Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:56:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 24201.89 | 522.49 | 522.49 |
Net Site Energy | 23602.13 | 509.54 | 509.54 |
Total Source Energy | 75067.90 | 1620.62 | 1620.62 |
Net Source Energy | 73168.48 | 1579.62 | 1579.62 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 43.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1729.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1816.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2153.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 360.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 765.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3716.69 |
Humidification | 475.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.94 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 714.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 23443.62 | 758.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6173.80 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 43.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1729.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1816.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2153.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 360.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 765.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3716.69 |
Humidification | General | 475.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.94 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 714.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 43.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1729.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1816.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2153.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 360.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 765.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3716.69 |
Humidification | Unassigned | 475.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.94 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 714.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 44.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.41 | 16.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 506.12 | 16.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 44.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.41 | 16.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 506.12 | 16.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 625.782 | 2.67 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -26.03 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 599.754 | 2.56 |
Electricity Coming From Utility | 22843.862 | 97.44 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 22843.862 | 97.44 |
Total On-Site and Utility Electric Sources | 23443.616 | 100.00 |
Total Electricity End Uses | 23443.616 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6173.80 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6173.80 | 100.00 |
Total Water End Uses | 6173.80 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 468.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5897.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:09 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 16-OCT-11:09 |
Heating | 0.00 | 353777.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 339402.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 154688.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52594.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 169796.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34713.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 70388.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30625.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1599954.87 | 384402.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 353777.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 339402.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 154688.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3364.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 169796.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 34713.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 70388.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 30625.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 47.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5477.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5751.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6820.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1140.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2425.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1506.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 774.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 74245.93 | 821.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 124.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 32.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1602.88 | 17.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 124.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 32.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1602.88 | 17.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 4.78 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.472001 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.51 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.458215 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.55 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.23 | 0.363435 | 0.309000 | 1.62 | 0.969161 | 0.500000 | 0.001048 | 0.000350 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.09 | 0.387499 | 0.329000 | 16.15 | 1.00 | 0.500000 | 0.000983 | 0.007257 | 16.15 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.77 | 0.398371 | 0.339000 | 1.62 | 1.00 | 0.500000 | 0.000956 | 0.001319 | 1.82 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.819984 | 0.291250 | 0.248000 | 0.203356 | 0.776667 | 0.500000 | 0.001308 | 0.000112 | 0.203356 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.02 | 0.151091 | 0.128000 | 0.130384 | 0.402908 | 0.500000 | 0.002522 | 0.000080 | 0.130384 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.16 | 0.205933 | 0.175000 | 0.202952 | 0.549155 | 0.500000 | 0.001850 | 0.000152 | 0.209847 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.29 | 0.119467 | 0.102000 | 0.131403 | 0.318578 | 0.500000 | 0.003189 | 0.000049 | 0.131403 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.62 | 0.313504 | 0.266000 | 2.03 | 0.836011 | 0.500000 | 0.001215 | 0.003168 | 4.40 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.54 | 0.389548 | 0.500000 | 0.002608 | 0.002128 | 2.95 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.26 | 0.212066 | 0.180000 | 2.03 | 0.565510 | 0.500000 | 0.001797 | 0.003188 | 4.42 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.26 | 0.136697 | 0.116000 | 1.31 | 0.364524 | 0.500000 | 0.002787 | 0.001883 | 2.61 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.866018 | 0.275769 | 0.234000 | 0.202648 | 0.735383 | 0.500000 | 0.001382 | 0.000425 | 0.589671 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.05 | 0.146433 | 0.124000 | 0.130327 | 0.390489 | 0.500000 | 0.002602 | 0.000282 | 0.391036 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.22 | 0.195139 | 0.166000 | 0.203164 | 0.520370 | 0.500000 | 0.001952 | 0.000426 | 0.592209 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.20 | 0.128617 | 0.109000 | 0.130431 | 0.342978 | 0.500000 | 0.002962 | 0.000263 | 0.365895 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15980.09 | 0.000350 | 446.01 |
CORE_MID VAV BOX REHEAT COIL | 331745.36 | 0.007257 | 10611.75 |
CORE_TOP VAV BOX REHEAT COIL | 60280.83 | 0.001319 | 2349.30 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5140.85 | 0.000112 | 175.44 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3675.98 | 0.000080 | 131.29 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6934.63 | 0.000152 | 270.25 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2221.57 | 0.000049 | 68.09 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 144821.11 | 0.003168 | 5631.56 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 97275.30 | 0.002128 | 3782.46 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 145718.23 | 0.003188 | 5666.39 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 86095.18 | 0.001883 | 3348.27 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19408.37 | 0.000425 | 754.38 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12869.66 | 0.000282 | 500.21 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19491.71 | 0.000426 | 757.62 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12043.82 | 0.000263 | 468.15 |
VAV_BOT WITH REHEAT HEATING COIL | 25244.99 | 0.000552 | 574.29 |
VAV_MID WITH REHEAT HEATING COIL | 185896.26 | 0.004066 | 4274.78 |
VAV_TOP WITH REHEAT HEATING COIL | 18489.31 | 0.000404 | 426.54 |
CAV_BAS HEATING COIL | 221830.05 | 0.004853 | 7214.95 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.76 | 2.29 | 9.52 | 2.29 | 8.46 | 8.46 | 0.300000 | 0.270067 | 8.46 |
VAV_MID WITH REHEAT | 44.88 | 22.81 | 89.76 | 25.17 | 78.34 | 78.34 | 0.300000 | 0.321239 | 78.34 |
VAV_TOP WITH REHEAT | 4.56 | 2.29 | 9.11 | 3.76 | 8.41 | 8.41 | 0.300000 | 0.447291 | 8.41 |
CAV_BAS | 4.78 | 4.78 | 4.78 | 4.78 | 4.78 | 4.78 | 1.00 | 1.00 | 4.78 |
AIRLOOP DATACENTER BASEMENT | 21.55 | 21.55 | 21.55 | 21.55 | 21.55 | 21.55 | 1.00 | 0.999989 | 21.55 |
AIRLOOP DATACENTER BOT | 0.472001 | 0.472001 | 0.472001 | 0.472001 | 0.472001 | 0.472001 | 1.00 | 1.00 | 0.472001 |
AIRLOOP DATACENTER MID | 4.51 | 4.51 | 4.51 | 4.51 | 4.51 | 4.51 | 1.00 | 1.00 | 4.51 |
AIRLOOP DATACENTER TOP | 0.458215 | 0.458215 | 0.458215 | 0.458215 | 0.458215 | 0.458215 | 1.00 | 1.00 | 0.458215 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.46 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 78.34 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.41 | |
CAV_BAS_OA_CONTROLLER | 4.78 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.55 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.472001 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.51 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.458215 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.82 | 6.67 | 11.01 | 0.008723 | 0.008500 | 156892.33 | 0.004487 | 8.46 |
VAV_MID WITH REHEAT COOLING COIL | 26.03 | 6.67 | 11.01 | 0.008731 | 0.008500 | 1474007.60 | 0.042156 | 78.34 |
VAV_TOP WITH REHEAT COOLING COIL | 25.76 | 6.67 | 11.01 | 0.008712 | 0.008500 | 155068.23 | 0.004435 | 8.41 |
CAV_BAS COOLING COIL | 25.71 | 6.67 | 11.40 | 0.008844 | 0.008500 | 87571.37 | 0.002505 | 4.78 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.46 |
VAV_MID WITH REHEAT FAN | 78.34 |
VAV_TOP WITH REHEAT FAN | 8.41 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004487 | 0.000106 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000552 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.042156 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004066 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004435 | 0.000107 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000404 | |
CAV_BAS_COOLC_CONTROLLER | 0.002505 | 0.000190 |
CAV_BAS_HEATC_CONTROLLER | 0.004853 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 4.78 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.55 | 425318.14 | 303049.05 | 0.010416 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.472001 | 9130.81 | 6570.83 | 0.000224 |
AIRLOOP DATACENTER MID COOLING COIL | 4.51 | 87261.81 | 62774.41 | 0.002137 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.458215 | 8871.14 | 6381.22 | 0.000217 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.55 | 21.55 | 21.55 | 21.55 | 425318.14 | 425318.14 | 14546.91 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.472001 | 0.472001 | 0.472001 | 0.472001 | 9130.81 | 9130.81 | 672.01 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.51 | 4.51 | 4.51 | 4.51 | 87261.81 | 87261.81 | 6720.07 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.458215 | 0.458215 | 0.458215 | 0.458215 | 8871.14 | 8871.14 | 672.01 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.55 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.472001 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.51 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.458215 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.55 | 425318.14 | 0.010416 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.472001 | 9130.81 | 0.000224 |
AIRLOOP DATACENTER MID HEATING COIL | 4.51 | 87261.81 | 0.002137 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.458215 | 8871.14 | 0.000217 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14546.91 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 672.01 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6720.07 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 672.01 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000084 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.053583 | 8661.85 | |
HEATSYS1 PUMP | 0.030957 | 9230.50 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.053583 | 6.43 |
HEATSYS1 | 0.030957 | 3.71 |
COOLSYS1_SUPPLY | 0.053583 | 6.43 |
SINGLE WATER PLANT LOOP | 0.012994 | 1.56 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.053583 | 0.053583 | 224914.71 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1415163.31 | 1415163.31 | 0.030957 |
CENTRAL BOILER | 535237.97 | 524422.25 | 0.012994 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.026791 | 2998.44 |
COOLSYS1 CHILLER2 PUMP | 0.026791 | 2998.44 |
PLANT CIRC PUMP | 0.012994 | 3281.29 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.053583 | 0.027123 | 949405.52 | 955184.83 | 0.048062 |
COOLSYS1 CHILLER2 | 0.053583 | 0.027123 | 949405.52 | 955184.83 | 0.048062 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.012994 | 139666.47 | 60547.96 | 69833.23 | 7004.20 | 21537.24 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.096123 | 11.53 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.096123 | 23562.32 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 35.68 | 1134074.27 | 7.14 | 141759.28 |
TOWERWATERSYS COOLTOWER 2 | 35.68 | 1134074.27 | 7.14 | 141759.28 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.049098 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.223 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.421 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6505 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6842 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5363 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.12806887E-14 | 0.42271709E-16 | -0.13586671E-09 | -0.40936836E-17 |
51 | 8 | 0.19922932E-07 | 0.16187222E-12 | 0.35697139E-03 | -0.22653060E-09 |
52 | 7 | -0.11619186E-01 | 0.85920355E-08 | -0.22189363E-01 | 0.13211437E-03 |
53 | 6 | 0.38843793 | 0.30204786E-05 | 0.45766083 | -0.45484060E-02 |
54 | 5 | -5.0254998 | 0.11379910E-03 | -4.3303126 | 0.61137149E-01 |
55 | 4 | 32.272621 | 0.93848507E-03 | 21.006408 | -0.41242756 |
56 | 3 | -109.67225 | 0.20601564E-02 | -54.766020 | 1.4927443 |
57 | 2 | 195.59070 | 0.11662962E-02 | 77.088399 | -2.8762550 |
58 | 1 | -170.59539 | 0.12524661E-03 | -55.026900 | 2.7356126 |
59 | 0 | 57.057407 | 0.71759292E-06 | 15.597005 | |
60 | 9 | 0.14110139E-14 | 0.39742576E-16 | -0.13817129E-09 | -0.60843190E-17 |
61 | 8 | 0.20247994E-07 | 0.15595569E-12 | 0.36048606E-03 | -0.23022666E-09 |
62 | 7 | -0.11724403E-01 | 0.82461052E-08 | -0.22340970E-01 | 0.13331073E-03 |
63 | 6 | 0.39129736 | 0.28944083E-05 | 0.46010459 | -0.45821116E-02 |
64 | 5 | -5.0534104 | 0.10890513E-03 | -4.3491197 | 0.61483222E-01 |
65 | 4 | 32.396114 | 0.89705981E-03 | 21.080005 | -0.41406715 |
66 | 3 | -109.93510 | 0.19671505E-02 | -54.911560 | 1.4965416 |
67 | 2 | 195.85133 | 0.11126060E-02 | 77.221727 | -2.8803937 |
68 | 1 | -170.69171 | 0.11937799E-03 | -55.065382 | 2.7373008 |
69 | 0 | 57.057407 | 0.68337402E-06 | 15.590414 | |
70 | 9 | 0.11953810E-14 | 0.45347951E-16 | -0.12637851E-09 | -0.31580148E-17 |
71 | 8 | 0.18583176E-07 | 0.18541820E-12 | 0.34227377E-03 | -0.21129711E-09 |
72 | 7 | -0.11178467E-01 | 0.10005971E-07 | -0.21554080E-01 | 0.12710323E-03 |
73 | 6 | 0.37645972 | 0.35409928E-05 | 0.44740546 | -0.44072130E-02 |
74 | 5 | -4.9085688 | 0.13417224E-03 | -4.2513079 | 0.59687292E-01 |
75 | 4 | 31.755172 | 0.11121548E-02 | 20.697061 | -0.40555762 |
76 | 3 | -108.57065 | 0.24524110E-02 | -54.154201 | 1.4768303 |
77 | 2 | 194.49811 | 0.13939007E-02 | 76.528253 | -2.8589059 |
78 | 1 | -170.19150 | 0.15023953E-03 | -54.865849 | 2.7285341 |
79 | 0 | 57.057407 | 0.86422455E-06 | 15.625098 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1598E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1613E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4848E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4861E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1390E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1400E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7516E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1956E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3022E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5154E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6096E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1648E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2402E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7664E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1051 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6440E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1176 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0925E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7574E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9570E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1496E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0924E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1939E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2918E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5133E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5977E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1629E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2328E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7668E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8046E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1596E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1611E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4846E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4858E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1388E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1397E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7515E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5873E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7463E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3347E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5002E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2762E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3577E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9952E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0209E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8165E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8760E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4211E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6386E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7363E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5402E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2799E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2243E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5425E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6119E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2772E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3272E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2497E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2683E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9953E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0213E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7723E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7737E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5128E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5139E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3406E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3414E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7516E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7522E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8039E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8858E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5380E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6016E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3596E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4010E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7668E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8046E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7764E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4548E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1339E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1037E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9136E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4491E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1496E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0921E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8037E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8833E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5383E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6012E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3610E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4057E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7664E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7723E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7737E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5128E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5139E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3406E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3414E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7515E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7521E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7781E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8460E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5676E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6169E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4526E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4721E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9954E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0213E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2252E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0327E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9208E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8303E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1082E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6843E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2799E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2243E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8282E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0104E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6317E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8261E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4799E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5664E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9952E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0208E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1033 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5600E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1118 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.1337E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.4862E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4245E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8633E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9092E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5840E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7303E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1403E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4333E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4690E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3150E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9603E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9312E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4734E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3076E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7435E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8265E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4985E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3751E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8633E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9088E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0465E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9472E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7063E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6993E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8862E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5081E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9603E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9312E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1034 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5742E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1119 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1500E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5000E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4356E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8716E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9134E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5872E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7344E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1438E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4370E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4761E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3198E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9686E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9354E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4738E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3102E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7441E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8286E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5025E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3776E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8716E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9131E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0505E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9518E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7109E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7036E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8941E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5134E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9686E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9354E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 65251.55761 | 65251.55761 | 4.78404 | 4.78404 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 71375.00542 | 71375.00542 | 5.23352 | 5.23352 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 669632.56875 | 669632.56875 | 49.08518 | 49.08518 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 172167.13139 | 172167.13139 | 7.33863 | 10.77825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 65140.37182 | 65140.37182 | 4.77455 | 4.77455 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 42256.99318 | 42256.99318 | 1.82398 | 1.82398 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11076.17930 | 11076.17930 | 0.81998 | 0.81998 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3135.72335 | 3135.72335 | 0.13446 | 0.13533 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13759.57658 | 13759.57658 | 1.01863 | 1.01863 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.22398E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2390.08373 | 2390.08373 | 0.10277 | 0.10277 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15665.37790 | 15665.37790 | 1.15972 | 1.15972 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 30.73633 | 8.23260E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4864.18558 | 4864.18558 | 0.20985 | 0.20985 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17401.84388 | 17401.84388 | 1.28827 | 1.28827 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 927.08668 | 927.08668 | 4.00596E-002 | 8.72129E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 102900.09362 | 102900.09362 | 7.61778 | 7.61778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 101414.61563 | 101414.61563 | 4.39698 | 4.39698 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 142315.06980 | 142315.06980 | 10.53563 | 10.53563 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12317 | 8.22530E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 68115.80493 | 68115.80493 | 2.95368 | 2.95368 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 152124.20346 | 152124.20346 | 11.26186 | 11.26186 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 102041.85524 | 102041.85524 | 4.42428 | 4.42428 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 152084.53654 | 152084.53654 | 11.25888 | 11.25888 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 60298.71899 | 60298.71899 | 2.61356 | 2.61356 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11698.10817 | 11698.10817 | 0.86602 | 0.86602 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13585.55033 | 13585.55033 | 0.58967 | 0.58967 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14197.24072 | 14197.24072 | 1.05102 | 1.05102 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9008.27546 | 9008.27546 | 0.39104 | 0.39104 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 16532.07370 | 16532.07370 | 1.22388 | 1.22388 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13643.80662 | 13643.80662 | 0.59221 | 0.59221 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16163.91338 | 16163.91338 | 1.19662 | 1.19662 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8430.99718 | 8430.99718 | 0.36590 | 0.36590 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8083.33963 | 8083.33963 | 0.47200 | 0.47200 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77201.69112 | 77201.69112 | 4.50799 | 4.50799 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7847.21395 | 7847.21395 | 0.45822 | 0.45822 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369033.86264 | 369033.86264 | 21.54816 | 21.54816 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 23.20100 | 8.22076E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 3.80000 | 5.05843E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 125615.42 | 8.46181 | 8.46181 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 17239.10 | 1.61299 | 1.61299 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1145696.46 | 78.34265 | 78.34265 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 216988.11 | 25.16674 | 25.16674 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 21:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 129480.14 | 8.41239 | 8.41239 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 21663.03 | 3.76279 | 3.76279 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
7 | CAV_BAS | Cooling | Sensible | 65998.86 | 4.78404 | 4.78404 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51592.61 | 1.20016 | 1.20016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 364658.96 | 21.54839 | 21.54839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14546.91 | 0.33839 | 0.33839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7994.42 | 0.47200 | 0.47200 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76368.64 | 4.50799 | 4.50799 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6720.07 | 0.15632 | 0.15632 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7764.99 | 0.45822 | 0.45822 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.78404 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.23352 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36344 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61716 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96916 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04833E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.49565E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61716 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15980.09497 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.49565E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 446.00605 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.08518 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38750 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.14902 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.83229E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.25694E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.14902 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 331745.36419 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.25694E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10611.75007 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.77455 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39837 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61857 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.56395E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31864E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.82398 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 60280.83384 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31864E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2349.30431 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81998 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29125 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24800 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20336 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77667 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30815E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12456E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20336 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5140.85017 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12456E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 175.44126 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01863 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15109 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12800 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13038 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40291 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52167E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.04123E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13038 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3675.98463 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.04123E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.28882 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15972 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20593 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17500 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20295 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54916 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85011E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51695E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20985 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6934.63097 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51695E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.24531 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28827 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11947 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13140 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31858 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18918E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.85968E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13140 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2221.56587 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.85968E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 68.09188 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.61778 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31350 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02633 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83601 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21530E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16797E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.39698 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 144821.11268 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16797E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5631.55505 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.53563 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38955 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60815E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.12790E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.95368 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 97275.29942 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.12790E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3782.46228 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.26186 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21207 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18000 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02713 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56551 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79661E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.18759E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.42428 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 145718.22552 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18759E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5666.39016 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.25888 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13670 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30603 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36452 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78719E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.88333E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.61356 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 86095.17743 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88333E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3348.26753 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86602 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27577 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23400 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20265 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73538 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38159E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.24559E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58967 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19408.36605 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.24559E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 754.38395 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05102 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14643 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13033 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39049 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60187E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.81524E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39104 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12869.66450 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.81524E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 500.20967 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22388 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19514 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16600 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20316 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52037 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95246E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.26382E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59221 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19491.70756 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.26382E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 757.61850 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19662 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12862 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10900 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13043 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34298 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96229E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.63459E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36590 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12043.82048 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.63459E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 468.15128 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47200 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.50799 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45822 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.54816 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.76006 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28525 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.52012 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28525 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.46181 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.46181 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27007 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 44.87967 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.81494 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 89.75933 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.16674 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 78.34265 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 78.34265 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32124 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.55604 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28514 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.11209 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.76279 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.41239 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.41239 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.44729 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.78404 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.78404 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.78404 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 4.78404 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.78404 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.78404 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.54816 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.54816 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.54816 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.54816 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.54839 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.54839 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47200 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47200 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47200 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47200 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47200 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47200 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.50799 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.50799 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.50799 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.50799 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.50799 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.50799 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45822 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45822 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45822 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45822 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45822 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45822 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.46181 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 78.34265 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.41239 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.78404 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.54839 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47200 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.50799 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45822 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.46181 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.82414 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00915 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72302E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 156892.32575 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.48710E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.46181 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 25244.98586 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.52235E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 574.28850 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.46181 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.48710E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.06124E-004 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.52235E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 78.34265 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.03221 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00918 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73053E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1474007.60256 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.21564E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 78.34265 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 185896.26375 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.06649E-003 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4274.78062 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 78.34265 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.21564E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.12958E-005 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.06649E-003 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.41239 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.76112 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00912 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71243E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 155068.23071 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.43493E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.41239 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 18489.31094 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.04454E-004 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 426.54097 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.41239 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.43493E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.07373E-004 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.04454E-004 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.78404 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.71184 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.39507 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84409E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 87571.36931 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.50453E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.78404 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 221830.05108 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.85254E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7214.95378 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.78404 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.50453E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.90132E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.85254E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.54839 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.54839 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 425318.14076 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 303049.05301 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04160E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.54839 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.54839 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.54839 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.54839 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 425318.14076 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 425318.14076 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14546.90948 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.54839 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.54839 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 425318.14076 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04160E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14546.90948 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 8.44207E-005 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47200 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47200 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9130.81123 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6570.83352 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.23613E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47200 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47200 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47200 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47200 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9130.81123 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9130.81123 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47200 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47200 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9130.81123 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.23613E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.50799 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50799 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 87261.81147 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 62774.40768 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.13704E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.50799 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.50799 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.50799 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.50799 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 87261.81147 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 87261.81147 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6720.06953 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.50799 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50799 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 87261.81147 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.13704E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6720.06953 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45822 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45822 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 8871.14246 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6381.21648 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.17254E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45822 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45822 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45822 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45822 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8871.14246 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8871.14246 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45822 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45822 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 8871.14246 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.17254E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.35830E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8661.84703 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.35830E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.42996 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.35830E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.35830E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 224914.70928 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.09567E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.71481 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.09567E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 9230.50460 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1415163.30990 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1415163.31000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.09567E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.35830E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.42996 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.67915E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 2998.44440 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.67915E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 2998.44440 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.35830E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.71226E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 949405.52437 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 955184.83000 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.80615E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.35830E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.71226E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 949405.52437 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 955184.83000 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.80615E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.29939E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.55927 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.29939E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3281.28570 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.29939E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60547.95754 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21537.24273 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 535237.97166 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 524422.25000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.29939E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.61231E-002 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.53477 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.61231E-002 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 23562.32388 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 35.68370 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1134074.26620 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.13674 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 141759.28327 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 35.68370 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1134074.26620 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.13674 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 141759.28327 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.90975E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.90975E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22246.05 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 462225.48 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 83889.86 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7159.51 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5118.14 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9650.59 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3096.42 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 201542.08 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 135374.39 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 202790.56 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 119815.36 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 27009.94 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17910.26 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 27125.92 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16760.96 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 29856.14 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 226866.01 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 22772.36 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 247104.26 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 195710.24 | 141763.00 | 53947.24 | 0.72 | 32518.58 | 329.82 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1823500.83 | 1316956.93 | 506543.90 | 0.72 | 300101.25 | 3043.79 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 194048.30 | 140732.40 | 53315.90 | 0.73 | 32354.59 | 328.16 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 108654.46 | 79214.09 | 29440.38 | 0.73 | 17420.34 | 176.69 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.90 | 23.54 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.90 | 23.54 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3365126041 | 0.2736085831 | Pass | Pass | 0.7956081364 | 1.4180991465 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.5460888298E-002 | 8.2507311789E-002 | Pass | Pass | 2.1414092972E-002 | 0.1447970212 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.0043030279E-003 | 6.1296649402E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.4638678186E-002 | 1.0119739228E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.4081062149E-002 | 5.7997039099E-002 | Pass | Pass | 2.0895049044E-002 | 0.1419082417 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.8000185841E-002 | 0.1232374013 | Pass | Pass | 3.4587228936E-002 | 0.2164881094 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.8503546916E-002 | 0.1007521199 | Pass | Pass | 2.0681347011E-002 | 0.1393383151 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.8550159902E-002 | 6.7817204875E-002 | Pass | Pass | 2.0882552222E-002 | 0.1420006078 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5261231771E-002 | 2.2499505300E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.3177983611E-002 | 0.1122512599 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.9499481037E-002 | 9.3742698216E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.9525789259E-002 | 3.8444991957E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.9330265965E-002 | 2.4668761431E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.2528454653E-002 | 0.1083950037 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.1203497876E-002 | 9.2326425240E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.4494250645E-002 | 3.9487088363E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6098591188E-003 | 8.9455225279E-003 | Pass | Pass | 0.1114011639 | 0.7637317298 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3181150557E-003 | 6.3436159333E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5220106953E-002 | 3.4613623857E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7694217489E-006 | 6.6809418987E-006 | Pass | Pass | 2.5548538321E-003 | 1.9640318818E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8677344764E-006 | 5.3870427771E-006 | Pass | Pass | 1.5041419729E-002 | 8.9970207559E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2356301737E-002 | 1.1752529639E-002 | Pass | Pass | 9.5591920037E-003 | 1.7295899675E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.4804504429E-005 | 1.7650356298E-004 | Pass | Pass | 5.1782804032E-005 | 1.0572530589E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6393.31 | 84.08 | 0.00 | 25380.50 | 12270.83 | 44128.73 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 1390.74 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 122.81 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 110.29 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 1102.91 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.74 | 0.0000 | Y | 110.29 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.54 | 0.0000 | Y | 8.00 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.45 | 0.0000 | Y | 5.14 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.27 | 0.0000 | Y | 7.91 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.33 | 0.0000 | Y | 5.11 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.51 | 0.0000 | Y | 79.90 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.42 | 0.0000 | Y | 51.31 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.26 | 0.0000 | Y | 79.05 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.31 | 0.0000 | Y | 51.06 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.51 | 0.0000 | Y | 7.99 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.42 | 0.0000 | Y | 5.13 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.26 | 0.0000 | Y | 7.91 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 23.31 | 0.0000 | Y | 5.11 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 42.05 | 168.00 | 40.96 | 0.0000 | Y | 34.81 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 37.39 | 168.00 | 36.42 | 0.0000 | Y | 1.78 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 37.39 | 168.00 | 36.42 | 0.0000 | Y | 17.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 37.39 | 168.00 | 36.42 | 0.0000 | Y | 1.78 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 572.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.14 | 42.14 | 102.47 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.75 | 62.95 | 10.87 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.75 | 46.20 | 149.32 | |
Exterior Lighting Total | 31088.59 | 262.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1867768.86 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1415163.31 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 955184.83 | 5.60 | 925458.33 | 4.71 | 6.90 | 23.54 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 955184.83 | 5.60 | 925458.33 | 4.71 | 6.90 | 23.54 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 524422.25 | 0.90 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1134074.27 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1134074.27 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 156892.33 | 195710.24 | 141763.00 | 53947.24 | 0.72 | - | 32518.58 | 329.82 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1474007.60 | 1823500.83 | 1316956.93 | 506543.90 | 0.72 | - | 300101.25 | 3043.79 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 155068.23 | 194048.30 | 140732.40 | 53315.90 | 0.73 | - | 32354.59 | 328.16 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 87571.37 | 108654.46 | 79214.09 | 29440.38 | 0.73 | - | 17420.34 | 176.69 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 425318.14 | 303049.05 | 122269.09 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9130.81 | 6570.83 | 2559.98 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 87261.81 | 62774.41 | 24487.40 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8871.14 | 6381.22 | 2489.93 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15980.09 | 22246.05 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 331745.36 | 462225.48 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 60280.83 | 83889.86 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5140.85 | 7159.51 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3675.98 | 5118.14 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6934.63 | 9650.59 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2221.57 | 3096.42 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 144821.11 | 201542.08 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 97275.30 | 135374.39 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 145718.23 | 202790.56 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 86095.18 | 119815.36 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19408.37 | 27009.94 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12869.66 | 17910.26 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19491.71 | 27125.92 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12043.82 | 16760.96 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 25244.99 | 29856.14 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 185896.26 | 226866.01 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 18489.31 | 22772.36 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 221830.05 | 247104.26 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 425318.14 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9130.81 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 87261.81 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 8871.14 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14546.91 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6720.07 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.46 | 18285.51 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 78.34 | 169294.29 | 2160.95 | 1.00 | 1.08 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.41 | 18178.73 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 4.78 | 8112.08 | 1695.65 | 1.00 | 1.17 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.55 | 35726.65 | 1657.97 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 528.69 | 1120.11 | 1.00 | 1.63 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.51 | 5049.43 | 1120.11 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 513.25 | 1120.11 | 1.00 | 1.65 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.053583 | 8661.85 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.030957 | 9230.50 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026791 | 2998.44 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.026791 | 2998.44 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.012994 | 3281.29 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.096123 | 23562.32 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 65251.56 | 65251.56 | 23.48 | 4.784 | 4.784 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00904 | 24.71 | 0.00822 | 1.200 | 0.00 |
CORE_BOTTOM | 71375.01 | 71375.01 | 28.59 | 5.234 | 5.234 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 24.71 | 0.00822 | 1.078 | 0.00 |
CORE_MID | 669632.57 | 669632.57 | 268.27 | 49.085 | 49.085 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 24.71 | 0.00822 | 10.778 | 0.00 |
CORE_TOP | 65140.37 | 65140.37 | 26.10 | 4.775 | 4.775 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 24.71 | 0.00822 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11076.18 | 11076.18 | 35.34 | 0.820 | 0.820 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00883 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13759.58 | 13759.58 | 68.13 | 1.019 | 1.019 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00867 | 25.28 | 0.00822 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15665.38 | 15665.38 | 49.98 | 1.160 | 1.160 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 24.00 | 24.00 | 0.00873 | 30.74 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17401.84 | 17401.84 | 86.16 | 1.288 | 1.288 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 102900.09 | 102900.09 | 328.32 | 7.618 | 7.618 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00883 | 31.30 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 142315.07 | 142315.07 | 704.62 | 10.536 | 10.536 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00866 | 26.12 | 0.00823 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 152124.20 | 152124.20 | 485.37 | 11.262 | 11.262 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00873 | 30.93 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 152084.54 | 152084.54 | 752.99 | 11.259 | 11.259 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00823 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11698.11 | 11698.11 | 37.32 | 0.866 | 0.866 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00878 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14197.24 | 14197.24 | 70.29 | 1.051 | 1.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00865 | 26.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16532.07 | 16532.07 | 52.75 | 1.224 | 1.224 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00870 | 31.00 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16163.91 | 16163.91 | 80.03 | 1.197 | 1.197 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00823 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8083.34 | 8083.34 | 223.28 | 0.472 | 0.472 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77201.69 | 77201.69 | 2132.48 | 4.508 | 4.508 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7847.21 | 7847.21 | 216.76 | 0.458 | 0.458 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369033.86 | 369033.86 | 470.90 | 21.548 | 21.548 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 23.20 | 0.00822 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.93 | 0.00506 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.80 | 0.00506 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 172167.13 | 172167.13 | 68.97 | 7.339 | 10.778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 42256.99 | 42256.99 | 16.93 | 1.824 | 1.824 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3135.72 | 3135.72 | 10.01 | 0.134 | 0.135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00689 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2390.08 | 2390.08 | 11.83 | 0.103 | 0.103 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00702 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4864.19 | 4864.19 | 15.52 | 0.210 | 0.210 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00725 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 927.09 | 927.09 | 4.59 | 0.040 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00636 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 101414.62 | 101414.62 | 323.58 | 4.397 | 4.397 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00756 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 68115.80 | 68115.80 | 337.25 | 2.954 | 2.954 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 102041.86 | 102041.86 | 325.58 | 4.424 | 4.424 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00756 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 60298.72 | 60298.72 | 298.55 | 2.614 | 2.614 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00748 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13585.55 | 13585.55 | 43.35 | 0.590 | 0.590 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9008.28 | 9008.28 | 44.60 | 0.391 | 0.391 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13643.81 | 13643.81 | 43.53 | 0.592 | 0.592 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8431.00 | 8431.00 | 41.74 | 0.366 | 0.366 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.01 | 0.00807 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.07 | 0.00534 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.46 | 8.46 | 1.61 | 1.61 | 8.4618 | 2.2853 | 8.4618 | 0.2701 | 0.3000 |
VAV_MID WITH REHEAT | 78.34 | 78.34 | 25.17 | 25.17 | 78.3426 | 25.1667 | 78.3426 | 0.3212 | 0.3000 |
VAV_TOP WITH REHEAT | 8.41 | 8.41 | 3.76 | 3.76 | 8.4124 | 3.7628 | 8.4124 | 0.4473 | 0.3000 |
CAV_BAS | 4.78 | 4.78 | 1.20 | 1.20 | 4.7840 | 4.7840 | 4.7840 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.55 | 21.55 | 0.34 | 0.34 | 21.5484 | 21.5482 | 21.5484 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4720 | 0.4720 | 0.4720 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.51 | 4.51 | 0.16 | 0.16 | 4.5080 | 4.5080 | 4.5080 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4582 | 0.4582 | 0.4582 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15980.095 | 15980.095 | 1.617156 | 0.00034957 | 446.006 | 12/21 00:10:00 | 12/21 00:10:00 | 15980.09 | 15980.09 | 1.617156 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 16007.52 | 16007.52 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 331745.364 | 331745.364 | 16.149024 | 0.00725694 | 10611.750 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 331745.36 | 331745.36 | 16.149024 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 172167.13 | 0.00 | 332603.79 | 332603.79 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 60280.834 | 60280.834 | 1.823980 | 0.00131864 | 2349.304 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 60280.83 | 60280.83 | 1.823980 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 42256.99 | 0.00 | 60409.14 | 60409.14 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5140.850 | 5140.850 | 0.203356 | 0.00011246 | 175.441 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5140.85 | 5140.85 | 0.203356 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00689209 | 43.8070 | 3135.72 | 0.00 | 5153.14 | 5153.14 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3675.985 | 3675.985 | 0.130384 | 0.00008041 | 131.289 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3675.98 | 3675.98 | 0.130384 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00702119 | 44.6187 | 2390.08 | 0.00 | 3684.46 | 3684.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6934.631 | 6934.631 | 0.209847 | 0.00015170 | 270.245 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6934.63 | 6934.63 | 0.209847 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00724543 | 46.0272 | 4864.19 | 0.00 | 6949.39 | 6949.39 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2221.566 | 2221.566 | 0.131403 | 0.00004860 | 68.092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2221.57 | 2221.57 | 0.131403 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00636089 | 40.4636 | 927.09 | 0.00 | 2227.66 | 2227.66 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 144821.113 | 144821.113 | 4.396980 | 0.00316797 | 5631.555 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 144821.11 | 144821.11 | 4.396980 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00755641 | 47.9795 | 101414.62 | 0.00 | 145129.51 | 145129.51 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 97275.299 | 97275.299 | 2.953676 | 0.00212790 | 3782.462 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 97275.30 | 97275.30 | 2.953676 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00757606 | 48.1027 | 68115.80 | 0.00 | 97482.45 | 97482.45 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 145718.226 | 145718.226 | 4.424278 | 0.00318759 | 5666.390 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 145718.23 | 145718.23 | 4.424278 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00756084 | 48.0073 | 102041.86 | 0.00 | 146028.53 | 146028.53 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 86095.177 | 86095.177 | 2.613558 | 0.00188333 | 3348.268 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 86095.18 | 86095.18 | 2.613558 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00747568 | 47.4734 | 60298.72 | 0.00 | 86278.51 | 86278.51 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19408.366 | 19408.366 | 0.589671 | 0.00042456 | 754.384 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19408.37 | 19408.37 | 0.589671 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00769570 | 48.8524 | 13585.55 | 0.00 | 19449.70 | 19449.70 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12869.665 | 12869.665 | 0.391036 | 0.00028152 | 500.210 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12869.66 | 12869.66 | 0.391036 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770012 | 48.8801 | 9008.28 | 0.00 | 12897.07 | 12897.07 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19491.708 | 19491.708 | 0.592209 | 0.00042638 | 757.619 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19491.71 | 19491.71 | 0.592209 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00769767 | 48.8647 | 13643.81 | 0.00 | 19533.22 | 19533.22 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12043.820 | 12043.820 | 0.365895 | 0.00026346 | 468.151 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12043.82 | 12043.82 | 0.365895 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00766124 | 48.6366 | 8431.00 | 0.00 | 12069.47 | 12069.47 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 156892.326 | -999.000 | 8.461807 | 0.00448710 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 156892.33 | 151092.19 | 8.461807 | 25.82 | 17.02 | 0.00872302 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 23.9961 | 24.00 | 0.00888620 | 46.9205 | 109706.76 | 0.00 | 159292.45 | 147393.24 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 25244.986 | 25244.986 | 2.538542 | 0.00055223 | 574.289 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25244.99 | 25244.99 | 2.538542 | 4.43 | 4.29 | 0.00518529 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 79.9869 | 21.84 | 0.00607452 | 36.7232 | 11317.08 | 0.00 | 26020.78 | 26020.78 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1474007.603 | -999.000 | 78.342647 | 0.04215643 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1474007.60 | 1418508.59 | 78.342647 | 26.03 | 17.10 | 0.00873053 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 25.9195 | 24.00 | 0.00892239 | 47.1088 | 984866.55 | 0.00 | 1496250.49 | 1383989.40 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 185896.264 | 185896.264 | 23.502794 | 0.00406649 | 4274.781 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 21:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 185896.26 | 185896.26 | 23.502794 | 6.14 | 5.49 | 0.00543358 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 86.3982 | 21.00 | 0.00772170 | 49.0136 | 306657.55 | 0.00 | 197730.09 | 197730.09 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 155068.231 | -999.000 | 8.412391 | 0.00443493 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 155068.23 | 149575.51 | 8.412391 | 25.76 | 16.99 | 0.00871243 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 24.1370 | 24.00 | 0.00886481 | 46.8090 | 113632.27 | 0.00 | 157452.92 | 145897.86 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 18489.311 | 18489.311 | 2.523717 | 0.00040445 | 426.541 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18489.31 | 18489.31 | 2.523717 | 6.63 | 5.89 | 0.00555998 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 80.4567 | 19.44 | 0.00743140 | 51.9617 | 35910.83 | 0.00 | 19848.06 | 19848.06 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 87571.369 | -999.000 | 4.784041 | 0.00250453 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 87571.37 | 82639.16 | 4.784041 | 25.71 | 17.08 | 0.00884409 | 11.40 | 11.35 | 0.00850000 | 30.14 | 0.00823165 | 18.07 | 25.0867 | 24.00 | 0.00908087 | 47.9340 | 59396.83 | 0.00 | 88913.56 | 81601.13 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 221830.051 | 221830.051 | 4.784041 | 0.00485254 | 7214.954 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 221830.05 | 221830.05 | 4.784041 | 0.95 | 0.95 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 25.0867 | 24.93 | 0.00505843 | 25.4102 | 0.00 | 0.00 | 177608.63 | 177608.63 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 425318.141 | 303049.053 | 21.548390 | 0.01041601 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 395227.64 | 393067.97 | -999.0 | 28.49 | 17.77 | 0.00853772 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | -999.0000 | 27.00 | 0.00854258 | 37.7685 | 368630.19 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9130.811 | 6570.834 | 0.472001 | 0.00022361 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8456.33 | 8359.19 | -999.0 | 28.03 | 17.65 | 0.00857764 | 12.80 | 11.93 | 0.00850000 | 28.94 | 0.00822975 | 17.67 | -999.0000 | 27.00 | 0.00858955 | 37.9710 | 8083.34 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87261.811 | 62774.408 | 4.507989 | 0.00213704 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 80824.28 | 79854.92 | -999.0 | 28.03 | 17.65 | 0.00858111 | 12.80 | 11.93 | 0.00850000 | 28.94 | 0.00822975 | 17.67 | -999.0000 | 27.00 | 0.00859374 | 37.9895 | 77201.69 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8871.142 | 6381.216 | 0.458215 | 0.00021725 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8216.94 | 8120.05 | -999.0 | 28.04 | 17.65 | 0.00857976 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00859212 | 37.9824 | 7846.11 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 425318.141 | 425318.141 | 21.548390 | 0.01041601 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 425318.14 | 425318.14 | 21.548390 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5704 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9130.811 | 9130.811 | 0.472001 | 0.00022361 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9130.81 | 9130.81 | 0.472001 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3119 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87261.811 | 87261.811 | 4.507989 | 0.00213704 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 87261.81 | 87261.81 | 4.507989 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4677 | 25.01 | 0.00807419 | 40.1884 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8871.142 | 8871.142 | 0.458215 | 0.00021725 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8871.14 | 8871.14 | 0.458215 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4116 | 24.07 | 0.00533899 | 28.2225 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.91 | 14546.91 | 21.548390 | 0.06 | 0.06 | 0.00844595 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5704 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.472001 | 0.13 | 0.13 | 0.00838602 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3119 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6720.07 | 6720.07 | 4.507989 | 0.13 | 0.13 | 0.00796962 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4677 | 25.01 | 0.00807419 | 40.1884 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.458215 | 0.13 | 0.13 | 0.00532942 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4116 | 24.07 | 0.00533899 | 28.2225 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15980.095 | 15980.095 | 1.617156 | 0.00034957 | 446.006 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 1.1069 | 1.129205 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 15980.09 | 15980.09 | 1.0000 | 1.91112082 | 1.617156 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.34952936 | 60.00 | 48.89 | 11.11 | 0.000 | 15980.09 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 16007.52 | 16007.52 | 1.91112082 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 331745.364 | 331745.364 | 16.149024 | 0.00725694 | 10611.750 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 22.9797 | 23.442197 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 331745.36 | 331745.36 | 1.0000 | 19.08457172 | 16.149024 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 7.25619878 | 60.00 | 48.89 | 11.11 | 0.000 | 331745.36 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 172167.13 | 0.00 | 332603.79 | 332603.79 | 19.08457172 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.89 | 18.00 | 0.00800000 | 50487.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 60280.834 | 60280.834 | 1.823980 | 0.00131864 | 2349.304 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 4.1756 | 4.259638 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 60280.83 | 60280.83 | 1.0000 | 2.15554020 | 1.823980 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.31851040 | 60.00 | 48.89 | 11.11 | 0.000 | 60280.83 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 42256.99 | 0.00 | 60409.14 | 60409.14 | 2.15554020 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61084.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5140.850 | 5140.850 | 0.203356 | 0.00011246 | 175.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 0.3561 | 0.363269 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5140.85 | 5140.85 | 1.0000 | 0.24032188 | 0.203356 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.11244477 | 60.00 | 48.89 | 11.11 | 0.000 | 5140.85 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00689209 | 21.00 | 0.00689209 | 43.8070 | 3135.72 | 0.00 | 5153.14 | 5153.14 | 0.24032188 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.83 | 19.29 | 0.00800000 | 54502.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3675.985 | 3675.985 | 0.130384 | 0.00008041 | 131.289 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 0.2546 | 0.259757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3675.98 | 3675.98 | 1.0000 | 0.15408539 | 0.130384 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.08040406 | 60.00 | 48.89 | 11.11 | 0.000 | 3675.98 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00702119 | 21.00 | 0.00702119 | 44.6187 | 2390.08 | 0.00 | 3684.46 | 3684.46 | 0.15408539 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.25 | 20.05 | 0.00800000 | 56971.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6934.631 | 6934.631 | 0.209847 | 0.00015170 | 270.245 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 0.4804 | 0.490023 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6934.63 | 6934.63 | 1.0000 | 0.24799268 | 0.209847 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.15167977 | 60.00 | 48.89 | 11.11 | 0.000 | 6934.63 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00724543 | 21.00 | 0.00724543 | 46.0272 | 4864.19 | 0.00 | 6949.39 | 6949.39 | 0.24799268 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61082.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2221.566 | 2221.566 | 0.131403 | 0.00004860 | 68.092 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 0.1539 | 0.156983 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2221.57 | 2221.57 | 1.0000 | 0.15528971 | 0.131403 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04859186 | 60.00 | 48.89 | 11.11 | 0.000 | 2221.57 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00636089 | 21.00 | 0.00636089 | 40.4636 | 927.09 | 0.00 | 2227.66 | 2227.66 | 0.15528971 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.87 | 16.97 | 0.00800000 | 47405.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 144821.113 | 144821.113 | 4.396980 | 0.00316797 | 5631.555 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 10.0316 | 10.233527 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 144821.11 | 144821.11 | 1.0000 | 5.19625732 | 4.396980 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 3.16764270 | 60.00 | 48.89 | 11.11 | 0.000 | 144821.11 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00755641 | 21.00 | 0.00755641 | 47.9795 | 101414.62 | 0.00 | 145129.51 | 145129.51 | 5.19625732 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 97275.299 | 97275.299 | 2.953676 | 0.00212790 | 3782.462 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 6.7382 | 6.873786 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 97275.30 | 97275.30 | 1.0000 | 3.49059180 | 2.953676 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 2.12768281 | 60.00 | 48.89 | 11.11 | 0.000 | 97275.30 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00757606 | 21.00 | 0.00757606 | 48.1027 | 68115.80 | 0.00 | 97482.45 | 97482.45 | 3.49059180 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 145718.226 | 145718.226 | 4.424278 | 0.00318759 | 5666.390 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 10.0938 | 10.296919 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 145718.23 | 145718.23 | 1.0000 | 5.22851784 | 4.424278 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 3.18726507 | 60.00 | 48.89 | 11.11 | 0.000 | 145718.23 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00756084 | 21.00 | 0.00756084 | 48.0073 | 102041.86 | 0.00 | 146028.53 | 146028.53 | 5.22851784 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 86095.177 | 86095.177 | 2.613558 | 0.00188333 | 3348.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 5.9637 | 6.083763 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 86095.18 | 86095.18 | 1.0000 | 3.08864732 | 2.613558 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.88314228 | 60.00 | 48.89 | 11.11 | 0.000 | 86095.18 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00747568 | 21.00 | 0.00747568 | 47.4734 | 60298.72 | 0.00 | 86278.51 | 86278.51 | 3.08864732 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19408.366 | 19408.366 | 0.589671 | 0.00042456 | 754.384 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 1.3444 | 1.371458 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19408.37 | 19408.37 | 1.0000 | 0.69686072 | 0.589671 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.42451524 | 60.00 | 48.89 | 11.11 | 0.000 | 19408.37 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00769570 | 21.00 | 0.00769570 | 48.8524 | 13585.55 | 0.00 | 19449.70 | 19449.70 | 0.69686072 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12869.665 | 12869.665 | 0.391036 | 0.00028152 | 500.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 0.8915 | 0.909412 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12869.66 | 12869.66 | 1.0000 | 0.46211814 | 0.391036 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.28149555 | 60.00 | 48.89 | 11.11 | 0.000 | 12869.66 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00770012 | 21.00 | 0.00770012 | 48.8801 | 9008.28 | 0.00 | 12897.07 | 12897.07 | 0.46211814 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60968.4 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19491.708 | 19491.708 | 0.592209 | 0.00042638 | 757.619 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 1.3502 | 1.377347 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19491.71 | 19491.71 | 1.0000 | 0.69986003 | 0.592209 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.42633815 | 60.00 | 48.89 | 11.11 | 0.000 | 19491.71 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00769767 | 21.00 | 0.00769767 | 48.8647 | 13643.81 | 0.00 | 19533.22 | 19533.22 | 0.69986003 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12043.820 | 12043.820 | 0.365895 | 0.00026346 | 468.151 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 0.8343 | 0.851055 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12043.82 | 12043.82 | 1.0000 | 0.43240700 | 0.365895 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.26343203 | 60.00 | 48.89 | 11.11 | 0.000 | 12043.82 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00766124 | 21.00 | 0.00766124 | 48.6366 | 8431.00 | 0.00 | 12069.47 | 12069.47 | 0.43240700 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 156892.326 | -999.000 | 8.461807 | 0.00448710 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0557 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.461807 | 9.99998242 | 4197.9300 | 999.8980 | 53.57752732 | 15.00 | 6.67 | 8.33 | 1873539.53 | 8.3741 | 8.374113 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 156892.33 | 151092.19 | 1.0000 | 9.99998242 | 8.461807 | 25.82 | 17.02 | 0.00872302 | 48183.6 | 11.01 | 11.01 | 0.00850000 | 32494.4 | 4.48664293 | 6.67 | 15.00 | 8.33 | 18285.513 | 138606.81 | 31.30 | 0.00823349 | 18.45 | 2.03050000 | 23.9961 | 24.00 | 0.00888620 | 24.00 | 0.00888620 | 46.9205 | 109706.76 | 0.00 | 159292.45 | 147393.24 | 9.99998242 | 25.82 | 17.22 | 0.00872302 | 48183.6 | 11.39 | 11.26 | 0.00825123 | 32254.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25244.986 | 25244.986 | 2.538542 | 0.00055223 | 574.289 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.461807 | 9.99998242 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 1.7487 | 1.783892 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25244.99 | 25244.99 | 1.0000 | 2.99999473 | 2.538542 | 4.43 | 4.29 | 0.00518529 | 17457.8 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.55217843 | 60.00 | 48.89 | 11.11 | 0.000 | 25244.99 | 3.80 | 0.00505843 | 3.80 | 2.03050000 | 79.9869 | 6.93 | 0.00569228 | 21.84 | 0.00607452 | 36.7232 | 11317.08 | 0.00 | 26020.78 | 26020.78 | 2.99999473 | 2.80 | 2.80 | 0.00518529 | 15808.6 | 11.35 | 7.88 | 0.00518529 | 24482.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1474007.603 | -999.000 | 78.342647 | 0.04215643 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0696 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.342647 | 92.58366853 | 4197.9300 | 999.8980 | 53.57752732 | 15.00 | 6.67 | 8.33 | 1873539.53 | 78.6750 | 78.675020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1474007.60 | 1418508.59 | 1.0000 | 92.58366853 | 78.342647 | 26.03 | 17.10 | 0.00873053 | 48415.2 | 11.01 | 11.01 | 0.00850000 | 32494.4 | 42.15213045 | 6.67 | 15.00 | 8.33 | 169294.288 | 1304713.31 | 31.30 | 0.00823349 | 18.45 | 20.30600000 | 25.9195 | 24.00 | 0.00892239 | 24.00 | 0.00892239 | 47.1088 | 984866.55 | 0.00 | 1496250.49 | 1383989.40 | 92.58366853 | 26.03 | 17.29 | 0.00873053 | 48415.2 | 11.39 | 11.26 | 0.00824977 | 32254.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 185896.264 | 185896.264 | 23.502794 | 0.00406649 | 4274.781 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.342647 | 92.58366853 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 12.8769 | 13.136029 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 21:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 185896.26 | 185896.26 | 1.0000 | 27.77510056 | 23.502794 | 6.14 | 5.49 | 0.00543358 | 19820.2 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 4.06607111 | 60.00 | 48.89 | 11.11 | 0.000 | 185896.26 | 3.80 | 0.00505843 | 3.80 | 20.30600000 | 86.3982 | 21.00 | 0.00781648 | 21.00 | 0.00772170 | 49.0136 | 306657.55 | 0.00 | 197730.09 | 197730.09 | 27.77510056 | 2.80 | 2.80 | 0.00543358 | 16430.9 | 9.81 | 7.44 | 0.00543358 | 23549.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 155068.231 | -999.000 | 8.412391 | 0.00443493 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0360 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.412391 | 9.94158438 | 4197.9300 | 999.8980 | 53.57752732 | 15.00 | 6.67 | 8.33 | 1873539.53 | 8.2768 | 8.276753 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 155068.23 | 149575.51 | 1.0000 | 9.94158438 | 8.412391 | 25.76 | 16.99 | 0.00871243 | 48092.3 | 11.01 | 11.01 | 0.00850000 | 32494.3 | 4.43447936 | 6.67 | 15.00 | 8.33 | 18178.729 | 136889.50 | 31.30 | 0.00823349 | 18.45 | 2.03050000 | 24.1370 | 24.00 | 0.00886481 | 24.00 | 0.00886481 | 46.8090 | 113632.27 | 0.00 | 157452.92 | 145897.86 | 9.94158438 | 25.76 | 17.19 | 0.00871243 | 48092.3 | 11.39 | 11.26 | 0.00825158 | 32254.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 18489.311 | 18489.311 | 2.523717 | 0.00040445 | 426.541 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.412391 | 9.94158438 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 1.2807 | 1.306514 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18489.31 | 18489.31 | 1.0000 | 2.98247531 | 2.523717 | 6.63 | 5.89 | 0.00555998 | 20636.5 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.40441293 | 60.00 | 48.89 | 11.11 | 0.000 | 18489.31 | 3.80 | 0.00505843 | 3.80 | 2.03050000 | 80.4567 | 18.28 | 0.00762479 | 19.44 | 0.00743140 | 51.9617 | 35910.83 | 0.00 | 19848.06 | 19848.06 | 2.98247531 | 2.80 | 2.80 | 0.00555998 | 16747.7 | 9.36 | 7.37 | 0.00555998 | 23402.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87571.369 | -999.000 | 4.784041 | 0.00250453 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2807 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 4.784041 | 5.65367736 | 4197.9300 | 999.8980 | 53.57752732 | 15.00 | 6.67 | 8.33 | 1873539.53 | 4.6741 | 4.674114 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 87571.37 | 82639.16 | 1.0000 | 5.65367736 | 4.784041 | 25.71 | 17.08 | 0.00884409 | 48377.5 | 11.40 | 11.35 | 0.00850000 | 32888.3 | 2.50427459 | 6.67 | 15.00 | 8.33 | 8112.080 | 79459.29 | 30.14 | 0.00823165 | 18.07 | 1.20015641 | 25.0867 | 24.00 | 0.00908087 | 24.00 | 0.00908087 | 47.9340 | 59396.83 | 0.00 | 88913.56 | 81601.13 | 5.65367736 | 25.71 | 17.28 | 0.00884409 | 48377.5 | 11.58 | 11.42 | 0.00833134 | 32650.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 221830.051 | 221830.051 | 4.784041 | 0.00485254 | 7214.954 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 4.784041 | 5.65367736 | 4197.9300 | 999.8980 | 30.95357882 | 48.89 | 60.00 | 11.11 | 1443644.03 | 15.3660 | 15.675226 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 221830.05 | 221830.05 | 1.0000 | 5.65367736 | 4.784041 | 0.95 | 0.95 | 0.00505843 | 13617.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 4.85204352 | 60.00 | 48.89 | 11.11 | 0.000 | 221830.05 | 3.80 | 0.00505843 | 3.80 | 1.20015641 | 25.0867 | 0.00 | 0.00505843 | 24.93 | 0.00505843 | 25.4102 | 0.00 | 0.00 | 177608.63 | 177608.63 | 5.65367736 | 12.80 | 8.42 | 0.00505843 | 25633.1 | 43.77 | 20.15 | 0.00505843 | 57047.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 425318.141 | 303049.053 | 21.548390 | 0.01041601 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7112 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 395227.64 | 393067.97 | 0.9293 | -999.0 | -999.0 | 28.49 | 17.77 | 0.00853772 | 50434.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 395227.64 | 31.30 | 0.00823349 | 18.45 | 0.33839277 | -999.0000 | 27.00 | 0.00854258 | 27.00 | 0.00854258 | 37.7685 | 368630.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9130.811 | 6570.834 | 0.472001 | 0.00022361 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7854 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8456.33 | 8359.19 | 0.9261 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00857764 | 50061.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8456.33 | 28.94 | 0.00822975 | 17.67 | 0.01563234 | -999.0000 | 27.00 | 0.00858955 | 27.00 | 0.00858955 | 37.9710 | 8083.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 87261.811 | 62774.408 | 4.507989 | 0.00213704 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7919 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 80824.28 | 79854.92 | 0.9262 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00858111 | 50073.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80824.28 | 28.94 | 0.00822975 | 17.67 | 0.15632344 | -999.0000 | 27.00 | 0.00859374 | 27.00 | 0.00859374 | 37.9895 | 77201.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8871.142 | 6381.216 | 0.458215 | 0.00021725 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7894 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8216.94 | 8120.05 | 0.9263 | -999.0 | -999.0 | 28.04 | 17.65 | 0.00857976 | 50076.5 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8216.94 | 29.16 | 0.00823009 | 17.74 | 0.01563234 | -999.0000 | 27.00 | 0.00859212 | 27.00 | 0.00859212 | 37.9824 | 7846.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 425318.141 | 425318.141 | 21.548390 | 0.01041601 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 425318.14 | 425318.14 | 1.0000 | 25.46542753 | 21.548390 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 425318.14 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.5704 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9130.811 | 9130.811 | 0.472001 | 0.00022361 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9130.81 | 9130.81 | 1.0000 | 0.55780118 | 0.472001 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9130.81 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3119 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87261.811 | 87261.811 | 4.507989 | 0.00213704 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 87261.81 | 87261.81 | 1.0000 | 5.32744570 | 4.507989 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87261.81 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.4677 | 0.00 | 0.00807419 | 25.01 | 0.00807419 | 40.1884 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8871.142 | 8871.142 | 0.458215 | 0.00021725 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8871.14 | 8871.14 | 1.0000 | 0.54150922 | 0.458215 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8871.14 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.4116 | 0.00 | 0.00533899 | 24.07 | 0.00533899 | 28.2225 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.548390 | 25.46542753 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14546.91 | 14546.91 | 1.0000 | 25.46542753 | 21.548390 | 0.06 | 0.06 | 0.00844595 | 21183.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14546.91 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.5704 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.472001 | 0.55780118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.55780118 | 0.472001 | 0.13 | 0.13 | 0.00838602 | 21101.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3119 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.507989 | 5.32744570 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6720.07 | 6720.07 | 1.0000 | 5.32744570 | 4.507989 | 0.13 | 0.13 | 0.00796962 | 20065.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6720.07 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.4677 | 0.00 | 0.00807419 | 25.01 | 0.00807419 | 40.1884 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.458215 | 0.54150922 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.54150922 | 0.458215 | 0.13 | 0.13 | 0.00532942 | 13460.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.4116 | 0.00 | 0.00533899 | 24.07 | 0.00533899 | 28.2225 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.46 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 78.34 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.41 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 4.78 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 21.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4021.33 | 640.33 | 444.50 |
CORE_BOTTOM | 4206.67 | 150.00 | 0.00 |
CORE_MID | 3019.83 | 1059.33 | 14.33 |
CORE_TOP | 2299.67 | 2476.50 | 26.33 |
PERIMETER_BOT_ZN_3 | 2718.00 | 1745.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 3178.50 | 1483.00 | 100.50 |
PERIMETER_BOT_ZN_1 | 3744.33 | 1148.83 | 165.00 |
PERIMETER_BOT_ZN_4 | 4714.33 | 537.83 | 342.33 |
PERIMETER_MID_ZN_3 | 1717.00 | 3297.83 | 42.67 |
PERIMETER_MID_ZN_2 | 2133.33 | 2109.33 | 118.83 |
PERIMETER_MID_ZN_1 | 3172.00 | 1842.33 | 157.00 |
PERIMETER_MID_ZN_4 | 3032.83 | 2076.83 | 148.50 |
PERIMETER_TOP_ZN_3 | 1845.00 | 3797.00 | 370.50 |
PERIMETER_TOP_ZN_2 | 2446.00 | 2851.67 | 240.17 |
PERIMETER_TOP_ZN_1 | 2834.83 | 2417.67 | 220.50 |
PERIMETER_TOP_ZN_4 | 2817.17 | 2609.50 | 286.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 741.50 | 741.50 |
DATACENTER_MID_ZN_6 | 5943.00 | 10.83 | 10.83 |
DATACENTER_TOP_ZN_6 | 5912.33 | 77.83 | 73.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5875.00 | 5875.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5897.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 53.17 | 0.00 | 5.83 |
CORE_BOTTOM | 0.00 | 0.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 24.67 | 0.00 | 24.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 64.00 | 0.00 | 64.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 107.83 | 0.00 | 70.17 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 22.00 | 0.00 | 22.00 |
PERIMETER_MID_ZN_1 | 0.00 | 88.50 | 0.00 | 88.33 |
PERIMETER_MID_ZN_4 | 0.00 | 38.50 | 0.00 | 29.33 |
PERIMETER_TOP_ZN_3 | 2.83 | 0.00 | 0.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 1.33 | 18.83 | 0.00 | 18.83 |
PERIMETER_TOP_ZN_1 | 1.00 | 42.67 | 0.00 | 42.33 |
PERIMETER_TOP_ZN_4 | 0.67 | 38.83 | 0.00 | 29.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 3.33 | 0.00 | 3.33 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 219.50 | 0.00 | 215.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.83 | 564.00 | 0.17 | 468.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.664 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.228 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.883 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.856 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 1.115 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.549 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.770 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.635 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.815 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.232 | 0.075 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.458 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.504 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.833 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.315 | 0.090 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.506 | 0.087 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.540 | 0.090 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 34.092 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 67039959.91 | 0.00 | 67039959.91 | 0.00 | 67039959.91 | 37848132.68 | 3961.98 | 333.40 | 4464.61 | 218.31 |
CORE_BOTTOM | 51494180.51 | 0.00 | 51494180.51 | 0.00 | 51494180.51 | 33990283.35 | 3471.83 | 10.61 | 5277.57 | 459.00 |
CORE_MID | 0.36E+09 | 0.00 | 0.36E+09 | 0.00 | 0.36E+09 | 0.34E+09 | 3996.18 | 150.95 | 4612.86 | 100.71 |
CORE_TOP | 34386080.23 | 0.00 | 34386080.23 | 0.00 | 34386080.23 | 33990283.35 | 4071.79 | 176.57 | 4511.65 | 82.69 |
PERIMETER_BOT_ZN_3 | 5871540.23 | 0.00 | 5871540.23 | 258141.27 | 6129681.50 | 4267819.30 | 3501.94 | 54.54 | 5203.52 | 459.00 |
PERIMETER_BOT_ZN_2 | 5180614.78 | 0.00 | 5180614.78 | 172094.06 | 5352708.85 | 2750345.05 | 3451.56 | 42.89 | 5265.55 | 459.00 |
PERIMETER_BOT_ZN_1 | 9150971.08 | 0.00 | 9150971.08 | 258141.27 | 9409112.35 | 4267912.63 | 3441.77 | 43.48 | 5274.74 | 459.00 |
PERIMETER_BOT_ZN_4 | 8768927.61 | 0.00 | 8768927.61 | 172094.06 | 8941021.67 | 2750345.05 | 3327.13 | 28.38 | 5404.49 | 459.00 |
PERIMETER_MID_ZN_3 | 41395262.96 | 0.00 | 41395262.96 | 605406.74 | 42000669.70 | 42678193.03 | 4226.46 | 151.29 | 4382.25 | 100.71 |
PERIMETER_MID_ZN_2 | 40884280.74 | 0.00 | 40884280.74 | 403604.22 | 41287884.95 | 27503450.52 | 4211.54 | 139.89 | 4408.57 | 919.91 |
PERIMETER_MID_ZN_1 | 73493409.42 | 0.00 | 73493409.42 | 605406.74 | 74098816.16 | 42679126.28 | 3807.83 | 135.87 | 4816.31 | 100.71 |
PERIMETER_MID_ZN_4 | 48925872.11 | 0.00 | 48925872.11 | 403604.22 | 49329476.32 | 27503450.52 | 3915.87 | 143.84 | 4700.29 | 100.71 |
PERIMETER_TOP_ZN_3 | 4208406.74 | 0.00 | 4208406.74 | 751668.47 | 4960075.21 | 4267819.30 | 3988.79 | 251.78 | 4519.43 | 82.69 |
PERIMETER_TOP_ZN_2 | 4256720.62 | 0.00 | 4256720.62 | 501111.97 | 4757832.59 | 2750345.05 | 3929.22 | 268.50 | 4562.28 | 82.69 |
PERIMETER_TOP_ZN_1 | 7566452.65 | 0.00 | 7566452.65 | 751668.47 | 8318121.12 | 4267912.63 | 3912.94 | 181.75 | 4665.30 | 82.69 |
PERIMETER_TOP_ZN_4 | 4994417.26 | 0.00 | 4994417.26 | 501111.97 | 5495529.23 | 2750345.05 | 3935.24 | 261.64 | 4563.12 | 82.69 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.53E+09 | 0.00 | 0.53E+09 | 0.00 | 0.53E+09 | 10671554.30 | 9.55 | 59.50 | 8690.95 | 2817.00 |
Total Facility | 0.64E+10 | 0.00 | 0.64E+10 | 23546250.62 | 0.64E+10 | 0.50E+10 | 5224.30 | 4366.44 | 8750.12 | 3636.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 3.0572 | 0.0000 | 3.0572 | 0.0000 | 3.0572 | 1.2002 | 1289.09 | 332.36 | 4321.55 |
CORE_BOTTOM | 2.2796 | 0.0000 | 2.2796 | 0.0000 | 2.2796 | 1.0778 | 1085.05 | 7.97 | 4849.97 |
CORE_MID | 16.3779 | 0.0000 | 16.3779 | 0.0000 | 16.3779 | 10.7782 | 1279.44 | 150.95 | 4512.61 |
CORE_TOP | 1.5899 | 0.0000 | 1.5899 | 0.0000 | 1.5899 | 1.0778 | 1306.45 | 176.57 | 4459.98 |
PERIMETER_BOT_ZN_3 | 0.2599 | 0.0000 | 0.2599 | 0.0069 | 0.2668 | 0.1353 | 1111.53 | 51.43 | 4780.03 |
PERIMETER_BOT_ZN_2 | 0.2328 | 0.0000 | 0.2328 | 0.0046 | 0.2374 | 0.0872 | 1060.23 | 39.79 | 4842.98 |
PERIMETER_BOT_ZN_1 | 0.4131 | 0.0000 | 0.4131 | 0.0069 | 0.4201 | 0.1353 | 1051.09 | 40.32 | 4851.59 |
PERIMETER_BOT_ZN_4 | 0.3956 | 0.0000 | 0.3956 | 0.0046 | 0.4002 | 0.0872 | 939.79 | 25.46 | 4977.75 |
PERIMETER_MID_ZN_3 | 1.9010 | 0.0000 | 1.9010 | 0.0163 | 1.9173 | 1.3533 | 1509.71 | 151.29 | 4281.99 |
PERIMETER_MID_ZN_2 | 1.8506 | 0.0000 | 1.8506 | 0.0112 | 1.8618 | 0.8721 | 1203.93 | 136.56 | 3693.51 |
PERIMETER_MID_ZN_1 | 3.4010 | 0.0000 | 3.4010 | 0.0163 | 3.4173 | 1.3533 | 1091.08 | 135.87 | 4716.05 |
PERIMETER_MID_ZN_4 | 2.2569 | 0.0000 | 2.2569 | 0.0109 | 2.2678 | 0.8721 | 1199.13 | 143.84 | 4600.04 |
PERIMETER_TOP_ZN_3 | 0.1945 | 0.0000 | 0.1945 | 0.0202 | 0.2147 | 0.1353 | 1225.71 | 251.69 | 4465.60 |
PERIMETER_TOP_ZN_2 | 0.1975 | 0.0000 | 0.1975 | 0.0135 | 0.2110 | 0.0872 | 1165.67 | 268.35 | 4508.99 |
PERIMETER_TOP_ZN_1 | 0.3514 | 0.0000 | 0.3514 | 0.0202 | 0.3717 | 0.1353 | 1148.09 | 181.75 | 4613.16 |
PERIMETER_TOP_ZN_4 | 0.2312 | 0.0000 | 0.2312 | 0.0135 | 0.2447 | 0.0872 | 1170.25 | 261.64 | 4511.11 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 17.4988 | 0.0000 | 17.4988 | 0.0000 | 17.4988 | 0.3384 | 9.55 | 59.50 | 5873.95 |
Total Facility | 285.7396 | 0.0000 | 285.7396 | 0.6373 | 286.3770 | 158.4706 | 2407.30 | 4360.37 | 5933.12 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.11E+09 | 0.00 | 0.11E+09 | 48026705.38 | 3244.25 | 1.20 | 5514.54 | 459.00 |
VAV_MID WITH REHEAT | 0.78E+09 | 0.00 | 0.78E+09 | 0.48E+09 | 3723.78 | 2.71 | 5033.51 | 100.71 |
VAV_TOP WITH REHEAT | 77388554.51 | 0.00 | 77388554.51 | 48026705.38 | 3845.87 | 3.24 | 4910.88 | 82.69 |
CAV_BAS | 93628062.31 | 0.00 | 93628062.31 | 37848132.68 | 3935.82 | 1.76 | 4822.42 | 218.31 |
AIRLOOP DATACENTER BASEMENT | 0.74E+09 | 0.00 | 0.74E+09 | 10671554.30 | 9.55 | 0.00 | 8750.45 | 2817.00 |
AIRLOOP DATACENTER BOT | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3411840.17 | 0.00 | 3411840.17 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 5.0012 | 0.0000 | 5.0012 | 1.5229 | 885.02 | 0.46 | 5057.53 |
VAV_MID WITH REHEAT | 36.0684 | 0.0000 | 36.0684 | 15.2292 | 1007.04 | 2.71 | 4933.25 |
VAV_TOP WITH REHEAT | 3.5817 | 0.0000 | 3.5817 | 1.5229 | 1085.64 | 2.71 | 4854.65 |
CAV_BAS | 4.2697 | 0.0000 | 4.2697 | 1.2002 | 1281.74 | 0.51 | 4660.76 |
AIRLOOP DATACENTER BASEMENT | 24.4389 | 0.0000 | 24.4389 | 0.3384 | 9.55 | 0.00 | 5933.45 |
AIRLOOP DATACENTER BOT | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1595 | 0.0000 | 0.1595 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 37.41 | 5266.51 | 0.00 | 0.00 | 0.00 | 214.60 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 452.95 | 4298.34 | 0.00 | 0.00 | 0.00 | 292.15 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 48.13 | 4529.22 | 0.00 | 0.00 | 0.00 | 409.06 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 331.75 | 4559.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 59.50 | 8690.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.8462 | 6.0570 | 0.0000 | 0.0000 | 0.0000 | 2.3399 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.4425 | 46.4002 | 0.0000 | 0.0000 | 0.0000 | 23.1401 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8197 | 4.5515 | 0.0000 | 0.0000 | 0.0000 | 2.2370 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6799 | 5.7186 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4766 | 24.7254 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2184 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1187 |
Fields with Defaults | 3885 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 23443.62 | 293093.23 | 01-JAN-02:10 | 1599954.87 | 18-AUG-15:10 |
Electricity:Building | 16492.43 | 215843.22 | 14-MAY-17:20 | 958209.73 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 547.21 | 14055.89 | 01-JAN-00:10 | 24238.09 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16492.43 | 215843.22 | 14-MAY-17:20 | 958209.73 | 01-DEC-16:40 |
InteriorLights:Electricity | 1816.04 | 8587.06 | 30-APR-17:20 | 179838.04 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 122.81 | 598.35 | 01-JAN-00:10 | 10780.55 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1816.04 | 8587.06 | 30-APR-17:20 | 179838.04 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 1816.04 | 8587.06 | 30-APR-17:20 | 179838.04 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 122.81 | 598.35 | 01-JAN-00:10 | 10780.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1816.04 | 8587.06 | 30-APR-17:20 | 179838.04 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 399.91 | 4990.59 | 01-JAN-00:10 | 26888.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3999.04 | 49905.77 | 01-JAN-00:10 | 268882.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1102.91 | 5373.60 | 01-JAN-00:10 | 96816.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1102.91 | 5373.60 | 01-JAN-00:10 | 96816.88 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 399.90 | 4990.58 | 01-JAN-00:10 | 26888.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 110.29 | 537.36 | 01-JAN-00:10 | 9681.69 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 44.37 | 591.30 | 16-APR-17:10 | 3376.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.00 | 32.13 | 01-JAN-08:40 | 1215.63 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.00 | 32.13 | 01-JAN-08:40 | 1215.63 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.57 | 381.06 | 16-APR-17:10 | 2175.74 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.14 | 20.71 | 01-JAN-07:20 | 783.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.14 | 20.71 | 01-JAN-07:20 | 783.40 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 44.28 | 591.31 | 16-APR-17:10 | 3376.24 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.91 | 32.13 | 01-JAN-07:20 | 1215.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.91 | 32.13 | 01-JAN-07:20 | 1215.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.55 | 381.06 | 12-MAR-17:10 | 2175.73 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.11 | 20.71 | 01-JAN-08:40 | 783.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.11 | 20.71 | 01-JAN-08:40 | 783.40 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 443.56 | 5913.03 | 16-APR-17:10 | 33761.84 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 79.90 | 321.32 | 01-JAN-08:40 | 12156.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 79.90 | 321.32 | 01-JAN-08:40 | 12156.33 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 285.66 | 3810.58 | 16-APR-17:10 | 21757.42 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 51.31 | 207.07 | 01-JAN-07:20 | 7834.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 51.31 | 207.07 | 01-JAN-07:20 | 7834.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 442.71 | 5913.12 | 16-APR-17:10 | 33762.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 79.05 | 321.33 | 01-JAN-07:20 | 12156.59 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 79.05 | 321.33 | 01-JAN-07:20 | 12156.59 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 285.41 | 3810.56 | 12-MAR-17:10 | 21757.33 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 51.06 | 207.07 | 01-JAN-08:40 | 7834.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 51.06 | 207.07 | 01-JAN-08:40 | 7834.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 44.36 | 591.30 | 16-APR-17:10 | 3376.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.99 | 32.13 | 01-JAN-08:40 | 1215.63 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.99 | 32.13 | 01-JAN-08:40 | 1215.63 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.57 | 381.06 | 16-APR-17:10 | 2175.74 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.13 | 20.71 | 01-JAN-07:20 | 783.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.13 | 20.71 | 01-JAN-07:20 | 783.40 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 44.27 | 591.31 | 16-APR-17:10 | 3376.24 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.91 | 32.13 | 01-JAN-07:20 | 1215.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.91 | 32.13 | 01-JAN-07:20 | 1215.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.54 | 381.06 | 12-MAR-17:10 | 2175.73 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.11 | 20.71 | 01-JAN-08:40 | 783.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.11 | 20.71 | 01-JAN-08:40 | 783.40 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7529.67 | 95077.00 | 01-JAN-00:10 | 382672.17 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 34.81 | 168.86 | 01-JAN-00:10 | 3039.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 34.81 | 168.86 | 01-JAN-00:10 | 3039.65 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.66 | 1957.22 | 01-JAN-00:10 | 7949.46 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1556.56 | 19572.19 | 01-JAN-00:10 | 79494.63 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 17.76 | 86.14 | 01-JAN-00:10 | 1550.41 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 17.76 | 86.14 | 01-JAN-00:10 | 1550.41 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.66 | 1957.22 | 01-JAN-00:10 | 7949.46 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.78 | 8.61 | 01-JAN-00:10 | 155.04 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1877.61 | 3771.43 | 03-JAN-05:00 | 338544.68 | 07-AUG-10:30 |
HeatRejection:Electricity | 765.73 | 365.79 | 03-JAN-07:10 | 70388.50 | 22-MAR-12:40 |
General:HeatRejection:Electricity | 765.73 | 365.79 | 03-JAN-07:10 | 70388.50 | 22-MAR-12:40 |
ElectricityProduced:Facility | 599.75 | -0.00 | 27-FEB-06:30 | 89495.83 | 27-MAY-11:40 |
ElectricityProduced:Plant | 599.75 | -0.00 | 27-FEB-06:30 | 89495.83 | 27-MAY-11:40 |
Photovoltaic:ElectricityProduced | 625.78 | 0.00 | 01-JAN-00:10 | 93851.32 | 27-MAY-11:50 |
PowerConversion:ElectricityProduced | -26.03 | -4355.49 | 27-MAY-11:50 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 3661.58 | 45928.78 | 01-JAN-07:30 | 347575.81 | 05-DEC-16:00 |
ExteriorEquipment:Electricity | 1203.73 | 17814.45 | 01-JAN-00:10 | 73697.50 | 24-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.40 | 979.82 | 01-JAN-00:10 | 3377.37 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
ElectricityPurchased:Plant | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
Cogeneration:ElectricityPurchased | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
ElectricityNet:Plant | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
Cogeneration:ElectricityNet | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
General:Cogeneration:ElectricityNet | 22843.86 | 243458.95 | 14-MAY-11:00 | 1554245.24 | 15-AUG-15:50 |
Fans:Electricity | 2153.74 | 41818.03 | 03-JAN-05:00 | 172171.51 | 16-OCT-08:20 |
General:Fans:Electricity | 2153.74 | 41818.03 | 03-JAN-05:00 | 172171.51 | 16-OCT-08:20 |
ExteriorLights:Electricity | 262.66 | 0.00 | 01-JAN-07:00 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 262.66 | 0.00 | 01-JAN-07:00 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 1729.45 | 2524.42 | 02-JAN-08:00 | 363058.63 | 07-AUG-10:30 |
General:Cooling:Electricity | 1729.45 | 2524.42 | 02-JAN-08:00 | 363058.63 | 07-AUG-10:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 475.66 | 0.00 | 01-JAN-00:40 | 100000.00 | 08-JAN-11:50 |
General:Humidifier:Electricity | 475.66 | 0.00 | 01-JAN-00:40 | 100000.00 | 08-JAN-11:50 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 360.21 | 3281.29 | 01-JAN-00:10 | 41094.79 | 16-OCT-14:50 |
General:Pumps:Electricity | 360.21 | 3281.29 | 01-JAN-00:10 | 41094.79 | 16-OCT-14:50 |
WIRED_LTG_ELECTRICITY | 51.03 | 0.00 | 01-JAN-00:10 | 5053.45 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 758.27 | 7280.88 | 02-JAN-05:20 | 384402.50 | 03-JAN-07:10 |
NaturalGas:Plant | 758.27 | 7280.88 | 02-JAN-05:20 | 384402.50 | 03-JAN-07:10 |
Heating:NaturalGas | 43.69 | 0.00 | 01-JAN-00:10 | 353777.37 | 03-JAN-07:10 |
Boiler:Heating:NaturalGas | 43.69 | 0.00 | 01-JAN-00:10 | 353777.37 | 03-JAN-07:10 |
WaterSystems:NaturalGas | 714.58 | 7280.88 | 02-JAN-05:20 | 78002.07 | 30-JAN-12:50 |
Water Heater:WaterSystems:NaturalGas | 714.58 | 7280.88 | 02-JAN-05:20 | 78002.07 | 30-JAN-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10313.31 | 9772.88 | 02-JAN-08:00 | 2221926.45 | 07-AUG-10:30 |
PlantLoopCoolingDemand:HVAC | 10313.31 | 9772.88 | 02-JAN-08:00 | 2221926.45 | 07-AUG-10:30 |
CoolingCoils:PlantLoopCoolingDemand | 10313.31 | 9772.88 | 02-JAN-08:00 | 2221926.45 | 07-AUG-10:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6173.80 | 0.00 | 01-JAN-00:40 | 0.00 | 16-OCT-11:10 |
Water:HVAC | 176.94 | 0.00 | 01-JAN-00:40 | 0.00 | 04-DEC-05:20 |
Humidifier:Water | 176.94 | 0.00 | 01-JAN-00:40 | 0.00 | 04-DEC-05:20 |
General:Humidifier:Water | 176.94 | 0.00 | 01-JAN-00:40 | 0.00 | 04-DEC-05:20 |
MainsWater:Facility | 6173.80 | 0.00 | 01-JAN-00:40 | 0.00 | 16-OCT-11:10 |
MainsWater:HVAC | 176.94 | 0.00 | 01-JAN-00:40 | 0.00 | 04-DEC-05:20 |
Humidifier:MainsWater | 176.94 | 0.00 | 01-JAN-00:40 | 0.00 | 04-DEC-05:20 |
General:Humidifier:MainsWater | 176.94 | 0.00 | 01-JAN-00:40 | 0.00 | 04-DEC-05:20 |
Water:Plant | 5996.86 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5996.86 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3716.69 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:Water | 3716.69 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 3716.69 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:MainsWater | 3716.69 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 44316.18 | 103412.89 | 01-JAN-05:30 | 8359134.92 | 07-AUG-10:30 |
EnergyTransfer:Building | 17784.71 | 93392.94 | 01-JAN-06:50 | 1352093.20 | 14-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 598.25 | 0.00 | 01-JAN-00:10 | 72214.64 | 10-OCT-05:10 |
Heating:EnergyTransfer | 27.44 | 0.00 | 03-JAN-22:10 | 157968.10 | 03-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.97 | 0.00 | 01-JAN-00:10 | 15723.00 | 14-OCT-16:10 |
General:Heating:EnergyTransfer | 27.44 | 0.00 | 03-JAN-22:10 | 157968.10 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.97 | 0.00 | 01-JAN-00:10 | 15723.00 | 14-OCT-16:10 |
Cooling:EnergyTransfer | 17757.27 | 92863.17 | 01-JAN-07:00 | 1352093.20 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 596.28 | 0.00 | 01-JAN-00:10 | 72214.64 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 17757.27 | 92863.17 | 01-JAN-07:00 | 1352093.20 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 596.28 | 0.00 | 01-JAN-00:10 | 72214.64 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 582.94 | 0.00 | 01-JAN-00:10 | 51711.12 | 13-NOV-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 582.94 | 0.00 | 01-JAN-00:10 | 51711.12 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 582.94 | 0.00 | 01-JAN-00:10 | 51711.12 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_MID | 4163.37 | 0.00 | 01-JAN-00:10 | 376509.36 | 26-APR-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4163.37 | 0.00 | 01-JAN-00:10 | 376509.36 | 26-APR-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4163.37 | 0.00 | 01-JAN-00:10 | 376509.36 | 26-APR-05:10 |
EnergyTransfer:Zone:CORE_TOP | 369.05 | 0.00 | 01-JAN-00:10 | 43292.79 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.15 | 0.00 | 01-JAN-00:10 | 25664.44 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.15 | 0.00 | 01-JAN-00:10 | 25664.44 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 368.90 | 0.00 | 01-JAN-00:10 | 43292.79 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 368.90 | 0.00 | 01-JAN-00:10 | 43292.79 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.25 | 0.00 | 01-JAN-00:10 | 8406.62 | 16-OCT-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.25 | 0.00 | 01-JAN-00:10 | 8406.62 | 16-OCT-11:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.25 | 0.00 | 01-JAN-00:10 | 8406.62 | 16-OCT-11:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 57.81 | 0.00 | 01-JAN-00:10 | 10704.96 | 16-OCT-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 57.81 | 0.00 | 01-JAN-00:10 | 10704.96 | 16-OCT-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 57.81 | 0.00 | 01-JAN-00:10 | 10704.96 | 16-OCT-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.56 | 0.00 | 01-JAN-00:10 | 17643.43 | 30-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.56 | 0.00 | 01-JAN-00:10 | 17643.43 | 30-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.56 | 0.00 | 01-JAN-00:10 | 17643.43 | 30-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.72 | 0.00 | 01-JAN-00:10 | 14725.27 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.72 | 0.00 | 01-JAN-00:10 | 14725.27 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 99.72 | 0.00 | 01-JAN-00:10 | 14725.27 | 18-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 451.14 | 0.00 | 01-JAN-00:10 | 72339.95 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.95 | 0.00 | 01-JAN-00:10 | 46661.87 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.95 | 0.00 | 01-JAN-00:10 | 46661.87 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 450.19 | 0.00 | 01-JAN-00:10 | 72339.95 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 450.19 | 0.00 | 01-JAN-00:10 | 72339.95 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 467.78 | 0.00 | 01-JAN-00:10 | 106982.35 | 14-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.33 | 0.00 | 01-JAN-00:10 | 29180.65 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.33 | 0.00 | 01-JAN-00:10 | 29180.65 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 467.45 | 0.00 | 01-JAN-00:10 | 106982.35 | 14-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 467.45 | 0.00 | 01-JAN-00:10 | 106982.35 | 14-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 918.09 | 0.00 | 01-JAN-00:10 | 171367.76 | 31-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.15 | 0.00 | 01-JAN-00:10 | 39138.16 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.15 | 0.00 | 01-JAN-00:10 | 39138.16 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 917.93 | 0.00 | 01-JAN-00:10 | 171367.76 | 31-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 917.93 | 0.00 | 01-JAN-00:10 | 171367.76 | 31-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 570.09 | 0.00 | 01-JAN-00:10 | 121846.26 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.10 | 0.00 | 01-JAN-00:10 | 20381.58 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.10 | 0.00 | 01-JAN-00:10 | 20381.58 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 570.00 | 0.00 | 01-JAN-00:10 | 121846.26 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 570.00 | 0.00 | 01-JAN-00:10 | 121846.26 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.93 | 0.00 | 01-JAN-00:10 | 10169.03 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.93 | 0.00 | 01-JAN-00:10 | 10169.03 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.93 | 0.00 | 01-JAN-00:10 | 10169.03 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 41.00 | 0.00 | 01-JAN-00:10 | 7971.16 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 41.00 | 0.00 | 01-JAN-00:10 | 7971.16 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.11 | 0.00 | 01-JAN-00:10 | 10544.63 | 14-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.72 | 0.00 | 01-JAN-00:10 | 6545.30 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.72 | 0.00 | 01-JAN-00:10 | 6545.30 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.39 | 0.00 | 01-JAN-00:10 | 10544.63 | 14-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.39 | 0.00 | 01-JAN-00:10 | 10544.63 | 14-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.63 | 0.00 | 01-JAN-00:10 | 18201.11 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.66 | 0.00 | 01-JAN-00:10 | 8713.47 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.66 | 0.00 | 01-JAN-00:10 | 8713.47 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 83.97 | 0.00 | 01-JAN-00:10 | 18201.11 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 83.97 | 0.00 | 01-JAN-00:10 | 18201.11 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.22 | 0.00 | 01-JAN-00:10 | 12746.24 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.42 | 0.00 | 01-JAN-00:10 | 4902.75 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.42 | 0.00 | 01-JAN-00:10 | 4902.75 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.80 | 0.00 | 01-JAN-00:10 | 12746.24 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.80 | 0.00 | 01-JAN-00:10 | 12746.24 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.37 | 0.00 | 01-JAN-00:10 | 8105.38 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.09 | 0.00 | 01-JAN-00:10 | 3126.11 | 03-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.09 | 0.00 | 01-JAN-00:10 | 3126.11 | 03-DEC-09:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 59.28 | 0.00 | 01-JAN-00:10 | 8105.38 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 59.28 | 0.00 | 01-JAN-00:10 | 8105.38 | 16-OCT-16:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 325.88 | 0.00 | 01-JAN-00:10 | 58335.57 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.60 | 0.00 | 01-JAN-00:10 | 28042.34 | 02-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.60 | 0.00 | 01-JAN-00:10 | 28042.34 | 02-JAN-11:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 316.27 | 0.00 | 01-JAN-00:10 | 58335.57 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 316.27 | 0.00 | 01-JAN-00:10 | 58335.57 | 16-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.25 | 0.00 | 01-JAN-00:10 | 15632.75 | 16-OCT-14:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.24 | 0.00 | 01-JAN-00:10 | 8806.18 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.24 | 0.00 | 01-JAN-00:10 | 8806.18 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 52.01 | 0.00 | 01-JAN-00:10 | 15632.75 | 16-OCT-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 52.01 | 0.00 | 01-JAN-00:10 | 15632.75 | 16-OCT-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.71 | 1127.55 | 10-JAN-07:40 | 8061.09 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.71 | 1127.55 | 10-JAN-07:40 | 8061.09 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.71 | 1127.55 | 10-JAN-07:40 | 8061.09 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1263.23 | 2631.80 | 01-JAN-07:00 | 74711.80 | 06-AUG-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1263.23 | 2631.80 | 01-JAN-07:00 | 74711.80 | 06-AUG-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1263.23 | 2631.80 | 01-JAN-07:00 | 74711.80 | 06-AUG-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.09 | 5.04 | 05-JAN-04:40 | 7610.17 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-11:00 | 531.82 | 08-JAN-07:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-11:00 | 531.82 | 08-JAN-07:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.96 | 0.00 | 01-JAN-00:10 | 7610.17 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.96 | 0.00 | 01-JAN-00:10 | 7610.17 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7138.24 | 87173.29 | 14-MAY-05:00 | 367587.65 | 18-AUG-19:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7138.24 | 87173.29 | 14-MAY-05:00 | 367587.65 | 18-AUG-19:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7138.24 | 87173.29 | 14-MAY-05:00 | 367587.65 | 18-AUG-19:50 |
PlantLoopHeatingDemand:Facility | 417.31 | 0.00 | 01-JAN-00:10 | 259728.96 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 377.81 | 0.00 | 01-JAN-00:10 | 43842.46 | 31-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 377.81 | 0.00 | 01-JAN-00:10 | 43842.46 | 31-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 377.81 | 0.00 | 01-JAN-00:10 | 43842.46 | 31-JAN-12:30 |
EnergyTransfer:HVAC | 9375.02 | 9715.80 | 01-JAN-07:00 | 2091745.58 | 07-AUG-10:30 |
HeatingCoils:EnergyTransfer | 39.50 | 0.00 | 01-JAN-00:10 | 245273.91 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 39.50 | 0.00 | 01-JAN-00:10 | 245273.91 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 39.50 | 0.00 | 01-JAN-00:10 | 245273.91 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 9335.52 | 7248.46 | 02-JAN-08:00 | 2091745.58 | 07-AUG-10:30 |
EnergyTransfer:Plant | 17156.45 | 0.00 | 01-JAN-00:10 | 4973493.56 | 07-AUG-10:30 |
LoopToLoop:EnergyTransfer | 5326.29 | 0.00 | 01-JAN-00:10 | 1570273.64 | 07-AUG-10:30 |
WaterSystems:EnergyTransfer | 377.81 | 0.00 | 01-JAN-00:10 | 43842.46 | 31-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 377.81 | 0.00 | 01-JAN-00:10 | 43842.46 | 31-JAN-12:30 |
Boilers:EnergyTransfer | 39.23 | 0.00 | 01-JAN-00:10 | 311973.85 | 03-JAN-07:10 |
Chillers:EnergyTransfer | 5330.72 | 0.00 | 01-JAN-00:10 | 1568915.70 | 07-AUG-10:30 |
HeatRejection:EnergyTransfer | 6082.39 | 0.00 | 01-JAN-00:10 | 1801793.46 | 07-AUG-10:30 |
General:HeatRejection:EnergyTransfer | 6082.39 | 0.00 | 01-JAN-00:10 | 1801793.46 | 07-AUG-10:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.968 | -596.280 | 0.000 | 0.000 | 92.728 | 122.809 | 424.397 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -45.623 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -582.946 | 0.000 | 0.000 | 83.412 | 110.291 | 289.614 | 0.000 | 0.000 | 0.000 | 99.629 | 0.000 | 0.000 | 0.000 | 0.000 | -0.006 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4163.389 | 0.000 | 0.000 | 836.788 | 1102.914 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -672.440 |
CORE_TOP | 0.000 | 0.000 | 0.146 | -368.903 | 0.000 | 0.000 | 84.993 | 110.291 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -116.141 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -65.251 | 0.000 | 0.000 | 10.539 | 8.002 | 36.365 | 22.049 | 0.000 | 0.020 | 40.210 | 0.000 | -49.290 | 0.000 | -2.646 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -57.814 | 0.000 | 0.000 | 6.775 | 5.136 | 23.435 | 50.898 | 0.000 | 0.012 | 4.463 | 0.000 | -31.127 | 0.000 | -1.778 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -105.561 | 0.000 | 0.000 | 10.498 | 7.911 | 36.366 | 100.577 | 0.000 | 0.018 | 1.248 | 0.000 | -48.327 | 0.000 | -2.729 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -99.717 | 0.000 | 0.000 | 6.739 | 5.111 | 23.435 | 56.701 | 0.000 | 0.012 | 46.697 | 0.000 | -36.946 | 0.000 | -2.032 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.952 | -450.191 | 0.000 | 0.000 | 108.230 | 79.902 | 363.654 | 235.540 | 0.000 | 0.523 | 162.288 | 0.000 | -446.290 | 0.000 | -54.608 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.327 | -467.457 | 0.000 | 0.000 | 50.097 | 51.309 | 234.352 | 507.523 | 0.000 | 0.265 | 0.003 | 0.000 | -297.124 | 0.000 | -39.379 | -39.913 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.154 | -917.952 | 0.000 | 0.000 | 105.574 | 79.055 | 363.660 | 1002.111 | 0.000 | 0.393 | 0.025 | 0.000 | -467.514 | 0.000 | -61.251 | -104.229 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.096 | -570.002 | 0.000 | 0.000 | 68.501 | 51.055 | 234.351 | 577.645 | 0.000 | 0.296 | 2.055 | 0.000 | -322.921 | 0.000 | -41.075 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.932 | -41.001 | 0.000 | 0.000 | 11.058 | 7.990 | 36.365 | 24.392 | 0.000 | 0.069 | 6.900 | 0.000 | -41.489 | 0.000 | -6.217 | -0.002 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.721 | -45.389 | 0.000 | 0.000 | 6.898 | 5.131 | 23.435 | 51.451 | 0.000 | 0.034 | 0.002 | 0.000 | -27.895 | 0.000 | -4.517 | -9.869 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.659 | -83.971 | 0.000 | 0.000 | 10.689 | 7.905 | 36.366 | 100.774 | 0.000 | 0.048 | 0.002 | 0.000 | -44.150 | 0.000 | -7.126 | -21.194 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.420 | -53.804 | 0.000 | 0.000 | 6.952 | 5.105 | 23.435 | 57.931 | 0.000 | 0.037 | 0.000 | 0.000 | -30.555 | 0.000 | -4.800 | -4.720 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.712 | 0.000 | 0.000 | 0.950 | 1.776 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.894 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1263.232 | 0.000 | 0.000 | 9.501 | 17.757 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -302.832 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.130 | -118.962 | 0.000 | 0.000 | 0.950 | 1.776 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -37.775 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7138.230 | 0.000 | 0.000 | 20.361 | 34.812 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -411.801 |
GROUNDFLOOR_PLENUM | 1.089 | -59.279 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.033 | 63.921 | 0.000 | 0.000 | 0.000 | -5.763 | 0.000 |
MIDFLOOR_PLENUM | 9.602 | -316.275 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.632 | 404.089 | 0.000 | 0.000 | 0.000 | -98.048 | 0.000 |
TOPFLOOR_PLENUM | 9.241 | -52.008 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.056 | 53.118 | 0.000 | 0.000 | 0.000 | -10.408 | -0.003 |
Total Facility | 19.933 | -427.562 | 7.506 | -17329.765 | 0.000 | 0.000 | 1532.234 | 1816.038 | 14676.396 | 2787.593 | 0.000 | 2.447 | 884.653 | 0.000 | -1843.628 | 0.000 | -342.378 | -1783.448 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-MAY-04:11 | 0.00 | 0.00 | 0.00 | -97771.24 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 83715.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | -86045.10 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 79570.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 | -723935.38 | 0.00 | 0.00 | 8362.05 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 633726.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-AUG-05:02 | 0.00 | 0.00 | 0.00 | -68157.31 | 0.00 | 0.00 | 847.15 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 59125.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 19-JUN-05:02 | 0.00 | 0.00 | 0.00 | -10290.85 | 0.00 | 0.00 | 114.92 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 10833.48 | 0.00 | -1662.62 | 0.00 | -22.64 | 0.00 |
PERIMETER_BOT_ZN_2 | 15-OCT-08:42 | 0.00 | 0.00 | 0.00 | -18413.22 | 0.00 | 0.00 | 22.83 | 20.71 | 464.11 | 13146.30 | 0.00 | 86.25 | 4673.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-11:21 | 0.00 | 0.00 | 0.00 | -22177.56 | 0.00 | 0.00 | 33.12 | 32.13 | 720.19 | 21340.42 | 0.00 | 68.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16.52 |
PERIMETER_BOT_ZN_4 | 30-JUL-15:31 | 0.00 | 0.00 | 0.00 | -24718.00 | 0.00 | 0.00 | 19.98 | 20.71 | 464.11 | 12455.98 | 0.00 | 0.00 | 11879.69 | 0.00 | -0.00 | 0.00 | -122.47 | 0.00 |
PERIMETER_MID_ZN_3 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -88921.13 | 0.00 | 0.00 | 1120.49 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 87136.06 | 0.00 | -9604.35 | 0.00 | -8.23 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-08:62 | 0.00 | 0.00 | 0.00 | -190089.58 | 0.00 | 0.00 | 231.09 | 207.07 | 4641.14 | 133295.62 | 0.00 | 0.00 | 51970.98 | 0.00 | -0.00 | 0.00 | -256.33 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:32 | 0.00 | 0.00 | 0.00 | -216561.50 | 0.00 | 0.00 | 337.10 | 321.33 | 7201.95 | 178948.88 | 0.00 | 0.00 | 35806.48 | 0.00 | -0.00 | 0.00 | -6054.24 | 0.00 |
PERIMETER_MID_ZN_4 | 20-AUG-16:01 | 0.00 | 0.00 | 0.00 | -212682.25 | 0.00 | 0.00 | 215.57 | 207.07 | 4641.11 | 131096.15 | 0.00 | 0.00 | 79176.45 | 0.00 | -0.00 | 0.00 | -2654.09 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -10382.75 | 0.00 | 0.00 | 111.67 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 10176.24 | 0.00 | -932.07 | 0.00 | -0.81 | 0.00 |
PERIMETER_TOP_ZN_2 | 13-AUG-09:02 | 0.00 | 0.00 | 0.00 | -18513.90 | 0.00 | 0.00 | 24.25 | 20.71 | 464.11 | 11588.47 | 0.00 | 0.00 | 6576.25 | 0.00 | -0.00 | 0.00 | -159.89 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-11:11 | 0.00 | 0.00 | 0.00 | -23860.59 | 0.00 | 0.00 | 32.02 | 32.13 | 720.19 | 21058.24 | 0.00 | 141.22 | 1876.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 15-OCT-15:11 | 0.00 | 0.00 | 0.00 | -23094.16 | 0.00 | 0.00 | 19.63 | 20.71 | 464.11 | 14084.47 | 0.00 | 67.33 | 8437.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-17:41 | 0.00 | 0.00 | 0.00 | -8061.09 | 0.00 | 0.00 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 258.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-17:52 | 0.00 | 0.00 | 0.00 | -74711.65 | 0.00 | 0.00 | 0.00 | 86.14 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3318.71 |
DATACENTER_TOP_ZN_6 | 06-AUG-17:41 | 0.00 | 0.00 | 0.00 | -7610.17 | 0.00 | 0.00 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -192.86 |
DATACENTER_BASEMENT_ZN_6 | 26-AUG-17:02 | 0.00 | 0.00 | 0.00 | -369270.66 | 0.00 | 0.00 | 111.49 | 168.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10642.22 |
GROUNDFLOOR_PLENUM | 16-OCT-05:15 | 0.00 | -9970.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10034.67 | 0.00 | -0.00 | 0.00 | -63.80 | 0.00 |
MIDFLOOR_PLENUM | 02-OCT-05:15 | 0.00 | -76223.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76980.70 | 0.00 | -0.00 | 0.00 | -757.53 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-14:20 | 0.00 | -15633.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.26 | 15467.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:02 | 0.00 | 1550.04 | 0.00 | -1582853.89 | 0.00 | 0.00 | 16133.05 | 10253.98 | 616289.16 | 0.00 | 0.00 | 0.00 | 1017064.70 | 0.00 | -74549.33 | 0.00 | -3887.71 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-OCT-16:02 | 0.00 | 0.00 | 16958.57 | 0.00 | 0.00 | 0.00 | 520.12 | 598.90 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31535.14 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 56055.69 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -62530.67 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 03-JAN-06:02 | 0.00 | 0.00 | 91087.41 | 0.00 | 0.00 | 0.00 | 1491.47 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39990.11 | 0.00 | -1203.20 | -61662.74 |
PERIMETER_MID_ZN_2 | 03-JAN-06:02 | 0.00 | 0.00 | 96282.04 | 0.00 | 0.00 | 0.00 | 956.89 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26862.23 | 0.00 | -824.51 | -76175.19 |
PERIMETER_MID_ZN_1 | 30-MAR-05:03 | 0.00 | 0.00 | 123792.15 | 0.00 | 0.00 | 0.00 | 1461.01 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40110.56 | 0.00 | -2884.50 | -92535.42 |
PERIMETER_MID_ZN_4 | 09-JAN-06:02 | 0.00 | 0.00 | 86979.73 | 0.00 | 0.00 | 0.00 | 941.49 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31353.96 | 0.00 | -1688.33 | -61501.88 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 11941.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1610.71 | 0.00 | -760.82 | -10382.50 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 13264.68 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1105.36 | 0.00 | -556.06 | -12127.22 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 16284.99 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1735.52 | 0.00 | -858.23 | -14504.29 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 13102.31 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1254.40 | 0.00 | -618.82 | -11753.04 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 08-JAN-07:00 | 0.00 | 0.00 | 531.83 | 0.00 | 0.00 | 0.00 | 5.49 | 8.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2494.54 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:12 | 10578.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -787.85 | -9790.32 |
MIDFLOOR_PLENUM | 15-OCT-14:12 | 66427.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5754.87 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -72181.97 |
TOPFLOOR_PLENUM | 05-JUN-05:02 | 13026.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -132.43 | -12893.98 |
Total Facility | 03-JAN-06:02 | -428356.05 | 416730.60 | 434301.67 | -416730.60 | 0.00 | 0.00 | 18375.03 | 10253.98 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -164097.78 | 0.00 | -7342.30 | -124549.51 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.5201 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.4618 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 89.7593 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 78.3426 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.1121 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.4124 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.7840 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.7840 | 0.2509 | 1.0000 | Not calculated | 1.2002 | 0.2509 | ||
AIRLOOP DATACENTER BASEMENT | 21.5482 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5484 | 0.0157 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4720 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4720 | 0.0331 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5080 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5080 | 0.0347 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4582 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4582 | 0.0341 | 1.0000 | Not calculated | 0.0156 | 0.0341 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.7601 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2853 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 44.8797 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8149 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.5560 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2851 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.7840 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.7840 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2509 | ||
AIRLOOP DATACENTER BASEMENT | 21.5482 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5482 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4720 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4720 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5080 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5080 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4582 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4582 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0341 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7840 | 4.7840 | 4.7840 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2335 | 5.2335 | 1.6172 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.0852 | 49.0852 | 16.1490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7746 | 4.7746 | 1.6186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8200 | 0.8200 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0186 | 1.0186 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1597 | 1.1597 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2883 | 1.2883 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.6178 | 7.6178 | 2.0263 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5356 | 10.5356 | 1.3064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2619 | 11.2619 | 2.0271 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2589 | 11.2589 | 1.3060 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8660 | 0.8660 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0510 | 1.0510 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2239 | 1.2239 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1966 | 1.1966 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4720 | 0.4720 | 0.4720 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5080 | 4.5080 | 4.5080 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4582 | 0.4582 | 0.4582 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5482 | 21.5482 | 21.5482 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.5201 | 8.4618 | 9.5201 | 2.2853 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 89.7593 | 78.3426 | 89.7593 | 22.8149 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.1121 | 8.4124 | 9.1121 | 2.2851 | 0.0000 | 1.0000 |
CAV_BAS | 4.7840 | 4.7840 | 4.7840 | 4.7840 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5482 | 21.5484 | 21.5482 | 21.5482 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4720 | 0.4720 | 0.4720 | 0.4720 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5080 | 4.5080 | 4.5080 | 4.5080 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4582 | 0.4582 | 0.4582 | 0.4582 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7840 | 4.7840 | 4.7840 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6168 | 2.6168 | 1.6172 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.5426 | 24.5426 | 16.1490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3873 | 2.3873 | 1.6186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4100 | 0.4100 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5093 | 0.5093 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5799 | 0.5799 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6441 | 0.6441 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8089 | 3.8089 | 2.0263 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2678 | 5.2678 | 1.3064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6309 | 5.6309 | 2.0271 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6294 | 5.6294 | 1.3060 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4330 | 0.4330 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5255 | 0.5255 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6119 | 0.6119 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5983 | 0.5983 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4720 | 0.4720 | 0.4720 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5080 | 4.5080 | 4.5080 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4582 | 0.4582 | 0.4582 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5482 | 21.5482 | 21.5482 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.7601 | 2.2853 | 2.2853 | 2.2853 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 44.8797 | 22.8149 | 22.8149 | 22.8149 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.5560 | 2.2851 | 2.2851 | 2.2851 | 0.0000 | 1.0000 |
CAV_BAS | 4.7840 | 4.7840 | 4.7840 | 4.7840 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5482 | 21.5482 | 21.5482 | 21.5482 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4720 | 0.4720 | 0.4720 | 0.4720 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5080 | 4.5080 | 4.5080 | 4.5080 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4582 | 0.4582 | 0.4582 | 0.4582 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 468.67 |
Number of hours not met | 468.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 43.69 | 353777.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1729.45 | 363058.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1816.04 | 179838.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.66 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.40 | 3377.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2153.74 | 172171.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 360.21 | 41094.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 765.73 | 70388.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 475.66 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 714.58 | 78002.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 23443.62 |
Natural Gas | 0.00 | 758.27 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 24201.89 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 625.78 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 39.21 |
Space Heating | 0.00 |
Space Cooling | 37.34 |
Fans (All) | 46.50 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 506.12 |
Subtotal | 506.12 |
Natural Gas [MJ/m2] | |
Space Heating | 0.94 |
Service Water Heating | 15.43 |
Miscellaneous (All) | 16.37 |
Subtotal | 16.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.50 |
Space Heating | 0.18 |
Space Cooling | 7.15 |
Fans (All) | 8.90 |
Service Water Heating | 2.95 |
Receptacle Equipment | 60.64 |
Miscellaneous | 12.68 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2192. | 8760. |
LTG_SCH_DATACENTER | 1950. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 970. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8223.17 | 536.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8698.50 | 61.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8688.17 | 71.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8687.00 | 73.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7957.33 | 802.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8682.67 | 77.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8680.33 | 79.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8608.33 | 151.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8680.50 | 79.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8697.33 | 62.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8613.17 | 146.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6871.50 | 1888.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6812.33 | 1947.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6760.67 | 1999.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 4109.83 | 4650.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8711.33 | 48.67 | 0.00 | 0.00 | 0.00 |
Min | 4109.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 4650.17 | 0.00 | 0.00 | 0.00 |
Average | 8208.79 | 551.21 | 0.00 | 0.00 | 0.00 |
Sum | 188802.17 | 12677.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367601.00 | 1015.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330730.00 | 83.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1053.00 | 1215.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1020.33 | 1247.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 989.17 | 1278.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 47907.83 | 55487.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367601.00 | 55487.17 | 0.00 | 0.00 | 0.00 |
Average | 77712.01 | 2622.90 | 0.00 | 0.00 | 0.00 |
Sum | 1787376.33 | 60326.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6949.50 | 1810.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7719.50 | 1040.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7900.83 | 859.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8135.17 | 624.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8448.50 | 311.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8421.33 | 338.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8343.67 | 416.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7254.67 | 1505.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8610.17 | 149.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8351.33 | 408.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8385.17 | 374.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7987.50 | 772.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8651.50 | 108.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8446.33 | 313.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8490.67 | 269.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8098.33 | 661.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7883.33 | 876.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7827.33 | 932.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7782.00 | 978.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 4959.33 | 3800.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7951.17 | 808.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8137.83 | 622.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7922.00 | 838.00 | 0.00 | 0.00 | 0.00 |
Min | 4959.33 | 108.50 | 0.00 | 0.00 | 0.00 |
Max | 8651.50 | 3800.67 | 0.00 | 0.00 | 0.00 |
Average | 7941.62 | 818.38 | 0.00 | 0.00 | 0.00 |
Sum | 182657.17 | 18822.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 345221.33 | 23394.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329211.00 | 1602.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329657.17 | 1155.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330045.00 | 768.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1575.50 | 692.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1534.83 | 733.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1511.67 | 756.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 58175.67 | 45219.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 345221.33 | 45219.33 | 0.00 | 0.00 | 0.00 |
Average | 77103.53 | 3231.38 | 0.00 | 0.00 | 0.00 |
Sum | 1773381.17 | 74321.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495171E+11 | 94182.01 | 02-JAN-05:11 | 11.00 | 9.07 | 0.566659E+10 | 7499.42 | 10-JAN-14:20 | 16.67 | 11.79 |
February | 0.424243E+11 | 93775.84 | 21-FEB-05:12 | 8.00 | 6.97 | 0.513732E+10 | 7500.20 | 01-FEB-14:09 | 8.00 | 6.97 |
March | 0.501676E+11 | 93970.49 | 20-MAR-04:12 | 11.00 | 10.65 | 0.613096E+10 | 7499.38 | 01-MAR-14:09 | 11.00 | 10.65 |
April | 0.477790E+11 | 94947.45 | 10-APR-04:12 | 12.00 | 10.34 | 0.544708E+10 | 7499.40 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.474912E+11 | 97779.94 | 30-MAY-04:11 | 11.00 | 10.06 | 0.589733E+10 | 7499.45 | 05-MAY-13:00 | 11.00 | 10.06 |
June | 0.485736E+11 | 93429.72 | 05-JUN-04:12 | 12.00 | 10.91 | 0.587792E+10 | 7499.21 | 27-JUN-09:20 | 23.00 | 18.04 |
July | 0.501401E+11 | 86924.11 | 10-JUL-04:12 | 17.00 | 13.94 | 0.546860E+10 | 7499.20 | 13-JUL-09:20 | 22.00 | 17.64 |
August | 0.548318E+11 | 88217.16 | 28-AUG-04:11 | 14.00 | 14.00 | 0.613322E+10 | 7499.21 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.485911E+11 | 88413.39 | 20-SEP-05:02 | 12.00 | 10.91 | 0.544884E+10 | 7499.41 | 21-SEP-09:20 | 19.67 | 17.71 |
October | 0.531001E+11 | 95252.23 | 30-OCT-04:12 | 9.67 | 6.78 | 0.566876E+10 | 7609.64 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.519481E+11 | 94597.88 | 06-NOV-05:12 | 10.00 | 8.45 | 0.561257E+10 | 7499.70 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.517132E+11 | 97740.15 | 04-DEC-05:11 | 14.00 | 8.01 | 0.546961E+10 | 7500.10 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.596277E+12 | 0.679588E+11 | ||||||||
Minimum of Months | 0.424243E+11 | 86924.11 | 8.00 | 6.78 | 0.513732E+10 | 7499.20 | 8.00 | 6.97 | ||
Maximum of Months | 0.548318E+11 | 97779.94 | 17.00 | 14.00 | 0.613322E+10 | 7609.64 | 26.17 | 18.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410297E+11 | 84946.30 | 02-JAN-05:11 | 11.00 | 9.07 | 0.507707E+10 | 6735.04 | 10-JAN-14:09 | 16.83 | 11.85 |
February | 0.389216E+11 | 82398.56 | 21-FEB-05:12 | 8.00 | 6.97 | 0.460394E+10 | 6735.50 | 01-FEB-14:09 | 8.00 | 6.97 |
March | 0.482156E+11 | 81065.14 | 13-MAR-04:12 | 12.00 | 11.28 | 0.549928E+10 | 6735.01 | 01-MAR-14:09 | 12.00 | 11.28 |
April | 0.513105E+11 | 82136.24 | 10-APR-04:12 | 12.00 | 10.34 | 0.488113E+10 | 6735.12 | 13-APR-09:00 | 23.00 | 15.74 |
May | 0.448609E+11 | 81727.07 | 30-MAY-04:11 | 11.00 | 10.06 | 0.528451E+10 | 6735.13 | 03-MAY-13:00 | 11.00 | 10.06 |
June | 0.486795E+11 | 82147.43 | 12-JUN-04:12 | 13.07 | 11.97 | 0.527046E+10 | 6734.75 | 23-JUN-09:20 | 21.33 | 15.56 |
July | 0.554029E+11 | 81340.17 | 17-JUL-04:13 | 15.33 | 14.53 | 0.489588E+10 | 6734.78 | 11-JUL-09:20 | 15.33 | 14.53 |
August | 0.631084E+11 | 80332.14 | 29-AUG-04:13 | 15.93 | 14.70 | 0.549561E+10 | 6734.74 | 21-AUG-09:20 | 15.93 | 14.70 |
September | 0.446050E+11 | 83478.70 | 05-SEP-04:13 | 16.00 | 14.34 | 0.488141E+10 | 6734.74 | 15-SEP-09:20 | 18.33 | 14.33 |
October | 0.498708E+11 | 85169.59 | 10-OCT-04:12 | 12.67 | 12.11 | 0.507729E+10 | 6855.64 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.476106E+11 | 86057.02 | 13-NOV-05:12 | 11.00 | 10.06 | 0.502927E+10 | 6735.31 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.493277E+11 | 84695.60 | 26-DEC-05:12 | 9.00 | 1.91 | 0.490091E+10 | 6735.74 | 20-DEC-14:00 | 9.00 | 1.91 |
Annual Sum or Average | 0.582943E+12 | 0.608967E+11 | ||||||||
Minimum of Months | 0.389216E+11 | 80332.14 | 8.00 | 1.91 | 0.460394E+10 | 6734.74 | 8.00 | 1.91 | ||
Maximum of Months | 0.631084E+11 | 86057.02 | 16.00 | 14.70 | 0.549928E+10 | 6855.64 | 26.17 | 16.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301430E+11 | 70950.85 | 20-JAN-06:02 | 11.33 | 10.71 | 0.503121E+10 | 6734.99 | 10-JAN-14:09 | 11.33 | 10.71 |
February | 0.278165E+11 | 69438.72 | 02-FEB-06:02 | 12.00 | 10.34 | 0.456897E+10 | 6735.32 | 01-FEB-14:09 | 12.00 | 10.34 |
March | 0.325504E+11 | 71878.37 | 24-MAR-05:02 | 12.00 | 12.00 | 0.546397E+10 | 6734.93 | 01-MAR-14:09 | 12.00 | 12.00 |
April | 0.335583E+11 | 72077.74 | 26-APR-05:02 | 13.83 | 12.28 | 0.485810E+10 | 6735.05 | 13-APR-13:00 | 13.83 | 12.28 |
May | 0.357272E+11 | 71446.32 | 24-MAY-05:02 | 15.17 | 7.58 | 0.526912E+10 | 6735.09 | 03-MAY-13:00 | 15.17 | 7.58 |
June | 0.377817E+11 | 72394.14 | 07-JUN-05:02 | 13.17 | 12.03 | 0.526128E+10 | 6734.80 | 13-JUN-13:20 | 22.00 | 16.42 |
July | 0.390753E+11 | 71648.22 | 21-JUL-04:11 | 17.00 | 16.37 | 0.488758E+10 | 6734.79 | 03-JUL-13:20 | 17.00 | 16.37 |
August | 0.419244E+11 | 71689.13 | 01-AUG-04:12 | 17.00 | 15.07 | 0.549023E+10 | 6734.80 | 22-AUG-13:20 | 22.33 | 16.84 |
September | 0.363597E+11 | 71850.51 | 02-SEP-05:02 | 14.33 | 11.88 | 0.487179E+10 | 6734.80 | 20-SEP-13:20 | 22.00 | 16.84 |
October | 0.377621E+11 | 71770.99 | 10-OCT-05:02 | 11.83 | 11.29 | 0.506367E+10 | 6734.95 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.323076E+11 | 71162.50 | 02-NOV-05:02 | 11.67 | 10.11 | 0.500196E+10 | 6734.92 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.313312E+11 | 70065.00 | 08-DEC-06:03 | 11.95 | 11.53 | 0.486178E+10 | 6735.09 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.416337E+12 | 0.606296E+11 | ||||||||
Minimum of Months | 0.278165E+11 | 69438.72 | 11.33 | 7.58 | 0.456897E+10 | 6734.79 | 11.33 | 7.58 | ||
Maximum of Months | 0.419244E+11 | 72394.14 | 17.00 | 16.37 | 0.549023E+10 | 6735.32 | 22.33 | 16.84 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229151E+11 | 30713.39 | 19-JAN-15:00 | 20.00 | 15.12 | 0.474538E+10 | 6734.80 | 27-JAN-14:20 | 16.67 | 12.79 |
February | 0.218659E+11 | 30970.11 | 02-FEB-16:20 | 17.67 | 13.13 | 0.436671E+10 | 6735.48 | 01-FEB-14:09 | 17.67 | 13.13 |
March | 0.262794E+11 | 50667.33 | 24-MAR-05:02 | 12.00 | 12.00 | 0.525245E+10 | 6734.83 | 01-MAR-14:20 | 12.00 | 12.00 |
April | 0.306083E+11 | 65013.36 | 27-APR-05:03 | 15.00 | 14.41 | 0.479621E+10 | 6735.05 | 13-APR-13:00 | 15.00 | 14.41 |
May | 0.328138E+11 | 65959.03 | 03-MAY-05:02 | 14.17 | 14.07 | 0.521408E+10 | 6735.13 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.369396E+11 | 67659.15 | 28-JUN-05:02 | 16.17 | 15.98 | 0.523863E+10 | 6734.72 | 23-JUN-09:20 | 16.17 | 15.98 |
July | 0.396369E+11 | 67664.34 | 31-JUL-05:04 | 17.00 | 16.37 | 0.487976E+10 | 6734.76 | 11-JUL-09:20 | 17.00 | 16.37 |
August | 0.418947E+11 | 68169.03 | 21-AUG-05:02 | 16.92 | 15.63 | 0.547931E+10 | 6734.78 | 29-AUG-13:20 | 25.33 | 17.78 |
September | 0.339275E+11 | 67468.12 | 25-SEP-05:03 | 17.00 | 16.37 | 0.484244E+10 | 6734.75 | 21-SEP-09:20 | 17.00 | 16.37 |
October | 0.335442E+11 | 67670.22 | 16-OCT-04:12 | 19.67 | 9.61 | 0.501131E+10 | 6734.87 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.249015E+11 | 39313.33 | 01-NOV-05:03 | 12.83 | 9.89 | 0.485520E+10 | 6735.10 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.235760E+11 | 30492.79 | 07-DEC-15:00 | 19.00 | 15.27 | 0.463386E+10 | 6735.40 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.368903E+12 | 0.593153E+11 | ||||||||
Minimum of Months | 0.218659E+11 | 30492.79 | 12.00 | 9.61 | 0.436671E+10 | 6734.72 | 12.00 | 10.62 | ||
Maximum of Months | 0.418947E+11 | 68169.03 | 20.00 | 16.37 | 0.547931E+10 | 6735.48 | 26.17 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356903E+10 | 5526.48 | 17-JAN-13:40 | 23.33 | 17.00 | 0.620763E+09 | 845.64 | 10-JAN-14:30 | 23.33 | 17.00 |
February | 0.353858E+10 | 4725.60 | 21-FEB-13:10 | 20.67 | 13.69 | 0.568186E+09 | 845.72 | 01-FEB-14:09 | 20.67 | 13.69 |
March | 0.450631E+10 | 5614.60 | 13-MAR-13:40 | 17.67 | 13.75 | 0.680108E+09 | 845.66 | 01-MAR-14:09 | 17.67 | 13.75 |
April | 0.563830E+10 | 6781.13 | 26-APR-13:40 | 26.33 | 16.87 | 0.609537E+09 | 845.67 | 13-APR-13:00 | 26.33 | 16.87 |
May | 0.542914E+10 | 7281.10 | 03-MAY-05:02 | 14.17 | 14.07 | 0.660220E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.664997E+10 | 10292.23 | 19-JUN-05:02 | 16.17 | 14.82 | 0.660901E+09 | 845.62 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.782155E+10 | 9884.29 | 03-JUL-05:02 | 17.17 | 15.14 | 0.614686E+09 | 845.63 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.834304E+10 | 9620.56 | 21-AUG-05:02 | 16.92 | 15.63 | 0.689604E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.540244E+10 | 9332.30 | 30-SEP-05:02 | 23.80 | 13.84 | 0.610501E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.575578E+10 | 9664.53 | 04-OCT-04:12 | 20.00 | 18.03 | 0.634406E+09 | 848.72 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.434865E+10 | 5334.11 | 13-NOV-11:30 | 18.50 | 14.08 | 0.624823E+09 | 845.69 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.424787E+10 | 5755.92 | 05-DEC-14:30 | 24.50 | 12.89 | 0.606240E+09 | 845.73 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.652507E+11 | 0.757998E+10 | ||||||||
Minimum of Months | 0.353858E+10 | 4725.60 | 14.17 | 12.89 | 0.568186E+09 | 845.62 | 17.67 | 10.63 | ||
Maximum of Months | 0.834304E+10 | 10292.23 | 26.33 | 18.03 | 0.689604E+09 | 848.72 | 26.33 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331143E+10 | 6870.65 | 20-JAN-09:00 | 17.00 | 13.94 | 0.406466E+09 | 544.98 | 10-JAN-14:09 | 17.00 | 13.94 |
February | 0.307328E+10 | 10310.79 | 20-FEB-08:43 | 13.67 | 8.40 | 0.367944E+09 | 545.01 | 01-FEB-14:09 | 13.67 | 8.40 |
March | 0.394678E+10 | 11218.61 | 12-MAR-09:03 | 18.67 | 11.88 | 0.439981E+09 | 544.98 | 01-MAR-14:09 | 18.67 | 11.88 |
April | 0.531602E+10 | 17511.52 | 30-APR-07:42 | 17.67 | 13.85 | 0.393329E+09 | 545.01 | 13-APR-09:00 | 17.67 | 13.85 |
May | 0.502035E+10 | 17379.18 | 28-MAY-08:23 | 18.50 | 14.07 | 0.426615E+09 | 545.00 | 03-MAY-13:00 | 18.50 | 14.07 |
June | 0.569119E+10 | 17400.24 | 18-JUN-09:23 | 22.00 | 16.85 | 0.425944E+09 | 544.96 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.697660E+10 | 18211.18 | 23-JUL-08:12 | 23.67 | 19.22 | 0.396612E+09 | 544.96 | 07-JUL-13:09 | 23.67 | 19.22 |
August | 0.745972E+10 | 18043.23 | 06-AUG-08:32 | 23.33 | 18.92 | 0.444654E+09 | 545.48 | 14-AUG-09:09 | 25.32 | 20.33 |
September | 0.500875E+10 | 18115.89 | 10-SEP-08:32 | 21.00 | 17.14 | 0.394129E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.492376E+10 | 18413.96 | 15-OCT-08:42 | 32.33 | 15.60 | 0.409847E+09 | 547.35 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.360966E+10 | 11607.42 | 19-NOV-09:43 | 25.67 | 13.67 | 0.403831E+09 | 545.00 | 06-NOV-10:00 | 25.67 | 13.67 |
December | 0.347600E+10 | 7462.28 | 05-DEC-08:50 | 23.17 | 11.57 | 0.392441E+09 | 545.02 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.578135E+11 | 0.490179E+10 | ||||||||
Minimum of Months | 0.307328E+10 | 6870.65 | 13.67 | 8.40 | 0.367944E+09 | 544.96 | 13.67 | 8.40 | ||
Maximum of Months | 0.745972E+10 | 18413.96 | 32.33 | 19.22 | 0.444654E+09 | 547.35 | 26.17 | 20.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.983889E+10 | 21709.13 | 22-JAN-13:12 | 17.33 | 12.40 | 0.633259E+09 | 879.50 | 18-JAN-14:09 | 17.33 | 12.40 |
February | 0.741630E+10 | 20506.47 | 19-FEB-12:13 | 16.10 | 13.53 | 0.571868E+09 | 846.86 | 08-FEB-14:09 | 16.10 | 13.53 |
March | 0.754158E+10 | 20242.92 | 19-MAR-12:53 | 20.00 | 15.11 | 0.680839E+09 | 846.48 | 10-MAR-14:00 | 20.00 | 15.11 |
April | 0.794618E+10 | 18242.85 | 30-APR-13:02 | 24.00 | 16.95 | 0.609966E+09 | 846.06 | 26-APR-13:30 | 24.00 | 16.95 |
May | 0.581896E+10 | 8569.79 | 04-MAY-12:30 | 23.50 | 16.62 | 0.658059E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.644582E+10 | 7684.65 | 26-JUN-12:30 | 23.00 | 18.43 | 0.659723E+09 | 845.64 | 22-JUN-09:00 | 23.00 | 18.43 |
July | 0.809177E+10 | 10917.41 | 31-JUL-12:30 | 28.00 | 21.19 | 0.614671E+09 | 845.65 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.105517E+11 | 15035.25 | 20-AUG-13:02 | 23.83 | 18.58 | 0.690180E+09 | 846.35 | 29-AUG-13:00 | 24.00 | 17.64 |
September | 0.919844E+10 | 19769.99 | 10-SEP-13:13 | 22.33 | 18.20 | 0.612714E+09 | 884.95 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.111164E+11 | 22177.77 | 15-OCT-11:21 | 32.00 | 16.63 | 0.640969E+09 | 1035.84 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.103501E+11 | 21282.98 | 23-NOV-13:32 | 20.33 | 7.78 | 0.631467E+09 | 879.35 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.112428E+11 | 22101.00 | 25-DEC-13:11 | 22.00 | 9.35 | 0.617620E+09 | 900.35 | 19-DEC-14:09 | 22.00 | 9.35 |
Annual Sum or Average | 0.105559E+12 | 0.762133E+10 | ||||||||
Minimum of Months | 0.581896E+10 | 7684.65 | 16.10 | 7.78 | 0.571868E+09 | 845.64 | 16.10 | 9.22 | ||
Maximum of Months | 0.112428E+11 | 22177.77 | 32.00 | 21.19 | 0.690180E+09 | 1035.84 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456159E+10 | 14244.03 | 22-JAN-14:32 | 17.33 | 12.40 | 0.409048E+09 | 544.99 | 10-JAN-14:09 | 17.33 | 12.40 |
February | 0.523923E+10 | 18101.80 | 26-FEB-16:23 | 12.30 | 8.60 | 0.372718E+09 | 545.03 | 01-FEB-14:09 | 12.30 | 8.60 |
March | 0.753524E+10 | 21946.81 | 19-MAR-15:32 | 18.00 | 14.77 | 0.445481E+09 | 545.00 | 01-MAR-14:09 | 18.00 | 14.77 |
April | 0.102950E+11 | 22900.09 | 30-APR-15:42 | 22.17 | 15.97 | 0.396540E+09 | 545.01 | 13-APR-13:50 | 22.17 | 15.97 |
May | 0.724832E+10 | 19646.84 | 28-MAY-16:02 | 19.83 | 14.53 | 0.428409E+09 | 545.02 | 03-MAY-13:00 | 19.83 | 14.53 |
June | 0.939518E+10 | 22040.01 | 25-JUN-16:02 | 21.00 | 16.52 | 0.427588E+09 | 544.96 | 22-JUN-09:00 | 21.00 | 16.52 |
July | 0.116412E+11 | 24731.08 | 30-JUL-15:31 | 22.33 | 18.75 | 0.398217E+09 | 544.96 | 07-JUL-13:09 | 22.33 | 18.75 |
August | 0.135571E+11 | 23486.05 | 06-AUG-16:31 | 23.33 | 19.29 | 0.446429E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.751282E+10 | 23462.87 | 10-SEP-15:52 | 22.00 | 16.83 | 0.395937E+09 | 544.96 | 01-SEP-13:09 | 22.00 | 16.83 |
October | 0.794597E+10 | 23865.91 | 15-OCT-14:01 | 31.00 | 15.28 | 0.412047E+09 | 549.22 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.714286E+10 | 21851.49 | 26-NOV-14:12 | 16.00 | 11.06 | 0.407737E+09 | 545.06 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.764175E+10 | 23116.03 | 25-DEC-14:32 | 22.00 | 9.59 | 0.397513E+09 | 545.09 | 20-DEC-14:50 | 22.00 | 9.59 |
Annual Sum or Average | 0.997163E+11 | 0.493766E+10 | ||||||||
Minimum of Months | 0.456159E+10 | 14244.03 | 12.30 | 8.60 | 0.372718E+09 | 544.96 | 12.30 | 8.60 | ||
Maximum of Months | 0.135571E+11 | 24731.08 | 31.00 | 19.29 | 0.446429E+09 | 549.22 | 26.17 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253737E+10 | 3720.66 | 18-JAN-14:20 | 24.07 | 14.82 | 0.567663E+09 | 845.62 | 18-JAN-10:20 | 24.07 | 14.82 |
February | 0.235069E+10 | 3217.78 | 01-FEB-13:10 | 23.17 | 14.41 | 0.529043E+09 | 845.69 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.279812E+10 | 3765.45 | 23-MAR-14:40 | 22.33 | 17.37 | 0.633842E+09 | 845.63 | 15-MAR-13:20 | 22.33 | 17.37 |
April | 0.343763E+10 | 5282.83 | 26-APR-14:00 | 26.00 | 16.74 | 0.592052E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.405732E+10 | 5801.79 | 04-MAY-13:50 | 23.00 | 16.67 | 0.650471E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.503770E+10 | 5591.48 | 29-JUN-16:00 | 23.00 | 18.43 | 0.656667E+09 | 845.63 | 20-JUN-13:20 | 23.00 | 18.43 |
July | 0.555398E+10 | 6245.27 | 19-JUL-14:40 | 27.00 | 20.40 | 0.611957E+09 | 845.63 | 03-JUL-13:20 | 27.00 | 20.40 |
August | 0.547495E+10 | 6169.51 | 17-AUG-14:00 | 28.00 | 21.19 | 0.685429E+09 | 845.63 | 01-AUG-13:20 | 28.00 | 21.19 |
September | 0.423050E+10 | 8892.12 | 30-SEP-05:02 | 23.80 | 13.84 | 0.603620E+09 | 845.63 | 01-SEP-13:20 | 23.80 | 13.84 |
October | 0.418842E+10 | 7310.51 | 05-OCT-05:02 | 20.00 | 18.62 | 0.622443E+09 | 845.64 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.274462E+10 | 3289.33 | 01-NOV-13:50 | 17.17 | 13.44 | 0.589677E+09 | 845.63 | 09-NOV-14:00 | 19.00 | 15.89 |
December | 0.260757E+10 | 3663.35 | 05-DEC-15:00 | 25.00 | 13.22 | 0.553477E+09 | 845.64 | 04-DEC-14:09 | 25.00 | 13.22 |
Annual Sum or Average | 0.450189E+11 | 0.729634E+10 | ||||||||
Minimum of Months | 0.235069E+10 | 3217.78 | 17.17 | 13.22 | 0.529043E+09 | 845.62 | 19.00 | 13.22 | ||
Maximum of Months | 0.555398E+10 | 8892.12 | 28.00 | 21.19 | 0.685429E+09 | 845.69 | 28.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222732E+10 | 6343.82 | 20-JAN-11:05 | 21.17 | 15.50 | 0.292490E+09 | 548.50 | 05-JAN-11:09 | 21.17 | 15.50 |
February | 0.215452E+10 | 6262.69 | 01-FEB-11:05 | 23.50 | 13.66 | 0.263916E+09 | 548.52 | 02-FEB-13:09 | 18.83 | 13.32 |
March | 0.282231E+10 | 9651.32 | 23-MAR-10:05 | 22.00 | 16.49 | 0.315143E+09 | 548.51 | 23-MAR-10:09 | 22.00 | 16.49 |
April | 0.428967E+10 | 16717.47 | 30-APR-07:42 | 17.67 | 13.85 | 0.287906E+09 | 548.55 | 13-APR-10:09 | 17.67 | 13.85 |
May | 0.422728E+10 | 17910.30 | 28-MAY-08:43 | 18.83 | 14.19 | 0.312452E+09 | 548.53 | 03-MAY-14:09 | 18.83 | 14.19 |
June | 0.506030E+10 | 18594.15 | 25-JUN-09:12 | 22.33 | 16.69 | 0.312688E+09 | 548.51 | 22-JUN-10:09 | 22.33 | 16.69 |
July | 0.622676E+10 | 19019.03 | 23-JUL-08:62 | 23.33 | 19.11 | 0.293056E+09 | 548.49 | 12-JUL-10:09 | 23.33 | 19.11 |
August | 0.650672E+10 | 18863.50 | 06-AUG-09:02 | 23.83 | 19.36 | 0.327429E+09 | 548.49 | 29-AUG-14:09 | 23.83 | 17.58 |
September | 0.440679E+10 | 17624.38 | 03-SEP-08:32 | 19.33 | 14.88 | 0.289147E+09 | 548.51 | 12-SEP-10:09 | 22.83 | 17.20 |
October | 0.407422E+10 | 15793.56 | 15-OCT-08:53 | 33.00 | 15.89 | 0.300859E+09 | 548.55 | 30-OCT-12:09 | 24.33 | 16.19 |
November | 0.248983E+10 | 9800.12 | 19-NOV-09:43 | 25.67 | 13.67 | 0.293549E+09 | 548.51 | 10-NOV-11:09 | 25.67 | 13.67 |
December | 0.225943E+10 | 6208.66 | 05-DEC-09:20 | 24.67 | 12.23 | 0.283361E+09 | 548.51 | 20-DEC-15:09 | 18.67 | 12.31 |
Annual Sum or Average | 0.467452E+11 | 0.357200E+10 | ||||||||
Minimum of Months | 0.215452E+10 | 6208.66 | 17.67 | 12.23 | 0.263916E+09 | 548.49 | 17.67 | 12.31 | ||
Maximum of Months | 0.650672E+10 | 19019.03 | 33.00 | 19.36 | 0.327429E+09 | 548.55 | 25.67 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.959647E+10 | 20084.52 | 22-JAN-13:22 | 17.50 | 12.39 | 0.630827E+09 | 908.85 | 18-JAN-14:09 | 17.50 | 12.39 |
February | 0.680829E+10 | 20667.98 | 20-FEB-13:12 | 17.00 | 10.50 | 0.563721E+09 | 867.44 | 22-FEB-14:09 | 18.80 | 12.73 |
March | 0.631059E+10 | 19587.72 | 19-MAR-12:53 | 20.00 | 15.11 | 0.665647E+09 | 846.34 | 10-MAR-14:20 | 20.00 | 15.11 |
April | 0.618747E+10 | 14783.64 | 30-APR-13:02 | 24.00 | 16.95 | 0.601640E+09 | 845.71 | 13-APR-13:50 | 24.00 | 16.95 |
May | 0.482704E+10 | 8031.56 | 04-MAY-12:30 | 23.50 | 16.62 | 0.650582E+09 | 845.71 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.520444E+10 | 6909.36 | 30-JUN-12:30 | 23.50 | 17.99 | 0.655197E+09 | 845.65 | 20-JUN-13:20 | 23.50 | 17.99 |
July | 0.616290E+10 | 10047.81 | 31-JUL-12:40 | 28.00 | 21.19 | 0.611807E+09 | 845.65 | 03-JUL-13:20 | 28.00 | 21.19 |
August | 0.806588E+10 | 12466.17 | 30-AUG-13:00 | 24.00 | 18.12 | 0.687747E+09 | 846.68 | 29-AUG-13:20 | 24.00 | 18.12 |
September | 0.864672E+10 | 18153.73 | 10-SEP-14:43 | 22.17 | 17.57 | 0.611058E+09 | 921.68 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.103905E+11 | 21655.24 | 29-OCT-13:32 | 22.00 | 15.54 | 0.640738E+09 | 971.69 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.944664E+10 | 20379.73 | 19-NOV-13:02 | 26.67 | 15.00 | 0.628721E+09 | 903.64 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.101464E+11 | 20811.84 | 24-DEC-13:52 | 17.00 | 11.90 | 0.614717E+09 | 924.69 | 19-DEC-14:09 | 17.00 | 11.90 |
Annual Sum or Average | 0.917933E+11 | 0.756240E+10 | ||||||||
Minimum of Months | 0.482704E+10 | 6909.36 | 17.00 | 10.50 | 0.563721E+09 | 845.65 | 17.00 | 9.22 | ||
Maximum of Months | 0.103905E+11 | 21655.24 | 28.00 | 21.19 | 0.687747E+09 | 971.69 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278171E+10 | 7827.19 | 26-JAN-15:30 | 16.00 | 12.30 | 0.386952E+09 | 544.99 | 10-JAN-14:09 | 16.00 | 12.30 |
February | 0.276456E+10 | 10416.66 | 20-FEB-15:52 | 17.00 | 10.63 | 0.356312E+09 | 545.01 | 01-FEB-14:09 | 17.00 | 10.63 |
March | 0.351370E+10 | 14473.99 | 19-MAR-16:12 | 17.67 | 14.82 | 0.425614E+09 | 544.98 | 01-MAR-14:09 | 17.67 | 14.82 |
April | 0.511979E+10 | 19940.18 | 09-APR-15:52 | 18.00 | 13.88 | 0.390646E+09 | 545.00 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.514586E+10 | 17674.36 | 14-MAY-15:23 | 17.50 | 12.65 | 0.424210E+09 | 545.01 | 03-MAY-13:00 | 17.50 | 12.65 |
June | 0.633095E+10 | 20488.78 | 18-JUN-16:42 | 21.17 | 17.23 | 0.425570E+09 | 544.96 | 20-JUN-13:20 | 21.33 | 15.56 |
July | 0.723615E+10 | 20915.09 | 30-JUL-15:31 | 22.33 | 18.75 | 0.396810E+09 | 544.96 | 03-JUL-13:20 | 22.33 | 18.75 |
August | 0.747587E+10 | 21274.23 | 20-AUG-16:01 | 21.80 | 17.34 | 0.444903E+09 | 544.96 | 21-AUG-13:20 | 22.00 | 16.84 |
September | 0.552410E+10 | 19730.43 | 03-SEP-16:32 | 19.00 | 15.88 | 0.393923E+09 | 544.96 | 01-SEP-13:09 | 19.00 | 15.88 |
October | 0.481743E+10 | 20401.97 | 01-OCT-15:12 | 22.67 | 19.46 | 0.407347E+09 | 544.98 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.332895E+10 | 8372.69 | 07-NOV-15:30 | 19.00 | 14.51 | 0.395851E+09 | 544.99 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.296077E+10 | 8295.99 | 18-DEC-15:30 | 22.00 | 8.99 | 0.378593E+09 | 545.01 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.569999E+11 | 0.482673E+10 | ||||||||
Minimum of Months | 0.276456E+10 | 7827.19 | 16.00 | 8.99 | 0.356312E+09 | 544.96 | 16.00 | 10.63 | ||
Maximum of Months | 0.747587E+10 | 21274.23 | 22.67 | 19.46 | 0.444903E+09 | 545.01 | 26.83 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188932E+10 | 3305.36 | 18-JAN-15:00 | 23.00 | 14.79 | 0.534468E+09 | 845.62 | 19-JAN-14:20 | 20.67 | 15.33 |
February | 0.181802E+10 | 2710.86 | 16-FEB-14:50 | 17.08 | 13.83 | 0.497028E+09 | 845.70 | 01-FEB-14:09 | 17.08 | 13.83 |
March | 0.229267E+10 | 3846.81 | 23-MAR-15:10 | 21.83 | 17.37 | 0.598170E+09 | 845.62 | 21-MAR-13:20 | 21.83 | 17.37 |
April | 0.316525E+10 | 5749.58 | 26-APR-14:00 | 26.00 | 16.74 | 0.576038E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.377941E+10 | 6338.14 | 04-MAY-13:50 | 23.00 | 16.67 | 0.635743E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.494589E+10 | 6200.38 | 30-JUN-14:00 | 23.00 | 17.85 | 0.650991E+09 | 845.62 | 26-JUN-09:00 | 23.00 | 17.85 |
July | 0.564187E+10 | 7026.55 | 19-JUL-14:50 | 27.00 | 20.29 | 0.609894E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.29 |
August | 0.549821E+10 | 6789.57 | 17-AUG-14:00 | 28.00 | 21.19 | 0.681875E+09 | 845.63 | 29-AUG-13:20 | 25.33 | 17.78 |
September | 0.401198E+10 | 10382.81 | 30-SEP-05:02 | 23.80 | 13.84 | 0.594369E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.381218E+10 | 8457.30 | 05-OCT-05:02 | 20.00 | 18.62 | 0.608345E+09 | 845.65 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.217543E+10 | 3037.27 | 10-NOV-14:30 | 19.50 | 15.78 | 0.556454E+09 | 845.62 | 28-NOV-14:00 | 23.00 | 10.79 |
December | 0.197086E+10 | 3265.83 | 05-DEC-15:00 | 25.00 | 13.22 | 0.517500E+09 | 845.60 | 05-DEC-14:20 | 25.00 | 13.22 |
Annual Sum or Average | 0.410011E+11 | 0.706087E+10 | ||||||||
Minimum of Months | 0.181802E+10 | 2710.86 | 17.08 | 13.22 | 0.497028E+09 | 845.60 | 17.08 | 10.79 | ||
Maximum of Months | 0.564187E+10 | 10382.81 | 28.00 | 21.19 | 0.681875E+09 | 845.70 | 27.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183864E+10 | 4811.06 | 20-JAN-09:40 | 18.33 | 14.51 | 0.385091E+09 | 544.96 | 24-JAN-14:00 | 25.00 | 15.45 |
February | 0.183231E+10 | 4686.90 | 02-FEB-10:10 | 17.17 | 12.19 | 0.347802E+09 | 545.02 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.249244E+10 | 7800.96 | 23-MAR-09:30 | 20.50 | 15.62 | 0.417234E+09 | 544.97 | 01-MAR-14:09 | 20.50 | 15.62 |
April | 0.420402E+10 | 15142.61 | 30-APR-10:13 | 25.33 | 16.65 | 0.387710E+09 | 545.01 | 13-APR-09:00 | 25.33 | 16.65 |
May | 0.416326E+10 | 14162.35 | 28-MAY-08:43 | 18.83 | 14.19 | 0.420250E+09 | 545.00 | 03-MAY-13:00 | 18.83 | 14.19 |
June | 0.521890E+10 | 14451.07 | 18-JUN-10:13 | 22.33 | 16.99 | 0.422769E+09 | 544.97 | 26-JUN-09:00 | 24.00 | 18.12 |
July | 0.652708E+10 | 18008.50 | 04-JUL-08:62 | 19.50 | 14.97 | 0.395769E+09 | 544.97 | 17-JUL-09:00 | 23.00 | 17.86 |
August | 0.679408E+10 | 18523.58 | 13-AUG-09:02 | 24.00 | 19.42 | 0.443693E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.445577E+10 | 18299.08 | 10-SEP-08:32 | 21.00 | 17.14 | 0.389459E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.394248E+10 | 18425.54 | 15-OCT-09:52 | 31.00 | 16.50 | 0.404656E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.207033E+10 | 4258.34 | 01-NOV-09:30 | 15.00 | 12.66 | 0.391383E+09 | 544.99 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.184925E+10 | 4859.50 | 05-DEC-09:50 | 25.67 | 12.88 | 0.373396E+09 | 545.01 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.453886E+11 | 0.477921E+10 | ||||||||
Minimum of Months | 0.183231E+10 | 4258.34 | 15.00 | 12.19 | 0.347802E+09 | 544.96 | 17.17 | 10.63 | ||
Maximum of Months | 0.679408E+10 | 18523.58 | 31.00 | 19.42 | 0.443693E+09 | 545.02 | 25.67 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.809958E+10 | 22763.95 | 22-JAN-13:42 | 17.83 | 12.38 | 0.616345E+09 | 873.19 | 18-JAN-14:09 | 17.83 | 12.38 |
February | 0.570628E+10 | 21320.94 | 20-FEB-13:32 | 17.00 | 10.76 | 0.547552E+09 | 846.18 | 16-FEB-14:00 | 17.00 | 10.76 |
March | 0.541288E+10 | 16959.37 | 19-MAR-12:23 | 20.50 | 15.55 | 0.642589E+09 | 846.09 | 10-MAR-14:39 | 20.50 | 15.55 |
April | 0.581130E+10 | 11786.57 | 26-APR-13:10 | 26.83 | 17.07 | 0.590698E+09 | 845.71 | 13-APR-13:50 | 26.83 | 17.07 |
May | 0.450033E+10 | 8520.25 | 04-MAY-12:30 | 23.50 | 16.62 | 0.637149E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.513268E+10 | 7516.26 | 30-JUN-13:10 | 23.00 | 17.85 | 0.648749E+09 | 845.64 | 26-JUN-09:00 | 23.00 | 17.85 |
July | 0.628099E+10 | 10736.93 | 31-JUL-12:40 | 28.00 | 21.19 | 0.609477E+09 | 845.65 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.812358E+10 | 12986.14 | 30-AUG-13:05 | 23.83 | 18.18 | 0.685081E+09 | 846.27 | 30-AUG-13:00 | 23.00 | 18.43 |
September | 0.836911E+10 | 20864.24 | 10-SEP-13:13 | 22.33 | 18.20 | 0.605706E+09 | 907.15 | 29-SEP-13:39 | 34.67 | 17.98 |
October | 0.980383E+10 | 23861.00 | 15-OCT-11:11 | 32.00 | 16.55 | 0.632225E+09 | 941.59 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.814798E+10 | 21798.41 | 19-NOV-12:42 | 26.83 | 15.05 | 0.616837E+09 | 853.81 | 30-NOV-14:09 | 22.67 | 10.93 |
December | 0.858127E+10 | 22586.95 | 25-DEC-13:11 | 22.00 | 9.35 | 0.598786E+09 | 887.07 | 19-DEC-14:09 | 22.00 | 9.35 |
Annual Sum or Average | 0.839698E+11 | 0.743119E+10 | ||||||||
Minimum of Months | 0.450033E+10 | 7516.26 | 17.00 | 9.35 | 0.547552E+09 | 845.64 | 17.00 | 9.35 | ||
Maximum of Months | 0.980383E+10 | 23861.00 | 32.00 | 21.19 | 0.685081E+09 | 941.59 | 34.67 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229382E+10 | 7637.96 | 18-JAN-15:00 | 23.00 | 14.79 | 0.371443E+09 | 544.98 | 10-JAN-14:09 | 23.00 | 14.79 |
February | 0.234762E+10 | 8449.53 | 22-FEB-15:50 | 16.30 | 12.09 | 0.341412E+09 | 545.04 | 01-FEB-14:09 | 16.30 | 12.09 |
March | 0.310449E+10 | 11523.00 | 19-MAR-16:23 | 17.50 | 14.74 | 0.408530E+09 | 544.98 | 01-MAR-14:09 | 17.50 | 14.74 |
April | 0.490404E+10 | 20920.25 | 02-APR-16:02 | 18.83 | 14.19 | 0.384463E+09 | 545.00 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.492369E+10 | 16531.11 | 29-MAY-15:32 | 18.33 | 14.18 | 0.418359E+09 | 545.01 | 03-MAY-13:00 | 18.33 | 14.18 |
June | 0.627515E+10 | 19813.40 | 25-JUN-16:42 | 21.00 | 16.52 | 0.423375E+09 | 544.95 | 26-JUN-09:00 | 24.00 | 18.12 |
July | 0.731255E+10 | 22020.86 | 16-JUL-15:52 | 21.00 | 16.52 | 0.396221E+09 | 544.96 | 07-JUL-13:09 | 21.00 | 16.52 |
August | 0.749797E+10 | 21581.72 | 20-AUG-16:11 | 21.60 | 17.28 | 0.444057E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.535214E+10 | 21587.84 | 10-SEP-15:52 | 22.00 | 16.83 | 0.391295E+09 | 544.96 | 01-SEP-13:09 | 22.00 | 16.83 |
October | 0.453049E+10 | 23094.58 | 15-OCT-15:11 | 30.67 | 15.29 | 0.401425E+09 | 544.98 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.283880E+10 | 8117.68 | 10-NOV-14:50 | 19.17 | 15.85 | 0.381831E+09 | 545.03 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.242301E+10 | 7987.82 | 19-DEC-15:30 | 21.50 | 8.94 | 0.362733E+09 | 545.05 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.538038E+11 | 0.472514E+10 | ||||||||
Minimum of Months | 0.229382E+10 | 7637.96 | 16.30 | 8.94 | 0.341412E+09 | 544.95 | 16.30 | 12.09 | ||
Maximum of Months | 0.749797E+10 | 23094.58 | 30.67 | 17.28 | 0.444057E+09 | 545.05 | 26.83 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326375E+10 | 6560.77 | 17-JAN-06:15 | 15.67 | 13.46 | 0.00 | 0.00 | 01-JAN-00:10 | 15.67 | 13.46 |
February | 0.304279E+10 | 5972.17 | 21-FEB-06:15 | 8.00 | 6.97 | 0.00 | 0.00 | 01-FEB-00:10 | 8.00 | 6.97 |
March | 0.379786E+10 | 6017.33 | 20-MAR-05:15 | 10.67 | 10.47 | 0.00 | 0.00 | 01-MAR-00:10 | 10.67 | 10.47 |
April | 0.518442E+10 | 6606.10 | 10-APR-05:15 | 12.00 | 10.34 | 0.00 | 0.00 | 01-APR-00:10 | 12.00 | 10.34 |
May | 0.425849E+10 | 7088.33 | 01-MAY-05:15 | 13.33 | 12.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13.33 | 12.00 |
June | 0.552577E+10 | 6596.67 | 26-JUN-05:15 | 17.33 | 15.20 | 0.00 | 0.00 | 01-JUN-00:10 | 17.33 | 15.20 |
July | 0.667509E+10 | 9147.37 | 24-JUL-05:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-JUL-00:10 | 16.67 | 16.67 |
August | 0.740654E+10 | 7948.94 | 07-AUG-05:15 | 18.00 | 17.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.00 | 17.96 |
September | 0.524250E+10 | 8965.22 | 05-SEP-05:15 | 16.00 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 16.00 | 14.76 |
October | 0.579069E+10 | 9970.98 | 16-OCT-05:15 | 18.33 | 9.34 | 0.00 | 0.00 | 01-OCT-00:10 | 18.33 | 9.34 |
November | 0.457933E+10 | 8413.11 | 13-NOV-06:10 | 11.17 | 10.55 | 0.00 | 0.00 | 01-NOV-00:10 | 11.17 | 10.55 |
December | 0.451175E+10 | 8531.78 | 26-DEC-06:10 | 7.00 | 1.09 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 1.09 |
Annual Sum or Average | 0.592790E+11 | 0.00 | ||||||||
Minimum of Months | 0.304279E+10 | 5972.17 | 7.00 | 1.09 | 0.00 | 0.00 | 7.00 | 1.09 | ||
Maximum of Months | 0.740654E+10 | 9970.98 | 18.33 | 17.96 | 0.00 | 0.00 | 18.33 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134400E+10 | 4704.32 | 09-JAN-06:02 | 2.17 | -0.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.17 | -0.2 |
February | 0.128167E+10 | 2864.27 | 04-FEB-06:08 | 5.67 | 0.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.67 | 0.59 |
March | 0.135092E+10 | 3868.65 | 30-MAR-05:03 | 4.97 | 3.93 | 0.00 | 0.00 | 01-MAR-00:10 | 4.97 | 3.93 |
April | 0.234681E+10 | 3662.65 | 27-APR-14:20 | 19.87 | 15.39 | 0.00 | 0.00 | 01-APR-00:10 | 19.87 | 15.39 |
May | 0.251196E+10 | 3474.12 | 04-MAY-14:20 | 22.67 | 16.59 | 0.00 | 0.00 | 01-MAY-00:10 | 22.67 | 16.59 |
June | 0.339624E+10 | 4035.45 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.423024E+10 | 4680.61 | 31-JUL-14:20 | 26.67 | 20.72 | 0.00 | 0.00 | 01-JUL-00:10 | 26.67 | 20.72 |
August | 0.462674E+10 | 4606.53 | 18-AUG-15:20 | 26.00 | 20.57 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 20.57 |
September | 0.354172E+10 | 5686.78 | 30-SEP-05:15 | 23.80 | 13.84 | 0.00 | 0.00 | 01-SEP-00:10 | 23.80 | 13.84 |
October | 0.355255E+10 | 7623.01 | 02-OCT-05:15 | 19.07 | 17.72 | 0.00 | 0.00 | 01-OCT-00:10 | 19.07 | 17.72 |
November | 0.187953E+10 | 3165.81 | 02-NOV-05:15 | 11.33 | 9.87 | 0.00 | 0.00 | 01-NOV-00:10 | 11.33 | 9.87 |
December | 0.156505E+10 | 2905.07 | 20-DEC-06:10 | 8.67 | 1.20 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 1.20 |
Annual Sum or Average | 0.316274E+11 | 0.00 | ||||||||
Minimum of Months | 0.128167E+10 | 2864.27 | 2.17 | -0.2 | 0.00 | 0.00 | 2.17 | -0.2 | ||
Maximum of Months | 0.462674E+10 | 7623.01 | 26.67 | 20.72 | 0.00 | 0.00 | 26.67 | 20.72 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125718E+10 | 6677.82 | 18-JAN-15:05 | 22.83 | 14.90 | 0.00 | 0.00 | 01-JAN-00:10 | 22.83 | 14.90 |
February | 0.135085E+10 | 6481.17 | 01-FEB-14:05 | 19.00 | 15.70 | 0.00 | 0.00 | 01-FEB-00:10 | 19.00 | 15.70 |
March | 0.215202E+10 | 9999.66 | 23-MAR-15:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-MAR-00:10 | 22.00 | 17.40 |
April | 0.485583E+10 | 13488.72 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.482513E+10 | 12512.29 | 03-MAY-13:05 | 23.83 | 15.35 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 15.35 |
June | 0.676015E+10 | 12642.30 | 30-JUN-13:30 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.860337E+10 | 14320.54 | 19-JUL-13:40 | 27.00 | 20.62 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 20.62 |
August | 0.882801E+10 | 13915.32 | 14-AUG-13:05 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.576232E+10 | 13869.77 | 29-SEP-14:05 | 33.83 | 17.79 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 17.79 |
October | 0.465642E+10 | 15632.75 | 16-OCT-14:20 | 31.33 | 15.95 | 0.00 | 0.00 | 01-OCT-00:10 | 31.33 | 15.95 |
November | 0.169729E+10 | 6412.00 | 10-NOV-14:05 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.125929E+10 | 6029.18 | 05-DEC-15:05 | 24.67 | 13.10 | 0.00 | 0.00 | 01-DEC-00:10 | 24.67 | 13.10 |
Annual Sum or Average | 0.520079E+11 | 0.00 | ||||||||
Minimum of Months | 0.125718E+10 | 6029.18 | 19.00 | 13.10 | 0.00 | 0.00 | 19.00 | 13.10 | ||
Maximum of Months | 0.882801E+10 | 15632.75 | 33.83 | 20.62 | 0.00 | 0.00 | 33.83 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389736E+10 | 1985.98 | 30-JAN-16:50 | 14.00 | 11.30 | 95232915.72 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.820752E+10 | 4114.68 | 20-FEB-16:55 | 17.00 | 11.53 | 86400208.04 | 126.84 | 13-FEB-14:00 | 17.00 | 11.53 |
March | 0.142513E+11 | 6975.73 | 31-MAR-24:00 | 9.70 | 9.11 | 0.103240E+09 | 126.83 | 22-MAR-13:00 | 9.70 | 9.11 |
April | 0.188579E+11 | 7919.93 | 30-APR-17:27 | 21.00 | 15.77 | 91606559.78 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.418902E+10 | 3259.00 | 31-MAY-24:00 | 13.10 | 11.97 | 99240161.28 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.914475E+10 | 5308.05 | 30-JUN-24:00 | 16.40 | 15.78 | 98966730.00 | 126.85 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.146079E+11 | 7220.88 | 31-JUL-24:00 | 18.10 | 17.45 | 91888165.11 | 126.84 | 20-JUL-09:09 | 18.10 | 17.45 |
August | 0.196137E+11 | 8061.09 | 06-AUG-17:41 | 21.33 | 19.00 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.420804E+10 | 3474.15 | 30-SEP-24:00 | 18.40 | 17.30 | 91614381.87 | 126.85 | 08-SEP-13:00 | 18.40 | 17.30 |
October | 0.943794E+10 | 5282.54 | 31-OCT-24:00 | 14.90 | 11.04 | 95235925.15 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.139137E+11 | 5968.15 | 12-NOV-16:20 | 16.33 | 13.71 | 94302810.45 | 126.83 | 20-NOV-14:09 | 18.00 | 14.97 |
December | 0.193827E+11 | 7979.72 | 25-DEC-16:20 | 19.33 | 9.96 | 92010403.51 | 133.67 | 19-DEC-10:00 | 19.33 | 9.96 |
Annual Sum or Average | 0.139712E+12 | 0.114298E+10 | ||||||||
Minimum of Months | 0.389736E+10 | 1985.98 | 9.70 | 9.11 | 86400208.04 | 126.83 | 9.70 | 9.11 | ||
Maximum of Months | 0.196137E+11 | 8061.09 | 21.33 | 19.00 | 0.103240E+09 | 133.67 | 21.00 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269352E+10 | 1799.76 | 30-JAN-16:50 | 14.00 | 11.30 | 95232733.05 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.698989E+10 | 3724.25 | 22-FEB-17:00 | 14.00 | 12.23 | 86400057.47 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.127581E+11 | 6263.94 | 31-MAR-23:30 | 9.90 | 9.31 | 0.103240E+09 | 126.83 | 22-MAR-13:00 | 9.90 | 9.31 |
April | 0.175180E+11 | 7360.19 | 30-APR-17:27 | 21.00 | 15.77 | 91606588.89 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.351342E+10 | 2930.65 | 31-MAY-24:00 | 13.10 | 11.97 | 99239671.13 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.837509E+10 | 5009.59 | 30-JUN-24:00 | 16.40 | 15.78 | 98966464.05 | 126.84 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.137219E+11 | 6865.87 | 31-JUL-24:00 | 18.10 | 17.45 | 91887829.12 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.185249E+11 | 7471.18 | 06-AUG-18:00 | 21.00 | 18.98 | 0.103238E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.362156E+10 | 3285.19 | 30-SEP-24:00 | 18.40 | 17.30 | 91611588.67 | 126.84 | 26-SEP-13:00 | 18.40 | 17.30 |
October | 0.852765E+10 | 4887.26 | 31-OCT-24:00 | 14.90 | 11.04 | 95235676.87 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.125016E+11 | 5480.24 | 07-NOV-16:30 | 18.00 | 14.13 | 94302749.55 | 126.83 | 10-NOV-14:39 | 19.33 | 15.82 |
December | 0.175777E+11 | 7280.69 | 18-DEC-16:20 | 20.33 | 7.98 | 91928466.21 | 129.55 | 19-DEC-14:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.126323E+12 | 0.114289E+10 | ||||||||
Minimum of Months | 0.269352E+10 | 1799.76 | 9.90 | 7.98 | 86400057.47 | 126.83 | 9.90 | 9.31 | ||
Maximum of Months | 0.185249E+11 | 7471.18 | 21.00 | 18.98 | 0.103240E+09 | 129.55 | 22.83 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157628E+10 | 1733.59 | 26-JAN-16:10 | 15.67 | 12.54 | 95099556.77 | 127.46 | 03-JAN-10:09 | 15.67 | 12.54 |
February | 0.596335E+10 | 3709.92 | 22-FEB-17:00 | 14.00 | 12.23 | 86400035.86 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.118284E+11 | 5883.37 | 31-MAR-23:20 | 9.97 | 9.37 | 0.103240E+09 | 126.83 | 22-MAR-13:00 | 9.97 | 9.37 |
April | 0.170449E+11 | 7404.41 | 30-APR-17:30 | 21.00 | 15.77 | 91606791.28 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.303985E+10 | 2675.75 | 31-MAY-23:40 | 13.20 | 12.26 | 99239686.84 | 126.84 | 05-MAY-13:00 | 13.20 | 12.26 |
June | 0.816221E+10 | 4890.71 | 30-JUN-24:00 | 16.40 | 15.78 | 98966745.84 | 126.85 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.136331E+11 | 6765.90 | 31-JUL-24:00 | 18.10 | 17.45 | 91888176.16 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.184030E+11 | 7610.17 | 06-AUG-17:41 | 21.33 | 19.00 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.331839E+10 | 3252.79 | 30-SEP-23:50 | 18.37 | 17.42 | 91611952.57 | 126.85 | 06-SEP-13:00 | 18.37 | 17.42 |
October | 0.805751E+10 | 4669.71 | 31-OCT-23:30 | 15.25 | 11.85 | 95235740.98 | 126.85 | 02-OCT-13:00 | 15.25 | 11.85 |
November | 0.115686E+11 | 5459.27 | 07-NOV-16:30 | 18.00 | 14.13 | 94302820.70 | 126.83 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.163662E+11 | 7277.72 | 19-DEC-16:20 | 20.33 | 7.94 | 91887251.17 | 127.05 | 19-DEC-14:09 | 20.33 | 7.94 |
Annual Sum or Average | 0.118962E+12 | 0.114272E+10 | ||||||||
Minimum of Months | 0.157628E+10 | 1733.59 | 9.97 | 7.94 | 86400035.86 | 126.83 | 9.97 | 7.94 | ||
Maximum of Months | 0.184030E+11 | 7610.17 | 21.33 | 19.00 | 0.103240E+09 | 127.46 | 21.00 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238235E+12 | 91301.06 | 02-JAN-17:00 | 11.00 | 7.91 | 0.206142E+10 | 2746.67 | 17-JAN-14:09 | 23.33 | 16.85 |
February | 0.434299E+12 | 182355.65 | 21-FEB-17:00 | 16.00 | 13.03 | 0.187017E+10 | 2746.64 | 01-FEB-14:09 | 16.00 | 13.03 |
March | 0.726480E+12 | 357342.15 | 31-MAR-24:00 | 9.70 | 9.11 | 0.223555E+10 | 2750.62 | 24-MAR-13:09 | 9.70 | 9.11 |
April | 0.940085E+12 | 365843.84 | 26-APR-14:05 | 25.50 | 16.68 | 0.198593E+10 | 2847.82 | 26-APR-13:09 | 25.50 | 16.68 |
May | 0.238159E+12 | 174650.47 | 31-MAY-24:00 | 13.10 | 11.97 | 0.214805E+10 | 2746.47 | 04-MAY-13:09 | 13.10 | 11.97 |
June | 0.466367E+12 | 266307.00 | 30-JUN-24:00 | 16.40 | 15.78 | 0.214274E+10 | 2748.87 | 23-JUN-13:09 | 16.40 | 15.78 |
July | 0.728136E+12 | 358644.66 | 31-JUL-24:00 | 18.10 | 17.45 | 0.199316E+10 | 2857.85 | 19-JUL-13:00 | 18.10 | 17.45 |
August | 0.970591E+12 | 369319.29 | 26-AUG-17:02 | 19.50 | 17.77 | 0.242874E+10 | 3723.63 | 17-AUG-13:00 | 19.50 | 17.77 |
September | 0.232232E+12 | 175353.07 | 30-SEP-24:00 | 18.40 | 17.30 | 0.198300E+10 | 2747.22 | 13-SEP-13:09 | 18.40 | 17.30 |
October | 0.484231E+12 | 267197.21 | 31-OCT-24:00 | 14.90 | 11.04 | 0.206175E+10 | 2748.93 | 06-OCT-13:09 | 14.90 | 11.04 |
November | 0.705458E+12 | 274888.68 | 13-NOV-17:00 | 15.00 | 13.80 | 0.204210E+10 | 2750.31 | 10-NOV-14:00 | 15.00 | 13.80 |
December | 0.973964E+12 | 367467.03 | 19-DEC-14:05 | 22.83 | 9.79 | 0.199296E+10 | 2981.53 | 05-DEC-10:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.713824E+13 | 0.249456E+11 | ||||||||
Minimum of Months | 0.232232E+12 | 91301.06 | 9.70 | 7.91 | 0.187017E+10 | 2746.47 | 9.70 | 9.11 | ||
Maximum of Months | 0.973964E+12 | 369319.29 | 25.50 | 17.77 | 0.242874E+10 | 3723.63 | 25.50 | 17.77 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404848E+09 | 9721.13 | 24-JAN-05:17 | 13.67 |
February | 0.192359E+09 | 9701.50 | 07-FEB-05:17 | 12.00 |
March | 78056938.71 | 9629.98 | 22-MAR-04:15 | 8.67 |
April | 65886931.40 | 9606.65 | 15-APR-04:15 | 12.00 |
May | 0.104372E+09 | 9722.33 | 23-MAY-04:17 | 12.67 |
June | 73442578.47 | 9590.49 | 07-JUN-04:15 | 13.00 |
July | 90066897.30 | 9352.80 | 06-JUL-04:57 | 14.00 |
August | 88363067.04 | 9332.98 | 22-AUG-04:57 | 15.00 |
September | 0.156663E+09 | 13298.45 | 30-SEP-16:02 | 28.50 |
October | 0.235018E+09 | 16958.54 | 14-OCT-16:02 | 31.17 |
November | 0.265217E+09 | 9686.26 | 18-NOV-05:17 | 8.00 |
December | 0.213536E+09 | 9677.93 | 16-DEC-05:17 | 11.33 |
Annual Sum or Average | 0.196783E+10 | |||
Minimum of Months | 65886931.40 | 9332.98 | 8.00 | |
Maximum of Months | 0.404848E+09 | 16958.54 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141965E+09 | 56065.97 | 02-JAN-05:11 | 11.00 |
February | 1760036.33 | 11733.58 | 27-FEB-06:03 | 11.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 2502499.30 | 16683.33 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 0.146227E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 0.141965E+09 | 56065.97 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57331496.57 | 9108.70 | 03-JAN-06:02 | 4.67 |
February | 1817254.79 | 4107.98 | 06-FEB-06:03 | 9.00 |
March | 23207200.55 | 8871.18 | 30-MAR-05:03 | 4.97 |
April | 1123449.58 | 4997.49 | 01-APR-05:02 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 1383767.11 | 4316.91 | 24-NOV-06:03 | 8.92 |
December | 10329380.77 | 8752.60 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 95192549.38 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 57331496.57 | 9108.70 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16970519.06 | 9628.13 | 03-JAN-06:02 | 4.67 |
February | 68865.85 | 688.66 | 28-FEB-06:02 | 10.17 |
March | 11763755.14 | 9149.03 | 30-MAR-05:03 | 4.97 |
April | 380066.97 | 2174.09 | 01-APR-05:02 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 3514904.45 | 7031.46 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 32698111.48 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 16970519.06 | 9628.13 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3791205.75 | 7326.94 | 03-JAN-06:02 | 4.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 10366971.28 | 12379.05 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1285942.86 | 5136.02 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 15444119.89 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 10366971.28 | 12379.05 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7199866.52 | 8697.97 | 09-JAN-06:02 | 2.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 2122508.04 | 6392.18 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 287857.48 | 1783.45 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 9610232.04 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 7199866.52 | 8697.97 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650819E+09 | 11941.02 | 02-JAN-05:11 | 11.00 |
February | 0.283649E+09 | 11000.15 | 06-FEB-05:12 | 8.33 |
March | 0.359001E+09 | 11428.24 | 30-MAR-04:11 | 4.57 |
April | 34388398.08 | 10271.84 | 01-APR-05:02 | 7.83 |
May | 4686439.38 | 10030.08 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 12764847.48 | 10062.15 | 30-OCT-05:03 | 10.83 |
November | 0.173667E+09 | 10947.30 | 24-NOV-05:12 | 8.33 |
December | 0.413148E+09 | 11097.06 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.193212E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.650819E+09 | 11941.02 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248632E+09 | 13264.73 | 02-JAN-05:11 | 11.00 |
February | 0.114849E+09 | 12042.92 | 06-FEB-05:12 | 8.33 |
March | 0.141971E+09 | 12910.89 | 30-MAR-04:11 | 4.57 |
April | 11973964.76 | 11319.35 | 01-APR-05:02 | 7.83 |
May | 1584008.20 | 8177.88 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 3197479.71 | 4702.24 | 30-OCT-05:03 | 10.83 |
November | 53404902.27 | 12002.43 | 24-NOV-05:12 | 8.33 |
December | 0.145432E+09 | 12421.13 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.721045E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.248632E+09 | 13264.73 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201351E+09 | 16285.04 | 02-JAN-05:11 | 11.00 |
February | 0.100267E+09 | 14360.47 | 28-FEB-06:02 | 10.17 |
March | 0.213956E+09 | 15847.55 | 30-MAR-04:11 | 4.57 |
April | 23219064.37 | 14245.09 | 01-APR-05:02 | 7.83 |
May | 8073279.86 | 14116.41 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 23144800.14 | 14053.89 | 18-NOV-06:02 | 8.17 |
December | 89147235.12 | 15251.47 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.659159E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.213956E+09 | 16285.04 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186989E+09 | 13102.36 | 02-JAN-05:11 | 11.00 |
February | 45244671.65 | 11352.15 | 28-FEB-06:02 | 10.17 |
March | 83630435.92 | 12386.98 | 30-MAR-04:11 | 4.57 |
April | 8019614.47 | 11126.25 | 01-APR-05:02 | 7.83 |
May | 670987.57 | 5572.28 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 18577762.97 | 8833.29 | 18-NOV-06:02 | 8.17 |
December | 76762787.54 | 12102.13 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.419896E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.186989E+09 | 13102.36 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73019908.74 | 7858.90 | 02-JAN-05:11 | 11.00 |
February | 76947685.37 | 7969.45 | 27-FEB-05:12 | 11.00 |
March | 83599747.66 | 8721.83 | 06-MAR-05:12 | 11.00 |
April | 0.109258E+09 | 9594.46 | 03-APR-04:12 | 11.67 |
May | 75954858.61 | 7398.72 | 01-MAY-04:12 | 13.00 |
June | 61999072.22 | 7308.51 | 19-JUN-04:12 | 16.00 |
July | 0.101021E+09 | 7910.33 | 13-JUL-04:12 | 17.00 |
August | 0.116587E+09 | 7944.65 | 29-AUG-04:11 | 15.93 |
September | 59496606.11 | 7442.31 | 01-SEP-04:12 | 15.00 |
October | 86020902.37 | 7879.99 | 23-OCT-04:12 | 16.67 |
November | 0.102294E+09 | 8368.30 | 13-NOV-05:12 | 11.00 |
December | 0.143245E+09 | 10577.58 | 18-DEC-05:12 | 17.67 |
Annual Sum or Average | 0.108944E+10 | |||
Minimum of Months | 59496606.11 | 7308.51 | 11.00 | |
Maximum of Months | 0.143245E+09 | 10577.58 | 17.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229686E+09 | 5341.59 | 17-JAN-06:03 | 15.83 |
February | 0.134737E+09 | 5806.47 | 20-FEB-15:52 | 17.00 |
March | 0.139240E+09 | 5876.20 | 19-MAR-15:32 | 18.00 |
April | 50748021.17 | 5046.39 | 02-APR-15:31 | 19.67 |
May | 46892794.75 | 4692.74 | 08-MAY-05:02 | 14.00 |
June | 31214402.34 | 4607.44 | 12-JUN-04:12 | 13.07 |
July | 46551550.03 | 3955.00 | 12-JUL-04:12 | 17.00 |
August | 36822895.78 | 3930.12 | 29-AUG-04:11 | 15.93 |
September | 43156666.15 | 5360.15 | 04-SEP-14:52 | 21.00 |
October | 62854734.85 | 6642.71 | 15-OCT-14:12 | 31.00 |
November | 58845247.56 | 5504.61 | 19-NOV-09:43 | 25.67 |
December | 79454454.50 | 5129.88 | 11-DEC-06:03 | 7.17 |
Annual Sum or Average | 0.960203E+09 | |||
Minimum of Months | 31214402.34 | 3930.12 | 7.17 | |
Maximum of Months | 0.229686E+09 | 6642.71 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170142E+10 | 10914.76 | 09-JAN-06:02 | 2.17 |
February | 0.121956E+10 | 5683.85 | 06-FEB-06:03 | 9.00 |
March | 0.141977E+10 | 10493.69 | 24-MAR-05:02 | 12.00 |
April | 0.581437E+09 | 12337.77 | 26-APR-05:02 | 13.83 |
May | 0.489470E+09 | 11218.35 | 04-MAY-05:02 | 14.33 |
June | 0.207755E+09 | 13025.98 | 05-JUN-05:02 | 12.17 |
July | 91365672.67 | 11195.78 | 06-JUL-05:03 | 14.33 |
August | 0.114869E+09 | 10887.98 | 31-AUG-05:03 | 15.17 |
September | 0.269057E+09 | 11147.89 | 12-SEP-05:03 | 15.00 |
October | 0.515232E+09 | 11417.95 | 18-OCT-05:03 | 15.00 |
November | 0.107196E+10 | 9220.40 | 01-NOV-05:03 | 12.83 |
December | 0.155947E+10 | 6418.98 | 24-DEC-11:18 | 16.00 |
Annual Sum or Average | 0.924136E+10 | |||
Minimum of Months | 91365672.67 | 5683.85 | 2.17 | |
Maximum of Months | 0.170142E+10 | 13025.98 | 16.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130000E+09 | 531.82 | 08-JAN-07:00 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.130000E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.130000E+09 | 531.82 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102471E+11 | 10780.55 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.929489E+10 | 10780.55 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.110442E+11 | 10780.55 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.986550E+10 | 10780.55 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.106457E+11 | 10780.55 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.105939E+11 | 10780.55 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.991722E+10 | 10780.55 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.110442E+11 | 10780.55 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.986550E+10 | 10780.55 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.102471E+11 | 10780.55 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.101268E+11 | 10780.55 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.991722E+10 | 10780.55 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.122809E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.929489E+10 | 10780.55 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.110442E+11 | 10780.55 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.920263E+10 | 9681.69 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.834746E+10 | 9681.69 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.991846E+10 | 9681.69 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.885991E+10 | 9681.69 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.956054E+10 | 9681.69 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.951409E+10 | 9681.69 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.890636E+10 | 9681.69 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.991846E+10 | 9681.69 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.885991E+10 | 9681.69 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.920263E+10 | 9681.69 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.909454E+10 | 9681.69 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.890636E+10 | 9681.69 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.110291E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.834746E+10 | 9681.69 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.991846E+10 | 9681.69 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.920263E+10 | 9681.69 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.834746E+10 | 9681.69 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.991846E+10 | 9681.69 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.885991E+10 | 9681.69 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.956054E+10 | 9681.69 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.951409E+10 | 9681.69 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.890636E+10 | 9681.69 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.991846E+10 | 9681.69 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.885991E+10 | 9681.69 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.920263E+10 | 9681.69 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.909454E+10 | 9681.69 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.890636E+10 | 9681.69 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.110291E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.834746E+10 | 9681.69 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.991846E+10 | 9681.69 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.920263E+10 | 9681.69 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.834746E+10 | 9681.69 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.991846E+10 | 9681.69 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.885991E+10 | 9681.69 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.956054E+10 | 9681.69 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.951409E+10 | 9681.69 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.890636E+10 | 9681.69 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.991846E+10 | 9681.69 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.885991E+10 | 9681.69 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.920263E+10 | 9681.69 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.909454E+10 | 9681.69 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.890636E+10 | 9681.69 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.110291E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.834746E+10 | 9681.69 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.991846E+10 | 9681.69 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.730609E+09 | 1215.63 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.621981E+09 | 1067.44 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.713949E+09 | 786.71 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.615670E+09 | 671.50 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.649207E+09 | 654.18 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.641066E+09 | 638.76 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.604094E+09 | 619.01 | 12-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.677962E+09 | 655.87 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.630374E+09 | 842.12 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.683637E+09 | 861.15 | 24-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.715820E+09 | 1215.63 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.717964E+09 | 1215.63 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.800233E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.604094E+09 | 619.01 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.730609E+09 | 1215.63 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.464034E+09 | 783.40 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.398715E+09 | 691.73 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.457446E+09 | 500.80 | 06-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.397017E+09 | 437.10 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.420179E+09 | 402.48 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.415664E+09 | 372.74 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.391389E+09 | 372.74 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.437843E+09 | 400.22 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.404413E+09 | 437.64 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.435666E+09 | 586.36 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.458095E+09 | 783.40 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.455221E+09 | 783.40 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.513568E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.391389E+09 | 372.74 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.464034E+09 | 783.40 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.706219E+09 | 1215.66 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.611350E+09 | 1057.90 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.708853E+09 | 676.46 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.616377E+09 | 668.69 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.652713E+09 | 657.86 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.646571E+09 | 647.52 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.608847E+09 | 630.68 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.680591E+09 | 657.75 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.628328E+09 | 823.48 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.665433E+09 | 800.87 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.695715E+09 | 1215.66 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.689765E+09 | 1215.66 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.791076E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.608847E+09 | 630.68 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.708853E+09 | 1215.66 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.460601E+09 | 783.40 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.396550E+09 | 673.47 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.457376E+09 | 546.64 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.397158E+09 | 434.90 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.419222E+09 | 431.57 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.413763E+09 | 425.48 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.389468E+09 | 419.12 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.437339E+09 | 433.57 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.405667E+09 | 572.64 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.432776E+09 | 577.93 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.450602E+09 | 783.40 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.450725E+09 | 783.40 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.511124E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.389468E+09 | 419.12 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.460601E+09 | 783.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.729060E+09 | 1215.63 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.620853E+09 | 1065.78 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.712811E+09 | 781.06 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.615243E+09 | 667.13 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.648908E+09 | 648.85 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.640733E+09 | 632.58 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.603833E+09 | 578.40 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.677497E+09 | 650.65 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.629659E+09 | 837.46 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.681406E+09 | 856.48 | 24-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.714453E+09 | 1215.63 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.715698E+09 | 1215.63 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.799015E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.603833E+09 | 578.40 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.729060E+09 | 1215.63 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463469E+09 | 783.40 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.398289E+09 | 689.34 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.457057E+09 | 494.23 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.396794E+09 | 434.61 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.419860E+09 | 398.59 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.415440E+09 | 372.74 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.391215E+09 | 372.74 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.437628E+09 | 396.42 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.404040E+09 | 435.39 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.434841E+09 | 581.07 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.457628E+09 | 783.40 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.454614E+09 | 783.40 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.513087E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.391215E+09 | 372.74 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.463469E+09 | 783.40 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.705642E+09 | 1215.66 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.611136E+09 | 1056.22 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.708326E+09 | 675.36 | 01-MAR-17:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.616031E+09 | 664.18 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.652233E+09 | 652.71 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.646082E+09 | 641.76 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.608471E+09 | 623.96 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.680155E+09 | 652.63 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.627771E+09 | 818.63 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.664716E+09 | 795.75 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.695482E+09 | 1215.66 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.689446E+09 | 1215.66 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.790549E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.608471E+09 | 623.96 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.708326E+09 | 1215.66 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.460031E+09 | 783.40 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.396199E+09 | 670.86 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.456708E+09 | 540.37 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.396825E+09 | 432.29 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.418896E+09 | 428.76 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.413383E+09 | 422.34 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.389211E+09 | 415.61 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.437092E+09 | 430.88 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.405162E+09 | 566.92 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.432000E+09 | 572.52 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.450054E+09 | 783.40 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.449970E+09 | 783.40 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.510553E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.389211E+09 | 415.61 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.460031E+09 | 783.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.729028E+09 | 1215.63 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.620830E+09 | 1065.47 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.712788E+09 | 780.23 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.615199E+09 | 666.95 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.648898E+09 | 648.64 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.640711E+09 | 632.32 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.603827E+09 | 578.40 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.677481E+09 | 650.44 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.629637E+09 | 836.70 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.681340E+09 | 855.78 | 24-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.714431E+09 | 1215.63 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.715666E+09 | 1215.63 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.798984E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.603827E+09 | 578.40 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.729028E+09 | 1215.63 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463431E+09 | 783.40 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.398265E+09 | 689.15 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.457047E+09 | 494.11 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.396704E+09 | 434.51 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.419853E+09 | 398.40 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.415435E+09 | 372.74 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.391210E+09 | 372.74 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.437613E+09 | 396.23 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.404032E+09 | 435.29 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.434820E+09 | 580.69 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.457606E+09 | 783.40 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.454587E+09 | 783.40 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.513060E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.391210E+09 | 372.74 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.463431E+09 | 783.40 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.705632E+09 | 1215.66 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.611129E+09 | 1055.90 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.708313E+09 | 675.36 | 01-MAR-17:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.615998E+09 | 664.00 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.652219E+09 | 652.50 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.646062E+09 | 641.53 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.608454E+09 | 623.69 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.680135E+09 | 652.42 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.627728E+09 | 817.84 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.664685E+09 | 794.95 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.695476E+09 | 1215.66 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.689419E+09 | 1215.66 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.790525E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.608454E+09 | 623.69 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.708313E+09 | 1215.66 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.460021E+09 | 783.40 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.396190E+09 | 670.65 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.456686E+09 | 539.89 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.396817E+09 | 432.19 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.418888E+09 | 428.66 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.413362E+09 | 422.22 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.389204E+09 | 415.48 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.437085E+09 | 430.78 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.405134E+09 | 566.51 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.431980E+09 | 572.11 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.450047E+09 | 783.40 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.449959E+09 | 783.40 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.510537E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.389204E+09 | 415.48 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.460021E+09 | 783.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148158E+09 | 155.04 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.134390E+09 | 155.04 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.159693E+09 | 155.04 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.142638E+09 | 155.04 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.153925E+09 | 155.04 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.153181E+09 | 155.04 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.143382E+09 | 155.04 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.159693E+09 | 155.04 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.142638E+09 | 155.04 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.148158E+09 | 155.04 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.146421E+09 | 155.04 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.143382E+09 | 155.04 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.177566E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.134390E+09 | 155.04 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.159693E+09 | 155.04 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148158E+09 | 155.04 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.134390E+09 | 155.04 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.159693E+09 | 155.04 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.142638E+09 | 155.04 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.153925E+09 | 155.04 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.153181E+09 | 155.04 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.143382E+09 | 155.04 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.159693E+09 | 155.04 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.142638E+09 | 155.04 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.148158E+09 | 155.04 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.146421E+09 | 155.04 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.143382E+09 | 155.04 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.177566E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.134390E+09 | 155.04 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.159693E+09 | 155.04 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148158E+09 | 155.04 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.134390E+09 | 155.04 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.159693E+09 | 155.04 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.142638E+09 | 155.04 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.153925E+09 | 155.04 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.153181E+09 | 155.04 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.143382E+09 | 155.04 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.159693E+09 | 155.04 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.142638E+09 | 155.04 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.148158E+09 | 155.04 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.146421E+09 | 155.04 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.143382E+09 | 155.04 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.177566E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.134390E+09 | 155.04 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.159693E+09 | 155.04 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.290468E+10 | 3039.65 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.263476E+10 | 3039.65 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.313083E+10 | 3039.65 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.279647E+10 | 3039.65 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.301776E+10 | 3039.65 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.300317E+10 | 3039.65 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.281106E+10 | 3039.65 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.313083E+10 | 3039.65 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.279647E+10 | 3039.65 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.290468E+10 | 3039.65 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.287064E+10 | 3039.65 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.281106E+10 | 3039.65 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.348124E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.263476E+10 | 3039.65 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.313083E+10 | 3039.65 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.102471E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.929489E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.110442E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.986550E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.106457E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.105939E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.991722E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.110442E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.986550E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.102471E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.101268E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.991722E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.122809E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.929489E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.110442E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.920263E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.991846E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.885991E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.956054E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.951409E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.890636E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.991846E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.885991E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.920263E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.909454E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.890636E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.110291E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.991846E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.920263E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.885991E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.956054E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.951409E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.890636E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.885991E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.920263E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.909454E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.890636E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.110291E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.920263E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.885991E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.956054E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.951409E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.890636E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.885991E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.920263E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.909454E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.890636E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.110291E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.834746E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.991846E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.730609E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259340.61 | 0.287368E+09 |
February | 0.136985E+10 | 0.621981E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45300.02 | 0.337820E+09 |
March | 0.163685E+10 | 0.713949E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.84 | 0.358032E+09 |
April | 0.145243E+10 | 0.615670E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 284989.79 | 0.209132E+09 |
May | 0.157338E+10 | 0.649207E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 0.245200E+09 |
June | 0.156900E+10 | 0.641066E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28183.28 | 0.131602E+09 |
July | 0.145680E+10 | 0.604094E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1899892.55 | 93240785.86 |
August | 0.163685E+10 | 0.677962E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1986377.73 | 0.113259E+09 |
September | 0.145243E+10 | 0.630374E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3201000.22 | 0.114515E+09 |
October | 0.150991E+10 | 0.683637E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11378506.40 | 0.183276E+09 |
November | 0.149516E+10 | 0.715820E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 586716.21 | 0.272957E+09 |
December | 0.145680E+10 | 0.717964E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 190300.38 | 0.299751E+09 |
Annual Sum or Average | 0.181194E+11 | 0.800233E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19860738.98 | 0.264615E+10 |
Minimum of Months | 0.136985E+10 | 0.604094E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 93240785.86 |
Maximum of Months | 0.163685E+10 | 0.730609E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11378506.40 | 0.358032E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.464034E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152437.25 | 0.194621E+09 |
February | 0.882782E+09 | 0.398715E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30198.25 | 0.225806E+09 |
March | 0.105485E+10 | 0.457446E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 | 0.238331E+09 |
April | 0.936002E+09 | 0.397017E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138902.21 | 0.140707E+09 |
May | 0.101394E+10 | 0.420179E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 | 0.167464E+09 |
June | 0.101113E+10 | 0.415664E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18780.39 | 88449693.54 |
July | 0.938820E+09 | 0.391389E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1256429.58 | 64298913.24 |
August | 0.105485E+10 | 0.437843E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1313894.13 | 76327231.81 |
September | 0.936002E+09 | 0.404413E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2132244.16 | 79231923.38 |
October | 0.973041E+09 | 0.435666E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7029991.17 | 0.123708E+09 |
November | 0.963541E+09 | 0.458095E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154218.31 | 0.181691E+09 |
December | 0.938820E+09 | 0.455221E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122410.33 | 0.197664E+09 |
Annual Sum or Average | 0.116768E+11 | 0.513568E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12349592.39 | 0.177830E+10 |
Minimum of Months | 0.882782E+09 | 0.391389E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 | 64298913.24 |
Maximum of Months | 0.105485E+10 | 0.464034E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7029991.17 | 0.238331E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.706219E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212831.60 | 0.299437E+09 |
February | 0.136988E+10 | 0.611350E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45279.58 | 0.347270E+09 |
March | 0.163688E+10 | 0.708853E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.68 | 0.360733E+09 |
April | 0.145246E+10 | 0.616377E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 208281.41 | 0.214825E+09 |
May | 0.157341E+10 | 0.652713E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 | 0.242407E+09 |
June | 0.156904E+10 | 0.646571E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28184.67 | 0.128678E+09 |
July | 0.145684E+10 | 0.608847E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1885911.97 | 93767674.64 |
August | 0.163688E+10 | 0.680591E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1970174.92 | 0.117893E+09 |
September | 0.145246E+10 | 0.628328E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3158335.95 | 0.124412E+09 |
October | 0.150994E+10 | 0.665433E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9833289.60 | 0.197099E+09 |
November | 0.149520E+10 | 0.695715E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88825.05 | 0.287709E+09 |
December | 0.145684E+10 | 0.689765E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135014.39 | 0.315234E+09 |
Annual Sum or Average | 0.181198E+11 | 0.791076E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17566267.69 | 0.272946E+10 |
Minimum of Months | 0.136988E+10 | 0.608847E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 | 93767674.64 |
Maximum of Months | 0.163688E+10 | 0.708853E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9833289.60 | 0.360733E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.460601E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152435.11 | 0.208904E+09 |
February | 0.882782E+09 | 0.396550E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30199.07 | 0.254642E+09 |
March | 0.105485E+10 | 0.457376E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.02 | 0.268839E+09 |
April | 0.936002E+09 | 0.397158E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138906.82 | 0.164867E+09 |
May | 0.101394E+10 | 0.419222E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 | 0.183498E+09 |
June | 0.101113E+10 | 0.413763E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18785.82 | 0.100394E+09 |
July | 0.938820E+09 | 0.389468E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1256339.30 | 77156265.84 |
August | 0.105485E+10 | 0.437339E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1312824.42 | 96686396.54 |
September | 0.936002E+09 | 0.405667E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2124697.83 | 90139637.46 |
October | 0.973041E+09 | 0.432776E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6831305.37 | 0.144078E+09 |
November | 0.963541E+09 | 0.450602E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63787.95 | 0.209569E+09 |
December | 0.938820E+09 | 0.450725E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122305.80 | 0.233327E+09 |
Annual Sum or Average | 0.116768E+11 | 0.511124E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12051681.88 | 0.203210E+10 |
Minimum of Months | 0.882782E+09 | 0.389468E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 | 77156265.84 |
Maximum of Months | 0.105485E+10 | 0.460601E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6831305.37 | 0.268839E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.729060E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1222431.19 | 0.576599E+09 |
February | 0.136985E+10 | 0.620853E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100133.30 | 0.677389E+09 |
March | 0.163685E+10 | 0.712811E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170705.07 | 0.736278E+09 |
April | 0.145243E+10 | 0.615243E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1651242.32 | 0.434425E+09 |
May | 0.157338E+10 | 0.648908E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533198E+09 |
June | 0.156900E+10 | 0.640733E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52727.10 | 0.289122E+09 |
July | 0.145680E+10 | 0.603833E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4520802.77 | 0.204209E+09 |
August | 0.163685E+10 | 0.677497E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4840280.15 | 0.251629E+09 |
September | 0.145243E+10 | 0.629659E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7378192.37 | 0.243332E+09 |
October | 0.150991E+10 | 0.681406E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27652375.45 | 0.378500E+09 |
November | 0.149516E+10 | 0.714453E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3146929.37 | 0.550377E+09 |
December | 0.145680E+10 | 0.715698E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1575451.94 | 0.585703E+09 |
Annual Sum or Average | 0.181194E+11 | 0.799015E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52311271.04 | 0.546076E+10 |
Minimum of Months | 0.136985E+10 | 0.603833E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204209E+09 |
Maximum of Months | 0.163685E+10 | 0.729060E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27652375.45 | 0.736278E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.463469E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 269514.85 | 0.412360E+09 |
February | 0.649041E+09 | 0.398289E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44439.43 | 0.480728E+09 |
March | 0.773965E+09 | 0.457057E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520593E+09 |
April | 0.688021E+09 | 0.396794E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265467.37 | 0.319974E+09 |
May | 0.744847E+09 | 0.419860E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382922E+09 |
June | 0.742030E+09 | 0.415440E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20999.08 | 0.206146E+09 |
July | 0.690839E+09 | 0.391215E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2499211.53 | 0.155935E+09 |
August | 0.773965E+09 | 0.437628E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2506468.69 | 0.189390E+09 |
September | 0.688021E+09 | 0.404040E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4757586.42 | 0.180511E+09 |
October | 0.715730E+09 | 0.434841E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15498445.67 | 0.275544E+09 |
November | 0.708685E+09 | 0.457628E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 383748.05 | 0.393214E+09 |
December | 0.690839E+09 | 0.454614E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 208942.81 | 0.420575E+09 |
Annual Sum or Average | 0.858171E+10 | 0.513087E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26454823.90 | 0.393789E+10 |
Minimum of Months | 0.649041E+09 | 0.391215E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155935E+09 |
Maximum of Months | 0.773965E+09 | 0.463469E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15498445.67 | 0.520593E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.705642E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374863.89 | 0.675715E+09 |
February | 0.136988E+10 | 0.611136E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95492.43 | 0.770726E+09 |
March | 0.163688E+10 | 0.708326E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797198E+09 |
April | 0.145246E+10 | 0.616031E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 461321.33 | 0.478777E+09 |
May | 0.157341E+10 | 0.652233E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545001E+09 |
June | 0.156904E+10 | 0.646082E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52728.81 | 0.287248E+09 |
July | 0.145684E+10 | 0.608471E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4397725.12 | 0.210205E+09 |
August | 0.163688E+10 | 0.680155E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4319729.90 | 0.274680E+09 |
September | 0.145246E+10 | 0.627771E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7119815.53 | 0.287302E+09 |
October | 0.150994E+10 | 0.664716E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22052821.44 | 0.449018E+09 |
November | 0.149520E+10 | 0.695482E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175066.09 | 0.646084E+09 |
December | 0.145684E+10 | 0.689446E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245984.60 | 0.703158E+09 |
Annual Sum or Average | 0.181198E+11 | 0.790549E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39295549.15 | 0.612511E+10 |
Minimum of Months | 0.136988E+10 | 0.608471E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210205E+09 |
Maximum of Months | 0.163688E+10 | 0.708326E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22052821.44 | 0.797198E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.460031E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 407522.11 | 0.420645E+09 |
February | 0.882782E+09 | 0.396199E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63697.02 | 0.499407E+09 |
March | 0.105485E+10 | 0.456708E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7372.05 | 0.533487E+09 |
April | 0.936002E+09 | 0.396825E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566823.03 | 0.337035E+09 |
May | 0.101394E+10 | 0.418896E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400217E+09 |
June | 0.101113E+10 | 0.413383E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35149.25 | 0.215431E+09 |
July | 0.938820E+09 | 0.389211E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2824421.10 | 0.165116E+09 |
August | 0.105485E+10 | 0.437092E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2911254.28 | 0.202074E+09 |
September | 0.936002E+09 | 0.405162E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4896418.25 | 0.194764E+09 |
October | 0.973041E+09 | 0.432000E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16548056.17 | 0.291896E+09 |
November | 0.963541E+09 | 0.450054E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1052604.00 | 0.409829E+09 |
December | 0.938820E+09 | 0.449970E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 274916.83 | 0.437571E+09 |
Annual Sum or Average | 0.116768E+11 | 0.510553E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29588234.09 | 0.410747E+10 |
Minimum of Months | 0.882782E+09 | 0.389211E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165116E+09 |
Maximum of Months | 0.105485E+10 | 0.460031E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16548056.17 | 0.533487E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.729028E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2466054.53 | 0.624565E+09 |
February | 0.136985E+10 | 0.620830E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173346.64 | 0.734682E+09 |
March | 0.163685E+10 | 0.712788E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 308686.41 | 0.831603E+09 |
April | 0.145243E+10 | 0.615199E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2557507.07 | 0.509861E+09 |
May | 0.157338E+10 | 0.648898E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628347E+09 |
June | 0.156900E+10 | 0.640711E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50741.84 | 0.353253E+09 |
July | 0.145680E+10 | 0.603827E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5223782.94 | 0.258216E+09 |
August | 0.163685E+10 | 0.677481E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5482877.60 | 0.310164E+09 |
September | 0.145243E+10 | 0.629637E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8988863.81 | 0.290851E+09 |
October | 0.150991E+10 | 0.681340E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33515706.12 | 0.431748E+09 |
November | 0.149516E+10 | 0.714431E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5083882.51 | 0.608340E+09 |
December | 0.145680E+10 | 0.715666E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5251578.79 | 0.635404E+09 |
Annual Sum or Average | 0.181194E+11 | 0.798984E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69103028.26 | 0.621703E+10 |
Minimum of Months | 0.136985E+10 | 0.603827E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258216E+09 |
Maximum of Months | 0.163685E+10 | 0.729028E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33515706.12 | 0.831603E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.463431E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706569.83 | 0.450377E+09 |
February | 0.882782E+09 | 0.398265E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70246.23 | 0.526757E+09 |
March | 0.105485E+10 | 0.457047E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592258E+09 |
April | 0.936002E+09 | 0.396704E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 359172.26 | 0.378988E+09 |
May | 0.101394E+10 | 0.419853E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454076E+09 |
June | 0.101113E+10 | 0.415435E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33816.38 | 0.251090E+09 |
July | 0.938820E+09 | 0.391210E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3265185.57 | 0.194932E+09 |
August | 0.105485E+10 | 0.437613E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3329540.92 | 0.233057E+09 |
September | 0.936002E+09 | 0.404032E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5986359.65 | 0.216958E+09 |
October | 0.973041E+09 | 0.434820E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19250968.16 | 0.317764E+09 |
November | 0.963541E+09 | 0.457606E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 802287.78 | 0.440987E+09 |
December | 0.938820E+09 | 0.454587E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 536544.39 | 0.460211E+09 |
Annual Sum or Average | 0.116768E+11 | 0.513060E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34340691.16 | 0.451746E+10 |
Minimum of Months | 0.882782E+09 | 0.391210E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194932E+09 |
Maximum of Months | 0.105485E+10 | 0.463431E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19250968.16 | 0.592258E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.705632E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 564675.74 | 0.760037E+09 |
February | 0.136988E+10 | 0.611129E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105313.87 | 0.864435E+09 |
March | 0.163688E+10 | 0.708313E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914166E+09 |
April | 0.145246E+10 | 0.615998E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 583407.62 | 0.568616E+09 |
May | 0.157341E+10 | 0.652219E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644413E+09 |
June | 0.156904E+10 | 0.646062E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50743.83 | 0.350954E+09 |
July | 0.145684E+10 | 0.608454E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5075010.44 | 0.265492E+09 |
August | 0.163688E+10 | 0.680135E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4994470.24 | 0.339363E+09 |
September | 0.145246E+10 | 0.627728E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8772485.42 | 0.348300E+09 |
October | 0.150994E+10 | 0.664685E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27258097.27 | 0.528505E+09 |
November | 0.149520E+10 | 0.695476E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 217858.68 | 0.743754E+09 |
December | 0.145684E+10 | 0.689419E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362746.18 | 0.797698E+09 |
Annual Sum or Average | 0.181198E+11 | 0.790525E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47984809.30 | 0.712573E+10 |
Minimum of Months | 0.136988E+10 | 0.608454E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265492E+09 |
Maximum of Months | 0.163688E+10 | 0.708313E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27258097.27 | 0.914166E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.460021E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 689489.05 | 0.473409E+09 |
February | 0.882782E+09 | 0.396190E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71316.57 | 0.562578E+09 |
March | 0.105485E+10 | 0.456686E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39170.67 | 0.617487E+09 |
April | 0.936002E+09 | 0.396817E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 853055.72 | 0.404058E+09 |
May | 0.101394E+10 | 0.418888E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480359E+09 |
June | 0.101113E+10 | 0.413362E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33824.76 | 0.264264E+09 |
July | 0.938820E+09 | 0.389204E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3283979.63 | 0.206297E+09 |
August | 0.105485E+10 | 0.437085E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3352144.07 | 0.249101E+09 |
September | 0.936002E+09 | 0.405134E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5969430.26 | 0.236923E+09 |
October | 0.973041E+09 | 0.431980E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20113445.73 | 0.343372E+09 |
November | 0.963541E+09 | 0.450047E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1602597.97 | 0.469867E+09 |
December | 0.938820E+09 | 0.449959E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 751401.66 | 0.492752E+09 |
Annual Sum or Average | 0.116768E+11 | 0.510537E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36759856.09 | 0.480047E+10 |
Minimum of Months | 0.882782E+09 | 0.389204E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206297E+09 |
Maximum of Months | 0.105485E+10 | 0.460021E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20113445.73 | 0.617487E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.148158E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.134390E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.159693E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.142638E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.153925E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.153181E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.143382E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.159693E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.142638E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.148158E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.146421E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.143382E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.177566E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.134390E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.159693E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.148158E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.134390E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.159693E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.142638E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.153925E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.153181E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.143382E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.159693E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.142638E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.148158E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.146421E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.143382E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.177566E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.134390E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.159693E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.148158E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.134390E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.159693E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.142638E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.153925E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.153181E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.143382E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.159693E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.142638E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.148158E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.146421E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.143382E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.177566E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.134390E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.159693E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.290468E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.263476E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.313083E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.279647E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.301776E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.300317E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.281106E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.313083E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.279647E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.290468E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.287064E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.281106E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.348124E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.263476E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.313083E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285484.42 | 0.632088E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51814.44 | 0.733997E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769214E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339991.82 | 0.452521E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522153E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7854.53 | 0.279547E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2584144.96 | 0.203651E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2450915.66 | 0.255847E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5645697.47 | 0.251942E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20451048.86 | 0.405148E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617598.74 | 0.598792E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139655.86 | 0.658284E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32574206.77 | 0.576318E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203651E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20451048.86 | 0.769214E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872469.65 | 0.105984E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109426.21 | 0.123919E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130906E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1104162.89 | 0.766072E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907419E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13592.79 | 0.483750E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4932919.03 | 0.350619E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4703899.67 | 0.445980E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10135062.27 | 0.435106E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38460557.50 | 0.693591E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2373599.99 | 0.101512E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464801.57 | 0.109905E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63170491.58 | 0.980480E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350619E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38460557.50 | 0.130906E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1623799.07 | 0.102813E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29629.91 | 0.122115E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135842E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271541.37 | 0.869517E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103474E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592497E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2252035.06 | 0.461237E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1684096.78 | 0.534475E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10255151.57 | 0.512294E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37142635.34 | 0.724483E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2558497.25 | 0.101471E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654378.50 | 0.105649E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56471764.85 | 0.104081E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461237E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37142635.34 | 0.135842E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10780.55 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10780.55 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10780.55 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10780.55 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10780.55 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10780.55 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10780.55 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10780.55 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10780.55 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10780.55 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10780.55 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10780.55 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10780.55 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10780.55 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9681.69 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9681.69 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9681.69 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9681.69 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9681.69 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9681.69 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9681.69 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9681.69 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9681.69 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9681.69 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9681.69 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9681.69 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9681.69 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9681.69 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9681.69 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9681.69 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9681.69 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9681.69 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9681.69 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9681.69 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9681.69 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9681.69 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9681.69 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9681.69 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9681.69 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9681.69 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9681.69 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9681.69 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9681.69 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9681.69 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9681.69 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9681.69 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9681.69 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9681.69 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9681.69 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9681.69 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9681.69 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9681.69 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1215.63 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 14-JAN-11:00 | 724.43 | 02-JAN-02:55 |
February | 2010.79 | 01-FEB-10:09 | 1067.44 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 01-FEB-12:00 | 638.27 | 12-FEB-19:00 |
March | 2010.79 | 01-MAR-10:09 | 786.71 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 683.55 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 671.50 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 | 30-APR-10:43 | 425.19 | 17-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 654.18 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 386.15 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 638.76 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 29-JUN-11:00 | 273.37 | 07-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 619.01 | 12-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.21 | 31-JUL-13:00 | 219.74 | 09-JUL-17:30 |
August | 2010.79 | 01-AUG-09:09 | 655.87 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 17-AUG-14:00 | 198.47 | 21-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 842.12 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.05 | 29-SEP-14:00 | 221.00 | 04-SEP-17:35 |
October | 2010.79 | 02-OCT-09:09 | 861.15 | 24-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.34 | 15-OCT-09:00 | 453.01 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1215.63 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 19-NOV-12:51 | 598.15 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1215.63 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 | 05-DEC-10:00 | 550.91 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 619.01 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 198.47 | |||||
Maximum of Months | 2010.79 | 1215.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 235.34 | 724.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 783.40 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 14-JAN-11:00 | 484.55 | 02-JAN-02:55 |
February | 1295.83 | 01-FEB-10:09 | 691.73 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 01-FEB-12:00 | 407.58 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 500.80 | 06-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 441.56 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 437.10 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 26-APR-13:00 | 277.17 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 402.48 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 251.34 | 27-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 372.74 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 29-JUN-11:00 | 177.55 | 07-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 372.74 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 31-JUL-13:00 | 140.03 | 09-JUL-16:52 |
August | 1295.83 | 01-AUG-09:09 | 400.22 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 17-AUG-14:00 | 128.34 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 437.64 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 29-SEP-14:00 | 183.93 | 03-SEP-06:45 |
October | 1295.83 | 02-OCT-09:09 | 586.36 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.42 | 15-OCT-12:45 | 301.90 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 | 19-NOV-12:51 | 397.74 | 23-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 05-DEC-10:00 | 358.13 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 128.34 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 145.42 | 484.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1215.66 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 14-JAN-11:00 | 651.84 | 02-JAN-02:55 |
February | 2010.83 | 01-FEB-10:09 | 1057.90 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 01-FEB-12:00 | 614.93 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 676.46 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 669.18 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 668.69 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 26-APR-13:00 | 418.73 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 657.86 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 03-MAY-12:00 | 367.24 | 07-MAY-14:53 |
June | 2010.83 | 01-JUN-09:09 | 647.52 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 29-JUN-11:00 | 268.73 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 630.68 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.21 | 31-JUL-13:00 | 213.67 | 09-JUL-16:52 |
August | 2010.83 | 01-AUG-09:09 | 657.75 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 17-AUG-14:00 | 202.44 | 27-AUG-18:00 |
September | 2010.83 | 01-SEP-09:09 | 823.48 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 29-SEP-14:00 | 270.97 | 03-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 800.87 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.98 | 15-OCT-13:00 | 467.40 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1215.66 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 18-NOV-13:10 | 606.89 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1215.66 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 05-DEC-10:00 | 557.30 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 630.68 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 202.44 | |||||
Maximum of Months | 2010.83 | 1215.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 205.98 | 669.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 783.40 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 14-JAN-11:00 | 500.63 | 02-JAN-02:55 |
February | 1295.83 | 01-FEB-10:09 | 673.47 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 01-FEB-12:00 | 485.59 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 546.64 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 508.81 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 434.90 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 26-APR-13:00 | 364.15 | 16-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 431.57 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 331.80 | 29-MAY-16:00 |
June | 1295.83 | 01-JUN-09:09 | 425.48 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 29-JUN-11:00 | 238.19 | 04-JUN-17:20 |
July | 1295.83 | 03-JUL-09:09 | 419.12 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 31-JUL-13:00 | 214.91 | 09-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 433.57 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 17-AUG-14:00 | 187.41 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 572.64 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 29-SEP-14:00 | 235.08 | 03-SEP-16:40 |
October | 1295.83 | 02-OCT-09:09 | 577.93 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.05 | 15-OCT-12:43 | 349.74 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 18-NOV-13:00 | 463.68 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 05-DEC-10:00 | 415.77 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 419.12 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 187.41 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 145.05 | 508.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1215.63 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.78 | 15-JAN-10:00 | 1225.32 | 27-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1065.78 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 01-FEB-12:00 | 1272.03 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 781.06 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 11-MAR-13:05 | 1398.04 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 667.13 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.67 | 30-APR-10:43 | 867.74 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 648.85 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 856.19 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 632.58 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 29-JUN-11:00 | 592.75 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 578.40 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.57 | 23-JUL-10:55 | 472.24 | 16-JUL-18:00 |
August | 2010.79 | 01-AUG-09:09 | 650.65 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.21 | 06-AUG-13:10 | 419.20 | 21-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 837.46 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.61 | 29-SEP-14:00 | 461.09 | 24-SEP-15:10 |
October | 2010.79 | 02-OCT-09:09 | 856.48 | 24-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.44 | 15-OCT-09:00 | 912.38 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1215.63 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.53 | 19-NOV-12:51 | 1177.44 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1215.63 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.18 | 25-DEC-11:52 | 1137.52 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.20 | |||||
Maximum of Months | 2010.79 | 1215.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 596.44 | 1398.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 783.40 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 14-JAN-11:10 | 826.06 | 27-JAN-05:00 |
February | 1239.33 | 01-FEB-08:09 | 689.34 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 | 01-FEB-12:00 | 847.61 | 25-FEB-03:00 |
March | 1239.33 | 01-MAR-08:09 | 494.23 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 932.01 | 28-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 434.61 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 26-APR-13:00 | 589.53 | 21-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 398.59 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 574.51 | 29-MAY-12:55 |
June | 1239.33 | 01-JUN-07:10 | 372.74 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 29-JUN-11:00 | 416.72 | 04-JUN-14:00 |
July | 1239.33 | 03-JUL-07:10 | 372.74 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 31-JUL-13:00 | 344.28 | 02-JUL-18:55 |
August | 1239.33 | 01-AUG-07:10 | 396.42 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 | 17-AUG-14:10 | 285.46 | 27-AUG-17:52 |
September | 1239.33 | 01-SEP-07:10 | 435.39 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.70 | 29-SEP-14:10 | 414.15 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 581.07 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.16 | 15-OCT-12:56 | 634.87 | 30-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 783.40 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.12 | 19-NOV-12:51 | 812.04 | 23-NOV-07:00 |
December | 1239.33 | 01-DEC-08:09 | 783.40 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 05-DEC-10:00 | 772.16 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.46 | |||||
Maximum of Months | 1239.33 | 783.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 339.16 | 932.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1215.66 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 14-JAN-11:00 | 1306.22 | 07-JAN-02:00 |
February | 2010.83 | 01-FEB-10:09 | 1056.22 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 01-FEB-12:00 | 1325.48 | 20-FEB-15:10 |
March | 2010.83 | 01-MAR-10:09 | 675.36 | 01-MAR-17:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1422.58 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 664.18 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 26-APR-13:00 | 906.07 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 652.71 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 838.93 | 07-MAY-15:00 |
June | 2010.83 | 01-JUN-09:09 | 641.76 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 29-JUN-11:00 | 591.55 | 06-JUN-21:10 |
July | 2010.83 | 03-JUL-09:09 | 623.96 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.32 | 31-JUL-13:00 | 474.24 | 09-JUL-17:10 |
August | 2010.83 | 01-AUG-09:09 | 652.63 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | 17-AUG-14:00 | 431.87 | 21-AUG-23:55 |
September | 2010.83 | 01-SEP-09:09 | 818.63 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.81 | 29-SEP-14:00 | 638.53 | 04-SEP-14:10 |
October | 2010.83 | 02-OCT-09:09 | 795.75 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.13 | 15-OCT-13:00 | 1041.40 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1215.66 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 18-NOV-13:30 | 1294.08 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1215.66 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 05-DEC-10:00 | 1223.83 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 623.96 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.87 | |||||
Maximum of Months | 2010.83 | 1215.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 473.13 | 1422.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 783.40 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 14-JAN-11:00 | 844.80 | 27-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 670.86 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 | 01-FEB-12:00 | 880.63 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 540.37 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 11-MAR-11:05 | 977.56 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 432.29 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 | 30-APR-10:43 | 754.18 | 16-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 428.76 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 756.40 | 07-MAY-15:00 |
June | 1295.83 | 01-JUN-09:09 | 422.34 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 29-JUN-11:00 | 536.31 | 04-JUN-17:20 |
July | 1295.83 | 03-JUL-09:09 | 415.61 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 31-JUL-13:00 | 513.09 | 09-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 430.88 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 | 17-AUG-14:00 | 373.02 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 566.92 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.07 | 29-SEP-14:00 | 541.37 | 03-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 572.52 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.67 | 15-OCT-09:00 | 668.61 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 | 19-NOV-12:02 | 844.96 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 05-DEC-10:00 | 800.93 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 415.61 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.02 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 368.67 | 977.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1215.63 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.27 | 15-JAN-10:00 | 1381.50 | 27-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1065.47 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 01-FEB-12:00 | 1400.83 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 780.23 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 | 11-MAR-13:05 | 1722.51 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 666.95 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.16 | 30-APR-11:20 | 1014.20 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 648.64 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1046.16 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 632.32 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 29-JUN-11:00 | 720.11 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 578.40 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 31-JUL-13:00 | 630.94 | 09-JUL-17:10 |
August | 2010.79 | 01-AUG-09:09 | 650.44 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.25 | 06-AUG-12:57 | 500.37 | 27-AUG-17:52 |
September | 2010.79 | 01-SEP-09:09 | 836.70 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.09 | 29-SEP-14:00 | 595.06 | 04-SEP-18:00 |
October | 2010.79 | 02-OCT-09:09 | 855.78 | 24-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.65 | 15-OCT-08:53 | 999.97 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1215.63 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.00 | 19-NOV-12:53 | 1247.99 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1215.63 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 330.86 | 25-DEC-12:00 | 1283.14 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.37 | |||||
Maximum of Months | 2010.79 | 1215.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 780.65 | 1722.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 783.40 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 | 15-JAN-10:00 | 942.43 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 689.15 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 01-FEB-12:00 | 935.73 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 494.11 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1147.85 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 434.51 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 26-APR-13:00 | 704.82 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 398.40 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 719.45 | 29-MAY-12:55 |
June | 1295.83 | 01-JUN-09:09 | 372.74 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 29-JUN-11:00 | 539.28 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 372.74 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 31-JUL-13:00 | 444.39 | 16-JUL-17:50 |
August | 1295.83 | 01-AUG-09:09 | 396.23 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 17-AUG-14:00 | 378.52 | 27-AUG-17:52 |
September | 1295.83 | 01-SEP-09:09 | 435.29 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.39 | 29-SEP-14:00 | 458.30 | 03-SEP-07:00 |
October | 1295.83 | 02-OCT-09:09 | 580.69 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.29 | 15-OCT-12:34 | 702.47 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.35 | 19-NOV-13:00 | 860.03 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.92 | 17-DEC-13:00 | 874.82 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.52 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 405.29 | 1147.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1215.66 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 15-JAN-10:00 | 1533.61 | 06-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 1055.90 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 | 01-FEB-12:00 | 1661.81 | 20-FEB-14:50 |
March | 2010.83 | 01-MAR-10:09 | 675.36 | 01-MAR-17:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1729.12 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 664.00 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.56 | 26-APR-13:00 | 1096.56 | 16-APR-18:00 |
May | 2010.83 | 01-MAY-09:09 | 652.50 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1021.17 | 20-MAY-17:55 |
June | 2010.83 | 01-JUN-09:09 | 641.53 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 29-JUN-11:00 | 719.03 | 06-JUN-21:10 |
July | 2010.83 | 03-JUL-09:09 | 623.69 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 31-JUL-13:00 | 635.12 | 09-JUL-17:10 |
August | 2010.83 | 01-AUG-09:09 | 652.42 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.08 | 17-AUG-14:00 | 564.69 | 27-AUG-17:52 |
September | 2010.83 | 01-SEP-09:09 | 817.84 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.38 | 29-SEP-14:00 | 802.69 | 03-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 794.95 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 575.10 | 15-OCT-12:58 | 1176.51 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1215.66 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 18-NOV-13:00 | 1409.84 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1215.66 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.65 | 05-DEC-10:00 | 1403.83 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 623.69 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.69 | |||||
Maximum of Months | 2010.83 | 1215.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 575.10 | 1729.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 783.40 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 15-JAN-10:00 | 983.63 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 670.65 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 01-FEB-12:00 | 990.58 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 539.89 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 11-MAR-11:05 | 1161.19 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 432.19 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.66 | 30-APR-11:10 | 995.95 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 428.66 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 935.61 | 20-MAY-17:55 |
June | 1295.83 | 01-JUN-09:09 | 422.22 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 29-JUN-11:00 | 676.50 | 04-JUN-17:20 |
July | 1295.83 | 03-JUL-09:09 | 415.48 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 31-JUL-13:00 | 652.55 | 09-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 430.78 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 17-AUG-14:00 | 474.54 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 566.51 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.39 | 29-SEP-14:00 | 671.53 | 03-SEP-16:40 |
October | 1295.83 | 02-OCT-09:09 | 572.11 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.51 | 15-OCT-08:53 | 758.55 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 783.40 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.97 | 19-NOV-12:22 | 926.20 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 783.40 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.68 | 25-DEC-12:00 | 921.87 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 415.48 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.54 | |||||
Maximum of Months | 1295.83 | 783.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 478.51 | 1161.19 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 155.04 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 155.04 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 155.04 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 155.04 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 155.04 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 155.04 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 155.04 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 155.04 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 155.04 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 155.04 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 155.04 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 155.04 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 155.04 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 155.04 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 155.04 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 155.04 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 155.04 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 155.04 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 155.04 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 155.04 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 155.04 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 155.04 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 155.04 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 155.04 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 155.04 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 155.04 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 155.04 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 155.04 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 155.04 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 155.04 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 155.04 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 155.04 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 155.04 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 155.04 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 155.04 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 155.04 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3039.65 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3039.65 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3039.65 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3039.65 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3039.65 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3039.65 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3039.65 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3039.65 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3039.65 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3039.65 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3039.65 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3039.65 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3039.65 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3039.65 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 | 14-JAN-11:00 | 1602.02 | 02-JAN-02:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 | 01-FEB-12:00 | 1386.26 | 12-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1475.59 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 | 26-APR-13:00 | 913.10 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 821.74 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 29-JUN-11:00 | 576.25 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 | 31-JUL-13:00 | 435.45 | 02-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | 17-AUG-14:00 | 414.28 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.96 | 29-SEP-13:50 | 498.68 | 04-SEP-17:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.48 | 15-OCT-13:00 | 983.71 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.77 | 19-NOV-13:00 | 1344.24 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 05-DEC-10:00 | 1202.67 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.28 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.48 | 1602.02 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.18 | 15-JAN-10:00 | 2308.60 | 02-JAN-02:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.28 | 01-FEB-12:00 | 2372.58 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2527.62 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.80 | 30-APR-10:53 | 1525.05 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1460.12 | 27-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 29-JUN-11:00 | 1001.97 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.57 | 23-JUL-11:00 | 741.27 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.03 | 06-AUG-12:53 | 723.31 | 21-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.95 | 29-SEP-13:50 | 825.35 | 04-SEP-17:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.69 | 15-OCT-13:00 | 1667.99 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.69 | 19-NOV-13:00 | 2300.05 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.77 | 05-DEC-10:00 | 2082.39 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.69 | 2527.62 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.80 | 15-JAN-10:00 | 2207.32 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 01-FEB-12:00 | 2316.37 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2666.32 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 30-APR-10:43 | 1701.71 | 16-APR-17:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1731.60 | 20-MAY-17:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 1276.29 | 04-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.38 | 31-JUL-13:00 | 1109.34 | 09-JUL-16:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 | 17-AUG-14:00 | 907.60 | 27-AUG-17:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.24 | 29-SEP-13:30 | 1053.35 | 24-SEP-14:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 15-OCT-08:53 | 1638.47 | 11-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.84 | 19-NOV-13:00 | 2041.19 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.64 | 04-DEC-10:00 | 2094.21 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.60 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 2666.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94182.01 | 02-JAN-05:11 | 0.00 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93775.84 | 21-FEB-05:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93970.49 | 20-MAR-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94947.45 | 10-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97779.94 | 30-MAY-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93429.72 | 05-JUN-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86924.11 | 10-JUL-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88217.16 | 28-AUG-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88413.39 | 20-SEP-05:02 | 10771.35 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95252.23 | 30-OCT-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94597.88 | 06-NOV-05:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 97740.15 | 04-DEC-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 86924.11 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97779.94 | 10771.35 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84946.30 | 02-JAN-05:11 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82398.56 | 21-FEB-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81065.14 | 13-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82136.24 | 10-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81727.07 | 30-MAY-04:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82147.43 | 12-JUN-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81340.17 | 17-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80332.14 | 29-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83478.70 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85169.59 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86057.02 | 13-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 84695.60 | 26-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80332.14 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86057.02 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 70950.85 | 20-JAN-06:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69438.72 | 02-FEB-06:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71878.37 | 24-MAR-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72077.74 | 26-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71446.32 | 24-MAY-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72394.14 | 07-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71648.22 | 21-JUL-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71689.13 | 01-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71850.51 | 02-SEP-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71770.99 | 10-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71162.50 | 02-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70065.00 | 08-DEC-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 69438.72 | 0.00 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72394.14 | 9673.43 | 3761.52 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30713.39 | 19-JAN-15:00 | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30970.11 | 02-FEB-16:20 | 15316.26 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50667.33 | 24-MAR-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65013.36 | 27-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65959.03 | 03-MAY-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67659.15 | 28-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67664.34 | 31-JUL-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68169.03 | 21-AUG-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67468.12 | 25-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67670.22 | 16-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39313.33 | 01-NOV-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30492.79 | 07-DEC-15:00 | 16014.58 | 9681.69 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 30492.79 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68169.03 | 16014.58 | 9681.69 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5526.48 | 17-JAN-13:40 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
February | 4725.60 | 21-FEB-13:10 | 3846.22 | 1156.80 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 |
March | 5614.60 | 13-MAR-13:40 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.27 |
April | 6781.13 | 26-APR-13:40 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 |
May | 7281.10 | 03-MAY-05:02 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
June | 10292.23 | 19-JUN-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 |
July | 9884.29 | 03-JUL-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9620.56 | 21-AUG-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.87 |
September | 9332.30 | 30-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 9664.53 | 04-OCT-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.86 |
November | 5334.11 | 13-NOV-11:30 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 |
December | 5755.92 | 05-DEC-14:30 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4725.60 | 0.00 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10292.23 | 3846.22 | 1156.80 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 62.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6870.65 | 20-JAN-09:00 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10310.79 | 20-FEB-08:43 | 195.68 | 62.12 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.03 |
March | 11218.61 | 12-MAR-09:03 | 195.68 | 62.12 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.05 |
April | 17511.52 | 30-APR-07:42 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
May | 17379.18 | 28-MAY-08:23 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.23 |
June | 17400.24 | 18-JUN-09:23 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 |
July | 18211.18 | 23-JUL-08:12 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 |
August | 18043.23 | 06-AUG-08:32 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.53 |
September | 18115.89 | 10-SEP-08:32 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.06 |
October | 18413.96 | 15-OCT-08:42 | 391.37 | 124.24 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 | 0.00 |
November | 11607.42 | 19-NOV-09:43 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
December | 7462.28 | 05-DEC-08:50 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6870.65 | 195.68 | 62.12 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18413.96 | 1239.33 | 372.74 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 | 162.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21709.13 | 22-JAN-13:12 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.63 |
February | 20506.47 | 19-FEB-12:13 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.90 |
March | 20242.92 | 19-MAR-12:53 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.80 |
April | 18242.85 | 30-APR-13:02 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.55 |
May | 8569.79 | 04-MAY-12:30 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
June | 7684.65 | 26-JUN-12:30 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
July | 10917.41 | 31-JUL-12:30 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 0.00 |
August | 15035.25 | 20-AUG-13:02 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 |
September | 19769.99 | 10-SEP-13:13 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.20 |
October | 22177.77 | 15-OCT-11:21 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 68.21 | 0.00 |
November | 21282.98 | 23-NOV-13:32 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.20 |
December | 22101.00 | 25-DEC-13:11 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7684.65 | 404.87 | 128.53 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22177.77 | 1923.15 | 578.41 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 68.21 | 303.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14244.03 | 22-JAN-14:32 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.95 |
February | 18101.80 | 26-FEB-16:23 | 260.91 | 82.83 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.66 |
March | 21946.81 | 19-MAR-15:32 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.23 |
April | 22900.09 | 30-APR-15:42 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.02 |
May | 19646.84 | 28-MAY-16:02 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.21 |
June | 22040.01 | 25-JUN-16:02 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.52 |
July | 24731.08 | 30-JUL-15:31 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.47 |
August | 23486.05 | 06-AUG-16:31 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.94 |
September | 23462.87 | 10-SEP-15:52 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 |
October | 23865.91 | 15-OCT-14:01 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 0.00 |
November | 21851.49 | 26-NOV-14:12 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.63 |
December | 23116.03 | 25-DEC-14:32 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14244.03 | 260.91 | 82.83 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24731.08 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 325.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3720.66 | 18-JAN-14:20 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 3217.78 | 01-FEB-13:10 | 3846.22 | 1156.80 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 |
March | 3765.45 | 23-MAR-14:40 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 |
April | 5282.83 | 26-APR-14:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 0.00 |
May | 5801.79 | 04-MAY-13:50 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.63 |
June | 5591.48 | 29-JUN-16:00 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 |
July | 6245.27 | 19-JUL-14:40 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 54.07 | 0.00 |
August | 6169.51 | 17-AUG-14:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | 0.00 |
September | 8892.12 | 30-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
October | 7310.51 | 05-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3289.33 | 01-NOV-13:50 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.61 |
December | 3663.35 | 05-DEC-15:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3217.78 | 1012.16 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8892.12 | 3846.22 | 1156.80 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | 85.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6343.82 | 20-JAN-11:05 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 |
February | 6262.69 | 01-FEB-11:05 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
March | 9651.32 | 23-MAR-10:05 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 |
April | 16717.47 | 30-APR-07:42 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 |
May | 17910.30 | 28-MAY-08:43 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.03 |
June | 18594.15 | 25-JUN-09:12 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.57 |
July | 19019.03 | 23-JUL-08:62 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 |
August | 18863.50 | 06-AUG-09:02 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.75 |
September | 17624.38 | 03-SEP-08:32 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.74 |
October | 15793.56 | 15-OCT-08:53 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 292.69 | 0.00 |
November | 9800.12 | 19-NOV-09:43 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 |
December | 6208.66 | 05-DEC-09:20 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6208.66 | 260.91 | 82.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19019.03 | 2478.65 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 292.69 | 277.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20084.52 | 22-JAN-13:22 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.77 |
February | 20667.98 | 20-FEB-13:12 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.20 |
March | 19587.72 | 19-MAR-12:53 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.88 |
April | 14783.64 | 30-APR-13:02 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.61 |
May | 8031.56 | 04-MAY-12:30 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 |
June | 6909.36 | 30-JUN-12:30 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
July | 10047.81 | 31-JUL-12:40 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 0.00 |
August | 12466.17 | 30-AUG-13:00 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
September | 18153.73 | 10-SEP-14:43 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.52 |
October | 21655.24 | 29-OCT-13:32 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.42 |
November | 20379.73 | 19-NOV-13:02 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.53 |
December | 20811.84 | 24-DEC-13:52 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6909.36 | 404.87 | 128.53 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21655.24 | 1923.15 | 578.41 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 1074.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7827.19 | 26-JAN-15:30 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.94 |
February | 10416.66 | 20-FEB-15:52 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.96 |
March | 14473.99 | 19-MAR-16:12 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.41 |
April | 19940.18 | 09-APR-15:52 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.17 |
May | 17674.36 | 14-MAY-15:23 | 260.91 | 82.83 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.14 |
June | 20488.78 | 18-JUN-16:42 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.11 |
July | 20915.09 | 30-JUL-15:31 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.57 |
August | 21274.23 | 20-AUG-16:01 | 456.59 | 144.95 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.41 |
September | 19730.43 | 03-SEP-16:32 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.49 |
October | 20401.97 | 01-OCT-15:12 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.11 |
November | 8372.69 | 07-NOV-15:30 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
December | 8295.99 | 18-DEC-15:30 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7827.19 | 260.91 | 82.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 | |
Maximum of Months | 21274.23 | 1239.33 | 372.74 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3305.36 | 18-JAN-15:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 |
February | 2710.86 | 16-FEB-14:50 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.65 |
March | 3846.81 | 23-MAR-15:10 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.15 |
April | 5749.58 | 26-APR-14:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | 0.00 |
May | 6338.14 | 04-MAY-13:50 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.77 |
June | 6200.38 | 30-JUN-14:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
July | 7026.55 | 19-JUL-14:50 | 1923.11 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 0.00 |
August | 6789.57 | 17-AUG-14:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 78.08 | 0.00 |
September | 10382.81 | 30-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
October | 8457.30 | 05-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3037.27 | 10-NOV-14:30 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.75 |
December | 3265.83 | 05-DEC-15:00 | 2010.79 | 578.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2710.86 | 1012.16 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10382.81 | 2010.79 | 578.40 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 78.08 | 134.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4811.06 | 20-JAN-09:40 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 |
February | 4686.90 | 02-FEB-10:10 | 2591.66 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.93 |
March | 7800.96 | 23-MAR-09:30 | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 |
April | 15142.61 | 30-APR-10:13 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.42 |
May | 14162.35 | 28-MAY-08:43 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.00 |
June | 14451.07 | 18-JUN-10:13 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.08 |
July | 18008.50 | 04-JUL-08:62 | 260.91 | 82.83 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.87 |
August | 18523.58 | 13-AUG-09:02 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.89 |
September | 18299.08 | 10-SEP-08:32 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.38 |
October | 18425.54 | 15-OCT-09:52 | 326.14 | 103.54 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 | 0.00 |
November | 4258.34 | 01-NOV-09:30 | 1295.83 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.68 |
December | 4859.50 | 05-DEC-09:50 | 1239.33 | 372.74 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4258.34 | 260.91 | 82.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18523.58 | 2591.66 | 745.48 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 | 343.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22763.95 | 22-JAN-13:42 | 607.31 | 192.80 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.64 |
February | 21320.94 | 20-FEB-13:32 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1255.77 |
March | 16959.37 | 19-MAR-12:23 | 303.66 | 96.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.74 |
April | 11786.57 | 26-APR-13:10 | 4021.67 | 1156.82 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 53.04 | 0.00 |
May | 8520.25 | 04-MAY-12:30 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 |
June | 7516.26 | 30-JUN-13:10 | 4021.67 | 1156.82 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
July | 10736.93 | 31-JUL-12:40 | 1923.15 | 578.41 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 87.42 | 0.00 |
August | 12986.14 | 30-AUG-13:05 | 4021.67 | 1156.82 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 |
September | 20864.24 | 10-SEP-13:13 | 404.87 | 128.53 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.00 |
October | 23861.00 | 15-OCT-11:11 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 141.22 | 0.00 |
November | 21798.41 | 19-NOV-12:42 | 506.09 | 160.66 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 |
December | 22586.95 | 25-DEC-13:11 | 708.53 | 224.93 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7516.26 | 303.66 | 96.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23861.00 | 4021.67 | 1156.82 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 141.22 | 1255.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7637.96 | 18-JAN-15:00 | 1295.83 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 |
February | 8449.53 | 22-FEB-15:50 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.95 |
March | 11523.00 | 19-MAR-16:23 | 260.91 | 82.83 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.70 |
April | 20920.25 | 02-APR-16:02 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.10 |
May | 16531.11 | 29-MAY-15:32 | 260.91 | 82.83 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.26 |
June | 19813.40 | 25-JUN-16:42 | 326.14 | 103.54 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.53 |
July | 22020.86 | 16-JUL-15:52 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.59 |
August | 21581.72 | 20-AUG-16:11 | 587.05 | 186.37 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.01 |
September | 21587.84 | 10-SEP-15:52 | 391.37 | 124.24 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.27 |
October | 23094.58 | 15-OCT-15:11 | 521.82 | 165.66 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 67.33 | 0.00 |
November | 8117.68 | 10-NOV-14:50 | 1295.83 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.16 |
December | 7987.82 | 19-DEC-15:30 | 1239.33 | 372.74 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7637.96 | 260.91 | 82.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23094.58 | 1295.83 | 372.74 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.33 | 734.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6560.77 | 17-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 |
February | 5972.17 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.34 |
March | 6017.33 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.78 |
April | 6606.10 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.28 |
May | 7088.33 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6596.67 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 |
July | 9147.37 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7948.94 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 |
September | 8965.22 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9970.98 | 16-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.80 |
November | 8413.11 | 13-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.29 |
December | 8531.78 | 26-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5972.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9970.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4704.32 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.34 |
February | 2864.27 | 04-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.26 |
March | 3868.65 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.47 |
April | 3662.65 | 27-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 |
May | 3474.12 | 04-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 |
June | 4035.45 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 |
July | 4680.61 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 | 0.00 |
August | 4606.53 | 18-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 0.00 |
September | 5686.78 | 30-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
October | 7623.01 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.75 |
November | 3165.81 | 02-NOV-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 |
December | 2905.07 | 20-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2864.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7623.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 | 527.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6677.82 | 18-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.31 |
February | 6481.17 | 01-FEB-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.31 |
March | 9999.66 | 23-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.85 |
April | 13488.72 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 | 0.00 |
May | 12512.29 | 03-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.18 |
June | 12642.30 | 30-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.31 |
July | 14320.54 | 19-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 | 0.00 |
August | 13915.32 | 14-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 |
September | 13869.77 | 29-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.44 | 0.00 |
October | 15632.75 | 16-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.26 | 0.00 |
November | 6412.00 | 10-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.33 |
December | 6029.18 | 05-DEC-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6029.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15632.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.44 | 219.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1985.98 | 30-JAN-16:50 | 222.14 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4114.68 | 20-FEB-16:55 | 23.38 | 17.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6975.73 | 31-MAR-24:00 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7919.93 | 30-APR-17:27 | 0.00 | 34.46 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3259.00 | 31-MAY-24:00 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5308.05 | 30-JUN-24:00 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7220.88 | 31-JUL-24:00 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8061.09 | 06-AUG-17:41 | 0.00 | 60.30 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3474.15 | 30-SEP-24:00 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5282.54 | 31-OCT-24:00 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5968.15 | 12-NOV-16:20 | 23.38 | 17.23 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7979.72 | 25-DEC-16:20 | 23.38 | 17.23 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1985.98 | 0.00 | 8.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8061.09 | 222.14 | 155.04 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1799.76 | 30-JAN-16:50 | 222.14 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3724.25 | 22-FEB-17:00 | 222.14 | 155.04 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6263.94 | 31-MAR-23:30 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7360.19 | 30-APR-17:27 | 0.00 | 34.46 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2930.65 | 31-MAY-24:00 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5009.59 | 30-JUN-24:00 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6865.87 | 31-JUL-24:00 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7471.18 | 06-AUG-18:00 | 0.00 | 43.07 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3285.19 | 30-SEP-24:00 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4887.26 | 31-OCT-24:00 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5480.24 | 07-NOV-16:30 | 222.14 | 155.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7280.69 | 18-DEC-16:20 | 222.14 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1799.76 | 0.00 | 8.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7471.18 | 222.14 | 155.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1733.59 | 26-JAN-16:10 | 222.14 | 155.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3709.92 | 22-FEB-17:00 | 222.14 | 155.04 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5883.37 | 31-MAR-23:20 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7404.41 | 30-APR-17:30 | 0.00 | 34.46 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2675.75 | 31-MAY-23:40 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4890.71 | 30-JUN-24:00 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6765.90 | 31-JUL-24:00 | 0.00 | 8.61 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7610.17 | 06-AUG-17:41 | 0.00 | 60.30 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3252.79 | 30-SEP-23:50 | 0.00 | 8.61 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4669.71 | 31-OCT-23:30 | 0.00 | 8.61 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5459.27 | 07-NOV-16:30 | 222.14 | 155.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7277.72 | 19-DEC-16:20 | 222.14 | 155.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1733.59 | 0.00 | 8.61 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7610.17 | 222.14 | 155.04 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91301.06 | 02-JAN-17:00 | 4808.68 | 3039.65 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182355.65 | 21-FEB-17:00 | 4808.68 | 3039.65 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357342.15 | 31-MAR-24:00 | 0.00 | 168.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365843.84 | 26-APR-14:05 | 9617.36 | 6079.31 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 174650.47 | 31-MAY-24:00 | 0.00 | 168.86 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266307.00 | 30-JUN-24:00 | 0.00 | 168.86 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358644.66 | 31-JUL-24:00 | 0.00 | 168.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369319.29 | 26-AUG-17:02 | 1265.44 | 844.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175353.07 | 30-SEP-24:00 | 0.00 | 168.86 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267197.21 | 31-OCT-24:00 | 0.00 | 168.86 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274888.68 | 13-NOV-17:00 | 4808.68 | 3039.65 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367467.03 | 19-DEC-14:05 | 10055.84 | 6079.31 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91301.06 | 0.00 | 168.86 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369319.29 | 10055.84 | 6079.31 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.137473E+13 | 993947.54 | 18-JAN-11:00 | 0.781240E+11 | 384402.50 | 03-JAN-07:10 |
February | 0.152284E+13 | 1159979.73 | 01-FEB-09:00 | 0.607012E+11 | 158636.46 | 09-FEB-07:10 |
March | 0.204308E+13 | 1341074.77 | 23-MAR-15:09 | 0.763229E+11 | 276036.85 | 30-MAR-06:10 |
April | 0.238231E+13 | 1503801.48 | 26-APR-15:30 | 0.593503E+11 | 158972.92 | 01-APR-06:10 |
May | 0.135791E+13 | 975758.49 | 04-MAY-12:20 | 0.610515E+11 | 76090.70 | 03-MAY-11:50 |
June | 0.173787E+13 | 1201519.52 | 29-JUN-15:00 | 0.590533E+11 | 74894.03 | 07-JUN-11:39 |
July | 0.230827E+13 | 1464429.96 | 31-JUL-15:09 | 0.572574E+11 | 74075.81 | 11-JUL-11:39 |
August | 0.282939E+13 | 1599954.87 | 18-AUG-15:09 | 0.606530E+11 | 74017.72 | 30-AUG-11:50 |
September | 0.140264E+13 | 1114211.44 | 29-SEP-15:00 | 0.567215E+11 | 74736.59 | 26-SEP-11:20 |
October | 0.189391E+13 | 1308337.60 | 16-OCT-07:30 | 0.595290E+11 | 75889.76 | 30-OCT-11:30 |
November | 0.205151E+13 | 1361111.96 | 28-NOV-13:00 | 0.602857E+11 | 91918.12 | 24-NOV-07:10 |
December | 0.253915E+13 | 1534387.17 | 05-DEC-16:10 | 0.692230E+11 | 214972.18 | 13-DEC-06:10 |
Annual Sum or Average | 0.234436E+14 | 0.758273E+12 | ||||
Minimum of Months | 0.135791E+13 | 975758.49 | 0.567215E+11 | 74017.72 | ||
Maximum of Months | 0.282939E+13 | 1599954.87 | 0.781240E+11 | 384402.50 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.318938E+11 | 59052.36 | 29-JAN-12:09 | 0.00 | 0.00 |
February | 0.331414E+11 | 69342.89 | 22-FEB-11:00 | 0.00 | 0.00 |
March | 0.453168E+11 | 78534.05 | 21-MAR-12:30 | 0.00 | 0.00 |
April | 0.633542E+11 | 88936.21 | 29-APR-11:39 | 0.00 | 0.00 |
May | 0.648777E+11 | 89495.83 | 27-MAY-11:39 | 0.00 | 0.00 |
June | 0.656517E+11 | 88962.51 | 13-JUN-11:50 | 0.00 | 0.00 |
July | 0.732037E+11 | 85998.43 | 02-JUL-11:00 | 0.00 | 0.00 |
August | 0.678157E+11 | 82289.80 | 01-AUG-12:09 | 0.00 | 0.00 |
September | 0.519688E+11 | 81778.31 | 02-SEP-11:00 | 0.00 | 0.00 |
October | 0.396094E+11 | 71300.47 | 03-OCT-11:39 | 0.00 | 0.00 |
November | 0.327837E+11 | 61658.83 | 02-NOV-11:30 | 0.00 | 0.00 |
December | 0.301372E+11 | 54794.46 | 02-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.599754E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.301372E+11 | 54794.46 | 0.00 | 0.00 | |
Maximum of Months | 0.732037E+11 | 89495.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.153663E+12 | 0.286141E+11 | 0.766053E+12 | 0.102198E+12 | 0.166115E+12 | 0.228808E+11 | 0.00 | 0.486221E+11 | 0.234387E+11 | 0.631489E+11 | 0.00 | 0.00 | 0.00 |
February | 0.138032E+12 | 0.235109E+11 | 0.978954E+12 | 0.923141E+11 | 0.151120E+12 | 0.185210E+11 | 0.00 | 0.454532E+11 | 0.202365E+11 | 0.546957E+11 | 0.00 | 0.00 | 0.00 |
March | 0.163134E+12 | 0.226451E+11 | 0.141687E+13 | 0.102366E+12 | 0.171279E+12 | 0.195413E+11 | 0.00 | 0.714085E+11 | 0.299473E+11 | 0.458850E+11 | 0.00 | 0.00 | 0.00 |
April | 0.144992E+12 | 0.187177E+11 | 0.165903E+13 | 0.988853E+11 | 0.178586E+12 | 0.255201E+11 | 0.00 | 0.171289E+12 | 0.693789E+11 | 0.159141E+11 | 0.00 | 0.00 | 0.00 |
May | 0.155917E+12 | 0.171901E+11 | 0.774844E+12 | 0.102281E+12 | 0.179682E+12 | 0.275954E+11 | 0.00 | 0.559654E+11 | 0.397721E+11 | 0.466045E+10 | 0.00 | 0.00 | 0.00 |
June | 0.154993E+12 | 0.158007E+11 | 0.106252E+13 | 0.990428E+11 | 0.186416E+12 | 0.331657E+11 | 0.00 | 0.118370E+12 | 0.672809E+11 | 0.287573E+09 | 0.00 | 0.00 | 0.00 |
July | 0.145239E+12 | 0.165213E+11 | 0.139340E+13 | 0.102123E+12 | 0.199741E+12 | 0.441518E+11 | 0.00 | 0.281018E+12 | 0.126074E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161903E+12 | 0.182604E+11 | 0.173200E+13 | 0.102366E+12 | 0.212039E+12 | 0.494798E+11 | 0.00 | 0.416162E+12 | 0.137180E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145494E+12 | 0.205015E+11 | 0.740713E+12 | 0.988846E+11 | 0.186420E+12 | 0.344055E+11 | 0.00 | 0.104157E+12 | 0.681444E+11 | 0.391586E+10 | 0.00 | 0.00 | 0.00 |
October | 0.151921E+12 | 0.246223E+11 | 0.108340E+13 | 0.102198E+12 | 0.185953E+12 | 0.372058E+11 | 0.00 | 0.165602E+12 | 0.851352E+11 | 0.578755E+11 | 0.00 | 0.00 | 0.00 |
November | 0.151703E+12 | 0.268384E+11 | 0.135889E+13 | 0.989495E+11 | 0.167868E+12 | 0.239468E+11 | 0.00 | 0.987340E+11 | 0.434416E+11 | 0.811380E+11 | 0.00 | 0.00 | 0.00 |
December | 0.149046E+12 | 0.294348E+11 | 0.170972E+13 | 0.102124E+12 | 0.168523E+12 | 0.237943E+11 | 0.00 | 0.152672E+12 | 0.557028E+11 | 0.148135E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181604E+13 | 0.262657E+12 | 0.146764E+14 | 0.120373E+13 | 0.215374E+13 | 0.360208E+12 | 0.00 | 0.172945E+13 | 0.765733E+12 | 0.475656E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138032E+12 | 0.158007E+11 | 0.740713E+12 | 0.923141E+11 | 0.151120E+12 | 0.185210E+11 | 0.00 | 0.454532E+11 | 0.202365E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163134E+12 | 0.294348E+11 | 0.173200E+13 | 0.102366E+12 | 0.212039E+12 | 0.494798E+11 | 0.00 | 0.416162E+12 | 0.137180E+12 | 0.148135E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.162335E+11 | 0.00 | 0.618905E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.453316E+10 | 0.00 | 0.561681E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.120055E+11 | 0.00 | 0.643174E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.602904E+09 | 0.00 | 0.587474E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 69116916.48 | 0.00 | 0.609824E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 703.34 | 0.00 | 0.590533E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.572574E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.606530E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.567215E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115784E+09 | 0.00 | 0.594132E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.127708E+10 | 0.00 | 0.590086E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.885611E+10 | 0.00 | 0.603668E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.436932E+11 | 0.00 | 0.714580E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.561681E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.162335E+11 | 0.00 | 0.643174E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 179838.04 | 02-JAN-16:49 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73695.62 | 31-JAN-08:20 | 128785.32 | 19-JAN-15:39 | 36854.28 | 18-JAN-13:39 | 0.00 | 01-JAN-00:10 |
February | 173654.74 | 27-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73693.80 | 10-FEB-08:20 | 133329.48 | 03-FEB-15:00 | 27715.95 | 01-FEB-12:09 | 0.00 | 01-FEB-00:10 |
March | 160844.95 | 16-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73695.98 | 16-MAR-07:19 | 156879.68 | 23-MAR-15:30 | 36041.88 | 23-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 158056.38 | 21-APR-15:00 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73694.18 | 05-APR-07:19 | 164502.37 | 26-APR-14:30 | 35885.43 | 12-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 157424.34 | 09-MAY-07:10 | 22480.63 | 01-MAY-18:30 | 423497.50 | 01-MAY-07:10 | 73694.18 | 09-MAY-07:19 | 144744.37 | 03-MAY-15:20 | 34005.50 | 04-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 156708.39 | 09-JUN-07:10 | 22480.63 | 01-JUN-18:49 | 541788.89 | 01-JUN-07:10 | 73693.81 | 09-JUN-07:19 | 152296.56 | 30-JUN-15:00 | 34687.53 | 27-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 155799.93 | 12-JUL-07:10 | 22480.63 | 01-JUL-18:00 | 660080.29 | 03-JUL-07:10 | 73693.33 | 12-JUL-07:19 | 171863.47 | 31-JUL-14:30 | 34855.55 | 28-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 157444.01 | 21-AUG-07:10 | 31088.59 | 08-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73694.19 | 21-AUG-07:19 | 172132.45 | 17-AUG-14:30 | 35278.41 | 07-AUG-10:30 | 0.00 | 01-AUG-00:10 |
September | 163677.65 | 18-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73697.47 | 18-SEP-07:19 | 163533.47 | 11-SEP-14:30 | 39710.13 | 29-SEP-10:39 | 0.00 | 01-SEP-00:10 |
October | 163746.20 | 24-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73697.50 | 24-OCT-07:19 | 172171.51 | 16-OCT-08:20 | 41094.79 | 16-OCT-14:50 | 0.00 | 01-OCT-00:10 |
November | 179838.04 | 06-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73694.01 | 24-NOV-08:39 | 134086.97 | 10-NOV-15:30 | 34087.45 | 28-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 179838.04 | 01-DEC-16:40 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73693.90 | 08-DEC-08:20 | 134037.14 | 05-DEC-15:00 | 34776.71 | 05-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 155799.93 | 22480.63 | 423497.50 | 73693.33 | 128785.32 | 27715.95 | 0.00 | |||||||
Maximum of Months | 179838.04 | 31088.59 | 778371.69 | 73697.50 | 172171.51 | 41094.79 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 189067.81 | 18-JAN-13:39 | 57082.37 | 13-JAN-13:50 | 100000.00 | 08-JAN-11:50 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 184619.25 | 01-FEB-11:50 | 57082.37 | 01-FEB-11:39 | 100000.00 | 01-FEB-08:20 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 228276.25 | 23-MAR-14:30 | 70388.50 | 22-MAR-12:39 | 100000.00 | 07-MAR-11:30 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 275964.05 | 26-APR-11:30 | 70388.50 | 11-APR-15:30 | 100000.00 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 150975.66 | 04-MAY-12:20 | 70388.50 | 04-MAY-12:20 | 100000.00 | 24-MAY-05:49 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 232463.65 | 29-JUN-12:00 | 70388.50 | 19-JUN-10:30 | 56064.09 | 12-JUN-09:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 337294.69 | 31-JUL-14:09 | 70388.50 | 12-JUL-12:30 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 363058.63 | 07-AUG-10:30 | 70388.50 | 02-AUG-09:50 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 243173.11 | 29-SEP-12:00 | 70388.50 | 05-SEP-12:39 | 100000.00 | 29-SEP-19:30 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 297353.52 | 16-OCT-10:00 | 70388.50 | 01-OCT-12:00 | 100000.00 | 13-OCT-04:30 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 247525.42 | 28-NOV-13:39 | 57082.37 | 10-NOV-12:20 | 100000.00 | 08-NOV-08:20 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 277643.81 | 05-DEC-14:00 | 57082.37 | 07-DEC-14:20 | 100000.00 | 04-DEC-04:19 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 150975.66 | 57082.37 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 363058.63 | 70388.50 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 993947.54 | 18-JAN-11:00 | 154688.45 | 423497.50 | 0.00 | 24462.73 | 90735.82 | 18770.76 | 0.00 | 135551.33 | 46240.96 |
February | 1159979.73 | 01-FEB-09:00 | 154688.45 | 541788.89 | 0.00 | 52594.17 | 104343.15 | 18340.07 | 0.00 | 142864.50 | 45360.50 |
March | 1341074.77 | 23-MAR-15:09 | 154688.45 | 660080.29 | 0.00 | 52594.17 | 147303.99 | 34731.54 | 0.00 | 221287.83 | 70388.50 |
April | 1503801.48 | 26-APR-15:30 | 154688.45 | 778371.69 | 0.00 | 52594.17 | 152261.07 | 34295.42 | 0.00 | 261202.19 | 70388.50 |
May | 975758.49 | 04-MAY-12:20 | 154688.45 | 423497.50 | 0.00 | 24462.73 | 132423.50 | 19322.14 | 0.00 | 150975.66 | 70388.50 |
June | 1201519.52 | 29-JUN-15:00 | 154688.45 | 541788.89 | 0.00 | 52594.17 | 151199.47 | 33874.27 | 0.00 | 196985.77 | 70388.50 |
July | 1464429.96 | 31-JUL-15:09 | 154688.45 | 660080.29 | 0.00 | 52594.17 | 169596.93 | 34627.30 | 0.00 | 322454.32 | 70388.50 |
August | 1599954.87 | 18-AUG-15:09 | 154688.45 | 778371.69 | 0.00 | 52594.17 | 169796.07 | 34713.95 | 0.00 | 339402.04 | 70388.50 |
September | 1114211.44 | 29-SEP-15:00 | 154688.45 | 423497.50 | 0.00 | 52594.17 | 156716.91 | 36482.02 | 0.00 | 219843.88 | 70388.50 |
October | 1308337.60 | 16-OCT-07:30 | 154749.70 | 541788.89 | 0.00 | 73693.19 | 143008.88 | 33325.67 | 0.00 | 216722.23 | 45049.05 |
November | 1361111.96 | 28-NOV-13:00 | 154688.45 | 660080.29 | 0.00 | 24462.73 | 96963.96 | 34087.45 | 0.00 | 245954.67 | 44874.41 |
December | 1534387.17 | 05-DEC-16:10 | 161976.34 | 778371.69 | 0.00 | 52595.54 | 131707.63 | 33139.43 | 0.00 | 232902.44 | 44302.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 975758.49 | 154688.45 | 423497.50 | 0.00 | 24462.73 | 90735.82 | 18340.07 | 0.00 | 135551.33 | 44302.62 | |
Maximum of Months | 1599954.87 | 161976.34 | 778371.69 | 0.00 | 73693.19 | 169796.07 | 36482.02 | 0.00 | 339402.04 | 70388.50 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 353777.37 | 03-JAN-07:10 | 0.00 | 78002.07 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 127897.01 | 09-FEB-07:10 | 0.00 | 78001.06 | 01-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 261735.78 | 30-MAR-05:10 | 0.00 | 77795.25 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 130151.01 | 01-APR-06:10 | 0.00 | 77066.51 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 23322.76 | 13-MAY-05:10 | 0.00 | 76090.70 | 03-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 1.17 | 30-JUN-14:00 | 0.00 | 74894.03 | 07-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 74075.81 | 11-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 74017.72 | 30-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 74736.59 | 26-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 27607.52 | 12-OCT-06:10 | 0.00 | 75889.76 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 78265.03 | 24-NOV-06:10 | 0.00 | 76951.50 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 189495.73 | 22-DEC-07:10 | 0.00 | 77588.70 | 27-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 74017.72 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 353777.37 | 0.00 | 78002.07 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.07 | 2.67 | 27.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.50 | 0.00 | 26.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.79 | 0.00 | 25.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.80 | 0.00 | 25.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.92 | 0.00 | 25.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.78 | 0.00 | 25.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.75 | 0.00 | 25.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.05 | 0.00 | 26.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.39 | 0.00 | 26.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.12 | 0.33 | 27.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.26 | 2.17 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.25 | 0.67 | 27.26 |
Annual Sum or Average | 0.00 | 0.00 | 53.17 | 26.68 | 5.83 | 26.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.75 | 0.00 | 25.75 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.26 | 2.67 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 25.59 | 0.00 | 25.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.46 | 0.50 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.51 | 1.50 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.66 | 3.17 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.64 | 2.33 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.71 | 3.00 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.80 | 5.33 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.78 | 3.67 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.33 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.72 | 2.33 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.67 | 27.70 | 24.67 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.80 | 5.33 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.79 | 4.67 | 27.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.78 | 4.50 | 27.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.61 | 2.50 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.36 | 1.83 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.32 | 1.17 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.48 | 4.67 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 26.17 | 21.67 | 26.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.86 | 6.50 | 27.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 26.27 | 16.17 | 26.27 |
Annual Sum or Average | 0.00 | 0.00 | 64.00 | 26.81 | 64.00 | 26.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.86 | 21.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.50 | 1.00 | 27.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.81 | 3.17 | 27.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.81 | 3.17 | 27.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.59 | 8.33 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.89 | 5.67 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.67 | 4.00 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.54 | 11.67 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.45 | 11.00 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.90 | 4.33 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.78 | 7.67 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.89 | 4.33 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.60 | 5.83 | 27.73 |
Annual Sum or Average | 0.00 | 0.00 | 107.83 | 27.63 | 70.17 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 1.00 | 27.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.90 | 11.67 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.68 | 2.17 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.62 | 2.00 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.75 | 2.83 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.85 | 5.83 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.82 | 4.17 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.79 | 1.83 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.72 | 2.17 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.00 | 27.76 | 22.00 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.85 | 5.83 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.31 | 9.00 | 26.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.84 | 4.33 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.58 | 2.00 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.33 | 7.00 | 26.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 26.08 | 26.67 | 26.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.18 | 12.67 | 26.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 25.67 | 26.67 | 25.67 |
Annual Sum or Average | 0.00 | 0.00 | 88.50 | 26.13 | 88.33 | 26.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.84 | 26.67 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 0.83 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.96 | 3.50 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.76 | 4.17 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.83 | 2.83 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.98 | 6.00 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.13 | 3.67 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.93 | 3.17 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.86 | 4.50 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 38.50 | 27.91 | 29.33 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.13 | 6.00 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.18 | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
February | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.67 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 2.83 | 19.25 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.60 | 1.17 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.49 | 1.17 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.68 | 2.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.75 | 6.50 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.72 | 4.17 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.67 | 1.33 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.71 | 2.17 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Annual Sum or Average | 1.33 | 19.14 | 0.00 | 19.14 | 18.83 | 27.13 | 18.83 | 27.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.28 | 0.00 | 19.28 | 6.50 | 27.75 | 6.50 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.27 | 0.00 | 19.27 | 2.83 | 26.46 | 2.83 | 27.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.60 | 3.00 | 27.60 |
March | 0.33 | 19.28 | 0.00 | 19.28 | 1.50 | 25.96 | 1.50 | 26.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.32 | 4.83 | 26.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 26.25 | 19.33 | 26.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.90 | 4.33 | 27.90 |
December | 0.17 | 19.44 | 0.00 | 19.44 | 6.17 | 27.11 | 6.17 | 27.21 |
Annual Sum or Average | 1.00 | 19.30 | 0.00 | 19.30 | 42.67 | 26.65 | 42.33 | 26.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.44 | 0.00 | 19.44 | 19.67 | 27.90 | 19.33 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.43 | 0.00 | 19.43 | 0.67 | 26.06 | 0.67 | 26.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.91 | 3.50 | 27.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.73 | 4.17 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.90 | 3.00 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.06 | 6.33 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.11 | 4.33 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.91 | 3.00 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.86 | 4.33 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.32 | 0.00 | 19.32 | 38.83 | 27.80 | 29.33 | 27.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.43 | 0.00 | 19.43 | 9.83 | 28.11 | 6.33 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.88 | 1.00 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.70 | 1.67 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 213.33 | 28.72 | 209.33 | 28.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.95 | 3.50 | 27.95 |
Annual Sum or Average | 0.00 | 0.00 | 219.50 | 28.69 | 215.50 | 28.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 213.33 | 28.72 | 209.33 | 28.72 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.83 | 24.00 | 203.83 | 25.01 | 0.00 | 25.01 |
February | 34.83 | 24.00 | 193.83 | 24.89 | 0.00 | 24.89 |
March | 0.00 | 0.00 | 265.50 | 24.71 | 0.00 | 24.71 |
April | 5.33 | 24.00 | 353.17 | 24.62 | 0.00 | 24.62 |
May | 2.67 | 24.00 | 340.00 | 24.63 | 0.00 | 24.63 |
June | 20.67 | 24.00 | 460.83 | 24.40 | 20.67 | 24.38 |
July | 162.50 | 24.69 | 497.00 | 24.57 | 162.50 | 24.59 |
August | 156.17 | 24.76 | 514.00 | 24.50 | 156.17 | 24.55 |
September | 67.17 | 24.64 | 440.83 | 24.55 | 67.17 | 24.56 |
October | 47.50 | 24.34 | 318.67 | 24.80 | 35.00 | 24.77 |
November | 39.17 | 24.26 | 254.17 | 24.92 | 3.00 | 24.95 |
December | 57.50 | 24.00 | 179.50 | 25.09 | 0.00 | 25.09 |
Annual Sum or Average | 640.33 | 24.47 | 4021.33 | 24.66 | 444.50 | 24.66 |
Minimum of Months | 0.00 | 0.00 | 179.50 | 24.40 | 0.00 | 24.38 |
Maximum of Months | 162.50 | 24.76 | 514.00 | 25.09 | 162.50 | 25.09 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.83 | 23.96 | 199.33 | 24.65 | 0.00 | 24.65 |
February | 33.17 | 24.00 | 215.33 | 24.51 | 0.00 | 24.51 |
March | 0.33 | 23.78 | 309.83 | 24.45 | 0.00 | 24.45 |
April | 4.50 | 24.00 | 409.50 | 24.33 | 0.00 | 24.33 |
May | 0.67 | 23.92 | 345.50 | 24.36 | 0.00 | 24.36 |
June | 0.00 | 0.00 | 474.17 | 24.27 | 0.00 | 24.27 |
July | 0.00 | 0.00 | 497.00 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 0.00 | 0.00 | 446.00 | 24.31 | 0.00 | 24.31 |
October | 3.67 | 24.00 | 328.17 | 24.50 | 0.00 | 24.50 |
November | 26.83 | 24.00 | 271.17 | 24.55 | 0.00 | 24.55 |
December | 34.00 | 24.00 | 196.67 | 24.74 | 0.00 | 24.74 |
Annual Sum or Average | 150.00 | 23.99 | 4206.67 | 24.39 | 0.00 | 24.39 |
Minimum of Months | 0.00 | 0.00 | 196.67 | 24.22 | 0.00 | 24.22 |
Maximum of Months | 46.83 | 24.00 | 514.00 | 24.74 | 0.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 217.83 | 23.62 | 84.00 | 23.79 | 13.17 | 23.78 |
February | 159.50 | 23.60 | 79.67 | 23.83 | 0.00 | 23.83 |
March | 127.67 | 23.54 | 142.33 | 23.93 | 0.00 | 23.93 |
April | 50.67 | 23.47 | 216.50 | 24.12 | 0.00 | 24.12 |
May | 41.50 | 23.58 | 243.00 | 24.19 | 0.00 | 24.19 |
June | 1.50 | 23.48 | 393.83 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 488.00 | 24.16 | 0.00 | 24.16 |
August | 0.00 | 0.00 | 511.33 | 24.14 | 0.00 | 24.14 |
September | 4.83 | 24.03 | 403.83 | 24.20 | 1.17 | 24.20 |
October | 59.17 | 23.79 | 254.17 | 24.23 | 0.00 | 24.23 |
November | 147.33 | 23.73 | 145.67 | 24.07 | 0.00 | 24.07 |
December | 249.33 | 23.69 | 57.50 | 23.83 | 0.00 | 23.83 |
Annual Sum or Average | 1059.33 | 23.64 | 3019.83 | 24.08 | 14.33 | 24.08 |
Minimum of Months | 0.00 | 0.00 | 57.50 | 23.79 | 0.00 | 23.78 |
Maximum of Months | 249.33 | 24.03 | 511.33 | 24.23 | 13.17 | 24.23 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.50 | 22.67 | 34.33 | 22.65 | 13.50 | 22.57 |
February | 347.33 | 22.81 | 20.50 | 22.87 | 0.00 | 22.87 |
March | 352.83 | 22.99 | 65.33 | 23.15 | 0.00 | 23.15 |
April | 172.17 | 23.10 | 152.00 | 23.56 | 0.00 | 23.56 |
May | 164.00 | 23.19 | 174.00 | 23.67 | 0.00 | 23.67 |
June | 41.33 | 23.32 | 331.33 | 24.05 | 0.00 | 24.05 |
July | 2.50 | 23.39 | 463.67 | 24.15 | 0.00 | 24.15 |
August | 3.17 | 23.45 | 482.17 | 24.10 | 0.00 | 24.10 |
September | 55.00 | 23.37 | 323.17 | 24.01 | 1.83 | 24.01 |
October | 187.00 | 23.40 | 186.50 | 23.79 | 0.00 | 23.79 |
November | 325.67 | 23.10 | 54.83 | 23.25 | 9.00 | 23.27 |
December | 427.00 | 22.85 | 11.83 | 22.87 | 2.00 | 22.86 |
Annual Sum or Average | 2476.50 | 22.97 | 2299.67 | 23.51 | 26.33 | 23.50 |
Minimum of Months | 2.50 | 22.67 | 11.83 | 22.65 | 0.00 | 22.57 |
Maximum of Months | 427.00 | 23.45 | 482.17 | 24.15 | 13.50 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 338.83 | 23.21 | 33.17 | 23.32 | 0.00 | 23.32 |
February | 272.50 | 23.35 | 36.00 | 23.43 | 0.00 | 23.43 |
March | 223.67 | 23.28 | 109.33 | 23.57 | 0.00 | 23.57 |
April | 81.50 | 23.55 | 214.67 | 24.02 | 0.00 | 24.02 |
May | 96.50 | 23.51 | 217.17 | 24.00 | 0.00 | 24.00 |
June | 3.33 | 23.46 | 417.83 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 490.00 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 506.33 | 24.18 | 0.00 | 24.18 |
September | 27.67 | 23.47 | 352.00 | 24.15 | 0.00 | 24.15 |
October | 107.83 | 23.68 | 239.00 | 24.14 | 0.00 | 24.14 |
November | 251.83 | 23.59 | 81.00 | 23.78 | 0.00 | 23.78 |
December | 342.00 | 23.57 | 21.50 | 23.61 | 0.00 | 23.61 |
Annual Sum or Average | 1745.67 | 23.43 | 2718.00 | 23.92 | 0.00 | 23.92 |
Minimum of Months | 0.00 | 0.00 | 21.50 | 23.32 | 0.00 | 23.32 |
Maximum of Months | 342.00 | 23.68 | 506.33 | 24.29 | 0.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 241.00 | 23.28 | 92.33 | 23.67 | 0.00 | 23.67 |
February | 222.50 | 23.25 | 93.50 | 23.61 | 0.50 | 23.62 |
March | 203.33 | 23.25 | 174.33 | 23.76 | 3.67 | 23.79 |
April | 93.67 | 23.71 | 288.17 | 24.21 | 8.00 | 24.27 |
May | 82.50 | 23.85 | 291.83 | 24.31 | 9.67 | 24.38 |
June | 31.67 | 24.86 | 401.67 | 24.35 | 12.83 | 24.42 |
July | 27.50 | 26.89 | 478.50 | 24.54 | 27.50 | 24.66 |
August | 20.83 | 26.75 | 489.67 | 24.36 | 20.17 | 24.46 |
September | 32.50 | 24.59 | 397.67 | 24.33 | 10.83 | 24.39 |
October | 75.00 | 23.89 | 289.50 | 24.36 | 6.83 | 24.41 |
November | 198.00 | 23.50 | 131.00 | 23.89 | 0.50 | 23.90 |
December | 254.50 | 23.41 | 50.33 | 23.65 | 0.00 | 23.65 |
Annual Sum or Average | 1483.00 | 23.59 | 3178.50 | 24.13 | 100.50 | 24.19 |
Minimum of Months | 20.83 | 23.25 | 50.33 | 23.61 | 0.00 | 23.62 |
Maximum of Months | 254.50 | 26.89 | 489.67 | 24.54 | 27.50 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 156.83 | 23.58 | 227.17 | 24.15 | 12.33 | 24.25 |
February | 176.00 | 23.50 | 162.67 | 24.01 | 13.17 | 24.12 |
March | 187.00 | 23.36 | 204.67 | 23.87 | 9.50 | 23.94 |
April | 81.50 | 23.57 | 285.83 | 24.21 | 4.33 | 24.24 |
May | 133.83 | 23.33 | 212.67 | 23.90 | 0.00 | 23.90 |
June | 28.50 | 23.45 | 370.67 | 24.14 | 0.00 | 24.14 |
July | 4.17 | 26.72 | 479.83 | 24.32 | 4.17 | 24.34 |
August | 15.83 | 26.71 | 505.33 | 24.32 | 15.83 | 24.39 |
September | 38.00 | 25.53 | 414.83 | 24.48 | 23.33 | 24.60 |
October | 73.83 | 25.30 | 360.67 | 24.73 | 38.00 | 24.91 |
November | 112.00 | 24.28 | 279.00 | 24.49 | 20.00 | 24.62 |
December | 141.33 | 24.18 | 241.00 | 24.52 | 24.33 | 24.68 |
Annual Sum or Average | 1148.83 | 23.87 | 3744.33 | 24.28 | 165.00 | 24.37 |
Minimum of Months | 4.17 | 23.33 | 162.67 | 23.87 | 0.00 | 23.90 |
Maximum of Months | 187.00 | 26.72 | 505.33 | 24.73 | 38.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 111.00 | 23.70 | 196.17 | 24.25 | 0.83 | 24.26 |
February | 44.50 | 24.69 | 255.50 | 24.59 | 11.17 | 24.68 |
March | 22.50 | 25.62 | 377.67 | 24.57 | 12.50 | 24.65 |
April | 37.67 | 26.94 | 474.50 | 24.79 | 36.00 | 24.94 |
May | 28.50 | 26.60 | 412.00 | 24.64 | 25.17 | 24.77 |
June | 25.17 | 26.99 | 494.33 | 24.61 | 25.17 | 24.72 |
July | 74.67 | 26.98 | 497.00 | 24.98 | 74.67 | 25.21 |
August | 63.00 | 26.98 | 514.00 | 24.81 | 63.00 | 25.02 |
September | 26.00 | 26.93 | 468.00 | 24.63 | 26.00 | 24.74 |
October | 37.67 | 26.48 | 397.83 | 24.86 | 31.00 | 25.01 |
November | 34.17 | 25.68 | 329.17 | 24.82 | 19.00 | 24.93 |
December | 33.00 | 25.65 | 298.17 | 24.98 | 17.83 | 25.08 |
Annual Sum or Average | 537.83 | 25.83 | 4714.33 | 24.73 | 342.33 | 24.87 |
Minimum of Months | 22.50 | 23.70 | 196.17 | 24.25 | 0.83 | 24.26 |
Maximum of Months | 111.00 | 26.99 | 514.00 | 24.98 | 74.67 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 460.00 | 22.21 | 22.67 | 22.17 | 17.33 | 22.12 |
February | 413.83 | 22.39 | 7.33 | 22.38 | 5.00 | 22.37 |
March | 440.33 | 22.48 | 28.67 | 22.57 | 1.67 | 22.56 |
April | 298.50 | 22.89 | 75.17 | 23.12 | 0.00 | 23.12 |
May | 233.33 | 23.12 | 106.67 | 23.42 | 0.00 | 23.42 |
June | 85.83 | 23.33 | 298.67 | 23.92 | 0.00 | 23.92 |
July | 22.67 | 23.31 | 419.17 | 24.10 | 0.00 | 24.10 |
August | 46.83 | 23.21 | 382.67 | 23.97 | 0.00 | 23.97 |
September | 143.33 | 23.16 | 223.67 | 23.70 | 0.00 | 23.70 |
October | 251.00 | 23.13 | 127.00 | 23.50 | 0.00 | 23.50 |
November | 415.33 | 22.62 | 11.50 | 22.62 | 4.83 | 22.60 |
December | 486.83 | 22.35 | 13.83 | 22.31 | 13.83 | 22.27 |
Annual Sum or Average | 3297.83 | 22.63 | 1717.00 | 23.10 | 42.67 | 23.08 |
Minimum of Months | 22.67 | 22.21 | 7.33 | 22.17 | 0.00 | 22.12 |
Maximum of Months | 486.83 | 23.33 | 419.17 | 24.10 | 17.33 | 24.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.17 | 22.77 | 35.50 | 22.87 | 5.33 | 22.83 |
February | 276.00 | 22.64 | 37.17 | 22.86 | 0.67 | 22.85 |
March | 263.33 | 22.66 | 90.17 | 23.09 | 3.33 | 23.10 |
April | 152.33 | 23.22 | 188.83 | 23.94 | 6.67 | 24.00 |
May | 143.17 | 23.44 | 197.17 | 24.10 | 8.00 | 24.17 |
June | 70.33 | 24.07 | 285.67 | 24.31 | 14.67 | 24.41 |
July | 46.67 | 26.03 | 383.17 | 24.67 | 35.33 | 24.84 |
August | 36.17 | 25.84 | 384.67 | 24.48 | 25.83 | 24.62 |
September | 80.67 | 23.66 | 266.33 | 24.18 | 9.83 | 24.25 |
October | 119.67 | 23.40 | 196.00 | 24.12 | 5.00 | 24.17 |
November | 266.83 | 23.00 | 56.33 | 23.25 | 0.83 | 23.25 |
December | 340.00 | 22.92 | 12.33 | 22.94 | 3.33 | 22.92 |
Annual Sum or Average | 2109.33 | 23.11 | 2133.33 | 23.77 | 118.83 | 23.84 |
Minimum of Months | 36.17 | 22.64 | 12.33 | 22.86 | 0.67 | 22.83 |
Maximum of Months | 340.00 | 26.03 | 384.67 | 24.67 | 35.33 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 200.50 | 23.24 | 214.17 | 23.92 | 15.00 | 24.03 |
February | 230.33 | 22.99 | 146.33 | 23.61 | 14.33 | 23.74 |
March | 263.00 | 22.79 | 161.50 | 23.36 | 9.33 | 23.43 |
April | 178.00 | 23.03 | 209.00 | 23.75 | 1.33 | 23.76 |
May | 217.00 | 23.06 | 164.50 | 23.56 | 0.00 | 23.56 |
June | 114.67 | 23.27 | 274.33 | 23.86 | 0.00 | 23.86 |
July | 30.83 | 23.59 | 402.00 | 24.16 | 2.50 | 24.18 |
August | 26.33 | 24.31 | 441.50 | 24.21 | 8.17 | 24.25 |
September | 72.33 | 24.37 | 374.67 | 24.37 | 22.50 | 24.49 |
October | 123.83 | 24.52 | 330.50 | 24.60 | 41.00 | 24.79 |
November | 178.83 | 23.66 | 237.50 | 24.21 | 19.50 | 24.34 |
December | 206.67 | 23.56 | 216.00 | 24.20 | 23.33 | 24.36 |
Annual Sum or Average | 1842.33 | 23.33 | 3172.00 | 24.00 | 157.00 | 24.09 |
Minimum of Months | 26.33 | 22.79 | 146.33 | 23.36 | 0.00 | 23.43 |
Maximum of Months | 263.00 | 24.52 | 441.50 | 24.60 | 41.00 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 344.00 | 22.70 | 68.83 | 22.94 | 2.33 | 22.92 |
February | 296.00 | 22.83 | 80.17 | 23.16 | 0.33 | 23.17 |
March | 290.00 | 22.88 | 124.83 | 23.29 | 2.33 | 23.31 |
April | 128.00 | 23.62 | 249.67 | 24.15 | 18.17 | 24.28 |
May | 129.00 | 23.78 | 268.50 | 24.21 | 18.67 | 24.33 |
June | 37.83 | 24.84 | 410.83 | 24.34 | 16.17 | 24.43 |
July | 32.33 | 26.95 | 488.33 | 24.58 | 32.33 | 24.72 |
August | 21.83 | 26.81 | 502.67 | 24.40 | 21.00 | 24.50 |
September | 43.00 | 24.82 | 390.00 | 24.40 | 17.17 | 24.50 |
October | 140.33 | 23.90 | 274.83 | 24.28 | 19.17 | 24.40 |
November | 269.67 | 23.12 | 118.50 | 23.50 | 0.83 | 23.51 |
December | 344.83 | 22.94 | 55.67 | 23.16 | 0.00 | 23.16 |
Annual Sum or Average | 2076.83 | 23.23 | 3032.83 | 23.90 | 148.50 | 23.99 |
Minimum of Months | 21.83 | 22.70 | 55.67 | 22.94 | 0.00 | 22.92 |
Maximum of Months | 344.83 | 26.95 | 502.67 | 24.58 | 32.33 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.67 | 21.52 | 108.17 | 21.26 | 108.17 | 21.09 |
February | 435.00 | 21.70 | 53.67 | 21.54 | 53.17 | 21.42 |
March | 469.00 | 21.89 | 59.67 | 21.85 | 41.50 | 21.74 |
April | 335.33 | 22.47 | 78.67 | 22.70 | 6.67 | 22.67 |
May | 288.83 | 22.67 | 95.83 | 22.99 | 1.50 | 22.98 |
June | 141.50 | 23.10 | 255.00 | 23.72 | 0.00 | 23.72 |
July | 54.17 | 23.19 | 378.67 | 24.03 | 1.83 | 24.04 |
August | 107.50 | 23.12 | 342.17 | 23.84 | 0.50 | 23.84 |
September | 216.67 | 22.89 | 195.33 | 23.43 | 0.50 | 23.43 |
October | 297.50 | 22.68 | 118.83 | 23.09 | 3.17 | 23.07 |
November | 474.67 | 22.07 | 49.33 | 21.95 | 43.83 | 21.83 |
December | 494.17 | 21.57 | 109.67 | 21.34 | 109.67 | 21.18 |
Annual Sum or Average | 3797.00 | 22.13 | 1845.00 | 22.52 | 370.50 | 22.38 |
Minimum of Months | 54.17 | 21.52 | 49.33 | 21.26 | 0.00 | 21.09 |
Maximum of Months | 494.17 | 23.19 | 378.67 | 24.03 | 109.67 | 24.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 425.50 | 22.30 | 69.17 | 22.19 | 47.00 | 22.02 |
February | 352.50 | 22.11 | 50.83 | 22.15 | 21.67 | 22.05 |
March | 332.50 | 22.13 | 100.50 | 22.49 | 15.67 | 22.41 |
April | 189.00 | 22.74 | 234.83 | 23.62 | 6.00 | 23.64 |
May | 177.67 | 22.90 | 221.83 | 23.73 | 3.67 | 23.76 |
June | 106.50 | 23.61 | 326.67 | 24.11 | 14.67 | 24.20 |
July | 67.00 | 25.49 | 434.17 | 24.57 | 43.50 | 24.75 |
August | 67.33 | 24.94 | 437.17 | 24.38 | 33.17 | 24.53 |
September | 127.00 | 23.18 | 296.83 | 23.93 | 8.17 | 23.98 |
October | 172.50 | 23.02 | 196.67 | 23.75 | 4.67 | 23.79 |
November | 363.67 | 22.62 | 42.83 | 22.69 | 11.33 | 22.63 |
December | 470.50 | 22.49 | 34.50 | 22.37 | 30.67 | 22.25 |
Annual Sum or Average | 2851.67 | 22.67 | 2446.00 | 23.34 | 240.17 | 23.34 |
Minimum of Months | 67.00 | 22.11 | 34.50 | 22.15 | 3.67 | 22.02 |
Maximum of Months | 470.50 | 25.49 | 437.17 | 24.57 | 47.00 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.00 | 22.49 | 188.67 | 23.10 | 33.33 | 23.02 |
February | 271.33 | 22.26 | 127.17 | 22.84 | 22.00 | 22.84 |
March | 329.33 | 22.29 | 146.00 | 22.71 | 30.33 | 22.66 |
April | 220.83 | 22.58 | 198.67 | 23.38 | 6.50 | 23.36 |
May | 259.50 | 22.61 | 144.17 | 23.14 | 2.17 | 23.12 |
June | 163.00 | 23.00 | 245.67 | 23.65 | 0.00 | 23.65 |
July | 72.67 | 23.38 | 365.83 | 24.09 | 6.00 | 24.11 |
August | 77.67 | 23.74 | 402.67 | 24.13 | 14.17 | 24.20 |
September | 122.50 | 23.64 | 330.50 | 24.16 | 21.00 | 24.27 |
October | 161.17 | 23.81 | 295.33 | 24.31 | 35.33 | 24.51 |
November | 230.67 | 22.90 | 201.00 | 23.61 | 19.00 | 23.64 |
December | 254.00 | 22.73 | 189.17 | 23.35 | 30.67 | 23.31 |
Annual Sum or Average | 2417.67 | 22.77 | 2834.83 | 23.55 | 220.50 | 23.57 |
Minimum of Months | 72.67 | 22.26 | 127.17 | 22.71 | 0.00 | 22.66 |
Maximum of Months | 329.33 | 23.81 | 402.67 | 24.31 | 35.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.00 | 22.12 | 97.83 | 22.14 | 49.50 | 21.97 |
February | 334.00 | 22.18 | 79.33 | 22.43 | 16.00 | 22.35 |
March | 347.00 | 22.35 | 118.17 | 22.70 | 19.00 | 22.64 |
April | 184.83 | 23.13 | 216.67 | 23.81 | 19.50 | 23.93 |
May | 187.17 | 23.26 | 228.33 | 23.88 | 18.50 | 24.01 |
June | 78.33 | 23.96 | 371.50 | 24.21 | 16.83 | 24.31 |
July | 44.83 | 26.14 | 465.83 | 24.57 | 35.33 | 24.72 |
August | 35.67 | 25.52 | 472.33 | 24.36 | 22.00 | 24.47 |
September | 93.17 | 23.83 | 343.50 | 24.22 | 18.00 | 24.33 |
October | 189.00 | 23.36 | 246.17 | 23.98 | 17.33 | 24.09 |
November | 332.17 | 22.56 | 104.33 | 22.85 | 16.33 | 22.77 |
December | 392.33 | 22.32 | 73.17 | 22.32 | 38.33 | 22.18 |
Annual Sum or Average | 2609.50 | 22.72 | 2817.17 | 23.46 | 286.67 | 23.48 |
Minimum of Months | 35.67 | 22.12 | 73.17 | 22.14 | 16.00 | 21.97 |
Maximum of Months | 392.33 | 26.14 | 472.33 | 24.57 | 49.50 | 24.72 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 8.67 | 27.00 | 454.00 | 27.00 | 8.67 | 27.00 |
March | 27.33 | 27.00 | 514.00 | 27.00 | 27.33 | 27.00 |
April | 151.00 | 27.00 | 485.00 | 27.00 | 151.00 | 27.00 |
May | 0.17 | 27.00 | 508.00 | 27.00 | 0.17 | 27.00 |
June | 9.67 | 27.00 | 496.00 | 27.00 | 9.67 | 27.00 |
July | 135.33 | 27.00 | 497.00 | 27.00 | 135.33 | 27.00 |
August | 283.50 | 27.00 | 514.00 | 27.00 | 283.50 | 27.00 |
September | 5.33 | 27.00 | 485.00 | 27.00 | 5.33 | 27.00 |
October | 24.00 | 27.00 | 502.00 | 27.00 | 24.00 | 27.00 |
November | 39.50 | 27.00 | 489.00 | 27.00 | 39.50 | 27.00 |
December | 57.00 | 27.01 | 497.00 | 27.01 | 57.00 | 27.01 |
Annual Sum or Average | 741.50 | 27.00 | 5943.00 | 27.00 | 741.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 283.50 | 27.01 | 514.00 | 27.01 | 283.50 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 2.67 | 27.00 | 485.00 | 27.00 | 2.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 0.33 | 27.00 | 497.00 | 27.00 | 0.33 | 27.00 |
August | 7.33 | 27.00 | 514.00 | 27.00 | 7.33 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.50 | 27.00 | 502.00 | 27.00 | 0.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 10.83 | 27.00 | 5943.00 | 27.00 | 10.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 7.33 | 27.00 | 514.00 | 27.00 | 7.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 25.51 | 478.33 | 26.98 | 0.00 | 26.98 |
February | 0.00 | 0.00 | 447.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 7.33 | 27.00 | 485.00 | 27.00 | 7.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.17 | 27.00 | 496.00 | 27.00 | 0.17 | 27.00 |
July | 15.00 | 27.00 | 497.00 | 27.00 | 15.00 | 27.00 |
August | 46.00 | 27.00 | 514.00 | 27.00 | 46.00 | 27.00 |
September | 0.50 | 27.00 | 485.00 | 27.00 | 0.50 | 27.00 |
October | 4.50 | 27.00 | 502.00 | 27.00 | 4.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 77.83 | 26.92 | 5912.33 | 27.00 | 73.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 447.00 | 26.98 | 0.00 | 26.98 |
Maximum of Months | 46.00 | 27.00 | 514.00 | 27.00 | 46.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.17 | 27.00 | 502.00 | 27.00 | 463.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 478.83 | 27.00 | 508.00 | 27.00 | 478.83 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.02 | 497.00 | 27.02 | 497.00 | 27.02 |
August | 514.00 | 27.74 | 514.00 | 27.74 | 514.00 | 27.74 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5875.00 | 27.07 | 5943.00 | 27.07 | 5875.00 | 27.07 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.74 | 514.00 | 27.74 | 514.00 | 27.74 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00027 | 32.18921 | 0.87615 | 21.27342 |
February | 454.00000 | 27.00034 | 32.94694 | 0.91855 | 22.88426 |
March | 514.00000 | 27.00028 | 34.36492 | 0.96503 | 24.70701 |
April | 485.00000 | 27.00014 | 35.21584 | 1.02186 | 27.08462 |
May | 508.00000 | 27.00062 | 36.39155 | 0.25038 | 6.35611 |
June | 496.00000 | 27.00085 | 36.81613 | 0.31798 | 7.14682 |
July | 497.00000 | 27.00070 | 37.30565 | 0.38187 | 8.08266 |
August | 514.00000 | 27.00022 | 37.34727 | 0.42368 | 8.79335 |
September | 485.00000 | 27.00094 | 37.73354 | 0.27774 | 6.66098 |
October | 502.00000 | 27.00054 | 34.14748 | 0.95349 | 24.25237 |
November | 489.00000 | 27.00022 | 31.94422 | 0.95659 | 24.40317 |
December | 497.00000 | 27.00796 | 29.53591 | 0.96451 | 24.72517 |
Annual Sum or Average | 5943.00000 | 27.00109 | 34.67746 | 0.69013 | 17.13639 |
Minimum of Months | 454.00000 | 27.00014 | 29.53591 | 0.25038 | 6.35611 |
Maximum of Months | 514.00000 | 27.00796 | 37.73354 | 1.02186 | 27.08462 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00025 | 32.25837 | 0.80076 | 18.63503 |
February | 454.00000 | 27.00032 | 32.97605 | 0.82893 | 19.59033 |
March | 514.00000 | 27.00027 | 34.35731 | 0.86009 | 20.68343 |
April | 485.00000 | 27.00014 | 35.20130 | 0.91277 | 22.66319 |
May | 508.00000 | 27.00058 | 36.48956 | 0.17939 | 5.75097 |
June | 496.00000 | 27.00083 | 36.86288 | 0.22865 | 6.15092 |
July | 497.00000 | 27.00068 | 37.33355 | 0.27210 | 6.59671 |
August | 514.00000 | 27.00021 | 37.36100 | 0.29179 | 6.83304 |
September | 485.00000 | 27.00072 | 37.90182 | 0.21162 | 6.00657 |
October | 502.00000 | 27.00052 | 34.17865 | 0.88393 | 21.55879 |
November | 489.00000 | 27.00022 | 31.93168 | 0.85119 | 20.39082 |
December | 497.00000 | 27.00303 | 29.52027 | 0.83160 | 19.68374 |
Annual Sum or Average | 5943.00000 | 27.00065 | 34.71351 | 0.59377 | 14.49175 |
Minimum of Months | 454.00000 | 27.00014 | 29.52027 | 0.17939 | 5.75097 |
Maximum of Months | 514.00000 | 27.00303 | 37.90182 | 0.91277 | 22.66319 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.96325 | 32.68823 | 0.73739 | 16.74080 |
February | 454.00000 | 27.00032 | 33.02738 | 0.77524 | 17.85456 |
March | 514.00000 | 27.00028 | 34.38050 | 0.81507 | 19.17410 |
April | 485.00000 | 27.00016 | 35.21149 | 0.89111 | 21.91494 |
May | 508.00000 | 27.00058 | 36.53427 | 0.15171 | 5.69201 |
June | 496.00000 | 27.00085 | 36.86565 | 0.22005 | 6.16047 |
July | 497.00000 | 27.00071 | 37.33108 | 0.27606 | 6.71550 |
August | 514.00000 | 27.00024 | 37.36361 | 0.29160 | 6.90687 |
September | 485.00000 | 27.00074 | 37.94028 | 0.19418 | 5.94991 |
October | 502.00000 | 27.00053 | 34.19206 | 0.86184 | 20.80126 |
November | 489.00000 | 27.00022 | 31.95194 | 0.80310 | 18.78293 |
December | 497.00000 | 27.00041 | 29.52962 | 0.76957 | 17.65049 |
Annual Sum or Average | 5943.00000 | 26.99732 | 34.76737 | 0.56345 | 13.64867 |
Minimum of Months | 454.00000 | 26.96325 | 29.52962 | 0.15171 | 5.69201 |
Maximum of Months | 514.00000 | 27.00085 | 37.94028 | 0.89111 | 21.91494 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99993 | 32.20811 | 1.07136 | 29.25697 |
February | 454.00000 | 26.99993 | 32.71262 | 1.21792 | 36.17223 |
March | 514.00000 | 27.00299 | 34.32756 | 1.37531 | 44.21342 |
April | 485.00000 | 27.01465 | 34.15629 | 1.51541 | 51.74190 |
May | 508.00000 | 26.99983 | 36.77404 | 0.49487 | 10.18882 |
June | 496.00000 | 27.00264 | 41.72819 | 0.76002 | 17.20473 |
July | 497.00000 | 27.01792 | 43.58725 | 0.99725 | 26.03071 |
August | 514.00000 | 27.74300 | 39.16050 | 1.35439 | 43.36447 |
September | 485.00000 | 27.00008 | 44.70539 | 0.59528 | 12.50809 |
October | 502.00000 | 27.00171 | 37.50057 | 1.28656 | 39.65319 |
November | 489.00000 | 27.00318 | 31.23019 | 1.37324 | 44.13347 |
December | 497.00000 | 27.01493 | 27.27396 | 1.46957 | 49.26483 |
Annual Sum or Average | 5943.00000 | 27.06907 | 36.30053 | 1.12557 | 33.63688 |
Minimum of Months | 454.00000 | 26.99983 | 27.27396 | 0.49487 | 10.18882 |
Maximum of Months | 514.00000 | 27.74300 | 44.70539 | 1.51541 | 51.74190 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.51896 | 35.36692 | 0.45346 | 9.95631 |
February | 454.00000 | 24.45992 | 38.16640 | 0.45393 | 9.87781 |
March | 514.00000 | 24.37599 | 40.82686 | 0.45721 | 9.74823 |
April | 485.00000 | 24.46427 | 44.49555 | 0.50491 | 10.74061 |
May | 508.00000 | 24.42559 | 43.97792 | -0.3805 | 8.75336 |
June | 496.00000 | 24.38923 | 50.85963 | -0.3362 | 8.00013 |
July | 497.00000 | 24.53571 | 57.73534 | -0.2335 | 7.14006 |
August | 514.00000 | 24.41708 | 59.20510 | -0.2533 | 7.13760 |
September | 485.00000 | 24.48655 | 52.73087 | -0.2859 | 7.72863 |
October | 502.00000 | 24.55488 | 42.18917 | 0.51851 | 11.39251 |
November | 489.00000 | 24.55631 | 36.19542 | 0.47651 | 10.52949 |
December | 497.00000 | 24.54900 | 31.43955 | 0.43972 | 9.86572 |
Annual Sum or Average | 5943.00000 | 24.47738 | 44.49244 | 0.14816 | 9.23003 |
Minimum of Months | 454.00000 | 24.37599 | 31.43955 | -0.3805 | 7.13760 |
Maximum of Months | 514.00000 | 24.55631 | 59.20510 | 0.51851 | 11.39251 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33865 | 37.18180 | 0.42664 | 9.22811 |
February | 454.00000 | 24.29468 | 39.38381 | 0.43717 | 9.28424 |
March | 514.00000 | 24.27804 | 42.21768 | 0.46144 | 9.70780 |
April | 485.00000 | 24.28906 | 45.52338 | 0.50035 | 10.44970 |
May | 508.00000 | 24.24354 | 45.50851 | -0.4060 | 8.76724 |
June | 496.00000 | 24.26241 | 51.61479 | -0.3395 | 7.76043 |
July | 497.00000 | 24.28276 | 55.44588 | -0.2925 | 7.07220 |
August | 514.00000 | 24.21573 | 56.36917 | -0.2977 | 7.06157 |
September | 485.00000 | 24.28938 | 52.94507 | -0.3276 | 7.68086 |
October | 502.00000 | 24.33683 | 42.86300 | 0.48989 | 10.43398 |
November | 489.00000 | 24.37041 | 37.32567 | 0.45661 | 9.83259 |
December | 497.00000 | 24.36747 | 32.06623 | 0.42112 | 9.13601 |
Annual Sum or Average | 5943.00000 | 24.29705 | 44.91984 | 0.12438 | 8.86164 |
Minimum of Months | 454.00000 | 24.21573 | 32.06623 | -0.4060 | 7.06157 |
Maximum of Months | 514.00000 | 24.37041 | 56.36917 | 0.50035 | 10.44970 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.92606 | 40.58872 | 0.31842 | 7.45633 |
February | 454.00000 | 23.93093 | 41.62240 | 0.32951 | 7.47903 |
March | 514.00000 | 23.96299 | 44.37606 | 0.35818 | 7.87789 |
April | 485.00000 | 24.02508 | 47.20108 | 0.40480 | 8.64552 |
May | 508.00000 | 24.08322 | 46.59144 | -0.4874 | 10.22518 |
June | 496.00000 | 24.12992 | 52.64173 | -0.4175 | 8.86803 |
July | 497.00000 | 24.14818 | 56.78828 | -0.3753 | 8.12876 |
August | 514.00000 | 24.13641 | 57.75532 | -0.3684 | 7.99609 |
September | 485.00000 | 24.14726 | 53.86821 | -0.4027 | 8.65068 |
October | 502.00000 | 24.14842 | 44.15767 | 0.42296 | 9.04014 |
November | 489.00000 | 24.05738 | 39.82118 | 0.35611 | 8.02760 |
December | 497.00000 | 23.94134 | 34.57396 | 0.28802 | 7.03972 |
Annual Sum or Average | 5943.00000 | 24.05384 | 46.71239 | 0.03257 | 8.29240 |
Minimum of Months | 454.00000 | 23.92606 | 34.57396 | -0.4874 | 7.03972 |
Maximum of Months | 514.00000 | 24.14842 | 57.75532 | 0.42296 | 10.22518 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.93832 | 42.92456 | 0.06165 | 6.43961 |
February | 454.00000 | 23.08307 | 44.32740 | 0.11291 | 6.25676 |
March | 514.00000 | 23.30258 | 46.67349 | 0.18663 | 6.57487 |
April | 485.00000 | 23.69418 | 48.44519 | 0.32190 | 7.74762 |
May | 508.00000 | 23.78218 | 47.67781 | -0.5951 | 13.20665 |
June | 496.00000 | 24.00438 | 53.15490 | -0.4574 | 9.67992 |
July | 497.00000 | 24.12008 | 56.94230 | -0.3763 | 8.13416 |
August | 514.00000 | 24.07840 | 58.07727 | -0.3814 | 8.19670 |
September | 485.00000 | 23.95942 | 54.82862 | -0.4692 | 9.97574 |
October | 502.00000 | 23.84968 | 45.49518 | 0.34600 | 8.04912 |
November | 489.00000 | 23.40260 | 41.92453 | 0.18251 | 6.65633 |
December | 497.00000 | 23.01158 | 37.38011 | 0.04981 | 6.06348 |
Annual Sum or Average | 5943.00000 | 23.60574 | 48.19208 | -0.0871 | 8.09755 |
Minimum of Months | 454.00000 | 22.93832 | 37.38011 | -0.5951 | 6.06348 |
Maximum of Months | 514.00000 | 24.12008 | 58.07727 | 0.34600 | 13.20665 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.51907 | 37.97093 | 0.19337 | 6.47220 |
February | 454.00000 | 23.61657 | 40.19270 | 0.23971 | 6.62006 |
March | 514.00000 | 23.72472 | 42.94512 | 0.29242 | 7.32054 |
April | 485.00000 | 24.01706 | 45.65842 | 0.40539 | 8.66472 |
May | 508.00000 | 24.00496 | 45.24886 | -0.5083 | 10.86682 |
June | 496.00000 | 24.18134 | 50.94797 | -0.3762 | 8.26422 |
July | 497.00000 | 24.28230 | 54.77339 | -0.2965 | 7.20045 |
August | 514.00000 | 24.17126 | 55.94011 | -0.3301 | 7.55140 |
September | 485.00000 | 24.08974 | 52.82315 | -0.4212 | 9.10238 |
October | 502.00000 | 24.10462 | 42.84975 | 0.40881 | 8.96620 |
November | 489.00000 | 23.84063 | 37.99033 | 0.28813 | 7.18565 |
December | 497.00000 | 23.73815 | 32.65352 | 0.22240 | 6.37886 |
Annual Sum or Average | 5943.00000 | 23.94280 | 45.04376 | 0.00729 | 7.89145 |
Minimum of Months | 454.00000 | 23.51907 | 32.65352 | -0.5083 | 6.37886 |
Maximum of Months | 514.00000 | 24.28230 | 55.94011 | 0.40881 | 10.86682 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.79999 | 36.72934 | 0.28227 | 7.48149 |
February | 454.00000 | 23.73314 | 39.60186 | 0.28906 | 7.47697 |
March | 514.00000 | 23.79801 | 42.55067 | 0.33702 | 8.31930 |
April | 485.00000 | 24.11004 | 45.15322 | 0.46981 | 10.38111 |
May | 508.00000 | 24.17021 | 44.52884 | -0.4040 | 9.85860 |
June | 496.00000 | 24.21706 | 50.65964 | -0.3190 | 8.30220 |
July | 497.00000 | 24.38434 | 54.17497 | -0.2008 | 7.30128 |
August | 514.00000 | 24.23362 | 55.39592 | -0.2425 | 7.46080 |
September | 485.00000 | 24.20013 | 52.15585 | -0.3328 | 8.45675 |
October | 502.00000 | 24.22286 | 42.31920 | 0.46499 | 10.25866 |
November | 489.00000 | 23.92817 | 37.52476 | 0.33038 | 7.92287 |
December | 497.00000 | 23.81154 | 32.20527 | 0.26030 | 7.03942 |
Annual Sum or Average | 5943.00000 | 24.05273 | 44.46062 | 0.07557 | 8.35859 |
Minimum of Months | 454.00000 | 23.73314 | 32.20527 | -0.4040 | 7.03942 |
Maximum of Months | 514.00000 | 24.38434 | 55.39592 | 0.46981 | 10.38111 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.05885 | 35.75348 | 0.40843 | 9.85165 |
February | 454.00000 | 23.92919 | 38.91772 | 0.37521 | 9.25843 |
March | 514.00000 | 23.85101 | 42.09019 | 0.36519 | 8.99010 |
April | 485.00000 | 24.13219 | 45.07131 | 0.46699 | 10.29756 |
May | 508.00000 | 23.92997 | 45.40700 | -0.5254 | 11.71916 |
June | 496.00000 | 24.10227 | 51.22686 | -0.4086 | 8.89150 |
July | 497.00000 | 24.28552 | 54.74003 | -0.2917 | 7.37339 |
August | 514.00000 | 24.24201 | 55.45301 | -0.2627 | 7.20559 |
September | 485.00000 | 24.29924 | 51.71518 | -0.2703 | 7.90519 |
October | 502.00000 | 24.41967 | 41.64354 | 0.55966 | 12.84097 |
November | 489.00000 | 24.27990 | 36.28199 | 0.47896 | 10.97285 |
December | 497.00000 | 24.27103 | 30.82677 | 0.44807 | 10.58973 |
Annual Sum or Average | 5943.00000 | 24.15039 | 44.14344 | 0.10883 | 9.65924 |
Minimum of Months | 454.00000 | 23.85101 | 30.82677 | -0.5254 | 7.20559 |
Maximum of Months | 514.00000 | 24.41967 | 55.45301 | 0.55966 | 12.84097 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18555 | 35.76660 | 0.39779 | 8.94133 |
February | 454.00000 | 24.34378 | 37.59594 | 0.47983 | 10.45120 |
March | 514.00000 | 24.37833 | 40.26318 | 0.53991 | 11.83327 |
April | 485.00000 | 24.60633 | 43.41176 | 0.68423 | 15.90503 |
May | 508.00000 | 24.40614 | 43.58295 | -0.2599 | 7.96805 |
June | 496.00000 | 24.48582 | 49.47984 | -0.1206 | 6.83326 |
July | 497.00000 | 24.68106 | 52.97976 | 0.02452 | 7.21998 |
August | 514.00000 | 24.54204 | 54.02719 | 0.01699 | 6.87820 |
September | 485.00000 | 24.48043 | 50.92928 | -0.1616 | 7.12314 |
October | 502.00000 | 24.56388 | 40.96080 | 0.60649 | 13.85158 |
November | 489.00000 | 24.52319 | 35.41398 | 0.54169 | 12.08987 |
December | 497.00000 | 24.54789 | 30.02149 | 0.51565 | 11.49348 |
Annual Sum or Average | 5943.00000 | 24.47894 | 42.91731 | 0.26976 | 10.03245 |
Minimum of Months | 454.00000 | 24.18555 | 30.02149 | -0.2599 | 6.83326 |
Maximum of Months | 514.00000 | 24.68106 | 54.02719 | 0.68423 | 15.90503 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35645 | 40.62292 | -0.0900 | 6.64173 |
February | 454.00000 | 22.52913 | 43.38106 | -0.0254 | 6.08737 |
March | 514.00000 | 22.69406 | 46.28301 | 0.03509 | 6.27769 |
April | 485.00000 | 23.30427 | 48.27752 | 0.21489 | 6.75883 |
May | 508.00000 | 23.59568 | 46.80050 | -0.6671 | 15.29003 |
June | 496.00000 | 23.91933 | 52.20892 | -0.4926 | 10.50087 |
July | 497.00000 | 24.06061 | 56.34966 | -0.4018 | 8.68206 |
August | 514.00000 | 23.92137 | 58.06482 | -0.4474 | 9.53844 |
September | 485.00000 | 23.73337 | 54.42440 | -0.5618 | 12.26073 |
October | 502.00000 | 23.60549 | 44.59123 | 0.27402 | 7.44415 |
November | 489.00000 | 22.81519 | 41.29275 | 0.03364 | 6.17107 |
December | 497.00000 | 22.38402 | 35.70447 | -0.1105 | 6.30019 |
Annual Sum or Average | 5943.00000 | 23.24834 | 47.37187 | -0.1886 | 8.51899 |
Minimum of Months | 454.00000 | 22.35645 | 35.70447 | -0.6671 | 6.08737 |
Maximum of Months | 514.00000 | 24.06061 | 58.06482 | 0.27402 | 15.29003 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.12359 | 38.45601 | 0.10578 | 6.65139 |
February | 385.00000 | 23.07570 | 41.48493 | 0.12146 | 6.65051 |
March | 433.00000 | 23.24318 | 43.86280 | 0.18725 | 7.44395 |
April | 410.00000 | 23.88841 | 45.80543 | 0.39368 | 9.55649 |
May | 430.00000 | 24.01122 | 44.99537 | -0.4828 | 12.05333 |
June | 418.00000 | 24.13589 | 50.96371 | -0.3715 | 9.63883 |
July | 422.00000 | 24.42476 | 54.53070 | -0.2106 | 8.02095 |
August | 433.00000 | 24.26729 | 56.13257 | -0.2528 | 8.08996 |
September | 410.00000 | 24.04703 | 52.77009 | -0.4091 | 10.12522 |
October | 427.00000 | 24.04177 | 43.32745 | 0.40507 | 9.48531 |
November | 417.00000 | 23.42780 | 39.32532 | 0.19612 | 6.85502 |
December | 422.00000 | 23.15264 | 33.60354 | 0.08504 | 6.21877 |
Annual Sum or Average | 5034.00000 | 23.74056 | 45.46073 | -0.0206 | 8.40806 |
Minimum of Months | 385.00000 | 23.07570 | 33.60354 | -0.4828 | 6.21877 |
Maximum of Months | 433.00000 | 24.42476 | 56.13257 | 0.40507 | 12.05333 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.85828 | 36.31290 | 0.36241 | 9.85842 |
February | 454.00000 | 23.58160 | 40.09044 | 0.29267 | 8.92558 |
March | 514.00000 | 23.42478 | 43.54063 | 0.25684 | 8.37206 |
April | 485.00000 | 23.78280 | 46.30747 | 0.36836 | 9.06673 |
May | 508.00000 | 23.65800 | 46.38808 | -0.6298 | 14.74751 |
June | 496.00000 | 23.86256 | 52.33848 | -0.5084 | 11.05106 |
July | 497.00000 | 24.08929 | 56.14496 | -0.3803 | 8.66433 |
August | 514.00000 | 24.10867 | 56.94257 | -0.3325 | 8.17407 |
September | 485.00000 | 24.18977 | 52.23844 | -0.3154 | 8.83074 |
October | 502.00000 | 24.30784 | 42.13092 | 0.52734 | 12.50226 |
November | 489.00000 | 24.05315 | 37.39362 | 0.42129 | 10.48161 |
December | 497.00000 | 24.02515 | 31.58509 | 0.38179 | 10.25953 |
Annual Sum or Average | 5943.00000 | 23.91272 | 45.16832 | 0.03383 | 10.09019 |
Minimum of Months | 454.00000 | 23.42478 | 31.58509 | -0.6298 | 8.17407 |
Maximum of Months | 514.00000 | 24.30784 | 56.94257 | 0.52734 | 14.74751 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.14776 | 38.48291 | 0.12204 | 6.99111 |
February | 454.00000 | 23.29949 | 41.03605 | 0.18590 | 7.22071 |
March | 514.00000 | 23.40724 | 43.72849 | 0.23853 | 7.77196 |
April | 485.00000 | 24.01333 | 45.65852 | 0.44629 | 10.54175 |
May | 508.00000 | 24.05530 | 44.99880 | -0.4355 | 11.13528 |
June | 496.00000 | 24.20577 | 50.83978 | -0.3004 | 8.25471 |
July | 497.00000 | 24.41635 | 54.66143 | -0.1711 | 7.29469 |
August | 514.00000 | 24.28189 | 56.12541 | -0.2085 | 7.25239 |
September | 485.00000 | 24.23127 | 52.20421 | -0.3046 | 8.48923 |
October | 502.00000 | 24.12421 | 42.83811 | 0.44317 | 10.38618 |
November | 489.00000 | 23.60133 | 38.89330 | 0.25321 | 7.68198 |
December | 497.00000 | 23.33049 | 33.41143 | 0.13943 | 6.81808 |
Annual Sum or Average | 5943.00000 | 23.84599 | 45.28164 | 0.03198 | 8.32504 |
Minimum of Months | 454.00000 | 23.14776 | 33.41143 | -0.4355 | 6.81808 |
Maximum of Months | 514.00000 | 24.41635 | 56.12541 | 0.44629 | 11.13528 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.61176 | 42.06759 | -0.2906 | 9.17307 |
February | 454.00000 | 21.79032 | 45.06426 | -0.2181 | 7.77932 |
March | 514.00000 | 22.07279 | 47.83390 | -0.1268 | 7.24805 |
April | 485.00000 | 22.92685 | 49.33055 | 0.12193 | 6.84062 |
May | 508.00000 | 23.23872 | 47.78990 | -0.7898 | 20.19216 |
June | 496.00000 | 23.75807 | 52.74031 | -0.5447 | 12.20341 |
July | 497.00000 | 23.99325 | 56.65132 | -0.4174 | 9.33283 |
August | 514.00000 | 23.82162 | 58.56366 | -0.4752 | 10.48945 |
September | 485.00000 | 23.49132 | 55.38454 | -0.6442 | 15.14026 |
October | 502.00000 | 23.25824 | 45.60305 | 0.18690 | 7.41304 |
November | 489.00000 | 22.12331 | 42.47822 | -0.1470 | 7.27831 |
December | 497.00000 | 21.58372 | 37.20391 | -0.3212 | 8.89009 |
Annual Sum or Average | 5943.00000 | 22.81329 | 48.42661 | -0.3070 | 10.19052 |
Minimum of Months | 454.00000 | 21.58372 | 37.20391 | -0.7898 | 6.84062 |
Maximum of Months | 514.00000 | 23.99325 | 58.56366 | 0.18690 | 20.19216 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.56327 | 39.81385 | -0.0479 | 7.42533 |
February | 454.00000 | 22.54075 | 43.04803 | -0.0219 | 7.14152 |
March | 514.00000 | 22.83847 | 45.46324 | 0.08007 | 7.65403 |
April | 485.00000 | 23.64672 | 46.60852 | 0.34097 | 9.21311 |
May | 508.00000 | 23.75746 | 45.78306 | -0.5628 | 14.27868 |
June | 496.00000 | 23.99831 | 51.51246 | -0.4001 | 10.38617 |
July | 497.00000 | 24.31721 | 54.96544 | -0.2188 | 8.16849 |
August | 514.00000 | 24.16588 | 56.53156 | -0.2610 | 8.26539 |
September | 485.00000 | 23.86419 | 53.55011 | -0.4576 | 11.49904 |
October | 502.00000 | 23.78265 | 43.84796 | 0.34402 | 8.82680 |
November | 489.00000 | 22.99376 | 40.23997 | 0.07514 | 6.75560 |
December | 497.00000 | 22.56814 | 35.21451 | -0.0728 | 6.82339 |
Annual Sum or Average | 5943.00000 | 23.42590 | 46.41579 | -0.1015 | 8.88244 |
Minimum of Months | 454.00000 | 22.54075 | 35.21451 | -0.5628 | 6.75560 |
Maximum of Months | 514.00000 | 24.31721 | 56.53156 | 0.34402 | 14.27868 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.34327 | 37.30730 | 0.21139 | 9.37489 |
February | 454.00000 | 23.04054 | 41.43971 | 0.14179 | 8.83663 |
March | 514.00000 | 22.93191 | 44.89350 | 0.12251 | 8.46650 |
April | 485.00000 | 23.47289 | 47.21168 | 0.29011 | 8.85968 |
May | 508.00000 | 23.32657 | 47.31024 | -0.7452 | 19.31565 |
June | 496.00000 | 23.69714 | 52.87387 | -0.5613 | 12.92029 |
July | 497.00000 | 24.01872 | 56.45881 | -0.3962 | 9.42319 |
August | 514.00000 | 24.01888 | 57.40857 | -0.3563 | 9.01331 |
September | 485.00000 | 24.00915 | 52.99964 | -0.3787 | 10.59591 |
October | 502.00000 | 24.07094 | 42.89243 | 0.46378 | 11.82736 |
November | 489.00000 | 23.63776 | 38.02647 | 0.29866 | 9.55938 |
December | 497.00000 | 23.51925 | 32.54447 | 0.23325 | 9.32492 |
Annual Sum or Average | 5943.00000 | 23.59292 | 45.99499 | -0.0592 | 10.64935 |
Minimum of Months | 454.00000 | 22.93191 | 32.54447 | -0.7452 | 8.46650 |
Maximum of Months | 514.00000 | 24.07094 | 57.40857 | 0.46378 | 19.31565 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.55318 | 39.55784 | -0.0395 | 7.86731 |
February | 454.00000 | 22.70289 | 42.38196 | 0.03002 | 7.53611 |
March | 514.00000 | 22.91033 | 45.02677 | 0.10838 | 7.82913 |
April | 485.00000 | 23.74470 | 46.46670 | 0.37840 | 10.16728 |
May | 508.00000 | 23.80018 | 45.74855 | -0.5260 | 14.26739 |
June | 496.00000 | 24.08580 | 51.26119 | -0.3390 | 9.38201 |
July | 497.00000 | 24.36444 | 54.92653 | -0.1812 | 7.71848 |
August | 514.00000 | 24.21676 | 56.52981 | -0.2254 | 7.74451 |
September | 485.00000 | 24.07913 | 52.90868 | -0.3588 | 9.93140 |
October | 502.00000 | 23.87355 | 43.59698 | 0.37824 | 9.99356 |
November | 489.00000 | 23.08359 | 39.71186 | 0.11413 | 7.58066 |
December | 497.00000 | 22.70639 | 34.54800 | -0.0275 | 7.37810 |
Annual Sum or Average | 5943.00000 | 23.51512 | 46.09390 | -0.0589 | 8.96038 |
Minimum of Months | 454.00000 | 22.55318 | 34.54800 | -0.5260 | 7.37810 |
Maximum of Months | 514.00000 | 24.36444 | 56.52981 | 0.37840 | 14.26739 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.332625E+11 | 120776.76 | 18-JAN-14:40 | 260.13 | 0.234693E+12 | 0.00 | 0.267955E+12 | 2.20 | 7.96 | 14-JAN-15:05 | 0.00 | 0.00 |
February | 0.207222E+11 | 119625.80 | 01-FEB-11:50 | 196.50 | 0.139419E+12 | 0.00 | 0.160141E+12 | 1.73 | 7.96 | 03-FEB-12:10 | 0.00 | 0.00 |
March | 0.205151E+11 | 135261.20 | 23-MAR-13:00 | 197.41 | 0.136108E+12 | 0.00 | 0.156624E+12 | 1.54 | 7.96 | 10-MAR-15:00 | 0.00 | 0.00 |
April | 0.387642E+11 | 133594.93 | 26-APR-09:50 | 310.26 | 0.267798E+12 | 0.00 | 0.306562E+12 | 2.66 | 7.96 | 13-APR-11:00 | 0.00 | 0.00 |
May | 0.409105E+11 | 131252.57 | 04-MAY-12:20 | 349.76 | 0.276177E+12 | 0.00 | 0.317088E+12 | 2.82 | 7.96 | 04-MAY-10:30 | 0.00 | 0.00 |
June | 0.637781E+11 | 133798.62 | 29-JUN-08:50 | 431.13 | 0.447271E+12 | 0.00 | 0.511049E+12 | 3.78 | 7.98 | 19-JUN-05:04 | 0.00 | 0.00 |
July | 0.951006E+11 | 136731.36 | 18-JUL-16:20 | 552.84 | 0.673453E+12 | 0.00 | 0.768554E+12 | 4.79 | 7.96 | 26-JUL-05:04 | 0.00 | 0.00 |
August | 0.105896E+12 | 138508.92 | 19-AUG-09:05 | 611.02 | 0.751479E+12 | 0.00 | 0.857375E+12 | 5.26 | 7.97 | 03-AUG-05:04 | 0.00 | 0.00 |
September | 0.681641E+11 | 135821.62 | 11-SEP-12:40 | 419.12 | 0.483633E+12 | 0.00 | 0.551797E+12 | 3.75 | 7.97 | 23-SEP-05:05 | 0.00 | 0.00 |
October | 0.767224E+11 | 134409.53 | 18-OCT-12:00 | 442.30 | 0.551448E+12 | 0.00 | 0.628170E+12 | 3.89 | 7.96 | 16-OCT-05:05 | 0.00 | 0.00 |
November | 0.379237E+11 | 120076.20 | 28-NOV-13:20 | 285.33 | 0.273238E+12 | 0.00 | 0.311162E+12 | 2.51 | 7.96 | 07-NOV-14:20 | 0.00 | 0.00 |
December | 0.407851E+11 | 125008.98 | 05-DEC-10:40 | 273.62 | 0.293475E+12 | 0.00 | 0.334261E+12 | 2.36 | 7.96 | 28-DEC-15:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.642544E+12 | 4329.41 | 0.452819E+13 | 0.00 | 0.517074E+13 | 3.12 | 0.00 | 0.00 | ||||
Minimum of Months | 0.205151E+11 | 119625.80 | 196.50 | 0.136108E+12 | 0.00 | 0.156624E+12 | 1.54 | 7.96 | 0.00 | 0.00 | ||
Maximum of Months | 0.105896E+12 | 138508.92 | 611.02 | 0.751479E+12 | 0.00 | 0.857375E+12 | 5.26 | 7.98 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 88122595.33 | 79612.89 | 18-JAN-13:40 | 0.42 | 0.649916E+09 | 0.00 | 0.738038E+09 | 0.00 | 7.86 | 18-JAN-13:40 | 0.00 | 0.00 |
February | 19921581.80 | 66405.27 | 01-FEB-12:10 | 0.08 | 0.150608E+09 | 0.00 | 0.170530E+09 | 0.00 | 7.56 | 01-FEB-12:10 | 0.00 | 0.00 |
March | 0.436807E+09 | 80462.75 | 23-MAR-14:05 | 1.92 | 0.329936E+10 | 0.00 | 0.373616E+10 | 0.02 | 7.75 | 23-MAR-14:00 | 0.00 | 0.00 |
April | 0.127359E+10 | 76804.49 | 12-APR-14:30 | 5.58 | 0.970265E+10 | 0.00 | 0.109762E+11 | 0.06 | 7.85 | 12-APR-14:05 | 0.00 | 0.00 |
May | 3613032.45 | 6021.72 | 04-MAY-12:30 | 0.17 | 19215042.48 | 0.00 | 22828074.93 | 0.00 | 5.32 | 04-MAY-12:30 | 0.00 | 0.00 |
June | 0.611942E+10 | 87887.92 | 27-JUN-10:05 | 24.67 | 0.456869E+11 | 0.00 | 0.518063E+11 | 0.26 | 7.68 | 30-JUN-13:30 | 0.00 | 0.00 |
July | 0.272993E+11 | 107148.68 | 28-JUL-12:30 | 97.00 | 0.198049E+12 | 0.00 | 0.225348E+12 | 0.95 | 7.67 | 12-JUL-15:30 | 0.00 | 0.00 |
August | 0.385307E+11 | 116438.88 | 07-AUG-10:30 | 134.75 | 0.279868E+12 | 0.00 | 0.318399E+12 | 1.32 | 7.82 | 29-AUG-15:30 | 0.00 | 0.00 |
September | 0.141269E+11 | 95132.01 | 21-SEP-12:05 | 55.15 | 0.105671E+12 | 0.00 | 0.119798E+12 | 0.57 | 7.94 | 29-SEP-09:00 | 0.00 | 0.00 |
October | 0.201494E+11 | 106699.88 | 04-OCT-10:50 | 75.00 | 0.151289E+12 | 0.00 | 0.171438E+12 | 0.76 | 7.96 | 16-OCT-15:50 | 0.00 | 0.00 |
November | 0.232974E+09 | 74133.64 | 28-NOV-13:40 | 0.92 | 0.175345E+10 | 0.00 | 0.198642E+10 | 0.01 | 7.85 | 28-NOV-14:05 | 0.00 | 0.00 |
December | 0.839973E+09 | 83354.24 | 19-DEC-13:05 | 3.50 | 0.639102E+10 | 0.00 | 0.723099E+10 | 0.04 | 7.93 | 19-DEC-13:15 | 0.00 | 0.00 |
Annual Sum or Average | 0.109121E+12 | 399.15 | 0.802530E+12 | 0.00 | 0.911651E+12 | 0.34 | 0.00 | 0.00 | ||||
Minimum of Months | 3613032.45 | 6021.72 | 0.08 | 19215042.48 | 0.00 | 22828074.93 | 0.00 | 5.32 | 0.00 | 0.00 | ||
Maximum of Months | 0.385307E+11 | 116438.88 | 134.75 | 0.279868E+12 | 0.00 | 0.318399E+12 | 1.32 | 7.96 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.226706E+11 | 744.00 | 43776.24 | 03-JAN-12:10 | 165121.17 | 14-JAN-12:00 | 19.36 | 18.77 | 13.84 |
February | 0.199814E+11 | 672.00 | 43776.24 | 01-FEB-07:55 | 306312.81 | 01-FEB-12:05 | 19.67 | 18.50 | 13.84 |
March | 0.292148E+11 | 744.00 | 43776.24 | 01-MAR-10:05 | 439460.43 | 23-MAR-14:05 | 20.95 | 18.74 | 13.84 |
April | 0.674517E+11 | 720.00 | 43776.24 | 01-APR-08:20 | 635347.84 | 26-APR-11:10 | 25.81 | 20.06 | 13.84 |
May | 0.385469E+11 | 744.00 | 43776.24 | 01-MAY-09:40 | 102876.95 | 04-MAY-12:05 | 19.44 | 18.82 | 13.84 |
June | 0.611583E+11 | 720.00 | 43776.24 | 01-JUN-08:40 | 376387.33 | 29-JUN-11:00 | 21.88 | 19.84 | 13.84 |
July | 0.109454E+12 | 744.00 | 43776.24 | 01-JUL-02:50 | 643698.19 | 31-JUL-14:05 | 28.80 | 22.28 | 13.84 |
August | 0.116537E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 678230.55 | 18-AUG-12:05 | 35.59 | 24.29 | 13.84 |
September | 0.589511E+11 | 720.00 | 43776.24 | 01-SEP-08:40 | 262298.48 | 21-SEP-13:30 | 20.79 | 19.94 | 13.84 |
October | 0.764165E+11 | 744.00 | 43776.24 | 01-OCT-00:10 | 457160.97 | 01-OCT-12:00 | 23.79 | 21.17 | 13.84 |
November | 0.428196E+11 | 720.00 | 43776.24 | 01-NOV-11:00 | 496283.96 | 19-NOV-13:02 | 21.68 | 19.06 | 13.84 |
December | 0.552367E+11 | 744.00 | 43776.24 | 01-DEC-14:00 | 580251.15 | 05-DEC-10:05 | 24.14 | 19.61 | 13.84 |
Annual Sum or Average | 0.698438E+12 | 8760.00 | 23.53 | 20.11 | 13.84 | ||||
Minimum of Months | 0.199814E+11 | 672.00 | 43776.24 | 102876.95 | 19.36 | 18.50 | 13.84 | ||
Maximum of Months | 0.116537E+12 | 744.00 | 43776.24 | 678230.55 | 35.59 | 24.29 | 13.84 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.766968E+09 | 189.62 | 13306.13 | 13-JAN-13:50 | 992821.96 | 18-JAN-12:00 | 21.75 | 21.23 | 14.38 |
February | 0.255124E+09 | 128.46 | 13306.13 | 01-FEB-11:40 | 1031965.36 | 03-FEB-14:30 | 21.46 | 21.11 | 12.01 |
March | 0.656695E+09 | 136.56 | 13306.13 | 22-MAR-12:05 | 1001570.56 | 23-MAR-12:50 | 21.43 | 21.12 | 10.99 |
April | 0.169960E+10 | 238.90 | 13306.13 | 04-APR-12:05 | 1031035.75 | 25-APR-14:30 | 21.71 | 21.10 | 18.64 |
May | 0.121715E+10 | 268.30 | 13306.13 | 02-MAY-12:40 | 1029091.95 | 03-MAY-13:50 | 21.70 | 21.08 | 20.55 |
June | 0.488910E+10 | 366.56 | 13306.13 | 13-JUN-11:00 | 1012342.97 | 21-JUN-14:00 | 22.28 | 21.27 | 27.30 |
July | 0.117536E+11 | 461.82 | 13306.13 | 01-JUL-10:20 | 963732.35 | 12-JUL-15:50 | 23.13 | 21.67 | 33.22 |
August | 0.138771E+11 | 485.73 | 13306.13 | 01-AUG-09:50 | 979477.57 | 22-AUG-13:20 | 23.38 | 21.75 | 36.62 |
September | 0.662420E+10 | 372.89 | 13306.13 | 01-SEP-10:40 | 980251.94 | 12-SEP-13:30 | 22.57 | 21.49 | 26.70 |
October | 0.611391E+10 | 379.33 | 13306.13 | 01-OCT-10:43 | 1048130.58 | 31-OCT-16:00 | 22.68 | 21.45 | 26.77 |
November | 0.621882E+09 | 199.58 | 13306.13 | 10-NOV-12:20 | 1029216.32 | 28-NOV-13:20 | 21.75 | 21.13 | 16.33 |
December | 0.462263E+09 | 206.52 | 13306.13 | 07-DEC-14:20 | 1061689.40 | 05-DEC-13:50 | 21.75 | 21.10 | 15.72 |
Annual Sum or Average | 0.489376E+11 | 3434.28 | 22.14 | 21.29 | 21.68 | ||||
Minimum of Months | 0.255124E+09 | 128.46 | 13306.13 | 963732.35 | 21.43 | 21.08 | 10.99 | ||
Maximum of Months | 0.138771E+11 | 485.73 | 13306.13 | 1061689.40 | 23.38 | 21.75 | 36.62 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 1052687.73 | 0.17 | 1754.48 | 18-JAN-13:40 | 742737.72 | 18-JAN-13:40 | 21.75 | 21.74 | 0.01 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.46 | 21.46 | 0.00 |
March | 75844946.61 | 1.58 | 13306.13 | 22-MAR-12:40 | 726943.46 | 23-MAR-14:00 | 21.43 | 21.42 | 0.10 |
April | 0.227535E+09 | 4.75 | 13306.13 | 11-APR-15:30 | 784889.34 | 26-APR-15:00 | 21.71 | 21.69 | 0.30 |
May | 7983678.59 | 0.17 | 13306.13 | 04-MAY-12:20 | 654024.35 | 04-MAY-12:20 | 21.70 | 21.70 | 0.01 |
June | 0.123348E+10 | 25.75 | 13306.13 | 19-JUN-10:30 | 748639.47 | 27-JUN-12:05 | 22.28 | 22.16 | 1.67 |
July | 0.486705E+10 | 101.60 | 13306.13 | 12-JUL-12:05 | 845663.47 | 28-JUL-12:30 | 23.13 | 22.66 | 6.39 |
August | 0.676617E+10 | 141.25 | 13306.13 | 02-AUG-09:50 | 907485.97 | 07-AUG-10:30 | 23.38 | 22.72 | 8.87 |
September | 0.256909E+10 | 54.37 | 13306.13 | 05-SEP-12:40 | 863379.39 | 29-SEP-08:20 | 22.57 | 22.32 | 3.56 |
October | 0.260475E+10 | 67.28 | 13306.13 | 01-OCT-11:40 | 950431.48 | 16-OCT-08:20 | 22.68 | 22.34 | 4.27 |
November | 127424.19 | 0.08 | 424.75 | 28-NOV-14:05 | 913012.64 | 28-NOV-14:05 | 21.75 | 21.75 | 0.01 |
December | 3862421.34 | 1.25 | 1569.12 | 05-DEC-11:05 | 905710.77 | 05-DEC-11:05 | 21.75 | 21.74 | 0.08 |
Annual Sum or Average | 0.183569E+11 | 398.25 | 22.14 | 21.98 | 2.13 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.43 | 21.42 | 0.00 | ||
Maximum of Months | 0.676617E+10 | 141.25 | 13306.13 | 950431.48 | 23.38 | 22.72 | 8.87 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.145018E+11 | 0.00 | 131.65 | 758730.83 | 03-JAN-06:02 | 0.00 | 34.71 | 39.21 | 0.06 | 0.00 | 0.00 | 0.54 | 03-JAN-06:02 |
February | 0.410937E+10 | 0.00 | 100.00 | 211830.59 | 06-FEB-06:03 | 0.00 | 31.62 | 35.80 | 0.01 | 0.00 | 0.00 | 0.15 | 06-FEB-06:03 |
March | 0.107863E+11 | 0.00 | 119.54 | 859565.09 | 29-MAR-05:02 | 0.00 | 32.29 | 36.58 | 0.04 | 0.00 | 0.00 | 0.61 | 29-MAR-05:02 |
April | 0.545479E+09 | 0.00 | 20.62 | 280083.02 | 01-APR-05:02 | 0.00 | 30.71 | 31.54 | 0.00 | 0.00 | 0.00 | 0.20 | 01-APR-05:02 |
May | 62951298.80 | 0.00 | 8.52 | 114094.35 | 13-MAY-05:02 | 0.00 | 30.61 | 30.94 | 0.00 | 0.00 | 0.00 | 0.08 | 13-MAY-05:02 |
June | 640.82 | 0.00 | 0.17 | 1.07 | 30-JUN-15:00 | 0.00 | 30.94 | 30.95 | 0.00 | 0.00 | 0.00 | 0.00 | 30-JUN-15:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 30.94 | 30.94 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 30.94 | 30.94 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 30.94 | 30.94 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.105632E+09 | 0.00 | 16.85 | 41671.62 | 30-OCT-05:03 | 0.00 | 30.56 | 31.23 | 0.00 | 0.00 | 0.00 | 0.03 | 30-OCT-05:03 |
November | 0.115719E+10 | 0.00 | 62.91 | 223332.60 | 24-NOV-06:03 | 0.00 | 31.53 | 33.98 | 0.00 | 0.00 | 0.00 | 0.16 | 24-NOV-06:03 |
December | 0.796443E+10 | 0.00 | 118.95 | 548179.11 | 13-DEC-06:03 | 0.00 | 33.32 | 37.50 | 0.03 | 0.00 | 0.00 | 0.39 | 13-DEC-06:03 |
Annual Sum or Average | 0.392331E+11 | 0.00 | 579.22 | 0.00 | 31.60 | 33.38 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 | 30.94 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.145018E+11 | 0.00 | 131.65 | 859565.09 | 0.00 | 34.71 | 39.21 | 0.06 | 0.00 | 0.00 | 0.61 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 19.36 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.67 | 19.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.95 | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 25.81 | 25.81 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.44 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 21.88 | 21.88 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 28.80 | 28.80 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 35.59 | 35.59 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20.79 | 20.79 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 23.79 | 23.79 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 21.68 | 21.68 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 24.14 | 24.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 23.53 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 | 35.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.187112E+11 | 0.00 | 218.51 | 0.186711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80484.04 | 18-JAN-14:10 | 80484.04 | 18-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.109026E+11 | 0.00 | 169.31 | 0.108345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75455.32 | 01-FEB-12:00 | 75455.32 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.130551E+11 | 0.00 | 172.61 | 0.127018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86557.75 | 23-MAR-14:00 | 74095.25 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.296910E+11 | 0.00 | 291.95 | 0.296734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99334.27 | 26-APR-13:50 | 99334.27 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.258458E+11 | 0.00 | 328.65 | 0.257727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71521.21 | 03-MAY-13:00 | 71521.21 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.473497E+11 | 0.00 | 419.12 | 0.434224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110158.79 | 29-JUN-13:00 | 80746.71 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.875780E+11 | 0.00 | 531.89 | 0.654215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153864.60 | 31-JUL-16:00 | 102545.13 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.108515E+12 | 0.00 | 593.46 | 0.761623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168820.68 | 07-AUG-10:40 | 106262.43 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.532685E+11 | 0.00 | 399.83 | 0.450449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124425.29 | 22-SEP-05:02 | 124158.43 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.669074E+11 | 0.00 | 418.49 | 0.569439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147846.93 | 05-OCT-04:12 | 124160.06 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.230624E+11 | 0.00 | 254.62 | 0.227089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86729.29 | 28-NOV-14:00 | 86729.29 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.269324E+11 | 0.00 | 232.99 | 0.268653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92657.00 | 05-DEC-15:00 | 92657.00 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.511819E+12 | 0.00 | 4031.44 | 0.434223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.109026E+11 | 0.00 | 169.31 | 0.108345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71521.21 | 71521.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108515E+12 | 0.00 | 593.46 | 0.761623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168820.68 | 124160.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.191014E+12 | 0.00 | 246.47 | 0.190588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 679674.72 | 18-JAN-13:05 | 679674.72 | 18-JAN-13:05 | 0.00 | 0.00 | 0.00 |
February | 0.114301E+12 | 0.00 | 187.78 | 0.113703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 633928.33 | 03-FEB-15:05 | 633928.33 | 03-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.109448E+12 | 0.00 | 185.46 | 0.106642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 746171.67 | 23-MAR-14:05 | 615411.07 | 23-MAR-14:05 | 0.00 | 0.00 | 0.00 |
April | 0.207545E+12 | 0.00 | 279.25 | 0.207460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 799921.25 | 26-APR-14:05 | 799921.25 | 26-APR-14:05 | 0.00 | 0.00 | 0.00 |
May | 0.212911E+12 | 0.00 | 328.31 | 0.212374E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 631215.24 | 04-MAY-12:05 | 631215.24 | 04-MAY-12:05 | 0.00 | 0.00 | 0.00 |
June | 0.373490E+12 | 0.00 | 408.72 | 0.344448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 927706.85 | 29-JUN-13:00 | 654017.91 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.653850E+12 | 0.00 | 451.98 | 0.497360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1151924.47 | 28-JUL-12:30 | 855201.87 | 31-JUL-14:05 | 0.00 | 0.00 | 0.00 |
August | 0.768562E+12 | 0.00 | 465.33 | 0.557666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1203322.21 | 07-AUG-10:05 | 876665.59 | 17-AUG-14:05 | 0.00 | 0.00 | 0.00 |
September | 0.450866E+12 | 0.00 | 398.34 | 0.384612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1138060.64 | 30-SEP-05:02 | 1138060.64 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.533331E+12 | 0.00 | 402.98 | 0.458534E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1245688.06 | 05-OCT-05:02 | 1091848.50 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.218934E+12 | 0.00 | 261.45 | 0.216282E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 644953.37 | 28-NOV-14:00 | 644953.37 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.229444E+12 | 0.00 | 252.88 | 0.228918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 702622.09 | 05-DEC-15:05 | 702622.09 | 05-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406370E+13 | 0.00 | 3868.95 | 0.351859E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.109448E+12 | 0.00 | 185.46 | 0.106642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 631215.24 | 615411.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.768562E+12 | 0.00 | 465.33 | 0.557666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1245688.06 | 1138060.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.115662E+11 | 0.00 | 201.62 | 0.115414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64955.05 | 18-JAN-13:50 | 64955.05 | 18-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.634914E+10 | 0.00 | 157.04 | 0.630173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55176.89 | 03-FEB-15:00 | 55176.89 | 03-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.790772E+10 | 0.00 | 151.69 | 0.778890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68780.23 | 23-MAR-14:00 | 62226.32 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.199934E+11 | 0.00 | 262.97 | 0.199901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93688.90 | 26-APR-14:00 | 93688.90 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.203643E+11 | 0.00 | 313.36 | 0.203193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70966.39 | 03-MAY-13:10 | 70966.39 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.384768E+11 | 0.00 | 397.19 | 0.353220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104142.28 | 29-JUN-13:00 | 70939.03 | 21-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.696404E+11 | 0.00 | 440.78 | 0.529290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150270.65 | 31-JUL-15:40 | 101495.32 | 31-JUL-13:50 | 0.00 | 0.00 | 0.00 |
August | 0.810754E+11 | 0.00 | 451.46 | 0.586424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151622.98 | 14-AUG-13:40 | 101596.17 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.440443E+11 | 0.00 | 381.39 | 0.378061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120568.32 | 29-SEP-13:40 | 120568.32 | 29-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.507875E+11 | 0.00 | 386.40 | 0.435588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135739.41 | 03-OCT-13:10 | 122692.81 | 16-OCT-13:05 | 0.00 | 0.00 | 0.00 |
November | 0.124077E+11 | 0.00 | 229.15 | 0.123445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60645.89 | 28-NOV-14:00 | 60645.89 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.145072E+11 | 0.00 | 206.31 | 0.144820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68362.56 | 05-DEC-15:00 | 68362.56 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377120E+12 | 0.00 | 3579.37 | 0.321026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.634914E+10 | 0.00 | 151.69 | 0.630173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55176.89 | 55176.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.810754E+11 | 0.00 | 451.46 | 0.586424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151622.98 | 122692.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.103200E+11 | 0.00 | 151.20 | 0.102645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61207.35 | 17-JAN-12:00 | 61207.35 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.450828E+10 | 0.00 | 92.24 | 0.446298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59851.49 | 13-FEB-06:02 | 47549.58 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.511424E+10 | 0.00 | 93.14 | 0.504709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44163.44 | 18-MAR-04:12 | 39375.78 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.135654E+11 | 0.00 | 190.83 | 0.134558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60347.99 | 27-APR-04:12 | 50774.34 | 03-APR-10:00 | 0.00 | 0.00 | 0.00 |
May | 0.127815E+11 | 0.00 | 207.68 | 0.126722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59176.58 | 03-MAY-04:12 | 44096.17 | 03-MAY-12:20 | 0.00 | 0.00 | 0.00 |
June | 0.233821E+11 | 0.00 | 276.17 | 0.226323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77080.89 | 30-JUN-04:12 | 55687.24 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.406492E+11 | 0.00 | 328.89 | 0.354082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92344.07 | 31-JUL-09:10 | 61473.85 | 31-JUL-12:05 | 0.00 | 0.00 | 0.00 |
August | 0.463271E+11 | 0.00 | 361.88 | 0.390344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109151.46 | 07-AUG-09:50 | 64107.97 | 14-AUG-11:00 | 0.00 | 0.00 | 0.00 |
September | 0.282003E+11 | 0.00 | 281.83 | 0.255894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85729.26 | 22-SEP-04:13 | 70114.26 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.374460E+11 | 0.00 | 307.61 | 0.330944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93280.94 | 02-OCT-13:00 | 79185.49 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.117432E+11 | 0.00 | 175.66 | 0.117082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56802.54 | 10-NOV-06:03 | 54063.58 | 27-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.146239E+11 | 0.00 | 158.34 | 0.146096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75991.03 | 25-DEC-11:57 | 75991.03 | 25-DEC-11:57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248661E+12 | 0.00 | 2625.47 | 0.227979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.450828E+10 | 0.00 | 92.24 | 0.446298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44163.44 | 39375.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.463271E+11 | 0.00 | 361.88 | 0.390344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109151.46 | 79185.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.882186E+10 | 0.493131E+10 | 464.46 | 0.871802E+10 | 0.103843E+09 | 0.00 | 0.34 | 14-JAN-11:10 | 0.01 | 22-JAN-12:45 | 103243.51 | 14-JAN-11:00 | 103243.51 | 14-JAN-11:00 | 10266.27 | 17-JAN-12:00 | 33969.44 | 14-JAN-11:20 | 0.00 |
February | 0.890193E+10 | 0.471330E+10 | 374.04 | 0.873937E+10 | 0.162558E+09 | 0.00 | 0.56 | 01-FEB-12:00 | 0.01 | 27-FEB-04:10 | 191930.18 | 01-FEB-12:00 | 191930.18 | 01-FEB-12:00 | 16842.82 | 01-FEB-13:40 | 57055.98 | 01-FEB-12:00 | 0.00 |
March | 0.593759E+11 | 0.172309E+11 | 466.52 | 0.457556E+11 | 0.136203E+11 | 0.00 | 0.71 | 23-MAR-14:00 | 0.01 | 06-MAR-05:10 | 273731.84 | 23-MAR-14:00 | 233147.56 | 11-MAR-13:30 | 88688.79 | 23-MAR-16:00 | 69792.80 | 23-MAR-14:00 | 0.00 |
April | 0.350390E+12 | 0.863884E+11 | 684.35 | 0.254629E+12 | 0.957609E+11 | 0.00 | 1.00 | 26-APR-10:20 | 0.01 | 30-APR-23:37 | 402417.61 | 26-APR-11:00 | 387454.20 | 26-APR-12:50 | 136531.61 | 30-APR-22:00 | 110227.55 | 26-APR-13:00 | 0.00 |
May | 0.128953E+10 | 0.261091E+10 | 233.21 | 0.115812E+10 | 0.131410E+09 | 0.00 | 0.16 | 04-MAY-12:00 | 0.01 | 14-MAY-14:15 | 54369.54 | 04-MAY-12:00 | 48500.02 | 03-MAY-13:00 | 7259.84 | 04-MAY-12:10 | 15499.87 | 04-MAY-12:00 | 0.00 |
June | 0.824113E+11 | 0.237287E+11 | 364.45 | 0.592087E+11 | 0.232025E+11 | 0.00 | 0.62 | 29-JUN-11:00 | 0.01 | 01-JUN-00:10 | 247184.84 | 29-JUN-11:00 | 165590.50 | 29-JUN-11:00 | 81594.34 | 29-JUN-11:00 | 63472.92 | 29-JUN-11:00 | 0.00 |
July | 0.489618E+12 | 0.118451E+12 | 729.82 | 0.296851E+12 | 0.192768E+12 | 0.00 | 1.00 | 18-JUL-11:00 | 0.01 | 06-JUL-04:10 | 427239.19 | 31-JUL-13:55 | 319192.32 | 31-JUL-12:05 | 207239.75 | 31-JUL-24:00 | 113177.56 | 31-JUL-11:50 | 0.00 |
August | 0.937178E+12 | 0.217608E+12 | 743.42 | 0.521128E+12 | 0.416050E+12 | 0.00 | 1.00 | 02-AUG-09:00 | 0.01 | 31-AUG-23:30 | 426494.46 | 14-AUG-10:00 | 354704.64 | 29-AUG-13:00 | 257987.41 | 18-AUG-07:00 | 114084.21 | 14-AUG-11:00 | 0.00 |
September | 0.191610E+11 | 0.841293E+10 | 269.91 | 0.171147E+11 | 0.204634E+10 | 0.00 | 0.46 | 21-SEP-13:30 | 0.01 | 18-SEP-21:03 | 182213.60 | 22-SEP-12:00 | 130475.40 | 29-SEP-07:40 | 82277.67 | 22-SEP-12:00 | 50540.68 | 29-SEP-12:20 | 0.00 |
October | 0.143167E+12 | 0.419539E+11 | 560.51 | 0.115409E+12 | 0.277572E+11 | 0.00 | 0.75 | 01-OCT-12:00 | 0.01 | 08-OCT-07:00 | 310927.70 | 01-OCT-11:52 | 222865.05 | 17-OCT-08:20 | 122110.72 | 01-OCT-11:52 | 86937.39 | 16-OCT-11:00 | 0.00 |
November | 0.942730E+11 | 0.273189E+11 | 537.81 | 0.812678E+11 | 0.130052E+11 | 0.00 | 0.87 | 19-NOV-12:59 | 0.01 | 07-NOV-03:10 | 310281.24 | 19-NOV-12:53 | 310281.24 | 19-NOV-12:53 | 68738.27 | 10-NOV-13:00 | 93126.99 | 19-NOV-12:59 | 0.00 |
December | 0.238652E+12 | 0.657357E+11 | 691.04 | 0.216037E+12 | 0.226149E+11 | 0.00 | 1.00 | 04-DEC-10:00 | 0.01 | 12-DEC-05:23 | 353305.29 | 16-DEC-12:45 | 353305.29 | 16-DEC-12:45 | 94594.87 | 07-DEC-15:50 | 106389.74 | 16-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.243324E+13 | 0.619084E+12 | 6119.54 | 0.162602E+13 | 0.807223E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.128953E+10 | 0.261091E+10 | 233.21 | 0.115812E+10 | 0.103843E+09 | 0.00 | 0.16 | 0.01 | 54369.54 | 48500.02 | 7259.84 | 15499.87 | 0.00 | ||||||
Maximum of Months | 0.937178E+12 | 0.217608E+12 | 743.42 | 0.521128E+12 | 0.416050E+12 | 0.00 | 1.00 | 0.01 | 427239.19 | 387454.20 | 257987.41 | 114084.21 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.507486E+10 | 0.112551E+10 | 744.00 | 0.503290E+10 | 41957726.46 | 0.00 | 0.33 | 15-JAN-16:03 | 0.17 | 28-JAN-07:10 | 2422.36 | 15-JAN-16:10 | 2422.36 | 15-JAN-16:10 | 170.12 | 17-JAN-15:00 | 625.94 | 15-JAN-14:13 | 0.00 |
February | 0.927580E+10 | 0.190777E+10 | 672.00 | 0.921488E+10 | 60915440.18 | 0.00 | 0.57 | 05-FEB-16:53 | 0.41 | 11-FEB-07:50 | 4664.66 | 20-FEB-17:10 | 4643.38 | 20-FEB-16:55 | 216.80 | 01-FEB-16:30 | 1111.75 | 01-FEB-12:00 | 0.00 |
March | 0.154285E+11 | 0.304488E+10 | 744.00 | 0.153325E+11 | 96056473.52 | 0.00 | 0.85 | 31-MAR-24:00 | 0.62 | 01-MAR-07:05 | 7504.43 | 31-MAR-24:00 | 7504.43 | 31-MAR-24:00 | 264.84 | 23-MAR-16:10 | 1522.00 | 11-MAR-14:00 | 0.00 |
April | 0.201168E+11 | 0.398447E+10 | 720.00 | 0.199891E+11 | 0.127701E+09 | 0.00 | 1.00 | 02-APR-13:53 | 0.31 | 30-APR-24:00 | 8460.58 | 16-APR-17:23 | 8448.62 | 30-APR-17:27 | 244.29 | 13-APR-16:00 | 2205.53 | 26-APR-13:00 | 0.00 |
May | 0.546005E+10 | 0.118366E+10 | 744.00 | 0.536153E+10 | 98525918.36 | 0.00 | 0.46 | 31-MAY-24:00 | 0.20 | 13-MAY-06:20 | 3806.76 | 31-MAY-24:00 | 3787.84 | 31-MAY-24:00 | 207.81 | 05-MAY-15:30 | 767.81 | 31-MAY-24:00 | 0.00 |
June | 0.105143E+11 | 0.221787E+10 | 720.00 | 0.103202E+11 | 0.194156E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.43 | 01-JUN-06:10 | 5841.37 | 30-JUN-24:00 | 5836.77 | 30-JUN-24:00 | 295.99 | 28-JUN-13:05 | 1145.31 | 29-JUN-11:00 | 0.00 |
July | 0.161703E+11 | 0.353105E+10 | 744.00 | 0.158857E+11 | 0.284630E+09 | 0.00 | 0.89 | 31-JUL-24:00 | 0.66 | 07-JUL-21:00 | 7749.57 | 31-JUL-24:00 | 7749.57 | 31-JUL-24:00 | 358.72 | 28-JUL-14:00 | 1823.14 | 31-JUL-11:50 | 0.00 |
August | 0.211971E+11 | 0.474059E+10 | 744.00 | 0.208787E+11 | 0.318376E+09 | 0.00 | 1.00 | 17-AUG-14:20 | 0.31 | 31-AUG-24:00 | 8600.74 | 06-AUG-18:05 | 8589.78 | 06-AUG-17:41 | 365.95 | 18-AUG-16:00 | 2351.81 | 17-AUG-14:00 | 0.00 |
September | 0.559105E+10 | 0.125173E+10 | 720.00 | 0.541139E+10 | 0.179658E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.22 | 20-SEP-06:20 | 4002.84 | 30-SEP-24:00 | 4002.84 | 30-SEP-24:00 | 323.87 | 22-SEP-10:50 | 917.29 | 29-SEP-13:00 | 0.00 |
October | 0.108294E+11 | 0.242532E+10 | 744.00 | 0.107018E+11 | 0.127603E+09 | 0.00 | 0.67 | 31-OCT-24:00 | 0.43 | 28-OCT-06:23 | 5818.29 | 31-OCT-24:00 | 5811.26 | 31-OCT-24:00 | 358.69 | 05-OCT-16:00 | 1694.04 | 16-OCT-11:00 | 0.00 |
November | 0.151034E+11 | 0.303849E+10 | 720.00 | 0.150288E+11 | 74613393.31 | 0.00 | 0.82 | 28-NOV-14:00 | 0.63 | 18-NOV-07:30 | 6529.66 | 12-NOV-16:15 | 6496.87 | 12-NOV-16:20 | 274.87 | 10-NOV-17:10 | 1726.55 | 28-NOV-14:00 | 0.00 |
December | 0.205640E+11 | 0.410752E+10 | 744.00 | 0.205311E+11 | 32859251.87 | 0.00 | 1.00 | 18-DEC-13:40 | 0.82 | 23-DEC-07:05 | 8508.42 | 25-DEC-16:15 | 8508.42 | 25-DEC-16:20 | 242.41 | 07-DEC-17:00 | 2207.27 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.155326E+12 | 0.325589E+11 | 8760.00 | 0.153689E+12 | 0.163705E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.507486E+10 | 0.112551E+10 | 672.00 | 0.503290E+10 | 32859251.87 | 0.00 | 0.33 | 0.17 | 2422.36 | 2422.36 | 170.12 | 625.94 | 0.00 | ||||||
Maximum of Months | 0.211971E+11 | 0.474059E+10 | 744.00 | 0.208787E+11 | 0.318376E+09 | 0.00 | 1.00 | 0.82 | 8600.74 | 8589.78 | 365.95 | 2351.81 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.380616E+11 | 0.861391E+10 | 744.00 | 0.376547E+11 | 0.406839E+09 | 0.00 | 0.30 | 15-JAN-16:15 | 0.07 | 03-JAN-07:05 | 22110.41 | 18-JAN-16:20 | 21217.27 | 18-JAN-16:10 | 1611.67 | 20-JAN-16:20 | 5501.82 | 24-JAN-15:50 | 0.00 |
February | 0.800006E+11 | 0.166186E+11 | 672.00 | 0.793982E+11 | 0.602431E+09 | 0.00 | 0.55 | 03-FEB-15:00 | 0.34 | 25-FEB-18:00 | 41476.68 | 20-FEB-17:10 | 41273.62 | 20-FEB-17:10 | 2139.71 | 01-FEB-16:30 | 10331.16 | 01-FEB-12:00 | 0.00 |
March | 0.138710E+12 | 0.275789E+11 | 744.00 | 0.137757E+12 | 0.953084E+09 | 0.00 | 0.81 | 31-MAR-23:30 | 0.55 | 30-MAR-06:05 | 67688.84 | 31-MAR-23:30 | 67688.84 | 31-MAR-23:30 | 2624.20 | 23-MAR-16:10 | 14310.02 | 23-MAR-14:00 | 0.00 |
April | 0.187146E+12 | 0.372223E+11 | 720.00 | 0.185876E+12 | 0.127026E+10 | 0.00 | 0.96 | 26-APR-13:40 | 0.26 | 30-APR-24:00 | 78725.05 | 16-APR-17:23 | 78651.29 | 30-APR-17:27 | 2422.70 | 13-APR-16:00 | 21014.78 | 26-APR-13:00 | 0.00 |
May | 0.471874E+11 | 0.103148E+11 | 744.00 | 0.462231E+11 | 0.964270E+09 | 0.00 | 0.44 | 31-MAY-23:50 | 0.15 | 13-MAY-06:20 | 34610.74 | 31-MAY-23:30 | 34357.82 | 31-MAY-24:00 | 2042.13 | 05-MAY-15:30 | 7008.81 | 31-MAY-23:50 | 0.00 |
June | 0.968099E+11 | 0.205061E+11 | 720.00 | 0.948894E+11 | 0.192053E+10 | 0.00 | 0.67 | 30-JUN-24:00 | 0.41 | 01-JUN-06:10 | 55196.19 | 30-JUN-24:00 | 55145.59 | 30-JUN-24:00 | 2931.77 | 28-JUN-13:05 | 10786.84 | 29-JUN-11:00 | 0.00 |
July | 0.152187E+12 | 0.333072E+11 | 744.00 | 0.149361E+12 | 0.282583E+10 | 0.00 | 0.88 | 31-JUL-24:00 | 0.64 | 08-JUL-06:40 | 73708.11 | 31-JUL-24:00 | 73708.11 | 31-JUL-24:00 | 3565.60 | 28-JUL-14:00 | 17350.58 | 31-JUL-11:50 | 0.00 |
August | 0.200436E+12 | 0.449017E+11 | 744.00 | 0.197262E+12 | 0.317391E+10 | 0.00 | 1.00 | 17-AUG-14:20 | 0.26 | 31-AUG-24:00 | 80079.14 | 17-AUG-16:00 | 79761.28 | 06-AUG-17:56 | 3638.40 | 18-AUG-16:00 | 22378.96 | 17-AUG-14:00 | 0.00 |
September | 0.493961E+11 | 0.111413E+11 | 720.00 | 0.476326E+11 | 0.176354E+10 | 0.00 | 0.48 | 30-SEP-24:00 | 0.18 | 20-SEP-06:30 | 37901.37 | 30-SEP-24:00 | 37901.37 | 30-SEP-24:00 | 3183.84 | 22-SEP-11:00 | 8600.16 | 29-SEP-13:00 | 0.00 |
October | 0.985416E+11 | 0.222115E+11 | 744.00 | 0.972793E+11 | 0.126228E+10 | 0.00 | 0.66 | 31-OCT-24:00 | 0.39 | 28-OCT-06:45 | 54002.81 | 31-OCT-23:50 | 53922.45 | 31-OCT-24:00 | 3538.36 | 05-OCT-16:00 | 15997.67 | 16-OCT-11:00 | 0.00 |
November | 0.136290E+12 | 0.276172E+11 | 720.00 | 0.135551E+12 | 0.739004E+09 | 0.00 | 0.80 | 28-NOV-14:00 | 0.58 | 18-NOV-07:30 | 60254.74 | 10-NOV-16:20 | 58960.27 | 12-NOV-16:25 | 2724.60 | 10-NOV-17:10 | 16244.27 | 28-NOV-14:00 | 0.00 |
December | 0.186956E+12 | 0.376368E+11 | 744.00 | 0.186626E+12 | 0.329508E+09 | 0.00 | 1.00 | 19-DEC-10:05 | 0.76 | 13-DEC-07:05 | 78218.29 | 07-DEC-16:10 | 76716.07 | 19-DEC-16:30 | 2403.30 | 07-DEC-17:00 | 21084.96 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.141172E+13 | 0.297670E+12 | 8760.00 | 0.139551E+13 | 0.162115E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.380616E+11 | 0.861391E+10 | 672.00 | 0.376547E+11 | 0.329508E+09 | 0.00 | 0.30 | 0.07 | 22110.41 | 21217.27 | 1611.67 | 5501.82 | 0.00 | ||||||
Maximum of Months | 0.200436E+12 | 0.449017E+11 | 744.00 | 0.197262E+12 | 0.317391E+10 | 0.00 | 1.00 | 0.76 | 80079.14 | 79761.28 | 3638.40 | 22378.96 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.258028E+10 | 0.600778E+09 | 688.17 | 0.254091E+10 | 39368663.05 | 0.00 | 0.30 | 18-JAN-16:10 | 0.00 | 01-JAN-00:05 | 2233.97 | 18-JAN-16:10 | 2144.71 | 18-JAN-16:10 | 161.66 | 20-JAN-16:20 | 549.53 | 24-JAN-16:00 | 0.00 |
February | 0.699281E+10 | 0.147142E+10 | 672.00 | 0.693340E+10 | 59410190.19 | 0.00 | 0.54 | 03-FEB-15:00 | 0.24 | 26-FEB-07:10 | 4132.16 | 01-FEB-16:50 | 3978.82 | 22-FEB-17:00 | 213.87 | 01-FEB-16:30 | 1021.81 | 03-FEB-15:00 | 0.00 |
March | 0.129630E+11 | 0.260183E+10 | 744.00 | 0.128682E+11 | 94804472.93 | 0.00 | 0.76 | 31-MAR-23:20 | 0.45 | 30-MAR-06:05 | 6396.63 | 31-MAR-23:20 | 6396.63 | 31-MAR-23:20 | 262.96 | 23-MAR-16:10 | 1447.02 | 23-MAR-14:00 | 0.00 |
April | 0.182629E+11 | 0.365560E+10 | 720.00 | 0.181360E+11 | 0.126850E+09 | 0.00 | 0.96 | 26-APR-13:30 | 0.24 | 30-APR-24:00 | 7917.66 | 30-APR-17:27 | 7917.66 | 30-APR-17:30 | 242.50 | 13-APR-16:00 | 2124.55 | 26-APR-13:00 | 0.00 |
May | 0.426672E+10 | 0.941932E+09 | 744.00 | 0.417099E+10 | 95730640.20 | 0.00 | 0.41 | 31-MAY-23:20 | 0.07 | 13-MAY-06:10 | 3234.40 | 31-MAY-23:20 | 3189.30 | 31-MAY-23:40 | 202.22 | 05-MAY-15:30 | 659.24 | 31-MAY-23:20 | 0.00 |
June | 0.948980E+10 | 0.201975E+10 | 720.00 | 0.929759E+10 | 0.192207E+09 | 0.00 | 0.65 | 30-JUN-23:50 | 0.35 | 01-JUN-06:10 | 5410.54 | 30-JUN-23:40 | 5403.99 | 30-JUN-24:00 | 295.45 | 28-JUN-13:05 | 1095.57 | 29-JUN-11:00 | 0.00 |
July | 0.151521E+11 | 0.332880E+10 | 744.00 | 0.148695E+11 | 0.282581E+09 | 0.00 | 0.86 | 31-JUL-23:50 | 0.60 | 06-JUL-06:10 | 7279.15 | 31-JUL-24:00 | 7279.15 | 31-JUL-24:00 | 357.04 | 28-JUL-14:00 | 1760.77 | 19-JUL-15:00 | 0.00 |
August | 0.199438E+11 | 0.448500E+10 | 744.00 | 0.196266E+11 | 0.317215E+09 | 0.00 | 0.99 | 17-AUG-14:30 | 0.23 | 31-AUG-24:00 | 8125.99 | 06-AUG-17:47 | 8123.42 | 06-AUG-17:47 | 364.30 | 18-AUG-16:00 | 2262.25 | 17-AUG-14:00 | 0.00 |
September | 0.465753E+10 | 0.105985E+10 | 720.00 | 0.448167E+10 | 0.175859E+09 | 0.00 | 0.47 | 30-SEP-24:00 | 0.12 | 20-SEP-06:30 | 3766.04 | 30-SEP-23:50 | 3766.04 | 30-SEP-23:50 | 320.02 | 22-SEP-13:00 | 897.68 | 29-SEP-13:00 | 0.00 |
October | 0.940594E+10 | 0.213967E+10 | 744.00 | 0.928005E+10 | 0.125896E+09 | 0.00 | 0.65 | 15-OCT-16:31 | 0.30 | 30-OCT-06:20 | 5196.91 | 31-OCT-23:30 | 5182.99 | 31-OCT-23:30 | 354.11 | 05-OCT-16:00 | 1623.46 | 16-OCT-11:00 | 0.00 |
November | 0.127172E+11 | 0.260273E+10 | 720.00 | 0.126437E+11 | 73477526.79 | 0.00 | 0.79 | 28-NOV-14:00 | 0.47 | 27-NOV-07:05 | 6046.02 | 10-NOV-16:20 | 5809.43 | 07-NOV-16:20 | 272.00 | 10-NOV-17:10 | 1624.24 | 28-NOV-14:00 | 0.00 |
December | 0.175062E+11 | 0.356659E+10 | 744.00 | 0.174735E+11 | 32698575.16 | 0.00 | 1.00 | 19-DEC-12:30 | 0.65 | 26-DEC-07:05 | 7822.33 | 07-DEC-16:10 | 7670.62 | 19-DEC-16:10 | 240.26 | 07-DEC-17:00 | 2142.72 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.133938E+12 | 0.284740E+11 | 8704.17 | 0.132322E+12 | 0.161610E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.258028E+10 | 0.600778E+09 | 672.00 | 0.254091E+10 | 32698575.16 | 0.00 | 0.30 | 0.00 | 2233.97 | 2144.71 | 161.66 | 549.53 | 0.00 | ||||||
Maximum of Months | 0.199438E+11 | 0.448500E+10 | 744.00 | 0.196266E+11 | 0.317215E+09 | 0.00 | 1.00 | 0.65 | 8125.99 | 8123.42 | 364.30 | 2262.25 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 52.40 | 433.07 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 65.05 | 395.51 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 99.19 | 401.57 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 144.70 | 315.59 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 191.47 | 265.29 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 248.73 | 209.66 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.98 | 185.63 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.71 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 161.12 | 238.24 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 135.95 | 271.32 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 62.15 | 398.77 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 43.19 | 447.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 139.84 | 312.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 43.19 | 185.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.98 | 447.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 52.40 | 433.07 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 65.05 | 395.51 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 99.19 | 401.57 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 144.70 | 315.59 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 191.47 | 265.29 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 248.73 | 209.66 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.98 | 185.63 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.71 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 161.12 | 238.24 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 135.95 | 271.32 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 62.15 | 398.77 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 43.19 | 447.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 139.84 | 312.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 43.19 | 185.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.98 | 447.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 52.40 | 433.07 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 65.05 | 395.51 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 99.19 | 401.57 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 144.70 | 315.59 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 191.47 | 265.29 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 248.73 | 209.66 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.98 | 185.63 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.71 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 161.12 | 238.24 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 135.95 | 271.32 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 62.15 | 398.77 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 43.19 | 447.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 139.84 | 312.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 43.19 | 185.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.98 | 447.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 52.40 | 433.07 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 65.05 | 395.51 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 99.19 | 401.57 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 144.70 | 315.59 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 191.47 | 265.29 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 248.73 | 209.66 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.98 | 185.63 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.71 | 194.56 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 161.12 | 238.24 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 135.95 | 271.32 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 62.15 | 398.77 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 43.19 | 447.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 139.84 | 312.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 43.19 | 185.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.98 | 447.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 52.40 | 433.05 | 0.00 | 0.00 | 0.00 |
February | 130.00 | 0.00 | 130.00 | 65.05 | 395.49 | 0.00 | 0.00 | 0.00 |
March | 159.31 | 0.00 | 159.31 | 99.19 | 401.56 | 0.00 | 0.00 | 0.00 |
April | 183.54 | 0.71 | 182.84 | 144.70 | 315.58 | 0.00 | 0.00 | 0.00 |
May | 220.56 | 10.27 | 210.29 | 191.47 | 265.28 | 0.00 | 0.00 | 0.00 |
June | 235.02 | 22.98 | 212.04 | 248.72 | 209.65 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.87 | 260.97 | 185.62 | 0.00 | 0.00 | 0.00 |
August | 184.80 | 3.70 | 181.10 | 207.70 | 194.55 | 0.00 | 0.00 | 0.00 |
September | 156.41 | 0.02 | 156.39 | 161.12 | 238.23 | 0.00 | 0.00 | 0.00 |
October | 124.07 | 0.00 | 124.07 | 135.95 | 271.31 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 62.15 | 398.75 | 0.00 | 0.00 | 0.00 |
December | 96.41 | 0.00 | 96.41 | 43.19 | 447.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.84 | 4.72 | 156.13 | 139.83 | 312.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.41 | 0.00 | 96.41 | 43.19 | 185.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.02 | 22.98 | 212.04 | 260.97 | 447.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.41 | 166.02 | 144.40 | 357.84 | 446.68 | 0.00 | 0.00 | 0.00 |
February | 327.45 | 150.01 | 177.44 | 355.39 | 407.88 | 0.00 | 0.00 | 0.00 |
March | 397.76 | 177.22 | 220.54 | 455.08 | 411.32 | 0.00 | 0.00 | 0.00 |
April | 508.53 | 255.04 | 253.49 | 671.58 | 330.74 | 0.00 | 0.00 | 0.00 |
May | 479.91 | 200.28 | 279.63 | 609.24 | 299.28 | 0.00 | 0.00 | 0.00 |
June | 476.92 | 206.93 | 269.99 | 651.58 | 238.48 | 0.00 | 0.00 | 0.00 |
July | 540.39 | 268.53 | 271.85 | 797.13 | 210.81 | 0.00 | 0.00 | 0.00 |
August | 533.68 | 283.47 | 250.21 | 798.47 | 211.87 | 0.00 | 0.00 | 0.00 |
September | 388.56 | 178.05 | 210.51 | 546.06 | 256.74 | 0.00 | 0.00 | 0.00 |
October | 343.95 | 176.78 | 167.17 | 491.12 | 283.85 | 0.00 | 0.00 | 0.00 |
November | 313.55 | 159.29 | 154.25 | 364.08 | 407.17 | 0.00 | 0.00 | 0.00 |
December | 299.12 | 166.19 | 132.93 | 343.35 | 448.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 410.57 | 199.38 | 211.19 | 538.00 | 329.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.12 | 150.01 | 132.93 | 343.35 | 210.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.39 | 283.47 | 279.63 | 798.47 | 448.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.41 | 166.02 | 144.40 | 357.84 | 446.68 | 0.00 | 0.00 | 0.00 |
February | 327.45 | 150.01 | 177.44 | 355.39 | 407.88 | 0.00 | 0.00 | 0.00 |
March | 397.76 | 177.22 | 220.54 | 455.08 | 411.32 | 0.00 | 0.00 | 0.00 |
April | 508.53 | 255.04 | 253.49 | 671.58 | 330.74 | 0.00 | 0.00 | 0.00 |
May | 479.91 | 200.28 | 279.63 | 609.24 | 299.28 | 0.00 | 0.00 | 0.00 |
June | 476.92 | 206.93 | 269.99 | 651.58 | 238.48 | 0.00 | 0.00 | 0.00 |
July | 540.39 | 268.53 | 271.85 | 797.13 | 210.81 | 0.00 | 0.00 | 0.00 |
August | 533.68 | 283.47 | 250.21 | 798.47 | 211.87 | 0.00 | 0.00 | 0.00 |
September | 388.56 | 178.05 | 210.51 | 546.06 | 256.74 | 0.00 | 0.00 | 0.00 |
October | 343.95 | 176.78 | 167.17 | 491.12 | 283.85 | 0.00 | 0.00 | 0.00 |
November | 313.55 | 159.29 | 154.25 | 364.08 | 407.17 | 0.00 | 0.00 | 0.00 |
December | 299.12 | 166.19 | 132.93 | 343.35 | 448.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 410.57 | 199.38 | 211.19 | 538.00 | 329.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.12 | 150.01 | 132.93 | 343.35 | 210.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.39 | 283.47 | 279.63 | 798.47 | 448.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.41 | 166.01 | 144.39 | 357.83 | 446.68 | 0.00 | 0.00 | 0.00 |
February | 327.45 | 150.01 | 177.44 | 355.38 | 407.87 | 0.00 | 0.00 | 0.00 |
March | 397.75 | 177.22 | 220.54 | 455.08 | 411.31 | 0.00 | 0.00 | 0.00 |
April | 508.52 | 255.03 | 253.49 | 671.57 | 330.73 | 0.00 | 0.00 | 0.00 |
May | 479.90 | 200.27 | 279.63 | 609.23 | 299.27 | 0.00 | 0.00 | 0.00 |
June | 476.91 | 206.92 | 269.99 | 651.57 | 238.48 | 0.00 | 0.00 | 0.00 |
July | 540.38 | 268.53 | 271.85 | 797.12 | 210.81 | 0.00 | 0.00 | 0.00 |
August | 533.67 | 283.47 | 250.20 | 798.45 | 211.86 | 0.00 | 0.00 | 0.00 |
September | 388.55 | 178.05 | 210.50 | 546.05 | 256.73 | 0.00 | 0.00 | 0.00 |
October | 343.94 | 176.78 | 167.16 | 491.11 | 283.84 | 0.00 | 0.00 | 0.00 |
November | 313.54 | 159.29 | 154.25 | 364.07 | 407.16 | 0.00 | 0.00 | 0.00 |
December | 299.11 | 166.19 | 132.92 | 343.34 | 448.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 410.56 | 199.37 | 211.19 | 537.99 | 329.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.11 | 150.01 | 132.92 | 343.34 | 210.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.38 | 283.47 | 279.63 | 798.45 | 448.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 987.19 | 401.21 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 729.05 | 369.67 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 570.18 | 386.41 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 509.45 | 322.10 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 293.82 | 284.10 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 257.58 | 224.26 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 319.29 | 197.73 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 476.23 | 205.98 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 667.01 | 243.04 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.44 | 848.10 | 265.94 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 941.77 | 372.31 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 637.86 | 306.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 257.58 | 197.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 987.19 | 401.21 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 729.05 | 369.67 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 570.18 | 386.41 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 509.45 | 322.10 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 293.82 | 284.10 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 257.58 | 224.26 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 319.29 | 197.73 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 476.23 | 205.98 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 667.01 | 243.04 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.43 | 848.10 | 265.94 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 941.76 | 372.31 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 637.86 | 306.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 257.58 | 197.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 987.19 | 401.21 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 729.05 | 369.67 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 570.18 | 386.41 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 509.45 | 322.10 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 293.82 | 284.10 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 257.58 | 224.26 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 319.29 | 197.73 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 476.23 | 205.98 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 667.01 | 243.04 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.44 | 848.10 | 265.94 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 941.77 | 372.31 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 637.86 | 306.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 257.58 | 197.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 987.19 | 401.21 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 729.05 | 369.67 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 570.18 | 386.41 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 509.45 | 322.10 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 293.82 | 284.10 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 257.58 | 224.26 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 319.29 | 197.73 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 476.23 | 205.98 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 667.01 | 243.04 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.43 | 848.10 | 265.94 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 941.76 | 372.31 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 637.86 | 306.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 257.58 | 197.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1057.81 | 409.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.47 | 501.36 | 182.11 | 987.15 | 401.19 | 0.00 | 0.00 | 0.00 |
February | 537.17 | 330.87 | 206.30 | 729.02 | 369.66 | 0.00 | 0.00 | 0.00 |
March | 428.25 | 206.86 | 221.39 | 570.15 | 386.39 | 0.00 | 0.00 | 0.00 |
April | 357.81 | 136.44 | 221.38 | 509.43 | 322.08 | 0.00 | 0.00 | 0.00 |
May | 254.79 | 31.36 | 223.44 | 293.81 | 284.09 | 0.00 | 0.00 | 0.00 |
June | 223.52 | 13.50 | 210.02 | 257.57 | 224.25 | 0.00 | 0.00 | 0.00 |
July | 236.77 | 26.65 | 210.11 | 319.28 | 197.72 | 0.00 | 0.00 | 0.00 |
August | 304.18 | 95.95 | 208.23 | 476.21 | 205.97 | 0.00 | 0.00 | 0.00 |
September | 423.26 | 214.48 | 208.78 | 666.99 | 243.03 | 0.00 | 0.00 | 0.00 |
October | 538.29 | 359.86 | 178.43 | 848.07 | 265.93 | 0.00 | 0.00 | 0.00 |
November | 654.24 | 461.88 | 192.36 | 941.73 | 372.29 | 0.00 | 0.00 | 0.00 |
December | 730.16 | 555.75 | 174.41 | 1057.77 | 409.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.28 | 244.29 | 203.00 | 637.84 | 306.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.52 | 13.50 | 174.41 | 257.57 | 197.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.16 | 555.75 | 223.44 | 1057.77 | 409.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.46 | 149.02 | 146.44 | 350.12 | 505.63 | 0.00 | 0.00 | 0.00 |
February | 352.48 | 162.72 | 189.76 | 397.02 | 477.54 | 0.00 | 0.00 | 0.00 |
March | 404.04 | 178.75 | 225.29 | 460.85 | 489.30 | 0.00 | 0.00 | 0.00 |
April | 556.99 | 290.03 | 266.97 | 731.54 | 407.67 | 0.00 | 0.00 | 0.00 |
May | 547.14 | 252.72 | 294.42 | 709.54 | 339.15 | 0.00 | 0.00 | 0.00 |
June | 579.64 | 289.81 | 289.83 | 795.10 | 278.34 | 0.00 | 0.00 | 0.00 |
July | 613.59 | 328.33 | 285.26 | 886.12 | 255.90 | 0.00 | 0.00 | 0.00 |
August | 575.67 | 311.99 | 263.68 | 839.95 | 271.87 | 0.00 | 0.00 | 0.00 |
September | 492.88 | 263.73 | 229.15 | 703.40 | 291.61 | 0.00 | 0.00 | 0.00 |
October | 376.78 | 205.71 | 171.08 | 541.27 | 337.17 | 0.00 | 0.00 | 0.00 |
November | 340.35 | 178.03 | 162.32 | 411.29 | 486.06 | 0.00 | 0.00 | 0.00 |
December | 300.59 | 161.22 | 139.37 | 354.08 | 551.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.36 | 231.30 | 222.06 | 599.33 | 390.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 295.46 | 149.02 | 139.37 | 350.12 | 255.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.59 | 328.33 | 294.42 | 886.12 | 551.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.46 | 149.02 | 146.44 | 350.12 | 505.63 | 0.00 | 0.00 | 0.00 |
February | 352.48 | 162.72 | 189.76 | 397.02 | 477.54 | 0.00 | 0.00 | 0.00 |
March | 404.04 | 178.75 | 225.29 | 460.85 | 489.30 | 0.00 | 0.00 | 0.00 |
April | 556.99 | 290.03 | 266.97 | 731.54 | 407.67 | 0.00 | 0.00 | 0.00 |
May | 547.14 | 252.72 | 294.42 | 709.54 | 339.15 | 0.00 | 0.00 | 0.00 |
June | 579.64 | 289.81 | 289.83 | 795.10 | 278.34 | 0.00 | 0.00 | 0.00 |
July | 613.59 | 328.33 | 285.26 | 886.12 | 255.90 | 0.00 | 0.00 | 0.00 |
August | 575.67 | 311.99 | 263.68 | 839.95 | 271.87 | 0.00 | 0.00 | 0.00 |
September | 492.88 | 263.73 | 229.15 | 703.40 | 291.61 | 0.00 | 0.00 | 0.00 |
October | 376.78 | 205.71 | 171.08 | 541.27 | 337.17 | 0.00 | 0.00 | 0.00 |
November | 340.35 | 178.03 | 162.32 | 411.29 | 486.06 | 0.00 | 0.00 | 0.00 |
December | 300.59 | 161.22 | 139.37 | 354.08 | 551.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.36 | 231.30 | 222.06 | 599.33 | 390.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 295.46 | 149.02 | 139.37 | 350.12 | 255.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.59 | 328.33 | 294.42 | 886.12 | 551.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.45 | 149.01 | 146.44 | 350.11 | 505.62 | 0.00 | 0.00 | 0.00 |
February | 352.48 | 162.72 | 189.76 | 397.02 | 477.53 | 0.00 | 0.00 | 0.00 |
March | 404.03 | 178.75 | 225.28 | 460.84 | 489.29 | 0.00 | 0.00 | 0.00 |
April | 556.98 | 290.02 | 266.96 | 731.53 | 407.66 | 0.00 | 0.00 | 0.00 |
May | 547.13 | 252.72 | 294.41 | 709.53 | 339.14 | 0.00 | 0.00 | 0.00 |
June | 579.63 | 289.80 | 289.82 | 795.08 | 278.34 | 0.00 | 0.00 | 0.00 |
July | 613.58 | 328.32 | 285.26 | 886.10 | 255.89 | 0.00 | 0.00 | 0.00 |
August | 575.66 | 311.98 | 263.68 | 839.94 | 271.86 | 0.00 | 0.00 | 0.00 |
September | 492.87 | 263.73 | 229.14 | 703.38 | 291.61 | 0.00 | 0.00 | 0.00 |
October | 376.78 | 205.70 | 171.07 | 541.26 | 337.16 | 0.00 | 0.00 | 0.00 |
November | 340.34 | 178.02 | 162.32 | 411.29 | 486.05 | 0.00 | 0.00 | 0.00 |
December | 300.58 | 161.22 | 139.36 | 354.07 | 551.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.35 | 231.29 | 222.06 | 599.32 | 390.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 295.45 | 149.01 | 139.36 | 350.11 | 255.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.58 | 328.32 | 294.41 | 886.10 | 551.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.85 | 0.00 | 517.85 | 324.38 | 1929.55 | 0.00 | 0.00 | 0.00 |
February | 650.04 | 0.00 | 650.04 | 386.17 | 1754.07 | 0.00 | 0.00 | 0.00 |
March | 796.57 | 0.00 | 796.57 | 559.85 | 1797.62 | 0.00 | 0.00 | 0.00 |
April | 917.74 | 3.53 | 914.21 | 783.29 | 1423.79 | 0.00 | 0.00 | 0.00 |
May | 1102.84 | 51.35 | 1051.48 | 992.82 | 1250.90 | 0.00 | 0.00 | 0.00 |
June | 1175.13 | 114.89 | 1060.24 | 1264.92 | 986.88 | 0.00 | 0.00 | 0.00 |
July | 1112.66 | 93.26 | 1019.40 | 1334.42 | 878.84 | 0.00 | 0.00 | 0.00 |
August | 924.03 | 18.50 | 905.52 | 1072.90 | 918.42 | 0.00 | 0.00 | 0.00 |
September | 782.09 | 0.12 | 781.97 | 831.00 | 1108.28 | 0.00 | 0.00 | 0.00 |
October | 620.38 | 0.00 | 620.38 | 719.78 | 1239.12 | 0.00 | 0.00 | 0.00 |
November | 561.71 | 0.00 | 561.71 | 373.91 | 1768.45 | 0.00 | 0.00 | 0.00 |
December | 482.07 | 0.00 | 482.07 | 292.93 | 1946.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 804.25 | 23.60 | 780.65 | 746.89 | 1415.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 482.07 | 0.00 | 482.07 | 292.93 | 878.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1175.13 | 114.89 | 1060.24 | 1334.42 | 1946.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 931.23 | 498.04 | 433.19 | 1089.12 | 1251.11 | 0.00 | 0.00 | 0.00 |
February | 982.35 | 450.02 | 532.33 | 1076.18 | 1140.57 | 0.00 | 0.00 | 0.00 |
March | 1193.27 | 531.66 | 661.61 | 1369.88 | 1166.42 | 0.00 | 0.00 | 0.00 |
April | 1525.58 | 765.11 | 760.47 | 2003.93 | 954.21 | 0.00 | 0.00 | 0.00 |
May | 1439.71 | 600.83 | 838.89 | 1812.11 | 871.27 | 0.00 | 0.00 | 0.00 |
June | 1430.75 | 620.78 | 809.97 | 1936.09 | 696.92 | 0.00 | 0.00 | 0.00 |
July | 1621.15 | 805.59 | 815.56 | 2367.89 | 629.00 | 0.00 | 0.00 | 0.00 |
August | 1601.02 | 850.41 | 750.61 | 2369.93 | 641.67 | 0.00 | 0.00 | 0.00 |
September | 1165.67 | 534.15 | 631.51 | 1627.27 | 743.43 | 0.00 | 0.00 | 0.00 |
October | 1031.83 | 530.33 | 501.49 | 1466.47 | 818.03 | 0.00 | 0.00 | 0.00 |
November | 940.63 | 477.88 | 462.75 | 1101.08 | 1149.32 | 0.00 | 0.00 | 0.00 |
December | 897.35 | 498.57 | 398.77 | 1048.04 | 1256.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1231.69 | 598.13 | 633.56 | 1609.35 | 942.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 897.35 | 450.02 | 398.77 | 1048.04 | 629.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1621.15 | 850.41 | 838.89 | 2369.93 | 1256.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3417.44 | 2506.85 | 910.59 | 4907.62 | 1969.99 | 0.00 | 0.00 | 0.00 |
February | 2685.93 | 1654.39 | 1031.54 | 3619.73 | 1785.19 | 0.00 | 0.00 | 0.00 |
March | 2141.31 | 1034.35 | 1106.96 | 2844.46 | 1849.84 | 0.00 | 0.00 | 0.00 |
April | 1789.12 | 682.21 | 1106.91 | 2548.21 | 1532.16 | 0.00 | 0.00 | 0.00 |
May | 1273.99 | 156.78 | 1117.21 | 1467.96 | 1374.31 | 0.00 | 0.00 | 0.00 |
June | 1117.63 | 67.48 | 1050.15 | 1297.70 | 1069.73 | 0.00 | 0.00 | 0.00 |
July | 1183.87 | 133.27 | 1050.60 | 1610.95 | 947.34 | 0.00 | 0.00 | 0.00 |
August | 1520.92 | 479.75 | 1041.18 | 2382.82 | 1001.64 | 0.00 | 0.00 | 0.00 |
September | 2116.36 | 1072.44 | 1043.93 | 3310.83 | 1190.18 | 0.00 | 0.00 | 0.00 |
October | 2691.52 | 1799.36 | 892.16 | 4211.48 | 1302.54 | 0.00 | 0.00 | 0.00 |
November | 3271.27 | 2309.47 | 961.80 | 4680.59 | 1805.79 | 0.00 | 0.00 | 0.00 |
December | 3650.92 | 2778.83 | 872.09 | 5264.33 | 1979.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2236.49 | 1221.47 | 1015.02 | 3177.67 | 1482.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1117.63 | 67.48 | 872.09 | 1297.70 | 947.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3650.92 | 2778.83 | 1117.21 | 5264.33 | 1979.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 886.37 | 447.04 | 439.32 | 1086.26 | 1347.13 | 0.00 | 0.00 | 0.00 |
February | 1057.44 | 488.16 | 569.28 | 1231.27 | 1234.30 | 0.00 | 0.00 | 0.00 |
March | 1212.11 | 536.26 | 675.85 | 1431.41 | 1257.75 | 0.00 | 0.00 | 0.00 |
April | 1670.96 | 870.07 | 800.89 | 2241.99 | 1054.02 | 0.00 | 0.00 | 0.00 |
May | 1641.41 | 758.16 | 883.25 | 2135.52 | 947.44 | 0.00 | 0.00 | 0.00 |
June | 1738.89 | 869.41 | 869.48 | 2400.74 | 750.56 | 0.00 | 0.00 | 0.00 |
July | 1840.76 | 984.97 | 855.78 | 2687.19 | 682.81 | 0.00 | 0.00 | 0.00 |
August | 1726.99 | 935.96 | 791.03 | 2558.02 | 708.12 | 0.00 | 0.00 | 0.00 |
September | 1478.62 | 791.19 | 687.43 | 2115.89 | 807.22 | 0.00 | 0.00 | 0.00 |
October | 1130.34 | 617.12 | 513.22 | 1652.91 | 895.66 | 0.00 | 0.00 | 0.00 |
November | 1021.03 | 534.07 | 486.96 | 1281.38 | 1242.73 | 0.00 | 0.00 | 0.00 |
December | 901.75 | 483.66 | 418.09 | 1122.72 | 1372.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1360.07 | 693.89 | 666.18 | 1831.70 | 1023.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 886.37 | 447.04 | 418.09 | 1086.26 | 682.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1840.76 | 984.97 | 883.25 | 2687.19 | 1372.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.85 | 0.00 | 517.85 | 380.26 | 1738.22 | 0.00 | 0.00 | 0.00 |
February | 650.04 | 0.00 | 650.04 | 441.66 | 1578.59 | 0.00 | 0.00 | 0.00 |
March | 796.57 | 0.00 | 796.57 | 608.56 | 1658.66 | 0.00 | 0.00 | 0.00 |
April | 917.74 | 3.53 | 914.21 | 806.30 | 1345.54 | 0.00 | 0.00 | 0.00 |
May | 1102.84 | 51.35 | 1051.48 | 1021.59 | 1188.62 | 0.00 | 0.00 | 0.00 |
June | 1175.13 | 114.89 | 1060.24 | 1263.26 | 955.49 | 0.00 | 0.00 | 0.00 |
July | 1112.66 | 93.26 | 1019.40 | 1318.09 | 861.85 | 0.00 | 0.00 | 0.00 |
August | 924.03 | 18.50 | 905.52 | 1063.82 | 896.37 | 0.00 | 0.00 | 0.00 |
September | 782.09 | 0.12 | 781.97 | 839.04 | 1057.47 | 0.00 | 0.00 | 0.00 |
October | 620.38 | 0.00 | 620.38 | 740.61 | 1163.35 | 0.00 | 0.00 | 0.00 |
November | 561.71 | 0.00 | 561.71 | 423.74 | 1609.13 | 0.00 | 0.00 | 0.00 |
December | 482.07 | 0.00 | 482.07 | 350.12 | 1749.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 804.25 | 23.60 | 780.65 | 773.45 | 1315.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 482.07 | 0.00 | 482.07 | 350.12 | 861.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1175.13 | 114.89 | 1060.24 | 1318.09 | 1749.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 931.23 | 498.04 | 433.19 | 1137.95 | 1136.77 | 0.00 | 0.00 | 0.00 |
February | 982.35 | 450.02 | 532.33 | 1119.91 | 1036.40 | 0.00 | 0.00 | 0.00 |
March | 1193.27 | 531.66 | 661.61 | 1406.57 | 1085.72 | 0.00 | 0.00 | 0.00 |
April | 1525.58 | 765.11 | 760.47 | 2019.99 | 911.50 | 0.00 | 0.00 | 0.00 |
May | 1439.71 | 600.83 | 838.89 | 1829.72 | 834.15 | 0.00 | 0.00 | 0.00 |
June | 1430.75 | 620.78 | 809.97 | 1938.79 | 678.05 | 0.00 | 0.00 | 0.00 |
July | 1621.15 | 805.59 | 815.56 | 2361.61 | 619.68 | 0.00 | 0.00 | 0.00 |
August | 1601.02 | 850.41 | 750.61 | 2366.24 | 629.39 | 0.00 | 0.00 | 0.00 |
September | 1165.67 | 534.15 | 631.51 | 1634.54 | 713.64 | 0.00 | 0.00 | 0.00 |
October | 1031.83 | 530.33 | 501.49 | 1482.75 | 775.65 | 0.00 | 0.00 | 0.00 |
November | 940.63 | 477.88 | 462.75 | 1139.51 | 1060.72 | 0.00 | 0.00 | 0.00 |
December | 897.35 | 498.57 | 398.77 | 1097.72 | 1141.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1231.69 | 598.13 | 633.56 | 1631.51 | 884.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 897.35 | 450.02 | 398.77 | 1097.72 | 619.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1621.15 | 850.41 | 838.89 | 2366.24 | 1141.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3417.44 | 2506.85 | 910.59 | 4957.11 | 1820.12 | 0.00 | 0.00 | 0.00 |
February | 2685.93 | 1654.39 | 1031.54 | 3663.21 | 1638.56 | 0.00 | 0.00 | 0.00 |
March | 2141.31 | 1034.35 | 1106.96 | 2881.39 | 1725.11 | 0.00 | 0.00 | 0.00 |
April | 1789.12 | 682.21 | 1106.91 | 2559.58 | 1459.62 | 0.00 | 0.00 | 0.00 |
May | 1273.99 | 156.78 | 1117.21 | 1485.11 | 1306.79 | 0.00 | 0.00 | 0.00 |
June | 1117.63 | 67.48 | 1050.15 | 1295.74 | 1036.47 | 0.00 | 0.00 | 0.00 |
July | 1183.87 | 133.27 | 1050.60 | 1595.97 | 931.41 | 0.00 | 0.00 | 0.00 |
August | 1520.92 | 479.75 | 1041.18 | 2368.65 | 981.06 | 0.00 | 0.00 | 0.00 |
September | 2116.36 | 1072.44 | 1043.93 | 3307.16 | 1146.02 | 0.00 | 0.00 | 0.00 |
October | 2691.52 | 1799.36 | 892.16 | 4219.86 | 1243.95 | 0.00 | 0.00 | 0.00 |
November | 3271.27 | 2309.47 | 961.80 | 4715.03 | 1688.65 | 0.00 | 0.00 | 0.00 |
December | 3650.92 | 2778.83 | 872.09 | 5313.63 | 1836.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2236.49 | 1221.47 | 1015.02 | 3195.53 | 1399.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1117.63 | 67.48 | 872.09 | 1295.74 | 931.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3650.92 | 2778.83 | 1117.21 | 5313.63 | 1836.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 886.37 | 447.04 | 439.32 | 1111.83 | 1243.76 | 0.00 | 0.00 | 0.00 |
February | 1057.44 | 488.16 | 569.28 | 1255.83 | 1138.55 | 0.00 | 0.00 | 0.00 |
March | 1212.11 | 536.26 | 675.85 | 1449.92 | 1179.58 | 0.00 | 0.00 | 0.00 |
April | 1670.96 | 870.07 | 800.89 | 2241.87 | 1010.14 | 0.00 | 0.00 | 0.00 |
May | 1641.41 | 758.16 | 883.25 | 2135.69 | 908.92 | 0.00 | 0.00 | 0.00 |
June | 1738.89 | 869.41 | 869.48 | 2388.50 | 730.38 | 0.00 | 0.00 | 0.00 |
July | 1840.76 | 984.97 | 855.78 | 2668.70 | 670.98 | 0.00 | 0.00 | 0.00 |
August | 1726.99 | 935.96 | 791.03 | 2542.16 | 694.45 | 0.00 | 0.00 | 0.00 |
September | 1478.62 | 791.19 | 687.43 | 2109.31 | 780.14 | 0.00 | 0.00 | 0.00 |
October | 1130.34 | 617.12 | 513.22 | 1655.96 | 854.91 | 0.00 | 0.00 | 0.00 |
November | 1021.03 | 534.07 | 486.96 | 1301.17 | 1158.11 | 0.00 | 0.00 | 0.00 |
December | 901.75 | 483.66 | 418.09 | 1148.84 | 1266.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1360.07 | 693.89 | 666.18 | 1836.97 | 968.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 886.37 | 447.04 | 418.09 | 1111.83 | 670.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1840.76 | 984.97 | 883.25 | 2668.70 | 1266.84 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277405E+09 | 0.00 | 0.277405E+09 | 0.140355E+09 | 0.115993E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.157379E+09 | 0.956814E+09 |
March | 0.426713E+09 | 0.00 | 0.426713E+09 | 0.265673E+09 | 0.107558E+10 |
April | 0.475764E+09 | 1831143.67 | 0.473933E+09 | 0.375069E+09 | 0.818022E+09 |
May | 0.590774E+09 | 27509653.95 | 0.563264E+09 | 0.512843E+09 | 0.710550E+09 |
June | 0.609193E+09 | 59558836.48 | 0.549634E+09 | 0.644706E+09 | 0.543443E+09 |
July | 0.596037E+09 | 49957737.97 | 0.546079E+09 | 0.699019E+09 | 0.497180E+09 |
August | 0.494989E+09 | 9911660.66 | 0.485077E+09 | 0.556331E+09 | 0.521102E+09 |
September | 0.405442E+09 | 63548.65 | 0.405379E+09 | 0.417630E+09 | 0.617519E+09 |
October | 0.332331E+09 | 0.00 | 0.332331E+09 | 0.364138E+09 | 0.726694E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.161103E+09 | 0.103361E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.119755E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148833E+09 | 0.492377E+10 | 0.440993E+10 | 0.985799E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.497180E+09 |
Maximum of Months | 0.609193E+09 | 59558836.48 | 0.563264E+09 | 0.699019E+09 | 0.119755E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277404E+09 | 0.00 | 0.277404E+09 | 0.140355E+09 | 0.115993E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.157379E+09 | 0.956814E+09 |
March | 0.426712E+09 | 0.00 | 0.426712E+09 | 0.265673E+09 | 0.107558E+10 |
April | 0.475764E+09 | 1831141.48 | 0.473933E+09 | 0.375069E+09 | 0.818021E+09 |
May | 0.590773E+09 | 27509620.94 | 0.563264E+09 | 0.512843E+09 | 0.710549E+09 |
June | 0.609193E+09 | 59558765.02 | 0.549634E+09 | 0.644705E+09 | 0.543443E+09 |
July | 0.596036E+09 | 49957678.03 | 0.546079E+09 | 0.699019E+09 | 0.497180E+09 |
August | 0.494988E+09 | 9911648.77 | 0.485077E+09 | 0.556331E+09 | 0.521102E+09 |
September | 0.405442E+09 | 63548.58 | 0.405378E+09 | 0.417630E+09 | 0.617519E+09 |
October | 0.332330E+09 | 0.00 | 0.332330E+09 | 0.364138E+09 | 0.726694E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.161102E+09 | 0.103361E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.119755E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148832E+09 | 0.492376E+10 | 0.440992E+10 | 0.985799E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.497180E+09 |
Maximum of Months | 0.609193E+09 | 59558765.02 | 0.563264E+09 | 0.699019E+09 | 0.119755E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277405E+09 | 0.00 | 0.277405E+09 | 0.140355E+09 | 0.115993E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.157379E+09 | 0.956814E+09 |
March | 0.426713E+09 | 0.00 | 0.426713E+09 | 0.265673E+09 | 0.107558E+10 |
April | 0.475764E+09 | 1831143.67 | 0.473933E+09 | 0.375069E+09 | 0.818022E+09 |
May | 0.590774E+09 | 27509653.95 | 0.563264E+09 | 0.512843E+09 | 0.710550E+09 |
June | 0.609193E+09 | 59558836.48 | 0.549634E+09 | 0.644706E+09 | 0.543443E+09 |
July | 0.596037E+09 | 49957737.97 | 0.546079E+09 | 0.699019E+09 | 0.497180E+09 |
August | 0.494989E+09 | 9911660.66 | 0.485077E+09 | 0.556331E+09 | 0.521102E+09 |
September | 0.405442E+09 | 63548.65 | 0.405379E+09 | 0.417630E+09 | 0.617519E+09 |
October | 0.332331E+09 | 0.00 | 0.332331E+09 | 0.364138E+09 | 0.726694E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.161103E+09 | 0.103361E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.119755E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148833E+09 | 0.492377E+10 | 0.440993E+10 | 0.985799E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.497180E+09 |
Maximum of Months | 0.609193E+09 | 59558836.48 | 0.563264E+09 | 0.699019E+09 | 0.119755E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277404E+09 | 0.00 | 0.277404E+09 | 0.140355E+09 | 0.115993E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.157379E+09 | 0.956814E+09 |
March | 0.426712E+09 | 0.00 | 0.426712E+09 | 0.265673E+09 | 0.107558E+10 |
April | 0.475764E+09 | 1831141.48 | 0.473933E+09 | 0.375069E+09 | 0.818021E+09 |
May | 0.590773E+09 | 27509620.94 | 0.563264E+09 | 0.512843E+09 | 0.710549E+09 |
June | 0.609193E+09 | 59558765.02 | 0.549634E+09 | 0.644705E+09 | 0.543443E+09 |
July | 0.596036E+09 | 49957678.03 | 0.546079E+09 | 0.699019E+09 | 0.497180E+09 |
August | 0.494988E+09 | 9911648.77 | 0.485077E+09 | 0.556331E+09 | 0.521102E+09 |
September | 0.405442E+09 | 63548.58 | 0.405378E+09 | 0.417630E+09 | 0.617519E+09 |
October | 0.332330E+09 | 0.00 | 0.332330E+09 | 0.364138E+09 | 0.726694E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.161102E+09 | 0.103361E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.119755E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148832E+09 | 0.492376E+10 | 0.440992E+10 | 0.985799E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.115679E+09 | 0.497180E+09 |
Maximum of Months | 0.609193E+09 | 59558765.02 | 0.563264E+09 | 0.699019E+09 | 0.119755E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277393E+09 | 0.00 | 0.277393E+09 | 0.140350E+09 | 0.115989E+10 |
February | 0.314506E+09 | 0.00 | 0.314506E+09 | 0.157373E+09 | 0.956775E+09 |
March | 0.426695E+09 | 0.00 | 0.426695E+09 | 0.265663E+09 | 0.107553E+10 |
April | 0.475745E+09 | 1831069.87 | 0.473914E+09 | 0.375054E+09 | 0.817989E+09 |
May | 0.590750E+09 | 27508545.19 | 0.563241E+09 | 0.512823E+09 | 0.710521E+09 |
June | 0.609169E+09 | 59556436.00 | 0.549612E+09 | 0.644680E+09 | 0.543421E+09 |
July | 0.596013E+09 | 49955724.46 | 0.546057E+09 | 0.698991E+09 | 0.497160E+09 |
August | 0.494969E+09 | 9911261.18 | 0.485057E+09 | 0.556309E+09 | 0.521081E+09 |
September | 0.405426E+09 | 63546.09 | 0.405362E+09 | 0.417613E+09 | 0.617494E+09 |
October | 0.332317E+09 | 0.00 | 0.332317E+09 | 0.364124E+09 | 0.726665E+09 |
November | 0.291183E+09 | 0.00 | 0.291183E+09 | 0.161096E+09 | 0.103357E+10 |
December | 0.258230E+09 | 0.00 | 0.258230E+09 | 0.115675E+09 | 0.119750E+10 |
Annual Sum or Average | 0.507240E+10 | 0.148827E+09 | 0.492357E+10 | 0.440975E+10 | 0.985759E+10 |
Minimum of Months | 0.258230E+09 | 0.00 | 0.258230E+09 | 0.115675E+09 | 0.497160E+09 |
Maximum of Months | 0.609169E+09 | 59556436.00 | 0.563241E+09 | 0.698991E+09 | 0.119750E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.831412E+09 | 0.444659E+09 | 0.386753E+09 | 0.958431E+09 | 0.119640E+10 |
February | 0.792177E+09 | 0.362903E+09 | 0.429275E+09 | 0.859756E+09 | 0.986748E+09 |
March | 0.106536E+10 | 0.474668E+09 | 0.590695E+09 | 0.121890E+10 | 0.110167E+10 |
April | 0.131812E+10 | 0.661062E+09 | 0.657055E+09 | 0.174073E+10 | 0.857272E+09 |
May | 0.128539E+10 | 0.536423E+09 | 0.748967E+09 | 0.163178E+10 | 0.801588E+09 |
June | 0.123618E+10 | 0.536357E+09 | 0.699823E+09 | 0.168890E+10 | 0.618141E+09 |
July | 0.144738E+10 | 0.719240E+09 | 0.728136E+09 | 0.213503E+10 | 0.564645E+09 |
August | 0.142940E+10 | 0.759250E+09 | 0.670151E+09 | 0.213861E+10 | 0.567462E+09 |
September | 0.100715E+10 | 0.461512E+09 | 0.545633E+09 | 0.141539E+10 | 0.665458E+09 |
October | 0.921225E+09 | 0.473486E+09 | 0.447739E+09 | 0.131542E+10 | 0.760262E+09 |
November | 0.812715E+09 | 0.412893E+09 | 0.399822E+09 | 0.943691E+09 | 0.105539E+10 |
December | 0.801158E+09 | 0.445132E+09 | 0.356026E+09 | 0.919616E+09 | 0.120075E+10 |
Annual Sum or Average | 0.129477E+11 | 0.628758E+10 | 0.666008E+10 | 0.169663E+11 | 0.103758E+11 |
Minimum of Months | 0.792177E+09 | 0.362903E+09 | 0.356026E+09 | 0.859756E+09 | 0.564645E+09 |
Maximum of Months | 0.144738E+10 | 0.759250E+09 | 0.748967E+09 | 0.213861E+10 | 0.120075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.831412E+09 | 0.444659E+09 | 0.386753E+09 | 0.958431E+09 | 0.119640E+10 |
February | 0.792177E+09 | 0.362903E+09 | 0.429275E+09 | 0.859756E+09 | 0.986748E+09 |
March | 0.106536E+10 | 0.474668E+09 | 0.590695E+09 | 0.121890E+10 | 0.110167E+10 |
April | 0.131812E+10 | 0.661062E+09 | 0.657055E+09 | 0.174073E+10 | 0.857272E+09 |
May | 0.128539E+10 | 0.536423E+09 | 0.748967E+09 | 0.163178E+10 | 0.801588E+09 |
June | 0.123618E+10 | 0.536357E+09 | 0.699823E+09 | 0.168890E+10 | 0.618141E+09 |
July | 0.144738E+10 | 0.719240E+09 | 0.728136E+09 | 0.213503E+10 | 0.564645E+09 |
August | 0.142940E+10 | 0.759250E+09 | 0.670151E+09 | 0.213861E+10 | 0.567462E+09 |
September | 0.100715E+10 | 0.461512E+09 | 0.545633E+09 | 0.141539E+10 | 0.665458E+09 |
October | 0.921225E+09 | 0.473486E+09 | 0.447739E+09 | 0.131542E+10 | 0.760262E+09 |
November | 0.812715E+09 | 0.412893E+09 | 0.399822E+09 | 0.943691E+09 | 0.105539E+10 |
December | 0.801158E+09 | 0.445132E+09 | 0.356026E+09 | 0.919616E+09 | 0.120075E+10 |
Annual Sum or Average | 0.129477E+11 | 0.628758E+10 | 0.666008E+10 | 0.169663E+11 | 0.103758E+11 |
Minimum of Months | 0.792177E+09 | 0.362903E+09 | 0.356026E+09 | 0.859756E+09 | 0.564645E+09 |
Maximum of Months | 0.144738E+10 | 0.759250E+09 | 0.748967E+09 | 0.213861E+10 | 0.120075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.831396E+09 | 0.444650E+09 | 0.386746E+09 | 0.958414E+09 | 0.119638E+10 |
February | 0.792163E+09 | 0.362896E+09 | 0.429267E+09 | 0.859741E+09 | 0.986730E+09 |
March | 0.106534E+10 | 0.474659E+09 | 0.590684E+09 | 0.121887E+10 | 0.110165E+10 |
April | 0.131809E+10 | 0.661050E+09 | 0.657043E+09 | 0.174070E+10 | 0.857257E+09 |
May | 0.128537E+10 | 0.536414E+09 | 0.748953E+09 | 0.163175E+10 | 0.801573E+09 |
June | 0.123616E+10 | 0.536347E+09 | 0.699810E+09 | 0.168887E+10 | 0.618130E+09 |
July | 0.144735E+10 | 0.719226E+09 | 0.728123E+09 | 0.213500E+10 | 0.564634E+09 |
August | 0.142937E+10 | 0.759236E+09 | 0.670139E+09 | 0.213857E+10 | 0.567451E+09 |
September | 0.100713E+10 | 0.461504E+09 | 0.545623E+09 | 0.141537E+10 | 0.665446E+09 |
October | 0.921208E+09 | 0.473477E+09 | 0.447731E+09 | 0.131540E+10 | 0.760248E+09 |
November | 0.812700E+09 | 0.412885E+09 | 0.399815E+09 | 0.943674E+09 | 0.105537E+10 |
December | 0.801144E+09 | 0.445124E+09 | 0.356020E+09 | 0.919599E+09 | 0.120072E+10 |
Annual Sum or Average | 0.129474E+11 | 0.628747E+10 | 0.665995E+10 | 0.169660E+11 | 0.103756E+11 |
Minimum of Months | 0.792163E+09 | 0.362896E+09 | 0.356020E+09 | 0.859741E+09 | 0.564634E+09 |
Maximum of Months | 0.144735E+10 | 0.759236E+09 | 0.748953E+09 | 0.213857E+10 | 0.120072E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487792E+09 | 0.264409E+10 | 0.107460E+10 |
February | 0.129958E+10 | 0.800470E+09 | 0.499105E+09 | 0.176373E+10 | 0.894310E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592982E+09 | 0.152716E+10 | 0.103496E+10 |
April | 0.927490E+09 | 0.353661E+09 | 0.573829E+09 | 0.132049E+10 | 0.834877E+09 |
May | 0.682459E+09 | 83985929.99 | 0.598473E+09 | 0.786971E+09 | 0.760930E+09 |
June | 0.579385E+09 | 34981177.23 | 0.544404E+09 | 0.667654E+09 | 0.581288E+09 |
July | 0.634185E+09 | 71391175.62 | 0.562794E+09 | 0.855199E+09 | 0.529596E+09 |
August | 0.814738E+09 | 0.256994E+09 | 0.557744E+09 | 0.127554E+10 | 0.551701E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541180E+09 | 0.172890E+10 | 0.629966E+09 |
October | 0.144181E+10 | 0.963892E+09 | 0.477920E+09 | 0.227156E+10 | 0.712293E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.244106E+10 | 0.965025E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.283325E+10 | 0.109598E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770413E+10 | 0.640200E+10 | 0.201156E+11 | 0.966553E+10 |
Minimum of Months | 0.579385E+09 | 34981177.23 | 0.467169E+09 | 0.667654E+09 | 0.529596E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.283325E+10 | 0.109598E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487791E+09 | 0.264408E+10 | 0.107460E+10 |
February | 0.129957E+10 | 0.800469E+09 | 0.499105E+09 | 0.176372E+10 | 0.894310E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592981E+09 | 0.152716E+10 | 0.103496E+10 |
April | 0.927489E+09 | 0.353660E+09 | 0.573829E+09 | 0.132049E+10 | 0.834877E+09 |
May | 0.682458E+09 | 83985829.21 | 0.598473E+09 | 0.786970E+09 | 0.760930E+09 |
June | 0.579385E+09 | 34981135.25 | 0.544403E+09 | 0.667653E+09 | 0.581288E+09 |
July | 0.634185E+09 | 71391089.96 | 0.562794E+09 | 0.855199E+09 | 0.529596E+09 |
August | 0.814737E+09 | 0.256994E+09 | 0.557744E+09 | 0.127554E+10 | 0.551701E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541179E+09 | 0.172890E+10 | 0.629966E+09 |
October | 0.144181E+10 | 0.963891E+09 | 0.477920E+09 | 0.227156E+10 | 0.712292E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.244105E+10 | 0.965025E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.283324E+10 | 0.109598E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770412E+10 | 0.640199E+10 | 0.201156E+11 | 0.966553E+10 |
Minimum of Months | 0.579385E+09 | 34981135.25 | 0.467169E+09 | 0.667653E+09 | 0.529596E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.283324E+10 | 0.109598E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487792E+09 | 0.264409E+10 | 0.107460E+10 |
February | 0.129958E+10 | 0.800470E+09 | 0.499105E+09 | 0.176373E+10 | 0.894310E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592982E+09 | 0.152716E+10 | 0.103496E+10 |
April | 0.927490E+09 | 0.353661E+09 | 0.573829E+09 | 0.132049E+10 | 0.834877E+09 |
May | 0.682459E+09 | 83985929.99 | 0.598473E+09 | 0.786971E+09 | 0.760930E+09 |
June | 0.579385E+09 | 34981177.23 | 0.544404E+09 | 0.667654E+09 | 0.581288E+09 |
July | 0.634185E+09 | 71391175.62 | 0.562794E+09 | 0.855199E+09 | 0.529596E+09 |
August | 0.814738E+09 | 0.256994E+09 | 0.557744E+09 | 0.127554E+10 | 0.551701E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541180E+09 | 0.172890E+10 | 0.629966E+09 |
October | 0.144181E+10 | 0.963892E+09 | 0.477920E+09 | 0.227156E+10 | 0.712293E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.244106E+10 | 0.965025E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.283325E+10 | 0.109598E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770413E+10 | 0.640200E+10 | 0.201156E+11 | 0.966553E+10 |
Minimum of Months | 0.579385E+09 | 34981177.23 | 0.467169E+09 | 0.667654E+09 | 0.529596E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.283325E+10 | 0.109598E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487791E+09 | 0.264408E+10 | 0.107460E+10 |
February | 0.129957E+10 | 0.800469E+09 | 0.499105E+09 | 0.176372E+10 | 0.894310E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592981E+09 | 0.152716E+10 | 0.103496E+10 |
April | 0.927489E+09 | 0.353660E+09 | 0.573829E+09 | 0.132049E+10 | 0.834877E+09 |
May | 0.682458E+09 | 83985829.21 | 0.598473E+09 | 0.786970E+09 | 0.760930E+09 |
June | 0.579385E+09 | 34981135.25 | 0.544403E+09 | 0.667653E+09 | 0.581288E+09 |
July | 0.634185E+09 | 71391089.96 | 0.562794E+09 | 0.855199E+09 | 0.529596E+09 |
August | 0.814737E+09 | 0.256994E+09 | 0.557744E+09 | 0.127554E+10 | 0.551701E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541179E+09 | 0.172890E+10 | 0.629966E+09 |
October | 0.144181E+10 | 0.963891E+09 | 0.477920E+09 | 0.227156E+10 | 0.712292E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.244105E+10 | 0.965025E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.283324E+10 | 0.109598E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770412E+10 | 0.640199E+10 | 0.201156E+11 | 0.966553E+10 |
Minimum of Months | 0.579385E+09 | 34981135.25 | 0.467169E+09 | 0.667653E+09 | 0.529596E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.283324E+10 | 0.109598E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183060E+10 | 0.134283E+10 | 0.487772E+09 | 0.264398E+10 | 0.107456E+10 |
February | 0.129952E+10 | 0.800438E+09 | 0.499085E+09 | 0.176366E+10 | 0.894274E+09 |
March | 0.114702E+10 | 0.554067E+09 | 0.592958E+09 | 0.152710E+10 | 0.103492E+10 |
April | 0.927453E+09 | 0.353647E+09 | 0.573806E+09 | 0.132044E+10 | 0.834843E+09 |
May | 0.682431E+09 | 83982544.98 | 0.598449E+09 | 0.786939E+09 | 0.760900E+09 |
June | 0.579362E+09 | 34979767.33 | 0.544382E+09 | 0.667627E+09 | 0.581265E+09 |
July | 0.634160E+09 | 71388298.25 | 0.562772E+09 | 0.855165E+09 | 0.529574E+09 |
August | 0.814705E+09 | 0.256984E+09 | 0.557722E+09 | 0.127549E+10 | 0.551678E+09 |
September | 0.109709E+10 | 0.555935E+09 | 0.541158E+09 | 0.172883E+10 | 0.629941E+09 |
October | 0.144175E+10 | 0.963853E+09 | 0.477901E+09 | 0.227147E+10 | 0.712264E+09 |
November | 0.169578E+10 | 0.119719E+10 | 0.498585E+09 | 0.244096E+10 | 0.964986E+09 |
December | 0.195567E+10 | 0.148852E+10 | 0.467151E+09 | 0.283313E+10 | 0.109594E+10 |
Annual Sum or Average | 0.141056E+11 | 0.770382E+10 | 0.640174E+10 | 0.201148E+11 | 0.966514E+10 |
Minimum of Months | 0.579362E+09 | 34979767.33 | 0.467151E+09 | 0.667627E+09 | 0.529574E+09 |
Maximum of Months | 0.195567E+10 | 0.148852E+10 | 0.598449E+09 | 0.283313E+10 | 0.109594E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791358E+09 | 0.399125E+09 | 0.392233E+09 | 0.937757E+09 | 0.135428E+10 |
February | 0.852730E+09 | 0.393660E+09 | 0.459070E+09 | 0.960479E+09 | 0.115526E+10 |
March | 0.108218E+10 | 0.478775E+09 | 0.603409E+09 | 0.123433E+10 | 0.131055E+10 |
April | 0.144373E+10 | 0.751746E+09 | 0.691980E+09 | 0.189615E+10 | 0.105668E+10 |
May | 0.146547E+10 | 0.676896E+09 | 0.788569E+09 | 0.190044E+10 | 0.908371E+09 |
June | 0.150242E+10 | 0.751181E+09 | 0.751238E+09 | 0.206089E+10 | 0.721468E+09 |
July | 0.164344E+10 | 0.879393E+09 | 0.764052E+09 | 0.237338E+10 | 0.685393E+09 |
August | 0.154187E+10 | 0.835631E+09 | 0.706241E+09 | 0.224973E+10 | 0.728174E+09 |
September | 0.127754E+10 | 0.683594E+09 | 0.593948E+09 | 0.182321E+10 | 0.755865E+09 |
October | 0.100918E+10 | 0.550967E+09 | 0.458209E+09 | 0.144973E+10 | 0.903077E+09 |
November | 0.882182E+09 | 0.461443E+09 | 0.420739E+09 | 0.106607E+10 | 0.125986E+10 |
December | 0.805090E+09 | 0.431812E+09 | 0.373277E+09 | 0.948369E+09 | 0.147648E+10 |
Annual Sum or Average | 0.142972E+11 | 0.729422E+10 | 0.700297E+10 | 0.189005E+11 | 0.123155E+11 |
Minimum of Months | 0.791358E+09 | 0.393660E+09 | 0.373277E+09 | 0.937757E+09 | 0.685393E+09 |
Maximum of Months | 0.164344E+10 | 0.879393E+09 | 0.788569E+09 | 0.237338E+10 | 0.147648E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791358E+09 | 0.399125E+09 | 0.392233E+09 | 0.937757E+09 | 0.135428E+10 |
February | 0.852730E+09 | 0.393660E+09 | 0.459070E+09 | 0.960479E+09 | 0.115526E+10 |
March | 0.108218E+10 | 0.478775E+09 | 0.603409E+09 | 0.123433E+10 | 0.131055E+10 |
April | 0.144373E+10 | 0.751746E+09 | 0.691980E+09 | 0.189615E+10 | 0.105668E+10 |
May | 0.146547E+10 | 0.676896E+09 | 0.788569E+09 | 0.190044E+10 | 0.908371E+09 |
June | 0.150242E+10 | 0.751181E+09 | 0.751238E+09 | 0.206089E+10 | 0.721468E+09 |
July | 0.164344E+10 | 0.879393E+09 | 0.764052E+09 | 0.237338E+10 | 0.685393E+09 |
August | 0.154187E+10 | 0.835631E+09 | 0.706241E+09 | 0.224973E+10 | 0.728174E+09 |
September | 0.127754E+10 | 0.683594E+09 | 0.593948E+09 | 0.182321E+10 | 0.755865E+09 |
October | 0.100918E+10 | 0.550967E+09 | 0.458209E+09 | 0.144973E+10 | 0.903077E+09 |
November | 0.882182E+09 | 0.461443E+09 | 0.420739E+09 | 0.106607E+10 | 0.125986E+10 |
December | 0.805090E+09 | 0.431812E+09 | 0.373277E+09 | 0.948369E+09 | 0.147648E+10 |
Annual Sum or Average | 0.142972E+11 | 0.729422E+10 | 0.700297E+10 | 0.189005E+11 | 0.123155E+11 |
Minimum of Months | 0.791358E+09 | 0.393660E+09 | 0.373277E+09 | 0.937757E+09 | 0.685393E+09 |
Maximum of Months | 0.164344E+10 | 0.879393E+09 | 0.788569E+09 | 0.237338E+10 | 0.147648E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791344E+09 | 0.399118E+09 | 0.392226E+09 | 0.937740E+09 | 0.135425E+10 |
February | 0.852714E+09 | 0.393653E+09 | 0.459061E+09 | 0.960461E+09 | 0.115524E+10 |
March | 0.108216E+10 | 0.478767E+09 | 0.603398E+09 | 0.123431E+10 | 0.131052E+10 |
April | 0.144370E+10 | 0.751732E+09 | 0.691967E+09 | 0.189612E+10 | 0.105666E+10 |
May | 0.146544E+10 | 0.676884E+09 | 0.788555E+09 | 0.190041E+10 | 0.908354E+09 |
June | 0.150239E+10 | 0.751167E+09 | 0.751224E+09 | 0.206085E+10 | 0.721455E+09 |
July | 0.164341E+10 | 0.879377E+09 | 0.764038E+09 | 0.237334E+10 | 0.685380E+09 |
August | 0.154184E+10 | 0.835616E+09 | 0.706228E+09 | 0.224969E+10 | 0.728161E+09 |
September | 0.127752E+10 | 0.683582E+09 | 0.593937E+09 | 0.182317E+10 | 0.755851E+09 |
October | 0.100916E+10 | 0.550957E+09 | 0.458201E+09 | 0.144970E+10 | 0.903060E+09 |
November | 0.882166E+09 | 0.461435E+09 | 0.420731E+09 | 0.106605E+10 | 0.125984E+10 |
December | 0.805075E+09 | 0.431805E+09 | 0.373270E+09 | 0.948351E+09 | 0.147645E+10 |
Annual Sum or Average | 0.142969E+11 | 0.729409E+10 | 0.700284E+10 | 0.189002E+11 | 0.123152E+11 |
Minimum of Months | 0.791344E+09 | 0.393653E+09 | 0.373270E+09 | 0.937740E+09 | 0.685380E+09 |
Maximum of Months | 0.164341E+10 | 0.879377E+09 | 0.788555E+09 | 0.237334E+10 | 0.147645E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.868809E+09 | 0.516811E+10 |
February | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.934214E+09 | 0.424345E+10 |
March | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.149951E+10 | 0.481474E+10 |
April | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.203029E+10 | 0.369046E+10 |
May | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.265917E+10 | 0.335040E+10 |
June | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.327868E+10 | 0.255798E+10 |
July | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.357411E+10 | 0.235390E+10 |
August | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.287366E+10 | 0.245989E+10 |
September | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.215394E+10 | 0.287267E+10 |
October | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.192785E+10 | 0.331886E+10 |
November | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.969166E+09 | 0.458382E+10 |
December | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.784595E+09 | 0.521472E+10 |
Annual Sum or Average | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.235540E+11 | 0.446290E+11 |
Minimum of Months | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.784595E+09 | 0.235390E+10 |
Maximum of Months | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.357411E+10 | 0.521472E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.291710E+10 | 0.335098E+10 |
February | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.260350E+10 | 0.275928E+10 |
March | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.366909E+10 | 0.312415E+10 |
April | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.519420E+10 | 0.247331E+10 |
May | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.485355E+10 | 0.233361E+10 |
June | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.501835E+10 | 0.180641E+10 |
July | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.634217E+10 | 0.168472E+10 |
August | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.634762E+10 | 0.171865E+10 |
September | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.421787E+10 | 0.192697E+10 |
October | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.392779E+10 | 0.219101E+10 |
November | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.285400E+10 | 0.297905E+10 |
December | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.280706E+10 | 0.336427E+10 |
Annual Sum or Average | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.507523E+11 | 0.297124E+11 |
Minimum of Months | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.260350E+10 | 0.168472E+10 |
Maximum of Months | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.634762E+10 | 0.336427E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.131446E+11 | 0.527641E+10 |
February | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.875686E+10 | 0.431873E+10 |
March | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.761860E+10 | 0.495461E+10 |
April | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.660496E+10 | 0.397137E+10 |
May | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.393180E+10 | 0.368096E+10 |
June | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.336363E+10 | 0.277274E+10 |
July | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.431477E+10 | 0.253736E+10 |
August | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.638214E+10 | 0.268280E+10 |
September | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.858167E+10 | 0.308495E+10 |
October | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.112800E+11 | 0.348871E+10 |
November | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.121321E+11 | 0.468061E+10 |
December | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.141000E+11 | 0.530211E+10 |
Annual Sum or Average | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.100211E+12 | 0.467514E+11 |
Minimum of Months | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.336363E+10 | 0.253736E+10 |
Maximum of Months | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.141000E+11 | 0.530211E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.290944E+10 | 0.360815E+10 |
February | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.297868E+10 | 0.298603E+10 |
March | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.383389E+10 | 0.336876E+10 |
April | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.581123E+10 | 0.273203E+10 |
May | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.571977E+10 | 0.253762E+10 |
June | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.622272E+10 | 0.194546E+10 |
July | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.719736E+10 | 0.182882E+10 |
August | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.685140E+10 | 0.189664E+10 |
September | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.548438E+10 | 0.209231E+10 |
October | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.442714E+10 | 0.239892E+10 |
November | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.332134E+10 | 0.322115E+10 |
December | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.300709E+10 | 0.367621E+10 |
Annual Sum or Average | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.577645E+11 | 0.322921E+11 |
Minimum of Months | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.290944E+10 | 0.182882E+10 |
Maximum of Months | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.719736E+10 | 0.367621E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.101848E+10 | 0.465565E+10 |
February | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.106846E+10 | 0.381892E+10 |
March | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.162996E+10 | 0.444255E+10 |
April | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.208994E+10 | 0.348763E+10 |
May | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.273623E+10 | 0.318359E+10 |
June | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.327438E+10 | 0.247662E+10 |
July | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.353037E+10 | 0.230837E+10 |
August | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.284932E+10 | 0.240084E+10 |
September | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.217479E+10 | 0.274096E+10 |
October | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.198365E+10 | 0.311592E+10 |
November | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.109833E+10 | 0.417086E+10 |
December | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.937750E+09 | 0.468682E+10 |
Annual Sum or Average | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.243917E+11 | 0.414887E+11 |
Minimum of Months | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.937750E+09 | 0.230837E+10 |
Maximum of Months | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.353037E+10 | 0.468682E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.304789E+10 | 0.304473E+10 |
February | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.270929E+10 | 0.250725E+10 |
March | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.376734E+10 | 0.290798E+10 |
April | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.523582E+10 | 0.236261E+10 |
May | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.490073E+10 | 0.223419E+10 |
June | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.502534E+10 | 0.175751E+10 |
July | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.632535E+10 | 0.165975E+10 |
August | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.633773E+10 | 0.168576E+10 |
September | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.423674E+10 | 0.184975E+10 |
October | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.397141E+10 | 0.207749E+10 |
November | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.295362E+10 | 0.274938E+10 |
December | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.294014E+10 | 0.305868E+10 |
Annual Sum or Average | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.514514E+11 | 0.278951E+11 |
Minimum of Months | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.270929E+10 | 0.165975E+10 |
Maximum of Months | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.633773E+10 | 0.305868E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.132771E+11 | 0.487500E+10 |
February | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.886204E+10 | 0.396399E+10 |
March | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.771752E+10 | 0.462055E+10 |
April | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.663443E+10 | 0.378335E+10 |
May | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.397771E+10 | 0.350011E+10 |
June | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.335856E+10 | 0.268652E+10 |
July | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.427464E+10 | 0.249470E+10 |
August | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.634420E+10 | 0.262766E+10 |
September | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.857215E+10 | 0.297048E+10 |
October | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.113025E+11 | 0.333178E+10 |
November | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.122213E+11 | 0.437698E+10 |
December | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.142320E+11 | 0.491901E+10 |
Annual Sum or Average | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.100774E+12 | 0.441501E+11 |
Minimum of Months | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.335856E+10 | 0.249470E+10 |
Maximum of Months | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.142320E+11 | 0.491901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.297791E+10 | 0.333130E+10 |
February | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.303809E+10 | 0.275438E+10 |
March | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.388346E+10 | 0.315939E+10 |
April | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.581092E+10 | 0.261829E+10 |
May | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.572023E+10 | 0.243444E+10 |
June | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.619099E+10 | 0.189315E+10 |
July | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.714785E+10 | 0.179715E+10 |
August | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.680892E+10 | 0.186001E+10 |
September | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.546733E+10 | 0.202213E+10 |
October | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.443533E+10 | 0.228980E+10 |
November | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.337264E+10 | 0.300182E+10 |
December | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.307706E+10 | 0.339311E+10 |
Annual Sum or Average | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.579307E+11 | 0.305550E+11 |
Minimum of Months | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.297791E+10 | 0.179715E+10 |
Maximum of Months | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.714785E+10 | 0.339311E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 262.01 | 2165.33 | 517.85 | 0.00 | 517.85 | 0.00 | 0.00 |
February | 325.27 | 1977.53 | 650.04 | 0.00 | 650.04 | 0.00 | 0.00 |
March | 495.95 | 2007.86 | 796.57 | 0.00 | 796.57 | 0.00 | 0.00 |
April | 723.51 | 1577.96 | 917.75 | 3.53 | 914.22 | 0.00 | 0.00 |
May | 957.36 | 1326.43 | 1102.84 | 51.35 | 1051.49 | 0.00 | 0.00 |
June | 1243.63 | 1048.30 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
July | 1304.91 | 928.12 | 1112.66 | 93.26 | 1019.40 | 0.00 | 0.00 |
August | 1038.54 | 972.78 | 924.03 | 18.50 | 905.53 | 0.00 | 0.00 |
September | 805.61 | 1191.19 | 782.10 | 0.12 | 781.97 | 0.00 | 0.00 |
October | 679.76 | 1356.57 | 620.38 | 0.00 | 620.38 | 0.00 | 0.00 |
November | 310.77 | 1993.84 | 561.71 | 0.00 | 561.71 | 0.00 | 0.00 |
December | 215.95 | 2235.54 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Annual Sum or Average | 699.18 | 1562.96 | 804.25 | 23.60 | 780.65 | 0.00 | 0.00 |
Minimum of Months | 215.95 | 928.12 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Maximum of Months | 1304.91 | 2235.54 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1073.51 | 1340.04 | 931.23 | 498.05 | 433.19 | 0.00 | 0.00 |
February | 1066.16 | 1223.64 | 982.36 | 450.03 | 532.33 | 0.00 | 0.00 |
March | 1365.24 | 1233.94 | 1193.28 | 531.66 | 661.62 | 0.00 | 0.00 |
April | 2014.72 | 992.21 | 1525.59 | 765.11 | 760.48 | 0.00 | 0.00 |
May | 1827.70 | 897.83 | 1439.72 | 600.83 | 838.89 | 0.00 | 0.00 |
June | 1954.73 | 715.44 | 1430.75 | 620.78 | 809.98 | 0.00 | 0.00 |
July | 2391.38 | 632.44 | 1621.15 | 805.59 | 815.56 | 0.00 | 0.00 |
August | 2395.38 | 635.59 | 1601.02 | 850.41 | 750.61 | 0.00 | 0.00 |
September | 1638.18 | 770.20 | 1165.67 | 534.15 | 631.52 | 0.00 | 0.00 |
October | 1473.36 | 851.54 | 1031.83 | 530.34 | 501.50 | 0.00 | 0.00 |
November | 1092.23 | 1221.50 | 940.64 | 477.88 | 462.75 | 0.00 | 0.00 |
December | 1030.03 | 1344.91 | 897.35 | 498.58 | 398.77 | 0.00 | 0.00 |
Annual Sum or Average | 1613.98 | 987.04 | 1231.70 | 598.13 | 633.56 | 0.00 | 0.00 |
Minimum of Months | 1030.03 | 632.44 | 897.35 | 450.03 | 398.77 | 0.00 | 0.00 |
Maximum of Months | 2395.38 | 1344.91 | 1621.15 | 850.41 | 838.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4935.90 | 2006.04 | 3417.46 | 2506.86 | 910.60 | 0.00 | 0.00 |
February | 3645.24 | 1848.34 | 2685.94 | 1654.40 | 1031.54 | 0.00 | 0.00 |
March | 2850.86 | 1932.03 | 2141.32 | 1034.36 | 1106.96 | 0.00 | 0.00 |
April | 2547.22 | 1610.47 | 1789.12 | 682.21 | 1106.91 | 0.00 | 0.00 |
May | 1469.09 | 1420.48 | 1273.99 | 156.78 | 1117.21 | 0.00 | 0.00 |
June | 1287.90 | 1121.30 | 1117.63 | 67.48 | 1050.15 | 0.00 | 0.00 |
July | 1596.46 | 988.63 | 1183.88 | 133.27 | 1050.61 | 0.00 | 0.00 |
August | 2381.15 | 1029.90 | 1520.93 | 479.75 | 1041.18 | 0.00 | 0.00 |
September | 3335.04 | 1215.20 | 2116.37 | 1072.44 | 1043.93 | 0.00 | 0.00 |
October | 4240.49 | 1329.69 | 2691.53 | 1799.36 | 892.17 | 0.00 | 0.00 |
November | 4708.79 | 1861.53 | 3271.28 | 2309.48 | 961.81 | 0.00 | 0.00 |
December | 5289.02 | 2045.95 | 3650.94 | 2778.84 | 872.10 | 0.00 | 0.00 |
Annual Sum or Average | 3189.28 | 1532.45 | 2236.49 | 1221.47 | 1015.02 | 0.00 | 0.00 |
Minimum of Months | 1287.90 | 988.63 | 1117.63 | 67.48 | 872.10 | 0.00 | 0.00 |
Maximum of Months | 5289.02 | 2045.95 | 3650.94 | 2778.84 | 1117.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1050.35 | 1516.88 | 886.37 | 447.05 | 439.33 | 0.00 | 0.00 |
February | 1191.06 | 1432.61 | 1057.45 | 488.17 | 569.28 | 0.00 | 0.00 |
March | 1382.53 | 1467.90 | 1212.12 | 536.26 | 675.86 | 0.00 | 0.00 |
April | 2194.61 | 1223.00 | 1670.97 | 870.07 | 800.90 | 0.00 | 0.00 |
May | 2128.62 | 1017.43 | 1641.42 | 758.17 | 883.25 | 0.00 | 0.00 |
June | 2385.27 | 835.03 | 1738.90 | 869.42 | 869.48 | 0.00 | 0.00 |
July | 2658.34 | 767.68 | 1840.76 | 984.98 | 855.79 | 0.00 | 0.00 |
August | 2519.85 | 815.60 | 1727.00 | 935.96 | 791.04 | 0.00 | 0.00 |
September | 2110.18 | 874.84 | 1478.63 | 791.19 | 687.44 | 0.00 | 0.00 |
October | 1623.79 | 1011.50 | 1130.34 | 617.12 | 513.22 | 0.00 | 0.00 |
November | 1233.87 | 1458.16 | 1021.04 | 534.07 | 486.96 | 0.00 | 0.00 |
December | 1062.23 | 1653.75 | 901.75 | 483.66 | 418.09 | 0.00 | 0.00 |
Annual Sum or Average | 1797.99 | 1171.55 | 1360.07 | 693.89 | 666.18 | 0.00 | 0.00 |
Minimum of Months | 1050.35 | 767.68 | 886.37 | 447.05 | 418.09 | 0.00 | 0.00 |
Maximum of Months | 2658.34 | 1653.75 | 1840.76 | 984.98 | 883.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.38 | 1929.55 | 517.85 | 0.00 | 517.85 | 0.00 | 0.00 |
February | 386.17 | 1754.07 | 650.04 | 0.00 | 650.04 | 0.00 | 0.00 |
March | 559.85 | 1797.62 | 796.57 | 0.00 | 796.57 | 0.00 | 0.00 |
April | 783.29 | 1423.79 | 917.74 | 3.53 | 914.21 | 0.00 | 0.00 |
May | 992.82 | 1250.90 | 1102.84 | 51.35 | 1051.48 | 0.00 | 0.00 |
June | 1264.92 | 986.88 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
July | 1334.42 | 878.84 | 1112.66 | 93.26 | 1019.40 | 0.00 | 0.00 |
August | 1072.90 | 918.42 | 924.03 | 18.50 | 905.52 | 0.00 | 0.00 |
September | 831.00 | 1108.28 | 782.09 | 0.12 | 781.97 | 0.00 | 0.00 |
October | 719.78 | 1239.12 | 620.38 | 0.00 | 620.38 | 0.00 | 0.00 |
November | 373.91 | 1768.45 | 561.71 | 0.00 | 561.71 | 0.00 | 0.00 |
December | 292.93 | 1946.95 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Annual Sum or Average | 746.89 | 1415.18 | 804.25 | 23.60 | 780.65 | 0.00 | 0.00 |
Minimum of Months | 292.93 | 878.84 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Maximum of Months | 1334.42 | 1946.95 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1089.12 | 1251.11 | 931.23 | 498.04 | 433.19 | 0.00 | 0.00 |
February | 1076.18 | 1140.57 | 982.35 | 450.02 | 532.33 | 0.00 | 0.00 |
March | 1369.88 | 1166.42 | 1193.27 | 531.66 | 661.61 | 0.00 | 0.00 |
April | 2003.93 | 954.21 | 1525.58 | 765.11 | 760.47 | 0.00 | 0.00 |
May | 1812.11 | 871.27 | 1439.71 | 600.83 | 838.89 | 0.00 | 0.00 |
June | 1936.09 | 696.92 | 1430.75 | 620.78 | 809.97 | 0.00 | 0.00 |
July | 2367.89 | 629.00 | 1621.15 | 805.59 | 815.56 | 0.00 | 0.00 |
August | 2369.93 | 641.67 | 1601.02 | 850.41 | 750.61 | 0.00 | 0.00 |
September | 1627.27 | 743.43 | 1165.67 | 534.15 | 631.51 | 0.00 | 0.00 |
October | 1466.47 | 818.03 | 1031.83 | 530.33 | 501.49 | 0.00 | 0.00 |
November | 1101.08 | 1149.32 | 940.63 | 477.88 | 462.75 | 0.00 | 0.00 |
December | 1048.04 | 1256.07 | 897.35 | 498.57 | 398.77 | 0.00 | 0.00 |
Annual Sum or Average | 1609.35 | 942.17 | 1231.69 | 598.13 | 633.56 | 0.00 | 0.00 |
Minimum of Months | 1048.04 | 629.00 | 897.35 | 450.02 | 398.77 | 0.00 | 0.00 |
Maximum of Months | 2369.93 | 1256.07 | 1621.15 | 850.41 | 838.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4907.62 | 1969.99 | 3417.44 | 2506.85 | 910.59 | 0.00 | 0.00 |
February | 3619.73 | 1785.19 | 2685.93 | 1654.39 | 1031.54 | 0.00 | 0.00 |
March | 2844.46 | 1849.84 | 2141.31 | 1034.35 | 1106.96 | 0.00 | 0.00 |
April | 2548.21 | 1532.16 | 1789.12 | 682.21 | 1106.91 | 0.00 | 0.00 |
May | 1467.96 | 1374.31 | 1273.99 | 156.78 | 1117.21 | 0.00 | 0.00 |
June | 1297.70 | 1069.73 | 1117.63 | 67.48 | 1050.15 | 0.00 | 0.00 |
July | 1610.95 | 947.34 | 1183.87 | 133.27 | 1050.60 | 0.00 | 0.00 |
August | 2382.82 | 1001.64 | 1520.92 | 479.75 | 1041.18 | 0.00 | 0.00 |
September | 3310.83 | 1190.18 | 2116.36 | 1072.44 | 1043.93 | 0.00 | 0.00 |
October | 4211.48 | 1302.54 | 2691.52 | 1799.36 | 892.16 | 0.00 | 0.00 |
November | 4680.59 | 1805.79 | 3271.27 | 2309.47 | 961.80 | 0.00 | 0.00 |
December | 5264.33 | 1979.58 | 3650.92 | 2778.83 | 872.09 | 0.00 | 0.00 |
Annual Sum or Average | 3177.67 | 1482.48 | 2236.49 | 1221.47 | 1015.02 | 0.00 | 0.00 |
Minimum of Months | 1297.70 | 947.34 | 1117.63 | 67.48 | 872.09 | 0.00 | 0.00 |
Maximum of Months | 5264.33 | 1979.58 | 3650.92 | 2778.83 | 1117.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1086.26 | 1347.13 | 886.37 | 447.04 | 439.32 | 0.00 | 0.00 |
February | 1231.27 | 1234.30 | 1057.44 | 488.16 | 569.28 | 0.00 | 0.00 |
March | 1431.41 | 1257.75 | 1212.11 | 536.26 | 675.85 | 0.00 | 0.00 |
April | 2241.99 | 1054.02 | 1670.96 | 870.07 | 800.89 | 0.00 | 0.00 |
May | 2135.52 | 947.44 | 1641.41 | 758.16 | 883.25 | 0.00 | 0.00 |
June | 2400.74 | 750.56 | 1738.89 | 869.41 | 869.48 | 0.00 | 0.00 |
July | 2687.19 | 682.81 | 1840.76 | 984.97 | 855.78 | 0.00 | 0.00 |
August | 2558.02 | 708.12 | 1726.99 | 935.96 | 791.03 | 0.00 | 0.00 |
September | 2115.89 | 807.22 | 1478.62 | 791.19 | 687.43 | 0.00 | 0.00 |
October | 1652.91 | 895.66 | 1130.34 | 617.12 | 513.22 | 0.00 | 0.00 |
November | 1281.38 | 1242.73 | 1021.03 | 534.07 | 486.96 | 0.00 | 0.00 |
December | 1122.72 | 1372.54 | 901.75 | 483.66 | 418.09 | 0.00 | 0.00 |
Annual Sum or Average | 1831.70 | 1023.98 | 1360.07 | 693.89 | 666.18 | 0.00 | 0.00 |
Minimum of Months | 1086.26 | 682.81 | 886.37 | 447.04 | 418.09 | 0.00 | 0.00 |
Maximum of Months | 2687.19 | 1372.54 | 1840.76 | 984.97 | 883.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 380.26 | 1738.22 | 517.85 | 0.00 | 517.85 | 0.00 | 0.00 |
February | 441.66 | 1578.59 | 650.04 | 0.00 | 650.04 | 0.00 | 0.00 |
March | 608.56 | 1658.66 | 796.57 | 0.00 | 796.57 | 0.00 | 0.00 |
April | 806.30 | 1345.54 | 917.74 | 3.53 | 914.21 | 0.00 | 0.00 |
May | 1021.59 | 1188.62 | 1102.84 | 51.35 | 1051.48 | 0.00 | 0.00 |
June | 1263.26 | 955.49 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
July | 1318.09 | 861.85 | 1112.66 | 93.26 | 1019.40 | 0.00 | 0.00 |
August | 1063.82 | 896.37 | 924.03 | 18.50 | 905.52 | 0.00 | 0.00 |
September | 839.04 | 1057.47 | 782.09 | 0.12 | 781.97 | 0.00 | 0.00 |
October | 740.61 | 1163.35 | 620.38 | 0.00 | 620.38 | 0.00 | 0.00 |
November | 423.74 | 1609.13 | 561.71 | 0.00 | 561.71 | 0.00 | 0.00 |
December | 350.12 | 1749.86 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Annual Sum or Average | 773.45 | 1315.60 | 804.25 | 23.60 | 780.65 | 0.00 | 0.00 |
Minimum of Months | 350.12 | 861.85 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Maximum of Months | 1318.09 | 1749.86 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1137.95 | 1136.77 | 931.23 | 498.04 | 433.19 | 0.00 | 0.00 |
February | 1119.91 | 1036.40 | 982.35 | 450.02 | 532.33 | 0.00 | 0.00 |
March | 1406.57 | 1085.72 | 1193.27 | 531.66 | 661.61 | 0.00 | 0.00 |
April | 2019.99 | 911.50 | 1525.58 | 765.11 | 760.47 | 0.00 | 0.00 |
May | 1829.72 | 834.15 | 1439.71 | 600.83 | 838.89 | 0.00 | 0.00 |
June | 1938.79 | 678.05 | 1430.75 | 620.78 | 809.97 | 0.00 | 0.00 |
July | 2361.61 | 619.68 | 1621.15 | 805.59 | 815.56 | 0.00 | 0.00 |
August | 2366.24 | 629.39 | 1601.02 | 850.41 | 750.61 | 0.00 | 0.00 |
September | 1634.54 | 713.64 | 1165.67 | 534.15 | 631.51 | 0.00 | 0.00 |
October | 1482.75 | 775.65 | 1031.83 | 530.33 | 501.49 | 0.00 | 0.00 |
November | 1139.51 | 1060.72 | 940.63 | 477.88 | 462.75 | 0.00 | 0.00 |
December | 1097.72 | 1141.98 | 897.35 | 498.57 | 398.77 | 0.00 | 0.00 |
Annual Sum or Average | 1631.51 | 884.55 | 1231.69 | 598.13 | 633.56 | 0.00 | 0.00 |
Minimum of Months | 1097.72 | 619.68 | 897.35 | 450.02 | 398.77 | 0.00 | 0.00 |
Maximum of Months | 2366.24 | 1141.98 | 1621.15 | 850.41 | 838.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4957.11 | 1820.12 | 3417.44 | 2506.85 | 910.59 | 0.00 | 0.00 |
February | 3663.21 | 1638.56 | 2685.93 | 1654.39 | 1031.54 | 0.00 | 0.00 |
March | 2881.39 | 1725.11 | 2141.31 | 1034.35 | 1106.96 | 0.00 | 0.00 |
April | 2559.58 | 1459.62 | 1789.12 | 682.21 | 1106.91 | 0.00 | 0.00 |
May | 1485.11 | 1306.79 | 1273.99 | 156.78 | 1117.21 | 0.00 | 0.00 |
June | 1295.74 | 1036.47 | 1117.63 | 67.48 | 1050.15 | 0.00 | 0.00 |
July | 1595.97 | 931.41 | 1183.87 | 133.27 | 1050.60 | 0.00 | 0.00 |
August | 2368.65 | 981.06 | 1520.92 | 479.75 | 1041.18 | 0.00 | 0.00 |
September | 3307.16 | 1146.02 | 2116.36 | 1072.44 | 1043.93 | 0.00 | 0.00 |
October | 4219.86 | 1243.95 | 2691.52 | 1799.36 | 892.16 | 0.00 | 0.00 |
November | 4715.03 | 1688.65 | 3271.27 | 2309.47 | 961.80 | 0.00 | 0.00 |
December | 5313.63 | 1836.55 | 3650.92 | 2778.83 | 872.09 | 0.00 | 0.00 |
Annual Sum or Average | 3195.53 | 1399.99 | 2236.49 | 1221.47 | 1015.02 | 0.00 | 0.00 |
Minimum of Months | 1295.74 | 931.41 | 1117.63 | 67.48 | 872.09 | 0.00 | 0.00 |
Maximum of Months | 5313.63 | 1836.55 | 3650.92 | 2778.83 | 1117.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1111.83 | 1243.76 | 886.37 | 447.04 | 439.32 | 0.00 | 0.00 |
February | 1255.83 | 1138.55 | 1057.44 | 488.16 | 569.28 | 0.00 | 0.00 |
March | 1449.92 | 1179.58 | 1212.11 | 536.26 | 675.85 | 0.00 | 0.00 |
April | 2241.87 | 1010.14 | 1670.96 | 870.07 | 800.89 | 0.00 | 0.00 |
May | 2135.69 | 908.92 | 1641.41 | 758.16 | 883.25 | 0.00 | 0.00 |
June | 2388.50 | 730.38 | 1738.89 | 869.41 | 869.48 | 0.00 | 0.00 |
July | 2668.70 | 670.98 | 1840.76 | 984.97 | 855.78 | 0.00 | 0.00 |
August | 2542.16 | 694.45 | 1726.99 | 935.96 | 791.03 | 0.00 | 0.00 |
September | 2109.31 | 780.14 | 1478.62 | 791.19 | 687.43 | 0.00 | 0.00 |
October | 1655.96 | 854.91 | 1130.34 | 617.12 | 513.22 | 0.00 | 0.00 |
November | 1301.17 | 1158.11 | 1021.03 | 534.07 | 486.96 | 0.00 | 0.00 |
December | 1148.84 | 1266.84 | 901.75 | 483.66 | 418.09 | 0.00 | 0.00 |
Annual Sum or Average | 1836.97 | 968.89 | 1360.07 | 693.89 | 666.18 | 0.00 | 0.00 |
Minimum of Months | 1111.83 | 670.98 | 886.37 | 447.04 | 418.09 | 0.00 | 0.00 |
Maximum of Months | 2668.70 | 1266.84 | 1840.76 | 984.97 | 883.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.701771E+09 | 0.579962E+10 | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.00 | 0.00 |
February | 0.786889E+09 | 0.478403E+10 | 0.157258E+10 | 0.00 | 0.157258E+10 | 0.00 | 0.00 |
March | 0.132835E+10 | 0.537784E+10 | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.00 | 0.00 |
April | 0.187533E+10 | 0.409007E+10 | 0.237880E+10 | 9155640.17 | 0.236965E+10 | 0.00 | 0.00 |
May | 0.256420E+10 | 0.355272E+10 | 0.295384E+10 | 0.137547E+09 | 0.281630E+10 | 0.00 | 0.00 |
June | 0.322350E+10 | 0.271719E+10 | 0.304594E+10 | 0.297792E+09 | 0.274815E+10 | 0.00 | 0.00 |
July | 0.349507E+10 | 0.248588E+10 | 0.298016E+10 | 0.249787E+09 | 0.273037E+10 | 0.00 | 0.00 |
August | 0.278163E+10 | 0.260549E+10 | 0.247492E+10 | 49557880.04 | 0.242536E+10 | 0.00 | 0.00 |
September | 0.208813E+10 | 0.308757E+10 | 0.202719E+10 | 317740.55 | 0.202688E+10 | 0.00 | 0.00 |
October | 0.182068E+10 | 0.363344E+10 | 0.166164E+10 | 0.00 | 0.166164E+10 | 0.00 | 0.00 |
November | 0.805506E+09 | 0.516802E+10 | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.00 | 0.00 |
December | 0.578392E+09 | 0.598768E+10 | 0.129119E+10 | 0.00 | 0.129119E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.220494E+11 | 0.492896E+11 | 0.253628E+11 | 0.744157E+09 | 0.246186E+11 | 0.00 | 0.00 |
Minimum of Months | 0.578392E+09 | 0.248588E+10 | 0.129119E+10 | 0.00 | 0.129119E+10 | 0.00 | 0.00 |
Maximum of Months | 0.349507E+10 | 0.598768E+10 | 0.304594E+10 | 0.297792E+09 | 0.281630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.287528E+10 | 0.358917E+10 | 0.249422E+10 | 0.133397E+10 | 0.116025E+10 | 0.00 | 0.00 |
February | 0.257925E+10 | 0.296023E+10 | 0.237652E+10 | 0.108870E+10 | 0.128782E+10 | 0.00 | 0.00 |
March | 0.365667E+10 | 0.330499E+10 | 0.319607E+10 | 0.142400E+10 | 0.177207E+10 | 0.00 | 0.00 |
April | 0.522216E+10 | 0.257180E+10 | 0.395433E+10 | 0.198317E+10 | 0.197115E+10 | 0.00 | 0.00 |
May | 0.489532E+10 | 0.240475E+10 | 0.385615E+10 | 0.160926E+10 | 0.224689E+10 | 0.00 | 0.00 |
June | 0.506667E+10 | 0.185441E+10 | 0.370852E+10 | 0.160906E+10 | 0.209946E+10 | 0.00 | 0.00 |
July | 0.640506E+10 | 0.169392E+10 | 0.434210E+10 | 0.215771E+10 | 0.218439E+10 | 0.00 | 0.00 |
August | 0.641579E+10 | 0.170237E+10 | 0.428818E+10 | 0.227774E+10 | 0.201044E+10 | 0.00 | 0.00 |
September | 0.424615E+10 | 0.199636E+10 | 0.302142E+10 | 0.138453E+10 | 0.163689E+10 | 0.00 | 0.00 |
October | 0.394625E+10 | 0.228077E+10 | 0.276366E+10 | 0.142045E+10 | 0.134321E+10 | 0.00 | 0.00 |
November | 0.283106E+10 | 0.316614E+10 | 0.243813E+10 | 0.123867E+10 | 0.119946E+10 | 0.00 | 0.00 |
December | 0.275883E+10 | 0.360222E+10 | 0.240346E+10 | 0.133539E+10 | 0.106807E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.508985E+11 | 0.311271E+11 | 0.388427E+11 | 0.188626E+11 | 0.199801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257925E+10 | 0.169392E+10 | 0.237652E+10 | 0.108870E+10 | 0.106807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.641579E+10 | 0.360222E+10 | 0.434210E+10 | 0.227774E+10 | 0.224689E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132203E+11 | 0.537297E+10 | 0.915332E+10 | 0.671438E+10 | 0.243894E+10 | 0.00 | 0.00 |
February | 0.881856E+10 | 0.447151E+10 | 0.649782E+10 | 0.400232E+10 | 0.249551E+10 | 0.00 | 0.00 |
March | 0.763575E+10 | 0.517476E+10 | 0.573531E+10 | 0.277042E+10 | 0.296488E+10 | 0.00 | 0.00 |
April | 0.660241E+10 | 0.417435E+10 | 0.463741E+10 | 0.176829E+10 | 0.286912E+10 | 0.00 | 0.00 |
May | 0.393482E+10 | 0.380462E+10 | 0.341227E+10 | 0.419926E+09 | 0.299234E+10 | 0.00 | 0.00 |
June | 0.333824E+10 | 0.290642E+10 | 0.289690E+10 | 0.174904E+09 | 0.272200E+10 | 0.00 | 0.00 |
July | 0.427596E+10 | 0.264796E+10 | 0.317090E+10 | 0.356953E+09 | 0.281395E+10 | 0.00 | 0.00 |
August | 0.637767E+10 | 0.275848E+10 | 0.407366E+10 | 0.128496E+10 | 0.278870E+10 | 0.00 | 0.00 |
September | 0.864442E+10 | 0.314981E+10 | 0.548564E+10 | 0.277976E+10 | 0.270588E+10 | 0.00 | 0.00 |
October | 0.113577E+11 | 0.356143E+10 | 0.720900E+10 | 0.481942E+10 | 0.238958E+10 | 0.00 | 0.00 |
November | 0.122052E+11 | 0.482509E+10 | 0.847917E+10 | 0.598616E+10 | 0.249301E+10 | 0.00 | 0.00 |
December | 0.141661E+11 | 0.547988E+10 | 0.977867E+10 | 0.744284E+10 | 0.233583E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100577E+12 | 0.483273E+11 | 0.705301E+11 | 0.385203E+11 | 0.320097E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333824E+10 | 0.264796E+10 | 0.289690E+10 | 0.174904E+09 | 0.233583E+10 | 0.00 | 0.00 |
Maximum of Months | 0.141661E+11 | 0.547988E+10 | 0.977867E+10 | 0.744284E+10 | 0.299234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.281325E+10 | 0.406281E+10 | 0.237406E+10 | 0.119737E+10 | 0.117669E+10 | 0.00 | 0.00 |
February | 0.288142E+10 | 0.346576E+10 | 0.255817E+10 | 0.118097E+10 | 0.137720E+10 | 0.00 | 0.00 |
March | 0.370298E+10 | 0.393162E+10 | 0.324653E+10 | 0.143632E+10 | 0.181021E+10 | 0.00 | 0.00 |
April | 0.568842E+10 | 0.317002E+10 | 0.433115E+10 | 0.225522E+10 | 0.207593E+10 | 0.00 | 0.00 |
May | 0.570130E+10 | 0.272510E+10 | 0.439637E+10 | 0.203068E+10 | 0.236569E+10 | 0.00 | 0.00 |
June | 0.618263E+10 | 0.216439E+10 | 0.450723E+10 | 0.225353E+10 | 0.225370E+10 | 0.00 | 0.00 |
July | 0.712011E+10 | 0.205617E+10 | 0.493030E+10 | 0.263816E+10 | 0.229214E+10 | 0.00 | 0.00 |
August | 0.674915E+10 | 0.218451E+10 | 0.462559E+10 | 0.250688E+10 | 0.211871E+10 | 0.00 | 0.00 |
September | 0.546958E+10 | 0.226758E+10 | 0.383260E+10 | 0.205077E+10 | 0.178183E+10 | 0.00 | 0.00 |
October | 0.434915E+10 | 0.270921E+10 | 0.302751E+10 | 0.165289E+10 | 0.137462E+10 | 0.00 | 0.00 |
November | 0.319820E+10 | 0.377955E+10 | 0.264653E+10 | 0.138432E+10 | 0.126221E+10 | 0.00 | 0.00 |
December | 0.284509E+10 | 0.442942E+10 | 0.241525E+10 | 0.129543E+10 | 0.111983E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.567013E+11 | 0.369461E+11 | 0.428913E+11 | 0.218825E+11 | 0.210088E+11 | 0.00 | 0.00 |
Minimum of Months | 0.281325E+10 | 0.205617E+10 | 0.237406E+10 | 0.118097E+10 | 0.111983E+10 | 0.00 | 0.00 |
Maximum of Months | 0.712011E+10 | 0.442942E+10 | 0.493030E+10 | 0.263816E+10 | 0.236569E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.868809E+09 | 0.516811E+10 | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.00 | 0.00 |
February | 0.934214E+09 | 0.424345E+10 | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.00 | 0.00 |
March | 0.149951E+10 | 0.481474E+10 | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.00 | 0.00 |
April | 0.203029E+10 | 0.369046E+10 | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.00 | 0.00 |
May | 0.265917E+10 | 0.335040E+10 | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.00 | 0.00 |
June | 0.327868E+10 | 0.255798E+10 | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.00 | 0.00 |
July | 0.357411E+10 | 0.235390E+10 | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.00 | 0.00 |
August | 0.287366E+10 | 0.245989E+10 | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.00 | 0.00 |
September | 0.215394E+10 | 0.287267E+10 | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.00 | 0.00 |
October | 0.192785E+10 | 0.331886E+10 | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.00 | 0.00 |
November | 0.969166E+09 | 0.458382E+10 | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.00 | 0.00 |
December | 0.784595E+09 | 0.521472E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.235540E+11 | 0.446290E+11 | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.00 | 0.00 |
Minimum of Months | 0.784595E+09 | 0.235390E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Maximum of Months | 0.357411E+10 | 0.521472E+10 | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291710E+10 | 0.335098E+10 | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.00 | 0.00 |
February | 0.260350E+10 | 0.275928E+10 | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.00 | 0.00 |
March | 0.366909E+10 | 0.312415E+10 | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.00 | 0.00 |
April | 0.519420E+10 | 0.247331E+10 | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.00 | 0.00 |
May | 0.485355E+10 | 0.233361E+10 | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.00 | 0.00 |
June | 0.501835E+10 | 0.180641E+10 | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.00 | 0.00 |
July | 0.634217E+10 | 0.168472E+10 | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.00 | 0.00 |
August | 0.634762E+10 | 0.171865E+10 | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.00 | 0.00 |
September | 0.421787E+10 | 0.192697E+10 | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.00 | 0.00 |
October | 0.392779E+10 | 0.219101E+10 | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.00 | 0.00 |
November | 0.285400E+10 | 0.297905E+10 | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.00 | 0.00 |
December | 0.280706E+10 | 0.336427E+10 | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.507523E+11 | 0.297124E+11 | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260350E+10 | 0.168472E+10 | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.634762E+10 | 0.336427E+10 | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131446E+11 | 0.527641E+10 | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.00 | 0.00 |
February | 0.875686E+10 | 0.431873E+10 | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.00 | 0.00 |
March | 0.761860E+10 | 0.495461E+10 | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.00 | 0.00 |
April | 0.660496E+10 | 0.397137E+10 | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.00 | 0.00 |
May | 0.393180E+10 | 0.368096E+10 | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.00 | 0.00 |
June | 0.336363E+10 | 0.277274E+10 | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.00 | 0.00 |
July | 0.431477E+10 | 0.253736E+10 | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.00 | 0.00 |
August | 0.638214E+10 | 0.268280E+10 | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.00 | 0.00 |
September | 0.858167E+10 | 0.308495E+10 | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.00 | 0.00 |
October | 0.112800E+11 | 0.348871E+10 | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.00 | 0.00 |
November | 0.121321E+11 | 0.468061E+10 | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.00 | 0.00 |
December | 0.141000E+11 | 0.530211E+10 | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100211E+12 | 0.467514E+11 | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.00 | 0.00 |
Minimum of Months | 0.336363E+10 | 0.253736E+10 | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.00 | 0.00 |
Maximum of Months | 0.141000E+11 | 0.530211E+10 | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290944E+10 | 0.360815E+10 | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.00 | 0.00 |
February | 0.297868E+10 | 0.298603E+10 | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.00 | 0.00 |
March | 0.383389E+10 | 0.336876E+10 | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.00 | 0.00 |
April | 0.581123E+10 | 0.273203E+10 | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.00 | 0.00 |
May | 0.571977E+10 | 0.253762E+10 | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.00 | 0.00 |
June | 0.622272E+10 | 0.194546E+10 | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.00 | 0.00 |
July | 0.719736E+10 | 0.182882E+10 | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.00 | 0.00 |
August | 0.685140E+10 | 0.189664E+10 | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.00 | 0.00 |
September | 0.548438E+10 | 0.209231E+10 | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.00 | 0.00 |
October | 0.442714E+10 | 0.239892E+10 | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.00 | 0.00 |
November | 0.332134E+10 | 0.322115E+10 | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.00 | 0.00 |
December | 0.300709E+10 | 0.367621E+10 | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.577645E+11 | 0.322921E+11 | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.00 | 0.00 |
Minimum of Months | 0.290944E+10 | 0.182882E+10 | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.719736E+10 | 0.367621E+10 | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101848E+10 | 0.465565E+10 | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.00 | 0.00 |
February | 0.106846E+10 | 0.381892E+10 | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.00 | 0.00 |
March | 0.162996E+10 | 0.444255E+10 | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.00 | 0.00 |
April | 0.208994E+10 | 0.348763E+10 | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.00 | 0.00 |
May | 0.273623E+10 | 0.318359E+10 | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.00 | 0.00 |
June | 0.327438E+10 | 0.247662E+10 | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.00 | 0.00 |
July | 0.353037E+10 | 0.230837E+10 | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.00 | 0.00 |
August | 0.284932E+10 | 0.240084E+10 | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.00 | 0.00 |
September | 0.217479E+10 | 0.274096E+10 | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.00 | 0.00 |
October | 0.198365E+10 | 0.311592E+10 | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.00 | 0.00 |
November | 0.109833E+10 | 0.417086E+10 | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.00 | 0.00 |
December | 0.937750E+09 | 0.468682E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.243917E+11 | 0.414887E+11 | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.00 | 0.00 |
Minimum of Months | 0.937750E+09 | 0.230837E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Maximum of Months | 0.353037E+10 | 0.468682E+10 | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.304789E+10 | 0.304473E+10 | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.00 | 0.00 |
February | 0.270929E+10 | 0.250725E+10 | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.00 | 0.00 |
March | 0.376734E+10 | 0.290798E+10 | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.00 | 0.00 |
April | 0.523582E+10 | 0.236261E+10 | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.00 | 0.00 |
May | 0.490073E+10 | 0.223419E+10 | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.00 | 0.00 |
June | 0.502534E+10 | 0.175751E+10 | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.00 | 0.00 |
July | 0.632535E+10 | 0.165975E+10 | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.00 | 0.00 |
August | 0.633773E+10 | 0.168576E+10 | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.00 | 0.00 |
September | 0.423674E+10 | 0.184975E+10 | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.00 | 0.00 |
October | 0.397141E+10 | 0.207749E+10 | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.00 | 0.00 |
November | 0.295362E+10 | 0.274938E+10 | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.00 | 0.00 |
December | 0.294014E+10 | 0.305868E+10 | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.514514E+11 | 0.278951E+11 | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.00 | 0.00 |
Minimum of Months | 0.270929E+10 | 0.165975E+10 | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.633773E+10 | 0.305868E+10 | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132771E+11 | 0.487500E+10 | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.00 | 0.00 |
February | 0.886204E+10 | 0.396399E+10 | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.00 | 0.00 |
March | 0.771752E+10 | 0.462055E+10 | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.00 | 0.00 |
April | 0.663443E+10 | 0.378335E+10 | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.00 | 0.00 |
May | 0.397771E+10 | 0.350011E+10 | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.00 | 0.00 |
June | 0.335856E+10 | 0.268652E+10 | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.00 | 0.00 |
July | 0.427464E+10 | 0.249470E+10 | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.00 | 0.00 |
August | 0.634420E+10 | 0.262766E+10 | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.00 | 0.00 |
September | 0.857215E+10 | 0.297048E+10 | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.00 | 0.00 |
October | 0.113025E+11 | 0.333178E+10 | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.00 | 0.00 |
November | 0.122213E+11 | 0.437698E+10 | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.00 | 0.00 |
December | 0.142320E+11 | 0.491901E+10 | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100774E+12 | 0.441501E+11 | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335856E+10 | 0.249470E+10 | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.00 | 0.00 |
Maximum of Months | 0.142320E+11 | 0.491901E+10 | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297791E+10 | 0.333130E+10 | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.00 | 0.00 |
February | 0.303809E+10 | 0.275438E+10 | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.00 | 0.00 |
March | 0.388346E+10 | 0.315939E+10 | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.00 | 0.00 |
April | 0.581092E+10 | 0.261829E+10 | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.00 | 0.00 |
May | 0.572023E+10 | 0.243444E+10 | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.00 | 0.00 |
June | 0.619099E+10 | 0.189315E+10 | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.00 | 0.00 |
July | 0.714785E+10 | 0.179715E+10 | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.00 | 0.00 |
August | 0.680892E+10 | 0.186001E+10 | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.00 | 0.00 |
September | 0.546733E+10 | 0.202213E+10 | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.00 | 0.00 |
October | 0.443533E+10 | 0.228980E+10 | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.00 | 0.00 |
November | 0.337264E+10 | 0.300182E+10 | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.00 | 0.00 |
December | 0.307706E+10 | 0.339311E+10 | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579307E+11 | 0.305550E+11 | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.00 | 0.00 |
Minimum of Months | 0.297791E+10 | 0.179715E+10 | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.714785E+10 | 0.339311E+10 | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.340802E+11 | -0.330572E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102302E+10 | 58.98 | 0.00 | 0.00 |
February | 0.310002E+11 | -0.300738E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -926446290.9 | 58.98 | 0.00 | 0.00 |
March | 0.360212E+11 | -0.349931E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102814E+10 | 58.98 | 0.00 | 0.00 |
April | 0.320570E+11 | -0.310659E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991094395.8 | 58.97 | 0.00 | 0.00 |
May | 0.333518E+11 | -0.323251E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102667E+10 | 58.97 | 0.00 | 0.00 |
June | 0.323049E+11 | -0.313106E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -994294138.3 | 58.97 | 0.00 | 0.00 |
July | 0.303463E+11 | -0.293252E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102113E+10 | 58.97 | 0.00 | 0.00 |
August | 0.330871E+11 | -0.320615E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102564E+10 | 58.98 | 0.00 | 0.00 |
September | 0.304284E+11 | -0.294381E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990305410.5 | 58.97 | 0.00 | 0.00 |
October | 0.320815E+11 | -0.310612E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102035E+10 | 58.96 | 0.00 | 0.00 |
November | 0.322680E+11 | -0.312804E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987544261.9 | 58.96 | 0.00 | 0.00 |
December | 0.328592E+11 | -0.318385E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102074E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.389886E+12 | -0.377831E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120554E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.303463E+11 | -0.349931E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102814E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.360212E+11 | -0.293252E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -926446290.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7834.21 | 37.54 | 285.17 | 281.00 | 1692.61 | 26.81 | 208.83 | 265.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 6954.72 | 35.76 | 275.67 | 274.67 | 1248.96 | 24.79 | 216.50 | 252.83 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2064.61 | 20.44 | 98.67 | 315.50 | 997.95 | 21.27 | 198.83 | 286.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1359.72 | 19.63 | 36.83 | 332.67 | 823.48 | 20.98 | 159.00 | 297.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1170.42 | 19.42 | 0.67 | 365.67 | 671.75 | 20.77 | 160.00 | 322.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1041.19 | 19.06 | 0.00 | 358.00 | 616.90 | 20.44 | 112.83 | 310.50 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 1050.72 | 19.08 | 1.00 | 368.00 | 642.36 | 20.48 | 143.83 | 331.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1173.52 | 19.23 | 8.83 | 354.83 | 726.09 | 20.59 | 153.33 | 317.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:49 | 1704.23 | 20.26 | 53.83 | 309.50 | 947.22 | 21.03 | 152.83 | 277.83 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3856.03 | 27.17 | 157.00 | 304.50 | 1165.20 | 21.76 | 138.67 | 276.17 |
November | 300.00 | 0.50 | 0.48 | 01-NOV-06:49 | 7582.60 | 37.31 | 294.83 | 279.50 | 1521.54 | 26.38 | 219.83 | 270.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7708.79 | 38.42 | 293.33 | 283.00 | 2157.92 | 29.56 | 209.33 | 271.50 |
Annual Sum or Average | 4065.67 | 0.50 | 3305.90 | 25.21 | 1505.83 | 3826.83 | 1052.24 | 22.61 | 2073.83 | 3479.67 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 1041.19 | 19.06 | 0.00 | 274.67 | 616.90 | 20.44 | 112.83 | 252.83 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7834.21 | 38.42 | 294.83 | 368.00 | 2157.92 | 29.56 | 219.83 | 331.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:19 | 1740.26 | 23.79 | 90.00 | 266.33 | 882.61 | 23.58 | 112.00 | 229.00 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1902.41 | 23.87 | 87.17 | 268.33 | 993.02 | 23.92 | 119.00 | 224.00 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2318.77 | 23.78 | 107.17 | 317.50 | 1263.35 | 23.98 | 141.67 | 279.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2350.46 | 23.18 | 93.83 | 339.00 | 1242.06 | 23.53 | 104.17 | 308.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2266.06 | 22.53 | 99.67 | 377.83 | 1233.25 | 23.12 | 126.00 | 333.17 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2258.88 | 21.75 | 89.33 | 369.33 | 1197.37 | 22.41 | 90.00 | 326.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:19 | 2487.22 | 22.18 | 99.67 | 378.17 | 1309.51 | 22.70 | 95.33 | 342.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:49 | 2500.57 | 22.99 | 103.33 | 363.17 | 1273.62 | 23.23 | 91.67 | 329.17 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:40 | 2610.78 | 23.28 | 98.83 | 312.67 | 989.90 | 22.25 | 86.50 | 277.00 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2360.91 | 23.19 | 89.17 | 286.33 | 971.28 | 22.12 | 89.50 | 241.33 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1983.63 | 24.04 | 98.50 | 264.83 | 1071.05 | 23.98 | 125.83 | 233.67 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1739.47 | 24.25 | 97.83 | 267.33 | 904.18 | 23.92 | 108.00 | 226.50 |
Annual Sum or Average | 4065.67 | 0.50 | 2234.51 | 23.16 | 1154.50 | 3810.83 | 1128.12 | 23.20 | 1289.67 | 3350.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1739.47 | 21.75 | 87.17 | 264.83 | 882.61 | 22.12 | 86.50 | 224.00 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2610.78 | 24.25 | 107.17 | 378.17 | 1309.51 | 23.98 | 141.67 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 553.44 | 16.92 | 0.00 | 237.50 | 357.08 | 18.68 | 0.00 | 163.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:30 | 659.33 | 17.67 | 0.00 | 249.00 | 403.28 | 19.16 | 0.00 | 178.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:00 | 770.98 | 17.99 | 0.00 | 306.50 | 459.53 | 19.31 | 6.50 | 251.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 860.57 | 19.15 | 0.00 | 336.33 | 545.08 | 20.53 | 63.83 | 297.33 |
May | 393.83 | 0.49 | 0.48 | 01-MAY-06:30 | 1067.79 | 19.84 | 27.00 | 382.50 | 619.37 | 21.15 | 156.00 | 352.17 |
June | 381.00 | 0.49 | 0.48 | 01-JUN-06:30 | 1128.29 | 21.52 | 83.17 | 375.00 | 668.82 | 22.71 | 181.00 | 341.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1060.36 | 21.41 | 84.83 | 385.00 | 622.39 | 21.20 | 174.33 | 360.67 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 872.98 | 19.23 | 7.17 | 364.33 | 561.51 | 20.58 | 85.17 | 337.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 769.32 | 18.47 | 0.00 | 305.50 | 490.54 | 19.91 | 8.50 | 259.17 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 589.17 | 17.10 | 0.00 | 263.50 | 384.16 | 18.68 | 0.50 | 184.33 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:40 | 561.97 | 16.50 | 0.00 | 241.00 | 359.57 | 18.15 | 0.00 | 171.00 |
December | 297.00 | 0.54 | 0.48 | 01-DEC-08:20 | 504.20 | 16.19 | 0.00 | 230.50 | 331.02 | 18.02 | 0.00 | 144.00 |
Annual Sum or Average | 4065.67 | 0.51 | 808.33 | 18.70 | 202.17 | 3676.67 | 497.33 | 19.99 | 675.83 | 3040.67 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 504.20 | 16.19 | 0.00 | 230.50 | 331.02 | 18.02 | 0.00 | 144.00 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 1128.29 | 21.52 | 84.83 | 385.00 | 668.82 | 22.71 | 181.00 | 360.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:39 | 2255.51 | 24.57 | 107.00 | 254.00 | 847.70 | 22.81 | 118.83 | 215.83 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:30 | 2076.54 | 23.92 | 90.00 | 256.83 | 1106.99 | 24.08 | 134.00 | 217.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:00 | 2315.05 | 23.32 | 101.17 | 311.00 | 1243.51 | 23.54 | 143.33 | 270.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 3186.72 | 22.08 | 82.33 | 332.83 | 1200.26 | 20.07 | 77.33 | 300.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2991.13 | 20.10 | 52.83 | 368.83 | 1210.03 | 20.25 | 97.17 | 330.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2536.68 | 17.89 | 0.00 | 362.17 | 1370.32 | 20.26 | 91.17 | 327.00 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:19 | 2675.91 | 17.95 | 5.67 | 372.17 | 1415.82 | 20.18 | 89.17 | 344.83 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:30 | 3304.97 | 21.76 | 88.33 | 356.17 | 1338.49 | 20.25 | 81.33 | 327.17 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:19 | 2946.08 | 24.52 | 106.67 | 306.67 | 1511.97 | 24.33 | 115.00 | 273.50 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2821.19 | 25.26 | 114.33 | 288.17 | 1117.57 | 23.53 | 105.33 | 244.17 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-07:49 | 2203.59 | 24.41 | 106.50 | 257.17 | 1199.47 | 24.34 | 135.67 | 218.67 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:20 | 2002.04 | 24.40 | 110.17 | 249.00 | 1101.35 | 24.30 | 121.83 | 204.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2645.64 | 22.23 | 965.00 | 3715.00 | 1235.74 | 22.12 | 1310.17 | 3274.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 2002.04 | 17.89 | 0.00 | 249.00 | 847.70 | 20.07 | 77.33 | 204.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3304.97 | 25.26 | 114.33 | 372.17 | 1511.97 | 24.34 | 143.33 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7903.14 | 37.01 | 284.83 | 281.00 | 1804.16 | 22.57 | 97.17 | 266.17 |
February | 279.67 | 0.49 | 0.48 | 01-FEB-07:19 | 6996.72 | 35.33 | 275.00 | 274.67 | 1338.60 | 20.76 | 61.00 | 254.67 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2099.74 | 14.21 | 11.17 | 315.83 | 1069.13 | 17.03 | 3.33 | 290.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1395.33 | 13.61 | 0.00 | 333.17 | 883.80 | 17.15 | 0.00 | 304.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1191.53 | 13.60 | 0.00 | 366.17 | 716.59 | 17.05 | 0.00 | 329.83 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1061.27 | 13.38 | 0.00 | 358.00 | 658.25 | 16.84 | 0.00 | 316.00 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:10 | 1073.76 | 13.53 | 0.00 | 368.83 | 686.43 | 17.03 | 0.00 | 335.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1204.37 | 13.51 | 0.00 | 355.00 | 778.76 | 17.01 | 0.00 | 323.83 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:49 | 1747.15 | 14.15 | 14.00 | 309.83 | 1018.93 | 16.90 | 0.17 | 282.67 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3916.32 | 23.17 | 141.67 | 304.67 | 1256.29 | 17.15 | 14.00 | 279.50 |
November | 300.00 | 0.50 | 0.48 | 01-NOV-06:49 | 7642.30 | 36.90 | 294.67 | 279.67 | 1624.68 | 22.18 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:10 | 7779.55 | 38.00 | 293.00 | 283.17 | 2272.76 | 25.99 | 142.83 | 272.83 |
Annual Sum or Average | 4065.67 | 0.50 | 3346.46 | 21.04 | 1314.33 | 3830.00 | 1123.83 | 18.71 | 411.17 | 3526.50 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 1061.27 | 13.38 | 0.00 | 274.67 | 658.25 | 16.84 | 0.00 | 254.67 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7903.14 | 38.00 | 294.67 | 368.83 | 2272.76 | 25.99 | 142.83 | 335.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:19 | 1773.54 | 21.07 | 85.00 | 266.50 | 926.85 | 21.54 | 55.00 | 234.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1908.04 | 19.70 | 70.83 | 268.50 | 1040.46 | 21.79 | 54.50 | 229.67 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2362.09 | 21.00 | 106.50 | 318.00 | 1315.39 | 21.84 | 77.67 | 284.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2392.29 | 19.99 | 93.67 | 339.83 | 1304.42 | 20.99 | 65.17 | 311.00 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2296.57 | 19.34 | 99.33 | 378.83 | 1289.96 | 20.62 | 70.17 | 338.33 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2295.22 | 18.50 | 88.83 | 369.83 | 1254.22 | 19.82 | 60.67 | 333.33 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:19 | 2523.26 | 19.00 | 99.67 | 378.83 | 1372.91 | 20.12 | 68.67 | 348.33 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:40 | 2534.79 | 19.85 | 103.33 | 363.17 | 1337.25 | 20.68 | 69.67 | 334.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:40 | 2657.11 | 20.47 | 98.83 | 313.50 | 1044.26 | 19.69 | 43.67 | 281.50 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2403.89 | 20.34 | 88.83 | 287.00 | 1020.31 | 19.67 | 42.50 | 246.83 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 2011.64 | 21.37 | 95.17 | 265.50 | 1115.31 | 22.13 | 68.33 | 238.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1747.67 | 20.72 | 86.17 | 266.67 | 947.66 | 22.12 | 64.33 | 232.33 |
Annual Sum or Average | 4065.67 | 0.50 | 2267.40 | 20.03 | 1116.17 | 3816.17 | 1182.12 | 20.86 | 740.33 | 3411.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1747.67 | 18.50 | 70.83 | 265.50 | 926.85 | 19.67 | 42.50 | 229.67 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2657.11 | 21.37 | 106.50 | 378.83 | 1372.91 | 22.13 | 77.67 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 562.61 | 11.18 | 0.00 | 238.17 | 380.37 | 14.99 | 0.00 | 178.83 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:30 | 670.49 | 12.14 | 0.00 | 250.00 | 429.47 | 15.69 | 0.00 | 191.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 784.95 | 12.60 | 0.00 | 306.83 | 489.53 | 15.97 | 0.00 | 260.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 880.11 | 13.79 | 0.00 | 336.33 | 582.18 | 17.34 | 0.00 | 304.33 |
May | 393.83 | 0.49 | 0.48 | 01-MAY-06:30 | 1088.32 | 14.12 | 0.00 | 382.83 | 659.72 | 17.67 | 0.00 | 355.83 |
June | 381.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1151.37 | 16.32 | 42.50 | 375.67 | 711.92 | 19.54 | 40.83 | 347.17 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1085.28 | 16.41 | 45.17 | 385.33 | 665.28 | 17.86 | 0.00 | 363.17 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:00 | 903.29 | 13.91 | 0.00 | 366.00 | 599.55 | 17.49 | 0.00 | 341.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 785.80 | 13.12 | 0.00 | 305.67 | 523.62 | 16.65 | 0.00 | 265.67 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 601.91 | 11.58 | 0.00 | 265.33 | 410.11 | 15.26 | 0.00 | 200.17 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:30 | 571.72 | 11.05 | 0.00 | 242.50 | 383.10 | 14.64 | 0.00 | 185.50 |
December | 297.00 | 0.54 | 0.48 | 01-DEC-08:09 | 512.27 | 10.52 | 0.00 | 231.33 | 352.60 | 14.31 | 0.00 | 160.17 |
Annual Sum or Average | 4065.67 | 0.51 | 825.79 | 13.28 | 87.67 | 3686.00 | 530.37 | 16.62 | 40.83 | 3153.83 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 512.27 | 10.52 | 0.00 | 231.33 | 352.60 | 14.31 | 0.00 | 160.17 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 1151.37 | 16.41 | 45.17 | 385.33 | 711.92 | 19.54 | 40.83 | 363.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-08:39 | 2287.66 | 22.15 | 105.33 | 255.00 | 892.02 | 20.70 | 45.33 | 221.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:30 | 2115.91 | 21.17 | 85.17 | 257.83 | 1156.95 | 21.96 | 60.00 | 222.83 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 2363.75 | 20.51 | 100.83 | 311.50 | 1296.79 | 21.32 | 71.50 | 275.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:10 | 3227.04 | 18.73 | 82.33 | 333.33 | 1266.85 | 16.74 | 0.00 | 304.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:00 | 3021.86 | 16.17 | 52.50 | 369.50 | 1273.28 | 16.87 | 0.00 | 336.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:49 | 2579.83 | 13.21 | 0.00 | 364.00 | 1435.04 | 16.79 | 0.00 | 330.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:19 | 2715.48 | 13.35 | 5.67 | 372.50 | 1484.59 | 16.71 | 0.00 | 348.83 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:30 | 3336.07 | 18.40 | 88.17 | 357.33 | 1405.95 | 16.95 | 7.00 | 330.83 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:10 | 2994.72 | 21.43 | 104.83 | 307.50 | 1577.89 | 21.99 | 73.67 | 277.50 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 2851.12 | 21.90 | 107.83 | 289.00 | 1172.20 | 21.22 | 58.50 | 250.33 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-07:40 | 2238.33 | 21.98 | 104.33 | 258.33 | 1245.91 | 22.49 | 75.00 | 225.50 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-08:09 | 2032.80 | 22.00 | 104.67 | 251.00 | 1145.04 | 22.54 | 74.67 | 211.17 |
Annual Sum or Average | 4065.67 | 0.51 | 2683.19 | 18.88 | 941.67 | 3726.83 | 1294.19 | 19.40 | 465.67 | 3334.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 2032.80 | 13.21 | 0.00 | 251.00 | 892.02 | 16.71 | 0.00 | 211.17 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 3336.07 | 22.15 | 107.83 | 372.50 | 1577.89 | 22.54 | 75.00 | 348.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7904.48 | 37.00 | 284.83 | 281.00 | 1806.00 | 22.56 | 97.17 | 266.17 |
February | 279.67 | 0.49 | 0.48 | 01-FEB-07:19 | 6999.06 | 35.32 | 275.00 | 274.67 | 1340.45 | 20.75 | 61.00 | 254.83 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2102.26 | 14.18 | 11.17 | 316.00 | 1070.72 | 17.02 | 3.33 | 290.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1396.94 | 13.58 | 0.00 | 333.17 | 884.89 | 17.13 | 0.00 | 304.50 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1193.09 | 13.57 | 0.00 | 366.17 | 717.60 | 17.03 | 0.00 | 330.00 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1062.50 | 13.35 | 0.00 | 358.17 | 659.10 | 16.83 | 0.00 | 316.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:10 | 1074.84 | 13.50 | 0.00 | 368.83 | 687.25 | 17.01 | 0.00 | 335.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1205.61 | 13.48 | 0.00 | 355.00 | 779.67 | 17.00 | 0.00 | 324.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:49 | 1749.07 | 14.12 | 14.00 | 309.83 | 1020.18 | 16.88 | 0.17 | 283.00 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3918.21 | 23.15 | 141.67 | 304.67 | 1257.64 | 17.13 | 14.00 | 279.50 |
November | 300.00 | 0.50 | 0.48 | 01-NOV-06:49 | 7643.96 | 36.90 | 294.67 | 279.67 | 1626.48 | 22.17 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:10 | 7780.51 | 37.99 | 293.00 | 283.17 | 2274.50 | 25.98 | 142.83 | 272.83 |
Annual Sum or Average | 4065.67 | 0.50 | 3348.05 | 21.02 | 1314.33 | 3830.33 | 1125.13 | 18.70 | 411.17 | 3527.83 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 1062.50 | 13.35 | 0.00 | 274.67 | 659.10 | 16.83 | 0.00 | 254.83 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7904.48 | 37.99 | 294.67 | 368.83 | 2274.50 | 25.98 | 142.83 | 335.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:19 | 1774.21 | 21.04 | 85.00 | 266.50 | 927.70 | 21.53 | 55.00 | 234.50 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1909.11 | 19.67 | 70.83 | 268.50 | 1041.49 | 21.78 | 54.50 | 229.67 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2363.57 | 20.97 | 106.50 | 318.00 | 1316.59 | 21.83 | 77.67 | 284.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2393.52 | 19.96 | 93.67 | 339.83 | 1305.56 | 20.97 | 65.17 | 311.00 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2298.09 | 19.31 | 99.17 | 378.83 | 1291.20 | 20.60 | 70.17 | 338.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2296.56 | 18.47 | 88.83 | 369.83 | 1255.37 | 19.81 | 60.67 | 333.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:19 | 2524.43 | 18.97 | 99.67 | 378.83 | 1374.07 | 20.11 | 68.67 | 348.67 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:40 | 2535.80 | 19.82 | 103.33 | 363.50 | 1338.32 | 20.66 | 69.67 | 334.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:40 | 2658.19 | 20.44 | 98.83 | 313.50 | 1045.27 | 19.68 | 43.67 | 281.67 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2404.72 | 20.31 | 88.83 | 287.00 | 1021.15 | 19.66 | 42.50 | 247.00 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 2012.38 | 21.34 | 95.17 | 265.50 | 1116.16 | 22.12 | 68.33 | 238.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1748.18 | 20.70 | 86.17 | 266.83 | 948.37 | 22.11 | 64.33 | 232.33 |
Annual Sum or Average | 4065.67 | 0.50 | 2268.48 | 20.01 | 1116.00 | 3816.67 | 1183.15 | 20.84 | 740.33 | 3413.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1748.18 | 18.47 | 70.83 | 265.50 | 927.70 | 19.66 | 42.50 | 229.67 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2658.19 | 21.34 | 106.50 | 378.83 | 1374.07 | 22.12 | 77.67 | 348.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 562.93 | 11.14 | 0.00 | 238.50 | 380.78 | 14.97 | 0.00 | 178.83 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:30 | 671.07 | 12.11 | 0.00 | 250.00 | 430.00 | 15.67 | 0.00 | 191.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 785.76 | 12.57 | 0.00 | 306.83 | 490.18 | 15.96 | 0.00 | 260.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 880.79 | 13.76 | 0.00 | 336.33 | 582.83 | 17.32 | 0.00 | 304.50 |
May | 393.83 | 0.49 | 0.48 | 01-MAY-06:30 | 1089.44 | 14.09 | 0.00 | 382.83 | 660.59 | 17.66 | 0.00 | 356.00 |
June | 381.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1152.48 | 16.29 | 42.50 | 375.67 | 712.80 | 19.53 | 40.83 | 347.33 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1086.12 | 16.38 | 45.17 | 385.33 | 666.06 | 17.85 | 0.00 | 363.17 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:00 | 903.90 | 13.88 | 0.00 | 366.17 | 600.19 | 17.47 | 0.00 | 341.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 786.37 | 13.09 | 0.00 | 305.67 | 524.19 | 16.63 | 0.00 | 266.17 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 602.30 | 11.54 | 0.00 | 265.50 | 410.53 | 15.25 | 0.00 | 200.50 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:30 | 572.08 | 11.01 | 0.00 | 243.00 | 383.52 | 14.62 | 0.00 | 186.00 |
December | 297.00 | 0.54 | 0.48 | 01-DEC-08:09 | 512.51 | 10.49 | 0.00 | 231.33 | 352.96 | 14.29 | 0.00 | 160.50 |
Annual Sum or Average | 4065.67 | 0.51 | 826.45 | 13.25 | 87.67 | 3687.17 | 530.99 | 16.60 | 40.83 | 3156.33 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 512.51 | 10.49 | 0.00 | 231.33 | 352.96 | 14.29 | 0.00 | 160.50 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 1152.48 | 16.38 | 45.17 | 385.33 | 712.80 | 19.53 | 40.83 | 363.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-08:39 | 2288.37 | 22.13 | 105.33 | 255.00 | 892.93 | 20.68 | 45.33 | 221.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:30 | 2116.97 | 21.14 | 85.17 | 257.83 | 1158.06 | 21.95 | 60.00 | 223.00 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 2365.19 | 20.48 | 100.83 | 311.50 | 1298.06 | 21.31 | 71.50 | 275.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:10 | 3228.23 | 18.70 | 82.33 | 333.33 | 1268.09 | 16.72 | 0.00 | 304.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:00 | 3023.33 | 16.14 | 52.33 | 369.67 | 1274.57 | 16.86 | 0.00 | 336.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:49 | 2581.13 | 13.17 | 0.00 | 364.00 | 1436.35 | 16.77 | 0.00 | 330.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:19 | 2716.50 | 13.31 | 5.67 | 372.50 | 1485.84 | 16.69 | 0.00 | 348.83 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:30 | 3337.08 | 18.37 | 88.17 | 357.33 | 1407.12 | 16.93 | 7.00 | 331.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:10 | 2995.91 | 21.41 | 104.83 | 307.50 | 1579.15 | 21.98 | 73.67 | 277.50 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 2851.96 | 21.87 | 107.83 | 289.00 | 1173.10 | 21.20 | 58.50 | 250.33 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-07:40 | 2239.10 | 21.96 | 104.33 | 258.33 | 1246.87 | 22.48 | 75.00 | 225.50 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-08:09 | 2033.35 | 21.97 | 104.67 | 251.00 | 1145.86 | 22.53 | 74.67 | 211.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2684.25 | 18.85 | 941.50 | 3727.00 | 1295.33 | 19.38 | 465.67 | 3335.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 2033.35 | 13.17 | 0.00 | 251.00 | 892.93 | 16.69 | 0.00 | 211.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 3337.08 | 22.13 | 107.83 | 372.50 | 1579.15 | 22.53 | 75.00 | 348.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.488393E+09 | 12985.35 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68364358.05 | 5828.06 | 09-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252464E+09 | 9430.86 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6906764.18 | 4940.53 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5435.95 | 0.79 | 03-MAY-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8542.68 | 0.84 | 28-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9438.40 | 0.90 | 19-JUL-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22601.90 | 0.98 | 31-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6585.18 | 0.80 | 06-SEP-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4650.73 | 0.82 | 19-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 289198.13 | 476.41 | 30-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139019E+09 | 7465.06 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.955493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4650.73 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.488393E+09 | 12985.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.754958E+10 | 144033.34 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184335E+10 | 71667.06 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.627367E+10 | 104825.55 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160505E+09 | 63568.80 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18435462.81 | 19338.27 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235732E+09 | 40583.48 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455901E+10 | 98880.37 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.754958E+10 | 144033.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183855E+10 | 122063.08 | 13-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399385E+09 | 59709.19 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.890008E+09 | 122047.61 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87036886.44 | 66535.98 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133706E+09 | 62053.08 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763414E+09 | 121845.70 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183855E+10 | 122063.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486232E+09 | 126894.65 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66187196.46 | 18952.38 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260418E+09 | 132348.57 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22502748.76 | 31652.56 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7685116.11 | 9876.28 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140163E+09 | 98322.50 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486232E+09 | 132348.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198696E+09 | 93856.90 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 663043.69 | 3450.81 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353229E+09 | 165392.29 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51411139.91 | 13373.87 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47314768.47 | 71859.38 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.353229E+09 | 165392.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.335817E+09 | 122412.88 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116685E+09 | 81774.82 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10729087.19 | 3139.02 | 01-APR-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43180462.00 | 29763.15 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.335817E+09 | 122412.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126056E+10 | 17498.12 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460532E+09 | 10066.27 | 09-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112740E+10 | 13732.36 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43711067.19 | 9147.26 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4689286.13 | 1948.81 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4987.90 | 0.84 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6690.92 | 0.92 | 31-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13751.96 | 0.91 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5207.57 | 0.66 | 28-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16617232.28 | 4499.89 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135511E+09 | 7463.26 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844235E+09 | 12835.83 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4987.90 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126056E+10 | 17498.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.393251E+09 | 66711.31 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59917667.06 | 22095.77 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10833832.53 | 2884.77 | 30-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7439739.30 | 2480.03 | 27-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41798739.01 | 26981.72 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393251E+09 | 66711.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110666E+10 | 12775.55 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.596778E+09 | 12769.86 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677418E+09 | 12724.49 | 28-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91331056.20 | 12727.61 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16048412.18 | 12689.99 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57538938.31 | 12685.51 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.379815E+09 | 12755.46 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.777588E+09 | 12728.03 | 11-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110666E+10 | 12775.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391076E+09 | 14524.75 | 03-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242306E+09 | 14521.53 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253578E+09 | 14516.86 | 30-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24126801.62 | 14480.54 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2094291.67 | 10479.11 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14683581.09 | 6028.15 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101221E+09 | 14511.34 | 08-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249871E+09 | 14506.27 | 14-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.391076E+09 | 14524.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348659E+09 | 18002.55 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244094E+09 | 18007.71 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.397498E+09 | 17945.24 | 30-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 56917496.91 | 17848.27 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30665377.02 | 17941.50 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5044756.64 | 992.60 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68607869.69 | 17925.32 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190971E+09 | 17865.60 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397498E+09 | 18007.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331715E+09 | 15082.72 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135781E+09 | 15048.71 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178834E+09 | 15051.44 | 15-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19234075.92 | 14758.07 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3539642.36 | 7143.67 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 682212.15 | 184.04 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66402214.94 | 11293.77 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184301E+09 | 15044.78 | 13-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.920490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331715E+09 | 15082.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 119.85 | 0.80 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82.18 | 0.82 | 15-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76.97 | 0.77 | 24-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 291.79 | 0.84 | 13-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 490.25 | 0.85 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 709.96 | 0.88 | 06-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1771.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 709.96 | 0.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.187112E+11 | 0.186711E+11 | 80484.04 | 18-JAN-14:10 | 80484.04 | 0.19 |
February | 0.00 | 0.00 | 0.109026E+11 | 0.108345E+11 | 75455.32 | 01-FEB-12:00 | 75455.32 | 0.16 |
March | 0.00 | 0.00 | 0.130551E+11 | 0.127018E+11 | 86557.75 | 23-MAR-14:00 | 74095.25 | 0.19 |
April | 0.00 | 0.00 | 0.296910E+11 | 0.296734E+11 | 99334.27 | 26-APR-13:50 | 99334.27 | 0.39 |
May | 0.00 | 0.00 | 0.258458E+11 | 0.257727E+11 | 71521.21 | 03-MAY-13:00 | 71521.21 | 0.42 |
June | 0.00 | 0.00 | 0.473497E+11 | 0.434224E+11 | 110158.79 | 29-JUN-13:00 | 73399.52 | 0.58 |
July | 0.00 | 0.00 | 0.875780E+11 | 0.654215E+11 | 153864.60 | 31-JUL-16:00 | 87032.14 | 0.71 |
August | 0.00 | 0.00 | 0.108515E+12 | 0.761623E+11 | 168820.68 | 07-AUG-10:40 | 99432.15 | 0.80 |
September | 0.00 | 0.00 | 0.532685E+11 | 0.450449E+11 | 124425.29 | 22-SEP-05:02 | 51503.84 | 0.54 |
October | 0.00 | 0.00 | 0.669074E+11 | 0.569439E+11 | 147846.93 | 05-OCT-04:12 | 69467.89 | 0.40 |
November | 0.00 | 0.00 | 0.230624E+11 | 0.227089E+11 | 86729.29 | 28-NOV-14:00 | 86729.29 | 0.23 |
December | 0.00 | 0.00 | 0.269324E+11 | 0.268653E+11 | 92657.00 | 05-DEC-15:00 | 92657.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.511819E+12 | 0.434223E+12 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.109026E+11 | 0.108345E+11 | 71521.21 | 51503.84 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.108515E+12 | 0.761623E+11 | 168820.68 | 99432.15 | 0.80 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.191014E+12 | 0.190588E+12 | 679674.72 | 18-JAN-13:05 | 679674.72 | 0.22 |
February | 0.00 | 0.00 | 0.114301E+12 | 0.113703E+12 | 633928.33 | 03-FEB-15:05 | 633928.33 | 0.18 |
March | 0.00 | 0.00 | 0.109448E+12 | 0.106642E+12 | 746171.67 | 23-MAR-14:05 | 615411.07 | 0.20 |
April | 0.00 | 0.00 | 0.207545E+12 | 0.207460E+12 | 799921.25 | 26-APR-14:05 | 799921.25 | 0.37 |
May | 0.00 | 0.00 | 0.212911E+12 | 0.212374E+12 | 631215.24 | 04-MAY-12:05 | 631215.24 | 0.42 |
June | 0.00 | 0.00 | 0.373490E+12 | 0.344448E+12 | 927706.85 | 29-JUN-13:00 | 624432.56 | 0.57 |
July | 0.00 | 0.00 | 0.653850E+12 | 0.497360E+12 | 1151924.47 | 28-JUL-12:30 | 693938.60 | 0.61 |
August | 0.00 | 0.00 | 0.768562E+12 | 0.557666E+12 | 1203322.21 | 07-AUG-10:05 | 711236.50 | 0.63 |
September | 0.00 | 0.00 | 0.450866E+12 | 0.384612E+12 | 1138060.64 | 30-SEP-05:02 | 1138060.64 | 0.54 |
October | 0.00 | 0.00 | 0.533331E+12 | 0.458534E+12 | 1245688.06 | 05-OCT-05:02 | 560695.93 | 0.39 |
November | 0.00 | 0.00 | 0.218934E+12 | 0.216282E+12 | 644953.37 | 28-NOV-14:00 | 644953.37 | 0.23 |
December | 0.00 | 0.00 | 0.229444E+12 | 0.228918E+12 | 702622.09 | 05-DEC-15:05 | 702622.09 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.406370E+13 | 0.351859E+13 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.109448E+12 | 0.106642E+12 | 631215.24 | 560695.93 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.768562E+12 | 0.557666E+12 | 1245688.06 | 1138060.64 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115662E+11 | 0.115414E+11 | 64955.05 | 18-JAN-13:50 | 64955.05 | 0.18 |
February | 0.00 | 0.00 | 0.634914E+10 | 0.630173E+10 | 55176.89 | 03-FEB-15:00 | 55176.89 | 0.15 |
March | 0.00 | 0.00 | 0.790772E+10 | 0.778890E+10 | 68780.23 | 23-MAR-14:00 | 62226.32 | 0.17 |
April | 0.00 | 0.00 | 0.199934E+11 | 0.199901E+11 | 93688.90 | 26-APR-14:00 | 93688.90 | 0.35 |
May | 0.00 | 0.00 | 0.203643E+11 | 0.203193E+11 | 70966.39 | 03-MAY-13:10 | 70966.39 | 0.40 |
June | 0.00 | 0.00 | 0.384768E+11 | 0.353220E+11 | 104142.28 | 29-JUN-13:00 | 69803.60 | 0.55 |
July | 0.00 | 0.00 | 0.696404E+11 | 0.529290E+11 | 150270.65 | 31-JUL-15:40 | 89349.80 | 0.59 |
August | 0.00 | 0.00 | 0.810754E+11 | 0.586424E+11 | 151622.98 | 14-AUG-13:40 | 92954.78 | 0.61 |
September | 0.00 | 0.00 | 0.440443E+11 | 0.378061E+11 | 120568.32 | 29-SEP-13:40 | 120568.32 | 0.51 |
October | 0.00 | 0.00 | 0.507875E+11 | 0.435588E+11 | 135739.41 | 03-OCT-13:10 | 81356.88 | 0.37 |
November | 0.00 | 0.00 | 0.124077E+11 | 0.123445E+11 | 60645.89 | 28-NOV-14:00 | 60645.89 | 0.20 |
December | 0.00 | 0.00 | 0.145072E+11 | 0.144820E+11 | 68362.56 | 05-DEC-15:00 | 68362.56 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.377120E+12 | 0.321026E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.634914E+10 | 0.630173E+10 | 55176.89 | 55176.89 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.810754E+11 | 0.586424E+11 | 151622.98 | 120568.32 | 0.61 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.103200E+11 | 0.102645E+11 | 61207.35 | 17-JAN-12:00 | 61207.35 | 0.12 |
February | 0.00 | 0.00 | 0.450828E+10 | 0.446298E+10 | 59851.49 | 13-FEB-06:02 | 26804.64 | 0.08 |
March | 0.00 | 0.00 | 0.511424E+10 | 0.504709E+10 | 44163.44 | 18-MAR-04:12 | 21841.77 | 0.10 |
April | 0.00 | 0.00 | 0.135654E+11 | 0.134558E+11 | 60347.99 | 27-APR-04:12 | 27615.70 | 0.25 |
May | 0.00 | 0.00 | 0.127815E+11 | 0.126722E+11 | 59176.58 | 03-MAY-04:12 | 26089.32 | 0.27 |
June | 0.00 | 0.00 | 0.233821E+11 | 0.226323E+11 | 77080.89 | 30-JUN-04:12 | 32879.73 | 0.38 |
July | 0.00 | 0.00 | 0.406492E+11 | 0.354082E+11 | 92344.07 | 31-JUL-09:10 | 56649.36 | 0.44 |
August | 0.00 | 0.00 | 0.463271E+11 | 0.390344E+11 | 109151.46 | 07-AUG-09:50 | 60390.90 | 0.49 |
September | 0.00 | 0.00 | 0.282003E+11 | 0.255894E+11 | 85729.26 | 22-SEP-04:13 | 35327.51 | 0.38 |
October | 0.00 | 0.00 | 0.374460E+11 | 0.330944E+11 | 93280.94 | 02-OCT-13:00 | 51563.47 | 0.29 |
November | 0.00 | 0.00 | 0.117432E+11 | 0.117082E+11 | 56802.54 | 10-NOV-06:03 | 29979.12 | 0.15 |
December | 0.00 | 0.00 | 0.146239E+11 | 0.146096E+11 | 75991.03 | 25-DEC-11:57 | 75991.03 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.248661E+12 | 0.227979E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.450828E+10 | 0.446298E+10 | 44163.44 | 21841.77 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.463271E+11 | 0.390344E+11 | 109151.46 | 75991.03 | 0.49 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.882186E+10 | 0.871802E+10 | 103243.51 | 14-JAN-11:00 | 103243.51 | 0.00 |
February | 0.00 | 0.00 | 0.890193E+10 | 0.873937E+10 | 191930.18 | 01-FEB-12:00 | 191930.18 | 0.00 |
March | 0.00 | 0.00 | 0.593759E+11 | 0.457556E+11 | 273731.84 | 23-MAR-14:00 | 204994.86 | 0.00 |
April | 0.00 | 0.00 | 0.350390E+12 | 0.254629E+12 | 402417.61 | 26-APR-11:00 | 339782.02 | 0.00 |
May | 0.00 | 0.00 | 0.128953E+10 | 0.115812E+10 | 54369.54 | 04-MAY-12:00 | 47320.39 | 0.00 |
June | 0.00 | 0.00 | 0.824113E+11 | 0.592087E+11 | 247184.84 | 29-JUN-11:00 | 165590.50 | 0.00 |
July | 0.00 | 0.00 | 0.489618E+12 | 0.296851E+12 | 427239.19 | 31-JUL-13:55 | 292980.33 | 0.00 |
August | 0.00 | 0.00 | 0.937178E+12 | 0.521128E+12 | 426494.46 | 14-AUG-10:00 | 287238.89 | 0.00 |
September | 0.00 | 0.00 | 0.191610E+11 | 0.171147E+11 | 182213.60 | 22-SEP-12:00 | 99935.94 | 0.00 |
October | 0.00 | 0.00 | 0.143167E+12 | 0.115409E+12 | 310927.70 | 01-OCT-11:52 | 188816.98 | 0.00 |
November | 0.00 | 0.00 | 0.942730E+11 | 0.812678E+11 | 310281.24 | 19-NOV-12:53 | 310281.24 | 0.00 |
December | 0.00 | 0.00 | 0.238652E+12 | 0.216037E+12 | 353305.29 | 16-DEC-12:45 | 353305.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.243324E+13 | 0.162602E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.128953E+10 | 0.115812E+10 | 54369.54 | 47320.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.937178E+12 | 0.521128E+12 | 427239.19 | 353305.29 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.507486E+10 | 0.503290E+10 | 2422.36 | 15-JAN-16:10 | 2422.36 | 0.00 |
February | 0.00 | 0.00 | 0.927580E+10 | 0.921488E+10 | 4664.66 | 20-FEB-17:10 | 4642.72 | 0.00 |
March | 0.00 | 0.00 | 0.154285E+11 | 0.153325E+11 | 7504.43 | 31-MAR-24:00 | 7504.43 | 0.00 |
April | 0.00 | 0.00 | 0.201168E+11 | 0.199891E+11 | 8460.58 | 16-APR-17:23 | 8431.73 | 0.00 |
May | 0.00 | 0.00 | 0.546005E+10 | 0.536153E+10 | 3806.76 | 31-MAY-24:00 | 3787.84 | 0.00 |
June | 0.00 | 0.00 | 0.105143E+11 | 0.103202E+11 | 5841.37 | 30-JUN-24:00 | 5836.77 | 0.00 |
July | 0.00 | 0.00 | 0.161703E+11 | 0.158857E+11 | 7749.57 | 31-JUL-24:00 | 7749.57 | 0.00 |
August | 0.00 | 0.00 | 0.211971E+11 | 0.208787E+11 | 8600.74 | 06-AUG-18:05 | 8585.05 | 0.00 |
September | 0.00 | 0.00 | 0.559105E+10 | 0.541139E+10 | 4002.84 | 30-SEP-24:00 | 4002.84 | 0.00 |
October | 0.00 | 0.00 | 0.108294E+11 | 0.107018E+11 | 5818.29 | 31-OCT-24:00 | 5811.26 | 0.00 |
November | 0.00 | 0.00 | 0.151034E+11 | 0.150288E+11 | 6529.66 | 12-NOV-16:15 | 6496.87 | 0.00 |
December | 0.00 | 0.00 | 0.205640E+11 | 0.205311E+11 | 8508.42 | 25-DEC-16:15 | 8508.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155326E+12 | 0.153689E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.507486E+10 | 0.503290E+10 | 2422.36 | 2422.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211971E+11 | 0.208787E+11 | 8600.74 | 8585.05 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.380616E+11 | 0.376547E+11 | 22110.41 | 18-JAN-16:20 | 21186.81 | 0.00 |
February | 0.00 | 0.00 | 0.800006E+11 | 0.793982E+11 | 41476.68 | 20-FEB-17:10 | 41273.62 | 0.00 |
March | 0.00 | 0.00 | 0.138710E+12 | 0.137757E+12 | 67688.84 | 31-MAR-23:30 | 67688.84 | 0.00 |
April | 0.00 | 0.00 | 0.187146E+12 | 0.185876E+12 | 78725.05 | 16-APR-17:23 | 78445.39 | 0.00 |
May | 0.00 | 0.00 | 0.471874E+11 | 0.462231E+11 | 34610.74 | 31-MAY-23:30 | 34231.33 | 0.00 |
June | 0.00 | 0.00 | 0.968099E+11 | 0.948894E+11 | 55196.19 | 30-JUN-24:00 | 55145.59 | 0.00 |
July | 0.00 | 0.00 | 0.152187E+12 | 0.149361E+12 | 73708.11 | 31-JUL-24:00 | 73708.11 | 0.00 |
August | 0.00 | 0.00 | 0.200436E+12 | 0.197262E+12 | 80079.14 | 17-AUG-16:00 | 76606.03 | 0.00 |
September | 0.00 | 0.00 | 0.493961E+11 | 0.476326E+11 | 37901.37 | 30-SEP-24:00 | 37901.37 | 0.00 |
October | 0.00 | 0.00 | 0.985416E+11 | 0.972793E+11 | 54002.81 | 31-OCT-23:50 | 53905.15 | 0.00 |
November | 0.00 | 0.00 | 0.136290E+12 | 0.135551E+12 | 60254.74 | 10-NOV-16:20 | 57704.11 | 0.00 |
December | 0.00 | 0.00 | 0.186956E+12 | 0.186626E+12 | 78218.29 | 07-DEC-16:10 | 75986.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.141172E+13 | 0.139551E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.380616E+11 | 0.376547E+11 | 22110.41 | 21186.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200436E+12 | 0.197262E+12 | 80079.14 | 78445.39 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.258028E+10 | 0.254091E+10 | 2233.97 | 18-JAN-16:10 | 2144.71 | 0.00 |
February | 0.00 | 0.00 | 0.699281E+10 | 0.693340E+10 | 4132.16 | 01-FEB-16:50 | 3926.15 | 0.00 |
March | 0.00 | 0.00 | 0.129630E+11 | 0.128682E+11 | 6396.63 | 31-MAR-23:20 | 6396.63 | 0.00 |
April | 0.00 | 0.00 | 0.182629E+11 | 0.181360E+11 | 7917.66 | 30-APR-17:27 | 7917.66 | 0.00 |
May | 0.00 | 0.00 | 0.426672E+10 | 0.417099E+10 | 3234.40 | 31-MAY-23:20 | 3185.74 | 0.00 |
June | 0.00 | 0.00 | 0.948980E+10 | 0.929759E+10 | 5410.54 | 30-JUN-23:40 | 5401.16 | 0.00 |
July | 0.00 | 0.00 | 0.151521E+11 | 0.148695E+11 | 7279.15 | 31-JUL-24:00 | 7279.15 | 0.00 |
August | 0.00 | 0.00 | 0.199438E+11 | 0.196266E+11 | 8125.99 | 06-AUG-17:47 | 8123.42 | 0.00 |
September | 0.00 | 0.00 | 0.465753E+10 | 0.448167E+10 | 3766.04 | 30-SEP-23:50 | 3766.04 | 0.00 |
October | 0.00 | 0.00 | 0.940594E+10 | 0.928005E+10 | 5196.91 | 31-OCT-23:30 | 5182.99 | 0.00 |
November | 0.00 | 0.00 | 0.127172E+11 | 0.126437E+11 | 6046.02 | 10-NOV-16:20 | 5791.02 | 0.00 |
December | 0.00 | 0.00 | 0.175062E+11 | 0.174735E+11 | 7822.33 | 07-DEC-16:10 | 7599.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133938E+12 | 0.132322E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.258028E+10 | 0.254091E+10 | 2233.97 | 2144.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199438E+11 | 0.196266E+11 | 8125.99 | 8123.42 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13.01 | 84789.28 | 02-JAN-05:11 | 5414.35 | 758730.83 | 03-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1698.65 | 211830.59 | 06-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 4027.14 | 859565.09 | 29-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 210.45 | 280083.02 | 01-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23.51 | 114094.35 | 13-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 1.07 | 30-JUN-15:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.59 | 31-JUL-14:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.01 | 0.63 | 31-AUG-14:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.52 | 06-SEP-08:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 39.44 | 41671.62 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 446.45 | 223332.60 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2973.58 | 548179.11 | 13-DEC-06:03 |
Annual Sum or Average | 1.11 | 1244.08 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.52 | ||
Maximum of Months | 13.01 | 84789.28 | 5414.35 | 859565.09 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 88140.67 | 1251203.44 | 18-JAN-13:40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 57833.11 | 1004055.82 | 01-FEB-12:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 52466.37 | 1236978.90 | 23-MAR-14:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 107317.29 | 1199323.95 | 12-APR-14:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 103307.76 | 987209.90 | 04-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 192340.54 | 1309906.02 | 27-JUN-10:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 328792.48 | 1470691.28 | 28-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 388421.82 | 1568915.70 | 07-AUG-10:30 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 230316.54 | 1368531.86 | 21-SEP-12:05 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 267383.55 | 1471984.35 | 03-OCT-14:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 106092.33 | 1133831.05 | 28-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 113168.45 | 1257786.71 | 19-DEC-13:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 170666.97 | 0.00 | ||||
Minimum of Months | 52466.37 | 987209.90 | 0.00 | 0.00 | ||
Maximum of Months | 388421.82 | 1568915.70 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 87993.50 | 1267247.21 | 18-JAN-14:50 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 57086.62 | 1002441.51 | 01-FEB-12:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 51962.00 | 1380561.68 | 23-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 106318.07 | 1265683.87 | 12-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 102118.58 | 959188.98 | 04-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 190778.55 | 1551796.56 | 28-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 327128.50 | 2068114.71 | 25-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 386785.45 | 2213957.91 | 07-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 229331.59 | 2441007.48 | 30-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 269868.67 | 2385103.60 | 05-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 105272.61 | 1114214.26 | 28-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 112226.80 | 1294138.67 | 05-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 169945.31 | 0.00 | ||||
Minimum of Months | 51962.00 | 959188.98 | 0.00 | 0.00 | ||
Maximum of Months | 386785.45 | 2441007.48 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 49780.91 | 603645.43 | 14-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 64421.67 | 800183.90 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 126201.92 | 840440.62 | 23-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 362463.07 | 1305286.26 | 26-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53373.41 | 412312.46 | 04-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 171428.28 | 854235.88 | 29-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 508894.56 | 1374149.00 | 31-JUL-11:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 842234.81 | 1424552.53 | 14-AUG-11:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 118977.22 | 1182424.29 | 29-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 264647.29 | 1460680.15 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 161689.18 | 1121256.61 | 19-NOV-12:59 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 281423.15 | 1182625.78 | 05-DEC-10:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 252503.50 | 0.00 | ||||
Minimum of Months | 49780.91 | 412312.46 | 0.00 | 0.00 | ||
Maximum of Months | 842234.81 | 1460680.15 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13760.85 | 45599.41 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13849.62 | 45635.06 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 14478.95 | 45386.18 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13398.87 | 44583.00 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 13485.91 | 43622.75 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13496.41 | 42533.22 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12368.02 | 41693.44 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13386.23 | 41636.73 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12779.56 | 42349.25 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13013.16 | 43399.20 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13484.82 | 44442.98 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13305.24 | 45225.55 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 13398.16 | ||||
Minimum of Months | 0.00 | 0.00 | 12368.02 | 41636.73 | ||
Maximum of Months | 0.00 | 0.00 | 14478.95 | 45635.06 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 101963.55 | 1485475.43 | 18-JAN-13:40 | 1127.03 | 100783.02 | 09-JAN-06:50 |
February | 65785.46 | 1195306.70 | 01-FEB-12:10 | 751.35 | 89938.25 | 07-FEB-06:30 |
March | 62415.64 | 1820683.32 | 23-MAR-14:00 | 647.81 | 74008.56 | 01-MAR-06:30 |
April | 131709.87 | 1861364.64 | 26-APR-13:00 | 517.27 | 46882.22 | 01-APR-06:00 |
May | 122338.96 | 1423073.66 | 04-MAY-12:20 | 562.80 | 53990.46 | 10-MAY-17:50 |
June | 256262.31 | 2362470.45 | 27-JUN-12:05 | 304.55 | 42980.88 | 22-JUN-20:20 |
July | 533138.55 | 3351275.26 | 31-JUL-13:00 | 421.03 | 38854.53 | 07-JUL-20:50 |
August | 650698.68 | 3403368.67 | 17-AUG-14:05 | 324.36 | 38711.72 | 21-AUG-20:20 |
September | 323858.25 | 2918280.21 | 22-SEP-11:30 | 266.00 | 43071.75 | 01-SEP-19:10 |
October | 378491.84 | 3119647.13 | 04-OCT-10:50 | 502.07 | 71875.69 | 30-OCT-05:50 |
November | 121260.43 | 1826025.28 | 28-NOV-14:05 | 1023.28 | 93882.22 | 22-NOV-20:10 |
December | 129298.25 | 1811421.54 | 05-DEC-11:05 | 775.82 | 97348.96 | 26-DEC-06:30 |
Annual Sum or Average | 241543.64 | 601.53 | ||||
Minimum of Months | 62415.64 | 1195306.70 | 266.00 | 38711.72 | ||
Maximum of Months | 650698.68 | 3403368.67 | 1127.03 | 100783.02 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125080E+11 | 0.81 | 8112.08 | 01-JAN-00:20 | 1.41 |
February | 0.108734E+11 | 0.78 | 8112.08 | 01-FEB-05:13 | 1.42 |
March | 0.126273E+11 | 0.82 | 8112.08 | 01-MAR-05:12 | 1.41 |
April | 0.115694E+11 | 0.77 | 8112.08 | 01-APR-04:13 | 1.41 |
May | 0.121535E+11 | 0.79 | 8112.08 | 01-MAY-04:12 | 1.41 |
June | 0.121478E+11 | 0.81 | 8112.08 | 01-JUN-04:13 | 1.41 |
July | 0.115840E+11 | 0.75 | 8112.08 | 01-JUL-04:12 | 1.41 |
August | 0.126792E+11 | 0.82 | 8112.08 | 01-AUG-04:12 | 1.41 |
September | 0.118755E+11 | 0.79 | 8112.08 | 01-SEP-04:12 | 1.41 |
October | 0.122385E+11 | 0.79 | 8112.08 | 02-OCT-01:15 | 1.40 |
November | 0.118710E+11 | 0.80 | 8112.08 | 01-NOV-04:12 | 1.41 |
December | 0.120682E+11 | 0.79 | 8112.08 | 01-DEC-05:12 | 1.41 |
Annual Sum or Average | 0.144196E+12 | 0.79 | |||
Minimum of Months | 0.108734E+11 | 0.75 | 8112.08 | 1.40 | |
Maximum of Months | 0.126792E+11 | 0.82 | 8112.08 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.518966E+10 | 0.38 | 9623.88 | 02-JAN-15:00 | 1.20 |
February | 0.516888E+10 | 0.40 | 11662.94 | 21-FEB-15:50 | 1.35 |
March | 0.681006E+10 | 0.45 | 11924.52 | 23-MAR-15:20 | 1.36 |
April | 0.873205E+10 | 0.53 | 13659.51 | 26-APR-14:00 | 1.48 |
May | 0.635572E+10 | 0.44 | 14510.12 | 03-MAY-05:02 | 1.55 |
June | 0.785261E+10 | 0.50 | 15122.11 | 19-JUN-05:02 | 1.59 |
July | 0.966118E+10 | 0.58 | 18278.20 | 24-JUL-05:02 | 1.79 |
August | 0.115826E+11 | 0.67 | 18278.20 | 07-AUG-05:02 | 1.79 |
September | 0.723464E+10 | 0.46 | 18278.20 | 30-SEP-05:02 | 1.80 |
October | 0.756840E+10 | 0.47 | 18278.20 | 02-OCT-05:03 | 1.79 |
November | 0.690104E+10 | 0.45 | 13859.84 | 13-NOV-09:10 | 1.50 |
December | 0.688991E+10 | 0.44 | 13776.62 | 26-DEC-16:00 | 1.51 |
Annual Sum or Average | 0.899468E+11 | 0.48 | |||
Minimum of Months | 0.516888E+10 | 0.38 | 9623.88 | 1.20 | |
Maximum of Months | 0.115826E+11 | 0.67 | 18278.20 | 1.80 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.336864E+11 | 0.32 | 79254.78 | 10-JAN-06:03 | 1.12 |
February | 0.313788E+11 | 0.33 | 68954.57 | 03-FEB-16:00 | 1.03 |
March | 0.368138E+11 | 0.35 | 104408.56 | 29-MAR-05:02 | 1.33 |
April | 0.457654E+11 | 0.38 | 96697.09 | 26-APR-14:05 | 1.26 |
May | 0.450809E+11 | 0.38 | 79839.07 | 03-MAY-14:05 | 1.12 |
June | 0.528341E+11 | 0.42 | 104924.29 | 19-JUN-05:02 | 1.32 |
July | 0.602547E+11 | 0.44 | 148443.01 | 24-JUL-05:02 | 1.64 |
August | 0.687905E+11 | 0.47 | 141414.60 | 07-AUG-05:02 | 1.59 |
September | 0.539380E+11 | 0.41 | 169226.57 | 30-SEP-05:02 | 1.80 |
October | 0.497810E+11 | 0.39 | 169226.57 | 02-OCT-05:03 | 1.79 |
November | 0.378065E+11 | 0.34 | 68835.04 | 01-NOV-05:03 | 1.03 |
December | 0.348286E+11 | 0.33 | 81180.08 | 13-DEC-06:03 | 1.14 |
Annual Sum or Average | 0.550959E+12 | 0.38 | |||
Minimum of Months | 0.313788E+11 | 0.32 | 68835.04 | 1.03 | |
Maximum of Months | 0.687905E+11 | 0.47 | 169226.57 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.272505E+10 | 0.30 | 5727.85 | 18-JAN-15:40 | 0.88 |
February | 0.253284E+10 | 0.30 | 5987.24 | 16-FEB-15:00 | 0.90 |
March | 0.302247E+10 | 0.32 | 8745.66 | 23-MAR-15:10 | 1.13 |
April | 0.412667E+10 | 0.35 | 10318.36 | 26-APR-14:20 | 1.25 |
May | 0.408676E+10 | 0.35 | 9222.82 | 03-MAY-15:20 | 1.17 |
June | 0.518882E+10 | 0.40 | 9801.85 | 30-JUN-16:00 | 1.21 |
July | 0.623577E+10 | 0.42 | 11748.57 | 31-JUL-14:40 | 1.35 |
August | 0.698082E+10 | 0.46 | 13934.51 | 07-AUG-05:02 | 1.51 |
September | 0.497994E+10 | 0.38 | 18171.46 | 30-SEP-05:02 | 1.80 |
October | 0.435978E+10 | 0.36 | 18171.46 | 05-OCT-05:02 | 1.79 |
November | 0.289743E+10 | 0.30 | 6233.93 | 10-NOV-15:05 | 0.92 |
December | 0.273130E+10 | 0.30 | 6030.18 | 05-DEC-15:50 | 0.91 |
Annual Sum or Average | 0.498677E+11 | 0.35 | |||
Minimum of Months | 0.253284E+10 | 0.30 | 5727.85 | 0.88 | |
Maximum of Months | 0.698082E+10 | 0.46 | 18171.46 | 1.80 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.956903E+11 | 1.38 | 35726.65 | 01-JAN-00:05 | 1.38 |
February | 0.864299E+11 | 1.38 | 35726.65 | 01-FEB-00:10 | 1.38 |
March | 0.956903E+11 | 1.38 | 35726.65 | 01-MAR-00:10 | 1.38 |
April | 0.926035E+11 | 1.38 | 35726.65 | 01-APR-00:10 | 1.38 |
May | 0.956903E+11 | 1.38 | 35726.65 | 01-MAY-00:05 | 1.37 |
June | 0.926035E+11 | 1.37 | 35726.65 | 01-JUN-00:10 | 1.37 |
July | 0.956903E+11 | 1.37 | 35726.65 | 01-JUL-00:10 | 1.37 |
August | 0.956903E+11 | 1.37 | 35726.65 | 01-AUG-00:05 | 1.37 |
September | 0.926035E+11 | 1.37 | 35726.65 | 01-SEP-00:10 | 1.37 |
October | 0.956903E+11 | 1.38 | 35726.65 | 01-OCT-00:10 | 1.37 |
November | 0.926035E+11 | 1.38 | 35726.65 | 01-NOV-00:10 | 1.38 |
December | 0.956903E+11 | 1.38 | 35726.65 | 01-DEC-00:10 | 1.39 |
Annual Sum or Average | 0.112668E+13 | 1.37 | |||
Minimum of Months | 0.864299E+11 | 1.37 | 35726.65 | 1.37 | |
Maximum of Months | 0.956903E+11 | 1.38 | 35726.65 | 1.39 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141605E+10 | 0.93 | 528.69 | 01-JAN-00:05 | 0.93 |
February | 0.127901E+10 | 0.93 | 528.69 | 01-FEB-00:10 | 0.93 |
March | 0.141605E+10 | 0.93 | 528.69 | 01-MAR-00:10 | 0.93 |
April | 0.137037E+10 | 0.93 | 528.69 | 01-APR-00:10 | 0.93 |
May | 0.141605E+10 | 0.93 | 528.69 | 01-MAY-00:05 | 0.93 |
June | 0.137037E+10 | 0.93 | 528.69 | 01-JUN-00:10 | 0.93 |
July | 0.141605E+10 | 0.93 | 528.69 | 01-JUL-00:10 | 0.93 |
August | 0.141605E+10 | 0.93 | 528.69 | 01-AUG-00:05 | 0.93 |
September | 0.137037E+10 | 0.93 | 528.69 | 01-SEP-00:10 | 0.93 |
October | 0.141605E+10 | 0.93 | 528.69 | 01-OCT-00:10 | 0.93 |
November | 0.137037E+10 | 0.93 | 528.69 | 01-NOV-00:10 | 0.93 |
December | 0.141605E+10 | 0.93 | 528.69 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.166728E+11 | 0.93 | |||
Minimum of Months | 0.127901E+10 | 0.93 | 528.69 | 0.93 | |
Maximum of Months | 0.141605E+10 | 0.93 | 528.69 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135244E+11 | 0.93 | 5049.43 | 01-JAN-00:05 | 0.93 |
February | 0.122156E+11 | 0.93 | 5049.43 | 01-FEB-00:10 | 0.93 |
March | 0.135244E+11 | 0.93 | 5049.43 | 01-MAR-00:10 | 0.93 |
April | 0.130881E+11 | 0.93 | 5049.43 | 01-APR-00:10 | 0.93 |
May | 0.135244E+11 | 0.93 | 5049.43 | 01-MAY-00:05 | 0.93 |
June | 0.130881E+11 | 0.93 | 5049.43 | 01-JUN-00:10 | 0.93 |
July | 0.135244E+11 | 0.93 | 5049.43 | 01-JUL-00:10 | 0.93 |
August | 0.135244E+11 | 0.93 | 5049.43 | 01-AUG-00:05 | 0.93 |
September | 0.130881E+11 | 0.93 | 5049.43 | 01-SEP-00:10 | 0.93 |
October | 0.135244E+11 | 0.93 | 5049.43 | 01-OCT-00:10 | 0.93 |
November | 0.130881E+11 | 0.93 | 5049.43 | 01-NOV-00:10 | 0.93 |
December | 0.135244E+11 | 0.93 | 5049.43 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.159239E+12 | 0.93 | |||
Minimum of Months | 0.122156E+11 | 0.93 | 5049.43 | 0.93 | |
Maximum of Months | 0.135244E+11 | 0.93 | 5049.43 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137469E+10 | 0.93 | 513.25 | 01-JAN-00:05 | 0.93 |
February | 0.124166E+10 | 0.93 | 513.25 | 01-FEB-00:10 | 0.93 |
March | 0.137469E+10 | 0.93 | 513.25 | 01-MAR-00:10 | 0.93 |
April | 0.133035E+10 | 0.93 | 513.25 | 01-APR-00:10 | 0.93 |
May | 0.137469E+10 | 0.93 | 513.25 | 01-MAY-00:05 | 0.93 |
June | 0.133035E+10 | 0.93 | 513.25 | 01-JUN-00:10 | 0.93 |
July | 0.137469E+10 | 0.93 | 513.25 | 01-JUL-00:10 | 0.93 |
August | 0.137469E+10 | 0.93 | 513.25 | 01-AUG-00:05 | 0.93 |
September | 0.133035E+10 | 0.93 | 513.25 | 01-SEP-00:10 | 0.93 |
October | 0.137469E+10 | 0.93 | 513.25 | 01-OCT-00:10 | 0.93 |
November | 0.133035E+10 | 0.93 | 513.25 | 01-NOV-00:10 | 0.93 |
December | 0.137469E+10 | 0.93 | 513.25 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.161859E+11 | 0.93 | |||
Minimum of Months | 0.124166E+10 | 0.93 | 513.25 | 0.93 | |
Maximum of Months | 0.137469E+10 | 0.93 | 513.25 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1962835.31 | 1784217.30 | 938.89 | 02-JAN-06:02 | 853.45 | 853.45 | 48.89 | 11.79 |
February | 279209.44 | 253801.38 | 29.06 | 06-FEB-06:03 | 26.41 | 26.41 | 34.30 | 1.97 |
March | 1153094.39 | 1048162.80 | 682.61 | 30-MAR-05:03 | 620.49 | 620.49 | 43.15 | 10.24 |
April | 42157.31 | 38321.00 | 49.93 | 01-APR-05:02 | 45.38 | 45.38 | 35.35 | 2.72 |
May | 3823.52 | 3475.58 | 9.27 | 13-MAY-05:02 | 8.42 | 8.42 | 30.57 | 0.93 |
June | 0.44 | 0.40 | 0.00 | 30-JUN-15:00 | 0.00 | 0.00 | 30.94 | 0.00 |
July | 0.53 | 0.48 | 0.00 | 31-JUL-14:30 | 0.00 | 0.00 | 30.94 | 0.00 |
August | 1.19 | 1.08 | 0.00 | 31-AUG-14:05 | 0.00 | 0.00 | 30.94 | 0.00 |
September | 0.39 | 0.35 | 0.00 | 06-SEP-08:20 | 0.00 | 0.00 | 30.94 | 0.00 |
October | 5521.33 | 5018.89 | 2.50 | 30-OCT-05:03 | 2.27 | 2.27 | 30.09 | 0.33 |
November | 75964.91 | 69052.10 | 30.72 | 24-NOV-06:03 | 27.92 | 27.92 | 33.81 | 2.04 |
December | 720446.58 | 654885.94 | 324.40 | 13-DEC-06:03 | 294.88 | 294.88 | 41.87 | 7.23 |
Annual Sum or Average | 4243055.32 | 3856937.29 | ||||||
Minimum of Months | 0.39 | 0.35 | 0.00 | 0.00 | 0.00 | 30.09 | 0.00 | |
Maximum of Months | 1962835.31 | 1784217.30 | 938.89 | 853.45 | 853.45 | 48.89 | 11.79 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.180258E+09 | 0.163855E+09 | 6592.71 | 18-JAN-15:00 | 5992.78 | 5992.78 | 9.38 | 47.99 |
February | 73334600.81 | 66661152.14 | 907.66 | 01-FEB-12:10 | 825.07 | 825.07 | 9.97 | 20.92 |
March | 74421951.01 | 67649553.46 | 3240.41 | 23-MAR-14:00 | 2945.54 | 2945.54 | 9.47 | 36.02 |
April | 0.176554E+09 | 0.160487E+09 | 3104.34 | 12-APR-14:00 | 2821.84 | 2821.84 | 10.39 | 35.39 |
May | 0.169286E+09 | 0.153881E+09 | 1611.88 | 03-MAY-13:00 | 1465.20 | 1465.20 | 6.72 | 26.87 |
June | 0.320955E+09 | 0.291748E+09 | 6557.54 | 28-JUN-05:03 | 5960.81 | 5960.81 | 9.15 | 47.89 |
July | 0.681776E+09 | 0.619734E+09 | 8712.95 | 20-JUL-05:02 | 7920.07 | 7920.07 | 9.30 | 53.58 |
August | 0.884638E+09 | 0.804136E+09 | 8712.95 | 07-AUG-05:02 | 7920.07 | 7920.07 | 9.54 | 53.58 |
September | 0.551308E+09 | 0.501139E+09 | 8454.15 | 22-SEP-05:02 | 7684.82 | 7684.82 | 9.27 | 52.94 |
October | 0.744794E+09 | 0.677018E+09 | 8712.95 | 02-OCT-04:12 | 7920.07 | 7920.07 | 9.54 | 53.58 |
November | 0.178696E+09 | 0.162434E+09 | 2615.40 | 08-NOV-14:30 | 2377.40 | 2377.40 | 7.83 | 32.97 |
December | 0.167406E+09 | 0.152172E+09 | 1999.10 | 05-DEC-15:00 | 1817.18 | 1817.18 | 8.35 | 29.45 |
Annual Sum or Average | 0.420343E+10 | 0.382092E+10 | ||||||
Minimum of Months | 73334600.81 | 66661152.14 | 907.66 | 825.07 | 825.07 | 6.72 | 20.92 | |
Maximum of Months | 0.884638E+09 | 0.804136E+09 | 8712.95 | 7920.07 | 7920.07 | 10.39 | 53.58 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.280792E+10 | 0.255240E+10 | 2998.44 | 02-JAN-05:11 | 2725.59 | 2725.59 | 6.71 | 26.79 |
February | 0.212110E+10 | 0.192808E+10 | 2998.44 | 01-FEB-05:13 | 2725.59 | 2725.59 | 7.08 | 26.79 |
March | 0.213090E+10 | 0.193699E+10 | 2998.44 | 01-MAR-06:02 | 2725.59 | 2725.59 | 6.88 | 26.79 |
April | 0.334903E+10 | 0.304427E+10 | 2998.44 | 01-APR-05:02 | 2725.59 | 2725.59 | 6.72 | 26.79 |
May | 0.377548E+10 | 0.343191E+10 | 2998.44 | 01-MAY-00:05 | 2725.59 | 2725.59 | 6.73 | 26.79 |
June | 0.465383E+10 | 0.423033E+10 | 2998.44 | 01-JUN-04:13 | 2725.59 | 2725.59 | 6.91 | 26.79 |
July | 0.596753E+10 | 0.542449E+10 | 2998.44 | 01-JUL-04:12 | 2725.59 | 2725.59 | 9.24 | 26.79 |
August | 0.659558E+10 | 0.599538E+10 | 2998.44 | 01-AUG-00:05 | 2725.59 | 2725.59 | 6.88 | 26.79 |
September | 0.452417E+10 | 0.411247E+10 | 2998.44 | 01-SEP-00:35 | 2725.59 | 2725.59 | 6.75 | 26.79 |
October | 0.477433E+10 | 0.433987E+10 | 2998.44 | 01-OCT-08:15 | 2725.59 | 2725.59 | 7.88 | 26.79 |
November | 0.307994E+10 | 0.279967E+10 | 2998.44 | 01-NOV-04:12 | 2725.59 | 2725.59 | 7.24 | 26.79 |
December | 0.295353E+10 | 0.268476E+10 | 2998.44 | 01-DEC-05:12 | 2725.59 | 2725.59 | 6.82 | 26.79 |
Annual Sum or Average | 0.467333E+11 | 0.424806E+11 | ||||||
Minimum of Months | 0.212110E+10 | 0.192808E+10 | 2998.44 | 2725.59 | 2725.59 | 6.71 | 26.79 | |
Maximum of Months | 0.659558E+10 | 0.599538E+10 | 2998.44 | 2725.59 | 2725.59 | 9.24 | 26.79 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 8995333.21 | 8176757.89 | 2998.44 | 18-JAN-13:20 | 2725.59 | 2725.59 | 14.92 | 13.39 |
February | 3598133.28 | 3270703.16 | 2998.44 | 01-FEB-12:00 | 2725.59 | 2725.59 | 15.14 | 13.39 |
March | 27885532.95 | 25347949.45 | 2998.44 | 22-MAR-12:40 | 2725.59 | 2725.59 | 15.53 | 13.39 |
April | 62067799.15 | 56419629.43 | 2998.44 | 12-APR-13:30 | 2725.59 | 2725.59 | 15.55 | 13.39 |
May | 3598133.28 | 3270703.16 | 2998.44 | 04-MAY-12:30 | 2725.59 | 2725.59 | 15.51 | 13.39 |
June | 0.306741E+09 | 0.278827E+09 | 2998.44 | 21-JUN-12:50 | 2725.59 | 2725.59 | 15.59 | 13.39 |
July | 0.111092E+10 | 0.100983E+10 | 2998.44 | 12-JUL-12:05 | 2725.59 | 2725.59 | 11.43 | 26.79 |
August | 0.152021E+10 | 0.138187E+10 | 2998.44 | 02-AUG-09:30 | 2725.59 | 2725.59 | 15.19 | 13.39 |
September | 0.642986E+09 | 0.584475E+09 | 2998.44 | 05-SEP-12:40 | 2725.59 | 2725.59 | 15.72 | 13.39 |
October | 0.900433E+09 | 0.818493E+09 | 2998.44 | 02-OCT-07:30 | 2725.59 | 2725.59 | 15.26 | 13.39 |
November | 9894866.53 | 8994433.68 | 2998.44 | 28-NOV-13:30 | 2725.59 | 2725.59 | 15.39 | 13.39 |
December | 62067799.15 | 56419629.43 | 2998.44 | 05-DEC-09:50 | 2725.59 | 2725.59 | 15.05 | 13.39 |
Annual Sum or Average | 0.465940E+10 | 0.423540E+10 | ||||||
Minimum of Months | 3598133.28 | 3270703.16 | 2998.44 | 2725.59 | 2725.59 | 11.43 | 13.39 | |
Maximum of Months | 0.152021E+10 | 0.138187E+10 | 2998.44 | 2725.59 | 2725.59 | 15.72 | 26.79 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.878860E+10 | 0.798883E+10 | 3281.29 | 01-JAN-00:05 | 2982.69 | 2982.69 | 18.68 | 13.84 |
February | 0.793809E+10 | 0.721572E+10 | 3281.29 | 01-FEB-00:10 | 2982.69 | 2982.69 | 19.35 | 13.84 |
March | 0.878860E+10 | 0.798883E+10 | 3281.29 | 01-MAR-00:10 | 2982.69 | 2982.69 | 19.90 | 13.84 |
April | 0.850509E+10 | 0.773113E+10 | 3281.29 | 01-APR-00:10 | 2982.69 | 2982.69 | 20.47 | 13.84 |
May | 0.878860E+10 | 0.798883E+10 | 3281.29 | 01-MAY-00:05 | 2982.69 | 2982.69 | 19.00 | 13.84 |
June | 0.850509E+10 | 0.773113E+10 | 3281.29 | 01-JUN-00:10 | 2982.69 | 2982.69 | 19.44 | 13.84 |
July | 0.878860E+10 | 0.798883E+10 | 3281.29 | 01-JUL-00:10 | 2982.69 | 2982.69 | 21.46 | 13.84 |
August | 0.878860E+10 | 0.798883E+10 | 3281.29 | 01-AUG-00:05 | 2982.69 | 2982.69 | 34.11 | 13.84 |
September | 0.850509E+10 | 0.773113E+10 | 3281.29 | 01-SEP-00:10 | 2982.69 | 2982.69 | 18.98 | 13.84 |
October | 0.878860E+10 | 0.798883E+10 | 3281.29 | 01-OCT-00:10 | 2982.69 | 2982.69 | 20.10 | 13.84 |
November | 0.850509E+10 | 0.773113E+10 | 3281.29 | 01-NOV-00:10 | 2982.69 | 2982.69 | 20.05 | 13.84 |
December | 0.878860E+10 | 0.798883E+10 | 3281.29 | 01-DEC-00:10 | 2982.69 | 2982.69 | 20.60 | 13.84 |
Annual Sum or Average | 0.103479E+12 | 0.940621E+11 | ||||||
Minimum of Months | 0.793809E+10 | 0.721572E+10 | 3281.29 | 2982.69 | 2982.69 | 18.68 | 13.84 | |
Maximum of Months | 0.878860E+10 | 0.798883E+10 | 3281.29 | 2982.69 | 2982.69 | 34.11 | 13.84 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.07 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.08 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 55.93 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 55.88 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 55.96 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.03 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.45 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 55.93 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.98 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.45 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 55.84 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.06 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.84 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.08 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.109801E+11 | 0.998095E+10 | 23451.14 | 18-JAN-13:40 | 21317.09 | 21317.09 | 24.81 | 95.73 |
February | 0.828266E+10 | 0.752894E+10 | 23438.93 | 01-FEB-12:10 | 21305.99 | 21305.99 | 24.09 | 95.73 |
March | 0.840546E+10 | 0.764056E+10 | 23467.08 | 23-MAR-14:00 | 21331.58 | 21331.58 | 25.65 | 95.73 |
April | 0.133181E+11 | 0.121061E+11 | 23469.08 | 26-APR-13:00 | 21333.40 | 21333.40 | 25.75 | 95.73 |
May | 0.147456E+11 | 0.134037E+11 | 23431.76 | 04-MAY-12:30 | 21299.47 | 21299.47 | 23.66 | 95.73 |
June | 0.192699E+11 | 0.175163E+11 | 23493.74 | 27-JUN-12:05 | 21355.81 | 21355.81 | 27.00 | 95.73 |
July | 0.274901E+11 | 0.249885E+11 | 23529.34 | 19-JUL-14:05 | 21388.17 | 21388.17 | 28.82 | 95.73 |
August | 0.315779E+11 | 0.287043E+11 | 23529.34 | 07-AUG-09:50 | 21388.17 | 21388.17 | 28.83 | 95.73 |
September | 0.200727E+11 | 0.182461E+11 | 23521.15 | 22-SEP-11:30 | 21380.73 | 21380.73 | 28.39 | 95.73 |
October | 0.218847E+11 | 0.198932E+11 | 23529.34 | 04-OCT-10:40 | 21388.17 | 21388.17 | 28.82 | 95.73 |
November | 0.120638E+11 | 0.109660E+11 | 23467.35 | 28-NOV-14:05 | 21331.82 | 21331.82 | 25.66 | 95.73 |
December | 0.117091E+11 | 0.106435E+11 | 23466.63 | 05-DEC-11:05 | 21331.16 | 21331.16 | 25.63 | 95.73 |
Annual Sum or Average | 0.199800E+12 | 0.181618E+12 | ||||||
Minimum of Months | 0.828266E+10 | 0.752894E+10 | 23431.76 | 21299.47 | 21299.47 | 23.66 | 95.73 | |
Maximum of Months | 0.315779E+11 | 0.287043E+11 | 23529.34 | 21388.17 | 21388.17 | 28.83 | 95.73 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13.01 | 84789.28 | 02-JAN-05:11 | 59.47 | 59.47 | 5414.35 | 758730.83 | 03-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 33.11 | 33.11 | 1698.65 | 211830.59 | 06-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 32.75 | 32.75 | 4027.14 | 859565.09 | 29-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33.80 | 33.80 | 210.45 | 280083.02 | 01-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.17 | 30.17 | 23.51 | 114094.35 | 13-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 30.94 | 30.94 | 0.00 | 1.07 | 30-JUN-15:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.94 | 30.94 | 0.00 | 0.59 | 31-JUL-14:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 30.94 | 30.94 | 0.01 | 0.63 | 31-AUG-14:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 30.94 | 30.94 | 0.00 | 0.52 | 06-SEP-08:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.94 | 30.94 | 39.44 | 41671.62 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 30.00 | 30.00 | 446.45 | 223332.60 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32.86 | 32.86 | 2973.58 | 548179.11 | 13-DEC-06:03 |
Annual Sum or Average | 1.11 | 1244.08 | ||||||
Minimum of Months | 0.00 | 0.00 | 30.00 | 30.00 | 0.00 | 0.52 | ||
Maximum of Months | 13.01 | 84789.28 | 59.47 | 59.47 | 5414.35 | 859565.09 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 88140.67 | 1251203.44 | 18-JAN-13:40 | 12.28 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 57833.11 | 1004055.82 | 01-FEB-12:10 | 15.66 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 52466.37 | 1236978.90 | 23-MAR-14:05 | 12.21 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 107317.29 | 1199323.95 | 12-APR-14:05 | 12.04 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 103307.76 | 987209.90 | 04-MAY-12:30 | 15.51 | 9.97 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 192340.54 | 1309906.02 | 27-JUN-10:05 | 12.54 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 328792.48 | 1470691.28 | 28-JUL-12:30 | 13.26 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 388421.82 | 1568915.70 | 07-AUG-10:30 | 13.69 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 230316.54 | 1368531.86 | 21-SEP-12:05 | 12.80 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 267383.55 | 1471984.35 | 03-OCT-14:05 | 13.26 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 106092.33 | 1133831.05 | 28-NOV-14:05 | 11.75 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 113168.45 | 1257786.71 | 19-DEC-13:05 | 12.31 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 170666.97 | 0.00 | ||||||
Minimum of Months | 52466.37 | 987209.90 | 11.75 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 388421.82 | 1568915.70 | 15.66 | 9.97 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 87993.50 | 1267247.21 | 18-JAN-14:50 | 13.15 | 9.46 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 57086.62 | 1002441.51 | 01-FEB-12:10 | 18.16 | 10.04 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 51962.00 | 1380561.68 | 23-MAR-14:00 | 15.86 | 9.52 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 106318.07 | 1265683.87 | 12-APR-14:00 | 15.25 | 10.72 | 0.00 | 0.00 | 01-APR-00:10 |
May | 102118.58 | 959188.98 | 04-MAY-12:30 | 16.26 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 190778.55 | 1551796.56 | 28-JUN-05:03 | 14.44 | 10.10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 327128.50 | 2068114.71 | 25-JUL-05:02 | 15.93 | 11.30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 386785.45 | 2213957.91 | 07-AUG-05:02 | 16.58 | 11.62 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 229331.59 | 2441007.48 | 30-SEP-05:02 | 18.71 | 12.07 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 269868.67 | 2385103.60 | 05-OCT-05:02 | 17.34 | 12.01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 105272.61 | 1114214.26 | 28-NOV-14:00 | 17.54 | 9.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 112226.80 | 1294138.67 | 05-DEC-15:00 | 17.20 | 8.20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 169945.31 | 0.00 | ||||||
Minimum of Months | 51962.00 | 959188.98 | 13.15 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 386785.45 | 2441007.48 | 18.71 | 12.07 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 49780.91 | 603645.43 | 14-JAN-12:00 | 30.77 | 27.37 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 64421.67 | 800183.90 | 01-FEB-12:00 | 34.77 | 28.53 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 126201.92 | 840440.62 | 23-MAR-14:00 | 35.58 | 26.63 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 362463.07 | 1305286.26 | 26-APR-13:00 | 44.88 | 32.22 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53373.41 | 412312.46 | 04-MAY-12:00 | 26.86 | 24.82 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 171428.28 | 854235.88 | 29-JUN-11:00 | 35.86 | 28.14 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 508894.56 | 1374149.00 | 31-JUL-11:50 | 46.25 | 33.22 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 842234.81 | 1424552.53 | 14-AUG-11:00 | 47.24 | 33.63 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 118977.22 | 1182424.29 | 29-SEP-13:00 | 42.44 | 37.87 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 264647.29 | 1460680.15 | 16-OCT-11:00 | 47.96 | 40.21 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 161689.18 | 1121256.61 | 19-NOV-12:59 | 41.22 | 31.13 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 281423.15 | 1182625.78 | 05-DEC-10:00 | 42.44 | 30.79 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 252503.50 | 0.00 | ||||||
Minimum of Months | 49780.91 | 412312.46 | 26.86 | 24.82 | 0.00 | 0.00 | ||
Maximum of Months | 842234.81 | 1460680.15 | 47.96 | 40.21 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.85 | 57.85 | 13760.85 | 45599.41 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.46 | 57.46 | 13849.62 | 45635.06 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.43 | 56.43 | 14478.95 | 45386.18 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.37 | 56.37 | 13398.87 | 44583.00 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 56.71 | 56.71 | 13485.91 | 43622.75 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.41 | 57.41 | 13496.41 | 42533.22 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.05 | 57.05 | 12368.02 | 41693.44 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.39 | 56.39 | 13386.23 | 41636.73 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.45 | 57.45 | 12779.56 | 42349.25 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.37 | 57.37 | 13013.16 | 43399.20 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.37 | 56.37 | 13484.82 | 44442.98 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.51 | 57.51 | 13305.24 | 45225.55 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 13398.16 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.37 | 56.37 | 12368.02 | 41636.73 | ||
Maximum of Months | 0.00 | 0.00 | 57.85 | 57.85 | 14478.95 | 45635.06 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 101963.55 | 1485475.43 | 18-JAN-13:40 | 24.81 | 21.10 | 1127.03 | 100783.02 | 09-JAN-06:50 |
February | 65785.46 | 1195306.70 | 01-FEB-12:10 | 24.09 | 22.56 | 751.35 | 89938.25 | 07-FEB-06:30 |
March | 62415.64 | 1820683.32 | 23-MAR-14:00 | 25.65 | 22.02 | 647.81 | 74008.56 | 01-MAR-06:30 |
April | 131709.87 | 1861364.64 | 26-APR-13:00 | 25.75 | 22.02 | 517.27 | 46882.22 | 01-APR-06:00 |
May | 122338.96 | 1423073.66 | 04-MAY-12:20 | 28.21 | 21.67 | 562.80 | 53990.46 | 10-MAY-17:50 |
June | 256262.31 | 2362470.45 | 27-JUN-12:05 | 27.00 | 23.26 | 304.55 | 42980.88 | 22-JUN-20:20 |
July | 533138.55 | 3351275.26 | 31-JUL-13:00 | 29.48 | 25.45 | 421.03 | 38854.53 | 07-JUL-20:50 |
August | 650698.68 | 3403368.67 | 17-AUG-14:05 | 29.61 | 25.49 | 324.36 | 38711.72 | 21-AUG-20:20 |
September | 323858.25 | 2918280.21 | 22-SEP-11:30 | 28.39 | 24.83 | 266.00 | 43071.75 | 01-SEP-19:10 |
October | 378491.84 | 3119647.13 | 04-OCT-10:50 | 28.90 | 24.64 | 502.07 | 71875.69 | 30-OCT-05:50 |
November | 121260.43 | 1826025.28 | 28-NOV-14:05 | 25.66 | 21.10 | 1023.28 | 93882.22 | 22-NOV-20:10 |
December | 129298.25 | 1811421.54 | 05-DEC-11:05 | 25.63 | 21.10 | 775.82 | 97348.96 | 26-DEC-06:30 |
Annual Sum or Average | 241543.64 | 601.53 | ||||||
Minimum of Months | 62415.64 | 1195306.70 | 24.09 | 21.10 | 266.00 | 38711.72 | ||
Maximum of Months | 650698.68 | 3403368.67 | 29.61 | 25.49 | 1127.03 | 100783.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.488393E+09 | 0.00 | 0.187112E+11 | 0.518966E+10 | 0.00 | 0.00 |
February | 68364358.05 | 0.00 | 0.109026E+11 | 0.516888E+10 | 0.00 | 0.00 |
March | 0.252464E+09 | 0.00 | 0.130551E+11 | 0.681006E+10 | 0.00 | 0.00 |
April | 6906764.18 | 0.00 | 0.296910E+11 | 0.873205E+10 | 0.00 | 0.00 |
May | 5435.95 | 0.00 | 0.258458E+11 | 0.635572E+10 | 0.00 | 0.00 |
June | 8542.68 | 0.00 | 0.473497E+11 | 0.785261E+10 | 0.00 | 0.00 |
July | 9438.40 | 0.00 | 0.875780E+11 | 0.966118E+10 | 0.00 | 0.00 |
August | 22601.90 | 0.00 | 0.108515E+12 | 0.115826E+11 | 0.00 | 0.00 |
September | 6585.18 | 0.00 | 0.532685E+11 | 0.723464E+10 | 0.00 | 0.00 |
October | 4650.73 | 0.00 | 0.669074E+11 | 0.756840E+10 | 0.00 | 0.00 |
November | 289198.13 | 0.00 | 0.230624E+11 | 0.690104E+10 | 0.00 | 0.00 |
December | 0.139019E+09 | 0.00 | 0.269324E+11 | 0.688991E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.955493E+09 | 0.00 | 0.511819E+12 | 0.899468E+11 | 0.00 | 0.00 |
Minimum of Months | 4650.73 | 0.00 | 0.109026E+11 | 0.516888E+10 | 0.00 | 0.00 |
Maximum of Months | 0.488393E+09 | 0.00 | 0.108515E+12 | 0.115826E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.104089E+11 | 0.00 | 0.191014E+12 | 0.336864E+11 | 0.00 | 0.00 |
February | 0.230959E+10 | 0.00 | 0.114301E+12 | 0.313788E+11 | 0.00 | 0.00 |
March | 0.789401E+10 | 0.00 | 0.109448E+12 | 0.368138E+11 | 0.00 | 0.00 |
April | 0.332185E+09 | 0.00 | 0.207545E+12 | 0.457654E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.212911E+12 | 0.450809E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.373490E+12 | 0.528341E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.653850E+12 | 0.602547E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.768562E+12 | 0.687905E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.450866E+12 | 0.539380E+11 | 0.00 | 0.00 |
October | 18435462.81 | 0.00 | 0.533331E+12 | 0.497810E+11 | 0.00 | 0.00 |
November | 0.377123E+09 | 0.00 | 0.218934E+12 | 0.378065E+11 | 0.00 | 0.00 |
December | 0.555308E+10 | 0.00 | 0.229444E+12 | 0.348286E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.268933E+11 | 0.00 | 0.406370E+13 | 0.550959E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.109448E+12 | 0.313788E+11 | 0.00 | 0.00 |
Maximum of Months | 0.104089E+11 | 0.00 | 0.768562E+12 | 0.687905E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.383191E+10 | 0.00 | 0.115662E+11 | 0.272505E+10 | 0.00 | 0.00 |
February | 0.173941E+10 | 0.00 | 0.634914E+10 | 0.253284E+10 | 0.00 | 0.00 |
March | 0.264557E+10 | 0.00 | 0.790772E+10 | 0.302247E+10 | 0.00 | 0.00 |
April | 0.235320E+09 | 0.00 | 0.199934E+11 | 0.412667E+10 | 0.00 | 0.00 |
May | 57037009.36 | 0.00 | 0.203643E+11 | 0.408676E+10 | 0.00 | 0.00 |
June | 4987.90 | 0.00 | 0.384768E+11 | 0.518882E+10 | 0.00 | 0.00 |
July | 6690.92 | 0.00 | 0.696404E+11 | 0.623577E+10 | 0.00 | 0.00 |
August | 13751.96 | 0.00 | 0.810754E+11 | 0.698082E+10 | 0.00 | 0.00 |
September | 5207.57 | 0.00 | 0.440443E+11 | 0.497994E+10 | 0.00 | 0.00 |
October | 94566720.48 | 0.00 | 0.507875E+11 | 0.435978E+10 | 0.00 | 0.00 |
November | 0.758997E+09 | 0.00 | 0.124077E+11 | 0.289743E+10 | 0.00 | 0.00 |
December | 0.228877E+10 | 0.00 | 0.145072E+11 | 0.273130E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.116516E+11 | 0.00 | 0.377120E+12 | 0.498677E+11 | 0.00 | 0.00 |
Minimum of Months | 4987.90 | 0.00 | 0.634914E+10 | 0.253284E+10 | 0.00 | 0.00 |
Maximum of Months | 0.383191E+10 | 0.00 | 0.810754E+11 | 0.698082E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 119.85 | 0.00 | 0.103200E+11 | 0.125080E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.450828E+10 | 0.108734E+11 | 0.00 | 0.00 |
March | 82.18 | 0.00 | 0.511424E+10 | 0.126273E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.135654E+11 | 0.115694E+11 | 0.00 | 0.00 |
May | 76.97 | 0.00 | 0.127815E+11 | 0.121535E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.233821E+11 | 0.121478E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.406492E+11 | 0.115840E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.463271E+11 | 0.126792E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.282003E+11 | 0.118755E+11 | 0.00 | 0.00 |
October | 291.79 | 0.00 | 0.374460E+11 | 0.122385E+11 | 0.00 | 0.00 |
November | 490.25 | 0.00 | 0.117432E+11 | 0.118710E+11 | 0.00 | 0.00 |
December | 709.96 | 0.00 | 0.146239E+11 | 0.120682E+11 | 0.00 | 0.00 |
Annual Sum or Average | 1771.00 | 0.00 | 0.248661E+12 | 0.144196E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.450828E+10 | 0.108734E+11 | 0.00 | 0.00 |
Maximum of Months | 709.96 | 0.00 | 0.463271E+11 | 0.126792E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.137532E+11 | 0.163770E+12 | 0.00 | 23.49 |
February | 0.00 | 0.00 | 0.136152E+11 | 0.145839E+12 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.766068E+11 | 0.158806E+12 | 0.00 | 17.07 |
April | 0.00 | 0.00 | 0.436778E+12 | 0.194906E+12 | 0.00 | 5.92 |
May | 0.00 | 0.00 | 0.390044E+10 | 0.102962E+12 | 0.00 | 1.73 |
June | 0.00 | 0.00 | 0.106140E+12 | 0.116620E+12 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.608069E+12 | 0.214141E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.115479E+13 | 0.313298E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.275740E+11 | 0.104932E+12 | 0.00 | 1.46 |
October | 0.00 | 0.00 | 0.185121E+12 | 0.195520E+12 | 0.00 | 21.53 |
November | 0.00 | 0.00 | 0.121592E+12 | 0.201060E+12 | 0.00 | 30.18 |
December | 0.00 | 0.00 | 0.304388E+12 | 0.309561E+12 | 0.00 | 55.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.305232E+13 | 0.222142E+13 | 0.00 | 176.94 |
Minimum of Months | 0.00 | 0.00 | 0.390044E+10 | 0.102962E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.115479E+13 | 0.313298E+12 | 0.00 | 55.11 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.620037E+10 | 0.254156E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.111836E+11 | 0.318679E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.184734E+11 | 0.446093E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241013E+11 | 0.535484E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.664371E+10 | 0.259971E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127322E+11 | 0.358824E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.197014E+11 | 0.494710E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259377E+11 | 0.615664E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.684278E+10 | 0.262210E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132547E+11 | 0.384137E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181419E+11 | 0.440886E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.246715E+11 | 0.552357E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187884E+12 | 0.492317E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.620037E+10 | 0.254156E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259377E+11 | 0.615664E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.466755E+11 | 0.221383E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.966192E+11 | 0.288342E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166289E+12 | 0.411033E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.224368E+12 | 0.503105E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.575021E+11 | 0.238392E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.117316E+12 | 0.335942E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.185494E+12 | 0.468316E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.245338E+12 | 0.584261E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.605374E+11 | 0.242294E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120753E+12 | 0.357359E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.163908E+12 | 0.407054E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.224593E+12 | 0.511612E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170939E+13 | 0.456909E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.466755E+11 | 0.221383E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.245338E+12 | 0.584261E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.318106E+10 | 0.197547E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.846423E+10 | 0.271308E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155649E+11 | 0.397652E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.219185E+11 | 0.498595E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.520865E+10 | 0.231662E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115096E+11 | 0.335010E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.184809E+11 | 0.470349E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.244288E+11 | 0.585969E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.571738E+10 | 0.239019E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115456E+11 | 0.351436E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.153199E+11 | 0.393308E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.210728E+11 | 0.494128E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162412E+12 | 0.446598E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.318106E+10 | 0.197547E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.244288E+11 | 0.585969E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.518966E+10 | 0.187112E+11 | 0.488393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.516888E+10 | 0.109026E+11 | 68364358.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681006E+10 | 0.130551E+11 | 0.252464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.873205E+10 | 0.296910E+11 | 6906764.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635572E+10 | 0.258458E+11 | 5435.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.785261E+10 | 0.473497E+11 | 8542.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.966118E+10 | 0.875780E+11 | 9438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115826E+11 | 0.108515E+12 | 22601.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.723464E+10 | 0.532685E+11 | 6585.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.756840E+10 | 0.669074E+11 | 4650.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690104E+10 | 0.230624E+11 | 289198.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688991E+10 | 0.269324E+11 | 0.139019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.899468E+11 | 0.511819E+12 | 0.955493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.516888E+10 | 0.109026E+11 | 4650.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115826E+11 | 0.108515E+12 | 0.488393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.336864E+11 | 0.191014E+12 | 0.104089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313788E+11 | 0.114301E+12 | 0.230959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368138E+11 | 0.109448E+12 | 0.789401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457654E+11 | 0.207545E+12 | 0.332185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450809E+11 | 0.212911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528341E+11 | 0.373490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602547E+11 | 0.653850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.687905E+11 | 0.768562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.539380E+11 | 0.450866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.497810E+11 | 0.533331E+12 | 18435462.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378065E+11 | 0.218934E+12 | 0.377123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348286E+11 | 0.229444E+12 | 0.555308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550959E+12 | 0.406370E+13 | 0.268933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.313788E+11 | 0.109448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.687905E+11 | 0.768562E+12 | 0.104089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.272505E+10 | 0.115662E+11 | 0.383191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253284E+10 | 0.634914E+10 | 0.173941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302247E+10 | 0.790772E+10 | 0.264557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.412667E+10 | 0.199934E+11 | 0.235320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.408676E+10 | 0.203643E+11 | 57037009.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.518882E+10 | 0.384768E+11 | 4987.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.623577E+10 | 0.696404E+11 | 6690.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.698082E+10 | 0.810754E+11 | 13751.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.497994E+10 | 0.440443E+11 | 5207.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435978E+10 | 0.507875E+11 | 94566720.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.289743E+10 | 0.124077E+11 | 0.758997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273130E+10 | 0.145072E+11 | 0.228877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498677E+11 | 0.377120E+12 | 0.116516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.253284E+10 | 0.634914E+10 | 4987.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.698082E+10 | 0.810754E+11 | 0.383191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125080E+11 | 0.103200E+11 | 119.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108734E+11 | 0.450828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126273E+11 | 0.511424E+10 | 82.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115694E+11 | 0.135654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121535E+11 | 0.127815E+11 | 76.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121478E+11 | 0.233821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115840E+11 | 0.406492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126792E+11 | 0.463271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118755E+11 | 0.282003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122385E+11 | 0.374460E+11 | 291.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118710E+11 | 0.117432E+11 | 490.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120682E+11 | 0.146239E+11 | 709.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144196E+12 | 0.248661E+12 | 1771.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108734E+11 | 0.450828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126792E+11 | 0.463271E+11 | 709.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.956903E+11 | 0.882186E+10 | 0.00 | 0.00 | 0.00 | 0.628659E+11 | 0.00 | 0.00 |
February | 0.864299E+11 | 0.890193E+10 | 0.00 | 0.00 | 0.00 | 0.544506E+11 | 0.00 | 0.00 |
March | 0.956903E+11 | 0.593759E+11 | 0.00 | 0.00 | 0.00 | 0.456794E+11 | 0.00 | 0.00 |
April | 0.926035E+11 | 0.350390E+12 | 0.00 | 0.00 | 0.00 | 0.158427E+11 | 0.00 | 0.00 |
May | 0.956903E+11 | 0.128953E+10 | 0.00 | 0.00 | 0.00 | 0.463957E+10 | 0.00 | 0.00 |
June | 0.926035E+11 | 0.824113E+11 | 0.00 | 0.00 | 0.00 | 0.286284E+09 | 0.00 | 0.00 |
July | 0.956903E+11 | 0.489618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.956903E+11 | 0.937178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926035E+11 | 0.191610E+11 | 0.00 | 0.00 | 0.00 | 0.389831E+10 | 0.00 | 0.00 |
October | 0.956903E+11 | 0.143167E+12 | 0.00 | 0.00 | 0.00 | 0.576161E+11 | 0.00 | 0.00 |
November | 0.926035E+11 | 0.942730E+11 | 0.00 | 0.00 | 0.00 | 0.807744E+11 | 0.00 | 0.00 |
December | 0.956903E+11 | 0.238652E+12 | 0.00 | 0.00 | 0.00 | 0.147471E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.112668E+13 | 0.243324E+13 | 0.00 | 0.00 | 0.00 | 0.473525E+12 | 0.00 | 0.00 |
Minimum of Months | 0.864299E+11 | 0.128953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956903E+11 | 0.937178E+12 | 0.00 | 0.00 | 0.00 | 0.147471E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141605E+10 | 0.507486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127901E+10 | 0.927580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141605E+10 | 0.154285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137037E+10 | 0.201168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141605E+10 | 0.546005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137037E+10 | 0.105143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141605E+10 | 0.161703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141605E+10 | 0.211971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137037E+10 | 0.559105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141605E+10 | 0.108294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137037E+10 | 0.151034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141605E+10 | 0.205640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166728E+11 | 0.155326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127901E+10 | 0.507486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141605E+10 | 0.211971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135244E+11 | 0.380616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122156E+11 | 0.800006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135244E+11 | 0.138710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130881E+11 | 0.187146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135244E+11 | 0.471874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130881E+11 | 0.968099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135244E+11 | 0.152187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135244E+11 | 0.200436E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130881E+11 | 0.493961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135244E+11 | 0.985416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130881E+11 | 0.136290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135244E+11 | 0.186956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159239E+12 | 0.141172E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122156E+11 | 0.380616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135244E+11 | 0.200436E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137469E+10 | 0.258028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124166E+10 | 0.699281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137469E+10 | 0.129630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133035E+10 | 0.182629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137469E+10 | 0.426672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133035E+10 | 0.948980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137469E+10 | 0.151521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137469E+10 | 0.199438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133035E+10 | 0.465753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137469E+10 | 0.940594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133035E+10 | 0.127172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137469E+10 | 0.175062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161859E+11 | 0.133938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124166E+10 | 0.258028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137469E+10 | 0.199438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.518966E+10 | 0.488393E+09 | 0.187112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.516888E+10 | 68364358.05 | 0.109026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681006E+10 | 0.252464E+09 | 0.130551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.873205E+10 | 6906764.18 | 0.296910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635572E+10 | 5435.95 | 0.258458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.785261E+10 | 8542.68 | 0.473497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.966118E+10 | 9438.40 | 0.875780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115826E+11 | 22601.90 | 0.108515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.723464E+10 | 6585.18 | 0.532685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.756840E+10 | 4650.73 | 0.669074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690104E+10 | 289198.13 | 0.230624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688991E+10 | 0.139019E+09 | 0.269324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.899468E+11 | 0.955493E+09 | 0.511819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.516888E+10 | 4650.73 | 0.109026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115826E+11 | 0.488393E+09 | 0.108515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.336864E+11 | 0.104089E+11 | 0.191014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313788E+11 | 0.230959E+10 | 0.114301E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368138E+11 | 0.789401E+10 | 0.109448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457654E+11 | 0.332185E+09 | 0.207545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450809E+11 | 0.00 | 0.212911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528341E+11 | 0.00 | 0.373490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602547E+11 | 0.00 | 0.653850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.687905E+11 | 0.00 | 0.768562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.539380E+11 | 0.00 | 0.450866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.497810E+11 | 18435462.81 | 0.533331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378065E+11 | 0.377123E+09 | 0.218934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348286E+11 | 0.555308E+10 | 0.229444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550959E+12 | 0.268933E+11 | 0.406370E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.313788E+11 | 0.00 | 0.109448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.687905E+11 | 0.104089E+11 | 0.768562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.272505E+10 | 0.383191E+10 | 0.115662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253284E+10 | 0.173941E+10 | 0.634914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302247E+10 | 0.264557E+10 | 0.790772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.412667E+10 | 0.235320E+09 | 0.199934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.408676E+10 | 57037009.36 | 0.203643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.518882E+10 | 4987.90 | 0.384768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.623577E+10 | 6690.92 | 0.696404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.698082E+10 | 13751.96 | 0.810754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.497994E+10 | 5207.57 | 0.440443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435978E+10 | 94566720.48 | 0.507875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.289743E+10 | 0.758997E+09 | 0.124077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273130E+10 | 0.228877E+10 | 0.145072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498677E+11 | 0.116516E+11 | 0.377120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.253284E+10 | 4987.90 | 0.634914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.698082E+10 | 0.383191E+10 | 0.810754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125080E+11 | 119.85 | 0.103200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108734E+11 | 0.00 | 0.450828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126273E+11 | 82.18 | 0.511424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115694E+11 | 0.00 | 0.135654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121535E+11 | 76.97 | 0.127815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121478E+11 | 0.00 | 0.233821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115840E+11 | 0.00 | 0.406492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126792E+11 | 0.00 | 0.463271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118755E+11 | 0.00 | 0.282003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122385E+11 | 291.79 | 0.374460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118710E+11 | 490.25 | 0.117432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120682E+11 | 709.96 | 0.146239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144196E+12 | 1771.00 | 0.248661E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108734E+11 | 0.00 | 0.450828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126792E+11 | 709.96 | 0.463271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.956903E+11 | 0.00 | 0.137532E+11 | 0.00 | 0.493131E+10 | 0.00 | 0.00 | 0.00 | 0.631489E+11 | 0.00 | 0.00 | 0.00 |
February | 0.864299E+11 | 0.00 | 0.136152E+11 | 0.00 | 0.471330E+10 | 0.00 | 0.00 | 0.00 | 0.546957E+11 | 0.00 | 0.00 | 0.00 |
March | 0.956903E+11 | 0.00 | 0.766068E+11 | 0.00 | 0.172309E+11 | 0.00 | 0.00 | 0.00 | 0.458850E+11 | 0.00 | 0.00 | 0.00 |
April | 0.926035E+11 | 0.00 | 0.436778E+12 | 0.00 | 0.863884E+11 | 0.00 | 0.00 | 0.00 | 0.159141E+11 | 0.00 | 0.00 | 0.00 |
May | 0.956903E+11 | 0.00 | 0.390044E+10 | 0.00 | 0.261091E+10 | 0.00 | 0.00 | 0.00 | 0.466045E+10 | 0.00 | 0.00 | 0.00 |
June | 0.926035E+11 | 0.00 | 0.106140E+12 | 0.00 | 0.237287E+11 | 0.00 | 0.00 | 0.00 | 0.287573E+09 | 0.00 | 0.00 | 0.00 |
July | 0.956903E+11 | 0.00 | 0.608069E+12 | 0.00 | 0.118451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.956903E+11 | 0.00 | 0.115479E+13 | 0.00 | 0.217608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926035E+11 | 0.00 | 0.275740E+11 | 0.00 | 0.841293E+10 | 0.00 | 0.00 | 0.00 | 0.391586E+10 | 0.00 | 0.00 | 0.00 |
October | 0.956903E+11 | 0.00 | 0.185121E+12 | 0.00 | 0.419539E+11 | 0.00 | 0.00 | 0.00 | 0.578755E+11 | 0.00 | 0.00 | 0.00 |
November | 0.926035E+11 | 0.00 | 0.121592E+12 | 0.00 | 0.273189E+11 | 0.00 | 0.00 | 0.00 | 0.811380E+11 | 0.00 | 0.00 | 0.00 |
December | 0.956903E+11 | 0.00 | 0.304388E+12 | 0.00 | 0.657357E+11 | 0.00 | 0.00 | 0.00 | 0.148135E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112668E+13 | 0.00 | 0.305232E+13 | 0.00 | 0.619084E+12 | 0.00 | 0.00 | 0.00 | 0.475656E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.864299E+11 | 0.00 | 0.390044E+10 | 0.00 | 0.261091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956903E+11 | 0.00 | 0.115479E+13 | 0.00 | 0.217608E+12 | 0.00 | 0.00 | 0.00 | 0.148135E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141605E+10 | 0.00 | 0.620037E+10 | 0.00 | 0.112551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127901E+10 | 0.00 | 0.111836E+11 | 0.00 | 0.190777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141605E+10 | 0.00 | 0.184734E+11 | 0.00 | 0.304488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137037E+10 | 0.00 | 0.241013E+11 | 0.00 | 0.398447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141605E+10 | 0.00 | 0.664371E+10 | 0.00 | 0.118366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137037E+10 | 0.00 | 0.127322E+11 | 0.00 | 0.221787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141605E+10 | 0.00 | 0.197014E+11 | 0.00 | 0.353105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141605E+10 | 0.00 | 0.259377E+11 | 0.00 | 0.474059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137037E+10 | 0.00 | 0.684278E+10 | 0.00 | 0.125173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141605E+10 | 0.00 | 0.132547E+11 | 0.00 | 0.242532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137037E+10 | 0.00 | 0.181419E+11 | 0.00 | 0.303849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141605E+10 | 0.00 | 0.246715E+11 | 0.00 | 0.410752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166728E+11 | 0.00 | 0.187884E+12 | 0.00 | 0.325589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127901E+10 | 0.00 | 0.620037E+10 | 0.00 | 0.112551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141605E+10 | 0.00 | 0.259377E+11 | 0.00 | 0.474059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135244E+11 | 0.00 | 0.466755E+11 | 0.00 | 0.861391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122156E+11 | 0.00 | 0.966192E+11 | 0.00 | 0.166186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135244E+11 | 0.00 | 0.166289E+12 | 0.00 | 0.275789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130881E+11 | 0.00 | 0.224368E+12 | 0.00 | 0.372223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135244E+11 | 0.00 | 0.575021E+11 | 0.00 | 0.103148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130881E+11 | 0.00 | 0.117316E+12 | 0.00 | 0.205061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135244E+11 | 0.00 | 0.185494E+12 | 0.00 | 0.333072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135244E+11 | 0.00 | 0.245338E+12 | 0.00 | 0.449017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130881E+11 | 0.00 | 0.605374E+11 | 0.00 | 0.111413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135244E+11 | 0.00 | 0.120753E+12 | 0.00 | 0.222115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130881E+11 | 0.00 | 0.163908E+12 | 0.00 | 0.276172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135244E+11 | 0.00 | 0.224593E+12 | 0.00 | 0.376368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159239E+12 | 0.00 | 0.170939E+13 | 0.00 | 0.297670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122156E+11 | 0.00 | 0.466755E+11 | 0.00 | 0.861391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135244E+11 | 0.00 | 0.245338E+12 | 0.00 | 0.449017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137469E+10 | 0.00 | 0.318106E+10 | 0.00 | 0.600778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124166E+10 | 0.00 | 0.846423E+10 | 0.00 | 0.147142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137469E+10 | 0.00 | 0.155649E+11 | 0.00 | 0.260183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133035E+10 | 0.00 | 0.219185E+11 | 0.00 | 0.365560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137469E+10 | 0.00 | 0.520865E+10 | 0.00 | 0.941932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133035E+10 | 0.00 | 0.115096E+11 | 0.00 | 0.201975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137469E+10 | 0.00 | 0.184809E+11 | 0.00 | 0.332880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137469E+10 | 0.00 | 0.244288E+11 | 0.00 | 0.448500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133035E+10 | 0.00 | 0.571738E+10 | 0.00 | 0.105985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137469E+10 | 0.00 | 0.115456E+11 | 0.00 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133035E+10 | 0.00 | 0.153199E+11 | 0.00 | 0.260273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137469E+10 | 0.00 | 0.210728E+11 | 0.00 | 0.356659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161859E+11 | 0.00 | 0.162412E+12 | 0.00 | 0.284740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124166E+10 | 0.00 | 0.318106E+10 | 0.00 | 0.600778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137469E+10 | 0.00 | 0.244288E+11 | 0.00 | 0.448500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.348989E+09 | 94156320.78 | 0.00 | 0.115945E+09 | 0.00 | 0.00 | 0.567645E+11 | 0.00 | 1.03 |
February | 0.236103E+09 | 7986846.23 | 0.00 | 95111308.27 | 0.00 | 0.00 | 0.535646E+11 | 0.00 | 1.02 |
March | 0.265216E+09 | 0.00 | 0.00 | 0.111844E+09 | 0.00 | 0.00 | 0.634629E+11 | 0.00 | 1.05 |
April | 0.219746E+09 | 6346669.09 | 0.00 | 0.105640E+09 | 0.00 | 0.00 | 0.508868E+11 | 0.00 | 1.16 |
May | 0.174793E+09 | 7282479.34 | 0.00 | 0.102930E+09 | 0.00 | 0.00 | 0.524767E+11 | 0.00 | 1.21 |
June | 0.157009E+09 | 36052134.71 | 0.00 | 0.105041E+09 | 0.00 | 0.00 | 0.430032E+11 | 0.00 | 1.35 |
July | 0.144265E+09 | 0.172792E+10 | 0.00 | 88516529.09 | 0.00 | 0.00 | 0.279781E+11 | 0.00 | 1.18 |
August | 0.128719E+09 | 0.219366E+10 | 0.00 | 93958221.27 | 0.00 | 0.00 | 0.292359E+11 | 0.00 | 1.29 |
September | 0.219310E+09 | 0.941473E+09 | 0.00 | 97495270.86 | 33383022.78 | 0.00 | 0.384842E+11 | 0.00 | 1.26 |
October | 0.227088E+09 | 0.233176E+10 | 0.00 | 95827641.45 | 22561704.47 | 0.00 | 0.353869E+11 | 0.00 | 1.17 |
November | 0.273148E+09 | 9023625.27 | 0.00 | 0.115556E+09 | 0.00 | 0.00 | 0.574326E+11 | 0.00 | 1.14 |
December | 0.425722E+09 | 431954.60 | 0.00 | 0.118064E+09 | 0.00 | 0.00 | 0.539137E+11 | 0.00 | 1.04 |
Annual Sum or Average | 0.282011E+10 | 0.735610E+10 | 0.00 | 0.124593E+10 | 55944727.25 | 0.00 | 0.562590E+12 | 0.00 | 1.16 |
Minimum of Months | 0.128719E+09 | 0.00 | 0.00 | 88516529.09 | 0.00 | 0.00 | 0.279781E+11 | 0.00 | 1.02 |
Maximum of Months | 0.425722E+09 | 0.233176E+10 | 0.00 | 0.118064E+09 | 33383022.78 | 0.00 | 0.634629E+11 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234764E+10 | 55442249.28 | 0.00 | 83514991.82 | 30251272.80 | 0.00 | 0.390111E+11 | 0.00 | 0.68 |
February | 0.255326E+10 | 16489761.17 | 0.00 | 77129206.92 | 0.00 | 0.00 | 0.405270E+11 | 0.00 | 0.75 |
March | 0.223279E+10 | 0.00 | 0.00 | 97241364.04 | 10587657.97 | 0.00 | 0.516497E+11 | 0.00 | 0.83 |
April | 0.516376E+10 | 6995620.82 | 0.00 | 97120517.80 | 41750122.40 | 0.00 | 0.426673E+11 | 0.00 | 0.97 |
May | 0.327052E+10 | 33999482.65 | 0.00 | 84332397.34 | 0.00 | 0.00 | 0.384688E+11 | 0.00 | 0.86 |
June | 0.246541E+10 | 0.302739E+09 | 0.00 | 89070682.91 | 0.00 | 0.00 | 0.319727E+11 | 0.00 | 0.98 |
July | 0.602113E+10 | 0.335017E+10 | 0.00 | 63380132.98 | 0.279308E+09 | 0.00 | 0.162733E+11 | 0.00 | 1.01 |
August | 0.661247E+10 | 0.469914E+10 | 0.00 | 59914142.56 | 0.312772E+09 | 0.00 | 0.150173E+11 | 0.00 | 1.14 |
September | 0.207599E+10 | 0.933412E+09 | 0.00 | 74881123.92 | 49346939.10 | 0.00 | 0.253901E+11 | 0.00 | 0.86 |
October | 0.204189E+10 | 0.238688E+10 | 0.00 | 73761962.40 | 0.273743E+09 | 0.00 | 0.247130E+11 | 0.00 | 0.82 |
November | 0.267496E+10 | 2954902.07 | 0.00 | 95318371.46 | 16291438.06 | 0.00 | 0.445677E+11 | 0.00 | 0.85 |
December | 0.363809E+10 | 2262197.33 | 0.00 | 0.100664E+09 | 0.00 | 0.00 | 0.426790E+11 | 0.00 | 0.80 |
Annual Sum or Average | 0.410979E+11 | 0.117905E+11 | 0.00 | 0.996329E+09 | 0.101405E+10 | 0.00 | 0.412937E+12 | 0.00 | 0.88 |
Minimum of Months | 0.204189E+10 | 0.00 | 0.00 | 59914142.56 | 0.00 | 0.00 | 0.150173E+11 | 0.00 | 0.68 |
Maximum of Months | 0.661247E+10 | 0.469914E+10 | 0.00 | 0.100664E+09 | 0.312772E+09 | 0.00 | 0.516497E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.713234E+11 | 56731777.82 | 0.00 | 0.445270E+09 | 0.543419E+09 | 0.00 | 0.202280E+12 | 0.00 | 0.45 |
February | 0.586413E+11 | 0.168892E+09 | 0.00 | 0.409005E+09 | 0.00 | 0.00 | 0.225688E+12 | 0.00 | 0.49 |
March | 0.594296E+11 | 0.00 | 0.00 | 0.485924E+09 | 0.266578E+09 | 0.00 | 0.292847E+12 | 0.00 | 0.54 |
April | 0.322144E+11 | 34635278.53 | 0.00 | 0.549124E+09 | 0.567203E+09 | 0.00 | 0.273498E+12 | 0.00 | 0.64 |
May | 0.283658E+11 | 0.348399E+09 | 0.00 | 0.605169E+09 | 0.00 | 0.00 | 0.297427E+12 | 0.00 | 0.68 |
June | 0.190109E+11 | 0.185322E+10 | 0.00 | 0.656255E+09 | 360114.96 | 0.00 | 0.242673E+12 | 0.00 | 0.76 |
July | 0.229246E+11 | 0.227108E+11 | 0.00 | 0.476508E+09 | 0.236196E+10 | 0.00 | 0.120709E+12 | 0.00 | 0.72 |
August | 0.121078E+11 | 0.290497E+11 | 0.00 | 0.501754E+09 | 0.265563E+10 | 0.00 | 0.116776E+12 | 0.00 | 0.76 |
September | 0.191490E+11 | 0.847306E+10 | 0.00 | 0.564070E+09 | 0.617961E+09 | 0.00 | 0.197357E+12 | 0.00 | 0.69 |
October | 0.130243E+11 | 0.183693E+11 | 0.00 | 0.504266E+09 | 0.338480E+10 | 0.00 | 0.178861E+12 | 0.00 | 0.62 |
November | 0.330869E+11 | 8201907.02 | 0.00 | 0.512797E+09 | 0.189696E+09 | 0.00 | 0.248182E+12 | 0.00 | 0.49 |
December | 0.561524E+11 | 21152524.43 | 0.00 | 0.456075E+09 | 11199692.26 | 0.00 | 0.204421E+12 | 0.00 | 0.45 |
Annual Sum or Average | 0.425430E+12 | 0.810940E+11 | 0.00 | 0.616622E+10 | 0.105988E+11 | 0.00 | 0.260072E+13 | 0.00 | 0.61 |
Minimum of Months | 0.121078E+11 | 0.00 | 0.00 | 0.409005E+09 | 0.00 | 0.00 | 0.116776E+12 | 0.00 | 0.45 |
Maximum of Months | 0.713234E+11 | 0.290497E+11 | 0.00 | 0.656255E+09 | 0.338480E+10 | 0.00 | 0.297427E+12 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150837E+11 | 3263448.87 | 0.00 | 15056282.26 | 45960151.83 | 0.216466E+09 | 0.858344E+10 | 0.00 | 0.43 |
February | 0.124827E+11 | 4252357.28 | 0.00 | 17472419.42 | 75426.05 | 1707987.40 | 0.120730E+11 | 0.00 | 0.46 |
March | 0.142232E+11 | 0.00 | 0.00 | 22040622.30 | 28084079.98 | 0.00 | 0.158112E+11 | 0.00 | 0.48 |
April | 0.760953E+10 | 175907.60 | 0.00 | 38931828.24 | 31838267.41 | 0.00 | 0.212120E+11 | 0.00 | 0.61 |
May | 0.761879E+10 | 14587367.68 | 0.00 | 44175601.03 | 0.00 | 0.00 | 0.234462E+11 | 0.00 | 0.65 |
June | 0.390361E+10 | 87989522.66 | 0.00 | 56187035.63 | 0.00 | 0.00 | 0.225557E+11 | 0.00 | 0.76 |
July | 0.254393E+10 | 0.189300E+10 | 0.00 | 46261352.41 | 0.160628E+09 | 0.00 | 0.121761E+11 | 0.00 | 0.74 |
August | 0.137088E+10 | 0.252909E+10 | 0.00 | 47009183.10 | 0.185797E+09 | 0.00 | 0.112086E+11 | 0.00 | 0.78 |
September | 0.424261E+10 | 0.632855E+09 | 0.00 | 44057457.26 | 48880288.95 | 0.00 | 0.163489E+11 | 0.00 | 0.66 |
October | 0.557750E+10 | 0.153826E+10 | 0.00 | 32235696.17 | 0.343243E+09 | 0.00 | 0.106842E+11 | 0.00 | 0.58 |
November | 0.107975E+11 | 1335.91 | 0.00 | 24339294.16 | 7029171.86 | 0.00 | 0.143869E+11 | 0.00 | 0.48 |
December | 0.137564E+11 | 746508.67 | 0.00 | 16181358.19 | 3442136.43 | 1569262.34 | 0.857728E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.992104E+11 | 0.670422E+10 | 0.00 | 0.403948E+09 | 0.854977E+09 | 0.219743E+09 | 0.177063E+12 | 0.00 | 0.59 |
Minimum of Months | 0.137088E+10 | 0.00 | 0.00 | 15056282.26 | 0.00 | 0.00 | 0.857728E+10 | 0.00 | 0.43 |
Maximum of Months | 0.150837E+11 | 0.252909E+10 | 0.00 | 56187035.63 | 0.343243E+09 | 0.216466E+09 | 0.234462E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201806E+10 | 5852925.11 | 0.00 | 3589336.48 | 4657196.34 | 0.00 | 0.170185E+10 | 0.00 | 0.50 |
February | 0.177233E+10 | 2000555.05 | 0.00 | 4004016.18 | 0.00 | 0.00 | 0.226189E+10 | 0.00 | 0.57 |
March | 0.170384E+10 | 0.00 | 0.00 | 5724139.02 | 1331389.34 | 0.00 | 0.337719E+10 | 0.00 | 0.65 |
April | 0.130820E+10 | 926617.90 | 0.00 | 7892578.86 | 5250043.78 | 0.00 | 0.375674E+10 | 0.00 | 0.87 |
May | 0.109996E+10 | 5075718.19 | 0.00 | 7964813.33 | 0.00 | 0.00 | 0.380987E+10 | 0.00 | 0.84 |
June | 0.461685E+09 | 47749449.71 | 0.00 | 10437584.45 | 0.00 | 0.00 | 0.394754E+10 | 0.00 | 1.07 |
July | 0.820970E+09 | 0.566137E+09 | 0.00 | 7345220.12 | 35122746.52 | 0.00 | 0.197591E+10 | 0.00 | 1.13 |
August | 0.876553E+09 | 0.737094E+09 | 0.00 | 6423401.93 | 39330851.66 | 0.00 | 0.159548E+10 | 0.00 | 1.19 |
September | 0.661443E+09 | 0.158212E+09 | 0.00 | 6637169.58 | 6205337.28 | 0.00 | 0.230979E+10 | 0.00 | 0.82 |
October | 0.776959E+09 | 0.371391E+09 | 0.00 | 5555151.24 | 34422975.63 | 0.00 | 0.184936E+10 | 0.00 | 0.74 |
November | 0.158587E+10 | 331426.46 | 0.00 | 5510121.45 | 2048635.03 | 0.00 | 0.267569E+10 | 0.00 | 0.64 |
December | 0.180884E+10 | 247894.37 | 0.00 | 5075090.83 | 0.00 | 0.00 | 0.211048E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.148947E+11 | 0.189502E+10 | 0.00 | 76158623.46 | 0.128369E+09 | 0.00 | 0.313718E+11 | 0.00 | 0.80 |
Minimum of Months | 0.461685E+09 | 0.00 | 0.00 | 3589336.48 | 0.00 | 0.00 | 0.159548E+10 | 0.00 | 0.50 |
Maximum of Months | 0.201806E+10 | 0.737094E+09 | 0.00 | 10437584.45 | 39330851.66 | 0.00 | 0.394754E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.994205E+09 | 5209925.74 | 0.00 | 5226145.66 | 2439028.98 | 0.00 | 0.240514E+10 | 0.00 | 0.70 |
February | 0.983585E+09 | 1518965.24 | 0.00 | 4704001.60 | 0.00 | 0.00 | 0.243966E+10 | 0.00 | 0.76 |
March | 0.100377E+10 | 209061.57 | 0.00 | 6358369.05 | 698615.84 | 0.00 | 0.325984E+10 | 0.00 | 0.88 |
April | 0.827390E+09 | 2233655.05 | 0.00 | 8908442.24 | 2711191.15 | 0.00 | 0.390811E+10 | 0.00 | 1.27 |
May | 0.571231E+09 | 5181263.97 | 0.00 | 8683345.72 | 0.00 | 0.00 | 0.389890E+10 | 0.00 | 1.20 |
June | 0.342660E+09 | 39340860.62 | 0.00 | 9682767.92 | 0.00 | 0.00 | 0.328419E+10 | 0.00 | 1.42 |
July | 0.494993E+09 | 0.492684E+09 | 0.00 | 8050020.16 | 13079674.84 | 0.00 | 0.194565E+10 | 0.00 | 1.56 |
August | 0.587102E+09 | 0.725667E+09 | 0.00 | 6496088.86 | 15826092.34 | 0.00 | 0.151575E+10 | 0.00 | 1.66 |
September | 0.378639E+09 | 0.125679E+09 | 0.00 | 7355232.11 | 3978629.77 | 0.00 | 0.232187E+10 | 0.00 | 1.16 |
October | 0.445284E+09 | 0.287947E+09 | 0.00 | 5703903.46 | 22062673.42 | 0.00 | 0.186712E+10 | 0.00 | 0.95 |
November | 0.895057E+09 | 245993.41 | 0.00 | 5775917.94 | 1313508.03 | 0.00 | 0.265914E+10 | 0.00 | 0.82 |
December | 0.104485E+10 | 223498.76 | 0.00 | 5334114.79 | 0.00 | 0.00 | 0.211219E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.856877E+10 | 0.168614E+10 | 0.00 | 82278349.51 | 62109414.38 | 0.00 | 0.316176E+11 | 0.00 | 1.09 |
Minimum of Months | 0.342660E+09 | 209061.57 | 0.00 | 4704001.60 | 0.00 | 0.00 | 0.151575E+10 | 0.00 | 0.70 |
Maximum of Months | 0.104485E+10 | 0.725667E+09 | 0.00 | 9682767.92 | 22062673.42 | 0.00 | 0.390811E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102884E+10 | 37205192.35 | 0.00 | 19069766.72 | 3088743.84 | 0.00 | 0.769168E+10 | 0.00 | 1.31 |
February | 0.112475E+10 | 6347484.60 | 0.00 | 13522743.67 | 0.00 | 0.00 | 0.625366E+10 | 0.00 | 1.16 |
March | 0.140056E+10 | 2642814.72 | 0.00 | 12246425.13 | 122029.20 | 0.00 | 0.620983E+10 | 0.00 | 1.10 |
April | 0.124703E+10 | 5453691.10 | 0.00 | 12552549.46 | 2288641.56 | 0.00 | 0.536451E+10 | 0.00 | 1.23 |
May | 0.130001E+10 | 6537289.88 | 0.00 | 8476475.76 | 0.00 | 0.00 | 0.379262E+10 | 0.00 | 0.91 |
June | 0.677183E+09 | 55345612.74 | 0.00 | 9476885.26 | 0.00 | 0.00 | 0.344120E+10 | 0.00 | 1.04 |
July | 0.830005E+09 | 0.651293E+09 | 0.00 | 7042596.47 | 27342606.04 | 0.00 | 0.184521E+10 | 0.00 | 1.16 |
August | 0.872623E+09 | 0.104644E+10 | 0.00 | 8072236.52 | 27093654.51 | 0.00 | 0.187245E+10 | 0.00 | 1.48 |
September | 0.433267E+09 | 0.278667E+09 | 0.00 | 13546386.05 | 6193002.41 | 0.00 | 0.394328E+10 | 0.00 | 1.35 |
October | 0.523809E+09 | 0.770140E+09 | 0.00 | 14568119.12 | 15673488.57 | 0.00 | 0.358945E+10 | 0.00 | 1.30 |
November | 0.667944E+09 | 5628032.31 | 0.00 | 20378900.59 | 316798.53 | 0.00 | 0.806043E+10 | 0.00 | 1.45 |
December | 0.813562E+09 | 737203.94 | 0.00 | 25288491.13 | 0.00 | 0.00 | 0.786610E+10 | 0.00 | 1.44 |
Annual Sum or Average | 0.109196E+11 | 0.286644E+10 | 0.00 | 0.164242E+09 | 82118964.67 | 0.00 | 0.599304E+11 | 0.00 | 1.24 |
Minimum of Months | 0.433267E+09 | 737203.94 | 0.00 | 7042596.47 | 0.00 | 0.00 | 0.184521E+10 | 0.00 | 0.91 |
Maximum of Months | 0.140056E+10 | 0.104644E+10 | 0.00 | 25288491.13 | 27342606.04 | 0.00 | 0.806043E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.477913E+09 | 15983967.66 | 0.00 | 7905857.05 | 1714230.24 | 0.00 | 0.374645E+10 | 0.00 | 0.95 |
February | 0.202783E+09 | 3032158.06 | 0.00 | 10104281.68 | 0.00 | 0.00 | 0.530146E+10 | 0.00 | 1.27 |
March | 0.152422E+09 | 541560.21 | 0.00 | 14727336.37 | 402974.53 | 0.00 | 0.791629E+10 | 0.00 | 1.64 |
April | 0.179892E+09 | 9217177.24 | 0.00 | 22705892.16 | 281409.34 | 0.00 | 0.879505E+10 | 0.00 | 2.40 |
May | 0.197248E+09 | 5210663.66 | 0.00 | 14459738.77 | 0.00 | 0.00 | 0.610059E+10 | 0.00 | 1.71 |
June | 0.115699E+09 | 52425465.92 | 0.00 | 17787631.13 | 0.00 | 0.00 | 0.603566E+10 | 0.00 | 2.33 |
July | 0.243814E+09 | 0.883474E+09 | 0.00 | 18263668.04 | 4677107.80 | 0.00 | 0.374568E+10 | 0.00 | 2.55 |
August | 0.275432E+09 | 0.119326E+10 | 0.00 | 17371451.15 | 2988368.41 | 0.00 | 0.345219E+10 | 0.00 | 2.93 |
September | 0.115942E+09 | 0.185870E+09 | 0.00 | 13113632.88 | 1986098.04 | 0.00 | 0.401516E+10 | 0.00 | 1.75 |
October | 0.126105E+09 | 0.475033E+09 | 0.00 | 11679592.88 | 7792161.73 | 0.00 | 0.340013E+10 | 0.00 | 1.54 |
November | 0.162128E+09 | 4314213.86 | 0.00 | 14183951.35 | 203586.81 | 0.00 | 0.645640E+10 | 0.00 | 1.58 |
December | 0.198615E+09 | 446326.27 | 0.00 | 16325544.21 | 0.00 | 0.00 | 0.640511E+10 | 0.00 | 1.54 |
Annual Sum or Average | 0.244799E+10 | 0.282880E+10 | 0.00 | 0.178629E+09 | 20045936.89 | 0.00 | 0.653702E+11 | 0.00 | 1.85 |
Minimum of Months | 0.115699E+09 | 446326.27 | 0.00 | 7905857.05 | 0.00 | 0.00 | 0.340013E+10 | 0.00 | 0.95 |
Maximum of Months | 0.477913E+09 | 0.119326E+10 | 0.00 | 22705892.16 | 7792161.73 | 0.00 | 0.879505E+10 | 0.00 | 2.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.246690E+11 | 2039278.40 | 0.00 | 8025215.88 | 72062790.44 | 0.173280E+10 | 0.303482E+10 | 0.00 | 0.38 |
February | 0.238547E+11 | 16536647.46 | 0.00 | 7788141.56 | 0.00 | 0.107219E+09 | 0.501555E+10 | 0.00 | 0.39 |
March | 0.275033E+11 | 0.00 | 0.00 | 12893917.34 | 33449402.19 | 0.650060E+09 | 0.742722E+10 | 0.00 | 0.43 |
April | 0.174191E+11 | 4207865.10 | 0.00 | 33690845.41 | 71170870.79 | 80254314.19 | 0.151085E+11 | 0.00 | 0.55 |
May | 0.146916E+11 | 48585287.97 | 0.00 | 48714228.08 | 0.00 | 0.00 | 0.224582E+11 | 0.00 | 0.64 |
June | 0.868851E+10 | 0.286693E+09 | 0.00 | 69830383.44 | 45186.14 | 0.00 | 0.246723E+11 | 0.00 | 0.82 |
July | 0.583783E+10 | 0.393071E+10 | 0.00 | 49469714.06 | 0.296371E+09 | 0.00 | 0.123036E+11 | 0.00 | 0.80 |
August | 0.650401E+10 | 0.446768E+10 | 0.00 | 40487751.60 | 0.333812E+09 | 0.00 | 0.823181E+10 | 0.00 | 0.78 |
September | 0.117938E+11 | 0.139887E+10 | 0.00 | 39913049.39 | 82020560.18 | 0.00 | 0.119765E+11 | 0.00 | 0.65 |
October | 0.128276E+11 | 0.291171E+10 | 0.00 | 25882982.41 | 0.293750E+09 | 0.00 | 0.728081E+10 | 0.00 | 0.55 |
November | 0.224902E+11 | 195186.66 | 0.00 | 12171730.07 | 24355772.92 | 39853945.73 | 0.557770E+10 | 0.00 | 0.38 |
December | 0.247837E+11 | 1686163.65 | 0.00 | 6084573.53 | 1542248.69 | 0.459248E+09 | 0.203721E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.201063E+12 | 0.130689E+11 | 0.00 | 0.354953E+09 | 0.120858E+10 | 0.306944E+10 | 0.125124E+12 | 0.00 | 0.56 |
Minimum of Months | 0.583783E+10 | 0.00 | 0.00 | 6084573.53 | 0.00 | 0.00 | 0.203721E+10 | 0.00 | 0.37 |
Maximum of Months | 0.275033E+11 | 0.446768E+10 | 0.00 | 69830383.44 | 0.333812E+09 | 0.173280E+10 | 0.246723E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105356E+11 | 33486411.50 | 0.00 | 28561496.63 | 3866704.66 | 0.347404E+09 | 0.115063E+11 | 0.00 | 0.45 |
February | 0.104469E+11 | 18388269.02 | 0.00 | 27343321.26 | 0.00 | 1935262.07 | 0.128314E+11 | 0.00 | 0.51 |
March | 0.110611E+11 | 6335264.59 | 0.00 | 40201111.88 | 16284954.30 | 0.143181E+09 | 0.185108E+11 | 0.00 | 0.62 |
April | 0.678153E+10 | 22726970.19 | 0.00 | 70947147.14 | 34851965.92 | 30794046.71 | 0.300631E+11 | 0.00 | 1.02 |
May | 0.636206E+10 | 58469792.58 | 0.00 | 70160539.86 | 0.00 | 0.00 | 0.302332E+11 | 0.00 | 1.00 |
June | 0.393783E+10 | 0.260510E+09 | 0.00 | 86688710.25 | 29132.46 | 0.00 | 0.273028E+11 | 0.00 | 1.25 |
July | 0.232742E+10 | 0.394461E+10 | 0.00 | 81156261.48 | 90241926.85 | 0.00 | 0.179900E+11 | 0.00 | 1.37 |
August | 0.218882E+10 | 0.562404E+10 | 0.00 | 68534563.26 | 0.119446E+09 | 0.00 | 0.143408E+11 | 0.00 | 1.42 |
September | 0.525496E+10 | 0.118393E+10 | 0.00 | 60759248.51 | 52839664.78 | 0.00 | 0.179366E+11 | 0.00 | 1.01 |
October | 0.540330E+10 | 0.264011E+10 | 0.00 | 41424133.52 | 0.177127E+09 | 0.00 | 0.130282E+11 | 0.00 | 0.76 |
November | 0.974318E+10 | 2065954.66 | 0.00 | 33536850.03 | 13659883.74 | 0.00 | 0.136787E+11 | 0.00 | 0.51 |
December | 0.107568E+11 | 2651893.23 | 0.00 | 27838489.63 | 0.00 | 83881606.81 | 0.903099E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.847996E+11 | 0.137973E+11 | 0.00 | 0.637152E+09 | 0.508347E+09 | 0.607196E+09 | 0.216453E+12 | 0.00 | 0.86 |
Minimum of Months | 0.218882E+10 | 2065954.66 | 0.00 | 27343321.26 | 0.00 | 0.00 | 0.903099E+10 | 0.00 | 0.44 |
Maximum of Months | 0.110611E+11 | 0.562404E+10 | 0.00 | 86688710.25 | 0.177127E+09 | 0.347404E+09 | 0.302332E+11 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104575E+11 | 0.389871E+09 | 0.00 | 0.188286E+09 | 3507191.87 | 0.133498E+09 | 0.606997E+11 | 0.00 | 1.07 |
February | 0.127589E+11 | 83703818.89 | 0.00 | 0.124307E+09 | 0.00 | 0.00 | 0.461543E+11 | 0.00 | 0.94 |
March | 0.163749E+11 | 46636218.98 | 0.00 | 96622813.51 | 7760393.21 | 0.257680E+09 | 0.434995E+11 | 0.00 | 0.87 |
April | 0.126661E+11 | 28686482.98 | 0.00 | 92456561.96 | 59048867.18 | 0.00 | 0.378008E+11 | 0.00 | 0.96 |
May | 0.143130E+11 | 67993882.54 | 0.00 | 64248447.98 | 0.00 | 0.00 | 0.277274E+11 | 0.00 | 0.75 |
June | 0.101806E+11 | 0.353093E+09 | 0.00 | 70193916.87 | 45204.06 | 0.00 | 0.232141E+11 | 0.00 | 0.85 |
July | 0.649388E+10 | 0.481046E+10 | 0.00 | 52665284.39 | 0.254438E+09 | 0.00 | 0.121170E+11 | 0.00 | 0.88 |
August | 0.449619E+10 | 0.730042E+10 | 0.00 | 69299225.15 | 0.309563E+09 | 0.00 | 0.137850E+11 | 0.00 | 1.13 |
September | 0.658713E+10 | 0.296876E+10 | 0.00 | 0.121973E+09 | 60234630.29 | 0.00 | 0.330463E+11 | 0.00 | 1.25 |
October | 0.607313E+10 | 0.793503E+10 | 0.00 | 0.132539E+09 | 49399903.35 | 0.00 | 0.290974E+11 | 0.00 | 1.16 |
November | 0.880126E+10 | 67378726.93 | 0.00 | 0.181477E+09 | 1279341.28 | 0.00 | 0.558255E+11 | 0.00 | 1.05 |
December | 0.966575E+10 | 17938610.92 | 0.00 | 0.224970E+09 | 0.00 | 43224357.14 | 0.533195E+11 | 0.00 | 1.07 |
Annual Sum or Average | 0.118868E+12 | 0.240700E+11 | 0.00 | 0.141904E+10 | 0.745277E+09 | 0.434402E+09 | 0.436287E+12 | 0.00 | 1.00 |
Minimum of Months | 0.449619E+10 | 17938610.92 | 0.00 | 52665284.39 | 0.00 | 0.00 | 0.121170E+11 | 0.00 | 0.75 |
Maximum of Months | 0.163749E+11 | 0.793503E+10 | 0.00 | 0.224970E+09 | 0.309563E+09 | 0.257680E+09 | 0.606997E+11 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129714E+11 | 91302954.28 | 0.00 | 31158091.76 | 12895075.10 | 0.296699E+09 | 0.107775E+11 | 0.00 | 0.51 |
February | 0.110224E+11 | 24926501.94 | 0.00 | 34171052.95 | 0.00 | 0.00 | 0.155901E+11 | 0.00 | 0.60 |
March | 0.108440E+11 | 0.00 | 0.00 | 47747437.14 | 21559129.87 | 55715933.00 | 0.255369E+11 | 0.00 | 0.75 |
April | 0.514733E+10 | 51850553.38 | 0.00 | 97334279.98 | 26502506.91 | 0.00 | 0.377928E+11 | 0.00 | 1.22 |
May | 0.492897E+10 | 43493688.04 | 0.00 | 94133649.43 | 0.00 | 0.00 | 0.386030E+11 | 0.00 | 1.22 |
June | 0.227306E+10 | 0.259521E+09 | 0.00 | 0.111784E+09 | 29123.80 | 0.00 | 0.372166E+11 | 0.00 | 1.57 |
July | 0.129543E+10 | 0.543191E+10 | 0.00 | 0.106821E+09 | 0.109659E+09 | 0.00 | 0.208736E+11 | 0.00 | 1.59 |
August | 0.101331E+10 | 0.587539E+10 | 0.00 | 91307561.55 | 0.112821E+09 | 0.00 | 0.168171E+11 | 0.00 | 1.63 |
September | 0.304098E+10 | 0.159077E+10 | 0.00 | 86015309.96 | 21442508.07 | 0.00 | 0.257238E+11 | 0.00 | 1.27 |
October | 0.443906E+10 | 0.338021E+10 | 0.00 | 52958346.55 | 90172340.95 | 0.00 | 0.140512E+11 | 0.00 | 0.90 |
November | 0.948575E+10 | 11422338.64 | 0.00 | 45347108.57 | 8375254.89 | 0.00 | 0.160736E+11 | 0.00 | 0.60 |
December | 0.119068E+11 | 3311549.23 | 0.00 | 35686488.67 | 894404.22 | 5289678.79 | 0.102667E+11 | 0.00 | 0.52 |
Annual Sum or Average | 0.783686E+11 | 0.167641E+11 | 0.00 | 0.834464E+09 | 0.404350E+09 | 0.357705E+09 | 0.269323E+12 | 0.00 | 1.03 |
Minimum of Months | 0.101331E+10 | 0.00 | 0.00 | 31158091.76 | 0.00 | 0.00 | 0.102667E+11 | 0.00 | 0.51 |
Maximum of Months | 0.129714E+11 | 0.587539E+10 | 0.00 | 0.111784E+09 | 0.112821E+09 | 0.296699E+09 | 0.386030E+11 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218643E+10 | 0.00 | 10778.97 | 325741.44 | 6149923.28 | 0.536868E+09 | 0.138458E+09 | 2179.74 | 0.40 |
February | 0.225582E+10 | 376432.87 | 0.00 | 313917.52 | 9443.48 | 0.291185E+09 | 0.247596E+09 | 0.00 | 0.41 |
March | 0.266931E+10 | 0.00 | 0.00 | 721955.68 | 3516176.56 | 0.304481E+09 | 0.483776E+09 | 0.00 | 0.43 |
April | 0.173090E+10 | 22926.81 | 0.00 | 2853604.28 | 3986207.47 | 41046829.42 | 0.144341E+10 | 0.00 | 0.54 |
May | 0.160003E+10 | 1926648.67 | 0.00 | 4130109.42 | 0.00 | 4041342.34 | 0.207685E+10 | 0.00 | 0.62 |
June | 0.928851E+09 | 13203711.15 | 0.00 | 6802674.68 | 0.00 | 0.00 | 0.253662E+10 | 0.00 | 0.82 |
July | 0.630263E+09 | 0.325278E+09 | 0.00 | 5278692.27 | 20110868.63 | 0.00 | 0.129770E+10 | 0.00 | 0.83 |
August | 0.590365E+09 | 0.384304E+09 | 0.00 | 4437317.64 | 25913377.02 | 0.00 | 0.909166E+09 | 0.00 | 0.82 |
September | 0.117201E+10 | 0.104478E+09 | 0.00 | 3801164.92 | 8112866.85 | 0.00 | 0.118921E+10 | 0.00 | 0.63 |
October | 0.123029E+10 | 0.241194E+09 | 0.00 | 2103856.75 | 34906694.08 | 34450028.96 | 0.583040E+09 | 0.00 | 0.54 |
November | 0.223983E+10 | 0.00 | 0.00 | 399813.93 | 880232.03 | 0.215170E+09 | 0.328686E+09 | 0.00 | 0.42 |
December | 0.214973E+10 | 0.00 | 0.00 | 183691.55 | 507419.61 | 0.408568E+09 | 87640164.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.193838E+11 | 0.107078E+10 | 10778.97 | 31352540.08 | 0.104093E+09 | 0.183581E+10 | 0.113221E+11 | 2179.74 | 0.57 |
Minimum of Months | 0.590365E+09 | 0.00 | 0.00 | 183691.55 | 0.00 | 0.00 | 87640164.00 | 0.00 | 0.40 |
Maximum of Months | 0.266931E+10 | 0.384304E+09 | 10778.97 | 6802674.68 | 34906694.08 | 0.536868E+09 | 0.253662E+10 | 2179.74 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108747E+10 | 1095355.20 | 7647.51 | 1592893.49 | 2962306.56 | 0.169509E+09 | 0.772812E+09 | 686.49 | 0.46 |
February | 0.102638E+10 | 449593.62 | 0.00 | 2036759.92 | 6073.28 | 0.115930E+09 | 0.107416E+10 | 0.00 | 0.52 |
March | 0.118440E+10 | 0.00 | 0.00 | 3119014.00 | 2261321.48 | 0.107679E+09 | 0.155934E+10 | 0.00 | 0.61 |
April | 0.701915E+09 | 393899.73 | 0.00 | 6732306.39 | 2403515.84 | 9078212.14 | 0.304290E+10 | 0.00 | 1.03 |
May | 0.716520E+09 | 2859506.86 | 0.00 | 6561460.11 | 0.00 | 586106.36 | 0.303675E+10 | 0.00 | 1.01 |
June | 0.440143E+09 | 13424483.02 | 0.00 | 8925411.90 | 0.00 | 0.00 | 0.296220E+10 | 0.00 | 1.32 |
July | 0.240533E+09 | 0.343578E+09 | 0.00 | 8798474.30 | 3210027.79 | 0.00 | 0.197301E+10 | 0.00 | 1.48 |
August | 0.224863E+09 | 0.524183E+09 | 0.00 | 7485350.38 | 3742656.74 | 0.00 | 0.151478E+10 | 0.00 | 1.54 |
September | 0.539978E+09 | 0.102102E+09 | 0.00 | 6208993.19 | 5032120.89 | 0.00 | 0.188563E+10 | 0.00 | 1.04 |
October | 0.555862E+09 | 0.254567E+09 | 0.00 | 3639219.81 | 16134959.61 | 10424228.30 | 0.110417E+10 | 0.00 | 0.77 |
November | 0.946105E+09 | 11348.57 | 0.00 | 2337022.25 | 554758.45 | 44431274.73 | 0.115792E+10 | 0.00 | 0.52 |
December | 0.113303E+10 | 123240.85 | 0.00 | 1541365.76 | 275765.24 | 0.123479E+09 | 0.544409E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.879720E+10 | 0.124279E+10 | 7647.51 | 58978271.51 | 36583505.90 | 0.581116E+09 | 0.206281E+11 | 686.49 | 0.90 |
Minimum of Months | 0.224863E+09 | 0.00 | 0.00 | 1541365.76 | 0.00 | 0.00 | 0.544409E+09 | 0.00 | 0.44 |
Maximum of Months | 0.118440E+10 | 0.524183E+09 | 7647.51 | 8925411.90 | 16134959.61 | 0.169509E+09 | 0.304290E+10 | 686.49 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103728E+10 | 36435672.22 | 0.00 | 14612686.02 | 22782.72 | 0.165142E+09 | 0.586004E+10 | 0.00 | 1.14 |
February | 0.119091E+10 | 2264571.58 | 0.00 | 9759242.65 | 9467.49 | 0.127898E+09 | 0.454239E+10 | 0.00 | 0.96 |
March | 0.165324E+10 | 4823899.53 | 0.00 | 7827046.81 | 414729.20 | 0.182114E+09 | 0.407730E+10 | 0.00 | 0.85 |
April | 0.125151E+10 | 1382319.96 | 0.00 | 8629273.98 | 3158859.00 | 28844580.28 | 0.391843E+10 | 0.00 | 0.93 |
May | 0.151113E+10 | 2668454.10 | 0.00 | 5684673.14 | 0.00 | 12486108.52 | 0.271270E+10 | 0.00 | 0.73 |
June | 0.102966E+10 | 16250868.30 | 0.00 | 6992978.49 | 0.00 | 0.00 | 0.249619E+10 | 0.00 | 0.85 |
July | 0.661075E+09 | 0.388140E+09 | 0.00 | 5859223.11 | 17676779.53 | 0.00 | 0.137167E+10 | 0.00 | 0.92 |
August | 0.431694E+09 | 0.605486E+09 | 0.00 | 7748961.18 | 20193833.05 | 0.00 | 0.155087E+10 | 0.00 | 1.18 |
September | 0.642770E+09 | 0.216786E+09 | 0.00 | 12223826.18 | 6242891.36 | 0.00 | 0.358275E+10 | 0.00 | 1.24 |
October | 0.649715E+09 | 0.694488E+09 | 0.00 | 12315647.10 | 4590635.49 | 0.00 | 0.273028E+10 | 0.00 | 1.17 |
November | 0.970198E+09 | 2034992.70 | 0.00 | 14656167.85 | 34452.68 | 29554578.24 | 0.599016E+10 | 0.00 | 1.20 |
December | 0.102154E+10 | 3063852.69 | 0.00 | 16901324.16 | 0.00 | 97087982.68 | 0.503542E+10 | 0.00 | 1.15 |
Annual Sum or Average | 0.120507E+11 | 0.197382E+10 | 0.00 | 0.123211E+09 | 52344430.53 | 0.643128E+09 | 0.438682E+11 | 0.00 | 1.03 |
Minimum of Months | 0.431694E+09 | 1382319.96 | 0.00 | 5684673.14 | 0.00 | 0.00 | 0.137167E+10 | 0.00 | 0.73 |
Maximum of Months | 0.165324E+10 | 0.694488E+09 | 0.00 | 16901324.16 | 20193833.05 | 0.182114E+09 | 0.599016E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112804E+10 | 7458377.05 | 0.00 | 2362294.71 | 1144327.39 | 0.188887E+09 | 0.115386E+10 | 0.00 | 0.56 |
February | 0.107802E+10 | 726036.15 | 0.00 | 2639621.65 | 6078.14 | 82823122.92 | 0.154804E+10 | 0.00 | 0.64 |
March | 0.115766E+10 | 0.00 | 0.00 | 3890600.39 | 2263131.33 | 91455185.22 | 0.239120E+10 | 0.00 | 0.75 |
April | 0.548879E+09 | 2595240.71 | 0.00 | 9213614.01 | 1523277.87 | 12046905.03 | 0.385861E+10 | 0.00 | 1.20 |
May | 0.557311E+09 | 1530023.49 | 0.00 | 8821482.77 | 0.00 | 933985.43 | 0.390883E+10 | 0.00 | 1.19 |
June | 0.294122E+09 | 11255126.33 | 0.00 | 11040553.42 | 0.00 | 0.00 | 0.394194E+10 | 0.00 | 1.57 |
July | 0.136409E+09 | 0.446171E+09 | 0.00 | 12101231.13 | 10479405.61 | 0.00 | 0.229777E+10 | 0.00 | 1.64 |
August | 0.109733E+09 | 0.484230E+09 | 0.00 | 9928066.47 | 9774055.74 | 0.00 | 0.179341E+10 | 0.00 | 1.70 |
September | 0.336760E+09 | 0.115308E+09 | 0.00 | 8579223.84 | 1398222.68 | 0.00 | 0.265481E+10 | 0.00 | 1.25 |
October | 0.504234E+09 | 0.276173E+09 | 0.00 | 4814191.28 | 11573475.94 | 0.00 | 0.126930E+10 | 0.00 | 0.88 |
November | 0.102071E+10 | 75017.72 | 0.00 | 3497001.86 | 534112.52 | 34512231.67 | 0.175327E+10 | 0.00 | 0.70 |
December | 0.108072E+10 | 120970.97 | 0.00 | 2634060.14 | 277381.59 | 0.124283E+09 | 0.102459E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.795259E+10 | 0.134564E+10 | 0.00 | 79521941.68 | 38973468.80 | 0.534941E+09 | 0.275956E+11 | 0.00 | 1.06 |
Minimum of Months | 0.109733E+09 | 0.00 | 0.00 | 2362294.71 | 0.00 | 0.00 | 0.102459E+10 | 0.00 | 0.56 |
Maximum of Months | 0.115766E+10 | 0.484230E+09 | 0.00 | 12101231.13 | 11573475.94 | 0.188887E+09 | 0.394194E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3830564.41 | 0.00 | 0.00 | 0.331723E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7773281.70 | 0.00 | 0.00 | 0.290962E+09 | 0.00 | 0.29 |
March | 0.00 | 10736.88 | 0.00 | 14180353.80 | 0.00 | 0.00 | 0.338627E+09 | 0.00 | 0.31 |
April | 0.00 | 163568.98 | 0.00 | 17501309.87 | 0.00 | 0.00 | 0.199408E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3971887.57 | 0.00 | 0.00 | 0.244491E+09 | 0.00 | 0.29 |
June | 0.00 | 7474887.22 | 0.00 | 7665936.84 | 0.00 | 0.00 | 0.118650E+09 | 0.00 | 0.30 |
July | 0.00 | 58934584.22 | 0.00 | 5030817.69 | 0.00 | 0.00 | 26737303.62 | 0.00 | 0.28 |
August | 0.00 | 76200553.98 | 0.00 | 5460397.65 | 0.00 | 0.00 | 19300053.02 | 0.00 | 0.31 |
September | 0.00 | 13410893.95 | 0.00 | 2990358.82 | 0.00 | 0.00 | 94801139.08 | 0.00 | 0.29 |
October | 0.00 | 22478127.86 | 0.00 | 6613503.89 | 0.00 | 0.00 | 0.147217E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12957905.70 | 0.00 | 0.00 | 0.275339E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18243375.85 | 0.00 | 0.00 | 0.309333E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.178673E+09 | 0.00 | 0.106220E+09 | 0.00 | 0.00 | 0.239659E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2990358.82 | 0.00 | 0.00 | 19300053.02 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 76200553.98 | 0.00 | 18243375.85 | 0.00 | 0.00 | 0.338627E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 29093784.35 | 0.00 | 0.00 | 0.333757E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 68486200.66 | 0.00 | 0.00 | 0.292402E+10 | 0.00 | 0.29 |
March | 0.00 | 82605.27 | 0.00 | 0.129307E+09 | 0.00 | 0.00 | 0.339901E+10 | 0.00 | 0.31 |
April | 0.00 | 1618655.31 | 0.00 | 0.164420E+09 | 0.00 | 0.00 | 0.200354E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 34608637.03 | 0.00 | 0.00 | 0.246795E+10 | 0.00 | 0.29 |
June | 0.00 | 72626420.79 | 0.00 | 71447978.79 | 0.00 | 0.00 | 0.119866E+10 | 0.00 | 0.30 |
July | 0.00 | 0.584966E+09 | 0.00 | 47631172.59 | 0.00 | 0.00 | 0.271289E+09 | 0.00 | 0.28 |
August | 0.00 | 0.758960E+09 | 0.00 | 52080839.04 | 0.00 | 0.00 | 0.195662E+09 | 0.00 | 0.31 |
September | 0.00 | 0.125912E+09 | 0.00 | 26794319.00 | 0.00 | 0.00 | 0.971588E+09 | 0.00 | 0.29 |
October | 0.00 | 0.221198E+09 | 0.00 | 60573366.99 | 0.00 | 0.00 | 0.147985E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.118793E+09 | 0.00 | 0.00 | 0.276369E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.168244E+09 | 0.00 | 0.00 | 0.310217E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.176536E+10 | 0.00 | 0.971480E+09 | 0.00 | 0.00 | 0.241150E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 26794319.00 | 0.00 | 0.00 | 0.195662E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.758960E+09 | 0.00 | 0.168244E+09 | 0.00 | 0.00 | 0.339901E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37990091.96 | 0.00 | 0.00 | 2073510.77 | 0.00 | 0.00 | 0.298969E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6167523.77 | 0.00 | 0.00 | 0.293879E+09 | 0.00 | 0.29 |
March | 0.00 | 8637.71 | 0.00 | 12250047.54 | 0.00 | 0.00 | 0.340968E+09 | 0.00 | 0.31 |
April | 0.00 | 161938.85 | 0.00 | 16171885.02 | 0.00 | 0.00 | 0.200770E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3223253.07 | 0.00 | 0.00 | 0.247785E+09 | 0.00 | 0.29 |
June | 0.00 | 7321759.38 | 0.00 | 7069479.55 | 0.00 | 0.00 | 0.120044E+09 | 0.00 | 0.30 |
July | 0.00 | 58551695.69 | 0.00 | 4742656.31 | 0.00 | 0.00 | 27175099.53 | 0.00 | 0.28 |
August | 0.00 | 75879410.83 | 0.00 | 5174788.90 | 0.00 | 0.00 | 19652121.37 | 0.00 | 0.31 |
September | 0.00 | 12486413.86 | 0.00 | 2545934.41 | 0.00 | 0.00 | 97728625.67 | 0.00 | 0.29 |
October | 0.00 | 22097219.96 | 0.00 | 5771910.59 | 0.00 | 0.00 | 0.148475E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11258068.98 | 0.00 | 0.00 | 0.277280E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16006093.60 | 0.00 | 0.00 | 0.311079E+09 | 0.00 | 0.28 |
Annual Sum or Average | 37990091.96 | 0.176507E+09 | 0.00 | 92455152.50 | 0.00 | 0.00 | 0.238380E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2073510.77 | 0.00 | 0.00 | 19652121.37 | 0.00 | 0.28 |
Maximum of Months | 37990091.96 | 75879410.83 | 0.00 | 16171885.02 | 0.00 | 0.00 | 0.340968E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.528643E+09 | 0.00 | 0.00 | 0.389559E+12 | 0.00 | 16.76 |
February | 0.00 | 0.00 | 0.00 | 0.925932E+09 | 0.00 | 0.00 | 0.567285E+12 | 0.00 | 26.58 |
March | 0.00 | 0.00 | 0.00 | 0.152592E+10 | 0.00 | 0.00 | 0.809348E+12 | 0.00 | 34.22 |
April | 0.00 | 49403874.67 | 0.00 | 0.229744E+10 | 0.00 | 0.00 | 0.697998E+12 | 0.00 | 41.59 |
May | 0.00 | 0.00 | 0.00 | 0.520420E+09 | 0.00 | 0.00 | 0.339034E+12 | 0.00 | 19.51 |
June | 0.00 | 0.103084E+09 | 0.00 | 0.102608E+10 | 0.00 | 0.00 | 0.478373E+12 | 0.00 | 35.21 |
July | 0.00 | 0.242069E+11 | 0.00 | 0.164166E+10 | 0.00 | 0.00 | 0.358871E+12 | 0.00 | 41.77 |
August | 0.00 | 0.200738E+11 | 0.00 | 0.166616E+10 | 0.00 | 0.00 | 0.149742E+12 | 0.00 | 42.12 |
September | 0.00 | 0.468279E+09 | 0.00 | 0.495845E+09 | 0.00 | 0.00 | 0.311552E+12 | 0.00 | 24.18 |
October | 0.00 | 0.134103E+10 | 0.00 | 0.106191E+10 | 0.00 | 0.00 | 0.497082E+12 | 0.00 | 34.04 |
November | 0.00 | 0.00 | 0.00 | 0.160437E+10 | 0.00 | 0.00 | 0.785280E+12 | 0.00 | 36.77 |
December | 0.00 | 0.00 | 0.00 | 0.224699E+10 | 0.00 | 0.00 | 0.978273E+12 | 0.00 | 39.54 |
Annual Sum or Average | 0.00 | 0.462425E+11 | 0.00 | 0.155414E+11 | 0.00 | 0.00 | 0.636240E+13 | 0.00 | 32.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.495845E+09 | 0.00 | 0.00 | 0.149742E+12 | 0.00 | 16.76 |
Maximum of Months | 0.00 | 0.242069E+11 | 0.00 | 0.229744E+10 | 0.00 | 0.00 | 0.978273E+12 | 0.00 | 42.12 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.313912E+12 | 0.920301E+10 | 0.00 | 0.216836E+13 | 0.379705E+12 |
February | 0.387347E+12 | 0.109047E+11 | 0.00 | 0.229531E+13 | 0.324717E+12 |
March | 0.540510E+12 | 0.112618E+11 | 0.00 | 0.267938E+13 | 0.483484E+12 |
April | 0.687389E+12 | 0.680398E+10 | 0.00 | 0.246040E+13 | 0.112049E+13 |
May | 0.724259E+12 | 0.815631E+10 | 0.00 | 0.216630E+13 | 0.449897E+12 |
June | 0.709789E+12 | 0.429020E+10 | 0.00 | 0.203805E+13 | 0.900805E+12 |
July | 0.759983E+12 | 0.222773E+10 | 0.00 | 0.141454E+13 | 0.198818E+13 |
August | 0.707004E+12 | 0.240204E+10 | 0.00 | 0.100574E+13 | 0.281433E+13 |
September | 0.549437E+12 | 0.360316E+10 | 0.00 | 0.172586E+13 | 0.862904E+12 |
October | 0.386722E+12 | 0.586139E+10 | 0.00 | 0.187880E+13 | 0.126029E+13 |
November | 0.343770E+12 | 0.918742E+10 | 0.00 | 0.266912E+13 | 0.693406E+12 |
December | 0.283187E+12 | 0.101814E+11 | 0.00 | 0.287839E+13 | 0.992623E+12 |
Annual Sum or Average | 0.639331E+13 | 0.840831E+11 | 0.00 | 0.253802E+14 | 0.122708E+14 |
Minimum of Months | 0.283187E+12 | 0.222773E+10 | 0.00 | 0.100574E+13 | 0.324717E+12 |