Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:56:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26388.73 | 569.70 | 569.70 |
Net Site Energy | 25863.95 | 558.37 | 558.37 |
Total Source Energy | 81261.20 | 1754.33 | 1754.33 |
Net Source Energy | 79599.22 | 1718.45 | 1718.45 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 402.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2694.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1715.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 266.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2248.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 460.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1014.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6779.65 |
Humidification | 959.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.08 |
Heat Recovery | 39.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 707.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25278.84 | 1109.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9416.90 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 402.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2694.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1715.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 266.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2248.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 460.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1014.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6779.65 |
Humidification | General | 959.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.08 |
Heat Recovery | General | 39.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 707.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 402.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2694.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1715.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 266.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2248.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 460.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1014.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6779.65 |
Humidification | Unassigned | 959.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.08 |
Heat Recovery | Unassigned | 39.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 707.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 159.27 | 23.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Other | 343.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 545.74 | 23.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 159.27 | 23.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Other | 343.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 545.74 | 23.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 548.164 | 2.17 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -23.39 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 524.779 | 2.08 |
Electricity Coming From Utility | 24754.058 | 97.92 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 24754.058 | 97.92 |
Total On-Site and Utility Electric Sources | 25278.837 | 100.00 |
Total Electricity End Uses | 25278.837 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 805.66 | 60.16 |
Air to Air Heat Recovery for Heating | 533.62 | 39.84 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1339.28 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9416.90 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9416.90 | 100.00 |
Total Water End Uses | 9416.90 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 37.17 |
Time Setpoint Not Met During Occupied Cooling | 579.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5884.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-APR-15:39 | 13-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 13-APR-15:30 |
Heating | 0.00 | 1307065.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 357284.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 214360.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46642.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 65216.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 67259.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30743.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1727711.55 | 1337808.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1307065.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 357284.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 214360.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 46642.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 65216.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 67259.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 30743.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 436.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8532.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5433.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 843.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7121.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1457.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3212.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3040.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 123.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 766.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 80058.08 | 1203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 69.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 65.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1728.36 | 25.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 69.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 65.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1728.36 | 25.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 4.92 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.472655 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.51 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.459934 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.95 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.38 | 0.353533 | 0.301000 | 1.62 | 0.942753 | 0.500000 | 0.001078 | 0.000344 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 50.55 | 0.376237 | 0.320000 | 16.18 | 1.00 | 0.500000 | 0.001013 | 0.009318 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.99 | 0.380890 | 0.324000 | 1.62 | 1.00 | 0.500000 | 0.001000 | 0.001868 | 2.64 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.936092 | 0.255125 | 0.217000 | 0.203132 | 0.680334 | 0.500000 | 0.001493 | 0.000289 | 0.408071 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.01 | 0.152873 | 0.130000 | 0.130878 | 0.407660 | 0.500000 | 0.002492 | 0.000200 | 0.282404 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.11 | 0.214811 | 0.183000 | 0.203459 | 0.572828 | 0.500000 | 0.001774 | 0.000329 | 0.465466 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.29 | 0.119309 | 0.101000 | 0.130287 | 0.318158 | 0.500000 | 0.003193 | 0.000151 | 0.213327 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.92 | 0.267732 | 0.228000 | 2.03 | 0.713953 | 0.500000 | 0.001423 | 0.005086 | 7.19 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.58 | 0.387788 | 0.500000 | 0.002620 | 0.003337 | 4.72 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 10.71 | 0.223093 | 0.190000 | 2.03 | 0.594914 | 0.500000 | 0.001708 | 0.005029 | 7.11 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.23 | 0.137015 | 0.116000 | 1.30 | 0.365374 | 0.500000 | 0.002781 | 0.003220 | 4.56 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.02 | 0.233351 | 0.198000 | 0.202641 | 0.622269 | 0.500000 | 0.001633 | 0.000645 | 0.913450 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.08 | 0.142501 | 0.121000 | 0.130684 | 0.380002 | 0.500000 | 0.002674 | 0.000422 | 0.597249 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.19 | 0.200183 | 0.170000 | 0.202816 | 0.533822 | 0.500000 | 0.001903 | 0.000639 | 0.904776 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.21 | 0.127176 | 0.108000 | 0.130699 | 0.339136 | 0.500000 | 0.002996 | 0.000414 | 0.585918 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15720.71 | 0.000344 | 438.77 |
CORE_MID VAV BOX REHEAT COIL | 425976.81 | 0.009318 | 14879.51 |
CORE_TOP VAV BOX REHEAT COIL | 85411.63 | 0.001868 | 3324.08 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13203.94 | 0.000289 | 513.45 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9136.26 | 0.000200 | 355.24 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15057.90 | 0.000329 | 585.47 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6906.99 | 0.000151 | 268.70 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 232479.90 | 0.005086 | 9032.58 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 152564.43 | 0.003337 | 5927.47 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 229886.49 | 0.005029 | 8931.93 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 147216.29 | 0.003220 | 5719.87 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29505.80 | 0.000645 | 1146.11 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19291.51 | 0.000422 | 749.33 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 29226.00 | 0.000639 | 1135.25 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 18925.85 | 0.000414 | 735.14 |
VAV_BOT WITH REHEAT HEATING COIL | 46551.00 | 0.001018 | 989.30 |
VAV_MID WITH REHEAT HEATING COIL | 423219.18 | 0.009258 | 9029.43 |
VAV_TOP WITH REHEAT HEATING COIL | 41194.84 | 0.000901 | 898.81 |
CAV_BAS HEATING COIL | 238392.83 | 0.005215 | 7553.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.86 | 2.29 | 9.72 | 2.45 | 8.69 | 8.69 | 0.300000 | 0.281488 | 8.69 |
VAV_MID WITH REHEAT | 46.00 | 22.86 | 92.00 | 35.34 | 80.80 | 80.80 | 0.300000 | 0.437421 | 80.80 |
VAV_TOP WITH REHEAT | 4.75 | 2.28 | 9.50 | 5.64 | 8.96 | 8.96 | 0.300000 | 0.629306 | 8.96 |
CAV_BAS | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 1.00 | 1.00 | 4.92 |
AIRLOOP DATACENTER BASEMENT | 21.95 | 21.95 | 21.95 | 21.95 | 21.95 | 21.95 | 1.00 | 0.999989 | 21.95 |
AIRLOOP DATACENTER BOT | 0.472655 | 0.472655 | 0.472655 | 0.472655 | 0.472655 | 0.472655 | 1.00 | 1.00 | 0.472655 |
AIRLOOP DATACENTER MID | 4.51 | 4.51 | 4.51 | 4.51 | 4.51 | 4.51 | 1.00 | 1.00 | 4.51 |
AIRLOOP DATACENTER TOP | 0.459934 | 0.459934 | 0.459934 | 0.459934 | 0.459934 | 0.459934 | 1.00 | 1.00 | 0.459934 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.69 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 80.80 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.96 | |
CAV_BAS_OA_CONTROLLER | 4.92 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.95 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.472655 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.51 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.459934 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.51 | 6.67 | 10.98 | 0.010273 | 0.008500 | 205633.76 | 0.005881 | 8.69 |
VAV_MID WITH REHEAT COOLING COIL | 26.79 | 6.67 | 10.98 | 0.010504 | 0.008500 | 1992740.54 | 0.056992 | 80.80 |
VAV_TOP WITH REHEAT COOLING COIL | 26.32 | 6.67 | 10.98 | 0.010239 | 0.008500 | 208919.27 | 0.005975 | 8.96 |
CAV_BAS COOLING COIL | 26.48 | 6.67 | 11.37 | 0.010539 | 0.008500 | 117776.77 | 0.003368 | 4.92 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.69 |
VAV_MID WITH REHEAT FAN | 80.80 |
VAV_TOP WITH REHEAT FAN | 8.96 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005881 | 0.000081 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001018 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.056992 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009258 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005975 | 0.000080 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000901 | |
CAV_BAS_COOLC_CONTROLLER | 0.003368 | 0.000141 |
CAV_BAS_HEATC_CONTROLLER | 0.005215 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 4.92 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.95 | 434858.77 | 301326.97 | 0.010650 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.472655 | 9323.29 | 6466.39 | 0.000228 |
AIRLOOP DATACENTER MID COOLING COIL | 4.51 | 89143.31 | 61767.56 | 0.002183 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.459934 | 9083.21 | 6295.77 | 0.000222 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.95 | 21.95 | 21.95 | 21.95 | 434858.77 | 434858.77 | 18278.08 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.472655 | 0.472655 | 0.472655 | 0.472655 | 9323.29 | 9323.29 | 844.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.51 | 4.51 | 4.51 | 4.51 | 89143.31 | 89143.31 | 8443.71 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.459934 | 0.459934 | 0.459934 | 0.459934 | 9083.21 | 9083.21 | 844.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.95 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.472655 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.51 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.459934 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.95 | 434858.77 | 0.010650 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.472655 | 9323.29 | 0.000228 |
AIRLOOP DATACENTER MID HEATING COIL | 4.51 | 89143.31 | 0.002183 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.459934 | 9083.21 | 0.000222 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 18278.08 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 844.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8443.71 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 844.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000152 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.072217 | 11674.04 | |
HEATSYS1 PUMP | 0.047685 | 14218.35 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.072217 | 8.67 |
HEATSYS1 | 0.047685 | 5.72 |
COOLSYS1_SUPPLY | 0.072217 | 8.67 |
SINGLE WATER PLANT LOOP | 0.013284 | 1.59 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.072217 | 0.072217 | 303129.69 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2179868.37 | 2179868.37 | 0.047685 |
CENTRAL BOILER | 547168.43 | 536325.16 | 0.013284 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.036108 | 4041.17 |
COOLSYS1 CHILLER2 PUMP | 0.036108 | 4041.17 |
PLANT CIRC PUMP | 0.013284 | 3354.43 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.072217 | 0.036449 | 1277589.11 | 1283648.70 | 0.063108 |
COOLSYS1 CHILLER2 | 0.072217 | 0.036449 | 1277589.11 | 1283648.70 | 0.063108 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013284 | 139666.47 | 59313.47 | 69833.23 | 7004.20 | 21419.15 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.126215 | 15.15 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.126215 | 30938.66 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 48.50 | 1523009.01 | 9.70 | 190376.13 |
TOWERWATERSYS COOLTOWER 2 | 48.50 | 1523009.01 | 9.70 | 190376.13 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.065980 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.223 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.421 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6505 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6842 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5363 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.12806887E-14 | 0.42271709E-16 | -0.13586671E-09 | -0.40936836E-17 |
51 | 8 | 0.19922932E-07 | 0.16187222E-12 | 0.35697139E-03 | -0.22653060E-09 |
52 | 7 | -0.11619186E-01 | 0.85920355E-08 | -0.22189363E-01 | 0.13211437E-03 |
53 | 6 | 0.38843793 | 0.30204786E-05 | 0.45766083 | -0.45484060E-02 |
54 | 5 | -5.0254998 | 0.11379910E-03 | -4.3303126 | 0.61137149E-01 |
55 | 4 | 32.272621 | 0.93848507E-03 | 21.006408 | -0.41242756 |
56 | 3 | -109.67225 | 0.20601564E-02 | -54.766020 | 1.4927443 |
57 | 2 | 195.59070 | 0.11662962E-02 | 77.088399 | -2.8762550 |
58 | 1 | -170.59539 | 0.12524661E-03 | -55.026900 | 2.7356126 |
59 | 0 | 57.057407 | 0.71759292E-06 | 15.597005 | |
60 | 9 | 0.14110139E-14 | 0.39742576E-16 | -0.13817129E-09 | -0.60843190E-17 |
61 | 8 | 0.20247994E-07 | 0.15595569E-12 | 0.36048606E-03 | -0.23022666E-09 |
62 | 7 | -0.11724403E-01 | 0.82461052E-08 | -0.22340970E-01 | 0.13331073E-03 |
63 | 6 | 0.39129736 | 0.28944083E-05 | 0.46010459 | -0.45821116E-02 |
64 | 5 | -5.0534104 | 0.10890513E-03 | -4.3491197 | 0.61483222E-01 |
65 | 4 | 32.396114 | 0.89705981E-03 | 21.080005 | -0.41406715 |
66 | 3 | -109.93510 | 0.19671505E-02 | -54.911560 | 1.4965416 |
67 | 2 | 195.85133 | 0.11126060E-02 | 77.221727 | -2.8803937 |
68 | 1 | -170.69171 | 0.11937799E-03 | -55.065382 | 2.7373008 |
69 | 0 | 57.057407 | 0.68337402E-06 | 15.590414 | |
70 | 9 | 0.11953810E-14 | 0.45347951E-16 | -0.12637851E-09 | -0.31580148E-17 |
71 | 8 | 0.18583176E-07 | 0.18541820E-12 | 0.34227377E-03 | -0.21129711E-09 |
72 | 7 | -0.11178467E-01 | 0.10005971E-07 | -0.21554080E-01 | 0.12710323E-03 |
73 | 6 | 0.37645972 | 0.35409928E-05 | 0.44740546 | -0.44072130E-02 |
74 | 5 | -4.9085688 | 0.13417224E-03 | -4.2513079 | 0.59687292E-01 |
75 | 4 | 31.755172 | 0.11121548E-02 | 20.697061 | -0.40555762 |
76 | 3 | -108.57065 | 0.24524110E-02 | -54.154201 | 1.4768303 |
77 | 2 | 194.49811 | 0.13939007E-02 | 76.528253 | -2.8589059 |
78 | 1 | -170.19150 | 0.15023953E-03 | -54.865849 | 2.7285341 |
79 | 0 | 57.057407 | 0.86422455E-06 | 15.625098 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0099E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0113E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2971E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2982E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0843E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0851E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7516E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0413E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1280E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3226E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3951E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1047E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1645E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7664E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1017 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3507E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1133 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7229E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5963E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8582E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1496E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0924E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0510E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1766E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3332E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4483E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1138E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1994E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7668E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8046E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0099E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0116E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2970E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2985E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0842E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0854E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7515E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1867E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3802E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0730E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2816E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7412E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8300E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9952E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0209E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8690E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2764E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7115E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1274E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5946E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8652E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2799E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2243E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1393E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2042E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0130E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0607E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7148E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7356E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9953E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0213E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7616E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7630E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5080E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5093E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3464E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3473E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7516E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7522E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7952E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8766E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5360E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6016E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3696E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4201E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7668E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8046E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7518E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4347E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1231E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0926E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9288E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.5117E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1496E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0921E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7923E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8745E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5320E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5946E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3626E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3984E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7664E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7615E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7628E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5079E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5090E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3463E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3469E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7515E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7521E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3209E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3904E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0063E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0562E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0091E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0268E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9954E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0213E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4361E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7304E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9620E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4609E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2978E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3658E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2799E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2243E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3537E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4810E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0486E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1753E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0329E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1060E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9952E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0208E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1090 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.2883E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1194 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.7955E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5339E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.3148E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8633E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9092E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7713E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2776E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5970E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1036E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.4316E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7514E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9603E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9312E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4479E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2830E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7331E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8136E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5164E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3841E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8633E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9088E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.1515E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5255E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6178E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1833E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9767E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0822E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9603E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9312E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1091 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3024E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1195 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.8117E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5483E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.3257E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8716E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9134E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7768E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2830E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6034E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1090E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4405E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7574E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9686E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9354E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4484E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2856E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7338E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8157E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5204E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3866E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8716E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9131E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.1539E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5290E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6204E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1864E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9830E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0864E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9686E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9354E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 65911.33408 | 65911.33408 | 4.91961 | 4.91961 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -6.30000 | 2.29779E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72073.41780 | 72073.41780 | 5.38011 | 5.38011 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 677436.51849 | 677436.51849 | 50.55436 | 50.55436 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 268932.13554 | 268932.13554 | 11.75808 | 11.75808 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 66918.50893 | 66918.50893 | 4.99368 | 4.99368 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 59818.95323 | 59818.95323 | 2.63634 | 2.63634 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12421.36685 | 12421.36685 | 0.93609 | 0.93609 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 9248.64615 | 9248.64615 | 0.40807 | 0.40807 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13359.08571 | 13359.08571 | 1.00675 | 1.00675 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.52083 | 1.44662E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 6398.61647 | 6398.61647 | 0.28240 | 0.28240 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 14752.89510 | 14752.89510 | 1.11180 | 1.11180 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 10544.85421 | 10544.85421 | 0.46547 | 0.46547 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17117.25886 | 17117.25886 | 1.28997 | 1.28997 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 4840.96205 | 4840.96205 | 0.21333 | 0.21333 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 118357.88030 | 118357.88030 | 8.92012 | 8.92012 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40000 | 1.44733E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 162738.08560 | 162738.08560 | 7.19437 | 7.19437 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 140429.00445 | 140429.00445 | 10.58346 | 10.58346 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.79000 | 1.44667E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 106795.65009 | 106795.65009 | 4.72147 | 4.72147 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 142043.91474 | 142043.91474 | 10.70522 | 10.70522 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 160924.90248 | 160924.90248 | 7.11398 | 7.11398 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 149044.05680 | 149044.05680 | 11.23270 | 11.23270 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 103056.23379 | 103056.23379 | 4.55573 | 4.55573 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13579.38157 | 13579.38157 | 1.02344 | 1.02344 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.21000 | 1.44729E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 20650.97365 | 20650.97365 | 0.91345 | 0.91345 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14330.31093 | 14330.31093 | 1.08003 | 1.08003 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 13502.03752 | 13502.03752 | 0.59725 | 0.59725 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15829.68844 | 15829.68844 | 1.19304 | 1.19304 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 20455.33610 | 20455.33610 | 0.90478 | 0.90478 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16057.19797 | 16057.19797 | 1.21017 | 1.21017 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13246.33429 | 13246.33429 | 0.58592 | 0.58592 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 7952.02777 | 7952.02777 | 0.47266 | 0.47266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 30.52083 | 1.44662E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 75897.54544 | 75897.54544 | 4.51126 | 4.51126 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 30.52083 | 1.44662E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7737.96946 | 7737.96946 | 0.45993 | 0.45993 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.69500 | 1.44665E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -6.30000 | 2.29779E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369342.83784 | 369342.83784 | 21.95264 | 21.95264 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.75500 | 1.44575E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -6.30000 | 2.29779E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 134363.33 | 8.69341 | 8.69341 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 45849.58 | 2.44709 | 2.44709 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1235901.39 | 80.80000 | 80.80000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 452401.61 | 35.34363 | 35.34363 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 140892.34 | 8.95864 | 8.95864 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 44661.80 | 5.63773 | 5.63773 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
7 | CAV_BAS | Cooling | Sensible | 70650.12 | 4.91961 | 4.91961 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 64825.70 | 1.20016 | 1.20016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366099.42 | 21.95287 | 21.95287 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 18278.08 | 0.33839 | 0.33839 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7894.48 | 0.47266 | 0.47266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 844.37 | 1.56323E-002 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75366.34 | 4.51126 | 4.51126 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8443.71 | 0.15632 | 0.15632 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7685.73 | 0.45993 | 0.45993 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 844.37 | 1.56323E-002 | 1.56323E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.91961 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.38011 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35353 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61941 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94275 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07769E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43891E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61941 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15720.71496 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43891E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 438.76673 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 50.55436 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37624 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.17739 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01266E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.31825E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.17739 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 425976.81169 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.31825E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 14879.50722 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.99368 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38089 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61795 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00029E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86838E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.63634 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85411.62998 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86838E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3324.07656 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93609 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25513 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20313 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68033 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49339E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.88836E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40807 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13203.93610 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.88836E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 513.45402 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00675 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15287 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13088 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40766 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49227E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99856E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28240 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9136.26286 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99856E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 355.23966 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11180 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21481 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18300 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20346 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57283 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77366E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29392E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46547 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15057.90274 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29392E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 585.46915 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28997 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11931 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10100 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13029 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31816 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19338E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51091E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21333 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6906.98599 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51091E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 268.69850 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.92012 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26773 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03379 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71395 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42306E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.08550E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.19437 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 232479.90241 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.08550E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9032.58110 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.58346 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38779 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61999E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.33735E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.72147 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 152564.43090 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.33735E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5927.46511 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.70522 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22309 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19000 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03399 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59491 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70781E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.02877E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.11398 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 229886.49222 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.02877E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8931.92977 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.23270 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13702 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30299 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36537 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78071E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.22036E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.55573 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 147216.28598 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.22036E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5719.86789 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02344 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23335 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19800 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20264 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62227 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63273E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.45440E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91345 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29505.80287 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.45440E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1146.10505 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08003 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14250 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13068 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67367E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.22002E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59725 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19291.51083 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.22002E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 749.33426 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19304 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20018 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17000 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20282 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53382 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90326E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.39320E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90478 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29226.00318 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.39320E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1135.24591 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21017 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12718 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10800 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13070 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33914 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99585E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.14004E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58592 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18925.85335 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.14004E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 735.13910 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47266 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.51126 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45993 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.95264 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.86236 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28717 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.72472 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.44709 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.69341 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.69341 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28149 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 45.99793 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.86052 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 91.99586 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 35.34363 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 80.80000 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 80.80000 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43742 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.75018 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28479 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.50036 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.63773 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.95864 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.95864 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.62931 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.91961 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.91961 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.91961 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 4.91961 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.91961 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.91961 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.95264 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.95264 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.95264 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.95264 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.95287 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.95287 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47266 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47266 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47266 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47266 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47266 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47266 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.51126 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.51126 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.51126 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.51126 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.51126 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.51126 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45993 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45993 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45993 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45993 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45993 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45993 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.69341 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 80.80000 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.95864 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.91961 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.95287 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47266 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.51126 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45993 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.69341 |
286 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.51324 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98220 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02734E-002 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 205633.75620 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.88110E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.69341 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 46550.99732 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01830E-003 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 989.30389 |
298 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.69341 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.88110E-003 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.09696E-005 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.01830E-003 |
302 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 80.80000 |
303 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.78690 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98296 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.05045E-002 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1992740.54277 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.69921E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 80.80000 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 423219.18085 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.25793E-003 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 9029.42654 |
315 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 80.80000 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.69921E-002 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.35537E-006 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.25793E-003 |
319 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.95864 |
320 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.31931 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98208 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02386E-002 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 208919.26665 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.97506E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.95864 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 41194.84106 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.01138E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 898.80746 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.95864 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.97506E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.96963E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.01138E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.91961 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.48451 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.37429 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.05386E-002 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 117776.76514 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.36840E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.91961 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 238392.82857 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.21485E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7553.39838 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.91961 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.36840E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.41370E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.21485E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.95287 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.95287 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 434858.76792 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 301326.97289 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06497E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.95287 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.95287 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.95287 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.95287 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 434858.76792 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 434858.76792 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 18278.07505 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.95287 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.95287 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 434858.76792 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06497E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 18278.07505 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.52129E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47266 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47266 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9323.28862 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6466.39033 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28327E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47266 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47266 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47266 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47266 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9323.28862 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9323.28862 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 844.37135 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47266 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47266 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9323.28862 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28327E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 844.37135 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.51126 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.51126 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 89143.30647 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 61767.56130 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.18311E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.51126 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.51126 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.51126 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.51126 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89143.30647 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89143.30647 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8443.71345 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.51126 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.51126 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 89143.30647 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.18311E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8443.71345 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45993 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45993 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9083.21331 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6295.76991 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22447E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45993 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45993 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45993 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45993 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9083.21331 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9083.21331 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 844.37135 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45993 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45993 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9083.21331 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22447E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 844.37135 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.22167E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11674.03869 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.22167E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 8.66600 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.22167E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.22167E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 303129.69157 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.76847E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 5.72216 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.76847E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 14218.34844 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2179868.37385 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2179868.37000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.76847E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.22167E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 8.66600 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.61083E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4041.16534 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.61083E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4041.16534 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.22167E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.64494E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1277589.10554 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1283648.70000 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.31075E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.22167E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.64494E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1277589.10554 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1283648.70000 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.31075E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.32836E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.59403 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.32836E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3354.42556 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.32836E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59313.47152 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21419.15162 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 547168.42577 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 536325.16000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.32836E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12622 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 15.14580 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12622 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 30938.65870 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 48.50010 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1523009.00889 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.70002 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 190376.12611 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 48.50010 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1523009.00889 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.70002 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 190376.12611 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.59800E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.59800E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 21885.50 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 593219.66 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 118871.93 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18376.68 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12715.47 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20956.96 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9612.84 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 323556.66 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 212333.38 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 319947.24 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 204890.01 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 41065.09 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 26849.22 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 40675.67 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26340.31 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 49018.02 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 448024.30 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 44929.78 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 255371.94 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 227599.64 | 154654.49 | 72945.15 | 0.68 | 36550.32 | 370.71 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2150432.35 | 1451830.04 | 698602.31 | 0.68 | 340571.47 | 3454.26 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 233384.15 | 158905.27 | 74478.88 | 0.68 | 37733.17 | 382.71 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 128083.19 | 87154.65 | 40928.54 | 0.68 | 19850.97 | 201.34 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.80 | 23.21 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.80 | 23.21 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2527800026 | 0.2378038574 | Pass | Pass | 2.1930337310 | 7.1756387172 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.5494716423E-003 | 5.8195425949E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.6139169611E-003 | 6.6013886392E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.3184603704E-002 | 2.7533773826E-002 | Pass | Pass | 0.1695158171 | 0.3727496680 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.6646634669E-002 | 2.7435160064E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.7196412810E-002 | 2.8711909346E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.6739832037E-002 | 2.7554180308E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.7127104621E-002 | 2.7972487039E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.2741986778E-002 | 3.2104531914E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.3736303741E-002 | 3.3375968789E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.4439073419E-002 | 3.4530476780E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.4443054707E-002 | 3.3590540880E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1305390109 | 0.1666257783 | Pass | Pass | 6.8060146065 | 29.2566162318 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1304135122 | 0.1660420833 | Pass | Pass | 7.9502246033 | 34.0312288128 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1172096145 | 0.1434747830 | Pass | Pass | 5.7873596031 | 26.1459308015 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.8642335492E-002 | 6.0441243844E-002 | Pass | Pass | 7.4493063196 | 36.5284452967 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.0786392460E-003 | 4.4186252614E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.4989326518E-003 | 6.4852204485E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.5838651758E-002 | 4.0644380141E-002 | Pass | Pass | 0.1625066165 | 0.3602805791 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.2753959956E-006 | 8.9104410060E-006 | Pass | Pass | 2.5592492073E-003 | 1.7425744413E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1944404944E-002 | 7.1050803216E-003 | Pass | Pass | 2.8042527763E-003 | 2.5934794350E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.6767837719E-002 | 1.2384831499E-002 | Pass | Pass | 3.9954689024E-003 | 4.0803138018E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2528103433E-004 | 2.8326333255E-004 | Pass | Pass | 4.5512896435E-005 | 1.1167969918E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5337.94 | 115.49 | 0.00 | 15757.10 | 18134.59 | 39345.11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 1390.74 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.30 | 0.0000 | Y | 7.58 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.06 | 0.0000 | Y | 4.83 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.93 | 0.0000 | Y | 7.46 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.16 | 0.0000 | Y | 4.86 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.25 | 0.0000 | Y | 75.62 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.02 | 0.0000 | Y | 48.24 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.91 | 0.0000 | Y | 74.47 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.12 | 0.0000 | Y | 48.45 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.25 | 0.0000 | Y | 7.56 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.02 | 0.0000 | Y | 4.82 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.91 | 0.0000 | Y | 7.45 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.12 | 0.0000 | Y | 4.85 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 540.63 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.77 | 41.77 | 101.56 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.77 | 62.77 | 10.84 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.77 | 47.60 | 153.83 | |
Exterior Lighting Total | 31088.59 | 266.23 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2517292.89 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2179868.37 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1283648.70 | 6.59 | 1126052.58 | 5.87 | 6.80 | 23.21 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1283648.70 | 6.59 | 1126052.58 | 5.87 | 6.80 | 23.21 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 536325.16 | 0.90 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1523009.01 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1523009.01 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 205633.76 | 227599.64 | 154654.49 | 72945.15 | 0.68 | - | 36550.32 | 370.71 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1992740.54 | 2150432.35 | 1451830.04 | 698602.31 | 0.68 | - | 340571.47 | 3454.26 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 208919.27 | 233384.15 | 158905.27 | 74478.88 | 0.68 | - | 37733.17 | 382.71 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 117776.77 | 128083.19 | 87154.65 | 40928.54 | 0.68 | - | 19850.97 | 201.34 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 434858.77 | 301326.97 | 133531.80 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9323.29 | 6466.39 | 2856.90 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89143.31 | 61767.56 | 27375.75 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9083.21 | 6295.77 | 2787.44 | 0.69 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15720.71 | 21885.50 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 425976.81 | 593219.66 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 85411.63 | 118871.93 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13203.94 | 18376.68 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9136.26 | 12715.47 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15057.90 | 20956.96 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6906.99 | 9612.84 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 232479.90 | 323556.66 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 152564.43 | 212333.38 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 229886.49 | 319947.24 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 147216.29 | 204890.01 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 29505.80 | 41065.09 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19291.51 | 26849.22 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29226.00 | 40675.67 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 18925.85 | 26340.31 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 46551.00 | 49018.02 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 423219.18 | 448024.30 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 41194.84 | 44929.78 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 238392.83 | 255371.94 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 434858.77 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9323.29 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 89143.31 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9083.21 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 18278.08 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 844.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8443.71 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 844.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.69 | 18785.99 | 2160.95 | 1.00 | 1.12 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 80.80 | 174604.49 | 2160.95 | 1.00 | 1.08 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.96 | 19359.15 | 2160.95 | 1.00 | 1.12 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 4.92 | 8341.96 | 1695.65 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.95 | 36205.71 | 1649.25 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 529.42 | 1120.11 | 1.00 | 1.63 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.51 | 5053.10 | 1120.11 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 515.18 | 1120.11 | 1.00 | 1.64 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.072217 | 11674.04 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.047685 | 14218.35 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.036108 | 4041.17 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.036108 | 4041.17 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013284 | 3354.43 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.126215 | 30938.66 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 65911.33 | 65911.33 | 23.71 | 4.920 | 4.920 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00904 | 27.37 | 0.01446 | 1.200 | 0.00 |
CORE_BOTTOM | 72073.42 | 72073.42 | 28.87 | 5.380 | 5.380 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 27.37 | 0.01446 | 1.078 | 0.00 |
CORE_MID | 677436.52 | 677436.52 | 271.40 | 50.554 | 50.554 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 27.37 | 0.01446 | 10.778 | 0.00 |
CORE_TOP | 66918.51 | 66918.51 | 26.81 | 4.994 | 4.994 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 27.37 | 0.01446 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12421.37 | 12421.37 | 39.63 | 0.936 | 0.936 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00894 | 34.40 | 0.01447 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13359.09 | 13359.09 | 66.14 | 1.007 | 1.007 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00877 | 30.52 | 0.01447 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14752.90 | 14752.90 | 47.07 | 1.112 | 1.112 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00887 | 34.24 | 0.01447 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17117.26 | 17117.26 | 84.75 | 1.290 | 1.290 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00871 | 32.91 | 0.01447 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 118357.88 | 118357.88 | 377.64 | 8.920 | 8.920 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00913 | 34.40 | 0.01447 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 140429.00 | 140429.00 | 695.28 | 10.583 | 10.583 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00886 | 30.79 | 0.01447 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 142043.91 | 142043.91 | 453.21 | 10.705 | 10.705 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00903 | 34.32 | 0.01447 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 149044.06 | 149044.06 | 737.93 | 11.233 | 11.233 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00884 | 32.75 | 0.01447 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13579.38 | 13579.38 | 43.33 | 1.023 | 1.023 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00912 | 34.21 | 0.01447 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14330.31 | 14330.31 | 70.95 | 1.080 | 1.080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00890 | 31.03 | 0.01447 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15829.69 | 15829.69 | 50.51 | 1.193 | 1.193 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00904 | 34.40 | 0.01447 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16057.20 | 16057.20 | 79.50 | 1.210 | 1.210 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00885 | 32.75 | 0.01447 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 7952.03 | 7952.03 | 219.65 | 0.473 | 0.473 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 30.52 | 0.01447 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 75897.55 | 75897.55 | 2096.46 | 4.511 | 4.511 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00860 | 30.52 | 0.01447 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7737.97 | 7737.97 | 213.74 | 0.460 | 0.460 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00859 | 30.70 | 0.01447 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369342.84 | 369342.84 | 471.29 | 21.953 | 21.953 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 25.75 | 0.01446 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 23.53 | 0.00230 | -6.30 | 0.00230 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 17.60 | 21.17 | 0.00230 | -6.30 | 0.00230 | 1.078 | 0.00 |
CORE_MID | 268932.14 | 268932.14 | 107.74 | 11.758 | 11.758 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 10.778 | 0.00 |
CORE_TOP | 59818.95 | 59818.95 | 23.96 | 2.636 | 2.636 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 9248.65 | 9248.65 | 29.51 | 0.408 | 0.408 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00730 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 6398.62 | 6398.62 | 31.68 | 0.282 | 0.282 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 10544.85 | 10544.85 | 33.64 | 0.465 | 0.465 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 4840.96 | 4840.96 | 23.97 | 0.213 | 0.213 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00690 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 162738.09 | 162738.09 | 519.25 | 7.194 | 7.194 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -6.30 | 0.00230 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 106795.65 | 106795.65 | 528.76 | 4.721 | 4.721 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -6.30 | 0.00230 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 160924.90 | 160924.90 | 513.45 | 7.114 | 7.114 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -6.30 | 0.00230 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 103056.23 | 103056.23 | 510.24 | 4.556 | 4.556 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -6.30 | 0.00230 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 20650.97 | 20650.97 | 65.89 | 0.913 | 0.913 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13502.04 | 13502.04 | 66.85 | 0.597 | 0.597 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00742 | -6.30 | 0.00230 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20455.34 | 20455.34 | 65.27 | 0.905 | 0.905 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00742 | -6.30 | 0.00230 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13246.33 | 13246.33 | 65.58 | 0.586 | 0.586 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00741 | -6.30 | 0.00230 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 18.00 | 25.55 | 0.00820 | -6.30 | 0.00230 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.93 | 0.00288 | -6.30 | 0.00230 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.09 | 0.00276 | -6.30 | 0.00230 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 18.00 | 27.00 | 0.00850 | -6.30 | 0.00230 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.69 | 8.69 | 2.45 | 2.45 | 8.6934 | 2.4471 | 8.6934 | 0.2815 | 0.3000 |
VAV_MID WITH REHEAT | 80.80 | 80.80 | 35.34 | 35.34 | 80.8000 | 35.3436 | 80.8000 | 0.4374 | 0.3000 |
VAV_TOP WITH REHEAT | 8.96 | 8.96 | 5.64 | 5.64 | 8.9586 | 5.6377 | 8.9586 | 0.6293 | 0.3000 |
CAV_BAS | 4.92 | 4.92 | 1.20 | 1.20 | 4.9196 | 4.9196 | 4.9196 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.95 | 21.95 | 0.34 | 0.34 | 21.9529 | 21.9526 | 21.9529 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4727 | 0.4727 | 0.4727 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.51 | 4.51 | 0.16 | 0.16 | 4.5113 | 4.5113 | 4.5113 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4599 | 0.4599 | 0.4599 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15720.715 | 15720.715 | 1.619413 | 0.00034389 | 438.767 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15720.71 | 15720.71 | 1.619413 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 0.00 | 0.00 | 15747.70 | 15747.70 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 425976.812 | 425976.812 | 16.177394 | 0.00931825 | 14879.507 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 425976.81 | 425976.81 | 16.177394 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 268932.14 | 0.00 | 426991.92 | 426991.92 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 85411.630 | 85411.630 | 2.636338 | 0.00186838 | 3324.077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 85411.63 | 85411.63 | 2.636338 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 59818.95 | 0.00 | 85593.48 | 85593.48 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13203.936 | 13203.936 | 0.408071 | 0.00028884 | 513.454 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13203.94 | 13203.94 | 0.408071 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00730092 | 45.5620 | 9248.65 | 0.00 | 13232.05 | 13232.05 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9136.263 | 9136.263 | 0.282404 | 0.00019986 | 355.240 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9136.26 | 9136.26 | 0.282404 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00737250 | 46.0031 | 6398.62 | 0.00 | 9155.72 | 9155.72 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15057.903 | 15057.903 | 0.465466 | 0.00032939 | 585.469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15057.90 | 15057.90 | 0.465466 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00745482 | 46.5101 | 10544.85 | 0.00 | 15089.97 | 15089.97 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6906.986 | 6906.986 | 0.213327 | 0.00015109 | 268.699 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6906.99 | 6906.99 | 0.213327 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00689994 | 43.0889 | 4840.96 | 0.00 | 6921.69 | 6921.69 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 232479.902 | 232479.902 | 7.194373 | 0.00508550 | 9032.581 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 232479.90 | 232479.90 | 7.194373 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00740477 | 46.2038 | 162738.09 | 0.00 | 232975.06 | 232975.06 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 152564.431 | 152564.431 | 4.721473 | 0.00333735 | 5927.465 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 152564.43 | 152564.43 | 4.721473 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00739777 | 46.1607 | 106795.65 | 0.00 | 152889.38 | 152889.38 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 229886.492 | 229886.492 | 7.113980 | 0.00502877 | 8931.930 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 229886.49 | 229886.49 | 7.113980 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00739798 | 46.1619 | 160924.90 | 0.00 | 230376.12 | 230376.12 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 147216.286 | 147216.286 | 4.555727 | 0.00322036 | 5719.868 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 147216.29 | 147216.29 | 4.555727 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00737538 | 46.0228 | 103056.23 | 0.00 | 147529.84 | 147529.84 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 29505.803 | 29505.803 | 0.913450 | 0.00064544 | 1146.105 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29505.80 | 29505.80 | 0.913450 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00742614 | 46.3367 | 20650.97 | 0.00 | 29568.65 | 29568.65 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 19291.511 | 19291.511 | 0.597249 | 0.00042200 | 749.334 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19291.51 | 19291.51 | 0.597249 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00741620 | 46.2756 | 13502.04 | 0.00 | 19332.60 | 19332.60 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 29226.003 | 29226.003 | 0.904776 | 0.00063932 | 1135.246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29226.00 | 29226.00 | 0.904776 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00742107 | 46.3054 | 20455.34 | 0.00 | 29288.26 | 29288.26 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 18925.853 | 18925.853 | 0.585918 | 0.00041400 | 735.139 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18925.85 | 18925.85 | 0.585918 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00740589 | 46.2121 | 13246.33 | 0.00 | 18966.17 | 18966.17 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 205633.756 | -999.000 | 8.693409 | 0.00588110 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 205633.76 | 159838.08 | 8.693409 | 26.51 | 18.31 | 0.01027341 | 10.98 | 10.98 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 23.3568 | 24.00 | 0.00893429 | 46.3411 | 111447.55 | 0.00 | 210925.61 | 158243.40 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 46550.997 | 46550.997 | 2.608023 | 0.00101830 | 989.304 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46551.00 | 46551.00 | 2.608023 | -2.50 | -3.01 | 0.00286164 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 77.8559 | 21.06 | 0.00572042 | 35.6566 | 28149.65 | 0.00 | 42694.25 | 42694.25 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1992740.543 | -999.000 | 80.799995 | 0.05699213 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1992740.54 | 1511627.69 | 80.799995 | 26.79 | 18.57 | 0.01050446 | 10.98 | 10.98 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.1312 | 24.00 | 0.00905069 | 46.9371 | 1005031.54 | 0.00 | 2042630.58 | 1498105.07 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 423219.181 | 423219.181 | 24.239999 | 0.00925793 | 9029.427 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 423219.18 | 423219.18 | 24.239999 | -2.17 | -2.41 | 0.00311203 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 83.7706 | 18.09 | 0.00716170 | 53.5756 | 257780.96 | 0.00 | 390248.04 | 390248.04 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 208919.267 | -999.000 | 8.958644 | 0.00597506 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 208919.27 | 162657.90 | 8.958644 | 26.32 | 18.22 | 0.01023856 | 10.98 | 10.98 | 0.00850000 | 34.21 | 0.01447292 | 23.49 | 22.6653 | 24.00 | 0.00899297 | 46.6422 | 118535.32 | 0.00 | 214349.42 | 161000.50 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 41194.841 | 41194.841 | 2.687593 | 0.00090114 | 898.807 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 41194.84 | 41194.84 | 2.687593 | -0.34 | -0.77 | 0.00351652 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 75.5509 | 17.34 | 0.00679198 | 53.3001 | 35778.75 | 0.00 | 39140.39 | 39140.39 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 117776.765 | -999.000 | 4.919610 | 0.00336840 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 117776.77 | 88556.80 | 4.919610 | 26.48 | 18.50 | 0.01053856 | 11.37 | 11.18 | 0.00850000 | 33.16 | 0.01447100 | 23.21 | 24.3954 | 24.00 | 0.00907526 | 47.0616 | 58724.15 | 0.00 | 120771.86 | 88395.60 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 238392.829 | 238392.829 | 4.919610 | 0.00521485 | 7553.398 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 238392.83 | 238392.83 | 4.919610 | -1.54 | -3.37 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 24.3954 | 23.62 | 0.00229779 | 12.3223 | 0.00 | 0.00 | 183127.14 | 183127.14 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434858.768 | 301326.973 | 21.952873 | 0.01064966 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 403097.68 | 395518.89 | -999.0 | 28.56 | 17.68 | 0.00863407 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | -999.0000 | 27.00 | 0.00854255 | 37.1036 | 368881.15 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9323.289 | 6466.390 | 0.472655 | 0.00022833 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8635.50 | 8288.50 | -999.0 | 28.10 | 17.65 | 0.00878542 | 12.80 | 11.77 | 0.00850000 | 30.70 | 0.01446650 | 22.54 | -999.0000 | 27.00 | 0.00859105 | 37.3092 | 7950.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89143.306 | 61767.561 | 4.511264 | 0.00218311 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 82591.25 | 79122.64 | -999.0 | 28.10 | 17.66 | 0.00879887 | 12.80 | 11.77 | 0.00850000 | 30.52 | 0.01446618 | 22.49 | -999.0000 | 27.00 | 0.00859543 | 37.3282 | 75897.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9083.213 | 6295.770 | 0.459934 | 0.00022245 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8414.83 | 8067.92 | -999.0 | 28.11 | 17.66 | 0.00879320 | 12.80 | 11.77 | 0.00850000 | 30.70 | 0.01446650 | 22.54 | -999.0000 | 27.00 | 0.00859359 | 37.3202 | 7737.97 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434858.768 | 434858.768 | 21.952873 | 0.01064966 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 434858.77 | 434858.77 | 21.952873 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 1.5415 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9323.289 | 9323.289 | 0.472655 | 0.00022833 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9323.29 | 9323.29 | 0.472655 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3073 | 26.08 | 0.00819648 | 37.5960 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89143.306 | 89143.306 | 4.511264 | 0.00218311 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 89143.31 | 89143.31 | 4.511264 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.4652 | 24.05 | 0.00287703 | 15.0165 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9083.213 | 9083.213 | 0.459934 | 0.00022245 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9083.21 | 9083.21 | 0.459934 | -6.30 | -6.30 | 0.00229779 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3988 | 22.96 | 0.00276448 | 15.4173 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 18278.075 | 18278.075 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18278.08 | 18278.08 | 21.952873 | -0.10 | -0.10 | 0.00840440 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 1.5415 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 844.37 | 844.37 | 0.472655 | -0.21 | -0.21 | 0.00800139 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3073 | 26.08 | 0.00819648 | 37.5960 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8443.713 | 8443.713 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8443.71 | 8443.71 | 4.511264 | -0.22 | -1.72 | 0.00285696 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.4652 | 24.05 | 0.00287703 | 15.0165 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 844.37 | 844.37 | 0.459934 | -0.21 | -1.89 | 0.00274862 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 3.3988 | 22.96 | 0.00276448 | 15.4173 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15720.715 | 15720.715 | 1.619413 | 0.00034389 | 438.767 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 0.7069 | 0.721177 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 15720.71 | 15720.71 | 1.0000 | 1.88010057 | 1.619413 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.34385600 | 60.00 | 48.89 | 11.11 | 0.000 | 15720.71 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 0.00 | 0.00 | 15747.70 | 15747.70 | 1.88010057 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 425976.812 | 425976.812 | 16.177394 | 0.00931825 | 14879.507 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 19.1559 | 19.541401 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 425976.81 | 425976.81 | 1.0000 | 18.78157488 | 16.177394 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 9.31730403 | 60.00 | 48.89 | 11.11 | 0.000 | 425976.81 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 268932.14 | 0.00 | 426991.92 | 426991.92 | 18.78157488 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.10 | 19.69 | 0.00800000 | 55794.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 85411.630 | 85411.630 | 2.636338 | 0.00186838 | 3324.077 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 3.8409 | 3.918201 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 85411.63 | 85411.63 | 1.0000 | 3.06072633 | 2.636338 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 1.86819118 | 60.00 | 48.89 | 11.11 | 0.000 | 85411.63 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 59818.95 | 0.00 | 85593.48 | 85593.48 | 3.06072633 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13203.936 | 13203.936 | 0.408071 | 0.00028884 | 513.454 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 0.5938 | 0.605722 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13203.94 | 13203.94 | 1.0000 | 0.47376129 | 0.408071 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.28880700 | 60.00 | 48.89 | 11.11 | 0.000 | 13203.94 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00730092 | 21.00 | 0.00730092 | 45.5620 | 9248.65 | 0.00 | 13232.05 | 13232.05 | 0.47376129 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9136.263 | 9136.263 | 0.282404 | 0.00019986 | 355.240 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 0.4109 | 0.419120 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9136.26 | 9136.26 | 1.0000 | 0.32786472 | 0.282404 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.19983562 | 60.00 | 48.89 | 11.11 | 0.000 | 9136.26 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00737250 | 21.00 | 0.00737250 | 46.0031 | 6398.62 | 0.00 | 9155.72 | 9155.72 | 0.32786472 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15057.903 | 15057.903 | 0.465466 | 0.00032939 | 585.469 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 0.6771 | 0.690771 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15057.90 | 15057.90 | 1.0000 | 0.54039483 | 0.465466 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.32935844 | 60.00 | 48.89 | 11.11 | 0.000 | 15057.90 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00745482 | 21.00 | 0.00745482 | 46.5101 | 10544.85 | 0.00 | 15089.97 | 15089.97 | 0.54039483 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6906.986 | 6906.986 | 0.213327 | 0.00015109 | 268.699 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 0.3106 | 0.316853 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6906.99 | 6906.99 | 1.0000 | 0.24766765 | 0.213327 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.15107510 | 60.00 | 48.89 | 11.11 | 0.000 | 6906.99 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00689994 | 21.00 | 0.00689994 | 43.0889 | 4840.96 | 0.00 | 6921.69 | 6921.69 | 0.24766765 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 232479.902 | 232479.902 | 7.194373 | 0.00508550 | 9032.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 10.4545 | 10.664860 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 232479.90 | 232479.90 | 1.0000 | 8.35249822 | 7.194373 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 5.08498555 | 60.00 | 48.89 | 11.11 | 0.000 | 232479.90 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00740477 | 21.00 | 0.00740477 | 46.2038 | 162738.09 | 0.00 | 232975.06 | 232975.06 | 8.35249822 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60952.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 152564.431 | 152564.431 | 4.721473 | 0.00333735 | 5927.465 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 6.8607 | 6.998791 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 152564.43 | 152564.43 | 1.0000 | 5.48151881 | 4.721473 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 3.33701072 | 60.00 | 48.89 | 11.11 | 0.000 | 152564.43 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00739777 | 21.00 | 0.00739777 | 46.1607 | 106795.65 | 0.00 | 152889.38 | 152889.38 | 5.48151881 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60951.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 229886.492 | 229886.492 | 7.113980 | 0.00502877 | 8931.930 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 10.3378 | 10.545889 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 229886.49 | 229886.49 | 1.0000 | 8.25916381 | 7.113980 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 5.02826042 | 60.00 | 48.89 | 11.11 | 0.000 | 229886.49 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00739798 | 21.00 | 0.00739798 | 46.1619 | 160924.90 | 0.00 | 230376.12 | 230376.12 | 8.25916381 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60953.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 147216.286 | 147216.286 | 4.555727 | 0.00322036 | 5719.868 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 6.6202 | 6.753448 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 147216.29 | 147216.29 | 1.0000 | 5.28909203 | 4.555727 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 3.22003184 | 60.00 | 48.89 | 11.11 | 0.000 | 147216.29 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00737538 | 21.00 | 0.00737538 | 46.0228 | 103056.23 | 0.00 | 147529.84 | 147529.84 | 5.28909203 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60953.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29505.803 | 29505.803 | 0.913450 | 0.00064544 | 1146.105 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 1.3269 | 1.353559 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29505.80 | 29505.80 | 1.0000 | 1.06049357 | 0.913450 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.64537442 | 60.00 | 48.89 | 11.11 | 0.000 | 29505.80 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00742614 | 21.00 | 0.00742614 | 46.3367 | 20650.97 | 0.00 | 29568.65 | 29568.65 | 1.06049357 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60941.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19291.511 | 19291.511 | 0.597249 | 0.00042200 | 749.334 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 0.8675 | 0.884985 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19291.51 | 19291.51 | 1.0000 | 0.69339179 | 0.597249 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.42195929 | 60.00 | 48.89 | 11.11 | 0.000 | 19291.51 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00741620 | 21.00 | 0.00741620 | 46.2756 | 13502.04 | 0.00 | 19332.60 | 19332.60 | 0.69339179 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60941.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29226.003 | 29226.003 | 0.904776 | 0.00063932 | 1135.246 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 1.3143 | 1.340723 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29226.00 | 29226.00 | 1.0000 | 1.05042382 | 0.904776 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.63925441 | 60.00 | 48.89 | 11.11 | 0.000 | 29226.00 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00742107 | 21.00 | 0.00742107 | 46.3054 | 20455.34 | 0.00 | 29288.26 | 29288.26 | 1.05042382 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60942.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18925.853 | 18925.853 | 0.585918 | 0.00041400 | 735.139 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 0.8511 | 0.868211 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18925.85 | 18925.85 | 1.0000 | 0.68023760 | 0.585918 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.41396134 | 60.00 | 48.89 | 11.11 | 0.000 | 18925.85 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00740589 | 21.00 | 0.00740589 | 46.2121 | 13246.33 | 0.00 | 18966.17 | 18966.17 | 0.68023760 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60941.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 205633.756 | -999.000 | 8.693409 | 0.00588110 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9378 | 1004.8586 | 1.1610 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.693409 | 10.09284395 | 4197.9300 | 999.8980 | 72.20932497 | 15.00 | 6.67 | 8.33 | 2525070.33 | 8.1437 | 8.143684 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 205633.76 | 159838.08 | 1.0000 | 10.09284395 | 8.693409 | 26.51 | 18.31 | 0.01027341 | 52841.1 | 10.98 | 10.98 | 0.00850000 | 32466.9 | 5.88049946 | 6.67 | 15.00 | 8.33 | 18785.994 | 186847.76 | 34.40 | 0.01447326 | 23.54 | 2.03050000 | 23.3568 | 24.00 | 0.00893429 | 24.00 | 0.00893429 | 46.3411 | 111447.55 | 0.00 | 210925.61 | 158243.40 | 10.09284395 | 26.51 | 18.70 | 0.01027341 | 52841.1 | 11.20 | 11.13 | 0.00820352 | 31942.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 46550.997 | 46550.997 | 2.608023 | 0.00101830 | 989.304 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.693409 | 10.09284395 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 2.0934 | 2.135496 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 46551.00 | 46551.00 | 1.0000 | 3.02785318 | 2.608023 | -2.50 | -3.01 | 0.00286164 | 4631.5 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 1.01820048 | 60.00 | 48.89 | 11.11 | 0.000 | 46551.00 | -6.30 | 0.00229779 | -6.30 | 2.03050000 | 77.8559 | 10.86 | 0.00484405 | 21.06 | 0.00572042 | 35.6566 | 28149.65 | 0.00 | 42694.25 | 42694.25 | 3.02785318 | 2.80 | 0.32 | 0.00286164 | 9985.2 | 16.76 | 7.74 | 0.00286164 | 24085.7 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1992740.543 | -999.000 | 80.799995 | 0.05699213 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3673 | 1004.8586 | 1.1610 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.799995 | 93.80689890 | 4197.9300 | 999.8980 | 72.20932497 | 15.00 | 6.67 | 8.33 | 2525070.33 | 78.9182 | 78.918219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1992740.54 | 1511627.69 | 1.0000 | 93.80689890 | 80.799995 | 26.79 | 18.57 | 0.01050446 | 53710.7 | 10.98 | 10.98 | 0.00850000 | 32467.6 | 56.98631348 | 6.67 | 15.00 | 8.33 | 174604.487 | 1818136.06 | 34.40 | 0.01447326 | 23.54 | 20.30600000 | 25.1312 | 24.00 | 0.00905069 | 24.00 | 0.00905069 | 46.9371 | 1005031.54 | 0.00 | 2042630.58 | 1498105.07 | 93.80689890 | 26.79 | 18.97 | 0.01050446 | 53710.7 | 11.20 | 11.12 | 0.00820259 | 31935.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 423219.181 | 423219.181 | 24.239999 | 0.00925793 | 9029.427 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.799995 | 93.80689890 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 19.0319 | 19.414896 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 423219.18 | 423219.18 | 1.0000 | 28.14206967 | 24.239999 | -2.17 | -2.41 | 0.00311203 | 5594.0 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 9.25698694 | 60.00 | 48.89 | 11.11 | 0.000 | 423219.18 | -6.30 | 0.00229779 | -6.30 | 20.30600000 | 83.7706 | 19.17 | 0.00731486 | 18.09 | 0.00716170 | 53.5756 | 257780.96 | 0.00 | 390248.04 | 390248.04 | 28.14206967 | 2.80 | 0.69 | 0.00311203 | 10612.8 | 16.52 | 7.92 | 0.00311203 | 24479.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 208919.267 | -999.000 | 8.958644 | 0.00597506 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8730 | 1004.8586 | 1.1610 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.958644 | 10.40077573 | 4197.9300 | 999.8980 | 72.20932497 | 15.00 | 6.67 | 8.33 | 2525070.33 | 8.2738 | 8.273800 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 208919.27 | 162657.90 | 1.0000 | 10.40077573 | 8.958644 | 26.32 | 18.22 | 0.01023856 | 52553.6 | 10.98 | 10.98 | 0.00850000 | 32466.8 | 5.97445506 | 6.67 | 15.00 | 8.33 | 19359.153 | 189560.11 | 34.21 | 0.01447292 | 23.49 | 2.03050000 | 22.6653 | 24.00 | 0.00899297 | 24.00 | 0.00899297 | 46.6422 | 118535.32 | 0.00 | 214349.42 | 161000.50 | 10.40077573 | 26.32 | 18.61 | 0.01023856 | 52553.6 | 11.20 | 11.13 | 0.00820453 | 31944.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 41194.841 | 41194.841 | 2.687593 | 0.00090114 | 898.807 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.958644 | 10.40077573 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 1.8525 | 1.889786 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 41194.84 | 41194.84 | 1.0000 | 3.12023272 | 2.687593 | -0.34 | -0.77 | 0.00351652 | 8452.1 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 0.90104637 | 60.00 | 48.89 | 11.11 | 0.000 | 41194.84 | -6.30 | 0.00229779 | -6.30 | 2.03050000 | 75.5509 | 18.08 | 0.00728254 | 17.34 | 0.00679198 | 53.3001 | 35778.75 | 0.00 | 39140.39 | 39140.39 | 3.12023272 | 2.80 | 1.27 | 0.00351652 | 11626.5 | 15.20 | 7.77 | 0.00351652 | 24170.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 117776.765 | -999.000 | 4.919610 | 0.00336840 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4307 | 1004.8586 | 1.1610 | CAV_BAS FAN | Fan:ConstantVolume | 4.919610 | 5.71155123 | 4197.9300 | 999.8980 | 72.20932497 | 15.00 | 6.67 | 8.33 | 2525070.33 | 4.6643 | 4.664296 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 117776.77 | 88556.80 | 1.0000 | 5.71155123 | 4.919610 | 26.48 | 18.50 | 0.01053856 | 53487.9 | 11.37 | 11.18 | 0.00850000 | 32867.1 | 3.36805696 | 6.67 | 15.00 | 8.33 | 8341.957 | 109434.81 | 33.16 | 0.01447100 | 23.21 | 1.20015641 | 24.3954 | 24.00 | 0.00907526 | 24.00 | 0.00907526 | 47.0616 | 58724.15 | 0.00 | 120771.86 | 88395.60 | 5.71155123 | 26.48 | 18.90 | 0.01053856 | 53487.9 | 11.38 | 11.29 | 0.00829100 | 32342.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 238392.829 | 238392.829 | 4.919610 | 0.00521485 | 7553.398 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | CAV_BAS FAN | Fan:ConstantVolume | 4.919610 | 5.71155123 | 4197.9300 | 999.8980 | 47.67981692 | 48.89 | 60.00 | 11.11 | 2223739.09 | 10.7204 | 10.936111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 238392.83 | 238392.83 | 1.0000 | 5.71155123 | 4.919610 | -1.54 | -3.37 | 0.00229779 | 4195.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 5.21431778 | 60.00 | 48.89 | 11.11 | 0.000 | 238392.83 | -6.30 | 0.00229779 | -6.30 | 1.20015641 | 24.3954 | 0.00 | 0.00229779 | 23.62 | 0.00229779 | 12.3223 | 0.00 | 0.00 | 183127.14 | 183127.14 | 5.71155123 | 12.80 | 5.08 | 0.00229779 | 18663.3 | 44.57 | 18.23 | 0.00229779 | 50725.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 434858.768 | 301326.973 | 21.952873 | 0.01064966 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8903 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 403097.68 | 395518.89 | 0.9270 | -999.0 | -999.0 | 28.56 | 17.68 | 0.00863407 | 50746.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 403097.68 | 34.40 | 0.01447326 | 23.54 | 0.33839277 | -999.0000 | 27.00 | 0.00854255 | 27.00 | 0.00854255 | 37.1036 | 368881.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9323.289 | 6466.390 | 0.472655 | 0.00022833 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1717 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8635.50 | 8288.50 | 0.9262 | -999.0 | -999.0 | 28.10 | 17.65 | 0.00878542 | 50668.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8635.50 | 30.70 | 0.01446650 | 22.54 | 0.01563234 | -999.0000 | 27.00 | 0.00859105 | 27.00 | 0.00859105 | 37.3092 | 7950.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89143.306 | 61767.561 | 4.511264 | 0.00218311 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1967 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 82591.25 | 79122.64 | 0.9265 | -999.0 | -999.0 | 28.10 | 17.66 | 0.00879887 | 50702.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82591.25 | 30.52 | 0.01446618 | 22.49 | 0.15632344 | -999.0000 | 27.00 | 0.00859543 | 27.00 | 0.00859543 | 37.3282 | 75897.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9083.213 | 6295.770 | 0.459934 | 0.00022245 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1861 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8414.83 | 8067.92 | 0.9264 | -999.0 | -999.0 | 28.11 | 17.66 | 0.00879320 | 50692.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8414.83 | 30.70 | 0.01446650 | 22.54 | 0.01563234 | -999.0000 | 27.00 | 0.00859359 | 27.00 | 0.00859359 | 37.3202 | 7737.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 434858.768 | 434858.768 | 21.952873 | 0.01064966 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 434858.77 | 434858.77 | 1.0000 | 25.48677089 | 21.952873 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 434858.77 | -6.30 | 0.00229779 | -6.30 | 0.33839277 | 1.5415 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9323.289 | 9323.289 | 0.472655 | 0.00022833 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9323.29 | 9323.29 | 1.0000 | 0.54874137 | 0.472655 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9323.29 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.3073 | 0.00 | 0.00819648 | 26.08 | 0.00819648 | 37.5960 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89143.306 | 89143.306 | 4.511264 | 0.00218311 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 89143.31 | 89143.31 | 1.0000 | 5.23747177 | 4.511264 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89143.31 | -6.30 | 0.00229779 | -6.30 | 0.15632344 | 3.4652 | 0.00 | 0.00287703 | 24.05 | 0.00287703 | 15.0165 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9083.213 | 9083.213 | 0.459934 | 0.00022245 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9083.21 | 9083.21 | 1.0000 | 0.53397225 | 0.459934 | -6.30 | -6.30 | 0.00229779 | -610.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9083.21 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.3988 | 0.00 | 0.00276448 | 22.96 | 0.00276448 | 15.4173 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18278.075 | 18278.075 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.952873 | 25.48677089 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 18278.08 | 18278.08 | 1.0000 | 25.48677089 | 21.952873 | -0.10 | -0.10 | 0.00840440 | 20919.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18278.08 | -6.30 | 0.00229779 | -6.30 | 0.33839277 | 1.5415 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.9155 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.472655 | 0.54874137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 844.37 | 844.37 | 1.0000 | 0.54874137 | 0.472655 | -0.21 | -0.21 | 0.00800139 | 19798.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 844.37 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.3073 | 0.00 | 0.00819648 | 26.08 | 0.00819648 | 37.5960 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8443.713 | 8443.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.511264 | 5.23747177 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8443.71 | 8443.71 | 1.0000 | 5.23747177 | 4.511264 | -0.22 | -1.72 | 0.00285696 | 6924.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8443.71 | -6.30 | 0.00229779 | -6.30 | 0.15632344 | 3.4652 | 0.00 | 0.00287703 | 24.05 | 0.00287703 | 15.0165 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 844.371 | 844.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.459934 | 0.53397225 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 844.37 | 844.37 | 1.0000 | 0.53397225 | 0.459934 | -0.21 | -1.89 | 0.00274862 | 6657.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 844.37 | -6.30 | 0.00229779 | -6.30 | 0.01563234 | 3.3988 | 0.00 | 0.00276448 | 22.96 | 0.00276448 | 15.4173 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.69 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 80.80 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.96 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 4.92 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialEnthalpy | 0.34 | 21.95 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3531.00 | 2216.83 | 1406.17 |
CORE_BOTTOM | 3527.33 | 856.00 | 41.67 |
CORE_MID | 2979.67 | 2201.17 | 123.17 |
CORE_TOP | 3157.00 | 2814.33 | 564.83 |
PERIMETER_BOT_ZN_3 | 3156.50 | 2456.17 | 349.83 |
PERIMETER_BOT_ZN_2 | 3234.83 | 2352.67 | 396.17 |
PERIMETER_BOT_ZN_1 | 3465.67 | 1958.50 | 360.83 |
PERIMETER_BOT_ZN_4 | 3934.50 | 1454.83 | 512.83 |
PERIMETER_MID_ZN_3 | 3479.00 | 3376.83 | 1260.17 |
PERIMETER_MID_ZN_2 | 3008.17 | 2636.50 | 1009.17 |
PERIMETER_MID_ZN_1 | 3446.17 | 2539.00 | 775.00 |
PERIMETER_MID_ZN_4 | 3559.00 | 2874.00 | 961.17 |
PERIMETER_TOP_ZN_3 | 3815.00 | 3593.00 | 1758.00 |
PERIMETER_TOP_ZN_2 | 3816.67 | 3215.17 | 1489.67 |
PERIMETER_TOP_ZN_1 | 3616.17 | 2898.50 | 1165.00 |
PERIMETER_TOP_ZN_4 | 3779.83 | 3152.50 | 1347.00 |
DATACENTER_BOT_ZN_6 | 5933.67 | 786.00 | 786.00 |
DATACENTER_MID_ZN_6 | 5656.33 | 165.83 | 129.00 |
DATACENTER_TOP_ZN_6 | 5321.50 | 449.50 | 240.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5486.50 | 5486.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5941.67 | 5884.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 61.17 | 0.00 | 7.00 |
CORE_BOTTOM | 0.00 | 1.33 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 5.67 | 0.00 | 0.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 7.00 | 0.00 | 4.83 |
PERIMETER_BOT_ZN_2 | 0.17 | 41.33 | 0.00 | 39.67 |
PERIMETER_BOT_ZN_1 | 0.33 | 51.00 | 0.00 | 46.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 176.83 | 0.00 | 75.83 |
PERIMETER_MID_ZN_3 | 28.67 | 3.67 | 6.33 | 2.50 |
PERIMETER_MID_ZN_2 | 29.67 | 44.33 | 0.50 | 40.67 |
PERIMETER_MID_ZN_1 | 12.67 | 46.67 | 1.17 | 45.17 |
PERIMETER_MID_ZN_4 | 11.00 | 54.83 | 0.83 | 29.33 |
PERIMETER_TOP_ZN_3 | 112.00 | 19.33 | 35.83 | 12.83 |
PERIMETER_TOP_ZN_2 | 59.33 | 53.00 | 6.17 | 43.17 |
PERIMETER_TOP_ZN_1 | 47.50 | 45.33 | 8.33 | 37.83 |
PERIMETER_TOP_ZN_4 | 35.50 | 60.67 | 6.17 | 30.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 79.17 | 0.00 | 71.67 |
DATACENTER_MID_ZN_6 | 0.00 | 61.17 | 0.00 | 57.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 51.00 | 0.00 | 44.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 458.67 | 0.00 | 401.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 133.00 | 796.83 | 37.17 | 579.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 149.60 | 6779.02 | 1.101 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.50 | 134.35 | 6849.35 | 0.764 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.50 | 134.35 | 6849.35 | 0.601 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.50 | 134.35 | 6849.35 | 0.578 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.97 | 16.87 | 860.00 | 0.724 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.49 | 10.87 | 554.22 | 0.939 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.97 | 16.87 | 860.02 | 1.040 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.49 | 10.87 | 554.22 | 1.495 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.97 | 16.87 | 860.00 | 0.644 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.92 | 10.87 | 554.22 | 0.838 | 0.111 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.97 | 16.87 | 860.02 | 0.973 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.49 | 10.87 | 554.22 | 0.949 | 0.105 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.97 | 16.87 | 860.00 | 0.650 | 0.126 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.49 | 10.87 | 554.22 | 0.913 | 0.130 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.97 | 16.87 | 860.02 | 0.954 | 0.126 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.49 | 10.87 | 554.22 | 0.949 | 0.130 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.43 | 42.18 | 1911.37 | 19.752 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.92 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.43 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.80 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.92 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.43 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1024.28 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 44841534.03 | 0.00 | 44841534.03 | 0.00 | 44841534.03 | 37848132.68 | 4095.16 | 1753.25 | 2911.58 | 192.56 |
CORE_BOTTOM | 31659392.67 | 0.00 | 31659392.67 | 0.00 | 31659392.67 | 33990283.35 | 5457.68 | 66.46 | 3235.86 | 215.43 |
CORE_MID | 0.24E+09 | 0.00 | 0.24E+09 | 0.00 | 0.24E+09 | 0.34E+09 | 5719.33 | 305.54 | 2735.14 | 135.80 |
CORE_TOP | 23401982.52 | 0.00 | 23401982.52 | 0.00 | 23401982.52 | 33990283.35 | 5812.98 | 564.20 | 2382.82 | 193.87 |
PERIMETER_BOT_ZN_3 | 3761899.03 | 0.00 | 3761899.03 | 439326.30 | 4201225.33 | 4267819.30 | 4880.44 | 112.68 | 3766.88 | 215.43 |
PERIMETER_BOT_ZN_2 | 3115948.09 | 0.00 | 3115948.09 | 292884.00 | 3408832.09 | 2750345.05 | 4782.81 | 101.73 | 3875.46 | 215.43 |
PERIMETER_BOT_ZN_1 | 5348416.77 | 0.00 | 5348416.77 | 439326.30 | 5787743.07 | 4267912.63 | 4564.48 | 103.68 | 4091.84 | 215.43 |
PERIMETER_BOT_ZN_4 | 4950962.84 | 0.00 | 4950962.84 | 292884.00 | 5243846.84 | 2750345.05 | 4264.67 | 113.21 | 4382.12 | 215.43 |
PERIMETER_MID_ZN_3 | 32888565.23 | 0.00 | 32888565.23 | 1030333.47 | 33918898.69 | 42678193.03 | 4639.51 | 264.58 | 3855.90 | 135.80 |
PERIMETER_MID_ZN_2 | 28013505.04 | 0.00 | 28013505.04 | 686888.51 | 28700393.55 | 27503450.52 | 4774.94 | 186.83 | 3798.23 | 755.22 |
PERIMETER_MID_ZN_1 | 49300647.76 | 0.00 | 49300647.76 | 1030333.47 | 50330981.23 | 42679126.28 | 4339.76 | 240.27 | 4179.98 | 135.80 |
PERIMETER_MID_ZN_4 | 31039347.55 | 0.00 | 31039347.55 | 686888.51 | 31726236.06 | 27503450.52 | 4432.43 | 471.92 | 3855.66 | 135.80 |
PERIMETER_TOP_ZN_3 | 3306892.82 | 0.00 | 3306892.82 | 1279256.65 | 4586149.47 | 4267819.30 | 4481.72 | 600.63 | 3677.65 | 193.87 |
PERIMETER_TOP_ZN_2 | 2976915.81 | 0.00 | 2976915.81 | 852837.19 | 3829753.00 | 2750345.05 | 4374.77 | 576.09 | 3809.14 | 193.71 |
PERIMETER_TOP_ZN_1 | 4826130.79 | 0.00 | 4826130.79 | 1279256.65 | 6105387.44 | 4267912.63 | 4344.16 | 595.92 | 3819.92 | 193.87 |
PERIMETER_TOP_ZN_4 | 3095996.18 | 0.00 | 3095996.18 | 852837.19 | 3948833.36 | 2750345.05 | 4358.19 | 582.22 | 3819.59 | 193.71 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 10671554.30 | 1535.72 | 1562.44 | 5661.83 | 1840.17 |
Total Facility | 0.43E+10 | 0.00 | 0.43E+10 | 40073047.80 | 0.44E+10 | 0.50E+10 | 7111.15 | 4356.71 | 7347.43 | 2554.31 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.0298 | 0.0000 | 2.0298 | 0.0000 | 2.0298 | 1.2002 | 1389.09 | 1751.68 | 2802.23 |
CORE_BOTTOM | 1.4230 | 0.0000 | 1.4230 | 0.0000 | 1.4230 | 1.0778 | 2811.72 | 65.93 | 3065.35 |
CORE_MID | 11.1965 | 0.0000 | 11.1965 | 0.0000 | 11.1965 | 10.7782 | 2956.73 | 305.17 | 2681.10 |
CORE_TOP | 1.0788 | 0.0000 | 1.0788 | 0.0000 | 1.0788 | 1.0778 | 3029.36 | 564.20 | 2349.43 |
PERIMETER_BOT_ZN_3 | 0.1695 | 0.0000 | 0.1695 | 0.0102 | 0.1797 | 0.1353 | 2230.47 | 112.04 | 3600.49 |
PERIMETER_BOT_ZN_2 | 0.1416 | 0.0000 | 0.1416 | 0.0068 | 0.1483 | 0.0872 | 2133.13 | 101.06 | 3708.81 |
PERIMETER_BOT_ZN_1 | 0.2436 | 0.0000 | 0.2436 | 0.0102 | 0.2538 | 0.1353 | 1914.94 | 102.90 | 3925.16 |
PERIMETER_BOT_ZN_4 | 0.2254 | 0.0000 | 0.2254 | 0.0068 | 0.2322 | 0.0872 | 1616.27 | 112.84 | 4213.89 |
PERIMETER_MID_ZN_3 | 1.5099 | 0.0000 | 1.5099 | 0.0239 | 1.5337 | 1.3533 | 1880.41 | 263.97 | 3798.62 |
PERIMETER_MID_ZN_2 | 1.2643 | 0.0000 | 1.2643 | 0.0169 | 1.2812 | 0.8721 | 1617.14 | 181.90 | 3234.96 |
PERIMETER_MID_ZN_1 | 2.2777 | 0.0000 | 2.2777 | 0.0239 | 2.3016 | 1.3533 | 1579.47 | 239.62 | 4123.91 |
PERIMETER_MID_ZN_4 | 1.4310 | 0.0000 | 1.4310 | 0.0159 | 1.4469 | 0.8721 | 1673.20 | 470.84 | 3798.96 |
PERIMETER_TOP_ZN_3 | 0.1525 | 0.0000 | 0.1525 | 0.0297 | 0.1821 | 0.1353 | 1701.24 | 600.17 | 3641.59 |
PERIMETER_TOP_ZN_2 | 0.1378 | 0.0000 | 0.1378 | 0.0198 | 0.1575 | 0.0872 | 1595.97 | 575.68 | 3771.35 |
PERIMETER_TOP_ZN_1 | 0.2236 | 0.0000 | 0.2236 | 0.0297 | 0.2532 | 0.1353 | 1562.67 | 595.76 | 3784.57 |
PERIMETER_TOP_ZN_4 | 0.1431 | 0.0000 | 0.1431 | 0.0198 | 0.1629 | 0.0872 | 1576.76 | 582.17 | 3784.07 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.1855 | 0.0000 | 10.1855 | 0.0000 | 10.1855 | 0.3384 | 558.89 | 1562.44 | 3821.67 |
Total Facility | 194.1126 | 0.0000 | 194.1126 | 0.9383 | 195.0510 | 158.4706 | 4294.15 | 4351.26 | 5418.18 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 65818184.31 | 0.00 | 65818184.31 | 48026705.38 | 3915.98 | 4.11 | 4839.91 | 215.43 |
VAV_MID WITH REHEAT | 0.52E+09 | 0.00 | 0.52E+09 | 0.48E+09 | 4133.31 | 2.95 | 4623.74 | 135.80 |
VAV_TOP WITH REHEAT | 50688616.56 | 0.00 | 50688616.56 | 48026705.38 | 4202.37 | 3.51 | 4554.12 | 193.65 |
CAV_BAS | 60440402.76 | 0.00 | 60440402.76 | 37848132.68 | 4064.37 | 1.60 | 4694.03 | 192.56 |
AIRLOOP DATACENTER BASEMENT | 0.41E+09 | 0.00 | 0.41E+09 | 10671554.30 | 1535.72 | 0.00 | 7224.28 | 1840.17 |
AIRLOOP DATACENTER BOT | 329278.43 | 0.00 | 329278.43 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3292784.26 | 0.00 | 3292784.26 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 329278.43 | 0.00 | 329278.43 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.9691 | 0.0000 | 2.9691 | 1.5229 | 1292.85 | 1.88 | 4648.26 |
VAV_MID WITH REHEAT | 23.8642 | 0.0000 | 23.8642 | 15.2292 | 1373.08 | 2.80 | 4567.11 |
VAV_TOP WITH REHEAT | 2.3393 | 0.0000 | 2.3393 | 1.5229 | 1422.22 | 3.33 | 4517.45 |
CAV_BAS | 2.7359 | 0.0000 | 2.7359 | 1.2002 | 1377.16 | 0.56 | 4565.29 |
AIRLOOP DATACENTER BASEMENT | 13.7287 | 0.0000 | 13.7287 | 0.3384 | 558.89 | 0.00 | 5384.11 |
AIRLOOP DATACENTER BOT | 0.0154 | 0.0000 | 0.0154 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1539 | 0.0000 | 0.1539 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0154 | 0.0000 | 0.0154 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 432.49 | 2481.93 | 0.00 | 0.00 | 0.00 | 2003.60 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 301.16 | 2221.93 | 0.00 | 0.00 | 0.00 | 2271.14 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 64.23 | 2301.47 | 0.00 | 0.00 | 0.00 | 2496.25 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1744.93 | 3034.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1562.44 | 5661.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.7171 | 5.2847 | 0.0000 | 0.0000 | 0.0000 | 2.2422 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.9737 | 39.8938 | 0.0000 | 0.0000 | 0.0000 | 22.2434 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.6117 | 3.9242 | 0.0000 | 0.0000 | 0.0000 | 2.1893 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6185 | 4.7280 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4562 | 21.1665 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0211 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2108 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0211 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1525 |
Defaulted Fields | 1187 |
Fields with Defaults | 3945 |
Autosized Fields | 336 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25278.84 | 290741.79 | 01-JAN-04:00 | 1727711.55 | 17-APR-15:40 |
Electricity:Building | 16392.13 | 215366.33 | 07-MAY-17:10 | 943583.07 | 06-DEC-08:10 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16392.13 | 215366.33 | 07-MAY-17:10 | 943583.07 | 06-DEC-08:10 |
InteriorLights:Electricity | 1715.74 | 8110.17 | 01-JAN-10:50 | 169602.33 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1715.74 | 8110.17 | 01-JAN-10:50 | 169602.33 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 1715.74 | 8110.17 | 01-JAN-10:50 | 169602.33 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1715.74 | 8110.17 | 01-JAN-10:50 | 169602.33 | 30-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.95 | 589.50 | 12-MAR-17:10 | 3304.82 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.58 | 30.32 | 01-JAN-10:50 | 1144.27 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.58 | 30.32 | 01-JAN-10:50 | 1144.27 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.27 | 379.89 | 26-MAR-17:10 | 2129.74 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.83 | 19.54 | 01-JAN-09:00 | 737.40 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.83 | 19.54 | 01-JAN-09:00 | 737.40 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.82 | 589.50 | 12-MAR-17:10 | 3304.88 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.46 | 30.33 | 01-JAN-09:10 | 1144.30 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.46 | 30.33 | 01-JAN-09:10 | 1144.30 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.29 | 379.89 | 20-FEB-18:10 | 2129.73 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.86 | 19.54 | 01-JAN-10:40 | 737.40 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.86 | 19.54 | 01-JAN-10:40 | 737.40 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 439.28 | 5894.96 | 12-MAR-17:10 | 33047.93 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.63 | 303.25 | 01-JAN-10:50 | 11442.41 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.63 | 303.25 | 01-JAN-10:50 | 11442.41 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.60 | 3798.93 | 12-MAR-17:10 | 21296.89 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.24 | 195.42 | 01-JAN-09:00 | 7373.47 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.24 | 195.42 | 01-JAN-09:00 | 7373.47 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 438.13 | 5895.05 | 12-MAR-17:10 | 33048.51 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.47 | 303.26 | 01-JAN-09:10 | 11442.66 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.47 | 303.26 | 01-JAN-09:10 | 11442.66 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.81 | 3798.91 | 20-FEB-18:10 | 21296.80 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.45 | 195.42 | 01-JAN-10:40 | 7373.47 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.45 | 195.42 | 01-JAN-10:40 | 7373.47 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.93 | 589.50 | 12-MAR-17:10 | 3304.79 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.56 | 30.32 | 01-JAN-10:50 | 1144.23 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.56 | 30.32 | 01-JAN-10:50 | 1144.23 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.26 | 379.89 | 12-MAR-17:10 | 2129.69 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.82 | 19.54 | 01-JAN-09:00 | 737.34 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.82 | 19.54 | 01-JAN-09:00 | 737.34 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.81 | 589.50 | 12-MAR-17:10 | 3304.84 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.45 | 30.33 | 01-JAN-09:10 | 1144.26 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.45 | 30.33 | 01-JAN-09:10 | 1144.26 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.28 | 379.89 | 20-FEB-18:10 | 2129.68 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.85 | 19.54 | 01-JAN-10:40 | 737.34 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.85 | 19.54 | 01-JAN-10:40 | 737.34 | 30-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2697.90 | 3480.15 | 08-JAN-05:10 | 369563.66 | 03-AUG-12:10 |
HeatRejection:Electricity | 1014.48 | 119.32 | 10-JAN-08:00 | 79310.05 | 16-MAY-16:00 |
General:HeatRejection:Electricity | 1014.48 | 119.32 | 10-JAN-08:00 | 79310.05 | 16-MAY-16:00 |
ElectricityProduced:Facility | 524.78 | -0.00 | 07-FEB-17:40 | 87760.65 | 06-APR-12:40 |
ElectricityProduced:Plant | 524.78 | -0.00 | 07-FEB-17:40 | 87760.65 | 06-APR-12:40 |
Photovoltaic:ElectricityProduced | 548.16 | 0.00 | 01-JAN-00:10 | 91398.42 | 06-APR-12:40 |
PowerConversion:ElectricityProduced | -23.39 | -3637.77 | 06-APR-12:40 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 4773.24 | 44487.31 | 01-JAN-03:50 | 445024.05 | 17-APR-15:50 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73700.58 | 30-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3371.98 | 30-OCT-07:20 |
ElectricityPurchased:Facility | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
ElectricityPurchased:Plant | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
Cogeneration:ElectricityPurchased | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
General:Cogeneration:ElectricityPurchased | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
ElectricityNet:Plant | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
Cogeneration:ElectricityNet | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
General:Cogeneration:ElectricityNet | 24754.06 | 285417.44 | 01-JAN-11:50 | 1671622.28 | 17-APR-15:40 |
Fans:Electricity | 2248.70 | 42303.41 | 28-JAN-05:20 | 246688.59 | 15-MAY-14:50 |
General:Fans:Electricity | 2248.70 | 42303.41 | 28-JAN-05:20 | 246688.59 | 15-MAY-14:50 |
ExteriorLights:Electricity | 266.23 | 0.00 | 01-JAN-07:50 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 266.23 | 0.00 | 01-JAN-07:50 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
HeatRecovery:Electricity | 39.13 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 39.13 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
Cooling:Electricity | 2694.26 | 1202.53 | 01-JAN-03:30 | 401101.85 | 03-AUG-12:10 |
General:Cooling:Electricity | 2694.26 | 1202.53 | 01-JAN-03:30 | 401101.85 | 03-AUG-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 959.90 | 0.00 | 01-JAN-02:20 | 100000.00 | 29-JAN-13:30 |
General:Humidifier:Electricity | 959.90 | 0.00 | 01-JAN-02:20 | 100000.00 | 29-JAN-13:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 460.31 | 3354.43 | 01-JAN-00:10 | 46863.08 | 30-MAR-13:50 |
General:Pumps:Electricity | 460.31 | 3354.43 | 01-JAN-00:10 | 46863.08 | 30-MAR-13:50 |
WIRED_LTG_ELECTRICITY | 48.21 | 0.00 | 01-JAN-00:10 | 4765.83 | 30-OCT-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1109.89 | 7280.88 | 09-APR-16:30 | 1337808.05 | 13-FEB-07:10 |
NaturalGas:Plant | 1109.89 | 7280.88 | 09-APR-16:30 | 1337808.05 | 13-FEB-07:10 |
Heating:NaturalGas | 402.61 | 0.00 | 01-JAN-00:10 | 1307065.00 | 13-FEB-07:10 |
Boiler:Heating:NaturalGas | 402.61 | 0.00 | 01-JAN-00:10 | 1307065.00 | 13-FEB-07:10 |
WaterSystems:NaturalGas | 707.28 | 7280.88 | 02-JAN-05:20 | 81280.70 | 02-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 707.28 | 7280.88 | 02-JAN-05:20 | 81280.70 | 02-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 15180.64 | 2859.10 | 18-JAN-08:20 | 2312063.44 | 25-AUG-14:00 |
PlantLoopCoolingDemand:HVAC | 15180.64 | 2859.10 | 18-JAN-08:20 | 2312063.44 | 25-AUG-14:00 |
CoolingCoils:PlantLoopCoolingDemand | 15180.64 | 2859.10 | 18-JAN-08:20 | 2312063.44 | 25-AUG-14:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9416.90 | 0.00 | 01-JAN-02:20 | 0.00 | 13-APR-15:30 |
Water:HVAC | 357.08 | 0.00 | 01-JAN-02:20 | 0.00 | 01-FEB-05:10 |
Humidifier:Water | 357.08 | 0.00 | 01-JAN-02:20 | 0.00 | 01-FEB-05:10 |
General:Humidifier:Water | 357.08 | 0.00 | 01-JAN-02:20 | 0.00 | 01-FEB-05:10 |
MainsWater:Facility | 9416.90 | 0.00 | 01-JAN-02:20 | 0.00 | 13-APR-15:30 |
MainsWater:HVAC | 357.08 | 0.00 | 01-JAN-02:20 | 0.00 | 01-FEB-05:10 |
Humidifier:MainsWater | 357.08 | 0.00 | 01-JAN-02:20 | 0.00 | 01-FEB-05:10 |
General:Humidifier:MainsWater | 357.08 | 0.00 | 01-JAN-02:20 | 0.00 | 01-FEB-05:10 |
Water:Plant | 9059.82 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-15:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 9059.82 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-15:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 6779.65 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-15:30 |
General:HeatRejection:Water | 6779.65 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-15:30 |
HeatRejection:MainsWater | 6779.65 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-15:30 |
General:HeatRejection:MainsWater | 6779.65 | 0.00 | 01-JAN-00:10 | 0.00 | 13-APR-15:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 60717.92 | 93476.80 | 09-JAN-04:30 | 9227461.04 | 25-AUG-13:50 |
EnergyTransfer:Building | 17928.19 | 87748.19 | 14-JAN-19:50 | 1499977.45 | 02-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 585.18 | 0.00 | 01-JAN-00:10 | 72495.44 | 13-NOV-06:20 |
Heating:EnergyTransfer | 318.12 | 0.00 | 19-JAN-22:10 | 901612.04 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.22 | 0.00 | 01-JAN-00:10 | 23219.54 | 08-JUL-16:10 |
General:Heating:EnergyTransfer | 318.12 | 0.00 | 19-JAN-22:10 | 901612.04 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.22 | 0.00 | 01-JAN-00:10 | 23219.54 | 08-JUL-16:10 |
Cooling:EnergyTransfer | 17610.07 | 84927.08 | 09-JAN-05:40 | 1499977.45 | 02-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 581.96 | 0.00 | 01-JAN-00:10 | 72495.44 | 13-NOV-06:20 |
General:Cooling:EnergyTransfer | 17610.07 | 84927.08 | 09-JAN-05:40 | 1499977.45 | 02-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 581.96 | 0.00 | 01-JAN-00:10 | 72495.44 | 13-NOV-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 570.83 | 0.00 | 01-JAN-00:10 | 49345.76 | 07-AUG-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 570.83 | 0.00 | 01-JAN-00:10 | 49345.76 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 570.83 | 0.00 | 01-JAN-00:10 | 49345.76 | 07-AUG-09:20 |
EnergyTransfer:Zone:CORE_MID | 4023.73 | 0.00 | 01-JAN-00:10 | 384682.91 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.88 | 0.00 | 01-JAN-00:10 | 246000.12 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.88 | 0.00 | 01-JAN-00:10 | 246000.12 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4021.84 | 0.00 | 01-JAN-00:10 | 384682.91 | 20-JUN-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4021.84 | 0.00 | 01-JAN-00:10 | 384682.91 | 20-JUN-05:10 |
EnergyTransfer:Zone:CORE_TOP | 383.83 | 0.00 | 01-JAN-00:10 | 63687.44 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 7.79 | 0.00 | 01-JAN-00:10 | 63687.44 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 7.79 | 0.00 | 01-JAN-00:10 | 63687.44 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 376.04 | 0.00 | 01-JAN-00:10 | 45132.72 | 18-MAY-14:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 376.04 | 0.00 | 01-JAN-00:10 | 45132.72 | 18-MAY-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.28 | 0.00 | 01-JAN-00:10 | 10059.71 | 09-AUG-14:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.35 | 0.00 | 01-JAN-00:10 | 4775.16 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.35 | 0.00 | 01-JAN-00:10 | 4775.16 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.93 | 0.00 | 01-JAN-00:10 | 10059.71 | 09-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.93 | 0.00 | 01-JAN-00:10 | 10059.71 | 09-AUG-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.98 | 0.00 | 01-JAN-00:10 | 11897.34 | 07-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.25 | 0.00 | 01-JAN-00:10 | 3647.68 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.25 | 0.00 | 01-JAN-00:10 | 3647.68 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.73 | 0.00 | 01-JAN-00:10 | 11897.34 | 07-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.73 | 0.00 | 01-JAN-00:10 | 11897.34 | 07-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.43 | 0.00 | 01-JAN-00:10 | 15759.05 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.46 | 0.00 | 01-JAN-00:10 | 8479.79 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.46 | 0.00 | 01-JAN-00:10 | 8479.79 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 98.97 | 0.00 | 01-JAN-00:10 | 15759.05 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 98.97 | 0.00 | 01-JAN-00:10 | 15759.05 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.39 | 0.00 | 01-JAN-00:10 | 15701.63 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 2063.04 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 2063.04 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.37 | 0.00 | 01-JAN-00:10 | 15701.63 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.37 | 0.00 | 01-JAN-00:10 | 15701.63 | 18-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 596.12 | 0.00 | 01-JAN-00:10 | 119465.56 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 67.87 | 0.00 | 01-JAN-00:10 | 119465.56 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 67.87 | 0.00 | 01-JAN-00:10 | 119465.56 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 528.26 | 0.00 | 01-JAN-00:10 | 94318.48 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 528.26 | 0.00 | 01-JAN-00:10 | 94318.48 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 529.83 | 0.00 | 01-JAN-00:10 | 128313.13 | 07-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.06 | 0.00 | 01-JAN-00:10 | 120124.58 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.06 | 0.00 | 01-JAN-00:10 | 120124.58 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 496.77 | 0.00 | 01-JAN-00:10 | 128313.13 | 07-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 496.77 | 0.00 | 01-JAN-00:10 | 128313.13 | 07-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 857.25 | 0.00 | 01-JAN-00:10 | 153713.92 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 31.50 | 0.00 | 01-JAN-00:10 | 136521.46 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 31.50 | 0.00 | 01-JAN-00:10 | 136521.46 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 825.75 | 0.00 | 01-JAN-00:10 | 153713.92 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 825.75 | 0.00 | 01-JAN-00:10 | 153713.92 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 575.47 | 0.00 | 01-JAN-00:10 | 126071.71 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.06 | 0.00 | 01-JAN-00:10 | 108226.56 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.06 | 0.00 | 01-JAN-00:10 | 108226.56 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 550.41 | 0.00 | 01-JAN-00:10 | 126071.71 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 550.41 | 0.00 | 01-JAN-00:10 | 126071.71 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 69.67 | 0.00 | 01-JAN-00:10 | 14791.48 | 13-FEB-04:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 17.78 | 0.00 | 01-JAN-00:10 | 14791.48 | 13-FEB-04:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 17.78 | 0.00 | 01-JAN-00:10 | 14791.48 | 13-FEB-04:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.90 | 0.00 | 01-JAN-00:10 | 10547.71 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.90 | 0.00 | 01-JAN-00:10 | 10547.71 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 60.14 | 0.00 | 01-JAN-00:10 | 13723.35 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.94 | 0.00 | 01-JAN-00:10 | 13723.35 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.94 | 0.00 | 01-JAN-00:10 | 13723.35 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.19 | 0.00 | 01-JAN-00:10 | 13084.94 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.19 | 0.00 | 01-JAN-00:10 | 13084.94 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.13 | 0.00 | 01-JAN-00:10 | 16636.92 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.65 | 0.00 | 01-JAN-00:10 | 15975.91 | 13-FEB-04:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.65 | 0.00 | 01-JAN-00:10 | 15975.91 | 13-FEB-04:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.48 | 0.00 | 01-JAN-00:10 | 16636.92 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.48 | 0.00 | 01-JAN-00:10 | 16636.92 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.45 | 0.00 | 01-JAN-00:10 | 13400.57 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.10 | 0.00 | 01-JAN-00:10 | 13342.94 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.10 | 0.00 | 01-JAN-00:10 | 13342.94 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.35 | 0.00 | 01-JAN-00:10 | 13400.57 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.35 | 0.00 | 01-JAN-00:10 | 13400.57 | 02-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.54 | 0.00 | 01-JAN-00:10 | 9607.16 | 07-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.23 | 0.00 | 01-JAN-00:10 | 3671.04 | 10-JAN-14:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.23 | 0.00 | 01-JAN-00:10 | 3671.04 | 10-JAN-14:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 59.30 | 0.00 | 01-JAN-00:10 | 9607.16 | 07-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 59.30 | 0.00 | 01-JAN-00:10 | 9607.16 | 07-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 448.05 | 0.00 | 01-JAN-00:10 | 70933.97 | 10-JUL-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 70.49 | 0.00 | 01-JAN-00:10 | 68771.30 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 70.49 | 0.00 | 01-JAN-00:10 | 68771.30 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 377.55 | 0.00 | 01-JAN-00:10 | 70933.97 | 10-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 377.55 | 0.00 | 01-JAN-00:10 | 70933.97 | 10-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 90.89 | 0.00 | 01-JAN-00:10 | 23991.59 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.08 | 0.00 | 01-JAN-00:10 | 23991.59 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.08 | 0.00 | 01-JAN-00:10 | 23991.59 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 64.82 | 0.00 | 01-JAN-00:10 | 19745.95 | 07-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 64.82 | 0.00 | 01-JAN-00:10 | 19745.95 | 07-JUL-15:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.56 | 227.39 | 08-JAN-06:00 | 7997.78 | 09-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.56 | 227.39 | 08-JAN-06:00 | 7997.78 | 09-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.56 | 227.39 | 08-JAN-06:00 | 7997.78 | 09-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1215.48 | 1.98 | 06-JAN-21:50 | 74239.14 | 09-APR-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.64 | 0.00 | 02-JAN-13:10 | 5238.05 | 08-JAN-19:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.64 | 0.00 | 02-JAN-13:10 | 5238.05 | 08-JAN-19:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1211.85 | 0.00 | 01-JAN-00:10 | 74239.14 | 09-APR-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1211.85 | 0.00 | 01-JAN-00:10 | 74239.14 | 09-APR-18:30 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 115.33 | 0.06 | 09-JAN-11:20 | 7612.94 | 20-AUG-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.74 | 0.00 | 02-JAN-16:40 | 572.56 | 22-JAN-19:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.74 | 0.00 | 02-JAN-16:40 | 572.56 | 22-JAN-19:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 114.59 | 0.00 | 01-JAN-00:10 | 7612.94 | 20-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 114.59 | 0.00 | 01-JAN-00:10 | 7612.94 | 20-AUG-17:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7129.62 | 84658.08 | 09-JAN-05:00 | 368964.36 | 07-AUG-21:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7129.62 | 84658.08 | 09-JAN-05:00 | 368964.36 | 07-AUG-21:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7129.62 | 84658.08 | 09-JAN-05:00 | 368964.36 | 07-AUG-21:30 |
PlantLoopHeatingDemand:Facility | 728.45 | 0.00 | 01-JAN-00:10 | 1124754.92 | 13-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 371.93 | 0.00 | 01-JAN-00:10 | 47932.33 | 01-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 371.93 | 0.00 | 01-JAN-00:10 | 47932.33 | 01-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 371.93 | 0.00 | 01-JAN-00:10 | 47932.33 | 01-FEB-12:50 |
EnergyTransfer:HVAC | 15405.30 | 1726.58 | 01-JAN-01:00 | 2425083.74 | 17-AUG-13:00 |
HeatingCoils:EnergyTransfer | 356.53 | 0.00 | 01-JAN-00:10 | 1108893.28 | 13-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 356.53 | 0.00 | 01-JAN-00:10 | 1108893.28 | 13-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 356.53 | 0.00 | 01-JAN-00:10 | 1108893.28 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 13709.49 | 1654.57 | 18-JAN-08:20 | 2159446.79 | 25-AUG-14:00 |
HeatRecoveryForHeating:EnergyTransfer | 533.62 | 0.00 | 01-JAN-00:10 | 517027.00 | 03-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 805.66 | 0.00 | 01-JAN-00:10 | 414815.83 | 15-JUL-12:20 |
EnergyTransfer:Plant | 27384.44 | 0.00 | 01-JAN-00:10 | 5683395.97 | 25-AUG-13:50 |
LoopToLoop:EnergyTransfer | 8510.16 | 0.00 | 01-JAN-00:10 | 1677269.14 | 25-AUG-14:00 |
WaterSystems:EnergyTransfer | 371.93 | 0.00 | 01-JAN-00:10 | 47932.33 | 01-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 371.93 | 0.00 | 01-JAN-00:10 | 47932.33 | 01-FEB-12:50 |
Boilers:EnergyTransfer | 355.88 | 0.00 | 01-JAN-00:10 | 1119517.31 | 13-FEB-07:10 |
Chillers:EnergyTransfer | 8461.68 | 0.00 | 01-JAN-00:10 | 1859286.21 | 25-AUG-13:50 |
HeatRejection:EnergyTransfer | 9684.80 | 0.00 | 01-JAN-00:10 | 2101156.91 | 25-AUG-13:50 |
General:HeatRejection:EnergyTransfer | 9684.80 | 0.00 | 01-JAN-00:10 | 2101156.91 | 25-AUG-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.224 | -581.957 | 0.000 | 0.000 | 92.795 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.500 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -570.832 | 0.000 | 0.000 | 83.470 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 93.536 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_MID | 0.000 | 0.000 | 1.880 | -4021.832 | 0.000 | 0.000 | 846.632 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -764.923 |
CORE_TOP | 0.000 | 0.000 | 7.793 | -376.033 | 0.000 | 0.000 | 86.821 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -112.406 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.347 | -72.930 | 0.000 | 0.000 | 10.731 | 7.581 | 36.365 | 30.352 | 0.000 | 0.221 | 44.593 | 0.000 | -52.296 | 0.000 | -4.965 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.252 | -59.731 | 0.000 | 0.000 | 6.874 | 4.831 | 23.435 | 50.508 | 0.000 | 0.145 | 8.409 | 0.000 | -31.422 | 0.000 | -3.301 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.462 | -98.971 | 0.000 | 0.000 | 10.636 | 7.456 | 36.366 | 89.177 | 0.000 | 0.214 | 6.621 | 0.000 | -46.920 | 0.000 | -5.040 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.015 | -95.374 | 0.000 | 0.000 | 6.786 | 4.855 | 23.435 | 49.631 | 0.000 | 0.131 | 52.481 | 0.000 | -38.202 | 0.000 | -3.758 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 67.868 | -528.250 | 0.000 | 0.000 | 111.374 | 75.625 | 363.654 | 314.484 | 0.000 | 5.170 | 152.398 | 0.000 | -462.007 | 0.000 | -100.315 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 33.062 | -496.767 | 0.000 | 0.000 | 51.701 | 48.243 | 234.352 | 504.399 | 0.000 | 3.112 | 0.006 | 0.000 | -290.061 | 0.000 | -69.988 | -18.053 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 31.501 | -825.730 | 0.000 | 0.000 | 107.920 | 74.472 | 363.660 | 891.523 | 0.000 | 4.836 | 0.020 | 0.000 | -445.748 | 0.000 | -110.168 | -92.265 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 25.063 | -550.401 | 0.000 | 0.000 | 70.546 | 48.455 | 234.351 | 509.000 | 0.000 | 3.069 | 54.585 | 0.000 | -321.796 | 0.000 | -72.871 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 17.777 | -51.895 | 0.000 | 0.000 | 11.280 | 7.562 | 36.365 | 31.651 | 0.000 | 0.609 | 1.708 | 0.000 | -43.408 | 0.000 | -11.649 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 8.945 | -51.192 | 0.000 | 0.000 | 7.133 | 4.824 | 23.435 | 50.885 | 0.000 | 0.378 | 0.000 | 0.000 | -27.292 | 0.000 | -8.101 | -9.015 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 9.650 | -78.474 | 0.000 | 0.000 | 10.930 | 7.447 | 36.366 | 89.554 | 0.000 | 0.568 | 0.001 | 0.000 | -42.044 | 0.000 | -12.777 | -21.219 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 7.104 | -54.346 | 0.000 | 0.000 | 7.145 | 4.845 | 23.435 | 50.941 | 0.000 | 0.367 | 0.001 | 0.000 | -30.505 | 0.000 | -8.527 | -0.460 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.562 | 0.000 | 0.000 | 0.948 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.942 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 3.635 | -1211.850 | 0.000 | 0.000 | 9.492 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -356.841 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.739 | -114.586 | 0.000 | 0.000 | 0.954 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -42.663 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7129.631 | 0.000 | 0.000 | 20.228 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -418.308 |
GROUNDFLOOR_PLENUM | 2.233 | -59.303 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.403 | 67.488 | 0.000 | 0.000 | 0.000 | -10.821 | 0.000 |
MIDFLOOR_PLENUM | 70.495 | -377.550 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.449 | 478.396 | 0.000 | 0.000 | 0.000 | -178.789 | -0.008 |
TOPFLOOR_PLENUM | 26.079 | -64.815 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.626 | 56.386 | 0.000 | 0.000 | 0.000 | -18.277 | -0.000 |
Total Facility | 98.807 | -501.669 | 219.318 | -17108.343 | 0.000 | 0.000 | 1554.397 | 1715.737 | 14676.396 | 2662.104 | 0.000 | 27.298 | 1016.629 | 0.000 | -1831.702 | 0.000 | -619.348 | -1909.609 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-04:12 | 0.00 | 0.00 | 0.00 | -97236.22 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 83180.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-04:13 | 0.00 | 0.00 | 0.00 | -87347.83 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 80872.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-SEP-04:12 | 0.00 | 0.00 | 0.00 | -739303.16 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 674553.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-MAY-04:13 | 0.00 | 0.00 | 0.00 | -75171.79 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 68696.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-15:52 | 0.00 | 0.00 | 0.00 | -14903.84 | 0.00 | 0.00 | 43.58 | 30.32 | 720.18 | 4507.94 | 0.00 | 173.96 | 9427.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 27-AUG-09:41 | 0.00 | 0.00 | 0.00 | -18433.16 | 0.00 | 0.00 | 22.41 | 19.54 | 464.11 | 12968.72 | 0.00 | 0.00 | 4966.80 | 0.00 | -0.00 | 0.00 | -8.42 | 0.00 |
PERIMETER_BOT_ZN_1 | 11-NOV-13:02 | 0.00 | 0.00 | 0.00 | -20480.16 | 0.00 | 0.00 | 35.44 | 30.33 | 720.19 | 22809.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -265.76 | -2849.95 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:21 | 0.00 | 0.00 | 0.00 | -23622.47 | 0.00 | 0.00 | 15.87 | 19.54 | 464.11 | 16118.15 | 0.00 | 39.13 | 6965.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-15:31 | 0.00 | 0.00 | 0.00 | -151864.55 | 0.00 | 0.00 | 413.00 | 303.25 | 7201.84 | 55127.84 | 0.00 | 2778.23 | 86040.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:41 | 0.00 | 0.00 | 0.00 | -199534.15 | 0.00 | 0.00 | 210.91 | 195.42 | 4641.14 | 128184.63 | 0.00 | 0.00 | 66560.55 | 0.00 | -0.00 | 0.00 | -258.50 | 0.00 |
PERIMETER_MID_ZN_1 | 26-FEB-13:42 | 0.00 | 0.00 | 0.00 | -194311.61 | 0.00 | 0.00 | 360.40 | 303.26 | 7201.95 | 207752.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3545.98 | -17760.90 |
PERIMETER_MID_ZN_4 | 13-AUG-16:41 | 0.00 | 0.00 | 0.00 | -220510.77 | 0.00 | 0.00 | 181.12 | 195.42 | 4641.11 | 146830.08 | 0.00 | 431.85 | 68231.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-15:31 | 0.00 | 0.00 | 0.00 | -17966.62 | 0.00 | 0.00 | 39.00 | 30.32 | 720.18 | 5356.92 | 0.00 | 314.54 | 11505.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:52 | 0.00 | 0.00 | 0.00 | -19336.26 | 0.00 | 0.00 | 22.72 | 19.54 | 464.11 | 11257.37 | 0.00 | 0.00 | 7727.10 | 0.00 | -0.00 | 0.00 | -154.58 | 0.00 |
PERIMETER_TOP_ZN_1 | 24-SEP-12:52 | 0.00 | 0.00 | 0.00 | -21528.62 | 0.00 | 0.00 | 36.27 | 30.33 | 720.19 | 15131.78 | 0.00 | 52.13 | 5557.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-16:11 | 0.00 | 0.00 | 0.00 | -23333.98 | 0.00 | 0.00 | 18.69 | 19.54 | 464.11 | 12224.85 | 0.00 | 121.02 | 10485.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 09-APR-18:15 | 0.00 | 0.00 | 0.00 | -7997.78 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 195.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 09-APR-18:30 | 0.00 | 0.00 | 0.00 | -74239.14 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3786.38 |
DATACENTER_TOP_ZN_6 | 20-AUG-17:17 | 0.00 | 0.00 | 0.00 | -7616.06 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -186.49 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-21:23 | 0.00 | 0.00 | 0.00 | -369421.91 | 0.00 | 0.00 | 114.27 | 318.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10643.62 |
GROUNDFLOOR_PLENUM | 10-JUL-05:13 | 0.00 | -12303.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12342.80 | 0.00 | -0.00 | 0.00 | -39.80 | 0.00 |
MIDFLOOR_PLENUM | 10-JUL-05:13 | 0.00 | -91540.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92257.58 | 0.00 | -0.00 | 0.00 | -717.07 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-15:10 | 0.00 | -19745.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.82 | 19630.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-AUG-05:03 | 0.00 | -23486.20 | 0.00 | -1704420.01 | 0.00 | 0.00 | 16024.67 | 18857.47 | 616289.16 | 0.00 | 0.00 | 0.00 | 1133434.11 | 0.00 | -54619.40 | 0.00 | -2079.79 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-JUL-16:01 | 0.00 | 0.00 | 24779.93 | 0.00 | 0.00 | 0.00 | 520.12 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39322.81 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 403359.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -468109.25 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 69904.98 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -76350.20 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:01 | 0.00 | 0.00 | 11413.14 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6200.90 | 0.00 | -1361.55 | -4723.73 |
PERIMETER_BOT_ZN_2 | 13-FEB-05:01 | 0.00 | 0.00 | 9849.26 | 0.00 | 0.00 | 0.00 | 0.00 | 82.15 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4115.17 | 0.00 | -906.46 | -5390.24 |
PERIMETER_BOT_ZN_1 | 09-JAN-05:01 | 0.00 | 0.00 | 14212.40 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4816.09 | 0.00 | -865.14 | -9404.22 |
PERIMETER_BOT_ZN_4 | 07-JAN-06:01 | 0.00 | 0.00 | 7703.11 | 0.00 | 0.00 | 0.00 | 94.15 | 82.15 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3500.31 | 0.00 | -237.94 | -4759.98 |
PERIMETER_MID_ZN_3 | 12-FEB-06:11 | 0.00 | 0.00 | 131229.11 | 0.00 | 0.00 | 0.00 | 901.64 | 637.34 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69042.96 | 0.00 | -40331.51 | -30595.45 |
PERIMETER_MID_ZN_2 | 12-FEB-06:11 | 0.00 | 0.00 | 152983.43 | 0.00 | 0.00 | 0.00 | 581.79 | 410.73 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44410.03 | 0.00 | -27267.08 | -86939.98 |
PERIMETER_MID_ZN_1 | 12-FEB-06:51 | 0.00 | 0.00 | 155403.12 | 0.00 | 0.00 | 0.00 | 892.47 | 637.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67741.45 | 0.00 | -37994.42 | -58399.03 |
PERIMETER_MID_ZN_4 | 13-FEB-04:01 | 0.00 | 0.00 | 152358.21 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35715.33 | 0.00 | -23520.12 | -98338.14 |
PERIMETER_TOP_ZN_3 | 12-FEB-05:02 | 0.00 | 0.00 | 16057.83 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6463.87 | 0.00 | -4060.05 | -6156.81 |
PERIMETER_TOP_ZN_2 | 12-FEB-05:02 | 0.00 | 0.00 | 16661.82 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4167.46 | 0.00 | -2753.84 | -10141.95 |
PERIMETER_TOP_ZN_1 | 12-FEB-05:02 | 0.00 | 0.00 | 18484.50 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6303.16 | 0.00 | -4110.30 | -8693.96 |
PERIMETER_TOP_ZN_4 | 12-FEB-05:02 | 0.00 | 0.00 | 18228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4415.73 | 0.00 | -2821.01 | -11393.49 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 08-JAN-19:00 | 0.00 | 0.00 | 5238.05 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24805.40 |
DATACENTER_TOP_ZN_6 | 22-JAN-18:55 | 0.00 | 0.00 | 578.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2535.22 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:11 | 12246.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2205.29 | -10041.11 |
MIDFLOOR_PLENUM | 09-JAN-06:15 | 76964.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7642.36 | -69321.69 |
TOPFLOOR_PLENUM | 13-FEB-05:12 | 25971.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4967.46 | -21004.28 |
Total Facility | 09-JAN-05:11 | -93207.73 | 99143.18 | 1117681.82 | -99143.18 | 0.00 | 0.00 | 0.00 | 10223.35 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -181736.12 | 0.00 | -109825.01 | -975561.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.7247 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.6934 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 91.9959 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 80.8000 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.5004 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.9586 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9196 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9196 | 0.2440 | 1.0000 | Not calculated | 1.2002 | 0.2440 | ||
AIRLOOP DATACENTER BASEMENT | 21.9526 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9529 | 0.0154 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4727 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4727 | 0.0331 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5113 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5113 | 0.0347 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4599 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4599 | 0.0340 | 1.0000 | Not calculated | 0.0156 | 0.0340 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.8624 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2872 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 45.9979 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8605 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.7502 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2848 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9196 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9196 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2440 | ||
AIRLOOP DATACENTER BASEMENT | 21.9526 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9526 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4727 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4727 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5113 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5113 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4599 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4599 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0340 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9196 | 4.9196 | 4.9196 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3801 | 5.3801 | 1.6194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 50.5544 | 50.5544 | 16.1774 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9937 | 4.9937 | 1.6180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9361 | 0.9361 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0068 | 1.0068 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1118 | 1.1118 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2900 | 1.2900 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.9201 | 8.9201 | 2.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5835 | 10.5835 | 1.3123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.7052 | 10.7052 | 2.0340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2327 | 11.2327 | 1.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0234 | 1.0234 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0800 | 1.0800 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1930 | 1.1930 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2102 | 1.2102 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4727 | 0.4727 | 0.4727 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5113 | 4.5113 | 4.5113 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4599 | 0.4599 | 0.4599 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9526 | 21.9526 | 21.9526 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.7247 | 8.6934 | 9.7247 | 2.2872 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 91.9959 | 80.8000 | 91.9959 | 22.8605 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.5004 | 8.9586 | 9.5004 | 2.2848 | 0.0000 | 1.0000 |
CAV_BAS | 4.9196 | 4.9196 | 4.9196 | 4.9196 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9526 | 21.9529 | 21.9526 | 21.9526 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4727 | 0.4727 | 0.4727 | 0.4727 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5113 | 4.5113 | 4.5113 | 4.5113 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4599 | 0.4599 | 0.4599 | 0.4599 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9196 | 4.9196 | 4.9196 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6901 | 2.6901 | 1.6194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.2772 | 25.2772 | 16.1774 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4968 | 2.4968 | 1.6180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4680 | 0.4680 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5034 | 0.5034 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5559 | 0.5559 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6450 | 0.6450 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4601 | 4.4601 | 2.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2917 | 5.2917 | 1.3123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3526 | 5.3526 | 2.0340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6164 | 5.6164 | 1.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5117 | 0.5117 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5400 | 0.5400 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5965 | 0.5965 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6051 | 0.6051 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4727 | 0.4727 | 0.4727 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5113 | 4.5113 | 4.5113 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4599 | 0.4599 | 0.4599 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9526 | 21.9526 | 21.9526 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.8624 | 2.2872 | 2.2872 | 2.2872 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 45.9979 | 22.8605 | 22.8605 | 22.8605 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.7502 | 2.2848 | 2.2848 | 2.2848 | 0.0000 | 1.0000 |
CAV_BAS | 4.9196 | 4.9196 | 4.9196 | 4.9196 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9526 | 21.9526 | 21.9526 | 21.9526 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4727 | 0.4727 | 0.4727 | 0.4727 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5113 | 4.5113 | 4.5113 | 4.5113 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4599 | 0.4599 | 0.4599 | 0.4599 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 37.17 |
Number of hours cooling loads not met | 579.67 |
Number of hours not met | 616.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 402.61 | 1307065.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2694.26 | 401101.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1715.74 | 169602.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 266.23 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3371.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2248.70 | 246688.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 460.31 | 46863.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1014.48 | 79310.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 959.90 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 39.13 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 707.28 | 81280.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 25278.84 |
Natural Gas | 0.00 | 1109.89 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 26388.73 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 548.16 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.04 |
Space Heating | 0.00 |
Space Cooling | 58.17 |
Fans (All) | 48.55 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 545.74 |
Subtotal | 545.74 |
Natural Gas [MJ/m2] | |
Space Heating | 8.69 |
Service Water Heating | 15.27 |
Miscellaneous (All) | 23.96 |
Subtotal | 23.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.50 |
Space Heating | 1.53 |
Space Cooling | 10.21 |
Fans (All) | 8.52 |
Service Water Heating | 2.68 |
Receptacle Equipment | 55.62 |
Miscellaneous | 14.94 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 970. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8141.33 | 618.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8712.00 | 48.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8723.17 | 36.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8631.50 | 128.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8653.67 | 106.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7788.17 | 971.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8720.50 | 39.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8549.67 | 210.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8620.83 | 139.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8242.67 | 517.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8671.50 | 88.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8489.50 | 270.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8567.50 | 192.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8225.67 | 534.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6818.50 | 1941.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6799.17 | 1960.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6776.50 | 1983.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5555.33 | 3204.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8558.00 | 202.00 | 0.00 | 0.00 | 0.00 |
Min | 5555.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3204.67 | 0.00 | 0.00 | 0.00 |
Average | 8186.31 | 573.69 | 0.00 | 0.00 | 0.00 |
Sum | 188285.17 | 13194.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 366728.33 | 1887.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330728.00 | 85.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1261.67 | 1006.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1250.17 | 1017.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1239.67 | 1028.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 53185.00 | 50210.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366728.33 | 50210.00 | 0.00 | 0.00 | 0.00 |
Average | 77933.38 | 2401.53 | 0.00 | 0.00 | 0.00 |
Sum | 1792467.83 | 55235.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6122.50 | 2637.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7449.33 | 1310.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7507.67 | 1252.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7472.67 | 1287.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7393.17 | 1366.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7499.17 | 1260.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7340.50 | 1419.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6926.33 | 1833.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7394.00 | 1366.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7314.00 | 1446.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7296.67 | 1463.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7216.50 | 1543.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7403.67 | 1356.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7349.83 | 1410.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7322.67 | 1437.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7254.67 | 1505.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7403.33 | 1356.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7359.50 | 1400.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7341.00 | 1419.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6383.67 | 2376.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7062.50 | 1697.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6865.00 | 1895.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6227.00 | 2533.00 | 0.00 | 0.00 | 0.00 |
Min | 6122.50 | 1252.33 | 0.00 | 0.00 | 0.00 |
Max | 7507.67 | 2637.50 | 0.00 | 0.00 | 0.00 |
Average | 7169.80 | 1590.20 | 0.00 | 0.00 | 0.00 |
Sum | 164905.33 | 36574.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 325652.17 | 42963.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 328294.17 | 2518.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328095.33 | 2717.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 327079.83 | 3733.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38923.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38923.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38871.67 | 53.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18325.33 | 28.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38894.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24890.50 | 18.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38735.83 | 189.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24819.00 | 90.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38804.17 | 120.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24834.50 | 74.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1484.67 | 783.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1463.50 | 804.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1450.50 | 817.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 63551.67 | 39843.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328294.17 | 42963.83 | 0.00 | 0.00 | 0.00 |
Average | 76213.48 | 4121.43 | 0.00 | 0.00 | 0.00 |
Sum | 1752910.00 | 94793.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387236E+11 | 93831.96 | 02-JAN-05:22 | 3.30 | 2.57 | 0.561220E+10 | 7499.25 | 30-JAN-10:50 | 13.67 | 9.38 |
February | 0.359504E+11 | 96705.36 | 21-FEB-05:11 | 6.33 | 4.24 | 0.512000E+10 | 7499.30 | 22-FEB-14:20 | 20.40 | 12.08 |
March | 0.459719E+11 | 93979.05 | 06-MAR-05:11 | 4.03 | 0.98 | 0.612888E+10 | 7499.56 | 08-MAR-10:20 | 16.10 | 12.08 |
April | 0.422115E+11 | 93206.24 | 17-APR-04:12 | 14.60 | 10.56 | 0.544410E+10 | 7499.23 | 03-APR-09:20 | 14.60 | 10.56 |
May | 0.456391E+11 | 91299.93 | 15-MAY-04:12 | 12.60 | 11.09 | 0.589745E+10 | 7499.45 | 11-MAY-09:00 | 12.60 | 11.09 |
June | 0.503591E+11 | 90011.06 | 07-JUN-04:12 | 15.03 | 12.52 | 0.587957E+10 | 7499.28 | 09-JUN-13:20 | 29.60 | 18.61 |
July | 0.520437E+11 | 82985.09 | 03-JUL-04:12 | 17.80 | 16.61 | 0.547112E+10 | 7498.95 | 28-JUL-13:20 | 19.40 | 19.40 |
August | 0.599134E+11 | 79555.63 | 26-AUG-04:12 | 21.70 | 17.11 | 0.613665E+10 | 7499.05 | 25-AUG-13:20 | 21.70 | 17.11 |
September | 0.540079E+11 | 90795.00 | 19-SEP-04:12 | 14.40 | 12.50 | 0.545177E+10 | 7499.17 | 15-SEP-13:20 | 14.40 | 12.50 |
October | 0.552464E+11 | 97283.22 | 30-OCT-04:12 | 8.90 | 8.90 | 0.566939E+10 | 7499.10 | 04-OCT-13:20 | 8.90 | 8.90 |
November | 0.533561E+11 | 97144.92 | 12-NOV-14:00 | 18.90 | 10.54 | 0.561349E+10 | 7499.34 | 16-NOV-10:20 | 10.77 | 10.06 |
December | 0.485331E+11 | 96730.89 | 11-DEC-05:11 | 6.33 | 5.61 | 0.546718E+10 | 7499.19 | 11-DEC-10:39 | 13.90 | 11.28 |
Annual Sum or Average | 0.581956E+12 | 0.678918E+11 | ||||||||
Minimum of Months | 0.359504E+11 | 79555.63 | 3.30 | 0.98 | 0.512000E+10 | 7498.95 | 8.90 | 8.90 | ||
Maximum of Months | 0.599134E+11 | 97283.22 | 21.70 | 17.11 | 0.613665E+10 | 7499.56 | 29.60 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290866E+11 | 80102.22 | 02-JAN-05:11 | 3.30 | 2.57 | 0.503517E+10 | 6734.87 | 30-JAN-10:50 | 13.67 | 9.38 |
February | 0.317404E+11 | 80377.13 | 21-FEB-05:11 | 6.33 | 4.24 | 0.458896E+10 | 6743.79 | 15-FEB-10:20 | 6.33 | 4.24 |
March | 0.476237E+11 | 80965.06 | 13-MAR-04:12 | 7.03 | 2.96 | 0.549801E+10 | 6735.18 | 08-MAR-10:09 | 7.03 | 2.96 |
April | 0.510912E+11 | 80419.15 | 21-APR-04:13 | 15.60 | 14.27 | 0.488102E+10 | 6734.82 | 12-APR-13:50 | 15.60 | 14.27 |
May | 0.473673E+11 | 84320.15 | 22-MAY-04:13 | 17.20 | 16.46 | 0.528585E+10 | 6743.05 | 19-MAY-13:00 | 17.20 | 16.46 |
June | 0.548665E+11 | 82535.74 | 06-JUN-04:13 | 18.90 | 15.23 | 0.526912E+10 | 6735.51 | 02-JUN-13:09 | 18.90 | 15.23 |
July | 0.606375E+11 | 78314.03 | 29-JUL-04:12 | 17.40 | 17.40 | 0.489369E+10 | 6734.67 | 28-JUL-09:20 | 17.40 | 17.40 |
August | 0.688241E+11 | 74537.48 | 07-AUG-05:05 | 23.22 | 22.48 | 0.549423E+10 | 6734.71 | 28-AUG-13:20 | 28.30 | 22.11 |
September | 0.478269E+11 | 83554.90 | 18-SEP-04:12 | 14.80 | 13.90 | 0.488362E+10 | 6769.96 | 22-SEP-13:50 | 26.60 | 17.45 |
October | 0.467709E+11 | 87368.14 | 10-OCT-04:13 | 16.10 | 15.06 | 0.507872E+10 | 6734.78 | 26-OCT-09:39 | 10.90 | 7.41 |
November | 0.445434E+11 | 86509.07 | 13-NOV-05:11 | 4.23 | 1.45 | 0.502905E+10 | 6735.00 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.404540E+11 | 82256.06 | 11-DEC-05:12 | 6.33 | 5.61 | 0.490065E+10 | 6734.91 | 11-DEC-10:00 | 15.00 | 12.11 |
Annual Sum or Average | 0.570833E+12 | 0.608381E+11 | ||||||||
Minimum of Months | 0.290866E+11 | 74537.48 | 3.30 | 1.45 | 0.458896E+10 | 6734.67 | 6.33 | 2.96 | ||
Maximum of Months | 0.688241E+11 | 87368.14 | 23.22 | 22.48 | 0.549801E+10 | 6769.96 | 28.30 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194440E+11 | 21177.60 | 21-JAN-08:40 | 5.00 | 2.71 | 0.451051E+10 | 6734.53 | 31-JAN-14:20 | 20.77 | 13.22 |
February | 0.210247E+11 | 66632.31 | 28-FEB-06:03 | 10.78 | 5.86 | 0.431700E+10 | 6770.11 | 01-FEB-14:50 | 10.78 | 5.86 |
March | 0.325034E+11 | 71484.76 | 31-MAR-04:12 | 17.03 | 14.86 | 0.545785E+10 | 6735.08 | 08-MAR-10:09 | 17.03 | 14.86 |
April | 0.339350E+11 | 72606.91 | 24-APR-04:12 | 13.90 | 13.90 | 0.486769E+10 | 6736.23 | 17-APR-13:09 | 13.90 | 13.90 |
May | 0.400065E+11 | 72821.00 | 31-MAY-04:12 | 20.00 | 19.09 | 0.527948E+10 | 6812.82 | 19-MAY-13:30 | 20.00 | 19.09 |
June | 0.433518E+11 | 73580.88 | 20-JUN-04:12 | 19.40 | 19.07 | 0.526602E+10 | 6734.83 | 09-JUN-13:20 | 19.40 | 19.07 |
July | 0.438180E+11 | 73020.90 | 28-JUL-04:12 | 19.40 | 19.40 | 0.489346E+10 | 6734.79 | 05-JUL-09:20 | 19.40 | 19.40 |
August | 0.469720E+11 | 73146.09 | 25-AUG-04:12 | 19.80 | 18.06 | 0.549425E+10 | 6734.73 | 14-AUG-13:20 | 19.80 | 18.06 |
September | 0.390246E+11 | 73941.67 | 18-SEP-04:12 | 14.80 | 13.90 | 0.487650E+10 | 6734.80 | 25-SEP-13:20 | 28.73 | 19.18 |
October | 0.328621E+11 | 72664.10 | 17-OCT-05:02 | 16.60 | 16.60 | 0.504821E+10 | 6745.28 | 26-OCT-09:20 | 9.60 | 6.55 |
November | 0.270821E+11 | 68583.05 | 06-NOV-06:03 | 9.32 | 8.73 | 0.496893E+10 | 6774.62 | 21-NOV-10:30 | 3.30 | 0.39 |
December | 0.221602E+11 | 66411.99 | 14-DEC-06:02 | 6.60 | 5.31 | 0.466540E+10 | 6734.76 | 12-DEC-10:09 | 6.60 | 5.31 |
Annual Sum or Average | 0.402184E+12 | 0.596453E+11 | ||||||||
Minimum of Months | 0.194440E+11 | 21177.60 | 5.00 | 2.71 | 0.431700E+10 | 6734.53 | 3.30 | 0.39 | ||
Maximum of Months | 0.469720E+11 | 73941.67 | 20.00 | 19.40 | 0.549425E+10 | 6812.82 | 28.73 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136168E+11 | 19867.10 | 20-JAN-17:00 | 16.70 | 11.48 | 0.406587E+10 | 6734.12 | 20-JAN-14:00 | 16.70 | 11.48 |
February | 0.159788E+11 | 29554.52 | 28-FEB-17:00 | 23.90 | 12.94 | 0.396054E+10 | 6734.77 | 22-FEB-14:20 | 23.90 | 12.94 |
March | 0.267169E+11 | 69358.79 | 31-MAR-05:03 | 16.78 | 15.18 | 0.525003E+10 | 6734.77 | 14-MAR-09:20 | 16.78 | 15.18 |
April | 0.307283E+11 | 70291.82 | 18-APR-05:02 | 14.22 | 12.17 | 0.479433E+10 | 6734.83 | 17-APR-13:20 | 14.22 | 12.17 |
May | 0.403539E+11 | 75191.09 | 30-MAY-04:13 | 19.43 | 17.60 | 0.526726E+10 | 6739.10 | 19-MAY-13:30 | 19.43 | 17.60 |
June | 0.467528E+11 | 72813.40 | 30-JUN-05:04 | 21.10 | 20.28 | 0.526592E+10 | 6734.81 | 09-JUN-13:20 | 21.10 | 20.28 |
July | 0.483101E+11 | 73184.76 | 27-JUL-05:04 | 22.12 | 22.12 | 0.489549E+10 | 6734.67 | 28-JUL-09:20 | 19.40 | 19.40 |
August | 0.514700E+11 | 71797.92 | 31-AUG-04:12 | 22.03 | 21.28 | 0.549706E+10 | 6734.72 | 25-AUG-13:20 | 22.03 | 21.28 |
September | 0.381248E+11 | 72188.54 | 07-SEP-05:04 | 22.20 | 21.11 | 0.486397E+10 | 6734.77 | 15-SEP-13:20 | 27.97 | 18.13 |
October | 0.275704E+11 | 68965.06 | 19-OCT-04:12 | 21.50 | 21.50 | 0.488542E+10 | 6734.74 | 12-OCT-09:20 | 21.50 | 21.50 |
November | 0.200978E+11 | 46243.44 | 04-NOV-05:03 | 16.60 | 15.28 | 0.460076E+10 | 6734.73 | 03-NOV-09:20 | 16.60 | 15.28 |
December | 0.163149E+11 | 26600.89 | 13-DEC-17:00 | 16.70 | 16.70 | 0.414101E+10 | 6734.69 | 13-DEC-10:20 | 16.70 | 16.70 |
Annual Sum or Average | 0.376036E+12 | 0.574876E+11 | ||||||||
Minimum of Months | 0.136168E+11 | 19867.10 | 14.22 | 11.48 | 0.396054E+10 | 6734.12 | 14.22 | 11.48 | ||
Maximum of Months | 0.514700E+11 | 75191.09 | 23.90 | 22.12 | 0.549706E+10 | 6739.10 | 27.97 | 21.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181320E+10 | 3445.60 | 31-JAN-14:40 | 20.93 | 13.10 | 0.534696E+09 | 845.60 | 19-JAN-14:09 | 20.93 | 13.10 |
February | 0.244575E+10 | 5815.08 | 28-FEB-15:00 | 25.00 | 13.71 | 0.517331E+09 | 845.64 | 22-FEB-14:39 | 25.00 | 13.71 |
March | 0.457865E+10 | 7545.54 | 30-MAR-15:20 | 27.80 | 17.21 | 0.675667E+09 | 845.66 | 08-MAR-10:39 | 27.80 | 17.21 |
April | 0.611673E+10 | 9745.06 | 03-APR-05:02 | 17.75 | 16.94 | 0.607754E+09 | 845.64 | 12-APR-13:50 | 28.72 | 17.01 |
May | 0.717445E+10 | 11373.04 | 30-MAY-04:12 | 19.43 | 17.60 | 0.662923E+09 | 847.86 | 19-MAY-13:00 | 19.43 | 17.60 |
June | 0.996300E+10 | 14908.41 | 18-JUN-15:52 | 31.70 | 23.72 | 0.662325E+09 | 845.80 | 02-JUN-13:09 | 31.70 | 23.72 |
July | 0.109536E+11 | 14735.52 | 16-JUL-15:42 | 33.30 | 22.52 | 0.615890E+09 | 846.01 | 21-JUL-13:50 | 32.80 | 23.28 |
August | 0.120491E+11 | 14457.61 | 27-AUG-15:41 | 31.70 | 21.48 | 0.690889E+09 | 846.03 | 14-AUG-13:50 | 31.70 | 21.48 |
September | 0.681013E+10 | 11593.65 | 25-SEP-04:12 | 20.20 | 17.47 | 0.612471E+09 | 851.10 | 22-SEP-13:50 | 20.20 | 17.47 |
October | 0.469643E+10 | 12055.01 | 02-OCT-04:12 | 18.70 | 18.70 | 0.626446E+09 | 845.62 | 12-OCT-09:20 | 13.87 | 9.56 |
November | 0.355814E+10 | 5405.08 | 02-NOV-13:40 | 23.30 | 17.25 | 0.610295E+09 | 845.63 | 16-NOV-10:30 | 10.85 | 10.10 |
December | 0.277099E+10 | 5119.96 | 13-DEC-12:00 | 20.00 | 17.41 | 0.571234E+09 | 845.64 | 11-DEC-10:00 | 20.00 | 17.41 |
Annual Sum or Average | 0.729301E+11 | 0.738792E+10 | ||||||||
Minimum of Months | 0.181320E+10 | 3445.60 | 17.75 | 13.10 | 0.517331E+09 | 845.60 | 10.85 | 9.56 | ||
Maximum of Months | 0.120491E+11 | 14908.41 | 33.30 | 23.72 | 0.690889E+09 | 851.10 | 32.80 | 23.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133779E+10 | 2996.77 | 31-JAN-11:00 | 14.40 | 11.88 | 0.360937E+09 | 544.96 | 30-JAN-10:09 | 14.40 | 11.88 |
February | 0.204244E+10 | 7382.48 | 27-FEB-09:40 | 12.23 | 5.46 | 0.342925E+09 | 544.96 | 22-FEB-14:39 | 12.23 | 5.46 |
March | 0.385210E+10 | 10539.39 | 26-MAR-09:43 | 11.73 | 6.53 | 0.437019E+09 | 545.00 | 08-MAR-10:09 | 11.73 | 6.53 |
April | 0.528990E+10 | 17244.92 | 16-APR-09:52 | 22.20 | 14.59 | 0.392764E+09 | 545.48 | 17-APR-09:09 | 20.47 | 14.59 |
May | 0.654399E+10 | 17754.24 | 07-MAY-08:42 | 22.93 | 19.01 | 0.427951E+09 | 545.95 | 19-MAY-13:00 | 30.60 | 18.49 |
June | 0.822580E+10 | 18259.25 | 04-JUN-08:22 | 23.30 | 17.57 | 0.427078E+09 | 545.51 | 19-JUN-09:00 | 28.30 | 22.45 |
July | 0.872679E+10 | 17035.76 | 04-JUL-09:32 | 26.47 | 23.26 | 0.397121E+09 | 546.22 | 17-JUL-09:50 | 27.52 | 21.93 |
August | 0.904904E+10 | 18439.10 | 27-AUG-09:41 | 26.83 | 21.78 | 0.445325E+09 | 545.79 | 14-AUG-09:00 | 26.83 | 21.78 |
September | 0.597983E+10 | 17077.88 | 24-SEP-09:02 | 23.77 | 18.55 | 0.394916E+09 | 548.78 | 22-SEP-13:50 | 23.77 | 18.55 |
October | 0.410859E+10 | 11746.63 | 09-OCT-08:53 | 21.10 | 16.86 | 0.405120E+09 | 544.95 | 26-OCT-09:39 | 10.90 | 7.41 |
November | 0.265685E+10 | 6909.00 | 06-NOV-09:30 | 13.30 | 11.71 | 0.397073E+09 | 544.96 | 06-NOV-10:09 | 14.87 | 12.62 |
December | 0.191805E+10 | 3888.78 | 11-DEC-10:25 | 13.35 | 10.86 | 0.374561E+09 | 544.97 | 11-DEC-10:00 | 15.00 | 12.11 |
Annual Sum or Average | 0.597312E+11 | 0.480279E+10 | ||||||||
Minimum of Months | 0.133779E+10 | 2996.77 | 11.73 | 5.46 | 0.342925E+09 | 544.95 | 10.90 | 5.46 | ||
Maximum of Months | 0.904904E+10 | 18439.10 | 26.83 | 23.26 | 0.445325E+09 | 548.78 | 30.60 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377858E+10 | 16975.69 | 29-JAN-12:43 | 13.72 | 6.05 | 0.577012E+09 | 848.11 | 11-JAN-14:30 | 13.72 | 6.05 |
February | 0.474085E+10 | 19252.58 | 26-FEB-12:32 | 23.53 | 12.41 | 0.537711E+09 | 886.13 | 21-FEB-14:39 | 23.53 | 12.41 |
March | 0.758517E+10 | 18212.59 | 26-MAR-13:43 | 18.72 | 8.91 | 0.677852E+09 | 855.54 | 30-MAR-13:50 | 27.62 | 17.92 |
April | 0.806211E+10 | 18873.94 | 16-APR-13:13 | 28.50 | 16.07 | 0.607655E+09 | 876.54 | 12-APR-13:39 | 28.50 | 16.07 |
May | 0.800633E+10 | 13495.96 | 29-MAY-13:03 | 28.80 | 20.58 | 0.662401E+09 | 862.05 | 19-MAY-13:00 | 28.80 | 20.58 |
June | 0.101204E+11 | 17202.46 | 18-JUN-15:52 | 31.70 | 23.72 | 0.662129E+09 | 845.87 | 02-JUN-13:09 | 31.70 | 23.72 |
July | 0.114074E+11 | 17218.76 | 16-JUL-15:42 | 33.30 | 22.52 | 0.615996E+09 | 846.18 | 31-JUL-13:00 | 30.60 | 24.81 |
August | 0.139323E+11 | 19120.69 | 27-AUG-13:02 | 31.70 | 22.66 | 0.691273E+09 | 846.57 | 28-AUG-13:30 | 28.30 | 22.11 |
September | 0.954023E+10 | 18537.90 | 17-SEP-14:23 | 27.75 | 22.29 | 0.613007E+09 | 863.44 | 22-SEP-13:50 | 26.60 | 17.45 |
October | 0.890025E+10 | 19957.83 | 08-OCT-12:42 | 24.32 | 17.57 | 0.628914E+09 | 906.09 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.706308E+10 | 20476.61 | 11-NOV-13:02 | 21.10 | 11.68 | 0.620378E+09 | 891.93 | 06-NOV-14:09 | 21.10 | 11.68 |
December | 0.583557E+10 | 19615.92 | 10-DEC-13:22 | 16.15 | 7.78 | 0.589036E+09 | 846.90 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.989722E+11 | 0.748336E+10 | ||||||||
Minimum of Months | 0.377858E+10 | 13495.96 | 13.72 | 6.05 | 0.537711E+09 | 845.87 | 13.72 | 6.05 | ||
Maximum of Months | 0.139323E+11 | 20476.61 | 33.30 | 23.72 | 0.691273E+09 | 906.09 | 31.70 | 24.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203760E+10 | 5867.36 | 23-JAN-16:30 | 10.00 | 3.54 | 0.377154E+09 | 544.96 | 30-JAN-10:50 | 13.67 | 9.38 |
February | 0.328315E+10 | 16289.43 | 26-FEB-17:53 | 22.80 | 11.66 | 0.360917E+09 | 545.49 | 15-FEB-10:20 | 22.80 | 11.66 |
March | 0.754881E+10 | 21196.59 | 26-MAR-16:22 | 20.30 | 9.51 | 0.445424E+09 | 545.00 | 30-MAR-13:09 | 26.88 | 18.10 |
April | 0.998296E+10 | 22625.70 | 09-APR-16:32 | 21.70 | 10.73 | 0.396530E+09 | 544.97 | 12-APR-13:50 | 28.72 | 17.01 |
May | 0.825373E+10 | 23260.26 | 21-MAY-17:32 | 25.97 | 19.50 | 0.428860E+09 | 546.24 | 19-MAY-13:00 | 25.97 | 19.50 |
June | 0.112118E+11 | 22543.07 | 11-JUN-16:31 | 32.40 | 21.14 | 0.427909E+09 | 545.14 | 02-JUN-13:09 | 32.40 | 21.14 |
July | 0.128420E+11 | 22789.57 | 09-JUL-16:32 | 33.50 | 22.89 | 0.398263E+09 | 544.95 | 17-JUL-09:00 | 27.80 | 22.02 |
August | 0.156661E+11 | 23630.56 | 13-AUG-16:21 | 30.55 | 22.29 | 0.446590E+09 | 544.96 | 28-AUG-13:30 | 28.30 | 22.11 |
September | 0.777958E+10 | 21944.41 | 17-SEP-17:02 | 24.90 | 20.68 | 0.396236E+09 | 549.85 | 22-SEP-13:50 | 26.60 | 17.45 |
October | 0.651529E+10 | 20992.98 | 09-OCT-16:12 | 27.43 | 19.51 | 0.411348E+09 | 544.96 | 16-OCT-13:00 | 25.00 | 19.11 |
November | 0.551825E+10 | 21710.59 | 11-NOV-15:02 | 21.20 | 11.80 | 0.406523E+09 | 544.98 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.473495E+10 | 19353.30 | 10-DEC-15:23 | 18.60 | 9.00 | 0.395038E+09 | 544.97 | 11-DEC-10:00 | 15.00 | 12.11 |
Annual Sum or Average | 0.953743E+11 | 0.489079E+10 | ||||||||
Minimum of Months | 0.203760E+10 | 5867.36 | 10.00 | 3.54 | 0.360917E+09 | 544.95 | 10.68 | 9.38 | ||
Maximum of Months | 0.156661E+11 | 23630.56 | 33.50 | 22.89 | 0.446590E+09 | 549.85 | 32.40 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472485E+09 | 1875.78 | 31-JAN-15:10 | 20.92 | 13.08 | 0.476752E+09 | 796.08 | 31-JAN-14:00 | 20.92 | 13.08 |
February | 0.111907E+10 | 4102.43 | 28-FEB-15:00 | 25.00 | 13.71 | 0.457335E+09 | 845.63 | 22-FEB-14:20 | 25.00 | 13.71 |
March | 0.291239E+10 | 6110.48 | 30-MAR-15:20 | 27.80 | 17.21 | 0.623167E+09 | 845.62 | 28-MAR-13:20 | 27.80 | 17.21 |
April | 0.386015E+10 | 6669.70 | 19-APR-14:30 | 26.15 | 17.54 | 0.587020E+09 | 845.84 | 17-APR-13:09 | 26.15 | 17.54 |
May | 0.605461E+10 | 10290.62 | 19-MAY-14:50 | 30.60 | 18.68 | 0.658616E+09 | 858.99 | 19-MAY-13:30 | 30.60 | 18.68 |
June | 0.848322E+10 | 12477.02 | 25-JUN-16:42 | 32.88 | 22.29 | 0.661658E+09 | 845.64 | 02-JUN-13:39 | 32.88 | 22.29 |
July | 0.885259E+10 | 15188.78 | 16-JUL-15:31 | 33.30 | 22.52 | 0.615734E+09 | 846.65 | 21-JUL-13:20 | 32.80 | 23.50 |
August | 0.916500E+10 | 14487.92 | 13-AUG-16:41 | 30.92 | 22.40 | 0.690965E+09 | 845.62 | 10-AUG-13:20 | 30.92 | 22.40 |
September | 0.558846E+10 | 10755.75 | 06-SEP-05:03 | 21.20 | 20.02 | 0.608580E+09 | 845.63 | 25-SEP-13:20 | 28.73 | 19.18 |
October | 0.323988E+10 | 7002.45 | 19-OCT-05:03 | 20.92 | 20.92 | 0.584985E+09 | 845.62 | 20-OCT-13:20 | 18.13 | 11.22 |
November | 0.199534E+10 | 3391.14 | 03-NOV-14:00 | 21.70 | 17.40 | 0.538183E+09 | 845.62 | 03-NOV-13:20 | 21.70 | 17.40 |
December | 0.108257E+10 | 2566.96 | 13-DEC-13:10 | 20.22 | 17.28 | 0.478928E+09 | 845.61 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.528258E+11 | 0.698192E+10 | ||||||||
Minimum of Months | 0.472485E+09 | 1875.78 | 20.22 | 13.08 | 0.457335E+09 | 796.08 | 18.13 | 11.22 | ||
Maximum of Months | 0.916500E+10 | 15188.78 | 33.30 | 22.52 | 0.690965E+09 | 858.99 | 32.88 | 23.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436993E+09 | 3254.20 | 31-JAN-15:05 | 20.92 | 13.08 | 0.233167E+09 | 548.48 | 31-JAN-15:09 | 20.92 | 13.08 |
February | 0.103711E+10 | 6957.79 | 27-FEB-11:05 | 15.37 | 6.82 | 0.230028E+09 | 548.50 | 28-FEB-11:09 | 20.87 | 12.02 |
March | 0.270824E+10 | 8569.82 | 13-MAR-10:05 | 13.77 | 6.49 | 0.310969E+09 | 548.51 | 08-MAR-11:09 | 13.77 | 6.49 |
April | 0.427803E+10 | 16438.87 | 16-APR-11:23 | 26.65 | 15.57 | 0.287345E+09 | 548.51 | 17-APR-12:09 | 26.88 | 16.71 |
May | 0.610702E+10 | 17784.19 | 07-MAY-09:32 | 24.43 | 19.78 | 0.315079E+09 | 548.55 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.783775E+10 | 19832.09 | 04-JUN-09:51 | 26.70 | 19.39 | 0.315126E+09 | 548.52 | 02-JUN-10:09 | 26.70 | 19.39 |
July | 0.823250E+10 | 19421.00 | 04-JUL-09:42 | 26.83 | 23.40 | 0.294240E+09 | 548.49 | 31-JUL-14:09 | 30.60 | 24.75 |
August | 0.826794E+10 | 19962.66 | 27-AUG-09:41 | 26.83 | 21.78 | 0.328934E+09 | 548.49 | 25-AUG-12:09 | 26.83 | 21.78 |
September | 0.543701E+10 | 18450.08 | 24-SEP-10:02 | 26.38 | 18.55 | 0.290717E+09 | 548.51 | 15-SEP-12:09 | 26.38 | 18.55 |
October | 0.308891E+10 | 9486.70 | 10-OCT-10:05 | 23.77 | 18.74 | 0.288963E+09 | 548.50 | 16-OCT-14:09 | 25.00 | 19.11 |
November | 0.145690E+10 | 5887.28 | 06-NOV-11:05 | 17.30 | 12.97 | 0.274053E+09 | 548.49 | 02-NOV-10:09 | 17.30 | 12.97 |
December | 0.788853E+09 | 4289.33 | 07-DEC-11:03 | 9.37 | 5.26 | 0.243040E+09 | 548.49 | 12-DEC-11:09 | 18.68 | 15.65 |
Annual Sum or Average | 0.496773E+11 | 0.341166E+10 | ||||||||
Minimum of Months | 0.436993E+09 | 3254.20 | 9.37 | 5.26 | 0.230028E+09 | 548.48 | 13.77 | 6.49 | ||
Maximum of Months | 0.826794E+10 | 19962.66 | 26.83 | 23.40 | 0.328934E+09 | 548.55 | 30.60 | 24.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289547E+10 | 18113.86 | 29-JAN-13:13 | 14.27 | 6.19 | 0.547496E+09 | 849.86 | 23-JAN-14:50 | 14.27 | 6.19 |
February | 0.375499E+10 | 19430.79 | 26-FEB-13:42 | 24.32 | 12.55 | 0.510806E+09 | 894.11 | 21-FEB-14:39 | 24.32 | 12.55 |
March | 0.623874E+10 | 17142.01 | 26-MAR-14:03 | 19.08 | 9.01 | 0.658238E+09 | 861.39 | 30-MAR-13:00 | 27.80 | 17.87 |
April | 0.617296E+10 | 18218.13 | 16-APR-13:23 | 28.60 | 16.10 | 0.597763E+09 | 875.15 | 12-APR-13:39 | 28.60 | 16.10 |
May | 0.714774E+10 | 13051.03 | 19-MAY-13:17 | 30.20 | 18.50 | 0.659076E+09 | 862.47 | 19-MAY-13:30 | 30.30 | 18.50 |
June | 0.874065E+10 | 16857.87 | 25-JUN-13:23 | 32.20 | 23.24 | 0.661284E+09 | 845.66 | 02-JUN-13:39 | 32.20 | 23.24 |
July | 0.938537E+10 | 18300.92 | 16-JUL-14:51 | 33.30 | 22.53 | 0.615937E+09 | 846.81 | 14-JUL-13:20 | 33.30 | 22.53 |
August | 0.112753E+11 | 18481.86 | 27-AUG-13:02 | 31.70 | 22.66 | 0.691541E+09 | 858.61 | 25-AUG-13:00 | 31.70 | 22.66 |
September | 0.880823E+10 | 19303.97 | 24-SEP-12:42 | 28.80 | 19.88 | 0.611181E+09 | 854.05 | 11-SEP-13:50 | 28.80 | 19.88 |
October | 0.792066E+10 | 18441.22 | 22-OCT-12:13 | 22.57 | 15.25 | 0.615892E+09 | 918.86 | 10-OCT-13:50 | 22.57 | 15.25 |
November | 0.583256E+10 | 18746.44 | 11-NOV-11:53 | 19.40 | 11.80 | 0.601200E+09 | 901.57 | 06-NOV-14:20 | 19.40 | 11.80 |
December | 0.440192E+10 | 18579.12 | 10-DEC-12:53 | 15.60 | 7.72 | 0.557352E+09 | 850.21 | 27-DEC-10:39 | 8.30 | 4.45 |
Annual Sum or Average | 0.825745E+11 | 0.732777E+10 | ||||||||
Minimum of Months | 0.289547E+10 | 13051.03 | 14.27 | 6.19 | 0.510806E+09 | 845.66 | 8.30 | 4.45 | ||
Maximum of Months | 0.112753E+11 | 19430.79 | 33.30 | 23.24 | 0.691541E+09 | 918.86 | 33.30 | 23.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.690516E+09 | 2745.33 | 23-JAN-16:40 | 10.00 | 3.54 | 0.323682E+09 | 544.93 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.131553E+10 | 9247.37 | 26-FEB-17:02 | 23.72 | 11.96 | 0.311513E+09 | 544.96 | 22-FEB-14:39 | 23.72 | 11.96 |
March | 0.353132E+10 | 11322.09 | 19-MAR-17:33 | 16.30 | 6.21 | 0.419014E+09 | 544.95 | 14-MAR-09:20 | 16.30 | 6.21 |
April | 0.487205E+10 | 20207.13 | 09-APR-16:42 | 21.70 | 10.75 | 0.386761E+09 | 546.83 | 17-APR-15:00 | 28.90 | 16.41 |
May | 0.634800E+10 | 19914.68 | 29-MAY-17:22 | 29.70 | 20.31 | 0.426674E+09 | 556.25 | 19-MAY-13:30 | 29.70 | 20.31 |
June | 0.808428E+10 | 19789.35 | 04-JUN-16:31 | 31.50 | 19.59 | 0.427080E+09 | 544.96 | 02-JUN-13:39 | 31.50 | 19.59 |
July | 0.851505E+10 | 21225.07 | 23-JUL-17:01 | 29.82 | 23.13 | 0.397518E+09 | 544.96 | 07-JUL-09:30 | 29.82 | 23.13 |
August | 0.906928E+10 | 22059.29 | 13-AUG-16:41 | 30.92 | 22.40 | 0.446048E+09 | 544.95 | 10-AUG-13:20 | 30.92 | 22.40 |
September | 0.575770E+10 | 20165.11 | 04-SEP-16:32 | 28.13 | 22.40 | 0.394173E+09 | 544.96 | 25-SEP-13:09 | 28.27 | 18.91 |
October | 0.355458E+10 | 15863.72 | 09-OCT-16:12 | 27.43 | 19.51 | 0.389725E+09 | 544.95 | 16-OCT-09:20 | 17.60 | 16.52 |
November | 0.206124E+10 | 7442.12 | 05-NOV-16:03 | 24.03 | 17.90 | 0.368468E+09 | 544.95 | 03-NOV-13:20 | 24.03 | 17.90 |
December | 0.124140E+10 | 4255.16 | 11-DEC-15:30 | 21.10 | 15.20 | 0.331596E+09 | 544.95 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.550409E+11 | 0.462225E+10 | ||||||||
Minimum of Months | 0.690516E+09 | 2745.33 | 10.00 | 3.54 | 0.311513E+09 | 544.93 | 16.30 | 6.21 | ||
Maximum of Months | 0.906928E+10 | 22059.29 | 31.50 | 23.13 | 0.446048E+09 | 556.25 | 31.50 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294403E+09 | 1833.66 | 20-JAN-16:00 | 17.20 | 12.77 | 0.471255E+09 | 776.93 | 20-JAN-14:00 | 17.20 | 12.77 |
February | 0.794196E+09 | 3664.58 | 28-FEB-15:00 | 25.00 | 13.71 | 0.446702E+09 | 845.62 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.242539E+10 | 6859.93 | 30-MAR-15:20 | 27.80 | 17.21 | 0.594740E+09 | 845.62 | 28-MAR-13:20 | 27.80 | 17.21 |
April | 0.360986E+10 | 7204.13 | 19-APR-14:30 | 26.15 | 17.54 | 0.570660E+09 | 845.64 | 12-APR-13:00 | 26.15 | 17.54 |
May | 0.614824E+10 | 16640.27 | 29-MAY-15:32 | 29.80 | 20.59 | 0.653256E+09 | 845.64 | 16-MAY-13:09 | 29.80 | 20.59 |
June | 0.899933E+10 | 16813.34 | 25-JUN-16:42 | 32.88 | 22.29 | 0.660989E+09 | 845.63 | 09-JUN-13:20 | 32.88 | 22.29 |
July | 0.956323E+10 | 17969.79 | 16-JUL-15:31 | 33.30 | 22.52 | 0.615630E+09 | 845.61 | 03-JUL-13:20 | 33.30 | 22.52 |
August | 0.981399E+10 | 16983.79 | 13-AUG-18:11 | 30.73 | 21.88 | 0.691043E+09 | 845.63 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.554439E+10 | 12336.67 | 07-SEP-05:02 | 22.20 | 21.11 | 0.603245E+09 | 845.63 | 15-SEP-13:20 | 27.97 | 18.13 |
October | 0.270342E+10 | 6496.64 | 02-OCT-14:40 | 26.70 | 20.10 | 0.560876E+09 | 845.62 | 05-OCT-13:20 | 20.00 | 14.95 |
November | 0.140452E+10 | 3083.44 | 02-NOV-15:30 | 22.50 | 16.22 | 0.506883E+09 | 845.62 | 03-NOV-13:20 | 21.30 | 17.04 |
December | 0.595215E+09 | 2041.92 | 13-DEC-15:00 | 18.30 | 16.86 | 0.463835E+09 | 844.87 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.518962E+11 | 0.683911E+10 | ||||||||
Minimum of Months | 0.294403E+09 | 1833.66 | 17.20 | 12.77 | 0.446702E+09 | 776.93 | 17.20 | 12.77 | ||
Maximum of Months | 0.981399E+10 | 17969.79 | 33.30 | 22.52 | 0.691043E+09 | 845.64 | 33.30 | 22.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355578E+09 | 1219.98 | 31-JAN-16:30 | 19.70 | 13.48 | 0.307981E+09 | 517.96 | 31-JAN-14:00 | 19.70 | 13.48 |
February | 0.870813E+09 | 4022.95 | 27-FEB-10:30 | 13.90 | 6.16 | 0.305083E+09 | 544.96 | 22-FEB-14:39 | 13.90 | 6.16 |
March | 0.243773E+10 | 6421.63 | 14-MAR-09:30 | 16.95 | 13.93 | 0.412829E+09 | 545.00 | 08-MAR-10:09 | 16.95 | 13.93 |
April | 0.419636E+10 | 18060.99 | 16-APR-10:13 | 23.50 | 14.96 | 0.386517E+09 | 544.98 | 12-APR-13:00 | 23.50 | 14.96 |
May | 0.641558E+10 | 19001.26 | 07-MAY-09:52 | 25.00 | 20.03 | 0.425813E+09 | 545.19 | 30-MAY-09:00 | 27.80 | 21.16 |
June | 0.850717E+10 | 19335.63 | 11-JUN-09:52 | 25.00 | 14.66 | 0.427032E+09 | 545.25 | 05-JUN-09:00 | 25.00 | 14.66 |
July | 0.901654E+10 | 19096.64 | 23-JUL-08:22 | 25.30 | 22.43 | 0.397303E+09 | 545.86 | 17-JUL-09:00 | 25.30 | 22.43 |
August | 0.900756E+10 | 18659.07 | 13-AUG-08:12 | 24.97 | 22.65 | 0.445876E+09 | 545.34 | 07-AUG-09:00 | 24.97 | 22.65 |
September | 0.566117E+10 | 18841.16 | 04-SEP-09:22 | 25.85 | 21.92 | 0.391802E+09 | 545.59 | 11-SEP-09:00 | 25.00 | 22.21 |
October | 0.283787E+10 | 7319.86 | 11-OCT-10:00 | 22.80 | 18.79 | 0.382920E+09 | 544.95 | 26-OCT-09:50 | 11.55 | 7.83 |
November | 0.126115E+10 | 3255.35 | 06-NOV-10:10 | 14.87 | 12.62 | 0.349855E+09 | 544.95 | 03-NOV-09:20 | 14.87 | 12.62 |
December | 0.625324E+09 | 1628.93 | 13-DEC-13:10 | 20.22 | 17.28 | 0.310795E+09 | 544.95 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.511928E+11 | 0.454381E+10 | ||||||||
Minimum of Months | 0.355578E+09 | 1219.98 | 13.90 | 6.16 | 0.305083E+09 | 517.96 | 11.55 | 6.16 | ||
Maximum of Months | 0.901654E+10 | 19335.63 | 25.85 | 22.65 | 0.445876E+09 | 545.86 | 27.80 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211758E+10 | 10215.96 | 11-JAN-14:30 | 6.70 | 2.05 | 0.533871E+09 | 845.63 | 24-JAN-14:20 | 10.77 | 5.31 |
February | 0.296105E+10 | 20074.17 | 26-FEB-14:52 | 25.00 | 12.75 | 0.497293E+09 | 848.29 | 21-FEB-14:39 | 25.00 | 12.75 |
March | 0.531740E+10 | 15716.14 | 30-MAR-13:40 | 27.43 | 17.97 | 0.636320E+09 | 845.89 | 10-MAR-14:50 | 27.43 | 17.97 |
April | 0.580733E+10 | 15517.40 | 16-APR-12:13 | 27.57 | 15.77 | 0.585214E+09 | 870.06 | 17-APR-13:20 | 28.17 | 16.82 |
May | 0.726240E+10 | 19811.86 | 29-MAY-15:32 | 29.80 | 20.59 | 0.654092E+09 | 857.39 | 19-MAY-13:00 | 29.80 | 20.59 |
June | 0.928487E+10 | 19734.86 | 25-JUN-13:23 | 32.20 | 23.24 | 0.660123E+09 | 845.65 | 02-JUN-13:09 | 32.20 | 23.24 |
July | 0.101228E+11 | 21016.17 | 16-JUL-15:31 | 33.30 | 22.52 | 0.615759E+09 | 846.01 | 31-JUL-13:50 | 30.60 | 24.75 |
August | 0.119816E+11 | 19991.02 | 13-AUG-15:31 | 30.20 | 22.22 | 0.691562E+09 | 853.70 | 25-AUG-13:50 | 30.92 | 18.65 |
September | 0.878361E+10 | 21535.75 | 24-SEP-12:52 | 28.90 | 19.89 | 0.607169E+09 | 855.41 | 22-SEP-13:00 | 28.90 | 19.89 |
October | 0.707293E+10 | 20196.65 | 09-OCT-14:13 | 27.40 | 19.48 | 0.598754E+09 | 890.49 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.457202E+10 | 21129.74 | 11-NOV-14:52 | 21.10 | 11.84 | 0.573905E+09 | 852.13 | 06-NOV-14:20 | 21.10 | 11.84 |
December | 0.319237E+10 | 13065.50 | 10-DEC-14:32 | 17.77 | 8.37 | 0.535563E+09 | 845.63 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.784760E+11 | 0.718962E+10 | ||||||||
Minimum of Months | 0.211758E+10 | 10215.96 | 6.70 | 2.05 | 0.497293E+09 | 845.63 | 10.77 | 5.31 | ||
Maximum of Months | 0.119816E+11 | 21535.75 | 33.30 | 23.24 | 0.691562E+09 | 890.49 | 32.20 | 24.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504684E+09 | 2673.68 | 20-JAN-16:30 | 16.95 | 12.13 | 0.317128E+09 | 544.81 | 20-JAN-14:00 | 16.95 | 12.13 |
February | 0.107006E+10 | 7657.86 | 26-FEB-16:53 | 23.90 | 12.02 | 0.303197E+09 | 544.96 | 22-FEB-14:39 | 23.90 | 12.02 |
March | 0.312669E+10 | 10887.63 | 30-MAR-16:30 | 27.25 | 17.64 | 0.402135E+09 | 544.95 | 09-MAR-10:20 | 27.25 | 17.64 |
April | 0.467365E+10 | 20052.88 | 09-APR-16:52 | 21.70 | 10.78 | 0.378684E+09 | 549.73 | 17-APR-15:00 | 28.90 | 16.41 |
May | 0.645516E+10 | 21771.77 | 21-MAY-16:42 | 26.70 | 19.84 | 0.424219E+09 | 544.96 | 16-MAY-13:09 | 26.70 | 19.84 |
June | 0.848442E+10 | 21153.31 | 25-JUN-16:42 | 32.88 | 22.29 | 0.426696E+09 | 544.96 | 09-JUN-13:20 | 32.88 | 22.29 |
July | 0.903957E+10 | 23341.38 | 16-JUL-16:11 | 33.13 | 22.54 | 0.397439E+09 | 544.94 | 03-JUL-13:20 | 33.13 | 22.54 |
August | 0.954573E+10 | 22660.50 | 13-AUG-18:11 | 30.73 | 21.88 | 0.446071E+09 | 544.96 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.574922E+10 | 21621.58 | 04-SEP-16:42 | 28.22 | 22.25 | 0.391915E+09 | 544.96 | 25-SEP-13:09 | 28.27 | 18.91 |
October | 0.320645E+10 | 15968.32 | 09-OCT-16:12 | 27.43 | 19.51 | 0.375977E+09 | 544.95 | 05-OCT-13:20 | 27.43 | 19.51 |
November | 0.163574E+10 | 7030.21 | 06-NOV-16:00 | 20.60 | 10.48 | 0.349577E+09 | 544.95 | 03-NOV-13:20 | 20.60 | 10.48 |
December | 0.855186E+09 | 3367.84 | 11-DEC-15:50 | 21.10 | 15.67 | 0.319230E+09 | 544.95 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.543466E+11 | 0.453227E+10 | ||||||||
Minimum of Months | 0.504684E+09 | 2673.68 | 16.95 | 10.48 | 0.303197E+09 | 544.81 | 16.95 | 10.48 | ||
Maximum of Months | 0.954573E+10 | 23341.38 | 33.13 | 22.54 | 0.446071E+09 | 549.73 | 33.13 | 22.54 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325906E+09 | 4635.26 | 14-JAN-06:01 | -6.7 | -7.8 | 0.00 | 0.00 | 01-JAN-00:10 | -6.7 | -7.8 |
February | 0.115540E+10 | 4678.94 | 27-FEB-06:15 | 9.63 | 4.65 | 0.00 | 0.00 | 01-FEB-00:10 | 9.63 | 4.65 |
March | 0.373143E+10 | 5892.03 | 13-MAR-05:15 | 6.70 | 2.88 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 2.88 |
April | 0.522603E+10 | 7723.87 | 17-APR-14:15 | 28.90 | 16.56 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.56 |
May | 0.591423E+10 | 11034.47 | 30-MAY-05:15 | 19.07 | 17.52 | 0.00 | 0.00 | 01-MAY-00:10 | 19.07 | 17.52 |
June | 0.811335E+10 | 10501.69 | 26-JUN-05:15 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.901765E+10 | 12303.81 | 10-JUL-05:13 | 20.73 | 19.68 | 0.00 | 0.00 | 01-JUL-00:10 | 20.73 | 19.68 |
August | 0.103146E+11 | 12125.54 | 14-AUG-05:15 | 23.30 | 20.62 | 0.00 | 0.00 | 01-AUG-00:10 | 23.30 | 20.62 |
September | 0.645039E+10 | 11791.23 | 05-SEP-05:15 | 21.70 | 20.50 | 0.00 | 0.00 | 01-SEP-00:10 | 21.70 | 20.50 |
October | 0.447522E+10 | 10080.89 | 10-OCT-05:15 | 15.73 | 14.81 | 0.00 | 0.00 | 01-OCT-00:10 | 15.73 | 14.81 |
November | 0.303532E+10 | 7224.23 | 06-NOV-06:13 | 9.23 | 8.65 | 0.00 | 0.00 | 01-NOV-00:10 | 9.23 | 8.65 |
December | 0.154427E+10 | 4574.21 | 13-DEC-06:15 | 16.70 | 15.65 | 0.00 | 0.00 | 01-DEC-00:10 | 16.70 | 15.65 |
Annual Sum or Average | 0.593037E+11 | 0.00 | ||||||||
Minimum of Months | 0.325906E+09 | 4574.21 | -6.7 | -7.8 | 0.00 | 0.00 | -6.7 | -7.8 | ||
Maximum of Months | 0.103146E+11 | 12303.81 | 28.90 | 21.67 | 0.00 | 0.00 | 28.90 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120680E+09 | 6684.76 | 28-JAN-05:01 | -3.3 | -5.3 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -5.3 |
February | 0.330692E+09 | 8558.45 | 12-FEB-06:11 | -12.4 | -13.5 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.5 |
March | 0.138778E+10 | 4999.67 | 18-MAR-05:03 | 3.22 | 0.02 | 0.00 | 0.00 | 01-MAR-00:10 | 3.22 | 0.02 |
April | 0.271640E+10 | 5579.06 | 17-APR-15:50 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.433390E+10 | 6122.93 | 30-MAY-14:20 | 30.60 | 21.17 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 21.17 |
June | 0.634328E+10 | 7612.28 | 19-JUN-05:15 | 20.93 | 20.12 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 20.12 |
July | 0.694269E+10 | 9154.66 | 10-JUL-05:13 | 20.73 | 19.68 | 0.00 | 0.00 | 01-JUL-00:10 | 20.73 | 19.68 |
August | 0.748294E+10 | 8703.12 | 21-AUG-05:15 | 21.87 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 21.87 | 21.87 |
September | 0.482787E+10 | 8023.06 | 11-SEP-05:13 | 20.20 | 19.05 | 0.00 | 0.00 | 01-SEP-00:10 | 20.20 | 19.05 |
October | 0.223787E+10 | 4020.10 | 11-OCT-15:50 | 26.28 | 17.62 | 0.00 | 0.00 | 01-OCT-00:10 | 26.28 | 17.62 |
November | 0.750385E+09 | 6931.98 | 21-NOV-05:01 | -2.3 | -3.6 | 0.00 | 0.00 | 01-NOV-00:10 | -2.3 | -3.6 |
December | 0.280931E+09 | 7079.86 | 01-DEC-05:01 | -3.0 | -4.3 | 0.00 | 0.00 | 01-DEC-00:10 | -3.0 | -4.3 |
Annual Sum or Average | 0.377554E+11 | 0.00 | ||||||||
Minimum of Months | 0.120680E+09 | 4020.10 | -12.4 | -13.5 | 0.00 | 0.00 | -12.4 | -13.5 | ||
Maximum of Months | 0.748294E+10 | 9154.66 | 30.60 | 21.87 | 0.00 | 0.00 | 30.60 | 21.87 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24274481.65 | 1045.02 | 29-JAN-15:30 | 16.15 | 6.57 | 0.00 | 0.00 | 01-JAN-00:10 | 16.15 | 6.57 |
February | 0.472766E+09 | 6099.72 | 28-FEB-16:00 | 23.30 | 12.53 | 0.00 | 0.00 | 01-FEB-00:10 | 23.30 | 12.53 |
March | 0.227017E+10 | 13174.89 | 30-MAR-15:40 | 27.80 | 17.34 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.34 |
April | 0.488686E+10 | 17770.84 | 17-APR-14:53 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.836913E+10 | 17835.49 | 19-MAY-13:20 | 30.20 | 18.50 | 0.00 | 0.00 | 01-MAY-00:10 | 30.20 | 18.50 |
June | 0.120358E+11 | 17871.80 | 12-JUN-14:50 | 33.12 | 22.69 | 0.00 | 0.00 | 01-JUN-00:10 | 33.12 | 22.69 |
July | 0.127998E+11 | 19745.95 | 07-JUL-15:10 | 35.10 | 23.86 | 0.00 | 0.00 | 01-JUL-00:10 | 35.10 | 23.86 |
August | 0.133211E+11 | 18576.88 | 01-AUG-14:20 | 34.27 | 23.72 | 0.00 | 0.00 | 01-AUG-00:10 | 34.27 | 23.72 |
September | 0.694905E+10 | 15268.31 | 06-SEP-14:50 | 29.68 | 22.88 | 0.00 | 0.00 | 01-SEP-00:10 | 29.68 | 22.88 |
October | 0.291627E+10 | 10753.99 | 10-OCT-14:50 | 28.98 | 20.71 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 20.71 |
November | 0.676193E+09 | 4574.90 | 02-NOV-15:00 | 22.80 | 16.47 | 0.00 | 0.00 | 01-NOV-00:10 | 22.80 | 16.47 |
December | 94325694.00 | 2411.99 | 12-DEC-14:40 | 22.80 | 16.47 | 0.00 | 0.00 | 01-DEC-00:10 | 22.80 | 16.47 |
Annual Sum or Average | 0.648157E+11 | 0.00 | ||||||||
Minimum of Months | 24274481.65 | 1045.02 | 16.15 | 6.57 | 0.00 | 0.00 | 16.15 | 6.57 | ||
Maximum of Months | 0.133211E+11 | 19745.95 | 35.10 | 23.86 | 0.00 | 0.00 | 35.10 | 23.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269179E+10 | 1729.68 | 26-JAN-17:30 | 1.40 | -3.2 | 95230835.48 | 126.84 | 20-JAN-10:00 | 1.40 | -3.2 |
February | 0.760296E+10 | 4046.79 | 20-FEB-17:45 | 17.38 | 9.48 | 86397281.96 | 126.84 | 17-FEB-14:00 | 17.38 | 9.48 |
March | 0.142400E+11 | 7114.52 | 31-MAR-24:00 | 12.10 | 7.93 | 0.103239E+09 | 126.84 | 31-MAR-13:09 | 12.10 | 7.93 |
April | 0.188170E+11 | 7997.78 | 09-APR-18:15 | 19.80 | 10.92 | 91606263.17 | 126.83 | 03-APR-09:00 | 19.80 | 10.92 |
May | 0.433792E+10 | 3423.53 | 31-MAY-24:00 | 21.00 | 18.72 | 99239468.09 | 126.85 | 30-MAY-13:00 | 21.00 | 18.72 |
June | 0.925801E+10 | 5338.51 | 30-JUN-24:00 | 22.30 | 21.46 | 98972922.82 | 126.86 | 26-JUN-09:00 | 22.30 | 21.46 |
July | 0.146550E+11 | 7232.14 | 31-JUL-24:00 | 25.20 | 21.98 | 91891644.45 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.196978E+11 | 7823.85 | 20-AUG-17:20 | 27.23 | 23.86 | 0.105152E+09 | 136.37 | 02-AUG-13:00 | 27.23 | 23.86 |
September | 0.430068E+10 | 3218.69 | 30-SEP-24:00 | 16.80 | 15.75 | 91610220.11 | 126.84 | 25-SEP-09:00 | 16.80 | 15.75 |
October | 0.928624E+10 | 5106.13 | 31-OCT-24:00 | 9.70 | 6.26 | 95237539.65 | 126.86 | 18-OCT-13:00 | 9.70 | 6.26 |
November | 0.137225E+11 | 5947.16 | 11-NOV-17:05 | 18.95 | 10.47 | 94301925.07 | 126.84 | 27-NOV-14:00 | 22.20 | 17.55 |
December | 0.189525E+11 | 7690.75 | 10-DEC-16:55 | 17.20 | 8.59 | 91881283.26 | 126.83 | 13-DEC-10:09 | 18.48 | 16.98 |
Annual Sum or Average | 0.137562E+12 | 0.114476E+10 | ||||||||
Minimum of Months | 0.269179E+10 | 1729.68 | 1.40 | -3.2 | 86397281.96 | 126.83 | 1.40 | -3.2 | ||
Maximum of Months | 0.196978E+11 | 7997.78 | 27.23 | 23.86 | 0.105152E+09 | 136.37 | 27.23 | 23.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.598920E+09 | 1442.62 | 26-JAN-17:40 | 1.13 | -3.4 | 94419857.53 | 127.14 | 17-JAN-10:39 | 1.13 | -3.4 |
February | 0.550422E+10 | 3588.91 | 24-FEB-18:00 | 15.00 | 6.59 | 86397246.82 | 126.84 | 17-FEB-14:00 | 15.00 | 6.59 |
March | 0.127523E+11 | 6660.66 | 31-MAR-23:40 | 12.17 | 7.92 | 0.103239E+09 | 126.84 | 31-MAR-13:09 | 12.17 | 7.92 |
April | 0.175861E+11 | 7423.91 | 09-APR-18:30 | 19.15 | 10.75 | 91606059.42 | 126.83 | 03-APR-09:00 | 19.15 | 10.75 |
May | 0.385294E+10 | 3233.72 | 31-MAY-24:00 | 21.00 | 18.72 | 99237100.27 | 126.84 | 04-MAY-13:00 | 21.00 | 18.72 |
June | 0.869663E+10 | 5075.51 | 30-JUN-24:00 | 22.30 | 21.46 | 98972300.34 | 126.85 | 23-JUN-09:00 | 22.30 | 21.46 |
July | 0.139322E+11 | 6965.54 | 31-JUL-24:00 | 25.20 | 21.98 | 91891058.90 | 126.84 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.186987E+11 | 7363.85 | 20-AUG-16:32 | 27.97 | 24.54 | 0.104980E+09 | 135.61 | 02-AUG-13:00 | 27.97 | 24.54 |
September | 0.377540E+10 | 2749.74 | 30-SEP-24:00 | 16.80 | 15.75 | 91608662.33 | 126.84 | 18-SEP-09:00 | 16.80 | 15.75 |
October | 0.803279E+10 | 4415.98 | 31-OCT-23:40 | 9.67 | 6.08 | 95237156.93 | 126.86 | 18-OCT-13:09 | 9.67 | 6.08 |
November | 0.118444E+11 | 5409.01 | 06-NOV-17:00 | 18.90 | 9.61 | 94301855.73 | 126.83 | 27-NOV-10:00 | 19.40 | 16.85 |
December | 0.159103E+11 | 6989.51 | 08-DEC-17:00 | 11.10 | 4.72 | 91881326.12 | 126.83 | 06-DEC-14:00 | 11.10 | 4.72 |
Annual Sum or Average | 0.121185E+12 | 0.114377E+10 | ||||||||
Minimum of Months | 0.598920E+09 | 1442.62 | 1.13 | -3.4 | 86397246.82 | 126.83 | 1.13 | -3.4 | ||
Maximum of Months | 0.186987E+11 | 7423.91 | 27.97 | 24.54 | 0.104980E+09 | 135.61 | 27.97 | 24.54 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270644E+09 | 1376.43 | 20-JAN-17:00 | 16.70 | 11.48 | 90526590.86 | 126.85 | 18-JAN-14:09 | 16.70 | 11.48 |
February | 0.431134E+10 | 3534.73 | 24-FEB-17:50 | 15.18 | 6.70 | 86394721.40 | 126.84 | 17-FEB-14:00 | 15.18 | 6.70 |
March | 0.119212E+11 | 6423.83 | 31-MAR-23:20 | 12.23 | 7.91 | 0.103239E+09 | 126.84 | 31-MAR-13:09 | 12.23 | 7.91 |
April | 0.171863E+11 | 7464.79 | 09-APR-18:23 | 19.15 | 10.75 | 91606216.15 | 126.83 | 03-APR-09:00 | 19.15 | 10.75 |
May | 0.376311E+10 | 3179.65 | 31-MAY-24:00 | 21.00 | 18.72 | 99237676.61 | 126.85 | 30-MAY-13:00 | 21.00 | 18.72 |
June | 0.875184E+10 | 5041.07 | 30-JUN-24:00 | 22.30 | 21.46 | 98973003.01 | 126.86 | 26-JUN-13:00 | 22.30 | 21.46 |
July | 0.140330E+11 | 6989.55 | 31-JUL-24:00 | 25.20 | 21.98 | 91891661.77 | 126.85 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.188127E+11 | 7616.07 | 20-AUG-17:17 | 27.23 | 23.86 | 0.104522E+09 | 134.99 | 02-AUG-13:00 | 27.23 | 23.86 |
September | 0.364449E+10 | 2291.63 | 30-SEP-24:00 | 16.80 | 15.75 | 91608510.06 | 126.84 | 25-SEP-13:09 | 16.80 | 15.75 |
October | 0.725875E+10 | 3930.52 | 31-OCT-23:20 | 9.63 | 5.89 | 95237215.11 | 126.86 | 18-OCT-13:00 | 9.63 | 5.89 |
November | 0.105397E+11 | 5389.58 | 06-NOV-17:00 | 18.90 | 9.61 | 94301913.33 | 126.83 | 27-NOV-10:00 | 19.40 | 16.85 |
December | 0.140930E+11 | 6889.15 | 07-DEC-17:00 | 14.40 | 6.55 | 91881410.23 | 126.83 | 06-DEC-14:00 | 14.40 | 6.55 |
Annual Sum or Average | 0.114586E+12 | 0.113942E+10 | ||||||||
Minimum of Months | 0.270644E+09 | 1376.43 | 9.63 | 5.89 | 86394721.40 | 126.83 | 9.63 | 5.89 | ||
Maximum of Months | 0.188127E+11 | 7616.07 | 27.23 | 23.86 | 0.104522E+09 | 134.99 | 27.23 | 23.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233837E+12 | 89960.77 | 20-JAN-17:00 | 16.70 | 11.48 | 0.206143E+10 | 2745.30 | 20-JAN-14:09 | 16.70 | 11.48 |
February | 0.431398E+12 | 181568.76 | 21-FEB-17:00 | 21.70 | 10.37 | 0.187024E+10 | 2745.64 | 08-FEB-10:20 | 21.70 | 10.37 |
March | 0.724288E+12 | 357116.18 | 31-MAR-24:00 | 12.10 | 7.93 | 0.223521E+10 | 2750.30 | 09-MAR-14:09 | 12.10 | 7.93 |
April | 0.936369E+12 | 367749.06 | 15-APR-17:01 | 26.42 | 15.32 | 0.200546E+10 | 3224.80 | 17-APR-13:00 | 28.90 | 16.63 |
May | 0.237025E+12 | 174425.08 | 31-MAY-24:00 | 21.00 | 18.72 | 0.214827E+10 | 2746.58 | 05-MAY-13:09 | 21.00 | 18.72 |
June | 0.467145E+12 | 266447.50 | 30-JUN-24:00 | 22.30 | 21.46 | 0.214261E+10 | 2748.26 | 02-JUN-09:09 | 22.30 | 21.46 |
July | 0.729070E+12 | 358856.28 | 31-JUL-24:00 | 25.20 | 21.98 | 0.198917E+10 | 2745.90 | 26-JUL-09:09 | 25.20 | 21.98 |
August | 0.970061E+12 | 369430.51 | 07-AUG-21:23 | 22.50 | 21.53 | 0.255040E+10 | 3590.40 | 18-AUG-13:39 | 33.67 | 22.87 |
September | 0.234612E+12 | 175310.44 | 30-SEP-24:00 | 16.80 | 15.75 | 0.198344E+10 | 2746.89 | 28-SEP-13:00 | 16.80 | 15.75 |
October | 0.485780E+12 | 267422.41 | 31-OCT-24:00 | 9.70 | 6.26 | 0.206162E+10 | 2747.18 | 05-OCT-13:00 | 9.70 | 6.26 |
November | 0.706821E+12 | 275577.47 | 06-NOV-17:00 | 18.90 | 9.61 | 0.204174E+10 | 2750.67 | 03-NOV-13:09 | 18.90 | 9.61 |
December | 0.973216E+12 | 366256.58 | 11-DEC-17:00 | 20.60 | 15.75 | 0.198934E+10 | 2771.03 | 13-DEC-10:00 | 19.40 | 17.57 |
Annual Sum or Average | 0.712962E+13 | 0.250789E+11 | ||||||||
Minimum of Months | 0.233837E+12 | 89960.77 | 9.70 | 6.26 | 0.187024E+10 | 2745.30 | 9.70 | 6.26 | ||
Maximum of Months | 0.973216E+12 | 369430.51 | 26.42 | 21.98 | 0.255040E+10 | 3590.40 | 33.67 | 22.87 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271864E+09 | 9764.44 | 31-JAN-05:15 | 10.00 |
February | 53462168.54 | 9881.07 | 28-FEB-05:15 | 10.60 |
March | 0.135417E+09 | 9872.68 | 15-MAR-04:15 | 8.30 |
April | 0.172586E+09 | 13212.06 | 15-APR-16:01 | 28.03 |
May | 0.246986E+09 | 15397.80 | 06-MAY-16:01 | 29.63 |
June | 0.235066E+09 | 20333.39 | 24-JUN-16:01 | 33.22 |
July | 0.328707E+09 | 24779.90 | 08-JUL-16:01 | 36.32 |
August | 0.360535E+09 | 19037.12 | 19-AUG-16:01 | 32.33 |
September | 0.487487E+09 | 13968.59 | 23-SEP-16:01 | 28.72 |
October | 0.412088E+09 | 9952.96 | 25-OCT-04:17 | 10.00 |
November | 0.394901E+09 | 11558.86 | 12-NOV-11:23 | 15.30 |
December | 0.125381E+09 | 9515.62 | 19-DEC-04:03 | 0.00 |
Annual Sum or Average | 0.322448E+10 | |||
Minimum of Months | 53462168.54 | 9515.62 | 0.00 | |
Maximum of Months | 0.487487E+09 | 24779.90 | 36.32 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152095E+09 | 40336.01 | 09-JAN-05:11 | -2.2 |
February | 35965180.10 | 37414.22 | 13-FEB-06:02 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.188060E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.152095E+09 | 40336.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406684E+10 | 69905.00 | 09-JAN-04:01 | -1.8 |
February | 0.177833E+10 | 69141.47 | 13-FEB-04:01 | -5.0 |
March | 10931930.80 | 55643.93 | 20-MAR-05:03 | 5.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 8802986.26 | 51402.30 | 30-OCT-05:03 | 8.90 |
November | 0.146426E+09 | 57698.70 | 22-NOV-06:01 | -3.3 |
December | 0.178203E+10 | 66470.82 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.779336E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.406684E+10 | 69905.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252921E+09 | 11340.49 | 09-JAN-05:01 | -2.2 |
February | 92513841.07 | 11413.00 | 13-FEB-05:01 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 580143.90 | 7008.56 | 22-NOV-06:01 | -3.3 |
December | 957578.33 | 6071.58 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.346973E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.252921E+09 | 11413.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180570E+09 | 9782.15 | 09-JAN-05:01 | -2.2 |
February | 59861745.13 | 9849.05 | 13-FEB-05:01 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 1791084.21 | 7985.70 | 22-NOV-06:01 | -3.3 |
December | 9678978.40 | 8031.66 | 01-DEC-06:01 | -3.9 |
Annual Sum or Average | 0.251901E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.180570E+09 | 9849.05 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316856E+09 | 14212.52 | 09-JAN-05:01 | -2.2 |
February | 0.118374E+09 | 13821.18 | 13-FEB-05:01 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 4362665.48 | 11643.62 | 22-NOV-06:01 | -3.3 |
December | 22668780.60 | 11884.22 | 01-DEC-06:01 | -3.9 |
Annual Sum or Average | 0.462261E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.316856E+09 | 14212.52 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13487993.88 | 7702.95 | 07-JAN-06:01 | -1.3 |
February | 1035453.59 | 6786.06 | 13-FEB-06:02 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 14523447.47 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 13487993.88 | 7702.95 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340936E+10 | 12801.17 | 09-JAN-03:13 | -1.3 |
February | 0.176292E+10 | 13122.75 | 12-FEB-06:11 | -12.4 |
March | 75155753.82 | 10613.50 | 22-MAR-04:11 | 6.50 |
April | 15713739.03 | 10145.50 | 06-APR-05:03 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 20167362.06 | 10396.59 | 26-OCT-05:02 | 2.20 |
November | 0.270965E+09 | 11474.04 | 22-NOV-05:01 | -2.9 |
December | 0.123239E+10 | 12252.66 | 18-DEC-04:01 | -4.1 |
Annual Sum or Average | 0.678666E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.340936E+10 | 13122.75 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174627E+10 | 14636.39 | 09-JAN-04:01 | -1.8 |
February | 0.837883E+09 | 15297.96 | 12-FEB-06:11 | -12.4 |
March | 35906437.31 | 11534.10 | 06-MAR-06:02 | 3.22 |
April | 5228616.52 | 8269.38 | 06-APR-05:03 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 12465158.70 | 11642.74 | 26-OCT-05:02 | 2.20 |
November | 0.105144E+09 | 13187.07 | 22-NOV-05:01 | -2.9 |
December | 0.563258E+09 | 14283.88 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.330615E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.174627E+10 | 15297.96 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169983E+10 | 14981.64 | 09-JAN-04:01 | -1.8 |
February | 0.810610E+09 | 15540.07 | 12-FEB-06:51 | -12.8 |
March | 27838125.41 | 12159.57 | 22-MAR-05:02 | 6.02 |
April | 6199750.75 | 9508.64 | 06-APR-05:03 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 7783704.93 | 7983.72 | 26-OCT-05:02 | 2.20 |
November | 90288185.22 | 13260.75 | 21-NOV-05:01 | -2.3 |
December | 0.507477E+09 | 14443.98 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.315002E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.169983E+10 | 15540.07 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135646E+10 | 15211.57 | 09-JAN-04:01 | -1.8 |
February | 0.633902E+09 | 15235.73 | 13-FEB-04:01 | -5.0 |
March | 10071553.02 | 10017.28 | 22-MAR-05:02 | 6.02 |
April | 874310.50 | 3000.87 | 06-APR-05:03 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 3530412.22 | 5769.45 | 26-OCT-05:02 | 2.20 |
November | 83506863.23 | 13562.50 | 22-NOV-05:01 | -2.9 |
December | 0.417869E+09 | 14350.00 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.250621E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.135646E+10 | 15235.73 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720214E+10 | 15298.05 | 08-JAN-03:13 | -5.6 |
February | 0.418147E+10 | 16058.81 | 12-FEB-05:02 | -11.8 |
March | 0.584642E+09 | 13238.08 | 20-MAR-04:11 | 6.13 |
April | 0.153046E+09 | 12768.90 | 06-APR-04:02 | 0.92 |
May | 459306.90 | 2129.83 | 11-MAY-05:02 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.270204E+09 | 13195.41 | 26-OCT-04:11 | 2.60 |
November | 0.134820E+10 | 14587.62 | 22-NOV-04:01 | -2.8 |
December | 0.403688E+10 | 15166.96 | 17-DEC-08:13 | -2.0 |
Annual Sum or Average | 0.177770E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.720214E+10 | 16058.81 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380384E+10 | 15788.72 | 08-JAN-03:13 | -5.6 |
February | 0.213276E+10 | 16663.10 | 12-FEB-05:02 | -11.8 |
March | 0.264537E+09 | 13752.26 | 22-MAR-04:11 | 6.50 |
April | 60848733.12 | 13134.25 | 06-APR-04:02 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.146529E+09 | 13653.07 | 26-OCT-04:11 | 2.60 |
November | 0.595075E+09 | 15025.49 | 22-NOV-04:01 | -2.8 |
December | 0.194085E+10 | 15542.91 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.894444E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.380384E+10 | 16663.10 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408747E+10 | 17628.10 | 09-JAN-03:13 | -1.3 |
February | 0.237871E+10 | 18486.01 | 12-FEB-05:02 | -11.8 |
March | 0.310715E+09 | 15196.35 | 22-MAR-04:11 | 6.50 |
April | 0.106343E+09 | 14526.33 | 06-APR-04:02 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.167938E+09 | 14736.24 | 31-OCT-04:12 | 8.70 |
November | 0.614118E+09 | 16338.09 | 21-NOV-04:01 | -1.8 |
December | 0.198475E+10 | 17296.08 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.965004E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.408747E+10 | 18486.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322828E+10 | 17183.52 | 23-JAN-04:11 | -1.3 |
February | 0.167556E+10 | 18229.90 | 12-FEB-05:02 | -11.8 |
March | 0.149240E+09 | 14917.40 | 22-MAR-04:11 | 6.50 |
April | 41650682.06 | 11488.62 | 06-APR-04:02 | 0.92 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 75341755.40 | 14505.90 | 26-OCT-04:11 | 2.60 |
November | 0.480806E+09 | 16309.37 | 22-NOV-04:01 | -2.8 |
December | 0.145314E+10 | 17111.62 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.710401E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.322828E+10 | 18229.90 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.866855E+09 | 9119.12 | 17-JAN-06:02 | 4.72 |
February | 0.512667E+09 | 9368.81 | 08-FEB-06:03 | 7.38 |
March | 0.103245E+09 | 8998.30 | 22-MAR-04:11 | 6.50 |
April | 0.101982E+09 | 8751.75 | 04-APR-04:12 | 15.60 |
May | 56723960.64 | 8153.46 | 01-MAY-04:12 | 16.10 |
June | 68956688.48 | 6420.71 | 16-JUN-04:12 | 20.60 |
July | 78313770.91 | 7414.49 | 28-JUL-04:12 | 19.40 |
August | 62335239.88 | 8143.48 | 27-AUG-15:41 | 31.70 |
September | 59174192.12 | 6116.79 | 27-SEP-04:12 | 22.80 |
October | 86029451.18 | 9421.87 | 02-OCT-04:12 | 18.70 |
November | 0.120093E+09 | 10092.15 | 27-NOV-05:12 | 15.73 |
December | 0.116600E+09 | 12241.11 | 26-DEC-05:11 | 3.70 |
Annual Sum or Average | 0.223297E+10 | |||
Minimum of Months | 56723960.64 | 6116.79 | 3.70 | |
Maximum of Months | 0.866855E+09 | 12241.11 | 31.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299077E+10 | 7696.41 | 09-JAN-06:15 | -2.6 |
February | 0.156492E+10 | 6102.59 | 26-FEB-17:02 | 23.72 |
March | 0.215714E+09 | 6089.28 | 24-MAR-05:03 | 11.52 |
April | 41797171.16 | 5931.14 | 16-APR-15:22 | 26.95 |
May | 43054013.60 | 5045.29 | 01-MAY-04:12 | 16.10 |
June | 38333067.04 | 5697.58 | 25-JUN-16:02 | 33.22 |
July | 55528310.14 | 7068.46 | 02-JUL-16:51 | 30.60 |
August | 40911160.36 | 7208.86 | 13-AUG-16:41 | 30.92 |
September | 41194177.74 | 5762.94 | 24-SEP-14:42 | 28.80 |
October | 0.143047E+09 | 5786.83 | 25-OCT-05:03 | 9.90 |
November | 0.416408E+09 | 6501.67 | 20-NOV-06:03 | 6.02 |
December | 0.145767E+10 | 5757.75 | 14-DEC-06:02 | 6.60 |
Annual Sum or Average | 0.704934E+10 | |||
Minimum of Months | 38333067.04 | 5045.29 | -2.6 | |
Maximum of Months | 0.299077E+10 | 7696.41 | 33.22 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.847112E+10 | 22156.84 | 09-JAN-05:20 | -2.2 |
February | 0.517486E+10 | 25971.76 | 13-FEB-05:12 | -5.2 |
March | 0.168214E+10 | 11594.68 | 14-MAR-05:03 | 13.30 |
April | 0.875404E+09 | 12275.16 | 05-APR-05:02 | 11.42 |
May | 0.275566E+09 | 12666.70 | 12-MAY-05:02 | 11.60 |
June | 0.121644E+09 | 13461.35 | 08-JUN-05:02 | 11.70 |
July | 41017323.10 | 10332.12 | 03-JUL-04:12 | 17.80 |
August | 36641991.78 | 9659.95 | 28-AUG-04:12 | 21.30 |
September | 0.236466E+09 | 12354.40 | 14-SEP-05:03 | 12.20 |
October | 0.131091E+10 | 12671.51 | 03-OCT-05:02 | 11.60 |
November | 0.254020E+10 | 14934.96 | 22-NOV-06:12 | -3.3 |
December | 0.531244E+10 | 22293.05 | 18-DEC-05:12 | -5.0 |
Annual Sum or Average | 0.260784E+11 | |||
Minimum of Months | 36641991.78 | 9659.95 | -5.2 | |
Maximum of Months | 0.847112E+10 | 25971.76 | 21.30 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363508E+09 | 523.80 | 08-JAN-19:00 | -0.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.363508E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.363508E+09 | 523.80 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692158E+09 | 578.49 | 22-JAN-18:55 | 1.10 |
February | 46981414.91 | 525.18 | 12-FEB-06:40 | -12.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.739140E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.692158E+09 | 578.49 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.690800E+09 | 1041.09 | 03-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.622349E+09 | 1113.16 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.672050E+09 | 1050.45 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.579748E+09 | 942.04 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.605943E+09 | 623.15 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.596395E+09 | 613.34 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565990E+09 | 641.91 | 27-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.640611E+09 | 892.47 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.597241E+09 | 988.16 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.665832E+09 | 1144.27 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.669654E+09 | 1128.98 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.674367E+09 | 1044.07 | 06-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.758098E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565990E+09 | 613.34 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.690800E+09 | 1144.27 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433145E+09 | 655.13 | 03-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.391696E+09 | 717.19 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.428468E+09 | 668.93 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.372798E+09 | 577.92 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.392770E+09 | 375.14 | 02-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.386909E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.366350E+09 | 402.23 | 27-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.413184E+09 | 542.31 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.381871E+09 | 616.86 | 29-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.416707E+09 | 737.40 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.424149E+09 | 720.94 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.423241E+09 | 657.31 | 06-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.483129E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.366350E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.433145E+09 | 737.40 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.657597E+09 | 1025.41 | 03-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.599994E+09 | 1113.19 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.666015E+09 | 1048.83 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.581621E+09 | 946.15 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.611998E+09 | 636.30 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.602316E+09 | 626.38 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.571664E+09 | 768.64 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.643738E+09 | 904.07 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.594706E+09 | 978.84 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.642552E+09 | 1144.30 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.644542E+09 | 1122.69 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.638968E+09 | 1026.93 | 06-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.745571E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.571664E+09 | 626.38 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.666015E+09 | 1144.30 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434124E+09 | 673.51 | 03-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.394983E+09 | 717.19 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.433381E+09 | 680.83 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.374554E+09 | 625.38 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.393829E+09 | 547.36 | 24-MAY-07:30 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.387082E+09 | 410.30 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.367787E+09 | 524.62 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.414926E+09 | 597.94 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.385682E+09 | 644.30 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.425453E+09 | 737.40 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.421509E+09 | 728.79 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.421830E+09 | 674.62 | 06-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.485514E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.367787E+09 | 410.30 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.434124E+09 | 737.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.687658E+09 | 1039.82 | 03-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.619995E+09 | 1112.80 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670684E+09 | 1049.36 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.578852E+09 | 939.57 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.605596E+09 | 618.50 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595954E+09 | 608.09 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565414E+09 | 638.34 | 27-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.640102E+09 | 889.42 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.596134E+09 | 986.31 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.663177E+09 | 1144.24 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.667293E+09 | 1128.73 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.671674E+09 | 1042.82 | 06-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.756253E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565414E+09 | 608.09 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.687658E+09 | 1144.24 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.432106E+09 | 653.22 | 03-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.390694E+09 | 716.62 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.427956E+09 | 667.33 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.372548E+09 | 574.83 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.392470E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.386627E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.366020E+09 | 399.77 | 27-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.412835E+09 | 538.28 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.381537E+09 | 614.12 | 29-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.415956E+09 | 737.35 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.423330E+09 | 720.56 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.422212E+09 | 655.44 | 06-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.482429E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.366020E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.432106E+09 | 737.35 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.656878E+09 | 1024.11 | 03-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.599079E+09 | 1112.82 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.665316E+09 | 1047.74 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.580835E+09 | 943.70 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.611402E+09 | 632.36 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.601843E+09 | 621.82 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.571092E+09 | 763.62 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.643152E+09 | 901.10 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.594034E+09 | 976.95 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.641715E+09 | 1144.27 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.643447E+09 | 1122.41 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.638418E+09 | 1025.65 | 06-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.744721E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.571092E+09 | 621.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.665316E+09 | 1144.27 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433119E+09 | 671.81 | 03-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.393674E+09 | 716.62 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432476E+09 | 679.29 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.374014E+09 | 622.37 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.393328E+09 | 541.74 | 24-MAY-07:30 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.386614E+09 | 407.83 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.367283E+09 | 518.93 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.414427E+09 | 594.22 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.385008E+09 | 641.81 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.424079E+09 | 737.35 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.420675E+09 | 728.51 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.420799E+09 | 672.95 | 06-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.484550E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.367283E+09 | 407.83 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.433119E+09 | 737.35 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.687505E+09 | 1039.60 | 03-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.619904E+09 | 1112.72 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670649E+09 | 1049.16 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.578832E+09 | 939.16 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.605564E+09 | 618.31 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595909E+09 | 607.88 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565394E+09 | 638.19 | 27-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.640076E+09 | 888.91 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.596052E+09 | 985.98 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.663117E+09 | 1144.23 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.667231E+09 | 1128.69 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.671599E+09 | 1042.61 | 06-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.756183E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565394E+09 | 607.88 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.687505E+09 | 1144.23 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.432064E+09 | 653.07 | 03-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.390661E+09 | 716.57 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.427941E+09 | 667.19 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.372535E+09 | 574.54 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.392459E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.386618E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.366010E+09 | 399.65 | 27-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.412823E+09 | 537.92 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.381525E+09 | 613.89 | 29-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.415910E+09 | 737.34 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.423306E+09 | 720.53 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.422172E+09 | 655.29 | 06-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.482402E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.366010E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.432064E+09 | 737.34 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.656850E+09 | 1023.87 | 03-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.598996E+09 | 1112.75 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.665248E+09 | 1047.53 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.580810E+09 | 943.30 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.611356E+09 | 632.22 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.601801E+09 | 621.65 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.571051E+09 | 762.87 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.643111E+09 | 900.61 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.593999E+09 | 976.61 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.641607E+09 | 1144.26 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.643406E+09 | 1122.37 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.638340E+09 | 1025.41 | 06-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.744657E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.571051E+09 | 621.65 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.665248E+09 | 1144.26 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433091E+09 | 671.67 | 03-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.393622E+09 | 716.57 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.432443E+09 | 679.17 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.374000E+09 | 622.14 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.393358E+09 | 541.43 | 24-MAY-07:30 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.386580E+09 | 407.73 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.367257E+09 | 518.50 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.414402E+09 | 593.92 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.384955E+09 | 641.62 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.424050E+09 | 737.34 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.420607E+09 | 728.49 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.420773E+09 | 672.81 | 06-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.484514E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.367257E+09 | 407.73 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.433091E+09 | 737.34 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.690800E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963413E+09 |
February | 0.136985E+10 | 0.622349E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 270579.45 | 0.821232E+09 |
March | 0.163685E+10 | 0.672050E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1582510.11 | 0.538151E+09 |
April | 0.145243E+10 | 0.579748E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4300862.37 | 0.321689E+09 |
May | 0.157338E+10 | 0.605943E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13061792.60 | 0.200581E+09 |
June | 0.156900E+10 | 0.596395E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57544581.11 | 92585769.34 |
July | 0.145680E+10 | 0.565990E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63447287.50 | 55945701.52 |
August | 0.163685E+10 | 0.640611E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60877503.35 | 27447081.85 |
September | 0.145243E+10 | 0.597241E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16464644.89 | 0.106240E+09 |
October | 0.150991E+10 | 0.665832E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3516144.32 | 0.365537E+09 |
November | 0.149516E+10 | 0.669654E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.05 | 0.538309E+09 |
December | 0.145680E+10 | 0.674367E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934299E+09 |
Annual Sum or Average | 0.181194E+11 | 0.758098E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221066E+09 | 0.496543E+10 |
Minimum of Months | 0.136985E+10 | 0.565990E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27447081.85 |
Maximum of Months | 0.163685E+10 | 0.690800E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63447287.50 | 0.963413E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.433145E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648623E+09 |
February | 0.882782E+09 | 0.391696E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64310.07 | 0.551355E+09 |
March | 0.105485E+10 | 0.428468E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057470.38 | 0.357796E+09 |
April | 0.936002E+09 | 0.372798E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2640523.18 | 0.210300E+09 |
May | 0.101394E+10 | 0.392770E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8089113.38 | 0.137362E+09 |
June | 0.101113E+10 | 0.386909E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37775422.93 | 61057224.78 |
July | 0.938820E+09 | 0.366350E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41818785.34 | 36214713.61 |
August | 0.105485E+10 | 0.413184E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41030752.49 | 15891804.82 |
September | 0.936002E+09 | 0.381871E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10294709.09 | 70399387.54 |
October | 0.973041E+09 | 0.416707E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1946449.86 | 0.243129E+09 |
November | 0.963541E+09 | 0.424149E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6248.15 | 0.356808E+09 |
December | 0.938820E+09 | 0.423241E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612458E+09 |
Annual Sum or Average | 0.116768E+11 | 0.483129E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144724E+09 | 0.330139E+10 |
Minimum of Months | 0.882782E+09 | 0.366350E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15891804.82 |
Maximum of Months | 0.105485E+10 | 0.433145E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41818785.34 | 0.648623E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.657597E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979096E+09 |
February | 0.136988E+10 | 0.599994E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95383.34 | 0.838679E+09 |
March | 0.163688E+10 | 0.666015E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1552122.09 | 0.555273E+09 |
April | 0.145246E+10 | 0.581621E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3756543.08 | 0.323387E+09 |
May | 0.157341E+10 | 0.611998E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12412291.15 | 0.201091E+09 |
June | 0.156904E+10 | 0.602316E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57284467.71 | 91645303.59 |
July | 0.145684E+10 | 0.571664E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62597881.37 | 55944667.21 |
August | 0.163688E+10 | 0.643738E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59061029.39 | 29418858.01 |
September | 0.145246E+10 | 0.594706E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14552444.62 | 0.108560E+09 |
October | 0.150994E+10 | 0.642552E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2368664.19 | 0.375471E+09 |
November | 0.149520E+10 | 0.644542E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552423E+09 |
December | 0.145684E+10 | 0.638968E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929219E+09 |
Annual Sum or Average | 0.181198E+11 | 0.745571E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213681E+09 | 0.504021E+10 |
Minimum of Months | 0.136988E+10 | 0.571664E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29418858.01 |
Maximum of Months | 0.163688E+10 | 0.666015E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62597881.37 | 0.979096E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.434124E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685132E+09 |
February | 0.882782E+09 | 0.394983E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63713.87 | 0.604726E+09 |
March | 0.105485E+10 | 0.433381E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1036768.79 | 0.416469E+09 |
April | 0.936002E+09 | 0.374554E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2457694.10 | 0.256455E+09 |
May | 0.101394E+10 | 0.393829E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7530477.01 | 0.154517E+09 |
June | 0.101113E+10 | 0.387082E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35520696.69 | 79222233.53 |
July | 0.938820E+09 | 0.367787E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37182273.72 | 52958607.73 |
August | 0.105485E+10 | 0.414926E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35990765.61 | 35778499.31 |
September | 0.936002E+09 | 0.385682E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9494736.29 | 84124161.83 |
October | 0.973041E+09 | 0.425453E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1626375.66 | 0.277916E+09 |
November | 0.963541E+09 | 0.421509E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407040E+09 |
December | 0.938820E+09 | 0.421830E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703550E+09 |
Annual Sum or Average | 0.116768E+11 | 0.485514E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130904E+09 | 0.375789E+10 |
Minimum of Months | 0.882782E+09 | 0.367787E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35778499.31 |
Maximum of Months | 0.105485E+10 | 0.434124E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37182273.72 | 0.703550E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.687658E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193186E+10 |
February | 0.136985E+10 | 0.619995E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3010541.03 | 0.165082E+10 |
March | 0.163685E+10 | 0.670684E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3948960.51 | 0.108460E+10 |
April | 0.145243E+10 | 0.578852E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11220315.57 | 0.684789E+09 |
May | 0.157338E+10 | 0.605596E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31322113.49 | 0.440740E+09 |
June | 0.156900E+10 | 0.595954E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132556E+09 | 0.217741E+09 |
July | 0.145680E+10 | 0.565414E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141896E+09 | 0.143817E+09 |
August | 0.163685E+10 | 0.640102E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140745E+09 | 86750016.86 |
September | 0.145243E+10 | 0.596134E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39668730.97 | 0.227311E+09 |
October | 0.150991E+10 | 0.663177E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12247702.15 | 0.733862E+09 |
November | 0.149516E+10 | 0.667293E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356943.21 | 0.105426E+10 |
December | 0.145680E+10 | 0.671674E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177499E+10 |
Annual Sum or Average | 0.181194E+11 | 0.756253E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516973E+09 | 0.100315E+11 |
Minimum of Months | 0.136985E+10 | 0.565414E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86750016.86 |
Maximum of Months | 0.163685E+10 | 0.687658E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141896E+09 | 0.193186E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.432106E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132099E+10 |
February | 0.649041E+09 | 0.390694E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125966.08 | 0.114438E+10 |
March | 0.773965E+09 | 0.427956E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2290122.02 | 0.772958E+09 |
April | 0.688021E+09 | 0.372548E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5417056.00 | 0.482615E+09 |
May | 0.744847E+09 | 0.392470E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17247123.79 | 0.316745E+09 |
June | 0.742030E+09 | 0.386627E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83093443.04 | 0.153927E+09 |
July | 0.690839E+09 | 0.366020E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88511741.55 | 0.103608E+09 |
August | 0.773965E+09 | 0.412835E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87494733.27 | 64035017.99 |
September | 0.688021E+09 | 0.381537E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22264232.55 | 0.159773E+09 |
October | 0.715730E+09 | 0.415956E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4636106.80 | 0.520602E+09 |
November | 0.708685E+09 | 0.423330E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82745.43 | 0.744000E+09 |
December | 0.690839E+09 | 0.422212E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121521E+10 |
Annual Sum or Average | 0.858171E+10 | 0.482429E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311163E+09 | 0.699883E+10 |
Minimum of Months | 0.649041E+09 | 0.366020E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64035017.99 |
Maximum of Months | 0.773965E+09 | 0.432106E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88511741.55 | 0.132099E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.656878E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212146E+10 |
February | 0.136988E+10 | 0.599079E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191328.66 | 0.181662E+10 |
March | 0.163688E+10 | 0.665316E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3390744.30 | 0.122054E+10 |
April | 0.145246E+10 | 0.580835E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8293719.38 | 0.723536E+09 |
May | 0.157341E+10 | 0.611402E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28407535.02 | 0.451007E+09 |
June | 0.156904E+10 | 0.601843E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131740E+09 | 0.216632E+09 |
July | 0.145684E+10 | 0.571092E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139744E+09 | 0.144684E+09 |
August | 0.163688E+10 | 0.643152E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134324E+09 | 93936171.46 |
September | 0.145246E+10 | 0.594034E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32508145.98 | 0.243762E+09 |
October | 0.150994E+10 | 0.641715E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5001816.29 | 0.826758E+09 |
November | 0.149520E+10 | 0.643447E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120996E+10 |
December | 0.145684E+10 | 0.638418E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194794E+10 |
Annual Sum or Average | 0.181198E+11 | 0.744721E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483602E+09 | 0.110168E+11 |
Minimum of Months | 0.136988E+10 | 0.571092E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93936171.46 |
Maximum of Months | 0.163688E+10 | 0.665316E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139744E+09 | 0.212146E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.433119E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135991E+10 |
February | 0.882782E+09 | 0.393674E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 490334.81 | 0.117432E+10 |
March | 0.105485E+10 | 0.432476E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2270453.32 | 0.819480E+09 |
April | 0.936002E+09 | 0.374014E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5765236.33 | 0.509240E+09 |
May | 0.101394E+10 | 0.393328E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17522703.68 | 0.327944E+09 |
June | 0.101113E+10 | 0.386614E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82618938.75 | 0.165393E+09 |
July | 0.938820E+09 | 0.367283E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87331450.67 | 0.111569E+09 |
August | 0.105485E+10 | 0.414427E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84349181.40 | 77609106.61 |
September | 0.936002E+09 | 0.385008E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22540939.71 | 0.170739E+09 |
October | 0.973041E+09 | 0.424079E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3998645.75 | 0.543618E+09 |
November | 0.963541E+09 | 0.420675E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770446E+09 |
December | 0.938820E+09 | 0.420799E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125683E+10 |
Annual Sum or Average | 0.116768E+11 | 0.484550E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306888E+09 | 0.728710E+10 |
Minimum of Months | 0.882782E+09 | 0.367283E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77609106.61 |
Maximum of Months | 0.105485E+10 | 0.433119E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87331450.67 | 0.135991E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.687505E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227545E+10 |
February | 0.136985E+10 | 0.619904E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6007875.36 | 0.194282E+10 |
March | 0.163685E+10 | 0.670649E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5023343.08 | 0.124302E+10 |
April | 0.145243E+10 | 0.578832E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12909548.82 | 0.802856E+09 |
May | 0.157338E+10 | 0.605564E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34555908.51 | 0.537368E+09 |
June | 0.156900E+10 | 0.595909E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155611E+09 | 0.274030E+09 |
July | 0.145680E+10 | 0.565394E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165804E+09 | 0.183241E+09 |
August | 0.163685E+10 | 0.640076E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164450E+09 | 0.114640E+09 |
September | 0.145243E+10 | 0.596052E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45329529.95 | 0.271324E+09 |
October | 0.150991E+10 | 0.663117E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16453507.76 | 0.831158E+09 |
November | 0.149516E+10 | 0.667231E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2966334.35 | 0.117051E+10 |
December | 0.145680E+10 | 0.671599E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200231E+10 |
Annual Sum or Average | 0.181194E+11 | 0.756183E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609111E+09 | 0.116487E+11 |
Minimum of Months | 0.136985E+10 | 0.565394E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114640E+09 |
Maximum of Months | 0.163685E+10 | 0.687505E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165804E+09 | 0.227545E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.432064E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154276E+10 |
February | 0.882782E+09 | 0.390661E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 810274.40 | 0.133821E+10 |
March | 0.105485E+10 | 0.427941E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2900990.10 | 0.890658E+09 |
April | 0.936002E+09 | 0.372535E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6488273.04 | 0.570169E+09 |
May | 0.101394E+10 | 0.392459E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20758426.76 | 0.387188E+09 |
June | 0.101113E+10 | 0.386618E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100901E+09 | 0.193595E+09 |
July | 0.938820E+09 | 0.366010E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106700E+09 | 0.131122E+09 |
August | 0.105485E+10 | 0.412823E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105493E+09 | 83690594.59 |
September | 0.936002E+09 | 0.381525E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26686903.54 | 0.190314E+09 |
October | 0.973041E+09 | 0.415910E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5850927.15 | 0.593150E+09 |
November | 0.963541E+09 | 0.423306E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1493009.57 | 0.824129E+09 |
December | 0.938820E+09 | 0.422172E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135564E+10 |
Annual Sum or Average | 0.116768E+11 | 0.482402E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378082E+09 | 0.810062E+10 |
Minimum of Months | 0.882782E+09 | 0.366010E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83690594.59 |
Maximum of Months | 0.105485E+10 | 0.432064E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106700E+09 | 0.154276E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.656850E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245523E+10 |
February | 0.136988E+10 | 0.598996E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201211.42 | 0.211771E+10 |
March | 0.163688E+10 | 0.665248E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3952326.94 | 0.142344E+10 |
April | 0.145246E+10 | 0.580810E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9482286.13 | 0.855290E+09 |
May | 0.157341E+10 | 0.611356E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32327706.40 | 0.551443E+09 |
June | 0.156904E+10 | 0.601801E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155125E+09 | 0.272593E+09 |
July | 0.145684E+10 | 0.571051E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164132E+09 | 0.184261E+09 |
August | 0.163688E+10 | 0.643111E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158881E+09 | 0.123716E+09 |
September | 0.145246E+10 | 0.593999E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38078428.36 | 0.293036E+09 |
October | 0.150994E+10 | 0.641607E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5901785.15 | 0.956816E+09 |
November | 0.149520E+10 | 0.643406E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136919E+10 |
December | 0.145684E+10 | 0.638340E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217455E+10 |
Annual Sum or Average | 0.181198E+11 | 0.744657E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568082E+09 | 0.127773E+11 |
Minimum of Months | 0.136988E+10 | 0.571051E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123716E+09 |
Maximum of Months | 0.163688E+10 | 0.665248E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164132E+09 | 0.245523E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.433091E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158727E+10 |
February | 0.882782E+09 | 0.393622E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1247408.37 | 0.138322E+10 |
March | 0.105485E+10 | 0.432443E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2633732.95 | 0.960428E+09 |
April | 0.936002E+09 | 0.374000E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6728780.21 | 0.606478E+09 |
May | 0.101394E+10 | 0.393358E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20597596.54 | 0.401260E+09 |
June | 0.101113E+10 | 0.386580E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99239108.91 | 0.207121E+09 |
July | 0.938820E+09 | 0.367257E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104427E+09 | 0.140711E+09 |
August | 0.105485E+10 | 0.414402E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101110E+09 | 0.100269E+09 |
September | 0.936002E+09 | 0.384955E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26540554.68 | 0.205974E+09 |
October | 0.973041E+09 | 0.424050E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4845788.24 | 0.630705E+09 |
November | 0.963541E+09 | 0.420607E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876916E+09 |
December | 0.938820E+09 | 0.420773E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142681E+10 |
Annual Sum or Average | 0.116768E+11 | 0.484514E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367369E+09 | 0.852717E+10 |
Minimum of Months | 0.882782E+09 | 0.367257E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100269E+09 |
Maximum of Months | 0.105485E+10 | 0.433091E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104427E+09 | 0.158727E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211777E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80654.32 | 0.180387E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2101839.60 | 0.116654E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6223042.52 | 0.691669E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22663528.18 | 0.425308E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106349E+09 | 0.197997E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121757E+09 | 0.126578E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111824E+09 | 74243770.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27899197.46 | 0.226786E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4582692.11 | 0.789834E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117028E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202967E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403480E+09 | 0.108206E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74243770.86 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121757E+09 | 0.211777E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340548E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 978401.51 | 0.294334E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4293027.69 | 0.196309E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12868028.88 | 0.118685E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43453842.16 | 0.744463E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193804E+09 | 0.350548E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219480E+09 | 0.228670E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205432E+09 | 0.137685E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52757763.69 | 0.392734E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11396295.00 | 0.133053E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413113.24 | 0.193534E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326015E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744876E+09 | 0.178789E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137685E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219480E+09 | 0.340548E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343315E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 962582.87 | 0.299601E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2513605.92 | 0.205161E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5696655.50 | 0.128890E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26081346.95 | 0.843968E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169909E+09 | 0.399752E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188676E+09 | 0.271759E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184593E+09 | 0.166846E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39356592.33 | 0.421564E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6930915.07 | 0.136383E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1753280.48 | 0.190114E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313805E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626473E+09 | 0.182766E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166846E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188676E+09 | 0.343315E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1041.09 | 03-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1728.01 | 07-JAN-18:03 |
February | 2010.79 | 01-FEB-10:09 | 1113.16 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 26-FEB-15:00 | 2108.93 | 12-FEB-00:52 |
March | 2010.79 | 01-MAR-10:09 | 1050.45 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 30-MAR-16:00 | 1375.05 | 22-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 942.04 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 16-APR-12:10 | 701.01 | 05-APR-04:55 |
May | 2010.79 | 01-MAY-09:09 | 623.15 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.32 | 07-MAY-12:20 | 544.26 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 613.34 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.06 | 11-JUN-15:00 | 393.32 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 641.91 | 27-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.32 | 08-JUL-18:53 | 293.34 | 28-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 892.47 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.03 | 06-AUG-14:00 | 155.83 | 25-AUG-04:43 |
September | 2010.79 | 01-SEP-09:09 | 988.16 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 17-SEP-14:53 | 379.21 | 30-SEP-19:00 |
October | 2010.79 | 02-OCT-09:09 | 1144.27 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 | 08-OCT-14:10 | 812.27 | 28-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 1128.98 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 19-NOV-15:00 | 1171.29 | 21-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1044.07 | 06-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2054.76 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 613.34 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.83 | |||||
Maximum of Months | 2010.79 | 1144.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 308.03 | 2108.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 655.13 | 03-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1142.00 | 07-JAN-18:03 |
February | 1295.83 | 01-FEB-10:09 | 717.19 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 28-FEB-15:00 | 1387.86 | 12-FEB-00:52 |
March | 1295.83 | 01-MAR-10:09 | 668.93 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 30-MAR-16:00 | 887.44 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 577.92 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.40 | 16-APR-14:00 | 449.83 | 05-APR-04:55 |
May | 1295.83 | 01-MAY-09:09 | 375.14 | 02-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.64 | 29-MAY-17:50 | 361.06 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.61 | 25-JUN-16:05 | 259.14 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 402.23 | 27-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.91 | 08-JUL-18:53 | 184.72 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 542.31 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.37 | 06-AUG-14:00 | 94.42 | 25-AUG-04:43 |
September | 1295.83 | 01-SEP-09:09 | 616.86 | 29-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.62 | 17-SEP-15:10 | 243.73 | 30-SEP-19:00 |
October | 1295.83 | 02-OCT-09:09 | 737.40 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 09-OCT-16:00 | 527.63 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 720.94 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 | 19-NOV-15:00 | 766.93 | 21-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 657.31 | 06-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1332.61 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.42 | |||||
Maximum of Months | 1295.83 | 737.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 202.37 | 1387.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1025.41 | 03-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1714.18 | 07-JAN-18:03 |
February | 2010.83 | 01-FEB-10:09 | 1113.19 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 28-FEB-15:00 | 2097.75 | 11-FEB-18:03 |
March | 2010.83 | 01-MAR-10:09 | 1048.83 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 | 30-MAR-16:00 | 1328.47 | 22-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 946.15 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 16-APR-13:55 | 688.31 | 05-APR-04:55 |
May | 2010.83 | 01-MAY-09:09 | 636.30 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 | 29-MAY-17:50 | 539.24 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 626.38 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.58 | 25-JUN-16:05 | 391.50 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 768.64 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.08 | 08-JUL-18:53 | 291.62 | 28-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 904.07 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.64 | 06-AUG-14:00 | 158.17 | 25-AUG-04:43 |
September | 2010.83 | 01-SEP-09:09 | 978.84 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.44 | 17-SEP-15:08 | 364.13 | 30-SEP-19:00 |
October | 2010.83 | 02-OCT-09:09 | 1144.30 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 | 10-OCT-16:00 | 811.05 | 28-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 1122.69 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1191.14 | 07-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1026.93 | 06-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1982.36 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 626.38 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.17 | |||||
Maximum of Months | 2010.83 | 1144.30 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 294.64 | 2097.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 673.51 | 03-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1198.67 | 07-JAN-18:03 |
February | 1295.83 | 01-FEB-10:09 | 717.19 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 28-FEB-15:00 | 1563.62 | 11-FEB-18:03 |
March | 1295.83 | 01-MAR-10:09 | 680.83 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 30-MAR-16:00 | 1019.71 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 625.38 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.96 | 16-APR-13:55 | 515.76 | 05-APR-04:55 |
May | 1295.83 | 01-MAY-09:09 | 547.36 | 24-MAY-07:30 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 29-MAY-17:45 | 392.90 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 410.30 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.34 | 25-JUN-16:10 | 306.39 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 524.62 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.61 | 08-JUL-19:07 | 232.92 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 597.94 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.43 | 06-AUG-14:00 | 156.68 | 29-AUG-02:30 |
September | 1295.83 | 01-SEP-09:09 | 644.30 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 | 17-SEP-15:05 | 284.54 | 30-SEP-19:00 |
October | 1295.83 | 02-OCT-09:09 | 737.40 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 09-OCT-15:34 | 606.21 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 728.79 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 870.18 | 07-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 674.62 | 06-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1515.93 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 410.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.68 | |||||
Maximum of Months | 1295.83 | 737.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 196.43 | 1563.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1039.82 | 03-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3739.45 | 07-JAN-18:03 |
February | 2010.79 | 01-FEB-10:09 | 1112.80 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.45 | 26-FEB-12:52 | 4433.05 | 12-FEB-00:55 |
March | 2010.79 | 01-MAR-10:09 | 1049.36 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.77 | 30-MAR-16:00 | 2716.05 | 22-MAR-04:55 |
April | 2010.79 | 03-APR-09:09 | 939.57 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.18 | 16-APR-11:53 | 1492.94 | 05-APR-04:55 |
May | 2010.79 | 01-MAY-09:09 | 618.50 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.91 | 07-MAY-12:00 | 1176.65 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 608.09 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.39 | 11-JUN-15:00 | 856.59 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 638.34 | 27-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 651.87 | 08-JUL-18:53 | 618.61 | 28-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 889.42 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 707.62 | 06-AUG-14:00 | 401.16 | 25-AUG-05:00 |
September | 2010.79 | 01-SEP-09:09 | 986.31 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.48 | 24-SEP-13:00 | 809.79 | 29-SEP-04:53 |
October | 2010.79 | 02-OCT-09:09 | 1144.24 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.27 | 08-OCT-13:52 | 1592.29 | 28-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 1128.73 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.74 | 19-NOV-15:00 | 2553.33 | 30-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 1042.82 | 06-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3849.19 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 608.09 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.16 | |||||
Maximum of Months | 2010.79 | 1144.24 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 707.62 | 4433.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 653.22 | 03-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2477.44 | 07-JAN-05:06 |
February | 1239.33 | 01-FEB-08:09 | 716.62 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 | 26-FEB-15:10 | 2969.56 | 12-FEB-00:53 |
March | 1239.33 | 01-MAR-08:09 | 667.33 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.51 | 30-MAR-16:00 | 1812.67 | 22-MAR-04:55 |
April | 1239.33 | 03-APR-07:10 | 574.83 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.94 | 16-APR-14:08 | 997.68 | 05-APR-04:55 |
May | 1239.33 | 01-MAY-07:10 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.06 | 29-MAY-17:25 | 793.42 | 10-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.23 | 11-JUN-15:00 | 586.19 | 07-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 399.77 | 27-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.05 | 08-JUL-18:53 | 410.29 | 28-JUL-22:00 |
August | 1239.33 | 01-AUG-07:10 | 538.28 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.45 | 06-AUG-14:00 | 268.39 | 25-AUG-05:00 |
September | 1239.33 | 01-SEP-07:10 | 614.12 | 29-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.90 | 17-SEP-15:10 | 538.93 | 29-SEP-04:53 |
October | 1239.33 | 02-OCT-07:10 | 737.35 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.61 | 09-OCT-16:00 | 1073.79 | 28-OCT-04:00 |
November | 1239.33 | 01-NOV-07:10 | 720.56 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.29 | 19-NOV-15:00 | 1700.66 | 30-NOV-22:03 |
December | 1239.33 | 01-DEC-08:09 | 655.44 | 06-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2569.17 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.39 | |||||
Maximum of Months | 1239.33 | 737.35 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 452.45 | 2969.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1024.11 | 03-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3793.05 | 07-JAN-18:03 |
February | 2010.83 | 01-FEB-10:09 | 1112.82 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 28-FEB-15:00 | 4665.97 | 11-FEB-18:03 |
March | 2010.83 | 01-MAR-10:09 | 1047.74 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.82 | 30-MAR-16:00 | 2706.27 | 22-MAR-04:55 |
April | 2010.83 | 03-APR-09:09 | 943.70 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.65 | 16-APR-13:48 | 1502.22 | 05-APR-04:55 |
May | 2010.83 | 01-MAY-09:09 | 632.36 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.22 | 29-MAY-17:32 | 1193.82 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 621.82 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.87 | 11-JUN-15:00 | 861.85 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 763.62 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 635.19 | 08-JUL-18:53 | 621.65 | 28-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 901.10 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 678.67 | 06-AUG-14:00 | 411.28 | 25-AUG-05:00 |
September | 2010.83 | 01-SEP-09:09 | 976.95 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.07 | 17-SEP-15:08 | 814.89 | 29-SEP-04:53 |
October | 2010.83 | 02-OCT-09:09 | 1144.27 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.97 | 10-OCT-16:00 | 1696.33 | 28-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 1122.41 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2555.88 | 30-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 1025.65 | 06-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4005.13 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 621.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.28 | |||||
Maximum of Months | 2010.83 | 1144.27 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 678.67 | 4665.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 671.81 | 03-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2553.98 | 07-JAN-18:03 |
February | 1295.83 | 01-FEB-10:09 | 716.62 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.88 | 26-FEB-12:52 | 3270.94 | 11-FEB-18:03 |
March | 1295.83 | 01-MAR-10:09 | 679.29 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 30-MAR-16:00 | 1830.77 | 22-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 622.37 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.45 | 16-APR-11:53 | 1021.12 | 05-APR-04:55 |
May | 1295.83 | 01-MAY-09:09 | 541.74 | 24-MAY-07:30 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.91 | 07-MAY-12:00 | 824.85 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 407.83 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.96 | 25-JUN-16:10 | 609.94 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 518.93 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.83 | 08-JUL-19:10 | 434.58 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 594.22 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.47 | 06-AUG-14:00 | 296.36 | 25-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 641.81 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.06 | 24-SEP-12:52 | 547.49 | 29-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 737.35 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.58 | 08-OCT-13:52 | 1119.57 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 728.51 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1706.80 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 672.95 | 06-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2647.40 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 407.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.36 | |||||
Maximum of Months | 1295.83 | 737.35 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 452.47 | 3270.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1039.60 | 03-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4475.55 | 07-JAN-18:03 |
February | 2010.79 | 01-FEB-10:09 | 1112.72 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 369.82 | 26-FEB-13:00 | 5438.28 | 12-FEB-00:52 |
March | 2010.79 | 01-MAR-10:09 | 1049.16 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.04 | 11-MAR-16:00 | 3374.09 | 22-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 939.16 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.16 | 16-APR-11:53 | 1742.52 | 05-APR-04:55 |
May | 2010.79 | 01-MAY-09:09 | 618.31 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.66 | 07-MAY-12:03 | 1346.73 | 10-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 607.88 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 779.54 | 25-JUN-16:05 | 1043.48 | 07-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 638.19 | 27-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 728.23 | 08-JUL-19:10 | 744.45 | 28-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 888.91 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 844.76 | 06-AUG-14:00 | 480.52 | 25-AUG-05:00 |
September | 2010.79 | 01-SEP-09:09 | 985.98 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.83 | 17-SEP-14:53 | 896.79 | 29-SEP-04:53 |
October | 2010.79 | 02-OCT-09:09 | 1144.23 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.70 | 08-OCT-13:52 | 1778.08 | 28-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 1128.69 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.02 | 19-NOV-15:00 | 3157.88 | 30-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 1042.61 | 06-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4460.16 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 607.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.52 | |||||
Maximum of Months | 2010.79 | 1144.23 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 844.76 | 5438.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 653.07 | 03-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3092.19 | 07-JAN-05:09 |
February | 1295.83 | 01-FEB-10:09 | 716.57 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 26-FEB-15:00 | 3624.80 | 12-FEB-00:52 |
March | 1295.83 | 01-MAR-10:09 | 667.19 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 | 30-MAR-16:00 | 2249.37 | 22-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 574.54 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 | 16-APR-13:53 | 1164.54 | 05-APR-04:55 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.46 | 29-MAY-17:35 | 909.61 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.87 | 25-JUN-16:05 | 714.54 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 399.65 | 27-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.16 | 08-JUL-19:10 | 529.15 | 01-JUL-19:55 |
August | 1295.83 | 01-AUG-09:09 | 537.92 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.08 | 06-AUG-14:00 | 321.21 | 25-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 613.89 | 29-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.65 | 24-SEP-12:56 | 596.09 | 29-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 737.34 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.72 | 09-OCT-15:40 | 1202.48 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 720.53 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.53 | 19-NOV-15:00 | 2103.08 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 655.29 | 06-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2980.93 | 17-DEC-04:17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.21 | |||||
Maximum of Months | 1295.83 | 737.34 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 552.08 | 3624.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1023.87 | 03-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4541.88 | 07-JAN-18:03 |
February | 2010.83 | 01-FEB-10:09 | 1112.75 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 | 28-FEB-15:00 | 5580.80 | 11-FEB-18:03 |
March | 2010.83 | 01-MAR-10:09 | 1047.53 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.41 | 30-MAR-16:00 | 3373.99 | 22-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 943.30 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.87 | 16-APR-14:00 | 1754.57 | 05-APR-04:55 |
May | 2010.83 | 01-MAY-09:09 | 632.22 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.51 | 29-MAY-17:35 | 1369.77 | 10-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 621.65 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 794.36 | 25-JUN-16:05 | 1050.63 | 07-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 762.87 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.26 | 08-JUL-19:10 | 748.58 | 28-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 900.61 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 827.30 | 06-AUG-14:00 | 494.05 | 25-AUG-05:00 |
September | 2010.83 | 01-SEP-09:09 | 976.61 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.89 | 06-SEP-12:00 | 903.46 | 29-SEP-04:53 |
October | 2010.83 | 02-OCT-09:09 | 1144.26 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | 10-OCT-16:00 | 1919.88 | 28-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 1122.37 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3159.88 | 30-NOV-22:03 |
December | 2010.83 | 01-DEC-10:09 | 1025.41 | 06-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4459.84 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 621.65 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.05 | |||||
Maximum of Months | 2010.83 | 1144.26 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 827.30 | 5580.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 671.67 | 03-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3092.12 | 07-JAN-05:10 |
February | 1295.83 | 01-FEB-10:09 | 716.57 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.44 | 26-FEB-13:02 | 3942.88 | 11-FEB-18:03 |
March | 1295.83 | 01-MAR-10:09 | 679.17 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.95 | 30-MAR-16:00 | 2296.34 | 22-MAR-04:55 |
April | 1295.83 | 03-APR-09:09 | 622.14 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.62 | 16-APR-11:53 | 1198.42 | 05-APR-04:55 |
May | 1295.83 | 01-MAY-09:09 | 541.43 | 24-MAY-07:30 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.71 | 07-MAY-12:03 | 955.11 | 10-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 407.73 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.11 | 25-JUN-16:10 | 744.18 | 07-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 518.50 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.18 | 08-JUL-19:10 | 525.82 | 28-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 593.92 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.56 | 06-AUG-14:00 | 358.44 | 25-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 641.62 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.21 | 24-SEP-12:40 | 615.10 | 29-SEP-04:53 |
October | 1295.83 | 02-OCT-09:09 | 737.34 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.03 | 08-OCT-13:52 | 1275.00 | 28-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 728.49 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2111.70 | 30-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 672.81 | 06-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2973.39 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 407.73 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.44 | |||||
Maximum of Months | 1295.83 | 737.34 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 551.56 | 3942.88 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3811.40 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 | 28-FEB-15:00 | 4738.91 | 12-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.30 | 30-MAR-16:00 | 3018.39 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.73 | 16-APR-14:00 | 1528.87 | 05-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.83 | 07-MAY-12:30 | 1199.64 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.51 | 11-JUN-15:00 | 820.13 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.12 | 08-JUL-18:53 | 587.69 | 28-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.32 | 06-AUG-14:00 | 374.28 | 25-AUG-04:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.90 | 17-SEP-14:53 | 826.74 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.48 | 09-OCT-16:00 | 1760.48 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2589.79 | 21-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4571.47 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.28 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.32 | 4738.91 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6436.55 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.16 | 26-FEB-15:00 | 7940.95 | 12-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.63 | 30-MAR-16:00 | 5051.14 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.72 | 16-APR-11:53 | 2637.60 | 05-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.95 | 07-MAY-12:00 | 2121.55 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.32 | 11-JUN-15:00 | 1436.99 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113.28 | 08-JUL-18:53 | 1029.08 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.86 | 06-AUG-14:00 | 685.04 | 25-AUG-04:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.09 | 17-SEP-14:53 | 1473.07 | 29-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.79 | 09-OCT-16:00 | 2969.11 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.91 | 19-NOV-15:00 | 4403.84 | 21-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7547.91 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.04 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.86 | 7940.95 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7116.63 | 07-JAN-18:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.99 | 26-FEB-13:13 | 8434.47 | 11-FEB-18:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.43 | 30-MAR-16:00 | 4864.82 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.88 | 16-APR-14:00 | 2777.32 | 05-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.98 | 19-MAY-13:00 | 2092.07 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.72 | 11-JUN-15:00 | 1604.18 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.30 | 08-JUL-18:53 | 1170.54 | 01-JUL-19:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924.84 | 06-AUG-14:00 | 723.67 | 23-AUG-04:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.46 | 06-SEP-12:00 | 1372.17 | 29-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.45 | 09-OCT-16:00 | 2975.43 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.22 | 19-NOV-15:00 | 4594.07 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7068.73 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.30 | 8434.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93831.96 | 02-JAN-05:22 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96705.36 | 21-FEB-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93979.05 | 06-MAR-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93206.24 | 17-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91299.93 | 15-MAY-04:12 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90011.06 | 07-JUN-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82985.09 | 03-JUL-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79555.63 | 26-AUG-04:12 | 0.00 | 3391.28 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90795.00 | 19-SEP-04:12 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97283.22 | 30-OCT-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97144.92 | 12-NOV-14:00 | 5385.68 | 3391.28 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96730.89 | 11-DEC-05:11 | 0.00 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79555.63 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97283.22 | 5385.68 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 80102.22 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80377.13 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80965.06 | 13-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80419.15 | 21-APR-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84320.15 | 22-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82535.74 | 06-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78314.03 | 29-JUL-04:12 | 0.00 | 3045.61 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74537.48 | 07-AUG-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83554.90 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87368.14 | 10-OCT-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86509.07 | 13-NOV-05:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82256.06 | 11-DEC-05:12 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 74537.48 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87368.14 | 9673.43 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21177.60 | 21-JAN-08:40 | 4836.72 | 3045.74 | 9559.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66632.31 | 28-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71484.76 | 31-MAR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72606.91 | 24-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72821.00 | 31-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73580.88 | 20-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73020.90 | 28-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73146.09 | 25-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73941.67 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72664.10 | 17-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68583.05 | 06-NOV-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66411.99 | 14-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21177.60 | 0.00 | 2149.44 | 9559.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73941.67 | 8061.19 | 3224.16 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19867.10 | 20-JAN-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29554.52 | 28-FEB-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69358.79 | 31-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70291.82 | 18-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75191.09 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72813.40 | 30-JUN-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73184.76 | 27-JUL-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71797.92 | 31-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72188.54 | 07-SEP-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68965.06 | 19-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46243.44 | 04-NOV-05:03 | 6448.95 | 4060.81 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26600.89 | 13-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19867.10 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75191.09 | 15316.26 | 9137.09 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3445.60 | 31-JAN-14:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.79 |
February | 5815.08 | 28-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 |
March | 7545.54 | 30-MAR-15:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 45.26 | 0.00 |
April | 9745.06 | 03-APR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.73 |
May | 11373.04 | 30-MAY-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.88 |
June | 14908.41 | 18-JUN-15:52 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 173.96 | 0.00 |
July | 14735.52 | 16-JUL-15:42 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.55 | 0.00 |
August | 14457.61 | 27-AUG-15:41 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 150.97 | 0.00 |
September | 11593.65 | 25-SEP-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.43 |
October | 12055.01 | 02-OCT-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.52 |
November | 5405.08 | 02-NOV-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 |
December | 5119.96 | 13-DEC-12:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3445.60 | 0.00 | 151.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14908.41 | 2010.79 | 545.86 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 173.96 | 144.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2996.77 | 31-JAN-11:00 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.06 |
February | 7382.48 | 27-FEB-09:40 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.24 |
March | 10539.39 | 26-MAR-09:43 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.88 |
April | 17244.92 | 16-APR-09:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 |
May | 17754.24 | 07-MAY-08:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.76 |
June | 18259.25 | 04-JUN-08:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 |
July | 17035.76 | 04-JUL-09:32 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 |
August | 18439.10 | 27-AUG-09:41 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 |
September | 17077.88 | 24-SEP-09:02 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 |
October | 11746.63 | 09-OCT-08:53 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.26 |
November | 6909.00 | 06-NOV-09:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
December | 3888.78 | 11-DEC-10:25 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2996.77 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 | |
Maximum of Months | 18439.10 | 2591.66 | 703.55 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16975.69 | 29-JAN-12:43 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.28 |
February | 19252.58 | 26-FEB-12:32 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 |
March | 18212.59 | 26-MAR-13:43 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.47 |
April | 18873.94 | 16-APR-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 | 0.00 |
May | 13495.96 | 29-MAY-13:03 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 0.00 |
June | 17202.46 | 18-JUN-15:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 173.49 | 0.00 |
July | 17218.76 | 16-JUL-15:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 125.29 | 0.00 |
August | 19120.69 | 27-AUG-13:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 129.84 | 0.00 |
September | 18537.90 | 17-SEP-14:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 35.03 | 0.00 |
October | 19957.83 | 08-OCT-12:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.47 |
November | 20476.61 | 11-NOV-13:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.76 |
December | 19615.92 | 10-DEC-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13495.96 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20476.61 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 173.49 | 294.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5867.36 | 23-JAN-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.30 |
February | 16289.43 | 26-FEB-17:53 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 |
March | 21196.59 | 26-MAR-16:22 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.09 |
April | 22625.70 | 09-APR-16:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 |
May | 23260.26 | 21-MAY-17:32 | 0.00 | 117.25 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.05 |
June | 22543.07 | 11-JUN-16:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 0.00 |
July | 22789.57 | 09-JUL-16:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 | 0.00 |
August | 23630.56 | 13-AUG-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 39.13 | 0.00 |
September | 21944.41 | 17-SEP-17:02 | 0.00 | 97.71 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.11 |
October | 20992.98 | 09-OCT-16:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
November | 21710.59 | 11-NOV-15:02 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.60 |
December | 19353.30 | 10-DEC-15:23 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5867.36 | 0.00 | 78.17 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23630.56 | 1239.33 | 351.77 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 | 193.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1875.78 | 31-JAN-15:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.97 |
February | 4102.43 | 28-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 0.00 |
March | 6110.48 | 30-MAR-15:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 | 0.00 |
April | 6669.70 | 19-APR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 | 0.00 |
May | 10290.62 | 19-MAY-14:50 | 5769.33 | 1637.59 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 96.11 | 0.00 |
June | 12477.02 | 25-JUN-16:42 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 548.12 | 0.00 |
July | 15188.78 | 16-JUL-15:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 277.82 | 0.00 |
August | 14487.92 | 13-AUG-16:41 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 235.98 | 0.00 |
September | 10755.75 | 06-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 |
October | 7002.45 | 19-OCT-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 |
November | 3391.14 | 03-NOV-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 |
December | 2566.96 | 13-DEC-13:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1875.78 | 607.30 | 181.95 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15188.78 | 5769.33 | 1637.59 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 548.12 | 77.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3254.20 | 31-JAN-15:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.01 |
February | 6957.79 | 27-FEB-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.54 |
March | 8569.82 | 13-MAR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 |
April | 16438.87 | 16-APR-11:23 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 |
May | 17784.19 | 07-MAY-09:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.22 |
June | 19832.09 | 04-JUN-09:51 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.24 |
July | 19421.00 | 04-JUL-09:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 |
August | 19962.66 | 27-AUG-09:41 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.85 |
September | 18450.08 | 24-SEP-10:02 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.93 |
October | 9486.70 | 10-OCT-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
November | 5887.28 | 06-NOV-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.40 |
December | 4289.33 | 07-DEC-11:03 | 3717.98 | 1055.32 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3254.20 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | |
Maximum of Months | 19962.66 | 3717.98 | 1055.32 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18113.86 | 29-JAN-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.86 |
February | 19430.79 | 26-FEB-13:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.60 |
March | 17142.01 | 26-MAR-14:03 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696.07 |
April | 18218.13 | 16-APR-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 40.37 | 0.00 |
May | 13051.03 | 19-MAY-13:17 | 6032.50 | 1637.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 136.39 | 0.00 |
June | 16857.87 | 25-JUN-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 342.53 | 0.00 |
July | 18300.92 | 16-JUL-14:51 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 363.86 | 0.00 |
August | 18481.86 | 27-AUG-13:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 300.75 | 0.00 |
September | 19303.97 | 24-SEP-12:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 42.81 | 0.00 |
October | 18441.22 | 22-OCT-12:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.30 |
November | 18746.44 | 11-NOV-11:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.42 |
December | 18579.12 | 10-DEC-12:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13051.03 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19430.79 | 6032.50 | 1637.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 363.86 | 919.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2745.33 | 23-JAN-16:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.25 |
February | 9247.37 | 26-FEB-17:02 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.60 |
March | 11322.09 | 19-MAR-17:33 | 0.00 | 58.63 | 1081.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.93 |
April | 20207.13 | 09-APR-16:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.60 |
May | 19914.68 | 29-MAY-17:22 | 0.00 | 117.25 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 0.00 |
June | 19789.35 | 04-JUN-16:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 118.56 | 0.00 |
July | 21225.07 | 23-JUL-17:01 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 | 0.00 |
August | 22059.29 | 13-AUG-16:41 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 | 0.00 |
September | 20165.11 | 04-SEP-16:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
October | 15863.72 | 09-OCT-16:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.34 | 0.00 |
November | 7442.12 | 05-NOV-16:03 | 195.68 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 |
December | 4255.16 | 11-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2745.33 | 0.00 | 58.63 | 1081.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22059.29 | 1239.33 | 351.77 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.56 | 404.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1833.66 | 20-JAN-16:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.70 |
February | 3664.58 | 28-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 | 0.00 |
March | 6859.93 | 30-MAR-15:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 121.56 | 0.00 |
April | 7204.13 | 19-APR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 57.48 | 0.00 |
May | 16640.27 | 29-MAY-15:32 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.23 | 0.00 |
June | 16813.34 | 25-JUN-16:42 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 648.51 | 0.00 |
July | 17969.79 | 16-JUL-15:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 314.54 | 0.00 |
August | 16983.79 | 13-AUG-18:11 | 0.00 | 242.60 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 227.57 | 0.00 |
September | 12336.67 | 07-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 |
October | 6496.64 | 02-OCT-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.58 | 0.00 |
November | 3083.44 | 02-NOV-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 |
December | 2041.92 | 13-DEC-15:00 | 2010.79 | 608.93 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1833.66 | 0.00 | 181.95 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17969.79 | 2010.79 | 608.93 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 648.51 | 197.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1219.98 | 31-JAN-16:30 | 1239.33 | 386.82 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 |
February | 4022.95 | 27-FEB-10:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.37 |
March | 6421.63 | 14-MAR-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.35 |
April | 18060.99 | 16-APR-10:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.46 |
May | 19001.26 | 07-MAY-09:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.04 |
June | 19335.63 | 11-JUN-09:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.58 |
July | 19096.64 | 23-JUL-08:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.50 |
August | 18659.07 | 13-AUG-08:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.56 |
September | 18841.16 | 04-SEP-09:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.93 |
October | 7319.86 | 11-OCT-10:00 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 |
November | 3255.35 | 06-NOV-10:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.02 |
December | 1628.93 | 13-DEC-13:10 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1219.98 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 | |
Maximum of Months | 19335.63 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10215.96 | 11-JAN-14:30 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.56 |
February | 20074.17 | 26-FEB-14:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.08 |
March | 15716.14 | 30-MAR-13:40 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 90.73 | 0.00 |
April | 15517.40 | 16-APR-12:13 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 | 0.00 |
May | 19811.86 | 29-MAY-15:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 66.14 | 0.00 |
June | 19734.86 | 25-JUN-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 397.14 | 0.00 |
July | 21016.17 | 16-JUL-15:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 311.53 | 0.00 |
August | 19991.02 | 13-AUG-15:31 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 239.64 | 0.00 |
September | 21535.75 | 24-SEP-12:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 0.00 |
October | 20196.65 | 09-OCT-14:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 0.00 |
November | 21129.74 | 11-NOV-14:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.14 |
December | 13065.50 | 10-DEC-14:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10215.96 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21535.75 | 2010.83 | 545.88 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 397.14 | 650.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2673.68 | 20-JAN-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.61 |
February | 7657.86 | 26-FEB-16:53 | 195.68 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.41 |
March | 10887.63 | 30-MAR-16:30 | 391.37 | 195.43 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 69.52 | 0.00 |
April | 20052.88 | 09-APR-16:52 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.04 |
May | 21771.77 | 21-MAY-16:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.53 |
June | 21153.31 | 25-JUN-16:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 365.55 | 0.00 |
July | 23341.38 | 16-JUL-16:11 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 121.02 | 0.00 |
August | 22660.50 | 13-AUG-18:11 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 70.78 | 0.00 |
September | 21621.58 | 04-SEP-16:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
October | 15968.32 | 09-OCT-16:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 | 0.00 |
November | 7030.21 | 06-NOV-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.76 |
December | 3367.84 | 11-DEC-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2673.68 | 0.00 | 58.63 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23341.38 | 1239.33 | 351.77 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 365.55 | 168.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4635.26 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.92 |
February | 4678.94 | 27-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.31 |
March | 5892.03 | 13-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 |
April | 7723.87 | 17-APR-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 0.00 |
May | 11034.47 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 |
June | 10501.69 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 |
July | 12303.81 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.80 |
August | 12125.54 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 |
September | 11791.23 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.57 |
October | 10080.89 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.58 |
November | 7224.23 | 06-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.26 |
December | 4574.21 | 13-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4574.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12303.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 560.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6684.76 | 28-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2184.16 |
February | 8558.45 | 12-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7180.11 |
March | 4999.67 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.96 |
April | 5579.06 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 0.00 |
May | 6122.93 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.85 | 0.00 |
June | 7612.28 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.31 |
July | 9154.66 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.71 |
August | 8703.12 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.14 |
September | 8023.06 | 11-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 |
October | 4020.10 | 11-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.08 | 0.00 |
November | 6931.98 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3708.59 |
December | 7079.86 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3067.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4020.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9154.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.85 | 7180.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1045.02 | 29-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.98 |
February | 6099.72 | 28-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.77 |
March | 13174.89 | 30-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.31 | 0.00 |
April | 17770.84 | 17-APR-14:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 | 0.00 |
May | 17835.49 | 19-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.22 | 0.00 |
June | 17871.80 | 12-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.61 | 0.00 |
July | 19745.95 | 07-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.82 | 0.00 |
August | 18576.88 | 01-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.95 | 0.00 |
September | 15268.31 | 06-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.41 | 0.00 |
October | 10753.99 | 10-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.40 | 0.00 |
November | 4574.90 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.89 |
December | 2411.99 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1045.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19745.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.61 | 577.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1729.68 | 26-JAN-17:30 | 70.15 | 81.29 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4046.79 | 20-FEB-17:45 | 23.38 | 16.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7114.52 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7997.78 | 09-APR-18:15 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3423.53 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5338.51 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7232.14 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7823.85 | 20-AUG-17:20 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3218.69 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5106.13 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5947.16 | 11-NOV-17:05 | 46.77 | 32.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7690.75 | 10-DEC-16:55 | 23.38 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1729.68 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7997.78 | 70.15 | 81.29 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1442.62 | 26-JAN-17:40 | 70.15 | 81.29 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3588.91 | 24-FEB-18:00 | 70.15 | 81.29 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6660.66 | 31-MAR-23:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7423.91 | 09-APR-18:30 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3233.72 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5075.51 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6965.54 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7363.85 | 20-AUG-16:32 | 58.46 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2749.74 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4415.98 | 31-OCT-23:40 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5409.01 | 06-NOV-17:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6989.51 | 08-DEC-17:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1442.62 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7423.91 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1376.43 | 20-JAN-17:00 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3534.73 | 24-FEB-17:50 | 70.15 | 81.29 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6423.83 | 31-MAR-23:20 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7464.79 | 09-APR-18:23 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3179.65 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5041.07 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6989.55 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7616.07 | 20-AUG-17:17 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2291.63 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3930.52 | 31-OCT-23:20 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5389.58 | 06-NOV-17:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6889.15 | 07-DEC-17:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1376.43 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7616.07 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89960.77 | 20-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181568.76 | 21-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357116.18 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367749.06 | 15-APR-17:01 | 1771.62 | 1115.56 | 2657427.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 174425.08 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266447.50 | 30-JUN-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358856.28 | 31-JUL-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369430.51 | 07-AUG-21:23 | 759.27 | 956.20 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175310.44 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267422.41 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275577.47 | 06-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366256.58 | 11-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89960.77 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369430.51 | 4808.68 | 2868.67 | 2657427.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.135171E+13 | 825626.46 | 31-JAN-14:00 | 0.252595E+12 | 1274561.21 | 09-JAN-06:10 |
February | 0.161285E+13 | 1187225.27 | 28-FEB-16:19 | 0.156457E+12 | 1337808.05 | 13-FEB-07:10 |
March | 0.221888E+13 | 1433482.78 | 30-MAR-15:39 | 0.760842E+11 | 341480.25 | 18-MAR-05:10 |
April | 0.256679E+13 | 1727711.55 | 17-APR-15:39 | 0.632731E+11 | 389339.86 | 06-APR-06:10 |
May | 0.161087E+13 | 1237900.94 | 15-MAY-14:50 | 0.613554E+11 | 160483.99 | 15-MAY-14:39 |
June | 0.214882E+13 | 1372599.23 | 19-JUN-15:00 | 0.557991E+11 | 107379.97 | 02-JUN-15:00 |
July | 0.264940E+13 | 1559513.22 | 07-JUL-15:09 | 0.525331E+11 | 68549.62 | 03-JUL-11:39 |
August | 0.314062E+13 | 1695869.43 | 03-AUG-15:50 | 0.555773E+11 | 81472.97 | 25-AUG-11:09 |
September | 0.160975E+13 | 1201684.70 | 06-SEP-15:50 | 0.532979E+11 | 89393.92 | 15-SEP-11:50 |
October | 0.180550E+13 | 1286800.72 | 02-OCT-15:50 | 0.617948E+11 | 351633.17 | 26-OCT-06:10 |
November | 0.210105E+13 | 1293309.62 | 08-NOV-16:40 | 0.814245E+11 | 665607.67 | 22-NOV-07:10 |
December | 0.246260E+13 | 1320817.45 | 12-DEC-16:00 | 0.139697E+12 | 932539.93 | 18-DEC-07:10 |
Annual Sum or Average | 0.252788E+14 | 0.110989E+13 | ||||
Minimum of Months | 0.135171E+13 | 825626.46 | 0.525331E+11 | 68549.62 | ||
Maximum of Months | 0.314062E+13 | 1727711.55 | 0.252595E+12 | 1337808.05 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.280538E+11 | 62621.79 | 27-JAN-12:50 | 0.00 | 0.00 |
February | 0.302613E+11 | 72322.58 | 24-FEB-12:50 | 0.00 | 0.00 |
March | 0.461621E+11 | 85454.00 | 18-MAR-12:50 | 0.00 | 0.00 |
April | 0.540037E+11 | 87760.65 | 06-APR-12:39 | 0.00 | 0.00 |
May | 0.605543E+11 | 87682.80 | 10-MAY-12:20 | 0.00 | 0.00 |
June | 0.617030E+11 | 85738.09 | 10-JUN-12:30 | 0.00 | 0.00 |
July | 0.591308E+11 | 82708.14 | 24-JUL-12:30 | 0.00 | 0.00 |
August | 0.546429E+11 | 79395.73 | 02-AUG-12:30 | 0.00 | 0.00 |
September | 0.403014E+11 | 75751.95 | 14-SEP-12:30 | 0.00 | 0.00 |
October | 0.371763E+11 | 72935.59 | 25-OCT-12:30 | 0.00 | 0.00 |
November | 0.278432E+11 | 59398.71 | 07-NOV-12:30 | 0.00 | 0.00 |
December | 0.249467E+11 | 55608.84 | 02-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.524779E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.249467E+11 | 55608.84 | 0.00 | 0.00 | |
Maximum of Months | 0.617030E+11 | 87760.65 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.144967E+12 | 0.288379E+11 | 0.766053E+12 | 0.102194E+12 | 0.154635E+12 | 0.140994E+11 | 0.00 | 0.103654E+11 | 0.362403E+10 | 0.122213E+12 | 0.471873E+10 | 0.00 | 0.00 |
February | 0.131486E+12 | 0.236415E+11 | 0.978954E+12 | 0.923114E+11 | 0.142892E+12 | 0.173609E+11 | 0.00 | 0.386810E+11 | 0.159669E+11 | 0.168610E+12 | 0.294947E+10 | 0.00 | 0.00 |
March | 0.154018E+12 | 0.231007E+11 | 0.141687E+13 | 0.102362E+12 | 0.173036E+12 | 0.285187E+11 | 0.00 | 0.115747E+12 | 0.506845E+11 | 0.153199E+12 | 0.134160E+10 | 0.00 | 0.00 |
April | 0.136914E+12 | 0.193773E+11 | 0.165903E+13 | 0.988820E+11 | 0.180963E+12 | 0.376250E+11 | 0.00 | 0.261609E+12 | 0.894093E+11 | 0.820195E+11 | 0.965025E+09 | 0.00 | 0.00 |
May | 0.147086E+12 | 0.173486E+11 | 0.774844E+12 | 0.102278E+12 | 0.204198E+12 | 0.447795E+11 | 0.00 | 0.194202E+12 | 0.108481E+12 | 0.153708E+11 | 0.228146E+10 | 0.00 | 0.00 |
June | 0.146108E+12 | 0.157152E+11 | 0.106252E+13 | 0.990390E+11 | 0.226380E+12 | 0.558499E+11 | 0.00 | 0.376171E+12 | 0.145955E+12 | 0.161282E+11 | 0.495988E+10 | 0.00 | 0.00 |
July | 0.137074E+12 | 0.167301E+11 | 0.139340E+13 | 0.102120E+12 | 0.234908E+12 | 0.662337E+11 | 0.00 | 0.522957E+12 | 0.170377E+12 | 0.00 | 0.559575E+10 | 0.00 | 0.00 |
August | 0.152986E+12 | 0.189002E+11 | 0.173200E+13 | 0.102362E+12 | 0.244962E+12 | 0.712332E+11 | 0.00 | 0.632226E+12 | 0.179750E+12 | 1333000.12 | 0.620243E+10 | 0.00 | 0.00 |
September | 0.137520E+12 | 0.210034E+11 | 0.740713E+12 | 0.988813E+11 | 0.197359E+12 | 0.466781E+11 | 0.00 | 0.237042E+12 | 0.126606E+12 | 0.543493E+09 | 0.340015E+10 | 0.00 | 0.00 |
October | 0.144189E+12 | 0.247756E+11 | 0.108340E+13 | 0.102195E+12 | 0.175479E+12 | 0.315649E+11 | 0.00 | 0.137645E+12 | 0.633532E+11 | 0.409723E+11 | 0.192146E+10 | 0.00 | 0.00 |
November | 0.142913E+12 | 0.270996E+11 | 0.135889E+13 | 0.989457E+11 | 0.157760E+12 | 0.250568E+11 | 0.00 | 0.918533E+11 | 0.384716E+11 | 0.158347E+12 | 0.170628E+10 | 0.00 | 0.00 |
December | 0.140476E+12 | 0.296960E+11 | 0.170972E+13 | 0.102120E+12 | 0.156130E+12 | 0.213112E+11 | 0.00 | 0.757637E+11 | 0.218004E+11 | 0.202493E+12 | 0.309263E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171574E+13 | 0.266226E+12 | 0.146764E+14 | 0.120369E+13 | 0.224870E+13 | 0.460311E+12 | 0.00 | 0.269426E+13 | 0.101448E+13 | 0.959899E+12 | 0.391349E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131486E+12 | 0.157152E+11 | 0.740713E+12 | 0.923114E+11 | 0.142892E+12 | 0.140994E+11 | 0.00 | 0.103654E+11 | 0.362403E+10 | 0.00 | 0.965025E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154018E+12 | 0.296960E+11 | 0.173200E+13 | 0.102362E+12 | 0.244962E+12 | 0.712332E+11 | 0.00 | 0.632226E+12 | 0.179750E+12 | 0.202493E+12 | 0.620243E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.187044E+12 | 0.00 | 0.655510E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.969106E+11 | 0.00 | 0.595463E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.896439E+10 | 0.00 | 0.671198E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.383585E+10 | 0.00 | 0.594373E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.195240E+10 | 0.00 | 0.594030E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.457394E+09 | 0.00 | 0.553417E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.525331E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.123653E+09 | 0.00 | 0.554537E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.218946E+09 | 0.00 | 0.530789E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.419649E+10 | 0.00 | 0.575983E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.219735E+11 | 0.00 | 0.594510E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.769327E+11 | 0.00 | 0.627645E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.402610E+12 | 0.00 | 0.707279E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.525331E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.187044E+12 | 0.00 | 0.671198E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 165116.73 | 03-JAN-08:09 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73698.22 | 03-JAN-08:20 | 86720.82 | 09-JAN-06:10 | 23199.66 | 06-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 168351.69 | 01-FEB-08:09 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73699.92 | 01-FEB-08:20 | 130528.25 | 28-FEB-16:19 | 23208.83 | 13-FEB-07:19 | 0.00 | 01-FEB-00:10 |
March | 165773.03 | 21-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73698.57 | 21-MAR-07:19 | 158674.39 | 29-MAR-15:00 | 46863.08 | 30-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 161419.16 | 03-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73696.28 | 03-APR-07:19 | 243358.10 | 12-APR-15:09 | 46642.65 | 17-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 150100.60 | 24-MAY-07:30 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73690.34 | 24-MAY-07:40 | 246688.59 | 15-MAY-14:50 | 45297.14 | 15-MAY-14:39 | 0.00 | 01-MAY-00:10 |
June | 148329.76 | 23-JUN-07:10 | 31088.59 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 73689.41 | 23-JUN-07:19 | 212231.94 | 02-JUN-14:39 | 45422.67 | 02-JUN-10:00 | 0.00 | 01-JUN-00:10 |
July | 152306.94 | 27-JUL-07:10 | 31088.59 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 73691.50 | 27-JUL-07:19 | 216308.60 | 06-JUL-15:20 | 44464.37 | 07-JUL-10:09 | 0.00 | 01-JUL-00:10 |
August | 159532.16 | 24-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73695.29 | 24-AUG-07:19 | 215751.16 | 17-AUG-15:00 | 45077.90 | 25-AUG-13:20 | 0.00 | 01-AUG-00:10 |
September | 163081.95 | 29-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73697.15 | 29-SEP-07:19 | 196070.54 | 05-SEP-15:50 | 45659.44 | 06-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 169602.33 | 30-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73700.58 | 30-OCT-07:19 | 149574.52 | 02-OCT-15:00 | 45897.32 | 11-OCT-11:50 | 0.00 | 01-OCT-00:10 |
November | 168847.32 | 01-NOV-07:10 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73700.18 | 01-NOV-07:19 | 125384.13 | 06-NOV-16:40 | 23462.39 | 06-NOV-13:20 | 0.00 | 01-NOV-00:10 |
December | 165211.38 | 06-DEC-08:09 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73698.27 | 06-DEC-08:20 | 95508.89 | 12-DEC-14:50 | 23116.81 | 12-DEC-13:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 148329.76 | 31088.59 | 423497.50 | 73689.41 | 86720.82 | 23116.81 | 0.00 | |||||||
Maximum of Months | 169602.33 | 31088.59 | 778371.69 | 73700.58 | 246688.59 | 46863.08 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 58740.51 | 31-JAN-15:09 | 44593.25 | 19-JAN-21:00 | 100000.00 | 29-JAN-13:30 | 4520.72 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 169071.50 | 28-FEB-14:00 | 45805.90 | 28-FEB-14:00 | 100000.00 | 03-FEB-18:10 | 4520.72 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 316926.16 | 30-MAR-15:09 | 79310.05 | 29-MAR-15:09 | 100000.00 | 05-MAR-13:30 | 4520.72 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 357284.21 | 17-APR-15:39 | 79310.05 | 04-APR-12:00 | 100000.00 | 01-APR-05:10 | 4520.72 | 04-APR-10:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 279308.48 | 19-MAY-14:39 | 79310.05 | 02-MAY-12:39 | 100000.00 | 09-MAY-09:00 | 4520.72 | 03-MAY-11:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 329007.50 | 27-JUN-12:09 | 79310.05 | 01-JUN-08:20 | 100000.00 | 10-JUN-17:10 | 4520.72 | 01-JUN-06:49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 374489.13 | 06-JUL-12:09 | 79310.05 | 01-JUL-07:30 | 0.00 | 01-JUL-00:10 | 4520.72 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 401101.85 | 03-AUG-12:09 | 79310.05 | 01-AUG-06:40 | 887.88 | 06-AUG-13:50 | 4520.72 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 294736.85 | 08-SEP-12:09 | 79310.05 | 01-SEP-09:39 | 52139.64 | 14-SEP-12:00 | 4520.72 | 01-SEP-09:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 285857.42 | 10-OCT-13:00 | 79310.05 | 02-OCT-09:20 | 100000.00 | 06-OCT-17:49 | 4520.72 | 02-OCT-08:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 174401.33 | 02-NOV-13:09 | 47221.98 | 02-NOV-12:00 | 100000.00 | 06-NOV-22:10 | 4520.72 | 01-NOV-06:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 203112.18 | 12-DEC-13:00 | 46601.64 | 12-DEC-13:00 | 100000.00 | 01-DEC-04:49 | 4520.72 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 58740.51 | 44593.25 | 0.00 | 4520.72 | 0.00 | 0.00 | |||||
Maximum of Months | 401101.85 | 79310.05 | 100000.00 | 4520.72 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 825626.46 | 31-JAN-14:00 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 73775.91 | 22927.68 | 0.00 | 56272.16 | 44060.51 |
February | 1187225.27 | 28-FEB-16:19 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 130528.25 | 23068.89 | 0.00 | 148079.18 | 45183.23 |
March | 1433482.78 | 30-MAR-15:39 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 154351.87 | 45493.74 | 0.00 | 294163.11 | 79310.05 |
April | 1727711.55 | 17-APR-15:39 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 214360.11 | 46642.65 | 0.00 | 357284.21 | 65216.68 |
May | 1237900.94 | 15-MAY-14:50 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 246688.59 | 45077.35 | 0.00 | 271375.17 | 79310.05 |
June | 1372599.23 | 19-JUN-15:00 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 202209.17 | 43934.79 | 0.00 | 302258.76 | 79310.05 |
July | 1559513.22 | 07-JUL-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 215082.09 | 44083.32 | 0.00 | 357859.91 | 79310.05 |
August | 1695869.43 | 03-AUG-15:50 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 212227.78 | 44167.16 | 0.00 | 378695.19 | 79310.05 |
September | 1201684.70 | 06-SEP-15:50 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 182944.16 | 43775.11 | 0.00 | 269060.33 | 79310.05 |
October | 1286800.72 | 02-OCT-15:50 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 144878.11 | 44200.67 | 0.00 | 273525.44 | 79310.05 |
November | 1293309.62 | 08-NOV-16:40 | 148329.09 | 660080.29 | 0.00 | 52590.27 | 115736.93 | 22996.46 | 0.00 | 149395.10 | 44181.49 |
December | 1320817.45 | 12-DEC-16:00 | 157161.91 | 778371.69 | 0.00 | 52593.54 | 86718.48 | 22982.84 | 0.00 | 177483.15 | 45505.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 825626.46 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 73775.91 | 22927.68 | 0.00 | 56272.16 | 44060.51 | |
Maximum of Months | 1727711.55 | 157161.91 | 778371.69 | 0.00 | 52593.54 | 246688.59 | 46642.65 | 0.00 | 378695.19 | 79310.05 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1267280.33 | 09-JAN-06:10 | 0.00 | 81272.79 | 27-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 1307065.00 | 13-FEB-07:10 | 0.00 | 81280.70 | 02-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 323464.28 | 23-MAR-05:10 | 0.00 | 80712.85 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 365608.87 | 06-APR-06:10 | 0.00 | 78566.68 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 128322.77 | 15-MAY-16:40 | 0.00 | 75678.56 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 63965.64 | 02-JUN-15:00 | 0.00 | 71795.90 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 68549.62 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 36296.70 | 25-AUG-13:50 | 0.00 | 68281.21 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 40308.82 | 23-SEP-11:00 | 0.00 | 71278.35 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 344352.29 | 26-OCT-06:10 | 0.00 | 75087.73 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 657090.85 | 22-NOV-07:10 | 0.00 | 78367.88 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 913035.62 | 26-DEC-05:19 | 0.00 | 80374.29 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 68281.21 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1307065.00 | 0.00 | 81280.70 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.15 | 2.67 | 27.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.70 | 0.00 | 25.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.72 | 0.00 | 25.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.69 | 0.00 | 25.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.05 | 0.00 | 26.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.70 | 0.17 | 25.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.34 | 0.50 | 26.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.71 | 0.17 | 26.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.24 | 0.33 | 27.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.31 | 1.00 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.17 | 1.50 | 27.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.81 | 0.67 | 26.91 |
Annual Sum or Average | 0.00 | 0.00 | 61.17 | 26.82 | 7.00 | 26.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.69 | 0.00 | 25.62 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.31 | 2.67 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.64 | 0.00 | 25.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 25.63 | 0.00 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.64 | 0.00 | 25.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.85 | 0.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 1.17 | 18.92 | 0.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Annual Sum or Average | 5.67 | 18.88 | 0.83 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 18.92 | 0.67 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.30 | 2.33 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.77 | 2.50 | 26.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.00 | 27.02 | 4.83 | 27.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.30 | 2.50 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.38 | 0.00 | 19.38 | 0.17 | 23.39 | 0.17 | 24.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.37 | 1.00 | 27.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.68 | 1.83 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.58 | 6.00 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.67 | 7.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.62 | 11.17 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.59 | 7.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.73 | 2.67 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.50 | 1.83 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.38 | 0.00 | 19.38 | 41.33 | 27.58 | 39.67 | 27.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 19.38 | 11.83 | 27.73 | 11.17 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.10 | 0.00 | 19.10 | 1.00 | 26.26 | 1.00 | 26.81 |
February | 0.17 | 19.26 | 0.00 | 19.26 | 2.83 | 27.35 | 2.83 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.47 | 3.33 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.48 | 2.33 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.39 | 1.17 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.23 | 2.50 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.32 | 6.50 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.34 | 6.50 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.54 | 5.17 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.23 | 8.00 | 27.22 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.39 | 6.00 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.74 | 1.50 | 27.74 |
Annual Sum or Average | 0.33 | 19.18 | 0.00 | 19.18 | 51.00 | 27.34 | 46.83 | 27.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.26 | 1.00 | 26.81 |
Maximum of Months | 0.17 | 19.26 | 0.00 | 19.26 | 9.00 | 27.74 | 8.00 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.85 | 2.17 | 27.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.89 | 3.83 | 27.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.47 | 8.50 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.69 | 4.17 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.51 | 8.33 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.61 | 14.83 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 | 27.55 | 18.00 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.40 | 5.83 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.70 | 4.67 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.79 | 4.33 | 27.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.17 | 27.55 |
Annual Sum or Average | 0.00 | 0.00 | 176.83 | 27.58 | 75.83 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 | 27.89 | 18.00 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 18.75 | 2.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 10.67 | 17.38 | 3.17 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.33 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.40 | 2.17 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
December | 4.00 | 18.92 | 0.33 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 28.67 | 18.28 | 6.33 | 18.44 | 3.67 | 19.29 | 2.50 | 19.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 19.20 | 3.17 | 19.20 | 3.17 | 27.40 | 2.17 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.50 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
February | 8.00 | 17.72 | 0.50 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 2.17 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.63 | 6.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.78 | 8.17 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.80 | 12.00 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.78 | 8.83 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.72 | 2.67 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.38 | 0.83 | 27.38 |
November | 0.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 2.67 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 29.67 | 18.53 | 0.50 | 18.46 | 44.33 | 23.99 | 40.67 | 25.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.50 | 19.18 | 0.50 | 19.18 | 14.00 | 27.80 | 12.00 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.33 | 18.72 | 0.50 | 18.84 | 1.00 | 19.95 | 1.00 | 20.81 |
February | 4.33 | 17.64 | 0.67 | 17.43 | 3.17 | 21.32 | 3.17 | 23.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.40 | 2.17 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.55 | 1.33 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.35 | 2.00 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.41 | 6.33 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.62 | 5.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.57 | 4.67 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.66 | 10.00 | 26.66 |
November | 0.33 | 19.25 | 0.00 | 19.25 | 6.83 | 26.35 | 6.83 | 26.52 |
December | 1.67 | 19.12 | 0.00 | 19.12 | 1.33 | 22.98 | 1.33 | 24.46 |
Annual Sum or Average | 12.67 | 18.42 | 1.17 | 18.37 | 46.67 | 25.18 | 45.17 | 26.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 19.95 | 0.67 | 20.81 |
Maximum of Months | 6.33 | 19.25 | 0.67 | 19.25 | 10.17 | 27.62 | 10.00 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
February | 3.67 | 17.11 | 0.83 | 16.69 | 0.50 | 17.77 | 0.50 | 18.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.50 | 1.00 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.85 | 2.17 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.91 | 2.67 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.86 | 4.17 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.94 | 6.83 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.71 | 5.33 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.77 | 3.83 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.75 | 2.33 | 27.76 |
November | 0.33 | 19.15 | 0.00 | 19.15 | 0.50 | 24.06 | 0.50 | 25.28 |
December | 1.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 11.00 | 18.18 | 0.83 | 17.95 | 54.83 | 26.07 | 29.33 | 26.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.77 | 0.00 | 18.58 |
Maximum of Months | 5.33 | 19.15 | 0.83 | 19.15 | 14.50 | 27.94 | 6.83 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.83 | 17.09 | 16.50 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
February | 30.00 | 16.72 | 10.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
March | 1.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
April | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.50 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.43 | 3.00 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.52 | 5.83 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.42 | 3.50 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
November | 4.33 | 18.87 | 0.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
December | 26.17 | 17.27 | 8.33 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
Annual Sum or Average | 112.00 | 17.13 | 35.83 | 17.34 | 19.33 | 18.51 | 12.83 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.83 | 19.30 | 16.50 | 19.30 | 9.17 | 27.52 | 5.83 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.83 | 16.00 | 3.17 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
February | 15.17 | 15.96 | 1.50 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
March | 1.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
April | 0.17 | 19.24 | 0.00 | 19.24 | 2.17 | 26.95 | 2.17 | 27.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.60 | 6.67 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.82 | 8.67 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.87 | 13.00 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.82 | 9.00 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.62 | 3.67 | 27.62 |
October | 0.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
November | 2.33 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
December | 14.33 | 16.37 | 1.50 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
Annual Sum or Average | 59.33 | 16.27 | 6.17 | 16.17 | 53.00 | 21.36 | 43.17 | 23.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 | 15.92 |
Maximum of Months | 25.83 | 19.29 | 3.17 | 19.29 | 17.50 | 27.87 | 13.00 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.83 | 16.91 | 4.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
February | 13.33 | 16.76 | 2.67 | 16.82 | 1.67 | 17.84 | 1.67 | 18.69 |
March | 0.50 | 19.16 | 0.00 | 19.16 | 0.33 | 22.41 | 0.33 | 23.80 |
April | 0.17 | 19.32 | 0.00 | 19.32 | 1.50 | 26.50 | 1.50 | 26.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.47 | 1.50 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.49 | 4.33 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.58 | 7.83 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.72 | 6.00 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.61 | 5.50 | 27.62 |
October | 0.17 | 19.38 | 0.00 | 19.38 | 5.67 | 27.43 | 5.50 | 27.55 |
November | 2.17 | 18.74 | 0.33 | 18.96 | 3.00 | 23.74 | 3.00 | 25.15 |
December | 9.33 | 17.88 | 1.33 | 17.93 | 0.67 | 18.48 | 0.67 | 18.98 |
Annual Sum or Average | 47.50 | 17.18 | 8.33 | 17.23 | 45.33 | 21.88 | 37.83 | 23.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 | 0.00 | 16.96 |
Maximum of Months | 21.83 | 19.38 | 4.00 | 19.38 | 11.17 | 27.72 | 7.83 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 16.12 | 3.17 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
February | 9.83 | 15.97 | 2.17 | 15.70 | 0.33 | 16.01 | 0.33 | 16.31 |
March | 0.33 | 19.22 | 0.00 | 19.22 | 0.67 | 24.71 | 0.50 | 25.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.92 | 2.17 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.01 | 2.83 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.99 | 4.83 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 28.03 | 8.33 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.74 | 6.17 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.85 | 3.83 | 27.87 |
October | 0.17 | 19.42 | 0.00 | 19.42 | 2.17 | 27.21 | 1.83 | 27.48 |
November | 1.50 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
December | 6.00 | 17.85 | 0.83 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
Annual Sum or Average | 35.50 | 16.50 | 6.17 | 16.24 | 60.67 | 23.16 | 30.83 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 0.00 | 15.93 |
Maximum of Months | 17.67 | 19.42 | 3.17 | 19.42 | 17.50 | 28.03 | 8.33 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 | 27.82 | 71.67 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 79.17 | 27.82 | 71.67 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 | 27.82 | 71.67 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 27.80 | 57.50 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 61.17 | 27.80 | 57.50 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 27.80 | 57.50 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 27.80 | 44.33 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 51.00 | 27.80 | 44.33 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 27.80 | 44.33 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 28.32 | 29.83 | 28.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 428.83 | 28.99 | 372.00 | 29.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 458.67 | 28.95 | 401.83 | 28.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 428.83 | 28.99 | 372.00 | 29.03 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.83 | 23.86 | 53.50 | 24.10 | 0.00 | 24.10 |
February | 194.50 | 24.09 | 83.83 | 24.44 | 12.67 | 24.53 |
March | 108.50 | 24.01 | 150.83 | 24.51 | 2.67 | 24.50 |
April | 76.83 | 24.38 | 240.67 | 24.69 | 35.33 | 24.70 |
May | 161.00 | 24.54 | 424.67 | 24.51 | 148.83 | 24.52 |
June | 296.00 | 24.41 | 446.33 | 24.44 | 295.83 | 24.43 |
July | 371.17 | 24.76 | 497.00 | 24.65 | 371.17 | 24.69 |
August | 278.17 | 24.84 | 514.00 | 24.60 | 278.17 | 24.66 |
September | 187.00 | 25.00 | 471.83 | 24.68 | 187.00 | 24.75 |
October | 50.83 | 25.15 | 300.17 | 24.97 | 46.83 | 25.01 |
November | 71.67 | 24.58 | 198.67 | 25.12 | 23.00 | 25.17 |
December | 149.33 | 24.00 | 149.50 | 24.71 | 4.67 | 24.70 |
Annual Sum or Average | 2216.83 | 24.46 | 3531.00 | 24.60 | 1406.17 | 24.64 |
Minimum of Months | 50.83 | 23.86 | 53.50 | 24.10 | 0.00 | 24.10 |
Maximum of Months | 371.17 | 25.15 | 514.00 | 25.12 | 371.17 | 25.17 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 358.00 | 23.88 | 44.50 | 23.97 | 18.83 | 24.03 |
February | 202.17 | 23.97 | 66.33 | 24.15 | 3.83 | 24.17 |
March | 62.67 | 24.02 | 167.67 | 24.45 | 0.00 | 24.45 |
April | 13.33 | 24.00 | 271.00 | 24.44 | 0.00 | 24.44 |
May | 7.50 | 24.00 | 435.67 | 24.30 | 0.00 | 24.30 |
June | 0.00 | 0.00 | 456.50 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 497.00 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
September | 6.33 | 26.18 | 472.00 | 24.36 | 6.33 | 24.39 |
October | 19.33 | 25.19 | 290.67 | 24.64 | 11.50 | 24.69 |
November | 66.67 | 24.04 | 185.50 | 24.62 | 1.17 | 24.62 |
December | 120.00 | 24.00 | 126.50 | 24.51 | 0.00 | 24.51 |
Annual Sum or Average | 856.00 | 23.99 | 3527.33 | 24.31 | 41.67 | 24.33 |
Minimum of Months | 0.00 | 0.00 | 44.50 | 23.97 | 0.00 | 24.03 |
Maximum of Months | 358.00 | 26.18 | 514.00 | 24.64 | 18.83 | 24.69 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.17 | 22.33 | 45.17 | 22.22 | 45.17 | 22.13 |
February | 417.67 | 22.95 | 36.67 | 22.91 | 29.83 | 22.86 |
March | 264.67 | 23.69 | 104.67 | 23.85 | 0.00 | 23.85 |
April | 99.83 | 23.86 | 198.33 | 24.21 | 5.00 | 24.23 |
May | 17.67 | 23.87 | 407.00 | 24.19 | 0.00 | 24.19 |
June | 7.50 | 24.01 | 439.00 | 24.21 | 0.67 | 24.21 |
July | 2.33 | 25.63 | 496.17 | 24.25 | 2.33 | 24.26 |
August | 0.00 | 0.00 | 514.00 | 24.20 | 0.00 | 24.20 |
September | 11.33 | 25.54 | 455.17 | 24.28 | 10.50 | 24.31 |
October | 124.33 | 23.68 | 190.33 | 24.06 | 15.50 | 24.08 |
November | 320.67 | 23.70 | 67.17 | 23.78 | 11.67 | 23.79 |
December | 442.00 | 23.08 | 26.00 | 23.14 | 2.50 | 23.14 |
Annual Sum or Average | 2201.17 | 23.14 | 2979.67 | 23.73 | 123.17 | 23.71 |
Minimum of Months | 0.00 | 0.00 | 26.00 | 22.22 | 0.00 | 22.13 |
Maximum of Months | 493.17 | 25.63 | 514.00 | 24.28 | 45.17 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.33 | 21.04 | 218.17 | 20.73 | 218.17 | 20.56 |
February | 437.33 | 21.86 | 98.67 | 21.58 | 96.67 | 21.38 |
March | 375.17 | 23.02 | 88.33 | 23.15 | 15.33 | 23.11 |
April | 184.83 | 23.41 | 170.00 | 23.80 | 10.83 | 23.83 |
May | 45.67 | 23.70 | 394.83 | 24.15 | 5.17 | 24.15 |
June | 11.50 | 23.70 | 436.83 | 24.24 | 0.17 | 24.24 |
July | 2.00 | 25.35 | 486.00 | 24.32 | 2.00 | 24.33 |
August | 0.00 | 0.00 | 514.00 | 24.24 | 0.00 | 24.24 |
September | 40.83 | 23.86 | 418.50 | 24.22 | 15.17 | 24.25 |
October | 302.50 | 23.04 | 132.50 | 23.33 | 27.67 | 23.34 |
November | 434.67 | 22.55 | 56.83 | 22.54 | 36.33 | 22.47 |
December | 481.50 | 21.56 | 142.33 | 21.31 | 137.33 | 21.14 |
Annual Sum or Average | 2814.33 | 22.22 | 3157.00 | 22.96 | 564.83 | 22.76 |
Minimum of Months | 0.00 | 0.00 | 56.83 | 20.73 | 0.00 | 20.56 |
Maximum of Months | 498.33 | 25.35 | 514.00 | 24.32 | 218.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.50 | 21.68 | 149.00 | 21.49 | 145.00 | 21.36 |
February | 404.67 | 22.34 | 73.83 | 22.14 | 64.50 | 21.95 |
March | 307.00 | 23.36 | 100.33 | 23.57 | 0.00 | 23.57 |
April | 113.33 | 23.50 | 217.33 | 24.04 | 0.00 | 24.04 |
May | 39.50 | 24.26 | 415.83 | 24.32 | 10.67 | 24.35 |
June | 20.17 | 25.73 | 454.33 | 24.42 | 16.17 | 24.48 |
July | 34.67 | 26.40 | 497.00 | 24.56 | 34.67 | 24.67 |
August | 27.00 | 26.47 | 514.00 | 24.43 | 27.00 | 24.52 |
September | 38.50 | 25.21 | 431.33 | 24.44 | 27.33 | 24.53 |
October | 214.83 | 23.45 | 182.00 | 23.85 | 10.50 | 23.88 |
November | 346.17 | 23.22 | 77.33 | 23.40 | 1.50 | 23.39 |
December | 430.83 | 22.69 | 44.17 | 22.73 | 12.50 | 22.68 |
Annual Sum or Average | 2456.17 | 22.88 | 3156.50 | 23.56 | 349.83 | 23.51 |
Minimum of Months | 20.17 | 21.68 | 44.17 | 21.49 | 0.00 | 21.36 |
Maximum of Months | 479.50 | 26.47 | 514.00 | 24.56 | 145.00 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.83 | 22.04 | 106.50 | 21.84 | 102.83 | 21.68 |
February | 366.17 | 22.42 | 57.50 | 22.39 | 38.67 | 22.25 |
March | 243.83 | 23.26 | 119.83 | 23.63 | 0.17 | 23.63 |
April | 100.17 | 23.51 | 258.50 | 24.12 | 4.00 | 24.15 |
May | 56.33 | 25.71 | 438.67 | 24.58 | 38.17 | 24.73 |
June | 39.83 | 26.39 | 467.67 | 24.56 | 36.67 | 24.70 |
July | 57.17 | 26.60 | 495.50 | 24.69 | 57.17 | 24.87 |
August | 41.50 | 26.66 | 514.00 | 24.50 | 41.50 | 24.65 |
September | 62.83 | 25.66 | 435.33 | 24.59 | 48.17 | 24.75 |
October | 179.17 | 23.39 | 219.67 | 23.99 | 16.50 | 24.05 |
November | 295.33 | 23.15 | 84.00 | 23.43 | 1.17 | 23.42 |
December | 433.50 | 22.70 | 37.67 | 22.73 | 11.17 | 22.68 |
Annual Sum or Average | 2352.67 | 23.10 | 3234.83 | 23.76 | 396.17 | 23.80 |
Minimum of Months | 39.83 | 22.04 | 37.67 | 21.84 | 0.17 | 21.68 |
Maximum of Months | 476.83 | 26.66 | 514.00 | 24.69 | 102.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.00 | 21.98 | 112.00 | 21.95 | 85.50 | 21.76 |
February | 313.67 | 22.48 | 73.17 | 22.66 | 32.33 | 22.58 |
March | 212.67 | 23.31 | 170.33 | 23.86 | 2.33 | 23.88 |
April | 102.17 | 23.60 | 270.67 | 24.18 | 7.83 | 24.24 |
May | 48.50 | 24.44 | 413.67 | 24.36 | 16.83 | 24.42 |
June | 28.67 | 25.63 | 445.17 | 24.44 | 21.17 | 24.52 |
July | 43.33 | 26.49 | 497.00 | 24.60 | 43.33 | 24.74 |
August | 32.33 | 26.71 | 514.00 | 24.49 | 32.33 | 24.62 |
September | 63.17 | 25.76 | 438.67 | 24.62 | 49.33 | 24.79 |
October | 165.17 | 23.81 | 274.83 | 24.24 | 35.33 | 24.40 |
November | 237.17 | 23.43 | 163.50 | 23.92 | 19.00 | 24.02 |
December | 320.67 | 22.66 | 92.67 | 22.97 | 15.50 | 22.91 |
Annual Sum or Average | 1958.50 | 23.15 | 3465.67 | 23.89 | 360.83 | 23.92 |
Minimum of Months | 28.67 | 21.98 | 73.17 | 21.95 | 2.33 | 21.76 |
Maximum of Months | 391.00 | 26.71 | 514.00 | 24.62 | 85.50 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.83 | 22.50 | 68.17 | 22.52 | 36.17 | 22.40 |
February | 249.50 | 23.24 | 106.00 | 23.56 | 19.00 | 23.53 |
March | 70.33 | 24.68 | 264.83 | 24.67 | 16.00 | 24.78 |
April | 52.50 | 26.44 | 399.33 | 24.91 | 43.50 | 25.09 |
May | 44.50 | 26.36 | 468.50 | 24.68 | 38.67 | 24.83 |
June | 53.67 | 26.96 | 483.50 | 24.80 | 53.67 | 24.99 |
July | 103.00 | 26.89 | 497.00 | 25.06 | 103.00 | 25.33 |
August | 96.17 | 26.90 | 514.00 | 24.93 | 96.17 | 25.20 |
September | 58.33 | 26.82 | 476.50 | 24.81 | 58.33 | 25.00 |
October | 49.33 | 25.72 | 323.33 | 24.86 | 32.17 | 25.01 |
November | 112.33 | 24.29 | 209.00 | 24.68 | 15.17 | 24.78 |
December | 161.33 | 23.86 | 124.33 | 24.27 | 1.00 | 24.29 |
Annual Sum or Average | 1454.83 | 24.33 | 3934.50 | 24.52 | 512.83 | 24.68 |
Minimum of Months | 44.50 | 22.50 | 68.17 | 22.52 | 1.00 | 22.40 |
Maximum of Months | 403.83 | 26.96 | 514.00 | 25.06 | 103.00 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 380.17 | 20.24 | 380.17 | 20.18 |
February | 450.33 | 21.10 | 184.00 | 20.80 | 184.00 | 20.64 |
March | 434.50 | 22.33 | 101.83 | 22.39 | 41.00 | 22.26 |
April | 252.00 | 22.91 | 147.17 | 23.37 | 15.67 | 23.37 |
May | 81.67 | 23.50 | 372.67 | 24.10 | 15.67 | 24.12 |
June | 54.67 | 25.02 | 434.83 | 24.41 | 42.83 | 24.50 |
July | 91.17 | 25.66 | 492.17 | 24.64 | 88.50 | 24.78 |
August | 79.00 | 25.54 | 514.00 | 24.50 | 79.00 | 24.62 |
September | 97.00 | 24.18 | 381.33 | 24.27 | 47.17 | 24.37 |
October | 377.50 | 22.52 | 120.50 | 22.87 | 30.00 | 22.92 |
November | 463.67 | 21.88 | 90.83 | 21.77 | 77.33 | 21.64 |
December | 493.33 | 20.83 | 259.50 | 20.62 | 258.83 | 20.52 |
Annual Sum or Average | 3376.83 | 21.95 | 3479.00 | 22.58 | 1260.17 | 22.40 |
Minimum of Months | 54.67 | 20.39 | 90.83 | 20.24 | 15.67 | 20.18 |
Maximum of Months | 502.00 | 25.66 | 514.00 | 24.64 | 380.17 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.63 | 280.17 | 20.40 | 280.17 | 20.30 |
February | 354.00 | 21.38 | 142.83 | 21.10 | 137.00 | 20.90 |
March | 288.83 | 22.68 | 80.83 | 22.90 | 13.67 | 22.82 |
April | 143.33 | 23.21 | 184.33 | 23.91 | 16.50 | 23.95 |
May | 81.00 | 25.03 | 350.00 | 24.61 | 46.50 | 24.78 |
June | 62.83 | 25.94 | 389.33 | 24.72 | 57.67 | 24.88 |
July | 92.50 | 26.24 | 417.67 | 24.95 | 89.50 | 25.16 |
August | 83.33 | 26.11 | 433.00 | 24.78 | 83.33 | 24.96 |
September | 94.67 | 25.01 | 349.33 | 24.61 | 61.17 | 24.79 |
October | 234.33 | 22.69 | 153.33 | 23.36 | 27.67 | 23.41 |
November | 364.00 | 22.36 | 56.33 | 22.35 | 32.17 | 22.23 |
December | 410.67 | 21.12 | 171.00 | 20.85 | 163.83 | 20.67 |
Annual Sum or Average | 2636.50 | 22.38 | 3008.17 | 23.03 | 1009.17 | 22.93 |
Minimum of Months | 62.83 | 20.63 | 56.33 | 20.40 | 13.67 | 20.30 |
Maximum of Months | 427.00 | 26.24 | 433.00 | 24.95 | 280.17 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 417.33 | 21.25 | 205.50 | 21.03 | 190.50 | 20.82 |
February | 357.50 | 21.83 | 116.67 | 21.80 | 90.17 | 21.63 |
March | 265.17 | 22.69 | 147.33 | 23.27 | 10.33 | 23.23 |
April | 178.83 | 23.16 | 216.67 | 23.83 | 18.67 | 23.88 |
May | 82.83 | 23.79 | 387.17 | 24.20 | 22.50 | 24.25 |
June | 65.17 | 24.89 | 434.50 | 24.42 | 45.00 | 24.51 |
July | 92.33 | 25.77 | 492.33 | 24.67 | 89.83 | 24.83 |
August | 80.83 | 25.88 | 514.00 | 24.60 | 80.83 | 24.75 |
September | 95.83 | 24.96 | 424.17 | 24.53 | 59.00 | 24.69 |
October | 231.00 | 23.21 | 253.00 | 23.87 | 46.83 | 24.02 |
November | 299.83 | 22.78 | 123.00 | 23.24 | 31.17 | 23.27 |
December | 372.33 | 21.66 | 131.83 | 21.63 | 90.17 | 21.40 |
Annual Sum or Average | 2539.00 | 22.66 | 3446.17 | 23.41 | 775.00 | 23.37 |
Minimum of Months | 65.17 | 21.25 | 116.67 | 21.03 | 10.33 | 20.82 |
Maximum of Months | 417.33 | 25.88 | 514.00 | 24.67 | 190.50 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.33 | 20.95 | 275.67 | 20.67 | 275.67 | 20.53 |
February | 414.50 | 21.56 | 134.33 | 21.32 | 123.33 | 21.11 |
March | 302.50 | 22.71 | 134.83 | 23.16 | 9.83 | 23.11 |
April | 152.83 | 23.56 | 261.33 | 24.10 | 25.83 | 24.20 |
May | 61.67 | 24.79 | 425.83 | 24.43 | 32.50 | 24.53 |
June | 58.83 | 25.85 | 458.33 | 24.61 | 50.83 | 24.75 |
July | 93.50 | 26.25 | 494.83 | 24.83 | 93.50 | 25.03 |
August | 80.00 | 26.42 | 514.00 | 24.74 | 80.00 | 24.94 |
September | 90.83 | 25.07 | 429.67 | 24.55 | 57.00 | 24.71 |
October | 275.00 | 22.99 | 185.67 | 23.55 | 31.00 | 23.65 |
November | 377.67 | 22.36 | 85.50 | 22.49 | 37.00 | 22.39 |
December | 470.33 | 21.43 | 159.00 | 21.20 | 144.67 | 21.02 |
Annual Sum or Average | 2874.00 | 22.46 | 3559.00 | 23.18 | 961.17 | 23.09 |
Minimum of Months | 58.83 | 20.95 | 85.50 | 20.67 | 9.83 | 20.53 |
Maximum of Months | 496.33 | 26.42 | 514.00 | 24.83 | 275.67 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 421.67 | 19.92 | 421.67 | 19.87 |
February | 451.17 | 20.75 | 264.50 | 20.49 | 264.50 | 20.37 |
March | 445.67 | 21.79 | 145.50 | 21.77 | 93.33 | 21.59 |
April | 283.33 | 22.50 | 153.83 | 22.90 | 38.83 | 22.82 |
May | 119.83 | 23.33 | 356.67 | 24.01 | 30.00 | 24.04 |
June | 76.00 | 24.83 | 432.33 | 24.43 | 53.83 | 24.53 |
July | 107.67 | 25.57 | 490.33 | 24.67 | 103.33 | 24.82 |
August | 92.50 | 25.54 | 512.33 | 24.54 | 92.50 | 24.67 |
September | 135.83 | 23.80 | 354.83 | 24.17 | 56.83 | 24.28 |
October | 406.50 | 22.01 | 134.67 | 22.31 | 63.33 | 22.31 |
November | 476.00 | 21.22 | 195.83 | 20.98 | 187.50 | 20.82 |
December | 496.50 | 20.31 | 352.50 | 20.12 | 352.33 | 20.04 |
Annual Sum or Average | 3593.00 | 21.62 | 3815.00 | 22.21 | 1758.00 | 22.00 |
Minimum of Months | 76.00 | 20.04 | 134.67 | 19.92 | 30.00 | 19.87 |
Maximum of Months | 502.00 | 25.57 | 512.33 | 24.67 | 421.67 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 384.33 | 20.09 | 384.33 | 20.02 |
February | 436.17 | 21.17 | 207.50 | 20.80 | 207.50 | 20.61 |
March | 364.83 | 22.34 | 120.17 | 22.46 | 42.83 | 22.31 |
April | 172.83 | 22.78 | 227.17 | 23.58 | 27.17 | 23.59 |
May | 103.67 | 24.54 | 408.17 | 24.44 | 52.33 | 24.60 |
June | 77.00 | 25.69 | 464.17 | 24.62 | 67.33 | 24.78 |
July | 105.33 | 26.00 | 490.50 | 24.82 | 101.00 | 25.01 |
August | 93.17 | 26.01 | 513.33 | 24.68 | 93.17 | 24.86 |
September | 116.33 | 24.51 | 400.50 | 24.44 | 66.83 | 24.61 |
October | 297.33 | 22.23 | 178.67 | 22.84 | 43.83 | 22.82 |
November | 454.00 | 21.74 | 130.33 | 21.55 | 112.17 | 21.36 |
December | 492.50 | 20.56 | 291.83 | 20.28 | 291.17 | 20.15 |
Annual Sum or Average | 3215.17 | 21.97 | 3816.67 | 22.63 | 1489.67 | 22.46 |
Minimum of Months | 77.00 | 20.26 | 120.17 | 20.09 | 27.17 | 20.02 |
Maximum of Months | 502.00 | 26.01 | 513.33 | 24.82 | 384.33 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 448.17 | 20.87 | 261.00 | 20.53 | 256.50 | 20.34 |
February | 374.83 | 21.36 | 183.17 | 21.21 | 159.17 | 20.99 |
March | 307.17 | 22.21 | 163.17 | 22.61 | 47.50 | 22.43 |
April | 211.67 | 22.72 | 214.83 | 23.42 | 35.83 | 23.41 |
May | 120.67 | 23.58 | 368.00 | 24.12 | 36.67 | 24.19 |
June | 84.67 | 24.71 | 431.50 | 24.42 | 55.17 | 24.53 |
July | 107.17 | 25.61 | 490.67 | 24.68 | 102.83 | 24.83 |
August | 91.00 | 25.80 | 513.50 | 24.61 | 91.00 | 24.77 |
September | 117.83 | 24.45 | 403.50 | 24.43 | 64.33 | 24.60 |
October | 268.67 | 22.58 | 236.00 | 23.36 | 58.00 | 23.47 |
November | 350.83 | 22.12 | 147.33 | 22.31 | 80.33 | 22.17 |
December | 415.83 | 21.09 | 203.50 | 20.82 | 177.67 | 20.55 |
Annual Sum or Average | 2898.50 | 22.25 | 3616.17 | 22.96 | 1165.00 | 22.83 |
Minimum of Months | 84.67 | 20.87 | 147.33 | 20.53 | 35.83 | 20.34 |
Maximum of Months | 448.17 | 25.80 | 513.50 | 24.68 | 256.50 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.00 | 20.52 | 334.83 | 20.25 | 334.83 | 20.14 |
February | 423.00 | 21.20 | 184.17 | 20.92 | 176.00 | 20.72 |
March | 337.50 | 22.18 | 156.00 | 22.52 | 47.33 | 22.35 |
April | 201.67 | 23.11 | 250.17 | 23.75 | 38.33 | 23.81 |
May | 94.67 | 24.25 | 405.50 | 24.35 | 40.67 | 24.46 |
June | 71.00 | 25.58 | 454.67 | 24.60 | 56.83 | 24.75 |
July | 104.50 | 26.08 | 492.83 | 24.83 | 101.33 | 25.03 |
August | 88.67 | 26.33 | 514.00 | 24.75 | 88.67 | 24.95 |
September | 115.83 | 24.57 | 412.50 | 24.46 | 64.17 | 24.63 |
October | 318.83 | 22.43 | 174.17 | 23.07 | 42.83 | 23.16 |
November | 415.67 | 21.79 | 141.83 | 21.71 | 108.00 | 21.52 |
December | 483.17 | 20.89 | 259.17 | 20.60 | 248.00 | 20.43 |
Annual Sum or Average | 3152.50 | 22.09 | 3779.83 | 22.79 | 1347.00 | 22.64 |
Minimum of Months | 71.00 | 20.52 | 141.83 | 20.25 | 38.33 | 20.14 |
Maximum of Months | 498.00 | 26.33 | 514.00 | 24.83 | 334.83 | 25.03 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 492.67 | 27.00 | 0.00 | 27.00 |
February | 1.17 | 27.00 | 454.00 | 27.00 | 1.17 | 27.00 |
March | 13.67 | 27.00 | 514.00 | 27.00 | 13.67 | 27.00 |
April | 103.17 | 27.00 | 485.00 | 27.00 | 103.17 | 27.00 |
May | 1.17 | 27.00 | 508.00 | 27.00 | 1.17 | 27.00 |
June | 34.33 | 27.00 | 496.00 | 27.00 | 34.33 | 27.00 |
July | 179.17 | 27.00 | 497.00 | 27.00 | 179.17 | 27.00 |
August | 424.83 | 27.22 | 514.00 | 27.20 | 424.83 | 27.20 |
September | 5.83 | 27.00 | 485.00 | 27.00 | 5.83 | 27.00 |
October | 9.17 | 27.00 | 502.00 | 27.00 | 9.17 | 27.00 |
November | 10.67 | 27.00 | 489.00 | 27.00 | 10.67 | 27.00 |
December | 2.83 | 27.00 | 497.00 | 27.00 | 2.83 | 27.00 |
Annual Sum or Average | 786.00 | 27.12 | 5933.67 | 27.03 | 786.00 | 27.04 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 424.83 | 27.22 | 514.00 | 27.20 | 424.83 | 27.20 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.83 | 25.85 | 303.67 | 26.86 | 0.00 | 26.86 |
February | 0.00 | 0.00 | 382.50 | 27.00 | 0.00 | 27.00 |
March | 0.33 | 27.00 | 514.00 | 27.00 | 0.33 | 27.00 |
April | 2.33 | 27.00 | 485.00 | 27.00 | 2.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.17 | 27.00 | 496.00 | 27.00 | 0.17 | 27.00 |
July | 6.33 | 27.00 | 497.00 | 27.00 | 6.33 | 27.00 |
August | 119.00 | 27.58 | 514.00 | 27.23 | 119.00 | 27.29 |
September | 0.83 | 27.00 | 485.00 | 27.00 | 0.83 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 480.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 165.83 | 27.16 | 5656.33 | 27.02 | 129.00 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 303.67 | 26.86 | 0.00 | 26.86 |
Maximum of Months | 119.00 | 27.58 | 514.00 | 27.23 | 119.00 | 27.29 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 193.50 | 24.83 | 202.50 | 25.71 | 21.17 | 25.56 |
February | 27.00 | 26.95 | 328.83 | 27.00 | 0.00 | 27.00 |
March | 1.50 | 27.00 | 489.83 | 27.00 | 1.50 | 27.00 |
April | 7.83 | 27.00 | 485.00 | 27.00 | 7.83 | 27.00 |
May | 2.00 | 27.00 | 508.00 | 27.00 | 2.00 | 27.00 |
June | 10.50 | 27.00 | 496.00 | 27.00 | 10.50 | 27.00 |
July | 59.33 | 27.00 | 497.00 | 27.00 | 59.33 | 27.00 |
August | 136.00 | 27.43 | 514.00 | 27.18 | 136.00 | 27.23 |
September | 2.17 | 27.00 | 485.00 | 27.00 | 2.17 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 444.50 | 27.00 | 0.00 | 27.00 |
December | 9.67 | 27.00 | 368.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 449.50 | 26.19 | 5321.50 | 26.93 | 240.50 | 26.93 |
Minimum of Months | 0.00 | 0.00 | 202.50 | 25.71 | 0.00 | 25.56 |
Maximum of Months | 193.50 | 27.43 | 514.00 | 27.18 | 136.00 | 27.23 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.00 | 27.00 | 502.00 | 27.00 | 82.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.10 | 485.00 | 27.10 | 485.00 | 27.10 |
May | 471.50 | 27.00 | 508.00 | 27.00 | 471.50 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.54 | 514.00 | 28.54 | 514.00 | 28.54 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5486.50 | 27.15 | 5943.00 | 27.15 | 5486.50 | 27.15 |
Minimum of Months | 82.00 | 27.00 | 454.00 | 27.00 | 82.00 | 27.00 |
Maximum of Months | 514.00 | 28.54 | 514.00 | 28.54 | 514.00 | 28.54 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00007 | 21.68054 | 0.71591 | 15.99454 |
February | 454.00000 | 27.00011 | 24.13223 | 0.80201 | 18.74433 |
March | 514.00000 | 27.00018 | 28.90970 | 0.91619 | 22.82502 |
April | 485.00000 | 27.00032 | 32.47618 | 0.99502 | 25.96209 |
May | 508.00000 | 27.00068 | 36.60290 | 0.26390 | 6.50511 |
June | 496.00000 | 27.00143 | 37.44833 | 0.33710 | 7.40945 |
July | 497.00000 | 27.00103 | 37.91332 | 0.39241 | 8.24986 |
August | 514.00000 | 27.17837 | 37.76979 | 0.48910 | 10.22489 |
September | 485.00000 | 27.00061 | 38.51258 | 0.29155 | 6.82502 |
October | 502.00000 | 27.00064 | 33.61061 | 0.93497 | 23.50679 |
November | 489.00000 | 27.00016 | 27.38076 | 0.89966 | 22.18686 |
December | 497.00000 | 27.00004 | 24.80942 | 0.88544 | 21.65835 |
Annual Sum or Average | 5943.00000 | 27.01587 | 31.82669 | 0.65883 | 15.80388 |
Minimum of Months | 454.00000 | 27.00004 | 21.68054 | 0.26390 | 6.50511 |
Maximum of Months | 514.00000 | 27.17837 | 38.51258 | 0.99502 | 25.96209 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.85280 | 22.20527 | 0.55551 | 11.97434 |
February | 454.00000 | 27.00010 | 24.13616 | 0.66563 | 14.59392 |
March | 514.00000 | 27.00017 | 28.88074 | 0.80990 | 18.99887 |
April | 485.00000 | 27.00009 | 32.44362 | 0.89162 | 21.87431 |
May | 508.00000 | 27.00046 | 36.73260 | 0.20758 | 5.97262 |
June | 496.00000 | 27.00139 | 37.49541 | 0.26215 | 6.48867 |
July | 497.00000 | 27.00098 | 37.93738 | 0.29806 | 6.89575 |
August | 514.00000 | 27.15436 | 37.80643 | 0.35891 | 7.88785 |
September | 485.00000 | 27.00041 | 38.73550 | 0.22850 | 6.16104 |
October | 502.00000 | 27.00061 | 33.64806 | 0.84579 | 20.18072 |
November | 489.00000 | 27.00015 | 27.35513 | 0.76782 | 17.58315 |
December | 497.00000 | 27.00004 | 24.78627 | 0.69564 | 15.36016 |
Annual Sum or Average | 5943.00000 | 27.00128 | 31.90366 | 0.54762 | 12.80434 |
Minimum of Months | 454.00000 | 26.85280 | 22.20527 | 0.20758 | 5.97262 |
Maximum of Months | 514.00000 | 27.15436 | 38.73550 | 0.89162 | 21.87431 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.09338 | 22.81047 | 0.35003 | 9.99267 |
February | 454.00000 | 26.99719 | 24.16857 | 0.60920 | 13.21840 |
March | 514.00000 | 27.00018 | 28.90507 | 0.76838 | 17.75151 |
April | 485.00000 | 27.00010 | 32.46515 | 0.87095 | 21.20444 |
May | 508.00000 | 27.00054 | 36.73612 | 0.20713 | 6.06161 |
June | 496.00000 | 27.00144 | 37.49254 | 0.27597 | 6.70900 |
July | 497.00000 | 27.00104 | 37.94921 | 0.31598 | 7.18979 |
August | 514.00000 | 27.11820 | 37.84131 | 0.36745 | 8.06155 |
September | 485.00000 | 27.00041 | 38.78253 | 0.22248 | 6.18738 |
October | 502.00000 | 27.00061 | 33.71772 | 0.80683 | 18.92121 |
November | 489.00000 | 27.00016 | 27.38820 | 0.70154 | 15.64966 |
December | 497.00000 | 27.00005 | 24.80652 | 0.61856 | 13.34197 |
Annual Sum or Average | 5943.00000 | 26.93381 | 31.97932 | 0.50834 | 12.00283 |
Minimum of Months | 454.00000 | 26.09338 | 22.81047 | 0.20713 | 6.06161 |
Maximum of Months | 514.00000 | 27.11820 | 38.78253 | 0.87095 | 21.20444 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99994 | 31.09014 | 0.99967 | 26.14477 |
February | 454.00000 | 27.00021 | 29.58458 | 1.15888 | 33.30728 |
March | 514.00000 | 27.00256 | 29.50875 | 1.31623 | 41.14560 |
April | 485.00000 | 27.10333 | 31.85245 | 1.48665 | 50.18224 |
May | 508.00000 | 27.00107 | 41.45450 | 0.51357 | 10.67107 |
June | 496.00000 | 27.00216 | 36.88878 | 0.73046 | 16.25895 |
July | 497.00000 | 27.00104 | 37.66854 | 0.95278 | 24.18736 |
August | 514.00000 | 28.53784 | 36.60566 | 1.58264 | 55.24346 |
September | 485.00000 | 27.00234 | 39.34507 | 0.59021 | 12.34201 |
October | 502.00000 | 27.00096 | 35.21425 | 1.27928 | 39.23963 |
November | 489.00000 | 27.00229 | 29.88091 | 1.37063 | 43.98162 |
December | 497.00000 | 27.00286 | 25.63179 | 1.44524 | 47.95526 |
Annual Sum or Average | 5943.00000 | 27.14273 | 33.76368 | 1.11942 | 33.42755 |
Minimum of Months | 454.00000 | 26.99994 | 25.63179 | 0.51357 | 10.67107 |
Maximum of Months | 514.00000 | 28.53784 | 41.45450 | 1.58264 | 55.24346 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.24471 | 23.10787 | 0.27497 | 7.18994 |
February | 454.00000 | 24.32930 | 26.57590 | 0.32380 | 7.91017 |
March | 514.00000 | 24.34570 | 32.80482 | 0.38330 | 8.48127 |
April | 485.00000 | 24.41628 | 40.18465 | 0.45017 | 9.77364 |
May | 508.00000 | 24.42597 | 53.26165 | -0.3204 | 8.10994 |
June | 496.00000 | 24.41943 | 57.55980 | -0.2729 | 7.42318 |
July | 497.00000 | 24.56976 | 63.05971 | -0.1773 | 7.01418 |
August | 514.00000 | 24.46474 | 61.69412 | -0.2059 | 7.06031 |
September | 485.00000 | 24.53644 | 57.20569 | -0.2196 | 7.52770 |
October | 502.00000 | 24.56981 | 42.15264 | 0.52608 | 11.64222 |
November | 489.00000 | 24.56757 | 30.26559 | 0.43887 | 9.84501 |
December | 497.00000 | 24.51302 | 26.70415 | 0.38902 | 8.92654 |
Annual Sum or Average | 5943.00000 | 24.45047 | 43.01735 | 0.13022 | 8.40703 |
Minimum of Months | 454.00000 | 24.24471 | 23.10787 | -0.3204 | 7.01418 |
Maximum of Months | 514.00000 | 24.56981 | 63.05971 | 0.52608 | 11.64222 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.98198 | 28.34983 | 0.24186 | 7.07278 |
February | 454.00000 | 24.13914 | 28.73193 | 0.29998 | 7.31358 |
March | 514.00000 | 24.25587 | 33.42218 | 0.39162 | 8.55464 |
April | 485.00000 | 24.28441 | 40.39530 | 0.45975 | 9.75680 |
May | 508.00000 | 24.26806 | 51.76769 | -0.3446 | 7.94085 |
June | 496.00000 | 24.23851 | 53.04791 | -0.3236 | 7.50340 |
July | 497.00000 | 24.23835 | 56.64149 | -0.2866 | 6.93092 |
August | 514.00000 | 24.18704 | 56.16155 | -0.2913 | 6.94117 |
September | 485.00000 | 24.33109 | 54.53898 | -0.2936 | 7.36018 |
October | 502.00000 | 24.36000 | 43.07576 | 0.48763 | 10.42342 |
November | 489.00000 | 24.36690 | 31.86615 | 0.40572 | 8.87440 |
December | 497.00000 | 24.36176 | 29.33363 | 0.37287 | 8.41610 |
Annual Sum or Average | 5943.00000 | 24.25125 | 42.38786 | 0.09091 | 8.09233 |
Minimum of Months | 454.00000 | 23.98198 | 28.34983 | -0.3446 | 6.93092 |
Maximum of Months | 514.00000 | 24.36690 | 56.64149 | 0.48763 | 10.42342 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35610 | 31.81930 | -0.1715 | 6.80865 |
February | 454.00000 | 23.03967 | 31.98634 | 0.01420 | 6.37009 |
March | 514.00000 | 23.91867 | 35.27474 | 0.28368 | 7.13774 |
April | 485.00000 | 24.13604 | 41.72317 | 0.39343 | 8.60101 |
May | 508.00000 | 24.17009 | 52.47242 | -0.3991 | 8.65778 |
June | 496.00000 | 24.18803 | 53.79870 | -0.3684 | 8.16802 |
July | 497.00000 | 24.24521 | 57.46982 | -0.3225 | 7.45253 |
August | 514.00000 | 24.19709 | 57.36244 | -0.3347 | 7.56194 |
September | 485.00000 | 24.22443 | 55.35230 | -0.3564 | 8.02246 |
October | 502.00000 | 24.03406 | 45.06427 | 0.38447 | 8.39985 |
November | 489.00000 | 23.83530 | 34.38258 | 0.24431 | 6.71532 |
December | 497.00000 | 23.18069 | 32.92620 | 0.05311 | 5.83960 |
Annual Sum or Average | 5943.00000 | 23.79876 | 44.23599 | -0.0496 | 7.48514 |
Minimum of Months | 454.00000 | 22.35610 | 31.81930 | -0.3991 | 5.83960 |
Maximum of Months | 514.00000 | 24.24521 | 57.46982 | 0.39343 | 8.65778 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.05928 | 32.12509 | -0.5114 | 13.75786 |
February | 454.00000 | 21.93986 | 34.03650 | -0.2641 | 9.58518 |
March | 514.00000 | 23.30231 | 37.04016 | 0.12500 | 6.87489 |
April | 485.00000 | 23.84505 | 42.51920 | 0.31794 | 7.89279 |
May | 508.00000 | 24.13299 | 52.51313 | -0.4072 | 8.98645 |
June | 496.00000 | 24.22245 | 53.58441 | -0.3419 | 7.90422 |
July | 497.00000 | 24.30007 | 57.22690 | -0.2861 | 7.16506 |
August | 514.00000 | 24.24254 | 57.20435 | -0.3009 | 7.19308 |
September | 485.00000 | 24.16208 | 55.86799 | -0.3771 | 8.52317 |
October | 502.00000 | 23.44360 | 47.08640 | 0.23300 | 7.14693 |
November | 489.00000 | 22.71110 | 37.12522 | -0.0402 | 6.86423 |
December | 497.00000 | 21.63056 | 34.85932 | -0.3382 | 10.10754 |
Annual Sum or Average | 5943.00000 | 23.25926 | 45.18792 | -0.1826 | 8.49155 |
Minimum of Months | 454.00000 | 21.05928 | 32.12509 | -0.5114 | 6.86423 |
Maximum of Months | 514.00000 | 24.30007 | 57.22690 | 0.31794 | 13.75786 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.78854 | 27.89547 | -0.3139 | 9.20884 |
February | 454.00000 | 22.52979 | 29.33509 | -0.1110 | 7.84931 |
March | 514.00000 | 23.66367 | 33.87819 | 0.21844 | 6.99756 |
April | 485.00000 | 24.05026 | 40.29189 | 0.38429 | 8.86645 |
May | 508.00000 | 24.24631 | 51.04965 | -0.3440 | 8.37308 |
June | 496.00000 | 24.33754 | 52.14321 | -0.2461 | 7.02985 |
July | 497.00000 | 24.42701 | 55.75705 | -0.1762 | 6.61641 |
August | 514.00000 | 24.31789 | 55.36536 | -0.2052 | 6.60285 |
September | 485.00000 | 24.31162 | 54.52004 | -0.3012 | 7.91478 |
October | 502.00000 | 23.86151 | 44.02959 | 0.33942 | 8.23801 |
November | 489.00000 | 23.49386 | 33.14221 | 0.15865 | 6.76058 |
December | 497.00000 | 22.86333 | 30.20866 | -0.0237 | 6.51383 |
Annual Sum or Average | 5943.00000 | 23.66536 | 42.40404 | -0.0520 | 7.57587 |
Minimum of Months | 454.00000 | 21.78854 | 27.89547 | -0.3440 | 6.51383 |
Maximum of Months | 514.00000 | 24.42701 | 55.75705 | 0.38429 | 9.20884 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15064 | 27.56966 | -0.2264 | 8.32109 |
February | 454.00000 | 22.78995 | 28.97268 | -0.0379 | 7.63247 |
March | 514.00000 | 23.75305 | 33.54525 | 0.26267 | 7.58430 |
April | 485.00000 | 24.06267 | 40.02826 | 0.42202 | 9.67658 |
May | 508.00000 | 24.36048 | 50.41584 | -0.2454 | 8.00216 |
June | 496.00000 | 24.38243 | 51.80494 | -0.1750 | 6.90680 |
July | 497.00000 | 24.46452 | 55.37995 | -0.1116 | 6.90302 |
August | 514.00000 | 24.33069 | 55.16162 | -0.1613 | 6.77500 |
September | 485.00000 | 24.35807 | 54.07188 | -0.2339 | 7.74236 |
October | 502.00000 | 23.94475 | 43.46546 | 0.38515 | 9.35796 |
November | 489.00000 | 23.58442 | 32.87484 | 0.19071 | 7.12017 |
December | 497.00000 | 22.86648 | 30.28919 | -0.0168 | 6.51820 |
Annual Sum or Average | 5943.00000 | 23.76085 | 42.06747 | 0.00401 | 7.70854 |
Minimum of Months | 454.00000 | 22.15064 | 27.56966 | -0.2454 | 6.51820 |
Maximum of Months | 514.00000 | 24.46452 | 55.37995 | 0.42202 | 9.67658 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.53158 | 26.59666 | -0.1196 | 8.85800 |
February | 454.00000 | 23.04161 | 28.27370 | 0.03983 | 8.25529 |
March | 514.00000 | 23.88397 | 32.99773 | 0.31207 | 8.55959 |
April | 485.00000 | 24.10445 | 39.87877 | 0.42595 | 9.88686 |
May | 508.00000 | 24.25208 | 50.92484 | -0.3253 | 8.42046 |
June | 496.00000 | 24.32615 | 52.16056 | -0.2476 | 7.20987 |
July | 497.00000 | 24.43562 | 55.67363 | -0.1645 | 6.72602 |
August | 514.00000 | 24.35303 | 55.06459 | -0.1576 | 6.54683 |
September | 485.00000 | 24.38546 | 53.94776 | -0.2189 | 7.63468 |
October | 502.00000 | 24.06544 | 42.82482 | 0.44653 | 10.80020 |
November | 489.00000 | 23.86947 | 31.69411 | 0.29566 | 8.89571 |
December | 497.00000 | 23.22753 | 29.09395 | 0.10163 | 7.56593 |
Annual Sum or Average | 5943.00000 | 23.87861 | 41.70034 | 0.03151 | 8.27625 |
Minimum of Months | 454.00000 | 22.53158 | 26.59666 | -0.3253 | 6.54683 |
Maximum of Months | 514.00000 | 24.43562 | 55.67363 | 0.44653 | 10.80020 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.85226 | 26.05460 | -0.0472 | 7.27766 |
February | 454.00000 | 23.72295 | 26.85304 | 0.20475 | 7.94561 |
March | 514.00000 | 24.38093 | 31.71333 | 0.47979 | 10.78081 |
April | 485.00000 | 24.59346 | 38.41137 | 0.63790 | 14.74018 |
May | 508.00000 | 24.48807 | 49.89174 | -0.1552 | 7.11629 |
June | 496.00000 | 24.54370 | 51.08799 | -0.0436 | 6.75590 |
July | 497.00000 | 24.68177 | 54.39014 | 0.06049 | 7.28127 |
August | 514.00000 | 24.56560 | 53.94465 | 0.07290 | 7.05089 |
September | 485.00000 | 24.54862 | 53.23889 | -0.1168 | 7.21493 |
October | 502.00000 | 24.47101 | 41.62814 | 0.55379 | 12.46941 |
November | 489.00000 | 24.39669 | 30.46623 | 0.43648 | 10.11032 |
December | 497.00000 | 24.23266 | 26.99878 | 0.35148 | 8.37768 |
Annual Sum or Average | 5943.00000 | 24.29295 | 40.49798 | 0.20221 | 8.92252 |
Minimum of Months | 454.00000 | 22.85226 | 26.05460 | -0.1552 | 6.75590 |
Maximum of Months | 514.00000 | 24.68177 | 54.39014 | 0.63790 | 14.74018 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38554 | 30.56601 | -0.7117 | 18.47606 |
February | 454.00000 | 21.12182 | 31.74030 | -0.4880 | 13.32399 |
March | 514.00000 | 22.58755 | 36.40174 | -0.0485 | 7.35413 |
April | 485.00000 | 23.49388 | 42.31922 | 0.23186 | 7.79269 |
May | 508.00000 | 24.06073 | 52.16540 | -0.4228 | 9.83107 |
June | 496.00000 | 24.28984 | 53.38591 | -0.2799 | 7.54784 |
July | 497.00000 | 24.44072 | 57.73583 | -0.1918 | 6.90450 |
August | 514.00000 | 24.34311 | 57.75229 | -0.2257 | 6.85808 |
September | 485.00000 | 24.12652 | 56.19735 | -0.3810 | 9.24941 |
October | 502.00000 | 22.88276 | 47.51355 | 0.10058 | 7.03911 |
November | 489.00000 | 21.98881 | 36.76606 | -0.2107 | 8.10493 |
December | 497.00000 | 20.85061 | 33.07097 | -0.5372 | 13.70246 |
Annual Sum or Average | 5943.00000 | 22.89436 | 44.73679 | -0.2626 | 9.65356 |
Minimum of Months | 454.00000 | 20.38554 | 30.56601 | -0.7117 | 6.85808 |
Maximum of Months | 514.00000 | 24.44072 | 57.75229 | 0.23186 | 18.47606 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.63240 | 29.50199 | -0.6389 | 16.35037 |
February | 385.00000 | 21.62722 | 30.44613 | -0.3520 | 11.61387 |
March | 433.00000 | 23.17711 | 34.34162 | 0.10554 | 7.30466 |
April | 410.00000 | 23.90089 | 40.66203 | 0.36166 | 9.39455 |
May | 430.00000 | 24.34839 | 50.65792 | -0.2712 | 8.97496 |
June | 418.00000 | 24.48056 | 52.47532 | -0.1576 | 7.32787 |
July | 422.00000 | 24.65335 | 56.61302 | -0.0600 | 7.48614 |
August | 433.00000 | 24.52176 | 56.87383 | -0.1106 | 7.08994 |
September | 410.00000 | 24.34296 | 55.17968 | -0.2596 | 8.66333 |
October | 427.00000 | 23.39961 | 45.50042 | 0.24016 | 8.55117 |
November | 417.00000 | 22.58933 | 34.99231 | -0.0621 | 7.32311 |
December | 422.00000 | 21.19790 | 32.03363 | -0.4420 | 11.93673 |
Annual Sum or Average | 5034.00000 | 23.24859 | 43.35666 | -0.1363 | 9.31930 |
Minimum of Months | 385.00000 | 20.63240 | 29.50199 | -0.6389 | 7.08994 |
Maximum of Months | 433.00000 | 24.65335 | 56.87383 | 0.36166 | 16.35037 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79270 | 28.38371 | -0.3167 | 12.31912 |
February | 454.00000 | 22.35195 | 29.66253 | -0.1404 | 9.95219 |
March | 514.00000 | 23.45568 | 34.22754 | 0.20292 | 8.30940 |
April | 485.00000 | 23.82767 | 41.09007 | 0.34544 | 9.21167 |
May | 508.00000 | 24.11538 | 51.80237 | -0.3818 | 9.46346 |
June | 496.00000 | 24.28264 | 53.37767 | -0.2776 | 7.72194 |
July | 497.00000 | 24.45981 | 57.57806 | -0.1752 | 6.98591 |
August | 514.00000 | 24.39666 | 57.20402 | -0.1671 | 6.76067 |
September | 485.00000 | 24.29852 | 55.05341 | -0.2558 | 8.32698 |
October | 502.00000 | 23.71852 | 44.45186 | 0.36192 | 10.33701 |
November | 489.00000 | 23.36057 | 33.39631 | 0.16967 | 8.80265 |
December | 497.00000 | 22.31353 | 30.36910 | -0.1320 | 9.66124 |
Annual Sum or Average | 5943.00000 | 23.53966 | 43.15785 | -0.0640 | 8.97856 |
Minimum of Months | 454.00000 | 21.79270 | 28.38371 | -0.3818 | 6.76067 |
Maximum of Months | 514.00000 | 24.45981 | 57.57806 | 0.36192 | 12.31912 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.98121 | 29.64214 | -0.5391 | 14.35172 |
February | 454.00000 | 21.80416 | 30.51878 | -0.2977 | 10.89643 |
March | 514.00000 | 23.33908 | 34.57506 | 0.16418 | 7.97137 |
April | 485.00000 | 23.99285 | 40.77966 | 0.40352 | 10.04920 |
May | 508.00000 | 24.27710 | 51.15697 | -0.2767 | 8.24786 |
June | 496.00000 | 24.40848 | 52.69386 | -0.1638 | 7.12655 |
July | 497.00000 | 24.56046 | 56.92150 | -0.0760 | 7.09638 |
August | 514.00000 | 24.47876 | 56.68025 | -0.0923 | 6.87533 |
September | 485.00000 | 24.33199 | 55.08541 | -0.2438 | 8.16404 |
October | 502.00000 | 23.51582 | 45.42684 | 0.28012 | 8.74290 |
November | 489.00000 | 22.78086 | 34.88694 | -0.0049 | 7.71046 |
December | 497.00000 | 21.56440 | 31.81551 | -0.3454 | 10.50857 |
Annual Sum or Average | 5943.00000 | 23.34777 | 43.45042 | -0.0983 | 8.96010 |
Minimum of Months | 454.00000 | 20.98121 | 29.64214 | -0.5391 | 6.87533 |
Maximum of Months | 514.00000 | 24.56046 | 56.92150 | 0.40352 | 14.35172 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03982 | 31.33477 | -0.8396 | 23.54111 |
February | 454.00000 | 20.76803 | 32.56717 | -0.6108 | 16.48313 |
March | 514.00000 | 22.08260 | 37.32602 | -0.1852 | 9.15978 |
April | 485.00000 | 23.16388 | 43.03140 | 0.14861 | 7.98963 |
May | 508.00000 | 23.96220 | 52.46754 | -0.4505 | 11.13579 |
June | 496.00000 | 24.28299 | 53.49271 | -0.2678 | 7.83880 |
July | 497.00000 | 24.44912 | 57.93410 | -0.1705 | 7.10975 |
August | 514.00000 | 24.35824 | 58.00233 | -0.2024 | 6.88352 |
September | 485.00000 | 24.01280 | 56.97736 | -0.4160 | 10.65135 |
October | 502.00000 | 22.37968 | 49.03463 | -0.0321 | 7.81844 |
November | 489.00000 | 21.29164 | 38.20802 | -0.4063 | 11.52609 |
December | 497.00000 | 20.31761 | 34.50141 | -0.7102 | 19.39058 |
Annual Sum or Average | 5943.00000 | 22.60683 | 45.50631 | -0.3436 | 11.58757 |
Minimum of Months | 454.00000 | 20.03982 | 31.33477 | -0.8396 | 6.88352 |
Maximum of Months | 514.00000 | 24.44912 | 58.00233 | 0.14861 | 23.54111 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25701 | 31.05234 | -0.7584 | 20.63897 |
February | 454.00000 | 21.27906 | 31.73501 | -0.4618 | 13.98133 |
March | 514.00000 | 22.83717 | 35.71244 | 0.01547 | 7.90905 |
April | 485.00000 | 23.68427 | 41.39137 | 0.31622 | 9.26432 |
May | 508.00000 | 24.22524 | 51.17660 | -0.2860 | 9.35290 |
June | 496.00000 | 24.39662 | 52.66469 | -0.1476 | 7.28038 |
July | 497.00000 | 24.54453 | 56.88158 | -0.0558 | 7.47307 |
August | 514.00000 | 24.44281 | 57.05278 | -0.0970 | 6.93935 |
September | 485.00000 | 24.18400 | 55.78346 | -0.2911 | 9.53945 |
October | 502.00000 | 23.02494 | 46.91886 | 0.14461 | 8.61193 |
November | 489.00000 | 21.90041 | 37.02110 | -0.2456 | 9.28022 |
December | 497.00000 | 20.59391 | 34.04993 | -0.6176 | 17.04933 |
Annual Sum or Average | 5943.00000 | 22.96088 | 44.38432 | -0.2054 | 10.57907 |
Minimum of Months | 454.00000 | 20.25701 | 31.05234 | -0.7584 | 6.93935 |
Maximum of Months | 514.00000 | 24.54453 | 57.05278 | 0.31622 | 20.63897 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.23170 | 29.48872 | -0.4858 | 16.04025 |
February | 454.00000 | 21.89048 | 30.62459 | -0.2826 | 12.18385 |
March | 514.00000 | 23.04162 | 35.04756 | 0.08567 | 8.86726 |
April | 485.00000 | 23.54522 | 41.75049 | 0.27232 | 9.16257 |
May | 508.00000 | 24.01812 | 52.11054 | -0.4087 | 10.72719 |
June | 496.00000 | 24.26651 | 53.50682 | -0.2679 | 8.09162 |
July | 497.00000 | 24.45933 | 57.80718 | -0.1564 | 7.19524 |
August | 514.00000 | 24.40440 | 57.49112 | -0.1457 | 6.83231 |
September | 485.00000 | 24.19571 | 55.78267 | -0.2865 | 9.48375 |
October | 502.00000 | 23.31505 | 45.75624 | 0.25097 | 10.20667 |
November | 489.00000 | 22.72492 | 34.77317 | -0.0108 | 9.44788 |
December | 497.00000 | 21.59313 | 32.08916 | -0.3385 | 13.40956 |
Annual Sum or Average | 5943.00000 | 23.23411 | 43.95745 | -0.1473 | 10.12013 |
Minimum of Months | 454.00000 | 21.23170 | 29.48872 | -0.4858 | 6.83231 |
Maximum of Months | 514.00000 | 24.45933 | 57.80718 | 0.27232 | 16.04025 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54605 | 30.53103 | -0.6795 | 19.00532 |
February | 454.00000 | 21.41301 | 31.37296 | -0.4180 | 13.30985 |
March | 514.00000 | 22.89140 | 35.41417 | 0.04529 | 8.74817 |
April | 485.00000 | 23.72520 | 41.36885 | 0.33531 | 9.86861 |
May | 508.00000 | 24.18988 | 51.45029 | -0.3001 | 9.24782 |
June | 496.00000 | 24.39236 | 52.83644 | -0.1550 | 7.44983 |
July | 497.00000 | 24.55715 | 57.15518 | -0.0591 | 7.36105 |
August | 514.00000 | 24.48058 | 56.95969 | -0.0737 | 6.99675 |
September | 485.00000 | 24.23926 | 55.76674 | -0.2717 | 9.16379 |
October | 502.00000 | 23.06894 | 46.78382 | 0.16473 | 8.83397 |
November | 489.00000 | 22.15183 | 36.14941 | -0.1767 | 9.36365 |
December | 497.00000 | 20.97210 | 33.24948 | -0.5165 | 14.80930 |
Annual Sum or Average | 5943.00000 | 23.06504 | 44.18612 | -0.1739 | 10.32006 |
Minimum of Months | 454.00000 | 20.54605 | 30.53103 | -0.6795 | 6.99675 |
Maximum of Months | 514.00000 | 24.55715 | 57.15518 | 0.33531 | 19.00532 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.298597E+10 | 53110.40 | 31-JAN-15:10 | 70.90 | 0.136762E+11 | 0.00 | 0.166622E+11 | 0.43 | 5.89 | 31-JAN-15:10 | 0.00 | 0.00 |
February | 0.134091E+11 | 108335.21 | 28-FEB-15:05 | 130.35 | 0.763470E+11 | 0.00 | 0.897561E+11 | 0.96 | 7.81 | 28-FEB-15:05 | 0.00 | 0.00 |
March | 0.383044E+11 | 167263.14 | 29-MAR-15:30 | 273.55 | 0.236771E+12 | 0.00 | 0.275075E+12 | 1.97 | 7.91 | 30-MAR-16:10 | 0.00 | 0.00 |
April | 0.724017E+11 | 164605.54 | 19-APR-13:50 | 400.27 | 0.485434E+12 | 0.00 | 0.557836E+12 | 3.17 | 7.95 | 13-APR-16:10 | 0.00 | 0.00 |
May | 0.122605E+12 | 173453.96 | 31-MAY-12:30 | 462.00 | 0.851905E+12 | 0.00 | 0.974510E+12 | 3.98 | 7.95 | 27-MAY-05:04 | 0.00 | 0.00 |
June | 0.160404E+12 | 175983.13 | 28-JUN-11:30 | 531.30 | 0.113875E+13 | 0.00 | 0.129915E+13 | 4.90 | 7.95 | 08-JUN-15:00 | 0.00 | 0.00 |
July | 0.180038E+12 | 182090.98 | 07-JUL-11:50 | 641.11 | 0.126175E+13 | 0.00 | 0.144179E+13 | 5.49 | 7.92 | 24-JUL-04:13 | 0.00 | 0.00 |
August | 0.195942E+12 | 179382.27 | 22-AUG-12:00 | 679.55 | 0.137341E+13 | 0.00 | 0.156935E+13 | 5.81 | 7.93 | 25-AUG-05:05 | 0.00 | 0.00 |
September | 0.131851E+12 | 176562.95 | 08-SEP-11:10 | 461.03 | 0.928694E+12 | 0.00 | 0.106054E+13 | 4.18 | 7.95 | 14-SEP-14:00 | 0.00 | 0.00 |
October | 0.654403E+11 | 172473.55 | 18-OCT-12:50 | 297.97 | 0.437913E+12 | 0.00 | 0.503353E+12 | 2.38 | 7.91 | 17-OCT-05:04 | 0.00 | 0.00 |
November | 0.271933E+11 | 87953.40 | 08-NOV-15:40 | 231.98 | 0.156898E+12 | 0.00 | 0.184091E+12 | 1.65 | 7.50 | 08-NOV-15:40 | 0.00 | 0.00 |
December | 0.926421E+10 | 80441.28 | 12-DEC-13:10 | 174.52 | 0.494901E+11 | 0.00 | 0.587543E+11 | 1.10 | 7.31 | 12-DEC-13:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101984E+13 | 4354.53 | 0.701103E+13 | 0.00 | 0.803087E+13 | 3.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.298597E+10 | 53110.40 | 70.90 | 0.136762E+11 | 0.00 | 0.166622E+11 | 0.43 | 5.89 | 0.00 | 0.00 | ||
Maximum of Months | 0.195942E+12 | 182090.98 | 679.55 | 0.137341E+13 | 0.00 | 0.156935E+13 | 5.81 | 7.95 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.793710E+09 | 104799.93 | 30-MAR-14:47 | 2.78 | 0.586091E+10 | 0.00 | 0.665462E+10 | 0.03 | 7.73 | 30-MAR-14:47 | 0.00 | 0.00 |
April | 0.191529E+10 | 140664.91 | 17-APR-15:00 | 6.58 | 0.143901E+11 | 0.00 | 0.163054E+11 | 0.07 | 7.87 | 14-APR-15:40 | 0.00 | 0.00 |
May | 0.122874E+11 | 136708.26 | 19-MAY-14:50 | 36.86 | 0.904509E+11 | 0.00 | 0.102738E+12 | 0.36 | 7.79 | 15-MAY-14:50 | 0.00 | 0.00 |
June | 0.413629E+11 | 159603.33 | 30-JUN-05:04 | 119.52 | 0.295110E+12 | 0.00 | 0.336473E+12 | 1.18 | 7.85 | 20-JUN-05:03 | 0.00 | 0.00 |
July | 0.537969E+11 | 176391.11 | 27-JUL-05:04 | 151.88 | 0.382408E+12 | 0.00 | 0.436205E+12 | 1.45 | 7.53 | 19-JUL-05:06 | 0.00 | 0.00 |
August | 0.650326E+11 | 155214.80 | 21-AUG-05:05 | 180.05 | 0.459705E+12 | 0.00 | 0.524738E+12 | 1.71 | 7.69 | 25-AUG-13:50 | 0.00 | 0.00 |
September | 0.221041E+11 | 160381.25 | 07-SEP-05:04 | 64.01 | 0.159010E+12 | 0.00 | 0.181114E+12 | 0.64 | 7.86 | 14-SEP-15:13 | 0.00 | 0.00 |
October | 0.598383E+10 | 114104.55 | 18-OCT-12:05 | 17.50 | 0.437138E+11 | 0.00 | 0.496976E+11 | 0.17 | 7.53 | 19-OCT-14:50 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.203277E+12 | 579.19 | 0.145065E+13 | 0.00 | 0.165393E+13 | 0.47 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.650326E+11 | 176391.11 | 180.05 | 0.459705E+12 | 0.00 | 0.524738E+12 | 1.71 | 7.87 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.359549E+10 | 744.00 | 43776.24 | 19-JAN-14:40 | 51431.70 | 25-JAN-17:00 | 18.62 | 18.35 | 14.13 |
February | 0.158971E+11 | 672.00 | 43776.24 | 16-FEB-13:40 | 285248.97 | 28-FEB-15:00 | 19.77 | 18.67 | 14.14 |
March | 0.492660E+11 | 744.00 | 43776.24 | 03-MAR-12:40 | 522331.89 | 30-MAR-15:00 | 22.78 | 19.71 | 14.14 |
April | 0.848569E+11 | 720.00 | 43776.24 | 01-APR-13:00 | 644162.52 | 23-APR-18:03 | 30.01 | 22.53 | 14.15 |
May | 0.903542E+11 | 744.00 | 43776.24 | 01-MAY-00:05 | 328216.93 | 31-MAY-23:40 | 24.65 | 22.50 | 14.15 |
June | 0.107889E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 473242.71 | 30-JUN-24:00 | 33.98 | 27.71 | 14.15 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 630395.64 | 31-JUL-24:00 | 40.45 | 30.46 | 14.15 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 681100.13 | 11-AUG-16:40 | 45.07 | 32.24 | 14.15 |
September | 0.990962E+11 | 720.00 | 43776.24 | 01-SEP-00:05 | 246608.27 | 21-SEP-12:40 | 27.29 | 24.19 | 14.15 |
October | 0.550313E+11 | 744.00 | 43776.24 | 01-OCT-07:10 | 431420.39 | 17-OCT-10:50 | 23.04 | 20.47 | 14.14 |
November | 0.380618E+11 | 720.00 | 43776.24 | 01-NOV-11:40 | 516139.37 | 19-NOV-14:10 | 21.98 | 19.24 | 14.13 |
December | 0.216601E+11 | 744.00 | 43776.24 | 05-DEC-13:40 | 634387.24 | 13-DEC-11:00 | 21.47 | 18.63 | 14.14 |
Annual Sum or Average | 0.800209E+12 | 8760.00 | 27.48 | 22.92 | 14.14 | ||||
Minimum of Months | 0.359549E+10 | 672.00 | 43776.24 | 51431.70 | 18.62 | 18.35 | 14.13 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 681100.13 | 45.07 | 32.24 | 14.15 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 28548947.74 | 20.04 | 817.00 | 19-JAN-22:00 | 377340.06 | 31-JAN-15:10 | 20.97 | 20.95 | 2.57 |
February | 69761991.48 | 61.11 | 2029.66 | 28-FEB-15:00 | 957723.98 | 28-FEB-15:05 | 21.20 | 21.05 | 8.35 |
March | 0.126214E+10 | 161.58 | 17766.91 | 29-MAR-13:10 | 1266312.65 | 29-MAR-15:00 | 21.51 | 21.10 | 18.43 |
April | 0.420543E+10 | 281.80 | 17766.91 | 04-APR-08:50 | 1372159.55 | 18-APR-13:50 | 22.04 | 21.19 | 30.39 |
May | 0.147273E+11 | 437.14 | 17766.91 | 01-MAY-13:30 | 1289349.90 | 16-MAY-14:50 | 23.27 | 21.87 | 37.78 |
June | 0.257681E+11 | 518.64 | 17766.91 | 01-JUN-04:15 | 1330730.38 | 08-JUN-15:30 | 24.96 | 23.03 | 42.96 |
July | 0.363531E+11 | 636.24 | 17766.91 | 01-JUL-04:12 | 1241587.99 | 25-JUL-07:40 | 25.87 | 23.79 | 49.54 |
August | 0.414970E+11 | 676.55 | 17766.91 | 01-AUG-00:20 | 1215061.53 | 25-AUG-12:20 | 26.59 | 24.33 | 51.22 |
September | 0.205043E+11 | 444.18 | 17766.91 | 01-SEP-04:15 | 1414075.84 | 22-SEP-13:00 | 24.51 | 22.93 | 37.82 |
October | 0.607089E+10 | 246.98 | 17766.91 | 01-OCT-16:35 | 1383881.06 | 11-OCT-16:00 | 22.32 | 21.60 | 22.68 |
November | 0.409744E+09 | 131.54 | 3445.74 | 02-NOV-13:00 | 760987.84 | 08-NOV-15:40 | 21.35 | 21.06 | 15.41 |
December | 0.140382E+09 | 34.97 | 2825.40 | 12-DEC-14:00 | 664951.62 | 12-DEC-14:00 | 21.04 | 20.95 | 6.46 |
Annual Sum or Average | 0.151037E+12 | 3650.77 | 22.98 | 21.99 | 27.07 | ||||
Minimum of Months | 28548947.74 | 20.04 | 817.00 | 377340.06 | 20.97 | 20.95 | 2.57 | ||
Maximum of Months | 0.414970E+11 | 676.55 | 17766.91 | 1414075.84 | 26.59 | 24.33 | 51.22 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.97 | 20.97 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.20 | 21.20 | 0.00 |
March | 0.156349E+09 | 2.44 | 17766.91 | 29-MAR-15:10 | 999810.98 | 30-MAR-15:20 | 21.51 | 21.50 | 0.20 |
April | 0.346986E+09 | 6.44 | 17766.91 | 04-APR-13:00 | 1180710.51 | 13-APR-15:30 | 22.04 | 22.00 | 0.49 |
May | 0.339970E+10 | 53.15 | 17766.91 | 02-MAY-12:40 | 1085753.23 | 15-MAY-15:05 | 23.27 | 23.00 | 3.83 |
June | 0.122974E+11 | 192.26 | 17766.91 | 01-JUN-08:20 | 1089663.10 | 02-JUN-14:05 | 24.96 | 24.00 | 13.71 |
July | 0.167734E+11 | 262.24 | 17766.91 | 01-JUL-04:15 | 1132526.12 | 27-JUL-05:04 | 25.87 | 24.59 | 17.60 |
August | 0.210032E+11 | 328.38 | 17766.91 | 01-AUG-06:40 | 1061414.57 | 10-AUG-12:05 | 26.59 | 24.98 | 21.62 |
September | 0.700526E+10 | 109.67 | 17766.91 | 01-SEP-09:40 | 1178255.22 | 14-SEP-15:17 | 24.51 | 23.95 | 7.63 |
October | 0.225107E+10 | 35.19 | 17766.91 | 02-OCT-09:20 | 967750.38 | 11-OCT-13:05 | 22.32 | 22.14 | 2.23 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.35 | 21.35 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.04 | 21.04 | 0.00 |
Annual Sum or Average | 0.632333E+11 | 989.79 | 22.98 | 22.57 | 5.66 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 20.97 | 0.00 | ||
Maximum of Months | 0.210032E+11 | 328.38 | 17766.91 | 1180710.51 | 26.59 | 24.98 | 21.62 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.164608E+12 | 0.00 | 464.41 | 1478461.16 | 09-JAN-05:11 | 0.00 | 34.46 | 49.80 | 0.78 | 0.00 | 0.03 | 0.68 | 09-JAN-05:11 |
February | 0.856483E+11 | 0.00 | 312.97 | 1712946.31 | 02-FEB-05:11 | 0.00 | 31.99 | 44.11 | 0.43 | 0.00 | 0.02 | 0.79 | 02-FEB-05:11 |
March | 0.809858E+10 | 0.00 | 119.96 | 1134747.97 | 23-MAR-05:02 | 0.00 | 30.67 | 35.29 | 0.03 | 0.00 | 0.00 | 0.52 | 23-MAR-05:02 |
April | 0.342197E+10 | 0.00 | 50.21 | 850023.64 | 06-APR-05:03 | 0.00 | 37.00 | 38.67 | 0.01 | 0.00 | 0.00 | 0.39 | 06-APR-05:03 |
May | 0.169665E+10 | 0.00 | 32.47 | 141926.68 | 15-MAY-16:20 | 0.00 | 41.06 | 41.82 | 0.01 | 0.00 | 0.00 | 0.07 | 15-MAY-16:20 |
June | 0.395252E+09 | 0.00 | 12.11 | 55162.47 | 02-JUN-16:00 | 0.00 | 45.86 | 46.11 | 0.00 | 0.00 | 0.00 | 0.03 | 02-JUN-16:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 45.96 | 45.96 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.107712E+09 | 0.00 | 2.58 | 31685.60 | 25-AUG-13:50 | 0.00 | 45.34 | 45.40 | 0.00 | 0.00 | 0.00 | 0.01 | 25-AUG-13:50 |
September | 0.190760E+09 | 0.00 | 6.60 | 35104.15 | 23-SEP-12:00 | 0.00 | 43.42 | 43.57 | 0.00 | 0.00 | 0.00 | 0.02 | 23-SEP-12:00 |
October | 0.379138E+10 | 0.00 | 97.99 | 1090682.79 | 26-OCT-05:02 | 0.00 | 34.95 | 38.55 | 0.01 | 0.00 | 0.00 | 0.50 | 26-OCT-05:02 |
November | 0.196508E+11 | 0.00 | 185.89 | 1516868.76 | 25-NOV-05:01 | 0.00 | 31.13 | 38.34 | 0.08 | 0.00 | 0.00 | 0.70 | 25-NOV-05:01 |
December | 0.682669E+11 | 0.00 | 366.39 | 1560247.66 | 21-DEC-05:01 | 0.00 | 30.82 | 44.30 | 0.29 | 0.00 | 0.01 | 0.72 | 21-DEC-05:01 |
Annual Sum or Average | 0.355876E+12 | 0.00 | 1651.58 | 0.00 | 37.75 | 42.66 | 0.14 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 35.29 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.164608E+12 | 0.00 | 464.41 | 1712946.31 | 0.00 | 45.96 | 49.80 | 0.78 | 0.00 | 0.03 | 0.79 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.62 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.77 | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 22.78 | 22.78 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 30.01 | 30.01 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 24.65 | 24.65 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 33.98 | 33.98 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 40.45 | 40.45 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 45.07 | 45.07 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 27.29 | 27.29 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 23.04 | 23.04 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 21.98 | 21.98 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 21.47 | 21.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | 27.48 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 45.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.177040E+10 | 0.00 | 66.27 | 0.172847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34767.24 | 31-JAN-15:00 | 34767.24 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.897768E+10 | 0.00 | 123.82 | 0.897179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83418.85 | 28-FEB-15:00 | 83418.85 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.252309E+11 | 0.00 | 262.51 | 0.244720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122933.65 | 30-MAR-15:20 | 122933.65 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 |
April | 0.537518E+11 | 0.00 | 387.27 | 0.514581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149830.17 | 17-APR-15:45 | 149830.17 | 17-APR-15:45 | 0.00 | 0.00 | 0.00 |
May | 0.820911E+11 | 0.00 | 446.90 | 0.709306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180458.89 | 16-MAY-15:50 | 180458.89 | 16-MAY-15:50 | 0.00 | 0.00 | 0.00 |
June | 0.127065E+12 | 0.00 | 517.95 | 0.109086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 201985.15 | 20-JUN-05:03 | 144057.02 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.151134E+12 | 0.00 | 609.54 | 0.125159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 206231.25 | 27-JUL-05:02 | 142554.69 | 17-JUL-04:22 | 0.00 | 0.00 | 0.00 |
August | 0.176067E+12 | 0.00 | 657.22 | 0.145793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 204966.47 | 28-AUG-04:21 | 146136.07 | 28-AUG-04:21 | 0.00 | 0.00 | 0.00 |
September | 0.951072E+11 | 0.00 | 440.61 | 0.796075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206988.22 | 07-SEP-05:02 | 139739.07 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.453087E+11 | 0.00 | 282.74 | 0.380245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199635.10 | 18-OCT-04:12 | 128410.57 | 18-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.196559E+11 | 0.00 | 214.92 | 0.186653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103431.19 | 27-NOV-06:02 | 103431.19 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.146916E+11 | 0.00 | 171.63 | 0.138709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79554.79 | 13-DEC-05:12 | 68145.33 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.800851E+12 | 0.00 | 4181.37 | 0.687766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.177040E+10 | 0.00 | 66.27 | 0.172847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34767.24 | 34767.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.176067E+12 | 0.00 | 657.22 | 0.145793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 206988.22 | 180458.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.974773E+10 | 0.00 | 59.20 | 0.933905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232249.00 | 31-JAN-15:05 | 232249.00 | 31-JAN-15:05 | 0.00 | 0.00 | 0.00 |
February | 0.578968E+11 | 0.00 | 104.87 | 0.578968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 658277.12 | 28-FEB-15:05 | 658277.12 | 28-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.185210E+12 | 0.00 | 244.73 | 0.180874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1012255.95 | 30-MAR-15:20 | 1012255.95 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 |
April | 0.373903E+12 | 0.00 | 318.15 | 0.359343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1376321.17 | 17-APR-15:35 | 1376321.17 | 17-APR-15:35 | 0.00 | 0.00 | 0.00 |
May | 0.705895E+12 | 0.00 | 433.90 | 0.608790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1532741.25 | 19-MAY-14:50 | 1400998.86 | 19-MAY-14:43 | 0.00 | 0.00 | 0.00 |
June | 0.106729E+13 | 0.00 | 457.58 | 0.884672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2143801.63 | 30-JUN-05:02 | 1311788.55 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.120934E+13 | 0.00 | 478.86 | 0.947040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2224993.70 | 27-JUL-05:02 | 1282509.96 | 27-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.134036E+13 | 0.00 | 503.14 | 0.103446E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1876895.41 | 23-AUG-04:12 | 1344958.34 | 25-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.811188E+12 | 0.00 | 419.74 | 0.658593E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2125693.16 | 07-SEP-05:02 | 1336505.50 | 08-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.349259E+12 | 0.00 | 265.14 | 0.286219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1721083.66 | 19-OCT-05:03 | 966225.34 | 19-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.116707E+12 | 0.00 | 184.33 | 0.111993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 590257.09 | 05-NOV-15:23 | 536235.02 | 08-NOV-15:05 | 0.00 | 0.00 | 0.00 |
December | 0.278513E+11 | 0.00 | 101.97 | 0.242455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 456248.33 | 12-DEC-13:05 | 420101.72 | 12-DEC-14:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625464E+13 | 0.00 | 3571.61 | 0.516346E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.974773E+10 | 0.00 | 59.20 | 0.933905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232249.00 | 232249.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.134036E+13 | 0.00 | 503.14 | 0.103446E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2224993.70 | 1400998.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.926077E+09 | 0.00 | 54.54 | 0.884736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17554.46 | 31-JAN-15:00 | 17554.46 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.456796E+10 | 0.00 | 105.56 | 0.456796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59952.37 | 28-FEB-15:00 | 59952.37 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.161113E+11 | 0.00 | 234.22 | 0.158516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118076.60 | 30-MAR-15:40 | 118076.60 | 30-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.379637E+11 | 0.00 | 310.68 | 0.365535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155833.63 | 17-APR-15:40 | 155833.63 | 17-APR-15:40 | 0.00 | 0.00 | 0.00 |
May | 0.773518E+11 | 0.00 | 429.75 | 0.675525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165153.98 | 19-MAY-13:50 | 165153.98 | 19-MAY-13:50 | 0.00 | 0.00 | 0.00 |
June | 0.119450E+12 | 0.00 | 458.96 | 0.100650E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231332.04 | 30-JUN-05:02 | 142526.26 | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.135290E+12 | 0.00 | 485.53 | 0.108490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244038.36 | 27-JUL-05:02 | 136474.87 | 27-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.148153E+12 | 0.00 | 508.57 | 0.116998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 214164.68 | 04-AUG-03:02 | 152153.29 | 25-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.835506E+11 | 0.00 | 417.04 | 0.686736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 228120.46 | 07-SEP-05:02 | 137179.40 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.327042E+11 | 0.00 | 255.32 | 0.264639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170806.40 | 19-OCT-04:12 | 93796.69 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.850273E+10 | 0.00 | 182.65 | 0.807501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45144.50 | 02-NOV-14:30 | 45144.50 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.220957E+10 | 0.00 | 107.72 | 0.192702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32846.44 | 12-DEC-14:30 | 32846.44 | 12-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666781E+12 | 0.00 | 3550.54 | 0.556687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.926077E+09 | 0.00 | 54.54 | 0.884736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17554.46 | 17554.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.148153E+12 | 0.00 | 508.57 | 0.116998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244038.36 | 165153.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.430296E+09 | 0.00 | 16.66 | 0.420442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52464.89 | 20-JAN-06:03 | 24574.51 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.360632E+10 | 0.00 | 45.71 | 0.358573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65753.56 | 18-FEB-06:02 | 50572.93 | 28-FEB-14:10 | 0.00 | 0.00 | 0.00 |
March | 0.111018E+11 | 0.00 | 137.49 | 0.110274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88430.65 | 30-MAR-05:02 | 65064.82 | 30-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.236845E+11 | 0.00 | 223.35 | 0.233089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90960.45 | 03-APR-04:13 | 90960.45 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 |
May | 0.431506E+11 | 0.00 | 343.84 | 0.392682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99753.56 | 31-MAY-04:12 | 74854.88 | 19-MAY-12:40 | 0.00 | 0.00 | 0.00 |
June | 0.761541E+11 | 0.00 | 392.94 | 0.637484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133491.88 | 26-JUN-04:53 | 98869.03 | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.880511E+11 | 0.00 | 395.64 | 0.689857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137556.86 | 07-JUL-03:02 | 81464.00 | 05-JUL-04:33 | 0.00 | 0.00 | 0.00 |
August | 0.106873E+12 | 0.00 | 455.28 | 0.814883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159572.27 | 20-AUG-16:29 | 86188.88 | 14-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.654682E+11 | 0.00 | 369.41 | 0.547658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149781.99 | 04-SEP-08:53 | 85329.49 | 05-SEP-04:45 | 0.00 | 0.00 | 0.00 |
October | 0.292103E+11 | 0.00 | 217.82 | 0.243009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131622.90 | 18-OCT-04:53 | 93369.91 | 09-OCT-16:42 | 0.00 | 0.00 | 0.00 |
November | 0.945071E+10 | 0.00 | 117.42 | 0.880899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86400.94 | 27-NOV-06:02 | 86400.94 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.266609E+10 | 0.00 | 37.84 | 0.247327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83455.64 | 13-DEC-06:03 | 42792.23 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459847E+12 | 0.00 | 2753.39 | 0.382182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.430296E+09 | 0.00 | 16.66 | 0.420442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52464.89 | 24574.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.106873E+12 | 0.00 | 455.28 | 0.814883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159572.27 | 98869.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.596588E+10 | 0.363841E+10 | 685.51 | 0.596247E+10 | 3408888.06 | 0.00 | 0.03 | 29-JAN-16:00 | 0.01 | 20-JAN-13:50 | 4898.13 | 29-JAN-17:55 | 4898.13 | 29-JAN-17:55 | 28.28 | 20-JAN-17:00 | 2159.41 | 25-JAN-16:50 | 0.00 |
February | 0.214346E+11 | 0.807452E+10 | 584.48 | 0.212312E+11 | 0.203375E+09 | 0.00 | 0.51 | 26-FEB-15:00 | 0.01 | 01-FEB-20:40 | 170042.05 | 28-FEB-15:00 | 170042.05 | 28-FEB-15:00 | 6778.25 | 19-FEB-15:35 | 51375.49 | 26-FEB-15:00 | 0.00 |
March | 0.151165E+12 | 0.412285E+11 | 687.13 | 0.127029E+12 | 0.241360E+11 | 0.00 | 0.86 | 30-MAR-15:00 | 0.01 | 24-MAR-03:10 | 343212.73 | 30-MAR-11:30 | 329499.94 | 30-MAR-15:00 | 120162.15 | 31-MAR-11:00 | 97048.77 | 30-MAR-15:00 | 0.00 |
April | 0.533372E+12 | 0.137627E+12 | 715.94 | 0.457720E+12 | 0.756520E+11 | 0.00 | 1.00 | 04-APR-08:20 | 0.01 | 05-APR-04:40 | 429046.73 | 23-APR-10:40 | 398676.11 | 19-APR-11:00 | 219926.20 | 23-APR-10:37 | 117780.29 | 12-APR-14:00 | 0.00 |
May | 0.152078E+12 | 0.433744E+11 | 531.96 | 0.143124E+12 | 0.895470E+10 | 0.00 | 0.55 | 31-MAY-23:20 | 0.01 | 14-MAY-08:17 | 212065.30 | 31-MAY-23:10 | 210634.28 | 31-MAY-24:00 | 52660.49 | 26-MAY-13:00 | 53936.82 | 15-MAY-16:50 | 0.00 |
June | 0.493465E+12 | 0.140527E+12 | 705.58 | 0.481618E+12 | 0.118470E+11 | 0.00 | 0.85 | 10-JUN-16:00 | 0.01 | 07-JUN-04:57 | 303214.50 | 30-JUN-24:00 | 302653.73 | 30-JUN-24:00 | 56427.71 | 04-JUN-08:52 | 98716.50 | 10-JUN-16:00 | 0.00 |
July | 0.836442E+12 | 0.236275E+12 | 744.00 | 0.824279E+12 | 0.121631E+11 | 0.00 | 0.99 | 31-JUL-24:00 | 0.37 | 03-JUL-04:53 | 395984.47 | 31-JUL-24:00 | 395062.07 | 31-JUL-24:00 | 126925.83 | 03-JUL-07:10 | 116739.46 | 08-JUL-15:50 | 0.00 |
August | 0.107792E+13 | 0.301811E+12 | 744.00 | 0.106661E+13 | 0.113080E+11 | 0.00 | 1.00 | 01-AUG-07:10 | 0.37 | 31-AUG-24:00 | 420842.22 | 08-AUG-17:00 | 406303.89 | 07-AUG-21:04 | 19087.05 | 11-AUG-17:00 | 132630.38 | 01-AUG-16:10 | 0.00 |
September | 0.239406E+12 | 0.664772E+11 | 588.68 | 0.230717E+12 | 0.868910E+10 | 0.00 | 0.43 | 21-SEP-12:30 | 0.01 | 28-SEP-18:00 | 170422.68 | 21-SEP-12:30 | 137952.08 | 01-SEP-00:05 | 43001.41 | 21-SEP-12:30 | 46125.91 | 07-SEP-16:00 | 0.00 |
October | 0.152017E+12 | 0.412351E+11 | 520.68 | 0.142676E+12 | 0.934164E+10 | 0.00 | 0.73 | 17-OCT-10:50 | 0.00 | 06-OCT-03:30 | 311561.31 | 17-OCT-10:50 | 221540.04 | 10-OCT-16:00 | 119250.52 | 17-OCT-10:40 | 73653.18 | 17-OCT-10:50 | 0.00 |
November | 0.119887E+12 | 0.319532E+11 | 654.43 | 0.946052E+11 | 0.252820E+11 | 0.00 | 0.86 | 19-NOV-14:05 | 0.01 | 01-NOV-04:16 | 359915.35 | 19-NOV-14:05 | 309159.66 | 05-NOV-16:53 | 141003.25 | 05-NOV-12:00 | 86078.67 | 19-NOV-14:05 | 0.00 |
December | 0.935717E+11 | 0.252565E+11 | 720.40 | 0.714228E+11 | 0.221489E+11 | 0.00 | 1.00 | 13-DEC-10:50 | 0.01 | 23-DEC-18:30 | 425027.47 | 13-DEC-10:50 | 400237.68 | 13-DEC-11:00 | 202626.52 | 13-DEC-10:40 | 101763.04 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.387672E+13 | 0.107748E+13 | 7882.80 | 0.366699E+13 | 0.209729E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.596588E+10 | 0.363841E+10 | 520.68 | 0.596247E+10 | 3408888.06 | 0.00 | 0.03 | 0.00 | 4898.13 | 4898.13 | 28.28 | 2159.41 | 0.00 | ||||||
Maximum of Months | 0.107792E+13 | 0.301811E+12 | 744.00 | 0.106661E+13 | 0.756520E+11 | 0.00 | 1.00 | 0.37 | 429046.73 | 406303.89 | 219926.20 | 132630.38 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.361075E+10 | 0.851489E+09 | 744.00 | 0.359245E+10 | 18296832.73 | 0.00 | 0.30 | 15-JAN-17:35 | 0.05 | 09-JAN-07:05 | 2226.34 | 22-JAN-17:40 | 2226.34 | 22-JAN-17:40 | 212.71 | 19-JAN-17:00 | 511.74 | 15-JAN-17:35 | 0.00 |
February | 0.852063E+10 | 0.185777E+10 | 672.00 | 0.850046E+10 | 20165341.33 | 0.00 | 0.60 | 26-FEB-17:33 | 0.32 | 13-FEB-07:10 | 4612.05 | 20-FEB-17:45 | 4576.27 | 20-FEB-17:45 | 216.52 | 17-FEB-17:00 | 1208.43 | 26-FEB-17:25 | 0.00 |
March | 0.154228E+11 | 0.323945E+10 | 744.00 | 0.153548E+11 | 68002230.01 | 0.00 | 0.86 | 31-MAR-24:00 | 0.61 | 22-MAR-06:30 | 7643.94 | 31-MAR-24:00 | 7643.94 | 31-MAR-24:00 | 334.49 | 31-MAR-12:00 | 1803.13 | 30-MAR-16:00 | 0.00 |
April | 0.201002E+11 | 0.438565E+10 | 720.00 | 0.200047E+11 | 95442281.72 | 0.00 | 1.00 | 08-APR-17:42 | 0.31 | 30-APR-24:00 | 8527.21 | 09-APR-18:15 | 8527.21 | 09-APR-18:15 | 333.56 | 04-APR-10:00 | 2435.04 | 16-APR-14:00 | 0.00 |
May | 0.587519E+10 | 0.144497E+10 | 744.00 | 0.565284E+10 | 0.222354E+09 | 0.00 | 0.49 | 31-MAY-24:00 | 0.20 | 11-MAY-06:05 | 4008.70 | 31-MAY-24:00 | 3953.22 | 31-MAY-24:00 | 334.79 | 31-MAY-13:50 | 971.55 | 31-MAY-23:20 | 0.00 |
June | 0.110060E+11 | 0.296993E+10 | 720.00 | 0.106337E+11 | 0.372249E+09 | 0.00 | 0.71 | 30-JUN-24:00 | 0.44 | 10-JUN-06:50 | 5890.40 | 30-JUN-24:00 | 5867.96 | 30-JUN-24:00 | 483.65 | 26-JUN-16:20 | 1578.96 | 06-JUN-15:10 | 0.00 |
July | 0.165775E+11 | 0.459791E+10 | 744.00 | 0.160987E+11 | 0.478847E+09 | 0.00 | 0.93 | 31-JUL-24:00 | 0.68 | 29-JUL-06:10 | 7783.57 | 31-JUL-24:00 | 7761.58 | 31-JUL-24:00 | 549.09 | 26-JUL-10:10 | 2327.57 | 07-JUL-16:00 | 0.00 |
August | 0.216943E+11 | 0.604797E+10 | 744.00 | 0.211445E+11 | 0.549816E+09 | 0.00 | 1.00 | 01-AUG-10:00 | 0.31 | 31-AUG-24:00 | 8679.10 | 04-AUG-15:00 | 8362.74 | 20-AUG-17:17 | 660.56 | 11-AUG-17:00 | 2745.30 | 01-AUG-16:10 | 0.00 |
September | 0.590744E+10 | 0.151649E+10 | 720.00 | 0.559953E+10 | 0.307907E+09 | 0.00 | 0.45 | 30-SEP-24:00 | 0.21 | 29-SEP-06:30 | 3750.58 | 30-SEP-24:00 | 3748.14 | 30-SEP-24:00 | 411.21 | 06-SEP-14:30 | 912.37 | 07-SEP-16:00 | 0.00 |
October | 0.106176E+11 | 0.233964E+10 | 744.00 | 0.104691E+11 | 0.148520E+09 | 0.00 | 0.67 | 31-OCT-24:00 | 0.40 | 26-OCT-07:00 | 5635.55 | 31-OCT-24:00 | 5635.55 | 31-OCT-24:00 | 503.16 | 18-OCT-16:00 | 1404.81 | 10-OCT-16:00 | 0.00 |
November | 0.148338E+11 | 0.308601E+10 | 720.00 | 0.147762E+11 | 57646010.62 | 0.00 | 0.81 | 19-NOV-17:00 | 0.61 | 30-NOV-22:00 | 6476.58 | 11-NOV-17:05 | 6476.58 | 11-NOV-17:05 | 285.00 | 27-NOV-17:10 | 1728.42 | 19-NOV-15:02 | 0.00 |
December | 0.200002E+11 | 0.397537E+10 | 744.00 | 0.199668E+11 | 33439837.43 | 0.00 | 1.00 | 10-DEC-16:42 | 0.77 | 01-DEC-07:10 | 8220.18 | 10-DEC-17:00 | 8220.18 | 10-DEC-17:00 | 336.68 | 13-DEC-17:10 | 1995.44 | 12-DEC-14:05 | 0.00 |
Annual Sum or Average | 0.154166E+12 | 0.363126E+11 | 8760.00 | 0.151794E+12 | 0.237268E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.361075E+10 | 0.851489E+09 | 672.00 | 0.359245E+10 | 18296832.73 | 0.00 | 0.30 | 0.05 | 2226.34 | 2226.34 | 212.71 | 511.74 | 0.00 | ||||||
Maximum of Months | 0.216943E+11 | 0.604797E+10 | 744.00 | 0.211445E+11 | 0.549816E+09 | 0.00 | 1.00 | 0.77 | 8679.10 | 8527.21 | 660.56 | 2745.30 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.108971E+11 | 0.277190E+10 | 548.66 | 0.107408E+11 | 0.156299E+09 | 0.00 | 0.23 | 20-JAN-17:00 | 0.00 | 01-JAN-00:05 | 17222.17 | 20-JAN-17:00 | 16266.36 | 20-JAN-17:00 | 1997.38 | 19-JAN-16:30 | 4061.83 | 25-JAN-16:50 | 0.00 |
February | 0.636318E+11 | 0.141777E+11 | 672.00 | 0.634344E+11 | 0.197356E+09 | 0.00 | 0.57 | 26-FEB-17:42 | 0.15 | 13-FEB-07:10 | 39967.59 | 26-FEB-17:57 | 39967.59 | 26-FEB-17:57 | 2123.72 | 17-FEB-17:00 | 10825.05 | 26-FEB-17:33 | 0.00 |
March | 0.138704E+12 | 0.293855E+11 | 744.00 | 0.138026E+12 | 0.677881E+09 | 0.00 | 0.85 | 31-MAR-23:40 | 0.53 | 22-MAR-06:30 | 71659.69 | 31-MAR-23:40 | 71659.69 | 31-MAR-23:40 | 3285.32 | 31-MAR-12:00 | 17193.21 | 30-MAR-16:00 | 0.00 |
April | 0.188067E+12 | 0.412116E+11 | 720.00 | 0.187114E+12 | 0.953433E+09 | 0.00 | 1.00 | 08-APR-18:12 | 0.26 | 30-APR-24:00 | 79292.24 | 09-APR-18:30 | 79292.24 | 09-APR-18:30 | 3338.51 | 04-APR-10:00 | 22904.79 | 17-APR-16:00 | 0.00 |
May | 0.532189E+11 | 0.131785E+11 | 744.00 | 0.510312E+11 | 0.218761E+10 | 0.00 | 0.49 | 31-MAY-23:30 | 0.17 | 11-MAY-06:15 | 38033.36 | 31-MAY-23:20 | 37393.14 | 31-MAY-24:00 | 3321.97 | 31-MAY-13:50 | 9224.93 | 31-MAY-23:20 | 0.00 |
June | 0.103795E+12 | 0.280699E+11 | 720.00 | 0.100098E+12 | 0.369716E+10 | 0.00 | 0.71 | 30-JUN-24:00 | 0.41 | 10-JUN-06:50 | 56035.94 | 30-JUN-24:00 | 55808.59 | 30-JUN-24:00 | 4800.60 | 26-JUN-16:20 | 15064.23 | 06-JUN-15:10 | 0.00 |
July | 0.157886E+12 | 0.438220E+11 | 744.00 | 0.153113E+12 | 0.477224E+10 | 0.00 | 0.93 | 31-JUL-24:00 | 0.65 | 29-JUL-06:10 | 74922.85 | 31-JUL-24:00 | 74708.64 | 31-JUL-24:00 | 5487.22 | 26-JUL-10:10 | 22305.82 | 07-JUL-16:00 | 0.00 |
August | 0.206312E+12 | 0.575792E+11 | 744.00 | 0.200814E+12 | 0.549837E+10 | 0.00 | 1.00 | 01-AUG-09:40 | 0.27 | 31-AUG-24:00 | 82862.10 | 04-AUG-15:00 | 78802.29 | 27-AUG-19:03 | 6520.01 | 11-AUG-17:00 | 26249.92 | 01-AUG-16:10 | 0.00 |
September | 0.531350E+11 | 0.137363E+11 | 720.00 | 0.501162E+11 | 0.301874E+10 | 0.00 | 0.41 | 30-SEP-24:00 | 0.17 | 29-SEP-07:00 | 32636.02 | 30-SEP-24:00 | 32551.29 | 30-SEP-24:00 | 4084.61 | 06-SEP-14:30 | 8660.15 | 07-SEP-16:00 | 0.00 |
October | 0.929785E+11 | 0.207159E+11 | 744.00 | 0.915105E+11 | 0.146796E+10 | 0.00 | 0.62 | 31-OCT-23:40 | 0.32 | 31-OCT-07:00 | 49212.90 | 31-OCT-23:40 | 49212.90 | 31-OCT-23:40 | 4998.77 | 18-OCT-16:00 | 13238.11 | 10-OCT-16:00 | 0.00 |
November | 0.128927E+12 | 0.271429E+11 | 720.00 | 0.128356E+12 | 0.571312E+09 | 0.00 | 0.77 | 19-NOV-17:03 | 0.51 | 22-NOV-07:10 | 58754.91 | 11-NOV-17:05 | 58754.91 | 11-NOV-17:05 | 2816.14 | 27-NOV-17:10 | 15482.50 | 19-NOV-17:00 | 0.00 |
December | 0.168935E+12 | 0.341648E+11 | 744.00 | 0.168601E+12 | 0.334592E+09 | 0.00 | 0.92 | 10-DEC-16:42 | 0.64 | 26-DEC-07:30 | 75186.52 | 11-DEC-17:00 | 73189.00 | 11-DEC-17:00 | 3344.25 | 13-DEC-17:10 | 18659.56 | 12-DEC-14:20 | 0.00 |
Annual Sum or Average | 0.136649E+13 | 0.325956E+12 | 8564.66 | 0.134295E+13 | 0.235330E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.108971E+11 | 0.277190E+10 | 548.66 | 0.107408E+11 | 0.156299E+09 | 0.00 | 0.23 | 0.00 | 17222.17 | 16266.36 | 1997.38 | 4061.83 | 0.00 | ||||||
Maximum of Months | 0.206312E+12 | 0.575792E+11 | 744.00 | 0.200814E+12 | 0.549837E+10 | 0.00 | 1.00 | 0.65 | 82862.10 | 79292.24 | 6520.01 | 26249.92 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.469789E+09 | 0.117617E+09 | 239.61 | 0.455245E+09 | 14543016.37 | 0.00 | 0.23 | 20-JAN-17:00 | 0.00 | 01-JAN-00:05 | 1801.10 | 20-JAN-17:00 | 1702.15 | 20-JAN-17:00 | 212.46 | 19-JAN-15:50 | 387.98 | 20-JAN-17:00 | 0.00 |
February | 0.514697E+10 | 0.116186E+10 | 659.91 | 0.512755E+10 | 19415939.07 | 0.00 | 0.53 | 26-FEB-17:42 | 0.00 | 05-FEB-20:45 | 3951.13 | 28-FEB-17:00 | 3951.13 | 28-FEB-17:00 | 211.78 | 17-FEB-17:00 | 1050.88 | 28-FEB-15:00 | 0.00 |
March | 0.130652E+11 | 0.279536E+10 | 744.00 | 0.129979E+11 | 67316222.06 | 0.00 | 0.81 | 31-MAR-23:20 | 0.44 | 23-MAR-06:10 | 6939.00 | 31-MAR-23:20 | 6939.00 | 31-MAR-23:20 | 329.18 | 31-MAR-12:00 | 1747.62 | 30-MAR-16:00 | 0.00 |
April | 0.184322E+11 | 0.406795E+10 | 720.00 | 0.183372E+11 | 94959891.17 | 0.00 | 0.99 | 08-APR-18:12 | 0.25 | 30-APR-24:00 | 7979.96 | 09-APR-18:25 | 7979.96 | 09-APR-18:25 | 334.36 | 04-APR-10:00 | 2320.40 | 17-APR-16:00 | 0.00 |
May | 0.525881E+10 | 0.131173E+10 | 744.00 | 0.503978E+10 | 0.219029E+09 | 0.00 | 0.48 | 31-MAY-23:20 | 0.10 | 11-MAY-06:35 | 3769.45 | 31-MAY-23:10 | 3695.13 | 31-MAY-24:00 | 337.16 | 31-MAY-13:40 | 916.36 | 31-MAY-23:20 | 0.00 |
June | 0.104606E+11 | 0.283769E+10 | 720.00 | 0.100906E+11 | 0.370018E+09 | 0.00 | 0.69 | 30-JUN-24:00 | 0.37 | 08-JUN-06:25 | 5579.40 | 30-JUN-24:00 | 5556.28 | 30-JUN-24:00 | 481.94 | 26-JUN-16:20 | 1538.84 | 06-JUN-15:10 | 0.00 |
July | 0.159156E+11 | 0.442757E+10 | 744.00 | 0.154385E+11 | 0.477064E+09 | 0.00 | 0.92 | 31-JUL-24:00 | 0.62 | 29-JUL-06:10 | 7526.36 | 31-JUL-24:00 | 7504.74 | 31-JUL-24:00 | 549.04 | 26-JUL-10:10 | 2270.97 | 07-JUL-16:00 | 0.00 |
August | 0.207737E+11 | 0.581270E+10 | 744.00 | 0.202233E+11 | 0.550345E+09 | 0.00 | 1.00 | 01-AUG-10:20 | 0.26 | 31-AUG-24:00 | 8372.45 | 04-AUG-14:50 | 8145.40 | 20-AUG-17:15 | 631.92 | 11-AUG-17:00 | 2674.64 | 01-AUG-16:10 | 0.00 |
September | 0.520740E+10 | 0.135682E+10 | 720.00 | 0.490629E+10 | 0.301105E+09 | 0.00 | 0.38 | 07-SEP-16:00 | 0.10 | 29-SEP-07:00 | 2832.22 | 30-SEP-23:30 | 2807.00 | 30-SEP-24:00 | 412.96 | 06-SEP-14:30 | 896.08 | 07-SEP-16:00 | 0.00 |
October | 0.854925E+10 | 0.192984E+10 | 744.00 | 0.840345E+10 | 0.145799E+09 | 0.00 | 0.58 | 10-OCT-16:00 | 0.22 | 30-OCT-06:10 | 4445.69 | 31-OCT-23:20 | 4445.69 | 31-OCT-23:20 | 500.58 | 18-OCT-16:00 | 1347.52 | 10-OCT-16:00 | 0.00 |
November | 0.116130E+11 | 0.247796E+10 | 720.00 | 0.115565E+11 | 56486159.45 | 0.00 | 0.73 | 08-NOV-17:00 | 0.38 | 22-NOV-07:10 | 5795.32 | 02-NOV-16:00 | 5754.76 | 06-NOV-17:00 | 280.70 | 27-NOV-17:10 | 1488.54 | 05-NOV-16:00 | 0.00 |
December | 0.151025E+11 | 0.310282E+10 | 744.00 | 0.150693E+11 | 33163179.94 | 0.00 | 0.89 | 12-DEC-15:05 | 0.48 | 18-DEC-04:07 | 7488.04 | 13-DEC-16:00 | 7242.53 | 12-DEC-15:30 | 333.97 | 13-DEC-17:10 | 1856.33 | 12-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.129995E+12 | 0.313999E+11 | 8243.52 | 0.127646E+12 | 0.234924E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.469789E+09 | 0.117617E+09 | 239.61 | 0.455245E+09 | 14543016.37 | 0.00 | 0.23 | 0.00 | 1801.10 | 1702.15 | 211.78 | 387.98 | 0.00 | ||||||
Maximum of Months | 0.207737E+11 | 0.581270E+10 | 744.00 | 0.202233E+11 | 0.550345E+09 | 0.00 | 1.00 | 0.62 | 8372.45 | 8145.40 | 631.92 | 2674.64 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.34 | 0.00 | 98.34 | 9.68 | 716.90 | 0.00 | 0.00 | 0.00 |
February | 109.00 | 0.00 | 109.00 | 37.98 | 592.68 | 0.00 | 0.00 | 0.00 |
March | 153.04 | 0.00 | 153.04 | 94.56 | 375.98 | 0.00 | 0.00 | 0.00 |
April | 185.11 | 0.82 | 184.29 | 195.14 | 286.71 | 0.00 | 0.00 | 0.00 |
May | 221.39 | 7.07 | 214.33 | 308.42 | 176.23 | 0.00 | 0.00 | 0.00 |
June | 243.65 | 16.09 | 227.56 | 440.27 | 108.18 | 0.00 | 0.00 | 0.00 |
July | 229.88 | 11.17 | 218.71 | 439.50 | 76.03 | 0.00 | 0.00 | 0.00 |
August | 204.44 | 2.23 | 202.22 | 399.66 | 63.11 | 0.00 | 0.00 | 0.00 |
September | 154.54 | 0.02 | 154.52 | 228.36 | 154.46 | 0.00 | 0.00 | 0.00 |
October | 117.50 | 0.00 | 117.50 | 95.48 | 343.22 | 0.00 | 0.00 | 0.00 |
November | 105.16 | 0.00 | 105.16 | 41.94 | 478.99 | 0.00 | 0.00 | 0.00 |
December | 90.91 | 0.00 | 90.91 | 8.38 | 623.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.69 | 3.13 | 156.56 | 192.50 | 331.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.91 | 0.00 | 90.91 | 8.38 | 63.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 243.65 | 16.09 | 227.56 | 440.27 | 716.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.34 | 0.00 | 98.34 | 9.68 | 716.90 | 0.00 | 0.00 | 0.00 |
February | 109.00 | 0.00 | 109.00 | 37.98 | 592.68 | 0.00 | 0.00 | 0.00 |
March | 153.04 | 0.00 | 153.04 | 94.56 | 375.98 | 0.00 | 0.00 | 0.00 |
April | 185.11 | 0.82 | 184.29 | 195.14 | 286.71 | 0.00 | 0.00 | 0.00 |
May | 221.39 | 7.07 | 214.33 | 308.42 | 176.23 | 0.00 | 0.00 | 0.00 |
June | 243.65 | 16.09 | 227.56 | 440.27 | 108.18 | 0.00 | 0.00 | 0.00 |
July | 229.88 | 11.17 | 218.71 | 439.50 | 76.03 | 0.00 | 0.00 | 0.00 |
August | 204.44 | 2.23 | 202.22 | 399.66 | 63.11 | 0.00 | 0.00 | 0.00 |
September | 154.54 | 0.02 | 154.52 | 228.36 | 154.46 | 0.00 | 0.00 | 0.00 |
October | 117.50 | 0.00 | 117.50 | 95.48 | 343.22 | 0.00 | 0.00 | 0.00 |
November | 105.16 | 0.00 | 105.16 | 41.94 | 478.99 | 0.00 | 0.00 | 0.00 |
December | 90.91 | 0.00 | 90.91 | 8.38 | 623.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.69 | 3.13 | 156.56 | 192.50 | 331.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.91 | 0.00 | 90.91 | 8.38 | 63.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 243.65 | 16.09 | 227.56 | 440.27 | 716.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.34 | 0.00 | 98.34 | 9.68 | 716.90 | 0.00 | 0.00 | 0.00 |
February | 109.00 | 0.00 | 109.00 | 37.98 | 592.68 | 0.00 | 0.00 | 0.00 |
March | 153.04 | 0.00 | 153.04 | 94.56 | 375.98 | 0.00 | 0.00 | 0.00 |
April | 185.11 | 0.82 | 184.29 | 195.14 | 286.71 | 0.00 | 0.00 | 0.00 |
May | 221.39 | 7.07 | 214.33 | 308.42 | 176.23 | 0.00 | 0.00 | 0.00 |
June | 243.65 | 16.09 | 227.56 | 440.27 | 108.18 | 0.00 | 0.00 | 0.00 |
July | 229.88 | 11.17 | 218.71 | 439.50 | 76.03 | 0.00 | 0.00 | 0.00 |
August | 204.44 | 2.23 | 202.22 | 399.66 | 63.11 | 0.00 | 0.00 | 0.00 |
September | 154.54 | 0.02 | 154.52 | 228.36 | 154.46 | 0.00 | 0.00 | 0.00 |
October | 117.50 | 0.00 | 117.50 | 95.48 | 343.22 | 0.00 | 0.00 | 0.00 |
November | 105.16 | 0.00 | 105.16 | 41.94 | 478.99 | 0.00 | 0.00 | 0.00 |
December | 90.91 | 0.00 | 90.91 | 8.38 | 623.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.69 | 3.13 | 156.56 | 192.50 | 331.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.91 | 0.00 | 90.91 | 8.38 | 63.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 243.65 | 16.09 | 227.56 | 440.27 | 716.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.34 | 0.00 | 98.34 | 9.68 | 716.90 | 0.00 | 0.00 | 0.00 |
February | 109.00 | 0.00 | 109.00 | 37.98 | 592.68 | 0.00 | 0.00 | 0.00 |
March | 153.04 | 0.00 | 153.04 | 94.56 | 375.98 | 0.00 | 0.00 | 0.00 |
April | 185.11 | 0.82 | 184.29 | 195.14 | 286.71 | 0.00 | 0.00 | 0.00 |
May | 221.39 | 7.07 | 214.33 | 308.42 | 176.23 | 0.00 | 0.00 | 0.00 |
June | 243.65 | 16.09 | 227.56 | 440.27 | 108.18 | 0.00 | 0.00 | 0.00 |
July | 229.88 | 11.17 | 218.71 | 439.50 | 76.03 | 0.00 | 0.00 | 0.00 |
August | 204.44 | 2.23 | 202.22 | 399.66 | 63.11 | 0.00 | 0.00 | 0.00 |
September | 154.54 | 0.02 | 154.52 | 228.36 | 154.46 | 0.00 | 0.00 | 0.00 |
October | 117.50 | 0.00 | 117.50 | 95.48 | 343.22 | 0.00 | 0.00 | 0.00 |
November | 105.16 | 0.00 | 105.16 | 41.94 | 478.99 | 0.00 | 0.00 | 0.00 |
December | 90.91 | 0.00 | 90.91 | 8.38 | 623.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.69 | 3.13 | 156.56 | 192.50 | 331.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.91 | 0.00 | 90.91 | 8.38 | 63.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 243.65 | 16.09 | 227.56 | 440.27 | 716.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.34 | 0.00 | 98.34 | 9.68 | 716.87 | 0.00 | 0.00 | 0.00 |
February | 109.00 | 0.00 | 109.00 | 37.98 | 592.66 | 0.00 | 0.00 | 0.00 |
March | 153.03 | 0.00 | 153.03 | 94.56 | 375.97 | 0.00 | 0.00 | 0.00 |
April | 185.10 | 0.82 | 184.28 | 195.13 | 286.70 | 0.00 | 0.00 | 0.00 |
May | 221.38 | 7.07 | 214.32 | 308.41 | 176.22 | 0.00 | 0.00 | 0.00 |
June | 243.64 | 16.09 | 227.55 | 440.25 | 108.18 | 0.00 | 0.00 | 0.00 |
July | 229.88 | 11.17 | 218.70 | 439.48 | 76.03 | 0.00 | 0.00 | 0.00 |
August | 204.44 | 2.23 | 202.21 | 399.64 | 63.11 | 0.00 | 0.00 | 0.00 |
September | 154.53 | 0.02 | 154.51 | 228.35 | 154.45 | 0.00 | 0.00 | 0.00 |
October | 117.50 | 0.00 | 117.50 | 95.48 | 343.20 | 0.00 | 0.00 | 0.00 |
November | 105.16 | 0.00 | 105.16 | 41.94 | 478.97 | 0.00 | 0.00 | 0.00 |
December | 90.91 | 0.00 | 90.91 | 8.38 | 623.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.68 | 3.13 | 156.55 | 192.49 | 331.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.91 | 0.00 | 90.91 | 8.38 | 63.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 243.64 | 16.09 | 227.55 | 440.25 | 716.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.97 | 108.24 | 131.73 | 156.45 | 713.43 | 0.00 | 0.00 | 0.00 |
February | 302.53 | 162.55 | 139.98 | 281.96 | 587.08 | 0.00 | 0.00 | 0.00 |
March | 380.61 | 173.27 | 207.35 | 424.39 | 374.17 | 0.00 | 0.00 | 0.00 |
April | 460.26 | 209.87 | 250.39 | 632.60 | 290.04 | 0.00 | 0.00 | 0.00 |
May | 505.40 | 213.73 | 291.67 | 775.38 | 192.23 | 0.00 | 0.00 | 0.00 |
June | 523.26 | 219.31 | 303.95 | 914.61 | 117.85 | 0.00 | 0.00 | 0.00 |
July | 510.20 | 214.50 | 295.70 | 921.78 | 81.14 | 0.00 | 0.00 | 0.00 |
August | 466.66 | 185.14 | 281.52 | 858.70 | 63.88 | 0.00 | 0.00 | 0.00 |
September | 383.53 | 169.93 | 213.60 | 610.17 | 163.92 | 0.00 | 0.00 | 0.00 |
October | 327.19 | 170.24 | 156.94 | 413.67 | 346.64 | 0.00 | 0.00 | 0.00 |
November | 261.59 | 118.45 | 143.14 | 243.98 | 468.08 | 0.00 | 0.00 | 0.00 |
December | 226.59 | 103.29 | 123.30 | 156.93 | 602.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 382.70 | 170.68 | 212.02 | 533.87 | 332.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.59 | 103.29 | 123.30 | 156.45 | 63.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 523.26 | 219.31 | 303.95 | 921.78 | 713.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.97 | 108.24 | 131.73 | 156.45 | 713.43 | 0.00 | 0.00 | 0.00 |
February | 302.53 | 162.55 | 139.98 | 281.96 | 587.08 | 0.00 | 0.00 | 0.00 |
March | 380.61 | 173.27 | 207.35 | 424.39 | 374.17 | 0.00 | 0.00 | 0.00 |
April | 460.26 | 209.87 | 250.39 | 632.60 | 290.04 | 0.00 | 0.00 | 0.00 |
May | 505.40 | 213.73 | 291.67 | 775.38 | 192.23 | 0.00 | 0.00 | 0.00 |
June | 523.26 | 219.31 | 303.95 | 914.61 | 117.85 | 0.00 | 0.00 | 0.00 |
July | 510.20 | 214.50 | 295.70 | 921.78 | 81.14 | 0.00 | 0.00 | 0.00 |
August | 466.66 | 185.14 | 281.52 | 858.70 | 63.88 | 0.00 | 0.00 | 0.00 |
September | 383.53 | 169.93 | 213.60 | 610.17 | 163.92 | 0.00 | 0.00 | 0.00 |
October | 327.19 | 170.24 | 156.94 | 413.67 | 346.64 | 0.00 | 0.00 | 0.00 |
November | 261.59 | 118.45 | 143.14 | 243.98 | 468.08 | 0.00 | 0.00 | 0.00 |
December | 226.59 | 103.29 | 123.30 | 156.93 | 602.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 382.70 | 170.68 | 212.02 | 533.87 | 332.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.59 | 103.29 | 123.30 | 156.45 | 63.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 523.26 | 219.31 | 303.95 | 921.78 | 713.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.97 | 108.24 | 131.73 | 156.45 | 713.41 | 0.00 | 0.00 | 0.00 |
February | 302.52 | 162.54 | 139.98 | 281.95 | 587.07 | 0.00 | 0.00 | 0.00 |
March | 380.61 | 173.26 | 207.34 | 424.38 | 374.17 | 0.00 | 0.00 | 0.00 |
April | 460.25 | 209.86 | 250.39 | 632.59 | 290.03 | 0.00 | 0.00 | 0.00 |
May | 505.39 | 213.72 | 291.67 | 775.36 | 192.23 | 0.00 | 0.00 | 0.00 |
June | 523.25 | 219.31 | 303.94 | 914.59 | 117.84 | 0.00 | 0.00 | 0.00 |
July | 510.19 | 214.49 | 295.70 | 921.76 | 81.14 | 0.00 | 0.00 | 0.00 |
August | 466.66 | 185.14 | 281.52 | 858.68 | 63.88 | 0.00 | 0.00 | 0.00 |
September | 383.53 | 169.93 | 213.60 | 610.16 | 163.91 | 0.00 | 0.00 | 0.00 |
October | 327.18 | 170.24 | 156.94 | 413.66 | 346.63 | 0.00 | 0.00 | 0.00 |
November | 261.58 | 118.44 | 143.14 | 243.97 | 468.08 | 0.00 | 0.00 | 0.00 |
December | 226.58 | 103.29 | 123.30 | 156.93 | 602.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 382.69 | 170.68 | 212.02 | 533.86 | 332.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.58 | 103.29 | 123.30 | 156.45 | 63.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 523.25 | 219.31 | 303.94 | 921.76 | 713.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 525.96 | 366.69 | 159.26 | 590.66 | 580.64 | 0.00 | 0.00 | 0.00 |
February | 490.89 | 329.06 | 161.83 | 601.64 | 504.67 | 0.00 | 0.00 | 0.00 |
March | 441.48 | 230.07 | 211.41 | 589.05 | 352.12 | 0.00 | 0.00 | 0.00 |
April | 330.64 | 107.63 | 223.01 | 489.53 | 289.09 | 0.00 | 0.00 | 0.00 |
May | 267.14 | 31.05 | 236.09 | 420.65 | 186.21 | 0.00 | 0.00 | 0.00 |
June | 247.00 | 13.74 | 233.26 | 461.38 | 115.73 | 0.00 | 0.00 | 0.00 |
July | 249.71 | 18.62 | 231.09 | 489.52 | 79.88 | 0.00 | 0.00 | 0.00 |
August | 298.14 | 55.69 | 242.45 | 595.78 | 67.07 | 0.00 | 0.00 | 0.00 |
September | 327.88 | 121.95 | 205.93 | 559.85 | 156.74 | 0.00 | 0.00 | 0.00 |
October | 475.33 | 307.92 | 167.41 | 699.76 | 320.32 | 0.00 | 0.00 | 0.00 |
November | 511.37 | 339.34 | 172.03 | 671.31 | 420.03 | 0.00 | 0.00 | 0.00 |
December | 518.45 | 364.73 | 153.72 | 618.49 | 511.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.90 | 189.90 | 200.01 | 565.56 | 297.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.00 | 13.74 | 153.72 | 420.65 | 67.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.96 | 366.69 | 242.45 | 699.76 | 580.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 525.95 | 366.69 | 159.26 | 590.66 | 580.64 | 0.00 | 0.00 | 0.00 |
February | 490.89 | 329.06 | 161.83 | 601.64 | 504.67 | 0.00 | 0.00 | 0.00 |
March | 441.48 | 230.07 | 211.41 | 589.05 | 352.12 | 0.00 | 0.00 | 0.00 |
April | 330.64 | 107.63 | 223.01 | 489.53 | 289.09 | 0.00 | 0.00 | 0.00 |
May | 267.14 | 31.05 | 236.09 | 420.65 | 186.21 | 0.00 | 0.00 | 0.00 |
June | 247.00 | 13.74 | 233.26 | 461.38 | 115.73 | 0.00 | 0.00 | 0.00 |
July | 249.71 | 18.62 | 231.09 | 489.52 | 79.88 | 0.00 | 0.00 | 0.00 |
August | 298.14 | 55.69 | 242.45 | 595.78 | 67.07 | 0.00 | 0.00 | 0.00 |
September | 327.88 | 121.95 | 205.93 | 559.85 | 156.74 | 0.00 | 0.00 | 0.00 |
October | 475.33 | 307.92 | 167.41 | 699.75 | 320.32 | 0.00 | 0.00 | 0.00 |
November | 511.37 | 339.34 | 172.03 | 671.31 | 420.03 | 0.00 | 0.00 | 0.00 |
December | 518.45 | 364.73 | 153.72 | 618.49 | 511.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.90 | 189.90 | 200.01 | 565.56 | 297.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.00 | 13.74 | 153.72 | 420.65 | 67.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.95 | 366.69 | 242.45 | 699.75 | 580.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 525.96 | 366.69 | 159.26 | 590.66 | 580.64 | 0.00 | 0.00 | 0.00 |
February | 490.89 | 329.06 | 161.83 | 601.64 | 504.67 | 0.00 | 0.00 | 0.00 |
March | 441.48 | 230.07 | 211.41 | 589.05 | 352.12 | 0.00 | 0.00 | 0.00 |
April | 330.64 | 107.63 | 223.01 | 489.53 | 289.09 | 0.00 | 0.00 | 0.00 |
May | 267.14 | 31.05 | 236.09 | 420.65 | 186.21 | 0.00 | 0.00 | 0.00 |
June | 247.00 | 13.74 | 233.26 | 461.38 | 115.73 | 0.00 | 0.00 | 0.00 |
July | 249.71 | 18.62 | 231.09 | 489.52 | 79.88 | 0.00 | 0.00 | 0.00 |
August | 298.14 | 55.69 | 242.45 | 595.78 | 67.07 | 0.00 | 0.00 | 0.00 |
September | 327.88 | 121.95 | 205.93 | 559.85 | 156.74 | 0.00 | 0.00 | 0.00 |
October | 475.33 | 307.92 | 167.41 | 699.76 | 320.32 | 0.00 | 0.00 | 0.00 |
November | 511.37 | 339.34 | 172.03 | 671.31 | 420.03 | 0.00 | 0.00 | 0.00 |
December | 518.45 | 364.73 | 153.72 | 618.49 | 511.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.90 | 189.90 | 200.01 | 565.56 | 297.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.00 | 13.74 | 153.72 | 420.65 | 67.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.96 | 366.69 | 242.45 | 699.76 | 580.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 525.95 | 366.69 | 159.26 | 590.66 | 580.64 | 0.00 | 0.00 | 0.00 |
February | 490.89 | 329.06 | 161.83 | 601.64 | 504.67 | 0.00 | 0.00 | 0.00 |
March | 441.48 | 230.07 | 211.41 | 589.05 | 352.12 | 0.00 | 0.00 | 0.00 |
April | 330.64 | 107.63 | 223.01 | 489.53 | 289.09 | 0.00 | 0.00 | 0.00 |
May | 267.14 | 31.05 | 236.09 | 420.65 | 186.21 | 0.00 | 0.00 | 0.00 |
June | 247.00 | 13.74 | 233.26 | 461.38 | 115.73 | 0.00 | 0.00 | 0.00 |
July | 249.71 | 18.62 | 231.09 | 489.52 | 79.88 | 0.00 | 0.00 | 0.00 |
August | 298.14 | 55.69 | 242.45 | 595.78 | 67.07 | 0.00 | 0.00 | 0.00 |
September | 327.88 | 121.95 | 205.93 | 559.85 | 156.74 | 0.00 | 0.00 | 0.00 |
October | 475.33 | 307.92 | 167.41 | 699.75 | 320.32 | 0.00 | 0.00 | 0.00 |
November | 511.37 | 339.34 | 172.03 | 671.31 | 420.03 | 0.00 | 0.00 | 0.00 |
December | 518.45 | 364.73 | 153.72 | 618.49 | 511.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.90 | 189.90 | 200.01 | 565.56 | 297.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.00 | 13.74 | 153.72 | 420.65 | 67.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.95 | 366.69 | 242.45 | 699.75 | 580.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 525.93 | 366.68 | 159.25 | 590.64 | 580.62 | 0.00 | 0.00 | 0.00 |
February | 490.87 | 329.05 | 161.83 | 601.61 | 504.65 | 0.00 | 0.00 | 0.00 |
March | 441.46 | 230.06 | 211.40 | 589.03 | 352.11 | 0.00 | 0.00 | 0.00 |
April | 330.62 | 107.63 | 223.00 | 489.51 | 289.08 | 0.00 | 0.00 | 0.00 |
May | 267.13 | 31.05 | 236.08 | 420.63 | 186.20 | 0.00 | 0.00 | 0.00 |
June | 246.99 | 13.74 | 233.25 | 461.36 | 115.73 | 0.00 | 0.00 | 0.00 |
July | 249.70 | 18.62 | 231.08 | 489.50 | 79.88 | 0.00 | 0.00 | 0.00 |
August | 298.13 | 55.69 | 242.44 | 595.75 | 67.07 | 0.00 | 0.00 | 0.00 |
September | 327.87 | 121.95 | 205.92 | 559.83 | 156.73 | 0.00 | 0.00 | 0.00 |
October | 475.31 | 307.91 | 167.40 | 699.73 | 320.31 | 0.00 | 0.00 | 0.00 |
November | 511.35 | 339.32 | 172.03 | 671.28 | 420.02 | 0.00 | 0.00 | 0.00 |
December | 518.43 | 364.72 | 153.71 | 618.47 | 511.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.89 | 189.89 | 200.00 | 565.54 | 297.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.99 | 13.74 | 153.71 | 420.63 | 67.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.93 | 366.68 | 242.44 | 699.73 | 580.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.48 | 114.34 | 132.15 | 177.87 | 783.30 | 0.00 | 0.00 | 0.00 |
February | 282.96 | 132.30 | 150.66 | 269.25 | 684.48 | 0.00 | 0.00 | 0.00 |
March | 417.07 | 201.54 | 215.53 | 492.54 | 462.20 | 0.00 | 0.00 | 0.00 |
April | 469.19 | 214.70 | 254.49 | 640.07 | 374.25 | 0.00 | 0.00 | 0.00 |
May | 471.55 | 178.65 | 292.90 | 725.50 | 231.15 | 0.00 | 0.00 | 0.00 |
June | 495.90 | 190.77 | 305.13 | 859.65 | 157.61 | 0.00 | 0.00 | 0.00 |
July | 467.75 | 173.42 | 294.32 | 833.18 | 120.33 | 0.00 | 0.00 | 0.00 |
August | 458.33 | 171.40 | 286.93 | 821.61 | 112.08 | 0.00 | 0.00 | 0.00 |
September | 373.41 | 155.54 | 217.87 | 588.74 | 197.20 | 0.00 | 0.00 | 0.00 |
October | 332.66 | 172.69 | 159.97 | 435.22 | 421.22 | 0.00 | 0.00 | 0.00 |
November | 265.49 | 119.17 | 146.32 | 271.60 | 576.20 | 0.00 | 0.00 | 0.00 |
December | 219.03 | 95.80 | 123.22 | 163.69 | 742.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.46 | 160.14 | 215.31 | 524.60 | 403.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.03 | 95.80 | 123.22 | 163.69 | 112.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 495.90 | 214.70 | 305.13 | 859.65 | 783.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.48 | 114.34 | 132.15 | 177.87 | 783.30 | 0.00 | 0.00 | 0.00 |
February | 282.96 | 132.30 | 150.66 | 269.25 | 684.48 | 0.00 | 0.00 | 0.00 |
March | 417.07 | 201.54 | 215.53 | 492.54 | 462.20 | 0.00 | 0.00 | 0.00 |
April | 469.19 | 214.70 | 254.49 | 640.07 | 374.25 | 0.00 | 0.00 | 0.00 |
May | 471.55 | 178.65 | 292.90 | 725.50 | 231.15 | 0.00 | 0.00 | 0.00 |
June | 495.90 | 190.77 | 305.13 | 859.65 | 157.61 | 0.00 | 0.00 | 0.00 |
July | 467.75 | 173.42 | 294.32 | 833.18 | 120.33 | 0.00 | 0.00 | 0.00 |
August | 458.33 | 171.40 | 286.93 | 821.61 | 112.08 | 0.00 | 0.00 | 0.00 |
September | 373.41 | 155.54 | 217.87 | 588.74 | 197.20 | 0.00 | 0.00 | 0.00 |
October | 332.66 | 172.69 | 159.97 | 435.22 | 421.22 | 0.00 | 0.00 | 0.00 |
November | 265.49 | 119.17 | 146.32 | 271.60 | 576.20 | 0.00 | 0.00 | 0.00 |
December | 219.03 | 95.80 | 123.22 | 163.69 | 742.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.46 | 160.14 | 215.31 | 524.60 | 403.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.03 | 95.80 | 123.22 | 163.69 | 112.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 495.90 | 214.70 | 305.13 | 859.65 | 783.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.48 | 114.33 | 132.14 | 177.87 | 783.29 | 0.00 | 0.00 | 0.00 |
February | 282.96 | 132.30 | 150.66 | 269.25 | 684.46 | 0.00 | 0.00 | 0.00 |
March | 417.06 | 201.53 | 215.53 | 492.53 | 462.19 | 0.00 | 0.00 | 0.00 |
April | 469.19 | 214.70 | 254.49 | 640.06 | 374.25 | 0.00 | 0.00 | 0.00 |
May | 471.55 | 178.65 | 292.90 | 725.49 | 231.15 | 0.00 | 0.00 | 0.00 |
June | 495.89 | 190.77 | 305.12 | 859.63 | 157.61 | 0.00 | 0.00 | 0.00 |
July | 467.74 | 173.42 | 294.32 | 833.16 | 120.32 | 0.00 | 0.00 | 0.00 |
August | 458.32 | 171.39 | 286.92 | 821.60 | 112.08 | 0.00 | 0.00 | 0.00 |
September | 373.40 | 155.54 | 217.86 | 588.73 | 197.19 | 0.00 | 0.00 | 0.00 |
October | 332.66 | 172.69 | 159.97 | 435.21 | 421.21 | 0.00 | 0.00 | 0.00 |
November | 265.49 | 119.16 | 146.32 | 271.59 | 576.19 | 0.00 | 0.00 | 0.00 |
December | 219.02 | 95.80 | 123.22 | 163.69 | 742.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.45 | 160.14 | 215.31 | 524.59 | 403.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.02 | 95.80 | 123.22 | 163.69 | 112.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 495.89 | 214.70 | 305.12 | 859.63 | 783.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.71 | 0.00 | 491.71 | 75.46 | 3136.11 | 0.00 | 0.00 | 0.00 |
February | 545.02 | 0.00 | 545.02 | 239.60 | 2590.94 | 0.00 | 0.00 | 0.00 |
March | 765.17 | 0.00 | 765.17 | 532.13 | 1659.40 | 0.00 | 0.00 | 0.00 |
April | 925.55 | 4.11 | 921.44 | 1020.45 | 1316.83 | 0.00 | 0.00 | 0.00 |
May | 1106.94 | 35.33 | 1071.61 | 1555.11 | 842.87 | 0.00 | 0.00 | 0.00 |
June | 1218.24 | 80.43 | 1137.80 | 2213.54 | 525.88 | 0.00 | 0.00 | 0.00 |
July | 1149.41 | 55.87 | 1093.53 | 2209.25 | 378.94 | 0.00 | 0.00 | 0.00 |
August | 1022.21 | 11.14 | 1011.07 | 2021.54 | 307.42 | 0.00 | 0.00 | 0.00 |
September | 772.69 | 0.11 | 772.59 | 1160.19 | 721.11 | 0.00 | 0.00 | 0.00 |
October | 587.50 | 0.00 | 587.50 | 529.26 | 1514.28 | 0.00 | 0.00 | 0.00 |
November | 525.80 | 0.00 | 525.80 | 279.00 | 2070.37 | 0.00 | 0.00 | 0.00 |
December | 454.55 | 0.00 | 454.55 | 79.90 | 2585.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 798.44 | 15.65 | 782.79 | 997.22 | 1465.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 454.55 | 0.00 | 454.55 | 75.46 | 307.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1218.24 | 80.43 | 1137.80 | 2213.54 | 3136.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 719.90 | 324.71 | 395.19 | 505.31 | 1890.86 | 0.00 | 0.00 | 0.00 |
February | 907.57 | 487.63 | 419.94 | 871.08 | 1585.13 | 0.00 | 0.00 | 0.00 |
March | 1141.83 | 519.79 | 622.04 | 1273.34 | 1050.43 | 0.00 | 0.00 | 0.00 |
April | 1380.77 | 629.59 | 751.17 | 1881.21 | 848.63 | 0.00 | 0.00 | 0.00 |
May | 1516.19 | 641.17 | 875.01 | 2298.41 | 569.59 | 0.00 | 0.00 | 0.00 |
June | 1569.76 | 657.93 | 911.84 | 2715.31 | 361.38 | 0.00 | 0.00 | 0.00 |
July | 1530.58 | 643.48 | 887.10 | 2733.55 | 263.97 | 0.00 | 0.00 | 0.00 |
August | 1399.98 | 555.42 | 844.56 | 2547.52 | 214.79 | 0.00 | 0.00 | 0.00 |
September | 1150.59 | 509.80 | 640.79 | 1813.64 | 479.23 | 0.00 | 0.00 | 0.00 |
October | 981.55 | 510.73 | 470.83 | 1241.97 | 964.98 | 0.00 | 0.00 | 0.00 |
November | 784.76 | 355.34 | 429.42 | 759.29 | 1278.57 | 0.00 | 0.00 | 0.00 |
December | 679.75 | 309.86 | 369.90 | 507.04 | 1571.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1148.09 | 512.04 | 636.05 | 1599.44 | 919.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 679.75 | 309.86 | 369.90 | 505.31 | 214.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1569.76 | 657.93 | 911.84 | 2733.55 | 1890.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2629.75 | 1833.45 | 796.30 | 2963.32 | 2736.80 | 0.00 | 0.00 | 0.00 |
February | 2454.43 | 1645.27 | 809.16 | 3008.89 | 2375.51 | 0.00 | 0.00 | 0.00 |
March | 2207.36 | 1150.35 | 1057.02 | 2931.02 | 1676.00 | 0.00 | 0.00 | 0.00 |
April | 1653.17 | 538.14 | 1115.03 | 2444.48 | 1385.12 | 0.00 | 0.00 | 0.00 |
May | 1335.69 | 155.24 | 1180.45 | 2099.20 | 904.44 | 0.00 | 0.00 | 0.00 |
June | 1234.99 | 68.72 | 1166.27 | 2314.22 | 563.83 | 0.00 | 0.00 | 0.00 |
July | 1248.55 | 93.10 | 1155.45 | 2454.79 | 398.40 | 0.00 | 0.00 | 0.00 |
August | 1490.68 | 278.46 | 1212.22 | 2985.16 | 332.43 | 0.00 | 0.00 | 0.00 |
September | 1639.38 | 609.76 | 1029.62 | 2787.35 | 760.56 | 0.00 | 0.00 | 0.00 |
October | 2376.63 | 1539.59 | 837.05 | 3479.13 | 1531.11 | 0.00 | 0.00 | 0.00 |
November | 2556.83 | 1696.67 | 860.16 | 3351.33 | 1996.12 | 0.00 | 0.00 | 0.00 |
December | 2592.20 | 1823.63 | 768.57 | 3109.48 | 2363.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1949.48 | 949.47 | 1000.02 | 2827.00 | 1413.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1234.99 | 68.72 | 768.57 | 2099.20 | 332.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2629.75 | 1833.45 | 1212.22 | 3479.13 | 2736.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 739.44 | 343.00 | 396.44 | 577.48 | 2024.91 | 0.00 | 0.00 | 0.00 |
February | 848.87 | 396.90 | 451.97 | 858.19 | 1728.74 | 0.00 | 0.00 | 0.00 |
March | 1251.19 | 604.60 | 646.59 | 1522.45 | 1175.14 | 0.00 | 0.00 | 0.00 |
April | 1407.57 | 644.10 | 763.47 | 1971.36 | 960.44 | 0.00 | 0.00 | 0.00 |
May | 1414.65 | 535.95 | 878.69 | 2187.55 | 641.22 | 0.00 | 0.00 | 0.00 |
June | 1487.69 | 572.31 | 915.38 | 2601.07 | 417.78 | 0.00 | 0.00 | 0.00 |
July | 1403.23 | 520.27 | 882.96 | 2537.95 | 303.27 | 0.00 | 0.00 | 0.00 |
August | 1374.96 | 514.18 | 860.78 | 2515.82 | 260.67 | 0.00 | 0.00 | 0.00 |
September | 1120.22 | 466.62 | 653.60 | 1782.74 | 529.41 | 0.00 | 0.00 | 0.00 |
October | 997.98 | 518.06 | 479.92 | 1339.99 | 1081.43 | 0.00 | 0.00 | 0.00 |
November | 796.46 | 357.49 | 438.97 | 874.71 | 1431.50 | 0.00 | 0.00 | 0.00 |
December | 657.08 | 287.41 | 369.67 | 550.85 | 1734.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.36 | 480.43 | 645.93 | 1614.03 | 1020.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 657.08 | 287.41 | 369.67 | 550.85 | 260.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1487.69 | 644.10 | 915.38 | 2601.07 | 2024.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.71 | 0.00 | 491.71 | 90.28 | 2960.56 | 0.00 | 0.00 | 0.00 |
February | 545.02 | 0.00 | 545.02 | 259.63 | 2438.31 | 0.00 | 0.00 | 0.00 |
March | 765.17 | 0.00 | 765.17 | 565.98 | 1536.55 | 0.00 | 0.00 | 0.00 |
April | 925.55 | 4.11 | 921.44 | 1036.86 | 1254.22 | 0.00 | 0.00 | 0.00 |
May | 1106.94 | 35.33 | 1071.61 | 1544.11 | 828.95 | 0.00 | 0.00 | 0.00 |
June | 1218.24 | 80.43 | 1137.80 | 2187.40 | 531.93 | 0.00 | 0.00 | 0.00 |
July | 1149.41 | 55.87 | 1093.53 | 2178.11 | 389.77 | 0.00 | 0.00 | 0.00 |
August | 1022.21 | 11.14 | 1011.07 | 1992.20 | 319.85 | 0.00 | 0.00 | 0.00 |
September | 772.69 | 0.11 | 772.59 | 1153.51 | 700.28 | 0.00 | 0.00 | 0.00 |
October | 587.50 | 0.00 | 587.50 | 558.04 | 1393.29 | 0.00 | 0.00 | 0.00 |
November | 525.80 | 0.00 | 525.80 | 326.25 | 1876.50 | 0.00 | 0.00 | 0.00 |
December | 454.55 | 0.00 | 454.55 | 101.61 | 2353.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 798.44 | 15.65 | 782.79 | 1003.64 | 1376.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 454.55 | 0.00 | 454.55 | 90.28 | 319.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1218.24 | 80.43 | 1137.80 | 2187.40 | 2960.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 719.90 | 324.71 | 395.19 | 533.74 | 1778.26 | 0.00 | 0.00 | 0.00 |
February | 907.57 | 487.63 | 419.94 | 898.82 | 1488.60 | 0.00 | 0.00 | 0.00 |
March | 1141.83 | 519.79 | 622.04 | 1303.01 | 980.55 | 0.00 | 0.00 | 0.00 |
April | 1380.77 | 629.59 | 751.17 | 1894.12 | 815.40 | 0.00 | 0.00 | 0.00 |
May | 1516.19 | 641.17 | 875.01 | 2294.34 | 562.85 | 0.00 | 0.00 | 0.00 |
June | 1569.76 | 657.93 | 911.84 | 2703.47 | 365.51 | 0.00 | 0.00 | 0.00 |
July | 1530.58 | 643.48 | 887.10 | 2718.45 | 270.33 | 0.00 | 0.00 | 0.00 |
August | 1399.98 | 555.42 | 844.56 | 2533.72 | 222.21 | 0.00 | 0.00 | 0.00 |
September | 1150.59 | 509.80 | 640.79 | 1813.55 | 467.23 | 0.00 | 0.00 | 0.00 |
October | 981.55 | 510.73 | 470.83 | 1266.65 | 896.15 | 0.00 | 0.00 | 0.00 |
November | 784.76 | 355.34 | 429.42 | 811.62 | 1158.46 | 0.00 | 0.00 | 0.00 |
December | 679.75 | 309.86 | 369.90 | 546.77 | 1418.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1148.09 | 512.04 | 636.05 | 1613.55 | 865.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 679.75 | 309.86 | 369.90 | 533.74 | 222.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1569.76 | 657.93 | 911.84 | 2718.45 | 1778.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2629.75 | 1833.45 | 796.30 | 3018.24 | 2559.96 | 0.00 | 0.00 | 0.00 |
February | 2454.43 | 1645.27 | 809.16 | 3048.71 | 2227.80 | 0.00 | 0.00 | 0.00 |
March | 2207.36 | 1150.35 | 1057.02 | 2957.35 | 1571.50 | 0.00 | 0.00 | 0.00 |
April | 1653.17 | 538.14 | 1115.03 | 2452.17 | 1326.73 | 0.00 | 0.00 | 0.00 |
May | 1335.69 | 155.24 | 1180.45 | 2084.79 | 889.81 | 0.00 | 0.00 | 0.00 |
June | 1234.99 | 68.72 | 1166.27 | 2288.08 | 569.08 | 0.00 | 0.00 | 0.00 |
July | 1248.55 | 93.10 | 1155.45 | 2423.81 | 409.14 | 0.00 | 0.00 | 0.00 |
August | 1490.68 | 278.46 | 1212.22 | 2954.62 | 344.97 | 0.00 | 0.00 | 0.00 |
September | 1639.38 | 609.76 | 1029.62 | 2776.38 | 742.93 | 0.00 | 0.00 | 0.00 |
October | 2376.63 | 1539.59 | 837.05 | 3498.13 | 1430.62 | 0.00 | 0.00 | 0.00 |
November | 2556.83 | 1696.67 | 860.16 | 3407.28 | 1834.34 | 0.00 | 0.00 | 0.00 |
December | 2592.20 | 1823.63 | 768.57 | 3173.54 | 2150.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1949.48 | 949.47 | 1000.02 | 2839.74 | 1333.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1234.99 | 68.72 | 768.57 | 2084.79 | 344.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2629.75 | 1833.45 | 1212.22 | 3498.13 | 2559.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 739.44 | 343.00 | 396.44 | 594.89 | 1907.70 | 0.00 | 0.00 | 0.00 |
February | 848.87 | 396.90 | 451.97 | 870.64 | 1636.28 | 0.00 | 0.00 | 0.00 |
March | 1251.19 | 604.60 | 646.59 | 1534.39 | 1104.68 | 0.00 | 0.00 | 0.00 |
April | 1407.57 | 644.10 | 763.47 | 1972.52 | 923.23 | 0.00 | 0.00 | 0.00 |
May | 1414.65 | 535.95 | 878.69 | 2175.41 | 631.06 | 0.00 | 0.00 | 0.00 |
June | 1487.69 | 572.31 | 915.38 | 2580.88 | 419.30 | 0.00 | 0.00 | 0.00 |
July | 1403.23 | 520.27 | 882.96 | 2517.50 | 308.73 | 0.00 | 0.00 | 0.00 |
August | 1374.96 | 514.18 | 860.78 | 2496.23 | 267.56 | 0.00 | 0.00 | 0.00 |
September | 1120.22 | 466.62 | 653.60 | 1774.56 | 517.15 | 0.00 | 0.00 | 0.00 |
October | 997.98 | 518.06 | 479.92 | 1349.66 | 1012.25 | 0.00 | 0.00 | 0.00 |
November | 796.46 | 357.49 | 438.97 | 899.68 | 1323.36 | 0.00 | 0.00 | 0.00 |
December | 657.08 | 287.41 | 369.67 | 570.18 | 1598.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.36 | 480.43 | 645.93 | 1615.32 | 967.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 657.08 | 287.41 | 369.67 | 570.18 | 267.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1487.69 | 644.10 | 915.38 | 2580.88 | 1907.70 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263404E+09 | 0.00 | 0.263404E+09 | 25932415.57 | 0.192014E+10 |
February | 0.263704E+09 | 0.00 | 0.263704E+09 | 91874059.63 | 0.143382E+10 |
March | 0.409893E+09 | 0.00 | 0.409893E+09 | 0.253274E+09 | 0.100703E+10 |
April | 0.479809E+09 | 2128096.13 | 0.477681E+09 | 0.505792E+09 | 0.743144E+09 |
May | 0.592973E+09 | 18924448.79 | 0.574049E+09 | 0.826073E+09 | 0.472019E+09 |
June | 0.631541E+09 | 41696653.39 | 0.589845E+09 | 0.114118E+10 | 0.280406E+09 |
July | 0.615723E+09 | 29930719.71 | 0.585792E+09 | 0.117715E+10 | 0.203639E+09 |
August | 0.547584E+09 | 5965069.54 | 0.541619E+09 | 0.107044E+10 | 0.169041E+09 |
September | 0.400569E+09 | 56389.02 | 0.400513E+09 | 0.591911E+09 | 0.400352E+09 |
October | 0.314718E+09 | 0.00 | 0.314718E+09 | 0.255740E+09 | 0.919271E+09 |
November | 0.272576E+09 | 0.00 | 0.272576E+09 | 0.108721E+09 | 0.124154E+10 |
December | 0.243498E+09 | 0.00 | 0.243498E+09 | 22454294.88 | 0.166892E+10 |
Annual Sum or Average | 0.503599E+10 | 98701376.58 | 0.493729E+10 | 0.607054E+10 | 0.104593E+11 |
Minimum of Months | 0.243498E+09 | 0.00 | 0.243498E+09 | 22454294.88 | 0.169041E+09 |
Maximum of Months | 0.631541E+09 | 41696653.39 | 0.589845E+09 | 0.117715E+10 | 0.192014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263404E+09 | 0.00 | 0.263404E+09 | 25932362.36 | 0.192014E+10 |
February | 0.263703E+09 | 0.00 | 0.263703E+09 | 91873939.98 | 0.143382E+10 |
March | 0.409892E+09 | 0.00 | 0.409892E+09 | 0.253273E+09 | 0.100703E+10 |
April | 0.479809E+09 | 2128093.57 | 0.477681E+09 | 0.505792E+09 | 0.743143E+09 |
May | 0.592973E+09 | 18924426.08 | 0.574048E+09 | 0.826072E+09 | 0.472019E+09 |
June | 0.631541E+09 | 41696603.36 | 0.589844E+09 | 0.114118E+10 | 0.280406E+09 |
July | 0.615722E+09 | 29930683.80 | 0.585791E+09 | 0.117715E+10 | 0.203639E+09 |
August | 0.547584E+09 | 5965062.39 | 0.541618E+09 | 0.107044E+10 | 0.169040E+09 |
September | 0.400569E+09 | 56388.95 | 0.400513E+09 | 0.591911E+09 | 0.400352E+09 |
October | 0.314718E+09 | 0.00 | 0.314718E+09 | 0.255740E+09 | 0.919270E+09 |
November | 0.272576E+09 | 0.00 | 0.272576E+09 | 0.108721E+09 | 0.124154E+10 |
December | 0.243497E+09 | 0.00 | 0.243497E+09 | 22454229.85 | 0.166892E+10 |
Annual Sum or Average | 0.503599E+10 | 98701258.15 | 0.493729E+10 | 0.607053E+10 | 0.104593E+11 |
Minimum of Months | 0.243497E+09 | 0.00 | 0.243497E+09 | 22454229.85 | 0.169040E+09 |
Maximum of Months | 0.631541E+09 | 41696603.36 | 0.589844E+09 | 0.117715E+10 | 0.192014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263404E+09 | 0.00 | 0.263404E+09 | 25932415.57 | 0.192014E+10 |
February | 0.263704E+09 | 0.00 | 0.263704E+09 | 91874059.63 | 0.143382E+10 |
March | 0.409893E+09 | 0.00 | 0.409893E+09 | 0.253274E+09 | 0.100703E+10 |
April | 0.479809E+09 | 2128096.13 | 0.477681E+09 | 0.505792E+09 | 0.743144E+09 |
May | 0.592973E+09 | 18924448.79 | 0.574049E+09 | 0.826073E+09 | 0.472019E+09 |
June | 0.631541E+09 | 41696653.39 | 0.589845E+09 | 0.114118E+10 | 0.280406E+09 |
July | 0.615723E+09 | 29930719.71 | 0.585792E+09 | 0.117715E+10 | 0.203639E+09 |
August | 0.547584E+09 | 5965069.54 | 0.541619E+09 | 0.107044E+10 | 0.169041E+09 |
September | 0.400569E+09 | 56389.02 | 0.400513E+09 | 0.591911E+09 | 0.400352E+09 |
October | 0.314718E+09 | 0.00 | 0.314718E+09 | 0.255740E+09 | 0.919271E+09 |
November | 0.272576E+09 | 0.00 | 0.272576E+09 | 0.108721E+09 | 0.124154E+10 |
December | 0.243498E+09 | 0.00 | 0.243498E+09 | 22454294.88 | 0.166892E+10 |
Annual Sum or Average | 0.503599E+10 | 98701376.58 | 0.493729E+10 | 0.607054E+10 | 0.104593E+11 |
Minimum of Months | 0.243498E+09 | 0.00 | 0.243498E+09 | 22454294.88 | 0.169041E+09 |
Maximum of Months | 0.631541E+09 | 41696653.39 | 0.589845E+09 | 0.117715E+10 | 0.192014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263404E+09 | 0.00 | 0.263404E+09 | 25932362.36 | 0.192014E+10 |
February | 0.263703E+09 | 0.00 | 0.263703E+09 | 91873939.98 | 0.143382E+10 |
March | 0.409892E+09 | 0.00 | 0.409892E+09 | 0.253273E+09 | 0.100703E+10 |
April | 0.479809E+09 | 2128093.57 | 0.477681E+09 | 0.505792E+09 | 0.743143E+09 |
May | 0.592973E+09 | 18924426.08 | 0.574048E+09 | 0.826072E+09 | 0.472019E+09 |
June | 0.631541E+09 | 41696603.36 | 0.589844E+09 | 0.114118E+10 | 0.280406E+09 |
July | 0.615722E+09 | 29930683.80 | 0.585791E+09 | 0.117715E+10 | 0.203639E+09 |
August | 0.547584E+09 | 5965062.39 | 0.541618E+09 | 0.107044E+10 | 0.169040E+09 |
September | 0.400569E+09 | 56388.95 | 0.400513E+09 | 0.591911E+09 | 0.400352E+09 |
October | 0.314718E+09 | 0.00 | 0.314718E+09 | 0.255740E+09 | 0.919270E+09 |
November | 0.272576E+09 | 0.00 | 0.272576E+09 | 0.108721E+09 | 0.124154E+10 |
December | 0.243497E+09 | 0.00 | 0.243497E+09 | 22454229.85 | 0.166892E+10 |
Annual Sum or Average | 0.503599E+10 | 98701258.15 | 0.493729E+10 | 0.607053E+10 | 0.104593E+11 |
Minimum of Months | 0.243497E+09 | 0.00 | 0.243497E+09 | 22454229.85 | 0.169040E+09 |
Maximum of Months | 0.631541E+09 | 41696603.36 | 0.589844E+09 | 0.117715E+10 | 0.192014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263394E+09 | 0.00 | 0.263394E+09 | 25931370.38 | 0.192006E+10 |
February | 0.263693E+09 | 0.00 | 0.263693E+09 | 91870356.70 | 0.143376E+10 |
March | 0.409876E+09 | 0.00 | 0.409876E+09 | 0.253263E+09 | 0.100699E+10 |
April | 0.479790E+09 | 2128010.36 | 0.477662E+09 | 0.505772E+09 | 0.743114E+09 |
May | 0.592949E+09 | 18923686.05 | 0.574025E+09 | 0.826039E+09 | 0.472000E+09 |
June | 0.631516E+09 | 41694972.83 | 0.589821E+09 | 0.114113E+10 | 0.280395E+09 |
July | 0.615698E+09 | 29929513.37 | 0.585768E+09 | 0.117710E+10 | 0.203631E+09 |
August | 0.547562E+09 | 5964829.13 | 0.541597E+09 | 0.107039E+10 | 0.169034E+09 |
September | 0.400553E+09 | 56386.75 | 0.400497E+09 | 0.591887E+09 | 0.400336E+09 |
October | 0.314705E+09 | 0.00 | 0.314705E+09 | 0.255730E+09 | 0.919233E+09 |
November | 0.272565E+09 | 0.00 | 0.272565E+09 | 0.108717E+09 | 0.124149E+10 |
December | 0.243488E+09 | 0.00 | 0.243488E+09 | 22453389.87 | 0.166886E+10 |
Annual Sum or Average | 0.503579E+10 | 98697398.48 | 0.493709E+10 | 0.607029E+10 | 0.104589E+11 |
Minimum of Months | 0.243488E+09 | 0.00 | 0.243488E+09 | 22453389.87 | 0.169034E+09 |
Maximum of Months | 0.631516E+09 | 41694972.83 | 0.589821E+09 | 0.117710E+10 | 0.192006E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.642737E+09 | 0.289907E+09 | 0.352830E+09 | 0.419044E+09 | 0.191084E+10 |
February | 0.731874E+09 | 0.393230E+09 | 0.338643E+09 | 0.682111E+09 | 0.142027E+10 |
March | 0.101944E+10 | 0.464078E+09 | 0.555360E+09 | 0.113667E+10 | 0.100218E+10 |
April | 0.119300E+10 | 0.543975E+09 | 0.649021E+09 | 0.163971E+10 | 0.751778E+09 |
May | 0.135367E+10 | 0.572446E+09 | 0.781220E+09 | 0.207677E+10 | 0.514876E+09 |
June | 0.135629E+10 | 0.568455E+09 | 0.787835E+09 | 0.237067E+10 | 0.305456E+09 |
July | 0.136652E+10 | 0.574504E+09 | 0.792015E+09 | 0.246888E+10 | 0.217324E+09 |
August | 0.124991E+10 | 0.495885E+09 | 0.754028E+09 | 0.229994E+10 | 0.171099E+09 |
September | 0.994121E+09 | 0.440469E+09 | 0.553652E+09 | 0.158157E+10 | 0.424875E+09 |
October | 0.876338E+09 | 0.455980E+09 | 0.420358E+09 | 0.110796E+10 | 0.928437E+09 |
November | 0.678039E+09 | 0.307013E+09 | 0.371025E+09 | 0.632388E+09 | 0.121327E+10 |
December | 0.606889E+09 | 0.276644E+09 | 0.330246E+09 | 0.420328E+09 | 0.161376E+10 |
Annual Sum or Average | 0.120688E+11 | 0.538259E+10 | 0.668623E+10 | 0.168361E+11 | 0.104742E+11 |
Minimum of Months | 0.606889E+09 | 0.276644E+09 | 0.330246E+09 | 0.419044E+09 | 0.171099E+09 |
Maximum of Months | 0.136652E+10 | 0.574504E+09 | 0.792015E+09 | 0.246888E+10 | 0.191084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.642737E+09 | 0.289907E+09 | 0.352830E+09 | 0.419044E+09 | 0.191084E+10 |
February | 0.731874E+09 | 0.393230E+09 | 0.338643E+09 | 0.682111E+09 | 0.142027E+10 |
March | 0.101944E+10 | 0.464078E+09 | 0.555360E+09 | 0.113667E+10 | 0.100218E+10 |
April | 0.119300E+10 | 0.543975E+09 | 0.649021E+09 | 0.163971E+10 | 0.751778E+09 |
May | 0.135367E+10 | 0.572446E+09 | 0.781220E+09 | 0.207677E+10 | 0.514876E+09 |
June | 0.135629E+10 | 0.568455E+09 | 0.787835E+09 | 0.237067E+10 | 0.305456E+09 |
July | 0.136652E+10 | 0.574504E+09 | 0.792015E+09 | 0.246888E+10 | 0.217324E+09 |
August | 0.124991E+10 | 0.495885E+09 | 0.754028E+09 | 0.229994E+10 | 0.171099E+09 |
September | 0.994121E+09 | 0.440469E+09 | 0.553652E+09 | 0.158157E+10 | 0.424875E+09 |
October | 0.876338E+09 | 0.455980E+09 | 0.420358E+09 | 0.110796E+10 | 0.928437E+09 |
November | 0.678039E+09 | 0.307013E+09 | 0.371025E+09 | 0.632388E+09 | 0.121327E+10 |
December | 0.606889E+09 | 0.276644E+09 | 0.330246E+09 | 0.420328E+09 | 0.161376E+10 |
Annual Sum or Average | 0.120688E+11 | 0.538259E+10 | 0.668623E+10 | 0.168361E+11 | 0.104742E+11 |
Minimum of Months | 0.606889E+09 | 0.276644E+09 | 0.330246E+09 | 0.419044E+09 | 0.171099E+09 |
Maximum of Months | 0.136652E+10 | 0.574504E+09 | 0.792015E+09 | 0.246888E+10 | 0.191084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.642725E+09 | 0.289901E+09 | 0.352823E+09 | 0.419036E+09 | 0.191081E+10 |
February | 0.731860E+09 | 0.393223E+09 | 0.338637E+09 | 0.682099E+09 | 0.142024E+10 |
March | 0.101942E+10 | 0.464069E+09 | 0.555350E+09 | 0.113665E+10 | 0.100217E+10 |
April | 0.119297E+10 | 0.543965E+09 | 0.649009E+09 | 0.163968E+10 | 0.751764E+09 |
May | 0.135364E+10 | 0.572435E+09 | 0.781206E+09 | 0.207674E+10 | 0.514866E+09 |
June | 0.135627E+10 | 0.568444E+09 | 0.787821E+09 | 0.237063E+10 | 0.305450E+09 |
July | 0.136649E+10 | 0.574494E+09 | 0.792000E+09 | 0.246884E+10 | 0.217320E+09 |
August | 0.124989E+10 | 0.495876E+09 | 0.754014E+09 | 0.229990E+10 | 0.171096E+09 |
September | 0.994102E+09 | 0.440461E+09 | 0.553641E+09 | 0.158154E+10 | 0.424867E+09 |
October | 0.876322E+09 | 0.455972E+09 | 0.420351E+09 | 0.110794E+10 | 0.928420E+09 |
November | 0.678026E+09 | 0.307008E+09 | 0.371018E+09 | 0.632377E+09 | 0.121325E+10 |
December | 0.606878E+09 | 0.276639E+09 | 0.330240E+09 | 0.420320E+09 | 0.161373E+10 |
Annual Sum or Average | 0.120686E+11 | 0.538249E+10 | 0.668611E+10 | 0.168357E+11 | 0.104740E+11 |
Minimum of Months | 0.606878E+09 | 0.276639E+09 | 0.330240E+09 | 0.419036E+09 | 0.171096E+09 |
Maximum of Months | 0.136649E+10 | 0.574494E+09 | 0.792000E+09 | 0.246884E+10 | 0.191081E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140872E+10 | 0.982154E+09 | 0.426565E+09 | 0.158203E+10 | 0.155519E+10 |
February | 0.118757E+10 | 0.796059E+09 | 0.391508E+09 | 0.145549E+10 | 0.122089E+10 |
March | 0.118246E+10 | 0.616226E+09 | 0.566229E+09 | 0.157772E+10 | 0.943119E+09 |
April | 0.857013E+09 | 0.278976E+09 | 0.578037E+09 | 0.126886E+10 | 0.749333E+09 |
May | 0.715513E+09 | 83161957.35 | 0.632351E+09 | 0.112667E+10 | 0.498741E+09 |
June | 0.640226E+09 | 35626047.07 | 0.604600E+09 | 0.119590E+10 | 0.299979E+09 |
July | 0.668831E+09 | 49871859.31 | 0.618959E+09 | 0.131112E+10 | 0.213962E+09 |
August | 0.798537E+09 | 0.149169E+09 | 0.649367E+09 | 0.159573E+10 | 0.179642E+09 |
September | 0.849865E+09 | 0.316106E+09 | 0.533759E+09 | 0.145113E+10 | 0.406264E+09 |
October | 0.127313E+10 | 0.824736E+09 | 0.448395E+09 | 0.187422E+10 | 0.857956E+09 |
November | 0.132548E+10 | 0.879564E+09 | 0.445912E+09 | 0.174004E+10 | 0.108873E+10 |
December | 0.138861E+10 | 0.976895E+09 | 0.411711E+09 | 0.165657E+10 | 0.137027E+10 |
Annual Sum or Average | 0.122959E+11 | 0.598855E+10 | 0.630739E+10 | 0.178355E+11 | 0.938408E+10 |
Minimum of Months | 0.640226E+09 | 35626047.07 | 0.391508E+09 | 0.112667E+10 | 0.179642E+09 |
Maximum of Months | 0.140872E+10 | 0.982154E+09 | 0.649367E+09 | 0.187422E+10 | 0.155519E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140872E+10 | 0.982153E+09 | 0.426564E+09 | 0.158203E+10 | 0.155519E+10 |
February | 0.118757E+10 | 0.796058E+09 | 0.391508E+09 | 0.145548E+10 | 0.122089E+10 |
March | 0.118245E+10 | 0.616225E+09 | 0.566229E+09 | 0.157772E+10 | 0.943119E+09 |
April | 0.857012E+09 | 0.278976E+09 | 0.578036E+09 | 0.126886E+10 | 0.749333E+09 |
May | 0.715512E+09 | 83161857.56 | 0.632350E+09 | 0.112667E+10 | 0.498741E+09 |
June | 0.640225E+09 | 35626004.32 | 0.604599E+09 | 0.119590E+10 | 0.299978E+09 |
July | 0.668830E+09 | 49871799.47 | 0.618959E+09 | 0.131112E+10 | 0.213962E+09 |
August | 0.798536E+09 | 0.149169E+09 | 0.649367E+09 | 0.159573E+10 | 0.179641E+09 |
September | 0.849864E+09 | 0.316105E+09 | 0.533759E+09 | 0.145113E+10 | 0.406264E+09 |
October | 0.127313E+10 | 0.824735E+09 | 0.448395E+09 | 0.187422E+10 | 0.857956E+09 |
November | 0.132547E+10 | 0.879563E+09 | 0.445912E+09 | 0.174004E+10 | 0.108873E+10 |
December | 0.138861E+10 | 0.976894E+09 | 0.411711E+09 | 0.165656E+10 | 0.137027E+10 |
Annual Sum or Average | 0.122959E+11 | 0.598854E+10 | 0.630739E+10 | 0.178355E+11 | 0.938407E+10 |
Minimum of Months | 0.640225E+09 | 35626004.32 | 0.391508E+09 | 0.112667E+10 | 0.179641E+09 |
Maximum of Months | 0.140872E+10 | 0.982153E+09 | 0.649367E+09 | 0.187422E+10 | 0.155519E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140872E+10 | 0.982154E+09 | 0.426565E+09 | 0.158203E+10 | 0.155519E+10 |
February | 0.118757E+10 | 0.796059E+09 | 0.391508E+09 | 0.145549E+10 | 0.122089E+10 |
March | 0.118246E+10 | 0.616226E+09 | 0.566229E+09 | 0.157772E+10 | 0.943119E+09 |
April | 0.857013E+09 | 0.278976E+09 | 0.578037E+09 | 0.126886E+10 | 0.749333E+09 |
May | 0.715513E+09 | 83161957.35 | 0.632351E+09 | 0.112667E+10 | 0.498741E+09 |
June | 0.640226E+09 | 35626047.07 | 0.604600E+09 | 0.119590E+10 | 0.299979E+09 |
July | 0.668831E+09 | 49871859.31 | 0.618959E+09 | 0.131112E+10 | 0.213962E+09 |
August | 0.798537E+09 | 0.149169E+09 | 0.649367E+09 | 0.159573E+10 | 0.179642E+09 |
September | 0.849865E+09 | 0.316106E+09 | 0.533759E+09 | 0.145113E+10 | 0.406264E+09 |
October | 0.127313E+10 | 0.824736E+09 | 0.448395E+09 | 0.187422E+10 | 0.857956E+09 |
November | 0.132548E+10 | 0.879564E+09 | 0.445912E+09 | 0.174004E+10 | 0.108873E+10 |
December | 0.138861E+10 | 0.976895E+09 | 0.411711E+09 | 0.165657E+10 | 0.137027E+10 |
Annual Sum or Average | 0.122959E+11 | 0.598855E+10 | 0.630739E+10 | 0.178355E+11 | 0.938408E+10 |
Minimum of Months | 0.640226E+09 | 35626047.07 | 0.391508E+09 | 0.112667E+10 | 0.179642E+09 |
Maximum of Months | 0.140872E+10 | 0.982154E+09 | 0.649367E+09 | 0.187422E+10 | 0.155519E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140872E+10 | 0.982153E+09 | 0.426564E+09 | 0.158203E+10 | 0.155519E+10 |
February | 0.118757E+10 | 0.796058E+09 | 0.391508E+09 | 0.145548E+10 | 0.122089E+10 |
March | 0.118245E+10 | 0.616225E+09 | 0.566229E+09 | 0.157772E+10 | 0.943119E+09 |
April | 0.857012E+09 | 0.278976E+09 | 0.578036E+09 | 0.126886E+10 | 0.749333E+09 |
May | 0.715512E+09 | 83161857.56 | 0.632350E+09 | 0.112667E+10 | 0.498741E+09 |
June | 0.640225E+09 | 35626004.32 | 0.604599E+09 | 0.119590E+10 | 0.299978E+09 |
July | 0.668830E+09 | 49871799.47 | 0.618959E+09 | 0.131112E+10 | 0.213962E+09 |
August | 0.798536E+09 | 0.149169E+09 | 0.649367E+09 | 0.159573E+10 | 0.179641E+09 |
September | 0.849864E+09 | 0.316105E+09 | 0.533759E+09 | 0.145113E+10 | 0.406264E+09 |
October | 0.127313E+10 | 0.824735E+09 | 0.448395E+09 | 0.187422E+10 | 0.857956E+09 |
November | 0.132547E+10 | 0.879563E+09 | 0.445912E+09 | 0.174004E+10 | 0.108873E+10 |
December | 0.138861E+10 | 0.976894E+09 | 0.411711E+09 | 0.165656E+10 | 0.137027E+10 |
Annual Sum or Average | 0.122959E+11 | 0.598854E+10 | 0.630739E+10 | 0.178355E+11 | 0.938407E+10 |
Minimum of Months | 0.640225E+09 | 35626004.32 | 0.391508E+09 | 0.112667E+10 | 0.179641E+09 |
Maximum of Months | 0.140872E+10 | 0.982153E+09 | 0.649367E+09 | 0.187422E+10 | 0.155519E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140866E+10 | 0.982114E+09 | 0.426548E+09 | 0.158197E+10 | 0.155513E+10 |
February | 0.118752E+10 | 0.796027E+09 | 0.391492E+09 | 0.145543E+10 | 0.122084E+10 |
March | 0.118241E+10 | 0.616201E+09 | 0.566207E+09 | 0.157766E+10 | 0.943081E+09 |
April | 0.856978E+09 | 0.278965E+09 | 0.578014E+09 | 0.126881E+10 | 0.749303E+09 |
May | 0.715484E+09 | 83158605.56 | 0.632325E+09 | 0.112662E+10 | 0.498721E+09 |
June | 0.640200E+09 | 35624611.18 | 0.604575E+09 | 0.119586E+10 | 0.299966E+09 |
July | 0.668804E+09 | 49869849.26 | 0.618934E+09 | 0.131107E+10 | 0.213953E+09 |
August | 0.798504E+09 | 0.149163E+09 | 0.649341E+09 | 0.159567E+10 | 0.179634E+09 |
September | 0.849831E+09 | 0.316093E+09 | 0.533738E+09 | 0.145107E+10 | 0.406248E+09 |
October | 0.127308E+10 | 0.824702E+09 | 0.448377E+09 | 0.187415E+10 | 0.857921E+09 |
November | 0.132542E+10 | 0.879529E+09 | 0.445894E+09 | 0.173997E+10 | 0.108868E+10 |
December | 0.138855E+10 | 0.976856E+09 | 0.411695E+09 | 0.165650E+10 | 0.137021E+10 |
Annual Sum or Average | 0.122954E+11 | 0.598830E+10 | 0.630714E+10 | 0.178348E+11 | 0.938370E+10 |
Minimum of Months | 0.640200E+09 | 35624611.18 | 0.391492E+09 | 0.112662E+10 | 0.179634E+09 |
Maximum of Months | 0.140866E+10 | 0.982114E+09 | 0.649341E+09 | 0.187415E+10 | 0.155513E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.660180E+09 | 0.306238E+09 | 0.353942E+09 | 0.476414E+09 | 0.209800E+10 |
February | 0.684539E+09 | 0.320063E+09 | 0.364475E+09 | 0.651376E+09 | 0.165588E+10 |
March | 0.111707E+10 | 0.539796E+09 | 0.577279E+09 | 0.131921E+10 | 0.123795E+10 |
April | 0.121615E+10 | 0.556505E+09 | 0.659645E+09 | 0.165906E+10 | 0.970061E+09 |
May | 0.126301E+10 | 0.478504E+09 | 0.784505E+09 | 0.194318E+10 | 0.619124E+09 |
June | 0.128537E+10 | 0.494477E+09 | 0.790896E+09 | 0.222821E+10 | 0.408528E+09 |
July | 0.125281E+10 | 0.464501E+09 | 0.788314E+09 | 0.223158E+10 | 0.322284E+09 |
August | 0.122758E+10 | 0.459066E+09 | 0.768514E+09 | 0.220060E+10 | 0.300197E+09 |
September | 0.967880E+09 | 0.403164E+09 | 0.564715E+09 | 0.152601E+10 | 0.511137E+09 |
October | 0.891008E+09 | 0.462531E+09 | 0.428477E+09 | 0.116569E+10 | 0.112819E+10 |
November | 0.688150E+09 | 0.308877E+09 | 0.379273E+09 | 0.703976E+09 | 0.149351E+10 |
December | 0.586643E+09 | 0.256599E+09 | 0.330045E+09 | 0.438424E+09 | 0.198935E+10 |
Annual Sum or Average | 0.118404E+11 | 0.505032E+10 | 0.679008E+10 | 0.165437E+11 | 0.127342E+11 |
Minimum of Months | 0.586643E+09 | 0.256599E+09 | 0.330045E+09 | 0.438424E+09 | 0.300197E+09 |
Maximum of Months | 0.128537E+10 | 0.556505E+09 | 0.790896E+09 | 0.223158E+10 | 0.209800E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.660180E+09 | 0.306238E+09 | 0.353942E+09 | 0.476414E+09 | 0.209800E+10 |
February | 0.684539E+09 | 0.320063E+09 | 0.364475E+09 | 0.651376E+09 | 0.165588E+10 |
March | 0.111707E+10 | 0.539796E+09 | 0.577279E+09 | 0.131921E+10 | 0.123795E+10 |
April | 0.121615E+10 | 0.556505E+09 | 0.659645E+09 | 0.165906E+10 | 0.970061E+09 |
May | 0.126301E+10 | 0.478504E+09 | 0.784505E+09 | 0.194318E+10 | 0.619124E+09 |
June | 0.128537E+10 | 0.494477E+09 | 0.790896E+09 | 0.222821E+10 | 0.408528E+09 |
July | 0.125281E+10 | 0.464501E+09 | 0.788314E+09 | 0.223158E+10 | 0.322284E+09 |
August | 0.122758E+10 | 0.459066E+09 | 0.768514E+09 | 0.220060E+10 | 0.300197E+09 |
September | 0.967880E+09 | 0.403164E+09 | 0.564715E+09 | 0.152601E+10 | 0.511137E+09 |
October | 0.891008E+09 | 0.462531E+09 | 0.428477E+09 | 0.116569E+10 | 0.112819E+10 |
November | 0.688150E+09 | 0.308877E+09 | 0.379273E+09 | 0.703976E+09 | 0.149351E+10 |
December | 0.586643E+09 | 0.256599E+09 | 0.330045E+09 | 0.438424E+09 | 0.198935E+10 |
Annual Sum or Average | 0.118404E+11 | 0.505032E+10 | 0.679008E+10 | 0.165437E+11 | 0.127342E+11 |
Minimum of Months | 0.586643E+09 | 0.256599E+09 | 0.330045E+09 | 0.438424E+09 | 0.300197E+09 |
Maximum of Months | 0.128537E+10 | 0.556505E+09 | 0.790896E+09 | 0.223158E+10 | 0.209800E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.660168E+09 | 0.306232E+09 | 0.353936E+09 | 0.476405E+09 | 0.209796E+10 |
February | 0.684526E+09 | 0.320057E+09 | 0.364469E+09 | 0.651364E+09 | 0.165585E+10 |
March | 0.111705E+10 | 0.539786E+09 | 0.577268E+09 | 0.131918E+10 | 0.123793E+10 |
April | 0.121613E+10 | 0.556495E+09 | 0.659633E+09 | 0.165903E+10 | 0.970043E+09 |
May | 0.126299E+10 | 0.478496E+09 | 0.784491E+09 | 0.194315E+10 | 0.619112E+09 |
June | 0.128535E+10 | 0.494468E+09 | 0.790882E+09 | 0.222817E+10 | 0.408521E+09 |
July | 0.125279E+10 | 0.464493E+09 | 0.788299E+09 | 0.223154E+10 | 0.322278E+09 |
August | 0.122756E+10 | 0.459058E+09 | 0.768500E+09 | 0.220056E+10 | 0.300192E+09 |
September | 0.967862E+09 | 0.403157E+09 | 0.564705E+09 | 0.152598E+10 | 0.511128E+09 |
October | 0.890992E+09 | 0.462523E+09 | 0.428469E+09 | 0.116567E+10 | 0.112817E+10 |
November | 0.688138E+09 | 0.308872E+09 | 0.379266E+09 | 0.703963E+09 | 0.149349E+10 |
December | 0.586633E+09 | 0.256594E+09 | 0.330039E+09 | 0.438416E+09 | 0.198931E+10 |
Annual Sum or Average | 0.118402E+11 | 0.505023E+10 | 0.678996E+10 | 0.165434E+11 | 0.127340E+11 |
Minimum of Months | 0.586633E+09 | 0.256594E+09 | 0.330039E+09 | 0.438416E+09 | 0.300192E+09 |
Maximum of Months | 0.128535E+10 | 0.556495E+09 | 0.790882E+09 | 0.223154E+10 | 0.209796E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131700E+10 | 0.00 | 0.131700E+10 | 0.202099E+09 | 0.839974E+10 |
February | 0.131850E+10 | 0.00 | 0.131850E+10 | 0.579637E+09 | 0.626801E+10 |
March | 0.204944E+10 | 0.00 | 0.204944E+10 | 0.142525E+10 | 0.444455E+10 |
April | 0.239902E+10 | 10640351.98 | 0.238838E+10 | 0.264500E+10 | 0.341322E+10 |
May | 0.296483E+10 | 94621099.77 | 0.287021E+10 | 0.416521E+10 | 0.225755E+10 |
June | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.573749E+10 | 0.136308E+10 |
July | 0.307858E+10 | 0.149652E+09 | 0.292892E+10 | 0.591725E+10 | 0.101495E+10 |
August | 0.273789E+10 | 29824987.08 | 0.270806E+10 | 0.541450E+10 | 0.823387E+09 |
September | 0.200282E+10 | 281941.69 | 0.200254E+10 | 0.300721E+10 | 0.186912E+10 |
October | 0.157357E+10 | 0.00 | 0.157357E+10 | 0.141756E+10 | 0.405585E+10 |
November | 0.136286E+10 | 0.00 | 0.136286E+10 | 0.723173E+09 | 0.536639E+10 |
December | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.214000E+09 | 0.692485E+10 |
Annual Sum or Average | 0.251797E+11 | 0.493501E+09 | 0.246862E+11 | 0.314484E+11 | 0.462007E+11 |
Minimum of Months | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.202099E+09 | 0.823387E+09 |
Maximum of Months | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.591725E+10 | 0.839974E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.192819E+10 | 0.869711E+09 | 0.105848E+10 | 0.135343E+10 | 0.506448E+10 |
February | 0.219560E+10 | 0.117968E+10 | 0.101592E+10 | 0.210731E+10 | 0.383475E+10 |
March | 0.305828E+10 | 0.139222E+10 | 0.166606E+10 | 0.341052E+10 | 0.281347E+10 |
April | 0.357895E+10 | 0.163191E+10 | 0.194704E+10 | 0.487609E+10 | 0.219964E+10 |
May | 0.406096E+10 | 0.171732E+10 | 0.234364E+10 | 0.615606E+10 | 0.152560E+10 |
June | 0.406883E+10 | 0.170535E+10 | 0.236348E+10 | 0.703809E+10 | 0.936690E+09 |
July | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.732155E+10 | 0.707007E+09 |
August | 0.374970E+10 | 0.148764E+10 | 0.226206E+10 | 0.682328E+10 | 0.575281E+09 |
September | 0.298233E+10 | 0.132139E+10 | 0.166094E+10 | 0.470094E+10 | 0.124217E+10 |
October | 0.262899E+10 | 0.136793E+10 | 0.126106E+10 | 0.332649E+10 | 0.258462E+10 |
November | 0.203409E+10 | 0.921030E+09 | 0.111306E+10 | 0.196809E+10 | 0.331405E+10 |
December | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.135806E+10 | 0.420831E+10 |
Annual Sum or Average | 0.362061E+11 | 0.161476E+11 | 0.200585E+11 | 0.504399E+11 | 0.290061E+11 |
Minimum of Months | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.135343E+10 | 0.575281E+09 |
Maximum of Months | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.732155E+10 | 0.506448E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.704351E+10 | 0.491071E+10 | 0.213280E+10 | 0.793695E+10 | 0.733025E+10 |
February | 0.593776E+10 | 0.398025E+10 | 0.195752E+10 | 0.727910E+10 | 0.574684E+10 |
March | 0.591221E+10 | 0.308109E+10 | 0.283111E+10 | 0.785044E+10 | 0.448899E+10 |
April | 0.428501E+10 | 0.139486E+10 | 0.289015E+10 | 0.633608E+10 | 0.359024E+10 |
May | 0.357752E+10 | 0.415805E+09 | 0.316172E+10 | 0.562250E+10 | 0.242244E+10 |
June | 0.320109E+10 | 0.178128E+09 | 0.302296E+10 | 0.599845E+10 | 0.146144E+10 |
July | 0.334411E+10 | 0.249356E+09 | 0.309476E+10 | 0.657491E+10 | 0.106708E+10 |
August | 0.399264E+10 | 0.745838E+09 | 0.324680E+10 | 0.799544E+10 | 0.890389E+09 |
September | 0.424927E+10 | 0.158051E+10 | 0.266877E+10 | 0.722482E+10 | 0.197138E+10 |
October | 0.636558E+10 | 0.412363E+10 | 0.224195E+10 | 0.931851E+10 | 0.410093E+10 |
November | 0.662730E+10 | 0.439777E+10 | 0.222953E+10 | 0.868664E+10 | 0.517395E+10 |
December | 0.694295E+10 | 0.488442E+10 | 0.205853E+10 | 0.832843E+10 | 0.633085E+10 |
Annual Sum or Average | 0.614790E+11 | 0.299424E+11 | 0.315366E+11 | 0.891523E+11 | 0.445748E+11 |
Minimum of Months | 0.320109E+10 | 0.178128E+09 | 0.195752E+10 | 0.562250E+10 | 0.890389E+09 |
Maximum of Months | 0.704351E+10 | 0.491071E+10 | 0.324680E+10 | 0.931851E+10 | 0.733025E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198052E+10 | 0.918704E+09 | 0.106182E+10 | 0.154671E+10 | 0.542351E+10 |
February | 0.205360E+10 | 0.960180E+09 | 0.109341E+10 | 0.207614E+10 | 0.418216E+10 |
March | 0.335119E+10 | 0.161937E+10 | 0.173182E+10 | 0.407773E+10 | 0.314751E+10 |
April | 0.364841E+10 | 0.166950E+10 | 0.197891E+10 | 0.510976E+10 | 0.248946E+10 |
May | 0.378899E+10 | 0.143550E+10 | 0.235349E+10 | 0.585914E+10 | 0.171744E+10 |
June | 0.385608E+10 | 0.148342E+10 | 0.237266E+10 | 0.674197E+10 | 0.108289E+10 |
July | 0.375841E+10 | 0.139349E+10 | 0.236492E+10 | 0.679766E+10 | 0.812278E+09 |
August | 0.368270E+10 | 0.137718E+10 | 0.230552E+10 | 0.673837E+10 | 0.698170E+09 |
September | 0.290361E+10 | 0.120948E+10 | 0.169413E+10 | 0.462087E+10 | 0.137222E+10 |
October | 0.267300E+10 | 0.138758E+10 | 0.128542E+10 | 0.358904E+10 | 0.289650E+10 |
November | 0.206443E+10 | 0.926622E+09 | 0.113781E+10 | 0.226724E+10 | 0.371045E+10 |
December | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.147540E+10 | 0.464700E+10 |
Annual Sum or Average | 0.355208E+11 | 0.151508E+11 | 0.203700E+11 | 0.509000E+11 | 0.321796E+11 |
Minimum of Months | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.147540E+10 | 0.698170E+09 |
Maximum of Months | 0.385608E+10 | 0.166950E+10 | 0.237266E+10 | 0.679766E+10 | 0.542351E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131700E+10 | 0.00 | 0.131700E+10 | 0.241815E+09 | 0.792956E+10 |
February | 0.131850E+10 | 0.00 | 0.131850E+10 | 0.628107E+09 | 0.589876E+10 |
March | 0.204944E+10 | 0.00 | 0.204944E+10 | 0.151592E+10 | 0.411550E+10 |
April | 0.239902E+10 | 10640351.98 | 0.238838E+10 | 0.268753E+10 | 0.325093E+10 |
May | 0.296483E+10 | 94621099.77 | 0.287021E+10 | 0.413574E+10 | 0.222025E+10 |
June | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.566974E+10 | 0.137876E+10 |
July | 0.307858E+10 | 0.149652E+09 | 0.292892E+10 | 0.583386E+10 | 0.104397E+10 |
August | 0.273789E+10 | 29824987.08 | 0.270806E+10 | 0.533590E+10 | 0.856683E+09 |
September | 0.200282E+10 | 281941.69 | 0.200254E+10 | 0.298990E+10 | 0.181513E+10 |
October | 0.157357E+10 | 0.00 | 0.157357E+10 | 0.149465E+10 | 0.373179E+10 |
November | 0.136286E+10 | 0.00 | 0.136286E+10 | 0.845633E+09 | 0.486389E+10 |
December | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.272160E+09 | 0.630326E+10 |
Annual Sum or Average | 0.251797E+11 | 0.493501E+09 | 0.246862E+11 | 0.316509E+11 | 0.434085E+11 |
Minimum of Months | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.241815E+09 | 0.856683E+09 |
Maximum of Months | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.583386E+10 | 0.792956E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.192819E+10 | 0.869711E+09 | 0.105848E+10 | 0.142956E+10 | 0.476290E+10 |
February | 0.219560E+10 | 0.117968E+10 | 0.101592E+10 | 0.217441E+10 | 0.360123E+10 |
March | 0.305828E+10 | 0.139222E+10 | 0.166606E+10 | 0.348998E+10 | 0.262630E+10 |
April | 0.357895E+10 | 0.163191E+10 | 0.194704E+10 | 0.490956E+10 | 0.211351E+10 |
May | 0.406096E+10 | 0.171732E+10 | 0.234364E+10 | 0.614515E+10 | 0.150754E+10 |
June | 0.406883E+10 | 0.170535E+10 | 0.236348E+10 | 0.700739E+10 | 0.947396E+09 |
July | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.728110E+10 | 0.724064E+09 |
August | 0.374970E+10 | 0.148764E+10 | 0.226206E+10 | 0.678631E+10 | 0.595171E+09 |
September | 0.298233E+10 | 0.132139E+10 | 0.166094E+10 | 0.470073E+10 | 0.121107E+10 |
October | 0.262899E+10 | 0.136793E+10 | 0.126106E+10 | 0.339259E+10 | 0.240026E+10 |
November | 0.203409E+10 | 0.921030E+09 | 0.111306E+10 | 0.210371E+10 | 0.300272E+10 |
December | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.146448E+10 | 0.379981E+10 |
Annual Sum or Average | 0.362061E+11 | 0.161476E+11 | 0.200585E+11 | 0.508850E+11 | 0.272920E+11 |
Minimum of Months | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.142956E+10 | 0.595171E+09 |
Maximum of Months | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.728110E+10 | 0.476290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.704351E+10 | 0.491071E+10 | 0.213280E+10 | 0.808406E+10 | 0.685659E+10 |
February | 0.593776E+10 | 0.398025E+10 | 0.195752E+10 | 0.737544E+10 | 0.538950E+10 |
March | 0.591221E+10 | 0.308109E+10 | 0.283111E+10 | 0.792096E+10 | 0.420910E+10 |
April | 0.428501E+10 | 0.139486E+10 | 0.289015E+10 | 0.635604E+10 | 0.343889E+10 |
May | 0.357752E+10 | 0.415805E+09 | 0.316172E+10 | 0.558390E+10 | 0.238327E+10 |
June | 0.320109E+10 | 0.178128E+09 | 0.302296E+10 | 0.593071E+10 | 0.147507E+10 |
July | 0.334411E+10 | 0.249356E+09 | 0.309476E+10 | 0.649193E+10 | 0.109583E+10 |
August | 0.399264E+10 | 0.745838E+09 | 0.324680E+10 | 0.791366E+10 | 0.923966E+09 |
September | 0.424927E+10 | 0.158051E+10 | 0.266877E+10 | 0.719638E+10 | 0.192568E+10 |
October | 0.636558E+10 | 0.412363E+10 | 0.224195E+10 | 0.936939E+10 | 0.383176E+10 |
November | 0.662730E+10 | 0.439777E+10 | 0.222953E+10 | 0.883167E+10 | 0.475462E+10 |
December | 0.694295E+10 | 0.488442E+10 | 0.205853E+10 | 0.850001E+10 | 0.576022E+10 |
Annual Sum or Average | 0.614790E+11 | 0.299424E+11 | 0.315366E+11 | 0.895542E+11 | 0.420445E+11 |
Minimum of Months | 0.320109E+10 | 0.178128E+09 | 0.195752E+10 | 0.558390E+10 | 0.923966E+09 |
Maximum of Months | 0.704351E+10 | 0.491071E+10 | 0.324680E+10 | 0.936939E+10 | 0.685659E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198052E+10 | 0.918704E+09 | 0.106182E+10 | 0.159335E+10 | 0.510959E+10 |
February | 0.205360E+10 | 0.960180E+09 | 0.109341E+10 | 0.210625E+10 | 0.395848E+10 |
March | 0.335119E+10 | 0.161937E+10 | 0.173182E+10 | 0.410971E+10 | 0.295877E+10 |
April | 0.364841E+10 | 0.166950E+10 | 0.197891E+10 | 0.511278E+10 | 0.239302E+10 |
May | 0.378899E+10 | 0.143550E+10 | 0.235349E+10 | 0.582662E+10 | 0.169024E+10 |
June | 0.385608E+10 | 0.148342E+10 | 0.237266E+10 | 0.668963E+10 | 0.108682E+10 |
July | 0.375841E+10 | 0.139349E+10 | 0.236492E+10 | 0.674287E+10 | 0.826891E+09 |
August | 0.368270E+10 | 0.137718E+10 | 0.230552E+10 | 0.668589E+10 | 0.716628E+09 |
September | 0.290361E+10 | 0.120948E+10 | 0.169413E+10 | 0.459966E+10 | 0.134046E+10 |
October | 0.267300E+10 | 0.138758E+10 | 0.128542E+10 | 0.361493E+10 | 0.271121E+10 |
November | 0.206443E+10 | 0.926622E+09 | 0.113781E+10 | 0.233196E+10 | 0.343015E+10 |
December | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.152718E+10 | 0.428226E+10 |
Annual Sum or Average | 0.355208E+11 | 0.151508E+11 | 0.203700E+11 | 0.509408E+11 | 0.305045E+11 |
Minimum of Months | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.152718E+10 | 0.716628E+09 |
Maximum of Months | 0.385608E+10 | 0.166950E+10 | 0.237266E+10 | 0.674287E+10 | 0.510959E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 48.41 | 3584.46 | 491.72 | 0.00 | 491.72 | 0.00 | 0.00 |
February | 189.88 | 2963.39 | 545.02 | 0.00 | 545.02 | 0.00 | 0.00 |
March | 472.80 | 1879.89 | 765.18 | 0.00 | 765.18 | 0.00 | 0.00 |
April | 975.67 | 1433.52 | 925.55 | 4.11 | 921.45 | 0.00 | 0.00 |
May | 1542.09 | 881.15 | 1106.94 | 35.33 | 1071.62 | 0.00 | 0.00 |
June | 2201.33 | 540.90 | 1218.24 | 80.43 | 1137.81 | 0.00 | 0.00 |
July | 2197.47 | 380.15 | 1149.41 | 55.87 | 1093.54 | 0.00 | 0.00 |
August | 1998.26 | 315.56 | 1022.21 | 11.14 | 1011.08 | 0.00 | 0.00 |
September | 1141.79 | 772.28 | 772.70 | 0.11 | 772.59 | 0.00 | 0.00 |
October | 477.41 | 1716.07 | 587.51 | 0.00 | 587.51 | 0.00 | 0.00 |
November | 209.72 | 2394.93 | 525.80 | 0.00 | 525.80 | 0.00 | 0.00 |
December | 41.92 | 3115.50 | 454.55 | 0.00 | 454.55 | 0.00 | 0.00 |
Annual Sum or Average | 962.47 | 1658.30 | 798.44 | 15.65 | 782.80 | 0.00 | 0.00 |
Minimum of Months | 41.92 | 315.56 | 454.55 | 0.00 | 454.55 | 0.00 | 0.00 |
Maximum of Months | 2201.33 | 3584.46 | 1218.24 | 80.43 | 1137.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 469.36 | 2140.27 | 719.91 | 324.71 | 395.19 | 0.00 | 0.00 |
February | 845.87 | 1761.23 | 907.58 | 487.63 | 419.94 | 0.00 | 0.00 |
March | 1273.15 | 1122.51 | 1141.84 | 519.80 | 622.04 | 0.00 | 0.00 |
April | 1897.80 | 870.11 | 1380.77 | 629.60 | 751.18 | 0.00 | 0.00 |
May | 2326.12 | 576.69 | 1516.19 | 641.18 | 875.02 | 0.00 | 0.00 |
June | 2743.82 | 353.53 | 1569.77 | 657.93 | 911.84 | 0.00 | 0.00 |
July | 2765.31 | 243.42 | 1530.59 | 643.48 | 887.11 | 0.00 | 0.00 |
August | 2576.08 | 191.64 | 1399.98 | 555.42 | 844.56 | 0.00 | 0.00 |
September | 1830.51 | 491.75 | 1150.60 | 509.80 | 640.80 | 0.00 | 0.00 |
October | 1240.99 | 1039.91 | 981.56 | 510.73 | 470.83 | 0.00 | 0.00 |
November | 731.93 | 1404.24 | 784.76 | 355.34 | 429.42 | 0.00 | 0.00 |
December | 470.79 | 1807.51 | 679.76 | 309.86 | 369.90 | 0.00 | 0.00 |
Annual Sum or Average | 1601.59 | 996.40 | 1148.09 | 512.04 | 636.05 | 0.00 | 0.00 |
Minimum of Months | 469.36 | 191.64 | 679.76 | 309.86 | 369.90 | 0.00 | 0.00 |
Maximum of Months | 2765.31 | 2140.27 | 1569.77 | 657.93 | 911.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2953.29 | 2903.19 | 2629.75 | 1833.46 | 796.30 | 0.00 | 0.00 |
February | 3008.17 | 2523.32 | 2454.44 | 1645.28 | 809.16 | 0.00 | 0.00 |
March | 2945.25 | 1760.59 | 2207.37 | 1150.35 | 1057.02 | 0.00 | 0.00 |
April | 2447.63 | 1445.46 | 1653.17 | 538.14 | 1115.03 | 0.00 | 0.00 |
May | 2103.23 | 931.04 | 1335.70 | 155.24 | 1180.45 | 0.00 | 0.00 |
June | 2306.90 | 578.66 | 1234.99 | 68.72 | 1166.27 | 0.00 | 0.00 |
July | 2447.56 | 399.42 | 1248.55 | 93.10 | 1155.45 | 0.00 | 0.00 |
August | 2978.86 | 335.35 | 1490.68 | 278.47 | 1212.22 | 0.00 | 0.00 |
September | 2799.22 | 783.68 | 1639.39 | 609.77 | 1029.62 | 0.00 | 0.00 |
October | 3498.75 | 1601.61 | 2376.64 | 1539.59 | 837.05 | 0.00 | 0.00 |
November | 3356.53 | 2100.15 | 2556.84 | 1696.68 | 860.16 | 0.00 | 0.00 |
December | 3092.43 | 2557.98 | 2592.21 | 1823.64 | 768.57 | 0.00 | 0.00 |
Annual Sum or Average | 2827.77 | 1487.82 | 1949.49 | 949.47 | 1000.02 | 0.00 | 0.00 |
Minimum of Months | 2103.23 | 335.35 | 1234.99 | 68.72 | 768.57 | 0.00 | 0.00 |
Maximum of Months | 3498.75 | 2903.19 | 2629.75 | 1833.46 | 1212.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 533.61 | 2349.89 | 739.44 | 343.01 | 396.44 | 0.00 | 0.00 |
February | 807.75 | 2053.41 | 848.88 | 396.90 | 451.98 | 0.00 | 0.00 |
March | 1477.60 | 1386.59 | 1251.20 | 604.61 | 646.59 | 0.00 | 0.00 |
April | 1920.20 | 1122.75 | 1407.57 | 644.10 | 763.47 | 0.00 | 0.00 |
May | 2176.49 | 693.46 | 1414.65 | 535.96 | 878.70 | 0.00 | 0.00 |
June | 2578.93 | 472.83 | 1487.69 | 572.31 | 915.38 | 0.00 | 0.00 |
July | 2499.52 | 360.98 | 1403.23 | 520.27 | 882.96 | 0.00 | 0.00 |
August | 2464.82 | 336.24 | 1374.97 | 514.18 | 860.79 | 0.00 | 0.00 |
September | 1766.20 | 591.59 | 1120.22 | 466.62 | 653.60 | 0.00 | 0.00 |
October | 1305.65 | 1263.64 | 997.99 | 518.06 | 479.92 | 0.00 | 0.00 |
November | 814.78 | 1728.59 | 796.47 | 357.49 | 438.97 | 0.00 | 0.00 |
December | 491.06 | 2228.20 | 657.08 | 287.41 | 369.67 | 0.00 | 0.00 |
Annual Sum or Average | 1573.79 | 1211.39 | 1126.36 | 480.43 | 645.93 | 0.00 | 0.00 |
Minimum of Months | 491.06 | 336.24 | 657.08 | 287.41 | 369.67 | 0.00 | 0.00 |
Maximum of Months | 2578.93 | 2349.89 | 1487.69 | 644.10 | 915.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 75.46 | 3136.11 | 491.71 | 0.00 | 491.71 | 0.00 | 0.00 |
February | 239.60 | 2590.94 | 545.02 | 0.00 | 545.02 | 0.00 | 0.00 |
March | 532.13 | 1659.40 | 765.17 | 0.00 | 765.17 | 0.00 | 0.00 |
April | 1020.45 | 1316.83 | 925.55 | 4.11 | 921.44 | 0.00 | 0.00 |
May | 1555.11 | 842.87 | 1106.94 | 35.33 | 1071.61 | 0.00 | 0.00 |
June | 2213.54 | 525.88 | 1218.24 | 80.43 | 1137.80 | 0.00 | 0.00 |
July | 2209.25 | 378.94 | 1149.41 | 55.87 | 1093.53 | 0.00 | 0.00 |
August | 2021.54 | 307.42 | 1022.21 | 11.14 | 1011.07 | 0.00 | 0.00 |
September | 1160.19 | 721.11 | 772.69 | 0.11 | 772.59 | 0.00 | 0.00 |
October | 529.26 | 1514.28 | 587.50 | 0.00 | 587.50 | 0.00 | 0.00 |
November | 279.00 | 2070.37 | 525.80 | 0.00 | 525.80 | 0.00 | 0.00 |
December | 79.90 | 2585.44 | 454.55 | 0.00 | 454.55 | 0.00 | 0.00 |
Annual Sum or Average | 997.22 | 1465.01 | 798.44 | 15.65 | 782.79 | 0.00 | 0.00 |
Minimum of Months | 75.46 | 307.42 | 454.55 | 0.00 | 454.55 | 0.00 | 0.00 |
Maximum of Months | 2213.54 | 3136.11 | 1218.24 | 80.43 | 1137.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 505.31 | 1890.86 | 719.90 | 324.71 | 395.19 | 0.00 | 0.00 |
February | 871.08 | 1585.13 | 907.57 | 487.63 | 419.94 | 0.00 | 0.00 |
March | 1273.34 | 1050.43 | 1141.83 | 519.79 | 622.04 | 0.00 | 0.00 |
April | 1881.21 | 848.63 | 1380.77 | 629.59 | 751.17 | 0.00 | 0.00 |
May | 2298.41 | 569.59 | 1516.19 | 641.17 | 875.01 | 0.00 | 0.00 |
June | 2715.31 | 361.38 | 1569.76 | 657.93 | 911.84 | 0.00 | 0.00 |
July | 2733.55 | 263.97 | 1530.58 | 643.48 | 887.10 | 0.00 | 0.00 |
August | 2547.52 | 214.79 | 1399.98 | 555.42 | 844.56 | 0.00 | 0.00 |
September | 1813.64 | 479.23 | 1150.59 | 509.80 | 640.79 | 0.00 | 0.00 |
October | 1241.97 | 964.98 | 981.55 | 510.73 | 470.83 | 0.00 | 0.00 |
November | 759.29 | 1278.57 | 784.76 | 355.34 | 429.42 | 0.00 | 0.00 |
December | 507.04 | 1571.20 | 679.75 | 309.86 | 369.90 | 0.00 | 0.00 |
Annual Sum or Average | 1599.44 | 919.78 | 1148.09 | 512.04 | 636.05 | 0.00 | 0.00 |
Minimum of Months | 505.31 | 214.79 | 679.75 | 309.86 | 369.90 | 0.00 | 0.00 |
Maximum of Months | 2733.55 | 1890.86 | 1569.76 | 657.93 | 911.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2963.32 | 2736.80 | 2629.75 | 1833.45 | 796.30 | 0.00 | 0.00 |
February | 3008.89 | 2375.51 | 2454.43 | 1645.27 | 809.16 | 0.00 | 0.00 |
March | 2931.02 | 1676.00 | 2207.36 | 1150.35 | 1057.02 | 0.00 | 0.00 |
April | 2444.48 | 1385.12 | 1653.17 | 538.14 | 1115.03 | 0.00 | 0.00 |
May | 2099.20 | 904.44 | 1335.69 | 155.24 | 1180.45 | 0.00 | 0.00 |
June | 2314.22 | 563.83 | 1234.99 | 68.72 | 1166.27 | 0.00 | 0.00 |
July | 2454.79 | 398.40 | 1248.55 | 93.10 | 1155.45 | 0.00 | 0.00 |
August | 2985.16 | 332.43 | 1490.68 | 278.46 | 1212.22 | 0.00 | 0.00 |
September | 2787.35 | 760.56 | 1639.38 | 609.76 | 1029.62 | 0.00 | 0.00 |
October | 3479.13 | 1531.11 | 2376.63 | 1539.59 | 837.05 | 0.00 | 0.00 |
November | 3351.33 | 1996.12 | 2556.83 | 1696.67 | 860.16 | 0.00 | 0.00 |
December | 3109.48 | 2363.67 | 2592.20 | 1823.63 | 768.57 | 0.00 | 0.00 |
Annual Sum or Average | 2827.00 | 1413.46 | 1949.48 | 949.47 | 1000.02 | 0.00 | 0.00 |
Minimum of Months | 2099.20 | 332.43 | 1234.99 | 68.72 | 768.57 | 0.00 | 0.00 |
Maximum of Months | 3479.13 | 2736.80 | 2629.75 | 1833.45 | 1212.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 577.48 | 2024.91 | 739.44 | 343.00 | 396.44 | 0.00 | 0.00 |
February | 858.19 | 1728.74 | 848.87 | 396.90 | 451.97 | 0.00 | 0.00 |
March | 1522.45 | 1175.14 | 1251.19 | 604.60 | 646.59 | 0.00 | 0.00 |
April | 1971.36 | 960.44 | 1407.57 | 644.10 | 763.47 | 0.00 | 0.00 |
May | 2187.55 | 641.22 | 1414.65 | 535.95 | 878.69 | 0.00 | 0.00 |
June | 2601.07 | 417.78 | 1487.69 | 572.31 | 915.38 | 0.00 | 0.00 |
July | 2537.95 | 303.27 | 1403.23 | 520.27 | 882.96 | 0.00 | 0.00 |
August | 2515.82 | 260.67 | 1374.96 | 514.18 | 860.78 | 0.00 | 0.00 |
September | 1782.74 | 529.41 | 1120.22 | 466.62 | 653.60 | 0.00 | 0.00 |
October | 1339.99 | 1081.43 | 997.98 | 518.06 | 479.92 | 0.00 | 0.00 |
November | 874.71 | 1431.50 | 796.46 | 357.49 | 438.97 | 0.00 | 0.00 |
December | 550.85 | 1734.99 | 657.08 | 287.41 | 369.67 | 0.00 | 0.00 |
Annual Sum or Average | 1614.03 | 1020.41 | 1126.36 | 480.43 | 645.93 | 0.00 | 0.00 |
Minimum of Months | 550.85 | 260.67 | 657.08 | 287.41 | 369.67 | 0.00 | 0.00 |
Maximum of Months | 2601.07 | 2024.91 | 1487.69 | 644.10 | 915.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 90.28 | 2960.56 | 491.71 | 0.00 | 491.71 | 0.00 | 0.00 |
February | 259.63 | 2438.31 | 545.02 | 0.00 | 545.02 | 0.00 | 0.00 |
March | 565.98 | 1536.55 | 765.17 | 0.00 | 765.17 | 0.00 | 0.00 |
April | 1036.86 | 1254.22 | 925.55 | 4.11 | 921.44 | 0.00 | 0.00 |
May | 1544.11 | 828.95 | 1106.94 | 35.33 | 1071.61 | 0.00 | 0.00 |
June | 2187.40 | 531.93 | 1218.24 | 80.43 | 1137.80 | 0.00 | 0.00 |
July | 2178.11 | 389.77 | 1149.41 | 55.87 | 1093.53 | 0.00 | 0.00 |
August | 1992.20 | 319.85 | 1022.21 | 11.14 | 1011.07 | 0.00 | 0.00 |
September | 1153.51 | 700.28 | 772.69 | 0.11 | 772.59 | 0.00 | 0.00 |
October | 558.04 | 1393.29 | 587.50 | 0.00 | 587.50 | 0.00 | 0.00 |
November | 326.25 | 1876.50 | 525.80 | 0.00 | 525.80 | 0.00 | 0.00 |
December | 101.61 | 2353.37 | 454.55 | 0.00 | 454.55 | 0.00 | 0.00 |
Annual Sum or Average | 1003.64 | 1376.47 | 798.44 | 15.65 | 782.79 | 0.00 | 0.00 |
Minimum of Months | 90.28 | 319.85 | 454.55 | 0.00 | 454.55 | 0.00 | 0.00 |
Maximum of Months | 2187.40 | 2960.56 | 1218.24 | 80.43 | 1137.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 533.74 | 1778.26 | 719.90 | 324.71 | 395.19 | 0.00 | 0.00 |
February | 898.82 | 1488.60 | 907.57 | 487.63 | 419.94 | 0.00 | 0.00 |
March | 1303.01 | 980.55 | 1141.83 | 519.79 | 622.04 | 0.00 | 0.00 |
April | 1894.12 | 815.40 | 1380.77 | 629.59 | 751.17 | 0.00 | 0.00 |
May | 2294.34 | 562.85 | 1516.19 | 641.17 | 875.01 | 0.00 | 0.00 |
June | 2703.47 | 365.51 | 1569.76 | 657.93 | 911.84 | 0.00 | 0.00 |
July | 2718.45 | 270.33 | 1530.58 | 643.48 | 887.10 | 0.00 | 0.00 |
August | 2533.72 | 222.21 | 1399.98 | 555.42 | 844.56 | 0.00 | 0.00 |
September | 1813.55 | 467.23 | 1150.59 | 509.80 | 640.79 | 0.00 | 0.00 |
October | 1266.65 | 896.15 | 981.55 | 510.73 | 470.83 | 0.00 | 0.00 |
November | 811.62 | 1158.46 | 784.76 | 355.34 | 429.42 | 0.00 | 0.00 |
December | 546.77 | 1418.69 | 679.75 | 309.86 | 369.90 | 0.00 | 0.00 |
Annual Sum or Average | 1613.55 | 865.42 | 1148.09 | 512.04 | 636.05 | 0.00 | 0.00 |
Minimum of Months | 533.74 | 222.21 | 679.75 | 309.86 | 369.90 | 0.00 | 0.00 |
Maximum of Months | 2718.45 | 1778.26 | 1569.76 | 657.93 | 911.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3018.24 | 2559.96 | 2629.75 | 1833.45 | 796.30 | 0.00 | 0.00 |
February | 3048.71 | 2227.80 | 2454.43 | 1645.27 | 809.16 | 0.00 | 0.00 |
March | 2957.35 | 1571.50 | 2207.36 | 1150.35 | 1057.02 | 0.00 | 0.00 |
April | 2452.17 | 1326.73 | 1653.17 | 538.14 | 1115.03 | 0.00 | 0.00 |
May | 2084.79 | 889.81 | 1335.69 | 155.24 | 1180.45 | 0.00 | 0.00 |
June | 2288.08 | 569.08 | 1234.99 | 68.72 | 1166.27 | 0.00 | 0.00 |
July | 2423.81 | 409.14 | 1248.55 | 93.10 | 1155.45 | 0.00 | 0.00 |
August | 2954.62 | 344.97 | 1490.68 | 278.46 | 1212.22 | 0.00 | 0.00 |
September | 2776.38 | 742.93 | 1639.38 | 609.76 | 1029.62 | 0.00 | 0.00 |
October | 3498.13 | 1430.62 | 2376.63 | 1539.59 | 837.05 | 0.00 | 0.00 |
November | 3407.28 | 1834.34 | 2556.83 | 1696.67 | 860.16 | 0.00 | 0.00 |
December | 3173.54 | 2150.62 | 2592.20 | 1823.63 | 768.57 | 0.00 | 0.00 |
Annual Sum or Average | 2839.74 | 1333.22 | 1949.48 | 949.47 | 1000.02 | 0.00 | 0.00 |
Minimum of Months | 2084.79 | 344.97 | 1234.99 | 68.72 | 768.57 | 0.00 | 0.00 |
Maximum of Months | 3498.13 | 2559.96 | 2629.75 | 1833.45 | 1212.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 594.89 | 1907.70 | 739.44 | 343.00 | 396.44 | 0.00 | 0.00 |
February | 870.64 | 1636.28 | 848.87 | 396.90 | 451.97 | 0.00 | 0.00 |
March | 1534.39 | 1104.68 | 1251.19 | 604.60 | 646.59 | 0.00 | 0.00 |
April | 1972.52 | 923.23 | 1407.57 | 644.10 | 763.47 | 0.00 | 0.00 |
May | 2175.41 | 631.06 | 1414.65 | 535.95 | 878.69 | 0.00 | 0.00 |
June | 2580.88 | 419.30 | 1487.69 | 572.31 | 915.38 | 0.00 | 0.00 |
July | 2517.50 | 308.73 | 1403.23 | 520.27 | 882.96 | 0.00 | 0.00 |
August | 2496.23 | 267.56 | 1374.96 | 514.18 | 860.78 | 0.00 | 0.00 |
September | 1774.56 | 517.15 | 1120.22 | 466.62 | 653.60 | 0.00 | 0.00 |
October | 1349.66 | 1012.25 | 997.98 | 518.06 | 479.92 | 0.00 | 0.00 |
November | 899.68 | 1323.36 | 796.46 | 357.49 | 438.97 | 0.00 | 0.00 |
December | 570.18 | 1598.81 | 657.08 | 287.41 | 369.67 | 0.00 | 0.00 |
Annual Sum or Average | 1615.32 | 967.29 | 1126.36 | 480.43 | 645.93 | 0.00 | 0.00 |
Minimum of Months | 570.18 | 267.56 | 657.08 | 287.41 | 369.67 | 0.00 | 0.00 |
Maximum of Months | 2580.88 | 1907.70 | 1487.69 | 644.10 | 915.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129661E+09 | 0.960061E+10 | 0.131701E+10 | 0.00 | 0.131701E+10 | 0.00 | 0.00 |
February | 0.459366E+09 | 0.716904E+10 | 0.131851E+10 | 0.00 | 0.131851E+10 | 0.00 | 0.00 |
March | 0.126636E+10 | 0.503510E+10 | 0.204945E+10 | 0.00 | 0.204945E+10 | 0.00 | 0.00 |
April | 0.252894E+10 | 0.371569E+10 | 0.239903E+10 | 10640389.76 | 0.238839E+10 | 0.00 | 0.00 |
May | 0.413033E+10 | 0.236008E+10 | 0.296484E+10 | 94621435.77 | 0.287022E+10 | 0.00 | 0.00 |
June | 0.570585E+10 | 0.140202E+10 | 0.315768E+10 | 0.208481E+09 | 0.294920E+10 | 0.00 | 0.00 |
July | 0.588570E+10 | 0.101819E+10 | 0.307859E+10 | 0.149652E+09 | 0.292893E+10 | 0.00 | 0.00 |
August | 0.535214E+10 | 0.845196E+09 | 0.273790E+10 | 29825092.99 | 0.270807E+10 | 0.00 | 0.00 |
September | 0.295953E+10 | 0.200174E+10 | 0.200283E+10 | 281942.69 | 0.200255E+10 | 0.00 | 0.00 |
October | 0.127869E+10 | 0.459632E+10 | 0.157358E+10 | 0.00 | 0.157358E+10 | 0.00 | 0.00 |
November | 0.543602E+09 | 0.620766E+10 | 0.136287E+10 | 0.00 | 0.136287E+10 | 0.00 | 0.00 |
December | 0.112270E+09 | 0.834455E+10 | 0.121748E+10 | 0.00 | 0.121748E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.303524E+11 | 0.522962E+11 | 0.251797E+11 | 0.493503E+09 | 0.246862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112270E+09 | 0.845196E+09 | 0.121748E+10 | 0.00 | 0.121748E+10 | 0.00 | 0.00 |
Maximum of Months | 0.588570E+10 | 0.960061E+10 | 0.315768E+10 | 0.208481E+09 | 0.294920E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125712E+10 | 0.573249E+10 | 0.192820E+10 | 0.869715E+09 | 0.105848E+10 | 0.00 | 0.00 |
February | 0.204632E+10 | 0.426078E+10 | 0.219561E+10 | 0.117968E+10 | 0.101592E+10 | 0.00 | 0.00 |
March | 0.341000E+10 | 0.300653E+10 | 0.305829E+10 | 0.139222E+10 | 0.166607E+10 | 0.00 | 0.00 |
April | 0.491910E+10 | 0.225532E+10 | 0.357897E+10 | 0.163192E+10 | 0.194705E+10 | 0.00 | 0.00 |
May | 0.623028E+10 | 0.154462E+10 | 0.406097E+10 | 0.171733E+10 | 0.234365E+10 | 0.00 | 0.00 |
June | 0.711197E+10 | 0.916361E+09 | 0.406884E+10 | 0.170535E+10 | 0.236349E+10 | 0.00 | 0.00 |
July | 0.740661E+10 | 0.651969E+09 | 0.409953E+10 | 0.172350E+10 | 0.237603E+10 | 0.00 | 0.00 |
August | 0.689978E+10 | 0.513295E+09 | 0.374972E+10 | 0.148765E+10 | 0.226207E+10 | 0.00 | 0.00 |
September | 0.474467E+10 | 0.127462E+10 | 0.298234E+10 | 0.132140E+10 | 0.166094E+10 | 0.00 | 0.00 |
October | 0.332387E+10 | 0.278529E+10 | 0.262900E+10 | 0.136793E+10 | 0.126107E+10 | 0.00 | 0.00 |
November | 0.189715E+10 | 0.363980E+10 | 0.203410E+10 | 0.921034E+09 | 0.111307E+10 | 0.00 | 0.00 |
December | 0.126098E+10 | 0.484124E+10 | 0.182066E+10 | 0.829926E+09 | 0.990731E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.505079E+11 | 0.314223E+11 | 0.362062E+11 | 0.161477E+11 | 0.200586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125712E+10 | 0.513295E+09 | 0.182066E+10 | 0.829926E+09 | 0.990731E+09 | 0.00 | 0.00 |
Maximum of Months | 0.740661E+10 | 0.573249E+10 | 0.409953E+10 | 0.172350E+10 | 0.237603E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791009E+10 | 0.777591E+10 | 0.704353E+10 | 0.491073E+10 | 0.213281E+10 | 0.00 | 0.00 |
February | 0.727736E+10 | 0.610440E+10 | 0.593778E+10 | 0.398026E+10 | 0.195752E+10 | 0.00 | 0.00 |
March | 0.788855E+10 | 0.471556E+10 | 0.591223E+10 | 0.308110E+10 | 0.283112E+10 | 0.00 | 0.00 |
April | 0.634425E+10 | 0.374663E+10 | 0.428503E+10 | 0.139487E+10 | 0.289016E+10 | 0.00 | 0.00 |
May | 0.563329E+10 | 0.249369E+10 | 0.357753E+10 | 0.415806E+09 | 0.316173E+10 | 0.00 | 0.00 |
June | 0.597947E+10 | 0.149988E+10 | 0.320110E+10 | 0.178129E+09 | 0.302297E+10 | 0.00 | 0.00 |
July | 0.655554E+10 | 0.106980E+10 | 0.334413E+10 | 0.249357E+09 | 0.309477E+10 | 0.00 | 0.00 |
August | 0.797858E+10 | 0.898200E+09 | 0.399265E+10 | 0.745841E+09 | 0.324681E+10 | 0.00 | 0.00 |
September | 0.725558E+10 | 0.203130E+10 | 0.424929E+10 | 0.158051E+10 | 0.266877E+10 | 0.00 | 0.00 |
October | 0.937104E+10 | 0.428974E+10 | 0.636560E+10 | 0.412364E+10 | 0.224196E+10 | 0.00 | 0.00 |
November | 0.870012E+10 | 0.544360E+10 | 0.662733E+10 | 0.439778E+10 | 0.222954E+10 | 0.00 | 0.00 |
December | 0.828276E+10 | 0.685129E+10 | 0.694298E+10 | 0.488444E+10 | 0.205854E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.891766E+11 | 0.469200E+11 | 0.614792E+11 | 0.299425E+11 | 0.315367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.563329E+10 | 0.898200E+09 | 0.320110E+10 | 0.178129E+09 | 0.195752E+10 | 0.00 | 0.00 |
Maximum of Months | 0.937104E+10 | 0.777591E+10 | 0.704353E+10 | 0.491073E+10 | 0.324681E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142923E+10 | 0.629395E+10 | 0.198053E+10 | 0.918708E+09 | 0.106182E+10 | 0.00 | 0.00 |
February | 0.195412E+10 | 0.496762E+10 | 0.205360E+10 | 0.960184E+09 | 0.109342E+10 | 0.00 | 0.00 |
March | 0.395760E+10 | 0.371383E+10 | 0.335120E+10 | 0.161938E+10 | 0.173183E+10 | 0.00 | 0.00 |
April | 0.497716E+10 | 0.291017E+10 | 0.364843E+10 | 0.166951E+10 | 0.197892E+10 | 0.00 | 0.00 |
May | 0.582951E+10 | 0.185736E+10 | 0.378901E+10 | 0.143550E+10 | 0.235350E+10 | 0.00 | 0.00 |
June | 0.668459E+10 | 0.122558E+10 | 0.385610E+10 | 0.148342E+10 | 0.237267E+10 | 0.00 | 0.00 |
July | 0.669471E+10 | 0.966846E+09 | 0.375842E+10 | 0.139350E+10 | 0.236493E+10 | 0.00 | 0.00 |
August | 0.660176E+10 | 0.900586E+09 | 0.368272E+10 | 0.137719E+10 | 0.230553E+10 | 0.00 | 0.00 |
September | 0.457800E+10 | 0.153340E+10 | 0.290362E+10 | 0.120949E+10 | 0.169414E+10 | 0.00 | 0.00 |
October | 0.349706E+10 | 0.338454E+10 | 0.267301E+10 | 0.138758E+10 | 0.128542E+10 | 0.00 | 0.00 |
November | 0.211192E+10 | 0.448051E+10 | 0.206444E+10 | 0.926626E+09 | 0.113781E+10 | 0.00 | 0.00 |
December | 0.131526E+10 | 0.596800E+10 | 0.175992E+10 | 0.769791E+09 | 0.990128E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.496309E+11 | 0.382024E+11 | 0.355210E+11 | 0.151509E+11 | 0.203701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131526E+10 | 0.900586E+09 | 0.175992E+10 | 0.769791E+09 | 0.990128E+09 | 0.00 | 0.00 |
Maximum of Months | 0.669471E+10 | 0.629395E+10 | 0.385610E+10 | 0.166951E+10 | 0.237267E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202099E+09 | 0.839974E+10 | 0.131700E+10 | 0.00 | 0.131700E+10 | 0.00 | 0.00 |
February | 0.579637E+09 | 0.626801E+10 | 0.131850E+10 | 0.00 | 0.131850E+10 | 0.00 | 0.00 |
March | 0.142525E+10 | 0.444455E+10 | 0.204944E+10 | 0.00 | 0.204944E+10 | 0.00 | 0.00 |
April | 0.264500E+10 | 0.341322E+10 | 0.239902E+10 | 10640351.98 | 0.238838E+10 | 0.00 | 0.00 |
May | 0.416521E+10 | 0.225755E+10 | 0.296483E+10 | 94621099.77 | 0.287021E+10 | 0.00 | 0.00 |
June | 0.573749E+10 | 0.136308E+10 | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.00 | 0.00 |
July | 0.591725E+10 | 0.101495E+10 | 0.307858E+10 | 0.149652E+09 | 0.292892E+10 | 0.00 | 0.00 |
August | 0.541450E+10 | 0.823387E+09 | 0.273789E+10 | 29824987.08 | 0.270806E+10 | 0.00 | 0.00 |
September | 0.300721E+10 | 0.186912E+10 | 0.200282E+10 | 281941.69 | 0.200254E+10 | 0.00 | 0.00 |
October | 0.141756E+10 | 0.405585E+10 | 0.157357E+10 | 0.00 | 0.157357E+10 | 0.00 | 0.00 |
November | 0.723173E+09 | 0.536639E+10 | 0.136286E+10 | 0.00 | 0.136286E+10 | 0.00 | 0.00 |
December | 0.214000E+09 | 0.692485E+10 | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.314484E+11 | 0.462007E+11 | 0.251797E+11 | 0.493501E+09 | 0.246862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202099E+09 | 0.823387E+09 | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.00 | 0.00 |
Maximum of Months | 0.591725E+10 | 0.839974E+10 | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135343E+10 | 0.506448E+10 | 0.192819E+10 | 0.869711E+09 | 0.105848E+10 | 0.00 | 0.00 |
February | 0.210731E+10 | 0.383475E+10 | 0.219560E+10 | 0.117968E+10 | 0.101592E+10 | 0.00 | 0.00 |
March | 0.341052E+10 | 0.281347E+10 | 0.305828E+10 | 0.139222E+10 | 0.166606E+10 | 0.00 | 0.00 |
April | 0.487609E+10 | 0.219964E+10 | 0.357895E+10 | 0.163191E+10 | 0.194704E+10 | 0.00 | 0.00 |
May | 0.615606E+10 | 0.152560E+10 | 0.406096E+10 | 0.171732E+10 | 0.234364E+10 | 0.00 | 0.00 |
June | 0.703809E+10 | 0.936690E+09 | 0.406883E+10 | 0.170535E+10 | 0.236348E+10 | 0.00 | 0.00 |
July | 0.732155E+10 | 0.707007E+09 | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.00 | 0.00 |
August | 0.682328E+10 | 0.575281E+09 | 0.374970E+10 | 0.148764E+10 | 0.226206E+10 | 0.00 | 0.00 |
September | 0.470094E+10 | 0.124217E+10 | 0.298233E+10 | 0.132139E+10 | 0.166094E+10 | 0.00 | 0.00 |
October | 0.332649E+10 | 0.258462E+10 | 0.262899E+10 | 0.136793E+10 | 0.126106E+10 | 0.00 | 0.00 |
November | 0.196809E+10 | 0.331405E+10 | 0.203409E+10 | 0.921030E+09 | 0.111306E+10 | 0.00 | 0.00 |
December | 0.135806E+10 | 0.420831E+10 | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.504399E+11 | 0.290061E+11 | 0.362061E+11 | 0.161476E+11 | 0.200585E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135343E+10 | 0.575281E+09 | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.00 | 0.00 |
Maximum of Months | 0.732155E+10 | 0.506448E+10 | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.793695E+10 | 0.733025E+10 | 0.704351E+10 | 0.491071E+10 | 0.213280E+10 | 0.00 | 0.00 |
February | 0.727910E+10 | 0.574684E+10 | 0.593776E+10 | 0.398025E+10 | 0.195752E+10 | 0.00 | 0.00 |
March | 0.785044E+10 | 0.448899E+10 | 0.591221E+10 | 0.308109E+10 | 0.283111E+10 | 0.00 | 0.00 |
April | 0.633608E+10 | 0.359024E+10 | 0.428501E+10 | 0.139486E+10 | 0.289015E+10 | 0.00 | 0.00 |
May | 0.562250E+10 | 0.242244E+10 | 0.357752E+10 | 0.415805E+09 | 0.316172E+10 | 0.00 | 0.00 |
June | 0.599845E+10 | 0.146144E+10 | 0.320109E+10 | 0.178128E+09 | 0.302296E+10 | 0.00 | 0.00 |
July | 0.657491E+10 | 0.106708E+10 | 0.334411E+10 | 0.249356E+09 | 0.309476E+10 | 0.00 | 0.00 |
August | 0.799544E+10 | 0.890389E+09 | 0.399264E+10 | 0.745838E+09 | 0.324680E+10 | 0.00 | 0.00 |
September | 0.722482E+10 | 0.197138E+10 | 0.424927E+10 | 0.158051E+10 | 0.266877E+10 | 0.00 | 0.00 |
October | 0.931851E+10 | 0.410093E+10 | 0.636558E+10 | 0.412363E+10 | 0.224195E+10 | 0.00 | 0.00 |
November | 0.868664E+10 | 0.517395E+10 | 0.662730E+10 | 0.439777E+10 | 0.222953E+10 | 0.00 | 0.00 |
December | 0.832843E+10 | 0.633085E+10 | 0.694295E+10 | 0.488442E+10 | 0.205853E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.891523E+11 | 0.445748E+11 | 0.614790E+11 | 0.299424E+11 | 0.315366E+11 | 0.00 | 0.00 |
Minimum of Months | 0.562250E+10 | 0.890389E+09 | 0.320109E+10 | 0.178128E+09 | 0.195752E+10 | 0.00 | 0.00 |
Maximum of Months | 0.931851E+10 | 0.733025E+10 | 0.704351E+10 | 0.491071E+10 | 0.324680E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154671E+10 | 0.542351E+10 | 0.198052E+10 | 0.918704E+09 | 0.106182E+10 | 0.00 | 0.00 |
February | 0.207614E+10 | 0.418216E+10 | 0.205360E+10 | 0.960180E+09 | 0.109341E+10 | 0.00 | 0.00 |
March | 0.407773E+10 | 0.314751E+10 | 0.335119E+10 | 0.161937E+10 | 0.173182E+10 | 0.00 | 0.00 |
April | 0.510976E+10 | 0.248946E+10 | 0.364841E+10 | 0.166950E+10 | 0.197891E+10 | 0.00 | 0.00 |
May | 0.585914E+10 | 0.171744E+10 | 0.378899E+10 | 0.143550E+10 | 0.235349E+10 | 0.00 | 0.00 |
June | 0.674197E+10 | 0.108289E+10 | 0.385608E+10 | 0.148342E+10 | 0.237266E+10 | 0.00 | 0.00 |
July | 0.679766E+10 | 0.812278E+09 | 0.375841E+10 | 0.139349E+10 | 0.236492E+10 | 0.00 | 0.00 |
August | 0.673837E+10 | 0.698170E+09 | 0.368270E+10 | 0.137718E+10 | 0.230552E+10 | 0.00 | 0.00 |
September | 0.462087E+10 | 0.137222E+10 | 0.290361E+10 | 0.120948E+10 | 0.169413E+10 | 0.00 | 0.00 |
October | 0.358904E+10 | 0.289650E+10 | 0.267300E+10 | 0.138758E+10 | 0.128542E+10 | 0.00 | 0.00 |
November | 0.226724E+10 | 0.371045E+10 | 0.206443E+10 | 0.926622E+09 | 0.113781E+10 | 0.00 | 0.00 |
December | 0.147540E+10 | 0.464700E+10 | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.509000E+11 | 0.321796E+11 | 0.355208E+11 | 0.151508E+11 | 0.203700E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147540E+10 | 0.698170E+09 | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.00 | 0.00 |
Maximum of Months | 0.679766E+10 | 0.542351E+10 | 0.385608E+10 | 0.166950E+10 | 0.237266E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241815E+09 | 0.792956E+10 | 0.131700E+10 | 0.00 | 0.131700E+10 | 0.00 | 0.00 |
February | 0.628107E+09 | 0.589876E+10 | 0.131850E+10 | 0.00 | 0.131850E+10 | 0.00 | 0.00 |
March | 0.151592E+10 | 0.411550E+10 | 0.204944E+10 | 0.00 | 0.204944E+10 | 0.00 | 0.00 |
April | 0.268753E+10 | 0.325093E+10 | 0.239902E+10 | 10640351.98 | 0.238838E+10 | 0.00 | 0.00 |
May | 0.413574E+10 | 0.222025E+10 | 0.296483E+10 | 94621099.77 | 0.287021E+10 | 0.00 | 0.00 |
June | 0.566974E+10 | 0.137876E+10 | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.00 | 0.00 |
July | 0.583386E+10 | 0.104397E+10 | 0.307858E+10 | 0.149652E+09 | 0.292892E+10 | 0.00 | 0.00 |
August | 0.533590E+10 | 0.856683E+09 | 0.273789E+10 | 29824987.08 | 0.270806E+10 | 0.00 | 0.00 |
September | 0.298990E+10 | 0.181513E+10 | 0.200282E+10 | 281941.69 | 0.200254E+10 | 0.00 | 0.00 |
October | 0.149465E+10 | 0.373179E+10 | 0.157357E+10 | 0.00 | 0.157357E+10 | 0.00 | 0.00 |
November | 0.845633E+09 | 0.486389E+10 | 0.136286E+10 | 0.00 | 0.136286E+10 | 0.00 | 0.00 |
December | 0.272160E+09 | 0.630326E+10 | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.316509E+11 | 0.434085E+11 | 0.251797E+11 | 0.493501E+09 | 0.246862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241815E+09 | 0.856683E+09 | 0.121747E+10 | 0.00 | 0.121747E+10 | 0.00 | 0.00 |
Maximum of Months | 0.583386E+10 | 0.792956E+10 | 0.315767E+10 | 0.208481E+09 | 0.294919E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142956E+10 | 0.476290E+10 | 0.192819E+10 | 0.869711E+09 | 0.105848E+10 | 0.00 | 0.00 |
February | 0.217441E+10 | 0.360123E+10 | 0.219560E+10 | 0.117968E+10 | 0.101592E+10 | 0.00 | 0.00 |
March | 0.348998E+10 | 0.262630E+10 | 0.305828E+10 | 0.139222E+10 | 0.166606E+10 | 0.00 | 0.00 |
April | 0.490956E+10 | 0.211351E+10 | 0.357895E+10 | 0.163191E+10 | 0.194704E+10 | 0.00 | 0.00 |
May | 0.614515E+10 | 0.150754E+10 | 0.406096E+10 | 0.171732E+10 | 0.234364E+10 | 0.00 | 0.00 |
June | 0.700739E+10 | 0.947396E+09 | 0.406883E+10 | 0.170535E+10 | 0.236348E+10 | 0.00 | 0.00 |
July | 0.728110E+10 | 0.724064E+09 | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.00 | 0.00 |
August | 0.678631E+10 | 0.595171E+09 | 0.374970E+10 | 0.148764E+10 | 0.226206E+10 | 0.00 | 0.00 |
September | 0.470073E+10 | 0.121107E+10 | 0.298233E+10 | 0.132139E+10 | 0.166094E+10 | 0.00 | 0.00 |
October | 0.339259E+10 | 0.240026E+10 | 0.262899E+10 | 0.136793E+10 | 0.126106E+10 | 0.00 | 0.00 |
November | 0.210371E+10 | 0.300272E+10 | 0.203409E+10 | 0.921030E+09 | 0.111306E+10 | 0.00 | 0.00 |
December | 0.146448E+10 | 0.379981E+10 | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.508850E+11 | 0.272920E+11 | 0.362061E+11 | 0.161476E+11 | 0.200585E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142956E+10 | 0.595171E+09 | 0.182065E+10 | 0.829922E+09 | 0.990727E+09 | 0.00 | 0.00 |
Maximum of Months | 0.728110E+10 | 0.476290E+10 | 0.409951E+10 | 0.172349E+10 | 0.237602E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.808406E+10 | 0.685659E+10 | 0.704351E+10 | 0.491071E+10 | 0.213280E+10 | 0.00 | 0.00 |
February | 0.737544E+10 | 0.538950E+10 | 0.593776E+10 | 0.398025E+10 | 0.195752E+10 | 0.00 | 0.00 |
March | 0.792096E+10 | 0.420910E+10 | 0.591221E+10 | 0.308109E+10 | 0.283111E+10 | 0.00 | 0.00 |
April | 0.635604E+10 | 0.343889E+10 | 0.428501E+10 | 0.139486E+10 | 0.289015E+10 | 0.00 | 0.00 |
May | 0.558390E+10 | 0.238327E+10 | 0.357752E+10 | 0.415805E+09 | 0.316172E+10 | 0.00 | 0.00 |
June | 0.593071E+10 | 0.147507E+10 | 0.320109E+10 | 0.178128E+09 | 0.302296E+10 | 0.00 | 0.00 |
July | 0.649193E+10 | 0.109583E+10 | 0.334411E+10 | 0.249356E+09 | 0.309476E+10 | 0.00 | 0.00 |
August | 0.791366E+10 | 0.923966E+09 | 0.399264E+10 | 0.745838E+09 | 0.324680E+10 | 0.00 | 0.00 |
September | 0.719638E+10 | 0.192568E+10 | 0.424927E+10 | 0.158051E+10 | 0.266877E+10 | 0.00 | 0.00 |
October | 0.936939E+10 | 0.383176E+10 | 0.636558E+10 | 0.412363E+10 | 0.224195E+10 | 0.00 | 0.00 |
November | 0.883167E+10 | 0.475462E+10 | 0.662730E+10 | 0.439777E+10 | 0.222953E+10 | 0.00 | 0.00 |
December | 0.850001E+10 | 0.576022E+10 | 0.694295E+10 | 0.488442E+10 | 0.205853E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.895542E+11 | 0.420445E+11 | 0.614790E+11 | 0.299424E+11 | 0.315366E+11 | 0.00 | 0.00 |
Minimum of Months | 0.558390E+10 | 0.923966E+09 | 0.320109E+10 | 0.178128E+09 | 0.195752E+10 | 0.00 | 0.00 |
Maximum of Months | 0.936939E+10 | 0.685659E+10 | 0.704351E+10 | 0.491071E+10 | 0.324680E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159335E+10 | 0.510959E+10 | 0.198052E+10 | 0.918704E+09 | 0.106182E+10 | 0.00 | 0.00 |
February | 0.210625E+10 | 0.395848E+10 | 0.205360E+10 | 0.960180E+09 | 0.109341E+10 | 0.00 | 0.00 |
March | 0.410971E+10 | 0.295877E+10 | 0.335119E+10 | 0.161937E+10 | 0.173182E+10 | 0.00 | 0.00 |
April | 0.511278E+10 | 0.239302E+10 | 0.364841E+10 | 0.166950E+10 | 0.197891E+10 | 0.00 | 0.00 |
May | 0.582662E+10 | 0.169024E+10 | 0.378899E+10 | 0.143550E+10 | 0.235349E+10 | 0.00 | 0.00 |
June | 0.668963E+10 | 0.108682E+10 | 0.385608E+10 | 0.148342E+10 | 0.237266E+10 | 0.00 | 0.00 |
July | 0.674287E+10 | 0.826891E+09 | 0.375841E+10 | 0.139349E+10 | 0.236492E+10 | 0.00 | 0.00 |
August | 0.668589E+10 | 0.716628E+09 | 0.368270E+10 | 0.137718E+10 | 0.230552E+10 | 0.00 | 0.00 |
September | 0.459966E+10 | 0.134046E+10 | 0.290361E+10 | 0.120948E+10 | 0.169413E+10 | 0.00 | 0.00 |
October | 0.361493E+10 | 0.271121E+10 | 0.267300E+10 | 0.138758E+10 | 0.128542E+10 | 0.00 | 0.00 |
November | 0.233196E+10 | 0.343015E+10 | 0.206443E+10 | 0.926622E+09 | 0.113781E+10 | 0.00 | 0.00 |
December | 0.152718E+10 | 0.428226E+10 | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.509408E+11 | 0.305045E+11 | 0.355208E+11 | 0.151508E+11 | 0.203700E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152718E+10 | 0.716628E+09 | 0.175991E+10 | 0.769788E+09 | 0.990124E+09 | 0.00 | 0.00 |
Maximum of Months | 0.674287E+10 | 0.510959E+10 | 0.385608E+10 | 0.166950E+10 | 0.237266E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.370265E+11 | -0.359918E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103474E+10 | 58.98 | 0.00 | 0.00 |
February | 0.337077E+11 | -0.327762E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -931573250.1 | 58.97 | 0.00 | 0.00 |
March | 0.382806E+11 | -0.372505E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103008E+10 | 58.97 | 0.00 | 0.00 |
April | 0.326129E+11 | -0.316185E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -994407823.9 | 58.97 | 0.00 | 0.00 |
May | 0.320816E+11 | -0.310545E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102704E+10 | 58.97 | 0.00 | 0.00 |
June | 0.293181E+11 | -0.283253E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992797775.8 | 58.98 | 0.00 | 0.00 |
July | 0.265565E+11 | -0.255366E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101999E+10 | 58.98 | 0.00 | 0.00 |
August | 0.288975E+11 | -0.278737E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102373E+10 | 58.98 | 0.00 | 0.00 |
September | 0.275035E+11 | -0.265156E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987929491.2 | 58.98 | 0.00 | 0.00 |
October | 0.306285E+11 | -0.296088E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101968E+10 | 58.97 | 0.00 | 0.00 |
November | 0.326225E+11 | -0.316351E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987382526.7 | 58.98 | 0.00 | 0.00 |
December | 0.347728E+11 | -0.337498E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102293E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.384009E+12 | -0.371936E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120723E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.265565E+11 | -0.372505E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103474E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.382806E+11 | -0.255366E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -931573250.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5921.93 | 33.91 | 269.33 | 272.00 | 1624.80 | 26.37 | 200.17 | 250.33 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6940.48 | 33.90 | 233.50 | 247.50 | 1123.22 | 21.82 | 121.83 | 215.83 |
March | 351.67 | 0.50 | 0.48 | 01-MAR-08:39 | 1656.11 | 19.81 | 68.50 | 318.33 | 952.21 | 21.08 | 174.83 | 282.83 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:20 | 1378.28 | 19.39 | 39.67 | 325.17 | 778.45 | 20.71 | 172.00 | 280.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1255.23 | 19.55 | 20.83 | 360.00 | 696.19 | 20.88 | 217.67 | 312.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:00 | 1170.33 | 19.28 | 7.67 | 360.67 | 656.31 | 20.63 | 200.50 | 313.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:10 | 1231.43 | 19.45 | 23.33 | 363.83 | 681.51 | 20.77 | 227.00 | 314.33 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 1495.66 | 20.07 | 74.17 | 350.67 | 809.17 | 21.39 | 265.67 | 312.33 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1589.40 | 20.19 | 69.83 | 308.67 | 878.80 | 21.27 | 179.00 | 268.67 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-08:20 | 2831.50 | 25.07 | 142.67 | 292.33 | 1046.08 | 20.42 | 118.33 | 254.50 |
November | 299.00 | 0.50 | 0.48 | 01-NOV-08:20 | 5834.01 | 34.76 | 286.83 | 273.17 | 1149.93 | 23.38 | 181.00 | 248.17 |
December | 285.17 | 0.49 | 0.48 | 01-DEC-07:00 | 5579.39 | 34.65 | 273.00 | 267.67 | 1564.86 | 27.28 | 215.67 | 245.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2790.92 | 24.14 | 1509.33 | 3740.00 | 957.77 | 21.98 | 2273.67 | 3298.00 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 1170.33 | 19.28 | 7.67 | 247.50 | 656.31 | 20.42 | 118.33 | 215.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6940.48 | 34.76 | 286.83 | 363.83 | 1624.80 | 27.28 | 265.67 | 314.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-08:00 | 1422.37 | 21.43 | 82.83 | 244.83 | 718.25 | 21.51 | 101.50 | 186.50 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-10:30 | 1945.19 | 22.72 | 75.67 | 229.00 | 1028.97 | 22.64 | 86.67 | 181.50 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2267.69 | 22.82 | 106.83 | 312.67 | 886.34 | 21.89 | 129.50 | 271.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2186.85 | 22.43 | 97.17 | 327.17 | 1168.48 | 22.92 | 133.17 | 291.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2499.41 | 23.36 | 118.83 | 368.83 | 1033.30 | 22.66 | 151.17 | 331.83 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:19 | 2531.73 | 23.45 | 123.67 | 371.00 | 1049.46 | 22.76 | 159.33 | 335.67 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2500.48 | 23.28 | 115.17 | 374.33 | 1056.26 | 22.73 | 169.00 | 334.17 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:30 | 2290.55 | 23.14 | 104.17 | 352.17 | 1197.21 | 23.59 | 189.17 | 316.67 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-06:00 | 2152.89 | 23.05 | 80.33 | 306.50 | 1126.82 | 23.36 | 121.00 | 262.33 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-07:49 | 2529.34 | 23.96 | 101.67 | 270.50 | 952.34 | 22.47 | 100.33 | 221.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:09 | 1721.15 | 23.31 | 103.00 | 249.33 | 920.52 | 23.35 | 115.00 | 205.17 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:49 | 1486.56 | 22.84 | 86.67 | 241.17 | 772.32 | 22.80 | 112.00 | 183.50 |
Annual Sum or Average | 4071.00 | 0.51 | 2170.32 | 23.01 | 1196.00 | 3647.50 | 1004.23 | 22.74 | 1567.83 | 3121.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1422.37 | 21.43 | 75.67 | 229.00 | 718.25 | 21.51 | 86.67 | 181.50 | |
Maximum of Months | 411.67 | 0.52 | 0.48 | 2531.73 | 23.96 | 123.67 | 374.33 | 1197.21 | 23.59 | 189.17 | 335.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-10:50 | 521.73 | 16.11 | 0.00 | 217.67 | 313.48 | 17.65 | 0.00 | 104.50 |
February | 263.00 | 0.54 | 0.48 | 01-FEB-13:39 | 556.34 | 16.28 | 0.00 | 197.67 | 343.95 | 17.78 | 0.00 | 123.00 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:00 | 707.91 | 17.99 | 0.00 | 303.67 | 429.32 | 19.36 | 2.33 | 231.83 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 843.70 | 18.82 | 0.00 | 330.83 | 502.84 | 20.10 | 48.83 | 274.50 |
May | 407.00 | 0.49 | 0.48 | 01-MAY-07:19 | 1048.66 | 21.66 | 61.67 | 383.33 | 610.33 | 22.81 | 212.33 | 352.00 |
June | 411.67 | 0.49 | 0.48 | 01-JUN-06:49 | 1138.44 | 22.33 | 116.50 | 386.67 | 654.59 | 22.47 | 241.67 | 358.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:19 | 1146.19 | 21.81 | 104.17 | 385.67 | 637.22 | 22.15 | 243.17 | 350.17 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 1026.04 | 19.74 | 3.67 | 360.33 | 593.54 | 21.01 | 182.50 | 325.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 784.71 | 18.62 | 0.00 | 303.67 | 471.84 | 19.92 | 27.17 | 223.67 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-10:39 | 584.51 | 16.78 | 0.00 | 242.50 | 371.97 | 18.31 | 1.83 | 158.83 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-09:39 | 540.04 | 16.39 | 0.00 | 228.83 | 326.11 | 17.88 | 0.00 | 133.33 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-09:20 | 504.04 | 16.21 | 0.00 | 210.17 | 303.39 | 17.78 | 0.00 | 94.83 |
Annual Sum or Average | 4071.00 | 0.52 | 819.64 | 18.90 | 286.00 | 3551.00 | 482.40 | 20.05 | 959.83 | 2729.67 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 504.04 | 16.11 | 0.00 | 197.67 | 303.39 | 17.65 | 0.00 | 94.83 | |
Maximum of Months | 411.67 | 0.54 | 0.48 | 1146.19 | 22.33 | 116.50 | 386.67 | 654.59 | 22.81 | 243.17 | 358.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:39 | 1740.54 | 23.32 | 95.33 | 247.33 | 956.18 | 23.34 | 119.83 | 197.17 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1691.29 | 22.26 | 78.00 | 219.50 | 881.90 | 22.32 | 106.00 | 172.00 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:09 | 2247.06 | 23.29 | 102.50 | 312.33 | 1183.87 | 23.51 | 150.00 | 271.00 |
April | 369.33 | 0.50 | 0.48 | 01-APR-09:50 | 2396.62 | 21.36 | 80.33 | 333.17 | 1309.01 | 21.97 | 123.50 | 292.83 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:00 | 2409.36 | 20.09 | 52.83 | 366.67 | 1017.19 | 20.34 | 124.50 | 329.00 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-07:30 | 2522.79 | 18.21 | 1.67 | 369.67 | 1075.07 | 20.28 | 129.17 | 334.17 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 2504.52 | 20.03 | 55.00 | 369.83 | 1052.62 | 20.32 | 139.50 | 331.67 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-07:30 | 2466.44 | 22.11 | 89.67 | 355.00 | 1065.51 | 20.94 | 169.00 | 321.50 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:09 | 2208.14 | 23.76 | 92.33 | 307.33 | 1154.14 | 23.92 | 144.67 | 260.33 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2376.49 | 23.29 | 97.67 | 268.17 | 905.40 | 21.84 | 106.33 | 217.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-09:39 | 1655.68 | 23.21 | 98.83 | 253.33 | 859.91 | 23.25 | 119.83 | 205.17 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-09:20 | 1443.22 | 22.77 | 93.00 | 241.33 | 758.97 | 22.85 | 110.00 | 183.50 |
Annual Sum or Average | 4071.00 | 0.51 | 2186.44 | 21.77 | 937.17 | 3643.67 | 1031.37 | 21.91 | 1542.33 | 3115.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1443.22 | 18.21 | 1.67 | 219.50 | 758.97 | 20.28 | 106.00 | 172.00 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2522.79 | 23.76 | 102.50 | 369.83 | 1309.01 | 23.92 | 169.00 | 334.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5963.97 | 33.12 | 257.33 | 272.00 | 1712.26 | 22.51 | 103.00 | 251.67 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6982.70 | 33.22 | 228.67 | 247.50 | 1207.84 | 16.99 | 25.83 | 217.83 |
March | 351.67 | 0.50 | 0.48 | 01-MAR-08:39 | 1692.26 | 13.33 | 6.67 | 319.33 | 1021.96 | 16.68 | 0.00 | 287.33 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:20 | 1404.06 | 13.21 | 0.00 | 326.00 | 832.43 | 16.69 | 0.00 | 287.67 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:30 | 1274.21 | 13.54 | 0.00 | 360.50 | 741.65 | 16.98 | 0.00 | 317.83 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:00 | 1188.15 | 13.39 | 0.00 | 361.67 | 698.88 | 16.81 | 0.00 | 319.50 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1249.18 | 13.55 | 0.00 | 365.67 | 725.54 | 16.94 | 0.00 | 319.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 1516.18 | 14.12 | 0.00 | 351.00 | 861.61 | 17.52 | 0.00 | 316.33 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1616.68 | 14.20 | 6.50 | 309.00 | 939.37 | 17.28 | 0.00 | 274.00 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-08:20 | 2884.38 | 20.61 | 117.00 | 292.67 | 1133.35 | 15.78 | 2.00 | 257.83 |
November | 299.00 | 0.50 | 0.48 | 01-NOV-08:20 | 5874.70 | 34.27 | 282.83 | 273.33 | 1258.70 | 20.88 | 81.67 | 254.83 |
December | 285.17 | 0.49 | 0.48 | 01-DEC-07:00 | 5619.04 | 34.03 | 265.00 | 268.33 | 1652.34 | 23.59 | 115.33 | 247.83 |
Annual Sum or Average | 4071.00 | 0.50 | 2821.15 | 19.72 | 1164.00 | 3747.00 | 1023.58 | 18.04 | 327.83 | 3351.83 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 1188.15 | 13.21 | 0.00 | 247.50 | 698.88 | 15.78 | 0.00 | 217.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6982.70 | 34.27 | 282.83 | 365.67 | 1712.26 | 23.59 | 115.33 | 319.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-08:00 | 1449.55 | 18.51 | 71.50 | 247.33 | 753.41 | 19.30 | 45.83 | 194.50 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-10:30 | 1983.82 | 19.80 | 71.17 | 230.50 | 1075.06 | 20.37 | 48.33 | 187.00 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2310.17 | 19.94 | 105.33 | 314.17 | 934.65 | 19.31 | 47.33 | 276.17 |
April | 369.33 | 0.50 | 0.48 | 01-APR-07:00 | 2224.33 | 19.23 | 92.83 | 328.00 | 1223.10 | 20.41 | 67.00 | 297.50 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2520.68 | 19.63 | 108.33 | 369.17 | 1091.40 | 19.95 | 57.33 | 335.83 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:19 | 2566.32 | 20.43 | 122.67 | 371.33 | 1107.30 | 20.13 | 64.00 | 339.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2524.45 | 19.57 | 104.83 | 375.17 | 1114.50 | 20.06 | 58.33 | 337.17 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:30 | 2318.05 | 20.05 | 103.33 | 353.00 | 1252.66 | 21.18 | 73.33 | 321.50 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-06:00 | 2197.04 | 19.96 | 78.83 | 307.50 | 1180.71 | 20.98 | 55.83 | 268.17 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-07:49 | 2551.68 | 20.27 | 90.50 | 272.00 | 1002.41 | 20.05 | 50.00 | 228.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:09 | 1748.93 | 20.63 | 97.00 | 251.00 | 957.67 | 21.39 | 71.33 | 211.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:49 | 1485.04 | 19.12 | 73.00 | 241.83 | 808.05 | 20.78 | 57.17 | 189.17 |
Annual Sum or Average | 4071.00 | 0.51 | 2199.29 | 19.77 | 1119.33 | 3661.00 | 1054.49 | 20.31 | 695.83 | 3185.83 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1449.55 | 18.51 | 71.17 | 230.50 | 753.41 | 19.30 | 45.83 | 187.00 | |
Maximum of Months | 411.67 | 0.52 | 0.48 | 2566.32 | 20.63 | 122.67 | 375.17 | 1252.66 | 21.39 | 73.33 | 339.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-10:50 | 530.22 | 9.99 | 0.00 | 219.50 | 333.71 | 13.64 | 0.00 | 126.67 |
February | 263.00 | 0.54 | 0.48 | 01-FEB-13:39 | 566.69 | 10.32 | 0.00 | 199.33 | 366.63 | 13.93 | 0.00 | 134.67 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:00 | 721.21 | 12.39 | 0.00 | 304.50 | 457.61 | 15.90 | 0.00 | 243.00 |
April | 369.33 | 0.50 | 0.48 | 01-APR-08:20 | 860.14 | 13.23 | 0.00 | 331.00 | 536.14 | 16.72 | 0.00 | 283.17 |
May | 407.00 | 0.49 | 0.48 | 01-MAY-07:19 | 1067.79 | 16.71 | 51.67 | 383.67 | 649.79 | 19.84 | 52.50 | 356.17 |
June | 411.67 | 0.49 | 0.48 | 01-JUN-06:40 | 1159.36 | 17.55 | 66.50 | 387.17 | 705.46 | 20.61 | 68.17 | 366.50 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1166.05 | 16.87 | 53.00 | 386.17 | 682.99 | 19.97 | 53.83 | 356.67 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 1043.85 | 14.20 | 0.00 | 360.50 | 631.83 | 17.63 | 0.00 | 331.50 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 799.20 | 13.31 | 0.00 | 304.33 | 502.79 | 16.72 | 0.00 | 237.67 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-10:39 | 596.69 | 11.09 | 0.00 | 246.00 | 396.93 | 14.75 | 0.00 | 174.83 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-09:20 | 548.63 | 10.44 | 0.00 | 230.50 | 347.11 | 14.01 | 0.00 | 149.17 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-09:09 | 511.53 | 10.03 | 0.00 | 211.83 | 322.80 | 13.73 | 0.00 | 115.83 |
Annual Sum or Average | 4071.00 | 0.51 | 834.39 | 13.41 | 171.17 | 3564.50 | 515.13 | 16.82 | 174.50 | 2875.83 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 511.53 | 9.99 | 0.00 | 199.33 | 322.80 | 13.64 | 0.00 | 115.83 | |
Maximum of Months | 411.67 | 0.54 | 0.48 | 1166.05 | 17.55 | 66.50 | 387.17 | 705.46 | 20.61 | 68.17 | 366.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-10:39 | 1769.18 | 20.66 | 89.00 | 248.17 | 993.76 | 21.37 | 67.17 | 204.33 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 1704.38 | 18.29 | 63.83 | 221.50 | 926.26 | 19.99 | 46.83 | 178.17 |
March | 351.67 | 0.50 | 0.48 | 01-MAR-09:09 | 2294.50 | 20.26 | 97.83 | 313.67 | 1236.86 | 21.15 | 72.33 | 276.50 |
April | 369.33 | 0.50 | 0.48 | 01-APR-09:39 | 2434.26 | 17.92 | 78.33 | 334.17 | 1364.16 | 19.25 | 51.17 | 296.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:00 | 2436.16 | 16.16 | 50.50 | 368.50 | 1072.18 | 17.06 | 0.00 | 333.33 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-07:19 | 2554.25 | 13.67 | 1.67 | 370.33 | 1130.03 | 17.00 | 0.00 | 338.67 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-07:19 | 2530.35 | 16.16 | 51.67 | 370.83 | 1106.77 | 17.06 | 0.00 | 335.83 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-07:30 | 2485.79 | 18.80 | 89.00 | 356.17 | 1121.03 | 17.81 | 7.67 | 325.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:00 | 2253.10 | 20.87 | 90.83 | 307.83 | 1208.01 | 21.58 | 62.67 | 266.50 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2419.11 | 20.47 | 93.17 | 269.67 | 953.99 | 19.30 | 42.50 | 224.67 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-09:30 | 1684.95 | 20.57 | 96.00 | 254.17 | 897.35 | 21.24 | 67.50 | 211.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-09:09 | 1469.07 | 20.09 | 85.17 | 242.50 | 793.67 | 20.86 | 59.33 | 192.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2217.50 | 18.39 | 887.00 | 3657.50 | 1080.99 | 19.24 | 477.17 | 3183.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1469.07 | 13.67 | 1.67 | 221.50 | 793.67 | 17.00 | 0.00 | 178.17 | |
Maximum of Months | 411.67 | 0.52 | 0.48 | 2554.25 | 20.87 | 97.83 | 370.83 | 1364.16 | 21.58 | 72.33 | 338.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5965.44 | 33.11 | 257.33 | 272.00 | 1713.88 | 22.50 | 102.83 | 252.17 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6984.55 | 33.21 | 228.67 | 247.50 | 1209.31 | 16.98 | 25.83 | 217.83 |
March | 351.67 | 0.50 | 0.48 | 01-MAR-08:39 | 1694.57 | 13.30 | 6.67 | 319.50 | 1023.42 | 16.67 | 0.00 | 287.33 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:20 | 1406.08 | 13.18 | 0.00 | 326.33 | 833.65 | 16.68 | 0.00 | 288.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:30 | 1276.05 | 13.51 | 0.00 | 360.50 | 742.78 | 16.96 | 0.00 | 317.83 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:00 | 1189.79 | 13.36 | 0.00 | 361.67 | 699.91 | 16.79 | 0.00 | 319.83 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1250.96 | 13.52 | 0.00 | 365.67 | 726.64 | 16.93 | 0.00 | 319.50 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 1518.48 | 14.09 | 0.00 | 351.00 | 863.00 | 17.50 | 0.00 | 316.33 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1619.03 | 14.17 | 6.50 | 309.00 | 940.81 | 17.27 | 0.00 | 274.17 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-08:20 | 2886.39 | 20.59 | 117.00 | 292.67 | 1134.71 | 15.77 | 2.00 | 258.00 |
November | 299.00 | 0.50 | 0.48 | 01-NOV-08:20 | 5876.44 | 34.26 | 282.83 | 273.33 | 1260.34 | 20.87 | 81.67 | 255.00 |
December | 285.17 | 0.49 | 0.48 | 01-DEC-07:00 | 5620.36 | 34.02 | 265.00 | 268.33 | 1653.97 | 23.58 | 115.33 | 248.33 |
Annual Sum or Average | 4071.00 | 0.50 | 2823.04 | 19.70 | 1164.00 | 3747.50 | 1024.93 | 18.03 | 327.67 | 3354.50 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 1189.79 | 13.18 | 0.00 | 247.50 | 699.91 | 15.77 | 0.00 | 217.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6984.55 | 34.26 | 282.83 | 365.67 | 1713.88 | 23.58 | 115.33 | 319.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-08:00 | 1450.45 | 18.48 | 71.33 | 247.33 | 754.22 | 19.28 | 45.83 | 195.17 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-10:30 | 1984.64 | 19.77 | 71.17 | 230.50 | 1075.81 | 20.36 | 48.33 | 187.17 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2311.45 | 19.91 | 105.17 | 314.17 | 935.71 | 19.30 | 47.33 | 276.17 |
April | 369.33 | 0.50 | 0.48 | 01-APR-07:00 | 2225.83 | 19.20 | 92.83 | 328.00 | 1224.27 | 20.40 | 67.00 | 297.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2522.40 | 19.60 | 108.33 | 369.17 | 1092.74 | 19.93 | 57.33 | 335.83 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:19 | 2568.05 | 20.40 | 122.67 | 371.33 | 1108.64 | 20.11 | 64.00 | 339.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2526.23 | 19.54 | 104.67 | 375.17 | 1115.90 | 20.04 | 58.33 | 337.33 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:30 | 2319.93 | 20.03 | 103.33 | 353.00 | 1254.12 | 21.17 | 73.33 | 321.50 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-06:00 | 2198.37 | 19.93 | 78.83 | 307.50 | 1181.88 | 20.96 | 55.83 | 268.17 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-07:49 | 2552.59 | 20.24 | 90.50 | 272.33 | 1003.26 | 20.04 | 50.00 | 228.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:09 | 1749.84 | 20.60 | 97.00 | 251.00 | 958.53 | 21.38 | 71.33 | 211.83 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:49 | 1485.86 | 19.09 | 73.00 | 242.17 | 808.82 | 20.77 | 57.17 | 189.50 |
Annual Sum or Average | 4071.00 | 0.51 | 2200.64 | 19.75 | 1118.83 | 3661.67 | 1055.61 | 20.30 | 695.83 | 3187.67 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1450.45 | 18.48 | 71.17 | 230.50 | 754.22 | 19.28 | 45.83 | 187.17 | |
Maximum of Months | 411.67 | 0.52 | 0.48 | 2568.05 | 20.60 | 122.67 | 375.17 | 1254.12 | 21.38 | 73.33 | 339.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-10:50 | 530.74 | 9.96 | 0.00 | 220.00 | 334.15 | 13.62 | 0.00 | 127.17 |
February | 263.00 | 0.54 | 0.48 | 01-FEB-13:39 | 567.20 | 10.28 | 0.00 | 199.33 | 367.07 | 13.91 | 0.00 | 134.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:00 | 721.91 | 12.36 | 0.00 | 304.50 | 458.19 | 15.88 | 0.00 | 243.33 |
April | 369.33 | 0.50 | 0.48 | 01-APR-08:20 | 861.06 | 13.20 | 0.00 | 331.33 | 536.85 | 16.70 | 0.00 | 283.50 |
May | 407.00 | 0.49 | 0.48 | 01-MAY-07:19 | 1069.04 | 16.69 | 51.67 | 383.67 | 650.69 | 19.83 | 52.50 | 356.17 |
June | 411.67 | 0.49 | 0.48 | 01-JUN-06:40 | 1160.72 | 17.52 | 66.50 | 387.33 | 706.44 | 20.60 | 68.17 | 366.50 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1167.38 | 16.84 | 53.00 | 386.17 | 683.95 | 19.95 | 53.83 | 356.83 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 1045.03 | 14.17 | 0.00 | 360.50 | 632.72 | 17.61 | 0.00 | 331.67 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 799.96 | 13.27 | 0.00 | 304.50 | 503.44 | 16.71 | 0.00 | 238.17 |
October | 293.50 | 0.53 | 0.48 | 01-OCT-10:39 | 597.15 | 11.06 | 0.00 | 246.33 | 397.37 | 14.73 | 0.00 | 175.00 |
November | 299.00 | 0.54 | 0.48 | 01-NOV-09:20 | 549.14 | 10.41 | 0.00 | 230.50 | 347.56 | 14.00 | 0.00 | 149.50 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-09:09 | 512.01 | 9.99 | 0.00 | 211.83 | 323.22 | 13.71 | 0.00 | 116.33 |
Annual Sum or Average | 4071.00 | 0.51 | 835.27 | 13.38 | 171.17 | 3566.00 | 515.82 | 16.80 | 174.50 | 2879.00 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 512.01 | 9.96 | 0.00 | 199.33 | 323.22 | 13.62 | 0.00 | 116.33 | |
Maximum of Months | 411.67 | 0.54 | 0.48 | 1167.38 | 17.52 | 66.50 | 387.33 | 706.44 | 20.60 | 68.17 | 366.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-10:39 | 1770.08 | 20.63 | 89.00 | 248.17 | 994.58 | 21.36 | 67.00 | 204.50 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 1705.36 | 18.26 | 63.83 | 221.50 | 927.17 | 19.98 | 46.83 | 178.33 |
March | 351.67 | 0.50 | 0.48 | 01-MAR-09:09 | 2295.72 | 20.23 | 97.67 | 313.83 | 1237.98 | 21.14 | 72.33 | 276.67 |
April | 369.33 | 0.50 | 0.48 | 01-APR-09:39 | 2435.78 | 17.89 | 78.33 | 334.17 | 1365.38 | 19.23 | 51.17 | 296.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:49 | 2427.81 | 16.12 | 50.50 | 367.50 | 1073.53 | 17.04 | 0.00 | 333.33 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-07:19 | 2556.00 | 13.64 | 1.67 | 370.33 | 1131.40 | 16.99 | 0.00 | 338.67 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-07:19 | 2532.16 | 16.13 | 51.67 | 370.83 | 1108.16 | 17.04 | 0.00 | 335.83 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-07:19 | 2487.76 | 18.77 | 89.00 | 356.17 | 1122.53 | 17.80 | 7.67 | 325.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:00 | 2254.70 | 20.84 | 90.83 | 307.83 | 1209.32 | 21.56 | 62.67 | 266.67 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2420.07 | 20.44 | 93.17 | 269.83 | 954.89 | 19.28 | 42.50 | 224.83 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-09:20 | 1685.88 | 20.54 | 96.00 | 254.17 | 898.22 | 21.23 | 67.50 | 211.83 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-09:09 | 1469.90 | 20.07 | 85.00 | 242.67 | 794.44 | 20.84 | 59.33 | 192.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2217.89 | 18.36 | 886.67 | 3657.00 | 1082.15 | 19.23 | 477.00 | 3184.67 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1469.90 | 13.64 | 1.67 | 221.50 | 794.44 | 16.99 | 0.00 | 178.33 | |
Maximum of Months | 411.67 | 0.52 | 0.48 | 2556.00 | 20.84 | 97.67 | 370.83 | 1365.38 | 21.56 | 72.33 | 338.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261462E+09 | 28608.03 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205177E+09 | 31510.59 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74903135.25 | 14525.78 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123995E+09 | 17690.11 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157947E+09 | 14122.69 | 15-MAY-15:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 52867493.35 | 9219.68 | 02-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2950631.21 | 2551.01 | 25-AUG-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14011077.10 | 6241.33 | 22-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32824672.92 | 15804.20 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130062E+09 | 26475.59 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267839E+09 | 31651.17 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267839E+09 | 31651.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.627019E+09 | 14160.46 | 23-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216372E+09 | 14155.98 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7147296.27 | 9838.03 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24669157.94 | 8584.02 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.875207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.627019E+09 | 14160.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382421E+09 | 12448.15 | 23-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127995E+09 | 12445.25 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8074852.68 | 12489.03 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36157643.44 | 12550.30 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382421E+09 | 12550.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.625878E+09 | 16616.15 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225193E+09 | 16535.72 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17336731.44 | 16666.09 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74065130.83 | 16638.71 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.942472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.625878E+09 | 16666.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64504533.05 | 11371.74 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5913247.51 | 9386.42 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70417780.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64504533.05 | 11371.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.437916E+10 | 319608.91 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321927E+10 | 381599.25 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143238E+10 | 215035.91 | 15-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159371E+10 | 234497.97 | 05-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123245E+10 | 125909.72 | 15-MAY-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.314128E+09 | 94180.02 | 02-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127941E+09 | 54410.19 | 25-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152201E+09 | 46632.71 | 15-SEP-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.763170E+09 | 188591.55 | 04-OCT-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227412E+10 | 266855.73 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336980E+10 | 326759.67 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437916E+10 | 381599.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.526372E+10 | 512430.30 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154412E+10 | 510245.49 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25277854.61 | 15676.70 | 26-DEC-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.683312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.526372E+10 | 512430.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.498577E+11 | 129187.36 | 10-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264918E+11 | 139916.19 | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206120E+10 | 139030.31 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452048E+09 | 139484.17 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.628459E+09 | 138675.55 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.584159E+10 | 139726.28 | 08-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217965E+11 | 128502.20 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.498577E+11 | 139916.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245054E+11 | 152576.54 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123851E+11 | 152232.27 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.851325E+09 | 161328.26 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152812E+09 | 115584.43 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371702E+09 | 161181.14 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218283E+10 | 151609.60 | 21-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929855E+10 | 152221.90 | 26-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245054E+11 | 161328.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249135E+11 | 155081.21 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128286E+11 | 154544.06 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812861E+09 | 153585.40 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250914E+09 | 133095.90 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.403657E+09 | 110965.47 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183416E+10 | 153281.19 | 21-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.851436E+10 | 154101.85 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.249135E+11 | 155081.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208277E+11 | 158275.79 | 09-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102269E+11 | 157986.91 | 02-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391154E+09 | 128070.88 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70820093.68 | 42037.15 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191783E+09 | 80172.30 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184824E+10 | 157553.57 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.734324E+10 | 157912.05 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208277E+11 | 158275.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105180E+10 | 37752.46 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695438E+09 | 38997.48 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108143E+09 | 18425.21 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116364E+09 | 21340.29 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160705E+09 | 10217.90 | 16-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25354848.82 | 4243.32 | 03-JUN-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11191757.89 | 7380.10 | 25-AUG-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10843728.97 | 2690.36 | 23-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72273017.75 | 19885.19 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197029E+09 | 34005.09 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431675E+09 | 39409.10 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105180E+10 | 39409.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.845079E+10 | 72109.11 | 02-JAN-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.388035E+10 | 71648.49 | 14-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89571052.99 | 70859.07 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75682404.78 | 65268.88 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.636530E+09 | 71629.45 | 21-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407653E+10 | 72023.94 | 26-DEC-05:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.845079E+10 | 72109.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.919506E+10 | 14843.35 | 19-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542790E+10 | 14858.85 | 08-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993183E+09 | 14772.88 | 22-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.259679E+09 | 14690.54 | 06-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7503228.86 | 3416.44 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 184390.19 | 120.46 | 29-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.588290E+09 | 14835.61 | 31-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210119E+10 | 14852.92 | 24-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554739E+10 | 14793.56 | 22-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.919506E+10 | 14858.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.496044E+10 | 15592.87 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281632E+10 | 15585.01 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.434766E+09 | 15565.63 | 22-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95656809.59 | 15427.80 | 06-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1861842.53 | 574.36 | 11-MAY-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 179098.21 | 74.21 | 29-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.298579E+09 | 15562.01 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.911295E+09 | 15581.07 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273104E+10 | 15593.04 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.496044E+10 | 15593.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.531783E+10 | 17256.47 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317745E+10 | 17286.14 | 11-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.568800E+09 | 17215.52 | 22-MAR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181795E+09 | 17117.87 | 27-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6890202.61 | 917.68 | 11-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341643E+09 | 17205.96 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.964926E+09 | 17207.68 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274738E+10 | 17250.00 | 26-DEC-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.531783E+10 | 17286.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.426255E+10 | 17502.50 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227588E+10 | 17458.42 | 11-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296917E+09 | 17391.94 | 22-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76263804.46 | 13958.55 | 06-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173091E+09 | 17319.90 | 26-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.772353E+09 | 17384.69 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210941E+10 | 17433.52 | 27-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.426255E+10 | 17502.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 75.82 | 0.63 | 31-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 75.59 | 0.63 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 104.02 | 0.69 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 193.78 | 0.70 | 10-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 449.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 193.78 | 0.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177040E+10 | 0.172847E+10 | 34767.24 | 31-JAN-15:00 | 34767.24 | 0.04 |
February | 0.00 | 0.00 | 0.897768E+10 | 0.897179E+10 | 83418.85 | 28-FEB-15:00 | 83418.85 | 0.04 |
March | 0.00 | 0.00 | 0.252309E+11 | 0.244720E+11 | 122933.65 | 30-MAR-15:20 | 122933.65 | 0.18 |
April | 0.00 | 0.00 | 0.537518E+11 | 0.514581E+11 | 149830.17 | 17-APR-15:45 | 149830.17 | 0.42 |
May | 0.00 | 0.00 | 0.820911E+11 | 0.709306E+11 | 180458.89 | 16-MAY-15:50 | 180458.89 | 0.56 |
June | 0.00 | 0.00 | 0.127065E+12 | 0.109086E+12 | 201985.15 | 20-JUN-05:03 | 137660.83 | 0.68 |
July | 0.00 | 0.00 | 0.151134E+12 | 0.125159E+12 | 206231.25 | 27-JUL-05:02 | 138738.40 | 0.82 |
August | 0.00 | 0.00 | 0.176067E+12 | 0.145793E+12 | 204966.47 | 28-AUG-04:21 | 146136.07 | 0.88 |
September | 0.00 | 0.00 | 0.951072E+11 | 0.796075E+11 | 206988.22 | 07-SEP-05:02 | 139739.07 | 0.61 |
October | 0.00 | 0.00 | 0.453087E+11 | 0.380245E+11 | 199635.10 | 18-OCT-04:12 | 128410.57 | 0.29 |
November | 0.00 | 0.00 | 0.196559E+11 | 0.186653E+11 | 103431.19 | 27-NOV-06:02 | 103431.19 | 0.12 |
December | 0.00 | 0.00 | 0.146916E+11 | 0.138709E+11 | 79554.79 | 13-DEC-05:12 | 42833.04 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.800851E+12 | 0.687766E+12 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.177040E+10 | 0.172847E+10 | 34767.24 | 34767.24 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.176067E+12 | 0.145793E+12 | 206988.22 | 180458.89 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.974773E+10 | 0.933905E+10 | 232249.00 | 31-JAN-15:05 | 232249.00 | 0.04 |
February | 0.00 | 0.00 | 0.578968E+11 | 0.578968E+11 | 658277.12 | 28-FEB-15:05 | 658277.12 | 0.03 |
March | 0.00 | 0.00 | 0.185210E+12 | 0.180874E+12 | 1012255.95 | 30-MAR-15:20 | 1012255.95 | 0.17 |
April | 0.00 | 0.00 | 0.373903E+12 | 0.359343E+12 | 1376321.17 | 17-APR-15:35 | 1376321.17 | 0.34 |
May | 0.00 | 0.00 | 0.705895E+12 | 0.608790E+12 | 1532741.25 | 19-MAY-14:50 | 1229938.50 | 0.54 |
June | 0.00 | 0.00 | 0.106729E+13 | 0.884672E+12 | 2143801.63 | 30-JUN-05:02 | 1311788.55 | 0.59 |
July | 0.00 | 0.00 | 0.120934E+13 | 0.947040E+12 | 2224993.70 | 27-JUL-05:02 | 1282509.96 | 0.64 |
August | 0.00 | 0.00 | 0.134036E+13 | 0.103446E+13 | 1876895.41 | 23-AUG-04:12 | 1127064.78 | 0.68 |
September | 0.00 | 0.00 | 0.811188E+12 | 0.658593E+12 | 2125693.16 | 07-SEP-05:02 | 1322433.89 | 0.58 |
October | 0.00 | 0.00 | 0.349259E+12 | 0.286219E+12 | 1721083.66 | 19-OCT-05:03 | 966225.34 | 0.28 |
November | 0.00 | 0.00 | 0.116707E+12 | 0.111993E+12 | 590257.09 | 05-NOV-15:23 | 446752.60 | 0.12 |
December | 0.00 | 0.00 | 0.278513E+11 | 0.242455E+11 | 456248.33 | 12-DEC-13:05 | 374564.51 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.625464E+13 | 0.516346E+13 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.974773E+10 | 0.933905E+10 | 232249.00 | 232249.00 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.134036E+13 | 0.103446E+13 | 2224993.70 | 1376321.17 | 0.68 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.926077E+09 | 0.884736E+09 | 17554.46 | 31-JAN-15:00 | 17554.46 | 0.04 |
February | 0.00 | 0.00 | 0.456796E+10 | 0.456796E+10 | 59952.37 | 28-FEB-15:00 | 59952.37 | 0.04 |
March | 0.00 | 0.00 | 0.161113E+11 | 0.158516E+11 | 118076.60 | 30-MAR-15:40 | 118076.60 | 0.17 |
April | 0.00 | 0.00 | 0.379637E+11 | 0.365535E+11 | 155833.63 | 17-APR-15:40 | 155833.63 | 0.33 |
May | 0.00 | 0.00 | 0.773518E+11 | 0.675525E+11 | 165153.98 | 19-MAY-13:50 | 165153.98 | 0.54 |
June | 0.00 | 0.00 | 0.119450E+12 | 0.100650E+12 | 231332.04 | 30-JUN-05:02 | 136420.96 | 0.60 |
July | 0.00 | 0.00 | 0.135290E+12 | 0.108490E+12 | 244038.36 | 27-JUL-05:02 | 136474.87 | 0.65 |
August | 0.00 | 0.00 | 0.148153E+12 | 0.116998E+12 | 214164.68 | 04-AUG-03:02 | 135526.29 | 0.68 |
September | 0.00 | 0.00 | 0.835506E+11 | 0.686736E+11 | 228120.46 | 07-SEP-05:02 | 137179.40 | 0.58 |
October | 0.00 | 0.00 | 0.327042E+11 | 0.264639E+11 | 170806.40 | 19-OCT-04:12 | 81514.12 | 0.26 |
November | 0.00 | 0.00 | 0.850273E+10 | 0.807501E+10 | 45144.50 | 02-NOV-14:30 | 45144.50 | 0.12 |
December | 0.00 | 0.00 | 0.220957E+10 | 0.192702E+10 | 32846.44 | 12-DEC-14:30 | 32846.44 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.666781E+12 | 0.556687E+12 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.926077E+09 | 0.884736E+09 | 17554.46 | 17554.46 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.148153E+12 | 0.116998E+12 | 244038.36 | 165153.98 | 0.68 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.430296E+09 | 0.420442E+09 | 52464.89 | 20-JAN-06:03 | 23656.79 | 0.02 |
February | 0.00 | 0.00 | 0.360632E+10 | 0.358573E+10 | 65753.56 | 18-FEB-06:02 | 27232.36 | 0.01 |
March | 0.00 | 0.00 | 0.111018E+11 | 0.110274E+11 | 88430.65 | 30-MAR-05:02 | 43937.00 | 0.13 |
April | 0.00 | 0.00 | 0.236845E+11 | 0.233089E+11 | 90960.45 | 03-APR-04:13 | 90960.45 | 0.26 |
May | 0.00 | 0.00 | 0.431506E+11 | 0.392682E+11 | 99753.56 | 31-MAY-04:12 | 39794.61 | 0.43 |
June | 0.00 | 0.00 | 0.761541E+11 | 0.637484E+11 | 133491.88 | 26-JUN-04:53 | 79282.15 | 0.52 |
July | 0.00 | 0.00 | 0.880511E+11 | 0.689857E+11 | 137556.86 | 07-JUL-03:02 | 80023.76 | 0.53 |
August | 0.00 | 0.00 | 0.106873E+12 | 0.814883E+11 | 159572.27 | 20-AUG-16:29 | 80354.51 | 0.61 |
September | 0.00 | 0.00 | 0.654682E+11 | 0.547658E+11 | 149781.99 | 04-SEP-08:53 | 83300.25 | 0.51 |
October | 0.00 | 0.00 | 0.292103E+11 | 0.243009E+11 | 131622.90 | 18-OCT-04:53 | 78083.22 | 0.22 |
November | 0.00 | 0.00 | 0.945071E+10 | 0.880899E+10 | 86400.94 | 27-NOV-06:02 | 86400.94 | 0.09 |
December | 0.00 | 0.00 | 0.266609E+10 | 0.247327E+10 | 83455.64 | 13-DEC-06:03 | 38688.68 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.459847E+12 | 0.382182E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.430296E+09 | 0.420442E+09 | 52464.89 | 23656.79 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.106873E+12 | 0.814883E+11 | 159572.27 | 90960.45 | 0.61 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.596588E+10 | 0.596247E+10 | 4898.13 | 29-JAN-17:55 | 4898.13 | 0.00 |
February | 0.00 | 0.00 | 0.214346E+11 | 0.212312E+11 | 170042.05 | 28-FEB-15:00 | 170042.05 | 0.00 |
March | 0.00 | 0.00 | 0.151165E+12 | 0.127029E+12 | 343212.73 | 30-MAR-11:30 | 306575.44 | 0.00 |
April | 0.00 | 0.00 | 0.533372E+12 | 0.457720E+12 | 429046.73 | 23-APR-10:40 | 395945.54 | 0.00 |
May | 0.00 | 0.00 | 0.152078E+12 | 0.143124E+12 | 212065.30 | 31-MAY-23:10 | 210050.38 | 0.00 |
June | 0.00 | 0.00 | 0.493465E+12 | 0.481618E+12 | 303214.50 | 30-JUN-24:00 | 302653.73 | 0.00 |
July | 0.00 | 0.00 | 0.836442E+12 | 0.824279E+12 | 395984.47 | 31-JUL-24:00 | 395062.07 | 0.00 |
August | 0.00 | 0.00 | 0.107792E+13 | 0.106661E+13 | 420842.22 | 08-AUG-17:00 | 402413.40 | 0.00 |
September | 0.00 | 0.00 | 0.239406E+12 | 0.230717E+12 | 170422.68 | 21-SEP-12:30 | 127421.27 | 0.00 |
October | 0.00 | 0.00 | 0.152017E+12 | 0.142676E+12 | 311561.31 | 17-OCT-10:50 | 217975.35 | 0.00 |
November | 0.00 | 0.00 | 0.119887E+12 | 0.946052E+11 | 359915.35 | 19-NOV-14:05 | 308475.62 | 0.00 |
December | 0.00 | 0.00 | 0.935717E+11 | 0.714228E+11 | 425027.47 | 13-DEC-10:50 | 395128.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.387672E+13 | 0.366699E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.596588E+10 | 0.596247E+10 | 4898.13 | 4898.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107792E+13 | 0.106661E+13 | 429046.73 | 402413.40 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.361075E+10 | 0.359245E+10 | 2226.34 | 22-JAN-17:40 | 2226.34 | 0.00 |
February | 0.00 | 0.00 | 0.852063E+10 | 0.850046E+10 | 4612.05 | 20-FEB-17:45 | 4576.27 | 0.00 |
March | 0.00 | 0.00 | 0.154228E+11 | 0.153548E+11 | 7643.94 | 31-MAR-24:00 | 7643.94 | 0.00 |
April | 0.00 | 0.00 | 0.201002E+11 | 0.200047E+11 | 8527.21 | 09-APR-18:15 | 8527.21 | 0.00 |
May | 0.00 | 0.00 | 0.587519E+10 | 0.565284E+10 | 4008.70 | 31-MAY-24:00 | 3953.22 | 0.00 |
June | 0.00 | 0.00 | 0.110060E+11 | 0.106337E+11 | 5890.40 | 30-JUN-24:00 | 5867.96 | 0.00 |
July | 0.00 | 0.00 | 0.165775E+11 | 0.160987E+11 | 7783.57 | 31-JUL-24:00 | 7761.58 | 0.00 |
August | 0.00 | 0.00 | 0.216943E+11 | 0.211445E+11 | 8679.10 | 04-AUG-15:00 | 8055.40 | 0.00 |
September | 0.00 | 0.00 | 0.590744E+10 | 0.559953E+10 | 3750.58 | 30-SEP-24:00 | 3748.14 | 0.00 |
October | 0.00 | 0.00 | 0.106176E+11 | 0.104691E+11 | 5635.55 | 31-OCT-24:00 | 5635.55 | 0.00 |
November | 0.00 | 0.00 | 0.148338E+11 | 0.147762E+11 | 6476.58 | 11-NOV-17:05 | 6476.58 | 0.00 |
December | 0.00 | 0.00 | 0.200002E+11 | 0.199668E+11 | 8220.18 | 10-DEC-17:00 | 8220.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154166E+12 | 0.151794E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.361075E+10 | 0.359245E+10 | 2226.34 | 2226.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216943E+11 | 0.211445E+11 | 8679.10 | 8527.21 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.108971E+11 | 0.107408E+11 | 17222.17 | 20-JAN-17:00 | 16266.36 | 0.00 |
February | 0.00 | 0.00 | 0.636318E+11 | 0.634344E+11 | 39967.59 | 26-FEB-17:57 | 39967.59 | 0.00 |
March | 0.00 | 0.00 | 0.138704E+12 | 0.138026E+12 | 71659.69 | 31-MAR-23:40 | 71659.69 | 0.00 |
April | 0.00 | 0.00 | 0.188067E+12 | 0.187114E+12 | 79292.24 | 09-APR-18:30 | 79292.24 | 0.00 |
May | 0.00 | 0.00 | 0.532189E+11 | 0.510312E+11 | 38033.36 | 31-MAY-23:20 | 37075.83 | 0.00 |
June | 0.00 | 0.00 | 0.103795E+12 | 0.100098E+12 | 56035.94 | 30-JUN-24:00 | 55808.59 | 0.00 |
July | 0.00 | 0.00 | 0.157886E+12 | 0.153113E+12 | 74922.85 | 31-JUL-24:00 | 74708.64 | 0.00 |
August | 0.00 | 0.00 | 0.206312E+12 | 0.200814E+12 | 82862.10 | 04-AUG-15:00 | 76674.93 | 0.00 |
September | 0.00 | 0.00 | 0.531350E+11 | 0.501162E+11 | 32636.02 | 30-SEP-24:00 | 32551.29 | 0.00 |
October | 0.00 | 0.00 | 0.929785E+11 | 0.915105E+11 | 49212.90 | 31-OCT-23:40 | 49212.90 | 0.00 |
November | 0.00 | 0.00 | 0.128927E+12 | 0.128356E+12 | 58754.91 | 11-NOV-17:05 | 58754.91 | 0.00 |
December | 0.00 | 0.00 | 0.168935E+12 | 0.168601E+12 | 75186.52 | 11-DEC-17:00 | 73189.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136649E+13 | 0.134295E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.108971E+11 | 0.107408E+11 | 17222.17 | 16266.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206312E+12 | 0.200814E+12 | 82862.10 | 79292.24 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.469789E+09 | 0.455245E+09 | 1801.10 | 20-JAN-17:00 | 1702.15 | 0.00 |
February | 0.00 | 0.00 | 0.514697E+10 | 0.512755E+10 | 3951.13 | 28-FEB-17:00 | 3951.13 | 0.00 |
March | 0.00 | 0.00 | 0.130652E+11 | 0.129979E+11 | 6939.00 | 31-MAR-23:20 | 6939.00 | 0.00 |
April | 0.00 | 0.00 | 0.184322E+11 | 0.183372E+11 | 7979.96 | 09-APR-18:25 | 7979.96 | 0.00 |
May | 0.00 | 0.00 | 0.525881E+10 | 0.503978E+10 | 3769.45 | 31-MAY-23:10 | 3656.45 | 0.00 |
June | 0.00 | 0.00 | 0.104606E+11 | 0.100906E+11 | 5579.40 | 30-JUN-24:00 | 5556.28 | 0.00 |
July | 0.00 | 0.00 | 0.159156E+11 | 0.154385E+11 | 7526.36 | 31-JUL-24:00 | 7504.74 | 0.00 |
August | 0.00 | 0.00 | 0.207737E+11 | 0.202233E+11 | 8372.45 | 04-AUG-14:50 | 7766.69 | 0.00 |
September | 0.00 | 0.00 | 0.520740E+10 | 0.490629E+10 | 2832.22 | 30-SEP-23:30 | 2799.50 | 0.00 |
October | 0.00 | 0.00 | 0.854925E+10 | 0.840345E+10 | 4445.69 | 31-OCT-23:20 | 4445.69 | 0.00 |
November | 0.00 | 0.00 | 0.116130E+11 | 0.115565E+11 | 5795.32 | 02-NOV-16:00 | 5600.65 | 0.00 |
December | 0.00 | 0.00 | 0.151025E+11 | 0.150693E+11 | 7488.04 | 13-DEC-16:00 | 7159.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129995E+12 | 0.127646E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.469789E+09 | 0.455245E+09 | 1801.10 | 1702.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207737E+11 | 0.202233E+11 | 8372.45 | 7979.96 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 61457.49 | 1478461.16 | 09-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 35403.57 | 1712946.31 | 02-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3023.66 | 1134747.97 | 23-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1320.20 | 850023.64 | 06-APR-05:03 |
May | 1.63 | 3173.85 | 17-MAY-12:20 | 633.46 | 141926.68 | 15-MAY-16:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 152.49 | 55162.47 | 02-JUN-16:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 40.21 | 31685.60 | 25-AUG-13:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 73.60 | 35104.15 | 23-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1415.54 | 1090682.79 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 7581.33 | 1516868.76 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25487.95 | 1560247.66 | 21-DEC-05:01 |
Annual Sum or Average | 0.14 | 11284.76 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 1.63 | 3173.85 | 61457.49 | 1712946.31 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5106.12 | 312803.59 | 31-JAN-15:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 31558.77 | 846549.11 | 28-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 90897.71 | 1620775.05 | 30-MAR-14:47 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 194249.46 | 2203562.73 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 357620.35 | 2107938.87 | 19-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 565193.41 | 2407633.67 | 30-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 622908.40 | 2615026.95 | 27-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 696360.50 | 2319310.10 | 21-AUG-05:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 429610.68 | 2383889.59 | 07-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 181411.60 | 1667213.61 | 18-OCT-12:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 60531.69 | 659953.74 | 08-NOV-15:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18477.49 | 588083.77 | 12-DEC-13:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 272677.95 | 0.00 | ||||
Minimum of Months | 5106.12 | 312803.59 | 0.00 | 0.00 | ||
Maximum of Months | 696360.50 | 2615026.95 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4758.02 | 328073.21 | 31-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 30877.87 | 857432.02 | 28-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 89965.41 | 1879503.80 | 30-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 193253.82 | 1864906.75 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 355955.16 | 3090597.09 | 31-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 564942.92 | 3396316.51 | 30-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 622780.65 | 3379764.06 | 06-JUL-04:12 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 695701.89 | 3413702.13 | 21-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 428835.34 | 3479675.60 | 05-SEP-04:12 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 181851.15 | 3427875.36 | 19-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 59392.97 | 843827.26 | 04-NOV-05:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17626.78 | 594695.58 | 12-DEC-13:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 272014.09 | 0.00 | ||||
Minimum of Months | 4758.02 | 328073.21 | 0.00 | 0.00 | ||
Maximum of Months | 695701.89 | 3479675.60 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14299.31 | 178023.61 | 31-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 70858.99 | 740875.90 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 219805.27 | 1228185.28 | 30-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 582104.13 | 1446660.90 | 12-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 312830.26 | 946204.23 | 16-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 780301.76 | 1363391.31 | 06-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1108087.72 | 1715884.37 | 08-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1344640.59 | 1811588.13 | 01-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 444014.80 | 1004944.52 | 07-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 233392.29 | 1120693.38 | 10-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 180008.42 | 1001946.16 | 05-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 154295.08 | 1113971.89 | 12-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 456396.69 | 0.00 | ||||
Minimum of Months | 14299.31 | 178023.61 | 0.00 | 0.00 | ||
Maximum of Months | 1344640.59 | 1811588.13 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14850.36 | 49688.84 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14959.43 | 49711.69 | 06-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15316.02 | 48920.84 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13612.56 | 46273.70 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 13011.66 | 43148.44 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12346.28 | 39636.44 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 10960.41 | 36991.45 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11827.98 | 36879.51 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 11654.71 | 39097.81 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12477.02 | 42627.92 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13621.75 | 46035.42 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14017.23 | 48554.52 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 13211.52 | ||||
Minimum of Months | 0.00 | 0.00 | 10960.41 | 36879.51 | ||
Maximum of Months | 0.00 | 0.00 | 15316.02 | 49711.69 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5378.97 | 377340.06 | 31-JAN-15:10 | 2351.61 | 154367.13 | 29-JAN-12:43 |
February | 35538.78 | 957723.98 | 28-FEB-15:05 | 2006.38 | 156611.03 | 02-FEB-14:00 |
March | 106344.50 | 2481917.27 | 30-MAR-14:00 | 2078.82 | 128939.24 | 20-MAR-07:50 |
April | 242122.62 | 2646674.15 | 17-APR-15:00 | 1567.97 | 112139.93 | 05-APR-10:50 |
May | 548663.17 | 3801928.49 | 31-MAY-14:00 | 161.25 | 50631.43 | 11-MAY-09:10 |
June | 1241820.44 | 5208144.58 | 28-JUN-12:05 | 66.51 | 42962.79 | 10-JUN-21:40 |
July | 1595473.85 | 5383950.72 | 31-JUL-12:05 | 4.05 | 8247.95 | 03-JUL-01:20 |
August | 1896079.22 | 5425766.43 | 10-AUG-12:05 | 3.77 | 7937.93 | 26-AUG-04:00 |
September | 843821.37 | 4861835.89 | 08-SEP-12:05 | 180.56 | 50717.24 | 18-SEP-05:40 |
October | 293716.86 | 4100429.11 | 18-OCT-15:20 | 608.74 | 87033.87 | 26-OCT-10:20 |
November | 68976.06 | 760987.84 | 08-NOV-15:40 | 2854.33 | 140447.26 | 20-NOV-16:50 |
December | 17053.30 | 664951.62 | 12-DEC-14:00 | 5532.96 | 156696.45 | 18-DEC-11:40 |
Annual Sum or Average | 578743.30 | 1449.96 | ||||
Minimum of Months | 5378.97 | 377340.06 | 3.77 | 7937.93 | ||
Maximum of Months | 1896079.22 | 5425766.43 | 5532.96 | 156696.45 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122427E+11 | 0.79 | 8341.96 | 01-JAN-00:30 | 1.44 |
February | 0.108346E+11 | 0.77 | 8341.96 | 01-FEB-05:01 | 1.44 |
March | 0.129747E+11 | 0.83 | 8341.96 | 01-MAR-05:12 | 1.44 |
April | 0.118673E+11 | 0.79 | 8341.96 | 01-APR-04:12 | 1.44 |
May | 0.125330E+11 | 0.80 | 8341.96 | 01-MAY-04:12 | 1.43 |
June | 0.125179E+11 | 0.82 | 8341.96 | 01-JUN-04:12 | 1.43 |
July | 0.123002E+11 | 0.78 | 8341.96 | 01-JUL-04:12 | 1.43 |
August | 0.139232E+11 | 0.89 | 8341.96 | 01-AUG-03:02 | 1.43 |
September | 0.129863E+11 | 0.86 | 8341.96 | 01-SEP-04:12 | 1.43 |
October | 0.129384E+11 | 0.83 | 8341.96 | 02-OCT-01:50 | 1.42 |
November | 0.125512E+11 | 0.83 | 8341.96 | 01-NOV-04:12 | 1.43 |
December | 0.122460E+11 | 0.79 | 8341.96 | 01-DEC-05:01 | 1.44 |
Annual Sum or Average | 0.149915E+12 | 0.82 | |||
Minimum of Months | 0.108346E+11 | 0.77 | 8341.96 | 1.42 | |
Maximum of Months | 0.139232E+11 | 0.89 | 8341.96 | 1.44 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.285860E+10 | 0.30 | 10712.82 | 27-JAN-06:01 | 1.30 |
February | 0.355282E+10 | 0.34 | 10613.01 | 09-FEB-06:01 | 1.29 |
March | 0.660844E+10 | 0.45 | 14541.21 | 29-MAR-16:00 | 1.55 |
April | 0.835766E+10 | 0.54 | 18778.48 | 14-APR-15:35 | 1.83 |
May | 0.801791E+10 | 0.50 | 18778.48 | 15-MAY-14:15 | 1.82 |
June | 0.108843E+11 | 0.63 | 18778.48 | 01-JUN-05:02 | 1.82 |
July | 0.121149E+11 | 0.69 | 18778.48 | 01-JUL-04:12 | 1.82 |
August | 0.143036E+11 | 0.78 | 18778.48 | 02-AUG-05:03 | 1.82 |
September | 0.800909E+10 | 0.50 | 18778.48 | 05-SEP-05:03 | 1.82 |
October | 0.653551E+10 | 0.44 | 18778.48 | 18-OCT-05:02 | 1.82 |
November | 0.557341E+10 | 0.41 | 11577.83 | 06-NOV-16:40 | 1.35 |
December | 0.473981E+10 | 0.36 | 11298.94 | 13-DEC-05:12 | 1.32 |
Annual Sum or Average | 0.915561E+11 | 0.50 | |||
Minimum of Months | 0.285860E+10 | 0.30 | 10613.01 | 1.29 | |
Maximum of Months | 0.143036E+11 | 0.78 | 18778.48 | 1.83 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.233544E+11 | 0.31 | 42145.62 | 09-JAN-05:11 | 0.78 |
February | 0.236829E+11 | 0.32 | 100799.30 | 24-FEB-06:02 | 1.30 |
March | 0.370140E+11 | 0.35 | 91850.58 | 06-MAR-06:02 | 1.23 |
April | 0.469043E+11 | 0.39 | 174534.64 | 12-APR-15:00 | 1.83 |
May | 0.639510E+11 | 0.45 | 174534.64 | 15-MAY-14:40 | 1.82 |
June | 0.843624E+11 | 0.54 | 174534.64 | 05-JUN-04:12 | 1.82 |
July | 0.876419E+11 | 0.54 | 174534.64 | 01-JUL-05:03 | 1.82 |
August | 0.933172E+11 | 0.57 | 174534.64 | 02-AUG-05:03 | 1.82 |
September | 0.608576E+11 | 0.44 | 174534.64 | 05-SEP-04:12 | 1.82 |
October | 0.393287E+11 | 0.35 | 150700.68 | 19-OCT-05:03 | 1.65 |
November | 0.276403E+11 | 0.31 | 88508.03 | 18-NOV-06:03 | 1.20 |
December | 0.232844E+11 | 0.29 | 70193.89 | 13-DEC-06:03 | 1.03 |
Annual Sum or Average | 0.611339E+12 | 0.41 | |||
Minimum of Months | 0.232844E+11 | 0.29 | 42145.62 | 0.78 | |
Maximum of Months | 0.933172E+11 | 0.57 | 174534.64 | 1.83 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.287351E+10 | 0.37 | 4019.86 | 02-JAN-05:11 | 0.72 |
February | 0.248073E+10 | 0.34 | 5317.49 | 28-FEB-16:10 | 0.84 |
March | 0.313314E+10 | 0.33 | 11872.79 | 30-MAR-15:40 | 1.34 |
April | 0.418349E+10 | 0.35 | 19351.41 | 17-APR-15:30 | 1.83 |
May | 0.639077E+10 | 0.43 | 19351.41 | 17-MAY-14:40 | 1.82 |
June | 0.896463E+10 | 0.53 | 19351.41 | 15-JUN-05:02 | 1.82 |
July | 0.954514E+10 | 0.54 | 19351.41 | 06-JUL-04:12 | 1.82 |
August | 0.101126E+11 | 0.57 | 19351.41 | 03-AUG-05:02 | 1.82 |
September | 0.585562E+10 | 0.42 | 19351.41 | 05-SEP-04:12 | 1.82 |
October | 0.337098E+10 | 0.32 | 9727.32 | 18-OCT-05:02 | 1.18 |
November | 0.234510E+10 | 0.30 | 5421.37 | 04-NOV-05:03 | 0.84 |
December | 0.255406E+10 | 0.33 | 4019.86 | 01-DEC-06:01 | 0.72 |
Annual Sum or Average | 0.618097E+11 | 0.40 | |||
Minimum of Months | 0.234510E+10 | 0.30 | 4019.86 | 0.72 | |
Maximum of Months | 0.101126E+11 | 0.57 | 19351.41 | 1.83 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.969734E+11 | 1.40 | 36205.71 | 01-JAN-00:05 | 1.40 |
February | 0.875889E+11 | 1.40 | 36205.71 | 01-FEB-00:10 | 1.40 |
March | 0.969734E+11 | 1.40 | 36205.71 | 01-MAR-00:10 | 1.40 |
April | 0.938452E+11 | 1.39 | 36205.71 | 01-APR-00:10 | 1.40 |
May | 0.969734E+11 | 1.39 | 36205.71 | 01-MAY-00:05 | 1.39 |
June | 0.938452E+11 | 1.39 | 36205.71 | 01-JUN-00:10 | 1.39 |
July | 0.969734E+11 | 1.39 | 36205.71 | 01-JUL-00:10 | 1.39 |
August | 0.969734E+11 | 1.39 | 36205.71 | 01-AUG-00:05 | 1.39 |
September | 0.938452E+11 | 1.39 | 36205.71 | 01-SEP-00:05 | 1.39 |
October | 0.969734E+11 | 1.39 | 36205.71 | 01-OCT-00:10 | 1.39 |
November | 0.938452E+11 | 1.40 | 36205.71 | 01-NOV-00:10 | 1.40 |
December | 0.969734E+11 | 1.40 | 36205.71 | 01-DEC-00:10 | 1.40 |
Annual Sum or Average | 0.114178E+13 | 1.39 | |||
Minimum of Months | 0.875889E+11 | 1.39 | 36205.71 | 1.39 | |
Maximum of Months | 0.969734E+11 | 1.40 | 36205.71 | 1.40 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141801E+10 | 0.95 | 529.42 | 01-JAN-00:05 | 0.95 |
February | 0.128078E+10 | 0.95 | 529.42 | 01-FEB-00:10 | 0.95 |
March | 0.141801E+10 | 0.95 | 529.42 | 01-MAR-00:10 | 0.95 |
April | 0.137227E+10 | 0.95 | 529.42 | 01-APR-00:10 | 0.95 |
May | 0.141801E+10 | 0.95 | 529.42 | 01-MAY-00:05 | 0.95 |
June | 0.137227E+10 | 0.95 | 529.42 | 01-JUN-00:10 | 0.95 |
July | 0.141801E+10 | 0.95 | 529.42 | 01-JUL-00:10 | 0.95 |
August | 0.141801E+10 | 0.94 | 529.42 | 01-AUG-00:05 | 0.95 |
September | 0.137227E+10 | 0.95 | 529.42 | 01-SEP-00:05 | 0.95 |
October | 0.141801E+10 | 0.95 | 529.42 | 01-OCT-00:10 | 0.95 |
November | 0.137227E+10 | 0.95 | 529.42 | 01-NOV-00:10 | 0.95 |
December | 0.141801E+10 | 0.95 | 529.42 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.166959E+11 | 0.95 | |||
Minimum of Months | 0.128078E+10 | 0.94 | 529.42 | 0.95 | |
Maximum of Months | 0.141801E+10 | 0.95 | 529.42 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135342E+11 | 0.95 | 5053.10 | 01-JAN-00:05 | 0.94 |
February | 0.122245E+11 | 0.95 | 5053.10 | 01-FEB-00:10 | 0.95 |
March | 0.135342E+11 | 0.95 | 5053.10 | 01-MAR-00:10 | 0.95 |
April | 0.130976E+11 | 0.95 | 5053.10 | 01-APR-00:10 | 0.95 |
May | 0.135342E+11 | 0.95 | 5053.10 | 01-MAY-00:05 | 0.95 |
June | 0.130976E+11 | 0.95 | 5053.10 | 01-JUN-00:10 | 0.95 |
July | 0.135342E+11 | 0.95 | 5053.10 | 01-JUL-00:10 | 0.95 |
August | 0.135342E+11 | 0.94 | 5053.10 | 01-AUG-00:05 | 0.95 |
September | 0.130976E+11 | 0.94 | 5053.10 | 01-SEP-00:05 | 0.95 |
October | 0.135342E+11 | 0.95 | 5053.10 | 01-OCT-00:10 | 0.95 |
November | 0.130976E+11 | 0.95 | 5053.10 | 01-NOV-00:10 | 0.95 |
December | 0.135342E+11 | 0.95 | 5053.10 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.159355E+12 | 0.95 | |||
Minimum of Months | 0.122245E+11 | 0.94 | 5053.10 | 0.94 | |
Maximum of Months | 0.135342E+11 | 0.95 | 5053.10 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137985E+10 | 0.95 | 515.18 | 01-JAN-00:05 | 0.94 |
February | 0.124631E+10 | 0.95 | 515.18 | 01-FEB-00:10 | 0.95 |
March | 0.137985E+10 | 0.95 | 515.18 | 01-MAR-00:10 | 0.95 |
April | 0.133533E+10 | 0.95 | 515.18 | 01-APR-00:10 | 0.95 |
May | 0.137985E+10 | 0.95 | 515.18 | 01-MAY-00:05 | 0.95 |
June | 0.133533E+10 | 0.95 | 515.18 | 01-JUN-00:10 | 0.95 |
July | 0.137985E+10 | 0.95 | 515.18 | 01-JUL-00:10 | 0.95 |
August | 0.137985E+10 | 0.94 | 515.18 | 01-AUG-00:05 | 0.95 |
September | 0.133533E+10 | 0.94 | 515.18 | 01-SEP-00:05 | 0.95 |
October | 0.137985E+10 | 0.95 | 515.18 | 01-OCT-00:10 | 0.95 |
November | 0.133533E+10 | 0.95 | 515.18 | 01-NOV-00:10 | 0.95 |
December | 0.137985E+10 | 0.95 | 515.18 | 01-DEC-00:10 | 0.95 |
Annual Sum or Average | 0.162466E+11 | 0.95 | |||
Minimum of Months | 0.124631E+10 | 0.94 | 515.18 | 0.94 | |
Maximum of Months | 0.137985E+10 | 0.95 | 515.18 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 47734229.96 | 43390415.03 | 2777.32 | 09-JAN-06:02 | 2524.58 | 2524.58 | 45.68 | 24.17 |
February | 22643366.81 | 20582820.43 | 2754.24 | 13-FEB-06:02 | 2503.60 | 2503.60 | 46.45 | 24.08 |
March | 818410.27 | 743934.94 | 530.31 | 22-MAR-05:02 | 482.05 | 482.05 | 39.37 | 11.48 |
April | 360624.60 | 327807.76 | 306.37 | 06-APR-05:03 | 278.49 | 278.49 | 36.83 | 8.78 |
May | 234742.75 | 213381.16 | 17.20 | 15-MAY-16:20 | 15.63 | 15.63 | 39.09 | 1.62 |
June | 47184.68 | 42890.88 | 8.05 | 02-JUN-16:00 | 7.32 | 7.32 | 45.79 | 0.93 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 45.96 | 0.00 |
August | 10892.96 | 9901.70 | 3.32 | 25-AUG-11:05 | 3.02 | 3.02 | 44.19 | 0.45 |
September | 19147.96 | 17405.49 | 3.82 | 23-SEP-12:00 | 3.48 | 3.48 | 43.49 | 0.51 |
October | 344526.65 | 313174.72 | 421.95 | 26-OCT-05:02 | 383.55 | 383.55 | 34.65 | 10.29 |
November | 2942688.47 | 2674903.82 | 890.42 | 22-NOV-06:01 | 809.39 | 809.39 | 44.37 | 14.61 |
December | 14624260.41 | 13293452.71 | 887.48 | 18-DEC-06:01 | 806.72 | 806.72 | 45.49 | 14.58 |
Annual Sum or Average | 89780075.51 | 81610088.64 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | 0.00 | |
Maximum of Months | 47734229.96 | 43390415.03 | 2777.32 | 2524.58 | 2524.58 | 46.45 | 24.17 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 3131150.53 | 2846215.83 | 151.43 | 31-JAN-15:05 | 137.65 | 137.65 | 6.70 | 10.31 |
February | 15929142.13 | 14479590.20 | 271.70 | 28-FEB-15:05 | 246.98 | 246.98 | 6.70 | 13.91 |
March | 0.113351E+09 | 0.103036E+09 | 4576.76 | 30-MAR-13:50 | 4160.27 | 4160.27 | 10.52 | 49.48 |
April | 0.371500E+09 | 0.337694E+09 | 5034.33 | 17-APR-14:15 | 4576.20 | 4576.20 | 9.45 | 51.46 |
May | 0.599765E+09 | 0.545186E+09 | 11742.92 | 30-MAY-04:12 | 10674.31 | 10674.31 | 9.28 | 72.21 |
June | 0.107686E+10 | 0.978866E+09 | 11742.92 | 15-JUN-04:12 | 10674.31 | 10674.31 | 9.44 | 72.21 |
July | 0.124176E+10 | 0.112876E+10 | 11742.92 | 01-JUL-05:03 | 10674.31 | 10674.31 | 10.24 | 72.21 |
August | 0.145872E+10 | 0.132597E+10 | 11742.92 | 02-AUG-05:03 | 10674.31 | 10674.31 | 10.15 | 72.21 |
September | 0.825995E+09 | 0.750830E+09 | 11742.92 | 05-SEP-04:12 | 10674.31 | 10674.31 | 9.67 | 72.21 |
October | 0.352479E+09 | 0.320403E+09 | 11742.92 | 18-OCT-05:02 | 10674.31 | 10674.31 | 9.76 | 72.21 |
November | 43999376.95 | 39995433.65 | 787.30 | 04-NOV-05:03 | 715.66 | 715.66 | 6.70 | 23.11 |
December | 11689000.69 | 10625301.63 | 342.22 | 13-DEC-06:03 | 311.08 | 311.08 | 6.70 | 15.58 |
Annual Sum or Average | 0.611518E+10 | 0.555870E+10 | ||||||
Minimum of Months | 3131150.53 | 2846215.83 | 151.43 | 137.65 | 137.65 | 6.70 | 10.31 | |
Maximum of Months | 0.145872E+10 | 0.132597E+10 | 11742.92 | 10674.31 | 10674.31 | 10.52 | 72.21 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103148E+10 | 0.937612E+09 | 4041.17 | 02-JAN-09:50 | 3673.42 | 3673.42 | 6.72 | 36.10 |
February | 0.189636E+10 | 0.172379E+10 | 4041.17 | 01-FEB-07:20 | 3673.42 | 3673.42 | 6.74 | 36.10 |
March | 0.397970E+10 | 0.361755E+10 | 4041.17 | 01-MAR-05:12 | 3673.42 | 3673.42 | 7.24 | 36.10 |
April | 0.582327E+10 | 0.529336E+10 | 4041.17 | 01-APR-04:12 | 3673.42 | 3673.42 | 6.87 | 36.10 |
May | 0.672131E+10 | 0.610967E+10 | 4041.17 | 01-MAY-00:15 | 3673.42 | 3673.42 | 6.82 | 36.10 |
June | 0.772942E+10 | 0.702604E+10 | 4041.17 | 01-JUN-04:12 | 3673.42 | 3673.42 | 12.79 | 36.10 |
July | 0.932701E+10 | 0.847825E+10 | 4041.17 | 01-JUL-04:12 | 3673.42 | 3673.42 | 13.32 | 36.10 |
August | 0.988616E+10 | 0.898652E+10 | 4041.17 | 01-AUG-00:20 | 3673.42 | 3673.42 | 6.91 | 36.10 |
September | 0.670712E+10 | 0.609677E+10 | 4041.17 | 01-SEP-00:25 | 3673.42 | 3673.42 | 6.92 | 36.10 |
October | 0.433485E+10 | 0.394038E+10 | 4041.17 | 01-OCT-12:05 | 3673.42 | 3673.42 | 7.05 | 36.10 |
November | 0.337494E+10 | 0.306782E+10 | 4041.17 | 01-NOV-04:12 | 3673.42 | 3673.42 | 6.91 | 36.10 |
December | 0.253894E+10 | 0.230790E+10 | 4041.17 | 01-DEC-07:20 | 3673.42 | 3673.42 | 6.73 | 36.10 |
Annual Sum or Average | 0.633506E+11 | 0.575857E+11 | ||||||
Minimum of Months | 0.103148E+10 | 0.937612E+09 | 4041.17 | 3673.42 | 3673.42 | 6.72 | 36.10 | |
Maximum of Months | 0.988616E+10 | 0.898652E+10 | 4041.17 | 3673.42 | 3673.42 | 13.32 | 36.10 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.78 | 0.00 |
March | 40411653.38 | 36734192.92 | 4041.17 | 29-MAR-15:40 | 3673.42 | 3673.42 | 15.48 | 18.05 |
April | 0.108707E+09 | 98814978.96 | 4041.17 | 12-APR-12:30 | 3673.42 | 3673.42 | 15.30 | 18.05 |
May | 0.646586E+09 | 0.587747E+09 | 4041.17 | 03-MAY-14:30 | 3673.42 | 3673.42 | 15.60 | 18.05 |
June | 0.197039E+10 | 0.179109E+10 | 4041.17 | 01-JUN-09:00 | 3673.42 | 3673.42 | 15.02 | 18.05 |
July | 0.240118E+10 | 0.218267E+10 | 4041.17 | 01-JUL-05:05 | 3673.42 | 3673.42 | 15.63 | 18.05 |
August | 0.286551E+10 | 0.260475E+10 | 4041.17 | 01-AUG-07:10 | 3673.42 | 3673.42 | 15.42 | 18.05 |
September | 0.112522E+10 | 0.102283E+10 | 4041.17 | 01-SEP-10:30 | 3673.42 | 3673.42 | 15.05 | 18.05 |
October | 0.288539E+09 | 0.262282E+09 | 4041.17 | 02-OCT-10:05 | 3673.42 | 3673.42 | 11.37 | 36.10 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.88 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.944655E+10 | 0.858691E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.286551E+10 | 0.260475E+10 | 4041.17 | 3673.42 | 3673.42 | 15.63 | 36.10 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.898449E+10 | 0.816690E+10 | 3354.43 | 01-JAN-00:05 | 3049.17 | 3049.17 | 18.48 | 14.15 |
February | 0.811503E+10 | 0.737656E+10 | 3354.43 | 01-FEB-00:10 | 3049.17 | 3049.17 | 19.29 | 14.15 |
March | 0.898449E+10 | 0.816690E+10 | 3354.43 | 01-MAR-00:10 | 3049.17 | 3049.17 | 20.05 | 14.15 |
April | 0.869467E+10 | 0.790346E+10 | 3354.43 | 01-APR-00:10 | 3049.17 | 3049.17 | 20.83 | 14.15 |
May | 0.898449E+10 | 0.816690E+10 | 3354.43 | 01-MAY-00:05 | 3049.17 | 3049.17 | 22.49 | 14.15 |
June | 0.869467E+10 | 0.790346E+10 | 3354.43 | 01-JUN-00:10 | 3049.17 | 3049.17 | 30.41 | 14.15 |
July | 0.898449E+10 | 0.816690E+10 | 3354.43 | 01-JUL-00:10 | 3049.17 | 3049.17 | 35.93 | 14.15 |
August | 0.898449E+10 | 0.816690E+10 | 3354.43 | 01-AUG-00:05 | 3049.17 | 3049.17 | 43.26 | 14.15 |
September | 0.869467E+10 | 0.790346E+10 | 3354.43 | 01-SEP-00:05 | 3049.17 | 3049.17 | 27.45 | 14.15 |
October | 0.898449E+10 | 0.816690E+10 | 3354.43 | 01-OCT-00:10 | 3049.17 | 3049.17 | 19.36 | 14.15 |
November | 0.869467E+10 | 0.790346E+10 | 3354.43 | 01-NOV-00:10 | 3049.17 | 3049.17 | 19.99 | 14.15 |
December | 0.898449E+10 | 0.816690E+10 | 3354.43 | 01-DEC-00:10 | 3049.17 | 3049.17 | 20.37 | 14.15 |
Annual Sum or Average | 0.105785E+12 | 0.961587E+11 | ||||||
Minimum of Months | 0.811503E+10 | 0.737656E+10 | 3354.43 | 3049.17 | 3049.17 | 18.48 | 14.15 | |
Maximum of Months | 0.898449E+10 | 0.816690E+10 | 3354.43 | 3049.17 | 3049.17 | 43.26 | 14.15 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 55.85 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.13 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.79 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 55.86 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.31 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 56.79 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.98 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.62 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.22 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.48 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.35 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.03 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.85 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.31 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.391964E+10 | 0.356296E+10 | 15371.08 | 31-JAN-15:10 | 13972.31 | 13972.31 | 22.54 | 62.85 |
February | 0.720900E+10 | 0.655298E+10 | 15395.54 | 28-FEB-15:05 | 13994.54 | 13994.54 | 24.75 | 62.85 |
March | 0.152870E+11 | 0.138959E+11 | 30818.09 | 30-MAR-14:00 | 28013.64 | 28013.64 | 25.82 | 125.70 |
April | 0.225173E+11 | 0.204682E+11 | 30826.19 | 17-APR-15:00 | 28021.01 | 28021.01 | 26.14 | 125.70 |
May | 0.277142E+11 | 0.251922E+11 | 30883.12 | 31-MAY-14:00 | 28072.75 | 28072.75 | 28.34 | 125.70 |
June | 0.362693E+11 | 0.329688E+11 | 30895.34 | 12-JUN-10:05 | 28083.87 | 28083.87 | 28.84 | 125.70 |
July | 0.441664E+11 | 0.401472E+11 | 30895.34 | 05-JUL-07:20 | 28083.87 | 28083.87 | 28.94 | 125.70 |
August | 0.479254E+11 | 0.435642E+11 | 30895.34 | 01-AUG-09:10 | 28083.87 | 28083.87 | 29.04 | 125.70 |
September | 0.292158E+11 | 0.265572E+11 | 30895.34 | 05-SEP-10:05 | 28083.87 | 28083.87 | 29.43 | 125.70 |
October | 0.174912E+11 | 0.158995E+11 | 30895.34 | 18-OCT-14:50 | 28083.87 | 28083.87 | 28.82 | 125.70 |
November | 0.128310E+11 | 0.116633E+11 | 15387.24 | 08-NOV-15:40 | 13987.00 | 13987.00 | 24.00 | 62.85 |
December | 0.964852E+10 | 0.877050E+10 | 15383.19 | 12-DEC-14:00 | 13983.32 | 13983.32 | 23.63 | 62.85 |
Annual Sum or Average | 0.274195E+12 | 0.249243E+12 | ||||||
Minimum of Months | 0.391964E+10 | 0.356296E+10 | 15371.08 | 13972.31 | 13972.31 | 22.54 | 62.85 | |
Maximum of Months | 0.479254E+11 | 0.435642E+11 | 30895.34 | 28083.87 | 28083.87 | 29.43 | 125.70 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 35.73 | 35.73 | 61457.49 | 1478461.16 | 09-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29.02 | 29.02 | 35403.57 | 1712946.31 | 02-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 30.84 | 30.84 | 3023.66 | 1134747.97 | 23-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30.33 | 30.33 | 1320.20 | 850023.64 | 06-APR-05:03 |
May | 1.63 | 3173.85 | 17-MAY-12:20 | 52.56 | 52.56 | 633.46 | 141926.68 | 15-MAY-16:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 45.73 | 45.73 | 152.49 | 55162.47 | 02-JUN-16:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 45.96 | 45.96 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 45.96 | 45.96 | 40.21 | 31685.60 | 25-AUG-13:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 43.10 | 43.10 | 73.60 | 35104.15 | 23-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 44.23 | 44.23 | 1415.54 | 1090682.79 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32.12 | 32.12 | 7581.33 | 1516868.76 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 27.97 | 27.97 | 25487.95 | 1560247.66 | 21-DEC-05:01 |
Annual Sum or Average | 0.14 | 11284.76 | ||||||
Minimum of Months | 0.00 | 0.00 | 27.97 | 27.97 | 0.00 | 0.00 | ||
Maximum of Months | 1.63 | 3173.85 | 52.56 | 52.56 | 61457.49 | 1712946.31 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5106.12 | 312803.59 | 31-JAN-15:10 | 8.77 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 31558.77 | 846549.11 | 28-FEB-15:05 | 12.30 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 90897.71 | 1620775.05 | 30-MAR-14:47 | 12.06 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 194249.46 | 2203562.73 | 17-APR-15:00 | 13.99 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 357620.35 | 2107938.87 | 19-MAY-14:50 | 13.67 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 565193.41 | 2407633.67 | 30-JUN-05:04 | 14.67 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 622908.40 | 2615026.95 | 27-JUL-05:04 | 15.35 | 6.86 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 696360.50 | 2319310.10 | 21-AUG-05:05 | 14.37 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 429610.68 | 2383889.59 | 07-SEP-05:04 | 14.59 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 181411.60 | 1667213.61 | 18-OCT-12:05 | 12.21 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 60531.69 | 659953.74 | 08-NOV-15:40 | 11.06 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18477.49 | 588083.77 | 12-DEC-13:10 | 10.59 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 272677.95 | 0.00 | ||||||
Minimum of Months | 5106.12 | 312803.59 | 8.77 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 696360.50 | 2615026.95 | 15.35 | 6.86 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4758.02 | 328073.21 | 31-JAN-15:05 | 14.30 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 30877.87 | 857432.02 | 28-FEB-15:05 | 21.45 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 89965.41 | 1879503.80 | 30-MAR-15:00 | 16.91 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 193253.82 | 1864906.75 | 17-APR-15:00 | 15.47 | 6.85 | 0.00 | 0.00 | 01-APR-00:10 |
May | 355955.16 | 3090597.09 | 31-MAY-05:03 | 16.93 | 11.80 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 564942.92 | 3396316.51 | 30-JUN-04:12 | 17.95 | 12.31 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 622780.65 | 3379764.06 | 06-JUL-04:12 | 17.89 | 12.28 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 695701.89 | 3413702.13 | 21-AUG-05:02 | 18.00 | 12.33 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 428835.34 | 3479675.60 | 05-SEP-04:12 | 18.22 | 12.44 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 181851.15 | 3427875.36 | 19-OCT-04:12 | 18.05 | 12.36 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 59392.97 | 843827.26 | 04-NOV-05:03 | 15.43 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17626.78 | 594695.58 | 12-DEC-13:05 | 16.68 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 272014.09 | 0.00 | ||||||
Minimum of Months | 4758.02 | 328073.21 | 14.30 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 695701.89 | 3479675.60 | 21.45 | 12.44 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14299.31 | 178023.61 | 31-JAN-15:00 | 21.95 | 21.35 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 70858.99 | 740875.90 | 28-FEB-15:00 | 33.24 | 27.50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 219805.27 | 1228185.28 | 30-MAR-15:00 | 42.82 | 32.40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 582104.13 | 1446660.90 | 12-APR-14:00 | 47.06 | 34.49 | 0.00 | 0.00 | 01-APR-00:10 |
May | 312830.26 | 946204.23 | 16-MAY-16:00 | 37.30 | 31.81 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 780301.76 | 1363391.31 | 06-JUN-15:00 | 45.45 | 37.80 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1108087.72 | 1715884.37 | 08-JUL-16:00 | 52.24 | 41.51 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1344640.59 | 1811588.13 | 01-AUG-16:10 | 54.07 | 40.92 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 444014.80 | 1004944.52 | 07-SEP-16:00 | 38.45 | 33.76 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 233392.29 | 1120693.38 | 10-OCT-16:00 | 40.72 | 33.28 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 180008.42 | 1001946.16 | 05-NOV-16:00 | 38.39 | 28.67 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 154295.08 | 1113971.89 | 12-DEC-14:00 | 40.59 | 28.24 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 456396.69 | 0.00 | ||||||
Minimum of Months | 14299.31 | 178023.61 | 21.95 | 21.35 | 0.00 | 0.00 | ||
Maximum of Months | 1344640.59 | 1811588.13 | 54.07 | 41.51 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.33 | 57.33 | 14850.36 | 49688.84 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.77 | 56.77 | 14959.43 | 49711.69 | 06-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.22 | 57.22 | 15316.02 | 48920.84 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.49 | 56.49 | 13612.56 | 46273.70 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.00 | 58.00 | 13011.66 | 43148.44 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.18 | 57.18 | 12346.28 | 39636.44 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.43 | 57.43 | 10960.41 | 36991.45 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.06 | 57.06 | 11827.98 | 36879.51 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.87 | 57.87 | 11654.71 | 39097.81 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.34 | 57.34 | 12477.02 | 42627.92 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.88 | 56.88 | 13621.75 | 46035.42 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.42 | 56.42 | 14017.23 | 48554.52 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 13211.52 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.42 | 56.42 | 10960.41 | 36879.51 | ||
Maximum of Months | 0.00 | 0.00 | 58.00 | 58.00 | 15316.02 | 49711.69 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5378.97 | 377340.06 | 31-JAN-15:10 | 22.54 | 21.10 | 2351.61 | 154367.13 | 29-JAN-12:43 |
February | 35538.78 | 957723.98 | 28-FEB-15:05 | 24.75 | 21.10 | 2006.38 | 156611.03 | 02-FEB-14:00 |
March | 106344.50 | 2481917.27 | 30-MAR-14:00 | 25.82 | 22.12 | 2078.82 | 128939.24 | 20-MAR-07:50 |
April | 242122.62 | 2646674.15 | 17-APR-15:00 | 26.14 | 21.72 | 1567.97 | 112139.93 | 05-APR-10:50 |
May | 548663.17 | 3801928.49 | 31-MAY-14:00 | 28.34 | 25.02 | 161.25 | 50631.43 | 11-MAY-09:10 |
June | 1241820.44 | 5208144.58 | 28-JUN-12:05 | 31.01 | 27.09 | 66.51 | 42962.79 | 10-JUN-21:40 |
July | 1595473.85 | 5383950.72 | 31-JUL-12:05 | 31.35 | 27.37 | 4.05 | 8247.95 | 03-JUL-01:20 |
August | 1896079.22 | 5425766.43 | 10-AUG-12:05 | 31.43 | 27.39 | 3.77 | 7937.93 | 26-AUG-04:00 |
September | 843821.37 | 4861835.89 | 08-SEP-12:05 | 30.35 | 26.55 | 180.56 | 50717.24 | 18-SEP-05:40 |
October | 293716.86 | 4100429.11 | 18-OCT-15:20 | 28.90 | 25.80 | 608.74 | 87033.87 | 26-OCT-10:20 |
November | 68976.06 | 760987.84 | 08-NOV-15:40 | 24.00 | 21.10 | 2854.33 | 140447.26 | 20-NOV-16:50 |
December | 17053.30 | 664951.62 | 12-DEC-14:00 | 23.63 | 21.10 | 5532.96 | 156696.45 | 18-DEC-11:40 |
Annual Sum or Average | 578743.30 | 1449.96 | ||||||
Minimum of Months | 5378.97 | 377340.06 | 22.54 | 21.10 | 3.77 | 7937.93 | ||
Maximum of Months | 1896079.22 | 5425766.43 | 31.43 | 27.39 | 5532.96 | 156696.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.196128E+10 | 0.00 | 0.177040E+10 | 0.285860E+10 | 0.00 | 0.00 |
February | 0.780650E+09 | 0.00 | 0.897768E+10 | 0.355282E+10 | 0.00 | 0.00 |
March | 74903135.25 | 0.00 | 0.252309E+11 | 0.660844E+10 | 0.00 | 0.00 |
April | 0.123995E+09 | 0.00 | 0.537518E+11 | 0.835766E+10 | 0.00 | 0.00 |
May | 0.157947E+09 | 0.00 | 0.820911E+11 | 0.801791E+10 | 0.00 | 0.00 |
June | 52867493.35 | 0.00 | 0.127065E+12 | 0.108843E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.151134E+12 | 0.121149E+11 | 0.00 | 0.00 |
August | 2950631.21 | 0.00 | 0.176067E+12 | 0.143036E+11 | 0.00 | 0.00 |
September | 14011077.10 | 0.00 | 0.951072E+11 | 0.800909E+10 | 0.00 | 0.00 |
October | 32824672.92 | 0.00 | 0.453087E+11 | 0.653551E+10 | 0.00 | 0.00 |
November | 0.162621E+09 | 0.00 | 0.196559E+11 | 0.557341E+10 | 0.00 | 0.00 |
December | 0.402731E+09 | 0.00 | 0.146916E+11 | 0.473981E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.376678E+10 | 0.00 | 0.800851E+12 | 0.915561E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.177040E+10 | 0.285860E+10 | 0.00 | 0.00 |
Maximum of Months | 0.196128E+10 | 0.00 | 0.176067E+12 | 0.143036E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.129747E+12 | 0.00 | 0.974773E+10 | 0.233544E+11 | 0.00 | 0.00 |
February | 0.666958E+11 | 0.00 | 0.578968E+11 | 0.236829E+11 | 0.00 | 0.00 |
March | 0.554892E+10 | 0.00 | 0.185210E+12 | 0.370140E+11 | 0.00 | 0.00 |
April | 0.252030E+10 | 0.00 | 0.373903E+12 | 0.469043E+11 | 0.00 | 0.00 |
May | 0.123245E+10 | 0.00 | 0.705895E+12 | 0.639510E+11 | 0.00 | 0.00 |
June | 0.314128E+09 | 0.00 | 0.106729E+13 | 0.843624E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.120934E+13 | 0.876419E+11 | 0.00 | 0.00 |
August | 0.127941E+09 | 0.00 | 0.134036E+13 | 0.933172E+11 | 0.00 | 0.00 |
September | 0.152201E+09 | 0.00 | 0.811188E+12 | 0.608576E+11 | 0.00 | 0.00 |
October | 0.235877E+10 | 0.00 | 0.349259E+12 | 0.393287E+11 | 0.00 | 0.00 |
November | 0.139809E+11 | 0.00 | 0.116707E+12 | 0.276403E+11 | 0.00 | 0.00 |
December | 0.503477E+11 | 0.00 | 0.278513E+11 | 0.232844E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.273026E+12 | 0.00 | 0.625464E+13 | 0.611339E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.974773E+10 | 0.232844E+11 | 0.00 | 0.00 |
Maximum of Months | 0.129747E+12 | 0.00 | 0.134036E+13 | 0.933172E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.332385E+11 | 0.00 | 0.926077E+09 | 0.287351E+10 | 0.00 | 0.00 |
February | 0.182733E+11 | 0.00 | 0.456796E+10 | 0.248073E+10 | 0.00 | 0.00 |
March | 0.249138E+10 | 0.00 | 0.161113E+11 | 0.313314E+10 | 0.00 | 0.00 |
April | 0.729759E+09 | 0.00 | 0.379637E+11 | 0.418349E+10 | 0.00 | 0.00 |
May | 0.176960E+09 | 0.00 | 0.773518E+11 | 0.639077E+10 | 0.00 | 0.00 |
June | 25354848.82 | 0.00 | 0.119450E+12 | 0.896463E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.135290E+12 | 0.954514E+10 | 0.00 | 0.00 |
August | 11191757.89 | 0.00 | 0.148153E+12 | 0.101126E+11 | 0.00 | 0.00 |
September | 11207217.38 | 0.00 | 0.835506E+11 | 0.585562E+10 | 0.00 | 0.00 |
October | 0.154956E+10 | 0.00 | 0.327042E+11 | 0.337098E+10 | 0.00 | 0.00 |
November | 0.558332E+10 | 0.00 | 0.850273E+10 | 0.234510E+10 | 0.00 | 0.00 |
December | 0.176434E+11 | 0.00 | 0.220957E+10 | 0.255406E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.797340E+11 | 0.00 | 0.666781E+12 | 0.618097E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.926077E+09 | 0.234510E+10 | 0.00 | 0.00 |
Maximum of Months | 0.332385E+11 | 0.00 | 0.148153E+12 | 0.101126E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 75.82 | 0.00 | 0.430296E+09 | 0.122427E+11 | 0.00 | 0.00 |
February | 75.59 | 0.00 | 0.360632E+10 | 0.108346E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.111018E+11 | 0.129747E+11 | 0.00 | 0.00 |
April | 104.02 | 0.00 | 0.236845E+11 | 0.118673E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.431506E+11 | 0.125330E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.761541E+11 | 0.125179E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.880511E+11 | 0.123002E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.106873E+12 | 0.139232E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.654682E+11 | 0.129863E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.292103E+11 | 0.129384E+11 | 0.00 | 0.00 |
November | 193.78 | 0.00 | 0.945071E+10 | 0.125512E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.266609E+10 | 0.122460E+11 | 0.00 | 0.00 |
Annual Sum or Average | 449.22 | 0.00 | 0.459847E+12 | 0.149915E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.430296E+09 | 0.108346E+11 | 0.00 | 0.00 |
Maximum of Months | 193.78 | 0.00 | 0.106873E+12 | 0.139232E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.960429E+10 | 0.222825E+12 | 0.00 | 45.46 |
February | 0.00 | 0.00 | 0.295091E+11 | 0.264274E+12 | 0.00 | 62.72 |
March | 0.00 | 0.00 | 0.192393E+12 | 0.291401E+12 | 0.00 | 56.99 |
April | 0.00 | 0.00 | 0.671000E+12 | 0.313492E+12 | 0.00 | 30.51 |
May | 0.00 | 0.00 | 0.195453E+12 | 0.155719E+12 | 0.00 | 5.72 |
June | 0.00 | 0.00 | 0.633992E+12 | 0.250501E+12 | 0.00 | 6.00 |
July | 0.00 | 0.00 | 0.107272E+13 | 0.333249E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137973E+13 | 0.398786E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.305883E+12 | 0.160866E+12 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.193252E+12 | 0.179181E+12 | 0.00 | 15.24 |
November | 0.00 | 0.00 | 0.151840E+12 | 0.284145E+12 | 0.00 | 58.91 |
December | 0.00 | 0.00 | 0.118828E+12 | 0.324723E+12 | 0.00 | 75.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.495420E+13 | 0.317916E+13 | 0.00 | 357.08 |
Minimum of Months | 0.00 | 0.00 | 0.960429E+10 | 0.155719E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.137973E+13 | 0.398786E+12 | 0.00 | 75.33 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.446224E+10 | 0.226950E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103784E+11 | 0.313855E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.186623E+11 | 0.465746E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.244858E+11 | 0.575792E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.732016E+10 | 0.286298E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139759E+11 | 0.434220E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211754E+11 | 0.601593E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.277423E+11 | 0.746598E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.742392E+10 | 0.288875E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129572E+11 | 0.375765E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179198E+11 | 0.445828E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.239756E+11 | 0.539338E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190479E+12 | 0.530086E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.446224E+10 | 0.226950E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.277423E+11 | 0.746598E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.136690E+11 | 0.163061E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.778095E+11 | 0.264022E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.168089E+12 | 0.429197E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.229279E+12 | 0.543092E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.663974E+11 | 0.267127E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.131865E+12 | 0.411675E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201708E+12 | 0.573562E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.263892E+12 | 0.711134E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.668712E+11 | 0.268339E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113694E+12 | 0.342502E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.156070E+12 | 0.402405E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.203100E+12 | 0.476991E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169244E+13 | 0.485311E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.136690E+11 | 0.163061E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.263892E+12 | 0.711134E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.587405E+09 | 0.149746E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.630883E+10 | 0.240818E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.158605E+11 | 0.417520E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.225001E+11 | 0.540328E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.657054E+10 | 0.269158E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132983E+11 | 0.417302E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203431E+11 | 0.580741E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.265864E+11 | 0.719255E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.656421E+10 | 0.269215E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104791E+11 | 0.330969E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.140909E+11 | 0.381330E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.182053E+11 | 0.448266E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161395E+12 | 0.476465E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.587405E+09 | 0.149746E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.265864E+11 | 0.719255E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.285860E+10 | 0.177040E+10 | 0.196128E+10 | 0.162689E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355282E+10 | 0.897768E+10 | 0.780650E+09 | 0.835178E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.660844E+10 | 0.252309E+11 | 74903135.25 | 0.748735E+09 | 80452581.89 | 0.00 | 0.00 | 0.00 |
April | 0.835766E+10 | 0.537518E+11 | 0.123995E+09 | 0.216444E+09 | 0.271505E+09 | 0.00 | 0.00 | 0.00 |
May | 0.801791E+10 | 0.820911E+11 | 0.157947E+09 | 5168746.59 | 0.210890E+10 | 0.00 | 0.00 | 0.00 |
June | 0.108843E+11 | 0.127065E+12 | 52867493.35 | 0.00 | 0.137124E+11 | 0.00 | 0.00 | 0.00 |
July | 0.121149E+11 | 0.151134E+12 | 0.00 | 0.00 | 0.191671E+11 | 0.00 | 0.00 | 0.00 |
August | 0.143036E+11 | 0.176067E+12 | 2950631.21 | 0.00 | 0.237620E+11 | 0.00 | 0.00 | 0.00 |
September | 0.800909E+10 | 0.951072E+11 | 14011077.10 | 0.00 | 0.651355E+10 | 0.00 | 0.00 | 0.00 |
October | 0.653551E+10 | 0.453087E+11 | 32824672.92 | 0.236906E+09 | 0.124806E+10 | 0.00 | 0.00 | 0.00 |
November | 0.557341E+10 | 0.196559E+11 | 0.162621E+09 | 0.158537E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473981E+10 | 0.146916E+11 | 0.402731E+09 | 0.366299E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915561E+11 | 0.800851E+12 | 0.376678E+10 | 0.310763E+11 | 0.668640E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285860E+10 | 0.177040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143036E+11 | 0.176067E+12 | 0.196128E+10 | 0.162689E+11 | 0.237620E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.233544E+11 | 0.974773E+10 | 0.129747E+12 | 0.203224E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236829E+11 | 0.578968E+11 | 0.666958E+11 | 0.106771E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370140E+11 | 0.185210E+12 | 0.554892E+10 | 0.180558E+11 | 0.104418E+10 | 0.00 | 0.00 | 0.00 |
April | 0.469043E+11 | 0.373903E+12 | 0.252030E+10 | 0.447927E+10 | 0.261901E+10 | 0.00 | 0.00 | 0.00 |
May | 0.639510E+11 | 0.705895E+12 | 0.123245E+10 | 0.177375E+09 | 0.210346E+11 | 0.00 | 0.00 | 0.00 |
June | 0.843624E+11 | 0.106729E+13 | 0.314128E+09 | 0.00 | 0.138810E+12 | 0.00 | 0.00 | 0.00 |
July | 0.876419E+11 | 0.120934E+13 | 0.00 | 0.00 | 0.194107E+12 | 0.00 | 0.00 | 0.00 |
August | 0.933172E+11 | 0.134036E+13 | 0.127941E+09 | 0.00 | 0.238991E+12 | 0.00 | 0.00 | 0.00 |
September | 0.608576E+11 | 0.811188E+12 | 0.152201E+09 | 0.00 | 0.676367E+11 | 0.00 | 0.00 | 0.00 |
October | 0.393287E+11 | 0.349259E+12 | 0.235877E+10 | 0.689368E+10 | 0.129678E+11 | 0.00 | 0.00 | 0.00 |
November | 0.276403E+11 | 0.116707E+12 | 0.139809E+11 | 0.346309E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232844E+11 | 0.278513E+11 | 0.503477E+11 | 0.750427E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.611339E+12 | 0.625464E+13 | 0.273026E+12 | 0.449275E+12 | 0.677210E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.232844E+11 | 0.974773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.933172E+11 | 0.134036E+13 | 0.129747E+12 | 0.203224E+12 | 0.238991E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.287351E+10 | 0.926077E+09 | 0.332385E+11 | 0.219966E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248073E+10 | 0.456796E+10 | 0.182733E+11 | 0.120870E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.313314E+10 | 0.161113E+11 | 0.249138E+10 | 0.283537E+10 | 59335162.50 | 0.00 | 0.00 | 0.00 |
April | 0.418349E+10 | 0.379637E+11 | 0.729759E+09 | 0.736152E+09 | 0.130190E+09 | 0.00 | 0.00 | 0.00 |
May | 0.639077E+10 | 0.773518E+11 | 0.176960E+09 | 46478370.21 | 0.155264E+10 | 0.00 | 0.00 | 0.00 |
June | 0.896463E+10 | 0.119450E+12 | 25354848.82 | 0.00 | 0.125554E+11 | 0.00 | 0.00 | 0.00 |
July | 0.954514E+10 | 0.135290E+12 | 0.00 | 0.00 | 0.179815E+11 | 0.00 | 0.00 | 0.00 |
August | 0.101126E+11 | 0.148153E+12 | 11191757.89 | 0.00 | 0.223047E+11 | 0.00 | 0.00 | 0.00 |
September | 0.585562E+10 | 0.835506E+11 | 11207217.38 | 0.00 | 0.608960E+10 | 0.00 | 0.00 | 0.00 |
October | 0.337098E+10 | 0.327042E+11 | 0.154956E+10 | 0.138780E+10 | 0.913835E+09 | 0.00 | 0.00 | 0.00 |
November | 0.234510E+10 | 0.850273E+10 | 0.558332E+10 | 0.490996E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255406E+10 | 0.220957E+10 | 0.176434E+11 | 0.927076E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618097E+11 | 0.666781E+12 | 0.797340E+11 | 0.532701E+11 | 0.615872E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.234510E+10 | 0.926077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101126E+11 | 0.148153E+12 | 0.332385E+11 | 0.219966E+11 | 0.223047E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122427E+11 | 0.430296E+09 | 75.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108346E+11 | 0.360632E+10 | 75.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129747E+11 | 0.111018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118673E+11 | 0.236845E+11 | 104.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125330E+11 | 0.431506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125179E+11 | 0.761541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123002E+11 | 0.880511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139232E+11 | 0.106873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129863E+11 | 0.654682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129384E+11 | 0.292103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125512E+11 | 0.945071E+10 | 193.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122460E+11 | 0.266609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149915E+12 | 0.459847E+12 | 449.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108346E+11 | 0.430296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139232E+11 | 0.106873E+12 | 193.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.969734E+11 | 0.596588E+10 | 0.00 | 0.00 | 0.00 | 0.121665E+12 | 0.00 | 0.00 |
February | 0.875889E+11 | 0.214346E+11 | 0.00 | 0.00 | 0.00 | 0.167855E+12 | 0.00 | 0.00 |
March | 0.969734E+11 | 0.151165E+12 | 0.00 | 0.00 | 0.00 | 0.152513E+12 | 0.00 | 0.00 |
April | 0.938452E+11 | 0.533372E+12 | 0.00 | 0.00 | 0.00 | 0.816520E+11 | 0.00 | 0.00 |
May | 0.969734E+11 | 0.152078E+12 | 0.00 | 0.00 | 0.00 | 0.153019E+11 | 0.00 | 0.00 |
June | 0.938452E+11 | 0.493465E+12 | 0.00 | 0.00 | 0.00 | 0.160559E+11 | 0.00 | 0.00 |
July | 0.969734E+11 | 0.836442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.969734E+11 | 0.107792E+13 | 0.00 | 0.00 | 0.00 | 1327026.63 | 0.00 | 0.00 |
September | 0.938452E+11 | 0.239406E+12 | 0.00 | 0.00 | 0.00 | 0.541057E+09 | 0.00 | 0.00 |
October | 0.969734E+11 | 0.152017E+12 | 0.00 | 0.00 | 0.00 | 0.407887E+11 | 0.00 | 0.00 |
November | 0.938452E+11 | 0.119887E+12 | 0.00 | 0.00 | 0.00 | 0.157638E+12 | 0.00 | 0.00 |
December | 0.969734E+11 | 0.935717E+11 | 0.00 | 0.00 | 0.00 | 0.201586E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.114178E+13 | 0.387672E+13 | 0.00 | 0.00 | 0.00 | 0.955597E+12 | 0.00 | 0.00 |
Minimum of Months | 0.875889E+11 | 0.596588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.969734E+11 | 0.107792E+13 | 0.00 | 0.00 | 0.00 | 0.201586E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141801E+10 | 0.361075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128078E+10 | 0.852063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141801E+10 | 0.154228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137227E+10 | 0.201002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141801E+10 | 0.587519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137227E+10 | 0.110060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141801E+10 | 0.165775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141801E+10 | 0.216943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137227E+10 | 0.590744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141801E+10 | 0.106176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137227E+10 | 0.148338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141801E+10 | 0.200002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166959E+11 | 0.154166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128078E+10 | 0.361075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141801E+10 | 0.216943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135342E+11 | 0.108971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122245E+11 | 0.636318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135342E+11 | 0.138704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130976E+11 | 0.188067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135342E+11 | 0.532189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130976E+11 | 0.103795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135342E+11 | 0.157886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135342E+11 | 0.206312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130976E+11 | 0.531350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135342E+11 | 0.929785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130976E+11 | 0.128927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135342E+11 | 0.168935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159355E+12 | 0.136649E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122245E+11 | 0.108971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135342E+11 | 0.206312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137985E+10 | 0.469789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124631E+10 | 0.514697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137985E+10 | 0.130652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133533E+10 | 0.184322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137985E+10 | 0.525881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133533E+10 | 0.104606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137985E+10 | 0.159156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137985E+10 | 0.207737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133533E+10 | 0.520740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137985E+10 | 0.854925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133533E+10 | 0.116130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137985E+10 | 0.151025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162466E+11 | 0.129995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124631E+10 | 0.469789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137985E+10 | 0.207737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.285860E+10 | 0.196128E+10 | 0.177040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355282E+10 | 0.780650E+09 | 0.897768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.660844E+10 | 74903135.25 | 0.252309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.835766E+10 | 0.123995E+09 | 0.537518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.801791E+10 | 0.157947E+09 | 0.820911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108843E+11 | 52867493.35 | 0.127065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121149E+11 | 0.00 | 0.151134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143036E+11 | 2950631.21 | 0.176067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.800909E+10 | 14011077.10 | 0.951072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.653551E+10 | 32824672.92 | 0.453087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.557341E+10 | 0.162621E+09 | 0.196559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473981E+10 | 0.402731E+09 | 0.146916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915561E+11 | 0.376678E+10 | 0.800851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285860E+10 | 0.00 | 0.177040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143036E+11 | 0.196128E+10 | 0.176067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.233544E+11 | 0.129747E+12 | 0.974773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236829E+11 | 0.666958E+11 | 0.578968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370140E+11 | 0.554892E+10 | 0.185210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469043E+11 | 0.252030E+10 | 0.373903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.639510E+11 | 0.123245E+10 | 0.705895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843624E+11 | 0.314128E+09 | 0.106729E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.876419E+11 | 0.00 | 0.120934E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.933172E+11 | 0.127941E+09 | 0.134036E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.608576E+11 | 0.152201E+09 | 0.811188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.393287E+11 | 0.235877E+10 | 0.349259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276403E+11 | 0.139809E+11 | 0.116707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232844E+11 | 0.503477E+11 | 0.278513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.611339E+12 | 0.273026E+12 | 0.625464E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.232844E+11 | 0.00 | 0.974773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.933172E+11 | 0.129747E+12 | 0.134036E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.287351E+10 | 0.332385E+11 | 0.926077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248073E+10 | 0.182733E+11 | 0.456796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.313314E+10 | 0.249138E+10 | 0.161113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418349E+10 | 0.729759E+09 | 0.379637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.639077E+10 | 0.176960E+09 | 0.773518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.896463E+10 | 25354848.82 | 0.119450E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.954514E+10 | 0.00 | 0.135290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101126E+11 | 11191757.89 | 0.148153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.585562E+10 | 11207217.38 | 0.835506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337098E+10 | 0.154956E+10 | 0.327042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234510E+10 | 0.558332E+10 | 0.850273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255406E+10 | 0.176434E+11 | 0.220957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618097E+11 | 0.797340E+11 | 0.666781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.234510E+10 | 0.00 | 0.926077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101126E+11 | 0.332385E+11 | 0.148153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122427E+11 | 75.82 | 0.430296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108346E+11 | 75.59 | 0.360632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129747E+11 | 0.00 | 0.111018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118673E+11 | 104.02 | 0.236845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125330E+11 | 0.00 | 0.431506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125179E+11 | 0.00 | 0.761541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123002E+11 | 0.00 | 0.880511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139232E+11 | 0.00 | 0.106873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129863E+11 | 0.00 | 0.654682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129384E+11 | 0.00 | 0.292103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125512E+11 | 193.78 | 0.945071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122460E+11 | 0.00 | 0.266609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149915E+12 | 449.22 | 0.459847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108346E+11 | 0.00 | 0.430296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139232E+11 | 193.78 | 0.106873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.969734E+11 | 0.00 | 0.960429E+10 | 0.00 | 0.363841E+10 | 0.00 | 0.00 | 0.00 | 0.122213E+12 | 0.00 | 0.00 | 0.00 |
February | 0.875889E+11 | 0.00 | 0.295091E+11 | 0.00 | 0.807452E+10 | 0.00 | 0.00 | 0.00 | 0.168610E+12 | 0.00 | 0.00 | 0.00 |
March | 0.969734E+11 | 0.00 | 0.192393E+12 | 0.00 | 0.412285E+11 | 0.00 | 0.00 | 0.00 | 0.153199E+12 | 0.00 | 0.00 | 0.00 |
April | 0.938452E+11 | 0.00 | 0.671000E+12 | 0.00 | 0.137627E+12 | 0.00 | 0.00 | 0.00 | 0.820195E+11 | 0.00 | 0.00 | 0.00 |
May | 0.969734E+11 | 0.00 | 0.195453E+12 | 0.00 | 0.433744E+11 | 0.00 | 0.00 | 0.00 | 0.153708E+11 | 0.00 | 0.00 | 0.00 |
June | 0.938452E+11 | 0.00 | 0.633992E+12 | 0.00 | 0.140527E+12 | 0.00 | 0.00 | 0.00 | 0.161282E+11 | 0.00 | 0.00 | 0.00 |
July | 0.969734E+11 | 0.00 | 0.107272E+13 | 0.00 | 0.236275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.969734E+11 | 0.00 | 0.137973E+13 | 0.00 | 0.301811E+12 | 0.00 | 0.00 | 0.00 | 1333000.12 | 0.00 | 0.00 | 0.00 |
September | 0.938452E+11 | 0.00 | 0.305883E+12 | 0.00 | 0.664772E+11 | 0.00 | 0.00 | 0.00 | 0.543493E+09 | 0.00 | 0.00 | 0.00 |
October | 0.969734E+11 | 0.00 | 0.193252E+12 | 0.00 | 0.412351E+11 | 0.00 | 0.00 | 0.00 | 0.409723E+11 | 0.00 | 0.00 | 0.00 |
November | 0.938452E+11 | 0.00 | 0.151840E+12 | 0.00 | 0.319532E+11 | 0.00 | 0.00 | 0.00 | 0.158347E+12 | 0.00 | 0.00 | 0.00 |
December | 0.969734E+11 | 0.00 | 0.118828E+12 | 0.00 | 0.252565E+11 | 0.00 | 0.00 | 0.00 | 0.202493E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114178E+13 | 0.00 | 0.495420E+13 | 0.00 | 0.107748E+13 | 0.00 | 0.00 | 0.00 | 0.959899E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.875889E+11 | 0.00 | 0.960429E+10 | 0.00 | 0.363841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.969734E+11 | 0.00 | 0.137973E+13 | 0.00 | 0.301811E+12 | 0.00 | 0.00 | 0.00 | 0.202493E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141801E+10 | 0.00 | 0.446224E+10 | 0.00 | 0.851489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128078E+10 | 0.00 | 0.103784E+11 | 0.00 | 0.185777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141801E+10 | 0.00 | 0.186623E+11 | 0.00 | 0.323945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137227E+10 | 0.00 | 0.244858E+11 | 0.00 | 0.438565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141801E+10 | 0.00 | 0.732016E+10 | 0.00 | 0.144497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137227E+10 | 0.00 | 0.139759E+11 | 0.00 | 0.296993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141801E+10 | 0.00 | 0.211754E+11 | 0.00 | 0.459791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141801E+10 | 0.00 | 0.277423E+11 | 0.00 | 0.604797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137227E+10 | 0.00 | 0.742392E+10 | 0.00 | 0.151649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141801E+10 | 0.00 | 0.129572E+11 | 0.00 | 0.233964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137227E+10 | 0.00 | 0.179198E+11 | 0.00 | 0.308601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141801E+10 | 0.00 | 0.239756E+11 | 0.00 | 0.397537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166959E+11 | 0.00 | 0.190479E+12 | 0.00 | 0.363126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128078E+10 | 0.00 | 0.446224E+10 | 0.00 | 0.851489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141801E+10 | 0.00 | 0.277423E+11 | 0.00 | 0.604797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135342E+11 | 0.00 | 0.136690E+11 | 0.00 | 0.277190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122245E+11 | 0.00 | 0.778095E+11 | 0.00 | 0.141777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135342E+11 | 0.00 | 0.168089E+12 | 0.00 | 0.293855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130976E+11 | 0.00 | 0.229279E+12 | 0.00 | 0.412116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135342E+11 | 0.00 | 0.663974E+11 | 0.00 | 0.131785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130976E+11 | 0.00 | 0.131865E+12 | 0.00 | 0.280699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135342E+11 | 0.00 | 0.201708E+12 | 0.00 | 0.438220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135342E+11 | 0.00 | 0.263892E+12 | 0.00 | 0.575792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130976E+11 | 0.00 | 0.668712E+11 | 0.00 | 0.137363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135342E+11 | 0.00 | 0.113694E+12 | 0.00 | 0.207159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130976E+11 | 0.00 | 0.156070E+12 | 0.00 | 0.271429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135342E+11 | 0.00 | 0.203100E+12 | 0.00 | 0.341648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159355E+12 | 0.00 | 0.169244E+13 | 0.00 | 0.325956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122245E+11 | 0.00 | 0.136690E+11 | 0.00 | 0.277190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135342E+11 | 0.00 | 0.263892E+12 | 0.00 | 0.575792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137985E+10 | 0.00 | 0.587405E+09 | 0.00 | 0.117617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124631E+10 | 0.00 | 0.630883E+10 | 0.00 | 0.116186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137985E+10 | 0.00 | 0.158605E+11 | 0.00 | 0.279536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133533E+10 | 0.00 | 0.225001E+11 | 0.00 | 0.406795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137985E+10 | 0.00 | 0.657054E+10 | 0.00 | 0.131173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133533E+10 | 0.00 | 0.132983E+11 | 0.00 | 0.283769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137985E+10 | 0.00 | 0.203431E+11 | 0.00 | 0.442757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137985E+10 | 0.00 | 0.265864E+11 | 0.00 | 0.581270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133533E+10 | 0.00 | 0.656421E+10 | 0.00 | 0.135682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137985E+10 | 0.00 | 0.104791E+11 | 0.00 | 0.192984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133533E+10 | 0.00 | 0.140909E+11 | 0.00 | 0.247796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137985E+10 | 0.00 | 0.182053E+11 | 0.00 | 0.310282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162466E+11 | 0.00 | 0.161395E+12 | 0.00 | 0.313999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124631E+10 | 0.00 | 0.587405E+09 | 0.00 | 0.117617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137985E+10 | 0.00 | 0.265864E+11 | 0.00 | 0.581270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.492228E+10 | 0.00 | 0.00 | 75122006.65 | 0.00 | 0.00 | 0.509830E+11 | 0.00 | 0.53 |
February | 0.155991E+10 | 230306.20 | 0.00 | 73686912.42 | 0.00 | 0.00 | 0.468338E+11 | 0.00 | 0.70 |
March | 0.146693E+09 | 95279251.40 | 0.00 | 98583352.27 | 655196.21 | 0.00 | 0.538246E+11 | 0.00 | 1.03 |
April | 82032594.87 | 0.254495E+09 | 0.00 | 79972737.12 | 10707300.61 | 0.00 | 0.357495E+11 | 0.00 | 1.04 |
May | 33510849.33 | 0.204145E+10 | 0.00 | 67734825.72 | 23027488.61 | 0.00 | 0.226518E+11 | 0.00 | 1.02 |
June | 20885459.92 | 0.136676E+11 | 0.00 | 30837533.17 | 75397601.52 | 0.00 | 0.596184E+10 | 0.00 | 0.58 |
July | 29814471.87 | 0.206343E+11 | 0.00 | 13572963.66 | 0.233102E+09 | 0.00 | 0.216718E+10 | 0.00 | 0.39 |
August | 5538476.35 | 0.277415E+11 | 0.00 | 4381683.08 | 0.191444E+09 | 0.00 | 0.611506E+09 | 0.00 | 0.38 |
September | 0.126258E+09 | 0.854873E+10 | 0.00 | 52610530.99 | 76265691.94 | 0.00 | 0.150712E+11 | 0.00 | 0.81 |
October | 0.157605E+09 | 0.240936E+10 | 0.00 | 96782004.31 | 0.00 | 0.00 | 0.467361E+11 | 0.00 | 0.98 |
November | 0.225921E+09 | 12204796.06 | 0.00 | 0.118562E+09 | 0.00 | 0.00 | 0.614471E+11 | 0.00 | 1.03 |
December | 0.474166E+09 | 0.00 | 0.00 | 0.115531E+09 | 0.00 | 0.00 | 0.629589E+11 | 0.00 | 0.77 |
Annual Sum or Average | 0.778462E+10 | 0.754051E+11 | 0.00 | 0.827377E+09 | 0.610599E+09 | 0.00 | 0.404997E+12 | 0.00 | 0.77 |
Minimum of Months | 5538476.35 | 0.00 | 0.00 | 4381683.08 | 0.00 | 0.00 | 0.611506E+09 | 0.00 | 0.38 |
Maximum of Months | 0.492228E+10 | 0.277415E+11 | 0.00 | 0.118562E+09 | 0.233102E+09 | 0.00 | 0.629589E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.597147E+10 | 0.00 | 0.00 | 44805230.12 | 0.00 | 0.00 | 0.286938E+11 | 0.00 | 0.39 |
February | 0.308133E+10 | 0.00 | 0.00 | 56023053.80 | 0.00 | 0.00 | 0.307400E+11 | 0.00 | 0.51 |
March | 0.307145E+10 | 45079481.21 | 0.00 | 92186595.10 | 276635.86 | 0.00 | 0.423030E+11 | 0.00 | 0.79 |
April | 0.358917E+10 | 0.196128E+09 | 0.00 | 82452525.12 | 5136227.16 | 0.00 | 0.298660E+11 | 0.00 | 0.85 |
May | 0.726147E+09 | 0.112796E+10 | 0.00 | 54777142.04 | 24929517.87 | 0.00 | 0.137504E+11 | 0.00 | 0.64 |
June | 0.395941E+09 | 0.573212E+10 | 0.00 | 19967210.97 | 71255562.40 | 0.00 | 0.461296E+10 | 0.00 | 0.41 |
July | 0.206229E+09 | 0.833999E+10 | 0.00 | 3382091.45 | 0.197283E+09 | 0.00 | 0.349841E+09 | 0.00 | 0.27 |
August | 0.101901E+09 | 0.112870E+11 | 0.00 | 1791704.52 | 0.102741E+09 | 0.00 | 0.234915E+09 | 0.00 | 0.28 |
September | 0.349991E+09 | 0.421182E+10 | 0.00 | 36306469.54 | 0.137221E+09 | 0.00 | 0.964792E+10 | 0.00 | 0.52 |
October | 0.826104E+09 | 0.148390E+10 | 0.00 | 71149356.82 | 0.00 | 0.00 | 0.332702E+11 | 0.00 | 0.64 |
November | 0.175260E+10 | 39937942.68 | 0.00 | 88803837.44 | 0.00 | 0.00 | 0.420142E+11 | 0.00 | 0.69 |
December | 0.167835E+10 | 0.00 | 0.00 | 84925939.25 | 0.00 | 0.00 | 0.384723E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.217507E+11 | 0.324640E+11 | 0.00 | 0.636571E+09 | 0.538843E+09 | 0.00 | 0.273956E+12 | 0.00 | 0.54 |
Minimum of Months | 0.101901E+09 | 0.00 | 0.00 | 1791704.52 | 0.00 | 0.00 | 0.234915E+09 | 0.00 | 0.27 |
Maximum of Months | 0.597147E+10 | 0.112870E+11 | 0.00 | 92186595.10 | 0.197283E+09 | 0.00 | 0.423030E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197382E+12 | 0.00 | 0.00 | 27338504.47 | 0.00 | 0.213790E+10 | 0.305604E+11 | 0.00 | 0.32 |
February | 0.139428E+12 | 0.00 | 0.00 | 0.139244E+09 | 0.00 | 0.734628E+09 | 0.823372E+11 | 0.00 | 0.38 |
March | 0.636965E+11 | 0.255562E+09 | 0.00 | 0.473244E+09 | 0.138973E+09 | 0.00 | 0.238904E+12 | 0.00 | 0.54 |
April | 0.160634E+11 | 0.147472E+10 | 0.00 | 0.525074E+09 | 96917240.39 | 0.00 | 0.202910E+12 | 0.00 | 0.59 |
May | 0.734890E+10 | 0.104071E+11 | 0.00 | 0.446229E+09 | 0.269993E+09 | 0.00 | 0.113449E+12 | 0.00 | 0.56 |
June | 0.353482E+10 | 0.551742E+11 | 0.00 | 0.168710E+09 | 0.651463E+09 | 0.00 | 0.359573E+11 | 0.00 | 0.37 |
July | 0.572446E+09 | 0.803794E+11 | 0.00 | 29841807.93 | 0.205310E+10 | 0.00 | 0.283582E+10 | 0.00 | 0.26 |
August | 0.233090E+09 | 0.107609E+12 | 0.00 | 25776520.44 | 0.102830E+10 | 0.00 | 0.253200E+10 | 0.00 | 0.28 |
September | 0.587141E+10 | 0.414006E+11 | 0.00 | 0.281613E+09 | 0.129404E+10 | 0.00 | 0.748897E+11 | 0.00 | 0.45 |
October | 0.291389E+11 | 0.132610E+11 | 0.00 | 0.392374E+09 | 0.00 | 0.00 | 0.199069E+12 | 0.00 | 0.45 |
November | 0.659468E+11 | 74358403.65 | 0.00 | 0.354161E+09 | 0.364604E+09 | 0.00 | 0.203676E+12 | 0.00 | 0.44 |
December | 0.143756E+12 | 0.00 | 0.00 | 0.140816E+09 | 0.00 | 0.00 | 0.109021E+12 | 0.00 | 0.35 |
Annual Sum or Average | 0.672973E+12 | 0.310036E+12 | 0.00 | 0.300442E+10 | 0.589739E+10 | 0.287253E+10 | 0.129614E+13 | 0.00 | 0.42 |
Minimum of Months | 0.233090E+09 | 0.00 | 0.00 | 25776520.44 | 0.00 | 0.00 | 0.253200E+10 | 0.00 | 0.26 |
Maximum of Months | 0.197382E+12 | 0.107609E+12 | 0.00 | 0.525074E+09 | 0.205310E+10 | 0.213790E+10 | 0.238904E+12 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154268E+11 | 0.00 | 0.00 | 523736.97 | 0.00 | 0.216817E+10 | 0.580417E+09 | 0.00 | 0.30 |
February | 0.142789E+11 | 0.00 | 0.00 | 4514831.51 | 0.00 | 0.724229E+09 | 0.281748E+10 | 0.00 | 0.36 |
March | 0.110630E+11 | 8604730.70 | 0.00 | 24891363.58 | 11288572.96 | 7481991.65 | 0.137106E+11 | 0.00 | 0.50 |
April | 0.489237E+10 | 80546252.92 | 0.00 | 37563209.81 | 2963482.71 | 0.00 | 0.136198E+11 | 0.00 | 0.57 |
May | 0.114791E+10 | 0.930263E+09 | 0.00 | 41330548.90 | 22214830.36 | 0.00 | 0.939976E+10 | 0.00 | 0.57 |
June | 0.538005E+09 | 0.542523E+10 | 0.00 | 14272239.71 | 68653784.71 | 0.00 | 0.282180E+10 | 0.00 | 0.37 |
July | 80628434.86 | 0.765907E+10 | 0.00 | 2067386.45 | 0.402536E+09 | 0.00 | 0.194823E+09 | 0.00 | 0.25 |
August | 28018077.30 | 0.105324E+11 | 0.00 | 2213697.06 | 97807986.63 | 0.00 | 0.187404E+09 | 0.00 | 0.28 |
September | 0.145977E+10 | 0.392320E+10 | 0.00 | 22395703.28 | 0.133200E+09 | 0.00 | 0.525018E+10 | 0.00 | 0.43 |
October | 0.785261E+10 | 0.125861E+10 | 0.00 | 18552443.32 | 0.00 | 12189467.39 | 0.100835E+11 | 0.00 | 0.42 |
November | 0.139349E+11 | 0.00 | 0.00 | 9360161.67 | 70929479.34 | 0.197434E+09 | 0.634592E+10 | 0.00 | 0.40 |
December | 0.165371E+11 | 0.00 | 0.00 | 2887762.86 | 0.00 | 0.748702E+09 | 0.221886E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.872400E+11 | 0.298179E+11 | 0.00 | 0.180573E+09 | 0.809594E+09 | 0.385821E+10 | 0.672305E+11 | 0.00 | 0.40 |
Minimum of Months | 28018077.30 | 0.00 | 0.00 | 523736.97 | 0.00 | 0.00 | 0.187404E+09 | 0.00 | 0.25 |
Maximum of Months | 0.165371E+11 | 0.105324E+11 | 0.00 | 41330548.90 | 0.402536E+09 | 0.216817E+10 | 0.137106E+11 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262124E+10 | 0.00 | 0.00 | 384314.52 | 0.00 | 0.441972E+09 | 0.280102E+09 | 0.00 | 0.30 |
February | 0.228182E+10 | 0.00 | 0.00 | 1464538.90 | 0.00 | 0.144612E+09 | 0.680347E+09 | 0.00 | 0.40 |
March | 0.161821E+10 | 6998843.11 | 0.00 | 5355330.05 | 34699.97 | 0.00 | 0.258429E+10 | 0.00 | 0.64 |
April | 0.999827E+09 | 32235751.52 | 0.00 | 6929300.09 | 644265.51 | 0.00 | 0.238851E+10 | 0.00 | 0.82 |
May | 0.259695E+09 | 0.210640E+09 | 0.00 | 5647650.11 | 3127047.95 | 0.00 | 0.137812E+10 | 0.00 | 0.73 |
June | 0.100134E+09 | 0.114745E+10 | 0.00 | 2180864.43 | 8937981.14 | 0.00 | 0.510492E+09 | 0.00 | 0.57 |
July | 29142374.00 | 0.167979E+10 | 0.00 | 339368.12 | 24746278.06 | 0.00 | 37127193.71 | 0.00 | 0.41 |
August | 13136144.08 | 0.209929E+10 | 0.00 | 199465.62 | 12887403.69 | 0.00 | 27383938.26 | 0.00 | 0.41 |
September | 0.222118E+09 | 0.686376E+09 | 0.00 | 3382597.65 | 17212434.71 | 0.00 | 0.817044E+09 | 0.00 | 0.54 |
October | 0.113428E+10 | 0.216352E+09 | 0.00 | 3408714.60 | 0.00 | 0.00 | 0.174238E+10 | 0.00 | 0.49 |
November | 0.171817E+10 | 1905978.72 | 0.00 | 3673346.95 | 874596.59 | 845989.63 | 0.184975E+10 | 0.00 | 0.49 |
December | 0.240322E+10 | 0.00 | 0.00 | 1525866.62 | 0.00 | 4795045.80 | 0.791096E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.134010E+11 | 0.608103E+10 | 0.00 | 34491357.67 | 68464707.64 | 0.592225E+09 | 0.130866E+11 | 0.00 | 0.51 |
Minimum of Months | 13136144.08 | 0.00 | 0.00 | 199465.62 | 0.00 | 0.00 | 27383938.26 | 0.00 | 0.30 |
Maximum of Months | 0.262124E+10 | 0.209929E+10 | 0.00 | 6929300.09 | 24746278.06 | 0.441972E+09 | 0.258429E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157681E+10 | 0.00 | 0.00 | 623847.87 | 0.00 | 0.246095E+09 | 0.403215E+09 | 0.00 | 0.31 |
February | 0.127794E+10 | 0.00 | 0.00 | 2343758.25 | 0.00 | 72048616.36 | 0.107966E+10 | 0.00 | 0.47 |
March | 0.966650E+09 | 4564198.15 | 0.00 | 5695593.50 | 22357.20 | 0.00 | 0.264728E+10 | 0.00 | 0.81 |
April | 0.648539E+09 | 21495671.38 | 0.00 | 7438782.48 | 415100.41 | 0.00 | 0.249775E+10 | 0.00 | 1.12 |
May | 0.144761E+09 | 0.177979E+09 | 0.00 | 6102389.61 | 2014757.68 | 0.00 | 0.154049E+10 | 0.00 | 1.06 |
June | 64115111.72 | 0.913270E+09 | 0.00 | 2530843.73 | 5758743.20 | 0.00 | 0.614347E+09 | 0.00 | 0.77 |
July | 21223342.84 | 0.136072E+10 | 0.00 | 176584.03 | 15290913.22 | 0.00 | 20920222.76 | 0.00 | 0.50 |
August | 8621995.92 | 0.154905E+10 | 0.00 | 178041.75 | 8303357.02 | 0.00 | 22828605.08 | 0.00 | 0.49 |
September | 0.161156E+09 | 0.572066E+09 | 0.00 | 3581169.31 | 11089975.45 | 0.00 | 0.854008E+09 | 0.00 | 0.77 |
October | 0.654384E+09 | 0.146797E+09 | 0.00 | 4475741.54 | 0.00 | 0.00 | 0.210910E+10 | 0.00 | 0.69 |
November | 0.100313E+10 | 168005.03 | 0.00 | 3471907.43 | 1584954.49 | 6840974.05 | 0.164900E+10 | 0.00 | 0.54 |
December | 0.137918E+10 | 0.00 | 0.00 | 1721713.26 | 0.00 | 37344781.11 | 0.788669E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.790650E+10 | 0.474611E+10 | 0.00 | 38340372.74 | 44480158.67 | 0.362330E+09 | 0.142273E+11 | 0.00 | 0.66 |
Minimum of Months | 8621995.92 | 0.00 | 0.00 | 176584.03 | 0.00 | 0.00 | 20920222.76 | 0.00 | 0.31 |
Maximum of Months | 0.157681E+10 | 0.154905E+10 | 0.00 | 7438782.48 | 15290913.22 | 0.246095E+09 | 0.264728E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172226E+10 | 0.00 | 0.00 | 4912792.58 | 0.00 | 0.417074E+09 | 0.329081E+10 | 0.00 | 0.46 |
February | 0.162530E+10 | 0.00 | 0.00 | 7605309.40 | 0.00 | 0.145970E+09 | 0.322989E+10 | 0.00 | 0.67 |
March | 0.120654E+10 | 14582650.96 | 0.00 | 11713981.45 | 34755.82 | 0.00 | 0.529796E+10 | 0.00 | 1.05 |
April | 0.991267E+09 | 42382830.68 | 0.00 | 9905406.31 | 645302.36 | 0.00 | 0.315877E+10 | 0.00 | 1.07 |
May | 0.320557E+09 | 0.242978E+09 | 0.00 | 5914859.80 | 3132080.47 | 0.00 | 0.136194E+10 | 0.00 | 0.80 |
June | 0.141128E+09 | 0.116303E+10 | 0.00 | 1995272.28 | 8952365.47 | 0.00 | 0.413928E+09 | 0.00 | 0.57 |
July | 29352953.60 | 0.173886E+10 | 0.00 | 293690.68 | 23770784.48 | 0.00 | 34154913.24 | 0.00 | 0.42 |
August | 13157284.72 | 0.239505E+10 | 0.00 | 207512.38 | 11212753.35 | 0.00 | 27846792.37 | 0.00 | 0.48 |
September | 0.234821E+09 | 0.901999E+09 | 0.00 | 5061356.88 | 17240135.53 | 0.00 | 0.107201E+10 | 0.00 | 0.77 |
October | 0.885649E+09 | 0.296272E+09 | 0.00 | 10261988.94 | 0.00 | 0.00 | 0.451274E+10 | 0.00 | 0.96 |
November | 0.113812E+10 | 153725.34 | 0.00 | 13774097.88 | 2540790.74 | 20884491.48 | 0.524446E+10 | 0.00 | 0.91 |
December | 0.165981E+10 | 0.00 | 0.00 | 9136313.85 | 0.00 | 64768066.79 | 0.383592E+10 | 0.00 | 0.55 |
Annual Sum or Average | 0.996796E+10 | 0.679531E+10 | 0.00 | 80782582.42 | 67528968.22 | 0.648696E+09 | 0.314804E+11 | 0.00 | 0.72 |
Minimum of Months | 13157284.72 | 0.00 | 0.00 | 207512.38 | 0.00 | 0.00 | 27846792.37 | 0.00 | 0.42 |
Maximum of Months | 0.172226E+10 | 0.239505E+10 | 0.00 | 13774097.88 | 23770784.48 | 0.417074E+09 | 0.529796E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138256E+10 | 0.00 | 0.00 | 1832863.84 | 0.00 | 41766619.60 | 0.131010E+10 | 0.00 | 0.39 |
February | 0.762043E+09 | 0.00 | 0.00 | 5277309.41 | 0.00 | 1087982.51 | 0.251641E+10 | 0.00 | 0.71 |
March | 0.166163E+09 | 16658786.52 | 0.00 | 14308564.15 | 17569.60 | 0.00 | 0.621565E+10 | 0.00 | 1.59 |
April | 0.157412E+09 | 49214488.58 | 0.00 | 16797978.87 | 51124.59 | 0.00 | 0.524593E+10 | 0.00 | 2.01 |
May | 65976826.03 | 0.229085E+09 | 0.00 | 7565883.05 | 274829.47 | 0.00 | 0.178769E+10 | 0.00 | 1.31 |
June | 25961106.35 | 0.124350E+10 | 0.00 | 3291342.03 | 3938347.45 | 0.00 | 0.688500E+09 | 0.00 | 1.01 |
July | 5355567.65 | 0.194897E+10 | 0.00 | 759242.80 | 8461209.29 | 0.00 | 73863029.57 | 0.00 | 0.74 |
August | 445550.36 | 0.272795E+10 | 0.00 | 525533.52 | 1055907.55 | 0.00 | 55836767.45 | 0.00 | 0.84 |
September | 35203742.96 | 0.750173E+09 | 0.00 | 4679709.72 | 8719700.07 | 0.00 | 0.107246E+10 | 0.00 | 0.97 |
October | 0.106404E+09 | 0.243045E+09 | 0.00 | 8623302.39 | 0.00 | 0.00 | 0.382482E+10 | 0.00 | 1.09 |
November | 0.202879E+09 | 4414124.22 | 0.00 | 10730823.98 | 0.00 | 0.00 | 0.483512E+10 | 0.00 | 1.12 |
December | 0.276739E+09 | 0.00 | 0.00 | 8593649.02 | 0.00 | 0.00 | 0.416808E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.318714E+10 | 0.721300E+10 | 0.00 | 82986202.79 | 22518688.03 | 42854602.11 | 0.317945E+11 | 0.00 | 1.04 |
Minimum of Months | 445550.36 | 0.00 | 0.00 | 525533.52 | 0.00 | 0.00 | 55836767.45 | 0.00 | 0.39 |
Maximum of Months | 0.138256E+10 | 0.272795E+10 | 0.00 | 16797978.87 | 8719700.07 | 41766619.60 | 0.621565E+10 | 0.00 | 2.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.937760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213439E+11 | 0.00 | 0.00 | 0.33 |
February | 0.145795E+11 | 0.00 | 0.00 | 2305783.44 | 0.00 | 0.123643E+11 | 0.494529E+09 | 0.00 | 0.36 |
March | 0.235536E+11 | 35962665.27 | 0.00 | 15966736.31 | 20339617.12 | 0.137622E+10 | 0.622434E+10 | 0.00 | 0.46 |
April | 0.126987E+11 | 0.242626E+09 | 0.00 | 34032558.35 | 7778906.81 | 0.313755E+09 | 0.919059E+10 | 0.00 | 0.56 |
May | 0.476374E+10 | 0.202712E+10 | 0.00 | 40109413.78 | 36071609.09 | 0.00 | 0.852536E+10 | 0.00 | 0.63 |
June | 0.139203E+10 | 0.119248E+11 | 0.00 | 16950653.70 | 81900620.62 | 0.00 | 0.335347E+10 | 0.00 | 0.56 |
July | 0.189852E+09 | 0.175986E+11 | 0.00 | 1865827.69 | 0.247415E+09 | 0.00 | 0.228366E+09 | 0.00 | 0.43 |
August | 52811630.54 | 0.218026E+11 | 0.00 | 2054625.25 | 0.129275E+09 | 0.00 | 0.249301E+09 | 0.00 | 0.45 |
September | 0.385081E+10 | 0.682585E+10 | 0.00 | 21760478.91 | 0.165121E+09 | 0.00 | 0.465054E+10 | 0.00 | 0.48 |
October | 0.187832E+11 | 0.187618E+10 | 0.00 | 7909718.32 | 17298773.90 | 0.435942E+09 | 0.335011E+10 | 0.00 | 0.38 |
November | 0.228094E+11 | 0.00 | 0.00 | 3580920.36 | 55185482.05 | 0.388833E+10 | 0.167123E+10 | 0.00 | 0.37 |
December | 0.191170E+11 | 0.00 | 0.00 | 1147685.60 | 0.00 | 0.113237E+11 | 0.384854E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.131168E+12 | 0.623337E+11 | 0.00 | 0.147684E+09 | 0.760387E+09 | 0.510462E+11 | 0.383227E+11 | 0.00 | 0.44 |
Minimum of Months | 52811630.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.235536E+11 | 0.218026E+11 | 0.00 | 40109413.78 | 0.247415E+09 | 0.213439E+11 | 0.919059E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.667443E+10 | 0.00 | 0.00 | 250142.41 | 0.00 | 0.959337E+10 | 0.189252E+09 | 0.00 | 0.27 |
February | 0.729169E+10 | 0.00 | 0.00 | 10620458.97 | 0.00 | 0.549023E+10 | 0.451589E+10 | 0.00 | 0.36 |
March | 0.918479E+10 | 42899077.79 | 0.00 | 35052554.46 | 470735.63 | 0.595479E+09 | 0.154651E+11 | 0.00 | 0.59 |
April | 0.477159E+10 | 0.203937E+09 | 0.00 | 61792980.32 | 4865707.48 | 0.138371E+09 | 0.192564E+11 | 0.00 | 0.93 |
May | 0.202014E+10 | 0.180844E+10 | 0.00 | 54118941.55 | 21709565.98 | 0.00 | 0.127777E+11 | 0.00 | 1.00 |
June | 0.607731E+09 | 0.101881E+11 | 0.00 | 24586774.07 | 52848247.08 | 0.00 | 0.562650E+10 | 0.00 | 0.82 |
July | 0.114768E+09 | 0.158604E+11 | 0.00 | 1700616.18 | 0.153075E+09 | 0.00 | 0.196188E+09 | 0.00 | 0.58 |
August | 33423802.62 | 0.186506E+11 | 0.00 | 2568250.00 | 83417889.17 | 0.00 | 0.281045E+09 | 0.00 | 0.61 |
September | 0.195757E+10 | 0.602692E+10 | 0.00 | 30182553.46 | 0.104504E+09 | 0.00 | 0.679323E+10 | 0.00 | 0.74 |
October | 0.710131E+10 | 0.136923E+10 | 0.00 | 28676675.83 | 9038083.68 | 0.325640E+09 | 0.127149E+11 | 0.00 | 0.53 |
November | 0.102676E+11 | 0.00 | 0.00 | 12360844.16 | 35609693.42 | 0.139623E+10 | 0.552431E+10 | 0.00 | 0.35 |
December | 0.107090E+11 | 0.00 | 0.00 | 1872319.99 | 0.00 | 0.447518E+10 | 0.983160E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.607340E+11 | 0.541506E+11 | 0.00 | 0.263783E+09 | 0.465539E+09 | 0.220145E+11 | 0.843236E+11 | 0.00 | 0.59 |
Minimum of Months | 33423802.62 | 0.00 | 0.00 | 250142.41 | 0.00 | 0.00 | 0.189252E+09 | 0.00 | 0.27 |
Maximum of Months | 0.107090E+11 | 0.186506E+11 | 0.00 | 61792980.32 | 0.153075E+09 | 0.959337E+10 | 0.192564E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119583E+11 | 0.00 | 0.00 | 37550748.83 | 0.00 | 0.970593E+10 | 0.228662E+11 | 0.00 | 0.47 |
February | 0.127500E+11 | 0.00 | 0.00 | 56148806.46 | 0.00 | 0.568471E+10 | 0.240920E+11 | 0.00 | 0.61 |
March | 0.138588E+11 | 0.164953E+09 | 0.00 | 90118943.82 | 729586.84 | 0.553102E+09 | 0.361599E+11 | 0.00 | 0.83 |
April | 0.940499E+10 | 0.395271E+09 | 0.00 | 74912627.51 | 7541294.80 | 0.155696E+09 | 0.208420E+11 | 0.00 | 0.85 |
May | 0.469791E+10 | 0.242901E+10 | 0.00 | 48297900.93 | 36075206.97 | 0.00 | 0.992374E+10 | 0.00 | 0.74 |
June | 0.166544E+10 | 0.121620E+11 | 0.00 | 16397331.55 | 81908789.63 | 0.00 | 0.293477E+10 | 0.00 | 0.57 |
July | 0.184805E+09 | 0.184662E+11 | 0.00 | 1796512.94 | 0.247440E+09 | 0.00 | 0.222109E+09 | 0.00 | 0.45 |
August | 51803103.57 | 0.260417E+11 | 0.00 | 2610740.46 | 0.129288E+09 | 0.00 | 0.270623E+09 | 0.00 | 0.54 |
September | 0.338604E+10 | 0.980277E+10 | 0.00 | 44222462.17 | 0.161969E+09 | 0.00 | 0.833997E+10 | 0.00 | 0.76 |
October | 0.995584E+10 | 0.299947E+10 | 0.00 | 89166835.90 | 0.00 | 0.340837E+09 | 0.352811E+11 | 0.00 | 0.83 |
November | 0.131514E+11 | 0.00 | 0.00 | 0.111519E+09 | 55190986.41 | 0.979617E+09 | 0.396808E+11 | 0.00 | 0.75 |
December | 0.148919E+11 | 0.00 | 0.00 | 64017432.91 | 0.00 | 0.430846E+10 | 0.362118E+11 | 0.00 | 0.61 |
Annual Sum or Average | 0.959573E+11 | 0.724613E+11 | 0.00 | 0.636760E+09 | 0.720144E+09 | 0.217284E+11 | 0.236825E+12 | 0.00 | 0.67 |
Minimum of Months | 51803103.57 | 0.00 | 0.00 | 1796512.94 | 0.00 | 0.00 | 0.222109E+09 | 0.00 | 0.45 |
Maximum of Months | 0.148919E+11 | 0.260417E+11 | 0.00 | 0.111519E+09 | 0.247440E+09 | 0.970593E+10 | 0.396808E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898089E+10 | 0.00 | 0.00 | 2261729.03 | 0.00 | 0.895913E+10 | 0.175961E+10 | 0.00 | 0.33 |
February | 0.103793E+11 | 0.00 | 0.00 | 11299135.60 | 0.00 | 0.469883E+10 | 0.425498E+10 | 0.00 | 0.43 |
March | 0.104844E+11 | 0.135926E+09 | 0.00 | 44060841.31 | 467380.07 | 0.311290E+09 | 0.168676E+11 | 0.00 | 0.73 |
April | 0.492611E+10 | 0.351636E+09 | 0.00 | 65266835.34 | 2648248.77 | 64264388.32 | 0.173974E+11 | 0.00 | 1.01 |
May | 0.208822E+10 | 0.207449E+10 | 0.00 | 47398398.69 | 5243196.45 | 0.00 | 0.102830E+11 | 0.00 | 1.02 |
June | 0.693581E+09 | 0.108990E+11 | 0.00 | 19031684.79 | 34879112.93 | 0.00 | 0.328419E+10 | 0.00 | 0.83 |
July | 73072570.55 | 0.162521E+11 | 0.00 | 2484104.86 | 0.111513E+09 | 0.00 | 0.273696E+09 | 0.00 | 0.62 |
August | 25533933.98 | 0.214576E+11 | 0.00 | 2309450.82 | 24466039.02 | 0.00 | 0.236558E+09 | 0.00 | 0.68 |
September | 0.190636E+10 | 0.672956E+10 | 0.00 | 26973494.67 | 85914465.70 | 0.00 | 0.509497E+10 | 0.00 | 0.76 |
October | 0.871920E+10 | 0.174821E+10 | 0.00 | 28920040.31 | 0.00 | 0.115276E+09 | 0.111038E+11 | 0.00 | 0.58 |
November | 0.127533E+11 | 0.00 | 0.00 | 19529042.65 | 35355855.47 | 0.966505E+09 | 0.757971E+10 | 0.00 | 0.46 |
December | 0.134672E+11 | 0.00 | 0.00 | 6330894.93 | 0.00 | 0.371273E+10 | 0.362947E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.744972E+11 | 0.596485E+11 | 0.00 | 0.275866E+09 | 0.300488E+09 | 0.188280E+11 | 0.817651E+11 | 0.00 | 0.65 |
Minimum of Months | 25533933.98 | 0.00 | 0.00 | 2261729.03 | 0.00 | 0.00 | 0.236558E+09 | 0.00 | 0.33 |
Maximum of Months | 0.134672E+11 | 0.214576E+11 | 0.00 | 65266835.34 | 0.111513E+09 | 0.895913E+10 | 0.173974E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.531229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206532E+10 | 0.00 | 0.00 | 0.35 |
February | 0.103366E+10 | 0.00 | 0.00 | 141965.97 | 0.00 | 0.128822E+10 | 40936412.28 | 0.00 | 0.37 |
March | 0.199642E+10 | 889004.52 | 0.00 | 1423982.08 | 1822384.18 | 0.390806E+09 | 0.516848E+09 | 0.00 | 0.47 |
April | 0.120947E+10 | 12796428.35 | 0.00 | 3316887.78 | 293844.56 | 90385119.90 | 0.793706E+09 | 0.00 | 0.57 |
May | 0.450399E+09 | 0.172355E+09 | 0.00 | 4382863.21 | 3470223.66 | 499506.03 | 0.805217E+09 | 0.00 | 0.66 |
June | 0.141899E+09 | 0.110769E+10 | 0.00 | 1637847.69 | 8621053.27 | 0.00 | 0.292621E+09 | 0.00 | 0.54 |
July | 16159499.35 | 0.162281E+10 | 0.00 | 161663.09 | 23833407.18 | 0.00 | 17037926.84 | 0.00 | 0.40 |
August | 9401971.05 | 0.203729E+10 | 0.00 | 188557.75 | 12249988.86 | 0.00 | 16210471.55 | 0.00 | 0.43 |
September | 0.379680E+09 | 0.627097E+09 | 0.00 | 2032606.45 | 20544717.46 | 0.00 | 0.402627E+09 | 0.00 | 0.47 |
October | 0.152217E+10 | 0.174194E+09 | 0.00 | 579925.73 | 2899631.73 | 0.279274E+09 | 0.246356E+09 | 0.00 | 0.39 |
November | 0.176226E+10 | 0.00 | 5091089.25 | 170439.63 | 3780584.78 | 0.676608E+09 | 95646573.47 | 11908.61 | 0.38 |
December | 0.104443E+10 | 0.00 | 0.00 | 53557.99 | 0.00 | 0.149497E+10 | 41151021.77 | 0.00 | 0.34 |
Annual Sum or Average | 0.100972E+11 | 0.575513E+10 | 5091089.25 | 14090297.38 | 77515835.67 | 0.628607E+10 | 0.326836E+10 | 11908.61 | 0.45 |
Minimum of Months | 9401971.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.199642E+10 | 0.203729E+10 | 5091089.25 | 4382863.21 | 23833407.18 | 0.206532E+10 | 0.805217E+09 | 11908.61 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.583369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105256E+10 | 0.00 | 0.00 | 0.33 |
February | 0.648562E+09 | 0.00 | 0.00 | 739360.43 | 0.00 | 0.623854E+09 | 0.343056E+09 | 0.00 | 0.40 |
March | 0.893135E+09 | 2076480.31 | 0.00 | 2975916.16 | 27041.14 | 0.169833E+09 | 0.133054E+10 | 0.00 | 0.61 |
April | 0.444671E+09 | 10931258.60 | 0.00 | 6410582.08 | 189501.04 | 26757937.33 | 0.183590E+10 | 0.00 | 0.98 |
May | 0.183955E+09 | 0.163523E+09 | 0.00 | 6041407.98 | 2199068.01 | 0.00 | 0.126699E+10 | 0.00 | 1.09 |
June | 57308220.99 | 0.991513E+09 | 0.00 | 2436304.26 | 5101903.13 | 0.00 | 0.548814E+09 | 0.00 | 0.83 |
July | 10459286.02 | 0.153114E+10 | 0.00 | 145818.40 | 14533390.71 | 0.00 | 14205544.97 | 0.00 | 0.58 |
August | 4798573.30 | 0.181462E+10 | 0.00 | 275880.47 | 6837166.56 | 0.00 | 23393210.13 | 0.00 | 0.61 |
September | 0.193704E+09 | 0.600208E+09 | 0.00 | 2998893.82 | 12194211.34 | 0.00 | 0.681946E+09 | 0.00 | 0.77 |
October | 0.670777E+09 | 0.137603E+09 | 0.00 | 2367050.16 | 1600322.70 | 0.139220E+09 | 0.107287E+10 | 0.00 | 0.56 |
November | 0.108239E+10 | 0.00 | 3286024.88 | 627824.96 | 2438107.94 | 0.270808E+09 | 0.344732E+09 | 4910.34 | 0.40 |
December | 0.920103E+09 | 0.00 | 0.00 | 92661.00 | 0.00 | 0.690460E+09 | 38619082.88 | 0.00 | 0.34 |
Annual Sum or Average | 0.569323E+10 | 0.525161E+10 | 3286024.88 | 25111699.72 | 45120712.56 | 0.297349E+10 | 0.750107E+10 | 4910.34 | 0.63 |
Minimum of Months | 4798573.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.108239E+10 | 0.181462E+10 | 3286024.88 | 6410582.08 | 14533390.71 | 0.105256E+10 | 0.183590E+10 | 4910.34 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.841595E+09 | 0.00 | 0.00 | 2380788.39 | 0.00 | 0.991721E+09 | 0.152324E+10 | 0.00 | 0.41 |
February | 0.912015E+09 | 0.00 | 0.00 | 4141127.11 | 0.00 | 0.655951E+09 | 0.199594E+10 | 0.00 | 0.58 |
March | 0.125388E+10 | 8586930.43 | 0.00 | 7461438.55 | 41966.84 | 0.214097E+09 | 0.336994E+10 | 0.00 | 0.84 |
April | 0.866269E+09 | 20009822.19 | 0.00 | 7828910.49 | 294098.55 | 55264473.64 | 0.201873E+10 | 0.00 | 0.87 |
May | 0.426060E+09 | 0.202784E+09 | 0.00 | 5444256.55 | 3488732.62 | 0.00 | 0.100068E+10 | 0.00 | 0.77 |
June | 0.160068E+09 | 0.112320E+10 | 0.00 | 1650432.47 | 8947428.56 | 0.00 | 0.279635E+09 | 0.00 | 0.55 |
July | 15958244.14 | 0.168770E+10 | 0.00 | 155177.66 | 23854008.25 | 0.00 | 16540035.38 | 0.00 | 0.42 |
August | 8585792.12 | 0.240550E+10 | 0.00 | 252421.42 | 10468881.09 | 0.00 | 18991628.22 | 0.00 | 0.51 |
September | 0.323299E+09 | 0.889015E+09 | 0.00 | 4443953.46 | 18338811.05 | 0.00 | 0.837465E+09 | 0.00 | 0.76 |
October | 0.852618E+09 | 0.272130E+09 | 0.00 | 7576518.02 | 2483641.17 | 0.148087E+09 | 0.337470E+10 | 0.00 | 0.86 |
November | 0.116133E+10 | 0.00 | 0.00 | 7907877.13 | 8891261.41 | 0.275397E+09 | 0.323942E+10 | 0.00 | 0.74 |
December | 0.109787E+10 | 0.00 | 0.00 | 4199812.56 | 0.00 | 0.571105E+09 | 0.245574E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.791955E+10 | 0.660893E+10 | 0.00 | 53442713.82 | 76808829.54 | 0.291162E+10 | 0.201310E+11 | 0.00 | 0.65 |
Minimum of Months | 8585792.12 | 0.00 | 0.00 | 155177.66 | 0.00 | 0.00 | 16540035.38 | 0.00 | 0.41 |
Maximum of Months | 0.125388E+10 | 0.240550E+10 | 0.00 | 7907877.13 | 23854008.25 | 0.991721E+09 | 0.337470E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.617119E+09 | 0.00 | 0.00 | 126987.77 | 0.00 | 0.895898E+09 | 0.112201E+09 | 0.00 | 0.33 |
February | 0.763238E+09 | 0.00 | 0.00 | 870785.00 | 0.00 | 0.519105E+09 | 0.395881E+09 | 0.00 | 0.43 |
March | 0.972509E+09 | 6163081.28 | 0.00 | 3784921.80 | 27044.28 | 0.120576E+09 | 0.163372E+10 | 0.00 | 0.77 |
April | 0.506725E+09 | 19237508.12 | 0.00 | 6808904.67 | 102127.05 | 30475832.16 | 0.166160E+10 | 0.00 | 1.04 |
May | 0.204452E+09 | 0.169323E+09 | 0.00 | 5406659.17 | 880935.20 | 0.00 | 0.102769E+10 | 0.00 | 1.05 |
June | 78097988.00 | 0.982318E+09 | 0.00 | 1876722.24 | 4073973.23 | 0.00 | 0.306744E+09 | 0.00 | 0.79 |
July | 7017299.28 | 0.145588E+10 | 0.00 | 229650.31 | 10990833.05 | 0.00 | 20554368.04 | 0.00 | 0.57 |
August | 2156532.74 | 0.195522E+10 | 0.00 | 225793.94 | 2203400.28 | 0.00 | 18625639.38 | 0.00 | 0.64 |
September | 0.194351E+09 | 0.612724E+09 | 0.00 | 2678841.88 | 7987541.96 | 0.00 | 0.477102E+09 | 0.00 | 0.75 |
October | 0.805292E+09 | 0.162073E+09 | 0.00 | 2443704.85 | 0.00 | 68835832.29 | 0.103195E+10 | 0.00 | 0.61 |
November | 0.103168E+10 | 9041.04 | 0.00 | 1376343.21 | 5720668.37 | 0.243910E+09 | 0.686474E+09 | 0.00 | 0.48 |
December | 0.923561E+09 | 0.00 | 0.00 | 385381.08 | 0.00 | 0.513030E+09 | 0.253523E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.610620E+10 | 0.536295E+10 | 0.00 | 26214695.92 | 31986523.42 | 0.239183E+10 | 0.762607E+10 | 0.00 | 0.65 |
Minimum of Months | 2156532.74 | 0.00 | 0.00 | 126987.77 | 0.00 | 0.00 | 18625639.38 | 0.00 | 0.33 |
Maximum of Months | 0.103168E+10 | 0.195522E+10 | 0.00 | 6808904.67 | 10990833.05 | 0.895898E+09 | 0.166160E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2879170.02 | 0.00 | 0.00 | 0.593693E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7343583.29 | 0.00 | 0.00 | 0.444697E+09 | 0.00 | 0.28 |
March | 0.00 | 4367351.49 | 0.00 | 12937646.87 | 0.00 | 0.00 | 0.338731E+09 | 0.00 | 0.30 |
April | 0.00 | 11496946.47 | 0.00 | 15256570.86 | 0.00 | 0.00 | 0.184368E+09 | 0.00 | 0.29 |
May | 0.00 | 65896501.31 | 0.00 | 1437369.82 | 0.00 | 0.00 | 59055374.12 | 0.00 | 0.29 |
June | 0.00 | 0.278694E+09 | 0.00 | 1383231.15 | 0.00 | 0.00 | 26924852.75 | 0.00 | 0.30 |
July | 0.00 | 0.392708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.476848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.154903E+09 | 0.00 | 1262944.84 | 0.00 | 0.00 | 33360726.37 | 0.00 | 0.29 |
October | 0.00 | 50565613.23 | 0.00 | 6364375.87 | 0.00 | 0.00 | 0.239816E+09 | 0.00 | 0.28 |
November | 0.00 | 3692186.12 | 0.00 | 11681063.32 | 0.00 | 0.00 | 0.354207E+09 | 0.00 | 0.28 |
December | 0.00 | 470238.83 | 0.00 | 16980450.09 | 0.00 | 0.00 | 0.448120E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.143964E+10 | 0.00 | 77526406.13 | 0.00 | 0.00 | 0.272297E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.476848E+09 | 0.00 | 16980450.09 | 0.00 | 0.00 | 0.593693E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169603E+10 | 0.00 | 0.00 | 9168247.27 | 0.00 | 0.00 | 0.427070E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 56695930.41 | 0.00 | 0.00 | 0.446682E+10 | 0.00 | 0.28 |
March | 0.00 | 43282996.09 | 0.00 | 0.117041E+09 | 0.00 | 0.00 | 0.339628E+10 | 0.00 | 0.30 |
April | 0.00 | 0.115144E+09 | 0.00 | 0.143400E+09 | 0.00 | 0.00 | 0.184934E+10 | 0.00 | 0.29 |
May | 0.00 | 0.638548E+09 | 0.00 | 13195374.69 | 0.00 | 0.00 | 0.595816E+09 | 0.00 | 0.29 |
June | 0.00 | 0.277562E+10 | 0.00 | 12911288.66 | 0.00 | 0.00 | 0.269349E+09 | 0.00 | 0.30 |
July | 0.00 | 0.392078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.477562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.151964E+10 | 0.00 | 11253419.47 | 0.00 | 0.00 | 0.344048E+09 | 0.00 | 0.29 |
October | 0.00 | 0.499050E+09 | 0.00 | 55552702.39 | 0.00 | 0.00 | 0.240804E+10 | 0.00 | 0.28 |
November | 0.00 | 35818545.67 | 0.00 | 0.103279E+09 | 0.00 | 0.00 | 0.355325E+10 | 0.00 | 0.28 |
December | 0.00 | 4587611.80 | 0.00 | 0.147244E+09 | 0.00 | 0.00 | 0.450131E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.169603E+10 | 0.143281E+11 | 0.00 | 0.669742E+09 | 0.00 | 0.00 | 0.256549E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.169603E+10 | 0.477562E+10 | 0.00 | 0.147244E+09 | 0.00 | 0.00 | 0.450131E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384707E+09 | 0.00 | 0.00 | 466083.96 | 0.00 | 0.00 | 0.198159E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4867434.60 | 0.00 | 0.00 | 0.447815E+09 | 0.00 | 0.28 |
March | 0.00 | 4313273.52 | 0.00 | 11030564.50 | 0.00 | 0.00 | 0.340644E+09 | 0.00 | 0.30 |
April | 0.00 | 11452870.40 | 0.00 | 14052302.25 | 0.00 | 0.00 | 0.185459E+09 | 0.00 | 0.29 |
May | 0.00 | 64192044.71 | 0.00 | 1245783.34 | 0.00 | 0.00 | 59938844.88 | 0.00 | 0.29 |
June | 0.00 | 0.277762E+09 | 0.00 | 1275825.86 | 0.00 | 0.00 | 27003985.43 | 0.00 | 0.30 |
July | 0.00 | 0.391929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.480029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.152105E+09 | 0.00 | 1044033.19 | 0.00 | 0.00 | 35280934.00 | 0.00 | 0.29 |
October | 0.00 | 49720125.84 | 0.00 | 5008270.60 | 0.00 | 0.00 | 0.242225E+09 | 0.00 | 0.28 |
November | 0.00 | 3499943.13 | 0.00 | 9452251.65 | 0.00 | 0.00 | 0.356562E+09 | 0.00 | 0.28 |
December | 0.00 | 443961.94 | 0.00 | 13635073.51 | 0.00 | 0.00 | 0.451477E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.384707E+09 | 0.143545E+10 | 0.00 | 62077623.46 | 0.00 | 0.00 | 0.234457E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.384707E+09 | 0.480029E+09 | 0.00 | 14052302.25 | 0.00 | 0.00 | 0.451477E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.602402E+09 | 0.00 | 0.00 | 0.447946E+12 | 0.00 | 9.71 |
February | 0.00 | 0.00 | 0.00 | 0.106438E+10 | 0.00 | 0.00 | 0.666196E+12 | 0.00 | 21.60 |
March | 0.00 | 52568445.82 | 0.00 | 0.154387E+10 | 0.00 | 0.00 | 0.823364E+12 | 0.00 | 34.31 |
April | 0.00 | 0.225569E+09 | 0.00 | 0.195322E+10 | 0.00 | 0.00 | 0.578862E+12 | 0.00 | 35.85 |
May | 0.00 | 0.111069E+10 | 0.00 | 0.319811E+09 | 0.00 | 0.00 | 0.200649E+12 | 0.00 | 17.50 |
June | 0.00 | 0.627371E+10 | 0.00 | 0.229121E+09 | 0.00 | 0.00 | 0.931499E+11 | 0.00 | 8.32 |
July | 0.00 | 0.865883E+10 | 0.00 | 10160640.40 | 0.00 | 0.00 | 0.137920E+10 | 0.00 | 0.49 |
August | 0.00 | 0.876581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.369637E+10 | 0.00 | 0.159662E+09 | 0.00 | 0.00 | 0.960560E+11 | 0.00 | 9.51 |
October | 0.00 | 0.108136E+10 | 0.00 | 0.847485E+09 | 0.00 | 0.00 | 0.474646E+12 | 0.00 | 23.90 |
November | 0.00 | 0.00 | 0.00 | 0.153315E+10 | 0.00 | 0.00 | 0.838771E+12 | 0.00 | 32.44 |
December | 0.00 | 7680092.71 | 0.00 | 0.219897E+10 | 0.00 | 0.00 | 0.117796E+13 | 0.00 | 33.60 |
Annual Sum or Average | 0.00 | 0.298726E+11 | 0.00 | 0.104622E+11 | 0.00 | 0.00 | 0.539898E+13 | 0.00 | 18.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.00 | 0.876581E+10 | 0.00 | 0.219897E+10 | 0.00 | 0.00 | 0.117796E+13 | 0.00 | 35.85 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.322762E+12 | 0.294510E+11 | 0.00 | 0.187725E+13 | 0.804266E+11 |
February | 0.327086E+12 | 0.259512E+11 | 0.00 | 0.207112E+13 | 0.255270E+12 |
March | 0.486332E+12 | 0.168342E+11 | 0.00 | 0.240863E+13 | 0.753101E+12 |
April | 0.552088E+12 | 0.937870E+10 | 0.00 | 0.191216E+13 | 0.165345E+13 |
May | 0.612115E+12 | 0.459242E+10 | 0.00 | 0.102861E+13 | 0.149341E+13 |
June | 0.596868E+12 | -0.373010E+10 | 0.00 | 0.931764E+11 | 0.262039E+13 |
July | 0.576179E+12 | -0.808255E+10 | 0.00 | -0.394725E+12 | 0.342212E+13 |
August | 0.534023E+12 | -0.109330E+11 | 0.00 | -0.549366E+12 | 0.403829E+13 |
September | 0.408565E+12 | -145511418.2 | 0.00 | 0.411923E+12 | 0.179044E+13 |
October | 0.383840E+12 | 0.940377E+10 | 0.00 | 0.176758E+13 | 0.969371E+12 |
November | 0.277130E+12 | 0.155673E+11 | 0.00 | 0.239501E+13 | 0.585700E+12 |
December | 0.260952E+12 | 0.272007E+11 | 0.00 | 0.273553E+13 | 0.472630E+12 |
Annual Sum or Average | 0.533794E+13 | 0.115488E+12 | 0.00 | 0.157569E+14 | 0.181346E+14 |
Minimum of Months | 0.260952E+12 | -0.109330E+11 | 0.00 | -0.549366E+12 | 0.804266E+11 |
Maximum of Months | 0.612115E+12 | 0.294510E+11 | 0.00 | 0.273553E+13 | 0.403829E+13 |