000 | 27.02429 | 17.88539 | 1.41349 | 46.24517 |
Annual Sum or Average | 5943.00000 | 27.59715 | 27.69604 | 1.21150 | 37.13956 |
Minimum of Months | 454.00000 | 26.99995 | 16.73832 | 0.43696 | 9.07976 |
Maximum of Months | 514.00000 | 31.29276 | 38.34159 | 2.35988 | 83.97160 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54694 | 20.62215 | 0.35874 | 8.30684 |
February | 454.00000 | 24.46831 | 32.86780 | 0.41877 | 9.27933 |
March | 514.00000 | 24.38076 | 26.14322 | 0.35398 | 8.03380 |
April | 485.00000 | 24.51460 | 18.72865 | 0.34002 | 7.86339 |
May | 508.00000 | 24.47480 | 18.09853 | -0.5370 | 11.84844 |
June | 496.00000 | 24.44123 | 25.59173 | -0.4847 | 10.84090 |
July | 497.00000 | 24.61878 | 45.55155 | -0.2751 | 7.87587 |
August | 514.00000 | 24.48668 | 48.01305 | -0.2770 | 7.76287 |
September | 485.00000 | 24.57293 | 46.99335 | -0.2639 | 8.04777 |
October | 502.00000 | 24.61442 | 26.67492 | 0.43754 | 9.91744 |
November | 489.00000 | 24.60903 | 26.49036 | 0.43300 | 9.90968 |
December | 497.00000 | 24.59647 | 14.70480 | 0.33828 | 8.08495 |
Annual Sum or Average | 5943.00000 | 24.52680 | 29.18481 | 0.06668 | 8.98069 |
Minimum of Months | 454.00000 | 24.38076 | 14.70480 | -0.5370 | 7.76287 |
Maximum of Months | 514.00000 | 24.61878 | 48.01305 | 0.43754 | 11.84844 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32069 | 22.22740 | 0.32254 | 7.45087 |
February | 454.00000 | 24.32237 | 34.30908 | 0.40430 | 8.78157 |
March | 514.00000 | 24.28068 | 27.12059 | 0.35954 | 7.98613 |
April | 485.00000 | 24.24850 | 20.00628 | 0.32831 | 7.40238 |
May | 508.00000 | 24.26488 | 19.42959 | -0.5531 | 11.70277 |
June | 496.00000 | 24.17423 | 27.45086 | -0.5076 | 10.62943 |
July | 497.00000 | 24.25380 | 45.71372 | -0.3466 | 7.88573 |
August | 514.00000 | 24.24457 | 47.76954 | -0.3130 | 7.43610 |
September | 485.00000 | 24.32189 | 47.19681 | -0.3314 | 7.92741 |
October | 502.00000 | 24.37883 | 27.88522 | 0.39950 | 8.82412 |
November | 489.00000 | 24.39308 | 27.29143 | 0.39500 | 8.84156 |
December | 497.00000 | 24.40364 | 16.36733 | 0.31242 | 7.38798 |
Annual Sum or Average | 5943.00000 | 24.30020 | 30.20453 | 0.03564 | 8.52273 |
Minimum of Months | 454.00000 | 24.17423 | 16.36733 | -0.5531 | 7.38798 |
Maximum of Months | 514.00000 | 24.40364 | 47.76954 | 0.40430 | 11.70277 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.94178 | 24.01020 | 0.21085 | 6.34292 |
February | 454.00000 | 23.96280 | 36.57475 | 0.29604 | 7.01846 |
March | 514.00000 | 24.09104 | 28.51332 | 0.28401 | 6.92072 |
April | 485.00000 | 24.17207 | 20.28030 | 0.27243 | 6.70037 |
May | 508.00000 | 24.20359 | 19.48415 | -0.5989 | 12.73790 |
June | 496.00000 | 24.12685 | 27.22560 | -0.5557 | 11.61619 |
July | 497.00000 | 24.20460 | 46.23592 | -0.4064 | 8.80270 |
August | 514.00000 | 24.16949 | 48.98587 | -0.3958 | 8.56662 |
September | 485.00000 | 24.27537 | 47.47752 | -0.3768 | 8.50194 |
October | 502.00000 | 24.22186 | 28.68105 | 0.33554 | 7.74279 |
November | 489.00000 | 24.13084 | 29.13510 | 0.29966 | 7.43707 |
December | 497.00000 | 23.88252 | 18.35698 | 0.14991 | 5.70824 |
Annual Sum or Average | 5943.00000 | 24.11607 | 31.21397 | -0.0438 | 8.18983 |
Minimum of Months | 454.00000 | 23.88252 | 18.35698 | -0.5989 | 5.70824 |
Maximum of Months | 514.00000 | 24.27537 | 48.98587 | 0.33554 | 12.73790 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19768 | 25.10635 | 0.01369 | 6.56941 |
February | 454.00000 | 23.11487 | 38.84144 | 0.07538 | 6.08702 |
March | 514.00000 | 23.65329 | 29.61548 | 0.16552 | 6.34697 |
April | 485.00000 | 24.13937 | 20.41830 | 0.26890 | 6.74022 |
May | 508.00000 | 24.22572 | 19.59684 | -0.5757 | 12.24446 |
June | 496.00000 | 24.19667 | 27.19013 | -0.5010 | 10.61583 |
July | 497.00000 | 24.29616 | 46.05069 | -0.3471 | 8.08317 |
August | 514.00000 | 24.21872 | 49.03364 | -0.3546 | 8.02366 |
September | 485.00000 | 24.31833 | 47.66410 | -0.3456 | 8.17631 |
October | 502.00000 | 24.00254 | 29.15707 | 0.27481 | 7.28956 |
November | 489.00000 | 23.48236 | 30.31438 | 0.12804 | 6.81569 |
December | 497.00000 | 22.70349 | 19.70996 | -0.1541 | 6.84367 |
Annual Sum or Average | 5943.00000 | 23.80057 | 31.84724 | -0.1149 | 7.83760 |
Minimum of Months | 454.00000 | 22.70349 | 19.59684 | -0.5757 | 6.08702 |
Maximum of Months | 514.00000 | 24.31833 | 49.03364 | 0.27481 | 12.24446 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.57045 | 23.08105 | 0.10738 | 5.70102 |
February | 454.00000 | 23.52848 | 35.58546 | 0.17590 | 6.17518 |
March | 514.00000 | 23.83227 | 27.31343 | 0.21861 | 6.57538 |
April | 485.00000 | 24.27473 | 19.19441 | 0.32966 | 7.69597 |
May | 508.00000 | 24.37970 | 18.17236 | -0.4812 | 10.57299 |
June | 496.00000 | 24.42031 | 25.77728 | -0.3363 | 8.50641 |
July | 497.00000 | 24.51706 | 44.20545 | -0.1885 | 6.95345 |
August | 514.00000 | 24.38632 | 46.50693 | -0.2132 | 6.95013 |
September | 485.00000 | 24.44646 | 46.07124 | -0.2540 | 7.51139 |
October | 502.00000 | 24.17018 | 27.51486 | 0.32826 | 8.14088 |
November | 489.00000 | 23.84891 | 27.71526 | 0.22331 | 6.83440 |
December | 497.00000 | 23.51126 | 17.07214 | 0.04875 | 5.78534 |
Annual Sum or Average | 5943.00000 | 24.07730 | 29.81277 | -0.0056 | 7.29317 |
Minimum of Months | 454.00000 | 23.51126 | 17.07214 | -0.4812 | 5.70102 |
Maximum of Months | 514.00000 | 24.51706 | 46.50693 | 0.32966 | 10.57299 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87799 | 21.83505 | 0.21258 | 6.77097 |
February | 454.00000 | 23.69197 | 34.62401 | 0.24317 | 7.22661 |
March | 514.00000 | 23.95619 | 26.64823 | 0.28356 | 7.58240 |
April | 485.00000 | 24.37636 | 18.74886 | 0.42023 | 9.66143 |
May | 508.00000 | 24.49454 | 17.81597 | -0.3336 | 9.06554 |
June | 496.00000 | 24.45960 | 25.55504 | -0.2241 | 7.88520 |
July | 497.00000 | 24.55441 | 43.97635 | -0.0965 | 6.92249 |
August | 514.00000 | 24.39613 | 46.29896 | -0.1395 | 6.96402 |
September | 485.00000 | 24.49314 | 45.66775 | -0.1670 | 7.20328 |
October | 502.00000 | 24.30400 | 26.83598 | 0.41117 | 9.88058 |
November | 489.00000 | 23.96776 | 27.15332 | 0.28056 | 7.56418 |
December | 497.00000 | 23.65035 | 16.53621 | 0.10287 | 6.42356 |
Annual Sum or Average | 5943.00000 | 24.18837 | 29.27269 | 0.08079 | 7.76450 |
Minimum of Months | 454.00000 | 23.65035 | 16.53621 | -0.3336 | 6.42356 |
Maximum of Months | 514.00000 | 24.55441 | 46.29896 | 0.42023 | 9.88058 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.21362 | 20.73753 | 0.37711 | 9.68554 |
February | 454.00000 | 23.83021 | 33.91170 | 0.30954 | 8.20080 |
March | 514.00000 | 23.99957 | 26.44810 | 0.30833 | 7.97319 |
April | 485.00000 | 24.36505 | 18.86474 | 0.40052 | 9.16175 |
May | 508.00000 | 24.39223 | 18.10560 | -0.4606 | 10.44946 |
June | 496.00000 | 24.39525 | 25.83578 | -0.3558 | 8.82088 |
July | 497.00000 | 24.51502 | 44.18412 | -0.1848 | 7.12625 |
August | 514.00000 | 24.40941 | 46.34388 | -0.1690 | 6.84157 |
September | 485.00000 | 24.53000 | 45.58651 | -0.1468 | 7.17083 |
October | 502.00000 | 24.44481 | 26.37169 | 0.49018 | 11.60702 |
November | 489.00000 | 24.28695 | 26.14941 | 0.42867 | 10.21716 |
December | 497.00000 | 24.09837 | 15.27057 | 0.29014 | 8.94029 |
Annual Sum or Average | 5943.00000 | 24.29248 | 28.95287 | 0.10468 | 8.85291 |
Minimum of Months | 454.00000 | 23.83021 | 15.27057 | -0.4606 | 6.84157 |
Maximum of Months | 514.00000 | 24.53000 | 46.34388 | 0.49018 | 11.60702 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.23219 | 21.17594 | 0.32918 | 8.04758 |
February | 454.00000 | 24.27897 | 33.03210 | 0.41384 | 9.08001 |
March | 514.00000 | 24.40682 | 25.55220 | 0.45356 | 10.03899 |
April | 485.00000 | 24.65331 | 18.30062 | 0.59272 | 13.63279 |
May | 508.00000 | 24.58391 | 17.69603 | -0.2645 | 8.51012 |
June | 496.00000 | 24.57288 | 25.34791 | -0.1132 | 7.47637 |
July | 497.00000 | 24.71026 | 43.53506 | 0.03630 | 7.36829 |
August | 514.00000 | 24.59365 | 45.64177 | 0.08443 | 7.39986 |
September | 485.00000 | 24.61833 | 45.32306 | -0.0777 | 7.14592 |
October | 502.00000 | 24.58830 | 26.20680 | 0.52507 | 12.06596 |
November | 489.00000 | 24.52144 | 25.75923 | 0.48474 | 11.06373 |
December | 497.00000 | 24.49349 | 14.87023 | 0.37415 | 8.85594 |
Annual Sum or Average | 5943.00000 | 24.52222 | 28.50744 | 0.23449 | 9.21514 |
Minimum of Months | 454.00000 | 24.23219 | 14.87023 | -0.2645 | 7.14592 |
Maximum of Months | 514.00000 | 24.71026 | 45.64177 | 0.59272 | 13.63279 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.43633 | 25.46568 | -0.1670 | 7.11319 |
February | 454.00000 | 22.33340 | 39.27500 | -0.1110 | 6.31727 |
March | 514.00000 | 23.04560 | 29.37235 | 0.01460 | 6.48396 |
April | 485.00000 | 24.07838 | 19.28192 | 0.24903 | 6.83050 |
May | 508.00000 | 24.34322 | 17.91052 | -0.5162 | 11.31741 |
June | 496.00000 | 24.44030 | 25.10359 | -0.3518 | 8.75437 |
July | 497.00000 | 24.54655 | 44.38561 | -0.2101 | 7.21391 |
August | 514.00000 | 24.36615 | 47.34443 | -0.2682 | 7.38001 |
September | 485.00000 | 24.42804 | 46.35010 | -0.2830 | 7.87713 |
October | 502.00000 | 23.70298 | 28.50473 | 0.19874 | 7.41360 |
November | 489.00000 | 22.84767 | 30.35830 | -0.0276 | 6.97356 |
December | 497.00000 | 21.85961 | 19.09569 | -0.3556 | 8.94263 |
Annual Sum or Average | 5943.00000 | 23.54394 | 30.98322 | -0.1536 | 7.73197 |
Minimum of Months | 454.00000 | 21.85961 | 17.91052 | -0.5162 | 6.31727 |
Maximum of Months | 514.00000 | 24.54655 | 47.34443 | 0.24903 | 11.31741 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.25113 | 23.24576 | 0.04604 | 6.80076 |
February | 385.00000 | 23.05794 | 36.78772 | 0.07917 | 6.79693 |
March | 433.00000 | 23.63320 | 27.24483 | 0.18201 | 7.34100 |
April | 410.00000 | 24.49375 | 17.89733 | 0.42050 | 9.98754 |
May | 430.00000 | 24.60996 | 16.94880 | -0.3174 | 9.36317 |
June | 418.00000 | 24.60668 | 24.31161 | -0.1914 | 8.13337 |
July | 422.00000 | 24.75160 | 43.36986 | -0.0530 | 7.36177 |
August | 433.00000 | 24.56150 | 46.01658 | -0.1143 | 7.27681 |
September | 410.00000 | 24.61779 | 45.33321 | -0.1519 | 7.60111 |
October | 427.00000 | 24.19230 | 26.63435 | 0.35797 | 9.68891 |
November | 417.00000 | 23.48694 | 28.48836 | 0.14637 | 7.04067 |
December | 422.00000 | 22.78172 | 17.40920 | -0.1271 | 7.29712 |
Annual Sum or Average | 5034.00000 | 24.00888 | 29.41745 | 0.02204 | 7.89565 |
Minimum of Months | 385.00000 | 22.78172 | 16.94880 | -0.3174 | 6.79693 |
Maximum of Months | 433.00000 | 24.75160 | 46.01658 | 0.42050 | 9.98754 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04621 | 21.49644 | 0.34083 | 10.03583 |
February | 454.00000 | 23.46474 | 35.50733 | 0.22379 | 8.08758 |
March | 514.00000 | 23.69374 | 27.30087 | 0.22405 | 7.70616 |
April | 485.00000 | 24.29139 | 18.67067 | 0.35653 | 8.61459 |
May | 508.00000 | 24.36699 | 17.82166 | -0.4875 | 11.06377 |
June | 496.00000 | 24.40908 | 25.17568 | -0.3756 | 9.11023 |
July | 497.00000 | 24.54223 | 44.37583 | -0.2061 | 7.36867 |
August | 514.00000 | 24.41058 | 47.06987 | -0.2089 | 7.13807 |
September | 485.00000 | 24.53912 | 45.70349 | -0.1555 | 7.37932 |
October | 502.00000 | 24.34917 | 26.51949 | 0.46009 | 11.48148 |
November | 489.00000 | 24.05890 | 27.12083 | 0.36933 | 9.94458 |
December | 497.00000 | 23.74347 | 15.87905 | 0.19725 | 9.19534 |
Annual Sum or Average | 5943.00000 | 24.16356 | 29.34909 | 0.05910 | 8.93399 |
Minimum of Months | 454.00000 | 23.46474 | 15.87905 | -0.4875 | 7.13807 |
Maximum of Months | 514.00000 | 24.54223 | 47.06987 | 0.46009 | 11.48148 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.33962 | 23.50275 | 0.08548 | 7.14737 |
February | 454.00000 | 23.05816 | 37.16297 | 0.08469 | 6.52962 |
March | 514.00000 | 23.61789 | 27.84567 | 0.19142 | 7.32520 |
April | 485.00000 | 24.41931 | 18.52561 | 0.42607 | 9.95859 |
May | 508.00000 | 24.50636 | 17.53934 | -0.3423 | 9.51776 |
June | 496.00000 | 24.53756 | 24.82900 | -0.2006 | 7.96281 |
July | 497.00000 | 24.65475 | 44.01976 | -0.0912 | 7.38748 |
August | 514.00000 | 24.48674 | 46.82308 | -0.1256 | 7.16664 |
September | 485.00000 | 24.54300 | 45.82566 | -0.1615 | 7.42937 |
October | 502.00000 | 24.13483 | 27.33362 | 0.35786 | 9.39269 |
November | 489.00000 | 23.61820 | 28.40387 | 0.19747 | 7.82233 |
December | 497.00000 | 22.86665 | 17.55390 | -0.0908 | 7.44511 |
Annual Sum or Average | 5943.00000 | 23.98795 | 29.90051 | 0.02623 | 7.93051 |
Minimum of Months | 454.00000 | 22.86665 | 17.53934 | -0.3423 | 6.52962 |
Maximum of Months | 514.00000 | 24.65475 | 46.82308 | 0.42607 | 9.95859 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.83636 | 25.80128 | -0.3323 | 9.70846 |
February | 454.00000 | 21.63484 | 40.42438 | -0.2990 | 8.58332 |
March | 514.00000 | 22.58859 | 29.99484 | -0.1067 | 7.64098 |
April | 485.00000 | 23.98284 | 19.55397 | 0.23223 | 7.15106 |
May | 508.00000 | 24.32882 | 18.19381 | -0.5055 | 11.45844 |
June | 496.00000 | 24.45697 | 25.43814 | -0.3160 | 8.50019 |
July | 497.00000 | 24.56594 | 44.54826 | -0.1756 | 7.24613 |
August | 514.00000 | 24.37789 | 47.63930 | -0.2411 | 7.33663 |
September | 485.00000 | 24.42963 | 46.79915 | -0.2655 | 7.94150 |
October | 502.00000 | 23.41428 | 28.86015 | 0.12520 | 7.92930 |
November | 489.00000 | 22.27195 | 30.96518 | -0.1823 | 8.77143 |
December | 497.00000 | 21.15343 | 19.22078 | -0.5598 | 13.52557 |
Annual Sum or Average | 5943.00000 | 23.26469 | 31.39372 | -0.2192 | 8.82031 |
Minimum of Months | 454.00000 | 21.15343 | 18.19381 | -0.5598 | 7.15106 |
Maximum of Months | 514.00000 | 24.56594 | 47.63930 | 0.23223 | 13.52557 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90205 | 23.65231 | -0.0570 | 7.63366 |
February | 454.00000 | 22.62092 | 37.77886 | -0.0468 | 7.43250 |
March | 514.00000 | 23.38197 | 27.91331 | 0.11607 | 7.33812 |
April | 485.00000 | 24.37069 | 18.51394 | 0.41718 | 9.99296 |
May | 508.00000 | 24.50870 | 17.69960 | -0.3092 | 9.10714 |
June | 496.00000 | 24.52147 | 25.15443 | -0.1635 | 7.75029 |
July | 497.00000 | 24.64733 | 44.14382 | -0.0329 | 7.28256 |
August | 514.00000 | 24.47518 | 47.05402 | -0.0901 | 7.06651 |
September | 485.00000 | 24.52305 | 46.13948 | -0.1410 | 7.44526 |
October | 502.00000 | 23.99164 | 27.26677 | 0.31892 | 9.57579 |
November | 489.00000 | 23.08750 | 29.11045 | 0.03816 | 7.35275 |
December | 497.00000 | 22.14808 | 18.17159 | -0.3039 | 9.58881 |
Annual Sum or Average | 5943.00000 | 23.77297 | 30.16605 | -0.0218 | 8.13161 |
Minimum of Months | 454.00000 | 22.14808 | 17.69960 | -0.3092 | 7.06651 |
Maximum of Months | 514.00000 | 24.64733 | 47.05402 | 0.41718 | 9.99296 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.61530 | 21.61310 | 0.21218 | 9.72296 |
February | 454.00000 | 22.92963 | 36.36755 | 0.07072 | 8.32800 |
March | 514.00000 | 23.36070 | 27.85278 | 0.12874 | 7.94981 |
April | 485.00000 | 24.19802 | 18.96243 | 0.34091 | 8.86152 |
May | 508.00000 | 24.33634 | 18.13332 | -0.4814 | 11.37151 |
June | 496.00000 | 24.42827 | 25.50851 | -0.3394 | 8.85901 |
July | 497.00000 | 24.55864 | 44.55454 | -0.1726 | 7.44686 |
August | 514.00000 | 24.41650 | 47.40885 | -0.1834 | 7.18510 |
September | 485.00000 | 24.53430 | 46.21124 | -0.1395 | 7.54738 |
October | 502.00000 | 24.13741 | 26.83614 | 0.40358 | 11.24441 |
November | 489.00000 | 23.65872 | 27.51434 | 0.25183 | 9.38340 |
December | 497.00000 | 23.21802 | 15.94908 | 0.03184 | 9.68464 |
Annual Sum or Average | 5943.00000 | 23.95557 | 29.70130 | 0.00861 | 8.97153 |
Minimum of Months | 454.00000 | 22.92963 | 15.94908 | -0.4814 | 7.18510 |
Maximum of Months | 514.00000 | 24.55864 | 47.40885 | 0.40358 | 11.37151 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.82044 | 23.74231 | -0.0560 | 8.39127 |
February | 454.00000 | 22.46053 | 38.09256 | -0.0748 | 7.42542 |
March | 514.00000 | 23.24495 | 28.40872 | 0.09186 | 7.75803 |
April | 485.00000 | 24.34050 | 18.81176 | 0.41256 | 10.11679 |
May | 508.00000 | 24.48845 | 17.85198 | -0.3335 | 9.76289 |
June | 496.00000 | 24.54311 | 25.21030 | -0.1697 | 8.00518 |
July | 497.00000 | 24.65928 | 44.23300 | -0.0631 | 7.58901 |
August | 514.00000 | 24.48694 | 47.17980 | -0.1035 | 7.31058 |
September | 485.00000 | 24.54345 | 46.30492 | -0.1450 | 7.56017 |
October | 502.00000 | 23.90359 | 27.65074 | 0.29879 | 9.53374 |
November | 489.00000 | 23.16590 | 28.86256 | 0.07388 | 8.29767 |
December | 497.00000 | 22.23051 | 17.64679 | -0.2700 | 9.87103 |
Annual Sum or Average | 5943.00000 | 23.74917 | 30.28245 | -0.0288 | 8.47273 |
Minimum of Months | 454.00000 | 22.23051 | 17.64679 | -0.3335 | 7.31058 |
Maximum of Months | 514.00000 | 24.65928 | 47.17980 | 0.41256 | 10.11679 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.614452E+11 | 131529.06 | 27-JAN-14:20 | 311.55 | 0.424649E+12 | 0.00 | 0.486094E+12 | 2.56 | 7.95 | 26-JAN-16:50 | 0.00 | 0.00 |
February | 0.239231E+11 | 86560.56 | 22-FEB-14:05 | 203.52 | 0.138939E+12 | 0.00 | 0.162862E+12 | 1.58 | 7.69 | 22-FEB-14:05 | 0.00 | 0.00 |
March | 0.590343E+11 | 140813.84 | 17-MAR-13:05 | 355.08 | 0.391268E+12 | 0.00 | 0.450302E+12 | 2.75 | 7.95 | 15-MAR-14:20 | 0.00 | 0.00 |
April | 0.118825E+12 | 138348.27 | 03-APR-12:20 | 592.24 | 0.854582E+12 | 0.00 | 0.973407E+12 | 5.16 | 7.95 | 12-APR-08:30 | 0.00 | 0.00 |
May | 0.139251E+12 | 138173.56 | 30-MAY-16:10 | 540.72 | 0.101504E+13 | 0.00 | 0.115429E+13 | 4.96 | 7.95 | 06-MAY-14:40 | 0.00 | 0.00 |
June | 0.165252E+12 | 151169.44 | 17-JUN-13:20 | 667.67 | 0.120152E+13 | 0.00 | 0.136677E+13 | 6.26 | 7.95 | 27-JUN-05:04 | 0.00 | 0.00 |
July | 0.175995E+12 | 154180.07 | 13-JUL-17:41 | 692.11 | 0.126030E+13 | 0.00 | 0.143629E+13 | 6.15 | 7.95 | 01-JUL-09:40 | 0.00 | 0.00 |
August | 0.175184E+12 | 150396.11 | 12-AUG-12:50 | 688.61 | 0.126574E+13 | 0.00 | 0.144093E+13 | 6.15 | 7.95 | 23-AUG-07:40 | 0.00 | 0.00 |
September | 0.150801E+12 | 152175.34 | 01-SEP-16:40 | 550.38 | 0.109608E+13 | 0.00 | 0.124688E+13 | 5.21 | 7.96 | 20-SEP-04:13 | 0.00 | 0.00 |
October | 0.100454E+12 | 144292.05 | 03-OCT-17:00 | 456.83 | 0.709274E+12 | 0.00 | 0.809727E+12 | 3.92 | 7.95 | 11-OCT-14:50 | 0.00 | 0.00 |
November | 0.621526E+11 | 146952.82 | 01-NOV-11:00 | 336.50 | 0.426991E+12 | 0.00 | 0.489143E+12 | 2.77 | 7.95 | 06-NOV-16:40 | 0.00 | 0.00 |
December | 0.390646E+11 | 128516.89 | 22-DEC-16:30 | 277.16 | 0.244091E+12 | 0.00 | 0.283156E+12 | 2.04 | 7.95 | 22-DEC-16:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.127138E+13 | 5672.34 | 0.902848E+13 | 0.00 | 0.102999E+14 | 4.14 | 0.00 | 0.00 | ||||
Minimum of Months | 0.239231E+11 | 86560.56 | 203.52 | 0.138939E+12 | 0.00 | 0.162862E+12 | 1.58 | 7.69 | 0.00 | 0.00 | ||
Maximum of Months | 0.175995E+12 | 154180.07 | 692.11 | 0.126574E+13 | 0.00 | 0.144093E+13 | 6.26 | 7.96 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.596894E+09 | 86648.01 | 31-JAN-15:50 | 2.42 | 0.430989E+10 | 0.00 | 0.490678E+10 | 0.02 | 7.66 | 31-JAN-14:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.100336E+10 | 94631.90 | 16-MAR-13:05 | 3.83 | 0.744550E+10 | 0.00 | 0.844886E+10 | 0.04 | 7.77 | 16-MAR-13:05 | 0.00 | 0.00 |
April | 0.283602E+11 | 103510.12 | 11-APR-12:05 | 97.00 | 0.214539E+12 | 0.00 | 0.242899E+12 | 1.01 | 7.89 | 11-APR-12:05 | 0.00 | 0.00 |
May | 0.466200E+11 | 105906.18 | 26-MAY-12:05 | 159.67 | 0.352444E+12 | 0.00 | 0.399064E+12 | 1.61 | 7.88 | 24-MAY-12:05 | 0.00 | 0.00 |
June | 0.847251E+11 | 118427.97 | 19-JUN-14:50 | 269.92 | 0.643376E+12 | 0.00 | 0.728102E+12 | 2.83 | 7.87 | 08-JUN-14:05 | 0.00 | 0.00 |
July | 0.765414E+11 | 154180.07 | 13-JUL-17:41 | 233.90 | 0.567403E+12 | 0.00 | 0.643945E+12 | 2.32 | 7.87 | 27-JUL-05:02 | 0.00 | 0.00 |
August | 0.818779E+11 | 134329.73 | 01-AUG-05:04 | 248.08 | 0.607695E+12 | 0.00 | 0.689573E+12 | 2.47 | 7.87 | 24-AUG-15:10 | 0.00 | 0.00 |
September | 0.585037E+11 | 130397.15 | 05-SEP-07:40 | 181.22 | 0.435091E+12 | 0.00 | 0.493595E+12 | 1.86 | 7.84 | 28-SEP-15:20 | 0.00 | 0.00 |
October | 0.236594E+11 | 108259.26 | 03-OCT-11:00 | 78.03 | 0.177348E+12 | 0.00 | 0.201007E+12 | 0.78 | 7.82 | 17-OCT-12:05 | 0.00 | 0.00 |
November | 0.238292E+10 | 100944.51 | 20-NOV-15:05 | 9.42 | 0.175328E+11 | 0.00 | 0.199157E+11 | 0.09 | 7.87 | 20-NOV-15:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.404271E+12 | 1283.48 | 0.302718E+13 | 0.00 | 0.343146E+13 | 1.09 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.847251E+11 | 154180.07 | 269.92 | 0.643376E+12 | 0.00 | 0.728102E+12 | 2.83 | 7.89 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.437176E+11 | 744.00 | 43776.24 | 02-JAN-12:10 | 227471.78 | 31-JAN-17:30 | 20.45 | 19.62 | 14.28 |
February | 0.193095E+11 | 672.00 | 43776.24 | 06-FEB-14:00 | 181111.93 | 18-FEB-14:05 | 19.63 | 18.48 | 14.28 |
March | 0.594500E+11 | 744.00 | 43776.24 | 01-MAR-10:00 | 514751.66 | 16-MAR-17:30 | 24.13 | 20.60 | 14.28 |
April | 0.105950E+12 | 720.00 | 43776.24 | 01-APR-07:05 | 619320.84 | 25-APR-18:15 | 37.01 | 27.84 | 14.28 |
May | 0.110557E+12 | 744.00 | 43776.24 | 01-MAY-00:10 | 350585.27 | 31-MAY-23:15 | 30.71 | 27.77 | 14.28 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:05 | 509610.61 | 30-JUN-23:43 | 41.09 | 34.29 | 14.28 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 702954.84 | 13-JUL-17:53 | 45.71 | 35.22 | 14.28 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 731915.41 | 05-AUG-16:43 | 48.39 | 35.66 | 14.28 |
September | 0.112985E+12 | 720.00 | 43776.24 | 01-SEP-00:10 | 333910.98 | 04-SEP-10:20 | 32.80 | 29.32 | 14.28 |
October | 0.845571E+11 | 744.00 | 43776.24 | 01-OCT-00:05 | 493003.23 | 03-OCT-08:30 | 27.66 | 23.98 | 14.28 |
November | 0.596658E+11 | 720.00 | 43776.24 | 01-NOV-00:10 | 531316.70 | 09-NOV-17:00 | 24.14 | 20.46 | 14.28 |
December | 0.477370E+11 | 744.00 | 43776.24 | 01-DEC-09:50 | 588783.30 | 25-DEC-16:11 | 23.71 | 19.64 | 14.28 |
Annual Sum or Average | 0.991897E+12 | 8760.00 | 31.35 | 26.11 | 14.28 | ||||
Minimum of Months | 0.193095E+11 | 672.00 | 43776.24 | 181111.93 | 19.63 | 18.48 | 14.28 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 731915.41 | 48.39 | 35.66 | 14.28 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.508345E+09 | 241.94 | 2124.20 | 31-JAN-13:50 | 1176113.05 | 24-JAN-16:20 | 21.96 | 21.15 | 21.00 |
February | 0.134130E+09 | 127.25 | 1155.16 | 22-FEB-14:05 | 683801.20 | 28-FEB-16:30 | 21.38 | 21.07 | 13.80 |
March | 0.826166E+09 | 251.93 | 15640.96 | 16-MAR-15:10 | 1229285.99 | 17-MAR-15:30 | 21.89 | 21.13 | 22.80 |
April | 0.207549E+10 | 421.49 | 15640.96 | 10-APR-14:20 | 1211050.64 | 21-APR-16:00 | 22.88 | 21.07 | 37.68 |
May | 0.244115E+10 | 496.14 | 15640.96 | 04-MAY-14:50 | 1210720.01 | 08-MAY-08:40 | 23.51 | 21.38 | 39.30 |
June | 0.130266E+11 | 597.78 | 15640.96 | 01-JUN-07:40 | 1213164.98 | 13-JUN-09:40 | 23.94 | 21.41 | 49.54 |
July | 0.260752E+11 | 661.35 | 15640.96 | 01-JUL-14:00 | 1199005.15 | 03-JUL-07:50 | 24.93 | 22.55 | 49.59 |
August | 0.262125E+11 | 651.26 | 15640.96 | 01-AUG-00:33 | 1165976.67 | 26-AUG-09:53 | 24.86 | 22.47 | 49.37 |
September | 0.216264E+11 | 537.92 | 15640.96 | 01-SEP-03:03 | 1155863.28 | 18-SEP-07:40 | 24.60 | 22.46 | 41.48 |
October | 0.572239E+10 | 388.33 | 15640.96 | 01-OCT-09:43 | 1235242.52 | 10-OCT-09:20 | 22.74 | 21.35 | 31.65 |
November | 0.167673E+10 | 245.68 | 15640.96 | 01-NOV-10:05 | 1218976.21 | 01-NOV-10:50 | 21.95 | 21.11 | 22.75 |
December | 0.204019E+09 | 176.01 | 1893.03 | 22-DEC-15:40 | 1161117.63 | 22-DEC-16:30 | 21.53 | 21.05 | 16.79 |
Annual Sum or Average | 0.100529E+12 | 4797.08 | 23.02 | 21.52 | 33.08 | ||||
Minimum of Months | 0.134130E+09 | 127.25 | 1155.16 | 683801.20 | 21.38 | 21.05 | 13.80 | ||
Maximum of Months | 0.262125E+11 | 661.35 | 15640.96 | 1235242.52 | 24.93 | 22.55 | 49.59 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 4360707.64 | 1.42 | 1165.44 | 31-JAN-14:50 | 1068705.15 | 27-JAN-15:50 | 21.96 | 21.95 | 0.11 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.38 | 21.38 | 0.00 |
March | 17304328.06 | 2.58 | 2555.71 | 20-MAR-16:00 | 1082544.63 | 20-MAR-15:10 | 21.89 | 21.88 | 0.19 |
April | 0.772574E+09 | 81.00 | 15640.96 | 10-APR-14:20 | 1152978.80 | 24-APR-14:40 | 22.88 | 22.39 | 6.22 |
May | 0.950164E+09 | 137.83 | 15640.96 | 04-MAY-14:50 | 1158055.74 | 05-MAY-15:00 | 23.51 | 22.71 | 10.25 |
June | 0.889466E+10 | 240.37 | 15640.96 | 01-JUN-08:40 | 1144738.07 | 05-JUN-11:00 | 23.94 | 22.62 | 18.45 |
July | 0.133790E+11 | 252.61 | 15640.96 | 01-JUL-14:00 | 1155067.34 | 03-JUL-10:30 | 24.93 | 23.68 | 17.88 |
August | 0.146209E+11 | 267.90 | 15640.96 | 01-AUG-05:02 | 1071441.77 | 24-AUG-08:35 | 24.86 | 23.55 | 19.03 |
September | 0.102316E+11 | 189.50 | 15640.96 | 01-SEP-05:07 | 1103356.66 | 05-SEP-07:50 | 24.60 | 23.62 | 13.96 |
October | 0.272589E+10 | 68.44 | 15640.96 | 02-OCT-07:20 | 1104824.63 | 31-OCT-14:40 | 22.74 | 22.39 | 5.07 |
November | 0.113488E+09 | 4.42 | 15640.96 | 01-NOV-12:05 | 1078199.49 | 09-NOV-15:05 | 21.95 | 21.93 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.53 | 21.53 | 0.00 |
Annual Sum or Average | 0.517100E+11 | 1246.07 | 23.02 | 22.48 | 7.66 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 | 21.38 | 0.00 | ||
Maximum of Months | 0.146209E+11 | 267.90 | 15640.96 | 1158055.74 | 24.93 | 23.68 | 19.03 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.844034E+10 | 0.00 | 101.64 | 902703.01 | 02-JAN-05:11 | 0.00 | 32.61 | 36.23 | 0.03 | 0.00 | 0.00 | 0.56 | 02-JAN-05:11 |
February | 0.911581E+10 | 0.00 | 119.49 | 796669.89 | 13-FEB-06:03 | 0.00 | 32.90 | 37.60 | 0.04 | 0.00 | 0.00 | 0.50 | 13-FEB-06:03 |
March | 0.859815E+10 | 0.00 | 65.53 | 907752.31 | 27-MAR-05:03 | 0.00 | 34.98 | 37.10 | 0.04 | 0.00 | 0.00 | 0.57 | 27-MAR-05:03 |
April | 17465145.16 | 0.00 | 3.47 | 12554.17 | 21-APR-06:10 | 0.00 | 37.55 | 37.65 | 0.00 | 0.00 | 0.00 | 0.01 | 21-APR-06:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 37.06 | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 37.06 | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 37.06 | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 37.06 | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1786.70 | 0.00 | 0.17 | 2.98 | 02-SEP-11:50 | 0.00 | 37.06 | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 | 02-SEP-11:50 |
October | 0.150764E+10 | 0.00 | 25.80 | 149984.57 | 25-OCT-06:10 | 0.00 | 34.93 | 35.82 | 0.01 | 0.00 | 0.00 | 0.09 | 25-OCT-06:10 |
November | 0.464049E+10 | 0.00 | 76.37 | 830716.92 | 24-NOV-06:02 | 0.00 | 32.66 | 35.50 | 0.02 | 0.00 | 0.00 | 0.52 | 24-NOV-06:02 |
December | 0.340878E+11 | 0.00 | 193.72 | 1069997.90 | 07-DEC-06:01 | 0.00 | 34.25 | 40.49 | 0.15 | 0.00 | 0.01 | 0.67 | 07-DEC-06:01 |
Annual Sum or Average | 0.664077E+11 | 0.00 | 586.18 | 0.00 | 35.44 | 37.14 | 0.02 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 | 35.50 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.340878E+11 | 0.00 | 193.72 | 1069997.90 | 0.00 | 37.55 | 40.49 | 0.15 | 0.00 | 0.01 | 0.67 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 20.45 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.63 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 24.13 | 24.13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 37.01 | 37.01 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 30.71 | 30.71 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 41.09 | 41.09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 45.71 | 45.71 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 48.39 | 48.39 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 32.80 | 32.80 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 27.66 | 27.66 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 24.14 | 24.14 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 23.71 | 23.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 | 31.35 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.39 | 48.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.383798E+11 | 0.00 | 291.14 | 0.383689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92151.47 | 31-JAN-16:30 | 92151.47 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.103346E+11 | 0.00 | 176.83 | 0.103346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61362.74 | 21-FEB-15:00 | 61362.74 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.420305E+11 | 0.00 | 338.67 | 0.420305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102925.77 | 20-MAR-14:50 | 102925.77 | 20-MAR-14:50 | 0.00 | 0.00 | 0.00 |
April | 0.109042E+12 | 0.00 | 566.62 | 0.109042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 133227.83 | 24-APR-15:00 | 133227.83 | 24-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.118971E+12 | 0.00 | 516.10 | 0.118971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 123242.72 | 15-MAY-15:20 | 123242.72 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.161754E+12 | 0.00 | 625.99 | 0.161754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 155249.33 | 29-JUN-05:02 | 155249.33 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.169378E+12 | 0.00 | 645.06 | 0.159160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267810.29 | 14-JUL-05:03 | 154954.20 | 10-JUL-04:02 | 0.00 | 0.00 | 0.00 |
August | 0.188241E+12 | 0.00 | 658.50 | 0.177705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 254013.66 | 01-AUG-05:02 | 168052.86 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.133737E+12 | 0.00 | 519.72 | 0.124889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235762.83 | 08-SEP-05:02 | 156019.10 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.817812E+11 | 0.00 | 429.87 | 0.804025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161583.65 | 03-OCT-05:02 | 153072.21 | 02-OCT-04:23 | 0.00 | 0.00 | 0.00 |
November | 0.444422E+11 | 0.00 | 313.46 | 0.419024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121825.52 | 13-NOV-06:03 | 103894.83 | 20-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.281142E+11 | 0.00 | 256.57 | 0.281142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90929.18 | 22-DEC-16:20 | 90929.18 | 22-DEC-16:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112621E+13 | 0.00 | 5338.53 | 0.109267E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103346E+11 | 0.00 | 176.83 | 0.103346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61362.74 | 61362.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.188241E+12 | 0.00 | 658.50 | 0.177705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267810.29 | 168052.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.323851E+12 | 0.00 | 292.02 | 0.323734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 808850.05 | 31-JAN-16:30 | 808850.05 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.117458E+12 | 0.00 | 189.36 | 0.117458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 516284.50 | 28-FEB-16:30 | 516284.50 | 28-FEB-16:30 | 0.00 | 0.00 | 0.00 |
March | 0.302944E+12 | 0.00 | 321.86 | 0.302944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 863610.46 | 16-MAR-15:50 | 863610.46 | 16-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.817647E+12 | 0.00 | 438.82 | 0.817647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1153304.47 | 14-APR-15:20 | 1153304.47 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.107128E+13 | 0.00 | 488.77 | 0.107128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1163220.21 | 18-MAY-15:20 | 1163220.21 | 18-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.143809E+13 | 0.00 | 556.15 | 0.143809E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1423114.24 | 29-JUN-05:02 | 1423114.24 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.138268E+13 | 0.00 | 551.29 | 0.131062E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2508141.43 | 18-JUL-05:03 | 1445767.61 | 07-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.139432E+13 | 0.00 | 544.13 | 0.132891E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2420429.54 | 01-AUG-05:02 | 1472607.50 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.115739E+13 | 0.00 | 469.90 | 0.108420E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2255482.16 | 08-SEP-05:02 | 1444935.17 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.671412E+12 | 0.00 | 397.41 | 0.659810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1645109.59 | 03-OCT-04:12 | 1256113.64 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.327562E+12 | 0.00 | 299.31 | 0.315099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 965215.25 | 13-NOV-06:03 | 887324.99 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.184411E+12 | 0.00 | 225.58 | 0.184411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 694723.94 | 22-DEC-15:05 | 694723.94 | 22-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.918905E+13 | 0.00 | 4774.60 | 0.895420E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.117458E+12 | 0.00 | 189.36 | 0.117458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 516284.50 | 516284.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143809E+13 | 0.00 | 556.15 | 0.143809E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2508141.43 | 1472607.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.265404E+11 | 0.00 | 281.56 | 0.265327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83629.74 | 31-JAN-16:30 | 83629.74 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.546916E+10 | 0.00 | 163.33 | 0.546916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42973.27 | 22-FEB-16:00 | 42973.27 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.279167E+11 | 0.00 | 304.22 | 0.279167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98148.47 | 16-MAR-15:30 | 98148.47 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.895349E+11 | 0.00 | 436.51 | 0.895349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137810.31 | 14-APR-15:20 | 137810.31 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.118803E+12 | 0.00 | 487.63 | 0.118803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 139052.10 | 18-MAY-15:20 | 139052.10 | 18-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.164382E+12 | 0.00 | 567.78 | 0.164382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 165335.65 | 28-JUN-14:50 | 165335.65 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.157601E+12 | 0.00 | 565.31 | 0.150133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 273231.66 | 18-JUL-05:03 | 163192.34 | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.156140E+12 | 0.00 | 553.20 | 0.149411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272408.07 | 01-AUG-05:02 | 175234.46 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.125669E+12 | 0.00 | 476.04 | 0.118511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 252539.71 | 08-SEP-05:02 | 160612.69 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.672157E+11 | 0.00 | 389.40 | 0.661432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173967.54 | 03-OCT-04:12 | 144736.62 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.268978E+11 | 0.00 | 284.87 | 0.260890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100636.89 | 01-NOV-15:30 | 100636.89 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.117466E+11 | 0.00 | 193.13 | 0.117466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69410.78 | 22-DEC-16:20 | 69410.78 | 22-DEC-16:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.977917E+12 | 0.00 | 4702.98 | 0.954672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.546916E+10 | 0.00 | 163.33 | 0.546916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42973.27 | 42973.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.164382E+12 | 0.00 | 567.78 | 0.164382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 273231.66 | 175234.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.229053E+11 | 0.00 | 220.38 | 0.229020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83482.57 | 16-JAN-14:50 | 83482.57 | 16-JAN-14:50 | 0.00 | 0.00 | 0.00 |
February | 0.379554E+10 | 0.00 | 89.13 | 0.377346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48374.82 | 17-FEB-06:02 | 45459.50 | 10-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.220022E+11 | 0.00 | 238.44 | 0.219930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59731.98 | 20-MAR-13:10 | 59731.98 | 20-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.549588E+11 | 0.00 | 340.65 | 0.549588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89690.36 | 25-APR-03:50 | 89690.36 | 25-APR-03:50 | 0.00 | 0.00 | 0.00 |
May | 0.676502E+11 | 0.00 | 397.72 | 0.676502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110407.99 | 29-MAY-14:30 | 110407.99 | 29-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.828312E+11 | 0.00 | 415.97 | 0.828312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101976.94 | 27-JUN-03:02 | 101976.94 | 27-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.895745E+11 | 0.00 | 437.61 | 0.864705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147000.77 | 14-JUL-05:03 | 111281.58 | 02-JUL-18:51 | 0.00 | 0.00 | 0.00 |
August | 0.100648E+12 | 0.00 | 478.05 | 0.967842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147367.41 | 01-AUG-03:02 | 111001.29 | 27-AUG-20:57 | 0.00 | 0.00 | 0.00 |
September | 0.852160E+11 | 0.00 | 431.89 | 0.809984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153781.39 | 04-SEP-14:51 | 105058.08 | 17-SEP-16:32 | 0.00 | 0.00 | 0.00 |
October | 0.532275E+11 | 0.00 | 349.09 | 0.527084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111756.19 | 03-OCT-04:22 | 110408.78 | 15-OCT-17:19 | 0.00 | 0.00 | 0.00 |
November | 0.281222E+11 | 0.00 | 235.91 | 0.259571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99899.05 | 13-NOV-05:53 | 81311.08 | 19-NOV-16:10 | 0.00 | 0.00 | 0.00 |
December | 0.122860E+11 | 0.00 | 157.71 | 0.122840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83339.95 | 24-DEC-15:51 | 83339.95 | 24-DEC-15:51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623217E+12 | 0.00 | 3792.56 | 0.609311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.379554E+10 | 0.00 | 89.13 | 0.377346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48374.82 | 45459.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100648E+12 | 0.00 | 478.05 | 0.967842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153781.39 | 111281.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.288478E+11 | 0.111221E+11 | 716.19 | 0.288193E+11 | 28516389.23 | 0.00 | 0.45 | 27-JAN-16:00 | 0.00 | 20-JAN-21:20 | 134486.96 | 27-JAN-16:00 | 134486.96 | 27-JAN-16:00 | 128.54 | 09-JAN-12:00 | 48047.93 | 27-JAN-16:00 | 0.00 |
February | 0.101054E+11 | 0.509544E+10 | 479.82 | 0.952526E+10 | 0.580091E+09 | 0.00 | 0.29 | 18-FEB-14:00 | 0.01 | 12-FEB-11:50 | 100783.47 | 18-FEB-14:00 | 87695.31 | 18-FEB-15:00 | 13976.81 | 18-FEB-14:00 | 27596.80 | 18-FEB-14:00 | 0.00 |
March | 0.193188E+12 | 0.579176E+11 | 722.94 | 0.189284E+12 | 0.390356E+10 | 0.00 | 0.91 | 15-MAR-12:40 | 0.00 | 04-MAR-22:50 | 316173.54 | 17-MAR-15:20 | 316173.54 | 17-MAR-15:20 | 25910.68 | 17-MAR-10:00 | 101409.64 | 16-MAR-12:40 | 0.00 |
April | 0.671426E+12 | 0.218537E+12 | 720.00 | 0.669674E+12 | 0.175160E+10 | 0.00 | 1.00 | 01-APR-09:10 | 0.03 | 30-APR-24:00 | 376042.78 | 15-APR-09:00 | 376042.78 | 15-APR-09:00 | 34280.34 | 16-APR-06:23 | 132317.20 | 14-APR-16:10 | 0.00 |
May | 0.216396E+12 | 0.756200E+11 | 743.50 | 0.216395E+12 | 467487.04 | 0.00 | 0.67 | 31-MAY-23:10 | 0.01 | 26-MAY-03:10 | 213134.16 | 31-MAY-23:10 | 213134.16 | 31-MAY-23:10 | 99.42 | 11-MAY-02:30 | 72031.59 | 31-MAY-23:10 | 0.00 |
June | 0.517468E+12 | 0.185145E+12 | 720.00 | 0.517451E+12 | 16764587.83 | 0.00 | 0.83 | 30-JUN-23:10 | 0.03 | 21-JUN-06:00 | 305707.12 | 30-JUN-24:00 | 305707.12 | 30-JUN-24:00 | 2806.16 | 04-JUN-05:00 | 102794.66 | 16-JUN-16:00 | 0.00 |
July | 0.869345E+12 | 0.279849E+12 | 744.00 | 0.786233E+12 | 0.831118E+11 | 0.00 | 1.00 | 08-JUL-20:25 | 0.29 | 01-JUL-06:00 | 467200.21 | 14-JUL-01:00 | 391310.93 | 31-JUL-24:00 | 312605.52 | 14-JUL-01:00 | 132574.49 | 05-JUL-16:00 | 0.00 |
August | 0.106296E+13 | 0.324937E+12 | 744.00 | 0.932046E+12 | 0.130918E+12 | 0.00 | 1.00 | 01-AUG-00:05 | 0.37 | 31-AUG-23:53 | 451312.81 | 09-AUG-18:30 | 412905.73 | 27-AUG-13:34 | 260689.18 | 28-AUG-17:00 | 147179.38 | 25-AUG-16:10 | 0.00 |
September | 0.265133E+12 | 0.859399E+11 | 677.91 | 0.238700E+12 | 0.264328E+11 | 0.00 | 0.55 | 04-SEP-10:20 | 0.01 | 27-SEP-04:53 | 233456.88 | 04-SEP-10:18 | 174560.86 | 30-SEP-23:10 | 111465.68 | 04-SEP-10:00 | 60755.46 | 04-SEP-10:20 | 0.00 |
October | 0.250565E+12 | 0.796146E+11 | 715.90 | 0.239527E+12 | 0.110373E+11 | 0.00 | 0.79 | 03-OCT-08:30 | 0.00 | 10-OCT-02:45 | 335824.24 | 03-OCT-08:30 | 228094.41 | 16-OCT-10:05 | 128098.12 | 03-OCT-02:55 | 89623.02 | 03-OCT-08:30 | 0.00 |
November | 0.202691E+12 | 0.588637E+11 | 685.92 | 0.175374E+12 | 0.273174E+11 | 0.00 | 0.96 | 09-NOV-13:00 | 0.01 | 02-NOV-02:70 | 319326.09 | 20-NOV-15:20 | 319326.09 | 20-NOV-15:20 | 172081.77 | 12-NOV-14:55 | 107874.05 | 09-NOV-17:00 | 0.00 |
December | 0.202559E+12 | 0.611295E+11 | 737.58 | 0.202170E+12 | 0.388831E+09 | 0.00 | 1.00 | 02-DEC-13:00 | 0.01 | 13-DEC-05:10 | 347164.48 | 25-DEC-13:52 | 347164.48 | 25-DEC-13:52 | 18373.14 | 13-DEC-11:20 | 110832.22 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.449069E+13 | 0.144377E+13 | 8407.77 | 0.420520E+13 | 0.285488E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.101054E+11 | 0.509544E+10 | 479.82 | 0.952526E+10 | 467487.04 | 0.00 | 0.29 | 0.00 | 100783.47 | 87695.31 | 99.42 | 27596.80 | 0.00 | ||||||
Maximum of Months | 0.106296E+13 | 0.324937E+12 | 744.00 | 0.932046E+12 | 0.130918E+12 | 0.00 | 1.00 | 0.37 | 467200.21 | 412905.73 | 312605.52 | 147179.38 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.534652E+10 | 0.128769E+10 | 744.00 | 0.534336E+10 | 3161960.70 | 0.00 | 0.41 | 29-JAN-17:12 | 0.19 | 12-JAN-07:35 | 2818.47 | 29-JAN-17:15 | 2818.47 | 29-JAN-17:15 | 95.86 | 09-JAN-11:20 | 867.52 | 31-JAN-17:00 | 0.00 |
February | 0.928562E+10 | 0.195541E+10 | 672.00 | 0.924195E+10 | 43669621.88 | 0.00 | 0.55 | 25-FEB-18:10 | 0.42 | 08-FEB-07:25 | 4543.13 | 20-FEB-17:03 | 4523.99 | 20-FEB-17:03 | 171.30 | 16-FEB-10:20 | 975.61 | 22-FEB-16:50 | 0.00 |
March | 0.156304E+11 | 0.343667E+10 | 744.00 | 0.156188E+11 | 11611863.62 | 0.00 | 0.95 | 31-MAR-24:00 | 0.63 | 07-MAR-08:00 | 7697.37 | 31-MAR-24:00 | 7697.37 | 31-MAR-24:00 | 211.86 | 06-MAR-11:10 | 1942.71 | 16-MAR-16:00 | 0.00 |
April | 0.198755E+11 | 0.542376E+10 | 720.00 | 0.198755E+11 | -0.0 | 0.00 | 1.00 | 01-APR-09:00 | 0.37 | 30-APR-23:05 | 8240.85 | 26-APR-19:00 | 8240.85 | 26-APR-19:00 | 0.00 | 10-APR-19:00 | 2709.98 | 14-APR-16:10 | 0.00 |
May | 0.619541E+10 | 0.199066E+10 | 744.00 | 0.619541E+10 | -0.0 | 0.00 | 0.59 | 31-MAY-23:15 | 0.26 | 13-MAY-06:30 | 4046.23 | 31-MAY-24:00 | 4046.23 | 31-MAY-24:00 | 0.00 | 02-MAY-13:20 | 1300.77 | 31-MAY-23:15 | 0.00 |
June | 0.111005E+11 | 0.388761E+10 | 720.00 | 0.110989E+11 | 1647242.83 | 0.00 | 0.79 | 30-JUN-23:10 | 0.49 | 21-JUN-06:10 | 5978.41 | 30-JUN-23:55 | 5978.41 | 30-JUN-23:55 | 94.32 | 30-JUN-10:00 | 2162.11 | 16-JUN-16:00 | 0.00 |
July | 0.166112E+11 | 0.539885E+10 | 744.00 | 0.164600E+11 | 0.151157E+09 | 0.00 | 1.00 | 01-JUL-18:22 | 0.69 | 01-JUL-06:10 | 7901.86 | 31-JUL-23:53 | 7888.34 | 31-JUL-23:57 | 413.40 | 13-JUL-18:00 | 2812.12 | 02-JUL-18:00 | 0.00 |
August | 0.212708E+11 | 0.660263E+10 | 744.00 | 0.211198E+11 | 0.150918E+09 | 0.00 | 1.00 | 01-AUG-08:40 | 0.35 | 31-AUG-24:00 | 8700.41 | 28-AUG-16:45 | 8319.37 | 21-AUG-00:12 | 589.74 | 28-AUG-16:15 | 3002.44 | 25-AUG-16:10 | 0.00 |
September | 0.618177E+10 | 0.188258E+10 | 720.00 | 0.604503E+10 | 0.136737E+09 | 0.00 | 0.55 | 30-SEP-23:40 | 0.25 | 22-SEP-06:30 | 4053.04 | 30-SEP-23:40 | 4053.04 | 30-SEP-23:40 | 292.82 | 11-SEP-15:10 | 1166.33 | 30-SEP-23:40 | 0.00 |
October | 0.110138E+11 | 0.285122E+10 | 744.00 | 0.109834E+11 | 30339514.02 | 0.00 | 0.74 | 15-OCT-17:05 | 0.43 | 25-OCT-06:45 | 5868.49 | 31-OCT-24:00 | 5868.49 | 31-OCT-24:00 | 309.32 | 03-OCT-09:40 | 1755.18 | 15-OCT-17:05 | 0.00 |
November | 0.153094E+11 | 0.337229E+10 | 720.00 | 0.152607E+11 | 48733332.22 | 0.00 | 0.89 | 09-NOV-17:00 | 0.64 | 18-NOV-07:15 | 6809.20 | 26-NOV-16:57 | 6809.20 | 26-NOV-16:57 | 403.61 | 13-NOV-16:10 | 2057.19 | 09-NOV-16:50 | 0.00 |
December | 0.205152E+11 | 0.439314E+10 | 744.00 | 0.205147E+11 | 498525.27 | 0.00 | 1.00 | 01-DEC-15:50 | 0.85 | 14-DEC-07:10 | 8294.11 | 24-DEC-18:35 | 8294.11 | 24-DEC-18:35 | 72.15 | 13-DEC-11:20 | 2279.27 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.158336E+12 | 0.424825E+11 | 8760.00 | 0.157758E+12 | 0.578474E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.534652E+10 | 0.128769E+10 | 672.00 | 0.534336E+10 | -0.0 | 0.00 | 0.41 | 0.19 | 2818.47 | 2818.47 | 0.00 | 867.52 | 0.00 | ||||||
Maximum of Months | 0.212708E+11 | 0.660263E+10 | 744.00 | 0.211198E+11 | 0.151157E+09 | 0.00 | 1.00 | 0.85 | 8700.41 | 8319.37 | 589.74 | 3002.44 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.413219E+11 | 0.101805E+11 | 743.94 | 0.412920E+11 | 29951241.06 | 0.00 | 0.39 | 29-JAN-17:12 | 0.00 | 01-JAN-01:43 | 25257.27 | 29-JAN-17:27 | 25257.27 | 29-JAN-17:27 | 881.74 | 09-JAN-11:30 | 8095.86 | 31-JAN-17:00 | 0.00 |
February | 0.792320E+11 | 0.168697E+11 | 672.00 | 0.788028E+11 | 0.429189E+09 | 0.00 | 0.53 | 25-FEB-18:10 | 0.33 | 13-FEB-07:10 | 41058.05 | 22-FEB-17:00 | 40847.55 | 27-FEB-17:40 | 1692.86 | 16-FEB-10:30 | 9165.93 | 22-FEB-17:00 | 0.00 |
March | 0.142437E+12 | 0.315596E+11 | 744.00 | 0.142321E+12 | 0.116361E+09 | 0.00 | 0.93 | 31-MAR-23:50 | 0.57 | 07-MAR-08:00 | 72005.98 | 31-MAR-23:50 | 72005.98 | 31-MAR-23:50 | 2105.08 | 06-MAR-11:20 | 18474.20 | 16-MAR-16:00 | 0.00 |
April | 0.188183E+12 | 0.515956E+11 | 720.00 | 0.188183E+12 | -0.0 | 0.00 | 1.00 | 01-APR-09:25 | 0.33 | 30-APR-23:05 | 78380.96 | 26-APR-18:50 | 78380.96 | 26-APR-18:50 | 0.00 | 09-APR-14:15 | 25886.54 | 14-APR-16:10 | 0.00 |
May | 0.575800E+11 | 0.185925E+11 | 744.00 | 0.575800E+11 | -0.0 | 0.00 | 0.60 | 31-MAY-23:15 | 0.24 | 13-MAY-06:10 | 39205.81 | 31-MAY-24:00 | 39205.81 | 31-MAY-24:00 | 0.00 | 11-MAY-16:10 | 12612.08 | 31-MAY-23:15 | 0.00 |
June | 0.105732E+12 | 0.370527E+11 | 720.00 | 0.105713E+12 | 18911936.88 | 0.00 | 0.79 | 30-JUN-23:10 | 0.49 | 21-JUN-06:10 | 57420.45 | 30-JUN-23:40 | 57420.45 | 30-JUN-23:40 | 959.35 | 30-JUN-10:00 | 20697.24 | 16-JUN-16:00 | 0.00 |
July | 0.158025E+12 | 0.513948E+11 | 744.00 | 0.156521E+12 | 0.150467E+10 | 0.00 | 1.00 | 01-JUL-18:11 | 0.69 | 01-JUL-06:10 | 75532.34 | 31-JUL-23:53 | 75400.45 | 31-JUL-23:57 | 4107.63 | 13-JUL-18:00 | 26865.94 | 02-JUL-18:00 | 0.00 |
August | 0.200639E+12 | 0.626132E+11 | 744.00 | 0.199111E+12 | 0.152819E+10 | 0.00 | 1.00 | 01-AUG-08:40 | 0.31 | 31-AUG-24:00 | 82100.49 | 28-AUG-16:25 | 78015.63 | 20-AUG-20:54 | 5766.56 | 28-AUG-16:15 | 28675.24 | 25-AUG-16:10 | 0.00 |
September | 0.571376E+11 | 0.174730E+11 | 720.00 | 0.557967E+11 | 0.134094E+10 | 0.00 | 0.56 | 30-SEP-23:55 | 0.23 | 22-SEP-06:10 | 39379.51 | 30-SEP-24:00 | 39379.51 | 30-SEP-24:00 | 2891.92 | 11-SEP-15:10 | 11295.97 | 30-SEP-23:40 | 0.00 |
October | 0.100584E+12 | 0.262571E+11 | 744.00 | 0.100283E+12 | 0.300597E+09 | 0.00 | 0.72 | 15-OCT-17:11 | 0.38 | 25-OCT-06:55 | 54399.08 | 31-OCT-24:00 | 54399.08 | 31-OCT-24:00 | 3073.75 | 03-OCT-09:40 | 16424.62 | 01-OCT-14:00 | 0.00 |
November | 0.138396E+12 | 0.307371E+11 | 720.00 | 0.137913E+12 | 0.483405E+09 | 0.00 | 0.88 | 09-NOV-17:00 | 0.58 | 18-NOV-07:35 | 63574.00 | 14-NOV-17:00 | 62377.03 | 09-NOV-17:00 | 3991.89 | 13-NOV-16:00 | 19466.77 | 09-NOV-16:50 | 0.00 |
December | 0.183880E+12 | 0.398070E+11 | 744.00 | 0.183874E+12 | 5721463.14 | 0.00 | 1.00 | 02-DEC-14:40 | 0.78 | 14-DEC-07:10 | 77864.26 | 26-DEC-17:30 | 77864.26 | 26-DEC-17:30 | 784.38 | 13-DEC-11:10 | 21747.37 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.145315E+13 | 0.394133E+12 | 8759.94 | 0.144739E+13 | 0.575794E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.413219E+11 | 0.101805E+11 | 672.00 | 0.412920E+11 | -0.0 | 0.00 | 0.39 | 0.00 | 25257.27 | 25257.27 | 0.00 | 8095.86 | 0.00 | ||||||
Maximum of Months | 0.200639E+12 | 0.626132E+11 | 744.00 | 0.199111E+12 | 0.152819E+10 | 0.00 | 1.00 | 0.78 | 82100.49 | 78380.96 | 5766.56 | 28675.24 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.318619E+10 | 0.808074E+09 | 711.39 | 0.318357E+10 | 2622844.41 | 0.00 | 0.37 | 31-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2486.06 | 24-JAN-17:00 | 2486.06 | 24-JAN-17:00 | 79.94 | 09-JAN-11:50 | 822.93 | 31-JAN-17:00 | 0.00 |
February | 0.689903E+10 | 0.148875E+10 | 672.00 | 0.685682E+10 | 42214437.04 | 0.00 | 0.52 | 22-FEB-17:00 | 0.20 | 13-FEB-07:10 | 4147.35 | 22-FEB-17:00 | 4094.77 | 22-FEB-17:00 | 169.64 | 16-FEB-10:40 | 926.99 | 22-FEB-17:00 | 0.00 |
March | 0.135869E+11 | 0.304206E+10 | 744.00 | 0.135755E+11 | 11439091.27 | 0.00 | 0.89 | 31-MAR-23:20 | 0.47 | 27-MAR-06:10 | 7036.01 | 31-MAR-23:20 | 7036.01 | 31-MAR-23:20 | 209.05 | 06-MAR-11:20 | 1875.12 | 16-MAR-16:00 | 0.00 |
April | 0.188898E+11 | 0.521379E+10 | 720.00 | 0.188898E+11 | 0.00 | 0.00 | 1.00 | 01-APR-10:30 | 0.34 | 30-APR-23:05 | 7952.94 | 26-APR-18:30 | 7952.94 | 26-APR-18:30 | 0.00 | 05-APR-02:30 | 2648.43 | 14-APR-16:10 | 0.00 |
May | 0.582896E+10 | 0.189375E+10 | 744.00 | 0.582896E+10 | 0.00 | 0.00 | 0.59 | 31-MAY-23:35 | 0.21 | 13-MAY-06:30 | 3945.43 | 31-MAY-24:00 | 3945.43 | 31-MAY-24:00 | 0.00 | 11-MAY-04:50 | 1265.43 | 31-MAY-23:15 | 0.00 |
June | 0.107650E+11 | 0.378022E+10 | 720.00 | 0.107632E+11 | 1756784.15 | 0.00 | 0.79 | 30-JUN-23:10 | 0.47 | 21-JUN-06:10 | 5812.09 | 30-JUN-23:40 | 5812.09 | 30-JUN-23:40 | 94.97 | 30-JUN-10:00 | 2127.25 | 16-JUN-16:00 | 0.00 |
July | 0.160141E+11 | 0.521849E+10 | 744.00 | 0.158636E+11 | 0.150481E+09 | 0.00 | 1.00 | 01-JUL-18:10 | 0.67 | 01-JUL-06:10 | 7613.33 | 31-JUL-23:53 | 7600.01 | 31-JUL-23:57 | 410.73 | 13-JUL-18:00 | 2749.89 | 02-JUL-18:00 | 0.00 |
August | 0.202826E+11 | 0.635179E+10 | 744.00 | 0.201288E+11 | 0.153808E+09 | 0.00 | 1.00 | 01-AUG-09:30 | 0.31 | 31-AUG-24:00 | 8316.71 | 28-AUG-16:15 | 8004.29 | 20-AUG-21:05 | 589.01 | 28-AUG-16:15 | 2933.88 | 25-AUG-16:10 | 0.00 |
September | 0.582207E+10 | 0.178596E+10 | 720.00 | 0.568743E+10 | 0.134640E+09 | 0.00 | 0.55 | 30-SEP-23:55 | 0.20 | 22-SEP-06:40 | 3981.41 | 30-SEP-23:55 | 3981.41 | 30-SEP-23:55 | 291.48 | 11-SEP-15:10 | 1143.45 | 30-SEP-23:40 | 0.00 |
October | 0.970800E+10 | 0.256391E+10 | 744.00 | 0.967805E+10 | 29952359.05 | 0.00 | 0.73 | 15-OCT-17:11 | 0.31 | 25-OCT-06:55 | 5255.56 | 31-OCT-23:40 | 5255.56 | 31-OCT-23:40 | 308.12 | 03-OCT-09:40 | 1710.97 | 01-OCT-14:00 | 0.00 |
November | 0.129882E+11 | 0.291944E+10 | 720.00 | 0.129403E+11 | 47951001.36 | 0.00 | 0.87 | 09-NOV-17:00 | 0.45 | 24-NOV-07:05 | 6379.85 | 14-NOV-17:00 | 6284.87 | 09-NOV-17:00 | 400.24 | 13-NOV-16:10 | 1965.87 | 09-NOV-16:50 | 0.00 |
December | 0.169957E+11 | 0.373431E+10 | 744.00 | 0.169951E+11 | 535911.21 | 0.00 | 1.00 | 21-DEC-16:10 | 0.65 | 18-DEC-07:10 | 7844.73 | 26-DEC-17:10 | 7844.73 | 26-DEC-17:10 | 72.25 | 13-DEC-11:20 | 2222.88 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.140966E+12 | 0.388006E+11 | 8727.39 | 0.140391E+12 | 0.575401E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.318619E+10 | 0.808074E+09 | 672.00 | 0.318357E+10 | 0.00 | 0.00 | 0.37 | 0.00 | 2486.06 | 2486.06 | 0.00 | 822.93 | 0.00 | ||||||
Maximum of Months | 0.202826E+11 | 0.635179E+10 | 744.00 | 0.201288E+11 | 0.153808E+09 | 0.00 | 1.00 | 0.67 | 8316.71 | 8004.29 | 589.01 | 2933.88 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.88 | 442.92 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 47.15 | 446.26 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.54 | 384.45 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.82 | 202.07 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.93 | 132.69 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 643.43 | 52.54 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 547.12 | 40.91 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 447.08 | 55.58 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.94 | 81.91 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.75 | 273.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.62 | 413.69 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.63 | 554.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.50 | 255.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.63 | 40.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 643.43 | 554.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.88 | 442.92 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 47.15 | 446.26 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.54 | 384.45 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.82 | 202.07 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.93 | 132.69 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 643.43 | 52.54 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 547.12 | 40.91 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 447.08 | 55.58 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.94 | 81.91 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.75 | 273.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.62 | 413.69 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.63 | 554.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.50 | 255.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.63 | 40.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 643.43 | 554.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.88 | 442.92 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 47.15 | 446.26 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.54 | 384.45 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.82 | 202.07 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.93 | 132.69 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 643.43 | 52.54 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 547.12 | 40.91 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 447.08 | 55.58 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.94 | 81.91 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.75 | 273.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.62 | 413.69 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.63 | 554.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.50 | 255.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.63 | 40.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 643.43 | 554.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.88 | 442.92 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 47.15 | 446.26 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.54 | 384.45 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.82 | 202.07 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.93 | 132.69 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 643.43 | 52.54 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 547.12 | 40.91 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 447.08 | 55.58 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.94 | 81.91 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.75 | 273.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.62 | 413.69 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.63 | 554.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.50 | 255.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.63 | 40.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 643.43 | 554.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.88 | 442.90 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 47.15 | 446.24 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.53 | 384.43 | 0.00 | 0.00 | 0.00 |
April | 185.18 | 1.92 | 183.26 | 296.80 | 202.06 | 0.00 | 0.00 | 0.00 |
May | 216.78 | 17.36 | 199.42 | 413.92 | 132.69 | 0.00 | 0.00 | 0.00 |
June | 251.91 | 45.77 | 206.14 | 643.40 | 52.54 | 0.00 | 0.00 | 0.00 |
July | 214.83 | 22.38 | 192.45 | 547.10 | 40.90 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.10 | 447.06 | 55.58 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.56 | 377.92 | 81.91 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.74 | 273.55 | 0.00 | 0.00 | 0.00 |
November | 105.46 | 0.00 | 105.46 | 70.62 | 413.67 | 0.00 | 0.00 | 0.00 |
December | 93.75 | 0.00 | 93.75 | 34.63 | 554.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.68 | 272.49 | 255.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.75 | 0.00 | 93.75 | 34.63 | 40.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.91 | 45.77 | 206.14 | 643.40 | 554.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.28 | 226.01 | 134.27 | 452.26 | 450.86 | 0.00 | 0.00 | 0.00 |
February | 355.13 | 203.15 | 151.98 | 396.41 | 455.75 | 0.00 | 0.00 | 0.00 |
March | 444.43 | 228.62 | 215.81 | 573.92 | 388.78 | 0.00 | 0.00 | 0.00 |
April | 634.39 | 378.11 | 256.29 | 1043.93 | 205.53 | 0.00 | 0.00 | 0.00 |
May | 657.46 | 389.74 | 267.72 | 1155.26 | 147.87 | 0.00 | 0.00 | 0.00 |
June | 685.29 | 425.83 | 259.46 | 1383.24 | 55.69 | 0.00 | 0.00 | 0.00 |
July | 578.77 | 326.34 | 252.42 | 1180.94 | 41.81 | 0.00 | 0.00 | 0.00 |
August | 549.30 | 313.49 | 235.82 | 1111.40 | 53.89 | 0.00 | 0.00 | 0.00 |
September | 450.74 | 217.26 | 233.47 | 877.86 | 85.18 | 0.00 | 0.00 | 0.00 |
October | 452.74 | 275.53 | 177.21 | 705.04 | 278.16 | 0.00 | 0.00 | 0.00 |
November | 348.13 | 208.99 | 139.14 | 435.50 | 418.65 | 0.00 | 0.00 | 0.00 |
December | 317.41 | 191.66 | 125.75 | 344.87 | 549.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 486.77 | 282.43 | 204.34 | 806.98 | 260.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 317.41 | 191.66 | 125.75 | 344.87 | 41.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.29 | 425.83 | 267.72 | 1383.24 | 549.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.28 | 226.01 | 134.27 | 452.26 | 450.86 | 0.00 | 0.00 | 0.00 |
February | 355.13 | 203.15 | 151.98 | 396.41 | 455.75 | 0.00 | 0.00 | 0.00 |
March | 444.43 | 228.62 | 215.81 | 573.92 | 388.78 | 0.00 | 0.00 | 0.00 |
April | 634.39 | 378.11 | 256.29 | 1043.93 | 205.53 | 0.00 | 0.00 | 0.00 |
May | 657.46 | 389.74 | 267.72 | 1155.26 | 147.87 | 0.00 | 0.00 | 0.00 |
June | 685.29 | 425.83 | 259.46 | 1383.24 | 55.69 | 0.00 | 0.00 | 0.00 |
July | 578.77 | 326.34 | 252.42 | 1180.94 | 41.81 | 0.00 | 0.00 | 0.00 |
August | 549.30 | 313.49 | 235.82 | 1111.40 | 53.89 | 0.00 | 0.00 | 0.00 |
September | 450.74 | 217.26 | 233.47 | 877.86 | 85.18 | 0.00 | 0.00 | 0.00 |
October | 452.74 | 275.53 | 177.21 | 705.04 | 278.16 | 0.00 | 0.00 | 0.00 |
November | 348.13 | 208.99 | 139.14 | 435.50 | 418.65 | 0.00 | 0.00 | 0.00 |
December | 317.41 | 191.66 | 125.75 | 344.87 | 549.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 486.77 | 282.43 | 204.34 | 806.98 | 260.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 317.41 | 191.66 | 125.75 | 344.87 | 41.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.29 | 425.83 | 267.72 | 1383.24 | 549.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.27 | 226.01 | 134.26 | 452.25 | 450.85 | 0.00 | 0.00 | 0.00 |
February | 355.12 | 203.15 | 151.98 | 396.40 | 455.74 | 0.00 | 0.00 | 0.00 |
March | 444.42 | 228.61 | 215.81 | 573.90 | 388.77 | 0.00 | 0.00 | 0.00 |
April | 634.38 | 378.10 | 256.28 | 1043.91 | 205.52 | 0.00 | 0.00 | 0.00 |
May | 657.45 | 389.73 | 267.72 | 1155.23 | 147.87 | 0.00 | 0.00 | 0.00 |
June | 685.27 | 425.82 | 259.45 | 1383.21 | 55.69 | 0.00 | 0.00 | 0.00 |
July | 578.76 | 326.34 | 252.42 | 1180.92 | 41.81 | 0.00 | 0.00 | 0.00 |
August | 549.29 | 313.48 | 235.81 | 1111.38 | 53.89 | 0.00 | 0.00 | 0.00 |
September | 450.73 | 217.26 | 233.47 | 877.84 | 85.18 | 0.00 | 0.00 | 0.00 |
October | 452.73 | 275.53 | 177.20 | 705.03 | 278.16 | 0.00 | 0.00 | 0.00 |
November | 348.13 | 208.98 | 139.14 | 435.49 | 418.64 | 0.00 | 0.00 | 0.00 |
December | 317.40 | 191.66 | 125.74 | 344.86 | 549.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 486.76 | 282.42 | 204.34 | 806.97 | 260.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 317.40 | 191.66 | 125.74 | 344.86 | 41.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.27 | 425.82 | 267.72 | 1383.21 | 549.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1249.20 | 420.23 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.91 | 411.43 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 632.58 | 372.78 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 690.08 | 212.20 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.66 | 146.10 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.68 | 55.38 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.60 | 42.01 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 650.04 | 56.86 | 0.00 | 0.00 | 0.00 |
September | 380.25 | 162.22 | 218.02 | 794.45 | 84.95 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.46 | 264.98 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.92 | 388.51 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1103.34 | 506.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.72 | 246.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.66 | 42.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1249.20 | 506.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1249.20 | 420.23 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.91 | 411.43 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 632.58 | 372.78 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 690.08 | 212.20 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.66 | 146.10 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.68 | 55.38 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.60 | 42.01 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 650.04 | 56.86 | 0.00 | 0.00 | 0.00 |
September | 380.24 | 162.22 | 218.02 | 794.45 | 84.95 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.46 | 264.98 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.92 | 388.51 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1103.34 | 506.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.72 | 246.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.66 | 42.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1249.20 | 506.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1249.20 | 420.23 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.91 | 411.43 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 632.58 | 372.78 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 690.08 | 212.20 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.66 | 146.10 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.68 | 55.38 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.60 | 42.01 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 650.04 | 56.86 | 0.00 | 0.00 | 0.00 |
September | 380.25 | 162.22 | 218.02 | 794.45 | 84.95 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.46 | 264.98 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.92 | 388.51 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1103.34 | 506.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.72 | 246.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.66 | 42.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1249.20 | 506.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1249.20 | 420.23 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.91 | 411.43 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 632.58 | 372.78 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 690.08 | 212.20 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.66 | 146.10 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.68 | 55.38 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.60 | 42.01 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 650.04 | 56.86 | 0.00 | 0.00 | 0.00 |
September | 380.24 | 162.22 | 218.02 | 794.45 | 84.95 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.46 | 264.98 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.92 | 388.51 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1103.34 | 506.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.72 | 246.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.66 | 42.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1249.20 | 506.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.45 | 660.06 | 166.39 | 1249.15 | 420.22 | 0.00 | 0.00 | 0.00 |
February | 522.55 | 352.43 | 170.12 | 707.88 | 411.41 | 0.00 | 0.00 | 0.00 |
March | 434.80 | 223.95 | 210.86 | 632.55 | 372.77 | 0.00 | 0.00 | 0.00 |
April | 370.13 | 149.57 | 220.56 | 690.05 | 212.19 | 0.00 | 0.00 | 0.00 |
May | 248.03 | 40.98 | 207.05 | 509.64 | 146.10 | 0.00 | 0.00 | 0.00 |
June | 212.38 | 16.37 | 196.01 | 577.66 | 55.38 | 0.00 | 0.00 | 0.00 |
July | 217.02 | 22.45 | 194.57 | 563.57 | 42.00 | 0.00 | 0.00 | 0.00 |
August | 263.88 | 72.92 | 190.96 | 650.01 | 56.86 | 0.00 | 0.00 | 0.00 |
September | 380.23 | 162.22 | 218.01 | 794.42 | 84.94 | 0.00 | 0.00 | 0.00 |
October | 605.86 | 419.34 | 186.51 | 1007.42 | 264.97 | 0.00 | 0.00 | 0.00 |
November | 706.05 | 540.80 | 165.25 | 1051.88 | 388.50 | 0.00 | 0.00 | 0.00 |
December | 768.35 | 608.25 | 160.10 | 1103.29 | 506.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 462.99 | 272.39 | 190.60 | 795.69 | 246.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.38 | 16.37 | 160.10 | 509.64 | 42.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.45 | 660.06 | 220.56 | 1249.15 | 506.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.74 | 234.15 | 142.59 | 526.31 | 531.65 | 0.00 | 0.00 | 0.00 |
February | 305.20 | 147.54 | 157.65 | 337.04 | 541.77 | 0.00 | 0.00 | 0.00 |
March | 404.24 | 192.71 | 211.53 | 518.11 | 474.02 | 0.00 | 0.00 | 0.00 |
April | 620.72 | 354.08 | 266.64 | 1021.17 | 287.88 | 0.00 | 0.00 | 0.00 |
May | 622.32 | 348.93 | 273.38 | 1108.58 | 190.74 | 0.00 | 0.00 | 0.00 |
June | 661.59 | 389.12 | 272.47 | 1331.15 | 87.09 | 0.00 | 0.00 | 0.00 |
July | 481.52 | 224.77 | 256.75 | 987.85 | 70.93 | 0.00 | 0.00 | 0.00 |
August | 459.17 | 230.60 | 228.57 | 926.06 | 101.91 | 0.00 | 0.00 | 0.00 |
September | 400.24 | 168.17 | 232.08 | 786.65 | 113.29 | 0.00 | 0.00 | 0.00 |
October | 409.53 | 234.17 | 175.36 | 646.05 | 343.44 | 0.00 | 0.00 | 0.00 |
November | 377.19 | 227.74 | 149.45 | 507.75 | 516.96 | 0.00 | 0.00 | 0.00 |
December | 304.00 | 173.09 | 130.91 | 363.93 | 685.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.39 | 244.10 | 208.29 | 756.77 | 327.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 304.00 | 147.54 | 130.91 | 337.04 | 70.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.59 | 389.12 | 273.38 | 1331.15 | 685.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.74 | 234.15 | 142.59 | 526.31 | 531.65 | 0.00 | 0.00 | 0.00 |
February | 305.20 | 147.54 | 157.65 | 337.04 | 541.77 | 0.00 | 0.00 | 0.00 |
March | 404.24 | 192.71 | 211.53 | 518.11 | 474.02 | 0.00 | 0.00 | 0.00 |
April | 620.72 | 354.08 | 266.64 | 1021.17 | 287.88 | 0.00 | 0.00 | 0.00 |
May | 622.32 | 348.93 | 273.38 | 1108.58 | 190.74 | 0.00 | 0.00 | 0.00 |
June | 661.59 | 389.12 | 272.47 | 1331.15 | 87.09 | 0.00 | 0.00 | 0.00 |
July | 481.52 | 224.77 | 256.75 | 987.85 | 70.93 | 0.00 | 0.00 | 0.00 |
August | 459.17 | 230.60 | 228.57 | 926.06 | 101.91 | 0.00 | 0.00 | 0.00 |
September | 400.24 | 168.17 | 232.08 | 786.65 | 113.29 | 0.00 | 0.00 | 0.00 |
October | 409.53 | 234.17 | 175.36 | 646.05 | 343.44 | 0.00 | 0.00 | 0.00 |
November | 377.19 | 227.74 | 149.45 | 507.75 | 516.96 | 0.00 | 0.00 | 0.00 |
December | 304.00 | 173.09 | 130.91 | 363.93 | 685.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.39 | 244.10 | 208.29 | 756.77 | 327.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 304.00 | 147.54 | 130.91 | 337.04 | 70.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.59 | 389.12 | 273.38 | 1331.15 | 685.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.73 | 234.15 | 142.59 | 526.30 | 531.64 | 0.00 | 0.00 | 0.00 |
February | 305.19 | 147.54 | 157.65 | 337.04 | 541.76 | 0.00 | 0.00 | 0.00 |
March | 404.23 | 192.70 | 211.53 | 518.10 | 474.01 | 0.00 | 0.00 | 0.00 |
April | 620.71 | 354.07 | 266.64 | 1021.15 | 287.88 | 0.00 | 0.00 | 0.00 |
May | 622.31 | 348.93 | 273.38 | 1108.56 | 190.74 | 0.00 | 0.00 | 0.00 |
June | 661.57 | 389.11 | 272.46 | 1331.13 | 87.09 | 0.00 | 0.00 | 0.00 |
July | 481.51 | 224.77 | 256.74 | 987.83 | 70.93 | 0.00 | 0.00 | 0.00 |
August | 459.16 | 230.60 | 228.56 | 926.05 | 101.91 | 0.00 | 0.00 | 0.00 |
September | 400.24 | 168.16 | 232.07 | 786.64 | 113.28 | 0.00 | 0.00 | 0.00 |
October | 409.52 | 234.16 | 175.36 | 646.04 | 343.43 | 0.00 | 0.00 | 0.00 |
November | 377.18 | 227.73 | 149.45 | 507.74 | 516.95 | 0.00 | 0.00 | 0.00 |
December | 303.99 | 173.08 | 130.91 | 363.92 | 685.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.38 | 244.09 | 208.28 | 756.76 | 327.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.99 | 147.54 | 130.91 | 337.04 | 70.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.57 | 389.11 | 273.38 | 1331.13 | 685.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.86 | 0.00 | 501.86 | 422.54 | 1968.52 | 0.00 | 0.00 | 0.00 |
February | 571.86 | 0.00 | 571.86 | 290.13 | 1965.05 | 0.00 | 0.00 | 0.00 |
March | 760.00 | 0.00 | 760.00 | 723.32 | 1739.61 | 0.00 | 0.00 | 0.00 |
April | 925.95 | 9.61 | 916.34 | 1539.09 | 951.20 | 0.00 | 0.00 | 0.00 |
May | 1083.92 | 86.79 | 997.13 | 2099.14 | 643.94 | 0.00 | 0.00 | 0.00 |
June | 1259.58 | 228.85 | 1030.73 | 3248.92 | 267.24 | 0.00 | 0.00 | 0.00 |
July | 1074.18 | 111.91 | 962.28 | 2772.81 | 203.13 | 0.00 | 0.00 | 0.00 |
August | 867.06 | 21.54 | 845.52 | 2298.95 | 253.52 | 0.00 | 0.00 | 0.00 |
September | 818.06 | 0.22 | 817.84 | 1914.81 | 395.59 | 0.00 | 0.00 | 0.00 |
October | 632.91 | 0.00 | 632.91 | 938.73 | 1250.18 | 0.00 | 0.00 | 0.00 |
November | 527.33 | 0.00 | 527.33 | 418.61 | 1823.43 | 0.00 | 0.00 | 0.00 |
December | 468.78 | 0.00 | 468.78 | 260.01 | 2398.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 791.75 | 38.32 | 753.43 | 1415.74 | 1151.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.78 | 0.00 | 468.78 | 260.01 | 203.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1259.58 | 228.85 | 1030.73 | 3248.92 | 2398.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1080.83 | 678.04 | 402.80 | 1369.94 | 1261.16 | 0.00 | 0.00 | 0.00 |
February | 1065.37 | 609.44 | 455.93 | 1191.42 | 1275.62 | 0.00 | 0.00 | 0.00 |
March | 1333.26 | 685.84 | 647.42 | 1712.77 | 1118.03 | 0.00 | 0.00 | 0.00 |
April | 1903.16 | 1134.31 | 768.85 | 3102.39 | 626.17 | 0.00 | 0.00 | 0.00 |
May | 1972.36 | 1169.20 | 803.16 | 3436.97 | 444.63 | 0.00 | 0.00 | 0.00 |
June | 2055.84 | 1277.47 | 778.37 | 4118.28 | 179.75 | 0.00 | 0.00 | 0.00 |
July | 1736.29 | 979.02 | 757.26 | 3512.90 | 137.51 | 0.00 | 0.00 | 0.00 |
August | 1647.89 | 940.45 | 707.44 | 3311.36 | 173.02 | 0.00 | 0.00 | 0.00 |
September | 1352.20 | 651.79 | 700.42 | 2610.59 | 259.42 | 0.00 | 0.00 | 0.00 |
October | 1358.21 | 826.60 | 531.61 | 2101.93 | 804.41 | 0.00 | 0.00 | 0.00 |
November | 1044.39 | 626.96 | 417.43 | 1311.74 | 1176.62 | 0.00 | 0.00 | 0.00 |
December | 952.21 | 574.97 | 377.24 | 1061.12 | 1529.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1460.30 | 847.28 | 613.02 | 2409.22 | 746.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 952.21 | 574.97 | 377.24 | 1061.12 | 137.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.84 | 1277.47 | 803.16 | 4118.28 | 1529.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4132.36 | 3300.40 | 831.96 | 6197.57 | 2066.93 | 0.00 | 0.00 | 0.00 |
February | 2612.84 | 1762.19 | 850.65 | 3515.60 | 1982.82 | 0.00 | 0.00 | 0.00 |
March | 2174.07 | 1119.76 | 1054.31 | 3151.80 | 1795.65 | 0.00 | 0.00 | 0.00 |
April | 1850.70 | 747.87 | 1102.84 | 3455.76 | 1029.59 | 0.00 | 0.00 | 0.00 |
May | 1240.16 | 204.89 | 1035.28 | 2567.07 | 711.62 | 0.00 | 0.00 | 0.00 |
June | 1061.94 | 81.86 | 980.08 | 2929.24 | 274.59 | 0.00 | 0.00 | 0.00 |
July | 1085.12 | 112.26 | 972.85 | 2854.65 | 205.09 | 0.00 | 0.00 | 0.00 |
August | 1319.45 | 364.63 | 954.82 | 3291.60 | 263.03 | 0.00 | 0.00 | 0.00 |
September | 1901.20 | 811.10 | 1090.10 | 3961.81 | 418.21 | 0.00 | 0.00 | 0.00 |
October | 3029.37 | 2096.77 | 932.59 | 5002.16 | 1293.62 | 0.00 | 0.00 | 0.00 |
November | 3530.36 | 2704.07 | 826.29 | 5225.72 | 1882.43 | 0.00 | 0.00 | 0.00 |
December | 3841.87 | 3041.36 | 800.51 | 5498.47 | 2447.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2315.01 | 1362.00 | 953.01 | 3975.55 | 1194.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.94 | 81.86 | 800.51 | 2567.07 | 205.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4132.36 | 3300.40 | 1102.84 | 6197.57 | 2447.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1130.21 | 702.44 | 427.76 | 1614.91 | 1430.92 | 0.00 | 0.00 | 0.00 |
February | 915.58 | 442.63 | 472.95 | 1048.36 | 1385.47 | 0.00 | 0.00 | 0.00 |
March | 1212.71 | 578.12 | 634.59 | 1607.41 | 1228.68 | 0.00 | 0.00 | 0.00 |
April | 1862.16 | 1062.23 | 799.93 | 3114.20 | 747.90 | 0.00 | 0.00 | 0.00 |
May | 1866.94 | 1046.79 | 820.14 | 3337.28 | 535.12 | 0.00 | 0.00 | 0.00 |
June | 1984.74 | 1167.35 | 817.39 | 4027.48 | 234.23 | 0.00 | 0.00 | 0.00 |
July | 1444.54 | 674.31 | 770.23 | 3025.46 | 173.41 | 0.00 | 0.00 | 0.00 |
August | 1377.50 | 691.81 | 685.69 | 2869.03 | 215.13 | 0.00 | 0.00 | 0.00 |
September | 1200.71 | 504.49 | 696.22 | 2382.67 | 301.47 | 0.00 | 0.00 | 0.00 |
October | 1228.58 | 702.50 | 526.08 | 1973.31 | 907.99 | 0.00 | 0.00 | 0.00 |
November | 1131.55 | 683.20 | 448.35 | 1569.41 | 1320.94 | 0.00 | 0.00 | 0.00 |
December | 911.99 | 519.26 | 392.73 | 1159.76 | 1706.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1357.14 | 732.28 | 624.86 | 2316.08 | 846.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 911.99 | 442.63 | 392.73 | 1048.36 | 173.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1984.74 | 1167.35 | 820.14 | 4027.48 | 1706.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.86 | 0.00 | 501.86 | 472.41 | 1805.23 | 0.00 | 0.00 | 0.00 |
February | 571.86 | 0.00 | 571.86 | 332.37 | 1769.87 | 0.00 | 0.00 | 0.00 |
March | 760.00 | 0.00 | 760.00 | 759.58 | 1629.51 | 0.00 | 0.00 | 0.00 |
April | 925.95 | 9.61 | 916.34 | 1527.05 | 933.78 | 0.00 | 0.00 | 0.00 |
May | 1083.92 | 86.79 | 997.13 | 2079.26 | 645.38 | 0.00 | 0.00 | 0.00 |
June | 1259.58 | 228.85 | 1030.73 | 3210.50 | 275.88 | 0.00 | 0.00 | 0.00 |
July | 1074.18 | 111.91 | 962.28 | 2728.74 | 213.85 | 0.00 | 0.00 | 0.00 |
August | 867.06 | 21.54 | 845.52 | 2265.33 | 261.13 | 0.00 | 0.00 | 0.00 |
September | 818.06 | 0.22 | 817.84 | 1889.09 | 401.81 | 0.00 | 0.00 | 0.00 |
October | 632.91 | 0.00 | 632.91 | 951.86 | 1181.25 | 0.00 | 0.00 | 0.00 |
November | 527.33 | 0.00 | 527.33 | 461.34 | 1668.61 | 0.00 | 0.00 | 0.00 |
December | 468.78 | 0.00 | 468.78 | 314.66 | 2180.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 791.75 | 38.32 | 753.43 | 1421.02 | 1077.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.78 | 0.00 | 468.78 | 314.66 | 213.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1259.58 | 228.85 | 1030.73 | 3210.50 | 2180.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1080.83 | 678.04 | 402.80 | 1411.82 | 1171.04 | 0.00 | 0.00 | 0.00 |
February | 1065.37 | 609.44 | 455.93 | 1225.54 | 1162.83 | 0.00 | 0.00 | 0.00 |
March | 1333.26 | 685.84 | 647.42 | 1740.01 | 1059.93 | 0.00 | 0.00 | 0.00 |
April | 1903.16 | 1134.31 | 768.85 | 3096.24 | 619.73 | 0.00 | 0.00 | 0.00 |
May | 1972.36 | 1169.20 | 803.16 | 3424.94 | 445.04 | 0.00 | 0.00 | 0.00 |
June | 2055.84 | 1277.47 | 778.37 | 4095.82 | 184.71 | 0.00 | 0.00 | 0.00 |
July | 1736.29 | 979.02 | 757.26 | 3488.36 | 143.89 | 0.00 | 0.00 | 0.00 |
August | 1647.89 | 940.45 | 707.44 | 3293.34 | 177.04 | 0.00 | 0.00 | 0.00 |
September | 1352.20 | 651.79 | 700.42 | 2597.65 | 263.48 | 0.00 | 0.00 | 0.00 |
October | 1358.21 | 826.60 | 531.61 | 2112.15 | 769.72 | 0.00 | 0.00 | 0.00 |
November | 1044.39 | 626.96 | 417.43 | 1347.68 | 1089.26 | 0.00 | 0.00 | 0.00 |
December | 952.21 | 574.97 | 377.24 | 1119.94 | 1395.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1460.30 | 847.28 | 613.02 | 2418.48 | 704.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 952.21 | 574.97 | 377.24 | 1119.94 | 143.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.84 | 1277.47 | 803.16 | 4095.82 | 1395.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4132.36 | 3300.40 | 831.96 | 6238.04 | 1942.07 | 0.00 | 0.00 | 0.00 |
February | 2612.84 | 1762.19 | 850.65 | 3554.99 | 1821.30 | 0.00 | 0.00 | 0.00 |
March | 2174.07 | 1119.76 | 1054.31 | 3175.48 | 1702.58 | 0.00 | 0.00 | 0.00 |
April | 1850.70 | 747.87 | 1102.84 | 3437.54 | 1012.80 | 0.00 | 0.00 | 0.00 |
May | 1240.16 | 204.89 | 1035.28 | 2545.46 | 709.16 | 0.00 | 0.00 | 0.00 |
June | 1061.94 | 81.86 | 980.08 | 2890.63 | 281.79 | 0.00 | 0.00 | 0.00 |
July | 1085.12 | 112.26 | 972.85 | 2810.43 | 214.77 | 0.00 | 0.00 | 0.00 |
August | 1319.45 | 364.63 | 954.82 | 3256.34 | 269.44 | 0.00 | 0.00 | 0.00 |
September | 1901.20 | 811.10 | 1090.10 | 3932.60 | 425.16 | 0.00 | 0.00 | 0.00 |
October | 3029.37 | 2096.77 | 932.59 | 5004.42 | 1241.60 | 0.00 | 0.00 | 0.00 |
November | 3530.36 | 2704.07 | 826.29 | 5260.71 | 1766.15 | 0.00 | 0.00 | 0.00 |
December | 3841.87 | 3041.36 | 800.51 | 5555.03 | 2276.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2315.01 | 1362.00 | 953.01 | 3976.23 | 1135.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.94 | 81.86 | 800.51 | 2545.46 | 214.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4132.36 | 3300.40 | 1102.84 | 6238.04 | 2276.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1130.21 | 702.44 | 427.76 | 1635.34 | 1337.59 | 0.00 | 0.00 | 0.00 |
February | 915.58 | 442.63 | 472.95 | 1066.39 | 1275.79 | 0.00 | 0.00 | 0.00 |
March | 1212.71 | 578.12 | 634.59 | 1620.09 | 1166.48 | 0.00 | 0.00 | 0.00 |
April | 1862.16 | 1062.23 | 799.93 | 3099.36 | 735.27 | 0.00 | 0.00 | 0.00 |
May | 1866.94 | 1046.79 | 820.14 | 3318.35 | 532.63 | 0.00 | 0.00 | 0.00 |
June | 1984.74 | 1167.35 | 817.39 | 3999.69 | 238.05 | 0.00 | 0.00 | 0.00 |
July | 1444.54 | 674.31 | 770.23 | 2998.05 | 178.71 | 0.00 | 0.00 | 0.00 |
August | 1377.50 | 691.81 | 685.69 | 2846.97 | 218.66 | 0.00 | 0.00 | 0.00 |
September | 1200.71 | 504.49 | 696.22 | 2364.34 | 305.26 | 0.00 | 0.00 | 0.00 |
October | 1228.58 | 702.50 | 526.08 | 1973.34 | 869.14 | 0.00 | 0.00 | 0.00 |
November | 1131.55 | 683.20 | 448.35 | 1584.92 | 1235.74 | 0.00 | 0.00 | 0.00 |
December | 911.99 | 519.26 | 392.73 | 1186.52 | 1583.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1357.14 | 732.28 | 624.86 | 2313.00 | 804.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 911.99 | 442.63 | 392.73 | 1066.39 | 178.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1984.74 | 1167.35 | 820.14 | 3999.69 | 1583.02 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.184485E+09 | 0.118631E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.114062E+09 | 0.107959E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.354985E+09 | 0.102970E+10 |
April | 0.480016E+09 | 4981337.40 | 0.475035E+09 | 0.769345E+09 | 0.523767E+09 |
May | 0.580640E+09 | 46492323.30 | 0.534148E+09 | 0.110868E+10 | 0.355400E+09 |
June | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.136185E+09 |
July | 0.575426E+09 | 59947998.39 | 0.515478E+09 | 0.146540E+10 | 0.109563E+09 |
August | 0.464473E+09 | 11538584.38 | 0.452934E+09 | 0.119745E+10 | 0.148865E+09 |
September | 0.424087E+09 | 113210.59 | 0.423974E+09 | 0.979610E+09 | 0.212307E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.476087E+09 | 0.732694E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.183052E+09 | 0.107229E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744365.66 | 0.148437E+10 |
Annual Sum or Average | 0.499381E+10 | 0.241712E+09 | 0.475209E+10 | 0.859368E+10 | 0.807104E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744365.66 | 0.109563E+09 |
Maximum of Months | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.148437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.184485E+09 | 0.118631E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.114062E+09 | 0.107959E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.354984E+09 | 0.102970E+10 |
April | 0.480016E+09 | 4981331.42 | 0.475035E+09 | 0.769345E+09 | 0.523767E+09 |
May | 0.580640E+09 | 46492267.52 | 0.534148E+09 | 0.110868E+10 | 0.355400E+09 |
June | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.136185E+09 |
July | 0.575426E+09 | 59947926.46 | 0.515478E+09 | 0.146540E+10 | 0.109563E+09 |
August | 0.464472E+09 | 11538570.53 | 0.452934E+09 | 0.119745E+10 | 0.148864E+09 |
September | 0.424086E+09 | 113210.45 | 0.423973E+09 | 0.979609E+09 | 0.212307E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.476087E+09 | 0.732694E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.183052E+09 | 0.107229E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744279.13 | 0.148437E+10 |
Annual Sum or Average | 0.499380E+10 | 0.241712E+09 | 0.475209E+10 | 0.859367E+10 | 0.807104E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744279.13 | 0.109563E+09 |
Maximum of Months | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.148437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.184485E+09 | 0.118631E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.114062E+09 | 0.107959E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.354985E+09 | 0.102970E+10 |
April | 0.480016E+09 | 4981337.40 | 0.475035E+09 | 0.769345E+09 | 0.523767E+09 |
May | 0.580640E+09 | 46492323.30 | 0.534148E+09 | 0.110868E+10 | 0.355400E+09 |
June | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.136185E+09 |
July | 0.575426E+09 | 59947998.39 | 0.515478E+09 | 0.146540E+10 | 0.109563E+09 |
August | 0.464473E+09 | 11538584.38 | 0.452934E+09 | 0.119745E+10 | 0.148865E+09 |
September | 0.424087E+09 | 113210.59 | 0.423974E+09 | 0.979610E+09 | 0.212307E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.476087E+09 | 0.732694E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.183052E+09 | 0.107229E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744365.66 | 0.148437E+10 |
Annual Sum or Average | 0.499381E+10 | 0.241712E+09 | 0.475209E+10 | 0.859368E+10 | 0.807104E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744365.66 | 0.109563E+09 |
Maximum of Months | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.148437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.184485E+09 | 0.118631E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.114062E+09 | 0.107959E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.354984E+09 | 0.102970E+10 |
April | 0.480016E+09 | 4981331.42 | 0.475035E+09 | 0.769345E+09 | 0.523767E+09 |
May | 0.580640E+09 | 46492267.52 | 0.534148E+09 | 0.110868E+10 | 0.355400E+09 |
June | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.136185E+09 |
July | 0.575426E+09 | 59947926.46 | 0.515478E+09 | 0.146540E+10 | 0.109563E+09 |
August | 0.464472E+09 | 11538570.53 | 0.452934E+09 | 0.119745E+10 | 0.148864E+09 |
September | 0.424086E+09 | 113210.45 | 0.423973E+09 | 0.979609E+09 | 0.212307E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.476087E+09 | 0.732694E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.183052E+09 | 0.107229E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744279.13 | 0.148437E+10 |
Annual Sum or Average | 0.499380E+10 | 0.241712E+09 | 0.475209E+10 | 0.859367E+10 | 0.807104E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 92744279.13 | 0.109563E+09 |
Maximum of Months | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166777E+10 | 0.148437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268829E+09 | 0.00 | 0.268829E+09 | 0.184478E+09 | 0.118626E+10 |
February | 0.276680E+09 | 0.00 | 0.276680E+09 | 0.114058E+09 | 0.107955E+10 |
March | 0.407105E+09 | 0.00 | 0.407105E+09 | 0.354970E+09 | 0.102966E+10 |
April | 0.479997E+09 | 4981136.63 | 0.475016E+09 | 0.769314E+09 | 0.523746E+09 |
May | 0.580617E+09 | 46490449.46 | 0.534127E+09 | 0.110864E+10 | 0.355386E+09 |
June | 0.652949E+09 | 0.118634E+09 | 0.534314E+09 | 0.166771E+10 | 0.136179E+09 |
July | 0.575403E+09 | 59945582.22 | 0.515457E+09 | 0.146534E+10 | 0.109559E+09 |
August | 0.464454E+09 | 11538119.32 | 0.452916E+09 | 0.119741E+10 | 0.148859E+09 |
September | 0.424070E+09 | 113206.03 | 0.423956E+09 | 0.979570E+09 | 0.212299E+09 |
October | 0.339029E+09 | 0.00 | 0.339029E+09 | 0.476068E+09 | 0.732664E+09 |
November | 0.273362E+09 | 0.00 | 0.273362E+09 | 0.183045E+09 | 0.107224E+10 |
December | 0.251111E+09 | 0.00 | 0.251111E+09 | 92740627.65 | 0.148431E+10 |
Annual Sum or Average | 0.499361E+10 | 0.241703E+09 | 0.475190E+10 | 0.859333E+10 | 0.807071E+10 |
Minimum of Months | 0.251111E+09 | 0.00 | 0.251111E+09 | 92740627.65 | 0.109559E+09 |
Maximum of Months | 0.652949E+09 | 0.118634E+09 | 0.534314E+09 | 0.166771E+10 | 0.148431E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.964978E+09 | 0.605357E+09 | 0.359620E+09 | 0.121134E+10 | 0.120759E+10 |
February | 0.859124E+09 | 0.491458E+09 | 0.367666E+09 | 0.958998E+09 | 0.110255E+10 |
March | 0.119035E+10 | 0.612325E+09 | 0.578025E+09 | 0.153718E+10 | 0.104130E+10 |
April | 0.164435E+10 | 0.980052E+09 | 0.664295E+09 | 0.270586E+10 | 0.532723E+09 |
May | 0.176094E+10 | 0.104387E+10 | 0.717070E+09 | 0.309424E+10 | 0.396064E+09 |
June | 0.177626E+10 | 0.110374E+10 | 0.672518E+09 | 0.358536E+10 | 0.144348E+09 |
July | 0.155017E+10 | 0.874079E+09 | 0.676093E+09 | 0.316303E+10 | 0.111984E+09 |
August | 0.147125E+10 | 0.839640E+09 | 0.631608E+09 | 0.297678E+10 | 0.144350E+09 |
September | 0.116832E+10 | 0.563149E+09 | 0.605167E+09 | 0.227540E+10 | 0.220799E+09 |
October | 0.121262E+10 | 0.737992E+09 | 0.474628E+09 | 0.188837E+10 | 0.745025E+09 |
November | 0.902358E+09 | 0.541698E+09 | 0.360661E+09 | 0.112881E+10 | 0.108514E+10 |
December | 0.850139E+09 | 0.513339E+09 | 0.336800E+09 | 0.923687E+09 | 0.147203E+10 |
Annual Sum or Average | 0.153509E+11 | 0.890670E+10 | 0.644415E+10 | 0.254490E+11 | 0.820391E+10 |
Minimum of Months | 0.850139E+09 | 0.491458E+09 | 0.336800E+09 | 0.923687E+09 | 0.111984E+09 |
Maximum of Months | 0.177626E+10 | 0.110374E+10 | 0.717070E+09 | 0.358536E+10 | 0.147203E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.964978E+09 | 0.605357E+09 | 0.359620E+09 | 0.121134E+10 | 0.120759E+10 |
February | 0.859124E+09 | 0.491458E+09 | 0.367666E+09 | 0.958998E+09 | 0.110255E+10 |
March | 0.119035E+10 | 0.612325E+09 | 0.578025E+09 | 0.153718E+10 | 0.104130E+10 |
April | 0.164435E+10 | 0.980052E+09 | 0.664295E+09 | 0.270586E+10 | 0.532723E+09 |
May | 0.176094E+10 | 0.104387E+10 | 0.717070E+09 | 0.309424E+10 | 0.396064E+09 |
June | 0.177626E+10 | 0.110374E+10 | 0.672518E+09 | 0.358536E+10 | 0.144348E+09 |
July | 0.155017E+10 | 0.874079E+09 | 0.676093E+09 | 0.316303E+10 | 0.111984E+09 |
August | 0.147125E+10 | 0.839640E+09 | 0.631608E+09 | 0.297678E+10 | 0.144350E+09 |
September | 0.116832E+10 | 0.563149E+09 | 0.605167E+09 | 0.227540E+10 | 0.220799E+09 |
October | 0.121262E+10 | 0.737992E+09 | 0.474628E+09 | 0.188837E+10 | 0.745025E+09 |
November | 0.902358E+09 | 0.541698E+09 | 0.360661E+09 | 0.112881E+10 | 0.108514E+10 |
December | 0.850139E+09 | 0.513339E+09 | 0.336800E+09 | 0.923687E+09 | 0.147203E+10 |
Annual Sum or Average | 0.153509E+11 | 0.890670E+10 | 0.644415E+10 | 0.254490E+11 | 0.820391E+10 |
Minimum of Months | 0.850139E+09 | 0.491458E+09 | 0.336800E+09 | 0.923687E+09 | 0.111984E+09 |
Maximum of Months | 0.177626E+10 | 0.110374E+10 | 0.717070E+09 | 0.358536E+10 | 0.147203E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.964960E+09 | 0.605346E+09 | 0.359614E+09 | 0.121132E+10 | 0.120757E+10 |
February | 0.859108E+09 | 0.491449E+09 | 0.367659E+09 | 0.958981E+09 | 0.110253E+10 |
March | 0.119033E+10 | 0.612314E+09 | 0.578014E+09 | 0.153715E+10 | 0.104128E+10 |
April | 0.164432E+10 | 0.980034E+09 | 0.664283E+09 | 0.270581E+10 | 0.532713E+09 |
May | 0.176091E+10 | 0.104385E+10 | 0.717057E+09 | 0.309418E+10 | 0.396057E+09 |
June | 0.177623E+10 | 0.110372E+10 | 0.672505E+09 | 0.358529E+10 | 0.144346E+09 |
July | 0.155014E+10 | 0.874063E+09 | 0.676081E+09 | 0.316297E+10 | 0.111982E+09 |
August | 0.147122E+10 | 0.839624E+09 | 0.631596E+09 | 0.297672E+10 | 0.144348E+09 |
September | 0.116829E+10 | 0.563138E+09 | 0.605156E+09 | 0.227536E+10 | 0.220795E+09 |
October | 0.121260E+10 | 0.737979E+09 | 0.474619E+09 | 0.188834E+10 | 0.745011E+09 |
November | 0.902342E+09 | 0.541688E+09 | 0.360654E+09 | 0.112879E+10 | 0.108512E+10 |
December | 0.850123E+09 | 0.513329E+09 | 0.336794E+09 | 0.923670E+09 | 0.147201E+10 |
Annual Sum or Average | 0.153506E+11 | 0.890654E+10 | 0.644403E+10 | 0.254486E+11 | 0.820376E+10 |
Minimum of Months | 0.850123E+09 | 0.491449E+09 | 0.336794E+09 | 0.923670E+09 | 0.111982E+09 |
Maximum of Months | 0.177623E+10 | 0.110372E+10 | 0.717057E+09 | 0.358529E+10 | 0.147201E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334587E+10 | 0.112555E+10 |
February | 0.126421E+10 | 0.852627E+09 | 0.411583E+09 | 0.171257E+10 | 0.995331E+09 |
March | 0.116462E+10 | 0.599841E+09 | 0.564780E+09 | 0.169429E+10 | 0.998457E+09 |
April | 0.959417E+09 | 0.387698E+09 | 0.571719E+09 | 0.178869E+10 | 0.550013E+09 |
May | 0.664339E+09 | 0.109757E+09 | 0.554583E+09 | 0.136508E+10 | 0.391324E+09 |
June | 0.550516E+09 | 42437723.04 | 0.508079E+09 | 0.149735E+10 | 0.143547E+09 |
July | 0.581283E+09 | 60138531.93 | 0.521144E+09 | 0.150954E+10 | 0.112509E+09 |
August | 0.706812E+09 | 0.195328E+09 | 0.511484E+09 | 0.174106E+10 | 0.152307E+09 |
September | 0.985596E+09 | 0.420480E+09 | 0.565116E+09 | 0.205923E+10 | 0.220185E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269838E+10 | 0.709727E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272657E+10 | 0.100703E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295518E+10 | 0.135622E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859052E+10 | 0.601091E+10 | 0.250938E+11 | 0.776220E+10 |
Minimum of Months | 0.550516E+09 | 42437723.04 | 0.411583E+09 | 0.136508E+10 | 0.112509E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571719E+09 | 0.334587E+10 | 0.135622E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334586E+10 | 0.112555E+10 |
February | 0.126421E+10 | 0.852626E+09 | 0.411582E+09 | 0.171257E+10 | 0.995331E+09 |
March | 0.116462E+10 | 0.599840E+09 | 0.564780E+09 | 0.169429E+10 | 0.998457E+09 |
April | 0.959416E+09 | 0.387698E+09 | 0.571718E+09 | 0.178869E+10 | 0.550013E+09 |
May | 0.664339E+09 | 0.109756E+09 | 0.554583E+09 | 0.136508E+10 | 0.391324E+09 |
June | 0.550516E+09 | 42437672.12 | 0.508078E+09 | 0.149735E+10 | 0.143547E+09 |
July | 0.581282E+09 | 60138459.77 | 0.521144E+09 | 0.150954E+10 | 0.112509E+09 |
August | 0.706811E+09 | 0.195328E+09 | 0.511483E+09 | 0.174106E+10 | 0.152307E+09 |
September | 0.985595E+09 | 0.420479E+09 | 0.565116E+09 | 0.205923E+10 | 0.220185E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269838E+10 | 0.709726E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272657E+10 | 0.100703E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295518E+10 | 0.135622E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859051E+10 | 0.601091E+10 | 0.250938E+11 | 0.776220E+10 |
Minimum of Months | 0.550516E+09 | 42437672.12 | 0.411582E+09 | 0.136508E+10 | 0.112509E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571718E+09 | 0.334586E+10 | 0.135622E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334587E+10 | 0.112555E+10 |
February | 0.126421E+10 | 0.852627E+09 | 0.411583E+09 | 0.171257E+10 | 0.995331E+09 |
March | 0.116462E+10 | 0.599841E+09 | 0.564780E+09 | 0.169429E+10 | 0.998457E+09 |
April | 0.959417E+09 | 0.387698E+09 | 0.571719E+09 | 0.178869E+10 | 0.550013E+09 |
May | 0.664339E+09 | 0.109757E+09 | 0.554583E+09 | 0.136508E+10 | 0.391324E+09 |
June | 0.550516E+09 | 42437723.04 | 0.508079E+09 | 0.149735E+10 | 0.143547E+09 |
July | 0.581283E+09 | 60138531.93 | 0.521144E+09 | 0.150954E+10 | 0.112509E+09 |
August | 0.706812E+09 | 0.195328E+09 | 0.511484E+09 | 0.174106E+10 | 0.152307E+09 |
September | 0.985596E+09 | 0.420480E+09 | 0.565116E+09 | 0.205923E+10 | 0.220185E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269838E+10 | 0.709727E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272657E+10 | 0.100703E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295518E+10 | 0.135622E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859052E+10 | 0.601091E+10 | 0.250938E+11 | 0.776220E+10 |
Minimum of Months | 0.550516E+09 | 42437723.04 | 0.411583E+09 | 0.136508E+10 | 0.112509E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571719E+09 | 0.334587E+10 | 0.135622E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334586E+10 | 0.112555E+10 |
February | 0.126421E+10 | 0.852626E+09 | 0.411582E+09 | 0.171257E+10 | 0.995331E+09 |
March | 0.116462E+10 | 0.599840E+09 | 0.564780E+09 | 0.169429E+10 | 0.998457E+09 |
April | 0.959416E+09 | 0.387698E+09 | 0.571718E+09 | 0.178869E+10 | 0.550013E+09 |
May | 0.664339E+09 | 0.109756E+09 | 0.554583E+09 | 0.136508E+10 | 0.391324E+09 |
June | 0.550516E+09 | 42437672.12 | 0.508078E+09 | 0.149735E+10 | 0.143547E+09 |
July | 0.581282E+09 | 60138459.77 | 0.521144E+09 | 0.150954E+10 | 0.112509E+09 |
August | 0.706811E+09 | 0.195328E+09 | 0.511483E+09 | 0.174106E+10 | 0.152307E+09 |
September | 0.985595E+09 | 0.420479E+09 | 0.565116E+09 | 0.205923E+10 | 0.220185E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269838E+10 | 0.709726E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272657E+10 | 0.100703E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295518E+10 | 0.135622E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859051E+10 | 0.601091E+10 | 0.250938E+11 | 0.776220E+10 |
Minimum of Months | 0.550516E+09 | 42437672.12 | 0.411582E+09 | 0.136508E+10 | 0.112509E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571718E+09 | 0.334586E+10 | 0.135622E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221356E+10 | 0.176791E+10 | 0.445652E+09 | 0.334573E+10 | 0.112551E+10 |
February | 0.126416E+10 | 0.852593E+09 | 0.411566E+09 | 0.171250E+10 | 0.995291E+09 |
March | 0.116457E+10 | 0.599817E+09 | 0.564758E+09 | 0.169423E+10 | 0.998417E+09 |
April | 0.959378E+09 | 0.387682E+09 | 0.571696E+09 | 0.178862E+10 | 0.549991E+09 |
May | 0.664313E+09 | 0.109752E+09 | 0.554561E+09 | 0.136502E+10 | 0.391309E+09 |
June | 0.550494E+09 | 42436012.61 | 0.508058E+09 | 0.149729E+10 | 0.143541E+09 |
July | 0.581259E+09 | 60136108.09 | 0.521123E+09 | 0.150948E+10 | 0.112504E+09 |
August | 0.706783E+09 | 0.195320E+09 | 0.511463E+09 | 0.174099E+10 | 0.152301E+09 |
September | 0.985556E+09 | 0.420463E+09 | 0.565093E+09 | 0.205914E+10 | 0.220176E+09 |
October | 0.162273E+10 | 0.112317E+10 | 0.499557E+09 | 0.269827E+10 | 0.709698E+09 |
November | 0.183009E+10 | 0.140175E+10 | 0.428334E+09 | 0.272647E+10 | 0.100699E+10 |
December | 0.205795E+10 | 0.162915E+10 | 0.428807E+09 | 0.295506E+10 | 0.135616E+10 |
Annual Sum or Average | 0.146008E+11 | 0.859018E+10 | 0.601067E+10 | 0.250928E+11 | 0.776189E+10 |
Minimum of Months | 0.550494E+09 | 42436012.61 | 0.411566E+09 | 0.136502E+10 | 0.112504E+09 |
Maximum of Months | 0.221356E+10 | 0.176791E+10 | 0.571696E+09 | 0.334573E+10 | 0.135616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100906E+10 | 0.627146E+09 | 0.381912E+09 | 0.140967E+10 | 0.142397E+10 |
February | 0.738329E+09 | 0.356937E+09 | 0.381392E+09 | 0.815378E+09 | 0.131065E+10 |
March | 0.108272E+10 | 0.516149E+09 | 0.566569E+09 | 0.138771E+10 | 0.126961E+10 |
April | 0.160892E+10 | 0.917776E+09 | 0.691142E+09 | 0.264687E+10 | 0.746195E+09 |
May | 0.166682E+10 | 0.934586E+09 | 0.732231E+09 | 0.296923E+10 | 0.510887E+09 |
June | 0.171483E+10 | 0.100860E+10 | 0.706234E+09 | 0.345035E+10 | 0.225731E+09 |
July | 0.128970E+10 | 0.602026E+09 | 0.687671E+09 | 0.264585E+10 | 0.189982E+09 |
August | 0.122984E+10 | 0.617651E+09 | 0.612190E+09 | 0.248036E+10 | 0.272966E+09 |
September | 0.103743E+10 | 0.435885E+09 | 0.601543E+09 | 0.203901E+10 | 0.293638E+09 |
October | 0.109689E+10 | 0.627199E+09 | 0.469690E+09 | 0.173038E+10 | 0.919860E+09 |
November | 0.977673E+09 | 0.590291E+09 | 0.387383E+09 | 0.131609E+10 | 0.133995E+10 |
December | 0.814229E+09 | 0.463597E+09 | 0.350632E+09 | 0.974738E+09 | 0.183670E+10 |
Annual Sum or Average | 0.142664E+11 | 0.769784E+10 | 0.656859E+10 | 0.238656E+11 | 0.103401E+11 |
Minimum of Months | 0.738329E+09 | 0.356937E+09 | 0.350632E+09 | 0.815378E+09 | 0.189982E+09 |
Maximum of Months | 0.171483E+10 | 0.100860E+10 | 0.732231E+09 | 0.345035E+10 | 0.183670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100906E+10 | 0.627146E+09 | 0.381912E+09 | 0.140967E+10 | 0.142397E+10 |
February | 0.738329E+09 | 0.356937E+09 | 0.381392E+09 | 0.815378E+09 | 0.131065E+10 |
March | 0.108272E+10 | 0.516149E+09 | 0.566569E+09 | 0.138771E+10 | 0.126961E+10 |
April | 0.160892E+10 | 0.917776E+09 | 0.691142E+09 | 0.264687E+10 | 0.746195E+09 |
May | 0.166682E+10 | 0.934586E+09 | 0.732231E+09 | 0.296923E+10 | 0.510887E+09 |
June | 0.171483E+10 | 0.100860E+10 | 0.706234E+09 | 0.345035E+10 | 0.225731E+09 |
July | 0.128970E+10 | 0.602026E+09 | 0.687671E+09 | 0.264585E+10 | 0.189982E+09 |
August | 0.122984E+10 | 0.617651E+09 | 0.612190E+09 | 0.248036E+10 | 0.272966E+09 |
September | 0.103743E+10 | 0.435885E+09 | 0.601543E+09 | 0.203901E+10 | 0.293638E+09 |
October | 0.109689E+10 | 0.627199E+09 | 0.469690E+09 | 0.173038E+10 | 0.919860E+09 |
November | 0.977673E+09 | 0.590291E+09 | 0.387383E+09 | 0.131609E+10 | 0.133995E+10 |
December | 0.814229E+09 | 0.463597E+09 | 0.350632E+09 | 0.974738E+09 | 0.183670E+10 |
Annual Sum or Average | 0.142664E+11 | 0.769784E+10 | 0.656859E+10 | 0.238656E+11 | 0.103401E+11 |
Minimum of Months | 0.738329E+09 | 0.356937E+09 | 0.350632E+09 | 0.815378E+09 | 0.189982E+09 |
Maximum of Months | 0.171483E+10 | 0.100860E+10 | 0.732231E+09 | 0.345035E+10 | 0.183670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100904E+10 | 0.627134E+09 | 0.381906E+09 | 0.140964E+10 | 0.142395E+10 |
February | 0.738315E+09 | 0.356930E+09 | 0.381385E+09 | 0.815363E+09 | 0.131063E+10 |
March | 0.108270E+10 | 0.516140E+09 | 0.566559E+09 | 0.138769E+10 | 0.126958E+10 |
April | 0.160889E+10 | 0.917759E+09 | 0.691130E+09 | 0.264683E+10 | 0.746181E+09 |
May | 0.166679E+10 | 0.934569E+09 | 0.732217E+09 | 0.296918E+10 | 0.510878E+09 |
June | 0.171480E+10 | 0.100858E+10 | 0.706221E+09 | 0.345028E+10 | 0.225727E+09 |
July | 0.128967E+10 | 0.602015E+09 | 0.687658E+09 | 0.264580E+10 | 0.189978E+09 |
August | 0.122982E+10 | 0.617640E+09 | 0.612179E+09 | 0.248032E+10 | 0.272961E+09 |
September | 0.103741E+10 | 0.435877E+09 | 0.601532E+09 | 0.203897E+10 | 0.293633E+09 |
October | 0.109687E+10 | 0.627187E+09 | 0.469682E+09 | 0.173035E+10 | 0.919843E+09 |
November | 0.977655E+09 | 0.590280E+09 | 0.387376E+09 | 0.131606E+10 | 0.133993E+10 |
December | 0.814214E+09 | 0.463589E+09 | 0.350626E+09 | 0.974720E+09 | 0.183666E+10 |
Annual Sum or Average | 0.142662E+11 | 0.769770E+10 | 0.656847E+10 | 0.238652E+11 | 0.103399E+11 |
Minimum of Months | 0.738315E+09 | 0.356930E+09 | 0.350626E+09 | 0.815363E+09 | 0.189978E+09 |
Maximum of Months | 0.171480E+10 | 0.100858E+10 | 0.732217E+09 | 0.345028E+10 | 0.183666E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.113173E+10 | 0.527247E+10 |
February | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.701871E+09 | 0.475386E+10 |
March | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.193735E+10 | 0.465937E+10 |
April | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.398933E+10 | 0.246551E+10 |
May | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.562234E+10 | 0.172474E+10 |
June | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.842120E+10 | 0.692673E+09 |
July | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.742669E+10 | 0.544075E+09 |
August | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.615750E+10 | 0.679036E+09 |
September | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.496318E+10 | 0.102536E+10 |
October | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.251429E+10 | 0.334849E+10 |
November | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.108503E+10 | 0.472633E+10 |
December | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.696401E+09 | 0.642297E+10 |
Annual Sum or Average | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.446469E+11 | 0.363149E+11 |
Minimum of Months | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.696401E+09 | 0.544075E+09 |
Maximum of Months | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.842120E+10 | 0.642297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.366924E+10 | 0.337788E+10 |
February | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.288229E+10 | 0.308597E+10 |
March | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.458748E+10 | 0.299453E+10 |
April | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.804141E+10 | 0.162303E+10 |
May | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.920557E+10 | 0.119090E+10 |
June | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.106746E+11 | 0.465909E+09 |
July | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.940895E+10 | 0.368303E+09 |
August | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.886913E+10 | 0.463413E+09 |
September | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.676665E+10 | 0.672414E+09 |
October | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.562980E+10 | 0.215452E+10 |
November | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.340003E+10 | 0.304981E+10 |
December | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.284212E+10 | 0.409539E+10 |
Annual Sum or Average | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.759773E+11 | 0.235421E+11 |
Minimum of Months | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.284212E+10 | 0.368303E+09 |
Maximum of Months | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.106746E+11 | 0.409539E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.165996E+11 | 0.553605E+10 |
February | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.850495E+10 | 0.479683E+10 |
March | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.844179E+10 | 0.480947E+10 |
April | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.895732E+10 | 0.266870E+10 |
May | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.687563E+10 | 0.190600E+10 |
June | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.759260E+10 | 0.711745E+09 |
July | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.764589E+10 | 0.549325E+09 |
August | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.881622E+10 | 0.704508E+09 |
September | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.102690E+11 | 0.108400E+10 |
October | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.133978E+11 | 0.346483E+10 |
November | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.135451E+11 | 0.487925E+10 |
December | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.147271E+11 | 0.655626E+10 |
Annual Sum or Average | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.125373E+12 | 0.376670E+11 |
Minimum of Months | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.687563E+10 | 0.549325E+09 |
Maximum of Months | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.165996E+11 | 0.655626E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.432538E+10 | 0.383256E+10 |
February | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.253619E+10 | 0.335173E+10 |
March | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.430530E+10 | 0.329090E+10 |
April | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.807199E+10 | 0.193855E+10 |
May | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.893857E+10 | 0.143327E+10 |
June | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.104392E+11 | 0.607126E+09 |
July | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.810340E+10 | 0.464458E+09 |
August | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.768440E+10 | 0.576193E+09 |
September | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.617589E+10 | 0.781401E+09 |
October | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.528531E+10 | 0.243195E+10 |
November | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.406791E+10 | 0.342387E+10 |
December | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.310631E+10 | 0.457124E+10 |
Annual Sum or Average | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.730399E+11 | 0.267032E+11 |
Minimum of Months | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.253619E+10 | 0.464458E+09 |
Maximum of Months | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.104392E+11 | 0.457124E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.126530E+10 | 0.483513E+10 |
February | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.804070E+09 | 0.428166E+10 |
March | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.203446E+10 | 0.436448E+10 |
April | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.395812E+10 | 0.242035E+10 |
May | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.556909E+10 | 0.172859E+10 |
June | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.832161E+10 | 0.715079E+09 |
July | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.730867E+10 | 0.572771E+09 |
August | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.606745E+10 | 0.699408E+09 |
September | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.489653E+10 | 0.104148E+10 |
October | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.254945E+10 | 0.316386E+10 |
November | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.119580E+10 | 0.432503E+10 |
December | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.842783E+09 | 0.583997E+10 |
Annual Sum or Average | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.448133E+11 | 0.339878E+11 |
Minimum of Months | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.804070E+09 | 0.572771E+09 |
Maximum of Months | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.832161E+10 | 0.583997E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.378142E+10 | 0.313652E+10 |
February | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.296482E+10 | 0.281312E+10 |
March | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.466043E+10 | 0.283890E+10 |
April | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.802546E+10 | 0.160635E+10 |
May | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.917337E+10 | 0.119200E+10 |
June | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.106164E+11 | 0.478763E+09 |
July | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.934324E+10 | 0.385403E+09 |
August | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.882089E+10 | 0.474177E+09 |
September | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.673310E+10 | 0.682930E+09 |
October | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.565718E+10 | 0.206161E+10 |
November | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.349317E+10 | 0.282336E+10 |
December | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.299964E+10 | 0.373765E+10 |
Annual Sum or Average | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.762691E+11 | 0.222308E+11 |
Minimum of Months | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.296482E+10 | 0.385403E+09 |
Maximum of Months | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.106164E+11 | 0.373765E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.167080E+11 | 0.520164E+10 |
February | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.860024E+10 | 0.440610E+10 |
March | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.850521E+10 | 0.456020E+10 |
April | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.891009E+10 | 0.262518E+10 |
May | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.681775E+10 | 0.189942E+10 |
June | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.749251E+10 | 0.730402E+09 |
July | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.752745E+10 | 0.575245E+09 |
August | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.872178E+10 | 0.721679E+09 |
September | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.101933E+11 | 0.110203E+10 |
October | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.134038E+11 | 0.332550E+10 |
November | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.136358E+11 | 0.457786E+10 |
December | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.148786E+11 | 0.609650E+10 |
Annual Sum or Average | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.125394E+12 | 0.358218E+11 |
Minimum of Months | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.681775E+10 | 0.575245E+09 |
Maximum of Months | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.167080E+11 | 0.609650E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.438008E+10 | 0.358260E+10 |
February | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.257981E+10 | 0.308640E+10 |
March | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.433924E+10 | 0.312430E+10 |
April | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.803355E+10 | 0.190583E+10 |
May | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.888786E+10 | 0.142659E+10 |
June | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.103672E+11 | 0.617032E+09 |
July | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.802998E+10 | 0.478668E+09 |
August | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.762532E+10 | 0.585665E+09 |
September | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.612836E+10 | 0.791246E+09 |
October | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.528540E+10 | 0.232791E+10 |
November | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.410811E+10 | 0.320304E+10 |
December | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.317797E+10 | 0.423997E+10 |
Annual Sum or Average | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.729429E+11 | 0.253693E+11 |
Minimum of Months | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.257981E+10 | 0.478668E+09 |
Maximum of Months | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.103672E+11 | 0.423997E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 344.39 | 2214.57 | 501.86 | 0.00 | 501.86 | 0.00 | 0.00 |
February | 235.74 | 2231.28 | 571.86 | 0.00 | 571.86 | 0.00 | 0.00 |
March | 662.67 | 1922.21 | 760.00 | 0.00 | 760.00 | 0.00 | 0.00 |
April | 1484.06 | 1010.34 | 925.95 | 9.61 | 916.34 | 0.00 | 0.00 |
May | 2069.65 | 663.45 | 1083.92 | 86.79 | 997.13 | 0.00 | 0.00 |
June | 3217.13 | 262.70 | 1259.59 | 228.85 | 1030.73 | 0.00 | 0.00 |
July | 2735.56 | 204.53 | 1074.19 | 111.91 | 962.28 | 0.00 | 0.00 |
August | 2235.37 | 277.90 | 867.06 | 21.54 | 845.52 | 0.00 | 0.00 |
September | 1889.66 | 409.54 | 818.06 | 0.22 | 817.84 | 0.00 | 0.00 |
October | 888.75 | 1367.77 | 632.92 | 0.00 | 632.92 | 0.00 | 0.00 |
November | 353.11 | 2068.44 | 527.34 | 0.00 | 527.34 | 0.00 | 0.00 |
December | 173.13 | 2770.98 | 468.79 | 0.00 | 468.79 | 0.00 | 0.00 |
Annual Sum or Average | 1362.51 | 1279.64 | 791.76 | 38.32 | 753.43 | 0.00 | 0.00 |
Minimum of Months | 173.13 | 204.53 | 468.79 | 0.00 | 468.79 | 0.00 | 0.00 |
Maximum of Months | 3217.13 | 2770.98 | 1259.59 | 228.85 | 1030.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1356.78 | 1352.58 | 1080.84 | 678.04 | 402.80 | 0.00 | 0.00 |
February | 1189.23 | 1367.24 | 1065.38 | 609.44 | 455.93 | 0.00 | 0.00 |
March | 1721.74 | 1166.32 | 1333.27 | 685.84 | 647.43 | 0.00 | 0.00 |
April | 3131.76 | 616.57 | 1903.17 | 1134.31 | 768.86 | 0.00 | 0.00 |
May | 3465.75 | 443.62 | 1972.37 | 1169.20 | 803.17 | 0.00 | 0.00 |
June | 4149.69 | 167.07 | 2055.85 | 1277.47 | 778.37 | 0.00 | 0.00 |
July | 3542.80 | 125.43 | 1736.29 | 979.02 | 757.27 | 0.00 | 0.00 |
August | 3334.18 | 161.68 | 1647.89 | 940.45 | 707.44 | 0.00 | 0.00 |
September | 2633.55 | 255.55 | 1352.21 | 651.79 | 700.42 | 0.00 | 0.00 |
October | 2115.10 | 834.48 | 1358.21 | 826.60 | 531.61 | 0.00 | 0.00 |
November | 1306.48 | 1255.94 | 1044.39 | 626.96 | 417.43 | 0.00 | 0.00 |
December | 1034.59 | 1648.77 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Annual Sum or Average | 2420.94 | 780.43 | 1460.31 | 847.28 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 1034.59 | 125.43 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Maximum of Months | 4149.69 | 1648.77 | 2055.85 | 1277.47 | 803.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6245.96 | 2101.15 | 4132.38 | 3300.42 | 831.96 | 0.00 | 0.00 |
February | 3539.52 | 2057.13 | 2612.85 | 1762.19 | 850.65 | 0.00 | 0.00 |
March | 3162.86 | 1863.89 | 2174.08 | 1119.77 | 1054.32 | 0.00 | 0.00 |
April | 3450.38 | 1060.97 | 1850.71 | 747.87 | 1102.84 | 0.00 | 0.00 |
May | 2548.29 | 730.51 | 1240.17 | 204.89 | 1035.28 | 0.00 | 0.00 |
June | 2888.38 | 276.90 | 1061.94 | 81.86 | 980.08 | 0.00 | 0.00 |
July | 2817.96 | 210.03 | 1085.12 | 112.26 | 972.86 | 0.00 | 0.00 |
August | 3250.17 | 284.32 | 1319.45 | 364.63 | 954.82 | 0.00 | 0.00 |
September | 3972.24 | 424.74 | 1901.21 | 811.10 | 1090.11 | 0.00 | 0.00 |
October | 5037.26 | 1324.90 | 3029.38 | 2096.78 | 932.60 | 0.00 | 0.00 |
November | 5259.55 | 1942.55 | 3530.37 | 2704.08 | 826.29 | 0.00 | 0.00 |
December | 5516.64 | 2531.75 | 3841.88 | 3041.37 | 800.52 | 0.00 | 0.00 |
Annual Sum or Average | 3978.57 | 1230.68 | 2315.02 | 1362.01 | 953.02 | 0.00 | 0.00 |
Minimum of Months | 2548.29 | 210.03 | 1061.94 | 81.86 | 800.52 | 0.00 | 0.00 |
Maximum of Months | 6245.96 | 2531.75 | 4132.38 | 3300.42 | 1102.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1578.92 | 1594.94 | 1130.21 | 702.44 | 427.77 | 0.00 | 0.00 |
February | 1011.13 | 1625.30 | 915.58 | 442.63 | 472.95 | 0.00 | 0.00 |
March | 1554.33 | 1422.04 | 1212.72 | 578.12 | 634.59 | 0.00 | 0.00 |
April | 3063.49 | 863.65 | 1862.16 | 1062.23 | 799.93 | 0.00 | 0.00 |
May | 3325.73 | 572.23 | 1866.94 | 1046.80 | 820.15 | 0.00 | 0.00 |
June | 3993.43 | 261.26 | 1984.75 | 1167.35 | 817.40 | 0.00 | 0.00 |
July | 2963.52 | 212.79 | 1444.54 | 674.31 | 770.24 | 0.00 | 0.00 |
August | 2778.17 | 305.74 | 1377.50 | 691.81 | 685.69 | 0.00 | 0.00 |
September | 2359.95 | 339.86 | 1200.72 | 504.49 | 696.23 | 0.00 | 0.00 |
October | 1938.14 | 1030.30 | 1228.59 | 702.50 | 526.08 | 0.00 | 0.00 |
November | 1523.24 | 1550.86 | 1131.56 | 683.20 | 448.36 | 0.00 | 0.00 |
December | 1091.77 | 2057.22 | 911.99 | 519.26 | 392.73 | 0.00 | 0.00 |
Annual Sum or Average | 2270.31 | 983.64 | 1357.15 | 732.29 | 624.86 | 0.00 | 0.00 |
Minimum of Months | 1011.13 | 212.79 | 911.99 | 442.63 | 392.73 | 0.00 | 0.00 |
Maximum of Months | 3993.43 | 2057.22 | 1984.75 | 1167.35 | 820.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 422.54 | 1968.52 | 501.86 | 0.00 | 501.86 | 0.00 | 0.00 |
February | 290.13 | 1965.05 | 571.86 | 0.00 | 571.86 | 0.00 | 0.00 |
March | 723.32 | 1739.61 | 760.00 | 0.00 | 760.00 | 0.00 | 0.00 |
April | 1539.09 | 951.20 | 925.95 | 9.61 | 916.34 | 0.00 | 0.00 |
May | 2099.14 | 643.94 | 1083.92 | 86.79 | 997.13 | 0.00 | 0.00 |
June | 3248.92 | 267.24 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
July | 2772.81 | 203.13 | 1074.18 | 111.91 | 962.28 | 0.00 | 0.00 |
August | 2298.95 | 253.52 | 867.06 | 21.54 | 845.52 | 0.00 | 0.00 |
September | 1914.81 | 395.59 | 818.06 | 0.22 | 817.84 | 0.00 | 0.00 |
October | 938.73 | 1250.18 | 632.91 | 0.00 | 632.91 | 0.00 | 0.00 |
November | 418.61 | 1823.43 | 527.33 | 0.00 | 527.33 | 0.00 | 0.00 |
December | 260.01 | 2398.06 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Annual Sum or Average | 1415.74 | 1151.54 | 791.75 | 38.32 | 753.43 | 0.00 | 0.00 |
Minimum of Months | 260.01 | 203.13 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Maximum of Months | 3248.92 | 2398.06 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1369.94 | 1261.16 | 1080.83 | 678.04 | 402.80 | 0.00 | 0.00 |
February | 1191.42 | 1275.62 | 1065.37 | 609.44 | 455.93 | 0.00 | 0.00 |
March | 1712.77 | 1118.03 | 1333.26 | 685.84 | 647.42 | 0.00 | 0.00 |
April | 3102.39 | 626.17 | 1903.16 | 1134.31 | 768.85 | 0.00 | 0.00 |
May | 3436.97 | 444.63 | 1972.36 | 1169.20 | 803.16 | 0.00 | 0.00 |
June | 4118.28 | 179.75 | 2055.84 | 1277.47 | 778.37 | 0.00 | 0.00 |
July | 3512.90 | 137.51 | 1736.29 | 979.02 | 757.26 | 0.00 | 0.00 |
August | 3311.36 | 173.02 | 1647.89 | 940.45 | 707.44 | 0.00 | 0.00 |
September | 2610.59 | 259.42 | 1352.20 | 651.79 | 700.42 | 0.00 | 0.00 |
October | 2101.93 | 804.41 | 1358.21 | 826.60 | 531.61 | 0.00 | 0.00 |
November | 1311.74 | 1176.62 | 1044.39 | 626.96 | 417.43 | 0.00 | 0.00 |
December | 1061.12 | 1529.04 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Annual Sum or Average | 2409.22 | 746.51 | 1460.30 | 847.28 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 1061.12 | 137.51 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Maximum of Months | 4118.28 | 1529.04 | 2055.84 | 1277.47 | 803.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6197.57 | 2066.93 | 4132.36 | 3300.40 | 831.96 | 0.00 | 0.00 |
February | 3515.60 | 1982.82 | 2612.84 | 1762.19 | 850.65 | 0.00 | 0.00 |
March | 3151.80 | 1795.65 | 2174.07 | 1119.76 | 1054.31 | 0.00 | 0.00 |
April | 3455.76 | 1029.59 | 1850.70 | 747.87 | 1102.84 | 0.00 | 0.00 |
May | 2567.07 | 711.62 | 1240.16 | 204.89 | 1035.28 | 0.00 | 0.00 |
June | 2929.24 | 274.59 | 1061.94 | 81.86 | 980.08 | 0.00 | 0.00 |
July | 2854.65 | 205.09 | 1085.12 | 112.26 | 972.85 | 0.00 | 0.00 |
August | 3291.60 | 263.03 | 1319.45 | 364.63 | 954.82 | 0.00 | 0.00 |
September | 3961.81 | 418.21 | 1901.20 | 811.10 | 1090.10 | 0.00 | 0.00 |
October | 5002.16 | 1293.62 | 3029.37 | 2096.77 | 932.59 | 0.00 | 0.00 |
November | 5225.72 | 1882.43 | 3530.36 | 2704.07 | 826.29 | 0.00 | 0.00 |
December | 5498.47 | 2447.83 | 3841.87 | 3041.36 | 800.51 | 0.00 | 0.00 |
Annual Sum or Average | 3975.55 | 1194.41 | 2315.01 | 1362.00 | 953.01 | 0.00 | 0.00 |
Minimum of Months | 2567.07 | 205.09 | 1061.94 | 81.86 | 800.51 | 0.00 | 0.00 |
Maximum of Months | 6197.57 | 2447.83 | 4132.36 | 3300.40 | 1102.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1614.91 | 1430.92 | 1130.21 | 702.44 | 427.76 | 0.00 | 0.00 |
February | 1048.36 | 1385.47 | 915.58 | 442.63 | 472.95 | 0.00 | 0.00 |
March | 1607.41 | 1228.68 | 1212.71 | 578.12 | 634.59 | 0.00 | 0.00 |
April | 3114.20 | 747.90 | 1862.16 | 1062.23 | 799.93 | 0.00 | 0.00 |
May | 3337.28 | 535.12 | 1866.94 | 1046.79 | 820.14 | 0.00 | 0.00 |
June | 4027.48 | 234.23 | 1984.74 | 1167.35 | 817.39 | 0.00 | 0.00 |
July | 3025.46 | 173.41 | 1444.54 | 674.31 | 770.23 | 0.00 | 0.00 |
August | 2869.03 | 215.13 | 1377.50 | 691.81 | 685.69 | 0.00 | 0.00 |
September | 2382.67 | 301.47 | 1200.71 | 504.49 | 696.22 | 0.00 | 0.00 |
October | 1973.31 | 907.99 | 1228.58 | 702.50 | 526.08 | 0.00 | 0.00 |
November | 1569.41 | 1320.94 | 1131.55 | 683.20 | 448.35 | 0.00 | 0.00 |
December | 1159.76 | 1706.71 | 911.99 | 519.26 | 392.73 | 0.00 | 0.00 |
Annual Sum or Average | 2316.08 | 846.75 | 1357.14 | 732.28 | 624.86 | 0.00 | 0.00 |
Minimum of Months | 1048.36 | 173.41 | 911.99 | 442.63 | 392.73 | 0.00 | 0.00 |
Maximum of Months | 4027.48 | 1706.71 | 1984.74 | 1167.35 | 820.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 472.41 | 1805.23 | 501.86 | 0.00 | 501.86 | 0.00 | 0.00 |
February | 332.37 | 1769.87 | 571.86 | 0.00 | 571.86 | 0.00 | 0.00 |
March | 759.58 | 1629.51 | 760.00 | 0.00 | 760.00 | 0.00 | 0.00 |
April | 1527.05 | 933.78 | 925.95 | 9.61 | 916.34 | 0.00 | 0.00 |
May | 2079.26 | 645.38 | 1083.92 | 86.79 | 997.13 | 0.00 | 0.00 |
June | 3210.50 | 275.88 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
July | 2728.74 | 213.85 | 1074.18 | 111.91 | 962.28 | 0.00 | 0.00 |
August | 2265.33 | 261.13 | 867.06 | 21.54 | 845.52 | 0.00 | 0.00 |
September | 1889.09 | 401.81 | 818.06 | 0.22 | 817.84 | 0.00 | 0.00 |
October | 951.86 | 1181.25 | 632.91 | 0.00 | 632.91 | 0.00 | 0.00 |
November | 461.34 | 1668.61 | 527.33 | 0.00 | 527.33 | 0.00 | 0.00 |
December | 314.66 | 2180.40 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Annual Sum or Average | 1421.02 | 1077.75 | 791.75 | 38.32 | 753.43 | 0.00 | 0.00 |
Minimum of Months | 314.66 | 213.85 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Maximum of Months | 3210.50 | 2180.40 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1411.82 | 1171.04 | 1080.83 | 678.04 | 402.80 | 0.00 | 0.00 |
February | 1225.54 | 1162.83 | 1065.37 | 609.44 | 455.93 | 0.00 | 0.00 |
March | 1740.01 | 1059.93 | 1333.26 | 685.84 | 647.42 | 0.00 | 0.00 |
April | 3096.24 | 619.73 | 1903.16 | 1134.31 | 768.85 | 0.00 | 0.00 |
May | 3424.94 | 445.04 | 1972.36 | 1169.20 | 803.16 | 0.00 | 0.00 |
June | 4095.82 | 184.71 | 2055.84 | 1277.47 | 778.37 | 0.00 | 0.00 |
July | 3488.36 | 143.89 | 1736.29 | 979.02 | 757.26 | 0.00 | 0.00 |
August | 3293.34 | 177.04 | 1647.89 | 940.45 | 707.44 | 0.00 | 0.00 |
September | 2597.65 | 263.48 | 1352.20 | 651.79 | 700.42 | 0.00 | 0.00 |
October | 2112.15 | 769.72 | 1358.21 | 826.60 | 531.61 | 0.00 | 0.00 |
November | 1347.68 | 1089.26 | 1044.39 | 626.96 | 417.43 | 0.00 | 0.00 |
December | 1119.94 | 1395.48 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Annual Sum or Average | 2418.48 | 704.93 | 1460.30 | 847.28 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 1119.94 | 143.89 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Maximum of Months | 4095.82 | 1395.48 | 2055.84 | 1277.47 | 803.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6238.04 | 1942.07 | 4132.36 | 3300.40 | 831.96 | 0.00 | 0.00 |
February | 3554.99 | 1821.30 | 2612.84 | 1762.19 | 850.65 | 0.00 | 0.00 |
March | 3175.48 | 1702.58 | 2174.07 | 1119.76 | 1054.31 | 0.00 | 0.00 |
April | 3437.54 | 1012.80 | 1850.70 | 747.87 | 1102.84 | 0.00 | 0.00 |
May | 2545.46 | 709.16 | 1240.16 | 204.89 | 1035.28 | 0.00 | 0.00 |
June | 2890.63 | 281.79 | 1061.94 | 81.86 | 980.08 | 0.00 | 0.00 |
July | 2810.43 | 214.77 | 1085.12 | 112.26 | 972.85 | 0.00 | 0.00 |
August | 3256.34 | 269.44 | 1319.45 | 364.63 | 954.82 | 0.00 | 0.00 |
September | 3932.60 | 425.16 | 1901.20 | 811.10 | 1090.10 | 0.00 | 0.00 |
October | 5004.42 | 1241.60 | 3029.37 | 2096.77 | 932.59 | 0.00 | 0.00 |
November | 5260.71 | 1766.15 | 3530.36 | 2704.07 | 826.29 | 0.00 | 0.00 |
December | 5555.03 | 2276.17 | 3841.87 | 3041.36 | 800.51 | 0.00 | 0.00 |
Annual Sum or Average | 3976.23 | 1135.90 | 2315.01 | 1362.00 | 953.01 | 0.00 | 0.00 |
Minimum of Months | 2545.46 | 214.77 | 1061.94 | 81.86 | 800.51 | 0.00 | 0.00 |
Maximum of Months | 6238.04 | 2276.17 | 4132.36 | 3300.40 | 1102.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1635.34 | 1337.59 | 1130.21 | 702.44 | 427.76 | 0.00 | 0.00 |
February | 1066.39 | 1275.79 | 915.58 | 442.63 | 472.95 | 0.00 | 0.00 |
March | 1620.09 | 1166.48 | 1212.71 | 578.12 | 634.59 | 0.00 | 0.00 |
April | 3099.36 | 735.27 | 1862.16 | 1062.23 | 799.93 | 0.00 | 0.00 |
May | 3318.35 | 532.63 | 1866.94 | 1046.79 | 820.14 | 0.00 | 0.00 |
June | 3999.69 | 238.05 | 1984.74 | 1167.35 | 817.39 | 0.00 | 0.00 |
July | 2998.05 | 178.71 | 1444.54 | 674.31 | 770.23 | 0.00 | 0.00 |
August | 2846.97 | 218.66 | 1377.50 | 691.81 | 685.69 | 0.00 | 0.00 |
September | 2364.34 | 305.26 | 1200.71 | 504.49 | 696.22 | 0.00 | 0.00 |
October | 1973.34 | 869.14 | 1228.58 | 702.50 | 526.08 | 0.00 | 0.00 |
November | 1584.92 | 1235.74 | 1131.55 | 683.20 | 448.35 | 0.00 | 0.00 |
December | 1186.52 | 1583.02 | 911.99 | 519.26 | 392.73 | 0.00 | 0.00 |
Annual Sum or Average | 2313.00 | 804.45 | 1357.14 | 732.28 | 624.86 | 0.00 | 0.00 |
Minimum of Months | 1066.39 | 178.71 | 911.99 | 442.63 | 392.73 | 0.00 | 0.00 |
Maximum of Months | 3999.69 | 1583.02 | 1984.74 | 1167.35 | 820.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.922419E+09 | 0.593149E+10 | 0.134419E+10 | 0.00 | 0.134419E+10 | 0.00 | 0.00 |
February | 0.570306E+09 | 0.539791E+10 | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.00 | 0.00 |
March | 0.177491E+10 | 0.514846E+10 | 0.203559E+10 | 0.00 | 0.203559E+10 | 0.00 | 0.00 |
April | 0.384669E+10 | 0.261881E+10 | 0.240006E+10 | 24906474.26 | 0.237516E+10 | 0.00 | 0.00 |
May | 0.554335E+10 | 0.177699E+10 | 0.290318E+10 | 0.232460E+09 | 0.267072E+10 | 0.00 | 0.00 |
June | 0.833879E+10 | 0.680919E+09 | 0.326485E+10 | 0.593189E+09 | 0.267166E+10 | 0.00 | 0.00 |
July | 0.732693E+10 | 0.547811E+09 | 0.287711E+10 | 0.299737E+09 | 0.257737E+10 | 0.00 | 0.00 |
August | 0.598723E+10 | 0.744316E+09 | 0.232234E+10 | 57692429.13 | 0.226465E+10 | 0.00 | 0.00 |
September | 0.489801E+10 | 0.106153E+10 | 0.212042E+10 | 566048.11 | 0.211985E+10 | 0.00 | 0.00 |
October | 0.238042E+10 | 0.366344E+10 | 0.169520E+10 | 0.00 | 0.169520E+10 | 0.00 | 0.00 |
November | 0.915254E+09 | 0.536139E+10 | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.00 | 0.00 |
December | 0.463718E+09 | 0.742179E+10 | 0.125560E+10 | 0.00 | 0.125560E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.429680E+11 | 0.403549E+11 | 0.249688E+11 | 0.120855E+10 | 0.237603E+11 | 0.00 | 0.00 |
Minimum of Months | 0.463718E+09 | 0.547811E+09 | 0.125560E+10 | 0.00 | 0.125560E+10 | 0.00 | 0.00 |
Maximum of Months | 0.833879E+10 | 0.742179E+10 | 0.326485E+10 | 0.593189E+09 | 0.267166E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.363400E+10 | 0.362275E+10 | 0.289492E+10 | 0.181606E+10 | 0.107885E+10 | 0.00 | 0.00 |
February | 0.287698E+10 | 0.330763E+10 | 0.257736E+10 | 0.147437E+10 | 0.110299E+10 | 0.00 | 0.00 |
March | 0.461150E+10 | 0.312387E+10 | 0.357103E+10 | 0.183696E+10 | 0.173406E+10 | 0.00 | 0.00 |
April | 0.811752E+10 | 0.159816E+10 | 0.493301E+10 | 0.294014E+10 | 0.199287E+10 | 0.00 | 0.00 |
May | 0.928265E+10 | 0.118819E+10 | 0.528279E+10 | 0.313159E+10 | 0.215120E+10 | 0.00 | 0.00 |
June | 0.107560E+11 | 0.433043E+09 | 0.532875E+10 | 0.331121E+10 | 0.201754E+10 | 0.00 | 0.00 |
July | 0.948902E+10 | 0.335949E+09 | 0.465049E+10 | 0.262222E+10 | 0.202827E+10 | 0.00 | 0.00 |
August | 0.893027E+10 | 0.433048E+09 | 0.441372E+10 | 0.251890E+10 | 0.189481E+10 | 0.00 | 0.00 |
September | 0.682617E+10 | 0.662392E+09 | 0.350492E+10 | 0.168944E+10 | 0.181549E+10 | 0.00 | 0.00 |
October | 0.566509E+10 | 0.223506E+10 | 0.363784E+10 | 0.221396E+10 | 0.142388E+10 | 0.00 | 0.00 |
November | 0.338641E+10 | 0.325540E+10 | 0.270706E+10 | 0.162508E+10 | 0.108198E+10 | 0.00 | 0.00 |
December | 0.277104E+10 | 0.441607E+10 | 0.255040E+10 | 0.154001E+10 | 0.101039E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.763467E+11 | 0.246116E+11 | 0.460523E+11 | 0.267199E+11 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 0.277104E+10 | 0.335949E+09 | 0.255040E+10 | 0.147437E+10 | 0.101039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107560E+11 | 0.441607E+10 | 0.532875E+10 | 0.331121E+10 | 0.215120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167292E+11 | 0.562771E+10 | 0.110682E+11 | 0.883983E+10 | 0.222833E+10 | 0.00 | 0.00 |
February | 0.856280E+10 | 0.497662E+10 | 0.632100E+10 | 0.426310E+10 | 0.205790E+10 | 0.00 | 0.00 |
March | 0.847140E+10 | 0.499225E+10 | 0.582306E+10 | 0.299918E+10 | 0.282388E+10 | 0.00 | 0.00 |
April | 0.894338E+10 | 0.275004E+10 | 0.479704E+10 | 0.193847E+10 | 0.285857E+10 | 0.00 | 0.00 |
May | 0.682534E+10 | 0.195661E+10 | 0.332167E+10 | 0.548778E+09 | 0.277289E+10 | 0.00 | 0.00 |
June | 0.748669E+10 | 0.717727E+09 | 0.275256E+10 | 0.212187E+09 | 0.254037E+10 | 0.00 | 0.00 |
July | 0.754762E+10 | 0.562540E+09 | 0.290639E+10 | 0.300690E+09 | 0.260570E+10 | 0.00 | 0.00 |
August | 0.870524E+10 | 0.761528E+09 | 0.353403E+10 | 0.976632E+09 | 0.255740E+10 | 0.00 | 0.00 |
September | 0.102960E+11 | 0.110092E+10 | 0.492794E+10 | 0.210238E+10 | 0.282556E+10 | 0.00 | 0.00 |
October | 0.134918E+11 | 0.354860E+10 | 0.811389E+10 | 0.561602E+10 | 0.249787E+10 | 0.00 | 0.00 |
November | 0.136328E+11 | 0.503510E+10 | 0.915072E+10 | 0.700898E+10 | 0.214174E+10 | 0.00 | 0.00 |
December | 0.147758E+11 | 0.678104E+10 | 0.102901E+11 | 0.814600E+10 | 0.214410E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125468E+12 | 0.388107E+11 | 0.730065E+11 | 0.429523E+11 | 0.300543E+11 | 0.00 | 0.00 |
Minimum of Months | 0.682534E+10 | 0.562540E+09 | 0.275256E+10 | 0.212187E+09 | 0.205790E+10 | 0.00 | 0.00 |
Maximum of Months | 0.167292E+11 | 0.678104E+10 | 0.110682E+11 | 0.883983E+10 | 0.285857E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.422898E+10 | 0.427189E+10 | 0.302716E+10 | 0.188143E+10 | 0.114573E+10 | 0.00 | 0.00 |
February | 0.244612E+10 | 0.393193E+10 | 0.221497E+10 | 0.107080E+10 | 0.114417E+10 | 0.00 | 0.00 |
March | 0.416311E+10 | 0.380880E+10 | 0.324814E+10 | 0.154844E+10 | 0.169970E+10 | 0.00 | 0.00 |
April | 0.794057E+10 | 0.223857E+10 | 0.482673E+10 | 0.275331E+10 | 0.207341E+10 | 0.00 | 0.00 |
May | 0.890764E+10 | 0.153265E+10 | 0.500042E+10 | 0.280374E+10 | 0.219668E+10 | 0.00 | 0.00 |
June | 0.103510E+11 | 0.677188E+09 | 0.514446E+10 | 0.302577E+10 | 0.211869E+10 | 0.00 | 0.00 |
July | 0.793749E+10 | 0.569941E+09 | 0.386907E+10 | 0.180607E+10 | 0.206300E+10 | 0.00 | 0.00 |
August | 0.744105E+10 | 0.818894E+09 | 0.368950E+10 | 0.185294E+10 | 0.183656E+10 | 0.00 | 0.00 |
September | 0.611699E+10 | 0.880909E+09 | 0.311227E+10 | 0.130765E+10 | 0.180462E+10 | 0.00 | 0.00 |
October | 0.519111E+10 | 0.275956E+10 | 0.329065E+10 | 0.188158E+10 | 0.140906E+10 | 0.00 | 0.00 |
November | 0.394824E+10 | 0.401983E+10 | 0.293300E+10 | 0.177086E+10 | 0.116214E+10 | 0.00 | 0.00 |
December | 0.292420E+10 | 0.551006E+10 | 0.244267E+10 | 0.139078E+10 | 0.105189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.715965E+11 | 0.310202E+11 | 0.427990E+11 | 0.230934E+11 | 0.197056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244612E+10 | 0.569941E+09 | 0.221497E+10 | 0.107080E+10 | 0.105189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103510E+11 | 0.551006E+10 | 0.514446E+10 | 0.302577E+10 | 0.219668E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113173E+10 | 0.527247E+10 | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.00 | 0.00 |
February | 0.701871E+09 | 0.475386E+10 | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.00 | 0.00 |
March | 0.193735E+10 | 0.465937E+10 | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.00 | 0.00 |
April | 0.398933E+10 | 0.246551E+10 | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.00 | 0.00 |
May | 0.562234E+10 | 0.172474E+10 | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.00 | 0.00 |
June | 0.842120E+10 | 0.692673E+09 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
July | 0.742669E+10 | 0.544075E+09 | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.00 | 0.00 |
August | 0.615750E+10 | 0.679036E+09 | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.00 | 0.00 |
September | 0.496318E+10 | 0.102536E+10 | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.00 | 0.00 |
October | 0.251429E+10 | 0.334849E+10 | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.00 | 0.00 |
November | 0.108503E+10 | 0.472633E+10 | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.00 | 0.00 |
December | 0.696401E+09 | 0.642297E+10 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.446469E+11 | 0.363149E+11 | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.696401E+09 | 0.544075E+09 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Maximum of Months | 0.842120E+10 | 0.642297E+10 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.366924E+10 | 0.337788E+10 | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.00 | 0.00 |
February | 0.288229E+10 | 0.308597E+10 | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.00 | 0.00 |
March | 0.458748E+10 | 0.299453E+10 | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.00 | 0.00 |
April | 0.804141E+10 | 0.162303E+10 | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.00 | 0.00 |
May | 0.920557E+10 | 0.119090E+10 | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.00 | 0.00 |
June | 0.106746E+11 | 0.465909E+09 | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.00 | 0.00 |
July | 0.940895E+10 | 0.368303E+09 | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.00 | 0.00 |
August | 0.886913E+10 | 0.463413E+09 | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.00 | 0.00 |
September | 0.676665E+10 | 0.672414E+09 | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.00 | 0.00 |
October | 0.562980E+10 | 0.215452E+10 | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.00 | 0.00 |
November | 0.340003E+10 | 0.304981E+10 | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.00 | 0.00 |
December | 0.284212E+10 | 0.409539E+10 | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.759773E+11 | 0.235421E+11 | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 0.284212E+10 | 0.368303E+09 | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106746E+11 | 0.409539E+10 | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165996E+11 | 0.553605E+10 | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.00 | 0.00 |
February | 0.850495E+10 | 0.479683E+10 | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.00 | 0.00 |
March | 0.844179E+10 | 0.480947E+10 | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.00 | 0.00 |
April | 0.895732E+10 | 0.266870E+10 | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.00 | 0.00 |
May | 0.687563E+10 | 0.190600E+10 | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.00 | 0.00 |
June | 0.759260E+10 | 0.711745E+09 | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.00 | 0.00 |
July | 0.764589E+10 | 0.549325E+09 | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.00 | 0.00 |
August | 0.881622E+10 | 0.704508E+09 | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.00 | 0.00 |
September | 0.102690E+11 | 0.108400E+10 | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.00 | 0.00 |
October | 0.133978E+11 | 0.346483E+10 | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.00 | 0.00 |
November | 0.135451E+11 | 0.487925E+10 | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.00 | 0.00 |
December | 0.147271E+11 | 0.655626E+10 | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125373E+12 | 0.376670E+11 | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.687563E+10 | 0.549325E+09 | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.00 | 0.00 |
Maximum of Months | 0.165996E+11 | 0.655626E+10 | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432538E+10 | 0.383256E+10 | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.00 | 0.00 |
February | 0.253619E+10 | 0.335173E+10 | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.00 | 0.00 |
March | 0.430530E+10 | 0.329090E+10 | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.00 | 0.00 |
April | 0.807199E+10 | 0.193855E+10 | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.00 | 0.00 |
May | 0.893857E+10 | 0.143327E+10 | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.00 | 0.00 |
June | 0.104392E+11 | 0.607126E+09 | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.00 | 0.00 |
July | 0.810340E+10 | 0.464458E+09 | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.00 | 0.00 |
August | 0.768440E+10 | 0.576193E+09 | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.00 | 0.00 |
September | 0.617589E+10 | 0.781401E+09 | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.00 | 0.00 |
October | 0.528531E+10 | 0.243195E+10 | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.00 | 0.00 |
November | 0.406791E+10 | 0.342387E+10 | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.00 | 0.00 |
December | 0.310631E+10 | 0.457124E+10 | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.730399E+11 | 0.267032E+11 | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253619E+10 | 0.464458E+09 | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104392E+11 | 0.457124E+10 | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126530E+10 | 0.483513E+10 | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.00 | 0.00 |
February | 0.804070E+09 | 0.428166E+10 | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.00 | 0.00 |
March | 0.203446E+10 | 0.436448E+10 | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.00 | 0.00 |
April | 0.395812E+10 | 0.242035E+10 | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.00 | 0.00 |
May | 0.556909E+10 | 0.172859E+10 | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.00 | 0.00 |
June | 0.832161E+10 | 0.715079E+09 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
July | 0.730867E+10 | 0.572771E+09 | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.00 | 0.00 |
August | 0.606745E+10 | 0.699408E+09 | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.00 | 0.00 |
September | 0.489653E+10 | 0.104148E+10 | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.00 | 0.00 |
October | 0.254945E+10 | 0.316386E+10 | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.00 | 0.00 |
November | 0.119580E+10 | 0.432503E+10 | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.00 | 0.00 |
December | 0.842783E+09 | 0.583997E+10 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.448133E+11 | 0.339878E+11 | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.804070E+09 | 0.572771E+09 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Maximum of Months | 0.832161E+10 | 0.583997E+10 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.378142E+10 | 0.313652E+10 | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.00 | 0.00 |
February | 0.296482E+10 | 0.281312E+10 | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.00 | 0.00 |
March | 0.466043E+10 | 0.283890E+10 | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.00 | 0.00 |
April | 0.802546E+10 | 0.160635E+10 | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.00 | 0.00 |
May | 0.917337E+10 | 0.119200E+10 | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.00 | 0.00 |
June | 0.106164E+11 | 0.478763E+09 | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.00 | 0.00 |
July | 0.934324E+10 | 0.385403E+09 | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.00 | 0.00 |
August | 0.882089E+10 | 0.474177E+09 | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.00 | 0.00 |
September | 0.673310E+10 | 0.682930E+09 | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.00 | 0.00 |
October | 0.565718E+10 | 0.206161E+10 | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.00 | 0.00 |
November | 0.349317E+10 | 0.282336E+10 | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.00 | 0.00 |
December | 0.299964E+10 | 0.373765E+10 | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.762691E+11 | 0.222308E+11 | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 0.296482E+10 | 0.385403E+09 | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106164E+11 | 0.373765E+10 | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167080E+11 | 0.520164E+10 | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.00 | 0.00 |
February | 0.860024E+10 | 0.440610E+10 | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.00 | 0.00 |
March | 0.850521E+10 | 0.456020E+10 | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.00 | 0.00 |
April | 0.891009E+10 | 0.262518E+10 | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.00 | 0.00 |
May | 0.681775E+10 | 0.189942E+10 | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.00 | 0.00 |
June | 0.749251E+10 | 0.730402E+09 | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.00 | 0.00 |
July | 0.752745E+10 | 0.575245E+09 | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.00 | 0.00 |
August | 0.872178E+10 | 0.721679E+09 | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.00 | 0.00 |
September | 0.101933E+11 | 0.110203E+10 | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.00 | 0.00 |
October | 0.134038E+11 | 0.332550E+10 | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.00 | 0.00 |
November | 0.136358E+11 | 0.457786E+10 | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.00 | 0.00 |
December | 0.148786E+11 | 0.609650E+10 | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125394E+12 | 0.358218E+11 | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.681775E+10 | 0.575245E+09 | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.00 | 0.00 |
Maximum of Months | 0.167080E+11 | 0.609650E+10 | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438008E+10 | 0.358260E+10 | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.00 | 0.00 |
February | 0.257981E+10 | 0.308640E+10 | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.00 | 0.00 |
March | 0.433924E+10 | 0.312430E+10 | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.00 | 0.00 |
April | 0.803355E+10 | 0.190583E+10 | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.00 | 0.00 |
May | 0.888786E+10 | 0.142659E+10 | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.00 | 0.00 |
June | 0.103672E+11 | 0.617032E+09 | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.00 | 0.00 |
July | 0.802998E+10 | 0.478668E+09 | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.00 | 0.00 |
August | 0.762532E+10 | 0.585665E+09 | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.00 | 0.00 |
September | 0.612836E+10 | 0.791246E+09 | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.00 | 0.00 |
October | 0.528540E+10 | 0.232791E+10 | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.00 | 0.00 |
November | 0.410811E+10 | 0.320304E+10 | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.00 | 0.00 |
December | 0.317797E+10 | 0.423997E+10 | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.729429E+11 | 0.253693E+11 | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257981E+10 | 0.478668E+09 | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103672E+11 | 0.423997E+10 | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.331043E+11 | -0.320830E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102128E+10 | 58.97 | 0.00 | 0.00 |
February | 0.297897E+11 | -0.288640E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -925685581.5 | 58.97 | 0.00 | 0.00 |
March | 0.333173E+11 | -0.322893E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102804E+10 | 58.98 | 0.00 | 0.00 |
April | 0.279363E+11 | -0.269473E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988949970.8 | 58.98 | 0.00 | 0.00 |
May | 0.271246E+11 | -0.261005E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102412E+10 | 58.97 | 0.00 | 0.00 |
June | 0.246442E+11 | -0.236527E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991560864.5 | 58.97 | 0.00 | 0.00 |
July | 0.224790E+11 | -0.214606E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101843E+10 | 58.96 | 0.00 | 0.00 |
August | 0.248812E+11 | -0.238588E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102240E+10 | 58.97 | 0.00 | 0.00 |
September | 0.241953E+11 | -0.232091E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986197139.8 | 58.97 | 0.00 | 0.00 |
October | 0.273846E+11 | -0.263668E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101777E+10 | 58.96 | 0.00 | 0.00 |
November | 0.294007E+11 | -0.284151E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985603726.6 | 58.97 | 0.00 | 0.00 |
December | 0.313342E+11 | -0.303150E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101916E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.335592E+12 | -0.323562E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120292E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.224790E+11 | -0.322893E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102804E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.333173E+11 | -0.214606E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925685581.5 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9166.72 | 39.08 | 306.50 | 291.50 | 2382.83 | 29.16 | 193.00 | 287.17 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8257.35 | 36.51 | 234.33 | 265.00 | 1310.38 | 23.39 | 146.00 | 223.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1590.94 | 19.58 | 47.50 | 328.83 | 927.17 | 20.91 | 180.00 | 286.83 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:40 | 1238.86 | 19.19 | 19.33 | 333.33 | 777.78 | 20.51 | 129.83 | 302.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:10 | 989.20 | 18.92 | 0.00 | 359.33 | 623.12 | 20.31 | 70.00 | 318.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-06:00 | 824.79 | 18.17 | 0.00 | 363.17 | 534.95 | 19.62 | 18.50 | 312.50 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 950.63 | 18.61 | 0.00 | 363.50 | 574.85 | 20.01 | 78.67 | 296.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 1087.34 | 18.97 | 3.33 | 337.50 | 662.74 | 20.33 | 90.83 | 288.17 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:00 | 1543.34 | 19.93 | 58.00 | 318.83 | 864.62 | 20.88 | 177.33 | 286.33 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3150.25 | 25.23 | 154.67 | 314.67 | 1124.32 | 20.58 | 125.50 | 298.33 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8680.98 | 37.78 | 282.50 | 285.33 | 1589.08 | 24.32 | 149.83 | 263.50 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8492.09 | 39.07 | 289.33 | 280.00 | 2219.15 | 28.88 | 188.17 | 274.33 |
Annual Sum or Average | 4135.50 | 0.51 | 3379.43 | 24.78 | 1395.50 | 3841.00 | 1066.63 | 22.08 | 1547.67 | 3438.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 824.79 | 18.17 | 0.00 | 265.00 | 534.95 | 19.62 | 18.50 | 223.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9166.72 | 39.08 | 306.50 | 363.50 | 2382.83 | 29.16 | 193.00 | 318.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:49 | 2183.39 | 24.58 | 107.50 | 274.67 | 1194.77 | 24.27 | 103.50 | 231.83 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2630.64 | 25.04 | 87.83 | 254.33 | 1459.25 | 24.82 | 100.83 | 190.17 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2206.07 | 23.47 | 100.17 | 316.00 | 1158.67 | 23.56 | 130.67 | 282.33 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3083.22 | 23.60 | 112.33 | 348.17 | 1725.66 | 23.89 | 101.00 | 326.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3501.21 | 24.68 | 134.17 | 380.67 | 1396.04 | 23.54 | 84.83 | 357.33 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3514.26 | 24.13 | 134.83 | 386.50 | 1379.14 | 23.02 | 78.00 | 353.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 3065.31 | 24.12 | 128.17 | 381.33 | 1243.94 | 23.02 | 90.00 | 325.17 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2997.07 | 23.91 | 114.50 | 353.33 | 1655.91 | 24.09 | 109.67 | 310.17 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2374.39 | 23.56 | 105.00 | 318.67 | 1267.12 | 23.75 | 126.33 | 278.83 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2300.61 | 23.23 | 103.33 | 295.00 | 1232.82 | 23.16 | 114.67 | 256.67 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:30 | 1861.25 | 23.16 | 80.33 | 273.67 | 978.90 | 23.03 | 86.33 | 209.83 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:30 | 2172.99 | 25.14 | 106.33 | 260.50 | 1194.23 | 24.72 | 103.00 | 208.67 |
Annual Sum or Average | 4135.50 | 0.50 | 2716.37 | 24.02 | 1314.50 | 3842.83 | 1333.59 | 23.68 | 1228.83 | 3331.17 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1861.25 | 23.16 | 80.33 | 254.33 | 978.90 | 23.02 | 78.00 | 190.17 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3514.26 | 25.14 | 134.83 | 386.50 | 1725.66 | 24.82 | 130.67 | 357.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:30 | 478.98 | 15.61 | 0.00 | 229.50 | 329.10 | 17.49 | 0.00 | 145.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:50 | 585.71 | 16.55 | 0.00 | 227.33 | 376.36 | 18.13 | 0.00 | 135.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 669.33 | 17.76 | 0.00 | 303.83 | 417.59 | 19.14 | 3.17 | 232.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:49 | 793.16 | 18.89 | 0.00 | 336.17 | 519.99 | 20.22 | 46.67 | 304.33 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 931.54 | 19.66 | 25.33 | 388.67 | 609.72 | 20.95 | 93.33 | 373.17 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1074.96 | 22.44 | 108.00 | 400.00 | 633.70 | 22.52 | 139.83 | 391.17 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:00 | 954.44 | 21.81 | 82.67 | 394.17 | 604.04 | 23.01 | 150.83 | 360.50 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-07:10 | 800.66 | 18.98 | 0.33 | 348.50 | 507.62 | 20.30 | 48.00 | 295.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 759.28 | 18.31 | 0.00 | 315.00 | 464.10 | 19.64 | 12.33 | 256.67 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:49 | 551.52 | 16.47 | 0.00 | 263.83 | 367.52 | 18.06 | 1.00 | 190.50 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:20 | 518.34 | 16.32 | 0.00 | 238.50 | 343.65 | 18.10 | 0.00 | 138.17 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-08:00 | 481.42 | 15.79 | 0.00 | 216.17 | 322.82 | 17.68 | 0.00 | 117.00 |
Annual Sum or Average | 4135.50 | 0.52 | 741.16 | 18.49 | 216.33 | 3661.67 | 472.35 | 19.83 | 495.17 | 2939.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 478.98 | 15.61 | 0.00 | 216.17 | 322.82 | 17.49 | 0.00 | 117.00 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 1074.96 | 22.44 | 108.00 | 400.00 | 633.70 | 23.01 | 150.83 | 391.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:30 | 2347.22 | 23.99 | 107.83 | 248.67 | 1305.43 | 23.75 | 108.67 | 215.67 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-09:50 | 2378.79 | 23.28 | 82.50 | 239.50 | 927.32 | 21.81 | 93.17 | 179.50 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-08:20 | 2017.77 | 22.97 | 95.33 | 315.17 | 1090.39 | 23.26 | 142.33 | 277.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 2880.93 | 21.65 | 85.00 | 335.00 | 1595.31 | 22.26 | 85.00 | 309.17 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-07:19 | 3088.07 | 19.73 | 54.50 | 365.33 | 1699.37 | 19.64 | 55.50 | 335.83 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:10 | 3142.63 | 16.66 | 0.00 | 372.50 | 1264.94 | 19.26 | 56.17 | 345.00 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 2353.83 | 17.39 | 3.67 | 371.83 | 1054.96 | 19.59 | 69.50 | 325.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2411.80 | 19.54 | 49.17 | 343.33 | 1317.18 | 19.69 | 50.67 | 298.50 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1927.63 | 21.72 | 82.83 | 318.33 | 1034.18 | 22.22 | 116.17 | 282.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2335.20 | 23.53 | 112.00 | 288.50 | 1269.65 | 23.57 | 122.67 | 256.83 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:30 | 2180.53 | 23.73 | 93.00 | 254.67 | 1175.66 | 23.56 | 96.67 | 210.83 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-08:00 | 1833.59 | 23.24 | 91.83 | 241.33 | 973.90 | 22.92 | 102.33 | 201.83 |
Annual Sum or Average | 4135.50 | 0.51 | 2445.39 | 21.16 | 857.67 | 3694.17 | 1244.96 | 21.63 | 1098.83 | 3239.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1833.59 | 16.66 | 0.00 | 239.50 | 927.32 | 19.26 | 50.67 | 179.50 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3142.63 | 23.99 | 112.00 | 372.50 | 1699.37 | 23.75 | 142.33 | 345.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9256.88 | 38.69 | 306.33 | 291.50 | 2505.87 | 25.50 | 145.33 | 288.17 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8318.88 | 36.07 | 234.00 | 265.00 | 1407.09 | 19.01 | 38.33 | 226.67 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1630.15 | 13.16 | 2.33 | 329.00 | 996.35 | 16.74 | 1.83 | 291.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 1275.21 | 13.41 | 0.00 | 333.83 | 836.27 | 16.97 | 0.00 | 308.50 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:10 | 1014.24 | 13.30 | 0.00 | 360.50 | 667.29 | 16.87 | 0.00 | 325.17 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-06:49 | 846.30 | 12.61 | 0.00 | 363.83 | 572.67 | 16.21 | 0.00 | 322.50 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:10 | 970.53 | 12.87 | 0.00 | 364.83 | 614.13 | 16.41 | 0.00 | 305.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1113.85 | 13.10 | 0.00 | 338.67 | 710.27 | 16.67 | 0.00 | 296.33 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:00 | 1577.54 | 13.87 | 10.83 | 320.00 | 926.40 | 16.82 | 0.00 | 290.50 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3232.10 | 20.63 | 139.83 | 318.17 | 1220.89 | 16.33 | 13.17 | 300.83 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8756.22 | 37.28 | 282.17 | 285.33 | 1739.06 | 21.55 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8573.64 | 38.67 | 289.33 | 280.00 | 2341.09 | 25.02 | 130.50 | 275.33 |
Annual Sum or Average | 4135.50 | 0.51 | 3426.00 | 20.52 | 1264.83 | 3850.67 | 1141.08 | 18.36 | 418.33 | 3500.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 846.30 | 12.61 | 0.00 | 265.00 | 572.67 | 16.21 | 0.00 | 226.67 | |
Maximum of Months | 418.17 | 0.51 | 0.48 | 9256.88 | 38.69 | 306.33 | 364.83 | 2505.87 | 25.50 | 145.33 | 325.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:49 | 2223.78 | 22.19 | 105.17 | 275.00 | 1244.13 | 22.47 | 74.67 | 240.33 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2678.60 | 22.49 | 85.83 | 255.33 | 1514.03 | 22.84 | 62.83 | 197.17 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2214.85 | 19.02 | 86.17 | 316.50 | 1215.79 | 21.16 | 69.67 | 286.17 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3128.81 | 20.61 | 112.33 | 348.17 | 1794.46 | 21.46 | 82.33 | 330.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3547.21 | 21.75 | 134.17 | 381.67 | 1469.49 | 20.84 | 72.33 | 361.00 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3569.44 | 21.13 | 134.83 | 387.17 | 1449.36 | 20.30 | 74.83 | 358.00 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 3109.29 | 21.13 | 128.17 | 382.33 | 1309.21 | 20.31 | 68.33 | 331.33 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 3035.23 | 20.86 | 114.50 | 353.83 | 1721.37 | 21.61 | 83.50 | 314.67 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2420.26 | 20.63 | 103.83 | 319.33 | 1323.34 | 21.45 | 75.17 | 283.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2351.56 | 20.37 | 102.83 | 296.50 | 1288.59 | 20.89 | 72.17 | 263.33 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:30 | 1899.20 | 20.32 | 80.17 | 274.00 | 1026.09 | 20.86 | 52.83 | 217.33 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:30 | 2208.99 | 22.78 | 105.00 | 261.50 | 1240.38 | 22.98 | 74.00 | 215.33 |
Annual Sum or Average | 4135.50 | 0.50 | 2758.11 | 21.05 | 1293.00 | 3851.33 | 1393.85 | 21.33 | 862.67 | 3398.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1899.20 | 19.02 | 80.17 | 255.33 | 1026.09 | 20.30 | 52.83 | 197.17 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3569.44 | 22.78 | 134.83 | 387.17 | 1794.46 | 22.98 | 83.50 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:30 | 488.59 | 10.03 | 0.00 | 231.33 | 351.23 | 13.84 | 0.00 | 166.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:39 | 597.62 | 11.03 | 0.00 | 228.83 | 401.50 | 14.64 | 0.00 | 150.33 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 683.44 | 12.34 | 0.00 | 304.83 | 445.52 | 15.87 | 0.00 | 243.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 813.24 | 13.74 | 0.00 | 337.33 | 556.13 | 17.32 | 0.00 | 310.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 955.77 | 14.15 | 2.67 | 389.50 | 651.37 | 17.80 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1101.70 | 17.70 | 81.33 | 400.83 | 700.30 | 20.91 | 81.50 | 395.17 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:49 | 976.42 | 16.91 | 62.50 | 394.17 | 643.54 | 20.14 | 62.83 | 365.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:00 | 820.02 | 13.49 | 0.00 | 349.17 | 542.63 | 17.12 | 0.00 | 302.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 774.40 | 12.92 | 0.00 | 316.17 | 494.86 | 16.37 | 0.00 | 268.83 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:49 | 564.29 | 11.02 | 0.00 | 266.50 | 392.61 | 14.70 | 0.00 | 205.83 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:09 | 528.68 | 10.59 | 0.00 | 240.17 | 366.65 | 14.42 | 0.00 | 157.17 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-08:50 | 490.23 | 10.02 | 0.00 | 220.17 | 344.25 | 13.88 | 0.00 | 140.00 |
Annual Sum or Average | 4135.50 | 0.51 | 758.17 | 13.13 | 146.50 | 3679.00 | 506.62 | 16.70 | 147.00 | 3080.67 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 488.59 | 10.02 | 0.00 | 220.17 | 344.25 | 13.84 | 0.00 | 140.00 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 1101.70 | 17.70 | 81.33 | 400.83 | 700.30 | 20.91 | 81.50 | 395.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:20 | 2386.59 | 21.56 | 105.67 | 250.67 | 1356.66 | 21.90 | 74.67 | 221.50 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-09:30 | 2420.04 | 20.74 | 81.17 | 241.17 | 975.34 | 19.48 | 36.50 | 184.83 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-08:09 | 2064.46 | 19.91 | 93.67 | 317.50 | 1142.85 | 20.86 | 65.33 | 283.33 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 2920.61 | 18.19 | 85.00 | 336.67 | 1663.66 | 19.43 | 55.00 | 313.67 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-07:19 | 3126.94 | 15.77 | 54.50 | 366.17 | 1769.88 | 16.17 | 0.00 | 341.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-06:00 | 3161.30 | 11.88 | 0.00 | 372.83 | 1333.80 | 15.73 | 0.00 | 350.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 2390.01 | 12.83 | 3.67 | 374.00 | 1110.62 | 16.24 | 0.00 | 333.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 2443.40 | 15.63 | 49.17 | 344.17 | 1374.51 | 16.39 | 5.00 | 304.00 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1968.16 | 18.49 | 81.83 | 319.00 | 1085.15 | 19.66 | 53.83 | 286.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2369.39 | 20.52 | 109.33 | 290.50 | 1321.06 | 21.41 | 81.17 | 263.50 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:20 | 2161.95 | 19.72 | 80.83 | 255.50 | 1228.36 | 21.48 | 62.50 | 216.83 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-08:50 | 1831.33 | 19.71 | 80.67 | 243.50 | 1020.30 | 21.01 | 57.50 | 208.50 |
Annual Sum or Average | 4135.50 | 0.51 | 2475.07 | 17.55 | 825.50 | 3711.67 | 1302.06 | 18.91 | 491.50 | 3307.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1831.33 | 11.88 | 0.00 | 241.17 | 975.34 | 15.73 | 0.00 | 184.83 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3161.30 | 21.56 | 109.33 | 374.00 | 1769.88 | 21.90 | 81.17 | 350.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9257.89 | 38.68 | 306.33 | 291.50 | 2507.30 | 25.49 | 145.33 | 288.17 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8320.89 | 36.06 | 234.00 | 265.17 | 1408.65 | 19.00 | 38.33 | 226.83 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1632.26 | 13.13 | 2.33 | 329.17 | 997.69 | 16.72 | 1.83 | 292.00 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 1276.52 | 13.38 | 0.00 | 333.83 | 837.21 | 16.96 | 0.00 | 308.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:10 | 1015.19 | 13.27 | 0.00 | 360.67 | 668.03 | 16.85 | 0.00 | 325.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-06:49 | 846.98 | 12.58 | 0.00 | 363.83 | 573.26 | 16.19 | 0.00 | 322.50 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:10 | 971.59 | 12.84 | 0.00 | 364.83 | 614.89 | 16.39 | 0.00 | 306.17 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1115.10 | 13.07 | 0.00 | 338.67 | 711.13 | 16.65 | 0.00 | 296.50 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:00 | 1579.61 | 13.84 | 10.83 | 320.00 | 927.71 | 16.80 | 0.00 | 290.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3233.79 | 20.61 | 139.83 | 318.17 | 1222.12 | 16.31 | 13.17 | 300.83 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8757.50 | 37.27 | 282.17 | 285.33 | 1740.49 | 21.54 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8574.53 | 38.67 | 289.33 | 280.00 | 2342.64 | 25.00 | 130.50 | 275.50 |
Annual Sum or Average | 4135.50 | 0.51 | 3427.33 | 20.50 | 1264.83 | 3851.17 | 1142.18 | 18.35 | 418.33 | 3502.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 846.98 | 12.58 | 0.00 | 265.17 | 573.26 | 16.19 | 0.00 | 226.83 | |
Maximum of Months | 418.17 | 0.51 | 0.48 | 9257.89 | 38.68 | 306.33 | 364.83 | 2507.30 | 25.49 | 145.33 | 325.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:49 | 2224.18 | 22.16 | 105.17 | 275.00 | 1244.74 | 22.45 | 74.67 | 240.33 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2679.37 | 22.46 | 85.83 | 255.50 | 1514.90 | 22.83 | 62.83 | 197.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2215.92 | 18.99 | 86.17 | 316.50 | 1216.82 | 21.15 | 69.67 | 286.17 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3129.66 | 20.59 | 112.33 | 348.17 | 1795.45 | 21.44 | 82.33 | 330.67 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3548.04 | 21.72 | 134.17 | 381.67 | 1470.46 | 20.83 | 72.33 | 361.17 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 3570.07 | 21.10 | 134.83 | 387.17 | 1450.20 | 20.28 | 74.83 | 358.17 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 3110.32 | 21.10 | 128.17 | 382.33 | 1310.22 | 20.29 | 68.33 | 331.33 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 3036.27 | 20.83 | 114.50 | 353.83 | 1722.42 | 21.60 | 83.50 | 314.83 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2421.59 | 20.60 | 103.83 | 319.50 | 1324.53 | 21.44 | 75.17 | 283.83 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2352.20 | 20.34 | 102.83 | 296.50 | 1289.38 | 20.88 | 72.17 | 263.50 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:30 | 1899.76 | 20.29 | 80.17 | 274.00 | 1026.79 | 20.84 | 52.83 | 217.67 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:30 | 2209.47 | 22.75 | 105.00 | 261.50 | 1241.04 | 22.96 | 74.00 | 215.33 |
Annual Sum or Average | 4135.50 | 0.50 | 2758.93 | 21.03 | 1293.00 | 3851.67 | 1394.75 | 21.32 | 862.67 | 3400.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1899.76 | 18.99 | 80.17 | 255.50 | 1026.79 | 20.28 | 52.83 | 197.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3570.07 | 22.75 | 134.83 | 387.17 | 1795.45 | 22.96 | 83.50 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:30 | 488.74 | 9.99 | 0.00 | 231.33 | 351.54 | 13.82 | 0.00 | 166.83 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:39 | 598.03 | 11.00 | 0.00 | 228.83 | 401.94 | 14.62 | 0.00 | 150.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 684.02 | 12.31 | 0.00 | 304.83 | 446.05 | 15.85 | 0.00 | 243.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 813.75 | 13.70 | 0.00 | 337.33 | 556.69 | 17.31 | 0.00 | 310.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 956.44 | 14.11 | 2.67 | 389.50 | 652.02 | 17.78 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1102.34 | 17.67 | 81.33 | 400.83 | 700.94 | 20.90 | 81.50 | 395.33 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:49 | 977.27 | 16.89 | 62.50 | 394.17 | 644.27 | 20.12 | 62.83 | 365.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:00 | 820.68 | 13.46 | 0.00 | 349.17 | 543.23 | 17.10 | 0.00 | 302.67 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 775.11 | 12.89 | 0.00 | 316.17 | 495.47 | 16.35 | 0.00 | 269.00 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:49 | 564.60 | 10.99 | 0.00 | 266.50 | 392.98 | 14.69 | 0.00 | 206.50 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:09 | 528.95 | 10.56 | 0.00 | 240.17 | 367.02 | 14.41 | 0.00 | 158.33 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-08:50 | 490.44 | 9.99 | 0.00 | 220.33 | 344.58 | 13.86 | 0.00 | 140.33 |
Annual Sum or Average | 4135.50 | 0.51 | 758.69 | 13.10 | 146.50 | 3679.17 | 507.15 | 16.69 | 147.00 | 3084.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 488.74 | 9.99 | 0.00 | 220.33 | 344.58 | 13.82 | 0.00 | 140.33 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 1102.34 | 17.67 | 81.33 | 400.83 | 700.94 | 20.90 | 81.50 | 395.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:20 | 2386.99 | 21.54 | 105.67 | 250.67 | 1357.37 | 21.89 | 74.67 | 221.50 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-09:30 | 2420.95 | 20.71 | 81.17 | 241.50 | 976.29 | 19.47 | 36.50 | 184.83 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-08:09 | 2065.56 | 19.89 | 93.67 | 317.50 | 1143.87 | 20.85 | 65.33 | 283.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 2921.58 | 18.16 | 85.00 | 336.67 | 1664.78 | 19.41 | 55.00 | 313.67 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-07:19 | 3127.85 | 15.73 | 54.50 | 366.17 | 1770.97 | 16.16 | 0.00 | 341.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-06:00 | 3160.48 | 11.84 | 0.00 | 372.83 | 1334.75 | 15.71 | 0.00 | 350.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 2369.07 | 12.80 | 3.67 | 373.83 | 1111.66 | 16.22 | 0.00 | 333.17 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 2444.37 | 15.60 | 49.17 | 344.33 | 1375.49 | 16.37 | 5.00 | 304.00 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1969.47 | 18.47 | 81.83 | 319.17 | 1086.28 | 19.65 | 53.83 | 286.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2370.07 | 20.49 | 109.33 | 290.50 | 1321.85 | 21.40 | 81.17 | 263.67 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:20 | 2162.47 | 19.69 | 80.83 | 255.50 | 1229.14 | 21.46 | 62.50 | 217.00 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-08:50 | 1831.80 | 19.68 | 80.67 | 243.67 | 1021.01 | 20.99 | 57.50 | 208.50 |
Annual Sum or Average | 4135.50 | 0.51 | 2473.64 | 17.52 | 825.50 | 3712.33 | 1303.01 | 18.90 | 491.50 | 3308.83 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1831.80 | 11.84 | 0.00 | 241.50 | 976.29 | 15.71 | 0.00 | 184.83 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3160.48 | 21.54 | 109.33 | 373.83 | 1770.97 | 21.89 | 81.17 | 350.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142168E+09 | 8877.17 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208214E+09 | 8307.10 | 01-FEB-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262883E+09 | 14277.08 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30612625.29 | 7315.73 | 25-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50392143.45 | 7686.40 | 04-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.845530E+09 | 19794.12 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.845530E+09 | 19794.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3014744.71 | 2525.13 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3014744.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3014744.71 | 2525.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 147828.62 | 176.67 | 07-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147828.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 147828.62 | 176.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320865E+10 | 102156.30 | 02-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451631E+10 | 144267.64 | 08-FEB-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.498400E+10 | 155707.90 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12274217.03 | 12980.02 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3475.45 | 5.79 | 02-SEP-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102428E+10 | 95124.58 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208351E+10 | 110981.53 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175499E+11 | 196314.41 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175499E+11 | 196314.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158039E+10 | 153752.92 | 02-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115538E+10 | 145677.16 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.845713E+09 | 164314.10 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27325518.92 | 9940.45 | 26-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690506E+09 | 153152.36 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479185E+10 | 166478.25 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.909117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479185E+10 | 166478.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.490438E+09 | 142272.75 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300244E+09 | 84044.78 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268523E+09 | 103154.23 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148318E+09 | 141852.11 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165803E+10 | 148390.94 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165803E+10 | 148390.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182078E+09 | 158084.43 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118966E+09 | 111998.83 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222258E+09 | 141165.96 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21366958.69 | 8004.92 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.970193E+09 | 171316.43 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.970193E+09 | 171316.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217716E+09 | 106985.31 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91677896.59 | 42735.60 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63187939.87 | 65205.57 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63847478.36 | 67677.28 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121410E+10 | 141255.17 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121410E+10 | 141255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.615947E+09 | 13093.17 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.859712E+09 | 12139.79 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.801742E+09 | 18471.18 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9725687.25 | 4120.88 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237398E+09 | 11862.57 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440012E+09 | 14956.83 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253786E+10 | 19676.37 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.253786E+10 | 19676.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397294E+09 | 74689.39 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134262E+09 | 74463.20 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48053056.59 | 61776.44 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63108093.06 | 73527.41 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.503061E+09 | 74279.22 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.503061E+09 | 74689.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.921504E+09 | 17858.50 | 21-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.847797E+09 | 17912.77 | 21-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.525865E+09 | 17899.09 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2572371.50 | 586.05 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137995E+09 | 17729.57 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606254E+09 | 17776.96 | 18-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212245E+10 | 17839.46 | 18-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212245E+10 | 17912.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353877E+09 | 16225.91 | 21-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340755E+09 | 16232.65 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207455E+09 | 16214.87 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52973036.33 | 13120.53 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211689E+09 | 16185.43 | 30-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.830296E+09 | 16217.87 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.830296E+09 | 16232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234014E+09 | 19471.62 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366643E+09 | 19655.38 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300449E+09 | 19633.03 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40709395.92 | 13448.36 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164433E+09 | 19391.61 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733009E+09 | 19572.96 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.733009E+09 | 19655.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224989E+09 | 16988.86 | 02-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225498E+09 | 17011.44 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141272E+09 | 16959.53 | 27-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23887315.45 | 8758.24 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148729E+09 | 16954.06 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665009E+09 | 17030.70 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.665009E+09 | 17030.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 562.13 | 0.95 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 390.71 | 0.80 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1325.67 | 0.95 | 11-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 862.72 | 0.98 | 23-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 107.31 | 0.72 | 03-JUL-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 767.87 | 0.76 | 31-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 597.94 | 0.91 | 22-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4614.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1325.67 | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.383798E+11 | 0.383689E+11 | 92151.47 | 31-JAN-16:30 | 92151.47 | 0.01 |
February | 0.00 | 0.00 | 0.103346E+11 | 0.103346E+11 | 61362.74 | 21-FEB-15:00 | 61362.74 | 0.10 |
March | 0.00 | 0.00 | 0.420305E+11 | 0.420305E+11 | 102925.77 | 20-MAR-14:50 | 102925.77 | 0.08 |
April | 0.00 | 0.00 | 0.109042E+12 | 0.109042E+12 | 133227.83 | 24-APR-15:00 | 133227.83 | 0.02 |
May | 0.00 | 0.00 | 0.118971E+12 | 0.118971E+12 | 123242.72 | 15-MAY-15:20 | 123242.72 | 0.00 |
June | 0.00 | 0.00 | 0.161754E+12 | 0.161754E+12 | 155249.33 | 29-JUN-05:02 | 155249.33 | 0.11 |
July | 0.00 | 0.00 | 0.169378E+12 | 0.159160E+12 | 267810.29 | 14-JUL-05:03 | 108821.80 | 0.66 |
August | 0.00 | 0.00 | 0.188241E+12 | 0.177705E+12 | 254013.66 | 01-AUG-05:02 | 122221.52 | 0.74 |
September | 0.00 | 0.00 | 0.133737E+12 | 0.124889E+12 | 235762.83 | 08-SEP-05:02 | 137483.49 | 0.58 |
October | 0.00 | 0.00 | 0.817812E+11 | 0.804025E+11 | 161583.65 | 03-OCT-05:02 | 91651.23 | 0.19 |
November | 0.00 | 0.00 | 0.444422E+11 | 0.419024E+11 | 121825.52 | 13-NOV-06:03 | 43304.88 | 0.15 |
December | 0.00 | 0.00 | 0.281142E+11 | 0.281142E+11 | 90929.18 | 22-DEC-16:20 | 90929.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.112621E+13 | 0.109267E+13 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.103346E+11 | 0.103346E+11 | 61362.74 | 43304.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.188241E+12 | 0.177705E+12 | 267810.29 | 155249.33 | 0.74 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.323851E+12 | 0.323734E+12 | 808850.05 | 31-JAN-16:30 | 808850.05 | 0.02 |
February | 0.00 | 0.00 | 0.117458E+12 | 0.117458E+12 | 516284.50 | 28-FEB-16:30 | 516284.50 | 0.12 |
March | 0.00 | 0.00 | 0.302944E+12 | 0.302944E+12 | 863610.46 | 16-MAR-15:50 | 863610.46 | 0.08 |
April | 0.00 | 0.00 | 0.817647E+12 | 0.817647E+12 | 1153304.47 | 14-APR-15:20 | 1153304.47 | 0.01 |
May | 0.00 | 0.00 | 0.107128E+13 | 0.107128E+13 | 1163220.21 | 18-MAY-15:20 | 1163220.21 | 0.00 |
June | 0.00 | 0.00 | 0.143809E+13 | 0.143809E+13 | 1423114.24 | 29-JUN-05:02 | 1423114.24 | 0.09 |
July | 0.00 | 0.00 | 0.138268E+13 | 0.131062E+13 | 2508141.43 | 18-JUL-05:03 | 1155032.48 | 0.57 |
August | 0.00 | 0.00 | 0.139432E+13 | 0.132891E+13 | 2420429.54 | 01-AUG-05:02 | 1161537.78 | 0.62 |
September | 0.00 | 0.00 | 0.115739E+13 | 0.108420E+13 | 2255482.16 | 08-SEP-05:02 | 1313149.04 | 0.51 |
October | 0.00 | 0.00 | 0.671412E+12 | 0.659810E+12 | 1645109.59 | 03-OCT-04:12 | 900759.67 | 0.16 |
November | 0.00 | 0.00 | 0.327562E+12 | 0.315099E+12 | 965215.25 | 13-NOV-06:03 | 342159.41 | 0.14 |
December | 0.00 | 0.00 | 0.184411E+12 | 0.184411E+12 | 694723.94 | 22-DEC-15:05 | 694723.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.918905E+13 | 0.895420E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.117458E+12 | 0.117458E+12 | 516284.50 | 342159.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143809E+13 | 0.143809E+13 | 2508141.43 | 1423114.24 | 0.62 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.265404E+11 | 0.265327E+11 | 83629.74 | 31-JAN-16:30 | 83629.74 | 0.01 |
February | 0.00 | 0.00 | 0.546916E+10 | 0.546916E+10 | 42973.27 | 22-FEB-16:00 | 42973.27 | 0.10 |
March | 0.00 | 0.00 | 0.279167E+11 | 0.279167E+11 | 98148.47 | 16-MAR-15:30 | 98148.47 | 0.08 |
April | 0.00 | 0.00 | 0.895349E+11 | 0.895349E+11 | 137810.31 | 14-APR-15:20 | 137810.31 | 0.01 |
May | 0.00 | 0.00 | 0.118803E+12 | 0.118803E+12 | 139052.10 | 18-MAY-15:20 | 139052.10 | 0.00 |
June | 0.00 | 0.00 | 0.164382E+12 | 0.164382E+12 | 165335.65 | 28-JUN-14:50 | 165335.65 | 0.09 |
July | 0.00 | 0.00 | 0.157601E+12 | 0.150133E+12 | 273231.66 | 18-JUL-05:03 | 124863.00 | 0.58 |
August | 0.00 | 0.00 | 0.156140E+12 | 0.149411E+12 | 272408.07 | 01-AUG-05:02 | 131306.73 | 0.63 |
September | 0.00 | 0.00 | 0.125669E+12 | 0.118511E+12 | 252539.71 | 08-SEP-05:02 | 147495.57 | 0.52 |
October | 0.00 | 0.00 | 0.672157E+11 | 0.661432E+11 | 173967.54 | 03-OCT-04:12 | 92600.66 | 0.16 |
November | 0.00 | 0.00 | 0.268978E+11 | 0.260890E+11 | 100636.89 | 01-NOV-15:30 | 100636.89 | 0.12 |
December | 0.00 | 0.00 | 0.117466E+11 | 0.117466E+11 | 69410.78 | 22-DEC-16:20 | 69410.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.977917E+12 | 0.954672E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.546916E+10 | 0.546916E+10 | 42973.27 | 42973.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.164382E+12 | 0.164382E+12 | 273231.66 | 165335.65 | 0.63 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.229053E+11 | 0.229020E+11 | 83482.57 | 16-JAN-14:50 | 83482.57 | 0.00 |
February | 0.00 | 0.00 | 0.379554E+10 | 0.377346E+10 | 48374.82 | 17-FEB-06:02 | 20406.85 | 0.06 |
March | 0.00 | 0.00 | 0.220022E+11 | 0.219930E+11 | 59731.98 | 20-MAR-13:10 | 59731.98 | 0.05 |
April | 0.00 | 0.00 | 0.549588E+11 | 0.549588E+11 | 89690.36 | 25-APR-03:50 | 89690.36 | 0.00 |
May | 0.00 | 0.00 | 0.676502E+11 | 0.676502E+11 | 110407.99 | 29-MAY-14:30 | 110407.99 | 0.00 |
June | 0.00 | 0.00 | 0.828312E+11 | 0.828312E+11 | 101976.94 | 27-JUN-03:02 | 101976.94 | 0.07 |
July | 0.00 | 0.00 | 0.895745E+11 | 0.864705E+11 | 147000.77 | 14-JUL-05:03 | 59833.07 | 0.46 |
August | 0.00 | 0.00 | 0.100648E+12 | 0.967842E+11 | 147367.41 | 01-AUG-03:02 | 77112.75 | 0.54 |
September | 0.00 | 0.00 | 0.852160E+11 | 0.809984E+11 | 153781.39 | 04-SEP-14:51 | 82539.86 | 0.47 |
October | 0.00 | 0.00 | 0.532275E+11 | 0.527084E+11 | 111756.19 | 03-OCT-04:22 | 58737.07 | 0.15 |
November | 0.00 | 0.00 | 0.281222E+11 | 0.259571E+11 | 99899.05 | 13-NOV-05:53 | 35825.14 | 0.11 |
December | 0.00 | 0.00 | 0.122860E+11 | 0.122840E+11 | 83339.95 | 24-DEC-15:51 | 83339.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.623217E+12 | 0.609311E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.379554E+10 | 0.377346E+10 | 48374.82 | 20406.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100648E+12 | 0.967842E+11 | 153781.39 | 110407.99 | 0.54 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.288478E+11 | 0.288193E+11 | 134486.96 | 27-JAN-16:00 | 134486.96 | 0.00 |
February | 0.00 | 0.00 | 0.101054E+11 | 0.952526E+10 | 100783.47 | 18-FEB-14:00 | 86806.67 | 0.00 |
March | 0.00 | 0.00 | 0.193188E+12 | 0.189284E+12 | 316173.54 | 17-MAR-15:20 | 316173.54 | 0.00 |
April | 0.00 | 0.00 | 0.671426E+12 | 0.669674E+12 | 376042.78 | 15-APR-09:00 | 376042.78 | 0.00 |
May | 0.00 | 0.00 | 0.216396E+12 | 0.216395E+12 | 213134.16 | 31-MAY-23:10 | 213134.16 | 0.00 |
June | 0.00 | 0.00 | 0.517468E+12 | 0.517451E+12 | 305707.12 | 30-JUN-24:00 | 305707.12 | 0.00 |
July | 0.00 | 0.00 | 0.869345E+12 | 0.786233E+12 | 467200.21 | 14-JUL-01:00 | 154594.70 | 0.00 |
August | 0.00 | 0.00 | 0.106296E+13 | 0.932046E+12 | 451312.81 | 09-AUG-18:30 | 232619.94 | 0.00 |
September | 0.00 | 0.00 | 0.265133E+12 | 0.238700E+12 | 233456.88 | 04-SEP-10:18 | 129388.76 | 0.00 |
October | 0.00 | 0.00 | 0.250565E+12 | 0.239527E+12 | 335824.24 | 03-OCT-08:30 | 223237.22 | 0.00 |
November | 0.00 | 0.00 | 0.202691E+12 | 0.175374E+12 | 319326.09 | 20-NOV-15:20 | 319326.09 | 0.00 |
December | 0.00 | 0.00 | 0.202559E+12 | 0.202170E+12 | 347164.48 | 25-DEC-13:52 | 347164.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.449069E+13 | 0.420520E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.101054E+11 | 0.952526E+10 | 100783.47 | 86806.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106296E+13 | 0.932046E+12 | 467200.21 | 376042.78 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.534652E+10 | 0.534336E+10 | 2818.47 | 29-JAN-17:15 | 2818.47 | 0.00 |
February | 0.00 | 0.00 | 0.928562E+10 | 0.924195E+10 | 4543.13 | 20-FEB-17:03 | 4523.99 | 0.00 |
March | 0.00 | 0.00 | 0.156304E+11 | 0.156188E+11 | 7697.37 | 31-MAR-24:00 | 7697.37 | 0.00 |
April | 0.00 | 0.00 | 0.198755E+11 | 0.198755E+11 | 8240.85 | 26-APR-19:00 | 8240.85 | 0.00 |
May | 0.00 | 0.00 | 0.619541E+10 | 0.619541E+10 | 4046.23 | 31-MAY-24:00 | 4046.23 | 0.00 |
June | 0.00 | 0.00 | 0.111005E+11 | 0.110989E+11 | 5978.41 | 30-JUN-23:55 | 5978.41 | 0.00 |
July | 0.00 | 0.00 | 0.166112E+11 | 0.164600E+11 | 7901.86 | 31-JUL-23:53 | 7888.23 | 0.00 |
August | 0.00 | 0.00 | 0.212708E+11 | 0.211198E+11 | 8700.41 | 28-AUG-16:45 | 8158.07 | 0.00 |
September | 0.00 | 0.00 | 0.618177E+10 | 0.604503E+10 | 4053.04 | 30-SEP-23:40 | 4053.04 | 0.00 |
October | 0.00 | 0.00 | 0.110138E+11 | 0.109834E+11 | 5868.49 | 31-OCT-24:00 | 5868.49 | 0.00 |
November | 0.00 | 0.00 | 0.153094E+11 | 0.152607E+11 | 6809.20 | 26-NOV-16:57 | 6809.20 | 0.00 |
December | 0.00 | 0.00 | 0.205152E+11 | 0.205147E+11 | 8294.11 | 24-DEC-18:35 | 8294.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158336E+12 | 0.157758E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.534652E+10 | 0.534336E+10 | 2818.47 | 2818.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212708E+11 | 0.211198E+11 | 8700.41 | 8294.11 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.413219E+11 | 0.412920E+11 | 25257.27 | 29-JAN-17:27 | 25257.27 | 0.00 |
February | 0.00 | 0.00 | 0.792320E+11 | 0.788028E+11 | 41058.05 | 22-FEB-17:00 | 40536.30 | 0.00 |
March | 0.00 | 0.00 | 0.142437E+12 | 0.142321E+12 | 72005.98 | 31-MAR-23:50 | 72005.98 | 0.00 |
April | 0.00 | 0.00 | 0.188183E+12 | 0.188183E+12 | 78380.96 | 26-APR-18:50 | 78380.96 | 0.00 |
May | 0.00 | 0.00 | 0.575800E+11 | 0.575800E+11 | 39205.81 | 31-MAY-24:00 | 39205.81 | 0.00 |
June | 0.00 | 0.00 | 0.105732E+12 | 0.105713E+12 | 57420.45 | 30-JUN-23:40 | 57420.45 | 0.00 |
July | 0.00 | 0.00 | 0.158025E+12 | 0.156521E+12 | 75532.34 | 31-JUL-23:53 | 75399.33 | 0.00 |
August | 0.00 | 0.00 | 0.200639E+12 | 0.199111E+12 | 82100.49 | 28-AUG-16:25 | 76513.78 | 0.00 |
September | 0.00 | 0.00 | 0.571376E+11 | 0.557967E+11 | 39379.51 | 30-SEP-24:00 | 39379.51 | 0.00 |
October | 0.00 | 0.00 | 0.100584E+12 | 0.100283E+12 | 54399.08 | 31-OCT-24:00 | 54399.08 | 0.00 |
November | 0.00 | 0.00 | 0.138396E+12 | 0.137913E+12 | 63574.00 | 14-NOV-17:00 | 61330.23 | 0.00 |
December | 0.00 | 0.00 | 0.183880E+12 | 0.183874E+12 | 77864.26 | 26-DEC-17:30 | 77864.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145315E+13 | 0.144739E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.413219E+11 | 0.412920E+11 | 25257.27 | 25257.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200639E+12 | 0.199111E+12 | 82100.49 | 78380.96 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.318619E+10 | 0.318357E+10 | 2486.06 | 24-JAN-17:00 | 2486.06 | 0.00 |
February | 0.00 | 0.00 | 0.689903E+10 | 0.685682E+10 | 4147.35 | 22-FEB-17:00 | 4094.77 | 0.00 |
March | 0.00 | 0.00 | 0.135869E+11 | 0.135755E+11 | 7036.01 | 31-MAR-23:20 | 7036.01 | 0.00 |
April | 0.00 | 0.00 | 0.188898E+11 | 0.188898E+11 | 7952.94 | 26-APR-18:30 | 7952.94 | 0.00 |
May | 0.00 | 0.00 | 0.582896E+10 | 0.582896E+10 | 3945.43 | 31-MAY-24:00 | 3945.43 | 0.00 |
June | 0.00 | 0.00 | 0.107650E+11 | 0.107632E+11 | 5812.09 | 30-JUN-23:40 | 5812.09 | 0.00 |
July | 0.00 | 0.00 | 0.160141E+11 | 0.158636E+11 | 7613.33 | 31-JUL-23:53 | 7599.90 | 0.00 |
August | 0.00 | 0.00 | 0.202826E+11 | 0.201288E+11 | 8316.71 | 28-AUG-16:15 | 7727.71 | 0.00 |
September | 0.00 | 0.00 | 0.582207E+10 | 0.568743E+10 | 3981.41 | 30-SEP-23:55 | 3981.41 | 0.00 |
October | 0.00 | 0.00 | 0.970800E+10 | 0.967805E+10 | 5255.56 | 31-OCT-23:40 | 5255.56 | 0.00 |
November | 0.00 | 0.00 | 0.129882E+11 | 0.129403E+11 | 6379.85 | 14-NOV-17:00 | 6155.10 | 0.00 |
December | 0.00 | 0.00 | 0.169957E+11 | 0.169951E+11 | 7844.73 | 26-DEC-17:10 | 7844.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140966E+12 | 0.140391E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.318619E+10 | 0.318357E+10 | 2486.06 | 2486.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202826E+11 | 0.201288E+11 | 8316.71 | 7952.94 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 3151.26 | 902703.01 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3768.11 | 796669.89 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3210.18 | 907752.31 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 6.74 | 12554.17 | 21-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.44 | 23-MAY-04:12 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.32 | 03-JUL-04:42 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 2.98 | 02-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 562.89 | 149984.57 | 25-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1790.31 | 830716.92 | 24-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12726.93 | 1069997.90 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 2105.77 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 12726.93 | 1069997.90 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 161657.33 | 1341433.94 | 27-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 57431.92 | 665932.49 | 22-FEB-14:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 153138.38 | 1470300.65 | 16-MAR-13:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 431295.42 | 1632436.42 | 11-APR-12:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 535741.29 | 1664857.70 | 26-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 729733.67 | 1807763.46 | 19-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 697961.20 | 2687421.11 | 14-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 710385.81 | 2027326.44 | 01-AUG-05:04 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 606915.28 | 1905258.24 | 05-SEP-07:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 340247.17 | 1608677.73 | 03-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 175388.80 | 1588161.59 | 20-NOV-15:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 91133.28 | 1020936.51 | 22-DEC-16:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 392619.96 | 0.00 | ||||
Minimum of Months | 57431.92 | 665932.49 | 0.00 | 0.00 | ||
Maximum of Months | 729733.67 | 2687421.11 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 160316.65 | 1350647.18 | 31-JAN-15:50 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56500.68 | 785835.56 | 22-FEB-14:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 151372.65 | 1480986.89 | 20-MAR-14:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 425551.07 | 1603978.24 | 25-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 529409.21 | 1660917.01 | 08-MAY-04:12 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 723468.17 | 2300757.69 | 29-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 694465.05 | 3478188.33 | 18-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 708140.34 | 3288089.33 | 01-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 604292.96 | 3184019.67 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 337680.53 | 2969435.21 | 03-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 175043.22 | 2324825.40 | 02-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 90031.26 | 1020350.94 | 22-DEC-16:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 389716.62 | 0.00 | ||||
Minimum of Months | 56500.68 | 785835.56 | 0.00 | 0.00 | ||
Maximum of Months | 723468.17 | 3478188.33 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 105430.88 | 851107.62 | 31-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 64306.87 | 444555.46 | 18-FEB-14:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 290381.36 | 1278508.36 | 16-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 944472.62 | 1732983.78 | 14-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 622479.62 | 1286991.77 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1152588.61 | 1813924.02 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1390981.52 | 1943324.51 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1531044.52 | 2095725.04 | 27-AUG-14:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 727527.49 | 1366649.99 | 08-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 469254.51 | 1504605.97 | 01-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 290633.90 | 1287600.68 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 268947.71 | 1231991.49 | 25-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 658332.59 | 0.00 | ||||
Minimum of Months | 64306.87 | 444555.46 | 0.00 | 0.00 | ||
Maximum of Months | 1531044.52 | 2095725.04 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13395.14 | 44380.43 | 26-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13350.47 | 44240.74 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13472.76 | 43013.50 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11814.36 | 39982.65 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 11167.63 | 36795.18 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 10551.93 | 33482.28 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9445.13 | 31299.17 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 10335.99 | 32147.70 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 10381.55 | 34800.97 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 11268.88 | 38432.46 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12383.29 | 41626.46 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12739.23 | 43718.68 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11683.05 | ||||
Minimum of Months | 0.00 | 0.00 | 9445.13 | 31299.17 | ||
Maximum of Months | 0.00 | 0.00 | 13472.76 | 44380.43 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 186143.61 | 2137410.29 | 27-JAN-15:50 | 1011.19 | 97097.74 | 05-JAN-06:03 |
February | 66196.90 | 683801.20 | 28-FEB-16:30 | 1052.99 | 91190.04 | 01-FEB-08:07 |
March | 173671.18 | 2165089.26 | 20-MAR-15:10 | 1356.71 | 116540.28 | 25-MAR-05:50 |
April | 539438.75 | 2305957.59 | 24-APR-14:40 | 3555.75 | 90990.32 | 24-APR-05:20 |
May | 699421.31 | 2320823.97 | 15-MAY-15:00 | 322.81 | 59074.87 | 01-MAY-06:30 |
June | 1020316.73 | 3746351.90 | 28-JUN-16:00 | 531.18 | 64155.93 | 12-JUN-03:20 |
July | 1286901.33 | 4520988.90 | 18-JUL-05:05 | 380.19 | 86058.37 | 02-JUL-05:20 |
August | 1306517.36 | 4411163.42 | 16-AUG-10:30 | 358.89 | 56729.53 | 26-AUG-02:50 |
September | 1035973.63 | 4577185.89 | 01-SEP-12:30 | 21.51 | 28266.19 | 16-SEP-23:30 |
October | 470041.95 | 3614822.69 | 03-OCT-10:05 | 844.54 | 109269.53 | 25-OCT-05:50 |
November | 207172.49 | 2291573.90 | 02-NOV-15:20 | 1230.85 | 92542.69 | 27-NOV-20:00 |
December | 103983.18 | 1161117.63 | 22-DEC-16:30 | 1981.26 | 121180.37 | 14-DEC-06:40 |
Annual Sum or Average | 594431.89 | 1050.92 | ||||
Minimum of Months | 66196.90 | 683801.20 | 21.51 | 28266.19 | ||
Maximum of Months | 1306517.36 | 4577185.89 | 3555.75 | 121180.37 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143057E+11 | 0.89 | 9240.63 | 01-JAN-00:20 | 1.53 |
February | 0.123778E+11 | 0.84 | 9240.63 | 01-FEB-05:13 | 1.53 |
March | 0.143932E+11 | 0.89 | 9240.63 | 01-MAR-05:13 | 1.52 |
April | 0.135273E+11 | 0.87 | 9240.63 | 01-APR-04:12 | 1.53 |
May | 0.142412E+11 | 0.88 | 9240.63 | 01-MAY-00:13 | 1.54 |
June | 0.142061E+11 | 0.91 | 9240.63 | 01-JUN-04:12 | 1.53 |
July | 0.149931E+11 | 0.92 | 9240.63 | 01-JUL-04:12 | 1.54 |
August | 0.162920E+11 | 1.00 | 9240.63 | 01-AUG-03:02 | 1.51 |
September | 0.152034E+11 | 0.96 | 9240.63 | 01-SEP-03:03 | 1.51 |
October | 0.153840E+11 | 0.95 | 9240.63 | 01-OCT-12:12 | 1.53 |
November | 0.145918E+11 | 0.93 | 9240.63 | 01-NOV-04:12 | 1.52 |
December | 0.147762E+11 | 0.92 | 9240.63 | 01-DEC-05:12 | 1.53 |
Annual Sum or Average | 0.174292E+12 | 0.91 | |||
Minimum of Months | 0.123778E+11 | 0.84 | 9240.63 | 1.51 | |
Maximum of Months | 0.162920E+11 | 1.00 | 9240.63 | 1.54 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.559368E+10 | 0.41 | 11047.52 | 17-JAN-17:00 | 1.31 |
February | 0.502638E+10 | 0.40 | 11335.23 | 21-FEB-16:00 | 1.32 |
March | 0.771945E+10 | 0.49 | 13579.57 | 20-MAR-15:00 | 1.47 |
April | 0.125788E+11 | 0.75 | 21083.88 | 24-APR-05:02 | 1.96 |
May | 0.113825E+11 | 0.64 | 21083.88 | 01-MAY-05:02 | 1.96 |
June | 0.142224E+11 | 0.81 | 21083.88 | 01-JUN-04:12 | 1.94 |
July | 0.146667E+11 | 0.80 | 21083.88 | 05-JUL-04:12 | 1.95 |
August | 0.174488E+11 | 0.88 | 21083.88 | 02-AUG-05:02 | 1.93 |
September | 0.107311E+11 | 0.63 | 21083.88 | 01-SEP-05:03 | 1.93 |
October | 0.886966E+10 | 0.54 | 21083.88 | 02-OCT-04:23 | 1.93 |
November | 0.741254E+10 | 0.48 | 14424.78 | 20-NOV-17:00 | 1.53 |
December | 0.657139E+10 | 0.44 | 14390.48 | 26-DEC-17:00 | 1.53 |
Annual Sum or Average | 0.122223E+12 | 0.61 | |||
Minimum of Months | 0.502638E+10 | 0.40 | 11047.52 | 1.31 | |
Maximum of Months | 0.174488E+11 | 0.88 | 21083.88 | 1.96 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.370334E+11 | 0.35 | 76787.00 | 31-JAN-17:00 | 1.09 |
February | 0.303257E+11 | 0.33 | 80123.44 | 03-FEB-06:02 | 1.11 |
March | 0.440628E+11 | 0.39 | 96190.97 | 16-MAR-15:50 | 1.24 |
April | 0.785200E+11 | 0.53 | 190300.04 | 25-APR-05:03 | 1.90 |
May | 0.958959E+11 | 0.58 | 198394.83 | 08-MAY-04:12 | 1.95 |
June | 0.118127E+12 | 0.71 | 198394.83 | 01-JUN-04:12 | 1.94 |
July | 0.106299E+12 | 0.64 | 198394.83 | 05-JUL-04:12 | 1.95 |
August | 0.109318E+12 | 0.65 | 198394.83 | 02-AUG-05:02 | 1.93 |
September | 0.860053E+11 | 0.55 | 198394.83 | 02-SEP-05:03 | 1.93 |
October | 0.596141E+11 | 0.44 | 198394.83 | 02-OCT-05:02 | 1.93 |
November | 0.407093E+11 | 0.37 | 92384.45 | 01-NOV-05:03 | 1.20 |
December | 0.322501E+11 | 0.34 | 111189.82 | 16-DEC-06:02 | 1.36 |
Annual Sum or Average | 0.838161E+12 | 0.49 | |||
Minimum of Months | 0.303257E+11 | 0.33 | 76787.00 | 1.09 | |
Maximum of Months | 0.118127E+12 | 0.71 | 198394.83 | 1.95 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.322779E+10 | 0.35 | 6616.29 | 31-JAN-16:40 | 0.92 |
February | 0.258526E+10 | 0.34 | 5971.96 | 22-FEB-16:30 | 0.86 |
March | 0.368955E+10 | 0.37 | 9522.06 | 16-MAR-15:30 | 1.13 |
April | 0.771307E+10 | 0.50 | 15761.72 | 14-APR-15:20 | 1.54 |
May | 0.973295E+10 | 0.55 | 22670.49 | 08-MAY-04:12 | 1.94 |
June | 0.130275E+11 | 0.71 | 22670.49 | 05-JUN-04:12 | 1.94 |
July | 0.116257E+11 | 0.65 | 22670.49 | 03-JUL-04:11 | 1.95 |
August | 0.117697E+11 | 0.64 | 22670.49 | 01-AUG-05:02 | 1.92 |
September | 0.882583E+10 | 0.53 | 22670.49 | 02-SEP-05:03 | 1.92 |
October | 0.539392E+10 | 0.41 | 22670.49 | 04-OCT-05:02 | 1.92 |
November | 0.338979E+10 | 0.35 | 8459.43 | 02-NOV-15:40 | 1.04 |
December | 0.281693E+10 | 0.34 | 5753.39 | 22-DEC-16:50 | 0.85 |
Annual Sum or Average | 0.837979E+11 | 0.48 | |||
Minimum of Months | 0.258526E+10 | 0.34 | 5753.39 | 0.85 | |
Maximum of Months | 0.130275E+11 | 0.71 | 22670.49 | 1.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103261E+12 | 1.49 | 38553.21 | 01-JAN-00:05 | 1.48 |
February | 0.932679E+11 | 1.48 | 38553.21 | 01-FEB-00:10 | 1.49 |
March | 0.103261E+12 | 1.49 | 38553.21 | 01-MAR-00:10 | 1.48 |
April | 0.999299E+11 | 1.49 | 38553.21 | 01-APR-00:10 | 1.49 |
May | 0.103261E+12 | 1.49 | 38553.21 | 01-MAY-00:10 | 1.49 |
June | 0.999299E+11 | 1.48 | 38553.21 | 01-JUN-00:05 | 1.49 |
July | 0.103261E+12 | 1.48 | 38553.21 | 01-JUL-00:10 | 1.48 |
August | 0.103261E+12 | 1.47 | 38553.21 | 01-AUG-00:05 | 1.48 |
September | 0.999299E+11 | 1.47 | 38553.21 | 01-SEP-00:10 | 1.48 |
October | 0.103261E+12 | 1.49 | 38553.21 | 01-OCT-00:05 | 1.48 |
November | 0.999299E+11 | 1.49 | 38553.21 | 01-NOV-00:10 | 1.49 |
December | 0.103261E+12 | 1.49 | 38553.21 | 01-DEC-00:10 | 1.49 |
Annual Sum or Average | 0.121581E+13 | 1.48 | |||
Minimum of Months | 0.932679E+11 | 1.47 | 38553.21 | 1.48 | |
Maximum of Months | 0.103261E+12 | 1.49 | 38553.21 | 1.49 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151789E+10 | 1.01 | 566.72 | 01-JAN-00:05 | 1.01 |
February | 0.137100E+10 | 1.01 | 566.72 | 01-FEB-00:10 | 1.01 |
March | 0.151789E+10 | 1.01 | 566.72 | 01-MAR-00:10 | 1.01 |
April | 0.146893E+10 | 1.01 | 566.72 | 01-APR-00:10 | 1.01 |
May | 0.151789E+10 | 1.01 | 566.72 | 01-MAY-00:10 | 1.01 |
June | 0.146893E+10 | 1.01 | 566.72 | 01-JUN-00:05 | 1.01 |
July | 0.151789E+10 | 1.00 | 566.72 | 01-JUL-00:10 | 1.01 |
August | 0.151789E+10 | 1.00 | 566.72 | 01-AUG-00:05 | 1.00 |
September | 0.146893E+10 | 1.00 | 566.72 | 01-SEP-00:20 | 1.00 |
October | 0.151789E+10 | 1.01 | 566.72 | 01-OCT-00:05 | 1.01 |
November | 0.146893E+10 | 1.01 | 566.72 | 01-NOV-00:10 | 1.01 |
December | 0.151789E+10 | 1.01 | 566.72 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.178719E+11 | 1.01 | |||
Minimum of Months | 0.137100E+10 | 1.00 | 566.72 | 1.00 | |
Maximum of Months | 0.151789E+10 | 1.01 | 566.72 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144924E+11 | 1.01 | 5410.86 | 01-JAN-00:05 | 1.01 |
February | 0.130900E+11 | 1.01 | 5410.86 | 01-FEB-00:10 | 1.01 |
March | 0.144924E+11 | 1.01 | 5410.86 | 01-MAR-00:10 | 1.01 |
April | 0.140250E+11 | 1.01 | 5410.86 | 01-APR-00:10 | 1.01 |
May | 0.144924E+11 | 1.01 | 5410.86 | 01-MAY-00:10 | 1.01 |
June | 0.140250E+11 | 1.01 | 5410.86 | 01-JUN-00:05 | 1.01 |
July | 0.144924E+11 | 1.00 | 5410.86 | 01-JUL-00:10 | 1.01 |
August | 0.144924E+11 | 1.00 | 5410.86 | 01-AUG-00:05 | 1.00 |
September | 0.140250E+11 | 1.00 | 5410.86 | 01-SEP-00:10 | 1.00 |
October | 0.144924E+11 | 1.01 | 5410.86 | 01-OCT-00:05 | 1.01 |
November | 0.140250E+11 | 1.01 | 5410.86 | 01-NOV-00:10 | 1.01 |
December | 0.144924E+11 | 1.01 | 5410.86 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.170637E+12 | 1.01 | |||
Minimum of Months | 0.130900E+11 | 1.00 | 5410.86 | 1.00 | |
Maximum of Months | 0.144924E+11 | 1.01 | 5410.86 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148332E+10 | 1.01 | 553.81 | 01-JAN-00:05 | 1.00 |
February | 0.133977E+10 | 1.01 | 553.81 | 01-FEB-00:10 | 1.01 |
March | 0.148332E+10 | 1.01 | 553.81 | 01-MAR-00:10 | 1.01 |
April | 0.143547E+10 | 1.01 | 553.81 | 01-APR-00:10 | 1.01 |
May | 0.148332E+10 | 1.01 | 553.81 | 01-MAY-00:10 | 1.01 |
June | 0.143547E+10 | 1.01 | 553.81 | 01-JUN-00:05 | 1.01 |
July | 0.148332E+10 | 1.00 | 553.81 | 01-JUL-00:10 | 1.01 |
August | 0.148332E+10 | 1.00 | 553.81 | 01-AUG-00:05 | 1.00 |
September | 0.143547E+10 | 1.00 | 553.81 | 01-SEP-00:10 | 1.00 |
October | 0.148332E+10 | 1.01 | 553.81 | 01-OCT-00:05 | 1.01 |
November | 0.143547E+10 | 1.01 | 553.81 | 01-NOV-00:10 | 1.01 |
December | 0.148332E+10 | 1.01 | 553.81 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.174649E+11 | 1.01 | |||
Minimum of Months | 0.133977E+10 | 1.00 | 553.81 | 1.00 | |
Maximum of Months | 0.148332E+10 | 1.01 | 553.81 | 1.01 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 79768228.44 | 72509319.65 | 7333.45 | 02-JAN-06:03 | 6666.10 | 6666.10 | 45.32 | 13.86 |
February | 81219260.70 | 73828307.98 | 6082.61 | 13-FEB-06:03 | 5529.10 | 5529.10 | 39.77 | 9.42 |
March | 86846350.64 | 78943332.73 | 6769.93 | 27-MAR-05:03 | 6153.86 | 6153.86 | 41.16 | 11.53 |
April | 179798.80 | 163437.11 | 129.35 | 21-APR-06:10 | 117.58 | 117.58 | 37.48 | 0.13 |
May | 3.90 | 3.55 | 0.00 | 23-MAY-04:12 | 0.00 | 0.00 | 37.06 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 37.06 | 0.00 |
July | 0.49 | 0.44 | 0.00 | 03-JUL-04:42 | 0.00 | 0.00 | 37.06 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 37.06 | 0.00 |
September | 18.17 | 16.51 | 0.03 | 02-SEP-11:50 | 0.03 | 0.03 | 37.06 | 0.00 |
October | 14026529.64 | 12750115.44 | 1282.68 | 25-OCT-06:30 | 1165.96 | 1165.96 | 37.23 | 1.40 |
November | 42167658.29 | 38330401.39 | 6178.20 | 24-NOV-06:02 | 5615.99 | 5615.99 | 39.47 | 9.68 |
December | 0.358213E+09 | 0.325615E+09 | 7396.00 | 07-DEC-06:01 | 6722.96 | 6722.96 | 41.97 | 14.20 |
Annual Sum or Average | 0.662421E+09 | 0.602140E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 | 0.00 | |
Maximum of Months | 0.358213E+09 | 0.325615E+09 | 7396.00 | 6722.96 | 6722.96 | 45.32 | 14.20 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.148583E+09 | 0.135062E+09 | 1046.22 | 27-JAN-15:40 | 951.02 | 951.02 | 7.88 | 24.46 |
February | 47761436.30 | 43415145.60 | 732.72 | 23-FEB-14:20 | 666.04 | 666.04 | 6.71 | 20.84 |
March | 0.144269E+09 | 0.131140E+09 | 3165.65 | 17-MAR-15:10 | 2877.58 | 2877.58 | 8.20 | 39.37 |
April | 0.369794E+09 | 0.336143E+09 | 1437.19 | 25-APR-05:03 | 1306.41 | 1306.41 | 6.71 | 28.14 |
May | 0.484343E+09 | 0.440268E+09 | 1394.34 | 26-MAY-05:02 | 1267.46 | 1267.46 | 6.70 | 27.77 |
June | 0.102704E+10 | 0.933578E+09 | 6008.50 | 19-JUN-14:50 | 5461.73 | 5461.73 | 6.72 | 51.16 |
July | 0.139233E+10 | 0.126562E+10 | 10308.57 | 10-JUL-05:02 | 9370.49 | 9370.49 | 9.73 | 63.39 |
August | 0.160690E+10 | 0.146067E+10 | 10308.57 | 01-AUG-05:02 | 9370.49 | 9370.49 | 6.72 | 63.39 |
September | 0.131372E+10 | 0.119417E+10 | 10308.57 | 02-SEP-05:03 | 9370.49 | 9370.49 | 10.46 | 63.39 |
October | 0.617221E+09 | 0.561054E+09 | 10308.57 | 02-OCT-05:02 | 9370.49 | 9370.49 | 9.36 | 63.39 |
November | 0.260339E+09 | 0.236648E+09 | 9174.29 | 02-NOV-14:30 | 8339.43 | 8339.43 | 11.44 | 60.53 |
December | 62400533.08 | 56722084.57 | 557.50 | 22-DEC-16:30 | 506.77 | 506.77 | 6.71 | 18.37 |
Annual Sum or Average | 0.747469E+10 | 0.679450E+10 | ||||||
Minimum of Months | 47761436.30 | 43415145.60 | 557.50 | 506.77 | 506.77 | 6.70 | 18.37 | |
Maximum of Months | 0.160690E+10 | 0.146067E+10 | 10308.57 | 9370.49 | 9370.49 | 11.44 | 63.39 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.397887E+10 | 0.361679E+10 | 3547.56 | 01-JAN-14:02 | 3224.73 | 3224.73 | 6.75 | 31.69 |
February | 0.259915E+10 | 0.236263E+10 | 3547.56 | 01-FEB-08:07 | 3224.73 | 3224.73 | 6.74 | 31.69 |
March | 0.453473E+10 | 0.412207E+10 | 3547.56 | 01-MAR-06:03 | 3224.73 | 3224.73 | 6.86 | 31.69 |
April | 0.756356E+10 | 0.687527E+10 | 3547.56 | 01-APR-04:12 | 3224.73 | 3224.73 | 7.12 | 31.69 |
May | 0.690563E+10 | 0.627721E+10 | 3547.56 | 01-MAY-00:10 | 3224.73 | 3224.73 | 6.82 | 31.69 |
June | 0.852691E+10 | 0.775096E+10 | 3547.56 | 01-JUN-00:25 | 3224.73 | 3224.73 | 6.93 | 31.69 |
July | 0.883908E+10 | 0.803472E+10 | 3547.56 | 01-JUL-00:10 | 3224.73 | 3224.73 | 7.14 | 31.69 |
August | 0.879433E+10 | 0.799405E+10 | 3547.56 | 01-AUG-00:05 | 3224.73 | 3224.73 | 7.14 | 31.69 |
September | 0.702895E+10 | 0.638932E+10 | 3547.56 | 01-SEP-00:10 | 3224.73 | 3224.73 | 6.93 | 31.69 |
October | 0.583420E+10 | 0.530329E+10 | 3547.56 | 01-OCT-03:35 | 3224.73 | 3224.73 | 7.01 | 31.69 |
November | 0.429747E+10 | 0.390640E+10 | 3547.56 | 01-NOV-04:12 | 3224.73 | 3224.73 | 9.03 | 31.69 |
December | 0.353968E+10 | 0.321757E+10 | 3547.56 | 01-DEC-06:02 | 3224.73 | 3224.73 | 6.76 | 31.69 |
Annual Sum or Average | 0.724426E+11 | 0.658503E+11 | ||||||
Minimum of Months | 0.259915E+10 | 0.236263E+10 | 3547.56 | 3224.73 | 3224.73 | 6.74 | 31.69 | |
Maximum of Months | 0.883908E+10 | 0.803472E+10 | 3547.56 | 3224.73 | 3224.73 | 9.03 | 31.69 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 57470405.83 | 52240598.90 | 3547.56 | 27-JAN-14:30 | 3224.73 | 3224.73 | 14.66 | 15.85 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.135162E+09 | 0.122862E+09 | 3547.56 | 10-MAR-15:05 | 3224.73 | 3224.73 | 15.72 | 15.85 |
April | 0.161130E+10 | 0.146467E+10 | 3547.56 | 03-APR-09:55 | 3224.73 | 3224.73 | 11.21 | 31.69 |
May | 0.254360E+10 | 0.231213E+10 | 3547.56 | 01-MAY-10:20 | 3224.73 | 3224.73 | 14.61 | 15.85 |
June | 0.377708E+10 | 0.343337E+10 | 3547.56 | 01-JUN-07:20 | 3224.73 | 3224.73 | 15.92 | 15.85 |
July | 0.327430E+10 | 0.297634E+10 | 3547.56 | 01-JUL-09:50 | 3224.73 | 3224.73 | 14.31 | 15.85 |
August | 0.337015E+10 | 0.306346E+10 | 3547.56 | 01-AUG-05:02 | 3224.73 | 3224.73 | 13.93 | 31.69 |
September | 0.260391E+10 | 0.236695E+10 | 3547.56 | 01-SEP-05:07 | 3224.73 | 3224.73 | 15.92 | 15.85 |
October | 0.116250E+10 | 0.105671E+10 | 3547.56 | 02-OCT-07:20 | 3224.73 | 3224.73 | 15.78 | 15.85 |
November | 0.180925E+09 | 0.164461E+09 | 3547.56 | 01-NOV-12:05 | 3224.73 | 3224.73 | 11.09 | 31.69 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
Annual Sum or Average | 0.187164E+11 | 0.170132E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.377708E+10 | 0.343337E+10 | 3547.56 | 3224.73 | 3224.73 | 15.92 | 31.69 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.906735E+10 | 0.824222E+10 | 3385.36 | 01-JAN-00:05 | 3077.29 | 3077.29 | 18.69 | 14.28 |
February | 0.818987E+10 | 0.744459E+10 | 3385.36 | 01-FEB-00:10 | 3077.29 | 3077.29 | 19.53 | 14.28 |
March | 0.906735E+10 | 0.824222E+10 | 3385.36 | 01-MAR-00:10 | 3077.29 | 3077.29 | 19.96 | 14.28 |
April | 0.877486E+10 | 0.797635E+10 | 3385.36 | 01-APR-00:10 | 3077.29 | 3077.29 | 23.03 | 14.28 |
May | 0.906735E+10 | 0.824222E+10 | 3385.36 | 01-MAY-00:10 | 3077.29 | 3077.29 | 20.50 | 14.28 |
June | 0.877486E+10 | 0.797635E+10 | 3385.36 | 01-JUN-00:05 | 3077.29 | 3077.29 | 35.18 | 14.28 |
July | 0.906735E+10 | 0.824222E+10 | 3385.36 | 01-JUL-00:10 | 3077.29 | 3077.29 | 42.16 | 14.28 |
August | 0.906735E+10 | 0.824222E+10 | 3385.36 | 01-AUG-00:05 | 3077.29 | 3077.29 | 47.92 | 14.28 |
September | 0.877486E+10 | 0.797635E+10 | 3385.36 | 01-SEP-00:10 | 3077.29 | 3077.29 | 32.45 | 14.28 |
October | 0.906735E+10 | 0.824222E+10 | 3385.36 | 01-OCT-00:05 | 3077.29 | 3077.29 | 33.51 | 14.28 |
November | 0.877486E+10 | 0.797635E+10 | 3385.36 | 01-NOV-00:10 | 3077.29 | 3077.29 | 21.82 | 14.28 |
December | 0.906735E+10 | 0.824222E+10 | 3385.36 | 01-DEC-00:10 | 3077.29 | 3077.29 | 20.55 | 14.28 |
Annual Sum or Average | 0.106761E+12 | 0.970455E+11 | ||||||
Minimum of Months | 0.818987E+10 | 0.744459E+10 | 3385.36 | 3077.29 | 3077.29 | 18.69 | 14.28 | |
Maximum of Months | 0.906735E+10 | 0.824222E+10 | 3385.36 | 3077.29 | 3077.29 | 47.92 | 14.28 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.85 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.66 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.84 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.33 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.52 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.28 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.24 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.71 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.78 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.45 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.75 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.08 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.84 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.28 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.153000E+11 | 0.139077E+11 | 27128.20 | 27-JAN-15:50 | 24659.53 | 24659.53 | 25.72 | 110.66 |
February | 0.991064E+10 | 0.900877E+10 | 13546.66 | 28-FEB-16:30 | 12313.91 | 12313.91 | 24.06 | 55.33 |
March | 0.175018E+11 | 0.159091E+11 | 27129.56 | 20-MAR-15:10 | 24660.77 | 24660.77 | 25.78 | 110.66 |
April | 0.336409E+11 | 0.305796E+11 | 27136.49 | 24-APR-14:40 | 24667.07 | 24667.07 | 26.09 | 110.66 |
May | 0.341880E+11 | 0.310769E+11 | 27137.22 | 15-MAY-15:00 | 24667.73 | 24667.73 | 26.12 | 110.66 |
June | 0.457648E+11 | 0.416002E+11 | 27198.55 | 17-JUN-16:00 | 24723.48 | 24723.48 | 28.95 | 110.66 |
July | 0.453366E+11 | 0.412110E+11 | 27198.55 | 13-JUL-10:05 | 24723.48 | 24723.48 | 29.04 | 110.66 |
August | 0.458991E+11 | 0.417223E+11 | 27198.55 | 01-AUG-07:20 | 24723.48 | 24723.48 | 28.87 | 110.66 |
September | 0.357884E+11 | 0.325316E+11 | 27198.55 | 01-SEP-09:20 | 24723.48 | 24723.48 | 28.91 | 110.66 |
October | 0.261187E+11 | 0.237419E+11 | 27198.55 | 03-OCT-09:00 | 24723.48 | 24723.48 | 28.83 | 110.66 |
November | 0.168645E+11 | 0.153299E+11 | 27135.78 | 02-NOV-15:20 | 24666.42 | 24666.42 | 26.06 | 110.66 |
December | 0.134994E+11 | 0.122710E+11 | 13568.62 | 22-DEC-16:30 | 12333.88 | 12333.88 | 26.12 | 55.33 |
Annual Sum or Average | 0.339813E+12 | 0.308890E+12 | ||||||
Minimum of Months | 0.991064E+10 | 0.900877E+10 | 13546.66 | 12313.91 | 12313.91 | 24.06 | 55.33 | |
Maximum of Months | 0.458991E+11 | 0.417223E+11 | 27198.55 | 24723.48 | 24723.48 | 29.04 | 110.66 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 37.28 | 37.28 | 3151.26 | 902703.01 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 32.02 | 32.02 | 3768.11 | 796669.89 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 36.02 | 36.02 | 3210.18 | 907752.31 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.84 | 37.84 | 6.74 | 12554.17 | 21-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 37.06 | 37.06 | 0.00 | 0.44 | 23-MAY-04:12 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 37.06 | 37.06 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 37.06 | 37.06 | 0.00 | 0.32 | 03-JUL-04:42 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 37.06 | 37.06 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 37.06 | 37.06 | 0.00 | 2.98 | 02-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 37.06 | 37.06 | 562.89 | 149984.57 | 25-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 31.04 | 31.04 | 1790.31 | 830716.92 | 24-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 30.16 | 30.16 | 12726.93 | 1069997.90 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 2105.77 | ||||||
Minimum of Months | 0.00 | 0.00 | 30.16 | 30.16 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 37.84 | 37.84 | 12726.93 | 1069997.90 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 161657.33 | 1341433.94 | 27-JAN-16:30 | 16.82 | 9.31 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 57431.92 | 665932.49 | 22-FEB-14:05 | 11.72 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 153138.38 | 1470300.65 | 16-MAR-13:05 | 12.24 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 431295.42 | 1632436.42 | 11-APR-12:05 | 12.85 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 535741.29 | 1664857.70 | 26-MAY-12:05 | 12.97 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 729733.67 | 1807763.46 | 19-JUN-14:50 | 13.51 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 697961.20 | 2687421.11 | 14-JUL-05:03 | 16.83 | 8.31 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 710385.81 | 2027326.44 | 01-AUG-05:04 | 14.34 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 606915.28 | 1905258.24 | 05-SEP-07:50 | 13.88 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 340247.17 | 1608677.73 | 03-OCT-11:00 | 12.76 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 175388.80 | 1588161.59 | 20-NOV-15:05 | 12.68 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 91133.28 | 1020936.51 | 22-DEC-16:30 | 14.40 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 392619.96 | 0.00 | ||||||
Minimum of Months | 57431.92 | 665932.49 | 11.72 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 729733.67 | 2687421.11 | 16.83 | 9.31 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 160316.65 | 1350647.18 | 31-JAN-15:50 | 20.26 | 7.32 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56500.68 | 785835.56 | 22-FEB-14:05 | 17.56 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 151372.65 | 1480986.89 | 20-MAR-14:05 | 17.14 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 425551.07 | 1603978.24 | 25-APR-05:03 | 20.33 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 529409.21 | 1660917.01 | 08-MAY-04:12 | 21.69 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 723468.17 | 2300757.69 | 29-JUN-05:02 | 22.13 | 8.37 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 694465.05 | 3478188.33 | 18-JUL-05:03 | 19.82 | 7.62 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 708140.34 | 3288089.33 | 01-AUG-05:02 | 19.10 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 604292.96 | 3184019.67 | 05-SEP-03:02 | 19.06 | 12.68 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 337680.53 | 2969435.21 | 03-OCT-05:02 | 17.90 | 12.28 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 175043.22 | 2324825.40 | 02-NOV-14:30 | 15.88 | 11.39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 90031.26 | 1020350.94 | 22-DEC-16:30 | 19.98 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 389716.62 | 0.00 | ||||||
Minimum of Months | 56500.68 | 785835.56 | 15.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 723468.17 | 3478188.33 | 22.13 | 12.68 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 105430.88 | 851107.62 | 31-JAN-17:00 | 35.27 | 30.94 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 64306.87 | 444555.46 | 18-FEB-14:05 | 27.24 | 23.61 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 290381.36 | 1278508.36 | 16-MAR-16:00 | 43.57 | 33.42 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 944472.62 | 1732983.78 | 14-APR-16:10 | 52.26 | 40.46 | 0.00 | 0.00 | 01-APR-00:10 |
May | 622479.62 | 1286991.77 | 31-MAY-16:00 | 43.73 | 39.11 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1152588.61 | 1813924.02 | 28-JUN-16:00 | 53.80 | 45.74 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1390981.52 | 1943324.51 | 19-JUL-14:00 | 56.25 | 45.16 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1531044.52 | 2095725.04 | 27-AUG-14:05 | 59.11 | 46.08 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 727527.49 | 1366649.99 | 08-SEP-16:00 | 45.27 | 40.49 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 469254.51 | 1504605.97 | 01-OCT-14:00 | 47.91 | 40.43 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 290633.90 | 1287600.68 | 01-NOV-15:00 | 43.75 | 33.62 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 268947.71 | 1231991.49 | 25-DEC-16:00 | 42.67 | 31.21 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 658332.59 | 0.00 | ||||||
Minimum of Months | 64306.87 | 444555.46 | 27.24 | 23.61 | 0.00 | 0.00 | ||
Maximum of Months | 1531044.52 | 2095725.04 | 59.11 | 46.08 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.13 | 57.13 | 13395.14 | 44380.43 | 26-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.22 | 57.22 | 13350.47 | 44240.74 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.36 | 56.36 | 13472.76 | 43013.50 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.72 | 56.72 | 11814.36 | 39982.65 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.02 | 57.02 | 11167.63 | 36795.18 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.69 | 57.69 | 10551.93 | 33482.28 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.64 | 57.64 | 9445.13 | 31299.17 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.99 | 56.99 | 10335.99 | 32147.70 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.20 | 57.20 | 10381.55 | 34800.97 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 57.16 | 57.16 | 11268.88 | 38432.46 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.22 | 57.22 | 12383.29 | 41626.46 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.49 | 57.49 | 12739.23 | 43718.68 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11683.05 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.36 | 56.36 | 9445.13 | 31299.17 | ||
Maximum of Months | 0.00 | 0.00 | 57.69 | 57.69 | 13472.76 | 44380.43 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 186143.61 | 2137410.29 | 27-JAN-15:50 | 25.72 | 21.10 | 1011.19 | 97097.74 | 05-JAN-06:03 |
February | 66196.90 | 683801.20 | 28-FEB-16:30 | 24.06 | 21.10 | 1052.99 | 91190.04 | 01-FEB-08:07 |
March | 173671.18 | 2165089.26 | 20-MAR-15:10 | 25.78 | 21.10 | 1356.71 | 116540.28 | 25-MAR-05:50 |
April | 539438.75 | 2305957.59 | 24-APR-14:40 | 26.09 | 21.10 | 3555.75 | 90990.32 | 24-APR-05:20 |
May | 699421.31 | 2320823.97 | 15-MAY-15:00 | 26.12 | 21.54 | 322.81 | 59074.87 | 01-MAY-06:30 |
June | 1020316.73 | 3746351.90 | 28-JUN-16:00 | 29.20 | 24.96 | 531.18 | 64155.93 | 12-JUN-03:20 |
July | 1286901.33 | 4520988.90 | 18-JUL-05:05 | 30.87 | 26.24 | 380.19 | 86058.37 | 02-JUL-05:20 |
August | 1306517.36 | 4411163.42 | 16-AUG-10:30 | 30.64 | 26.45 | 358.89 | 56729.53 | 26-AUG-02:50 |
September | 1035973.63 | 4577185.89 | 01-SEP-12:30 | 31.00 | 26.59 | 21.51 | 28266.19 | 16-SEP-23:30 |
October | 470041.95 | 3614822.69 | 03-OCT-10:05 | 28.92 | 24.97 | 844.54 | 109269.53 | 25-OCT-05:50 |
November | 207172.49 | 2291573.90 | 02-NOV-15:20 | 26.06 | 21.62 | 1230.85 | 92542.69 | 27-NOV-20:00 |
December | 103983.18 | 1161117.63 | 22-DEC-16:30 | 26.12 | 21.10 | 1981.26 | 121180.37 | 14-DEC-06:40 |
Annual Sum or Average | 594431.89 | 1050.92 | ||||||
Minimum of Months | 66196.90 | 683801.20 | 24.06 | 21.10 | 21.51 | 28266.19 | ||
Maximum of Months | 1306517.36 | 4577185.89 | 31.00 | 26.59 | 3555.75 | 121180.37 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.142168E+09 | 0.00 | 0.383798E+11 | 0.559368E+10 | 0.00 | 0.00 |
February | 0.208214E+09 | 0.00 | 0.103346E+11 | 0.502638E+10 | 0.00 | 0.00 |
March | 0.262883E+09 | 0.00 | 0.420305E+11 | 0.771945E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.109042E+12 | 0.125788E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.118971E+12 | 0.113825E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.161754E+12 | 0.142224E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.169378E+12 | 0.146667E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.188241E+12 | 0.174488E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.133737E+12 | 0.107311E+11 | 0.00 | 0.00 |
October | 30612625.29 | 0.00 | 0.817812E+11 | 0.886966E+10 | 0.00 | 0.00 |
November | 50392143.45 | 0.00 | 0.444422E+11 | 0.741254E+10 | 0.00 | 0.00 |
December | 0.848693E+09 | 0.00 | 0.281142E+11 | 0.657139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.154296E+10 | 0.00 | 0.112621E+13 | 0.122223E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.103346E+11 | 0.502638E+10 | 0.00 | 0.00 |
Maximum of Months | 0.848693E+09 | 0.00 | 0.188241E+12 | 0.174488E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.567928E+10 | 0.00 | 0.323851E+12 | 0.370334E+11 | 0.00 | 0.00 |
February | 0.618259E+10 | 0.00 | 0.117458E+12 | 0.303257E+11 | 0.00 | 0.00 |
March | 0.638368E+10 | 0.00 | 0.302944E+12 | 0.440628E+11 | 0.00 | 0.00 |
April | 12274217.03 | 0.00 | 0.817647E+12 | 0.785200E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.107128E+13 | 0.958959E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143809E+13 | 0.118127E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.138268E+13 | 0.106299E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.139432E+13 | 0.109318E+12 | 0.00 | 0.00 |
September | 3475.45 | 0.00 | 0.115739E+13 | 0.860053E+11 | 0.00 | 0.00 |
October | 0.105161E+10 | 0.00 | 0.671412E+12 | 0.596141E+11 | 0.00 | 0.00 |
November | 0.300755E+10 | 0.00 | 0.327562E+12 | 0.407093E+11 | 0.00 | 0.00 |
December | 0.261841E+11 | 0.00 | 0.184411E+12 | 0.322501E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.485010E+11 | 0.00 | 0.918905E+13 | 0.838161E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.117458E+12 | 0.303257E+11 | 0.00 | 0.00 |
Maximum of Months | 0.261841E+11 | 0.00 | 0.143809E+13 | 0.118127E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.274762E+10 | 0.00 | 0.265404E+11 | 0.322779E+10 | 0.00 | 0.00 |
February | 0.277467E+10 | 0.00 | 0.546916E+10 | 0.258526E+10 | 0.00 | 0.00 |
March | 0.202484E+10 | 0.00 | 0.279167E+11 | 0.368955E+10 | 0.00 | 0.00 |
April | 12298058.76 | 0.00 | 0.895349E+11 | 0.771307E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.118803E+12 | 0.973295E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.164382E+12 | 0.130275E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.157601E+12 | 0.116257E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.156140E+12 | 0.117697E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.125669E+12 | 0.882583E+10 | 0.00 | 0.00 |
October | 0.492963E+09 | 0.00 | 0.672157E+11 | 0.539392E+10 | 0.00 | 0.00 |
November | 0.163422E+10 | 0.00 | 0.268978E+11 | 0.338979E+10 | 0.00 | 0.00 |
December | 0.739168E+10 | 0.00 | 0.117466E+11 | 0.281693E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.170783E+11 | 0.00 | 0.977917E+12 | 0.837979E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.546916E+10 | 0.258526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.739168E+10 | 0.00 | 0.164382E+12 | 0.130275E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 562.13 | 0.00 | 0.229053E+11 | 0.143057E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.379554E+10 | 0.123778E+11 | 0.00 | 0.00 |
March | 390.71 | 0.00 | 0.220022E+11 | 0.143932E+11 | 0.00 | 0.00 |
April | 1325.67 | 0.00 | 0.549588E+11 | 0.135273E+11 | 0.00 | 0.00 |
May | 862.72 | 0.00 | 0.676502E+11 | 0.142412E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.828312E+11 | 0.142061E+11 | 0.00 | 0.00 |
July | 107.31 | 0.00 | 0.895745E+11 | 0.149931E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.100648E+12 | 0.162920E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.852160E+11 | 0.152034E+11 | 0.00 | 0.00 |
October | 767.87 | 0.00 | 0.532275E+11 | 0.153840E+11 | 0.00 | 0.00 |
November | 597.94 | 0.00 | 0.281222E+11 | 0.145918E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.122860E+11 | 0.147762E+11 | 0.00 | 0.00 |
Annual Sum or Average | 4614.34 | 0.00 | 0.623217E+12 | 0.174292E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.379554E+10 | 0.123778E+11 | 0.00 | 0.00 |
Maximum of Months | 1325.67 | 0.00 | 0.100648E+12 | 0.162920E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.399699E+11 | 0.302219E+12 | 0.00 | 69.88 |
February | 0.00 | 0.00 | 0.152008E+11 | 0.190823E+12 | 0.00 | 34.39 |
March | 0.00 | 0.00 | 0.251105E+12 | 0.352630E+12 | 0.00 | 71.22 |
April | 0.00 | 0.00 | 0.889963E+12 | 0.573195E+12 | 0.00 | 94.76 |
May | 0.00 | 0.00 | 0.292016E+12 | 0.318695E+12 | 0.00 | 52.01 |
June | 0.00 | 0.00 | 0.702613E+12 | 0.351588E+12 | 0.00 | 24.74 |
July | 0.00 | 0.00 | 0.114919E+13 | 0.403231E+12 | 0.00 | 7.48 |
August | 0.00 | 0.00 | 0.138790E+13 | 0.471242E+12 | 0.00 | 16.01 |
September | 0.00 | 0.00 | 0.351073E+12 | 0.205260E+12 | 0.00 | 7.21 |
October | 0.00 | 0.00 | 0.330179E+12 | 0.339799E+12 | 0.00 | 58.38 |
November | 0.00 | 0.00 | 0.261555E+12 | 0.333202E+12 | 0.00 | 64.88 |
December | 0.00 | 0.00 | 0.263689E+12 | 0.426967E+12 | 0.00 | 97.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.593446E+13 | 0.426885E+13 | 0.00 | 598.65 |
Minimum of Months | 0.00 | 0.00 | 0.152008E+11 | 0.190823E+12 | 0.00 | 7.21 |
Maximum of Months | 0.00 | 0.00 | 0.138790E+13 | 0.573195E+12 | 0.00 | 97.68 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.663421E+10 | 0.280558E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112410E+11 | 0.332641E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.190671E+11 | 0.495456E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.252993E+11 | 0.689268E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.818607E+10 | 0.350855E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149881E+11 | 0.535653E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220100E+11 | 0.691674E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278734E+11 | 0.812052E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.806435E+10 | 0.335150E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.138650E+11 | 0.436911E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.186817E+11 | 0.484122E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.249084E+11 | 0.591103E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200819E+12 | 0.603545E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.663421E+10 | 0.280558E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278734E+11 | 0.812052E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.515025E+11 | 0.246730E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.961017E+11 | 0.299597E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.173997E+12 | 0.460521E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.239779E+12 | 0.656206E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.761725E+11 | 0.330850E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.142785E+12 | 0.510777E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.209420E+12 | 0.658872E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.263252E+12 | 0.771057E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.746107E+11 | 0.314980E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126841E+12 | 0.407495E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.169134E+12 | 0.447621E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223687E+12 | 0.542994E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184728E+13 | 0.564770E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.515025E+11 | 0.246730E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.263252E+12 | 0.771057E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.399427E+10 | 0.229140E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.838778E+10 | 0.282853E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166290E+11 | 0.452538E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241035E+11 | 0.664926E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.772270E+10 | 0.337707E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.145452E+11 | 0.521570E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212326E+11 | 0.670181E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.266344E+11 | 0.783511E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.760804E+10 | 0.322144E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122719E+11 | 0.404723E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159077E+11 | 0.435491E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.207300E+11 | 0.521763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179767E+12 | 0.562655E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.399427E+10 | 0.229140E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266344E+11 | 0.783511E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.559368E+10 | 0.383798E+11 | 0.142168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502638E+10 | 0.103346E+11 | 0.208214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771945E+10 | 0.420305E+11 | 0.262883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125788E+11 | 0.109042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113825E+11 | 0.118971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142224E+11 | 0.161754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146667E+11 | 0.169378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174488E+11 | 0.188241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107311E+11 | 0.133737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886966E+10 | 0.817812E+11 | 30612625.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.741254E+10 | 0.444422E+11 | 50392143.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.657139E+10 | 0.281142E+11 | 0.848693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122223E+12 | 0.112621E+13 | 0.154296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.502638E+10 | 0.103346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174488E+11 | 0.188241E+12 | 0.848693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.370334E+11 | 0.323851E+12 | 0.567928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303257E+11 | 0.117458E+12 | 0.618259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440628E+11 | 0.302944E+12 | 0.638368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.785200E+11 | 0.817647E+12 | 12274217.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.958959E+11 | 0.107128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118127E+12 | 0.143809E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106299E+12 | 0.138268E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109318E+12 | 0.139432E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.860053E+11 | 0.115739E+13 | 3475.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.596141E+11 | 0.671412E+12 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407093E+11 | 0.327562E+12 | 0.300755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322501E+11 | 0.184411E+12 | 0.261841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.838161E+12 | 0.918905E+13 | 0.485010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303257E+11 | 0.117458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118127E+12 | 0.143809E+13 | 0.261841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.322779E+10 | 0.265404E+11 | 0.274762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258526E+10 | 0.546916E+10 | 0.277467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368955E+10 | 0.279167E+11 | 0.202484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771307E+10 | 0.895349E+11 | 12298058.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.973295E+10 | 0.118803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130275E+11 | 0.164382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116257E+11 | 0.157601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117697E+11 | 0.156140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.882583E+10 | 0.125669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539392E+10 | 0.672157E+11 | 0.492963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338979E+10 | 0.268978E+11 | 0.163422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281693E+10 | 0.117466E+11 | 0.739168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.837979E+11 | 0.977917E+12 | 0.170783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258526E+10 | 0.546916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130275E+11 | 0.164382E+12 | 0.739168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143057E+11 | 0.229053E+11 | 562.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123778E+11 | 0.379554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143932E+11 | 0.220022E+11 | 390.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135273E+11 | 0.549588E+11 | 1325.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142412E+11 | 0.676502E+11 | 862.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142061E+11 | 0.828312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149931E+11 | 0.895745E+11 | 107.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162920E+11 | 0.100648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152034E+11 | 0.852160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153840E+11 | 0.532275E+11 | 767.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145918E+11 | 0.281222E+11 | 597.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147762E+11 | 0.122860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174292E+12 | 0.623217E+12 | 4614.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123778E+11 | 0.379554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162920E+11 | 0.100648E+12 | 1325.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.103261E+12 | 0.288478E+11 | 0.00 | 0.00 | 0.00 | 0.186995E+12 | 0.00 | 0.00 |
February | 0.932679E+11 | 0.101054E+11 | 0.00 | 0.00 | 0.00 | 0.920452E+11 | 0.00 | 0.00 |
March | 0.103261E+12 | 0.193188E+12 | 0.00 | 0.00 | 0.00 | 0.190594E+12 | 0.00 | 0.00 |
April | 0.999299E+11 | 0.671426E+12 | 0.00 | 0.00 | 0.00 | 0.253587E+12 | 0.00 | 0.00 |
May | 0.103261E+12 | 0.216396E+12 | 0.00 | 0.00 | 0.00 | 0.139188E+12 | 0.00 | 0.00 |
June | 0.999299E+11 | 0.517468E+12 | 0.00 | 0.00 | 0.00 | 0.662153E+11 | 0.00 | 0.00 |
July | 0.103261E+12 | 0.869345E+12 | 0.00 | 0.00 | 0.00 | 0.200306E+11 | 0.00 | 0.00 |
August | 0.103261E+12 | 0.106296E+13 | 0.00 | 0.00 | 0.00 | 0.428517E+11 | 0.00 | 0.00 |
September | 0.999299E+11 | 0.265133E+12 | 0.00 | 0.00 | 0.00 | 0.193036E+11 | 0.00 | 0.00 |
October | 0.103261E+12 | 0.250565E+12 | 0.00 | 0.00 | 0.00 | 0.156220E+12 | 0.00 | 0.00 |
November | 0.999299E+11 | 0.202691E+12 | 0.00 | 0.00 | 0.00 | 0.173627E+12 | 0.00 | 0.00 |
December | 0.103261E+12 | 0.202559E+12 | 0.00 | 0.00 | 0.00 | 0.261400E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.121581E+13 | 0.449069E+13 | 0.00 | 0.00 | 0.00 | 0.160206E+13 | 0.00 | 0.00 |
Minimum of Months | 0.932679E+11 | 0.101054E+11 | 0.00 | 0.00 | 0.00 | 0.193036E+11 | 0.00 | 0.00 |
Maximum of Months | 0.103261E+12 | 0.106296E+13 | 0.00 | 0.00 | 0.00 | 0.261400E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151789E+10 | 0.534652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137100E+10 | 0.928562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151789E+10 | 0.156304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146893E+10 | 0.198755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151789E+10 | 0.619541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146893E+10 | 0.111005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151789E+10 | 0.166112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151789E+10 | 0.212708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146893E+10 | 0.618177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151789E+10 | 0.110138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146893E+10 | 0.153094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151789E+10 | 0.205152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178719E+11 | 0.158336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137100E+10 | 0.534652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151789E+10 | 0.212708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144924E+11 | 0.413219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130900E+11 | 0.792320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144924E+11 | 0.142437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140250E+11 | 0.188183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144924E+11 | 0.575800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140250E+11 | 0.105732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144924E+11 | 0.158025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144924E+11 | 0.200639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140250E+11 | 0.571376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144924E+11 | 0.100584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140250E+11 | 0.138396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144924E+11 | 0.183880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170637E+12 | 0.145315E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130900E+11 | 0.413219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144924E+11 | 0.200639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148332E+10 | 0.318619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133977E+10 | 0.689903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148332E+10 | 0.135869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143547E+10 | 0.188898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148332E+10 | 0.582896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143547E+10 | 0.107650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148332E+10 | 0.160141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148332E+10 | 0.202826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143547E+10 | 0.582207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148332E+10 | 0.970800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143547E+10 | 0.129882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148332E+10 | 0.169957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174649E+11 | 0.140966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133977E+10 | 0.318619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148332E+10 | 0.202826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.559368E+10 | 0.142168E+09 | 0.383798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502638E+10 | 0.208214E+09 | 0.103346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771945E+10 | 0.262883E+09 | 0.420305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125788E+11 | 0.00 | 0.109042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113825E+11 | 0.00 | 0.118971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142224E+11 | 0.00 | 0.161754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146667E+11 | 0.00 | 0.169378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174488E+11 | 0.00 | 0.188241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107311E+11 | 0.00 | 0.133737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886966E+10 | 30612625.29 | 0.817812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.741254E+10 | 50392143.45 | 0.444422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.657139E+10 | 0.848693E+09 | 0.281142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122223E+12 | 0.154296E+10 | 0.112621E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.502638E+10 | 0.00 | 0.103346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174488E+11 | 0.848693E+09 | 0.188241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.370334E+11 | 0.567928E+10 | 0.323851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303257E+11 | 0.618259E+10 | 0.117458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440628E+11 | 0.638368E+10 | 0.302944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.785200E+11 | 12274217.03 | 0.817647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.958959E+11 | 0.00 | 0.107128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118127E+12 | 0.00 | 0.143809E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106299E+12 | 0.00 | 0.138268E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109318E+12 | 0.00 | 0.139432E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.860053E+11 | 3475.45 | 0.115739E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.596141E+11 | 0.105161E+10 | 0.671412E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407093E+11 | 0.300755E+10 | 0.327562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322501E+11 | 0.261841E+11 | 0.184411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.838161E+12 | 0.485010E+11 | 0.918905E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303257E+11 | 0.00 | 0.117458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118127E+12 | 0.261841E+11 | 0.143809E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.322779E+10 | 0.274762E+10 | 0.265404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258526E+10 | 0.277467E+10 | 0.546916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368955E+10 | 0.202484E+10 | 0.279167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771307E+10 | 12298058.76 | 0.895349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.973295E+10 | 0.00 | 0.118803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130275E+11 | 0.00 | 0.164382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116257E+11 | 0.00 | 0.157601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117697E+11 | 0.00 | 0.156140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.882583E+10 | 0.00 | 0.125669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539392E+10 | 0.492963E+09 | 0.672157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338979E+10 | 0.163422E+10 | 0.268978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281693E+10 | 0.739168E+10 | 0.117466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.837979E+11 | 0.170783E+11 | 0.977917E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258526E+10 | 0.00 | 0.546916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130275E+11 | 0.739168E+10 | 0.164382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143057E+11 | 562.13 | 0.229053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123778E+11 | 0.00 | 0.379554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143932E+11 | 390.71 | 0.220022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135273E+11 | 1325.67 | 0.549588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142412E+11 | 862.72 | 0.676502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142061E+11 | 0.00 | 0.828312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149931E+11 | 107.31 | 0.895745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162920E+11 | 0.00 | 0.100648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152034E+11 | 0.00 | 0.852160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153840E+11 | 767.87 | 0.532275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145918E+11 | 597.94 | 0.281222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147762E+11 | 0.00 | 0.122860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174292E+12 | 4614.34 | 0.623217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123778E+11 | 0.00 | 0.379554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162920E+11 | 1325.67 | 0.100648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.103261E+12 | 0.00 | 0.399699E+11 | 0.00 | 0.111221E+11 | 0.00 | 0.00 | 0.00 | 0.187836E+12 | 0.00 | 0.00 | 0.00 |
February | 0.932679E+11 | 0.00 | 0.152008E+11 | 0.00 | 0.509544E+10 | 0.00 | 0.00 | 0.00 | 0.924595E+11 | 0.00 | 0.00 | 0.00 |
March | 0.103261E+12 | 0.00 | 0.251105E+12 | 0.00 | 0.579176E+11 | 0.00 | 0.00 | 0.00 | 0.191451E+12 | 0.00 | 0.00 | 0.00 |
April | 0.999299E+11 | 0.00 | 0.889963E+12 | 0.00 | 0.218537E+12 | 0.00 | 0.00 | 0.00 | 0.254728E+12 | 0.00 | 0.00 | 0.00 |
May | 0.103261E+12 | 0.00 | 0.292016E+12 | 0.00 | 0.756200E+11 | 0.00 | 0.00 | 0.00 | 0.139815E+12 | 0.00 | 0.00 | 0.00 |
June | 0.999299E+11 | 0.00 | 0.702613E+12 | 0.00 | 0.185145E+12 | 0.00 | 0.00 | 0.00 | 0.665134E+11 | 0.00 | 0.00 | 0.00 |
July | 0.103261E+12 | 0.00 | 0.114919E+13 | 0.00 | 0.279849E+12 | 0.00 | 0.00 | 0.00 | 0.201208E+11 | 0.00 | 0.00 | 0.00 |
August | 0.103261E+12 | 0.00 | 0.138790E+13 | 0.00 | 0.324937E+12 | 0.00 | 0.00 | 0.00 | 0.430446E+11 | 0.00 | 0.00 | 0.00 |
September | 0.999299E+11 | 0.00 | 0.351073E+12 | 0.00 | 0.859399E+11 | 0.00 | 0.00 | 0.00 | 0.193905E+11 | 0.00 | 0.00 | 0.00 |
October | 0.103261E+12 | 0.00 | 0.330179E+12 | 0.00 | 0.796146E+11 | 0.00 | 0.00 | 0.00 | 0.156923E+12 | 0.00 | 0.00 | 0.00 |
November | 0.999299E+11 | 0.00 | 0.261555E+12 | 0.00 | 0.588637E+11 | 0.00 | 0.00 | 0.00 | 0.174409E+12 | 0.00 | 0.00 | 0.00 |
December | 0.103261E+12 | 0.00 | 0.263689E+12 | 0.00 | 0.611295E+11 | 0.00 | 0.00 | 0.00 | 0.262577E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121581E+13 | 0.00 | 0.593446E+13 | 0.00 | 0.144377E+13 | 0.00 | 0.00 | 0.00 | 0.160927E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.932679E+11 | 0.00 | 0.152008E+11 | 0.00 | 0.509544E+10 | 0.00 | 0.00 | 0.00 | 0.193905E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103261E+12 | 0.00 | 0.138790E+13 | 0.00 | 0.324937E+12 | 0.00 | 0.00 | 0.00 | 0.262577E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151789E+10 | 0.00 | 0.663421E+10 | 0.00 | 0.128769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137100E+10 | 0.00 | 0.112410E+11 | 0.00 | 0.195541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151789E+10 | 0.00 | 0.190671E+11 | 0.00 | 0.343667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146893E+10 | 0.00 | 0.252993E+11 | 0.00 | 0.542376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151789E+10 | 0.00 | 0.818607E+10 | 0.00 | 0.199066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146893E+10 | 0.00 | 0.149881E+11 | 0.00 | 0.388761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151789E+10 | 0.00 | 0.220100E+11 | 0.00 | 0.539885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151789E+10 | 0.00 | 0.278734E+11 | 0.00 | 0.660263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146893E+10 | 0.00 | 0.806435E+10 | 0.00 | 0.188258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151789E+10 | 0.00 | 0.138650E+11 | 0.00 | 0.285122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146893E+10 | 0.00 | 0.186817E+11 | 0.00 | 0.337229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151789E+10 | 0.00 | 0.249084E+11 | 0.00 | 0.439314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178719E+11 | 0.00 | 0.200819E+12 | 0.00 | 0.424825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137100E+10 | 0.00 | 0.663421E+10 | 0.00 | 0.128769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151789E+10 | 0.00 | 0.278734E+11 | 0.00 | 0.660263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144924E+11 | 0.00 | 0.515025E+11 | 0.00 | 0.101805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130900E+11 | 0.00 | 0.961017E+11 | 0.00 | 0.168697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144924E+11 | 0.00 | 0.173997E+12 | 0.00 | 0.315596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140250E+11 | 0.00 | 0.239779E+12 | 0.00 | 0.515956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144924E+11 | 0.00 | 0.761725E+11 | 0.00 | 0.185925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140250E+11 | 0.00 | 0.142785E+12 | 0.00 | 0.370527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144924E+11 | 0.00 | 0.209420E+12 | 0.00 | 0.513948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144924E+11 | 0.00 | 0.263252E+12 | 0.00 | 0.626132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140250E+11 | 0.00 | 0.746107E+11 | 0.00 | 0.174730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144924E+11 | 0.00 | 0.126841E+12 | 0.00 | 0.262571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140250E+11 | 0.00 | 0.169134E+12 | 0.00 | 0.307371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144924E+11 | 0.00 | 0.223687E+12 | 0.00 | 0.398070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170637E+12 | 0.00 | 0.184728E+13 | 0.00 | 0.394133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130900E+11 | 0.00 | 0.515025E+11 | 0.00 | 0.101805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144924E+11 | 0.00 | 0.263252E+12 | 0.00 | 0.626132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148332E+10 | 0.00 | 0.399427E+10 | 0.00 | 0.808074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133977E+10 | 0.00 | 0.838778E+10 | 0.00 | 0.148875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148332E+10 | 0.00 | 0.166290E+11 | 0.00 | 0.304206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143547E+10 | 0.00 | 0.241035E+11 | 0.00 | 0.521379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148332E+10 | 0.00 | 0.772270E+10 | 0.00 | 0.189375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143547E+10 | 0.00 | 0.145452E+11 | 0.00 | 0.378022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148332E+10 | 0.00 | 0.212326E+11 | 0.00 | 0.521849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148332E+10 | 0.00 | 0.266344E+11 | 0.00 | 0.635179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143547E+10 | 0.00 | 0.760804E+10 | 0.00 | 0.178596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148332E+10 | 0.00 | 0.122719E+11 | 0.00 | 0.256391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143547E+10 | 0.00 | 0.159077E+11 | 0.00 | 0.291944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148332E+10 | 0.00 | 0.207300E+11 | 0.00 | 0.373431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174649E+11 | 0.00 | 0.179767E+12 | 0.00 | 0.388006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133977E+10 | 0.00 | 0.399427E+10 | 0.00 | 0.808074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148332E+10 | 0.00 | 0.266344E+11 | 0.00 | 0.635179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243911E+09 | 23415525.84 | 0.00 | 0.118249E+09 | 164716.77 | 0.00 | 0.481955E+11 | 0.00 | 1.19 |
February | 0.212471E+09 | 0.00 | 0.00 | 97111772.92 | 0.00 | 0.00 | 0.559688E+11 | 0.00 | 1.14 |
March | 0.143556E+09 | 33785415.77 | 0.00 | 0.108413E+09 | 1046219.53 | 0.00 | 0.484842E+11 | 0.00 | 1.24 |
April | 37635491.11 | 0.241418E+10 | 0.00 | 70936979.79 | 0.118112E+09 | 0.00 | 0.172993E+11 | 0.00 | 0.78 |
May | 38260558.47 | 0.508817E+10 | 0.00 | 47686851.65 | 0.112569E+09 | 0.00 | 0.869133E+10 | 0.00 | 0.62 |
June | 30725307.87 | 0.129411E+11 | 0.00 | 19997680.45 | 0.192623E+09 | 0.00 | 0.271238E+10 | 0.00 | 0.51 |
July | 20628741.84 | 0.127605E+11 | 0.00 | 11936672.45 | 0.233779E+09 | 0.00 | 0.126658E+10 | 0.00 | 0.44 |
August | 29262507.78 | 0.128500E+11 | 0.00 | 22542658.19 | 0.169941E+09 | 0.00 | 0.175934E+10 | 0.00 | 0.55 |
September | 53578888.27 | 0.925076E+10 | 0.00 | 36623336.85 | 0.188454E+09 | 0.00 | 0.450391E+10 | 0.00 | 0.65 |
October | 0.200280E+09 | 0.206405E+10 | 0.00 | 98744602.33 | 27842339.89 | 0.00 | 0.310357E+11 | 0.00 | 1.04 |
November | 0.275449E+09 | 0.235179E+09 | 0.00 | 0.131215E+09 | 0.00 | 0.00 | 0.507327E+11 | 0.00 | 1.28 |
December | 0.354331E+09 | 1265593.22 | 0.00 | 0.137093E+09 | 0.00 | 0.00 | 0.638187E+11 | 0.00 | 1.19 |
Annual Sum or Average | 0.164009E+10 | 0.576625E+11 | 0.00 | 0.900550E+09 | 0.104453E+10 | 0.00 | 0.334468E+12 | 0.00 | 0.89 |
Minimum of Months | 20628741.84 | 0.00 | 0.00 | 11936672.45 | 0.00 | 0.00 | 0.126658E+10 | 0.00 | 0.44 |
Maximum of Months | 0.354331E+09 | 0.129411E+11 | 0.00 | 0.137093E+09 | 0.233779E+09 | 0.00 | 0.638187E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185651E+10 | 1929018.03 | 0.00 | 86226976.58 | 23497360.62 | 0.00 | 0.301584E+11 | 0.00 | 0.71 |
February | 0.183304E+10 | 0.00 | 0.00 | 78178911.74 | 0.00 | 0.00 | 0.399664E+11 | 0.00 | 0.77 |
March | 0.211964E+10 | 11157412.38 | 0.00 | 98836488.43 | 634599.96 | 0.00 | 0.364887E+11 | 0.00 | 0.86 |
April | 0.605738E+10 | 0.114324E+10 | 0.00 | 65384649.47 | 0.211209E+09 | 0.00 | 0.136946E+11 | 0.00 | 0.75 |
May | 0.101504E+10 | 0.256622E+10 | 0.00 | 41988612.66 | 0.170787E+09 | 0.00 | 0.622576E+10 | 0.00 | 0.47 |
June | 0.159901E+10 | 0.772113E+10 | 0.00 | 11292889.85 | 0.336897E+09 | 0.00 | 0.130115E+10 | 0.00 | 0.39 |
July | 0.867245E+09 | 0.941873E+10 | 0.00 | 5585530.85 | 0.145681E+10 | 0.00 | 0.493865E+09 | 0.00 | 0.36 |
August | 0.112774E+10 | 0.949455E+10 | 0.00 | 14496528.82 | 0.676727E+09 | 0.00 | 0.910392E+09 | 0.00 | 0.47 |
September | 0.225587E+09 | 0.596055E+10 | 0.00 | 28172224.31 | 0.976424E+09 | 0.00 | 0.272971E+10 | 0.00 | 0.45 |
October | 0.156262E+10 | 0.125999E+10 | 0.00 | 73033526.47 | 0.172069E+09 | 0.00 | 0.215921E+11 | 0.00 | 0.71 |
November | 0.221303E+10 | 69349234.03 | 0.00 | 0.100609E+09 | 28029967.58 | 0.00 | 0.344258E+11 | 0.00 | 0.86 |
December | 0.227871E+10 | 76040.19 | 0.00 | 0.102639E+09 | 1517721.94 | 0.00 | 0.415364E+11 | 0.00 | 0.75 |
Annual Sum or Average | 0.227556E+11 | 0.376469E+11 | 0.00 | 0.706445E+09 | 0.405460E+10 | 0.00 | 0.229523E+12 | 0.00 | 0.63 |
Minimum of Months | 0.225587E+09 | 0.00 | 0.00 | 5585530.85 | 0.00 | 0.00 | 0.493865E+09 | 0.00 | 0.36 |
Maximum of Months | 0.605738E+10 | 0.949455E+10 | 0.00 | 0.102639E+09 | 0.145681E+10 | 0.00 | 0.415364E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.312752E+11 | 0.00 | 0.00 | 0.505175E+09 | 0.333906E+09 | 0.00 | 0.180607E+12 | 0.00 | 0.47 |
February | 0.442127E+11 | 0.00 | 0.00 | 0.412123E+09 | 0.00 | 0.00 | 0.220791E+12 | 0.00 | 0.48 |
March | 0.225120E+11 | 95319102.93 | 0.00 | 0.599701E+09 | 17177022.04 | 0.00 | 0.239765E+12 | 0.00 | 0.59 |
April | 0.111294E+11 | 0.121817E+11 | 0.00 | 0.483238E+09 | 0.194063E+10 | 0.00 | 0.979501E+11 | 0.00 | 0.49 |
May | 0.549578E+10 | 0.268821E+11 | 0.00 | 0.341371E+09 | 0.145457E+10 | 0.00 | 0.483224E+11 | 0.00 | 0.41 |
June | 0.466074E+10 | 0.775991E+11 | 0.00 | 0.110590E+09 | 0.253408E+10 | 0.00 | 0.131596E+11 | 0.00 | 0.32 |
July | 0.240991E+10 | 0.884301E+11 | 0.00 | 39771224.65 | 0.389566E+10 | 0.00 | 0.414561E+10 | 0.00 | 0.28 |
August | 0.237723E+10 | 0.831159E+11 | 0.00 | 93382924.68 | 0.316887E+10 | 0.00 | 0.789157E+10 | 0.00 | 0.34 |
September | 0.144840E+10 | 0.570120E+11 | 0.00 | 0.215770E+09 | 0.524583E+10 | 0.00 | 0.216124E+11 | 0.00 | 0.38 |
October | 0.839945E+10 | 0.127465E+11 | 0.00 | 0.499850E+09 | 0.876123E+09 | 0.00 | 0.146234E+12 | 0.00 | 0.51 |
November | 0.271552E+11 | 0.415565E+09 | 0.00 | 0.573669E+09 | 0.241549E+09 | 0.00 | 0.199293E+12 | 0.00 | 0.53 |
December | 0.644975E+11 | 1775780.61 | 0.00 | 0.406802E+09 | 1140635.04 | 0.00 | 0.193623E+12 | 0.00 | 0.43 |
Annual Sum or Average | 0.225574E+12 | 0.358480E+12 | 0.00 | 0.428144E+10 | 0.197095E+11 | 0.00 | 0.137340E+13 | 0.00 | 0.44 |
Minimum of Months | 0.144840E+10 | 0.00 | 0.00 | 39771224.65 | 0.00 | 0.00 | 0.414561E+10 | 0.00 | 0.28 |
Maximum of Months | 0.644975E+11 | 0.884301E+11 | 0.00 | 0.599701E+09 | 0.524583E+10 | 0.00 | 0.239765E+12 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.871782E+10 | 0.00 | 0.00 | 22208766.44 | 21042944.22 | 0.103423E+09 | 0.842785E+10 | 0.00 | 0.45 |
February | 0.103996E+11 | 0.00 | 0.00 | 16903826.42 | 0.00 | 44455951.52 | 0.126513E+11 | 0.00 | 0.45 |
March | 0.731247E+10 | 2607132.43 | 0.00 | 35290561.60 | 443709.03 | 1168629.89 | 0.140027E+11 | 0.00 | 0.52 |
April | 0.170077E+10 | 0.785978E+09 | 0.00 | 47509330.57 | 0.186706E+09 | 0.00 | 0.693736E+10 | 0.00 | 0.46 |
May | 0.492272E+09 | 0.198378E+10 | 0.00 | 37982144.50 | 0.126089E+09 | 0.00 | 0.353446E+10 | 0.00 | 0.38 |
June | 0.509102E+09 | 0.684439E+10 | 0.00 | 9483209.04 | 0.227528E+09 | 0.00 | 0.969580E+09 | 0.00 | 0.32 |
July | 0.268826E+09 | 0.811168E+10 | 0.00 | 4073420.56 | 0.413529E+09 | 0.00 | 0.317417E+09 | 0.00 | 0.29 |
August | 0.220827E+09 | 0.747551E+10 | 0.00 | 8290928.25 | 0.305831E+09 | 0.00 | 0.571774E+09 | 0.00 | 0.33 |
September | 0.179351E+09 | 0.500654E+10 | 0.00 | 22429537.56 | 0.592840E+09 | 0.00 | 0.164880E+10 | 0.00 | 0.37 |
October | 0.283949E+10 | 0.101117E+10 | 0.00 | 35728646.07 | 99898650.16 | 0.00 | 0.916648E+10 | 0.00 | 0.45 |
November | 0.749207E+10 | 29802476.23 | 0.00 | 30775912.83 | 30759771.99 | 1824886.67 | 0.114552E+11 | 0.00 | 0.49 |
December | 0.144111E+11 | 0.00 | 0.00 | 10575354.87 | 5370638.02 | 0.111819E+09 | 0.623153E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.545437E+11 | 0.312515E+11 | 0.00 | 0.281252E+09 | 0.201004E+10 | 0.262691E+09 | 0.759144E+11 | 0.00 | 0.41 |
Minimum of Months | 0.179351E+09 | 0.00 | 0.00 | 4073420.56 | 0.00 | 0.00 | 0.317417E+09 | 0.00 | 0.29 |
Maximum of Months | 0.144111E+11 | 0.811168E+10 | 0.00 | 47509330.57 | 0.592840E+09 | 0.111819E+09 | 0.140027E+11 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147147E+10 | 233549.38 | 0.00 | 4010416.46 | 2958129.84 | 0.00 | 0.118215E+10 | 0.00 | 0.50 |
February | 0.152690E+10 | 0.00 | 0.00 | 3321024.55 | 0.00 | 0.00 | 0.201732E+10 | 0.00 | 0.54 |
March | 0.114823E+10 | 1751598.81 | 0.00 | 6851164.47 | 79700.96 | 0.00 | 0.235273E+10 | 0.00 | 0.69 |
April | 0.939943E+09 | 0.223485E+09 | 0.00 | 7362143.73 | 26526212.04 | 0.00 | 0.119318E+10 | 0.00 | 0.77 |
May | 0.196958E+09 | 0.581563E+09 | 0.00 | 4972858.12 | 21605220.40 | 0.00 | 0.685026E+09 | 0.00 | 0.60 |
June | 0.200502E+09 | 0.206604E+10 | 0.00 | 1908042.36 | 36743492.84 | 0.00 | 0.215878E+09 | 0.00 | 0.66 |
July | 0.108910E+09 | 0.214069E+10 | 0.00 | 907162.23 | 0.170590E+09 | 0.00 | 76393413.49 | 0.00 | 0.56 |
August | 0.142183E+09 | 0.193358E+10 | 0.00 | 1900620.75 | 77408024.28 | 0.00 | 0.123171E+09 | 0.00 | 0.63 |
September | 43842763.93 | 0.122347E+10 | 0.00 | 3480938.91 | 0.117792E+09 | 0.00 | 0.302606E+09 | 0.00 | 0.57 |
October | 0.617759E+09 | 0.225302E+09 | 0.00 | 5606168.03 | 22110026.53 | 0.00 | 0.141640E+10 | 0.00 | 0.61 |
November | 0.113940E+10 | 3273647.96 | 0.00 | 6280045.93 | 6027327.94 | 0.00 | 0.194350E+10 | 0.00 | 0.62 |
December | 0.173644E+10 | 8718.01 | 0.00 | 3578608.49 | 190614.42 | 0.00 | 0.154652E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.927254E+10 | 0.839940E+10 | 0.00 | 50179194.03 | 0.482031E+09 | 0.00 | 0.130549E+11 | 0.00 | 0.60 |
Minimum of Months | 43842763.93 | 0.00 | 0.00 | 907162.23 | 0.00 | 0.00 | 76393413.49 | 0.00 | 0.48 |
Maximum of Months | 0.173644E+10 | 0.214069E+10 | 0.00 | 7362143.73 | 0.170590E+09 | 0.00 | 0.235273E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.687982E+09 | 201371.68 | 0.00 | 6566731.03 | 1907719.82 | 0.00 | 0.223134E+10 | 0.00 | 0.80 |
February | 0.789715E+09 | 0.00 | 0.00 | 5131028.46 | 0.00 | 0.00 | 0.272968E+10 | 0.00 | 0.78 |
March | 0.618863E+09 | 1221382.25 | 0.00 | 7995231.28 | 51522.34 | 0.00 | 0.286944E+10 | 0.00 | 1.00 |
April | 0.573928E+09 | 0.172788E+09 | 0.00 | 10174984.18 | 17126221.76 | 0.00 | 0.179281E+10 | 0.00 | 1.25 |
May | 0.112675E+09 | 0.465968E+09 | 0.00 | 7328619.89 | 13630136.37 | 0.00 | 0.964813E+09 | 0.00 | 1.04 |
June | 0.127689E+09 | 0.166048E+10 | 0.00 | 1825819.54 | 22690564.91 | 0.00 | 0.190313E+09 | 0.00 | 0.88 |
July | 69132492.65 | 0.175118E+10 | 0.00 | 926384.16 | 0.116114E+09 | 0.00 | 67155418.66 | 0.00 | 0.72 |
August | 93867167.24 | 0.156167E+10 | 0.00 | 1399291.02 | 51134784.90 | 0.00 | 94743130.23 | 0.00 | 0.76 |
September | 29782438.85 | 0.108562E+10 | 0.00 | 3110114.86 | 67733041.81 | 0.00 | 0.291317E+09 | 0.00 | 0.79 |
October | 0.337500E+09 | 0.194716E+09 | 0.00 | 7164523.10 | 12964175.46 | 0.00 | 0.200123E+10 | 0.00 | 1.00 |
November | 0.631107E+09 | 1943764.60 | 0.00 | 7034522.98 | 3976985.71 | 0.00 | 0.233824E+10 | 0.00 | 0.88 |
December | 0.965182E+09 | 6127.17 | 0.00 | 4769160.64 | 123221.85 | 155403.22 | 0.186902E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.503742E+10 | 0.689580E+10 | 0.00 | 63426411.13 | 0.307452E+09 | 155403.22 | 0.174401E+11 | 0.00 | 0.88 |
Minimum of Months | 29782438.85 | 0.00 | 0.00 | 926384.16 | 0.00 | 0.00 | 67155418.66 | 0.00 | 0.62 |
Maximum of Months | 0.965182E+09 | 0.175118E+10 | 0.00 | 10174984.18 | 0.116114E+09 | 155403.22 | 0.286944E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.622559E+09 | 4793618.36 | 0.00 | 27676290.82 | 713313.58 | 0.00 | 0.650242E+10 | 0.00 | 1.55 |
February | 0.907339E+09 | 0.00 | 0.00 | 12682423.83 | 0.00 | 0.00 | 0.697803E+10 | 0.00 | 1.21 |
March | 0.879944E+09 | 2766515.48 | 0.00 | 14042836.62 | 0.00 | 0.00 | 0.468440E+10 | 0.00 | 1.16 |
April | 0.942238E+09 | 0.342159E+09 | 0.00 | 10338991.86 | 24652819.70 | 0.00 | 0.146978E+10 | 0.00 | 0.95 |
May | 0.199706E+09 | 0.652841E+09 | 0.00 | 4923887.09 | 21733073.08 | 0.00 | 0.592090E+09 | 0.00 | 0.61 |
June | 0.200819E+09 | 0.200719E+10 | 0.00 | 1587546.93 | 37311713.37 | 0.00 | 0.173275E+09 | 0.00 | 0.61 |
July | 0.108677E+09 | 0.216940E+10 | 0.00 | 812461.86 | 0.171361E+09 | 0.00 | 65304846.46 | 0.00 | 0.55 |
August | 0.140016E+09 | 0.225154E+10 | 0.00 | 1942862.56 | 74611230.79 | 0.00 | 0.123847E+09 | 0.00 | 0.68 |
September | 39643108.45 | 0.177802E+10 | 0.00 | 4618392.09 | 96573765.08 | 0.00 | 0.354967E+09 | 0.00 | 0.74 |
October | 0.439445E+09 | 0.414468E+09 | 0.00 | 15434586.04 | 17432640.40 | 0.00 | 0.353411E+10 | 0.00 | 1.23 |
November | 0.547076E+09 | 6968882.08 | 0.00 | 24572155.99 | 4852166.77 | 0.00 | 0.661973E+10 | 0.00 | 1.49 |
December | 0.949512E+09 | 1020003.63 | 0.00 | 24338307.01 | 0.00 | 0.00 | 0.717360E+10 | 0.00 | 1.34 |
Annual Sum or Average | 0.597697E+10 | 0.963116E+10 | 0.00 | 0.142971E+09 | 0.449241E+09 | 0.00 | 0.382716E+11 | 0.00 | 1.01 |
Minimum of Months | 39643108.45 | 0.00 | 0.00 | 812461.86 | 0.00 | 0.00 | 65304846.46 | 0.00 | 0.55 |
Maximum of Months | 0.949512E+09 | 0.225154E+10 | 0.00 | 27676290.82 | 0.171361E+09 | 0.00 | 0.717360E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374100E+09 | 4191817.44 | 0.00 | 10439360.64 | 0.00 | 0.00 | 0.278165E+10 | 0.00 | 1.09 |
February | 0.231076E+09 | 0.00 | 0.00 | 8800360.73 | 0.00 | 0.00 | 0.475805E+10 | 0.00 | 1.23 |
March | 0.128620E+09 | 2483501.16 | 0.00 | 15241674.95 | 0.00 | 0.00 | 0.517592E+10 | 0.00 | 1.71 |
April | 0.127390E+09 | 0.448064E+09 | 0.00 | 18238348.90 | 1530263.32 | 0.00 | 0.300477E+10 | 0.00 | 1.82 |
May | 62476845.94 | 0.826830E+09 | 0.00 | 6043322.62 | 3281134.29 | 0.00 | 0.839866E+09 | 0.00 | 1.04 |
June | 51771948.55 | 0.250754E+10 | 0.00 | 3261756.73 | 7667578.62 | 0.00 | 0.371436E+09 | 0.00 | 1.12 |
July | 16881662.60 | 0.259116E+10 | 0.00 | 1743442.57 | 14446229.13 | 0.00 | 0.171079E+09 | 0.00 | 0.95 |
August | 13308581.30 | 0.261805E+10 | 0.00 | 5103045.47 | 7901498.57 | 0.00 | 0.347033E+09 | 0.00 | 1.29 |
September | 13895817.83 | 0.138578E+10 | 0.00 | 4058378.43 | 35860873.23 | 0.00 | 0.357634E+09 | 0.00 | 0.93 |
October | 0.106019E+09 | 0.281234E+09 | 0.00 | 11171425.37 | 8475549.93 | 0.00 | 0.268683E+10 | 0.00 | 1.31 |
November | 0.145830E+09 | 13869540.71 | 0.00 | 15739909.62 | 1061741.64 | 0.00 | 0.480257E+10 | 0.00 | 1.59 |
December | 0.177656E+09 | 486120.94 | 0.00 | 15029754.16 | 682.34 | 0.00 | 0.545712E+10 | 0.00 | 1.37 |
Annual Sum or Average | 0.144903E+10 | 0.106797E+11 | 0.00 | 0.114871E+09 | 80225551.07 | 0.00 | 0.307540E+11 | 0.00 | 1.29 |
Minimum of Months | 13308581.30 | 0.00 | 0.00 | 1743442.57 | 0.00 | 0.00 | 0.171079E+09 | 0.00 | 0.93 |
Maximum of Months | 0.374100E+09 | 0.261805E+10 | 0.00 | 18238348.90 | 35860873.23 | 0.00 | 0.545712E+10 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191379E+11 | 0.00 | 0.00 | 8288853.23 | 41935568.67 | 0.686110E+09 | 0.155672E+10 | 0.00 | 0.38 |
February | 0.220680E+11 | 0.00 | 0.00 | 4352393.04 | 0.00 | 0.830711E+09 | 0.288066E+10 | 0.00 | 0.37 |
March | 0.172660E+11 | 13928299.59 | 0.00 | 27128690.43 | 2157277.84 | 0.529366E+09 | 0.722939E+10 | 0.00 | 0.46 |
April | 0.503352E+10 | 0.258625E+10 | 0.00 | 47343297.12 | 0.241687E+09 | 0.00 | 0.599157E+10 | 0.00 | 0.51 |
May | 0.161136E+10 | 0.673815E+10 | 0.00 | 38615172.87 | 0.187113E+09 | 0.00 | 0.478513E+10 | 0.00 | 0.56 |
June | 0.619994E+09 | 0.240829E+11 | 0.00 | 18834484.35 | 0.259013E+09 | 0.00 | 0.223807E+10 | 0.00 | 0.65 |
July | 0.296681E+09 | 0.235584E+11 | 0.00 | 6092395.23 | 0.417608E+09 | 0.00 | 0.696007E+09 | 0.00 | 0.54 |
August | 0.334350E+09 | 0.200164E+11 | 0.00 | 11647789.48 | 0.324320E+09 | 0.00 | 0.999837E+09 | 0.00 | 0.55 |
September | 0.478659E+09 | 0.130508E+11 | 0.00 | 25849424.38 | 0.617364E+09 | 0.00 | 0.216271E+10 | 0.00 | 0.53 |
October | 0.911683E+10 | 0.239874E+10 | 0.00 | 26830182.62 | 87726807.30 | 0.00 | 0.510477E+10 | 0.00 | 0.45 |
November | 0.168171E+11 | 12579226.16 | 0.00 | 20128279.79 | 55616241.55 | 0.314360E+09 | 0.506450E+10 | 0.00 | 0.41 |
December | 0.229759E+11 | 0.00 | 0.00 | 1048505.59 | 315709.31 | 0.356235E+10 | 0.459486E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.115756E+12 | 0.924582E+11 | 0.00 | 0.236159E+09 | 0.223486E+10 | 0.592289E+10 | 0.391689E+11 | 0.00 | 0.48 |
Minimum of Months | 0.296681E+09 | 0.00 | 0.00 | 1048505.59 | 0.00 | 0.00 | 0.459486E+09 | 0.00 | 0.35 |
Maximum of Months | 0.229759E+11 | 0.240829E+11 | 0.00 | 47343297.12 | 0.617364E+09 | 0.356235E+10 | 0.722939E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.711708E+10 | 4083765.60 | 0.00 | 39480294.64 | 22747842.09 | 0.203132E+09 | 0.124502E+11 | 0.00 | 0.54 |
February | 0.797124E+10 | 0.00 | 0.00 | 29882417.97 | 0.00 | 88630219.92 | 0.147402E+11 | 0.00 | 0.50 |
March | 0.605542E+10 | 11423414.29 | 0.00 | 57789019.95 | 1390233.50 | 0.169609E+09 | 0.204822E+11 | 0.00 | 0.77 |
April | 0.160700E+10 | 0.252433E+10 | 0.00 | 96445376.95 | 0.149761E+09 | 0.00 | 0.164783E+11 | 0.00 | 1.12 |
May | 0.713113E+09 | 0.573877E+10 | 0.00 | 69476461.11 | 0.106044E+09 | 0.00 | 0.887234E+10 | 0.00 | 1.05 |
June | 0.338137E+09 | 0.204896E+11 | 0.00 | 20661319.71 | 0.123302E+09 | 0.00 | 0.225071E+10 | 0.00 | 0.95 |
July | 0.136647E+09 | 0.212957E+11 | 0.00 | 8732824.91 | 0.202323E+09 | 0.00 | 0.827217E+09 | 0.00 | 0.78 |
August | 0.164344E+09 | 0.190841E+11 | 0.00 | 14884003.48 | 0.168303E+09 | 0.00 | 0.119824E+10 | 0.00 | 0.83 |
September | 0.254757E+09 | 0.121558E+11 | 0.00 | 28232424.30 | 0.296147E+09 | 0.00 | 0.255292E+10 | 0.00 | 0.80 |
October | 0.316089E+10 | 0.227830E+10 | 0.00 | 56508651.89 | 38710007.97 | 0.00 | 0.144498E+11 | 0.00 | 0.83 |
November | 0.669862E+10 | 11374091.37 | 0.00 | 45125862.20 | 35841262.90 | 60557909.49 | 0.141814E+11 | 0.00 | 0.61 |
December | 0.979867E+10 | 0.00 | 0.00 | 19217814.89 | 92318.04 | 0.118225E+10 | 0.733390E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.440159E+11 | 0.835934E+11 | 0.00 | 0.486436E+09 | 0.114466E+10 | 0.170418E+10 | 0.115817E+12 | 0.00 | 0.76 |
Minimum of Months | 0.136647E+09 | 0.00 | 0.00 | 8732824.91 | 0.00 | 0.00 | 0.827217E+09 | 0.00 | 0.37 |
Maximum of Months | 0.979867E+10 | 0.212957E+11 | 0.00 | 96445376.95 | 0.296147E+09 | 0.118225E+10 | 0.204822E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605205E+10 | 69951432.33 | 0.00 | 0.275065E+09 | 13401639.12 | 0.108602E+09 | 0.543807E+11 | 0.00 | 1.33 |
February | 0.102252E+11 | 0.00 | 0.00 | 0.111944E+09 | 0.00 | 0.109955E+09 | 0.510962E+11 | 0.00 | 0.91 |
March | 0.101108E+11 | 28745844.31 | 0.00 | 0.115113E+09 | 0.00 | 0.153228E+09 | 0.352731E+11 | 0.00 | 0.95 |
April | 0.389807E+10 | 0.460719E+10 | 0.00 | 82488489.62 | 0.231977E+09 | 0.00 | 0.105787E+11 | 0.00 | 0.77 |
May | 0.164220E+10 | 0.766260E+10 | 0.00 | 39869499.14 | 0.187068E+09 | 0.00 | 0.436934E+10 | 0.00 | 0.59 |
June | 0.665896E+09 | 0.231175E+11 | 0.00 | 15288478.84 | 0.270002E+09 | 0.00 | 0.172777E+10 | 0.00 | 0.59 |
July | 0.305435E+09 | 0.240261E+11 | 0.00 | 5309385.80 | 0.413406E+09 | 0.00 | 0.572278E+09 | 0.00 | 0.53 |
August | 0.312142E+09 | 0.246677E+11 | 0.00 | 13439849.58 | 0.270706E+09 | 0.00 | 0.108612E+10 | 0.00 | 0.64 |
September | 0.404662E+09 | 0.202138E+11 | 0.00 | 38799006.10 | 0.481152E+09 | 0.00 | 0.282012E+10 | 0.00 | 0.75 |
October | 0.432997E+10 | 0.503899E+10 | 0.00 | 0.135053E+09 | 39643842.93 | 0.00 | 0.281815E+11 | 0.00 | 1.10 |
November | 0.616333E+10 | 57090926.65 | 0.00 | 0.225093E+09 | 33758103.42 | 0.00 | 0.532420E+11 | 0.00 | 1.21 |
December | 0.996276E+10 | 629348.60 | 0.00 | 0.210750E+09 | 172147.47 | 0.833421E+09 | 0.596137E+11 | 0.00 | 1.11 |
Annual Sum or Average | 0.540725E+11 | 0.109490E+12 | 0.00 | 0.126821E+10 | 0.194129E+10 | 0.120521E+10 | 0.302942E+12 | 0.00 | 0.87 |
Minimum of Months | 0.305435E+09 | 0.00 | 0.00 | 5309385.80 | 0.00 | 0.00 | 0.572278E+09 | 0.00 | 0.53 |
Maximum of Months | 0.102252E+11 | 0.246677E+11 | 0.00 | 0.275065E+09 | 0.481152E+09 | 0.833421E+09 | 0.596137E+11 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.870334E+10 | 18506223.70 | 0.00 | 48766149.98 | 22669053.75 | 0.116152E+09 | 0.938494E+10 | 0.00 | 0.60 |
February | 0.107824E+11 | 0.00 | 0.00 | 27278928.26 | 0.00 | 45859799.04 | 0.117309E+11 | 0.00 | 0.53 |
March | 0.768040E+10 | 22163223.63 | 0.00 | 57388916.64 | 0.00 | 40100247.12 | 0.159334E+11 | 0.00 | 0.81 |
April | 0.182557E+10 | 0.444463E+10 | 0.00 | 68606405.73 | 35436181.40 | 0.00 | 0.953339E+10 | 0.00 | 1.00 |
May | 0.554658E+09 | 0.918063E+10 | 0.00 | 37655052.25 | 21136106.85 | 0.00 | 0.461734E+10 | 0.00 | 0.90 |
June | 0.224388E+09 | 0.262265E+11 | 0.00 | 19306372.41 | 87486074.98 | 0.00 | 0.213272E+10 | 0.00 | 0.98 |
July | 0.117298E+09 | 0.222841E+11 | 0.00 | 6676833.23 | 93119586.18 | 0.00 | 0.709763E+09 | 0.00 | 0.74 |
August | 0.134160E+09 | 0.204708E+11 | 0.00 | 14087603.81 | 0.100895E+09 | 0.00 | 0.111294E+10 | 0.00 | 0.83 |
September | 0.159711E+09 | 0.130170E+11 | 0.00 | 24433794.18 | 0.266501E+09 | 0.00 | 0.201156E+10 | 0.00 | 0.76 |
October | 0.389900E+10 | 0.261951E+10 | 0.00 | 50937562.88 | 21381213.58 | 0.00 | 0.995936E+10 | 0.00 | 0.77 |
November | 0.695837E+10 | 37702914.17 | 0.00 | 58312791.28 | 23610751.83 | 55848651.57 | 0.142814E+11 | 0.00 | 0.68 |
December | 0.119911E+11 | 110752.35 | 0.00 | 28926689.58 | 91998.29 | 0.963908E+09 | 0.886401E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.530304E+11 | 0.983217E+11 | 0.00 | 0.442377E+09 | 0.672327E+09 | 0.122187E+10 | 0.902717E+11 | 0.00 | 0.76 |
Minimum of Months | 0.117298E+09 | 0.00 | 0.00 | 6676833.23 | 0.00 | 0.00 | 0.709763E+09 | 0.00 | 0.49 |
Maximum of Months | 0.119911E+11 | 0.262265E+11 | 0.00 | 68606405.73 | 0.266501E+09 | 0.963908E+09 | 0.159334E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155028E+10 | 0.00 | 0.00 | 452114.09 | 2651584.85 | 0.389051E+09 | 0.106578E+09 | 0.00 | 0.41 |
February | 0.205934E+10 | 0.00 | 0.00 | 187020.35 | 0.00 | 0.366889E+09 | 0.177730E+09 | 0.00 | 0.40 |
March | 0.159438E+10 | 334019.31 | 0.00 | 2192784.63 | 55911.00 | 0.265130E+09 | 0.524592E+09 | 0.00 | 0.46 |
April | 0.465921E+09 | 0.160333E+09 | 0.00 | 5762323.92 | 23101648.41 | 0.00 | 0.515015E+09 | 0.00 | 0.49 |
May | 0.162986E+09 | 0.465693E+09 | 0.00 | 5033922.43 | 14827605.41 | 0.00 | 0.341070E+09 | 0.00 | 0.51 |
June | 68887989.99 | 0.191680E+10 | 0.00 | 1583038.48 | 20177259.67 | 0.00 | 0.159949E+09 | 0.00 | 0.59 |
July | 34097981.99 | 0.199288E+10 | 0.00 | 663282.99 | 40862283.18 | 0.00 | 52029814.79 | 0.00 | 0.51 |
August | 30645054.95 | 0.167622E+10 | 0.00 | 1078772.21 | 28196942.76 | 0.00 | 74027845.19 | 0.00 | 0.52 |
September | 69757251.81 | 0.107931E+10 | 0.00 | 2944226.81 | 68557461.52 | 0.00 | 0.165963E+09 | 0.00 | 0.50 |
October | 0.832270E+09 | 0.186118E+09 | 0.00 | 2756310.60 | 10581966.23 | 98728562.34 | 0.370095E+09 | 0.00 | 0.43 |
November | 0.145556E+10 | 656264.33 | 0.00 | 1368626.00 | 6214673.76 | 0.261309E+09 | 0.381581E+09 | 0.00 | 0.42 |
December | 0.165926E+10 | 0.00 | 0.00 | 39394.75 | 676744.77 | 0.935883E+09 | 14452451.19 | 0.00 | 0.39 |
Annual Sum or Average | 0.998338E+10 | 0.747835E+10 | 0.00 | 24061817.27 | 0.215904E+09 | 0.231699E+10 | 0.288308E+10 | 0.00 | 0.47 |
Minimum of Months | 30645054.95 | 0.00 | 0.00 | 39394.75 | 0.00 | 0.00 | 14452451.19 | 0.00 | 0.39 |
Maximum of Months | 0.205934E+10 | 0.199288E+10 | 0.00 | 5762323.92 | 68557461.52 | 0.935883E+09 | 0.524592E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.583090E+09 | 54977.94 | 0.00 | 2931619.02 | 1650557.87 | 0.146984E+09 | 0.986346E+09 | 0.00 | 0.55 |
February | 0.729539E+09 | 0.00 | 0.00 | 2025978.03 | 0.00 | 0.154835E+09 | 0.128542E+10 | 0.00 | 0.52 |
March | 0.573995E+09 | 355907.29 | 0.00 | 5129563.06 | 35962.73 | 94871691.72 | 0.180580E+10 | 0.00 | 0.77 |
April | 0.153399E+09 | 0.167215E+09 | 0.00 | 10915289.12 | 13286406.81 | 0.00 | 0.146513E+10 | 0.00 | 1.11 |
May | 71150008.66 | 0.401822E+09 | 0.00 | 8283046.53 | 7643828.36 | 0.00 | 0.716543E+09 | 0.00 | 1.00 |
June | 36229565.66 | 0.169849E+10 | 0.00 | 1818323.82 | 10656507.92 | 0.00 | 0.167111E+09 | 0.00 | 0.90 |
July | 17503547.58 | 0.186502E+10 | 0.00 | 867375.23 | 21000055.95 | 0.00 | 60630340.14 | 0.00 | 0.75 |
August | 15631198.87 | 0.167503E+10 | 0.00 | 1397136.80 | 16079224.35 | 0.00 | 89639692.90 | 0.00 | 0.80 |
September | 29229618.19 | 0.107121E+10 | 0.00 | 3249094.84 | 28137006.93 | 0.00 | 0.214612E+09 | 0.00 | 0.78 |
October | 0.268403E+09 | 0.190585E+09 | 0.00 | 5520455.29 | 4405836.79 | 34907938.36 | 0.126857E+10 | 0.00 | 0.80 |
November | 0.632718E+09 | 599622.46 | 0.00 | 3624064.23 | 3997363.55 | 81039381.87 | 0.116164E+10 | 0.00 | 0.61 |
December | 0.105724E+10 | 0.00 | 0.00 | 903980.44 | 435291.53 | 0.308454E+09 | 0.379833E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.416813E+10 | 0.707037E+10 | 0.00 | 46665926.42 | 0.107328E+09 | 0.821092E+09 | 0.960127E+10 | 0.00 | 0.75 |
Minimum of Months | 15631198.87 | 0.00 | 0.00 | 867375.23 | 0.00 | 0.00 | 60630340.14 | 0.00 | 0.42 |
Maximum of Months | 0.105724E+10 | 0.186502E+10 | 0.00 | 10915289.12 | 28137006.93 | 0.308454E+09 | 0.180580E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.572286E+09 | 2707413.13 | 0.00 | 22645656.15 | 1889198.95 | 98237624.28 | 0.558265E+10 | 0.00 | 1.50 |
February | 0.981629E+09 | 0.00 | 0.00 | 8867420.28 | 0.00 | 0.156405E+09 | 0.562619E+10 | 0.00 | 1.02 |
March | 0.864056E+09 | 786350.03 | 0.00 | 10118346.53 | 0.00 | 0.167275E+09 | 0.336471E+10 | 0.00 | 0.93 |
April | 0.401171E+09 | 0.281091E+09 | 0.00 | 10319064.65 | 19163806.33 | 0.00 | 0.965120E+09 | 0.00 | 0.74 |
May | 0.191281E+09 | 0.516945E+09 | 0.00 | 5434850.62 | 14356569.24 | 0.00 | 0.308684E+09 | 0.00 | 0.54 |
June | 70721720.41 | 0.183375E+10 | 0.00 | 1301510.20 | 20930884.16 | 0.00 | 0.123129E+09 | 0.00 | 0.55 |
July | 36780928.81 | 0.201062E+10 | 0.00 | 600550.46 | 40922405.00 | 0.00 | 41520902.55 | 0.00 | 0.50 |
August | 27715068.31 | 0.201353E+10 | 0.00 | 1253669.53 | 24853285.16 | 0.00 | 81382804.84 | 0.00 | 0.60 |
September | 44763053.16 | 0.163185E+10 | 0.00 | 4599769.44 | 42501143.67 | 0.00 | 0.249163E+09 | 0.00 | 0.70 |
October | 0.388511E+09 | 0.385477E+09 | 0.00 | 14062853.52 | 4696482.53 | 24979717.09 | 0.282690E+10 | 0.00 | 1.10 |
November | 0.589390E+09 | 2050314.73 | 0.00 | 18254011.66 | 5948494.88 | 81263829.49 | 0.537974E+10 | 0.00 | 1.33 |
December | 0.882404E+09 | 940967.36 | 0.00 | 15137737.52 | 225140.31 | 0.272762E+09 | 0.566580E+10 | 0.00 | 1.19 |
Annual Sum or Average | 0.505071E+10 | 0.867976E+10 | 0.00 | 0.112595E+09 | 0.175487E+09 | 0.800923E+09 | 0.302150E+11 | 0.00 | 0.89 |
Minimum of Months | 27715068.31 | 0.00 | 0.00 | 600550.46 | 0.00 | 0.00 | 41520902.55 | 0.00 | 0.50 |
Maximum of Months | 0.981629E+09 | 0.201353E+10 | 0.00 | 22645656.15 | 42501143.67 | 0.272762E+09 | 0.566580E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.799544E+09 | 984480.91 | 0.00 | 4061714.54 | 1504357.96 | 0.105530E+09 | 0.993928E+09 | 0.00 | 0.70 |
February | 0.102943E+10 | 0.00 | 0.00 | 2161416.93 | 0.00 | 0.114881E+09 | 0.139035E+10 | 0.00 | 0.63 |
March | 0.741627E+09 | 530976.19 | 0.00 | 5183547.24 | 0.00 | 87649684.89 | 0.149457E+10 | 0.00 | 0.82 |
April | 0.167796E+09 | 0.275179E+09 | 0.00 | 9059942.59 | 3011626.48 | 0.00 | 0.870397E+09 | 0.00 | 0.96 |
May | 53270077.24 | 0.609105E+09 | 0.00 | 5022510.64 | 2093253.76 | 0.00 | 0.351283E+09 | 0.00 | 0.80 |
June | 22964692.72 | 0.197247E+10 | 0.00 | 1639713.21 | 7887341.85 | 0.00 | 0.165773E+09 | 0.00 | 0.87 |
July | 11739347.34 | 0.181409E+10 | 0.00 | 744941.71 | 12151069.02 | 0.00 | 59867994.87 | 0.00 | 0.68 |
August | 11932186.21 | 0.162583E+10 | 0.00 | 1308761.61 | 10360460.28 | 0.00 | 85419522.76 | 0.00 | 0.76 |
September | 22872663.79 | 0.104465E+10 | 0.00 | 2920094.33 | 26326104.64 | 0.00 | 0.168268E+09 | 0.00 | 0.70 |
October | 0.394192E+09 | 0.198930E+09 | 0.00 | 5480662.45 | 2584999.16 | 9818208.31 | 0.936422E+09 | 0.00 | 0.75 |
November | 0.670043E+09 | 1598940.62 | 0.00 | 4848798.87 | 3690051.38 | 81966922.22 | 0.139803E+10 | 0.00 | 0.74 |
December | 0.990700E+09 | 0.00 | 0.00 | 2167736.51 | 437074.86 | 0.286515E+09 | 0.902869E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.491611E+10 | 0.754337E+10 | 0.00 | 44599840.64 | 70046339.39 | 0.686361E+09 | 0.881718E+10 | 0.00 | 0.75 |
Minimum of Months | 11739347.34 | 0.00 | 0.00 | 744941.71 | 0.00 | 0.00 | 59867994.87 | 0.00 | 0.54 |
Maximum of Months | 0.102943E+10 | 0.197247E+10 | 0.00 | 9059942.59 | 26326104.64 | 0.286515E+09 | 0.149457E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 4043407.82 | 0.00 | 0.00 | 0.294148E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8028946.07 | 0.00 | 0.00 | 0.293167E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14610358.68 | 0.00 | 0.00 | 0.292101E+09 | 0.00 | 0.31 |
April | 0.00 | 233952.61 | 0.00 | 19524411.40 | 0.00 | 0.00 | 0.124385E+09 | 0.00 | 0.29 |
May | 0.00 | 13877007.56 | 0.00 | 2924166.61 | 0.00 | 0.00 | 54713615.85 | 0.00 | 0.29 |
June | 0.00 | 92072576.79 | 0.00 | 1604387.85 | 0.00 | 0.00 | 14563311.49 | 0.00 | 0.30 |
July | 0.00 | 0.186464E+09 | 0.00 | 514369.71 | 0.00 | 0.00 | 4095129.62 | 0.00 | 0.28 |
August | 0.00 | 0.153931E+09 | 0.00 | 2986910.72 | 0.00 | 0.00 | 5891592.27 | 0.00 | 0.31 |
September | 0.00 | 0.112401E+09 | 0.00 | 695951.25 | 0.00 | 0.00 | 10824759.67 | 0.00 | 0.29 |
October | 0.00 | 22344028.83 | 0.00 | 7114078.97 | 0.00 | 0.00 | 0.169298E+09 | 0.00 | 0.28 |
November | 0.00 | 1930002.54 | 0.00 | 12772866.24 | 0.00 | 0.00 | 0.236148E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 19088075.53 | 0.00 | 0.00 | 0.349683E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.583253E+09 | 0.00 | 93907930.86 | 0.00 | 0.00 | 0.184902E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 514369.71 | 0.00 | 0.00 | 4095129.62 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.186464E+09 | 0.00 | 19524411.40 | 0.00 | 0.00 | 0.349683E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19943797.48 | 0.00 | 0.00 | 31297409.53 | 0.00 | 0.00 | 0.292927E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 69693178.00 | 0.00 | 0.00 | 0.294682E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.134240E+09 | 0.00 | 0.00 | 0.293076E+10 | 0.00 | 0.31 |
April | 0.00 | 3947769.87 | 0.00 | 0.179590E+09 | 0.00 | 0.00 | 0.121531E+10 | 0.00 | 0.29 |
May | 0.00 | 0.138441E+09 | 0.00 | 27021261.93 | 0.00 | 0.00 | 0.548139E+09 | 0.00 | 0.29 |
June | 0.00 | 0.919768E+09 | 0.00 | 15145859.48 | 0.00 | 0.00 | 0.144961E+09 | 0.00 | 0.30 |
July | 0.00 | 0.186110E+10 | 0.00 | 4887999.14 | 0.00 | 0.00 | 40394174.28 | 0.00 | 0.28 |
August | 0.00 | 0.161280E+10 | 0.00 | 25330856.80 | 0.00 | 0.00 | 51167768.91 | 0.00 | 0.31 |
September | 0.00 | 0.111034E+10 | 0.00 | 6365761.31 | 0.00 | 0.00 | 0.108314E+09 | 0.00 | 0.29 |
October | 0.00 | 0.222209E+09 | 0.00 | 64818490.31 | 0.00 | 0.00 | 0.169643E+10 | 0.00 | 0.28 |
November | 0.00 | 18640499.71 | 0.00 | 0.116966E+09 | 0.00 | 0.00 | 0.237079E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.172985E+09 | 0.00 | 0.00 | 0.350754E+10 | 0.00 | 0.28 |
Annual Sum or Average | 19943797.48 | 0.588725E+10 | 0.00 | 0.848343E+09 | 0.00 | 0.00 | 0.184899E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4887999.14 | 0.00 | 0.00 | 40394174.28 | 0.00 | 0.28 |
Maximum of Months | 19943797.48 | 0.186110E+10 | 0.00 | 0.179590E+09 | 0.00 | 0.00 | 0.350754E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13166697.76 | 0.00 | 0.00 | 2408390.76 | 0.00 | 0.00 | 0.282599E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6221853.30 | 0.00 | 0.00 | 0.296090E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12896064.34 | 0.00 | 0.00 | 0.293852E+09 | 0.00 | 0.31 |
April | 0.00 | 538551.79 | 0.00 | 17424445.66 | 0.00 | 0.00 | 0.118439E+09 | 0.00 | 0.29 |
May | 0.00 | 13859417.80 | 0.00 | 2718222.84 | 0.00 | 0.00 | 54833384.74 | 0.00 | 0.29 |
June | 0.00 | 92023530.47 | 0.00 | 1514913.04 | 0.00 | 0.00 | 14574727.25 | 0.00 | 0.30 |
July | 0.00 | 0.186123E+09 | 0.00 | 490298.91 | 0.00 | 0.00 | 4079009.51 | 0.00 | 0.28 |
August | 0.00 | 0.165463E+09 | 0.00 | 2366716.14 | 0.00 | 0.00 | 4828911.23 | 0.00 | 0.31 |
September | 0.00 | 0.111328E+09 | 0.00 | 631896.58 | 0.00 | 0.00 | 10909417.04 | 0.00 | 0.29 |
October | 0.00 | 22235420.77 | 0.00 | 6192535.22 | 0.00 | 0.00 | 0.170115E+09 | 0.00 | 0.28 |
November | 0.00 | 1811197.67 | 0.00 | 11111778.34 | 0.00 | 0.00 | 0.237897E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16206693.44 | 0.00 | 0.00 | 0.351661E+09 | 0.00 | 0.28 |
Annual Sum or Average | 13166697.76 | 0.593382E+09 | 0.00 | 80183808.58 | 0.00 | 0.00 | 0.183988E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 490298.91 | 0.00 | 0.00 | 4079009.51 | 0.00 | 0.28 |
Maximum of Months | 13166697.76 | 0.186123E+09 | 0.00 | 17424445.66 | 0.00 | 0.00 | 0.351661E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.568304E+09 | 0.00 | 0.00 | 0.502046E+12 | 0.00 | 22.23 |
February | 0.00 | 0.00 | 0.00 | 0.915270E+09 | 0.00 | 0.00 | 0.610477E+12 | 0.00 | 28.37 |
March | 0.00 | 0.00 | 0.00 | 0.157178E+10 | 0.00 | 0.00 | 0.827592E+12 | 0.00 | 38.77 |
April | 0.00 | 0.00 | 0.00 | 0.363866E+10 | 0.00 | 0.00 | 0.614730E+12 | 0.00 | 45.56 |
May | 0.00 | 27789.60 | 0.00 | 0.470101E+09 | 0.00 | 0.00 | 0.267558E+12 | 0.00 | 19.11 |
June | 0.00 | 0.918073E+09 | 0.00 | 0.593943E+09 | 0.00 | 0.00 | 0.119012E+12 | 0.00 | 12.17 |
July | 0.00 | 0.521135E+11 | 0.00 | 0.317790E+09 | 0.00 | 0.00 | 0.400461E+11 | 0.00 | 13.75 |
August | 0.00 | 0.252434E+11 | 0.00 | 0.138848E+10 | 0.00 | 0.00 | 0.723019E+11 | 0.00 | 29.56 |
September | 0.00 | 0.103301E+11 | 0.00 | 0.262175E+09 | 0.00 | 0.00 | 0.104649E+12 | 0.00 | 21.05 |
October | 0.00 | 0.310698E+10 | 0.00 | 0.100774E+10 | 0.00 | 0.00 | 0.501965E+12 | 0.00 | 31.22 |
November | 0.00 | 21760725.82 | 0.00 | 0.169435E+10 | 0.00 | 0.00 | 0.780530E+12 | 0.00 | 39.71 |
December | 0.00 | 0.00 | 0.00 | 0.239582E+10 | 0.00 | 0.00 | 0.113855E+13 | 0.00 | 40.60 |
Annual Sum or Average | 0.00 | 0.917338E+11 | 0.00 | 0.148244E+11 | 0.00 | 0.00 | 0.557946E+13 | 0.00 | 28.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.262175E+09 | 0.00 | 0.00 | 0.400461E+11 | 0.00 | 12.17 |
Maximum of Months | 0.00 | 0.521135E+11 | 0.00 | 0.363866E+10 | 0.00 | 0.00 | 0.113855E+13 | 0.00 | 45.56 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:57:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.317068E+12 | 0.100715E+11 | 0.00 | 0.205665E+13 | 0.663320E+12 |
February | 0.357653E+12 | 0.794661E+10 | 0.00 | 0.223675E+13 | 0.329447E+12 |
March | 0.464222E+12 | 0.104547E+11 | 0.00 | 0.243671E+13 | 0.101245E+13 |
April | 0.552923E+12 | 0.272739E+10 | 0.00 | 0.139492E+13 | 0.268529E+13 |
May | 0.547351E+12 | 0.384511E+09 | 0.00 | 0.737415E+12 | 0.233475E+13 |
June | 0.560099E+12 | -0.297635E+10 | 0.00 | 0.263947E+11 | 0.333728E+13 |
July | 0.530864E+12 | -0.535833E+10 | 0.00 | -0.258247E+12 | 0.373173E+13 |
August | 0.474908E+12 | -0.339815E+10 | 0.00 | -0.897057E+11 | 0.407978E+13 |
September | 0.396398E+12 | -0.203040E+10 | 0.00 | 0.144894E+11 | 0.239705E+13 |
October | 0.371141E+12 | 0.453202E+10 | 0.00 | 0.163395E+13 | 0.166455E+13 |
November | 0.332774E+12 | 0.923318E+10 | 0.00 | 0.233223E+13 | 0.106144E+13 |
December | 0.263049E+12 | 0.976015E+10 | 0.00 | 0.286893E+13 | 0.894609E+12 |
Annual Sum or Average | 0.516845E+13 | 0.413468E+11 | 0.00 | 0.153905E+14 | 0.241917E+14 |
Minimum of Months | 0.263049E+12 | -0.535833E+10 | 0.00 | -0.258247E+12 | 0.329447E+12 |
Maximum of Months | 0.560099E+12 | 0.104547E+11 | 0.00 | 0.286893E+13 | 0.407978E+13 |