Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:56:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27579.60 | 595.41 | 595.41 |
Net Site Energy | 27117.68 | 585.44 | 585.44 |
Total Source Energy | 79637.75 | 1719.28 | 1719.28 |
Net Source Energy | 78174.85 | 1687.70 | 1687.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2834.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1272.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1717.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2252.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 322.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 414.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2641.94 |
Humidification | 1702.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.42 |
Heat Recovery | 48.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 865.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 23879.72 | 3699.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5555.53 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2834.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1272.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1717.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2252.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 322.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 414.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2641.94 |
Humidification | General | 1702.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.42 |
Heat Recovery | General | 48.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 865.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2834.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1272.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1717.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2252.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 322.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 414.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2641.94 |
Humidification | Unassigned | 1702.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.42 |
Heat Recovery | Unassigned | 48.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 865.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 128.76 | 79.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 343.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 515.53 | 79.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 128.76 | 79.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 343.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 515.53 | 79.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 484.114 | 2.03 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -22.20 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 461.918 | 1.93 |
Electricity Coming From Utility | 23417.806 | 98.07 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 23417.806 | 98.07 |
Total On-Site and Utility Electric Sources | 23879.725 | 100.00 |
Total Electricity End Uses | 23879.725 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 127.94 | 3.85 |
Air to Air Heat Recovery for Heating | 3191.36 | 96.15 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3319.30 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5555.53 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5555.53 | 100.00 |
Total Water End Uses | 5555.53 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 219.00 |
Time Setpoint Not Met During Occupied Cooling | 327.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5941.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-AUG-15:20 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 18-MAY-15:39 |
Heating | 0.00 | 2665274.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 373186.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 263000.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40993.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 76123.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5431.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 32381.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1735683.59 | 2697655.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2665274.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 373186.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 263000.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 40993.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 76123.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5431.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 32381.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3072.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4028.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5440.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 853.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7133.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1019.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1314.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5392.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 152.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 938.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 75627.09 | 4010.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 66.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 86.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 154.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 116.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1632.70 | 86.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 66.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 86.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 154.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 116.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1632.70 | 86.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.05 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.509486 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.90 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.496816 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 22.16 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.44 | 0.349771 | 0.297000 | 1.62 | 0.932724 | 0.500000 | 0.001089 | 0.000183 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 50.77 | 0.374673 | 0.318000 | 16.14 | 0.999127 | 0.500000 | 0.001017 | 0.004150 | 16.14 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.98 | 0.381716 | 0.324000 | 1.61 | 1.00 | 0.500000 | 0.000998 | 0.000941 | 3.34 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.915203 | 0.260948 | 0.222000 | 0.203175 | 0.695862 | 0.500000 | 0.001460 | 0.000164 | 0.584097 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.36 | 0.113133 | 0.096000 | 0.130598 | 0.301688 | 0.500000 | 0.003368 | 0.000113 | 0.401083 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.65 | 0.144685 | 0.123000 | 0.203032 | 0.385825 | 0.500000 | 0.002633 | 0.000182 | 0.645967 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.65 | 0.093182 | 0.079000 | 0.130482 | 0.300000 | 0.500000 | 0.004089 | 0.000092 | 0.327906 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.66 | 0.275820 | 0.236000 | 2.04 | 0.735521 | 0.500000 | 0.001381 | 0.002432 | 8.66 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.58 | 0.300000 | 0.500000 | 0.003610 | 0.001614 | 5.75 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.97 | 0.140764 | 0.120000 | 2.04 | 0.375371 | 0.500000 | 0.002707 | 0.002458 | 8.75 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 15.44 | 0.099662 | 0.085000 | 1.31 | 0.300000 | 0.500000 | 0.003823 | 0.001577 | 5.61 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.11 | 0.215569 | 0.211000 | 0.233759 | 0.574850 | 0.500000 | 0.001767 | 0.000311 | 1.11 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.46 | 0.105559 | 0.090000 | 0.131221 | 0.300000 | 0.500000 | 0.003609 | 0.000205 | 0.731034 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.80 | 0.132937 | 0.113000 | 0.203009 | 0.354498 | 0.500000 | 0.002866 | 0.000314 | 1.12 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.61 | 0.095309 | 0.081000 | 0.130799 | 0.300000 | 0.500000 | 0.003998 | 0.000204 | 0.725234 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20886.45 | 0.000183 | 435.66 |
CORE_MID VAV BOX REHEAT COIL | 474406.82 | 0.004150 | 12044.93 |
CORE_TOP VAV BOX REHEAT COIL | 107555.30 | 0.000941 | 2838.40 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18771.95 | 0.000164 | 495.14 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12888.31 | 0.000113 | 339.93 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20756.27 | 0.000182 | 547.44 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10541.78 | 0.000092 | 278.10 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 278040.94 | 0.002432 | 7331.05 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 184534.17 | 0.001614 | 4865.47 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 281009.90 | 0.002458 | 7409.28 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 180211.02 | 0.001577 | 4751.55 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35563.65 | 0.000311 | 937.56 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23466.29 | 0.000205 | 618.63 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 35884.99 | 0.000314 | 946.03 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23280.16 | 0.000204 | 613.72 |
VAV_BOT WITH REHEAT HEATING COIL | 100260.99 | 0.000877 | 1506.59 |
VAV_MID WITH REHEAT HEATING COIL | 1036778.04 | 0.009070 | 15132.05 |
VAV_TOP WITH REHEAT HEATING COIL | 101867.31 | 0.000891 | 1535.65 |
CAV_BAS HEATING COIL | 279782.76 | 0.002448 | 5834.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.51 | 2.28 | 11.02 | 3.04 | 9.18 | 9.18 | 0.300000 | 0.330982 | 9.18 |
VAV_MID WITH REHEAT | 53.21 | 22.85 | 106.41 | 42.82 | 85.05 | 85.05 | 0.300000 | 0.503461 | 85.05 |
VAV_TOP WITH REHEAT | 5.48 | 2.31 | 10.96 | 7.02 | 9.44 | 9.44 | 0.300000 | 0.744280 | 9.44 |
CAV_BAS | 5.05 | 5.05 | 5.05 | 5.05 | 5.05 | 5.05 | 1.00 | 1.00 | 5.05 |
AIRLOOP DATACENTER BASEMENT | 22.16 | 22.16 | 22.16 | 22.16 | 22.16 | 22.16 | 1.00 | 0.999993 | 22.16 |
AIRLOOP DATACENTER BOT | 0.509486 | 0.509486 | 0.509486 | 0.509486 | 0.509486 | 0.509486 | 1.00 | 1.00 | 0.509486 |
AIRLOOP DATACENTER MID | 4.90 | 4.90 | 4.90 | 4.90 | 4.90 | 4.90 | 1.00 | 1.00 | 4.90 |
AIRLOOP DATACENTER TOP | 0.496816 | 0.496816 | 0.496816 | 0.496816 | 0.496816 | 0.496816 | 1.00 | 1.00 | 0.496816 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.18 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 85.05 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.44 | |
CAV_BAS_OA_CONTROLLER | 5.05 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 22.16 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.509486 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.90 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.496816 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
CAV_BAS OA HEAT RECOVERY | 1.20 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.36 | 6.67 | 10.87 | 0.009754 | 0.008500 | 190496.76 | 0.005448 | 9.18 |
VAV_MID WITH REHEAT COOLING COIL | 25.49 | 6.67 | 10.87 | 0.009900 | 0.008500 | 1814923.28 | 0.051907 | 85.05 |
VAV_TOP WITH REHEAT COOLING COIL | 25.31 | 6.67 | 10.87 | 0.009762 | 0.008500 | 195616.69 | 0.005595 | 9.44 |
CAV_BAS COOLING COIL | 25.47 | 6.67 | 11.36 | 0.010049 | 0.008500 | 106901.67 | 0.003057 | 5.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.18 |
VAV_MID WITH REHEAT FAN | 85.05 |
VAV_TOP WITH REHEAT FAN | 9.44 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005448 | 0.000087 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000877 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.051907 | 0.000009 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009070 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005595 | 0.000085 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000891 | |
CAV_BAS_COOLC_CONTROLLER | 0.003057 | 0.000156 |
CAV_BAS_HEATC_CONTROLLER | 0.002448 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.05 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 22.16 | 434218.98 | 300032.00 | 0.010634 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.509486 | 9815.93 | 6833.83 | 0.000240 |
AIRLOOP DATACENTER MID COOLING COIL | 4.90 | 94449.74 | 65718.53 | 0.002313 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.496816 | 9577.96 | 6665.73 | 0.000235 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 22.16 | 22.16 | 22.16 | 22.16 | 434218.98 | 434218.98 | 28525.81 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.509486 | 0.509486 | 0.509486 | 0.509486 | 9815.93 | 9815.93 | 1317.77 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.90 | 4.90 | 4.90 | 4.90 | 94449.74 | 94449.74 | 13177.74 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.496816 | 0.496816 | 0.496816 | 0.496816 | 9577.96 | 9577.96 | 1317.77 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 22.16 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.509486 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.90 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.496816 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 22.16 | 434218.98 | 0.010634 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.509486 | 9815.93 | 0.000240 |
AIRLOOP DATACENTER MID HEATING COIL | 4.90 | 94449.74 | 0.002313 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.496816 | 9577.96 | 0.000235 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 28525.81 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1317.77 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 13177.74 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1317.77 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000205 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.066007 | 10670.18 | |
HEATSYS1 PUMP | 0.028227 | 8416.48 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.066007 | 7.92 |
HEATSYS1 | 0.028227 | 3.39 |
COOLSYS1_SUPPLY | 0.066007 | 7.92 |
SINGLE WATER PLANT LOOP | 0.013422 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.066007 | 0.066007 | 277063.44 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3226487.10 | 3226487.10 | 0.028227 |
CENTRAL BOILER | 552872.08 | 541884.34 | 0.013422 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.033003 | 3693.66 |
COOLSYS1 CHILLER2 PUMP | 0.033003 | 3693.66 |
PLANT CIRC PUMP | 0.013422 | 3389.39 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.066007 | 0.033180 | 1162994.86 | 1168511.32 | 0.057447 |
COOLSYS1 CHILLER2 | 0.066007 | 0.033180 | 1162994.86 | 1168511.32 | 0.057447 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013422 | 139666.47 | 58773.12 | 69833.23 | 7004.20 | 21365.11 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.114894 | 13.79 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.114894 | 28163.60 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 44.42 | 1386902.02 | 8.88 | 173362.75 |
TOWERWATERSYS COOLTOWER 2 | 44.42 | 1386902.02 | 8.88 | 173362.75 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.060062 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.7036 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.6740 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 0.7860 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.254 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.316 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.105 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
47 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
48 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
49 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
50 | 9 | -0.28558746E-14 | 0.26675028E-16 | -0.16026559E-09 | 0.69076497E-16 |
51 | 8 | 0.23353949E-07 | 0.95729520E-13 | 0.39316180E-03 | -0.26554240E-09 |
52 | 7 | -0.12699588E-01 | 0.48940425E-08 | -0.23745122E-01 | 0.14439895E-03 |
53 | 6 | 0.41779519 | 0.16947569E-05 | 0.48267585 | -0.48944572E-02 |
54 | 5 | -5.3120007 | 0.63029714E-04 | -4.5224959 | 0.64689622E-01 |
55 | 4 | 33.539944 | 0.51375985E-03 | 21.757730 | -0.42925403 |
56 | 3 | -112.36878 | 0.11161347E-02 | -56.251442 | 1.5317020 |
57 | 2 | 198.26343 | 0.62604307E-03 | 78.450513 | -2.9186979 |
58 | 1 | -171.58271 | 0.66656834E-04 | -55.422538 | 2.7529166 |
59 | 0 | 57.057407 | 0.37829650E-06 | 15.531296 | |
60 | 9 | -0.19534884E-14 | 0.26880518E-16 | -0.16163544E-09 | 0.39229747E-16 |
61 | 8 | 0.23545384E-07 | 0.91820279E-13 | 0.39512614E-03 | -0.26771911E-09 |
62 | 7 | -0.12758046E-01 | 0.46850258E-08 | -0.23829243E-01 | 0.14506364E-03 |
63 | 6 | 0.41938339 | 0.16211288E-05 | 0.48402465 | -0.49131784E-02 |
64 | 5 | -5.3274970 | 0.60251426E-04 | -4.5328381 | 0.64881772E-01 |
65 | 4 | 33.608472 | 0.49081832E-03 | 21.798117 | -0.43016391 |
66 | 3 | -112.51454 | 0.10657201E-02 | -56.331268 | 1.5338078 |
67 | 2 | 198.40783 | 0.59747734E-03 | 78.523793 | -2.9209911 |
68 | 1 | -171.63603 | 0.63586949E-04 | -55.443973 | 2.7538511 |
69 | 0 | 57.057407 | 0.36069615E-06 | 15.527859 | |
70 | 9 | -0.39622448E-14 | 0.30965005E-16 | -0.15644622E-09 | 0.83761896E-16 |
71 | 8 | 0.22817631E-07 | 0.10657885E-12 | 0.38762953E-03 | -0.25944428E-09 |
72 | 7 | -0.12534851E-01 | 0.54782651E-08 | -0.23508037E-01 | 0.14252583E-03 |
73 | 6 | 0.41331945 | 0.19012310E-05 | 0.47887242 | -0.48416988E-02 |
74 | 5 | -5.2683287 | 0.70842384E-04 | -4.4933212 | 0.64148104E-01 |
75 | 4 | 33.346808 | 0.57843093E-03 | 21.643778 | -0.42668966 |
76 | 3 | -111.95797 | 0.12585571E-02 | -56.026198 | 1.5257666 |
77 | 2 | 197.85639 | 0.70689485E-03 | 78.243783 | -2.9122339 |
78 | 1 | -171.43240 | 0.75360767E-04 | -55.362146 | 2.7502824 |
79 | 0 | 57.057407 | 0.42830732E-06 | 15.541045 | |
80 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
81 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
82 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
83 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
84 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
85 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
86 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
87 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
88 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
89 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
90 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
91 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
92 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
93 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
94 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
95 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
96 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
97 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
98 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
99 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
100 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
101 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
102 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
103 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
104 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
105 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
106 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
107 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
108 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
109 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
110 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
111 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
112 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
113 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
114 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
115 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
116 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
117 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
118 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
119 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
120 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
121 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
122 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
123 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
124 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
125 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
126 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
127 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.292_SHGC_EAST_0.399 | 35 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
2 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 36 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
3 | WINDOW_U_0.292_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
4 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 38 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7884E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7908E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7418E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7438E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9550E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9565E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7638E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7647E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8428E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0036E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7880E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9295E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9937E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1087E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7863E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8441E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1827 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1011 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2097 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1177 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1191 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9483E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0013E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7395E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8513E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0491E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7974E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9799E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0006E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1357E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7869E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8458E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7882E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7909E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7416E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7439E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9549E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9567E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7637E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7646E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6900E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.1647E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5180E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0725E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8166E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9698E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7253E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7651E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.6221E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7379E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3339E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5056E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.1119E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9769E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2070E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9476E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5294E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6515E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3049E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3946E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7691E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8041E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7254E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7657E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0569E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0593E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5882E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5902E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2573E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2587E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7639E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7647E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1104E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2490E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6329E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7451E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2939E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3767E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7869E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8459E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0767E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6842E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9042E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0403E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4687E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3443E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0013E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7390E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1083E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2487E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6297E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7401E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2884E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3593E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7864E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8442E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0568E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0591E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5881E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5899E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2571E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2584E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7638E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7646E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8409E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9680E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4164E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5088E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2936E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3257E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7255E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7658E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4218E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2387E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7937E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8629E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2334E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6158E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2070E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9476E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9596E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2919E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5748E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9431E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3376E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4742E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7252E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7650E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1834 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1368 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2046 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1572 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1334 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.2772E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1234E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0279E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.0423E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.3532E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.7247E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.0875E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.4051E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3551E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2797E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0626E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.2526E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.1586E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.9277E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.2812E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4535E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4091E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1234E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0274E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.6839E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.6634E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9805E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.1980E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.4215E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8785E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2797E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0626E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1835 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1370 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2046 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1574 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1336 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.2944E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1365E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0346E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.0479E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.3615E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.7312E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.0957E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.4177E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3644E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2928E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0693E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.2529E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.1635E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.9284E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.2850E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4606E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4137E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1365E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0341E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.6878E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.6701E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9848E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.2042E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.4327E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8866E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2928E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0693E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 67254.82195 | 67254.82195 | 5.05111 | 5.05111 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -32.70000 | 1.83376E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72404.32491 | 72404.32491 | 5.43796 | 5.43796 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 5303.85940 | 5303.85940 | 0.23498 | 1.07782 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 676134.31318 | 676134.31318 | 50.76547 | 50.76547 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 318643.84402 | 318643.84402 | 14.05252 | 14.05252 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 66367.97546 | 66367.97546 | 4.98288 | 4.98288 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 75300.35214 | 75300.35214 | 3.34293 | 3.34293 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12070.51024 | 12070.51024 | 0.91520 | 0.91520 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13139.60686 | 13139.60686 | 0.58410 | 0.58410 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17942.32039 | 17942.32039 | 1.36039 | 1.36039 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 22.10200 | 1.27119E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9020.58664 | 9020.58664 | 0.40108 | 0.40108 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 21770.63958 | 21770.63958 | 1.65067 | 1.65067 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27251E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14526.77056 | 14526.77056 | 0.64597 | 0.64597 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21783.98763 | 21783.98763 | 1.65167 | 1.65167 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7380.63874 | 7380.63874 | 0.32791 | 0.32791 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 113297.44189 | 113297.44189 | 8.59076 | 8.59076 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 194571.19438 | 194571.19438 | 8.65856 | 8.65856 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 192303.02306 | 192303.02306 | 14.58115 | 14.58115 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 129133.53933 | 129133.53933 | 5.74690 | 5.74690 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 223759.82158 | 223759.82158 | 16.96638 | 16.96638 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 196646.94102 | 196646.94102 | 8.75115 | 8.75115 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 203665.22205 | 203665.22205 | 15.44267 | 15.44267 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 126110.77306 | 126110.77306 | 5.61211 | 5.61211 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12707.81639 | 12707.81639 | 0.96358 | 0.96358 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24883.86446 | 24883.86446 | 1.10786 | 1.10786 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 19228.51691 | 19228.51691 | 1.45801 | 1.45801 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 16419.22533 | 16419.22533 | 0.73103 | 0.73103 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 23693.13758 | 23693.13758 | 1.79654 | 1.79654 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 25108.54021 | 25108.54021 | 1.11788 | 1.11788 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 21296.41934 | 21296.41934 | 1.61480 | 1.61480 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16289.05030 | 16289.05030 | 0.72523 | 0.72523 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8519.67189 | 8519.67189 | 0.50949 | 0.50949 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81894.99315 | 81894.99315 | 4.89743 | 4.89743 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8307.78883 | 8307.78883 | 0.49682 | 0.49682 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370568.85910 | 370568.85910 | 22.16011 | 22.16011 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.81600 | 1.27063E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -32.70000 | 1.83376E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 132184.86 | 9.17534 | 9.17534 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 106753.87 | 3.03688 | 3.03688 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1222640.65 | 85.05376 | 85.05376 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1068091.55 | 42.82124 | 42.82124 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 136794.57 | 9.43858 | 9.43858 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 107112.79 | 7.02495 | 7.02495 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 |
7 | CAV_BAS | Cooling | Sensible | 65849.74 | 5.05111 | 5.05111 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 101170.70 | 1.20016 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 365672.08 | 22.16025 | 22.16025 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 28525.81 | 0.33839 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8348.25 | 0.50949 | 0.50949 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1317.77 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80231.84 | 4.89743 | 4.89743 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 13177.74 | 0.15632 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8139.64 | 0.49682 | 0.49682 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1317.77 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.05111 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.43796 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34977 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61508 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93272 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08928E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82724E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61508 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20886.44983 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82724E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 435.66135 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 50.76547 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37467 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31800 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.14342 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99913 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01689E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.15032E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.14342 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 474406.81784 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.15032E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12044.93252 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.98288 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38172 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61445 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.98125E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.40941E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.34293 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 107555.29729 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.40941E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2838.40379 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91520 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26095 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20318 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69586 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46006E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.64225E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58410 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18771.94551 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64225E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 495.14437 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36039 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11313 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.60000E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13060 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30169 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36772E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12753E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40108 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12888.31203 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12753E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 339.93045 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65067 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14468 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20303 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38583 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63332E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.81585E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64597 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20756.26733 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81585E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 547.43520 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65167 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.31816E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.90000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13048 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.08879E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.22241E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32791 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10541.78067 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.22241E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 278.09981 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.65856 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27582 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.04342 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73552 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38133E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.43242E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.65856 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 278040.94400 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.43242E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7331.05170 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.58115 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60964E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61439E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.74690 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 184534.16514 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61439E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4865.47200 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.96638 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14076 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12000 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03597 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37537 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70666E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.45840E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.75115 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 281009.90273 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45840E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7409.28211 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.44267 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.96622E-002 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.50000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31263 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.82291E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57656E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.61211 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 180211.01626 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57656E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4751.54691 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10786 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21557 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23376 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57485 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76742E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.11126E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10786 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35563.65220 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.11126E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 937.55875 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45801 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10556 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.00000E-002 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13122 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60937E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05293E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73103 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23466.29456 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05293E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 618.62936 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79654 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13294 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20301 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35450 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86603E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.13938E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.11788 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35884.99305 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.13938E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 946.02597 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61480 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.53089E-002 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.10000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13080 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.99753E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03665E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72523 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23280.16058 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03665E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 613.72320 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50949 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.89743 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49682 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 22.16011 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.50795 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28236 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.01589 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.03688 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.17534 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.17534 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33098 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 53.20711 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.84773 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 106.41422 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 42.82124 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 85.05376 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 85.05376 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50346 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.48005 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.31324 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.96009 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.02495 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.43858 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.43858 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.74428 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.05111 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.05111 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.05111 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.05111 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.05111 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.05111 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.16011 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.16011 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.16011 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.16011 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.16025 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 22.16025 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50949 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50949 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50949 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50949 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50949 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50949 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.89743 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.89743 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.89743 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.89743 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.89743 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.89743 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49682 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49682 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49682 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49682 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49682 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49682 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.17534 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 85.05376 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.43858 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.05111 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 22.16025 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50949 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.89743 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49682 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.17534 |
286 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.36400 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86535 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.75365E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 190496.76215 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.44818E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.17534 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 100260.98980 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.77127E-004 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1506.58587 |
298 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.17534 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.44818E-003 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.74035E-005 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.77127E-004 |
302 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 85.05376 |
303 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.48939 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86586 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.89965E-003 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1814923.28485 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.19066E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 85.05376 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1036778.04155 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.07019E-003 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15132.05427 |
315 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 85.05376 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.19066E-002 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.17399E-006 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.07019E-003 |
319 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.43858 |
320 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.31229 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86538 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.76198E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 195616.69193 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.59461E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.43858 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 101867.31265 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.91180E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1535.65213 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.43858 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.59461E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.51159E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.91180E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.05111 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | CAV_BAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.20016 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.46583 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.36430 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00494E-002 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 106901.67495 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.05737E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.05111 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 279782.75898 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44766E-003 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5834.69675 |
350 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.05111 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.05737E-003 |
352 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.55751E-004 |
353 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.44766E-003 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.16025 |
355 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.16025 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 434218.98185 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 300031.99573 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06340E-002 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 22.16025 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 22.16025 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 22.16025 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 22.16025 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 434218.98185 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 434218.98185 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 28525.80837 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 22.16025 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.16025 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 434218.98185 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06340E-002 |
372 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28525.80837 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.04845E-004 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50949 |
378 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50949 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9815.92882 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6833.82693 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40391E-004 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50949 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50949 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50949 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50949 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9815.92882 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9815.92882 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1317.77417 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
391 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50949 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50949 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9815.92882 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40391E-004 |
395 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1317.77417 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.89743 |
397 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.89743 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94449.74012 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65718.52791 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31307E-003 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.89743 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.89743 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.89743 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.89743 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94449.74012 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94449.74012 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13177.74171 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.89743 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.89743 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94449.74012 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31307E-003 |
414 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13177.74171 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49682 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49682 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9577.95933 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6665.73305 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34564E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49682 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49682 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49682 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49682 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9577.95933 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9577.95933 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1317.77417 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49682 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49682 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9577.95933 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34564E-004 |
433 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1317.77417 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.60067E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 10670.18293 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.60067E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.92081 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.60067E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.60067E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 277063.43504 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.82267E-002 |
443 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.38721 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.82267E-002 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8416.48267 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
447 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3226487.10200 |
448 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3226487.10000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.82267E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.60067E-002 |
451 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.92081 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.30034E-002 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3693.66374 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.30034E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3693.66374 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.60067E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.31800E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1162994.85510 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1168511.32000 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.74471E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.60067E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.31800E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1162994.85510 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1168511.32000 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.74471E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34220E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.61064 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34220E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3389.39188 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34220E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58773.11791 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21365.10823 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 552872.07594 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 541884.34000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34220E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11489 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.78729 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11489 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28163.60342 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 44.42011 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1386902.01888 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.88402 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 173362.75236 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 44.42011 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1386902.01888 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.88402 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 173362.75236 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.00625E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.00625E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 19802.13 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 449322.63 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 101921.88 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17787.05 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12211.96 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19666.93 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9988.97 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 263434.37 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 174839.16 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 266247.01 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 170743.54 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33694.40 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22232.83 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33998.83 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22056.49 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 65499.66 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 653810.10 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 66804.82 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 205213.73 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 229065.76 | 157979.85 | 71085.91 | 0.69 | 39611.21 | 401.76 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2150006.36 | 1475180.36 | 674826.01 | 0.69 | 367932.82 | 3731.78 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 235511.48 | 162465.07 | 73046.41 | 0.69 | 40796.04 | 413.78 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 125334.07 | 86549.20 | 38784.87 | 0.69 | 20421.53 | 207.13 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.80 | 23.21 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.80 | 23.21 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.704 | 0.637 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.674 | 0.612 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.786 | 0.703 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.2763556076E-003 | 1.4735178367E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.4678276886E-002 | 6.1523697119E-002 | Pass | Pass | 7.1107327183E-002 | 0.2564141538 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.2551420854E-002 | 1.0080653050E-002 | Pass | Pass | 0.4980452240 | 0.4972998807 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1566864773 | 0.1706186557 | Pass | Pass | 0.5908430113 | 0.5620740651 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.3302670302E-002 | 4.3778893282E-002 | Pass | Pass | 0.1726342553 | 0.9782869889 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.2208593133E-002 | 0.1087930908 | Pass | Pass | 0.4680885613 | 3.0001881193 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1598365222 | 0.1643156465 | Pass | Pass | 0.9229535460 | 8.8911946978 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.6943642272E-002 | 9.1070323865E-002 | Pass | Pass | 7.7091242841E-002 | 0.2793932516 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.8903703409 | 0.6987980922 | Pass | Pass | 0.5753603320 | 0.5254112800 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7721954400 | 0.8085306586 | Pass | Pass | 0.5571506467 | 0.5089252993 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4997240682 | 0.5976716740 | Pass | Pass | 0.5692584029 | 0.5659256251 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7187856132 | 0.7675119403 | Pass | Pass | 0.5735838046 | 0.5525838927 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.1194458257 | 0.9024641542 | Pass | Pass | 0.5554256677 | 0.5101008207 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.0074114789 | 1.0131211407 | Pass | Pass | 0.5517293029 | 0.5002800809 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6727318154 | 0.8060989853 | Pass | Pass | 0.6313657622 | 0.9321089760 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.9611066426 | 0.9847412807 | Pass | Pass | 0.5584183336 | 0.5021963325 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3402388083E-002 | 1.5114146232E-002 | Pass | Pass | 9.2634576877E-002 | 0.3197845051 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1584189968E-002 | 5.9351128053E-002 | Pass | Pass | 0.4991745359 | 0.4914928327 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2168612214 | 0.1714256834 | Pass | Pass | 0.5100206303 | 0.4913173725 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7947551888E-003 | 8.0213828889E-003 | Pass | Pass | 0.1338201040 | 0.6164760273 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.1380408985E-002 | 4.0532743965E-002 | Pass | Pass | 9.6903634475E-003 | 1.6873319561E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5995841959E-002 | 4.1186723074E-002 | Pass | Pass | 1.1282954203E-002 | 1.7357971785E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.9973020148E-006 | 6.4806560880E-006 | Pass | Pass | 1.3389653997E-004 | 1.1961035510E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6100.60 | 319.10 | 0.00 | 28253.93 | 9214.74 | 43888.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.637 | 0.704 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.612 | 0.674 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.703 | 0.786 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.292_SHGC_EAST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.292_SHGC_EAST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.292_SHGC_EAST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.292_SHGC_WEST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.292_SHGC_WEST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.292_SHGC_WEST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.292_SHGC_NORTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.292_SHGC_EAST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.292_SHGC_WEST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.292_SHGC_NORTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.292_SHGC_EAST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.292_SHGC_WEST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 1390.74 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 1.658 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.43 | 0.0000 | Y | 7.62 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.28 | 0.0000 | Y | 4.88 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.12 | 0.0000 | Y | 7.52 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.23 | 0.0000 | Y | 4.87 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.40 | 0.0000 | Y | 76.13 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.26 | 0.0000 | Y | 48.76 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.10 | 0.0000 | Y | 75.12 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.21 | 0.0000 | Y | 48.64 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.39 | 0.0000 | Y | 7.61 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.26 | 0.0000 | Y | 4.88 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.10 | 0.0000 | Y | 7.51 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.21 | 0.0000 | Y | 4.86 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 541.18 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.55 | 42.55 | 103.47 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.52 | 63.04 | 10.88 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.52 | 47.99 | 155.08 | |
Exterior Lighting Total | 31088.59 | 269.43 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2300829.76 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3226487.10 | 0.85 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1168511.32 | 6.59 | 1025050.75 | 5.87 | 6.80 | 23.21 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1168511.32 | 6.59 | 1025050.75 | 5.87 | 6.80 | 23.21 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 541884.34 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1386902.02 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1386902.02 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 190496.76 | 229065.76 | 157979.85 | 71085.91 | 0.69 | - | 39611.21 | 401.76 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1814923.28 | 2150006.36 | 1475180.36 | 674826.01 | 0.69 | - | 367932.82 | 3731.78 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 195616.69 | 235511.48 | 162465.07 | 73046.41 | 0.69 | - | 40796.04 | 413.78 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 106901.67 | 125334.07 | 86549.20 | 38784.87 | 0.69 | - | 20421.53 | 207.13 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 434218.98 | 300032.00 | 134186.99 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9815.93 | 6833.83 | 2982.10 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94449.74 | 65718.53 | 28731.21 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9577.96 | 6665.73 | 2912.23 | 0.70 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 20886.45 | 19802.13 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 474406.82 | 449322.63 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 107555.30 | 101921.88 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18771.95 | 17787.05 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12888.31 | 12211.96 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20756.27 | 19666.93 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10541.78 | 9988.97 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 278040.94 | 263434.37 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 184534.17 | 174839.16 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 281009.90 | 266247.01 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 180211.02 | 170743.54 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 35563.65 | 33694.40 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 23466.29 | 22232.83 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35884.99 | 33998.83 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23280.16 | 22056.49 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 100260.99 | 65499.66 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1036778.04 | 653810.10 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 101867.31 | 66804.82 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 279782.76 | 205213.73 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 434218.98 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9815.93 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94449.74 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9577.96 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 28525.81 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1317.77 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 13177.74 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1317.77 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.18 | 20953.99 | 2283.73 | 1.00 | 1.12 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 85.05 | 194239.65 | 2283.73 | 1.00 | 1.07 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.44 | 21555.16 | 2283.73 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.05 | 8564.94 | 1695.65 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 22.16 | 36547.73 | 1649.25 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 570.68 | 1120.11 | 1.00 | 1.60 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.90 | 5485.66 | 1120.11 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 556.49 | 1120.11 | 1.00 | 1.61 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.066007 | 10670.18 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.028227 | 8416.48 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.033003 | 3693.66 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.033003 | 3693.66 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013422 | 3389.39 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.114894 | 28163.60 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 67254.82 | 67254.82 | 24.20 | 5.051 | 5.051 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00902 | 20.92 | 0.01271 | 1.200 | 0.00 |
CORE_BOTTOM | 72404.32 | 72404.32 | 29.01 | 5.438 | 5.438 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 20.92 | 0.01271 | 1.078 | 0.00 |
CORE_MID | 676134.31 | 676134.31 | 270.87 | 50.765 | 50.765 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 20.92 | 0.01271 | 10.778 | 0.00 |
CORE_TOP | 66367.98 | 66367.98 | 26.59 | 4.983 | 4.983 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 20.92 | 0.01271 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12070.51 | 12070.51 | 38.51 | 0.915 | 0.915 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00893 | 30.10 | 0.01273 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17942.32 | 17942.32 | 88.83 | 1.360 | 1.360 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.00 | 24.00 | 0.00869 | 22.10 | 0.01271 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 21770.64 | 21770.64 | 69.46 | 1.651 | 1.651 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00874 | 29.69 | 0.01273 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21783.99 | 21783.99 | 107.85 | 1.652 | 1.652 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00866 | 28.16 | 0.01272 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 113297.44 | 113297.44 | 361.50 | 8.591 | 8.591 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00910 | 30.10 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 192303.02 | 192303.02 | 952.11 | 14.581 | 14.581 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00874 | 23.63 | 0.01271 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 223759.82 | 223759.82 | 713.93 | 16.966 | 16.966 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00881 | 29.79 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 203665.22 | 203665.22 | 1008.37 | 15.443 | 15.443 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00873 | 27.95 | 0.01272 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12707.82 | 12707.82 | 40.55 | 0.964 | 0.964 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00909 | 30.10 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 19228.52 | 19228.52 | 95.20 | 1.458 | 1.458 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00877 | 23.63 | 0.01271 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23693.14 | 23693.14 | 75.60 | 1.797 | 1.797 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00883 | 29.89 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 21296.42 | 21296.42 | 105.44 | 1.615 | 1.615 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00874 | 27.95 | 0.01272 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8519.67 | 8519.67 | 235.33 | 0.509 | 0.509 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00858 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81894.99 | 81894.99 | 2262.12 | 4.897 | 4.897 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00859 | 24.81 | 0.01272 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8307.79 | 8307.79 | 229.48 | 0.497 | 0.497 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00859 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370568.86 | 370568.86 | 472.86 | 22.160 | 22.160 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 18.82 | 0.01271 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 21.00 | 22.94 | 0.00018 | -32.70 | 0.00018 | 1.200 | 0.00 |
CORE_BOTTOM | 5303.86 | 5303.86 | 2.12 | 0.235 | 1.078 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -32.70 | 0.00018 | 1.078 | 0.00 |
CORE_MID | 318643.84 | 318643.84 | 127.66 | 14.053 | 14.053 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 10.778 | 0.00 |
CORE_TOP | 75300.35 | 75300.35 | 30.17 | 3.343 | 3.343 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13139.61 | 13139.61 | 41.92 | 0.584 | 0.584 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9020.59 | 9020.59 | 44.66 | 0.401 | 0.401 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14526.77 | 14526.77 | 46.35 | 0.646 | 0.646 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7380.64 | 7380.64 | 36.54 | 0.328 | 0.328 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 194571.19 | 194571.19 | 620.81 | 8.659 | 8.659 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 129133.54 | 129133.54 | 639.35 | 5.747 | 5.747 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 196646.94 | 196646.94 | 627.42 | 8.751 | 8.751 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 126110.77 | 126110.77 | 624.39 | 5.612 | 5.612 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24883.86 | 24883.86 | 79.40 | 1.108 | 1.108 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16419.23 | 16419.23 | 81.29 | 0.731 | 0.731 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25108.54 | 25108.54 | 80.11 | 1.118 | 1.118 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16289.05 | 16289.05 | 80.65 | 0.725 | 0.725 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -32.70 | 0.00018 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.50 | 0.00082 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.43 | 0.00082 | -32.70 | 0.00018 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.01 | 0.00082 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 18.00 | 27.00 | 0.00850 | -32.70 | 0.00018 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.18 | 9.18 | 3.04 | 3.04 | 9.1753 | 3.0369 | 9.1753 | 0.3310 | 0.3000 |
VAV_MID WITH REHEAT | 85.05 | 85.05 | 42.82 | 42.82 | 85.0538 | 42.8212 | 85.0538 | 0.5035 | 0.3000 |
VAV_TOP WITH REHEAT | 9.44 | 9.44 | 7.02 | 7.02 | 9.4386 | 7.0249 | 9.4386 | 0.7443 | 0.3000 |
CAV_BAS | 5.05 | 5.05 | 1.20 | 1.20 | 5.0511 | 5.0511 | 5.0511 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.16 | 22.16 | 0.34 | 0.34 | 22.1603 | 22.1601 | 22.1603 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5095 | 0.5095 | 0.5095 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.90 | 4.90 | 0.16 | 0.16 | 4.8974 | 4.8974 | 4.8974 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.50 | 0.50 | 0.02 | 0.02 | 0.4968 | 0.4968 | 0.4968 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20886.450 | 20886.450 | 1.615075 | 0.00018272 | 435.661 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20886.45 | 20886.45 | 1.615075 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00797276 | 49.3929 | 5303.86 | 0.00 | 20962.18 | 20962.18 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 474406.818 | 474406.818 | 16.143418 | 0.00415032 | 12044.933 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 474406.82 | 474406.82 | 16.143418 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 318643.84 | 0.00 | 475873.83 | 475873.83 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 107555.297 | 107555.297 | 3.342932 | 0.00094094 | 2838.404 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 107555.30 | 107555.30 | 3.342932 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 75300.35 | 0.00 | 107921.75 | 107921.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18771.946 | 18771.946 | 0.584097 | 0.00016423 | 495.144 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18771.95 | 18771.95 | 0.584097 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773725 | 47.9550 | 13139.61 | 0.00 | 18834.10 | 18834.10 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12888.312 | 12888.312 | 0.401083 | 0.00011275 | 339.930 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12888.31 | 12888.31 | 0.401083 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00775626 | 48.0712 | 9020.59 | 0.00 | 12930.83 | 12930.83 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 20756.267 | 20756.267 | 0.645967 | 0.00018158 | 547.435 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20756.27 | 20756.27 | 0.645967 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00777780 | 48.2029 | 14526.77 | 0.00 | 20824.64 | 20824.64 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10541.781 | 10541.781 | 0.327906 | 0.00009222 | 278.100 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10541.78 | 10541.78 | 0.327906 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00762553 | 47.2721 | 7380.64 | 0.00 | 10576.98 | 10576.98 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 278040.944 | 278040.944 | 8.658557 | 0.00243242 | 7331.052 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 278040.94 | 277120.92 | 8.658557 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00764068 | 47.3661 | 194571.19 | 0.00 | 278941.47 | 278941.47 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 184534.165 | 184534.165 | 5.746905 | 0.00161439 | 4865.472 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 184534.17 | 184534.17 | 5.746905 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00763973 | 47.3604 | 129133.54 | 0.00 | 185131.08 | 185131.08 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 281009.903 | 281009.903 | 8.751148 | 0.00245840 | 7409.282 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 281009.90 | 281009.90 | 8.751148 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00764452 | 47.3896 | 196646.94 | 0.00 | 281919.67 | 281919.67 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 180211.016 | 180211.016 | 5.612114 | 0.00157656 | 4751.547 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180211.02 | 180211.02 | 5.612114 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00763100 | 47.3070 | 126110.77 | 0.00 | 180794.38 | 180794.38 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 35563.652 | 35563.652 | 1.107864 | 0.00031113 | 937.559 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35563.65 | 35457.66 | 1.107864 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00765283 | 47.4415 | 24883.86 | 0.00 | 35677.82 | 35677.82 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 23466.295 | 23466.295 | 0.731034 | 0.00020529 | 618.629 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23466.29 | 23466.29 | 0.731034 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00764939 | 47.4205 | 16419.23 | 0.00 | 23541.56 | 23541.56 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 35884.993 | 35884.993 | 1.117885 | 0.00031394 | 946.026 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35884.99 | 35884.99 | 1.117885 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00765582 | 47.4597 | 25108.54 | 0.00 | 36000.16 | 36000.16 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23280.161 | 23280.161 | 0.725234 | 0.00020366 | 613.723 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23280.16 | 23280.16 | 0.725234 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00764685 | 47.4050 | 16289.05 | 0.00 | 23354.84 | 23354.84 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 190496.762 | -999.000 | 9.175345 | 0.00544818 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 190496.76 | 156500.80 | 9.175345 | 25.36 | 17.45 | 0.00975365 | 10.87 | 10.87 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 22.1300 | 24.00 | 0.00889675 | 45.8688 | 119670.03 | 0.00 | 196560.58 | 154267.36 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 100260.990 | 100260.990 | 2.752603 | 0.00087713 | 1506.586 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 100260.99 | 100260.99 | 2.752603 | -18.61 | -18.61 | 0.00218550 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 73.7665 | 18.42 | 0.00764669 | 55.6162 | 23516.08 | 0.00 | 79222.05 | 79222.05 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1814923.285 | -999.000 | 85.053764 | 0.05190658 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1814923.28 | 1463113.02 | 85.053764 | 25.49 | 17.61 | 0.00989965 | 10.87 | 10.87 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 23.8743 | 24.00 | 0.00898566 | 46.3214 | 1095920.38 | 0.00 | 1871968.42 | 1443452.27 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1036778.042 | 1036778.042 | 25.516129 | 0.00907019 | 15132.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1036778.04 | 1036778.04 | 25.516129 | -22.24 | -22.24 | 0.00168012 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 79.5810 | 17.86 | 0.00745559 | 56.2161 | 283682.09 | 0.00 | 790572.24 | 790572.24 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 195616.692 | -999.000 | 9.438584 | 0.00559461 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 195616.69 | 160414.17 | 9.438584 | 25.31 | 17.44 | 0.00976198 | 10.87 | 10.87 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 21.5128 | 24.00 | 0.00894851 | 46.1328 | 124351.32 | 0.00 | 201853.88 | 158126.22 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 101867.313 | 101867.313 | 2.831575 | 0.00089118 | 1535.652 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101867.31 | 101867.31 | 2.831575 | -18.23 | -18.23 | 0.00223799 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 71.7092 | 16.52 | 0.00752268 | 61.7051 | 27415.72 | 0.00 | 80802.82 | 80802.82 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 106901.675 | -999.000 | 5.051110 | 0.00305737 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 106901.67 | 84400.16 | 5.051110 | 25.47 | 17.72 | 0.01004939 | 11.36 | 11.13 | 0.00850000 | 29.48 | 0.01272477 | 20.95 | 23.7602 | 24.00 | 0.00907153 | 46.7568 | 59136.20 | 0.00 | 110234.59 | 84214.92 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 279782.759 | 279782.759 | 5.051110 | 0.00244766 | 5834.697 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 279782.76 | 279782.76 | 5.051110 | -7.77 | -11.40 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 23.7602 | 23.04 | 0.00018338 | 1.0155 | 0.00 | 0.00 | 216471.85 | 216471.85 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434218.982 | 300031.996 | 22.160253 | 0.01063399 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 401331.40 | 395334.75 | -999.0 | 28.50 | 17.57 | 0.00860634 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | -999.0000 | 27.00 | 0.00854240 | 36.8776 | 370178.85 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9815.929 | 6833.827 | 0.509486 | 0.00024039 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 9045.72 | 8771.95 | -999.0 | 27.92 | 17.46 | 0.00871165 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858488 | 37.0560 | 8519.67 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94449.740 | 65718.528 | 4.897435 | 0.00231307 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 87052.63 | 84316.54 | -999.0 | 27.92 | 17.47 | 0.00872003 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858825 | 37.0706 | 81894.99 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9577.959 | 6665.733 | 0.496816 | 0.00023456 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 8827.33 | 8553.58 | -999.0 | 27.92 | 17.47 | 0.00871702 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858708 | 37.0655 | 8307.79 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434218.982 | 434218.982 | 22.160253 | 0.01063399 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 434218.98 | 434218.98 | 22.160253 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.5270 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9815.929 | 9815.929 | 0.509486 | 0.00024039 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9815.93 | 9815.93 | 0.509486 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0683 | 25.31 | 0.00082456 | 3.9817 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94449.740 | 94449.740 | 4.897435 | 0.00231307 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 94449.74 | 94449.74 | 4.897435 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.1919 | 23.64 | 0.00082458 | 4.3992 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9577.959 | 9577.959 | 0.496816 | 0.00023456 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9577.96 | 9577.96 | 0.496816 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.1465 | 22.23 | 0.00082394 | 4.7888 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 28525.808 | 28525.808 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 28525.81 | 28525.81 | 22.160253 | -0.50 | -0.50 | 0.00837300 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.5270 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1317.77 | 1317.77 | 0.509486 | -1.00 | -5.62 | 0.00080489 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0683 | 25.31 | 0.00082456 | 3.9817 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 13177.742 | 13177.742 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13177.74 | 13177.74 | 4.897435 | -1.04 | -5.65 | 0.00080411 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.1919 | 23.64 | 0.00082458 | 4.3992 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1317.77 | 1317.77 | 0.496816 | -1.03 | -5.64 | 0.00080379 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.1465 | 22.23 | 0.00082394 | 4.7888 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 20886.450 | 20886.450 | 1.615075 | 0.00018272 | 435.661 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 0.6346 | 0.647343 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20886.45 | 20886.45 | 1.0000 | 1.86367548 | 1.615075 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.18270513 | 60.00 | 32.22 | 27.78 | 0.000 | 20886.45 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.87 | 0.00797276 | 21.00 | 0.00797276 | 49.3929 | 5303.86 | 0.00 | 20962.18 | 20962.18 | 1.86367548 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.83 | 15.89 | 0.00800000 | 44307.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 474406.818 | 474406.818 | 16.143418 | 0.00415032 | 12044.933 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 14.4134 | 14.703509 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 474406.82 | 474406.82 | 1.0000 | 18.62829119 | 16.143418 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 4.14989442 | 60.00 | 32.22 | 27.78 | 0.000 | 474406.82 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 318643.84 | 0.00 | 475873.83 | 475873.83 | 18.62829119 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.85 | 20.54 | 0.00800000 | 58605.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 107555.297 | 107555.297 | 3.342932 | 0.00094094 | 2838.404 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 3.2677 | 3.333511 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 107555.30 | 107555.30 | 1.0000 | 3.85749255 | 3.342932 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.94084467 | 60.00 | 32.22 | 27.78 | 0.000 | 107555.30 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 75300.35 | 0.00 | 107921.75 | 107921.75 | 3.85749255 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61037.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18771.946 | 18771.946 | 0.584097 | 0.00016423 | 495.144 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 0.5703 | 0.581808 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18771.95 | 18771.95 | 1.0000 | 0.67400422 | 0.584097 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.16420842 | 60.00 | 32.22 | 27.78 | 0.000 | 18771.95 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00773725 | 21.00 | 0.00773725 | 47.9550 | 13139.61 | 0.00 | 18834.10 | 18834.10 | 0.67400422 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12888.312 | 12888.312 | 0.401083 | 0.00011275 | 339.930 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 0.3916 | 0.399453 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12888.31 | 12888.31 | 1.0000 | 0.46281960 | 0.401083 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.11274107 | 60.00 | 32.22 | 27.78 | 0.000 | 12888.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00775626 | 21.00 | 0.00775626 | 48.0712 | 9020.59 | 0.00 | 12930.83 | 12930.83 | 0.46281960 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20756.267 | 20756.267 | 0.645967 | 0.00018158 | 547.435 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 0.6306 | 0.643309 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20756.27 | 20756.27 | 1.0000 | 0.74539773 | 0.645967 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.18156636 | 60.00 | 32.22 | 27.78 | 0.000 | 20756.27 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00777780 | 21.00 | 0.00777780 | 48.2029 | 14526.77 | 0.00 | 20824.64 | 20824.64 | 0.74539773 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10541.781 | 10541.781 | 0.327906 | 0.00009222 | 278.100 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 0.3203 | 0.326726 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10541.78 | 10541.78 | 1.0000 | 0.37837909 | 0.327906 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.09221469 | 60.00 | 32.22 | 27.78 | 0.000 | 10541.78 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00762553 | 21.00 | 0.00762553 | 47.2721 | 7380.64 | 0.00 | 10576.98 | 10576.98 | 0.37837909 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 278040.944 | 278040.944 | 8.658557 | 0.00243242 | 7331.052 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 8.4474 | 8.617451 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 278040.94 | 277120.92 | 1.0000 | 9.99132429 | 8.658557 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.43217534 | 60.00 | 32.22 | 27.78 | 0.000 | 278040.94 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764068 | 21.00 | 0.00764068 | 47.3661 | 194571.19 | 0.00 | 278941.47 | 278941.47 | 9.99132429 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 184534.165 | 184534.165 | 5.746905 | 0.00161439 | 4865.472 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 5.6065 | 5.719352 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 184534.17 | 184534.17 | 1.0000 | 6.63149606 | 5.746905 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 1.61422069 | 60.00 | 32.22 | 27.78 | 0.000 | 184534.17 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00763973 | 21.00 | 0.00763973 | 47.3604 | 129133.54 | 0.00 | 185131.08 | 185131.08 | 6.63149606 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 281009.903 | 281009.903 | 8.751148 | 0.00245840 | 7409.282 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 8.5376 | 8.709469 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 281009.90 | 281009.90 | 1.0000 | 10.09816679 | 8.751148 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.45814643 | 60.00 | 32.22 | 27.78 | 0.000 | 281009.90 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764452 | 21.00 | 0.00764452 | 47.3896 | 196646.94 | 0.00 | 281919.67 | 281919.67 | 10.09816679 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60977.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 180211.016 | 180211.016 | 5.612114 | 0.00157656 | 4751.547 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 5.4752 | 5.585363 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 180211.02 | 180211.02 | 1.0000 | 6.47595835 | 5.612114 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 1.57640376 | 60.00 | 32.22 | 27.78 | 0.000 | 180211.02 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00763100 | 21.00 | 0.00763100 | 47.3070 | 126110.77 | 0.00 | 180794.38 | 180794.38 | 6.47595835 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35563.652 | 35563.652 | 1.107864 | 0.00031113 | 937.559 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 1.0805 | 1.102241 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35563.65 | 35457.66 | 1.0000 | 1.27839133 | 1.107864 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.31109461 | 60.00 | 32.22 | 27.78 | 0.000 | 35563.65 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00765283 | 21.00 | 0.00765283 | 47.4415 | 24883.86 | 0.00 | 35677.82 | 35677.82 | 1.27839133 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60968.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23466.295 | 23466.295 | 0.731034 | 0.00020529 | 618.629 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 0.7130 | 0.727302 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23466.29 | 23466.29 | 1.0000 | 0.84355886 | 0.731034 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.20527244 | 60.00 | 32.22 | 27.78 | 0.000 | 23466.29 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764939 | 21.00 | 0.00764939 | 47.4205 | 16419.23 | 0.00 | 23541.56 | 23541.56 | 0.84355886 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60967.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35884.993 | 35884.993 | 1.117885 | 0.00031394 | 946.026 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 1.0903 | 1.112200 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35884.99 | 35884.99 | 1.0000 | 1.28995507 | 1.117885 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.31390555 | 60.00 | 32.22 | 27.78 | 0.000 | 35884.99 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00765582 | 21.00 | 0.00765582 | 47.4597 | 25108.54 | 0.00 | 36000.16 | 36000.16 | 1.28995507 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60967.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23280.161 | 23280.161 | 0.725234 | 0.00020366 | 613.723 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 0.7073 | 0.721533 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23280.16 | 23280.16 | 1.0000 | 0.83686542 | 0.725234 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.20364422 | 60.00 | 32.22 | 27.78 | 0.000 | 23280.16 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764685 | 21.00 | 0.00764685 | 47.4050 | 16289.05 | 0.00 | 23354.84 | 23354.84 | 0.83686542 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60967.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 190496.762 | -999.000 | 9.175345 | 0.00544818 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9716 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.175345 | 10.58765848 | 4197.9300 | 999.8980 | 66.00001311 | 15.00 | 6.67 | 8.33 | 2307938.41 | 8.2540 | 8.253979 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 190496.76 | 156500.80 | 1.0000 | 10.58765848 | 9.175345 | 25.36 | 17.45 | 0.00975365 | 50339.9 | 10.87 | 10.87 | 0.00850000 | 32347.6 | 5.44762751 | 6.67 | 15.00 | 8.33 | 20953.990 | 169542.77 | 30.10 | 0.01272586 | 21.13 | 2.03050000 | 22.1300 | 24.00 | 0.00889675 | 24.00 | 0.00889675 | 45.8688 | 119670.03 | 0.00 | 196560.58 | 154267.36 | 10.58765848 | 25.36 | 17.91 | 0.00975365 | 50339.9 | 11.12 | 11.06 | 0.00816952 | 31774.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100260.990 | 100260.990 | 2.752603 | 0.00087713 | 1506.586 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.175345 | 10.58765848 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 3.0461 | 3.107435 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 100260.99 | 100260.99 | 1.0000 | 3.17629754 | 2.752603 | -18.61 | -18.61 | 0.00218550 | -13312.6 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 0.87703740 | 60.00 | 32.22 | 27.78 | 0.000 | 100260.99 | -32.70 | 0.00018338 | -32.70 | 2.03050000 | 73.7665 | 21.00 | 0.00781531 | 18.42 | 0.00764669 | 55.6162 | 23516.08 | 0.00 | 79222.05 | 79222.05 | 3.17629754 | 2.80 | -0.89 | 0.00218550 | 8290.7 | 27.52 | 11.79 | 0.00218550 | 33232.4 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1814923.285 | -999.000 | 85.053764 | 0.05190658 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2430 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 85.053764 | 98.14565290 | 4197.9300 | 999.8980 | 66.00001311 | 15.00 | 6.67 | 8.33 | 2307938.41 | 78.6383 | 78.638289 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1814923.28 | 1463113.02 | 1.0000 | 98.14565290 | 85.053764 | 25.49 | 17.61 | 0.00989965 | 50840.3 | 10.87 | 10.87 | 0.00850000 | 32348.1 | 51.90128119 | 6.67 | 15.00 | 8.33 | 194239.647 | 1620683.64 | 30.10 | 0.01272586 | 21.13 | 20.30600000 | 23.8743 | 24.00 | 0.00898566 | 24.00 | 0.00898566 | 46.3214 | 1095920.38 | 0.00 | 1871968.42 | 1443452.27 | 98.14565290 | 25.49 | 18.07 | 0.00989965 | 50840.3 | 11.12 | 11.05 | 0.00816817 | 31766.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1036778.042 | 1036778.042 | 25.516129 | 0.00907019 | 15132.054 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 85.053764 | 98.14565290 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 31.4994 | 32.133339 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1036778.04 | 1036778.04 | 1.0000 | 29.44369587 | 25.516129 | -22.24 | -22.24 | 0.00168012 | -18217.2 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 9.06926134 | 60.00 | 32.22 | 27.78 | 0.000 | 1036778.04 | -32.70 | 0.00018338 | -32.70 | 20.30600000 | 79.5810 | 18.52 | 0.00751356 | 17.86 | 0.00745559 | 56.2161 | 283682.09 | 0.00 | 790572.24 | 790572.24 | 29.44369587 | 2.80 | -1.69 | 0.00168012 | 7024.2 | 29.44 | 12.07 | 0.00168012 | 33874.5 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 195616.692 | -999.000 | 9.438584 | 0.00559461 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9870 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.438584 | 10.89141713 | 4197.9300 | 999.8980 | 66.00001311 | 15.00 | 6.67 | 8.33 | 2307938.41 | 8.4758 | 8.475819 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 195616.69 | 160414.17 | 1.0000 | 10.89141713 | 9.438584 | 25.31 | 17.44 | 0.00976198 | 50308.3 | 10.87 | 10.87 | 0.00850000 | 32347.6 | 5.59404192 | 6.67 | 15.00 | 8.33 | 21555.158 | 174061.53 | 30.10 | 0.01272586 | 21.13 | 2.03050000 | 21.5128 | 24.00 | 0.00894851 | 24.00 | 0.00894851 | 46.1328 | 124351.32 | 0.00 | 201853.88 | 158126.22 | 10.89141713 | 25.31 | 17.90 | 0.00976198 | 50308.3 | 11.12 | 11.06 | 0.00816979 | 31775.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 101867.313 | 101867.313 | 2.831575 | 0.00089118 | 1535.652 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.438584 | 10.89141713 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 3.0949 | 3.157221 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101867.31 | 101867.31 | 1.0000 | 3.26742514 | 2.831575 | -18.23 | -18.23 | 0.00223799 | -12792.9 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 0.89108878 | 60.00 | 32.22 | 27.78 | 0.000 | 101867.31 | -32.70 | 0.00018338 | -32.70 | 2.03050000 | 71.7092 | 18.46 | 0.00744585 | 16.52 | 0.00752268 | 61.7051 | 27415.72 | 0.00 | 80802.82 | 80802.82 | 3.26742514 | 2.80 | -0.81 | 0.00223799 | 8422.3 | 27.31 | 11.76 | 0.00223799 | 33152.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 106901.675 | -999.000 | 5.051110 | 0.00305737 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5213 | 1004.8586 | 1.1539 | CAV_BAS FAN | Fan:ConstantVolume | 5.051110 | 5.82860171 | 4197.9300 | 999.8980 | 66.00001311 | 15.00 | 6.67 | 8.33 | 2307938.41 | 4.6319 | 4.631912 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 106901.67 | 84400.16 | 1.0000 | 5.82860171 | 5.051110 | 25.47 | 17.72 | 0.01004939 | 51197.7 | 11.36 | 11.13 | 0.00850000 | 32856.9 | 3.05706249 | 6.67 | 15.00 | 8.33 | 8564.937 | 98336.74 | 29.48 | 0.01272477 | 20.95 | 1.20015641 | 23.7602 | 24.00 | 0.00907153 | 24.00 | 0.00907153 | 46.7568 | 59136.20 | 0.00 | 110234.59 | 84214.92 | 5.82860171 | 25.47 | 18.18 | 0.01004939 | 51197.7 | 11.35 | 11.27 | 0.00827934 | 32285.0 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 279782.759 | 279782.759 | 5.051110 | 0.00244766 | 5834.697 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | CAV_BAS FAN | Fan:ConstantVolume | 5.051110 | 5.82860171 | 4197.9300 | 999.8980 | 28.22383727 | 54.44 | 82.22 | 27.78 | 3291421.44 | 8.5004 | 8.671436 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 279782.76 | 279782.76 | 1.0000 | 5.82860171 | 5.051110 | -7.77 | -11.40 | 0.00018338 | -7351.2 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.44741194 | 60.00 | 32.22 | 27.78 | 0.000 | 279782.76 | -32.70 | 0.00018338 | -32.70 | 1.20015641 | 23.7602 | 0.00 | 0.00018338 | 23.04 | 0.00018338 | 1.0155 | 0.00 | 0.00 | 216471.85 | 216471.85 | 5.82860171 | 12.80 | 2.24 | 0.00018338 | 13324.9 | 49.75 | 18.20 | 0.00018338 | 50464.5 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 434218.982 | 300031.996 | 22.160253 | 0.01063399 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8388 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 401331.40 | 395334.75 | 0.9243 | -999.0 | -999.0 | 28.50 | 17.57 | 0.00860634 | 50616.1 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 401331.40 | 30.10 | 0.01272586 | 21.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854240 | 27.00 | 0.00854240 | 36.8776 | 370178.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9815.929 | 6833.827 | 0.509486 | 0.00024039 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0345 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 9045.72 | 8771.95 | 0.9215 | -999.0 | -999.0 | 27.92 | 17.46 | 0.00871165 | 50292.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9045.72 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | -999.0000 | 27.00 | 0.00858488 | 27.00 | 0.00858488 | 37.0560 | 8519.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94449.740 | 65718.528 | 4.897435 | 0.00231307 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0501 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 87052.63 | 84316.54 | 0.9217 | -999.0 | -999.0 | 27.92 | 17.47 | 0.00872003 | 50311.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87052.63 | 24.81 | 0.01271660 | 19.55 | 0.15632344 | -999.0000 | 27.00 | 0.00858825 | 27.00 | 0.00858825 | 37.0706 | 81894.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9577.959 | 6665.733 | 0.496816 | 0.00023456 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0445 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 8827.33 | 8553.58 | 0.9216 | -999.0 | -999.0 | 27.92 | 17.47 | 0.00871702 | 50304.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8827.33 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | -999.0000 | 27.00 | 0.00858708 | 27.00 | 0.00858708 | 37.0655 | 8307.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 434218.982 | 434218.982 | 22.160253 | 0.01063399 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 434218.98 | 434218.98 | 1.0000 | 25.57126700 | 22.160253 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 434218.98 | -32.70 | 0.00018338 | -32.70 | 0.33839277 | 1.5270 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9815.929 | 9815.929 | 0.509486 | 0.00024039 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9815.93 | 9815.93 | 1.0000 | 0.58790809 | 0.509486 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9815.93 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 3.0683 | 0.00 | 0.00082456 | 25.31 | 0.00082456 | 3.9817 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94449.740 | 94449.740 | 4.897435 | 0.00231307 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 94449.74 | 94449.74 | 1.0000 | 5.65127189 | 4.897435 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94449.74 | -32.70 | 0.00018338 | -32.70 | 0.15632344 | 3.1919 | 0.00 | 0.00082458 | 23.64 | 0.00082458 | 4.3992 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9577.959 | 9577.959 | 0.496816 | 0.00023456 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9577.96 | 9577.96 | 1.0000 | 0.57328843 | 0.496816 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9577.96 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 3.1465 | 0.00 | 0.00082394 | 22.23 | 0.00082394 | 4.7888 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28525.808 | 28525.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 22.160253 | 25.57126700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 28525.81 | 28525.81 | 1.0000 | 25.57126700 | 22.160253 | -0.50 | -0.50 | 0.00837300 | 20430.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28525.81 | -32.70 | 0.00018338 | -32.70 | 0.33839277 | 1.5270 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.509486 | 0.58790809 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1317.77 | 1317.77 | 1.0000 | 0.58790809 | 0.509486 | -1.00 | -5.62 | 0.00080489 | 1003.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1317.77 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 3.0683 | 0.00 | 0.00082456 | 25.31 | 0.00082456 | 3.9817 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13177.742 | 13177.742 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.897435 | 5.65127189 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13177.74 | 13177.74 | 1.0000 | 5.65127189 | 4.897435 | -1.04 | -5.65 | 0.00080411 | 960.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13177.74 | -32.70 | 0.00018338 | -32.70 | 0.15632344 | 3.1919 | 0.00 | 0.00082458 | 23.64 | 0.00082458 | 4.3992 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.496816 | 0.57328843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1317.77 | 1317.77 | 1.0000 | 0.57328843 | 0.496816 | -1.03 | -5.64 | 0.00080379 | 974.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1317.77 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 3.1465 | 0.00 | 0.00082394 | 22.23 | 0.00082394 | 4.7888 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.18 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 85.05 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.44 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.05 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 22.16 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1977.50 | 2773.67 | 501.50 |
CORE_BOTTOM | 1870.50 | 2376.50 | 9.50 |
CORE_MID | 2055.67 | 3568.83 | 623.17 |
CORE_TOP | 2977.33 | 4049.33 | 1706.17 |
PERIMETER_BOT_ZN_3 | 2740.50 | 3646.33 | 1125.17 |
PERIMETER_BOT_ZN_2 | 2969.17 | 3435.67 | 1173.67 |
PERIMETER_BOT_ZN_1 | 2964.00 | 3138.17 | 1030.50 |
PERIMETER_BOT_ZN_4 | 2792.17 | 2660.00 | 694.33 |
PERIMETER_MID_ZN_3 | 3718.83 | 4148.67 | 2456.00 |
PERIMETER_MID_ZN_2 | 3303.17 | 3252.50 | 1968.00 |
PERIMETER_MID_ZN_1 | 3441.17 | 3501.33 | 1720.17 |
PERIMETER_MID_ZN_4 | 3732.33 | 3733.00 | 2074.50 |
PERIMETER_TOP_ZN_3 | 3995.67 | 4417.33 | 2865.67 |
PERIMETER_TOP_ZN_2 | 4084.17 | 3964.17 | 2604.00 |
PERIMETER_TOP_ZN_1 | 3695.17 | 3815.00 | 2161.17 |
PERIMETER_TOP_ZN_4 | 3956.33 | 3987.33 | 2461.00 |
DATACENTER_BOT_ZN_6 | 5662.83 | 596.83 | 593.33 |
DATACENTER_MID_ZN_6 | 4384.00 | 569.50 | 146.17 |
DATACENTER_TOP_ZN_6 | 3931.83 | 960.67 | 272.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5432.50 | 5432.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5941.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 31.33 | 0.00 | 1.83 |
CORE_BOTTOM | 0.00 | 2.67 | 0.00 | 2.17 |
CORE_MID | 3.83 | 0.67 | 1.67 | 0.67 |
CORE_TOP | 41.83 | 0.67 | 11.67 | 0.67 |
PERIMETER_BOT_ZN_3 | 11.00 | 5.83 | 1.50 | 5.83 |
PERIMETER_BOT_ZN_2 | 10.33 | 27.33 | 0.17 | 27.00 |
PERIMETER_BOT_ZN_1 | 12.50 | 44.17 | 0.50 | 43.33 |
PERIMETER_BOT_ZN_4 | 3.17 | 103.83 | 0.00 | 53.33 |
PERIMETER_MID_ZN_3 | 277.17 | 4.00 | 113.17 | 4.00 |
PERIMETER_MID_ZN_2 | 255.17 | 28.50 | 20.67 | 28.00 |
PERIMETER_MID_ZN_1 | 93.50 | 41.17 | 7.83 | 39.83 |
PERIMETER_MID_ZN_4 | 91.17 | 36.17 | 14.00 | 18.83 |
PERIMETER_TOP_ZN_3 | 488.67 | 2.17 | 192.83 | 1.83 |
PERIMETER_TOP_ZN_2 | 268.17 | 25.33 | 56.67 | 24.33 |
PERIMETER_TOP_ZN_1 | 231.50 | 33.50 | 44.00 | 31.67 |
PERIMETER_TOP_ZN_4 | 203.67 | 34.83 | 43.00 | 18.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 6.83 | 0.00 | 3.33 |
DATACENTER_MID_ZN_6 | 0.00 | 5.17 | 0.00 | 2.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 4.50 | 0.00 | 1.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 201.17 | 0.00 | 185.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 709.83 | 434.83 | 219.00 | 327.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 1.048 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.829 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.643 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.618 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.849 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 1.213 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 1.294 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 1.738 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.747 | 0.104 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.110 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 1.226 | 0.104 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.178 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.811 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 1.210 | 0.134 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 1.224 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.205 | 0.134 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 22.881 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.29 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.88 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.28 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1015.76 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42438801.79 | 0.00 | 42438801.79 | 0.00 | 42438801.79 | 37848132.68 | 4125.05 | 1718.52 | 2916.44 | 221.49 |
CORE_BOTTOM | 35265582.06 | 0.00 | 35265582.06 | 0.00 | 35265582.06 | 33990283.35 | 4110.26 | 377.90 | 4271.84 | 493.67 |
CORE_MID | 0.27E+09 | 0.00 | 0.27E+09 | 0.00 | 0.27E+09 | 0.34E+09 | 5111.95 | 1000.35 | 2647.70 | 531.06 |
CORE_TOP | 25257859.93 | 0.00 | 25257859.93 | 0.00 | 25257859.93 | 33990283.35 | 5548.27 | 1294.12 | 1917.60 | 422.85 |
PERIMETER_BOT_ZN_3 | 4519566.92 | 0.00 | 4519566.92 | 431999.69 | 4951566.60 | 4267819.30 | 5307.98 | 358.29 | 3093.73 | 493.67 |
PERIMETER_BOT_ZN_2 | 4086902.24 | 0.00 | 4086902.24 | 287999.59 | 4374901.84 | 2750345.05 | 5115.41 | 431.41 | 3213.17 | 493.67 |
PERIMETER_BOT_ZN_1 | 6753110.51 | 0.00 | 6753110.51 | 431999.69 | 7185110.19 | 4267912.63 | 4806.48 | 372.42 | 3581.10 | 493.67 |
PERIMETER_BOT_ZN_4 | 5892210.19 | 0.00 | 5892210.19 | 287999.59 | 6180209.79 | 2750345.05 | 4243.65 | 442.02 | 4074.33 | 493.67 |
PERIMETER_MID_ZN_3 | 38710532.43 | 0.00 | 38710532.43 | 1013169.02 | 39723701.45 | 42678193.03 | 4763.17 | 357.14 | 3639.68 | 531.06 |
PERIMETER_MID_ZN_2 | 37152374.15 | 0.00 | 37152374.15 | 675445.55 | 37827819.70 | 27503450.52 | 4959.95 | 568.15 | 3231.90 | 994.06 |
PERIMETER_MID_ZN_1 | 62655168.96 | 0.00 | 62655168.96 | 1013169.02 | 63668337.98 | 42679126.28 | 4352.35 | 715.69 | 3691.96 | 531.06 |
PERIMETER_MID_ZN_4 | 39286826.40 | 0.00 | 39286826.40 | 675445.55 | 39962271.95 | 27503450.52 | 4581.37 | 655.95 | 3522.68 | 531.06 |
PERIMETER_TOP_ZN_3 | 4161113.88 | 0.00 | 4161113.88 | 1257968.18 | 5419082.06 | 4267819.30 | 4187.83 | 26.18 | 4545.99 | 422.83 |
PERIMETER_TOP_ZN_2 | 3955474.21 | 0.00 | 3955474.21 | 838644.88 | 4794119.09 | 2750345.05 | 4516.62 | 1041.18 | 3202.20 | 422.83 |
PERIMETER_TOP_ZN_1 | 6210774.65 | 0.00 | 6210774.65 | 1257968.18 | 7468742.83 | 4267912.63 | 4493.44 | 1248.99 | 3017.57 | 422.83 |
PERIMETER_TOP_ZN_4 | 3986139.19 | 0.00 | 3986139.19 | 838644.88 | 4824784.07 | 2750345.05 | 4594.71 | 1249.50 | 2915.79 | 422.83 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.36E+09 | 0.00 | 0.36E+09 | 0.00 | 0.36E+09 | 10671554.30 | 12.67 | 94.00 | 8653.33 | 2813.67 |
Total Facility | 0.50E+10 | 0.00 | 0.50E+10 | 39405516.14 | 0.50E+10 | 0.50E+10 | 7163.47 | 4373.93 | 8747.44 | 3276.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.9281 | 0.0000 | 1.9281 | 0.0000 | 1.9281 | 1.2002 | 1403.43 | 1716.77 | 2822.79 |
CORE_BOTTOM | 1.5410 | 0.0000 | 1.5410 | 0.0000 | 1.5410 | 1.0778 | 1641.65 | 371.87 | 3929.49 |
CORE_MID | 11.9743 | 0.0000 | 11.9743 | 0.0000 | 11.9743 | 10.7782 | 2399.66 | 999.59 | 2543.75 |
CORE_TOP | 1.1528 | 0.0000 | 1.1528 | 0.0000 | 1.1528 | 1.0778 | 2810.45 | 1293.96 | 1838.59 |
PERIMETER_BOT_ZN_3 | 0.1983 | 0.0000 | 0.1983 | 0.0105 | 0.2088 | 0.1353 | 2832.97 | 352.44 | 2757.59 |
PERIMETER_BOT_ZN_2 | 0.1827 | 0.0000 | 0.1827 | 0.0070 | 0.1897 | 0.0872 | 2642.24 | 424.96 | 2875.80 |
PERIMETER_BOT_ZN_1 | 0.3026 | 0.0000 | 0.3026 | 0.0105 | 0.3131 | 0.1353 | 2332.61 | 366.42 | 3243.96 |
PERIMETER_BOT_ZN_4 | 0.2614 | 0.0000 | 0.2614 | 0.0070 | 0.2684 | 0.0872 | 1781.71 | 436.78 | 3724.51 |
PERIMETER_MID_ZN_3 | 1.7500 | 0.0000 | 1.7500 | 0.0246 | 1.7746 | 1.3533 | 2051.82 | 355.94 | 3535.24 |
PERIMETER_MID_ZN_2 | 1.6737 | 0.0000 | 1.6737 | 0.0173 | 1.6910 | 0.8721 | 1730.92 | 564.90 | 2738.18 |
PERIMETER_MID_ZN_1 | 2.8687 | 0.0000 | 2.8687 | 0.0246 | 2.8933 | 1.3533 | 1643.26 | 714.32 | 3585.41 |
PERIMETER_MID_ZN_4 | 1.7755 | 0.0000 | 1.7755 | 0.0164 | 1.7919 | 0.8721 | 1875.94 | 654.60 | 3412.46 |
PERIMETER_TOP_ZN_3 | 0.1903 | 0.0000 | 0.1903 | 0.0305 | 0.2208 | 0.1353 | 1451.75 | 26.06 | 4465.19 |
PERIMETER_TOP_ZN_2 | 0.1824 | 0.0000 | 0.1824 | 0.0204 | 0.2028 | 0.0872 | 1781.49 | 1040.99 | 3120.52 |
PERIMETER_TOP_ZN_1 | 0.2865 | 0.0000 | 0.2865 | 0.0305 | 0.3170 | 0.1353 | 1757.26 | 1248.73 | 2937.01 |
PERIMETER_TOP_ZN_4 | 0.1816 | 0.0000 | 0.1816 | 0.0204 | 0.2020 | 0.0872 | 1859.08 | 1249.45 | 2834.47 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 11.7390 | 0.0000 | 11.7390 | 0.0000 | 11.7390 | 0.3384 | 9.33 | 94.00 | 5839.67 |
Total Facility | 219.7329 | 0.0000 | 219.7329 | 0.9658 | 220.6986 | 158.4706 | 4346.47 | 4363.65 | 5933.77 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 75255522.20 | 0.00 | 75255522.20 | 48026705.38 | 3609.72 | 6.69 | 5143.59 | 493.67 |
VAV_MID WITH REHEAT | 0.59E+09 | 0.00 | 0.59E+09 | 0.48E+09 | 4009.89 | 2.57 | 4747.54 | 531.06 |
VAV_TOP WITH REHEAT | 58017251.81 | 0.00 | 58017251.81 | 48026705.38 | 4081.05 | 2.53 | 4676.42 | 422.33 |
CAV_BAS | 56509071.40 | 0.00 | 56509071.40 | 37848132.68 | 4067.36 | 2.73 | 4689.91 | 221.49 |
AIRLOOP DATACENTER BASEMENT | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 12.67 | 0.00 | 8747.33 | 2813.67 |
AIRLOOP DATACENTER BOT | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3252905.49 | 0.00 | 3252905.49 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.3102 | 0.0000 | 3.3102 | 1.5229 | 1175.74 | 4.21 | 4763.06 |
VAV_MID WITH REHEAT | 26.7176 | 0.0000 | 26.7176 | 15.2292 | 1307.95 | 2.31 | 4632.75 |
VAV_TOP WITH REHEAT | 2.6546 | 0.0000 | 2.6546 | 1.5229 | 1345.92 | 2.32 | 4594.76 |
CAV_BAS | 2.5673 | 0.0000 | 2.5673 | 1.2002 | 1369.61 | 1.43 | 4571.96 |
AIRLOOP DATACENTER BASEMENT | 15.6309 | 0.0000 | 15.6309 | 0.3384 | 9.33 | 0.00 | 5933.67 |
AIRLOOP DATACENTER BOT | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1520 | 0.0000 | 0.1520 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 766.40 | 2934.62 | 0.00 | 0.00 | 0.00 | 1726.67 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 368.09 | 2647.49 | 0.00 | 0.00 | 0.00 | 2441.79 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 120.19 | 2561.54 | 0.00 | 0.00 | 0.00 | 2649.39 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1702.58 | 3172.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 94.00 | 8653.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.7183 | 5.6270 | 0.0000 | 0.0000 | 0.0000 | 2.2349 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 27.0512 | 45.4164 | 0.0000 | 0.0000 | 0.0000 | 21.6115 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.7179 | 4.5326 | 0.0000 | 0.0000 | 0.0000 | 2.1735 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.5986 | 4.2498 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4506 | 15.9021 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1528 |
Defaulted Fields | 1187 |
Fields with Defaults | 3962 |
Autosized Fields | 337 |
Autosizable Fields | 415 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 23879.72 | 295960.87 | 30-SEP-02:10 | 1735683.59 | 08-AUG-15:20 |
Electricity:Building | 16394.34 | 215366.33 | 06-MAY-18:10 | 948093.84 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16394.34 | 215366.33 | 06-MAY-18:10 | 948093.84 | 01-DEC-16:20 |
InteriorLights:Electricity | 1717.95 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1717.95 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 1717.95 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1717.95 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.99 | 589.50 | 26-MAR-17:10 | 3307.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.62 | 30.32 | 01-JAN-10:00 | 1147.25 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.62 | 30.32 | 01-JAN-10:00 | 1147.25 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.32 | 379.89 | 26-MAR-17:10 | 2131.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.88 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.88 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.88 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.52 | 30.33 | 01-JAN-08:40 | 1147.28 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.52 | 30.33 | 01-JAN-08:40 | 1147.28 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.30 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.87 | 19.54 | 01-JAN-10:00 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.87 | 19.54 | 01-JAN-10:00 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 439.78 | 5894.96 | 19-MAR-17:10 | 33078.05 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 76.13 | 303.25 | 01-JAN-09:50 | 11472.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 76.13 | 303.25 | 01-JAN-09:50 | 11472.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 283.11 | 3798.93 | 19-MAR-17:10 | 21316.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.76 | 195.42 | 01-JAN-08:40 | 7393.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.76 | 195.42 | 01-JAN-08:40 | 7393.34 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 438.78 | 5895.05 | 12-MAR-17:10 | 33078.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.12 | 303.26 | 01-JAN-08:40 | 11472.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.12 | 303.26 | 01-JAN-08:40 | 11472.78 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.99 | 3798.91 | 12-MAR-17:10 | 21316.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.64 | 195.42 | 01-JAN-09:50 | 7393.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.64 | 195.42 | 01-JAN-09:50 | 7393.34 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.98 | 589.50 | 19-MAR-17:10 | 3307.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.61 | 30.32 | 01-JAN-09:50 | 1147.25 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.61 | 30.32 | 01-JAN-09:50 | 1147.25 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.31 | 379.89 | 19-MAR-17:10 | 2131.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.88 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.88 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.88 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.51 | 30.33 | 01-JAN-08:40 | 1147.28 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.51 | 30.33 | 01-JAN-08:40 | 1147.28 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.30 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.86 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.86 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1262.98 | 3438.77 | 06-JAN-05:20 | 455625.16 | 05-JUL-10:10 |
HeatRejection:Electricity | 414.93 | 43.68 | 06-JAN-09:00 | 76123.16 | 16-MAY-13:40 |
General:HeatRejection:Electricity | 414.93 | 43.68 | 06-JAN-09:00 | 76123.16 | 16-MAY-13:40 |
ElectricityProduced:Facility | 461.92 | -0.00 | 26-MAY-04:30 | 92732.08 | 19-APR-12:20 |
ElectricityProduced:Plant | 461.92 | -0.00 | 26-MAY-04:30 | 92732.08 | 19-APR-12:20 |
Photovoltaic:ElectricityProduced | 484.11 | 0.00 | 01-JAN-00:10 | 96507.12 | 19-APR-12:20 |
PowerConversion:ElectricityProduced | -22.20 | -3775.04 | 19-APR-12:20 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 4803.64 | 48899.18 | 17-SEP-05:00 | 427485.49 | 08-AUG-15:20 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73700.64 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.36 | 979.82 | 01-JAN-00:10 | 3372.05 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
ElectricityPurchased:Plant | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
Cogeneration:ElectricityPurchased | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
ElectricityNet:Plant | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
Cogeneration:ElectricityNet | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
General:Cogeneration:ElectricityNet | 23417.81 | 269488.82 | 04-SEP-09:10 | 1679564.35 | 08-AUG-15:50 |
Fans:Electricity | 2252.43 | 43160.55 | 01-JAN-08:00 | 288379.59 | 05-JUL-10:40 |
General:Fans:Electricity | 2252.43 | 43160.55 | 01-JAN-08:00 | 288379.59 | 05-JUL-10:40 |
ExteriorLights:Electricity | 269.43 | 0.00 | 01-JAN-08:20 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 269.43 | 0.00 | 01-JAN-08:20 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
HeatRecovery:Electricity | 48.08 | 0.00 | 01-JAN-00:10 | 5431.84 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 48.08 | 0.00 | 01-JAN-00:10 | 5431.84 | 02-JAN-07:10 |
Cooling:Electricity | 1272.06 | 1188.67 | 06-JAN-09:00 | 461910.36 | 05-JUL-10:10 |
General:Cooling:Electricity | 1272.06 | 1188.67 | 06-JAN-09:00 | 461910.36 | 05-JUL-10:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1702.75 | 0.00 | 23-APR-10:50 | 100000.00 | 04-FEB-17:10 |
General:Humidifier:Electricity | 1702.75 | 0.00 | 23-APR-10:50 | 100000.00 | 04-FEB-17:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 322.02 | 3389.39 | 01-JAN-00:40 | 49690.24 | 05-JUL-10:30 |
General:Pumps:Electricity | 322.02 | 3389.39 | 01-JAN-00:40 | 49690.24 | 05-JUL-10:30 |
WIRED_LTG_ELECTRICITY | 48.27 | 0.00 | 01-JAN-00:10 | 4769.19 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3699.87 | 7280.88 | 02-JAN-04:40 | 2697655.94 | 09-JAN-07:10 |
NaturalGas:Plant | 3699.87 | 7280.88 | 02-JAN-04:40 | 2697655.94 | 09-JAN-07:10 |
Heating:NaturalGas | 2834.25 | 0.00 | 01-JAN-00:40 | 2665274.07 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 2834.25 | 0.00 | 01-JAN-00:40 | 2665274.07 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 865.62 | 7280.88 | 02-JAN-04:10 | 89127.61 | 02-MAR-13:00 |
Water Heater:WaterSystems:NaturalGas | 865.62 | 7280.88 | 02-JAN-04:10 | 89127.61 | 02-MAR-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7335.85 | 2766.08 | 06-JAN-09:00 | 3276142.39 | 05-JUL-12:20 |
PlantLoopCoolingDemand:HVAC | 7335.85 | 2766.08 | 06-JAN-09:00 | 3276142.39 | 05-JUL-12:20 |
CoolingCoils:PlantLoopCoolingDemand | 7335.85 | 2766.08 | 06-JAN-09:00 | 3276142.39 | 05-JUL-12:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5555.53 | 0.00 | 18-MAY-23:10 | 0.00 | 18-MAY-15:40 |
Water:HVAC | 633.42 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
Humidifier:Water | 633.42 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
General:Humidifier:Water | 633.42 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
MainsWater:Facility | 5555.53 | 0.00 | 18-MAY-23:10 | 0.00 | 18-MAY-15:40 |
MainsWater:HVAC | 633.42 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
Humidifier:MainsWater | 633.42 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
General:Humidifier:MainsWater | 633.42 | 0.00 | 23-APR-10:50 | 0.00 | 01-MAR-05:10 |
Water:Plant | 4922.11 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:40 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 4922.11 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:40 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 2641.94 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:40 |
General:HeatRejection:Water | 2641.94 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:40 |
HeatRejection:MainsWater | 2641.94 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:40 |
General:HeatRejection:MainsWater | 2641.94 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 43971.27 | 91404.16 | 01-JAN-06:00 | 11924069.00 | 05-JUL-12:20 |
EnergyTransfer:Building | 17580.47 | 88943.60 | 07-JAN-18:10 | 1773166.25 | 26-DEC-06:20 |
EnergyTransfer:Zone:BASEMENT | 553.73 | 0.00 | 01-JAN-00:10 | 69512.89 | 30-MAY-05:10 |
Heating:EnergyTransfer | 1546.56 | 0.00 | 01-FEB-22:10 | 1475179.19 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.98 | 0.00 | 01-JAN-00:10 | 15400.40 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 1546.56 | 0.00 | 01-FEB-22:10 | 1475179.19 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.98 | 0.00 | 01-JAN-00:10 | 15400.40 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 16033.91 | 82774.93 | 01-JAN-10:00 | 1546232.88 | 08-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 551.75 | 0.00 | 01-JAN-00:10 | 69512.89 | 30-MAY-05:10 |
General:Cooling:EnergyTransfer | 16033.91 | 82774.93 | 01-JAN-10:00 | 1546232.88 | 08-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 551.75 | 0.00 | 01-JAN-00:10 | 69512.89 | 30-MAY-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 502.97 | 0.00 | 01-JAN-00:10 | 49468.16 | 30-MAY-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 502.97 | 0.00 | 01-JAN-00:10 | 49468.16 | 30-MAY-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 502.97 | 0.00 | 01-JAN-00:10 | 49468.16 | 30-MAY-05:10 |
EnergyTransfer:Zone:CORE_MID | 3464.10 | 0.00 | 01-JAN-00:40 | 482304.23 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 35.01 | 0.00 | 01-JAN-00:20 | 482304.23 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 35.01 | 0.00 | 01-JAN-00:20 | 482304.23 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3429.09 | 0.00 | 01-JAN-00:40 | 392806.12 | 05-JUL-12:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3429.09 | 0.00 | 01-JAN-00:40 | 392806.12 | 05-JUL-12:00 |
EnergyTransfer:Zone:CORE_TOP | 317.47 | 0.00 | 01-JAN-00:40 | 63310.49 | 21-FEB-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 39.77 | 0.00 | 01-JAN-00:40 | 63310.49 | 21-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 39.77 | 0.00 | 01-JAN-00:40 | 63310.49 | 21-FEB-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 277.70 | 0.00 | 01-JAN-00:10 | 44453.15 | 05-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 277.70 | 0.00 | 01-JAN-00:10 | 44453.15 | 05-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.59 | 0.00 | 01-JAN-00:10 | 11434.52 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.03 | 0.00 | 01-JAN-00:10 | 11434.52 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.03 | 0.00 | 01-JAN-00:10 | 11434.52 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 54.56 | 0.00 | 01-JAN-00:10 | 10094.03 | 05-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 54.56 | 0.00 | 01-JAN-00:10 | 10094.03 | 05-JUL-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 54.28 | 0.00 | 01-JAN-00:10 | 15712.37 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.53 | 0.00 | 01-JAN-00:10 | 10002.59 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.53 | 0.00 | 01-JAN-00:10 | 10002.59 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.74 | 0.00 | 01-JAN-00:10 | 15712.37 | 31-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.74 | 0.00 | 01-JAN-00:10 | 15712.37 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.92 | 0.00 | 01-JAN-00:10 | 22490.79 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.87 | 0.00 | 01-JAN-00:10 | 15571.06 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.87 | 0.00 | 01-JAN-00:10 | 15571.06 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.05 | 0.00 | 01-JAN-00:10 | 22490.79 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.05 | 0.00 | 01-JAN-00:10 | 22490.79 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 82.01 | 0.00 | 01-JAN-00:10 | 18596.86 | 24-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.80 | 0.00 | 01-JAN-00:10 | 7581.36 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.80 | 0.00 | 01-JAN-00:10 | 7581.36 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.22 | 0.00 | 01-JAN-00:10 | 18596.86 | 24-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.22 | 0.00 | 01-JAN-00:10 | 18596.86 | 24-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 719.84 | 0.00 | 01-JAN-00:40 | 126185.19 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 360.37 | 0.00 | 01-JAN-00:40 | 126185.19 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 360.37 | 0.00 | 01-JAN-00:40 | 126185.19 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 359.48 | 0.00 | 01-JAN-00:10 | 96495.46 | 29-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 359.48 | 0.00 | 01-JAN-00:10 | 96495.46 | 29-JUN-14:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 616.42 | 0.00 | 01-JAN-00:40 | 166796.09 | 24-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 200.04 | 0.00 | 01-JAN-00:40 | 157886.89 | 04-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 200.04 | 0.00 | 01-JAN-00:40 | 157886.89 | 04-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 416.39 | 0.00 | 01-JAN-00:20 | 166796.09 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 416.39 | 0.00 | 01-JAN-00:20 | 166796.09 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1001.21 | 0.00 | 01-JAN-00:40 | 238757.57 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 208.23 | 0.00 | 01-JAN-00:40 | 215648.52 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 208.23 | 0.00 | 01-JAN-00:40 | 215648.52 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 792.98 | 0.00 | 01-JAN-00:20 | 238757.57 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 792.98 | 0.00 | 01-JAN-00:20 | 238757.57 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 633.07 | 0.00 | 01-JAN-00:40 | 178817.80 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 165.36 | 0.00 | 01-JAN-00:40 | 154052.73 | 04-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 165.36 | 0.00 | 01-JAN-00:40 | 154052.73 | 04-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 467.71 | 0.00 | 01-JAN-00:20 | 178817.80 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 467.71 | 0.00 | 01-JAN-00:20 | 178817.80 | 30-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 97.98 | 0.00 | 01-JAN-00:40 | 16815.07 | 13-FEB-04:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.79 | 0.00 | 01-JAN-00:40 | 16815.07 | 13-FEB-04:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.79 | 0.00 | 01-JAN-00:40 | 16815.07 | 13-FEB-04:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.19 | 0.00 | 01-JAN-00:10 | 10440.36 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.19 | 0.00 | 01-JAN-00:10 | 10440.36 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 77.43 | 0.00 | 01-JAN-00:40 | 19036.26 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.65 | 0.00 | 01-JAN-00:40 | 19036.26 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.65 | 0.00 | 01-JAN-00:40 | 19036.26 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.78 | 0.00 | 01-JAN-00:10 | 16733.09 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.78 | 0.00 | 01-JAN-00:10 | 16733.09 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 114.37 | 0.00 | 01-JAN-00:40 | 24888.97 | 01-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 43.16 | 0.00 | 01-JAN-00:40 | 24298.01 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 43.16 | 0.00 | 01-JAN-00:40 | 24298.01 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 71.21 | 0.00 | 01-JAN-00:10 | 24888.97 | 01-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 71.21 | 0.00 | 01-JAN-00:10 | 24888.97 | 01-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 74.52 | 0.00 | 01-JAN-00:40 | 19263.94 | 04-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.85 | 0.00 | 01-JAN-00:40 | 19263.94 | 04-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.85 | 0.00 | 01-JAN-00:40 | 19263.94 | 04-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.67 | 0.00 | 01-JAN-00:10 | 18505.46 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.67 | 0.00 | 01-JAN-00:10 | 18505.46 | 30-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 47.27 | 0.00 | 01-JAN-00:10 | 8985.96 | 24-JUL-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 9.02 | 0.00 | 01-JAN-00:10 | 7287.90 | 02-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 9.02 | 0.00 | 01-JAN-00:10 | 7287.90 | 02-JAN-12:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 38.25 | 0.00 | 01-JAN-00:10 | 8985.96 | 24-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 38.25 | 0.00 | 01-JAN-00:10 | 8985.96 | 24-JUL-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 477.65 | 0.00 | 01-JAN-00:40 | 197255.31 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 247.80 | 0.00 | 01-JAN-00:40 | 197255.31 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 247.80 | 0.00 | 01-JAN-00:40 | 197255.31 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 229.86 | 0.00 | 01-JAN-00:10 | 74142.01 | 05-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 229.86 | 0.00 | 01-JAN-00:10 | 74142.01 | 05-JUL-12:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 114.19 | 0.00 | 01-JAN-00:40 | 32409.78 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 79.81 | 0.00 | 01-JAN-00:40 | 32409.78 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 79.81 | 0.00 | 01-JAN-00:40 | 32409.78 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.38 | 0.00 | 01-JAN-00:10 | 18224.37 | 30-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.38 | 0.00 | 01-JAN-00:10 | 18224.37 | 30-JUN-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 132.86 | 5.47 | 15-JAN-07:00 | 8481.29 | 13-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.09 | 0.00 | 01-JAN-15:00 | 575.86 | 01-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.09 | 0.00 | 01-JAN-15:00 | 575.86 | 01-JAN-05:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 132.77 | 0.00 | 01-JAN-00:10 | 8481.29 | 13-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 132.77 | 0.00 | 01-JAN-00:10 | 8481.29 | 13-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1106.99 | 1.06 | 17-JAN-14:40 | 80743.82 | 21-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.46 | 0.00 | 02-JAN-07:10 | 5970.39 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.46 | 0.00 | 02-JAN-07:10 | 5970.39 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1099.53 | 0.00 | 01-JAN-00:10 | 80743.82 | 21-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1099.53 | 0.00 | 01-JAN-00:10 | 80743.82 | 21-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 99.27 | 0.27 | 17-JAN-14:50 | 8093.45 | 05-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.95 | 0.00 | 02-JAN-07:10 | 608.78 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.95 | 0.00 | 02-JAN-07:10 | 608.78 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 98.33 | 0.00 | 01-JAN-00:10 | 8093.45 | 05-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 98.33 | 0.00 | 01-JAN-00:10 | 8093.45 | 05-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7137.31 | 82773.22 | 01-JAN-09:40 | 372640.16 | 09-AUG-23:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7137.31 | 82773.22 | 01-JAN-09:40 | 372640.16 | 09-AUG-23:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7137.31 | 82773.22 | 01-JAN-09:40 | 372640.16 | 09-AUG-23:10 |
PlantLoopHeatingDemand:Facility | 2781.36 | 0.00 | 01-JAN-00:40 | 2318902.98 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 499.04 | 0.00 | 01-JAN-00:10 | 61547.47 | 23-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 499.04 | 0.00 | 01-JAN-00:10 | 61547.47 | 23-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 499.04 | 0.00 | 01-JAN-00:10 | 61547.47 | 23-FEB-12:20 |
EnergyTransfer:HVAC | 12191.45 | 1884.95 | 01-JAN-06:40 | 3155615.48 | 05-JUL-12:20 |
HeatingCoils:EnergyTransfer | 2282.32 | 0.00 | 01-JAN-00:40 | 2299113.15 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 2282.32 | 0.00 | 01-JAN-00:40 | 2299113.15 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2282.32 | 0.00 | 01-JAN-00:40 | 2299113.15 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 6589.83 | 1577.42 | 06-JAN-09:00 | 3145875.22 | 05-JUL-12:20 |
HeatRecoveryForHeating:EnergyTransfer | 3191.36 | 0.00 | 01-JAN-00:10 | 943831.29 | 13-JAN-13:20 |
HeatRecoveryForCooling:EnergyTransfer | 127.94 | 0.00 | 01-JAN-00:10 | 523916.68 | 15-JUL-14:00 |
EnergyTransfer:Plant | 14199.35 | 0.00 | 01-JAN-00:40 | 7501587.26 | 05-JUL-10:20 |
LoopToLoop:EnergyTransfer | 3629.15 | 0.00 | 01-JAN-00:10 | 2469786.02 | 05-JUL-10:20 |
WaterSystems:EnergyTransfer | 499.04 | 0.00 | 01-JAN-00:10 | 61547.47 | 23-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 499.04 | 0.00 | 01-JAN-00:10 | 61547.47 | 23-FEB-12:20 |
Boilers:EnergyTransfer | 2270.41 | 0.00 | 01-JAN-00:40 | 2307154.69 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 3637.36 | 0.00 | 01-JAN-00:10 | 2337022.64 | 05-JUL-10:10 |
HeatRejection:EnergyTransfer | 4163.39 | 0.00 | 01-JAN-00:10 | 2673078.26 | 05-JUL-10:10 |
General:HeatRejection:EnergyTransfer | 4163.39 | 0.00 | 01-JAN-00:10 | 2673078.26 | 05-JUL-10:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.980 | -551.749 | 0.000 | 0.000 | 93.210 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -83.877 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -502.971 | 0.000 | 0.000 | 83.701 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 25.445 | 0.000 | 0.000 | 0.000 | 0.000 | -0.007 |
CORE_MID | 0.000 | 0.000 | 35.007 | -3429.089 | 0.000 | 0.000 | 871.326 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1415.486 |
CORE_TOP | 0.000 | 0.000 | 39.771 | -277.703 | 0.000 | 0.000 | 90.286 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -246.179 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 5.028 | -54.559 | 0.000 | 0.000 | 11.098 | 7.624 | 36.365 | 28.092 | 0.000 | 0.031 | 58.898 | 0.000 | -82.166 | 0.000 | -10.410 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 3.531 | -50.745 | 0.000 | 0.000 | 7.099 | 4.881 | 23.435 | 57.284 | 0.000 | 0.021 | 11.753 | 0.000 | -50.335 | 0.000 | -6.925 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 4.873 | -91.050 | 0.000 | 0.000 | 10.893 | 7.518 | 36.366 | 122.581 | 0.000 | 0.030 | 0.002 | 0.000 | -71.923 | 0.000 | -10.458 | -8.832 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.797 | -81.218 | 0.000 | 0.000 | 6.901 | 4.869 | 23.435 | 57.236 | 0.000 | 0.019 | 51.626 | 0.000 | -56.205 | 0.000 | -7.460 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 360.365 | -359.476 | 0.000 | 0.000 | 115.454 | 76.126 | 363.654 | 290.021 | 0.000 | 0.725 | 134.870 | 0.000 | -759.356 | 0.000 | -222.384 | -0.012 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 200.036 | -416.389 | 0.000 | 0.000 | 53.775 | 48.756 | 234.352 | 574.018 | 0.000 | 0.442 | 0.034 | 0.000 | -473.667 | 0.000 | -151.306 | -70.017 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 208.234 | -792.974 | 0.000 | 0.000 | 111.253 | 75.124 | 363.660 | 1226.087 | 0.000 | 0.666 | 0.005 | 0.000 | -693.166 | 0.000 | -232.703 | -266.182 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 165.357 | -467.709 | 0.000 | 0.000 | 73.129 | 48.644 | 234.351 | 583.073 | 0.000 | 0.433 | 18.173 | 0.000 | -501.145 | 0.000 | -154.306 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 64.793 | -33.190 | 0.000 | 0.000 | 11.712 | 7.612 | 36.365 | 29.596 | 0.000 | 0.088 | 0.000 | 0.000 | -73.148 | 0.000 | -26.708 | -17.120 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 37.651 | -39.775 | 0.000 | 0.000 | 7.394 | 4.875 | 23.435 | 57.901 | 0.000 | 0.055 | 0.000 | 0.000 | -45.732 | 0.000 | -18.214 | -27.591 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 43.162 | -71.209 | 0.000 | 0.000 | 11.292 | 7.512 | 36.366 | 123.293 | 0.000 | 0.079 | 0.001 | 0.000 | -66.580 | 0.000 | -27.859 | -56.056 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 30.846 | -43.669 | 0.000 | 0.000 | 7.406 | 4.864 | 23.435 | 58.583 | 0.000 | 0.052 | 0.000 | 0.000 | -48.470 | 0.000 | -18.584 | -14.463 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.093 | -132.767 | 0.000 | 0.000 | 0.951 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.833 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.459 | -1099.532 | 0.000 | 0.000 | 9.588 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -473.078 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.949 | -98.325 | 0.000 | 0.000 | 0.964 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -59.145 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7137.313 | 0.000 | 0.000 | 20.370 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -410.769 |
GROUNDFLOOR_PLENUM | 9.025 | -38.249 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.054 | 51.223 | 0.000 | 0.000 | 0.000 | -22.052 | -0.000 |
MIDFLOOR_PLENUM | 247.800 | -229.856 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.991 | 351.763 | 0.000 | 0.000 | 0.000 | -370.697 | -0.004 |
TOPFLOOR_PLENUM | 79.805 | -34.384 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.076 | 0.000 | 0.000 | 0.000 | 0.000 | -40.187 | -5.311 |
Total Facility | 336.630 | -302.489 | 1209.932 | -15731.412 | 0.000 | 0.000 | 1597.802 | 1717.947 | 14676.396 | 3207.766 | 0.000 | 3.761 | 703.794 | 0.000 | -2921.891 | 0.000 | -1320.254 | -3177.963 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-SEP-04:11 | 0.00 | 0.00 | 0.00 | -100941.00 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 86885.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 19-JUN-04:13 | 0.00 | 0.00 | 0.00 | -86909.32 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 80434.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 | -772524.28 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 707774.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-04:12 | 0.00 | 0.00 | 0.00 | -72685.87 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 66210.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-15:21 | 0.00 | 0.00 | 0.00 | -15218.03 | 0.00 | 0.00 | 42.02 | 30.32 | 720.18 | 5586.08 | 0.00 | 115.02 | 8724.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 20-AUG-08:21 | 0.00 | 0.00 | 0.00 | -25708.82 | 0.00 | 0.00 | 19.59 | 19.54 | 464.11 | 21731.67 | 0.00 | 0.00 | 3768.69 | 0.00 | -0.00 | 0.00 | -294.79 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-APR-13:21 | 0.00 | 0.00 | 0.00 | -30831.91 | 0.00 | 0.00 | 31.63 | 30.33 | 720.19 | 28180.12 | 0.00 | 0.00 | 2242.89 | 0.00 | -0.00 | 0.00 | -373.25 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-APR-16:41 | 0.00 | 0.00 | 0.00 | -34718.84 | 0.00 | 0.00 | 12.43 | 19.54 | 464.11 | 23106.34 | 0.00 | 0.00 | 11296.70 | 0.00 | -0.00 | 0.00 | -180.28 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-15:21 | 0.00 | 0.00 | 0.00 | -142920.86 | 0.00 | 0.00 | 422.61 | 303.25 | 7201.84 | 55971.35 | 0.00 | 2612.31 | 76409.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-08:41 | 0.00 | 0.00 | 0.00 | -288892.78 | 0.00 | 0.00 | 173.14 | 195.42 | 4641.14 | 179787.20 | 0.00 | 0.00 | 106543.45 | 0.00 | -0.00 | 0.00 | -2447.56 | 0.00 |
PERIMETER_MID_ZN_1 | 20-AUG-13:11 | 0.00 | 0.00 | 0.00 | -319960.68 | 0.00 | 0.00 | 308.39 | 303.26 | 7201.95 | 239315.20 | 0.00 | 0.00 | 77725.03 | 0.00 | -0.00 | 0.00 | -4893.14 | 0.00 |
PERIMETER_MID_ZN_4 | 14-MAY-17:11 | 0.00 | 0.00 | 0.00 | -309364.69 | 0.00 | 0.00 | 0.00 | 195.42 | 3603.49 | 236739.14 | 0.00 | 0.00 | 75467.19 | 0.00 | -0.00 | 0.00 | -6640.55 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-15:31 | 0.00 | 0.00 | 0.00 | -17722.37 | 0.00 | 0.00 | 40.65 | 30.32 | 720.18 | 5474.41 | 0.00 | 355.26 | 11101.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-08:41 | 0.00 | 0.00 | 0.00 | -27711.25 | 0.00 | 0.00 | 18.94 | 19.54 | 464.11 | 19681.37 | 0.00 | 0.00 | 8314.96 | 0.00 | -0.00 | 0.00 | -787.67 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-14:21 | 0.00 | 0.00 | 0.00 | -34639.15 | 0.00 | 0.00 | 29.66 | 30.33 | 720.19 | 20969.63 | 0.00 | 0.00 | 13835.17 | 0.00 | -0.00 | 0.00 | -945.84 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-APR-16:51 | 0.00 | 0.00 | 0.00 | -32478.46 | 0.00 | 0.00 | 15.36 | 19.54 | 464.11 | 22383.24 | 0.00 | 0.00 | 10044.03 | 0.00 | -0.00 | 0.00 | -447.83 | 0.00 |
DATACENTER_BOT_ZN_6 | 13-AUG-18:33 | 0.00 | 0.00 | 0.00 | -8481.29 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 678.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 21-APR-18:20 | 0.00 | 0.00 | 0.00 | -80737.75 | 0.00 | 0.00 | 106.16 | 487.73 | 77944.22 | 0.00 | 0.00 | 0.00 | 2199.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 05-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8093.45 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 290.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 09-AUG-23:03 | 0.00 | 0.00 | 0.00 | -375566.18 | 0.00 | 0.00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4225.71 |
GROUNDFLOOR_PLENUM | 24-JUL-05:15 | 0.00 | -11627.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11730.94 | 0.00 | -0.00 | 0.00 | -103.30 | 0.00 |
MIDFLOOR_PLENUM | 25-FEB-04:01 | 0.00 | -119977.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119977.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:50 | 0.00 | -18225.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.46 | 17870.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-05:02 | 0.00 | 12779.74 | 0.00 | -1752153.57 | 0.00 | 0.00 | 15789.19 | 10223.35 | 497997.76 | 115212.67 | 0.00 | 0.00 | 1123974.27 | 0.00 | -20178.66 | 0.00 | -3644.75 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:01 | 0.00 | 0.00 | 16721.76 | 0.00 | 0.00 | 0.00 | 520.12 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31264.64 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 555123.71 | 0.00 | 0.00 | 0.00 | 0.00 | 5076.02 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -619575.95 |
CORE_TOP | 26-DEC-04:11 | 0.00 | 0.00 | 71432.97 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -77878.19 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 12780.45 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8076.43 | 0.00 | -931.38 | -4581.93 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 15589.76 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5372.62 | 0.00 | -625.06 | -10113.62 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 22208.81 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8144.66 | 0.00 | -935.96 | -13937.50 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 13543.16 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5641.71 | 0.00 | -640.12 | -7782.87 |
PERIMETER_MID_ZN_3 | 08-JAN-21:42 | 0.00 | 0.00 | 132647.22 | 0.00 | 0.00 | 0.00 | 0.00 | 637.34 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72399.07 | 0.00 | -25943.21 | -40534.00 |
PERIMETER_MID_ZN_2 | 18-DEC-04:11 | 0.00 | 0.00 | 212390.26 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32922.01 | 0.00 | -25955.51 | -158728.14 |
PERIMETER_MID_ZN_1 | 18-DEC-04:11 | 0.00 | 0.00 | 253779.05 | 0.00 | 0.00 | 0.00 | 0.00 | 637.36 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49712.53 | 0.00 | -38856.08 | -173303.52 |
PERIMETER_MID_ZN_4 | 18-DEC-04:11 | 0.00 | 0.00 | 212161.85 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34626.60 | 0.00 | -26371.15 | -156379.48 |
PERIMETER_TOP_ZN_3 | 13-FEB-04:21 | 0.00 | 0.00 | 18018.73 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6396.36 | 0.00 | -5781.22 | -6650.45 |
PERIMETER_TOP_ZN_2 | 26-DEC-04:11 | 0.00 | 0.00 | 22740.60 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4303.80 | 0.00 | -1596.56 | -17361.78 |
PERIMETER_TOP_ZN_1 | 26-DEC-04:11 | 0.00 | 0.00 | 28115.08 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6476.19 | 0.00 | -2390.69 | -20057.50 |
PERIMETER_TOP_ZN_4 | 26-DEC-04:11 | 0.00 | 0.00 | 24543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4488.05 | 0.00 | -1625.24 | -18951.85 |
DATACENTER_BOT_ZN_6 | 01-JAN-05:10 | 0.00 | 0.00 | 575.86 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2532.59 |
DATACENTER_MID_ZN_6 | 01-JAN-17:05 | 0.00 | 0.00 | 6110.44 | 0.00 | 0.00 | 0.00 | 69.67 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25747.46 |
DATACENTER_TOP_ZN_6 | 01-JAN-17:05 | 0.00 | 0.00 | 623.97 | 0.00 | 0.00 | 0.00 | 7.36 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2588.06 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-MAR-15:22 | 15346.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -937.89 | -14408.70 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 203871.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5838.94 | -198032.93 |
TOPFLOOR_PLENUM | 06-JAN-06:12 | 33224.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33224.45 |
Total Facility | 02-JAN-06:01 | 73798.43 | 94049.71 | 1477955.47 | -94049.71 | 0.00 | 0.00 | 23373.89 | 10223.35 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -225301.09 | 0.00 | -22378.13 | -1599086.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.0159 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.1753 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 106.4142 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 85.0538 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.9601 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.4386 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0511 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0511 | 0.2376 | 1.0000 | Not calculated | 1.2002 | 0.2376 | ||
AIRLOOP DATACENTER BASEMENT | 22.1601 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.1603 | 0.0153 | 1.0000 | Not calculated | 0.3384 | 0.0153 | ||
AIRLOOP DATACENTER BOT | 0.5095 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5095 | 0.0307 | 1.0000 | Not calculated | 0.0156 | 0.0307 | ||
AIRLOOP DATACENTER MID | 4.8974 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8974 | 0.0319 | 1.0000 | Not calculated | 0.1563 | 0.0319 | ||
AIRLOOP DATACENTER TOP | 0.4968 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4968 | 0.0315 | 1.0000 | Not calculated | 0.0156 | 0.0315 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5079 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2824 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 53.2071 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8477 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4800 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3132 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0511 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0511 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2376 | ||
AIRLOOP DATACENTER BASEMENT | 22.1601 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.1601 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0153 | ||
AIRLOOP DATACENTER BOT | 0.5095 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5095 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0307 | ||
AIRLOOP DATACENTER MID | 4.8974 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8974 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0319 | ||
AIRLOOP DATACENTER TOP | 0.4968 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4968 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0315 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0511 | 5.0511 | 5.0511 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4380 | 5.4380 | 1.6151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 50.7655 | 50.7655 | 16.1434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9829 | 4.9829 | 1.6145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9152 | 0.9152 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3604 | 1.3604 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6507 | 1.6507 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6517 | 1.6517 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.6586 | 8.6586 | 2.0434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.5811 | 14.5811 | 1.3123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.9664 | 16.9664 | 2.0360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.4427 | 15.4427 | 1.3126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1079 | 1.1079 | 0.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4580 | 1.4580 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7965 | 1.7965 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6148 | 1.6148 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5095 | 0.5095 | 0.5095 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8974 | 4.8974 | 4.8974 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4968 | 0.4968 | 0.4968 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.1601 | 22.1601 | 22.1601 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.0159 | 9.1753 | 11.0159 | 2.2824 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 106.4142 | 85.0538 | 106.4142 | 22.8477 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.9601 | 9.4386 | 10.9601 | 2.3132 | 0.0000 | 1.0000 |
CAV_BAS | 5.0511 | 5.0511 | 5.0511 | 5.0511 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.1601 | 22.1603 | 22.1601 | 22.1601 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5095 | 0.5095 | 0.5095 | 0.5095 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8974 | 4.8974 | 4.8974 | 4.8974 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4968 | 0.4968 | 0.4968 | 0.4968 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0511 | 5.0511 | 5.0511 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7190 | 2.7190 | 1.6151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.3827 | 25.3827 | 16.1434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4914 | 2.4914 | 1.6145 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4576 | 0.4576 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6802 | 0.6802 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8253 | 0.8253 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8258 | 0.8258 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3293 | 4.3293 | 2.0434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2906 | 7.2906 | 1.3123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4832 | 8.4832 | 2.0360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7213 | 7.7213 | 1.3126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5539 | 0.5539 | 0.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7290 | 0.7290 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8983 | 0.8983 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8074 | 0.8074 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5095 | 0.5095 | 0.5095 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8974 | 4.8974 | 4.8974 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4968 | 0.4968 | 0.4968 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.1601 | 22.1601 | 22.1601 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5079 | 2.2824 | 2.2824 | 2.2824 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 53.2071 | 22.8477 | 22.8477 | 22.8477 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4800 | 2.3132 | 2.3132 | 2.3132 | 0.0000 | 1.0000 |
CAV_BAS | 5.0511 | 5.0511 | 5.0511 | 5.0511 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.1601 | 22.1601 | 22.1601 | 22.1601 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5095 | 0.5095 | 0.5095 | 0.5095 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8974 | 4.8974 | 4.8974 | 4.8974 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4968 | 0.4968 | 0.4968 | 0.4968 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 219.00 |
Number of hours cooling loads not met | 327.67 |
Number of hours not met | 546.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2834.25 | 2665274.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1272.06 | 461910.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1717.95 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 269.43 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.36 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2252.43 | 288379.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 322.02 | 49690.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 414.93 | 76123.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1702.75 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 48.08 | 5431.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 865.62 | 89127.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 23879.72 |
Natural Gas | 0.00 | 3699.87 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27579.60 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 484.11 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.09 |
Space Heating | 0.00 |
Space Cooling | 27.46 |
Fans (All) | 48.63 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 515.53 |
Subtotal | 515.53 |
Natural Gas [MJ/m2] | |
Space Heating | 61.19 |
Service Water Heating | 18.69 |
Miscellaneous (All) | 79.88 |
Subtotal | 79.88 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.23 |
Space Heating | 10.28 |
Space Cooling | 4.61 |
Fans (All) | 8.17 |
Service Water Heating | 3.14 |
Receptacle Equipment | 53.21 |
Miscellaneous | 14.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 704. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8467.67 | 292.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8713.00 | 47.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8702.83 | 57.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8349.83 | 410.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8692.50 | 67.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8693.00 | 67.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8612.33 | 147.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8690.83 | 69.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8695.50 | 64.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8627.67 | 132.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8148.17 | 611.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8137.50 | 622.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8127.00 | 633.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7041.83 | 1707.00 | 11.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
Min | 7041.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1707.00 | 11.17 | 0.00 | 0.00 |
Average | 8542.43 | 217.08 | 0.49 | 0.00 | 0.00 |
Sum | 196476.00 | 4992.83 | 11.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367711.83 | 904.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330798.00 | 15.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1918.00 | 350.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1911.50 | 356.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1906.17 | 361.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82415.33 | 20736.33 | 243.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367711.83 | 20736.33 | 243.33 | 0.00 | 0.00 |
Average | 79336.34 | 987.99 | 10.58 | 0.00 | 0.00 |
Sum | 1824735.83 | 22723.83 | 243.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7794.33 | 965.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8390.83 | 369.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8296.17 | 463.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8344.33 | 415.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8469.33 | 290.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8517.50 | 242.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8413.83 | 346.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8084.50 | 675.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8442.00 | 318.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8372.00 | 388.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8346.33 | 413.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8271.83 | 488.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8478.33 | 281.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8419.50 | 340.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8386.00 | 374.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8314.17 | 445.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8473.00 | 287.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8461.83 | 298.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8460.33 | 299.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7240.83 | 1518.17 | 1.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8282.17 | 477.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8303.67 | 456.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8184.83 | 575.17 | 0.00 | 0.00 | 0.00 |
Min | 7240.83 | 242.50 | 0.00 | 0.00 | 0.00 |
Max | 8517.50 | 1518.17 | 1.00 | 0.00 | 0.00 |
Average | 8293.38 | 466.58 | 0.04 | 0.00 | 0.00 |
Sum | 190747.67 | 10731.33 | 1.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 355770.50 | 12845.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329731.50 | 1081.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329820.33 | 992.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329595.17 | 1217.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38866.33 | 58.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24895.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38877.00 | 48.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24894.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38884.17 | 40.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18345.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38891.50 | 33.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24895.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38895.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24898.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38889.83 | 35.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24899.00 | 10.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2081.33 | 186.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2074.00 | 194.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2073.33 | 194.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 84539.67 | 18851.33 | 4.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 355770.50 | 18851.33 | 4.00 | 0.00 | 0.00 |
Average | 78774.68 | 1560.06 | 0.17 | 0.00 | 0.00 |
Sum | 1811817.67 | 35881.33 | 4.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323352E+11 | 88465.77 | 23-JAN-06:01 | -22.7 | -22.9 | 0.536000E+10 | 7509.25 | 11-JAN-10:39 | -22.7 | -22.9 |
February | 0.332196E+11 | 91847.07 | 21-FEB-05:11 | 2.40 | 0.83 | 0.506937E+10 | 7508.51 | 01-FEB-10:20 | 2.40 | 0.83 |
March | 0.423711E+11 | 93637.36 | 20-MAR-03:01 | -7.4 | -7.7 | 0.612484E+10 | 7500.73 | 14-MAR-13:00 | -7.4 | -7.7 |
April | 0.447313E+11 | 96799.47 | 24-APR-04:12 | 4.40 | 3.41 | 0.544488E+10 | 7499.94 | 05-APR-09:20 | 4.40 | 3.41 |
May | 0.492569E+11 | 97758.21 | 30-MAY-04:12 | 10.60 | 8.25 | 0.589902E+10 | 7499.27 | 18-MAY-09:20 | 10.60 | 8.25 |
June | 0.515121E+11 | 97450.55 | 12-JUN-04:12 | 12.03 | 11.73 | 0.587936E+10 | 7499.34 | 06-JUN-13:30 | 12.03 | 11.73 |
July | 0.536934E+11 | 98548.73 | 10-JUL-04:12 | 8.33 | 7.93 | 0.547550E+10 | 7834.21 | 05-JUL-13:09 | 8.33 | 7.93 |
August | 0.595303E+11 | 94872.06 | 22-AUG-04:12 | 14.03 | 11.70 | 0.613612E+10 | 7499.22 | 10-AUG-13:00 | 14.03 | 11.70 |
September | 0.510684E+11 | 100943.80 | 05-SEP-04:11 | 6.33 | 5.88 | 0.545019E+10 | 7499.19 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.502684E+11 | 100857.13 | 23-OCT-04:11 | 5.60 | 4.25 | 0.566695E+10 | 7499.21 | 25-OCT-09:20 | 1.10 | 1.02 |
November | 0.445022E+11 | 98043.63 | 13-NOV-04:01 | -8.2 | -8.9 | 0.560751E+10 | 7500.87 | 28-NOV-14:00 | -7.2 | -8.5 |
December | 0.392599E+11 | 91902.17 | 18-DEC-05:01 | -15.2 | -16.2 | 0.536349E+10 | 7500.98 | 06-DEC-14:20 | -15.2 | -16.2 |
Annual Sum or Average | 0.551749E+12 | 0.674772E+11 | ||||||||
Minimum of Months | 0.323352E+11 | 88465.77 | -22.7 | -22.9 | 0.506937E+10 | 7499.19 | -22.7 | -22.9 | ||
Maximum of Months | 0.595303E+11 | 100943.80 | 14.03 | 11.73 | 0.613612E+10 | 7834.21 | 18.90 | 14.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230033E+11 | 36668.04 | 19-JAN-06:01 | -3.3 | -3.7 | 0.488023E+10 | 6734.84 | 23-JAN-10:20 | -21.5 | -21.8 |
February | 0.263273E+11 | 73948.19 | 09-FEB-06:01 | -3.2 | -4.5 | 0.456276E+10 | 6734.84 | 02-FEB-10:30 | -3.2 | -4.5 |
March | 0.380712E+11 | 77249.86 | 28-MAR-04:11 | 2.03 | 0.68 | 0.548624E+10 | 6734.81 | 13-MAR-09:20 | 2.03 | 0.68 |
April | 0.449149E+11 | 81693.14 | 24-APR-04:13 | 4.40 | 3.41 | 0.488168E+10 | 6734.83 | 07-APR-09:20 | 4.40 | 3.41 |
May | 0.467262E+11 | 86637.38 | 30-MAY-04:12 | 10.60 | 8.25 | 0.528521E+10 | 6734.87 | 24-MAY-09:09 | 10.60 | 8.25 |
June | 0.522084E+11 | 86935.94 | 19-JUN-04:13 | 17.40 | 16.54 | 0.526902E+10 | 6734.86 | 13-JUN-09:00 | 17.40 | 16.54 |
July | 0.588711E+11 | 85008.94 | 13-JUL-04:13 | 15.73 | 15.39 | 0.490000E+10 | 7100.48 | 05-JUL-13:09 | 15.73 | 15.39 |
August | 0.641006E+11 | 81716.06 | 02-AUG-04:13 | 10.40 | 9.44 | 0.549630E+10 | 6734.79 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.434822E+11 | 86770.23 | 05-SEP-04:11 | 6.33 | 5.88 | 0.488153E+10 | 6734.81 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.407803E+11 | 83050.52 | 23-OCT-04:11 | 5.60 | 4.25 | 0.507565E+10 | 6734.80 | 25-OCT-09:00 | 3.30 | 3.04 |
November | 0.350807E+11 | 77736.60 | 13-NOV-05:01 | -7.9 | -8.8 | 0.502120E+10 | 6734.79 | 27-NOV-10:20 | -6.5 | -7.0 |
December | 0.294046E+11 | 74873.28 | 29-DEC-06:02 | -16.7 | -17.0 | 0.486736E+10 | 6734.85 | 11-DEC-10:20 | -16.7 | -17.0 |
Annual Sum or Average | 0.502971E+12 | 0.606072E+11 | ||||||||
Minimum of Months | 0.230033E+11 | 36668.04 | -16.7 | -17.0 | 0.456276E+10 | 6734.79 | -21.5 | -21.8 | ||
Maximum of Months | 0.641006E+11 | 86935.94 | 17.40 | 16.54 | 0.549630E+10 | 7100.48 | 19.03 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164123E+11 | 16648.86 | 18-JAN-15:20 | -1.8 | -2.3 | 0.405764E+10 | 6279.93 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.179282E+11 | 17412.44 | 28-FEB-13:40 | 3.33 | -0.5 | 0.392110E+10 | 6559.89 | 10-FEB-14:00 | 3.33 | -0.5 |
March | 0.231214E+11 | 42908.52 | 30-MAR-05:03 | -1.9 | -2.1 | 0.506269E+10 | 6734.73 | 31-MAR-09:09 | 0.28 | -1.7 |
April | 0.265140E+11 | 68113.64 | 15-APR-05:02 | 5.60 | 5.31 | 0.478656E+10 | 6734.82 | 07-APR-09:20 | 5.60 | 5.31 |
May | 0.371393E+11 | 77265.42 | 30-MAY-04:12 | 10.60 | 8.25 | 0.527397E+10 | 6735.36 | 09-MAY-09:30 | 10.60 | 8.25 |
June | 0.405069E+11 | 73185.42 | 19-JUN-04:12 | 17.40 | 16.54 | 0.526313E+10 | 6734.81 | 13-JUN-09:00 | 17.40 | 16.54 |
July | 0.414570E+11 | 74300.61 | 31-JUL-04:12 | 15.20 | 13.38 | 0.489567E+10 | 6907.62 | 05-JUL-13:09 | 15.20 | 13.38 |
August | 0.422531E+11 | 73061.64 | 28-AUG-04:12 | 13.90 | 12.96 | 0.549071E+10 | 6734.82 | 10-AUG-13:39 | 13.90 | 12.96 |
September | 0.336462E+11 | 72453.49 | 05-SEP-04:11 | 6.33 | 5.88 | 0.486183E+10 | 6734.81 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.263223E+11 | 66909.01 | 03-OCT-05:02 | 5.50 | 4.25 | 0.497853E+10 | 6734.80 | 26-OCT-09:20 | 8.13 | 6.70 |
November | 0.196559E+11 | 22162.88 | 17-NOV-17:00 | 6.70 | 1.30 | 0.459877E+10 | 6734.66 | 10-NOV-14:09 | 6.70 | 1.30 |
December | 0.179528E+11 | 14907.29 | 01-DEC-17:00 | -19.7 | -20.2 | 0.398528E+10 | 6371.13 | 01-DEC-14:00 | -19.7 | -20.2 |
Annual Sum or Average | 0.342909E+12 | 0.571759E+11 | ||||||||
Minimum of Months | 0.164123E+11 | 14907.29 | -19.7 | -20.2 | 0.392110E+10 | 6279.93 | -19.7 | -20.2 | ||
Maximum of Months | 0.422531E+11 | 77265.42 | 17.40 | 16.54 | 0.549071E+10 | 6907.62 | 18.90 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.810690E+10 | 12885.85 | 20-JAN-16:55 | -7.2 | -8.4 | 0.378767E+10 | 5619.41 | 19-JAN-14:00 | -7.2 | -8.4 |
February | 0.102611E+11 | 15063.51 | 28-FEB-14:10 | 4.27 | 0.38 | 0.354687E+10 | 6133.65 | 08-FEB-14:00 | 4.27 | 0.38 |
March | 0.157220E+11 | 20962.85 | 29-MAR-15:40 | 4.80 | 1.35 | 0.447871E+10 | 6732.57 | 29-MAR-13:00 | 4.80 | 1.35 |
April | 0.205811E+11 | 31676.83 | 13-APR-16:00 | 20.00 | 8.11 | 0.441970E+10 | 6734.65 | 20-APR-13:20 | 9.60 | 2.32 |
May | 0.334985E+11 | 70621.26 | 26-MAY-04:12 | 19.40 | 15.71 | 0.520532E+10 | 6734.84 | 24-MAY-09:09 | 19.40 | 15.71 |
June | 0.397007E+11 | 72695.62 | 19-JUN-04:12 | 17.40 | 16.54 | 0.524436E+10 | 6734.79 | 26-JUN-13:20 | 25.97 | 17.06 |
July | 0.413457E+11 | 71318.22 | 20-JUL-05:04 | 15.37 | 15.25 | 0.488766E+10 | 6958.23 | 05-JUL-13:09 | 15.37 | 15.25 |
August | 0.400789E+11 | 71087.82 | 09-AUG-04:12 | 18.70 | 17.59 | 0.547553E+10 | 6734.80 | 10-AUG-13:50 | 19.22 | 16.66 |
September | 0.274719E+11 | 69284.43 | 01-SEP-05:02 | 15.68 | 15.63 | 0.477417E+10 | 6734.77 | 14-SEP-09:20 | 13.73 | 10.59 |
October | 0.187522E+11 | 29614.89 | 20-OCT-16:00 | 18.30 | 9.93 | 0.448131E+10 | 6734.63 | 02-OCT-13:20 | 18.30 | 9.93 |
November | 0.133629E+11 | 15270.65 | 17-NOV-16:50 | 7.25 | 1.63 | 0.404422E+10 | 6439.94 | 17-NOV-14:00 | 7.25 | 1.63 |
December | 0.882185E+10 | 13063.76 | 28-DEC-17:00 | -2.4 | -4.0 | 0.367650E+10 | 5754.18 | 28-DEC-14:00 | -2.4 | -4.0 |
Annual Sum or Average | 0.277704E+12 | 0.540220E+11 | ||||||||
Minimum of Months | 0.810690E+10 | 12885.85 | -7.2 | -8.4 | 0.354687E+10 | 5619.41 | -7.2 | -8.4 | ||
Maximum of Months | 0.413457E+11 | 72695.62 | 20.00 | 17.59 | 0.547553E+10 | 6958.23 | 25.97 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419322E+09 | 1642.44 | 19-JAN-14:20 | -2.8 | -3.6 | 0.474291E+09 | 731.72 | 19-JAN-14:30 | -2.8 | -3.6 |
February | 0.114703E+10 | 2158.02 | 28-FEB-13:30 | 3.05 | -0.7 | 0.459941E+09 | 835.04 | 21-FEB-14:30 | 3.05 | -0.7 |
March | 0.243263E+10 | 4413.27 | 27-MAR-13:30 | 6.15 | 2.33 | 0.603853E+09 | 845.62 | 24-MAR-13:30 | 6.15 | 2.33 |
April | 0.394945E+10 | 6536.84 | 18-APR-13:10 | 18.22 | 10.57 | 0.594221E+09 | 845.63 | 18-APR-09:20 | 18.22 | 10.57 |
May | 0.675420E+10 | 11338.60 | 24-MAY-05:02 | 13.13 | 10.07 | 0.661503E+09 | 845.64 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.901327E+10 | 11749.98 | 19-JUN-04:12 | 17.40 | 16.54 | 0.661737E+09 | 845.97 | 29-JUN-13:50 | 32.88 | 24.59 |
July | 0.100983E+11 | 15219.29 | 23-JUL-15:21 | 30.00 | 22.65 | 0.616703E+09 | 934.51 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.934615E+10 | 11252.73 | 31-AUG-05:02 | 16.70 | 16.02 | 0.689969E+09 | 845.71 | 09-AUG-13:39 | 16.70 | 16.02 |
September | 0.492459E+10 | 7215.85 | 01-SEP-15:00 | 26.10 | 17.82 | 0.607348E+09 | 845.64 | 11-SEP-13:39 | 18.90 | 14.59 |
October | 0.329285E+10 | 5323.20 | 02-OCT-13:10 | 10.92 | 9.77 | 0.614555E+09 | 845.62 | 06-OCT-13:20 | 5.97 | 5.15 |
November | 0.220764E+10 | 4065.59 | 01-NOV-13:30 | 17.80 | 13.07 | 0.563939E+09 | 845.62 | 21-NOV-10:00 | 12.80 | 12.80 |
December | 0.973688E+09 | 2137.33 | 06-DEC-06:03 | -0.8 | -0.8 | 0.473786E+09 | 770.44 | 05-DEC-14:09 | -0.8 | -0.8 |
Annual Sum or Average | 0.545592E+11 | 0.702185E+10 | ||||||||
Minimum of Months | 0.419322E+09 | 1642.44 | -2.8 | -3.6 | 0.459941E+09 | 731.72 | -2.8 | -3.6 | ||
Maximum of Months | 0.100983E+11 | 15219.29 | 30.00 | 22.65 | 0.689969E+09 | 934.51 | 32.88 | 24.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442201E+09 | 1415.81 | 25-JAN-10:20 | -23.1 | -23.4 | 0.313895E+09 | 544.96 | 25-JAN-10:20 | -23.1 | -23.4 |
February | 0.103600E+10 | 5417.47 | 28-FEB-09:45 | -6.8 | -8.3 | 0.316580E+09 | 544.95 | 27-FEB-10:09 | -6.8 | -8.3 |
March | 0.246092E+10 | 10153.83 | 20-MAR-09:05 | -2.5 | -4.0 | 0.405572E+09 | 544.96 | 24-MAR-09:30 | -1.7 | -4.2 |
April | 0.473732E+10 | 17879.20 | 16-APR-09:13 | 4.80 | 1.81 | 0.386664E+09 | 544.96 | 18-APR-09:39 | 18.13 | 11.06 |
May | 0.680133E+10 | 21615.93 | 21-MAY-08:22 | 10.70 | 6.49 | 0.427592E+09 | 545.72 | 17-MAY-09:09 | 10.70 | 6.49 |
June | 0.868340E+10 | 23592.62 | 25-JUN-08:12 | 24.27 | 20.87 | 0.426779E+09 | 545.97 | 27-JUN-09:30 | 25.55 | 19.23 |
July | 0.945879E+10 | 24924.56 | 23-JUL-09:21 | 25.85 | 22.64 | 0.396930E+09 | 552.98 | 05-JUL-13:09 | 25.85 | 22.64 |
August | 0.772845E+10 | 25709.03 | 20-AUG-08:21 | 19.45 | 15.19 | 0.444755E+09 | 545.80 | 22-AUG-09:09 | 20.18 | 14.51 |
September | 0.481878E+10 | 17265.03 | 10-SEP-10:23 | 16.40 | 10.55 | 0.392260E+09 | 546.27 | 05-SEP-09:09 | 16.40 | 10.55 |
October | 0.257592E+10 | 17954.58 | 22-OCT-09:13 | 13.67 | 11.29 | 0.396262E+09 | 544.96 | 19-OCT-09:00 | 13.67 | 11.29 |
November | 0.144860E+10 | 5113.63 | 16-NOV-09:25 | 0.55 | -1.2 | 0.365257E+09 | 544.95 | 29-NOV-10:30 | -8.6 | -9.6 |
December | 0.553052E+09 | 1690.32 | 01-DEC-10:05 | -20.6 | -20.9 | 0.305757E+09 | 544.95 | 01-DEC-10:39 | -20.1 | -20.5 |
Annual Sum or Average | 0.507448E+11 | 0.457830E+10 | ||||||||
Minimum of Months | 0.442201E+09 | 1415.81 | -23.1 | -23.4 | 0.305757E+09 | 544.95 | -23.1 | -23.4 | ||
Maximum of Months | 0.945879E+10 | 25709.03 | 25.85 | 22.64 | 0.444755E+09 | 552.98 | 25.85 | 22.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250895E+10 | 15781.48 | 27-JAN-13:25 | -15.0 | -16.1 | 0.541055E+09 | 845.66 | 06-JAN-14:09 | -15.0 | -16.1 |
February | 0.455133E+10 | 20530.76 | 28-FEB-13:20 | 2.77 | -0.9 | 0.520203E+09 | 848.50 | 27-FEB-14:00 | 2.77 | -0.9 |
March | 0.618648E+10 | 27597.17 | 26-MAR-13:22 | 8.60 | 4.34 | 0.634164E+09 | 853.52 | 17-MAR-13:09 | 8.60 | 4.34 |
April | 0.822835E+10 | 30835.42 | 23-APR-13:21 | 23.60 | 15.70 | 0.592834E+09 | 846.67 | 18-APR-13:50 | 23.60 | 15.70 |
May | 0.974600E+10 | 27190.71 | 21-MAY-11:43 | 17.48 | 10.01 | 0.660631E+09 | 847.33 | 24-MAY-13:00 | 27.10 | 17.69 |
June | 0.109554E+11 | 26924.46 | 04-JUN-13:13 | 19.80 | 11.16 | 0.661524E+09 | 846.51 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.130918E+11 | 30193.47 | 23-JUL-13:21 | 30.00 | 22.65 | 0.616781E+09 | 945.51 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.136117E+11 | 30342.26 | 20-AUG-12:21 | 24.70 | 15.94 | 0.690685E+09 | 848.58 | 01-AUG-13:00 | 24.70 | 15.94 |
September | 0.940913E+10 | 28999.13 | 04-SEP-12:12 | 15.77 | 9.39 | 0.608072E+09 | 874.09 | 01-SEP-13:20 | 15.77 | 9.39 |
October | 0.642601E+10 | 29949.88 | 22-OCT-13:11 | 18.67 | 12.99 | 0.610899E+09 | 852.27 | 18-OCT-13:09 | 18.67 | 12.99 |
November | 0.406623E+10 | 18589.99 | 17-NOV-12:00 | 8.90 | 2.91 | 0.578902E+09 | 845.90 | 17-NOV-14:09 | 10.60 | 3.43 |
December | 0.226861E+10 | 13138.19 | 02-DEC-12:50 | -19.2 | -19.9 | 0.510647E+09 | 845.65 | 19-DEC-14:20 | -22.5 | -23.0 |
Annual Sum or Average | 0.910499E+11 | 0.722640E+10 | ||||||||
Minimum of Months | 0.226861E+10 | 13138.19 | -19.2 | -19.9 | 0.510647E+09 | 845.65 | -22.5 | -23.0 | ||
Maximum of Months | 0.136117E+11 | 30835.42 | 30.00 | 22.65 | 0.690685E+09 | 945.51 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.906058E+09 | 4903.48 | 20-JAN-15:50 | -5.5 | -7.2 | 0.332571E+09 | 544.95 | 26-JAN-14:39 | -16.5 | -17.6 |
February | 0.218810E+10 | 10575.84 | 20-FEB-16:13 | 8.33 | 2.67 | 0.338325E+09 | 544.95 | 01-FEB-14:30 | 8.33 | 2.67 |
March | 0.480539E+10 | 27793.15 | 26-MAR-16:42 | 10.18 | 5.01 | 0.435181E+09 | 544.95 | 24-MAR-09:30 | 10.18 | 5.01 |
April | 0.849951E+10 | 34718.12 | 23-APR-16:41 | 26.20 | 16.72 | 0.395516E+09 | 544.96 | 07-APR-09:20 | 26.20 | 16.72 |
May | 0.923878E+10 | 29313.73 | 14-MAY-16:41 | 20.00 | 8.40 | 0.428548E+09 | 544.97 | 16-MAY-13:20 | 24.67 | 15.35 |
June | 0.113268E+11 | 28809.56 | 17-JUN-17:41 | 23.90 | 13.28 | 0.427703E+09 | 544.97 | 13-JUN-09:00 | 23.90 | 13.28 |
July | 0.137946E+11 | 33334.38 | 23-JUL-16:01 | 29.72 | 22.65 | 0.398567E+09 | 558.47 | 05-JUL-13:00 | 29.72 | 22.65 |
August | 0.140679E+11 | 29213.16 | 05-AUG-17:41 | 22.30 | 14.14 | 0.446528E+09 | 544.98 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.654080E+10 | 28210.92 | 03-SEP-16:52 | 21.70 | 16.12 | 0.395437E+09 | 544.96 | 11-SEP-13:39 | 18.90 | 14.59 |
October | 0.478087E+10 | 19941.42 | 22-OCT-14:32 | 19.40 | 12.77 | 0.409440E+09 | 544.95 | 25-OCT-09:00 | 3.30 | 3.04 |
November | 0.314151E+10 | 9070.13 | 21-NOV-06:03 | 10.10 | 9.75 | 0.400264E+09 | 544.96 | 21-NOV-10:00 | 12.80 | 12.80 |
December | 0.192754E+10 | 5787.20 | 06-DEC-06:01 | -0.8 | -0.8 | 0.367546E+09 | 544.96 | 19-DEC-14:20 | -22.5 | -23.0 |
Annual Sum or Average | 0.812179E+11 | 0.477563E+10 | ||||||||
Minimum of Months | 0.906058E+09 | 4903.48 | -5.5 | -7.2 | 0.332571E+09 | 544.95 | -22.5 | -23.0 | ||
Maximum of Months | 0.140679E+11 | 34718.12 | 29.72 | 22.65 | 0.446528E+09 | 558.47 | 29.72 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11026624.68 | 1204.91 | 21-JAN-17:02 | -5.0 | -7.1 | 0.459013E+09 | 625.98 | 04-JAN-14:50 | -5.0 | -7.1 |
February | 98079663.81 | 1541.85 | 08-FEB-14:00 | 5.00 | -0.5 | 0.420953E+09 | 656.72 | 08-FEB-14:00 | 5.00 | -0.5 |
March | 0.729339E+09 | 2630.81 | 31-MAR-09:10 | 0.28 | -1.7 | 0.521613E+09 | 781.89 | 28-MAR-13:00 | 0.28 | -1.7 |
April | 0.205080E+10 | 4111.38 | 18-APR-14:00 | 17.80 | 10.49 | 0.522946E+09 | 845.61 | 14-APR-13:20 | 17.80 | 10.49 |
May | 0.535432E+10 | 7871.80 | 26-MAY-13:30 | 22.50 | 17.44 | 0.650523E+09 | 845.64 | 24-MAY-09:09 | 22.50 | 17.44 |
June | 0.740553E+10 | 13756.67 | 25-JUN-11:21 | 27.25 | 21.76 | 0.659908E+09 | 846.65 | 28-JUN-13:20 | 30.00 | 21.52 |
July | 0.781303E+10 | 14292.91 | 23-JUL-15:21 | 30.00 | 22.65 | 0.615485E+09 | 914.01 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.634270E+10 | 8018.81 | 09-AUG-14:00 | 27.20 | 21.48 | 0.686098E+09 | 845.65 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.358071E+10 | 6628.96 | 01-SEP-05:02 | 15.68 | 15.63 | 0.587183E+09 | 845.63 | 11-SEP-13:39 | 18.90 | 14.59 |
October | 0.197849E+10 | 2808.88 | 02-OCT-13:30 | 10.55 | 9.63 | 0.533442E+09 | 845.61 | 02-OCT-13:30 | 10.55 | 9.63 |
November | 0.571051E+09 | 1869.94 | 01-NOV-15:30 | 18.05 | 13.35 | 0.472136E+09 | 790.03 | 01-NOV-13:00 | 18.05 | 13.35 |
December | 12525375.19 | 1206.83 | 30-DEC-17:03 | -3.3 | -3.3 | 0.444630E+09 | 625.90 | 21-DEC-10:09 | -3.3 | -3.3 |
Annual Sum or Average | 0.359476E+11 | 0.657393E+10 | ||||||||
Minimum of Months | 11026624.68 | 1204.91 | -5.0 | -7.1 | 0.420953E+09 | 625.90 | -5.0 | -7.1 | ||
Maximum of Months | 0.781303E+10 | 14292.91 | 30.00 | 22.65 | 0.686098E+09 | 914.01 | 30.00 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52220258.35 | 1143.39 | 18-JAN-15:20 | -1.8 | -2.3 | 0.216162E+09 | 425.58 | 25-JAN-11:09 | -22.4 | -22.8 |
February | 0.232732E+09 | 3676.69 | 28-FEB-11:05 | -2.4 | -4.8 | 0.204984E+09 | 548.49 | 28-FEB-11:09 | -2.4 | -4.8 |
March | 0.115379E+10 | 9283.95 | 31-MAR-10:05 | 2.07 | -0.7 | 0.270834E+09 | 548.49 | 20-MAR-10:09 | 2.07 | -0.7 |
April | 0.351065E+10 | 13462.53 | 18-APR-10:05 | 18.12 | 11.26 | 0.273949E+09 | 548.50 | 18-APR-10:09 | 18.12 | 11.26 |
May | 0.627048E+10 | 26162.82 | 21-MAY-08:11 | 10.20 | 6.18 | 0.313997E+09 | 548.51 | 23-MAY-10:09 | 18.85 | 13.45 |
June | 0.849987E+10 | 28901.68 | 25-JUN-08:41 | 24.82 | 21.01 | 0.314335E+09 | 548.52 | 13-JUN-10:09 | 24.82 | 21.01 |
July | 0.905154E+10 | 27960.63 | 23-JUL-09:21 | 25.85 | 22.64 | 0.293775E+09 | 551.32 | 05-JUL-14:09 | 25.85 | 22.64 |
August | 0.680615E+10 | 27884.83 | 20-AUG-09:11 | 21.33 | 15.66 | 0.327300E+09 | 548.51 | 04-AUG-10:09 | 21.33 | 15.66 |
September | 0.405451E+10 | 20524.99 | 10-SEP-10:52 | 17.20 | 10.48 | 0.283555E+09 | 548.50 | 06-SEP-10:09 | 17.20 | 10.48 |
October | 0.153967E+10 | 12355.83 | 22-OCT-09:13 | 13.67 | 11.29 | 0.265083E+09 | 548.50 | 19-OCT-10:09 | 13.67 | 11.29 |
November | 0.418202E+09 | 3404.74 | 16-NOV-11:05 | 4.68 | 0.79 | 0.231882E+09 | 548.48 | 17-NOV-11:09 | 7.07 | 2.03 |
December | 48921906.86 | 950.74 | 01-DEC-10:00 | -20.8 | -21.1 | 0.208319E+09 | 416.87 | 01-DEC-09:00 | -20.8 | -21.1 |
Annual Sum or Average | 0.416387E+11 | 0.320417E+10 | ||||||||
Minimum of Months | 48921906.86 | 950.74 | -20.8 | -21.1 | 0.204984E+09 | 416.87 | -22.4 | -22.8 | ||
Maximum of Months | 0.905154E+10 | 28901.68 | 25.85 | 22.64 | 0.327300E+09 | 551.32 | 25.85 | 22.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194431E+10 | 16459.03 | 27-JAN-13:35 | -14.8 | -15.9 | 0.517334E+09 | 845.66 | 06-JAN-14:09 | -14.8 | -15.9 |
February | 0.371932E+10 | 21517.07 | 28-FEB-13:30 | 3.05 | -0.7 | 0.496147E+09 | 845.84 | 27-FEB-14:00 | 3.05 | -0.7 |
March | 0.513957E+10 | 30591.37 | 26-MAR-13:12 | 8.50 | 4.25 | 0.600946E+09 | 868.66 | 24-MAR-13:20 | 8.50 | 4.25 |
April | 0.705201E+10 | 29718.47 | 23-APR-13:42 | 24.13 | 15.95 | 0.568408E+09 | 846.67 | 20-APR-13:20 | 24.13 | 15.95 |
May | 0.925763E+10 | 28994.14 | 21-MAY-12:12 | 18.37 | 10.32 | 0.655282E+09 | 847.24 | 25-MAY-13:20 | 27.07 | 19.13 |
June | 0.100502E+11 | 29777.34 | 18-JUN-12:32 | 26.10 | 17.75 | 0.659515E+09 | 847.48 | 26-JUN-13:20 | 25.97 | 17.06 |
July | 0.115427E+11 | 31417.83 | 23-JUL-13:21 | 30.00 | 22.65 | 0.615860E+09 | 924.20 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.115646E+11 | 32014.85 | 20-AUG-13:11 | 25.00 | 15.73 | 0.688588E+09 | 847.70 | 01-AUG-13:00 | 25.00 | 15.73 |
September | 0.916679E+10 | 30717.28 | 03-SEP-15:11 | 21.70 | 16.21 | 0.599948E+09 | 904.17 | 01-SEP-13:20 | 21.70 | 16.21 |
October | 0.587568E+10 | 31728.22 | 22-OCT-13:11 | 18.67 | 12.99 | 0.578664E+09 | 879.82 | 18-OCT-13:39 | 18.67 | 12.99 |
November | 0.287039E+10 | 19092.54 | 17-NOV-13:10 | 10.10 | 3.25 | 0.534886E+09 | 862.03 | 10-NOV-10:50 | 10.10 | 3.25 |
December | 0.111463E+10 | 12061.69 | 02-DEC-13:25 | -18.6 | -19.3 | 0.478901E+09 | 845.65 | 14-DEC-14:20 | -16.7 | -17.6 |
Annual Sum or Average | 0.792977E+11 | 0.699448E+10 | ||||||||
Minimum of Months | 0.111463E+10 | 12061.69 | -18.6 | -19.3 | 0.478901E+09 | 845.65 | -16.7 | -17.6 | ||
Maximum of Months | 0.115646E+11 | 32014.85 | 30.00 | 22.65 | 0.688588E+09 | 924.20 | 30.00 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146188E+09 | 2254.69 | 27-JAN-15:50 | -14.4 | -15.6 | 0.304969E+09 | 521.18 | 25-JAN-16:30 | -14.4 | -15.6 |
February | 0.569961E+09 | 5920.12 | 08-FEB-16:30 | 3.85 | -1.1 | 0.288245E+09 | 544.92 | 28-FEB-14:00 | 6.10 | 1.55 |
March | 0.173273E+10 | 24448.50 | 26-MAR-16:31 | 10.37 | 5.10 | 0.360850E+09 | 544.94 | 24-MAR-13:00 | 10.37 | 5.10 |
April | 0.388067E+10 | 27869.75 | 23-APR-17:01 | 26.02 | 16.64 | 0.357982E+09 | 544.95 | 18-APR-09:20 | 26.02 | 16.64 |
May | 0.731465E+10 | 30937.24 | 14-MAY-17:11 | 20.00 | 8.46 | 0.423567E+09 | 544.96 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.832862E+10 | 27227.03 | 17-JUN-17:41 | 23.90 | 13.28 | 0.426156E+09 | 544.96 | 13-JUN-09:00 | 23.90 | 13.28 |
July | 0.938376E+10 | 30528.19 | 23-JUL-16:01 | 29.72 | 22.65 | 0.397479E+09 | 553.97 | 05-JUL-13:09 | 29.72 | 22.65 |
August | 0.787981E+10 | 27492.86 | 20-AUG-15:51 | 24.40 | 15.10 | 0.444516E+09 | 544.97 | 10-AUG-13:39 | 24.40 | 15.10 |
September | 0.445956E+10 | 29771.58 | 03-SEP-16:31 | 21.70 | 16.02 | 0.385425E+09 | 544.96 | 11-SEP-13:39 | 18.90 | 14.59 |
October | 0.223473E+10 | 14038.17 | 22-OCT-15:52 | 18.90 | 12.36 | 0.363321E+09 | 544.95 | 19-OCT-13:20 | 18.90 | 12.36 |
November | 0.724215E+09 | 4099.22 | 17-NOV-15:40 | 10.20 | 3.28 | 0.321356E+09 | 544.94 | 16-NOV-14:39 | 10.20 | 3.28 |
December | 0.116350E+09 | 1101.49 | 20-DEC-15:40 | -19.8 | -20.5 | 0.290078E+09 | 464.58 | 20-DEC-15:50 | -20.0 | -20.7 |
Annual Sum or Average | 0.467712E+11 | 0.436394E+10 | ||||||||
Minimum of Months | 0.116350E+09 | 1101.49 | -19.8 | -20.5 | 0.288245E+09 | 464.58 | -20.0 | -20.7 | ||
Maximum of Months | 0.938376E+10 | 30937.24 | 29.72 | 22.65 | 0.444516E+09 | 553.97 | 29.72 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8923570.78 | 1348.74 | 21-JAN-17:02 | -5.0 | -7.1 | 0.457527E+09 | 626.05 | 13-JAN-10:20 | -5.0 | -7.1 |
February | 58347723.57 | 1491.75 | 08-FEB-14:50 | 5.00 | -0.5 | 0.418648E+09 | 630.23 | 08-FEB-14:50 | 5.00 | -0.5 |
March | 0.383269E+09 | 2042.91 | 31-MAR-14:00 | 8.30 | 3.10 | 0.509235E+09 | 717.24 | 28-MAR-13:00 | 8.30 | 3.10 |
April | 0.154898E+10 | 3886.93 | 13-APR-16:00 | 20.00 | 8.11 | 0.492226E+09 | 845.61 | 14-APR-13:20 | 16.10 | 7.09 |
May | 0.508228E+10 | 8526.99 | 24-MAY-14:30 | 27.45 | 17.67 | 0.631744E+09 | 845.64 | 23-MAY-13:50 | 27.45 | 17.67 |
June | 0.735541E+10 | 12980.21 | 27-JUN-05:02 | 15.68 | 14.97 | 0.655670E+09 | 845.66 | 26-JUN-13:09 | 15.68 | 14.97 |
July | 0.786925E+10 | 17727.51 | 23-JUL-15:31 | 30.00 | 22.71 | 0.613126E+09 | 866.90 | 05-JUL-13:09 | 30.00 | 22.71 |
August | 0.621422E+10 | 8615.20 | 08-AUG-15:10 | 30.60 | 23.30 | 0.678316E+09 | 845.65 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.316759E+10 | 7150.99 | 01-SEP-15:20 | 26.10 | 17.76 | 0.555431E+09 | 845.63 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.124274E+10 | 2775.19 | 20-OCT-13:10 | 18.40 | 9.83 | 0.491212E+09 | 812.87 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.247445E+09 | 1909.44 | 01-NOV-16:00 | 17.80 | 13.26 | 0.461091E+09 | 718.95 | 01-NOV-13:00 | 17.80 | 13.26 |
December | 11378389.65 | 1353.34 | 30-DEC-17:03 | -3.3 | -3.3 | 0.443120E+09 | 625.91 | 15-DEC-10:09 | -3.3 | -3.3 |
Annual Sum or Average | 0.331898E+11 | 0.640735E+10 | ||||||||
Minimum of Months | 8923570.78 | 1348.74 | -5.0 | -7.1 | 0.418648E+09 | 625.91 | -5.0 | -7.1 | ||
Maximum of Months | 0.786925E+10 | 17727.51 | 30.60 | 23.30 | 0.678316E+09 | 866.90 | 30.00 | 22.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12616511.34 | 895.89 | 19-JAN-06:04 | -3.3 | -3.7 | 0.298365E+09 | 404.28 | 25-JAN-10:30 | -23.1 | -23.4 |
February | 0.178099E+09 | 1247.89 | 28-FEB-10:20 | -5.0 | -6.8 | 0.276397E+09 | 536.92 | 28-FEB-10:50 | -3.3 | -5.5 |
March | 0.843437E+09 | 5412.53 | 31-MAR-10:00 | 1.70 | -0.9 | 0.358102E+09 | 544.95 | 14-MAR-09:00 | 1.70 | -0.9 |
April | 0.295732E+10 | 11936.84 | 18-APR-09:30 | 18.05 | 10.95 | 0.362430E+09 | 544.96 | 18-APR-09:39 | 18.13 | 11.06 |
May | 0.600232E+10 | 24199.66 | 21-MAY-08:41 | 11.70 | 7.10 | 0.422089E+09 | 546.02 | 18-MAY-09:50 | 11.70 | 7.10 |
June | 0.856766E+10 | 27720.88 | 18-JUN-08:41 | 21.32 | 14.26 | 0.425159E+09 | 546.03 | 27-JUN-09:50 | 25.92 | 19.10 |
July | 0.923525E+10 | 25497.54 | 23-JUL-09:32 | 26.13 | 22.79 | 0.396406E+09 | 547.05 | 05-JUL-13:00 | 26.13 | 22.79 |
August | 0.680400E+10 | 24851.78 | 20-AUG-09:22 | 21.70 | 15.75 | 0.442257E+09 | 544.97 | 10-AUG-13:39 | 21.70 | 15.75 |
September | 0.370423E+10 | 14489.74 | 10-SEP-09:22 | 14.45 | 10.33 | 0.374948E+09 | 544.96 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.116376E+10 | 7198.95 | 19-OCT-09:30 | 12.50 | 9.01 | 0.334930E+09 | 544.95 | 18-OCT-13:20 | 12.50 | 9.01 |
November | 0.288116E+09 | 1231.56 | 16-NOV-10:10 | 2.15 | -0.3 | 0.303804E+09 | 526.05 | 16-NOV-10:20 | 2.60 | 0.02 |
December | 18289753.57 | 896.12 | 28-DEC-06:04 | -2.3 | -2.8 | 0.287767E+09 | 407.31 | 28-DEC-10:30 | -2.8 | -4.0 |
Annual Sum or Average | 0.397751E+11 | 0.428266E+10 | ||||||||
Minimum of Months | 12616511.34 | 895.89 | -5.0 | -6.8 | 0.276397E+09 | 404.28 | -23.1 | -23.4 | ||
Maximum of Months | 0.923525E+10 | 27720.88 | 26.13 | 22.79 | 0.442257E+09 | 547.05 | 26.13 | 22.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147875E+10 | 14203.02 | 27-JAN-13:35 | -14.8 | -15.9 | 0.507825E+09 | 845.65 | 06-JAN-14:09 | -14.8 | -15.9 |
February | 0.297180E+10 | 20603.17 | 28-FEB-13:40 | 3.33 | -0.5 | 0.484039E+09 | 845.81 | 28-FEB-14:50 | 5.73 | 1.32 |
March | 0.385998E+10 | 29401.26 | 26-MAR-14:21 | 9.75 | 4.96 | 0.583114E+09 | 848.48 | 17-MAR-13:39 | 9.75 | 4.96 |
April | 0.589913E+10 | 32770.83 | 23-APR-14:51 | 25.60 | 16.48 | 0.548745E+09 | 846.30 | 13-APR-13:00 | 25.60 | 16.48 |
May | 0.865644E+10 | 30169.15 | 21-MAY-14:02 | 21.38 | 11.23 | 0.644043E+09 | 847.20 | 24-MAY-13:00 | 27.10 | 17.69 |
June | 0.992888E+10 | 31650.54 | 18-JUN-12:42 | 26.10 | 17.78 | 0.655582E+09 | 846.53 | 28-JUN-13:00 | 30.00 | 21.52 |
July | 0.115247E+11 | 31147.63 | 23-JUL-12:52 | 30.00 | 22.84 | 0.613748E+09 | 901.11 | 05-JUL-13:09 | 30.00 | 22.84 |
August | 0.112247E+11 | 31636.31 | 27-AUG-14:32 | 22.93 | 18.30 | 0.684458E+09 | 847.24 | 01-AUG-13:50 | 22.93 | 18.30 |
September | 0.818121E+10 | 32402.95 | 03-SEP-14:02 | 21.20 | 15.97 | 0.582731E+09 | 890.61 | 01-SEP-13:39 | 21.20 | 15.97 |
October | 0.460259E+10 | 34635.93 | 22-OCT-14:21 | 19.40 | 12.77 | 0.540458E+09 | 845.98 | 20-OCT-13:00 | 19.40 | 12.77 |
November | 0.213763E+10 | 16954.05 | 17-NOV-13:10 | 10.10 | 3.25 | 0.510664E+09 | 845.64 | 28-NOV-14:39 | -7.4 | -8.7 |
December | 0.743974E+09 | 9599.53 | 02-DEC-13:30 | -18.6 | -19.3 | 0.472480E+09 | 845.65 | 19-DEC-14:20 | -22.5 | -23.0 |
Annual Sum or Average | 0.712099E+11 | 0.682788E+10 | ||||||||
Minimum of Months | 0.743974E+09 | 9599.53 | -18.6 | -19.3 | 0.472480E+09 | 845.64 | -22.5 | -23.0 | ||
Maximum of Months | 0.115247E+11 | 34635.93 | 30.00 | 22.84 | 0.684458E+09 | 901.11 | 30.00 | 22.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101726E+09 | 1280.93 | 27-JAN-16:00 | -14.4 | -15.6 | 0.302659E+09 | 520.50 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.446259E+09 | 5666.60 | 28-FEB-15:50 | 6.10 | 1.55 | 0.284629E+09 | 544.92 | 28-FEB-14:00 | 6.10 | 1.55 |
March | 0.131354E+10 | 10189.85 | 28-MAR-17:00 | 7.20 | 3.52 | 0.349724E+09 | 544.91 | 31-MAR-13:00 | 8.30 | 3.10 |
April | 0.336983E+10 | 32494.90 | 23-APR-16:51 | 26.10 | 16.67 | 0.341161E+09 | 544.95 | 18-APR-09:00 | 26.10 | 16.67 |
May | 0.698540E+10 | 31928.89 | 14-MAY-17:11 | 20.00 | 8.46 | 0.416706E+09 | 544.97 | 23-MAY-13:50 | 25.63 | 17.00 |
June | 0.825525E+10 | 28485.30 | 17-JUN-17:41 | 23.90 | 13.28 | 0.424616E+09 | 544.98 | 26-JUN-13:09 | 25.78 | 17.07 |
July | 0.934630E+10 | 29056.28 | 16-JUL-16:41 | 21.38 | 15.74 | 0.396783E+09 | 547.93 | 05-JUL-13:00 | 21.38 | 15.74 |
August | 0.766935E+10 | 29537.94 | 27-AUG-17:11 | 22.80 | 19.07 | 0.442800E+09 | 544.97 | 10-AUG-13:39 | 22.80 | 19.07 |
September | 0.398787E+10 | 30959.18 | 03-SEP-16:41 | 21.70 | 16.07 | 0.373122E+09 | 544.96 | 11-SEP-13:39 | 18.90 | 14.59 |
October | 0.168678E+10 | 16686.32 | 22-OCT-15:01 | 19.32 | 12.70 | 0.339732E+09 | 544.94 | 02-OCT-13:20 | 19.32 | 12.70 |
November | 0.444040E+09 | 3263.29 | 17-NOV-15:40 | 10.20 | 3.28 | 0.310310E+09 | 544.93 | 16-NOV-14:00 | 10.20 | 3.28 |
December | 63039445.48 | 1005.36 | 20-DEC-15:40 | -19.8 | -20.5 | 0.288840E+09 | 442.87 | 28-DEC-14:00 | -1.7 | -3.7 |
Annual Sum or Average | 0.436694E+11 | 0.427108E+10 | ||||||||
Minimum of Months | 63039445.48 | 1005.36 | -19.8 | -20.5 | 0.284629E+09 | 442.87 | -14.8 | -15.9 | ||
Maximum of Months | 0.934630E+10 | 32494.90 | 26.10 | 19.07 | 0.442800E+09 | 547.93 | 26.10 | 19.07 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33861448.53 | 8253.92 | 09-JAN-04:01 | -32.4 | -32.5 | 0.00 | 0.00 | 01-JAN-00:10 | -32.4 | -32.5 |
February | 86037896.74 | 8309.24 | 13-FEB-05:01 | -23.4 | -23.8 | 0.00 | 0.00 | 01-FEB-00:10 | -23.4 | -23.8 |
March | 0.703330E+09 | 4788.04 | 16-MAR-04:01 | -26.3 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.5 |
April | 0.290382E+10 | 6347.60 | 24-APR-05:15 | 4.40 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.40 | 3.41 |
May | 0.509917E+10 | 8591.83 | 30-MAY-05:15 | 10.60 | 8.25 | 0.00 | 0.00 | 01-MAY-00:10 | 10.60 | 8.25 |
June | 0.685805E+10 | 9534.35 | 19-JUN-05:15 | 17.80 | 16.82 | 0.00 | 0.00 | 01-JUN-00:10 | 17.80 | 16.82 |
July | 0.795384E+10 | 11628.84 | 24-JUL-05:15 | 17.97 | 16.19 | 0.00 | 0.00 | 01-JUL-00:10 | 17.97 | 16.19 |
August | 0.754358E+10 | 9703.17 | 14-AUG-05:15 | 15.73 | 13.37 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.37 |
September | 0.416499E+10 | 8531.19 | 05-SEP-05:15 | 5.60 | 5.31 | 0.00 | 0.00 | 01-SEP-00:10 | 5.60 | 5.31 |
October | 0.226301E+10 | 5985.27 | 23-OCT-05:15 | 5.60 | 4.15 | 0.00 | 0.00 | 01-OCT-00:10 | 5.60 | 4.15 |
November | 0.606337E+09 | 4826.02 | 25-NOV-05:01 | -19.0 | -19.3 | 0.00 | 0.00 | 01-NOV-00:10 | -19.0 | -19.3 |
December | 33277344.52 | 6363.75 | 19-DEC-05:01 | -25.4 | -25.8 | 0.00 | 0.00 | 01-DEC-00:10 | -25.4 | -25.8 |
Annual Sum or Average | 0.382493E+11 | 0.00 | ||||||||
Minimum of Months | 33277344.52 | 4788.04 | -32.4 | -32.5 | 0.00 | 0.00 | -32.4 | -32.5 | ||
Maximum of Months | 0.795384E+10 | 11628.84 | 17.97 | 16.82 | 0.00 | 0.00 | 17.97 | 16.82 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152820E+09 | 10470.65 | 28-JAN-04:01 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.147404E+09 | 11998.07 | 25-FEB-04:01 | -27.5 | -27.7 | 0.00 | 0.00 | 01-FEB-00:10 | -27.5 | -27.7 |
March | 0.177930E+09 | 9615.32 | 15-MAR-03:01 | -21.7 | -22.0 | 0.00 | 0.00 | 01-MAR-00:10 | -21.7 | -22.0 |
April | 0.736652E+09 | 8372.70 | 03-APR-04:01 | -5.4 | -6.8 | 0.00 | 0.00 | 01-APR-00:10 | -5.4 | -6.8 |
May | 0.315281E+10 | 5380.82 | 18-MAY-15:20 | 28.77 | 16.51 | 0.00 | 0.00 | 01-MAY-00:10 | 28.77 | 16.51 |
June | 0.480157E+10 | 6807.00 | 30-JUN-14:20 | 31.47 | 24.01 | 0.00 | 0.00 | 01-JUN-00:10 | 31.47 | 24.01 |
July | 0.575812E+10 | 7441.90 | 24-JUL-05:15 | 17.97 | 16.19 | 0.00 | 0.00 | 01-JUL-00:10 | 17.97 | 16.19 |
August | 0.469881E+10 | 5601.13 | 08-AUG-15:20 | 30.60 | 23.24 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.24 |
September | 0.232985E+10 | 5426.24 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.683143E+09 | 9570.34 | 30-OCT-04:01 | -10.0 | -10.7 | 0.00 | 0.00 | 01-OCT-00:10 | -10.0 | -10.7 |
November | 0.162634E+09 | 11297.58 | 24-NOV-04:01 | -11.0 | -11.5 | 0.00 | 0.00 | 01-NOV-00:10 | -11.0 | -11.5 |
December | 0.183890E+09 | 11354.38 | 02-DEC-04:01 | -26.8 | -27.0 | 0.00 | 0.00 | 01-DEC-00:10 | -26.8 | -27.0 |
Annual Sum or Average | 0.229856E+11 | 0.00 | ||||||||
Minimum of Months | 0.147404E+09 | 5380.82 | -27.5 | -27.7 | 0.00 | 0.00 | -27.5 | -27.7 | ||
Maximum of Months | 0.575812E+10 | 11998.07 | 31.47 | 24.01 | 0.00 | 0.00 | 31.47 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 53775385.34 | 2337.79 | 26-MAR-15:05 | 10.68 | 5.32 | 0.00 | 0.00 | 01-MAR-00:10 | 10.68 | 5.32 |
April | 0.133711E+10 | 8649.02 | 13-APR-14:50 | 19.82 | 7.99 | 0.00 | 0.00 | 01-APR-00:10 | 19.82 | 7.99 |
May | 0.545210E+10 | 15855.67 | 18-MAY-14:40 | 28.77 | 16.65 | 0.00 | 0.00 | 01-MAY-00:10 | 28.77 | 16.65 |
June | 0.820352E+10 | 18224.37 | 30-JUN-14:50 | 32.02 | 24.38 | 0.00 | 0.00 | 01-JUN-00:10 | 32.02 | 24.38 |
July | 0.954686E+10 | 17017.37 | 24-JUL-14:40 | 29.40 | 19.47 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.47 |
August | 0.681964E+10 | 15431.52 | 08-AUG-15:20 | 30.60 | 23.24 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.24 |
September | 0.255679E+10 | 12831.88 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.410279E+09 | 5424.93 | 20-OCT-14:40 | 18.90 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 18.90 | 10.07 |
November | 3893059.66 | 717.77 | 01-NOV-16:50 | 16.88 | 12.87 | 0.00 | 0.00 | 01-NOV-00:10 | 16.88 | 12.87 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.343840E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.954686E+10 | 18224.37 | 32.02 | 24.38 | 0.00 | 0.00 | 32.02 | 24.38 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135465E+10 | 1966.45 | 25-JAN-16:30 | -18.4 | -19.1 | 94856815.16 | 126.82 | 02-JAN-14:39 | -18.4 | -19.1 |
February | 0.689621E+10 | 4333.50 | 27-FEB-17:00 | -7.8 | -10.2 | 86396434.72 | 126.82 | 16-FEB-14:09 | -7.8 | -10.2 |
March | 0.136200E+11 | 7036.44 | 31-MAR-24:00 | 3.60 | 0.45 | 0.103236E+09 | 126.82 | 02-MAR-14:09 | 3.60 | 0.45 |
April | 0.186742E+11 | 8436.82 | 21-APR-18:20 | 10.53 | 2.25 | 91615144.92 | 126.82 | 19-APR-09:20 | 10.53 | 2.25 |
May | 0.441594E+10 | 3270.09 | 31-MAY-24:00 | 11.20 | 9.10 | 99235847.09 | 126.85 | 26-MAY-09:00 | 11.20 | 9.10 |
June | 0.928351E+10 | 5366.56 | 30-JUN-23:50 | 16.35 | 13.47 | 98966614.57 | 126.86 | 30-JUN-09:00 | 16.35 | 13.47 |
July | 0.147785E+11 | 7238.39 | 31-JUL-23:55 | 17.00 | 15.17 | 91888389.62 | 126.85 | 05-JUL-09:00 | 17.00 | 15.17 |
August | 0.197184E+11 | 8481.29 | 13-AUG-18:33 | 21.13 | 14.84 | 0.103244E+09 | 126.83 | 15-AUG-09:09 | 15.10 | 14.70 |
September | 0.413588E+10 | 3305.97 | 30-SEP-24:00 | 7.80 | 6.76 | 91607776.22 | 126.85 | 01-SEP-09:00 | 7.80 | 6.76 |
October | 0.896833E+10 | 4896.92 | 31-OCT-24:00 | 3.30 | -0.4 | 95230324.09 | 126.83 | 02-OCT-13:00 | 3.30 | -0.4 |
November | 0.130998E+11 | 5908.51 | 09-NOV-16:10 | 0.82 | -3.8 | 94300508.55 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.178217E+11 | 7550.69 | 20-DEC-16:00 | -20.2 | -20.8 | 91880821.08 | 126.82 | 01-DEC-10:09 | -20.2 | -20.8 |
Annual Sum or Average | 0.132767E+12 | 0.114246E+10 | ||||||||
Minimum of Months | 0.135465E+10 | 1966.45 | -20.2 | -20.8 | 86396434.72 | 126.82 | -20.2 | -20.8 | ||
Maximum of Months | 0.197184E+11 | 8481.29 | 21.13 | 15.17 | 0.103244E+09 | 126.86 | 17.00 | 15.17 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368109E+09 | 1481.14 | 27-JAN-16:30 | -15.6 | -16.5 | 86630368.84 | 126.82 | 20-JAN-14:09 | -15.6 | -16.5 |
February | 0.388965E+10 | 3647.58 | 08-FEB-17:00 | 3.30 | -1.3 | 86396460.65 | 126.82 | 16-FEB-14:09 | -13.8 | -14.7 |
March | 0.106989E+11 | 6353.95 | 31-MAR-23:20 | 3.93 | 0.64 | 0.103236E+09 | 126.82 | 02-MAR-14:09 | 3.93 | 0.64 |
April | 0.165727E+11 | 8074.38 | 21-APR-18:20 | 10.53 | 2.25 | 91609758.86 | 126.82 | 19-APR-09:20 | 10.53 | 2.25 |
May | 0.378531E+10 | 2947.48 | 31-MAY-24:00 | 11.20 | 9.10 | 99235506.43 | 126.84 | 26-MAY-09:39 | 11.20 | 9.10 |
June | 0.858482E+10 | 5217.22 | 30-JUN-23:55 | 16.10 | 13.43 | 98966289.61 | 126.86 | 30-JUN-13:00 | 16.10 | 13.43 |
July | 0.139692E+11 | 6884.51 | 31-JUL-23:55 | 17.00 | 15.17 | 91888298.03 | 126.85 | 05-JUL-13:09 | 17.00 | 15.17 |
August | 0.185900E+11 | 7992.20 | 05-AUG-18:40 | 21.13 | 13.90 | 0.103240E+09 | 126.83 | 31-AUG-09:09 | 18.40 | 17.58 |
September | 0.333149E+10 | 2913.33 | 30-SEP-23:30 | 8.65 | 7.70 | 91607108.54 | 126.84 | 01-SEP-13:09 | 8.65 | 7.70 |
October | 0.705694E+10 | 3953.21 | 18-OCT-16:50 | 15.28 | 10.42 | 95230312.14 | 126.83 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.980268E+10 | 5356.47 | 09-NOV-16:20 | 0.53 | -4.0 | 94300518.96 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.133035E+11 | 6631.21 | 20-DEC-16:10 | -20.4 | -21.0 | 91880840.21 | 126.82 | 01-DEC-10:09 | -20.4 | -21.0 |
Annual Sum or Average | 0.109953E+12 | 0.113422E+10 | ||||||||
Minimum of Months | 0.368109E+09 | 1481.14 | -20.4 | -21.0 | 86396460.65 | 126.82 | -20.4 | -21.0 | ||
Maximum of Months | 0.185900E+11 | 8074.38 | 21.13 | 15.17 | 0.103240E+09 | 126.86 | 18.40 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310995E+09 | 1185.11 | 27-JAN-16:30 | -15.6 | -16.5 | 80934557.24 | 126.82 | 19-JAN-14:00 | -15.6 | -16.5 |
February | 0.249222E+10 | 3585.95 | 08-FEB-17:00 | 3.30 | -1.3 | 86382434.59 | 126.82 | 16-FEB-14:09 | -13.8 | -14.7 |
March | 0.894696E+10 | 5872.87 | 28-MAR-17:50 | 7.20 | 2.87 | 0.103236E+09 | 126.82 | 02-MAR-14:09 | 7.20 | 2.87 |
April | 0.151829E+11 | 8054.04 | 21-APR-18:20 | 10.53 | 2.25 | 91608105.55 | 126.82 | 19-APR-09:20 | 10.53 | 2.25 |
May | 0.332680E+10 | 2699.30 | 14-MAY-18:47 | 18.17 | 8.43 | 99224241.83 | 126.84 | 25-MAY-13:00 | 27.80 | 19.36 |
June | 0.837047E+10 | 5189.21 | 30-JUN-23:40 | 16.60 | 13.50 | 98966459.43 | 126.86 | 30-JUN-13:09 | 16.60 | 13.50 |
July | 0.138560E+11 | 6791.33 | 31-JUL-23:55 | 17.00 | 15.17 | 91888510.26 | 126.85 | 05-JUL-13:09 | 17.00 | 15.17 |
August | 0.184096E+11 | 8093.45 | 05-AUG-18:40 | 21.13 | 13.90 | 0.103240E+09 | 126.83 | 31-AUG-09:09 | 18.40 | 17.58 |
September | 0.266261E+10 | 2809.08 | 03-SEP-17:50 | 20.78 | 15.57 | 91606983.39 | 126.84 | 01-SEP-13:00 | 20.78 | 15.57 |
October | 0.529364E+10 | 3922.29 | 19-OCT-16:50 | 19.78 | 12.93 | 95230308.44 | 126.83 | 02-OCT-13:00 | 19.78 | 12.93 |
November | 0.781634E+10 | 5161.00 | 09-NOV-16:20 | 0.53 | -4.0 | 94300528.35 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.116568E+11 | 6356.89 | 20-DEC-16:10 | -20.4 | -21.0 | 91880843.83 | 126.82 | 01-DEC-10:09 | -20.4 | -21.0 |
Annual Sum or Average | 0.983254E+11 | 0.112850E+10 | ||||||||
Minimum of Months | 0.310995E+09 | 1185.11 | -20.4 | -21.0 | 80934557.24 | 126.82 | -20.4 | -21.0 | ||
Maximum of Months | 0.184096E+11 | 8093.45 | 21.13 | 15.57 | 0.103240E+09 | 126.86 | 27.80 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231029E+12 | 89551.36 | 20-JAN-17:00 | -7.2 | -8.4 | 0.206144E+10 | 2745.29 | 19-JAN-14:00 | -7.2 | -8.4 |
February | 0.431520E+12 | 181791.61 | 22-FEB-17:00 | -1.1 | -3.9 | 0.187026E+10 | 2745.50 | 13-FEB-10:09 | -1.1 | -3.9 |
March | 0.725087E+12 | 358186.84 | 31-MAR-24:00 | 3.60 | 0.45 | 0.223477E+10 | 2745.47 | 20-MAR-09:09 | 3.60 | 0.45 |
April | 0.940680E+12 | 366151.00 | 19-APR-16:00 | 7.20 | 1.06 | 0.198300E+10 | 2746.12 | 13-APR-09:09 | 7.20 | 1.06 |
May | 0.239674E+12 | 175051.66 | 31-MAY-24:00 | 11.20 | 9.10 | 0.214815E+10 | 2746.96 | 23-MAY-13:09 | 11.20 | 9.10 |
June | 0.468965E+12 | 267741.51 | 30-JUN-23:55 | 16.10 | 13.43 | 0.214245E+10 | 2748.42 | 21-JUN-09:00 | 16.10 | 13.43 |
July | 0.731047E+12 | 359900.61 | 31-JUL-23:43 | 16.95 | 15.06 | 0.202225E+10 | 3375.74 | 21-JUL-13:00 | 16.95 | 15.06 |
August | 0.975312E+12 | 375649.20 | 09-AUG-23:03 | 18.95 | 17.54 | 0.239973E+10 | 4298.86 | 08-AUG-13:00 | 18.95 | 17.54 |
September | 0.234499E+12 | 175815.03 | 30-SEP-24:00 | 7.80 | 6.76 | 0.198295E+10 | 2745.81 | 12-SEP-13:39 | 7.80 | 6.76 |
October | 0.484862E+12 | 266845.82 | 31-OCT-24:00 | 3.30 | -0.4 | 0.206147E+10 | 2747.26 | 19-OCT-13:50 | 3.30 | -0.4 |
November | 0.704489E+12 | 274740.30 | 17-NOV-17:00 | 6.70 | 1.30 | 0.204137E+10 | 2748.15 | 01-NOV-13:00 | 6.70 | 1.30 |
December | 0.970148E+12 | 365524.74 | 06-DEC-17:00 | -7.0 | -7.2 | 0.198896E+10 | 2745.46 | 04-DEC-10:09 | -7.0 | -7.2 |
Annual Sum or Average | 0.713731E+13 | 0.249368E+11 | ||||||||
Minimum of Months | 0.231029E+12 | 89551.36 | -7.2 | -8.4 | 0.187026E+10 | 2745.29 | -7.2 | -8.4 | ||
Maximum of Months | 0.975312E+12 | 375649.20 | 18.95 | 17.54 | 0.239973E+10 | 4298.86 | 18.95 | 17.54 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123187E+09 | 9961.48 | 13-JAN-06:05 | -31.3 |
February | 45837224.26 | 9837.56 | 07-FEB-06:00 | -7.8 |
March | 81085938.05 | 10008.48 | 30-MAR-04:04 | -1.2 |
April | 99122408.71 | 10257.99 | 17-APR-03:05 | -0.7 |
May | 0.180298E+09 | 10274.16 | 01-MAY-03:07 | -2.1 |
June | 0.157979E+09 | 14696.49 | 24-JUN-16:01 | 28.98 |
July | 0.336301E+09 | 16721.83 | 29-JUL-16:01 | 30.50 |
August | 0.269334E+09 | 11273.00 | 26-AUG-16:01 | 26.60 |
September | 0.348850E+09 | 10235.08 | 27-SEP-04:17 | 8.30 |
October | 0.218466E+09 | 10220.77 | 20-OCT-04:17 | 7.07 |
November | 70507612.17 | 9919.54 | 13-NOV-04:04 | -8.2 |
December | 48937128.30 | 9754.97 | 30-DEC-05:03 | -5.3 |
Annual Sum or Average | 0.197991E+10 | |||
Minimum of Months | 45837224.26 | 9754.97 | -31.3 | |
Maximum of Months | 0.348850E+09 | 16721.83 | 30.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207367E+10 | 55512.40 | 02-JAN-04:01 | -18.8 |
February | 0.273494E+09 | 46091.94 | 27-FEB-05:01 | -17.4 |
March | 35917083.64 | 44880.31 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.152276E+09 | 47085.17 | 27-NOV-05:11 | -7.2 |
December | 0.965267E+09 | 51076.41 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.350062E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.207367E+10 | 55512.40 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133039E+11 | 70863.74 | 01-JAN-05:21 | -26.7 |
February | 0.673745E+10 | 69680.69 | 13-FEB-04:01 | -22.9 |
March | 0.327629E+10 | 69530.45 | 06-MAR-04:01 | -17.4 |
April | 0.773960E+09 | 63540.35 | 03-APR-04:01 | -5.4 |
May | 5059991.10 | 33733.27 | 01-MAY-05:03 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.810503E+09 | 65155.81 | 30-OCT-03:01 | -9.5 |
November | 0.426668E+10 | 69448.50 | 27-NOV-04:01 | -7.2 |
December | 0.105968E+11 | 71432.47 | 26-DEC-04:11 | -25.1 |
Annual Sum or Average | 0.397707E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.133039E+11 | 71432.47 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307731E+10 | 12780.36 | 09-JAN-04:01 | -32.4 |
February | 0.812211E+09 | 11597.63 | 13-FEB-05:01 | -23.4 |
March | 0.139308E+09 | 10853.29 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 54125998.31 | 10695.59 | 25-NOV-05:01 | -19.0 |
December | 0.945402E+09 | 11585.65 | 19-DEC-05:01 | -25.4 |
Annual Sum or Average | 0.502836E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.307731E+10 | 12780.36 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187603E+10 | 15589.46 | 09-JAN-04:01 | -32.4 |
February | 0.557250E+09 | 13951.81 | 14-FEB-05:01 | -32.1 |
March | 0.120728E+09 | 12893.54 | 06-MAR-05:01 | -18.4 |
April | 408556.27 | 2876.49 | 04-APR-05:01 | -9.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 79900851.40 | 12820.98 | 25-NOV-05:01 | -19.0 |
December | 0.896797E+09 | 14385.00 | 20-DEC-04:01 | -28.5 |
Annual Sum or Average | 0.353111E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.187603E+10 | 15589.46 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236687E+10 | 22208.51 | 09-JAN-04:01 | -32.4 |
February | 0.852826E+09 | 20879.32 | 13-FEB-04:01 | -22.9 |
March | 0.247930E+09 | 19812.79 | 06-MAR-05:01 | -18.4 |
April | 5496992.32 | 16028.33 | 04-APR-05:01 | -9.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 13402184.25 | 15369.25 | 30-OCT-05:03 | -9.9 |
November | 0.196059E+09 | 19438.56 | 24-NOV-05:01 | -10.6 |
December | 0.119068E+10 | 21401.23 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.487327E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.236687E+10 | 22208.51 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.719989E+09 | 13542.84 | 09-JAN-04:01 | -32.4 |
February | 65693299.89 | 11349.09 | 13-FEB-05:01 | -23.4 |
March | 370472.73 | 6174.55 | 06-MAR-06:01 | -19.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 172031.84 | 2293.76 | 25-NOV-06:01 | -19.4 |
December | 10317186.67 | 10545.38 | 20-DEC-06:01 | -28.9 |
Annual Sum or Average | 0.796542E+09 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.719989E+09 | 13542.84 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120507E+11 | 13264.92 | 08-JAN-21:42 | -28.9 |
February | 0.662937E+10 | 13157.80 | 13-FEB-04:21 | -23.1 |
March | 0.322480E+10 | 12605.79 | 06-MAR-04:01 | -17.4 |
April | 0.422606E+09 | 11267.70 | 03-APR-03:01 | -7.4 |
May | 1066310.45 | 7065.39 | 01-MAY-05:03 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.236856E+09 | 10999.56 | 30-OCT-04:01 | -10.0 |
November | 0.277162E+10 | 12322.87 | 26-NOV-23:52 | -6.7 |
December | 0.106995E+11 | 13180.67 | 18-DEC-04:11 | -14.3 |
Annual Sum or Average | 0.360365E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.120507E+11 | 13264.92 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692684E+10 | 20988.28 | 08-JAN-21:42 | -28.9 |
February | 0.332657E+10 | 20846.58 | 12-FEB-23:01 | -17.4 |
March | 0.149747E+10 | 20246.76 | 06-MAR-04:01 | -17.4 |
April | 0.175362E+09 | 17970.31 | 04-APR-04:01 | -7.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.140991E+09 | 17606.56 | 30-OCT-04:01 | -10.0 |
November | 0.163176E+10 | 19642.74 | 25-NOV-04:01 | -18.0 |
December | 0.630460E+10 | 21240.49 | 18-DEC-04:11 | -14.3 |
Annual Sum or Average | 0.200036E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.692684E+10 | 21240.49 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709495E+10 | 25093.47 | 09-JAN-01:02 | -30.4 |
February | 0.329237E+10 | 24720.15 | 13-FEB-04:21 | -23.1 |
March | 0.160376E+10 | 23985.60 | 06-MAR-04:01 | -17.4 |
April | 0.238391E+09 | 21391.93 | 04-APR-04:01 | -7.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.141626E+09 | 20942.94 | 30-OCT-04:01 | -10.0 |
November | 0.175710E+10 | 23557.52 | 25-NOV-04:01 | -18.0 |
December | 0.669525E+10 | 25379.66 | 18-DEC-04:11 | -14.3 |
Annual Sum or Average | 0.208234E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.4 | |
Maximum of Months | 0.709495E+10 | 25379.66 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625325E+10 | 21146.95 | 01-JAN-08:61 | -26.7 |
February | 0.275487E+10 | 20804.87 | 13-FEB-04:21 | -23.1 |
March | 0.109911E+10 | 20236.21 | 06-MAR-04:01 | -17.4 |
April | 0.116593E+09 | 17570.91 | 04-APR-04:01 | -7.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 77683317.80 | 17212.22 | 30-OCT-04:01 | -10.0 |
November | 0.112586E+10 | 19741.82 | 27-NOV-04:01 | -7.2 |
December | 0.510840E+10 | 21217.55 | 18-DEC-04:11 | -14.3 |
Annual Sum or Average | 0.165358E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.625325E+10 | 21217.55 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181099E+11 | 17511.63 | 09-JAN-06:01 | -31.8 |
February | 0.118705E+11 | 18019.38 | 13-FEB-04:21 | -23.1 |
March | 0.720862E+10 | 16893.03 | 06-MAR-05:21 | -18.6 |
April | 0.188453E+10 | 15879.88 | 02-APR-07:43 | -5.7 |
May | 68315297.68 | 13889.26 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 30113.81 | 200.76 | 19-AUG-05:08 | 4.60 |
September | 49567050.21 | 12765.48 | 28-SEP-05:02 | 6.70 |
October | 0.163186E+10 | 15770.32 | 10-OCT-04:11 | 2.57 |
November | 0.703477E+10 | 16755.47 | 23-NOV-21:42 | -10.5 |
December | 0.169346E+11 | 17599.17 | 26-DEC-04:11 | -25.1 |
Annual Sum or Average | 0.647927E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.8 | |
Maximum of Months | 0.181099E+11 | 18019.38 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110081E+11 | 22044.65 | 07-JAN-02:42 | -25.0 |
February | 0.648230E+10 | 22610.18 | 13-FEB-04:21 | -23.1 |
March | 0.356118E+10 | 21459.12 | 06-MAR-04:01 | -17.4 |
April | 0.844306E+09 | 20143.56 | 10-APR-03:11 | -2.1 |
May | 20586972.71 | 17217.07 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 28206706.28 | 16311.04 | 28-SEP-05:02 | 6.70 |
October | 0.925129E+09 | 19981.66 | 16-OCT-04:11 | 4.80 |
November | 0.419620E+10 | 21312.67 | 23-NOV-21:42 | -10.5 |
December | 0.105855E+11 | 22740.99 | 26-DEC-04:11 | -25.1 |
Annual Sum or Average | 0.376515E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.1 | |
Maximum of Months | 0.110081E+11 | 22740.99 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122156E+11 | 27272.23 | 08-JAN-04:42 | -21.7 |
February | 0.709436E+10 | 27938.88 | 13-FEB-04:21 | -23.1 |
March | 0.430505E+10 | 26564.14 | 05-MAR-04:02 | -28.3 |
April | 0.127265E+10 | 25029.56 | 10-APR-03:11 | -2.1 |
May | 52549523.38 | 21188.88 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 31622544.39 | 20110.11 | 28-SEP-05:02 | 6.70 |
October | 0.112329E+10 | 24656.32 | 30-OCT-03:01 | -9.5 |
November | 0.490780E+10 | 26465.66 | 23-NOV-21:42 | -10.5 |
December | 0.121595E+11 | 28115.49 | 26-DEC-04:11 | -25.1 |
Annual Sum or Average | 0.431624E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.122156E+11 | 28115.49 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100461E+11 | 24066.99 | 09-JAN-04:01 | -32.4 |
February | 0.535782E+10 | 24506.42 | 13-FEB-04:21 | -23.1 |
March | 0.275395E+10 | 23328.11 | 06-MAR-04:01 | -17.4 |
April | 0.601277E+09 | 21636.67 | 10-APR-03:11 | -2.1 |
May | 16202421.49 | 10746.78 | 09-MAY-05:02 | 4.83 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 6406292.27 | 9864.02 | 28-SEP-05:02 | 6.70 |
October | 0.571064E+09 | 21702.82 | 30-OCT-03:01 | -9.5 |
November | 0.296349E+10 | 22891.76 | 25-NOV-04:11 | -18.2 |
December | 0.852961E+10 | 24544.03 | 26-DEC-04:11 | -25.1 |
Annual Sum or Average | 0.308459E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.100461E+11 | 24544.03 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329485E+10 | 7287.90 | 02-JAN-12:00 | -13.3 |
February | 0.164706E+10 | 10715.43 | 21-FEB-06:03 | 2.80 |
March | 0.765207E+09 | 15346.60 | 26-MAR-15:22 | 10.85 |
April | 0.179026E+09 | 13293.06 | 23-APR-16:01 | 26.60 |
May | 98987783.41 | 9733.14 | 21-MAY-15:02 | 22.73 |
June | 94578979.62 | 9457.29 | 25-JUN-10:52 | 27.80 |
July | 0.131990E+09 | 13420.27 | 23-JUL-16:01 | 29.72 |
August | 0.153650E+09 | 12317.35 | 20-AUG-15:01 | 25.40 |
September | 88926515.39 | 10706.44 | 03-SEP-15:32 | 21.70 |
October | 0.104165E+09 | 9637.55 | 22-OCT-14:32 | 19.40 |
November | 0.411772E+09 | 10991.21 | 13-NOV-05:01 | -7.9 |
December | 0.205440E+10 | 11659.98 | 06-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.902462E+10 | |||
Minimum of Months | 88926515.39 | 7287.90 | -13.3 | |
Maximum of Months | 0.329485E+10 | 15346.60 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.733032E+10 | 20387.18 | 02-JAN-06:12 | -17.8 |
February | 0.427389E+10 | 9617.24 | 27-FEB-15:00 | -7.8 |
March | 0.299849E+10 | 18247.42 | 26-MAR-16:31 | 10.37 |
April | 0.912367E+09 | 13813.16 | 23-APR-15:42 | 26.52 |
May | 0.114508E+09 | 13479.42 | 21-MAY-15:31 | 22.53 |
June | 70078074.31 | 12468.79 | 25-JUN-10:41 | 27.62 |
July | 80063562.65 | 13635.32 | 23-JUL-16:01 | 29.72 |
August | 85168278.93 | 14124.91 | 20-AUG-14:31 | 25.40 |
September | 82492491.08 | 11544.72 | 03-SEP-15:11 | 21.70 |
October | 0.668417E+09 | 10297.85 | 09-OCT-13:32 | 5.93 |
November | 0.256305E+10 | 9668.47 | 27-NOV-06:12 | -7.0 |
December | 0.560069E+10 | 15173.53 | 26-DEC-06:23 | -26.6 |
Annual Sum or Average | 0.247795E+11 | |||
Minimum of Months | 70078074.31 | 9617.24 | -26.6 | |
Maximum of Months | 0.733032E+10 | 20387.18 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205386E+11 | 33224.43 | 06-JAN-06:12 | -34.6 |
February | 0.136243E+11 | 31499.11 | 13-FEB-05:10 | -23.4 |
March | 0.912791E+10 | 27707.51 | 06-MAR-05:09 | -18.4 |
April | 0.324071E+10 | 21944.57 | 03-APR-04:12 | -5.2 |
May | 0.659246E+09 | 12389.38 | 30-MAY-05:02 | 10.60 |
June | 0.206027E+09 | 12871.39 | 02-JUN-05:02 | 7.07 |
July | 0.144595E+09 | 12189.77 | 18-JUL-05:03 | 8.27 |
August | 0.229546E+09 | 11290.06 | 25-AUG-05:03 | 7.88 |
September | 0.870389E+09 | 10666.35 | 12-SEP-05:02 | 10.50 |
October | 0.333292E+10 | 24019.66 | 30-OCT-04:23 | -10.0 |
November | 0.909270E+10 | 26214.54 | 24-NOV-05:12 | -10.6 |
December | 0.187384E+11 | 31086.10 | 11-DEC-05:11 | -24.5 |
Annual Sum or Average | 0.798053E+11 | |||
Minimum of Months | 0.144595E+09 | 10666.35 | -34.6 | |
Maximum of Months | 0.205386E+11 | 33224.43 | 10.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93309159.11 | 575.86 | 01-JAN-05:10 | -26.7 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 93309159.11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 93309159.11 | 575.86 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.745901E+09 | 611.04 | 01-JAN-17:05 | -19.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.745901E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.745901E+09 | 611.04 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.780166E+09 | 623.97 | 01-JAN-17:05 | -19.1 |
February | 0.159140E+09 | 569.88 | 12-FEB-23:14 | -17.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 5183436.29 | 434.58 | 01-MAY-05:20 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 4748024.55 | 388.79 | 29-OCT-21:25 | -5.8 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.949238E+09 | |||
Minimum of Months | 0.00 | 0.00 | -19.1 | |
Maximum of Months | 0.780166E+09 | 623.97 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.736061E+09 | 1147.25 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.601730E+09 | 982.32 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.671515E+09 | 888.47 | 03-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571786E+09 | 619.02 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.593890E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.585027E+09 | 611.95 | 30-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.552111E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.630998E+09 | 773.48 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.584687E+09 | 794.02 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.650421E+09 | 1131.56 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.712899E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.733096E+09 | 1147.25 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.762422E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.552111E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.736061E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463248E+09 | 739.33 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.384270E+09 | 647.49 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.430080E+09 | 583.12 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.368611E+09 | 376.20 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.385122E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.379638E+09 | 382.56 | 30-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.358225E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.407210E+09 | 413.00 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.376034E+09 | 411.58 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.413902E+09 | 725.95 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.452238E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.462317E+09 | 739.33 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.488090E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.358225E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.463248E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.703260E+09 | 1147.28 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.588409E+09 | 931.01 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.665849E+09 | 867.08 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.572711E+09 | 615.70 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.597488E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.588903E+09 | 614.22 | 30-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.555706E+09 | 545.88 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.632729E+09 | 761.80 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.583493E+09 | 777.44 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.637870E+09 | 1127.84 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.688186E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.703570E+09 | 1147.28 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.751817E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.555706E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.703570E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463144E+09 | 739.33 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.382083E+09 | 577.71 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.430171E+09 | 586.81 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367777E+09 | 408.29 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.382922E+09 | 351.77 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.376953E+09 | 400.13 | 30-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.355611E+09 | 373.81 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.406810E+09 | 512.19 | 31-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.376370E+09 | 532.02 | 19-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.416327E+09 | 729.58 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.449449E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.461789E+09 | 739.33 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.486941E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.355611E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.463144E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.734395E+09 | 1147.25 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.600463E+09 | 980.29 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670356E+09 | 885.60 | 03-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571361E+09 | 614.13 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.593734E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.584657E+09 | 606.61 | 30-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.551964E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.630452E+09 | 769.37 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.584122E+09 | 789.96 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.648897E+09 | 1131.37 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.711025E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.731132E+09 | 1147.25 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.761256E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.551964E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.734395E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462532E+09 | 739.33 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.383840E+09 | 645.15 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.429613E+09 | 579.06 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.368406E+09 | 372.61 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.384928E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.379388E+09 | 378.87 | 30-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.358056E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.406869E+09 | 410.88 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375741E+09 | 409.48 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.413208E+09 | 725.66 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.451434E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.461572E+09 | 739.33 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.487559E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.358056E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.462532E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.702880E+09 | 1147.28 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.587637E+09 | 928.97 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.665208E+09 | 864.13 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.572310E+09 | 610.65 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.597180E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.588540E+09 | 608.99 | 30-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.555454E+09 | 545.88 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.632240E+09 | 757.61 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.583043E+09 | 773.26 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.637322E+09 | 1127.64 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.687649E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.702974E+09 | 1147.28 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.751244E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.555454E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.702974E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462535E+09 | 739.33 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381668E+09 | 573.59 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429599E+09 | 582.83 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367527E+09 | 405.73 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.382776E+09 | 351.77 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.376790E+09 | 397.11 | 30-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.355484E+09 | 351.77 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.406429E+09 | 506.28 | 31-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.376031E+09 | 526.61 | 19-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.415596E+09 | 729.33 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.448787E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.461138E+09 | 739.33 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.486436E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.355484E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.462535E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.734356E+09 | 1147.25 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.600381E+09 | 979.99 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670242E+09 | 885.07 | 03-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571349E+09 | 613.93 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.593730E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.584644E+09 | 606.39 | 30-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.551957E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.630432E+09 | 768.59 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.584101E+09 | 789.25 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.648830E+09 | 1131.33 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.710948E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.731002E+09 | 1147.25 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.761197E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.551957E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.734356E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462515E+09 | 739.33 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.383831E+09 | 644.98 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.429598E+09 | 578.74 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.368389E+09 | 372.42 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.384923E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.379381E+09 | 378.70 | 30-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.358039E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.406857E+09 | 410.79 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375731E+09 | 409.38 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.413192E+09 | 725.64 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.451409E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.461500E+09 | 739.33 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.487536E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.358039E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.462515E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.702865E+09 | 1147.28 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.587625E+09 | 928.60 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.665185E+09 | 863.57 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.572295E+09 | 610.45 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.597161E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.588528E+09 | 608.78 | 30-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.555438E+09 | 545.88 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.632219E+09 | 756.81 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.583026E+09 | 772.52 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.637299E+09 | 1127.61 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.687624E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.702930E+09 | 1147.28 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.751219E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.555438E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.702930E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462519E+09 | 739.33 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381656E+09 | 573.29 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429582E+09 | 582.52 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367520E+09 | 405.63 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.382772E+09 | 351.77 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.376781E+09 | 396.99 | 30-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.355472E+09 | 351.77 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.406400E+09 | 505.81 | 31-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.376012E+09 | 526.18 | 19-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.415566E+09 | 729.31 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.448762E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.461103E+09 | 739.33 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.486414E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.355472E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.462519E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.736061E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165388E+10 |
February | 0.136985E+10 | 0.601730E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147350E+10 |
March | 0.163685E+10 | 0.671515E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102158E+10 |
April | 0.145243E+10 | 0.571786E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 280596.72 | 0.984204E+09 |
May | 0.157338E+10 | 0.593890E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2792336.31 | 0.458704E+09 |
June | 0.156900E+10 | 0.585027E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11190389.72 | 0.248885E+09 |
July | 0.145680E+10 | 0.552111E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12744939.04 | 0.172620E+09 |
August | 0.163685E+10 | 0.630998E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4272683.00 | 0.246993E+09 |
September | 0.145243E+10 | 0.584687E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140600.51 | 0.441145E+09 |
October | 0.150991E+10 | 0.650421E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692866E+09 |
November | 0.149516E+10 | 0.712899E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121456E+10 |
December | 0.145680E+10 | 0.733096E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180131E+10 |
Annual Sum or Average | 0.181194E+11 | 0.762422E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31421545.30 | 0.104102E+11 |
Minimum of Months | 0.136985E+10 | 0.552111E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172620E+09 |
Maximum of Months | 0.163685E+10 | 0.736061E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12744939.04 | 0.180131E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.463248E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110115E+10 |
February | 0.882782E+09 | 0.384270E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985672E+09 |
March | 0.105485E+10 | 0.430080E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682999E+09 |
April | 0.936002E+09 | 0.368611E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167644.43 | 0.654051E+09 |
May | 0.101394E+10 | 0.385122E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1861531.14 | 0.310950E+09 |
June | 0.101113E+10 | 0.379638E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7658890.04 | 0.166177E+09 |
July | 0.938820E+09 | 0.358225E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8516537.93 | 0.112762E+09 |
August | 0.105485E+10 | 0.407210E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2847506.66 | 0.164556E+09 |
September | 0.936002E+09 | 0.376034E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93730.20 | 0.297236E+09 |
October | 0.973041E+09 | 0.413902E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460075E+09 |
November | 0.963541E+09 | 0.452238E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800181E+09 |
December | 0.938820E+09 | 0.462317E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118931E+10 |
Annual Sum or Average | 0.116768E+11 | 0.488090E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21145840.40 | 0.692512E+10 |
Minimum of Months | 0.882782E+09 | 0.358225E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112762E+09 |
Maximum of Months | 0.105485E+10 | 0.463248E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8516537.93 | 0.118931E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.703260E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166183E+10 |
February | 0.136988E+10 | 0.588409E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149498E+10 |
March | 0.163688E+10 | 0.665849E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103291E+10 |
April | 0.145246E+10 | 0.572711E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3625.40 | 0.985462E+09 |
May | 0.157341E+10 | 0.597488E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2791296.16 | 0.462108E+09 |
June | 0.156904E+10 | 0.588903E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10980182.30 | 0.248121E+09 |
July | 0.145684E+10 | 0.555706E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12272284.55 | 0.174563E+09 |
August | 0.163688E+10 | 0.632729E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4237788.38 | 0.255840E+09 |
September | 0.145246E+10 | 0.583493E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130206.72 | 0.453093E+09 |
October | 0.150994E+10 | 0.637870E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690398E+09 |
November | 0.149520E+10 | 0.688186E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119901E+10 |
December | 0.145684E+10 | 0.703570E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179999E+10 |
Annual Sum or Average | 0.181198E+11 | 0.751817E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30415383.50 | 0.104583E+11 |
Minimum of Months | 0.136988E+10 | 0.555706E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174563E+09 |
Maximum of Months | 0.163688E+10 | 0.703570E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12272284.55 | 0.179999E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.463144E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113743E+10 |
February | 0.882782E+09 | 0.382083E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103999E+10 |
March | 0.105485E+10 | 0.430171E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734481E+09 |
April | 0.936002E+09 | 0.367777E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723490E+09 |
May | 0.101394E+10 | 0.382922E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1861512.25 | 0.331428E+09 |
June | 0.101113E+10 | 0.376953E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6542510.27 | 0.187274E+09 |
July | 0.938820E+09 | 0.355611E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7790843.55 | 0.137179E+09 |
August | 0.105485E+10 | 0.406810E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2819785.00 | 0.195814E+09 |
September | 0.936002E+09 | 0.376370E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93721.50 | 0.319170E+09 |
October | 0.973041E+09 | 0.416327E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498296E+09 |
November | 0.963541E+09 | 0.449449E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871035E+09 |
December | 0.938820E+09 | 0.461789E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128492E+10 |
Annual Sum or Average | 0.116768E+11 | 0.486941E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19108372.58 | 0.746050E+10 |
Minimum of Months | 0.882782E+09 | 0.355611E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137179E+09 |
Maximum of Months | 0.105485E+10 | 0.463144E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7790843.55 | 0.128492E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.734395E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364651E+10 |
February | 0.136985E+10 | 0.600463E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312760E+10 |
March | 0.163685E+10 | 0.670356E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217577E+10 |
April | 0.145243E+10 | 0.571361E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3273918.58 | 0.202631E+10 |
May | 0.157338E+10 | 0.593734E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6205182.11 | 0.101523E+10 |
June | 0.156900E+10 | 0.584657E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24257078.12 | 0.556074E+09 |
July | 0.145680E+10 | 0.551964E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28796808.28 | 0.404086E+09 |
August | 0.163685E+10 | 0.630452E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9643887.85 | 0.551468E+09 |
September | 0.145243E+10 | 0.584122E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 300638.43 | 0.949140E+09 |
October | 0.150991E+10 | 0.648897E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141831E+10 |
November | 0.149516E+10 | 0.711025E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248407E+10 |
December | 0.145680E+10 | 0.731132E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388380E+10 |
Annual Sum or Average | 0.181194E+11 | 0.761256E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72477513.37 | 0.222384E+11 |
Minimum of Months | 0.136985E+10 | 0.551964E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404086E+09 |
Maximum of Months | 0.163685E+10 | 0.734395E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28796808.28 | 0.388380E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.462532E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243561E+10 |
February | 0.649041E+09 | 0.383840E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210720E+10 |
March | 0.773965E+09 | 0.429613E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149017E+10 |
April | 0.688021E+09 | 0.368406E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 722874.97 | 0.141697E+10 |
May | 0.744847E+09 | 0.384928E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3890779.52 | 0.711408E+09 |
June | 0.742030E+09 | 0.379388E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576197.17 | 0.387122E+09 |
July | 0.690839E+09 | 0.358056E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17851647.78 | 0.279702E+09 |
August | 0.773965E+09 | 0.406869E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6018047.91 | 0.397052E+09 |
September | 0.688021E+09 | 0.375741E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180937.56 | 0.665509E+09 |
October | 0.715730E+09 | 0.413208E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977417E+09 |
November | 0.708685E+09 | 0.451434E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167172E+10 |
December | 0.690839E+09 | 0.461572E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259074E+10 |
Annual Sum or Average | 0.858171E+10 | 0.487559E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44240484.92 | 0.151306E+11 |
Minimum of Months | 0.649041E+09 | 0.358056E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279702E+09 |
Maximum of Months | 0.773965E+09 | 0.462532E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17851647.78 | 0.259074E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.702880E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372074E+10 |
February | 0.136988E+10 | 0.587637E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330709E+10 |
March | 0.163688E+10 | 0.665208E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231328E+10 |
April | 0.145246E+10 | 0.572310E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217324E+10 |
May | 0.157341E+10 | 0.597180E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6201027.79 | 0.105422E+10 |
June | 0.156904E+10 | 0.588540E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23560928.51 | 0.566718E+09 |
July | 0.145684E+10 | 0.555454E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27153999.47 | 0.418179E+09 |
August | 0.163688E+10 | 0.632240E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9468951.55 | 0.599633E+09 |
September | 0.145246E+10 | 0.583043E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 247965.10 | 0.103015E+10 |
October | 0.150994E+10 | 0.637322E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152760E+10 |
November | 0.149520E+10 | 0.687649E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259769E+10 |
December | 0.145684E+10 | 0.702974E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396173E+10 |
Annual Sum or Average | 0.181198E+11 | 0.751244E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66632872.42 | 0.232703E+11 |
Minimum of Months | 0.136988E+10 | 0.555454E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418179E+09 |
Maximum of Months | 0.163688E+10 | 0.702974E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27153999.47 | 0.396173E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.462535E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245773E+10 |
February | 0.882782E+09 | 0.381668E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214945E+10 |
March | 0.105485E+10 | 0.429599E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152205E+10 |
April | 0.936002E+09 | 0.367527E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144899E+10 |
May | 0.101394E+10 | 0.382776E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4136727.33 | 0.728747E+09 |
June | 0.101113E+10 | 0.376790E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14899478.37 | 0.400235E+09 |
July | 0.938820E+09 | 0.355484E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17768023.61 | 0.302338E+09 |
August | 0.105485E+10 | 0.406429E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6305563.62 | 0.414623E+09 |
September | 0.936002E+09 | 0.376031E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 200405.96 | 0.683159E+09 |
October | 0.973041E+09 | 0.415596E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100046E+10 |
November | 0.963541E+09 | 0.448787E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170095E+10 |
December | 0.938820E+09 | 0.461138E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262185E+10 |
Annual Sum or Average | 0.116768E+11 | 0.486436E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43310198.89 | 0.154306E+11 |
Minimum of Months | 0.882782E+09 | 0.355484E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302338E+09 |
Maximum of Months | 0.105485E+10 | 0.462535E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17768023.61 | 0.262185E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.734356E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450143E+10 |
February | 0.136985E+10 | 0.600381E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383587E+10 |
March | 0.163685E+10 | 0.670242E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260832E+10 |
April | 0.145243E+10 | 0.571349E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4996310.73 | 0.232273E+10 |
May | 0.157338E+10 | 0.593730E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7290511.60 | 0.119681E+10 |
June | 0.156900E+10 | 0.584644E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29100577.85 | 0.665578E+09 |
July | 0.145680E+10 | 0.551957E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34372180.94 | 0.488624E+09 |
August | 0.163685E+10 | 0.630432E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11537669.27 | 0.662308E+09 |
September | 0.145243E+10 | 0.584101E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339665.55 | 0.109571E+10 |
October | 0.150991E+10 | 0.648830E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159355E+10 |
November | 0.149516E+10 | 0.710948E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295660E+10 |
December | 0.145680E+10 | 0.731002E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478070E+10 |
Annual Sum or Average | 0.181194E+11 | 0.761197E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87636915.94 | 0.267082E+11 |
Minimum of Months | 0.136985E+10 | 0.551957E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488624E+09 |
Maximum of Months | 0.163685E+10 | 0.734356E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34372180.94 | 0.478070E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.462515E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302057E+10 |
February | 0.882782E+09 | 0.383831E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257582E+10 |
March | 0.105485E+10 | 0.429598E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177907E+10 |
April | 0.936002E+09 | 0.368389E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1030412.52 | 0.163225E+10 |
May | 0.101394E+10 | 0.384923E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4859980.12 | 0.850834E+09 |
June | 0.101113E+10 | 0.379381E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19017505.98 | 0.466113E+09 |
July | 0.938820E+09 | 0.358039E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21919678.74 | 0.339913E+09 |
August | 0.105485E+10 | 0.406857E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7498600.51 | 0.482823E+09 |
September | 0.936002E+09 | 0.375731E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226426.85 | 0.779756E+09 |
October | 0.973041E+09 | 0.413192E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109939E+10 |
November | 0.963541E+09 | 0.451409E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198309E+10 |
December | 0.938820E+09 | 0.461500E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320471E+10 |
Annual Sum or Average | 0.116768E+11 | 0.487536E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54552604.72 | 0.182143E+11 |
Minimum of Months | 0.882782E+09 | 0.358039E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339913E+09 |
Maximum of Months | 0.105485E+10 | 0.462515E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21919678.74 | 0.320471E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.702865E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456841E+10 |
February | 0.136988E+10 | 0.587625E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398654E+10 |
March | 0.163688E+10 | 0.665185E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276414E+10 |
April | 0.145246E+10 | 0.572295E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251016E+10 |
May | 0.157341E+10 | 0.597161E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7286088.17 | 0.125804E+10 |
June | 0.156904E+10 | 0.588528E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28008740.55 | 0.683015E+09 |
July | 0.145684E+10 | 0.555438E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31996497.66 | 0.508889E+09 |
August | 0.163688E+10 | 0.632219E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11186262.67 | 0.729674E+09 |
September | 0.145246E+10 | 0.583026E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295936.85 | 0.121881E+10 |
October | 0.150994E+10 | 0.637299E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173508E+10 |
November | 0.149520E+10 | 0.687624E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305018E+10 |
December | 0.145684E+10 | 0.702930E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484557E+10 |
Annual Sum or Average | 0.181198E+11 | 0.751219E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78773525.91 | 0.278585E+11 |
Minimum of Months | 0.136988E+10 | 0.555438E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508889E+09 |
Maximum of Months | 0.163688E+10 | 0.702930E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31996497.66 | 0.484557E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.462519E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303005E+10 |
February | 0.882782E+09 | 0.381656E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261492E+10 |
March | 0.105485E+10 | 0.429582E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182556E+10 |
April | 0.936002E+09 | 0.367520E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168374E+10 |
May | 0.101394E+10 | 0.382772E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4860270.03 | 0.874664E+09 |
June | 0.101113E+10 | 0.376781E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17960862.93 | 0.484975E+09 |
July | 0.938820E+09 | 0.355472E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21064841.88 | 0.369662E+09 |
August | 0.105485E+10 | 0.406400E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7452670.28 | 0.505201E+09 |
September | 0.936002E+09 | 0.376012E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226397.05 | 0.808490E+09 |
October | 0.973041E+09 | 0.415566E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114805E+10 |
November | 0.963541E+09 | 0.448762E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201747E+10 |
December | 0.938820E+09 | 0.461103E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322150E+10 |
Annual Sum or Average | 0.116768E+11 | 0.486414E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51565042.17 | 0.185843E+11 |
Minimum of Months | 0.882782E+09 | 0.355472E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369662E+09 |
Maximum of Months | 0.105485E+10 | 0.462519E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21064841.88 | 0.322150E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349466E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314324E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216865E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567253.10 | 0.207081E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3984030.45 | 0.953865E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19994676.65 | 0.515453E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22766576.72 | 0.364657E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6139736.69 | 0.527160E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147377.19 | 0.929269E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145972E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258474E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384024E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53599650.79 | 0.220525E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364657E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22766576.72 | 0.384024E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586429E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521464E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365161E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3198744.54 | 0.350805E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7124592.22 | 0.167596E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36233420.00 | 0.903289E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41308073.56 | 0.648317E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10944265.34 | 0.921070E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241094.10 | 0.161893E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246444E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426478E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633430E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99050189.76 | 0.370697E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648317E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41308073.56 | 0.633430E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649566E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564016E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395209E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264563.27 | 0.369673E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4946289.69 | 0.188481E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32195172.08 | 0.103907E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29876506.99 | 0.760027E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8355703.31 | 0.106728E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62066.77 | 0.177453E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251605E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443481E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692576E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75700302.11 | 0.401870E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760027E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32195172.08 | 0.692576E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2909.25 | 04-JAN-05:52 |
February | 2010.79 | 01-FEB-10:09 | 982.32 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3627.95 | 12-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 888.47 | 03-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1786.11 | 15-MAR-04:51 |
April | 2010.79 | 03-APR-09:09 | 619.02 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.86 | 23-APR-15:51 | 1574.94 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 24-MAY-15:00 | 777.12 | 08-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 611.95 | 30-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.77 | 29-JUN-21:02 | 537.37 | 10-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.21 | 23-JUL-14:45 | 495.09 | 09-JUL-10:00 |
August | 2010.79 | 01-AUG-09:09 | 773.48 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.02 | 08-AUG-16:00 | 698.00 | 27-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 794.02 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 01-SEP-15:00 | 922.81 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 1131.56 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1194.53 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2204.89 | 22-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2896.49 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.09 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 187.21 | 3627.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1938.50 | 04-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 647.49 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2391.86 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 583.12 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1190.73 | 15-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 376.20 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.28 | 23-APR-15:51 | 1027.40 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 24-MAY-15:00 | 556.14 | 14-MAY-08:00 |
June | 1295.83 | 01-JUN-09:09 | 382.56 | 30-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 | 29-JUN-21:02 | 345.31 | 20-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.56 | 23-JUL-14:44 | 325.73 | 09-JUL-08:00 |
August | 1295.83 | 01-AUG-09:09 | 413.00 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 08-AUG-16:00 | 452.58 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 411.58 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 606.68 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 725.95 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 784.70 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1433.60 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1930.99 | 16-DEC-05:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.73 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 135.56 | 2391.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2906.98 | 04-JAN-05:52 |
February | 2010.83 | 01-FEB-10:09 | 931.01 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3508.69 | 12-FEB-22:51 |
March | 2010.83 | 01-MAR-10:09 | 867.08 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1786.12 | 15-MAR-04:51 |
April | 2010.83 | 03-APR-09:09 | 615.70 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 23-APR-16:04 | 1658.48 | 16-APR-11:50 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 24-MAY-15:00 | 766.70 | 08-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 614.22 | 30-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.91 | 29-JUN-21:02 | 525.94 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 545.88 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.05 | 23-JUL-14:44 | 497.55 | 06-JUL-21:55 |
August | 2010.83 | 01-AUG-09:09 | 761.80 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.02 | 08-AUG-16:00 | 708.56 | 27-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 777.44 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 01-SEP-15:00 | 909.50 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 1127.84 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1166.40 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2116.50 | 22-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2896.48 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.55 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 195.05 | 3508.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1943.17 | 04-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 577.71 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2527.12 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 586.81 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1243.46 | 17-MAR-03:52 |
April | 1295.83 | 03-APR-09:09 | 408.29 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1156.99 | 09-APR-13:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 24-MAY-15:00 | 541.80 | 08-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 400.13 | 30-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.74 | 29-JUN-16:00 | 411.85 | 10-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 373.81 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.06 | 23-JUL-14:44 | 407.73 | 06-JUL-21:55 |
August | 1295.83 | 01-AUG-09:09 | 512.19 | 31-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 08-AUG-16:00 | 563.49 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 532.02 | 19-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 647.59 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 729.58 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 843.23 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1576.57 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1978.74 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.73 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 127.06 | 2527.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6406.49 | 04-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 980.29 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7769.10 | 12-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 885.60 | 03-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4074.33 | 15-MAR-04:51 |
April | 2010.79 | 03-APR-09:09 | 614.13 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.78 | 23-APR-16:00 | 3188.53 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 24-MAY-15:00 | 1682.44 | 08-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 606.61 | 30-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.59 | 29-JUN-21:02 | 1132.69 | 20-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.04 | 23-JUL-14:45 | 1111.47 | 06-JUL-21:55 |
August | 2010.79 | 01-AUG-09:09 | 769.37 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.57 | 08-AUG-16:00 | 1491.84 | 27-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 789.96 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 01-SEP-15:00 | 1962.68 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 1131.37 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2672.12 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4281.28 | 22-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6408.15 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.47 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 428.04 | 7769.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 739.33 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4594.96 | 04-JAN-06:00 |
February | 1239.33 | 01-FEB-08:09 | 645.15 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5178.24 | 12-FEB-22:51 |
March | 1239.33 | 01-MAR-08:09 | 579.06 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2769.97 | 15-MAR-04:51 |
April | 1239.33 | 03-APR-07:10 | 372.61 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.45 | 23-APR-16:00 | 2339.35 | 16-APR-11:53 |
May | 1239.33 | 01-MAY-07:10 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.37 | 24-MAY-15:00 | 1279.62 | 14-MAY-07:50 |
June | 1239.33 | 01-JUN-07:10 | 378.87 | 30-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.65 | 29-JUN-21:02 | 790.21 | 18-JUN-07:10 |
July | 1239.33 | 03-JUL-07:10 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.81 | 23-JUL-14:44 | 742.71 | 06-JUL-21:55 |
August | 1239.33 | 01-AUG-07:10 | 410.88 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.05 | 08-AUG-16:00 | 1022.15 | 27-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 409.48 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 01-SEP-15:00 | 1307.08 | 20-SEP-01:00 |
October | 1239.33 | 02-OCT-07:10 | 725.66 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1780.96 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2834.31 | 22-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4480.12 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.71 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 285.81 | 5178.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6892.55 | 04-JAN-05:58 |
February | 2010.83 | 01-FEB-10:09 | 928.97 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7781.51 | 12-FEB-22:51 |
March | 2010.83 | 01-MAR-10:09 | 864.13 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4162.44 | 15-MAR-04:51 |
April | 2010.83 | 03-APR-09:09 | 610.65 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3889.21 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 24-MAY-15:00 | 1712.43 | 29-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 608.99 | 30-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.66 | 29-JUN-21:02 | 1131.86 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 545.88 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.08 | 23-JUL-14:44 | 1132.50 | 06-JUL-21:55 |
August | 2010.83 | 01-AUG-09:09 | 757.61 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.57 | 08-AUG-16:00 | 1560.08 | 27-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 773.26 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 01-SEP-15:00 | 1976.40 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 1127.64 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2675.31 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4293.36 | 22-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6726.48 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.86 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 420.08 | 7781.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4595.04 | 04-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 573.59 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5188.93 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 582.83 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2773.91 | 15-MAR-04:51 |
April | 1295.83 | 03-APR-09:09 | 405.73 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2225.10 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 24-MAY-15:00 | 1163.65 | 29-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 397.11 | 30-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.47 | 29-JUN-16:00 | 793.89 | 10-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.46 | 23-JUL-14:44 | 890.95 | 16-JUL-17:20 |
August | 1295.83 | 01-AUG-09:09 | 506.28 | 31-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.05 | 08-AUG-16:00 | 1086.61 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 526.61 | 19-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 01-SEP-15:00 | 1325.18 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 729.33 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1784.15 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2896.84 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4486.74 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 793.89 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 284.46 | 5188.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 7848.45 | 04-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 979.99 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9538.15 | 12-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 885.07 | 03-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4996.54 | 15-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 613.93 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.28 | 23-APR-16:00 | 3652.64 | 01-APR-18:00 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 | 24-MAY-15:00 | 2042.53 | 29-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 606.39 | 30-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.65 | 29-JUN-16:00 | 1340.22 | 20-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 573.01 | 23-JUL-14:55 | 1359.09 | 06-JUL-21:55 |
August | 2010.79 | 01-AUG-09:09 | 768.59 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.31 | 08-AUG-16:00 | 1761.09 | 27-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 789.25 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 01-SEP-15:00 | 2269.92 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 1131.33 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3308.17 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5175.72 | 21-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7890.07 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.22 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 573.01 | 9538.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5694.47 | 04-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 644.98 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6409.28 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 578.74 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3485.55 | 15-MAR-04:56 |
April | 1295.83 | 03-APR-09:09 | 372.42 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.22 | 23-APR-16:00 | 2479.05 | 16-APR-11:53 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 24-MAY-15:00 | 1521.81 | 14-MAY-08:20 |
June | 1295.83 | 01-JUN-09:09 | 378.70 | 30-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.43 | 29-JUN-16:00 | 959.07 | 18-JUN-07:20 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.47 | 23-JUL-14:53 | 907.00 | 06-JUL-21:55 |
August | 1295.83 | 01-AUG-09:09 | 410.79 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.21 | 08-AUG-16:00 | 1208.11 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 409.38 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 01-SEP-15:00 | 1513.70 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 725.64 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2204.95 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3448.02 | 21-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5657.79 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.00 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 371.47 | 6409.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 8365.75 | 04-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 928.60 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9627.00 | 12-FEB-22:51 |
March | 2010.83 | 01-MAR-10:09 | 863.57 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5228.37 | 15-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 610.45 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4167.94 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 | 24-MAY-15:00 | 2086.38 | 29-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 608.78 | 30-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.65 | 29-JUN-16:00 | 1339.28 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 545.88 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.05 | 23-JUL-15:00 | 1385.90 | 06-JUL-21:55 |
August | 2010.83 | 01-AUG-09:09 | 756.81 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.30 | 08-AUG-16:00 | 1848.56 | 27-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 772.52 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 | 01-SEP-15:00 | 2295.12 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 1127.61 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3311.68 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5177.34 | 21-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8486.52 | 16-DEC-05:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.28 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 491.05 | 9627.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5718.14 | 04-JAN-05:58 |
February | 1295.83 | 01-FEB-10:09 | 573.29 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6423.93 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 582.52 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3485.61 | 15-MAR-04:54 |
April | 1295.83 | 03-APR-09:09 | 405.63 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2558.80 | 01-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 24-MAY-15:00 | 1417.17 | 29-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 396.99 | 30-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.44 | 29-JUN-16:00 | 921.04 | 20-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.65 | 23-JUL-14:53 | 1134.43 | 16-JUL-17:20 |
August | 1295.83 | 01-AUG-09:09 | 505.81 | 31-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.20 | 08-AUG-16:00 | 1290.02 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 526.18 | 19-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 01-SEP-15:00 | 1547.59 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 729.31 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2210.56 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3456.40 | 21-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5657.73 | 16-DEC-05:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.04 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 340.65 | 6423.93 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5886.66 | 04-JAN-05:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7879.08 | 12-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3782.70 | 15-MAR-04:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.07 | 23-APR-16:00 | 3344.76 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.56 | 24-MAY-15:00 | 1642.86 | 09-MAY-01:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.16 | 24-JUN-17:02 | 1105.26 | 10-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.62 | 23-JUL-15:00 | 1028.47 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.72 | 08-AUG-16:00 | 1450.43 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 | 01-SEP-15:00 | 1960.37 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2546.04 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4750.64 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6094.90 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1028.47 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.62 | 7879.08 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 10085.82 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13019.69 | 12-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6462.40 | 15-MAR-04:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.12 | 23-APR-16:00 | 5672.05 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.46 | 24-MAY-15:00 | 2879.85 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.36 | 24-JUN-17:02 | 1912.15 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.88 | 23-JUL-15:00 | 1796.88 | 06-JUL-21:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.59 | 08-AUG-16:00 | 2554.77 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.82 | 01-SEP-15:00 | 3420.86 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4345.79 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7810.78 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10181.36 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1796.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.88 | 13019.69 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 11484.30 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13437.37 | 12-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7110.55 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.65 | 23-APR-16:00 | 5809.89 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.39 | 24-MAY-15:00 | 3172.79 | 29-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.73 | 29-JUN-16:00 | 2058.20 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.54 | 15-JUL-17:03 | 1965.67 | 06-JUL-21:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.92 | 08-AUG-16:00 | 2795.43 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 01-SEP-16:00 | 3610.07 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4743.74 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7821.64 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 11276.89 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.54 | 13437.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88465.77 | 23-JAN-06:01 | 17952.25 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91847.07 | 21-FEB-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93637.36 | 20-MAR-03:01 | 0.00 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96799.47 | 24-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97758.21 | 30-MAY-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97450.55 | 12-JUN-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98548.73 | 10-JUL-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 94872.06 | 22-AUG-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100943.80 | 05-SEP-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 100857.13 | 23-OCT-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98043.63 | 13-NOV-04:01 | 0.00 | 3956.50 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91902.17 | 18-DEC-05:01 | 0.00 | 9043.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 88465.77 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100943.80 | 17952.25 | 9043.42 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36668.04 | 19-JAN-06:01 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73948.19 | 09-FEB-06:01 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77249.86 | 28-MAR-04:11 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81693.14 | 24-APR-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86637.38 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86935.94 | 19-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85008.94 | 13-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81716.06 | 02-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86770.23 | 05-SEP-04:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83050.52 | 23-OCT-04:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77736.60 | 13-NOV-05:01 | 0.00 | 10152.03 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74873.28 | 29-DEC-06:02 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 36668.04 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86935.94 | 12897.91 | 10152.03 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16648.86 | 18-JAN-15:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17412.44 | 28-FEB-13:40 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42908.52 | 30-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68113.64 | 15-APR-05:02 | 9673.43 | 6091.22 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77265.42 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73185.42 | 19-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74300.61 | 31-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73061.64 | 28-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72453.49 | 05-SEP-04:11 | 0.00 | 4298.88 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66909.01 | 03-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22162.88 | 17-NOV-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14907.29 | 01-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14907.29 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 77265.42 | 15316.26 | 9137.09 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12885.85 | 20-JAN-16:55 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15063.51 | 28-FEB-14:10 | 32029.16 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20962.85 | 29-MAR-15:40 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31676.83 | 13-APR-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70621.26 | 26-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72695.62 | 19-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71318.22 | 20-JUL-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71087.82 | 09-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69284.43 | 01-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29614.89 | 20-OCT-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15270.65 | 17-NOV-16:50 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13063.76 | 28-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12885.85 | 0.00 | 2686.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72695.62 | 32029.16 | 18274.19 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1642.44 | 19-JAN-14:20 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.55 |
February | 2158.02 | 28-FEB-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.79 |
March | 4413.27 | 27-MAR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.91 |
April | 6536.84 | 18-APR-13:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.64 |
May | 11338.60 | 24-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 |
June | 11749.98 | 19-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.50 |
July | 15219.29 | 23-JUL-15:21 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 115.02 | 0.00 |
August | 11252.73 | 31-AUG-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
September | 7215.85 | 01-SEP-15:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 |
October | 5323.20 | 02-OCT-13:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.74 |
November | 4065.59 | 01-NOV-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 |
December | 2137.33 | 06-DEC-06:03 | 1417.03 | 472.30 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1642.44 | 0.00 | 303.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15219.29 | 4021.58 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 115.02 | 303.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1415.81 | 25-JAN-10:20 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.68 |
February | 5417.47 | 28-FEB-09:45 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.59 |
March | 10153.83 | 20-MAR-09:05 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 |
April | 17879.20 | 16-APR-09:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.02 |
May | 21615.93 | 21-MAY-08:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.85 |
June | 23592.62 | 25-JUN-08:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 |
July | 24924.56 | 23-JUL-09:21 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 |
August | 25709.03 | 20-AUG-08:21 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.79 |
September | 17265.03 | 10-SEP-10:23 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.97 |
October | 17954.58 | 22-OCT-09:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.10 |
November | 5113.63 | 16-NOV-09:25 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.47 |
December | 1690.32 | 01-DEC-10:05 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1415.81 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 | |
Maximum of Months | 25709.03 | 2591.66 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15781.48 | 27-JAN-13:25 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20530.76 | 28-FEB-13:20 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.47 |
March | 27597.17 | 26-MAR-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.69 |
April | 30835.42 | 23-APR-13:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.25 |
May | 27190.71 | 21-MAY-11:43 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.50 |
June | 26924.46 | 04-JUN-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.06 |
July | 30193.47 | 23-JUL-13:21 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | 0.00 |
August | 30342.26 | 20-AUG-12:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.17 |
September | 28999.13 | 04-SEP-12:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.84 |
October | 29949.88 | 22-OCT-13:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.56 |
November | 18589.99 | 17-NOV-12:00 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.05 |
December | 13138.19 | 02-DEC-12:50 | 211.67 | 90.98 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13138.19 | 211.67 | 90.98 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30835.42 | 3846.30 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | 711.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4903.48 | 20-JAN-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.28 |
February | 10575.84 | 20-FEB-16:13 | 195.68 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 805.55 |
March | 27793.15 | 26-MAR-16:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.11 |
April | 34718.12 | 23-APR-16:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.28 |
May | 29313.73 | 14-MAY-16:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.02 |
June | 28809.56 | 17-JUN-17:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.52 |
July | 33334.38 | 23-JUL-16:01 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 |
August | 29213.16 | 05-AUG-17:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 |
September | 28210.92 | 03-SEP-16:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.64 |
October | 19941.42 | 22-OCT-14:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.61 |
November | 9070.13 | 21-NOV-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.12 |
December | 5787.20 | 06-DEC-06:01 | 913.19 | 304.37 | 4331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4903.48 | 195.68 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 | |
Maximum of Months | 34718.12 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 805.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1204.91 | 21-JAN-17:02 | 506.08 | 318.67 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.38 |
February | 1541.85 | 08-FEB-14:00 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.69 |
March | 2630.81 | 31-MAR-09:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.83 |
April | 4111.38 | 18-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.82 |
May | 7871.80 | 26-MAY-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.42 |
June | 13756.67 | 25-JUN-11:21 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
July | 14292.91 | 23-JUL-15:21 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 261.23 | 0.00 |
August | 8018.81 | 09-AUG-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.31 | 0.00 |
September | 6628.96 | 01-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 |
October | 2808.88 | 02-OCT-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.91 |
November | 1869.94 | 01-NOV-15:30 | 1923.11 | 578.36 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.18 |
December | 1206.83 | 30-DEC-17:03 | 404.87 | 254.94 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1204.91 | 404.87 | 212.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14292.91 | 4021.58 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 261.23 | 934.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1143.39 | 18-JAN-15:20 | 1239.33 | 375.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.37 |
February | 3676.69 | 28-FEB-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.62 |
March | 9283.95 | 31-MAR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.99 |
April | 13462.53 | 18-APR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.90 |
May | 26162.82 | 21-MAY-08:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.30 |
June | 28901.68 | 25-JUN-08:41 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.76 |
July | 27960.63 | 23-JUL-09:21 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.88 |
August | 27884.83 | 20-AUG-09:11 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.10 |
September | 20524.99 | 10-SEP-10:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.67 |
October | 12355.83 | 22-OCT-09:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.01 |
November | 3404.74 | 16-NOV-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.93 |
December | 950.74 | 01-DEC-10:00 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 950.74 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.88 | |
Maximum of Months | 28901.68 | 2478.65 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16459.03 | 27-JAN-13:35 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21517.07 | 28-FEB-13:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.68 |
March | 30591.37 | 26-MAR-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.07 |
April | 29718.47 | 23-APR-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.24 |
May | 28994.14 | 21-MAY-12:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.35 |
June | 29777.34 | 18-JUN-12:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.34 |
July | 31417.83 | 23-JUL-13:21 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 | 0.00 |
August | 32014.85 | 20-AUG-13:11 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.31 |
September | 30717.28 | 03-SEP-15:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.26 |
October | 31728.22 | 22-OCT-13:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.89 |
November | 19092.54 | 17-NOV-13:10 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.28 |
December | 12061.69 | 02-DEC-13:25 | 404.87 | 181.95 | 1680.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12061.69 | 404.87 | 151.63 | 1680.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32014.85 | 3846.30 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 | 1879.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2254.69 | 27-JAN-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5920.12 | 08-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.06 |
March | 24448.50 | 26-MAR-16:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.93 |
April | 27869.75 | 23-APR-17:01 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.12 |
May | 30937.24 | 14-MAY-17:11 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.05 |
June | 27227.03 | 17-JUN-17:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.40 |
July | 30528.19 | 23-JUL-16:01 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.46 |
August | 27492.86 | 20-AUG-15:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.31 |
September | 29771.58 | 03-SEP-16:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.69 |
October | 14038.17 | 22-OCT-15:52 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.30 |
November | 4099.22 | 17-NOV-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.80 |
December | 1101.49 | 20-DEC-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1101.49 | 0.00 | 97.71 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30937.24 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1348.74 | 21-JAN-17:02 | 506.08 | 318.67 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.11 |
February | 1491.75 | 08-FEB-14:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.15 |
March | 2042.91 | 31-MAR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.78 |
April | 3886.93 | 13-APR-16:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.01 |
May | 8526.99 | 24-MAY-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 86.45 | 0.00 |
June | 12980.21 | 27-JUN-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 |
July | 17727.51 | 23-JUL-15:31 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 355.26 | 0.00 |
August | 8615.20 | 08-AUG-15:10 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 212.29 | 0.00 |
September | 7150.99 | 01-SEP-15:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 0.00 |
October | 2775.19 | 20-OCT-13:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.85 |
November | 1909.44 | 01-NOV-16:00 | 1923.11 | 617.07 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.35 |
December | 1353.34 | 30-DEC-17:03 | 404.87 | 254.94 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1348.74 | 404.87 | 212.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17727.51 | 4021.58 | 1091.73 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 355.26 | 1160.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 895.89 | 19-JAN-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.15 |
February | 1247.89 | 28-FEB-10:20 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.08 |
March | 5412.53 | 31-MAR-10:00 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.26 |
April | 11936.84 | 18-APR-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.57 |
May | 24199.66 | 21-MAY-08:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.19 |
June | 27720.88 | 18-JUN-08:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.67 |
July | 25497.54 | 23-JUL-09:32 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 |
August | 24851.78 | 20-AUG-09:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.51 |
September | 14489.74 | 10-SEP-09:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.79 |
October | 7198.95 | 19-OCT-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.81 |
November | 1231.56 | 16-NOV-10:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.21 |
December | 896.12 | 28-DEC-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 895.89 | 391.37 | 117.25 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 | |
Maximum of Months | 27720.88 | 2591.66 | 703.55 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14203.02 | 27-JAN-13:35 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20603.17 | 28-FEB-13:40 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.96 |
March | 29401.26 | 26-MAR-14:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1643.53 |
April | 32770.83 | 23-APR-14:51 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.81 |
May | 30169.15 | 21-MAY-14:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.87 |
June | 31650.54 | 18-JUN-12:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.91 |
July | 31147.63 | 23-JUL-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 0.00 |
August | 31636.31 | 27-AUG-14:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.06 |
September | 32402.95 | 03-SEP-14:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1054.04 |
October | 34635.93 | 22-OCT-14:21 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.84 |
November | 16954.05 | 17-NOV-13:10 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.15 |
December | 9599.53 | 02-DEC-13:30 | 404.87 | 181.95 | 1680.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9599.53 | 404.87 | 151.63 | 1680.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34635.93 | 3846.30 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 1643.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1280.93 | 27-JAN-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5666.60 | 28-FEB-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.38 |
March | 10189.85 | 28-MAR-17:00 | 391.37 | 195.43 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.26 |
April | 32494.90 | 23-APR-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.83 |
May | 31928.89 | 14-MAY-17:11 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.63 |
June | 28485.30 | 17-JUN-17:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 |
July | 29056.28 | 16-JUL-16:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.55 |
August | 29537.94 | 27-AUG-17:11 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.50 |
September | 30959.18 | 03-SEP-16:41 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.23 |
October | 16686.32 | 22-OCT-15:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.80 |
November | 3263.29 | 17-NOV-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.34 |
December | 1005.36 | 20-DEC-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1005.36 | 0.00 | 136.80 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32494.90 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8253.92 | 09-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1988.86 |
February | 8309.24 | 13-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4461.11 |
March | 4788.04 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.54 |
April | 6347.60 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.47 |
May | 8591.83 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 |
June | 9534.35 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.17 |
July | 11628.84 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.30 |
August | 9703.17 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.37 |
September | 8531.19 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.86 |
October | 5985.27 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.52 |
November | 4826.02 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2696.22 |
December | 6363.75 | 19-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3472.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4788.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.30 | |
Maximum of Months | 11628.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4461.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10470.65 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.03 |
February | 11998.07 | 25-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9615.32 | 15-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4530.79 |
April | 8372.70 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2568.99 |
May | 5380.82 | 18-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.45 | 0.00 |
June | 6807.00 | 30-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.07 | 0.00 |
July | 7441.90 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.29 |
August | 5601.13 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.93 | 0.00 |
September | 5426.24 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 | 0.00 |
October | 9570.34 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.21 |
November | 11297.58 | 24-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.05 |
December | 11354.38 | 02-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3846.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5380.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11998.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.07 | 4530.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3844.85 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6690.90 |
March | 2337.79 | 26-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1583.72 |
April | 8649.02 | 13-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.62 |
May | 15855.67 | 18-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.34 | 0.00 |
June | 18224.37 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.46 | 0.00 |
July | 17017.37 | 24-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.83 | 0.00 |
August | 15431.52 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.02 | 0.00 |
September | 12831.88 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 0.00 |
October | 5424.93 | 20-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.04 |
November | 717.77 | 01-NOV-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.73 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4162.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18224.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.46 | 6690.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1966.45 | 25-JAN-16:30 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4333.50 | 27-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7036.44 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8436.82 | 21-APR-18:20 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3270.09 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5366.56 | 30-JUN-23:50 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7238.39 | 31-JUL-23:55 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8481.29 | 13-AUG-18:33 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3305.97 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4896.92 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5908.51 | 09-NOV-16:10 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7550.69 | 20-DEC-16:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1966.45 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8481.29 | 222.14 | 146.32 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1481.14 | 27-JAN-16:30 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3647.58 | 08-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6353.95 | 31-MAR-23:20 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8074.38 | 21-APR-18:20 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2947.48 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5217.22 | 30-JUN-23:55 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6884.51 | 31-JUL-23:55 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7992.20 | 05-AUG-18:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2913.33 | 30-SEP-23:30 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3953.21 | 18-OCT-16:50 | 70.15 | 81.29 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5356.47 | 09-NOV-16:20 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6631.21 | 20-DEC-16:10 | 444.28 | 292.64 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1481.14 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8074.38 | 444.28 | 292.64 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1185.11 | 27-JAN-16:30 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3585.95 | 08-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5872.87 | 28-MAR-17:50 | 23.38 | 48.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8054.04 | 21-APR-18:20 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2699.30 | 14-MAY-18:47 | 0.00 | 48.78 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5189.21 | 30-JUN-23:40 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6791.33 | 31-JUL-23:55 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8093.45 | 05-AUG-18:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2809.08 | 03-SEP-17:50 | 0.00 | 65.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3922.29 | 19-OCT-16:50 | 70.15 | 81.29 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5161.00 | 09-NOV-16:20 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6356.89 | 20-DEC-16:10 | 444.28 | 292.64 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1185.11 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8093.45 | 444.28 | 292.64 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89551.36 | 20-JAN-17:00 | 9617.36 | 5737.34 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181791.61 | 22-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358186.84 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366151.00 | 19-APR-16:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175051.66 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267741.51 | 30-JUN-23:55 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359900.61 | 31-JUL-23:43 | 0.00 | 478.10 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 375649.20 | 09-AUG-23:03 | 0.00 | 478.10 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175815.03 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266845.82 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274740.30 | 17-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 365524.74 | 06-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89551.36 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 375649.20 | 9617.36 | 5737.34 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.136538E+13 | 835221.79 | 02-JAN-08:09 | 0.111973E+13 | 2697655.94 | 09-JAN-07:10 |
February | 0.162779E+13 | 970562.06 | 28-FEB-16:10 | 0.548348E+12 | 2150239.15 | 14-FEB-07:10 |
March | 0.220232E+13 | 1178438.92 | 31-MAR-15:30 | 0.297849E+12 | 1442905.30 | 15-MAR-06:00 |
April | 0.245371E+13 | 1487354.75 | 13-APR-15:09 | 0.114596E+12 | 700263.19 | 04-APR-04:10 |
May | 0.150167E+13 | 1212395.99 | 25-MAY-15:20 | 0.785362E+11 | 333254.95 | 02-MAY-06:10 |
June | 0.191812E+13 | 1445730.42 | 30-JUN-15:09 | 0.715621E+11 | 292620.57 | 09-JUN-09:39 |
July | 0.240605E+13 | 1694569.31 | 05-JUL-15:09 | 0.669493E+11 | 87841.33 | 08-JUL-09:39 |
August | 0.274029E+13 | 1735683.59 | 08-AUG-15:20 | 0.701788E+11 | 321656.53 | 17-AUG-13:20 |
September | 0.131725E+13 | 1196711.72 | 01-SEP-15:00 | 0.683303E+11 | 409385.98 | 20-SEP-13:20 |
October | 0.175179E+13 | 1132454.11 | 20-OCT-15:20 | 0.105861E+12 | 853709.21 | 30-OCT-06:10 |
November | 0.209536E+13 | 1144604.08 | 17-NOV-16:30 | 0.280713E+12 | 1339786.49 | 27-NOV-07:10 |
December | 0.249998E+13 | 1270075.27 | 27-DEC-08:09 | 0.877216E+12 | 2457314.91 | 26-DEC-07:10 |
Annual Sum or Average | 0.238797E+14 | 0.369987E+13 | ||||
Minimum of Months | 0.131725E+13 | 835221.79 | 0.669493E+11 | 87841.33 | ||
Maximum of Months | 0.274029E+13 | 1735683.59 | 0.111973E+13 | 2697655.94 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.167117E+11 | 44458.58 | 25-JAN-12:30 | 0.00 | 0.00 |
February | 0.262803E+11 | 68582.88 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.384785E+11 | 81287.19 | 31-MAR-12:30 | 0.00 | 0.00 |
April | 0.509706E+11 | 92732.08 | 19-APR-12:20 | 0.00 | 0.00 |
May | 0.615614E+11 | 92575.96 | 06-MAY-12:20 | 0.00 | 0.00 |
June | 0.615834E+11 | 91344.24 | 16-JUN-12:30 | 0.00 | 0.00 |
July | 0.645435E+11 | 90460.72 | 07-JUL-12:30 | 0.00 | 0.00 |
August | 0.518972E+11 | 84008.73 | 05-AUG-12:30 | 0.00 | 0.00 |
September | 0.383491E+11 | 75455.28 | 04-SEP-11:00 | 0.00 | 0.00 |
October | 0.239057E+11 | 55646.39 | 09-OCT-11:30 | 0.00 | 0.00 |
November | 0.146625E+11 | 43312.97 | 07-NOV-12:20 | 0.00 | 0.00 |
December | 0.129746E+11 | 35144.22 | 02-DEC-12:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.461918E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.129746E+11 | 35144.22 | 0.00 | 0.00 | |
Maximum of Months | 0.645435E+11 | 92732.08 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.146796E+12 | 0.339302E+11 | 0.766053E+12 | 0.102195E+12 | 0.169248E+12 | 0.167446E+11 | 0.00 | 0.459305E+10 | 0.261626E+09 | 0.118551E+12 | 0.700926E+10 | 0.00 | 0.00 |
February | 0.130885E+12 | 0.262716E+11 | 0.978954E+12 | 0.923110E+11 | 0.149979E+12 | 0.186148E+11 | 0.00 | 0.183878E+11 | 0.136651E+10 | 0.204821E+12 | 0.620511E+10 | 0.00 | 0.00 |
March | 0.153998E+12 | 0.233192E+11 | 0.141687E+13 | 0.102362E+12 | 0.167280E+12 | 0.223901E+11 | 0.00 | 0.382598E+11 | 0.341612E+10 | 0.267562E+12 | 0.685660E+10 | 0.00 | 0.00 |
April | 0.136593E+12 | 0.172563E+11 | 0.165903E+13 | 0.988819E+11 | 0.172688E+12 | 0.198391E+11 | 0.00 | 0.768721E+11 | 0.167455E+11 | 0.252124E+12 | 0.368868E+10 | 0.00 | 0.00 |
May | 0.146555E+12 | 0.141801E+11 | 0.774844E+12 | 0.102278E+12 | 0.211023E+12 | 0.281516E+11 | 0.00 | 0.831569E+11 | 0.406765E+11 | 0.990697E+11 | 0.173204E+10 | 0.00 | 0.00 |
June | 0.145607E+12 | 0.121684E+11 | 0.106252E+13 | 0.990389E+11 | 0.230206E+12 | 0.399957E+11 | 0.00 | 0.200242E+12 | 0.835734E+11 | 0.434728E+11 | 0.130021E+10 | 0.00 | 0.00 |
July | 0.136486E+12 | 0.131139E+11 | 0.139340E+13 | 0.102120E+12 | 0.248643E+12 | 0.505271E+11 | 0.00 | 0.342689E+12 | 0.116130E+12 | 0.715718E+09 | 0.222434E+10 | 0.00 | 0.00 |
August | 0.152571E+12 | 0.158923E+11 | 0.173200E+13 | 0.102362E+12 | 0.230070E+12 | 0.468961E+11 | 0.00 | 0.343838E+12 | 0.113818E+12 | 0.159919E+10 | 0.124401E+10 | 0.00 | 0.00 |
September | 0.137066E+12 | 0.200871E+11 | 0.740713E+12 | 0.988811E+11 | 0.184267E+12 | 0.235808E+11 | 0.00 | 0.483131E+11 | 0.232682E+11 | 0.396938E+11 | 0.138328E+10 | 0.00 | 0.00 |
October | 0.143828E+12 | 0.266369E+11 | 0.108340E+13 | 0.102194E+12 | 0.166334E+12 | 0.162642E+11 | 0.00 | 0.352367E+11 | 0.795823E+10 | 0.165807E+12 | 0.413255E+10 | 0.00 | 0.00 |
November | 0.144641E+12 | 0.312033E+11 | 0.135889E+13 | 0.989464E+11 | 0.155650E+12 | 0.181735E+11 | 0.00 | 0.361426E+11 | 0.477024E+10 | 0.241495E+12 | 0.544368E+10 | 0.00 | 0.00 |
December | 0.142920E+12 | 0.353665E+11 | 0.170972E+13 | 0.102122E+12 | 0.167042E+12 | 0.208403E+11 | 0.00 | 0.443299E+11 | 0.294478E+10 | 0.267840E+12 | 0.685768E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171795E+13 | 0.269426E+12 | 0.146764E+14 | 0.120369E+13 | 0.225243E+13 | 0.322018E+12 | 0.00 | 0.127206E+13 | 0.414930E+12 | 0.170275E+13 | 0.480774E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130885E+12 | 0.121684E+11 | 0.740713E+12 | 0.923110E+11 | 0.149979E+12 | 0.162642E+11 | 0.00 | 0.459305E+10 | 0.261626E+09 | 0.715718E+09 | 0.124401E+10 | 0.00 | 0.00 |
Maximum of Months | 0.153998E+12 | 0.353665E+11 | 0.173200E+13 | 0.102362E+12 | 0.248643E+12 | 0.505271E+11 | 0.00 | 0.343838E+12 | 0.116130E+12 | 0.267840E+12 | 0.700926E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.104240E+13 | 0.00 | 0.773321E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.477037E+12 | 0.00 | 0.713109E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.215509E+12 | 0.00 | 0.823400E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.403559E+11 | 0.00 | 0.742402E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.285206E+10 | 0.00 | 0.756842E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.271327E+09 | 0.00 | 0.712908E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 87149224.95 | 0.00 | 0.668622E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.370449E+09 | 0.00 | 0.698084E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.353903E+10 | 0.00 | 0.647913E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.371742E+11 | 0.00 | 0.686871E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.210824E+12 | 0.00 | 0.698888E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.803834E+12 | 0.00 | 0.733826E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.283425E+13 | 0.00 | 0.865619E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 87149224.95 | 0.00 | 0.647913E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.104240E+13 | 0.00 | 0.823400E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 169722.15 | 02-JAN-08:09 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73700.64 | 02-JAN-08:20 | 111587.82 | 02-JAN-06:19 | 21357.42 | 17-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 161956.77 | 02-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73694.08 | 15-FEB-08:20 | 96785.29 | 28-FEB-15:30 | 21429.89 | 27-FEB-06:19 | 0.00 | 01-FEB-00:10 |
March | 158770.01 | 03-MAR-16:00 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73694.60 | 13-MAR-07:19 | 133802.11 | 31-MAR-15:30 | 21248.94 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 148496.55 | 03-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73689.50 | 03-APR-07:19 | 179118.98 | 13-APR-14:00 | 21588.68 | 23-APR-15:09 | 0.00 | 01-APR-00:10 |
May | 145987.23 | 01-MAY-07:10 | 22480.63 | 01-MAY-19:30 | 423497.50 | 01-MAY-07:10 | 73688.19 | 01-MAY-07:19 | 247573.37 | 18-MAY-14:39 | 44059.76 | 17-MAY-12:39 | 0.00 | 01-MAY-00:10 |
June | 148359.19 | 30-JUN-07:10 | 22480.63 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 73689.43 | 30-JUN-07:19 | 242774.25 | 30-JUN-14:30 | 42226.22 | 21-JUN-13:30 | 0.00 | 01-JUN-00:10 |
July | 146009.26 | 03-JUL-07:10 | 22480.63 | 01-JUL-20:19 | 660080.29 | 03-JUL-07:10 | 73688.20 | 03-JUL-07:19 | 288379.59 | 05-JUL-10:39 | 49690.24 | 05-JUL-10:30 | 0.00 | 01-JUL-00:10 |
August | 153787.63 | 31-AUG-07:10 | 31088.59 | 15-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73692.28 | 31-AUG-07:19 | 263000.22 | 08-AUG-15:20 | 42289.26 | 22-AUG-15:09 | 0.00 | 01-AUG-00:10 |
September | 154449.25 | 19-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73692.62 | 19-SEP-07:19 | 235847.70 | 01-SEP-15:00 | 41518.45 | 01-SEP-12:09 | 0.00 | 01-SEP-00:10 |
October | 169012.59 | 31-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73700.27 | 31-OCT-07:19 | 154313.86 | 20-OCT-15:20 | 22345.45 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 06-NOV-16:49 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73700.16 | 01-NOV-07:19 | 99972.45 | 17-NOV-13:00 | 21250.84 | 27-NOV-07:19 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:19 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73700.64 | 26-DEC-08:20 | 109559.35 | 26-DEC-06:19 | 21396.81 | 11-DEC-07:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 145987.23 | 22480.63 | 423497.50 | 73688.19 | 96785.29 | 21248.94 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 73700.64 | 288379.59 | 49690.24 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 5643.85 | 27-JAN-16:40 | 429.50 | 20-JAN-16:19 | 57305.38 | 21-JAN-15:00 | 5431.84 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 19000.04 | 28-FEB-15:20 | 1911.35 | 20-FEB-16:40 | 100000.00 | 04-FEB-17:10 | 5431.84 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 61826.07 | 31-MAR-15:00 | 3954.70 | 26-MAR-15:00 | 100000.00 | 01-MAR-05:30 | 5431.84 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 209554.08 | 23-APR-15:00 | 46583.26 | 23-APR-15:00 | 100000.00 | 01-APR-04:10 | 5431.84 | 01-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 244155.69 | 25-MAY-12:09 | 76123.16 | 16-MAY-13:39 | 100000.00 | 06-MAY-16:19 | 5431.84 | 10-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 379464.96 | 19-JUN-15:20 | 76123.16 | 06-JUN-12:30 | 100000.00 | 03-JUN-16:10 | 5431.84 | 06-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 461910.36 | 05-JUL-10:09 | 76123.16 | 03-JUL-08:00 | 42096.18 | 07-JUL-17:00 | 5431.84 | 03-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 428523.70 | 31-AUG-12:50 | 76123.16 | 04-AUG-15:30 | 80106.69 | 19-AUG-04:00 | 5431.84 | 08-AUG-10:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 227294.69 | 01-SEP-14:00 | 76123.16 | 01-SEP-09:20 | 100000.00 | 08-SEP-14:39 | 5431.84 | 01-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 140135.85 | 19-OCT-14:00 | 46445.06 | 19-OCT-14:39 | 100000.00 | 09-OCT-09:39 | 5431.84 | 05-OCT-20:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 72610.62 | 01-NOV-14:00 | 44117.18 | 01-NOV-12:50 | 100000.00 | 02-NOV-21:10 | 5431.84 | 03-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 19890.09 | 02-DEC-15:00 | 1962.63 | 05-DEC-22:19 | 100000.00 | 01-DEC-03:09 | 5431.84 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 5643.85 | 429.50 | 42096.18 | 5431.84 | 0.00 | 0.00 | |||||
Maximum of Months | 461910.36 | 76123.16 | 100000.00 | 5431.84 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 835221.79 | 02-JAN-08:09 | 169722.15 | 423497.50 | 31088.59 | 73641.61 | 85066.81 | 3981.14 | 0.00 | 1294.70 | 68.07 |
February | 970562.06 | 28-FEB-16:10 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 88855.07 | 21118.19 | 0.00 | 15402.83 | 1806.41 |
March | 1178438.92 | 31-MAR-15:30 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 133802.11 | 21179.20 | 0.00 | 61668.35 | 3132.13 |
April | 1487354.75 | 13-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 178864.37 | 21336.94 | 0.00 | 166112.94 | 44091.99 |
May | 1212395.99 | 25-MAY-15:20 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 229645.52 | 40462.00 | 0.00 | 238659.14 | 76123.16 |
June | 1445730.42 | 30-JUN-15:09 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 236662.67 | 41679.33 | 0.00 | 345467.70 | 76123.16 |
July | 1694569.31 | 05-JUL-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 288379.59 | 49421.11 | 0.00 | 421077.22 | 76123.16 |
August | 1735683.59 | 08-AUG-15:20 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 263000.22 | 40993.38 | 0.00 | 373186.47 | 76123.16 |
September | 1196711.72 | 01-SEP-15:00 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 235847.70 | 40458.26 | 0.00 | 216776.43 | 76123.16 |
October | 1132454.11 | 20-OCT-15:20 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 154313.86 | 21241.98 | 0.00 | 72497.52 | 44035.02 |
November | 1144604.08 | 17-NOV-16:30 | 169722.15 | 660080.29 | 31088.59 | 52596.36 | 81597.67 | 21115.04 | 0.00 | 22284.34 | 3105.81 |
December | 1270075.27 | 27-DEC-08:09 | 169722.15 | 778371.69 | 31088.59 | 73641.61 | 72899.53 | 21161.17 | 0.00 | 16601.45 | 1157.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 835221.79 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 72899.53 | 3981.14 | 0.00 | 1294.70 | 68.07 | |
Maximum of Months | 1735683.59 | 169722.15 | 778371.69 | 31088.59 | 73641.61 | 288379.59 | 49421.11 | 0.00 | 421077.22 | 76123.16 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2665274.07 | 09-JAN-07:10 | 0.00 | 88810.80 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 2118508.30 | 14-FEB-07:10 | 0.00 | 89098.26 | 24-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 1410143.81 | 15-MAR-06:00 | 0.00 | 89127.61 | 02-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 692982.31 | 04-APR-04:10 | 0.00 | 88522.01 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 301394.76 | 02-MAY-06:10 | 0.00 | 87351.06 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 233523.01 | 09-JUN-09:39 | 0.00 | 85560.76 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 60341.30 | 08-JUL-11:30 | 0.00 | 83544.79 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 273336.00 | 17-AUG-13:20 | 0.00 | 82134.99 | 01-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 368764.56 | 20-SEP-13:20 | 0.00 | 82423.67 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 823882.34 | 30-OCT-06:10 | 0.00 | 84167.42 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 1308278.06 | 27-NOV-07:10 | 0.00 | 86099.22 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 2426109.16 | 26-DEC-07:10 | 0.00 | 87675.90 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 60341.30 | 0.00 | 82134.99 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2665274.07 | 0.00 | 89127.61 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.71 | 0.00 | 25.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.81 | 0.00 | 25.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.03 | 0.33 | 26.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.04 | 0.00 | 26.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.55 | 1.00 | 26.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.15 | 0.00 | 27.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.01 | 0.17 | 27.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.84 | 0.33 | 26.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.82 | 0.00 | 25.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
Annual Sum or Average | 0.00 | 0.00 | 31.33 | 26.56 | 1.83 | 26.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.15 | 1.00 | 27.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.77 | 2.17 | 24.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.67 | 24.92 | 2.17 | 24.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.58 | 2.17 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.10 | 1.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.68 | 0.67 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
December | 0.67 | 19.44 | 0.17 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Annual Sum or Average | 3.83 | 19.15 | 1.67 | 19.35 | 0.67 | 19.93 | 0.67 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.44 | 1.50 | 19.56 | 0.67 | 24.68 | 0.67 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.17 | 18.91 | 5.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 6.83 | 18.89 | 1.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
March | 3.17 | 19.06 | 0.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.67 | 0.67 | 24.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
November | 4.17 | 18.81 | 0.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
December | 11.50 | 18.88 | 3.67 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Annual Sum or Average | 41.83 | 18.90 | 11.67 | 19.12 | 0.67 | 19.19 | 0.67 | 19.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.17 | 19.38 | 5.00 | 19.38 | 0.67 | 24.67 | 0.67 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 18.75 | 1.17 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 1.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.44 | 5.83 | 25.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 19.29 | 0.33 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Annual Sum or Average | 11.00 | 18.87 | 1.50 | 19.03 | 5.83 | 21.07 | 5.83 | 22.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 19.29 | 1.17 | 19.46 | 5.83 | 25.44 | 5.83 | 25.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 18.41 | 0.17 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
February | 1.67 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
March | 0.17 | 19.43 | 0.00 | 19.43 | 0.17 | 23.35 | 0.17 | 24.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.87 | 1.33 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.12 | 3.33 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.18 | 6.00 | 28.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.85 | 5.83 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.03 | 6.17 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.90 | 2.50 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.69 | 1.67 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Annual Sum or Average | 10.33 | 18.68 | 0.17 | 18.70 | 27.33 | 25.41 | 27.00 | 26.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 19.43 | 0.17 | 19.43 | 6.17 | 28.18 | 6.17 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 18.44 | 0.33 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
February | 2.33 | 18.92 | 0.00 | 18.92 | 1.33 | 22.06 | 1.33 | 23.52 |
March | 0.17 | 19.08 | 0.00 | 19.08 | 3.67 | 27.70 | 3.67 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.02 | 2.67 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.81 | 2.67 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.84 | 3.67 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.78 | 10.50 | 26.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.08 | 7.33 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.07 | 6.67 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.24 | 4.83 | 28.24 |
November | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 3.00 | 18.95 | 0.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Annual Sum or Average | 12.50 | 18.67 | 0.50 | 18.74 | 44.17 | 25.68 | 43.33 | 26.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 0.00 | 18.53 |
Maximum of Months | 6.83 | 19.22 | 0.33 | 19.22 | 11.00 | 28.24 | 10.50 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.44 | 2.33 | 28.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.00 | 5.17 | 28.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.42 | 3.33 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.53 | 6.67 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.69 | 15.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.60 | 11.83 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.89 | 4.83 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.79 | 2.67 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.17 | 19.06 | 0.00 | 19.06 | 103.83 | 27.49 | 53.33 | 27.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.06 | 0.00 | 19.06 | 31.33 | 28.44 | 15.67 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.67 | 17.18 | 50.00 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
February | 51.50 | 17.54 | 19.17 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
March | 19.00 | 18.35 | 5.50 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
April | 1.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.38 | 4.00 | 25.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
November | 12.67 | 18.26 | 2.33 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
December | 87.50 | 16.92 | 36.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 277.17 | 17.31 | 113.17 | 17.64 | 4.00 | 17.71 | 4.00 | 17.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.67 | 19.28 | 50.00 | 19.28 | 4.00 | 25.38 | 4.00 | 25.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.33 | 17.14 | 8.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
February | 34.83 | 17.36 | 1.17 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
March | 15.17 | 18.50 | 0.17 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
April | 1.00 | 19.11 | 0.00 | 19.11 | 0.67 | 22.46 | 0.67 | 23.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.01 | 3.83 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.31 | 7.00 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.94 | 6.83 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.07 | 6.83 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.77 | 2.33 | 27.77 |
October | 0.17 | 19.09 | 0.00 | 19.09 | 0.50 | 25.39 | 0.50 | 26.29 |
November | 17.83 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
December | 95.83 | 17.20 | 10.83 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
Annual Sum or Average | 255.17 | 17.36 | 20.67 | 17.17 | 28.50 | 18.19 | 28.00 | 19.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 | 0.00 | 16.92 |
Maximum of Months | 95.83 | 19.11 | 10.83 | 19.11 | 7.33 | 28.31 | 7.00 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.33 | 15.89 | 2.67 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
February | 15.33 | 16.91 | 0.83 | 16.91 | 0.17 | 17.01 | 0.17 | 17.12 |
March | 5.67 | 18.36 | 0.17 | 18.41 | 3.67 | 22.18 | 3.67 | 23.85 |
April | 0.83 | 19.26 | 0.00 | 19.26 | 2.50 | 25.86 | 2.33 | 26.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.91 | 2.83 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.86 | 3.67 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.10 | 8.33 | 27.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.17 | 6.33 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.53 | 8.00 | 27.53 |
October | 0.17 | 19.22 | 0.00 | 19.22 | 4.50 | 28.20 | 4.50 | 28.36 |
November | 5.33 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
December | 32.83 | 15.98 | 4.17 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
Annual Sum or Average | 93.50 | 16.39 | 7.83 | 16.33 | 41.17 | 19.64 | 39.83 | 21.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 0.00 | 15.81 |
Maximum of Months | 33.33 | 19.26 | 4.17 | 19.26 | 8.83 | 28.20 | 8.33 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.50 | 15.60 | 6.17 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
February | 13.83 | 16.84 | 1.00 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
March | 5.17 | 18.32 | 0.17 | 18.38 | 1.17 | 20.09 | 0.67 | 20.81 |
April | 0.33 | 19.19 | 0.00 | 19.19 | 2.33 | 27.50 | 1.17 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.76 | 2.00 | 28.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.97 | 2.67 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.38 | 5.83 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.32 | 4.17 | 28.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.12 | 1.83 | 28.15 |
October | 0.17 | 19.33 | 0.00 | 19.33 | 0.50 | 25.75 | 0.50 | 26.66 |
November | 4.67 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
December | 32.50 | 15.69 | 6.67 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
Annual Sum or Average | 91.17 | 16.13 | 14.00 | 15.96 | 36.17 | 19.13 | 18.83 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 | 0.00 | 15.45 |
Maximum of Months | 34.50 | 19.33 | 6.67 | 19.33 | 11.33 | 28.76 | 5.83 | 28.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 149.67 | 16.39 | 67.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
February | 98.33 | 16.51 | 36.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
March | 44.83 | 17.09 | 13.67 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
April | 9.83 | 17.37 | 1.50 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
May | 0.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.40 | 1.83 | 26.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.50 | 18.73 | 0.67 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
November | 48.67 | 16.51 | 16.17 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
December | 132.67 | 16.17 | 57.17 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
Annual Sum or Average | 488.67 | 16.48 | 192.83 | 16.78 | 2.17 | 16.82 | 1.83 | 16.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.67 | 19.24 | 67.17 | 19.24 | 2.17 | 26.40 | 1.83 | 26.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 78.33 | 14.92 | 20.17 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
February | 50.33 | 15.19 | 6.83 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
March | 23.83 | 16.22 | 1.83 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
April | 7.00 | 16.90 | 0.83 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
May | 0.17 | 19.44 | 0.00 | 19.44 | 2.33 | 27.27 | 2.33 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.31 | 6.67 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.93 | 7.00 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.96 | 7.00 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.60 | 1.33 | 27.60 |
October | 3.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
November | 33.67 | 15.45 | 8.17 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
December | 71.83 | 14.77 | 18.83 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
Annual Sum or Average | 268.17 | 15.20 | 56.67 | 15.11 | 25.33 | 16.04 | 24.33 | 16.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 0.00 | 14.69 |
Maximum of Months | 78.33 | 19.44 | 20.17 | 19.44 | 8.00 | 28.31 | 7.00 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.83 | 15.41 | 16.83 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
February | 41.83 | 15.68 | 5.00 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
March | 18.50 | 16.76 | 1.83 | 16.75 | 1.83 | 17.66 | 1.83 | 18.42 |
April | 5.33 | 17.38 | 0.83 | 17.05 | 1.50 | 19.25 | 1.33 | 20.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.77 | 2.33 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.86 | 3.83 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.54 | 6.83 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.19 | 6.17 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.97 | 5.67 | 27.98 |
October | 2.67 | 18.68 | 0.00 | 18.68 | 3.67 | 24.21 | 3.67 | 25.69 |
November | 27.67 | 15.84 | 7.00 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
December | 63.67 | 15.27 | 12.50 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
Annual Sum or Average | 231.50 | 15.66 | 44.00 | 15.61 | 33.50 | 16.94 | 31.67 | 17.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 0.00 | 15.22 |
Maximum of Months | 71.83 | 18.68 | 16.83 | 18.68 | 7.83 | 28.19 | 6.83 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.67 | 14.89 | 18.00 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
February | 37.83 | 15.44 | 5.83 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
March | 15.33 | 16.80 | 1.17 | 16.76 | 0.33 | 16.98 | 0.17 | 17.08 |
April | 3.67 | 18.34 | 0.00 | 18.34 | 1.83 | 21.85 | 1.00 | 22.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.74 | 1.83 | 28.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.96 | 3.17 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.43 | 6.00 | 28.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.36 | 4.17 | 28.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.16 | 1.67 | 28.18 |
October | 1.83 | 18.56 | 0.00 | 18.56 | 0.50 | 20.49 | 0.50 | 21.74 |
November | 22.83 | 15.85 | 4.67 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
December | 55.50 | 14.94 | 13.33 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
Annual Sum or Average | 203.67 | 15.35 | 43.00 | 15.24 | 34.83 | 16.86 | 18.50 | 17.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 | 14.83 |
Maximum of Months | 66.67 | 18.56 | 18.00 | 18.56 | 11.50 | 28.74 | 6.00 | 28.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.97 | 3.33 | 28.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 28.97 | 3.33 | 28.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.97 | 3.33 | 28.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.79 | 2.00 | 28.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 28.79 | 2.00 | 28.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.79 | 2.00 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.68 | 1.50 | 28.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 28.68 | 1.50 | 28.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.68 | 1.50 | 28.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 29.00 | 49.67 | 29.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 142.33 | 29.38 | 135.67 | 29.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 201.17 | 29.27 | 185.33 | 29.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 142.33 | 29.38 | 135.67 | 29.41 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.50 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
February | 355.33 | 23.90 | 0.00 | 23.90 | 0.00 | 23.90 |
March | 370.50 | 24.01 | 10.33 | 24.06 | 0.00 | 24.06 |
April | 282.67 | 24.00 | 66.50 | 24.42 | 0.00 | 24.42 |
May | 105.67 | 24.00 | 193.50 | 24.68 | 14.00 | 24.65 |
June | 158.67 | 24.57 | 352.17 | 24.58 | 150.33 | 24.58 |
July | 207.17 | 24.85 | 477.33 | 24.68 | 207.17 | 24.72 |
August | 112.00 | 24.55 | 472.17 | 24.51 | 112.00 | 24.51 |
September | 18.00 | 24.00 | 212.17 | 25.06 | 18.00 | 24.98 |
October | 45.17 | 24.00 | 119.83 | 25.48 | 0.00 | 25.48 |
November | 263.83 | 24.01 | 66.17 | 24.40 | 0.00 | 24.40 |
December | 382.17 | 23.82 | 7.33 | 23.86 | 0.00 | 23.86 |
Annual Sum or Average | 2773.67 | 24.01 | 1977.50 | 24.37 | 501.50 | 24.40 |
Minimum of Months | 18.00 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
Maximum of Months | 472.50 | 24.85 | 477.33 | 25.48 | 207.17 | 25.48 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.29 | 4.33 | 23.27 | 4.33 | 23.25 |
February | 433.83 | 23.86 | 0.00 | 23.86 | 0.00 | 23.86 |
March | 365.33 | 23.97 | 2.67 | 23.99 | 0.00 | 23.99 |
April | 208.17 | 24.00 | 44.33 | 24.30 | 0.00 | 24.30 |
May | 81.67 | 24.01 | 176.67 | 24.38 | 0.00 | 24.38 |
June | 6.83 | 24.59 | 355.83 | 24.31 | 1.83 | 24.32 |
July | 3.33 | 24.64 | 485.67 | 24.28 | 3.33 | 24.28 |
August | 0.00 | 0.00 | 478.50 | 24.24 | 0.00 | 24.24 |
September | 2.33 | 23.96 | 199.83 | 24.67 | 0.00 | 24.67 |
October | 64.00 | 23.98 | 92.67 | 24.78 | 0.00 | 24.78 |
November | 269.33 | 23.99 | 30.00 | 24.07 | 0.00 | 24.07 |
December | 439.67 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 2376.50 | 23.81 | 1870.50 | 24.09 | 9.50 | 24.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.27 | 0.00 | 23.25 |
Maximum of Months | 502.00 | 24.64 | 485.67 | 24.78 | 4.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.15 | 252.50 | 20.90 | 252.50 | 20.78 |
February | 454.00 | 21.85 | 93.83 | 21.63 | 93.83 | 21.48 |
March | 514.00 | 22.76 | 19.33 | 22.70 | 19.33 | 22.64 |
April | 436.83 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
May | 159.00 | 23.86 | 137.00 | 24.15 | 0.00 | 24.15 |
June | 37.83 | 24.24 | 308.33 | 24.23 | 9.50 | 24.26 |
July | 3.33 | 24.31 | 457.83 | 24.27 | 3.33 | 24.27 |
August | 4.33 | 23.58 | 430.50 | 24.18 | 0.00 | 24.18 |
September | 106.17 | 23.68 | 117.17 | 24.10 | 7.00 | 24.10 |
October | 373.83 | 23.49 | 1.50 | 23.50 | 0.00 | 23.50 |
November | 480.50 | 22.70 | 37.00 | 22.55 | 37.00 | 22.42 |
December | 497.00 | 21.37 | 200.67 | 21.14 | 200.67 | 21.02 |
Annual Sum or Average | 3568.83 | 22.49 | 2055.67 | 22.74 | 623.17 | 22.53 |
Minimum of Months | 3.33 | 21.15 | 0.00 | 20.90 | 0.00 | 20.78 |
Maximum of Months | 514.00 | 24.31 | 457.83 | 24.27 | 252.50 | 24.27 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.32 | 424.67 | 20.22 | 424.67 | 20.18 |
February | 454.00 | 20.71 | 308.00 | 20.51 | 308.00 | 20.42 |
March | 514.00 | 21.39 | 213.00 | 21.10 | 213.00 | 20.95 |
April | 476.00 | 22.51 | 64.33 | 22.26 | 64.33 | 22.06 |
May | 221.67 | 23.38 | 129.33 | 23.74 | 2.00 | 23.73 |
June | 81.83 | 23.41 | 284.83 | 24.02 | 9.17 | 24.02 |
July | 26.50 | 23.50 | 431.50 | 24.20 | 3.33 | 24.20 |
August | 41.67 | 23.42 | 392.17 | 24.08 | 5.83 | 24.08 |
September | 261.50 | 23.28 | 69.00 | 23.48 | 15.33 | 23.50 |
October | 484.17 | 22.16 | 53.67 | 21.95 | 53.67 | 21.78 |
November | 489.00 | 21.08 | 214.83 | 20.75 | 214.83 | 20.58 |
December | 497.00 | 20.40 | 392.00 | 20.26 | 392.00 | 20.21 |
Annual Sum or Average | 4049.33 | 21.55 | 2977.33 | 21.72 | 1706.17 | 21.43 |
Minimum of Months | 26.50 | 20.32 | 53.67 | 20.22 | 2.00 | 20.18 |
Maximum of Months | 514.00 | 23.50 | 431.50 | 24.20 | 424.67 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 426.00 | 20.46 | 426.00 | 20.43 |
February | 454.00 | 21.26 | 238.83 | 21.06 | 238.83 | 20.96 |
March | 511.67 | 22.16 | 82.50 | 21.97 | 82.50 | 21.83 |
April | 434.17 | 23.39 | 8.33 | 23.41 | 1.83 | 23.40 |
May | 156.83 | 23.80 | 171.00 | 24.14 | 0.00 | 24.14 |
June | 9.17 | 24.94 | 367.33 | 24.35 | 3.00 | 24.37 |
July | 13.00 | 26.38 | 485.00 | 24.44 | 13.00 | 24.49 |
August | 5.67 | 23.81 | 461.83 | 24.24 | 0.33 | 24.24 |
September | 167.50 | 23.52 | 131.17 | 23.94 | 0.00 | 23.94 |
October | 422.00 | 23.24 | 5.17 | 23.25 | 0.00 | 23.25 |
November | 473.33 | 22.26 | 54.67 | 22.12 | 51.00 | 22.00 |
December | 497.00 | 20.90 | 308.67 | 20.73 | 308.67 | 20.65 |
Annual Sum or Average | 3646.33 | 22.09 | 2740.50 | 22.40 | 1125.17 | 22.13 |
Minimum of Months | 5.67 | 20.53 | 5.17 | 20.46 | 0.00 | 20.43 |
Maximum of Months | 511.67 | 26.38 | 485.00 | 24.44 | 426.00 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.66 | 383.50 | 20.51 | 383.50 | 20.46 |
February | 448.67 | 21.62 | 185.17 | 21.34 | 185.17 | 21.19 |
March | 453.00 | 22.25 | 89.17 | 22.12 | 75.17 | 21.96 |
April | 322.17 | 23.22 | 71.00 | 23.47 | 7.17 | 23.48 |
May | 100.17 | 24.11 | 253.67 | 24.49 | 10.50 | 24.57 |
June | 37.17 | 26.12 | 414.50 | 24.53 | 26.83 | 24.67 |
July | 37.00 | 26.47 | 475.83 | 24.56 | 34.50 | 24.70 |
August | 43.17 | 25.57 | 451.67 | 24.43 | 25.00 | 24.55 |
September | 137.83 | 23.62 | 189.33 | 24.20 | 9.00 | 24.27 |
October | 389.67 | 23.12 | 40.50 | 23.32 | 4.67 | 23.36 |
November | 467.83 | 22.13 | 79.50 | 21.93 | 76.83 | 21.77 |
December | 497.00 | 20.84 | 335.33 | 20.68 | 335.33 | 20.61 |
Annual Sum or Average | 3435.67 | 22.14 | 2969.17 | 22.56 | 1173.67 | 22.34 |
Minimum of Months | 37.00 | 20.66 | 40.50 | 20.51 | 4.67 | 20.46 |
Maximum of Months | 502.00 | 26.47 | 475.83 | 24.56 | 383.50 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.50 | 21.02 | 306.33 | 20.73 | 301.17 | 20.59 |
February | 359.50 | 21.71 | 187.83 | 21.59 | 155.00 | 21.37 |
March | 393.50 | 22.26 | 131.67 | 22.31 | 87.17 | 22.17 |
April | 312.00 | 23.15 | 91.67 | 23.40 | 19.50 | 23.39 |
May | 125.33 | 23.66 | 231.50 | 24.23 | 4.67 | 24.27 |
June | 41.67 | 24.87 | 374.67 | 24.40 | 14.67 | 24.49 |
July | 35.00 | 26.69 | 475.00 | 24.59 | 34.33 | 24.72 |
August | 37.00 | 26.31 | 461.33 | 24.49 | 29.50 | 24.64 |
September | 145.83 | 23.94 | 234.17 | 24.35 | 24.33 | 24.52 |
October | 355.83 | 23.10 | 91.00 | 23.44 | 19.00 | 23.55 |
November | 414.50 | 22.10 | 122.00 | 22.00 | 87.33 | 21.78 |
December | 456.50 | 21.14 | 256.83 | 20.90 | 253.83 | 20.77 |
Annual Sum or Average | 3138.17 | 22.28 | 2964.00 | 22.76 | 1030.50 | 22.55 |
Minimum of Months | 35.00 | 21.02 | 91.00 | 20.73 | 4.67 | 20.59 |
Maximum of Months | 461.50 | 26.69 | 475.00 | 24.59 | 301.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.17 | 21.23 | 281.67 | 20.99 | 281.67 | 20.88 |
February | 403.67 | 22.51 | 73.50 | 22.36 | 61.83 | 22.20 |
March | 350.17 | 23.56 | 50.50 | 23.69 | 8.83 | 23.73 |
April | 103.50 | 24.41 | 139.50 | 24.86 | 13.50 | 24.98 |
May | 52.00 | 24.96 | 305.00 | 24.70 | 18.67 | 24.80 |
June | 47.83 | 26.37 | 466.33 | 24.71 | 47.83 | 24.85 |
July | 108.17 | 26.38 | 497.00 | 25.00 | 108.17 | 25.21 |
August | 77.33 | 26.48 | 512.17 | 24.81 | 77.33 | 25.00 |
September | 48.83 | 25.19 | 281.00 | 24.76 | 22.17 | 24.90 |
October | 157.00 | 23.99 | 109.17 | 24.37 | 6.83 | 24.44 |
November | 343.00 | 23.56 | 28.83 | 23.65 | 0.00 | 23.65 |
December | 473.33 | 22.78 | 47.50 | 22.59 | 47.50 | 22.43 |
Annual Sum or Average | 2660.00 | 23.19 | 2792.17 | 23.66 | 694.33 | 23.61 |
Minimum of Months | 47.83 | 21.23 | 28.83 | 20.99 | 0.00 | 20.88 |
Maximum of Months | 495.17 | 26.48 | 512.17 | 25.00 | 281.67 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 20.00 | 441.00 | 19.98 | 441.00 | 19.97 |
March | 514.00 | 20.64 | 378.33 | 20.49 | 378.33 | 20.43 |
April | 475.33 | 21.83 | 127.67 | 21.52 | 126.00 | 21.31 |
May | 231.17 | 23.23 | 137.67 | 23.64 | 1.00 | 23.63 |
June | 64.67 | 23.99 | 295.17 | 24.22 | 11.33 | 24.26 |
July | 55.17 | 25.39 | 455.50 | 24.47 | 46.17 | 24.58 |
August | 62.00 | 23.25 | 370.83 | 24.02 | 1.17 | 24.02 |
September | 307.00 | 22.92 | 67.33 | 23.14 | 5.67 | 23.15 |
October | 497.33 | 21.68 | 87.50 | 21.46 | 87.50 | 21.30 |
November | 489.00 | 20.35 | 358.83 | 20.18 | 358.83 | 20.12 |
December | 497.00 | 19.76 | 497.00 | 19.76 | 497.00 | 19.76 |
Annual Sum or Average | 4148.67 | 21.04 | 3718.83 | 21.25 | 2456.00 | 20.98 |
Minimum of Months | 55.17 | 19.69 | 67.33 | 19.69 | 1.00 | 19.69 |
Maximum of Months | 514.00 | 25.39 | 502.00 | 24.47 | 502.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.62 | 425.67 | 19.61 | 425.67 | 19.61 |
February | 385.00 | 20.12 | 338.33 | 20.00 | 338.33 | 19.96 |
March | 418.67 | 21.20 | 234.00 | 20.90 | 233.50 | 20.75 |
April | 309.50 | 22.19 | 106.33 | 22.16 | 63.17 | 21.90 |
May | 127.33 | 23.68 | 201.33 | 24.35 | 10.50 | 24.44 |
June | 51.00 | 25.56 | 322.33 | 24.63 | 31.83 | 24.80 |
July | 65.00 | 26.37 | 398.83 | 24.82 | 60.67 | 25.03 |
August | 59.50 | 25.09 | 360.33 | 24.52 | 30.33 | 24.69 |
September | 195.50 | 23.09 | 129.50 | 23.72 | 10.17 | 23.79 |
October | 375.00 | 21.83 | 88.50 | 21.80 | 65.83 | 21.62 |
November | 417.00 | 20.44 | 279.00 | 20.19 | 279.00 | 20.08 |
December | 422.00 | 19.64 | 419.00 | 19.63 | 419.00 | 19.63 |
Annual Sum or Average | 3252.50 | 21.18 | 3303.17 | 21.57 | 1968.00 | 21.29 |
Minimum of Months | 51.00 | 19.62 | 88.50 | 19.61 | 10.17 | 19.61 |
Maximum of Months | 427.00 | 26.37 | 425.67 | 24.82 | 425.67 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.83 | 20.32 | 380.17 | 20.07 | 376.00 | 19.96 |
February | 378.33 | 20.93 | 268.83 | 20.74 | 240.67 | 20.55 |
March | 410.50 | 21.52 | 241.83 | 21.48 | 199.17 | 21.30 |
April | 337.17 | 22.28 | 140.50 | 22.39 | 72.00 | 22.20 |
May | 156.00 | 23.29 | 221.83 | 23.99 | 5.83 | 24.04 |
June | 91.83 | 24.15 | 331.83 | 24.30 | 22.83 | 24.40 |
July | 75.50 | 25.75 | 444.67 | 24.65 | 61.17 | 24.82 |
August | 71.67 | 24.71 | 425.33 | 24.40 | 28.17 | 24.54 |
September | 200.67 | 23.48 | 214.17 | 24.07 | 32.17 | 24.25 |
October | 389.17 | 22.33 | 134.00 | 22.54 | 68.67 | 22.48 |
November | 434.50 | 21.01 | 237.00 | 20.79 | 212.50 | 20.58 |
December | 482.17 | 20.31 | 401.00 | 20.12 | 401.00 | 20.04 |
Annual Sum or Average | 3501.33 | 21.65 | 3441.17 | 22.05 | 1720.17 | 21.78 |
Minimum of Months | 71.67 | 20.31 | 134.00 | 20.07 | 5.83 | 19.96 |
Maximum of Months | 482.17 | 25.75 | 444.67 | 24.65 | 401.00 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 470.50 | 19.91 | 470.50 | 19.88 |
February | 445.00 | 20.55 | 339.17 | 20.35 | 339.17 | 20.27 |
March | 468.33 | 21.22 | 260.33 | 21.02 | 244.50 | 20.87 |
April | 382.50 | 22.38 | 116.67 | 22.34 | 69.33 | 22.16 |
May | 151.17 | 23.65 | 237.33 | 24.19 | 13.50 | 24.27 |
June | 64.33 | 24.74 | 372.67 | 24.46 | 31.17 | 24.56 |
July | 69.83 | 26.27 | 483.17 | 24.75 | 69.83 | 24.92 |
August | 48.50 | 25.09 | 453.33 | 24.43 | 26.00 | 24.54 |
September | 191.17 | 23.26 | 167.83 | 23.85 | 14.00 | 23.94 |
October | 428.83 | 22.13 | 92.17 | 22.12 | 57.33 | 21.97 |
November | 484.33 | 20.79 | 274.33 | 20.51 | 274.33 | 20.38 |
December | 497.00 | 19.99 | 464.83 | 19.95 | 464.83 | 19.93 |
Annual Sum or Average | 3733.00 | 21.39 | 3732.33 | 21.79 | 2074.50 | 21.51 |
Minimum of Months | 48.50 | 19.98 | 92.17 | 19.91 | 13.50 | 19.88 |
Maximum of Months | 502.00 | 26.27 | 483.17 | 24.75 | 470.50 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.54 | 502.00 | 19.54 | 502.00 | 19.54 |
February | 454.00 | 19.77 | 450.00 | 19.76 | 450.00 | 19.76 |
March | 514.00 | 20.26 | 446.50 | 20.18 | 446.50 | 20.15 |
April | 478.83 | 21.09 | 228.00 | 20.74 | 227.33 | 20.56 |
May | 274.17 | 22.64 | 146.50 | 23.05 | 19.33 | 22.94 |
June | 116.83 | 23.37 | 278.83 | 23.98 | 14.00 | 24.03 |
July | 81.00 | 24.46 | 427.67 | 24.34 | 48.33 | 24.45 |
August | 125.00 | 22.93 | 324.83 | 23.79 | 7.67 | 23.80 |
September | 383.50 | 22.34 | 57.33 | 22.48 | 16.50 | 22.46 |
October | 502.00 | 20.76 | 212.83 | 20.47 | 212.83 | 20.30 |
November | 489.00 | 19.90 | 424.17 | 19.81 | 424.17 | 19.78 |
December | 497.00 | 19.59 | 497.00 | 19.59 | 497.00 | 19.59 |
Annual Sum or Average | 4417.33 | 20.72 | 3995.67 | 20.91 | 2865.67 | 20.66 |
Minimum of Months | 81.00 | 19.54 | 57.33 | 19.54 | 7.67 | 19.54 |
Maximum of Months | 514.00 | 24.46 | 502.00 | 24.34 | 502.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 502.00 | 19.72 | 502.00 | 19.72 |
February | 454.00 | 19.97 | 410.17 | 19.88 | 410.17 | 19.85 |
March | 501.33 | 20.85 | 343.83 | 20.57 | 343.83 | 20.46 |
April | 381.17 | 21.71 | 157.50 | 21.39 | 127.83 | 21.09 |
May | 162.50 | 23.15 | 226.83 | 23.96 | 9.00 | 23.98 |
June | 81.50 | 24.50 | 375.83 | 24.39 | 31.33 | 24.54 |
July | 85.33 | 25.57 | 453.67 | 24.63 | 64.83 | 24.82 |
August | 95.33 | 24.36 | 403.67 | 24.35 | 39.83 | 24.50 |
September | 260.33 | 22.56 | 138.83 | 23.17 | 17.67 | 23.19 |
October | 454.67 | 21.03 | 188.00 | 20.79 | 173.67 | 20.58 |
November | 489.00 | 20.05 | 388.33 | 19.88 | 388.33 | 19.82 |
December | 497.00 | 19.73 | 495.50 | 19.73 | 495.50 | 19.73 |
Annual Sum or Average | 3964.17 | 20.94 | 4084.17 | 21.30 | 2604.00 | 21.03 |
Minimum of Months | 81.50 | 19.72 | 138.83 | 19.72 | 9.00 | 19.72 |
Maximum of Months | 502.00 | 25.57 | 502.00 | 24.63 | 502.00 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.67 | 20.10 | 401.00 | 19.85 | 401.00 | 19.76 |
February | 402.33 | 20.60 | 297.83 | 20.31 | 282.50 | 20.14 |
March | 426.17 | 21.03 | 309.17 | 20.92 | 273.83 | 20.74 |
April | 361.67 | 21.63 | 199.17 | 21.52 | 144.83 | 21.26 |
May | 186.00 | 22.74 | 215.17 | 23.49 | 20.33 | 23.42 |
June | 128.33 | 23.59 | 319.83 | 24.11 | 25.33 | 24.22 |
July | 104.00 | 24.81 | 424.50 | 24.52 | 61.00 | 24.69 |
August | 106.67 | 24.01 | 387.67 | 24.27 | 33.67 | 24.41 |
September | 259.17 | 22.89 | 186.17 | 23.58 | 35.00 | 23.73 |
October | 415.17 | 21.37 | 210.17 | 21.42 | 152.17 | 21.21 |
November | 454.50 | 20.40 | 309.67 | 20.15 | 296.67 | 20.00 |
December | 488.33 | 20.04 | 434.83 | 19.88 | 434.83 | 19.82 |
Annual Sum or Average | 3815.00 | 21.24 | 3695.17 | 21.58 | 2161.17 | 21.29 |
Minimum of Months | 104.00 | 20.04 | 186.17 | 19.85 | 20.33 | 19.76 |
Maximum of Months | 488.33 | 24.81 | 434.83 | 24.52 | 434.83 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 477.83 | 19.77 | 477.83 | 19.75 |
February | 445.67 | 20.23 | 371.50 | 20.06 | 371.50 | 20.00 |
March | 477.17 | 20.80 | 334.33 | 20.61 | 321.17 | 20.49 |
April | 398.33 | 21.67 | 186.83 | 21.48 | 145.33 | 21.23 |
May | 182.50 | 23.08 | 228.50 | 23.80 | 21.17 | 23.84 |
June | 107.83 | 24.02 | 353.17 | 24.29 | 34.83 | 24.41 |
July | 95.67 | 25.47 | 452.17 | 24.69 | 74.67 | 24.86 |
August | 77.83 | 24.31 | 416.67 | 24.33 | 28.50 | 24.45 |
September | 263.17 | 22.77 | 139.50 | 23.36 | 17.33 | 23.45 |
October | 451.33 | 21.32 | 167.00 | 21.14 | 139.83 | 20.92 |
November | 488.83 | 20.28 | 349.50 | 20.04 | 349.50 | 19.94 |
December | 497.00 | 19.81 | 479.33 | 19.78 | 479.33 | 19.77 |
Annual Sum or Average | 3987.33 | 21.07 | 3956.33 | 21.42 | 2461.00 | 21.16 |
Minimum of Months | 77.83 | 19.81 | 139.50 | 19.77 | 17.33 | 19.75 |
Maximum of Months | 502.00 | 25.47 | 479.33 | 24.69 | 479.33 | 24.86 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 25.95 | 247.00 | 26.98 | 0.00 | 26.98 |
February | 0.00 | 0.00 | 428.83 | 27.00 | 0.00 | 27.00 |
March | 6.67 | 27.00 | 514.00 | 27.00 | 6.67 | 27.00 |
April | 21.67 | 27.24 | 485.00 | 27.02 | 21.67 | 27.03 |
May | 15.67 | 27.00 | 508.00 | 27.00 | 15.67 | 27.00 |
June | 54.67 | 27.00 | 496.00 | 27.00 | 54.67 | 27.00 |
July | 198.50 | 27.00 | 497.00 | 27.00 | 198.50 | 27.00 |
August | 270.33 | 27.00 | 514.00 | 27.00 | 270.33 | 27.00 |
September | 17.67 | 27.00 | 485.00 | 27.00 | 17.67 | 27.00 |
October | 8.17 | 27.00 | 502.00 | 27.00 | 8.17 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 596.83 | 27.00 | 5662.83 | 27.00 | 593.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 247.00 | 26.98 | 0.00 | 26.98 |
Maximum of Months | 270.33 | 27.24 | 514.00 | 27.02 | 270.33 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 341.67 | 25.29 | 38.67 | 25.34 | 8.83 | 25.27 |
February | 28.50 | 27.00 | 115.67 | 27.00 | 0.00 | 27.00 |
March | 1.67 | 27.00 | 329.67 | 27.00 | 0.33 | 27.00 |
April | 4.83 | 27.35 | 475.67 | 27.01 | 4.83 | 27.01 |
May | 10.00 | 27.00 | 508.00 | 27.00 | 10.00 | 27.00 |
June | 16.67 | 27.00 | 496.00 | 27.00 | 16.67 | 27.00 |
July | 48.67 | 27.00 | 497.00 | 27.00 | 48.67 | 27.00 |
August | 46.00 | 27.00 | 514.00 | 27.00 | 46.00 | 27.00 |
September | 9.17 | 27.00 | 485.00 | 27.00 | 9.17 | 27.00 |
October | 1.67 | 27.00 | 502.00 | 27.00 | 1.67 | 27.00 |
November | 12.83 | 27.00 | 325.50 | 27.00 | 0.00 | 27.00 |
December | 47.83 | 27.00 | 96.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 569.50 | 25.97 | 4384.00 | 26.87 | 146.17 | 26.87 |
Minimum of Months | 1.67 | 25.29 | 38.67 | 25.34 | 0.00 | 25.27 |
Maximum of Months | 341.67 | 27.35 | 514.00 | 27.01 | 48.67 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.83 | 24.43 | 94.50 | 24.19 | 78.33 | 23.94 |
February | 104.00 | 26.95 | 71.83 | 26.97 | 0.00 | 26.97 |
March | 44.50 | 27.00 | 210.50 | 27.00 | 0.00 | 27.00 |
April | 9.00 | 27.12 | 389.17 | 27.01 | 4.17 | 27.01 |
May | 14.50 | 27.00 | 501.33 | 27.00 | 14.50 | 27.00 |
June | 29.83 | 27.00 | 496.00 | 27.00 | 29.83 | 27.00 |
July | 72.67 | 27.00 | 497.00 | 27.00 | 72.67 | 27.00 |
August | 62.50 | 27.00 | 514.00 | 27.00 | 62.50 | 27.00 |
September | 9.67 | 27.00 | 485.00 | 27.00 | 9.67 | 27.00 |
October | 1.17 | 27.00 | 432.83 | 27.00 | 1.17 | 27.00 |
November | 65.33 | 27.00 | 192.67 | 27.00 | 0.00 | 27.00 |
December | 109.67 | 27.00 | 47.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 960.67 | 25.83 | 3931.83 | 26.69 | 272.83 | 26.64 |
Minimum of Months | 1.17 | 24.43 | 47.00 | 24.19 | 0.00 | 23.94 |
Maximum of Months | 437.83 | 27.12 | 514.00 | 27.01 | 78.33 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 27.00 | 502.00 | 27.00 | 0.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 498.67 | 27.00 | 508.00 | 27.00 | 498.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.23 | 497.00 | 27.23 | 497.00 | 27.23 |
August | 514.00 | 27.67 | 514.00 | 27.67 | 514.00 | 27.67 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5432.50 | 27.08 | 5943.00 | 27.08 | 5432.50 | 27.08 |
Minimum of Months | 0.83 | 27.00 | 454.00 | 27.00 | 0.83 | 27.00 |
Maximum of Months | 514.00 | 27.67 | 514.00 | 27.67 | 514.00 | 27.67 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.96467 | 11.06832 | 0.54886 | 11.46643 |
February | 454.00000 | 27.00000 | 11.53368 | 0.65867 | 14.26277 |
March | 514.00000 | 26.99999 | 14.98844 | 0.76320 | 17.39756 |
April | 485.00000 | 27.01133 | 18.06146 | 0.86567 | 20.91177 |
May | 508.00000 | 27.00024 | 29.11693 | 0.21717 | 6.16024 |
June | 496.00000 | 27.00086 | 34.59577 | 0.32180 | 7.25353 |
July | 497.00000 | 27.00071 | 36.31130 | 0.39816 | 8.38195 |
August | 514.00000 | 27.00066 | 35.62411 | 0.41935 | 8.74898 |
September | 485.00000 | 27.00027 | 32.69267 | 0.22962 | 6.22012 |
October | 502.00000 | 27.00003 | 27.17424 | 0.86147 | 20.74865 |
November | 489.00000 | 27.00002 | 17.95253 | 0.78000 | 17.94460 |
December | 497.00000 | 27.00000 | 11.56533 | 0.70380 | 15.52209 |
Annual Sum or Average | 5943.00000 | 26.99817 | 23.48797 | 0.56286 | 12.89381 |
Minimum of Months | 454.00000 | 26.96467 | 11.06832 | 0.21717 | 6.16024 |
Maximum of Months | 514.00000 | 27.01133 | 36.31130 | 0.86567 | 20.91177 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.75925 | 10.96610 | 0.18543 | 7.06052 |
February | 454.00000 | 27.00000 | 11.51980 | 0.48597 | 10.13999 |
March | 514.00000 | 27.00000 | 14.97627 | 0.59133 | 12.58826 |
April | 485.00000 | 27.00544 | 18.05234 | 0.71697 | 16.01926 |
May | 508.00000 | 27.00021 | 29.12379 | 0.14843 | 5.73905 |
June | 496.00000 | 27.00084 | 34.62414 | 0.23756 | 6.32555 |
July | 497.00000 | 27.00071 | 36.32602 | 0.29725 | 6.94495 |
August | 514.00000 | 27.00032 | 35.62587 | 0.28432 | 6.80026 |
September | 485.00000 | 27.00022 | 32.74306 | 0.14297 | 5.60704 |
October | 502.00000 | 27.00003 | 27.15785 | 0.74110 | 16.73320 |
November | 489.00000 | 27.00002 | 17.92731 | 0.58612 | 12.45123 |
December | 497.00000 | 27.00000 | 11.54410 | 0.46665 | 9.71017 |
Annual Sum or Average | 5943.00000 | 26.89584 | 23.47970 | 0.40592 | 9.66206 |
Minimum of Months | 454.00000 | 25.75925 | 10.96610 | 0.14297 | 5.60704 |
Maximum of Months | 514.00000 | 27.00544 | 36.32602 | 0.74110 | 16.73320 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.72780 | 10.99711 | -0.0574 | 7.75903 |
February | 454.00000 | 26.98786 | 11.52223 | 0.42198 | 9.06182 |
March | 514.00000 | 27.00000 | 14.98071 | 0.52004 | 11.01704 |
April | 485.00000 | 27.00359 | 18.05802 | 0.65095 | 14.28468 |
May | 508.00000 | 26.99904 | 29.12912 | 0.11864 | 5.81242 |
June | 496.00000 | 27.00085 | 34.64263 | 0.22839 | 6.37082 |
July | 497.00000 | 27.00073 | 36.33910 | 0.29459 | 7.00895 |
August | 514.00000 | 27.00035 | 35.64499 | 0.27273 | 6.75927 |
September | 485.00000 | 27.00021 | 32.80591 | 0.09289 | 5.51994 |
October | 502.00000 | 27.00003 | 27.17556 | 0.65988 | 14.45119 |
November | 489.00000 | 27.00002 | 17.94142 | 0.50615 | 10.70650 |
December | 497.00000 | 27.00000 | 11.55178 | 0.40931 | 8.75644 |
Annual Sum or Average | 5943.00000 | 26.80753 | 23.49652 | 0.34211 | 8.94992 |
Minimum of Months | 454.00000 | 24.72780 | 10.99711 | -0.0574 | 5.51994 |
Maximum of Months | 514.00000 | 27.00359 | 36.33910 | 0.65988 | 14.45119 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99997 | 30.00070 | 0.95383 | 24.24177 |
February | 454.00000 | 27.00037 | 29.77124 | 1.15937 | 33.29652 |
March | 514.00000 | 27.00016 | 25.62399 | 1.28791 | 39.65534 |
April | 485.00000 | 27.00024 | 21.31215 | 1.40892 | 45.99628 |
May | 508.00000 | 27.00020 | 31.75025 | 0.48187 | 9.92136 |
June | 496.00000 | 27.00174 | 39.22978 | 0.77458 | 17.78783 |
July | 497.00000 | 27.23228 | 41.58263 | 1.07996 | 30.01773 |
August | 514.00000 | 27.66801 | 36.74548 | 1.35955 | 43.19215 |
September | 485.00000 | 26.99998 | 33.77409 | 0.53811 | 11.22299 |
October | 502.00000 | 27.00028 | 30.06559 | 1.22736 | 36.60030 |
November | 489.00000 | 27.00030 | 25.87211 | 1.31619 | 41.11361 |
December | 497.00000 | 27.00018 | 22.36292 | 1.39021 | 44.99520 |
Annual Sum or Average | 5943.00000 | 27.07748 | 30.70228 | 1.08139 | 31.50649 |
Minimum of Months | 454.00000 | 26.99997 | 21.31215 | 0.48187 | 9.92136 |
Maximum of Months | 514.00000 | 27.66801 | 41.58263 | 1.40892 | 45.99628 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.68646 | 14.57426 | 0.06290 | 6.07594 |
February | 454.00000 | 24.21261 | 13.17781 | 0.19155 | 6.08833 |
March | 514.00000 | 24.30433 | 15.60863 | 0.24266 | 6.40658 |
April | 485.00000 | 24.43214 | 17.04423 | 0.29510 | 7.21413 |
May | 508.00000 | 24.44946 | 32.17679 | -0.4511 | 10.19493 |
June | 496.00000 | 24.41870 | 47.36436 | -0.3406 | 8.40979 |
July | 497.00000 | 24.58112 | 55.37854 | -0.2232 | 7.43635 |
August | 514.00000 | 24.45694 | 52.98881 | -0.2715 | 7.46538 |
September | 485.00000 | 24.51009 | 37.16930 | -0.3813 | 9.23663 |
October | 502.00000 | 24.53262 | 27.43117 | 0.40146 | 9.05468 |
November | 489.00000 | 24.47872 | 17.99109 | 0.30922 | 7.39744 |
December | 497.00000 | 24.20066 | 13.02545 | 0.19436 | 6.28771 |
Annual Sum or Average | 5943.00000 | 24.35561 | 28.81627 | 0.00037 | 7.61517 |
Minimum of Months | 454.00000 | 23.68646 | 13.02545 | -0.4511 | 6.07594 |
Maximum of Months | 514.00000 | 24.58112 | 55.37854 | 0.40146 | 10.19493 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.29091 | 16.91757 | -0.0299 | 5.72052 |
February | 454.00000 | 23.90594 | 16.70915 | 0.13874 | 5.60350 |
March | 514.00000 | 24.12885 | 18.42676 | 0.22832 | 6.20448 |
April | 485.00000 | 24.29541 | 18.58683 | 0.29501 | 7.04714 |
May | 508.00000 | 24.25379 | 32.94217 | -0.4829 | 10.40816 |
June | 496.00000 | 24.23718 | 45.79483 | -0.3787 | 8.39517 |
July | 497.00000 | 24.27350 | 52.42431 | -0.3075 | 7.27751 |
August | 514.00000 | 24.22333 | 51.58947 | -0.3246 | 7.43430 |
September | 485.00000 | 24.29062 | 38.77252 | -0.4336 | 9.50224 |
October | 502.00000 | 24.31073 | 29.72499 | 0.36530 | 8.05966 |
November | 489.00000 | 24.27226 | 21.31364 | 0.27844 | 6.84490 |
December | 497.00000 | 24.03420 | 16.79458 | 0.16821 | 5.76923 |
Annual Sum or Average | 5943.00000 | 24.12707 | 30.13313 | -0.0423 | 7.36684 |
Minimum of Months | 454.00000 | 23.29091 | 16.70915 | -0.4829 | 5.60350 |
Maximum of Months | 514.00000 | 24.31073 | 52.42431 | 0.36530 | 10.40816 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.14821 | 17.04239 | -0.5704 | 13.58466 |
February | 454.00000 | 21.85050 | 19.16232 | -0.3750 | 9.12838 |
March | 514.00000 | 22.75971 | 22.37521 | -0.1228 | 6.35735 |
April | 485.00000 | 23.68375 | 21.81473 | 0.11843 | 5.66130 |
May | 508.00000 | 24.13660 | 33.87200 | -0.5525 | 12.06277 |
June | 496.00000 | 24.14805 | 46.65645 | -0.4426 | 9.44787 |
July | 497.00000 | 24.24605 | 53.36270 | -0.3584 | 8.01604 |
August | 514.00000 | 24.14612 | 53.09996 | -0.3976 | 8.55910 |
September | 485.00000 | 24.07358 | 40.03623 | -0.5366 | 11.46300 |
October | 502.00000 | 23.66182 | 33.14881 | 0.18806 | 6.12194 |
November | 489.00000 | 22.71787 | 26.04730 | -0.1178 | 6.64667 |
December | 497.00000 | 21.37462 | 19.21159 | -0.4951 | 11.48222 |
Annual Sum or Average | 5943.00000 | 23.17146 | 32.28046 | -0.3053 | 9.04665 |
Minimum of Months | 454.00000 | 21.14821 | 17.04239 | -0.5704 | 5.66130 |
Maximum of Months | 514.00000 | 24.24605 | 53.36270 | 0.18806 | 13.58466 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31706 | 17.54368 | -0.8111 | 21.51260 |
February | 454.00000 | 20.70784 | 19.64596 | -0.6860 | 17.33023 |
March | 514.00000 | 21.38781 | 23.88131 | -0.4767 | 11.91259 |
April | 485.00000 | 22.53514 | 23.66859 | -0.1709 | 7.66640 |
May | 508.00000 | 23.85356 | 34.43212 | -0.6588 | 15.84619 |
June | 496.00000 | 24.01598 | 47.23991 | -0.4834 | 10.57763 |
July | 497.00000 | 24.17922 | 53.68105 | -0.3755 | 8.42078 |
August | 514.00000 | 24.05274 | 53.73198 | -0.4309 | 9.28150 |
September | 485.00000 | 23.64362 | 41.79236 | -0.7013 | 16.41414 |
October | 502.00000 | 22.22666 | 37.16455 | -0.1699 | 7.50404 |
November | 489.00000 | 21.08217 | 27.43607 | -0.5344 | 13.86578 |
December | 497.00000 | 20.39556 | 19.66156 | -0.7722 | 20.22580 |
Annual Sum or Average | 5943.00000 | 22.37991 | 33.45358 | -0.5216 | 13.34699 |
Minimum of Months | 454.00000 | 20.31706 | 17.54368 | -0.8111 | 7.50404 |
Maximum of Months | 514.00000 | 24.17922 | 53.73198 | -0.1699 | 21.51260 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.53263 | 16.54572 | -0.7394 | 18.04929 |
February | 454.00000 | 21.25795 | 17.14435 | -0.5162 | 11.79630 |
March | 514.00000 | 22.16535 | 19.36136 | -0.2655 | 7.94586 |
April | 485.00000 | 23.48978 | 18.74583 | 0.07184 | 5.93718 |
May | 508.00000 | 24.11605 | 32.06735 | -0.5263 | 11.88253 |
June | 496.00000 | 24.26427 | 44.70506 | -0.3368 | 8.05425 |
July | 497.00000 | 24.38110 | 51.36546 | -0.2349 | 7.00084 |
August | 514.00000 | 24.21790 | 50.86982 | -0.3250 | 7.71766 |
September | 485.00000 | 23.96650 | 38.65116 | -0.5714 | 12.90062 |
October | 502.00000 | 23.37194 | 29.74999 | 0.10224 | 5.90201 |
November | 489.00000 | 22.31362 | 22.18437 | -0.2120 | 7.44123 |
December | 497.00000 | 20.90191 | 17.16750 | -0.6031 | 14.15533 |
Annual Sum or Average | 5943.00000 | 22.92639 | 30.00729 | -0.3457 | 9.88576 |
Minimum of Months | 454.00000 | 20.53263 | 16.54572 | -0.7394 | 5.90201 |
Maximum of Months | 514.00000 | 24.38110 | 51.36546 | 0.10224 | 18.04929 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.65958 | 16.51459 | -0.7005 | 17.07552 |
February | 454.00000 | 21.64944 | 16.85539 | -0.4169 | 10.58296 |
March | 514.00000 | 22.49544 | 18.82272 | -0.1684 | 7.96274 |
April | 485.00000 | 23.58973 | 18.10985 | 0.14884 | 7.18713 |
May | 508.00000 | 24.29065 | 31.59656 | -0.3911 | 10.19747 |
June | 496.00000 | 24.32794 | 44.36896 | -0.2270 | 7.91780 |
July | 497.00000 | 24.39692 | 51.05423 | -0.1403 | 6.99358 |
August | 514.00000 | 24.25807 | 50.71829 | -0.2571 | 8.13370 |
September | 485.00000 | 24.07699 | 38.16668 | -0.4789 | 11.98768 |
October | 502.00000 | 23.40352 | 29.58364 | 0.12232 | 6.78122 |
November | 489.00000 | 22.20993 | 22.29977 | -0.2340 | 7.98825 |
December | 497.00000 | 20.83916 | 17.29739 | -0.6241 | 14.64489 |
Annual Sum or Average | 5943.00000 | 23.02667 | 29.74344 | -0.2800 | 9.77995 |
Minimum of Months | 454.00000 | 20.65958 | 16.51459 | -0.7005 | 6.78122 |
Maximum of Months | 514.00000 | 24.39692 | 51.05423 | 0.14884 | 17.07552 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26080 | 15.78874 | -0.5256 | 15.11977 |
February | 454.00000 | 22.24722 | 15.73065 | -0.2369 | 10.59347 |
March | 514.00000 | 22.73464 | 18.09129 | -0.0884 | 8.98581 |
April | 485.00000 | 23.54852 | 17.99003 | 0.14606 | 7.80983 |
May | 508.00000 | 24.15240 | 31.77004 | -0.4539 | 11.46839 |
June | 496.00000 | 24.26019 | 44.57849 | -0.3013 | 8.26511 |
July | 497.00000 | 24.41464 | 51.03628 | -0.1660 | 7.16747 |
August | 514.00000 | 24.30279 | 50.40657 | -0.2147 | 7.72774 |
September | 485.00000 | 24.13720 | 37.88659 | -0.4202 | 11.92521 |
October | 502.00000 | 23.42676 | 29.12196 | 0.15680 | 8.20798 |
November | 489.00000 | 22.43344 | 21.63079 | -0.1630 | 8.80438 |
December | 497.00000 | 21.40422 | 16.76513 | -0.4739 | 13.03163 |
Annual Sum or Average | 5943.00000 | 23.20084 | 29.36561 | -0.2287 | 9.91956 |
Minimum of Months | 454.00000 | 21.26080 | 15.73065 | -0.5256 | 7.16747 |
Maximum of Months | 514.00000 | 24.41464 | 51.03628 | 0.15680 | 15.11977 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26431 | 15.87568 | -0.5234 | 12.75449 |
February | 454.00000 | 22.70536 | 15.41227 | -0.1381 | 7.61914 |
March | 514.00000 | 23.78060 | 16.82016 | 0.17001 | 6.93925 |
April | 485.00000 | 24.41093 | 16.67358 | 0.40817 | 9.52075 |
May | 508.00000 | 24.43684 | 31.01861 | -0.2792 | 8.70087 |
June | 496.00000 | 24.50414 | 43.72299 | -0.1015 | 7.02688 |
July | 497.00000 | 24.69545 | 50.01086 | 0.06457 | 7.63145 |
August | 514.00000 | 24.55110 | 49.42860 | -0.0011 | 7.15921 |
September | 485.00000 | 24.41172 | 37.09897 | -0.3175 | 9.09830 |
October | 502.00000 | 24.21049 | 27.36349 | 0.35125 | 8.28969 |
November | 489.00000 | 23.78012 | 19.71879 | 0.15872 | 6.41301 |
December | 497.00000 | 22.84919 | 15.34147 | -0.1179 | 6.97875 |
Annual Sum or Average | 5943.00000 | 23.80686 | 28.33610 | -0.0268 | 8.17814 |
Minimum of Months | 454.00000 | 21.26431 | 15.34147 | -0.5234 | 6.41301 |
Maximum of Months | 514.00000 | 24.69545 | 50.01086 | 0.40817 | 12.75449 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68647 | 15.42054 | -1.0562 | 30.75443 |
February | 454.00000 | 19.99503 | 17.95368 | -0.9128 | 24.79658 |
March | 514.00000 | 20.63681 | 21.75426 | -0.6852 | 16.90426 |
April | 485.00000 | 21.87288 | 21.72898 | -0.3201 | 9.44759 |
May | 508.00000 | 23.75980 | 32.95038 | -0.6650 | 16.53806 |
June | 496.00000 | 24.12695 | 45.40265 | -0.4086 | 9.34830 |
July | 497.00000 | 24.31551 | 52.49268 | -0.2852 | 7.64359 |
August | 514.00000 | 23.99969 | 52.43266 | -0.4356 | 9.65024 |
September | 485.00000 | 23.33283 | 40.59354 | -0.7989 | 20.31163 |
October | 502.00000 | 21.69968 | 33.24845 | -0.2977 | 8.52395 |
November | 489.00000 | 20.34748 | 25.04845 | -0.7276 | 18.82702 |
December | 497.00000 | 19.75773 | 17.73283 | -1.0099 | 28.91938 |
Annual Sum or Average | 5943.00000 | 21.97758 | 31.52458 | -0.6315 | 16.73800 |
Minimum of Months | 454.00000 | 19.68647 | 15.42054 | -1.0562 | 7.64359 |
Maximum of Months | 514.00000 | 24.31551 | 52.49268 | -0.2852 | 30.75443 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.61608 | 15.05807 | -1.0552 | 30.89434 |
February | 385.00000 | 20.11652 | 17.35538 | -0.8516 | 22.94369 |
March | 433.00000 | 21.30007 | 20.33040 | -0.5021 | 13.63641 |
April | 410.00000 | 22.74082 | 19.69337 | -0.0701 | 9.02762 |
May | 430.00000 | 24.20484 | 31.54863 | -0.4420 | 12.29525 |
June | 418.00000 | 24.34848 | 44.43526 | -0.2329 | 8.70315 |
July | 422.00000 | 24.52833 | 51.38479 | -0.1112 | 7.54936 |
August | 433.00000 | 24.28786 | 51.09646 | -0.2685 | 8.98258 |
September | 410.00000 | 23.72157 | 39.05429 | -0.6192 | 16.58584 |
October | 427.00000 | 22.17050 | 31.51725 | -0.1821 | 8.78789 |
November | 417.00000 | 20.44368 | 24.03161 | -0.6989 | 18.51380 |
December | 422.00000 | 19.63920 | 17.30452 | -1.0272 | 29.75934 |
Annual Sum or Average | 5034.00000 | 22.27381 | 30.34004 | -0.5029 | 15.58653 |
Minimum of Months | 385.00000 | 19.61608 | 15.05807 | -1.0552 | 7.54936 |
Maximum of Months | 433.00000 | 24.52833 | 51.38479 | -0.0701 | 30.89434 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52458 | 14.99772 | -0.7485 | 22.61318 |
February | 454.00000 | 21.48026 | 16.41527 | -0.4467 | 15.76824 |
March | 514.00000 | 22.07759 | 19.81531 | -0.2607 | 12.15259 |
April | 485.00000 | 22.88292 | 19.72737 | -0.0092 | 9.30871 |
May | 508.00000 | 23.97479 | 32.21528 | -0.5149 | 13.68953 |
June | 496.00000 | 24.14851 | 45.09879 | -0.3500 | 9.42907 |
July | 497.00000 | 24.38962 | 51.92874 | -0.1883 | 7.71051 |
August | 514.00000 | 24.21065 | 51.42668 | -0.2642 | 8.79784 |
September | 485.00000 | 23.89473 | 38.67230 | -0.4970 | 14.85956 |
October | 502.00000 | 22.75908 | 30.78968 | 0.00516 | 9.47610 |
November | 489.00000 | 21.37231 | 23.63502 | -0.4322 | 14.09058 |
December | 497.00000 | 20.42303 | 17.40720 | -0.7733 | 22.04220 |
Annual Sum or Average | 5943.00000 | 22.68880 | 30.30992 | -0.3728 | 13.30409 |
Minimum of Months | 454.00000 | 20.42303 | 14.99772 | -0.7733 | 7.71051 |
Maximum of Months | 514.00000 | 24.38962 | 51.92874 | 0.00516 | 22.61318 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98170 | 15.38772 | -0.9424 | 26.63362 |
February | 454.00000 | 20.61999 | 17.34931 | -0.7104 | 19.00980 |
March | 514.00000 | 21.48469 | 20.58227 | -0.4332 | 12.90722 |
April | 485.00000 | 22.75041 | 20.19021 | -0.0562 | 8.85049 |
May | 508.00000 | 24.09525 | 31.98538 | -0.4436 | 12.41412 |
June | 496.00000 | 24.27350 | 44.76001 | -0.2582 | 8.40613 |
July | 497.00000 | 24.51930 | 51.53721 | -0.0952 | 7.61846 |
August | 514.00000 | 24.27566 | 51.24666 | -0.2346 | 8.22875 |
September | 485.00000 | 23.83021 | 39.08069 | -0.5659 | 14.87862 |
October | 502.00000 | 22.43614 | 31.52019 | -0.1027 | 7.99799 |
November | 489.00000 | 20.81836 | 24.43219 | -0.5892 | 15.38358 |
December | 497.00000 | 19.99239 | 17.63560 | -0.9085 | 24.89879 |
Annual Sum or Average | 5943.00000 | 22.43819 | 30.60181 | -0.4430 | 13.88987 |
Minimum of Months | 454.00000 | 19.98170 | 15.38772 | -0.9424 | 7.61846 |
Maximum of Months | 514.00000 | 24.51930 | 51.53721 | -0.0562 | 26.63362 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.54276 | 15.04801 | -1.1436 | 34.56103 |
February | 454.00000 | 19.76919 | 17.54503 | -1.0236 | 29.59161 |
March | 514.00000 | 20.26022 | 22.22684 | -0.8280 | 21.86896 |
April | 485.00000 | 21.13007 | 22.58414 | -0.5225 | 14.22139 |
May | 508.00000 | 23.34472 | 33.38777 | -0.8068 | 22.58804 |
June | 496.00000 | 23.93726 | 46.02328 | -0.4676 | 11.32752 |
July | 497.00000 | 24.18954 | 52.95205 | -0.3212 | 8.58765 |
August | 514.00000 | 23.79158 | 53.23897 | -0.5027 | 11.74370 |
September | 485.00000 | 22.68410 | 42.23438 | -1.0216 | 29.70834 |
October | 502.00000 | 20.76404 | 34.95192 | -0.5534 | 14.31576 |
November | 489.00000 | 19.89791 | 25.79246 | -0.8926 | 25.08081 |
December | 497.00000 | 19.59427 | 17.32431 | -1.1062 | 32.95296 |
Annual Sum or Average | 5943.00000 | 21.59252 | 32.07475 | -0.7634 | 21.29513 |
Minimum of Months | 454.00000 | 19.54276 | 15.04801 | -1.1436 | 8.58765 |
Maximum of Months | 514.00000 | 24.18954 | 53.23897 | -0.3212 | 34.56103 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72186 | 15.23551 | -1.0739 | 31.64115 |
February | 454.00000 | 19.97183 | 17.63158 | -0.9277 | 26.26623 |
March | 514.00000 | 20.92455 | 21.66942 | -0.6257 | 17.13533 |
April | 485.00000 | 22.22351 | 20.98452 | -0.2093 | 11.34813 |
May | 508.00000 | 23.97204 | 32.17107 | -0.5153 | 14.35181 |
June | 496.00000 | 24.18803 | 45.00971 | -0.2685 | 9.33626 |
July | 497.00000 | 24.37103 | 51.84494 | -0.1369 | 7.93108 |
August | 514.00000 | 24.14238 | 51.93030 | -0.3014 | 9.58605 |
September | 485.00000 | 23.32783 | 40.48938 | -0.7549 | 21.43833 |
October | 502.00000 | 21.34450 | 33.94775 | -0.4045 | 12.85422 |
November | 489.00000 | 20.04947 | 25.76708 | -0.8382 | 23.49866 |
December | 497.00000 | 19.72798 | 17.42708 | -1.0569 | 30.91575 |
Annual Sum or Average | 5943.00000 | 22.01511 | 31.30336 | -0.5899 | 17.93993 |
Minimum of Months | 454.00000 | 19.72186 | 15.23551 | -1.0739 | 7.93108 |
Maximum of Months | 514.00000 | 24.37103 | 51.93030 | -0.1369 | 31.64115 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24600 | 14.94320 | -0.8630 | 26.61852 |
February | 454.00000 | 20.98863 | 16.49974 | -0.6079 | 20.34360 |
March | 514.00000 | 21.60303 | 20.61434 | -0.4222 | 15.42797 |
April | 485.00000 | 22.26440 | 20.72807 | -0.1852 | 12.05183 |
May | 508.00000 | 23.70346 | 32.53555 | -0.6170 | 17.73066 |
June | 496.00000 | 23.98566 | 45.69554 | -0.4016 | 11.35381 |
July | 497.00000 | 24.28129 | 52.38527 | -0.2194 | 8.70734 |
August | 514.00000 | 24.08453 | 52.03647 | -0.3086 | 10.15910 |
September | 485.00000 | 23.50080 | 39.88778 | -0.6485 | 20.40974 |
October | 502.00000 | 21.88472 | 32.65360 | -0.2355 | 12.95072 |
November | 489.00000 | 20.65235 | 24.83299 | -0.6475 | 19.75828 |
December | 497.00000 | 20.11191 | 17.28313 | -0.8992 | 26.61986 |
Annual Sum or Average | 5943.00000 | 22.28818 | 30.97548 | -0.5036 | 16.80186 |
Minimum of Months | 454.00000 | 20.11191 | 14.94320 | -0.8992 | 8.70734 |
Maximum of Months | 514.00000 | 24.28129 | 52.38527 | -0.1852 | 26.61986 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82649 | 15.10467 | -1.0321 | 30.26981 |
February | 454.00000 | 20.30224 | 17.18257 | -0.8282 | 23.48053 |
March | 514.00000 | 21.04565 | 21.32420 | -0.5762 | 16.70168 |
April | 485.00000 | 22.09925 | 21.17122 | -0.2297 | 11.85181 |
May | 508.00000 | 23.83799 | 32.29423 | -0.5379 | 16.10870 |
June | 496.00000 | 24.14516 | 45.25247 | -0.2992 | 9.78079 |
July | 497.00000 | 24.44406 | 51.88759 | -0.1168 | 8.18670 |
August | 514.00000 | 24.17096 | 51.77706 | -0.2723 | 9.26483 |
September | 485.00000 | 23.40719 | 40.33853 | -0.7202 | 20.66964 |
October | 502.00000 | 21.61314 | 33.26119 | -0.3216 | 11.52580 |
November | 489.00000 | 20.27688 | 25.41409 | -0.7575 | 20.99176 |
December | 497.00000 | 19.80813 | 17.37031 | -1.0011 | 28.76776 |
Annual Sum or Average | 5943.00000 | 22.09764 | 31.16039 | -0.5553 | 17.23491 |
Minimum of Months | 454.00000 | 19.80813 | 15.10467 | -1.0321 | 8.18670 |
Maximum of Months | 514.00000 | 24.44406 | 51.88759 | -0.1168 | 30.26981 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.308436E+09 | 1083.05 | 27-JAN-13:07 | 114.42 | 0.138639E+10 | 0.00 | 0.169483E+10 | 0.69 | 4.51 | 19-JAN-10:50 | 0.00 | 0.00 |
February | 0.586622E+09 | 8753.52 | 28-FEB-15:20 | 160.92 | 0.263685E+10 | 0.00 | 0.322347E+10 | 1.08 | 4.51 | 06-FEB-12:40 | 0.00 | 0.00 |
March | 0.170723E+10 | 45804.54 | 31-MAR-15:50 | 207.25 | 0.788252E+10 | 0.00 | 0.958975E+10 | 1.25 | 5.62 | 31-MAR-15:50 | 0.00 | 0.00 |
April | 0.150753E+11 | 79373.74 | 13-APR-13:00 | 171.60 | 0.862949E+11 | 0.00 | 0.101370E+12 | 1.19 | 7.49 | 13-APR-13:00 | 0.00 | 0.00 |
May | 0.516722E+11 | 151922.84 | 24-MAY-12:10 | 266.97 | 0.348698E+12 | 0.00 | 0.400370E+12 | 2.12 | 7.95 | 10-MAY-15:00 | 0.00 | 0.00 |
June | 0.100769E+12 | 160946.96 | 29-JUN-18:40 | 411.34 | 0.707869E+12 | 0.00 | 0.808638E+12 | 3.65 | 7.95 | 08-JUN-11:50 | 0.00 | 0.00 |
July | 0.124697E+12 | 168266.97 | 05-JUL-10:10 | 527.35 | 0.884310E+12 | 0.00 | 0.100901E+13 | 4.47 | 8.11 | 05-JUL-13:50 | 0.00 | 0.00 |
August | 0.983689E+11 | 159166.08 | 08-AUG-16:40 | 507.87 | 0.674865E+12 | 0.00 | 0.773234E+12 | 4.07 | 7.94 | 22-AUG-15:30 | 0.00 | 0.00 |
September | 0.303085E+11 | 152639.99 | 01-SEP-09:00 | 221.23 | 0.187710E+12 | 0.00 | 0.218018E+12 | 1.65 | 7.94 | 07-SEP-13:05 | 0.00 | 0.00 |
October | 0.946326E+10 | 101492.15 | 19-OCT-15:00 | 110.60 | 0.573682E+11 | 0.00 | 0.668314E+11 | 0.75 | 7.84 | 19-OCT-15:00 | 0.00 | 0.00 |
November | 0.185677E+10 | 38751.55 | 17-NOV-13:30 | 145.61 | 0.832649E+10 | 0.00 | 0.101833E+11 | 0.91 | 4.51 | 09-NOV-14:50 | 0.00 | 0.00 |
December | 0.503168E+09 | 2508.92 | 18-DEC-16:20 | 180.86 | 0.226175E+10 | 0.00 | 0.276492E+10 | 1.09 | 4.51 | 18-DEC-15:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.435316E+12 | 3026.02 | 0.296961E+13 | 0.00 | 0.340492E+13 | 1.92 | 0.00 | 0.00 | ||||
Minimum of Months | 0.308436E+09 | 1083.05 | 110.60 | 0.138639E+10 | 0.00 | 0.169483E+10 | 0.69 | 4.51 | 0.00 | 0.00 | ||
Maximum of Months | 0.124697E+12 | 168266.97 | 527.35 | 0.884310E+12 | 0.00 | 0.100901E+13 | 4.47 | 8.11 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.728465E+10 | 112250.65 | 25-MAY-12:05 | 24.67 | 0.542344E+11 | 0.00 | 0.615191E+11 | 0.24 | 7.76 | 17-MAY-12:50 | 0.00 | 0.00 |
June | 0.223536E+11 | 143059.36 | 19-JUN-15:20 | 63.63 | 0.161727E+12 | 0.00 | 0.184081E+12 | 0.64 | 7.84 | 08-JUN-14:05 | 0.00 | 0.00 |
July | 0.349918E+11 | 168266.97 | 05-JUL-10:10 | 99.96 | 0.259026E+12 | 0.00 | 0.294017E+12 | 0.99 | 8.11 | 05-JUL-13:50 | 0.00 | 0.00 |
August | 0.238461E+11 | 149222.49 | 31-AUG-12:50 | 70.58 | 0.175836E+12 | 0.00 | 0.199682E+12 | 0.70 | 7.74 | 04-AUG-15:30 | 0.00 | 0.00 |
September | 0.224168E+10 | 103534.36 | 01-SEP-10:05 | 6.92 | 0.169266E+11 | 0.00 | 0.191683E+11 | 0.07 | 7.70 | 01-SEP-10:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.907179E+11 | 265.76 | 0.667749E+12 | 0.00 | 0.758467E+12 | 0.22 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.349918E+11 | 168266.97 | 99.96 | 0.259026E+12 | 0.00 | 0.294017E+12 | 0.99 | 8.11 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.261626E+09 | 744.00 | 429.50 | 20-JAN-16:20 | 26843.65 | 20-JAN-16:30 | 18.49 | 18.33 | 14.30 |
February | 0.136651E+10 | 672.00 | 1915.88 | 20-FEB-16:40 | 66103.23 | 08-FEB-17:00 | 19.08 | 18.33 | 14.30 |
March | 0.341612E+10 | 744.00 | 3958.97 | 26-MAR-16:00 | 138012.55 | 29-MAR-15:10 | 19.82 | 18.33 | 14.28 |
April | 0.166798E+11 | 720.00 | 43776.24 | 11-APR-13:50 | 635989.82 | 23-APR-16:01 | 21.22 | 18.57 | 14.27 |
May | 0.358837E+11 | 744.00 | 43776.24 | 02-MAY-14:40 | 239779.85 | 25-MAY-13:10 | 20.41 | 19.50 | 14.26 |
June | 0.687438E+11 | 720.00 | 43776.24 | 01-JUN-07:50 | 657699.19 | 30-JUN-02:65 | 24.56 | 21.61 | 14.29 |
July | 0.920230E+11 | 744.00 | 43776.24 | 01-JUL-08:00 | 707274.01 | 15-JUL-14:10 | 30.95 | 23.99 | 14.30 |
August | 0.985886E+11 | 744.00 | 43776.24 | 01-AUG-00:05 | 713893.05 | 08-AUG-15:10 | 31.76 | 22.99 | 14.30 |
September | 0.217289E+11 | 720.00 | 43776.24 | 01-SEP-00:05 | 207496.32 | 01-SEP-15:10 | 19.30 | 18.65 | 14.25 |
October | 0.788760E+10 | 744.00 | 43776.24 | 19-OCT-11:50 | 185290.02 | 19-OCT-15:10 | 19.47 | 18.38 | 14.25 |
November | 0.476615E+10 | 720.00 | 43776.24 | 01-NOV-11:50 | 214961.91 | 01-NOV-15:00 | 19.79 | 18.34 | 14.29 |
December | 0.294478E+10 | 744.00 | 1964.13 | 05-DEC-22:10 | 104721.73 | 08-DEC-16:00 | 20.11 | 18.33 | 14.30 |
Annual Sum or Average | 0.354291E+12 | 8760.00 | 22.11 | 19.63 | 14.28 | ||||
Minimum of Months | 0.261626E+09 | 672.00 | 429.50 | 26843.65 | 18.49 | 18.33 | 14.25 | ||
Maximum of Months | 0.985886E+11 | 744.00 | 43776.24 | 713893.05 | 31.76 | 23.99 | 14.30 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 210152.23 | 11-JAN-18:10 | 21.00 | 20.98 | 1.11 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 210993.09 | 08-FEB-16:00 | 20.92 | 20.90 | 1.24 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 315644.99 | 31-MAR-15:50 | 20.92 | 20.89 | 1.83 |
April | 65730543.16 | 49.65 | 2852.32 | 23-APR-15:52 | 681797.71 | 13-APR-13:00 | 21.15 | 20.97 | 8.10 |
May | 0.355875E+10 | 201.68 | 16173.46 | 16-MAY-12:05 | 1242283.82 | 16-MAY-13:20 | 21.99 | 21.34 | 18.40 |
June | 0.103129E+11 | 371.53 | 16173.46 | 06-JUN-09:40 | 1395624.11 | 20-JUN-04:12 | 23.25 | 21.92 | 30.88 |
July | 0.163923E+11 | 462.56 | 16173.46 | 03-JUL-07:20 | 1348673.30 | 05-JUL-15:35 | 23.68 | 22.08 | 37.29 |
August | 0.105765E+11 | 394.97 | 16173.46 | 01-AUG-05:06 | 1288112.96 | 04-AUG-15:00 | 22.86 | 21.62 | 34.92 |
September | 0.113662E+10 | 149.74 | 16173.46 | 01-SEP-08:20 | 1170147.78 | 07-SEP-13:10 | 21.60 | 21.23 | 15.26 |
October | 70633803.08 | 45.00 | 2668.82 | 19-OCT-14:40 | 908986.64 | 19-OCT-15:00 | 21.13 | 21.02 | 4.67 |
November | 4084035.29 | 5.75 | 340.94 | 01-NOV-12:50 | 214998.95 | 17-NOV-13:40 | 20.93 | 20.89 | 2.40 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 210157.54 | 02-DEC-12:13 | 20.94 | 20.92 | 1.25 |
Annual Sum or Average | 0.421176E+11 | 1680.89 | 21.70 | 21.23 | 13.20 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 210152.23 | 20.92 | 20.89 | 1.11 | ||
Maximum of Months | 0.163923E+11 | 462.56 | 16173.46 | 1395624.11 | 23.68 | 22.08 | 37.29 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.00 | 21.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.92 | 20.92 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.92 | 20.92 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.15 | 21.15 | 0.00 |
May | 0.123403E+10 | 21.42 | 16173.46 | 16-MAY-13:40 | 1027501.02 | 16-MAY-15:20 | 21.99 | 21.89 | 1.61 |
June | 0.451662E+10 | 78.59 | 16173.46 | 06-JUN-12:05 | 1177839.50 | 19-JUN-15:20 | 23.25 | 22.83 | 5.56 |
July | 0.771518E+10 | 132.64 | 16173.46 | 03-JUL-09:00 | 1348673.30 | 05-JUL-15:35 | 23.68 | 23.00 | 8.90 |
August | 0.465310E+10 | 79.92 | 16173.46 | 04-AUG-15:30 | 1194809.82 | 31-AUG-12:50 | 22.86 | 22.47 | 5.79 |
September | 0.402719E+09 | 6.92 | 16173.46 | 01-SEP-09:05 | 872977.91 | 01-SEP-09:05 | 21.60 | 21.57 | 0.55 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.13 | 21.13 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.93 | 20.93 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.94 | 20.94 | 0.00 |
Annual Sum or Average | 0.185217E+11 | 319.49 | 21.70 | 21.57 | 1.89 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 20.92 | 0.00 | ||
Maximum of Months | 0.771518E+10 | 132.64 | 16173.46 | 1348673.30 | 23.68 | 23.00 | 8.90 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.864682E+12 | 0.00 | 655.73 | 2367618.07 | 09-JAN-07:02 | 0.00 | 39.34 | 76.85 | 2.11 | 0.00 | 0.10 | 0.73 | 09-JAN-07:02 |
February | 0.378563E+12 | 0.00 | 550.03 | 2009106.97 | 14-FEB-07:03 | 0.00 | 35.57 | 73.63 | 0.95 | 0.00 | 0.05 | 0.62 | 14-FEB-07:03 |
March | 0.160705E+12 | 0.00 | 503.96 | 1719212.05 | 06-MAR-05:01 | 0.00 | 30.38 | 64.84 | 0.32 | 0.00 | 0.02 | 0.53 | 06-MAR-05:01 |
April | 0.291106E+11 | 0.00 | 278.07 | 1494343.54 | 04-APR-04:01 | 0.00 | 27.70 | 48.34 | 0.06 | 0.00 | 0.00 | 0.46 | 04-APR-04:01 |
May | 0.198732E+10 | 0.00 | 53.82 | 328564.25 | 31-MAY-09:10 | 0.00 | 27.41 | 31.36 | 0.00 | 0.00 | 0.00 | 0.10 | 31-MAY-09:10 |
June | 0.184950E+09 | 0.00 | 2.50 | 159180.68 | 09-JUN-09:40 | 0.00 | 27.98 | 28.17 | 0.00 | 0.00 | 0.00 | 0.05 | 09-JUN-09:40 |
July | 59406198.73 | 0.00 | 1.25 | 41131.57 | 08-JUL-11:30 | 0.00 | 27.29 | 27.39 | 0.00 | 0.00 | 0.00 | 0.01 | 08-JUL-11:30 |
August | 0.258515E+09 | 0.00 | 3.88 | 196317.08 | 17-AUG-13:20 | 0.00 | 26.97 | 27.25 | 0.00 | 0.00 | 0.00 | 0.06 | 17-AUG-13:20 |
September | 0.247316E+10 | 0.00 | 96.18 | 299668.82 | 27-SEP-13:10 | 0.00 | 26.31 | 33.74 | 0.00 | 0.00 | 0.00 | 0.09 | 27-SEP-13:10 |
October | 0.266355E+11 | 0.00 | 297.72 | 1282095.83 | 14-OCT-05:02 | 0.00 | 26.89 | 48.71 | 0.05 | 0.00 | 0.00 | 0.40 | 14-OCT-05:02 |
November | 0.158550E+12 | 0.00 | 497.50 | 1749813.65 | 27-NOV-06:01 | 0.00 | 30.42 | 65.15 | 0.33 | 0.00 | 0.02 | 0.54 | 27-NOV-06:01 |
December | 0.647206E+12 | 0.00 | 646.67 | 2123545.47 | 26-DEC-07:10 | 0.00 | 37.80 | 75.96 | 1.49 | 0.00 | 0.07 | 0.66 | 26-DEC-07:10 |
Annual Sum or Average | 0.227041E+13 | 0.00 | 3587.32 | 0.00 | 30.32 | 49.99 | 0.44 | 0.00 | 0.02 | ||||
Minimum of Months | 59406198.73 | 0.00 | 1.25 | 41131.57 | 0.00 | 26.31 | 27.25 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.864682E+12 | 0.00 | 655.73 | 2367618.07 | 0.00 | 39.34 | 76.85 | 2.11 | 0.00 | 0.10 | 0.73 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 18.49 | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.08 | 19.08 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.82 | 19.82 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.22 | 21.22 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.41 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 24.56 | 24.56 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 30.95 | 30.95 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 31.76 | 31.76 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 19.30 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.47 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.79 | 19.79 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.11 | 20.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.76 | 31.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7203143.71 | 0.00 | 42.27 | 7203143.71 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.41 | 27-JAN-13:07 | 4553.41 | 27-JAN-13:07 | 0.00 | 0.00 | 0.00 |
February | 0.571018E+09 | 0.00 | 90.36 | 0.571018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21938.44 | 28-FEB-15:40 | 21938.44 | 28-FEB-15:40 | 0.00 | 0.00 | 0.00 |
March | 0.111982E+10 | 0.00 | 120.40 | 0.111982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21503.13 | 23-MAR-15:20 | 21503.13 | 23-MAR-15:20 | 0.00 | 0.00 | 0.00 |
April | 0.685018E+10 | 0.00 | 108.93 | 0.685018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83635.20 | 23-APR-16:01 | 83635.20 | 23-APR-16:01 | 0.00 | 0.00 | 0.00 |
May | 0.338152E+11 | 0.00 | 240.23 | 0.331321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117798.79 | 26-MAY-11:00 | 104422.59 | 18-MAY-14:20 | 0.00 | 0.00 | 0.00 |
June | 0.786817E+11 | 0.00 | 396.13 | 0.634222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 212833.59 | 30-JUN-05:02 | 143346.23 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.109737E+12 | 0.00 | 508.74 | 0.831548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 240742.81 | 05-JUL-10:20 | 124876.39 | 24-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.850143E+11 | 0.00 | 482.51 | 0.647775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213341.11 | 31-AUG-12:50 | 124054.32 | 08-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.175228E+11 | 0.00 | 189.33 | 0.157105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129546.48 | 01-SEP-11:00 | 110277.99 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.515813E+10 | 0.00 | 86.53 | 0.515813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70225.25 | 19-OCT-15:00 | 70225.25 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.277345E+10 | 0.00 | 102.79 | 0.277345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41030.79 | 17-NOV-14:10 | 41030.79 | 17-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 21788093.76 | 0.00 | 97.52 | 21788093.76 | 0.00 | 0.00 | 0.00 | 0.00 | 4709.07 | 08-DEC-13:04 | 4709.07 | 08-DEC-13:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341272E+12 | 0.00 | 2465.74 | 0.276699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7203143.71 | 0.00 | 42.27 | 7203143.71 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.41 | 4553.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109737E+12 | 0.00 | 508.74 | 0.831548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 240742.81 | 143346.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 11711209.26 | 0.00 | 12.36 | 11711209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12652.93 | 21-JAN-15:02 | 12652.93 | 21-JAN-15:02 | 0.00 | 0.00 | 0.00 |
February | 0.206438E+09 | 0.00 | 47.03 | 0.206438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18598.76 | 28-FEB-15:20 | 18598.76 | 28-FEB-15:20 | 0.00 | 0.00 | 0.00 |
March | 0.406025E+10 | 0.00 | 92.99 | 0.406025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249983.75 | 31-MAR-15:40 | 249983.75 | 31-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.725900E+11 | 0.00 | 136.47 | 0.725900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 776081.70 | 23-APR-15:42 | 776081.70 | 23-APR-15:42 | 0.00 | 0.00 | 0.00 |
May | 0.309043E+12 | 0.00 | 249.86 | 0.302460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1118530.50 | 25-MAY-16:00 | 1021812.33 | 18-MAY-14:40 | 0.00 | 0.00 | 0.00 |
June | 0.665319E+12 | 0.00 | 368.40 | 0.541347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2171584.79 | 30-JUN-05:02 | 1312547.84 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.862259E+12 | 0.00 | 415.83 | 0.672090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2122421.42 | 05-JUL-10:25 | 1179947.89 | 23-JUL-16:01 | 0.00 | 0.00 | 0.00 |
August | 0.638476E+12 | 0.00 | 404.45 | 0.500143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1692368.16 | 31-AUG-12:50 | 1070539.24 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.162239E+12 | 0.00 | 193.41 | 0.148975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1195614.24 | 01-SEP-12:05 | 1022772.06 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.474152E+11 | 0.00 | 91.81 | 0.474152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 638076.68 | 19-OCT-15:00 | 638076.68 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.342402E+10 | 0.00 | 73.91 | 0.342402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130100.19 | 17-NOV-13:20 | 130100.19 | 17-NOV-13:20 | 0.00 | 0.00 | 0.00 |
December | 22881801.89 | 0.00 | 34.94 | 22881801.89 | 0.00 | 0.00 | 0.00 | 0.00 | 13282.80 | 08-DEC-15:02 | 13282.80 | 08-DEC-15:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276507E+13 | 0.00 | 2121.45 | 0.229275E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11711209.26 | 0.00 | 12.36 | 11711209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12652.93 | 12652.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.862259E+12 | 0.00 | 415.83 | 0.672090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2171584.79 | 1312547.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 265049.85 | 0.00 | 4.09 | 265049.85 | 0.00 | 0.00 | 0.00 | 0.00 | 60.77 | 19-JAN-12:10 | 60.77 | 19-JAN-12:10 | 0.00 | 0.00 | 0.00 |
February | 15230552.88 | 0.00 | 18.28 | 15230552.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.93 | 28-FEB-14:50 | 1160.93 | 28-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.179030E+09 | 0.00 | 52.44 | 0.179030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12954.22 | 31-MAR-15:40 | 12954.22 | 31-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.442438E+10 | 0.00 | 115.71 | 0.442438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88306.29 | 23-APR-15:31 | 88306.29 | 23-APR-15:31 | 0.00 | 0.00 | 0.00 |
May | 0.317803E+11 | 0.00 | 235.25 | 0.311057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128990.60 | 25-MAY-16:00 | 122241.32 | 18-MAY-14:40 | 0.00 | 0.00 | 0.00 |
June | 0.697829E+11 | 0.00 | 361.66 | 0.571348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 237772.12 | 30-JUN-05:02 | 143070.13 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.916194E+11 | 0.00 | 412.25 | 0.716487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 236652.25 | 05-JUL-12:05 | 139206.05 | 23-JUL-15:31 | 0.00 | 0.00 | 0.00 |
August | 0.653099E+11 | 0.00 | 391.15 | 0.511509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182375.01 | 29-AUG-16:00 | 126759.74 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.138756E+11 | 0.00 | 178.79 | 0.126934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137925.15 | 01-SEP-14:00 | 117868.42 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.271757E+10 | 0.00 | 80.31 | 0.271757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53248.02 | 19-OCT-15:00 | 53248.02 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.213783E+09 | 0.00 | 51.81 | 0.213783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8924.83 | 01-NOV-15:00 | 8924.83 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 84616.64 | 0.00 | 0.75 | 84616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 121.31 | 28-DEC-12:20 | 121.31 | 28-DEC-12:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279918E+12 | 0.00 | 1902.49 | 0.231284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 84616.64 | 0.00 | 0.75 | 84616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 60.77 | 60.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.916194E+11 | 0.00 | 412.25 | 0.716487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 237772.12 | 143070.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 17241436.13 | 0.00 | 114.27 | 17241436.13 | 0.00 | 0.00 | 0.00 | 0.00 | 329.15 | 25-JAN-10:30 | 329.15 | 25-JAN-10:30 | 0.00 | 0.00 | 0.00 |
February | 22903698.24 | 0.00 | 138.25 | 22903698.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1913.87 | 08-FEB-18:10 | 1913.87 | 08-FEB-18:10 | 0.00 | 0.00 | 0.00 |
March | 41648361.69 | 0.00 | 162.01 | 41648361.69 | 0.00 | 0.00 | 0.00 | 0.00 | 5098.18 | 22-MAR-16:10 | 5098.18 | 22-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.655600E+09 | 0.00 | 43.81 | 0.655600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21678.46 | 13-APR-15:00 | 21678.46 | 13-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.160077E+11 | 0.00 | 166.41 | 0.159129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83768.13 | 26-MAY-04:12 | 54095.72 | 26-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.371949E+11 | 0.00 | 293.00 | 0.313691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137898.43 | 30-JUN-04:03 | 78142.60 | 30-JUN-04:03 | 0.00 | 0.00 | 0.00 |
July | 0.500980E+11 | 0.00 | 333.96 | 0.408458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145049.04 | 05-JUL-10:05 | 65255.28 | 24-JUL-09:10 | 0.00 | 0.00 | 0.00 |
August | 0.407455E+11 | 0.00 | 319.05 | 0.323403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118467.57 | 27-AUG-17:54 | 64037.98 | 27-AUG-17:54 | 0.00 | 0.00 | 0.00 |
September | 0.751855E+10 | 0.00 | 111.57 | 0.690966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84488.15 | 01-SEP-04:12 | 49671.50 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.947010E+09 | 0.00 | 23.79 | 0.947010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36652.13 | 19-OCT-15:00 | 36652.13 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.130720E+09 | 0.00 | 82.21 | 0.129086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16367.82 | 21-NOV-06:03 | 12195.93 | 01-NOV-04:11 | 0.00 | 0.00 | 0.00 |
December | 52940311.20 | 0.00 | 175.87 | 52940311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 15357.27 | 18-DEC-16:20 | 15357.27 | 18-DEC-16:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153433E+12 | 0.00 | 1964.20 | 0.129244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17241436.13 | 0.00 | 23.79 | 17241436.13 | 0.00 | 0.00 | 0.00 | 0.00 | 329.15 | 329.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.500980E+11 | 0.00 | 333.96 | 0.408458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145049.04 | 78142.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.577875E+10 | 0.356101E+10 | 744.00 | 0.577875E+10 | -0.0 | 0.00 | 0.02 | 21-JAN-16:00 | 0.01 | 06-JAN-09:00 | 2796.40 | 21-JAN-16:00 | 2796.40 | 21-JAN-16:00 | 0.00 | 29-JAN-05:43 | 1764.32 | 20-JAN-11:02 | 0.00 |
February | 0.105608E+11 | 0.461979E+10 | 672.00 | 0.104892E+11 | 71618215.47 | 0.00 | 0.03 | 20-FEB-15:07 | 0.02 | 14-FEB-08:65 | 5158.72 | 20-FEB-17:33 | 5158.72 | 20-FEB-17:33 | 128.11 | 14-FEB-07:10 | 2158.20 | 20-FEB-16:03 | 0.00 |
March | 0.144194E+11 | 0.607514E+10 | 744.00 | 0.143527E+11 | 66733335.07 | 0.00 | 0.03 | 31-MAR-23:40 | 0.03 | 20-MAR-18:00 | 5688.79 | 05-MAR-03:43 | 5626.63 | 31-MAR-23:10 | 369.87 | 20-MAR-18:00 | 2897.85 | 29-MAR-14:50 | 0.00 |
April | 0.570164E+11 | 0.179012E+11 | 720.00 | 0.555489E+11 | 0.146747E+10 | 0.00 | 1.00 | 23-APR-15:51 | 0.02 | 30-APR-24:00 | 392423.50 | 23-APR-15:51 | 390820.06 | 23-APR-15:51 | 44180.30 | 23-APR-11:23 | 112965.52 | 23-APR-16:00 | 0.00 |
May | 0.271925E+11 | 0.100729E+11 | 601.10 | 0.257659E+11 | 0.142656E+10 | 0.00 | 0.41 | 25-MAY-13:10 | 0.01 | 19-MAY-10:05 | 155591.20 | 25-MAY-13:05 | 128752.65 | 25-MAY-16:00 | 46833.65 | 26-MAY-12:00 | 43529.14 | 25-MAY-13:10 | 0.00 |
June | 0.175492E+12 | 0.492781E+11 | 468.92 | 0.129232E+12 | 0.462595E+11 | 0.00 | 1.00 | 29-JUN-21:45 | 0.01 | 11-JUN-10:00 | 467044.78 | 29-JUN-23:03 | 222862.61 | 29-JUN-16:00 | 276381.46 | 29-JUN-23:00 | 114806.41 | 30-JUN-01:10 | 0.00 |
July | 0.550004E+12 | 0.138921E+12 | 615.88 | 0.338501E+12 | 0.211502E+12 | 0.00 | 1.00 | 03-JUL-13:00 | 0.01 | 01-JUL-05:08 | 472302.78 | 15-JUL-14:00 | 342904.59 | 23-JUL-12:55 | 309177.87 | 04-JUL-01:00 | 126094.32 | 15-JUL-14:10 | 0.00 |
August | 0.697069E+12 | 0.168179E+12 | 715.89 | 0.418985E+12 | 0.278084E+12 | 0.00 | 1.00 | 03-AUG-14:00 | 0.01 | 05-AUG-00:35 | 451040.45 | 31-AUG-12:55 | 374007.14 | 25-AUG-14:00 | 261432.37 | 28-AUG-20:00 | 124626.59 | 08-AUG-15:10 | 0.00 |
September | 0.529868E+10 | 0.367941E+10 | 416.44 | 0.471358E+10 | 0.585098E+09 | 0.00 | 0.35 | 01-SEP-15:00 | 0.00 | 05-SEP-01:00 | 128043.14 | 01-SEP-15:00 | 110603.33 | 01-SEP-15:00 | 23567.55 | 01-SEP-13:40 | 36365.31 | 01-SEP-15:00 | 0.00 |
October | 0.105685E+11 | 0.488219E+10 | 705.71 | 0.102835E+11 | 0.285053E+09 | 0.00 | 0.29 | 19-OCT-15:00 | 0.00 | 07-OCT-03:10 | 96161.97 | 19-OCT-15:00 | 96161.97 | 19-OCT-15:00 | 5721.22 | 19-OCT-13:00 | 27227.18 | 19-OCT-15:00 | 0.00 |
November | 0.149171E+11 | 0.608960E+10 | 696.66 | 0.143700E+11 | 0.547099E+09 | 0.00 | 0.31 | 01-NOV-15:00 | 0.01 | 01-NOV-04:57 | 106508.67 | 01-NOV-15:00 | 82386.62 | 01-NOV-15:00 | 24122.05 | 01-NOV-15:00 | 26648.41 | 01-NOV-15:00 | 0.00 |
December | 0.150684E+11 | 0.656994E+10 | 744.00 | 0.150225E+11 | 45933866.96 | 0.00 | 0.03 | 06-DEC-03:00 | 0.03 | 17-DEC-12:33 | 6091.57 | 06-DEC-03:00 | 5645.66 | 17-DEC-05:23 | 476.14 | 06-DEC-03:00 | 2505.74 | 06-DEC-03:00 | 0.00 |
Annual Sum or Average | 0.158338E+13 | 0.419830E+12 | 7844.61 | 0.104304E+13 | 0.540341E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.529868E+10 | 0.356101E+10 | 416.44 | 0.471358E+10 | -0.0 | 0.00 | 0.02 | 0.00 | 2796.40 | 2796.40 | 0.00 | 1764.32 | 0.00 | ||||||
Maximum of Months | 0.697069E+12 | 0.168179E+12 | 744.00 | 0.418985E+12 | 0.278084E+12 | 0.00 | 1.00 | 0.03 | 472302.78 | 390820.06 | 309177.87 | 126094.32 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.175496E+10 | 0.467175E+09 | 682.25 | 0.175496E+10 | 0.00 | 0.00 | 0.25 | 20-JAN-16:30 | 0.00 | 01-JAN-02:31 | 1865.81 | 20-JAN-16:30 | 1865.81 | 20-JAN-16:30 | 0.00 | 20-JAN-14:20 | 443.17 | 20-JAN-16:30 | 0.00 |
February | 0.746594E+10 | 0.174750E+10 | 672.00 | 0.746594E+10 | -0.0 | 0.00 | 0.59 | 20-FEB-16:53 | 0.26 | 14-FEB-07:03 | 4573.10 | 20-FEB-17:00 | 4573.10 | 20-FEB-17:00 | 0.00 | 03-FEB-04:48 | 1037.91 | 20-FEB-16:53 | 0.00 |
March | 0.143469E+11 | 0.311537E+10 | 744.00 | 0.143469E+11 | -0.0 | 0.00 | 0.87 | 19-MAR-17:37 | 0.54 | 06-MAR-07:05 | 7607.11 | 31-MAR-24:00 | 7607.11 | 31-MAR-24:00 | 0.00 | 20-MAR-22:50 | 1547.46 | 31-MAR-24:00 | 0.00 |
April | 0.196626E+11 | 0.404904E+10 | 720.00 | 0.196626E+11 | 0.00 | 0.00 | 1.00 | 21-APR-18:20 | 0.32 | 30-APR-24:00 | 8937.29 | 16-APR-18:10 | 8937.29 | 16-APR-18:10 | 0.00 | 01-APR-06:40 | 2456.07 | 23-APR-16:00 | 0.00 |
May | 0.571594E+10 | 0.132164E+10 | 744.00 | 0.567318E+10 | 42762455.31 | 0.00 | 0.45 | 31-MAY-24:00 | 0.19 | 13-MAY-06:10 | 3840.77 | 31-MAY-24:00 | 3840.77 | 31-MAY-24:00 | 253.34 | 26-MAY-13:40 | 932.59 | 25-MAY-18:40 | 0.00 |
June | 0.108041E+11 | 0.247072E+10 | 720.00 | 0.106050E+11 | 0.199114E+09 | 0.00 | 0.65 | 30-JUN-23:20 | 0.42 | 09-JUN-21:00 | 5969.65 | 30-JUN-23:35 | 5937.34 | 30-JUN-23:50 | 485.96 | 30-JUN-16:00 | 1722.48 | 29-JUN-16:00 | 0.00 |
July | 0.164710E+11 | 0.385210E+10 | 744.00 | 0.161967E+11 | 0.274351E+09 | 0.00 | 0.84 | 31-JUL-24:00 | 0.62 | 08-JUL-07:00 | 7809.07 | 31-JUL-23:55 | 7809.07 | 31-JUL-23:55 | 500.65 | 05-JUL-11:00 | 2133.74 | 15-JUL-14:50 | 0.00 |
August | 0.213478E+11 | 0.468180E+10 | 744.00 | 0.210639E+11 | 0.283977E+09 | 0.00 | 1.00 | 08-AUG-15:00 | 0.31 | 31-AUG-24:00 | 9051.97 | 13-AUG-18:33 | 9051.97 | 13-AUG-18:33 | 412.85 | 31-AUG-16:00 | 2700.12 | 08-AUG-15:20 | 0.00 |
September | 0.535558E+10 | 0.118172E+10 | 720.00 | 0.530057E+10 | 55015782.09 | 0.00 | 0.45 | 30-SEP-24:00 | 0.18 | 23-SEP-06:55 | 3876.65 | 30-SEP-24:00 | 3876.65 | 30-SEP-24:00 | 247.75 | 18-SEP-16:00 | 801.98 | 03-SEP-17:41 | 0.00 |
October | 0.100259E+11 | 0.212765E+10 | 744.00 | 0.100201E+11 | 5789433.01 | 0.00 | 0.65 | 31-OCT-24:00 | 0.35 | 30-OCT-06:10 | 5467.60 | 31-OCT-24:00 | 5467.60 | 31-OCT-24:00 | 93.60 | 02-OCT-14:05 | 1155.90 | 31-OCT-24:00 | 0.00 |
November | 0.139676E+11 | 0.299007E+10 | 720.00 | 0.139622E+11 | 5384503.90 | 0.00 | 0.76 | 12-NOV-15:55 | 0.54 | 25-NOV-07:05 | 6395.78 | 12-NOV-16:05 | 6395.78 | 12-NOV-16:05 | 186.73 | 21-NOV-12:10 | 1345.66 | 12-NOV-15:55 | 0.00 |
December | 0.184047E+11 | 0.394522E+10 | 744.00 | 0.184047E+11 | -0.0 | 0.00 | 0.96 | 10-DEC-15:53 | 0.72 | 26-DEC-07:03 | 7901.90 | 10-DEC-15:58 | 7901.90 | 10-DEC-15:58 | 0.00 | 09-DEC-03:25 | 1694.92 | 10-DEC-15:53 | 0.00 |
Annual Sum or Average | 0.145323E+12 | 0.319500E+11 | 8698.25 | 0.144457E+12 | 0.866394E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.175496E+10 | 0.467175E+09 | 672.00 | 0.175496E+10 | -0.0 | 0.00 | 0.25 | 0.00 | 1865.81 | 1865.81 | 0.00 | 443.17 | 0.00 | ||||||
Maximum of Months | 0.213478E+11 | 0.468180E+10 | 744.00 | 0.210639E+11 | 0.283977E+09 | 0.00 | 1.00 | 0.72 | 9051.97 | 9051.97 | 500.65 | 2700.12 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.834902E+09 | 0.247248E+09 | 75.42 | 0.834902E+09 | 0.00 | 0.00 | 0.19 | 27-JAN-16:30 | 0.00 | 01-JAN-00:01 | 13006.37 | 20-JAN-16:30 | 13006.37 | 20-JAN-16:30 | 0.00 | 30-JAN-15:10 | 3177.68 | 27-JAN-16:30 | 0.00 |
February | 0.440597E+11 | 0.107205E+11 | 672.00 | 0.440597E+11 | 0.00 | 0.00 | 0.49 | 08-FEB-17:00 | 0.09 | 14-FEB-07:03 | 37645.02 | 08-FEB-17:00 | 37645.02 | 08-FEB-17:00 | 0.00 | 06-FEB-15:20 | 8324.24 | 08-FEB-17:00 | 0.00 |
March | 0.113666E+12 | 0.251926E+11 | 744.00 | 0.113666E+12 | 0.00 | 0.00 | 0.83 | 31-MAR-23:20 | 0.36 | 06-MAR-07:05 | 69025.16 | 31-MAR-23:20 | 69025.16 | 31-MAR-23:20 | 0.00 | 02-MAR-05:05 | 14157.32 | 31-MAR-23:20 | 0.00 |
April | 0.175038E+12 | 0.364461E+11 | 720.00 | 0.175038E+12 | 0.00 | 0.00 | 1.00 | 22-APR-17:31 | 0.21 | 30-APR-24:00 | 83228.53 | 21-APR-18:20 | 83228.53 | 21-APR-18:20 | 0.00 | 30-APR-03:00 | 23615.35 | 23-APR-16:00 | 0.00 |
May | 0.502557E+11 | 0.117263E+11 | 744.00 | 0.498333E+11 | 0.422418E+09 | 0.00 | 0.43 | 14-MAY-18:42 | 0.09 | 01-MAY-06:05 | 34960.47 | 31-MAY-24:00 | 34960.47 | 31-MAY-24:00 | 2491.61 | 26-MAY-13:30 | 9150.75 | 25-MAY-18:40 | 0.00 |
June | 0.100466E+12 | 0.230926E+11 | 720.00 | 0.984900E+11 | 0.197610E+10 | 0.00 | 0.66 | 30-JUN-23:20 | 0.39 | 10-JUN-06:10 | 57964.89 | 30-JUN-23:30 | 57658.82 | 30-JUN-23:55 | 4848.02 | 30-JUN-16:00 | 16539.81 | 29-JUN-16:00 | 0.00 |
July | 0.156012E+12 | 0.365762E+11 | 744.00 | 0.153281E+12 | 0.273019E+10 | 0.00 | 0.83 | 31-JUL-24:00 | 0.60 | 08-JUL-07:00 | 74330.74 | 31-JUL-23:55 | 74330.74 | 31-JUL-23:55 | 4995.52 | 05-JUL-11:00 | 20266.60 | 15-JUL-14:40 | 0.00 |
August | 0.201593E+12 | 0.443448E+11 | 744.00 | 0.198763E+12 | 0.283040E+10 | 0.00 | 1.00 | 08-AUG-16:00 | 0.26 | 31-AUG-24:00 | 85407.64 | 05-AUG-18:40 | 85407.64 | 05-AUG-18:40 | 4119.56 | 31-AUG-16:00 | 25895.48 | 08-AUG-16:00 | 0.00 |
September | 0.449271E+11 | 0.100326E+11 | 720.00 | 0.443887E+11 | 0.538363E+09 | 0.00 | 0.42 | 30-SEP-23:30 | 0.12 | 23-SEP-06:55 | 34618.97 | 30-SEP-23:30 | 34618.97 | 30-SEP-23:30 | 2416.64 | 18-SEP-16:00 | 7604.55 | 03-SEP-17:32 | 0.00 |
October | 0.805533E+11 | 0.173779E+11 | 744.00 | 0.804953E+11 | 57950430.82 | 0.00 | 0.55 | 31-OCT-23:40 | 0.22 | 30-OCT-06:10 | 44353.89 | 22-OCT-16:50 | 44353.89 | 22-OCT-16:50 | 930.05 | 02-OCT-14:05 | 9956.18 | 19-OCT-16:00 | 0.00 |
November | 0.106133E+12 | 0.232748E+11 | 720.00 | 0.106079E+12 | 53964638.20 | 0.00 | 0.68 | 17-NOV-16:10 | 0.38 | 27-NOV-04:08 | 55268.12 | 17-NOV-16:10 | 55268.12 | 17-NOV-16:10 | 1823.73 | 21-NOV-12:10 | 11613.28 | 17-NOV-16:10 | 0.00 |
December | 0.138274E+12 | 0.305751E+11 | 744.00 | 0.138274E+12 | 0.00 | 0.00 | 0.81 | 02-DEC-16:00 | 0.52 | 26-DEC-07:03 | 63694.21 | 08-DEC-15:55 | 63694.21 | 08-DEC-15:55 | 0.00 | 05-DEC-17:30 | 13775.09 | 02-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.121181E+13 | 0.269607E+12 | 8091.42 | 0.120320E+13 | 0.860939E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.834902E+09 | 0.247248E+09 | 75.42 | 0.834902E+09 | 0.00 | 0.00 | 0.19 | 0.00 | 13006.37 | 13006.37 | 0.00 | 3177.68 | 0.00 | ||||||
Maximum of Months | 0.201593E+12 | 0.443448E+11 | 744.00 | 0.198763E+12 | 0.283040E+10 | 0.00 | 1.00 | 0.60 | 85407.64 | 85407.64 | 4995.52 | 25895.48 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 32396296.86 | 9178659.50 | 21.99 | 32396296.86 | 0.00 | 0.00 | 0.16 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 | 1084.31 | 20-JAN-16:30 | 1084.31 | 20-JAN-16:30 | 0.00 | 19-JAN-17:00 | 269.76 | 20-JAN-16:30 | 0.00 |
February | 0.286856E+10 | 0.713411E+09 | 627.55 | 0.286856E+10 | -0.0 | 0.00 | 0.47 | 08-FEB-17:00 | 0.00 | 01-FEB-00:03 | 3710.81 | 08-FEB-17:00 | 3710.81 | 08-FEB-17:00 | 0.00 | 22-FEB-09:45 | 822.78 | 08-FEB-17:00 | 0.00 |
March | 0.963595E+10 | 0.216947E+10 | 744.00 | 0.963595E+10 | 0.00 | 0.00 | 0.77 | 31-MAR-23:10 | 0.21 | 06-MAR-04:12 | 6426.82 | 31-MAR-23:10 | 6426.82 | 31-MAR-23:10 | 0.00 | 28-MAR-09:15 | 1332.88 | 31-MAR-23:10 | 0.00 |
April | 0.161345E+11 | 0.340040E+10 | 720.00 | 0.161345E+11 | 0.00 | 0.00 | 1.00 | 23-APR-14:41 | 0.11 | 30-APR-24:00 | 8310.45 | 21-APR-18:20 | 8310.45 | 21-APR-18:20 | 0.00 | 02-APR-15:10 | 2393.97 | 23-APR-16:00 | 0.00 |
May | 0.458318E+10 | 0.107920E+10 | 742.17 | 0.454087E+10 | 42311239.33 | 0.00 | 0.42 | 14-MAY-18:42 | 0.00 | 01-MAY-06:05 | 3255.79 | 14-MAY-18:42 | 3255.79 | 14-MAY-18:43 | 251.30 | 26-MAY-13:30 | 939.05 | 25-MAY-18:40 | 0.00 |
June | 0.985254E+10 | 0.227778E+10 | 720.00 | 0.965518E+10 | 0.197359E+09 | 0.00 | 0.65 | 30-JUN-23:10 | 0.34 | 11-JUN-05:30 | 5781.71 | 30-JUN-23:30 | 5745.86 | 30-JUN-23:40 | 485.57 | 30-JUN-16:00 | 1682.58 | 29-JUN-16:00 | 0.00 |
July | 0.155089E+11 | 0.365111E+10 | 744.00 | 0.152361E+11 | 0.272768E+09 | 0.00 | 0.81 | 31-JUL-24:00 | 0.55 | 09-JUL-05:00 | 7347.81 | 31-JUL-23:55 | 7347.81 | 31-JUL-23:55 | 499.46 | 05-JUL-11:00 | 2047.98 | 15-JUL-14:50 | 0.00 |
August | 0.199997E+11 | 0.441723E+10 | 744.00 | 0.197171E+11 | 0.282588E+09 | 0.00 | 1.00 | 08-AUG-16:00 | 0.25 | 31-AUG-24:00 | 8649.94 | 05-AUG-18:40 | 8649.94 | 05-AUG-18:40 | 411.89 | 31-AUG-16:00 | 2621.14 | 08-AUG-16:00 | 0.00 |
September | 0.384349E+10 | 0.869140E+09 | 720.00 | 0.379053E+10 | 52958830.95 | 0.00 | 0.41 | 03-SEP-17:41 | 0.05 | 23-SEP-06:55 | 3375.35 | 03-SEP-17:42 | 3365.63 | 03-SEP-17:44 | 242.72 | 18-SEP-16:00 | 768.90 | 03-SEP-17:41 | 0.00 |
October | 0.630846E+10 | 0.138573E+10 | 743.92 | 0.630278E+10 | 5680643.84 | 0.00 | 0.52 | 19-OCT-16:40 | 0.00 | 29-OCT-21:25 | 4400.16 | 19-OCT-16:50 | 4346.35 | 19-OCT-16:50 | 93.39 | 02-OCT-14:05 | 1001.47 | 19-OCT-16:00 | 0.00 |
November | 0.864745E+10 | 0.193130E+10 | 720.00 | 0.864218E+10 | 5262255.70 | 0.00 | 0.65 | 17-NOV-16:10 | 0.24 | 27-NOV-03:45 | 5372.34 | 17-NOV-16:10 | 5372.34 | 17-NOV-16:10 | 177.20 | 21-NOV-12:10 | 1134.47 | 17-NOV-16:10 | 0.00 |
December | 0.122020E+11 | 0.273638E+10 | 744.00 | 0.122020E+11 | 0.00 | 0.00 | 0.77 | 20-DEC-16:00 | 0.40 | 25-DEC-07:50 | 6056.14 | 20-DEC-16:00 | 6056.14 | 20-DEC-16:00 | 0.00 | 05-DEC-06:04 | 1323.18 | 20-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.109617E+12 | 0.246403E+11 | 7991.62 | 0.108758E+12 | 0.858928E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 32396296.86 | 9178659.50 | 21.99 | 32396296.86 | -0.0 | 0.00 | 0.16 | 0.00 | 1084.31 | 1084.31 | 0.00 | 269.76 | 0.00 | ||||||
Maximum of Months | 0.199997E+11 | 0.441723E+10 | 744.00 | 0.197171E+11 | 0.282588E+09 | 0.00 | 1.00 | 0.55 | 8649.94 | 8649.94 | 499.46 | 2621.14 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.29 | 0.00 | 117.29 | 0.43 | 1086.18 | 0.00 | 0.00 | 0.00 |
February | 180.17 | 0.00 | 180.17 | 9.80 | 883.64 | 0.00 | 0.00 | 0.00 |
March | 221.67 | 0.00 | 221.67 | 28.49 | 704.61 | 0.00 | 0.00 | 0.00 |
April | 290.56 | 2.23 | 288.33 | 123.62 | 435.89 | 0.00 | 0.00 | 0.00 |
May | 408.55 | 21.84 | 386.71 | 363.23 | 218.17 | 0.00 | 0.00 | 0.00 |
June | 455.88 | 49.89 | 405.99 | 501.21 | 149.91 | 0.00 | 0.00 | 0.00 |
July | 435.46 | 37.17 | 398.29 | 503.33 | 137.60 | 0.00 | 0.00 | 0.00 |
August | 330.85 | 5.62 | 325.23 | 342.27 | 166.30 | 0.00 | 0.00 | 0.00 |
September | 257.87 | 0.06 | 257.81 | 191.54 | 279.01 | 0.00 | 0.00 | 0.00 |
October | 179.05 | 0.00 | 179.05 | 55.03 | 450.85 | 0.00 | 0.00 | 0.00 |
November | 118.55 | 0.00 | 118.55 | 6.19 | 692.64 | 0.00 | 0.00 | 0.00 |
December | 99.38 | 0.00 | 99.38 | 0.00 | 1066.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.33 | 9.78 | 248.55 | 178.16 | 521.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.38 | 0.00 | 99.38 | 0.00 | 137.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.88 | 49.89 | 405.99 | 503.33 | 1086.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.29 | 0.00 | 117.29 | 0.43 | 1086.18 | 0.00 | 0.00 | 0.00 |
February | 180.17 | 0.00 | 180.17 | 9.80 | 883.64 | 0.00 | 0.00 | 0.00 |
March | 221.67 | 0.00 | 221.67 | 28.49 | 704.61 | 0.00 | 0.00 | 0.00 |
April | 290.56 | 2.23 | 288.33 | 123.62 | 435.89 | 0.00 | 0.00 | 0.00 |
May | 408.55 | 21.84 | 386.71 | 363.23 | 218.17 | 0.00 | 0.00 | 0.00 |
June | 455.88 | 49.89 | 405.99 | 501.21 | 149.91 | 0.00 | 0.00 | 0.00 |
July | 435.46 | 37.17 | 398.29 | 503.33 | 137.60 | 0.00 | 0.00 | 0.00 |
August | 330.85 | 5.62 | 325.23 | 342.27 | 166.30 | 0.00 | 0.00 | 0.00 |
September | 257.87 | 0.06 | 257.81 | 191.54 | 279.01 | 0.00 | 0.00 | 0.00 |
October | 179.05 | 0.00 | 179.05 | 55.03 | 450.85 | 0.00 | 0.00 | 0.00 |
November | 118.55 | 0.00 | 118.55 | 6.19 | 692.64 | 0.00 | 0.00 | 0.00 |
December | 99.38 | 0.00 | 99.38 | 0.00 | 1066.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.33 | 9.78 | 248.55 | 178.16 | 521.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.38 | 0.00 | 99.38 | 0.00 | 137.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.88 | 49.89 | 405.99 | 503.33 | 1086.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.29 | 0.00 | 117.29 | 0.43 | 1086.18 | 0.00 | 0.00 | 0.00 |
February | 180.17 | 0.00 | 180.17 | 9.80 | 883.64 | 0.00 | 0.00 | 0.00 |
March | 221.67 | 0.00 | 221.67 | 28.49 | 704.61 | 0.00 | 0.00 | 0.00 |
April | 290.56 | 2.23 | 288.33 | 123.62 | 435.89 | 0.00 | 0.00 | 0.00 |
May | 408.55 | 21.84 | 386.71 | 363.23 | 218.17 | 0.00 | 0.00 | 0.00 |
June | 455.88 | 49.89 | 405.99 | 501.21 | 149.91 | 0.00 | 0.00 | 0.00 |
July | 435.46 | 37.17 | 398.29 | 503.33 | 137.60 | 0.00 | 0.00 | 0.00 |
August | 330.85 | 5.62 | 325.23 | 342.27 | 166.30 | 0.00 | 0.00 | 0.00 |
September | 257.87 | 0.06 | 257.81 | 191.54 | 279.01 | 0.00 | 0.00 | 0.00 |
October | 179.05 | 0.00 | 179.05 | 55.03 | 450.85 | 0.00 | 0.00 | 0.00 |
November | 118.55 | 0.00 | 118.55 | 6.19 | 692.64 | 0.00 | 0.00 | 0.00 |
December | 99.38 | 0.00 | 99.38 | 0.00 | 1066.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.33 | 9.78 | 248.55 | 178.16 | 521.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.38 | 0.00 | 99.38 | 0.00 | 137.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.88 | 49.89 | 405.99 | 503.33 | 1086.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.29 | 0.00 | 117.29 | 0.43 | 1086.18 | 0.00 | 0.00 | 0.00 |
February | 180.17 | 0.00 | 180.17 | 9.80 | 883.64 | 0.00 | 0.00 | 0.00 |
March | 221.67 | 0.00 | 221.67 | 28.49 | 704.61 | 0.00 | 0.00 | 0.00 |
April | 290.56 | 2.23 | 288.33 | 123.62 | 435.89 | 0.00 | 0.00 | 0.00 |
May | 408.55 | 21.84 | 386.71 | 363.23 | 218.17 | 0.00 | 0.00 | 0.00 |
June | 455.88 | 49.89 | 405.99 | 501.21 | 149.91 | 0.00 | 0.00 | 0.00 |
July | 435.46 | 37.17 | 398.29 | 503.33 | 137.60 | 0.00 | 0.00 | 0.00 |
August | 330.85 | 5.62 | 325.23 | 342.27 | 166.30 | 0.00 | 0.00 | 0.00 |
September | 257.87 | 0.06 | 257.81 | 191.54 | 279.01 | 0.00 | 0.00 | 0.00 |
October | 179.05 | 0.00 | 179.05 | 55.03 | 450.85 | 0.00 | 0.00 | 0.00 |
November | 118.55 | 0.00 | 118.55 | 6.19 | 692.64 | 0.00 | 0.00 | 0.00 |
December | 99.38 | 0.00 | 99.38 | 0.00 | 1066.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.33 | 9.78 | 248.55 | 178.16 | 521.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.38 | 0.00 | 99.38 | 0.00 | 137.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.88 | 49.89 | 405.99 | 503.33 | 1086.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.29 | 0.00 | 117.29 | 0.43 | 1086.14 | 0.00 | 0.00 | 0.00 |
February | 180.17 | 0.00 | 180.17 | 9.80 | 883.60 | 0.00 | 0.00 | 0.00 |
March | 221.66 | 0.00 | 221.66 | 28.49 | 704.58 | 0.00 | 0.00 | 0.00 |
April | 290.55 | 2.23 | 288.32 | 123.61 | 435.88 | 0.00 | 0.00 | 0.00 |
May | 408.53 | 21.84 | 386.69 | 363.21 | 218.16 | 0.00 | 0.00 | 0.00 |
June | 455.86 | 49.88 | 405.97 | 501.19 | 149.91 | 0.00 | 0.00 | 0.00 |
July | 435.44 | 37.17 | 398.27 | 503.31 | 137.59 | 0.00 | 0.00 | 0.00 |
August | 330.84 | 5.62 | 325.21 | 342.26 | 166.30 | 0.00 | 0.00 | 0.00 |
September | 257.86 | 0.06 | 257.80 | 191.53 | 279.00 | 0.00 | 0.00 | 0.00 |
October | 179.04 | 0.00 | 179.04 | 55.03 | 450.83 | 0.00 | 0.00 | 0.00 |
November | 118.55 | 0.00 | 118.55 | 6.19 | 692.61 | 0.00 | 0.00 | 0.00 |
December | 99.38 | 0.00 | 99.38 | 0.00 | 1066.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.32 | 9.78 | 248.54 | 178.15 | 521.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.38 | 0.00 | 99.38 | 0.00 | 137.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 455.86 | 49.88 | 405.97 | 503.31 | 1086.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 285.63 | 119.17 | 166.46 | 106.45 | 1085.83 | 0.00 | 0.00 | 0.00 |
February | 448.93 | 191.46 | 257.48 | 256.74 | 879.08 | 0.00 | 0.00 | 0.00 |
March | 611.88 | 306.97 | 304.91 | 456.72 | 709.57 | 0.00 | 0.00 | 0.00 |
April | 848.29 | 457.63 | 390.66 | 813.08 | 446.18 | 0.00 | 0.00 | 0.00 |
May | 918.08 | 403.69 | 514.39 | 1018.27 | 244.21 | 0.00 | 0.00 | 0.00 |
June | 1039.41 | 497.35 | 542.06 | 1264.36 | 169.20 | 0.00 | 0.00 | 0.00 |
July | 1018.22 | 478.22 | 540.00 | 1273.24 | 152.32 | 0.00 | 0.00 | 0.00 |
August | 785.00 | 343.18 | 441.82 | 941.32 | 179.72 | 0.00 | 0.00 | 0.00 |
September | 628.64 | 281.43 | 347.21 | 660.87 | 294.82 | 0.00 | 0.00 | 0.00 |
October | 380.60 | 144.33 | 236.27 | 281.99 | 466.53 | 0.00 | 0.00 | 0.00 |
November | 242.23 | 80.95 | 161.29 | 108.10 | 700.83 | 0.00 | 0.00 | 0.00 |
December | 221.01 | 81.64 | 139.37 | 64.75 | 1073.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 619.62 | 282.40 | 337.22 | 605.50 | 532.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 221.01 | 80.95 | 139.37 | 64.75 | 152.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1039.41 | 497.35 | 542.06 | 1273.24 | 1085.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 285.63 | 119.17 | 166.46 | 106.45 | 1085.83 | 0.00 | 0.00 | 0.00 |
February | 448.93 | 191.46 | 257.48 | 256.74 | 879.08 | 0.00 | 0.00 | 0.00 |
March | 611.88 | 306.97 | 304.91 | 456.72 | 709.57 | 0.00 | 0.00 | 0.00 |
April | 848.29 | 457.63 | 390.66 | 813.08 | 446.18 | 0.00 | 0.00 | 0.00 |
May | 918.08 | 403.69 | 514.39 | 1018.27 | 244.21 | 0.00 | 0.00 | 0.00 |
June | 1039.41 | 497.35 | 542.06 | 1264.36 | 169.20 | 0.00 | 0.00 | 0.00 |
July | 1018.22 | 478.22 | 540.00 | 1273.24 | 152.32 | 0.00 | 0.00 | 0.00 |
August | 785.00 | 343.18 | 441.82 | 941.32 | 179.72 | 0.00 | 0.00 | 0.00 |
September | 628.64 | 281.43 | 347.21 | 660.87 | 294.82 | 0.00 | 0.00 | 0.00 |
October | 380.60 | 144.33 | 236.27 | 281.99 | 466.53 | 0.00 | 0.00 | 0.00 |
November | 242.23 | 80.95 | 161.29 | 108.10 | 700.83 | 0.00 | 0.00 | 0.00 |
December | 221.01 | 81.64 | 139.37 | 64.75 | 1073.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 619.62 | 282.40 | 337.22 | 605.50 | 532.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 221.01 | 80.95 | 139.37 | 64.75 | 152.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1039.41 | 497.35 | 542.06 | 1273.24 | 1085.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 285.63 | 119.17 | 166.45 | 106.45 | 1085.81 | 0.00 | 0.00 | 0.00 |
February | 448.92 | 191.45 | 257.47 | 256.74 | 879.06 | 0.00 | 0.00 | 0.00 |
March | 611.87 | 306.97 | 304.90 | 456.71 | 709.56 | 0.00 | 0.00 | 0.00 |
April | 848.27 | 457.62 | 390.65 | 813.06 | 446.17 | 0.00 | 0.00 | 0.00 |
May | 918.06 | 403.69 | 514.38 | 1018.25 | 244.21 | 0.00 | 0.00 | 0.00 |
June | 1039.39 | 497.34 | 542.05 | 1264.34 | 169.20 | 0.00 | 0.00 | 0.00 |
July | 1018.20 | 478.21 | 539.99 | 1273.22 | 152.32 | 0.00 | 0.00 | 0.00 |
August | 784.98 | 343.17 | 441.81 | 941.30 | 179.72 | 0.00 | 0.00 | 0.00 |
September | 628.63 | 281.42 | 347.20 | 660.86 | 294.81 | 0.00 | 0.00 | 0.00 |
October | 380.60 | 144.33 | 236.27 | 281.98 | 466.52 | 0.00 | 0.00 | 0.00 |
November | 242.23 | 80.94 | 161.28 | 108.10 | 700.82 | 0.00 | 0.00 | 0.00 |
December | 221.00 | 81.64 | 139.37 | 64.75 | 1073.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 619.61 | 282.39 | 337.21 | 605.49 | 532.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 221.00 | 80.94 | 139.37 | 64.75 | 152.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1039.39 | 497.34 | 542.05 | 1273.22 | 1085.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.34 | 562.54 | 245.80 | 683.89 | 858.97 | 0.00 | 0.00 | 0.00 |
February | 1023.50 | 691.56 | 331.94 | 978.40 | 736.34 | 0.00 | 0.00 | 0.00 |
March | 901.40 | 570.55 | 330.85 | 881.16 | 622.73 | 0.00 | 0.00 | 0.00 |
April | 815.92 | 442.63 | 373.29 | 871.45 | 425.88 | 0.00 | 0.00 | 0.00 |
May | 685.60 | 233.87 | 451.73 | 800.10 | 239.31 | 0.00 | 0.00 | 0.00 |
June | 615.09 | 163.37 | 451.72 | 766.72 | 163.76 | 0.00 | 0.00 | 0.00 |
July | 672.47 | 212.43 | 460.04 | 877.06 | 148.88 | 0.00 | 0.00 | 0.00 |
August | 718.50 | 300.19 | 418.31 | 909.14 | 175.58 | 0.00 | 0.00 | 0.00 |
September | 770.21 | 410.16 | 360.05 | 899.87 | 277.68 | 0.00 | 0.00 | 0.00 |
October | 658.11 | 387.21 | 270.90 | 671.11 | 411.70 | 0.00 | 0.00 | 0.00 |
November | 586.35 | 368.15 | 218.20 | 525.85 | 580.12 | 0.00 | 0.00 | 0.00 |
December | 624.10 | 409.39 | 214.71 | 482.17 | 847.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.11 | 394.12 | 343.99 | 777.41 | 456.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 586.35 | 163.37 | 214.71 | 482.17 | 148.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1023.50 | 691.56 | 460.04 | 978.40 | 858.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.34 | 562.54 | 245.80 | 683.89 | 858.97 | 0.00 | 0.00 | 0.00 |
February | 1023.50 | 691.56 | 331.94 | 978.40 | 736.34 | 0.00 | 0.00 | 0.00 |
March | 901.39 | 570.55 | 330.85 | 881.16 | 622.73 | 0.00 | 0.00 | 0.00 |
April | 815.92 | 442.63 | 373.29 | 871.45 | 425.88 | 0.00 | 0.00 | 0.00 |
May | 685.60 | 233.87 | 451.73 | 800.10 | 239.31 | 0.00 | 0.00 | 0.00 |
June | 615.09 | 163.37 | 451.72 | 766.72 | 163.76 | 0.00 | 0.00 | 0.00 |
July | 672.47 | 212.43 | 460.04 | 877.06 | 148.88 | 0.00 | 0.00 | 0.00 |
August | 718.50 | 300.19 | 418.31 | 909.13 | 175.58 | 0.00 | 0.00 | 0.00 |
September | 770.21 | 410.16 | 360.05 | 899.87 | 277.68 | 0.00 | 0.00 | 0.00 |
October | 658.11 | 387.21 | 270.90 | 671.11 | 411.70 | 0.00 | 0.00 | 0.00 |
November | 586.35 | 368.15 | 218.20 | 525.85 | 580.12 | 0.00 | 0.00 | 0.00 |
December | 624.10 | 409.39 | 214.71 | 482.17 | 847.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.11 | 394.12 | 343.99 | 777.41 | 456.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 586.35 | 163.37 | 214.71 | 482.17 | 148.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1023.50 | 691.56 | 460.04 | 978.40 | 858.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.34 | 562.54 | 245.80 | 683.89 | 858.97 | 0.00 | 0.00 | 0.00 |
February | 1023.50 | 691.56 | 331.94 | 978.40 | 736.34 | 0.00 | 0.00 | 0.00 |
March | 901.40 | 570.55 | 330.85 | 881.16 | 622.73 | 0.00 | 0.00 | 0.00 |
April | 815.92 | 442.63 | 373.29 | 871.45 | 425.88 | 0.00 | 0.00 | 0.00 |
May | 685.60 | 233.87 | 451.73 | 800.10 | 239.31 | 0.00 | 0.00 | 0.00 |
June | 615.09 | 163.37 | 451.72 | 766.72 | 163.76 | 0.00 | 0.00 | 0.00 |
July | 672.47 | 212.43 | 460.04 | 877.06 | 148.88 | 0.00 | 0.00 | 0.00 |
August | 718.50 | 300.19 | 418.31 | 909.14 | 175.58 | 0.00 | 0.00 | 0.00 |
September | 770.21 | 410.16 | 360.05 | 899.87 | 277.68 | 0.00 | 0.00 | 0.00 |
October | 658.11 | 387.21 | 270.90 | 671.11 | 411.70 | 0.00 | 0.00 | 0.00 |
November | 586.35 | 368.15 | 218.20 | 525.85 | 580.12 | 0.00 | 0.00 | 0.00 |
December | 624.10 | 409.39 | 214.71 | 482.17 | 847.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.11 | 394.12 | 343.99 | 777.41 | 456.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 586.35 | 163.37 | 214.71 | 482.17 | 148.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1023.50 | 691.56 | 460.04 | 978.40 | 858.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.34 | 562.54 | 245.80 | 683.89 | 858.97 | 0.00 | 0.00 | 0.00 |
February | 1023.50 | 691.56 | 331.94 | 978.40 | 736.34 | 0.00 | 0.00 | 0.00 |
March | 901.39 | 570.55 | 330.85 | 881.16 | 622.73 | 0.00 | 0.00 | 0.00 |
April | 815.92 | 442.63 | 373.29 | 871.45 | 425.88 | 0.00 | 0.00 | 0.00 |
May | 685.60 | 233.87 | 451.73 | 800.10 | 239.31 | 0.00 | 0.00 | 0.00 |
June | 615.09 | 163.37 | 451.72 | 766.72 | 163.76 | 0.00 | 0.00 | 0.00 |
July | 672.47 | 212.43 | 460.04 | 877.06 | 148.88 | 0.00 | 0.00 | 0.00 |
August | 718.50 | 300.19 | 418.31 | 909.13 | 175.58 | 0.00 | 0.00 | 0.00 |
September | 770.21 | 410.16 | 360.05 | 899.87 | 277.68 | 0.00 | 0.00 | 0.00 |
October | 658.11 | 387.21 | 270.90 | 671.11 | 411.70 | 0.00 | 0.00 | 0.00 |
November | 586.35 | 368.15 | 218.20 | 525.85 | 580.12 | 0.00 | 0.00 | 0.00 |
December | 624.10 | 409.39 | 214.71 | 482.17 | 847.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.11 | 394.12 | 343.99 | 777.41 | 456.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 586.35 | 163.37 | 214.71 | 482.17 | 148.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1023.50 | 691.56 | 460.04 | 978.40 | 858.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.31 | 562.52 | 245.79 | 683.86 | 858.94 | 0.00 | 0.00 | 0.00 |
February | 1023.46 | 691.53 | 331.93 | 978.37 | 736.31 | 0.00 | 0.00 | 0.00 |
March | 901.36 | 570.52 | 330.84 | 881.13 | 622.71 | 0.00 | 0.00 | 0.00 |
April | 815.88 | 442.61 | 373.27 | 871.42 | 425.86 | 0.00 | 0.00 | 0.00 |
May | 685.57 | 233.86 | 451.71 | 800.07 | 239.30 | 0.00 | 0.00 | 0.00 |
June | 615.07 | 163.36 | 451.71 | 766.69 | 163.76 | 0.00 | 0.00 | 0.00 |
July | 672.45 | 212.42 | 460.03 | 877.03 | 148.87 | 0.00 | 0.00 | 0.00 |
August | 718.47 | 300.18 | 418.30 | 909.10 | 175.57 | 0.00 | 0.00 | 0.00 |
September | 770.18 | 410.15 | 360.03 | 899.84 | 277.67 | 0.00 | 0.00 | 0.00 |
October | 658.09 | 387.20 | 270.89 | 671.08 | 411.68 | 0.00 | 0.00 | 0.00 |
November | 586.32 | 368.14 | 218.19 | 525.83 | 580.10 | 0.00 | 0.00 | 0.00 |
December | 624.07 | 409.37 | 214.70 | 482.15 | 847.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.08 | 394.11 | 343.97 | 777.38 | 456.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 586.32 | 163.36 | 214.70 | 482.15 | 148.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1023.46 | 691.53 | 460.03 | 978.37 | 858.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 288.72 | 120.86 | 167.86 | 115.75 | 1143.77 | 0.00 | 0.00 | 0.00 |
February | 470.50 | 214.88 | 255.62 | 295.23 | 961.03 | 0.00 | 0.00 | 0.00 |
March | 619.27 | 316.92 | 302.34 | 475.55 | 797.90 | 0.00 | 0.00 | 0.00 |
April | 791.10 | 400.76 | 390.34 | 736.60 | 525.25 | 0.00 | 0.00 | 0.00 |
May | 972.06 | 463.80 | 508.26 | 1098.91 | 280.05 | 0.00 | 0.00 | 0.00 |
June | 938.03 | 405.73 | 532.30 | 1123.08 | 200.33 | 0.00 | 0.00 | 0.00 |
July | 1001.39 | 465.65 | 535.74 | 1239.00 | 190.11 | 0.00 | 0.00 | 0.00 |
August | 824.03 | 374.50 | 449.53 | 982.98 | 226.12 | 0.00 | 0.00 | 0.00 |
September | 644.02 | 289.40 | 354.61 | 680.54 | 330.01 | 0.00 | 0.00 | 0.00 |
October | 406.78 | 163.31 | 243.47 | 317.77 | 522.66 | 0.00 | 0.00 | 0.00 |
November | 247.00 | 83.24 | 163.75 | 111.51 | 785.71 | 0.00 | 0.00 | 0.00 |
December | 220.16 | 77.01 | 143.15 | 60.36 | 1184.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 619.40 | 281.74 | 337.67 | 604.98 | 594.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 220.16 | 77.01 | 143.15 | 60.36 | 190.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.39 | 465.65 | 535.74 | 1239.00 | 1184.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 288.72 | 120.86 | 167.86 | 115.75 | 1143.77 | 0.00 | 0.00 | 0.00 |
February | 470.50 | 214.88 | 255.62 | 295.23 | 961.03 | 0.00 | 0.00 | 0.00 |
March | 619.27 | 316.92 | 302.34 | 475.55 | 797.90 | 0.00 | 0.00 | 0.00 |
April | 791.10 | 400.76 | 390.34 | 736.60 | 525.25 | 0.00 | 0.00 | 0.00 |
May | 972.06 | 463.80 | 508.26 | 1098.91 | 280.05 | 0.00 | 0.00 | 0.00 |
June | 938.03 | 405.73 | 532.30 | 1123.08 | 200.33 | 0.00 | 0.00 | 0.00 |
July | 1001.39 | 465.65 | 535.74 | 1239.00 | 190.11 | 0.00 | 0.00 | 0.00 |
August | 824.03 | 374.50 | 449.53 | 982.98 | 226.12 | 0.00 | 0.00 | 0.00 |
September | 644.02 | 289.40 | 354.61 | 680.54 | 330.01 | 0.00 | 0.00 | 0.00 |
October | 406.78 | 163.31 | 243.47 | 317.77 | 522.66 | 0.00 | 0.00 | 0.00 |
November | 247.00 | 83.24 | 163.75 | 111.51 | 785.71 | 0.00 | 0.00 | 0.00 |
December | 220.16 | 77.01 | 143.15 | 60.36 | 1184.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 619.40 | 281.74 | 337.67 | 604.98 | 594.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 220.16 | 77.01 | 143.15 | 60.36 | 190.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.39 | 465.65 | 535.74 | 1239.00 | 1184.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 288.71 | 120.85 | 167.86 | 115.75 | 1143.75 | 0.00 | 0.00 | 0.00 |
February | 470.49 | 214.88 | 255.61 | 295.22 | 961.01 | 0.00 | 0.00 | 0.00 |
March | 619.26 | 316.92 | 302.34 | 475.54 | 797.88 | 0.00 | 0.00 | 0.00 |
April | 791.09 | 400.75 | 390.34 | 736.59 | 525.24 | 0.00 | 0.00 | 0.00 |
May | 972.04 | 463.79 | 508.25 | 1098.89 | 280.05 | 0.00 | 0.00 | 0.00 |
June | 938.01 | 405.72 | 532.29 | 1123.06 | 200.33 | 0.00 | 0.00 | 0.00 |
July | 1001.37 | 465.64 | 535.73 | 1238.98 | 190.10 | 0.00 | 0.00 | 0.00 |
August | 824.01 | 374.49 | 449.52 | 982.97 | 226.12 | 0.00 | 0.00 | 0.00 |
September | 644.00 | 289.40 | 354.61 | 680.52 | 330.00 | 0.00 | 0.00 | 0.00 |
October | 406.77 | 163.30 | 243.47 | 317.77 | 522.66 | 0.00 | 0.00 | 0.00 |
November | 246.99 | 83.24 | 163.75 | 111.51 | 785.70 | 0.00 | 0.00 | 0.00 |
December | 220.15 | 77.01 | 143.15 | 60.36 | 1184.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 619.39 | 281.73 | 337.66 | 604.97 | 594.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 220.15 | 77.01 | 143.15 | 60.36 | 190.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.37 | 465.64 | 535.73 | 1238.98 | 1184.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 586.46 | 0.00 | 586.46 | 7.70 | 5166.27 | 0.00 | 0.00 | 0.00 |
February | 900.85 | 0.00 | 900.85 | 82.53 | 4098.58 | 0.00 | 0.00 | 0.00 |
March | 1108.34 | 0.00 | 1108.34 | 187.69 | 3215.60 | 0.00 | 0.00 | 0.00 |
April | 1452.80 | 11.17 | 1441.63 | 698.46 | 1950.97 | 0.00 | 0.00 | 0.00 |
May | 2042.72 | 109.21 | 1933.50 | 1838.30 | 1043.18 | 0.00 | 0.00 | 0.00 |
June | 2279.36 | 249.43 | 2029.93 | 2520.37 | 721.10 | 0.00 | 0.00 | 0.00 |
July | 2177.26 | 185.85 | 1991.42 | 2530.11 | 673.32 | 0.00 | 0.00 | 0.00 |
August | 1654.22 | 28.10 | 1626.12 | 1737.45 | 792.54 | 0.00 | 0.00 | 0.00 |
September | 1289.32 | 0.31 | 1289.01 | 988.53 | 1306.95 | 0.00 | 0.00 | 0.00 |
October | 895.24 | 0.00 | 895.24 | 333.06 | 2009.34 | 0.00 | 0.00 | 0.00 |
November | 592.77 | 0.00 | 592.77 | 48.55 | 3044.07 | 0.00 | 0.00 | 0.00 |
December | 496.90 | 0.00 | 496.90 | 0.67 | 4952.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1291.64 | 48.89 | 1242.74 | 919.65 | 2407.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.90 | 0.00 | 496.90 | 0.67 | 673.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2279.36 | 249.43 | 2029.93 | 2530.11 | 5166.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 856.89 | 357.52 | 499.37 | 336.19 | 3099.88 | 0.00 | 0.00 | 0.00 |
February | 1346.79 | 574.37 | 772.42 | 807.14 | 2462.25 | 0.00 | 0.00 | 0.00 |
March | 1835.62 | 920.91 | 914.71 | 1389.23 | 1989.85 | 0.00 | 0.00 | 0.00 |
April | 2544.85 | 1372.88 | 1171.97 | 2447.02 | 1254.89 | 0.00 | 0.00 | 0.00 |
May | 2754.21 | 1211.07 | 1543.14 | 3034.49 | 716.32 | 0.00 | 0.00 | 0.00 |
June | 3118.19 | 1492.03 | 1626.17 | 3769.12 | 501.52 | 0.00 | 0.00 | 0.00 |
July | 3054.63 | 1434.66 | 1619.98 | 3795.32 | 463.61 | 0.00 | 0.00 | 0.00 |
August | 2354.97 | 1029.52 | 1325.45 | 2804.60 | 540.55 | 0.00 | 0.00 | 0.00 |
September | 1885.90 | 844.28 | 1041.62 | 1977.28 | 852.06 | 0.00 | 0.00 | 0.00 |
October | 1141.80 | 432.99 | 708.81 | 869.69 | 1289.00 | 0.00 | 0.00 | 0.00 |
November | 726.68 | 242.83 | 483.85 | 347.33 | 1888.51 | 0.00 | 0.00 | 0.00 |
December | 663.02 | 244.92 | 418.10 | 207.59 | 3009.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1858.83 | 847.18 | 1011.65 | 1820.20 | 1501.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 663.02 | 242.83 | 418.10 | 207.59 | 463.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3118.19 | 1492.03 | 1626.17 | 3795.32 | 3099.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4041.65 | 2812.66 | 1228.98 | 3435.84 | 4178.25 | 0.00 | 0.00 | 0.00 |
February | 5117.45 | 3457.76 | 1659.70 | 4896.72 | 3550.87 | 0.00 | 0.00 | 0.00 |
March | 4506.92 | 2852.70 | 1654.22 | 4406.26 | 3001.90 | 0.00 | 0.00 | 0.00 |
April | 4079.53 | 2213.11 | 1866.42 | 4358.43 | 2033.78 | 0.00 | 0.00 | 0.00 |
May | 3427.95 | 1169.33 | 2258.63 | 3983.45 | 1172.54 | 0.00 | 0.00 | 0.00 |
June | 3075.42 | 816.82 | 2258.60 | 3825.56 | 798.33 | 0.00 | 0.00 | 0.00 |
July | 3362.32 | 1062.13 | 2300.19 | 4373.48 | 736.80 | 0.00 | 0.00 | 0.00 |
August | 3592.47 | 1500.93 | 2091.54 | 4531.80 | 861.27 | 0.00 | 0.00 | 0.00 |
September | 3851.00 | 2050.79 | 1800.21 | 4476.72 | 1361.72 | 0.00 | 0.00 | 0.00 |
October | 3290.52 | 1936.04 | 1354.48 | 3359.51 | 1978.62 | 0.00 | 0.00 | 0.00 |
November | 2931.70 | 1840.73 | 1090.97 | 2654.19 | 2729.64 | 0.00 | 0.00 | 0.00 |
December | 3120.46 | 2046.92 | 1073.54 | 2442.81 | 4043.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3690.49 | 1970.58 | 1719.91 | 3887.90 | 2198.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2931.70 | 816.82 | 1073.54 | 2442.81 | 736.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5117.45 | 3457.76 | 2300.19 | 4896.72 | 4178.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.14 | 362.57 | 503.58 | 368.88 | 3213.98 | 0.00 | 0.00 | 0.00 |
February | 1411.48 | 644.64 | 766.85 | 932.27 | 2605.91 | 0.00 | 0.00 | 0.00 |
March | 1857.78 | 950.76 | 907.02 | 1477.49 | 2108.34 | 0.00 | 0.00 | 0.00 |
April | 2373.28 | 1202.26 | 1171.02 | 2274.90 | 1360.39 | 0.00 | 0.00 | 0.00 |
May | 2916.15 | 1391.39 | 1524.77 | 3308.83 | 791.60 | 0.00 | 0.00 | 0.00 |
June | 2814.05 | 1217.17 | 1596.88 | 3392.69 | 548.32 | 0.00 | 0.00 | 0.00 |
July | 3004.13 | 1396.94 | 1607.19 | 3743.03 | 520.24 | 0.00 | 0.00 | 0.00 |
August | 2472.06 | 1123.49 | 1348.57 | 2984.67 | 597.10 | 0.00 | 0.00 | 0.00 |
September | 1932.03 | 868.20 | 1063.83 | 2060.30 | 915.71 | 0.00 | 0.00 | 0.00 |
October | 1220.32 | 489.91 | 730.41 | 999.89 | 1363.70 | 0.00 | 0.00 | 0.00 |
November | 740.98 | 249.72 | 491.26 | 373.84 | 1974.27 | 0.00 | 0.00 | 0.00 |
December | 660.46 | 231.02 | 429.44 | 204.25 | 3118.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1858.19 | 845.20 | 1012.99 | 1848.91 | 1589.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 660.46 | 231.02 | 429.44 | 204.25 | 520.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3004.13 | 1396.94 | 1607.19 | 3743.03 | 3213.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 586.46 | 0.00 | 586.46 | 9.61 | 5089.73 | 0.00 | 0.00 | 0.00 |
February | 900.85 | 0.00 | 900.85 | 90.57 | 3998.64 | 0.00 | 0.00 | 0.00 |
March | 1108.34 | 0.00 | 1108.34 | 208.79 | 3086.18 | 0.00 | 0.00 | 0.00 |
April | 1452.80 | 11.17 | 1441.63 | 749.75 | 1815.12 | 0.00 | 0.00 | 0.00 |
May | 2042.72 | 109.21 | 1933.50 | 1868.20 | 998.45 | 0.00 | 0.00 | 0.00 |
June | 2279.36 | 249.43 | 2029.93 | 2528.63 | 699.54 | 0.00 | 0.00 | 0.00 |
July | 2177.26 | 185.85 | 1991.42 | 2530.54 | 660.81 | 0.00 | 0.00 | 0.00 |
August | 1654.22 | 28.10 | 1626.12 | 1743.24 | 769.43 | 0.00 | 0.00 | 0.00 |
September | 1289.32 | 0.31 | 1289.01 | 1024.65 | 1225.10 | 0.00 | 0.00 | 0.00 |
October | 895.24 | 0.00 | 895.24 | 383.95 | 1827.49 | 0.00 | 0.00 | 0.00 |
November | 592.77 | 0.00 | 592.77 | 60.05 | 2877.57 | 0.00 | 0.00 | 0.00 |
December | 496.90 | 0.00 | 496.90 | 1.52 | 4862.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1291.64 | 48.89 | 1242.74 | 938.49 | 2319.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.90 | 0.00 | 496.90 | 1.52 | 660.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2279.36 | 249.43 | 2029.93 | 2530.54 | 5089.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 856.89 | 357.52 | 499.37 | 339.88 | 3067.91 | 0.00 | 0.00 | 0.00 |
February | 1346.79 | 574.37 | 772.42 | 823.06 | 2402.59 | 0.00 | 0.00 | 0.00 |
March | 1835.62 | 920.91 | 914.71 | 1416.06 | 1903.41 | 0.00 | 0.00 | 0.00 |
April | 2544.85 | 1372.88 | 1171.97 | 2483.70 | 1173.23 | 0.00 | 0.00 | 0.00 |
May | 2754.21 | 1211.07 | 1543.14 | 3047.51 | 691.37 | 0.00 | 0.00 | 0.00 |
June | 3118.19 | 1492.03 | 1626.17 | 3772.54 | 488.13 | 0.00 | 0.00 | 0.00 |
July | 3054.63 | 1434.66 | 1619.98 | 3796.10 | 456.07 | 0.00 | 0.00 | 0.00 |
August | 2354.97 | 1029.52 | 1325.45 | 2807.03 | 527.82 | 0.00 | 0.00 | 0.00 |
September | 1885.90 | 844.28 | 1041.62 | 1999.38 | 807.69 | 0.00 | 0.00 | 0.00 |
October | 1141.80 | 432.99 | 708.81 | 914.18 | 1175.39 | 0.00 | 0.00 | 0.00 |
November | 726.68 | 242.83 | 483.85 | 365.35 | 1780.55 | 0.00 | 0.00 | 0.00 |
December | 663.02 | 244.92 | 418.10 | 210.84 | 2969.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1858.83 | 847.18 | 1011.65 | 1836.04 | 1450.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 663.02 | 242.83 | 418.10 | 210.84 | 456.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3118.19 | 1492.03 | 1626.17 | 3796.10 | 3067.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4041.65 | 2812.66 | 1228.98 | 3453.19 | 4098.13 | 0.00 | 0.00 | 0.00 |
February | 5117.45 | 3457.76 | 1659.70 | 4926.70 | 3436.84 | 0.00 | 0.00 | 0.00 |
March | 4506.92 | 2852.70 | 1654.22 | 4440.74 | 2869.92 | 0.00 | 0.00 | 0.00 |
April | 4079.53 | 2213.11 | 1866.42 | 4398.55 | 1904.32 | 0.00 | 0.00 | 0.00 |
May | 3427.95 | 1169.33 | 2258.63 | 3993.74 | 1127.19 | 0.00 | 0.00 | 0.00 |
June | 3075.42 | 816.82 | 2258.60 | 3826.11 | 775.08 | 0.00 | 0.00 | 0.00 |
July | 3362.32 | 1062.13 | 2300.19 | 4367.57 | 723.65 | 0.00 | 0.00 | 0.00 |
August | 3592.47 | 1500.93 | 2091.54 | 4526.50 | 841.05 | 0.00 | 0.00 | 0.00 |
September | 3851.00 | 2050.79 | 1800.21 | 4494.27 | 1294.86 | 0.00 | 0.00 | 0.00 |
October | 3290.52 | 1936.04 | 1354.48 | 3417.14 | 1816.13 | 0.00 | 0.00 | 0.00 |
November | 2931.70 | 1840.73 | 1090.97 | 2698.58 | 2560.75 | 0.00 | 0.00 | 0.00 |
December | 3120.46 | 2046.92 | 1073.54 | 2463.22 | 3953.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3690.49 | 1970.58 | 1719.91 | 3909.58 | 2111.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2931.70 | 816.82 | 1073.54 | 2463.22 | 723.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5117.45 | 3457.76 | 2300.19 | 4926.70 | 4098.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.14 | 362.57 | 503.58 | 372.35 | 3163.31 | 0.00 | 0.00 | 0.00 |
February | 1411.48 | 644.64 | 766.85 | 940.54 | 2541.65 | 0.00 | 0.00 | 0.00 |
March | 1857.78 | 950.76 | 907.02 | 1492.86 | 2028.48 | 0.00 | 0.00 | 0.00 |
April | 2373.28 | 1202.26 | 1171.02 | 2300.92 | 1282.42 | 0.00 | 0.00 | 0.00 |
May | 2916.15 | 1391.39 | 1524.77 | 3314.01 | 764.87 | 0.00 | 0.00 | 0.00 |
June | 2814.05 | 1217.17 | 1596.88 | 3390.37 | 534.44 | 0.00 | 0.00 | 0.00 |
July | 3004.13 | 1396.94 | 1607.19 | 3736.28 | 511.83 | 0.00 | 0.00 | 0.00 |
August | 2472.06 | 1123.49 | 1348.57 | 2980.62 | 584.42 | 0.00 | 0.00 | 0.00 |
September | 1932.03 | 868.20 | 1063.83 | 2072.73 | 873.49 | 0.00 | 0.00 | 0.00 |
October | 1220.32 | 489.91 | 730.41 | 1029.99 | 1264.02 | 0.00 | 0.00 | 0.00 |
November | 740.98 | 249.72 | 491.26 | 388.21 | 1874.50 | 0.00 | 0.00 | 0.00 |
December | 660.46 | 231.02 | 429.44 | 207.54 | 3066.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1858.19 | 845.20 | 1012.99 | 1857.66 | 1536.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 660.46 | 231.02 | 429.44 | 207.54 | 511.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3004.13 | 1396.94 | 1607.19 | 3736.28 | 3163.31 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314161E+09 | 0.00 | 0.314161E+09 | 1165059.96 | 0.290923E+10 |
February | 0.435874E+09 | 0.00 | 0.435874E+09 | 23702616.08 | 0.213769E+10 |
March | 0.593725E+09 | 0.00 | 0.593725E+09 | 76310840.59 | 0.188722E+10 |
April | 0.753140E+09 | 5790844.06 | 0.747349E+09 | 0.320417E+09 | 0.112984E+10 |
May | 0.109426E+10 | 58503709.75 | 0.103575E+10 | 0.972865E+09 | 0.584351E+09 |
June | 0.118163E+10 | 0.129305E+09 | 0.105233E+10 | 0.129914E+10 | 0.388575E+09 |
July | 0.116633E+10 | 99556376.96 | 0.106677E+10 | 0.134811E+10 | 0.368540E+09 |
August | 0.886144E+09 | 15053987.06 | 0.871091E+09 | 0.916734E+09 | 0.445426E+09 |
September | 0.668392E+09 | 159433.89 | 0.668233E+09 | 0.496466E+09 | 0.723196E+09 |
October | 0.479571E+09 | 0.00 | 0.479571E+09 | 0.147401E+09 | 0.120756E+10 |
November | 0.307294E+09 | 0.00 | 0.307294E+09 | 16035292.14 | 0.179533E+10 |
December | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.285646E+10 |
Annual Sum or Average | 0.814670E+10 | 0.308370E+09 | 0.783833E+10 | 0.561835E+10 | 0.164334E+11 |
Minimum of Months | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.368540E+09 |
Maximum of Months | 0.118163E+10 | 0.129305E+09 | 0.106677E+10 | 0.134811E+10 | 0.290923E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314160E+09 | 0.00 | 0.314160E+09 | 1165051.30 | 0.290923E+10 |
February | 0.435874E+09 | 0.00 | 0.435874E+09 | 23702522.78 | 0.213769E+10 |
March | 0.593724E+09 | 0.00 | 0.593724E+09 | 76310614.33 | 0.188722E+10 |
April | 0.753140E+09 | 5790837.12 | 0.747349E+09 | 0.320417E+09 | 0.112984E+10 |
May | 0.109426E+10 | 58503639.55 | 0.103575E+10 | 0.972864E+09 | 0.584351E+09 |
June | 0.118163E+10 | 0.129305E+09 | 0.105233E+10 | 0.129914E+10 | 0.388575E+09 |
July | 0.116633E+10 | 99556257.50 | 0.106677E+10 | 0.134811E+10 | 0.368540E+09 |
August | 0.886144E+09 | 15053968.99 | 0.871090E+09 | 0.916734E+09 | 0.445426E+09 |
September | 0.668392E+09 | 159433.70 | 0.668232E+09 | 0.496465E+09 | 0.723196E+09 |
October | 0.479570E+09 | 0.00 | 0.479570E+09 | 0.147401E+09 | 0.120756E+10 |
November | 0.307293E+09 | 0.00 | 0.307293E+09 | 16035242.55 | 0.179533E+10 |
December | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.285646E+10 |
Annual Sum or Average | 0.814670E+10 | 0.308369E+09 | 0.783833E+10 | 0.561835E+10 | 0.164334E+11 |
Minimum of Months | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.368540E+09 |
Maximum of Months | 0.118163E+10 | 0.129305E+09 | 0.106677E+10 | 0.134811E+10 | 0.290923E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314161E+09 | 0.00 | 0.314161E+09 | 1165059.96 | 0.290923E+10 |
February | 0.435874E+09 | 0.00 | 0.435874E+09 | 23702616.08 | 0.213769E+10 |
March | 0.593725E+09 | 0.00 | 0.593725E+09 | 76310840.59 | 0.188722E+10 |
April | 0.753140E+09 | 5790844.06 | 0.747349E+09 | 0.320417E+09 | 0.112984E+10 |
May | 0.109426E+10 | 58503709.75 | 0.103575E+10 | 0.972865E+09 | 0.584351E+09 |
June | 0.118163E+10 | 0.129305E+09 | 0.105233E+10 | 0.129914E+10 | 0.388575E+09 |
July | 0.116633E+10 | 99556376.96 | 0.106677E+10 | 0.134811E+10 | 0.368540E+09 |
August | 0.886144E+09 | 15053987.06 | 0.871091E+09 | 0.916734E+09 | 0.445426E+09 |
September | 0.668392E+09 | 159433.89 | 0.668233E+09 | 0.496466E+09 | 0.723196E+09 |
October | 0.479571E+09 | 0.00 | 0.479571E+09 | 0.147401E+09 | 0.120756E+10 |
November | 0.307294E+09 | 0.00 | 0.307294E+09 | 16035292.14 | 0.179533E+10 |
December | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.285646E+10 |
Annual Sum or Average | 0.814670E+10 | 0.308370E+09 | 0.783833E+10 | 0.561835E+10 | 0.164334E+11 |
Minimum of Months | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.368540E+09 |
Maximum of Months | 0.118163E+10 | 0.129305E+09 | 0.106677E+10 | 0.134811E+10 | 0.290923E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314160E+09 | 0.00 | 0.314160E+09 | 1165051.30 | 0.290923E+10 |
February | 0.435874E+09 | 0.00 | 0.435874E+09 | 23702522.78 | 0.213769E+10 |
March | 0.593724E+09 | 0.00 | 0.593724E+09 | 76310614.33 | 0.188722E+10 |
April | 0.753140E+09 | 5790837.12 | 0.747349E+09 | 0.320417E+09 | 0.112984E+10 |
May | 0.109426E+10 | 58503639.55 | 0.103575E+10 | 0.972864E+09 | 0.584351E+09 |
June | 0.118163E+10 | 0.129305E+09 | 0.105233E+10 | 0.129914E+10 | 0.388575E+09 |
July | 0.116633E+10 | 99556257.50 | 0.106677E+10 | 0.134811E+10 | 0.368540E+09 |
August | 0.886144E+09 | 15053968.99 | 0.871090E+09 | 0.916734E+09 | 0.445426E+09 |
September | 0.668392E+09 | 159433.70 | 0.668232E+09 | 0.496465E+09 | 0.723196E+09 |
October | 0.479570E+09 | 0.00 | 0.479570E+09 | 0.147401E+09 | 0.120756E+10 |
November | 0.307293E+09 | 0.00 | 0.307293E+09 | 16035242.55 | 0.179533E+10 |
December | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.285646E+10 |
Annual Sum or Average | 0.814670E+10 | 0.308369E+09 | 0.783833E+10 | 0.561835E+10 | 0.164334E+11 |
Minimum of Months | 0.266182E+09 | 0.00 | 0.266182E+09 | 0.00 | 0.368540E+09 |
Maximum of Months | 0.118163E+10 | 0.129305E+09 | 0.106677E+10 | 0.134811E+10 | 0.290923E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314148E+09 | 0.00 | 0.314148E+09 | 1165013.00 | 0.290912E+10 |
February | 0.435857E+09 | 0.00 | 0.435857E+09 | 23701660.76 | 0.213760E+10 |
March | 0.593701E+09 | 0.00 | 0.593701E+09 | 76307764.93 | 0.188714E+10 |
April | 0.753110E+09 | 5790610.67 | 0.747319E+09 | 0.320404E+09 | 0.112979E+10 |
May | 0.109421E+10 | 58501351.79 | 0.103571E+10 | 0.972826E+09 | 0.584327E+09 |
June | 0.118159E+10 | 0.129300E+09 | 0.105229E+10 | 0.129909E+10 | 0.388559E+09 |
July | 0.116628E+10 | 99552364.39 | 0.106673E+10 | 0.134806E+10 | 0.368525E+09 |
August | 0.886109E+09 | 15053380.31 | 0.871055E+09 | 0.916698E+09 | 0.445408E+09 |
September | 0.668365E+09 | 159427.47 | 0.668206E+09 | 0.496446E+09 | 0.723167E+09 |
October | 0.479551E+09 | 0.00 | 0.479551E+09 | 0.147395E+09 | 0.120752E+10 |
November | 0.307281E+09 | 0.00 | 0.307281E+09 | 16034645.84 | 0.179525E+10 |
December | 0.266171E+09 | 0.00 | 0.266171E+09 | 0.00 | 0.285634E+10 |
Annual Sum or Average | 0.814637E+10 | 0.308357E+09 | 0.783802E+10 | 0.561813E+10 | 0.164328E+11 |
Minimum of Months | 0.266171E+09 | 0.00 | 0.266171E+09 | 0.00 | 0.368525E+09 |
Maximum of Months | 0.118159E+10 | 0.129300E+09 | 0.106673E+10 | 0.134806E+10 | 0.290912E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.765036E+09 | 0.319198E+09 | 0.445838E+09 | 0.285123E+09 | 0.290828E+10 |
February | 0.108606E+10 | 0.463174E+09 | 0.622885E+09 | 0.621113E+09 | 0.212667E+10 |
March | 0.163886E+10 | 0.822195E+09 | 0.816661E+09 | 0.122327E+10 | 0.190051E+10 |
April | 0.219877E+10 | 0.118618E+10 | 0.101259E+10 | 0.210749E+10 | 0.115650E+10 |
May | 0.245899E+10 | 0.108125E+10 | 0.137773E+10 | 0.272734E+10 | 0.654104E+09 |
June | 0.269415E+10 | 0.128913E+10 | 0.140502E+10 | 0.327722E+10 | 0.438567E+09 |
July | 0.272720E+10 | 0.128087E+10 | 0.144633E+10 | 0.341026E+10 | 0.407969E+09 |
August | 0.210254E+10 | 0.919167E+09 | 0.118337E+10 | 0.252123E+10 | 0.481361E+09 |
September | 0.162943E+10 | 0.729464E+09 | 0.899966E+09 | 0.171297E+10 | 0.764168E+09 |
October | 0.101941E+10 | 0.386575E+09 | 0.632833E+09 | 0.755275E+09 | 0.124955E+10 |
November | 0.627862E+09 | 0.209810E+09 | 0.418053E+09 | 0.280195E+09 | 0.181655E+10 |
December | 0.591949E+09 | 0.218663E+09 | 0.373286E+09 | 0.173439E+09 | 0.287407E+10 |
Annual Sum or Average | 0.195402E+11 | 0.890568E+10 | 0.106346E+11 | 0.190949E+11 | 0.167783E+11 |
Minimum of Months | 0.591949E+09 | 0.209810E+09 | 0.373286E+09 | 0.173439E+09 | 0.407969E+09 |
Maximum of Months | 0.272720E+10 | 0.128913E+10 | 0.144633E+10 | 0.341026E+10 | 0.290828E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.765036E+09 | 0.319198E+09 | 0.445838E+09 | 0.285123E+09 | 0.290828E+10 |
February | 0.108606E+10 | 0.463174E+09 | 0.622885E+09 | 0.621113E+09 | 0.212667E+10 |
March | 0.163886E+10 | 0.822195E+09 | 0.816661E+09 | 0.122327E+10 | 0.190051E+10 |
April | 0.219877E+10 | 0.118618E+10 | 0.101259E+10 | 0.210749E+10 | 0.115650E+10 |
May | 0.245899E+10 | 0.108125E+10 | 0.137773E+10 | 0.272734E+10 | 0.654104E+09 |
June | 0.269415E+10 | 0.128913E+10 | 0.140502E+10 | 0.327722E+10 | 0.438567E+09 |
July | 0.272720E+10 | 0.128087E+10 | 0.144633E+10 | 0.341026E+10 | 0.407969E+09 |
August | 0.210254E+10 | 0.919167E+09 | 0.118337E+10 | 0.252123E+10 | 0.481361E+09 |
September | 0.162943E+10 | 0.729464E+09 | 0.899966E+09 | 0.171297E+10 | 0.764168E+09 |
October | 0.101941E+10 | 0.386575E+09 | 0.632833E+09 | 0.755275E+09 | 0.124955E+10 |
November | 0.627862E+09 | 0.209810E+09 | 0.418053E+09 | 0.280195E+09 | 0.181655E+10 |
December | 0.591949E+09 | 0.218663E+09 | 0.373286E+09 | 0.173439E+09 | 0.287407E+10 |
Annual Sum or Average | 0.195402E+11 | 0.890568E+10 | 0.106346E+11 | 0.190949E+11 | 0.167783E+11 |
Minimum of Months | 0.591949E+09 | 0.209810E+09 | 0.373286E+09 | 0.173439E+09 | 0.407969E+09 |
Maximum of Months | 0.272720E+10 | 0.128913E+10 | 0.144633E+10 | 0.341026E+10 | 0.290828E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.765022E+09 | 0.319192E+09 | 0.445830E+09 | 0.285117E+09 | 0.290823E+10 |
February | 0.108604E+10 | 0.463166E+09 | 0.622874E+09 | 0.621101E+09 | 0.212663E+10 |
March | 0.163883E+10 | 0.822180E+09 | 0.816646E+09 | 0.122325E+10 | 0.190048E+10 |
April | 0.219873E+10 | 0.118616E+10 | 0.101257E+10 | 0.210746E+10 | 0.115648E+10 |
May | 0.245894E+10 | 0.108123E+10 | 0.137771E+10 | 0.272729E+10 | 0.654092E+09 |
June | 0.269410E+10 | 0.128910E+10 | 0.140500E+10 | 0.327716E+10 | 0.438559E+09 |
July | 0.272715E+10 | 0.128085E+10 | 0.144630E+10 | 0.341019E+10 | 0.407962E+09 |
August | 0.210250E+10 | 0.919150E+09 | 0.118335E+10 | 0.252118E+10 | 0.481352E+09 |
September | 0.162940E+10 | 0.729451E+09 | 0.899950E+09 | 0.171294E+10 | 0.764154E+09 |
October | 0.101939E+10 | 0.386568E+09 | 0.632821E+09 | 0.755261E+09 | 0.124953E+10 |
November | 0.627851E+09 | 0.209806E+09 | 0.418045E+09 | 0.280190E+09 | 0.181652E+10 |
December | 0.591938E+09 | 0.218659E+09 | 0.373279E+09 | 0.173436E+09 | 0.287402E+10 |
Annual Sum or Average | 0.195399E+11 | 0.890552E+10 | 0.106344E+11 | 0.190946E+11 | 0.167780E+11 |
Minimum of Months | 0.591938E+09 | 0.209806E+09 | 0.373279E+09 | 0.173436E+09 | 0.407962E+09 |
Maximum of Months | 0.272715E+10 | 0.128910E+10 | 0.144630E+10 | 0.341019E+10 | 0.290823E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216506E+10 | 0.150671E+10 | 0.658349E+09 | 0.183173E+10 | 0.230067E+10 |
February | 0.247606E+10 | 0.167302E+10 | 0.803039E+09 | 0.236696E+10 | 0.178134E+10 |
March | 0.241430E+10 | 0.152815E+10 | 0.886145E+09 | 0.236010E+10 | 0.166792E+10 |
April | 0.211485E+10 | 0.114729E+10 | 0.967563E+09 | 0.225880E+10 | 0.110387E+10 |
May | 0.183631E+10 | 0.626392E+09 | 0.120992E+10 | 0.214299E+10 | 0.640975E+09 |
June | 0.159432E+10 | 0.423446E+09 | 0.117087E+10 | 0.198733E+10 | 0.424477E+09 |
July | 0.180115E+10 | 0.568967E+09 | 0.123218E+10 | 0.234913E+10 | 0.398760E+09 |
August | 0.192444E+10 | 0.804027E+09 | 0.112041E+10 | 0.243503E+10 | 0.470274E+09 |
September | 0.199638E+10 | 0.106314E+10 | 0.933241E+09 | 0.233247E+10 | 0.719755E+09 |
October | 0.176269E+10 | 0.103711E+10 | 0.725577E+09 | 0.179750E+10 | 0.110270E+10 |
November | 0.151981E+10 | 0.954248E+09 | 0.565565E+09 | 0.136300E+10 | 0.150367E+10 |
December | 0.167159E+10 | 0.109651E+10 | 0.575081E+09 | 0.129143E+10 | 0.227026E+10 |
Annual Sum or Average | 0.232770E+11 | 0.124290E+11 | 0.108479E+11 | 0.245165E+11 | 0.143847E+11 |
Minimum of Months | 0.151981E+10 | 0.423446E+09 | 0.565565E+09 | 0.129143E+10 | 0.398760E+09 |
Maximum of Months | 0.247606E+10 | 0.167302E+10 | 0.123218E+10 | 0.243503E+10 | 0.230067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216505E+10 | 0.150670E+10 | 0.658349E+09 | 0.183172E+10 | 0.230067E+10 |
February | 0.247606E+10 | 0.167302E+10 | 0.803038E+09 | 0.236695E+10 | 0.178134E+10 |
March | 0.241429E+10 | 0.152815E+10 | 0.886144E+09 | 0.236010E+10 | 0.166792E+10 |
April | 0.211485E+10 | 0.114729E+10 | 0.967562E+09 | 0.225880E+10 | 0.110387E+10 |
May | 0.183631E+10 | 0.626391E+09 | 0.120991E+10 | 0.214298E+10 | 0.640975E+09 |
June | 0.159432E+10 | 0.423445E+09 | 0.117087E+10 | 0.198733E+10 | 0.424477E+09 |
July | 0.180115E+10 | 0.568967E+09 | 0.123218E+10 | 0.234913E+10 | 0.398760E+09 |
August | 0.192444E+10 | 0.804026E+09 | 0.112041E+10 | 0.243502E+10 | 0.470274E+09 |
September | 0.199638E+10 | 0.106314E+10 | 0.933240E+09 | 0.233247E+10 | 0.719755E+09 |
October | 0.176269E+10 | 0.103711E+10 | 0.725576E+09 | 0.179750E+10 | 0.110270E+10 |
November | 0.151981E+10 | 0.954246E+09 | 0.565564E+09 | 0.136300E+10 | 0.150367E+10 |
December | 0.167159E+10 | 0.109651E+10 | 0.575080E+09 | 0.129143E+10 | 0.227026E+10 |
Annual Sum or Average | 0.232769E+11 | 0.124290E+11 | 0.108479E+11 | 0.245164E+11 | 0.143847E+11 |
Minimum of Months | 0.151981E+10 | 0.423445E+09 | 0.565564E+09 | 0.129143E+10 | 0.398760E+09 |
Maximum of Months | 0.247606E+10 | 0.167302E+10 | 0.123218E+10 | 0.243502E+10 | 0.230067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216506E+10 | 0.150671E+10 | 0.658349E+09 | 0.183173E+10 | 0.230067E+10 |
February | 0.247606E+10 | 0.167302E+10 | 0.803039E+09 | 0.236696E+10 | 0.178134E+10 |
March | 0.241430E+10 | 0.152815E+10 | 0.886145E+09 | 0.236010E+10 | 0.166792E+10 |
April | 0.211485E+10 | 0.114729E+10 | 0.967563E+09 | 0.225880E+10 | 0.110387E+10 |
May | 0.183631E+10 | 0.626392E+09 | 0.120992E+10 | 0.214299E+10 | 0.640975E+09 |
June | 0.159432E+10 | 0.423446E+09 | 0.117087E+10 | 0.198733E+10 | 0.424477E+09 |
July | 0.180115E+10 | 0.568967E+09 | 0.123218E+10 | 0.234913E+10 | 0.398760E+09 |
August | 0.192444E+10 | 0.804027E+09 | 0.112041E+10 | 0.243503E+10 | 0.470274E+09 |
September | 0.199638E+10 | 0.106314E+10 | 0.933241E+09 | 0.233247E+10 | 0.719755E+09 |
October | 0.176269E+10 | 0.103711E+10 | 0.725577E+09 | 0.179750E+10 | 0.110270E+10 |
November | 0.151981E+10 | 0.954248E+09 | 0.565565E+09 | 0.136300E+10 | 0.150367E+10 |
December | 0.167159E+10 | 0.109651E+10 | 0.575081E+09 | 0.129143E+10 | 0.227026E+10 |
Annual Sum or Average | 0.232770E+11 | 0.124290E+11 | 0.108479E+11 | 0.245165E+11 | 0.143847E+11 |
Minimum of Months | 0.151981E+10 | 0.423446E+09 | 0.565565E+09 | 0.129143E+10 | 0.398760E+09 |
Maximum of Months | 0.247606E+10 | 0.167302E+10 | 0.123218E+10 | 0.243503E+10 | 0.230067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216505E+10 | 0.150670E+10 | 0.658349E+09 | 0.183172E+10 | 0.230067E+10 |
February | 0.247606E+10 | 0.167302E+10 | 0.803038E+09 | 0.236695E+10 | 0.178134E+10 |
March | 0.241429E+10 | 0.152815E+10 | 0.886144E+09 | 0.236010E+10 | 0.166792E+10 |
April | 0.211485E+10 | 0.114729E+10 | 0.967562E+09 | 0.225880E+10 | 0.110387E+10 |
May | 0.183631E+10 | 0.626391E+09 | 0.120991E+10 | 0.214298E+10 | 0.640975E+09 |
June | 0.159432E+10 | 0.423445E+09 | 0.117087E+10 | 0.198733E+10 | 0.424477E+09 |
July | 0.180115E+10 | 0.568967E+09 | 0.123218E+10 | 0.234913E+10 | 0.398760E+09 |
August | 0.192444E+10 | 0.804026E+09 | 0.112041E+10 | 0.243502E+10 | 0.470274E+09 |
September | 0.199638E+10 | 0.106314E+10 | 0.933240E+09 | 0.233247E+10 | 0.719755E+09 |
October | 0.176269E+10 | 0.103711E+10 | 0.725576E+09 | 0.179750E+10 | 0.110270E+10 |
November | 0.151981E+10 | 0.954246E+09 | 0.565564E+09 | 0.136300E+10 | 0.150367E+10 |
December | 0.167159E+10 | 0.109651E+10 | 0.575080E+09 | 0.129143E+10 | 0.227026E+10 |
Annual Sum or Average | 0.232769E+11 | 0.124290E+11 | 0.108479E+11 | 0.245164E+11 | 0.143847E+11 |
Minimum of Months | 0.151981E+10 | 0.423445E+09 | 0.565564E+09 | 0.129143E+10 | 0.398760E+09 |
Maximum of Months | 0.247606E+10 | 0.167302E+10 | 0.123218E+10 | 0.243502E+10 | 0.230067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216497E+10 | 0.150665E+10 | 0.658323E+09 | 0.183165E+10 | 0.230057E+10 |
February | 0.247596E+10 | 0.167295E+10 | 0.803007E+09 | 0.236686E+10 | 0.178127E+10 |
March | 0.241420E+10 | 0.152809E+10 | 0.886109E+09 | 0.236001E+10 | 0.166786E+10 |
April | 0.211477E+10 | 0.114724E+10 | 0.967524E+09 | 0.225871E+10 | 0.110383E+10 |
May | 0.183623E+10 | 0.626366E+09 | 0.120987E+10 | 0.214290E+10 | 0.640949E+09 |
June | 0.159425E+10 | 0.423429E+09 | 0.117082E+10 | 0.198725E+10 | 0.424460E+09 |
July | 0.180108E+10 | 0.568945E+09 | 0.123213E+10 | 0.234903E+10 | 0.398744E+09 |
August | 0.192436E+10 | 0.803995E+09 | 0.112036E+10 | 0.243493E+10 | 0.470255E+09 |
September | 0.199630E+10 | 0.106310E+10 | 0.933204E+09 | 0.233237E+10 | 0.719726E+09 |
October | 0.176262E+10 | 0.103707E+10 | 0.725548E+09 | 0.179743E+10 | 0.110265E+10 |
November | 0.151975E+10 | 0.954209E+09 | 0.565542E+09 | 0.136294E+10 | 0.150361E+10 |
December | 0.167152E+10 | 0.109646E+10 | 0.575058E+09 | 0.129138E+10 | 0.227016E+10 |
Annual Sum or Average | 0.232760E+11 | 0.124285E+11 | 0.108475E+11 | 0.245155E+11 | 0.143841E+11 |
Minimum of Months | 0.151975E+10 | 0.423429E+09 | 0.565542E+09 | 0.129138E+10 | 0.398744E+09 |
Maximum of Months | 0.247596E+10 | 0.167295E+10 | 0.123213E+10 | 0.243493E+10 | 0.230057E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.773301E+09 | 0.323703E+09 | 0.449597E+09 | 0.310023E+09 | 0.306348E+10 |
February | 0.113823E+10 | 0.519841E+09 | 0.618391E+09 | 0.714212E+09 | 0.232493E+10 |
March | 0.165864E+10 | 0.848845E+09 | 0.809798E+09 | 0.127371E+10 | 0.213708E+10 |
April | 0.205053E+10 | 0.103876E+10 | 0.101177E+10 | 0.190927E+10 | 0.136145E+10 |
May | 0.260357E+10 | 0.124224E+10 | 0.136133E+10 | 0.294331E+10 | 0.750088E+09 |
June | 0.243136E+10 | 0.105165E+10 | 0.137972E+10 | 0.291103E+10 | 0.519261E+09 |
July | 0.268211E+10 | 0.124720E+10 | 0.143492E+10 | 0.331854E+10 | 0.509177E+09 |
August | 0.220708E+10 | 0.100306E+10 | 0.120402E+10 | 0.263283E+10 | 0.605648E+09 |
September | 0.166929E+10 | 0.750133E+09 | 0.919158E+09 | 0.176395E+10 | 0.855375E+09 |
October | 0.108951E+10 | 0.437399E+09 | 0.652115E+09 | 0.851128E+09 | 0.139991E+10 |
November | 0.640213E+09 | 0.215764E+09 | 0.424450E+09 | 0.289037E+09 | 0.203657E+10 |
December | 0.589665E+09 | 0.206256E+09 | 0.383409E+09 | 0.161664E+09 | 0.317199E+10 |
Annual Sum or Average | 0.195335E+11 | 0.888485E+10 | 0.106487E+11 | 0.190787E+11 | 0.187350E+11 |
Minimum of Months | 0.589665E+09 | 0.206256E+09 | 0.383409E+09 | 0.161664E+09 | 0.509177E+09 |
Maximum of Months | 0.268211E+10 | 0.124720E+10 | 0.143492E+10 | 0.331854E+10 | 0.317199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.773301E+09 | 0.323703E+09 | 0.449597E+09 | 0.310023E+09 | 0.306348E+10 |
February | 0.113823E+10 | 0.519841E+09 | 0.618391E+09 | 0.714212E+09 | 0.232493E+10 |
March | 0.165864E+10 | 0.848845E+09 | 0.809798E+09 | 0.127371E+10 | 0.213708E+10 |
April | 0.205053E+10 | 0.103876E+10 | 0.101177E+10 | 0.190927E+10 | 0.136145E+10 |
May | 0.260357E+10 | 0.124224E+10 | 0.136133E+10 | 0.294331E+10 | 0.750088E+09 |
June | 0.243136E+10 | 0.105165E+10 | 0.137972E+10 | 0.291103E+10 | 0.519261E+09 |
July | 0.268211E+10 | 0.124720E+10 | 0.143492E+10 | 0.331854E+10 | 0.509177E+09 |
August | 0.220708E+10 | 0.100306E+10 | 0.120402E+10 | 0.263283E+10 | 0.605648E+09 |
September | 0.166929E+10 | 0.750133E+09 | 0.919158E+09 | 0.176395E+10 | 0.855375E+09 |
October | 0.108951E+10 | 0.437399E+09 | 0.652115E+09 | 0.851128E+09 | 0.139991E+10 |
November | 0.640213E+09 | 0.215764E+09 | 0.424450E+09 | 0.289037E+09 | 0.203657E+10 |
December | 0.589665E+09 | 0.206256E+09 | 0.383409E+09 | 0.161664E+09 | 0.317199E+10 |
Annual Sum or Average | 0.195335E+11 | 0.888485E+10 | 0.106487E+11 | 0.190787E+11 | 0.187350E+11 |
Minimum of Months | 0.589665E+09 | 0.206256E+09 | 0.383409E+09 | 0.161664E+09 | 0.509177E+09 |
Maximum of Months | 0.268211E+10 | 0.124720E+10 | 0.143492E+10 | 0.331854E+10 | 0.317199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.773286E+09 | 0.323697E+09 | 0.449589E+09 | 0.310018E+09 | 0.306342E+10 |
February | 0.113821E+10 | 0.519831E+09 | 0.618379E+09 | 0.714199E+09 | 0.232489E+10 |
March | 0.165861E+10 | 0.848830E+09 | 0.809783E+09 | 0.127369E+10 | 0.213705E+10 |
April | 0.205049E+10 | 0.103874E+10 | 0.101175E+10 | 0.190923E+10 | 0.136143E+10 |
May | 0.260352E+10 | 0.124222E+10 | 0.136130E+10 | 0.294326E+10 | 0.750074E+09 |
June | 0.243132E+10 | 0.105163E+10 | 0.137969E+10 | 0.291098E+10 | 0.519251E+09 |
July | 0.268206E+10 | 0.124717E+10 | 0.143489E+10 | 0.331848E+10 | 0.509168E+09 |
August | 0.220704E+10 | 0.100304E+10 | 0.120399E+10 | 0.263278E+10 | 0.605637E+09 |
September | 0.166926E+10 | 0.750120E+09 | 0.919141E+09 | 0.176392E+10 | 0.855360E+09 |
October | 0.108949E+10 | 0.437391E+09 | 0.652103E+09 | 0.851113E+09 | 0.139988E+10 |
November | 0.640201E+09 | 0.215760E+09 | 0.424442E+09 | 0.289032E+09 | 0.203653E+10 |
December | 0.589654E+09 | 0.206252E+09 | 0.383402E+09 | 0.161661E+09 | 0.317193E+10 |
Annual Sum or Average | 0.195332E+11 | 0.888469E+10 | 0.106485E+11 | 0.190784E+11 | 0.187346E+11 |
Minimum of Months | 0.589654E+09 | 0.206252E+09 | 0.383402E+09 | 0.161661E+09 | 0.509168E+09 |
Maximum of Months | 0.268206E+10 | 0.124717E+10 | 0.143489E+10 | 0.331848E+10 | 0.317193E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157078E+10 | 0.00 | 0.157078E+10 | 20619749.28 | 0.138373E+11 |
February | 0.217934E+10 | 0.00 | 0.217934E+10 | 0.199648E+09 | 0.991528E+10 |
March | 0.296859E+10 | 0.00 | 0.296859E+10 | 0.502712E+09 | 0.861266E+10 |
April | 0.376566E+10 | 28953870.21 | 0.373670E+10 | 0.181041E+10 | 0.505691E+10 |
May | 0.547121E+10 | 0.292515E+09 | 0.517870E+10 | 0.492369E+10 | 0.279405E+10 |
June | 0.590809E+10 | 0.646519E+09 | 0.526157E+10 | 0.653280E+10 | 0.186908E+10 |
July | 0.583158E+10 | 0.497776E+09 | 0.533381E+10 | 0.677666E+10 | 0.180342E+10 |
August | 0.443067E+10 | 75269025.12 | 0.435540E+10 | 0.465358E+10 | 0.212273E+10 |
September | 0.334192E+10 | 797159.82 | 0.334112E+10 | 0.256228E+10 | 0.338762E+10 |
October | 0.239782E+10 | 0.00 | 0.239782E+10 | 0.892073E+09 | 0.538182E+10 |
November | 0.153645E+10 | 0.00 | 0.153645E+10 | 0.125848E+09 | 0.789023E+10 |
December | 0.133089E+10 | 0.00 | 0.133089E+10 | 1792784.22 | 0.132645E+11 |
Annual Sum or Average | 0.407330E+11 | 0.154183E+10 | 0.391912E+11 | 0.290021E+11 | 0.759356E+11 |
Minimum of Months | 0.133089E+10 | 0.00 | 0.133089E+10 | 1792784.22 | 0.180342E+10 |
Maximum of Months | 0.590809E+10 | 0.646519E+09 | 0.533381E+10 | 0.677666E+10 | 0.138373E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229508E+10 | 0.957583E+09 | 0.133750E+10 | 0.900448E+09 | 0.830272E+10 |
February | 0.325814E+10 | 0.138951E+10 | 0.186864E+10 | 0.195263E+10 | 0.595669E+10 |
March | 0.491652E+10 | 0.246656E+10 | 0.244996E+10 | 0.372090E+10 | 0.532960E+10 |
April | 0.659624E+10 | 0.355850E+10 | 0.303774E+10 | 0.634267E+10 | 0.325268E+10 |
May | 0.737689E+10 | 0.324373E+10 | 0.413316E+10 | 0.812757E+10 | 0.191858E+10 |
June | 0.808236E+10 | 0.386734E+10 | 0.421502E+10 | 0.976956E+10 | 0.129994E+10 |
July | 0.818153E+10 | 0.384258E+10 | 0.433894E+10 | 0.101654E+11 | 0.124172E+10 |
August | 0.630756E+10 | 0.275747E+10 | 0.355008E+10 | 0.751183E+10 | 0.144782E+10 |
September | 0.488824E+10 | 0.218837E+10 | 0.269987E+10 | 0.512510E+10 | 0.220854E+10 |
October | 0.305819E+10 | 0.115971E+10 | 0.189848E+10 | 0.232937E+10 | 0.345245E+10 |
November | 0.188357E+10 | 0.629423E+09 | 0.125414E+10 | 0.900278E+09 | 0.489501E+10 |
December | 0.177583E+10 | 0.655981E+09 | 0.111985E+10 | 0.556016E+09 | 0.806094E+10 |
Annual Sum or Average | 0.586201E+11 | 0.267168E+11 | 0.319034E+11 | 0.574018E+11 | 0.473667E+11 |
Minimum of Months | 0.177583E+10 | 0.629423E+09 | 0.111985E+10 | 0.556016E+09 | 0.124172E+10 |
Maximum of Months | 0.818153E+10 | 0.386734E+10 | 0.433894E+10 | 0.101654E+11 | 0.830272E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108251E+11 | 0.753344E+10 | 0.329171E+10 | 0.920256E+10 | 0.111910E+11 |
February | 0.123801E+11 | 0.836500E+10 | 0.401515E+10 | 0.118461E+11 | 0.859027E+10 |
March | 0.120713E+11 | 0.764067E+10 | 0.443067E+10 | 0.118017E+11 | 0.804030E+10 |
April | 0.105741E+11 | 0.573638E+10 | 0.483776E+10 | 0.112971E+11 | 0.527155E+10 |
May | 0.918142E+10 | 0.313192E+10 | 0.604950E+10 | 0.106693E+11 | 0.314053E+10 |
June | 0.797149E+10 | 0.211720E+10 | 0.585428E+10 | 0.991585E+10 | 0.206926E+10 |
July | 0.900564E+10 | 0.284480E+10 | 0.616084E+10 | 0.117139E+11 | 0.197345E+10 |
August | 0.962207E+10 | 0.402009E+10 | 0.560198E+10 | 0.121380E+11 | 0.230683E+10 |
September | 0.998179E+10 | 0.531564E+10 | 0.466615E+10 | 0.116037E+11 | 0.352958E+10 |
October | 0.881334E+10 | 0.518550E+10 | 0.362784E+10 | 0.899811E+10 | 0.529954E+10 |
November | 0.759897E+10 | 0.477118E+10 | 0.282779E+10 | 0.687965E+10 | 0.707524E+10 |
December | 0.835784E+10 | 0.548247E+10 | 0.287537E+10 | 0.654283E+10 | 0.108290E+11 |
Annual Sum or Average | 0.116383E+12 | 0.621443E+11 | 0.542390E+11 | 0.122609E+12 | 0.693166E+11 |
Minimum of Months | 0.759897E+10 | 0.211720E+10 | 0.282779E+10 | 0.654283E+10 | 0.197345E+10 |
Maximum of Months | 0.123801E+11 | 0.836500E+10 | 0.616084E+10 | 0.121380E+11 | 0.111910E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231988E+10 | 0.971100E+09 | 0.134878E+10 | 0.988015E+09 | 0.860834E+10 |
February | 0.341466E+10 | 0.155951E+10 | 0.185515E+10 | 0.225535E+10 | 0.630422E+10 |
March | 0.497588E+10 | 0.254651E+10 | 0.242937E+10 | 0.395731E+10 | 0.564699E+10 |
April | 0.615153E+10 | 0.311626E+10 | 0.303528E+10 | 0.589653E+10 | 0.352613E+10 |
May | 0.781062E+10 | 0.372669E+10 | 0.408394E+10 | 0.886236E+10 | 0.212023E+10 |
June | 0.729402E+10 | 0.315491E+10 | 0.413910E+10 | 0.879384E+10 | 0.142125E+10 |
July | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.100253E+11 | 0.139341E+10 |
August | 0.662116E+10 | 0.300915E+10 | 0.361201E+10 | 0.799414E+10 | 0.159926E+10 |
September | 0.500782E+10 | 0.225038E+10 | 0.275744E+10 | 0.534029E+10 | 0.237351E+10 |
October | 0.326851E+10 | 0.131218E+10 | 0.195633E+10 | 0.267810E+10 | 0.365253E+10 |
November | 0.192062E+10 | 0.647284E+09 | 0.127334E+10 | 0.968987E+09 | 0.511731E+10 |
December | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.547071E+09 | 0.835127E+10 |
Annual Sum or Average | 0.585999E+11 | 0.266543E+11 | 0.319457E+11 | 0.583073E+11 | 0.501145E+11 |
Minimum of Months | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.547071E+09 | 0.139341E+10 |
Maximum of Months | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.100253E+11 | 0.860834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157078E+10 | 0.00 | 0.157078E+10 | 25734928.92 | 0.136323E+11 |
February | 0.217934E+10 | 0.00 | 0.217934E+10 | 0.219110E+09 | 0.967351E+10 |
March | 0.296859E+10 | 0.00 | 0.296859E+10 | 0.559219E+09 | 0.826602E+10 |
April | 0.376566E+10 | 28953870.21 | 0.373670E+10 | 0.194336E+10 | 0.470480E+10 |
May | 0.547121E+10 | 0.292515E+09 | 0.517870E+10 | 0.500380E+10 | 0.267425E+10 |
June | 0.590809E+10 | 0.646519E+09 | 0.526157E+10 | 0.655422E+10 | 0.181321E+10 |
July | 0.583158E+10 | 0.497776E+09 | 0.533381E+10 | 0.677780E+10 | 0.176992E+10 |
August | 0.443067E+10 | 75269025.12 | 0.435540E+10 | 0.466908E+10 | 0.206085E+10 |
September | 0.334192E+10 | 797159.82 | 0.334112E+10 | 0.265589E+10 | 0.317545E+10 |
October | 0.239782E+10 | 0.00 | 0.239782E+10 | 0.102838E+10 | 0.489476E+10 |
November | 0.153645E+10 | 0.00 | 0.153645E+10 | 0.155646E+09 | 0.745866E+10 |
December | 0.133089E+10 | 0.00 | 0.133089E+10 | 4080375.74 | 0.130245E+11 |
Annual Sum or Average | 0.407330E+11 | 0.154183E+10 | 0.391912E+11 | 0.295963E+11 | 0.731483E+11 |
Minimum of Months | 0.133089E+10 | 0.00 | 0.133089E+10 | 4080375.74 | 0.176992E+10 |
Maximum of Months | 0.590809E+10 | 0.646519E+09 | 0.533381E+10 | 0.677780E+10 | 0.136323E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229508E+10 | 0.957583E+09 | 0.133750E+10 | 0.910327E+09 | 0.821710E+10 |
February | 0.325814E+10 | 0.138951E+10 | 0.186864E+10 | 0.199115E+10 | 0.581235E+10 |
March | 0.491652E+10 | 0.246656E+10 | 0.244996E+10 | 0.379278E+10 | 0.509809E+10 |
April | 0.659624E+10 | 0.355850E+10 | 0.303774E+10 | 0.643774E+10 | 0.304102E+10 |
May | 0.737689E+10 | 0.324373E+10 | 0.413316E+10 | 0.816245E+10 | 0.185176E+10 |
June | 0.808236E+10 | 0.386734E+10 | 0.421502E+10 | 0.977841E+10 | 0.126524E+10 |
July | 0.818153E+10 | 0.384258E+10 | 0.433894E+10 | 0.101675E+11 | 0.122154E+10 |
August | 0.630756E+10 | 0.275747E+10 | 0.355008E+10 | 0.751834E+10 | 0.141373E+10 |
September | 0.488824E+10 | 0.218837E+10 | 0.269987E+10 | 0.518239E+10 | 0.209353E+10 |
October | 0.305819E+10 | 0.115971E+10 | 0.189848E+10 | 0.244854E+10 | 0.314815E+10 |
November | 0.188357E+10 | 0.629423E+09 | 0.125414E+10 | 0.946987E+09 | 0.461517E+10 |
December | 0.177583E+10 | 0.655981E+09 | 0.111985E+10 | 0.564727E+09 | 0.795399E+10 |
Annual Sum or Average | 0.586201E+11 | 0.267168E+11 | 0.319034E+11 | 0.579013E+11 | 0.457317E+11 |
Minimum of Months | 0.177583E+10 | 0.629423E+09 | 0.111985E+10 | 0.564727E+09 | 0.122154E+10 |
Maximum of Months | 0.818153E+10 | 0.386734E+10 | 0.433894E+10 | 0.101675E+11 | 0.821710E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108251E+11 | 0.753344E+10 | 0.329171E+10 | 0.924902E+10 | 0.109764E+11 |
February | 0.123801E+11 | 0.836500E+10 | 0.401515E+10 | 0.119187E+11 | 0.831441E+10 |
March | 0.120713E+11 | 0.764067E+10 | 0.443067E+10 | 0.118941E+11 | 0.768679E+10 |
April | 0.105741E+11 | 0.573638E+10 | 0.483776E+10 | 0.114011E+11 | 0.493600E+10 |
May | 0.918142E+10 | 0.313192E+10 | 0.604950E+10 | 0.106968E+11 | 0.301907E+10 |
June | 0.797149E+10 | 0.211720E+10 | 0.585428E+10 | 0.991728E+10 | 0.200901E+10 |
July | 0.900564E+10 | 0.284480E+10 | 0.616084E+10 | 0.116981E+11 | 0.193823E+10 |
August | 0.962207E+10 | 0.402009E+10 | 0.560198E+10 | 0.121238E+11 | 0.225267E+10 |
September | 0.998179E+10 | 0.531564E+10 | 0.466615E+10 | 0.116492E+11 | 0.335628E+10 |
October | 0.881334E+10 | 0.518550E+10 | 0.362784E+10 | 0.915246E+10 | 0.486433E+10 |
November | 0.759897E+10 | 0.477118E+10 | 0.282779E+10 | 0.699471E+10 | 0.663747E+10 |
December | 0.835784E+10 | 0.548247E+10 | 0.287537E+10 | 0.659749E+10 | 0.105895E+11 |
Annual Sum or Average | 0.116383E+12 | 0.621443E+11 | 0.542390E+11 | 0.123293E+12 | 0.665802E+11 |
Minimum of Months | 0.759897E+10 | 0.211720E+10 | 0.282779E+10 | 0.659749E+10 | 0.193823E+10 |
Maximum of Months | 0.123801E+11 | 0.836500E+10 | 0.616084E+10 | 0.121238E+11 | 0.109764E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231988E+10 | 0.971100E+09 | 0.134878E+10 | 0.997296E+09 | 0.847261E+10 |
February | 0.341466E+10 | 0.155951E+10 | 0.185515E+10 | 0.227536E+10 | 0.614877E+10 |
March | 0.497588E+10 | 0.254651E+10 | 0.242937E+10 | 0.399847E+10 | 0.543307E+10 |
April | 0.615153E+10 | 0.311626E+10 | 0.303528E+10 | 0.596398E+10 | 0.332402E+10 |
May | 0.781062E+10 | 0.372669E+10 | 0.408394E+10 | 0.887624E+10 | 0.204863E+10 |
June | 0.729402E+10 | 0.315491E+10 | 0.413910E+10 | 0.878783E+10 | 0.138527E+10 |
July | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.100072E+11 | 0.137087E+10 |
August | 0.662116E+10 | 0.300915E+10 | 0.361201E+10 | 0.798328E+10 | 0.156530E+10 |
September | 0.500782E+10 | 0.225038E+10 | 0.275744E+10 | 0.537253E+10 | 0.226408E+10 |
October | 0.326851E+10 | 0.131218E+10 | 0.195633E+10 | 0.275872E+10 | 0.338555E+10 |
November | 0.192062E+10 | 0.647284E+09 | 0.127334E+10 | 0.100624E+10 | 0.485869E+10 |
December | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.555866E+09 | 0.821274E+10 |
Annual Sum or Average | 0.585999E+11 | 0.266543E+11 | 0.319457E+11 | 0.585831E+11 | 0.484696E+11 |
Minimum of Months | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.555866E+09 | 0.137087E+10 |
Maximum of Months | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.100072E+11 | 0.847261E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.17 | 5430.87 | 586.47 | 0.00 | 586.47 | 0.00 | 0.00 |
February | 48.99 | 4418.14 | 900.86 | 0.00 | 900.86 | 0.00 | 0.00 |
March | 142.45 | 3523.01 | 1108.35 | 0.00 | 1108.35 | 0.00 | 0.00 |
April | 618.08 | 2179.45 | 1452.80 | 11.17 | 1441.63 | 0.00 | 0.00 |
May | 1816.12 | 1090.85 | 2042.72 | 109.21 | 1933.51 | 0.00 | 0.00 |
June | 2506.04 | 749.56 | 2279.37 | 249.43 | 2029.94 | 0.00 | 0.00 |
July | 2516.61 | 687.98 | 2177.27 | 185.85 | 1991.42 | 0.00 | 0.00 |
August | 1711.33 | 831.51 | 1654.23 | 28.10 | 1626.13 | 0.00 | 0.00 |
September | 957.68 | 1395.04 | 1289.33 | 0.31 | 1289.02 | 0.00 | 0.00 |
October | 275.16 | 2254.25 | 895.25 | 0.00 | 895.25 | 0.00 | 0.00 |
November | 30.93 | 3463.18 | 592.77 | 0.00 | 592.77 | 0.00 | 0.00 |
December | 0.00 | 5332.35 | 496.90 | 0.00 | 496.90 | 0.00 | 0.00 |
Annual Sum or Average | 890.78 | 2605.48 | 1291.64 | 48.89 | 1242.75 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 687.98 | 496.90 | 0.00 | 496.90 | 0.00 | 0.00 |
Maximum of Months | 2516.61 | 5430.87 | 2279.37 | 249.43 | 2029.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 319.36 | 3257.46 | 856.89 | 357.52 | 499.37 | 0.00 | 0.00 |
February | 770.22 | 2637.22 | 1346.79 | 574.37 | 772.42 | 0.00 | 0.00 |
March | 1370.14 | 2128.70 | 1835.62 | 920.91 | 914.71 | 0.00 | 0.00 |
April | 2439.22 | 1338.54 | 2544.86 | 1372.89 | 1171.97 | 0.00 | 0.00 |
May | 3054.80 | 732.64 | 2754.23 | 1211.07 | 1543.15 | 0.00 | 0.00 |
June | 3793.06 | 507.60 | 3118.21 | 1492.03 | 1626.17 | 0.00 | 0.00 |
July | 3819.71 | 456.95 | 3054.64 | 1434.66 | 1619.98 | 0.00 | 0.00 |
August | 2823.94 | 539.16 | 2354.98 | 1029.53 | 1325.45 | 0.00 | 0.00 |
September | 1982.59 | 884.45 | 1885.90 | 844.28 | 1041.62 | 0.00 | 0.00 |
October | 845.96 | 1399.58 | 1141.80 | 432.99 | 708.81 | 0.00 | 0.00 |
November | 324.30 | 2102.48 | 726.69 | 242.83 | 483.85 | 0.00 | 0.00 |
December | 194.26 | 3219.15 | 663.02 | 244.92 | 418.10 | 0.00 | 0.00 |
Annual Sum or Average | 1816.48 | 1596.10 | 1858.84 | 847.19 | 1011.65 | 0.00 | 0.00 |
Minimum of Months | 194.26 | 456.95 | 663.02 | 242.83 | 418.10 | 0.00 | 0.00 |
Maximum of Months | 3819.71 | 3257.46 | 3118.21 | 1492.03 | 1626.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3419.41 | 4294.82 | 4041.66 | 2812.67 | 1228.99 | 0.00 | 0.00 |
February | 4891.98 | 3681.65 | 5117.47 | 3457.77 | 1659.71 | 0.00 | 0.00 |
March | 4405.77 | 3113.63 | 4506.94 | 2852.71 | 1654.23 | 0.00 | 0.00 |
April | 4357.23 | 2129.37 | 4079.54 | 2213.12 | 1866.43 | 0.00 | 0.00 |
May | 4000.46 | 1196.55 | 3427.96 | 1169.33 | 2258.63 | 0.00 | 0.00 |
June | 3833.55 | 818.81 | 3075.43 | 816.83 | 2258.61 | 0.00 | 0.00 |
July | 4385.28 | 744.39 | 3362.33 | 1062.13 | 2300.20 | 0.00 | 0.00 |
August | 4545.64 | 877.89 | 3592.48 | 1500.93 | 2091.55 | 0.00 | 0.00 |
September | 4499.32 | 1388.40 | 3851.01 | 2050.80 | 1800.22 | 0.00 | 0.00 |
October | 3355.52 | 2058.48 | 3290.54 | 1936.05 | 1354.49 | 0.00 | 0.00 |
November | 2629.22 | 2900.58 | 2931.71 | 1840.74 | 1090.97 | 0.00 | 0.00 |
December | 2410.81 | 4238.05 | 3120.47 | 2046.93 | 1073.54 | 0.00 | 0.00 |
Annual Sum or Average | 3887.03 | 2280.66 | 3690.50 | 1970.59 | 1719.91 | 0.00 | 0.00 |
Minimum of Months | 2410.81 | 744.39 | 2931.71 | 816.83 | 1073.54 | 0.00 | 0.00 |
Maximum of Months | 4891.98 | 4294.82 | 5117.47 | 3457.77 | 2300.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.25 | 3431.30 | 866.15 | 362.57 | 503.58 | 0.00 | 0.00 |
February | 885.67 | 2883.08 | 1411.49 | 644.64 | 766.85 | 0.00 | 0.00 |
March | 1426.64 | 2393.67 | 1857.79 | 950.76 | 907.03 | 0.00 | 0.00 |
April | 2209.79 | 1575.75 | 2373.29 | 1202.26 | 1171.02 | 0.00 | 0.00 |
May | 3296.70 | 840.15 | 2916.16 | 1391.39 | 1524.77 | 0.00 | 0.00 |
June | 3369.23 | 600.99 | 2814.06 | 1217.18 | 1596.88 | 0.00 | 0.00 |
July | 3716.98 | 570.31 | 3004.14 | 1396.94 | 1607.20 | 0.00 | 0.00 |
August | 2948.94 | 678.37 | 2472.07 | 1123.49 | 1348.58 | 0.00 | 0.00 |
September | 2041.60 | 990.01 | 1932.04 | 868.20 | 1063.83 | 0.00 | 0.00 |
October | 953.32 | 1567.99 | 1220.33 | 489.92 | 730.41 | 0.00 | 0.00 |
November | 334.53 | 2357.13 | 740.98 | 249.72 | 491.26 | 0.00 | 0.00 |
December | 181.07 | 3552.83 | 660.46 | 231.02 | 429.44 | 0.00 | 0.00 |
Annual Sum or Average | 1814.93 | 1782.23 | 1858.20 | 845.21 | 1012.99 | 0.00 | 0.00 |
Minimum of Months | 181.07 | 570.31 | 660.46 | 231.02 | 429.44 | 0.00 | 0.00 |
Maximum of Months | 3716.98 | 3552.83 | 3004.14 | 1396.94 | 1607.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.70 | 5166.27 | 586.46 | 0.00 | 586.46 | 0.00 | 0.00 |
February | 82.53 | 4098.58 | 900.85 | 0.00 | 900.85 | 0.00 | 0.00 |
March | 187.69 | 3215.60 | 1108.34 | 0.00 | 1108.34 | 0.00 | 0.00 |
April | 698.46 | 1950.97 | 1452.80 | 11.17 | 1441.63 | 0.00 | 0.00 |
May | 1838.30 | 1043.18 | 2042.72 | 109.21 | 1933.50 | 0.00 | 0.00 |
June | 2520.37 | 721.10 | 2279.36 | 249.43 | 2029.93 | 0.00 | 0.00 |
July | 2530.11 | 673.32 | 2177.26 | 185.85 | 1991.42 | 0.00 | 0.00 |
August | 1737.45 | 792.54 | 1654.22 | 28.10 | 1626.12 | 0.00 | 0.00 |
September | 988.53 | 1306.95 | 1289.32 | 0.31 | 1289.01 | 0.00 | 0.00 |
October | 333.06 | 2009.34 | 895.24 | 0.00 | 895.24 | 0.00 | 0.00 |
November | 48.55 | 3044.07 | 592.77 | 0.00 | 592.77 | 0.00 | 0.00 |
December | 0.67 | 4952.38 | 496.90 | 0.00 | 496.90 | 0.00 | 0.00 |
Annual Sum or Average | 919.65 | 2407.90 | 1291.64 | 48.89 | 1242.74 | 0.00 | 0.00 |
Minimum of Months | 0.67 | 673.32 | 496.90 | 0.00 | 496.90 | 0.00 | 0.00 |
Maximum of Months | 2530.11 | 5166.27 | 2279.36 | 249.43 | 2029.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 336.19 | 3099.88 | 856.89 | 357.52 | 499.37 | 0.00 | 0.00 |
February | 807.14 | 2462.25 | 1346.79 | 574.37 | 772.42 | 0.00 | 0.00 |
March | 1389.23 | 1989.85 | 1835.62 | 920.91 | 914.71 | 0.00 | 0.00 |
April | 2447.02 | 1254.89 | 2544.85 | 1372.88 | 1171.97 | 0.00 | 0.00 |
May | 3034.49 | 716.32 | 2754.21 | 1211.07 | 1543.14 | 0.00 | 0.00 |
June | 3769.12 | 501.52 | 3118.19 | 1492.03 | 1626.17 | 0.00 | 0.00 |
July | 3795.32 | 463.61 | 3054.63 | 1434.66 | 1619.98 | 0.00 | 0.00 |
August | 2804.60 | 540.55 | 2354.97 | 1029.52 | 1325.45 | 0.00 | 0.00 |
September | 1977.28 | 852.06 | 1885.90 | 844.28 | 1041.62 | 0.00 | 0.00 |
October | 869.69 | 1289.00 | 1141.80 | 432.99 | 708.81 | 0.00 | 0.00 |
November | 347.33 | 1888.51 | 726.68 | 242.83 | 483.85 | 0.00 | 0.00 |
December | 207.59 | 3009.61 | 663.02 | 244.92 | 418.10 | 0.00 | 0.00 |
Annual Sum or Average | 1820.20 | 1501.99 | 1858.83 | 847.18 | 1011.65 | 0.00 | 0.00 |
Minimum of Months | 207.59 | 463.61 | 663.02 | 242.83 | 418.10 | 0.00 | 0.00 |
Maximum of Months | 3795.32 | 3099.88 | 3118.19 | 1492.03 | 1626.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3435.84 | 4178.25 | 4041.65 | 2812.66 | 1228.98 | 0.00 | 0.00 |
February | 4896.72 | 3550.87 | 5117.45 | 3457.76 | 1659.70 | 0.00 | 0.00 |
March | 4406.26 | 3001.90 | 4506.92 | 2852.70 | 1654.22 | 0.00 | 0.00 |
April | 4358.43 | 2033.78 | 4079.53 | 2213.11 | 1866.42 | 0.00 | 0.00 |
May | 3983.45 | 1172.54 | 3427.95 | 1169.33 | 2258.63 | 0.00 | 0.00 |
June | 3825.56 | 798.33 | 3075.42 | 816.82 | 2258.60 | 0.00 | 0.00 |
July | 4373.48 | 736.80 | 3362.32 | 1062.13 | 2300.19 | 0.00 | 0.00 |
August | 4531.80 | 861.27 | 3592.47 | 1500.93 | 2091.54 | 0.00 | 0.00 |
September | 4476.72 | 1361.72 | 3851.00 | 2050.79 | 1800.21 | 0.00 | 0.00 |
October | 3359.51 | 1978.62 | 3290.52 | 1936.04 | 1354.48 | 0.00 | 0.00 |
November | 2654.19 | 2729.64 | 2931.70 | 1840.73 | 1090.97 | 0.00 | 0.00 |
December | 2442.81 | 4043.09 | 3120.46 | 2046.92 | 1073.54 | 0.00 | 0.00 |
Annual Sum or Average | 3887.90 | 2198.01 | 3690.49 | 1970.58 | 1719.91 | 0.00 | 0.00 |
Minimum of Months | 2442.81 | 736.80 | 2931.70 | 816.82 | 1073.54 | 0.00 | 0.00 |
Maximum of Months | 4896.72 | 4178.25 | 5117.45 | 3457.76 | 2300.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 368.88 | 3213.98 | 866.14 | 362.57 | 503.58 | 0.00 | 0.00 |
February | 932.27 | 2605.91 | 1411.48 | 644.64 | 766.85 | 0.00 | 0.00 |
March | 1477.49 | 2108.34 | 1857.78 | 950.76 | 907.02 | 0.00 | 0.00 |
April | 2274.90 | 1360.39 | 2373.28 | 1202.26 | 1171.02 | 0.00 | 0.00 |
May | 3308.83 | 791.60 | 2916.15 | 1391.39 | 1524.77 | 0.00 | 0.00 |
June | 3392.69 | 548.32 | 2814.05 | 1217.17 | 1596.88 | 0.00 | 0.00 |
July | 3743.03 | 520.24 | 3004.13 | 1396.94 | 1607.19 | 0.00 | 0.00 |
August | 2984.67 | 597.10 | 2472.06 | 1123.49 | 1348.57 | 0.00 | 0.00 |
September | 2060.30 | 915.71 | 1932.03 | 868.20 | 1063.83 | 0.00 | 0.00 |
October | 999.89 | 1363.70 | 1220.32 | 489.91 | 730.41 | 0.00 | 0.00 |
November | 373.84 | 1974.27 | 740.98 | 249.72 | 491.26 | 0.00 | 0.00 |
December | 204.25 | 3118.01 | 660.46 | 231.02 | 429.44 | 0.00 | 0.00 |
Annual Sum or Average | 1848.91 | 1589.12 | 1858.19 | 845.20 | 1012.99 | 0.00 | 0.00 |
Minimum of Months | 204.25 | 520.24 | 660.46 | 231.02 | 429.44 | 0.00 | 0.00 |
Maximum of Months | 3743.03 | 3213.98 | 3004.13 | 1396.94 | 1607.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.61 | 5089.73 | 586.46 | 0.00 | 586.46 | 0.00 | 0.00 |
February | 90.57 | 3998.64 | 900.85 | 0.00 | 900.85 | 0.00 | 0.00 |
March | 208.79 | 3086.18 | 1108.34 | 0.00 | 1108.34 | 0.00 | 0.00 |
April | 749.75 | 1815.12 | 1452.80 | 11.17 | 1441.63 | 0.00 | 0.00 |
May | 1868.20 | 998.45 | 2042.72 | 109.21 | 1933.50 | 0.00 | 0.00 |
June | 2528.63 | 699.54 | 2279.36 | 249.43 | 2029.93 | 0.00 | 0.00 |
July | 2530.54 | 660.81 | 2177.26 | 185.85 | 1991.42 | 0.00 | 0.00 |
August | 1743.24 | 769.43 | 1654.22 | 28.10 | 1626.12 | 0.00 | 0.00 |
September | 1024.65 | 1225.10 | 1289.32 | 0.31 | 1289.01 | 0.00 | 0.00 |
October | 383.95 | 1827.49 | 895.24 | 0.00 | 895.24 | 0.00 | 0.00 |
November | 60.05 | 2877.57 | 592.77 | 0.00 | 592.77 | 0.00 | 0.00 |
December | 1.52 | 4862.79 | 496.90 | 0.00 | 496.90 | 0.00 | 0.00 |
Annual Sum or Average | 938.49 | 2319.52 | 1291.64 | 48.89 | 1242.74 | 0.00 | 0.00 |
Minimum of Months | 1.52 | 660.81 | 496.90 | 0.00 | 496.90 | 0.00 | 0.00 |
Maximum of Months | 2530.54 | 5089.73 | 2279.36 | 249.43 | 2029.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 339.88 | 3067.91 | 856.89 | 357.52 | 499.37 | 0.00 | 0.00 |
February | 823.06 | 2402.59 | 1346.79 | 574.37 | 772.42 | 0.00 | 0.00 |
March | 1416.06 | 1903.41 | 1835.62 | 920.91 | 914.71 | 0.00 | 0.00 |
April | 2483.70 | 1173.23 | 2544.85 | 1372.88 | 1171.97 | 0.00 | 0.00 |
May | 3047.51 | 691.37 | 2754.21 | 1211.07 | 1543.14 | 0.00 | 0.00 |
June | 3772.54 | 488.13 | 3118.19 | 1492.03 | 1626.17 | 0.00 | 0.00 |
July | 3796.10 | 456.07 | 3054.63 | 1434.66 | 1619.98 | 0.00 | 0.00 |
August | 2807.03 | 527.82 | 2354.97 | 1029.52 | 1325.45 | 0.00 | 0.00 |
September | 1999.38 | 807.69 | 1885.90 | 844.28 | 1041.62 | 0.00 | 0.00 |
October | 914.18 | 1175.39 | 1141.80 | 432.99 | 708.81 | 0.00 | 0.00 |
November | 365.35 | 1780.55 | 726.68 | 242.83 | 483.85 | 0.00 | 0.00 |
December | 210.84 | 2969.68 | 663.02 | 244.92 | 418.10 | 0.00 | 0.00 |
Annual Sum or Average | 1836.04 | 1450.14 | 1858.83 | 847.18 | 1011.65 | 0.00 | 0.00 |
Minimum of Months | 210.84 | 456.07 | 663.02 | 242.83 | 418.10 | 0.00 | 0.00 |
Maximum of Months | 3796.10 | 3067.91 | 3118.19 | 1492.03 | 1626.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3453.19 | 4098.13 | 4041.65 | 2812.66 | 1228.98 | 0.00 | 0.00 |
February | 4926.70 | 3436.84 | 5117.45 | 3457.76 | 1659.70 | 0.00 | 0.00 |
March | 4440.74 | 2869.92 | 4506.92 | 2852.70 | 1654.22 | 0.00 | 0.00 |
April | 4398.55 | 1904.32 | 4079.53 | 2213.11 | 1866.42 | 0.00 | 0.00 |
May | 3993.74 | 1127.19 | 3427.95 | 1169.33 | 2258.63 | 0.00 | 0.00 |
June | 3826.11 | 775.08 | 3075.42 | 816.82 | 2258.60 | 0.00 | 0.00 |
July | 4367.57 | 723.65 | 3362.32 | 1062.13 | 2300.19 | 0.00 | 0.00 |
August | 4526.50 | 841.05 | 3592.47 | 1500.93 | 2091.54 | 0.00 | 0.00 |
September | 4494.27 | 1294.86 | 3851.00 | 2050.79 | 1800.21 | 0.00 | 0.00 |
October | 3417.14 | 1816.13 | 3290.52 | 1936.04 | 1354.48 | 0.00 | 0.00 |
November | 2698.58 | 2560.75 | 2931.70 | 1840.73 | 1090.97 | 0.00 | 0.00 |
December | 2463.22 | 3953.66 | 3120.46 | 2046.92 | 1073.54 | 0.00 | 0.00 |
Annual Sum or Average | 3909.58 | 2111.24 | 3690.49 | 1970.58 | 1719.91 | 0.00 | 0.00 |
Minimum of Months | 2463.22 | 723.65 | 2931.70 | 816.82 | 1073.54 | 0.00 | 0.00 |
Maximum of Months | 4926.70 | 4098.13 | 5117.45 | 3457.76 | 2300.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.35 | 3163.31 | 866.14 | 362.57 | 503.58 | 0.00 | 0.00 |
February | 940.54 | 2541.65 | 1411.48 | 644.64 | 766.85 | 0.00 | 0.00 |
March | 1492.86 | 2028.48 | 1857.78 | 950.76 | 907.02 | 0.00 | 0.00 |
April | 2300.92 | 1282.42 | 2373.28 | 1202.26 | 1171.02 | 0.00 | 0.00 |
May | 3314.01 | 764.87 | 2916.15 | 1391.39 | 1524.77 | 0.00 | 0.00 |
June | 3390.37 | 534.44 | 2814.05 | 1217.17 | 1596.88 | 0.00 | 0.00 |
July | 3736.28 | 511.83 | 3004.13 | 1396.94 | 1607.19 | 0.00 | 0.00 |
August | 2980.62 | 584.42 | 2472.06 | 1123.49 | 1348.57 | 0.00 | 0.00 |
September | 2072.73 | 873.49 | 1932.03 | 868.20 | 1063.83 | 0.00 | 0.00 |
October | 1029.99 | 1264.02 | 1220.32 | 489.91 | 730.41 | 0.00 | 0.00 |
November | 388.21 | 1874.50 | 740.98 | 249.72 | 491.26 | 0.00 | 0.00 |
December | 207.54 | 3066.29 | 660.46 | 231.02 | 429.44 | 0.00 | 0.00 |
Annual Sum or Average | 1857.66 | 1536.96 | 1858.19 | 845.20 | 1012.99 | 0.00 | 0.00 |
Minimum of Months | 207.54 | 511.83 | 660.46 | 231.02 | 429.44 | 0.00 | 0.00 |
Maximum of Months | 3736.28 | 3163.31 | 3004.13 | 1396.94 | 1607.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5825235.53 | 0.145460E+11 | 0.157079E+10 | 0.00 | 0.157079E+10 | 0.00 | 0.00 |
February | 0.118512E+09 | 0.106884E+11 | 0.217935E+10 | 0.00 | 0.217935E+10 | 0.00 | 0.00 |
March | 0.381551E+09 | 0.943602E+10 | 0.296860E+10 | 0.00 | 0.296860E+10 | 0.00 | 0.00 |
April | 0.160207E+10 | 0.564913E+10 | 0.376567E+10 | 28953973.03 | 0.373672E+10 | 0.00 | 0.00 |
May | 0.486429E+10 | 0.292173E+10 | 0.547123E+10 | 0.292516E+09 | 0.517872E+10 | 0.00 | 0.00 |
June | 0.649566E+10 | 0.194286E+10 | 0.590811E+10 | 0.646522E+09 | 0.526159E+10 | 0.00 | 0.00 |
July | 0.674050E+10 | 0.184269E+10 | 0.583161E+10 | 0.497778E+09 | 0.533383E+10 | 0.00 | 0.00 |
August | 0.458363E+10 | 0.222711E+10 | 0.443069E+10 | 75269292.41 | 0.435542E+10 | 0.00 | 0.00 |
September | 0.248231E+10 | 0.361595E+10 | 0.334193E+10 | 797162.65 | 0.334114E+10 | 0.00 | 0.00 |
October | 0.736999E+09 | 0.603777E+10 | 0.239783E+10 | 0.00 | 0.239783E+10 | 0.00 | 0.00 |
November | 80175715.21 | 0.897656E+10 | 0.153645E+10 | 0.00 | 0.153645E+10 | 0.00 | 0.00 |
December | 0.00 | 0.142822E+11 | 0.133090E+10 | 0.00 | 0.133090E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.280915E+11 | 0.821664E+11 | 0.407332E+11 | 0.154184E+10 | 0.391913E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.184269E+10 | 0.133090E+10 | 0.00 | 0.133090E+10 | 0.00 | 0.00 |
Maximum of Months | 0.674050E+10 | 0.145460E+11 | 0.590811E+10 | 0.646522E+09 | 0.533383E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.855363E+09 | 0.872479E+10 | 0.229509E+10 | 0.957587E+09 | 0.133751E+10 | 0.00 | 0.00 |
February | 0.186333E+10 | 0.637997E+10 | 0.325816E+10 | 0.138951E+10 | 0.186864E+10 | 0.00 | 0.00 |
March | 0.366979E+10 | 0.570151E+10 | 0.491654E+10 | 0.246657E+10 | 0.244997E+10 | 0.00 | 0.00 |
April | 0.632245E+10 | 0.346948E+10 | 0.659627E+10 | 0.355852E+10 | 0.303775E+10 | 0.00 | 0.00 |
May | 0.818197E+10 | 0.196230E+10 | 0.737692E+10 | 0.324374E+10 | 0.413318E+10 | 0.00 | 0.00 |
June | 0.983161E+10 | 0.131569E+10 | 0.808239E+10 | 0.386735E+10 | 0.421504E+10 | 0.00 | 0.00 |
July | 0.102307E+11 | 0.122390E+10 | 0.818156E+10 | 0.384260E+10 | 0.433896E+10 | 0.00 | 0.00 |
August | 0.756364E+10 | 0.144407E+10 | 0.630758E+10 | 0.275748E+10 | 0.355010E+10 | 0.00 | 0.00 |
September | 0.513887E+10 | 0.229249E+10 | 0.488826E+10 | 0.218838E+10 | 0.269988E+10 | 0.00 | 0.00 |
October | 0.226581E+10 | 0.374863E+10 | 0.305821E+10 | 0.115972E+10 | 0.189849E+10 | 0.00 | 0.00 |
November | 0.840581E+09 | 0.544963E+10 | 0.188358E+10 | 0.629425E+09 | 0.125415E+10 | 0.00 | 0.00 |
December | 0.520314E+09 | 0.862216E+10 | 0.177583E+10 | 0.655984E+09 | 0.111985E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.572844E+11 | 0.503346E+11 | 0.586204E+11 | 0.267169E+11 | 0.319035E+11 | 0.00 | 0.00 |
Minimum of Months | 0.520314E+09 | 0.122390E+10 | 0.177583E+10 | 0.629425E+09 | 0.111985E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102307E+11 | 0.872479E+10 | 0.818156E+10 | 0.386735E+10 | 0.433896E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.915856E+10 | 0.115032E+11 | 0.108252E+11 | 0.753347E+10 | 0.329172E+10 | 0.00 | 0.00 |
February | 0.118347E+11 | 0.890664E+10 | 0.123802E+11 | 0.836503E+10 | 0.401516E+10 | 0.00 | 0.00 |
March | 0.118004E+11 | 0.833955E+10 | 0.120714E+11 | 0.764070E+10 | 0.443069E+10 | 0.00 | 0.00 |
April | 0.112939E+11 | 0.551933E+10 | 0.105742E+11 | 0.573640E+10 | 0.483778E+10 | 0.00 | 0.00 |
May | 0.107148E+11 | 0.320485E+10 | 0.918146E+10 | 0.313193E+10 | 0.604953E+10 | 0.00 | 0.00 |
June | 0.993656E+10 | 0.212237E+10 | 0.797152E+10 | 0.211721E+10 | 0.585431E+10 | 0.00 | 0.00 |
July | 0.117455E+11 | 0.199379E+10 | 0.900567E+10 | 0.284481E+10 | 0.616086E+10 | 0.00 | 0.00 |
August | 0.121750E+11 | 0.235135E+10 | 0.962210E+10 | 0.402010E+10 | 0.560200E+10 | 0.00 | 0.00 |
September | 0.116622E+11 | 0.359874E+10 | 0.998183E+10 | 0.531566E+10 | 0.466617E+10 | 0.00 | 0.00 |
October | 0.898742E+10 | 0.551344E+10 | 0.881337E+10 | 0.518552E+10 | 0.362785E+10 | 0.00 | 0.00 |
November | 0.681493E+10 | 0.751829E+10 | 0.759900E+10 | 0.477120E+10 | 0.282780E+10 | 0.00 | 0.00 |
December | 0.645711E+10 | 0.113512E+11 | 0.835787E+10 | 0.548249E+10 | 0.287538E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.122581E+12 | 0.719228E+11 | 0.116384E+12 | 0.621445E+11 | 0.542392E+11 | 0.00 | 0.00 |
Minimum of Months | 0.645711E+10 | 0.199379E+10 | 0.759900E+10 | 0.211721E+10 | 0.282780E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121750E+11 | 0.115032E+11 | 0.123802E+11 | 0.836503E+10 | 0.616086E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930064E+09 | 0.919038E+10 | 0.231989E+10 | 0.971104E+09 | 0.134878E+10 | 0.00 | 0.00 |
February | 0.214262E+10 | 0.697474E+10 | 0.341467E+10 | 0.155951E+10 | 0.185516E+10 | 0.00 | 0.00 |
March | 0.382112E+10 | 0.641122E+10 | 0.497590E+10 | 0.254652E+10 | 0.242938E+10 | 0.00 | 0.00 |
April | 0.572777E+10 | 0.408433E+10 | 0.615156E+10 | 0.311627E+10 | 0.303529E+10 | 0.00 | 0.00 |
May | 0.882988E+10 | 0.225025E+10 | 0.781065E+10 | 0.372670E+10 | 0.408395E+10 | 0.00 | 0.00 |
June | 0.873305E+10 | 0.155777E+10 | 0.729405E+10 | 0.315493E+10 | 0.413912E+10 | 0.00 | 0.00 |
July | 0.995557E+10 | 0.152752E+10 | 0.804629E+10 | 0.374157E+10 | 0.430472E+10 | 0.00 | 0.00 |
August | 0.789843E+10 | 0.181693E+10 | 0.662119E+10 | 0.300916E+10 | 0.361203E+10 | 0.00 | 0.00 |
September | 0.529182E+10 | 0.256611E+10 | 0.500784E+10 | 0.225039E+10 | 0.275746E+10 | 0.00 | 0.00 |
October | 0.255337E+10 | 0.419969E+10 | 0.326852E+10 | 0.131219E+10 | 0.195633E+10 | 0.00 | 0.00 |
November | 0.867105E+09 | 0.610968E+10 | 0.192063E+10 | 0.647287E+09 | 0.127334E+10 | 0.00 | 0.00 |
December | 0.484988E+09 | 0.951590E+10 | 0.176898E+10 | 0.618765E+09 | 0.115022E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.572358E+11 | 0.562045E+11 | 0.586002E+11 | 0.266544E+11 | 0.319458E+11 | 0.00 | 0.00 |
Minimum of Months | 0.484988E+09 | 0.152752E+10 | 0.176898E+10 | 0.618765E+09 | 0.115022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.995557E+10 | 0.951590E+10 | 0.804629E+10 | 0.374157E+10 | 0.430472E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 20619749.28 | 0.138373E+11 | 0.157078E+10 | 0.00 | 0.157078E+10 | 0.00 | 0.00 |
February | 0.199648E+09 | 0.991528E+10 | 0.217934E+10 | 0.00 | 0.217934E+10 | 0.00 | 0.00 |
March | 0.502712E+09 | 0.861266E+10 | 0.296859E+10 | 0.00 | 0.296859E+10 | 0.00 | 0.00 |
April | 0.181041E+10 | 0.505691E+10 | 0.376566E+10 | 28953870.21 | 0.373670E+10 | 0.00 | 0.00 |
May | 0.492369E+10 | 0.279405E+10 | 0.547121E+10 | 0.292515E+09 | 0.517870E+10 | 0.00 | 0.00 |
June | 0.653280E+10 | 0.186908E+10 | 0.590809E+10 | 0.646519E+09 | 0.526157E+10 | 0.00 | 0.00 |
July | 0.677666E+10 | 0.180342E+10 | 0.583158E+10 | 0.497776E+09 | 0.533381E+10 | 0.00 | 0.00 |
August | 0.465358E+10 | 0.212273E+10 | 0.443067E+10 | 75269025.12 | 0.435540E+10 | 0.00 | 0.00 |
September | 0.256228E+10 | 0.338762E+10 | 0.334192E+10 | 797159.82 | 0.334112E+10 | 0.00 | 0.00 |
October | 0.892073E+09 | 0.538182E+10 | 0.239782E+10 | 0.00 | 0.239782E+10 | 0.00 | 0.00 |
November | 0.125848E+09 | 0.789023E+10 | 0.153645E+10 | 0.00 | 0.153645E+10 | 0.00 | 0.00 |
December | 1792784.22 | 0.132645E+11 | 0.133089E+10 | 0.00 | 0.133089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290021E+11 | 0.759356E+11 | 0.407330E+11 | 0.154183E+10 | 0.391912E+11 | 0.00 | 0.00 |
Minimum of Months | 1792784.22 | 0.180342E+10 | 0.133089E+10 | 0.00 | 0.133089E+10 | 0.00 | 0.00 |
Maximum of Months | 0.677666E+10 | 0.138373E+11 | 0.590809E+10 | 0.646519E+09 | 0.533381E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.900448E+09 | 0.830272E+10 | 0.229508E+10 | 0.957583E+09 | 0.133750E+10 | 0.00 | 0.00 |
February | 0.195263E+10 | 0.595669E+10 | 0.325814E+10 | 0.138951E+10 | 0.186864E+10 | 0.00 | 0.00 |
March | 0.372090E+10 | 0.532960E+10 | 0.491652E+10 | 0.246656E+10 | 0.244996E+10 | 0.00 | 0.00 |
April | 0.634267E+10 | 0.325268E+10 | 0.659624E+10 | 0.355850E+10 | 0.303774E+10 | 0.00 | 0.00 |
May | 0.812757E+10 | 0.191858E+10 | 0.737689E+10 | 0.324373E+10 | 0.413316E+10 | 0.00 | 0.00 |
June | 0.976956E+10 | 0.129994E+10 | 0.808236E+10 | 0.386734E+10 | 0.421502E+10 | 0.00 | 0.00 |
July | 0.101654E+11 | 0.124172E+10 | 0.818153E+10 | 0.384258E+10 | 0.433894E+10 | 0.00 | 0.00 |
August | 0.751183E+10 | 0.144782E+10 | 0.630756E+10 | 0.275747E+10 | 0.355008E+10 | 0.00 | 0.00 |
September | 0.512510E+10 | 0.220854E+10 | 0.488824E+10 | 0.218837E+10 | 0.269987E+10 | 0.00 | 0.00 |
October | 0.232937E+10 | 0.345245E+10 | 0.305819E+10 | 0.115971E+10 | 0.189848E+10 | 0.00 | 0.00 |
November | 0.900278E+09 | 0.489501E+10 | 0.188357E+10 | 0.629423E+09 | 0.125414E+10 | 0.00 | 0.00 |
December | 0.556016E+09 | 0.806094E+10 | 0.177583E+10 | 0.655981E+09 | 0.111985E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574018E+11 | 0.473667E+11 | 0.586201E+11 | 0.267168E+11 | 0.319034E+11 | 0.00 | 0.00 |
Minimum of Months | 0.556016E+09 | 0.124172E+10 | 0.177583E+10 | 0.629423E+09 | 0.111985E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101654E+11 | 0.830272E+10 | 0.818153E+10 | 0.386734E+10 | 0.433894E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.920256E+10 | 0.111910E+11 | 0.108251E+11 | 0.753344E+10 | 0.329171E+10 | 0.00 | 0.00 |
February | 0.118461E+11 | 0.859027E+10 | 0.123801E+11 | 0.836500E+10 | 0.401515E+10 | 0.00 | 0.00 |
March | 0.118017E+11 | 0.804030E+10 | 0.120713E+11 | 0.764067E+10 | 0.443067E+10 | 0.00 | 0.00 |
April | 0.112971E+11 | 0.527155E+10 | 0.105741E+11 | 0.573638E+10 | 0.483776E+10 | 0.00 | 0.00 |
May | 0.106693E+11 | 0.314053E+10 | 0.918142E+10 | 0.313192E+10 | 0.604950E+10 | 0.00 | 0.00 |
June | 0.991585E+10 | 0.206926E+10 | 0.797149E+10 | 0.211720E+10 | 0.585428E+10 | 0.00 | 0.00 |
July | 0.117139E+11 | 0.197345E+10 | 0.900564E+10 | 0.284480E+10 | 0.616084E+10 | 0.00 | 0.00 |
August | 0.121380E+11 | 0.230683E+10 | 0.962207E+10 | 0.402009E+10 | 0.560198E+10 | 0.00 | 0.00 |
September | 0.116037E+11 | 0.352958E+10 | 0.998179E+10 | 0.531564E+10 | 0.466615E+10 | 0.00 | 0.00 |
October | 0.899811E+10 | 0.529954E+10 | 0.881334E+10 | 0.518550E+10 | 0.362784E+10 | 0.00 | 0.00 |
November | 0.687965E+10 | 0.707524E+10 | 0.759897E+10 | 0.477118E+10 | 0.282779E+10 | 0.00 | 0.00 |
December | 0.654283E+10 | 0.108290E+11 | 0.835784E+10 | 0.548247E+10 | 0.287537E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.122609E+12 | 0.693166E+11 | 0.116383E+12 | 0.621443E+11 | 0.542390E+11 | 0.00 | 0.00 |
Minimum of Months | 0.654283E+10 | 0.197345E+10 | 0.759897E+10 | 0.211720E+10 | 0.282779E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121380E+11 | 0.111910E+11 | 0.123801E+11 | 0.836500E+10 | 0.616084E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.988015E+09 | 0.860834E+10 | 0.231988E+10 | 0.971100E+09 | 0.134878E+10 | 0.00 | 0.00 |
February | 0.225535E+10 | 0.630422E+10 | 0.341466E+10 | 0.155951E+10 | 0.185515E+10 | 0.00 | 0.00 |
March | 0.395731E+10 | 0.564699E+10 | 0.497588E+10 | 0.254651E+10 | 0.242937E+10 | 0.00 | 0.00 |
April | 0.589653E+10 | 0.352613E+10 | 0.615153E+10 | 0.311626E+10 | 0.303528E+10 | 0.00 | 0.00 |
May | 0.886236E+10 | 0.212023E+10 | 0.781062E+10 | 0.372669E+10 | 0.408394E+10 | 0.00 | 0.00 |
June | 0.879384E+10 | 0.142125E+10 | 0.729402E+10 | 0.315491E+10 | 0.413910E+10 | 0.00 | 0.00 |
July | 0.100253E+11 | 0.139341E+10 | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.00 | 0.00 |
August | 0.799414E+10 | 0.159926E+10 | 0.662116E+10 | 0.300915E+10 | 0.361201E+10 | 0.00 | 0.00 |
September | 0.534029E+10 | 0.237351E+10 | 0.500782E+10 | 0.225038E+10 | 0.275744E+10 | 0.00 | 0.00 |
October | 0.267810E+10 | 0.365253E+10 | 0.326851E+10 | 0.131218E+10 | 0.195633E+10 | 0.00 | 0.00 |
November | 0.968987E+09 | 0.511731E+10 | 0.192062E+10 | 0.647284E+09 | 0.127334E+10 | 0.00 | 0.00 |
December | 0.547071E+09 | 0.835127E+10 | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.583073E+11 | 0.501145E+11 | 0.585999E+11 | 0.266543E+11 | 0.319457E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547071E+09 | 0.139341E+10 | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.00 | 0.00 |
Maximum of Months | 0.100253E+11 | 0.860834E+10 | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 25734928.92 | 0.136323E+11 | 0.157078E+10 | 0.00 | 0.157078E+10 | 0.00 | 0.00 |
February | 0.219110E+09 | 0.967351E+10 | 0.217934E+10 | 0.00 | 0.217934E+10 | 0.00 | 0.00 |
March | 0.559219E+09 | 0.826602E+10 | 0.296859E+10 | 0.00 | 0.296859E+10 | 0.00 | 0.00 |
April | 0.194336E+10 | 0.470480E+10 | 0.376566E+10 | 28953870.21 | 0.373670E+10 | 0.00 | 0.00 |
May | 0.500380E+10 | 0.267425E+10 | 0.547121E+10 | 0.292515E+09 | 0.517870E+10 | 0.00 | 0.00 |
June | 0.655422E+10 | 0.181321E+10 | 0.590809E+10 | 0.646519E+09 | 0.526157E+10 | 0.00 | 0.00 |
July | 0.677780E+10 | 0.176992E+10 | 0.583158E+10 | 0.497776E+09 | 0.533381E+10 | 0.00 | 0.00 |
August | 0.466908E+10 | 0.206085E+10 | 0.443067E+10 | 75269025.12 | 0.435540E+10 | 0.00 | 0.00 |
September | 0.265589E+10 | 0.317545E+10 | 0.334192E+10 | 797159.82 | 0.334112E+10 | 0.00 | 0.00 |
October | 0.102838E+10 | 0.489476E+10 | 0.239782E+10 | 0.00 | 0.239782E+10 | 0.00 | 0.00 |
November | 0.155646E+09 | 0.745866E+10 | 0.153645E+10 | 0.00 | 0.153645E+10 | 0.00 | 0.00 |
December | 4080375.74 | 0.130245E+11 | 0.133089E+10 | 0.00 | 0.133089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.295963E+11 | 0.731483E+11 | 0.407330E+11 | 0.154183E+10 | 0.391912E+11 | 0.00 | 0.00 |
Minimum of Months | 4080375.74 | 0.176992E+10 | 0.133089E+10 | 0.00 | 0.133089E+10 | 0.00 | 0.00 |
Maximum of Months | 0.677780E+10 | 0.136323E+11 | 0.590809E+10 | 0.646519E+09 | 0.533381E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.910327E+09 | 0.821710E+10 | 0.229508E+10 | 0.957583E+09 | 0.133750E+10 | 0.00 | 0.00 |
February | 0.199115E+10 | 0.581235E+10 | 0.325814E+10 | 0.138951E+10 | 0.186864E+10 | 0.00 | 0.00 |
March | 0.379278E+10 | 0.509809E+10 | 0.491652E+10 | 0.246656E+10 | 0.244996E+10 | 0.00 | 0.00 |
April | 0.643774E+10 | 0.304102E+10 | 0.659624E+10 | 0.355850E+10 | 0.303774E+10 | 0.00 | 0.00 |
May | 0.816245E+10 | 0.185176E+10 | 0.737689E+10 | 0.324373E+10 | 0.413316E+10 | 0.00 | 0.00 |
June | 0.977841E+10 | 0.126524E+10 | 0.808236E+10 | 0.386734E+10 | 0.421502E+10 | 0.00 | 0.00 |
July | 0.101675E+11 | 0.122154E+10 | 0.818153E+10 | 0.384258E+10 | 0.433894E+10 | 0.00 | 0.00 |
August | 0.751834E+10 | 0.141373E+10 | 0.630756E+10 | 0.275747E+10 | 0.355008E+10 | 0.00 | 0.00 |
September | 0.518239E+10 | 0.209353E+10 | 0.488824E+10 | 0.218837E+10 | 0.269987E+10 | 0.00 | 0.00 |
October | 0.244854E+10 | 0.314815E+10 | 0.305819E+10 | 0.115971E+10 | 0.189848E+10 | 0.00 | 0.00 |
November | 0.946987E+09 | 0.461517E+10 | 0.188357E+10 | 0.629423E+09 | 0.125414E+10 | 0.00 | 0.00 |
December | 0.564727E+09 | 0.795399E+10 | 0.177583E+10 | 0.655981E+09 | 0.111985E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579013E+11 | 0.457317E+11 | 0.586201E+11 | 0.267168E+11 | 0.319034E+11 | 0.00 | 0.00 |
Minimum of Months | 0.564727E+09 | 0.122154E+10 | 0.177583E+10 | 0.629423E+09 | 0.111985E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101675E+11 | 0.821710E+10 | 0.818153E+10 | 0.386734E+10 | 0.433894E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.924902E+10 | 0.109764E+11 | 0.108251E+11 | 0.753344E+10 | 0.329171E+10 | 0.00 | 0.00 |
February | 0.119187E+11 | 0.831441E+10 | 0.123801E+11 | 0.836500E+10 | 0.401515E+10 | 0.00 | 0.00 |
March | 0.118941E+11 | 0.768679E+10 | 0.120713E+11 | 0.764067E+10 | 0.443067E+10 | 0.00 | 0.00 |
April | 0.114011E+11 | 0.493600E+10 | 0.105741E+11 | 0.573638E+10 | 0.483776E+10 | 0.00 | 0.00 |
May | 0.106968E+11 | 0.301907E+10 | 0.918142E+10 | 0.313192E+10 | 0.604950E+10 | 0.00 | 0.00 |
June | 0.991728E+10 | 0.200901E+10 | 0.797149E+10 | 0.211720E+10 | 0.585428E+10 | 0.00 | 0.00 |
July | 0.116981E+11 | 0.193823E+10 | 0.900564E+10 | 0.284480E+10 | 0.616084E+10 | 0.00 | 0.00 |
August | 0.121238E+11 | 0.225267E+10 | 0.962207E+10 | 0.402009E+10 | 0.560198E+10 | 0.00 | 0.00 |
September | 0.116492E+11 | 0.335628E+10 | 0.998179E+10 | 0.531564E+10 | 0.466615E+10 | 0.00 | 0.00 |
October | 0.915246E+10 | 0.486433E+10 | 0.881334E+10 | 0.518550E+10 | 0.362784E+10 | 0.00 | 0.00 |
November | 0.699471E+10 | 0.663747E+10 | 0.759897E+10 | 0.477118E+10 | 0.282779E+10 | 0.00 | 0.00 |
December | 0.659749E+10 | 0.105895E+11 | 0.835784E+10 | 0.548247E+10 | 0.287537E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123293E+12 | 0.665802E+11 | 0.116383E+12 | 0.621443E+11 | 0.542390E+11 | 0.00 | 0.00 |
Minimum of Months | 0.659749E+10 | 0.193823E+10 | 0.759897E+10 | 0.211720E+10 | 0.282779E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121238E+11 | 0.109764E+11 | 0.123801E+11 | 0.836500E+10 | 0.616084E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.997296E+09 | 0.847261E+10 | 0.231988E+10 | 0.971100E+09 | 0.134878E+10 | 0.00 | 0.00 |
February | 0.227536E+10 | 0.614877E+10 | 0.341466E+10 | 0.155951E+10 | 0.185515E+10 | 0.00 | 0.00 |
March | 0.399847E+10 | 0.543307E+10 | 0.497588E+10 | 0.254651E+10 | 0.242937E+10 | 0.00 | 0.00 |
April | 0.596398E+10 | 0.332402E+10 | 0.615153E+10 | 0.311626E+10 | 0.303528E+10 | 0.00 | 0.00 |
May | 0.887624E+10 | 0.204863E+10 | 0.781062E+10 | 0.372669E+10 | 0.408394E+10 | 0.00 | 0.00 |
June | 0.878783E+10 | 0.138527E+10 | 0.729402E+10 | 0.315491E+10 | 0.413910E+10 | 0.00 | 0.00 |
July | 0.100072E+11 | 0.137087E+10 | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.00 | 0.00 |
August | 0.798328E+10 | 0.156530E+10 | 0.662116E+10 | 0.300915E+10 | 0.361201E+10 | 0.00 | 0.00 |
September | 0.537253E+10 | 0.226408E+10 | 0.500782E+10 | 0.225038E+10 | 0.275744E+10 | 0.00 | 0.00 |
October | 0.275872E+10 | 0.338555E+10 | 0.326851E+10 | 0.131218E+10 | 0.195633E+10 | 0.00 | 0.00 |
November | 0.100624E+10 | 0.485869E+10 | 0.192062E+10 | 0.647284E+09 | 0.127334E+10 | 0.00 | 0.00 |
December | 0.555866E+09 | 0.821274E+10 | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.585831E+11 | 0.484696E+11 | 0.585999E+11 | 0.266543E+11 | 0.319457E+11 | 0.00 | 0.00 |
Minimum of Months | 0.555866E+09 | 0.137087E+10 | 0.176898E+10 | 0.618762E+09 | 0.115021E+10 | 0.00 | 0.00 |
Maximum of Months | 0.100072E+11 | 0.847261E+10 | 0.804626E+10 | 0.374155E+10 | 0.430471E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.464919E+11 | -0.454372E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.105471E+10 | 58.98 | 0.00 | 0.00 |
February | 0.431688E+11 | -0.422327E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -936119969.1 | 58.98 | 0.00 | 0.00 |
March | 0.505231E+11 | -0.494899E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103320E+10 | 58.98 | 0.00 | 0.00 |
April | 0.445109E+11 | -0.435173E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993568270.8 | 58.98 | 0.00 | 0.00 |
May | 0.451712E+11 | -0.441457E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102554E+10 | 58.97 | 0.00 | 0.00 |
June | 0.421400E+11 | -0.411472E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992869269.7 | 58.98 | 0.00 | 0.00 |
July | 0.380781E+11 | -0.370586E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101953E+10 | 58.98 | 0.00 | 0.00 |
August | 0.404353E+11 | -0.394115E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102382E+10 | 58.98 | 0.00 | 0.00 |
September | 0.369223E+11 | -0.359333E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989082771.7 | 58.97 | 0.00 | 0.00 |
October | 0.395405E+11 | -0.385180E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102242E+10 | 58.98 | 0.00 | 0.00 |
November | 0.410167E+11 | -0.400240E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992714234.7 | 58.98 | 0.00 | 0.00 |
December | 0.433100E+11 | -0.422746E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103539E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.511309E+12 | -0.499190E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.121190E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.369223E+11 | -0.494899E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.105471E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.505231E+11 | -0.359333E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -936119969.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5063.31 | 35.68 | 237.33 | 236.17 | 4200.97 | 36.63 | 241.50 | 223.67 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 7827.87 | 36.20 | 261.67 | 256.67 | 3311.50 | 30.30 | 230.33 | 237.50 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 11024.10 | 35.36 | 229.50 | 319.67 | 1796.96 | 22.49 | 209.83 | 284.17 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:49 | 2331.80 | 20.03 | 102.67 | 347.00 | 1418.96 | 21.47 | 213.50 | 311.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 2053.24 | 20.52 | 174.67 | 408.50 | 1137.84 | 21.94 | 285.17 | 364.33 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-05:19 | 1960.21 | 20.58 | 164.50 | 408.50 | 1100.33 | 22.01 | 280.00 | 365.83 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2122.65 | 20.86 | 187.33 | 415.67 | 1200.20 | 22.30 | 298.33 | 375.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2676.60 | 21.50 | 177.83 | 374.83 | 1387.63 | 22.56 | 268.33 | 335.33 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:40 | 5192.36 | 25.28 | 217.17 | 328.67 | 1429.55 | 22.58 | 241.50 | 295.17 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 5535.25 | 32.03 | 275.50 | 295.50 | 1535.54 | 26.10 | 248.50 | 269.17 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-07:00 | 4008.38 | 34.23 | 245.00 | 238.83 | 3286.05 | 35.42 | 247.50 | 216.33 |
December | 226.33 | 0.49 | 0.48 | 01-DEC-08:20 | 3770.50 | 33.78 | 213.50 | 221.33 | 3101.55 | 35.03 | 217.67 | 201.83 |
Annual Sum or Average | 3785.50 | 0.50 | 4126.40 | 26.75 | 2486.67 | 3851.33 | 1899.73 | 25.65 | 2982.17 | 3480.17 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1960.21 | 20.03 | 102.67 | 221.33 | 1100.33 | 21.47 | 209.83 | 201.83 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 11024.10 | 36.20 | 275.50 | 415.67 | 4200.97 | 36.63 | 298.33 | 375.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-08:39 | 1691.47 | 24.60 | 112.33 | 218.17 | 984.67 | 24.71 | 142.33 | 185.33 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2242.81 | 24.69 | 128.50 | 244.83 | 1194.93 | 24.77 | 171.67 | 217.50 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3787.91 | 26.43 | 118.00 | 315.17 | 2286.78 | 26.59 | 171.00 | 274.67 |
April | 296.33 | 0.50 | 0.48 | 01-APR-06:00 | 4052.56 | 25.33 | 113.00 | 354.50 | 2371.02 | 25.60 | 178.00 | 319.83 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:10 | 3679.19 | 24.71 | 172.50 | 417.33 | 1639.59 | 24.46 | 256.33 | 383.00 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 4468.18 | 25.58 | 145.50 | 416.50 | 2081.56 | 25.21 | 234.50 | 380.67 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:40 | 4272.86 | 25.64 | 160.50 | 423.00 | 1969.21 | 25.21 | 251.83 | 390.17 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 3582.39 | 24.75 | 134.33 | 379.33 | 1595.40 | 24.34 | 219.67 | 341.00 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:10 | 2797.24 | 23.59 | 141.33 | 328.33 | 1483.57 | 24.02 | 202.33 | 291.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2091.45 | 23.95 | 128.50 | 283.67 | 920.62 | 23.40 | 165.67 | 241.00 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-07:00 | 1388.98 | 23.45 | 97.00 | 222.33 | 756.08 | 23.68 | 132.67 | 179.33 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-08:20 | 1231.74 | 22.90 | 77.17 | 203.00 | 813.04 | 24.31 | 112.50 | 165.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3119.66 | 24.71 | 1528.67 | 3806.17 | 1565.44 | 24.69 | 2238.50 | 3368.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1231.74 | 22.90 | 77.17 | 203.00 | 756.08 | 23.40 | 112.50 | 165.00 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 4468.18 | 26.43 | 172.50 | 423.00 | 2371.02 | 26.59 | 256.33 | 390.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.53 | 0.48 | 01-JAN-09:00 | 631.71 | 17.11 | 0.00 | 202.17 | 362.52 | 18.75 | 1.50 | 134.33 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:20 | 802.97 | 18.34 | 0.00 | 234.50 | 476.78 | 19.95 | 41.00 | 187.17 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 878.08 | 18.92 | 0.17 | 306.00 | 555.53 | 20.51 | 61.83 | 244.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 998.71 | 19.28 | 11.00 | 351.50 | 629.02 | 20.70 | 107.50 | 311.00 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:30 | 1347.46 | 22.35 | 115.67 | 429.50 | 768.95 | 22.84 | 309.67 | 403.17 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1592.84 | 23.62 | 184.67 | 435.50 | 877.25 | 23.78 | 319.50 | 400.00 |
July | 409.17 | 0.48 | 0.48 | 01-JUL-04:49 | 1525.36 | 23.19 | 186.00 | 436.67 | 895.75 | 24.47 | 334.67 | 412.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1265.87 | 20.57 | 66.50 | 382.17 | 756.48 | 21.93 | 225.50 | 345.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 971.36 | 19.38 | 0.00 | 326.00 | 568.63 | 20.77 | 117.83 | 275.17 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 792.15 | 18.28 | 0.00 | 273.00 | 443.02 | 19.69 | 18.17 | 203.83 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:50 | 611.76 | 16.90 | 0.00 | 205.67 | 339.38 | 18.31 | 0.33 | 122.00 |
December | 226.33 | 0.53 | 0.48 | 01-DEC-09:20 | 583.67 | 16.83 | 0.00 | 185.83 | 324.17 | 18.34 | 0.00 | 92.00 |
Annual Sum or Average | 3785.50 | 0.50 | 1068.76 | 20.03 | 564.00 | 3768.50 | 621.56 | 21.23 | 1537.50 | 3131.00 | ||
Minimum of Months | 226.33 | 0.48 | 0.48 | 583.67 | 16.83 | 0.00 | 185.83 | 324.17 | 18.31 | 0.00 | 92.00 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 1592.84 | 23.62 | 186.00 | 436.67 | 895.75 | 24.47 | 334.67 | 412.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-09:00 | 1646.27 | 24.51 | 108.67 | 221.33 | 930.85 | 24.52 | 141.83 | 187.67 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:20 | 2253.77 | 24.92 | 131.50 | 247.00 | 1210.22 | 24.98 | 175.67 | 219.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3473.79 | 25.14 | 107.67 | 314.50 | 2010.45 | 25.35 | 170.67 | 272.67 |
April | 296.33 | 0.50 | 0.48 | 01-APR-08:09 | 4137.52 | 23.81 | 102.67 | 350.67 | 1799.73 | 23.00 | 153.83 | 316.67 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-06:19 | 3377.94 | 22.09 | 110.83 | 418.83 | 1935.27 | 22.99 | 228.33 | 386.50 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 3622.11 | 21.21 | 68.83 | 428.00 | 1593.95 | 21.69 | 219.33 | 391.33 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 3902.13 | 21.63 | 80.67 | 431.00 | 1733.99 | 21.90 | 220.83 | 394.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3545.23 | 23.36 | 118.33 | 380.00 | 1980.76 | 23.92 | 205.67 | 341.33 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:00 | 3009.06 | 24.00 | 139.83 | 329.50 | 1709.89 | 24.49 | 205.33 | 295.17 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2253.20 | 24.65 | 129.00 | 285.17 | 962.32 | 23.79 | 168.33 | 243.67 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:50 | 1372.02 | 23.31 | 95.67 | 224.33 | 720.15 | 23.38 | 128.83 | 183.67 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-09:09 | 1257.69 | 22.45 | 78.67 | 207.33 | 654.65 | 22.63 | 102.67 | 164.67 |
Annual Sum or Average | 3785.50 | 0.50 | 2967.36 | 23.24 | 1272.33 | 3837.67 | 1504.66 | 23.42 | 2121.33 | 3397.33 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1257.69 | 21.21 | 68.83 | 207.33 | 654.65 | 21.69 | 102.67 | 164.67 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 4137.52 | 25.14 | 139.83 | 431.00 | 2010.45 | 25.35 | 228.33 | 394.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5099.51 | 35.11 | 232.50 | 236.17 | 4326.65 | 36.17 | 233.17 | 226.17 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 7881.60 | 35.66 | 255.83 | 256.83 | 4279.00 | 31.68 | 200.00 | 242.83 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 11098.43 | 34.29 | 215.00 | 320.17 | 1936.36 | 17.74 | 5.33 | 287.33 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:49 | 2391.30 | 13.66 | 0.00 | 347.67 | 1528.48 | 17.27 | 2.83 | 316.17 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:10 | 2084.77 | 14.31 | 0.00 | 408.67 | 1215.32 | 17.79 | 0.00 | 369.00 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-05:19 | 1991.73 | 14.61 | 0.00 | 409.33 | 1174.68 | 18.08 | 0.00 | 370.00 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:19 | 2158.79 | 14.88 | 0.00 | 415.83 | 1282.43 | 18.38 | 1.00 | 379.67 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2715.51 | 15.45 | 10.00 | 374.83 | 1483.76 | 18.36 | 8.83 | 338.33 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:40 | 5229.29 | 21.07 | 113.67 | 328.83 | 1528.89 | 18.05 | 11.83 | 298.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 5563.46 | 31.01 | 261.83 | 296.00 | 1625.18 | 22.47 | 104.17 | 271.33 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-07:00 | 4032.04 | 33.69 | 242.17 | 239.17 | 3371.20 | 34.97 | 245.17 | 218.17 |
December | 226.33 | 0.49 | 0.48 | 01-DEC-08:20 | 3791.36 | 32.98 | 207.00 | 221.50 | 3190.52 | 34.37 | 210.33 | 203.33 |
Annual Sum or Average | 3785.50 | 0.50 | 4165.10 | 22.99 | 1538.00 | 3855.00 | 2055.43 | 22.59 | 1022.67 | 3520.33 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1991.73 | 13.66 | 0.00 | 221.50 | 1174.68 | 17.27 | 0.00 | 203.33 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 11098.43 | 35.66 | 261.83 | 415.83 | 4326.65 | 36.17 | 245.17 | 379.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-08:39 | 1717.92 | 22.40 | 97.83 | 218.67 | 1022.39 | 23.08 | 82.67 | 189.17 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2284.05 | 22.16 | 86.33 | 246.00 | 1250.10 | 22.86 | 85.17 | 220.00 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3792.76 | 22.32 | 80.83 | 315.50 | 2365.30 | 24.67 | 77.00 | 279.33 |
April | 296.33 | 0.50 | 0.48 | 01-APR-06:00 | 4071.26 | 21.20 | 84.33 | 354.83 | 2461.61 | 23.40 | 75.17 | 323.67 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:10 | 3726.91 | 21.24 | 133.83 | 418.50 | 1716.40 | 21.94 | 85.67 | 386.00 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 4527.27 | 22.72 | 132.83 | 417.33 | 2170.87 | 22.75 | 83.00 | 385.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:40 | 4317.10 | 22.11 | 126.00 | 423.50 | 2059.28 | 22.74 | 81.67 | 393.33 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 3638.78 | 21.77 | 99.50 | 380.00 | 1674.44 | 21.79 | 56.83 | 345.17 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:10 | 2849.75 | 20.58 | 96.00 | 329.50 | 1547.70 | 21.68 | 69.50 | 294.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2107.74 | 20.68 | 98.50 | 283.83 | 965.97 | 21.18 | 58.83 | 245.83 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-07:00 | 1412.59 | 20.96 | 90.00 | 223.33 | 788.74 | 21.81 | 68.83 | 184.00 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-08:20 | 1254.04 | 20.26 | 66.33 | 203.67 | 843.97 | 22.63 | 75.83 | 171.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3156.86 | 21.57 | 1192.33 | 3814.67 | 1633.02 | 22.48 | 900.17 | 3417.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1254.04 | 20.26 | 66.33 | 203.67 | 788.74 | 21.18 | 56.83 | 171.00 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 4527.27 | 22.72 | 133.83 | 423.50 | 2461.61 | 24.67 | 85.67 | 393.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.53 | 0.48 | 01-JAN-09:50 | 638.90 | 11.04 | 0.00 | 202.83 | 384.79 | 14.71 | 0.00 | 145.83 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:20 | 813.74 | 12.57 | 0.00 | 234.67 | 506.73 | 16.18 | 0.00 | 193.00 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 894.26 | 13.53 | 0.00 | 306.33 | 592.02 | 17.14 | 0.00 | 253.50 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 1020.27 | 14.02 | 0.00 | 352.00 | 671.50 | 17.57 | 0.00 | 316.83 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1370.72 | 17.37 | 53.00 | 429.50 | 824.52 | 20.52 | 59.50 | 410.00 |
June | 401.83 | 0.48 | 0.48 | 01-JUN-04:49 | 1620.75 | 18.96 | 76.83 | 435.50 | 969.53 | 22.02 | 99.67 | 410.33 |
July | 409.17 | 0.48 | 0.48 | 01-JUL-04:49 | 1555.75 | 18.46 | 64.83 | 436.83 | 952.69 | 21.61 | 92.50 | 415.00 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1303.84 | 15.08 | 0.00 | 383.83 | 805.48 | 18.58 | 15.00 | 349.50 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:40 | 986.73 | 13.78 | 0.00 | 326.50 | 605.12 | 17.24 | 0.00 | 281.50 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 802.39 | 12.31 | 0.00 | 273.33 | 470.62 | 15.80 | 0.00 | 215.83 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:39 | 618.65 | 10.66 | 0.00 | 206.33 | 360.16 | 14.17 | 0.00 | 137.33 |
December | 226.33 | 0.53 | 0.48 | 01-DEC-09:09 | 589.89 | 10.55 | 0.00 | 186.67 | 343.87 | 14.16 | 0.00 | 110.50 |
Annual Sum or Average | 3785.50 | 0.50 | 1088.27 | 14.59 | 194.67 | 3774.33 | 665.88 | 18.00 | 266.67 | 3239.17 | ||
Minimum of Months | 226.33 | 0.48 | 0.48 | 589.89 | 10.55 | 0.00 | 186.67 | 343.87 | 14.16 | 0.00 | 110.50 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 1620.75 | 18.96 | 76.83 | 436.83 | 969.53 | 22.02 | 99.67 | 415.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-09:50 | 1672.47 | 22.22 | 91.33 | 221.83 | 969.42 | 22.85 | 77.33 | 191.17 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:20 | 2250.59 | 20.97 | 75.00 | 247.50 | 1266.49 | 23.06 | 79.50 | 222.67 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3535.96 | 22.36 | 78.83 | 315.00 | 2085.72 | 23.21 | 63.33 | 277.67 |
April | 296.33 | 0.50 | 0.48 | 01-APR-08:09 | 4203.28 | 20.76 | 84.50 | 351.33 | 1883.84 | 20.27 | 39.50 | 320.83 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-06:19 | 3433.94 | 18.45 | 80.33 | 418.83 | 2014.57 | 20.14 | 51.50 | 390.50 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3673.43 | 17.27 | 46.50 | 428.67 | 1674.08 | 18.39 | 0.00 | 395.67 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 3958.19 | 17.75 | 53.50 | 431.17 | 1821.49 | 18.62 | 2.17 | 398.33 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3586.33 | 19.98 | 79.17 | 380.67 | 2065.76 | 21.24 | 55.00 | 346.83 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:49 | 3022.72 | 20.91 | 99.00 | 329.17 | 1777.10 | 22.18 | 73.00 | 298.50 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2268.70 | 21.17 | 101.67 | 285.50 | 1009.72 | 21.53 | 59.50 | 248.33 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:39 | 1395.16 | 20.76 | 86.17 | 225.00 | 752.83 | 21.43 | 67.17 | 187.50 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-09:09 | 1278.90 | 19.83 | 64.00 | 207.83 | 684.93 | 20.65 | 55.17 | 169.67 |
Annual Sum or Average | 3785.50 | 0.50 | 3005.26 | 19.93 | 940.00 | 3842.50 | 1571.64 | 20.90 | 623.17 | 3447.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1278.90 | 17.27 | 46.50 | 207.83 | 684.93 | 18.39 | 0.00 | 169.67 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 4203.28 | 22.36 | 101.67 | 431.17 | 2085.72 | 23.21 | 79.50 | 398.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5100.74 | 35.11 | 232.50 | 236.17 | 4328.57 | 36.17 | 233.17 | 226.17 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 7883.56 | 35.65 | 255.83 | 256.83 | 4281.77 | 31.67 | 200.00 | 242.83 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 11101.09 | 34.28 | 215.00 | 320.17 | 1938.87 | 17.73 | 5.17 | 287.33 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:49 | 2394.14 | 13.63 | 0.00 | 347.67 | 1530.38 | 17.26 | 2.83 | 316.17 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:10 | 2087.86 | 14.28 | 0.00 | 408.67 | 1217.20 | 17.78 | 0.00 | 369.00 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-05:19 | 1994.52 | 14.58 | 0.00 | 409.33 | 1176.43 | 18.07 | 0.00 | 370.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:19 | 2161.77 | 14.85 | 0.00 | 415.83 | 1284.31 | 18.37 | 1.00 | 379.67 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2719.10 | 15.42 | 10.00 | 375.00 | 1486.03 | 18.35 | 8.17 | 338.50 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:40 | 5232.62 | 21.05 | 113.67 | 328.83 | 1531.24 | 18.03 | 11.50 | 298.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 5565.84 | 31.00 | 261.83 | 296.00 | 1627.45 | 22.46 | 104.00 | 271.33 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-07:00 | 4033.42 | 33.68 | 242.00 | 239.17 | 3373.11 | 34.97 | 245.17 | 218.33 |
December | 226.33 | 0.49 | 0.48 | 01-DEC-08:20 | 3792.64 | 32.97 | 207.00 | 221.50 | 3192.17 | 34.36 | 210.33 | 203.67 |
Annual Sum or Average | 3785.50 | 0.50 | 4167.69 | 22.97 | 1537.83 | 3855.17 | 2057.50 | 22.58 | 1021.33 | 3521.33 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1994.52 | 13.63 | 0.00 | 221.50 | 1176.43 | 17.26 | 0.00 | 203.67 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 11101.09 | 35.65 | 261.83 | 415.83 | 4328.57 | 36.17 | 245.17 | 379.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-08:39 | 1718.97 | 22.37 | 97.83 | 218.67 | 1023.40 | 23.07 | 82.33 | 189.33 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2229.90 | 20.65 | 73.67 | 245.50 | 1251.41 | 22.85 | 84.83 | 220.00 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3794.02 | 22.30 | 80.83 | 315.67 | 2366.72 | 24.65 | 76.83 | 279.67 |
April | 296.33 | 0.50 | 0.48 | 01-APR-06:00 | 4072.57 | 21.17 | 84.33 | 354.83 | 2463.09 | 23.39 | 75.17 | 323.83 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:10 | 3729.25 | 21.21 | 133.83 | 418.50 | 1718.24 | 21.93 | 85.67 | 386.50 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 4529.51 | 22.69 | 132.83 | 417.33 | 2172.85 | 22.74 | 83.00 | 385.33 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:40 | 4319.29 | 22.08 | 126.00 | 423.50 | 2061.29 | 22.73 | 81.67 | 393.33 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 3640.81 | 21.74 | 99.50 | 380.33 | 1676.32 | 21.78 | 56.83 | 345.17 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:10 | 2851.42 | 20.56 | 96.00 | 329.50 | 1549.25 | 21.67 | 69.33 | 295.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2109.24 | 20.65 | 98.33 | 284.00 | 967.22 | 21.17 | 58.67 | 245.83 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-07:00 | 1413.73 | 20.94 | 90.00 | 223.33 | 789.72 | 21.80 | 68.67 | 184.00 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-08:20 | 1255.08 | 20.24 | 66.33 | 203.67 | 844.89 | 22.62 | 75.50 | 171.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3154.66 | 21.44 | 1179.50 | 3814.83 | 1634.56 | 22.47 | 898.50 | 3419.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1255.08 | 20.24 | 66.33 | 203.67 | 789.72 | 21.17 | 56.83 | 171.00 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 4529.51 | 22.69 | 133.83 | 423.50 | 2463.09 | 24.65 | 85.67 | 393.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.53 | 0.48 | 01-JAN-09:50 | 639.58 | 11.01 | 0.00 | 202.83 | 385.36 | 14.70 | 0.00 | 146.00 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:20 | 814.51 | 12.54 | 0.00 | 234.67 | 507.42 | 16.16 | 0.00 | 193.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 894.88 | 13.50 | 0.00 | 306.50 | 592.70 | 17.12 | 0.00 | 253.50 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 1021.00 | 13.99 | 0.00 | 352.00 | 672.25 | 17.56 | 0.00 | 316.83 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1372.20 | 17.34 | 53.00 | 429.50 | 825.65 | 20.51 | 59.50 | 410.00 |
June | 401.83 | 0.48 | 0.48 | 01-JUN-04:49 | 1622.23 | 18.93 | 76.83 | 435.50 | 970.77 | 22.01 | 99.50 | 410.33 |
July | 409.17 | 0.48 | 0.48 | 01-JUL-04:49 | 1557.12 | 18.43 | 64.83 | 436.83 | 953.90 | 21.60 | 91.50 | 415.00 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1305.11 | 15.05 | 0.00 | 384.00 | 806.55 | 18.56 | 14.17 | 349.67 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:40 | 987.80 | 13.75 | 0.00 | 326.50 | 605.97 | 17.22 | 0.00 | 281.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 803.41 | 12.28 | 0.00 | 273.33 | 471.36 | 15.78 | 0.00 | 215.83 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:39 | 619.44 | 10.63 | 0.00 | 206.50 | 360.74 | 14.16 | 0.00 | 137.50 |
December | 226.33 | 0.53 | 0.48 | 01-DEC-09:09 | 590.61 | 10.52 | 0.00 | 186.67 | 344.42 | 14.14 | 0.00 | 111.17 |
Annual Sum or Average | 3785.50 | 0.50 | 1089.34 | 14.56 | 194.67 | 3774.83 | 666.77 | 17.99 | 264.67 | 3241.00 | ||
Minimum of Months | 226.33 | 0.48 | 0.48 | 590.61 | 10.52 | 0.00 | 186.67 | 344.42 | 14.14 | 0.00 | 111.17 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 1622.23 | 18.93 | 76.83 | 436.83 | 970.77 | 22.01 | 99.50 | 415.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-09:50 | 1673.52 | 22.20 | 91.33 | 221.83 | 970.43 | 22.84 | 77.00 | 191.17 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:20 | 2251.83 | 20.95 | 75.00 | 247.50 | 1267.80 | 23.04 | 78.83 | 222.83 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3537.16 | 22.34 | 78.83 | 315.17 | 2087.14 | 23.19 | 62.50 | 277.67 |
April | 296.33 | 0.50 | 0.48 | 01-APR-08:09 | 4204.65 | 20.73 | 84.50 | 351.33 | 1885.30 | 20.26 | 39.50 | 321.17 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-06:19 | 3436.09 | 18.42 | 80.33 | 418.83 | 2016.34 | 20.12 | 51.50 | 390.50 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3675.60 | 17.24 | 46.50 | 428.67 | 1675.98 | 18.37 | 0.00 | 395.83 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 3960.38 | 17.72 | 53.50 | 431.17 | 1823.46 | 18.60 | 2.17 | 398.83 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3588.52 | 19.95 | 79.17 | 380.67 | 2067.78 | 21.22 | 55.00 | 347.00 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:49 | 3024.53 | 20.88 | 99.00 | 329.17 | 1778.69 | 22.17 | 73.00 | 298.50 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2270.24 | 21.14 | 101.67 | 285.50 | 1011.04 | 21.52 | 59.50 | 248.67 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:39 | 1396.29 | 20.73 | 86.17 | 225.17 | 753.82 | 21.42 | 67.17 | 187.50 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-09:09 | 1279.95 | 19.80 | 64.00 | 207.83 | 685.87 | 20.64 | 54.67 | 170.17 |
Annual Sum or Average | 3785.50 | 0.50 | 3006.94 | 19.90 | 940.00 | 3842.83 | 1573.18 | 20.89 | 620.83 | 3449.83 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1279.95 | 17.24 | 46.50 | 207.83 | 685.87 | 18.37 | 0.00 | 170.17 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 4204.65 | 22.34 | 101.67 | 431.17 | 2087.14 | 23.19 | 78.83 | 398.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211352E+11 | 94572.88 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.638915E+10 | 84167.46 | 14-FEB-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677877E+09 | 63184.09 | 15-MAR-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273373E+09 | 30709.61 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70964519.39 | 17288.43 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 59893.98 | 99.55 | 02-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6.14 | 0.01 | 26-JUL-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 147050.70 | 402.49 | 19-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54821785.07 | 10833.10 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344254E+09 | 38529.90 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.499222E+09 | 39328.52 | 13-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102409E+11 | 84695.86 | 20-DEC-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6.14 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.211352E+11 | 94572.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.462405E+10 | 13077.98 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152345E+10 | 14046.49 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344634E+09 | 14103.62 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 758555.95 | 458.59 | 05-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169421E+09 | 13023.33 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188344E+10 | 14137.55 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.854575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.462405E+10 | 14137.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275475E+10 | 16090.12 | 12-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.932504E+09 | 16503.34 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261345E+09 | 16535.78 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4479422.47 | 4059.00 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3586895.72 | 941.38 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195504E+09 | 16066.68 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158726E+10 | 16536.27 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275475E+10 | 16536.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.343314E+10 | 22752.67 | 04-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133845E+10 | 23359.29 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459289E+09 | 23464.21 | 23-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30465406.06 | 23444.84 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25705892.71 | 21918.18 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.389433E+09 | 23484.21 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195327E+10 | 23438.55 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.762975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.343314E+10 | 23484.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128039E+10 | 15241.50 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151615E+09 | 15215.11 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 511119.13 | 7917.21 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 233092.18 | 3107.90 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36374304.15 | 15214.84 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128039E+10 | 15241.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.265825E+12 | 1026793.27 | 06-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.883792E+11 | 977726.06 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135363E+11 | 700146.14 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291719E+10 | 394056.53 | 24-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141448E+10 | 307532.81 | 31-MAY-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186363E+09 | 159792.80 | 09-JUN-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65063758.40 | 44568.35 | 08-JUL-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.253595E+09 | 190484.17 | 17-AUG-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193044E+10 | 272077.35 | 27-SEP-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.395054E+10 | 382751.82 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.893697E+10 | 438772.20 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148843E+12 | 932070.78 | 20-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 65063758.40 | 44568.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.265825E+12 | 1026793.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.539375E+11 | 571505.37 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.994258E+10 | 571719.80 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160230E+10 | 569302.93 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568847E+10 | 570832.16 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303986E+11 | 571302.33 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101570E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.539375E+11 | 571719.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145722E+12 | 126232.86 | 06-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852998E+11 | 125181.26 | 22-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474509E+11 | 124226.51 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.768832E+10 | 134434.03 | 20-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30708384.90 | 90075.38 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.533509E+10 | 123825.01 | 06-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.414102E+11 | 124817.94 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130174E+12 | 124750.02 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145722E+12 | 134434.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.843388E+11 | 201810.83 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425891E+11 | 202072.17 | 21-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212739E+11 | 201724.36 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.300753E+10 | 201509.28 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290962E+10 | 201314.42 | 16-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231084E+11 | 201786.37 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.766152E+11 | 201815.82 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.843388E+11 | 202072.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.886711E+11 | 243776.05 | 17-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431791E+11 | 243717.32 | 21-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242900E+11 | 242317.67 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.433605E+10 | 241569.43 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4685257.01 | 3222.19 | 01-MAY-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315432E+10 | 242204.70 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258351E+11 | 242394.39 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.853471E+11 | 243658.53 | 04-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274817E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.886711E+11 | 243776.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.779843E+11 | 205053.47 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368602E+11 | 204977.17 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172895E+11 | 204970.98 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216038E+10 | 204132.31 | 04-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193061E+10 | 204092.50 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175767E+11 | 205030.13 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648279E+11 | 205058.23 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.779843E+11 | 205058.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.336215E+11 | 106712.88 | 06-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134834E+11 | 104125.13 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352723E+10 | 78819.35 | 15-MAR-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350341E+09 | 34829.31 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102720E+09 | 20495.08 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7473967.20 | 5425.82 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4.49 | 0.00 | 07-JUL-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 724229.61 | 503.18 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87491465.64 | 13893.56 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352351E+09 | 48152.76 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221302E+10 | 45499.79 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221830E+11 | 100916.55 | 20-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336215E+11 | 106712.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.227267E+11 | 71584.38 | 17-JAN-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130892E+11 | 71582.88 | 07-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.733166E+10 | 71624.99 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163257E+10 | 71603.95 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41645974.16 | 43764.26 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181485E+10 | 71829.30 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.861656E+10 | 71568.96 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192538E+11 | 71593.47 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.745070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227267E+11 | 71829.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212522E+11 | 17077.26 | 06-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143287E+11 | 16135.69 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.951399E+10 | 15951.57 | 25-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288169E+10 | 15954.59 | 10-APR-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138459E+09 | 15781.13 | 01-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3044210.94 | 1683.36 | 19-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196652E+09 | 15865.08 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277425E+10 | 15953.11 | 30-OCT-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.913586E+10 | 15985.15 | 21-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198580E+11 | 15951.15 | 07-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.800828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212522E+11 | 17077.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131215E+11 | 20863.69 | 20-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790849E+10 | 20865.20 | 10-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.463264E+10 | 20913.94 | 03-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119885E+10 | 20836.48 | 10-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37394490.30 | 20667.98 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 779713.77 | 778.54 | 19-AUG-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77543006.56 | 20777.65 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146408E+10 | 20933.38 | 31-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.536279E+10 | 20865.95 | 28-NOV-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125376E+11 | 20862.06 | 23-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131215E+11 | 20933.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145117E+11 | 25750.36 | 03-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.859954E+10 | 25754.83 | 08-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566298E+10 | 25828.74 | 23-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185889E+10 | 25830.66 | 27-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104558E+09 | 25440.82 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2629556.42 | 748.32 | 19-AUG-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106388E+09 | 25529.48 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176496E+10 | 25736.42 | 30-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.626295E+10 | 25832.39 | 07-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145205E+11 | 25837.58 | 06-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145205E+11 | 25837.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120441E+11 | 23062.72 | 28-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.662926E+10 | 23059.79 | 24-FEB-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.372844E+10 | 23076.67 | 02-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918958E+09 | 22945.59 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36242103.43 | 13739.07 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39907102.14 | 12600.79 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957885E+09 | 23042.68 | 30-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394278E+10 | 23151.56 | 14-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102770E+11 | 23073.73 | 01-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120441E+11 | 23151.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220991E+10 | 38754.57 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 162.97 | 0.82 | 19-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 126.79 | 0.85 | 06-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 272.00 | 0.90 | 05-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 248.27 | 0.88 | 11-SEP-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220991E+10 | 38754.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7203143.71 | 7203143.71 | 4553.41 | 27-JAN-13:07 | 4553.41 | 0.00 |
February | 0.00 | 0.00 | 0.571018E+09 | 0.571018E+09 | 21938.44 | 28-FEB-15:40 | 21938.44 | 0.00 |
March | 0.00 | 0.00 | 0.111982E+10 | 0.111982E+10 | 21503.13 | 23-MAR-15:20 | 21503.13 | 0.00 |
April | 0.00 | 0.00 | 0.685018E+10 | 0.685018E+10 | 83635.20 | 23-APR-16:01 | 83635.20 | 0.01 |
May | 0.00 | 0.00 | 0.338152E+11 | 0.331321E+11 | 117798.79 | 26-MAY-11:00 | 79347.31 | 0.21 |
June | 0.00 | 0.00 | 0.786817E+11 | 0.634222E+11 | 212833.59 | 30-JUN-05:02 | 143346.23 | 0.46 |
July | 0.00 | 0.00 | 0.109737E+12 | 0.831548E+11 | 240742.81 | 05-JUL-10:20 | 87720.73 | 0.68 |
August | 0.00 | 0.00 | 0.850143E+11 | 0.647775E+11 | 213341.11 | 31-AUG-12:50 | 96701.93 | 0.65 |
September | 0.00 | 0.00 | 0.175228E+11 | 0.157105E+11 | 129546.48 | 01-SEP-11:00 | 86094.95 | 0.17 |
October | 0.00 | 0.00 | 0.515813E+10 | 0.515813E+10 | 70225.25 | 19-OCT-15:00 | 70225.25 | 0.03 |
November | 0.00 | 0.00 | 0.277345E+10 | 0.277345E+10 | 41030.79 | 17-NOV-14:10 | 41030.79 | 0.02 |
December | 0.00 | 0.00 | 21788093.76 | 21788093.76 | 4709.07 | 08-DEC-13:04 | 4709.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.341272E+12 | 0.276699E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 7203143.71 | 7203143.71 | 4553.41 | 4553.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109737E+12 | 0.831548E+11 | 240742.81 | 143346.23 | 0.68 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11711209.26 | 11711209.26 | 12652.93 | 21-JAN-15:02 | 12652.93 | 0.00 |
February | 0.00 | 0.00 | 0.206438E+09 | 0.206438E+09 | 18598.76 | 28-FEB-15:20 | 18598.76 | 0.00 |
March | 0.00 | 0.00 | 0.406025E+10 | 0.406025E+10 | 249983.75 | 31-MAR-15:40 | 249983.75 | 0.00 |
April | 0.00 | 0.00 | 0.725900E+11 | 0.725900E+11 | 776081.70 | 23-APR-15:42 | 776081.70 | 0.01 |
May | 0.00 | 0.00 | 0.309043E+12 | 0.302460E+12 | 1118530.50 | 25-MAY-16:00 | 953188.22 | 0.21 |
June | 0.00 | 0.00 | 0.665319E+12 | 0.541347E+12 | 2171584.79 | 30-JUN-05:02 | 1312547.84 | 0.42 |
July | 0.00 | 0.00 | 0.862259E+12 | 0.672090E+12 | 2122421.42 | 05-JUL-10:25 | 765074.82 | 0.56 |
August | 0.00 | 0.00 | 0.638476E+12 | 0.500143E+12 | 1692368.16 | 31-AUG-12:50 | 771691.29 | 0.54 |
September | 0.00 | 0.00 | 0.162239E+12 | 0.148975E+12 | 1195614.24 | 01-SEP-12:05 | 828552.00 | 0.17 |
October | 0.00 | 0.00 | 0.474152E+11 | 0.474152E+11 | 638076.68 | 19-OCT-15:00 | 638076.68 | 0.03 |
November | 0.00 | 0.00 | 0.342402E+10 | 0.342402E+10 | 130100.19 | 17-NOV-13:20 | 130100.19 | 0.01 |
December | 0.00 | 0.00 | 22881801.89 | 22881801.89 | 13282.80 | 08-DEC-15:02 | 13282.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.276507E+13 | 0.229275E+13 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 11711209.26 | 11711209.26 | 12652.93 | 12652.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.862259E+12 | 0.672090E+12 | 2171584.79 | 1312547.84 | 0.56 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 265049.85 | 265049.85 | 60.77 | 19-JAN-12:10 | 60.77 | 0.00 |
February | 0.00 | 0.00 | 15230552.88 | 15230552.88 | 1160.93 | 28-FEB-14:50 | 1160.93 | 0.00 |
March | 0.00 | 0.00 | 0.179030E+09 | 0.179030E+09 | 12954.22 | 31-MAR-15:40 | 12954.22 | 0.00 |
April | 0.00 | 0.00 | 0.442438E+10 | 0.442438E+10 | 88306.29 | 23-APR-15:31 | 88306.29 | 0.01 |
May | 0.00 | 0.00 | 0.317803E+11 | 0.311057E+11 | 128990.60 | 25-MAY-16:00 | 112301.96 | 0.20 |
June | 0.00 | 0.00 | 0.697829E+11 | 0.571348E+11 | 237772.12 | 30-JUN-05:02 | 143070.13 | 0.41 |
July | 0.00 | 0.00 | 0.916194E+11 | 0.716487E+11 | 236652.25 | 05-JUL-12:05 | 105149.88 | 0.55 |
August | 0.00 | 0.00 | 0.653099E+11 | 0.511509E+11 | 182375.01 | 29-AUG-16:00 | 105632.29 | 0.53 |
September | 0.00 | 0.00 | 0.138756E+11 | 0.126934E+11 | 137925.15 | 01-SEP-14:00 | 107872.71 | 0.16 |
October | 0.00 | 0.00 | 0.271757E+10 | 0.271757E+10 | 53248.02 | 19-OCT-15:00 | 53248.02 | 0.03 |
November | 0.00 | 0.00 | 0.213783E+09 | 0.213783E+09 | 8924.83 | 01-NOV-15:00 | 8924.83 | 0.01 |
December | 0.00 | 0.00 | 84616.64 | 84616.64 | 121.31 | 28-DEC-12:20 | 121.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.279918E+12 | 0.231284E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 84616.64 | 84616.64 | 60.77 | 60.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.916194E+11 | 0.716487E+11 | 237772.12 | 143070.13 | 0.55 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 17241436.13 | 17241436.13 | 329.15 | 25-JAN-10:30 | 329.15 | 0.00 |
February | 0.00 | 0.00 | 22903698.24 | 22903698.24 | 1913.87 | 08-FEB-18:10 | 1913.87 | 0.00 |
March | 0.00 | 0.00 | 41648361.69 | 41648361.69 | 5098.18 | 22-MAR-16:10 | 5098.18 | 0.00 |
April | 0.00 | 0.00 | 0.655600E+09 | 0.655600E+09 | 21678.46 | 13-APR-15:00 | 21678.46 | 0.00 |
May | 0.00 | 0.00 | 0.160077E+11 | 0.159129E+11 | 83768.13 | 26-MAY-04:12 | 54095.72 | 0.18 |
June | 0.00 | 0.00 | 0.371949E+11 | 0.313691E+11 | 137898.43 | 30-JUN-04:03 | 78142.60 | 0.34 |
July | 0.00 | 0.00 | 0.500980E+11 | 0.408458E+11 | 145049.04 | 05-JUL-10:05 | 53478.05 | 0.45 |
August | 0.00 | 0.00 | 0.407455E+11 | 0.323403E+11 | 118467.57 | 27-AUG-17:54 | 64037.98 | 0.43 |
September | 0.00 | 0.00 | 0.751855E+10 | 0.690966E+10 | 84488.15 | 01-SEP-04:12 | 32171.43 | 0.10 |
October | 0.00 | 0.00 | 0.947010E+09 | 0.947010E+09 | 36652.13 | 19-OCT-15:00 | 36652.13 | 0.01 |
November | 0.00 | 0.00 | 0.130720E+09 | 0.129086E+09 | 16367.82 | 21-NOV-06:03 | 9166.42 | 0.01 |
December | 0.00 | 0.00 | 52940311.20 | 52940311.20 | 15357.27 | 18-DEC-16:20 | 15357.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153433E+12 | 0.129244E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 17241436.13 | 17241436.13 | 329.15 | 329.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.500980E+11 | 0.408458E+11 | 145049.04 | 78142.60 | 0.45 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.577875E+10 | 0.577875E+10 | 2796.40 | 21-JAN-16:00 | 2796.40 | 0.00 |
February | 0.00 | 0.00 | 0.105608E+11 | 0.104892E+11 | 5158.72 | 20-FEB-17:33 | 5158.72 | 0.00 |
March | 0.00 | 0.00 | 0.144194E+11 | 0.143527E+11 | 5688.79 | 05-MAR-03:43 | 5366.11 | 0.00 |
April | 0.00 | 0.00 | 0.570164E+11 | 0.555489E+11 | 392423.50 | 23-APR-15:51 | 390820.06 | 0.00 |
May | 0.00 | 0.00 | 0.271925E+11 | 0.257659E+11 | 155591.20 | 25-MAY-13:05 | 124799.28 | 0.00 |
June | 0.00 | 0.00 | 0.175492E+12 | 0.129232E+12 | 467044.78 | 29-JUN-23:03 | 192266.59 | 0.00 |
July | 0.00 | 0.00 | 0.550004E+12 | 0.338501E+12 | 472302.78 | 15-JUL-14:00 | 244837.08 | 0.00 |
August | 0.00 | 0.00 | 0.697069E+12 | 0.418985E+12 | 451040.45 | 31-AUG-12:55 | 213475.88 | 0.00 |
September | 0.00 | 0.00 | 0.529868E+10 | 0.471358E+10 | 128043.14 | 01-SEP-15:00 | 110603.33 | 0.00 |
October | 0.00 | 0.00 | 0.105685E+11 | 0.102835E+11 | 96161.97 | 19-OCT-15:00 | 96161.97 | 0.00 |
November | 0.00 | 0.00 | 0.149171E+11 | 0.143700E+11 | 106508.67 | 01-NOV-15:00 | 82386.62 | 0.00 |
December | 0.00 | 0.00 | 0.150684E+11 | 0.150225E+11 | 6091.57 | 06-DEC-03:00 | 5615.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158338E+13 | 0.104304E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.529868E+10 | 0.471358E+10 | 2796.40 | 2796.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.697069E+12 | 0.418985E+12 | 472302.78 | 390820.06 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.175496E+10 | 0.175496E+10 | 1865.81 | 20-JAN-16:30 | 1865.81 | 0.00 |
February | 0.00 | 0.00 | 0.746594E+10 | 0.746594E+10 | 4573.10 | 20-FEB-17:00 | 4573.10 | 0.00 |
March | 0.00 | 0.00 | 0.143469E+11 | 0.143469E+11 | 7607.11 | 31-MAR-24:00 | 7607.11 | 0.00 |
April | 0.00 | 0.00 | 0.196626E+11 | 0.196626E+11 | 8937.29 | 16-APR-18:10 | 8937.29 | 0.00 |
May | 0.00 | 0.00 | 0.571594E+10 | 0.567318E+10 | 3840.77 | 31-MAY-24:00 | 3840.77 | 0.00 |
June | 0.00 | 0.00 | 0.108041E+11 | 0.106050E+11 | 5969.65 | 30-JUN-23:35 | 5936.11 | 0.00 |
July | 0.00 | 0.00 | 0.164710E+11 | 0.161967E+11 | 7809.07 | 31-JUL-23:55 | 7809.07 | 0.00 |
August | 0.00 | 0.00 | 0.213478E+11 | 0.210639E+11 | 9051.97 | 13-AUG-18:33 | 9051.97 | 0.00 |
September | 0.00 | 0.00 | 0.535558E+10 | 0.530057E+10 | 3876.65 | 30-SEP-24:00 | 3876.65 | 0.00 |
October | 0.00 | 0.00 | 0.100259E+11 | 0.100201E+11 | 5467.60 | 31-OCT-24:00 | 5467.60 | 0.00 |
November | 0.00 | 0.00 | 0.139676E+11 | 0.139622E+11 | 6395.78 | 12-NOV-16:05 | 6395.78 | 0.00 |
December | 0.00 | 0.00 | 0.184047E+11 | 0.184047E+11 | 7901.90 | 10-DEC-15:58 | 7901.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145323E+12 | 0.144457E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.175496E+10 | 0.175496E+10 | 1865.81 | 1865.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213478E+11 | 0.210639E+11 | 9051.97 | 9051.97 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.834902E+09 | 0.834902E+09 | 13006.37 | 20-JAN-16:30 | 13006.37 | 0.00 |
February | 0.00 | 0.00 | 0.440597E+11 | 0.440597E+11 | 37645.02 | 08-FEB-17:00 | 37645.02 | 0.00 |
March | 0.00 | 0.00 | 0.113666E+12 | 0.113666E+12 | 69025.16 | 31-MAR-23:20 | 69025.16 | 0.00 |
April | 0.00 | 0.00 | 0.175038E+12 | 0.175038E+12 | 83228.53 | 21-APR-18:20 | 83228.53 | 0.00 |
May | 0.00 | 0.00 | 0.502557E+11 | 0.498333E+11 | 34960.47 | 31-MAY-24:00 | 34960.47 | 0.00 |
June | 0.00 | 0.00 | 0.100466E+12 | 0.984900E+11 | 57964.89 | 30-JUN-23:30 | 57596.71 | 0.00 |
July | 0.00 | 0.00 | 0.156012E+12 | 0.153281E+12 | 74330.74 | 31-JUL-23:55 | 74330.74 | 0.00 |
August | 0.00 | 0.00 | 0.201593E+12 | 0.198763E+12 | 85407.64 | 05-AUG-18:40 | 85407.64 | 0.00 |
September | 0.00 | 0.00 | 0.449271E+11 | 0.443887E+11 | 34618.97 | 30-SEP-23:30 | 34618.97 | 0.00 |
October | 0.00 | 0.00 | 0.805533E+11 | 0.804953E+11 | 44353.89 | 22-OCT-16:50 | 44353.89 | 0.00 |
November | 0.00 | 0.00 | 0.106133E+12 | 0.106079E+12 | 55268.12 | 17-NOV-16:10 | 55268.12 | 0.00 |
December | 0.00 | 0.00 | 0.138274E+12 | 0.138274E+12 | 63694.21 | 08-DEC-15:55 | 63694.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121181E+13 | 0.120320E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.834902E+09 | 0.834902E+09 | 13006.37 | 13006.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201593E+12 | 0.198763E+12 | 85407.64 | 85407.64 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 32396296.86 | 32396296.86 | 1084.31 | 20-JAN-16:30 | 1084.31 | 0.00 |
February | 0.00 | 0.00 | 0.286856E+10 | 0.286856E+10 | 3710.81 | 08-FEB-17:00 | 3710.81 | 0.00 |
March | 0.00 | 0.00 | 0.963595E+10 | 0.963595E+10 | 6426.82 | 31-MAR-23:10 | 6426.82 | 0.00 |
April | 0.00 | 0.00 | 0.161345E+11 | 0.161345E+11 | 8310.45 | 21-APR-18:20 | 8310.45 | 0.00 |
May | 0.00 | 0.00 | 0.458318E+10 | 0.454087E+10 | 3255.79 | 14-MAY-18:42 | 3255.79 | 0.00 |
June | 0.00 | 0.00 | 0.985254E+10 | 0.965518E+10 | 5781.71 | 30-JUN-23:30 | 5744.62 | 0.00 |
July | 0.00 | 0.00 | 0.155089E+11 | 0.152361E+11 | 7347.81 | 31-JUL-23:55 | 7347.81 | 0.00 |
August | 0.00 | 0.00 | 0.199997E+11 | 0.197171E+11 | 8649.94 | 05-AUG-18:40 | 8649.94 | 0.00 |
September | 0.00 | 0.00 | 0.384349E+10 | 0.379053E+10 | 3375.35 | 03-SEP-17:42 | 3365.62 | 0.00 |
October | 0.00 | 0.00 | 0.630846E+10 | 0.630278E+10 | 4400.16 | 19-OCT-16:50 | 4346.35 | 0.00 |
November | 0.00 | 0.00 | 0.864745E+10 | 0.864218E+10 | 5372.34 | 17-NOV-16:10 | 5372.34 | 0.00 |
December | 0.00 | 0.00 | 0.122020E+11 | 0.122020E+11 | 6056.14 | 20-DEC-16:00 | 6056.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109617E+12 | 0.108758E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 32396296.86 | 32396296.86 | 1084.31 | 1084.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199997E+11 | 0.197171E+11 | 8649.94 | 8649.94 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 322835.24 | 2367618.07 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 156482.73 | 2009106.97 | 14-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 60000.32 | 1719212.05 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11230.95 | 1494343.54 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 741.98 | 328564.25 | 31-MAY-09:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 71.35 | 159180.68 | 09-JUN-09:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.18 | 41131.57 | 08-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 96.52 | 196317.08 | 17-AUG-13:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 954.15 | 299668.82 | 27-SEP-13:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 9944.57 | 1282095.83 | 14-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 61168.95 | 1749813.65 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 241638.94 | 2123545.47 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 71994.39 | ||||
Minimum of Months | 0.00 | 0.00 | 22.18 | 41131.57 | ||
Maximum of Months | 0.00 | 0.00 | 322835.24 | 2367618.07 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 517.81 | 4876.17 | 27-JAN-13:07 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1089.97 | 39312.35 | 28-FEB-15:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2943.00 | 257471.32 | 31-MAR-15:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33293.86 | 594220.34 | 13-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 152348.41 | 1715167.26 | 25-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 340319.16 | 2035049.65 | 19-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 440268.92 | 4029284.27 | 05-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 321651.85 | 2121480.28 | 31-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 79052.21 | 1595415.88 | 01-SEP-10:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 21418.81 | 795933.83 | 19-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3212.38 | 172969.68 | 17-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 844.44 | 11302.29 | 18-DEC-16:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 117388.05 | 0.00 | ||||
Minimum of Months | 517.81 | 4876.17 | 0.00 | 0.00 | ||
Maximum of Months | 440268.92 | 4029284.27 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.41 | 2951.23 | 27-JAN-13:07 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 285.98 | 38058.61 | 28-FEB-15:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2008.48 | 256201.43 | 31-MAR-15:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 32517.99 | 980084.90 | 23-APR-14:22 | 0.00 | 0.00 | 01-APR-00:10 |
May | 151954.98 | 2136981.07 | 17-MAY-12:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 338373.23 | 3162890.27 | 29-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 439876.98 | 4034582.89 | 05-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 320087.18 | 2540220.97 | 09-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 78431.68 | 1503312.35 | 01-SEP-12:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 20938.98 | 794771.11 | 19-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2533.88 | 170132.89 | 17-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28.25 | 11592.13 | 08-DEC-15:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 116563.00 | 0.00 | ||||
Minimum of Months | 1.41 | 2951.23 | 0.00 | 0.00 | ||
Maximum of Months | 439876.98 | 4034582.89 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7818.00 | 26843.65 | 20-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 37314.49 | 66103.23 | 08-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 73605.01 | 138012.55 | 29-MAR-15:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142959.85 | 1348106.37 | 23-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 103093.13 | 879475.65 | 25-MAY-18:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 312924.20 | 1430456.11 | 29-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 636191.20 | 1687283.61 | 15-JUL-14:10 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 676738.08 | 1671096.91 | 08-AUG-15:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 47589.82 | 690463.22 | 01-SEP-15:10 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 55419.83 | 461195.13 | 19-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 72199.56 | 308832.27 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88271.77 | 104721.73 | 08-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 189562.35 | 0.00 | ||||
Minimum of Months | 7818.00 | 26843.65 | 0.00 | 0.00 | ||
Maximum of Months | 676738.08 | 1687283.61 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 18359.95 | 62731.53 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18851.05 | 63325.53 | 27-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 19869.41 | 63295.47 | 02-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18187.16 | 62021.43 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 17880.39 | 59679.22 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17275.83 | 56260.04 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15245.00 | 52938.35 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16118.07 | 50920.93 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 15272.29 | 51367.81 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 15792.20 | 54008.78 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 16846.97 | 57247.03 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 17181.98 | 60339.81 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 17230.56 | ||||
Minimum of Months | 0.00 | 0.00 | 15245.00 | 50920.93 | ||
Maximum of Months | 0.00 | 0.00 | 19869.41 | 63325.53 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 111.99 | 8818.32 | 11-JAN-18:10 | 6583.59 | 142040.85 | 23-JAN-11:01 |
February | 122.26 | 34388.70 | 28-FEB-15:20 | 11664.06 | 138876.45 | 19-FEB-03:07 |
March | 1407.00 | 315644.99 | 31-MAR-15:50 | 13319.00 | 135319.05 | 04-MAR-15:02 |
April | 35706.61 | 681797.71 | 13-APR-13:00 | 4109.90 | 124813.85 | 04-APR-20:20 |
May | 204361.45 | 2889187.04 | 25-MAY-16:00 | 1081.13 | 115628.82 | 06-MAY-07:20 |
June | 617582.13 | 5449347.49 | 30-JUN-16:00 | 320.22 | 73798.00 | 04-JUN-21:00 |
July | 805826.08 | 6145392.22 | 05-JUL-11:00 | 402.10 | 44437.68 | 09-JUL-13:10 |
August | 546821.57 | 5032845.45 | 31-AUG-12:50 | 888.42 | 59391.80 | 05-AUG-22:00 |
September | 98287.89 | 2486251.38 | 01-SEP-11:00 | 1001.37 | 101480.75 | 27-SEP-07:30 |
October | 24361.44 | 908986.64 | 19-OCT-15:00 | 2446.46 | 125405.09 | 13-OCT-08:50 |
November | 1943.77 | 214998.95 | 17-NOV-13:40 | 7684.45 | 132747.47 | 28-NOV-13:20 |
December | 130.77 | 8927.38 | 02-DEC-12:13 | 11925.92 | 143782.13 | 18-DEC-15:01 |
Annual Sum or Average | 196390.86 | 5085.25 | ||||
Minimum of Months | 111.99 | 8818.32 | 320.22 | 44437.68 | ||
Maximum of Months | 805826.08 | 6145392.22 | 13319.00 | 143782.13 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118402E+11 | 0.75 | 8564.94 | 02-JAN-06:01 | 1.44 |
February | 0.111012E+11 | 0.78 | 8564.94 | 01-FEB-06:01 | 1.46 |
March | 0.133948E+11 | 0.85 | 8564.94 | 01-MAR-05:01 | 1.45 |
April | 0.123283E+11 | 0.81 | 8564.94 | 01-APR-04:02 | 1.45 |
May | 0.132106E+11 | 0.83 | 8564.94 | 01-MAY-03:03 | 1.46 |
June | 0.128774E+11 | 0.83 | 8564.94 | 01-JUN-04:13 | 1.44 |
July | 0.126958E+11 | 0.79 | 8564.94 | 01-JUL-04:12 | 1.44 |
August | 0.140218E+11 | 0.88 | 8564.94 | 01-AUG-04:12 | 1.44 |
September | 0.129437E+11 | 0.84 | 8564.94 | 01-SEP-04:12 | 1.44 |
October | 0.128998E+11 | 0.81 | 8564.94 | 02-OCT-02:30 | 1.44 |
November | 0.120967E+11 | 0.79 | 8564.94 | 01-NOV-04:11 | 1.44 |
December | 0.120795E+11 | 0.77 | 8564.94 | 01-DEC-05:01 | 1.46 |
Annual Sum or Average | 0.151490E+12 | 0.81 | |||
Minimum of Months | 0.111012E+11 | 0.75 | 8564.94 | 1.44 | |
Maximum of Months | 0.140218E+11 | 0.88 | 8564.94 | 1.46 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.255634E+10 | 0.32 | 6251.12 | 19-JAN-06:01 | 0.93 |
February | 0.293454E+10 | 0.34 | 12276.10 | 11-FEB-06:02 | 1.40 |
March | 0.468645E+10 | 0.39 | 12276.10 | 11-MAR-06:01 | 1.40 |
April | 0.743661E+10 | 0.49 | 16033.38 | 17-APR-14:50 | 1.65 |
May | 0.871725E+10 | 0.52 | 20945.61 | 27-MAY-05:02 | 1.94 |
June | 0.113274E+11 | 0.63 | 20945.61 | 19-JUN-04:12 | 1.94 |
July | 0.135224E+11 | 0.72 | 20945.61 | 03-JUL-05:03 | 1.94 |
August | 0.129902E+11 | 0.72 | 20945.61 | 14-AUG-05:02 | 1.94 |
September | 0.683041E+10 | 0.46 | 18555.35 | 05-SEP-15:30 | 1.81 |
October | 0.502793E+10 | 0.39 | 12129.25 | 19-OCT-15:20 | 1.38 |
November | 0.385574E+10 | 0.35 | 9180.51 | 13-NOV-06:01 | 1.17 |
December | 0.290037E+10 | 0.32 | 12276.10 | 29-DEC-06:01 | 1.40 |
Annual Sum or Average | 0.827857E+11 | 0.47 | |||
Minimum of Months | 0.255634E+10 | 0.32 | 6251.12 | 0.93 | |
Maximum of Months | 0.135224E+11 | 0.72 | 20945.61 | 1.94 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349630E+11 | 0.43 | 57951.09 | 10-JAN-06:01 | 0.94 |
February | 0.279955E+11 | 0.39 | 57951.09 | 22-FEB-06:01 | 0.93 |
March | 0.302060E+11 | 0.37 | 67714.17 | 30-MAR-05:03 | 1.02 |
April | 0.377049E+11 | 0.36 | 102766.10 | 13-APR-15:00 | 1.31 |
May | 0.675816E+11 | 0.47 | 176367.52 | 18-MAY-05:02 | 1.83 |
June | 0.859657E+11 | 0.54 | 194161.95 | 27-JUN-05:02 | 1.94 |
July | 0.975468E+11 | 0.56 | 194161.95 | 03-JUL-04:12 | 1.94 |
August | 0.802117E+11 | 0.52 | 173660.67 | 08-AUG-15:20 | 1.80 |
September | 0.487186E+11 | 0.40 | 151361.18 | 01-SEP-16:00 | 1.65 |
October | 0.300649E+11 | 0.33 | 125610.92 | 06-OCT-05:02 | 1.49 |
November | 0.246643E+11 | 0.33 | 57951.09 | 25-NOV-06:01 | 0.94 |
December | 0.324087E+11 | 0.42 | 57951.09 | 12-DEC-05:01 | 0.94 |
Annual Sum or Average | 0.598032E+12 | 0.43 | |||
Minimum of Months | 0.246643E+11 | 0.33 | 57951.09 | 0.93 | |
Maximum of Months | 0.975468E+11 | 0.56 | 194161.95 | 1.94 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.428720E+10 | 0.49 | 5432.29 | 31-JAN-05:03 | 0.85 |
February | 0.353343E+10 | 0.46 | 5432.29 | 03-FEB-06:01 | 0.85 |
March | 0.339130E+10 | 0.41 | 5432.29 | 04-MAR-06:01 | 0.85 |
April | 0.334594E+10 | 0.36 | 9126.05 | 13-APR-15:20 | 1.15 |
May | 0.591233E+10 | 0.42 | 17781.78 | 18-MAY-14:40 | 1.71 |
June | 0.816307E+10 | 0.50 | 21546.54 | 29-JUN-05:02 | 1.93 |
July | 0.927653E+10 | 0.52 | 21546.54 | 05-JUL-10:30 | 1.92 |
August | 0.724475E+10 | 0.47 | 19240.77 | 08-AUG-15:20 | 1.80 |
September | 0.390167E+10 | 0.36 | 16790.11 | 01-SEP-16:00 | 1.65 |
October | 0.274023E+10 | 0.33 | 7009.64 | 20-OCT-15:10 | 0.98 |
November | 0.316108E+10 | 0.41 | 5432.29 | 04-NOV-05:01 | 0.85 |
December | 0.405244E+10 | 0.47 | 5432.29 | 01-DEC-05:11 | 0.85 |
Annual Sum or Average | 0.590100E+11 | 0.43 | |||
Minimum of Months | 0.274023E+10 | 0.33 | 5432.29 | 0.85 | |
Maximum of Months | 0.927653E+10 | 0.52 | 21546.54 | 1.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.978894E+11 | 1.41 | 36547.73 | 01-JAN-00:01 | 1.41 |
February | 0.884163E+11 | 1.41 | 36547.73 | 01-FEB-00:03 | 1.41 |
March | 0.978894E+11 | 1.41 | 36547.73 | 01-MAR-00:10 | 1.41 |
April | 0.947317E+11 | 1.41 | 36547.73 | 01-APR-00:10 | 1.41 |
May | 0.978894E+11 | 1.40 | 36547.73 | 01-MAY-00:10 | 1.41 |
June | 0.947317E+11 | 1.40 | 36547.73 | 01-JUN-00:10 | 1.41 |
July | 0.978894E+11 | 1.39 | 36547.73 | 01-JUL-00:05 | 1.40 |
August | 0.978894E+11 | 1.40 | 36547.73 | 01-AUG-00:05 | 1.39 |
September | 0.947317E+11 | 1.40 | 36547.73 | 01-SEP-00:05 | 1.39 |
October | 0.978894E+11 | 1.41 | 36547.73 | 01-OCT-00:10 | 1.41 |
November | 0.947317E+11 | 1.41 | 36547.73 | 01-NOV-00:10 | 1.41 |
December | 0.978894E+11 | 1.41 | 36547.73 | 01-DEC-00:10 | 1.41 |
Annual Sum or Average | 0.115257E+13 | 1.41 | |||
Minimum of Months | 0.884163E+11 | 1.39 | 36547.73 | 1.39 | |
Maximum of Months | 0.978894E+11 | 1.41 | 36547.73 | 1.41 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152851E+10 | 0.96 | 570.68 | 01-JAN-00:01 | 0.95 |
February | 0.138059E+10 | 0.96 | 570.68 | 01-FEB-00:03 | 0.96 |
March | 0.152851E+10 | 0.96 | 570.68 | 01-MAR-00:10 | 0.96 |
April | 0.147920E+10 | 0.96 | 570.68 | 01-APR-00:10 | 0.96 |
May | 0.152851E+10 | 0.95 | 570.68 | 01-MAY-00:10 | 0.96 |
June | 0.147920E+10 | 0.95 | 570.68 | 01-JUN-00:20 | 0.95 |
July | 0.152851E+10 | 0.95 | 570.68 | 01-JUL-00:05 | 0.95 |
August | 0.152851E+10 | 0.95 | 570.68 | 01-AUG-00:05 | 0.95 |
September | 0.147920E+10 | 0.95 | 570.68 | 01-SEP-00:05 | 0.95 |
October | 0.152851E+10 | 0.96 | 570.68 | 01-OCT-00:10 | 0.95 |
November | 0.147920E+10 | 0.96 | 570.68 | 01-NOV-00:10 | 0.96 |
December | 0.152851E+10 | 0.96 | 570.68 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.179969E+11 | 0.96 | |||
Minimum of Months | 0.138059E+10 | 0.95 | 570.68 | 0.95 | |
Maximum of Months | 0.152851E+10 | 0.96 | 570.68 | 0.96 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146928E+11 | 0.96 | 5485.66 | 01-JAN-00:01 | 0.96 |
February | 0.132709E+11 | 0.96 | 5485.66 | 01-FEB-00:03 | 0.96 |
March | 0.146928E+11 | 0.96 | 5485.66 | 01-MAR-00:10 | 0.96 |
April | 0.142188E+11 | 0.96 | 5485.66 | 01-APR-00:10 | 0.96 |
May | 0.146928E+11 | 0.95 | 5485.66 | 01-MAY-00:10 | 0.96 |
June | 0.142188E+11 | 0.95 | 5485.66 | 01-JUN-00:10 | 0.95 |
July | 0.146928E+11 | 0.95 | 5485.66 | 01-JUL-00:05 | 0.95 |
August | 0.146928E+11 | 0.95 | 5485.66 | 01-AUG-00:05 | 0.95 |
September | 0.142188E+11 | 0.95 | 5485.66 | 01-SEP-00:05 | 0.95 |
October | 0.146928E+11 | 0.96 | 5485.66 | 01-OCT-00:10 | 0.95 |
November | 0.142188E+11 | 0.96 | 5485.66 | 01-NOV-00:10 | 0.96 |
December | 0.146928E+11 | 0.96 | 5485.66 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.172996E+12 | 0.96 | |||
Minimum of Months | 0.132709E+11 | 0.95 | 5485.66 | 0.95 | |
Maximum of Months | 0.146928E+11 | 0.96 | 5485.66 | 0.96 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149050E+10 | 0.96 | 556.49 | 01-JAN-00:01 | 0.96 |
February | 0.134625E+10 | 0.96 | 556.49 | 01-FEB-00:03 | 0.96 |
March | 0.149050E+10 | 0.96 | 556.49 | 01-MAR-00:10 | 0.96 |
April | 0.144242E+10 | 0.96 | 556.49 | 01-APR-00:10 | 0.96 |
May | 0.149050E+10 | 0.95 | 556.49 | 01-MAY-00:10 | 0.96 |
June | 0.144242E+10 | 0.95 | 556.49 | 01-JUN-00:10 | 0.95 |
July | 0.149050E+10 | 0.95 | 556.49 | 01-JUL-00:05 | 0.95 |
August | 0.149050E+10 | 0.95 | 556.49 | 01-AUG-00:05 | 0.95 |
September | 0.144242E+10 | 0.95 | 556.49 | 01-SEP-00:05 | 0.95 |
October | 0.149050E+10 | 0.96 | 556.49 | 01-OCT-00:10 | 0.95 |
November | 0.144242E+10 | 0.96 | 556.49 | 01-NOV-00:10 | 0.96 |
December | 0.149050E+10 | 0.96 | 556.49 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.175494E+11 | 0.96 | |||
Minimum of Months | 0.134625E+10 | 0.95 | 556.49 | 0.95 | |
Maximum of Months | 0.149050E+10 | 0.96 | 556.49 | 0.96 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.274444E+09 | 0.249470E+09 | 2558.59 | 09-JAN-07:08 | 2325.76 | 2325.76 | 50.19 | 17.21 |
February | 76970245.58 | 69965953.23 | 1620.89 | 14-FEB-07:10 | 1473.39 | 1473.39 | 52.13 | 14.18 |
March | 14393774.59 | 13083941.10 | 1019.68 | 06-MAR-06:01 | 926.89 | 926.89 | 47.53 | 11.62 |
April | 1917741.66 | 1743227.17 | 359.80 | 04-APR-05:01 | 327.06 | 327.06 | 44.68 | 7.23 |
May | 73654.04 | 66951.52 | 19.18 | 31-MAY-09:10 | 17.44 | 17.44 | 28.58 | 1.47 |
June | 6825.65 | 6204.51 | 6.58 | 09-JUN-09:40 | 5.98 | 5.98 | 28.01 | 0.71 |
July | 1781.07 | 1619.00 | 1.25 | 08-JUL-11:30 | 1.14 | 1.14 | 27.44 | 0.18 |
August | 9822.68 | 8928.82 | 8.57 | 17-AUG-13:20 | 7.79 | 7.79 | 27.06 | 0.85 |
September | 88365.47 | 80324.21 | 15.56 | 27-SEP-13:10 | 14.14 | 14.14 | 26.23 | 1.29 |
October | 1502745.26 | 1365995.44 | 247.96 | 14-OCT-05:02 | 225.40 | 225.40 | 31.53 | 6.08 |
November | 14832187.50 | 13482458.44 | 1009.44 | 25-NOV-06:01 | 917.58 | 917.58 | 47.24 | 11.57 |
December | 0.144657E+09 | 0.131493E+09 | 1937.08 | 26-DEC-07:07 | 1760.81 | 1760.81 | 48.90 | 15.32 |
Annual Sum or Average | 0.528899E+09 | 0.480769E+09 | ||||||
Minimum of Months | 1781.07 | 1619.00 | 1.25 | 1.14 | 1.14 | 26.23 | 0.18 | |
Maximum of Months | 0.274444E+09 | 0.249470E+09 | 2558.59 | 2325.76 | 2325.76 | 52.13 | 17.21 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 2966.22 | 2696.30 | 1.62 | 27-JAN-13:07 | 1.48 | 1.48 | 6.70 | 0.43 |
February | 79762.44 | 72504.06 | 4.66 | 28-FEB-15:20 | 4.24 | 4.24 | 6.70 | 1.06 |
March | 886253.46 | 805604.39 | 60.09 | 31-MAR-14:10 | 54.62 | 54.62 | 6.70 | 5.97 |
April | 21246810.23 | 19313350.50 | 1315.79 | 23-APR-15:42 | 1196.06 | 1196.06 | 6.71 | 27.69 |
May | 0.332135E+09 | 0.301911E+09 | 5191.81 | 17-MAY-12:40 | 4719.36 | 4719.36 | 10.63 | 49.40 |
June | 0.709715E+09 | 0.645131E+09 | 10733.14 | 19-JUN-05:03 | 9756.42 | 9756.42 | 9.47 | 66.00 |
July | 0.117178E+10 | 0.106515E+10 | 10733.14 | 05-JUL-04:12 | 9756.42 | 9756.42 | 9.47 | 66.00 |
August | 0.701298E+09 | 0.637480E+09 | 10679.63 | 09-AUG-05:03 | 9707.79 | 9707.79 | 9.66 | 65.86 |
September | 0.158987E+09 | 0.144519E+09 | 3543.00 | 07-SEP-14:00 | 3220.58 | 3220.58 | 8.01 | 42.24 |
October | 32841763.23 | 29853162.77 | 1210.96 | 19-OCT-14:05 | 1100.77 | 1100.77 | 6.71 | 26.70 |
November | 1127162.35 | 1024590.58 | 42.22 | 01-NOV-15:00 | 38.37 | 38.37 | 6.70 | 4.85 |
December | 7952.93 | 7229.22 | 1.36 | 08-DEC-15:02 | 1.23 | 1.23 | 6.70 | 0.37 |
Annual Sum or Average | 0.313011E+10 | 0.284527E+10 | ||||||
Minimum of Months | 2966.22 | 2696.30 | 1.36 | 1.23 | 1.23 | 6.70 | 0.37 | |
Maximum of Months | 0.117178E+10 | 0.106515E+10 | 10733.14 | 9756.42 | 9756.42 | 10.63 | 66.00 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.152205E+10 | 0.138354E+10 | 3693.66 | 02-JAN-17:10 | 3357.54 | 3357.54 | 6.72 | 33.00 |
February | 0.213977E+10 | 0.194506E+10 | 3693.66 | 01-FEB-02:62 | 3357.54 | 3357.54 | 6.72 | 33.00 |
March | 0.275590E+10 | 0.250512E+10 | 3693.66 | 01-MAR-07:20 | 3357.54 | 3357.54 | 6.72 | 33.00 |
April | 0.228291E+10 | 0.207517E+10 | 3693.66 | 01-APR-14:00 | 3357.54 | 3357.54 | 6.73 | 33.00 |
May | 0.354994E+10 | 0.322690E+10 | 3693.66 | 01-MAY-07:10 | 3357.54 | 3357.54 | 6.77 | 33.00 |
June | 0.546965E+10 | 0.497192E+10 | 3693.66 | 01-JUN-04:13 | 3357.54 | 3357.54 | 7.93 | 33.00 |
July | 0.701223E+10 | 0.637412E+10 | 3693.66 | 01-JUL-00:15 | 3357.54 | 3357.54 | 6.75 | 33.00 |
August | 0.675319E+10 | 0.613865E+10 | 3693.66 | 01-AUG-00:35 | 3357.54 | 3357.54 | 6.76 | 33.00 |
September | 0.294174E+10 | 0.267405E+10 | 3693.66 | 01-SEP-00:20 | 3357.54 | 3357.54 | 6.91 | 33.00 |
October | 0.147072E+10 | 0.133688E+10 | 3693.66 | 01-OCT-08:53 | 3357.54 | 3357.54 | 6.74 | 33.00 |
November | 0.193625E+10 | 0.176005E+10 | 3693.66 | 01-NOV-04:11 | 3357.54 | 3357.54 | 6.83 | 33.00 |
December | 0.240493E+10 | 0.218608E+10 | 3693.66 | 01-DEC-07:05 | 3357.54 | 3357.54 | 6.72 | 33.00 |
Annual Sum or Average | 0.402393E+11 | 0.365775E+11 | ||||||
Minimum of Months | 0.147072E+10 | 0.133688E+10 | 3693.66 | 3357.54 | 3357.54 | 6.72 | 33.00 | |
Maximum of Months | 0.701223E+10 | 0.637412E+10 | 3693.66 | 3357.54 | 3357.54 | 7.93 | 33.00 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.76 | 0.00 |
May | 0.354592E+09 | 0.322324E+09 | 3693.66 | 16-MAY-13:30 | 3357.54 | 3357.54 | 15.21 | 16.50 |
June | 0.937009E+09 | 0.851741E+09 | 3693.66 | 06-JUN-12:05 | 3357.54 | 3357.54 | 11.37 | 33.00 |
July | 0.143517E+10 | 0.130457E+10 | 3693.66 | 03-JUL-12:05 | 3357.54 | 3357.54 | 11.91 | 33.00 |
August | 0.102056E+10 | 0.927688E+09 | 3693.66 | 04-AUG-15:10 | 3357.54 | 3357.54 | 14.88 | 16.50 |
September | 94188425.36 | 85617278.65 | 3693.66 | 01-SEP-09:05 | 3357.54 | 3357.54 | 11.25 | 33.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.75 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.384152E+10 | 0.349194E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.143517E+10 | 0.130457E+10 | 3693.66 | 3357.54 | 3357.54 | 15.21 | 33.00 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.907815E+10 | 0.825204E+10 | 3389.39 | 01-JAN-00:01 | 3080.96 | 3080.96 | 18.46 | 14.30 |
February | 0.819962E+10 | 0.745345E+10 | 3389.39 | 01-FEB-00:03 | 3080.96 | 3080.96 | 18.79 | 14.30 |
March | 0.907815E+10 | 0.825204E+10 | 3389.39 | 01-MAR-00:10 | 3080.96 | 3080.96 | 19.75 | 14.30 |
April | 0.878530E+10 | 0.798584E+10 | 3389.39 | 01-APR-00:10 | 3080.96 | 3080.96 | 20.57 | 14.30 |
May | 0.907815E+10 | 0.825204E+10 | 3389.39 | 01-MAY-00:10 | 3080.96 | 3080.96 | 18.93 | 14.30 |
June | 0.878530E+10 | 0.798584E+10 | 3389.39 | 01-JUN-00:10 | 3080.96 | 3080.96 | 19.46 | 14.30 |
July | 0.907815E+10 | 0.825204E+10 | 3389.39 | 01-JUL-00:05 | 3080.96 | 3080.96 | 20.65 | 14.30 |
August | 0.907815E+10 | 0.825204E+10 | 3389.39 | 01-AUG-00:05 | 3080.96 | 3080.96 | 29.39 | 14.30 |
September | 0.878530E+10 | 0.798584E+10 | 3389.39 | 01-SEP-00:05 | 3080.96 | 3080.96 | 20.83 | 14.30 |
October | 0.907815E+10 | 0.825204E+10 | 3389.39 | 01-OCT-00:10 | 3080.96 | 3080.96 | 19.46 | 14.30 |
November | 0.878530E+10 | 0.798584E+10 | 3389.39 | 01-NOV-00:10 | 3080.96 | 3080.96 | 19.85 | 14.30 |
December | 0.907815E+10 | 0.825204E+10 | 3389.39 | 01-DEC-00:10 | 3080.96 | 3080.96 | 20.25 | 14.30 |
Annual Sum or Average | 0.106888E+12 | 0.971611E+11 | ||||||
Minimum of Months | 0.819962E+10 | 0.745345E+10 | 3389.39 | 3080.96 | 3080.96 | 18.46 | 14.30 | |
Maximum of Months | 0.907815E+10 | 0.825204E+10 | 3389.39 | 3080.96 | 3080.96 | 29.39 | 14.30 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:01 | 16.86 | 16.86 | 56.15 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 55.14 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 55.00 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 55.82 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.24 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 55.84 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.10 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 55.66 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 55.48 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 55.45 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 56.20 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 55.38 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.00 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.24 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.575705E+10 | 0.523316E+10 | 13978.29 | 11-JAN-18:10 | 12706.27 | 12706.27 | 21.14 | 57.21 |
February | 0.809637E+10 | 0.735960E+10 | 13979.37 | 28-FEB-15:20 | 12707.25 | 12707.25 | 21.24 | 57.21 |
March | 0.104278E+11 | 0.947889E+10 | 13991.20 | 31-MAR-15:50 | 12718.00 | 12718.00 | 22.42 | 57.21 |
April | 0.863847E+10 | 0.785237E+10 | 14006.61 | 13-APR-13:00 | 12732.01 | 12732.01 | 23.95 | 57.21 |
May | 0.147238E+11 | 0.133839E+11 | 28084.85 | 25-MAY-16:00 | 25529.13 | 25529.13 | 27.14 | 114.43 |
June | 0.239847E+11 | 0.218021E+11 | 28124.17 | 19-JUN-14:00 | 25564.87 | 25564.87 | 28.95 | 114.43 |
July | 0.317169E+11 | 0.288306E+11 | 28124.17 | 03-JUL-12:50 | 25564.87 | 25564.87 | 29.53 | 114.43 |
August | 0.292300E+11 | 0.265701E+11 | 28124.17 | 07-AUG-15:30 | 25564.87 | 25564.87 | 29.01 | 114.43 |
September | 0.114912E+11 | 0.104455E+11 | 28065.01 | 01-SEP-11:00 | 25511.09 | 25511.09 | 26.30 | 114.43 |
October | 0.556811E+10 | 0.506141E+10 | 14016.20 | 19-OCT-15:00 | 12740.72 | 12740.72 | 24.90 | 57.21 |
November | 0.732671E+10 | 0.665998E+10 | 13986.96 | 17-NOV-13:40 | 12714.15 | 12714.15 | 22.00 | 57.21 |
December | 0.909965E+10 | 0.827158E+10 | 13978.30 | 02-DEC-12:13 | 12706.27 | 12706.27 | 21.14 | 57.21 |
Annual Sum or Average | 0.166061E+12 | 0.150949E+12 | ||||||
Minimum of Months | 0.556811E+10 | 0.506141E+10 | 13978.29 | 12706.27 | 12706.27 | 21.14 | 57.21 | |
Maximum of Months | 0.317169E+11 | 0.288306E+11 | 28124.17 | 25564.87 | 25564.87 | 29.53 | 114.43 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 45.29 | 45.29 | 322835.24 | 2367618.07 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46.29 | 46.29 | 156482.73 | 2009106.97 | 14-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.36 | 33.36 | 60000.32 | 1719212.05 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.59 | 26.59 | 11230.95 | 1494343.54 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.76 | 26.76 | 741.98 | 328564.25 | 31-MAY-09:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.99 | 28.99 | 71.35 | 159180.68 | 09-JUN-09:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.86 | 27.86 | 22.18 | 41131.57 | 08-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.11 | 27.11 | 96.52 | 196317.08 | 17-AUG-13:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.98 | 26.98 | 954.15 | 299668.82 | 27-SEP-13:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.00 | 26.00 | 9944.57 | 1282095.83 | 14-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.78 | 24.78 | 61168.95 | 1749813.65 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.45 | 28.45 | 241638.94 | 2123545.47 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 71994.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.78 | 24.78 | 22.18 | 41131.57 | ||
Maximum of Months | 0.00 | 0.00 | 46.29 | 46.29 | 322835.24 | 2367618.07 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 517.81 | 4876.17 | 27-JAN-13:07 | 6.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1089.97 | 39312.35 | 28-FEB-15:20 | 6.98 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2943.00 | 257471.32 | 31-MAR-15:50 | 8.56 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33293.86 | 594220.34 | 13-APR-13:00 | 11.00 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 152348.41 | 1715167.26 | 25-MAY-12:05 | 12.91 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 340319.16 | 2035049.65 | 19-JUN-15:20 | 14.07 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 440268.92 | 4029284.27 | 05-JUL-11:00 | 21.30 | 12.83 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 321651.85 | 2121480.28 | 31-AUG-12:50 | 14.38 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 79052.21 | 1595415.88 | 01-SEP-10:05 | 12.47 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 21418.81 | 795933.83 | 19-OCT-15:00 | 12.46 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3212.38 | 172969.68 | 17-NOV-13:30 | 7.95 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 844.44 | 11302.29 | 18-DEC-16:20 | 6.78 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 117388.05 | 0.00 | ||||||
Minimum of Months | 517.81 | 4876.17 | 6.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 440268.92 | 4029284.27 | 21.30 | 12.83 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.41 | 2951.23 | 27-JAN-13:07 | 8.33 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 285.98 | 38058.61 | 28-FEB-15:20 | 15.28 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2008.48 | 256201.43 | 31-MAR-15:40 | 17.67 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 32517.99 | 980084.90 | 23-APR-14:22 | 15.63 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 151954.98 | 2136981.07 | 17-MAY-12:40 | 17.04 | 10.54 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 338373.23 | 3162890.27 | 29-JUN-05:02 | 18.16 | 12.41 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 439876.98 | 4034582.89 | 05-JUL-11:00 | 21.32 | 12.80 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 320087.18 | 2540220.97 | 09-AUG-05:03 | 15.92 | 11.29 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 78431.68 | 1503312.35 | 01-SEP-12:05 | 16.18 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 20938.98 | 794771.11 | 19-OCT-15:00 | 14.04 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2533.88 | 170132.89 | 17-NOV-13:30 | 16.53 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28.25 | 11592.13 | 08-DEC-15:02 | 14.23 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 116563.00 | 0.00 | ||||||
Minimum of Months | 1.41 | 2951.23 | 8.33 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 439876.98 | 4034582.89 | 21.32 | 12.80 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7818.00 | 26843.65 | 20-JAN-16:30 | 18.87 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 37314.49 | 66103.23 | 08-FEB-17:00 | 19.66 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 73605.01 | 138012.55 | 29-MAR-15:10 | 21.11 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142959.85 | 1348106.37 | 23-APR-16:00 | 44.88 | 32.41 | 0.00 | 0.00 | 01-APR-00:10 |
May | 103093.13 | 879475.65 | 25-MAY-18:00 | 35.80 | 31.39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 312924.20 | 1430456.11 | 29-JUN-16:00 | 46.46 | 38.61 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 636191.20 | 1687283.61 | 15-JUL-14:10 | 51.36 | 37.51 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 676738.08 | 1671096.91 | 08-AUG-15:10 | 51.05 | 37.07 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 47589.82 | 690463.22 | 01-SEP-15:10 | 32.09 | 27.96 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 55419.83 | 461195.13 | 19-OCT-15:00 | 27.56 | 23.85 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 72199.56 | 308832.27 | 01-NOV-15:00 | 24.53 | 20.21 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88271.77 | 104721.73 | 08-DEC-16:00 | 20.44 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 189562.35 | 0.00 | ||||||
Minimum of Months | 7818.00 | 26843.65 | 18.87 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 676738.08 | 1687283.61 | 51.36 | 38.61 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.21 | 57.21 | 18359.95 | 62731.53 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 55.62 | 55.62 | 18851.05 | 63325.53 | 27-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.63 | 55.63 | 19869.41 | 63295.47 | 02-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.56 | 56.56 | 18187.16 | 62021.43 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.14 | 57.14 | 17880.39 | 59679.22 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.49 | 56.49 | 17275.83 | 56260.04 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 56.72 | 56.72 | 15245.00 | 52938.35 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.19 | 56.19 | 16118.07 | 50920.93 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.01 | 56.01 | 15272.29 | 51367.81 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.64 | 56.64 | 15792.20 | 54008.78 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.78 | 56.78 | 16846.97 | 57247.03 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 55.87 | 55.87 | 17181.98 | 60339.81 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 17230.56 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.62 | 55.62 | 15245.00 | 50920.93 | ||
Maximum of Months | 0.00 | 0.00 | 57.21 | 57.21 | 19869.41 | 63325.53 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 111.99 | 8818.32 | 11-JAN-18:10 | 21.14 | 20.26 | 6583.59 | 142040.85 | 23-JAN-11:01 |
February | 122.26 | 34388.70 | 28-FEB-15:20 | 21.24 | 20.44 | 11664.06 | 138876.45 | 19-FEB-03:07 |
March | 1407.00 | 315644.99 | 31-MAR-15:50 | 22.42 | 21.10 | 13319.00 | 135319.05 | 04-MAR-15:02 |
April | 35706.61 | 681797.71 | 13-APR-13:00 | 23.95 | 21.10 | 4109.90 | 124813.85 | 04-APR-20:20 |
May | 204361.45 | 2889187.04 | 25-MAY-16:00 | 27.14 | 23.74 | 1081.13 | 115628.82 | 06-MAY-07:20 |
June | 617582.13 | 5449347.49 | 30-JUN-16:00 | 32.49 | 28.37 | 320.22 | 73798.00 | 04-JUN-21:00 |
July | 805826.08 | 6145392.22 | 05-JUL-11:00 | 33.95 | 28.41 | 402.10 | 44437.68 | 09-JUL-13:10 |
August | 546821.57 | 5032845.45 | 31-AUG-12:50 | 31.62 | 26.63 | 888.42 | 59391.80 | 05-AUG-22:00 |
September | 98287.89 | 2486251.38 | 01-SEP-11:00 | 26.30 | 22.77 | 1001.37 | 101480.75 | 27-SEP-07:30 |
October | 24361.44 | 908986.64 | 19-OCT-15:00 | 24.90 | 21.10 | 2446.46 | 125405.09 | 13-OCT-08:50 |
November | 1943.77 | 214998.95 | 17-NOV-13:40 | 22.00 | 21.10 | 7684.45 | 132747.47 | 28-NOV-13:20 |
December | 130.77 | 8927.38 | 02-DEC-12:13 | 21.14 | 20.26 | 11925.92 | 143782.13 | 18-DEC-15:01 |
Annual Sum or Average | 196390.86 | 5085.25 | ||||||
Minimum of Months | 111.99 | 8818.32 | 21.14 | 20.26 | 320.22 | 44437.68 | ||
Maximum of Months | 805826.08 | 6145392.22 | 33.95 | 28.41 | 13319.00 | 143782.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.332276E+11 | 0.00 | 7203143.71 | 0.255634E+10 | 0.00 | 0.00 |
February | 0.103352E+11 | 0.00 | 0.571018E+09 | 0.293454E+10 | 0.00 | 0.00 |
March | 0.174366E+10 | 0.00 | 0.111982E+10 | 0.468645E+10 | 0.00 | 0.00 |
April | 0.309077E+09 | 0.00 | 0.685018E+10 | 0.743661E+10 | 0.00 | 0.00 |
May | 70964519.39 | 0.00 | 0.338152E+11 | 0.871725E+10 | 0.00 | 0.00 |
June | 59893.98 | 0.00 | 0.786817E+11 | 0.113274E+11 | 0.00 | 0.00 |
July | 6.14 | 0.00 | 0.109737E+12 | 0.135224E+11 | 0.00 | 0.00 |
August | 147050.70 | 0.00 | 0.850143E+11 | 0.129902E+11 | 0.00 | 0.00 |
September | 54821785.07 | 0.00 | 0.175228E+11 | 0.683041E+10 | 0.00 | 0.00 |
October | 0.373547E+09 | 0.00 | 0.515813E+10 | 0.502793E+10 | 0.00 | 0.00 |
November | 0.125381E+10 | 0.00 | 0.277345E+10 | 0.385574E+10 | 0.00 | 0.00 |
December | 0.157013E+11 | 0.00 | 21788093.76 | 0.290037E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.630701E+11 | 0.00 | 0.341272E+12 | 0.827857E+11 | 0.00 | 0.00 |
Minimum of Months | 6.14 | 0.00 | 7203143.71 | 0.255634E+10 | 0.00 | 0.00 |
Maximum of Months | 0.332276E+11 | 0.00 | 0.109737E+12 | 0.135224E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.716479E+12 | 0.00 | 11711209.26 | 0.349630E+11 | 0.00 | 0.00 |
February | 0.306250E+12 | 0.00 | 0.206438E+09 | 0.279955E+11 | 0.00 | 0.00 |
March | 0.125443E+12 | 0.00 | 0.406025E+10 | 0.302060E+11 | 0.00 | 0.00 |
April | 0.201095E+11 | 0.00 | 0.725900E+11 | 0.377049E+11 | 0.00 | 0.00 |
May | 0.144987E+10 | 0.00 | 0.309043E+12 | 0.675816E+11 | 0.00 | 0.00 |
June | 0.186363E+09 | 0.00 | 0.665319E+12 | 0.859657E+11 | 0.00 | 0.00 |
July | 65063758.40 | 0.00 | 0.862259E+12 | 0.975468E+11 | 0.00 | 0.00 |
August | 0.253595E+09 | 0.00 | 0.638476E+12 | 0.802117E+11 | 0.00 | 0.00 |
September | 0.193044E+10 | 0.00 | 0.162239E+12 | 0.487186E+11 | 0.00 | 0.00 |
October | 0.172802E+11 | 0.00 | 0.474152E+11 | 0.300649E+11 | 0.00 | 0.00 |
November | 0.122556E+12 | 0.00 | 0.342402E+10 | 0.246643E+11 | 0.00 | 0.00 |
December | 0.536206E+12 | 0.00 | 22881801.89 | 0.324087E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.184821E+13 | 0.00 | 0.276507E+13 | 0.598032E+12 | 0.00 | 0.00 |
Minimum of Months | 65063758.40 | 0.00 | 11711209.26 | 0.246643E+11 | 0.00 | 0.00 |
Maximum of Months | 0.716479E+12 | 0.00 | 0.862259E+12 | 0.975468E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.117278E+12 | 0.00 | 265049.85 | 0.428720E+10 | 0.00 | 0.00 |
February | 0.640386E+11 | 0.00 | 15230552.88 | 0.353343E+10 | 0.00 | 0.00 |
March | 0.343969E+11 | 0.00 | 0.179030E+09 | 0.339130E+10 | 0.00 | 0.00 |
April | 0.884130E+10 | 0.00 | 0.442438E+10 | 0.334594E+10 | 0.00 | 0.00 |
May | 0.461019E+09 | 0.00 | 0.317803E+11 | 0.591233E+10 | 0.00 | 0.00 |
June | 7473967.20 | 0.00 | 0.697829E+11 | 0.816307E+10 | 0.00 | 0.00 |
July | 4.49 | 0.00 | 0.916194E+11 | 0.927653E+10 | 0.00 | 0.00 |
August | 7177710.74 | 0.00 | 0.653099E+11 | 0.724475E+10 | 0.00 | 0.00 |
September | 0.507981E+09 | 0.00 | 0.138756E+11 | 0.390167E+10 | 0.00 | 0.00 |
October | 0.912839E+10 | 0.00 | 0.271757E+10 | 0.274023E+10 | 0.00 | 0.00 |
November | 0.355339E+11 | 0.00 | 0.213783E+09 | 0.316108E+10 | 0.00 | 0.00 |
December | 0.986299E+11 | 0.00 | 84616.64 | 0.405244E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.368830E+12 | 0.00 | 0.279918E+12 | 0.590100E+11 | 0.00 | 0.00 |
Minimum of Months | 4.49 | 0.00 | 84616.64 | 0.274023E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117278E+12 | 0.00 | 0.916194E+11 | 0.927653E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.220991E+10 | 0.00 | 17241436.13 | 0.118402E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 22903698.24 | 0.111012E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 41648361.69 | 0.133948E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.655600E+09 | 0.123283E+11 | 0.00 | 0.00 |
May | 162.97 | 0.00 | 0.160077E+11 | 0.132106E+11 | 0.00 | 0.00 |
June | 126.79 | 0.00 | 0.371949E+11 | 0.128774E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.500980E+11 | 0.126958E+11 | 0.00 | 0.00 |
August | 272.00 | 0.00 | 0.407455E+11 | 0.140218E+11 | 0.00 | 0.00 |
September | 248.27 | 0.00 | 0.751855E+10 | 0.129437E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.947010E+09 | 0.128998E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.130720E+09 | 0.120967E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 52940311.20 | 0.120795E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.220992E+10 | 0.00 | 0.153433E+12 | 0.151490E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 17241436.13 | 0.111012E+11 | 0.00 | 0.00 |
Maximum of Months | 0.220991E+10 | 0.00 | 0.500980E+11 | 0.140218E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.933976E+10 | 0.220002E+12 | 0.00 | 44.10 |
February | 0.00 | 0.00 | 0.151806E+11 | 0.297857E+12 | 0.00 | 76.19 |
March | 0.00 | 0.00 | 0.204945E+11 | 0.371526E+12 | 0.00 | 99.53 |
April | 0.00 | 0.00 | 0.749176E+11 | 0.364757E+12 | 0.00 | 93.79 |
May | 0.00 | 0.00 | 0.372654E+11 | 0.207032E+12 | 0.00 | 36.85 |
June | 0.00 | 0.00 | 0.224770E+12 | 0.187483E+12 | 0.00 | 16.17 |
July | 0.00 | 0.00 | 0.688924E+12 | 0.237526E+12 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.865248E+12 | 0.267668E+12 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.897809E+10 | 0.138105E+12 | 0.00 | 14.77 |
October | 0.00 | 0.00 | 0.154507E+11 | 0.268578E+12 | 0.00 | 61.68 |
November | 0.00 | 0.00 | 0.210067E+11 | 0.342316E+12 | 0.00 | 89.84 |
December | 0.00 | 0.00 | 0.216383E+11 | 0.372299E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.200321E+13 | 0.327515E+13 | 0.00 | 633.42 |
Minimum of Months | 0.00 | 0.00 | 0.897809E+10 | 0.138105E+12 | 0.00 | 0.27 |
Maximum of Months | 0.00 | 0.00 | 0.865248E+12 | 0.372299E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.222214E+10 | 0.199568E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.921343E+10 | 0.312808E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.174623E+11 | 0.464388E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.237117E+11 | 0.552824E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.703758E+10 | 0.285015E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132748E+11 | 0.394992E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203231E+11 | 0.538060E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260296E+11 | 0.621031E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.653730E+10 | 0.266092E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.121535E+11 | 0.365615E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.169577E+11 | 0.446927E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223499E+11 | 0.547372E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177273E+12 | 0.499469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.222214E+10 | 0.199568E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260296E+11 | 0.621031E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.108215E+10 | 0.149400E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.547802E+11 | 0.239914E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.138859E+12 | 0.398854E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.211484E+12 | 0.506649E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.619821E+11 | 0.264191E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123559E+12 | 0.373115E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192588E+12 | 0.512690E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.245938E+12 | 0.590376E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.549597E+11 | 0.242514E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.979312E+11 | 0.320707E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.129408E+12 | 0.374937E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.168849E+12 | 0.452679E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148142E+13 | 0.442603E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.108215E+10 | 0.149400E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.245938E+12 | 0.590376E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 41574956.36 | 0.149968E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.358197E+10 | 0.205967E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.118054E+11 | 0.365997E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.195349E+11 | 0.484282E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.566238E+10 | 0.256969E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.121303E+11 | 0.372019E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191600E+11 | 0.514160E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.244170E+11 | 0.590773E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.471263E+10 | 0.231156E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.769419E+10 | 0.287622E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.105787E+11 | 0.337372E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.149384E+11 | 0.422687E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134257E+12 | 0.421897E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 41574956.36 | 0.149968E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.244170E+11 | 0.590773E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.255634E+10 | 7203143.71 | 0.332276E+11 | 0.547006E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293454E+10 | 0.571018E+09 | 0.103352E+11 | 0.458671E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468645E+10 | 0.111982E+10 | 0.174366E+10 | 0.376297E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.743661E+10 | 0.685018E+10 | 0.309077E+09 | 0.736924E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.871725E+10 | 0.338152E+11 | 70964519.39 | 0.925725E+09 | 0.155558E+09 | 0.00 | 0.00 | 0.00 |
June | 0.113274E+11 | 0.786817E+11 | 59893.98 | 43623196.11 | 0.350062E+10 | 0.00 | 0.00 | 0.00 |
July | 0.135224E+11 | 0.109737E+12 | 6.14 | 68648322.54 | 0.426038E+10 | 0.00 | 0.00 | 0.00 |
August | 0.129902E+11 | 0.850143E+11 | 147050.70 | 6752574.46 | 0.212689E+10 | 0.00 | 0.00 | 0.00 |
September | 0.683041E+10 | 0.175228E+11 | 54821785.07 | 0.579050E+09 | 31203525.33 | 0.00 | 0.00 | 0.00 |
October | 0.502793E+10 | 0.515813E+10 | 0.373547E+09 | 0.661208E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385574E+10 | 0.277345E+10 | 0.125381E+10 | 0.227508E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290037E+10 | 21788093.76 | 0.157013E+11 | 0.572922E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.827857E+11 | 0.341272E+12 | 0.630701E+11 | 0.233845E+12 | 0.100746E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.255634E+10 | 7203143.71 | 6.14 | 6752574.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135224E+11 | 0.109737E+12 | 0.332276E+11 | 0.572922E+11 | 0.426038E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.349630E+11 | 11711209.26 | 0.716479E+12 | 0.527237E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279955E+11 | 0.206438E+09 | 0.306250E+12 | 0.471851E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302060E+11 | 0.406025E+10 | 0.125443E+12 | 0.455374E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377049E+11 | 0.725900E+11 | 0.201095E+11 | 0.143777E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675816E+11 | 0.309043E+12 | 0.144987E+10 | 0.156200E+11 | 0.182467E+10 | 0.00 | 0.00 | 0.00 |
June | 0.859657E+11 | 0.665319E+12 | 0.186363E+09 | 0.590345E+09 | 0.364865E+11 | 0.00 | 0.00 | 0.00 |
July | 0.975468E+11 | 0.862259E+12 | 65063758.40 | 0.106178E+10 | 0.437635E+11 | 0.00 | 0.00 | 0.00 |
August | 0.802117E+11 | 0.638476E+12 | 0.253595E+09 | 0.543739E+09 | 0.213472E+11 | 0.00 | 0.00 | 0.00 |
September | 0.487186E+11 | 0.162239E+12 | 0.193044E+10 | 0.126591E+11 | 0.412197E+09 | 0.00 | 0.00 | 0.00 |
October | 0.300649E+11 | 0.474152E+11 | 0.172802E+11 | 0.122759E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246643E+11 | 0.342402E+10 | 0.122556E+12 | 0.305851E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324087E+11 | 22881801.89 | 0.536206E+12 | 0.542850E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598032E+12 | 0.276507E+13 | 0.184821E+13 | 0.260017E+13 | 0.103834E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246643E+11 | 11711209.26 | 65063758.40 | 0.543739E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.975468E+11 | 0.862259E+12 | 0.716479E+12 | 0.542850E+12 | 0.437635E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.428720E+10 | 265049.85 | 0.117278E+12 | 0.527088E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353343E+10 | 15230552.88 | 0.640386E+11 | 0.464206E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339130E+10 | 0.179030E+09 | 0.343969E+11 | 0.467832E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334594E+10 | 0.442438E+10 | 0.884130E+10 | 0.167080E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.591233E+10 | 0.317803E+11 | 0.461019E+09 | 0.223826E+10 | 0.129749E+09 | 0.00 | 0.00 | 0.00 |
June | 0.816307E+10 | 0.697829E+11 | 7473967.20 | 51814989.09 | 0.323928E+10 | 0.00 | 0.00 | 0.00 |
July | 0.927653E+10 | 0.916194E+11 | 4.49 | 68106789.67 | 0.369256E+10 | 0.00 | 0.00 | 0.00 |
August | 0.724475E+10 | 0.653099E+11 | 7177710.74 | 68249290.38 | 0.163692E+10 | 0.00 | 0.00 | 0.00 |
September | 0.390167E+10 | 0.138756E+11 | 0.507981E+09 | 0.220183E+10 | 14476635.39 | 0.00 | 0.00 | 0.00 |
October | 0.274023E+10 | 0.271757E+10 | 0.912839E+10 | 0.153875E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316108E+10 | 0.213783E+09 | 0.355339E+11 | 0.323799E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405244E+10 | 84616.64 | 0.986299E+11 | 0.536643E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.590100E+11 | 0.279918E+12 | 0.368830E+12 | 0.268681E+12 | 0.871298E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274023E+10 | 84616.64 | 4.49 | 51814989.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.927653E+10 | 0.916194E+11 | 0.117278E+12 | 0.536643E+11 | 0.369256E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.118402E+11 | 17241436.13 | 0.220991E+10 | 0.319611E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111012E+11 | 22903698.24 | 0.00 | 0.194017E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133948E+11 | 41648361.69 | 0.00 | 0.102599E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123283E+11 | 0.655600E+09 | 0.00 | 0.838796E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132106E+11 | 0.160077E+11 | 162.97 | 0.518020E+09 | 37231242.84 | 0.00 | 0.00 | 0.00 |
June | 0.128774E+11 | 0.371949E+11 | 126.79 | 0.149844E+09 | 0.194843E+10 | 0.00 | 0.00 | 0.00 |
July | 0.126958E+11 | 0.500980E+11 | 0.00 | 0.232550E+09 | 0.216775E+10 | 0.00 | 0.00 | 0.00 |
August | 0.140218E+11 | 0.407455E+11 | 272.00 | 0.141970E+09 | 0.116550E+10 | 0.00 | 0.00 | 0.00 |
September | 0.129437E+11 | 0.751855E+10 | 248.27 | 0.193488E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128998E+11 | 0.947010E+09 | 0.00 | 0.264747E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120967E+11 | 0.130720E+09 | 0.00 | 0.307946E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120795E+11 | 52940311.20 | 0.00 | 0.216193E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151490E+12 | 0.153433E+12 | 0.220992E+10 | 0.886609E+11 | 0.531891E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111012E+11 | 17241436.13 | 0.00 | 0.141970E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140218E+11 | 0.500980E+11 | 0.220991E+10 | 0.319611E+11 | 0.216775E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.978894E+11 | 0.577875E+10 | 0.00 | 0.00 | 0.00 | 0.118020E+12 | 0.00 | 0.00 |
February | 0.884163E+11 | 0.105608E+11 | 0.00 | 0.00 | 0.00 | 0.203903E+12 | 0.00 | 0.00 |
March | 0.978894E+11 | 0.144194E+11 | 0.00 | 0.00 | 0.00 | 0.266363E+12 | 0.00 | 0.00 |
April | 0.947317E+11 | 0.570164E+11 | 0.00 | 0.00 | 0.00 | 0.250994E+12 | 0.00 | 0.00 |
May | 0.978894E+11 | 0.271925E+11 | 0.00 | 0.00 | 0.00 | 0.986258E+11 | 0.00 | 0.00 |
June | 0.947317E+11 | 0.175492E+12 | 0.00 | 0.00 | 0.00 | 0.432780E+11 | 0.00 | 0.00 |
July | 0.978894E+11 | 0.550004E+12 | 0.00 | 0.00 | 0.00 | 0.712511E+09 | 0.00 | 0.00 |
August | 0.978894E+11 | 0.697069E+12 | 0.00 | 0.00 | 0.00 | 0.159202E+10 | 0.00 | 0.00 |
September | 0.947317E+11 | 0.529868E+10 | 0.00 | 0.00 | 0.00 | 0.395159E+11 | 0.00 | 0.00 |
October | 0.978894E+11 | 0.105685E+11 | 0.00 | 0.00 | 0.00 | 0.165064E+12 | 0.00 | 0.00 |
November | 0.947317E+11 | 0.149171E+11 | 0.00 | 0.00 | 0.00 | 0.240413E+12 | 0.00 | 0.00 |
December | 0.978894E+11 | 0.150684E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.115257E+13 | 0.158338E+13 | 0.00 | 0.00 | 0.00 | 0.169512E+13 | 0.00 | 0.00 |
Minimum of Months | 0.884163E+11 | 0.529868E+10 | 0.00 | 0.00 | 0.00 | 0.712511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.978894E+11 | 0.697069E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152851E+10 | 0.175496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138059E+10 | 0.746594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152851E+10 | 0.143469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147920E+10 | 0.196626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152851E+10 | 0.571594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147920E+10 | 0.108041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152851E+10 | 0.164710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152851E+10 | 0.213478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147920E+10 | 0.535558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152851E+10 | 0.100259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147920E+10 | 0.139676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152851E+10 | 0.184047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179969E+11 | 0.145323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138059E+10 | 0.175496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152851E+10 | 0.213478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146928E+11 | 0.834902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132709E+11 | 0.440597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146928E+11 | 0.113666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142188E+11 | 0.175038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146928E+11 | 0.502557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142188E+11 | 0.100466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146928E+11 | 0.156012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146928E+11 | 0.201593E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142188E+11 | 0.449271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146928E+11 | 0.805533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142188E+11 | 0.106133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146928E+11 | 0.138274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172996E+12 | 0.121181E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132709E+11 | 0.834902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146928E+11 | 0.201593E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149050E+10 | 32396296.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134625E+10 | 0.286856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149050E+10 | 0.963595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144242E+10 | 0.161345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149050E+10 | 0.458318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144242E+10 | 0.985254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149050E+10 | 0.155089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149050E+10 | 0.199997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144242E+10 | 0.384349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149050E+10 | 0.630846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144242E+10 | 0.864745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149050E+10 | 0.122020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175494E+11 | 0.109617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134625E+10 | 32396296.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149050E+10 | 0.199997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.255634E+10 | 0.332276E+11 | 7203143.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293454E+10 | 0.103352E+11 | 0.571018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468645E+10 | 0.174366E+10 | 0.111982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.743661E+10 | 0.309077E+09 | 0.685018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.871725E+10 | 70964519.39 | 0.338152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113274E+11 | 59893.98 | 0.786817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135224E+11 | 6.14 | 0.109737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129902E+11 | 147050.70 | 0.850143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.683041E+10 | 54821785.07 | 0.175228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.502793E+10 | 0.373547E+09 | 0.515813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385574E+10 | 0.125381E+10 | 0.277345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290037E+10 | 0.157013E+11 | 21788093.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.827857E+11 | 0.630701E+11 | 0.341272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.255634E+10 | 6.14 | 7203143.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135224E+11 | 0.332276E+11 | 0.109737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.349630E+11 | 0.716479E+12 | 11711209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279955E+11 | 0.306250E+12 | 0.206438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302060E+11 | 0.125443E+12 | 0.406025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377049E+11 | 0.201095E+11 | 0.725900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675816E+11 | 0.144987E+10 | 0.309043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.859657E+11 | 0.186363E+09 | 0.665319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.975468E+11 | 65063758.40 | 0.862259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802117E+11 | 0.253595E+09 | 0.638476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.487186E+11 | 0.193044E+10 | 0.162239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300649E+11 | 0.172802E+11 | 0.474152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246643E+11 | 0.122556E+12 | 0.342402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324087E+11 | 0.536206E+12 | 22881801.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598032E+12 | 0.184821E+13 | 0.276507E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246643E+11 | 65063758.40 | 11711209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.975468E+11 | 0.716479E+12 | 0.862259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.428720E+10 | 0.117278E+12 | 265049.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353343E+10 | 0.640386E+11 | 15230552.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339130E+10 | 0.343969E+11 | 0.179030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334594E+10 | 0.884130E+10 | 0.442438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.591233E+10 | 0.461019E+09 | 0.317803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.816307E+10 | 7473967.20 | 0.697829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.927653E+10 | 4.49 | 0.916194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724475E+10 | 7177710.74 | 0.653099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.390167E+10 | 0.507981E+09 | 0.138756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274023E+10 | 0.912839E+10 | 0.271757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316108E+10 | 0.355339E+11 | 0.213783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405244E+10 | 0.986299E+11 | 84616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.590100E+11 | 0.368830E+12 | 0.279918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274023E+10 | 4.49 | 84616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.927653E+10 | 0.117278E+12 | 0.916194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.118402E+11 | 0.220991E+10 | 17241436.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111012E+11 | 0.00 | 22903698.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133948E+11 | 0.00 | 41648361.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123283E+11 | 0.00 | 0.655600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132106E+11 | 162.97 | 0.160077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128774E+11 | 126.79 | 0.371949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126958E+11 | 0.00 | 0.500980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140218E+11 | 272.00 | 0.407455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129437E+11 | 248.27 | 0.751855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128998E+11 | 0.00 | 0.947010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120967E+11 | 0.00 | 0.130720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120795E+11 | 0.00 | 52940311.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151490E+12 | 0.220992E+10 | 0.153433E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111012E+11 | 0.00 | 17241436.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140218E+11 | 0.220991E+10 | 0.500980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.978894E+11 | 0.00 | 0.933976E+10 | 0.00 | 0.356101E+10 | 0.00 | 0.00 | 0.00 | 0.118551E+12 | 0.00 | 0.00 | 0.00 |
February | 0.884163E+11 | 0.00 | 0.151806E+11 | 0.00 | 0.461979E+10 | 0.00 | 0.00 | 0.00 | 0.204821E+12 | 0.00 | 0.00 | 0.00 |
March | 0.978894E+11 | 0.00 | 0.204945E+11 | 0.00 | 0.607514E+10 | 0.00 | 0.00 | 0.00 | 0.267562E+12 | 0.00 | 0.00 | 0.00 |
April | 0.947317E+11 | 0.00 | 0.749176E+11 | 0.00 | 0.179012E+11 | 0.00 | 0.00 | 0.00 | 0.252124E+12 | 0.00 | 0.00 | 0.00 |
May | 0.978894E+11 | 0.00 | 0.372654E+11 | 0.00 | 0.100729E+11 | 0.00 | 0.00 | 0.00 | 0.990697E+11 | 0.00 | 0.00 | 0.00 |
June | 0.947317E+11 | 0.00 | 0.224770E+12 | 0.00 | 0.492781E+11 | 0.00 | 0.00 | 0.00 | 0.434728E+11 | 0.00 | 0.00 | 0.00 |
July | 0.978894E+11 | 0.00 | 0.688924E+12 | 0.00 | 0.138921E+12 | 0.00 | 0.00 | 0.00 | 0.715718E+09 | 0.00 | 0.00 | 0.00 |
August | 0.978894E+11 | 0.00 | 0.865248E+12 | 0.00 | 0.168179E+12 | 0.00 | 0.00 | 0.00 | 0.159919E+10 | 0.00 | 0.00 | 0.00 |
September | 0.947317E+11 | 0.00 | 0.897809E+10 | 0.00 | 0.367941E+10 | 0.00 | 0.00 | 0.00 | 0.396938E+11 | 0.00 | 0.00 | 0.00 |
October | 0.978894E+11 | 0.00 | 0.154507E+11 | 0.00 | 0.488219E+10 | 0.00 | 0.00 | 0.00 | 0.165807E+12 | 0.00 | 0.00 | 0.00 |
November | 0.947317E+11 | 0.00 | 0.210067E+11 | 0.00 | 0.608960E+10 | 0.00 | 0.00 | 0.00 | 0.241495E+12 | 0.00 | 0.00 | 0.00 |
December | 0.978894E+11 | 0.00 | 0.216383E+11 | 0.00 | 0.656994E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115257E+13 | 0.00 | 0.200321E+13 | 0.00 | 0.419830E+12 | 0.00 | 0.00 | 0.00 | 0.170275E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.884163E+11 | 0.00 | 0.897809E+10 | 0.00 | 0.356101E+10 | 0.00 | 0.00 | 0.00 | 0.715718E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.978894E+11 | 0.00 | 0.865248E+12 | 0.00 | 0.168179E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152851E+10 | 0.00 | 0.222214E+10 | 0.00 | 0.467175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138059E+10 | 0.00 | 0.921343E+10 | 0.00 | 0.174750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152851E+10 | 0.00 | 0.174623E+11 | 0.00 | 0.311537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147920E+10 | 0.00 | 0.237117E+11 | 0.00 | 0.404904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152851E+10 | 0.00 | 0.703758E+10 | 0.00 | 0.132164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147920E+10 | 0.00 | 0.132748E+11 | 0.00 | 0.247072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152851E+10 | 0.00 | 0.203231E+11 | 0.00 | 0.385210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152851E+10 | 0.00 | 0.260296E+11 | 0.00 | 0.468180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147920E+10 | 0.00 | 0.653730E+10 | 0.00 | 0.118172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152851E+10 | 0.00 | 0.121535E+11 | 0.00 | 0.212765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147920E+10 | 0.00 | 0.169577E+11 | 0.00 | 0.299007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152851E+10 | 0.00 | 0.223499E+11 | 0.00 | 0.394522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179969E+11 | 0.00 | 0.177273E+12 | 0.00 | 0.319500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138059E+10 | 0.00 | 0.222214E+10 | 0.00 | 0.467175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152851E+10 | 0.00 | 0.260296E+11 | 0.00 | 0.468180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146928E+11 | 0.00 | 0.108215E+10 | 0.00 | 0.247248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132709E+11 | 0.00 | 0.547802E+11 | 0.00 | 0.107205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146928E+11 | 0.00 | 0.138859E+12 | 0.00 | 0.251926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142188E+11 | 0.00 | 0.211484E+12 | 0.00 | 0.364461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146928E+11 | 0.00 | 0.619821E+11 | 0.00 | 0.117263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142188E+11 | 0.00 | 0.123559E+12 | 0.00 | 0.230926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146928E+11 | 0.00 | 0.192588E+12 | 0.00 | 0.365762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146928E+11 | 0.00 | 0.245938E+12 | 0.00 | 0.443448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142188E+11 | 0.00 | 0.549597E+11 | 0.00 | 0.100326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146928E+11 | 0.00 | 0.979312E+11 | 0.00 | 0.173779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142188E+11 | 0.00 | 0.129408E+12 | 0.00 | 0.232748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146928E+11 | 0.00 | 0.168849E+12 | 0.00 | 0.305751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172996E+12 | 0.00 | 0.148142E+13 | 0.00 | 0.269607E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132709E+11 | 0.00 | 0.108215E+10 | 0.00 | 0.247248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146928E+11 | 0.00 | 0.245938E+12 | 0.00 | 0.443448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149050E+10 | 0.00 | 41574956.36 | 0.00 | 9178659.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134625E+10 | 0.00 | 0.358197E+10 | 0.00 | 0.713411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149050E+10 | 0.00 | 0.118054E+11 | 0.00 | 0.216947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144242E+10 | 0.00 | 0.195349E+11 | 0.00 | 0.340040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149050E+10 | 0.00 | 0.566238E+10 | 0.00 | 0.107920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144242E+10 | 0.00 | 0.121303E+11 | 0.00 | 0.227778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149050E+10 | 0.00 | 0.191600E+11 | 0.00 | 0.365111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149050E+10 | 0.00 | 0.244170E+11 | 0.00 | 0.441723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144242E+10 | 0.00 | 0.471263E+10 | 0.00 | 0.869140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149050E+10 | 0.00 | 0.769419E+10 | 0.00 | 0.138573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144242E+10 | 0.00 | 0.105787E+11 | 0.00 | 0.193130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149050E+10 | 0.00 | 0.149384E+11 | 0.00 | 0.273638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175494E+11 | 0.00 | 0.134257E+12 | 0.00 | 0.246403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134625E+10 | 0.00 | 41574956.36 | 0.00 | 9178659.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149050E+10 | 0.00 | 0.244170E+11 | 0.00 | 0.441723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214148E+11 | 0.00 | 0.00 | 50683220.42 | 0.00 | 0.00 | 0.304600E+11 | 0.00 | 0.32 |
February | 0.605074E+10 | 0.00 | 0.00 | 77988430.49 | 0.00 | 0.00 | 0.432418E+11 | 0.00 | 0.35 |
March | 0.316480E+09 | 0.00 | 0.00 | 0.110462E+09 | 0.00 | 0.00 | 0.614251E+11 | 0.00 | 0.40 |
April | 0.158243E+09 | 0.00 | 0.00 | 0.104998E+09 | 0.00 | 0.00 | 0.615999E+11 | 0.00 | 0.64 |
May | 0.129831E+09 | 2325550.04 | 0.00 | 0.105519E+09 | 0.00 | 0.00 | 0.519278E+11 | 0.00 | 0.98 |
June | 50152771.47 | 0.265812E+10 | 0.00 | 85128233.06 | 28203510.42 | 0.00 | 0.354120E+11 | 0.00 | 1.19 |
July | 0.121310E+09 | 0.432768E+10 | 0.00 | 81652780.15 | 90189861.44 | 0.00 | 0.257958E+11 | 0.00 | 1.04 |
August | 0.162167E+09 | 0.264740E+10 | 0.00 | 0.102736E+09 | 2068773.84 | 0.00 | 0.410601E+11 | 0.00 | 1.30 |
September | 0.158541E+09 | 0.00 | 0.00 | 0.113413E+09 | 0.00 | 0.00 | 0.617021E+11 | 0.00 | 1.04 |
October | 0.186679E+09 | 0.00 | 0.00 | 0.112065E+09 | 0.00 | 0.00 | 0.676938E+11 | 0.00 | 0.67 |
November | 0.157329E+09 | 0.00 | 0.00 | 0.109651E+09 | 0.00 | 0.00 | 0.618302E+11 | 0.00 | 0.48 |
December | 0.960893E+10 | 0.00 | 0.00 | 97710181.93 | 0.00 | 0.00 | 0.468728E+11 | 0.00 | 0.33 |
Annual Sum or Average | 0.385152E+11 | 0.963552E+10 | 0.00 | 0.115201E+10 | 0.120462E+09 | 0.00 | 0.589021E+12 | 0.00 | 0.73 |
Minimum of Months | 50152771.47 | 0.00 | 0.00 | 50683220.42 | 0.00 | 0.00 | 0.257958E+11 | 0.00 | 0.32 |
Maximum of Months | 0.214148E+11 | 0.432768E+10 | 0.00 | 0.113413E+09 | 90189861.44 | 0.00 | 0.676938E+11 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.257941E+11 | 0.00 | 0.00 | 21982843.05 | 0.00 | 0.00 | 0.147343E+11 | 0.00 | 0.30 |
February | 0.960942E+10 | 0.00 | 0.00 | 43385303.23 | 0.00 | 0.00 | 0.256269E+11 | 0.00 | 0.33 |
March | 0.281738E+10 | 0.00 | 0.00 | 79520667.31 | 0.00 | 0.00 | 0.432741E+11 | 0.00 | 0.39 |
April | 0.351321E+10 | 0.00 | 0.00 | 92174787.18 | 21345647.32 | 0.00 | 0.491063E+11 | 0.00 | 0.56 |
May | 0.381095E+10 | 72833968.61 | 0.00 | 85270176.68 | 0.00 | 0.00 | 0.385932E+11 | 0.00 | 0.72 |
June | 0.268395E+10 | 0.346483E+10 | 0.00 | 74069952.85 | 0.462055E+09 | 0.00 | 0.264257E+11 | 0.00 | 0.91 |
July | 0.592416E+10 | 0.537072E+10 | 0.00 | 59251532.21 | 0.193606E+10 | 0.00 | 0.180348E+11 | 0.00 | 0.92 |
August | 0.988844E+10 | 0.342993E+10 | 0.00 | 74442595.84 | 63318921.02 | 0.00 | 0.289033E+11 | 0.00 | 1.10 |
September | 0.320806E+10 | 71209221.46 | 0.00 | 80382464.09 | 0.00 | 0.00 | 0.432628E+11 | 0.00 | 0.73 |
October | 0.268377E+10 | 0.00 | 0.00 | 78579146.14 | 0.00 | 0.00 | 0.463074E+11 | 0.00 | 0.49 |
November | 0.181354E+10 | 0.00 | 0.00 | 70658181.35 | 0.00 | 0.00 | 0.397200E+11 | 0.00 | 0.39 |
December | 0.774366E+10 | 0.00 | 0.00 | 58171038.10 | 0.00 | 0.00 | 0.333767E+11 | 0.00 | 0.34 |
Annual Sum or Average | 0.794906E+11 | 0.124095E+11 | 0.00 | 0.817889E+09 | 0.248278E+10 | 0.00 | 0.407365E+12 | 0.00 | 0.60 |
Minimum of Months | 0.181354E+10 | 0.00 | 0.00 | 21982843.05 | 0.00 | 0.00 | 0.147343E+11 | 0.00 | 0.30 |
Maximum of Months | 0.257941E+11 | 0.537072E+10 | 0.00 | 92174787.18 | 0.193606E+10 | 0.00 | 0.491063E+11 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212033E+11 | 0.00 | 0.00 | 0.29 |
February | 0.253479E+12 | 0.00 | 0.00 | 3037750.44 | 0.00 | 0.428682E+10 | 0.543594E+10 | 0.00 | 0.29 |
March | 0.210673E+12 | 0.00 | 0.00 | 87767434.61 | 0.00 | 0.756347E+09 | 0.699306E+11 | 0.00 | 0.32 |
April | 0.949165E+11 | 0.00 | 0.00 | 0.313279E+09 | 0.767804E+09 | 0.00 | 0.199374E+12 | 0.00 | 0.36 |
May | 0.350713E+11 | 0.715953E+09 | 0.00 | 0.625129E+09 | 0.00 | 0.00 | 0.288261E+12 | 0.00 | 0.58 |
June | 0.163936E+11 | 0.279263E+11 | 0.00 | 0.550345E+09 | 0.351090E+10 | 0.00 | 0.200716E+12 | 0.00 | 0.70 |
July | 0.187703E+11 | 0.424492E+11 | 0.00 | 0.458086E+09 | 0.685517E+10 | 0.00 | 0.139889E+12 | 0.00 | 0.64 |
August | 0.236788E+11 | 0.222635E+11 | 0.00 | 0.543410E+09 | 0.316302E+09 | 0.00 | 0.213992E+12 | 0.00 | 0.73 |
September | 0.402235E+11 | 0.625605E+09 | 0.00 | 0.532471E+09 | 0.00 | 0.00 | 0.308961E+12 | 0.00 | 0.56 |
October | 0.107032E+12 | 0.00 | 0.00 | 0.289076E+09 | 0.00 | 0.00 | 0.202758E+12 | 0.00 | 0.35 |
November | 0.173721E+12 | 0.00 | 0.00 | 68243898.92 | 0.00 | 0.109170E+10 | 0.650083E+11 | 0.00 | 0.30 |
December | 0.286515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147377E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.160429E+13 | 0.939806E+11 | 0.00 | 0.347084E+10 | 0.114502E+11 | 0.420759E+11 | 0.169432E+13 | 0.00 | 0.45 |
Minimum of Months | 0.163936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.343819E+12 | 0.424492E+11 | 0.00 | 0.625129E+09 | 0.685517E+10 | 0.212033E+11 | 0.308961E+12 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143860E+11 | 0.00 | 0.00 | 0.26 |
February | 0.145417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663733E+10 | 0.00 | 0.00 | 0.27 |
March | 0.191889E+11 | 0.00 | 0.00 | 669979.22 | 0.00 | 0.222717E+10 | 0.828286E+09 | 0.00 | 0.30 |
April | 0.142671E+11 | 0.00 | 0.00 | 11929949.12 | 89680214.16 | 0.356920E+09 | 0.920270E+10 | 0.00 | 0.34 |
May | 0.714378E+10 | 68322990.00 | 0.00 | 46352147.40 | 0.00 | 1249629.71 | 0.209973E+11 | 0.00 | 0.55 |
June | 0.289278E+10 | 0.275387E+10 | 0.00 | 46466547.84 | 0.445971E+09 | 0.00 | 0.174889E+11 | 0.00 | 0.70 |
July | 0.241977E+10 | 0.434721E+10 | 0.00 | 39330490.89 | 0.848722E+09 | 0.00 | 0.121107E+11 | 0.00 | 0.65 |
August | 0.331038E+10 | 0.237436E+10 | 0.00 | 46450924.77 | 7794910.19 | 0.00 | 0.180111E+11 | 0.00 | 0.70 |
September | 0.910823E+10 | 44345197.19 | 0.00 | 29646888.33 | 0.00 | 0.00 | 0.193113E+11 | 0.00 | 0.50 |
October | 0.172650E+11 | 0.00 | 0.00 | 5596665.47 | 0.00 | 0.375193E+09 | 0.506872E+10 | 0.00 | 0.32 |
November | 0.154959E+11 | 0.00 | 0.00 | 50651.29 | 0.00 | 0.263990E+10 | 0.223503E+09 | 0.00 | 0.29 |
December | 0.127837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111371E+11 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.133993E+12 | 0.958811E+10 | 0.00 | 0.226494E+09 | 0.139217E+10 | 0.377609E+11 | 0.103243E+12 | 0.00 | 0.43 |
Minimum of Months | 0.241977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.191889E+11 | 0.434721E+10 | 0.00 | 46466547.84 | 0.848722E+09 | 0.143860E+11 | 0.209973E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.986330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413881E+10 | 0.00 | 0.00 | 0.29 |
February | 0.207689E+10 | 0.00 | 0.00 | 20109.10 | 0.00 | 0.144586E+10 | 31661323.74 | 0.00 | 0.26 |
March | 0.309693E+10 | 0.00 | 0.00 | 782354.77 | 0.00 | 0.240751E+09 | 0.637764E+09 | 0.00 | 0.28 |
April | 0.183183E+10 | 0.00 | 0.00 | 4426892.48 | 2685263.59 | 0.00 | 0.302603E+10 | 0.00 | 0.45 |
May | 0.871476E+09 | 15101369.08 | 0.00 | 10418388.31 | 0.00 | 0.00 | 0.464610E+10 | 0.00 | 0.83 |
June | 0.432910E+09 | 0.721763E+09 | 0.00 | 11126033.67 | 52047351.69 | 0.00 | 0.402572E+10 | 0.00 | 1.21 |
July | 0.809930E+09 | 0.101669E+10 | 0.00 | 8784099.07 | 0.239775E+09 | 0.00 | 0.276756E+10 | 0.00 | 1.20 |
August | 0.133838E+10 | 0.598984E+09 | 0.00 | 9378524.58 | 7859383.24 | 0.00 | 0.360617E+10 | 0.00 | 1.25 |
September | 0.120974E+10 | 12032522.46 | 0.00 | 6725042.18 | 0.00 | 0.00 | 0.389981E+10 | 0.00 | 0.69 |
October | 0.216521E+10 | 0.00 | 0.00 | 2802760.64 | 0.00 | 0.00 | 0.207005E+10 | 0.00 | 0.35 |
November | 0.272219E+10 | 0.00 | 0.00 | 610189.39 | 0.00 | 0.117625E+09 | 0.514736E+09 | 0.00 | 0.26 |
December | 0.197661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205199E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.195184E+11 | 0.236457E+10 | 0.00 | 55074394.20 | 0.302367E+09 | 0.799503E+10 | 0.252256E+11 | 0.00 | 0.61 |
Minimum of Months | 0.432910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.309693E+10 | 0.101669E+10 | 0.00 | 11126033.67 | 0.239775E+09 | 0.413881E+10 | 0.464610E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108096E+10 | 0.00 | 0.00 | 14908.59 | 0.00 | 0.225064E+10 | 8838341.69 | 0.00 | 0.29 |
February | 0.134692E+10 | 0.00 | 0.00 | 758697.01 | 0.00 | 0.731238E+09 | 0.371392E+09 | 0.00 | 0.28 |
March | 0.167287E+10 | 0.00 | 0.00 | 3630937.78 | 0.00 | 0.180958E+09 | 0.166643E+10 | 0.00 | 0.37 |
April | 0.105058E+10 | 0.00 | 0.00 | 8825901.42 | 1726043.52 | 987972.78 | 0.446837E+10 | 0.00 | 0.75 |
May | 0.410677E+09 | 11286999.30 | 0.00 | 12893308.85 | 0.00 | 0.00 | 0.533219E+10 | 0.00 | 1.30 |
June | 0.257712E+09 | 0.598799E+09 | 0.00 | 12878812.78 | 16406330.95 | 0.00 | 0.465975E+10 | 0.00 | 1.84 |
July | 0.510986E+09 | 0.997646E+09 | 0.00 | 9809181.20 | 0.132877E+09 | 0.00 | 0.315153E+10 | 0.00 | 1.82 |
August | 0.876777E+09 | 0.460669E+09 | 0.00 | 11306151.76 | 5120070.24 | 0.00 | 0.328545E+10 | 0.00 | 1.65 |
September | 0.672127E+09 | 11081863.59 | 0.00 | 8474402.23 | 0.00 | 0.00 | 0.433146E+10 | 0.00 | 1.05 |
October | 0.136364E+10 | 0.00 | 0.00 | 3285819.79 | 0.00 | 0.00 | 0.182011E+10 | 0.00 | 0.42 |
November | 0.161365E+10 | 0.00 | 0.00 | 786499.17 | 0.00 | 0.146832E+09 | 0.491283E+09 | 0.00 | 0.27 |
December | 0.129955E+10 | 0.00 | 0.00 | 35449.70 | 0.00 | 0.131051E+10 | 19537184.19 | 0.00 | 0.26 |
Annual Sum or Average | 0.121565E+11 | 0.207948E+10 | 0.00 | 72700070.28 | 0.156130E+09 | 0.462116E+10 | 0.296064E+11 | 0.00 | 0.86 |
Minimum of Months | 0.257712E+09 | 0.00 | 0.00 | 14908.59 | 0.00 | 0.00 | 8838341.69 | 0.00 | 0.26 |
Maximum of Months | 0.167287E+10 | 0.997646E+09 | 0.00 | 12893308.85 | 0.132877E+09 | 0.225064E+10 | 0.533219E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160497E+10 | 0.00 | 0.00 | 5693025.87 | 0.00 | 0.260960E+10 | 0.296457E+10 | 0.00 | 0.41 |
February | 0.147903E+10 | 0.00 | 0.00 | 9042538.19 | 0.00 | 0.104299E+10 | 0.429840E+10 | 0.00 | 0.50 |
March | 0.207671E+10 | 0.00 | 0.00 | 12133347.99 | 0.00 | 0.294083E+09 | 0.579830E+10 | 0.00 | 0.52 |
April | 0.164779E+10 | 11805449.67 | 0.00 | 13405525.27 | 172656.57 | 20773806.54 | 0.808288E+10 | 0.00 | 0.95 |
May | 0.882076E+09 | 20511636.09 | 0.00 | 16775834.70 | 0.00 | 0.00 | 0.657183E+10 | 0.00 | 1.19 |
June | 0.490816E+09 | 0.852263E+09 | 0.00 | 13509461.25 | 45653367.93 | 0.00 | 0.430842E+10 | 0.00 | 1.44 |
July | 0.781634E+09 | 0.135711E+10 | 0.00 | 12045321.94 | 0.228065E+09 | 0.00 | 0.319677E+10 | 0.00 | 1.46 |
August | 0.129718E+10 | 0.913641E+09 | 0.00 | 18458080.89 | 5531458.47 | 0.00 | 0.473653E+10 | 0.00 | 1.74 |
September | 0.980072E+09 | 38690905.06 | 0.00 | 18920812.23 | 0.00 | 0.00 | 0.789174E+10 | 0.00 | 1.34 |
October | 0.185516E+10 | 0.00 | 0.00 | 12184538.18 | 0.00 | 26107980.37 | 0.534839E+10 | 0.00 | 0.70 |
November | 0.201706E+10 | 0.00 | 0.00 | 5496674.54 | 0.00 | 0.247471E+09 | 0.312719E+10 | 0.00 | 0.38 |
December | 0.198987E+10 | 0.00 | 0.00 | 4065827.98 | 0.00 | 0.161557E+10 | 0.164496E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.171024E+11 | 0.319402E+10 | 0.00 | 0.141731E+09 | 0.279423E+09 | 0.585660E+10 | 0.579700E+11 | 0.00 | 0.92 |
Minimum of Months | 0.490816E+09 | 0.00 | 0.00 | 4065827.98 | 0.00 | 0.00 | 0.164496E+10 | 0.00 | 0.34 |
Maximum of Months | 0.207671E+10 | 0.135711E+10 | 0.00 | 18920812.23 | 0.228065E+09 | 0.260960E+10 | 0.808288E+10 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147916E+10 | 0.00 | 0.00 | 504226.12 | 0.00 | 0.156808E+10 | 0.270759E+09 | 0.00 | 0.30 |
February | 0.148026E+10 | 0.00 | 0.00 | 2782104.50 | 0.00 | 0.172713E+09 | 0.157777E+10 | 0.00 | 0.37 |
March | 0.784228E+09 | 0.00 | 0.00 | 9590579.64 | 0.00 | 157379.55 | 0.511670E+10 | 0.00 | 0.61 |
April | 0.182528E+09 | 8083605.29 | 0.00 | 17154333.61 | 106749.96 | 0.00 | 0.949944E+10 | 0.00 | 1.42 |
May | 0.222879E+09 | 17921148.98 | 0.00 | 19002754.07 | 0.00 | 0.00 | 0.675961E+10 | 0.00 | 1.72 |
June | 0.132701E+09 | 0.882959E+09 | 0.00 | 16541978.26 | 8274301.85 | 0.00 | 0.502886E+10 | 0.00 | 2.31 |
July | 0.213038E+09 | 0.159594E+10 | 0.00 | 17776945.36 | 21259883.47 | 0.00 | 0.419324E+10 | 0.00 | 2.41 |
August | 0.295936E+09 | 0.842282E+09 | 0.00 | 24274850.15 | 219768.99 | 0.00 | 0.643997E+10 | 0.00 | 2.78 |
September | 0.236261E+09 | 13716244.20 | 0.00 | 13519028.89 | 0.00 | 0.00 | 0.602408E+10 | 0.00 | 1.42 |
October | 0.335939E+09 | 0.00 | 0.00 | 8758903.50 | 0.00 | 0.00 | 0.522389E+10 | 0.00 | 0.76 |
November | 0.575083E+09 | 0.00 | 0.00 | 4871246.30 | 0.00 | 96882.51 | 0.316809E+10 | 0.00 | 0.44 |
December | 0.187309E+10 | 0.00 | 0.00 | 2104433.50 | 0.00 | 51333533.14 | 0.108813E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.781111E+10 | 0.336090E+10 | 0.00 | 0.136881E+09 | 29860704.27 | 0.179238E+10 | 0.543905E+11 | 0.00 | 1.24 |
Minimum of Months | 0.132701E+09 | 0.00 | 0.00 | 504226.12 | 0.00 | 0.00 | 0.270759E+09 | 0.00 | 0.30 |
Maximum of Months | 0.187309E+10 | 0.159594E+10 | 0.00 | 24274850.15 | 21259883.47 | 0.156808E+10 | 0.949944E+10 | 0.00 | 2.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.599936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693698E+11 | 0.00 | 0.00 | 0.40 |
February | 0.287389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390834E+11 | 0.00 | 0.00 | 0.34 |
March | 0.144420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222507E+11 | 0.00 | 0.00 | 0.32 |
April | 0.238117E+11 | 0.00 | 0.00 | 6526846.17 | 97187961.84 | 0.430694E+10 | 0.431388E+10 | 0.00 | 0.32 |
May | 0.117435E+11 | 0.159114E+09 | 0.00 | 72565879.28 | 0.00 | 12124897.52 | 0.294347E+11 | 0.00 | 0.66 |
June | 0.349529E+10 | 0.637401E+10 | 0.00 | 84732668.35 | 0.429319E+09 | 0.00 | 0.301483E+11 | 0.00 | 0.98 |
July | 0.372145E+10 | 0.879585E+10 | 0.00 | 67560528.04 | 0.837677E+09 | 0.00 | 0.211152E+11 | 0.00 | 0.91 |
August | 0.781680E+10 | 0.415515E+10 | 0.00 | 58567930.32 | 42022301.07 | 0.00 | 0.217863E+11 | 0.00 | 0.84 |
September | 0.189669E+11 | 0.108264E+09 | 0.00 | 33066667.09 | 0.00 | 0.00 | 0.184228E+11 | 0.00 | 0.51 |
October | 0.288966E+11 | 0.00 | 0.00 | 1785637.22 | 0.00 | 0.320848E+10 | 0.164359E+10 | 0.00 | 0.31 |
November | 0.124231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188964E+11 | 0.00 | 0.00 | 0.31 |
December | 0.468245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530455E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.129259E+12 | 0.195924E+11 | 0.00 | 0.324806E+09 | 0.140621E+10 | 0.210173E+12 | 0.126865E+12 | 0.00 | 0.52 |
Minimum of Months | 0.468245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.288966E+11 | 0.879585E+10 | 0.00 | 84732668.35 | 0.837677E+09 | 0.693698E+11 | 0.301483E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360522E+11 | 0.00 | 0.00 | 0.33 |
February | 0.426525E+10 | 0.00 | 0.00 | 303185.17 | 0.00 | 0.179830E+11 | 0.129521E+09 | 0.00 | 0.27 |
March | 0.807504E+10 | 0.00 | 0.00 | 16159666.26 | 0.00 | 0.910459E+10 | 0.712112E+10 | 0.00 | 0.32 |
April | 0.780980E+10 | 0.00 | 0.00 | 63234075.78 | 62415018.41 | 0.172891E+10 | 0.304986E+11 | 0.00 | 0.62 |
May | 0.425426E+10 | 0.120374E+09 | 0.00 | 0.120228E+09 | 0.00 | 0.00 | 0.445240E+11 | 0.00 | 1.18 |
June | 0.159397E+10 | 0.593298E+10 | 0.00 | 0.128766E+09 | 0.106143E+09 | 0.00 | 0.443156E+11 | 0.00 | 1.76 |
July | 0.174277E+10 | 0.952438E+10 | 0.00 | 0.100756E+09 | 0.298625E+09 | 0.00 | 0.315751E+11 | 0.00 | 1.71 |
August | 0.316686E+10 | 0.379255E+10 | 0.00 | 0.111196E+09 | 26296222.55 | 0.00 | 0.297406E+11 | 0.00 | 1.41 |
September | 0.806103E+10 | 0.115973E+09 | 0.00 | 67770576.44 | 0.00 | 0.00 | 0.312626E+11 | 0.00 | 0.86 |
October | 0.132284E+11 | 0.00 | 0.00 | 14416740.99 | 0.00 | 0.188449E+10 | 0.655102E+10 | 0.00 | 0.32 |
November | 0.693639E+10 | 0.00 | 0.00 | 640388.35 | 0.00 | 0.960447E+10 | 0.439804E+09 | 0.00 | 0.26 |
December | 0.139519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285690E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.623280E+11 | 0.194863E+11 | 0.00 | 0.623472E+09 | 0.493479E+09 | 0.104927E+12 | 0.226158E+12 | 0.00 | 0.78 |
Minimum of Months | 0.139519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.132284E+11 | 0.952438E+10 | 0.00 | 0.128766E+09 | 0.298625E+09 | 0.360522E+11 | 0.445240E+11 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111559E+11 | 0.00 | 0.00 | 45841880.08 | 0.00 | 0.380707E+11 | 0.209483E+11 | 0.00 | 0.44 |
February | 0.100609E+11 | 0.00 | 0.00 | 71485532.56 | 0.00 | 0.200825E+11 | 0.302489E+11 | 0.00 | 0.55 |
March | 0.132322E+11 | 0.00 | 0.00 | 0.110703E+09 | 0.00 | 0.112948E+11 | 0.460993E+11 | 0.00 | 0.59 |
April | 0.140361E+11 | 0.410032E+09 | 0.00 | 0.113115E+09 | 473543.20 | 0.234968E+10 | 0.575893E+11 | 0.00 | 0.78 |
May | 0.937031E+10 | 0.232059E+09 | 0.00 | 0.161558E+09 | 0.00 | 0.00 | 0.562258E+11 | 0.00 | 1.11 |
June | 0.517107E+10 | 0.802752E+10 | 0.00 | 0.121592E+09 | 0.338796E+09 | 0.00 | 0.360364E+11 | 0.00 | 1.30 |
July | 0.357612E+10 | 0.127474E+11 | 0.00 | 0.110853E+09 | 0.728807E+09 | 0.00 | 0.279042E+11 | 0.00 | 1.26 |
August | 0.589010E+10 | 0.749145E+10 | 0.00 | 0.166146E+09 | 19422835.88 | 0.00 | 0.382531E+11 | 0.00 | 1.44 |
September | 0.118147E+11 | 0.405691E+09 | 0.00 | 0.188120E+09 | 0.00 | 0.00 | 0.684189E+11 | 0.00 | 1.25 |
October | 0.196578E+11 | 0.00 | 0.00 | 0.116720E+09 | 0.00 | 0.210230E+10 | 0.395964E+11 | 0.00 | 0.63 |
November | 0.146672E+11 | 0.00 | 0.00 | 38393718.46 | 0.00 | 0.111115E+11 | 0.219114E+11 | 0.00 | 0.45 |
December | 0.733356E+10 | 0.00 | 0.00 | 24458488.30 | 0.00 | 0.355917E+11 | 0.843961E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.125966E+12 | 0.293141E+11 | 0.00 | 0.126899E+10 | 0.108750E+10 | 0.120603E+12 | 0.451672E+12 | 0.00 | 0.85 |
Minimum of Months | 0.357612E+10 | 0.00 | 0.00 | 24458488.30 | 0.00 | 0.00 | 0.843961E+10 | 0.00 | 0.38 |
Maximum of Months | 0.196578E+11 | 0.127474E+11 | 0.00 | 0.188120E+09 | 0.728807E+09 | 0.380707E+11 | 0.684189E+11 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293906E+10 | 0.00 | 0.00 | 284303.77 | 0.00 | 0.375434E+11 | 0.229228E+09 | 0.00 | 0.36 |
February | 0.568051E+10 | 0.00 | 0.00 | 3893085.55 | 0.00 | 0.182212E+11 | 0.240764E+10 | 0.00 | 0.34 |
March | 0.113251E+11 | 0.00 | 0.00 | 23402693.11 | 0.00 | 0.824195E+10 | 0.119256E+11 | 0.00 | 0.42 |
April | 0.109180E+11 | 23392171.50 | 0.00 | 56177880.24 | 50613175.05 | 0.974736E+09 | 0.286622E+11 | 0.00 | 0.65 |
May | 0.467244E+10 | 0.200908E+09 | 0.00 | 0.150241E+09 | 0.00 | 0.00 | 0.442300E+11 | 0.00 | 1.34 |
June | 0.203975E+10 | 0.674107E+10 | 0.00 | 0.110848E+09 | 0.157674E+09 | 0.00 | 0.308412E+11 | 0.00 | 1.66 |
July | 0.121787E+10 | 0.106397E+11 | 0.00 | 0.110819E+09 | 0.272921E+09 | 0.00 | 0.241904E+11 | 0.00 | 1.61 |
August | 0.258136E+10 | 0.487706E+10 | 0.00 | 0.113473E+09 | 5262539.30 | 0.00 | 0.281090E+11 | 0.00 | 1.51 |
September | 0.802176E+10 | 0.117776E+09 | 0.00 | 80800584.32 | 0.00 | 0.00 | 0.320333E+11 | 0.00 | 0.95 |
October | 0.151357E+11 | 0.00 | 0.00 | 21675474.85 | 0.00 | 0.147659E+10 | 0.109948E+11 | 0.00 | 0.41 |
November | 0.109693E+11 | 0.00 | 0.00 | 1973963.87 | 0.00 | 0.801309E+10 | 0.143617E+10 | 0.00 | 0.31 |
December | 0.283146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284020E+11 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.783323E+11 | 0.225999E+11 | 0.00 | 0.673589E+09 | 0.486471E+09 | 0.102873E+12 | 0.215059E+12 | 0.00 | 0.83 |
Minimum of Months | 0.121787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.151357E+11 | 0.106397E+11 | 0.00 | 0.150241E+09 | 0.272921E+09 | 0.375434E+11 | 0.442300E+11 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27514677.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739747E+10 | 0.00 | 0.00 | 0.46 |
February | 0.209803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411966E+10 | 0.00 | 0.00 | 0.40 |
March | 0.901018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267759E+10 | 0.00 | 0.00 | 0.38 |
April | 0.208853E+10 | 0.00 | 0.00 | 376282.22 | 12984937.15 | 0.909632E+09 | 0.322152E+09 | 0.00 | 0.38 |
May | 0.166471E+10 | 14705746.48 | 0.00 | 6128394.22 | 0.00 | 53076355.18 | 0.229790E+10 | 0.00 | 0.67 |
June | 0.568953E+09 | 0.613540E+09 | 0.00 | 7613718.41 | 60684833.02 | 0.00 | 0.274635E+10 | 0.00 | 0.99 |
July | 0.448665E+09 | 0.920500E+09 | 0.00 | 6265830.32 | 0.120402E+09 | 0.00 | 0.195928E+10 | 0.00 | 0.93 |
August | 0.105137E+10 | 0.437614E+09 | 0.00 | 5196596.83 | 2526204.46 | 366112.04 | 0.186862E+10 | 0.00 | 0.85 |
September | 0.242505E+10 | 7528022.92 | 0.00 | 1885457.27 | 0.00 | 0.117060E+09 | 0.113379E+10 | 0.00 | 0.52 |
October | 0.216621E+10 | 0.00 | 0.00 | 28888.74 | 0.00 | 0.107929E+10 | 26897333.75 | 0.00 | 0.36 |
November | 0.576573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233202E+10 | 0.00 | 0.00 | 0.36 |
December | 38086316.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543071E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.121665E+11 | 0.199389E+10 | 0.00 | 27495168.00 | 0.196598E+09 | 0.241169E+11 | 0.103550E+11 | 0.00 | 0.56 |
Minimum of Months | 27514677.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.242505E+10 | 0.920500E+09 | 0.00 | 7613718.41 | 0.120402E+09 | 0.739747E+10 | 0.274635E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53076382.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399633E+10 | 0.00 | 0.00 | 0.40 |
February | 0.310118E+09 | 0.00 | 0.00 | 2590.85 | 0.00 | 0.199182E+10 | 2645169.48 | 0.00 | 0.33 |
March | 0.686935E+09 | 0.00 | 0.00 | 857019.14 | 0.00 | 0.110461E+10 | 0.365144E+09 | 0.00 | 0.35 |
April | 0.738614E+09 | 0.00 | 0.00 | 4998766.21 | 7289087.69 | 0.298129E+09 | 0.259804E+10 | 0.00 | 0.64 |
May | 0.453832E+09 | 11747202.51 | 0.00 | 10763393.36 | 0.00 | 14301143.12 | 0.414077E+10 | 0.00 | 1.21 |
June | 0.147848E+09 | 0.600233E+09 | 0.00 | 12439174.73 | 14014276.49 | 0.00 | 0.446506E+10 | 0.00 | 1.82 |
July | 0.159651E+09 | 0.101816E+10 | 0.00 | 10156554.52 | 30769534.39 | 0.00 | 0.320045E+10 | 0.00 | 1.79 |
August | 0.347886E+09 | 0.409143E+09 | 0.00 | 11100237.69 | 1066568.72 | 0.00 | 0.291011E+10 | 0.00 | 1.47 |
September | 0.926778E+09 | 7436715.45 | 0.00 | 5559625.90 | 0.00 | 43755379.32 | 0.273936E+10 | 0.00 | 0.86 |
October | 0.111673E+10 | 0.00 | 0.00 | 903784.59 | 0.00 | 0.505321E+09 | 0.456634E+09 | 0.00 | 0.36 |
November | 0.510866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117726E+10 | 0.00 | 0.00 | 0.32 |
December | 48220891.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303926E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.550056E+10 | 0.204672E+10 | 0.00 | 56781147.00 | 53139467.29 | 0.121708E+11 | 0.208782E+11 | 0.00 | 0.83 |
Minimum of Months | 48220891.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.111673E+10 | 0.101816E+10 | 0.00 | 12439174.73 | 30769534.39 | 0.399633E+10 | 0.446506E+10 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.820922E+09 | 0.00 | 0.00 | 3334639.70 | 0.00 | 0.381706E+10 | 0.138221E+10 | 0.00 | 0.41 |
February | 0.638988E+09 | 0.00 | 0.00 | 5530494.65 | 0.00 | 0.207823E+10 | 0.239931E+10 | 0.00 | 0.50 |
March | 0.846094E+09 | 0.00 | 0.00 | 7312644.72 | 0.00 | 0.132569E+10 | 0.344811E+10 | 0.00 | 0.53 |
April | 0.102365E+10 | 40582327.23 | 0.00 | 9341350.29 | 648145.52 | 0.482390E+09 | 0.569349E+10 | 0.00 | 0.82 |
May | 0.925984E+09 | 19928207.07 | 0.00 | 14606020.32 | 0.00 | 45703820.30 | 0.533191E+10 | 0.00 | 1.10 |
June | 0.527397E+09 | 0.779127E+09 | 0.00 | 11533107.46 | 39953641.05 | 0.00 | 0.369139E+10 | 0.00 | 1.31 |
July | 0.415149E+09 | 0.128084E+10 | 0.00 | 10742467.03 | 94291150.13 | 0.00 | 0.279384E+10 | 0.00 | 1.29 |
August | 0.648367E+09 | 0.784543E+09 | 0.00 | 17221021.77 | 987940.58 | 0.00 | 0.375059E+10 | 0.00 | 1.46 |
September | 0.122904E+10 | 26461616.52 | 0.00 | 16207701.40 | 0.00 | 64188985.64 | 0.627468E+10 | 0.00 | 1.22 |
October | 0.143554E+10 | 0.00 | 0.00 | 9621531.85 | 0.00 | 0.564079E+09 | 0.348097E+10 | 0.00 | 0.66 |
November | 0.899576E+09 | 0.00 | 0.00 | 2860627.40 | 0.00 | 0.125759E+10 | 0.156997E+10 | 0.00 | 0.42 |
December | 0.430270E+09 | 0.00 | 0.00 | 1571166.68 | 0.00 | 0.347619E+10 | 0.500292E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.984097E+10 | 0.293148E+10 | 0.00 | 0.109883E+09 | 0.135881E+09 | 0.131111E+11 | 0.403168E+11 | 0.00 | 0.84 |
Minimum of Months | 0.415149E+09 | 0.00 | 0.00 | 1571166.68 | 0.00 | 0.00 | 0.500292E+09 | 0.00 | 0.36 |
Maximum of Months | 0.143554E+10 | 0.128084E+10 | 0.00 | 17221021.77 | 94291150.13 | 0.381706E+10 | 0.627468E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166283E+09 | 0.00 | 0.00 | 4552.02 | 0.00 | 0.395972E+10 | 3944545.41 | 0.00 | 0.39 |
February | 0.371502E+09 | 0.00 | 0.00 | 311320.51 | 0.00 | 0.186565E+10 | 0.210453E+09 | 0.00 | 0.35 |
March | 0.688984E+09 | 0.00 | 0.00 | 1604060.38 | 0.00 | 0.975930E+09 | 0.984639E+09 | 0.00 | 0.40 |
April | 0.888372E+09 | 8772469.20 | 0.00 | 4959506.82 | 5321500.32 | 0.248151E+09 | 0.286907E+10 | 0.00 | 0.71 |
May | 0.521583E+09 | 16675302.15 | 0.00 | 14003509.68 | 0.00 | 14844291.36 | 0.424177E+10 | 0.00 | 1.33 |
June | 0.232718E+09 | 0.651889E+09 | 0.00 | 10691618.40 | 16564418.48 | 0.00 | 0.312778E+10 | 0.00 | 1.68 |
July | 0.152038E+09 | 0.106437E+10 | 0.00 | 10603639.78 | 41019434.19 | 0.00 | 0.236778E+10 | 0.00 | 1.63 |
August | 0.291174E+09 | 0.526365E+09 | 0.00 | 11685862.85 | 175799.96 | 0.00 | 0.270627E+10 | 0.00 | 1.52 |
September | 0.899109E+09 | 9297728.18 | 0.00 | 6955735.50 | 0.00 | 16708131.51 | 0.281321E+10 | 0.00 | 0.92 |
October | 0.116437E+10 | 0.00 | 0.00 | 1590471.01 | 0.00 | 0.316422E+09 | 0.916918E+09 | 0.00 | 0.43 |
November | 0.613370E+09 | 0.00 | 0.00 | 103816.48 | 0.00 | 0.931675E+09 | 87972215.19 | 0.00 | 0.31 |
December | 0.133207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281825E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.612271E+10 | 0.227737E+10 | 0.00 | 62514093.41 | 63081152.94 | 0.111473E+11 | 0.203298E+11 | 0.00 | 0.84 |
Minimum of Months | 0.133207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.116437E+10 | 0.106437E+10 | 0.00 | 14003509.68 | 41019434.19 | 0.395972E+10 | 0.424177E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71714266.86 | 0.00 | 0.00 | 2363678.04 | 0.00 | 0.00 | 0.106374E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8238564.85 | 0.00 | 0.00 | 0.889545E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 15760456.08 | 0.00 | 0.00 | 0.889909E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 18538588.05 | 0.00 | 0.00 | 0.565767E+09 | 0.00 | 0.29 |
May | 0.00 | 4125717.47 | 0.00 | 3919682.24 | 0.00 | 0.00 | 0.329669E+09 | 0.00 | 0.29 |
June | 0.00 | 82411922.28 | 0.00 | 5637216.49 | 0.00 | 0.00 | 0.147725E+09 | 0.00 | 0.31 |
July | 0.00 | 0.115870E+09 | 0.00 | 5471918.38 | 0.00 | 0.00 | 57407645.97 | 0.00 | 0.28 |
August | 0.00 | 76398803.88 | 0.00 | 10075397.46 | 0.00 | 0.00 | 83697678.28 | 0.00 | 0.31 |
September | 0.00 | 1009095.01 | 0.00 | 3775307.43 | 0.00 | 0.00 | 0.352200E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8168410.18 | 0.00 | 0.00 | 0.563633E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12743334.73 | 0.00 | 0.00 | 0.695254E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 22082351.13 | 0.00 | 0.00 | 0.101828E+10 | 0.00 | 0.28 |
Annual Sum or Average | 71714266.86 | 0.279816E+09 | 0.00 | 0.116775E+09 | 0.00 | 0.00 | 0.665683E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2363678.04 | 0.00 | 0.00 | 57407645.97 | 0.00 | 0.28 |
Maximum of Months | 71714266.86 | 0.115870E+09 | 0.00 | 22082351.13 | 0.00 | 0.00 | 0.106374E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.921037E+10 | 0.00 | 0.00 | 2601788.65 | 0.00 | 0.00 | 0.180841E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 55488729.12 | 0.00 | 0.00 | 0.892176E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.128860E+09 | 0.00 | 0.00 | 0.892782E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.167621E+09 | 0.00 | 0.00 | 0.567467E+10 | 0.00 | 0.29 |
May | 0.00 | 40124098.45 | 0.00 | 34431547.54 | 0.00 | 0.00 | 0.330388E+10 | 0.00 | 0.29 |
June | 0.00 | 0.818033E+09 | 0.00 | 52875722.47 | 0.00 | 0.00 | 0.148131E+10 | 0.00 | 0.31 |
July | 0.00 | 0.115481E+10 | 0.00 | 51930425.92 | 0.00 | 0.00 | 0.576768E+09 | 0.00 | 0.28 |
August | 0.00 | 0.762166E+09 | 0.00 | 95591891.04 | 0.00 | 0.00 | 0.841526E+09 | 0.00 | 0.31 |
September | 0.00 | 8304075.35 | 0.00 | 31507957.78 | 0.00 | 0.00 | 0.353647E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 67420699.98 | 0.00 | 0.00 | 0.564958E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.101124E+09 | 0.00 | 0.00 | 0.697781E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.176542E+09 | 0.00 | 0.00 | 0.102256E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.921037E+10 | 0.278344E+10 | 0.00 | 0.965995E+09 | 0.00 | 0.00 | 0.579256E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2601788.65 | 0.00 | 0.00 | 0.576768E+09 | 0.00 | 0.28 |
Maximum of Months | 0.921037E+10 | 0.115481E+10 | 0.00 | 0.176542E+09 | 0.00 | 0.00 | 0.102256E+11 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100192E+10 | 0.00 | 0.00 | 120953.21 | 0.00 | 0.00 | 75407870.43 | 0.00 | 0.28 |
February | 1182424.39 | 0.00 | 0.00 | 4469264.24 | 0.00 | 0.00 | 0.891964E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 11515845.61 | 0.00 | 0.00 | 0.894153E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15804418.55 | 0.00 | 0.00 | 0.568446E+09 | 0.00 | 0.29 |
May | 4266483.67 | 4058309.75 | 0.00 | 3170079.90 | 0.00 | 0.00 | 0.326371E+09 | 0.00 | 0.29 |
June | 0.00 | 81750336.57 | 0.00 | 5238191.65 | 0.00 | 0.00 | 0.148378E+09 | 0.00 | 0.31 |
July | 0.00 | 0.115422E+09 | 0.00 | 5154188.66 | 0.00 | 0.00 | 57837132.94 | 0.00 | 0.28 |
August | 0.00 | 76098398.46 | 0.00 | 9472078.07 | 0.00 | 0.00 | 84437879.13 | 0.00 | 0.31 |
September | 0.00 | 844777.24 | 0.00 | 2658483.62 | 0.00 | 0.00 | 0.355081E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5585330.51 | 0.00 | 0.00 | 0.566260E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 8986659.22 | 0.00 | 0.00 | 0.699034E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16539254.08 | 0.00 | 0.00 | 0.102373E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.100737E+10 | 0.278174E+09 | 0.00 | 88714747.31 | 0.00 | 0.00 | 0.569110E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 120953.21 | 0.00 | 0.00 | 57837132.94 | 0.00 | 0.28 |
Maximum of Months | 0.100192E+10 | 0.115422E+09 | 0.00 | 16539254.08 | 0.00 | 0.00 | 0.102373E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.984005E+09 | 0.00 | 0.00 | 0.442235E+12 | 0.00 | 4.89 |
February | 0.00 | 0.00 | 0.00 | 0.152572E+10 | 0.00 | 0.00 | 0.713630E+12 | 0.00 | 9.91 |
March | 0.00 | 0.00 | 0.00 | 0.207848E+10 | 0.00 | 0.00 | 0.107510E+13 | 0.00 | 16.27 |
April | 0.00 | 0.00 | 0.00 | 0.233140E+10 | 0.00 | 0.00 | 0.122889E+13 | 0.00 | 29.81 |
May | 0.00 | 0.169952E+09 | 0.00 | 0.554234E+09 | 0.00 | 0.00 | 0.410833E+12 | 0.00 | 18.46 |
June | 0.00 | 0.187669E+11 | 0.00 | 0.977461E+09 | 0.00 | 0.00 | 0.451525E+12 | 0.00 | 32.73 |
July | 0.00 | 0.680383E+11 | 0.00 | 0.139525E+10 | 0.00 | 0.00 | 0.348611E+12 | 0.00 | 39.30 |
August | 0.00 | 0.177984E+11 | 0.00 | 0.230399E+10 | 0.00 | 0.00 | 0.395548E+12 | 0.00 | 42.86 |
September | 0.00 | 0.00 | 0.00 | 0.554554E+09 | 0.00 | 0.00 | 0.365140E+12 | 0.00 | 16.39 |
October | 0.00 | 0.00 | 0.00 | 0.106700E+10 | 0.00 | 0.00 | 0.738280E+12 | 0.00 | 17.96 |
November | 0.00 | 0.00 | 0.00 | 0.188019E+10 | 0.00 | 0.00 | 0.102489E+13 | 0.00 | 18.88 |
December | 0.00 | 0.00 | 0.00 | 0.411673E+10 | 0.00 | 0.00 | 0.131751E+13 | 0.00 | 16.57 |
Annual Sum or Average | 0.00 | 0.104774E+12 | 0.00 | 0.197690E+11 | 0.00 | 0.00 | 0.851219E+13 | 0.00 | 22.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.554234E+09 | 0.00 | 0.00 | 0.348611E+12 | 0.00 | 4.89 |
Maximum of Months | 0.00 | 0.680383E+11 | 0.00 | 0.411673E+10 | 0.00 | 0.00 | 0.131751E+13 | 0.00 | 42.86 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.257563E+12 | 0.517765E+11 | 0.00 | 0.218386E+13 | 0.209828E+12 |
February | 0.373312E+12 | 0.457593E+11 | 0.00 | 0.231535E+13 | 0.201063E+12 |
March | 0.541317E+12 | 0.327316E+11 | 0.00 | 0.299097E+13 | 0.273592E+12 |
April | 0.680796E+12 | 0.296140E+11 | 0.00 | 0.306038E+13 | 0.477015E+12 |
May | 0.790132E+12 | 0.148320E+11 | 0.00 | 0.233832E+13 | 0.638299E+12 |
June | 0.804762E+12 | 0.591805E+10 | 0.00 | 0.170235E+13 | 0.148114E+13 |
July | 0.829570E+12 | 0.298958E+10 | 0.00 | 0.124031E+13 | 0.238360E+13 |
August | 0.691177E+12 | 0.727845E+10 | 0.00 | 0.176449E+13 | 0.229302E+13 |
September | 0.502779E+12 | 0.140126E+11 | 0.00 | 0.227235E+13 | 0.354459E+12 |
October | 0.292760E+12 | 0.214339E+11 | 0.00 | 0.269173E+13 | 0.231456E+12 |
November | 0.150168E+12 | 0.368409E+11 | 0.00 | 0.266942E+13 | 0.262989E+12 |
December | 0.186264E+12 | 0.559133E+11 | 0.00 | 0.302438E+13 | 0.408276E+12 |
Annual Sum or Average | 0.610060E+13 | 0.319100E+12 | 0.00 | 0.282539E+14 | 0.921474E+13 |
Minimum of Months | 0.150168E+12 | 0.298958E+10 | 0.00 | 0.124031E+13 | 0.201063E+12 |
Maximum of Months | 0.829570E+12 | 0.559133E+11 | 0.00 | 0.306038E+13 | 0.238360E+13 |