Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:56:55
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27473.70 | 593.12 | 593.12 |
Net Site Energy | 26931.00 | 581.41 | 581.41 |
Total Source Energy | 85526.36 | 1846.41 | 1846.41 |
Net Source Energy | 83807.63 | 1809.30 | 1809.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 67.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4290.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1712.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 264.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2028.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 645.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1551.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11173.78 |
Humidification | 338.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.96 |
Heat Recovery | 50.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 644.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26761.82 | 711.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13579.90 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 67.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 4290.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1712.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 264.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2028.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 645.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1551.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11173.78 |
Humidification | General | 338.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.96 |
Heat Recovery | General | 50.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 644.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 67.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4290.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1712.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 264.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2028.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 645.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1551.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11173.78 |
Humidification | Unassigned | 338.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.96 |
Heat Recovery | Unassigned | 50.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 644.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 191.16 | 15.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Other | 343.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 577.75 | 15.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 191.16 | 15.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Other | 343.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 577.75 | 15.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 566.520 | 2.12 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -23.82 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 542.701 | 2.03 |
Electricity Coming From Utility | 26219.119 | 97.97 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26219.119 | 97.97 |
Total On-Site and Utility Electric Sources | 26761.820 | 100.00 |
Total Electricity End Uses | 26761.820 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 2689.18 | 99.32 |
Air to Air Heat Recovery for Heating | 18.50 | 0.68 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2707.67 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 13579.90 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 13579.90 | 100.00 |
Total Water End Uses | 13579.90 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.83 |
Time Setpoint Not Met During Occupied Cooling | 800.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:30 | 06-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 30-AUG-15:00 |
Heating | 0.00 | 459264.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 386512.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 131212.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 81663.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28158.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1628470.72 | 487423.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 459264.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 386512.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 131212.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 47613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 81663.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 28158.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 72.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13587.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5422.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 837.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6422.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2045.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4914.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1072.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 160.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 699.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84754.68 | 771.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 106.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 23.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1829.75 | 16.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 106.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 23.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1829.75 | 16.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.01 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.461005 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.40 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.448267 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.26 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.25 | 0.362370 | 0.308000 | 1.62 | 0.966319 | 0.500000 | 0.001051 | 0.000356 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 48.98 | 0.388321 | 0.330000 | 16.16 | 1.00 | 0.500000 | 0.000981 | 0.007470 | 16.16 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.85 | 0.392283 | 0.333000 | 1.61 | 1.00 | 0.500000 | 0.000971 | 0.001299 | 1.76 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.893749 | 0.267212 | 0.227000 | 0.202881 | 0.712566 | 0.500000 | 0.001426 | 0.000109 | 0.202881 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.01 | 0.151940 | 0.129000 | 0.130669 | 0.405172 | 0.500000 | 0.002508 | 0.000077 | 0.130669 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.12 | 0.212603 | 0.181000 | 0.203325 | 0.566940 | 0.500000 | 0.001792 | 0.000145 | 0.203325 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.29 | 0.119591 | 0.102000 | 0.131267 | 0.318910 | 0.500000 | 0.003186 | 0.000047 | 0.131267 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.40 | 0.284273 | 0.242000 | 2.03 | 0.758061 | 0.500000 | 0.001340 | 0.003189 | 4.35 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.56 | 0.388467 | 0.500000 | 0.002615 | 0.002128 | 2.90 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 10.79 | 0.221316 | 0.188000 | 2.03 | 0.590175 | 0.500000 | 0.001722 | 0.003168 | 4.32 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.21 | 0.137258 | 0.117000 | 1.31 | 0.366021 | 0.500000 | 0.002776 | 0.001884 | 2.57 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.962940 | 0.248012 | 0.211000 | 0.203180 | 0.661365 | 0.500000 | 0.001536 | 0.000421 | 0.573847 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.07 | 0.143393 | 0.122000 | 0.130944 | 0.382381 | 0.500000 | 0.002657 | 0.000278 | 0.378953 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.19 | 0.199985 | 0.170000 | 0.203017 | 0.533294 | 0.500000 | 0.001905 | 0.000419 | 0.571197 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.20 | 0.127907 | 0.109000 | 0.131155 | 0.341085 | 0.500000 | 0.002979 | 0.000259 | 0.353943 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16264.35 | 0.000356 | 453.94 |
CORE_MID VAV BOX REHEAT COIL | 341488.44 | 0.007470 | 10952.26 |
CORE_TOP VAV BOX REHEAT COIL | 59375.28 | 0.001299 | 2314.26 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4993.32 | 0.000109 | 167.70 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3507.79 | 0.000077 | 121.70 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6612.92 | 0.000145 | 252.30 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2142.61 | 0.000047 | 65.06 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 145764.75 | 0.003189 | 5668.51 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 97272.91 | 0.002128 | 3782.56 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 144832.07 | 0.003168 | 5632.29 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 86146.19 | 0.001884 | 3350.47 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19231.19 | 0.000421 | 747.54 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12699.03 | 0.000278 | 493.61 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19142.58 | 0.000419 | 744.10 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11862.62 | 0.000259 | 461.14 |
VAV_BOT WITH REHEAT HEATING COIL | 23877.66 | 0.000522 | 545.16 |
VAV_MID WITH REHEAT HEATING COIL | 170146.35 | 0.003722 | 3929.58 |
VAV_TOP WITH REHEAT HEATING COIL | 14410.06 | 0.000315 | 336.08 |
CAV_BAS HEATING COIL | 235688.33 | 0.005156 | 7677.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.78 | 2.28 | 9.57 | 2.28 | 8.46 | 8.46 | 0.300000 | 0.270092 | 8.46 |
VAV_MID WITH REHEAT | 44.98 | 22.85 | 89.95 | 24.91 | 78.17 | 78.17 | 0.300000 | 0.318719 | 78.17 |
VAV_TOP WITH REHEAT | 4.64 | 2.28 | 9.28 | 3.64 | 8.69 | 8.69 | 0.300000 | 0.419054 | 8.69 |
CAV_BAS | 5.01 | 5.01 | 5.01 | 5.01 | 5.01 | 5.01 | 1.00 | 1.00 | 5.01 |
AIRLOOP DATACENTER BASEMENT | 21.26 | 21.26 | 21.26 | 21.26 | 21.26 | 21.26 | 1.00 | 0.999991 | 21.26 |
AIRLOOP DATACENTER BOT | 0.461005 | 0.461005 | 0.461005 | 0.461005 | 0.461005 | 0.461005 | 1.00 | 1.00 | 0.461005 |
AIRLOOP DATACENTER MID | 4.40 | 4.40 | 4.40 | 4.40 | 4.40 | 4.40 | 1.00 | 1.00 | 4.40 |
AIRLOOP DATACENTER TOP | 0.448267 | 0.448267 | 0.448267 | 0.448267 | 0.448267 | 0.448267 | 1.00 | 1.00 | 0.448267 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.46 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 78.17 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.69 | |
CAV_BAS_OA_CONTROLLER | 5.01 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.26 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.461005 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.40 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.448267 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.44 | 6.67 | 11.05 | 0.010806 | 0.008500 | 219741.72 | 0.006285 | 8.46 |
VAV_MID WITH REHEAT COOLING COIL | 26.72 | 6.67 | 11.05 | 0.011115 | 0.008500 | 2131844.07 | 0.060970 | 78.17 |
VAV_TOP WITH REHEAT COOLING COIL | 26.30 | 6.67 | 11.05 | 0.010769 | 0.008500 | 223281.80 | 0.006386 | 8.69 |
CAV_BAS COOLING COIL | 25.09 | 6.67 | 11.42 | 0.010810 | 0.008500 | 119601.09 | 0.003421 | 5.01 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.46 |
VAV_MID WITH REHEAT FAN | 78.17 |
VAV_TOP WITH REHEAT FAN | 8.69 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006285 | 0.000076 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000522 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.060970 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003722 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006386 | 0.000075 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000315 | |
CAV_BAS_COOLC_CONTROLLER | 0.003421 | 0.000139 |
CAV_BAS_HEATC_CONTROLLER | 0.005156 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.01 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.26 | 432910.51 | 311283.87 | 0.010602 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.461005 | 9410.66 | 6753.82 | 0.000230 |
AIRLOOP DATACENTER MID COOLING COIL | 4.40 | 89955.59 | 64470.36 | 0.002203 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.448267 | 9167.81 | 6573.01 | 0.000225 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.26 | 21.26 | 21.26 | 21.26 | 432910.51 | 432910.51 | 14482.89 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.461005 | 0.461005 | 0.461005 | 0.461005 | 9410.66 | 9410.66 | 669.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.40 | 4.40 | 4.40 | 4.40 | 89955.59 | 89955.59 | 6690.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.448267 | 0.448267 | 0.448267 | 0.448267 | 9167.81 | 9167.81 | 669.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.26 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.461005 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.40 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.448267 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.26 | 432910.51 | 0.010602 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.461005 | 9410.66 | 0.000230 |
AIRLOOP DATACENTER MID HEATING COIL | 4.40 | 89955.59 | 0.002203 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.448267 | 9167.81 | 0.000225 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14482.89 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 669.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6690.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 669.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000080 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.077061 | 12457.21 | |
HEATSYS1 PUMP | 0.030963 | 9232.43 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.077061 | 9.25 |
HEATSYS1 | 0.030963 | 3.72 |
COOLSYS1_SUPPLY | 0.077061 | 9.25 |
SINGLE WATER PLANT LOOP | 0.013260 | 1.59 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.077061 | 0.077061 | 323465.63 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1415458.45 | 1415458.45 | 0.030963 |
CENTRAL BOILER | 546195.96 | 535638.85 | 0.013260 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.038531 | 4312.27 |
COOLSYS1 CHILLER2 PUMP | 0.038531 | 4312.27 |
PLANT CIRC PUMP | 0.013260 | 3348.46 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.077061 | 0.038863 | 1362188.39 | 1368648.74 | 0.067286 |
COOLSYS1 CHILLER2 | 0.077061 | 0.038863 | 1362188.39 | 1368648.74 | 0.067286 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013260 | 139666.47 | 59408.87 | 69833.23 | 7004.20 | 21428.40 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.134573 | 16.15 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.134573 | 32987.34 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 49.90 | 1623881.23 | 9.98 | 202985.15 |
TOWERWATERSYS COOLTOWER 2 | 49.90 | 1623881.23 | 9.98 | 202985.15 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.070350 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.452 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.400 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.662 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5215 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5467 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4343 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.81534556E-15 | 0.47534309E-16 | -0.12491808E-09 | -0.15651055E-17 |
51 | 8 | 0.18376575E-07 | 0.18892299E-12 | 0.33997552E-03 | -0.20894799E-09 |
52 | 7 | -0.11109444E-01 | 0.10222184E-07 | -0.21454547E-01 | 0.12631841E-03 |
53 | 6 | 0.37458360 | 0.36213810E-05 | 0.44579641 | -0.43850983E-02 |
54 | 5 | -4.8902522 | 0.13734403E-03 | -4.2389002 | 0.59460182E-01 |
55 | 4 | 31.674104 | 0.11393769E-02 | 20.648451 | -0.40448134 |
56 | 3 | -108.39803 | 0.25142476E-02 | -54.058051 | 1.4743366 |
57 | 2 | 194.32686 | 0.14299560E-02 | 76.440274 | -2.8561868 |
58 | 1 | -170.12819 | 0.15421596E-03 | -54.840647 | 2.7274244 |
59 | 0 | 57.057407 | 0.88766417E-06 | 15.629571 | |
60 | 9 | 0.15527634E-14 | 0.48972640E-16 | -0.12737755E-09 | -0.48559044E-17 |
61 | 8 | 0.18724477E-07 | 0.18300980E-12 | 0.34384059E-03 | -0.21290374E-09 |
62 | 7 | -0.11225506E-01 | 0.98577958E-08 | -0.21621905E-01 | 0.12763808E-03 |
63 | 6 | 0.37773826 | 0.34860306E-05 | 0.44850155 | -0.44222837E-02 |
64 | 5 | -4.9210508 | 0.13200769E-03 | -4.2597582 | 0.59842059E-01 |
65 | 4 | 31.810414 | 0.10936068E-02 | 20.730162 | -0.40629104 |
66 | 3 | -108.68827 | 0.24103335E-02 | -54.219675 | 1.4785295 |
67 | 2 | 194.61479 | 0.13693941E-02 | 76.588171 | -2.8607587 |
68 | 1 | -170.23464 | 0.14753937E-03 | -54.883028 | 2.7292902 |
69 | 0 | 57.057407 | 0.84836289E-06 | 15.622061 | |
70 | 9 | 0.10580992E-14 | 0.52916478E-16 | -0.11479962E-09 | -0.26242945E-17 |
71 | 8 | 0.16943687E-07 | 0.21219816E-12 | 0.32378363E-03 | -0.19265555E-09 |
72 | 7 | -0.10622292E-01 | 0.11706466E-07 | -0.20751735E-01 | 0.12077931E-03 |
73 | 6 | 0.36134106 | 0.41796623E-05 | 0.43441658 | -0.42290030E-02 |
74 | 5 | -4.7609497 | 0.15957712E-03 | -4.1510514 | 0.57856955E-01 |
75 | 4 | 31.101728 | 0.13316855E-02 | 20.304070 | -0.39688243 |
76 | 3 | -107.17897 | 0.29539374E-02 | -53.376774 | 1.4567269 |
77 | 2 | 193.11717 | 0.16877407E-02 | 75.817308 | -2.8369794 |
78 | 1 | -169.68078 | 0.18278585E-03 | -54.662957 | 2.7195831 |
79 | 0 | 57.057407 | 0.10570564E-05 | 15.661738 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6847E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6860E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8818E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8829E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9924E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9931E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7516E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7154E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8001E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9067E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9772E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0116E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0681E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7664E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.1920E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6854E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1006 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8760E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2933E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6417E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1496E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0924E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7233E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8383E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9152E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0185E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0194E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0976E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7668E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8046E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6846E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6862E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8817E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8831E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9923E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9934E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7515E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9759E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1286E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8196E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9773E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5901E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6698E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9952E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0209E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5185E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1055E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2851E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9265E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3008E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7275E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2799E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2243E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9415E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0029E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7769E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8221E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5667E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5861E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9953E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0213E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7132E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7146E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4753E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4765E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3125E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3134E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7516E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7522E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7456E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8245E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5020E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5652E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3339E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3802E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7668E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8046E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6290E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3597E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0389E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0404E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8205E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.0923E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1496E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0921E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7429E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8213E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4984E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5582E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3278E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3618E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7664E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7131E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7144E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4752E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4762E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3124E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3130E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7515E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7521E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2773E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3420E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9736E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0203E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9448E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9618E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9954E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0213E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3704E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6802E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9096E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4183E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1697E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3027E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2799E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2243E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3031E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4167E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0063E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1165E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9664E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0342E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9952E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0208E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.8268E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4412E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1055 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7165E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.1592E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0480E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8633E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9092E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.3778E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0518E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1188E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8366E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1059E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5769E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9603E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9312E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3109E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1835E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.6391E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7446E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3925E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3248E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8633E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9088E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0772E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4619E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5589E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1293E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8349E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0028E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9603E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9312E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.8394E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4529E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1057 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7296E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.1744E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0581E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8716E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9134E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.3832E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0568E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1250E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8414E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1147E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5824E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9686E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9354E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3115E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1860E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.6399E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7466E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3963E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3272E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8716E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9131E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0799E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4654E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5618E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1323E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8411E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0068E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9686E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9354E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69579.95808 | 69579.95808 | 5.01159 | 5.01159 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 4.60000 | 5.25715E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 72878.93664 | 72878.93664 | 5.24891 | 5.24891 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 680307.28509 | 680307.28509 | 48.98126 | 48.98126 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 178873.28890 | 178873.28890 | 7.48994 | 10.77825 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67345.89878 | 67345.89878 | 4.84865 | 4.84865 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 41625.15625 | 41625.15625 | 1.76435 | 1.76435 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12290.45537 | 12290.45537 | 0.89375 | 0.89375 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 2956.16406 | 2956.16406 | 0.12440 | 0.13533 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13929.54397 | 13929.54397 | 1.01294 | 1.01294 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 30.22650 | 1.65295E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2195.48401 | 2195.48401 | 9.25703E-002 | 9.25703E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15447.79565 | 15447.79565 | 1.12334 | 1.12334 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4570.13840 | 4570.13840 | 0.19350 | 0.19350 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17697.50656 | 17697.50656 | 1.28693 | 1.28693 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 825.57409 | 825.57409 | 3.50739E-002 | 8.72129E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 115521.18973 | 115521.18973 | 8.40110 | 8.40110 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 102071.53484 | 102071.53484 | 4.34665 | 4.34665 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 145277.19753 | 145277.19753 | 10.56496 | 10.56496 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65303E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 68112.18998 | 68112.18998 | 2.90087 | 2.90087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 148387.26493 | 148387.26493 | 10.79119 | 10.79119 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 101419.45529 | 101419.45529 | 4.31877 | 4.31877 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 154186.37661 | 154186.37661 | 11.21284 | 11.21284 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65340E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 60332.62421 | 60332.62421 | 2.56836 | 2.56836 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13240.83711 | 13240.83711 | 0.96294 | 0.96294 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13461.41067 | 13461.41067 | 0.57385 | 0.57385 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14758.57010 | 14758.57010 | 1.07331 | 1.07331 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 30.89800 | 1.65307E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8888.80223 | 8888.80223 | 0.37895 | 0.37895 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 16421.04825 | 16421.04825 | 1.19422 | 1.19422 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13399.47505 | 13399.47505 | 0.57120 | 0.57120 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16545.49841 | 16545.49841 | 1.20326 | 1.20326 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8304.14824 | 8304.14824 | 0.35394 | 0.35394 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8037.91551 | 8037.91551 | 0.46101 | 0.46101 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76632.48465 | 76632.48465 | 4.39521 | 4.39521 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7815.78906 | 7815.78906 | 0.44827 | 0.44827 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370704.02631 | 370704.02631 | 21.26087 | 21.26087 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 26.71100 | 1.65229E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 4.60000 | 5.25715E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 135848.58 | 8.45934 | 8.45934 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 15727.81 | 1.58644 | 1.58644 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1242389.73 | 78.16574 | 78.16574 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 201288.10 | 24.91290 | 24.91290 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 141445.17 | 8.69169 | 8.69169 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 19839.11 | 3.64229 | 3.64229 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
7 | CAV_BAS | Cooling | Sensible | 74266.08 | 5.01159 | 5.01159 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51365.55 | 1.20016 | 1.20016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367336.59 | 21.26107 | 21.26107 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14482.89 | 0.33839 | 0.33839 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7993.30 | 0.46101 | 0.46101 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 669.05 | 1.56323E-002 | 1.56323E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76244.26 | 4.39521 | 4.39521 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6690.49 | 0.15632 | 0.15632 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7775.52 | 0.44827 | 0.44827 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 669.05 | 1.56323E-002 | 1.56323E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.01159 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.24891 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36237 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61666 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96632 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05141E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55783E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61666 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16264.34832 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55783E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.93959 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 48.98126 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38832 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.16382 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.81148E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.47007E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.16382 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 341488.44435 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.47007E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10952.25502 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.84865 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39228 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33300 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61460 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.71237E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29884E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.76435 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 59375.27514 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29884E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2314.26439 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89375 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26721 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20288 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71257 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42583E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09229E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20288 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4993.32313 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09229E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 167.69943 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01294 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15194 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12900 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13067 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40517 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50757E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.67330E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13067 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3507.78936 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.67330E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 121.69949 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12334 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21260 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18100 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20333 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56694 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79208E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.44658E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20333 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6612.92475 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44658E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.30492 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28693 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11959 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13127 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31891 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18586E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.68696E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13127 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2142.60933 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.68696E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 65.05808 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.40110 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28427 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03307 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75806 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34026E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.18861E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.34665 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 145764.74658 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18861E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5668.50787 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.56496 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38847 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61541E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.12785E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.90087 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 97272.91006 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.12785E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3782.56465 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.79119 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22132 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18800 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02874 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59017 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72152E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16821E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.31877 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 144832.07362 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16821E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5632.29418 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.21284 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13726 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11700 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31190 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36602 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77580E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.88445E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.56836 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 86146.19400 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88445E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3350.47037 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96294 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24801 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20318 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66137 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53622E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.20683E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57385 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19231.18650 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.20683E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 747.54290 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07331 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14339 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12200 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13094 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38238 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65704E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.77792E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37895 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12699.03161 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.77792E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 493.61041 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19422 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19999 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17000 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20302 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53329 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90514E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.18744E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57120 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19142.57844 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.18744E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 744.10398 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20326 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12791 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10900 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13116 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34108 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.97873E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.59495E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35394 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11862.61716 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.59495E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 461.14155 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46101 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.39521 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44827 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.26087 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.78293 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28480 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.56586 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28480 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.45934 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.45934 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27009 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 44.97568 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.84758 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 89.95135 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.91290 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 78.16574 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 78.16574 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31872 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.64119 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28290 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.28237 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.64229 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.69169 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.69169 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.41905 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.01159 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.01159 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.01159 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.01159 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.01159 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.01159 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.26087 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.26087 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.26087 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.26087 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.26107 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.26107 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46101 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46101 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46101 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46101 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46101 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46101 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.39521 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.39521 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.39521 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.39521 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.39521 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.39521 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44827 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44827 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44827 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44827 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44827 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44827 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.45934 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 78.16574 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.69169 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.01159 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.26107 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46101 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.39521 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44827 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.45934 |
286 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.43894 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04763 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08061E-002 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 219741.71708 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.28459E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.45934 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 23877.65950 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22324E-004 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 545.15698 |
298 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.45934 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.28459E-003 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.57712E-005 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.22324E-004 |
302 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 78.16574 |
303 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.72230 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04862 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11154E-002 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2131844.06773 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.09705E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 78.16574 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 170146.34531 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.72196E-003 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3929.58049 |
315 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 78.16574 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.09705E-002 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.81018E-006 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.72196E-003 |
319 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.69169 |
320 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.29960 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04751 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.07685E-002 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 223281.79897 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.38583E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.69169 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 14410.05568 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.15220E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 336.08450 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.69169 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.38583E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.45699E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.15220E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.01159 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.09278 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42496 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08101E-002 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 119601.09011 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.42058E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.01159 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 235688.33338 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.15569E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7677.65215 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.01159 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.42058E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.39214E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.15569E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.26107 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.26107 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 432910.50933 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 311283.87307 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06020E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.26107 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.26107 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.26107 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.26107 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 432910.50933 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 432910.50933 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14482.88751 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.26107 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.26107 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 432910.50933 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06020E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14482.88751 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 7.98784E-005 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46101 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46101 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9410.65657 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6753.81825 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30466E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46101 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46101 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46101 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46101 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9410.65657 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9410.65657 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.04940 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46101 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46101 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9410.65657 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30466E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.04940 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.39521 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.39521 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 89955.58797 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64470.35503 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.20301E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.39521 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.39521 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.39521 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.39521 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89955.58797 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89955.58797 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6690.49404 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.39521 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.39521 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 89955.58797 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.20301E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6690.49404 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44827 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44827 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9167.81324 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6573.00875 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24519E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44827 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44827 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44827 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44827 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9167.81324 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9167.81324 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.04940 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44827 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44827 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9167.81324 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24519E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.04940 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.70615E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 12457.21006 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.70615E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.24738 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.70615E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.70615E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 323465.62712 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.09632E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.71558 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.09632E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 9232.42964 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1415458.44624 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1415458.45000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.09632E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.70615E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.24738 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.85307E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4312.27332 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.85307E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4312.27332 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.70615E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.88630E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1362188.39373 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1368648.73500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.72863E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.70615E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.88630E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1362188.39373 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1368648.73500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.72863E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.32599E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.59119 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.32599E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3348.46382 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.32599E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59408.86576 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21428.39722 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 546195.95699 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 535638.85000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.32599E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13457 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.14872 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13457 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 32987.33999 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 49.89902 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1623881.23333 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.97980 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 202985.15417 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 49.89902 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1623881.23333 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.97980 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 202985.15417 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.03500E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.03500E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22641.21 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 475777.46 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 82623.97 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6954.76 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4884.61 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9203.41 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2986.51 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 202841.48 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 135361.84 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 201543.59 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 119878.18 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26761.54 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17671.59 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 26638.23 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16507.66 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 28542.78 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 210220.62 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 18297.99 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 263141.24 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 227181.20 | 156643.00 | 70538.20 | 0.69 | 33863.39 | 343.46 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2140936.27 | 1465293.11 | 675643.15 | 0.68 | 315642.63 | 3201.42 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 232447.38 | 160535.62 | 71911.76 | 0.69 | 34782.14 | 352.78 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 129160.56 | 90444.41 | 38716.15 | 0.70 | 19326.46 | 196.02 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.80 | 23.21 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.80 | 23.21 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2062150862 | 0.2045242813 | Pass | Pass | 0.6903209525 | 0.6698616097 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2268131950 | 0.2454809854 | Pass | Pass | 0.2456524943 | 0.4298035093 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1489488211 | 0.1979885214 | Pass | Pass | 0.2101226406 | 0.4059826448 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1294061398 | 0.1915938219 | Pass | Pass | 0.2021045376 | 0.4001507662 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1916320922 | 0.2088710204 | Pass | Pass | 0.2448478581 | 0.4288006160 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2650807081 | 0.3243621900 | Pass | Pass | 0.2584364502 | 0.4422923565 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4214655507 | 0.5916622276 | Pass | Pass | 0.2716686247 | 0.4604852213 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2772749753 | 0.3871329540 | Pass | Pass | 0.2635250320 | 0.4618078656 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1354837136 | 0.1825093347 | Pass | Pass | 0.2097839782 | 0.4048457179 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1863863296 | 0.2143306997 | Pass | Pass | 0.2099018211 | 0.4064953317 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3862944234 | 0.6388230730 | Pass | Pass | 0.2244814218 | 0.4164633016 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1946849405 | 0.3001732031 | Pass | Pass | 0.2139155751 | 0.4092015438 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1269756527 | 0.1685991667 | Pass | Pass | 0.2015841346 | 0.3994391884 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1726423570 | 0.1945740047 | Pass | Pass | 0.2206734701 | 0.4421786278 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3705802531 | 0.6213418348 | Pass | Pass | 0.2485149218 | 0.4800692624 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1837957131 | 0.3065478421 | Pass | Pass | 0.2115919599 | 0.4139387188 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.5793523121E-002 | 4.4113560054E-002 | Pass | Pass | 0.2572071566 | 0.4141134757 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.4663841509E-002 | 3.9370865316E-002 | Pass | Pass | 0.2292753661 | 0.4127331609 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6745987978E-002 | 7.0154025508E-002 | Pass | Pass | 0.3180098741 | 1.0161074396 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0821657501E-005 | 1.8405177376E-005 | Pass | Pass | 3.3431930516E-003 | 4.5451741177E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0183300872E-005 | 1.7681559951E-005 | Pass | Pass | 4.9298052253E-003 | 5.5109787832E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0076726795E-005 | 1.8080486856E-005 | Pass | Pass | 7.5672828905E-003 | 5.3524390241E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4742683405E-004 | 2.4379604983E-004 | Pass | Pass | 6.3129202607E-005 | 1.1179500889E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5694.90 | -54.0 | 0.00 | 4642.90 | 29380.26 | 39664.12 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 1390.74 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.586 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.95 | 0.0000 | Y | 7.46 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.85 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.71 | 0.0000 | Y | 7.38 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.83 | 0.0000 | Y | 4.78 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.91 | 0.0000 | Y | 74.48 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.82 | 0.0000 | Y | 47.80 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.69 | 0.0000 | Y | 73.74 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.80 | 0.0000 | Y | 47.76 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.91 | 0.0000 | Y | 7.45 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.82 | 0.0000 | Y | 4.78 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.69 | 0.0000 | Y | 7.37 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.80 | 0.0000 | Y | 4.78 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 539.72 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.73 | 41.73 | 101.45 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.73 | 62.73 | 10.83 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.73 | 47.05 | 152.06 | |
Exterior Lighting Total | 31088.59 | 264.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2686169.47 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1415458.45 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1368648.74 | 6.59 | 1200617.12 | 5.87 | 6.80 | 23.21 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1368648.74 | 6.59 | 1200617.12 | 5.87 | 6.80 | 23.21 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 535638.85 | 0.90 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1623881.23 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1623881.23 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 219741.72 | 227181.20 | 156643.00 | 70538.20 | 0.69 | - | 33863.39 | 343.46 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2131844.07 | 2140936.27 | 1465293.11 | 675643.15 | 0.68 | - | 315642.63 | 3201.42 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 223281.80 | 232447.38 | 160535.62 | 71911.76 | 0.69 | - | 34782.14 | 352.78 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 119601.09 | 129160.56 | 90444.41 | 38716.15 | 0.70 | - | 19326.46 | 196.02 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 432910.51 | 311283.87 | 121626.64 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9410.66 | 6753.82 | 2656.84 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89955.59 | 64470.36 | 25485.23 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9167.81 | 6573.01 | 2594.80 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16264.35 | 22641.21 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 341488.44 | 475777.46 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 59375.28 | 82623.97 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 4993.32 | 6954.76 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3507.79 | 4884.61 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6612.92 | 9203.41 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2142.61 | 2986.51 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 145764.75 | 202841.48 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 97272.91 | 135361.84 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 144832.07 | 201543.59 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 86146.19 | 119878.18 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19231.19 | 26761.54 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12699.03 | 17671.59 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19142.58 | 26638.23 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11862.62 | 16507.66 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 23877.66 | 28542.78 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 170146.35 | 210220.62 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 14410.06 | 18297.99 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 235688.33 | 263141.24 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 432910.51 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9410.66 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 89955.59 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9167.81 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14482.89 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 669.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6690.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 669.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.46 | 18280.19 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 78.17 | 168911.99 | 2160.95 | 1.00 | 1.08 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.69 | 18782.28 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.01 | 8497.92 | 1695.65 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.26 | 35250.28 | 1657.97 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 516.38 | 1120.11 | 1.00 | 1.64 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.40 | 4923.11 | 1120.11 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 502.11 | 1120.11 | 1.00 | 1.66 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.077061 | 12457.21 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.030963 | 9232.43 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.038531 | 4312.27 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.038531 | 4312.27 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013260 | 3348.46 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.134573 | 32987.34 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69579.96 | 69579.96 | 25.03 | 5.012 | 5.012 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00901 | 28.05 | 0.01653 | 1.200 | 0.00 |
CORE_BOTTOM | 72878.94 | 72878.94 | 29.20 | 5.249 | 5.249 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.05 | 0.01653 | 1.078 | 0.00 |
CORE_MID | 680307.29 | 680307.29 | 272.55 | 48.981 | 48.981 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.05 | 0.01653 | 10.778 | 0.00 |
CORE_TOP | 67345.90 | 67345.90 | 26.98 | 4.849 | 4.849 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.05 | 0.01653 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12290.46 | 12290.46 | 39.21 | 0.894 | 0.894 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00896 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13929.54 | 13929.54 | 68.97 | 1.013 | 1.013 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 24.00 | 24.00 | 0.00877 | 30.23 | 0.01653 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15447.80 | 15447.80 | 49.29 | 1.123 | 1.123 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00886 | 33.77 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17697.51 | 17697.51 | 87.62 | 1.287 | 1.287 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00871 | 32.79 | 0.01653 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 115521.19 | 115521.19 | 368.59 | 8.401 | 8.401 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00918 | 33.90 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 145277.20 | 145277.20 | 719.28 | 10.565 | 10.565 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00887 | 30.67 | 0.01653 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 148387.26 | 148387.26 | 473.45 | 10.791 | 10.791 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00904 | 33.83 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 154186.38 | 154186.38 | 763.39 | 11.213 | 11.213 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00884 | 32.66 | 0.01653 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13240.84 | 13240.84 | 42.25 | 0.963 | 0.963 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00917 | 33.82 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14758.57 | 14758.57 | 73.07 | 1.073 | 1.073 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 24.00 | 24.00 | 0.00891 | 30.90 | 0.01653 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16421.05 | 16421.05 | 52.39 | 1.194 | 1.194 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00905 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16545.50 | 16545.50 | 81.92 | 1.203 | 1.203 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00886 | 32.79 | 0.01653 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8037.92 | 8037.92 | 222.03 | 0.461 | 0.461 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76632.48 | 76632.48 | 2116.76 | 4.395 | 4.395 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7815.79 | 7815.79 | 215.89 | 0.448 | 0.448 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370704.03 | 370704.03 | 473.03 | 21.261 | 21.261 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 26.71 | 0.01652 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.44 | 0.00526 | 4.60 | 0.00526 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.06 | 0.00526 | 4.60 | 0.00526 | 1.078 | 0.00 | |
CORE_MID | 178873.29 | 178873.29 | 71.66 | 7.490 | 10.778 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 10.778 | 0.00 |
CORE_TOP | 41625.16 | 41625.16 | 16.68 | 1.764 | 1.764 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 2956.16 | 2956.16 | 9.43 | 0.124 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00701 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2195.48 | 2195.48 | 10.87 | 0.093 | 0.093 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00712 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4570.14 | 4570.14 | 14.58 | 0.193 | 0.193 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00733 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 825.57 | 825.57 | 4.09 | 0.035 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00656 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 102071.53 | 102071.53 | 325.68 | 4.347 | 4.347 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 68112.19 | 68112.19 | 337.23 | 2.901 | 2.901 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 101419.46 | 101419.46 | 323.59 | 4.319 | 4.319 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 60332.62 | 60332.62 | 298.71 | 2.568 | 2.568 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13461.41 | 13461.41 | 42.95 | 0.574 | 0.574 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8888.80 | 8888.80 | 44.01 | 0.379 | 0.379 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13399.48 | 13399.48 | 42.75 | 0.571 | 0.571 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8304.15 | 8304.15 | 41.11 | 0.354 | 0.354 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | 4.60 | 0.00526 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.97 | 0.00801 | 4.60 | 0.00526 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.09 | 0.00553 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.46 | 8.46 | 1.59 | 1.59 | 8.4593 | 2.2848 | 8.4593 | 0.2701 | 0.3000 |
VAV_MID WITH REHEAT | 78.17 | 78.17 | 24.91 | 24.91 | 78.1657 | 24.9129 | 78.1657 | 0.3187 | 0.3000 |
VAV_TOP WITH REHEAT | 8.69 | 8.69 | 3.64 | 3.64 | 8.6917 | 3.6423 | 8.6917 | 0.4191 | 0.3000 |
CAV_BAS | 5.01 | 5.01 | 1.20 | 1.20 | 5.0116 | 5.0116 | 5.0116 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.26 | 21.26 | 0.34 | 0.34 | 21.2611 | 21.2609 | 21.2611 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4610 | 0.4610 | 0.4610 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.40 | 4.40 | 0.16 | 0.16 | 4.3952 | 4.3952 | 4.3952 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4483 | 0.4483 | 0.4483 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16264.348 | 16264.348 | 1.616663 | 0.00035578 | 453.940 | 1/21 00:10:00 | 1/21 00:10:00 | 16264.35 | 16264.35 | 1.616663 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 16292.26 | 16292.26 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 341488.444 | 341488.444 | 16.163817 | 0.00747007 | 10952.255 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 341488.44 | 341488.44 | 16.163817 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 178873.29 | 0.00 | 342371.31 | 342371.31 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 59375.275 | 59375.275 | 1.764348 | 0.00129884 | 2314.264 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59375.28 | 59375.28 | 1.764348 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 41625.16 | 0.00 | 59501.65 | 59501.65 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4993.323 | 4993.323 | 0.202881 | 0.00010923 | 167.699 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4993.32 | 4993.32 | 0.202881 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00701233 | 45.3685 | 2956.16 | 0.00 | 5005.67 | 5005.67 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3507.789 | 3507.789 | 0.130669 | 0.00007673 | 121.699 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3507.79 | 3507.79 | 0.130669 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00711975 | 46.0560 | 2195.48 | 0.00 | 3516.14 | 3516.14 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6612.925 | 6612.925 | 0.203325 | 0.00014466 | 252.305 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6612.92 | 6612.92 | 0.203325 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00733049 | 47.4033 | 4570.14 | 0.00 | 6627.34 | 6627.34 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2142.609 | 2142.609 | 0.131267 | 0.00004687 | 65.058 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2142.61 | 2142.61 | 0.131267 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00655722 | 42.4538 | 825.57 | 0.00 | 2148.53 | 2148.53 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 145764.747 | 145764.747 | 4.346652 | 0.00318861 | 5668.508 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 145764.75 | 145764.75 | 4.346652 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00762834 | 49.3064 | 102071.53 | 0.00 | 146075.15 | 146075.15 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 97272.910 | 97272.910 | 2.900868 | 0.00212785 | 3782.565 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 97272.91 | 97272.91 | 2.900868 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00764147 | 49.3903 | 68112.19 | 0.00 | 97480.05 | 97480.05 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 144832.074 | 144832.074 | 4.318773 | 0.00316821 | 5632.294 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 144832.07 | 144832.07 | 4.318773 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00762426 | 49.2804 | 101419.46 | 0.00 | 145140.49 | 145140.49 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 86146.194 | 86146.194 | 2.568360 | 0.00188445 | 3350.470 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 86146.19 | 86146.19 | 2.568360 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00755344 | 48.8286 | 60332.62 | 0.00 | 86329.63 | 86329.63 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19231.187 | 19231.187 | 0.573847 | 0.00042068 | 747.543 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19231.19 | 19231.19 | 0.573847 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00774524 | 50.0521 | 13461.41 | 0.00 | 19272.14 | 19272.14 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12699.032 | 12699.032 | 0.378953 | 0.00027779 | 493.610 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12699.03 | 12699.03 | 0.378953 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00774823 | 50.0712 | 8888.80 | 0.00 | 12726.08 | 12726.08 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19142.578 | 19142.578 | 0.571197 | 0.00041874 | 744.104 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19142.58 | 19142.58 | 0.571197 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00774325 | 50.0395 | 13399.48 | 0.00 | 19183.35 | 19183.35 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11862.617 | 11862.617 | 0.353943 | 0.00025950 | 461.142 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11862.62 | 11862.62 | 0.353943 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00771023 | 49.8290 | 8304.15 | 0.00 | 11887.88 | 11887.88 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 219741.717 | -999.000 | 8.459342 | 0.00628459 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 219741.72 | 158323.34 | 8.459342 | 26.44 | 19.08 | 0.01080614 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 24.0030 | 24.00 | 0.00893188 | 48.0124 | 113293.42 | 0.00 | 220088.75 | 156323.13 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 23877.660 | 23877.660 | 2.537803 | 0.00052232 | 545.157 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23877.66 | 23877.66 | 2.537803 | 5.02 | 4.97 | 0.00537364 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 80.0102 | 22.01 | 0.00618518 | 37.6578 | 10547.36 | 0.00 | 24877.50 | 24877.50 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2131844.068 | -999.000 | 78.165735 | 0.06097047 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2131844.07 | 1488927.20 | 78.165735 | 26.72 | 19.41 | 0.01111536 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 25.9781 | 24.00 | 0.00905797 | 48.6815 | 1014993.87 | 0.00 | 2135157.79 | 1473109.93 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 170146.345 | 170146.345 | 23.449721 | 0.00372196 | 3929.580 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 170146.35 | 170146.35 | 23.449721 | 6.80 | 6.16 | 0.00560538 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 86.5938 | 21.00 | 0.00778325 | 50.2931 | 317305.64 | 0.00 | 183229.05 | 183229.05 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 223281.799 | -999.000 | 8.691689 | 0.00638583 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 223281.80 | 161193.83 | 8.691689 | 26.30 | 19.01 | 0.01076852 | 11.05 | 11.05 | 0.00850000 | 33.82 | 0.01653623 | 25.11 | 23.3614 | 24.00 | 0.00900366 | 48.3940 | 119173.84 | 0.00 | 223637.32 | 159117.86 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 14410.056 | 14410.056 | 2.607507 | 0.00031522 | 336.084 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14410.06 | 14410.06 | 2.607507 | 8.23 | 7.14 | 0.00582862 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 77.8713 | 20.26 | 0.00780385 | 52.7922 | 39251.06 | 0.00 | 15948.68 | 15948.68 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 119601.090 | -999.000 | 5.011589 | 0.00342058 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 119601.09 | 83818.70 | 5.011589 | 25.09 | 18.65 | 0.01081008 | 11.42 | 11.42 | 0.00850000 | 28.55 | 0.01652632 | 23.72 | 23.9476 | 24.00 | 0.00900322 | 48.3901 | 68718.32 | 0.00 | 119785.18 | 83293.03 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 235688.333 | 235688.333 | 5.011589 | 0.00515569 | 7677.652 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 235688.33 | 235688.33 | 5.011589 | 1.10 | 1.10 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 23.9476 | 25.44 | 0.00525715 | 26.0830 | 0.00 | 0.00 | 189179.92 | 189179.92 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 432910.509 | 311283.873 | 21.261066 | 0.01060195 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 405616.00 | 395683.06 | -999.0 | 28.51 | 18.07 | 0.00866978 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | -999.0000 | 27.00 | 0.00854239 | 38.4511 | 370237.69 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9410.657 | 6753.818 | 0.461005 | 0.00023047 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8820.41 | 8364.79 | -999.0 | 28.09 | 18.09 | 0.00885932 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00859004 | 38.6604 | 8037.92 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89955.588 | 64470.355 | 4.395207 | 0.00220301 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 84350.72 | 79796.12 | -999.0 | 28.10 | 18.10 | 0.00887670 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00859441 | 38.6801 | 76632.48 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9167.813 | 6573.009 | 0.448267 | 0.00022452 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8595.56 | 8139.92 | -999.0 | 28.10 | 18.10 | 0.00886951 | 12.80 | 12.09 | 0.00850000 | 31.41 | 0.01653169 | 24.48 | -999.0000 | 27.00 | 0.00859255 | 38.6717 | 7812.93 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 432910.509 | 432910.509 | 21.261066 | 0.01060195 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 432910.51 | 432910.51 | 21.261066 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5916 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9410.657 | 9410.657 | 0.461005 | 0.00023047 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9410.66 | 9410.66 | 0.461005 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3909 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89955.588 | 89955.588 | 4.395207 | 0.00220301 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 89955.59 | 89955.59 | 4.395207 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5567 | 24.97 | 0.00801468 | 40.7015 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9167.813 | 9167.813 | 0.448267 | 0.00022452 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9167.81 | 9167.81 | 0.448267 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4873 | 24.09 | 0.00552860 | 29.7080 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14482.888 | 14482.888 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14482.89 | 14482.89 | 21.261066 | 0.07 | 0.07 | 0.00844839 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5916 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.05 | 669.05 | 0.461005 | 0.16 | 0.16 | 0.00839004 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3909 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6690.494 | 6690.494 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.49 | 6690.49 | 4.395207 | 0.16 | 0.16 | 0.00791660 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5567 | 24.97 | 0.00801468 | 40.7015 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.05 | 669.05 | 0.448267 | 0.16 | 0.16 | 0.00551913 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4873 | 24.09 | 0.00552860 | 29.7080 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16264.348 | 16264.348 | 1.616663 | 0.00035578 | 453.940 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 1.1264 | 1.149052 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 16264.35 | 16264.35 | 1.0000 | 1.94511577 | 1.616663 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.35574678 | 60.00 | 48.89 | 11.11 | 0.000 | 16264.35 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 16292.26 | 16292.26 | 1.94511577 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 341488.444 | 341488.444 | 16.163817 | 0.00747007 | 10952.255 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 23.6497 | 24.125642 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 341488.44 | 341488.44 | 1.0000 | 19.44776985 | 16.163817 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 7.46930718 | 60.00 | 48.89 | 11.11 | 0.000 | 341488.44 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 178873.29 | 0.00 | 342371.31 | 342371.31 | 19.44776985 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.06 | 18.06 | 0.00800000 | 50664.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 59375.275 | 59375.275 | 1.764348 | 0.00129884 | 2314.264 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 4.1120 | 4.194773 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59375.28 | 59375.28 | 1.0000 | 2.12280477 | 1.764348 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.29870330 | 60.00 | 48.89 | 11.11 | 0.000 | 59375.28 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 41625.16 | 0.00 | 59501.65 | 59501.65 | 2.12280477 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61089.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4993.323 | 4993.323 | 0.202881 | 0.00010923 | 167.699 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 0.3458 | 0.352771 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4993.32 | 4993.32 | 1.0000 | 0.24409968 | 0.202881 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.10921794 | 60.00 | 48.89 | 11.11 | 0.000 | 4993.32 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.83 | 0.00701233 | 21.00 | 0.00701233 | 45.3685 | 2956.16 | 0.00 | 5005.67 | 5005.67 | 0.24409968 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.91 | 18.99 | 0.00800000 | 53566.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3507.789 | 3507.789 | 0.130669 | 0.00007673 | 121.699 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 0.2429 | 0.247820 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3507.79 | 3507.79 | 1.0000 | 0.15721620 | 0.130669 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.07672516 | 60.00 | 48.89 | 11.11 | 0.000 | 3507.79 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00711975 | 21.00 | 0.00711975 | 46.0560 | 2195.48 | 0.00 | 3516.14 | 3516.14 | 0.15721620 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.73 | 19.57 | 0.00800000 | 55424.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6612.925 | 6612.925 | 0.203325 | 0.00014466 | 252.305 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 0.4580 | 0.467193 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6612.92 | 6612.92 | 1.0000 | 0.24463411 | 0.203325 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.14464316 | 60.00 | 48.89 | 11.11 | 0.000 | 6612.92 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00733049 | 21.00 | 0.00733049 | 47.4033 | 4570.14 | 0.00 | 6627.34 | 6627.34 | 0.24463411 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.37 | 20.99 | 0.00800000 | 60150.7 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2142.609 | 2142.609 | 0.131267 | 0.00004687 | 65.058 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 0.1484 | 0.151372 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2142.61 | 2142.61 | 1.0000 | 0.15793565 | 0.131267 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04686486 | 60.00 | 48.89 | 11.11 | 0.000 | 2142.61 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.93 | 0.00655722 | 21.00 | 0.00655722 | 42.4538 | 825.57 | 0.00 | 2148.53 | 2148.53 | 0.15793565 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.14 | 16.72 | 0.00800000 | 46663.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 145764.747 | 145764.747 | 4.346652 | 0.00318861 | 5668.508 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 10.0949 | 10.298059 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 145764.75 | 145764.75 | 1.0000 | 5.22974729 | 4.346652 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.18828261 | 60.00 | 48.89 | 11.11 | 0.000 | 145764.75 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00762834 | 21.00 | 0.00762834 | 49.3064 | 102071.53 | 0.00 | 146075.15 | 146075.15 | 5.22974729 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 97272.910 | 97272.910 | 2.900868 | 0.00212785 | 3782.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 6.7366 | 6.872184 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 97272.91 | 97272.91 | 1.0000 | 3.49022778 | 2.900868 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.12763055 | 60.00 | 48.89 | 11.11 | 0.000 | 97272.91 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00764147 | 21.00 | 0.00764147 | 49.3903 | 68112.19 | 0.00 | 97480.05 | 97480.05 | 3.49022778 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 144832.074 | 144832.074 | 4.318773 | 0.00316821 | 5632.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 10.0303 | 10.232167 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 144832.07 | 144832.07 | 1.0000 | 5.19620487 | 4.318773 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.16788244 | 60.00 | 48.89 | 11.11 | 0.000 | 144832.07 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00762426 | 21.00 | 0.00762426 | 49.2804 | 101419.46 | 0.00 | 145140.49 | 145140.49 | 5.19620487 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 86146.194 | 86146.194 | 2.568360 | 0.00188445 | 3350.470 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 5.9660 | 6.086098 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 86146.19 | 86146.19 | 1.0000 | 3.09016607 | 2.568360 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.88425815 | 60.00 | 48.89 | 11.11 | 0.000 | 86146.19 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00755344 | 21.00 | 0.00755344 | 48.8286 | 60332.62 | 0.00 | 86329.63 | 86329.63 | 3.09016607 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19231.187 | 19231.187 | 0.573847 | 0.00042068 | 747.543 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 1.3319 | 1.358654 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19231.19 | 19231.19 | 1.0000 | 0.69043371 | 0.573847 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.42063983 | 60.00 | 48.89 | 11.11 | 0.000 | 19231.19 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00774524 | 21.00 | 0.00774524 | 50.0521 | 13461.41 | 0.00 | 19272.14 | 19272.14 | 0.69043371 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12699.032 | 12699.032 | 0.378953 | 0.00027779 | 493.610 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 0.8795 | 0.897167 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12699.03 | 12699.03 | 1.0000 | 0.45594428 | 0.378953 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.27776333 | 60.00 | 48.89 | 11.11 | 0.000 | 12699.03 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00774823 | 21.00 | 0.00774823 | 50.0712 | 8888.80 | 0.00 | 12726.08 | 12726.08 | 0.45594428 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19142.578 | 19142.578 | 0.571197 | 0.00041874 | 744.104 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 1.3257 | 1.352394 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19142.58 | 19142.58 | 1.0000 | 0.68724482 | 0.571197 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.41870172 | 60.00 | 48.89 | 11.11 | 0.000 | 19142.58 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00774325 | 21.00 | 0.00774325 | 50.0395 | 13399.48 | 0.00 | 19183.35 | 19183.35 | 0.68724482 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11862.617 | 11862.617 | 0.353943 | 0.00025950 | 461.142 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 0.8215 | 0.838076 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11862.62 | 11862.62 | 1.0000 | 0.42585306 | 0.353943 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.25946861 | 60.00 | 48.89 | 11.11 | 0.000 | 11862.62 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00771023 | 21.00 | 0.00771023 | 49.8290 | 8304.15 | 0.00 | 11887.88 | 11887.88 | 0.42585306 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 219741.717 | -999.000 | 8.459342 | 0.00628459 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9281 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.459342 | 10.17800048 | 4197.9300 | 999.8980 | 77.05360192 | 15.00 | 6.67 | 8.33 | 2694468.67 | 8.1553 | 8.155289 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 219741.72 | 158323.34 | 1.0000 | 10.17800048 | 8.459342 | 26.44 | 19.08 | 0.01080614 | 54123.5 | 11.05 | 11.05 | 0.00850000 | 32533.7 | 6.28394420 | 6.67 | 15.00 | 8.33 | 18280.188 | 201461.53 | 33.90 | 0.01653638 | 25.13 | 2.03050000 | 24.0030 | 24.00 | 0.00893188 | 24.00 | 0.00893188 | 48.0124 | 113293.42 | 0.00 | 220088.75 | 156323.13 | 10.17800048 | 26.44 | 19.09 | 0.01080614 | 54123.5 | 11.45 | 11.36 | 0.00832222 | 32499.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23877.660 | 23877.660 | 2.537803 | 0.00052232 | 545.157 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.459342 | 10.17800048 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 1.6536 | 1.686921 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23877.66 | 23877.66 | 1.0000 | 3.05340014 | 2.537803 | 5.02 | 4.97 | 0.00537364 | 18531.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.52227118 | 60.00 | 48.89 | 11.11 | 0.000 | 23877.66 | 4.60 | 0.00525715 | 4.60 | 2.03050000 | 80.0102 | 6.69 | 0.00583992 | 22.01 | 0.00618518 | 37.6578 | 10547.36 | 0.00 | 24877.50 | 24877.50 | 3.05340014 | 2.80 | 2.80 | 0.00537364 | 16280.7 | 10.83 | 7.86 | 0.00537364 | 24428.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2131844.068 | -999.000 | 78.165735 | 0.06097047 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5029 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.165735 | 94.04642517 | 4197.9300 | 999.8980 | 77.05360192 | 15.00 | 6.67 | 8.33 | 2694468.67 | 79.1193 | 79.119275 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2131844.07 | 1488927.20 | 1.0000 | 94.04642517 | 78.165735 | 26.72 | 19.41 | 0.01111536 | 55202.7 | 11.05 | 11.05 | 0.00850000 | 32534.7 | 60.96425085 | 6.67 | 15.00 | 8.33 | 168911.991 | 1962932.08 | 33.90 | 0.01653638 | 25.13 | 20.30600000 | 25.9781 | 24.00 | 0.00905797 | 24.00 | 0.00905797 | 48.6815 | 1014993.87 | 0.00 | 2135157.79 | 1473109.93 | 94.04642517 | 26.72 | 19.42 | 0.01111536 | 55202.7 | 11.45 | 11.36 | 0.00832434 | 32499.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 170146.345 | 170146.345 | 23.449721 | 0.00372196 | 3929.580 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.165735 | 94.04642517 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 11.7834 | 12.020582 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 170146.35 | 170146.35 | 1.0000 | 28.21392755 | 23.449721 | 6.80 | 6.16 | 0.00560538 | 20921.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 3.72157635 | 60.00 | 48.89 | 11.11 | 0.000 | 170146.35 | 4.60 | 0.00525715 | 4.60 | 20.30600000 | 86.5938 | 21.00 | 0.00785472 | 21.00 | 0.00778325 | 50.2931 | 317305.64 | 0.00 | 183229.05 | 183229.05 | 28.21392755 | 2.80 | 2.80 | 0.00560538 | 16861.5 | 9.20 | 7.35 | 0.00560538 | 23355.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 223281.799 | -999.000 | 8.691689 | 0.00638583 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8581 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.691689 | 10.45755211 | 4197.9300 | 999.8980 | 77.05360192 | 15.00 | 6.67 | 8.33 | 2694468.67 | 8.2867 | 8.286673 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | Sensible | 223281.80 | 161193.83 | 1.0000 | 10.45755211 | 8.691689 | 26.30 | 19.01 | 0.01076852 | 53884.8 | 11.05 | 11.05 | 0.00850000 | 32533.5 | 6.38517977 | 6.67 | 15.00 | 8.33 | 18782.276 | 204499.52 | 33.82 | 0.01653623 | 25.11 | 2.03050000 | 23.3614 | 24.00 | 0.00900366 | 24.00 | 0.00900366 | 48.3940 | 119173.84 | 0.00 | 223637.32 | 159117.86 | 10.45755211 | 26.30 | 19.02 | 0.01076852 | 53884.8 | 11.45 | 11.36 | 0.00832241 | 32499.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14410.056 | 14410.056 | 2.607507 | 0.00031522 | 336.084 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.691689 | 10.45755211 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 0.9980 | 1.018049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14410.06 | 14410.06 | 1.0000 | 3.13726563 | 2.607507 | 8.23 | 7.14 | 0.00582862 | 22935.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.31518821 | 60.00 | 48.89 | 11.11 | 0.000 | 14410.06 | 4.60 | 0.00525715 | 4.60 | 2.03050000 | 77.8713 | 21.00 | 0.00783966 | 20.26 | 0.00780385 | 52.7922 | 39251.06 | 0.00 | 15948.68 | 15948.68 | 3.13726563 | 2.80 | 2.80 | 0.00582862 | 17420.9 | 7.81 | 6.94 | 0.00582862 | 22504.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 119601.090 | -999.000 | 5.011589 | 0.00342058 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9354 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.011589 | 6.02977761 | 4197.9300 | 999.8980 | 77.05360192 | 15.00 | 6.67 | 8.33 | 2694468.67 | 4.4388 | 4.438763 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 119601.09 | 83818.70 | 1.0000 | 6.02977761 | 5.011589 | 25.09 | 18.65 | 0.01081008 | 52753.8 | 11.42 | 11.42 | 0.00850000 | 32918.8 | 3.42022710 | 6.67 | 15.00 | 8.33 | 8497.922 | 111103.17 | 28.55 | 0.01652632 | 23.72 | 1.20015641 | 23.9476 | 24.00 | 0.00900322 | 24.00 | 0.00900322 | 48.3901 | 68718.32 | 0.00 | 119785.18 | 83293.03 | 6.02977761 | 25.09 | 18.66 | 0.01081008 | 52753.8 | 11.62 | 11.52 | 0.00841091 | 32888.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 235688.333 | 235688.333 | 5.011589 | 0.00515569 | 7677.652 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.011589 | 6.02977761 | 4197.9300 | 999.8980 | 30.96003428 | 48.89 | 60.00 | 11.11 | 1443945.11 | 16.3225 | 16.651025 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 235688.33 | 235688.33 | 1.0000 | 6.02977761 | 5.011589 | 1.10 | 1.10 | 0.00525715 | 14265.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 5.15516291 | 60.00 | 48.89 | 11.11 | 0.000 | 235688.33 | 4.60 | 0.00525715 | 4.60 | 1.20015641 | 23.9476 | 0.00 | 0.00525715 | 25.44 | 0.00525715 | 26.0830 | 0.00 | 0.00 | 189179.92 | 189179.92 | 6.02977761 | 12.80 | 8.65 | 0.00525715 | 26134.9 | 43.72 | 20.28 | 0.00525715 | 57509.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 432910.509 | 311283.873 | 21.261066 | 0.01060195 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9567 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 405616.00 | 395683.06 | 0.9370 | -999.0 | -999.0 | 28.51 | 18.07 | 0.00866978 | 50789.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 405616.00 | 33.90 | 0.01653638 | 25.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854239 | 27.00 | 0.00854239 | 38.4511 | 370237.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9410.657 | 6753.818 | 0.461005 | 0.00023047 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3090 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8820.41 | 8364.79 | 0.9373 | -999.0 | -999.0 | 28.09 | 18.09 | 0.00885932 | 50843.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8820.41 | 31.21 | 0.01653132 | 24.43 | 0.01563234 | -999.0000 | 27.00 | 0.00859004 | 27.00 | 0.00859004 | 38.6604 | 8037.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89955.588 | 64470.355 | 4.395207 | 0.00220301 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3413 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 84350.72 | 79796.12 | 0.9377 | -999.0 | -999.0 | 28.10 | 18.10 | 0.00887670 | 50894.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84350.72 | 31.21 | 0.01653132 | 24.43 | 0.15632344 | -999.0000 | 27.00 | 0.00859441 | 27.00 | 0.00859441 | 38.6801 | 76632.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9167.813 | 6573.009 | 0.448267 | 0.00022452 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3280 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8595.56 | 8139.92 | 0.9376 | -999.0 | -999.0 | 28.10 | 18.10 | 0.00886951 | 50880.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8595.56 | 31.41 | 0.01653169 | 24.48 | 0.01563234 | -999.0000 | 27.00 | 0.00859255 | 27.00 | 0.00859255 | 38.6717 | 7812.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 432910.509 | 432910.509 | 21.261066 | 0.01060195 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 432910.51 | 432910.51 | 1.0000 | 25.58061117 | 21.261066 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 432910.51 | 4.60 | 0.00525715 | 4.60 | 0.33839277 | 1.5916 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9410.657 | 9410.657 | 0.461005 | 0.00023047 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9410.66 | 9410.66 | 1.0000 | 0.55466648 | 0.461005 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9410.66 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.3909 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89955.588 | 89955.588 | 4.395207 | 0.00220301 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 89955.59 | 89955.59 | 1.0000 | 5.28816788 | 4.395207 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89955.59 | 4.60 | 0.00525715 | 4.60 | 0.15632344 | 3.5567 | 0.00 | 0.00801468 | 24.97 | 0.00801468 | 40.7015 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9167.813 | 9167.813 | 0.448267 | 0.00022452 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9167.81 | 9167.81 | 1.0000 | 0.53934038 | 0.448267 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9167.81 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.4873 | 0.00 | 0.00552860 | 24.09 | 0.00552860 | 29.7080 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14482.888 | 14482.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.261066 | 25.58061117 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14482.89 | 14482.89 | 1.0000 | 25.58061117 | 21.261066 | 0.07 | 0.07 | 0.00844839 | 21203.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14482.89 | 4.60 | 0.00525715 | 4.60 | 0.33839277 | 1.5916 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.461005 | 0.55466648 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.05 | 669.05 | 1.0000 | 0.55466648 | 0.461005 | 0.16 | 0.16 | 0.00839004 | 21142.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.05 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.3909 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6690.494 | 6690.494 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.395207 | 5.28816788 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6690.49 | 6690.49 | 1.0000 | 5.28816788 | 4.395207 | 0.16 | 0.16 | 0.00791660 | 19965.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.49 | 4.60 | 0.00525715 | 4.60 | 0.15632344 | 3.5567 | 0.00 | 0.00801468 | 24.97 | 0.00801468 | 40.7015 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.448267 | 0.53934038 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.05 | 669.05 | 1.0000 | 0.53934038 | 0.448267 | 0.16 | 0.16 | 0.00551913 | 13965.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.05 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.4873 | 0.00 | 0.00552860 | 24.09 | 0.00552860 | 29.7080 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.46 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 78.17 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.69 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.01 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialEnthalpy | 0.34 | 21.26 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4892.17 | 2512.00 | 2393.33 |
CORE_BOTTOM | 4712.17 | 235.00 | 0.00 |
CORE_MID | 2660.00 | 1476.00 | 0.00 |
CORE_TOP | 3090.00 | 1860.83 | 49.67 |
PERIMETER_BOT_ZN_3 | 4123.50 | 1236.50 | 51.67 |
PERIMETER_BOT_ZN_2 | 4238.50 | 1231.00 | 242.33 |
PERIMETER_BOT_ZN_1 | 4704.17 | 930.17 | 269.00 |
PERIMETER_BOT_ZN_4 | 5105.17 | 831.17 | 512.67 |
PERIMETER_MID_ZN_3 | 3561.00 | 2307.50 | 362.00 |
PERIMETER_MID_ZN_2 | 3326.17 | 1727.67 | 462.17 |
PERIMETER_MID_ZN_1 | 4419.50 | 1384.83 | 433.83 |
PERIMETER_MID_ZN_4 | 4239.83 | 1671.67 | 433.83 |
PERIMETER_TOP_ZN_3 | 3825.83 | 2539.67 | 772.17 |
PERIMETER_TOP_ZN_2 | 4074.00 | 2117.50 | 662.83 |
PERIMETER_TOP_ZN_1 | 4355.33 | 1672.67 | 601.67 |
PERIMETER_TOP_ZN_4 | 4231.50 | 1938.50 | 640.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1088.17 | 1088.17 |
DATACENTER_MID_ZN_6 | 5936.50 | 80.33 | 80.33 |
DATACENTER_TOP_ZN_6 | 5860.67 | 263.33 | 243.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5936.67 | 5936.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 71.83 | 0.00 | 2.33 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 2.83 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 49.00 | 0.00 | 48.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 76.17 | 0.00 | 72.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 238.17 | 0.00 | 97.33 |
PERIMETER_MID_ZN_3 | 0.33 | 0.50 | 0.00 | 0.50 |
PERIMETER_MID_ZN_2 | 0.00 | 60.33 | 0.00 | 58.50 |
PERIMETER_MID_ZN_1 | 0.00 | 88.17 | 0.00 | 86.33 |
PERIMETER_MID_ZN_4 | 0.00 | 67.50 | 0.00 | 40.83 |
PERIMETER_TOP_ZN_3 | 8.67 | 24.67 | 1.83 | 19.50 |
PERIMETER_TOP_ZN_2 | 5.67 | 74.83 | 0.33 | 65.83 |
PERIMETER_TOP_ZN_1 | 2.67 | 81.83 | 0.17 | 74.67 |
PERIMETER_TOP_ZN_4 | 2.33 | 84.17 | 0.00 | 49.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 34.33 | 0.00 | 34.33 |
DATACENTER_MID_ZN_6 | 0.00 | 26.83 | 0.00 | 26.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 16.00 | 0.00 | 16.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 633.33 | 0.00 | 552.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 8.83 | 1083.83 | 1.83 | 800.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.930 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.562 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.488 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.476 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.627 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.776 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.915 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 1.216 | 0.035 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.595 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.729 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.893 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.846 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.591 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.777 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.860 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.822 | 0.101 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 11.824 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38012388.04 | 0.00 | 38012388.04 | 0.00 | 38012388.04 | 37848132.68 | 4161.85 | 2793.80 | 1804.36 | 166.75 |
CORE_BOTTOM | 23111782.05 | 0.00 | 23111782.05 | 0.00 | 23111782.05 | 33990283.35 | 6770.76 | 101.36 | 1887.88 | 112.49 |
CORE_MID | 0.20E+09 | 0.00 | 0.20E+09 | 0.00 | 0.20E+09 | 0.34E+09 | 6726.36 | 301.63 | 1732.01 | 16.64 |
CORE_TOP | 19173554.20 | 0.00 | 19173554.20 | 0.00 | 19173554.20 | 33990283.35 | 6803.26 | 340.71 | 1616.03 | 42.28 |
PERIMETER_BOT_ZN_3 | 3220940.10 | 0.00 | 3220940.10 | 328931.10 | 3549871.19 | 4267819.30 | 4470.16 | 116.54 | 4173.30 | 112.49 |
PERIMETER_BOT_ZN_2 | 2555739.04 | 0.00 | 2555739.04 | 219287.25 | 2775026.29 | 2750345.05 | 4421.79 | 85.57 | 4252.65 | 112.49 |
PERIMETER_BOT_ZN_1 | 4665652.31 | 0.00 | 4665652.31 | 328931.10 | 4994583.41 | 4267912.63 | 4194.97 | 55.83 | 4509.20 | 112.49 |
PERIMETER_BOT_ZN_4 | 3993026.52 | 0.00 | 3993026.52 | 219287.25 | 4212313.77 | 2750345.05 | 4097.63 | 8.88 | 4653.49 | 112.49 |
PERIMETER_MID_ZN_3 | 29942300.42 | 0.00 | 29942300.42 | 771421.61 | 30713722.03 | 42678193.03 | 4656.95 | 253.43 | 3849.62 | 16.64 |
PERIMETER_MID_ZN_2 | 24308021.96 | 0.00 | 24308021.96 | 514280.72 | 24822302.68 | 27503450.52 | 4584.58 | 157.68 | 4017.73 | 830.33 |
PERIMETER_MID_ZN_1 | 44875292.25 | 0.00 | 44875292.25 | 771421.61 | 45646713.87 | 42679126.28 | 4289.62 | 184.81 | 4285.57 | 16.64 |
PERIMETER_MID_ZN_4 | 27375612.53 | 0.00 | 27375612.53 | 514280.72 | 27889893.26 | 27503450.52 | 4286.39 | 40.04 | 4433.57 | 16.64 |
PERIMETER_TOP_ZN_3 | 2987664.38 | 0.00 | 2987664.38 | 957784.80 | 3945449.18 | 4267819.30 | 4623.42 | 273.69 | 3862.89 | 42.28 |
PERIMETER_TOP_ZN_2 | 2524046.73 | 0.00 | 2524046.73 | 638522.76 | 3162569.49 | 2750345.05 | 4314.60 | 173.58 | 4271.82 | 42.28 |
PERIMETER_TOP_ZN_1 | 4331275.02 | 0.00 | 4331275.02 | 957784.80 | 5289059.81 | 4267912.63 | 4310.10 | 179.17 | 4270.73 | 42.28 |
PERIMETER_TOP_ZN_4 | 2668587.02 | 0.00 | 2668587.02 | 638522.76 | 3307109.78 | 2750345.05 | 4316.48 | 73.03 | 4370.49 | 42.28 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.19E+09 | 0.00 | 0.19E+09 | 0.00 | 0.19E+09 | 10671554.30 | 2699.81 | 2876.00 | 3184.19 | 1095.83 |
Total Facility | 0.35E+10 | 0.00 | 0.35E+10 | 30003098.57 | 0.36E+10 | 0.50E+10 | 7588.50 | 4354.12 | 6115.65 | 1950.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.7139 | 0.0000 | 1.7139 | 0.0000 | 1.7139 | 1.2002 | 1452.92 | 2792.74 | 1697.34 |
CORE_BOTTOM | 1.0481 | 0.0000 | 1.0481 | 0.0000 | 1.0481 | 1.0778 | 4061.57 | 101.05 | 1780.38 |
CORE_MID | 9.0987 | 0.0000 | 9.0987 | 0.0000 | 9.0987 | 10.7782 | 3921.44 | 301.41 | 1720.15 |
CORE_TOP | 0.8897 | 0.0000 | 0.8897 | 0.0000 | 0.8897 | 1.0778 | 3999.68 | 340.11 | 1603.21 |
PERIMETER_BOT_ZN_3 | 0.1469 | 0.0000 | 0.1469 | 0.0079 | 0.1548 | 0.1353 | 1760.40 | 116.16 | 4066.45 |
PERIMETER_BOT_ZN_2 | 0.1171 | 0.0000 | 0.1171 | 0.0053 | 0.1224 | 0.0872 | 1712.02 | 85.05 | 4145.93 |
PERIMETER_BOT_ZN_1 | 0.2144 | 0.0000 | 0.2144 | 0.0079 | 0.2223 | 0.1353 | 1485.21 | 55.61 | 4402.18 |
PERIMETER_BOT_ZN_4 | 0.1835 | 0.0000 | 0.1835 | 0.0053 | 0.1887 | 0.0872 | 1387.95 | 8.71 | 4546.34 |
PERIMETER_MID_ZN_3 | 1.3946 | 0.0000 | 1.3946 | 0.0185 | 1.4131 | 1.3533 | 1852.79 | 253.26 | 3836.95 |
PERIMETER_MID_ZN_2 | 1.1002 | 0.0000 | 1.1002 | 0.0131 | 1.1133 | 0.8721 | 1512.37 | 151.38 | 3370.25 |
PERIMETER_MID_ZN_1 | 2.0926 | 0.0000 | 2.0926 | 0.0185 | 2.1111 | 1.3533 | 1484.73 | 184.58 | 4273.69 |
PERIMETER_MID_ZN_4 | 1.2758 | 0.0000 | 1.2758 | 0.0123 | 1.2881 | 0.8721 | 1481.53 | 39.82 | 4421.65 |
PERIMETER_TOP_ZN_3 | 0.1387 | 0.0000 | 0.1387 | 0.0229 | 0.1616 | 0.1353 | 1827.10 | 273.15 | 3842.74 |
PERIMETER_TOP_ZN_2 | 0.1173 | 0.0000 | 0.1173 | 0.0153 | 0.1326 | 0.0872 | 1516.76 | 173.12 | 4253.12 |
PERIMETER_TOP_ZN_1 | 0.2016 | 0.0000 | 0.2016 | 0.0229 | 0.2245 | 0.1353 | 1509.28 | 178.65 | 4255.07 |
PERIMETER_TOP_ZN_4 | 0.1241 | 0.0000 | 0.1241 | 0.0153 | 0.1394 | 0.0872 | 1515.10 | 72.54 | 4355.35 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6.1071 | 0.0000 | 6.1071 | 0.0000 | 6.1071 | 0.3384 | 978.64 | 2876.00 | 2088.36 |
Total Facility | 161.7859 | 0.0000 | 161.7859 | 0.7263 | 162.5123 | 158.4706 | 4771.50 | 4351.57 | 4981.40 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 54353238.83 | 0.00 | 54353238.83 | 48026705.38 | 4065.56 | 0.00 | 4694.44 | 112.49 |
VAV_MID WITH REHEAT | 0.47E+09 | 0.00 | 0.47E+09 | 0.48E+09 | 4216.43 | 0.83 | 4542.74 | 16.64 |
VAV_TOP WITH REHEAT | 45867664.74 | 0.00 | 45867664.74 | 48026705.38 | 4229.79 | 1.40 | 4528.81 | 42.28 |
CAV_BAS | 55027135.14 | 0.00 | 55027135.14 | 37848132.68 | 4139.73 | 0.96 | 4619.31 | 166.75 |
AIRLOOP DATACENTER BASEMENT | 0.28E+09 | 0.00 | 0.28E+09 | 10671554.30 | 2699.81 | 0.00 | 6060.19 | 1095.83 |
AIRLOOP DATACENTER BOT | 353645.50 | 0.00 | 353645.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3536455.01 | 0.00 | 3536455.01 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353645.50 | 0.00 | 353645.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.4754 | 0.0000 | 2.4754 | 1.5229 | 1361.05 | 0.00 | 4581.95 |
VAV_MID WITH REHEAT | 21.7065 | 0.0000 | 21.7065 | 15.2292 | 1416.07 | 0.33 | 4526.60 |
VAV_TOP WITH REHEAT | 2.1299 | 0.0000 | 2.1299 | 1.5229 | 1441.19 | 1.26 | 4500.56 |
CAV_BAS | 2.4811 | 0.0000 | 2.4811 | 1.2002 | 1447.30 | 0.25 | 4495.45 |
AIRLOOP DATACENTER BASEMENT | 8.8407 | 0.0000 | 8.8407 | 0.3384 | 978.64 | 0.00 | 4964.36 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1653 | 0.0000 | 0.1653 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 114.45 | 1634.20 | 0.00 | 0.00 | 0.00 | 2945.79 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 266.91 | 1341.50 | 0.00 | 0.00 | 0.00 | 2935.49 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 102.62 | 1410.58 | 0.00 | 0.00 | 0.00 | 3042.49 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2792.33 | 1873.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 2876.00 | 3184.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.7320 | 4.7091 | 0.0000 | 0.0000 | 0.0000 | 2.4567 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.3843 | 36.7535 | 0.0000 | 0.0000 | 0.0000 | 24.7882 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.7126 | 3.6046 | 0.0000 | 0.0000 | 0.0000 | 2.4491 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7376 | 5.7960 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4900 | 24.4881 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2263 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1528 |
Defaulted Fields | 1187 |
Fields with Defaults | 3933 |
Autosized Fields | 336 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26761.82 | 292329.59 | 15-JAN-05:00 | 1628470.72 | 03-AUG-15:30 |
Electricity:Building | 16388.50 | 215366.33 | 14-MAY-17:10 | 942265.72 | 12-DEC-08:10 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16388.50 | 215366.33 | 14-MAY-17:10 | 942265.72 | 12-DEC-08:10 |
InteriorLights:Electricity | 1712.11 | 8110.17 | 01-JAN-08:50 | 164275.09 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1712.11 | 8110.17 | 01-JAN-08:50 | 164275.09 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 1712.11 | 8110.17 | 01-JAN-08:50 | 164275.09 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1712.11 | 8110.17 | 01-JAN-08:50 | 164275.09 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.83 | 589.50 | 26-MAR-17:10 | 3177.78 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.46 | 30.32 | 01-JAN-08:50 | 1017.23 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.46 | 30.32 | 01-JAN-08:50 | 1017.23 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.22 | 379.89 | 26-MAR-17:10 | 2031.40 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-07:50 | 639.05 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-07:50 | 639.05 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.75 | 589.50 | 12-MAR-17:10 | 3169.66 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.38 | 30.33 | 01-JAN-07:50 | 1009.08 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.38 | 30.33 | 01-JAN-07:50 | 1009.08 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.22 | 379.89 | 26-FEB-18:10 | 2054.08 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.78 | 19.54 | 01-JAN-08:50 | 661.75 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.78 | 19.54 | 01-JAN-08:50 | 661.75 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 438.13 | 5894.96 | 12-MAR-17:10 | 31762.48 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.48 | 303.25 | 01-JAN-08:50 | 10156.96 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.48 | 303.25 | 01-JAN-08:50 | 10156.96 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.15 | 3798.93 | 26-MAR-17:10 | 20289.56 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.80 | 195.42 | 01-JAN-07:50 | 6366.14 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.80 | 195.42 | 01-JAN-07:50 | 6366.14 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 437.40 | 5895.05 | 12-MAR-17:10 | 31680.82 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.74 | 303.26 | 01-JAN-07:50 | 10074.98 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.74 | 303.26 | 01-JAN-07:50 | 10074.98 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.11 | 3798.91 | 26-FEB-18:10 | 20520.50 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.76 | 195.42 | 01-JAN-08:50 | 6597.18 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.76 | 195.42 | 01-JAN-08:50 | 6597.18 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.81 | 589.50 | 12-MAR-17:10 | 3175.98 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.45 | 30.32 | 01-JAN-08:50 | 1015.43 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.45 | 30.32 | 01-JAN-08:50 | 1015.43 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.21 | 379.89 | 26-MAR-17:10 | 2028.75 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.78 | 19.54 | 01-JAN-07:50 | 636.41 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.78 | 19.54 | 01-JAN-07:50 | 636.41 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.74 | 589.50 | 12-MAR-17:10 | 3167.81 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.37 | 30.33 | 01-JAN-07:50 | 1007.22 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.37 | 30.33 | 01-JAN-07:50 | 1007.22 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.21 | 379.89 | 26-FEB-18:10 | 2051.89 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.78 | 19.54 | 01-JAN-08:50 | 659.56 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.78 | 19.54 | 01-JAN-08:50 | 659.56 | 25-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 4389.50 | 3744.32 | 10-JAN-05:00 | 378949.82 | 05-JUL-12:10 |
HeatRejection:Electricity | 1551.85 | 244.67 | 05-JAN-08:00 | 81663.54 | 02-JAN-11:30 |
General:HeatRejection:Electricity | 1551.85 | 244.67 | 05-JAN-08:00 | 81663.54 | 02-JAN-11:30 |
ElectricityProduced:Facility | 542.70 | -0.00 | 20-DEC-17:30 | 86329.64 | 10-APR-12:30 |
ElectricityProduced:Plant | 542.70 | -0.00 | 20-DEC-17:30 | 86329.64 | 10-APR-12:30 |
Photovoltaic:ElectricityProduced | 566.52 | 0.00 | 01-JAN-00:10 | 89893.10 | 10-APR-12:30 |
PowerConversion:ElectricityProduced | -23.82 | -3563.46 | 10-APR-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 4570.14 | 45577.39 | 15-JAN-06:00 | 389944.97 | 18-APR-14:20 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73697.78 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3369.18 | 25-OCT-07:20 |
ElectricityPurchased:Facility | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
ElectricityPurchased:Plant | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
Cogeneration:ElectricityPurchased | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
ElectricityNet:Plant | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
Cogeneration:ElectricityNet | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
General:Cogeneration:ElectricityNet | 26219.12 | 279944.38 | 15-JAN-10:10 | 1580520.21 | 30-AUG-16:00 |
Fans:Electricity | 2028.07 | 41191.87 | 01-JAN-04:50 | 255581.86 | 03-MAY-12:30 |
General:Fans:Electricity | 2028.07 | 41191.87 | 01-JAN-04:50 | 255581.86 | 03-MAY-12:30 |
ExteriorLights:Electricity | 264.34 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 264.34 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
HeatRecovery:Electricity | 50.61 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-10:10 |
General:HeatRecovery:Electricity | 50.61 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-10:10 |
Cooling:Electricity | 4290.25 | 2318.74 | 10-JAN-07:10 | 395912.86 | 10-AUG-12:10 |
General:Cooling:Electricity | 4290.25 | 2318.74 | 10-JAN-07:10 | 395912.86 | 10-AUG-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 338.60 | 0.00 | 01-JAN-00:10 | 100000.00 | 04-FEB-17:10 |
General:Humidifier:Electricity | 338.60 | 0.00 | 01-JAN-00:10 | 100000.00 | 04-FEB-17:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 645.91 | 3348.46 | 01-JAN-00:20 | 57493.23 | 23-OCT-09:30 |
General:Pumps:Electricity | 645.91 | 3348.46 | 01-JAN-00:20 | 57493.23 | 23-OCT-09:30 |
WIRED_LTG_ELECTRICITY | 48.11 | 0.00 | 01-JAN-00:10 | 4616.13 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 711.88 | 7280.88 | 29-APR-16:10 | 487423.11 | 06-FEB-06:10 |
NaturalGas:Plant | 711.88 | 7280.88 | 29-APR-16:10 | 487423.11 | 06-FEB-06:10 |
Heating:NaturalGas | 67.00 | 0.00 | 01-JAN-00:10 | 463207.59 | 06-FEB-05:20 |
Boiler:Heating:NaturalGas | 67.00 | 0.00 | 01-JAN-00:10 | 463207.59 | 06-FEB-05:20 |
WaterSystems:NaturalGas | 644.88 | 7280.88 | 23-JAN-05:20 | 74963.99 | 27-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 644.88 | 7280.88 | 23-JAN-05:20 | 74963.99 | 27-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 24230.16 | 7740.17 | 11-JAN-07:10 | 2298996.09 | 07-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 24230.16 | 7740.17 | 11-JAN-07:10 | 2298996.09 | 07-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 24230.16 | 7740.17 | 11-JAN-07:10 | 2298996.09 | 07-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 13579.90 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Water:HVAC | 125.96 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:20 |
Humidifier:Water | 125.96 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:20 |
General:Humidifier:Water | 125.96 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:20 |
MainsWater:Facility | 13579.90 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
MainsWater:HVAC | 125.96 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:20 |
Humidifier:MainsWater | 125.96 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:20 |
General:Humidifier:MainsWater | 125.96 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:20 |
Water:Plant | 13453.94 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 13453.94 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 11173.78 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
General:HeatRejection:Water | 11173.78 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
HeatRejection:MainsWater | 11173.78 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
General:HeatRejection:MainsWater | 11173.78 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 93508.47 | 102164.61 | 10-JAN-05:40 | 9078055.15 | 06-OCT-14:10 |
EnergyTransfer:Building | 20150.36 | 91472.38 | 10-JAN-05:40 | 1508089.36 | 30-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 645.27 | 0.00 | 01-JAN-00:10 | 73609.86 | 26-DEC-06:10 |
Heating:EnergyTransfer | 38.69 | 0.00 | 01-JAN-00:10 | 260580.87 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.13 | 0.00 | 01-JAN-00:10 | 23297.97 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 38.69 | 0.00 | 01-JAN-00:10 | 260580.87 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.13 | 0.00 | 01-JAN-00:10 | 23297.97 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 20111.67 | 90968.41 | 10-JAN-05:40 | 1508089.36 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 641.14 | 0.00 | 01-JAN-00:10 | 73609.86 | 26-DEC-06:10 |
General:Cooling:EnergyTransfer | 20111.67 | 90968.41 | 10-JAN-05:40 | 1508089.36 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 641.14 | 0.00 | 01-JAN-00:10 | 73609.86 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 667.13 | 0.00 | 01-JAN-00:10 | 51428.08 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 667.13 | 0.00 | 01-JAN-00:10 | 51428.08 | 02-JAN-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 667.13 | 0.00 | 01-JAN-00:10 | 51428.08 | 02-JAN-06:10 |
EnergyTransfer:Zone:CORE_MID | 4875.37 | 0.00 | 01-JAN-00:10 | 412029.20 | 14-APR-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4875.37 | 0.00 | 01-JAN-00:10 | 412029.20 | 14-APR-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4875.37 | 0.00 | 01-JAN-00:10 | 412029.20 | 14-APR-05:10 |
EnergyTransfer:Zone:CORE_TOP | 496.34 | 0.00 | 01-JAN-00:10 | 49653.73 | 03-MAY-12:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.52 | 0.00 | 01-JAN-00:10 | 47188.79 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.52 | 0.00 | 01-JAN-00:10 | 47188.79 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 495.82 | 0.00 | 01-JAN-00:10 | 49653.73 | 03-MAY-12:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 495.82 | 0.00 | 01-JAN-00:10 | 49653.73 | 03-MAY-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 99.89 | 0.00 | 01-JAN-00:10 | 11244.43 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 99.89 | 0.00 | 01-JAN-00:10 | 11244.43 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 99.89 | 0.00 | 01-JAN-00:10 | 11244.43 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 78.07 | 0.00 | 01-JAN-00:10 | 11496.63 | 12-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 281.36 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 281.36 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 78.07 | 0.00 | 01-JAN-00:10 | 11496.63 | 12-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 78.07 | 0.00 | 01-JAN-00:10 | 11496.63 | 12-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 132.43 | 0.00 | 01-JAN-00:10 | 17250.63 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 46.31 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 46.31 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 132.43 | 0.00 | 01-JAN-00:10 | 17250.63 | 06-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 132.43 | 0.00 | 01-JAN-00:10 | 17250.63 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 118.40 | 0.00 | 01-JAN-00:10 | 16563.04 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 118.40 | 0.00 | 01-JAN-00:10 | 16563.04 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 118.40 | 0.00 | 01-JAN-00:10 | 16563.04 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 769.10 | 0.00 | 01-JAN-00:10 | 99383.41 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.58 | 0.00 | 01-JAN-00:10 | 66990.99 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.58 | 0.00 | 01-JAN-00:10 | 66990.99 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 763.51 | 0.00 | 01-JAN-00:10 | 99383.41 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 763.51 | 0.00 | 01-JAN-00:10 | 99383.41 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 666.51 | 0.00 | 01-JAN-00:10 | 120704.12 | 20-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.28 | 0.00 | 01-JAN-00:10 | 35915.53 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.28 | 0.00 | 01-JAN-00:10 | 35915.53 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 664.24 | 0.00 | 01-JAN-00:10 | 120704.12 | 20-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 664.24 | 0.00 | 01-JAN-00:10 | 120704.12 | 20-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1129.83 | 0.00 | 01-JAN-00:10 | 168068.16 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.21 | 0.00 | 01-JAN-00:10 | 39170.74 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.21 | 0.00 | 01-JAN-00:10 | 39170.74 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1128.61 | 0.00 | 01-JAN-00:10 | 168068.16 | 06-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1128.61 | 0.00 | 01-JAN-00:10 | 168068.16 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 730.57 | 0.00 | 01-JAN-00:10 | 136245.33 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.05 | 0.00 | 01-JAN-00:10 | 26778.08 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.05 | 0.00 | 01-JAN-00:10 | 26778.08 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 729.53 | 0.00 | 01-JAN-00:10 | 136245.33 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 729.53 | 0.00 | 01-JAN-00:10 | 136245.33 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 81.84 | 0.00 | 01-JAN-00:10 | 12962.10 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.28 | 0.00 | 01-JAN-00:10 | 12962.10 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.28 | 0.00 | 01-JAN-00:10 | 12962.10 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.56 | 0.00 | 01-JAN-00:10 | 10951.03 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.56 | 0.00 | 01-JAN-00:10 | 10951.03 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.54 | 0.00 | 01-JAN-00:10 | 12288.46 | 03-MAY-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.41 | 0.00 | 01-JAN-00:10 | 10082.83 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.41 | 0.00 | 01-JAN-00:10 | 10082.83 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.14 | 0.00 | 01-JAN-00:10 | 12288.46 | 03-MAY-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.14 | 0.00 | 01-JAN-00:10 | 12288.46 | 03-MAY-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 114.92 | 0.00 | 01-JAN-00:10 | 18114.15 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.35 | 0.00 | 01-JAN-00:10 | 13231.71 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.35 | 0.00 | 01-JAN-00:10 | 13231.71 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.57 | 0.00 | 01-JAN-00:10 | 18114.15 | 06-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.57 | 0.00 | 01-JAN-00:10 | 18114.15 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 75.71 | 0.00 | 01-JAN-00:10 | 14402.58 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.93 | 0.00 | 01-JAN-00:10 | 8000.75 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.93 | 0.00 | 01-JAN-00:10 | 8000.75 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 74.78 | 0.00 | 01-JAN-00:10 | 14402.58 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 74.78 | 0.00 | 01-JAN-00:10 | 14402.58 | 30-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 74.69 | 0.00 | 01-JAN-00:10 | 8655.57 | 23-OCT-09:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.74 | 0.00 | 01-JAN-00:10 | 2964.94 | 31-DEC-10:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.74 | 0.00 | 01-JAN-00:10 | 2964.94 | 31-DEC-10:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 73.95 | 0.00 | 01-JAN-00:10 | 8655.57 | 23-OCT-09:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 73.95 | 0.00 | 01-JAN-00:10 | 8655.57 | 23-OCT-09:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 523.70 | 0.00 | 01-JAN-00:10 | 69985.07 | 03-MAY-12:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.32 | 0.00 | 01-JAN-00:10 | 25075.15 | 24-DEC-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.32 | 0.00 | 01-JAN-00:10 | 25075.15 | 24-DEC-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 513.37 | 0.00 | 01-JAN-00:10 | 69985.07 | 03-MAY-12:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 513.37 | 0.00 | 01-JAN-00:10 | 69985.07 | 03-MAY-12:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 93.30 | 0.00 | 01-JAN-00:10 | 21132.46 | 08-MAY-13:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.72 | 0.00 | 01-JAN-00:10 | 15918.58 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.72 | 0.00 | 01-JAN-00:10 | 15918.58 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 87.58 | 0.00 | 01-JAN-00:10 | 21132.46 | 08-MAY-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 87.58 | 0.00 | 01-JAN-00:10 | 21132.46 | 08-MAY-13:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.58 | 952.60 | 10-JAN-08:00 | 7989.48 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.58 | 952.60 | 10-JAN-08:00 | 7989.48 | 16-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.58 | 952.60 | 10-JAN-08:00 | 7989.48 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.42 | 1448.14 | 10-JAN-06:20 | 74843.34 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.42 | 1448.14 | 10-JAN-06:20 | 74843.34 | 16-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.42 | 1448.14 | 10-JAN-06:20 | 74843.34 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.03 | 3.43 | 09-JAN-21:50 | 7684.29 | 23-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.18 | 0.00 | 01-JAN-00:10 | 524.49 | 10-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.18 | 0.00 | 01-JAN-00:10 | 524.49 | 10-JAN-04:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 124.85 | 0.00 | 04-JAN-02:50 | 7684.29 | 23-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 124.85 | 0.00 | 04-JAN-02:50 | 7684.29 | 23-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.74 | 87805.49 | 22-JAN-06:00 | 369239.30 | 03-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.74 | 87805.49 | 22-JAN-06:00 | 369239.30 | 03-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.74 | 87805.49 | 22-JAN-06:00 | 369239.30 | 03-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 383.04 | 0.00 | 01-JAN-00:10 | 384146.15 | 06-FEB-06:10 |
PlantLoopHeatingDemand:Plant | 321.87 | 0.00 | 01-JAN-00:10 | 40642.48 | 24-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40642.48 | 24-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40642.48 | 24-JAN-12:10 |
EnergyTransfer:HVAC | 24900.50 | 10160.14 | 11-JAN-05:50 | 2612479.20 | 07-AUG-13:00 |
HeatingCoils:EnergyTransfer | 61.18 | 0.00 | 01-JAN-00:10 | 379229.26 | 06-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 61.18 | 0.00 | 01-JAN-00:10 | 379229.26 | 06-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 61.18 | 0.00 | 01-JAN-00:10 | 379229.26 | 06-FEB-06:10 |
CoolingCoils:EnergyTransfer | 22131.66 | 5414.70 | 11-JAN-07:10 | 2164922.47 | 07-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 18.50 | 0.00 | 01-JAN-00:10 | 180581.29 | 20-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 2689.18 | 0.00 | 01-JAN-00:10 | 689518.00 | 22-JUL-16:00 |
EnergyTransfer:Plant | 48457.60 | 0.00 | 01-JAN-00:10 | 5467494.07 | 26-MAY-15:00 |
LoopToLoop:EnergyTransfer | 15296.08 | 0.00 | 01-JAN-00:10 | 1676769.28 | 06-OCT-14:10 |
WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40642.48 | 24-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40642.48 | 24-JAN-12:10 |
Boilers:EnergyTransfer | 60.36 | 0.00 | 01-JAN-00:10 | 405708.31 | 06-FEB-05:20 |
Chillers:EnergyTransfer | 15293.77 | 0.00 | 01-JAN-00:10 | 1784506.26 | 10-MAY-16:00 |
HeatRejection:EnergyTransfer | 17485.52 | 0.00 | 01-JAN-00:10 | 2031682.67 | 10-MAY-16:00 |
General:HeatRejection:EnergyTransfer | 17485.52 | 0.00 | 01-JAN-00:10 | 2031682.67 | 10-MAY-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.130 | -641.143 | 0.000 | 0.000 | 92.699 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 3.878 | 0.000 | 0.000 | 0.000 | 0.000 | -0.011 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -667.126 | 0.000 | 0.000 | 83.505 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 189.795 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4875.360 | 0.000 | 0.000 | 842.106 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 95.011 | 0.000 | 0.000 | 0.000 | 0.000 | -0.016 |
CORE_TOP | 0.000 | 0.000 | 0.517 | -495.822 | 0.000 | 0.000 | 85.618 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 15.863 | 0.000 | 0.000 | 0.000 | 0.000 | -0.006 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -99.890 | 0.000 | 0.000 | 10.576 | 7.461 | 36.365 | 41.236 | 0.000 | 0.401 | 35.619 | 0.000 | -29.993 | 0.000 | -1.776 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -78.068 | 0.000 | 0.000 | 6.784 | 4.786 | 23.435 | 60.025 | 0.000 | 0.260 | 2.318 | 0.000 | -18.346 | 0.000 | -1.194 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -132.424 | 0.000 | 0.000 | 10.507 | 7.381 | 36.366 | 103.629 | 0.000 | 0.381 | 4.473 | 0.000 | -28.422 | 0.000 | -1.890 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -118.395 | 0.000 | 0.000 | 6.744 | 4.783 | 23.435 | 57.179 | 0.000 | 0.217 | 51.059 | 0.000 | -23.557 | 0.000 | -1.465 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 5.582 | -763.492 | 0.000 | 0.000 | 108.395 | 74.476 | 363.654 | 424.949 | 0.000 | 8.953 | 78.021 | 0.000 | -264.507 | 0.000 | -36.032 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.277 | -664.219 | 0.000 | 0.000 | 50.185 | 47.799 | 234.352 | 595.966 | 0.000 | 5.201 | 0.003 | 0.000 | -174.446 | 0.000 | -26.525 | -70.588 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.214 | -1128.588 | 0.000 | 0.000 | 105.623 | 73.744 | 363.660 | 1033.887 | 0.000 | 8.218 | 0.043 | 0.000 | -273.636 | 0.000 | -42.956 | -141.167 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.048 | -729.507 | 0.000 | 0.000 | 68.732 | 47.760 | 234.351 | 585.488 | 0.000 | 5.154 | 10.621 | 0.000 | -195.370 | 0.000 | -28.277 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.282 | -78.556 | 0.000 | 0.000 | 10.945 | 7.447 | 36.365 | 42.304 | 0.000 | 1.032 | 6.416 | 0.000 | -25.072 | 0.000 | -4.165 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.405 | -71.135 | 0.000 | 0.000 | 6.904 | 4.780 | 23.435 | 59.736 | 0.000 | 0.623 | 0.000 | 0.000 | -16.571 | 0.000 | -3.061 | -6.116 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.348 | -113.565 | 0.000 | 0.000 | 10.642 | 7.374 | 36.366 | 103.109 | 0.000 | 0.955 | 0.001 | 0.000 | -26.231 | 0.000 | -5.042 | -14.956 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.928 | -74.776 | 0.000 | 0.000 | 6.932 | 4.776 | 23.435 | 58.322 | 0.000 | 0.612 | 1.837 | 0.000 | -18.736 | 0.000 | -3.330 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.577 | 0.000 | 0.000 | 0.949 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.928 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1280.423 | 0.000 | 0.000 | 9.489 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -284.630 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.178 | -124.850 | 0.000 | 0.000 | 0.950 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -31.834 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7158.757 | 0.000 | 0.000 | 20.112 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -389.067 |
GROUNDFLOOR_PLENUM | 0.736 | -73.953 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.690 | 76.514 | 0.000 | 0.000 | 0.000 | -3.987 | 0.000 |
MIDFLOOR_PLENUM | 10.325 | -513.365 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.862 | 556.190 | 0.000 | 0.000 | 0.000 | -66.011 | 0.000 |
TOPFLOOR_PLENUM | 5.722 | -87.576 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.087 | 87.568 | 0.000 | 0.000 | 0.000 | -6.801 | -0.001 |
Total Facility | 16.783 | -674.894 | 21.911 | -19436.674 | 0.000 | 0.000 | 1538.395 | 1712.108 | 14676.396 | 3165.829 | 0.000 | 46.646 | 1215.231 | 0.000 | -1094.887 | 0.000 | -232.511 | -954.323 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-MAR-04:12 | 0.00 | 0.00 | 0.00 | -102199.42 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 88143.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-OCT-04:13 | 0.00 | 0.00 | 0.00 | -87349.75 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 80874.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 08-NOV-05:11 | 0.00 | 0.00 | 0.00 | -728985.65 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 664235.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 31-MAY-04:13 | 0.00 | 0.00 | 0.00 | -73315.61 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 66840.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-JUL-15:32 | 0.00 | 0.00 | 0.00 | -15188.97 | 0.00 | 0.00 | 42.97 | 30.32 | 720.18 | 5853.27 | 0.00 | 66.76 | 8475.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24-SEP-09:32 | 0.00 | 0.00 | 0.00 | -18969.61 | 0.00 | 0.00 | 22.55 | 19.54 | 464.11 | 12670.05 | 0.00 | 10.71 | 5782.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-JAN-13:31 | 0.00 | 0.00 | 0.00 | -22904.73 | 0.00 | 0.00 | 30.83 | 30.33 | 720.19 | 21889.98 | 0.00 | 0.00 | 284.69 | 0.00 | -0.00 | 0.00 | -51.30 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-DEC-15:01 | 0.00 | 0.00 | 0.00 | -24521.08 | 0.00 | 0.00 | 21.16 | 19.54 | 464.11 | 10422.50 | 0.00 | 0.00 | 13601.32 | 0.00 | -0.00 | 0.00 | -7.55 | 0.00 |
PERIMETER_MID_ZN_3 | 10-SEP-14:31 | 0.00 | 0.00 | 0.00 | -144445.80 | 0.00 | 0.00 | 427.14 | 303.25 | 7201.84 | 53352.37 | 0.00 | 2803.29 | 80357.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 03-SEP-08:52 | 0.00 | 0.00 | 0.00 | -201114.70 | 0.00 | 0.00 | 219.57 | 195.42 | 4641.14 | 141072.08 | 0.00 | 283.64 | 54702.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 10-DEC-13:51 | 0.00 | 0.00 | 0.00 | -222756.27 | 0.00 | 0.00 | 305.86 | 303.26 | 7201.95 | 208928.25 | 0.00 | 0.00 | 7183.54 | 0.00 | -0.00 | 0.00 | -1166.58 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:21 | 0.00 | 0.00 | 0.00 | -218973.48 | 0.00 | 0.00 | 0.00 | 195.42 | 3603.49 | 111482.61 | 0.00 | 1012.65 | 102679.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 10-SEP-14:31 | 0.00 | 0.00 | 0.00 | -17237.41 | 0.00 | 0.00 | 39.87 | 30.32 | 720.18 | 5131.84 | 0.00 | 322.22 | 10992.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-10:01 | 0.00 | 0.00 | 0.00 | -21184.17 | 0.00 | 0.00 | 20.13 | 19.54 | 464.11 | 10496.08 | 0.00 | 0.00 | 10185.55 | 0.00 | -0.00 | 0.00 | -1.24 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-14:01 | 0.00 | 0.00 | 0.00 | -24851.36 | 0.00 | 0.00 | 29.48 | 30.33 | 720.19 | 20614.96 | 0.00 | 0.00 | 3593.21 | 0.00 | -0.00 | 0.00 | -136.81 | 0.00 |
PERIMETER_TOP_ZN_4 | 03-SEP-15:31 | 0.00 | 0.00 | 0.00 | -23912.68 | 0.00 | 0.00 | 18.83 | 19.54 | 464.11 | 13891.72 | 0.00 | 162.22 | 9356.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:12 | 0.00 | 0.00 | 0.00 | -7989.44 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 186.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:12 | 0.00 | 0.00 | 0.00 | -74842.96 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3182.55 |
DATACENTER_TOP_ZN_6 | 23-APR-17:52 | 0.00 | 0.00 | 0.00 | -7684.29 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -118.26 |
DATACENTER_BASEMENT_ZN_6 | 09-AUG-21:14 | 0.00 | 0.00 | 0.00 | -370265.48 | 0.00 | 0.00 | 114.52 | 318.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9800.30 |
GROUNDFLOOR_PLENUM | 02-JAN-06:03 | 0.00 | -11431.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11477.49 | 0.00 | -0.00 | 0.00 | -46.28 | 0.00 |
MIDFLOOR_PLENUM | 25-SEP-05:02 | 0.00 | -81663.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82207.48 | 0.00 | -0.00 | 0.00 | -543.60 | 0.00 |
TOPFLOOR_PLENUM | 08-MAY-13:40 | 0.00 | -21131.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.13 | 20914.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-AUG-05:02 | 0.00 | -61664.79 | 0.00 | -1714285.07 | 0.00 | 0.00 | 16325.63 | 10223.35 | 616289.16 | 0.00 | 0.00 | 0.05 | 1170875.52 | 0.00 | -37753.60 | 0.00 | -10.24 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:01 | 0.00 | 0.00 | 24888.72 | 0.00 | 0.00 | 0.00 | 520.12 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39431.60 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-05:11 | 0.00 | 0.00 | 56949.36 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -63424.35 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-DEC-06:01 | 0.00 | 0.00 | 1969.51 | 0.00 | 0.00 | 0.00 | 90.46 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 975.87 | 0.00 | -3629.95 | 0.00 | -68.19 | 0.00 |
PERIMETER_BOT_ZN_1 | 06-FEB-06:04 | 0.00 | 0.00 | 231.56 | 0.00 | 0.00 | 0.00 | 138.94 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 3273.65 | 0.00 | -4618.86 | 0.00 | -53.03 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-05:11 | 0.00 | 0.00 | 110630.55 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40279.84 | 0.00 | -4435.35 | -74045.68 |
PERIMETER_MID_ZN_2 | 06-FEB-05:11 | 0.00 | 0.00 | 96424.40 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27782.50 | 0.00 | -3077.67 | -70803.72 |
PERIMETER_MID_ZN_1 | 21-JAN-06:02 | 0.00 | 0.00 | 116740.83 | 0.00 | 0.00 | 0.00 | 1462.99 | 1274.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52476.56 | 0.00 | -3493.07 | -73111.51 |
PERIMETER_MID_ZN_4 | 10-JAN-05:01 | 0.00 | 0.00 | 82828.85 | 0.00 | 0.00 | 0.00 | 0.00 | 821.46 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33185.16 | 0.00 | -5899.93 | -49369.86 |
PERIMETER_TOP_ZN_3 | 05-FEB-07:43 | 0.00 | 0.00 | 14465.58 | 0.00 | 0.00 | 0.00 | 88.55 | 51.84 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4495.42 | 0.00 | -2205.70 | -8625.04 |
PERIMETER_TOP_ZN_2 | 06-FEB-05:11 | 0.00 | 0.00 | 13397.98 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2215.84 | 0.00 | -317.81 | -11388.27 |
PERIMETER_TOP_ZN_1 | 06-FEB-05:11 | 0.00 | 0.00 | 17126.94 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3437.61 | 0.00 | -482.37 | -14020.01 |
PERIMETER_TOP_ZN_4 | 06-FEB-05:11 | 0.00 | 0.00 | 13091.30 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2406.89 | 0.00 | -333.16 | -10875.20 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 05-JAN-04:45 | 0.00 | 0.00 | 527.04 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2483.77 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:12 | 9386.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -784.26 | -8602.45 |
MIDFLOOR_PLENUM | 10-SEP-15:51 | 79571.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4871.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84442.96 |
TOPFLOOR_PLENUM | 06-FEB-06:13 | 17815.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -185.17 | -17630.62 |
Total Facility | 06-FEB-06:02 | -565912.05 | 550866.40 | 476315.66 | -550866.40 | 0.00 | 0.00 | 19725.81 | 10223.35 | 379706.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -174634.14 | 0.00 | -7044.46 | -138380.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.5659 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.4593 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 89.9514 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 78.1657 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.2824 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.6917 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0116 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0116 | 0.2395 | 1.0000 | Not calculated | 1.2002 | 0.2395 | ||
AIRLOOP DATACENTER BASEMENT | 21.2609 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2611 | 0.0159 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4610 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4610 | 0.0339 | 1.0000 | Not calculated | 0.0156 | 0.0339 | ||
AIRLOOP DATACENTER MID | 4.3952 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3952 | 0.0356 | 1.0000 | Not calculated | 0.1563 | 0.0356 | ||
AIRLOOP DATACENTER TOP | 0.4483 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4483 | 0.0349 | 1.0000 | Not calculated | 0.0156 | 0.0349 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.7829 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2848 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 44.9757 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8476 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.6412 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2829 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0116 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0116 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2395 | ||
AIRLOOP DATACENTER BASEMENT | 21.2609 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2609 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4610 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4610 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0339 | ||
AIRLOOP DATACENTER MID | 4.3952 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3952 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0356 | ||
AIRLOOP DATACENTER TOP | 0.4483 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4483 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0349 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0116 | 5.0116 | 5.0116 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2489 | 5.2489 | 1.6167 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 48.9813 | 48.9813 | 16.1638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8486 | 4.8486 | 1.6146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8937 | 0.8937 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0129 | 1.0129 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1233 | 1.1233 | 0.2033 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2869 | 1.2869 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4011 | 8.4011 | 2.0331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5650 | 10.5650 | 1.3101 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.7912 | 10.7912 | 2.0287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2128 | 11.2128 | 1.3119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9629 | 0.9629 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0733 | 1.0733 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1942 | 1.1942 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2033 | 1.2033 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4610 | 0.4610 | 0.4610 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3952 | 4.3952 | 4.3952 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4483 | 0.4483 | 0.4483 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2609 | 21.2609 | 21.2609 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.5659 | 8.4593 | 9.5659 | 2.2848 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 89.9514 | 78.1657 | 89.9514 | 22.8476 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.2824 | 8.6917 | 9.2824 | 2.2829 | 0.0000 | 1.0000 |
CAV_BAS | 5.0116 | 5.0116 | 5.0116 | 5.0116 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2609 | 21.2611 | 21.2609 | 21.2609 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4610 | 0.4610 | 0.4610 | 0.4610 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3952 | 4.3952 | 4.3952 | 4.3952 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4483 | 0.4483 | 0.4483 | 0.4483 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0116 | 5.0116 | 5.0116 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6245 | 2.6245 | 1.6167 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.4906 | 24.4906 | 16.1638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4243 | 2.4243 | 1.6146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4469 | 0.4469 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5065 | 0.5065 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5617 | 0.5617 | 0.2033 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6435 | 0.6435 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2005 | 4.2005 | 2.0331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2825 | 5.2825 | 1.3101 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3956 | 5.3956 | 2.0287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6064 | 5.6064 | 1.3119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4815 | 0.4815 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5367 | 0.5367 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5971 | 0.5971 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6016 | 0.6016 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4610 | 0.4610 | 0.4610 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3952 | 4.3952 | 4.3952 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4483 | 0.4483 | 0.4483 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2609 | 21.2609 | 21.2609 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.7829 | 2.2848 | 2.2848 | 2.2848 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 44.9757 | 22.8476 | 22.8476 | 22.8476 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.6412 | 2.2829 | 2.2829 | 2.2829 | 0.0000 | 1.0000 |
CAV_BAS | 5.0116 | 5.0116 | 5.0116 | 5.0116 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2609 | 21.2609 | 21.2609 | 21.2609 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4610 | 0.4610 | 0.4610 | 0.4610 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3952 | 4.3952 | 4.3952 | 4.3952 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4483 | 0.4483 | 0.4483 | 0.4483 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 1.83 |
Number of hours cooling loads not met | 800.83 |
Number of hours not met | 802.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 67.00 | 463207.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4290.25 | 395912.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1712.11 | 164275.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 264.34 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3369.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2028.07 | 255581.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 645.91 | 57493.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1551.85 | 81663.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 338.60 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 50.61 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 644.88 | 74963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26761.82 |
Natural Gas | 0.00 | 711.88 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27473.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 566.52 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 36.96 |
Space Heating | 0.00 |
Space Cooling | 92.62 |
Fans (All) | 43.78 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 577.75 |
Subtotal | 577.75 |
Natural Gas [MJ/m2] | |
Space Heating | 1.45 |
Service Water Heating | 13.92 |
Miscellaneous (All) | 15.37 |
Subtotal | 15.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.23 |
Space Heating | 0.24 |
Space Cooling | 15.62 |
Fans (All) | 7.38 |
Service Water Heating | 2.35 |
Receptacle Equipment | 53.42 |
Miscellaneous | 14.76 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 970. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7575.00 | 1185.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8601.17 | 158.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8583.17 | 176.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7375.83 | 1384.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8698.50 | 61.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8443.00 | 317.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8463.83 | 296.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7977.50 | 782.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8595.33 | 164.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8334.50 | 425.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8368.83 | 391.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7904.33 | 855.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 3575.17 | 5184.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 3647.17 | 5112.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 3600.17 | 5159.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 2183.83 | 6576.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8496.33 | 263.67 | 0.00 | 0.00 | 0.00 |
Min | 2183.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 6576.17 | 0.00 | 0.00 | 0.00 |
Average | 7518.71 | 1241.29 | 0.00 | 0.00 | 0.00 |
Sum | 172930.33 | 28549.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 365089.17 | 3526.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330771.00 | 42.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 544.00 | 1724.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 539.50 | 1728.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 531.00 | 1737.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 25094.50 | 78300.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365089.17 | 78300.50 | 0.00 | 0.00 | 0.00 |
Average | 76549.75 | 3785.17 | 0.00 | 0.00 | 0.00 |
Sum | 1760644.17 | 87058.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3721.17 | 5038.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8515.50 | 244.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8010.50 | 749.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7927.50 | 832.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7811.00 | 949.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6339.33 | 2420.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6962.33 | 1797.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6780.83 | 1979.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6709.33 | 2050.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6559.00 | 2201.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6857.17 | 1902.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6719.00 | 2041.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6639.83 | 2120.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6532.50 | 2227.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5782.83 | 2977.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5767.17 | 2992.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5735.83 | 3024.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 4404.33 | 4355.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8493.33 | 266.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7832.17 | 927.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7350.67 | 1409.33 | 0.00 | 0.00 | 0.00 |
Min | 3721.17 | 4.50 | 0.00 | 0.00 | 0.00 |
Max | 8755.50 | 5038.83 | 0.00 | 0.00 | 0.00 |
Average | 6910.85 | 1849.15 | 0.00 | 0.00 | 0.00 |
Sum | 158949.50 | 42530.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 244406.00 | 124210.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330484.00 | 329.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330786.00 | 27.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330744.00 | 69.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38901.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18332.00 | 22.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38903.67 | 21.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24892.83 | 16.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38894.33 | 30.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24879.83 | 29.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38896.50 | 28.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24884.83 | 24.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 744.50 | 1523.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 732.67 | 1535.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 719.33 | 1548.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 30859.17 | 72535.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330786.00 | 124210.00 | 0.00 | 0.00 | 0.00 |
Average | 71553.41 | 8781.50 | 0.00 | 0.00 | 0.00 |
Sum | 1645728.50 | 201974.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:55
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510023E+11 | 100389.24 | 09-JAN-05:11 | 7.67 | 5.62 | 0.566603E+10 | 7499.38 | 12-JAN-10:09 | 18.17 | 17.41 |
February | 0.445611E+11 | 101761.78 | 13-FEB-05:11 | 5.53 | 1.73 | 0.513857E+10 | 7499.16 | 09-FEB-14:20 | 5.53 | 1.73 |
March | 0.514577E+11 | 102273.27 | 20-MAR-04:12 | 12.27 | 8.01 | 0.613158E+10 | 7499.55 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.475629E+11 | 101596.78 | 17-APR-04:11 | 12.83 | 10.47 | 0.544749E+10 | 7499.32 | 13-APR-09:20 | 12.83 | 10.47 |
May | 0.513999E+11 | 74422.79 | 29-MAY-18:50 | 28.48 | 23.49 | 0.590069E+10 | 7502.27 | 08-MAY-09:20 | 28.48 | 23.49 |
June | 0.513594E+11 | 76867.29 | 12-JUN-03:02 | 23.90 | 21.55 | 0.587992E+10 | 7498.98 | 23-JUN-09:20 | 29.80 | 25.86 |
July | 0.534806E+11 | 73797.60 | 25-JUL-03:02 | 25.10 | 23.49 | 0.547173E+10 | 7498.97 | 14-JUL-09:20 | 25.10 | 23.49 |
August | 0.627445E+11 | 78181.38 | 28-AUG-03:02 | 26.27 | 23.76 | 0.613838E+10 | 7543.13 | 07-AUG-09:09 | 26.27 | 23.76 |
September | 0.559182E+11 | 76867.75 | 05-SEP-04:23 | 22.75 | 22.75 | 0.545323E+10 | 7508.81 | 05-SEP-09:30 | 27.15 | 25.12 |
October | 0.590223E+11 | 97383.83 | 17-OCT-04:12 | 17.33 | 12.72 | 0.567205E+10 | 7691.40 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.572719E+11 | 98018.34 | 14-NOV-05:12 | 15.50 | 12.19 | 0.561605E+10 | 7545.06 | 06-NOV-10:00 | 15.50 | 12.19 |
December | 0.553592E+11 | 100547.99 | 26-DEC-05:12 | 6.97 | 3.20 | 0.547244E+10 | 7499.61 | 08-DEC-10:00 | 6.97 | 3.20 |
Annual Sum or Average | 0.641140E+12 | 0.679881E+11 | ||||||||
Minimum of Months | 0.445611E+11 | 73797.60 | 5.53 | 1.73 | 0.513857E+10 | 7498.97 | 5.53 | 1.73 | ||
Maximum of Months | 0.627445E+11 | 102273.27 | 28.48 | 23.76 | 0.613838E+10 | 7691.40 | 29.80 | 25.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430957E+11 | 84197.76 | 02-JAN-05:14 | 16.67 | 15.63 | 0.505357E+10 | 6734.83 | 11-JAN-10:09 | 14.67 | 12.06 |
February | 0.414654E+11 | 86975.84 | 27-FEB-05:13 | 17.77 | 17.77 | 0.459398E+10 | 6734.72 | 07-FEB-10:20 | 17.77 | 17.77 |
March | 0.523219E+11 | 82946.94 | 30-MAR-04:13 | 20.83 | 19.79 | 0.549235E+10 | 6734.96 | 23-MAR-09:09 | 20.83 | 19.79 |
April | 0.584344E+11 | 82662.20 | 04-APR-04:13 | 16.67 | 14.88 | 0.487526E+10 | 6734.84 | 10-APR-13:00 | 20.50 | 10.92 |
May | 0.547623E+11 | 81174.35 | 16-MAY-04:13 | 23.30 | 22.20 | 0.528101E+10 | 6734.91 | 02-MAY-13:09 | 23.30 | 22.20 |
June | 0.600887E+11 | 84051.95 | 01-JUN-04:13 | 21.50 | 20.44 | 0.526226E+10 | 6734.69 | 02-JUN-09:39 | 29.03 | 24.19 |
July | 0.654121E+11 | 73687.97 | 24-JUL-05:03 | 27.02 | 24.85 | 0.488697E+10 | 6734.61 | 24-JUL-09:20 | 30.37 | 25.95 |
August | 0.726654E+11 | 75624.07 | 07-AUG-05:03 | 24.17 | 23.42 | 0.548943E+10 | 6734.83 | 15-AUG-09:20 | 26.10 | 22.41 |
September | 0.539228E+11 | 83872.84 | 22-SEP-04:13 | 21.70 | 20.03 | 0.487610E+10 | 6734.69 | 22-SEP-13:00 | 30.00 | 22.00 |
October | 0.583462E+11 | 87354.71 | 02-OCT-04:13 | 18.03 | 15.02 | 0.507251E+10 | 6780.52 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.532584E+11 | 86186.58 | 13-NOV-05:11 | 9.93 | 8.14 | 0.502534E+10 | 6734.78 | 13-NOV-10:20 | 16.83 | 13.24 |
December | 0.533520E+11 | 85415.91 | 26-DEC-05:12 | 6.97 | 3.20 | 0.489480E+10 | 6734.80 | 14-DEC-14:50 | 6.97 | 3.20 |
Annual Sum or Average | 0.667125E+12 | 0.608036E+11 | ||||||||
Minimum of Months | 0.414654E+11 | 73687.97 | 6.97 | 3.20 | 0.459398E+10 | 6734.61 | 6.97 | 3.20 | ||
Maximum of Months | 0.726654E+11 | 87354.71 | 27.02 | 24.85 | 0.549235E+10 | 6780.52 | 30.37 | 25.95 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324436E+11 | 71078.18 | 02-JAN-05:12 | 16.67 | 15.63 | 0.488542E+10 | 6734.80 | 05-JAN-14:20 | 14.33 | 9.84 |
February | 0.302851E+11 | 72117.45 | 27-FEB-06:04 | 17.70 | 17.70 | 0.447224E+10 | 6734.67 | 14-FEB-14:20 | 17.70 | 17.70 |
March | 0.370245E+11 | 71138.87 | 29-MAR-05:02 | 17.10 | 16.79 | 0.539349E+10 | 6734.85 | 23-MAR-09:39 | 17.10 | 16.79 |
April | 0.385160E+11 | 71652.15 | 14-APR-05:04 | 18.80 | 18.80 | 0.484400E+10 | 6734.77 | 03-APR-09:20 | 18.80 | 18.80 |
May | 0.467854E+11 | 70176.17 | 17-MAY-04:12 | 22.20 | 20.38 | 0.526185E+10 | 6734.99 | 02-MAY-13:09 | 22.20 | 20.38 |
June | 0.469736E+11 | 72613.14 | 07-JUN-04:12 | 21.10 | 18.59 | 0.524500E+10 | 6734.64 | 13-JUN-13:20 | 33.17 | 21.40 |
July | 0.472117E+11 | 69603.24 | 12-JUL-04:12 | 23.50 | 23.01 | 0.486818E+10 | 6734.63 | 12-JUL-13:20 | 25.03 | 23.05 |
August | 0.487305E+11 | 71846.21 | 17-AUG-04:12 | 21.93 | 21.62 | 0.547414E+10 | 6734.71 | 15-AUG-09:20 | 21.93 | 21.62 |
September | 0.444175E+11 | 71237.92 | 28-SEP-04:12 | 22.20 | 20.76 | 0.485210E+10 | 6734.70 | 22-SEP-13:00 | 22.20 | 20.76 |
October | 0.440336E+11 | 72628.96 | 17-OCT-04:12 | 17.33 | 12.72 | 0.504822E+10 | 6734.96 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.371631E+11 | 72900.24 | 08-NOV-05:11 | 19.80 | 19.09 | 0.497486E+10 | 6735.06 | 27-NOV-14:09 | 25.82 | 17.52 |
December | 0.339522E+11 | 71060.55 | 14-DEC-05:12 | 20.00 | 20.00 | 0.477839E+10 | 6734.75 | 15-DEC-14:09 | 29.00 | 22.01 |
Annual Sum or Average | 0.487537E+12 | 0.600979E+11 | ||||||||
Minimum of Months | 0.302851E+11 | 69603.24 | 16.67 | 12.72 | 0.447224E+10 | 6734.63 | 14.33 | 9.84 | ||
Maximum of Months | 0.487305E+11 | 72900.24 | 23.50 | 23.01 | 0.547414E+10 | 6735.06 | 33.17 | 23.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278935E+11 | 68060.47 | 02-JAN-06:03 | 16.00 | 15.39 | 0.447474E+10 | 6734.62 | 20-JAN-10:20 | 14.67 | 14.08 |
February | 0.278380E+11 | 67175.00 | 03-FEB-06:02 | 18.90 | 18.50 | 0.422506E+10 | 6734.63 | 03-FEB-10:20 | 14.80 | 13.72 |
March | 0.343515E+11 | 70037.88 | 27-MAR-04:12 | 19.97 | 18.72 | 0.516035E+10 | 6734.62 | 29-MAR-09:20 | 21.63 | 19.76 |
April | 0.386155E+11 | 71987.21 | 26-APR-05:04 | 21.00 | 20.56 | 0.480483E+10 | 6734.69 | 27-APR-13:00 | 28.80 | 22.60 |
May | 0.514586E+11 | 73320.11 | 31-MAY-04:13 | 23.17 | 21.09 | 0.527195E+10 | 6831.36 | 08-MAY-13:50 | 23.17 | 21.09 |
June | 0.527005E+11 | 71597.80 | 07-JUN-04:12 | 21.10 | 18.59 | 0.525765E+10 | 6734.66 | 06-JUN-13:50 | 21.10 | 18.59 |
July | 0.528277E+11 | 70927.33 | 12-JUL-04:12 | 23.50 | 23.01 | 0.488287E+10 | 6734.61 | 13-JUL-09:20 | 24.63 | 23.37 |
August | 0.538400E+11 | 70329.09 | 26-AUG-04:02 | 23.85 | 23.13 | 0.548458E+10 | 6734.67 | 15-AUG-09:20 | 23.85 | 23.13 |
September | 0.472555E+11 | 72365.21 | 28-SEP-05:04 | 22.28 | 21.10 | 0.485769E+10 | 6734.68 | 22-SEP-13:00 | 22.28 | 21.10 |
October | 0.455150E+11 | 71072.37 | 02-OCT-04:11 | 18.03 | 15.02 | 0.502867E+10 | 6734.96 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.338955E+11 | 69603.10 | 03-NOV-04:12 | 22.50 | 22.14 | 0.481229E+10 | 6734.70 | 06-NOV-10:20 | 24.37 | 20.12 |
December | 0.296327E+11 | 67472.98 | 15-DEC-06:03 | 21.00 | 21.00 | 0.442967E+10 | 6734.73 | 15-DEC-14:09 | 29.00 | 22.01 |
Annual Sum or Average | 0.495824E+12 | 0.586903E+11 | ||||||||
Minimum of Months | 0.278380E+11 | 67175.00 | 16.00 | 15.02 | 0.422506E+10 | 6734.61 | 14.67 | 13.72 | ||
Maximum of Months | 0.538400E+11 | 73320.11 | 23.85 | 23.13 | 0.548458E+10 | 6831.36 | 29.00 | 23.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438395E+10 | 8168.35 | 02-JAN-06:03 | 16.00 | 15.39 | 0.595705E+09 | 845.61 | 27-JAN-14:20 | 19.33 | 12.72 |
February | 0.456822E+10 | 7277.06 | 27-FEB-05:11 | 17.77 | 17.77 | 0.558250E+09 | 845.62 | 28-FEB-14:09 | 25.00 | 20.38 |
March | 0.611022E+10 | 8959.58 | 27-MAR-05:03 | 19.82 | 18.59 | 0.675363E+09 | 845.62 | 24-MAR-09:20 | 19.82 | 18.59 |
April | 0.827059E+10 | 8901.00 | 26-APR-14:30 | 28.00 | 22.41 | 0.610406E+09 | 845.65 | 27-APR-13:00 | 28.80 | 22.60 |
May | 0.101105E+11 | 13839.86 | 07-MAY-14:42 | 32.98 | 23.21 | 0.664592E+09 | 857.39 | 08-MAY-13:50 | 32.70 | 22.56 |
June | 0.115666E+11 | 11852.75 | 01-JUN-04:12 | 21.50 | 20.44 | 0.662247E+09 | 845.63 | 02-JUN-09:39 | 29.03 | 24.19 |
July | 0.121249E+11 | 15188.76 | 02-JUL-15:32 | 29.07 | 24.97 | 0.615716E+09 | 845.61 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.128887E+11 | 13978.52 | 13-AUG-16:22 | 30.50 | 26.21 | 0.690551E+09 | 845.64 | 15-AUG-09:20 | 26.10 | 22.41 |
September | 0.905055E+10 | 11970.26 | 06-SEP-03:02 | 24.70 | 23.43 | 0.613512E+09 | 845.63 | 28-SEP-13:39 | 28.80 | 23.39 |
October | 0.897254E+10 | 14901.05 | 08-OCT-13:01 | 32.17 | 26.14 | 0.636301E+09 | 852.30 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.626031E+10 | 10947.35 | 02-NOV-05:02 | 23.38 | 22.55 | 0.624880E+09 | 845.63 | 13-NOV-10:20 | 16.83 | 13.24 |
December | 0.558392E+10 | 7328.47 | 11-DEC-13:30 | 26.00 | 22.83 | 0.595664E+09 | 845.64 | 14-DEC-14:50 | 27.83 | 23.02 |
Annual Sum or Average | 0.998910E+11 | 0.754319E+10 | ||||||||
Minimum of Months | 0.438395E+10 | 7277.06 | 16.00 | 15.39 | 0.558250E+09 | 845.61 | 16.83 | 12.72 | ||
Maximum of Months | 0.128887E+11 | 15188.76 | 32.98 | 26.21 | 0.690551E+09 | 857.39 | 32.70 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352042E+10 | 16181.85 | 01-JAN-10:52 | 22.00 | 17.44 | 0.400380E+09 | 544.96 | 11-JAN-10:09 | 14.67 | 12.06 |
February | 0.378282E+10 | 11893.63 | 26-FEB-11:13 | 25.37 | 20.01 | 0.367075E+09 | 544.96 | 09-FEB-10:00 | 25.37 | 20.01 |
March | 0.526355E+10 | 17576.05 | 26-MAR-09:32 | 24.77 | 20.03 | 0.438103E+09 | 544.97 | 23-MAR-09:09 | 24.77 | 20.03 |
April | 0.673098E+10 | 17524.62 | 23-APR-07:53 | 22.20 | 19.24 | 0.393544E+09 | 544.97 | 03-APR-09:09 | 22.20 | 19.24 |
May | 0.844666E+10 | 18963.41 | 14-MAY-08:42 | 27.93 | 23.47 | 0.428722E+09 | 545.00 | 02-MAY-13:09 | 27.93 | 23.47 |
June | 0.898236E+10 | 17436.51 | 04-JUN-09:22 | 28.90 | 24.82 | 0.426979E+09 | 544.97 | 02-JUN-09:39 | 28.90 | 24.82 |
July | 0.909243E+10 | 17601.14 | 09-JUL-09:02 | 30.68 | 26.13 | 0.397035E+09 | 544.94 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.920673E+10 | 16092.80 | 06-AUG-09:42 | 29.83 | 26.91 | 0.445001E+09 | 544.97 | 15-AUG-09:20 | 26.10 | 22.41 |
September | 0.706659E+10 | 18968.24 | 24-SEP-09:32 | 29.03 | 25.00 | 0.395804E+09 | 544.96 | 21-SEP-13:50 | 29.03 | 25.00 |
October | 0.710177E+10 | 17718.60 | 15-OCT-08:43 | 23.00 | 19.57 | 0.410613E+09 | 550.32 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.491142E+10 | 17395.89 | 11-NOV-09:23 | 24.40 | 21.68 | 0.404558E+09 | 544.98 | 06-NOV-10:00 | 24.40 | 21.68 |
December | 0.396353E+10 | 14330.37 | 10-DEC-10:22 | 25.00 | 20.24 | 0.385431E+09 | 544.96 | 14-DEC-14:50 | 27.83 | 23.02 |
Annual Sum or Average | 0.780693E+11 | 0.489324E+10 | ||||||||
Minimum of Months | 0.352042E+10 | 11893.63 | 22.00 | 17.44 | 0.367075E+09 | 544.94 | 14.67 | 12.06 | ||
Maximum of Months | 0.920673E+10 | 18968.24 | 30.68 | 26.91 | 0.445001E+09 | 550.32 | 29.03 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.918409E+10 | 22906.72 | 01-JAN-13:31 | 25.67 | 18.12 | 0.625544E+09 | 892.85 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.877568E+10 | 21347.51 | 26-FEB-13:52 | 26.60 | 19.72 | 0.571256E+09 | 899.94 | 27-FEB-14:09 | 25.60 | 20.00 |
March | 0.883988E+10 | 20079.33 | 05-MAR-13:23 | 27.70 | 18.32 | 0.677026E+09 | 845.68 | 23-MAR-09:09 | 16.78 | 14.63 |
April | 0.977160E+10 | 14629.76 | 23-APR-12:33 | 27.20 | 20.85 | 0.610476E+09 | 845.69 | 27-APR-13:00 | 28.80 | 22.60 |
May | 0.103271E+11 | 18741.38 | 07-MAY-14:42 | 32.98 | 23.21 | 0.664609E+09 | 850.01 | 08-MAY-13:50 | 32.70 | 22.56 |
June | 0.111878E+11 | 13924.72 | 26-JUN-05:02 | 25.00 | 23.50 | 0.662127E+09 | 845.65 | 02-JUN-09:39 | 25.00 | 23.50 |
July | 0.120374E+11 | 18904.83 | 02-JUL-15:32 | 29.07 | 24.97 | 0.615701E+09 | 845.63 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.140327E+11 | 19040.09 | 27-AUG-12:23 | 32.00 | 23.77 | 0.690791E+09 | 845.65 | 15-AUG-09:20 | 32.00 | 23.77 |
September | 0.112016E+11 | 20106.27 | 03-SEP-13:02 | 31.28 | 23.99 | 0.614252E+09 | 845.66 | 21-SEP-13:50 | 26.78 | 22.76 |
October | 0.139340E+11 | 21499.87 | 15-OCT-13:22 | 29.50 | 22.51 | 0.639542E+09 | 886.69 | 03-OCT-13:50 | 29.50 | 22.51 |
November | 0.119777E+11 | 22188.74 | 11-NOV-13:21 | 26.35 | 22.79 | 0.633139E+09 | 922.46 | 06-NOV-14:09 | 26.35 | 22.79 |
December | 0.111555E+11 | 22407.76 | 10-DEC-12:21 | 27.00 | 20.56 | 0.608348E+09 | 916.69 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.132425E+12 | 0.761281E+10 | ||||||||
Minimum of Months | 0.877568E+10 | 13924.72 | 25.00 | 18.12 | 0.571256E+09 | 845.63 | 16.78 | 14.63 | ||
Maximum of Months | 0.140327E+11 | 22906.72 | 32.98 | 24.97 | 0.690791E+09 | 922.46 | 32.70 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495244E+10 | 23457.23 | 01-JAN-15:31 | 25.00 | 18.55 | 0.403478E+09 | 544.96 | 05-JAN-14:50 | 14.83 | 10.49 |
February | 0.605585E+10 | 22725.05 | 26-FEB-15:12 | 25.90 | 20.05 | 0.371548E+09 | 544.97 | 28-FEB-14:09 | 25.00 | 20.38 |
March | 0.852925E+10 | 21167.69 | 26-MAR-15:32 | 25.33 | 20.03 | 0.445376E+09 | 544.97 | 23-MAR-09:09 | 25.33 | 20.03 |
April | 0.117870E+11 | 23485.85 | 23-APR-16:32 | 27.37 | 21.80 | 0.396559E+09 | 545.00 | 27-APR-13:00 | 28.80 | 22.60 |
May | 0.994680E+10 | 23471.22 | 28-MAY-16:31 | 32.03 | 24.85 | 0.429259E+09 | 545.00 | 08-MAY-13:50 | 32.03 | 24.85 |
June | 0.119351E+11 | 23512.99 | 04-JUN-16:02 | 29.50 | 24.64 | 0.427914E+09 | 544.97 | 02-JUN-09:39 | 29.50 | 24.64 |
July | 0.130435E+11 | 23627.09 | 30-JUL-16:52 | 27.20 | 24.74 | 0.398220E+09 | 544.94 | 14-JUL-13:20 | 27.20 | 24.74 |
August | 0.156917E+11 | 22793.51 | 06-AUG-16:22 | 25.00 | 22.52 | 0.446504E+09 | 544.97 | 15-AUG-09:20 | 26.10 | 22.41 |
September | 0.921654E+10 | 24307.61 | 24-SEP-16:11 | 30.13 | 25.90 | 0.396455E+09 | 544.96 | 21-SEP-13:50 | 30.13 | 25.90 |
October | 0.103700E+11 | 22925.95 | 08-OCT-15:41 | 31.00 | 25.31 | 0.412314E+09 | 550.37 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.849376E+10 | 23528.68 | 05-NOV-14:52 | 27.20 | 20.06 | 0.407933E+09 | 544.97 | 06-NOV-10:00 | 25.50 | 20.23 |
December | 0.837407E+10 | 24523.34 | 10-DEC-15:01 | 27.83 | 20.05 | 0.397479E+09 | 545.00 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.118396E+12 | 0.493304E+10 | ||||||||
Minimum of Months | 0.495244E+10 | 21167.69 | 25.00 | 18.55 | 0.371548E+09 | 544.94 | 14.83 | 10.49 | ||
Maximum of Months | 0.156917E+11 | 24523.34 | 32.03 | 25.90 | 0.446504E+09 | 550.37 | 32.03 | 25.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288310E+10 | 4908.68 | 02-JAN-13:30 | 26.00 | 18.64 | 0.536347E+09 | 845.61 | 02-JAN-14:20 | 26.33 | 18.48 |
February | 0.316136E+10 | 5193.86 | 28-FEB-15:00 | 25.00 | 20.38 | 0.513454E+09 | 845.60 | 27-FEB-10:20 | 25.00 | 20.38 |
March | 0.415596E+10 | 6738.93 | 30-MAR-13:30 | 28.55 | 22.55 | 0.627796E+09 | 845.62 | 24-MAR-13:20 | 28.55 | 22.55 |
April | 0.549160E+10 | 8633.09 | 29-APR-05:03 | 23.20 | 21.68 | 0.598390E+09 | 845.62 | 12-APR-13:20 | 23.20 | 21.68 |
May | 0.905657E+10 | 11275.05 | 30-MAY-05:02 | 25.50 | 24.21 | 0.664271E+09 | 845.68 | 02-MAY-13:09 | 25.50 | 24.21 |
June | 0.985411E+10 | 14326.72 | 11-JUN-17:21 | 32.75 | 21.65 | 0.662320E+09 | 845.61 | 13-JUN-13:20 | 33.17 | 21.40 |
July | 0.973111E+10 | 14116.80 | 04-JUL-16:42 | 30.68 | 26.02 | 0.616040E+09 | 845.61 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.960643E+10 | 12963.88 | 21-AUG-03:02 | 26.27 | 23.88 | 0.690797E+09 | 845.61 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.772593E+10 | 14442.94 | 10-SEP-14:31 | 35.67 | 27.27 | 0.612395E+09 | 845.61 | 22-SEP-13:00 | 30.00 | 22.00 |
October | 0.700295E+10 | 9930.41 | 10-OCT-04:11 | 22.00 | 19.99 | 0.630475E+09 | 845.66 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.432752E+10 | 9699.76 | 03-NOV-05:02 | 22.28 | 21.91 | 0.593729E+09 | 845.62 | 17-NOV-14:20 | 23.10 | 14.77 |
December | 0.335475E+10 | 5619.61 | 15-DEC-14:05 | 29.00 | 22.01 | 0.533889E+09 | 845.62 | 15-DEC-14:09 | 29.00 | 22.01 |
Annual Sum or Average | 0.763514E+11 | 0.727990E+10 | ||||||||
Minimum of Months | 0.288310E+10 | 4908.68 | 22.00 | 18.64 | 0.513454E+09 | 845.60 | 23.10 | 14.77 | ||
Maximum of Months | 0.985411E+10 | 14442.94 | 35.67 | 27.27 | 0.690797E+09 | 845.68 | 33.17 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224378E+10 | 8515.06 | 19-JAN-11:05 | 24.92 | 21.49 | 0.281325E+09 | 548.49 | 24-JAN-13:09 | 17.00 | 10.00 |
February | 0.272143E+10 | 9231.37 | 27-FEB-11:05 | 22.80 | 19.34 | 0.261939E+09 | 548.50 | 09-FEB-11:09 | 22.80 | 19.34 |
March | 0.401961E+10 | 17836.15 | 26-MAR-10:13 | 26.07 | 20.20 | 0.314505E+09 | 548.52 | 15-MAR-12:09 | 26.07 | 20.20 |
April | 0.552332E+10 | 18533.61 | 23-APR-09:32 | 25.53 | 20.92 | 0.289451E+09 | 548.51 | 10-APR-14:09 | 25.53 | 20.92 |
May | 0.812307E+10 | 20106.58 | 14-MAY-09:22 | 28.60 | 23.59 | 0.316789E+09 | 548.48 | 03-MAY-12:09 | 28.60 | 23.59 |
June | 0.845312E+10 | 18828.40 | 11-JUN-08:62 | 25.47 | 21.10 | 0.315302E+09 | 548.49 | 08-JUN-14:09 | 25.47 | 21.10 |
July | 0.831720E+10 | 18585.88 | 23-JUL-09:42 | 30.82 | 26.39 | 0.294417E+09 | 548.49 | 05-JUL-12:09 | 30.82 | 26.39 |
August | 0.809374E+10 | 18309.57 | 06-AUG-08:32 | 28.67 | 26.43 | 0.328767E+09 | 548.48 | 30-AUG-12:09 | 31.18 | 24.70 |
September | 0.652789E+10 | 20105.30 | 03-SEP-08:52 | 29.90 | 24.25 | 0.292448E+09 | 548.48 | 01-SEP-10:09 | 29.90 | 24.25 |
October | 0.619988E+10 | 19702.04 | 09-OCT-09:12 | 27.73 | 22.40 | 0.302334E+09 | 548.51 | 17-OCT-12:09 | 21.17 | 14.63 |
November | 0.371824E+10 | 15424.61 | 11-NOV-10:52 | 26.10 | 21.82 | 0.294739E+09 | 548.49 | 13-NOV-11:09 | 18.77 | 14.38 |
December | 0.248238E+10 | 10207.59 | 10-DEC-11:12 | 26.33 | 20.64 | 0.271204E+09 | 548.49 | 01-DEC-11:09 | 26.33 | 20.64 |
Annual Sum or Average | 0.664237E+11 | 0.356322E+10 | ||||||||
Minimum of Months | 0.224378E+10 | 8515.06 | 22.80 | 19.34 | 0.261939E+09 | 548.48 | 17.00 | 10.00 | ||
Maximum of Months | 0.845312E+10 | 20106.58 | 30.82 | 26.43 | 0.328767E+09 | 548.52 | 31.18 | 26.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.842714E+10 | 20323.28 | 01-JAN-13:42 | 25.83 | 18.00 | 0.616634E+09 | 927.44 | 19-JAN-14:39 | 25.00 | 21.54 |
February | 0.784745E+10 | 19568.68 | 26-FEB-11:32 | 25.73 | 19.91 | 0.562848E+09 | 912.43 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.716647E+10 | 19280.86 | 05-MAR-13:53 | 27.70 | 18.31 | 0.659938E+09 | 845.67 | 24-MAR-13:30 | 24.40 | 16.03 |
April | 0.726048E+10 | 12629.96 | 23-APR-13:33 | 27.53 | 21.02 | 0.603926E+09 | 845.67 | 10-APR-13:00 | 27.53 | 21.02 |
May | 0.931773E+10 | 13108.03 | 03-MAY-04:12 | 23.13 | 21.53 | 0.664311E+09 | 845.72 | 02-MAY-13:09 | 23.13 | 21.53 |
June | 0.943405E+10 | 13785.27 | 26-JUN-05:02 | 25.00 | 23.50 | 0.662090E+09 | 845.63 | 13-JUN-13:20 | 25.00 | 23.50 |
July | 0.964969E+10 | 17241.91 | 09-JUL-14:12 | 29.07 | 25.40 | 0.615930E+09 | 845.62 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.108875E+11 | 16842.12 | 06-AUG-12:32 | 31.00 | 25.63 | 0.691132E+09 | 845.63 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.102406E+11 | 20133.70 | 10-SEP-14:31 | 35.67 | 27.27 | 0.613750E+09 | 845.64 | 21-SEP-13:50 | 26.78 | 22.76 |
October | 0.125704E+11 | 20776.04 | 01-OCT-13:42 | 27.87 | 18.52 | 0.639780E+09 | 908.05 | 13-OCT-13:50 | 32.87 | 23.24 |
November | 0.107024E+11 | 21812.98 | 11-NOV-13:31 | 26.27 | 22.81 | 0.631069E+09 | 954.74 | 06-NOV-14:09 | 26.27 | 22.81 |
December | 0.935755E+10 | 22277.23 | 10-DEC-13:51 | 27.00 | 20.22 | 0.596008E+09 | 927.07 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.112861E+12 | 0.755742E+10 | ||||||||
Minimum of Months | 0.716647E+10 | 12629.96 | 23.13 | 18.00 | 0.562848E+09 | 845.62 | 23.13 | 16.03 | ||
Maximum of Months | 0.125704E+11 | 22277.23 | 35.67 | 27.27 | 0.691132E+09 | 954.74 | 32.87 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306063E+10 | 14119.22 | 01-JAN-17:03 | 23.33 | 19.19 | 0.371761E+09 | 544.95 | 24-JAN-14:39 | 17.00 | 10.58 |
February | 0.347971E+10 | 20154.00 | 26-FEB-17:32 | 23.67 | 19.48 | 0.349853E+09 | 544.95 | 14-FEB-14:50 | 23.67 | 19.48 |
March | 0.439509E+10 | 16030.07 | 05-MAR-16:32 | 26.10 | 18.81 | 0.421619E+09 | 544.95 | 24-MAR-13:20 | 24.03 | 15.88 |
April | 0.618519E+10 | 20821.61 | 16-APR-16:52 | 19.40 | 13.58 | 0.392736E+09 | 544.96 | 12-APR-13:20 | 19.40 | 13.58 |
May | 0.799723E+10 | 20437.72 | 29-MAY-16:12 | 32.07 | 23.52 | 0.428731E+09 | 545.00 | 02-MAY-13:09 | 32.07 | 23.52 |
June | 0.864065E+10 | 21899.98 | 11-JUN-17:21 | 32.75 | 21.65 | 0.427496E+09 | 544.95 | 13-JUN-13:20 | 33.17 | 21.40 |
July | 0.835280E+10 | 19729.66 | 16-JUL-15:52 | 31.70 | 25.48 | 0.397751E+09 | 544.94 | 14-JUL-13:20 | 31.70 | 25.48 |
August | 0.881735E+10 | 17528.24 | 07-AUG-03:02 | 26.67 | 24.75 | 0.445977E+09 | 544.94 | 15-AUG-09:20 | 26.10 | 22.41 |
September | 0.709189E+10 | 21837.94 | 03-SEP-15:31 | 32.37 | 24.62 | 0.395867E+09 | 544.94 | 21-SEP-13:50 | 26.78 | 22.76 |
October | 0.695101E+10 | 20927.79 | 09-OCT-16:31 | 28.00 | 21.42 | 0.409802E+09 | 544.99 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.440247E+10 | 19972.98 | 11-NOV-15:32 | 26.27 | 22.90 | 0.395779E+09 | 545.01 | 27-NOV-14:09 | 25.82 | 17.52 |
December | 0.357863E+10 | 19941.82 | 10-DEC-15:52 | 27.00 | 20.22 | 0.366285E+09 | 544.96 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.729526E+11 | 0.480366E+10 | ||||||||
Minimum of Months | 0.306063E+10 | 14119.22 | 19.40 | 13.58 | 0.349853E+09 | 544.94 | 17.00 | 10.58 | ||
Maximum of Months | 0.881735E+10 | 21899.98 | 32.75 | 25.48 | 0.445977E+09 | 545.01 | 33.17 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220744E+10 | 5117.66 | 31-JAN-15:00 | 25.00 | 21.54 | 0.518356E+09 | 845.60 | 02-JAN-14:20 | 25.00 | 21.54 |
February | 0.278850E+10 | 5572.84 | 22-FEB-14:30 | 25.55 | 20.41 | 0.498114E+09 | 845.60 | 28-FEB-14:09 | 25.00 | 20.38 |
March | 0.386878E+10 | 7208.56 | 30-MAR-13:30 | 28.55 | 22.55 | 0.607542E+09 | 845.61 | 24-MAR-13:20 | 28.55 | 22.55 |
April | 0.560764E+10 | 8901.26 | 28-APR-15:00 | 33.30 | 23.06 | 0.590322E+09 | 845.64 | 27-APR-13:00 | 33.30 | 23.06 |
May | 0.982291E+10 | 16588.55 | 29-MAY-14:42 | 32.70 | 23.12 | 0.664539E+09 | 868.45 | 08-MAY-13:50 | 32.70 | 23.12 |
June | 0.108268E+11 | 17046.92 | 11-JUN-17:21 | 32.75 | 21.65 | 0.662580E+09 | 845.62 | 13-JUN-13:20 | 33.17 | 21.40 |
July | 0.107154E+11 | 16579.98 | 04-JUL-16:42 | 30.68 | 26.02 | 0.616383E+09 | 845.61 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.104734E+11 | 16307.81 | 20-AUG-14:12 | 33.67 | 24.98 | 0.690930E+09 | 845.60 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.821823E+10 | 17234.90 | 10-SEP-14:31 | 35.67 | 27.27 | 0.612229E+09 | 845.62 | 21-SEP-13:50 | 26.78 | 22.76 |
October | 0.729467E+10 | 16837.32 | 08-OCT-13:01 | 32.17 | 26.14 | 0.625953E+09 | 845.66 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.398788E+10 | 9477.66 | 03-NOV-05:02 | 22.28 | 21.91 | 0.573701E+09 | 845.61 | 06-NOV-10:20 | 24.37 | 20.12 |
December | 0.274729E+10 | 6165.33 | 15-DEC-15:00 | 29.00 | 21.56 | 0.513544E+09 | 845.62 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.785589E+11 | 0.717419E+10 | ||||||||
Minimum of Months | 0.220744E+10 | 5117.66 | 22.28 | 20.41 | 0.498114E+09 | 845.60 | 24.37 | 20.12 | ||
Maximum of Months | 0.108268E+11 | 17234.90 | 35.67 | 27.27 | 0.690930E+09 | 868.45 | 33.30 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213782E+10 | 6983.78 | 19-JAN-10:20 | 23.57 | 21.08 | 0.364610E+09 | 544.94 | 02-JAN-14:20 | 23.57 | 21.08 |
February | 0.267506E+10 | 7499.19 | 27-FEB-10:30 | 21.90 | 19.28 | 0.346647E+09 | 544.95 | 09-FEB-10:00 | 21.90 | 19.28 |
March | 0.400745E+10 | 11706.57 | 26-MAR-09:13 | 24.03 | 19.81 | 0.419056E+09 | 544.98 | 23-MAR-09:09 | 24.03 | 19.81 |
April | 0.582951E+10 | 18817.68 | 23-APR-09:32 | 25.53 | 20.92 | 0.390837E+09 | 544.97 | 27-APR-13:00 | 28.80 | 22.60 |
May | 0.896815E+10 | 21185.53 | 29-MAY-10:01 | 29.08 | 23.08 | 0.428896E+09 | 548.16 | 02-MAY-13:09 | 29.08 | 23.08 |
June | 0.942541E+10 | 19139.94 | 11-JUN-08:62 | 25.47 | 21.10 | 0.427404E+09 | 544.95 | 13-JUN-13:20 | 33.17 | 21.40 |
July | 0.929889E+10 | 19032.38 | 23-JUL-09:42 | 30.82 | 26.39 | 0.397746E+09 | 544.94 | 14-JUL-13:20 | 30.82 | 26.39 |
August | 0.901478E+10 | 18687.05 | 06-AUG-08:32 | 28.67 | 26.43 | 0.445729E+09 | 544.94 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.716806E+10 | 20484.99 | 03-SEP-08:52 | 29.90 | 24.25 | 0.395580E+09 | 544.95 | 21-SEP-13:50 | 26.78 | 22.76 |
October | 0.667783E+10 | 20097.43 | 09-OCT-09:12 | 27.73 | 22.40 | 0.407765E+09 | 545.00 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.358544E+10 | 11558.52 | 11-NOV-09:43 | 24.40 | 21.68 | 0.395029E+09 | 544.95 | 24-NOV-10:20 | 20.87 | 16.31 |
December | 0.234875E+10 | 6975.23 | 10-DEC-10:43 | 25.67 | 20.42 | 0.353121E+09 | 544.95 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.711372E+11 | 0.477242E+10 | ||||||||
Minimum of Months | 0.213782E+10 | 6975.23 | 21.90 | 19.28 | 0.346647E+09 | 544.94 | 20.87 | 16.31 | ||
Maximum of Months | 0.942541E+10 | 21185.53 | 30.82 | 26.43 | 0.445729E+09 | 548.16 | 33.17 | 26.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.715397E+10 | 24854.72 | 01-JAN-14:01 | 25.83 | 18.00 | 0.602394E+09 | 900.32 | 19-JAN-14:39 | 25.00 | 21.54 |
February | 0.719884E+10 | 23011.79 | 26-FEB-14:02 | 26.52 | 19.79 | 0.550982E+09 | 887.31 | 27-FEB-14:09 | 25.60 | 20.00 |
March | 0.674925E+10 | 21161.47 | 05-MAR-13:53 | 27.70 | 18.31 | 0.643126E+09 | 845.63 | 15-MAR-13:20 | 22.20 | 16.14 |
April | 0.739959E+10 | 16370.41 | 23-APR-13:33 | 27.53 | 21.02 | 0.597161E+09 | 845.68 | 27-APR-13:00 | 28.80 | 22.60 |
May | 0.101015E+11 | 20502.38 | 29-MAY-14:42 | 32.70 | 23.12 | 0.664474E+09 | 863.74 | 08-MAY-13:50 | 32.70 | 23.12 |
June | 0.103970E+11 | 20445.16 | 11-JUN-16:01 | 32.38 | 21.26 | 0.662283E+09 | 845.64 | 13-JUN-13:20 | 33.17 | 21.40 |
July | 0.106316E+11 | 20187.94 | 09-JUL-14:12 | 29.07 | 25.40 | 0.616225E+09 | 845.62 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.118087E+11 | 20419.67 | 27-AUG-12:23 | 32.00 | 23.77 | 0.691209E+09 | 845.62 | 25-AUG-13:20 | 32.00 | 23.77 |
September | 0.108489E+11 | 23019.05 | 10-SEP-14:31 | 35.67 | 27.27 | 0.613496E+09 | 845.66 | 21-SEP-13:50 | 26.78 | 22.76 |
October | 0.129887E+11 | 23663.83 | 08-OCT-13:01 | 32.17 | 26.14 | 0.635799E+09 | 891.24 | 13-OCT-13:50 | 32.87 | 23.24 |
November | 0.998826E+10 | 23124.18 | 05-NOV-13:42 | 27.20 | 20.74 | 0.621516E+09 | 927.17 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.830212E+10 | 22493.87 | 10-DEC-14:02 | 27.17 | 20.19 | 0.579086E+09 | 907.30 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.113568E+12 | 0.747775E+10 | ||||||||
Minimum of Months | 0.674925E+10 | 16370.41 | 25.83 | 18.00 | 0.550982E+09 | 845.62 | 22.20 | 16.14 | ||
Maximum of Months | 0.129887E+11 | 24854.72 | 35.67 | 27.27 | 0.691209E+09 | 927.17 | 33.17 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263006E+10 | 21034.49 | 01-JAN-15:21 | 25.00 | 18.55 | 0.360710E+09 | 544.94 | 02-JAN-14:20 | 26.33 | 18.48 |
February | 0.325481E+10 | 22035.62 | 26-FEB-16:42 | 24.58 | 19.86 | 0.341429E+09 | 544.94 | 28-FEB-14:09 | 25.00 | 20.38 |
March | 0.422058E+10 | 18307.64 | 26-MAR-15:13 | 24.57 | 19.90 | 0.409655E+09 | 544.95 | 15-MAR-13:20 | 24.57 | 19.90 |
April | 0.630117E+10 | 21535.74 | 23-APR-16:52 | 27.20 | 21.71 | 0.389052E+09 | 544.97 | 27-APR-13:00 | 28.80 | 22.60 |
May | 0.854712E+10 | 22325.15 | 29-MAY-16:41 | 30.97 | 23.75 | 0.428842E+09 | 547.91 | 02-MAY-13:09 | 30.97 | 23.75 |
June | 0.933077E+10 | 23905.70 | 11-JUN-17:21 | 32.75 | 21.65 | 0.427552E+09 | 544.95 | 13-JUN-13:20 | 33.17 | 21.40 |
July | 0.905185E+10 | 21168.61 | 16-JUL-15:52 | 31.70 | 25.48 | 0.397833E+09 | 544.94 | 14-JUL-13:20 | 31.70 | 25.48 |
August | 0.943262E+10 | 20390.21 | 20-AUG-16:51 | 30.00 | 24.17 | 0.446035E+09 | 544.94 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.748067E+10 | 23909.97 | 03-SEP-15:31 | 32.37 | 24.62 | 0.395788E+09 | 544.95 | 21-SEP-13:50 | 26.78 | 22.76 |
October | 0.719906E+10 | 22853.09 | 01-OCT-15:51 | 27.70 | 18.29 | 0.407876E+09 | 544.98 | 23-OCT-09:39 | 25.67 | 23.79 |
November | 0.415397E+10 | 21120.67 | 05-NOV-15:42 | 27.20 | 19.63 | 0.386524E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.317538E+10 | 16690.96 | 10-DEC-15:22 | 27.50 | 20.13 | 0.353458E+09 | 544.97 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.747781E+11 | 0.474475E+10 | ||||||||
Minimum of Months | 0.263006E+10 | 16690.96 | 24.57 | 18.29 | 0.341429E+09 | 544.94 | 22.20 | 15.14 | ||
Maximum of Months | 0.943262E+10 | 23909.97 | 32.75 | 25.48 | 0.446035E+09 | 547.91 | 33.17 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306823E+10 | 11431.37 | 02-JAN-06:03 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 16.00 | 15.39 |
February | 0.338077E+10 | 7259.44 | 27-FEB-16:50 | 24.58 | 20.33 | 0.00 | 0.00 | 01-FEB-00:10 | 24.58 | 20.33 |
March | 0.448508E+10 | 6378.88 | 27-MAR-05:03 | 19.82 | 18.59 | 0.00 | 0.00 | 01-MAR-00:10 | 19.82 | 18.59 |
April | 0.593307E+10 | 6508.12 | 24-APR-05:03 | 20.08 | 20.03 | 0.00 | 0.00 | 01-APR-00:10 | 20.08 | 20.03 |
May | 0.728347E+10 | 9311.33 | 30-MAY-05:02 | 25.50 | 24.21 | 0.00 | 0.00 | 01-MAY-00:10 | 25.50 | 24.21 |
June | 0.786206E+10 | 8859.71 | 26-JUN-05:02 | 25.00 | 23.50 | 0.00 | 0.00 | 01-JUN-00:10 | 25.00 | 23.50 |
July | 0.843312E+10 | 10723.15 | 05-JUL-05:02 | 26.10 | 24.88 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 24.88 |
August | 0.936954E+10 | 10014.19 | 21-AUG-05:15 | 26.00 | 23.88 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 23.88 |
September | 0.698553E+10 | 10755.25 | 11-SEP-05:02 | 25.42 | 23.91 | 0.00 | 0.00 | 01-SEP-00:10 | 25.42 | 23.91 |
October | 0.733811E+10 | 9638.47 | 10-OCT-05:03 | 21.98 | 20.05 | 0.00 | 0.00 | 01-OCT-00:10 | 21.98 | 20.05 |
November | 0.541317E+10 | 8061.94 | 06-NOV-06:03 | 18.80 | 17.70 | 0.00 | 0.00 | 01-NOV-00:10 | 18.80 | 17.70 |
December | 0.440118E+10 | 6586.65 | 26-DEC-06:13 | 5.90 | 2.19 | 0.00 | 0.00 | 01-DEC-00:10 | 5.90 | 2.19 |
Annual Sum or Average | 0.739533E+11 | 0.00 | ||||||||
Minimum of Months | 0.306823E+10 | 6378.88 | 5.90 | 2.19 | 0.00 | 0.00 | 5.90 | 2.19 | ||
Maximum of Months | 0.936954E+10 | 11431.37 | 26.10 | 24.88 | 0.00 | 0.00 | 26.10 | 24.88 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158076E+10 | 6879.02 | 05-JAN-06:01 | 0.17 | 0.10 | 0.00 | 0.00 | 01-JAN-00:10 | 0.17 | 0.10 |
February | 0.176936E+10 | 6252.11 | 17-FEB-06:02 | 1.52 | -1.3 | 0.00 | 0.00 | 01-FEB-00:10 | 1.52 | -1.3 |
March | 0.241563E+10 | 4351.55 | 11-MAR-06:02 | 6.60 | 5.25 | 0.00 | 0.00 | 01-MAR-00:10 | 6.60 | 5.25 |
April | 0.365836E+10 | 5273.75 | 28-APR-05:03 | 22.80 | 21.69 | 0.00 | 0.00 | 01-APR-00:10 | 22.80 | 21.69 |
May | 0.614524E+10 | 6998.51 | 03-MAY-12:30 | 31.15 | 21.48 | 0.00 | 0.00 | 01-MAY-00:10 | 31.15 | 21.48 |
June | 0.639174E+10 | 6683.54 | 27-JUN-05:02 | 24.50 | 23.30 | 0.00 | 0.00 | 01-JUN-00:10 | 24.50 | 23.30 |
July | 0.650860E+10 | 7066.13 | 01-JUL-05:02 | 24.50 | 23.30 | 0.00 | 0.00 | 01-JUL-00:10 | 24.50 | 23.30 |
August | 0.665929E+10 | 5918.43 | 30-AUG-16:00 | 36.30 | 23.74 | 0.00 | 0.00 | 01-AUG-00:10 | 36.30 | 23.74 |
September | 0.557282E+10 | 8166.78 | 25-SEP-05:02 | 23.38 | 22.59 | 0.00 | 0.00 | 01-SEP-00:10 | 23.38 | 22.59 |
October | 0.546781E+10 | 7914.22 | 16-OCT-05:02 | 22.17 | 20.62 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.62 |
November | 0.299768E+10 | 4710.32 | 06-NOV-16:20 | 27.73 | 20.09 | 0.00 | 0.00 | 01-NOV-00:10 | 27.73 | 20.09 |
December | 0.217011E+10 | 5982.38 | 20-DEC-06:02 | 2.83 | 1.61 | 0.00 | 0.00 | 01-DEC-00:10 | 2.83 | 1.61 |
Annual Sum or Average | 0.513374E+11 | 0.00 | ||||||||
Minimum of Months | 0.158076E+10 | 4351.55 | 0.17 | -1.3 | 0.00 | 0.00 | 0.17 | -1.3 | ||
Maximum of Months | 0.665929E+10 | 8166.78 | 36.30 | 23.74 | 0.00 | 0.00 | 36.30 | 23.74 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177700E+10 | 8976.59 | 19-JAN-16:00 | 25.00 | 20.82 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 20.82 |
February | 0.273427E+10 | 11082.53 | 27-FEB-15:30 | 25.80 | 20.48 | 0.00 | 0.00 | 01-FEB-00:10 | 25.80 | 20.48 |
March | 0.383976E+10 | 10702.72 | 06-MAR-14:40 | 26.27 | 21.25 | 0.00 | 0.00 | 01-MAR-00:10 | 26.27 | 21.25 |
April | 0.679426E+10 | 15593.71 | 28-APR-15:00 | 33.30 | 23.06 | 0.00 | 0.00 | 01-APR-00:10 | 33.30 | 23.06 |
May | 0.113609E+11 | 21132.46 | 08-MAY-13:40 | 32.60 | 22.45 | 0.00 | 0.00 | 01-MAY-00:10 | 32.60 | 22.45 |
June | 0.125753E+11 | 19580.76 | 08-JUN-14:30 | 31.65 | 22.58 | 0.00 | 0.00 | 01-JUN-00:10 | 31.65 | 22.58 |
July | 0.120811E+11 | 17655.94 | 07-JUL-14:40 | 34.63 | 24.19 | 0.00 | 0.00 | 01-JUL-00:10 | 34.63 | 24.19 |
August | 0.121463E+11 | 16962.02 | 03-AUG-15:00 | 35.00 | 24.85 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 24.85 |
September | 0.921566E+10 | 15626.96 | 01-SEP-14:00 | 32.20 | 22.62 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 22.62 |
October | 0.873654E+10 | 15416.72 | 05-OCT-15:20 | 33.33 | 23.87 | 0.00 | 0.00 | 01-OCT-00:10 | 33.33 | 23.87 |
November | 0.388663E+10 | 12059.36 | 02-NOV-14:20 | 29.40 | 24.36 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.36 |
December | 0.242941E+10 | 10819.25 | 15-DEC-14:50 | 29.00 | 21.65 | 0.00 | 0.00 | 01-DEC-00:10 | 29.00 | 21.65 |
Annual Sum or Average | 0.875772E+11 | 0.00 | ||||||||
Minimum of Months | 0.177700E+10 | 8976.59 | 25.00 | 20.48 | 0.00 | 0.00 | 25.00 | 20.48 | ||
Maximum of Months | 0.125753E+11 | 21132.46 | 35.00 | 24.85 | 0.00 | 0.00 | 35.00 | 24.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381441E+10 | 2153.84 | 01-JAN-17:12 | 22.67 | 19.00 | 95231661.64 | 126.84 | 02-JAN-10:00 | 24.00 | 19.35 |
February | 0.823335E+10 | 4198.55 | 26-FEB-17:54 | 23.30 | 19.29 | 86405106.17 | 126.85 | 24-FEB-14:00 | 23.30 | 19.29 |
March | 0.142992E+11 | 7164.26 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.84 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.188816E+11 | 7989.48 | 16-APR-18:20 | 18.07 | 13.19 | 91642358.55 | 128.20 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.449422E+10 | 3450.02 | 31-MAY-24:00 | 23.00 | 21.40 | 99235360.36 | 126.85 | 12-MAY-13:00 | 23.00 | 21.40 |
June | 0.922292E+10 | 5326.41 | 30-JUN-24:00 | 25.10 | 23.16 | 98979906.40 | 126.86 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.145957E+11 | 7201.91 | 31-JUL-23:55 | 25.20 | 23.65 | 91894572.22 | 126.85 | 31-JUL-13:00 | 25.20 | 23.65 |
August | 0.196852E+11 | 7780.83 | 06-AUG-18:00 | 25.00 | 23.59 | 0.104659E+09 | 135.22 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.437582E+10 | 3472.55 | 30-SEP-24:00 | 22.30 | 21.22 | 91605768.38 | 126.82 | 05-SEP-13:09 | 22.30 | 21.22 |
October | 0.956305E+10 | 5327.92 | 31-OCT-24:00 | 21.60 | 20.90 | 95247478.84 | 126.87 | 24-OCT-09:09 | 21.60 | 20.90 |
November | 0.140133E+11 | 6014.84 | 12-NOV-17:10 | 14.53 | 8.53 | 94306907.27 | 126.85 | 29-NOV-10:00 | 22.70 | 21.98 |
December | 0.193979E+11 | 7881.62 | 10-DEC-16:53 | 25.00 | 19.63 | 91882342.29 | 126.83 | 28-DEC-14:09 | 19.17 | 19.17 |
Annual Sum or Average | 0.140577E+12 | 0.114433E+10 | ||||||||
Minimum of Months | 0.381441E+10 | 2153.84 | 14.53 | 8.53 | 86405106.17 | 126.82 | 19.17 | 19.17 | ||
Maximum of Months | 0.196852E+11 | 7989.48 | 25.20 | 23.65 | 0.104659E+09 | 135.22 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239880E+10 | 1795.43 | 01-JAN-17:25 | 22.00 | 18.79 | 95230990.10 | 126.84 | 02-JAN-14:09 | 26.17 | 18.43 |
February | 0.688831E+10 | 3840.77 | 26-FEB-17:54 | 23.30 | 19.29 | 86404719.73 | 126.85 | 24-FEB-14:00 | 23.30 | 19.29 |
March | 0.128311E+11 | 6688.59 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.84 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.177654E+11 | 7484.34 | 16-APR-18:20 | 18.07 | 13.19 | 91644552.47 | 128.48 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.407633E+10 | 3224.12 | 31-MAY-24:00 | 23.00 | 21.40 | 99233646.70 | 126.82 | 26-MAY-13:09 | 23.00 | 21.40 |
June | 0.869887E+10 | 5143.36 | 30-JUN-24:00 | 25.10 | 23.16 | 98978968.51 | 126.86 | 19-JUN-09:09 | 25.10 | 23.16 |
July | 0.138528E+11 | 6895.06 | 31-JUL-24:00 | 25.20 | 23.65 | 91893857.10 | 126.85 | 14-JUL-13:00 | 25.20 | 23.65 |
August | 0.186458E+11 | 7255.41 | 06-AUG-17:40 | 25.33 | 23.69 | 0.104451E+09 | 133.63 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.388522E+10 | 3201.26 | 30-SEP-24:00 | 22.30 | 21.22 | 91605380.76 | 126.82 | 05-SEP-13:09 | 22.30 | 21.22 |
October | 0.882342E+10 | 4919.07 | 31-OCT-24:00 | 21.60 | 20.90 | 95246779.25 | 126.87 | 24-OCT-09:09 | 21.60 | 20.90 |
November | 0.126999E+11 | 5574.67 | 06-NOV-17:00 | 26.60 | 19.72 | 94306534.22 | 126.84 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.174762E+11 | 7293.24 | 15-DEC-17:00 | 28.00 | 21.24 | 91882381.84 | 126.83 | 28-DEC-14:09 | 19.17 | 19.17 |
Annual Sum or Average | 0.128042E+12 | 0.114412E+10 | ||||||||
Minimum of Months | 0.239880E+10 | 1795.43 | 18.07 | 13.19 | 86404719.73 | 126.82 | 19.17 | 18.43 | ||
Maximum of Months | 0.186458E+11 | 7484.34 | 28.00 | 23.69 | 0.104451E+09 | 133.63 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149766E+10 | 1873.38 | 01-JAN-17:12 | 22.67 | 19.00 | 94926405.92 | 127.12 | 09-JAN-10:39 | 10.33 | 6.44 |
February | 0.608554E+10 | 3889.11 | 26-FEB-17:43 | 23.48 | 19.39 | 86405000.01 | 126.85 | 24-FEB-14:00 | 23.48 | 19.39 |
March | 0.122436E+11 | 6592.86 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.84 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.176336E+11 | 7684.29 | 23-APR-17:53 | 25.50 | 21.28 | 91633878.37 | 127.40 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.422583E+10 | 3196.11 | 31-MAY-24:00 | 23.00 | 21.40 | 99235005.07 | 126.85 | 03-MAY-13:00 | 23.00 | 21.40 |
June | 0.886252E+10 | 5179.29 | 30-JUN-24:00 | 25.10 | 23.16 | 98980118.78 | 126.86 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.140244E+11 | 6886.20 | 31-JUL-24:00 | 25.20 | 23.65 | 91894688.17 | 126.85 | 12-JUL-13:09 | 25.20 | 23.65 |
August | 0.187938E+11 | 7529.91 | 06-AUG-17:40 | 25.33 | 23.69 | 0.104040E+09 | 132.78 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.398845E+10 | 3226.95 | 30-SEP-24:00 | 22.30 | 21.22 | 91605403.01 | 126.82 | 05-SEP-13:09 | 22.30 | 21.22 |
October | 0.876641E+10 | 4850.49 | 31-OCT-24:00 | 21.60 | 20.90 | 95247428.42 | 126.87 | 06-OCT-13:00 | 21.60 | 20.90 |
November | 0.121525E+11 | 5634.82 | 06-NOV-17:00 | 26.60 | 19.72 | 94306819.65 | 126.85 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.165758E+11 | 7357.72 | 15-DEC-17:00 | 28.00 | 21.24 | 91882707.05 | 126.83 | 28-DEC-14:09 | 19.17 | 19.17 |
Annual Sum or Average | 0.124850E+12 | 0.114340E+10 | ||||||||
Minimum of Months | 0.149766E+10 | 1873.38 | 20.70 | 19.00 | 86405000.01 | 126.82 | 10.33 | 6.44 | ||
Maximum of Months | 0.187938E+11 | 7684.29 | 28.00 | 23.69 | 0.104040E+09 | 132.78 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239468E+12 | 92414.33 | 02-JAN-14:40 | 26.67 | 18.58 | 0.206150E+10 | 2746.60 | 19-JAN-14:00 | 25.00 | 21.54 |
February | 0.435721E+12 | 182989.29 | 27-FEB-17:00 | 24.40 | 20.28 | 0.187039E+10 | 2747.66 | 10-FEB-10:30 | 24.40 | 20.28 |
March | 0.727335E+12 | 358132.21 | 31-MAR-24:00 | 20.70 | 19.78 | 0.223521E+10 | 2749.13 | 16-MAR-13:00 | 20.70 | 19.78 |
April | 0.939332E+12 | 367507.40 | 18-APR-16:05 | 27.75 | 17.06 | 0.204232E+10 | 3328.67 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.239656E+12 | 175300.28 | 31-MAY-24:00 | 23.00 | 21.40 | 0.214895E+10 | 2747.11 | 26-MAY-09:09 | 23.00 | 21.40 |
June | 0.467970E+12 | 266915.32 | 30-JUN-24:00 | 25.10 | 23.16 | 0.214274E+10 | 2746.54 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.730091E+12 | 359206.29 | 31-JUL-23:55 | 25.20 | 23.65 | 0.198923E+10 | 2745.90 | 12-JUL-13:09 | 25.20 | 23.65 |
August | 0.971271E+12 | 370273.17 | 09-AUG-21:14 | 23.27 | 22.90 | 0.260155E+10 | 3580.64 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.235752E+12 | 176353.33 | 30-SEP-24:00 | 22.30 | 21.22 | 0.198389E+10 | 2747.09 | 18-SEP-13:00 | 22.30 | 21.22 |
October | 0.487433E+12 | 268263.94 | 31-OCT-24:00 | 21.60 | 20.90 | 0.206196E+10 | 2747.60 | 30-OCT-09:50 | 21.60 | 20.90 |
November | 0.708416E+12 | 275826.39 | 06-NOV-17:00 | 26.60 | 19.72 | 0.204207E+10 | 2750.52 | 20-NOV-10:09 | 20.18 | 16.15 |
December | 0.976300E+12 | 367285.59 | 26-DEC-17:00 | 12.70 | 5.60 | 0.201532E+10 | 3137.15 | 13-DEC-14:00 | 12.70 | 5.60 |
Annual Sum or Average | 0.715874E+13 | 0.251951E+11 | ||||||||
Minimum of Months | 0.235752E+12 | 92414.33 | 12.70 | 5.60 | 0.187039E+10 | 2745.90 | 12.70 | 5.60 | ||
Maximum of Months | 0.976300E+12 | 370273.17 | 27.75 | 23.65 | 0.260155E+10 | 3580.64 | 33.00 | 25.67 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213079E+09 | 10197.59 | 06-JAN-05:15 | 11.33 |
February | 0.198242E+09 | 10977.80 | 25-FEB-17:02 | 26.55 |
March | 0.121702E+09 | 10195.01 | 15-MAR-04:15 | 9.87 |
April | 0.159995E+09 | 16377.62 | 22-APR-16:01 | 30.08 |
May | 0.298958E+09 | 18309.83 | 27-MAY-16:02 | 31.60 |
June | 0.322241E+09 | 21599.03 | 10-JUN-16:01 | 33.72 |
July | 0.386526E+09 | 24886.91 | 22-JUL-16:01 | 35.92 |
August | 0.407463E+09 | 19265.77 | 19-AUG-16:02 | 32.63 |
September | 0.516467E+09 | 24565.58 | 09-SEP-16:01 | 35.73 |
October | 0.511804E+09 | 18512.29 | 07-OCT-16:01 | 31.58 |
November | 0.502777E+09 | 12019.02 | 12-NOV-08:43 | 8.12 |
December | 0.490471E+09 | 11989.64 | 25-DEC-09:53 | 12.00 |
Annual Sum or Average | 0.412973E+10 | |||
Minimum of Months | 0.121702E+09 | 10195.01 | 8.12 | |
Maximum of Months | 0.516467E+09 | 24886.91 | 35.92 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123463E+09 | 49534.88 | 10-JAN-06:02 | 3.00 |
February | 0.306635E+09 | 56949.33 | 06-FEB-05:11 | 2.97 |
March | 31895001.19 | 49490.01 | 13-MAR-05:02 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 54638561.19 | 49515.16 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.516631E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.306635E+09 | 56949.33 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12397.59 | 144.64 | 05-JAN-06:04 | 0.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 168814.96 | 1969.51 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 181212.55 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 168814.96 | 1969.51 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10796.21 | 125.96 | 05-JAN-06:06 | 0.17 |
February | 27786.91 | 231.56 | 06-FEB-06:04 | 2.88 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 38583.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 27786.91 | 231.56 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249155E+09 | 10753.19 | 10-JAN-05:01 | 1.33 |
February | 0.117167E+09 | 11063.11 | 06-FEB-05:11 | 2.97 |
March | 59347724.04 | 10158.00 | 13-MAR-05:02 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 327337.35 | 2240.63 | 16-NOV-06:02 | 9.40 |
December | 0.132234E+09 | 10730.64 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.558232E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.249155E+09 | 11063.11 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94387644.73 | 9388.93 | 10-JAN-05:01 | 1.33 |
February | 43365039.40 | 9642.54 | 06-FEB-05:11 | 2.97 |
March | 23594342.07 | 8808.72 | 09-MAR-06:02 | 1.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 66331594.04 | 9397.82 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.227679E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 94387644.73 | 9642.54 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42696624.17 | 11674.16 | 21-JAN-06:02 | 1.00 |
February | 17241039.93 | 11445.05 | 06-FEB-06:02 | 2.88 |
March | 18697758.49 | 11402.67 | 11-MAR-06:02 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 42811701.97 | 11556.44 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.121447E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 42811701.97 | 11674.16 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52299256.06 | 8282.78 | 10-JAN-05:01 | 1.33 |
February | 19522247.04 | 8245.13 | 06-FEB-05:11 | 2.97 |
March | 5892436.39 | 7535.40 | 11-MAR-06:02 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 27051874.29 | 7859.15 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.104766E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 52299256.06 | 8282.78 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124326E+10 | 13662.00 | 23-JAN-05:11 | 7.67 |
February | 0.715932E+09 | 14465.74 | 05-FEB-07:43 | -3.4 |
March | 0.437296E+09 | 12917.07 | 13-MAR-04:11 | 7.00 |
April | 321400.74 | 1547.46 | 03-APR-05:03 | 12.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 3301330.59 | 5911.62 | 28-OCT-05:03 | 10.00 |
November | 90327978.90 | 11838.68 | 16-NOV-05:12 | 9.27 |
December | 0.791982E+09 | 13330.15 | 21-DEC-04:02 | 1.67 |
Annual Sum or Average | 0.328242E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 0.124326E+10 | 14465.74 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505638E+09 | 12611.10 | 23-JAN-05:11 | 7.67 |
February | 0.266326E+09 | 13397.98 | 06-FEB-05:11 | 2.97 |
March | 0.218413E+09 | 11903.19 | 10-MAR-05:11 | 5.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 1055665.78 | 2580.99 | 28-OCT-05:03 | 10.00 |
November | 25145665.97 | 10458.94 | 16-NOV-06:02 | 9.40 |
December | 0.388544E+09 | 12417.36 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.140512E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.97 | |
Maximum of Months | 0.505638E+09 | 13397.98 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466791E+09 | 15724.09 | 10-JAN-05:01 | 1.33 |
February | 0.279231E+09 | 17126.95 | 06-FEB-05:11 | 2.97 |
March | 0.274102E+09 | 15328.08 | 11-MAR-05:11 | 7.13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 7397802.13 | 13840.18 | 16-NOV-06:02 | 9.40 |
December | 0.320788E+09 | 15991.28 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.134831E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.466791E+09 | 17126.95 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385104E+09 | 11998.08 | 10-JAN-05:01 | 1.33 |
February | 0.206489E+09 | 13091.31 | 06-FEB-05:11 | 2.97 |
March | 0.120570E+09 | 11250.19 | 10-MAR-05:11 | 5.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 7661590.64 | 10072.19 | 16-NOV-06:02 | 9.40 |
December | 0.208516E+09 | 11922.83 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.928341E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.385104E+09 | 13091.31 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63804380.99 | 8879.19 | 09-JAN-05:11 | 7.67 |
February | 64467120.48 | 8831.42 | 21-FEB-05:12 | 17.27 |
March | 66380050.01 | 8819.59 | 13-MAR-04:11 | 7.00 |
April | 71235334.80 | 9176.42 | 03-APR-04:12 | 12.43 |
May | 39260254.26 | 6137.27 | 28-MAY-14:32 | 33.13 |
June | 35876702.68 | 6256.00 | 07-JUN-04:12 | 21.10 |
July | 41961593.05 | 6777.38 | 02-JUL-15:32 | 29.07 |
August | 34747591.91 | 6929.54 | 06-AUG-15:02 | 30.67 |
September | 46694898.33 | 6757.27 | 29-SEP-04:12 | 23.80 |
October | 69387999.70 | 8404.62 | 30-OCT-04:12 | 16.67 |
November | 82777301.35 | 8905.12 | 27-NOV-05:12 | 14.33 |
December | 0.119054E+09 | 9386.51 | 26-DEC-05:12 | 6.97 |
Annual Sum or Average | 0.735647E+09 | |||
Minimum of Months | 34747591.91 | 6137.27 | 6.97 | |
Maximum of Months | 0.119054E+09 | 9386.51 | 33.13 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309415E+09 | 5719.58 | 16-JAN-16:03 | 24.67 |
February | 0.191206E+09 | 5811.85 | 26-FEB-16:52 | 24.40 |
March | 0.112267E+09 | 5267.36 | 20-MAR-05:02 | 12.10 |
April | 26668759.11 | 4361.19 | 10-APR-05:02 | 12.20 |
May | 28311814.12 | 5965.54 | 22-MAY-03:02 | 26.10 |
June | 22263167.80 | 5721.23 | 11-JUN-16:01 | 32.38 |
July | 29892221.17 | 5029.66 | 09-JUL-14:12 | 29.07 |
August | 21472603.77 | 4459.92 | 23-AUG-03:02 | 26.48 |
September | 39213966.83 | 7957.14 | 10-SEP-15:51 | 34.30 |
October | 45516224.95 | 5715.51 | 29-OCT-16:22 | 23.50 |
November | 53735155.15 | 5738.77 | 11-NOV-14:51 | 26.60 |
December | 0.152506E+09 | 6746.87 | 10-DEC-15:11 | 27.67 |
Annual Sum or Average | 0.103247E+10 | |||
Minimum of Months | 21472603.77 | 4361.19 | 12.10 | |
Maximum of Months | 0.309415E+09 | 7957.14 | 34.30 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167735E+10 | 12230.17 | 10-JAN-06:02 | 3.00 |
February | 0.106115E+10 | 17815.77 | 06-FEB-06:13 | 3.07 |
March | 0.915331E+09 | 13235.78 | 08-MAR-06:02 | 11.00 |
April | 0.184463E+09 | 9568.65 | 21-APR-05:02 | 18.30 |
May | 28763481.26 | 7937.25 | 16-MAY-04:11 | 23.30 |
June | 24039865.67 | 7454.53 | 07-JUN-04:12 | 21.10 |
July | 18419366.82 | 6219.50 | 10-JUL-03:02 | 25.60 |
August | 19103450.25 | 6099.11 | 17-AUG-04:12 | 21.93 |
September | 25002678.25 | 7738.66 | 08-SEP-05:02 | 24.58 |
October | 0.106884E+09 | 11851.71 | 18-OCT-05:02 | 15.17 |
November | 0.388325E+09 | 10431.26 | 06-NOV-06:03 | 18.80 |
December | 0.127328E+10 | 13038.38 | 21-DEC-06:03 | 0.83 |
Annual Sum or Average | 0.572211E+10 | |||
Minimum of Months | 18419366.82 | 6099.11 | 0.83 | |
Maximum of Months | 0.167735E+10 | 17815.77 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177733E+09 | 527.04 | 05-JAN-04:45 | 1.00 |
February | 536620.06 | 359.36 | 05-FEB-09:45 | 0.82 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.178269E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.82 | |
Maximum of Months | 0.177733E+09 | 527.04 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.664968E+09 | 931.91 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.582070E+09 | 966.94 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.669166E+09 | 884.16 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.585341E+09 | 911.52 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.611318E+09 | 633.47 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.600969E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.569095E+09 | 614.12 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.643095E+09 | 636.61 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.592374E+09 | 881.55 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.630880E+09 | 1017.23 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.654186E+09 | 972.76 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.657998E+09 | 1008.39 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.746146E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.569095E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.669166E+09 | 1017.23 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421632E+09 | 559.07 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.371000E+09 | 596.94 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.427704E+09 | 521.53 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.376432E+09 | 560.54 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.396067E+09 | 396.42 | 30-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.390235E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.368669E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.414822E+09 | 393.46 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.380730E+09 | 517.96 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.403613E+09 | 638.09 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.416522E+09 | 635.00 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.418287E+09 | 639.05 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478571E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.368669E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.427704E+09 | 639.05 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639397E+09 | 900.67 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.568375E+09 | 947.39 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.663304E+09 | 873.47 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.586845E+09 | 915.69 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.616885E+09 | 638.12 | 23-MAY-07:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.607661E+09 | 594.92 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.574045E+09 | 627.82 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.645744E+09 | 642.27 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.590925E+09 | 878.36 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.623797E+09 | 1009.08 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.632431E+09 | 941.76 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.631727E+09 | 996.90 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.738114E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.568375E+09 | 594.92 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.663304E+09 | 1009.08 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418287E+09 | 610.15 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.370477E+09 | 628.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.430478E+09 | 594.28 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.378493E+09 | 603.80 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.396849E+09 | 493.50 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.389823E+09 | 402.05 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.369330E+09 | 412.08 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.416566E+09 | 538.63 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.383350E+09 | 594.97 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.405140E+09 | 661.75 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.411929E+09 | 642.01 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.412200E+09 | 650.56 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.478292E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.369330E+09 | 402.05 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.430478E+09 | 661.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.662709E+09 | 929.22 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.580637E+09 | 964.77 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.667836E+09 | 880.98 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.584690E+09 | 908.75 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.610808E+09 | 629.38 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.600154E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.568752E+09 | 609.00 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.642612E+09 | 632.75 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.591506E+09 | 878.25 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.629940E+09 | 1015.70 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.652202E+09 | 970.46 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.655760E+09 | 1006.81 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744761E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.568752E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.667836E+09 | 1015.70 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420825E+09 | 554.83 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.370357E+09 | 593.51 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.427254E+09 | 517.36 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.376102E+09 | 556.92 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.395720E+09 | 393.40 | 23-MAY-07:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.389980E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.368305E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.414527E+09 | 390.64 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.380313E+09 | 514.09 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.403213E+09 | 635.82 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.415832E+09 | 632.29 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.417458E+09 | 636.61 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.477989E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.368305E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.427254E+09 | 636.61 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639091E+09 | 897.79 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.568114E+09 | 945.10 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.662588E+09 | 870.22 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.586270E+09 | 912.93 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.616241E+09 | 634.26 | 23-MAY-07:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.607062E+09 | 588.56 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.573522E+09 | 623.37 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.645201E+09 | 638.68 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.590352E+09 | 875.03 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.623305E+09 | 1007.50 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.631540E+09 | 939.58 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.631143E+09 | 995.27 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.737443E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.568114E+09 | 588.56 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.662588E+09 | 1007.50 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417688E+09 | 606.77 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.369936E+09 | 626.03 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429752E+09 | 590.44 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.377953E+09 | 600.23 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.396323E+09 | 486.52 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.389439E+09 | 399.09 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.368830E+09 | 409.72 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.416018E+09 | 533.48 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.382685E+09 | 591.15 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.404588E+09 | 659.72 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.411300E+09 | 639.49 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.411480E+09 | 648.25 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.477599E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.368830E+09 | 399.09 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.429752E+09 | 659.72 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.662584E+09 | 928.78 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.580604E+09 | 964.40 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.667805E+09 | 880.47 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.584672E+09 | 908.27 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.610774E+09 | 629.21 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.600119E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.568736E+09 | 608.79 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.642593E+09 | 632.59 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.591463E+09 | 877.73 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.629910E+09 | 1015.43 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.652117E+09 | 970.14 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.655711E+09 | 1006.51 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744709E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.568736E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.667805E+09 | 1015.43 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420812E+09 | 554.50 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.370334E+09 | 593.24 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.427241E+09 | 516.98 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.376092E+09 | 556.58 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.395693E+09 | 393.26 | 23-MAY-07:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.389958E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.368277E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.414513E+09 | 390.50 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.380295E+09 | 513.70 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.403201E+09 | 635.63 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.415791E+09 | 632.08 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.417428E+09 | 636.41 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.477964E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.368277E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.427241E+09 | 636.41 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639084E+09 | 897.30 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.568102E+09 | 944.70 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.662566E+09 | 869.70 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.586251E+09 | 912.46 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.616217E+09 | 634.10 | 23-MAY-07:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.607005E+09 | 588.32 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.573497E+09 | 623.20 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.645173E+09 | 638.54 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.590332E+09 | 874.51 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.623279E+09 | 1007.22 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.631527E+09 | 939.19 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.631126E+09 | 994.96 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.737416E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.568102E+09 | 588.32 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.662566E+09 | 1007.22 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.417651E+09 | 606.51 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.369924E+09 | 625.80 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429736E+09 | 590.15 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.377928E+09 | 599.95 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.396307E+09 | 486.10 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.389429E+09 | 398.99 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.368797E+09 | 409.63 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.415992E+09 | 533.21 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.382663E+09 | 590.85 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.404567E+09 | 659.56 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.411287E+09 | 639.30 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.411461E+09 | 648.06 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.477574E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.368797E+09 | 398.99 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.429736E+09 | 659.56 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.664968E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1017678.85 | 0.366520E+09 |
February | 0.136985E+10 | 0.582070E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1955978.84 | 0.285251E+09 |
March | 0.163685E+10 | 0.669166E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5989378.11 | 0.298898E+09 |
April | 0.145243E+10 | 0.585341E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12926596.54 | 0.124626E+09 |
May | 0.157338E+10 | 0.611318E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55196529.58 | 18111891.91 |
June | 0.156900E+10 | 0.600969E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52355288.17 | 11019401.04 |
July | 0.145680E+10 | 0.569095E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76858743.32 | 1616113.15 |
August | 0.163685E+10 | 0.643095E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73325234.28 | 9333660.43 |
September | 0.145243E+10 | 0.592374E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62536722.16 | 30968487.71 |
October | 0.150991E+10 | 0.630880E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50501593.55 | 0.104901E+09 |
November | 0.149516E+10 | 0.654186E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5239227.71 | 0.190293E+09 |
December | 0.145680E+10 | 0.657998E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3380708.72 | 0.334836E+09 |
Annual Sum or Average | 0.181194E+11 | 0.746146E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401284E+09 | 0.177637E+10 |
Minimum of Months | 0.136985E+10 | 0.569095E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1017678.85 | 1616113.15 |
Maximum of Months | 0.163685E+10 | 0.669166E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76858743.32 | 0.366520E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.421632E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530162.73 | 0.252445E+09 |
February | 0.882782E+09 | 0.371000E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1111995.45 | 0.194692E+09 |
March | 0.105485E+10 | 0.427704E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3353399.07 | 0.199822E+09 |
April | 0.936002E+09 | 0.376432E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8311668.47 | 82609729.80 |
May | 0.101394E+10 | 0.396067E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35052840.37 | 12354876.77 |
June | 0.101113E+10 | 0.390235E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34590155.34 | 6887753.31 |
July | 0.938820E+09 | 0.368669E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51241512.61 | 1017315.57 |
August | 0.105485E+10 | 0.414822E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50647392.85 | 4691669.00 |
September | 0.936002E+09 | 0.380730E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39009136.84 | 20630850.82 |
October | 0.973041E+09 | 0.403613E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31279623.46 | 70376181.39 |
November | 0.963541E+09 | 0.416522E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3102183.00 | 0.128399E+09 |
December | 0.938820E+09 | 0.418287E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2045118.04 | 0.219742E+09 |
Annual Sum or Average | 0.116768E+11 | 0.478571E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260275E+09 | 0.119367E+10 |
Minimum of Months | 0.882782E+09 | 0.368669E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530162.73 | 1017315.57 |
Maximum of Months | 0.105485E+10 | 0.427704E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51241512.61 | 0.252445E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.639397E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 572682.71 | 0.395615E+09 |
February | 0.136988E+10 | 0.568375E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1473897.49 | 0.303534E+09 |
March | 0.163688E+10 | 0.663304E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4586439.13 | 0.304101E+09 |
April | 0.145246E+10 | 0.586845E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11691947.03 | 0.128504E+09 |
May | 0.157341E+10 | 0.616885E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55112730.10 | 17924776.37 |
June | 0.156904E+10 | 0.607661E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53035104.78 | 10656145.03 |
July | 0.145684E+10 | 0.574045E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76723355.69 | 1667860.10 |
August | 0.163688E+10 | 0.645744E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71505916.18 | 9962694.90 |
September | 0.145246E+10 | 0.590925E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57385499.50 | 33931949.58 |
October | 0.150994E+10 | 0.623797E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41939220.86 | 0.120163E+09 |
November | 0.149520E+10 | 0.632431E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3935777.96 | 0.207800E+09 |
December | 0.145684E+10 | 0.631727E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2551605.33 | 0.356048E+09 |
Annual Sum or Average | 0.181198E+11 | 0.738114E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380514E+09 | 0.188991E+10 |
Minimum of Months | 0.136988E+10 | 0.568375E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 572682.71 | 1667860.10 |
Maximum of Months | 0.163688E+10 | 0.663304E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76723355.69 | 0.395615E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.418287E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 441447.90 | 0.274619E+09 |
February | 0.882782E+09 | 0.370477E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1010356.95 | 0.219033E+09 |
March | 0.105485E+10 | 0.430478E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3062232.83 | 0.237069E+09 |
April | 0.936002E+09 | 0.378493E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6822950.17 | 0.112922E+09 |
May | 0.101394E+10 | 0.396849E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31959522.91 | 21476617.73 |
June | 0.101113E+10 | 0.389823E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29092643.09 | 15465915.85 |
July | 0.938820E+09 | 0.369330E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38816561.88 | 7237325.10 |
August | 0.105485E+10 | 0.416566E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39257147.42 | 21483590.54 |
September | 0.936002E+09 | 0.383350E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35124402.49 | 32320448.47 |
October | 0.973041E+09 | 0.405140E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27284271.39 | 97701412.51 |
November | 0.963541E+09 | 0.411929E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2747347.70 | 0.154507E+09 |
December | 0.938820E+09 | 0.412200E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1775951.06 | 0.271164E+09 |
Annual Sum or Average | 0.116768E+11 | 0.478292E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217395E+09 | 0.146500E+10 |
Minimum of Months | 0.882782E+09 | 0.369330E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 441447.90 | 7237325.10 |
Maximum of Months | 0.105485E+10 | 0.430478E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39257147.42 | 0.274619E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.662709E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5672474.40 | 0.721986E+09 |
February | 0.136985E+10 | 0.580637E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6764732.34 | 0.556178E+09 |
March | 0.163685E+10 | 0.667836E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18333120.25 | 0.599993E+09 |
April | 0.145243E+10 | 0.584690E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29968170.85 | 0.270234E+09 |
May | 0.157338E+10 | 0.610808E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123380E+09 | 43734540.92 |
June | 0.156900E+10 | 0.600154E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112381E+09 | 34085559.77 |
July | 0.145680E+10 | 0.568752E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158406E+09 | 12572914.99 |
August | 0.163685E+10 | 0.642612E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154390E+09 | 43517296.18 |
September | 0.145243E+10 | 0.591506E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143172E+09 | 68312547.65 |
October | 0.150991E+10 | 0.629940E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116356E+09 | 0.228093E+09 |
November | 0.149516E+10 | 0.652202E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15675970.14 | 0.375910E+09 |
December | 0.145680E+10 | 0.655760E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10796287.88 | 0.648536E+09 |
Annual Sum or Average | 0.181194E+11 | 0.744761E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895297E+09 | 0.360315E+10 |
Minimum of Months | 0.136985E+10 | 0.568752E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5672474.40 | 12572914.99 |
Maximum of Months | 0.163685E+10 | 0.667836E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158406E+09 | 0.721986E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.420825E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1321654.53 | 0.528862E+09 |
February | 0.649041E+09 | 0.370357E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2419560.47 | 0.408122E+09 |
March | 0.773965E+09 | 0.427254E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6918912.07 | 0.437004E+09 |
April | 0.688021E+09 | 0.376102E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16577179.39 | 0.203022E+09 |
May | 0.744847E+09 | 0.395720E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73457914.87 | 34847198.96 |
June | 0.742030E+09 | 0.389980E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69795559.27 | 25807124.42 |
July | 0.690839E+09 | 0.368305E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95539581.71 | 11563599.41 |
August | 0.773965E+09 | 0.414527E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95040955.71 | 33031064.94 |
September | 0.688021E+09 | 0.380313E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83407068.88 | 52365264.99 |
October | 0.715730E+09 | 0.403213E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64975772.10 | 0.171167E+09 |
November | 0.708685E+09 | 0.415832E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6414359.75 | 0.281037E+09 |
December | 0.690839E+09 | 0.417458E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4202210.66 | 0.465716E+09 |
Annual Sum or Average | 0.858171E+10 | 0.477989E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520071E+09 | 0.265254E+10 |
Minimum of Months | 0.649041E+09 | 0.368305E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1321654.53 | 11563599.41 |
Maximum of Months | 0.773965E+09 | 0.427254E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95539581.71 | 0.528862E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.639091E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1001078.36 | 0.887429E+09 |
February | 0.136988E+10 | 0.568114E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3103848.22 | 0.672916E+09 |
March | 0.163688E+10 | 0.662588E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10128293.32 | 0.664419E+09 |
April | 0.145246E+10 | 0.586270E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26294904.78 | 0.297290E+09 |
May | 0.157341E+10 | 0.616241E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123120E+09 | 44364647.33 |
June | 0.156904E+10 | 0.607062E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115106E+09 | 32455738.56 |
July | 0.145684E+10 | 0.573522E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159753E+09 | 12379377.95 |
August | 0.163688E+10 | 0.645201E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149776E+09 | 46557321.67 |
September | 0.145246E+10 | 0.590352E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127663E+09 | 81368599.19 |
October | 0.150994E+10 | 0.623305E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91760258.93 | 0.295240E+09 |
November | 0.149520E+10 | 0.631540E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8524404.13 | 0.468752E+09 |
December | 0.145684E+10 | 0.631143E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5525931.59 | 0.792428E+09 |
Annual Sum or Average | 0.181198E+11 | 0.737443E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821757E+09 | 0.429560E+10 |
Minimum of Months | 0.136988E+10 | 0.568114E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1001078.36 | 12379377.95 |
Maximum of Months | 0.163688E+10 | 0.662588E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159753E+09 | 0.887429E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417688E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1489433.05 | 0.547138E+09 |
February | 0.882782E+09 | 0.369936E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2662210.62 | 0.421821E+09 |
March | 0.105485E+10 | 0.429752E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8544853.04 | 0.451440E+09 |
April | 0.936002E+09 | 0.377953E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15811264.96 | 0.223137E+09 |
May | 0.101394E+10 | 0.396323E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75143142.73 | 42077901.01 |
June | 0.101113E+10 | 0.389439E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67747905.51 | 33480398.56 |
July | 0.938820E+09 | 0.368830E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92078845.64 | 17483313.04 |
August | 0.105485E+10 | 0.416018E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92958774.41 | 44613359.05 |
September | 0.936002E+09 | 0.382685E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81695695.90 | 63616690.03 |
October | 0.973041E+09 | 0.404588E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65293309.07 | 0.195228E+09 |
November | 0.963541E+09 | 0.411300E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7196301.02 | 0.290983E+09 |
December | 0.938820E+09 | 0.411480E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4783287.51 | 0.496635E+09 |
Annual Sum or Average | 0.116768E+11 | 0.477599E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515405E+09 | 0.282765E+10 |
Minimum of Months | 0.882782E+09 | 0.368830E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1489433.05 | 17483313.04 |
Maximum of Months | 0.105485E+10 | 0.429752E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92958774.41 | 0.547138E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.662584E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8578720.40 | 0.811669E+09 |
February | 0.136985E+10 | 0.580604E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8696212.69 | 0.623213E+09 |
March | 0.163685E+10 | 0.667805E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21518704.73 | 0.692690E+09 |
April | 0.145243E+10 | 0.584672E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33556241.63 | 0.325608E+09 |
May | 0.157338E+10 | 0.610774E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142281E+09 | 61591494.12 |
June | 0.156900E+10 | 0.600119E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130225E+09 | 47752732.92 |
July | 0.145680E+10 | 0.568736E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179630E+09 | 20223538.56 |
August | 0.163685E+10 | 0.642593E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179353E+09 | 60485317.32 |
September | 0.145243E+10 | 0.591463E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162411E+09 | 91055199.89 |
October | 0.150991E+10 | 0.629910E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131341E+09 | 0.272089E+09 |
November | 0.149516E+10 | 0.652117E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20147134.63 | 0.424369E+09 |
December | 0.145680E+10 | 0.655711E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14676828.70 | 0.734186E+09 |
Annual Sum or Average | 0.181194E+11 | 0.744709E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103241E+10 | 0.416493E+10 |
Minimum of Months | 0.136985E+10 | 0.568736E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8578720.40 | 20223538.56 |
Maximum of Months | 0.163685E+10 | 0.667805E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179630E+09 | 0.811669E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.420812E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2219598.40 | 0.589618E+09 |
February | 0.882782E+09 | 0.370334E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3220725.91 | 0.454103E+09 |
March | 0.105485E+10 | 0.427241E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8626522.46 | 0.506801E+09 |
April | 0.936002E+09 | 0.376092E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19930711.26 | 0.245751E+09 |
May | 0.101394E+10 | 0.395693E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88067589.50 | 47873476.49 |
June | 0.101113E+10 | 0.389958E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83619796.78 | 35434792.44 |
July | 0.938820E+09 | 0.368277E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112522E+09 | 17314325.05 |
August | 0.105485E+10 | 0.414513E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114020E+09 | 44914884.49 |
September | 0.936002E+09 | 0.380295E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99366346.33 | 68554008.76 |
October | 0.973041E+09 | 0.403201E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77580366.77 | 0.204533E+09 |
November | 0.963541E+09 | 0.415791E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8102101.59 | 0.321764E+09 |
December | 0.938820E+09 | 0.417428E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5729348.03 | 0.524203E+09 |
Annual Sum or Average | 0.116768E+11 | 0.477964E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623005E+09 | 0.306086E+10 |
Minimum of Months | 0.882782E+09 | 0.368277E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2219598.40 | 17314325.05 |
Maximum of Months | 0.105485E+10 | 0.427241E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114020E+09 | 0.589618E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.639084E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1230957.17 | 0.102150E+10 |
February | 0.136988E+10 | 0.568102E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3705614.66 | 0.763299E+09 |
March | 0.163688E+10 | 0.662566E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11712300.15 | 0.773976E+09 |
April | 0.145246E+10 | 0.586251E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30138777.03 | 0.360046E+09 |
May | 0.157341E+10 | 0.616217E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142347E+09 | 62378965.26 |
June | 0.156904E+10 | 0.607005E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132962E+09 | 45650885.17 |
July | 0.145684E+10 | 0.573497E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181750E+09 | 19864674.75 |
August | 0.163688E+10 | 0.645173E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175612E+09 | 64411570.39 |
September | 0.145246E+10 | 0.590332E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149655E+09 | 0.107346E+09 |
October | 0.150994E+10 | 0.623279E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108920E+09 | 0.359012E+09 |
November | 0.149520E+10 | 0.631527E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10519788.35 | 0.549958E+09 |
December | 0.145684E+10 | 0.631126E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6771825.34 | 0.914847E+09 |
Annual Sum or Average | 0.181198E+11 | 0.737416E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955325E+09 | 0.504229E+10 |
Minimum of Months | 0.136988E+10 | 0.568102E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1230957.17 | 19864674.75 |
Maximum of Months | 0.163688E+10 | 0.662566E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181750E+09 | 0.102150E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.417651E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1966642.11 | 0.630485E+09 |
February | 0.882782E+09 | 0.369924E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3153906.03 | 0.482657E+09 |
March | 0.105485E+10 | 0.429736E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10178122.71 | 0.529854E+09 |
April | 0.936002E+09 | 0.377928E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18634823.54 | 0.270763E+09 |
May | 0.101394E+10 | 0.396307E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88716823.79 | 56644607.09 |
June | 0.101113E+10 | 0.389429E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80945033.52 | 44585006.96 |
July | 0.938820E+09 | 0.368797E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108687E+09 | 24324889.56 |
August | 0.105485E+10 | 0.415992E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110859E+09 | 59370071.70 |
September | 0.936002E+09 | 0.382663E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97007590.88 | 82131368.73 |
October | 0.973041E+09 | 0.404567E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76772389.65 | 0.236318E+09 |
November | 0.963541E+09 | 0.411287E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8845660.45 | 0.338583E+09 |
December | 0.938820E+09 | 0.411461E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6052310.87 | 0.574080E+09 |
Annual Sum or Average | 0.116768E+11 | 0.477574E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611820E+09 | 0.332980E+10 |
Minimum of Months | 0.882782E+09 | 0.368797E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1966642.11 | 24324889.56 |
Maximum of Months | 0.105485E+10 | 0.429736E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110859E+09 | 0.630485E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 801688.05 | 0.821786E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116564.36 | 0.636444E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8479388.39 | 0.657571E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20015053.92 | 0.283203E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97668743.31 | 34546197.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91400264.80 | 26412422.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138982E+09 | 6574843.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124768E+09 | 32881054.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109971E+09 | 66702625.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84123513.55 | 0.244763E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7075426.32 | 0.428436E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4639267.51 | 0.747607E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690042E+09 | 0.398693E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 801688.05 | 6574843.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138982E+09 | 0.821786E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3465029.88 | 0.135427E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6001163.51 | 0.104942E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21314865.30 | 0.108916E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38329841.90 | 0.479379E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181665E+09 | 56995619.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165556E+09 | 47109209.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251660E+09 | 13024303.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227215E+09 | 64488031.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208353E+09 | 0.107369E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157009E+09 | 0.412988E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15265212.27 | 0.710497E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10328007.20 | 0.121638E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128616E+10 | 0.660108E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3465029.88 | 13024303.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251660E+09 | 0.135427E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1777910.39 | 0.134047E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2082895.63 | 0.103848E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11081623.04 | 0.113949E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23199055.79 | 0.542005E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153394E+09 | 75505008.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144612E+09 | 59572690.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215418E+09 | 22652887.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207677E+09 | 82503762.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188444E+09 | 0.127262E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120685E+09 | 0.444235E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10738213.39 | 0.716736E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7842796.58 | 0.121215E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108695E+10 | 0.680106E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1777910.39 | 22652887.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215418E+09 | 0.134047E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 931.91 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.07 | 16-JAN-15:00 | 693.91 | 09-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 966.94 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 02-FEB-13:00 | 969.27 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 884.16 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.78 | 05-MAR-12:50 | 831.60 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 911.52 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.47 | 29-APR-17:01 | 505.17 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 633.47 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.74 | 07-MAY-13:52 | 114.02 | 14-MAY-12:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.65 | 10-JUN-17:02 | 149.16 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 614.12 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.90 | 22-JUL-18:50 | 70.62 | 30-JUL-10:53 |
August | 2010.79 | 01-AUG-09:09 | 636.61 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.24 | 20-AUG-14:00 | 152.93 | 25-AUG-23:40 |
September | 2010.79 | 01-SEP-09:09 | 881.55 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.95 | 09-SEP-22:53 | 196.86 | 05-SEP-02:50 |
October | 2010.79 | 02-OCT-09:09 | 1017.23 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.88 | 09-OCT-13:51 | 410.05 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 972.76 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 05-NOV-13:00 | 593.62 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 1008.39 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.69 | 10-DEC-14:51 | 897.15 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 70.62 | |||||
Maximum of Months | 2010.79 | 1017.23 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 360.88 | 969.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 559.07 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 16-JAN-15:00 | 472.20 | 22-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 596.94 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 02-FEB-13:00 | 709.36 | 05-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 521.53 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.34 | 26-MAR-14:00 | 547.03 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 560.54 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.66 | 29-APR-17:01 | 325.27 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 396.42 | 30-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.27 | 21-MAY-14:00 | 102.08 | 14-MAY-12:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.85 | 10-JUN-17:02 | 93.22 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.18 | 22-JUL-18:50 | 68.93 | 30-JUL-10:53 |
August | 1295.83 | 01-AUG-09:09 | 393.46 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.33 | 20-AUG-14:00 | 93.57 | 25-AUG-23:40 |
September | 1295.83 | 01-SEP-09:09 | 517.96 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.65 | 09-SEP-22:53 | 132.29 | 05-SEP-02:50 |
October | 1295.83 | 02-OCT-09:09 | 638.09 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.84 | 09-OCT-14:06 | 269.67 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 635.00 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 05-NOV-13:00 | 461.24 | 12-NOV-08:10 |
December | 1295.83 | 01-DEC-10:09 | 639.05 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 | 10-DEC-14:51 | 578.10 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 68.93 | |||||
Maximum of Months | 1295.83 | 639.05 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 234.84 | 709.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 900.67 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 19-JAN-12:10 | 690.21 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 947.39 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 02-FEB-13:00 | 969.65 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 873.47 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.61 | 26-MAR-13:55 | 836.42 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 915.69 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.22 | 29-APR-17:01 | 507.94 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 638.12 | 23-MAY-07:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.90 | 21-MAY-14:00 | 121.43 | 14-MAY-12:00 |
June | 2010.83 | 01-JUN-09:09 | 594.92 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.08 | 10-JUN-17:02 | 146.96 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 627.82 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.12 | 22-JUL-18:50 | 79.40 | 30-JUL-10:53 |
August | 2010.83 | 01-AUG-09:09 | 642.27 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.48 | 20-AUG-14:00 | 155.08 | 25-AUG-23:40 |
September | 2010.83 | 01-SEP-09:09 | 878.36 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.30 | 09-SEP-22:53 | 207.25 | 05-SEP-02:50 |
October | 2010.83 | 02-OCT-09:09 | 1009.08 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.50 | 09-OCT-13:44 | 423.44 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 941.76 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.92 | 28-NOV-13:00 | 652.40 | 12-NOV-08:10 |
December | 2010.83 | 01-DEC-10:09 | 996.90 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 13-DEC-14:00 | 873.58 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 594.92 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 79.40 | |||||
Maximum of Months | 2010.83 | 1009.08 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 328.50 | 969.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 610.15 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 19-JAN-12:05 | 490.02 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 628.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 02-FEB-13:00 | 687.29 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 594.28 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 26-MAR-13:35 | 621.37 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 603.80 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 | 29-APR-17:10 | 421.73 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 493.50 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.75 | 21-MAY-13:50 | 93.36 | 14-MAY-12:00 |
June | 1295.83 | 01-JUN-09:09 | 402.05 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.96 | 10-JUN-17:07 | 140.17 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 412.08 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.00 | 02-JUL-11:38 | 80.87 | 31-JUL-02:10 |
August | 1295.83 | 01-AUG-09:09 | 538.63 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.29 | 20-AUG-14:00 | 160.64 | 25-AUG-23:40 |
September | 1295.83 | 01-SEP-09:09 | 594.97 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.74 | 09-SEP-17:07 | 158.21 | 05-SEP-02:50 |
October | 1295.83 | 02-OCT-09:09 | 661.75 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.47 | 09-OCT-14:04 | 321.34 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 642.01 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 | 07-NOV-13:00 | 438.40 | 12-NOV-08:00 |
December | 1295.83 | 01-DEC-10:09 | 650.56 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 | 13-DEC-14:00 | 687.52 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 402.05 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 80.87 | |||||
Maximum of Months | 1295.83 | 661.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 225.47 | 687.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 929.22 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 194.02 | 16-JAN-15:00 | 1402.99 | 21-JAN-05:53 |
February | 2010.79 | 01-FEB-10:09 | 964.77 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 213.23 | 20-FEB-14:53 | 1928.45 | 05-FEB-07:55 |
March | 2010.79 | 01-MAR-10:09 | 880.98 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 333.72 | 05-MAR-12:40 | 1711.55 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 908.75 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.13 | 29-APR-17:01 | 1000.03 | 01-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 629.38 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.40 | 07-MAY-14:00 | 251.01 | 14-MAY-12:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.24 | 10-JUN-17:02 | 300.82 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 609.00 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.42 | 22-JUL-18:50 | 199.95 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 632.75 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 770.85 | 20-AUG-14:00 | 432.86 | 25-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 878.25 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 765.71 | 09-SEP-22:53 | 425.11 | 05-SEP-02:53 |
October | 2010.79 | 02-OCT-09:09 | 1015.70 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 860.82 | 09-OCT-14:00 | 801.20 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 970.46 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.99 | 05-NOV-13:00 | 1217.13 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 1006.81 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.34 | 10-DEC-15:00 | 1734.97 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 189.34 | 199.95 | |||||
Maximum of Months | 2010.79 | 1015.70 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 860.82 | 1928.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 554.83 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.85 | 16-JAN-15:00 | 936.53 | 21-JAN-05:53 |
February | 1239.33 | 01-FEB-08:09 | 593.51 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.50 | 20-FEB-14:53 | 1443.95 | 05-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 517.36 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.76 | 26-MAR-14:00 | 1174.13 | 20-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 556.92 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.27 | 29-APR-17:01 | 705.01 | 01-APR-17:53 |
May | 1239.33 | 01-MAY-07:10 | 393.40 | 23-MAY-07:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.49 | 21-MAY-13:50 | 262.29 | 14-MAY-12:00 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.49 | 10-JUN-17:02 | 217.17 | 11-JUN-08:00 |
July | 1239.33 | 03-JUL-07:10 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.31 | 22-JUL-18:50 | 262.67 | 30-JUL-11:00 |
August | 1239.33 | 01-AUG-07:10 | 390.64 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.42 | 20-AUG-14:00 | 298.48 | 25-AUG-23:55 |
September | 1239.33 | 01-SEP-07:10 | 514.09 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.63 | 09-SEP-22:53 | 305.25 | 05-SEP-02:53 |
October | 1239.33 | 02-OCT-07:10 | 635.82 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 584.26 | 09-OCT-13:54 | 558.80 | 29-OCT-02:00 |
November | 1239.33 | 01-NOV-07:10 | 632.29 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.38 | 05-NOV-13:00 | 1005.25 | 12-NOV-08:50 |
December | 1239.33 | 01-DEC-08:09 | 636.61 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.52 | 10-DEC-15:00 | 1171.15 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 73.38 | 217.17 | |||||
Maximum of Months | 1239.33 | 636.61 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 584.26 | 1443.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 897.79 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 | 19-JAN-12:00 | 1637.01 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 945.10 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.06 | 02-FEB-13:00 | 2058.38 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 870.22 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.87 | 26-MAR-13:55 | 1796.36 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 912.93 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.84 | 29-APR-17:01 | 1079.12 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 634.26 | 23-MAY-07:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.09 | 07-MAY-13:52 | 271.76 | 14-MAY-12:00 |
June | 2010.83 | 01-JUN-09:09 | 588.56 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 658.66 | 10-JUN-17:02 | 299.70 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 623.37 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.47 | 22-JUL-18:50 | 213.77 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 638.68 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.90 | 20-AUG-14:00 | 444.19 | 25-AUG-23:55 |
September | 2010.83 | 01-SEP-09:09 | 875.03 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 729.40 | 09-SEP-22:53 | 462.17 | 05-SEP-02:53 |
October | 2010.83 | 02-OCT-09:09 | 1007.50 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.91 | 09-OCT-13:57 | 926.36 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 939.58 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 | 28-NOV-13:00 | 1428.53 | 12-NOV-08:50 |
December | 2010.83 | 01-DEC-10:09 | 995.27 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.26 | 13-DEC-14:00 | 1813.58 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 588.56 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 | 213.77 | |||||
Maximum of Months | 2010.83 | 1007.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 780.91 | 2058.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 606.77 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 | 16-JAN-13:40 | 984.64 | 22-JAN-16:55 |
February | 1295.83 | 01-FEB-10:09 | 626.03 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.05 | 02-FEB-13:00 | 1323.90 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 590.44 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.78 | 05-MAR-12:40 | 1230.72 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 600.23 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.51 | 23-APR-14:54 | 814.52 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 486.52 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.29 | 21-MAY-13:50 | 182.92 | 06-MAY-19:55 |
June | 1295.83 | 01-JUN-09:09 | 399.09 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.06 | 10-JUN-17:07 | 240.24 | 06-JUN-21:20 |
July | 1295.83 | 03-JUL-09:09 | 409.72 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.46 | 02-JUL-11:28 | 172.01 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 533.48 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.79 | 20-AUG-14:00 | 332.02 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 591.15 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.84 | 09-SEP-17:07 | 327.56 | 05-SEP-02:53 |
October | 1295.83 | 02-OCT-09:09 | 659.72 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.29 | 09-OCT-13:53 | 608.28 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 639.49 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 | 05-NOV-12:52 | 861.40 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 648.25 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.17 | 10-DEC-10:52 | 1215.25 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 399.09 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 | 172.01 | |||||
Maximum of Months | 1295.83 | 659.72 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 559.29 | 1323.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 928.78 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 260.10 | 15-JAN-14:00 | 1790.94 | 21-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 964.40 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 291.35 | 20-FEB-15:00 | 2289.85 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 880.47 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 411.29 | 05-MAR-13:00 | 1998.75 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 908.27 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 419.17 | 29-APR-17:01 | 1227.13 | 01-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 629.21 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.52 | 07-MAY-13:52 | 259.22 | 14-MAY-11:53 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 714.48 | 10-JUN-17:02 | 387.92 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 608.79 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.90 | 02-JUL-11:48 | 320.87 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 632.59 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 887.00 | 20-AUG-14:00 | 528.95 | 25-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 877.73 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 890.07 | 09-SEP-17:02 | 565.48 | 05-SEP-02:53 |
October | 2010.79 | 02-OCT-09:09 | 1015.43 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.61 | 09-OCT-13:54 | 857.03 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 970.14 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.38 | 05-NOV-12:52 | 1424.83 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 1006.51 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.04 | 10-DEC-11:10 | 1861.38 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 227.04 | 259.22 | |||||
Maximum of Months | 2010.79 | 1015.43 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.61 | 2289.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 554.50 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.92 | 16-JAN-15:00 | 1193.96 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 593.24 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.72 | 20-FEB-15:00 | 1526.76 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 516.98 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 | 26-MAR-14:00 | 1381.54 | 20-MAR-21:25 |
April | 1295.83 | 03-APR-09:09 | 556.58 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.37 | 29-APR-17:01 | 864.49 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 393.26 | 23-MAY-07:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.47 | 07-MAY-13:52 | 275.30 | 14-MAY-12:10 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 471.59 | 10-JUN-17:02 | 278.20 | 11-JUN-08:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.38 | 02-JUL-11:48 | 354.21 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 390.50 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.32 | 20-AUG-14:00 | 363.67 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 513.70 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.51 | 09-SEP-17:02 | 398.80 | 05-SEP-02:53 |
October | 1295.83 | 02-OCT-09:09 | 635.63 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.49 | 09-OCT-13:54 | 600.09 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 632.08 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.51 | 05-NOV-13:10 | 1171.05 | 12-NOV-08:50 |
December | 1295.83 | 01-DEC-10:09 | 636.41 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.51 | 10-DEC-15:00 | 1250.20 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 82.51 | 275.30 | |||||
Maximum of Months | 1295.83 | 636.41 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 722.49 | 1526.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 897.30 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.82 | 19-JAN-12:05 | 1899.72 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 944.70 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.94 | 02-FEB-13:00 | 2290.11 | 05-FEB-07:55 |
March | 2010.83 | 01-MAR-10:09 | 869.70 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 193.22 | 26-MAR-13:58 | 2116.33 | 20-MAR-21:25 |
April | 2010.83 | 03-APR-09:09 | 912.46 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.18 | 29-APR-17:01 | 1329.72 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 634.10 | 23-MAY-07:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.72 | 07-MAY-13:52 | 278.28 | 14-MAY-11:53 |
June | 2010.83 | 01-JUN-09:09 | 588.32 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 745.23 | 10-JUN-17:02 | 387.54 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 623.20 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 619.55 | 02-JUL-11:48 | 335.97 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 638.54 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.99 | 20-AUG-14:00 | 543.21 | 25-AUG-23:55 |
September | 2010.83 | 01-SEP-09:09 | 874.51 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 835.52 | 09-SEP-22:53 | 605.00 | 05-SEP-02:53 |
October | 2010.83 | 02-OCT-09:09 | 1007.22 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 944.37 | 09-OCT-13:57 | 1025.65 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 939.19 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.59 | 07-NOV-13:00 | 1764.01 | 12-NOV-10:53 |
December | 2010.83 | 01-DEC-10:09 | 994.96 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.07 | 13-DEC-14:00 | 1939.09 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 588.32 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 42.82 | 278.28 | |||||
Maximum of Months | 2010.83 | 1007.22 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 944.37 | 2290.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 606.51 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.76 | 16-JAN-12:50 | 1194.01 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 625.80 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.96 | 02-FEB-13:00 | 1526.64 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 590.15 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 207.38 | 05-MAR-12:40 | 1455.41 | 20-MAR-21:25 |
April | 1295.83 | 03-APR-09:09 | 599.95 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.63 | 23-APR-14:54 | 999.73 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 486.10 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.48 | 07-MAY-13:52 | 260.37 | 06-MAY-19:55 |
June | 1295.83 | 01-JUN-09:09 | 398.99 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.32 | 10-JUN-17:07 | 307.21 | 06-JUN-21:20 |
July | 1295.83 | 03-JUL-09:09 | 409.63 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.62 | 02-JUL-11:48 | 254.47 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 533.21 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.35 | 20-AUG-14:00 | 406.63 | 25-AUG-23:55 |
September | 1295.83 | 01-SEP-09:09 | 590.85 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 544.62 | 09-SEP-17:10 | 420.67 | 05-SEP-02:53 |
October | 1295.83 | 02-OCT-09:09 | 659.56 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 670.68 | 09-OCT-13:53 | 679.64 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 639.30 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.06 | 11-NOV-11:50 | 1015.28 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 648.06 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.26 | 10-DEC-11:30 | 1332.37 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 398.99 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 78.76 | 254.47 | |||||
Maximum of Months | 1295.83 | 659.56 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 670.68 | 1526.64 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.42 | 16-JAN-15:00 | 1511.05 | 26-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 02-FEB-13:00 | 2182.52 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.83 | 26-MAR-14:00 | 1840.75 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.48 | 29-APR-17:01 | 1073.82 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.72 | 21-MAY-14:00 | 174.87 | 14-MAY-12:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.44 | 10-JUN-17:02 | 281.78 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.46 | 22-JUL-18:53 | 112.44 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.12 | 20-AUG-14:00 | 390.65 | 25-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.56 | 09-SEP-17:02 | 375.17 | 05-SEP-02:57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.23 | 09-OCT-13:51 | 903.16 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.97 | 05-NOV-13:00 | 1280.14 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.41 | 10-DEC-14:51 | 2018.14 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.42 | 112.44 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.23 | 2182.52 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.91 | 16-JAN-15:00 | 2601.76 | 21-JAN-05:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.42 | 20-FEB-14:53 | 3732.14 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.05 | 05-MAR-13:00 | 3142.45 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.09 | 29-APR-17:01 | 1784.38 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.75 | 21-MAY-14:00 | 290.59 | 14-MAY-12:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.42 | 10-JUN-17:02 | 479.39 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 943.99 | 22-JUL-18:53 | 204.40 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.89 | 20-AUG-14:00 | 721.64 | 25-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1207.02 | 09-SEP-17:02 | 599.26 | 05-SEP-02:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.03 | 09-OCT-14:00 | 1521.96 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.61 | 05-NOV-13:00 | 2188.96 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.25 | 10-DEC-15:00 | 3400.77 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.91 | 204.40 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.03 | 3732.14 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.39 | 16-JAN-15:00 | 2571.53 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.78 | 02-FEB-13:00 | 3368.91 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.81 | 05-MAR-12:55 | 3290.77 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.45 | 29-APR-17:01 | 1997.56 | 01-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.90 | 07-MAY-14:00 | 583.47 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 968.72 | 10-JUN-17:02 | 504.58 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.14 | 02-JUL-10:53 | 569.49 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.37 | 20-AUG-14:00 | 788.33 | 25-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.45 | 09-SEP-22:53 | 789.72 | 05-SEP-02:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.95 | 08-OCT-14:00 | 1411.41 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.09 | 05-NOV-12:52 | 2259.37 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.87 | 10-DEC-15:00 | 3133.40 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.78 | 504.58 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.45 | 3368.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 100389.24 | 09-JAN-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 101761.78 | 13-FEB-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 102273.27 | 20-MAR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 101596.78 | 17-APR-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74422.79 | 29-MAY-18:50 | 0.00 | 2826.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76867.29 | 12-JUN-03:02 | 0.00 | 2826.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73797.60 | 25-JUL-03:02 | 0.00 | 2826.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78181.38 | 28-AUG-03:02 | 0.00 | 3391.28 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76867.75 | 05-SEP-04:23 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97383.83 | 17-OCT-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98018.34 | 14-NOV-05:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 100547.99 | 26-DEC-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 73797.60 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102273.27 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84197.76 | 02-JAN-05:14 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86975.84 | 27-FEB-05:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82946.94 | 30-MAR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82662.20 | 04-APR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81174.35 | 16-MAY-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84051.95 | 01-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73687.97 | 24-JUL-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75624.07 | 07-AUG-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83872.84 | 22-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87354.71 | 02-OCT-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86186.58 | 13-NOV-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85415.91 | 26-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 73687.97 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87354.71 | 9673.43 | 3761.52 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 71078.18 | 02-JAN-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72117.45 | 27-FEB-06:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71138.87 | 29-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71652.15 | 14-APR-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70176.17 | 17-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72613.14 | 07-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69603.24 | 12-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71846.21 | 17-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71237.92 | 28-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72628.96 | 17-OCT-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72900.24 | 08-NOV-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71060.55 | 14-DEC-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 69603.24 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72900.24 | 8061.19 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 68060.47 | 02-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67175.00 | 03-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70037.88 | 27-MAR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71987.21 | 26-APR-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73320.11 | 31-MAY-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71597.80 | 07-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70927.33 | 12-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70329.09 | 26-AUG-04:02 | 0.00 | 2538.01 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72365.21 | 28-SEP-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71072.37 | 02-OCT-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 69603.10 | 03-NOV-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67472.98 | 15-DEC-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 67175.00 | 0.00 | 2149.44 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73320.11 | 8061.19 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8168.35 | 02-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 |
February | 7277.06 | 27-FEB-05:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8959.58 | 27-MAR-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 |
April | 8901.00 | 26-APR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 | 0.00 |
May | 13839.86 | 07-MAY-14:42 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 124.56 | 0.00 |
June | 11852.75 | 01-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15188.76 | 02-JUL-15:32 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.76 | 0.00 |
August | 13978.52 | 13-AUG-16:22 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 | 0.00 |
September | 11970.26 | 06-SEP-03:02 | 0.00 | 318.67 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 |
October | 14901.05 | 08-OCT-13:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 254.39 | 0.00 |
November | 10947.35 | 02-NOV-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
December | 7328.47 | 11-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7277.06 | 0.00 | 151.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15188.76 | 1923.11 | 545.86 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 254.39 | 26.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16181.85 | 01-JAN-10:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.99 |
February | 11893.63 | 26-FEB-11:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 |
March | 17576.05 | 26-MAR-09:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 |
April | 17524.62 | 23-APR-07:53 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.40 |
May | 18963.41 | 14-MAY-08:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
June | 17436.51 | 04-JUN-09:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 | 0.00 |
July | 17601.14 | 09-JUL-09:02 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 55.88 | 0.00 |
August | 16092.80 | 06-AUG-09:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 32.39 | 0.00 |
September | 18968.24 | 24-SEP-09:32 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 0.00 |
October | 17718.60 | 15-OCT-08:43 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.23 |
November | 17395.89 | 11-NOV-09:23 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.78 |
December | 14330.37 | 10-DEC-10:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11893.63 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18968.24 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 55.88 | 105.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22906.72 | 01-JAN-13:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.30 |
February | 21347.51 | 26-FEB-13:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.86 |
March | 20079.33 | 05-MAR-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
April | 14629.76 | 23-APR-12:33 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 0.00 |
May | 18741.38 | 07-MAY-14:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 123.02 | 0.00 |
June | 13924.72 | 26-JUN-05:02 | 1012.19 | 337.36 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
July | 18904.83 | 02-JUL-15:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 | 0.00 |
August | 19040.09 | 27-AUG-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 113.39 | 0.00 |
September | 20106.27 | 03-SEP-13:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 0.00 |
October | 21499.87 | 15-OCT-13:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 | 0.00 |
November | 22188.74 | 11-NOV-13:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.54 |
December | 22407.76 | 10-DEC-12:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13924.72 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22906.72 | 1012.19 | 337.36 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 123.02 | 81.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23457.23 | 01-JAN-15:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 |
February | 22725.05 | 26-FEB-15:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
March | 21167.69 | 26-MAR-15:32 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 |
April | 23485.85 | 23-APR-16:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 |
May | 23471.22 | 28-MAY-16:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.49 | 0.00 |
June | 23512.99 | 04-JUN-16:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 0.00 |
July | 23627.09 | 30-JUL-16:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 |
August | 22793.51 | 06-AUG-16:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.86 |
September | 24307.61 | 24-SEP-16:11 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 0.00 |
October | 22925.95 | 08-OCT-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 132.33 | 0.00 |
November | 23528.68 | 05-NOV-14:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 |
December | 24523.34 | 10-DEC-15:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21167.69 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24523.34 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.33 | 37.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4908.68 | 02-JAN-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 | 0.00 |
February | 5193.86 | 28-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 0.00 |
March | 6738.93 | 30-MAR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 50.32 | 0.00 |
April | 8633.09 | 29-APR-05:03 | 809.73 | 509.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 |
May | 11275.05 | 30-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14326.72 | 11-JUN-17:21 | 0.00 | 242.60 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 237.61 | 0.00 |
July | 14116.80 | 04-JUL-16:42 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 284.66 | 0.00 |
August | 12963.88 | 21-AUG-03:02 | 0.00 | 382.41 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 0.00 |
September | 14442.94 | 10-SEP-14:31 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 280.33 | 0.00 |
October | 9930.41 | 10-OCT-04:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.44 |
November | 9699.76 | 03-NOV-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5619.61 | 15-DEC-14:05 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4908.68 | 0.00 | 151.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14442.94 | 4021.58 | 1091.73 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 284.66 | 285.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8515.06 | 19-JAN-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 0.00 |
February | 9231.37 | 27-FEB-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 |
March | 17836.15 | 26-MAR-10:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 |
April | 18533.61 | 23-APR-09:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 |
May | 20106.58 | 14-MAY-09:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 0.00 |
June | 18828.40 | 11-JUN-08:62 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.52 |
July | 18585.88 | 23-JUL-09:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 0.00 |
August | 18309.57 | 06-AUG-08:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 51.82 | 0.00 |
September | 20105.30 | 03-SEP-08:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 0.00 |
October | 19702.04 | 09-OCT-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 |
November | 15424.61 | 11-NOV-10:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 |
December | 10207.59 | 10-DEC-11:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8515.06 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20106.58 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 51.82 | 110.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20323.28 | 01-JAN-13:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 |
February | 19568.68 | 26-FEB-11:32 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.74 |
March | 19280.86 | 05-MAR-13:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 | 0.00 |
April | 12629.96 | 23-APR-13:33 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 58.14 | 0.00 |
May | 13108.03 | 03-MAY-04:12 | 0.00 | 404.83 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.90 |
June | 13785.27 | 26-JUN-05:02 | 1012.19 | 337.36 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 0.00 |
July | 17241.91 | 09-JUL-14:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 168.75 | 0.00 |
August | 16842.12 | 06-AUG-12:32 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 268.90 | 0.00 |
September | 20133.70 | 10-SEP-14:31 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 | 0.00 |
October | 20776.04 | 01-OCT-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.69 |
November | 21812.98 | 11-NOV-13:31 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.22 |
December | 22277.23 | 10-DEC-13:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12629.96 | 0.00 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22277.23 | 1012.19 | 404.83 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 268.90 | 218.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14119.22 | 01-JAN-17:03 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 |
February | 20154.00 | 26-FEB-17:32 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.63 |
March | 16030.07 | 05-MAR-16:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.66 |
April | 20821.61 | 16-APR-16:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.39 |
May | 20437.72 | 29-MAY-16:12 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 120.18 | 0.00 |
June | 21899.98 | 11-JUN-17:21 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 101.27 | 0.00 |
July | 19729.66 | 16-JUL-15:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 246.12 | 0.00 |
August | 17528.24 | 07-AUG-03:02 | 0.00 | 246.44 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 0.00 |
September | 21837.94 | 03-SEP-15:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 150.34 | 0.00 |
October | 20927.79 | 09-OCT-16:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 |
November | 19972.98 | 11-NOV-15:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 |
December | 19941.82 | 10-DEC-15:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14119.22 | 0.00 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21899.98 | 521.82 | 246.44 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 246.12 | 506.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5117.66 | 31-JAN-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 | 0.00 |
February | 5572.84 | 22-FEB-14:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 0.00 |
March | 7208.56 | 30-MAR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 60.95 | 0.00 |
April | 8901.26 | 28-APR-15:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 188.11 | 0.00 |
May | 16588.55 | 29-MAY-14:42 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.64 | 0.00 |
June | 17046.92 | 11-JUN-17:21 | 0.00 | 242.60 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 258.28 | 0.00 |
July | 16579.98 | 04-JUL-16:42 | 506.08 | 151.62 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 307.86 | 0.00 |
August | 16307.81 | 20-AUG-14:12 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 732.71 | 0.00 |
September | 17234.90 | 10-SEP-14:31 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 322.22 | 0.00 |
October | 16837.32 | 08-OCT-13:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 632.36 | 0.00 |
November | 9477.66 | 03-NOV-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6165.33 | 15-DEC-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5117.66 | 0.00 | 151.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17234.90 | 2010.79 | 545.86 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 732.71 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6983.78 | 19-JAN-10:20 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 |
February | 7499.19 | 27-FEB-10:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 |
March | 11706.57 | 26-MAR-09:13 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.04 |
April | 18817.68 | 23-APR-09:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.24 |
May | 21185.53 | 29-MAY-10:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
June | 19139.94 | 11-JUN-08:62 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.85 |
July | 19032.38 | 23-JUL-09:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 0.00 |
August | 18687.05 | 06-AUG-08:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 58.74 | 0.00 |
September | 20484.99 | 03-SEP-08:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 32.05 | 0.00 |
October | 20097.43 | 09-OCT-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.51 |
November | 11558.52 | 11-NOV-09:43 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.43 |
December | 6975.23 | 10-DEC-10:43 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6975.23 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21185.53 | 1295.83 | 351.77 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 58.74 | 143.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24854.72 | 01-JAN-14:01 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.81 |
February | 23011.79 | 26-FEB-14:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.88 |
March | 21161.47 | 05-MAR-13:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 0.00 |
April | 16370.41 | 23-APR-13:33 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 56.48 | 0.00 |
May | 20502.38 | 29-MAY-14:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 151.92 | 0.00 |
June | 20445.16 | 11-JUN-16:01 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 162.63 | 0.00 |
July | 20187.94 | 09-JUL-14:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 180.05 | 0.00 |
August | 20419.67 | 27-AUG-12:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 307.77 | 0.00 |
September | 23019.05 | 10-SEP-14:31 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 274.77 | 0.00 |
October | 23663.83 | 08-OCT-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 366.31 | 0.00 |
November | 23124.18 | 05-NOV-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 |
December | 22493.87 | 10-DEC-14:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16370.41 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24854.72 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 366.31 | 136.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21034.49 | 01-JAN-15:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.62 |
February | 22035.62 | 26-FEB-16:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.59 |
March | 18307.64 | 26-MAR-15:13 | 260.91 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.80 |
April | 21535.74 | 23-APR-16:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 |
May | 22325.15 | 29-MAY-16:41 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 111.08 | 0.00 |
June | 23905.70 | 11-JUN-17:21 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 110.23 | 0.00 |
July | 21168.61 | 16-JUL-15:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 285.19 | 0.00 |
August | 20390.21 | 20-AUG-16:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 157.81 | 0.00 |
September | 23909.97 | 03-SEP-15:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 162.22 | 0.00 |
October | 22853.09 | 01-OCT-15:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.44 |
November | 21120.67 | 05-NOV-15:42 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
December | 16690.96 | 10-DEC-15:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16690.96 | 0.00 | 78.17 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23909.97 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 285.19 | 165.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11431.37 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 |
February | 7259.44 | 27-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 |
March | 6378.88 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 |
April | 6508.12 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
May | 9311.33 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8859.71 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
July | 10723.15 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 0.00 |
August | 10014.19 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 0.00 |
September | 10755.25 | 11-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 9638.47 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.60 |
November | 8061.94 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
December | 6586.65 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6378.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11431.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 274.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6879.02 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.07 |
February | 6252.11 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.47 |
March | 4351.55 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.04 |
April | 5273.75 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 |
May | 6998.51 | 03-MAY-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.23 | 0.00 |
June | 6683.54 | 27-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
July | 7066.13 | 01-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 |
August | 5918.43 | 30-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.67 | 0.00 |
September | 8166.78 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 |
October | 7914.22 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.22 |
November | 4710.32 | 06-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 0.00 |
December | 5982.38 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4351.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8166.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.67 | 571.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8976.59 | 19-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 |
February | 11082.53 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
March | 10702.72 | 06-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 | 0.00 |
April | 15593.71 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.30 | 0.00 |
May | 21132.46 | 08-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.13 | 0.00 |
June | 19580.76 | 08-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.72 | 0.00 |
July | 17655.94 | 07-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.46 | 0.00 |
August | 16962.02 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.52 | 0.00 |
September | 15626.96 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.43 | 0.00 |
October | 15416.72 | 05-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.13 | 0.00 |
November | 12059.36 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.56 | 0.00 |
December | 10819.25 | 15-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8976.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21132.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.52 | 31.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2153.84 | 01-JAN-17:12 | 46.77 | 32.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4198.55 | 26-FEB-17:54 | 58.46 | 40.65 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7164.26 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7989.48 | 16-APR-18:20 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3450.02 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5326.41 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7201.91 | 31-JUL-23:55 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7780.83 | 06-AUG-18:00 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3472.55 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5327.92 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6014.84 | 12-NOV-17:10 | 23.38 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7881.62 | 10-DEC-16:53 | 70.15 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2153.84 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7989.48 | 70.15 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1795.43 | 01-JAN-17:25 | 46.77 | 32.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3840.77 | 26-FEB-17:54 | 58.46 | 40.65 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6688.59 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7484.34 | 16-APR-18:20 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3224.12 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5143.36 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6895.06 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7255.41 | 06-AUG-17:40 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3201.26 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4919.07 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5574.67 | 06-NOV-17:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7293.24 | 15-DEC-17:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1795.43 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7484.34 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1873.38 | 01-JAN-17:12 | 46.77 | 32.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3889.11 | 26-FEB-17:43 | 70.15 | 48.78 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6592.86 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7684.29 | 23-APR-17:53 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3196.11 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5179.29 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6886.20 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7529.91 | 06-AUG-17:40 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3226.95 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4850.49 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5634.82 | 06-NOV-17:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7357.72 | 15-DEC-17:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1873.38 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7684.29 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92414.33 | 02-JAN-14:40 | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182989.29 | 27-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358132.21 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367507.40 | 18-APR-16:05 | 3037.06 | 3187.40 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175300.28 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266915.32 | 30-JUN-24:00 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359206.29 | 31-JUL-23:55 | 0.00 | 318.73 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370273.17 | 09-AUG-21:14 | 1265.44 | 1593.66 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176353.33 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268263.94 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275826.39 | 06-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367285.59 | 26-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92414.33 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370273.17 | 5027.92 | 3187.40 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.140157E+13 | 1137367.16 | 19-JAN-16:40 | 0.844033E+11 | 420754.96 | 23-JAN-06:10 |
February | 0.166272E+13 | 1295279.61 | 27-FEB-16:49 | 0.659341E+11 | 487423.11 | 06-FEB-06:10 |
March | 0.229342E+13 | 1435753.91 | 29-MAR-15:30 | 0.702644E+11 | 399917.86 | 11-MAR-06:10 |
April | 0.271439E+13 | 1604210.16 | 28-APR-15:00 | 0.534248E+11 | 118006.72 | 18-APR-14:20 |
May | 0.184330E+13 | 1248950.56 | 03-MAY-12:30 | 0.536083E+11 | 67295.98 | 09-MAY-11:20 |
June | 0.222282E+13 | 1313000.21 | 28-JUN-15:09 | 0.506235E+11 | 64098.75 | 06-JUN-11:39 |
July | 0.268546E+13 | 1479149.93 | 18-JUL-15:30 | 0.488411E+11 | 61920.46 | 03-JUL-11:39 |
August | 0.313650E+13 | 1628470.72 | 03-AUG-15:30 | 0.518580E+11 | 62569.74 | 25-AUG-11:20 |
September | 0.178182E+13 | 1154546.03 | 01-SEP-15:09 | 0.497641E+11 | 64999.44 | 19-SEP-11:00 |
October | 0.215743E+13 | 1321211.05 | 06-OCT-15:09 | 0.536614E+11 | 69169.43 | 25-OCT-11:30 |
November | 0.225740E+13 | 1436772.08 | 02-NOV-15:09 | 0.555800E+11 | 107843.87 | 16-NOV-06:10 |
December | 0.260499E+13 | 1569295.52 | 14-DEC-16:10 | 0.739192E+11 | 444098.91 | 21-DEC-07:10 |
Annual Sum or Average | 0.267618E+14 | 0.711882E+12 | ||||
Minimum of Months | 0.140157E+13 | 1137367.16 | 0.488411E+11 | 61920.46 | ||
Maximum of Months | 0.313650E+13 | 1628470.72 | 0.844033E+11 | 487423.11 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.348992E+11 | 62801.03 | 23-JAN-12:50 | 0.00 | 0.00 |
February | 0.389133E+11 | 72705.70 | 13-FEB-12:30 | 0.00 | 0.00 |
March | 0.458785E+11 | 84375.12 | 22-MAR-12:30 | 0.00 | 0.00 |
April | 0.547081E+11 | 86329.64 | 10-APR-12:30 | 0.00 | 0.00 |
May | 0.530214E+11 | 83915.95 | 15-MAY-12:30 | 0.00 | 0.00 |
June | 0.562117E+11 | 84613.62 | 09-JUN-12:30 | 0.00 | 0.00 |
July | 0.546688E+11 | 79965.54 | 06-JUL-12:39 | 0.00 | 0.00 |
August | 0.516110E+11 | 80137.75 | 03-AUG-12:30 | 0.00 | 0.00 |
September | 0.433131E+11 | 74836.43 | 03-SEP-12:30 | 0.00 | 0.00 |
October | 0.429860E+11 | 71885.92 | 01-OCT-12:30 | 0.00 | 0.00 |
November | 0.348223E+11 | 64831.49 | 15-NOV-12:20 | 0.00 | 0.00 |
December | 0.316676E+11 | 57802.88 | 26-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.542701E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.316676E+11 | 57802.88 | 0.00 | 0.00 | |
Maximum of Months | 0.562117E+11 | 86329.64 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.144132E+12 | 0.273830E+11 | 0.766053E+12 | 0.102194E+12 | 0.155049E+12 | 0.314002E+11 | 0.00 | 0.840496E+11 | 0.410433E+11 | 0.482065E+11 | 0.206055E+10 | 0.00 | 0.00 |
February | 0.130110E+12 | 0.228767E+11 | 0.978954E+12 | 0.923108E+11 | 0.142223E+12 | 0.342773E+11 | 0.00 | 0.145159E+12 | 0.584184E+11 | 0.559137E+11 | 0.247811E+10 | 0.00 | 0.00 |
March | 0.153910E+12 | 0.228740E+11 | 0.141687E+13 | 0.102362E+12 | 0.160456E+12 | 0.417905E+11 | 0.00 | 0.233590E+12 | 0.845625E+11 | 0.744739E+11 | 0.252693E+10 | 0.00 | 0.00 |
April | 0.137139E+12 | 0.198050E+11 | 0.165903E+13 | 0.988820E+11 | 0.161678E+12 | 0.533269E+11 | 0.00 | 0.430654E+12 | 0.130007E+12 | 0.199018E+11 | 0.396739E+10 | 0.00 | 0.00 |
May | 0.147282E+12 | 0.183091E+11 | 0.774844E+12 | 0.102278E+12 | 0.181976E+12 | 0.615864E+11 | 0.00 | 0.375555E+12 | 0.175379E+12 | 0.00 | 0.608670E+10 | 0.00 | 0.00 |
June | 0.146295E+12 | 0.166074E+11 | 0.106252E+13 | 0.990391E+11 | 0.180470E+12 | 0.668417E+11 | 0.00 | 0.469603E+12 | 0.175359E+12 | 0.00 | 0.608670E+10 | 0.00 | 0.00 |
July | 0.137189E+12 | 0.178700E+11 | 0.139340E+13 | 0.102120E+12 | 0.182986E+12 | 0.730666E+11 | 0.00 | 0.583960E+12 | 0.189092E+12 | 0.00 | 0.577748E+10 | 0.00 | 0.00 |
August | 0.153080E+12 | 0.195477E+11 | 0.173200E+13 | 0.102362E+12 | 0.189495E+12 | 0.760738E+11 | 0.00 | 0.668553E+12 | 0.189054E+12 | 1328817.66 | 0.633082E+10 | 0.00 | 0.00 |
September | 0.137377E+12 | 0.210774E+11 | 0.740713E+12 | 0.988812E+11 | 0.173386E+12 | 0.612057E+11 | 0.00 | 0.370280E+12 | 0.173126E+12 | 0.00 | 0.577748E+10 | 0.00 | 0.00 |
October | 0.143179E+12 | 0.242140E+11 | 0.108340E+13 | 0.102194E+12 | 0.180843E+12 | 0.608732E+11 | 0.00 | 0.389720E+12 | 0.152274E+12 | 0.159977E+11 | 0.473591E+10 | 0.00 | 0.00 |
November | 0.142385E+12 | 0.257752E+11 | 0.135889E+13 | 0.989455E+11 | 0.160573E+12 | 0.460388E+11 | 0.00 | 0.275286E+12 | 0.999375E+11 | 0.471324E+11 | 0.243079E+10 | 0.00 | 0.00 |
December | 0.140028E+12 | 0.279985E+11 | 0.170972E+13 | 0.102120E+12 | 0.158937E+12 | 0.394242E+11 | 0.00 | 0.263840E+12 | 0.835968E+11 | 0.769723E+11 | 0.235349E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171211E+13 | 0.264338E+12 | 0.146764E+14 | 0.120369E+13 | 0.202807E+13 | 0.645906E+12 | 0.00 | 0.429025E+13 | 0.155185E+13 | 0.338600E+12 | 0.506124E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130110E+12 | 0.166074E+11 | 0.740713E+12 | 0.923108E+11 | 0.142223E+12 | 0.314002E+11 | 0.00 | 0.840496E+11 | 0.410433E+11 | 0.00 | 0.206055E+10 | 0.00 | 0.00 |
Maximum of Months | 0.153910E+12 | 0.279985E+11 | 0.173200E+13 | 0.102362E+12 | 0.189495E+12 | 0.760738E+11 | 0.00 | 0.668553E+12 | 0.189092E+12 | 0.769723E+11 | 0.633082E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.255229E+11 | 0.00 | 0.588805E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.128096E+11 | 0.00 | 0.531245E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.106280E+11 | 0.00 | 0.596364E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.239679E+09 | 0.00 | 0.531851E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.536083E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.506235E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.488411E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.518580E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.497641E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 42109672.15 | 0.00 | 0.536192E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.898335E+09 | 0.00 | 0.546816E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.168595E+11 | 0.00 | 0.570597E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.670001E+11 | 0.00 | 0.644882E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.488411E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.255229E+11 | 0.00 | 0.596364E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 160318.72 | 31-JAN-08:09 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73695.70 | 31-JAN-08:20 | 131021.01 | 19-JAN-16:40 | 57103.63 | 19-JAN-16:40 | 0.00 | 01-JAN-00:10 |
February | 162006.23 | 01-FEB-08:09 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73696.59 | 01-FEB-08:20 | 143288.51 | 27-FEB-16:49 | 57350.74 | 27-FEB-16:49 | 0.00 | 01-FEB-00:10 |
March | 158764.49 | 27-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73694.89 | 27-MAR-07:19 | 113688.48 | 07-MAR-06:10 | 50276.81 | 07-MAR-11:50 | 0.00 | 01-MAR-00:10 |
April | 160200.83 | 14-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73695.64 | 14-APR-07:19 | 145236.34 | 18-APR-14:20 | 50702.25 | 27-APR-10:50 | 0.00 | 01-APR-00:10 |
May | 150024.83 | 23-MAY-07:30 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73690.30 | 23-MAY-07:40 | 255581.86 | 03-MAY-12:30 | 57427.71 | 08-MAY-13:39 | 0.00 | 01-MAY-00:10 |
June | 147076.19 | 16-JUN-07:10 | 31088.59 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 73688.76 | 16-JUN-07:19 | 165597.38 | 08-JUN-14:30 | 57261.45 | 01-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 148381.65 | 14-JUL-07:10 | 31088.59 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 73689.44 | 14-JUL-07:19 | 126749.37 | 07-JUL-15:00 | 50441.00 | 24-JUL-07:30 | 0.00 | 01-JUL-00:10 |
August | 150535.37 | 21-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73690.57 | 21-AUG-07:19 | 144054.57 | 15-AUG-10:30 | 57456.38 | 15-AUG-10:30 | 0.00 | 01-AUG-00:10 |
September | 158758.58 | 26-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73694.88 | 26-SEP-07:19 | 126906.44 | 01-SEP-14:00 | 57490.94 | 25-SEP-10:39 | 0.00 | 01-SEP-00:10 |
October | 164275.09 | 25-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73697.78 | 25-OCT-07:19 | 135550.30 | 11-OCT-15:30 | 57493.23 | 23-OCT-09:30 | 0.00 | 01-OCT-00:10 |
November | 161990.68 | 21-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73696.41 | 01-NOV-07:19 | 132518.81 | 06-NOV-16:19 | 57254.33 | 29-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 163894.04 | 12-DEC-08:09 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73697.58 | 12-DEC-08:20 | 124324.51 | 15-DEC-15:30 | 50666.79 | 12-DEC-13:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 147076.19 | 31088.59 | 423497.50 | 73688.76 | 113688.48 | 50276.81 | 0.00 | |||||||
Maximum of Months | 164275.09 | 31088.59 | 778371.69 | 73697.78 | 255581.86 | 57493.23 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 264276.26 | 19-JAN-11:00 | 81663.54 | 02-JAN-11:30 | 100000.00 | 06-JAN-12:00 | 4520.72 | 02-JAN-10:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 301723.40 | 24-FEB-10:39 | 81663.54 | 01-FEB-13:50 | 100000.00 | 04-FEB-17:10 | 4520.72 | 01-FEB-11:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 349223.40 | 30-MAR-12:00 | 81663.54 | 06-MAR-09:39 | 100000.00 | 03-MAR-22:10 | 4520.72 | 04-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 381769.27 | 28-APR-11:50 | 81663.54 | 04-APR-15:39 | 100000.00 | 10-APR-04:19 | 4520.72 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 303897.87 | 10-MAY-15:00 | 81663.54 | 01-MAY-06:19 | 0.00 | 01-MAY-00:10 | 4520.72 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 329057.00 | 16-JUN-16:00 | 81663.54 | 01-JUN-06:49 | 0.00 | 01-JUN-00:10 | 4520.72 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 379739.99 | 05-JUL-12:09 | 81663.54 | 01-JUL-06:30 | 0.00 | 01-JUL-00:10 | 4520.72 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 395912.86 | 10-AUG-12:09 | 81663.54 | 01-AUG-06:19 | 1230.55 | 20-AUG-14:09 | 4520.72 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 300121.13 | 01-SEP-12:09 | 81663.54 | 01-SEP-06:19 | 0.00 | 01-SEP-00:10 | 4520.72 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 338325.47 | 06-OCT-14:09 | 81663.54 | 02-OCT-09:39 | 100000.00 | 27-OCT-04:30 | 4520.72 | 02-OCT-08:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 346315.36 | 02-NOV-13:20 | 81663.54 | 01-NOV-06:19 | 100000.00 | 09-NOV-05:30 | 4520.72 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 377967.77 | 14-DEC-15:09 | 81663.54 | 08-DEC-15:50 | 100000.00 | 06-DEC-05:30 | 4520.72 | 02-DEC-13:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 264276.26 | 81663.54 | 0.00 | 4520.72 | 0.00 | 0.00 | |||||
Maximum of Months | 395912.86 | 81663.54 | 100000.00 | 4520.72 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1137367.16 | 19-JAN-16:40 | 146044.91 | 423497.50 | 0.00 | 52589.61 | 131021.01 | 57103.63 | 0.00 | 240926.25 | 81663.54 |
February | 1295279.61 | 27-FEB-16:49 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 143288.51 | 57350.74 | 0.00 | 268090.37 | 81663.54 |
March | 1435753.91 | 29-MAR-15:30 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 101330.87 | 48399.70 | 0.00 | 341181.96 | 81663.54 |
April | 1604210.16 | 28-APR-15:00 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 119889.50 | 47343.40 | 0.00 | 373844.49 | 81663.54 |
May | 1248950.56 | 03-MAY-12:30 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 255581.86 | 57045.66 | 0.00 | 256195.89 | 81663.54 |
June | 1313000.21 | 28-JUN-15:09 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 119965.66 | 47395.35 | 0.00 | 319089.22 | 81663.54 |
July | 1479149.93 | 18-JUL-15:30 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 124667.48 | 47505.09 | 0.00 | 362135.98 | 81663.54 |
August | 1628470.72 | 03-AUG-15:30 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 131212.37 | 47613.48 | 0.00 | 386512.09 | 81663.54 |
September | 1154546.03 | 01-SEP-15:09 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 125457.29 | 47425.35 | 0.00 | 273404.80 | 81663.54 |
October | 1321211.05 | 06-OCT-15:09 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 123587.45 | 47749.30 | 0.00 | 323324.31 | 81663.54 |
November | 1436772.08 | 02-NOV-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 118477.80 | 47155.39 | 0.00 | 326297.52 | 81663.54 |
December | 1569295.52 | 14-DEC-16:10 | 146638.83 | 778371.69 | 0.00 | 52589.61 | 105980.95 | 47022.27 | 0.00 | 352507.91 | 81663.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1137367.16 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 101330.87 | 47022.27 | 0.00 | 240926.25 | 81663.54 | |
Maximum of Months | 1628470.72 | 146638.83 | 778371.69 | 0.00 | 52589.61 | 255581.86 | 57350.74 | 0.00 | 386512.09 | 81663.54 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 410819.46 | 10-JAN-06:10 | 0.00 | 74963.99 | 27-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 463207.59 | 06-FEB-05:19 | 0.00 | 74904.20 | 01-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 374870.31 | 11-MAR-06:10 | 0.00 | 73556.25 | 07-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 85194.95 | 18-APR-14:20 | 0.00 | 71224.17 | 04-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 67295.98 | 09-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 64098.75 | 06-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 61920.46 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 62569.74 | 25-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 64999.44 | 19-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 6469.01 | 28-OCT-05:10 | 0.00 | 69169.43 | 25-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 79767.41 | 16-NOV-06:10 | 0.00 | 72693.89 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 436818.03 | 21-DEC-07:10 | 0.00 | 73987.51 | 18-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 61920.46 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 463207.59 | 0.00 | 74963.99 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.83 | 0.17 | 26.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.96 | 0.00 | 26.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.81 | 0.00 | 25.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.65 | 0.00 | 25.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.85 | 0.00 | 25.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.82 | 0.17 | 25.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.16 | 0.00 | 26.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.40 | 0.00 | 26.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.72 | 0.50 | 26.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.99 | 0.17 | 26.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.21 | 0.50 | 27.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.30 | 0.83 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 71.83 | 26.78 | 2.33 | 26.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.65 | 0.00 | 25.65 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.30 | 0.83 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.37 | 0.50 | 26.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.15 | 0.50 | 26.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 26.24 | 1.00 | 26.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.37 | 0.50 | 26.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.59 | 1.67 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.73 | 2.17 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.82 | 8.50 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.67 | 4.17 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.61 | 7.67 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.52 | 5.17 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.69 | 9.17 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.66 | 6.00 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.47 | 1.83 | 27.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 49.00 | 27.66 | 48.33 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.82 | 9.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.46 | 9.33 | 27.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.43 | 5.33 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.62 | 2.67 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.83 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.66 | 1.00 | 26.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.10 | 4.50 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.72 | 7.67 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.80 | 11.00 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 26.69 | 16.67 | 26.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.84 | 13.33 | 26.84 |
Annual Sum or Average | 0.00 | 0.00 | 76.17 | 27.22 | 72.50 | 27.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.80 | 16.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.75 | 3.17 | 27.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.59 | 3.50 | 27.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.46 | 3.83 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.44 | 8.00 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.03 | 6.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.10 | 9.33 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 27.34 | 15.17 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 27.43 | 15.00 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.28 | 8.17 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.29 | 10.00 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.39 | 7.50 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.55 | 7.50 | 27.70 |
Annual Sum or Average | 0.00 | 0.00 | 238.17 | 27.34 | 97.33 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.03 | 3.17 | 27.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 27.75 | 15.17 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 0.33 | 19.37 | 0.00 | 19.37 | 0.50 | 24.12 | 0.50 | 25.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.43 | 0.00 | 19.43 | 0.50 | 27.29 | 0.50 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.54 | 1.33 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.84 | 2.17 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.90 | 9.00 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.71 | 7.50 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.73 | 12.83 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.66 | 7.00 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.81 | 10.00 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.67 | 7.67 | 27.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.67 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 60.33 | 27.75 | 58.50 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.90 | 12.83 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.93 | 11.00 | 26.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.61 | 7.00 | 26.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.62 | 2.00 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.38 | 2.83 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.78 | 7.67 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 26.82 | 16.33 | 26.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 26.31 | 21.67 | 26.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 26.33 | 17.00 | 26.33 |
Annual Sum or Average | 0.00 | 0.00 | 88.17 | 26.73 | 86.33 | 26.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.78 | 21.67 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.03 | 0.67 | 28.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.72 | 1.67 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.83 | 3.50 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.84 | 3.67 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.60 | 3.83 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.43 | 8.00 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.32 | 4.33 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.79 | 5.67 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.86 | 5.17 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.64 | 2.17 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
Annual Sum or Average | 0.00 | 0.00 | 67.50 | 27.64 | 40.83 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.67 | 27.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.03 | 8.00 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 3.67 | 17.58 | 1.67 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
March | 0.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.35 | 2.33 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.49 | 2.67 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.45 | 6.50 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.44 | 3.67 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.53 | 2.17 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.45 | 2.17 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 18.97 | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
Annual Sum or Average | 8.67 | 18.37 | 1.83 | 18.18 | 24.67 | 24.68 | 19.50 | 25.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.14 | 1.67 | 19.14 | 8.50 | 27.53 | 6.50 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 1.83 | 17.93 | 0.33 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
March | 0.67 | 19.23 | 0.00 | 19.23 | 1.00 | 24.23 | 1.00 | 25.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.86 | 2.50 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.97 | 9.67 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.82 | 8.33 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.82 | 14.17 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.70 | 8.67 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.89 | 11.83 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.72 | 9.00 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.46 | 0.67 | 27.46 |
December | 1.17 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Annual Sum or Average | 5.67 | 18.70 | 0.33 | 18.49 | 74.83 | 27.13 | 65.83 | 27.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 0.00 | 17.46 |
Maximum of Months | 2.00 | 19.23 | 0.33 | 19.23 | 16.67 | 27.97 | 14.17 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.14 | 0.00 | 19.14 | 8.17 | 26.26 | 8.17 | 26.67 |
February | 0.67 | 17.87 | 0.17 | 17.30 | 2.67 | 25.19 | 2.67 | 26.26 |
March | 0.50 | 19.33 | 0.00 | 19.33 | 2.17 | 26.10 | 2.17 | 26.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.42 | 3.67 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.44 | 2.67 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.46 | 7.33 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.59 | 5.50 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.90 | 8.67 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.84 | 11.00 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.62 | 14.67 | 26.62 |
December | 0.50 | 18.85 | 0.00 | 18.85 | 7.00 | 27.02 | 7.00 | 27.30 |
Annual Sum or Average | 2.67 | 18.80 | 0.17 | 18.58 | 81.83 | 27.13 | 74.67 | 27.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.19 | 1.17 | 26.26 |
Maximum of Months | 1.00 | 19.33 | 0.17 | 19.33 | 14.67 | 27.90 | 14.67 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.15 | 0.00 | 19.15 | 0.83 | 22.70 | 0.83 | 24.16 |
February | 0.50 | 19.02 | 0.00 | 19.02 | 0.83 | 24.68 | 0.83 | 25.99 |
March | 0.17 | 19.41 | 0.00 | 19.41 | 2.00 | 27.15 | 1.67 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.92 | 3.33 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.82 | 5.17 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.65 | 5.67 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.55 | 9.67 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.43 | 6.17 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.89 | 7.17 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.92 | 6.00 | 28.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.77 | 1.67 | 27.77 |
December | 0.50 | 18.91 | 0.00 | 18.91 | 1.17 | 25.05 | 1.17 | 26.13 |
Annual Sum or Average | 2.33 | 19.09 | 0.00 | 19.09 | 84.17 | 27.48 | 49.33 | 27.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 22.70 | 0.83 | 24.16 |
Maximum of Months | 1.17 | 19.41 | 0.00 | 19.41 | 18.83 | 27.92 | 9.67 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.59 | 0.67 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.74 | 33.67 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.33 | 27.73 | 34.33 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.74 | 33.67 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.71 | 26.17 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.83 | 27.70 | 26.83 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.71 | 26.17 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.69 | 16.00 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.00 | 27.69 | 16.00 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.69 | 16.00 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 98.50 | 28.19 | 97.17 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 495.33 | 28.86 | 415.33 | 28.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 28.01 | 39.50 | 28.01 |
Annual Sum or Average | 0.00 | 0.00 | 633.33 | 28.70 | 552.00 | 28.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 495.33 | 28.86 | 415.33 | 28.93 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.67 | 24.31 | 228.00 | 24.87 | 43.17 | 24.84 |
February | 126.33 | 24.38 | 301.33 | 24.60 | 97.83 | 24.58 |
March | 148.17 | 24.38 | 302.67 | 24.55 | 113.83 | 24.54 |
April | 242.00 | 24.51 | 428.83 | 24.53 | 240.83 | 24.52 |
May | 418.83 | 24.58 | 508.00 | 24.53 | 418.83 | 24.54 |
June | 401.67 | 24.50 | 496.00 | 24.46 | 401.67 | 24.47 |
July | 293.83 | 24.97 | 497.00 | 24.72 | 293.83 | 24.79 |
August | 219.17 | 25.10 | 514.00 | 24.66 | 219.17 | 24.76 |
September | 241.33 | 25.09 | 485.00 | 24.73 | 241.33 | 24.82 |
October | 179.00 | 25.38 | 452.33 | 24.87 | 179.00 | 24.98 |
November | 80.50 | 25.27 | 373.50 | 24.87 | 80.50 | 24.93 |
December | 74.50 | 24.89 | 305.50 | 24.93 | 63.33 | 24.95 |
Annual Sum or Average | 2512.00 | 24.76 | 4892.17 | 24.66 | 2393.33 | 24.70 |
Minimum of Months | 74.50 | 24.31 | 228.00 | 24.46 | 43.17 | 24.47 |
Maximum of Months | 418.83 | 25.38 | 514.00 | 24.93 | 418.83 | 24.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 127.00 | 23.62 | 183.67 | 24.15 | 0.00 | 24.15 |
February | 56.17 | 23.73 | 257.83 | 24.25 | 0.00 | 24.25 |
March | 36.00 | 23.74 | 303.67 | 24.30 | 0.00 | 24.30 |
April | 0.00 | 0.00 | 421.00 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 483.50 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 479.83 | 24.14 | 0.00 | 24.14 |
July | 0.00 | 0.00 | 491.33 | 24.14 | 0.00 | 24.14 |
August | 0.00 | 0.00 | 514.00 | 24.11 | 0.00 | 24.11 |
September | 0.00 | 0.00 | 464.50 | 24.23 | 0.00 | 24.23 |
October | 0.33 | 23.94 | 446.33 | 24.30 | 0.00 | 24.30 |
November | 1.17 | 23.92 | 372.33 | 24.39 | 0.00 | 24.39 |
December | 14.33 | 23.78 | 294.17 | 24.44 | 0.00 | 24.44 |
Annual Sum or Average | 235.00 | 23.67 | 4712.17 | 24.23 | 0.00 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 183.67 | 24.11 | 0.00 | 24.11 |
Maximum of Months | 127.00 | 23.94 | 514.00 | 24.44 | 0.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 364.33 | 23.15 | 65.00 | 23.31 | 0.00 | 23.31 |
February | 246.00 | 23.14 | 112.33 | 23.46 | 0.00 | 23.46 |
March | 247.33 | 23.24 | 140.50 | 23.60 | 0.00 | 23.60 |
April | 76.83 | 23.36 | 228.50 | 24.09 | 0.00 | 24.09 |
May | 17.33 | 23.26 | 322.50 | 24.19 | 0.00 | 24.19 |
June | 15.00 | 23.27 | 300.50 | 24.17 | 0.00 | 24.17 |
July | 22.33 | 23.28 | 293.83 | 24.18 | 0.00 | 24.18 |
August | 11.50 | 23.27 | 329.67 | 24.20 | 0.00 | 24.20 |
September | 28.33 | 23.25 | 288.83 | 24.13 | 0.00 | 24.13 |
October | 40.17 | 23.33 | 295.67 | 24.17 | 0.00 | 24.17 |
November | 148.83 | 23.33 | 176.00 | 23.83 | 0.00 | 23.83 |
December | 258.00 | 23.13 | 106.67 | 23.47 | 0.00 | 23.47 |
Annual Sum or Average | 1476.00 | 23.20 | 2660.00 | 23.87 | 0.00 | 23.87 |
Minimum of Months | 11.50 | 23.13 | 65.00 | 23.31 | 0.00 | 23.31 |
Maximum of Months | 364.33 | 23.36 | 329.67 | 24.20 | 0.00 | 24.20 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.67 | 22.02 | 65.33 | 22.20 | 14.17 | 22.16 |
February | 323.67 | 22.28 | 99.50 | 22.51 | 18.00 | 22.39 |
March | 311.50 | 22.61 | 128.33 | 23.00 | 7.67 | 22.95 |
April | 108.50 | 23.22 | 240.50 | 23.95 | 0.00 | 23.95 |
May | 2.33 | 23.29 | 414.67 | 24.25 | 0.00 | 24.25 |
June | 0.00 | 0.00 | 421.50 | 24.22 | 0.00 | 24.22 |
July | 1.17 | 23.35 | 418.00 | 24.26 | 0.00 | 24.26 |
August | 0.00 | 0.00 | 424.33 | 24.25 | 0.00 | 24.25 |
September | 1.50 | 23.34 | 352.67 | 24.24 | 0.00 | 24.24 |
October | 63.83 | 22.98 | 326.33 | 24.09 | 0.00 | 24.09 |
November | 264.00 | 22.87 | 120.83 | 23.27 | 0.00 | 23.27 |
December | 371.67 | 22.32 | 78.00 | 22.56 | 9.83 | 22.51 |
Annual Sum or Average | 1860.83 | 22.45 | 3090.00 | 23.53 | 49.67 | 23.49 |
Minimum of Months | 0.00 | 0.00 | 65.33 | 22.20 | 0.00 | 22.16 |
Maximum of Months | 412.67 | 23.35 | 424.33 | 24.26 | 18.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.67 | 22.58 | 103.00 | 22.97 | 0.00 | 22.97 |
February | 219.83 | 22.79 | 145.17 | 23.31 | 4.33 | 23.27 |
March | 205.67 | 23.09 | 199.17 | 23.66 | 0.00 | 23.66 |
April | 33.17 | 23.54 | 355.50 | 24.14 | 0.00 | 24.14 |
May | 9.50 | 26.03 | 507.83 | 24.42 | 9.50 | 24.45 |
June | 1.67 | 26.84 | 495.83 | 24.33 | 1.67 | 24.34 |
July | 11.17 | 26.78 | 496.33 | 24.46 | 11.17 | 24.51 |
August | 9.33 | 26.79 | 514.00 | 24.32 | 9.33 | 24.37 |
September | 10.83 | 25.95 | 481.50 | 24.42 | 10.83 | 24.45 |
October | 37.17 | 23.83 | 421.83 | 24.34 | 4.83 | 24.36 |
November | 133.50 | 23.42 | 238.00 | 23.94 | 0.00 | 23.94 |
December | 224.00 | 23.00 | 165.33 | 23.51 | 0.00 | 23.51 |
Annual Sum or Average | 1236.50 | 23.07 | 4123.50 | 24.03 | 51.67 | 24.04 |
Minimum of Months | 1.67 | 22.58 | 103.00 | 22.97 | 0.00 | 22.97 |
Maximum of Months | 340.67 | 26.84 | 514.00 | 24.46 | 11.17 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.00 | 22.87 | 136.33 | 23.44 | 4.50 | 23.47 |
February | 177.83 | 22.97 | 180.67 | 23.65 | 3.83 | 23.65 |
March | 175.83 | 23.06 | 230.17 | 23.82 | 6.67 | 23.87 |
April | 50.33 | 23.89 | 352.33 | 24.24 | 7.67 | 24.29 |
May | 43.67 | 26.76 | 506.33 | 24.65 | 43.67 | 24.80 |
June | 22.00 | 26.87 | 494.00 | 24.47 | 22.00 | 24.57 |
July | 42.00 | 26.83 | 493.67 | 24.64 | 42.00 | 24.80 |
August | 23.33 | 26.83 | 505.67 | 24.40 | 23.33 | 24.50 |
September | 47.33 | 26.77 | 477.67 | 24.68 | 47.33 | 24.85 |
October | 58.00 | 25.25 | 425.17 | 24.56 | 32.33 | 24.70 |
November | 108.17 | 23.54 | 271.00 | 24.18 | 6.83 | 24.22 |
December | 211.50 | 22.87 | 165.50 | 23.53 | 2.17 | 23.55 |
Annual Sum or Average | 1231.00 | 23.69 | 4238.50 | 24.24 | 242.33 | 24.35 |
Minimum of Months | 22.00 | 22.87 | 136.33 | 23.44 | 2.17 | 23.47 |
Maximum of Months | 271.00 | 26.87 | 506.33 | 24.68 | 47.33 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 199.50 | 23.32 | 220.00 | 24.01 | 26.50 | 24.19 |
February | 129.67 | 23.30 | 258.83 | 24.05 | 18.33 | 24.12 |
March | 164.00 | 23.10 | 255.83 | 23.89 | 10.67 | 23.96 |
April | 39.33 | 23.77 | 364.33 | 24.25 | 3.83 | 24.27 |
May | 13.50 | 26.21 | 507.67 | 24.43 | 13.50 | 24.48 |
June | 2.17 | 26.88 | 494.00 | 24.32 | 2.17 | 24.33 |
July | 16.17 | 26.76 | 495.50 | 24.48 | 16.17 | 24.55 |
August | 21.17 | 26.80 | 514.00 | 24.40 | 21.17 | 24.49 |
September | 43.67 | 26.68 | 481.83 | 24.65 | 43.67 | 24.81 |
October | 63.67 | 25.99 | 453.17 | 24.73 | 46.00 | 24.91 |
November | 81.33 | 24.97 | 372.67 | 24.66 | 35.67 | 24.84 |
December | 156.00 | 23.76 | 286.33 | 24.33 | 31.33 | 24.51 |
Annual Sum or Average | 930.17 | 24.05 | 4704.17 | 24.37 | 269.00 | 24.48 |
Minimum of Months | 2.17 | 23.10 | 220.00 | 23.89 | 2.17 | 23.96 |
Maximum of Months | 199.50 | 26.88 | 514.00 | 24.73 | 46.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 195.50 | 23.51 | 217.33 | 24.07 | 12.17 | 24.15 |
February | 81.67 | 24.02 | 313.50 | 24.43 | 12.50 | 24.50 |
March | 54.83 | 24.80 | 365.33 | 24.60 | 18.00 | 24.70 |
April | 45.50 | 26.95 | 467.50 | 24.84 | 45.50 | 25.01 |
May | 45.67 | 26.83 | 508.00 | 24.75 | 45.67 | 24.91 |
June | 49.50 | 26.92 | 496.00 | 24.75 | 49.50 | 24.93 |
July | 81.17 | 26.91 | 497.00 | 24.99 | 81.17 | 25.22 |
August | 76.83 | 26.91 | 514.00 | 24.86 | 76.83 | 25.09 |
September | 56.17 | 26.86 | 485.00 | 24.82 | 56.17 | 25.01 |
October | 55.33 | 26.77 | 471.17 | 24.88 | 52.00 | 25.07 |
November | 34.33 | 26.62 | 423.00 | 24.79 | 29.83 | 24.93 |
December | 54.67 | 25.75 | 347.33 | 24.94 | 33.33 | 25.10 |
Annual Sum or Average | 831.17 | 25.58 | 5105.17 | 24.75 | 512.67 | 24.92 |
Minimum of Months | 34.33 | 23.51 | 217.33 | 24.07 | 12.17 | 24.15 |
Maximum of Months | 195.50 | 26.95 | 514.00 | 24.99 | 81.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.33 | 21.62 | 97.83 | 21.66 | 63.83 | 21.56 |
February | 361.83 | 21.92 | 96.33 | 21.98 | 44.33 | 21.81 |
March | 359.17 | 22.29 | 108.00 | 22.54 | 20.83 | 22.45 |
April | 168.17 | 23.22 | 235.83 | 23.80 | 11.33 | 23.85 |
May | 30.00 | 25.58 | 506.67 | 24.42 | 30.00 | 24.49 |
June | 13.83 | 25.98 | 492.83 | 24.40 | 13.67 | 24.44 |
July | 41.83 | 26.19 | 490.00 | 24.60 | 41.83 | 24.72 |
August | 27.67 | 25.71 | 508.83 | 24.41 | 27.67 | 24.47 |
September | 42.33 | 25.27 | 448.50 | 24.43 | 42.00 | 24.49 |
October | 116.00 | 23.68 | 374.50 | 24.18 | 34.67 | 24.27 |
November | 301.17 | 22.52 | 114.00 | 22.95 | 2.50 | 22.96 |
December | 401.17 | 21.91 | 87.67 | 22.12 | 29.33 | 22.06 |
Annual Sum or Average | 2307.50 | 22.44 | 3561.00 | 23.48 | 362.00 | 23.48 |
Minimum of Months | 13.83 | 21.62 | 87.67 | 21.66 | 2.50 | 21.56 |
Maximum of Months | 444.33 | 26.19 | 508.83 | 24.60 | 63.83 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.00 | 22.23 | 83.33 | 22.51 | 25.67 | 22.45 |
February | 237.17 | 22.37 | 105.33 | 22.74 | 21.83 | 22.64 |
March | 212.50 | 22.54 | 156.67 | 23.26 | 16.83 | 23.24 |
April | 87.67 | 23.91 | 270.17 | 24.35 | 22.67 | 24.47 |
May | 62.00 | 26.56 | 430.00 | 24.82 | 62.00 | 25.02 |
June | 44.00 | 26.71 | 416.00 | 24.73 | 44.00 | 24.91 |
July | 69.83 | 26.77 | 418.50 | 24.98 | 69.83 | 25.21 |
August | 50.67 | 26.49 | 430.50 | 24.71 | 50.67 | 24.88 |
September | 66.50 | 26.40 | 398.33 | 24.82 | 66.50 | 25.02 |
October | 99.67 | 24.80 | 340.17 | 24.64 | 52.67 | 24.84 |
November | 181.83 | 23.03 | 172.00 | 23.74 | 7.17 | 23.79 |
December | 287.83 | 22.32 | 105.17 | 22.72 | 22.33 | 22.69 |
Annual Sum or Average | 1727.67 | 23.36 | 3326.17 | 24.09 | 462.17 | 24.22 |
Minimum of Months | 44.00 | 22.23 | 83.33 | 22.51 | 7.17 | 22.45 |
Maximum of Months | 328.00 | 26.77 | 430.50 | 24.98 | 69.83 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 238.83 | 22.90 | 210.83 | 23.65 | 38.50 | 23.78 |
February | 178.83 | 22.81 | 222.00 | 23.66 | 22.17 | 23.69 |
March | 223.50 | 22.60 | 209.50 | 23.36 | 18.67 | 23.37 |
April | 110.17 | 23.45 | 300.00 | 24.11 | 14.67 | 24.17 |
May | 32.50 | 25.62 | 506.67 | 24.44 | 32.50 | 24.50 |
June | 14.00 | 25.75 | 491.00 | 24.37 | 13.50 | 24.41 |
July | 44.33 | 26.15 | 487.00 | 24.60 | 44.33 | 24.72 |
August | 41.50 | 26.10 | 511.00 | 24.50 | 41.50 | 24.61 |
September | 67.17 | 26.20 | 471.00 | 24.67 | 67.17 | 24.84 |
October | 90.50 | 25.52 | 440.83 | 24.74 | 62.33 | 24.94 |
November | 134.00 | 24.16 | 323.33 | 24.49 | 39.33 | 24.68 |
December | 209.50 | 23.09 | 246.33 | 23.92 | 39.17 | 24.08 |
Annual Sum or Average | 1384.83 | 23.66 | 4419.50 | 24.25 | 433.83 | 24.36 |
Minimum of Months | 14.00 | 22.60 | 209.50 | 23.36 | 13.50 | 23.37 |
Maximum of Months | 238.83 | 26.20 | 511.00 | 24.74 | 67.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 335.00 | 22.17 | 126.50 | 22.63 | 27.33 | 22.60 |
February | 229.33 | 22.31 | 177.50 | 22.99 | 20.67 | 22.89 |
March | 228.00 | 22.64 | 219.67 | 23.39 | 18.17 | 23.39 |
April | 73.33 | 24.42 | 368.33 | 24.44 | 25.50 | 24.56 |
May | 48.83 | 26.32 | 508.00 | 24.63 | 48.83 | 24.77 |
June | 36.00 | 26.76 | 495.00 | 24.62 | 36.00 | 24.76 |
July | 68.83 | 26.68 | 497.00 | 24.85 | 68.83 | 25.05 |
August | 45.00 | 26.57 | 514.00 | 24.64 | 45.00 | 24.78 |
September | 64.67 | 26.29 | 481.67 | 24.70 | 64.67 | 24.87 |
October | 86.83 | 25.04 | 430.83 | 24.59 | 51.67 | 24.75 |
November | 181.83 | 23.13 | 242.00 | 23.83 | 11.50 | 23.90 |
December | 274.00 | 22.36 | 179.33 | 23.10 | 15.67 | 23.11 |
Annual Sum or Average | 1671.67 | 23.32 | 4239.83 | 24.10 | 433.83 | 24.21 |
Minimum of Months | 36.00 | 22.17 | 126.50 | 22.63 | 11.50 | 22.60 |
Maximum of Months | 335.00 | 26.76 | 514.00 | 24.85 | 68.83 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.33 | 21.21 | 194.33 | 21.15 | 160.83 | 20.99 |
February | 378.50 | 21.54 | 143.83 | 21.51 | 92.50 | 21.27 |
March | 372.17 | 21.89 | 149.83 | 22.07 | 62.50 | 21.89 |
April | 187.50 | 22.93 | 233.00 | 23.65 | 11.50 | 23.70 |
May | 49.00 | 25.94 | 505.50 | 24.53 | 49.00 | 24.64 |
June | 32.00 | 26.20 | 491.67 | 24.51 | 30.50 | 24.61 |
July | 59.83 | 26.42 | 487.83 | 24.73 | 59.83 | 24.89 |
August | 49.83 | 26.03 | 505.17 | 24.52 | 49.83 | 24.65 |
September | 69.50 | 25.53 | 445.17 | 24.54 | 66.50 | 24.67 |
October | 135.33 | 23.50 | 371.33 | 24.12 | 46.83 | 24.21 |
November | 338.33 | 22.09 | 128.83 | 22.47 | 27.33 | 22.39 |
December | 413.33 | 21.48 | 169.33 | 21.55 | 115.00 | 21.40 |
Annual Sum or Average | 2539.67 | 22.26 | 3825.83 | 23.24 | 772.17 | 23.17 |
Minimum of Months | 32.00 | 21.21 | 128.83 | 21.15 | 11.50 | 20.99 |
Maximum of Months | 454.33 | 26.42 | 505.50 | 24.73 | 160.83 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.67 | 21.78 | 151.33 | 21.86 | 88.50 | 21.67 |
February | 297.00 | 21.95 | 145.17 | 22.20 | 47.83 | 21.97 |
March | 259.50 | 22.16 | 223.67 | 22.86 | 46.67 | 22.73 |
April | 108.67 | 23.50 | 328.67 | 24.17 | 22.83 | 24.27 |
May | 66.17 | 26.56 | 507.00 | 24.73 | 66.17 | 24.92 |
June | 51.17 | 26.63 | 492.67 | 24.66 | 49.83 | 24.84 |
July | 71.00 | 26.83 | 492.17 | 24.88 | 71.00 | 25.10 |
August | 57.33 | 26.45 | 510.50 | 24.64 | 57.33 | 24.80 |
September | 75.67 | 26.26 | 465.17 | 24.73 | 75.00 | 24.92 |
October | 127.17 | 24.42 | 403.50 | 24.48 | 60.33 | 24.67 |
November | 232.00 | 22.65 | 194.50 | 23.35 | 16.00 | 23.34 |
December | 360.17 | 21.88 | 159.67 | 22.21 | 61.33 | 22.07 |
Annual Sum or Average | 2117.50 | 22.93 | 4074.00 | 23.78 | 662.83 | 23.82 |
Minimum of Months | 51.17 | 21.78 | 145.17 | 21.86 | 16.00 | 21.67 |
Maximum of Months | 411.67 | 26.83 | 510.50 | 24.88 | 88.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.83 | 22.34 | 204.17 | 22.97 | 68.17 | 22.94 |
February | 213.33 | 22.26 | 218.50 | 23.04 | 42.33 | 22.92 |
March | 261.00 | 22.26 | 222.50 | 22.89 | 48.83 | 22.78 |
April | 139.50 | 23.16 | 289.67 | 23.97 | 17.17 | 24.05 |
May | 50.67 | 25.93 | 502.00 | 24.53 | 50.67 | 24.65 |
June | 31.50 | 26.06 | 489.67 | 24.48 | 29.50 | 24.57 |
July | 60.17 | 26.34 | 486.00 | 24.71 | 59.50 | 24.87 |
August | 52.67 | 26.18 | 508.50 | 24.56 | 52.67 | 24.70 |
September | 74.50 | 26.10 | 461.33 | 24.70 | 73.67 | 24.87 |
October | 100.50 | 25.08 | 432.00 | 24.66 | 62.83 | 24.87 |
November | 170.67 | 23.46 | 293.33 | 24.17 | 36.67 | 24.34 |
December | 244.33 | 22.49 | 247.67 | 23.32 | 59.67 | 23.32 |
Annual Sum or Average | 1672.67 | 23.30 | 4355.33 | 24.04 | 601.67 | 24.12 |
Minimum of Months | 31.50 | 22.26 | 204.17 | 22.89 | 17.17 | 22.78 |
Maximum of Months | 273.83 | 26.34 | 508.50 | 24.71 | 73.67 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 364.17 | 21.77 | 165.17 | 22.04 | 81.83 | 21.90 |
February | 263.33 | 21.93 | 181.67 | 22.42 | 53.17 | 22.22 |
March | 261.50 | 22.25 | 225.50 | 22.92 | 44.00 | 22.82 |
April | 107.00 | 23.84 | 346.00 | 24.30 | 26.33 | 24.43 |
May | 58.67 | 26.34 | 508.00 | 24.68 | 58.67 | 24.83 |
June | 47.17 | 26.73 | 493.00 | 24.68 | 47.17 | 24.85 |
July | 74.17 | 26.72 | 495.83 | 24.89 | 74.17 | 25.10 |
August | 56.50 | 26.56 | 513.83 | 24.68 | 56.50 | 24.85 |
September | 75.17 | 26.21 | 478.00 | 24.72 | 75.17 | 24.90 |
October | 101.00 | 24.66 | 421.17 | 24.53 | 55.17 | 24.70 |
November | 222.83 | 22.65 | 211.67 | 23.46 | 14.67 | 23.52 |
December | 307.00 | 21.91 | 191.67 | 22.52 | 53.17 | 22.42 |
Annual Sum or Average | 1938.50 | 23.01 | 4231.50 | 23.87 | 640.00 | 23.93 |
Minimum of Months | 47.17 | 21.77 | 165.17 | 22.04 | 14.67 | 21.90 |
Maximum of Months | 364.17 | 26.73 | 513.83 | 24.89 | 81.83 | 25.10 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 27.00 | 502.00 | 27.00 | 4.00 | 27.00 |
February | 8.83 | 27.00 | 454.00 | 27.00 | 8.83 | 27.00 |
March | 18.00 | 27.00 | 514.00 | 27.00 | 18.00 | 27.00 |
April | 180.00 | 27.01 | 485.00 | 27.00 | 180.00 | 27.01 |
May | 2.33 | 27.00 | 508.00 | 27.00 | 2.33 | 27.00 |
June | 38.33 | 27.00 | 496.00 | 27.00 | 38.33 | 27.00 |
July | 178.83 | 27.00 | 497.00 | 27.00 | 178.83 | 27.00 |
August | 427.17 | 27.13 | 514.00 | 27.12 | 427.17 | 27.12 |
September | 14.50 | 27.00 | 485.00 | 27.00 | 14.50 | 27.00 |
October | 53.50 | 27.00 | 502.00 | 27.00 | 53.50 | 27.00 |
November | 52.83 | 27.00 | 489.00 | 27.00 | 52.83 | 27.00 |
December | 109.83 | 27.00 | 497.00 | 27.00 | 109.83 | 27.00 |
Annual Sum or Average | 1088.17 | 27.05 | 5943.00 | 27.02 | 1088.17 | 27.02 |
Minimum of Months | 2.33 | 27.00 | 454.00 | 27.00 | 2.33 | 27.00 |
Maximum of Months | 427.17 | 27.13 | 514.00 | 27.12 | 427.17 | 27.12 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.33 | 27.00 | 447.50 | 27.00 | 0.33 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 4.67 | 27.28 | 485.00 | 27.01 | 4.67 | 27.01 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
August | 72.50 | 27.50 | 514.00 | 27.14 | 72.50 | 27.18 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.50 | 27.00 | 502.00 | 27.00 | 0.50 | 27.00 |
November | 1.00 | 27.00 | 489.00 | 27.00 | 1.00 | 27.00 |
December | 1.33 | 27.00 | 497.00 | 27.00 | 1.33 | 27.00 |
Annual Sum or Average | 80.33 | 27.46 | 5936.50 | 27.01 | 80.33 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 447.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 72.50 | 27.50 | 514.00 | 27.14 | 72.50 | 27.18 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 25.99 | 459.83 | 26.97 | 0.00 | 26.97 |
February | 8.17 | 27.01 | 429.50 | 27.00 | 1.17 | 27.00 |
March | 0.33 | 27.00 | 506.17 | 27.00 | 0.33 | 27.00 |
April | 29.00 | 27.04 | 485.00 | 27.00 | 29.00 | 27.01 |
May | 6.00 | 27.00 | 508.00 | 27.00 | 6.00 | 27.00 |
June | 17.67 | 27.00 | 496.00 | 27.00 | 17.67 | 27.00 |
July | 46.17 | 27.00 | 497.00 | 27.00 | 46.17 | 27.00 |
August | 105.00 | 27.28 | 514.00 | 27.10 | 105.00 | 27.13 |
September | 10.83 | 27.00 | 485.00 | 27.00 | 10.83 | 27.00 |
October | 19.17 | 27.00 | 502.00 | 27.00 | 19.17 | 27.00 |
November | 2.33 | 27.00 | 489.00 | 27.00 | 2.33 | 27.00 |
December | 5.33 | 27.00 | 489.17 | 27.00 | 5.33 | 27.00 |
Annual Sum or Average | 263.33 | 27.07 | 5860.67 | 27.01 | 243.00 | 27.01 |
Minimum of Months | 0.33 | 25.99 | 429.50 | 26.97 | 0.00 | 26.97 |
Maximum of Months | 105.00 | 27.28 | 514.00 | 27.10 | 105.00 | 27.13 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.67 | 27.00 | 502.00 | 27.00 | 495.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.27 | 485.00 | 27.27 | 485.00 | 27.27 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.66 | 514.00 | 28.66 | 514.00 | 28.66 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.10 | 497.00 | 27.10 | 497.00 | 27.10 |
Annual Sum or Average | 5936.67 | 27.18 | 5943.00 | 27.18 | 5936.67 | 27.18 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.66 | 514.00 | 28.66 | 514.00 | 28.66 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00016 | 32.39973 | 0.87215 | 21.19393 |
February | 454.00000 | 27.00088 | 33.55156 | 0.92594 | 23.22518 |
March | 514.00000 | 27.00052 | 33.86258 | 0.96452 | 24.72001 |
April | 485.00000 | 27.00329 | 36.53116 | 1.03694 | 27.73110 |
May | 508.00000 | 27.00030 | 42.35146 | 0.32872 | 7.28020 |
June | 496.00000 | 27.00216 | 40.66373 | 0.36186 | 7.75542 |
July | 497.00000 | 27.00135 | 39.88758 | 0.40361 | 8.42422 |
August | 514.00000 | 27.10931 | 39.18812 | 0.48120 | 9.97181 |
September | 485.00000 | 27.00019 | 42.76276 | 0.33489 | 7.37288 |
October | 502.00000 | 27.00169 | 38.48460 | 1.00118 | 26.21543 |
November | 489.00000 | 27.00063 | 35.41219 | 0.99356 | 25.89871 |
December | 497.00000 | 27.00015 | 33.44707 | 0.99621 | 26.03701 |
Annual Sum or Average | 5943.00000 | 27.01039 | 37.40023 | 0.72308 | 17.92655 |
Minimum of Months | 454.00000 | 27.00015 | 32.39973 | 0.32872 | 7.28020 |
Maximum of Months | 514.00000 | 27.10931 | 42.76276 | 1.03694 | 27.73110 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00010 | 32.56580 | 0.78399 | 18.16256 |
February | 454.00000 | 27.00085 | 33.60476 | 0.82608 | 19.61705 |
March | 514.00000 | 27.00050 | 33.84823 | 0.85690 | 20.63408 |
April | 485.00000 | 27.00345 | 36.49595 | 0.93847 | 23.65535 |
May | 508.00000 | 27.00015 | 42.61186 | 0.27641 | 6.62882 |
June | 496.00000 | 27.00209 | 40.75352 | 0.28889 | 6.77069 |
July | 497.00000 | 27.00129 | 39.91963 | 0.30530 | 6.97123 |
August | 514.00000 | 27.09135 | 39.20621 | 0.34551 | 7.61055 |
September | 485.00000 | 27.00011 | 43.13409 | 0.27417 | 6.61126 |
October | 502.00000 | 27.00163 | 38.56298 | 0.93798 | 23.65529 |
November | 489.00000 | 27.00060 | 35.39974 | 0.88887 | 21.77052 |
December | 497.00000 | 27.00015 | 33.40577 | 0.85349 | 20.53849 |
Annual Sum or Average | 5943.00000 | 27.00880 | 37.48065 | 0.62930 | 15.16735 |
Minimum of Months | 454.00000 | 27.00010 | 32.56580 | 0.27417 | 6.61126 |
Maximum of Months | 514.00000 | 27.09135 | 43.13409 | 0.93847 | 23.65535 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.95331 | 32.72327 | 0.72488 | 16.54577 |
February | 454.00000 | 27.00108 | 33.66466 | 0.78803 | 18.50874 |
March | 514.00000 | 27.00052 | 33.87928 | 0.82977 | 19.80851 |
April | 485.00000 | 27.00265 | 36.52396 | 0.93690 | 23.65230 |
May | 508.00000 | 27.00026 | 42.49314 | 0.29772 | 6.92205 |
June | 496.00000 | 27.00220 | 40.72136 | 0.31592 | 7.15338 |
July | 497.00000 | 27.00137 | 39.92282 | 0.33346 | 7.39034 |
August | 514.00000 | 27.06189 | 39.24306 | 0.36245 | 7.88900 |
September | 485.00000 | 27.00012 | 43.04143 | 0.28959 | 6.83731 |
October | 502.00000 | 27.00169 | 38.56560 | 0.94053 | 23.82590 |
November | 489.00000 | 27.00062 | 35.43738 | 0.86101 | 20.83167 |
December | 497.00000 | 27.00018 | 33.44287 | 0.80771 | 19.07284 |
Annual Sum or Average | 5943.00000 | 27.00229 | 37.49298 | 0.62217 | 14.82364 |
Minimum of Months | 454.00000 | 26.95331 | 32.72327 | 0.28959 | 6.83731 |
Maximum of Months | 514.00000 | 27.06189 | 43.04143 | 0.94053 | 23.82590 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00034 | 36.93628 | 1.12348 | 31.72195 |
February | 454.00000 | 27.00097 | 37.84081 | 1.27479 | 39.05221 |
March | 514.00000 | 27.00245 | 34.45412 | 1.38338 | 44.65581 |
April | 485.00000 | 27.27271 | 36.06971 | 1.58315 | 55.38025 |
May | 508.00000 | 27.00394 | 40.24686 | 0.55397 | 11.46088 |
June | 496.00000 | 27.00277 | 39.73511 | 0.76515 | 17.34589 |
July | 497.00000 | 27.00133 | 39.47584 | 0.97885 | 25.24857 |
August | 514.00000 | 28.66117 | 37.84920 | 1.64998 | 58.74331 |
September | 485.00000 | 27.00441 | 40.29959 | 0.61537 | 12.98952 |
October | 502.00000 | 27.00249 | 38.34598 | 1.32108 | 41.37309 |
November | 489.00000 | 27.00405 | 35.42983 | 1.43163 | 47.22017 |
December | 497.00000 | 27.10167 | 32.86869 | 1.55126 | 53.67751 |
Annual Sum or Average | 5943.00000 | 27.17633 | 37.45732 | 1.18624 | 36.59305 |
Minimum of Months | 454.00000 | 27.00034 | 32.86869 | 0.55397 | 11.46088 |
Maximum of Months | 514.00000 | 28.66117 | 40.29959 | 1.64998 | 58.74331 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.51544 | 38.29537 | 0.47637 | 10.59705 |
February | 454.00000 | 24.48703 | 46.71570 | 0.52591 | 11.55301 |
March | 514.00000 | 24.38753 | 45.70718 | 0.49810 | 10.91769 |
April | 485.00000 | 24.47232 | 57.60872 | 0.60087 | 13.24922 |
May | 508.00000 | 24.48104 | 66.10830 | -0.1916 | 6.95353 |
June | 496.00000 | 24.42447 | 65.52763 | -0.2111 | 6.84088 |
July | 497.00000 | 24.57626 | 64.62722 | -0.1612 | 6.99811 |
August | 514.00000 | 24.47716 | 62.66835 | -0.1878 | 6.99356 |
September | 485.00000 | 24.55143 | 63.38262 | -0.1666 | 7.08611 |
October | 502.00000 | 24.60307 | 57.71676 | 0.65379 | 15.09767 |
November | 489.00000 | 24.60364 | 48.13331 | 0.58322 | 13.02480 |
December | 497.00000 | 24.58750 | 43.26585 | 0.53967 | 12.11155 |
Annual Sum or Average | 5943.00000 | 24.51355 | 55.02905 | 0.24357 | 10.09674 |
Minimum of Months | 454.00000 | 24.38753 | 38.29537 | -0.2111 | 6.84088 |
Maximum of Months | 514.00000 | 24.60364 | 66.10830 | 0.65379 | 15.09767 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12214 | 38.30103 | 0.38871 | 8.61914 |
February | 454.00000 | 24.19880 | 41.98012 | 0.43895 | 9.42291 |
March | 514.00000 | 24.20247 | 41.13675 | 0.44263 | 9.40016 |
April | 485.00000 | 24.18857 | 46.62821 | 0.49048 | 10.18362 |
May | 508.00000 | 24.20471 | 49.84191 | -0.3613 | 8.00752 |
June | 496.00000 | 24.12938 | 49.80148 | -0.3781 | 8.11722 |
July | 497.00000 | 24.13401 | 49.51692 | -0.3693 | 7.94400 |
August | 514.00000 | 24.11203 | 49.44988 | -0.3612 | 7.78882 |
September | 485.00000 | 24.21235 | 49.66022 | -0.3563 | 7.94090 |
October | 502.00000 | 24.26412 | 47.13223 | 0.51229 | 10.71122 |
November | 489.00000 | 24.30823 | 43.57697 | 0.49589 | 10.44391 |
December | 497.00000 | 24.27924 | 40.26391 | 0.46091 | 9.78738 |
Annual Sum or Average | 5943.00000 | 24.19595 | 45.62668 | 0.11366 | 9.02253 |
Minimum of Months | 454.00000 | 24.11203 | 38.30103 | -0.3781 | 7.78882 |
Maximum of Months | 514.00000 | 24.30823 | 49.84191 | 0.51229 | 10.71122 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39302 | 40.91440 | 0.19722 | 6.48173 |
February | 454.00000 | 23.53607 | 44.52589 | 0.26102 | 7.14961 |
March | 514.00000 | 23.67593 | 43.71122 | 0.29646 | 7.39595 |
April | 485.00000 | 23.96988 | 48.30803 | 0.41169 | 8.80301 |
May | 508.00000 | 24.03025 | 50.69882 | -0.4369 | 9.30100 |
June | 496.00000 | 24.00623 | 50.66511 | -0.4435 | 9.38996 |
July | 497.00000 | 24.00305 | 50.62136 | -0.4468 | 9.49909 |
August | 514.00000 | 24.03488 | 50.68692 | -0.4339 | 9.22557 |
September | 485.00000 | 23.97942 | 50.80394 | -0.4547 | 9.63246 |
October | 502.00000 | 24.04441 | 48.38884 | 0.44149 | 9.33141 |
November | 489.00000 | 23.86159 | 45.93706 | 0.36536 | 8.12223 |
December | 497.00000 | 23.58313 | 43.37301 | 0.26818 | 7.22760 |
Annual Sum or Average | 5943.00000 | 23.84500 | 47.40001 | -0.0007 | 8.46980 |
Minimum of Months | 454.00000 | 23.39302 | 40.91440 | -0.4547 | 6.48173 |
Maximum of Months | 514.00000 | 24.04441 | 50.80394 | 0.44149 | 9.63246 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.36949 | 43.17232 | -0.0553 | 7.08437 |
February | 454.00000 | 22.76614 | 46.15132 | 0.07298 | 7.75841 |
March | 514.00000 | 23.17955 | 44.97695 | 0.17436 | 7.40745 |
April | 485.00000 | 23.90458 | 48.72557 | 0.40013 | 8.77523 |
May | 508.00000 | 24.15427 | 50.11299 | -0.3787 | 8.31258 |
June | 496.00000 | 24.15627 | 49.92828 | -0.3738 | 8.18421 |
July | 497.00000 | 24.17754 | 49.85239 | -0.3705 | 8.18091 |
August | 514.00000 | 24.16183 | 50.08528 | -0.3745 | 8.23707 |
September | 485.00000 | 24.08726 | 50.42093 | -0.4075 | 8.77717 |
October | 502.00000 | 24.02413 | 48.45144 | 0.44141 | 9.66661 |
November | 489.00000 | 23.38829 | 47.41470 | 0.24866 | 7.22465 |
December | 497.00000 | 22.73884 | 45.39297 | 0.05883 | 7.06414 |
Annual Sum or Average | 5943.00000 | 23.59770 | 47.89507 | -0.0489 | 8.05608 |
Minimum of Months | 454.00000 | 22.36949 | 43.17232 | -0.4075 | 7.06414 |
Maximum of Months | 514.00000 | 24.17754 | 50.42093 | 0.44141 | 9.66661 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.07226 | 40.07486 | 0.11807 | 7.07124 |
February | 454.00000 | 23.44915 | 42.47953 | 0.23738 | 7.78215 |
March | 514.00000 | 23.72255 | 41.45903 | 0.30693 | 8.10137 |
April | 485.00000 | 24.10461 | 46.10317 | 0.46561 | 9.79150 |
May | 508.00000 | 24.38569 | 49.51502 | -0.2501 | 7.10253 |
June | 496.00000 | 24.32469 | 48.49996 | -0.2518 | 6.89762 |
July | 497.00000 | 24.41034 | 48.57480 | -0.2188 | 6.90163 |
August | 514.00000 | 24.27709 | 48.70582 | -0.2569 | 7.00475 |
September | 485.00000 | 24.37805 | 49.92748 | -0.2666 | 7.35823 |
October | 502.00000 | 24.28274 | 47.40037 | 0.52902 | 11.48369 |
November | 489.00000 | 23.93996 | 43.92399 | 0.38442 | 8.67021 |
December | 497.00000 | 23.60905 | 41.49486 | 0.27174 | 7.68354 |
Annual Sum or Average | 5943.00000 | 23.99954 | 45.69593 | 0.08703 | 7.98380 |
Minimum of Months | 454.00000 | 23.07226 | 40.07486 | -0.2666 | 6.89762 |
Maximum of Months | 514.00000 | 24.41034 | 49.92748 | 0.52902 | 11.48369 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.50806 | 38.79752 | 0.23508 | 8.12613 |
February | 454.00000 | 23.71101 | 41.59566 | 0.31957 | 8.71136 |
March | 514.00000 | 23.81046 | 40.78095 | 0.35753 | 9.34829 |
April | 485.00000 | 24.13678 | 45.63197 | 0.50574 | 10.95827 |
May | 508.00000 | 24.46251 | 48.82932 | -0.1689 | 7.17823 |
June | 496.00000 | 24.36459 | 48.11306 | -0.1937 | 6.82721 |
July | 497.00000 | 24.45276 | 48.21538 | -0.1659 | 7.07768 |
August | 514.00000 | 24.27736 | 48.56292 | -0.2294 | 7.08078 |
September | 485.00000 | 24.45964 | 49.23421 | -0.2009 | 7.58382 |
October | 502.00000 | 24.35873 | 46.80176 | 0.57467 | 12.91912 |
November | 489.00000 | 24.08369 | 43.24837 | 0.43942 | 9.96361 |
December | 497.00000 | 23.62074 | 41.33007 | 0.28627 | 8.26199 |
Annual Sum or Average | 5943.00000 | 24.10593 | 45.11358 | 0.14439 | 8.66330 |
Minimum of Months | 454.00000 | 23.50806 | 38.79752 | -0.2294 | 6.82721 |
Maximum of Months | 514.00000 | 24.46251 | 49.23421 | 0.57467 | 12.91912 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.84269 | 37.32728 | 0.36266 | 10.34981 |
February | 454.00000 | 23.97140 | 40.41892 | 0.42137 | 10.80021 |
March | 514.00000 | 23.84639 | 40.51380 | 0.37216 | 9.68361 |
April | 485.00000 | 24.17420 | 45.69001 | 0.50295 | 10.77831 |
May | 508.00000 | 24.38492 | 49.50026 | -0.2465 | 7.12085 |
June | 496.00000 | 24.31012 | 48.60829 | -0.2648 | 7.04780 |
July | 497.00000 | 24.40495 | 48.59883 | -0.2227 | 6.99586 |
August | 514.00000 | 24.30205 | 48.49250 | -0.2274 | 6.88871 |
September | 485.00000 | 24.46475 | 49.25189 | -0.1934 | 7.34687 |
October | 502.00000 | 24.48579 | 46.09996 | 0.64304 | 14.88507 |
November | 489.00000 | 24.39528 | 41.96543 | 0.57093 | 13.19104 |
December | 497.00000 | 24.09835 | 39.46905 | 0.46233 | 11.81077 |
Annual Sum or Average | 5943.00000 | 24.22394 | 44.68676 | 0.17876 | 9.72413 |
Minimum of Months | 454.00000 | 23.84269 | 37.32728 | -0.2648 | 6.88871 |
Maximum of Months | 514.00000 | 24.48579 | 49.50026 | 0.64304 | 14.88507 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.99458 | 37.27449 | 0.37537 | 9.52654 |
February | 454.00000 | 24.30525 | 39.63893 | 0.50580 | 11.70111 |
March | 514.00000 | 24.40179 | 38.86349 | 0.55458 | 12.51278 |
April | 485.00000 | 24.60787 | 43.94700 | 0.71062 | 16.59445 |
May | 508.00000 | 24.56304 | 48.37036 | -0.0966 | 6.88306 |
June | 496.00000 | 24.53518 | 47.33786 | -0.0603 | 6.70935 |
July | 497.00000 | 24.67325 | 47.09197 | 0.00397 | 7.07865 |
August | 514.00000 | 24.54944 | 47.05150 | 0.01458 | 6.67076 |
September | 485.00000 | 24.58226 | 48.46452 | -0.0994 | 7.20118 |
October | 502.00000 | 24.61840 | 45.54406 | 0.69616 | 16.31354 |
November | 489.00000 | 24.56368 | 41.45235 | 0.62207 | 14.08974 |
December | 497.00000 | 24.56981 | 38.17326 | 0.58994 | 13.61195 |
Annual Sum or Average | 5943.00000 | 24.49762 | 43.62268 | 0.31582 | 10.71560 |
Minimum of Months | 454.00000 | 23.99458 | 37.27449 | -0.0994 | 6.67076 |
Maximum of Months | 514.00000 | 24.67325 | 48.46452 | 0.71062 | 16.59445 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.88137 | 43.57127 | -0.1795 | 8.06392 |
February | 454.00000 | 22.32673 | 45.73508 | -0.0412 | 8.23938 |
March | 514.00000 | 22.79471 | 44.57002 | 0.07413 | 7.50887 |
April | 485.00000 | 23.77370 | 48.88798 | 0.37097 | 8.72865 |
May | 508.00000 | 24.35496 | 51.66145 | -0.2653 | 7.26423 |
June | 496.00000 | 24.35062 | 50.21715 | -0.2560 | 7.11030 |
July | 497.00000 | 24.46083 | 51.27661 | -0.2170 | 7.23896 |
August | 514.00000 | 24.33383 | 51.71714 | -0.2657 | 7.29927 |
September | 485.00000 | 24.29881 | 53.00596 | -0.2980 | 7.75716 |
October | 502.00000 | 24.06530 | 50.70034 | 0.47586 | 10.92021 |
November | 489.00000 | 23.08128 | 47.34412 | 0.16982 | 7.16975 |
December | 497.00000 | 22.30566 | 45.97066 | -0.0490 | 7.61699 |
Annual Sum or Average | 5943.00000 | 23.51013 | 48.73517 | -0.0411 | 7.90578 |
Minimum of Months | 454.00000 | 21.88137 | 43.57127 | -0.2980 | 7.11030 |
Maximum of Months | 514.00000 | 24.46083 | 53.00596 | 0.47586 | 10.92021 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.69906 | 41.53748 | 0.02742 | 7.83906 |
February | 385.00000 | 23.04352 | 43.28386 | 0.14214 | 8.25900 |
March | 433.00000 | 23.39238 | 42.14417 | 0.23747 | 9.03749 |
April | 410.00000 | 24.16319 | 47.03947 | 0.49521 | 11.28912 |
May | 430.00000 | 24.57122 | 50.41416 | -0.1391 | 7.51144 |
June | 418.00000 | 24.52157 | 49.25563 | -0.1524 | 7.13826 |
July | 422.00000 | 24.67769 | 50.10513 | -0.0996 | 7.67035 |
August | 433.00000 | 24.50032 | 50.77667 | -0.1686 | 7.26860 |
September | 410.00000 | 24.53710 | 51.64162 | -0.1817 | 8.08240 |
October | 427.00000 | 24.35589 | 49.29624 | 0.57138 | 13.58855 |
November | 417.00000 | 23.72992 | 44.84322 | 0.33793 | 8.99056 |
December | 422.00000 | 22.90242 | 44.23234 | 0.10102 | 8.10380 |
Annual Sum or Average | 5034.00000 | 23.92902 | 47.06421 | 0.09670 | 8.73096 |
Minimum of Months | 385.00000 | 22.69906 | 41.53748 | -0.1817 | 7.13826 |
Maximum of Months | 433.00000 | 24.67769 | 51.64162 | 0.57138 | 13.58855 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.57724 | 38.61690 | 0.29745 | 10.26566 |
February | 454.00000 | 23.67719 | 41.53831 | 0.34554 | 10.55011 |
March | 514.00000 | 23.46952 | 42.13671 | 0.27254 | 9.18933 |
April | 485.00000 | 24.01412 | 47.73718 | 0.45163 | 10.19417 |
May | 508.00000 | 24.35976 | 51.61565 | -0.2590 | 7.26716 |
June | 496.00000 | 24.32663 | 50.42669 | -0.2727 | 7.24909 |
July | 497.00000 | 24.44784 | 51.35913 | -0.2231 | 7.29473 |
August | 514.00000 | 24.36919 | 51.31955 | -0.2298 | 7.13640 |
September | 485.00000 | 24.43299 | 51.74803 | -0.2040 | 7.61618 |
October | 502.00000 | 24.45758 | 48.19015 | 0.63938 | 15.15461 |
November | 489.00000 | 24.22357 | 43.16526 | 0.52371 | 12.69934 |
December | 497.00000 | 23.76645 | 41.38417 | 0.37611 | 11.56065 |
Annual Sum or Average | 5943.00000 | 24.09515 | 46.63570 | 0.14043 | 9.66659 |
Minimum of Months | 454.00000 | 23.46952 | 38.61690 | -0.2727 | 7.13640 |
Maximum of Months | 514.00000 | 24.45758 | 51.74803 | 0.63938 | 15.15461 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.83207 | 40.88200 | 0.07221 | 8.17701 |
February | 454.00000 | 23.22441 | 42.93237 | 0.20328 | 9.29363 |
March | 514.00000 | 23.47556 | 42.32240 | 0.26928 | 9.09336 |
April | 485.00000 | 24.24714 | 46.87727 | 0.53724 | 12.13381 |
May | 508.00000 | 24.47078 | 50.73220 | -0.1667 | 7.07290 |
June | 496.00000 | 24.46849 | 49.38880 | -0.1523 | 7.02587 |
July | 497.00000 | 24.59403 | 50.22039 | -0.1142 | 7.34424 |
August | 514.00000 | 24.46696 | 50.45447 | -0.1480 | 6.95270 |
September | 485.00000 | 24.47846 | 51.55600 | -0.1770 | 7.56400 |
October | 502.00000 | 24.36013 | 48.91771 | 0.59290 | 13.72969 |
November | 489.00000 | 23.78730 | 44.83870 | 0.36826 | 9.38193 |
December | 497.00000 | 23.18769 | 43.29960 | 0.18922 | 8.70188 |
Annual Sum or Average | 5943.00000 | 23.97035 | 46.89089 | 0.12121 | 8.86053 |
Minimum of Months | 454.00000 | 22.83207 | 40.88200 | -0.1770 | 6.95270 |
Maximum of Months | 514.00000 | 24.59403 | 51.55600 | 0.59290 | 13.72969 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.47238 | 44.77691 | -0.3064 | 10.33886 |
February | 454.00000 | 21.93970 | 46.86633 | -0.1496 | 10.00701 |
March | 514.00000 | 22.47598 | 45.35956 | -0.0119 | 8.65907 |
April | 485.00000 | 23.64086 | 49.42511 | 0.34487 | 8.88389 |
May | 508.00000 | 24.38709 | 51.82967 | -0.2336 | 7.22001 |
June | 496.00000 | 24.38763 | 50.23397 | -0.2197 | 7.06276 |
July | 497.00000 | 24.50598 | 51.26819 | -0.1784 | 7.32904 |
August | 514.00000 | 24.36134 | 51.92887 | -0.2344 | 7.27335 |
September | 485.00000 | 24.32526 | 53.40294 | -0.2726 | 7.90037 |
October | 502.00000 | 23.99051 | 51.26330 | 0.46631 | 11.43751 |
November | 489.00000 | 22.67952 | 48.43603 | 0.06857 | 7.64403 |
December | 497.00000 | 21.89702 | 47.24721 | -0.1689 | 9.14703 |
Annual Sum or Average | 5943.00000 | 23.34821 | 49.34549 | -0.0750 | 8.56503 |
Minimum of Months | 454.00000 | 21.47238 | 44.77691 | -0.3064 | 7.06276 |
Maximum of Months | 514.00000 | 24.50598 | 53.40294 | 0.46631 | 11.43751 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.21143 | 42.91778 | -0.1053 | 8.86756 |
February | 454.00000 | 22.67782 | 44.69373 | 0.05138 | 9.28510 |
March | 514.00000 | 23.15707 | 43.07537 | 0.18082 | 9.61609 |
April | 485.00000 | 24.03323 | 47.45045 | 0.48329 | 11.28337 |
May | 508.00000 | 24.49386 | 50.52610 | -0.1243 | 7.33515 |
June | 496.00000 | 24.45403 | 49.33567 | -0.1280 | 6.95755 |
July | 497.00000 | 24.59057 | 50.08994 | -0.0830 | 7.53622 |
August | 514.00000 | 24.42936 | 50.86577 | -0.1496 | 7.09481 |
September | 485.00000 | 24.45065 | 51.87613 | -0.1764 | 8.00834 |
October | 502.00000 | 24.22107 | 49.57924 | 0.55872 | 13.64192 |
November | 489.00000 | 23.45798 | 45.97238 | 0.27278 | 8.68285 |
December | 497.00000 | 22.49945 | 45.54036 | -0.0095 | 8.84641 |
Annual Sum or Average | 5943.00000 | 23.72972 | 47.67459 | 0.06337 | 8.92249 |
Minimum of Months | 454.00000 | 22.21143 | 42.91778 | -0.1764 | 6.95755 |
Maximum of Months | 514.00000 | 24.59057 | 51.87613 | 0.55872 | 13.64192 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17788 | 39.86196 | 0.17649 | 10.40925 |
February | 454.00000 | 23.29237 | 42.60277 | 0.23994 | 10.82584 |
March | 514.00000 | 23.16875 | 42.97308 | 0.19160 | 9.75633 |
April | 485.00000 | 23.88442 | 48.30273 | 0.42693 | 10.28065 |
May | 508.00000 | 24.38535 | 51.80173 | -0.2291 | 7.23718 |
June | 496.00000 | 24.36338 | 50.44159 | -0.2365 | 7.17897 |
July | 497.00000 | 24.48926 | 51.35605 | -0.1856 | 7.37013 |
August | 514.00000 | 24.38813 | 51.55232 | -0.2008 | 7.14067 |
September | 485.00000 | 24.43322 | 52.19882 | -0.1856 | 7.81528 |
October | 502.00000 | 24.37868 | 48.73051 | 0.62947 | 15.33263 |
November | 489.00000 | 23.96921 | 43.91939 | 0.45353 | 12.03823 |
December | 497.00000 | 23.38886 | 42.58391 | 0.26608 | 11.39710 |
Annual Sum or Average | 5943.00000 | 23.94662 | 47.22252 | 0.11003 | 9.71735 |
Minimum of Months | 454.00000 | 23.16875 | 39.86196 | -0.2365 | 7.14067 |
Maximum of Months | 514.00000 | 24.48926 | 52.19882 | 0.62947 | 15.33263 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.41873 | 42.06886 | -0.0455 | 9.26158 |
February | 454.00000 | 22.85768 | 43.98966 | 0.10634 | 10.14089 |
March | 514.00000 | 23.16969 | 43.12878 | 0.19098 | 9.62202 |
April | 485.00000 | 24.12690 | 47.42183 | 0.51482 | 12.10403 |
May | 508.00000 | 24.48692 | 50.96880 | -0.1408 | 7.14926 |
June | 496.00000 | 24.48167 | 49.49161 | -0.1242 | 7.09851 |
July | 497.00000 | 24.60858 | 50.31983 | -0.0860 | 7.50364 |
August | 514.00000 | 24.47646 | 50.72102 | -0.1231 | 7.02082 |
September | 485.00000 | 24.47788 | 52.02982 | -0.1600 | 7.74020 |
October | 502.00000 | 24.29033 | 49.45881 | 0.58492 | 14.01835 |
November | 489.00000 | 23.47074 | 45.71446 | 0.28844 | 9.22965 |
December | 497.00000 | 22.78313 | 44.50183 | 0.07882 | 9.26480 |
Annual Sum or Average | 5943.00000 | 23.80985 | 47.50324 | 0.08925 | 9.16528 |
Minimum of Months | 454.00000 | 22.41873 | 42.06886 | -0.1600 | 7.02082 |
Maximum of Months | 514.00000 | 24.60858 | 52.02982 | 0.58492 | 14.01835 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.605366E+11 | 180605.42 | 31-JAN-15:00 | 285.80 | 0.398754E+12 | 0.00 | 0.459291E+12 | 2.22 | 7.93 | 20-JAN-06:04 | 0.00 | 0.00 |
February | 0.820175E+11 | 182713.76 | 24-FEB-16:20 | 326.18 | 0.557632E+12 | 0.00 | 0.639650E+12 | 2.97 | 7.93 | 03-FEB-06:04 | 0.00 | 0.00 |
March | 0.977547E+11 | 186962.31 | 07-MAR-12:30 | 409.89 | 0.664887E+12 | 0.00 | 0.762642E+12 | 3.32 | 7.93 | 28-MAR-05:04 | 0.00 | 0.00 |
April | 0.148096E+12 | 187755.82 | 27-APR-11:20 | 549.60 | 0.105468E+13 | 0.00 | 0.120277E+13 | 4.83 | 7.95 | 18-APR-13:40 | 0.00 | 0.00 |
May | 0.210828E+12 | 197647.32 | 24-MAY-11:10 | 540.60 | 0.150527E+13 | 0.00 | 0.171610E+13 | 4.98 | 7.89 | 13-MAY-04:13 | 0.00 | 0.00 |
June | 0.213231E+12 | 203463.34 | 24-JUN-10:00 | 596.88 | 0.149815E+13 | 0.00 | 0.171138E+13 | 5.45 | 7.92 | 08-JUN-05:04 | 0.00 | 0.00 |
July | 0.221354E+12 | 205427.64 | 22-JUL-11:20 | 658.73 | 0.152089E+13 | 0.00 | 0.174225E+13 | 5.60 | 7.71 | 12-JUL-15:10 | 0.00 | 0.00 |
August | 0.224907E+12 | 200291.36 | 10-AUG-17:20 | 679.36 | 0.156487E+13 | 0.00 | 0.178978E+13 | 5.79 | 7.82 | 16-AUG-04:13 | 0.00 | 0.00 |
September | 0.206450E+12 | 197643.95 | 08-SEP-08:00 | 534.81 | 0.146120E+13 | 0.00 | 0.166765E+13 | 5.02 | 7.92 | 22-SEP-05:04 | 0.00 | 0.00 |
October | 0.178691E+12 | 204877.40 | 14-OCT-11:00 | 549.58 | 0.125333E+13 | 0.00 | 0.143202E+13 | 4.79 | 7.95 | 26-OCT-15:00 | 0.00 | 0.00 |
November | 0.115489E+12 | 192887.50 | 01-NOV-12:00 | 450.99 | 0.787722E+12 | 0.00 | 0.903211E+12 | 3.85 | 7.92 | 08-NOV-06:04 | 0.00 | 0.00 |
December | 0.836780E+11 | 188640.02 | 13-DEC-11:30 | 376.17 | 0.569175E+12 | 0.00 | 0.652853E+12 | 2.98 | 7.88 | 16-DEC-06:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.184303E+13 | 5958.57 | 0.128366E+14 | 0.00 | 0.146796E+14 | 4.32 | 0.00 | 0.00 | ||||
Minimum of Months | 0.605366E+11 | 180605.42 | 285.80 | 0.398754E+12 | 0.00 | 0.459291E+12 | 2.22 | 7.71 | 0.00 | 0.00 | ||
Maximum of Months | 0.224907E+12 | 205427.64 | 679.36 | 0.156487E+13 | 0.00 | 0.178978E+13 | 5.79 | 7.95 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.173825E+10 | 110084.60 | 19-JAN-11:05 | 5.83 | 0.127127E+11 | 0.00 | 0.144510E+11 | 0.05 | 7.50 | 19-JAN-10:05 | 0.00 | 0.00 |
February | 0.333279E+10 | 140187.00 | 27-FEB-16:13 | 12.19 | 0.245353E+11 | 0.00 | 0.278681E+11 | 0.12 | 7.67 | 27-FEB-16:13 | 0.00 | 0.00 |
March | 0.531534E+10 | 115449.70 | 30-MAR-13:00 | 17.75 | 0.387701E+11 | 0.00 | 0.440854E+11 | 0.16 | 7.66 | 17-MAR-16:00 | 0.00 | 0.00 |
April | 0.923889E+10 | 155642.44 | 27-APR-15:23 | 29.75 | 0.668469E+11 | 0.00 | 0.760858E+11 | 0.29 | 7.75 | 20-APR-15:03 | 0.00 | 0.00 |
May | 0.428665E+11 | 162062.56 | 10-MAY-15:53 | 122.12 | 0.305034E+12 | 0.00 | 0.347900E+12 | 1.15 | 7.52 | 12-MAY-12:05 | 0.00 | 0.00 |
June | 0.512908E+11 | 156616.03 | 12-JUN-15:13 | 142.53 | 0.360010E+12 | 0.00 | 0.411301E+12 | 1.37 | 7.62 | 12-JUN-11:00 | 0.00 | 0.00 |
July | 0.607825E+11 | 138879.71 | 05-JUL-12:05 | 163.00 | 0.421862E+12 | 0.00 | 0.482644E+12 | 1.51 | 7.44 | 12-JUL-15:30 | 0.00 | 0.00 |
August | 0.668206E+11 | 136882.00 | 22-AUG-12:05 | 180.67 | 0.467096E+12 | 0.00 | 0.533916E+12 | 1.69 | 7.46 | 15-AUG-10:05 | 0.00 | 0.00 |
September | 0.472370E+11 | 150427.51 | 22-SEP-14:03 | 131.28 | 0.333773E+12 | 0.00 | 0.381010E+12 | 1.28 | 7.57 | 13-SEP-04:15 | 0.00 | 0.00 |
October | 0.412091E+11 | 142098.89 | 18-OCT-15:03 | 112.94 | 0.291157E+12 | 0.00 | 0.332366E+12 | 1.06 | 7.80 | 02-OCT-10:43 | 0.00 | 0.00 |
November | 0.123894E+11 | 139790.72 | 06-NOV-10:23 | 34.67 | 0.884285E+11 | 0.00 | 0.100818E+12 | 0.34 | 7.74 | 06-NOV-09:43 | 0.00 | 0.00 |
December | 0.649604E+10 | 152898.45 | 15-DEC-13:53 | 18.92 | 0.469957E+11 | 0.00 | 0.534918E+11 | 0.18 | 7.52 | 11-DEC-17:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348717E+12 | 971.64 | 0.245722E+13 | 0.00 | 0.280594E+13 | 0.77 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173825E+10 | 110084.60 | 5.83 | 0.127127E+11 | 0.00 | 0.144510E+11 | 0.05 | 7.44 | 0.00 | 0.00 | ||
Maximum of Months | 0.668206E+11 | 162062.56 | 180.67 | 0.467096E+12 | 0.00 | 0.533916E+12 | 1.69 | 7.80 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.352858E+11 | 744.00 | 43776.24 | 01-JAN-08:43 | 275331.83 | 31-JAN-13:00 | 20.13 | 19.29 | 14.12 |
February | 0.504049E+11 | 672.00 | 43776.24 | 01-FEB-00:10 | 421877.81 | 24-FEB-10:30 | 22.83 | 20.21 | 14.12 |
March | 0.732820E+11 | 744.00 | 43776.24 | 01-MAR-00:10 | 604837.54 | 31-MAR-24:00 | 26.92 | 21.83 | 14.12 |
April | 0.107161E+12 | 720.00 | 43776.24 | 01-APR-00:10 | 681836.41 | 28-APR-17:20 | 36.90 | 26.20 | 14.12 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:03 | 331361.79 | 31-MAY-23:40 | 32.87 | 28.70 | 14.12 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 479456.68 | 30-JUN-23:55 | 37.89 | 30.73 | 14.12 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 626134.36 | 31-JUL-23:33 | 42.51 | 32.38 | 14.12 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:10 | 691090.32 | 06-AUG-15:31 | 46.03 | 33.13 | 14.12 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:10 | 330798.55 | 30-SEP-23:50 | 32.24 | 28.04 | 14.12 |
October | 0.107934E+12 | 744.00 | 43776.24 | 01-OCT-00:10 | 467693.82 | 31-OCT-24:00 | 33.12 | 27.13 | 14.12 |
November | 0.836272E+11 | 720.00 | 43776.24 | 01-NOV-00:10 | 531439.10 | 01-NOV-14:05 | 28.73 | 22.90 | 14.12 |
December | 0.717103E+11 | 744.00 | 43776.24 | 01-DEC-09:50 | 664223.09 | 13-DEC-17:10 | 28.90 | 22.02 | 14.12 |
Annual Sum or Average | 0.110809E+13 | 8760.00 | 32.48 | 26.09 | 14.12 | ||||
Minimum of Months | 0.352858E+11 | 672.00 | 43776.24 | 275331.83 | 20.13 | 19.29 | 14.12 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 691090.32 | 46.03 | 33.13 | 14.12 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.479709E+10 | 201.99 | 18943.65 | 02-JAN-10:20 | 1448397.94 | 02-JAN-11:20 | 21.96 | 21.33 | 22.25 |
February | 0.616463E+10 | 267.45 | 18943.65 | 01-FEB-13:00 | 1426086.80 | 27-FEB-10:20 | 22.51 | 21.55 | 29.53 |
March | 0.858101E+10 | 325.18 | 18943.65 | 06-MAR-08:30 | 1425666.21 | 31-MAR-10:50 | 22.56 | 21.53 | 32.42 |
April | 0.177225E+11 | 472.79 | 18943.65 | 01-APR-04:12 | 1467532.20 | 05-APR-10:40 | 23.55 | 21.87 | 46.35 |
May | 0.367080E+11 | 540.60 | 18943.65 | 01-MAY-01:05 | 1282035.31 | 17-MAY-04:14 | 27.18 | 24.91 | 40.14 |
June | 0.398424E+11 | 596.88 | 18943.65 | 01-JUN-04:12 | 1436606.02 | 07-JUN-04:13 | 27.26 | 24.92 | 47.19 |
July | 0.449235E+11 | 658.73 | 18943.65 | 01-JUL-00:10 | 1172817.00 | 12-JUL-12:05 | 28.10 | 25.78 | 49.01 |
August | 0.454753E+11 | 677.52 | 18943.65 | 01-AUG-00:10 | 1230426.70 | 16-AUG-17:20 | 27.52 | 25.14 | 51.99 |
September | 0.364588E+11 | 534.81 | 18943.65 | 01-SEP-00:10 | 1288067.34 | 22-SEP-07:30 | 27.81 | 25.53 | 40.16 |
October | 0.285151E+11 | 527.90 | 18943.65 | 02-OCT-09:00 | 1437026.06 | 02-OCT-12:00 | 25.62 | 23.71 | 43.43 |
November | 0.116275E+11 | 389.16 | 18943.65 | 01-NOV-03:43 | 1428092.28 | 06-NOV-09:00 | 23.21 | 21.94 | 38.42 |
December | 0.873243E+10 | 285.41 | 18943.65 | 08-DEC-11:00 | 1465941.74 | 08-DEC-16:30 | 22.39 | 21.50 | 28.98 |
Annual Sum or Average | 0.289548E+12 | 5478.42 | 24.99 | 23.32 | 39.19 | ||||
Minimum of Months | 0.479709E+10 | 201.99 | 18943.65 | 1172817.00 | 21.96 | 21.33 | 22.25 | ||
Maximum of Months | 0.454753E+11 | 677.52 | 18943.65 | 1467532.20 | 28.10 | 25.78 | 51.99 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.960443E+09 | 14.08 | 18943.65 | 02-JAN-11:30 | 1038970.94 | 31-JAN-15:05 | 21.96 | 21.88 | 0.90 |
February | 0.184890E+10 | 27.11 | 18943.65 | 01-FEB-13:50 | 1129684.72 | 27-FEB-15:05 | 22.51 | 22.33 | 1.87 |
March | 0.269947E+10 | 39.58 | 18943.65 | 06-MAR-09:40 | 1078515.52 | 07-MAR-13:05 | 22.56 | 22.34 | 2.60 |
April | 0.512331E+10 | 75.12 | 18943.65 | 04-APR-15:40 | 1151454.19 | 25-APR-14:05 | 23.55 | 23.13 | 4.85 |
May | 0.214204E+11 | 314.10 | 18943.65 | 01-MAY-05:06 | 1173137.52 | 10-MAY-15:53 | 27.18 | 25.56 | 19.74 |
June | 0.220482E+11 | 323.30 | 18943.65 | 01-JUN-06:50 | 1157650.47 | 08-JUN-14:05 | 27.26 | 25.57 | 21.72 |
July | 0.269178E+11 | 394.71 | 18943.65 | 01-JUL-05:06 | 1172817.00 | 12-JUL-12:05 | 28.10 | 26.21 | 25.23 |
August | 0.263285E+11 | 386.06 | 18943.65 | 01-AUG-06:20 | 1154193.48 | 22-AUG-12:05 | 27.52 | 25.63 | 25.59 |
September | 0.231992E+11 | 340.18 | 18943.65 | 01-SEP-05:08 | 1173802.42 | 01-SEP-12:05 | 27.81 | 26.07 | 22.04 |
October | 0.158257E+11 | 232.06 | 18943.65 | 02-OCT-09:40 | 1185291.21 | 03-OCT-15:43 | 25.62 | 24.49 | 15.57 |
November | 0.468287E+10 | 68.67 | 18943.65 | 01-NOV-06:20 | 1094641.92 | 06-NOV-13:05 | 23.21 | 22.85 | 4.82 |
December | 0.315412E+10 | 46.25 | 18943.65 | 08-DEC-15:50 | 1150883.87 | 15-DEC-13:53 | 22.39 | 22.14 | 2.95 |
Annual Sum or Average | 0.154209E+12 | 2261.22 | 24.99 | 24.03 | 12.40 | ||||
Minimum of Months | 0.960443E+09 | 14.08 | 18943.65 | 1038970.94 | 21.96 | 21.88 | 0.90 | ||
Maximum of Months | 0.269178E+11 | 394.71 | 18943.65 | 1185291.21 | 28.10 | 26.21 | 25.59 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.229603E+11 | 0.00 | 213.14 | 1164287.24 | 09-JAN-06:02 | 0.00 | 29.65 | 38.29 | 0.08 | 0.00 | 0.01 | 0.82 | 09-JAN-06:02 |
February | 0.114890E+11 | 0.00 | 118.17 | 1053750.78 | 17-FEB-06:02 | 0.00 | 26.69 | 32.03 | 0.05 | 0.00 | 0.00 | 0.74 | 17-FEB-06:02 |
March | 0.963574E+10 | 0.00 | 93.83 | 1204389.09 | 11-MAR-06:02 | 0.00 | 27.25 | 31.19 | 0.03 | 0.00 | 0.00 | 0.85 | 11-MAR-06:02 |
April | 0.217796E+09 | 0.00 | 10.21 | 77297.97 | 18-APR-14:20 | 0.00 | 33.03 | 33.47 | 0.00 | 0.00 | 0.00 | 0.05 | 18-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 39.42 | 39.42 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 39.42 | 39.42 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 39.42 | 39.42 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 39.42 | 39.42 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 39.42 | 39.42 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 37483238.36 | 0.00 | 6.75 | 16441.45 | 28-OCT-05:03 | 0.00 | 39.07 | 39.27 | 0.00 | 0.00 | 0.00 | 0.01 | 28-OCT-05:03 |
November | 0.819410E+09 | 0.00 | 43.58 | 211962.11 | 16-NOV-06:02 | 0.00 | 31.49 | 33.32 | 0.00 | 0.00 | 0.00 | 0.15 | 16-NOV-06:02 |
December | 0.151990E+11 | 0.00 | 159.29 | 1213618.47 | 20-DEC-05:11 | 0.00 | 27.33 | 33.95 | 0.05 | 0.00 | 0.00 | 0.86 | 20-DEC-05:11 |
Annual Sum or Average | 0.603588E+11 | 0.00 | 644.97 | 0.00 | 34.35 | 36.59 | 0.02 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 | 31.19 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.229603E+11 | 0.00 | 213.14 | 1213618.47 | 0.00 | 39.42 | 39.42 | 0.08 | 0.00 | 0.01 | 0.86 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 20.13 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 22.83 | 22.83 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 26.92 | 26.92 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 36.90 | 36.90 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 32.87 | 32.87 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 37.89 | 37.89 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 42.51 | 42.51 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 46.03 | 46.03 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 32.24 | 32.24 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 33.12 | 33.12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.73 | 28.73 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 28.90 | 28.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 32.48 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.03 | 46.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.389122E+11 | 0.00 | 270.89 | 0.292565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132707.43 | 30-JAN-06:02 | 108360.00 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.554933E+11 | 0.00 | 316.93 | 0.405615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151496.21 | 28-FEB-05:12 | 141705.55 | 27-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.694834E+11 | 0.00 | 403.42 | 0.548985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155185.81 | 28-MAR-04:12 | 133662.05 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.113392E+12 | 0.00 | 539.42 | 0.901505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151446.33 | 01-APR-04:12 | 129226.91 | 27-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.142564E+12 | 0.00 | 513.61 | 0.109169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 176689.16 | 22-MAY-05:02 | 143786.38 | 31-MAY-04:11 | 0.00 | 0.00 | 0.00 |
June | 0.154722E+12 | 0.00 | 574.55 | 0.121502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 171250.04 | 07-JUN-04:12 | 140975.66 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.168254E+12 | 0.00 | 626.05 | 0.130387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164096.97 | 24-JUL-05:03 | 145552.63 | 24-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.185142E+12 | 0.00 | 655.42 | 0.145190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 176546.98 | 07-AUG-05:02 | 148808.83 | 21-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.143539E+12 | 0.00 | 504.28 | 0.103867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 194757.12 | 06-SEP-03:02 | 142409.50 | 06-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.134782E+12 | 0.00 | 525.20 | 0.105470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 178077.97 | 21-OCT-04:11 | 144805.62 | 10-OCT-04:11 | 0.00 | 0.00 | 0.00 |
November | 0.847191E+11 | 0.00 | 435.50 | 0.682199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173699.87 | 08-NOV-05:11 | 138388.80 | 08-NOV-05:11 | 0.00 | 0.00 | 0.00 |
December | 0.633503E+11 | 0.00 | 361.54 | 0.498403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141176.64 | 11-DEC-06:03 | 128658.57 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135435E+13 | 0.00 | 5726.80 | 0.104851E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.389122E+11 | 0.00 | 270.89 | 0.292565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132707.43 | 108360.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.185142E+12 | 0.00 | 655.42 | 0.145190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 194757.12 | 148808.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.308391E+12 | 0.00 | 264.49 | 0.225246E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1086610.00 | 19-JAN-06:03 | 826674.22 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.436165E+12 | 0.00 | 300.19 | 0.304722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1300453.40 | 27-FEB-06:02 | 1179700.80 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.518457E+12 | 0.00 | 363.22 | 0.387582E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1585560.07 | 07-MAR-06:02 | 1157412.51 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.818957E+12 | 0.00 | 413.54 | 0.609615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1571671.91 | 29-APR-04:11 | 1257316.61 | 28-APR-04:12 | 0.00 | 0.00 | 0.00 |
May | 0.129612E+13 | 0.00 | 479.96 | 0.950414E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2012289.33 | 24-MAY-05:02 | 1289933.92 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.132443E+13 | 0.00 | 486.59 | 0.983251E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1669297.10 | 09-JUN-04:12 | 1282046.96 | 16-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.137971E+13 | 0.00 | 502.13 | 0.980776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1632799.65 | 29-JUL-05:02 | 1281498.94 | 07-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.142465E+13 | 0.00 | 501.26 | 0.101288E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1830270.31 | 16-AUG-04:12 | 1265232.28 | 31-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.128209E+13 | 0.00 | 465.78 | 0.871973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2158839.05 | 05-SEP-04:11 | 1296756.61 | 01-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.112227E+13 | 0.00 | 450.41 | 0.824566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1825929.02 | 21-OCT-04:11 | 1290285.76 | 10-OCT-04:11 | 0.00 | 0.00 | 0.00 |
November | 0.643854E+12 | 0.00 | 391.87 | 0.495761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1556379.23 | 02-NOV-05:02 | 1263701.95 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.450324E+12 | 0.00 | 301.79 | 0.329179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1323950.75 | 16-DEC-06:03 | 1030499.51 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110054E+14 | 0.00 | 4921.23 | 0.797597E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.308391E+12 | 0.00 | 264.49 | 0.225246E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1086610.00 | 826674.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.142465E+13 | 0.00 | 502.13 | 0.101288E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2158839.05 | 1296756.61 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.303282E+11 | 0.00 | 253.19 | 0.215849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123310.99 | 19-JAN-15:00 | 83205.69 | 19-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 0.440308E+11 | 0.00 | 295.21 | 0.305756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122032.23 | 27-FEB-16:00 | 90350.17 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.534965E+11 | 0.00 | 360.99 | 0.396660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144840.10 | 07-MAR-06:02 | 104574.28 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.866360E+11 | 0.00 | 408.23 | 0.652177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159578.45 | 26-APR-05:02 | 119870.28 | 26-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.143674E+12 | 0.00 | 485.19 | 0.107950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234436.44 | 24-MAY-05:02 | 147051.59 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.149056E+12 | 0.00 | 495.98 | 0.113927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 182076.64 | 19-JUN-05:02 | 139550.10 | 16-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.154574E+12 | 0.00 | 515.05 | 0.112965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 201930.60 | 27-JUL-03:02 | 146936.65 | 20-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.157917E+12 | 0.00 | 509.03 | 0.115222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 212218.32 | 23-AUG-03:02 | 147498.35 | 03-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.138163E+12 | 0.00 | 469.81 | 0.957260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 240696.43 | 05-SEP-04:11 | 140509.56 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.120021E+12 | 0.00 | 451.34 | 0.893688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206501.13 | 06-OCT-03:02 | 147080.15 | 06-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.626074E+11 | 0.00 | 386.54 | 0.478871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166848.53 | 01-NOV-05:02 | 128779.38 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.433980E+11 | 0.00 | 297.68 | 0.314509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134246.73 | 15-DEC-06:03 | 94824.36 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118390E+13 | 0.00 | 4928.24 | 0.871540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.303282E+11 | 0.00 | 253.19 | 0.215849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122032.23 | 83205.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.157917E+12 | 0.00 | 515.05 | 0.115222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 240696.43 | 147498.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.203163E+11 | 0.00 | 145.35 | 0.158448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120528.60 | 01-JAN-16:12 | 97241.30 | 30-JAN-05:15 | 0.00 | 0.00 | 0.00 |
February | 0.237956E+11 | 0.00 | 190.53 | 0.193774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117803.38 | 03-FEB-05:12 | 101361.26 | 21-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.325190E+11 | 0.00 | 238.29 | 0.276503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140960.90 | 07-MAR-05:11 | 93505.33 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 |
April | 0.512819E+11 | 0.00 | 349.58 | 0.446918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138277.68 | 26-APR-04:12 | 84763.60 | 24-APR-04:53 | 0.00 | 0.00 | 0.00 |
May | 0.953758E+11 | 0.00 | 424.13 | 0.731138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164826.03 | 29-MAY-11:20 | 86157.34 | 29-MAY-18:50 | 0.00 | 0.00 | 0.00 |
June | 0.100442E+12 | 0.00 | 421.62 | 0.746899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162971.22 | 19-JUN-03:02 | 88911.18 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.109203E+12 | 0.00 | 414.74 | 0.760260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167486.31 | 03-JUL-03:02 | 85832.43 | 05-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.121463E+12 | 0.00 | 464.88 | 0.871028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164242.89 | 06-AUG-17:20 | 89674.88 | 28-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.103109E+12 | 0.00 | 428.58 | 0.741632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160914.75 | 24-SEP-16:01 | 90860.05 | 05-SEP-04:23 | 0.00 | 0.00 | 0.00 |
October | 0.887705E+11 | 0.00 | 404.00 | 0.674879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170718.78 | 15-OCT-15:38 | 91473.68 | 09-OCT-17:08 | 0.00 | 0.00 | 0.00 |
November | 0.489548E+11 | 0.00 | 303.77 | 0.403978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142478.22 | 01-NOV-04:15 | 88879.35 | 05-NOV-15:18 | 0.00 | 0.00 | 0.00 |
December | 0.317500E+11 | 0.00 | 204.59 | 0.256639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141806.98 | 15-DEC-05:12 | 84824.61 | 12-DEC-05:14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.826981E+12 | 0.00 | 3990.06 | 0.626210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.203163E+11 | 0.00 | 145.35 | 0.158448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117803.38 | 84763.60 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.121463E+12 | 0.00 | 464.88 | 0.871028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170718.78 | 101361.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.382904E+11 | 0.118644E+11 | 534.03 | 0.341162E+11 | 0.417421E+10 | 0.00 | 0.49 | 31-JAN-12:50 | 0.01 | 28-JAN-10:07 | 206710.47 | 31-JAN-12:50 | 127695.78 | 02-JAN-15:00 | 81442.71 | 31-JAN-12:50 | 50169.67 | 31-JAN-12:50 | 0.00 |
February | 0.147440E+12 | 0.383266E+11 | 494.56 | 0.137605E+12 | 0.983564E+10 | 0.00 | 0.72 | 24-FEB-10:30 | 0.00 | 03-FEB-20:20 | 310688.50 | 24-FEB-10:30 | 217821.93 | 24-FEB-13:05 | 112095.02 | 24-FEB-10:20 | 72270.11 | 24-FEB-10:30 | 0.00 |
March | 0.360646E+12 | 0.926839E+11 | 699.18 | 0.334091E+12 | 0.265546E+11 | 0.00 | 0.95 | 31-MAR-24:00 | 0.01 | 11-MAR-17:13 | 393382.55 | 31-MAR-24:00 | 393382.55 | 31-MAR-24:00 | 169281.52 | 29-MAR-08:40 | 96482.29 | 30-MAR-13:00 | 0.00 |
April | 0.853578E+12 | 0.217778E+12 | 719.83 | 0.778393E+12 | 0.751856E+11 | 0.00 | 1.00 | 04-APR-12:10 | 0.01 | 11-APR-06:50 | 428399.79 | 05-APR-07:15 | 403299.07 | 28-APR-21:02 | 220465.81 | 05-APR-07:10 | 127990.90 | 28-APR-15:00 | 0.00 |
May | 0.347644E+12 | 0.101274E+12 | 744.00 | 0.334917E+12 | 0.127271E+11 | 0.00 | 0.56 | 31-MAY-23:20 | 0.34 | 07-MAY-01:00 | 212295.34 | 31-MAY-23:10 | 210555.14 | 31-MAY-24:00 | 14625.84 | 23-MAY-16:00 | 54896.44 | 31-MAY-23:20 | 0.00 |
June | 0.574680E+12 | 0.168227E+12 | 720.00 | 0.560727E+12 | 0.139532E+11 | 0.00 | 0.78 | 30-JUN-23:55 | 0.55 | 01-JUN-05:00 | 302399.82 | 30-JUN-23:03 | 302165.61 | 30-JUN-24:00 | 17666.92 | 29-JUN-15:00 | 82416.44 | 30-JUN-23:20 | 0.00 |
July | 0.840727E+12 | 0.246595E+12 | 744.00 | 0.825771E+12 | 0.149566E+11 | 0.00 | 0.99 | 31-JUL-23:23 | 0.78 | 01-JUL-04:10 | 394456.57 | 31-JUL-23:55 | 394456.57 | 31-JUL-23:55 | 16547.80 | 12-JUL-12:50 | 116091.94 | 21-JUL-16:00 | 0.00 |
August | 0.107906E+13 | 0.306089E+12 | 744.00 | 0.106521E+13 | 0.138474E+11 | 0.00 | 1.00 | 01-AUG-06:40 | 0.39 | 31-AUG-24:00 | 423562.46 | 07-AUG-14:00 | 409616.88 | 06-AUG-15:54 | 89469.74 | 20-AUG-04:10 | 134496.65 | 30-AUG-16:00 | 0.00 |
September | 0.340724E+12 | 0.972231E+11 | 720.00 | 0.327114E+12 | 0.136103E+11 | 0.00 | 0.55 | 30-SEP-23:20 | 0.34 | 22-SEP-06:10 | 212878.39 | 30-SEP-24:00 | 211605.14 | 30-SEP-24:00 | 14011.68 | 18-SEP-10:40 | 54317.16 | 30-SEP-23:20 | 0.00 |
October | 0.485368E+12 | 0.136100E+12 | 708.31 | 0.470419E+12 | 0.149497E+11 | 0.00 | 0.76 | 31-OCT-24:00 | 0.01 | 18-OCT-04:12 | 303514.43 | 31-OCT-24:00 | 303514.43 | 31-OCT-24:00 | 80873.59 | 31-OCT-11:00 | 79184.37 | 05-OCT-15:00 | 0.00 |
November | 0.417925E+12 | 0.108799E+12 | 679.49 | 0.381085E+12 | 0.368399E+11 | 0.00 | 0.86 | 28-NOV-09:00 | 0.01 | 26-NOV-09:40 | 358650.74 | 28-NOV-09:00 | 311604.57 | 03-NOV-14:00 | 132715.05 | 28-NOV-08:50 | 99154.86 | 02-NOV-13:00 | 0.00 |
December | 0.499357E+12 | 0.124975E+12 | 718.97 | 0.447798E+12 | 0.515592E+11 | 0.00 | 1.00 | 08-DEC-11:20 | 0.01 | 19-DEC-21:30 | 431788.40 | 28-DEC-09:50 | 402932.62 | 13-DEC-18:00 | 235944.04 | 28-DEC-09:40 | 120444.25 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.598544E+13 | 0.164994E+13 | 8226.37 | 0.569724E+13 | 0.288193E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.382904E+11 | 0.118644E+11 | 494.56 | 0.341162E+11 | 0.417421E+10 | 0.00 | 0.49 | 0.00 | 206710.47 | 127695.78 | 14011.68 | 50169.67 | 0.00 | ||||||
Maximum of Months | 0.107906E+13 | 0.306089E+12 | 744.00 | 0.106521E+13 | 0.751856E+11 | 0.00 | 1.00 | 0.78 | 431788.40 | 409616.88 | 235944.04 | 134496.65 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.500004E+10 | 0.113324E+10 | 744.00 | 0.489472E+10 | 0.105316E+09 | 0.00 | 0.34 | 01-JAN-17:03 | 0.14 | 05-JAN-07:55 | 2718.81 | 19-JAN-17:00 | 2670.29 | 01-JAN-17:17 | 398.64 | 31-JAN-17:00 | 704.22 | 02-JAN-15:00 | 0.00 |
February | 0.945244E+10 | 0.206303E+10 | 672.00 | 0.926618E+10 | 0.186265E+09 | 0.00 | 0.57 | 26-FEB-17:42 | 0.39 | 17-FEB-07:20 | 4714.93 | 26-FEB-17:54 | 4714.93 | 26-FEB-17:54 | 393.39 | 24-FEB-17:00 | 1259.06 | 02-FEB-13:20 | 0.00 |
March | 0.156588E+11 | 0.344335E+10 | 744.00 | 0.154535E+11 | 0.205244E+09 | 0.00 | 0.88 | 31-MAR-24:00 | 0.60 | 11-MAR-08:00 | 7680.64 | 31-MAR-24:00 | 7680.64 | 31-MAR-24:00 | 480.70 | 07-MAR-15:00 | 1901.42 | 30-MAR-13:00 | 0.00 |
April | 0.204232E+11 | 0.487265E+10 | 720.00 | 0.201307E+11 | 0.292502E+09 | 0.00 | 1.00 | 28-APR-12:50 | 0.31 | 30-APR-23:55 | 8597.65 | 28-APR-17:20 | 8505.87 | 16-APR-18:15 | 551.99 | 28-APR-17:30 | 2685.94 | 28-APR-15:00 | 0.00 |
May | 0.642048E+10 | 0.183532E+10 | 744.00 | 0.591644E+10 | 0.504039E+09 | 0.00 | 0.50 | 31-MAY-23:20 | 0.26 | 02-MAY-06:10 | 4057.69 | 31-MAY-23:10 | 3966.77 | 31-MAY-24:00 | 548.16 | 23-MAY-16:00 | 1030.77 | 31-MAY-23:20 | 0.00 |
June | 0.112072E+11 | 0.321944E+10 | 720.00 | 0.106254E+11 | 0.581839E+09 | 0.00 | 0.71 | 30-JUN-23:55 | 0.48 | 01-JUN-06:10 | 5863.84 | 30-JUN-23:03 | 5842.81 | 30-JUN-24:00 | 682.70 | 29-JUN-15:00 | 1604.00 | 29-JUN-14:00 | 0.00 |
July | 0.166897E+11 | 0.480878E+10 | 744.00 | 0.160371E+11 | 0.652530E+09 | 0.00 | 0.91 | 31-JUL-23:55 | 0.70 | 15-JUL-06:00 | 7719.89 | 31-JUL-24:00 | 7718.29 | 31-JUL-23:55 | 666.06 | 12-JUL-10:00 | 2358.40 | 21-JUL-16:00 | 0.00 |
August | 0.217761E+11 | 0.616973E+10 | 744.00 | 0.211186E+11 | 0.657475E+09 | 0.00 | 1.00 | 01-AUG-10:30 | 0.33 | 31-AUG-24:00 | 8784.00 | 07-AUG-13:40 | 8297.21 | 06-AUG-17:55 | 739.52 | 07-AUG-13:40 | 2822.42 | 30-AUG-16:00 | 0.00 |
September | 0.625484E+10 | 0.175008E+10 | 720.00 | 0.571383E+10 | 0.541003E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.26 | 07-SEP-21:00 | 4019.99 | 30-SEP-24:00 | 3989.00 | 30-SEP-24:00 | 583.00 | 18-SEP-14:30 | 1018.31 | 09-SEP-17:00 | 0.00 |
October | 0.113695E+11 | 0.299231E+10 | 744.00 | 0.109175E+11 | 0.451968E+09 | 0.00 | 0.69 | 31-OCT-24:00 | 0.43 | 28-OCT-07:00 | 5854.39 | 31-OCT-24:00 | 5844.30 | 31-OCT-24:00 | 685.11 | 24-OCT-14:05 | 1584.22 | 05-OCT-15:00 | 0.00 |
November | 0.154616E+11 | 0.348474E+10 | 720.00 | 0.152084E+11 | 0.253215E+09 | 0.00 | 0.80 | 02-NOV-16:00 | 0.62 | 15-NOV-07:10 | 6709.07 | 07-NOV-16:40 | 6531.26 | 12-NOV-17:10 | 560.58 | 01-NOV-11:00 | 1971.43 | 01-NOV-14:00 | 0.00 |
December | 0.207200E+11 | 0.441960E+10 | 744.00 | 0.205395E+11 | 0.180522E+09 | 0.00 | 1.00 | 15-DEC-17:00 | 0.78 | 20-DEC-07:40 | 8667.17 | 14-DEC-17:00 | 8398.00 | 10-DEC-16:53 | 565.40 | 12-DEC-15:00 | 2503.83 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.160434E+12 | 0.401923E+11 | 8760.00 | 0.155822E+12 | 0.461192E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.500004E+10 | 0.113324E+10 | 672.00 | 0.489472E+10 | 0.105316E+09 | 0.00 | 0.34 | 0.14 | 2718.81 | 2670.29 | 393.39 | 704.22 | 0.00 | ||||||
Maximum of Months | 0.217761E+11 | 0.616973E+10 | 744.00 | 0.211186E+11 | 0.657475E+09 | 0.00 | 1.00 | 0.78 | 8784.00 | 8505.87 | 739.52 | 2822.42 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.351623E+11 | 0.818706E+10 | 744.00 | 0.341466E+11 | 0.101574E+10 | 0.00 | 0.33 | 19-JAN-17:00 | 0.04 | 10-JAN-07:10 | 25419.11 | 19-JAN-17:00 | 22879.44 | 01-JAN-17:30 | 3960.36 | 31-JAN-17:00 | 6533.83 | 19-JAN-17:00 | 0.00 |
February | 0.804711E+11 | 0.177921E+11 | 672.00 | 0.786294E+11 | 0.184173E+10 | 0.00 | 0.56 | 27-FEB-17:00 | 0.28 | 06-FEB-07:10 | 44065.51 | 27-FEB-17:00 | 43330.78 | 26-FEB-17:54 | 3906.76 | 24-FEB-17:00 | 11780.61 | 24-FEB-14:00 | 0.00 |
March | 0.141251E+12 | 0.313525E+11 | 744.00 | 0.139210E+12 | 0.204062E+10 | 0.00 | 0.86 | 31-MAR-24:00 | 0.50 | 13-MAR-06:55 | 71809.06 | 31-MAR-24:00 | 71809.06 | 31-MAR-24:00 | 4788.74 | 07-MAR-15:00 | 18105.63 | 30-MAR-13:00 | 0.00 |
April | 0.192445E+12 | 0.460661E+11 | 720.00 | 0.189521E+12 | 0.292361E+10 | 0.00 | 1.00 | 28-APR-12:40 | 0.29 | 30-APR-23:55 | 82229.22 | 28-APR-17:20 | 79766.64 | 16-APR-18:15 | 5464.84 | 28-APR-17:30 | 25675.68 | 28-APR-15:00 | 0.00 |
May | 0.593120E+11 | 0.169985E+11 | 744.00 | 0.543394E+11 | 0.497263E+10 | 0.00 | 0.49 | 31-MAY-23:20 | 0.25 | 02-MAY-06:10 | 38224.32 | 31-MAY-23:10 | 37168.52 | 31-MAY-24:00 | 5406.61 | 23-MAY-16:00 | 9712.46 | 31-MAY-23:20 | 0.00 |
June | 0.106174E+12 | 0.305255E+11 | 720.00 | 0.100389E+12 | 0.578503E+10 | 0.00 | 0.71 | 30-JUN-23:55 | 0.46 | 07-JUN-06:10 | 56528.30 | 30-JUN-23:55 | 56356.97 | 30-JUN-24:00 | 6774.08 | 29-JUN-15:00 | 15367.98 | 29-JUN-14:00 | 0.00 |
July | 0.158805E+12 | 0.457789E+11 | 744.00 | 0.152298E+12 | 0.650734E+10 | 0.00 | 0.91 | 31-JUL-23:55 | 0.69 | 11-JUL-21:20 | 73901.90 | 31-JUL-24:00 | 73873.71 | 31-JUL-24:00 | 6651.09 | 12-JUL-10:00 | 22609.51 | 21-JUL-16:00 | 0.00 |
August | 0.206729E+12 | 0.586400E+11 | 744.00 | 0.200154E+12 | 0.657500E+10 | 0.00 | 1.00 | 01-AUG-09:50 | 0.29 | 31-AUG-24:00 | 83611.52 | 14-AUG-16:00 | 77558.79 | 03-AUG-18:00 | 7310.00 | 07-AUG-13:40 | 26977.47 | 30-AUG-16:00 | 0.00 |
September | 0.569287E+11 | 0.159823E+11 | 720.00 | 0.516073E+11 | 0.532134E+10 | 0.00 | 0.48 | 30-SEP-23:50 | 0.24 | 28-SEP-06:10 | 37263.99 | 30-SEP-24:00 | 36936.72 | 30-SEP-24:00 | 5799.86 | 18-SEP-14:30 | 9454.69 | 09-SEP-17:00 | 0.00 |
October | 0.105621E+12 | 0.279284E+11 | 744.00 | 0.101134E+12 | 0.448671E+10 | 0.00 | 0.67 | 31-OCT-24:00 | 0.38 | 28-OCT-07:00 | 54238.24 | 31-OCT-24:00 | 54113.87 | 31-OCT-24:00 | 6829.33 | 24-OCT-14:05 | 15093.69 | 05-OCT-15:00 | 0.00 |
November | 0.140840E+12 | 0.320116E+11 | 720.00 | 0.138326E+12 | 0.251448E+10 | 0.00 | 0.80 | 02-NOV-16:00 | 0.56 | 15-NOV-07:40 | 64109.61 | 07-NOV-16:50 | 60609.65 | 06-NOV-17:00 | 5600.04 | 01-NOV-11:00 | 18807.20 | 01-NOV-14:00 | 0.00 |
December | 0.187339E+12 | 0.403770E+11 | 744.00 | 0.185534E+12 | 0.180496E+10 | 0.00 | 1.00 | 15-DEC-17:00 | 0.70 | 20-DEC-07:10 | 82357.51 | 14-DEC-17:00 | 78069.53 | 15-DEC-17:00 | 5644.47 | 12-DEC-15:00 | 23843.12 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.147108E+13 | 0.371640E+12 | 8760.00 | 0.142529E+13 | 0.457892E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.351623E+11 | 0.818706E+10 | 672.00 | 0.341466E+11 | 0.101574E+10 | 0.00 | 0.33 | 0.04 | 25419.11 | 22879.44 | 3906.76 | 6533.83 | 0.00 | ||||||
Maximum of Months | 0.206729E+12 | 0.586400E+11 | 744.00 | 0.200154E+12 | 0.657500E+10 | 0.00 | 1.00 | 0.70 | 83611.52 | 79766.64 | 7310.00 | 26977.47 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.246367E+10 | 0.589996E+09 | 671.56 | 0.236381E+10 | 99854633.74 | 0.00 | 0.33 | 19-JAN-17:00 | 0.00 | 04-JAN-07:10 | 2623.37 | 19-JAN-17:00 | 2375.56 | 01-JAN-17:17 | 398.81 | 31-JAN-17:00 | 674.55 | 19-JAN-16:50 | 0.00 |
February | 0.726646E+10 | 0.162665E+10 | 671.75 | 0.708331E+10 | 0.183146E+09 | 0.00 | 0.55 | 27-FEB-17:00 | 0.00 | 05-FEB-09:45 | 4480.53 | 27-FEB-17:00 | 4391.22 | 26-FEB-17:43 | 391.59 | 24-FEB-17:00 | 1200.76 | 24-FEB-14:00 | 0.00 |
March | 0.135633E+11 | 0.304002E+10 | 744.00 | 0.133598E+11 | 0.203456E+09 | 0.00 | 0.84 | 31-MAR-24:00 | 0.37 | 12-MAR-07:50 | 7094.97 | 31-MAR-24:00 | 7094.97 | 31-MAR-24:00 | 479.18 | 07-MAR-15:00 | 1834.66 | 30-MAR-13:00 | 0.00 |
April | 0.191377E+11 | 0.460336E+10 | 720.00 | 0.188458E+11 | 0.291870E+09 | 0.00 | 1.00 | 28-APR-13:30 | 0.28 | 30-APR-23:55 | 8335.05 | 28-APR-17:20 | 8186.40 | 23-APR-17:58 | 543.72 | 28-APR-17:30 | 2616.39 | 28-APR-15:00 | 0.00 |
May | 0.610987E+10 | 0.175227E+10 | 744.00 | 0.560978E+10 | 0.500092E+09 | 0.00 | 0.48 | 31-MAY-23:20 | 0.24 | 02-MAY-06:10 | 3810.97 | 31-MAY-23:10 | 3698.66 | 31-MAY-24:00 | 547.78 | 23-MAY-16:00 | 970.16 | 31-MAY-23:20 | 0.00 |
June | 0.108075E+11 | 0.310972E+10 | 720.00 | 0.102280E+11 | 0.579555E+09 | 0.00 | 0.71 | 30-JUN-23:55 | 0.44 | 07-JUN-06:10 | 5698.59 | 30-JUN-23:55 | 5681.43 | 30-JUN-24:00 | 680.96 | 29-JUN-15:00 | 1574.43 | 29-JUN-14:00 | 0.00 |
July | 0.160785E+11 | 0.464053E+10 | 744.00 | 0.154276E+11 | 0.650880E+09 | 0.00 | 0.89 | 31-JUL-23:55 | 0.67 | 15-JUL-06:00 | 7391.30 | 31-JUL-24:00 | 7388.31 | 31-JUL-24:00 | 666.76 | 12-JUL-10:00 | 2302.68 | 21-JUL-16:00 | 0.00 |
August | 0.208483E+11 | 0.592667E+10 | 744.00 | 0.201905E+11 | 0.657728E+09 | 0.00 | 1.00 | 01-AUG-11:40 | 0.29 | 31-AUG-24:00 | 8486.67 | 09-AUG-17:00 | 8032.02 | 06-AUG-17:35 | 726.60 | 09-AUG-17:00 | 2749.09 | 30-AUG-16:00 | 0.00 |
September | 0.582362E+10 | 0.163764E+10 | 720.00 | 0.528939E+10 | 0.534230E+09 | 0.00 | 0.47 | 30-SEP-23:30 | 0.23 | 28-SEP-06:20 | 3761.03 | 30-SEP-24:00 | 3729.16 | 30-SEP-24:00 | 580.59 | 18-SEP-14:30 | 1008.55 | 09-SEP-17:00 | 0.00 |
October | 0.105314E+11 | 0.279878E+10 | 744.00 | 0.100826E+11 | 0.448776E+09 | 0.00 | 0.65 | 31-OCT-24:00 | 0.30 | 28-OCT-07:00 | 5365.55 | 31-OCT-24:00 | 5352.61 | 31-OCT-24:00 | 684.25 | 24-OCT-14:05 | 1544.06 | 05-OCT-15:00 | 0.00 |
November | 0.135610E+11 | 0.311217E+10 | 720.00 | 0.133106E+11 | 0.250436E+09 | 0.00 | 0.79 | 02-NOV-16:00 | 0.47 | 16-NOV-07:05 | 6470.34 | 07-NOV-16:40 | 6130.94 | 06-NOV-17:00 | 560.64 | 01-NOV-11:00 | 1905.02 | 01-NOV-14:00 | 0.00 |
December | 0.178591E+11 | 0.389457E+10 | 744.00 | 0.176792E+11 | 0.179844E+09 | 0.00 | 0.99 | 15-DEC-17:00 | 0.60 | 20-DEC-07:10 | 8297.11 | 14-DEC-17:00 | 7881.24 | 15-DEC-17:00 | 564.60 | 12-DEC-15:00 | 2403.17 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.144050E+12 | 0.367324E+11 | 8687.31 | 0.139471E+12 | 0.457987E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.246367E+10 | 0.589996E+09 | 671.56 | 0.236381E+10 | 99854633.74 | 0.00 | 0.33 | 0.00 | 2623.37 | 2375.56 | 391.59 | 674.55 | 0.00 | ||||||
Maximum of Months | 0.208483E+11 | 0.592667E+10 | 744.00 | 0.201905E+11 | 0.657728E+09 | 0.00 | 1.00 | 0.67 | 8486.67 | 8186.40 | 726.60 | 2749.09 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.45 | 0.00 | 110.45 | 70.80 | 432.01 | 0.00 | 0.00 | 0.00 |
February | 130.31 | 0.00 | 130.31 | 99.60 | 367.45 | 0.00 | 0.00 | 0.00 |
March | 151.17 | 0.00 | 151.17 | 147.68 | 312.37 | 0.00 | 0.00 | 0.00 |
April | 178.41 | 0.73 | 177.68 | 240.78 | 187.05 | 0.00 | 0.00 | 0.00 |
May | 202.09 | 7.39 | 194.70 | 409.22 | 50.45 | 0.00 | 0.00 | 0.00 |
June | 229.82 | 15.91 | 213.90 | 484.22 | 40.08 | 0.00 | 0.00 | 0.00 |
July | 223.02 | 8.50 | 214.53 | 465.21 | 25.46 | 0.00 | 0.00 | 0.00 |
August | 199.72 | 1.57 | 198.15 | 417.77 | 37.87 | 0.00 | 0.00 | 0.00 |
September | 172.51 | 0.01 | 172.50 | 333.74 | 60.40 | 0.00 | 0.00 | 0.00 |
October | 149.91 | 0.00 | 149.91 | 266.69 | 116.84 | 0.00 | 0.00 | 0.00 |
November | 113.81 | 0.00 | 113.81 | 115.13 | 281.39 | 0.00 | 0.00 | 0.00 |
December | 102.68 | 0.00 | 102.68 | 75.80 | 382.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.82 | 2.85 | 160.97 | 261.52 | 190.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.68 | 0.00 | 102.68 | 70.80 | 25.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.82 | 15.91 | 214.53 | 484.22 | 432.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.45 | 0.00 | 110.45 | 70.80 | 432.01 | 0.00 | 0.00 | 0.00 |
February | 130.31 | 0.00 | 130.31 | 99.60 | 367.45 | 0.00 | 0.00 | 0.00 |
March | 151.17 | 0.00 | 151.17 | 147.68 | 312.37 | 0.00 | 0.00 | 0.00 |
April | 178.41 | 0.73 | 177.68 | 240.78 | 187.05 | 0.00 | 0.00 | 0.00 |
May | 202.09 | 7.39 | 194.70 | 409.22 | 50.45 | 0.00 | 0.00 | 0.00 |
June | 229.82 | 15.91 | 213.90 | 484.22 | 40.08 | 0.00 | 0.00 | 0.00 |
July | 223.02 | 8.50 | 214.53 | 465.21 | 25.46 | 0.00 | 0.00 | 0.00 |
August | 199.72 | 1.57 | 198.15 | 417.77 | 37.87 | 0.00 | 0.00 | 0.00 |
September | 172.51 | 0.01 | 172.50 | 333.74 | 60.40 | 0.00 | 0.00 | 0.00 |
October | 149.91 | 0.00 | 149.91 | 266.69 | 116.84 | 0.00 | 0.00 | 0.00 |
November | 113.81 | 0.00 | 113.81 | 115.13 | 281.39 | 0.00 | 0.00 | 0.00 |
December | 102.68 | 0.00 | 102.68 | 75.80 | 382.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.82 | 2.85 | 160.97 | 261.52 | 190.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.68 | 0.00 | 102.68 | 70.80 | 25.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.82 | 15.91 | 214.53 | 484.22 | 432.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.45 | 0.00 | 110.45 | 70.80 | 432.01 | 0.00 | 0.00 | 0.00 |
February | 130.31 | 0.00 | 130.31 | 99.60 | 367.45 | 0.00 | 0.00 | 0.00 |
March | 151.17 | 0.00 | 151.17 | 147.68 | 312.37 | 0.00 | 0.00 | 0.00 |
April | 178.41 | 0.73 | 177.68 | 240.78 | 187.05 | 0.00 | 0.00 | 0.00 |
May | 202.09 | 7.39 | 194.70 | 409.22 | 50.45 | 0.00 | 0.00 | 0.00 |
June | 229.82 | 15.91 | 213.90 | 484.22 | 40.08 | 0.00 | 0.00 | 0.00 |
July | 223.02 | 8.50 | 214.53 | 465.21 | 25.46 | 0.00 | 0.00 | 0.00 |
August | 199.72 | 1.57 | 198.15 | 417.77 | 37.87 | 0.00 | 0.00 | 0.00 |
September | 172.51 | 0.01 | 172.50 | 333.74 | 60.40 | 0.00 | 0.00 | 0.00 |
October | 149.91 | 0.00 | 149.91 | 266.69 | 116.84 | 0.00 | 0.00 | 0.00 |
November | 113.81 | 0.00 | 113.81 | 115.13 | 281.39 | 0.00 | 0.00 | 0.00 |
December | 102.68 | 0.00 | 102.68 | 75.80 | 382.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.82 | 2.85 | 160.97 | 261.52 | 190.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.68 | 0.00 | 102.68 | 70.80 | 25.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.82 | 15.91 | 214.53 | 484.22 | 432.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.45 | 0.00 | 110.45 | 70.80 | 432.01 | 0.00 | 0.00 | 0.00 |
February | 130.31 | 0.00 | 130.31 | 99.60 | 367.45 | 0.00 | 0.00 | 0.00 |
March | 151.17 | 0.00 | 151.17 | 147.68 | 312.37 | 0.00 | 0.00 | 0.00 |
April | 178.41 | 0.73 | 177.68 | 240.78 | 187.05 | 0.00 | 0.00 | 0.00 |
May | 202.09 | 7.39 | 194.70 | 409.22 | 50.45 | 0.00 | 0.00 | 0.00 |
June | 229.82 | 15.91 | 213.90 | 484.22 | 40.08 | 0.00 | 0.00 | 0.00 |
July | 223.02 | 8.50 | 214.53 | 465.21 | 25.46 | 0.00 | 0.00 | 0.00 |
August | 199.72 | 1.57 | 198.15 | 417.77 | 37.87 | 0.00 | 0.00 | 0.00 |
September | 172.51 | 0.01 | 172.50 | 333.74 | 60.40 | 0.00 | 0.00 | 0.00 |
October | 149.91 | 0.00 | 149.91 | 266.69 | 116.84 | 0.00 | 0.00 | 0.00 |
November | 113.81 | 0.00 | 113.81 | 115.13 | 281.39 | 0.00 | 0.00 | 0.00 |
December | 102.68 | 0.00 | 102.68 | 75.80 | 382.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.82 | 2.85 | 160.97 | 261.52 | 190.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.68 | 0.00 | 102.68 | 70.80 | 25.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.82 | 15.91 | 214.53 | 484.22 | 432.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.45 | 0.00 | 110.45 | 70.79 | 432.00 | 0.00 | 0.00 | 0.00 |
February | 130.30 | 0.00 | 130.30 | 99.60 | 367.43 | 0.00 | 0.00 | 0.00 |
March | 151.16 | 0.00 | 151.16 | 147.67 | 312.35 | 0.00 | 0.00 | 0.00 |
April | 178.41 | 0.73 | 177.67 | 240.77 | 187.05 | 0.00 | 0.00 | 0.00 |
May | 202.08 | 7.39 | 194.69 | 409.21 | 50.45 | 0.00 | 0.00 | 0.00 |
June | 229.81 | 15.91 | 213.90 | 484.20 | 40.08 | 0.00 | 0.00 | 0.00 |
July | 223.01 | 8.50 | 214.52 | 465.19 | 25.45 | 0.00 | 0.00 | 0.00 |
August | 199.71 | 1.57 | 198.14 | 417.75 | 37.87 | 0.00 | 0.00 | 0.00 |
September | 172.51 | 0.01 | 172.49 | 333.73 | 60.39 | 0.00 | 0.00 | 0.00 |
October | 149.91 | 0.00 | 149.91 | 266.68 | 116.83 | 0.00 | 0.00 | 0.00 |
November | 113.80 | 0.00 | 113.80 | 115.13 | 281.38 | 0.00 | 0.00 | 0.00 |
December | 102.68 | 0.00 | 102.68 | 75.80 | 382.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.82 | 2.85 | 160.97 | 261.51 | 190.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.68 | 0.00 | 102.68 | 70.79 | 25.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.81 | 15.91 | 214.52 | 484.20 | 432.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.85 | 160.83 | 155.02 | 363.79 | 440.72 | 0.00 | 0.00 | 0.00 |
February | 351.71 | 169.80 | 181.91 | 431.58 | 372.02 | 0.00 | 0.00 | 0.00 |
March | 413.73 | 199.53 | 214.20 | 556.08 | 316.23 | 0.00 | 0.00 | 0.00 |
April | 454.02 | 205.34 | 248.68 | 700.23 | 193.95 | 0.00 | 0.00 | 0.00 |
May | 467.97 | 202.92 | 265.05 | 865.87 | 55.62 | 0.00 | 0.00 | 0.00 |
June | 474.60 | 188.21 | 286.39 | 909.86 | 42.10 | 0.00 | 0.00 | 0.00 |
July | 457.58 | 167.45 | 290.13 | 879.11 | 24.52 | 0.00 | 0.00 | 0.00 |
August | 421.65 | 144.97 | 276.68 | 811.23 | 36.04 | 0.00 | 0.00 | 0.00 |
September | 373.50 | 128.41 | 245.09 | 682.76 | 65.51 | 0.00 | 0.00 | 0.00 |
October | 369.10 | 155.76 | 213.34 | 640.78 | 122.21 | 0.00 | 0.00 | 0.00 |
November | 326.78 | 166.70 | 160.08 | 449.25 | 283.41 | 0.00 | 0.00 | 0.00 |
December | 257.29 | 116.55 | 140.74 | 310.02 | 385.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 390.45 | 167.13 | 223.32 | 634.47 | 193.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.29 | 116.55 | 140.74 | 310.02 | 24.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 474.60 | 205.34 | 290.13 | 909.86 | 440.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.85 | 160.83 | 155.02 | 363.79 | 440.72 | 0.00 | 0.00 | 0.00 |
February | 351.71 | 169.80 | 181.91 | 431.58 | 372.02 | 0.00 | 0.00 | 0.00 |
March | 413.73 | 199.53 | 214.20 | 556.08 | 316.23 | 0.00 | 0.00 | 0.00 |
April | 454.02 | 205.34 | 248.68 | 700.23 | 193.95 | 0.00 | 0.00 | 0.00 |
May | 467.97 | 202.92 | 265.05 | 865.87 | 55.62 | 0.00 | 0.00 | 0.00 |
June | 474.60 | 188.21 | 286.39 | 909.86 | 42.10 | 0.00 | 0.00 | 0.00 |
July | 457.58 | 167.45 | 290.13 | 879.11 | 24.52 | 0.00 | 0.00 | 0.00 |
August | 421.65 | 144.97 | 276.68 | 811.23 | 36.04 | 0.00 | 0.00 | 0.00 |
September | 373.50 | 128.41 | 245.09 | 682.76 | 65.51 | 0.00 | 0.00 | 0.00 |
October | 369.10 | 155.76 | 213.34 | 640.78 | 122.21 | 0.00 | 0.00 | 0.00 |
November | 326.78 | 166.70 | 160.08 | 449.25 | 283.41 | 0.00 | 0.00 | 0.00 |
December | 257.29 | 116.55 | 140.74 | 310.02 | 385.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 390.45 | 167.13 | 223.32 | 634.47 | 193.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.29 | 116.55 | 140.74 | 310.02 | 24.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 474.60 | 205.34 | 290.13 | 909.86 | 440.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.84 | 160.83 | 155.01 | 363.78 | 440.71 | 0.00 | 0.00 | 0.00 |
February | 351.70 | 169.79 | 181.91 | 431.57 | 372.01 | 0.00 | 0.00 | 0.00 |
March | 413.72 | 199.52 | 214.19 | 556.07 | 316.22 | 0.00 | 0.00 | 0.00 |
April | 454.01 | 205.33 | 248.67 | 700.22 | 193.95 | 0.00 | 0.00 | 0.00 |
May | 467.96 | 202.92 | 265.04 | 865.86 | 55.62 | 0.00 | 0.00 | 0.00 |
June | 474.59 | 188.21 | 286.38 | 909.84 | 42.10 | 0.00 | 0.00 | 0.00 |
July | 457.57 | 167.45 | 290.13 | 879.10 | 24.52 | 0.00 | 0.00 | 0.00 |
August | 421.64 | 144.96 | 276.68 | 811.22 | 36.04 | 0.00 | 0.00 | 0.00 |
September | 373.49 | 128.41 | 245.09 | 682.74 | 65.51 | 0.00 | 0.00 | 0.00 |
October | 369.09 | 155.75 | 213.33 | 640.77 | 122.21 | 0.00 | 0.00 | 0.00 |
November | 326.77 | 166.70 | 160.07 | 449.24 | 283.41 | 0.00 | 0.00 | 0.00 |
December | 257.28 | 116.54 | 140.74 | 310.01 | 385.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 390.44 | 167.13 | 223.31 | 634.46 | 193.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.28 | 116.54 | 140.74 | 310.01 | 24.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 474.59 | 205.33 | 290.13 | 909.84 | 440.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 638.45 | 455.32 | 183.12 | 907.88 | 388.08 | 0.00 | 0.00 | 0.00 |
February | 579.04 | 374.80 | 204.24 | 840.13 | 335.95 | 0.00 | 0.00 | 0.00 |
March | 369.67 | 166.83 | 202.84 | 550.27 | 297.36 | 0.00 | 0.00 | 0.00 |
April | 273.99 | 64.20 | 209.79 | 451.05 | 190.91 | 0.00 | 0.00 | 0.00 |
May | 209.35 | 8.90 | 200.45 | 428.93 | 51.96 | 0.00 | 0.00 | 0.00 |
June | 206.80 | 1.93 | 204.88 | 436.95 | 41.54 | 0.00 | 0.00 | 0.00 |
July | 216.49 | 3.98 | 212.51 | 453.66 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 254.69 | 30.57 | 224.12 | 534.89 | 40.54 | 0.00 | 0.00 | 0.00 |
September | 305.58 | 80.53 | 225.05 | 595.21 | 64.46 | 0.00 | 0.00 | 0.00 |
October | 474.12 | 246.97 | 227.15 | 848.51 | 121.77 | 0.00 | 0.00 | 0.00 |
November | 603.34 | 415.41 | 187.94 | 930.13 | 264.50 | 0.00 | 0.00 | 0.00 |
December | 623.84 | 448.01 | 175.83 | 919.70 | 350.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 395.31 | 190.51 | 204.81 | 657.21 | 180.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 206.80 | 1.93 | 175.83 | 428.93 | 25.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 638.45 | 455.32 | 227.15 | 930.13 | 388.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 638.45 | 455.32 | 183.12 | 907.88 | 388.08 | 0.00 | 0.00 | 0.00 |
February | 579.04 | 374.80 | 204.24 | 840.13 | 335.95 | 0.00 | 0.00 | 0.00 |
March | 369.67 | 166.83 | 202.84 | 550.27 | 297.36 | 0.00 | 0.00 | 0.00 |
April | 273.99 | 64.20 | 209.79 | 451.05 | 190.91 | 0.00 | 0.00 | 0.00 |
May | 209.35 | 8.90 | 200.45 | 428.93 | 51.96 | 0.00 | 0.00 | 0.00 |
June | 206.80 | 1.93 | 204.88 | 436.95 | 41.54 | 0.00 | 0.00 | 0.00 |
July | 216.49 | 3.98 | 212.51 | 453.66 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 254.69 | 30.57 | 224.12 | 534.89 | 40.54 | 0.00 | 0.00 | 0.00 |
September | 305.58 | 80.53 | 225.05 | 595.21 | 64.46 | 0.00 | 0.00 | 0.00 |
October | 474.12 | 246.97 | 227.15 | 848.51 | 121.77 | 0.00 | 0.00 | 0.00 |
November | 603.34 | 415.41 | 187.93 | 930.13 | 264.50 | 0.00 | 0.00 | 0.00 |
December | 623.84 | 448.01 | 175.83 | 919.70 | 350.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 395.31 | 190.51 | 204.81 | 657.21 | 180.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 206.80 | 1.93 | 175.83 | 428.93 | 25.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 638.45 | 455.32 | 227.15 | 930.13 | 388.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 638.45 | 455.32 | 183.12 | 907.88 | 388.08 | 0.00 | 0.00 | 0.00 |
February | 579.04 | 374.80 | 204.24 | 840.13 | 335.95 | 0.00 | 0.00 | 0.00 |
March | 369.67 | 166.83 | 202.84 | 550.27 | 297.36 | 0.00 | 0.00 | 0.00 |
April | 273.99 | 64.20 | 209.79 | 451.05 | 190.91 | 0.00 | 0.00 | 0.00 |
May | 209.35 | 8.90 | 200.45 | 428.93 | 51.96 | 0.00 | 0.00 | 0.00 |
June | 206.80 | 1.93 | 204.88 | 436.95 | 41.54 | 0.00 | 0.00 | 0.00 |
July | 216.49 | 3.98 | 212.51 | 453.66 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 254.69 | 30.57 | 224.12 | 534.89 | 40.54 | 0.00 | 0.00 | 0.00 |
September | 305.58 | 80.53 | 225.05 | 595.21 | 64.46 | 0.00 | 0.00 | 0.00 |
October | 474.12 | 246.97 | 227.15 | 848.51 | 121.77 | 0.00 | 0.00 | 0.00 |
November | 603.34 | 415.41 | 187.94 | 930.13 | 264.50 | 0.00 | 0.00 | 0.00 |
December | 623.84 | 448.01 | 175.83 | 919.70 | 350.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 395.31 | 190.51 | 204.81 | 657.21 | 180.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 206.80 | 1.93 | 175.83 | 428.93 | 25.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 638.45 | 455.32 | 227.15 | 930.13 | 388.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 638.45 | 455.32 | 183.12 | 907.88 | 388.08 | 0.00 | 0.00 | 0.00 |
February | 579.04 | 374.80 | 204.24 | 840.13 | 335.95 | 0.00 | 0.00 | 0.00 |
March | 369.67 | 166.83 | 202.84 | 550.27 | 297.36 | 0.00 | 0.00 | 0.00 |
April | 273.99 | 64.20 | 209.79 | 451.05 | 190.91 | 0.00 | 0.00 | 0.00 |
May | 209.35 | 8.90 | 200.45 | 428.93 | 51.96 | 0.00 | 0.00 | 0.00 |
June | 206.80 | 1.93 | 204.88 | 436.95 | 41.54 | 0.00 | 0.00 | 0.00 |
July | 216.49 | 3.98 | 212.51 | 453.66 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 254.69 | 30.57 | 224.12 | 534.89 | 40.54 | 0.00 | 0.00 | 0.00 |
September | 305.58 | 80.53 | 225.05 | 595.21 | 64.46 | 0.00 | 0.00 | 0.00 |
October | 474.12 | 246.97 | 227.15 | 848.51 | 121.77 | 0.00 | 0.00 | 0.00 |
November | 603.34 | 415.41 | 187.93 | 930.13 | 264.50 | 0.00 | 0.00 | 0.00 |
December | 623.84 | 448.01 | 175.83 | 919.70 | 350.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 395.31 | 190.51 | 204.81 | 657.21 | 180.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 206.80 | 1.93 | 175.83 | 428.93 | 25.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 638.45 | 455.32 | 227.15 | 930.13 | 388.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 638.42 | 455.31 | 183.12 | 907.85 | 388.06 | 0.00 | 0.00 | 0.00 |
February | 579.01 | 374.79 | 204.23 | 840.10 | 335.93 | 0.00 | 0.00 | 0.00 |
March | 369.65 | 166.83 | 202.83 | 550.24 | 297.35 | 0.00 | 0.00 | 0.00 |
April | 273.98 | 64.20 | 209.78 | 451.04 | 190.90 | 0.00 | 0.00 | 0.00 |
May | 209.34 | 8.90 | 200.45 | 428.92 | 51.96 | 0.00 | 0.00 | 0.00 |
June | 206.80 | 1.93 | 204.87 | 436.93 | 41.53 | 0.00 | 0.00 | 0.00 |
July | 216.48 | 3.98 | 212.50 | 453.65 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 254.68 | 30.57 | 224.11 | 534.87 | 40.54 | 0.00 | 0.00 | 0.00 |
September | 305.57 | 80.53 | 225.04 | 595.18 | 64.46 | 0.00 | 0.00 | 0.00 |
October | 474.10 | 246.96 | 227.14 | 848.48 | 121.76 | 0.00 | 0.00 | 0.00 |
November | 603.32 | 415.39 | 187.93 | 930.09 | 264.49 | 0.00 | 0.00 | 0.00 |
December | 623.82 | 447.99 | 175.83 | 919.67 | 350.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 395.30 | 190.50 | 204.80 | 657.19 | 180.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 206.80 | 1.93 | 175.83 | 428.92 | 25.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 638.42 | 455.31 | 227.14 | 930.09 | 388.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 335.96 | 181.67 | 154.29 | 410.81 | 501.82 | 0.00 | 0.00 | 0.00 |
February | 380.38 | 192.52 | 187.85 | 481.66 | 444.55 | 0.00 | 0.00 | 0.00 |
March | 374.90 | 165.96 | 208.94 | 492.31 | 394.75 | 0.00 | 0.00 | 0.00 |
April | 465.64 | 214.20 | 251.43 | 701.12 | 263.10 | 0.00 | 0.00 | 0.00 |
May | 387.23 | 126.14 | 261.09 | 723.28 | 80.25 | 0.00 | 0.00 | 0.00 |
June | 430.17 | 150.84 | 279.33 | 816.08 | 74.15 | 0.00 | 0.00 | 0.00 |
July | 392.66 | 108.92 | 283.75 | 738.89 | 58.83 | 0.00 | 0.00 | 0.00 |
August | 397.03 | 121.54 | 275.50 | 743.00 | 83.98 | 0.00 | 0.00 | 0.00 |
September | 365.60 | 125.42 | 240.18 | 661.79 | 92.09 | 0.00 | 0.00 | 0.00 |
October | 374.30 | 161.73 | 212.57 | 644.53 | 165.98 | 0.00 | 0.00 | 0.00 |
November | 320.82 | 161.23 | 159.59 | 445.64 | 359.95 | 0.00 | 0.00 | 0.00 |
December | 308.60 | 164.11 | 144.49 | 388.27 | 480.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 377.56 | 155.82 | 221.74 | 604.38 | 249.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.60 | 108.92 | 144.49 | 388.27 | 58.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 465.64 | 214.20 | 283.75 | 816.08 | 501.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 335.96 | 181.67 | 154.29 | 410.81 | 501.82 | 0.00 | 0.00 | 0.00 |
February | 380.38 | 192.52 | 187.85 | 481.66 | 444.55 | 0.00 | 0.00 | 0.00 |
March | 374.90 | 165.96 | 208.94 | 492.31 | 394.75 | 0.00 | 0.00 | 0.00 |
April | 465.64 | 214.20 | 251.43 | 701.12 | 263.10 | 0.00 | 0.00 | 0.00 |
May | 387.23 | 126.14 | 261.09 | 723.28 | 80.25 | 0.00 | 0.00 | 0.00 |
June | 430.17 | 150.84 | 279.33 | 816.08 | 74.15 | 0.00 | 0.00 | 0.00 |
July | 392.66 | 108.92 | 283.75 | 738.89 | 58.83 | 0.00 | 0.00 | 0.00 |
August | 397.03 | 121.54 | 275.50 | 743.00 | 83.98 | 0.00 | 0.00 | 0.00 |
September | 365.60 | 125.42 | 240.18 | 661.79 | 92.09 | 0.00 | 0.00 | 0.00 |
October | 374.30 | 161.73 | 212.57 | 644.53 | 165.98 | 0.00 | 0.00 | 0.00 |
November | 320.82 | 161.23 | 159.59 | 445.64 | 359.95 | 0.00 | 0.00 | 0.00 |
December | 308.60 | 164.11 | 144.49 | 388.27 | 480.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 377.56 | 155.82 | 221.74 | 604.38 | 249.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.60 | 108.92 | 144.49 | 388.27 | 58.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 465.64 | 214.20 | 283.75 | 816.08 | 501.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 335.95 | 181.66 | 154.29 | 410.80 | 501.81 | 0.00 | 0.00 | 0.00 |
February | 380.37 | 192.52 | 187.85 | 481.65 | 444.54 | 0.00 | 0.00 | 0.00 |
March | 374.89 | 165.96 | 208.94 | 492.30 | 394.74 | 0.00 | 0.00 | 0.00 |
April | 465.63 | 214.20 | 251.43 | 701.11 | 263.10 | 0.00 | 0.00 | 0.00 |
May | 387.22 | 126.14 | 261.08 | 723.26 | 80.25 | 0.00 | 0.00 | 0.00 |
June | 430.16 | 150.83 | 279.33 | 816.06 | 74.15 | 0.00 | 0.00 | 0.00 |
July | 392.66 | 108.92 | 283.74 | 738.87 | 58.82 | 0.00 | 0.00 | 0.00 |
August | 397.03 | 121.53 | 275.49 | 742.98 | 83.98 | 0.00 | 0.00 | 0.00 |
September | 365.59 | 125.42 | 240.18 | 661.78 | 92.09 | 0.00 | 0.00 | 0.00 |
October | 374.29 | 161.73 | 212.56 | 644.52 | 165.98 | 0.00 | 0.00 | 0.00 |
November | 320.81 | 161.23 | 159.59 | 445.63 | 359.95 | 0.00 | 0.00 | 0.00 |
December | 308.59 | 164.11 | 144.49 | 388.26 | 480.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 377.55 | 155.81 | 221.74 | 604.37 | 249.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.59 | 108.92 | 144.49 | 388.26 | 58.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 465.63 | 214.20 | 283.74 | 816.06 | 501.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.27 | 0.00 | 552.27 | 426.25 | 1894.16 | 0.00 | 0.00 | 0.00 |
February | 651.54 | 0.00 | 651.54 | 569.91 | 1589.08 | 0.00 | 0.00 | 0.00 |
March | 755.84 | 0.00 | 755.84 | 805.49 | 1367.53 | 0.00 | 0.00 | 0.00 |
April | 892.06 | 3.66 | 888.40 | 1242.64 | 858.75 | 0.00 | 0.00 | 0.00 |
May | 1010.43 | 36.96 | 973.47 | 2054.63 | 239.98 | 0.00 | 0.00 | 0.00 |
June | 1149.07 | 79.56 | 1069.51 | 2427.07 | 205.66 | 0.00 | 0.00 | 0.00 |
July | 1115.10 | 42.48 | 1072.62 | 2337.27 | 132.99 | 0.00 | 0.00 | 0.00 |
August | 998.59 | 7.85 | 990.74 | 2113.25 | 189.07 | 0.00 | 0.00 | 0.00 |
September | 862.56 | 0.07 | 862.49 | 1684.07 | 273.70 | 0.00 | 0.00 | 0.00 |
October | 749.55 | 0.00 | 749.55 | 1361.38 | 530.26 | 0.00 | 0.00 | 0.00 |
November | 569.03 | 0.00 | 569.03 | 639.24 | 1213.15 | 0.00 | 0.00 | 0.00 |
December | 513.39 | 0.00 | 513.39 | 453.06 | 1617.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 819.11 | 14.26 | 804.85 | 1347.51 | 838.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.39 | 0.00 | 513.39 | 426.25 | 132.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1149.07 | 79.56 | 1072.62 | 2427.07 | 1894.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 947.54 | 482.49 | 465.05 | 1108.57 | 1211.86 | 0.00 | 0.00 | 0.00 |
February | 1055.12 | 509.38 | 545.73 | 1308.20 | 1024.41 | 0.00 | 0.00 | 0.00 |
March | 1241.16 | 598.58 | 642.58 | 1663.65 | 889.08 | 0.00 | 0.00 | 0.00 |
April | 1362.03 | 616.01 | 746.02 | 2075.46 | 583.35 | 0.00 | 0.00 | 0.00 |
May | 1403.89 | 608.75 | 795.14 | 2565.57 | 171.84 | 0.00 | 0.00 | 0.00 |
June | 1423.78 | 564.63 | 859.15 | 2696.54 | 146.60 | 0.00 | 0.00 | 0.00 |
July | 1372.73 | 502.34 | 870.38 | 2601.39 | 96.53 | 0.00 | 0.00 | 0.00 |
August | 1264.93 | 434.89 | 830.03 | 2401.46 | 135.94 | 0.00 | 0.00 | 0.00 |
September | 1120.49 | 385.22 | 735.27 | 2025.27 | 194.69 | 0.00 | 0.00 | 0.00 |
October | 1107.28 | 467.27 | 640.01 | 1900.45 | 361.42 | 0.00 | 0.00 | 0.00 |
November | 980.33 | 500.11 | 480.23 | 1347.79 | 793.96 | 0.00 | 0.00 | 0.00 |
December | 771.86 | 349.63 | 422.22 | 945.79 | 1057.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1171.32 | 501.38 | 669.94 | 1889.79 | 553.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 771.86 | 349.63 | 422.22 | 945.79 | 96.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1423.78 | 616.01 | 870.38 | 2696.54 | 1211.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3192.21 | 2276.60 | 915.61 | 4505.70 | 1882.40 | 0.00 | 0.00 | 0.00 |
February | 2895.15 | 1873.98 | 1021.17 | 4178.29 | 1613.71 | 0.00 | 0.00 | 0.00 |
March | 1848.33 | 834.15 | 1014.17 | 2749.25 | 1402.35 | 0.00 | 0.00 | 0.00 |
April | 1369.96 | 321.01 | 1048.94 | 2260.19 | 914.82 | 0.00 | 0.00 | 0.00 |
May | 1046.75 | 44.49 | 1002.26 | 2149.73 | 249.07 | 0.00 | 0.00 | 0.00 |
June | 1034.01 | 9.64 | 1024.37 | 2195.02 | 209.95 | 0.00 | 0.00 | 0.00 |
July | 1082.44 | 19.90 | 1062.54 | 2283.20 | 129.34 | 0.00 | 0.00 | 0.00 |
August | 1273.43 | 152.85 | 1120.58 | 2686.07 | 204.83 | 0.00 | 0.00 | 0.00 |
September | 1527.90 | 402.67 | 1125.23 | 2965.51 | 308.36 | 0.00 | 0.00 | 0.00 |
October | 2370.55 | 1234.83 | 1135.72 | 4214.63 | 600.67 | 0.00 | 0.00 | 0.00 |
November | 3016.68 | 2077.02 | 939.66 | 4626.07 | 1274.39 | 0.00 | 0.00 | 0.00 |
December | 3119.17 | 2240.02 | 879.15 | 4580.24 | 1670.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1976.55 | 952.52 | 1024.03 | 3278.43 | 867.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1034.01 | 9.64 | 879.15 | 2149.73 | 129.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3192.21 | 2276.60 | 1135.72 | 4626.07 | 1882.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1007.86 | 544.99 | 462.86 | 1275.14 | 1318.24 | 0.00 | 0.00 | 0.00 |
February | 1141.12 | 577.56 | 563.55 | 1496.61 | 1132.02 | 0.00 | 0.00 | 0.00 |
March | 1124.69 | 497.87 | 626.82 | 1528.76 | 980.95 | 0.00 | 0.00 | 0.00 |
April | 1396.89 | 642.60 | 754.30 | 2153.72 | 659.35 | 0.00 | 0.00 | 0.00 |
May | 1161.68 | 378.42 | 783.26 | 2187.45 | 206.53 | 0.00 | 0.00 | 0.00 |
June | 1290.49 | 452.51 | 837.99 | 2475.84 | 183.76 | 0.00 | 0.00 | 0.00 |
July | 1177.98 | 326.75 | 851.23 | 2263.62 | 127.15 | 0.00 | 0.00 | 0.00 |
August | 1191.09 | 364.61 | 826.48 | 2291.23 | 173.66 | 0.00 | 0.00 | 0.00 |
September | 1096.79 | 376.25 | 720.54 | 2002.28 | 230.75 | 0.00 | 0.00 | 0.00 |
October | 1122.89 | 485.19 | 637.70 | 1965.12 | 419.12 | 0.00 | 0.00 | 0.00 |
November | 962.45 | 483.69 | 478.76 | 1390.89 | 888.35 | 0.00 | 0.00 | 0.00 |
December | 925.79 | 492.32 | 433.47 | 1232.58 | 1147.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1132.66 | 467.45 | 665.21 | 1856.57 | 619.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 925.79 | 326.75 | 433.47 | 1232.58 | 127.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1396.89 | 642.60 | 851.23 | 2475.84 | 1318.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.27 | 0.00 | 552.27 | 460.09 | 1745.53 | 0.00 | 0.00 | 0.00 |
February | 651.54 | 0.00 | 651.54 | 598.97 | 1467.39 | 0.00 | 0.00 | 0.00 |
March | 755.84 | 0.00 | 755.84 | 823.95 | 1284.59 | 0.00 | 0.00 | 0.00 |
April | 892.06 | 3.66 | 888.40 | 1237.41 | 837.14 | 0.00 | 0.00 | 0.00 |
May | 1010.43 | 36.96 | 973.47 | 2020.13 | 256.80 | 0.00 | 0.00 | 0.00 |
June | 1149.07 | 79.56 | 1069.51 | 2387.33 | 223.08 | 0.00 | 0.00 | 0.00 |
July | 1115.10 | 42.48 | 1072.62 | 2292.50 | 149.54 | 0.00 | 0.00 | 0.00 |
August | 998.59 | 7.85 | 990.74 | 2077.03 | 204.17 | 0.00 | 0.00 | 0.00 |
September | 862.56 | 0.07 | 862.49 | 1651.45 | 285.72 | 0.00 | 0.00 | 0.00 |
October | 749.55 | 0.00 | 749.55 | 1347.16 | 520.58 | 0.00 | 0.00 | 0.00 |
November | 569.03 | 0.00 | 569.03 | 665.74 | 1120.86 | 0.00 | 0.00 | 0.00 |
December | 513.39 | 0.00 | 513.39 | 482.53 | 1486.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 819.11 | 14.26 | 804.85 | 1341.46 | 795.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.39 | 0.00 | 513.39 | 460.09 | 149.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1149.07 | 79.56 | 1072.62 | 2387.33 | 1745.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 947.54 | 482.49 | 465.05 | 1152.36 | 1112.22 | 0.00 | 0.00 | 0.00 |
February | 1055.12 | 509.38 | 545.73 | 1342.68 | 946.39 | 0.00 | 0.00 | 0.00 |
March | 1241.16 | 598.58 | 642.58 | 1681.32 | 839.76 | 0.00 | 0.00 | 0.00 |
April | 1362.03 | 616.01 | 746.02 | 2075.18 | 571.61 | 0.00 | 0.00 | 0.00 |
May | 1403.89 | 608.75 | 795.14 | 2547.91 | 181.63 | 0.00 | 0.00 | 0.00 |
June | 1423.78 | 564.63 | 859.15 | 2677.55 | 157.47 | 0.00 | 0.00 | 0.00 |
July | 1372.73 | 502.34 | 870.38 | 2579.88 | 106.82 | 0.00 | 0.00 | 0.00 |
August | 1264.93 | 434.89 | 830.03 | 2384.46 | 145.22 | 0.00 | 0.00 | 0.00 |
September | 1120.49 | 385.22 | 735.27 | 2011.20 | 201.15 | 0.00 | 0.00 | 0.00 |
October | 1107.28 | 467.27 | 640.01 | 1895.74 | 355.00 | 0.00 | 0.00 | 0.00 |
November | 980.33 | 500.11 | 480.23 | 1369.65 | 742.99 | 0.00 | 0.00 | 0.00 |
December | 771.86 | 349.63 | 422.22 | 977.07 | 972.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1171.32 | 501.38 | 669.94 | 1894.20 | 525.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 771.86 | 349.63 | 422.22 | 977.07 | 106.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1423.78 | 616.01 | 870.38 | 2677.55 | 1112.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3192.21 | 2276.60 | 915.61 | 4539.59 | 1755.73 | 0.00 | 0.00 | 0.00 |
February | 2895.15 | 1873.98 | 1021.17 | 4208.30 | 1506.92 | 0.00 | 0.00 | 0.00 |
March | 1848.33 | 834.15 | 1014.17 | 2761.64 | 1326.70 | 0.00 | 0.00 | 0.00 |
April | 1369.96 | 321.01 | 1048.94 | 2249.58 | 894.12 | 0.00 | 0.00 | 0.00 |
May | 1046.75 | 44.49 | 1002.26 | 2115.36 | 266.09 | 0.00 | 0.00 | 0.00 |
June | 1034.01 | 9.64 | 1024.37 | 2156.77 | 228.58 | 0.00 | 0.00 | 0.00 |
July | 1082.44 | 19.90 | 1062.54 | 2236.97 | 145.01 | 0.00 | 0.00 | 0.00 |
August | 1273.43 | 152.85 | 1120.58 | 2649.05 | 220.41 | 0.00 | 0.00 | 0.00 |
September | 1527.90 | 402.67 | 1125.23 | 2933.91 | 320.01 | 0.00 | 0.00 | 0.00 |
October | 2370.55 | 1234.83 | 1135.72 | 4194.57 | 593.56 | 0.00 | 0.00 | 0.00 |
November | 3016.68 | 2077.02 | 939.66 | 4639.58 | 1209.15 | 0.00 | 0.00 | 0.00 |
December | 3119.17 | 2240.02 | 879.15 | 4604.95 | 1558.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1976.55 | 952.52 | 1024.03 | 3269.57 | 831.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1034.01 | 9.64 | 879.15 | 2115.36 | 145.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3192.21 | 2276.60 | 1135.72 | 4639.58 | 1755.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1007.86 | 544.99 | 462.86 | 1291.18 | 1234.20 | 0.00 | 0.00 | 0.00 |
February | 1141.12 | 577.56 | 563.55 | 1508.06 | 1061.91 | 0.00 | 0.00 | 0.00 |
March | 1124.69 | 497.87 | 626.82 | 1532.84 | 931.77 | 0.00 | 0.00 | 0.00 |
April | 1396.89 | 642.60 | 754.30 | 2142.92 | 644.25 | 0.00 | 0.00 | 0.00 |
May | 1161.68 | 378.42 | 783.26 | 2165.47 | 215.33 | 0.00 | 0.00 | 0.00 |
June | 1290.49 | 452.51 | 837.99 | 2451.28 | 192.91 | 0.00 | 0.00 | 0.00 |
July | 1177.98 | 326.75 | 851.23 | 2237.36 | 135.74 | 0.00 | 0.00 | 0.00 |
August | 1191.09 | 364.61 | 826.48 | 2268.31 | 182.66 | 0.00 | 0.00 | 0.00 |
September | 1096.79 | 376.25 | 720.54 | 1983.03 | 236.61 | 0.00 | 0.00 | 0.00 |
October | 1122.89 | 485.19 | 637.70 | 1953.16 | 413.19 | 0.00 | 0.00 | 0.00 |
November | 962.45 | 483.69 | 478.76 | 1399.11 | 838.82 | 0.00 | 0.00 | 0.00 |
December | 925.79 | 492.32 | 433.47 | 1245.47 | 1072.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1132.66 | 467.45 | 665.21 | 1849.38 | 594.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 925.79 | 326.75 | 433.47 | 1245.47 | 135.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1396.89 | 642.60 | 851.23 | 2451.28 | 1234.20 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295841E+09 | 0.00 | 0.295841E+09 | 0.189622E+09 | 0.115710E+10 |
February | 0.315245E+09 | 0.00 | 0.315245E+09 | 0.240959E+09 | 0.888928E+09 |
March | 0.404895E+09 | 0.00 | 0.404895E+09 | 0.395548E+09 | 0.836640E+09 |
April | 0.462450E+09 | 1898057.14 | 0.460552E+09 | 0.624113E+09 | 0.484842E+09 |
May | 0.541273E+09 | 19798542.17 | 0.521475E+09 | 0.109607E+10 | 0.135129E+09 |
June | 0.595687E+09 | 41246703.62 | 0.554440E+09 | 0.125510E+10 | 0.103889E+09 |
July | 0.597345E+09 | 22757759.15 | 0.574588E+09 | 0.124602E+10 | 68180344.45 |
August | 0.534933E+09 | 4207320.32 | 0.530726E+09 | 0.111894E+10 | 0.101429E+09 |
September | 0.447157E+09 | 34439.89 | 0.447123E+09 | 0.865056E+09 | 0.156550E+09 |
October | 0.401523E+09 | 0.00 | 0.401523E+09 | 0.714306E+09 | 0.312931E+09 |
November | 0.294987E+09 | 0.00 | 0.294987E+09 | 0.298418E+09 | 0.729366E+09 |
December | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.203019E+09 | 0.102357E+10 |
Annual Sum or Average | 0.516636E+10 | 89942822.29 | 0.507641E+10 | 0.824717E+10 | 0.599856E+10 |
Minimum of Months | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.189622E+09 | 68180344.45 |
Maximum of Months | 0.597345E+09 | 41246703.62 | 0.574588E+09 | 0.125510E+10 | 0.115710E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295841E+09 | 0.00 | 0.295841E+09 | 0.189622E+09 | 0.115710E+10 |
February | 0.315244E+09 | 0.00 | 0.315244E+09 | 0.240959E+09 | 0.888928E+09 |
March | 0.404895E+09 | 0.00 | 0.404895E+09 | 0.395547E+09 | 0.836640E+09 |
April | 0.462450E+09 | 1898054.86 | 0.460552E+09 | 0.624113E+09 | 0.484842E+09 |
May | 0.541273E+09 | 19798518.42 | 0.521474E+09 | 0.109607E+10 | 0.135129E+09 |
June | 0.595687E+09 | 41246654.13 | 0.554440E+09 | 0.125510E+10 | 0.103889E+09 |
July | 0.597345E+09 | 22757731.84 | 0.574587E+09 | 0.124602E+10 | 68180259.89 |
August | 0.534933E+09 | 4207315.27 | 0.530726E+09 | 0.111894E+10 | 0.101429E+09 |
September | 0.447157E+09 | 34439.85 | 0.447122E+09 | 0.865056E+09 | 0.156550E+09 |
October | 0.401523E+09 | 0.00 | 0.401523E+09 | 0.714305E+09 | 0.312931E+09 |
November | 0.294987E+09 | 0.00 | 0.294987E+09 | 0.298417E+09 | 0.729366E+09 |
December | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.203019E+09 | 0.102357E+10 |
Annual Sum or Average | 0.516635E+10 | 89942714.37 | 0.507641E+10 | 0.824717E+10 | 0.599856E+10 |
Minimum of Months | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.189622E+09 | 68180259.89 |
Maximum of Months | 0.597345E+09 | 41246654.13 | 0.574587E+09 | 0.125510E+10 | 0.115710E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295841E+09 | 0.00 | 0.295841E+09 | 0.189622E+09 | 0.115710E+10 |
February | 0.315245E+09 | 0.00 | 0.315245E+09 | 0.240959E+09 | 0.888928E+09 |
March | 0.404895E+09 | 0.00 | 0.404895E+09 | 0.395548E+09 | 0.836640E+09 |
April | 0.462450E+09 | 1898057.14 | 0.460552E+09 | 0.624113E+09 | 0.484842E+09 |
May | 0.541273E+09 | 19798542.17 | 0.521475E+09 | 0.109607E+10 | 0.135129E+09 |
June | 0.595687E+09 | 41246703.62 | 0.554440E+09 | 0.125510E+10 | 0.103889E+09 |
July | 0.597345E+09 | 22757759.15 | 0.574588E+09 | 0.124602E+10 | 68180344.45 |
August | 0.534933E+09 | 4207320.32 | 0.530726E+09 | 0.111894E+10 | 0.101429E+09 |
September | 0.447157E+09 | 34439.89 | 0.447123E+09 | 0.865056E+09 | 0.156550E+09 |
October | 0.401523E+09 | 0.00 | 0.401523E+09 | 0.714306E+09 | 0.312931E+09 |
November | 0.294987E+09 | 0.00 | 0.294987E+09 | 0.298418E+09 | 0.729366E+09 |
December | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.203019E+09 | 0.102357E+10 |
Annual Sum or Average | 0.516636E+10 | 89942822.29 | 0.507641E+10 | 0.824717E+10 | 0.599856E+10 |
Minimum of Months | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.189622E+09 | 68180344.45 |
Maximum of Months | 0.597345E+09 | 41246703.62 | 0.574588E+09 | 0.125510E+10 | 0.115710E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295841E+09 | 0.00 | 0.295841E+09 | 0.189622E+09 | 0.115710E+10 |
February | 0.315244E+09 | 0.00 | 0.315244E+09 | 0.240959E+09 | 0.888928E+09 |
March | 0.404895E+09 | 0.00 | 0.404895E+09 | 0.395547E+09 | 0.836640E+09 |
April | 0.462450E+09 | 1898054.86 | 0.460552E+09 | 0.624113E+09 | 0.484842E+09 |
May | 0.541273E+09 | 19798518.42 | 0.521474E+09 | 0.109607E+10 | 0.135129E+09 |
June | 0.595687E+09 | 41246654.13 | 0.554440E+09 | 0.125510E+10 | 0.103889E+09 |
July | 0.597345E+09 | 22757731.84 | 0.574587E+09 | 0.124602E+10 | 68180259.89 |
August | 0.534933E+09 | 4207315.27 | 0.530726E+09 | 0.111894E+10 | 0.101429E+09 |
September | 0.447157E+09 | 34439.85 | 0.447122E+09 | 0.865056E+09 | 0.156550E+09 |
October | 0.401523E+09 | 0.00 | 0.401523E+09 | 0.714305E+09 | 0.312931E+09 |
November | 0.294987E+09 | 0.00 | 0.294987E+09 | 0.298417E+09 | 0.729366E+09 |
December | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.203019E+09 | 0.102357E+10 |
Annual Sum or Average | 0.516635E+10 | 89942714.37 | 0.507641E+10 | 0.824717E+10 | 0.599856E+10 |
Minimum of Months | 0.275018E+09 | 0.00 | 0.275018E+09 | 0.189622E+09 | 68180259.89 |
Maximum of Months | 0.597345E+09 | 41246654.13 | 0.574587E+09 | 0.125510E+10 | 0.115710E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295829E+09 | 0.00 | 0.295829E+09 | 0.189615E+09 | 0.115706E+10 |
February | 0.315232E+09 | 0.00 | 0.315232E+09 | 0.240950E+09 | 0.888892E+09 |
March | 0.404879E+09 | 0.00 | 0.404879E+09 | 0.395532E+09 | 0.836607E+09 |
April | 0.462432E+09 | 1897980.64 | 0.460534E+09 | 0.624088E+09 | 0.484823E+09 |
May | 0.541251E+09 | 19797744.20 | 0.521454E+09 | 0.109602E+10 | 0.135123E+09 |
June | 0.595663E+09 | 41245041.19 | 0.554418E+09 | 0.125505E+10 | 0.103885E+09 |
July | 0.597321E+09 | 22756841.91 | 0.574564E+09 | 0.124597E+10 | 68177596.48 |
August | 0.534912E+09 | 4207150.75 | 0.530705E+09 | 0.111890E+10 | 0.101425E+09 |
September | 0.447139E+09 | 34438.50 | 0.447104E+09 | 0.865021E+09 | 0.156543E+09 |
October | 0.401507E+09 | 0.00 | 0.401507E+09 | 0.714277E+09 | 0.312919E+09 |
November | 0.294975E+09 | 0.00 | 0.294975E+09 | 0.298406E+09 | 0.729337E+09 |
December | 0.275007E+09 | 0.00 | 0.275007E+09 | 0.203011E+09 | 0.102353E+10 |
Annual Sum or Average | 0.516615E+10 | 89939197.20 | 0.507621E+10 | 0.824684E+10 | 0.599832E+10 |
Minimum of Months | 0.275007E+09 | 0.00 | 0.275007E+09 | 0.189615E+09 | 68177596.48 |
Maximum of Months | 0.597321E+09 | 41245041.19 | 0.574564E+09 | 0.125505E+10 | 0.115706E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845971E+09 | 0.430772E+09 | 0.415200E+09 | 0.974370E+09 | 0.118043E+10 |
February | 0.850854E+09 | 0.410770E+09 | 0.440084E+09 | 0.104407E+10 | 0.899987E+09 |
March | 0.110812E+10 | 0.534417E+09 | 0.573705E+09 | 0.148940E+10 | 0.846987E+09 |
April | 0.117681E+10 | 0.532238E+09 | 0.644570E+09 | 0.181500E+10 | 0.502724E+09 |
May | 0.125340E+10 | 0.543500E+09 | 0.709904E+09 | 0.231915E+10 | 0.148982E+09 |
June | 0.123016E+10 | 0.487847E+09 | 0.742311E+09 | 0.235835E+10 | 0.109125E+09 |
July | 0.122558E+10 | 0.448497E+09 | 0.777086E+09 | 0.235462E+10 | 65665630.31 |
August | 0.112934E+10 | 0.388275E+09 | 0.741062E+09 | 0.217280E+10 | 96537488.49 |
September | 0.968114E+09 | 0.332835E+09 | 0.635280E+09 | 0.176970E+10 | 0.169798E+09 |
October | 0.988586E+09 | 0.417180E+09 | 0.571406E+09 | 0.171628E+10 | 0.327324E+09 |
November | 0.847016E+09 | 0.432096E+09 | 0.414920E+09 | 0.116445E+10 | 0.734608E+09 |
December | 0.689122E+09 | 0.312157E+09 | 0.376965E+09 | 0.830356E+09 | 0.103316E+10 |
Annual Sum or Average | 0.123131E+11 | 0.527058E+10 | 0.704249E+10 | 0.200085E+11 | 0.611533E+10 |
Minimum of Months | 0.689122E+09 | 0.312157E+09 | 0.376965E+09 | 0.830356E+09 | 65665630.31 |
Maximum of Months | 0.125340E+10 | 0.543500E+09 | 0.777086E+09 | 0.235835E+10 | 0.118043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845971E+09 | 0.430772E+09 | 0.415200E+09 | 0.974370E+09 | 0.118043E+10 |
February | 0.850854E+09 | 0.410770E+09 | 0.440084E+09 | 0.104407E+10 | 0.899987E+09 |
March | 0.110812E+10 | 0.534417E+09 | 0.573705E+09 | 0.148940E+10 | 0.846987E+09 |
April | 0.117681E+10 | 0.532238E+09 | 0.644570E+09 | 0.181500E+10 | 0.502724E+09 |
May | 0.125340E+10 | 0.543500E+09 | 0.709904E+09 | 0.231915E+10 | 0.148982E+09 |
June | 0.123016E+10 | 0.487847E+09 | 0.742311E+09 | 0.235835E+10 | 0.109125E+09 |
July | 0.122558E+10 | 0.448497E+09 | 0.777086E+09 | 0.235462E+10 | 65665630.31 |
August | 0.112934E+10 | 0.388275E+09 | 0.741062E+09 | 0.217280E+10 | 96537488.49 |
September | 0.968114E+09 | 0.332835E+09 | 0.635280E+09 | 0.176970E+10 | 0.169798E+09 |
October | 0.988586E+09 | 0.417180E+09 | 0.571406E+09 | 0.171628E+10 | 0.327324E+09 |
November | 0.847016E+09 | 0.432096E+09 | 0.414920E+09 | 0.116445E+10 | 0.734608E+09 |
December | 0.689122E+09 | 0.312157E+09 | 0.376965E+09 | 0.830356E+09 | 0.103316E+10 |
Annual Sum or Average | 0.123131E+11 | 0.527058E+10 | 0.704249E+10 | 0.200085E+11 | 0.611533E+10 |
Minimum of Months | 0.689122E+09 | 0.312157E+09 | 0.376965E+09 | 0.830356E+09 | 65665630.31 |
Maximum of Months | 0.125340E+10 | 0.543500E+09 | 0.777086E+09 | 0.235835E+10 | 0.118043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845956E+09 | 0.430764E+09 | 0.415192E+09 | 0.974353E+09 | 0.118040E+10 |
February | 0.850839E+09 | 0.410762E+09 | 0.440076E+09 | 0.104405E+10 | 0.899970E+09 |
March | 0.110810E+10 | 0.534407E+09 | 0.573695E+09 | 0.148938E+10 | 0.846972E+09 |
April | 0.117679E+10 | 0.532228E+09 | 0.644558E+09 | 0.181497E+10 | 0.502714E+09 |
May | 0.125338E+10 | 0.543490E+09 | 0.709891E+09 | 0.231911E+10 | 0.148979E+09 |
June | 0.123014E+10 | 0.487838E+09 | 0.742298E+09 | 0.235831E+10 | 0.109123E+09 |
July | 0.122556E+10 | 0.448489E+09 | 0.777071E+09 | 0.235457E+10 | 65664430.46 |
August | 0.112932E+10 | 0.388268E+09 | 0.741048E+09 | 0.217276E+10 | 96535724.54 |
September | 0.968097E+09 | 0.332828E+09 | 0.635268E+09 | 0.176967E+10 | 0.169795E+09 |
October | 0.988568E+09 | 0.417173E+09 | 0.571395E+09 | 0.171624E+10 | 0.327318E+09 |
November | 0.847001E+09 | 0.432088E+09 | 0.414912E+09 | 0.116442E+10 | 0.734594E+09 |
December | 0.689109E+09 | 0.312151E+09 | 0.376958E+09 | 0.830341E+09 | 0.103314E+10 |
Annual Sum or Average | 0.123128E+11 | 0.527049E+10 | 0.704236E+10 | 0.200082E+11 | 0.611522E+10 |
Minimum of Months | 0.689109E+09 | 0.312151E+09 | 0.376958E+09 | 0.830341E+09 | 65664430.46 |
Maximum of Months | 0.125338E+10 | 0.543490E+09 | 0.777071E+09 | 0.235831E+10 | 0.118040E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171002E+10 | 0.121954E+10 | 0.490479E+09 | 0.243167E+10 | 0.103943E+10 |
February | 0.140081E+10 | 0.906719E+09 | 0.494088E+09 | 0.203244E+10 | 0.812719E+09 |
March | 0.990124E+09 | 0.446844E+09 | 0.543280E+09 | 0.147383E+10 | 0.796452E+09 |
April | 0.710194E+09 | 0.166416E+09 | 0.543778E+09 | 0.116913E+10 | 0.494838E+09 |
May | 0.560728E+09 | 23830137.60 | 0.536897E+09 | 0.114886E+10 | 0.139165E+09 |
June | 0.536035E+09 | 4996364.11 | 0.531039E+09 | 0.113258E+10 | 0.107659E+09 |
July | 0.579847E+09 | 10657518.52 | 0.569189E+09 | 0.121510E+10 | 67635935.68 |
August | 0.682159E+09 | 81879609.18 | 0.600279E+09 | 0.143265E+10 | 0.108587E+09 |
September | 0.792074E+09 | 0.208745E+09 | 0.583329E+09 | 0.154278E+10 | 0.167084E+09 |
October | 0.126987E+10 | 0.661484E+09 | 0.608389E+09 | 0.227265E+10 | 0.326140E+09 |
November | 0.156387E+10 | 0.107674E+10 | 0.487128E+09 | 0.241089E+10 | 0.685593E+09 |
December | 0.167090E+10 | 0.119995E+10 | 0.470949E+09 | 0.246333E+10 | 0.939217E+09 |
Annual Sum or Average | 0.124666E+11 | 0.600780E+10 | 0.645882E+10 | 0.207259E+11 | 0.568452E+10 |
Minimum of Months | 0.536035E+09 | 4996364.11 | 0.470949E+09 | 0.113258E+10 | 67635935.68 |
Maximum of Months | 0.171002E+10 | 0.121954E+10 | 0.608389E+09 | 0.246333E+10 | 0.103943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171002E+10 | 0.121954E+10 | 0.490479E+09 | 0.243167E+10 | 0.103943E+10 |
February | 0.140081E+10 | 0.906718E+09 | 0.494088E+09 | 0.203244E+10 | 0.812719E+09 |
March | 0.990123E+09 | 0.446843E+09 | 0.543279E+09 | 0.147383E+10 | 0.796452E+09 |
April | 0.710194E+09 | 0.166416E+09 | 0.543778E+09 | 0.116913E+10 | 0.494838E+09 |
May | 0.560727E+09 | 23830109.01 | 0.536897E+09 | 0.114886E+10 | 0.139165E+09 |
June | 0.536035E+09 | 4996358.11 | 0.531038E+09 | 0.113258E+10 | 0.107659E+09 |
July | 0.579846E+09 | 10657505.73 | 0.569189E+09 | 0.121510E+10 | 67635853.96 |
August | 0.682158E+09 | 81879510.93 | 0.600279E+09 | 0.143265E+10 | 0.108587E+09 |
September | 0.792073E+09 | 0.208745E+09 | 0.583328E+09 | 0.154278E+10 | 0.167084E+09 |
October | 0.126987E+10 | 0.661483E+09 | 0.608389E+09 | 0.227265E+10 | 0.326140E+09 |
November | 0.156386E+10 | 0.107674E+10 | 0.487127E+09 | 0.241089E+10 | 0.685593E+09 |
December | 0.167090E+10 | 0.119995E+10 | 0.470948E+09 | 0.246333E+10 | 0.939217E+09 |
Annual Sum or Average | 0.124666E+11 | 0.600780E+10 | 0.645882E+10 | 0.207259E+11 | 0.568451E+10 |
Minimum of Months | 0.536035E+09 | 4996358.11 | 0.470948E+09 | 0.113258E+10 | 67635853.96 |
Maximum of Months | 0.171002E+10 | 0.121954E+10 | 0.608389E+09 | 0.246333E+10 | 0.103943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171002E+10 | 0.121954E+10 | 0.490479E+09 | 0.243167E+10 | 0.103943E+10 |
February | 0.140081E+10 | 0.906719E+09 | 0.494088E+09 | 0.203244E+10 | 0.812719E+09 |
March | 0.990124E+09 | 0.446844E+09 | 0.543280E+09 | 0.147383E+10 | 0.796452E+09 |
April | 0.710194E+09 | 0.166416E+09 | 0.543778E+09 | 0.116913E+10 | 0.494838E+09 |
May | 0.560728E+09 | 23830137.60 | 0.536897E+09 | 0.114886E+10 | 0.139165E+09 |
June | 0.536035E+09 | 4996364.11 | 0.531039E+09 | 0.113258E+10 | 0.107659E+09 |
July | 0.579847E+09 | 10657518.52 | 0.569189E+09 | 0.121510E+10 | 67635935.68 |
August | 0.682159E+09 | 81879609.18 | 0.600279E+09 | 0.143265E+10 | 0.108587E+09 |
September | 0.792074E+09 | 0.208745E+09 | 0.583329E+09 | 0.154278E+10 | 0.167084E+09 |
October | 0.126987E+10 | 0.661484E+09 | 0.608389E+09 | 0.227265E+10 | 0.326140E+09 |
November | 0.156387E+10 | 0.107674E+10 | 0.487128E+09 | 0.241089E+10 | 0.685593E+09 |
December | 0.167090E+10 | 0.119995E+10 | 0.470949E+09 | 0.246333E+10 | 0.939217E+09 |
Annual Sum or Average | 0.124666E+11 | 0.600780E+10 | 0.645882E+10 | 0.207259E+11 | 0.568452E+10 |
Minimum of Months | 0.536035E+09 | 4996364.11 | 0.470949E+09 | 0.113258E+10 | 67635935.68 |
Maximum of Months | 0.171002E+10 | 0.121954E+10 | 0.608389E+09 | 0.246333E+10 | 0.103943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171002E+10 | 0.121954E+10 | 0.490479E+09 | 0.243167E+10 | 0.103943E+10 |
February | 0.140081E+10 | 0.906718E+09 | 0.494088E+09 | 0.203244E+10 | 0.812719E+09 |
March | 0.990123E+09 | 0.446843E+09 | 0.543279E+09 | 0.147383E+10 | 0.796452E+09 |
April | 0.710194E+09 | 0.166416E+09 | 0.543778E+09 | 0.116913E+10 | 0.494838E+09 |
May | 0.560727E+09 | 23830109.01 | 0.536897E+09 | 0.114886E+10 | 0.139165E+09 |
June | 0.536035E+09 | 4996358.11 | 0.531038E+09 | 0.113258E+10 | 0.107659E+09 |
July | 0.579846E+09 | 10657505.73 | 0.569189E+09 | 0.121510E+10 | 67635853.96 |
August | 0.682158E+09 | 81879510.93 | 0.600279E+09 | 0.143265E+10 | 0.108587E+09 |
September | 0.792073E+09 | 0.208745E+09 | 0.583328E+09 | 0.154278E+10 | 0.167084E+09 |
October | 0.126987E+10 | 0.661483E+09 | 0.608389E+09 | 0.227265E+10 | 0.326140E+09 |
November | 0.156386E+10 | 0.107674E+10 | 0.487127E+09 | 0.241089E+10 | 0.685593E+09 |
December | 0.167090E+10 | 0.119995E+10 | 0.470948E+09 | 0.246333E+10 | 0.939217E+09 |
Annual Sum or Average | 0.124666E+11 | 0.600780E+10 | 0.645882E+10 | 0.207259E+11 | 0.568451E+10 |
Minimum of Months | 0.536035E+09 | 4996358.11 | 0.470948E+09 | 0.113258E+10 | 67635853.96 |
Maximum of Months | 0.171002E+10 | 0.121954E+10 | 0.608389E+09 | 0.246333E+10 | 0.103943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170995E+10 | 0.121949E+10 | 0.490460E+09 | 0.243157E+10 | 0.103938E+10 |
February | 0.140075E+10 | 0.906682E+09 | 0.494068E+09 | 0.203236E+10 | 0.812686E+09 |
March | 0.990084E+09 | 0.446826E+09 | 0.543258E+09 | 0.147377E+10 | 0.796420E+09 |
April | 0.710166E+09 | 0.166409E+09 | 0.543756E+09 | 0.116909E+10 | 0.494818E+09 |
May | 0.560705E+09 | 23829177.14 | 0.536876E+09 | 0.114881E+10 | 0.139160E+09 |
June | 0.536013E+09 | 4996162.73 | 0.531017E+09 | 0.113253E+10 | 0.107655E+09 |
July | 0.579823E+09 | 10657088.97 | 0.569166E+09 | 0.121505E+10 | 67633209.66 |
August | 0.682131E+09 | 81876309.07 | 0.600255E+09 | 0.143259E+10 | 0.108582E+09 |
September | 0.792042E+09 | 0.208737E+09 | 0.583305E+09 | 0.154271E+10 | 0.167077E+09 |
October | 0.126982E+10 | 0.661457E+09 | 0.608365E+09 | 0.227256E+10 | 0.326127E+09 |
November | 0.156380E+10 | 0.107669E+10 | 0.487108E+09 | 0.241079E+10 | 0.685565E+09 |
December | 0.167083E+10 | 0.119990E+10 | 0.470930E+09 | 0.246323E+10 | 0.939179E+09 |
Annual Sum or Average | 0.124661E+11 | 0.600756E+10 | 0.645856E+10 | 0.207251E+11 | 0.568429E+10 |
Minimum of Months | 0.536013E+09 | 4996162.73 | 0.470930E+09 | 0.113253E+10 | 67633209.66 |
Maximum of Months | 0.170995E+10 | 0.121949E+10 | 0.608365E+09 | 0.246323E+10 | 0.103938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.899823E+09 | 0.486575E+09 | 0.413249E+09 | 0.110030E+10 | 0.134408E+10 |
February | 0.920207E+09 | 0.465752E+09 | 0.454455E+09 | 0.116522E+10 | 0.107545E+10 |
March | 0.100413E+10 | 0.444504E+09 | 0.559628E+09 | 0.131859E+10 | 0.105730E+10 |
April | 0.120693E+10 | 0.555209E+09 | 0.651718E+09 | 0.181730E+10 | 0.681964E+09 |
May | 0.103716E+10 | 0.337857E+09 | 0.699303E+09 | 0.193722E+10 | 0.214947E+09 |
June | 0.111500E+10 | 0.390971E+09 | 0.724027E+09 | 0.211527E+10 | 0.192199E+09 |
July | 0.105171E+10 | 0.291728E+09 | 0.759983E+09 | 0.197903E+10 | 0.157557E+09 |
August | 0.106341E+10 | 0.325525E+09 | 0.737888E+09 | 0.199004E+10 | 0.224932E+09 |
September | 0.947636E+09 | 0.325084E+09 | 0.622551E+09 | 0.171537E+10 | 0.238702E+09 |
October | 0.100252E+10 | 0.433179E+09 | 0.569344E+09 | 0.172630E+10 | 0.444564E+09 |
November | 0.831563E+09 | 0.417910E+09 | 0.413653E+09 | 0.115510E+10 | 0.932997E+09 |
December | 0.826555E+09 | 0.439551E+09 | 0.387004E+09 | 0.103993E+10 | 0.128776E+10 |
Annual Sum or Average | 0.119066E+11 | 0.491384E+10 | 0.699280E+10 | 0.190597E+11 | 0.785246E+10 |
Minimum of Months | 0.826555E+09 | 0.291728E+09 | 0.387004E+09 | 0.103993E+10 | 0.157557E+09 |
Maximum of Months | 0.120693E+10 | 0.555209E+09 | 0.759983E+09 | 0.211527E+10 | 0.134408E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.899823E+09 | 0.486575E+09 | 0.413249E+09 | 0.110030E+10 | 0.134408E+10 |
February | 0.920207E+09 | 0.465752E+09 | 0.454455E+09 | 0.116522E+10 | 0.107545E+10 |
March | 0.100413E+10 | 0.444504E+09 | 0.559628E+09 | 0.131859E+10 | 0.105730E+10 |
April | 0.120693E+10 | 0.555209E+09 | 0.651718E+09 | 0.181730E+10 | 0.681964E+09 |
May | 0.103716E+10 | 0.337857E+09 | 0.699303E+09 | 0.193722E+10 | 0.214947E+09 |
June | 0.111500E+10 | 0.390971E+09 | 0.724027E+09 | 0.211527E+10 | 0.192199E+09 |
July | 0.105171E+10 | 0.291728E+09 | 0.759983E+09 | 0.197903E+10 | 0.157557E+09 |
August | 0.106341E+10 | 0.325525E+09 | 0.737888E+09 | 0.199004E+10 | 0.224932E+09 |
September | 0.947636E+09 | 0.325084E+09 | 0.622551E+09 | 0.171537E+10 | 0.238702E+09 |
October | 0.100252E+10 | 0.433179E+09 | 0.569344E+09 | 0.172630E+10 | 0.444564E+09 |
November | 0.831563E+09 | 0.417910E+09 | 0.413653E+09 | 0.115510E+10 | 0.932997E+09 |
December | 0.826555E+09 | 0.439551E+09 | 0.387004E+09 | 0.103993E+10 | 0.128776E+10 |
Annual Sum or Average | 0.119066E+11 | 0.491384E+10 | 0.699280E+10 | 0.190597E+11 | 0.785246E+10 |
Minimum of Months | 0.826555E+09 | 0.291728E+09 | 0.387004E+09 | 0.103993E+10 | 0.157557E+09 |
Maximum of Months | 0.120693E+10 | 0.555209E+09 | 0.759983E+09 | 0.211527E+10 | 0.134408E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.899807E+09 | 0.486566E+09 | 0.413241E+09 | 0.110028E+10 | 0.134406E+10 |
February | 0.920190E+09 | 0.465743E+09 | 0.454447E+09 | 0.116520E+10 | 0.107543E+10 |
March | 0.100411E+10 | 0.444496E+09 | 0.559617E+09 | 0.131857E+10 | 0.105728E+10 |
April | 0.120690E+10 | 0.555199E+09 | 0.651706E+09 | 0.181727E+10 | 0.681951E+09 |
May | 0.103714E+10 | 0.337850E+09 | 0.699290E+09 | 0.193718E+10 | 0.214943E+09 |
June | 0.111498E+10 | 0.390964E+09 | 0.724014E+09 | 0.211524E+10 | 0.192195E+09 |
July | 0.105169E+10 | 0.291723E+09 | 0.759969E+09 | 0.197900E+10 | 0.157555E+09 |
August | 0.106339E+10 | 0.325519E+09 | 0.737874E+09 | 0.199000E+10 | 0.224928E+09 |
September | 0.947618E+09 | 0.325078E+09 | 0.622540E+09 | 0.171534E+10 | 0.238698E+09 |
October | 0.100250E+10 | 0.433171E+09 | 0.569333E+09 | 0.172627E+10 | 0.444556E+09 |
November | 0.831548E+09 | 0.417903E+09 | 0.413645E+09 | 0.115508E+10 | 0.932980E+09 |
December | 0.826540E+09 | 0.439543E+09 | 0.386997E+09 | 0.103992E+10 | 0.128774E+10 |
Annual Sum or Average | 0.119064E+11 | 0.491376E+10 | 0.699267E+10 | 0.190593E+11 | 0.785232E+10 |
Minimum of Months | 0.826540E+09 | 0.291723E+09 | 0.386997E+09 | 0.103992E+10 | 0.157555E+09 |
Maximum of Months | 0.120690E+10 | 0.555199E+09 | 0.759969E+09 | 0.211524E+10 | 0.134406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147919E+10 | 0.00 | 0.147919E+10 | 0.114167E+10 | 0.507331E+10 |
February | 0.157620E+10 | 0.00 | 0.157620E+10 | 0.137872E+10 | 0.384430E+10 |
March | 0.202445E+10 | 0.00 | 0.202445E+10 | 0.215744E+10 | 0.366280E+10 |
April | 0.231222E+10 | 9490170.94 | 0.230273E+10 | 0.322092E+10 | 0.222589E+10 |
May | 0.270633E+10 | 98991513.86 | 0.260734E+10 | 0.550312E+10 | 0.642760E+09 |
June | 0.297840E+10 | 0.206231E+09 | 0.277217E+10 | 0.629096E+10 | 0.533076E+09 |
July | 0.298669E+10 | 0.113787E+09 | 0.287290E+10 | 0.626015E+10 | 0.356202E+09 |
August | 0.267463E+10 | 21036347.24 | 0.265360E+10 | 0.566013E+10 | 0.506396E+09 |
September | 0.223576E+10 | 172197.38 | 0.223559E+10 | 0.436511E+10 | 0.709430E+09 |
October | 0.200759E+10 | 0.00 | 0.200759E+10 | 0.364633E+10 | 0.142026E+10 |
November | 0.147492E+10 | 0.00 | 0.147492E+10 | 0.165692E+10 | 0.314448E+10 |
December | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.121348E+10 | 0.433177E+10 |
Annual Sum or Average | 0.258315E+11 | 0.449709E+09 | 0.253818E+11 | 0.424949E+11 | 0.264507E+11 |
Minimum of Months | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.114167E+10 | 0.356202E+09 |
Maximum of Months | 0.298669E+10 | 0.206231E+09 | 0.287290E+10 | 0.629096E+10 | 0.507331E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253789E+10 | 0.129230E+10 | 0.124559E+10 | 0.296918E+10 | 0.324585E+10 |
February | 0.255254E+10 | 0.123230E+10 | 0.132024E+10 | 0.316481E+10 | 0.247824E+10 |
March | 0.332433E+10 | 0.160323E+10 | 0.172110E+10 | 0.445592E+10 | 0.238132E+10 |
April | 0.353039E+10 | 0.159670E+10 | 0.193369E+10 | 0.537959E+10 | 0.151204E+10 |
May | 0.376017E+10 | 0.163048E+10 | 0.212969E+10 | 0.687161E+10 | 0.460263E+09 |
June | 0.369044E+10 | 0.146352E+10 | 0.222691E+10 | 0.698944E+10 | 0.379984E+09 |
July | 0.367671E+10 | 0.134548E+10 | 0.233123E+10 | 0.696757E+10 | 0.258555E+09 |
August | 0.338798E+10 | 0.116481E+10 | 0.222316E+10 | 0.643207E+10 | 0.364094E+09 |
September | 0.290431E+10 | 0.998493E+09 | 0.190582E+10 | 0.524950E+10 | 0.504639E+09 |
October | 0.296573E+10 | 0.125153E+10 | 0.171420E+10 | 0.509016E+10 | 0.968039E+09 |
November | 0.254102E+10 | 0.129628E+10 | 0.124475E+10 | 0.349348E+10 | 0.205795E+10 |
December | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.253321E+10 | 0.283365E+10 |
Annual Sum or Average | 0.369388E+11 | 0.158116E+11 | 0.211273E+11 | 0.595966E+11 | 0.174446E+11 |
Minimum of Months | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.253321E+10 | 0.258555E+09 |
Maximum of Months | 0.376017E+10 | 0.163048E+10 | 0.233123E+10 | 0.698944E+10 | 0.324585E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.855001E+10 | 0.609764E+10 | 0.245237E+10 | 0.120681E+11 | 0.504183E+10 |
February | 0.700395E+10 | 0.453354E+10 | 0.247041E+10 | 0.101081E+11 | 0.390389E+10 |
March | 0.495056E+10 | 0.223419E+10 | 0.271637E+10 | 0.736360E+10 | 0.375605E+10 |
April | 0.355093E+10 | 0.832070E+09 | 0.271886E+10 | 0.585840E+10 | 0.237122E+10 |
May | 0.280360E+10 | 0.119149E+09 | 0.268445E+10 | 0.575782E+10 | 0.667114E+09 |
June | 0.268014E+10 | 24981518.47 | 0.265516E+10 | 0.568948E+10 | 0.544190E+09 |
July | 0.289920E+10 | 53286948.24 | 0.284591E+10 | 0.611533E+10 | 0.346433E+09 |
August | 0.341075E+10 | 0.409393E+09 | 0.300136E+10 | 0.719438E+10 | 0.548604E+09 |
September | 0.396032E+10 | 0.104371E+10 | 0.291661E+10 | 0.768660E+10 | 0.799264E+09 |
October | 0.634929E+10 | 0.330738E+10 | 0.304191E+10 | 0.112885E+11 | 0.160884E+10 |
November | 0.781924E+10 | 0.538363E+10 | 0.243561E+10 | 0.119908E+11 | 0.330321E+10 |
December | 0.835440E+10 | 0.599968E+10 | 0.235471E+10 | 0.122677E+11 | 0.447293E+10 |
Annual Sum or Average | 0.623324E+11 | 0.300386E+11 | 0.322937E+11 | 0.103389E+12 | 0.273636E+11 |
Minimum of Months | 0.268014E+10 | 24981518.47 | 0.235471E+10 | 0.568948E+10 | 0.346433E+09 |
Maximum of Months | 0.855001E+10 | 0.609764E+10 | 0.304191E+10 | 0.122677E+11 | 0.504183E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269944E+10 | 0.145971E+10 | 0.123973E+10 | 0.341535E+10 | 0.353078E+10 |
February | 0.276059E+10 | 0.139724E+10 | 0.136335E+10 | 0.362060E+10 | 0.273858E+10 |
March | 0.301236E+10 | 0.133350E+10 | 0.167887E+10 | 0.409463E+10 | 0.262737E+10 |
April | 0.362074E+10 | 0.166561E+10 | 0.195513E+10 | 0.558244E+10 | 0.170903E+10 |
May | 0.311145E+10 | 0.101356E+10 | 0.209789E+10 | 0.585886E+10 | 0.553168E+09 |
June | 0.334496E+10 | 0.117290E+10 | 0.217206E+10 | 0.641739E+10 | 0.476306E+09 |
July | 0.315510E+10 | 0.875176E+09 | 0.227992E+10 | 0.606288E+10 | 0.340561E+09 |
August | 0.319021E+10 | 0.976566E+09 | 0.221364E+10 | 0.613684E+10 | 0.465121E+09 |
September | 0.284288E+10 | 0.975243E+09 | 0.186763E+10 | 0.518990E+10 | 0.598098E+09 |
October | 0.300754E+10 | 0.129952E+10 | 0.170801E+10 | 0.526337E+10 | 0.112257E+10 |
November | 0.249466E+10 | 0.125372E+10 | 0.124095E+10 | 0.360519E+10 | 0.230261E+10 |
December | 0.247964E+10 | 0.131864E+10 | 0.116100E+10 | 0.330135E+10 | 0.307279E+10 |
Annual Sum or Average | 0.357196E+11 | 0.147414E+11 | 0.209782E+11 | 0.585488E+11 | 0.195370E+11 |
Minimum of Months | 0.247964E+10 | 0.875176E+09 | 0.116100E+10 | 0.330135E+10 | 0.340561E+09 |
Maximum of Months | 0.362074E+10 | 0.166561E+10 | 0.227992E+10 | 0.641739E+10 | 0.353078E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147919E+10 | 0.00 | 0.147919E+10 | 0.123230E+10 | 0.467524E+10 |
February | 0.157620E+10 | 0.00 | 0.157620E+10 | 0.144902E+10 | 0.354992E+10 |
March | 0.202445E+10 | 0.00 | 0.202445E+10 | 0.220686E+10 | 0.344065E+10 |
April | 0.231222E+10 | 9490170.94 | 0.230273E+10 | 0.320738E+10 | 0.216988E+10 |
May | 0.270633E+10 | 98991513.86 | 0.260734E+10 | 0.541072E+10 | 0.687823E+09 |
June | 0.297840E+10 | 0.206231E+09 | 0.277217E+10 | 0.618795E+10 | 0.578213E+09 |
July | 0.298669E+10 | 0.113787E+09 | 0.287290E+10 | 0.614024E+10 | 0.400533E+09 |
August | 0.267463E+10 | 21036347.24 | 0.265360E+10 | 0.556312E+10 | 0.546841E+09 |
September | 0.223576E+10 | 172197.38 | 0.223559E+10 | 0.428056E+10 | 0.740596E+09 |
October | 0.200759E+10 | 0.00 | 0.200759E+10 | 0.360823E+10 | 0.139433E+10 |
November | 0.147492E+10 | 0.00 | 0.147492E+10 | 0.172559E+10 | 0.290526E+10 |
December | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.129240E+10 | 0.398265E+10 |
Annual Sum or Average | 0.258315E+11 | 0.449709E+09 | 0.253818E+11 | 0.423044E+11 | 0.250719E+11 |
Minimum of Months | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.123230E+10 | 0.400533E+09 |
Maximum of Months | 0.298669E+10 | 0.206231E+09 | 0.287290E+10 | 0.618795E+10 | 0.467524E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253789E+10 | 0.129230E+10 | 0.124559E+10 | 0.308648E+10 | 0.297896E+10 |
February | 0.255254E+10 | 0.123230E+10 | 0.132024E+10 | 0.324820E+10 | 0.228951E+10 |
March | 0.332433E+10 | 0.160323E+10 | 0.172110E+10 | 0.450326E+10 | 0.224922E+10 |
April | 0.353039E+10 | 0.159670E+10 | 0.193369E+10 | 0.537886E+10 | 0.148161E+10 |
May | 0.376017E+10 | 0.163048E+10 | 0.212969E+10 | 0.682433E+10 | 0.486471E+09 |
June | 0.369044E+10 | 0.146352E+10 | 0.222691E+10 | 0.694020E+10 | 0.408172E+09 |
July | 0.367671E+10 | 0.134548E+10 | 0.233123E+10 | 0.690996E+10 | 0.286118E+09 |
August | 0.338798E+10 | 0.116481E+10 | 0.222316E+10 | 0.638654E+10 | 0.388967E+09 |
September | 0.290431E+10 | 0.998493E+09 | 0.190582E+10 | 0.521304E+10 | 0.521389E+09 |
October | 0.296573E+10 | 0.125153E+10 | 0.171420E+10 | 0.507755E+10 | 0.950820E+09 |
November | 0.254102E+10 | 0.129628E+10 | 0.124475E+10 | 0.355013E+10 | 0.192583E+10 |
December | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.261698E+10 | 0.260434E+10 |
Annual Sum or Average | 0.369388E+11 | 0.158116E+11 | 0.211273E+11 | 0.597355E+11 | 0.165714E+11 |
Minimum of Months | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.261698E+10 | 0.286118E+09 |
Maximum of Months | 0.376017E+10 | 0.163048E+10 | 0.233123E+10 | 0.694020E+10 | 0.297896E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.855001E+10 | 0.609764E+10 | 0.245237E+10 | 0.121588E+11 | 0.470256E+10 |
February | 0.700395E+10 | 0.453354E+10 | 0.247041E+10 | 0.101807E+11 | 0.364555E+10 |
March | 0.495056E+10 | 0.223419E+10 | 0.271637E+10 | 0.739677E+10 | 0.355342E+10 |
April | 0.355093E+10 | 0.832070E+09 | 0.271886E+10 | 0.583090E+10 | 0.231756E+10 |
May | 0.280360E+10 | 0.119149E+09 | 0.268445E+10 | 0.566579E+10 | 0.712682E+09 |
June | 0.268014E+10 | 24981518.47 | 0.265516E+10 | 0.559033E+10 | 0.592471E+09 |
July | 0.289920E+10 | 53286948.24 | 0.284591E+10 | 0.599151E+10 | 0.388382E+09 |
August | 0.341075E+10 | 0.409393E+09 | 0.300136E+10 | 0.709521E+10 | 0.590339E+09 |
September | 0.396032E+10 | 0.104371E+10 | 0.291661E+10 | 0.760469E+10 | 0.829462E+09 |
October | 0.634929E+10 | 0.330738E+10 | 0.304191E+10 | 0.112347E+11 | 0.158980E+10 |
November | 0.781924E+10 | 0.538363E+10 | 0.243561E+10 | 0.120258E+11 | 0.313412E+10 |
December | 0.835440E+10 | 0.599968E+10 | 0.235471E+10 | 0.123339E+11 | 0.417484E+10 |
Annual Sum or Average | 0.623324E+11 | 0.300386E+11 | 0.322937E+11 | 0.103109E+12 | 0.262312E+11 |
Minimum of Months | 0.268014E+10 | 24981518.47 | 0.235471E+10 | 0.559033E+10 | 0.388382E+09 |
Maximum of Months | 0.855001E+10 | 0.609764E+10 | 0.304191E+10 | 0.123339E+11 | 0.470256E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269944E+10 | 0.145971E+10 | 0.123973E+10 | 0.345831E+10 | 0.330568E+10 |
February | 0.276059E+10 | 0.139724E+10 | 0.136335E+10 | 0.364830E+10 | 0.256896E+10 |
March | 0.301236E+10 | 0.133350E+10 | 0.167887E+10 | 0.410557E+10 | 0.249566E+10 |
April | 0.362074E+10 | 0.166561E+10 | 0.195513E+10 | 0.555444E+10 | 0.166990E+10 |
May | 0.311145E+10 | 0.101356E+10 | 0.209789E+10 | 0.579999E+10 | 0.576728E+09 |
June | 0.334496E+10 | 0.117290E+10 | 0.217206E+10 | 0.635373E+10 | 0.500011E+09 |
July | 0.315510E+10 | 0.875176E+09 | 0.227992E+10 | 0.599255E+10 | 0.363563E+09 |
August | 0.319021E+10 | 0.976566E+09 | 0.221364E+10 | 0.607545E+10 | 0.489245E+09 |
September | 0.284288E+10 | 0.975243E+09 | 0.186763E+10 | 0.514002E+10 | 0.613306E+09 |
October | 0.300754E+10 | 0.129952E+10 | 0.170801E+10 | 0.523134E+10 | 0.110668E+10 |
November | 0.249466E+10 | 0.125372E+10 | 0.124095E+10 | 0.362648E+10 | 0.217422E+10 |
December | 0.247964E+10 | 0.131864E+10 | 0.116100E+10 | 0.333585E+10 | 0.287202E+10 |
Annual Sum or Average | 0.357196E+11 | 0.147414E+11 | 0.209782E+11 | 0.583220E+11 | 0.187360E+11 |
Minimum of Months | 0.247964E+10 | 0.875176E+09 | 0.116100E+10 | 0.333585E+10 | 0.363563E+09 |
Maximum of Months | 0.362074E+10 | 0.166561E+10 | 0.227992E+10 | 0.635373E+10 | 0.330568E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 353.98 | 2160.05 | 552.27 | 0.00 | 552.27 | 0.00 | 0.00 |
February | 498.01 | 1837.22 | 651.54 | 0.00 | 651.54 | 0.00 | 0.00 |
March | 738.40 | 1561.82 | 755.85 | 0.00 | 755.85 | 0.00 | 0.00 |
April | 1203.91 | 935.26 | 892.06 | 3.66 | 888.40 | 0.00 | 0.00 |
May | 2046.10 | 252.25 | 1010.43 | 36.96 | 973.47 | 0.00 | 0.00 |
June | 2421.09 | 200.40 | 1149.08 | 79.56 | 1069.51 | 0.00 | 0.00 |
July | 2326.03 | 127.28 | 1115.11 | 42.48 | 1072.62 | 0.00 | 0.00 |
August | 2088.81 | 189.35 | 998.60 | 7.85 | 990.74 | 0.00 | 0.00 |
September | 1668.69 | 301.98 | 862.56 | 0.07 | 862.50 | 0.00 | 0.00 |
October | 1333.45 | 584.17 | 749.55 | 0.00 | 749.55 | 0.00 | 0.00 |
November | 575.65 | 1406.94 | 569.03 | 0.00 | 569.03 | 0.00 | 0.00 |
December | 378.99 | 1910.78 | 513.40 | 0.00 | 513.40 | 0.00 | 0.00 |
Annual Sum or Average | 1307.57 | 951.06 | 819.11 | 14.26 | 804.85 | 0.00 | 0.00 |
Minimum of Months | 353.98 | 127.28 | 513.40 | 0.00 | 513.40 | 0.00 | 0.00 |
Maximum of Months | 2421.09 | 2160.05 | 1149.08 | 79.56 | 1072.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1091.36 | 1322.15 | 947.54 | 482.49 | 465.05 | 0.00 | 0.00 |
February | 1294.72 | 1116.05 | 1055.12 | 509.38 | 545.74 | 0.00 | 0.00 |
March | 1668.23 | 948.68 | 1241.17 | 598.58 | 642.59 | 0.00 | 0.00 |
April | 2100.69 | 581.85 | 1362.04 | 616.01 | 746.03 | 0.00 | 0.00 |
May | 2597.60 | 166.87 | 1403.89 | 608.76 | 795.14 | 0.00 | 0.00 |
June | 2729.55 | 126.30 | 1423.79 | 564.63 | 859.15 | 0.00 | 0.00 |
July | 2637.32 | 73.55 | 1372.73 | 502.35 | 870.39 | 0.00 | 0.00 |
August | 2433.68 | 108.13 | 1264.93 | 434.89 | 830.04 | 0.00 | 0.00 |
September | 2048.26 | 196.52 | 1120.50 | 385.22 | 735.27 | 0.00 | 0.00 |
October | 1922.34 | 366.62 | 1107.28 | 467.27 | 640.01 | 0.00 | 0.00 |
November | 1347.73 | 850.24 | 980.34 | 500.11 | 480.23 | 0.00 | 0.00 |
December | 930.05 | 1157.21 | 771.86 | 349.64 | 422.23 | 0.00 | 0.00 |
Annual Sum or Average | 1903.39 | 581.74 | 1171.33 | 501.38 | 669.94 | 0.00 | 0.00 |
Minimum of Months | 930.05 | 73.55 | 771.86 | 349.64 | 422.23 | 0.00 | 0.00 |
Maximum of Months | 2729.55 | 1322.15 | 1423.79 | 616.01 | 870.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4539.37 | 1940.37 | 3192.22 | 2276.61 | 915.61 | 0.00 | 0.00 |
February | 4200.62 | 1679.71 | 2895.16 | 1873.99 | 1021.17 | 0.00 | 0.00 |
March | 2751.31 | 1486.79 | 1848.33 | 834.16 | 1014.18 | 0.00 | 0.00 |
April | 2255.25 | 954.54 | 1369.96 | 321.02 | 1048.95 | 0.00 | 0.00 |
May | 2144.65 | 259.79 | 1046.75 | 44.49 | 1002.26 | 0.00 | 0.00 |
June | 2184.74 | 207.67 | 1034.01 | 9.64 | 1024.37 | 0.00 | 0.00 |
July | 2268.31 | 126.26 | 1082.44 | 19.90 | 1062.55 | 0.00 | 0.00 |
August | 2674.43 | 202.71 | 1273.43 | 152.85 | 1120.58 | 0.00 | 0.00 |
September | 2976.01 | 322.30 | 1527.91 | 402.67 | 1125.24 | 0.00 | 0.00 |
October | 4242.52 | 608.83 | 2370.56 | 1234.84 | 1135.72 | 0.00 | 0.00 |
November | 4650.60 | 1322.51 | 3016.69 | 2077.02 | 939.67 | 0.00 | 0.00 |
December | 4598.47 | 1753.30 | 3119.19 | 2240.03 | 879.15 | 0.00 | 0.00 |
Annual Sum or Average | 3286.04 | 901.27 | 1976.55 | 952.52 | 1024.03 | 0.00 | 0.00 |
Minimum of Months | 2144.65 | 126.26 | 1034.01 | 9.64 | 879.15 | 0.00 | 0.00 |
Maximum of Months | 4650.60 | 1940.37 | 3192.22 | 2276.61 | 1135.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1232.41 | 1505.46 | 1007.86 | 545.00 | 462.87 | 0.00 | 0.00 |
February | 1444.96 | 1333.64 | 1141.12 | 577.57 | 563.56 | 0.00 | 0.00 |
March | 1476.91 | 1184.24 | 1124.69 | 497.87 | 626.82 | 0.00 | 0.00 |
April | 2103.35 | 789.31 | 1396.90 | 642.60 | 754.30 | 0.00 | 0.00 |
May | 2169.81 | 240.75 | 1161.69 | 378.42 | 783.26 | 0.00 | 0.00 |
June | 2448.22 | 222.45 | 1290.50 | 452.51 | 837.99 | 0.00 | 0.00 |
July | 2216.64 | 176.47 | 1177.98 | 326.75 | 851.23 | 0.00 | 0.00 |
August | 2228.97 | 251.94 | 1191.09 | 364.61 | 826.48 | 0.00 | 0.00 |
September | 1985.37 | 276.27 | 1096.79 | 376.25 | 720.54 | 0.00 | 0.00 |
October | 1933.57 | 497.94 | 1122.89 | 485.19 | 637.70 | 0.00 | 0.00 |
November | 1336.92 | 1079.85 | 962.45 | 483.69 | 478.76 | 0.00 | 0.00 |
December | 1164.79 | 1442.38 | 925.80 | 492.33 | 433.47 | 0.00 | 0.00 |
Annual Sum or Average | 1813.13 | 747.00 | 1132.66 | 467.45 | 665.22 | 0.00 | 0.00 |
Minimum of Months | 1164.79 | 176.47 | 925.80 | 326.75 | 433.47 | 0.00 | 0.00 |
Maximum of Months | 2448.22 | 1505.46 | 1396.90 | 642.60 | 851.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 426.25 | 1894.16 | 552.27 | 0.00 | 552.27 | 0.00 | 0.00 |
February | 569.91 | 1589.08 | 651.54 | 0.00 | 651.54 | 0.00 | 0.00 |
March | 805.49 | 1367.53 | 755.84 | 0.00 | 755.84 | 0.00 | 0.00 |
April | 1242.64 | 858.75 | 892.06 | 3.66 | 888.40 | 0.00 | 0.00 |
May | 2054.63 | 239.98 | 1010.43 | 36.96 | 973.47 | 0.00 | 0.00 |
June | 2427.07 | 205.66 | 1149.07 | 79.56 | 1069.51 | 0.00 | 0.00 |
July | 2337.27 | 132.99 | 1115.10 | 42.48 | 1072.62 | 0.00 | 0.00 |
August | 2113.25 | 189.07 | 998.59 | 7.85 | 990.74 | 0.00 | 0.00 |
September | 1684.07 | 273.70 | 862.56 | 0.07 | 862.49 | 0.00 | 0.00 |
October | 1361.38 | 530.26 | 749.55 | 0.00 | 749.55 | 0.00 | 0.00 |
November | 639.24 | 1213.15 | 569.03 | 0.00 | 569.03 | 0.00 | 0.00 |
December | 453.06 | 1617.30 | 513.39 | 0.00 | 513.39 | 0.00 | 0.00 |
Annual Sum or Average | 1347.51 | 838.75 | 819.11 | 14.26 | 804.85 | 0.00 | 0.00 |
Minimum of Months | 426.25 | 132.99 | 513.39 | 0.00 | 513.39 | 0.00 | 0.00 |
Maximum of Months | 2427.07 | 1894.16 | 1149.07 | 79.56 | 1072.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1108.57 | 1211.86 | 947.54 | 482.49 | 465.05 | 0.00 | 0.00 |
February | 1308.20 | 1024.41 | 1055.12 | 509.38 | 545.73 | 0.00 | 0.00 |
March | 1663.65 | 889.08 | 1241.16 | 598.58 | 642.58 | 0.00 | 0.00 |
April | 2075.46 | 583.35 | 1362.03 | 616.01 | 746.02 | 0.00 | 0.00 |
May | 2565.57 | 171.84 | 1403.89 | 608.75 | 795.14 | 0.00 | 0.00 |
June | 2696.54 | 146.60 | 1423.78 | 564.63 | 859.15 | 0.00 | 0.00 |
July | 2601.39 | 96.53 | 1372.73 | 502.34 | 870.38 | 0.00 | 0.00 |
August | 2401.46 | 135.94 | 1264.93 | 434.89 | 830.03 | 0.00 | 0.00 |
September | 2025.27 | 194.69 | 1120.49 | 385.22 | 735.27 | 0.00 | 0.00 |
October | 1900.45 | 361.42 | 1107.28 | 467.27 | 640.01 | 0.00 | 0.00 |
November | 1347.79 | 793.96 | 980.33 | 500.11 | 480.23 | 0.00 | 0.00 |
December | 945.79 | 1057.96 | 771.86 | 349.63 | 422.22 | 0.00 | 0.00 |
Annual Sum or Average | 1889.79 | 553.17 | 1171.32 | 501.38 | 669.94 | 0.00 | 0.00 |
Minimum of Months | 945.79 | 96.53 | 771.86 | 349.63 | 422.22 | 0.00 | 0.00 |
Maximum of Months | 2696.54 | 1211.86 | 1423.78 | 616.01 | 870.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4505.70 | 1882.40 | 3192.21 | 2276.60 | 915.61 | 0.00 | 0.00 |
February | 4178.29 | 1613.71 | 2895.15 | 1873.98 | 1021.17 | 0.00 | 0.00 |
March | 2749.25 | 1402.35 | 1848.33 | 834.15 | 1014.17 | 0.00 | 0.00 |
April | 2260.19 | 914.82 | 1369.96 | 321.01 | 1048.94 | 0.00 | 0.00 |
May | 2149.73 | 249.07 | 1046.75 | 44.49 | 1002.26 | 0.00 | 0.00 |
June | 2195.02 | 209.95 | 1034.01 | 9.64 | 1024.37 | 0.00 | 0.00 |
July | 2283.20 | 129.34 | 1082.44 | 19.90 | 1062.54 | 0.00 | 0.00 |
August | 2686.07 | 204.83 | 1273.43 | 152.85 | 1120.58 | 0.00 | 0.00 |
September | 2965.51 | 308.36 | 1527.90 | 402.67 | 1125.23 | 0.00 | 0.00 |
October | 4214.63 | 600.67 | 2370.55 | 1234.83 | 1135.72 | 0.00 | 0.00 |
November | 4626.07 | 1274.39 | 3016.68 | 2077.02 | 939.66 | 0.00 | 0.00 |
December | 4580.24 | 1670.00 | 3119.17 | 2240.02 | 879.15 | 0.00 | 0.00 |
Annual Sum or Average | 3278.43 | 867.69 | 1976.55 | 952.52 | 1024.03 | 0.00 | 0.00 |
Minimum of Months | 2149.73 | 129.34 | 1034.01 | 9.64 | 879.15 | 0.00 | 0.00 |
Maximum of Months | 4626.07 | 1882.40 | 3192.21 | 2276.60 | 1135.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1275.14 | 1318.24 | 1007.86 | 544.99 | 462.86 | 0.00 | 0.00 |
February | 1496.61 | 1132.02 | 1141.12 | 577.56 | 563.55 | 0.00 | 0.00 |
March | 1528.76 | 980.95 | 1124.69 | 497.87 | 626.82 | 0.00 | 0.00 |
April | 2153.72 | 659.35 | 1396.89 | 642.60 | 754.30 | 0.00 | 0.00 |
May | 2187.45 | 206.53 | 1161.68 | 378.42 | 783.26 | 0.00 | 0.00 |
June | 2475.84 | 183.76 | 1290.49 | 452.51 | 837.99 | 0.00 | 0.00 |
July | 2263.62 | 127.15 | 1177.98 | 326.75 | 851.23 | 0.00 | 0.00 |
August | 2291.23 | 173.66 | 1191.09 | 364.61 | 826.48 | 0.00 | 0.00 |
September | 2002.28 | 230.75 | 1096.79 | 376.25 | 720.54 | 0.00 | 0.00 |
October | 1965.12 | 419.12 | 1122.89 | 485.19 | 637.70 | 0.00 | 0.00 |
November | 1390.89 | 888.35 | 962.45 | 483.69 | 478.76 | 0.00 | 0.00 |
December | 1232.58 | 1147.25 | 925.79 | 492.32 | 433.47 | 0.00 | 0.00 |
Annual Sum or Average | 1856.57 | 619.51 | 1132.66 | 467.45 | 665.21 | 0.00 | 0.00 |
Minimum of Months | 1232.58 | 127.15 | 925.79 | 326.75 | 433.47 | 0.00 | 0.00 |
Maximum of Months | 2475.84 | 1318.24 | 1396.89 | 642.60 | 851.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 460.09 | 1745.53 | 552.27 | 0.00 | 552.27 | 0.00 | 0.00 |
February | 598.97 | 1467.39 | 651.54 | 0.00 | 651.54 | 0.00 | 0.00 |
March | 823.95 | 1284.59 | 755.84 | 0.00 | 755.84 | 0.00 | 0.00 |
April | 1237.41 | 837.14 | 892.06 | 3.66 | 888.40 | 0.00 | 0.00 |
May | 2020.13 | 256.80 | 1010.43 | 36.96 | 973.47 | 0.00 | 0.00 |
June | 2387.33 | 223.08 | 1149.07 | 79.56 | 1069.51 | 0.00 | 0.00 |
July | 2292.50 | 149.54 | 1115.10 | 42.48 | 1072.62 | 0.00 | 0.00 |
August | 2077.03 | 204.17 | 998.59 | 7.85 | 990.74 | 0.00 | 0.00 |
September | 1651.45 | 285.72 | 862.56 | 0.07 | 862.49 | 0.00 | 0.00 |
October | 1347.16 | 520.58 | 749.55 | 0.00 | 749.55 | 0.00 | 0.00 |
November | 665.74 | 1120.86 | 569.03 | 0.00 | 569.03 | 0.00 | 0.00 |
December | 482.53 | 1486.95 | 513.39 | 0.00 | 513.39 | 0.00 | 0.00 |
Annual Sum or Average | 1341.46 | 795.03 | 819.11 | 14.26 | 804.85 | 0.00 | 0.00 |
Minimum of Months | 460.09 | 149.54 | 513.39 | 0.00 | 513.39 | 0.00 | 0.00 |
Maximum of Months | 2387.33 | 1745.53 | 1149.07 | 79.56 | 1072.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1152.36 | 1112.22 | 947.54 | 482.49 | 465.05 | 0.00 | 0.00 |
February | 1342.68 | 946.39 | 1055.12 | 509.38 | 545.73 | 0.00 | 0.00 |
March | 1681.32 | 839.76 | 1241.16 | 598.58 | 642.58 | 0.00 | 0.00 |
April | 2075.18 | 571.61 | 1362.03 | 616.01 | 746.02 | 0.00 | 0.00 |
May | 2547.91 | 181.63 | 1403.89 | 608.75 | 795.14 | 0.00 | 0.00 |
June | 2677.55 | 157.47 | 1423.78 | 564.63 | 859.15 | 0.00 | 0.00 |
July | 2579.88 | 106.82 | 1372.73 | 502.34 | 870.38 | 0.00 | 0.00 |
August | 2384.46 | 145.22 | 1264.93 | 434.89 | 830.03 | 0.00 | 0.00 |
September | 2011.20 | 201.15 | 1120.49 | 385.22 | 735.27 | 0.00 | 0.00 |
October | 1895.74 | 355.00 | 1107.28 | 467.27 | 640.01 | 0.00 | 0.00 |
November | 1369.65 | 742.99 | 980.33 | 500.11 | 480.23 | 0.00 | 0.00 |
December | 977.07 | 972.35 | 771.86 | 349.63 | 422.22 | 0.00 | 0.00 |
Annual Sum or Average | 1894.20 | 525.48 | 1171.32 | 501.38 | 669.94 | 0.00 | 0.00 |
Minimum of Months | 977.07 | 106.82 | 771.86 | 349.63 | 422.22 | 0.00 | 0.00 |
Maximum of Months | 2677.55 | 1112.22 | 1423.78 | 616.01 | 870.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4539.59 | 1755.73 | 3192.21 | 2276.60 | 915.61 | 0.00 | 0.00 |
February | 4208.30 | 1506.92 | 2895.15 | 1873.98 | 1021.17 | 0.00 | 0.00 |
March | 2761.64 | 1326.70 | 1848.33 | 834.15 | 1014.17 | 0.00 | 0.00 |
April | 2249.58 | 894.12 | 1369.96 | 321.01 | 1048.94 | 0.00 | 0.00 |
May | 2115.36 | 266.09 | 1046.75 | 44.49 | 1002.26 | 0.00 | 0.00 |
June | 2156.77 | 228.58 | 1034.01 | 9.64 | 1024.37 | 0.00 | 0.00 |
July | 2236.97 | 145.01 | 1082.44 | 19.90 | 1062.54 | 0.00 | 0.00 |
August | 2649.05 | 220.41 | 1273.43 | 152.85 | 1120.58 | 0.00 | 0.00 |
September | 2933.91 | 320.01 | 1527.90 | 402.67 | 1125.23 | 0.00 | 0.00 |
October | 4194.57 | 593.56 | 2370.55 | 1234.83 | 1135.72 | 0.00 | 0.00 |
November | 4639.58 | 1209.15 | 3016.68 | 2077.02 | 939.66 | 0.00 | 0.00 |
December | 4604.95 | 1558.71 | 3119.17 | 2240.02 | 879.15 | 0.00 | 0.00 |
Annual Sum or Average | 3269.57 | 831.79 | 1976.55 | 952.52 | 1024.03 | 0.00 | 0.00 |
Minimum of Months | 2115.36 | 145.01 | 1034.01 | 9.64 | 879.15 | 0.00 | 0.00 |
Maximum of Months | 4639.58 | 1755.73 | 3192.21 | 2276.60 | 1135.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1291.18 | 1234.20 | 1007.86 | 544.99 | 462.86 | 0.00 | 0.00 |
February | 1508.06 | 1061.91 | 1141.12 | 577.56 | 563.55 | 0.00 | 0.00 |
March | 1532.84 | 931.77 | 1124.69 | 497.87 | 626.82 | 0.00 | 0.00 |
April | 2142.92 | 644.25 | 1396.89 | 642.60 | 754.30 | 0.00 | 0.00 |
May | 2165.47 | 215.33 | 1161.68 | 378.42 | 783.26 | 0.00 | 0.00 |
June | 2451.28 | 192.91 | 1290.49 | 452.51 | 837.99 | 0.00 | 0.00 |
July | 2237.36 | 135.74 | 1177.98 | 326.75 | 851.23 | 0.00 | 0.00 |
August | 2268.31 | 182.66 | 1191.09 | 364.61 | 826.48 | 0.00 | 0.00 |
September | 1983.03 | 236.61 | 1096.79 | 376.25 | 720.54 | 0.00 | 0.00 |
October | 1953.16 | 413.19 | 1122.89 | 485.19 | 637.70 | 0.00 | 0.00 |
November | 1399.11 | 838.82 | 962.45 | 483.69 | 478.76 | 0.00 | 0.00 |
December | 1245.47 | 1072.29 | 925.79 | 492.32 | 433.47 | 0.00 | 0.00 |
Annual Sum or Average | 1849.38 | 594.11 | 1132.66 | 467.45 | 665.21 | 0.00 | 0.00 |
Minimum of Months | 1245.47 | 135.74 | 925.79 | 326.75 | 433.47 | 0.00 | 0.00 |
Maximum of Months | 2451.28 | 1234.20 | 1396.89 | 642.60 | 851.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.948103E+09 | 0.578547E+10 | 0.147919E+10 | 0.00 | 0.147919E+10 | 0.00 | 0.00 |
February | 0.120479E+10 | 0.444460E+10 | 0.157621E+10 | 0.00 | 0.157621E+10 | 0.00 | 0.00 |
March | 0.197772E+10 | 0.418317E+10 | 0.202446E+10 | 0.00 | 0.202446E+10 | 0.00 | 0.00 |
April | 0.312054E+10 | 0.242419E+10 | 0.231223E+10 | 9490204.64 | 0.230274E+10 | 0.00 | 0.00 |
May | 0.548029E+10 | 0.675637E+09 | 0.270634E+10 | 98991865.38 | 0.260735E+10 | 0.00 | 0.00 |
June | 0.627547E+10 | 0.519439E+09 | 0.297841E+10 | 0.206232E+09 | 0.277218E+10 | 0.00 | 0.00 |
July | 0.623004E+10 | 0.340899E+09 | 0.298670E+10 | 0.113788E+09 | 0.287291E+10 | 0.00 | 0.00 |
August | 0.559468E+10 | 0.507142E+09 | 0.267464E+10 | 21036421.94 | 0.265361E+10 | 0.00 | 0.00 |
September | 0.432524E+10 | 0.782742E+09 | 0.223577E+10 | 172197.99 | 0.223559E+10 | 0.00 | 0.00 |
October | 0.357150E+10 | 0.156464E+10 | 0.200760E+10 | 0.00 | 0.200760E+10 | 0.00 | 0.00 |
November | 0.149208E+10 | 0.364680E+10 | 0.147492E+10 | 0.00 | 0.147492E+10 | 0.00 | 0.00 |
December | 0.101509E+10 | 0.511783E+10 | 0.137508E+10 | 0.00 | 0.137508E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.412355E+11 | 0.299926E+11 | 0.258316E+11 | 0.449710E+09 | 0.253818E+11 | 0.00 | 0.00 |
Minimum of Months | 0.948103E+09 | 0.340899E+09 | 0.137508E+10 | 0.00 | 0.137508E+10 | 0.00 | 0.00 |
Maximum of Months | 0.627547E+10 | 0.578547E+10 | 0.298670E+10 | 0.206232E+09 | 0.287291E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.292309E+10 | 0.354126E+10 | 0.253790E+10 | 0.129231E+10 | 0.124559E+10 | 0.00 | 0.00 |
February | 0.313218E+10 | 0.269994E+10 | 0.255255E+10 | 0.123230E+10 | 0.132024E+10 | 0.00 | 0.00 |
March | 0.446819E+10 | 0.254095E+10 | 0.332435E+10 | 0.160324E+10 | 0.172110E+10 | 0.00 | 0.00 |
April | 0.544498E+10 | 0.150816E+10 | 0.353040E+10 | 0.159670E+10 | 0.193370E+10 | 0.00 | 0.00 |
May | 0.695740E+10 | 0.446943E+09 | 0.376019E+10 | 0.163049E+10 | 0.212970E+10 | 0.00 | 0.00 |
June | 0.707500E+10 | 0.327373E+09 | 0.369045E+10 | 0.146353E+10 | 0.222692E+10 | 0.00 | 0.00 |
July | 0.706380E+10 | 0.196996E+09 | 0.367673E+10 | 0.134548E+10 | 0.233124E+10 | 0.00 | 0.00 |
August | 0.651837E+10 | 0.289611E+09 | 0.338799E+10 | 0.116482E+10 | 0.222317E+10 | 0.00 | 0.00 |
September | 0.530908E+10 | 0.509392E+09 | 0.290433E+10 | 0.998497E+09 | 0.190583E+10 | 0.00 | 0.00 |
October | 0.514880E+10 | 0.981967E+09 | 0.296574E+10 | 0.125153E+10 | 0.171421E+10 | 0.00 | 0.00 |
November | 0.349332E+10 | 0.220381E+10 | 0.254103E+10 | 0.129628E+10 | 0.124475E+10 | 0.00 | 0.00 |
December | 0.249105E+10 | 0.309947E+10 | 0.206735E+10 | 0.936465E+09 | 0.113089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.600253E+11 | 0.183459E+11 | 0.369390E+11 | 0.158117E+11 | 0.211273E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249105E+10 | 0.196996E+09 | 0.206735E+10 | 0.936465E+09 | 0.113089E+10 | 0.00 | 0.00 |
Maximum of Months | 0.707500E+10 | 0.354126E+10 | 0.376019E+10 | 0.163049E+10 | 0.233124E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121583E+11 | 0.519709E+10 | 0.855004E+10 | 0.609766E+10 | 0.245238E+10 | 0.00 | 0.00 |
February | 0.101621E+11 | 0.406356E+10 | 0.700398E+10 | 0.453355E+10 | 0.247042E+10 | 0.00 | 0.00 |
March | 0.736910E+10 | 0.398223E+10 | 0.495058E+10 | 0.223420E+10 | 0.271638E+10 | 0.00 | 0.00 |
April | 0.584562E+10 | 0.247417E+10 | 0.355094E+10 | 0.832073E+09 | 0.271887E+10 | 0.00 | 0.00 |
May | 0.574423E+10 | 0.695820E+09 | 0.280361E+10 | 0.119150E+09 | 0.268446E+10 | 0.00 | 0.00 |
June | 0.566284E+10 | 0.538292E+09 | 0.268015E+10 | 24981607.18 | 0.265517E+10 | 0.00 | 0.00 |
July | 0.607543E+10 | 0.338177E+09 | 0.289921E+10 | 53287137.46 | 0.284592E+10 | 0.00 | 0.00 |
August | 0.716320E+10 | 0.542929E+09 | 0.341077E+10 | 0.409395E+09 | 0.300137E+10 | 0.00 | 0.00 |
September | 0.771382E+10 | 0.835412E+09 | 0.396034E+10 | 0.104372E+10 | 0.291662E+10 | 0.00 | 0.00 |
October | 0.113632E+11 | 0.163069E+10 | 0.634931E+10 | 0.330739E+10 | 0.304192E+10 | 0.00 | 0.00 |
November | 0.120544E+11 | 0.342794E+10 | 0.781926E+10 | 0.538364E+10 | 0.243562E+10 | 0.00 | 0.00 |
December | 0.123166E+11 | 0.469605E+10 | 0.835443E+10 | 0.599970E+10 | 0.235472E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103629E+12 | 0.284223E+11 | 0.623326E+11 | 0.300388E+11 | 0.322939E+11 | 0.00 | 0.00 |
Minimum of Months | 0.566284E+10 | 0.338177E+09 | 0.268015E+10 | 24981607.18 | 0.235472E+10 | 0.00 | 0.00 |
Maximum of Months | 0.123166E+11 | 0.519709E+10 | 0.855004E+10 | 0.609766E+10 | 0.304192E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.330088E+10 | 0.403222E+10 | 0.269945E+10 | 0.145972E+10 | 0.123974E+10 | 0.00 | 0.00 |
February | 0.349565E+10 | 0.322634E+10 | 0.276060E+10 | 0.139725E+10 | 0.136336E+10 | 0.00 | 0.00 |
March | 0.395575E+10 | 0.317187E+10 | 0.301238E+10 | 0.133350E+10 | 0.167887E+10 | 0.00 | 0.00 |
April | 0.545188E+10 | 0.204588E+10 | 0.362076E+10 | 0.166562E+10 | 0.195514E+10 | 0.00 | 0.00 |
May | 0.581162E+10 | 0.644837E+09 | 0.311146E+10 | 0.101356E+10 | 0.209789E+10 | 0.00 | 0.00 |
June | 0.634578E+10 | 0.576593E+09 | 0.334497E+10 | 0.117291E+10 | 0.217207E+10 | 0.00 | 0.00 |
July | 0.593706E+10 | 0.472669E+09 | 0.315511E+10 | 0.875179E+09 | 0.227993E+10 | 0.00 | 0.00 |
August | 0.597008E+10 | 0.674792E+09 | 0.319022E+10 | 0.976570E+09 | 0.221365E+10 | 0.00 | 0.00 |
September | 0.514607E+10 | 0.716102E+09 | 0.284289E+10 | 0.975247E+09 | 0.186764E+10 | 0.00 | 0.00 |
October | 0.517887E+10 | 0.133368E+10 | 0.300755E+10 | 0.129953E+10 | 0.170802E+10 | 0.00 | 0.00 |
November | 0.346529E+10 | 0.279897E+10 | 0.249467E+10 | 0.125372E+10 | 0.124095E+10 | 0.00 | 0.00 |
December | 0.311979E+10 | 0.386327E+10 | 0.247965E+10 | 0.131864E+10 | 0.116101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.571787E+11 | 0.235572E+11 | 0.357197E+11 | 0.147414E+11 | 0.209783E+11 | 0.00 | 0.00 |
Minimum of Months | 0.311979E+10 | 0.472669E+09 | 0.247965E+10 | 0.875179E+09 | 0.116101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.634578E+10 | 0.403222E+10 | 0.362076E+10 | 0.166562E+10 | 0.227993E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114167E+10 | 0.507331E+10 | 0.147919E+10 | 0.00 | 0.147919E+10 | 0.00 | 0.00 |
February | 0.137872E+10 | 0.384430E+10 | 0.157620E+10 | 0.00 | 0.157620E+10 | 0.00 | 0.00 |
March | 0.215744E+10 | 0.366280E+10 | 0.202445E+10 | 0.00 | 0.202445E+10 | 0.00 | 0.00 |
April | 0.322092E+10 | 0.222589E+10 | 0.231222E+10 | 9490170.94 | 0.230273E+10 | 0.00 | 0.00 |
May | 0.550312E+10 | 0.642760E+09 | 0.270633E+10 | 98991513.86 | 0.260734E+10 | 0.00 | 0.00 |
June | 0.629096E+10 | 0.533076E+09 | 0.297840E+10 | 0.206231E+09 | 0.277217E+10 | 0.00 | 0.00 |
July | 0.626015E+10 | 0.356202E+09 | 0.298669E+10 | 0.113787E+09 | 0.287290E+10 | 0.00 | 0.00 |
August | 0.566013E+10 | 0.506396E+09 | 0.267463E+10 | 21036347.24 | 0.265360E+10 | 0.00 | 0.00 |
September | 0.436511E+10 | 0.709430E+09 | 0.223576E+10 | 172197.38 | 0.223559E+10 | 0.00 | 0.00 |
October | 0.364633E+10 | 0.142026E+10 | 0.200759E+10 | 0.00 | 0.200759E+10 | 0.00 | 0.00 |
November | 0.165692E+10 | 0.314448E+10 | 0.147492E+10 | 0.00 | 0.147492E+10 | 0.00 | 0.00 |
December | 0.121348E+10 | 0.433177E+10 | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.424949E+11 | 0.264507E+11 | 0.258315E+11 | 0.449709E+09 | 0.253818E+11 | 0.00 | 0.00 |
Minimum of Months | 0.114167E+10 | 0.356202E+09 | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.629096E+10 | 0.507331E+10 | 0.298669E+10 | 0.206231E+09 | 0.287290E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.296918E+10 | 0.324585E+10 | 0.253789E+10 | 0.129230E+10 | 0.124559E+10 | 0.00 | 0.00 |
February | 0.316481E+10 | 0.247824E+10 | 0.255254E+10 | 0.123230E+10 | 0.132024E+10 | 0.00 | 0.00 |
March | 0.445592E+10 | 0.238132E+10 | 0.332433E+10 | 0.160323E+10 | 0.172110E+10 | 0.00 | 0.00 |
April | 0.537959E+10 | 0.151204E+10 | 0.353039E+10 | 0.159670E+10 | 0.193369E+10 | 0.00 | 0.00 |
May | 0.687161E+10 | 0.460263E+09 | 0.376017E+10 | 0.163048E+10 | 0.212969E+10 | 0.00 | 0.00 |
June | 0.698944E+10 | 0.379984E+09 | 0.369044E+10 | 0.146352E+10 | 0.222691E+10 | 0.00 | 0.00 |
July | 0.696757E+10 | 0.258555E+09 | 0.367671E+10 | 0.134548E+10 | 0.233123E+10 | 0.00 | 0.00 |
August | 0.643207E+10 | 0.364094E+09 | 0.338798E+10 | 0.116481E+10 | 0.222316E+10 | 0.00 | 0.00 |
September | 0.524950E+10 | 0.504639E+09 | 0.290431E+10 | 0.998493E+09 | 0.190582E+10 | 0.00 | 0.00 |
October | 0.509016E+10 | 0.968039E+09 | 0.296573E+10 | 0.125153E+10 | 0.171420E+10 | 0.00 | 0.00 |
November | 0.349348E+10 | 0.205795E+10 | 0.254102E+10 | 0.129628E+10 | 0.124475E+10 | 0.00 | 0.00 |
December | 0.253321E+10 | 0.283365E+10 | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.595966E+11 | 0.174446E+11 | 0.369388E+11 | 0.158116E+11 | 0.211273E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253321E+10 | 0.258555E+09 | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.698944E+10 | 0.324585E+10 | 0.376017E+10 | 0.163048E+10 | 0.233123E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120681E+11 | 0.504183E+10 | 0.855001E+10 | 0.609764E+10 | 0.245237E+10 | 0.00 | 0.00 |
February | 0.101081E+11 | 0.390389E+10 | 0.700395E+10 | 0.453354E+10 | 0.247041E+10 | 0.00 | 0.00 |
March | 0.736360E+10 | 0.375605E+10 | 0.495056E+10 | 0.223419E+10 | 0.271637E+10 | 0.00 | 0.00 |
April | 0.585840E+10 | 0.237122E+10 | 0.355093E+10 | 0.832070E+09 | 0.271886E+10 | 0.00 | 0.00 |
May | 0.575782E+10 | 0.667114E+09 | 0.280360E+10 | 0.119149E+09 | 0.268445E+10 | 0.00 | 0.00 |
June | 0.568948E+10 | 0.544190E+09 | 0.268014E+10 | 24981518.47 | 0.265516E+10 | 0.00 | 0.00 |
July | 0.611533E+10 | 0.346433E+09 | 0.289920E+10 | 53286948.24 | 0.284591E+10 | 0.00 | 0.00 |
August | 0.719438E+10 | 0.548604E+09 | 0.341075E+10 | 0.409393E+09 | 0.300136E+10 | 0.00 | 0.00 |
September | 0.768660E+10 | 0.799264E+09 | 0.396032E+10 | 0.104371E+10 | 0.291661E+10 | 0.00 | 0.00 |
October | 0.112885E+11 | 0.160884E+10 | 0.634929E+10 | 0.330738E+10 | 0.304191E+10 | 0.00 | 0.00 |
November | 0.119908E+11 | 0.330321E+10 | 0.781924E+10 | 0.538363E+10 | 0.243561E+10 | 0.00 | 0.00 |
December | 0.122677E+11 | 0.447293E+10 | 0.835440E+10 | 0.599968E+10 | 0.235471E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103389E+12 | 0.273636E+11 | 0.623324E+11 | 0.300386E+11 | 0.322937E+11 | 0.00 | 0.00 |
Minimum of Months | 0.568948E+10 | 0.346433E+09 | 0.268014E+10 | 24981518.47 | 0.235471E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122677E+11 | 0.504183E+10 | 0.855001E+10 | 0.609764E+10 | 0.304191E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.341535E+10 | 0.353078E+10 | 0.269944E+10 | 0.145971E+10 | 0.123973E+10 | 0.00 | 0.00 |
February | 0.362060E+10 | 0.273858E+10 | 0.276059E+10 | 0.139724E+10 | 0.136335E+10 | 0.00 | 0.00 |
March | 0.409463E+10 | 0.262737E+10 | 0.301236E+10 | 0.133350E+10 | 0.167887E+10 | 0.00 | 0.00 |
April | 0.558244E+10 | 0.170903E+10 | 0.362074E+10 | 0.166561E+10 | 0.195513E+10 | 0.00 | 0.00 |
May | 0.585886E+10 | 0.553168E+09 | 0.311145E+10 | 0.101356E+10 | 0.209789E+10 | 0.00 | 0.00 |
June | 0.641739E+10 | 0.476306E+09 | 0.334496E+10 | 0.117290E+10 | 0.217206E+10 | 0.00 | 0.00 |
July | 0.606288E+10 | 0.340561E+09 | 0.315510E+10 | 0.875176E+09 | 0.227992E+10 | 0.00 | 0.00 |
August | 0.613684E+10 | 0.465121E+09 | 0.319021E+10 | 0.976566E+09 | 0.221364E+10 | 0.00 | 0.00 |
September | 0.518990E+10 | 0.598098E+09 | 0.284288E+10 | 0.975243E+09 | 0.186763E+10 | 0.00 | 0.00 |
October | 0.526337E+10 | 0.112257E+10 | 0.300754E+10 | 0.129952E+10 | 0.170801E+10 | 0.00 | 0.00 |
November | 0.360519E+10 | 0.230261E+10 | 0.249466E+10 | 0.125372E+10 | 0.124095E+10 | 0.00 | 0.00 |
December | 0.330135E+10 | 0.307279E+10 | 0.247964E+10 | 0.131864E+10 | 0.116100E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.585488E+11 | 0.195370E+11 | 0.357196E+11 | 0.147414E+11 | 0.209782E+11 | 0.00 | 0.00 |
Minimum of Months | 0.330135E+10 | 0.340561E+09 | 0.247964E+10 | 0.875176E+09 | 0.116100E+10 | 0.00 | 0.00 |
Maximum of Months | 0.641739E+10 | 0.353078E+10 | 0.362074E+10 | 0.166561E+10 | 0.227992E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123230E+10 | 0.467524E+10 | 0.147919E+10 | 0.00 | 0.147919E+10 | 0.00 | 0.00 |
February | 0.144902E+10 | 0.354992E+10 | 0.157620E+10 | 0.00 | 0.157620E+10 | 0.00 | 0.00 |
March | 0.220686E+10 | 0.344065E+10 | 0.202445E+10 | 0.00 | 0.202445E+10 | 0.00 | 0.00 |
April | 0.320738E+10 | 0.216988E+10 | 0.231222E+10 | 9490170.94 | 0.230273E+10 | 0.00 | 0.00 |
May | 0.541072E+10 | 0.687823E+09 | 0.270633E+10 | 98991513.86 | 0.260734E+10 | 0.00 | 0.00 |
June | 0.618795E+10 | 0.578213E+09 | 0.297840E+10 | 0.206231E+09 | 0.277217E+10 | 0.00 | 0.00 |
July | 0.614024E+10 | 0.400533E+09 | 0.298669E+10 | 0.113787E+09 | 0.287290E+10 | 0.00 | 0.00 |
August | 0.556312E+10 | 0.546841E+09 | 0.267463E+10 | 21036347.24 | 0.265360E+10 | 0.00 | 0.00 |
September | 0.428056E+10 | 0.740596E+09 | 0.223576E+10 | 172197.38 | 0.223559E+10 | 0.00 | 0.00 |
October | 0.360823E+10 | 0.139433E+10 | 0.200759E+10 | 0.00 | 0.200759E+10 | 0.00 | 0.00 |
November | 0.172559E+10 | 0.290526E+10 | 0.147492E+10 | 0.00 | 0.147492E+10 | 0.00 | 0.00 |
December | 0.129240E+10 | 0.398265E+10 | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.423044E+11 | 0.250719E+11 | 0.258315E+11 | 0.449709E+09 | 0.253818E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123230E+10 | 0.400533E+09 | 0.137507E+10 | 0.00 | 0.137507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.618795E+10 | 0.467524E+10 | 0.298669E+10 | 0.206231E+09 | 0.287290E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.308648E+10 | 0.297896E+10 | 0.253789E+10 | 0.129230E+10 | 0.124559E+10 | 0.00 | 0.00 |
February | 0.324820E+10 | 0.228951E+10 | 0.255254E+10 | 0.123230E+10 | 0.132024E+10 | 0.00 | 0.00 |
March | 0.450326E+10 | 0.224922E+10 | 0.332433E+10 | 0.160323E+10 | 0.172110E+10 | 0.00 | 0.00 |
April | 0.537886E+10 | 0.148161E+10 | 0.353039E+10 | 0.159670E+10 | 0.193369E+10 | 0.00 | 0.00 |
May | 0.682433E+10 | 0.486471E+09 | 0.376017E+10 | 0.163048E+10 | 0.212969E+10 | 0.00 | 0.00 |
June | 0.694020E+10 | 0.408172E+09 | 0.369044E+10 | 0.146352E+10 | 0.222691E+10 | 0.00 | 0.00 |
July | 0.690996E+10 | 0.286118E+09 | 0.367671E+10 | 0.134548E+10 | 0.233123E+10 | 0.00 | 0.00 |
August | 0.638654E+10 | 0.388967E+09 | 0.338798E+10 | 0.116481E+10 | 0.222316E+10 | 0.00 | 0.00 |
September | 0.521304E+10 | 0.521389E+09 | 0.290431E+10 | 0.998493E+09 | 0.190582E+10 | 0.00 | 0.00 |
October | 0.507755E+10 | 0.950820E+09 | 0.296573E+10 | 0.125153E+10 | 0.171420E+10 | 0.00 | 0.00 |
November | 0.355013E+10 | 0.192583E+10 | 0.254102E+10 | 0.129628E+10 | 0.124475E+10 | 0.00 | 0.00 |
December | 0.261698E+10 | 0.260434E+10 | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.597355E+11 | 0.165714E+11 | 0.369388E+11 | 0.158116E+11 | 0.211273E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261698E+10 | 0.286118E+09 | 0.206734E+10 | 0.936461E+09 | 0.113088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.694020E+10 | 0.297896E+10 | 0.376017E+10 | 0.163048E+10 | 0.233123E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121588E+11 | 0.470256E+10 | 0.855001E+10 | 0.609764E+10 | 0.245237E+10 | 0.00 | 0.00 |
February | 0.101807E+11 | 0.364555E+10 | 0.700395E+10 | 0.453354E+10 | 0.247041E+10 | 0.00 | 0.00 |
March | 0.739677E+10 | 0.355342E+10 | 0.495056E+10 | 0.223419E+10 | 0.271637E+10 | 0.00 | 0.00 |
April | 0.583090E+10 | 0.231756E+10 | 0.355093E+10 | 0.832070E+09 | 0.271886E+10 | 0.00 | 0.00 |
May | 0.566579E+10 | 0.712682E+09 | 0.280360E+10 | 0.119149E+09 | 0.268445E+10 | 0.00 | 0.00 |
June | 0.559033E+10 | 0.592471E+09 | 0.268014E+10 | 24981518.47 | 0.265516E+10 | 0.00 | 0.00 |
July | 0.599151E+10 | 0.388382E+09 | 0.289920E+10 | 53286948.24 | 0.284591E+10 | 0.00 | 0.00 |
August | 0.709521E+10 | 0.590339E+09 | 0.341075E+10 | 0.409393E+09 | 0.300136E+10 | 0.00 | 0.00 |
September | 0.760469E+10 | 0.829462E+09 | 0.396032E+10 | 0.104371E+10 | 0.291661E+10 | 0.00 | 0.00 |
October | 0.112347E+11 | 0.158980E+10 | 0.634929E+10 | 0.330738E+10 | 0.304191E+10 | 0.00 | 0.00 |
November | 0.120258E+11 | 0.313412E+10 | 0.781924E+10 | 0.538363E+10 | 0.243561E+10 | 0.00 | 0.00 |
December | 0.123339E+11 | 0.417484E+10 | 0.835440E+10 | 0.599968E+10 | 0.235471E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103109E+12 | 0.262312E+11 | 0.623324E+11 | 0.300386E+11 | 0.322937E+11 | 0.00 | 0.00 |
Minimum of Months | 0.559033E+10 | 0.388382E+09 | 0.268014E+10 | 24981518.47 | 0.235471E+10 | 0.00 | 0.00 |
Maximum of Months | 0.123339E+11 | 0.470256E+10 | 0.855001E+10 | 0.609764E+10 | 0.304191E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.345831E+10 | 0.330568E+10 | 0.269944E+10 | 0.145971E+10 | 0.123973E+10 | 0.00 | 0.00 |
February | 0.364830E+10 | 0.256896E+10 | 0.276059E+10 | 0.139724E+10 | 0.136335E+10 | 0.00 | 0.00 |
March | 0.410557E+10 | 0.249566E+10 | 0.301236E+10 | 0.133350E+10 | 0.167887E+10 | 0.00 | 0.00 |
April | 0.555444E+10 | 0.166990E+10 | 0.362074E+10 | 0.166561E+10 | 0.195513E+10 | 0.00 | 0.00 |
May | 0.579999E+10 | 0.576728E+09 | 0.311145E+10 | 0.101356E+10 | 0.209789E+10 | 0.00 | 0.00 |
June | 0.635373E+10 | 0.500011E+09 | 0.334496E+10 | 0.117290E+10 | 0.217206E+10 | 0.00 | 0.00 |
July | 0.599255E+10 | 0.363563E+09 | 0.315510E+10 | 0.875176E+09 | 0.227992E+10 | 0.00 | 0.00 |
August | 0.607545E+10 | 0.489245E+09 | 0.319021E+10 | 0.976566E+09 | 0.221364E+10 | 0.00 | 0.00 |
September | 0.514002E+10 | 0.613306E+09 | 0.284288E+10 | 0.975243E+09 | 0.186763E+10 | 0.00 | 0.00 |
October | 0.523134E+10 | 0.110668E+10 | 0.300754E+10 | 0.129952E+10 | 0.170801E+10 | 0.00 | 0.00 |
November | 0.362648E+10 | 0.217422E+10 | 0.249466E+10 | 0.125372E+10 | 0.124095E+10 | 0.00 | 0.00 |
December | 0.333585E+10 | 0.287202E+10 | 0.247964E+10 | 0.131864E+10 | 0.116100E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.583220E+11 | 0.187360E+11 | 0.357196E+11 | 0.147414E+11 | 0.209782E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333585E+10 | 0.363563E+09 | 0.247964E+10 | 0.875176E+09 | 0.116100E+10 | 0.00 | 0.00 |
Maximum of Months | 0.635373E+10 | 0.330568E+10 | 0.362074E+10 | 0.166561E+10 | 0.227992E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.316654E+11 | -0.306424E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102298E+10 | 58.98 | 0.00 | 0.00 |
February | 0.285447E+11 | -0.276197E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -925033711.4 | 58.98 | 0.00 | 0.00 |
March | 0.322693E+11 | -0.312421E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102719E+10 | 58.97 | 0.00 | 0.00 |
April | 0.275772E+11 | -0.265862E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991009905.9 | 58.97 | 0.00 | 0.00 |
May | 0.274213E+11 | -0.263973E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102402E+10 | 58.97 | 0.00 | 0.00 |
June | 0.255250E+11 | -0.245324E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992650969.0 | 58.97 | 0.00 | 0.00 |
July | 0.235918E+11 | -0.225716E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102011E+10 | 58.97 | 0.00 | 0.00 |
August | 0.260128E+11 | -0.249897E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102314E+10 | 58.97 | 0.00 | 0.00 |
September | 0.248319E+11 | -0.238443E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987542950.6 | 58.97 | 0.00 | 0.00 |
October | 0.274241E+11 | -0.264052E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101887E+10 | 58.97 | 0.00 | 0.00 |
November | 0.287894E+11 | -0.278037E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985687268.6 | 58.97 | 0.00 | 0.00 |
December | 0.301990E+11 | -0.291796E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101939E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.333852E+12 | -0.321814E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120376E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.235918E+11 | -0.312421E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102719E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.322693E+11 | -0.225716E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925033711.4 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.50 | 0.48 | 01-JAN-07:49 | 7755.15 | 36.97 | 300.33 | 296.17 | 1434.31 | 25.98 | 217.00 | 278.67 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3369.40 | 28.26 | 173.67 | 279.67 | 1244.31 | 23.23 | 186.33 | 266.33 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 1582.52 | 20.02 | 56.00 | 319.67 | 923.77 | 21.35 | 174.17 | 281.00 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1258.74 | 19.22 | 29.50 | 323.33 | 725.51 | 20.52 | 172.33 | 284.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:19 | 1125.05 | 19.46 | 8.50 | 349.50 | 632.91 | 20.81 | 166.17 | 299.83 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:00 | 1068.89 | 19.10 | 2.50 | 350.33 | 605.06 | 20.47 | 166.17 | 303.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1178.73 | 19.47 | 15.00 | 360.00 | 647.27 | 20.81 | 195.00 | 313.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1368.33 | 19.76 | 42.67 | 346.67 | 736.37 | 21.08 | 240.83 | 307.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1609.71 | 20.05 | 88.00 | 317.50 | 851.55 | 21.28 | 225.33 | 281.83 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2775.33 | 23.94 | 167.83 | 314.17 | 1154.73 | 22.37 | 237.67 | 283.33 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-07:00 | 7827.42 | 36.40 | 297.33 | 288.67 | 1366.65 | 24.17 | 202.00 | 270.67 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7905.21 | 37.74 | 279.33 | 284.33 | 1821.31 | 27.87 | 206.83 | 267.17 |
Annual Sum or Average | 4027.67 | 0.51 | 3028.53 | 24.45 | 1460.67 | 3830.00 | 977.62 | 22.31 | 2389.83 | 3437.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1068.89 | 19.10 | 2.50 | 279.67 | 605.06 | 20.47 | 166.17 | 266.33 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7905.21 | 37.74 | 300.33 | 360.00 | 1821.31 | 27.87 | 240.83 | 313.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1992.23 | 23.66 | 104.50 | 271.00 | 1073.98 | 23.73 | 125.50 | 222.83 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2205.56 | 23.74 | 91.00 | 261.50 | 1169.87 | 23.89 | 114.00 | 228.00 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 2297.05 | 23.70 | 86.33 | 315.33 | 1213.61 | 23.84 | 122.67 | 276.17 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:10 | 2350.89 | 22.79 | 96.00 | 326.33 | 1247.80 | 23.15 | 121.83 | 293.33 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2660.08 | 24.08 | 112.00 | 359.83 | 1066.29 | 23.06 | 127.67 | 314.83 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2392.43 | 23.70 | 122.83 | 358.83 | 1009.20 | 22.95 | 145.33 | 320.83 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2303.45 | 23.16 | 112.83 | 365.17 | 990.92 | 22.42 | 158.50 | 318.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2122.09 | 23.07 | 106.17 | 347.17 | 1104.79 | 23.47 | 171.50 | 308.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2027.04 | 23.20 | 101.17 | 314.17 | 1035.72 | 23.49 | 171.17 | 278.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-06:49 | 2109.35 | 23.42 | 93.17 | 303.00 | 1078.59 | 23.56 | 160.67 | 269.83 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-07:49 | 1752.12 | 22.80 | 86.00 | 266.83 | 897.81 | 22.84 | 124.00 | 230.50 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1885.48 | 23.39 | 91.50 | 257.50 | 1004.69 | 23.42 | 111.00 | 208.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2188.11 | 23.39 | 1203.50 | 3746.67 | 1072.92 | 23.29 | 1653.83 | 3268.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1752.12 | 22.79 | 86.00 | 257.50 | 897.81 | 22.42 | 111.00 | 208.00 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2660.08 | 24.08 | 122.83 | 365.17 | 1247.80 | 23.89 | 171.50 | 320.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:50 | 544.72 | 16.25 | 0.00 | 251.67 | 352.43 | 17.93 | 0.00 | 164.00 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 629.09 | 17.42 | 0.00 | 248.17 | 408.48 | 19.01 | 2.83 | 184.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 735.30 | 18.42 | 0.00 | 306.33 | 462.02 | 19.81 | 11.00 | 236.67 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:49 | 875.26 | 18.83 | 0.00 | 326.50 | 532.86 | 20.12 | 79.67 | 284.83 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1074.01 | 21.05 | 56.50 | 370.33 | 618.05 | 22.22 | 188.50 | 330.67 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1242.28 | 22.16 | 108.17 | 374.00 | 654.87 | 21.35 | 217.33 | 338.17 |
July | 390.00 | 0.49 | 0.48 | 01-JUL-06:40 | 1214.98 | 20.86 | 80.83 | 376.50 | 659.51 | 22.13 | 241.67 | 340.17 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-07:10 | 1066.39 | 19.59 | 11.33 | 353.17 | 598.95 | 20.89 | 175.83 | 317.50 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 893.27 | 18.81 | 0.17 | 315.50 | 513.67 | 20.10 | 75.50 | 264.83 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 771.07 | 18.58 | 0.00 | 296.50 | 471.76 | 20.03 | 13.83 | 244.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:50 | 559.79 | 16.86 | 0.00 | 242.83 | 364.10 | 18.51 | 0.00 | 169.00 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:39 | 545.21 | 16.51 | 0.00 | 242.83 | 354.44 | 18.24 | 0.00 | 148.50 |
Annual Sum or Average | 4027.67 | 0.51 | 871.71 | 18.95 | 257.00 | 3704.33 | 510.62 | 20.16 | 1006.17 | 3022.67 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 544.72 | 16.25 | 0.00 | 242.83 | 352.43 | 17.93 | 0.00 | 148.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1242.28 | 22.16 | 108.17 | 376.50 | 659.51 | 22.22 | 241.67 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2280.62 | 24.58 | 112.67 | 275.83 | 1263.44 | 24.48 | 128.00 | 230.00 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2036.90 | 23.84 | 89.33 | 266.00 | 1073.39 | 23.83 | 128.83 | 234.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2184.74 | 23.22 | 81.00 | 311.67 | 1146.46 | 23.53 | 115.17 | 269.00 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:20 | 2468.66 | 21.70 | 82.83 | 327.00 | 1295.37 | 22.11 | 108.67 | 293.67 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:40 | 2045.61 | 18.24 | 1.17 | 356.33 | 904.53 | 20.35 | 102.50 | 317.50 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2165.45 | 18.10 | 0.67 | 359.00 | 922.97 | 20.14 | 103.67 | 318.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 2003.70 | 18.58 | 6.50 | 365.83 | 890.49 | 20.40 | 122.33 | 322.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2069.13 | 20.52 | 59.17 | 349.17 | 947.33 | 20.62 | 137.50 | 309.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1919.80 | 21.94 | 82.33 | 314.67 | 983.40 | 22.33 | 153.00 | 278.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:49 | 2455.72 | 24.58 | 110.67 | 309.33 | 1014.45 | 23.45 | 166.67 | 273.00 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1978.57 | 23.73 | 96.67 | 266.50 | 1063.11 | 23.78 | 124.83 | 231.33 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:39 | 2124.31 | 25.20 | 106.67 | 271.00 | 1147.23 | 24.95 | 124.33 | 219.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2142.81 | 21.78 | 829.67 | 3772.33 | 1045.16 | 22.32 | 1515.50 | 3295.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1919.80 | 18.10 | 0.67 | 266.00 | 890.49 | 20.14 | 102.50 | 219.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2468.66 | 25.20 | 112.67 | 365.83 | 1295.37 | 24.95 | 166.67 | 322.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.50 | 0.48 | 01-JAN-07:49 | 7818.77 | 36.47 | 297.33 | 296.17 | 1535.46 | 21.75 | 92.17 | 281.67 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3425.14 | 24.68 | 165.33 | 280.00 | 1336.98 | 18.93 | 36.50 | 268.00 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 1621.49 | 13.81 | 0.00 | 319.83 | 991.74 | 17.38 | 0.00 | 286.00 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1284.11 | 13.39 | 0.00 | 323.83 | 775.30 | 16.80 | 0.00 | 289.67 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 1142.90 | 13.60 | 0.00 | 350.00 | 673.87 | 17.05 | 0.00 | 305.50 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:49 | 1085.60 | 13.25 | 0.00 | 350.67 | 644.09 | 16.68 | 0.00 | 308.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1195.27 | 13.48 | 0.00 | 360.00 | 688.40 | 16.89 | 0.00 | 318.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1386.82 | 13.75 | 0.00 | 346.83 | 783.48 | 17.12 | 0.00 | 312.50 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:10 | 1629.69 | 13.91 | 3.67 | 318.17 | 906.66 | 17.13 | 0.00 | 286.67 |
October | 330.00 | 0.49 | 0.48 | 01-OCT-07:10 | 2814.82 | 18.77 | 80.67 | 314.50 | 1241.50 | 18.27 | 10.50 | 287.83 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-07:00 | 7883.76 | 35.88 | 296.00 | 289.00 | 1496.85 | 21.56 | 90.83 | 276.33 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7967.38 | 37.33 | 279.33 | 284.33 | 1927.93 | 23.98 | 110.83 | 268.50 |
Annual Sum or Average | 4027.67 | 0.50 | 3062.68 | 19.94 | 1122.33 | 3833.33 | 1046.51 | 18.44 | 340.83 | 3489.67 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 1085.60 | 13.25 | 0.00 | 280.00 | 644.09 | 16.68 | 0.00 | 268.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7967.38 | 37.33 | 297.33 | 360.00 | 1927.93 | 23.98 | 110.83 | 318.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 2025.64 | 21.16 | 100.17 | 272.67 | 1118.26 | 21.82 | 72.33 | 229.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2247.37 | 20.99 | 89.67 | 262.67 | 1218.85 | 21.80 | 64.33 | 231.67 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 2322.08 | 19.46 | 74.33 | 316.00 | 1274.62 | 21.39 | 56.50 | 282.17 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:10 | 2380.85 | 19.75 | 95.67 | 327.17 | 1303.95 | 20.73 | 68.00 | 296.67 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2679.10 | 20.41 | 106.00 | 361.17 | 1125.28 | 20.39 | 55.00 | 320.50 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2420.29 | 19.85 | 114.00 | 359.50 | 1064.00 | 20.35 | 62.67 | 326.67 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2333.56 | 20.10 | 112.33 | 366.33 | 1045.23 | 19.74 | 53.67 | 323.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2144.89 | 20.01 | 105.17 | 347.67 | 1156.72 | 21.11 | 75.50 | 312.50 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2063.30 | 20.20 | 96.00 | 314.67 | 1085.54 | 21.13 | 67.50 | 282.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-06:49 | 2156.18 | 20.45 | 87.67 | 303.17 | 1130.67 | 21.24 | 57.00 | 273.17 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-07:49 | 1786.71 | 19.96 | 84.00 | 267.83 | 942.70 | 20.65 | 55.50 | 234.17 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1915.03 | 20.90 | 89.17 | 258.50 | 1045.95 | 21.56 | 61.67 | 213.67 |
Annual Sum or Average | 4027.67 | 0.51 | 2219.26 | 20.25 | 1154.17 | 3757.33 | 1124.75 | 20.94 | 749.67 | 3326.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1786.71 | 19.46 | 74.33 | 258.50 | 942.70 | 19.74 | 53.67 | 213.67 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2679.10 | 21.16 | 114.00 | 366.33 | 1303.95 | 21.82 | 75.50 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-08:50 | 554.53 | 10.76 | 0.00 | 252.67 | 375.65 | 14.39 | 0.00 | 179.67 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 641.40 | 11.98 | 0.00 | 249.33 | 435.66 | 15.61 | 0.00 | 193.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 750.69 | 13.17 | 0.00 | 307.67 | 492.99 | 16.68 | 0.00 | 248.83 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:49 | 893.47 | 13.44 | 0.00 | 327.33 | 568.46 | 16.87 | 0.00 | 291.50 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1093.61 | 15.68 | 27.17 | 370.67 | 658.39 | 19.00 | 27.50 | 336.00 |
June | 394.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1263.02 | 17.19 | 58.00 | 374.33 | 707.06 | 20.31 | 59.33 | 348.67 |
July | 390.00 | 0.49 | 0.48 | 01-JUL-06:40 | 1234.24 | 15.30 | 23.50 | 376.67 | 701.51 | 18.62 | 24.50 | 343.33 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-06:00 | 1083.71 | 13.86 | 0.00 | 353.33 | 637.21 | 17.27 | 0.00 | 322.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 908.54 | 13.25 | 0.00 | 316.00 | 546.69 | 16.60 | 0.00 | 271.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 784.88 | 13.18 | 0.00 | 297.33 | 502.55 | 16.68 | 0.00 | 252.33 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:39 | 570.14 | 11.28 | 0.00 | 244.33 | 388.17 | 14.97 | 0.00 | 180.50 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-08:30 | 554.52 | 10.91 | 0.00 | 243.67 | 377.66 | 14.62 | 0.00 | 162.33 |
Annual Sum or Average | 4027.67 | 0.51 | 887.19 | 13.51 | 108.67 | 3713.33 | 544.86 | 16.96 | 111.33 | 3130.17 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 554.52 | 10.76 | 0.00 | 243.67 | 375.65 | 14.39 | 0.00 | 162.33 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1263.02 | 17.19 | 58.00 | 376.67 | 707.06 | 20.31 | 59.33 | 348.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2314.52 | 22.16 | 109.33 | 276.83 | 1309.65 | 22.68 | 81.83 | 237.00 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2056.29 | 19.85 | 79.17 | 266.83 | 1126.49 | 21.64 | 60.17 | 237.67 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2235.47 | 20.17 | 81.00 | 313.33 | 1200.28 | 21.13 | 56.67 | 276.50 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:09 | 2497.62 | 18.40 | 82.00 | 327.67 | 1352.65 | 19.42 | 53.00 | 297.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:40 | 2069.90 | 13.72 | 0.00 | 357.33 | 955.03 | 17.13 | 0.00 | 320.67 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-07:10 | 2193.28 | 13.62 | 0.00 | 359.17 | 973.97 | 16.95 | 0.00 | 324.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 2026.98 | 14.18 | 3.67 | 366.67 | 939.37 | 17.25 | 0.00 | 327.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2092.83 | 16.85 | 59.00 | 350.67 | 997.72 | 17.53 | 5.50 | 316.50 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1954.55 | 18.73 | 80.50 | 315.67 | 1032.02 | 19.80 | 51.67 | 282.83 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:40 | 2502.37 | 21.91 | 108.83 | 310.17 | 1066.59 | 21.07 | 53.50 | 276.83 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-09:39 | 2013.78 | 21.06 | 95.17 | 268.17 | 1108.33 | 21.76 | 66.67 | 236.00 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:30 | 2159.94 | 22.85 | 103.00 | 271.50 | 1194.42 | 23.17 | 74.00 | 226.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2174.37 | 18.32 | 801.67 | 3784.00 | 1095.57 | 19.74 | 503.00 | 3359.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1954.55 | 13.62 | 0.00 | 266.83 | 939.37 | 16.95 | 0.00 | 226.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2502.37 | 22.85 | 109.33 | 366.67 | 1352.65 | 23.17 | 81.83 | 327.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.50 | 0.48 | 01-JAN-07:49 | 7820.39 | 36.46 | 297.33 | 296.17 | 1537.13 | 21.74 | 92.17 | 281.67 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3427.36 | 24.66 | 165.33 | 280.00 | 1338.57 | 18.92 | 36.50 | 268.00 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 1623.59 | 13.78 | 0.00 | 320.33 | 993.08 | 17.37 | 0.00 | 286.00 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1285.78 | 13.36 | 0.00 | 323.83 | 776.38 | 16.79 | 0.00 | 289.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 1144.44 | 13.57 | 0.00 | 350.33 | 674.86 | 17.04 | 0.00 | 305.67 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:49 | 1087.04 | 13.22 | 0.00 | 350.67 | 645.02 | 16.67 | 0.00 | 308.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1197.01 | 13.45 | 0.00 | 360.17 | 689.47 | 16.87 | 0.00 | 318.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1388.97 | 13.72 | 0.00 | 346.83 | 784.75 | 17.11 | 0.00 | 312.50 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:10 | 1632.29 | 13.88 | 3.67 | 318.17 | 908.20 | 17.12 | 0.00 | 286.67 |
October | 330.00 | 0.49 | 0.48 | 01-OCT-07:10 | 2817.67 | 18.74 | 80.67 | 314.67 | 1243.35 | 18.26 | 10.50 | 288.00 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-07:00 | 7885.67 | 35.88 | 296.00 | 289.00 | 1498.51 | 21.55 | 90.83 | 276.50 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7968.96 | 37.33 | 279.33 | 284.33 | 1929.71 | 23.97 | 110.83 | 268.50 |
Annual Sum or Average | 4027.67 | 0.50 | 3064.63 | 19.92 | 1122.33 | 3834.50 | 1047.88 | 18.43 | 340.83 | 3490.33 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 1087.04 | 13.22 | 0.00 | 280.00 | 645.02 | 16.67 | 0.00 | 268.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7968.96 | 37.33 | 297.33 | 360.17 | 1929.71 | 23.97 | 110.83 | 318.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 2026.36 | 21.14 | 100.17 | 272.67 | 1119.11 | 21.81 | 72.33 | 229.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2248.17 | 20.97 | 89.67 | 262.67 | 1219.82 | 21.79 | 64.33 | 231.83 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 2323.21 | 19.43 | 74.33 | 316.17 | 1275.78 | 21.37 | 56.50 | 282.17 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:10 | 2382.24 | 19.72 | 95.67 | 327.17 | 1305.15 | 20.72 | 68.00 | 297.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2680.73 | 20.38 | 106.00 | 361.17 | 1126.63 | 20.38 | 55.00 | 320.83 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2422.08 | 19.82 | 114.00 | 359.50 | 1065.36 | 20.33 | 62.67 | 326.83 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2335.59 | 20.07 | 112.33 | 366.67 | 1046.70 | 19.73 | 53.67 | 323.67 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2146.90 | 19.98 | 105.17 | 347.67 | 1158.18 | 21.09 | 75.50 | 312.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2065.24 | 20.18 | 96.00 | 314.67 | 1086.96 | 21.12 | 67.50 | 282.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-06:49 | 2157.53 | 20.42 | 87.67 | 303.17 | 1131.94 | 21.22 | 57.00 | 273.17 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-07:49 | 1787.48 | 19.93 | 84.00 | 267.83 | 943.59 | 20.63 | 55.50 | 234.33 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1915.74 | 20.88 | 89.17 | 258.50 | 1046.79 | 21.55 | 61.67 | 213.67 |
Annual Sum or Average | 4027.67 | 0.51 | 2220.67 | 20.22 | 1154.17 | 3757.83 | 1125.96 | 20.93 | 749.67 | 3328.00 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1787.48 | 19.43 | 74.33 | 258.50 | 943.59 | 19.73 | 53.67 | 213.67 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2680.73 | 21.14 | 114.00 | 366.67 | 1305.15 | 21.81 | 75.50 | 326.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-08:50 | 554.85 | 10.72 | 0.00 | 252.67 | 376.05 | 14.37 | 0.00 | 179.83 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 641.78 | 11.95 | 0.00 | 249.67 | 436.11 | 15.59 | 0.00 | 194.00 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 751.28 | 13.14 | 0.00 | 307.83 | 493.55 | 16.66 | 0.00 | 249.00 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:49 | 894.31 | 13.41 | 0.00 | 327.33 | 569.17 | 16.85 | 0.00 | 291.83 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1094.90 | 15.65 | 27.17 | 370.83 | 659.33 | 18.98 | 27.50 | 336.00 |
June | 394.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1264.52 | 17.16 | 58.00 | 374.33 | 708.10 | 20.30 | 59.33 | 348.67 |
July | 390.00 | 0.49 | 0.48 | 01-JUL-06:40 | 1235.87 | 15.27 | 23.50 | 376.67 | 702.59 | 18.60 | 24.50 | 343.50 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-06:00 | 1085.11 | 13.83 | 0.00 | 353.33 | 638.17 | 17.25 | 0.00 | 322.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 909.61 | 13.22 | 0.00 | 316.00 | 547.48 | 16.58 | 0.00 | 271.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 785.55 | 13.15 | 0.00 | 297.33 | 503.17 | 16.67 | 0.00 | 252.33 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:39 | 570.46 | 11.24 | 0.00 | 244.33 | 388.57 | 14.95 | 0.00 | 181.17 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-08:30 | 554.82 | 10.88 | 0.00 | 243.83 | 378.05 | 14.60 | 0.00 | 162.33 |
Annual Sum or Average | 4027.67 | 0.51 | 888.10 | 13.48 | 108.67 | 3714.17 | 545.58 | 16.95 | 111.33 | 3132.00 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 554.82 | 10.72 | 0.00 | 243.83 | 376.05 | 14.37 | 0.00 | 162.33 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1264.52 | 17.16 | 58.00 | 376.67 | 708.10 | 20.30 | 59.33 | 348.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2315.23 | 22.13 | 109.33 | 276.83 | 1310.50 | 22.67 | 81.83 | 237.33 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2057.17 | 19.82 | 79.17 | 266.83 | 1127.49 | 21.62 | 60.17 | 237.67 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2236.62 | 20.14 | 81.00 | 313.33 | 1201.37 | 21.12 | 56.67 | 276.83 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:09 | 2499.05 | 18.37 | 82.00 | 327.67 | 1353.89 | 19.40 | 53.00 | 297.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:40 | 2071.62 | 13.69 | 0.00 | 357.33 | 1137.83 | 17.11 | 0.00 | 320.83 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-07:10 | 2195.02 | 13.58 | 0.00 | 359.17 | 975.26 | 16.94 | 0.00 | 324.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 2029.01 | 14.14 | 3.67 | 366.83 | 948.38 | 17.24 | 0.00 | 327.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2094.90 | 16.82 | 59.00 | 350.67 | 1125.48 | 17.52 | 5.50 | 316.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1956.38 | 18.71 | 80.50 | 315.67 | 1033.37 | 19.78 | 51.67 | 282.83 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:40 | 2503.78 | 21.88 | 108.83 | 310.17 | 1067.87 | 21.06 | 53.50 | 277.00 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-09:39 | 2014.51 | 21.03 | 95.17 | 268.17 | 1109.21 | 21.74 | 66.67 | 236.17 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:30 | 2160.65 | 22.82 | 103.00 | 271.50 | 1195.27 | 23.16 | 74.00 | 226.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2175.78 | 18.29 | 801.67 | 3784.17 | 1125.37 | 19.72 | 503.00 | 3360.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1956.38 | 13.58 | 0.00 | 266.83 | 948.38 | 16.94 | 0.00 | 226.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2503.78 | 22.82 | 109.33 | 366.83 | 1353.89 | 23.16 | 81.83 | 327.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 42550292.76 | 11142.12 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15820188.31 | 10529.94 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13572752.88 | 10681.55 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13748102.89 | 5068.05 | 18-APR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 58268.81 | 100.87 | 18-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21077994.80 | 12167.68 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42550292.76 | 12167.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16341503.97 | 1701.81 | 05-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1570688.51 | 454.73 | 06-FEB-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3981116.31 | 1069.70 | 21-DEC-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21893308.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16341503.97 | 1701.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10225748.42 | 1524.95 | 05-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2774405.17 | 536.60 | 17-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 142339.56 | 179.40 | 09-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12143397.41 | 3210.37 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25285890.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12143397.41 | 3210.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22253865.13 | 2155.63 | 05-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9518535.63 | 2259.13 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 235258.83 | 117.41 | 11-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15176007.95 | 1744.34 | 20-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47183667.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22253865.13 | 2259.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.609042E+09 | 119063.55 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350759E+09 | 114056.33 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517475E+09 | 113159.59 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52089634.06 | 14741.43 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6813311.22 | 16304.69 | 15-NOV-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356574E+09 | 133562.85 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.609042E+09 | 133562.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.892601E+10 | 139703.91 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419053E+10 | 139664.81 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282691E+10 | 139501.02 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349651E+09 | 41547.31 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.550374E+10 | 139666.12 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.892601E+10 | 139703.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279479E+10 | 135835.29 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115811E+10 | 135823.88 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112711E+10 | 135787.43 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31641153.16 | 12097.70 | 16-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219829E+10 | 135703.96 | 20-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.730995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279479E+10 | 135835.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205388E+10 | 165448.35 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.964711E+09 | 165200.11 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153585E+10 | 165383.97 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144193E+10 | 165324.20 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.599638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205388E+10 | 165448.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225033E+10 | 130444.52 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.957014E+09 | 130383.73 | 06-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.742397E+09 | 130366.49 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2660324.74 | 2132.32 | 16-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114547E+10 | 130336.91 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225033E+10 | 130444.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 67030316.12 | 14564.73 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26245917.05 | 14112.27 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19178156.80 | 14003.45 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3592899.00 | 5988.17 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 792877.58 | 1136.65 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38533665.95 | 14976.84 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67030316.12 | 14976.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144142E+10 | 71491.10 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108504E+10 | 71771.19 | 06-FEB-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.634456E+09 | 71470.68 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3006217.66 | 1618.86 | 16-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883672E+09 | 71658.63 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144142E+10 | 71771.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255447E+10 | 16115.67 | 09-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138537E+10 | 16103.93 | 18-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.938687E+09 | 16111.88 | 13-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29721977.26 | 3585.53 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33747236.30 | 8456.21 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300470E+09 | 16014.23 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173816E+10 | 16061.85 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255447E+10 | 16115.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.953166E+09 | 15610.70 | 11-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.508090E+09 | 15606.52 | 18-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.438043E+09 | 15604.59 | 11-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5528400.07 | 881.23 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10844821.33 | 3887.53 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88255840.76 | 15581.60 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794735E+09 | 15596.18 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.953166E+09 | 15610.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.871295E+09 | 19717.30 | 09-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.517584E+09 | 19689.75 | 06-FEB-05:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.607464E+09 | 19707.80 | 11-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11308889.23 | 1235.63 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10808796.14 | 1647.78 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55415033.84 | 19656.38 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.693036E+09 | 19694.62 | 20-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.871295E+09 | 19717.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.823847E+09 | 16017.11 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.423826E+09 | 16002.68 | 06-FEB-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306934E+09 | 15995.04 | 11-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5983386.10 | 739.90 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53695946.11 | 15991.46 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516871E+09 | 16012.93 | 20-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.823847E+09 | 16017.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80.37 | 0.67 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 261.28 | 0.75 | 14-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79.87 | 0.67 | 07-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 261.28 | 0.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.389122E+11 | 0.292565E+11 | 132707.43 | 30-JAN-06:02 | 54684.77 | 0.27 |
February | 0.00 | 0.00 | 0.554933E+11 | 0.405615E+11 | 151496.21 | 28-FEB-05:12 | 135794.50 | 0.42 |
March | 0.00 | 0.00 | 0.694834E+11 | 0.548985E+11 | 155185.81 | 28-MAR-04:12 | 120169.68 | 0.42 |
April | 0.00 | 0.00 | 0.113392E+12 | 0.901505E+11 | 151446.33 | 01-APR-04:12 | 117278.69 | 0.69 |
May | 0.00 | 0.00 | 0.142564E+12 | 0.109169E+12 | 176689.16 | 22-MAY-05:02 | 142221.01 | 0.69 |
June | 0.00 | 0.00 | 0.154722E+12 | 0.121502E+12 | 171250.04 | 07-JUN-04:12 | 136429.65 | 0.80 |
July | 0.00 | 0.00 | 0.168254E+12 | 0.130387E+12 | 164096.97 | 24-JUL-05:03 | 143586.24 | 0.84 |
August | 0.00 | 0.00 | 0.185142E+12 | 0.145190E+12 | 176546.98 | 07-AUG-05:02 | 147426.02 | 0.88 |
September | 0.00 | 0.00 | 0.143539E+12 | 0.103867E+12 | 194757.12 | 06-SEP-03:02 | 142409.50 | 0.70 |
October | 0.00 | 0.00 | 0.134782E+12 | 0.105470E+12 | 178077.97 | 21-OCT-04:11 | 134166.47 | 0.66 |
November | 0.00 | 0.00 | 0.847191E+11 | 0.682199E+11 | 173699.87 | 08-NOV-05:11 | 138388.80 | 0.52 |
December | 0.00 | 0.00 | 0.633503E+11 | 0.498403E+11 | 141176.64 | 11-DEC-06:03 | 128658.57 | 0.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.135435E+13 | 0.104851E+13 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.389122E+11 | 0.292565E+11 | 132707.43 | 54684.77 | 0.27 | |
Maximum of Months | 0.00 | 0.00 | 0.185142E+12 | 0.145190E+12 | 194757.12 | 147426.02 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.308391E+12 | 0.225246E+12 | 1086610.00 | 19-JAN-06:03 | 826674.22 | 0.26 |
February | 0.00 | 0.00 | 0.436165E+12 | 0.304722E+12 | 1300453.40 | 27-FEB-06:02 | 1179700.80 | 0.40 |
March | 0.00 | 0.00 | 0.518457E+12 | 0.387582E+12 | 1585560.07 | 07-MAR-06:02 | 1157412.51 | 0.38 |
April | 0.00 | 0.00 | 0.818957E+12 | 0.609615E+12 | 1571671.91 | 29-APR-04:11 | 1243013.26 | 0.52 |
May | 0.00 | 0.00 | 0.129612E+13 | 0.950414E+12 | 2012289.33 | 24-MAY-05:02 | 1266858.69 | 0.65 |
June | 0.00 | 0.00 | 0.132443E+13 | 0.983251E+12 | 1669297.10 | 09-JUN-04:12 | 1260871.41 | 0.68 |
July | 0.00 | 0.00 | 0.137971E+13 | 0.980776E+12 | 1632799.65 | 29-JUL-05:02 | 1249838.02 | 0.67 |
August | 0.00 | 0.00 | 0.142465E+13 | 0.101288E+13 | 1830270.31 | 16-AUG-04:12 | 1149573.81 | 0.67 |
September | 0.00 | 0.00 | 0.128209E+13 | 0.871973E+12 | 2158839.05 | 05-SEP-04:11 | 1102728.41 | 0.65 |
October | 0.00 | 0.00 | 0.112227E+13 | 0.824566E+12 | 1825929.02 | 21-OCT-04:11 | 1098504.77 | 0.56 |
November | 0.00 | 0.00 | 0.643854E+12 | 0.495761E+12 | 1556379.23 | 02-NOV-05:02 | 1218098.88 | 0.46 |
December | 0.00 | 0.00 | 0.450324E+12 | 0.329179E+12 | 1323950.75 | 16-DEC-06:03 | 1003734.96 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.110054E+14 | 0.797597E+13 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 0.308391E+12 | 0.225246E+12 | 1086610.00 | 826674.22 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.142465E+13 | 0.101288E+13 | 2158839.05 | 1266858.69 | 0.68 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.303282E+11 | 0.215849E+11 | 123310.99 | 19-JAN-15:00 | 81786.28 | 0.26 |
February | 0.00 | 0.00 | 0.440308E+11 | 0.305756E+11 | 122032.23 | 27-FEB-16:00 | 89455.23 | 0.40 |
March | 0.00 | 0.00 | 0.534965E+11 | 0.396660E+11 | 144840.10 | 07-MAR-06:02 | 97073.18 | 0.37 |
April | 0.00 | 0.00 | 0.866360E+11 | 0.652177E+11 | 159578.45 | 26-APR-05:02 | 119870.28 | 0.52 |
May | 0.00 | 0.00 | 0.143674E+12 | 0.107950E+12 | 234436.44 | 24-MAY-05:02 | 140492.74 | 0.65 |
June | 0.00 | 0.00 | 0.149056E+12 | 0.113927E+12 | 182076.64 | 19-JUN-05:02 | 136347.45 | 0.69 |
July | 0.00 | 0.00 | 0.154574E+12 | 0.112965E+12 | 201930.60 | 27-JUL-03:02 | 143823.48 | 0.69 |
August | 0.00 | 0.00 | 0.157917E+12 | 0.115222E+12 | 212218.32 | 23-AUG-03:02 | 143992.28 | 0.68 |
September | 0.00 | 0.00 | 0.138163E+12 | 0.957260E+11 | 240696.43 | 05-SEP-04:11 | 119511.59 | 0.65 |
October | 0.00 | 0.00 | 0.120021E+12 | 0.893688E+11 | 206501.13 | 06-OCT-03:02 | 147080.15 | 0.56 |
November | 0.00 | 0.00 | 0.626074E+11 | 0.478871E+11 | 166848.53 | 01-NOV-05:02 | 120202.71 | 0.45 |
December | 0.00 | 0.00 | 0.433980E+11 | 0.314509E+11 | 134246.73 | 15-DEC-06:03 | 94824.36 | 0.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.118390E+13 | 0.871540E+12 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 0.303282E+11 | 0.215849E+11 | 122032.23 | 81786.28 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.157917E+12 | 0.115222E+12 | 240696.43 | 147080.15 | 0.69 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.203163E+11 | 0.158448E+11 | 120528.60 | 01-JAN-16:12 | 96396.40 | 0.18 |
February | 0.00 | 0.00 | 0.237956E+11 | 0.193774E+11 | 117803.38 | 03-FEB-05:12 | 44151.29 | 0.28 |
March | 0.00 | 0.00 | 0.325190E+11 | 0.276503E+11 | 140960.90 | 07-MAR-05:11 | 84096.90 | 0.26 |
April | 0.00 | 0.00 | 0.512819E+11 | 0.446918E+11 | 138277.68 | 26-APR-04:12 | 50604.74 | 0.44 |
May | 0.00 | 0.00 | 0.953758E+11 | 0.731138E+11 | 164826.03 | 29-MAY-11:20 | 82262.49 | 0.57 |
June | 0.00 | 0.00 | 0.100442E+12 | 0.746899E+11 | 162971.22 | 19-JUN-03:02 | 80763.06 | 0.59 |
July | 0.00 | 0.00 | 0.109203E+12 | 0.760260E+11 | 167486.31 | 03-JUL-03:02 | 79318.49 | 0.56 |
August | 0.00 | 0.00 | 0.121463E+12 | 0.871028E+11 | 164242.89 | 06-AUG-17:20 | 82522.41 | 0.62 |
September | 0.00 | 0.00 | 0.103109E+12 | 0.741632E+11 | 160914.75 | 24-SEP-16:01 | 82930.90 | 0.60 |
October | 0.00 | 0.00 | 0.887705E+11 | 0.674879E+11 | 170718.78 | 15-OCT-15:38 | 79958.62 | 0.51 |
November | 0.00 | 0.00 | 0.489548E+11 | 0.403978E+11 | 142478.22 | 01-NOV-04:15 | 84860.74 | 0.38 |
December | 0.00 | 0.00 | 0.317500E+11 | 0.256639E+11 | 141806.98 | 15-DEC-05:12 | 84158.09 | 0.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.826981E+12 | 0.626210E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.203163E+11 | 0.158448E+11 | 117803.38 | 44151.29 | 0.18 | |
Maximum of Months | 0.00 | 0.00 | 0.121463E+12 | 0.871028E+11 | 170718.78 | 96396.40 | 0.62 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.382904E+11 | 0.341162E+11 | 206710.47 | 31-JAN-12:50 | 125267.76 | 0.00 |
February | 0.00 | 0.00 | 0.147440E+12 | 0.137605E+12 | 310688.50 | 24-FEB-10:30 | 215849.15 | 0.00 |
March | 0.00 | 0.00 | 0.360646E+12 | 0.334091E+12 | 393382.55 | 31-MAR-24:00 | 393382.55 | 0.00 |
April | 0.00 | 0.00 | 0.853578E+12 | 0.778393E+12 | 428399.79 | 05-APR-07:15 | 396349.65 | 0.00 |
May | 0.00 | 0.00 | 0.347644E+12 | 0.334917E+12 | 212295.34 | 31-MAY-23:10 | 209953.86 | 0.00 |
June | 0.00 | 0.00 | 0.574680E+12 | 0.560727E+12 | 302399.82 | 30-JUN-23:03 | 301477.89 | 0.00 |
July | 0.00 | 0.00 | 0.840727E+12 | 0.825771E+12 | 394456.57 | 31-JUL-23:55 | 394456.57 | 0.00 |
August | 0.00 | 0.00 | 0.107906E+13 | 0.106521E+13 | 423562.46 | 07-AUG-14:00 | 402875.99 | 0.00 |
September | 0.00 | 0.00 | 0.340724E+12 | 0.327114E+12 | 212878.39 | 30-SEP-24:00 | 211605.14 | 0.00 |
October | 0.00 | 0.00 | 0.485368E+12 | 0.470419E+12 | 303514.43 | 31-OCT-24:00 | 303514.43 | 0.00 |
November | 0.00 | 0.00 | 0.417925E+12 | 0.381085E+12 | 358650.74 | 28-NOV-09:00 | 308171.33 | 0.00 |
December | 0.00 | 0.00 | 0.499357E+12 | 0.447798E+12 | 431788.40 | 28-DEC-09:50 | 397906.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.598544E+13 | 0.569724E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.382904E+11 | 0.341162E+11 | 206710.47 | 125267.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107906E+13 | 0.106521E+13 | 431788.40 | 402875.99 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.500004E+10 | 0.489472E+10 | 2718.81 | 19-JAN-17:00 | 2362.07 | 0.00 |
February | 0.00 | 0.00 | 0.945244E+10 | 0.926618E+10 | 4714.93 | 26-FEB-17:54 | 4714.93 | 0.00 |
March | 0.00 | 0.00 | 0.156588E+11 | 0.154535E+11 | 7680.64 | 31-MAR-24:00 | 7680.64 | 0.00 |
April | 0.00 | 0.00 | 0.204232E+11 | 0.201307E+11 | 8597.65 | 28-APR-17:20 | 8064.96 | 0.00 |
May | 0.00 | 0.00 | 0.642048E+10 | 0.591644E+10 | 4057.69 | 31-MAY-23:10 | 3909.74 | 0.00 |
June | 0.00 | 0.00 | 0.112072E+11 | 0.106254E+11 | 5863.84 | 30-JUN-23:03 | 5814.96 | 0.00 |
July | 0.00 | 0.00 | 0.166897E+11 | 0.160371E+11 | 7719.89 | 31-JUL-24:00 | 7718.29 | 0.00 |
August | 0.00 | 0.00 | 0.217761E+11 | 0.211186E+11 | 8784.00 | 07-AUG-13:40 | 8044.48 | 0.00 |
September | 0.00 | 0.00 | 0.625484E+10 | 0.571383E+10 | 4019.99 | 30-SEP-24:00 | 3989.00 | 0.00 |
October | 0.00 | 0.00 | 0.113695E+11 | 0.109175E+11 | 5854.39 | 31-OCT-24:00 | 5844.30 | 0.00 |
November | 0.00 | 0.00 | 0.154616E+11 | 0.152084E+11 | 6709.07 | 07-NOV-16:40 | 6174.56 | 0.00 |
December | 0.00 | 0.00 | 0.207200E+11 | 0.205395E+11 | 8667.17 | 14-DEC-17:00 | 8198.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160434E+12 | 0.155822E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.500004E+10 | 0.489472E+10 | 2718.81 | 2362.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217761E+11 | 0.211186E+11 | 8784.00 | 8198.33 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.351623E+11 | 0.341466E+11 | 25419.11 | 19-JAN-17:00 | 21866.79 | 0.00 |
February | 0.00 | 0.00 | 0.804711E+11 | 0.786294E+11 | 44065.51 | 27-FEB-17:00 | 40554.82 | 0.00 |
March | 0.00 | 0.00 | 0.141251E+12 | 0.139210E+12 | 71809.06 | 31-MAR-24:00 | 71809.06 | 0.00 |
April | 0.00 | 0.00 | 0.192445E+12 | 0.189521E+12 | 82229.22 | 28-APR-17:20 | 76953.75 | 0.00 |
May | 0.00 | 0.00 | 0.593120E+11 | 0.543394E+11 | 38224.32 | 31-MAY-23:10 | 36595.73 | 0.00 |
June | 0.00 | 0.00 | 0.106174E+12 | 0.100389E+12 | 56528.30 | 30-JUN-23:55 | 56356.65 | 0.00 |
July | 0.00 | 0.00 | 0.158805E+12 | 0.152298E+12 | 73901.90 | 31-JUL-24:00 | 73873.71 | 0.00 |
August | 0.00 | 0.00 | 0.206729E+12 | 0.200154E+12 | 83611.52 | 14-AUG-16:00 | 76992.10 | 0.00 |
September | 0.00 | 0.00 | 0.569287E+11 | 0.516073E+11 | 37263.99 | 30-SEP-24:00 | 36936.72 | 0.00 |
October | 0.00 | 0.00 | 0.105621E+12 | 0.101134E+12 | 54238.24 | 31-OCT-24:00 | 54113.87 | 0.00 |
November | 0.00 | 0.00 | 0.140840E+12 | 0.138326E+12 | 64109.61 | 07-NOV-16:50 | 58799.48 | 0.00 |
December | 0.00 | 0.00 | 0.187339E+12 | 0.185534E+12 | 82357.51 | 14-DEC-17:00 | 77679.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147108E+13 | 0.142529E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.351623E+11 | 0.341466E+11 | 25419.11 | 21866.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206729E+12 | 0.200154E+12 | 83611.52 | 77679.41 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.246367E+10 | 0.236381E+10 | 2623.37 | 19-JAN-17:00 | 2267.31 | 0.00 |
February | 0.00 | 0.00 | 0.726646E+10 | 0.708331E+10 | 4480.53 | 27-FEB-17:00 | 4128.91 | 0.00 |
March | 0.00 | 0.00 | 0.135633E+11 | 0.133598E+11 | 7094.97 | 31-MAR-24:00 | 7094.97 | 0.00 |
April | 0.00 | 0.00 | 0.191377E+11 | 0.188458E+11 | 8335.05 | 28-APR-17:20 | 7803.90 | 0.00 |
May | 0.00 | 0.00 | 0.610987E+10 | 0.560978E+10 | 3810.97 | 31-MAY-23:10 | 3649.70 | 0.00 |
June | 0.00 | 0.00 | 0.108075E+11 | 0.102280E+11 | 5698.59 | 30-JUN-23:55 | 5681.40 | 0.00 |
July | 0.00 | 0.00 | 0.160785E+11 | 0.154276E+11 | 7391.30 | 31-JUL-24:00 | 7388.31 | 0.00 |
August | 0.00 | 0.00 | 0.208483E+11 | 0.201905E+11 | 8486.67 | 09-AUG-17:00 | 7760.07 | 0.00 |
September | 0.00 | 0.00 | 0.582362E+10 | 0.528939E+10 | 3761.03 | 30-SEP-24:00 | 3729.16 | 0.00 |
October | 0.00 | 0.00 | 0.105314E+11 | 0.100826E+11 | 5365.55 | 31-OCT-24:00 | 5352.61 | 0.00 |
November | 0.00 | 0.00 | 0.135610E+11 | 0.133106E+11 | 6470.34 | 07-NOV-16:40 | 5937.40 | 0.00 |
December | 0.00 | 0.00 | 0.178591E+11 | 0.176792E+11 | 8297.11 | 14-DEC-17:00 | 7829.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144050E+12 | 0.139471E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.246367E+10 | 0.236381E+10 | 2623.37 | 2267.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208483E+11 | 0.201905E+11 | 8486.67 | 7829.23 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6.44 | 25927.45 | 03-JAN-06:02 | 8572.41 | 1164287.24 | 09-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4749.09 | 1053750.78 | 17-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3597.57 | 1204389.09 | 11-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 84.03 | 77297.97 | 18-APR-14:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13.99 | 16441.45 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 316.13 | 211962.11 | 16-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5674.67 | 1213618.47 | 20-DEC-05:11 |
Annual Sum or Average | 0.55 | 1913.96 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 6.44 | 25927.45 | 8572.41 | 1213618.47 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 155415.61 | 1647444.04 | 19-JAN-11:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 246911.76 | 2149587.64 | 27-FEB-16:13 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 267252.40 | 1739370.42 | 29-MAR-15:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 441450.73 | 2358139.95 | 27-APR-15:43 | 0.00 | 0.00 | 01-APR-00:10 |
May | 689550.16 | 2375306.43 | 10-MAY-15:53 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 729226.94 | 2366601.31 | 12-JUN-15:13 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 732255.39 | 1898447.88 | 05-JUL-12:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 765211.80 | 1890540.71 | 22-AUG-12:05 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 701565.61 | 2259829.37 | 22-SEP-14:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 585483.75 | 2155621.31 | 18-OCT-15:23 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 341124.03 | 2156864.77 | 06-NOV-10:23 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 234147.69 | 2282359.68 | 15-DEC-13:53 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 492118.82 | 0.00 | ||||
Minimum of Months | 155415.61 | 1647444.04 | 0.00 | 0.00 | ||
Maximum of Months | 765211.80 | 2375306.43 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 156058.93 | 2940493.59 | 19-JAN-16:40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 252609.81 | 2891095.84 | 27-FEB-16:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 268570.88 | 2993786.35 | 07-MAR-06:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 447767.42 | 2872550.23 | 29-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 721235.73 | 3347722.94 | 22-MAY-03:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 751672.02 | 3070520.94 | 08-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 738940.52 | 2935279.82 | 28-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 774729.78 | 3186751.68 | 26-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 721580.27 | 3466056.12 | 05-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 603218.57 | 3190567.08 | 21-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 347198.99 | 3071952.52 | 01-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 239924.81 | 2720740.29 | 14-DEC-13:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 503295.05 | 0.00 | ||||
Minimum of Months | 156058.93 | 2720740.29 | 0.00 | 0.00 | ||
Maximum of Months | 774729.78 | 3466056.12 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 88504.30 | 741087.86 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 222623.58 | 1007467.46 | 02-FEB-13:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 426437.92 | 1301755.61 | 26-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 927026.05 | 1713091.31 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 721789.62 | 1081890.85 | 18-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 975042.31 | 1393306.28 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1210588.40 | 1696436.49 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1391459.26 | 1862941.62 | 30-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 689728.83 | 1245663.26 | 09-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 736031.95 | 1345475.24 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 516883.38 | 1345271.70 | 02-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 525932.07 | 1534746.33 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 705799.80 | 0.00 | ||||
Minimum of Months | 88504.30 | 741087.86 | 0.00 | 0.00 | ||
Maximum of Months | 1391459.26 | 1862941.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 12860.29 | 42455.45 | 20-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12838.17 | 42389.67 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13080.93 | 41428.83 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11678.42 | 39124.16 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 11278.54 | 36812.07 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10889.39 | 34304.54 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9856.44 | 32638.70 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 10755.60 | 33324.48 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 10627.69 | 35276.17 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11283.71 | 37983.60 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12147.09 | 40383.69 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12315.54 | 41971.21 | 28-DEC-12:15 |
Annual Sum or Average | 0.00 | 11627.70 | ||||
Minimum of Months | 0.00 | 0.00 | 9856.44 | 32638.70 | ||
Maximum of Months | 0.00 | 0.00 | 13080.93 | 42455.45 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 216004.53 | 3685892.62 | 31-JAN-15:05 | 1514.07 | 137258.57 | 09-JAN-18:30 |
February | 338884.50 | 3568314.30 | 24-FEB-13:05 | 1034.47 | 153597.34 | 17-FEB-12:50 |
March | 403296.82 | 4251035.70 | 28-MAR-12:05 | 1742.95 | 126159.02 | 09-MAR-08:00 |
April | 726316.42 | 5047230.40 | 28-APR-16:00 | 884.30 | 103820.54 | 03-APR-06:20 |
May | 1706898.91 | 5968741.97 | 26-MAY-10:05 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1996074.53 | 6050985.62 | 23-JUN-10:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2356342.13 | 6428734.21 | 05-JUL-12:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2289078.55 | 6198678.52 | 22-AUG-12:05 | 3.03 | 13530.86 | 20-AUG-04:50 |
September | 1891687.94 | 5944327.10 | 01-SEP-12:05 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 1426420.45 | 5990228.93 | 06-OCT-14:05 | 293.44 | 108377.47 | 28-OCT-09:00 |
November | 605448.27 | 5427698.26 | 01-NOV-14:05 | 766.81 | 130170.93 | 15-NOV-10:30 |
December | 384964.95 | 4945556.40 | 12-DEC-14:05 | 1858.03 | 172934.60 | 26-DEC-09:10 |
Annual Sum or Average | 1200952.81 | 674.67 | ||||
Minimum of Months | 216004.53 | 3568314.30 | 0.00 | 0.00 | ||
Maximum of Months | 2356342.13 | 6428734.21 | 1858.03 | 172934.60 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131757E+11 | 0.80 | 8497.92 | 01-JAN-00:13 | 1.37 |
February | 0.113966E+11 | 0.77 | 8497.92 | 01-FEB-05:12 | 1.38 |
March | 0.132440E+11 | 0.80 | 8497.92 | 01-MAR-05:12 | 1.38 |
April | 0.121248E+11 | 0.76 | 8497.92 | 01-APR-04:12 | 1.38 |
May | 0.132025E+11 | 0.80 | 8497.92 | 01-MAY-03:02 | 1.38 |
June | 0.130953E+11 | 0.82 | 8497.92 | 01-JUN-04:12 | 1.38 |
July | 0.129134E+11 | 0.78 | 8497.92 | 01-JUL-03:55 | 1.37 |
August | 0.145093E+11 | 0.88 | 8497.92 | 01-AUG-03:03 | 1.38 |
September | 0.135144E+11 | 0.84 | 8497.92 | 01-SEP-04:12 | 1.38 |
October | 0.138340E+11 | 0.84 | 8497.92 | 01-OCT-16:02 | 1.38 |
November | 0.132427E+11 | 0.83 | 8497.92 | 01-NOV-04:15 | 1.38 |
December | 0.133320E+11 | 0.81 | 8497.92 | 01-DEC-05:12 | 1.38 |
Annual Sum or Average | 0.157585E+12 | 0.81 | |||
Minimum of Months | 0.113966E+11 | 0.76 | 8497.92 | 1.37 | |
Maximum of Months | 0.145093E+11 | 0.88 | 8497.92 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345896E+10 | 0.32 | 17688.74 | 02-JAN-06:03 | 1.72 |
February | 0.363917E+10 | 0.35 | 18272.88 | 27-FEB-05:11 | 1.76 |
March | 0.454453E+10 | 0.38 | 17152.25 | 27-MAR-05:03 | 1.69 |
April | 0.548427E+10 | 0.46 | 16132.23 | 27-APR-05:02 | 1.62 |
May | 0.553935E+10 | 0.43 | 18272.88 | 01-MAY-05:02 | 1.76 |
June | 0.615410E+10 | 0.50 | 18272.88 | 01-JUN-14:30 | 1.75 |
July | 0.665993E+10 | 0.52 | 18272.88 | 01-JUL-05:02 | 1.76 |
August | 0.794075E+10 | 0.58 | 18272.88 | 01-AUG-05:02 | 1.76 |
September | 0.529625E+10 | 0.43 | 18272.88 | 02-SEP-05:02 | 1.76 |
October | 0.611159E+10 | 0.46 | 18272.88 | 02-OCT-04:11 | 1.76 |
November | 0.512788E+10 | 0.41 | 18272.88 | 01-NOV-05:02 | 1.76 |
December | 0.473504E+10 | 0.39 | 14905.21 | 11-DEC-06:03 | 1.54 |
Annual Sum or Average | 0.646918E+11 | 0.44 | |||
Minimum of Months | 0.345896E+10 | 0.32 | 14905.21 | 1.54 | |
Maximum of Months | 0.794075E+10 | 0.58 | 18272.88 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.256211E+11 | 0.29 | 122260.21 | 21-JAN-06:02 | 1.44 |
February | 0.250590E+11 | 0.30 | 150395.35 | 27-FEB-06:02 | 1.63 |
March | 0.294774E+11 | 0.32 | 168844.43 | 07-MAR-06:02 | 1.76 |
April | 0.338811E+11 | 0.33 | 168844.43 | 15-APR-05:02 | 1.76 |
May | 0.476289E+11 | 0.40 | 168844.43 | 03-MAY-12:30 | 1.76 |
June | 0.489041E+11 | 0.42 | 168844.43 | 03-JUN-05:02 | 1.76 |
July | 0.477314E+11 | 0.41 | 168844.43 | 07-JUL-05:02 | 1.76 |
August | 0.510673E+11 | 0.42 | 168844.43 | 01-AUG-05:02 | 1.76 |
September | 0.432731E+11 | 0.39 | 168844.43 | 01-SEP-04:12 | 1.76 |
October | 0.458851E+11 | 0.38 | 168844.43 | 03-OCT-05:03 | 1.76 |
November | 0.324815E+11 | 0.33 | 168844.43 | 01-NOV-05:02 | 1.76 |
December | 0.279184E+11 | 0.30 | 111332.26 | 11-DEC-06:03 | 1.35 |
Annual Sum or Average | 0.458928E+12 | 0.36 | |||
Minimum of Months | 0.250590E+11 | 0.29 | 111332.26 | 1.35 | |
Maximum of Months | 0.510673E+11 | 0.42 | 168844.43 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.246492E+10 | 0.29 | 8973.13 | 02-JAN-06:03 | 1.11 |
February | 0.247665E+10 | 0.30 | 8898.74 | 27-FEB-06:02 | 1.10 |
March | 0.286172E+10 | 0.31 | 10716.99 | 27-MAR-05:03 | 1.23 |
April | 0.341813E+10 | 0.32 | 14919.09 | 26-APR-05:02 | 1.52 |
May | 0.527734E+10 | 0.40 | 18774.76 | 02-MAY-13:00 | 1.76 |
June | 0.554736E+10 | 0.43 | 18774.76 | 08-JUN-14:30 | 1.75 |
July | 0.535312E+10 | 0.42 | 18774.76 | 05-JUL-05:02 | 1.76 |
August | 0.564949E+10 | 0.43 | 18774.76 | 03-AUG-03:02 | 1.76 |
September | 0.453244E+10 | 0.39 | 18774.76 | 01-SEP-04:12 | 1.76 |
October | 0.468393E+10 | 0.37 | 18774.76 | 06-OCT-05:02 | 1.76 |
November | 0.295175E+10 | 0.31 | 17251.58 | 03-NOV-05:02 | 1.67 |
December | 0.262336E+10 | 0.29 | 8428.01 | 15-DEC-06:03 | 1.07 |
Annual Sum or Average | 0.478402E+11 | 0.36 | |||
Minimum of Months | 0.246492E+10 | 0.29 | 8428.01 | 1.07 | |
Maximum of Months | 0.564949E+10 | 0.43 | 18774.76 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.944143E+11 | 1.35 | 35250.28 | 01-JAN-00:05 | 1.34 |
February | 0.852775E+11 | 1.35 | 35250.28 | 01-FEB-00:10 | 1.35 |
March | 0.944143E+11 | 1.35 | 35250.28 | 01-MAR-00:10 | 1.35 |
April | 0.913687E+11 | 1.35 | 35250.28 | 01-APR-00:10 | 1.35 |
May | 0.944143E+11 | 1.35 | 35250.28 | 01-MAY-00:03 | 1.35 |
June | 0.913687E+11 | 1.35 | 35250.28 | 01-JUN-00:10 | 1.35 |
July | 0.944143E+11 | 1.35 | 35250.28 | 01-JUL-00:10 | 1.35 |
August | 0.944143E+11 | 1.35 | 35250.28 | 01-AUG-00:10 | 1.35 |
September | 0.913687E+11 | 1.35 | 35250.28 | 01-SEP-00:10 | 1.35 |
October | 0.944143E+11 | 1.35 | 35250.28 | 01-OCT-00:10 | 1.35 |
November | 0.913687E+11 | 1.35 | 35250.28 | 01-NOV-00:10 | 1.35 |
December | 0.944143E+11 | 1.35 | 35250.28 | 01-DEC-00:20 | 1.35 |
Annual Sum or Average | 0.111165E+13 | 1.35 | |||
Minimum of Months | 0.852775E+11 | 1.35 | 35250.28 | 1.34 | |
Maximum of Months | 0.944143E+11 | 1.35 | 35250.28 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138306E+10 | 0.91 | 516.38 | 01-JAN-00:05 | 0.91 |
February | 0.124922E+10 | 0.91 | 516.38 | 01-FEB-00:10 | 0.91 |
March | 0.138306E+10 | 0.91 | 516.38 | 01-MAR-00:10 | 0.91 |
April | 0.133845E+10 | 0.91 | 516.38 | 01-APR-00:10 | 0.91 |
May | 0.138306E+10 | 0.91 | 516.38 | 01-MAY-00:03 | 0.91 |
June | 0.133845E+10 | 0.91 | 516.38 | 01-JUN-00:10 | 0.91 |
July | 0.138306E+10 | 0.91 | 516.38 | 01-JUL-00:10 | 0.91 |
August | 0.138306E+10 | 0.91 | 516.38 | 01-AUG-00:10 | 0.91 |
September | 0.133845E+10 | 0.91 | 516.38 | 01-SEP-00:10 | 0.91 |
October | 0.138306E+10 | 0.91 | 516.38 | 01-OCT-00:10 | 0.91 |
November | 0.133845E+10 | 0.91 | 516.38 | 01-NOV-00:10 | 0.91 |
December | 0.138306E+10 | 0.91 | 516.38 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.162844E+11 | 0.91 | |||
Minimum of Months | 0.124922E+10 | 0.91 | 516.38 | 0.91 | |
Maximum of Months | 0.138306E+10 | 0.91 | 516.38 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131860E+11 | 0.91 | 4923.11 | 01-JAN-00:10 | 0.91 |
February | 0.119100E+11 | 0.91 | 4923.11 | 01-FEB-00:10 | 0.91 |
March | 0.131860E+11 | 0.91 | 4923.11 | 01-MAR-00:10 | 0.91 |
April | 0.127607E+11 | 0.91 | 4923.11 | 01-APR-00:20 | 0.91 |
May | 0.131860E+11 | 0.91 | 4923.11 | 01-MAY-00:03 | 0.91 |
June | 0.127607E+11 | 0.91 | 4923.11 | 01-JUN-00:10 | 0.91 |
July | 0.131860E+11 | 0.91 | 4923.11 | 01-JUL-00:10 | 0.91 |
August | 0.131860E+11 | 0.91 | 4923.11 | 01-AUG-00:10 | 0.91 |
September | 0.127607E+11 | 0.91 | 4923.11 | 01-SEP-00:10 | 0.91 |
October | 0.131860E+11 | 0.91 | 4923.11 | 01-OCT-00:10 | 0.91 |
November | 0.127607E+11 | 0.91 | 4923.11 | 01-NOV-00:10 | 0.91 |
December | 0.131860E+11 | 0.91 | 4923.11 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.155255E+12 | 0.91 | |||
Minimum of Months | 0.119100E+11 | 0.91 | 4923.11 | 0.91 | |
Maximum of Months | 0.131860E+11 | 0.91 | 4923.11 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134485E+10 | 0.91 | 502.11 | 01-JAN-00:05 | 0.91 |
February | 0.121470E+10 | 0.91 | 502.11 | 01-FEB-00:10 | 0.91 |
March | 0.134485E+10 | 0.91 | 502.11 | 01-MAR-00:10 | 0.91 |
April | 0.130146E+10 | 0.91 | 502.11 | 01-APR-00:10 | 0.91 |
May | 0.134485E+10 | 0.91 | 502.11 | 01-MAY-00:03 | 0.91 |
June | 0.130146E+10 | 0.91 | 502.11 | 01-JUN-00:10 | 0.91 |
July | 0.134485E+10 | 0.91 | 502.11 | 01-JUL-00:10 | 0.91 |
August | 0.134485E+10 | 0.91 | 502.11 | 01-AUG-00:10 | 0.91 |
September | 0.130146E+10 | 0.91 | 502.11 | 01-SEP-00:10 | 0.91 |
October | 0.134485E+10 | 0.91 | 502.11 | 01-OCT-00:10 | 0.91 |
November | 0.130146E+10 | 0.91 | 502.11 | 01-NOV-00:10 | 0.91 |
December | 0.134485E+10 | 0.91 | 502.11 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.158345E+11 | 0.91 | |||
Minimum of Months | 0.121470E+10 | 0.91 | 502.11 | 0.91 | |
Maximum of Months | 0.134485E+10 | 0.91 | 502.11 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.195199E+09 | 0.177436E+09 | 6559.61 | 09-JAN-06:02 | 5962.68 | 5962.68 | 38.05 | 12.69 |
February | 0.100646E+09 | 91486907.96 | 6556.47 | 06-FEB-06:02 | 5959.83 | 5959.83 | 44.51 | 12.64 |
March | 75734217.24 | 68842403.47 | 6554.23 | 11-MAR-06:02 | 5957.80 | 5957.80 | 37.25 | 12.67 |
April | 1774969.12 | 1613446.93 | 624.88 | 18-APR-14:20 | 568.01 | 568.01 | 32.08 | 0.66 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 39.42 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 39.42 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 39.42 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 39.42 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 39.42 | 0.00 |
October | 398396.11 | 362142.06 | 185.20 | 28-OCT-05:03 | 168.35 | 168.35 | 39.46 | 0.19 |
November | 6377733.06 | 5797359.35 | 1499.87 | 16-NOV-06:02 | 1363.38 | 1363.38 | 29.64 | 1.67 |
December | 0.125685E+09 | 0.114248E+09 | 6564.39 | 21-DEC-06:01 | 5967.03 | 5967.03 | 41.84 | 12.70 |
Annual Sum or Average | 0.505815E+09 | 0.459786E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.64 | 0.00 | |
Maximum of Months | 0.195199E+09 | 0.177436E+09 | 6564.39 | 5967.03 | 5967.03 | 44.51 | 12.70 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.332919E+09 | 0.302624E+09 | 12211.70 | 19-JAN-16:40 | 11100.43 | 11100.43 | 11.51 | 76.25 |
February | 0.645774E+09 | 0.587009E+09 | 12456.02 | 27-FEB-16:50 | 11322.52 | 11322.52 | 10.98 | 76.85 |
March | 0.643381E+09 | 0.584833E+09 | 12530.71 | 07-MAR-06:04 | 11390.41 | 11390.41 | 10.89 | 77.05 |
April | 0.117683E+10 | 0.106974E+10 | 12030.88 | 25-APR-14:00 | 10936.07 | 10936.07 | 12.34 | 75.80 |
May | 0.265781E+10 | 0.241595E+10 | 12530.71 | 03-MAY-04:13 | 11390.41 | 11390.41 | 10.54 | 77.05 |
June | 0.254924E+10 | 0.231726E+10 | 12530.71 | 03-JUN-05:02 | 11390.41 | 11390.41 | 9.37 | 77.05 |
July | 0.231362E+10 | 0.210308E+10 | 12530.71 | 24-JUL-14:30 | 11390.41 | 11390.41 | 12.50 | 77.05 |
August | 0.254880E+10 | 0.231686E+10 | 12530.71 | 01-AUG-05:02 | 11390.41 | 11390.41 | 9.38 | 77.05 |
September | 0.237870E+10 | 0.216224E+10 | 12530.71 | 06-SEP-05:02 | 11390.41 | 11390.41 | 9.46 | 77.05 |
October | 0.207977E+10 | 0.189051E+10 | 12530.71 | 06-OCT-05:02 | 11390.41 | 11390.41 | 9.37 | 77.05 |
November | 0.916653E+09 | 0.833237E+09 | 12530.71 | 01-NOV-05:02 | 11390.41 | 11390.41 | 9.42 | 77.05 |
December | 0.670206E+09 | 0.609217E+09 | 12262.47 | 14-DEC-13:30 | 11146.58 | 11146.58 | 11.56 | 76.37 |
Annual Sum or Average | 0.189137E+11 | 0.171925E+11 | ||||||
Minimum of Months | 0.332919E+09 | 0.302624E+09 | 12030.88 | 10936.07 | 10936.07 | 9.37 | 75.80 | |
Maximum of Months | 0.265781E+10 | 0.241595E+10 | 12530.71 | 11390.41 | 11390.41 | 12.50 | 77.05 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.443677E+10 | 0.403302E+10 | 4312.27 | 01-JAN-04:03 | 3919.86 | 3919.86 | 6.93 | 38.53 |
February | 0.506364E+10 | 0.460285E+10 | 4312.27 | 01-FEB-05:12 | 3919.86 | 3919.86 | 9.50 | 38.53 |
March | 0.636315E+10 | 0.578410E+10 | 4312.27 | 01-MAR-05:12 | 3919.86 | 3919.86 | 10.14 | 38.53 |
April | 0.853209E+10 | 0.775567E+10 | 4312.27 | 01-APR-04:12 | 3919.86 | 3919.86 | 9.64 | 38.53 |
May | 0.839233E+10 | 0.762863E+10 | 4312.27 | 01-MAY-00:10 | 3919.86 | 3919.86 | 6.95 | 38.53 |
June | 0.926608E+10 | 0.842287E+10 | 4312.27 | 01-JUN-04:12 | 3919.86 | 3919.86 | 13.03 | 38.53 |
July | 0.102263E+11 | 0.929567E+10 | 4312.27 | 01-JUL-00:10 | 3919.86 | 3919.86 | 6.97 | 38.53 |
August | 0.105464E+11 | 0.958671E+10 | 4312.27 | 01-AUG-00:10 | 3919.86 | 3919.86 | 6.98 | 38.53 |
September | 0.830242E+10 | 0.754690E+10 | 4312.27 | 01-SEP-00:10 | 3919.86 | 3919.86 | 6.96 | 38.53 |
October | 0.853175E+10 | 0.775536E+10 | 4312.27 | 01-OCT-07:30 | 3919.86 | 3919.86 | 8.23 | 38.53 |
November | 0.700128E+10 | 0.636416E+10 | 4312.27 | 01-NOV-03:43 | 3919.86 | 3919.86 | 8.70 | 38.53 |
December | 0.583972E+10 | 0.530831E+10 | 4312.27 | 01-DEC-05:12 | 3919.86 | 3919.86 | 7.19 | 38.53 |
Annual Sum or Average | 0.925019E+11 | 0.840842E+11 | ||||||
Minimum of Months | 0.443677E+10 | 0.403302E+10 | 4312.27 | 3919.86 | 3919.86 | 6.93 | 38.53 | |
Maximum of Months | 0.105464E+11 | 0.958671E+10 | 4312.27 | 3919.86 | 3919.86 | 13.03 | 38.53 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.111257E+09 | 0.101132E+09 | 4312.27 | 18-JAN-14:50 | 3919.86 | 3919.86 | 15.50 | 19.26 |
February | 0.256580E+09 | 0.233231E+09 | 4312.27 | 01-FEB-16:20 | 3919.86 | 3919.86 | 15.33 | 19.26 |
March | 0.316952E+09 | 0.288109E+09 | 4312.27 | 06-MAR-09:40 | 3919.86 | 3919.86 | 15.45 | 19.26 |
April | 0.561027E+09 | 0.509973E+09 | 4312.27 | 05-APR-14:50 | 3919.86 | 3919.86 | 15.35 | 19.26 |
May | 0.207300E+10 | 0.188435E+10 | 4312.27 | 01-MAY-07:50 | 3919.86 | 3919.86 | 15.51 | 19.26 |
June | 0.235752E+10 | 0.214299E+10 | 4312.27 | 01-JUN-08:00 | 3919.86 | 3919.86 | 15.33 | 19.26 |
July | 0.261065E+10 | 0.237308E+10 | 4312.27 | 03-JUL-07:50 | 3919.86 | 3919.86 | 15.68 | 19.26 |
August | 0.287068E+10 | 0.260945E+10 | 4312.27 | 01-AUG-08:00 | 3919.86 | 3919.86 | 15.50 | 19.26 |
September | 0.214534E+10 | 0.195012E+10 | 4312.27 | 01-SEP-07:30 | 3919.86 | 3919.86 | 15.55 | 19.26 |
October | 0.188662E+10 | 0.171494E+10 | 4312.27 | 02-OCT-09:40 | 3919.86 | 3919.86 | 15.38 | 19.26 |
November | 0.585607E+09 | 0.532317E+09 | 4312.27 | 01-NOV-07:40 | 3919.86 | 3919.86 | 15.47 | 19.26 |
December | 0.357056E+09 | 0.324564E+09 | 4312.27 | 11-DEC-09:50 | 3919.86 | 3919.86 | 15.37 | 19.26 |
Annual Sum or Average | 0.161323E+11 | 0.146643E+11 | ||||||
Minimum of Months | 0.111257E+09 | 0.101132E+09 | 4312.27 | 3919.86 | 3919.86 | 15.33 | 19.26 | |
Maximum of Months | 0.287068E+10 | 0.260945E+10 | 4312.27 | 3919.86 | 3919.86 | 15.68 | 19.26 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.896853E+10 | 0.815239E+10 | 3348.46 | 01-JAN-00:05 | 3043.75 | 3043.75 | 18.98 | 14.12 |
February | 0.810060E+10 | 0.736345E+10 | 3348.46 | 01-FEB-00:10 | 3043.75 | 3043.75 | 26.84 | 14.12 |
March | 0.896853E+10 | 0.815239E+10 | 3348.46 | 01-MAR-00:10 | 3043.75 | 3043.75 | 30.18 | 14.12 |
April | 0.867922E+10 | 0.788941E+10 | 3348.46 | 01-APR-00:10 | 3043.75 | 3043.75 | 38.15 | 14.12 |
May | 0.896853E+10 | 0.815239E+10 | 3348.46 | 01-MAY-00:03 | 3043.75 | 3043.75 | 28.39 | 14.12 |
June | 0.867922E+10 | 0.788941E+10 | 3348.46 | 01-JUN-00:10 | 3043.75 | 3043.75 | 32.50 | 14.12 |
July | 0.896853E+10 | 0.815239E+10 | 3348.46 | 01-JUL-00:10 | 3043.75 | 3043.75 | 38.89 | 14.12 |
August | 0.896853E+10 | 0.815239E+10 | 3348.46 | 01-AUG-00:10 | 3043.75 | 3043.75 | 43.13 | 14.12 |
September | 0.867922E+10 | 0.788941E+10 | 3348.46 | 01-SEP-00:10 | 3043.75 | 3043.75 | 31.24 | 14.12 |
October | 0.896853E+10 | 0.815239E+10 | 3348.46 | 01-OCT-00:10 | 3043.75 | 3043.75 | 31.73 | 14.12 |
November | 0.867922E+10 | 0.788941E+10 | 3348.46 | 01-NOV-00:10 | 3043.75 | 3043.75 | 35.14 | 14.12 |
December | 0.896853E+10 | 0.815239E+10 | 3348.46 | 01-DEC-00:10 | 3043.75 | 3043.75 | 22.56 | 14.12 |
Annual Sum or Average | 0.105597E+12 | 0.959878E+11 | ||||||
Minimum of Months | 0.810060E+10 | 0.736345E+10 | 3348.46 | 3043.75 | 3043.75 | 18.98 | 14.12 | |
Maximum of Months | 0.896853E+10 | 0.815239E+10 | 3348.46 | 3043.75 | 3043.75 | 43.13 | 14.12 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.98 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.17 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.70 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.38 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.55 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.65 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 57.91 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.02 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 56.87 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.99 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 56.26 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.00 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.98 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.91 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.172427E+11 | 0.156736E+11 | 32909.98 | 31-JAN-15:05 | 29915.17 | 29915.17 | 27.68 | 134.03 |
February | 0.200081E+11 | 0.181874E+11 | 32904.18 | 24-FEB-13:05 | 29909.90 | 29909.90 | 27.47 | 134.03 |
March | 0.253099E+11 | 0.230067E+11 | 32937.87 | 28-MAR-12:05 | 29940.52 | 29940.52 | 28.69 | 134.03 |
April | 0.342667E+11 | 0.311484E+11 | 32941.16 | 25-APR-14:05 | 29943.51 | 29943.51 | 29.18 | 134.03 |
May | 0.393818E+11 | 0.357981E+11 | 32941.16 | 01-MAY-09:30 | 29943.51 | 29943.51 | 28.88 | 134.03 |
June | 0.438804E+11 | 0.398873E+11 | 32941.16 | 01-JUN-09:05 | 29943.51 | 29943.51 | 28.88 | 134.03 |
July | 0.488347E+11 | 0.443907E+11 | 32941.16 | 03-JUL-07:50 | 29943.51 | 29943.51 | 29.48 | 134.03 |
August | 0.510265E+11 | 0.463831E+11 | 32941.16 | 01-AUG-08:30 | 29943.51 | 29943.51 | 29.43 | 134.03 |
September | 0.395907E+11 | 0.359880E+11 | 32941.16 | 01-SEP-07:40 | 29943.51 | 29943.51 | 28.81 | 134.03 |
October | 0.392933E+11 | 0.357176E+11 | 32941.16 | 04-OCT-09:05 | 29943.51 | 29943.51 | 29.23 | 134.03 |
November | 0.287405E+11 | 0.261251E+11 | 32941.16 | 01-NOV-10:05 | 29943.51 | 29943.51 | 29.53 | 134.03 |
December | 0.233501E+11 | 0.212253E+11 | 32941.16 | 12-DEC-14:05 | 29943.51 | 29943.51 | 29.93 | 134.03 |
Annual Sum or Average | 0.410925E+12 | 0.373531E+12 | ||||||
Minimum of Months | 0.172427E+11 | 0.156736E+11 | 32904.18 | 29909.90 | 29909.90 | 27.47 | 134.03 | |
Maximum of Months | 0.510265E+11 | 0.463831E+11 | 32941.16 | 29943.51 | 29943.51 | 29.93 | 134.03 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6.44 | 25927.45 | 03-JAN-06:02 | 59.75 | 59.75 | 8572.41 | 1164287.24 | 09-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 25.30 | 25.30 | 4749.09 | 1053750.78 | 17-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.01 | 25.01 | 3597.57 | 1204389.09 | 11-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.08 | 26.08 | 84.03 | 77297.97 | 18-APR-14:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 39.42 | 39.42 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 39.42 | 39.42 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 39.42 | 39.42 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 39.42 | 39.42 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 39.42 | 39.42 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 39.42 | 39.42 | 13.99 | 16441.45 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 36.39 | 36.39 | 316.13 | 211962.11 | 16-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 27.87 | 27.87 | 5674.67 | 1213618.47 | 20-DEC-05:11 |
Annual Sum or Average | 0.55 | 1913.96 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.01 | 25.01 | 0.00 | 0.00 | ||
Maximum of Months | 6.44 | 25927.45 | 59.75 | 59.75 | 8572.41 | 1213618.47 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 155415.61 | 1647444.04 | 19-JAN-11:05 | 11.80 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 246911.76 | 2149587.64 | 27-FEB-16:13 | 13.36 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 267252.40 | 1739370.42 | 29-MAR-15:30 | 12.09 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 441450.73 | 2358139.95 | 27-APR-15:43 | 14.01 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 689550.16 | 2375306.43 | 10-MAY-15:53 | 14.06 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 729226.94 | 2366601.31 | 12-JUN-15:13 | 14.04 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 732255.39 | 1898447.88 | 05-JUL-12:05 | 12.58 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 765211.80 | 1890540.71 | 22-AUG-12:05 | 12.56 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 701565.61 | 2259829.37 | 22-SEP-14:03 | 13.71 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 585483.75 | 2155621.31 | 18-OCT-15:23 | 13.38 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 341124.03 | 2156864.77 | 06-NOV-10:23 | 13.39 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 234147.69 | 2282359.68 | 15-DEC-13:53 | 13.78 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 492118.82 | 0.00 | ||||||
Minimum of Months | 155415.61 | 1647444.04 | 11.80 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 765211.80 | 2375306.43 | 14.06 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 156058.93 | 2940493.59 | 19-JAN-16:40 | 15.92 | 11.57 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 252609.81 | 2891095.84 | 27-FEB-16:50 | 15.69 | 11.17 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 268570.88 | 2993786.35 | 07-MAR-06:02 | 16.06 | 11.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 447767.42 | 2872550.23 | 29-APR-05:03 | 15.85 | 11.14 | 0.00 | 0.00 | 01-APR-00:10 |
May | 721235.73 | 3347722.94 | 22-MAY-03:02 | 17.09 | 11.88 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 751672.02 | 3070520.94 | 08-JUN-05:02 | 16.22 | 11.45 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 738940.52 | 2935279.82 | 28-JUL-05:03 | 15.80 | 11.24 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 774729.78 | 3186751.68 | 26-AUG-05:02 | 16.59 | 11.63 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 721580.27 | 3466056.12 | 05-SEP-04:11 | 17.95 | 12.05 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 603218.57 | 3190567.08 | 21-OCT-05:03 | 16.60 | 11.63 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 347198.99 | 3071952.52 | 01-NOV-05:02 | 16.23 | 11.45 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 239924.81 | 2720740.29 | 14-DEC-13:30 | 15.21 | 11.54 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 503295.05 | 0.00 | ||||||
Minimum of Months | 156058.93 | 2720740.29 | 15.21 | 11.14 | 0.00 | 0.00 | ||
Maximum of Months | 774729.78 | 3466056.12 | 17.95 | 12.05 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 88504.30 | 741087.86 | 02-JAN-15:00 | 33.27 | 28.89 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 222623.58 | 1007467.46 | 02-FEB-13:05 | 38.54 | 31.34 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 426437.92 | 1301755.61 | 26-MAR-14:00 | 44.29 | 34.37 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 927026.05 | 1713091.31 | 28-APR-15:00 | 52.24 | 39.15 | 0.00 | 0.00 | 01-APR-00:10 |
May | 721789.62 | 1081890.85 | 18-MAY-16:00 | 40.00 | 35.34 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 975042.31 | 1393306.28 | 14-JUN-14:00 | 46.07 | 38.39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1210588.40 | 1696436.49 | 21-JUL-16:00 | 51.92 | 40.98 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1391459.26 | 1862941.62 | 30-AUG-16:10 | 55.12 | 41.96 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 689728.83 | 1245663.26 | 09-SEP-17:00 | 43.20 | 38.48 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 736031.95 | 1345475.24 | 05-OCT-15:00 | 45.14 | 37.41 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 516883.38 | 1345271.70 | 02-NOV-13:00 | 45.14 | 34.63 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 525932.07 | 1534746.33 | 13-DEC-15:00 | 48.81 | 35.78 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 705799.80 | 0.00 | ||||||
Minimum of Months | 88504.30 | 741087.86 | 33.27 | 28.89 | 0.00 | 0.00 | ||
Maximum of Months | 1391459.26 | 1862941.62 | 55.12 | 41.96 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.27 | 57.27 | 12860.29 | 42455.45 | 20-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.69 | 56.69 | 12838.17 | 42389.67 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.29 | 57.29 | 13080.93 | 41428.83 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.85 | 56.85 | 11678.42 | 39124.16 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.15 | 57.15 | 11278.54 | 36812.07 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.93 | 57.93 | 10889.39 | 34304.54 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.10 | 58.10 | 9856.44 | 32638.70 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.32 | 57.32 | 10755.60 | 33324.48 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.18 | 57.18 | 10627.69 | 35276.17 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.74 | 57.74 | 11283.71 | 37983.60 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.70 | 56.70 | 12147.09 | 40383.69 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.49 | 56.49 | 12315.54 | 41971.21 | 28-DEC-12:15 |
Annual Sum or Average | 0.00 | 11627.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.49 | 56.49 | 9856.44 | 32638.70 | ||
Maximum of Months | 0.00 | 0.00 | 58.10 | 58.10 | 13080.93 | 42455.45 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 216004.53 | 3685892.62 | 31-JAN-15:05 | 27.68 | 23.97 | 1514.07 | 137258.57 | 09-JAN-18:30 |
February | 338884.50 | 3568314.30 | 24-FEB-13:05 | 27.47 | 23.85 | 1034.47 | 153597.34 | 17-FEB-12:50 |
March | 403296.82 | 4251035.70 | 28-MAR-12:05 | 28.69 | 24.85 | 1742.95 | 126159.02 | 09-MAR-08:00 |
April | 726316.42 | 5047230.40 | 28-APR-16:00 | 30.11 | 27.05 | 884.30 | 103820.54 | 03-APR-06:20 |
May | 1706898.91 | 5968741.97 | 26-MAY-10:05 | 31.75 | 27.77 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1996074.53 | 6050985.62 | 23-JUN-10:05 | 31.90 | 27.95 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2356342.13 | 6428734.21 | 05-JUL-12:05 | 32.58 | 28.44 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2289078.55 | 6198678.52 | 22-AUG-12:05 | 32.16 | 28.04 | 3.03 | 13530.86 | 20-AUG-04:50 |
September | 1891687.94 | 5944327.10 | 01-SEP-12:05 | 31.71 | 27.52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 1426420.45 | 5990228.93 | 06-OCT-14:05 | 31.79 | 28.29 | 293.44 | 108377.47 | 28-OCT-09:00 |
November | 605448.27 | 5427698.26 | 01-NOV-14:05 | 30.79 | 26.94 | 766.81 | 130170.93 | 15-NOV-10:30 |
December | 384964.95 | 4945556.40 | 12-DEC-14:05 | 29.93 | 26.17 | 1858.03 | 172934.60 | 26-DEC-09:10 |
Annual Sum or Average | 1200952.81 | 674.67 | ||||||
Minimum of Months | 216004.53 | 3568314.30 | 27.47 | 23.85 | 0.00 | 0.00 | ||
Maximum of Months | 2356342.13 | 6428734.21 | 32.58 | 28.44 | 1858.03 | 172934.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 91371410.27 | 0.00 | 0.389122E+11 | 0.345896E+10 | 0.00 | 0.00 |
February | 29683817.63 | 0.00 | 0.554933E+11 | 0.363917E+10 | 0.00 | 0.00 |
March | 13950351.28 | 0.00 | 0.694834E+11 | 0.454453E+10 | 0.00 | 0.00 |
April | 13748102.89 | 0.00 | 0.113392E+12 | 0.548427E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.142564E+12 | 0.553935E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.154722E+12 | 0.615410E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.168254E+12 | 0.665993E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.185142E+12 | 0.794075E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.143539E+12 | 0.529625E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.134782E+12 | 0.611159E+10 | 0.00 | 0.00 |
November | 58268.81 | 0.00 | 0.847191E+11 | 0.512788E+10 | 0.00 | 0.00 |
December | 52378516.45 | 0.00 | 0.633503E+11 | 0.473504E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.201190E+09 | 0.00 | 0.135435E+13 | 0.646918E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.389122E+11 | 0.345896E+10 | 0.00 | 0.00 |
Maximum of Months | 91371410.27 | 0.00 | 0.185142E+12 | 0.794075E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.166341E+11 | 0.00 | 0.308391E+12 | 0.256211E+11 | 0.00 | 0.00 |
February | 0.762112E+10 | 0.00 | 0.436165E+12 | 0.250590E+11 | 0.00 | 0.00 |
March | 0.674975E+10 | 0.00 | 0.518457E+12 | 0.294774E+11 | 0.00 | 0.00 |
April | 52089634.06 | 0.00 | 0.818957E+12 | 0.338811E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.129612E+13 | 0.476289E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132443E+13 | 0.489041E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.137971E+13 | 0.477314E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.142465E+13 | 0.510673E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.128209E+13 | 0.432731E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112227E+13 | 0.458851E+11 | 0.00 | 0.00 |
November | 0.390766E+09 | 0.00 | 0.643854E+12 | 0.324815E+11 | 0.00 | 0.00 |
December | 0.106460E+11 | 0.00 | 0.450324E+12 | 0.279184E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.420938E+11 | 0.00 | 0.110054E+14 | 0.458928E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.308391E+12 | 0.250590E+11 | 0.00 | 0.00 |
Maximum of Months | 0.166341E+11 | 0.00 | 0.142465E+13 | 0.510673E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.671123E+10 | 0.00 | 0.303282E+11 | 0.246492E+10 | 0.00 | 0.00 |
February | 0.394616E+10 | 0.00 | 0.440308E+11 | 0.247665E+10 | 0.00 | 0.00 |
March | 0.294476E+10 | 0.00 | 0.534965E+11 | 0.286172E+10 | 0.00 | 0.00 |
April | 50152165.55 | 0.00 | 0.866360E+11 | 0.341813E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.143674E+12 | 0.527734E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149056E+12 | 0.554736E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.154574E+12 | 0.535312E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.157917E+12 | 0.564949E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.138163E+12 | 0.453244E+10 | 0.00 | 0.00 |
October | 61384239.87 | 0.00 | 0.120021E+12 | 0.468393E+10 | 0.00 | 0.00 |
November | 0.501636E+09 | 0.00 | 0.626074E+11 | 0.295175E+10 | 0.00 | 0.00 |
December | 0.466501E+10 | 0.00 | 0.433980E+11 | 0.262336E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.188803E+11 | 0.00 | 0.118390E+13 | 0.478402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.303282E+11 | 0.246492E+10 | 0.00 | 0.00 |
Maximum of Months | 0.671123E+10 | 0.00 | 0.157917E+12 | 0.564949E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.203163E+11 | 0.131757E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.237956E+11 | 0.113966E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.325190E+11 | 0.132440E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.512819E+11 | 0.121248E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.953758E+11 | 0.132025E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.100442E+12 | 0.130953E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109203E+12 | 0.129134E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.121463E+12 | 0.145093E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.103109E+12 | 0.135144E+11 | 0.00 | 0.00 |
October | 80.37 | 0.00 | 0.887705E+11 | 0.138340E+11 | 0.00 | 0.00 |
November | 261.28 | 0.00 | 0.489548E+11 | 0.132427E+11 | 0.00 | 0.00 |
December | 79.87 | 0.00 | 0.317500E+11 | 0.133320E+11 | 0.00 | 0.00 |
Annual Sum or Average | 421.52 | 0.00 | 0.826981E+12 | 0.157585E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.203163E+11 | 0.113966E+11 | 0.00 | 0.00 |
Maximum of Months | 261.28 | 0.00 | 0.121463E+12 | 0.145093E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.501548E+11 | 0.154485E+12 | 0.00 | 17.93 |
February | 0.00 | 0.00 | 0.185767E+12 | 0.179518E+12 | 0.00 | 20.80 |
March | 0.00 | 0.00 | 0.453330E+12 | 0.261572E+12 | 0.00 | 27.70 |
April | 0.00 | 0.00 | 0.107136E+13 | 0.329048E+12 | 0.00 | 7.40 |
May | 0.00 | 0.00 | 0.448919E+12 | 0.195689E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.742908E+12 | 0.259596E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.108732E+13 | 0.341010E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.138515E+13 | 0.400504E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.437947E+12 | 0.188592E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.621469E+12 | 0.246512E+12 | 0.00 | 5.95 |
November | 0.00 | 0.00 | 0.526723E+12 | 0.247300E+12 | 0.00 | 17.53 |
December | 0.00 | 0.00 | 0.624332E+12 | 0.296362E+12 | 0.00 | 28.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.763537E+13 | 0.310019E+13 | 0.00 | 125.96 |
Minimum of Months | 0.00 | 0.00 | 0.501548E+11 | 0.154485E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.138515E+13 | 0.400504E+12 | 0.00 | 28.63 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.613328E+10 | 0.251630E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.115155E+11 | 0.331225E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191021E+11 | 0.482641E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.252959E+11 | 0.621109E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.825580E+10 | 0.321838E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.144267E+11 | 0.455788E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.214984E+11 | 0.619184E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279458E+11 | 0.755279E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.800491E+10 | 0.308853E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.143618E+11 | 0.437537E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.189464E+11 | 0.482319E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.251396E+11 | 0.580267E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200626E+12 | 0.564767E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.613328E+10 | 0.251630E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.279458E+11 | 0.755279E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.433494E+11 | 0.213731E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.982632E+11 | 0.297021E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172604E+12 | 0.445385E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238511E+12 | 0.588268E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.763105E+11 | 0.301846E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136700E+12 | 0.432862E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204584E+12 | 0.589649E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.265369E+12 | 0.718260E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.729110E+11 | 0.287430E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133549E+12 | 0.411145E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.172852E+12 | 0.447722E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.227716E+12 | 0.535630E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184272E+13 | 0.526895E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.433494E+11 | 0.213731E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.265369E+12 | 0.718260E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.305367E+10 | 0.193484E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.889310E+10 | 0.284135E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166033E+11 | 0.438486E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.237410E+11 | 0.590482E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.786214E+10 | 0.309711E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139173E+11 | 0.441118E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.207190E+11 | 0.598537E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.267749E+11 | 0.727152E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.746126E+10 | 0.293910E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133302E+11 | 0.414363E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.166732E+11 | 0.441363E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.217536E+11 | 0.523942E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180783E+12 | 0.525668E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.305367E+10 | 0.193484E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.267749E+11 | 0.727152E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.345896E+10 | 0.389122E+11 | 91371410.27 | 0.386326E+09 | 0.789578E+09 | 0.00 | 0.00 | 0.00 |
February | 0.363917E+10 | 0.554933E+11 | 29683817.63 | 0.132152E+09 | 0.134728E+10 | 0.00 | 0.00 | 0.00 |
March | 0.454453E+10 | 0.694834E+11 | 13950351.28 | 78596446.47 | 0.259508E+10 | 0.00 | 0.00 | 0.00 |
April | 0.548427E+10 | 0.113392E+12 | 13748102.89 | 0.00 | 0.733585E+10 | 0.00 | 0.00 | 0.00 |
May | 0.553935E+10 | 0.142564E+12 | 0.00 | 0.00 | 0.309942E+11 | 0.00 | 0.00 | 0.00 |
June | 0.615410E+10 | 0.154722E+12 | 0.00 | 0.00 | 0.379873E+11 | 0.00 | 0.00 | 0.00 |
July | 0.665993E+10 | 0.168254E+12 | 0.00 | 0.00 | 0.415012E+11 | 0.00 | 0.00 | 0.00 |
August | 0.794075E+10 | 0.185142E+12 | 0.00 | 0.00 | 0.404826E+11 | 0.00 | 0.00 | 0.00 |
September | 0.529625E+10 | 0.143539E+12 | 0.00 | 0.00 | 0.270041E+11 | 0.00 | 0.00 | 0.00 |
October | 0.611159E+10 | 0.134782E+12 | 0.00 | 0.00 | 0.229330E+11 | 0.00 | 0.00 | 0.00 |
November | 0.512788E+10 | 0.847191E+11 | 58268.81 | 0.00 | 0.542459E+10 | 0.00 | 0.00 | 0.00 |
December | 0.473504E+10 | 0.633503E+11 | 52378516.45 | 0.217240E+09 | 0.301986E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646918E+11 | 0.135435E+13 | 0.201190E+09 | 0.814314E+09 | 0.221415E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345896E+10 | 0.389122E+11 | 0.00 | 0.00 | 0.789578E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.794075E+10 | 0.185142E+12 | 91371410.27 | 0.386326E+09 | 0.415012E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.256211E+11 | 0.308391E+12 | 0.166341E+11 | 0.615686E+10 | 0.972959E+10 | 0.00 | 0.00 | 0.00 |
February | 0.250590E+11 | 0.436165E+12 | 0.762112E+10 | 0.273490E+10 | 0.161120E+11 | 0.00 | 0.00 | 0.00 |
March | 0.294774E+11 | 0.518457E+12 | 0.674975E+10 | 0.170043E+10 | 0.304610E+11 | 0.00 | 0.00 | 0.00 |
April | 0.338811E+11 | 0.818957E+12 | 52089634.06 | 17980834.19 | 0.733600E+11 | 0.00 | 0.00 | 0.00 |
May | 0.476289E+11 | 0.129612E+13 | 0.00 | 0.00 | 0.312719E+12 | 0.00 | 0.00 | 0.00 |
June | 0.489041E+11 | 0.132443E+13 | 0.00 | 0.00 | 0.382447E+12 | 0.00 | 0.00 | 0.00 |
July | 0.477314E+11 | 0.137971E+13 | 0.00 | 0.00 | 0.419472E+12 | 0.00 | 0.00 | 0.00 |
August | 0.510673E+11 | 0.142465E+13 | 0.00 | 0.00 | 0.411574E+12 | 0.00 | 0.00 | 0.00 |
September | 0.432731E+11 | 0.128209E+13 | 0.00 | 0.00 | 0.275513E+12 | 0.00 | 0.00 | 0.00 |
October | 0.458851E+11 | 0.112227E+13 | 0.00 | 0.00 | 0.232576E+12 | 0.00 | 0.00 | 0.00 |
November | 0.324815E+11 | 0.643854E+12 | 0.390766E+09 | 5087996.78 | 0.600954E+11 | 0.00 | 0.00 | 0.00 |
December | 0.279184E+11 | 0.450324E+12 | 0.106460E+11 | 0.456138E+10 | 0.322830E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458928E+12 | 0.110054E+14 | 0.420938E+11 | 0.151766E+11 | 0.225634E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.250590E+11 | 0.308391E+12 | 0.00 | 0.00 | 0.972959E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.510673E+11 | 0.142465E+13 | 0.166341E+11 | 0.615686E+10 | 0.419472E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.246492E+10 | 0.303282E+11 | 0.671123E+10 | 0.101392E+10 | 0.268089E+09 | 0.00 | 0.00 | 0.00 |
February | 0.247665E+10 | 0.440308E+11 | 0.394616E+10 | 0.470814E+09 | 0.760532E+09 | 0.00 | 0.00 | 0.00 |
March | 0.286172E+10 | 0.534965E+11 | 0.294476E+10 | 0.296831E+09 | 0.194530E+10 | 0.00 | 0.00 | 0.00 |
April | 0.341813E+10 | 0.866360E+11 | 50152165.55 | 0.00 | 0.617322E+10 | 0.00 | 0.00 | 0.00 |
May | 0.527734E+10 | 0.143674E+12 | 0.00 | 0.00 | 0.297913E+11 | 0.00 | 0.00 | 0.00 |
June | 0.554736E+10 | 0.149056E+12 | 0.00 | 0.00 | 0.364207E+11 | 0.00 | 0.00 | 0.00 |
July | 0.535312E+10 | 0.154574E+12 | 0.00 | 0.00 | 0.399118E+11 | 0.00 | 0.00 | 0.00 |
August | 0.564949E+10 | 0.157917E+12 | 0.00 | 0.00 | 0.391881E+11 | 0.00 | 0.00 | 0.00 |
September | 0.453244E+10 | 0.138163E+12 | 0.00 | 0.00 | 0.262538E+11 | 0.00 | 0.00 | 0.00 |
October | 0.468393E+10 | 0.120021E+12 | 61384239.87 | 0.00 | 0.223347E+11 | 0.00 | 0.00 | 0.00 |
November | 0.295175E+10 | 0.626074E+11 | 0.501636E+09 | 2604559.76 | 0.553273E+10 | 0.00 | 0.00 | 0.00 |
December | 0.262336E+10 | 0.433980E+11 | 0.466501E+10 | 0.721659E+09 | 0.283982E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478402E+11 | 0.118390E+13 | 0.188803E+11 | 0.250583E+10 | 0.211420E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246492E+10 | 0.303282E+11 | 0.00 | 0.00 | 0.268089E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.564949E+10 | 0.157917E+12 | 0.671123E+10 | 0.101392E+10 | 0.399118E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131757E+11 | 0.203163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113966E+11 | 0.237956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132440E+11 | 0.325190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121248E+11 | 0.512819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132025E+11 | 0.953758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130953E+11 | 0.100442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129134E+11 | 0.109203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145093E+11 | 0.121463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135144E+11 | 0.103109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138340E+11 | 0.887705E+11 | 80.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132427E+11 | 0.489548E+11 | 261.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133320E+11 | 0.317500E+11 | 79.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157585E+12 | 0.826981E+12 | 421.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.113966E+11 | 0.203163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145093E+11 | 0.121463E+12 | 261.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.944143E+11 | 0.382904E+11 | 0.00 | 0.00 | 0.00 | 0.479905E+11 | 0.00 | 0.00 |
February | 0.852775E+11 | 0.147440E+12 | 0.00 | 0.00 | 0.00 | 0.556631E+11 | 0.00 | 0.00 |
March | 0.944143E+11 | 0.360646E+12 | 0.00 | 0.00 | 0.00 | 0.741402E+11 | 0.00 | 0.00 |
April | 0.913687E+11 | 0.853578E+12 | 0.00 | 0.00 | 0.00 | 0.198127E+11 | 0.00 | 0.00 |
May | 0.944143E+11 | 0.347644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913687E+11 | 0.574680E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.944143E+11 | 0.840727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944143E+11 | 0.107906E+13 | 0.00 | 0.00 | 0.00 | 1322862.92 | 0.00 | 0.00 |
September | 0.913687E+11 | 0.340724E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944143E+11 | 0.485368E+12 | 0.00 | 0.00 | 0.00 | 0.159260E+11 | 0.00 | 0.00 |
November | 0.913687E+11 | 0.417925E+12 | 0.00 | 0.00 | 0.00 | 0.469212E+11 | 0.00 | 0.00 |
December | 0.944143E+11 | 0.499357E+12 | 0.00 | 0.00 | 0.00 | 0.766274E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.111165E+13 | 0.598544E+13 | 0.00 | 0.00 | 0.00 | 0.337082E+12 | 0.00 | 0.00 |
Minimum of Months | 0.852775E+11 | 0.382904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944143E+11 | 0.107906E+13 | 0.00 | 0.00 | 0.00 | 0.766274E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138306E+10 | 0.500004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124922E+10 | 0.945244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138306E+10 | 0.156588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133845E+10 | 0.204232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138306E+10 | 0.642048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133845E+10 | 0.112072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138306E+10 | 0.166897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138306E+10 | 0.217761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133845E+10 | 0.625484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138306E+10 | 0.113695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133845E+10 | 0.154616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138306E+10 | 0.207200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162844E+11 | 0.160434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124922E+10 | 0.500004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138306E+10 | 0.217761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131860E+11 | 0.351623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119100E+11 | 0.804711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131860E+11 | 0.141251E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127607E+11 | 0.192445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131860E+11 | 0.593120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127607E+11 | 0.106174E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131860E+11 | 0.158805E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131860E+11 | 0.206729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127607E+11 | 0.569287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131860E+11 | 0.105621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127607E+11 | 0.140840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131860E+11 | 0.187339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155255E+12 | 0.147108E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119100E+11 | 0.351623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131860E+11 | 0.206729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134485E+10 | 0.246367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121470E+10 | 0.726646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134485E+10 | 0.135633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130146E+10 | 0.191377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134485E+10 | 0.610987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130146E+10 | 0.108075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134485E+10 | 0.160785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134485E+10 | 0.208483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130146E+10 | 0.582362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134485E+10 | 0.105314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130146E+10 | 0.135610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134485E+10 | 0.178591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158345E+11 | 0.144050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121470E+10 | 0.246367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134485E+10 | 0.208483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.345896E+10 | 91371410.27 | 0.389122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363917E+10 | 29683817.63 | 0.554933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.454453E+10 | 13950351.28 | 0.694834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.548427E+10 | 13748102.89 | 0.113392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.553935E+10 | 0.00 | 0.142564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.615410E+10 | 0.00 | 0.154722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665993E+10 | 0.00 | 0.168254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.794075E+10 | 0.00 | 0.185142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529625E+10 | 0.00 | 0.143539E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.611159E+10 | 0.00 | 0.134782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.512788E+10 | 58268.81 | 0.847191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473504E+10 | 52378516.45 | 0.633503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646918E+11 | 0.201190E+09 | 0.135435E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345896E+10 | 0.00 | 0.389122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.794075E+10 | 91371410.27 | 0.185142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.256211E+11 | 0.166341E+11 | 0.308391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250590E+11 | 0.762112E+10 | 0.436165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294774E+11 | 0.674975E+10 | 0.518457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338811E+11 | 52089634.06 | 0.818957E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.476289E+11 | 0.00 | 0.129612E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.489041E+11 | 0.00 | 0.132443E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.477314E+11 | 0.00 | 0.137971E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.510673E+11 | 0.00 | 0.142465E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.432731E+11 | 0.00 | 0.128209E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.458851E+11 | 0.00 | 0.112227E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324815E+11 | 0.390766E+09 | 0.643854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279184E+11 | 0.106460E+11 | 0.450324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458928E+12 | 0.420938E+11 | 0.110054E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.250590E+11 | 0.00 | 0.308391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.510673E+11 | 0.166341E+11 | 0.142465E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.246492E+10 | 0.671123E+10 | 0.303282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.247665E+10 | 0.394616E+10 | 0.440308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286172E+10 | 0.294476E+10 | 0.534965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341813E+10 | 50152165.55 | 0.866360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.527734E+10 | 0.00 | 0.143674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.554736E+10 | 0.00 | 0.149056E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.535312E+10 | 0.00 | 0.154574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.564949E+10 | 0.00 | 0.157917E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453244E+10 | 0.00 | 0.138163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468393E+10 | 61384239.87 | 0.120021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295175E+10 | 0.501636E+09 | 0.626074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262336E+10 | 0.466501E+10 | 0.433980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478402E+11 | 0.188803E+11 | 0.118390E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246492E+10 | 0.00 | 0.303282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.564949E+10 | 0.671123E+10 | 0.157917E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.131757E+11 | 0.00 | 0.203163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113966E+11 | 0.00 | 0.237956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132440E+11 | 0.00 | 0.325190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121248E+11 | 0.00 | 0.512819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132025E+11 | 0.00 | 0.953758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130953E+11 | 0.00 | 0.100442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129134E+11 | 0.00 | 0.109203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145093E+11 | 0.00 | 0.121463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135144E+11 | 0.00 | 0.103109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138340E+11 | 80.37 | 0.887705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132427E+11 | 261.28 | 0.489548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133320E+11 | 79.87 | 0.317500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157585E+12 | 421.52 | 0.826981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.113966E+11 | 0.00 | 0.203163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145093E+11 | 261.28 | 0.121463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.944143E+11 | 0.00 | 0.501548E+11 | 0.00 | 0.118644E+11 | 0.00 | 0.00 | 0.00 | 0.482065E+11 | 0.00 | 0.00 | 0.00 |
February | 0.852775E+11 | 0.00 | 0.185767E+12 | 0.00 | 0.383266E+11 | 0.00 | 0.00 | 0.00 | 0.559137E+11 | 0.00 | 0.00 | 0.00 |
March | 0.944143E+11 | 0.00 | 0.453330E+12 | 0.00 | 0.926839E+11 | 0.00 | 0.00 | 0.00 | 0.744739E+11 | 0.00 | 0.00 | 0.00 |
April | 0.913687E+11 | 0.00 | 0.107136E+13 | 0.00 | 0.217778E+12 | 0.00 | 0.00 | 0.00 | 0.199018E+11 | 0.00 | 0.00 | 0.00 |
May | 0.944143E+11 | 0.00 | 0.448919E+12 | 0.00 | 0.101274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913687E+11 | 0.00 | 0.742908E+12 | 0.00 | 0.168227E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.944143E+11 | 0.00 | 0.108732E+13 | 0.00 | 0.246595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944143E+11 | 0.00 | 0.138515E+13 | 0.00 | 0.306089E+12 | 0.00 | 0.00 | 0.00 | 1328817.66 | 0.00 | 0.00 | 0.00 |
September | 0.913687E+11 | 0.00 | 0.437947E+12 | 0.00 | 0.972231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944143E+11 | 0.00 | 0.621469E+12 | 0.00 | 0.136100E+12 | 0.00 | 0.00 | 0.00 | 0.159977E+11 | 0.00 | 0.00 | 0.00 |
November | 0.913687E+11 | 0.00 | 0.526723E+12 | 0.00 | 0.108799E+12 | 0.00 | 0.00 | 0.00 | 0.471324E+11 | 0.00 | 0.00 | 0.00 |
December | 0.944143E+11 | 0.00 | 0.624332E+12 | 0.00 | 0.124975E+12 | 0.00 | 0.00 | 0.00 | 0.769723E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111165E+13 | 0.00 | 0.763537E+13 | 0.00 | 0.164994E+13 | 0.00 | 0.00 | 0.00 | 0.338600E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852775E+11 | 0.00 | 0.501548E+11 | 0.00 | 0.118644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944143E+11 | 0.00 | 0.138515E+13 | 0.00 | 0.306089E+12 | 0.00 | 0.00 | 0.00 | 0.769723E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138306E+10 | 0.00 | 0.613328E+10 | 0.00 | 0.113324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124922E+10 | 0.00 | 0.115155E+11 | 0.00 | 0.206303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138306E+10 | 0.00 | 0.191021E+11 | 0.00 | 0.344335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133845E+10 | 0.00 | 0.252959E+11 | 0.00 | 0.487265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138306E+10 | 0.00 | 0.825580E+10 | 0.00 | 0.183532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133845E+10 | 0.00 | 0.144267E+11 | 0.00 | 0.321944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138306E+10 | 0.00 | 0.214984E+11 | 0.00 | 0.480878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138306E+10 | 0.00 | 0.279458E+11 | 0.00 | 0.616973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133845E+10 | 0.00 | 0.800491E+10 | 0.00 | 0.175008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138306E+10 | 0.00 | 0.143618E+11 | 0.00 | 0.299231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133845E+10 | 0.00 | 0.189464E+11 | 0.00 | 0.348474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138306E+10 | 0.00 | 0.251396E+11 | 0.00 | 0.441960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162844E+11 | 0.00 | 0.200626E+12 | 0.00 | 0.401923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124922E+10 | 0.00 | 0.613328E+10 | 0.00 | 0.113324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138306E+10 | 0.00 | 0.279458E+11 | 0.00 | 0.616973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.131860E+11 | 0.00 | 0.433494E+11 | 0.00 | 0.818706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119100E+11 | 0.00 | 0.982632E+11 | 0.00 | 0.177921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131860E+11 | 0.00 | 0.172604E+12 | 0.00 | 0.313525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127607E+11 | 0.00 | 0.238511E+12 | 0.00 | 0.460661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131860E+11 | 0.00 | 0.763105E+11 | 0.00 | 0.169985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127607E+11 | 0.00 | 0.136700E+12 | 0.00 | 0.305255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131860E+11 | 0.00 | 0.204584E+12 | 0.00 | 0.457789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131860E+11 | 0.00 | 0.265369E+12 | 0.00 | 0.586400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127607E+11 | 0.00 | 0.729110E+11 | 0.00 | 0.159823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131860E+11 | 0.00 | 0.133549E+12 | 0.00 | 0.279284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127607E+11 | 0.00 | 0.172852E+12 | 0.00 | 0.320116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131860E+11 | 0.00 | 0.227716E+12 | 0.00 | 0.403770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155255E+12 | 0.00 | 0.184272E+13 | 0.00 | 0.371640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119100E+11 | 0.00 | 0.433494E+11 | 0.00 | 0.818706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131860E+11 | 0.00 | 0.265369E+12 | 0.00 | 0.586400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134485E+10 | 0.00 | 0.305367E+10 | 0.00 | 0.589996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121470E+10 | 0.00 | 0.889310E+10 | 0.00 | 0.162665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134485E+10 | 0.00 | 0.166033E+11 | 0.00 | 0.304002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130146E+10 | 0.00 | 0.237410E+11 | 0.00 | 0.460336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134485E+10 | 0.00 | 0.786214E+10 | 0.00 | 0.175227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130146E+10 | 0.00 | 0.139173E+11 | 0.00 | 0.310972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134485E+10 | 0.00 | 0.207190E+11 | 0.00 | 0.464053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134485E+10 | 0.00 | 0.267749E+11 | 0.00 | 0.592667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130146E+10 | 0.00 | 0.746126E+10 | 0.00 | 0.163764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134485E+10 | 0.00 | 0.133302E+11 | 0.00 | 0.279878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130146E+10 | 0.00 | 0.166732E+11 | 0.00 | 0.311217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134485E+10 | 0.00 | 0.217536E+11 | 0.00 | 0.389457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158345E+11 | 0.00 | 0.180783E+12 | 0.00 | 0.367324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121470E+10 | 0.00 | 0.305367E+10 | 0.00 | 0.589996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134485E+10 | 0.00 | 0.267749E+11 | 0.00 | 0.592667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278126E+09 | 0.138008E+10 | 0.00 | 0.103891E+09 | 0.00 | 0.00 | 0.504310E+11 | 0.00 | 0.87 |
February | 0.207358E+09 | 0.137261E+10 | 0.00 | 81118419.90 | 4333917.25 | 0.00 | 0.383351E+11 | 0.00 | 0.97 |
March | 0.119261E+09 | 0.293867E+10 | 0.00 | 88541877.73 | 5579004.37 | 0.00 | 0.411031E+11 | 0.00 | 0.97 |
April | 0.136435E+09 | 0.509566E+10 | 0.00 | 59864775.18 | 72116959.85 | 0.00 | 0.187607E+11 | 0.00 | 0.87 |
May | 0.00 | 0.250156E+11 | 0.00 | 1252492.73 | 0.144868E+09 | 0.00 | 6257107.62 | 0.00 | 0.33 |
June | 2642122.16 | 0.304291E+11 | 0.00 | 2063613.49 | 0.207405E+09 | 0.00 | 88282348.33 | 0.00 | 0.35 |
July | 0.00 | 0.374439E+11 | 0.00 | 0.00 | 0.401138E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.382943E+11 | 0.00 | 243525.09 | 0.229350E+09 | 0.00 | 23024107.59 | 0.00 | 0.35 |
September | 38932.55 | 0.285555E+11 | 0.00 | 1540556.53 | 0.289238E+09 | 0.00 | 0.103184E+09 | 0.00 | 0.34 |
October | 92194253.89 | 0.215812E+11 | 0.00 | 38164411.92 | 0.229906E+09 | 0.00 | 0.110898E+11 | 0.00 | 0.63 |
November | 0.198188E+09 | 0.636098E+10 | 0.00 | 92150712.80 | 7684014.13 | 0.00 | 0.330678E+11 | 0.00 | 1.02 |
December | 0.303146E+09 | 0.397671E+10 | 0.00 | 98106306.57 | 11548314.92 | 0.00 | 0.456600E+11 | 0.00 | 0.87 |
Annual Sum or Average | 0.133739E+10 | 0.202444E+12 | 0.00 | 0.566938E+09 | 0.160317E+10 | 0.00 | 0.238668E+12 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.137261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.303146E+09 | 0.382943E+11 | 0.00 | 0.103891E+09 | 0.401138E+09 | 0.00 | 0.504310E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.331334E+10 | 0.216799E+10 | 0.00 | 52980958.94 | 0.00 | 0.00 | 0.274935E+11 | 0.00 | 0.48 |
February | 0.218286E+10 | 0.251918E+10 | 0.00 | 45041773.99 | 38453681.61 | 0.00 | 0.174113E+11 | 0.00 | 0.48 |
March | 0.188129E+10 | 0.391879E+10 | 0.00 | 64028606.53 | 84251367.34 | 0.00 | 0.240264E+11 | 0.00 | 0.54 |
April | 0.252364E+10 | 0.628254E+10 | 0.00 | 34363966.95 | 81447912.09 | 0.00 | 0.681554E+10 | 0.00 | 0.48 |
May | 0.00 | 0.133330E+11 | 0.00 | 0.00 | 0.143634E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.137733E+11 | 0.00 | 0.00 | 0.147551E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.158082E+11 | 0.00 | 0.00 | 0.253020E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 3729338.07 | 0.165282E+11 | 0.00 | 0.00 | 0.160481E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.162519E+11 | 0.00 | 0.00 | 0.284737E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.428058E+09 | 0.105745E+11 | 0.00 | 20475087.33 | 0.176487E+09 | 0.00 | 0.544054E+10 | 0.00 | 0.35 |
November | 0.235766E+10 | 0.506368E+10 | 0.00 | 59715223.67 | 48495853.95 | 0.00 | 0.167325E+11 | 0.00 | 0.55 |
December | 0.264316E+10 | 0.433178E+10 | 0.00 | 67742139.85 | 79244220.45 | 0.00 | 0.280454E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.153337E+11 | 0.110553E+12 | 0.00 | 0.344348E+09 | 0.149781E+10 | 0.00 | 0.125965E+12 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.216799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.331334E+10 | 0.165282E+11 | 0.00 | 67742139.85 | 0.284737E+09 | 0.00 | 0.280454E+11 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137501E+12 | 0.147353E+11 | 0.00 | 0.145599E+09 | 0.649543E+10 | 0.00 | 0.972734E+11 | 0.00 | 0.38 |
February | 0.797423E+11 | 0.193492E+11 | 0.00 | 0.140188E+09 | 0.558424E+10 | 0.00 | 0.599281E+11 | 0.00 | 0.39 |
March | 0.760434E+11 | 0.277415E+11 | 0.00 | 0.246102E+09 | 0.954273E+10 | 0.00 | 0.108057E+12 | 0.00 | 0.43 |
April | 0.190404E+11 | 0.530366E+11 | 0.00 | 0.171810E+09 | 0.946925E+10 | 0.00 | 0.374336E+11 | 0.00 | 0.38 |
May | 0.00 | 0.124413E+12 | 0.00 | 0.00 | 0.768651E+10 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.130463E+12 | 0.00 | 682600.71 | 0.721449E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.147184E+12 | 0.00 | 0.00 | 0.119656E+11 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.155375E+12 | 0.00 | 0.00 | 0.725555E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.147422E+12 | 0.00 | 0.00 | 0.132138E+11 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.103345E+11 | 0.962385E+11 | 0.00 | 0.114403E+09 | 0.810907E+10 | 0.00 | 0.358751E+11 | 0.00 | 0.32 |
November | 0.523581E+11 | 0.420105E+11 | 0.00 | 0.258350E+09 | 0.510974E+10 | 0.00 | 0.753669E+11 | 0.00 | 0.41 |
December | 0.104229E+12 | 0.351821E+11 | 0.00 | 0.184422E+09 | 0.702190E+10 | 0.00 | 0.903655E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.479250E+12 | 0.993150E+12 | 0.00 | 0.126156E+10 | 0.986683E+11 | 0.00 | 0.504299E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.147353E+11 | 0.00 | 0.00 | 0.510974E+10 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.137501E+12 | 0.155375E+12 | 0.00 | 0.258350E+09 | 0.132138E+11 | 0.00 | 0.108057E+12 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179900E+11 | 0.148530E+10 | 0.00 | 3340849.49 | 0.851250E+09 | 0.227116E+09 | 0.205106E+10 | 0.00 | 0.38 |
February | 0.101349E+11 | 0.194358E+10 | 0.00 | 4617685.32 | 0.807287E+09 | 0.156524E+09 | 0.221711E+10 | 0.00 | 0.37 |
March | 0.112458E+11 | 0.303327E+10 | 0.00 | 9440020.08 | 0.984611E+09 | 64703123.29 | 0.477005E+10 | 0.00 | 0.41 |
April | 0.243013E+10 | 0.552244E+10 | 0.00 | 12106834.66 | 0.765952E+09 | 0.00 | 0.279083E+10 | 0.00 | 0.36 |
May | 0.00 | 0.126251E+11 | 0.00 | 0.00 | 0.288498E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.133054E+11 | 0.00 | 0.00 | 0.143713E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.153909E+11 | 0.00 | 0.00 | 0.382464E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.157726E+11 | 0.00 | 0.00 | 0.235273E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.151516E+11 | 0.00 | 0.00 | 0.687665E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.139828E+10 | 0.971577E+10 | 0.00 | 8236588.95 | 0.430486E+09 | 0.00 | 0.253266E+10 | 0.00 | 0.31 |
November | 0.708161E+10 | 0.370565E+10 | 0.00 | 11009898.82 | 0.107846E+10 | 0.00 | 0.400638E+10 | 0.00 | 0.40 |
December | 0.152414E+11 | 0.282634E+10 | 0.00 | 2245379.83 | 0.134608E+10 | 0.112736E+09 | 0.119773E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.655221E+11 | 0.100478E+12 | 0.00 | 50997257.15 | 0.800174E+10 | 0.561079E+09 | 0.195658E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.148530E+10 | 0.00 | 0.00 | 0.143713E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.179900E+11 | 0.157726E+11 | 0.00 | 12106834.66 | 0.134608E+10 | 0.227116E+09 | 0.477005E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259137E+10 | 0.273348E+09 | 0.00 | 898726.95 | 8358989.42 | 0.00 | 0.554289E+09 | 0.00 | 0.40 |
February | 0.142030E+10 | 0.334583E+09 | 0.00 | 1615962.84 | 6661036.36 | 0.00 | 0.600002E+09 | 0.00 | 0.42 |
March | 0.140439E+10 | 0.576949E+09 | 0.00 | 3149689.26 | 10886070.15 | 0.00 | 0.120754E+10 | 0.00 | 0.49 |
April | 0.510685E+09 | 0.100051E+10 | 0.00 | 2717736.89 | 10598477.31 | 0.00 | 0.530702E+09 | 0.00 | 0.52 |
May | 0.00 | 0.257785E+10 | 0.00 | 0.00 | 18025213.15 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.294916E+10 | 0.00 | 0.00 | 18516742.35 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.332161E+10 | 0.00 | 0.00 | 31752453.57 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 468008.25 | 0.319692E+10 | 0.00 | 0.00 | 20139408.99 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.280441E+10 | 0.00 | 0.00 | 35732743.60 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.219285E+09 | 0.183201E+10 | 0.00 | 1556762.49 | 22147996.51 | 0.00 | 0.436409E+09 | 0.00 | 0.42 |
November | 0.967399E+09 | 0.708396E+09 | 0.00 | 3447661.56 | 6085921.79 | 0.00 | 0.977262E+09 | 0.00 | 0.49 |
December | 0.193304E+10 | 0.566110E+09 | 0.00 | 2068654.26 | 11618608.16 | 0.00 | 0.914036E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.904693E+10 | 0.201419E+11 | 0.00 | 15455194.26 | 0.200524E+09 | 0.00 | 0.522024E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.273348E+09 | 0.00 | 0.00 | 6085921.79 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.259137E+10 | 0.332161E+10 | 0.00 | 3447661.56 | 35732743.60 | 0.00 | 0.120754E+10 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109146E+10 | 0.202576E+09 | 0.00 | 2901371.30 | 9986497.59 | 167798.55 | 0.137815E+10 | 0.00 | 0.49 |
February | 0.690589E+09 | 0.273294E+09 | 0.00 | 2667517.13 | 4177037.53 | 0.00 | 0.957263E+09 | 0.00 | 0.53 |
March | 0.777800E+09 | 0.463976E+09 | 0.00 | 4005343.35 | 11044352.45 | 0.00 | 0.144501E+10 | 0.00 | 0.66 |
April | 0.311370E+09 | 0.810340E+09 | 0.00 | 2897401.94 | 12524015.42 | 0.00 | 0.675704E+09 | 0.00 | 0.68 |
May | 0.00 | 0.213448E+10 | 0.00 | 0.00 | 11609419.40 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.00 | 0.231510E+10 | 0.00 | 0.00 | 11925996.43 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.255833E+10 | 0.00 | 0.00 | 20450662.48 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 301428.01 | 0.230211E+10 | 0.00 | 0.00 | 12971100.17 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.216745E+10 | 0.00 | 0.00 | 23014230.30 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.131883E+09 | 0.145399E+10 | 0.00 | 1637861.72 | 14264762.25 | 0.00 | 0.388942E+09 | 0.00 | 0.51 |
November | 0.538460E+09 | 0.520143E+09 | 0.00 | 3727987.90 | 8361842.89 | 0.00 | 0.109418E+10 | 0.00 | 0.61 |
December | 0.118915E+10 | 0.355254E+09 | 0.00 | 2483849.95 | 19001967.47 | 165843.42 | 0.962970E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.473101E+10 | 0.155570E+11 | 0.00 | 20321333.29 | 0.159332E+09 | 333641.97 | 0.690222E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.202576E+09 | 0.00 | 0.00 | 4177037.53 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.118915E+10 | 0.255833E+10 | 0.00 | 4005343.35 | 23014230.30 | 167798.55 | 0.144501E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132387E+10 | 0.449024E+09 | 0.00 | 11729126.08 | 4555675.48 | 251591.26 | 0.486124E+10 | 0.00 | 0.83 |
February | 0.855198E+09 | 0.670817E+09 | 0.00 | 7434530.75 | 4808523.95 | 359245.62 | 0.266733E+10 | 0.00 | 0.77 |
March | 0.123240E+10 | 0.794037E+09 | 0.00 | 6602279.80 | 11340093.87 | 0.00 | 0.230513E+10 | 0.00 | 0.72 |
April | 0.516548E+09 | 0.118498E+10 | 0.00 | 3329160.85 | 10645534.55 | 0.00 | 0.637030E+09 | 0.00 | 0.62 |
May | 0.00 | 0.259674E+10 | 0.00 | 0.00 | 18064677.17 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.281197E+10 | 0.00 | 0.00 | 18557282.51 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.327109E+10 | 0.00 | 0.00 | 31821971.72 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 469032.90 | 0.347900E+10 | 0.00 | 0.00 | 20183501.78 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.344450E+10 | 0.00 | 0.00 | 35810976.11 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.165058E+09 | 0.272666E+10 | 0.00 | 3382213.02 | 18837691.38 | 0.00 | 0.755477E+09 | 0.00 | 0.65 |
November | 0.493676E+09 | 0.116971E+10 | 0.00 | 13565523.80 | 6099246.18 | 0.00 | 0.317088E+10 | 0.00 | 0.96 |
December | 0.115696E+10 | 0.942643E+09 | 0.00 | 12926278.40 | 9966419.17 | 0.00 | 0.416339E+10 | 0.00 | 0.89 |
Annual Sum or Average | 0.574418E+10 | 0.235412E+11 | 0.00 | 58969112.69 | 0.190692E+09 | 610836.88 | 0.185605E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.449024E+09 | 0.00 | 0.00 | 4555675.48 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.132387E+10 | 0.347900E+10 | 0.00 | 13565523.80 | 35810976.11 | 359245.62 | 0.486124E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.837195E+09 | 0.331406E+09 | 0.00 | 4888699.22 | 0.00 | 0.00 | 0.221541E+10 | 0.00 | 0.67 |
February | 0.289817E+09 | 0.470666E+09 | 0.00 | 5841487.51 | 1203395.71 | 0.00 | 0.197069E+10 | 0.00 | 0.82 |
March | 0.164371E+09 | 0.764935E+09 | 0.00 | 9465192.95 | 1779770.77 | 0.00 | 0.329612E+10 | 0.00 | 1.08 |
April | 0.107404E+09 | 0.152915E+10 | 0.00 | 8389677.34 | 1144500.00 | 0.00 | 0.131518E+10 | 0.00 | 1.18 |
May | 0.00 | 0.257561E+10 | 0.00 | 0.00 | 7023051.86 | 0.00 | 0.00 | 0.00 | 0.64 |
June | 0.00 | 0.309564E+10 | 0.00 | 0.00 | 2440331.05 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.00 | 0.369633E+10 | 0.00 | 0.00 | 2859992.97 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 138373.11 | 0.404983E+10 | 0.00 | 6923.56 | 2326074.78 | 0.00 | 196662.74 | 0.00 | 0.81 |
September | 0.00 | 0.294449E+10 | 0.00 | 0.00 | 10809607.16 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 32861360.64 | 0.212948E+10 | 0.00 | 2974651.93 | 10545376.39 | 0.00 | 0.733147E+09 | 0.00 | 0.77 |
November | 0.160390E+09 | 0.948527E+09 | 0.00 | 9455550.95 | 282855.07 | 0.00 | 0.236922E+10 | 0.00 | 1.05 |
December | 0.178585E+09 | 0.845958E+09 | 0.00 | 10092701.48 | 2983944.23 | 0.00 | 0.370696E+10 | 0.00 | 1.01 |
Annual Sum or Average | 0.177076E+10 | 0.233820E+11 | 0.00 | 51114884.94 | 43398899.99 | 0.00 | 0.156069E+11 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 0.331406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.837195E+09 | 0.404983E+10 | 0.00 | 10092701.48 | 10809607.16 | 0.00 | 0.370696E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235917E+11 | 0.145505E+10 | 0.00 | 182325.36 | 0.125237E+10 | 0.500413E+10 | 65513268.39 | 0.00 | 0.38 |
February | 0.144055E+11 | 0.209719E+10 | 0.00 | 1177972.75 | 0.110473E+10 | 0.188935E+10 | 0.752006E+09 | 0.00 | 0.38 |
March | 0.181449E+11 | 0.401967E+10 | 0.00 | 4330635.37 | 0.111058E+10 | 0.180990E+10 | 0.155103E+10 | 0.00 | 0.41 |
April | 0.466391E+10 | 0.838371E+10 | 0.00 | 11683973.27 | 0.100498E+10 | 0.00 | 0.193699E+10 | 0.00 | 0.41 |
May | 0.00 | 0.254728E+11 | 0.00 | 0.00 | 0.180602E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 28332.72 | 0.298852E+11 | 0.00 | 0.00 | 0.229031E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.343453E+11 | 0.00 | 0.00 | 0.322854E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.325498E+11 | 0.00 | 0.00 | 0.205161E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.269374E+11 | 0.00 | 0.00 | 0.583964E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.310856E+10 | 0.173391E+11 | 0.00 | 8142858.70 | 0.530967E+09 | 0.00 | 0.225402E+10 | 0.00 | 0.38 |
November | 0.128394E+11 | 0.530238E+10 | 0.00 | 7857387.58 | 0.110876E+10 | 11065106.97 | 0.195245E+10 | 0.00 | 0.40 |
December | 0.205229E+11 | 0.358899E+10 | 0.00 | 656236.77 | 0.178484E+10 | 0.288376E+10 | 0.173179E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.972770E+11 | 0.191377E+12 | 0.00 | 34031389.80 | 0.941883E+10 | 0.115982E+11 | 0.868519E+10 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.145505E+10 | 0.00 | 0.00 | 0.180602E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.235917E+11 | 0.343453E+11 | 0.00 | 11683973.27 | 0.178484E+10 | 0.500413E+10 | 0.225402E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100719E+11 | 0.154979E+10 | 0.00 | 9179005.97 | 0.485234E+09 | 0.184472E+10 | 0.500500E+10 | 0.00 | 0.35 |
February | 0.611949E+10 | 0.259262E+10 | 0.00 | 12151584.05 | 0.271797E+09 | 0.617565E+09 | 0.409768E+10 | 0.00 | 0.42 |
March | 0.709667E+10 | 0.456010E+10 | 0.00 | 24296567.76 | 0.318391E+09 | 0.713317E+09 | 0.805574E+10 | 0.00 | 0.55 |
April | 0.187361E+10 | 0.891095E+10 | 0.00 | 23744084.14 | 0.211711E+09 | 0.00 | 0.545174E+10 | 0.00 | 0.63 |
May | 0.00 | 0.224972E+11 | 0.00 | 0.00 | 0.116375E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 18256.88 | 0.254226E+11 | 0.00 | 0.00 | 0.131514E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.294115E+11 | 0.00 | 0.00 | 0.208039E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.272647E+11 | 0.00 | 0.00 | 0.132200E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.222391E+11 | 0.00 | 0.00 | 0.258391E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.145917E+10 | 0.153799E+11 | 0.00 | 12174539.02 | 0.229297E+09 | 0.00 | 0.272782E+10 | 0.00 | 0.51 |
November | 0.537437E+10 | 0.499698E+10 | 0.00 | 22178265.73 | 0.388396E+09 | 0.00 | 0.598278E+10 | 0.00 | 0.49 |
December | 0.946793E+10 | 0.311199E+10 | 0.00 | 9763215.18 | 0.626211E+09 | 0.126523E+10 | 0.333569E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.414632E+11 | 0.167938E+12 | 0.00 | 0.113487E+09 | 0.337756E+10 | 0.444084E+10 | 0.346565E+11 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.154979E+10 | 0.00 | 0.00 | 0.116375E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.100719E+11 | 0.294115E+11 | 0.00 | 24296567.76 | 0.626211E+09 | 0.184472E+10 | 0.805574E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122103E+11 | 0.474108E+10 | 0.00 | 0.103764E+09 | 0.329958E+09 | 0.120977E+10 | 0.411711E+11 | 0.00 | 0.78 |
February | 0.805554E+10 | 0.764586E+10 | 0.00 | 62115239.28 | 0.107812E+09 | 0.443262E+09 | 0.206179E+11 | 0.00 | 0.74 |
March | 0.127657E+11 | 0.741049E+10 | 0.00 | 47853416.54 | 0.463322E+09 | 0.909282E+09 | 0.154812E+11 | 0.00 | 0.65 |
April | 0.386745E+10 | 0.112101E+11 | 0.00 | 23835099.22 | 0.564864E+09 | 0.00 | 0.416930E+10 | 0.00 | 0.53 |
May | 0.00 | 0.258952E+11 | 0.00 | 0.00 | 0.180218E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 28272.48 | 0.283038E+11 | 0.00 | 0.00 | 0.228545E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.338797E+11 | 0.00 | 0.00 | 0.322168E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.366419E+11 | 0.00 | 0.00 | 0.204725E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.352448E+11 | 0.00 | 0.00 | 0.434337E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.204512E+10 | 0.290165E+11 | 0.00 | 27365934.12 | 0.186953E+09 | 0.00 | 0.584306E+10 | 0.00 | 0.67 |
November | 0.512787E+10 | 0.121184E+11 | 0.00 | 0.127277E+09 | 0.206472E+09 | 0.00 | 0.247988E+11 | 0.00 | 0.87 |
December | 0.116062E+11 | 0.989876E+10 | 0.00 | 0.108691E+09 | 0.372990E+09 | 0.906985E+09 | 0.295985E+11 | 0.00 | 0.78 |
Annual Sum or Average | 0.556783E+11 | 0.242007E+12 | 0.00 | 0.500902E+09 | 0.360236E+10 | 0.346930E+10 | 0.141680E+12 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.474108E+10 | 0.00 | 0.00 | 0.107812E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.127657E+11 | 0.366419E+11 | 0.00 | 0.127277E+09 | 0.564864E+09 | 0.120977E+10 | 0.411711E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128243E+11 | 0.252833E+10 | 0.00 | 14609541.38 | 0.185623E+09 | 0.139306E+10 | 0.717104E+10 | 0.00 | 0.47 |
February | 0.758853E+10 | 0.356455E+10 | 0.00 | 14878979.79 | 0.137325E+09 | 0.413856E+09 | 0.520316E+10 | 0.00 | 0.52 |
March | 0.910817E+10 | 0.471605E+10 | 0.00 | 26102083.25 | 0.137197E+09 | 0.355225E+09 | 0.890036E+10 | 0.00 | 0.62 |
April | 0.167046E+10 | 0.104064E+11 | 0.00 | 31507661.14 | 0.109145E+09 | 0.00 | 0.448127E+10 | 0.00 | 0.70 |
May | 0.00 | 0.223877E+11 | 0.00 | 0.00 | 76840449.15 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.259989E+11 | 0.00 | 33484.26 | 37833236.90 | 0.00 | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.298653E+11 | 0.00 | 0.00 | 64456788.75 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.305120E+11 | 0.00 | 0.00 | 63120763.01 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.247663E+11 | 0.00 | 0.00 | 0.127673E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.144049E+10 | 0.169485E+11 | 0.00 | 12702806.34 | 0.105453E+09 | 0.00 | 0.303233E+10 | 0.00 | 0.58 |
November | 0.606305E+10 | 0.615642E+10 | 0.00 | 25938581.53 | 25475545.41 | 0.00 | 0.577575E+10 | 0.00 | 0.55 |
December | 0.121870E+11 | 0.497817E+10 | 0.00 | 14483236.76 | 0.207484E+09 | 0.612102E+09 | 0.411763E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.508820E+11 | 0.182829E+12 | 0.00 | 0.140256E+09 | 0.127763E+10 | 0.277425E+10 | 0.386815E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.252833E+10 | 0.00 | 0.00 | 25475545.41 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.128243E+11 | 0.305120E+11 | 0.00 | 31507661.14 | 0.207484E+09 | 0.139306E+10 | 0.890036E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153755E+10 | 0.154571E+09 | 0.00 | 14144.00 | 0.149562E+09 | 0.106695E+10 | 3964973.90 | 0.00 | 0.38 |
February | 0.100488E+10 | 0.216688E+09 | 0.00 | 66961.59 | 0.142692E+09 | 0.532342E+09 | 53780070.92 | 0.00 | 0.38 |
March | 0.150547E+10 | 0.430018E+09 | 0.00 | 354585.64 | 0.127489E+09 | 0.372410E+09 | 0.124478E+09 | 0.00 | 0.42 |
April | 0.432691E+09 | 0.826354E+09 | 0.00 | 1148382.84 | 0.127639E+09 | 2161696.90 | 0.218746E+09 | 0.00 | 0.41 |
May | 0.00 | 0.247817E+10 | 0.00 | 0.00 | 18252978.29 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.288789E+10 | 0.00 | 0.00 | 22752665.71 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.336211E+10 | 0.00 | 0.00 | 37057661.83 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.317042E+10 | 0.00 | 0.00 | 35427720.29 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.261191E+10 | 0.00 | 0.00 | 0.117036E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.277465E+09 | 0.167405E+10 | 0.00 | 712592.86 | 65974312.69 | 17422206.79 | 0.186321E+09 | 0.00 | 0.38 |
November | 0.110200E+10 | 0.490681E+09 | 1342361.91 | 481211.49 | 0.156994E+09 | 0.106911E+09 | 0.157462E+09 | 8857.44 | 0.40 |
December | 0.135374E+10 | 0.322810E+09 | 591530.72 | 28807.49 | 0.215471E+09 | 0.754235E+09 | 13655102.29 | 9217.47 | 0.37 |
Annual Sum or Average | 0.721380E+10 | 0.186257E+11 | 1933892.62 | 2806685.91 | 0.121635E+10 | 0.285243E+10 | 0.758407E+09 | 18074.92 | 0.40 |
Minimum of Months | 0.00 | 0.154571E+09 | 0.00 | 0.00 | 18252978.29 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.153755E+10 | 0.336211E+10 | 1342361.91 | 1148382.84 | 0.215471E+09 | 0.106695E+10 | 0.218746E+09 | 9217.47 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119616E+10 | 0.190089E+09 | 0.00 | 172595.22 | 59922983.09 | 0.358785E+09 | 0.126588E+09 | 0.00 | 0.40 |
February | 0.649737E+09 | 0.291959E+09 | 0.00 | 742030.16 | 46961940.67 | 0.168912E+09 | 0.247971E+09 | 0.00 | 0.45 |
March | 0.687687E+09 | 0.527179E+09 | 0.00 | 2019143.94 | 39228308.66 | 0.185962E+09 | 0.659601E+09 | 0.00 | 0.57 |
April | 0.168276E+09 | 0.929583E+09 | 0.00 | 2358565.93 | 37892794.65 | 0.00 | 0.566381E+09 | 0.00 | 0.65 |
May | 0.00 | 0.224102E+10 | 0.00 | 0.00 | 11763518.50 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.252128E+10 | 0.00 | 0.00 | 13807433.57 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 0.00 | 0.296996E+10 | 0.00 | 0.00 | 22729461.77 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.274266E+10 | 0.00 | 0.00 | 21826044.01 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.228575E+10 | 0.00 | 0.00 | 36820698.05 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.127283E+09 | 0.155572E+10 | 0.00 | 1118120.36 | 27102554.13 | 10277485.00 | 0.248576E+09 | 0.00 | 0.53 |
November | 0.516561E+09 | 0.513037E+09 | 182923.76 | 1631297.36 | 62394386.56 | 27320161.93 | 0.471045E+09 | 315.02 | 0.50 |
December | 0.938546E+09 | 0.309188E+09 | 0.00 | 441992.57 | 95393552.20 | 0.320760E+09 | 0.134702E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.428425E+10 | 0.170774E+11 | 182923.76 | 8483745.54 | 0.475844E+09 | 0.107202E+10 | 0.245486E+10 | 315.02 | 0.53 |
Minimum of Months | 0.00 | 0.190089E+09 | 0.00 | 0.00 | 11763518.50 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.119616E+10 | 0.296996E+10 | 182923.76 | 2358565.93 | 95393552.20 | 0.358785E+09 | 0.659601E+09 | 315.02 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.996061E+09 | 0.544124E+09 | 0.00 | 7738205.63 | 46641890.92 | 0.344881E+09 | 0.305832E+10 | 0.00 | 0.70 |
February | 0.669993E+09 | 0.813559E+09 | 0.00 | 4689733.92 | 30406313.51 | 0.172889E+09 | 0.167909E+10 | 0.00 | 0.68 |
March | 0.104076E+10 | 0.796372E+09 | 0.00 | 4077950.64 | 64618107.88 | 0.271938E+09 | 0.140889E+10 | 0.00 | 0.62 |
April | 0.347045E+09 | 0.108484E+10 | 0.00 | 2381962.46 | 93035525.34 | 0.00 | 0.476908E+09 | 0.00 | 0.53 |
May | 0.00 | 0.251511E+10 | 0.00 | 0.00 | 18238287.29 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.273493E+10 | 0.00 | 0.00 | 29099348.46 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.330518E+10 | 0.00 | 0.00 | 45044352.46 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.353296E+10 | 0.00 | 0.00 | 35399206.10 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.342696E+10 | 0.00 | 0.00 | 65916373.75 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.190556E+09 | 0.276902E+10 | 0.00 | 2503799.77 | 22050890.35 | 0.00 | 0.530579E+09 | 0.00 | 0.65 |
November | 0.489406E+09 | 0.118009E+10 | 0.00 | 10174716.22 | 51838491.54 | 16434506.10 | 0.230077E+10 | 0.00 | 0.86 |
December | 0.917867E+09 | 0.928839E+09 | 0.00 | 8480335.35 | 76394728.36 | 0.298894E+09 | 0.232122E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.465169E+10 | 0.236320E+11 | 0.00 | 40046704.00 | 0.578684E+09 | 0.110504E+10 | 0.117758E+11 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.544124E+09 | 0.00 | 0.00 | 18238287.29 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.104076E+10 | 0.353296E+10 | 0.00 | 10174716.22 | 93035525.34 | 0.344881E+09 | 0.305832E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100554E+10 | 0.273799E+09 | 0.00 | 1040683.67 | 34315827.22 | 0.331407E+09 | 0.516062E+09 | 0.00 | 0.46 |
February | 0.591595E+09 | 0.370816E+09 | 0.00 | 1170872.37 | 34917261.45 | 0.152684E+09 | 0.457965E+09 | 0.00 | 0.51 |
March | 0.761131E+09 | 0.491105E+09 | 0.00 | 2361452.46 | 33637266.58 | 0.130951E+09 | 0.865984E+09 | 0.00 | 0.61 |
April | 0.165529E+09 | 0.101819E+10 | 0.00 | 3008673.62 | 22724898.79 | 0.00 | 0.489493E+09 | 0.00 | 0.68 |
May | 0.00 | 0.212953E+10 | 0.00 | 0.00 | 6858173.53 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.244624E+10 | 0.00 | 0.00 | 4575514.16 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.286784E+10 | 0.00 | 0.00 | 5615519.24 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.291915E+10 | 0.00 | 0.00 | 7571380.27 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.241502E+10 | 0.00 | 0.00 | 15110996.33 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.134346E+09 | 0.161472E+10 | 0.00 | 1162426.75 | 13194995.20 | 0.00 | 0.277117E+09 | 0.00 | 0.57 |
November | 0.555527E+09 | 0.588459E+09 | 0.00 | 2091253.94 | 26015229.81 | 21424928.14 | 0.575954E+09 | 0.00 | 0.57 |
December | 0.920806E+09 | 0.463170E+09 | 232662.58 | 1124364.99 | 46087970.14 | 0.227516E+09 | 0.369356E+09 | 802.74 | 0.48 |
Annual Sum or Average | 0.413447E+10 | 0.175980E+11 | 232662.58 | 11959727.81 | 0.250625E+09 | 0.863984E+09 | 0.355193E+10 | 802.74 | 0.56 |
Minimum of Months | 0.00 | 0.273799E+09 | 0.00 | 0.00 | 4575514.16 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.100554E+10 | 0.291915E+10 | 232662.58 | 3008673.62 | 46087970.14 | 0.331407E+09 | 0.865984E+09 | 802.74 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 30983105.82 | 0.00 | 2869269.68 | 0.00 | 0.00 | 0.326060E+09 | 0.00 | 0.28 |
February | 0.00 | 48505141.51 | 0.00 | 4874561.50 | 0.00 | 0.00 | 0.174295E+09 | 0.00 | 0.29 |
March | 0.00 | 83354432.08 | 0.00 | 9328562.03 | 0.00 | 0.00 | 0.218732E+09 | 0.00 | 0.31 |
April | 0.00 | 0.159563E+09 | 0.00 | 5193842.58 | 0.00 | 0.00 | 49767031.09 | 0.00 | 0.29 |
May | 0.00 | 0.419999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.518933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.601516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.606859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.425161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.348101E+09 | 0.00 | 1650267.42 | 0.00 | 0.00 | 44681357.65 | 0.00 | 0.28 |
November | 0.00 | 0.123863E+09 | 0.00 | 7382482.06 | 0.00 | 0.00 | 0.123885E+09 | 0.00 | 0.28 |
December | 0.00 | 90559953.86 | 0.00 | 12252749.18 | 0.00 | 0.00 | 0.238931E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.345740E+10 | 0.00 | 43551734.44 | 0.00 | 0.00 | 0.117635E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 30983105.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.606859E+09 | 0.00 | 12252749.18 | 0.00 | 0.00 | 0.326060E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.288631E+09 | 0.00 | 18552228.89 | 0.00 | 0.00 | 0.327919E+10 | 0.00 | 0.28 |
February | 0.00 | 0.476778E+09 | 0.00 | 41124985.93 | 0.00 | 0.00 | 0.175270E+10 | 0.00 | 0.29 |
March | 0.00 | 0.830614E+09 | 0.00 | 83588511.04 | 0.00 | 0.00 | 0.219364E+10 | 0.00 | 0.31 |
April | 0.00 | 0.159687E+10 | 0.00 | 48723371.65 | 0.00 | 0.00 | 0.498911E+09 | 0.00 | 0.29 |
May | 0.00 | 0.415389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.517159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.600650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.607670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.418905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.346453E+10 | 0.00 | 14916666.35 | 0.00 | 0.00 | 0.447485E+09 | 0.00 | 0.28 |
November | 0.00 | 0.123538E+10 | 0.00 | 67063013.88 | 0.00 | 0.00 | 0.124311E+10 | 0.00 | 0.28 |
December | 0.00 | 0.905075E+09 | 0.00 | 0.110203E+09 | 0.00 | 0.00 | 0.239662E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.343956E+11 | 0.00 | 0.384171E+09 | 0.00 | 0.00 | 0.118117E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.288631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.607670E+10 | 0.00 | 0.110203E+09 | 0.00 | 0.00 | 0.327919E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73918065.87 | 28487667.51 | 0.00 | 1117397.74 | 0.00 | 0.00 | 0.254753E+09 | 0.00 | 0.28 |
February | 0.00 | 47402806.33 | 0.00 | 3658636.20 | 0.00 | 0.00 | 0.176330E+09 | 0.00 | 0.29 |
March | 0.00 | 82907161.24 | 0.00 | 7886856.72 | 0.00 | 0.00 | 0.220185E+09 | 0.00 | 0.31 |
April | 0.00 | 0.159463E+09 | 0.00 | 4798667.41 | 0.00 | 0.00 | 50091015.71 | 0.00 | 0.29 |
May | 0.00 | 0.417541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.517788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.600669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.609521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.420576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.346570E+09 | 0.00 | 1416678.57 | 0.00 | 0.00 | 44920194.79 | 0.00 | 0.28 |
November | 0.00 | 0.123306E+09 | 0.00 | 6378102.41 | 0.00 | 0.00 | 0.124962E+09 | 0.00 | 0.28 |
December | 0.00 | 90281077.89 | 0.00 | 10343956.78 | 0.00 | 0.00 | 0.240682E+09 | 0.00 | 0.28 |
Annual Sum or Average | 73918065.87 | 0.344451E+10 | 0.00 | 35600295.83 | 0.00 | 0.00 | 0.111192E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 28487667.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 73918065.87 | 0.609521E+09 | 0.00 | 10343956.78 | 0.00 | 0.00 | 0.254753E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.423039E+09 | 0.00 | 0.522740E+09 | 0.00 | 0.00 | 0.345920E+12 | 0.00 | 15.61 |
February | 0.00 | 0.885337E+09 | 0.00 | 0.740973E+09 | 0.00 | 0.00 | 0.431602E+12 | 0.00 | 21.44 |
March | 0.00 | 0.177769E+10 | 0.00 | 0.109099E+10 | 0.00 | 0.00 | 0.538634E+12 | 0.00 | 25.12 |
April | 0.00 | 0.308551E+10 | 0.00 | 0.108268E+10 | 0.00 | 0.00 | 0.201126E+12 | 0.00 | 17.33 |
May | 0.00 | 0.994340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.116470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.132558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.112746E+11 | 0.00 | 4024830.50 | 0.00 | 0.00 | 77861455.53 | 0.00 | 0.40 |
September | 0.00 | 0.101565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.779559E+10 | 0.00 | 0.267179E+09 | 0.00 | 0.00 | 0.123253E+12 | 0.00 | 8.36 |
November | 0.00 | 0.270032E+10 | 0.00 | 0.114000E+10 | 0.00 | 0.00 | 0.432973E+12 | 0.00 | 25.18 |
December | 0.00 | 0.182445E+10 | 0.00 | 0.171273E+10 | 0.00 | 0.00 | 0.650157E+12 | 0.00 | 27.11 |
Annual Sum or Average | 0.00 | 0.747693E+11 | 0.00 | 0.656131E+10 | 0.00 | 0.00 | 0.272374E+13 | 0.00 | 11.75 |
Minimum of Months | 0.00 | 0.423039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.132558E+11 | 0.00 | 0.171273E+10 | 0.00 | 0.00 | 0.650157E+12 | 0.00 | 27.11 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:55
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.400076E+12 | 0.939272E+10 | 0.00 | 0.178873E+13 | 0.644120E+12 |
February | 0.430415E+12 | 0.722136E+10 | 0.00 | 0.143866E+13 | 0.105544E+13 |
March | 0.494733E+12 | 0.641207E+10 | 0.00 | 0.161315E+13 | 0.159003E+13 |
April | 0.554660E+12 | -382918631.3 | 0.00 | 0.560390E+12 | 0.282085E+13 |
May | 0.553913E+12 | -0.134217E+11 | 0.00 | -0.688243E+12 | 0.281283E+13 |
June | 0.551801E+12 | -0.108468E+11 | 0.00 | -0.800599E+12 | 0.324665E+13 |
July | 0.570055E+12 | -0.183162E+11 | 0.00 | -0.904147E+12 | 0.380245E+13 |
August | 0.525011E+12 | -0.175923E+11 | 0.00 | -0.893690E+12 | 0.427833E+13 |
September | 0.452611E+12 | -0.168134E+11 | 0.00 | -0.698747E+12 | 0.278364E+13 |
October | 0.454583E+12 | -0.104715E+11 | 0.00 | -0.504640E+11 | 0.274201E+13 |
November | 0.348252E+12 | 0.327180E+10 | 0.00 | 0.134112E+13 | 0.187721E+13 |
December | 0.358796E+12 | 0.759176E+10 | 0.00 | 0.193662E+13 | 0.172669E+13 |
Annual Sum or Average | 0.569490E+13 | -0.539551E+11 | 0.00 | 0.464277E+13 | 0.293802E+14 |
Minimum of Months | 0.348252E+12 | -0.183162E+11 | 0.00 | -0.904147E+12 | 0.644120E+12 |
Maximum of Months | 0.570055E+12 | 0.939272E+10 | 0.00 | 0.193662E+13 | 0.427833E+13 |