Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:56:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29083.75 | 627.88 | 627.88 |
Net Site Energy | 28629.22 | 618.07 | 618.07 |
Total Source Energy | 83131.55 | 1794.71 | 1794.71 |
Net Source Energy | 81692.06 | 1763.63 | 1763.63 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3488.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1717.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 268.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2505.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 302.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 385.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3076.66 |
Humidification | 2431.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.65 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 821.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 24774.25 | 4309.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6261.47 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3488.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1717.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 268.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2505.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 302.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 385.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3076.66 |
Humidification | General | 2431.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.65 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 821.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3488.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1717.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 268.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2505.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 302.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 385.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3076.66 |
Humidification | Unassigned | 2431.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.65 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 821.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.14 | 93.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 534.85 | 93.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.14 | 93.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 534.85 | 93.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 475.569 | 1.92 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -21.04 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 454.529 | 1.83 |
Electricity Coming From Utility | 24319.722 | 98.17 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 24319.722 | 98.17 |
Total On-Site and Utility Electric Sources | 24774.251 | 100.00 |
Total Electricity End Uses | 24774.251 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6261.47 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6261.47 | 100.00 |
Total Water End Uses | 6261.47 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 123.67 |
Time Setpoint Not Met During Occupied Cooling | 380.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5924.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:50 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 25-JUL-11:00 |
Heating | 0.00 | 2364675.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 377258.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 310123.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41837.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 44969.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 32185.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1851136.76 | 2396861.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2364675.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 377258.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 310123.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 41837.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 44969.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 32185.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3781.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5439.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 850.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7933.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 956.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1220.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7701.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 890.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 78460.05 | 4671.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 171.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 26.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1693.86 | 100.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 171.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 26.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1693.86 | 100.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.52 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.558535 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.37 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.546556 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.33 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.98 | 0.318192 | 0.270000 | 1.61 | 0.848511 | 0.500000 | 0.001197 | 0.000170 | 1.61 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.92 | 0.340147 | 0.289000 | 16.16 | 0.907059 | 0.500000 | 0.001120 | 0.003992 | 16.16 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.54 | 0.343383 | 0.292000 | 1.62 | 0.915689 | 0.500000 | 0.001110 | 0.000944 | 3.67 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.04 | 0.229295 | 0.195000 | 0.203101 | 0.611453 | 0.500000 | 0.001662 | 0.000164 | 0.639194 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.47 | 0.104616 | 0.089000 | 0.130932 | 0.300000 | 0.500000 | 0.003642 | 0.000113 | 0.439281 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.80 | 0.132686 | 0.113000 | 0.203393 | 0.353828 | 0.500000 | 0.002871 | 0.000182 | 0.708105 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.82 | 0.084428 | 0.072000 | 0.131249 | 0.300000 | 0.500000 | 0.004513 | 0.000092 | 0.360073 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.92 | 0.240659 | 0.205000 | 2.03 | 0.641757 | 0.500000 | 0.001583 | 0.002417 | 9.43 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 15.82 | 0.300000 | 0.500000 | 0.003916 | 0.001605 | 6.26 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.49 | 0.129178 | 0.110000 | 2.03 | 0.344474 | 0.500000 | 0.002949 | 0.002447 | 9.55 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 17.08 | 0.090124 | 0.077000 | 1.31 | 0.300000 | 0.500000 | 0.004227 | 0.001570 | 6.12 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.21 | 0.198045 | 0.179000 | 0.215854 | 0.528120 | 0.500000 | 0.001924 | 0.000309 | 1.21 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.58 | 0.097190 | 0.083000 | 0.131435 | 0.300000 | 0.500000 | 0.003920 | 0.000204 | 0.795652 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.99 | 0.120205 | 0.102000 | 0.202656 | 0.320546 | 0.500000 | 0.003170 | 0.000312 | 1.22 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.80 | 0.085308 | 0.073000 | 0.131700 | 0.300000 | 0.500000 | 0.004466 | 0.000203 | 0.790583 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19381.83 | 0.000170 | 405.25 |
CORE_MID VAV BOX REHEAT COIL | 456310.78 | 0.003992 | 11835.47 |
CORE_TOP VAV BOX REHEAT COIL | 107858.01 | 0.000944 | 2846.06 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18744.58 | 0.000164 | 494.38 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12880.36 | 0.000113 | 339.69 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20761.64 | 0.000182 | 547.53 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10562.34 | 0.000092 | 278.61 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 276330.01 | 0.002417 | 7285.50 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 183409.24 | 0.001605 | 4835.53 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 279727.61 | 0.002447 | 7375.03 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 179447.43 | 0.001570 | 4731.13 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35325.93 | 0.000309 | 931.25 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23307.55 | 0.000204 | 614.42 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 35690.84 | 0.000312 | 940.86 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23159.07 | 0.000203 | 610.50 |
VAV_BOT WITH REHEAT HEATING COIL | 79868.24 | 0.000699 | 1254.06 |
VAV_MID WITH REHEAT HEATING COIL | 823876.98 | 0.007208 | 12741.50 |
VAV_TOP WITH REHEAT HEATING COIL | 79632.98 | 0.000697 | 1260.99 |
CAV_BAS HEATING COIL | 268531.98 | 0.002349 | 5694.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.06 | 2.28 | 12.11 | 3.22 | 10.05 | 10.05 | 0.300000 | 0.320912 | 10.05 |
VAV_MID WITH REHEAT | 58.61 | 22.86 | 117.23 | 46.55 | 92.45 | 92.45 | 0.300000 | 0.503474 | 92.45 |
VAV_TOP WITH REHEAT | 6.06 | 2.30 | 12.12 | 7.68 | 10.77 | 10.77 | 0.300000 | 0.713331 | 10.77 |
CAV_BAS | 5.52 | 5.52 | 5.52 | 5.52 | 5.52 | 5.52 | 1.00 | 1.00 | 5.52 |
AIRLOOP DATACENTER BASEMENT | 24.33 | 24.33 | 24.33 | 24.33 | 24.33 | 24.33 | 1.00 | 0.999993 | 24.33 |
AIRLOOP DATACENTER BOT | 0.558535 | 0.558535 | 0.558535 | 0.558535 | 0.558535 | 0.558535 | 1.00 | 1.00 | 0.558535 |
AIRLOOP DATACENTER MID | 5.37 | 5.37 | 5.37 | 5.37 | 5.37 | 5.37 | 1.00 | 1.00 | 5.37 |
AIRLOOP DATACENTER TOP | 0.546556 | 0.546556 | 0.546556 | 0.546556 | 0.546556 | 0.546556 | 1.00 | 1.00 | 0.546556 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.05 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 92.45 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.77 | |
CAV_BAS_OA_CONTROLLER | 5.52 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.33 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.558535 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.37 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.546556 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.90 | 6.67 | 10.68 | 0.007137 | 0.007000 | 167595.86 | 0.004793 | 10.05 |
VAV_MID WITH REHEAT COOLING COIL | 26.07 | 6.67 | 10.67 | 0.007133 | 0.007000 | 1558666.34 | 0.044578 | 92.45 |
VAV_TOP WITH REHEAT COOLING COIL | 25.78 | 6.67 | 10.68 | 0.007121 | 0.007000 | 177833.62 | 0.005086 | 10.77 |
CAV_BAS COOLING COIL | 26.34 | 6.67 | 11.22 | 0.007265 | 0.007000 | 93360.09 | 0.002670 | 5.52 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.05 |
VAV_MID WITH REHEAT FAN | 92.45 |
VAV_TOP WITH REHEAT FAN | 10.77 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004793 | 0.000099 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000699 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.044578 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007208 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005086 | 0.000094 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000697 | |
CAV_BAS_COOLC_CONTROLLER | 0.002670 | 0.000178 |
CAV_BAS_HEATC_CONTROLLER | 0.002349 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.52 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.33 | 462527.06 | 260292.55 | 0.011327 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.558535 | 10314.97 | 5866.68 | 0.000253 |
AIRLOOP DATACENTER MID COOLING COIL | 5.37 | 99179.97 | 56398.66 | 0.002429 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.546556 | 10095.41 | 5741.19 | 0.000247 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.33 | 24.33 | 24.33 | 24.33 | 462527.06 | 462527.06 | 24207.99 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.558535 | 0.558535 | 0.558535 | 0.558535 | 10314.97 | 10314.97 | 1118.31 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.37 | 5.37 | 5.37 | 5.37 | 99179.97 | 99179.97 | 11183.09 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.546556 | 0.546556 | 0.546556 | 0.546556 | 10095.41 | 10095.41 | 1118.31 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.33 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.558535 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.37 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.546556 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.33 | 462527.06 | 0.011327 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.558535 | 10314.97 | 0.000253 |
AIRLOOP DATACENTER MID HEATING COIL | 5.37 | 99179.97 | 0.002429 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.546556 | 10095.41 | 0.000247 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 24207.99 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.31 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.09 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.31 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000189 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.057127 | 9234.74 | |
HEATSYS1 PUMP | 0.025675 | 7655.62 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.057127 | 6.86 |
HEATSYS1 | 0.025675 | 3.08 |
COOLSYS1_SUPPLY | 0.057127 | 6.86 |
SINGLE WATER PLANT LOOP | 0.014256 | 1.71 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.057127 | 0.057127 | 239790.62 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2934807.38 | 2934807.38 | 0.025675 |
CENTRAL BOILER | 587225.73 | 574567.17 | 0.014256 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.028563 | 3196.76 |
COOLSYS1 CHILLER2 PUMP | 0.028563 | 3196.76 |
PLANT CIRC PUMP | 0.014256 | 3600.00 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.057127 | 0.028761 | 1006740.80 | 1012868.40 | 0.050964 |
COOLSYS1 CHILLER2 | 0.057127 | 0.028761 | 1006740.80 | 1012868.40 | 0.050964 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014256 | 139666.47 | 55968.34 | 69833.23 | 7004.20 | 21069.01 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.101928 | 12.23 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.101928 | 24985.25 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 42.46 | 1203257.44 | 8.49 | 150407.18 |
TOWERWATERSYS COOLTOWER 2 | 42.46 | 1203257.44 | 8.49 | 150407.18 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.052062 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.7665 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.7365 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 0.8503 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.137 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.190 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.44021978E-14 | 0.26910102E-16 | -0.15734890E-09 | 0.82303633E-16 |
51 | 8 | 0.22944372E-07 | 0.10402404E-12 | 0.38894080E-03 | -0.26088539E-09 |
52 | 7 | -0.12573911E-01 | 0.53403908E-08 | -0.23564254E-01 | 0.14296995E-03 |
53 | 6 | 0.41438068 | 0.18524112E-05 | 0.47977456 | -0.48542082E-02 |
54 | 5 | -5.2786839 | 0.68992212E-04 | -4.5002426 | 0.64276505E-01 |
55 | 4 | 33.392604 | 0.56309435E-03 | 21.670815 | -0.42729772 |
56 | 3 | -112.05539 | 0.12247409E-02 | -56.079643 | 1.5271740 |
57 | 2 | 197.95292 | 0.68767709E-03 | 78.292830 | -2.9137667 |
58 | 1 | -171.46805 | 0.73289974E-04 | -55.376463 | 2.7509071 |
59 | 0 | 57.057407 | 0.41637142E-06 | 15.538725 | |
60 | 9 | -0.30638523E-14 | 0.28130415E-16 | -0.15873428E-09 | 0.70776160E-16 |
61 | 8 | 0.23140014E-07 | 0.10007808E-12 | 0.39096019E-03 | -0.26310989E-09 |
62 | 7 | -0.12634047E-01 | 0.51273238E-08 | -0.23650802E-01 | 0.14365373E-03 |
63 | 6 | 0.41601453 | 0.17770828E-05 | 0.48116310 | -0.48734675E-02 |
64 | 5 | -5.2946262 | 0.66140948E-04 | -4.5108940 | 0.64474185E-01 |
65 | 4 | 33.463109 | 0.53948557E-03 | 21.712419 | -0.42823385 |
66 | 3 | -112.20536 | 0.11727349E-02 | -56.161880 | 1.5293408 |
67 | 2 | 198.10151 | 0.65814741E-03 | 78.368305 | -2.9161265 |
68 | 1 | -171.52292 | 0.70110241E-04 | -55.398508 | 2.7518688 |
69 | 0 | 57.057407 | 0.39813911E-06 | 15.535164 | |
70 | 9 | -0.27193088E-14 | 0.32918029E-16 | -0.15343093E-09 | 0.41430680E-16 |
71 | 8 | 0.22396221E-07 | 0.11497495E-12 | 0.38325188E-03 | -0.25465275E-09 |
72 | 7 | -0.12404391E-01 | 0.59358465E-08 | -0.23320250E-01 | 0.14104245E-03 |
73 | 6 | 0.40977485 | 0.20636698E-05 | 0.47585773 | -0.47999164E-02 |
74 | 5 | -5.2337405 | 0.77011785E-04 | -4.4701852 | 0.63719223E-01 |
75 | 4 | 33.193833 | 0.62966818E-03 | 21.553386 | -0.42465855 |
76 | 3 | -111.63255 | 0.13717202E-02 | -55.847513 | 1.5210650 |
77 | 2 | 197.53393 | 0.77129909E-03 | 78.079831 | -2.9071130 |
78 | 1 | -171.31331 | 0.82309882E-04 | -55.314336 | 2.7481952 |
79 | 0 | 57.057407 | 0.46839615E-06 | 15.548831 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3093E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3116E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1817E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1836E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7111E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7125E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6293E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6301E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3606E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5081E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2248E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3532E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7469E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8525E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6510E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7062E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1729 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.4524E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1983 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1097 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1134 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6933E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7533E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6532E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3722E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5706E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2378E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4231E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7565E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8895E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6516E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7078E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3091E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3118E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1815E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1838E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7110E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7127E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6292E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6300E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5567E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0294E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4478E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0025E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6481E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7972E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4956E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5336E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.6012E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6946E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4278E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5140E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9759E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9143E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9489E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8512E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4067E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5210E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2495E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3336E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6024E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6364E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4957E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5342E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8902E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8925E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4496E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4515E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1436E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1450E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6294E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6302E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9423E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0738E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4934E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6004E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1799E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2611E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6516E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7079E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7816E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5253E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6801E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9208E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2854E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2743E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7533E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6527E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9396E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0746E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4892E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5944E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1723E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2373E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6511E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7062E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8900E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8923E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4494E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4512E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1434E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1446E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6293E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6301E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4291E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5502E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9909E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0787E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9235E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9535E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4958E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5343E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8894E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9861E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2362E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6040E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7206E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4002E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9489E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8512E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5282E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8138E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1232E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4337E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9646E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0909E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4955E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5335E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1776 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1307 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1988 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1504 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1275 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9340E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8206E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8791E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.9955E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.2808E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.8065E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.0828E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2319E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2531E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9696E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9121E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8957E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9199E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6504E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0956E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2200E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2855E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8206E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8786E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0602E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.3050E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3274E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8275E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8265E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.5743E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9696E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9121E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1777 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1310 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1988 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1506 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1277 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9505E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8330E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8854E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.0015E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.2891E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.8135E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.0912E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2443E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2623E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9821E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9184E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8961E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9244E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6511E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0991E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2267E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2898E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8331E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8850E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0636E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.3111E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3312E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8330E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8368E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.5816E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9821E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9184E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 66817.73037 | 66817.73037 | 5.51563 | 5.51563 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72413.70203 | 72413.70203 | 5.97767 | 5.97767 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 5169.74448 | 5169.74448 | 0.25121 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 677584.72373 | 677584.72373 | 55.91829 | 55.91829 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 314002.87553 | 314002.87553 | 15.18748 | 15.18748 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 66493.05153 | 66493.05153 | 5.53913 | 5.53913 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 75504.15896 | 75504.15896 | 3.67408 | 3.67408 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12503.26454 | 12503.26454 | 1.04154 | 1.04154 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13119.16255 | 13119.16255 | 0.63919 | 0.63919 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17660.58998 | 17660.58998 | 1.47114 | 1.47114 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.29334E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9014.19268 | 9014.19268 | 0.43928 | 0.43928 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 21607.59097 | 21607.59097 | 1.79994 | 1.79994 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.00000 | 6.30621E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14529.25117 | 14529.25117 | 0.70810 | 0.70810 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21883.44285 | 21883.44285 | 1.82290 | 1.82290 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7394.10486 | 7394.10486 | 0.36007 | 0.36007 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 119129.95179 | 119129.95179 | 9.92361 | 9.92361 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 193362.72547 | 193362.72547 | 9.43003 | 9.43003 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 189907.60461 | 189907.60461 | 15.81929 | 15.81929 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 128339.16960 | 128339.16960 | 6.25929 | 6.25929 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 221945.79730 | 221945.79730 | 18.48815 | 18.48815 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 195738.18203 | 195738.18203 | 9.54613 | 9.54613 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 205006.04368 | 205006.04368 | 17.07699 | 17.07699 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 30.09333 | 6.30170E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 125568.99734 | 125568.99734 | 6.12395 | 6.12395 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13641.64799 | 13641.64799 | 1.13635 | 1.13635 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24716.48568 | 24716.48568 | 1.20589 | 1.20589 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 19010.29948 | 19010.29948 | 1.58355 | 1.58355 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 16307.48848 | 16307.48848 | 0.79565 | 0.79565 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 23851.44917 | 23851.44917 | 1.98682 | 1.98682 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24971.62639 | 24971.62639 | 1.21836 | 1.21836 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 21658.10135 | 21658.10135 | 1.80411 | 1.80411 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16203.63323 | 16203.63323 | 0.79058 | 0.79058 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8500.79787 | 8500.79787 | 0.55853 | 0.55853 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81713.06684 | 81713.06684 | 5.36889 | 5.36889 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8318.47083 | 8318.47083 | 0.54656 | 0.54656 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370322.78318 | 370322.78318 | 24.33127 | 24.33127 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 139224.18 | 10.04785 | 10.04785 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 86432.15 | 3.22448 | 3.22448 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1296647.90 | 92.45133 | 92.45133 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 861179.62 | 46.54689 | 46.54689 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 147397.62 | 10.77279 | 10.77279 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 86731.61 | 7.68457 | 7.68457 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
7 | CAV_BAS | Cooling | Sensible | 68940.14 | 5.51563 | 5.51563 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85856.97 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367477.48 | 24.33144 | 24.33144 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24207.99 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8380.39 | 0.55853 | 0.55853 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80551.08 | 5.36889 | 5.36889 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.09 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8200.39 | 0.54656 | 0.54656 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.51563 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.97767 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31819 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61397 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84851 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19739E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69561E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61397 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19381.83305 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69561E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 405.24885 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.91829 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34015 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.16039 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90706 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12010E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.99201E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.16039 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 456310.77887 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.99201E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11835.47346 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.53913 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34338 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61742 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91569 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10955E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.43589E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.67408 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 107858.01419 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.43589E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2846.06487 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04154 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22929 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19500 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20310 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61145 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66162E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63986E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63919 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18744.58147 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63986E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 494.37577 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47114 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10462 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.90000E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13093 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64189E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12683E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43928 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12880.35506 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12683E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 339.69007 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79994 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13269 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20339 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35383 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87145E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.81632E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70810 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20761.63763 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81632E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 547.52883 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82290 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.44285E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.20000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13125 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.51270E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.24040E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36007 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10562.34068 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.24040E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 278.61176 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.92361 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24066 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03434 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64176 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58315E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41746E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.43003 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 276330.00758 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41746E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7285.50345 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.81929 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.91615E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60454E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.25929 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 183409.23709 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60454E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4835.53110 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.48815 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12918 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03370 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34447 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94942E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.44718E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.54613 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 279727.60808 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44718E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7375.02849 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.07699 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.01242E-002 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.70000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31493 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22750E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.56988E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.12395 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 179447.43322 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56988E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4731.12687 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20589 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19804 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17900 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21585 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52812 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92381E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.09047E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20589 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35325.92563 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09047E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 931.24948 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58355 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.71899E-002 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.30000E-002 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13143 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92016E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03905E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79565 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23307.55388 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03905E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 614.41753 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98682 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12020 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20266 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32055 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16959E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.12239E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21836 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35690.83568 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12239E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 940.86478 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80411 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.53080E-002 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.30000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13170 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.46617E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.02606E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79058 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23159.06653 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02606E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 610.50332 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55853 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.36889 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.54656 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.33127 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.05660 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28264 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.11319 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.22448 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.04785 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.04785 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32091 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 58.61317 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.85635 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 117.22633 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 46.54689 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 92.45133 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 92.45133 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50347 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.05975 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.29907 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.11950 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.68457 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.77279 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.77279 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.71333 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.51563 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.51563 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.51563 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.51563 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.51563 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.51563 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.33127 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.33127 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.33127 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.33127 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.33144 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.33144 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55853 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55853 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55853 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55853 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55853 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.55853 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.36889 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.36889 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.36889 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.36889 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.36889 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.36889 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.54656 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.54656 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.54656 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.54656 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.54656 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.54656 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.04785 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 92.45133 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.77279 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.51563 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.33144 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.55853 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.36889 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.54656 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.04785 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.89949 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68139 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13666E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 167595.85603 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.79322E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.04785 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 79868.23960 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.98722E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1254.05615 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.04785 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.79322E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.93467E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.98722E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 92.45133 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.06565 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.67006 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13265E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1558666.33572 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.45777E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 92.45133 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 823876.97639 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.20764E-003 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 12741.50036 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 92.45133 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.45777E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.06823E-005 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.20764E-003 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.77279 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.77743 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68133 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.12127E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 177833.61683 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.08602E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.77279 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 79632.97878 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.96664E-004 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1260.99199 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.77279 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.08602E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.36274E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.96664E-004 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.51563 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.34448 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.21891 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.26542E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 93360.08570 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.67009E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.51563 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 268531.97719 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34923E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5694.25432 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.51563 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.67009E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.78343E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.34923E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.33144 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.33144 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 462527.06463 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 260292.55194 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13273E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.33144 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.33144 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.33144 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.33144 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 462527.06463 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 462527.06463 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 24207.99248 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.33144 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.33144 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 462527.06463 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13273E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 24207.99248 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.89463E-004 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55853 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55853 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10314.96783 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5866.67549 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.52613E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.55853 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.55853 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.55853 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.55853 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10314.96783 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10314.96783 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55853 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55853 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10314.96783 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.52613E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.36889 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.36889 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 99179.97227 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 56398.65703 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42891E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.36889 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.36889 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.36889 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.36889 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 99179.97227 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 99179.97227 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.08965 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.36889 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.36889 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 99179.97227 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42891E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.08965 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.54656 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.54656 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10095.41020 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5741.19025 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47236E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.54656 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.54656 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.54656 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.54656 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10095.41020 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10095.41020 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.54656 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.54656 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10095.41020 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47236E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.71270E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9234.74372 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.71270E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.85524 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.71270E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.71270E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 239790.62356 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.56750E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.08100 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.56750E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7655.61884 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2934807.38057 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2934807.38000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.56750E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.71270E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.85524 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.85635E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3196.76225 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.85635E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3196.76225 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.71270E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.87605E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1006740.79626 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1012868.39500 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.09640E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.71270E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.87605E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1006740.79626 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1012868.39500 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.09640E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.42560E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.71072 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.42560E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3599.99753 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.42560E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55968.33713 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21069.00854 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 587225.72511 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 574567.17000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.42560E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10193 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.23135 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10193 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 24985.25146 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 42.46055 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1203257.44475 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.49211 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 150407.18059 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 42.46055 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1203257.44475 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.49211 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 150407.18059 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.20625E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.20625E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18377.39 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 432266.42 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 102225.78 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17764.14 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12206.50 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19675.39 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10010.12 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 261859.49 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 173804.04 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 265078.81 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 170050.04 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33475.16 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22086.39 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33820.93 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21945.69 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 55658.56 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 556778.14 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 56540.38 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 200952.25 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 179332.66 | 127439.74 | 51892.91 | 0.71 | 18447.13 | 187.10 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1658689.34 | 1176160.72 | 482528.62 | 0.71 | 170256.38 | 1726.83 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 191234.74 | 136192.48 | 55042.25 | 0.71 | 19702.02 | 199.83 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 96798.50 | 68777.61 | 28020.90 | 0.71 | 9535.26 | 96.71 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.90 | 23.54 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.90 | 23.54 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.767 | 0.688 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.736 | 0.663 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.850 | 0.754 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2654928900 | 0.2035913838 | Pass | Pass | 6.2248667804 | 19.6486068382 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.4051051774E-002 | 0.1271091525 | Pass | Pass | 7.7210075121E-002 | 0.2658363953 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.3808880974E-002 | 5.8381888871E-002 | Pass | Pass | 3.5800657541E-002 | 0.1855044979 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.5017784082E-002 | 2.5234027376E-002 | Pass | Pass | 0.4910154064 | 0.5054983356 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.4523023740E-002 | 7.3350796480E-002 | Pass | Pass | 7.6529412778E-002 | 0.2649566762 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.5281287105E-002 | 0.1293367465 | Pass | Pass | 7.7784101101E-002 | 0.2681659351 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1874859118 | 0.3191503797 | Pass | Pass | 9.1713879938E-002 | 0.3216812442 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.6446443154E-002 | 9.9808246096E-002 | Pass | Pass | 7.5579324780E-002 | 0.2604475842 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8974110375E-002 | 2.6731074432E-002 | Pass | Pass | 3.4545689063E-002 | 0.1808834262 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.5761300034E-002 | 9.0630328454E-002 | Pass | Pass | 3.5547868296E-002 | 0.1853900800 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1687875119 | 0.1851203995 | Pass | Pass | 4.4286835389E-002 | 0.2220527346 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.1608437644E-002 | 6.7806506383E-002 | Pass | Pass | 3.3109073425E-002 | 0.1701906285 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3344219795 | 0.3472182168 | Pass | Pass | 11.3061470583 | 36.2659231685 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2372695667 | 0.3265106450 | Pass | Pass | 23.0739086744 | 150.1929816102 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2340758029 | 0.2254672762 | Pass | Pass | 0.7990365230 | 1.2434991136 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1979414303 | 0.2541558164 | Pass | Pass | 11.6144222574 | 52.0188858645 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6944219387E-002 | 2.7981164613E-002 | Pass | Pass | 0.1230931890 | 0.4313135259 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.8626645901E-002 | 3.0552690905E-002 | Pass | Pass | 4.7751675315E-002 | 0.2406758714 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.7979424051E-002 | 6.8256378685E-002 | Pass | Pass | 0.4884616952 | 0.4877752654 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5949809443E-006 | 5.6727768809E-006 | Pass | Pass | 4.7028283674E-003 | 4.3377025423E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2867186655E-002 | 1.1989568191E-002 | Pass | Pass | 2.2077249194E-002 | 4.7483988498E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2449870714E-002 | 2.5155579168E-002 | Pass | Pass | 5.3612442129E-003 | 6.2664238234E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8113445884E-005 | 3.1748248068E-005 | Pass | Pass | 6.1800487817E-005 | 1.0646158582E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6619.36 | 311.02 | 0.00 | 28363.66 | 9308.88 | 44602.92 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.688 | 0.767 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.663 | 0.736 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.754 | 0.850 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.342_SHGC_EAST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.342_SHGC_EAST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.342_SHGC_WEST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.342_SHGC_WEST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 1390.74 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.42 | 0.0000 | Y | 7.62 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.20 | 0.0000 | Y | 4.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.06 | 0.0000 | Y | 7.50 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.24 | 0.0000 | Y | 4.87 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.38 | 0.0000 | Y | 76.08 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.18 | 0.0000 | Y | 48.58 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.04 | 0.0000 | Y | 74.93 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.21 | 0.0000 | Y | 48.66 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.38 | 0.0000 | Y | 7.61 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.18 | 0.0000 | Y | 4.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.04 | 0.0000 | Y | 7.49 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.21 | 0.0000 | Y | 4.87 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 541.05 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.11 | 42.11 | 102.38 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.57 | 62.84 | 10.85 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.57 | 48.07 | 155.34 | |
Exterior Lighting Total | 31088.59 | 268.57 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1991303.55 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2934807.38 | 0.85 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1012868.40 | 5.60 | 981346.76 | 4.71 | 6.90 | 23.54 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1012868.40 | 5.60 | 981346.76 | 4.71 | 6.90 | 23.54 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 574567.17 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1203257.44 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1203257.44 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 167595.86 | 179332.66 | 127439.74 | 51892.91 | 0.71 | - | 18447.13 | 187.10 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1558666.34 | 1658689.34 | 1176160.72 | 482528.62 | 0.71 | - | 170256.38 | 1726.83 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 177833.62 | 191234.74 | 136192.48 | 55042.25 | 0.71 | - | 19702.02 | 199.83 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 93360.09 | 96798.50 | 68777.61 | 28020.90 | 0.71 | - | 9535.26 | 96.71 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 462527.06 | 260292.55 | 202234.51 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10314.97 | 5866.68 | 4448.29 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 99179.97 | 56398.66 | 42781.32 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10095.41 | 5741.19 | 4354.22 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19381.83 | 18377.39 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 456310.78 | 432266.42 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 107858.01 | 102225.78 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18744.58 | 17764.14 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12880.36 | 12206.50 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20761.64 | 19675.39 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10562.34 | 10010.12 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 276330.01 | 261859.49 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 183409.24 | 173804.04 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 279727.61 | 265078.81 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 179447.43 | 170050.04 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 35325.93 | 33475.16 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 23307.55 | 22086.39 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35690.84 | 33820.93 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23159.07 | 21945.69 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 79868.24 | 55658.56 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 823876.98 | 556778.14 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 79632.98 | 56540.38 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 268531.98 | 200952.25 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 462527.06 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10314.97 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 99179.97 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10095.41 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 24207.99 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.09 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.05 | 22824.62 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 92.45 | 211133.68 | 2283.73 | 1.00 | 1.07 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.77 | 24471.39 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.52 | 9352.60 | 1695.65 | 1.00 | 1.16 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.33 | 40128.55 | 1649.25 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 625.62 | 1120.11 | 1.00 | 1.56 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.37 | 6013.74 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 612.20 | 1120.11 | 1.00 | 1.57 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.057127 | 9234.74 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.025675 | 7655.62 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028563 | 3196.76 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028563 | 3196.76 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014256 | 3600.00 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.101928 | 24985.25 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 66817.73 | 66817.73 | 24.04 | 5.516 | 5.516 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00752 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 72413.70 | 72413.70 | 29.01 | 5.978 | 5.978 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 677584.72 | 677584.72 | 271.46 | 55.918 | 55.918 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 66493.05 | 66493.05 | 26.64 | 5.539 | 5.539 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00746 | 33.24 | 0.00631 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12503.26 | 12503.26 | 39.89 | 1.042 | 1.042 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00728 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17660.59 | 17660.59 | 87.44 | 1.471 | 1.471 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00713 | 24.60 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 21607.59 | 21607.59 | 68.94 | 1.800 | 1.800 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00716 | 33.00 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21883.44 | 21883.44 | 108.35 | 1.823 | 1.823 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00710 | 30.36 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 119129.95 | 119129.95 | 380.11 | 9.924 | 9.924 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00726 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 189907.60 | 189907.60 | 940.25 | 15.819 | 15.819 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00711 | 25.51 | 0.00629 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 221945.80 | 221945.80 | 708.14 | 18.488 | 18.488 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00714 | 33.27 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 205006.04 | 205006.04 | 1015.01 | 17.077 | 17.077 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00710 | 30.09 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13641.65 | 13641.65 | 43.53 | 1.136 | 1.136 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00721 | 33.24 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 19010.30 | 19010.30 | 94.12 | 1.584 | 1.584 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00710 | 26.41 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23851.45 | 23851.45 | 76.10 | 1.987 | 1.987 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00713 | 33.27 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 21658.10 | 21658.10 | 107.23 | 1.804 | 1.804 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00709 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8500.80 | 8500.80 | 234.81 | 0.559 | 0.559 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81713.07 | 81713.07 | 2257.10 | 5.369 | 5.369 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8318.47 | 8318.47 | 229.77 | 0.547 | 0.547 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370322.78 | 370322.78 | 472.54 | 24.331 | 24.331 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 21.00 | 22.92 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 5169.74 | 5169.74 | 2.07 | 0.251 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 314002.88 | 314002.88 | 125.80 | 15.187 | 15.187 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 75504.16 | 75504.16 | 30.25 | 3.674 | 3.674 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13119.16 | 13119.16 | 41.86 | 0.639 | 0.639 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9014.19 | 9014.19 | 44.63 | 0.439 | 0.439 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14529.25 | 14529.25 | 46.36 | 0.708 | 0.708 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7394.10 | 7394.10 | 36.61 | 0.360 | 0.360 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 193362.73 | 193362.73 | 616.96 | 9.430 | 9.430 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 128339.17 | 128339.17 | 635.42 | 6.259 | 6.259 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 195738.18 | 195738.18 | 624.52 | 9.546 | 9.546 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 125569.00 | 125569.00 | 621.71 | 6.124 | 6.124 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24716.49 | 24716.49 | 78.86 | 1.206 | 1.206 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16307.49 | 16307.49 | 80.74 | 0.796 | 0.796 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24971.63 | 24971.63 | 79.67 | 1.218 | 1.218 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16203.63 | 16203.63 | 80.23 | 0.791 | 0.791 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.49 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.43 | 0.00098 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 19.97 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.05 | 10.05 | 3.22 | 3.22 | 10.0478 | 3.2245 | 10.0478 | 0.3209 | 0.3000 |
VAV_MID WITH REHEAT | 92.45 | 92.45 | 46.55 | 46.55 | 92.4513 | 46.5469 | 92.4513 | 0.5035 | 0.3000 |
VAV_TOP WITH REHEAT | 10.77 | 10.77 | 7.68 | 7.68 | 10.7728 | 7.6846 | 10.7728 | 0.7133 | 0.3000 |
CAV_BAS | 5.52 | 5.52 | 1.20 | 1.20 | 5.5156 | 5.5156 | 5.5156 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.33 | 24.33 | 0.34 | 0.34 | 24.3314 | 24.3313 | 24.3314 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.56 | 0.56 | 0.02 | 0.02 | 0.5585 | 0.5585 | 0.5585 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.37 | 5.37 | 0.16 | 0.16 | 5.3689 | 5.3689 | 5.3689 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.55 | 0.55 | 0.02 | 0.02 | 0.5466 | 0.5466 | 0.5466 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19381.833 | 19381.833 | 1.613970 | 0.00016956 | 405.249 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19381.83 | 19381.83 | 1.613970 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00798160 | 45.1283 | 5169.74 | 0.00 | 19452.04 | 19452.04 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 456310.779 | 456310.779 | 16.160387 | 0.00399201 | 11835.473 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 456310.78 | 456310.78 | 16.160387 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 314002.88 | 0.00 | 457708.68 | 457708.68 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 107858.014 | 107858.014 | 3.674081 | 0.00094359 | 2846.065 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 107858.01 | 107858.01 | 3.674081 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 75504.16 | 0.00 | 108223.14 | 108223.14 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18744.581 | 18744.581 | 0.639194 | 0.00016399 | 494.376 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18744.58 | 18744.58 | 0.639194 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00774890 | 43.8316 | 13119.16 | 0.00 | 18806.31 | 18806.31 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12880.355 | 12880.355 | 0.439281 | 0.00011268 | 339.690 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12880.36 | 12880.36 | 0.439281 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00776541 | 43.9238 | 9014.19 | 0.00 | 12922.62 | 12922.62 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 20761.638 | 20761.638 | 0.708105 | 0.00018163 | 547.529 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20761.64 | 20761.64 | 0.708105 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00778531 | 44.0347 | 14529.25 | 0.00 | 20829.68 | 20829.68 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10562.341 | 10562.341 | 0.360073 | 0.00009240 | 278.612 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10562.34 | 10562.34 | 0.360073 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765243 | 43.2935 | 7394.10 | 0.00 | 10597.39 | 10597.39 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 276330.008 | 276330.008 | 9.430033 | 0.00241746 | 7285.503 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 276330.01 | 276330.01 | 9.430033 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00764520 | 43.2545 | 193362.73 | 0.00 | 277221.84 | 277221.84 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 183409.237 | 183409.237 | 6.259290 | 0.00160454 | 4835.531 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 183409.24 | 183409.24 | 6.259290 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00764408 | 43.2483 | 128339.17 | 0.00 | 184000.49 | 184000.49 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 279727.608 | 279727.608 | 9.546131 | 0.00244718 | 7375.028 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 279727.61 | 279727.61 | 9.546131 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00764948 | 43.2784 | 195738.18 | 0.00 | 280630.02 | 280630.02 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 179447.433 | 179447.433 | 6.123949 | 0.00156988 | 4731.127 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 179447.43 | 179447.43 | 6.123949 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00763636 | 43.2052 | 125569.00 | 0.00 | 180026.26 | 180026.26 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 35325.926 | 35325.926 | 1.205891 | 0.00030905 | 931.249 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35325.93 | 35224.13 | 1.205891 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765584 | 43.3148 | 24716.49 | 0.00 | 35439.02 | 35439.02 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 23307.554 | 23307.554 | 0.795652 | 0.00020390 | 614.418 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23307.55 | 23307.55 | 0.795652 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765236 | 43.2955 | 16307.49 | 0.00 | 23382.12 | 23382.12 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 35690.836 | 35690.836 | 1.218360 | 0.00031224 | 940.865 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35690.84 | 35690.84 | 1.218360 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765921 | 43.3336 | 24971.63 | 0.00 | 35805.07 | 35805.07 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23159.067 | 23159.067 | 0.790583 | 0.00020261 | 610.503 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23159.07 | 23159.07 | 0.790583 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765044 | 43.2848 | 16203.63 | 0.00 | 23233.16 | 23233.16 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 167595.856 | -999.000 | 10.047847 | 0.00479322 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 167595.86 | 164650.42 | 10.047847 | 25.90 | 14.53 | 0.00713666 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 20.2083 | 24.00 | 0.00734695 | 34.6549 | 120562.03 | 0.00 | 122213.09 | 122213.09 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 79868.240 | 79868.240 | 3.014354 | 0.00069872 | 1254.056 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79868.24 | 79868.24 | 3.014354 | -12.24 | -12.24 | 0.00271652 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 67.3610 | 19.75 | 0.00752253 | 45.9859 | 23820.74 | 0.00 | 67294.71 | 67294.71 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1558666.336 | -999.000 | 92.451334 | 0.04457766 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 1558666.34 | 1532285.38 | 92.451334 | 26.07 | 14.58 | 0.00713265 | 10.67 | 8.50 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 21.9640 | 24.00 | 0.00736537 | 34.7406 | 1108781.25 | 0.00 | 1137702.44 | 1137702.44 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 823876.976 | 823876.976 | 27.735400 | 0.00720764 | 12741.500 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 823876.98 | 823876.98 | 27.735400 | -15.27 | -15.27 | 0.00225876 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 73.2133 | 17.87 | 0.00746105 | 51.3017 | 276429.28 | 0.00 | 673435.30 | 673435.30 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 177833.617 | -999.000 | 10.772786 | 0.00508602 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 177833.62 | 175037.28 | 10.772786 | 25.78 | 14.47 | 0.00712127 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 18.8484 | 24.00 | 0.00731131 | 34.4886 | 128841.34 | 0.00 | 129487.79 | 129487.79 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 79632.979 | 79632.979 | 3.231836 | 0.00069666 | 1260.992 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79632.98 | 79632.98 | 3.231836 | -10.48 | -10.48 | 0.00297511 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 62.8281 | 16.63 | 0.00753111 | 55.9814 | 25315.19 | 0.00 | 68372.15 | 68372.15 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 93360.086 | -999.000 | 5.515627 | 0.00267009 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 93360.09 | 90293.27 | 5.515627 | 26.34 | 14.79 | 0.00726542 | 11.22 | 8.74 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 21.7592 | 24.00 | 0.00758414 | 35.7607 | 58763.52 | 0.00 | 68000.70 | 68000.70 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 268531.977 | 268531.977 | 5.515627 | 0.00234923 | 5694.254 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 268531.98 | 268531.98 | 5.515627 | -6.01 | -10.13 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.7592 | 23.01 | 0.00034190 | 1.7307 | 0.00 | 0.00 | 211949.63 | 211949.63 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 462527.065 | 260292.552 | 24.331438 | 0.01132726 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 401910.64 | 400439.83 | -999.0 | 28.68 | 15.39 | 0.00703207 | 12.80 | 9.41 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | -999.0000 | 27.00 | 0.00704231 | 27.8128 | 369906.87 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10314.968 | 5866.675 | 0.558535 | 0.00025261 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 8914.99 | 8849.57 | -999.0 | 28.06 | 15.21 | 0.00706275 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708484 | 27.9769 | 8500.80 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99179.972 | 56398.657 | 5.368890 | 0.00242891 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 85723.22 | 85070.36 | -999.0 | 28.06 | 15.21 | 0.00706514 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708821 | 27.9902 | 81713.07 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10095.410 | 5741.190 | 0.546556 | 0.00024724 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 8725.49 | 8660.06 | -999.0 | 28.06 | 15.21 | 0.00706413 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708675 | 27.9844 | 8318.47 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 462527.065 | 462527.065 | 24.331438 | 0.01132726 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 462527.06 | 462527.06 | 24.331438 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3908 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10314.968 | 10314.968 | 0.558535 | 0.00025261 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10314.97 | 10314.97 | 0.558535 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7988 | 25.28 | 0.00098265 | 4.3366 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99179.972 | 99179.972 | 5.368890 | 0.00242891 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 99179.97 | 99179.97 | 5.368890 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9117 | 23.63 | 0.00098266 | 4.7878 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10095.410 | 10095.410 | 0.546556 | 0.00024724 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10095.41 | 10095.41 | 0.546556 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8602 | 22.18 | 0.00098212 | 5.2240 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 24207.99 | 24207.99 | 24.331438 | -0.38 | -0.38 | 0.00690740 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3908 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.558535 | -0.77 | -5.61 | 0.00096472 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7988 | 25.28 | 0.00098265 | 4.3366 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.09 | 11183.09 | 5.368890 | -0.80 | -5.63 | 0.00096400 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9117 | 23.63 | 0.00098266 | 4.7878 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.546556 | -0.79 | -5.62 | 0.00096381 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8602 | 22.18 | 0.00098212 | 5.2240 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19381.833 | 19381.833 | 1.613970 | 0.00016956 | 405.249 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 0.6474 | 0.660412 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19381.83 | 19381.83 | 1.0000 | 1.69973598 | 1.613970 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.16954343 | 60.00 | 32.22 | 27.78 | 0.000 | 19381.83 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.86 | 0.00798160 | 21.00 | 0.00798160 | 45.1283 | 5169.74 | 0.00 | 19452.04 | 19452.04 | 1.69973598 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.02 | 15.96 | 0.00800000 | 44504.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 456310.779 | 456310.779 | 16.160387 | 0.00399201 | 11835.473 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 15.2415 | 15.548236 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 456310.78 | 456310.78 | 1.0000 | 17.01914773 | 16.160387 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 3.99159853 | 60.00 | 32.22 | 27.78 | 0.000 | 456310.78 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 314002.88 | 0.00 | 457708.68 | 457708.68 | 17.01914773 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.17 | 20.94 | 0.00800000 | 59953.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 107858.014 | 107858.014 | 3.674081 | 0.00094359 | 2846.065 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 3.6026 | 3.675131 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 107858.01 | 107858.01 | 1.0000 | 3.86932158 | 3.674081 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.94349270 | 60.00 | 32.22 | 27.78 | 0.000 | 107858.01 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 75504.16 | 0.00 | 108223.14 | 108223.14 | 3.86932158 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61029.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18744.581 | 18744.581 | 0.639194 | 0.00016399 | 494.376 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 0.6261 | 0.638699 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18744.58 | 18744.58 | 1.0000 | 0.67316108 | 0.639194 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.16396905 | 60.00 | 32.22 | 27.78 | 0.000 | 18744.58 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00774890 | 21.00 | 0.00774890 | 43.8316 | 13119.16 | 0.00 | 18806.31 | 18806.31 | 0.67316108 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12880.355 | 12880.355 | 0.439281 | 0.00011268 | 339.690 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 0.4302 | 0.438882 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12880.36 | 12880.36 | 1.0000 | 0.46262474 | 0.439281 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.11267147 | 60.00 | 32.22 | 27.78 | 0.000 | 12880.36 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776541 | 21.00 | 0.00776541 | 43.9238 | 9014.19 | 0.00 | 12922.62 | 12922.62 | 0.46262474 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20761.638 | 20761.638 | 0.708105 | 0.00018163 | 547.529 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 0.6935 | 0.707428 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20761.64 | 20761.64 | 1.0000 | 0.74573355 | 0.708105 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.18161333 | 60.00 | 32.22 | 27.78 | 0.000 | 20761.64 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00778531 | 21.00 | 0.00778531 | 44.0347 | 14529.25 | 0.00 | 20829.68 | 20829.68 | 0.74573355 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10562.341 | 10562.341 | 0.360073 | 0.00009240 | 278.612 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 0.3528 | 0.359899 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10562.34 | 10562.34 | 1.0000 | 0.37920755 | 0.360073 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09239454 | 60.00 | 32.22 | 27.78 | 0.000 | 10562.34 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765243 | 21.00 | 0.00765243 | 43.2935 | 7394.10 | 0.00 | 10597.39 | 10597.39 | 0.37920755 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 276330.008 | 276330.008 | 9.430033 | 0.00241746 | 7285.503 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 9.2299 | 9.415610 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 276330.01 | 276330.01 | 1.0000 | 9.93114402 | 9.430033 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.41720885 | 60.00 | 32.22 | 27.78 | 0.000 | 276330.01 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00764520 | 21.00 | 0.00764520 | 43.2545 | 193362.73 | 0.00 | 277221.84 | 277221.84 | 9.93114402 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 183409.237 | 183409.237 | 6.259290 | 0.00160454 | 4835.531 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 6.1262 | 6.249447 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 183409.24 | 183409.24 | 1.0000 | 6.59190800 | 6.259290 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.60438034 | 60.00 | 32.22 | 27.78 | 0.000 | 183409.24 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00764408 | 21.00 | 0.00764408 | 43.2483 | 128339.17 | 0.00 | 184000.49 | 184000.49 | 6.59190800 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 279727.608 | 279727.608 | 9.546131 | 0.00244718 | 7375.028 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 9.3433 | 9.531379 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 279727.61 | 279727.61 | 1.0000 | 10.05341143 | 9.546131 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.44692951 | 60.00 | 32.22 | 27.78 | 0.000 | 279727.61 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00764948 | 21.00 | 0.00764948 | 43.2784 | 195738.18 | 0.00 | 280630.02 | 280630.02 | 10.05341143 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 179447.433 | 179447.433 | 6.123949 | 0.00156988 | 4731.127 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 5.9938 | 6.114454 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 179447.43 | 179447.43 | 1.0000 | 6.44937490 | 6.123949 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.56972428 | 60.00 | 32.22 | 27.78 | 0.000 | 179447.43 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00763636 | 21.00 | 0.00763636 | 43.2052 | 125569.00 | 0.00 | 180026.26 | 180026.26 | 6.44937490 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35325.926 | 35325.926 | 1.205891 | 0.00030905 | 931.249 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 1.1799 | 1.203688 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35325.93 | 35224.13 | 1.0000 | 1.26997165 | 1.205891 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.30901508 | 60.00 | 32.22 | 27.78 | 0.000 | 35325.93 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765584 | 21.00 | 0.00765584 | 43.3148 | 24716.49 | 0.00 | 35439.02 | 35439.02 | 1.26997165 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60965.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23307.554 | 23307.554 | 0.795652 | 0.00020390 | 614.418 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 0.7785 | 0.794177 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23307.55 | 23307.55 | 1.0000 | 0.83793323 | 0.795652 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.20388385 | 60.00 | 32.22 | 27.78 | 0.000 | 23307.55 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765236 | 21.00 | 0.00765236 | 43.2955 | 16307.49 | 0.00 | 23382.12 | 23382.12 | 0.83793323 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60964.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35690.836 | 35690.836 | 1.218360 | 0.00031224 | 940.865 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 1.1921 | 1.216122 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35690.84 | 35690.84 | 1.0000 | 1.28310314 | 1.218360 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.31220715 | 60.00 | 32.22 | 27.78 | 0.000 | 35690.84 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765921 | 21.00 | 0.00765921 | 43.3336 | 24971.63 | 0.00 | 35805.07 | 35805.07 | 1.28310314 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60964.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23159.067 | 23159.067 | 0.790583 | 0.00020261 | 610.503 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 0.7735 | 0.789117 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23159.07 | 23159.07 | 1.0000 | 0.83259462 | 0.790583 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.20258495 | 60.00 | 32.22 | 27.78 | 0.000 | 23159.07 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765044 | 21.00 | 0.00765044 | 43.2848 | 16203.63 | 0.00 | 23233.16 | 23233.16 | 0.83259462 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60964.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 167595.856 | -999.000 | 10.047847 | 0.00479322 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1067 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.047847 | 10.58178855 | 4197.9300 | 999.8980 | 57.12115818 | 15.00 | 6.67 | 8.33 | 1997455.89 | 8.3905 | 8.390466 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 167595.86 | 164650.42 | 1.0000 | 10.58178855 | 10.047847 | 25.90 | 14.53 | 0.00713666 | 44216.8 | 10.68 | 8.51 | 0.00700000 | 28378.7 | 4.79273131 | 6.67 | 15.00 | 8.33 | 22824.622 | 144771.23 | 33.40 | 0.00630683 | 16.37 | 2.03050000 | 20.2083 | 24.00 | 0.00734695 | 24.00 | 0.00734695 | 34.6549 | 120562.03 | 0.00 | 122213.09 | 122213.09 | 10.58178855 | 25.90 | 15.88 | 0.00713666 | 44216.8 | 14.56 | 11.45 | 0.00713666 | 32667.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 79868.240 | 79868.240 | 3.014354 | 0.00069872 | 1254.056 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.047847 | 10.58178855 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 2.6677 | 2.721413 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 79868.24 | 79868.24 | 1.0000 | 3.17453656 | 3.014354 | -12.24 | -12.24 | 0.00271652 | -5564.5 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.69865092 | 60.00 | 32.22 | 27.78 | 0.000 | 79868.24 | -27.60 | 0.00034190 | -27.60 | 2.03050000 | 67.3610 | 19.47 | 0.00761732 | 19.75 | 0.00752253 | 45.9859 | 23820.74 | 0.00 | 67294.71 | 67294.71 | 3.17453656 | 2.80 | 0.11 | 0.00271652 | 9621.5 | 23.79 | 10.76 | 0.00271652 | 30819.8 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1558666.336 | -999.000 | 92.451334 | 0.04457766 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0992 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.451334 | 97.36418661 | 4197.9300 | 999.8980 | 57.12115818 | 15.00 | 6.67 | 8.33 | 1997455.89 | 78.0326 | 78.032578 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 1558666.34 | 1532285.38 | 1.0000 | 97.36418661 | 92.451334 | 26.07 | 14.58 | 0.00713265 | 44375.7 | 10.67 | 8.50 | 0.00700000 | 28367.1 | 44.57311251 | 6.67 | 15.00 | 8.33 | 211133.682 | 1347532.65 | 33.40 | 0.00630683 | 16.37 | 20.30600000 | 21.9640 | 24.00 | 0.00736537 | 24.00 | 0.00736537 | 34.7406 | 1108781.25 | 0.00 | 1137702.44 | 1137702.44 | 97.36418661 | 26.07 | 15.94 | 0.00713265 | 44375.7 | 14.59 | 11.46 | 0.00713265 | 32690.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 823876.976 | 823876.976 | 27.735400 | 0.00720764 | 12741.500 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.451334 | 97.36418661 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 27.5188 | 28.072608 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 823876.98 | 823876.98 | 1.0000 | 29.20925598 | 27.735400 | -15.27 | -15.27 | 0.00225876 | -9758.6 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 7.20689994 | 60.00 | 32.22 | 27.78 | 0.000 | 823876.98 | -27.60 | 0.00034190 | -27.60 | 20.30600000 | 73.2133 | 18.43 | 0.00749791 | 17.87 | 0.00746105 | 51.3017 | 276429.28 | 0.00 | 673435.30 | 673435.30 | 29.20925598 | 2.80 | -0.78 | 0.00225876 | 8474.3 | 25.65 | 11.08 | 0.00225876 | 31529.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 177833.617 | -999.000 | 10.772786 | 0.00508602 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0781 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.772786 | 11.34525078 | 4197.9300 | 999.8980 | 57.12115818 | 15.00 | 6.67 | 8.33 | 1997455.89 | 8.9030 | 8.903006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 177833.62 | 175037.28 | 1.0000 | 11.34525078 | 10.772786 | 25.78 | 14.47 | 0.00712127 | 44053.3 | 10.68 | 8.51 | 0.00700000 | 28378.6 | 5.08550010 | 6.67 | 15.00 | 8.33 | 24471.388 | 153362.23 | 33.40 | 0.00630683 | 16.37 | 2.03050000 | 18.8484 | 24.00 | 0.00731131 | 24.00 | 0.00731131 | 34.4886 | 128841.34 | 0.00 | 129487.79 | 129487.79 | 11.34525078 | 25.78 | 15.83 | 0.00712127 | 44053.3 | 14.57 | 11.44 | 0.00712127 | 32639.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 79632.979 | 79632.979 | 3.231836 | 0.00069666 | 1260.992 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.772786 | 11.34525078 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 2.6599 | 2.713397 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 79632.98 | 79632.98 | 1.0000 | 3.40357524 | 3.231836 | -10.48 | -10.48 | 0.00297511 | -3151.9 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.69659297 | 60.00 | 32.22 | 27.78 | 0.000 | 79632.98 | -27.60 | 0.00034190 | -27.60 | 2.03050000 | 62.8281 | 18.45 | 0.00742578 | 16.63 | 0.00753111 | 55.9814 | 25315.19 | 0.00 | 68372.15 | 68372.15 | 3.40357524 | 2.80 | 0.49 | 0.00297511 | 10269.6 | 22.68 | 10.56 | 0.00297511 | 30358.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 93360.086 | -999.000 | 5.515627 | 0.00267009 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3460 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 5.515627 | 5.80872649 | 4197.9300 | 999.8980 | 57.12115818 | 15.00 | 6.67 | 8.33 | 1997455.89 | 4.6739 | 4.673950 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 93360.09 | 90293.27 | 1.0000 | 5.80872649 | 5.515627 | 26.34 | 14.79 | 0.00726542 | 44998.2 | 11.22 | 8.74 | 0.00700000 | 28925.8 | 2.66981426 | 6.67 | 15.00 | 8.33 | 9352.596 | 84007.49 | 33.40 | 0.00630683 | 16.37 | 1.20015641 | 21.7592 | 24.00 | 0.00758414 | 24.00 | 0.00758414 | 35.7607 | 58763.52 | 0.00 | 68000.70 | 68000.70 | 5.80872649 | 26.34 | 16.16 | 0.00726542 | 44998.2 | 14.85 | 11.71 | 0.00726542 | 33291.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 268531.977 | 268531.977 | 5.515627 | 0.00234923 | 5694.254 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 5.515627 | 5.80872649 | 4197.9300 | 999.8980 | 25.67235613 | 54.44 | 82.22 | 27.78 | 2993871.55 | 8.9694 | 9.149901 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 268531.98 | 268531.98 | 1.0000 | 5.80872649 | 5.515627 | -6.01 | -10.13 | 0.00034190 | -5183.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.34899523 | 60.00 | 32.22 | 27.78 | 0.000 | 268531.98 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 21.7592 | 0.00 | 0.00034190 | 23.01 | 0.00034190 | 1.7307 | 0.00 | 0.00 | 211949.63 | 211949.63 | 5.80872649 | 12.80 | 2.46 | 0.00034190 | 13725.2 | 49.09 | 18.11 | 0.00034190 | 50213.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 462527.065 | 260292.552 | 24.331438 | 0.01132726 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9123 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 401910.64 | 400439.83 | 0.8689 | -999.0 | -999.0 | 28.68 | 15.39 | 0.00703207 | 46780.3 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 401910.64 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | -999.0000 | 27.00 | 0.00704231 | 27.00 | 0.00704231 | 27.8128 | 369906.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10314.968 | 5866.675 | 0.558535 | 0.00025261 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9693 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 8914.99 | 8849.57 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706275 | 46227.8 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8914.99 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708484 | 27.00 | 0.00708484 | 27.9769 | 8500.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 99179.972 | 56398.657 | 5.368890 | 0.00242891 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9737 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 85723.22 | 85070.36 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706514 | 46233.0 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85723.22 | 26.28 | 0.00629588 | 13.94 | 0.15632344 | -999.0000 | 27.00 | 0.00708821 | 27.00 | 0.00708821 | 27.9902 | 81713.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10095.410 | 5741.190 | 0.546556 | 0.00024724 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9719 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 8725.49 | 8660.06 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706413 | 46230.9 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8725.49 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708675 | 27.00 | 0.00708675 | 27.9844 | 8318.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 462527.065 | 462527.065 | 24.331438 | 0.01132726 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 462527.06 | 462527.06 | 1.0000 | 25.62440722 | 24.331438 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 462527.06 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3908 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10314.968 | 10314.968 | 0.558535 | 0.00025261 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10314.97 | 10314.97 | 1.0000 | 0.58821522 | 0.558535 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10314.97 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7988 | 0.00 | 0.00098265 | 25.28 | 0.00098265 | 4.3366 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99179.972 | 99179.972 | 5.368890 | 0.00242891 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 99179.97 | 99179.97 | 1.0000 | 5.65419212 | 5.368890 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99179.97 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.9117 | 0.00 | 0.00098266 | 23.63 | 0.00098266 | 4.7878 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10095.410 | 10095.410 | 0.546556 | 0.00024724 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10095.41 | 10095.41 | 1.0000 | 0.57560037 | 0.546556 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10095.41 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8602 | 0.00 | 0.00098212 | 22.18 | 0.00098212 | 5.2240 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.331438 | 25.62440722 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 24207.99 | 24207.99 | 1.0000 | 25.62440722 | 24.331438 | -0.38 | -0.38 | 0.00690740 | 16884.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24207.99 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3908 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.558535 | 0.58821522 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.58821522 | 0.558535 | -0.77 | -5.61 | 0.00096472 | 1635.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7988 | 0.00 | 0.00098265 | 25.28 | 0.00098265 | 4.3366 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.368890 | 5.65419212 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.09 | 11183.09 | 1.0000 | 5.65419212 | 5.368890 | -0.80 | -5.63 | 0.00096400 | 1602.0 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.09 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.9117 | 0.00 | 0.00098266 | 23.63 | 0.00098266 | 4.7878 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.546556 | 0.57560037 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.57560037 | 0.546556 | -0.79 | -5.62 | 0.00096381 | 1615.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8602 | 0.00 | 0.00098212 | 22.18 | 0.00098212 | 5.2240 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.05 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 92.45 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.77 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.52 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.33 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1390.00 | 2125.50 | 37.50 |
CORE_BOTTOM | 1249.00 | 1986.00 | 7.00 |
CORE_MID | 938.00 | 3686.83 | 270.00 |
CORE_TOP | 1977.00 | 4249.00 | 1334.17 |
PERIMETER_BOT_ZN_3 | 1686.33 | 3820.00 | 690.67 |
PERIMETER_BOT_ZN_2 | 2192.17 | 3455.50 | 807.83 |
PERIMETER_BOT_ZN_1 | 2437.50 | 3067.67 | 783.33 |
PERIMETER_BOT_ZN_4 | 2489.67 | 2395.83 | 512.00 |
PERIMETER_MID_ZN_3 | 2785.33 | 4400.83 | 2086.17 |
PERIMETER_MID_ZN_2 | 2577.83 | 3357.00 | 1613.67 |
PERIMETER_MID_ZN_1 | 2799.67 | 3439.50 | 1323.17 |
PERIMETER_MID_ZN_4 | 2930.83 | 3794.50 | 1660.17 |
PERIMETER_TOP_ZN_3 | 3384.83 | 4582.17 | 2707.33 |
PERIMETER_TOP_ZN_2 | 3478.17 | 4067.17 | 2327.83 |
PERIMETER_TOP_ZN_1 | 3166.33 | 3770.33 | 1874.00 |
PERIMETER_TOP_ZN_4 | 3371.83 | 4064.83 | 2202.33 |
DATACENTER_BOT_ZN_6 | 5774.33 | 305.33 | 303.83 |
DATACENTER_MID_ZN_6 | 5114.17 | 239.33 | 72.17 |
DATACENTER_TOP_ZN_6 | 4364.17 | 620.00 | 149.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5532.33 | 5532.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5941.67 | 5924.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 44.83 | 0.00 | 11.00 |
CORE_BOTTOM | 0.00 | 28.33 | 0.00 | 26.33 |
CORE_MID | 0.33 | 9.00 | 0.00 | 9.00 |
CORE_TOP | 22.67 | 25.33 | 5.83 | 25.33 |
PERIMETER_BOT_ZN_3 | 7.17 | 67.67 | 0.83 | 65.50 |
PERIMETER_BOT_ZN_2 | 6.83 | 65.33 | 0.17 | 62.67 |
PERIMETER_BOT_ZN_1 | 7.83 | 160.67 | 0.33 | 155.17 |
PERIMETER_BOT_ZN_4 | 2.83 | 157.33 | 0.00 | 97.50 |
PERIMETER_MID_ZN_3 | 129.17 | 42.50 | 44.83 | 41.33 |
PERIMETER_MID_ZN_2 | 135.17 | 58.83 | 7.67 | 48.17 |
PERIMETER_MID_ZN_1 | 49.83 | 122.00 | 5.17 | 117.00 |
PERIMETER_MID_ZN_4 | 52.83 | 72.17 | 7.17 | 48.67 |
PERIMETER_TOP_ZN_3 | 317.00 | 38.33 | 110.83 | 35.50 |
PERIMETER_TOP_ZN_2 | 180.00 | 63.83 | 30.67 | 58.33 |
PERIMETER_TOP_ZN_1 | 140.67 | 107.83 | 18.17 | 100.67 |
PERIMETER_TOP_ZN_4 | 134.50 | 73.83 | 24.33 | 50.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 22.67 | 0.00 | 16.83 |
DATACENTER_MID_ZN_6 | 0.00 | 12.17 | 0.00 | 7.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 12.83 | 0.00 | 8.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 112.50 | 0.00 | 105.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 433.33 | 501.67 | 123.67 | 380.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 1.158 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 0.880 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.651 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.618 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 0.826 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 1.335 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 1.439 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 1.808 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 0.685 | 0.137 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 1.156 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 1.342 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 1.146 | 0.143 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 0.738 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 1.288 | 0.176 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 1.363 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 1.190 | 0.177 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.22 | 42.18 | 1911.37 | 26.772 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.22 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.09 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.87 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.22 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1012.40 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 47446414.27 | 0.00 | 47446414.27 | 0.00 | 47446414.27 | 37848132.68 | 4040.53 | 1155.81 | 3563.66 | 264.08 |
CORE_BOTTOM | 37356356.80 | 0.00 | 37356356.80 | 0.00 | 37356356.80 | 33990283.35 | 4272.54 | 205.90 | 4281.56 | 456.16 |
CORE_MID | 0.27E+09 | 0.00 | 0.27E+09 | 0.00 | 0.27E+09 | 0.34E+09 | 5177.34 | 758.70 | 2823.96 | 381.77 |
CORE_TOP | 25507926.81 | 0.00 | 25507926.81 | 0.00 | 25507926.81 | 33990283.35 | 5469.27 | 1045.67 | 2245.05 | 417.50 |
PERIMETER_BOT_ZN_3 | 4410176.03 | 0.00 | 4410176.03 | 591585.02 | 5001761.05 | 4267819.30 | 5535.69 | 191.47 | 3032.84 | 456.16 |
PERIMETER_BOT_ZN_2 | 4489995.72 | 0.00 | 4489995.72 | 394389.74 | 4884385.46 | 2750345.05 | 5264.49 | 176.67 | 3318.84 | 456.16 |
PERIMETER_BOT_ZN_1 | 7487928.15 | 0.00 | 7487928.15 | 591585.02 | 8079513.17 | 4267912.63 | 4936.24 | 165.62 | 3658.14 | 456.16 |
PERIMETER_BOT_ZN_4 | 6149846.61 | 0.00 | 6149846.61 | 394389.74 | 6544236.35 | 2750345.05 | 4326.42 | 159.13 | 4274.45 | 456.16 |
PERIMETER_MID_ZN_3 | 35707156.59 | 0.00 | 35707156.59 | 1387434.57 | 37094591.16 | 42678193.03 | 5110.26 | 505.27 | 3144.47 | 381.77 |
PERIMETER_MID_ZN_2 | 39681669.62 | 0.00 | 39681669.62 | 924955.75 | 40606625.37 | 27503450.52 | 5049.80 | 399.28 | 3310.92 | 900.55 |
PERIMETER_MID_ZN_1 | 68649110.27 | 0.00 | 68649110.27 | 1387434.57 | 70036544.84 | 42679126.28 | 4486.24 | 552.30 | 3721.46 | 381.77 |
PERIMETER_MID_ZN_4 | 38414902.27 | 0.00 | 38414902.27 | 924955.75 | 39339858.02 | 27503450.52 | 4804.29 | 391.94 | 3563.77 | 381.77 |
PERIMETER_TOP_ZN_3 | 3831649.14 | 0.00 | 3831649.14 | 1722650.34 | 5554299.49 | 4267819.30 | 4417.54 | 71.07 | 4271.39 | 417.50 |
PERIMETER_TOP_ZN_2 | 4242605.98 | 0.00 | 4242605.98 | 1148432.78 | 5391038.76 | 2750345.05 | 4523.96 | 584.31 | 3651.74 | 417.50 |
PERIMETER_TOP_ZN_1 | 6957177.30 | 0.00 | 6957177.30 | 1722650.34 | 8679827.65 | 4267912.63 | 4439.12 | 1150.42 | 3170.46 | 417.50 |
PERIMETER_TOP_ZN_4 | 3980776.93 | 0.00 | 3980776.93 | 1148432.78 | 5129209.71 | 2750345.05 | 4527.63 | 538.79 | 3693.58 | 417.50 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.42E+09 | 0.00 | 0.42E+09 | 0.00 | 0.42E+09 | 10671554.30 | 51.83 | 189.83 | 8518.33 | 2801.17 |
Total Facility | 0.51E+10 | 0.00 | 0.51E+10 | 53961922.12 | 0.52E+10 | 0.50E+10 | 7296.61 | 4369.79 | 8708.95 | 3320.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.1404 | 0.0000 | 2.1404 | 0.0000 | 2.1404 | 1.2002 | 1356.31 | 1154.00 | 3432.69 |
CORE_BOTTOM | 1.6422 | 0.0000 | 1.6422 | 0.0000 | 1.6422 | 1.0778 | 1792.14 | 203.33 | 3947.53 |
CORE_MID | 12.1586 | 0.0000 | 12.1586 | 0.0000 | 12.1586 | 10.7782 | 2467.89 | 757.20 | 2717.91 |
CORE_TOP | 1.1572 | 0.0000 | 1.1572 | 0.0000 | 1.1572 | 1.0778 | 2745.16 | 1045.62 | 2152.22 |
PERIMETER_BOT_ZN_3 | 0.1938 | 0.0000 | 0.1938 | 0.0139 | 0.2077 | 0.1353 | 3046.73 | 188.12 | 2708.15 |
PERIMETER_BOT_ZN_2 | 0.2019 | 0.0000 | 0.2019 | 0.0092 | 0.2111 | 0.0872 | 2776.74 | 173.30 | 2992.96 |
PERIMETER_BOT_ZN_1 | 0.3375 | 0.0000 | 0.3375 | 0.0139 | 0.3513 | 0.1353 | 2448.92 | 162.02 | 3332.06 |
PERIMETER_BOT_ZN_4 | 0.2731 | 0.0000 | 0.2731 | 0.0092 | 0.2823 | 0.0872 | 1848.25 | 156.36 | 3938.39 |
PERIMETER_MID_ZN_3 | 1.6113 | 0.0000 | 1.6113 | 0.0325 | 1.6438 | 1.3533 | 2407.07 | 503.18 | 3032.75 |
PERIMETER_MID_ZN_2 | 1.7490 | 0.0000 | 1.7490 | 0.0230 | 1.7720 | 0.8721 | 1880.80 | 396.38 | 2756.81 |
PERIMETER_MID_ZN_1 | 3.1506 | 0.0000 | 3.1506 | 0.0325 | 3.1832 | 1.3533 | 1782.44 | 550.68 | 3609.88 |
PERIMETER_MID_ZN_4 | 1.7339 | 0.0000 | 1.7339 | 0.0217 | 1.7556 | 0.8721 | 2100.99 | 390.50 | 3451.51 |
PERIMETER_TOP_ZN_3 | 0.1739 | 0.0000 | 0.1739 | 0.0404 | 0.2143 | 0.1353 | 1698.83 | 70.61 | 4173.55 |
PERIMETER_TOP_ZN_2 | 0.1950 | 0.0000 | 0.1950 | 0.0269 | 0.2219 | 0.0872 | 1807.64 | 583.89 | 3551.47 |
PERIMETER_TOP_ZN_1 | 0.3202 | 0.0000 | 0.3202 | 0.0404 | 0.3605 | 0.1353 | 1719.91 | 1150.20 | 3072.90 |
PERIMETER_TOP_ZN_4 | 0.1801 | 0.0000 | 0.1801 | 0.0269 | 0.2070 | 0.0872 | 1807.93 | 538.36 | 3596.71 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.7812 | 0.0000 | 13.7812 | 0.0000 | 13.7812 | 0.3384 | 36.00 | 189.83 | 5717.17 |
Total Facility | 225.7954 | 0.0000 | 225.7954 | 1.2778 | 227.0731 | 158.4706 | 4479.61 | 4359.41 | 5907.53 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 66428858.86 | 0.00 | 66428858.86 | 48026705.38 | 3669.44 | 5.34 | 5085.21 | 456.16 |
VAV_MID WITH REHEAT | 0.50E+09 | 0.00 | 0.50E+09 | 0.48E+09 | 4049.72 | 5.22 | 4705.06 | 381.77 |
VAV_TOP WITH REHEAT | 49377320.31 | 0.00 | 49377320.31 | 48026705.38 | 4110.43 | 2.69 | 4646.87 | 417.19 |
CAV_BAS | 52622989.20 | 0.00 | 52622989.20 | 37848132.68 | 4015.92 | 4.90 | 4739.19 | 264.00 |
AIRLOOP DATACENTER BASEMENT | 0.47E+09 | 0.00 | 0.47E+09 | 10671554.30 | 51.83 | 0.00 | 8708.17 | 2801.17 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.9374 | 0.0000 | 2.9374 | 1.5229 | 1199.74 | 4.43 | 4738.83 |
VAV_MID WITH REHEAT | 22.7037 | 0.0000 | 22.7037 | 15.2292 | 1346.91 | 3.48 | 4592.61 |
VAV_TOP WITH REHEAT | 2.2475 | 0.0000 | 2.2475 | 1.5229 | 1388.16 | 2.57 | 4552.27 |
CAV_BAS | 2.3739 | 0.0000 | 2.3739 | 1.2002 | 1344.84 | 2.42 | 4595.74 |
AIRLOOP DATACENTER BASEMENT | 15.2848 | 0.0000 | 15.2848 | 0.3384 | 36.00 | 0.00 | 5907.00 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 952.71 | 2947.08 | 0.00 | 0.00 | 0.00 | 1484.89 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 539.13 | 2918.34 | 0.00 | 0.00 | 0.00 | 1792.94 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 152.25 | 2574.79 | 0.00 | 0.00 | 0.00 | 2538.47 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1143.42 | 3773.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 189.83 | 8518.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.2898 | 5.0089 | 0.0000 | 0.0000 | 0.0000 | 1.8882 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 22.5175 | 35.5535 | 0.0000 | 0.0000 | 0.0000 | 18.1929 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.2735 | 3.9041 | 0.0000 | 0.0000 | 0.0000 | 1.8073 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3316 | 3.5868 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3770 | 15.8765 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1520 |
Defaulted Fields | 1187 |
Fields with Defaults | 3882 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 24774.25 | 304371.25 | 21-MAY-02:10 | 1851136.76 | 10-AUG-15:50 |
Electricity:Building | 16393.86 | 215366.33 | 06-MAY-18:10 | 948093.84 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16393.86 | 215366.33 | 06-MAY-18:10 | 948093.84 | 01-DEC-16:40 |
InteriorLights:Electricity | 1717.46 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1717.46 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 1717.46 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1717.46 | 8110.17 | 01-JAN-10:00 | 169722.15 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.99 | 589.50 | 12-MAR-17:10 | 3307.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.62 | 30.32 | 01-JAN-10:00 | 1147.25 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.62 | 30.32 | 01-JAN-10:00 | 1147.25 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.30 | 379.89 | 26-MAR-17:10 | 2131.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.86 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.86 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.86 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.50 | 30.33 | 01-JAN-08:50 | 1147.28 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.50 | 30.33 | 01-JAN-08:50 | 1147.28 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.31 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.87 | 19.54 | 01-JAN-10:00 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.87 | 19.54 | 01-JAN-10:00 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 439.74 | 5894.96 | 12-MAR-17:10 | 33078.05 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 76.08 | 303.25 | 01-JAN-09:50 | 11472.53 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 76.08 | 303.25 | 01-JAN-09:50 | 11472.53 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.93 | 3798.93 | 19-MAR-17:10 | 21316.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.58 | 195.42 | 01-JAN-08:40 | 7393.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.58 | 195.42 | 01-JAN-08:40 | 7393.34 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 438.59 | 5895.05 | 12-MAR-17:10 | 33078.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.93 | 303.26 | 01-JAN-08:50 | 11472.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.93 | 303.26 | 01-JAN-08:50 | 11472.78 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 283.01 | 3798.91 | 12-MAR-17:10 | 21316.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.66 | 195.42 | 01-JAN-09:50 | 7393.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.66 | 195.42 | 01-JAN-09:50 | 7393.34 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.97 | 589.50 | 12-MAR-17:10 | 3307.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.61 | 30.32 | 01-JAN-09:50 | 1147.25 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.61 | 30.32 | 01-JAN-09:50 | 1147.25 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.29 | 379.89 | 19-MAR-17:10 | 2131.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.86 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.86 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.86 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.49 | 30.33 | 01-JAN-08:50 | 1147.28 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.49 | 30.33 | 01-JAN-08:50 | 1147.28 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.30 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.87 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.87 | 19.54 | 01-JAN-09:50 | 739.33 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1174.93 | 3661.85 | 11-JAN-02:00 | 423210.62 | 07-SEP-14:50 |
HeatRejection:Electricity | 385.37 | 54.41 | 10-JAN-22:00 | 71995.62 | 20-JUN-13:20 |
General:HeatRejection:Electricity | 385.37 | 54.41 | 10-JAN-22:00 | 71995.62 | 20-JUN-13:20 |
ElectricityProduced:Facility | 454.53 | -0.00 | 13-JAN-08:30 | 85349.02 | 14-MAY-12:30 |
ElectricityProduced:Plant | 454.53 | -0.00 | 13-JAN-08:30 | 85349.02 | 14-MAY-12:30 |
Photovoltaic:ElectricityProduced | 475.57 | 0.00 | 01-JAN-00:10 | 88862.04 | 14-MAY-12:30 |
PowerConversion:ElectricityProduced | -21.04 | -3513.01 | 14-MAY-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 5787.55 | 54012.95 | 11-SEP-22:40 | 589819.53 | 07-AUG-15:00 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73700.64 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.36 | 979.82 | 01-JAN-00:10 | 3372.05 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
ElectricityPurchased:Plant | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
Cogeneration:ElectricityPurchased | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
ElectricityNet:Plant | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
Cogeneration:ElectricityNet | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
General:Cogeneration:ElectricityNet | 24319.72 | 304371.25 | 21-MAY-02:10 | 1805669.73 | 09-AUG-16:00 |
Fans:Electricity | 2505.09 | 47380.11 | 01-JAN-06:00 | 315059.02 | 06-JUN-15:30 |
General:Fans:Electricity | 2505.09 | 47380.11 | 01-JAN-06:00 | 315059.02 | 06-JUN-15:30 |
ExteriorLights:Electricity | 268.57 | 0.00 | 01-JAN-08:20 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 268.57 | 0.00 | 01-JAN-08:20 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 1283.71 | 1432.39 | 10-JAN-22:00 | 384328.86 | 10-AUG-15:00 |
General:Cooling:Electricity | 1283.71 | 1432.39 | 10-JAN-22:00 | 384328.86 | 10-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2431.85 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:30 |
General:Humidifier:Electricity | 2431.85 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 302.11 | 3600.00 | 01-JAN-06:00 | 44235.51 | 17-JUL-16:00 |
General:Pumps:Electricity | 302.11 | 3600.00 | 01-JAN-06:00 | 44235.51 | 17-JUL-16:00 |
WIRED_LTG_ELECTRICITY | 48.26 | 0.00 | 01-JAN-00:10 | 4769.19 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4309.50 | 7280.88 | 05-JAN-22:20 | 2396861.01 | 09-JAN-07:10 |
NaturalGas:Plant | 4309.50 | 7280.88 | 05-JAN-22:20 | 2396861.01 | 09-JAN-07:10 |
Heating:NaturalGas | 3488.37 | 0.00 | 01-JAN-00:40 | 2364675.41 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 3488.37 | 0.00 | 01-JAN-00:40 | 2364675.41 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 821.13 | 7280.88 | 03-JAN-05:20 | 87109.56 | 16-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 821.13 | 7280.88 | 03-JAN-05:20 | 87109.56 | 16-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7262.65 | 3786.24 | 10-JAN-22:00 | 2281517.15 | 10-AUG-15:00 |
PlantLoopCoolingDemand:HVAC | 7262.65 | 3786.24 | 10-JAN-22:00 | 2281517.15 | 10-AUG-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 7262.65 | 3786.24 | 10-JAN-22:00 | 2281517.15 | 10-AUG-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6261.47 | 0.00 | 20-MAY-23:10 | 0.00 | 25-JUL-12:00 |
Water:HVAC | 904.65 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
Humidifier:Water | 904.65 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
General:Humidifier:Water | 904.65 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
MainsWater:Facility | 6261.47 | 0.00 | 20-MAY-23:10 | 0.00 | 25-JUL-12:00 |
MainsWater:HVAC | 904.65 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
Humidifier:MainsWater | 904.65 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
General:Humidifier:MainsWater | 904.65 | 0.00 | 02-MAY-11:50 | 0.00 | 01-FEB-22:10 |
Water:Plant | 5356.83 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5356.83 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3076.66 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:00 |
General:HeatRejection:Water | 3076.66 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:00 |
HeatRejection:MainsWater | 3076.66 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:00 |
General:HeatRejection:MainsWater | 3076.66 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 41170.85 | 94978.52 | 28-JAN-06:00 | 9706926.00 | 07-SEP-14:50 |
EnergyTransfer:Building | 17317.93 | 86835.62 | 28-JAN-18:10 | 1663104.46 | 10-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 585.34 | 0.00 | 01-JAN-00:40 | 69949.51 | 05-SEP-05:10 |
Heating:EnergyTransfer | 958.89 | 0.00 | 14-JAN-18:10 | 1279979.91 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.27 | 0.00 | 01-JAN-00:30 | 21005.59 | 05-AUG-16:10 |
General:Heating:EnergyTransfer | 958.89 | 0.00 | 14-JAN-18:10 | 1279979.91 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.27 | 0.00 | 01-JAN-00:30 | 21005.59 | 05-AUG-16:10 |
Cooling:EnergyTransfer | 16359.04 | 83017.96 | 09-JAN-05:40 | 1663104.46 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 583.07 | 0.00 | 01-JAN-00:20 | 69949.51 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 16359.04 | 83017.96 | 09-JAN-05:40 | 1663104.46 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 583.07 | 0.00 | 01-JAN-00:20 | 69949.51 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 513.83 | 0.00 | 01-JAN-00:10 | 53884.80 | 07-AUG-07:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 513.83 | 0.00 | 01-JAN-00:10 | 53884.80 | 07-AUG-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 513.83 | 0.00 | 01-JAN-00:10 | 53884.80 | 07-AUG-07:30 |
EnergyTransfer:Zone:CORE_MID | 3467.59 | 0.00 | 01-JAN-00:10 | 452894.99 | 14-JUL-09:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 8.44 | 0.00 | 01-JAN-00:10 | 355311.35 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 8.44 | 0.00 | 01-JAN-00:10 | 355311.35 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3459.15 | 0.00 | 01-JAN-00:10 | 452894.99 | 14-JUL-09:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3459.15 | 0.00 | 01-JAN-00:10 | 452894.99 | 14-JUL-09:50 |
EnergyTransfer:Zone:CORE_TOP | 307.54 | 0.00 | 01-JAN-00:40 | 64842.53 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 24.87 | 0.00 | 01-JAN-00:10 | 64842.53 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 24.87 | 0.00 | 01-JAN-00:10 | 64842.53 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 282.67 | 0.00 | 01-JAN-00:40 | 51872.53 | 21-JUN-12:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 282.67 | 0.00 | 01-JAN-00:40 | 51872.53 | 21-JUN-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 57.58 | 0.00 | 01-JAN-00:10 | 11741.09 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.35 | 0.00 | 01-JAN-00:10 | 11741.09 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.35 | 0.00 | 01-JAN-00:10 | 11741.09 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 54.23 | 0.00 | 01-JAN-00:10 | 10596.60 | 10-AUG-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 54.23 | 0.00 | 01-JAN-00:10 | 10596.60 | 10-AUG-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.03 | 0.00 | 01-JAN-00:10 | 16882.72 | 07-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.44 | 0.00 | 01-JAN-00:10 | 9491.22 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.44 | 0.00 | 01-JAN-00:10 | 9491.22 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.60 | 0.00 | 01-JAN-00:10 | 16882.72 | 07-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.60 | 0.00 | 01-JAN-00:10 | 16882.72 | 07-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.09 | 0.00 | 01-JAN-00:10 | 23658.40 | 18-OCT-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.46 | 0.00 | 01-JAN-00:10 | 14714.52 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.46 | 0.00 | 01-JAN-00:10 | 14714.52 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.64 | 0.00 | 01-JAN-00:10 | 23658.40 | 18-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.64 | 0.00 | 01-JAN-00:10 | 23658.40 | 18-OCT-14:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 85.18 | 0.00 | 01-JAN-00:10 | 21556.66 | 24-JUL-17:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.66 | 0.00 | 01-JAN-00:10 | 6891.91 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.66 | 0.00 | 01-JAN-00:10 | 6891.91 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.52 | 0.00 | 01-JAN-00:10 | 21556.66 | 24-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.52 | 0.00 | 01-JAN-00:10 | 21556.66 | 24-JUL-17:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 564.91 | 0.00 | 01-JAN-00:10 | 127723.86 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 213.61 | 0.00 | 01-JAN-00:10 | 127723.86 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 213.61 | 0.00 | 01-JAN-00:10 | 127723.86 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 351.30 | 0.00 | 01-JAN-00:10 | 98129.16 | 25-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 351.30 | 0.00 | 01-JAN-00:10 | 98129.16 | 25-JUL-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 579.37 | 0.00 | 01-JAN-00:10 | 175199.22 | 07-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 118.95 | 0.00 | 01-JAN-00:10 | 149062.13 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 118.95 | 0.00 | 01-JAN-00:10 | 149062.13 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 460.41 | 0.00 | 01-JAN-00:10 | 175199.22 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 460.41 | 0.00 | 01-JAN-00:10 | 175199.22 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1032.84 | 0.00 | 01-JAN-00:10 | 251082.42 | 18-OCT-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 124.37 | 0.00 | 01-JAN-00:10 | 205962.50 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 124.37 | 0.00 | 01-JAN-00:10 | 205962.50 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 908.47 | 0.00 | 01-JAN-00:10 | 251082.42 | 18-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 908.47 | 0.00 | 01-JAN-00:10 | 251082.42 | 18-OCT-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 581.05 | 0.00 | 01-JAN-00:10 | 202666.34 | 31-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 97.84 | 0.00 | 01-JAN-00:10 | 143467.21 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 97.84 | 0.00 | 01-JAN-00:10 | 143467.21 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 483.21 | 0.00 | 01-JAN-00:10 | 202666.34 | 31-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 483.21 | 0.00 | 01-JAN-00:10 | 202666.34 | 31-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.50 | 0.00 | 01-JAN-00:40 | 16352.61 | 30-JAN-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.43 | 0.00 | 01-JAN-00:40 | 16352.61 | 30-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.43 | 0.00 | 01-JAN-00:40 | 16352.61 | 30-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.07 | 0.00 | 01-JAN-00:20 | 11811.07 | 25-JUL-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.07 | 0.00 | 01-JAN-00:20 | 11811.07 | 25-JUL-16:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 70.76 | 0.00 | 01-JAN-00:40 | 18696.33 | 14-JUL-10:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.48 | 0.00 | 01-JAN-00:40 | 17927.80 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.48 | 0.00 | 01-JAN-00:40 | 17927.80 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.28 | 0.00 | 01-JAN-00:20 | 18696.33 | 14-JUL-10:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.28 | 0.00 | 01-JAN-00:20 | 18696.33 | 14-JUL-10:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 112.07 | 0.00 | 01-JAN-00:40 | 25508.52 | 18-OCT-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 30.44 | 0.00 | 01-JAN-00:10 | 23679.10 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 30.44 | 0.00 | 01-JAN-00:10 | 23679.10 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.63 | 0.00 | 01-JAN-00:40 | 25508.52 | 18-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.63 | 0.00 | 01-JAN-00:40 | 25508.52 | 18-OCT-14:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 67.09 | 0.00 | 01-JAN-00:40 | 21377.02 | 31-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.69 | 0.00 | 01-JAN-00:40 | 19386.96 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.69 | 0.00 | 01-JAN-00:40 | 19386.96 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.40 | 0.00 | 01-JAN-00:10 | 21377.02 | 31-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.40 | 0.00 | 01-JAN-00:10 | 21377.02 | 31-JUL-16:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 46.61 | 0.00 | 01-JAN-00:10 | 10485.89 | 07-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.60 | 0.00 | 01-JAN-00:10 | 6341.91 | 30-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.60 | 0.00 | 01-JAN-00:10 | 6341.91 | 30-JAN-13:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 41.01 | 0.00 | 01-JAN-00:10 | 10485.89 | 07-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 41.01 | 0.00 | 01-JAN-00:10 | 10485.89 | 07-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 380.75 | 0.00 | 01-JAN-00:10 | 112285.87 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 160.52 | 0.00 | 01-JAN-00:10 | 112285.87 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 160.52 | 0.00 | 01-JAN-00:10 | 112285.87 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 220.23 | 0.00 | 01-JAN-00:10 | 80063.91 | 05-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 220.23 | 0.00 | 01-JAN-00:10 | 80063.91 | 05-SEP-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 100.97 | 0.00 | 01-JAN-00:40 | 32046.98 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 59.50 | 0.00 | 01-JAN-00:40 | 32046.98 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 59.50 | 0.00 | 01-JAN-00:40 | 32046.98 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 41.47 | 0.00 | 01-JAN-00:10 | 22125.33 | 25-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 41.47 | 0.00 | 01-JAN-00:10 | 22125.33 | 25-JUL-16:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.76 | 7.33 | 08-JAN-14:30 | 8412.58 | 22-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.08 | 0.00 | 01-JAN-00:10 | 626.88 | 09-JAN-03:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.08 | 0.00 | 01-JAN-00:10 | 626.88 | 09-JAN-03:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.68 | 0.00 | 07-JAN-23:00 | 8412.58 | 22-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.68 | 0.00 | 07-JAN-23:00 | 8412.58 | 22-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1144.07 | 0.26 | 12-JAN-20:10 | 78924.11 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.75 | 0.00 | 02-JAN-11:10 | 6412.59 | 29-JAN-18:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.75 | 0.00 | 02-JAN-11:10 | 6412.59 | 29-JAN-18:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1137.32 | 0.00 | 01-JAN-00:10 | 78924.11 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1137.32 | 0.00 | 01-JAN-00:10 | 78924.11 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.09 | 0.25 | 18-JAN-13:50 | 8013.46 | 03-AUG-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.15 | 0.00 | 02-JAN-14:20 | 723.98 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.15 | 0.00 | 02-JAN-14:20 | 723.98 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.93 | 0.00 | 01-JAN-00:10 | 8013.46 | 03-AUG-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.93 | 0.00 | 01-JAN-00:10 | 8013.46 | 03-AUG-19:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7140.92 | 83010.36 | 09-JAN-05:00 | 376739.43 | 06-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7140.92 | 83010.36 | 09-JAN-05:00 | 376739.43 | 06-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7140.92 | 83010.36 | 09-JAN-05:00 | 376739.43 | 06-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 3317.63 | 0.00 | 01-JAN-00:40 | 2066678.92 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 463.31 | 0.00 | 01-JAN-00:10 | 57402.85 | 17-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57402.85 | 17-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57402.85 | 17-FEB-12:50 |
EnergyTransfer:HVAC | 9320.71 | 2844.21 | 10-JAN-22:10 | 2224629.88 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 2854.32 | 0.00 | 01-JAN-00:40 | 2048096.94 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 2854.32 | 0.00 | 01-JAN-00:40 | 2048096.94 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2854.32 | 0.00 | 01-JAN-00:40 | 2048096.94 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 6466.39 | 2353.84 | 10-JAN-22:00 | 2224629.88 | 07-SEP-15:00 |
EnergyTransfer:Plant | 14532.20 | 0.00 | 01-JAN-00:40 | 6440491.33 | 07-SEP-14:50 |
LoopToLoop:EnergyTransfer | 3567.42 | 0.00 | 01-JAN-00:10 | 2055847.35 | 07-SEP-14:50 |
WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57402.85 | 17-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57402.85 | 17-FEB-12:50 |
Boilers:EnergyTransfer | 2839.51 | 0.00 | 01-JAN-00:40 | 2049224.00 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 3587.26 | 0.00 | 01-JAN-00:10 | 2025736.79 | 07-SEP-14:50 |
HeatRejection:EnergyTransfer | 4074.70 | 0.00 | 01-JAN-00:10 | 2332831.08 | 07-SEP-14:50 |
General:HeatRejection:EnergyTransfer | 4074.70 | 0.00 | 01-JAN-00:10 | 2332831.08 | 07-SEP-14:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.271 | -583.064 | 0.000 | 0.000 | 93.559 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.202 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -513.830 | 0.000 | 0.000 | 83.529 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 36.476 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_MID | 0.000 | 0.000 | 8.435 | -3459.142 | 0.000 | 0.000 | 855.562 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1343.098 |
CORE_TOP | 0.000 | 0.000 | 24.871 | -282.667 | 0.000 | 0.000 | 89.144 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -225.172 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.350 | -54.232 | 0.000 | 0.000 | 10.928 | 7.620 | 36.365 | 28.023 | 0.000 | 0.082 | 57.194 | 0.000 | -78.959 | 0.000 | -10.372 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.438 | -55.596 | 0.000 | 0.000 | 6.995 | 4.863 | 23.435 | 65.464 | 0.000 | 0.054 | 8.055 | 0.000 | -48.797 | 0.000 | -6.912 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.457 | -101.635 | 0.000 | 0.000 | 10.761 | 7.498 | 36.366 | 142.390 | 0.000 | 0.077 | 0.001 | 0.000 | -72.012 | 0.000 | -10.502 | -16.399 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.664 | -84.516 | 0.000 | 0.000 | 6.843 | 4.871 | 23.435 | 61.328 | 0.000 | 0.051 | 50.730 | 0.000 | -55.860 | 0.000 | -7.546 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 213.607 | -351.301 | 0.000 | 0.000 | 114.817 | 76.082 | 363.654 | 293.644 | 0.000 | 1.947 | 223.311 | 0.000 | -720.443 | 0.000 | -215.319 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 118.954 | -460.413 | 0.000 | 0.000 | 53.072 | 48.583 | 234.352 | 656.264 | 0.000 | 1.201 | 0.035 | 0.000 | -457.701 | 0.000 | -148.414 | -45.899 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 124.372 | -908.464 | 0.000 | 0.000 | 109.826 | 74.926 | 363.660 | 1420.212 | 0.000 | 1.760 | 0.035 | 0.000 | -695.199 | 0.000 | -232.348 | -258.744 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 97.840 | -483.198 | 0.000 | 0.000 | 72.508 | 48.657 | 234.351 | 626.037 | 0.000 | 1.200 | 47.369 | 0.000 | -492.609 | 0.000 | -152.153 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 46.434 | -32.065 | 0.000 | 0.000 | 11.687 | 7.608 | 36.365 | 30.086 | 0.000 | 0.235 | 0.000 | 0.000 | -68.418 | 0.000 | -25.274 | -6.659 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 26.480 | -44.278 | 0.000 | 0.000 | 7.326 | 4.858 | 23.435 | 66.292 | 0.000 | 0.146 | 0.001 | 0.000 | -43.562 | 0.000 | -17.420 | -23.279 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 30.437 | -81.629 | 0.000 | 0.000 | 11.178 | 7.492 | 36.366 | 142.837 | 0.000 | 0.211 | 0.001 | 0.000 | -65.971 | 0.000 | -27.209 | -53.713 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 21.687 | -45.402 | 0.000 | 0.000 | 7.372 | 4.866 | 23.435 | 62.941 | 0.000 | 0.144 | 0.002 | 0.000 | -47.074 | 0.000 | -17.963 | -10.007 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.077 | -134.678 | 0.000 | 0.000 | 0.950 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.905 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 6.745 | -1137.318 | 0.000 | 0.000 | 9.533 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -434.524 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.154 | -101.932 | 0.000 | 0.000 | 0.960 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.738 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7140.926 | 0.000 | 0.000 | 20.390 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -407.175 |
GROUNDFLOOR_PLENUM | 5.598 | -41.011 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.154 | 57.446 | 0.000 | 0.000 | 0.000 | -22.187 | 0.000 |
MIDFLOOR_PLENUM | 160.518 | -220.229 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.852 | 429.236 | 0.000 | 0.000 | 0.000 | -372.377 | -0.002 |
TOPFLOOR_PLENUM | 59.503 | -41.468 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.242 | 20.674 | 0.000 | 0.000 | 0.000 | -38.951 | -0.003 |
Total Facility | 225.619 | -302.708 | 733.274 | -16056.287 | 0.000 | 0.000 | 1576.941 | 1717.464 | 14676.396 | 3595.520 | 0.000 | 10.356 | 930.566 | 0.000 | -2846.603 | 0.000 | -1304.947 | -2955.532 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-NOV-04:02 | 0.00 | 0.00 | 0.00 | -98705.87 | 0.00 | 0.00 | 0.00 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 84683.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 26-JUN-04:12 | 0.00 | 0.00 | 0.00 | -88403.81 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 81928.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-04:13 | 0.00 | 0.00 | 0.00 | -795093.47 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 730343.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-04:13 | 0.00 | 0.00 | 0.00 | -81026.17 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 74551.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-AUG-15:41 | 0.00 | 0.00 | 0.00 | -15342.22 | 0.00 | 0.00 | 40.42 | 30.32 | 720.18 | 5862.81 | 0.00 | 253.34 | 8435.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-07:31 | 0.00 | 0.00 | 0.00 | -25982.93 | 0.00 | 0.00 | 18.47 | 19.54 | 464.11 | 22539.17 | 0.00 | 0.00 | 3150.18 | 0.00 | -0.00 | 0.00 | -208.54 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:51 | 0.00 | 0.00 | 0.00 | -30227.28 | 0.00 | 0.00 | 27.16 | 30.33 | 720.19 | 35983.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -392.48 | -6141.83 |
PERIMETER_BOT_ZN_4 | 02-JUL-17:31 | 0.00 | 0.00 | 0.00 | -34095.86 | 0.00 | 0.00 | 0.00 | 19.54 | 360.35 | 23554.45 | 0.00 | 0.00 | 10245.70 | 0.00 | -0.00 | 0.00 | -84.17 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JUL-18:21 | 0.00 | 0.00 | 0.00 | -142792.78 | 0.00 | 0.00 | 0.00 | 303.25 | 5591.71 | 68833.66 | 0.00 | 0.00 | 69071.88 | 0.00 | -0.00 | 0.00 | -1007.70 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -295546.60 | 0.00 | 0.00 | 153.66 | 195.42 | 4641.14 | 201360.98 | 0.00 | 0.00 | 92418.26 | 0.00 | -0.00 | 0.00 | -3222.87 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-12:01 | 0.00 | 0.00 | 0.00 | -339217.44 | 0.00 | 0.00 | 247.39 | 303.26 | 7201.95 | 311364.76 | 0.00 | 1642.30 | 18457.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-18:21 | 0.00 | 0.00 | 0.00 | -313639.27 | 0.00 | 0.00 | 0.00 | 195.42 | 3603.49 | 211166.64 | 0.00 | 0.00 | 100378.49 | 0.00 | -0.00 | 0.00 | -1704.78 | 0.00 |
PERIMETER_TOP_ZN_3 | 03-SEP-15:31 | 0.00 | 0.00 | 0.00 | -17853.58 | 0.00 | 0.00 | 40.68 | 30.32 | 720.18 | 5098.26 | 0.00 | 705.81 | 11258.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:11 | 0.00 | 0.00 | 0.00 | -27079.07 | 0.00 | 0.00 | 19.50 | 19.54 | 464.11 | 20057.68 | 0.00 | 0.00 | 6915.06 | 0.00 | -0.00 | 0.00 | -396.82 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-12:51 | 0.00 | 0.00 | 0.00 | -36743.18 | 0.00 | 0.00 | 21.43 | 30.33 | 720.19 | 29735.58 | 0.00 | 330.72 | 5904.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-17:41 | 0.00 | 0.00 | 0.00 | -32305.98 | 0.00 | 0.00 | 0.00 | 19.54 | 360.35 | 22223.91 | 0.00 | 25.79 | 9676.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 22-APR-18:12 | 0.00 | 0.00 | 0.00 | -8412.58 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 610.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -78921.24 | 0.00 | 0.00 | 104.71 | 487.73 | 77944.22 | 0.00 | 0.00 | 0.00 | 384.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 03-AUG-19:00 | 0.00 | 0.00 | 0.00 | -8013.19 | 0.00 | 0.00 | 10.55 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 159.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 06-AUG-19:53 | 0.00 | 0.00 | 0.00 | -382099.50 | 0.00 | 0.00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 2307.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 07-AUG-19:30 | 0.00 | -12175.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 | 12148.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-04:01 | 0.00 | -150653.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182312.81 | 0.00 | -0.00 | 0.00 | -31659.40 | 0.00 |
TOPFLOOR_PLENUM | 25-JUL-16:38 | 0.00 | -23845.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.09 | 23619.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | -69958.60 | 0.00 | -1793389.29 | 0.00 | 0.00 | 16429.86 | 10223.35 | 616289.16 | 0.00 | 0.00 | 0.00 | 1306593.72 | 0.00 | -80524.31 | 0.00 | -5663.90 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-AUG-16:01 | 0.00 | 0.00 | 22417.44 | 0.00 | 0.00 | 0.00 | 520.13 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36960.32 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 484972.37 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -549722.20 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 71993.24 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78438.47 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 13235.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8284.48 | 0.00 | -842.16 | -4918.39 |
PERIMETER_BOT_ZN_2 | 11-JAN-04:01 | 0.00 | 0.00 | 15579.80 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5838.75 | 0.00 | -643.04 | -9619.55 |
PERIMETER_BOT_ZN_1 | 11-JAN-04:01 | 0.00 | 0.00 | 22411.43 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8706.24 | 0.00 | -959.27 | -13555.23 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 13724.53 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5564.90 | 0.00 | -578.41 | -8102.75 |
PERIMETER_MID_ZN_3 | 31-DEC-21:02 | 0.00 | 0.00 | 137664.41 | 0.00 | 0.00 | 0.00 | 0.00 | 637.34 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75878.57 | 0.00 | -19354.82 | -48660.07 |
PERIMETER_MID_ZN_2 | 09-JAN-02:31 | 0.00 | 0.00 | 207198.60 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53162.56 | 0.00 | -17775.07 | -141476.38 |
PERIMETER_MID_ZN_1 | 09-JAN-02:31 | 0.00 | 0.00 | 247603.93 | 0.00 | 0.00 | 0.00 | 0.00 | 637.36 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77836.88 | 0.00 | -26614.98 | -151245.16 |
PERIMETER_MID_ZN_4 | 09-JAN-02:31 | 0.00 | 0.00 | 210875.37 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52017.74 | 0.00 | -17879.46 | -146193.54 |
PERIMETER_TOP_ZN_3 | 30-JAN-05:31 | 0.00 | 0.00 | 17687.99 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5857.23 | 0.00 | -3786.38 | -8857.41 |
PERIMETER_TOP_ZN_2 | 06-MAR-03:21 | 0.00 | 0.00 | 22227.27 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4178.74 | 0.00 | -2221.46 | -16348.61 |
PERIMETER_TOP_ZN_1 | 06-MAR-03:21 | 0.00 | 0.00 | 27944.32 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6498.48 | 0.00 | -3326.03 | -18929.12 |
PERIMETER_TOP_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 24617.94 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5009.95 | 0.00 | -1577.15 | -18552.38 |
DATACENTER_BOT_ZN_6 | 09-JAN-03:35 | 0.00 | 0.00 | 627.45 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2584.19 |
DATACENTER_MID_ZN_6 | 29-JAN-18:40 | 0.00 | 0.00 | 6447.97 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26015.32 |
DATACENTER_TOP_ZN_6 | 30-APR-23:10 | 0.00 | 0.00 | 723.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2680.71 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-AUG-15:41 | 14277.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14810.63 |
MIDFLOOR_PLENUM | 09-JUL-16:31 | 149660.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3610.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -153271.41 |
TOPFLOOR_PLENUM | 11-JAN-05:11 | 34098.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1467.72 | -32630.51 |
Total Facility | 30-JAN-05:01 | -82970.52 | 93865.61 | 1440746.97 | -93865.61 | 0.00 | 0.00 | 0.00 | 18857.47 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -260531.45 | 0.00 | -201819.07 | -1146708.62 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.1132 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.0478 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 117.2263 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 92.4513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.1195 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7728 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5156 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5156 | 0.2176 | 1.0000 | Not calculated | 1.2002 | 0.2176 | ||
AIRLOOP DATACENTER BASEMENT | 24.3313 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.3314 | 0.0139 | 1.0000 | Not calculated | 0.3384 | 0.0139 | ||
AIRLOOP DATACENTER BOT | 0.5585 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5585 | 0.0280 | 1.0000 | Not calculated | 0.0156 | 0.0280 | ||
AIRLOOP DATACENTER MID | 5.3689 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.3689 | 0.0291 | 1.0000 | Not calculated | 0.1563 | 0.0291 | ||
AIRLOOP DATACENTER TOP | 0.5466 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5466 | 0.0286 | 1.0000 | Not calculated | 0.0156 | 0.0286 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.0566 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2826 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 58.6132 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8564 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.0598 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2991 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5156 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5156 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2176 | ||
AIRLOOP DATACENTER BASEMENT | 24.3313 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.3313 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0139 | ||
AIRLOOP DATACENTER BOT | 0.5585 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5585 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0280 | ||
AIRLOOP DATACENTER MID | 5.3689 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.3689 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0291 | ||
AIRLOOP DATACENTER TOP | 0.5466 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5466 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0286 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5156 | 5.5156 | 5.5156 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9777 | 5.9777 | 1.6140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.9183 | 55.9183 | 16.1604 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5391 | 5.5391 | 1.6174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0415 | 1.0415 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4711 | 1.4711 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7999 | 1.7999 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8229 | 1.8229 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.9236 | 9.9236 | 2.0343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.8193 | 15.8193 | 1.3130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.4882 | 18.4882 | 2.0337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.0770 | 17.0770 | 1.3149 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2059 | 1.2059 | 0.2159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5835 | 1.5835 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9868 | 1.9868 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8041 | 1.8041 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5585 | 0.5585 | 0.5585 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3689 | 5.3689 | 5.3689 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5466 | 0.5466 | 0.5466 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.3313 | 24.3313 | 24.3313 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.1132 | 10.0478 | 12.1132 | 2.2826 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 117.2263 | 92.4513 | 117.2263 | 22.8564 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.1195 | 10.7728 | 12.1195 | 2.2991 | 0.0000 | 1.0000 |
CAV_BAS | 5.5156 | 5.5156 | 5.5156 | 5.5156 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.3313 | 24.3314 | 24.3313 | 24.3313 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5585 | 0.5585 | 0.5585 | 0.5585 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.3689 | 5.3689 | 5.3689 | 5.3689 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5466 | 0.5466 | 0.5466 | 0.5466 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5156 | 5.5156 | 5.5156 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9888 | 2.9888 | 1.6140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.9591 | 27.9591 | 16.1604 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7696 | 2.7696 | 1.6174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5208 | 0.5208 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7356 | 0.7356 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9000 | 0.9000 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9115 | 0.9115 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9618 | 4.9618 | 2.0343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9096 | 7.9096 | 1.3130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2441 | 9.2441 | 2.0337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5385 | 8.5385 | 1.3149 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6029 | 0.6029 | 0.2159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7918 | 0.7918 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9934 | 0.9934 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9021 | 0.9021 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5585 | 0.5585 | 0.5585 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3689 | 5.3689 | 5.3689 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5466 | 0.5466 | 0.5466 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.3313 | 24.3313 | 24.3313 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.0566 | 2.2826 | 2.2826 | 2.2826 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 58.6132 | 22.8564 | 22.8564 | 22.8564 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.0598 | 2.2991 | 2.2991 | 2.2991 | 0.0000 | 1.0000 |
CAV_BAS | 5.5156 | 5.5156 | 5.5156 | 5.5156 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.3313 | 24.3313 | 24.3313 | 24.3313 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5585 | 0.5585 | 0.5585 | 0.5585 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.3689 | 5.3689 | 5.3689 | 5.3689 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5466 | 0.5466 | 0.5466 | 0.5466 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 123.67 |
Number of hours cooling loads not met | 380.67 |
Number of hours not met | 503.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3488.37 | 2364675.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1283.71 | 384328.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1717.46 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 268.57 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.36 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2505.09 | 315059.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 302.11 | 44235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 385.37 | 71995.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2431.85 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 821.13 | 87109.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 24774.25 |
Natural Gas | 0.00 | 4309.50 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 29083.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 475.57 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.08 |
Space Heating | 0.00 |
Space Cooling | 27.71 |
Fans (All) | 54.08 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 534.85 |
Subtotal | 534.85 |
Natural Gas [MJ/m2] | |
Space Heating | 75.31 |
Service Water Heating | 17.73 |
Miscellaneous (All) | 93.04 |
Subtotal | 93.04 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.91 |
Space Heating | 11.99 |
Space Cooling | 4.41 |
Fans (All) | 8.61 |
Service Water Heating | 2.82 |
Receptacle Equipment | 50.46 |
Miscellaneous | 15.79 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 649. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8667.83 | 92.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8722.83 | 37.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8504.67 | 250.17 | 5.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8717.33 | 42.67 | 0.00 | 0.00 | 0.00 |
Min | 8504.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 250.17 | 5.17 | 0.00 | 0.00 |
Average | 8727.31 | 32.46 | 0.22 | 0.00 | 0.00 |
Sum | 200728.17 | 746.67 | 5.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368450.33 | 165.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24900.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18352.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38917.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24904.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2265.83 | 2.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2267.83 | 0.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 99796.50 | 3576.83 | 21.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368450.33 | 3576.83 | 21.67 | 0.00 | 0.00 |
Average | 80169.69 | 164.28 | 0.94 | 0.00 | 0.00 |
Sum | 1843902.83 | 3778.50 | 21.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8687.83 | 72.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8724.67 | 35.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8689.50 | 70.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8728.33 | 31.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8562.83 | 197.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
Min | 8562.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 197.17 | 0.00 | 0.00 | 0.00 |
Average | 8730.01 | 29.99 | 0.00 | 0.00 | 0.00 |
Sum | 200790.33 | 689.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368379.17 | 236.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330752.00 | 61.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330723.00 | 90.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330765.00 | 48.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24900.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18352.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24904.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 100528.00 | 2867.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368379.17 | 2867.00 | 0.00 | 0.00 | 0.00 |
Average | 80190.62 | 144.29 | 0.00 | 0.00 | 0.00 |
Sum | 1844384.33 | 3318.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437187E+11 | 96452.09 | 02-JAN-04:11 | -0.4 | -2.9 | 0.515784E+10 | 7499.21 | 13-JAN-14:30 | 8.90 | 4.37 |
February | 0.382385E+11 | 96795.76 | 21-FEB-05:11 | 7.43 | 1.21 | 0.490916E+10 | 7499.13 | 23-FEB-10:39 | -5.6 | -6.9 |
March | 0.464556E+11 | 93903.40 | 27-MAR-03:31 | 1.47 | -1.7 | 0.609595E+10 | 7499.17 | 07-MAR-10:39 | 1.47 | -1.7 |
April | 0.449699E+11 | 96853.90 | 10-APR-04:11 | 4.23 | 0.21 | 0.544425E+10 | 7499.17 | 04-APR-09:09 | 4.23 | 0.21 |
May | 0.467609E+11 | 94436.66 | 22-MAY-03:02 | 0.50 | 0.24 | 0.589843E+10 | 7499.53 | 02-MAY-13:09 | 0.50 | 0.24 |
June | 0.512564E+11 | 96838.95 | 05-JUN-04:12 | 8.33 | 5.29 | 0.588526E+10 | 7783.12 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.539742E+11 | 95749.20 | 05-JUL-04:12 | 9.40 | 8.79 | 0.549981E+10 | 7959.17 | 03-JUL-09:09 | 9.40 | 8.79 |
August | 0.596758E+11 | 98495.15 | 28-AUG-04:11 | 8.67 | 4.95 | 0.615465E+10 | 8096.44 | 07-AUG-13:30 | 8.67 | 4.95 |
September | 0.508859E+11 | 96613.52 | 18-SEP-04:11 | 3.90 | 1.62 | 0.545308E+10 | 7601.94 | 05-SEP-13:30 | 3.90 | 1.62 |
October | 0.520263E+11 | 98217.59 | 10-OCT-03:01 | -4.1 | -4.8 | 0.566804E+10 | 7499.23 | 18-OCT-13:20 | 24.60 | 11.01 |
November | 0.478925E+11 | 98717.11 | 06-NOV-04:02 | -2.8 | -3.9 | 0.560943E+10 | 7499.15 | 28-NOV-10:20 | -4.0 | -4.8 |
December | 0.472116E+11 | 96275.30 | 11-DEC-04:01 | -2.6 | -4.7 | 0.535202E+10 | 7499.18 | 07-DEC-10:20 | -2.6 | -4.7 |
Annual Sum or Average | 0.583066E+12 | 0.671279E+11 | ||||||||
Minimum of Months | 0.382385E+11 | 93903.40 | -4.1 | -4.8 | 0.490916E+10 | 7499.13 | -5.6 | -6.9 | ||
Maximum of Months | 0.596758E+11 | 98717.11 | 9.40 | 8.79 | 0.615465E+10 | 8096.44 | 27.48 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251656E+11 | 78491.27 | 02-JAN-05:01 | -0.2 | -2.7 | 0.492305E+10 | 6734.79 | 26-JAN-10:20 | -22.0 | -22.6 |
February | 0.276218E+11 | 78289.23 | 27-FEB-05:11 | 4.07 | 0.00 | 0.456196E+10 | 6734.77 | 23-FEB-10:39 | 4.07 | 0.00 |
March | 0.405687E+11 | 78129.29 | 20-MAR-04:01 | -1.1 | -3.1 | 0.549224E+10 | 6734.78 | 01-MAR-10:09 | -1.1 | -3.1 |
April | 0.452179E+11 | 83759.74 | 10-APR-04:12 | 4.23 | 0.21 | 0.488350E+10 | 6734.77 | 04-APR-09:09 | 4.23 | 0.21 |
May | 0.417113E+11 | 83868.97 | 30-MAY-04:13 | 15.60 | 10.93 | 0.528841E+10 | 6735.26 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.510783E+11 | 88403.68 | 26-JUN-04:12 | 12.73 | 10.54 | 0.528282E+10 | 7398.57 | 20-JUN-13:09 | 12.73 | 10.54 |
July | 0.576698E+11 | 85567.67 | 05-JUL-04:12 | 9.40 | 8.79 | 0.493658E+10 | 7400.01 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.638182E+11 | 84630.16 | 07-AUG-04:23 | 18.90 | 10.50 | 0.553537E+10 | 7506.87 | 07-AUG-13:39 | 32.80 | 15.78 |
September | 0.444476E+11 | 84241.05 | 11-SEP-04:12 | 11.10 | 10.17 | 0.488251E+10 | 6761.03 | 01-SEP-13:00 | 11.10 | 10.17 |
October | 0.426370E+11 | 81802.98 | 02-OCT-04:11 | 4.80 | 2.84 | 0.507904E+10 | 6734.77 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.388232E+11 | 80824.83 | 06-NOV-04:02 | -2.8 | -3.9 | 0.502699E+10 | 6734.78 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.350715E+11 | 78174.79 | 11-DEC-05:01 | -1.6 | -4.2 | 0.488718E+10 | 6734.83 | 07-DEC-10:20 | -1.6 | -4.2 |
Annual Sum or Average | 0.513831E+12 | 0.607796E+11 | ||||||||
Minimum of Months | 0.251656E+11 | 78129.29 | -2.8 | -4.2 | 0.456196E+10 | 6734.77 | -22.0 | -22.6 | ||
Maximum of Months | 0.638182E+11 | 88403.68 | 18.90 | 10.93 | 0.553537E+10 | 7506.87 | 32.80 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174770E+11 | 14062.06 | 19-JAN-17:00 | -6.7 | -8.2 | 0.433028E+10 | 6478.09 | 19-JAN-14:00 | -6.7 | -8.2 |
February | 0.179124E+11 | 25825.81 | 28-FEB-17:00 | 10.00 | 4.31 | 0.419294E+10 | 6734.72 | 28-FEB-10:20 | 10.00 | 4.31 |
March | 0.247334E+11 | 52158.90 | 24-MAR-05:02 | -0.6 | -2.5 | 0.530091E+10 | 6734.76 | 01-MAR-10:09 | -0.6 | -2.5 |
April | 0.271602E+11 | 68792.23 | 26-APR-05:03 | 5.37 | 2.97 | 0.483362E+10 | 6734.76 | 04-APR-09:09 | 5.37 | 2.97 |
May | 0.307866E+11 | 72078.13 | 30-MAY-04:12 | 15.60 | 10.93 | 0.525198E+10 | 6735.28 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.393220E+11 | 73029.22 | 22-JUN-04:12 | 16.10 | 12.27 | 0.527176E+10 | 7232.50 | 20-JUN-13:09 | 16.10 | 12.27 |
July | 0.416664E+11 | 73617.91 | 05-JUL-04:12 | 9.40 | 8.79 | 0.490442E+10 | 7268.76 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.430028E+11 | 75200.68 | 14-AUG-04:12 | 12.20 | 9.88 | 0.550699E+10 | 7102.70 | 07-AUG-13:00 | 12.20 | 9.88 |
September | 0.342956E+11 | 79513.80 | 05-SEP-04:13 | 18.30 | 11.92 | 0.486819E+10 | 6735.06 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.281190E+11 | 69110.48 | 19-OCT-05:03 | 12.20 | 5.54 | 0.503369E+10 | 6734.78 | 19-OCT-13:20 | 21.10 | 10.10 |
November | 0.223801E+11 | 64004.73 | 08-NOV-06:02 | 10.13 | 4.88 | 0.482238E+10 | 6734.76 | 03-NOV-09:09 | 10.13 | 4.88 |
December | 0.190599E+11 | 20095.87 | 07-DEC-16:20 | 5.93 | 1.89 | 0.443509E+10 | 6734.63 | 12-DEC-14:39 | -2.4 | -5.4 |
Annual Sum or Average | 0.345915E+12 | 0.587523E+11 | ||||||||
Minimum of Months | 0.174770E+11 | 14062.06 | -6.7 | -8.2 | 0.419294E+10 | 6478.09 | -6.7 | -8.2 | ||
Maximum of Months | 0.430028E+11 | 79513.80 | 18.30 | 12.27 | 0.550699E+10 | 7268.76 | 27.33 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.926011E+10 | 13091.56 | 13-JAN-17:00 | 7.80 | 3.93 | 0.386779E+10 | 5984.33 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.117076E+11 | 17676.34 | 28-FEB-17:00 | 10.00 | 4.31 | 0.371656E+10 | 6516.12 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.169954E+11 | 21265.41 | 29-MAR-16:00 | 12.20 | 4.07 | 0.476304E+10 | 6734.56 | 29-MAR-13:20 | 12.20 | 4.07 |
April | 0.204820E+11 | 34335.07 | 25-APR-16:00 | 17.80 | 7.70 | 0.455231E+10 | 6734.72 | 25-APR-09:20 | 17.80 | 7.70 |
May | 0.264618E+11 | 67820.63 | 30-MAY-05:03 | 15.60 | 11.34 | 0.503937E+10 | 6735.31 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.384254E+11 | 73491.50 | 21-JUN-04:12 | 17.40 | 12.31 | 0.525126E+10 | 7350.43 | 20-JUN-13:09 | 17.40 | 12.31 |
July | 0.427256E+11 | 79823.74 | 17-JUL-04:13 | 16.10 | 11.78 | 0.491541E+10 | 7433.62 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.417461E+11 | 71841.18 | 08-AUG-04:12 | 17.97 | 11.68 | 0.550084E+10 | 7469.73 | 07-AUG-13:00 | 17.97 | 11.68 |
September | 0.293948E+11 | 81030.92 | 05-SEP-04:13 | 18.30 | 11.92 | 0.475094E+10 | 6738.61 | 01-SEP-13:00 | 18.30 | 11.92 |
October | 0.200130E+11 | 31696.72 | 18-OCT-16:00 | 24.40 | 11.02 | 0.469631E+10 | 6734.73 | 13-OCT-09:20 | 24.40 | 11.02 |
November | 0.144865E+11 | 18883.45 | 03-NOV-16:00 | 14.30 | 7.69 | 0.424240E+10 | 6734.38 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.109718E+11 | 13991.61 | 06-DEC-16:50 | 7.15 | 2.74 | 0.386792E+10 | 6414.06 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.282670E+12 | 0.551642E+11 | ||||||||
Minimum of Months | 0.926011E+10 | 13091.56 | 7.15 | 2.74 | 0.371656E+10 | 5984.33 | 7.80 | 2.55 | ||
Maximum of Months | 0.427256E+11 | 81030.92 | 24.40 | 12.31 | 0.550084E+10 | 7469.73 | 33.90 | 15.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.933058E+09 | 2035.15 | 02-JAN-05:01 | -0.2 | -2.7 | 0.496602E+09 | 822.83 | 02-JAN-14:50 | 6.20 | 1.19 |
February | 0.155936E+10 | 3974.19 | 27-FEB-16:00 | 18.90 | 7.06 | 0.487881E+09 | 845.61 | 27-FEB-10:20 | 18.90 | 7.06 |
March | 0.279384E+10 | 4745.75 | 27-MAR-14:00 | 8.90 | 2.28 | 0.643102E+09 | 845.62 | 14-MAR-09:00 | 8.90 | 2.28 |
April | 0.408928E+10 | 6921.52 | 07-APR-14:00 | 23.30 | 9.68 | 0.598763E+09 | 845.63 | 13-APR-13:20 | 12.97 | 7.01 |
May | 0.493916E+10 | 10363.24 | 30-MAY-05:03 | 15.60 | 11.34 | 0.652063E+09 | 845.69 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.814662E+10 | 15275.94 | 25-JUN-19:01 | 21.42 | 13.81 | 0.663009E+09 | 944.39 | 20-JUN-13:09 | 21.42 | 13.81 |
July | 0.969652E+10 | 15206.08 | 02-JUL-18:51 | 23.90 | 14.41 | 0.624222E+09 | 970.93 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.939087E+10 | 15342.10 | 06-AUG-15:41 | 35.40 | 16.19 | 0.696498E+09 | 977.13 | 07-AUG-13:50 | 32.80 | 15.88 |
September | 0.509398E+10 | 13115.71 | 04-SEP-16:02 | 32.80 | 16.54 | 0.605797E+09 | 849.62 | 01-SEP-13:00 | 32.80 | 16.54 |
October | 0.347357E+10 | 5555.97 | 19-OCT-14:30 | 21.40 | 10.24 | 0.618542E+09 | 845.63 | 18-OCT-13:39 | 21.40 | 10.24 |
November | 0.242407E+10 | 3804.96 | 08-NOV-13:30 | 13.80 | 7.89 | 0.579614E+09 | 845.62 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.169200E+10 | 2386.82 | 06-DEC-13:30 | 12.25 | 6.08 | 0.525110E+09 | 845.61 | 05-DEC-14:09 | 12.25 | 6.08 |
Annual Sum or Average | 0.542323E+11 | 0.719120E+10 | ||||||||
Minimum of Months | 0.933058E+09 | 2035.15 | -0.2 | -2.7 | 0.487881E+09 | 822.83 | 6.20 | 1.19 | ||
Maximum of Months | 0.969652E+10 | 15342.10 | 35.40 | 16.54 | 0.696498E+09 | 977.13 | 33.90 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.728796E+09 | 3215.47 | 17-JAN-10:05 | 4.68 | 0.96 | 0.332043E+09 | 544.95 | 19-JAN-10:00 | -11.1 | -11.8 |
February | 0.149829E+10 | 9189.53 | 26-FEB-09:33 | 9.27 | 2.86 | 0.328579E+09 | 544.95 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.288442E+10 | 11272.19 | 28-MAR-09:15 | 5.73 | 0.86 | 0.421175E+09 | 544.96 | 06-MAR-10:09 | 5.73 | 0.86 |
April | 0.441786E+10 | 18902.91 | 16-APR-08:52 | 12.20 | 5.44 | 0.385017E+09 | 546.13 | 24-APR-09:30 | 13.05 | 8.33 |
May | 0.560861E+10 | 13727.94 | 19-MAY-08:30 | 16.95 | 11.09 | 0.421641E+09 | 545.73 | 19-MAY-09:09 | 18.17 | 11.56 |
June | 0.862954E+10 | 24362.35 | 11-JUN-09:01 | 19.37 | 11.25 | 0.427615E+09 | 663.98 | 22-JUN-09:50 | 25.32 | 16.54 |
July | 0.103366E+11 | 25985.00 | 02-JUL-07:31 | 19.47 | 14.13 | 0.401674E+09 | 706.78 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.954666E+10 | 24251.08 | 06-AUG-08:21 | 25.25 | 14.09 | 0.448439E+09 | 671.76 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.551781E+10 | 24112.59 | 04-SEP-08:61 | 25.78 | 14.40 | 0.392729E+09 | 547.98 | 01-SEP-13:00 | 25.78 | 14.40 |
October | 0.348184E+10 | 16394.51 | 15-OCT-08:53 | 12.80 | 6.63 | 0.402258E+09 | 544.96 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.185930E+10 | 7215.92 | 06-NOV-09:25 | 0.80 | -1.3 | 0.378598E+09 | 544.95 | 03-NOV-09:09 | 0.80 | -1.3 |
December | 0.108621E+10 | 3376.00 | 20-DEC-10:05 | 3.48 | -0.5 | 0.341630E+09 | 544.95 | 01-DEC-10:39 | 3.48 | -0.5 |
Annual Sum or Average | 0.555959E+11 | 0.468140E+10 | ||||||||
Minimum of Months | 0.728796E+09 | 3215.47 | 0.80 | -1.3 | 0.328579E+09 | 544.95 | -11.1 | -11.8 | ||
Maximum of Months | 0.103366E+11 | 25985.00 | 25.78 | 14.40 | 0.448439E+09 | 706.78 | 30.60 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297500E+10 | 25283.36 | 01-JAN-12:43 | 7.70 | 2.79 | 0.542661E+09 | 845.64 | 06-JAN-14:20 | -14.4 | -15.9 |
February | 0.544792E+10 | 29092.79 | 26-FEB-13:32 | 15.40 | 5.68 | 0.533056E+09 | 848.55 | 27-FEB-14:09 | 18.40 | 7.06 |
March | 0.735108E+10 | 29277.50 | 26-MAR-13:12 | 9.27 | 1.72 | 0.653046E+09 | 864.55 | 01-MAR-14:09 | 9.27 | 1.72 |
April | 0.755838E+10 | 27101.14 | 16-APR-12:52 | 18.30 | 7.69 | 0.593786E+09 | 846.56 | 05-APR-13:00 | 18.30 | 7.69 |
May | 0.760771E+10 | 24396.57 | 14-MAY-14:02 | 16.70 | 6.66 | 0.645111E+09 | 846.42 | 19-MAY-13:50 | 27.02 | 15.00 |
June | 0.104399E+11 | 27314.62 | 11-JUN-13:02 | 25.82 | 13.32 | 0.662618E+09 | 1006.14 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.132319E+11 | 28192.21 | 09-JUL-13:22 | 26.95 | 12.75 | 0.627918E+09 | 1043.77 | 31-JUL-13:00 | 30.60 | 14.62 |
August | 0.151275E+11 | 28205.53 | 06-AUG-13:42 | 34.32 | 15.27 | 0.710809E+09 | 1127.96 | 07-AUG-13:39 | 32.80 | 15.78 |
September | 0.114337E+11 | 29799.77 | 03-SEP-13:01 | 33.40 | 15.99 | 0.610966E+09 | 1029.34 | 01-SEP-13:00 | 33.40 | 15.99 |
October | 0.970624E+10 | 30228.70 | 15-OCT-12:51 | 22.20 | 10.64 | 0.624844E+09 | 1007.95 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.652660E+10 | 27296.53 | 12-NOV-12:52 | -1.7 | -4.4 | 0.597270E+09 | 862.23 | 03-NOV-13:20 | -1.7 | -4.4 |
December | 0.422987E+10 | 17185.04 | 12-DEC-12:30 | -2.8 | -5.7 | 0.557040E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.101636E+12 | 0.735913E+10 | ||||||||
Minimum of Months | 0.297500E+10 | 17185.04 | -2.8 | -5.7 | 0.533056E+09 | 845.64 | -14.4 | -15.9 | ||
Maximum of Months | 0.151275E+11 | 30228.70 | 34.32 | 15.99 | 0.710809E+09 | 1127.96 | 33.40 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116531E+10 | 5666.11 | 13-JAN-15:30 | 9.45 | 4.93 | 0.346913E+09 | 544.95 | 13-JAN-14:30 | 9.45 | 4.93 |
February | 0.273740E+10 | 19271.85 | 26-FEB-16:12 | 15.93 | 6.13 | 0.350269E+09 | 544.95 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.527187E+10 | 17415.64 | 12-MAR-16:02 | 5.92 | -0.8 | 0.440467E+09 | 544.95 | 01-MAR-10:09 | 5.92 | -0.8 |
April | 0.824913E+10 | 30320.35 | 16-APR-16:51 | 20.00 | 8.97 | 0.395812E+09 | 544.96 | 13-APR-13:39 | 20.00 | 8.97 |
May | 0.752632E+10 | 29214.70 | 28-MAY-17:21 | 20.55 | 10.38 | 0.426184E+09 | 545.00 | 02-MAY-13:09 | 20.55 | 10.38 |
June | 0.110723E+11 | 33102.35 | 18-JUN-17:21 | 25.30 | 14.49 | 0.428595E+09 | 601.32 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.138173E+11 | 34095.61 | 02-JUL-17:31 | 25.60 | 14.12 | 0.402449E+09 | 648.39 | 25-JUL-15:00 | 33.90 | 15.43 |
August | 0.146313E+11 | 31046.24 | 06-AUG-16:21 | 35.30 | 16.02 | 0.450595E+09 | 662.98 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.719605E+10 | 28265.49 | 04-SEP-16:41 | 32.80 | 16.72 | 0.395281E+09 | 575.34 | 01-SEP-15:00 | 32.80 | 16.72 |
October | 0.561443E+10 | 27802.26 | 15-OCT-15:31 | 22.40 | 10.89 | 0.409919E+09 | 544.97 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.415981E+10 | 11472.97 | 08-NOV-06:02 | 10.13 | 4.88 | 0.402402E+09 | 544.96 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.307579E+10 | 9507.79 | 06-DEC-15:30 | 10.25 | 4.94 | 0.384897E+09 | 544.96 | 07-DEC-10:20 | 3.90 | 1.50 |
Annual Sum or Average | 0.845170E+11 | 0.483378E+10 | ||||||||
Minimum of Months | 0.116531E+10 | 5666.11 | 5.92 | -0.8 | 0.346913E+09 | 544.95 | 2.03 | -0.8 | ||
Maximum of Months | 0.146313E+11 | 34095.61 | 35.30 | 16.72 | 0.450595E+09 | 662.98 | 33.90 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49998257.78 | 1182.00 | 13-JAN-15:00 | 10.00 | 5.18 | 0.462231E+09 | 627.32 | 13-JAN-14:00 | 10.00 | 5.18 |
February | 0.469978E+09 | 2123.60 | 27-FEB-14:10 | 18.40 | 7.06 | 0.430470E+09 | 761.78 | 27-FEB-16:19 | 16.67 | 6.71 |
March | 0.130576E+10 | 2184.95 | 23-MAR-13:40 | 9.80 | 2.29 | 0.547771E+09 | 822.61 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.213260E+10 | 5152.64 | 07-APR-14:30 | 22.50 | 9.29 | 0.541154E+09 | 845.62 | 06-APR-13:20 | 22.50 | 9.29 |
May | 0.347930E+10 | 7160.12 | 19-MAY-16:00 | 27.80 | 14.54 | 0.614032E+09 | 845.69 | 02-MAY-13:09 | 27.80 | 14.54 |
June | 0.645432E+10 | 11106.92 | 21-JUN-05:02 | 15.87 | 11.84 | 0.657434E+09 | 926.62 | 20-JUN-13:09 | 15.87 | 11.84 |
July | 0.762100E+10 | 14280.23 | 02-JUL-18:21 | 24.75 | 14.30 | 0.617752E+09 | 922.68 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.654745E+10 | 13187.90 | 06-AUG-16:41 | 35.10 | 15.80 | 0.687758E+09 | 942.67 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.376866E+10 | 14108.78 | 04-SEP-13:31 | 30.37 | 15.75 | 0.579679E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.206861E+10 | 4158.85 | 19-OCT-14:30 | 21.40 | 10.24 | 0.557530E+09 | 845.63 | 19-OCT-13:20 | 21.40 | 10.24 |
November | 0.101362E+10 | 2135.04 | 03-NOV-14:10 | 14.93 | 7.82 | 0.491906E+09 | 804.61 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.219043E+09 | 1324.25 | 06-DEC-15:50 | 9.68 | 4.65 | 0.449990E+09 | 672.91 | 06-DEC-14:00 | 9.68 | 4.65 |
Annual Sum or Average | 0.351303E+11 | 0.663771E+10 | ||||||||
Minimum of Months | 49998257.78 | 1182.00 | 9.68 | 2.29 | 0.430470E+09 | 627.32 | 9.68 | 4.50 | ||
Maximum of Months | 0.762100E+10 | 14280.23 | 35.10 | 15.80 | 0.687758E+09 | 942.67 | 32.80 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134124E+09 | 1036.30 | 20-JAN-11:05 | -1.9 | -4.9 | 0.219783E+09 | 482.16 | 20-JAN-11:09 | -1.9 | -4.9 |
February | 0.593288E+09 | 6413.09 | 27-FEB-11:05 | 14.68 | 5.50 | 0.220000E+09 | 548.49 | 28-FEB-11:09 | 4.37 | 1.41 |
March | 0.159882E+10 | 10885.68 | 28-MAR-10:05 | 7.38 | 1.58 | 0.285584E+09 | 548.50 | 22-MAR-10:09 | 7.38 | 1.58 |
April | 0.330703E+10 | 17526.04 | 16-APR-08:32 | 11.47 | 4.88 | 0.270677E+09 | 548.50 | 12-APR-10:09 | 11.47 | 4.88 |
May | 0.477504E+10 | 14701.29 | 19-MAY-08:50 | 17.52 | 11.29 | 0.302567E+09 | 548.55 | 02-MAY-12:09 | 17.52 | 11.29 |
June | 0.834395E+10 | 26347.42 | 11-JUN-09:11 | 19.83 | 11.39 | 0.314112E+09 | 638.99 | 22-JUN-10:20 | 26.13 | 16.61 |
July | 0.102151E+11 | 29551.98 | 02-JUL-09:01 | 22.48 | 15.33 | 0.295719E+09 | 666.75 | 14-JUL-08:00 | 25.00 | 16.36 |
August | 0.895102E+10 | 26529.64 | 06-AUG-08:41 | 26.55 | 14.17 | 0.328910E+09 | 642.00 | 07-AUG-10:20 | 30.60 | 15.25 |
September | 0.481761E+10 | 26650.20 | 04-SEP-08:51 | 26.70 | 14.88 | 0.284115E+09 | 549.06 | 01-SEP-14:09 | 26.70 | 14.88 |
October | 0.228432E+10 | 10697.33 | 18-OCT-10:05 | 20.28 | 8.90 | 0.284040E+09 | 548.50 | 27-OCT-10:09 | 10.18 | 4.94 |
November | 0.793415E+09 | 6732.11 | 03-NOV-10:05 | 9.10 | 5.57 | 0.251879E+09 | 548.50 | 03-NOV-10:09 | 9.10 | 5.57 |
December | 0.227386E+09 | 1112.93 | 07-DEC-11:10 | 6.38 | 2.62 | 0.217080E+09 | 510.44 | 07-DEC-11:09 | 6.38 | 2.62 |
Annual Sum or Average | 0.460411E+11 | 0.327447E+10 | ||||||||
Minimum of Months | 0.134124E+09 | 1036.30 | -1.9 | -4.9 | 0.217080E+09 | 482.16 | -1.9 | -4.9 | ||
Maximum of Months | 0.102151E+11 | 29551.98 | 26.70 | 15.33 | 0.328910E+09 | 666.75 | 30.60 | 16.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226110E+10 | 17887.46 | 15-JAN-13:13 | 5.20 | -0.5 | 0.519409E+09 | 845.64 | 06-JAN-14:30 | 5.20 | -0.5 |
February | 0.481701E+10 | 31097.76 | 26-FEB-13:51 | 15.60 | 5.76 | 0.514471E+09 | 876.32 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.640401E+10 | 27941.02 | 26-MAR-13:22 | 9.45 | 1.83 | 0.619807E+09 | 897.41 | 01-MAR-14:09 | 9.45 | 1.83 |
April | 0.629011E+10 | 28019.31 | 16-APR-13:52 | 19.40 | 8.41 | 0.566769E+09 | 846.72 | 05-APR-13:20 | 19.40 | 8.41 |
May | 0.686887E+10 | 25064.85 | 14-MAY-13:53 | 16.70 | 6.76 | 0.626954E+09 | 847.38 | 19-MAY-13:20 | 26.47 | 14.93 |
June | 0.944442E+10 | 28085.27 | 11-JUN-13:12 | 25.53 | 13.23 | 0.657389E+09 | 1002.74 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.120076E+11 | 29011.87 | 09-JUL-13:52 | 27.20 | 12.79 | 0.621910E+09 | 1055.77 | 31-JUL-13:00 | 30.60 | 14.62 |
August | 0.136421E+11 | 28978.96 | 20-AUG-13:32 | 20.53 | 12.72 | 0.701671E+09 | 1137.27 | 07-AUG-13:00 | 20.53 | 12.72 |
September | 0.114467E+11 | 33922.01 | 03-SEP-12:01 | 32.88 | 15.93 | 0.601745E+09 | 1049.41 | 01-SEP-13:00 | 32.88 | 15.93 |
October | 0.932523E+10 | 31950.55 | 15-OCT-13:31 | 22.93 | 11.00 | 0.611603E+09 | 1009.28 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.557131E+10 | 30044.38 | 11-NOV-14:02 | -0.1 | -2.9 | 0.572226E+09 | 880.31 | 03-NOV-13:39 | -0.1 | -2.9 |
December | 0.276884E+10 | 15654.94 | 12-DEC-12:40 | -2.8 | -5.7 | 0.523236E+09 | 845.64 | 07-DEC-10:30 | -2.8 | -5.7 |
Annual Sum or Average | 0.908473E+11 | 0.713719E+10 | ||||||||
Minimum of Months | 0.226110E+10 | 15654.94 | -2.8 | -5.7 | 0.514471E+09 | 845.64 | -2.8 | -5.7 | ||
Maximum of Months | 0.136421E+11 | 33922.01 | 32.88 | 15.93 | 0.701671E+09 | 1137.27 | 32.88 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233320E+09 | 2514.45 | 13-JAN-15:40 | 9.27 | 4.85 | 0.306810E+09 | 530.91 | 13-JAN-14:00 | 9.27 | 4.85 |
February | 0.940654E+09 | 11376.94 | 26-FEB-16:32 | 15.77 | 6.02 | 0.297576E+09 | 544.94 | 28-FEB-14:20 | 10.20 | 4.61 |
March | 0.198947E+10 | 11658.50 | 28-MAR-17:00 | 10.60 | 2.97 | 0.376488E+09 | 544.95 | 02-MAR-14:50 | 10.60 | 2.97 |
April | 0.352718E+10 | 26571.85 | 16-APR-17:12 | 19.80 | 8.90 | 0.363996E+09 | 544.95 | 17-APR-09:09 | 11.47 | 6.52 |
May | 0.547931E+10 | 27561.89 | 28-MAY-17:41 | 20.18 | 10.35 | 0.404876E+09 | 545.00 | 02-MAY-13:09 | 20.18 | 10.35 |
June | 0.803047E+10 | 27835.01 | 18-JUN-17:31 | 25.20 | 14.48 | 0.424689E+09 | 608.51 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.966155E+10 | 31372.75 | 02-JUL-18:21 | 24.75 | 14.30 | 0.399078E+09 | 635.83 | 31-JUL-15:00 | 31.10 | 14.09 |
August | 0.866503E+10 | 27137.06 | 05-AUG-18:21 | 33.60 | 16.58 | 0.445401E+09 | 636.89 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.520460E+10 | 30105.68 | 04-SEP-16:51 | 32.80 | 16.77 | 0.381341E+09 | 584.16 | 01-SEP-15:00 | 32.80 | 16.77 |
October | 0.281772E+10 | 22007.78 | 15-OCT-16:12 | 21.83 | 10.69 | 0.377077E+09 | 544.96 | 19-OCT-13:20 | 21.10 | 10.10 |
November | 0.132272E+10 | 7161.44 | 03-NOV-15:40 | 14.40 | 7.69 | 0.342371E+09 | 544.94 | 14-NOV-14:30 | 9.15 | 1.19 |
December | 0.448914E+09 | 3829.08 | 06-DEC-15:40 | 9.97 | 4.80 | 0.306311E+09 | 544.93 | 06-DEC-14:39 | 9.97 | 4.80 |
Annual Sum or Average | 0.483209E+11 | 0.442601E+10 | ||||||||
Minimum of Months | 0.233320E+09 | 2514.45 | 9.27 | 2.97 | 0.297576E+09 | 530.91 | 9.15 | 1.19 | ||
Maximum of Months | 0.966155E+10 | 31372.75 | 33.60 | 16.77 | 0.445401E+09 | 636.89 | 32.80 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18084540.74 | 1174.06 | 14-JAN-17:03 | 8.90 | 4.06 | 0.458617E+09 | 626.05 | 09-JAN-14:50 | 8.90 | 4.06 |
February | 0.194178E+09 | 1948.89 | 27-FEB-13:30 | 17.75 | 6.76 | 0.423480E+09 | 720.37 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.776590E+09 | 2044.43 | 23-MAR-13:30 | 9.70 | 2.18 | 0.522517E+09 | 769.54 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.161173E+10 | 5017.63 | 07-APR-14:30 | 22.50 | 9.29 | 0.507816E+09 | 845.61 | 25-APR-13:20 | 16.50 | 7.26 |
May | 0.314074E+10 | 7945.37 | 19-MAY-16:00 | 27.80 | 14.54 | 0.589036E+09 | 845.63 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.641046E+10 | 11706.36 | 25-JUN-16:51 | 23.90 | 12.91 | 0.647415E+09 | 907.64 | 20-JUN-13:09 | 23.90 | 12.91 |
July | 0.787650E+10 | 17743.53 | 30-JUL-16:21 | 30.85 | 14.76 | 0.615549E+09 | 955.42 | 25-JUL-13:00 | 30.85 | 14.76 |
August | 0.657897E+10 | 17065.86 | 06-AUG-18:02 | 32.85 | 14.96 | 0.677346E+09 | 933.55 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.343621E+10 | 17854.06 | 03-SEP-15:31 | 33.67 | 16.05 | 0.555897E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.145826E+10 | 3643.33 | 19-OCT-14:40 | 21.50 | 10.24 | 0.519003E+09 | 845.62 | 19-OCT-13:20 | 21.50 | 10.24 |
November | 0.484879E+09 | 1913.15 | 03-NOV-13:30 | 14.35 | 7.74 | 0.468903E+09 | 736.53 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 78434846.79 | 1289.16 | 06-DEC-16:00 | 9.40 | 4.51 | 0.446484E+09 | 635.87 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.320650E+11 | 0.643206E+10 | ||||||||
Minimum of Months | 18084540.74 | 1174.06 | 8.90 | 2.18 | 0.423480E+09 | 626.05 | 8.90 | 4.06 | ||
Maximum of Months | 0.787650E+10 | 17854.06 | 33.67 | 16.05 | 0.677346E+09 | 955.42 | 32.80 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81984544.59 | 925.98 | 31-JAN-10:50 | -5.4 | -8.1 | 0.299649E+09 | 457.17 | 31-JAN-10:50 | -5.4 | -8.1 |
February | 0.449720E+09 | 3545.14 | 28-FEB-10:20 | 2.03 | 0.11 | 0.289497E+09 | 544.95 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.124835E+10 | 7626.75 | 28-MAR-09:40 | 6.47 | 1.20 | 0.374513E+09 | 544.95 | 22-MAR-09:00 | 6.47 | 1.20 |
April | 0.282434E+10 | 12101.01 | 25-APR-09:20 | 10.33 | 5.07 | 0.355054E+09 | 544.96 | 25-APR-09:09 | 10.33 | 5.07 |
May | 0.450359E+10 | 14221.57 | 19-MAY-08:50 | 17.52 | 11.29 | 0.404429E+09 | 544.99 | 02-MAY-13:09 | 17.52 | 11.29 |
June | 0.842224E+10 | 27086.01 | 25-JUN-08:11 | 15.97 | 11.51 | 0.423873E+09 | 662.05 | 22-JUN-09:00 | 15.97 | 11.51 |
July | 0.105698E+11 | 26887.56 | 16-JUL-09:01 | 22.38 | 16.15 | 0.399144E+09 | 710.74 | 14-JUL-09:50 | 22.38 | 16.15 |
August | 0.913509E+10 | 26639.71 | 06-AUG-09:21 | 28.60 | 14.63 | 0.443443E+09 | 659.87 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.456666E+10 | 25434.34 | 03-SEP-10:51 | 29.40 | 15.12 | 0.376777E+09 | 544.98 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.176915E+10 | 8117.48 | 18-OCT-09:50 | 19.53 | 8.61 | 0.372442E+09 | 544.95 | 16-OCT-09:20 | 19.53 | 8.61 |
November | 0.566292E+09 | 3103.20 | 03-NOV-09:50 | 8.30 | 5.09 | 0.320976E+09 | 544.95 | 03-NOV-09:20 | 8.30 | 5.09 |
December | 0.140515E+09 | 965.37 | 20-DEC-10:30 | 3.85 | -0.4 | 0.290940E+09 | 468.86 | 20-DEC-10:39 | 4.03 | -0.3 |
Annual Sum or Average | 0.442777E+11 | 0.435074E+10 | ||||||||
Minimum of Months | 81984544.59 | 925.98 | -5.4 | -8.1 | 0.289497E+09 | 457.17 | -5.4 | -8.1 | ||
Maximum of Months | 0.105698E+11 | 27086.01 | 29.40 | 16.15 | 0.443443E+09 | 710.74 | 30.60 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162786E+10 | 14291.52 | 31-JAN-13:30 | -0.9 | -4.5 | 0.506285E+09 | 845.64 | 06-JAN-14:30 | -0.9 | -4.5 |
February | 0.374389E+10 | 34430.67 | 26-FEB-14:41 | 16.52 | 6.36 | 0.498860E+09 | 845.76 | 24-FEB-14:00 | 16.52 | 6.36 |
March | 0.516074E+10 | 23239.58 | 01-MAR-13:55 | 6.70 | 2.77 | 0.594182E+09 | 846.22 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.522574E+10 | 30536.77 | 16-APR-15:02 | 19.50 | 8.48 | 0.542529E+09 | 846.18 | 06-APR-13:00 | 19.50 | 8.48 |
May | 0.628306E+10 | 22709.24 | 14-MAY-13:43 | 16.52 | 6.74 | 0.609483E+09 | 846.42 | 19-MAY-13:50 | 27.02 | 15.00 |
June | 0.934543E+10 | 30181.95 | 25-JUN-13:32 | 23.87 | 13.41 | 0.648859E+09 | 984.36 | 20-JUN-13:09 | 23.87 | 13.41 |
July | 0.122462E+11 | 30581.18 | 30-JUL-16:21 | 30.85 | 14.76 | 0.621202E+09 | 1047.96 | 25-JUL-13:00 | 30.85 | 14.76 |
August | 0.136323E+11 | 30353.83 | 06-AUG-10:41 | 30.50 | 14.92 | 0.693004E+09 | 1128.87 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.107497E+11 | 36744.06 | 03-SEP-12:51 | 33.30 | 15.94 | 0.583934E+09 | 1029.67 | 01-SEP-13:00 | 33.30 | 15.94 |
October | 0.764977E+10 | 32822.00 | 15-OCT-13:41 | 23.12 | 11.08 | 0.589259E+09 | 945.99 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.401485E+10 | 22499.00 | 03-NOV-13:30 | 14.35 | 7.74 | 0.549595E+09 | 845.73 | 09-NOV-14:09 | 9.33 | 4.09 |
December | 0.195087E+10 | 12666.73 | 12-DEC-14:25 | -2.2 | -5.4 | 0.504406E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.816304E+11 | 0.694160E+10 | ||||||||
Minimum of Months | 0.162786E+10 | 12666.73 | -2.2 | -5.4 | 0.498860E+09 | 845.64 | -0.9 | -4.5 | ||
Maximum of Months | 0.136323E+11 | 36744.06 | 33.30 | 15.94 | 0.693004E+09 | 1128.87 | 33.30 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152538E+09 | 2156.86 | 13-JAN-15:40 | 9.27 | 4.85 | 0.304121E+09 | 521.18 | 13-JAN-16:49 | 7.98 | 4.06 |
February | 0.687425E+09 | 9012.97 | 26-FEB-16:41 | 15.68 | 5.96 | 0.290571E+09 | 544.94 | 27-FEB-14:20 | 18.50 | 7.10 |
March | 0.155039E+10 | 11281.02 | 28-MAR-17:00 | 10.60 | 2.97 | 0.360424E+09 | 544.93 | 02-MAR-14:20 | 10.60 | 2.97 |
April | 0.303945E+10 | 30179.08 | 16-APR-17:41 | 19.50 | 8.78 | 0.345131E+09 | 544.95 | 13-APR-13:20 | 19.50 | 8.78 |
May | 0.516813E+10 | 29002.48 | 28-MAY-17:41 | 20.18 | 10.35 | 0.392136E+09 | 545.00 | 02-MAY-13:09 | 20.18 | 10.35 |
June | 0.799965E+10 | 32155.01 | 18-JUN-17:51 | 25.00 | 14.46 | 0.419861E+09 | 601.94 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.982813E+10 | 32307.87 | 16-JUL-17:41 | 32.88 | 16.92 | 0.398251E+09 | 642.35 | 25-JUL-15:00 | 33.90 | 15.43 |
August | 0.864496E+10 | 27910.79 | 05-AUG-19:01 | 31.68 | 16.00 | 0.441221E+09 | 628.73 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.490366E+10 | 31171.39 | 03-SEP-15:31 | 33.67 | 16.05 | 0.368950E+09 | 567.91 | 01-SEP-15:00 | 33.67 | 16.05 |
October | 0.225942E+10 | 14425.49 | 15-OCT-15:42 | 22.30 | 10.85 | 0.357093E+09 | 544.95 | 19-OCT-13:20 | 21.10 | 10.10 |
November | 0.890351E+09 | 6344.99 | 03-NOV-15:40 | 14.40 | 7.69 | 0.327572E+09 | 544.94 | 06-NOV-14:30 | 8.05 | 3.12 |
December | 0.278956E+09 | 3231.56 | 06-DEC-15:40 | 9.97 | 4.80 | 0.299366E+09 | 544.92 | 06-DEC-14:00 | 9.97 | 4.80 |
Annual Sum or Average | 0.454031E+11 | 0.430470E+10 | ||||||||
Minimum of Months | 0.152538E+09 | 2156.86 | 9.27 | 2.97 | 0.290571E+09 | 521.18 | 7.98 | 2.97 | ||
Maximum of Months | 0.982813E+10 | 32307.87 | 33.67 | 16.92 | 0.441221E+09 | 642.35 | 33.90 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224168E+09 | 10825.07 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.445088E+09 | 7196.08 | 04-FEB-05:01 | -20.4 | -20.8 | 0.00 | 0.00 | 01-FEB-00:10 | -20.4 | -20.8 |
March | 0.145438E+10 | 6890.05 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.326231E+10 | 5774.92 | 24-APR-15:50 | 18.72 | 9.95 | 0.00 | 0.00 | 01-APR-00:10 | 18.72 | 9.95 |
May | 0.314938E+10 | 9042.64 | 30-MAY-05:15 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.643452E+10 | 8791.41 | 22-JUN-10:35 | 26.67 | 16.56 | 0.00 | 0.00 | 01-JUN-00:10 | 26.67 | 16.56 |
July | 0.813883E+10 | 11496.51 | 17-JUL-05:10 | 16.47 | 12.08 | 0.00 | 0.00 | 01-JUL-00:10 | 16.47 | 12.08 |
August | 0.838523E+10 | 12176.10 | 07-AUG-19:30 | 27.75 | 14.31 | 0.00 | 0.00 | 01-AUG-00:10 | 27.75 | 14.31 |
September | 0.453274E+10 | 11603.63 | 05-SEP-05:10 | 18.40 | 11.40 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 11.40 |
October | 0.306121E+10 | 5487.26 | 16-OCT-16:00 | 19.40 | 8.07 | 0.00 | 0.00 | 01-OCT-00:10 | 19.40 | 8.07 |
November | 0.150050E+10 | 4629.03 | 27-NOV-05:41 | -14.8 | -15.9 | 0.00 | 0.00 | 01-NOV-00:10 | -14.8 | -15.9 |
December | 0.422856E+09 | 6746.34 | 29-DEC-05:01 | -25.0 | -25.3 | 0.00 | 0.00 | 01-DEC-00:10 | -25.0 | -25.3 |
Annual Sum or Average | 0.410112E+11 | 0.00 | ||||||||
Minimum of Months | 0.224168E+09 | 4629.03 | -25.0 | -25.3 | 0.00 | 0.00 | -25.0 | -25.3 | ||
Maximum of Months | 0.838523E+10 | 12176.10 | 27.75 | 16.56 | 0.00 | 0.00 | 27.75 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176743E+09 | 13234.52 | 06-JAN-04:11 | -24.4 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.4 | -24.9 |
February | 0.104331E+09 | 12256.34 | 04-FEB-04:11 | -21.7 | -22.0 | 0.00 | 0.00 | 01-FEB-00:10 | -21.7 | -22.0 |
March | 0.311273E+09 | 15065.49 | 04-MAR-04:01 | -18.4 | -18.9 | 0.00 | 0.00 | 01-MAR-00:10 | -18.4 | -18.9 |
April | 0.650687E+09 | 8697.02 | 29-APR-04:01 | -7.8 | -8.7 | 0.00 | 0.00 | 01-APR-00:10 | -7.8 | -8.7 |
May | 0.136012E+10 | 9711.46 | 08-MAY-04:01 | -2.3 | -2.7 | 0.00 | 0.00 | 01-MAY-00:10 | -2.3 | -2.7 |
June | 0.415336E+10 | 7556.02 | 22-JUN-10:30 | 26.40 | 16.59 | 0.00 | 0.00 | 01-JUN-00:10 | 26.40 | 16.59 |
July | 0.574962E+10 | 8607.05 | 31-JUL-16:38 | 31.50 | 14.32 | 0.00 | 0.00 | 01-JUL-00:10 | 31.50 | 14.32 |
August | 0.545474E+10 | 8328.59 | 10-AUG-12:23 | 31.95 | 14.25 | 0.00 | 0.00 | 01-AUG-00:10 | 31.95 | 14.25 |
September | 0.275366E+10 | 8115.14 | 05-SEP-05:03 | 18.40 | 11.40 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 11.40 |
October | 0.844795E+09 | 9235.47 | 10-OCT-04:01 | -5.2 | -5.7 | 0.00 | 0.00 | 01-OCT-00:10 | -5.2 | -5.7 |
November | 0.285208E+09 | 11851.85 | 27-NOV-04:11 | -15.7 | -16.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.7 | -16.7 |
December | 0.178436E+09 | 11712.07 | 23-DEC-04:01 | -11.7 | -12.5 | 0.00 | 0.00 | 01-DEC-00:10 | -11.7 | -12.5 |
Annual Sum or Average | 0.220230E+11 | 0.00 | ||||||||
Minimum of Months | 0.104331E+09 | 7556.02 | -24.4 | -24.9 | 0.00 | 0.00 | -24.4 | -24.9 | ||
Maximum of Months | 0.574962E+10 | 15065.49 | 31.95 | 16.59 | 0.00 | 0.00 | 31.95 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64088.04 | 53.20 | 14-JAN-13:40 | 9.80 | 4.59 | 0.00 | 0.00 | 01-JAN-00:10 | 9.80 | 4.59 |
February | 42460405.12 | 2985.24 | 26-FEB-15:24 | 16.40 | 6.36 | 0.00 | 0.00 | 01-FEB-00:10 | 16.40 | 6.36 |
March | 0.330747E+09 | 3510.47 | 28-MAR-15:40 | 10.60 | 3.05 | 0.00 | 0.00 | 01-MAR-00:10 | 10.60 | 3.05 |
April | 0.168974E+10 | 10770.91 | 25-APR-15:10 | 17.13 | 7.50 | 0.00 | 0.00 | 01-APR-00:10 | 17.13 | 7.50 |
May | 0.397474E+10 | 17093.03 | 19-MAY-15:10 | 28.22 | 14.82 | 0.00 | 0.00 | 01-MAY-00:10 | 28.22 | 14.82 |
June | 0.866833E+10 | 20049.97 | 21-JUN-12:45 | 26.52 | 17.70 | 0.00 | 0.00 | 01-JUN-00:10 | 26.52 | 17.70 |
July | 0.116664E+11 | 23846.76 | 25-JUL-16:38 | 33.90 | 15.42 | 0.00 | 0.00 | 01-JUL-00:10 | 33.90 | 15.42 |
August | 0.988521E+10 | 19700.23 | 10-AUG-12:35 | 32.03 | 14.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.03 | 14.10 |
September | 0.432520E+10 | 14983.55 | 01-SEP-13:50 | 27.62 | 14.47 | 0.00 | 0.00 | 01-SEP-00:10 | 27.62 | 14.47 |
October | 0.866343E+09 | 8239.80 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 19721188.64 | 1512.45 | 04-NOV-16:02 | 16.02 | 7.50 | 0.00 | 0.00 | 01-NOV-00:10 | 16.02 | 7.50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.414690E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.116664E+11 | 23846.76 | 33.90 | 17.70 | 0.00 | 0.00 | 33.90 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190196E+10 | 1996.01 | 19-JAN-16:50 | -6.4 | -8.0 | 95113682.18 | 126.82 | 05-JAN-14:50 | -6.4 | -8.0 |
February | 0.717654E+10 | 4568.41 | 26-FEB-17:17 | 14.10 | 5.35 | 86396436.07 | 126.82 | 14-FEB-14:09 | 14.10 | 5.35 |
March | 0.137627E+11 | 6854.73 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.50 | 0.99 |
April | 0.187016E+11 | 8412.58 | 22-APR-18:15 | 15.17 | 8.10 | 91605270.02 | 126.82 | 24-APR-09:50 | 13.95 | 8.78 |
May | 0.415071E+10 | 3454.50 | 31-MAY-24:00 | 15.50 | 10.27 | 99234823.30 | 126.84 | 30-MAY-09:09 | 15.50 | 10.27 |
June | 0.928260E+10 | 5368.48 | 30-JUN-24:00 | 19.60 | 12.23 | 98962248.33 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.148317E+11 | 7302.92 | 31-JUL-24:00 | 19.20 | 11.32 | 91883891.48 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.197781E+11 | 8210.94 | 03-AUG-19:00 | 24.40 | 12.51 | 0.103459E+09 | 130.07 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.415791E+10 | 3291.95 | 30-SEP-24:00 | 11.80 | 6.26 | 91609938.86 | 126.85 | 06-SEP-13:00 | 11.80 | 6.26 |
October | 0.912008E+10 | 4970.30 | 31-OCT-24:00 | 4.70 | 1.47 | 95230856.43 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.133991E+11 | 6137.21 | 12-NOV-16:30 | -0.9 | -4.0 | 94300328.72 | 126.83 | 08-NOV-14:00 | -0.9 | -4.0 |
December | 0.184157E+11 | 7798.65 | 10-DEC-16:10 | 5.22 | -0.8 | 91880772.82 | 126.82 | 13-DEC-14:09 | -5.6 | -7.0 |
Annual Sum or Average | 0.134679E+12 | 0.114291E+10 | ||||||||
Minimum of Months | 0.190196E+10 | 1996.01 | -6.4 | -8.0 | 86396436.07 | 126.82 | -6.4 | -8.0 | ||
Maximum of Months | 0.197781E+11 | 8412.58 | 24.40 | 12.51 | 0.103459E+09 | 130.07 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297549E+09 | 1596.20 | 19-JAN-16:50 | -6.4 | -8.0 | 92051536.47 | 126.82 | 05-JAN-14:50 | -6.4 | -8.0 |
February | 0.474629E+10 | 3955.32 | 28-FEB-17:00 | 10.00 | 4.31 | 86396457.64 | 126.82 | 14-FEB-14:09 | 10.00 | 4.31 |
March | 0.112904E+11 | 6013.01 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 9.18 | 2.32 |
April | 0.168037E+11 | 7867.50 | 25-APR-18:10 | 16.73 | 7.64 | 91605300.95 | 126.82 | 24-APR-09:50 | 16.73 | 7.64 |
May | 0.319504E+10 | 3263.60 | 31-MAY-24:00 | 15.50 | 10.27 | 99234743.93 | 126.84 | 30-MAY-09:39 | 15.50 | 10.27 |
June | 0.852067E+10 | 5213.73 | 30-JUN-24:00 | 19.60 | 12.23 | 98962067.30 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.139697E+11 | 7053.94 | 31-JUL-24:00 | 19.20 | 11.32 | 91883792.54 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.186356E+11 | 7892.41 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103310E+09 | 127.88 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.339364E+10 | 2931.99 | 30-SEP-23:30 | 12.50 | 6.83 | 91609421.78 | 126.84 | 11-SEP-13:00 | 12.50 | 6.83 |
October | 0.751482E+10 | 4240.05 | 15-OCT-17:03 | 20.45 | 10.12 | 95230835.32 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.108210E+11 | 5528.79 | 03-NOV-16:20 | 14.17 | 7.63 | 94300355.36 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.145437E+11 | 7105.71 | 06-DEC-16:20 | 8.50 | 3.80 | 91880817.11 | 126.82 | 13-DEC-14:09 | -5.6 | -7.0 |
Annual Sum or Average | 0.113732E+12 | 0.113970E+10 | ||||||||
Minimum of Months | 0.297549E+09 | 1596.20 | -6.4 | -8.0 | 86396457.64 | 126.82 | -6.4 | -8.0 | ||
Maximum of Months | 0.186356E+11 | 7892.41 | 24.60 | 12.54 | 0.103310E+09 | 127.88 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143209E+09 | 1346.60 | 13-JAN-16:30 | 8.35 | 4.30 | 86068409.02 | 128.23 | 04-JAN-14:20 | 8.35 | 4.30 |
February | 0.322599E+10 | 3864.83 | 28-FEB-17:00 | 10.00 | 4.31 | 86391357.21 | 126.82 | 14-FEB-14:09 | 10.00 | 4.31 |
March | 0.954628E+10 | 5957.56 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 9.18 | 2.32 |
April | 0.155685E+11 | 7923.85 | 25-APR-18:10 | 16.73 | 7.64 | 91605336.22 | 126.83 | 24-APR-09:50 | 16.73 | 7.64 |
May | 0.260889E+10 | 3173.05 | 31-MAY-23:30 | 15.80 | 10.39 | 98832462.41 | 126.84 | 30-MAY-09:39 | 15.80 | 10.39 |
June | 0.828784E+10 | 5204.62 | 30-JUN-23:50 | 19.75 | 12.25 | 98962166.16 | 126.85 | 01-JUN-13:00 | 19.75 | 12.25 |
July | 0.139014E+11 | 7030.50 | 31-JUL-24:00 | 19.20 | 11.32 | 91883888.67 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.184689E+11 | 8013.46 | 03-AUG-19:00 | 24.40 | 12.51 | 0.103295E+09 | 126.91 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.282530E+10 | 3050.60 | 04-SEP-17:51 | 31.70 | 16.34 | 91602961.42 | 126.85 | 19-SEP-09:09 | 5.10 | 3.14 |
October | 0.601833E+10 | 4079.51 | 18-OCT-17:00 | 21.70 | 10.27 | 95230821.81 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.881332E+10 | 5425.81 | 03-NOV-16:20 | 14.17 | 7.63 | 94300363.45 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.125242E+11 | 7007.03 | 06-DEC-16:20 | 8.50 | 3.80 | 91880828.23 | 126.82 | 13-DEC-14:09 | -5.6 | -7.0 |
Annual Sum or Average | 0.101932E+12 | 0.113329E+10 | ||||||||
Minimum of Months | 0.143209E+09 | 1346.60 | 8.35 | 2.32 | 86068409.02 | 126.82 | -5.6 | -7.0 | ||
Maximum of Months | 0.184689E+11 | 8013.46 | 31.70 | 16.34 | 0.103295E+09 | 128.23 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232537E+12 | 90708.34 | 02-JAN-17:00 | 2.20 | -1.7 | 0.206151E+10 | 2745.43 | 02-JAN-14:00 | 2.20 | -1.7 |
February | 0.431929E+12 | 182465.07 | 27-FEB-17:00 | 12.20 | 5.32 | 0.187030E+10 | 2745.67 | 24-FEB-10:20 | 12.20 | 5.32 |
March | 0.725773E+12 | 357332.42 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223480E+10 | 2745.60 | 23-MAR-09:30 | 2.50 | 0.99 |
April | 0.940322E+12 | 366041.84 | 24-APR-16:00 | 18.90 | 10.03 | 0.198311E+10 | 2747.24 | 24-APR-09:00 | 18.90 | 10.03 |
May | 0.238765E+12 | 175669.84 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214818E+10 | 2747.07 | 19-MAY-13:09 | 15.50 | 10.27 |
June | 0.468747E+12 | 267630.40 | 30-JUN-24:00 | 19.60 | 12.23 | 0.214257E+10 | 2748.80 | 06-JUN-13:09 | 19.60 | 12.23 |
July | 0.731518E+12 | 360265.09 | 31-JUL-23:55 | 19.20 | 11.32 | 0.199018E+10 | 2751.26 | 07-JUL-09:09 | 19.20 | 11.32 |
August | 0.974465E+12 | 382083.14 | 06-AUG-19:53 | 26.10 | 13.21 | 0.241172E+10 | 4565.00 | 10-AUG-15:09 | 33.53 | 14.51 |
September | 0.233992E+12 | 175623.85 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198305E+10 | 2746.90 | 05-SEP-13:39 | 11.80 | 6.26 |
October | 0.485287E+12 | 267236.45 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206152E+10 | 2745.54 | 31-OCT-09:39 | 4.70 | 1.47 |
November | 0.705504E+12 | 275242.53 | 06-NOV-17:00 | 6.70 | 2.26 | 0.204136E+10 | 2745.60 | 03-NOV-13:50 | 6.70 | 2.26 |
December | 0.972085E+12 | 366262.03 | 06-DEC-17:00 | 6.70 | 2.38 | 0.198898E+10 | 2746.00 | 19-DEC-14:00 | 12.80 | 7.62 |
Annual Sum or Average | 0.714092E+13 | 0.249173E+11 | ||||||||
Minimum of Months | 0.232537E+12 | 90708.34 | 2.20 | -1.7 | 0.187030E+10 | 2745.43 | 2.20 | -1.7 | ||
Maximum of Months | 0.974465E+12 | 382083.14 | 26.10 | 13.21 | 0.241172E+10 | 4565.00 | 33.53 | 14.51 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324781E+09 | 10741.49 | 14-JAN-06:05 | 3.12 |
February | 54962959.57 | 10615.38 | 25-FEB-05:58 | 3.30 |
March | 80825020.16 | 10890.63 | 01-MAR-05:05 | -12.3 |
April | 74936577.79 | 11135.73 | 03-APR-04:55 | 1.10 |
May | 0.217206E+09 | 14690.51 | 20-MAY-16:03 | 29.82 |
June | 0.151710E+09 | 13696.64 | 24-JUN-16:01 | 28.22 |
July | 0.350550E+09 | 17972.35 | 15-JUL-16:03 | 32.80 |
August | 0.352651E+09 | 22417.49 | 05-AUG-16:01 | 35.22 |
September | 0.272780E+09 | 20860.58 | 02-SEP-16:01 | 33.98 |
October | 0.216400E+09 | 10920.00 | 26-OCT-04:15 | 6.50 |
November | 0.122815E+09 | 10858.29 | 08-NOV-05:17 | 10.47 |
December | 50913027.04 | 10582.50 | 11-DEC-04:03 | -2.6 |
Annual Sum or Average | 0.227053E+10 | |||
Minimum of Months | 50913027.04 | 10582.50 | -12.3 | |
Maximum of Months | 0.352651E+09 | 22417.49 | 35.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534551E+09 | 48496.97 | 09-JAN-05:11 | -27.2 |
February | 0.142145E+09 | 47351.79 | 06-FEB-05:11 | -0.2 |
March | 23041335.91 | 44277.59 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 15828626.50 | 43732.87 | 27-NOV-06:02 | -14.5 |
December | 0.127946E+09 | 46795.74 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.843512E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.534551E+09 | 48496.97 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101409E+11 | 71993.35 | 09-JAN-04:01 | -27.2 |
February | 0.370706E+10 | 71032.21 | 06-FEB-04:11 | -0.6 |
March | 0.201279E+10 | 71133.04 | 06-MAR-04:01 | -18.4 |
April | 74541529.02 | 57478.81 | 29-APR-05:01 | -7.7 |
May | 0.544672E+09 | 64040.64 | 08-MAY-04:11 | -2.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.321191E+09 | 64685.54 | 10-OCT-04:11 | -5.4 |
November | 0.249591E+10 | 70597.40 | 27-NOV-04:01 | -15.8 |
December | 0.557396E+10 | 70616.14 | 26-DEC-04:01 | -6.3 |
Annual Sum or Average | 0.248710E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.101409E+11 | 71993.35 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227532E+10 | 13235.71 | 09-JAN-04:01 | -27.2 |
February | 0.616644E+09 | 11977.92 | 04-FEB-05:01 | -20.4 |
March | 87616608.45 | 11947.00 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 28863383.00 | 11338.34 | 27-NOV-05:01 | -15.4 |
December | 0.342029E+09 | 11750.85 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.335048E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.227532E+10 | 13235.71 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148308E+10 | 15579.53 | 11-JAN-04:01 | -28.9 |
February | 0.458294E+09 | 13602.01 | 01-FEB-05:01 | -25.0 |
March | 76887925.70 | 13731.65 | 06-MAR-05:01 | -18.4 |
April | 697942.50 | 6958.77 | 29-APR-05:01 | -7.7 |
May | 245121.94 | 1361.12 | 08-MAY-05:02 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 43538543.11 | 13228.65 | 27-NOV-05:01 | -15.4 |
December | 0.375043E+09 | 13802.70 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.243779E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.148308E+10 | 15579.53 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212051E+10 | 22411.13 | 11-JAN-04:01 | -28.9 |
February | 0.543069E+09 | 19827.96 | 04-FEB-05:01 | -20.4 |
March | 0.150658E+09 | 20822.03 | 06-MAR-04:01 | -18.4 |
April | 2867467.59 | 16170.50 | 29-APR-05:01 | -7.7 |
May | 14567959.71 | 16332.74 | 08-MAY-05:02 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 4463998.28 | 10826.08 | 10-OCT-05:03 | -6.1 |
November | 0.106600E+09 | 20241.10 | 27-NOV-05:01 | -15.4 |
December | 0.513787E+09 | 20147.60 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.345653E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.212051E+10 | 22411.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.623660E+09 | 13724.44 | 09-JAN-04:01 | -27.2 |
February | 36675382.61 | 10629.09 | 04-FEB-06:01 | -19.5 |
March | 2135088.51 | 10312.09 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 475069.15 | 4750.69 | 27-NOV-06:02 | -14.5 |
December | 1043707.44 | 6009.75 | 29-DEC-06:01 | -25.1 |
Annual Sum or Average | 0.663989E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.623660E+09 | 13724.44 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844094E+10 | 13660.19 | 09-JAN-05:11 | -27.2 |
February | 0.392240E+10 | 13219.60 | 05-FEB-05:53 | -20.0 |
March | 0.166152E+10 | 13411.92 | 06-MAR-03:42 | -18.4 |
April | 0.172887E+09 | 11189.85 | 29-APR-04:01 | -7.8 |
May | 0.183565E+09 | 11503.22 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 23747185.27 | 10399.64 | 20-SEP-05:02 | 3.30 |
October | 0.174005E+09 | 11534.06 | 10-OCT-04:01 | -5.2 |
November | 0.171711E+10 | 13343.25 | 27-NOV-03:32 | -15.8 |
December | 0.506460E+10 | 13766.67 | 31-DEC-21:02 | -24.3 |
Annual Sum or Average | 0.213608E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.844094E+10 | 13766.67 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482378E+10 | 20719.78 | 09-JAN-02:31 | -27.2 |
February | 0.205401E+10 | 19738.59 | 04-FEB-04:11 | -21.7 |
March | 0.867939E+09 | 19350.38 | 06-MAR-04:01 | -18.4 |
April | 88168165.99 | 16799.39 | 29-APR-04:01 | -7.8 |
May | 0.113506E+09 | 17315.88 | 22-MAY-04:01 | -0.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 10070423.46 | 10985.46 | 19-SEP-05:02 | 2.20 |
October | 85996130.47 | 17422.42 | 10-OCT-04:01 | -5.2 |
November | 0.980728E+09 | 20157.00 | 27-NOV-04:11 | -15.7 |
December | 0.287127E+10 | 20631.29 | 31-DEC-21:02 | -24.3 |
Annual Sum or Average | 0.118955E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.482378E+10 | 20719.78 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533001E+10 | 24760.32 | 09-JAN-02:31 | -27.2 |
February | 0.194279E+10 | 23636.67 | 04-FEB-04:11 | -21.7 |
March | 0.942056E+09 | 23266.25 | 06-MAR-04:01 | -18.4 |
April | 0.122239E+09 | 20219.89 | 29-APR-04:01 | -7.8 |
May | 0.182919E+09 | 20947.82 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 10969163.01 | 13225.56 | 19-SEP-05:02 | 2.20 |
October | 80230369.28 | 20751.65 | 10-OCT-04:01 | -5.2 |
November | 0.956166E+09 | 24043.94 | 27-NOV-04:11 | -15.7 |
December | 0.286978E+10 | 24749.52 | 31-DEC-06:22 | -27.2 |
Annual Sum or Average | 0.124372E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.533001E+10 | 24760.32 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443755E+10 | 21087.44 | 09-JAN-02:31 | -27.2 |
February | 0.160625E+10 | 20015.89 | 04-FEB-04:11 | -21.7 |
March | 0.658211E+09 | 19763.98 | 06-MAR-04:01 | -18.4 |
April | 44435276.49 | 15275.73 | 29-APR-05:01 | -7.7 |
May | 83093392.58 | 17528.72 | 22-MAY-04:01 | -0.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 5544443.26 | 8586.55 | 19-SEP-05:02 | 2.20 |
October | 55278441.24 | 17270.37 | 10-OCT-04:01 | -5.2 |
November | 0.698545E+09 | 20509.75 | 27-NOV-04:11 | -15.7 |
December | 0.219509E+10 | 20769.23 | 31-DEC-09:02 | -26.2 |
Annual Sum or Average | 0.978399E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.443755E+10 | 21087.44 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145759E+11 | 17688.13 | 30-JAN-05:31 | -16.5 |
February | 0.756419E+10 | 16935.48 | 05-FEB-05:32 | -20.0 |
March | 0.463008E+10 | 17403.78 | 06-MAR-03:21 | -18.6 |
April | 0.118361E+10 | 14928.93 | 29-APR-03:02 | -6.9 |
May | 0.921296E+09 | 15709.67 | 07-MAY-22:53 | -2.2 |
June | 13967264.24 | 13102.24 | 17-JUN-04:12 | 2.03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 13046785.81 | 12398.62 | 18-AUG-05:02 | 7.30 |
September | 0.317219E+09 | 14323.22 | 19-SEP-04:11 | 2.20 |
October | 0.125349E+10 | 15346.16 | 10-OCT-03:01 | -4.1 |
November | 0.513292E+10 | 17124.69 | 27-NOV-05:11 | -15.3 |
December | 0.108283E+11 | 16980.35 | 31-DEC-01:22 | -20.0 |
Annual Sum or Average | 0.464340E+11 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.145759E+11 | 17688.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.876004E+10 | 21897.32 | 10-JAN-04:11 | -23.9 |
February | 0.412816E+10 | 21584.85 | 05-FEB-05:32 | -20.0 |
March | 0.247133E+10 | 22227.55 | 06-MAR-03:21 | -18.6 |
April | 0.581780E+09 | 18980.37 | 29-APR-03:02 | -6.9 |
May | 0.518685E+09 | 19551.15 | 08-MAY-03:01 | -2.7 |
June | 7999234.14 | 12694.75 | 17-JUN-04:12 | 2.03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 7138533.40 | 10146.78 | 18-AUG-05:02 | 7.30 |
September | 0.153337E+09 | 18314.98 | 19-SEP-04:11 | 2.20 |
October | 0.607129E+09 | 19542.97 | 10-OCT-03:01 | -4.1 |
November | 0.285342E+10 | 21656.36 | 26-NOV-22:32 | -14.3 |
December | 0.639085E+10 | 21615.85 | 31-DEC-01:22 | -20.0 |
Annual Sum or Average | 0.264799E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.9 | |
Maximum of Months | 0.876004E+10 | 22227.55 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101148E+11 | 27554.81 | 10-JAN-04:11 | -23.9 |
February | 0.441762E+10 | 27268.92 | 05-FEB-05:32 | -20.0 |
March | 0.314366E+10 | 27944.70 | 06-MAR-03:21 | -18.6 |
April | 0.925279E+09 | 23892.68 | 29-APR-03:02 | -6.9 |
May | 0.899507E+09 | 24783.28 | 08-MAY-03:01 | -2.7 |
June | 27702616.11 | 20408.97 | 17-JUN-05:02 | 2.35 |
July | 559.45 | 3.73 | 08-JUL-05:03 | 6.23 |
August | 16836781.81 | 15553.79 | 18-AUG-05:02 | 7.30 |
September | 0.202744E+09 | 22881.45 | 19-SEP-04:11 | 2.20 |
October | 0.680312E+09 | 24758.86 | 10-OCT-03:01 | -4.1 |
November | 0.304666E+10 | 27087.22 | 27-NOV-05:11 | -15.3 |
December | 0.696198E+10 | 27284.02 | 31-DEC-04:42 | -24.5 |
Annual Sum or Average | 0.304371E+11 | |||
Minimum of Months | 559.45 | 3.73 | -24.5 | |
Maximum of Months | 0.101148E+11 | 27944.70 | 7.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.805916E+10 | 24617.85 | 09-JAN-04:01 | -27.2 |
February | 0.330164E+10 | 23836.92 | 05-FEB-05:32 | -20.0 |
March | 0.196742E+10 | 24555.71 | 06-MAR-03:21 | -18.6 |
April | 0.400168E+09 | 20789.58 | 01-APR-04:11 | 6.33 |
May | 0.393720E+09 | 22009.36 | 08-MAY-03:01 | -2.7 |
June | 7815479.77 | 12146.15 | 17-JUN-05:02 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 5711199.88 | 9586.74 | 18-AUG-05:02 | 7.30 |
September | 0.103369E+09 | 20197.72 | 19-SEP-04:11 | 2.20 |
October | 0.420461E+09 | 22014.74 | 10-OCT-03:01 | -4.1 |
November | 0.209145E+10 | 24086.83 | 27-NOV-05:11 | -15.3 |
December | 0.493639E+10 | 23956.36 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.216873E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.805916E+10 | 24617.85 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215791E+10 | 10105.57 | 24-JAN-06:03 | 8.22 |
February | 0.120085E+10 | 12303.97 | 26-FEB-16:12 | 15.93 |
March | 0.415496E+09 | 11116.70 | 26-MAR-14:32 | 10.00 |
April | 0.195080E+09 | 14051.67 | 16-APR-15:31 | 19.80 |
May | 93630940.93 | 9577.89 | 22-MAY-04:01 | -0.1 |
June | 0.113248E+09 | 12487.63 | 18-JUN-16:41 | 25.50 |
July | 0.149110E+09 | 14158.40 | 09-JUL-16:01 | 28.30 |
August | 0.131825E+09 | 14277.83 | 06-AUG-15:41 | 35.40 |
September | 0.112939E+09 | 12041.40 | 03-SEP-15:41 | 34.03 |
October | 0.127756E+09 | 13650.46 | 15-OCT-14:51 | 22.80 |
November | 0.324652E+09 | 11216.86 | 24-NOV-05:11 | 12.20 |
December | 0.575301E+09 | 11944.13 | 04-DEC-05:01 | 1.32 |
Annual Sum or Average | 0.559780E+10 | |||
Minimum of Months | 93630940.93 | 9577.89 | -0.1 | |
Maximum of Months | 0.215791E+10 | 14277.83 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473239E+10 | 13593.50 | 09-JAN-06:12 | -27.2 |
February | 0.300054E+10 | 13321.37 | 26-FEB-16:32 | 15.77 |
March | 0.187205E+10 | 11082.24 | 26-MAR-13:22 | 9.45 |
April | 0.413782E+09 | 14854.49 | 16-APR-15:52 | 20.00 |
May | 0.539819E+09 | 10706.86 | 14-MAY-15:11 | 16.50 |
June | 86947267.68 | 11222.76 | 18-JUN-15:32 | 24.80 |
July | 0.116363E+09 | 14966.13 | 09-JUL-16:31 | 28.30 |
August | 67581162.42 | 14883.93 | 06-AUG-16:01 | 35.50 |
September | 0.169152E+09 | 14519.53 | 03-SEP-15:21 | 33.30 |
October | 0.452297E+09 | 14523.00 | 15-OCT-15:31 | 22.40 |
November | 0.158693E+10 | 10695.21 | 12-NOV-13:12 | -1.1 |
December | 0.301368E+10 | 6800.74 | 26-DEC-06:03 | -7.9 |
Annual Sum or Average | 0.160515E+11 | |||
Minimum of Months | 67581162.42 | 6800.74 | -27.2 | |
Maximum of Months | 0.473239E+10 | 14966.13 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164861E+11 | 34098.23 | 11-JAN-05:11 | -30.2 |
February | 0.873475E+10 | 28170.90 | 04-FEB-05:13 | -20.2 |
March | 0.611148E+10 | 30844.96 | 06-MAR-05:32 | -16.7 |
April | 0.247251E+10 | 15939.96 | 29-APR-05:02 | -7.7 |
May | 0.191231E+10 | 21137.67 | 08-MAY-04:22 | -2.5 |
June | 0.505961E+09 | 13271.65 | 20-JUN-05:03 | 9.68 |
July | 0.244175E+09 | 13977.86 | 12-JUL-05:03 | 6.85 |
August | 0.435892E+09 | 13058.14 | 28-AUG-05:03 | 7.12 |
September | 0.116615E+10 | 11834.80 | 11-SEP-05:03 | 11.02 |
October | 0.265055E+10 | 21112.42 | 10-OCT-04:23 | -5.5 |
November | 0.659840E+10 | 30017.86 | 27-NOV-05:17 | -15.3 |
December | 0.121847E+11 | 31498.91 | 29-DEC-06:13 | -25.2 |
Annual Sum or Average | 0.595030E+11 | |||
Minimum of Months | 0.244175E+09 | 11834.80 | -30.2 | |
Maximum of Months | 0.164861E+11 | 34098.23 | 11.02 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77138503.42 | 627.45 | 09-JAN-03:35 | -27.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 77138503.42 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 77138503.42 | 627.45 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.672042E+09 | 644.80 | 29-JAN-18:40 | -24.5 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 2505690.29 | 168.02 | 08-MAY-04:11 | -2.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.674547E+09 | |||
Minimum of Months | 0.00 | 0.00 | -24.5 | |
Maximum of Months | 0.672042E+09 | 644.80 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.918345E+09 | 700.49 | 29-JAN-17:32 | -21.7 |
February | 66762657.24 | 631.55 | 05-FEB-19:13 | -18.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2429565.05 | 723.98 | 30-APR-23:10 | -1.3 |
May | 0.129660E+09 | 653.50 | 01-MAY-00:30 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 36080199.64 | 604.39 | 19-SEP-04:25 | 2.20 |
October | 561946.03 | 497.99 | 10-OCT-03:22 | -4.5 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.115384E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.918345E+09 | 723.98 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.747158E+09 | 1147.25 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.602222E+09 | 964.15 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.670700E+09 | 1086.80 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.573423E+09 | 812.97 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.597714E+09 | 636.21 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.582117E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.557039E+09 | 610.35 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.622862E+09 | 624.60 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587950E+09 | 829.30 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.647986E+09 | 1147.25 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.702924E+09 | 1147.25 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.727901E+09 | 1147.25 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.762000E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.557039E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.747158E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.468213E+09 | 739.33 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.382838E+09 | 579.45 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.428840E+09 | 700.08 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.368383E+09 | 495.90 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.385947E+09 | 402.38 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.377829E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.359779E+09 | 381.86 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.402606E+09 | 387.09 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.377014E+09 | 411.83 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.410621E+09 | 739.33 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.444223E+09 | 739.33 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.456662E+09 | 739.33 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.486295E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.359779E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.468213E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.715050E+09 | 1147.28 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.585932E+09 | 829.93 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.664426E+09 | 1086.83 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.574215E+09 | 811.05 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.600496E+09 | 637.33 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.586223E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.559636E+09 | 612.11 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.626146E+09 | 625.82 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585929E+09 | 803.85 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.633497E+09 | 1147.28 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.673940E+09 | 1147.28 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.692546E+09 | 1147.28 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.749804E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.559636E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.715050E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.472683E+09 | 739.33 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.382441E+09 | 634.38 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.430766E+09 | 700.08 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.370565E+09 | 536.73 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.385818E+09 | 413.50 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.375340E+09 | 377.77 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359848E+09 | 398.66 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.401977E+09 | 408.96 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.378372E+09 | 582.60 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.414451E+09 | 739.33 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.441593E+09 | 739.33 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.457154E+09 | 739.33 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.487101E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359848E+09 | 377.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.472683E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.745269E+09 | 1147.25 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.600888E+09 | 961.26 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.669852E+09 | 1086.20 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.572849E+09 | 809.34 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.597424E+09 | 632.26 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.581959E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.556872E+09 | 604.90 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.622651E+09 | 620.00 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587318E+09 | 825.02 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.646608E+09 | 1147.25 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.700797E+09 | 1147.25 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.725760E+09 | 1147.25 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.760825E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.556872E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.745269E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.467493E+09 | 739.33 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.382364E+09 | 577.29 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.428571E+09 | 699.06 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.368110E+09 | 490.58 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.385685E+09 | 399.71 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.377611E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.359640E+09 | 378.12 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.402416E+09 | 383.86 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.376735E+09 | 409.73 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.410154E+09 | 739.33 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.443624E+09 | 739.33 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.455847E+09 | 739.33 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.485825E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.359640E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.467493E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.714422E+09 | 1147.28 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.585385E+09 | 822.38 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.663978E+09 | 1086.22 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573664E+09 | 807.40 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.600133E+09 | 633.43 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.585861E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.559329E+09 | 606.75 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.625724E+09 | 621.28 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585561E+09 | 799.34 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.632667E+09 | 1147.28 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.673644E+09 | 1147.28 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.692217E+09 | 1147.28 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.749258E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.559329E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.714422E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471701E+09 | 739.33 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381956E+09 | 631.98 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.430187E+09 | 699.06 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.370132E+09 | 531.46 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.385509E+09 | 411.22 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.375210E+09 | 373.50 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359687E+09 | 395.55 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.401770E+09 | 406.43 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.378057E+09 | 578.36 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.413878E+09 | 739.33 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.440917E+09 | 739.33 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.456676E+09 | 739.33 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.486568E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359687E+09 | 373.50 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.471701E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.745161E+09 | 1147.25 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.600854E+09 | 961.17 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.669817E+09 | 1086.07 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.572830E+09 | 808.64 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.597414E+09 | 632.10 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.581955E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.556860E+09 | 604.68 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.622625E+09 | 619.82 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587261E+09 | 824.45 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.646578E+09 | 1147.25 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.700757E+09 | 1147.25 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.725684E+09 | 1147.25 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.760779E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.556860E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.745161E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.467469E+09 | 739.33 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.382348E+09 | 577.25 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.428558E+09 | 698.98 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.368100E+09 | 490.11 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.385672E+09 | 399.59 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.377598E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.359624E+09 | 377.95 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.402395E+09 | 383.71 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.376721E+09 | 409.63 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.410171E+09 | 739.33 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.443727E+09 | 739.33 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.455793E+09 | 739.33 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.485817E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.359624E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.467469E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.714395E+09 | 1147.28 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.585354E+09 | 822.01 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.663958E+09 | 1086.09 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573647E+09 | 806.70 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.600108E+09 | 633.27 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.585846E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.559321E+09 | 606.54 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.625706E+09 | 621.10 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585545E+09 | 798.72 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.632654E+09 | 1147.28 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.673613E+09 | 1147.28 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.692200E+09 | 1147.28 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.749235E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.559321E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.714395E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471670E+09 | 739.33 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381942E+09 | 631.83 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.430171E+09 | 698.98 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.370108E+09 | 531.03 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.385498E+09 | 411.13 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.375207E+09 | 373.33 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.359681E+09 | 395.43 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.401765E+09 | 406.33 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.378046E+09 | 578.07 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.413864E+09 | 739.33 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.440901E+09 | 739.33 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.456653E+09 | 739.33 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.486551E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.359681E+09 | 373.33 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.471670E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.747158E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153614E+10 |
February | 0.136985E+10 | 0.602222E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123301E+10 |
March | 0.163685E+10 | 0.670700E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113010E+10 |
April | 0.145243E+10 | 0.573423E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824227E+09 |
May | 0.157338E+10 | 0.597714E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1803654.81 | 0.802874E+09 |
June | 0.156900E+10 | 0.582117E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9089407.34 | 0.399387E+09 |
July | 0.145680E+10 | 0.557039E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29115973.85 | 0.263421E+09 |
August | 0.163685E+10 | 0.622862E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25866836.42 | 0.289025E+09 |
September | 0.145243E+10 | 0.587950E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16233094.94 | 0.527979E+09 |
October | 0.150991E+10 | 0.647986E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108335.96 | 0.800629E+09 |
November | 0.149516E+10 | 0.702924E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113059E+10 |
December | 0.145680E+10 | 0.727901E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143463E+10 |
Annual Sum or Average | 0.181194E+11 | 0.762000E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82217303.32 | 0.103720E+11 |
Minimum of Months | 0.136985E+10 | 0.557039E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263421E+09 |
Maximum of Months | 0.163685E+10 | 0.747158E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29115973.85 | 0.153614E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.468213E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102754E+10 |
February | 0.882782E+09 | 0.382838E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829560E+09 |
March | 0.105485E+10 | 0.428840E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752777E+09 |
April | 0.936002E+09 | 0.368383E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548032E+09 |
May | 0.101394E+10 | 0.385947E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1197591.22 | 0.534201E+09 |
June | 0.101113E+10 | 0.377829E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6061088.56 | 0.266753E+09 |
July | 0.938820E+09 | 0.359779E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19326292.18 | 0.175995E+09 |
August | 0.105485E+10 | 0.402606E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17211526.13 | 0.190030E+09 |
September | 0.936002E+09 | 0.377014E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10306220.51 | 0.356646E+09 |
October | 0.973041E+09 | 0.410621E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72219.45 | 0.538628E+09 |
November | 0.963541E+09 | 0.444223E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747056E+09 |
December | 0.938820E+09 | 0.456662E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944655E+09 |
Annual Sum or Average | 0.116768E+11 | 0.486295E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54174938.05 | 0.691187E+10 |
Minimum of Months | 0.882782E+09 | 0.359779E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175995E+09 |
Maximum of Months | 0.105485E+10 | 0.468213E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19326292.18 | 0.102754E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.715050E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155444E+10 |
February | 0.136988E+10 | 0.585932E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127191E+10 |
March | 0.163688E+10 | 0.664426E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114034E+10 |
April | 0.145246E+10 | 0.574215E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826129E+09 |
May | 0.157341E+10 | 0.600496E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1765311.39 | 0.797179E+09 |
June | 0.156904E+10 | 0.586223E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8948978.60 | 0.399598E+09 |
July | 0.145684E+10 | 0.559636E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27639680.93 | 0.267769E+09 |
August | 0.163688E+10 | 0.626146E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24181990.01 | 0.295511E+09 |
September | 0.145246E+10 | 0.585929E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14075082.23 | 0.540960E+09 |
October | 0.150994E+10 | 0.633497E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52325.75 | 0.823079E+09 |
November | 0.149520E+10 | 0.673940E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113913E+10 |
December | 0.145684E+10 | 0.692546E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144559E+10 |
Annual Sum or Average | 0.181198E+11 | 0.749804E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76663368.91 | 0.105016E+11 |
Minimum of Months | 0.136988E+10 | 0.559636E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267769E+09 |
Maximum of Months | 0.163688E+10 | 0.715050E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27639680.93 | 0.155444E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.472683E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106736E+10 |
February | 0.882782E+09 | 0.382441E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894525E+09 |
March | 0.105485E+10 | 0.430766E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816853E+09 |
April | 0.936002E+09 | 0.370565E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614788E+09 |
May | 0.101394E+10 | 0.385818E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1126027.17 | 0.575515E+09 |
June | 0.101113E+10 | 0.375340E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5932003.54 | 0.295116E+09 |
July | 0.938820E+09 | 0.359848E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18035338.38 | 0.208247E+09 |
August | 0.105485E+10 | 0.401977E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16402246.26 | 0.224274E+09 |
September | 0.936002E+09 | 0.378372E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9753600.84 | 0.381692E+09 |
October | 0.973041E+09 | 0.414451E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72213.21 | 0.586058E+09 |
November | 0.963541E+09 | 0.441593E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826563E+09 |
December | 0.938820E+09 | 0.457154E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105531E+10 |
Annual Sum or Average | 0.116768E+11 | 0.487101E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51321429.40 | 0.754630E+10 |
Minimum of Months | 0.882782E+09 | 0.359848E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208247E+09 |
Maximum of Months | 0.105485E+10 | 0.472683E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18035338.38 | 0.106736E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.745269E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325928E+10 |
February | 0.136985E+10 | 0.600888E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251174E+10 |
March | 0.163685E+10 | 0.669852E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234836E+10 |
April | 0.145243E+10 | 0.572849E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169634E+10 |
May | 0.157338E+10 | 0.597424E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4059631.88 | 0.171583E+10 |
June | 0.156900E+10 | 0.581959E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20807020.45 | 0.883377E+09 |
July | 0.145680E+10 | 0.556872E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70232300.89 | 0.596131E+09 |
August | 0.163685E+10 | 0.622651E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61001233.36 | 0.644765E+09 |
September | 0.145243E+10 | 0.587318E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37857653.06 | 0.113110E+10 |
October | 0.150991E+10 | 0.646608E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724125.69 | 0.161398E+10 |
November | 0.149516E+10 | 0.700797E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227212E+10 |
December | 0.145680E+10 | 0.725760E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285887E+10 |
Annual Sum or Average | 0.181194E+11 | 0.760825E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194682E+09 | 0.215319E+11 |
Minimum of Months | 0.136985E+10 | 0.556872E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596131E+09 |
Maximum of Months | 0.163685E+10 | 0.745269E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70232300.89 | 0.325928E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.467493E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219711E+10 |
February | 0.649041E+09 | 0.382364E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174023E+10 |
March | 0.773965E+09 | 0.428571E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162748E+10 |
April | 0.688021E+09 | 0.368110E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119257E+10 |
May | 0.744847E+09 | 0.385685E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2551673.46 | 0.116969E+10 |
June | 0.742030E+09 | 0.377611E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13261158.26 | 0.612191E+09 |
July | 0.690839E+09 | 0.359640E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42793643.65 | 0.421007E+09 |
August | 0.773965E+09 | 0.402416E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38481078.04 | 0.451252E+09 |
September | 0.688021E+09 | 0.376735E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22876867.54 | 0.796428E+09 |
October | 0.715730E+09 | 0.410154E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109199.63 | 0.114710E+10 |
November | 0.708685E+09 | 0.443624E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155537E+10 |
December | 0.690839E+09 | 0.455847E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193100E+10 |
Annual Sum or Average | 0.858171E+10 | 0.485825E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120074E+09 | 0.148414E+11 |
Minimum of Months | 0.649041E+09 | 0.359640E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421007E+09 |
Maximum of Months | 0.773965E+09 | 0.467493E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42793643.65 | 0.219711E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.714422E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345571E+10 |
February | 0.136988E+10 | 0.585385E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280847E+10 |
March | 0.163688E+10 | 0.663978E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253284E+10 |
April | 0.145246E+10 | 0.573664E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182284E+10 |
May | 0.157341E+10 | 0.600133E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3905878.30 | 0.177219E+10 |
June | 0.156904E+10 | 0.585861E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20300090.25 | 0.902966E+09 |
July | 0.145684E+10 | 0.559329E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64152628.12 | 0.621857E+09 |
August | 0.163688E+10 | 0.625724E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56355001.95 | 0.681744E+09 |
September | 0.145246E+10 | 0.585561E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31267502.94 | 0.122189E+10 |
October | 0.150994E+10 | 0.632667E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43569.20 | 0.182973E+10 |
November | 0.149520E+10 | 0.673644E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248614E+10 |
December | 0.145684E+10 | 0.692217E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309846E+10 |
Annual Sum or Average | 0.181198E+11 | 0.749258E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176025E+09 | 0.232348E+11 |
Minimum of Months | 0.136988E+10 | 0.559329E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621857E+09 |
Maximum of Months | 0.163688E+10 | 0.714422E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64152628.12 | 0.345571E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.471701E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222889E+10 |
February | 0.882782E+09 | 0.381956E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177732E+10 |
March | 0.105485E+10 | 0.430187E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165270E+10 |
April | 0.936002E+09 | 0.370132E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123260E+10 |
May | 0.101394E+10 | 0.385509E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2526914.98 | 0.122796E+10 |
June | 0.101113E+10 | 0.375210E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13509057.99 | 0.633567E+09 |
July | 0.938820E+09 | 0.359687E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42486233.43 | 0.447917E+09 |
August | 0.105485E+10 | 0.401770E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38733848.88 | 0.469574E+09 |
September | 0.936002E+09 | 0.378057E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22550758.09 | 0.812030E+09 |
October | 0.973041E+09 | 0.413878E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144458.16 | 0.116446E+10 |
November | 0.963541E+09 | 0.440917E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159279E+10 |
December | 0.938820E+09 | 0.456676E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197554E+10 |
Annual Sum or Average | 0.116768E+11 | 0.486568E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119951E+09 | 0.152153E+11 |
Minimum of Months | 0.882782E+09 | 0.359687E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447917E+09 |
Maximum of Months | 0.105485E+10 | 0.471701E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42486233.43 | 0.222889E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.745161E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395005E+10 |
February | 0.136985E+10 | 0.600854E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292987E+10 |
March | 0.163685E+10 | 0.669817E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274583E+10 |
April | 0.145243E+10 | 0.572830E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193827E+10 |
May | 0.157338E+10 | 0.597414E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4713327.89 | 0.201233E+10 |
June | 0.156900E+10 | 0.581955E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24902912.96 | 0.106731E+10 |
July | 0.145680E+10 | 0.556860E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83288584.99 | 0.725452E+09 |
August | 0.163685E+10 | 0.622625E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73645915.65 | 0.776126E+09 |
September | 0.145243E+10 | 0.587261E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44999674.00 | 0.131425E+10 |
October | 0.150991E+10 | 0.646578E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3309791.20 | 0.177977E+10 |
November | 0.149516E+10 | 0.700757E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260430E+10 |
December | 0.145680E+10 | 0.725684E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343007E+10 |
Annual Sum or Average | 0.181194E+11 | 0.760779E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234860E+09 | 0.252736E+11 |
Minimum of Months | 0.136985E+10 | 0.556860E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725452E+09 |
Maximum of Months | 0.163685E+10 | 0.745161E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83288584.99 | 0.395005E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.467469E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266023E+10 |
February | 0.882782E+09 | 0.382348E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201773E+10 |
March | 0.105485E+10 | 0.428558E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190108E+10 |
April | 0.936002E+09 | 0.368100E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137359E+10 |
May | 0.101394E+10 | 0.385672E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3073708.74 | 0.137813E+10 |
June | 0.101113E+10 | 0.377598E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16400897.97 | 0.742362E+09 |
July | 0.938820E+09 | 0.359624E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51834911.20 | 0.514213E+09 |
August | 0.105485E+10 | 0.402395E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47394612.89 | 0.545537E+09 |
September | 0.936002E+09 | 0.376721E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27599310.83 | 0.934916E+09 |
October | 0.973041E+09 | 0.410171E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 148946.34 | 0.127685E+10 |
November | 0.963541E+09 | 0.443727E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177162E+10 |
December | 0.938820E+09 | 0.455793E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230338E+10 |
Annual Sum or Average | 0.116768E+11 | 0.485817E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146452E+09 | 0.174196E+11 |
Minimum of Months | 0.882782E+09 | 0.359624E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514213E+09 |
Maximum of Months | 0.105485E+10 | 0.467469E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51834911.20 | 0.266023E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.714395E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412281E+10 |
February | 0.136988E+10 | 0.585354E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326084E+10 |
March | 0.163688E+10 | 0.663958E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297255E+10 |
April | 0.145246E+10 | 0.573647E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211101E+10 |
May | 0.157341E+10 | 0.600108E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4529282.20 | 0.208933E+10 |
June | 0.156904E+10 | 0.585846E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24306044.43 | 0.109336E+10 |
July | 0.145684E+10 | 0.559321E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75768263.96 | 0.758102E+09 |
August | 0.163688E+10 | 0.625706E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68376436.83 | 0.825058E+09 |
September | 0.145246E+10 | 0.585545E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37812346.02 | 0.143906E+10 |
October | 0.150994E+10 | 0.632654E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95068.66 | 0.207475E+10 |
November | 0.149520E+10 | 0.673613E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284136E+10 |
December | 0.145684E+10 | 0.692200E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362061E+10 |
Annual Sum or Average | 0.181198E+11 | 0.749235E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210887E+09 | 0.272088E+11 |
Minimum of Months | 0.136988E+10 | 0.559321E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758102E+09 |
Maximum of Months | 0.163688E+10 | 0.714395E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75768263.96 | 0.412281E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.471670E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268407E+10 |
February | 0.882782E+09 | 0.381942E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208171E+10 |
March | 0.105485E+10 | 0.430171E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194929E+10 |
April | 0.936002E+09 | 0.370108E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143730E+10 |
May | 0.101394E+10 | 0.385498E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2944782.32 | 0.145348E+10 |
June | 0.101113E+10 | 0.375207E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16252136.88 | 0.768899E+09 |
July | 0.938820E+09 | 0.359681E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50764196.33 | 0.546483E+09 |
August | 0.105485E+10 | 0.401765E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46911712.85 | 0.569303E+09 |
September | 0.936002E+09 | 0.378046E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27016263.61 | 0.957542E+09 |
October | 0.973041E+09 | 0.413864E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 148986.48 | 0.132152E+10 |
November | 0.963541E+09 | 0.440901E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184121E+10 |
December | 0.938820E+09 | 0.456653E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235211E+10 |
Annual Sum or Average | 0.116768E+11 | 0.486551E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144038E+09 | 0.179629E+11 |
Minimum of Months | 0.882782E+09 | 0.359681E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546483E+09 |
Maximum of Months | 0.105485E+10 | 0.471670E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50764196.33 | 0.268407E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329965E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265914E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240593E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174255E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2883568.07 | 0.168869E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14986478.11 | 0.834675E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55796905.92 | 0.559402E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48156565.72 | 0.620411E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31860196.24 | 0.113171E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44264.72 | 0.171341E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243353E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309762E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153728E+09 | 0.221867E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559402E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55796905.92 | 0.329965E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547722E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437985E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406223E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295744E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5290568.85 | 0.291681E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27186192.24 | 0.146144E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104930E+09 | 0.980470E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88914321.12 | 0.108684E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58837288.58 | 0.197593E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89334.64 | 0.289890E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403472E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500588E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285248E+09 | 0.372377E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980470E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104930E+09 | 0.547722E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578206E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451136E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426133E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310411E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3282019.19 | 0.316840E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22829215.23 | 0.166565E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86086524.96 | 0.112557E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82129137.19 | 0.121750E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47503453.75 | 0.210948E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290218E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401353E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508965E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241830E+09 | 0.389508E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112557E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86086524.96 | 0.578206E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2512.57 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 964.15 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1576.93 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1086.80 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1921.85 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 812.97 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1369.18 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 636.21 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.32 | 20-MAY-17:03 | 2618.31 | 22-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1087.75 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 610.35 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.43 | 30-JUL-11:58 | 662.97 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 624.60 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.53 | 06-AUG-17:45 | 835.06 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 829.30 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.69 | 03-SEP-12:51 | 1459.13 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1147.25 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 | 18-OCT-14:00 | 1260.32 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.88 | 28-NOV-05:51 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2335.57 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.97 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 356.69 | 2618.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1674.51 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 579.45 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1035.48 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 700.08 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1266.04 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 495.90 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 896.38 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 402.38 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.00 | 20-MAY-17:03 | 1728.19 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 708.49 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 381.86 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.59 | 30-JUL-11:55 | 431.39 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 387.09 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.92 | 06-AUG-17:45 | 538.55 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 411.83 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.90 | 03-SEP-13:04 | 961.10 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 739.33 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 831.92 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1003.92 | 28-NOV-05:56 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1509.07 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.39 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 235.90 | 1728.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2511.38 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 829.93 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1620.17 | 19-FEB-12:20 |
March | 2010.83 | 01-MAR-10:09 | 1086.83 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1952.09 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 811.05 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1354.16 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 637.33 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 19-MAY-16:00 | 2540.59 | 22-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1070.08 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 612.11 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.76 | 30-JUL-11:55 | 652.52 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 625.82 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.67 | 06-AUG-17:43 | 830.55 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 803.85 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.15 | 03-SEP-13:10 | 1424.52 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1147.28 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 18-OCT-15:00 | 1302.89 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.88 | 28-NOV-05:51 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2248.40 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.52 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 332.15 | 2540.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1677.02 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 634.38 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1130.69 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 700.08 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1377.38 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 536.73 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1000.29 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 413.50 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.34 | 19-MAY-16:00 | 1791.19 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 377.77 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 790.85 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 398.66 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.30 | 30-JUL-11:55 | 500.15 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 408.96 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.22 | 06-AUG-17:43 | 649.78 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 582.60 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.08 | 03-SEP-13:03 | 1014.11 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 739.33 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 911.66 | 08-OCT-15:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1081.17 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1720.71 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 377.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.15 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 234.08 | 1791.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5878.37 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 961.26 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3238.70 | 08-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 1086.20 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4096.07 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 809.34 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2882.56 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 632.26 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.64 | 20-MAY-17:03 | 5691.49 | 22-MAY-04:56 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2291.12 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 604.90 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 571.23 | 30-JUL-11:53 | 1392.42 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 620.00 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 724.37 | 06-AUG-17:24 | 1689.98 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 825.02 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 848.72 | 03-SEP-12:51 | 2997.22 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1147.25 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.73 | 15-OCT-13:55 | 2572.42 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3528.94 | 28-NOV-05:50 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.10 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1392.42 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 848.72 | 5878.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 739.33 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3917.81 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 577.29 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2158.21 | 08-FEB-22:01 |
March | 1239.33 | 01-MAR-08:09 | 699.06 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2750.62 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 490.58 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1939.81 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 399.71 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.30 | 20-MAY-17:03 | 3845.34 | 22-MAY-04:45 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1539.70 | 04-JUN-14:00 |
July | 1239.33 | 03-JUL-07:10 | 378.12 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.30 | 30-JUL-14:54 | 934.83 | 05-JUL-01:00 |
August | 1239.33 | 01-AUG-07:10 | 383.86 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.57 | 06-AUG-17:24 | 1138.08 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 409.73 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.09 | 03-SEP-12:53 | 1995.27 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 739.33 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 | 18-OCT-14:20 | 1759.21 | 30-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.69 | 28-NOV-05:44 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.19 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.83 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 540.09 | 3917.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5880.33 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 822.38 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3685.29 | 19-FEB-12:40 |
March | 2010.83 | 01-MAR-10:09 | 1086.22 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4308.52 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 807.40 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2925.84 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 633.43 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 19-MAY-16:00 | 5706.76 | 22-MAY-04:45 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2288.99 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 606.75 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 535.68 | 30-JUL-14:14 | 1416.43 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 621.28 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 721.61 | 06-AUG-17:23 | 1742.38 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 799.34 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 03-SEP-13:00 | 3014.25 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1147.28 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 18-OCT-15:40 | 2908.86 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3529.08 | 28-NOV-05:50 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.27 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.43 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 5880.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3919.08 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 631.98 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2163.55 | 08-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 699.06 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2856.67 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 531.46 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1979.82 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 411.22 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.23 | 19-MAY-16:00 | 3843.09 | 22-MAY-04:45 |
June | 1295.83 | 01-JUN-09:09 | 373.50 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1569.55 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 395.55 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.60 | 30-JUL-14:53 | 1006.25 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 406.43 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.42 | 06-AUG-17:45 | 1185.53 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 578.36 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.42 | 03-SEP-12:51 | 2007.11 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 739.33 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.70 | 18-OCT-14:00 | 1818.80 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.69 | 28-NOV-05:50 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3366.12 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 373.50 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.25 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 540.42 | 3919.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7292.33 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 961.17 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4035.85 | 17-FEB-06:00 |
March | 2010.79 | 01-MAR-10:09 | 1086.07 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4958.14 | 17-MAR-04:50 |
April | 2010.79 | 03-APR-09:09 | 808.64 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3325.86 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 632.10 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.02 | 20-MAY-17:03 | 7102.25 | 22-MAY-04:45 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.93 | 29-JUN-15:00 | 2654.28 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 604.68 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 682.50 | 30-JUL-11:53 | 1603.49 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 619.82 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 867.49 | 06-AUG-17:43 | 2028.77 | 22-AUG-21:03 |
September | 2010.79 | 01-SEP-09:09 | 824.45 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1024.89 | 03-SEP-12:54 | 3310.68 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1147.25 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.18 | 15-OCT-13:55 | 3156.78 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4277.58 | 28-NOV-05:51 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5912.08 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.49 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1024.89 | 7292.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4860.84 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 577.25 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2690.52 | 17-FEB-05:52 |
March | 1295.83 | 01-MAR-10:09 | 698.98 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3305.29 | 17-MAR-04:45 |
April | 1295.83 | 03-APR-09:09 | 490.11 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2245.73 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 399.59 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.65 | 19-MAY-16:00 | 4734.99 | 22-MAY-04:50 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1941.64 | 04-JUN-13:53 |
July | 1295.83 | 03-JUL-09:09 | 377.95 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.87 | 30-JUL-11:44 | 1077.58 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 383.71 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.66 | 06-AUG-17:24 | 1382.06 | 22-AUG-21:03 |
September | 1295.83 | 01-SEP-09:09 | 409.63 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.01 | 03-SEP-12:53 | 2204.67 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 739.33 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 | 18-OCT-14:00 | 2111.80 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.85 | 28-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.71 | 01-DEC-05:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.58 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 690.01 | 4860.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7295.92 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 822.01 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4055.73 | 19-FEB-13:00 |
March | 2010.83 | 01-MAR-10:09 | 1086.09 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5078.12 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 806.70 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3390.44 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 633.27 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.47 | 19-MAY-16:00 | 7101.98 | 22-MAY-04:50 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.92 | 29-JUN-15:00 | 2816.01 | 04-JUN-13:53 |
July | 2010.83 | 03-JUL-09:09 | 606.54 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 678.62 | 30-JUL-11:44 | 1634.59 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 621.10 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 867.49 | 06-AUG-17:43 | 2121.03 | 22-AUG-21:03 |
September | 2010.83 | 01-SEP-09:09 | 798.72 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 988.95 | 03-SEP-13:00 | 3337.24 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1147.28 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 | 18-OCT-15:10 | 3284.87 | 30-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4423.15 | 28-NOV-05:54 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6297.77 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1634.59 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 988.95 | 7295.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4862.64 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 631.83 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2690.58 | 17-FEB-05:58 |
March | 1295.83 | 01-MAR-10:09 | 698.98 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3379.25 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 531.03 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2308.48 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 411.13 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.51 | 19-MAY-16:00 | 4734.85 | 22-MAY-04:47 |
June | 1295.83 | 01-JUN-09:09 | 373.33 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1828.18 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 395.43 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.64 | 30-JUL-11:46 | 1178.04 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 406.33 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 578.32 | 06-AUG-17:45 | 1452.99 | 22-AUG-21:03 |
September | 1295.83 | 01-SEP-09:09 | 578.07 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 713.71 | 03-SEP-12:53 | 2244.49 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 739.33 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 | 18-OCT-14:00 | 2133.80 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.75 | 28-NOV-05:57 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.70 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 373.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.04 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 713.71 | 4862.64 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5218.67 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3480.40 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4119.18 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2929.92 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.30 | 20-MAY-17:03 | 5843.66 | 22-MAY-04:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.85 | 29-JUN-15:00 | 2321.17 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.58 | 30-JUL-12:00 | 1375.20 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.11 | 06-AUG-18:00 | 1778.81 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764.68 | 03-SEP-12:51 | 3188.61 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 | 18-OCT-15:00 | 2709.36 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3305.72 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5169.34 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.20 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764.68 | 5843.66 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9096.79 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5812.14 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7167.70 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5103.28 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.81 | 20-MAY-17:03 | 9998.77 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.48 | 29-JUN-15:00 | 4039.22 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.18 | 30-JUL-12:00 | 2378.51 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.94 | 06-AUG-17:51 | 3053.40 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1390.02 | 03-SEP-13:00 | 5552.41 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 | 18-OCT-15:00 | 4615.69 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5458.22 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8199.91 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1390.02 | 9998.77 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 10258.87 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5709.32 | 08-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7729.72 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5347.65 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.12 | 20-MAY-17:03 | 10029.57 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.63 | 29-JUN-15:00 | 4285.81 | 04-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 890.94 | 30-JUL-14:10 | 2508.62 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1066.56 | 06-AUG-17:50 | 3243.28 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.55 | 03-SEP-13:00 | 5465.17 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4837.68 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5755.99 | 28-NOV-05:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8146.60 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.62 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.55 | 10258.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96452.09 | 02-JAN-04:11 | 0.00 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96795.76 | 21-FEB-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93903.40 | 27-MAR-03:31 | 0.00 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96853.90 | 10-APR-04:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94436.66 | 22-MAY-03:02 | 0.00 | 2260.85 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96838.95 | 05-JUN-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95749.20 | 05-JUL-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 98495.15 | 28-AUG-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96613.52 | 18-SEP-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98217.59 | 10-OCT-03:01 | 0.00 | 3956.50 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98717.11 | 06-NOV-04:02 | 0.00 | 3391.28 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96275.30 | 11-DEC-04:01 | 0.00 | 5086.92 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93903.40 | 0.00 | 2260.85 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98717.11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 78491.27 | 02-JAN-05:01 | 0.00 | 7106.42 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78289.23 | 27-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78129.29 | 20-MAR-04:01 | 0.00 | 10152.03 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83759.74 | 10-APR-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83868.97 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88403.68 | 26-JUN-04:12 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85567.67 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84630.16 | 07-AUG-04:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84241.05 | 11-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81802.98 | 02-OCT-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80824.83 | 06-NOV-04:02 | 0.00 | 3045.61 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78174.79 | 11-DEC-05:01 | 0.00 | 7106.42 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78129.29 | 0.00 | 3045.61 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88403.68 | 0.00 | 10152.03 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14062.06 | 19-JAN-17:00 | 45948.79 | 27411.28 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25825.81 | 28-FEB-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52158.90 | 24-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68792.23 | 26-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72078.13 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73029.22 | 22-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73617.91 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75200.68 | 14-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79513.80 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69110.48 | 19-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64004.73 | 08-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20095.87 | 07-DEC-16:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14062.06 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79513.80 | 45948.79 | 27411.28 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13091.56 | 13-JAN-17:00 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17676.34 | 28-FEB-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21265.41 | 29-MAR-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34335.07 | 25-APR-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67820.63 | 30-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73491.50 | 21-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79823.74 | 17-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71841.18 | 08-AUG-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81030.92 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31696.72 | 18-OCT-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18883.45 | 03-NOV-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13991.61 | 06-DEC-16:50 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13091.56 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81030.92 | 30632.53 | 18274.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2035.15 | 02-JAN-05:01 | 0.00 | 892.28 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.66 |
February | 3974.19 | 27-FEB-16:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
March | 4745.75 | 27-MAR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.82 |
April | 6921.52 | 07-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
May | 10363.24 | 30-MAY-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 |
June | 15275.94 | 25-JUN-19:01 | 0.00 | 212.27 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.60 |
July | 15206.08 | 02-JUL-18:51 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 |
August | 15342.10 | 06-AUG-15:41 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 253.34 | 0.00 |
September | 13115.71 | 04-SEP-16:02 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 109.62 | 0.00 |
October | 5555.97 | 19-OCT-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
November | 3804.96 | 08-NOV-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.57 |
December | 2386.82 | 06-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2035.15 | 0.00 | 212.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15342.10 | 2010.79 | 892.28 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 253.34 | 320.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3215.47 | 17-JAN-10:05 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.46 |
February | 9189.53 | 26-FEB-09:33 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.19 |
March | 11272.19 | 28-MAR-09:15 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.10 |
April | 18902.91 | 16-APR-08:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.45 |
May | 13727.94 | 19-MAY-08:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 |
June | 24362.35 | 11-JUN-09:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.26 |
July | 25985.00 | 02-JUL-07:31 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.54 |
August | 24251.08 | 06-AUG-08:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 |
September | 24112.59 | 04-SEP-08:61 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 |
October | 16394.51 | 15-OCT-08:53 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.25 |
November | 7215.92 | 06-NOV-09:25 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.75 |
December | 3376.00 | 20-DEC-10:05 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3215.47 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 | |
Maximum of Months | 25985.00 | 2591.66 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25283.36 | 01-JAN-12:43 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.98 |
February | 29092.79 | 26-FEB-13:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.63 |
March | 29277.50 | 26-MAR-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.17 |
April | 27101.14 | 16-APR-12:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.31 |
May | 24396.57 | 14-MAY-14:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.12 |
June | 27314.62 | 11-JUN-13:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 |
July | 28192.21 | 09-JUL-13:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 |
August | 28205.53 | 06-AUG-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 204.43 | 0.00 |
September | 29799.77 | 03-SEP-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 245.09 | 0.00 |
October | 30228.70 | 15-OCT-12:51 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.48 |
November | 27296.53 | 12-NOV-12:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.14 |
December | 17185.04 | 12-DEC-12:30 | 1058.33 | 545.88 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17185.04 | 404.87 | 121.30 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30228.70 | 1058.33 | 545.88 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 245.09 | 921.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5666.11 | 13-JAN-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.78 |
February | 19271.85 | 26-FEB-16:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.90 |
March | 17415.64 | 12-MAR-16:02 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 930.67 |
April | 30320.35 | 16-APR-16:51 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.26 |
May | 29214.70 | 28-MAY-17:21 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.60 |
June | 33102.35 | 18-JUN-17:21 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.20 |
July | 34095.61 | 02-JUL-17:31 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.17 |
August | 31046.24 | 06-AUG-16:21 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 134.36 | 0.00 |
September | 28265.49 | 04-SEP-16:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
October | 27802.26 | 15-OCT-15:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.94 |
November | 11472.97 | 08-NOV-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 |
December | 9507.79 | 06-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5666.11 | 0.00 | 97.71 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34095.61 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 134.36 | 930.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1182.00 | 13-JAN-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.09 |
February | 2123.60 | 27-FEB-14:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.73 |
March | 2184.95 | 23-MAR-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.94 |
April | 5152.64 | 07-APR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 |
May | 7160.12 | 19-MAY-16:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 0.00 |
June | 11106.92 | 21-JUN-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.82 |
July | 14280.23 | 02-JUL-18:21 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.77 |
August | 13187.90 | 06-AUG-16:41 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 641.88 | 0.00 |
September | 14108.78 | 04-SEP-13:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 332.76 | 0.00 |
October | 4158.85 | 19-OCT-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.64 |
November | 2135.04 | 03-NOV-14:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.44 |
December | 1324.25 | 06-DEC-15:50 | 1923.11 | 733.26 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1182.00 | 0.00 | 242.60 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14280.23 | 4021.58 | 1091.73 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 641.88 | 602.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1036.30 | 20-JAN-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.55 |
February | 6413.09 | 27-FEB-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.08 |
March | 10885.68 | 28-MAR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.84 |
April | 17526.04 | 16-APR-08:32 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.03 |
May | 14701.29 | 19-MAY-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.44 |
June | 26347.42 | 11-JUN-09:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.68 |
July | 29551.98 | 02-JUL-09:01 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.29 |
August | 26529.64 | 06-AUG-08:41 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 |
September | 26650.20 | 04-SEP-08:51 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.89 |
October | 10697.33 | 18-OCT-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.41 |
November | 6732.11 | 03-NOV-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.58 |
December | 1112.93 | 07-DEC-11:10 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1036.30 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 | |
Maximum of Months | 29551.98 | 2478.65 | 703.55 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17887.46 | 15-JAN-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.36 |
February | 31097.76 | 26-FEB-13:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.03 |
March | 27941.02 | 26-MAR-13:22 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1880.28 |
April | 28019.31 | 16-APR-13:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.89 |
May | 25064.85 | 14-MAY-13:53 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1662.68 |
June | 28085.27 | 11-JUN-13:12 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 |
July | 29011.87 | 09-JUL-13:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 |
August | 28978.96 | 20-AUG-13:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.91 |
September | 33922.01 | 03-SEP-12:01 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 164.23 | 0.00 |
October | 31950.55 | 15-OCT-13:31 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 863.55 |
November | 30044.38 | 11-NOV-14:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.02 |
December | 15654.94 | 12-DEC-12:40 | 1058.33 | 545.88 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15654.94 | 404.87 | 121.30 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33922.01 | 1058.33 | 545.88 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 164.23 | 1880.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2514.45 | 13-JAN-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.19 |
February | 11376.94 | 26-FEB-16:32 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.63 |
March | 11658.50 | 28-MAR-17:00 | 391.37 | 195.43 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.45 |
April | 26571.85 | 16-APR-17:12 | 0.00 | 117.25 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.76 |
May | 27561.89 | 28-MAY-17:41 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.99 |
June | 27835.01 | 18-JUN-17:31 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.95 |
July | 31372.75 | 02-JUL-18:21 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.48 |
August | 27137.06 | 05-AUG-18:21 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 | 0.00 |
September | 30105.68 | 04-SEP-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 52.24 | 0.00 |
October | 22007.78 | 15-OCT-16:12 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.57 |
November | 7161.44 | 03-NOV-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.90 |
December | 3829.08 | 06-DEC-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2514.45 | 0.00 | 97.71 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31372.75 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 | 731.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1174.06 | 14-JAN-17:03 | 303.65 | 191.20 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.93 |
February | 1948.89 | 27-FEB-13:30 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.82 |
March | 2044.43 | 23-MAR-13:30 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.60 |
April | 5017.63 | 07-APR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 |
May | 7945.37 | 19-MAY-16:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 215.48 | 0.00 |
June | 11706.36 | 25-JUN-16:51 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.79 |
July | 17743.53 | 30-JUL-16:21 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 254.55 | 0.00 |
August | 17065.86 | 06-AUG-18:02 | 0.00 | 181.95 | 3355.02 | 0.00 | 0.00 | 0.00 | 0.00 | 773.10 | 0.00 |
September | 17854.06 | 03-SEP-15:31 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 705.81 | 0.00 |
October | 3643.33 | 19-OCT-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 |
November | 1913.15 | 03-NOV-13:30 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.55 |
December | 1289.16 | 06-DEC-16:00 | 1923.11 | 798.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1174.06 | 0.00 | 181.95 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17854.06 | 4021.58 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 773.10 | 704.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 925.98 | 31-JAN-10:50 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.61 |
February | 3545.14 | 28-FEB-10:20 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.73 |
March | 7626.75 | 28-MAR-09:40 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.31 |
April | 12101.01 | 25-APR-09:20 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.06 |
May | 14221.57 | 19-MAY-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 |
June | 27086.01 | 25-JUN-08:11 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.82 |
July | 26887.56 | 16-JUL-09:01 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.37 |
August | 26639.71 | 06-AUG-09:21 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 |
September | 25434.34 | 03-SEP-10:51 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 0.00 |
October | 8117.48 | 18-OCT-09:50 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.07 |
November | 3103.20 | 03-NOV-09:50 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.56 |
December | 965.37 | 20-DEC-10:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 925.98 | 456.59 | 136.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27086.01 | 2591.66 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 590.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14291.52 | 31-JAN-13:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.37 |
February | 34430.67 | 26-FEB-14:41 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1287.76 |
March | 23239.58 | 01-MAR-13:55 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.58 |
April | 30536.77 | 16-APR-15:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.77 |
May | 22709.24 | 14-MAY-13:43 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2120.65 |
June | 30181.95 | 25-JUN-13:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.70 |
July | 30581.18 | 30-JUL-16:21 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 205.11 | 0.00 |
August | 30353.83 | 06-AUG-10:41 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 226.46 | 0.00 |
September | 36744.06 | 03-SEP-12:51 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 330.72 | 0.00 |
October | 32822.00 | 15-OCT-13:41 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.39 |
November | 22499.00 | 03-NOV-13:30 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.00 |
December | 12666.73 | 12-DEC-14:25 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12666.73 | 404.87 | 121.30 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36744.06 | 4021.67 | 1091.75 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 330.72 | 2120.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2156.86 | 13-JAN-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.01 |
February | 9012.97 | 26-FEB-16:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.93 |
March | 11281.02 | 28-MAR-17:00 | 391.37 | 195.43 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.15 |
April | 30179.08 | 16-APR-17:41 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.33 |
May | 29002.48 | 28-MAY-17:41 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.89 |
June | 32155.01 | 18-JUN-17:51 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.95 |
July | 32307.87 | 16-JUL-17:41 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 0.00 |
August | 27910.79 | 05-AUG-19:01 | 0.00 | 136.80 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 159.96 | 0.00 |
September | 31171.39 | 03-SEP-15:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 285.06 | 0.00 |
October | 14425.49 | 15-OCT-15:42 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.24 |
November | 6344.99 | 03-NOV-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.44 |
December | 3231.56 | 06-DEC-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2156.86 | 0.00 | 97.71 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32307.87 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 285.06 | 911.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10825.07 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2615.18 |
February | 7196.08 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.28 |
March | 6890.05 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1644.48 |
April | 5774.92 | 24-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.41 |
May | 9042.64 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.18 |
June | 8791.41 | 22-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
July | 11496.51 | 17-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.47 |
August | 12176.10 | 07-AUG-19:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 | 0.00 |
September | 11603.63 | 05-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.33 |
October | 5487.26 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.65 |
November | 4629.03 | 27-NOV-05:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2861.09 |
December | 6746.34 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4629.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12176.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 | 2861.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13234.52 | 06-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5954.11 |
February | 12256.34 | 04-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.96 |
March | 15065.49 | 04-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3165.94 |
April | 8697.02 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3285.40 |
May | 9711.46 | 08-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4249.68 |
June | 7556.02 | 22-JUN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 0.00 |
July | 8607.05 | 31-JUL-16:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.43 | 0.00 |
August | 8328.59 | 10-AUG-12:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.95 | 0.00 |
September | 8115.14 | 05-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.60 |
October | 9235.47 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2717.57 |
November | 11851.85 | 27-NOV-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.79 |
December | 11712.07 | 23-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3953.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7556.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15065.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.95 | 5954.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 53.20 | 14-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.71 |
February | 2985.24 | 26-FEB-15:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1005.22 |
March | 3510.47 | 28-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.70 |
April | 10770.91 | 25-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.83 |
May | 17093.03 | 19-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.67 | 0.00 |
June | 20049.97 | 21-JUN-12:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 0.00 |
July | 23846.76 | 25-JUL-16:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.09 | 0.00 |
August | 19700.23 | 10-AUG-12:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.74 | 0.00 |
September | 14983.55 | 01-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.30 | 0.00 |
October | 8239.80 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
November | 1512.45 | 04-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.07 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23846.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.74 | 5114.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1996.01 | 19-JAN-16:50 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4568.41 | 26-FEB-17:17 | 35.07 | 24.39 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6854.73 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8412.58 | 22-APR-18:15 | 0.00 | 65.03 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3454.50 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5368.48 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7302.92 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8210.94 | 03-AUG-19:00 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3291.95 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4970.30 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6137.21 | 12-NOV-16:30 | 23.38 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7798.65 | 10-DEC-16:10 | 23.38 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1996.01 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8412.58 | 222.14 | 146.32 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1596.20 | 19-JAN-16:50 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3955.32 | 28-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6013.01 | 28-MAR-17:50 | 23.38 | 48.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7867.50 | 25-APR-18:10 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3263.60 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5213.73 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7053.94 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7892.41 | 03-AUG-18:50 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2931.99 | 30-SEP-23:30 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4240.05 | 15-OCT-17:03 | 0.00 | 32.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5528.79 | 03-NOV-16:20 | 70.15 | 81.29 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7105.71 | 06-DEC-16:20 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1596.20 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7892.41 | 222.14 | 146.32 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1346.60 | 13-JAN-16:30 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3864.83 | 28-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5957.56 | 28-MAR-17:50 | 23.38 | 48.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7923.85 | 25-APR-18:10 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3173.05 | 31-MAY-23:30 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5204.62 | 30-JUN-23:50 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7030.50 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8013.46 | 03-AUG-19:00 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3050.60 | 04-SEP-17:51 | 0.00 | 73.16 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4079.51 | 18-OCT-17:00 | 70.15 | 81.29 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5425.81 | 03-NOV-16:20 | 70.15 | 81.29 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7007.03 | 06-DEC-16:20 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1346.60 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8013.46 | 222.14 | 146.32 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90708.34 | 02-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182465.07 | 27-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357332.42 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366041.84 | 24-APR-16:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175669.84 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267630.40 | 30-JUN-24:00 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360265.09 | 31-JUL-23:55 | 0.00 | 318.73 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 382083.14 | 06-AUG-19:53 | 0.00 | 637.46 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175623.85 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267236.45 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275242.53 | 06-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366262.03 | 06-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90708.34 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 382083.14 | 4808.68 | 2868.67 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.140533E+13 | 859819.77 | 03-JAN-08:09 | 0.117231E+13 | 2396861.01 | 09-JAN-07:10 |
February | 0.166356E+13 | 1091830.00 | 27-FEB-16:10 | 0.661463E+12 | 1692261.44 | 01-FEB-07:10 |
March | 0.221661E+13 | 1203657.56 | 28-MAR-15:00 | 0.470062E+12 | 1621878.22 | 06-MAR-07:10 |
April | 0.248307E+13 | 1545643.97 | 06-APR-15:00 | 0.206676E+12 | 595008.39 | 29-APR-06:10 |
May | 0.149967E+13 | 1202948.20 | 31-MAY-15:00 | 0.161709E+12 | 626197.71 | 08-MAY-06:19 |
June | 0.196216E+13 | 1495036.68 | 23-JUN-15:50 | 0.729683E+11 | 274826.16 | 16-JUN-06:00 |
July | 0.252209E+13 | 1651812.84 | 17-JUL-15:00 | 0.630365E+11 | 80286.25 | 06-JUL-11:30 |
August | 0.301000E+13 | 1851136.76 | 10-AUG-15:50 | 0.673457E+11 | 410104.89 | 17-AUG-13:00 |
September | 0.148464E+13 | 1368092.97 | 07-SEP-14:00 | 0.927986E+11 | 392195.73 | 11-SEP-09:30 |
October | 0.188882E+13 | 1295966.18 | 18-OCT-15:00 | 0.166947E+12 | 725216.07 | 10-OCT-06:30 |
November | 0.213533E+13 | 1220600.55 | 17-NOV-16:00 | 0.377156E+12 | 1418647.58 | 27-NOV-07:10 |
December | 0.250297E+13 | 1264270.32 | 07-DEC-16:30 | 0.797028E+12 | 1793418.33 | 29-DEC-07:10 |
Annual Sum or Average | 0.247743E+14 | 0.430950E+13 | ||||
Minimum of Months | 0.140533E+13 | 859819.77 | 0.630365E+11 | 80286.25 | ||
Maximum of Months | 0.301000E+13 | 1851136.76 | 0.117231E+13 | 2396861.01 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.155271E+11 | 48104.25 | 27-JAN-12:30 | 0.00 | 0.00 |
February | 0.226532E+11 | 53037.46 | 28-FEB-12:30 | 0.00 | 0.00 |
March | 0.380012E+11 | 76202.84 | 16-MAR-12:39 | 0.00 | 0.00 |
April | 0.438874E+11 | 80259.03 | 25-APR-12:30 | 0.00 | 0.00 |
May | 0.558893E+11 | 85349.02 | 14-MAY-12:30 | 0.00 | 0.00 |
June | 0.628206E+11 | 83636.98 | 19-JUN-12:50 | 0.00 | 0.00 |
July | 0.656521E+11 | 81483.50 | 11-JUL-12:30 | 0.00 | 0.00 |
August | 0.553030E+11 | 78294.70 | 03-AUG-12:39 | 0.00 | 0.00 |
September | 0.392127E+11 | 70532.41 | 01-SEP-12:30 | 0.00 | 0.00 |
October | 0.269794E+11 | 58326.46 | 10-OCT-12:09 | 0.00 | 0.00 |
November | 0.164997E+11 | 41542.57 | 03-NOV-12:09 | 0.00 | 0.00 |
December | 0.121036E+11 | 31025.58 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.454529E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.121036E+11 | 31025.58 | 0.00 | 0.00 | |
Maximum of Months | 0.656521E+11 | 85349.02 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.147235E+12 | 0.333520E+11 | 0.766053E+12 | 0.102195E+12 | 0.179019E+12 | 0.111745E+11 | 0.00 | 0.677029E+10 | 0.654342E+09 | 0.158877E+12 | 0.00 | 0.00 | 0.00 |
February | 0.130849E+12 | 0.260478E+11 | 0.978954E+12 | 0.923110E+11 | 0.160940E+12 | 0.130519E+11 | 0.00 | 0.253419E+11 | 0.340249E+10 | 0.232661E+12 | 0.00 | 0.00 | 0.00 |
March | 0.153971E+12 | 0.234193E+11 | 0.141687E+13 | 0.102362E+12 | 0.184704E+12 | 0.169259E+11 | 0.00 | 0.454024E+11 | 0.511033E+10 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
April | 0.136656E+12 | 0.175978E+11 | 0.165903E+13 | 0.988819E+11 | 0.187378E+12 | 0.195966E+11 | 0.00 | 0.835681E+11 | 0.223373E+11 | 0.258032E+12 | 0.00 | 0.00 | 0.00 |
May | 0.146677E+12 | 0.141543E+11 | 0.774844E+12 | 0.102278E+12 | 0.204772E+12 | 0.236170E+11 | 0.00 | 0.494005E+11 | 0.252835E+11 | 0.158642E+12 | 0.00 | 0.00 | 0.00 |
June | 0.145502E+12 | 0.122114E+11 | 0.106252E+13 | 0.990389E+11 | 0.251805E+12 | 0.357981E+11 | 0.00 | 0.157109E+12 | 0.602676E+11 | 0.137905E+12 | 0.00 | 0.00 | 0.00 |
July | 0.136661E+12 | 0.131242E+11 | 0.139340E+13 | 0.102120E+12 | 0.293343E+12 | 0.499840E+11 | 0.00 | 0.325182E+12 | 0.958415E+11 | 0.112433E+12 | 0.00 | 0.00 | 0.00 |
August | 0.152290E+12 | 0.162612E+11 | 0.173200E+13 | 0.102362E+12 | 0.286643E+12 | 0.473900E+11 | 0.00 | 0.351479E+12 | 0.971144E+11 | 0.224462E+12 | 0.00 | 0.00 | 0.00 |
September | 0.137170E+12 | 0.203115E+11 | 0.740713E+12 | 0.988811E+11 | 0.213888E+12 | 0.304558E+11 | 0.00 | 0.897209E+11 | 0.454719E+11 | 0.108028E+12 | 0.00 | 0.00 | 0.00 |
October | 0.143687E+12 | 0.264503E+11 | 0.108340E+13 | 0.102194E+12 | 0.191334E+12 | 0.226332E+11 | 0.00 | 0.562354E+11 | 0.169571E+11 | 0.245928E+12 | 0.00 | 0.00 | 0.00 |
November | 0.144162E+12 | 0.308116E+11 | 0.135889E+13 | 0.989462E+11 | 0.174531E+12 | 0.169484E+11 | 0.00 | 0.441867E+11 | 0.765500E+10 | 0.259199E+12 | 0.00 | 0.00 | 0.00 |
December | 0.142604E+12 | 0.348256E+11 | 0.170972E+13 | 0.102121E+12 | 0.176735E+12 | 0.145363E+11 | 0.00 | 0.493120E+11 | 0.527800E+10 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171746E+13 | 0.268567E+12 | 0.146764E+14 | 0.120369E+13 | 0.250509E+13 | 0.302112E+12 | 0.00 | 0.128371E+13 | 0.385373E+12 | 0.243185E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130849E+12 | 0.122114E+11 | 0.740713E+12 | 0.923110E+11 | 0.160940E+12 | 0.111745E+11 | 0.00 | 0.677029E+10 | 0.654342E+09 | 0.108028E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153971E+12 | 0.348256E+11 | 0.173200E+13 | 0.102362E+12 | 0.293343E+12 | 0.499840E+11 | 0.00 | 0.351479E+12 | 0.971144E+11 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.109846E+13 | 0.00 | 0.738521E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.593635E+12 | 0.00 | 0.678280E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.392180E+12 | 0.00 | 0.778816E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.136701E+12 | 0.00 | 0.699747E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.905941E+11 | 0.00 | 0.711147E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.605307E+10 | 0.00 | 0.669152E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 28337662.53 | 0.00 | 0.630082E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.136355E+10 | 0.00 | 0.659821E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.311249E+11 | 0.00 | 0.616736E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.101280E+12 | 0.00 | 0.656663E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.310205E+12 | 0.00 | 0.669509E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.726742E+12 | 0.00 | 0.702866E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.348837E+13 | 0.00 | 0.821134E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 28337662.53 | 0.00 | 0.616736E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.109846E+13 | 0.00 | 0.778816E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 169722.15 | 02-JAN-08:09 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73700.64 | 02-JAN-08:20 | 114730.60 | 09-JAN-06:10 | 19410.50 | 25-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 158809.92 | 02-FEB-08:09 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73694.91 | 02-FEB-08:20 | 140011.35 | 28-FEB-16:19 | 19664.41 | 27-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 167293.14 | 17-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73699.36 | 17-MAR-07:19 | 155469.70 | 28-MAR-15:00 | 19509.73 | 01-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 156124.73 | 14-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73693.50 | 14-APR-07:19 | 219204.07 | 25-APR-15:30 | 20131.04 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 149375.52 | 03-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73689.96 | 03-MAY-07:19 | 259145.49 | 19-MAY-15:20 | 43491.79 | 19-MAY-15:39 | 0.00 | 01-MAY-00:10 |
June | 146252.02 | 16-JUN-07:10 | 22480.63 | 01-JUN-20:10 | 541788.89 | 01-JUN-07:10 | 73688.33 | 16-JUN-07:19 | 315059.02 | 06-JUN-15:30 | 44181.75 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 148284.63 | 07-JUL-07:30 | 22480.63 | 01-JUL-20:30 | 660080.29 | 03-JUL-07:10 | 73689.39 | 07-JUL-07:40 | 315059.02 | 11-JUL-14:09 | 44235.51 | 17-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 148836.91 | 17-AUG-07:10 | 31088.59 | 03-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73689.68 | 17-AUG-07:19 | 315059.02 | 07-AUG-10:30 | 44231.29 | 10-AUG-10:20 | 0.00 | 01-AUG-00:10 |
September | 155417.53 | 11-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73693.13 | 11-SEP-07:19 | 315059.02 | 01-SEP-14:30 | 44221.56 | 25-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 169722.15 | 30-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73700.64 | 30-OCT-07:19 | 174303.77 | 16-OCT-15:00 | 39704.98 | 18-OCT-14:09 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 01-NOV-07:10 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73700.64 | 01-NOV-07:19 | 143252.78 | 03-NOV-15:39 | 19778.57 | 03-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:40 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73700.64 | 13-DEC-08:20 | 97969.61 | 07-DEC-13:00 | 19352.33 | 11-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 146252.02 | 22480.63 | 423497.50 | 73688.33 | 97969.61 | 19352.33 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 73700.64 | 315059.02 | 44235.51 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 10122.14 | 02-JAN-14:50 | 1302.45 | 13-JAN-16:10 | 96046.86 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 82972.41 | 27-FEB-15:30 | 43776.24 | 27-FEB-13:30 | 100000.00 | 01-FEB-17:30 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66183.08 | 28-MAR-15:00 | 8405.05 | 14-MAR-13:00 | 100000.00 | 01-MAR-04:40 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 237761.20 | 07-APR-13:00 | 45168.56 | 06-APR-15:00 | 100000.00 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 220442.71 | 19-MAY-15:09 | 71995.62 | 19-MAY-14:20 | 100000.00 | 02-MAY-21:10 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 336957.65 | 21-JUN-12:30 | 71995.62 | 20-JUN-13:09 | 100000.00 | 04-JUN-12:50 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 361865.56 | 17-JUL-15:00 | 71995.62 | 13-JUL-12:39 | 100000.00 | 08-JUL-04:00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 384328.86 | 10-AUG-14:00 | 71995.62 | 05-AUG-12:39 | 100000.00 | 02-AUG-21:10 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 348329.35 | 07-SEP-14:00 | 71995.62 | 02-SEP-13:09 | 100000.00 | 02-SEP-19:10 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 229841.65 | 18-OCT-14:09 | 47001.09 | 18-OCT-14:09 | 100000.00 | 08-OCT-11:30 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 79785.61 | 03-NOV-14:09 | 43788.11 | 17-NOV-16:00 | 100000.00 | 01-NOV-04:49 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 37850.82 | 06-DEC-11:00 | 19627.95 | 10-DEC-01:00 | 100000.00 | 01-DEC-03:39 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 10122.14 | 1302.45 | 96046.86 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 384328.86 | 71995.62 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 859819.77 | 03-JAN-08:09 | 169722.15 | 423497.50 | 31088.59 | 73641.61 | 76621.40 | 3681.22 | 0.00 | 2249.47 | 256.94 |
February | 1091830.00 | 27-FEB-16:10 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 118374.87 | 19438.83 | 0.00 | 69874.33 | 43776.24 |
March | 1203657.56 | 28-MAR-15:00 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 155469.70 | 19412.58 | 0.00 | 66183.08 | 3935.08 |
April | 1545643.97 | 06-APR-15:00 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 191872.71 | 20026.25 | 0.00 | 211627.93 | 45168.56 |
May | 1202948.20 | 31-MAY-15:00 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 218143.02 | 36631.65 | 0.00 | 179458.58 | 46640.62 |
June | 1495036.68 | 23-JUN-15:50 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 301820.10 | 43781.86 | 0.00 | 258272.43 | 50796.56 |
July | 1651812.84 | 17-JUL-15:00 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 315059.02 | 44235.51 | 0.00 | 361865.56 | 71995.62 |
August | 1851136.76 | 10-AUG-15:50 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 310123.35 | 41837.56 | 0.00 | 377258.28 | 44969.05 |
September | 1368092.97 | 07-SEP-14:00 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 309874.97 | 43950.13 | 0.00 | 348329.35 | 71995.62 |
October | 1295966.18 | 18-OCT-15:00 | 146739.54 | 541788.89 | 0.00 | 52589.64 | 171718.12 | 36801.65 | 0.00 | 199327.24 | 47001.09 |
November | 1220600.55 | 17-NOV-16:00 | 169722.15 | 660080.29 | 31088.59 | 52602.06 | 87818.68 | 19276.93 | 0.00 | 56223.74 | 43788.11 |
December | 1264270.32 | 07-DEC-16:30 | 169722.15 | 778371.69 | 31088.59 | 52596.49 | 85016.05 | 19256.58 | 0.00 | 25056.20 | 3162.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 859819.77 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 76621.40 | 3681.22 | 0.00 | 2249.47 | 256.94 | |
Maximum of Months | 1851136.76 | 169722.15 | 778371.69 | 31088.59 | 73641.61 | 315059.02 | 44235.51 | 0.00 | 377258.28 | 71995.62 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2364675.41 | 09-JAN-07:10 | 0.00 | 86953.36 | 31-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 1660240.62 | 01-FEB-07:10 | 0.00 | 87109.56 | 16-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 1597522.37 | 06-MAR-07:10 | 0.00 | 87022.39 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 565556.71 | 29-APR-06:10 | 0.00 | 86198.59 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 594547.36 | 08-MAY-06:19 | 0.00 | 84757.85 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 243644.60 | 16-JUN-06:00 | 0.00 | 82664.35 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 7857.70 | 08-JUL-06:10 | 0.00 | 80286.25 | 06-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 374781.73 | 17-AUG-13:00 | 0.00 | 79127.95 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 335454.72 | 11-SEP-09:30 | 0.00 | 80004.65 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 694221.50 | 10-OCT-06:30 | 0.00 | 82120.42 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 1388101.21 | 27-NOV-07:10 | 0.00 | 84051.58 | 28-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 1773945.84 | 29-DEC-07:10 | 0.00 | 85883.04 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 7857.70 | 0.00 | 79127.95 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2364675.41 | 0.00 | 87109.56 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.24 | 1.17 | 27.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.91 | 0.00 | 25.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.87 | 0.00 | 25.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.82 | 0.00 | 25.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.98 | 0.00 | 25.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.40 | 0.00 | 26.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.49 | 1.17 | 26.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 25.62 | 7.33 | 25.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.93 | 0.17 | 26.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.98 | 1.17 | 27.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.48 | 0.00 | 26.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.69 | 0.00 | 25.69 |
Annual Sum or Average | 0.00 | 0.00 | 44.83 | 26.31 | 11.00 | 26.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.24 | 7.33 | 27.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.82 | 5.67 | 24.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 24.81 | 11.17 | 24.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.00 | 9.50 | 24.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.33 | 24.90 | 26.33 | 24.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 25.62 | 11.17 | 25.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
February | 0.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.70 | 4.17 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.66 | 2.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.62 | 2.83 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.66 | 0.00 | 18.66 | 9.00 | 24.45 | 9.00 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.95 | 0.00 | 18.95 | 4.17 | 24.70 | 4.17 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 18.85 | 3.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 2.17 | 18.74 | 0.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
March | 1.83 | 18.71 | 0.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.75 | 5.83 | 24.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 24.86 | 12.83 | 24.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.91 | 6.67 | 24.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
November | 2.50 | 18.89 | 0.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
December | 4.83 | 18.91 | 0.83 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 22.67 | 18.84 | 5.83 | 19.06 | 25.33 | 21.78 | 25.33 | 22.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 18.91 | 3.33 | 19.14 | 12.83 | 24.91 | 12.83 | 24.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 18.50 | 0.83 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
February | 1.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
March | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25.03 | 6.50 | 25.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 25.21 | 37.33 | 25.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 25.31 | 19.50 | 25.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.41 | 2.17 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 7.17 | 18.68 | 0.83 | 18.83 | 67.67 | 24.62 | 65.50 | 24.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 19.34 | 0.83 | 19.34 | 38.67 | 27.41 | 37.33 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 18.06 | 0.17 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
February | 1.33 | 19.09 | 0.00 | 19.09 | 0.33 | 20.77 | 0.33 | 21.88 |
March | 0.50 | 19.05 | 0.00 | 19.05 | 0.17 | 21.13 | 0.17 | 22.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.94 | 2.00 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.10 | 12.33 | 27.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 26.81 | 25.00 | 26.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 26.38 | 14.33 | 26.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.99 | 7.00 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.70 | 1.17 | 27.70 |
November | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
December | 0.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 6.83 | 18.44 | 0.17 | 18.49 | 65.33 | 26.14 | 62.67 | 26.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 | 0.00 | 18.15 |
Maximum of Months | 4.33 | 19.40 | 0.17 | 19.40 | 26.50 | 27.99 | 25.00 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 17.98 | 0.33 | 18.12 | 1.83 | 20.44 | 1.83 | 21.87 |
February | 1.17 | 19.04 | 0.00 | 19.04 | 3.83 | 25.98 | 3.83 | 26.90 |
March | 0.50 | 18.86 | 0.00 | 18.86 | 2.17 | 26.17 | 2.17 | 26.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.93 | 3.67 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.75 | 1.83 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.07 | 14.17 | 26.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 26.04 | 44.17 | 26.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 25.82 | 53.17 | 25.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 26.62 | 18.33 | 26.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.33 | 7.33 | 27.33 |
November | 0.17 | 19.00 | 0.00 | 19.00 | 3.00 | 27.63 | 3.00 | 27.86 |
December | 0.50 | 18.95 | 0.00 | 18.95 | 1.67 | 25.49 | 1.67 | 26.34 |
Annual Sum or Average | 7.83 | 18.28 | 0.33 | 18.37 | 160.67 | 25.92 | 155.17 | 26.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 20.44 | 1.67 | 21.87 |
Maximum of Months | 5.50 | 19.04 | 0.33 | 19.04 | 54.83 | 27.93 | 53.17 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.10 | 1.67 | 28.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.82 | 1.50 | 27.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.07 | 4.33 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.29 | 3.17 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.28 | 10.83 | 27.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 27.12 | 35.00 | 27.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 26.94 | 29.33 | 26.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.78 | 7.50 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.22 | 2.50 | 28.22 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.55 | 1.33 | 27.55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
Annual Sum or Average | 2.83 | 18.84 | 0.00 | 18.84 | 157.33 | 27.12 | 97.50 | 27.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 0.00 | 18.84 |
Maximum of Months | 2.83 | 18.84 | 0.00 | 18.84 | 55.17 | 28.29 | 35.00 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.00 | 17.20 | 27.00 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
February | 21.50 | 17.37 | 6.00 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
March | 9.17 | 17.60 | 2.00 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
April | 0.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
May | 0.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.95 | 5.83 | 24.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 25.15 | 20.50 | 25.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 25.23 | 13.00 | 25.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.39 | 2.00 | 27.39 |
October | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
November | 9.83 | 17.61 | 2.17 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
December | 24.33 | 17.39 | 7.67 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
Annual Sum or Average | 129.17 | 17.34 | 44.83 | 17.60 | 42.50 | 19.10 | 41.33 | 20.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 0.00 | 17.46 |
Maximum of Months | 63.00 | 19.18 | 27.00 | 19.18 | 21.17 | 27.39 | 20.50 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.83 | 17.22 | 4.33 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
February | 24.33 | 17.74 | 0.83 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
March | 8.83 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
April | 0.50 | 19.24 | 0.00 | 19.24 | 1.17 | 25.27 | 1.17 | 26.34 |
May | 0.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.23 | 11.00 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.21 | 19.33 | 27.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.80 | 9.33 | 26.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.01 | 7.00 | 28.05 |
October | 0.33 | 19.17 | 0.00 | 19.17 | 0.33 | 23.33 | 0.33 | 24.72 |
November | 10.33 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
December | 32.33 | 17.71 | 2.50 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
Annual Sum or Average | 135.17 | 17.51 | 7.67 | 17.38 | 58.83 | 20.26 | 48.17 | 21.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 0.00 | 17.10 |
Maximum of Months | 57.83 | 19.24 | 4.33 | 19.24 | 23.33 | 28.01 | 19.33 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.83 | 16.02 | 3.00 | 16.00 | 1.00 | 16.44 | 1.00 | 16.84 |
February | 7.83 | 17.17 | 0.50 | 17.02 | 2.50 | 19.67 | 2.50 | 21.33 |
March | 3.50 | 17.71 | 0.00 | 17.71 | 2.50 | 21.33 | 2.50 | 22.82 |
April | 0.33 | 19.28 | 0.00 | 19.28 | 3.00 | 27.04 | 3.00 | 27.45 |
May | 0.50 | 18.98 | 0.00 | 18.98 | 1.50 | 25.51 | 1.50 | 26.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.08 | 13.33 | 26.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 26.38 | 30.67 | 26.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 26.18 | 33.67 | 26.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.15 | 16.17 | 27.13 |
October | 0.17 | 19.12 | 0.00 | 19.12 | 10.00 | 26.41 | 9.83 | 26.46 |
November | 3.17 | 17.37 | 0.00 | 17.37 | 2.83 | 22.49 | 2.83 | 24.32 |
December | 11.50 | 16.60 | 1.67 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
Annual Sum or Average | 49.83 | 16.60 | 5.17 | 16.48 | 122.00 | 23.43 | 117.00 | 24.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 | 16.32 |
Maximum of Months | 22.83 | 19.28 | 3.00 | 19.28 | 34.67 | 27.15 | 33.67 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 15.73 | 3.83 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
February | 8.33 | 17.27 | 0.83 | 17.06 | 0.50 | 17.60 | 0.50 | 18.10 |
March | 3.67 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.65 | 0.67 | 28.71 |
May | 0.33 | 18.93 | 0.00 | 18.93 | 5.00 | 27.73 | 2.17 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.18 | 7.17 | 26.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 27.13 | 20.83 | 26.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.84 | 11.00 | 26.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.82 | 5.67 | 27.80 |
October | 0.17 | 19.18 | 0.00 | 19.18 | 0.83 | 26.72 | 0.67 | 27.37 |
November | 3.50 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
December | 11.83 | 16.51 | 2.50 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
Annual Sum or Average | 52.83 | 16.39 | 7.17 | 16.22 | 72.17 | 22.26 | 48.67 | 23.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 | 15.65 |
Maximum of Months | 25.00 | 19.18 | 3.83 | 19.18 | 29.83 | 28.65 | 20.83 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.67 | 16.39 | 48.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 48.83 | 16.98 | 15.50 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
March | 27.00 | 16.76 | 7.67 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
April | 4.33 | 18.62 | 0.17 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
May | 6.50 | 17.63 | 0.83 | 17.91 | 0.00 | 17.91 | 0.00 | 17.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.77 | 3.67 | 24.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 25.51 | 21.83 | 25.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.59 | 7.33 | 25.50 |
September | 0.83 | 19.13 | 0.00 | 19.13 | 3.17 | 25.79 | 2.67 | 26.51 |
October | 4.33 | 18.24 | 0.33 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
November | 31.33 | 16.39 | 9.83 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
December | 77.17 | 16.16 | 28.50 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
Annual Sum or Average | 317.00 | 16.55 | 110.83 | 16.82 | 38.33 | 17.54 | 35.50 | 18.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 0.00 | 16.35 |
Maximum of Months | 116.67 | 19.13 | 48.00 | 19.13 | 23.50 | 25.79 | 21.83 | 26.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.00 | 14.89 | 10.50 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
February | 24.50 | 15.50 | 3.33 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
March | 17.00 | 16.09 | 2.00 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
April | 3.50 | 18.64 | 0.00 | 18.64 | 0.50 | 19.73 | 0.50 | 20.58 |
May | 4.50 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.21 | 13.00 | 27.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 26.70 | 28.17 | 26.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.74 | 11.00 | 26.70 |
September | 0.67 | 19.12 | 0.00 | 19.12 | 6.67 | 27.34 | 5.67 | 27.74 |
October | 3.17 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
November | 20.00 | 15.62 | 3.17 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
December | 50.67 | 15.08 | 11.67 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
Annual Sum or Average | 180.00 | 15.41 | 30.67 | 15.28 | 63.83 | 18.00 | 58.33 | 19.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 | 14.83 |
Maximum of Months | 56.00 | 19.12 | 11.67 | 19.12 | 31.17 | 27.34 | 28.17 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.00 | 15.43 | 7.50 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
February | 18.17 | 16.06 | 1.00 | 16.01 | 1.50 | 16.92 | 1.50 | 17.70 |
March | 15.00 | 16.42 | 1.17 | 16.38 | 0.50 | 16.71 | 0.50 | 17.03 |
April | 2.50 | 18.60 | 0.00 | 18.60 | 1.83 | 22.48 | 1.83 | 24.06 |
May | 4.00 | 17.14 | 0.00 | 17.14 | 1.33 | 19.76 | 1.33 | 21.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.15 | 12.50 | 26.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 26.38 | 34.83 | 26.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 26.21 | 30.00 | 26.18 |
September | 0.67 | 19.20 | 0.00 | 19.20 | 14.50 | 27.06 | 12.83 | 27.21 |
October | 2.17 | 18.56 | 0.00 | 18.56 | 4.50 | 24.38 | 4.50 | 25.51 |
November | 13.67 | 16.29 | 1.50 | 16.18 | 0.83 | 16.77 | 0.83 | 17.29 |
December | 37.50 | 15.42 | 7.00 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
Annual Sum or Average | 140.67 | 15.87 | 18.17 | 15.78 | 107.83 | 20.14 | 100.67 | 21.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 | 15.30 |
Maximum of Months | 47.00 | 19.20 | 7.50 | 19.20 | 38.17 | 27.06 | 34.83 | 27.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.50 | 14.88 | 9.17 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
February | 18.33 | 15.85 | 2.00 | 15.71 | 0.33 | 15.89 | 0.33 | 16.08 |
March | 14.00 | 16.29 | 1.67 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
April | 1.83 | 18.82 | 0.00 | 18.82 | 1.33 | 22.94 | 0.67 | 23.98 |
May | 2.17 | 17.93 | 0.00 | 17.93 | 4.67 | 25.07 | 2.17 | 25.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.44 | 6.83 | 27.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 27.10 | 23.83 | 26.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 26.96 | 11.00 | 26.77 |
September | 0.50 | 19.26 | 0.00 | 19.26 | 8.50 | 27.51 | 5.00 | 27.71 |
October | 1.83 | 18.56 | 0.00 | 18.56 | 0.67 | 21.09 | 0.67 | 22.56 |
November | 13.67 | 16.05 | 2.33 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
December | 36.67 | 15.33 | 9.17 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
Annual Sum or Average | 134.50 | 15.57 | 24.33 | 15.41 | 73.83 | 19.20 | 50.50 | 20.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 | 14.81 |
Maximum of Months | 45.50 | 19.26 | 9.17 | 19.26 | 32.67 | 27.51 | 23.83 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.75 | 0.00 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 28.18 | 16.83 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.67 | 28.17 | 16.83 | 28.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 28.18 | 16.83 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.10 | 7.83 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.17 | 28.10 | 7.83 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.10 | 7.83 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.22 | 8.00 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.83 | 28.22 | 8.00 | 28.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.22 | 8.00 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 | 30.90 | 105.33 | 30.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 112.50 | 30.90 | 105.33 | 30.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 | 30.90 | 105.33 | 30.90 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.83 | 22.97 | 31.50 | 23.16 | 3.50 | 23.15 |
February | 354.00 | 23.44 | 29.33 | 23.64 | 0.83 | 23.64 |
March | 369.33 | 23.92 | 30.00 | 24.08 | 0.00 | 24.08 |
April | 169.33 | 24.00 | 69.00 | 24.62 | 0.00 | 24.62 |
May | 150.33 | 24.00 | 87.33 | 24.74 | 0.00 | 24.74 |
June | 34.00 | 24.10 | 205.50 | 24.86 | 8.17 | 24.85 |
July | 10.17 | 24.97 | 322.33 | 24.94 | 8.67 | 24.95 |
August | 0.50 | 24.00 | 195.50 | 25.23 | 0.00 | 25.23 |
September | 30.33 | 24.00 | 191.17 | 25.10 | 16.33 | 25.03 |
October | 50.67 | 24.00 | 104.67 | 25.62 | 0.00 | 25.62 |
November | 196.33 | 23.99 | 84.67 | 24.71 | 0.00 | 24.71 |
December | 343.67 | 23.68 | 39.00 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 2125.50 | 23.64 | 1390.00 | 24.36 | 37.50 | 24.36 |
Minimum of Months | 0.50 | 22.97 | 29.33 | 23.16 | 0.00 | 23.15 |
Maximum of Months | 416.83 | 24.97 | 322.33 | 25.62 | 16.33 | 25.62 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.00 | 23.47 | 10.50 | 23.52 | 0.83 | 23.51 |
February | 376.67 | 23.77 | 2.00 | 23.78 | 0.00 | 23.78 |
March | 287.33 | 23.99 | 11.33 | 24.06 | 0.00 | 24.06 |
April | 87.00 | 24.01 | 55.33 | 24.74 | 0.00 | 24.74 |
May | 140.83 | 24.00 | 72.67 | 24.47 | 0.00 | 24.47 |
June | 4.33 | 24.00 | 215.67 | 24.56 | 0.00 | 24.56 |
July | 0.00 | 0.00 | 347.17 | 24.50 | 0.00 | 24.50 |
August | 0.00 | 0.00 | 227.83 | 24.62 | 0.00 | 24.62 |
September | 29.17 | 24.06 | 179.00 | 24.61 | 6.17 | 24.60 |
October | 73.00 | 24.00 | 75.50 | 24.96 | 0.00 | 24.96 |
November | 203.00 | 24.00 | 38.00 | 24.30 | 0.00 | 24.30 |
December | 319.67 | 23.95 | 14.00 | 24.02 | 0.00 | 24.02 |
Annual Sum or Average | 1986.00 | 23.83 | 1249.00 | 24.22 | 7.00 | 24.22 |
Minimum of Months | 0.00 | 0.00 | 2.00 | 23.52 | 0.00 | 23.51 |
Maximum of Months | 465.00 | 24.06 | 347.17 | 24.96 | 6.17 | 24.96 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.89 | 131.33 | 21.66 | 131.33 | 21.50 |
February | 453.33 | 22.59 | 41.50 | 22.43 | 41.50 | 22.29 |
March | 512.67 | 23.34 | 17.00 | 23.27 | 17.00 | 23.21 |
April | 391.67 | 23.72 | 0.00 | 23.72 | 0.00 | 23.72 |
May | 279.17 | 23.80 | 42.67 | 23.99 | 0.00 | 23.99 |
June | 64.67 | 23.88 | 138.67 | 24.22 | 0.00 | 24.22 |
July | 27.67 | 24.26 | 239.83 | 24.44 | 5.00 | 24.46 |
August | 18.67 | 23.89 | 130.83 | 24.60 | 0.00 | 24.60 |
September | 139.00 | 23.83 | 122.67 | 24.19 | 6.67 | 24.19 |
October | 336.17 | 23.77 | 5.00 | 23.79 | 0.00 | 23.79 |
November | 464.83 | 23.36 | 4.33 | 23.33 | 4.33 | 23.31 |
December | 497.00 | 22.43 | 64.17 | 22.22 | 64.17 | 22.05 |
Annual Sum or Average | 3686.83 | 23.08 | 938.00 | 23.17 | 270.00 | 23.04 |
Minimum of Months | 18.67 | 21.89 | 0.00 | 21.66 | 0.00 | 21.50 |
Maximum of Months | 512.67 | 24.26 | 239.83 | 24.60 | 131.33 | 24.60 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.58 | 378.00 | 20.42 | 378.00 | 20.35 |
February | 454.00 | 21.22 | 230.33 | 20.94 | 230.33 | 20.81 |
March | 514.00 | 21.96 | 133.33 | 21.63 | 133.33 | 21.41 |
April | 461.50 | 22.77 | 47.00 | 22.58 | 47.00 | 22.42 |
May | 347.00 | 23.14 | 53.00 | 23.11 | 24.83 | 22.97 |
June | 129.50 | 23.57 | 136.00 | 23.96 | 0.00 | 23.96 |
July | 50.33 | 23.81 | 249.83 | 24.35 | 5.83 | 24.36 |
August | 77.17 | 23.67 | 134.33 | 24.25 | 0.00 | 24.25 |
September | 247.17 | 23.21 | 109.50 | 23.62 | 9.17 | 23.63 |
October | 480.33 | 22.73 | 26.33 | 22.60 | 26.33 | 22.48 |
November | 489.00 | 21.69 | 166.67 | 21.36 | 166.67 | 21.16 |
December | 497.00 | 20.84 | 312.67 | 20.57 | 312.67 | 20.45 |
Annual Sum or Average | 4249.00 | 22.00 | 1977.00 | 21.90 | 1334.17 | 21.62 |
Minimum of Months | 50.33 | 20.58 | 26.33 | 20.42 | 0.00 | 20.35 |
Maximum of Months | 514.00 | 23.81 | 378.00 | 24.35 | 378.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.01 | 297.67 | 20.78 | 297.67 | 20.67 |
February | 454.00 | 21.81 | 145.17 | 21.51 | 145.17 | 21.33 |
March | 511.83 | 22.79 | 46.00 | 22.61 | 46.00 | 22.45 |
April | 382.83 | 23.47 | 5.17 | 23.50 | 0.00 | 23.50 |
May | 281.33 | 23.46 | 57.50 | 23.73 | 0.00 | 23.73 |
June | 48.00 | 23.82 | 227.00 | 24.37 | 0.00 | 24.37 |
July | 10.67 | 25.72 | 366.67 | 24.65 | 6.50 | 24.69 |
August | 33.17 | 24.02 | 217.67 | 24.54 | 1.83 | 24.56 |
September | 200.83 | 23.48 | 132.17 | 23.95 | 7.00 | 23.99 |
October | 419.83 | 23.38 | 4.83 | 23.40 | 0.00 | 23.40 |
November | 478.50 | 22.68 | 33.00 | 22.56 | 33.00 | 22.45 |
December | 497.00 | 21.78 | 153.50 | 21.49 | 153.50 | 21.31 |
Annual Sum or Average | 3820.00 | 22.55 | 1686.33 | 22.68 | 690.67 | 22.45 |
Minimum of Months | 10.67 | 21.01 | 4.83 | 20.78 | 0.00 | 20.67 |
Maximum of Months | 511.83 | 25.72 | 366.67 | 24.65 | 297.67 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.17 | 21.23 | 279.83 | 20.94 | 278.50 | 20.79 |
February | 417.17 | 21.96 | 139.17 | 21.70 | 130.50 | 21.49 |
March | 434.17 | 22.65 | 70.17 | 22.54 | 48.67 | 22.37 |
April | 301.83 | 23.27 | 69.00 | 23.57 | 4.67 | 23.60 |
May | 200.83 | 23.29 | 131.83 | 23.82 | 0.33 | 23.82 |
June | 79.50 | 24.82 | 297.67 | 24.61 | 26.67 | 24.77 |
July | 56.83 | 26.48 | 408.67 | 24.86 | 48.83 | 25.06 |
August | 57.50 | 24.90 | 315.17 | 24.56 | 22.67 | 24.69 |
September | 156.50 | 23.89 | 209.50 | 24.36 | 26.67 | 24.52 |
October | 314.50 | 23.25 | 48.17 | 23.48 | 1.67 | 23.50 |
November | 447.50 | 22.64 | 48.83 | 22.50 | 44.50 | 22.36 |
December | 492.00 | 21.72 | 174.17 | 21.41 | 174.17 | 21.22 |
Annual Sum or Average | 3455.50 | 22.58 | 2192.17 | 22.88 | 807.83 | 22.72 |
Minimum of Months | 56.83 | 21.23 | 48.17 | 20.94 | 0.33 | 20.79 |
Maximum of Months | 497.17 | 26.48 | 408.67 | 24.86 | 278.50 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 433.33 | 21.39 | 262.17 | 21.20 | 241.50 | 21.02 |
February | 335.17 | 22.11 | 167.17 | 22.12 | 118.33 | 21.91 |
March | 373.67 | 22.62 | 116.67 | 22.70 | 47.83 | 22.55 |
April | 294.00 | 23.21 | 81.83 | 23.52 | 11.83 | 23.58 |
May | 236.83 | 23.12 | 130.17 | 23.60 | 12.67 | 23.58 |
June | 99.17 | 24.22 | 254.67 | 24.45 | 18.33 | 24.57 |
July | 62.50 | 26.08 | 383.67 | 24.90 | 48.67 | 25.08 |
August | 76.17 | 25.29 | 327.67 | 24.83 | 43.33 | 24.99 |
September | 157.00 | 23.98 | 254.67 | 24.45 | 33.83 | 24.63 |
October | 260.50 | 23.38 | 145.50 | 23.83 | 16.50 | 23.93 |
November | 337.00 | 22.69 | 128.67 | 22.89 | 51.17 | 22.76 |
December | 402.33 | 21.87 | 184.67 | 21.75 | 139.33 | 21.50 |
Annual Sum or Average | 3067.67 | 22.72 | 2437.50 | 23.15 | 783.33 | 23.01 |
Minimum of Months | 62.50 | 21.39 | 81.83 | 21.20 | 11.83 | 21.02 |
Maximum of Months | 433.33 | 26.08 | 383.67 | 24.90 | 241.50 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.17 | 21.79 | 192.33 | 21.44 | 191.50 | 21.25 |
February | 368.00 | 22.89 | 78.17 | 22.80 | 54.50 | 22.62 |
March | 280.67 | 23.69 | 60.83 | 23.80 | 10.33 | 23.76 |
April | 72.67 | 24.66 | 170.17 | 25.01 | 15.83 | 25.14 |
May | 132.67 | 23.97 | 195.50 | 24.50 | 12.50 | 24.59 |
June | 35.67 | 26.42 | 380.33 | 24.81 | 29.67 | 24.95 |
July | 82.50 | 26.64 | 476.00 | 25.09 | 82.50 | 25.29 |
August | 57.00 | 26.50 | 472.67 | 24.87 | 57.00 | 25.03 |
September | 92.50 | 24.60 | 248.00 | 24.74 | 25.83 | 24.89 |
October | 144.17 | 24.05 | 113.67 | 24.50 | 7.17 | 24.58 |
November | 266.50 | 23.67 | 65.17 | 23.97 | 2.33 | 23.96 |
December | 378.33 | 23.35 | 36.83 | 23.27 | 22.83 | 23.14 |
Annual Sum or Average | 2395.83 | 23.44 | 2489.67 | 23.91 | 512.00 | 23.86 |
Minimum of Months | 35.67 | 21.79 | 36.83 | 21.44 | 2.33 | 21.25 |
Maximum of Months | 485.17 | 26.64 | 476.00 | 25.09 | 191.50 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.92 | 494.83 | 19.92 | 494.83 | 19.91 |
February | 454.00 | 20.43 | 385.50 | 20.34 | 385.50 | 20.31 |
March | 514.00 | 21.07 | 263.50 | 20.81 | 263.50 | 20.68 |
April | 477.83 | 22.16 | 76.33 | 21.93 | 76.33 | 21.75 |
May | 381.00 | 22.69 | 65.67 | 22.65 | 34.17 | 22.47 |
June | 127.33 | 23.37 | 168.17 | 23.92 | 0.00 | 23.92 |
July | 44.17 | 23.93 | 274.83 | 24.48 | 4.67 | 24.50 |
August | 123.33 | 23.43 | 147.50 | 24.06 | 0.67 | 24.06 |
September | 291.33 | 22.68 | 98.00 | 23.10 | 15.50 | 23.06 |
October | 499.83 | 22.09 | 67.17 | 21.90 | 67.17 | 21.74 |
November | 489.00 | 20.85 | 282.00 | 20.60 | 282.00 | 20.48 |
December | 497.00 | 20.05 | 461.83 | 20.01 | 461.83 | 19.99 |
Annual Sum or Average | 4400.83 | 21.38 | 2785.33 | 21.32 | 2086.17 | 21.06 |
Minimum of Months | 44.17 | 19.92 | 65.67 | 19.92 | 0.00 | 19.91 |
Maximum of Months | 514.00 | 23.93 | 494.83 | 24.48 | 494.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.01 | 397.17 | 19.96 | 397.17 | 19.94 |
February | 377.00 | 20.88 | 254.00 | 20.61 | 252.50 | 20.49 |
March | 409.67 | 21.58 | 172.83 | 21.22 | 168.17 | 21.01 |
April | 301.00 | 22.33 | 90.83 | 22.39 | 50.67 | 22.21 |
May | 228.83 | 22.62 | 109.17 | 22.90 | 28.50 | 22.68 |
June | 103.83 | 24.48 | 230.67 | 24.63 | 31.50 | 24.84 |
July | 67.17 | 26.14 | 327.83 | 25.01 | 50.33 | 25.23 |
August | 77.50 | 24.32 | 242.67 | 24.60 | 20.83 | 24.75 |
September | 187.67 | 23.30 | 154.83 | 24.00 | 28.83 | 24.17 |
October | 342.50 | 22.38 | 48.83 | 22.30 | 36.17 | 22.15 |
November | 412.83 | 21.33 | 189.00 | 20.98 | 189.00 | 20.80 |
December | 422.00 | 20.10 | 360.00 | 19.99 | 360.00 | 19.94 |
Annual Sum or Average | 3357.00 | 21.65 | 2577.83 | 21.83 | 1613.67 | 21.57 |
Minimum of Months | 67.17 | 20.01 | 48.83 | 19.96 | 20.83 | 19.94 |
Maximum of Months | 427.00 | 26.14 | 397.17 | 25.01 | 397.17 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 446.00 | 20.81 | 335.50 | 20.63 | 321.67 | 20.50 |
February | 356.00 | 21.55 | 233.83 | 21.50 | 188.83 | 21.27 |
March | 395.33 | 21.81 | 210.00 | 21.80 | 143.00 | 21.57 |
April | 330.33 | 22.38 | 121.50 | 22.59 | 54.17 | 22.48 |
May | 276.50 | 22.61 | 139.83 | 22.91 | 40.33 | 22.74 |
June | 146.00 | 23.65 | 226.00 | 24.18 | 17.33 | 24.30 |
July | 85.00 | 25.20 | 343.17 | 24.78 | 45.17 | 24.97 |
August | 117.67 | 24.37 | 297.00 | 24.60 | 36.17 | 24.77 |
September | 191.83 | 23.51 | 246.00 | 24.20 | 39.50 | 24.38 |
October | 294.50 | 22.77 | 158.67 | 23.24 | 36.17 | 23.24 |
November | 365.50 | 21.93 | 200.67 | 21.93 | 136.83 | 21.71 |
December | 434.83 | 20.97 | 287.50 | 20.75 | 264.00 | 20.56 |
Annual Sum or Average | 3439.50 | 22.11 | 2799.67 | 22.45 | 1323.17 | 22.23 |
Minimum of Months | 85.00 | 20.81 | 121.50 | 20.63 | 17.33 | 20.50 |
Maximum of Months | 446.00 | 25.20 | 343.17 | 24.78 | 321.67 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.50 | 20.32 | 445.83 | 20.21 | 445.83 | 20.18 |
February | 431.67 | 21.00 | 276.33 | 20.76 | 270.67 | 20.63 |
March | 463.17 | 21.61 | 187.67 | 21.35 | 171.00 | 21.14 |
April | 356.00 | 22.54 | 87.17 | 22.63 | 41.83 | 22.52 |
May | 242.83 | 22.81 | 149.83 | 23.21 | 35.83 | 23.11 |
June | 93.83 | 23.94 | 280.67 | 24.35 | 17.17 | 24.46 |
July | 63.83 | 25.72 | 388.00 | 24.82 | 43.17 | 24.98 |
August | 81.50 | 24.24 | 295.00 | 24.53 | 21.33 | 24.64 |
September | 212.83 | 23.13 | 191.17 | 23.89 | 23.33 | 24.00 |
October | 393.50 | 22.50 | 68.00 | 22.57 | 31.33 | 22.47 |
November | 459.33 | 21.51 | 189.17 | 21.15 | 186.67 | 20.95 |
December | 494.50 | 20.48 | 372.00 | 20.28 | 372.00 | 20.20 |
Annual Sum or Average | 3794.50 | 21.73 | 2930.83 | 21.98 | 1660.17 | 21.71 |
Minimum of Months | 63.83 | 20.32 | 68.00 | 20.21 | 17.17 | 20.18 |
Maximum of Months | 501.50 | 25.72 | 445.83 | 24.82 | 445.83 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 497.17 | 19.64 | 497.17 | 19.64 |
February | 454.00 | 20.04 | 430.67 | 20.00 | 430.67 | 19.99 |
March | 514.00 | 20.50 | 364.67 | 20.31 | 364.67 | 20.24 |
April | 479.33 | 21.42 | 189.50 | 21.05 | 189.50 | 20.84 |
May | 400.50 | 22.18 | 119.33 | 21.99 | 88.33 | 21.72 |
June | 167.17 | 22.93 | 165.33 | 23.62 | 0.50 | 23.62 |
July | 83.50 | 23.66 | 273.83 | 24.34 | 10.17 | 24.40 |
August | 160.00 | 23.11 | 150.00 | 23.77 | 4.50 | 23.80 |
September | 333.67 | 22.25 | 128.00 | 22.52 | 55.50 | 22.39 |
October | 502.00 | 21.24 | 198.00 | 20.91 | 198.00 | 20.72 |
November | 489.00 | 20.19 | 385.50 | 20.05 | 385.50 | 20.00 |
December | 497.00 | 19.81 | 482.83 | 19.80 | 482.83 | 19.79 |
Annual Sum or Average | 4582.17 | 20.94 | 3384.83 | 20.91 | 2707.33 | 20.67 |
Minimum of Months | 83.50 | 19.65 | 119.33 | 19.64 | 0.50 | 19.64 |
Maximum of Months | 514.00 | 23.66 | 497.17 | 24.34 | 497.17 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 477.83 | 19.84 | 477.83 | 19.83 |
February | 452.83 | 20.55 | 335.33 | 20.31 | 335.33 | 20.21 |
March | 496.17 | 21.17 | 266.33 | 20.78 | 266.33 | 20.59 |
April | 362.00 | 21.72 | 153.67 | 21.54 | 114.67 | 21.26 |
May | 276.33 | 22.24 | 154.17 | 22.39 | 61.00 | 22.07 |
June | 127.67 | 24.06 | 281.67 | 24.40 | 36.33 | 24.60 |
July | 90.50 | 25.57 | 391.67 | 24.81 | 57.83 | 25.02 |
August | 97.17 | 23.77 | 309.00 | 24.34 | 20.67 | 24.45 |
September | 233.17 | 22.81 | 195.00 | 23.48 | 47.50 | 23.52 |
October | 445.00 | 21.91 | 127.33 | 21.52 | 124.17 | 21.26 |
November | 487.33 | 20.64 | 323.83 | 20.36 | 323.83 | 20.24 |
December | 497.00 | 19.93 | 462.33 | 19.87 | 462.33 | 19.85 |
Annual Sum or Average | 4067.17 | 21.27 | 3478.17 | 21.45 | 2327.83 | 21.18 |
Minimum of Months | 90.50 | 19.87 | 127.33 | 19.84 | 20.67 | 19.83 |
Maximum of Months | 502.00 | 25.57 | 477.83 | 24.81 | 477.83 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.33 | 20.46 | 377.00 | 20.24 | 373.50 | 20.14 |
February | 376.50 | 21.09 | 265.17 | 20.90 | 237.50 | 20.70 |
March | 408.17 | 21.14 | 278.00 | 21.04 | 225.33 | 20.81 |
April | 351.33 | 21.65 | 188.50 | 21.63 | 131.83 | 21.37 |
May | 305.33 | 22.16 | 174.83 | 22.34 | 80.50 | 22.06 |
June | 171.33 | 23.22 | 221.50 | 23.93 | 21.00 | 24.05 |
July | 118.00 | 24.64 | 329.33 | 24.68 | 50.83 | 24.88 |
August | 147.50 | 23.90 | 289.67 | 24.38 | 39.17 | 24.54 |
September | 221.00 | 22.88 | 243.33 | 23.63 | 59.67 | 23.68 |
October | 339.50 | 22.00 | 202.50 | 22.17 | 106.17 | 21.94 |
November | 406.17 | 21.25 | 257.67 | 21.09 | 214.33 | 20.85 |
December | 458.17 | 20.52 | 338.83 | 20.24 | 334.17 | 20.11 |
Annual Sum or Average | 3770.33 | 21.61 | 3166.33 | 21.85 | 1874.00 | 21.58 |
Minimum of Months | 118.00 | 20.46 | 174.83 | 20.24 | 21.00 | 20.11 |
Maximum of Months | 467.33 | 24.64 | 377.00 | 24.68 | 373.50 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.00 | 459.83 | 19.91 | 459.83 | 19.88 |
February | 436.17 | 20.59 | 331.00 | 20.38 | 326.50 | 20.28 |
March | 473.00 | 21.05 | 272.00 | 20.79 | 258.83 | 20.62 |
April | 382.67 | 21.87 | 160.67 | 21.76 | 118.83 | 21.52 |
May | 284.17 | 22.38 | 169.50 | 22.63 | 66.67 | 22.43 |
June | 140.67 | 23.48 | 272.33 | 24.13 | 19.67 | 24.24 |
July | 95.50 | 25.01 | 367.50 | 24.74 | 52.83 | 24.91 |
August | 115.33 | 23.76 | 286.67 | 24.34 | 23.00 | 24.44 |
September | 248.67 | 22.61 | 195.00 | 23.30 | 47.17 | 23.29 |
October | 421.00 | 21.77 | 150.00 | 21.58 | 122.17 | 21.35 |
November | 470.00 | 20.85 | 286.67 | 20.54 | 286.17 | 20.39 |
December | 495.67 | 20.14 | 420.67 | 20.00 | 420.67 | 19.94 |
Annual Sum or Average | 4064.83 | 21.33 | 3371.83 | 21.53 | 2202.33 | 21.26 |
Minimum of Months | 95.50 | 20.00 | 150.00 | 19.91 | 19.67 | 19.88 |
Maximum of Months | 502.00 | 25.01 | 459.83 | 24.74 | 459.83 | 24.91 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 26.19 | 364.67 | 27.00 | 0.00 | 27.00 |
February | 2.17 | 27.00 | 426.83 | 27.00 | 2.17 | 27.00 |
March | 5.50 | 27.00 | 512.50 | 27.00 | 5.50 | 27.00 |
April | 17.67 | 27.00 | 485.00 | 27.00 | 17.67 | 27.00 |
May | 1.50 | 27.00 | 508.00 | 27.00 | 1.50 | 27.00 |
June | 16.00 | 27.00 | 496.00 | 27.00 | 16.00 | 27.00 |
July | 83.50 | 27.00 | 497.00 | 27.00 | 83.50 | 27.00 |
August | 154.17 | 27.16 | 514.00 | 27.08 | 154.17 | 27.09 |
September | 9.50 | 27.00 | 485.00 | 27.00 | 9.50 | 27.00 |
October | 7.67 | 27.00 | 502.00 | 27.00 | 7.67 | 27.00 |
November | 4.33 | 27.00 | 489.00 | 27.00 | 4.33 | 27.00 |
December | 1.83 | 27.00 | 494.33 | 27.00 | 1.83 | 27.00 |
Annual Sum or Average | 305.33 | 27.08 | 5774.33 | 27.01 | 303.83 | 27.01 |
Minimum of Months | 1.50 | 26.19 | 364.67 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 154.17 | 27.16 | 514.00 | 27.08 | 154.17 | 27.09 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 137.83 | 25.51 | 153.50 | 26.29 | 0.00 | 26.29 |
February | 12.00 | 27.00 | 277.17 | 27.00 | 0.00 | 27.00 |
March | 5.33 | 27.00 | 459.33 | 27.00 | 0.00 | 27.00 |
April | 3.83 | 27.00 | 481.50 | 27.00 | 3.83 | 27.00 |
May | 1.17 | 27.00 | 503.00 | 27.00 | 1.17 | 27.00 |
June | 8.00 | 27.00 | 496.00 | 27.00 | 8.00 | 27.00 |
July | 22.00 | 27.00 | 497.00 | 27.00 | 22.00 | 27.00 |
August | 31.50 | 27.36 | 514.00 | 27.04 | 31.50 | 27.06 |
September | 5.17 | 27.00 | 485.00 | 27.00 | 5.17 | 27.00 |
October | 0.50 | 27.00 | 502.00 | 27.00 | 0.50 | 27.00 |
November | 0.00 | 0.00 | 440.83 | 27.00 | 0.00 | 27.00 |
December | 12.00 | 27.00 | 304.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 239.33 | 26.19 | 5114.17 | 26.97 | 72.17 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 153.50 | 26.29 | 0.00 | 26.29 |
Maximum of Months | 137.83 | 27.36 | 514.00 | 27.04 | 31.50 | 27.06 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 319.33 | 24.67 | 87.00 | 24.80 | 28.17 | 24.61 |
February | 47.33 | 26.94 | 162.83 | 26.99 | 0.00 | 26.99 |
March | 21.83 | 27.00 | 337.33 | 27.00 | 0.00 | 27.00 |
April | 4.67 | 27.00 | 423.17 | 27.00 | 4.67 | 27.00 |
May | 24.00 | 25.92 | 468.67 | 26.95 | 1.67 | 26.95 |
June | 13.00 | 27.00 | 496.00 | 27.00 | 13.00 | 27.00 |
July | 44.00 | 27.00 | 497.00 | 27.00 | 44.00 | 27.00 |
August | 47.00 | 27.26 | 514.00 | 27.04 | 47.00 | 27.06 |
September | 9.67 | 27.00 | 472.50 | 27.00 | 9.67 | 27.00 |
October | 1.00 | 27.00 | 450.33 | 27.00 | 1.00 | 27.00 |
November | 22.33 | 27.00 | 290.00 | 27.00 | 0.00 | 27.00 |
December | 65.83 | 27.00 | 165.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 620.00 | 25.77 | 4364.17 | 26.82 | 149.17 | 26.80 |
Minimum of Months | 1.00 | 24.67 | 87.00 | 24.80 | 0.00 | 24.61 |
Maximum of Months | 319.33 | 27.26 | 514.00 | 27.04 | 47.00 | 27.06 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 124.67 | 27.00 | 502.00 | 27.00 | 124.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 474.67 | 27.00 | 508.00 | 27.00 | 474.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.81 | 514.00 | 27.81 | 514.00 | 27.81 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5532.33 | 27.08 | 5943.00 | 27.07 | 5532.33 | 27.07 |
Minimum of Months | 124.67 | 27.00 | 454.00 | 27.00 | 124.67 | 27.00 |
Maximum of Months | 514.00 | 27.81 | 514.00 | 27.81 | 514.00 | 27.81 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98619 | 13.69948 | 0.60276 | 12.87259 |
February | 454.00000 | 27.00000 | 14.95881 | 0.70391 | 15.60747 |
March | 514.00000 | 26.99999 | 16.91443 | 0.78927 | 18.23881 |
April | 485.00000 | 27.00003 | 19.95972 | 0.87978 | 21.40723 |
May | 508.00000 | 27.00014 | 22.25983 | 0.13598 | 5.53617 |
June | 496.00000 | 27.00042 | 25.60908 | 0.24621 | 6.34906 |
July | 497.00000 | 27.00027 | 26.65601 | 0.32293 | 7.26933 |
August | 514.00000 | 27.04903 | 26.08200 | 0.36611 | 8.04614 |
September | 485.00000 | 27.00043 | 25.40155 | 0.17262 | 5.75993 |
October | 502.00000 | 27.00006 | 22.37376 | 0.83398 | 19.72809 |
November | 489.00000 | 27.00000 | 18.52057 | 0.80693 | 18.81743 |
December | 497.00000 | 26.99999 | 14.85346 | 0.76959 | 17.61837 |
Annual Sum or Average | 5943.00000 | 27.00318 | 20.64569 | 0.55088 | 13.06921 |
Minimum of Months | 454.00000 | 26.98619 | 13.69948 | 0.13598 | 5.53617 |
Maximum of Months | 514.00000 | 27.04903 | 26.65601 | 0.87978 | 21.40723 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.53953 | 13.81110 | 0.38777 | 9.11636 |
February | 454.00000 | 27.00000 | 14.94936 | 0.55521 | 11.69544 |
March | 514.00000 | 26.99999 | 16.89840 | 0.63879 | 13.78860 |
April | 485.00000 | 27.00002 | 19.93256 | 0.74052 | 16.70826 |
May | 508.00000 | 27.00013 | 22.27374 | 0.04303 | 5.34042 |
June | 496.00000 | 27.00040 | 25.62378 | 0.15516 | 5.64744 |
July | 497.00000 | 27.00026 | 26.66068 | 0.21496 | 6.10046 |
August | 514.00000 | 27.02499 | 26.10441 | 0.22474 | 6.28035 |
September | 485.00000 | 27.00039 | 25.49522 | 0.09001 | 5.40731 |
October | 502.00000 | 27.00006 | 22.35686 | 0.72936 | 16.31522 |
November | 489.00000 | 27.00000 | 18.49503 | 0.64527 | 13.94988 |
December | 497.00000 | 26.99999 | 14.82869 | 0.55147 | 11.60122 |
Annual Sum or Average | 5943.00000 | 26.96337 | 20.65758 | 0.41306 | 10.13817 |
Minimum of Months | 454.00000 | 26.53953 | 13.81110 | 0.04303 | 5.34042 |
Maximum of Months | 514.00000 | 27.02499 | 26.66068 | 0.74052 | 16.70826 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.46524 | 14.57907 | 0.12252 | 8.21826 |
February | 454.00000 | 26.99401 | 14.95131 | 0.48523 | 10.26513 |
March | 514.00000 | 26.99999 | 16.90564 | 0.56527 | 12.05443 |
April | 485.00000 | 27.00002 | 19.94859 | 0.67839 | 15.02060 |
May | 508.00000 | 26.94301 | 22.32587 | -0.0204 | 6.03719 |
June | 496.00000 | 27.00041 | 25.63528 | 0.14467 | 5.74750 |
July | 497.00000 | 27.00027 | 26.66885 | 0.21831 | 6.26956 |
August | 514.00000 | 27.02432 | 26.11341 | 0.21699 | 6.37445 |
September | 485.00000 | 26.99965 | 25.59131 | 0.04789 | 5.55895 |
October | 502.00000 | 27.00006 | 22.38232 | 0.65897 | 14.38261 |
November | 489.00000 | 27.00000 | 18.50812 | 0.55601 | 11.78568 |
December | 497.00000 | 27.00000 | 14.84027 | 0.47288 | 10.00104 |
Annual Sum or Average | 5943.00000 | 26.86717 | 20.74345 | 0.34389 | 9.29276 |
Minimum of Months | 454.00000 | 25.46524 | 14.57907 | -0.0204 | 5.55895 |
Maximum of Months | 514.00000 | 27.02432 | 26.66885 | 0.67839 | 15.02060 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00038 | 30.00068 | 0.97263 | 25.02141 |
February | 454.00000 | 27.00047 | 27.33275 | 1.14395 | 32.57747 |
March | 514.00000 | 27.00016 | 22.31808 | 1.26764 | 38.62459 |
April | 485.00000 | 27.00081 | 21.71351 | 1.40942 | 46.02542 |
May | 508.00000 | 27.00047 | 29.15292 | 0.44261 | 9.13213 |
June | 496.00000 | 27.00207 | 29.67138 | 0.69159 | 15.08426 |
July | 497.00000 | 27.00637 | 30.15894 | 0.92010 | 22.89887 |
August | 514.00000 | 27.81441 | 27.21415 | 1.30710 | 40.35416 |
September | 485.00000 | 27.00053 | 31.11112 | 0.50913 | 10.50030 |
October | 502.00000 | 27.00045 | 27.26219 | 1.20856 | 35.67359 |
November | 489.00000 | 27.00019 | 22.67077 | 1.29843 | 40.19485 |
December | 497.00000 | 27.00020 | 19.60757 | 1.38458 | 44.69858 |
Annual Sum or Average | 5943.00000 | 27.07144 | 26.51543 | 1.04601 | 30.05910 |
Minimum of Months | 454.00000 | 27.00016 | 19.60757 | 0.44261 | 9.13213 |
Maximum of Months | 514.00000 | 27.81441 | 31.11112 | 1.40942 | 46.02542 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.36870 | 12.79579 | 0.00828 | 6.96122 |
February | 454.00000 | 23.83916 | 14.59125 | 0.12857 | 6.52747 |
March | 514.00000 | 24.21446 | 15.59586 | 0.23186 | 6.48009 |
April | 485.00000 | 24.42585 | 19.03169 | 0.30800 | 7.31672 |
May | 508.00000 | 24.44266 | 22.73590 | -0.5288 | 11.81734 |
June | 496.00000 | 24.42553 | 31.24866 | -0.4541 | 10.10861 |
July | 497.00000 | 24.61673 | 35.59653 | -0.3538 | 8.92378 |
August | 514.00000 | 24.47671 | 30.79458 | -0.4220 | 9.66965 |
September | 485.00000 | 24.51751 | 30.40495 | -0.4290 | 9.97963 |
October | 502.00000 | 24.54753 | 21.16204 | 0.36391 | 8.32984 |
November | 489.00000 | 24.51311 | 16.75331 | 0.31641 | 7.58063 |
December | 497.00000 | 24.13436 | 13.86105 | 0.20575 | 6.70989 |
Annual Sum or Average | 5943.00000 | 24.29579 | 22.09569 | -0.0545 | 8.38351 |
Minimum of Months | 454.00000 | 23.36870 | 12.79579 | -0.5288 | 6.48009 |
Maximum of Months | 514.00000 | 24.61673 | 35.59653 | 0.36391 | 11.81734 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.58331 | 14.26801 | 0.03094 | 5.97063 |
February | 454.00000 | 23.93350 | 16.01940 | 0.14581 | 5.91066 |
March | 514.00000 | 24.19276 | 16.95498 | 0.24062 | 6.39344 |
April | 485.00000 | 24.32592 | 20.12084 | 0.31389 | 7.29712 |
May | 508.00000 | 24.30641 | 24.12672 | -0.5499 | 11.90730 |
June | 496.00000 | 24.26503 | 32.49024 | -0.4655 | 9.92578 |
July | 497.00000 | 24.35700 | 36.38792 | -0.3923 | 8.69214 |
August | 514.00000 | 24.28817 | 31.94532 | -0.4363 | 9.34051 |
September | 485.00000 | 24.29603 | 31.88471 | -0.4785 | 10.33747 |
October | 502.00000 | 24.36466 | 23.03974 | 0.33583 | 7.63259 |
November | 489.00000 | 24.33840 | 18.50885 | 0.28694 | 6.94671 |
December | 497.00000 | 24.19755 | 15.32469 | 0.21725 | 6.28714 |
Annual Sum or Average | 5943.00000 | 24.20541 | 23.47001 | -0.0651 | 8.07101 |
Minimum of Months | 454.00000 | 23.58331 | 14.26801 | -0.5499 | 5.91066 |
Maximum of Months | 514.00000 | 24.36466 | 36.38792 | 0.33583 | 11.90730 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.89209 | 15.82784 | -0.3937 | 9.41135 |
February | 454.00000 | 22.59063 | 17.95458 | -0.2012 | 7.15017 |
March | 514.00000 | 23.34528 | 19.00746 | 0.00295 | 5.89255 |
April | 485.00000 | 23.83996 | 22.12202 | 0.16350 | 5.86461 |
May | 508.00000 | 24.05847 | 25.26640 | -0.6706 | 15.15972 |
June | 496.00000 | 24.14342 | 33.21732 | -0.5424 | 11.44874 |
July | 497.00000 | 24.24514 | 37.12193 | -0.4716 | 10.04450 |
August | 514.00000 | 24.20943 | 32.52710 | -0.5164 | 10.84556 |
September | 485.00000 | 24.13847 | 32.73266 | -0.5656 | 12.25671 |
October | 502.00000 | 23.94042 | 25.08173 | 0.20704 | 6.09264 |
November | 489.00000 | 23.39707 | 20.53609 | 0.02278 | 5.89569 |
December | 497.00000 | 22.43481 | 17.54670 | -0.2439 | 7.76281 |
Annual Sum or Average | 5943.00000 | 23.52594 | 24.95454 | -0.2689 | 9.00797 |
Minimum of Months | 454.00000 | 21.89209 | 15.82784 | -0.6706 | 5.86461 |
Maximum of Months | 514.00000 | 24.24514 | 37.12193 | 0.20704 | 15.15972 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57653 | 16.11716 | -0.7476 | 19.15518 |
February | 454.00000 | 21.22330 | 18.82780 | -0.5551 | 13.58247 |
March | 514.00000 | 21.96099 | 20.53429 | -0.3500 | 9.98987 |
April | 485.00000 | 22.83316 | 23.75869 | -0.0945 | 6.91824 |
May | 508.00000 | 23.50964 | 26.16538 | -0.8737 | 23.65644 |
June | 496.00000 | 24.02208 | 33.32002 | -0.5841 | 12.90376 |
July | 497.00000 | 24.22796 | 36.97272 | -0.4703 | 10.21045 |
August | 514.00000 | 24.15452 | 32.64731 | -0.5372 | 11.55546 |
September | 485.00000 | 23.73999 | 33.75654 | -0.7181 | 17.95427 |
October | 502.00000 | 22.78126 | 27.16538 | -0.0913 | 6.67072 |
November | 489.00000 | 21.69182 | 22.36197 | -0.4100 | 11.00682 |
December | 497.00000 | 20.83509 | 18.36591 | -0.6578 | 17.01446 |
Annual Sum or Average | 5943.00000 | 22.64072 | 25.87295 | -0.5078 | 13.39380 |
Minimum of Months | 454.00000 | 20.57653 | 16.11716 | -0.8737 | 6.67072 |
Maximum of Months | 514.00000 | 24.22796 | 36.97272 | -0.0913 | 23.65644 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.00728 | 14.06828 | -0.6234 | 15.50080 |
February | 454.00000 | 21.81258 | 16.64459 | -0.3843 | 10.30892 |
March | 514.00000 | 22.79029 | 17.60273 | -0.1239 | 6.92127 |
April | 485.00000 | 23.61293 | 20.39930 | 0.11268 | 5.89382 |
May | 508.00000 | 23.85648 | 24.01913 | -0.7121 | 17.47226 |
June | 496.00000 | 24.23394 | 31.64492 | -0.4566 | 10.17520 |
July | 497.00000 | 24.48308 | 35.21496 | -0.3202 | 8.22796 |
August | 514.00000 | 24.29529 | 31.18897 | -0.4315 | 9.75628 |
September | 485.00000 | 23.96602 | 31.86921 | -0.6158 | 14.91550 |
October | 502.00000 | 23.50775 | 23.60910 | 0.09676 | 5.80586 |
November | 489.00000 | 22.71652 | 19.52516 | -0.1326 | 6.79792 |
December | 497.00000 | 21.78431 | 16.26629 | -0.3862 | 10.11630 |
Annual Sum or Average | 5943.00000 | 23.18183 | 23.54559 | -0.3319 | 10.16407 |
Minimum of Months | 454.00000 | 21.00728 | 14.06828 | -0.7121 | 5.80586 |
Maximum of Months | 514.00000 | 24.48308 | 35.21496 | 0.11268 | 17.47226 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26362 | 13.86004 | -0.5595 | 14.68397 |
February | 454.00000 | 22.17469 | 16.15846 | -0.2874 | 10.09302 |
March | 514.00000 | 22.89302 | 17.11986 | -0.0730 | 7.48805 |
April | 485.00000 | 23.66024 | 20.06857 | 0.16926 | 7.23037 |
May | 508.00000 | 23.90273 | 23.44892 | -0.6178 | 15.70186 |
June | 496.00000 | 24.32413 | 31.26985 | -0.3184 | 9.64289 |
July | 497.00000 | 24.54113 | 34.84358 | -0.1730 | 8.22811 |
August | 514.00000 | 24.31566 | 30.89177 | -0.3164 | 9.12538 |
September | 485.00000 | 24.14447 | 31.22679 | -0.4786 | 12.94445 |
October | 502.00000 | 23.63516 | 23.01548 | 0.15780 | 6.71072 |
November | 489.00000 | 22.78505 | 19.30184 | -0.1080 | 7.11745 |
December | 497.00000 | 21.74544 | 16.27250 | -0.3966 | 10.73366 |
Annual Sum or Average | 5943.00000 | 23.28970 | 23.16488 | -0.2507 | 9.97986 |
Minimum of Months | 454.00000 | 21.26362 | 13.86004 | -0.6178 | 6.71072 |
Maximum of Months | 514.00000 | 24.54113 | 34.84358 | 0.16926 | 15.70186 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.81759 | 13.17567 | -0.4024 | 13.89008 |
February | 454.00000 | 22.72185 | 15.07758 | -0.1127 | 10.48342 |
March | 514.00000 | 23.04541 | 16.54938 | -0.0048 | 8.34877 |
April | 485.00000 | 23.61731 | 19.99332 | 0.16508 | 7.59605 |
May | 508.00000 | 23.75926 | 23.69162 | -0.6894 | 18.67230 |
June | 496.00000 | 24.23361 | 31.43153 | -0.4104 | 10.57712 |
July | 497.00000 | 24.55232 | 34.87114 | -0.2263 | 8.41169 |
August | 514.00000 | 24.46101 | 30.54377 | -0.2664 | 9.15990 |
September | 485.00000 | 24.20057 | 30.91938 | -0.4048 | 12.88648 |
October | 502.00000 | 23.80091 | 22.34427 | 0.25292 | 8.59965 |
November | 489.00000 | 23.21637 | 18.17870 | 0.04038 | 8.51911 |
December | 497.00000 | 22.35406 | 15.16272 | -0.2217 | 10.73224 |
Annual Sum or Average | 5943.00000 | 23.48663 | 22.70846 | -0.1916 | 10.66716 |
Minimum of Months | 454.00000 | 21.81759 | 13.17567 | -0.6894 | 7.59605 |
Maximum of Months | 514.00000 | 24.55232 | 34.87114 | 0.25292 | 18.67230 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.87473 | 13.33521 | -0.3896 | 11.09828 |
February | 454.00000 | 23.17509 | 14.78919 | -0.0194 | 7.77290 |
March | 514.00000 | 23.95649 | 15.43191 | 0.21551 | 7.09946 |
April | 485.00000 | 24.46345 | 18.52121 | 0.42838 | 9.77031 |
May | 508.00000 | 24.28087 | 22.79398 | -0.4438 | 11.65284 |
June | 496.00000 | 24.50614 | 30.75120 | -0.2009 | 7.89961 |
July | 497.00000 | 24.78363 | 34.29649 | -0.0196 | 8.02262 |
August | 514.00000 | 24.61712 | 30.09071 | -0.0975 | 7.65276 |
September | 485.00000 | 24.39615 | 30.51631 | -0.3516 | 10.32290 |
October | 502.00000 | 24.28669 | 21.63563 | 0.34926 | 8.30289 |
November | 489.00000 | 24.03964 | 17.15034 | 0.22688 | 7.12942 |
December | 497.00000 | 23.58204 | 14.01243 | 0.07031 | 6.69775 |
Annual Sum or Average | 5943.00000 | 24.00154 | 21.98880 | -0.0202 | 8.62129 |
Minimum of Months | 454.00000 | 21.87473 | 13.33521 | -0.4438 | 6.69775 |
Maximum of Months | 514.00000 | 24.78363 | 34.29649 | 0.42838 | 11.65284 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92388 | 14.00202 | -0.9704 | 27.02081 |
February | 454.00000 | 20.42804 | 17.23021 | -0.7768 | 19.51712 |
March | 514.00000 | 21.06979 | 18.95852 | -0.5597 | 13.68575 |
April | 485.00000 | 22.19172 | 22.78123 | -0.2360 | 8.14354 |
May | 508.00000 | 23.08521 | 25.40821 | -0.9889 | 28.77510 |
June | 496.00000 | 23.98321 | 32.34282 | -0.5679 | 12.95568 |
July | 497.00000 | 24.30776 | 35.52131 | -0.4130 | 9.64876 |
August | 514.00000 | 24.05867 | 31.73426 | -0.5547 | 12.66275 |
September | 485.00000 | 23.34730 | 33.17523 | -0.8414 | 23.71489 |
October | 502.00000 | 22.10235 | 26.05827 | -0.2425 | 7.88306 |
November | 489.00000 | 20.85480 | 20.73752 | -0.6092 | 15.21315 |
December | 497.00000 | 20.04994 | 16.77668 | -0.8835 | 23.85715 |
Annual Sum or Average | 5943.00000 | 22.13035 | 24.60204 | -0.6366 | 16.91274 |
Minimum of Months | 454.00000 | 19.92388 | 14.00202 | -0.9889 | 7.88306 |
Maximum of Months | 514.00000 | 24.30776 | 35.52131 | -0.2360 | 28.77510 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.01335 | 13.35185 | -0.9336 | 25.64183 |
February | 385.00000 | 20.95463 | 16.20146 | -0.6316 | 16.89349 |
March | 433.00000 | 21.71562 | 17.48409 | -0.3878 | 11.87944 |
April | 410.00000 | 22.86628 | 20.91837 | -0.0383 | 8.39089 |
May | 430.00000 | 23.41830 | 23.99451 | -0.8074 | 23.39301 |
June | 418.00000 | 24.29636 | 31.09705 | -0.3486 | 11.16587 |
July | 422.00000 | 24.60394 | 34.36492 | -0.1749 | 9.04952 |
August | 433.00000 | 24.33649 | 30.37720 | -0.3435 | 10.37873 |
September | 410.00000 | 23.86911 | 31.54772 | -0.5978 | 18.07000 |
October | 427.00000 | 22.75242 | 24.22708 | -0.0691 | 7.51608 |
November | 417.00000 | 21.35921 | 19.46188 | -0.4838 | 13.06747 |
December | 422.00000 | 20.10494 | 16.01727 | -0.8585 | 23.17673 |
Annual Sum or Average | 5034.00000 | 22.53283 | 23.28405 | -0.4727 | 14.88361 |
Minimum of Months | 385.00000 | 20.01335 | 13.35185 | -0.9336 | 7.51608 |
Maximum of Months | 433.00000 | 24.60394 | 34.36492 | -0.0383 | 25.64183 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.21839 | 12.94668 | -0.5818 | 18.21341 |
February | 454.00000 | 22.17618 | 15.15645 | -0.2624 | 13.29925 |
March | 514.00000 | 22.36747 | 16.99763 | -0.1748 | 10.77909 |
April | 485.00000 | 22.97208 | 21.09546 | 0.00939 | 8.65231 |
May | 508.00000 | 23.36421 | 24.35612 | -0.8253 | 24.32519 |
June | 496.00000 | 24.05389 | 31.86675 | -0.4830 | 12.78409 |
July | 497.00000 | 24.43634 | 35.00469 | -0.2820 | 9.46136 |
August | 514.00000 | 24.31552 | 30.72346 | -0.3321 | 10.65887 |
September | 485.00000 | 23.98723 | 31.33130 | -0.4698 | 16.07565 |
October | 502.00000 | 23.37003 | 23.26612 | 0.15747 | 9.25194 |
November | 489.00000 | 22.53391 | 18.34297 | -0.1364 | 10.93111 |
December | 497.00000 | 21.39294 | 15.27521 | -0.4905 | 16.13291 |
Annual Sum or Average | 5943.00000 | 23.02165 | 23.07809 | -0.3240 | 13.39415 |
Minimum of Months | 454.00000 | 21.21839 | 12.94668 | -0.8253 | 8.65231 |
Maximum of Months | 514.00000 | 24.43634 | 35.00469 | 0.15747 | 24.32519 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31894 | 13.75388 | -0.8445 | 22.58053 |
February | 454.00000 | 21.16611 | 16.40213 | -0.5594 | 15.38985 |
March | 514.00000 | 21.85276 | 17.84771 | -0.3403 | 10.99579 |
April | 485.00000 | 22.99289 | 21.31550 | 0.00133 | 7.93765 |
May | 508.00000 | 23.55973 | 24.25571 | -0.7342 | 21.57560 |
June | 496.00000 | 24.18290 | 31.67903 | -0.3894 | 10.90231 |
July | 497.00000 | 24.51503 | 34.90350 | -0.2143 | 8.91174 |
August | 514.00000 | 24.29793 | 30.89574 | -0.3471 | 10.01194 |
September | 485.00000 | 23.82248 | 31.93082 | -0.5961 | 17.81430 |
October | 502.00000 | 22.87714 | 24.44616 | -0.0266 | 7.55519 |
November | 489.00000 | 21.65906 | 19.57538 | -0.3932 | 11.76824 |
December | 497.00000 | 20.50145 | 16.37569 | -0.7411 | 19.73346 |
Annual Sum or Average | 5943.00000 | 22.65662 | 23.65715 | -0.4318 | 13.75771 |
Minimum of Months | 454.00000 | 20.31894 | 13.75388 | -0.8445 | 7.55519 |
Maximum of Months | 514.00000 | 24.51503 | 34.90350 | 0.00133 | 22.58053 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65047 | 13.86865 | -1.0941 | 32.48782 |
February | 454.00000 | 20.04121 | 17.24030 | -0.9204 | 25.19535 |
March | 514.00000 | 20.50032 | 19.18795 | -0.7412 | 19.24173 |
April | 485.00000 | 21.45487 | 23.33336 | -0.4362 | 12.37086 |
May | 508.00000 | 22.62022 | 25.90263 | -1.1615 | 35.95182 |
June | 496.00000 | 23.76813 | 32.65079 | -0.6371 | 15.94770 |
July | 497.00000 | 24.20706 | 35.65222 | -0.4379 | 10.85888 |
August | 514.00000 | 23.87473 | 32.06683 | -0.6128 | 15.08123 |
September | 485.00000 | 22.89087 | 33.87489 | -1.0065 | 31.25522 |
October | 502.00000 | 21.24208 | 26.80595 | -0.4763 | 12.48953 |
November | 489.00000 | 20.19468 | 21.21185 | -0.8215 | 22.09230 |
December | 497.00000 | 19.81320 | 16.62712 | -1.0095 | 28.94964 |
Annual Sum or Average | 5943.00000 | 21.70227 | 24.91090 | -0.7789 | 21.80372 |
Minimum of Months | 454.00000 | 19.65047 | 13.86865 | -1.1615 | 10.85888 |
Maximum of Months | 514.00000 | 24.20706 | 35.65222 | -0.4362 | 35.95182 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87022 | 13.89291 | -1.0136 | 29.06872 |
February | 454.00000 | 20.55948 | 16.87119 | -0.7608 | 20.73339 |
March | 514.00000 | 21.27275 | 18.37188 | -0.5249 | 15.45132 |
April | 485.00000 | 22.35079 | 21.72547 | -0.1780 | 10.73758 |
May | 508.00000 | 23.14851 | 24.54601 | -0.9021 | 26.71503 |
June | 496.00000 | 24.13995 | 31.44327 | -0.3799 | 12.21253 |
July | 497.00000 | 24.46559 | 34.75647 | -0.1851 | 9.19330 |
August | 514.00000 | 24.18405 | 30.93154 | -0.3625 | 11.19011 |
September | 485.00000 | 23.56049 | 32.30883 | -0.7012 | 21.90938 |
October | 502.00000 | 22.15746 | 25.32265 | -0.2342 | 9.98321 |
November | 489.00000 | 20.65274 | 20.81541 | -0.6906 | 18.53537 |
December | 497.00000 | 19.92930 | 16.63267 | -0.9566 | 27.01129 |
Annual Sum or Average | 5943.00000 | 22.20427 | 24.00786 | -0.5731 | 17.70665 |
Minimum of Months | 454.00000 | 19.87022 | 13.89291 | -1.0136 | 9.19330 |
Maximum of Months | 514.00000 | 24.46559 | 34.75647 | -0.1780 | 29.06872 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72234 | 13.17373 | -0.7497 | 22.79036 |
February | 454.00000 | 21.63042 | 15.53777 | -0.4361 | 16.51163 |
March | 514.00000 | 21.76086 | 17.46509 | -0.3614 | 14.40874 |
April | 485.00000 | 22.37914 | 21.63509 | -0.1616 | 11.40903 |
May | 508.00000 | 22.99855 | 24.82288 | -0.9700 | 30.10088 |
June | 496.00000 | 23.86833 | 32.12123 | -0.5445 | 15.60087 |
July | 497.00000 | 24.34574 | 35.13044 | -0.3045 | 10.81292 |
August | 514.00000 | 24.16509 | 31.02228 | -0.3811 | 12.55656 |
September | 485.00000 | 23.64401 | 31.92717 | -0.6032 | 21.34052 |
October | 502.00000 | 22.71627 | 23.93366 | -0.0326 | 10.88339 |
November | 489.00000 | 21.76731 | 19.11478 | -0.3663 | 14.26646 |
December | 497.00000 | 20.79220 | 15.68529 | -0.6854 | 21.02690 |
Annual Sum or Average | 5943.00000 | 22.57333 | 23.51118 | -0.4673 | 16.82217 |
Minimum of Months | 454.00000 | 20.72234 | 13.17373 | -0.9700 | 10.81292 |
Maximum of Months | 514.00000 | 24.34574 | 35.13044 | -0.0326 | 30.10088 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.99994 | 13.77919 | -0.9727 | 27.87031 |
February | 454.00000 | 20.73791 | 16.58661 | -0.6992 | 19.65459 |
March | 514.00000 | 21.29163 | 18.22972 | -0.5072 | 14.98356 |
April | 485.00000 | 22.37240 | 21.88354 | -0.1669 | 10.36300 |
May | 508.00000 | 23.18725 | 24.70732 | -0.8749 | 27.30373 |
June | 496.00000 | 24.01311 | 31.91717 | -0.4453 | 13.31141 |
July | 497.00000 | 24.43541 | 35.01541 | -0.2339 | 9.99043 |
August | 514.00000 | 24.17066 | 31.16991 | -0.3890 | 11.69011 |
September | 485.00000 | 23.45460 | 32.54834 | -0.7313 | 23.68331 |
October | 502.00000 | 22.16256 | 25.13693 | -0.2203 | 10.07778 |
November | 489.00000 | 20.97119 | 20.25102 | -0.5951 | 16.66678 |
December | 497.00000 | 20.15075 | 16.46617 | -0.8756 | 24.50519 |
Annual Sum or Average | 5943.00000 | 22.25781 | 24.01622 | -0.5587 | 17.49335 |
Minimum of Months | 454.00000 | 19.99994 | 13.77919 | -0.9727 | 9.99043 |
Maximum of Months | 514.00000 | 24.43541 | 35.01541 | -0.1669 | 27.87031 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.142907E+09 | 5858.47 | 02-JAN-14:10 | 20.10 | 0.722818E+09 | 0.00 | 0.865725E+09 | 0.14 | 5.16 | 13-JAN-06:30 | 0.00 | 0.00 |
February | 0.353417E+10 | 66339.56 | 27-FEB-15:30 | 73.87 | 0.229162E+11 | 0.00 | 0.264503E+11 | 0.60 | 7.87 | 27-FEB-15:30 | 0.00 | 0.00 |
March | 0.600139E+10 | 49434.81 | 28-MAR-16:00 | 126.92 | 0.358859E+11 | 0.00 | 0.418873E+11 | 0.91 | 7.41 | 28-MAR-16:00 | 0.00 | 0.00 |
April | 0.144115E+11 | 110749.29 | 07-APR-14:00 | 180.04 | 0.954212E+11 | 0.00 | 0.109833E+12 | 1.42 | 7.96 | 07-APR-13:05 | 0.00 | 0.00 |
May | 0.271365E+11 | 128236.02 | 31-MAY-15:10 | 235.15 | 0.186093E+12 | 0.00 | 0.213230E+12 | 1.89 | 7.96 | 19-MAY-15:30 | 0.00 | 0.00 |
June | 0.676222E+11 | 139725.29 | 20-JUN-18:20 | 377.88 | 0.495202E+12 | 0.00 | 0.562824E+12 | 3.45 | 7.96 | 30-JUN-16:10 | 0.00 | 0.00 |
July | 0.101838E+12 | 143649.55 | 15-JUL-16:00 | 520.40 | 0.761591E+12 | 0.00 | 0.863429E+12 | 4.75 | 7.99 | 26-JUL-04:13 | 0.00 | 0.00 |
August | 0.884564E+11 | 132932.32 | 08-AUG-18:50 | 497.01 | 0.664420E+12 | 0.00 | 0.752876E+12 | 4.44 | 7.99 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.495947E+11 | 155665.94 | 07-SEP-15:03 | 318.06 | 0.358667E+12 | 0.00 | 0.408261E+12 | 2.85 | 7.96 | 27-SEP-16:30 | 0.00 | 0.00 |
October | 0.229650E+11 | 128397.76 | 18-OCT-14:00 | 224.38 | 0.155433E+12 | 0.00 | 0.178398E+12 | 1.77 | 7.96 | 12-OCT-15:00 | 0.00 | 0.00 |
November | 0.594343E+10 | 63766.67 | 03-NOV-14:10 | 133.08 | 0.346540E+11 | 0.00 | 0.405975E+11 | 0.97 | 7.83 | 03-NOV-14:10 | 0.00 | 0.00 |
December | 0.103111E+10 | 9072.67 | 07-DEC-15:30 | 83.17 | 0.520248E+10 | 0.00 | 0.623359E+10 | 0.56 | 5.17 | 11-DEC-07:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388678E+12 | 2790.05 | 0.281621E+13 | 0.00 | 0.320489E+13 | 1.99 | 0.00 | 0.00 | ||||
Minimum of Months | 0.142907E+09 | 5858.47 | 20.10 | 0.722818E+09 | 0.00 | 0.865725E+09 | 0.14 | 5.16 | 0.00 | 0.00 | ||
Maximum of Months | 0.101838E+12 | 155665.94 | 520.40 | 0.761591E+12 | 0.00 | 0.863429E+12 | 4.75 | 7.99 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.175756E+10 | 83656.47 | 19-MAY-12:20 | 6.75 | 0.137703E+11 | 0.00 | 0.155279E+11 | 0.07 | 7.96 | 19-MAY-15:30 | 0.00 | 0.00 |
June | 0.175644E+11 | 133254.80 | 21-JUN-12:23 | 62.42 | 0.136682E+12 | 0.00 | 0.154246E+12 | 0.67 | 7.96 | 30-JUN-16:10 | 0.00 | 0.00 |
July | 0.371700E+11 | 123334.33 | 14-JUL-09:45 | 128.78 | 0.290145E+12 | 0.00 | 0.327315E+12 | 1.35 | 7.96 | 20-JUL-15:00 | 0.00 | 0.00 |
August | 0.323406E+11 | 127776.50 | 08-AUG-18:10 | 113.94 | 0.254337E+12 | 0.00 | 0.286678E+12 | 1.20 | 7.96 | 10-AUG-11:30 | 0.00 | 0.00 |
September | 0.944658E+10 | 155665.94 | 07-SEP-15:03 | 33.08 | 0.722504E+11 | 0.00 | 0.816970E+11 | 0.35 | 7.96 | 01-SEP-13:50 | 0.00 | 0.00 |
October | 0.490166E+09 | 92542.74 | 18-OCT-14:05 | 2.00 | 0.386255E+10 | 0.00 | 0.435272E+10 | 0.02 | 7.94 | 18-OCT-14:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.987693E+11 | 346.97 | 0.771048E+12 | 0.00 | 0.869817E+12 | 0.31 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.371700E+11 | 155665.94 | 128.78 | 0.290145E+12 | 0.00 | 0.327315E+12 | 1.35 | 7.96 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.654342E+09 | 744.00 | 1302.45 | 13-JAN-16:10 | 33727.24 | 13-JAN-16:30 | 18.56 | 18.33 | 15.19 |
February | 0.340249E+10 | 672.00 | 43776.24 | 27-FEB-13:25 | 85116.28 | 27-FEB-16:00 | 19.21 | 18.33 | 15.19 |
March | 0.511033E+10 | 744.00 | 8405.05 | 14-MAR-14:00 | 107339.26 | 31-MAR-23:30 | 19.84 | 18.33 | 15.19 |
April | 0.222972E+11 | 720.00 | 43776.24 | 01-APR-13:10 | 538313.98 | 07-APR-14:05 | 21.37 | 18.65 | 15.19 |
May | 0.249720E+11 | 744.00 | 43776.24 | 02-MAY-11:40 | 231091.35 | 20-MAY-17:03 | 19.67 | 18.95 | 15.19 |
June | 0.570653E+11 | 720.00 | 43776.24 | 01-JUN-14:50 | 484154.15 | 20-JUN-19:00 | 23.66 | 21.20 | 15.19 |
July | 0.892142E+11 | 744.00 | 43776.24 | 01-JUL-00:05 | 636811.55 | 19-JUL-10:50 | 30.96 | 25.10 | 15.19 |
August | 0.940396E+11 | 744.00 | 43776.24 | 01-AUG-00:10 | 724225.40 | 05-AUG-19:01 | 32.04 | 24.60 | 15.19 |
September | 0.430853E+11 | 720.00 | 43776.24 | 01-SEP-00:05 | 313858.51 | 07-SEP-16:00 | 21.22 | 20.19 | 15.19 |
October | 0.168431E+11 | 744.00 | 43776.24 | 12-OCT-10:40 | 303422.86 | 18-OCT-15:00 | 19.81 | 18.59 | 15.19 |
November | 0.764943E+10 | 720.00 | 43776.24 | 04-NOV-13:20 | 173907.37 | 17-NOV-17:00 | 19.85 | 18.33 | 15.19 |
December | 0.527800E+10 | 744.00 | 19627.95 | 10-DEC-02:00 | 184101.81 | 10-DEC-02:00 | 20.19 | 18.33 | 15.19 |
Annual Sum or Average | 0.369611E+12 | 8760.00 | 22.23 | 19.93 | 15.19 | ||||
Minimum of Months | 0.654342E+09 | 672.00 | 1302.45 | 33727.24 | 18.56 | 18.33 | 15.19 | ||
Maximum of Months | 0.940396E+11 | 744.00 | 43776.24 | 724225.40 | 32.04 | 25.10 | 15.19 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 198696.95 | 13-JAN-06:03 | 20.92 | 20.92 | 0.10 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 596108.09 | 27-FEB-15:30 | 21.00 | 20.94 | 2.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 426346.88 | 28-MAR-16:00 | 21.01 | 20.93 | 3.86 |
April | 40017562.13 | 55.80 | 1392.32 | 06-APR-16:00 | 974912.66 | 07-APR-14:00 | 21.30 | 21.09 | 7.58 |
May | 0.253805E+09 | 136.14 | 14109.69 | 19-MAY-14:20 | 1089159.44 | 31-MAY-15:10 | 21.54 | 21.14 | 12.62 |
June | 0.229911E+10 | 290.93 | 14109.69 | 06-JUN-13:55 | 1132446.62 | 22-JUN-10:00 | 22.27 | 21.17 | 23.87 |
July | 0.439580E+10 | 413.83 | 14109.69 | 01-JUL-12:30 | 1136873.41 | 12-JUL-18:40 | 22.82 | 21.17 | 31.55 |
August | 0.204100E+10 | 355.95 | 14109.69 | 01-AUG-12:20 | 1140754.79 | 12-AUG-09:50 | 22.54 | 21.09 | 28.27 |
September | 0.164000E+10 | 229.26 | 14109.69 | 02-SEP-11:10 | 1176310.24 | 07-SEP-15:03 | 22.02 | 21.22 | 18.95 |
October | 0.102443E+09 | 112.50 | 1910.74 | 18-OCT-14:00 | 1116995.49 | 18-OCT-14:00 | 21.33 | 21.00 | 10.82 |
November | 5567806.42 | 24.17 | 218.73 | 03-NOV-14:10 | 571663.34 | 03-NOV-14:10 | 21.04 | 20.96 | 3.99 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 199409.16 | 12-DEC-12:10 | 20.92 | 20.91 | 0.85 |
Annual Sum or Average | 0.107777E+11 | 1618.56 | 21.56 | 21.04 | 12.11 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 198696.95 | 20.92 | 20.91 | 0.10 | ||
Maximum of Months | 0.439580E+10 | 413.83 | 14109.69 | 1176310.24 | 22.82 | 21.22 | 31.55 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.92 | 20.92 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.00 | 21.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.01 | 21.01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.30 | 21.30 | 0.00 |
May | 57710188.04 | 5.00 | 14109.69 | 19-MAY-14:20 | 1042519.99 | 19-MAY-15:40 | 21.54 | 21.51 | 0.34 |
June | 0.903134E+09 | 52.17 | 14109.69 | 20-JUN-11:25 | 1046609.27 | 30-JUN-15:10 | 22.27 | 21.98 | 3.67 |
July | 0.223148E+10 | 114.68 | 14109.69 | 13-JUL-12:40 | 1098375.26 | 13-JUL-18:42 | 22.82 | 22.18 | 7.78 |
August | 0.103373E+10 | 98.88 | 14109.69 | 05-AUG-12:40 | 1045613.05 | 15-AUG-14:50 | 22.54 | 21.99 | 6.75 |
September | 0.746654E+09 | 29.75 | 14109.69 | 02-SEP-12:55 | 1176310.24 | 07-SEP-15:03 | 22.02 | 21.84 | 2.08 |
October | 11609465.34 | 2.00 | 1612.43 | 18-OCT-14:05 | 898597.58 | 18-OCT-15:20 | 21.33 | 21.32 | 0.14 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.04 | 21.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.92 | 20.92 | 0.00 |
Annual Sum or Average | 0.498432E+10 | 302.48 | 21.56 | 21.42 | 1.75 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 20.92 | 0.00 | ||
Maximum of Months | 0.223148E+10 | 114.68 | 14109.69 | 1176310.24 | 22.82 | 22.18 | 7.78 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.930118E+12 | 0.00 | 607.00 | 2060137.74 | 09-JAN-07:02 | 0.00 | 38.09 | 72.93 | 2.24 | 0.00 | 0.12 | 0.70 | 09-JAN-07:02 |
February | 0.489283E+12 | 0.00 | 450.53 | 1717391.72 | 07-FEB-06:01 | 0.00 | 33.28 | 64.70 | 1.16 | 0.00 | 0.07 | 0.59 | 07-FEB-06:01 |
March | 0.306888E+12 | 0.00 | 431.00 | 1635490.26 | 06-MAR-06:01 | 0.00 | 29.83 | 59.12 | 0.59 | 0.00 | 0.04 | 0.56 | 06-MAR-06:01 |
April | 0.994441E+11 | 0.00 | 253.13 | 1289943.93 | 01-APR-04:11 | 0.00 | 26.03 | 45.22 | 0.17 | 0.00 | 0.01 | 0.44 | 01-APR-04:11 |
May | 0.666262E+11 | 0.00 | 185.21 | 1373556.12 | 22-MAY-04:01 | 0.00 | 25.35 | 38.92 | 0.12 | 0.00 | 0.01 | 0.47 | 22-MAY-04:01 |
June | 0.415259E+10 | 0.00 | 38.69 | 173815.93 | 16-JUN-07:00 | 0.00 | 23.73 | 26.86 | 0.01 | 0.00 | 0.00 | 0.06 | 16-JUN-07:00 |
July | 19316334.37 | 0.00 | 2.79 | 5914.80 | 08-JUL-06:10 | 0.00 | 24.10 | 24.32 | 0.00 | 0.00 | 0.00 | 0.00 | 08-JUL-06:10 |
August | 0.955558E+09 | 0.00 | 22.47 | 298961.19 | 17-AUG-14:00 | 0.00 | 23.85 | 25.60 | 0.00 | 0.00 | 0.00 | 0.10 | 17-AUG-14:00 |
September | 0.215428E+11 | 0.00 | 103.21 | 879185.54 | 19-SEP-05:02 | 0.00 | 23.96 | 32.08 | 0.04 | 0.00 | 0.00 | 0.30 | 19-SEP-05:02 |
October | 0.736940E+11 | 0.00 | 230.67 | 1196868.69 | 10-OCT-04:01 | 0.00 | 25.63 | 42.70 | 0.13 | 0.00 | 0.01 | 0.41 | 10-OCT-04:01 |
November | 0.245806E+12 | 0.00 | 405.28 | 1593802.57 | 27-NOV-06:02 | 0.00 | 29.51 | 58.16 | 0.48 | 0.00 | 0.03 | 0.54 | 27-NOV-06:02 |
December | 0.600982E+12 | 0.00 | 564.26 | 1738826.95 | 27-DEC-06:01 | 0.00 | 34.91 | 69.94 | 1.30 | 0.00 | 0.08 | 0.59 | 27-DEC-06:01 |
Annual Sum or Average | 0.283951E+13 | 0.00 | 3294.24 | 0.00 | 28.17 | 46.63 | 0.52 | 0.00 | 0.03 | ||||
Minimum of Months | 19316334.37 | 0.00 | 2.79 | 5914.80 | 0.00 | 23.73 | 24.32 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.930118E+12 | 0.00 | 607.00 | 2060137.74 | 0.00 | 38.09 | 72.93 | 2.24 | 0.00 | 0.12 | 0.70 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.56 | 18.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.21 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.84 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.37 | 21.37 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.67 | 19.67 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 23.66 | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 30.96 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 32.04 | 32.04 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 21.22 | 21.22 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.81 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.85 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.19 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 | 22.23 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 18.56 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 | 32.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.648927E+09 | 0.00 | 12.67 | 0.648927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30412.55 | 02-JAN-14:10 | 30412.55 | 02-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.359370E+10 | 0.00 | 61.24 | 0.359370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53407.50 | 28-FEB-16:00 | 53407.50 | 28-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.562545E+10 | 0.00 | 79.98 | 0.562545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49925.77 | 01-MAR-16:10 | 49925.77 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.808496E+10 | 0.00 | 130.38 | 0.808496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78461.25 | 06-APR-16:00 | 78461.25 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.175451E+11 | 0.00 | 190.44 | 0.175451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105590.39 | 19-MAY-15:20 | 105590.39 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.565943E+11 | 0.00 | 355.81 | 0.562972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141948.95 | 20-JUN-13:13 | 132552.74 | 20-JUN-13:13 | 0.00 | 0.00 | 0.00 |
July | 0.965038E+11 | 0.00 | 495.36 | 0.960691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148523.84 | 25-JUL-16:45 | 148523.84 | 25-JUL-16:45 | 0.00 | 0.00 | 0.00 |
August | 0.881294E+11 | 0.00 | 474.45 | 0.881281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146808.68 | 10-AUG-12:35 | 146808.68 | 10-AUG-12:35 | 0.00 | 0.00 | 0.00 |
September | 0.378222E+11 | 0.00 | 286.41 | 0.363333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179132.93 | 07-SEP-14:45 | 114874.57 | 01-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.147715E+11 | 0.00 | 170.96 | 0.147715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99290.94 | 18-OCT-14:00 | 99290.94 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.897770E+10 | 0.00 | 115.15 | 0.897770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61873.25 | 03-NOV-15:00 | 61873.25 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.437107E+10 | 0.00 | 78.50 | 0.437107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40627.39 | 06-DEC-13:20 | 40627.39 | 06-DEC-13:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342668E+12 | 0.00 | 2451.36 | 0.340446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.648927E+09 | 0.00 | 12.67 | 0.648927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30412.55 | 30412.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.965038E+11 | 0.00 | 495.36 | 0.960691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179132.93 | 148523.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 18472.87 | 0.00 | 9.67 | 18472.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 02-JAN-06:01 | 2.10 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.176101E+11 | 0.00 | 37.45 | 0.176101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 440069.75 | 27-FEB-15:30 | 440069.75 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.278900E+11 | 0.00 | 62.80 | 0.278900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 344213.15 | 28-MAR-16:00 | 344213.15 | 28-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.790463E+11 | 0.00 | 121.87 | 0.790463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 639046.49 | 06-APR-14:05 | 639046.49 | 06-APR-14:05 | 0.00 | 0.00 | 0.00 |
May | 0.156529E+12 | 0.00 | 201.22 | 0.156529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1027942.23 | 19-MAY-15:20 | 1027942.23 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.482315E+12 | 0.00 | 338.09 | 0.479653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1304775.10 | 21-JUN-12:45 | 1213262.17 | 20-JUN-13:13 | 0.00 | 0.00 | 0.00 |
July | 0.806670E+12 | 0.00 | 422.11 | 0.803530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1354228.88 | 25-JUL-12:13 | 1354228.88 | 25-JUL-12:13 | 0.00 | 0.00 | 0.00 |
August | 0.698662E+12 | 0.00 | 392.36 | 0.698662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1346986.21 | 10-AUG-12:10 | 1346986.21 | 10-AUG-12:10 | 0.00 | 0.00 | 0.00 |
September | 0.337933E+12 | 0.00 | 267.84 | 0.324395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1656852.90 | 07-SEP-14:45 | 1142557.55 | 04-SEP-16:51 | 0.00 | 0.00 | 0.00 |
October | 0.130250E+12 | 0.00 | 178.11 | 0.130250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 836728.65 | 18-OCT-15:20 | 836728.65 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.238565E+11 | 0.00 | 71.12 | 0.238565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 432686.42 | 03-NOV-14:05 | 432686.42 | 03-NOV-14:05 | 0.00 | 0.00 | 0.00 |
December | 5706452.74 | 0.00 | 6.33 | 5706452.74 | 0.00 | 0.00 | 0.00 | 0.00 | 8261.28 | 07-DEC-15:30 | 8261.28 | 07-DEC-15:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276077E+13 | 0.00 | 2108.96 | 0.274143E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 18472.87 | 0.00 | 6.33 | 18472.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 2.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.806670E+12 | 0.00 | 422.11 | 0.803530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1656852.90 | 1354228.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7235.46 | 0.00 | 0.12 | 7235.46 | 0.00 | 0.00 | 0.00 | 0.00 | 59.71 | 02-JAN-04:56 | 59.71 | 02-JAN-04:56 | 0.00 | 0.00 | 0.00 |
February | 0.750984E+09 | 0.00 | 21.13 | 0.750984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23061.66 | 27-FEB-13:35 | 23061.66 | 27-FEB-13:35 | 0.00 | 0.00 | 0.00 |
March | 0.115081E+10 | 0.00 | 32.08 | 0.115081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29177.17 | 28-MAR-15:50 | 29177.17 | 28-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.451285E+10 | 0.00 | 72.63 | 0.451285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62593.36 | 06-APR-16:00 | 62593.36 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.150073E+11 | 0.00 | 161.44 | 0.150073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129792.49 | 19-MAY-15:10 | 129792.49 | 19-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.523869E+11 | 0.00 | 325.49 | 0.520945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155701.87 | 21-JUN-12:32 | 145396.07 | 21-JUN-12:32 | 0.00 | 0.00 | 0.00 |
July | 0.888580E+11 | 0.00 | 421.75 | 0.885673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167488.54 | 25-JUL-16:32 | 167488.54 | 25-JUL-16:32 | 0.00 | 0.00 | 0.00 |
August | 0.748657E+11 | 0.00 | 382.19 | 0.748657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155427.61 | 10-AUG-12:23 | 155427.61 | 10-AUG-12:23 | 0.00 | 0.00 | 0.00 |
September | 0.325942E+11 | 0.00 | 242.72 | 0.312685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187303.56 | 07-SEP-15:03 | 139164.51 | 03-SEP-12:51 | 0.00 | 0.00 | 0.00 |
October | 0.665796E+10 | 0.00 | 103.29 | 0.665796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84982.85 | 18-OCT-15:10 | 84982.85 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.422306E+09 | 0.00 | 29.92 | 0.422306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10528.46 | 09-NOV-14:50 | 10528.46 | 09-NOV-14:50 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277207E+12 | 0.00 | 1792.75 | 0.275298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.888580E+11 | 0.00 | 421.75 | 0.885673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187303.56 | 167488.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 334457.24 | 0.00 | 0.18 | 334457.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3666.49 | 24-JAN-05:11 | 3666.49 | 24-JAN-05:11 | 0.00 | 0.00 | 0.00 |
February | 0.262399E+09 | 0.00 | 5.50 | 0.262399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22155.19 | 27-FEB-15:00 | 22155.19 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 55797.28 | 0.00 | 0.56 | 55797.28 | 0.00 | 0.00 | 0.00 | 0.00 | 61.20 | 07-MAR-12:10 | 61.20 | 07-MAR-12:10 | 0.00 | 0.00 | 0.00 |
April | 0.204208E+10 | 0.00 | 38.90 | 0.204208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41674.39 | 07-APR-14:00 | 41674.39 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.773335E+10 | 0.00 | 104.45 | 0.773335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61626.12 | 29-MAY-18:37 | 61626.12 | 29-MAY-18:37 | 0.00 | 0.00 | 0.00 |
June | 0.277385E+11 | 0.00 | 233.56 | 0.277015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69873.85 | 20-JUN-13:13 | 64631.60 | 20-JUN-13:13 | 0.00 | 0.00 | 0.00 |
July | 0.474299E+11 | 0.00 | 329.52 | 0.473710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80161.41 | 16-JUL-18:51 | 80161.41 | 16-JUL-18:51 | 0.00 | 0.00 | 0.00 |
August | 0.438544E+11 | 0.00 | 322.75 | 0.438544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76329.09 | 07-AUG-18:00 | 76329.09 | 07-AUG-18:00 | 0.00 | 0.00 | 0.00 |
September | 0.181207E+11 | 0.00 | 185.74 | 0.176542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87803.53 | 07-SEP-14:50 | 79488.22 | 04-SEP-09:31 | 0.00 | 0.00 | 0.00 |
October | 0.518394E+10 | 0.00 | 63.39 | 0.518394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50959.88 | 18-OCT-14:00 | 50959.88 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 63463694.89 | 0.00 | 5.22 | 63463694.89 | 0.00 | 0.00 | 0.00 | 0.00 | 22384.12 | 17-NOV-06:03 | 22384.12 | 17-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 11486.92 | 0.00 | 0.17 | 11486.92 | 0.00 | 0.00 | 0.00 | 0.00 | 19.14 | 26-DEC-19:20 | 19.14 | 26-DEC-19:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152429E+12 | 0.00 | 1289.94 | 0.151867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11486.92 | 0.00 | 0.17 | 11486.92 | 0.00 | 0.00 | 0.00 | 0.00 | 19.14 | 19.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.474299E+11 | 0.00 | 329.52 | 0.473710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87803.53 | 80161.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.889853E+10 | 0.447660E+10 | 744.00 | 0.774860E+10 | 0.114993E+10 | 0.00 | 0.02 | 03-JAN-15:00 | 0.02 | 10-JAN-22:01 | 5163.07 | 03-JAN-15:00 | 4689.52 | 03-JAN-15:00 | 493.88 | 21-JAN-15:00 | 2134.05 | 03-JAN-15:00 | 0.00 |
February | 0.135512E+11 | 0.558241E+10 | 672.00 | 0.119748E+11 | 0.157644E+10 | 0.00 | 0.07 | 27-FEB-16:00 | 0.02 | 01-FEB-08:10 | 17662.38 | 27-FEB-16:00 | 17662.38 | 27-FEB-16:00 | 965.78 | 08-FEB-04:02 | 6160.71 | 27-FEB-16:00 | 0.00 |
March | 0.151137E+11 | 0.652954E+10 | 744.00 | 0.143703E+11 | 0.743421E+09 | 0.00 | 0.03 | 14-MAR-13:05 | 0.03 | 06-MAR-09:05 | 7051.77 | 14-MAR-13:05 | 7051.77 | 14-MAR-13:05 | 1155.96 | 21-MAR-15:10 | 2882.10 | 14-MAR-13:05 | 0.00 |
April | 0.757828E+11 | 0.237380E+11 | 720.00 | 0.726815E+11 | 0.310125E+10 | 0.00 | 0.92 | 07-APR-14:00 | 0.02 | 30-APR-23:30 | 314513.23 | 07-APR-14:00 | 314513.23 | 07-APR-14:00 | 24891.21 | 24-APR-11:00 | 101472.36 | 07-APR-14:00 | 0.00 |
May | 0.179629E+11 | 0.745753E+10 | 730.31 | 0.167730E+11 | 0.118994E+10 | 0.00 | 0.38 | 19-MAY-15:10 | 0.00 | 04-MAY-18:00 | 137228.90 | 19-MAY-13:50 | 131653.68 | 19-MAY-16:00 | 9339.06 | 19-MAY-12:20 | 45337.09 | 20-MAY-16:00 | 0.00 |
June | 0.136129E+12 | 0.430823E+11 | 645.75 | 0.122882E+12 | 0.132469E+11 | 0.00 | 0.76 | 20-JUN-18:50 | 0.00 | 17-JUN-24:00 | 323560.09 | 20-JUN-18:50 | 226663.42 | 23-JUN-15:50 | 112068.86 | 20-JUN-20:00 | 90791.96 | 20-JUN-18:50 | 0.00 |
July | 0.448109E+12 | 0.137562E+12 | 690.94 | 0.400325E+12 | 0.477836E+11 | 0.00 | 0.98 | 19-JUL-10:50 | 0.00 | 03-JUL-04:53 | 413514.14 | 19-JUL-10:50 | 319597.50 | 17-JUL-16:00 | 164981.95 | 01-JUL-00:55 | 129638.34 | 17-JUL-16:00 | 0.00 |
August | 0.571233E+12 | 0.170738E+12 | 744.00 | 0.519635E+12 | 0.515981E+11 | 0.00 | 1.00 | 03-AUG-15:40 | 0.01 | 31-AUG-23:55 | 413207.05 | 05-AUG-19:07 | 397498.27 | 08-AUG-14:50 | 142371.04 | 01-AUG-01:00 | 144518.75 | 05-AUG-16:00 | 0.00 |
September | 0.450197E+11 | 0.163054E+11 | 643.93 | 0.410304E+11 | 0.398937E+10 | 0.00 | 0.51 | 07-SEP-16:00 | 0.00 | 24-SEP-10:52 | 212544.73 | 07-SEP-16:00 | 136909.97 | 01-SEP-13:10 | 87732.87 | 07-SEP-15:50 | 58262.98 | 07-SEP-16:00 | 0.00 |
October | 0.246686E+11 | 0.914209E+10 | 743.50 | 0.230531E+11 | 0.161553E+10 | 0.00 | 0.52 | 18-OCT-14:00 | 0.01 | 01-OCT-01:10 | 176407.85 | 18-OCT-15:00 | 176407.85 | 18-OCT-15:00 | 1389.47 | 12-OCT-12:00 | 57085.94 | 18-OCT-14:30 | 0.00 |
November | 0.166347E+11 | 0.684722E+10 | 720.00 | 0.157252E+11 | 0.909546E+09 | 0.00 | 0.22 | 17-NOV-17:00 | 0.03 | 18-NOV-13:05 | 67900.68 | 17-NOV-17:00 | 64759.63 | 17-NOV-17:00 | 3141.05 | 17-NOV-17:00 | 18975.17 | 17-NOV-17:00 | 0.00 |
December | 0.167490E+11 | 0.733950E+10 | 744.00 | 0.164012E+11 | 0.347801E+09 | 0.00 | 0.24 | 10-DEC-02:00 | 0.03 | 10-DEC-09:25 | 68185.89 | 10-DEC-02:00 | 68185.89 | 10-DEC-02:00 | 9206.48 | 19-DEC-15:00 | 20404.83 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.138985E+13 | 0.438801E+12 | 8542.43 | 0.126260E+13 | 0.127252E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.889853E+10 | 0.447660E+10 | 643.93 | 0.774860E+10 | 0.347801E+09 | 0.00 | 0.02 | 0.00 | 5163.07 | 4689.52 | 493.88 | 2134.05 | 0.00 | ||||||
Maximum of Months | 0.571233E+12 | 0.170738E+12 | 744.00 | 0.519635E+12 | 0.515981E+11 | 0.00 | 1.00 | 0.03 | 413514.14 | 397498.27 | 164981.95 | 144518.75 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.274882E+10 | 0.695587E+09 | 718.76 | 0.274849E+10 | 323959.83 | 0.00 | 0.28 | 29-JAN-16:42 | 0.00 | 07-JAN-22:15 | 2251.34 | 01-JAN-16:05 | 2244.69 | 01-JAN-16:10 | 13.74 | 02-JAN-07:10 | 524.63 | 29-JAN-16:42 | 0.00 |
February | 0.812256E+10 | 0.187763E+10 | 672.00 | 0.812256E+10 | -0.0 | 0.00 | 0.62 | 26-FEB-17:13 | 0.26 | 01-FEB-07:02 | 5194.02 | 26-FEB-17:17 | 5194.02 | 26-FEB-17:17 | 0.00 | 07-FEB-04:03 | 1157.61 | 26-FEB-17:13 | 0.00 |
March | 0.148683E+11 | 0.323623E+10 | 744.00 | 0.148683E+11 | 0.00 | 0.00 | 0.83 | 31-MAR-24:00 | 0.53 | 06-MAR-07:03 | 7480.35 | 31-MAR-24:00 | 7480.35 | 31-MAR-24:00 | 0.00 | 25-MAR-06:30 | 1547.50 | 31-MAR-24:00 | 0.00 |
April | 0.199386E+11 | 0.414595E+10 | 720.00 | 0.199297E+11 | 8944970.50 | 0.00 | 1.00 | 16-APR-16:51 | 0.31 | 30-APR-24:00 | 9038.20 | 22-APR-18:15 | 9038.20 | 22-APR-18:15 | 132.08 | 24-APR-10:50 | 2225.89 | 07-APR-14:00 | 0.00 |
May | 0.551760E+10 | 0.131029E+10 | 744.00 | 0.549061E+10 | 26996852.58 | 0.00 | 0.48 | 31-MAY-24:00 | 0.14 | 08-MAY-06:10 | 4080.12 | 31-MAY-24:00 | 4080.12 | 31-MAY-24:00 | 146.74 | 30-MAY-09:30 | 894.80 | 31-MAY-24:00 | 0.00 |
June | 0.108206E+11 | 0.257369E+10 | 720.00 | 0.107265E+11 | 94098515.11 | 0.00 | 0.68 | 30-JUN-23:20 | 0.40 | 17-JUN-06:10 | 6007.78 | 30-JUN-23:55 | 5994.17 | 30-JUN-24:00 | 341.22 | 06-JUN-16:40 | 1600.32 | 28-JUN-19:00 | 0.00 |
July | 0.165424E+11 | 0.425710E+10 | 744.00 | 0.164397E+11 | 0.102680E+09 | 0.00 | 0.92 | 16-JUL-18:51 | 0.63 | 08-JUL-06:15 | 7928.54 | 31-JUL-24:00 | 7928.54 | 31-JUL-24:00 | 376.93 | 03-JUL-17:00 | 2689.17 | 17-JUL-16:00 | 0.00 |
August | 0.214075E+11 | 0.524942E+10 | 744.00 | 0.213296E+11 | 77955357.03 | 0.00 | 1.00 | 03-AUG-18:20 | 0.31 | 31-AUG-24:00 | 8869.36 | 05-AUG-20:23 | 8868.70 | 05-AUG-20:14 | 427.35 | 22-AUG-16:00 | 3103.13 | 05-AUG-16:00 | 0.00 |
September | 0.563123E+10 | 0.137952E+10 | 720.00 | 0.554151E+10 | 89719393.15 | 0.00 | 0.46 | 04-SEP-17:41 | 0.17 | 19-SEP-06:40 | 3917.57 | 30-SEP-24:00 | 3917.57 | 30-SEP-24:00 | 340.22 | 07-SEP-14:10 | 1245.47 | 04-SEP-17:31 | 0.00 |
October | 0.104489E+11 | 0.231023E+10 | 744.00 | 0.104360E+11 | 12923522.39 | 0.00 | 0.66 | 31-OCT-24:00 | 0.37 | 10-OCT-06:20 | 5595.92 | 31-OCT-24:00 | 5595.92 | 31-OCT-24:00 | 111.14 | 25-OCT-11:00 | 1344.66 | 15-OCT-16:52 | 0.00 |
November | 0.145606E+11 | 0.312945E+10 | 720.00 | 0.145579E+11 | 2699385.35 | 0.00 | 0.76 | 12-NOV-16:25 | 0.54 | 27-NOV-07:10 | 6762.83 | 12-NOV-16:30 | 6762.83 | 12-NOV-16:30 | 85.30 | 17-NOV-17:05 | 1413.50 | 12-NOV-16:25 | 0.00 |
December | 0.194532E+11 | 0.414097E+10 | 744.00 | 0.194529E+11 | 355565.13 | 0.00 | 0.93 | 10-DEC-16:05 | 0.74 | 29-DEC-07:03 | 8424.26 | 10-DEC-16:10 | 8424.26 | 10-DEC-16:10 | 55.95 | 19-DEC-17:05 | 1737.80 | 10-DEC-16:05 | 0.00 |
Annual Sum or Average | 0.150060E+12 | 0.343061E+11 | 8734.76 | 0.149644E+12 | 0.416698E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.274882E+10 | 0.695587E+09 | 672.00 | 0.274849E+10 | -0.0 | 0.00 | 0.28 | 0.00 | 2251.34 | 2244.69 | 0.00 | 524.63 | 0.00 | ||||||
Maximum of Months | 0.214075E+11 | 0.524942E+10 | 744.00 | 0.213296E+11 | 0.102680E+09 | 0.00 | 1.00 | 0.74 | 9038.20 | 9038.20 | 427.35 | 3103.13 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.493682E+10 | 0.141525E+10 | 372.18 | 0.493431E+10 | 2505124.66 | 0.00 | 0.23 | 19-JAN-16:50 | 0.00 | 01-JAN-00:05 | 16874.07 | 13-JAN-16:30 | 16874.07 | 13-JAN-16:30 | 255.65 | 01-JAN-15:55 | 4029.70 | 19-JAN-16:50 | 0.00 |
February | 0.563373E+11 | 0.133622E+11 | 672.00 | 0.563373E+11 | -0.0 | 0.00 | 0.57 | 26-FEB-17:22 | 0.13 | 06-FEB-04:03 | 45490.91 | 26-FEB-17:25 | 45490.91 | 26-FEB-17:30 | 0.00 | 07-FEB-16:20 | 10244.84 | 26-FEB-17:22 | 0.00 |
March | 0.123310E+12 | 0.272551E+11 | 744.00 | 0.123310E+12 | -0.0 | 0.00 | 0.76 | 31-MAR-23:30 | 0.37 | 06-MAR-07:03 | 64921.56 | 31-MAR-23:30 | 64921.56 | 31-MAR-23:30 | 0.00 | 18-MAR-05:50 | 13615.70 | 31-MAR-23:30 | 0.00 |
April | 0.179779E+12 | 0.377167E+11 | 720.00 | 0.179689E+12 | 90349774.65 | 0.00 | 1.00 | 16-APR-17:31 | 0.15 | 30-APR-24:00 | 84626.25 | 22-APR-18:17 | 84626.25 | 22-APR-18:17 | 1292.34 | 24-APR-10:50 | 21181.04 | 07-APR-14:00 | 0.00 |
May | 0.449368E+11 | 0.108134E+11 | 744.00 | 0.446752E+11 | 0.261657E+09 | 0.00 | 0.47 | 31-MAY-24:00 | 0.02 | 08-MAY-06:10 | 38649.78 | 31-MAY-24:00 | 38649.78 | 31-MAY-24:00 | 1410.92 | 30-MAY-09:30 | 8492.66 | 31-MAY-24:00 | 0.00 |
June | 0.999470E+11 | 0.239088E+11 | 720.00 | 0.990170E+11 | 0.930006E+09 | 0.00 | 0.68 | 30-JUN-23:20 | 0.35 | 17-JUN-06:10 | 58286.30 | 30-JUN-23:55 | 58151.76 | 30-JUN-24:00 | 3335.11 | 06-JUN-16:40 | 15475.74 | 28-JUN-19:00 | 0.00 |
July | 0.156148E+12 | 0.403123E+11 | 744.00 | 0.155128E+12 | 0.102034E+10 | 0.00 | 0.91 | 16-JUL-18:50 | 0.59 | 08-JUL-06:05 | 76553.13 | 31-JUL-24:00 | 76553.13 | 31-JUL-24:00 | 3675.40 | 03-JUL-17:00 | 25587.81 | 17-JUL-18:10 | 0.00 |
August | 0.202004E+12 | 0.497279E+11 | 744.00 | 0.201229E+12 | 0.775270E+09 | 0.00 | 1.00 | 03-AUG-18:20 | 0.27 | 31-AUG-24:00 | 84857.76 | 05-AUG-20:05 | 84857.76 | 05-AUG-20:05 | 4191.89 | 22-AUG-16:00 | 29831.71 | 05-AUG-16:00 | 0.00 |
September | 0.480174E+11 | 0.119253E+11 | 720.00 | 0.471439E+11 | 0.873506E+09 | 0.00 | 0.46 | 04-SEP-17:41 | 0.09 | 19-SEP-06:10 | 35333.61 | 30-SEP-23:30 | 35333.61 | 30-SEP-23:30 | 3399.58 | 07-SEP-15:10 | 11934.94 | 04-SEP-17:41 | 0.00 |
October | 0.877869E+11 | 0.196630E+11 | 744.00 | 0.876587E+11 | 0.128233E+09 | 0.00 | 0.60 | 15-OCT-17:03 | 0.24 | 10-OCT-06:10 | 48414.27 | 15-OCT-17:03 | 48414.27 | 15-OCT-17:03 | 1097.91 | 25-OCT-11:00 | 12225.69 | 15-OCT-16:41 | 0.00 |
November | 0.119199E+12 | 0.260549E+11 | 720.00 | 0.119171E+12 | 27422667.81 | 0.00 | 0.69 | 13-NOV-16:30 | 0.37 | 27-NOV-07:10 | 59839.07 | 03-NOV-16:00 | 59177.05 | 03-NOV-16:00 | 819.66 | 17-NOV-17:05 | 12327.74 | 13-NOV-16:30 | 0.00 |
December | 0.155165E+12 | 0.338053E+11 | 744.00 | 0.155161E+12 | 4262371.30 | 0.00 | 0.84 | 10-DEC-16:05 | 0.56 | 31-DEC-23:51 | 74352.69 | 06-DEC-16:10 | 74033.78 | 06-DEC-16:10 | 563.02 | 19-DEC-17:05 | 15067.10 | 10-DEC-16:05 | 0.00 |
Annual Sum or Average | 0.127757E+13 | 0.295960E+12 | 8388.18 | 0.127345E+13 | 0.411355E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.493682E+10 | 0.141525E+10 | 372.18 | 0.493431E+10 | -0.0 | 0.00 | 0.23 | 0.00 | 16874.07 | 16874.07 | 0.00 | 4029.70 | 0.00 | ||||||
Maximum of Months | 0.202004E+12 | 0.497279E+11 | 744.00 | 0.201229E+12 | 0.102034E+10 | 0.00 | 1.00 | 0.59 | 84857.76 | 84857.76 | 4191.89 | 29831.71 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.138862E+09 | 39950510.84 | 108.69 | 0.138803E+09 | 59517.00 | 0.00 | 0.21 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1647.68 | 13-JAN-16:30 | 1647.68 | 13-JAN-16:30 | 7.75 | 02-JAN-15:10 | 387.55 | 13-JAN-16:30 | 0.00 |
February | 0.407281E+10 | 0.985498E+09 | 650.54 | 0.407281E+10 | -0.0 | 0.00 | 0.52 | 26-FEB-17:22 | 0.00 | 03-FEB-03:55 | 4194.06 | 26-FEB-17:40 | 4194.06 | 26-FEB-17:40 | 0.00 | 08-FEB-22:20 | 954.38 | 26-FEB-17:22 | 0.00 |
March | 0.106160E+11 | 0.238014E+10 | 744.00 | 0.106160E+11 | 0.00 | 0.00 | 0.73 | 28-MAR-17:50 | 0.19 | 06-MAR-04:16 | 6273.10 | 28-MAR-17:50 | 6273.10 | 28-MAR-17:50 | 0.00 | 01-MAR-05:55 | 1333.45 | 28-MAR-17:50 | 0.00 |
April | 0.167685E+11 | 0.355596E+10 | 719.00 | 0.167596E+11 | 8904445.01 | 0.00 | 0.99 | 16-APR-17:52 | 0.00 | 30-APR-23:10 | 8410.95 | 22-APR-18:10 | 8410.95 | 22-APR-18:10 | 128.99 | 24-APR-10:50 | 2132.61 | 07-APR-14:00 | 0.00 |
May | 0.380983E+10 | 0.925234E+09 | 684.66 | 0.378399E+10 | 25838113.57 | 0.00 | 0.46 | 31-MAY-23:30 | 0.00 | 01-MAY-00:05 | 3785.26 | 31-MAY-23:30 | 3785.26 | 31-MAY-23:30 | 138.08 | 30-MAY-09:30 | 834.65 | 31-MAY-23:30 | 0.00 |
June | 0.978982E+10 | 0.235752E+10 | 720.00 | 0.969694E+10 | 92872786.14 | 0.00 | 0.67 | 30-JUN-23:20 | 0.26 | 17-JUN-06:10 | 5829.92 | 30-JUN-23:55 | 5816.86 | 30-JUN-23:50 | 336.43 | 06-JUN-16:40 | 1579.92 | 28-JUN-19:00 | 0.00 |
July | 0.155754E+11 | 0.404212E+10 | 744.00 | 0.154735E+11 | 0.101884E+09 | 0.00 | 0.95 | 16-JUL-18:50 | 0.54 | 08-JUL-06:05 | 7642.70 | 31-JUL-24:00 | 7642.70 | 31-JUL-24:00 | 368.40 | 03-JUL-17:00 | 2663.45 | 16-JUL-18:50 | 0.00 |
August | 0.200627E+11 | 0.496600E+10 | 744.00 | 0.199854E+11 | 77360782.05 | 0.00 | 1.00 | 03-AUG-18:30 | 0.25 | 31-AUG-24:00 | 8647.45 | 05-AUG-20:05 | 8647.45 | 05-AUG-20:05 | 420.96 | 22-AUG-16:00 | 3036.43 | 05-AUG-16:00 | 0.00 |
September | 0.422405E+10 | 0.106935E+10 | 716.21 | 0.413822E+10 | 85830627.06 | 0.00 | 0.49 | 04-SEP-17:51 | 0.00 | 12-SEP-03:45 | 3662.80 | 04-SEP-17:51 | 3662.80 | 04-SEP-17:51 | 341.87 | 07-SEP-15:10 | 1285.85 | 04-SEP-17:21 | 0.00 |
October | 0.731036E+10 | 0.166489E+10 | 743.74 | 0.729785E+10 | 12514699.75 | 0.00 | 0.57 | 15-OCT-16:52 | 0.00 | 10-OCT-02:35 | 4645.97 | 15-OCT-17:05 | 4645.97 | 15-OCT-17:05 | 109.02 | 25-OCT-11:00 | 1229.76 | 18-OCT-16:00 | 0.00 |
November | 0.994023E+10 | 0.221168E+10 | 720.00 | 0.993757E+10 | 2661978.67 | 0.00 | 0.66 | 03-NOV-16:00 | 0.19 | 27-NOV-04:01 | 5884.58 | 03-NOV-16:00 | 5823.67 | 03-NOV-16:20 | 80.03 | 17-NOV-17:05 | 1213.53 | 03-NOV-16:00 | 0.00 |
December | 0.135261E+11 | 0.299518E+10 | 744.00 | 0.135257E+11 | 386785.53 | 0.00 | 0.81 | 06-DEC-16:10 | 0.41 | 31-DEC-23:42 | 7343.55 | 06-DEC-16:10 | 7312.60 | 06-DEC-16:10 | 54.50 | 19-DEC-17:05 | 1478.49 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.115835E+12 | 0.271935E+11 | 8038.85 | 0.115426E+12 | 0.408313E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.138862E+09 | 39950510.84 | 108.69 | 0.138803E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 1647.68 | 1647.68 | 0.00 | 387.55 | 0.00 | ||||||
Maximum of Months | 0.200627E+11 | 0.496600E+10 | 744.00 | 0.199854E+11 | 0.101884E+09 | 0.00 | 1.00 | 0.54 | 8647.45 | 8647.45 | 420.96 | 3036.43 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.73 | 1001.71 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 18.18 | 755.97 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 75.20 | 619.73 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 141.40 | 446.09 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 279.71 | 320.19 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 456.86 | 200.45 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 495.87 | 166.10 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 358.93 | 192.22 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 207.76 | 297.89 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 71.05 | 458.36 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.59 | 664.02 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.49 | 898.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.21 | 177.72 | 500.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.49 | 166.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 495.87 | 1001.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.73 | 1001.71 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 18.18 | 755.97 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 75.20 | 619.73 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 141.40 | 446.09 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 279.71 | 320.19 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 456.86 | 200.45 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 495.87 | 166.10 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 358.93 | 192.22 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 207.76 | 297.89 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 71.05 | 458.36 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.59 | 664.02 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.49 | 898.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.20 | 177.72 | 500.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.49 | 166.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 495.87 | 1001.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.73 | 1001.71 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 18.18 | 755.97 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 75.20 | 619.73 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 141.40 | 446.09 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 279.71 | 320.19 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 456.86 | 200.45 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 495.87 | 166.10 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 358.93 | 192.22 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 207.76 | 297.89 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 71.05 | 458.36 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.59 | 664.02 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.49 | 898.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.21 | 177.72 | 500.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.49 | 166.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 495.87 | 1001.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.73 | 1001.71 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 18.18 | 755.97 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 75.20 | 619.73 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 141.40 | 446.09 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 279.71 | 320.19 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 456.86 | 200.45 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 495.87 | 166.10 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 358.93 | 192.22 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 207.76 | 297.89 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 71.05 | 458.36 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.59 | 664.02 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.49 | 898.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.20 | 177.72 | 500.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.49 | 166.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 495.87 | 1001.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.73 | 1001.67 | 0.00 | 0.00 | 0.00 |
February | 158.47 | 0.00 | 158.47 | 18.18 | 755.93 | 0.00 | 0.00 | 0.00 |
March | 257.43 | 0.00 | 257.43 | 75.20 | 619.71 | 0.00 | 0.00 | 0.00 |
April | 293.52 | 1.71 | 291.81 | 141.40 | 446.07 | 0.00 | 0.00 | 0.00 |
May | 385.46 | 22.84 | 362.62 | 279.70 | 320.18 | 0.00 | 0.00 | 0.00 |
June | 448.85 | 51.59 | 397.26 | 456.84 | 200.44 | 0.00 | 0.00 | 0.00 |
July | 410.05 | 38.41 | 371.64 | 495.85 | 166.10 | 0.00 | 0.00 | 0.00 |
August | 328.57 | 8.81 | 319.77 | 358.92 | 192.21 | 0.00 | 0.00 | 0.00 |
September | 246.08 | 0.09 | 245.99 | 207.75 | 297.88 | 0.00 | 0.00 | 0.00 |
October | 179.50 | 0.00 | 179.50 | 71.05 | 458.35 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.59 | 664.00 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.49 | 898.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.53 | 10.34 | 243.20 | 177.72 | 500.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.49 | 166.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.85 | 51.59 | 397.26 | 495.85 | 1001.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 286.37 | 131.29 | 155.08 | 146.65 | 1019.63 | 0.00 | 0.00 | 0.00 |
February | 447.90 | 222.37 | 225.53 | 326.29 | 764.57 | 0.00 | 0.00 | 0.00 |
March | 602.25 | 249.19 | 353.05 | 480.86 | 637.85 | 0.00 | 0.00 | 0.00 |
April | 768.41 | 380.82 | 387.59 | 738.92 | 462.45 | 0.00 | 0.00 | 0.00 |
May | 848.81 | 377.67 | 471.14 | 882.73 | 356.90 | 0.00 | 0.00 | 0.00 |
June | 1098.67 | 565.37 | 533.29 | 1322.75 | 227.01 | 0.00 | 0.00 | 0.00 |
July | 1153.08 | 651.87 | 501.21 | 1498.31 | 182.44 | 0.00 | 0.00 | 0.00 |
August | 1002.08 | 558.33 | 443.75 | 1271.20 | 205.86 | 0.00 | 0.00 | 0.00 |
September | 708.87 | 365.92 | 342.96 | 811.79 | 311.45 | 0.00 | 0.00 | 0.00 |
October | 508.58 | 258.25 | 250.33 | 474.85 | 471.29 | 0.00 | 0.00 | 0.00 |
November | 322.33 | 150.48 | 171.84 | 212.92 | 661.60 | 0.00 | 0.00 | 0.00 |
December | 237.74 | 102.11 | 135.63 | 111.08 | 899.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 666.56 | 335.05 | 331.51 | 691.95 | 515.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.74 | 102.11 | 135.63 | 111.08 | 182.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1153.08 | 651.87 | 533.29 | 1498.31 | 1019.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 286.37 | 131.29 | 155.08 | 146.65 | 1019.63 | 0.00 | 0.00 | 0.00 |
February | 447.90 | 222.37 | 225.53 | 326.29 | 764.57 | 0.00 | 0.00 | 0.00 |
March | 602.25 | 249.19 | 353.05 | 480.86 | 637.85 | 0.00 | 0.00 | 0.00 |
April | 768.41 | 380.82 | 387.59 | 738.92 | 462.45 | 0.00 | 0.00 | 0.00 |
May | 848.81 | 377.67 | 471.14 | 882.73 | 356.90 | 0.00 | 0.00 | 0.00 |
June | 1098.67 | 565.37 | 533.29 | 1322.75 | 227.01 | 0.00 | 0.00 | 0.00 |
July | 1153.08 | 651.87 | 501.21 | 1498.31 | 182.44 | 0.00 | 0.00 | 0.00 |
August | 1002.08 | 558.33 | 443.75 | 1271.20 | 205.86 | 0.00 | 0.00 | 0.00 |
September | 708.87 | 365.92 | 342.96 | 811.79 | 311.45 | 0.00 | 0.00 | 0.00 |
October | 508.58 | 258.25 | 250.33 | 474.85 | 471.29 | 0.00 | 0.00 | 0.00 |
November | 322.33 | 150.48 | 171.84 | 212.92 | 661.60 | 0.00 | 0.00 | 0.00 |
December | 237.74 | 102.11 | 135.63 | 111.08 | 899.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 666.56 | 335.05 | 331.51 | 691.95 | 515.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.74 | 102.11 | 135.63 | 111.08 | 182.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1153.08 | 651.87 | 533.29 | 1498.31 | 1019.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 286.36 | 131.29 | 155.08 | 146.64 | 1019.61 | 0.00 | 0.00 | 0.00 |
February | 447.89 | 222.37 | 225.53 | 326.29 | 764.56 | 0.00 | 0.00 | 0.00 |
March | 602.24 | 249.19 | 353.05 | 480.85 | 637.83 | 0.00 | 0.00 | 0.00 |
April | 768.39 | 380.81 | 387.58 | 738.91 | 462.44 | 0.00 | 0.00 | 0.00 |
May | 848.79 | 377.66 | 471.13 | 882.72 | 356.89 | 0.00 | 0.00 | 0.00 |
June | 1098.65 | 565.36 | 533.28 | 1322.72 | 227.01 | 0.00 | 0.00 | 0.00 |
July | 1153.06 | 651.86 | 501.21 | 1498.28 | 182.44 | 0.00 | 0.00 | 0.00 |
August | 1002.06 | 558.32 | 443.74 | 1271.18 | 205.85 | 0.00 | 0.00 | 0.00 |
September | 708.86 | 365.91 | 342.95 | 811.77 | 311.44 | 0.00 | 0.00 | 0.00 |
October | 508.57 | 258.24 | 250.33 | 474.84 | 471.28 | 0.00 | 0.00 | 0.00 |
November | 322.32 | 150.48 | 171.84 | 212.91 | 661.59 | 0.00 | 0.00 | 0.00 |
December | 237.73 | 102.11 | 135.63 | 111.08 | 899.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 666.55 | 335.05 | 331.50 | 691.94 | 515.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.73 | 102.11 | 135.63 | 111.08 | 182.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1153.06 | 651.86 | 533.28 | 1498.28 | 1019.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 739.53 | 842.38 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1037.74 | 644.08 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 923.41 | 582.23 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 769.64 | 441.25 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 698.41 | 340.42 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 793.41 | 230.99 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 953.86 | 183.54 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1100.48 | 208.17 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1135.34 | 297.36 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1085.59 | 426.09 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 897.10 | 553.14 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 714.45 | 739.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 903.04 | 456.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 698.41 | 183.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1135.34 | 842.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 739.52 | 842.38 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1037.74 | 644.08 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 923.41 | 582.23 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 769.64 | 441.25 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 698.41 | 340.42 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 793.41 | 230.99 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 953.86 | 183.54 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1100.48 | 208.17 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1135.34 | 297.36 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1085.58 | 426.09 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 897.10 | 553.14 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 714.45 | 739.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 903.04 | 456.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 698.41 | 183.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1135.34 | 842.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 739.53 | 842.38 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1037.74 | 644.08 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 923.41 | 582.23 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 769.64 | 441.25 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 698.41 | 340.42 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 793.41 | 230.99 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 953.86 | 183.54 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1100.48 | 208.17 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1135.34 | 297.36 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1085.59 | 426.09 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 897.10 | 553.14 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 714.45 | 739.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 903.04 | 456.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 698.41 | 183.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1135.34 | 842.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 739.52 | 842.38 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1037.74 | 644.08 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 923.41 | 582.23 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 769.64 | 441.25 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 698.41 | 340.42 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 793.41 | 230.99 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 953.86 | 183.54 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1100.48 | 208.17 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1135.34 | 297.36 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1085.58 | 426.09 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 897.10 | 553.14 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 714.45 | 739.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 903.04 | 456.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 698.41 | 183.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1135.34 | 842.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.13 | 565.04 | 226.09 | 739.50 | 842.35 | 0.00 | 0.00 | 0.00 |
February | 1007.50 | 724.63 | 282.87 | 1037.70 | 644.05 | 0.00 | 0.00 | 0.00 |
March | 900.57 | 505.72 | 394.85 | 923.37 | 582.21 | 0.00 | 0.00 | 0.00 |
April | 723.91 | 346.25 | 377.66 | 769.61 | 441.23 | 0.00 | 0.00 | 0.00 |
May | 643.17 | 213.62 | 429.56 | 698.39 | 340.40 | 0.00 | 0.00 | 0.00 |
June | 639.06 | 186.38 | 452.68 | 793.38 | 230.98 | 0.00 | 0.00 | 0.00 |
July | 688.97 | 254.50 | 434.47 | 953.82 | 183.54 | 0.00 | 0.00 | 0.00 |
August | 818.79 | 412.82 | 405.97 | 1100.44 | 208.16 | 0.00 | 0.00 | 0.00 |
September | 908.14 | 556.45 | 351.69 | 1135.30 | 297.35 | 0.00 | 0.00 | 0.00 |
October | 949.41 | 656.51 | 292.91 | 1085.54 | 426.07 | 0.00 | 0.00 | 0.00 |
November | 865.58 | 626.99 | 238.59 | 897.07 | 553.11 | 0.00 | 0.00 | 0.00 |
December | 752.32 | 543.25 | 209.07 | 714.42 | 739.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 805.99 | 464.29 | 341.70 | 903.00 | 456.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.06 | 186.38 | 209.07 | 698.39 | 183.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.50 | 724.63 | 452.68 | 1135.30 | 842.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 259.39 | 104.54 | 154.85 | 125.41 | 1103.24 | 0.00 | 0.00 | 0.00 |
February | 442.74 | 217.63 | 225.11 | 320.24 | 844.52 | 0.00 | 0.00 | 0.00 |
March | 566.59 | 207.61 | 358.98 | 427.49 | 730.18 | 0.00 | 0.00 | 0.00 |
April | 739.69 | 327.72 | 411.97 | 696.19 | 550.73 | 0.00 | 0.00 | 0.00 |
May | 914.94 | 417.26 | 497.68 | 970.64 | 402.45 | 0.00 | 0.00 | 0.00 |
June | 995.42 | 457.24 | 538.19 | 1184.13 | 277.41 | 0.00 | 0.00 | 0.00 |
July | 1019.70 | 515.27 | 504.43 | 1316.57 | 236.42 | 0.00 | 0.00 | 0.00 |
August | 865.86 | 424.95 | 440.92 | 1080.82 | 265.01 | 0.00 | 0.00 | 0.00 |
September | 696.53 | 352.14 | 344.39 | 801.33 | 357.62 | 0.00 | 0.00 | 0.00 |
October | 497.83 | 247.34 | 250.49 | 465.63 | 540.72 | 0.00 | 0.00 | 0.00 |
November | 352.42 | 174.83 | 177.59 | 257.39 | 758.72 | 0.00 | 0.00 | 0.00 |
December | 236.89 | 99.98 | 136.90 | 112.39 | 1029.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 633.19 | 295.83 | 337.37 | 648.23 | 590.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.89 | 99.98 | 136.90 | 112.39 | 236.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1019.70 | 515.27 | 538.19 | 1316.57 | 1103.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 259.39 | 104.54 | 154.85 | 125.41 | 1103.24 | 0.00 | 0.00 | 0.00 |
February | 442.74 | 217.63 | 225.11 | 320.24 | 844.52 | 0.00 | 0.00 | 0.00 |
March | 566.59 | 207.61 | 358.98 | 427.49 | 730.18 | 0.00 | 0.00 | 0.00 |
April | 739.69 | 327.72 | 411.97 | 696.19 | 550.73 | 0.00 | 0.00 | 0.00 |
May | 914.94 | 417.26 | 497.68 | 970.64 | 402.45 | 0.00 | 0.00 | 0.00 |
June | 995.42 | 457.24 | 538.19 | 1184.13 | 277.41 | 0.00 | 0.00 | 0.00 |
July | 1019.70 | 515.27 | 504.43 | 1316.57 | 236.42 | 0.00 | 0.00 | 0.00 |
August | 865.86 | 424.95 | 440.92 | 1080.82 | 265.01 | 0.00 | 0.00 | 0.00 |
September | 696.53 | 352.14 | 344.39 | 801.33 | 357.62 | 0.00 | 0.00 | 0.00 |
October | 497.83 | 247.34 | 250.49 | 465.63 | 540.72 | 0.00 | 0.00 | 0.00 |
November | 352.42 | 174.83 | 177.59 | 257.39 | 758.72 | 0.00 | 0.00 | 0.00 |
December | 236.89 | 99.98 | 136.90 | 112.39 | 1029.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 633.19 | 295.83 | 337.37 | 648.23 | 590.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.89 | 99.98 | 136.90 | 112.39 | 236.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1019.70 | 515.27 | 538.19 | 1316.57 | 1103.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 259.38 | 104.53 | 154.85 | 125.41 | 1103.22 | 0.00 | 0.00 | 0.00 |
February | 442.73 | 217.62 | 225.10 | 320.23 | 844.50 | 0.00 | 0.00 | 0.00 |
March | 566.58 | 207.60 | 358.98 | 427.48 | 730.16 | 0.00 | 0.00 | 0.00 |
April | 739.68 | 327.71 | 411.97 | 696.18 | 550.72 | 0.00 | 0.00 | 0.00 |
May | 914.93 | 417.26 | 497.67 | 970.62 | 402.44 | 0.00 | 0.00 | 0.00 |
June | 995.41 | 457.23 | 538.18 | 1184.11 | 277.40 | 0.00 | 0.00 | 0.00 |
July | 1019.68 | 515.26 | 504.42 | 1316.54 | 236.41 | 0.00 | 0.00 | 0.00 |
August | 865.85 | 424.94 | 440.91 | 1080.80 | 265.00 | 0.00 | 0.00 | 0.00 |
September | 696.52 | 352.13 | 344.39 | 801.32 | 357.62 | 0.00 | 0.00 | 0.00 |
October | 497.82 | 247.34 | 250.48 | 465.63 | 540.71 | 0.00 | 0.00 | 0.00 |
November | 352.41 | 174.83 | 177.58 | 257.38 | 758.70 | 0.00 | 0.00 | 0.00 |
December | 236.88 | 99.98 | 136.90 | 112.38 | 1029.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 633.18 | 295.82 | 337.36 | 648.22 | 590.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.88 | 99.98 | 136.90 | 112.38 | 236.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1019.68 | 515.26 | 538.18 | 1316.54 | 1103.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 561.19 | 0.00 | 561.19 | 19.85 | 4683.24 | 0.00 | 0.00 | 0.00 |
February | 792.37 | 0.00 | 792.37 | 146.06 | 3461.72 | 0.00 | 0.00 | 0.00 |
March | 1287.17 | 0.00 | 1287.17 | 462.09 | 2805.03 | 0.00 | 0.00 | 0.00 |
April | 1467.64 | 8.56 | 1459.08 | 786.94 | 2000.60 | 0.00 | 0.00 | 0.00 |
May | 1927.37 | 114.21 | 1813.16 | 1446.80 | 1487.94 | 0.00 | 0.00 | 0.00 |
June | 2244.31 | 257.96 | 1986.35 | 2310.67 | 958.44 | 0.00 | 0.00 | 0.00 |
July | 2050.30 | 192.04 | 1858.27 | 2509.78 | 799.31 | 0.00 | 0.00 | 0.00 |
August | 1642.92 | 44.04 | 1598.88 | 1829.18 | 912.34 | 0.00 | 0.00 | 0.00 |
September | 1230.43 | 0.44 | 1229.99 | 1072.22 | 1387.25 | 0.00 | 0.00 | 0.00 |
October | 897.53 | 0.00 | 897.53 | 418.45 | 2053.30 | 0.00 | 0.00 | 0.00 |
November | 610.15 | 0.00 | 610.15 | 102.92 | 2917.99 | 0.00 | 0.00 | 0.00 |
December | 470.59 | 0.00 | 470.59 | 10.43 | 4000.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.70 | 51.69 | 1216.01 | 931.14 | 2284.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.59 | 0.00 | 470.59 | 10.43 | 799.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2244.31 | 257.96 | 1986.35 | 2509.78 | 4683.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 859.09 | 393.86 | 465.23 | 464.70 | 2874.80 | 0.00 | 0.00 | 0.00 |
February | 1343.70 | 667.11 | 676.58 | 1011.12 | 2142.66 | 0.00 | 0.00 | 0.00 |
March | 1806.72 | 747.57 | 1059.15 | 1467.07 | 1790.19 | 0.00 | 0.00 | 0.00 |
April | 2305.20 | 1142.44 | 1162.76 | 2223.28 | 1302.70 | 0.00 | 0.00 | 0.00 |
May | 2546.39 | 1132.98 | 1413.41 | 2641.65 | 1016.48 | 0.00 | 0.00 | 0.00 |
June | 3295.97 | 1696.11 | 1599.87 | 3941.92 | 668.71 | 0.00 | 0.00 | 0.00 |
July | 3459.22 | 1955.59 | 1503.63 | 4467.79 | 546.86 | 0.00 | 0.00 | 0.00 |
August | 3006.21 | 1674.97 | 1331.24 | 3788.48 | 617.13 | 0.00 | 0.00 | 0.00 |
September | 2126.60 | 1097.74 | 1028.86 | 2423.10 | 898.77 | 0.00 | 0.00 | 0.00 |
October | 1525.72 | 774.74 | 750.99 | 1437.06 | 1319.88 | 0.00 | 0.00 | 0.00 |
November | 966.97 | 451.45 | 515.52 | 668.24 | 1810.64 | 0.00 | 0.00 | 0.00 |
December | 713.20 | 306.32 | 406.88 | 364.13 | 2458.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1999.67 | 1005.15 | 994.52 | 2081.00 | 1451.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.20 | 306.32 | 406.88 | 364.13 | 546.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3459.22 | 1955.59 | 1599.87 | 4467.79 | 2874.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3955.78 | 2825.30 | 1130.48 | 3692.73 | 4105.86 | 0.00 | 0.00 | 0.00 |
February | 5037.63 | 3623.25 | 1414.38 | 5169.38 | 3119.67 | 0.00 | 0.00 | 0.00 |
March | 4502.98 | 2528.67 | 1974.31 | 4602.68 | 2807.05 | 0.00 | 0.00 | 0.00 |
April | 3619.64 | 1731.30 | 1888.35 | 3843.78 | 2103.79 | 0.00 | 0.00 | 0.00 |
May | 3215.96 | 1068.11 | 2147.85 | 3480.03 | 1644.60 | 0.00 | 0.00 | 0.00 |
June | 3195.38 | 931.93 | 2263.46 | 3953.64 | 1123.51 | 0.00 | 0.00 | 0.00 |
July | 3444.94 | 1272.55 | 2172.39 | 4761.03 | 896.92 | 0.00 | 0.00 | 0.00 |
August | 4094.09 | 2064.17 | 2029.92 | 5485.96 | 1016.01 | 0.00 | 0.00 | 0.00 |
September | 4540.83 | 2782.32 | 1758.52 | 5634.19 | 1457.01 | 0.00 | 0.00 | 0.00 |
October | 4747.20 | 3282.63 | 1464.57 | 5397.48 | 2066.15 | 0.00 | 0.00 | 0.00 |
November | 4328.04 | 3135.06 | 1192.98 | 4484.53 | 2650.41 | 0.00 | 0.00 | 0.00 |
December | 3761.73 | 2716.35 | 1045.38 | 3597.43 | 3503.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4030.07 | 2321.53 | 1708.53 | 4503.46 | 2204.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3195.38 | 931.93 | 1045.38 | 3480.03 | 896.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5037.63 | 3623.25 | 2263.46 | 5634.19 | 4105.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 778.15 | 313.60 | 464.55 | 400.14 | 3048.22 | 0.00 | 0.00 | 0.00 |
February | 1328.19 | 652.87 | 675.32 | 1017.49 | 2246.93 | 0.00 | 0.00 | 0.00 |
March | 1699.76 | 622.82 | 1076.94 | 1350.06 | 1908.71 | 0.00 | 0.00 | 0.00 |
April | 2219.05 | 983.14 | 1235.91 | 2152.83 | 1423.50 | 0.00 | 0.00 | 0.00 |
May | 2744.81 | 1251.78 | 1493.03 | 2930.54 | 1111.61 | 0.00 | 0.00 | 0.00 |
June | 2986.24 | 1371.69 | 1614.55 | 3573.79 | 765.12 | 0.00 | 0.00 | 0.00 |
July | 3059.07 | 1545.79 | 1513.28 | 3982.27 | 644.39 | 0.00 | 0.00 | 0.00 |
August | 2597.57 | 1274.83 | 1322.74 | 3287.30 | 698.19 | 0.00 | 0.00 | 0.00 |
September | 2089.58 | 1056.41 | 1033.17 | 2419.17 | 988.46 | 0.00 | 0.00 | 0.00 |
October | 1493.48 | 742.03 | 751.45 | 1443.17 | 1423.66 | 0.00 | 0.00 | 0.00 |
November | 1057.24 | 524.48 | 532.76 | 823.42 | 1924.75 | 0.00 | 0.00 | 0.00 |
December | 710.66 | 299.95 | 410.71 | 381.17 | 2590.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1899.56 | 887.47 | 1012.09 | 1985.15 | 1562.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 710.66 | 299.95 | 410.71 | 381.17 | 644.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3059.07 | 1545.79 | 1614.55 | 3982.27 | 3048.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 561.19 | 0.00 | 561.19 | 26.68 | 4546.60 | 0.00 | 0.00 | 0.00 |
February | 792.37 | 0.00 | 792.37 | 171.07 | 3313.32 | 0.00 | 0.00 | 0.00 |
March | 1287.17 | 0.00 | 1287.17 | 506.56 | 2643.12 | 0.00 | 0.00 | 0.00 |
April | 1467.64 | 8.56 | 1459.08 | 841.81 | 1853.65 | 0.00 | 0.00 | 0.00 |
May | 1927.37 | 114.21 | 1813.16 | 1479.62 | 1403.06 | 0.00 | 0.00 | 0.00 |
June | 2244.31 | 257.96 | 1986.35 | 2318.44 | 932.46 | 0.00 | 0.00 | 0.00 |
July | 2050.30 | 192.04 | 1858.27 | 2502.96 | 788.03 | 0.00 | 0.00 | 0.00 |
August | 1642.92 | 44.04 | 1598.88 | 1831.26 | 887.15 | 0.00 | 0.00 | 0.00 |
September | 1230.43 | 0.44 | 1229.99 | 1095.76 | 1308.67 | 0.00 | 0.00 | 0.00 |
October | 897.53 | 0.00 | 897.53 | 474.86 | 1872.10 | 0.00 | 0.00 | 0.00 |
November | 610.15 | 0.00 | 610.15 | 128.89 | 2697.71 | 0.00 | 0.00 | 0.00 |
December | 470.59 | 0.00 | 470.59 | 13.01 | 3838.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.70 | 51.69 | 1216.01 | 954.03 | 2169.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.59 | 0.00 | 470.59 | 13.01 | 788.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2244.31 | 257.96 | 1986.35 | 2502.96 | 4546.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 859.09 | 393.86 | 465.23 | 478.66 | 2800.14 | 0.00 | 0.00 | 0.00 |
February | 1343.70 | 667.11 | 676.58 | 1043.08 | 2048.66 | 0.00 | 0.00 | 0.00 |
March | 1806.72 | 747.57 | 1059.15 | 1508.31 | 1686.51 | 0.00 | 0.00 | 0.00 |
April | 2305.20 | 1142.44 | 1162.76 | 2260.44 | 1213.77 | 0.00 | 0.00 | 0.00 |
May | 2546.39 | 1132.98 | 1413.41 | 2659.43 | 964.38 | 0.00 | 0.00 | 0.00 |
June | 3295.97 | 1696.11 | 1599.87 | 3944.17 | 653.42 | 0.00 | 0.00 | 0.00 |
July | 3459.22 | 1955.59 | 1503.63 | 4463.38 | 539.75 | 0.00 | 0.00 | 0.00 |
August | 3006.21 | 1674.97 | 1331.24 | 3789.25 | 603.01 | 0.00 | 0.00 | 0.00 |
September | 2126.60 | 1097.74 | 1028.86 | 2438.98 | 855.21 | 0.00 | 0.00 | 0.00 |
October | 1525.72 | 774.74 | 750.99 | 1480.64 | 1211.38 | 0.00 | 0.00 | 0.00 |
November | 966.97 | 451.45 | 515.52 | 708.16 | 1668.88 | 0.00 | 0.00 | 0.00 |
December | 713.20 | 306.32 | 406.88 | 378.69 | 2358.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1999.67 | 1005.15 | 994.52 | 2102.10 | 1381.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.20 | 306.32 | 406.88 | 378.69 | 539.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3459.22 | 1955.59 | 1599.87 | 4463.38 | 2800.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3955.78 | 2825.30 | 1130.48 | 3726.90 | 3955.47 | 0.00 | 0.00 | 0.00 |
February | 5037.63 | 3623.25 | 1414.38 | 5211.84 | 2967.75 | 0.00 | 0.00 | 0.00 |
March | 4502.98 | 2528.67 | 1974.31 | 4647.18 | 2646.91 | 0.00 | 0.00 | 0.00 |
April | 3619.64 | 1731.30 | 1888.35 | 3881.69 | 1964.11 | 0.00 | 0.00 | 0.00 |
May | 3215.96 | 1068.11 | 2147.85 | 3496.38 | 1559.34 | 0.00 | 0.00 | 0.00 |
June | 3195.38 | 931.93 | 2263.46 | 3948.85 | 1092.37 | 0.00 | 0.00 | 0.00 |
July | 3444.94 | 1272.55 | 2172.39 | 4745.58 | 882.48 | 0.00 | 0.00 | 0.00 |
August | 4094.09 | 2064.17 | 2029.92 | 5476.72 | 990.14 | 0.00 | 0.00 | 0.00 |
September | 4540.83 | 2782.32 | 1758.52 | 5642.60 | 1387.26 | 0.00 | 0.00 | 0.00 |
October | 4747.20 | 3282.63 | 1464.57 | 5442.47 | 1909.20 | 0.00 | 0.00 | 0.00 |
November | 4328.04 | 3135.06 | 1192.98 | 4550.20 | 2453.09 | 0.00 | 0.00 | 0.00 |
December | 3761.73 | 2716.35 | 1045.38 | 3644.73 | 3332.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4030.07 | 2321.53 | 1708.53 | 4529.34 | 2091.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3195.38 | 931.93 | 1045.38 | 3496.38 | 882.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5037.63 | 3623.25 | 2263.46 | 5642.60 | 3955.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 778.15 | 313.60 | 464.55 | 409.10 | 2957.66 | 0.00 | 0.00 | 0.00 |
February | 1328.19 | 652.87 | 675.32 | 1034.41 | 2157.31 | 0.00 | 0.00 | 0.00 |
March | 1699.76 | 622.82 | 1076.94 | 1374.13 | 1813.24 | 0.00 | 0.00 | 0.00 |
April | 2219.05 | 983.14 | 1235.91 | 2177.54 | 1338.91 | 0.00 | 0.00 | 0.00 |
May | 2744.81 | 1251.78 | 1493.03 | 2939.48 | 1058.22 | 0.00 | 0.00 | 0.00 |
June | 2986.24 | 1371.69 | 1614.55 | 3568.10 | 744.70 | 0.00 | 0.00 | 0.00 |
July | 3059.07 | 1545.79 | 1513.28 | 3971.38 | 634.12 | 0.00 | 0.00 | 0.00 |
August | 2597.57 | 1274.83 | 1322.74 | 3280.95 | 681.36 | 0.00 | 0.00 | 0.00 |
September | 2089.58 | 1056.41 | 1033.17 | 2426.07 | 942.51 | 0.00 | 0.00 | 0.00 |
October | 1493.48 | 742.03 | 751.45 | 1471.67 | 1322.01 | 0.00 | 0.00 | 0.00 |
November | 1057.24 | 524.48 | 532.76 | 847.29 | 1797.76 | 0.00 | 0.00 | 0.00 |
December | 710.66 | 299.95 | 410.71 | 390.57 | 2491.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1899.56 | 887.47 | 1012.09 | 1995.86 | 1492.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 710.66 | 299.95 | 410.71 | 390.57 | 634.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3059.07 | 1545.79 | 1614.55 | 3971.38 | 2957.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 4638748.59 | 0.268299E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 43971722.87 | 0.182883E+10 |
March | 0.689519E+09 | 0.00 | 0.689519E+09 | 0.201423E+09 | 0.165989E+10 |
April | 0.760836E+09 | 4440069.61 | 0.756396E+09 | 0.366511E+09 | 0.115627E+10 |
May | 0.103247E+10 | 61179947.39 | 0.971285E+09 | 0.749172E+09 | 0.857595E+09 |
June | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.118417E+10 | 0.519565E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995449E+09 | 0.132815E+10 | 0.444894E+09 |
August | 0.880089E+09 | 23590500.52 | 0.856499E+09 | 0.961361E+09 | 0.514836E+09 |
September | 0.637864E+09 | 228900.10 | 0.637635E+09 | 0.538502E+09 | 0.772128E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.190297E+09 | 0.122768E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 35222839.66 | 0.172115E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310685.55 | 0.240616E+10 |
Annual Sum or Average | 0.799576E+10 | 0.326041E+09 | 0.766971E+10 | 0.560473E+10 | 0.157920E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310685.55 | 0.444894E+09 |
Maximum of Months | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.132815E+10 | 0.268299E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 4638722.46 | 0.268299E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 43971602.04 | 0.182883E+10 |
March | 0.689518E+09 | 0.00 | 0.689518E+09 | 0.201422E+09 | 0.165989E+10 |
April | 0.760836E+09 | 4440064.28 | 0.756395E+09 | 0.366511E+09 | 0.115627E+10 |
May | 0.103246E+10 | 61179873.98 | 0.971284E+09 | 0.749171E+09 | 0.857595E+09 |
June | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.118417E+10 | 0.519565E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995448E+09 | 0.132815E+10 | 0.444894E+09 |
August | 0.880089E+09 | 23590472.21 | 0.856498E+09 | 0.961360E+09 | 0.514836E+09 |
September | 0.637863E+09 | 228899.82 | 0.637634E+09 | 0.538502E+09 | 0.772128E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.190296E+09 | 0.122768E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 35222736.97 | 0.172115E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310676.99 | 0.240616E+10 |
Annual Sum or Average | 0.799575E+10 | 0.326040E+09 | 0.766971E+10 | 0.560472E+10 | 0.157920E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310676.99 | 0.444894E+09 |
Maximum of Months | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.132815E+10 | 0.268299E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 4638748.59 | 0.268299E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 43971722.87 | 0.182883E+10 |
March | 0.689519E+09 | 0.00 | 0.689519E+09 | 0.201423E+09 | 0.165989E+10 |
April | 0.760836E+09 | 4440069.61 | 0.756396E+09 | 0.366511E+09 | 0.115627E+10 |
May | 0.103247E+10 | 61179947.39 | 0.971285E+09 | 0.749172E+09 | 0.857595E+09 |
June | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.118417E+10 | 0.519565E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995449E+09 | 0.132815E+10 | 0.444894E+09 |
August | 0.880089E+09 | 23590500.52 | 0.856499E+09 | 0.961361E+09 | 0.514836E+09 |
September | 0.637864E+09 | 228900.10 | 0.637635E+09 | 0.538502E+09 | 0.772128E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.190297E+09 | 0.122768E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 35222839.66 | 0.172115E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310685.55 | 0.240616E+10 |
Annual Sum or Average | 0.799576E+10 | 0.326041E+09 | 0.766971E+10 | 0.560473E+10 | 0.157920E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310685.55 | 0.444894E+09 |
Maximum of Months | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.132815E+10 | 0.268299E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 4638722.46 | 0.268299E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 43971602.04 | 0.182883E+10 |
March | 0.689518E+09 | 0.00 | 0.689518E+09 | 0.201422E+09 | 0.165989E+10 |
April | 0.760836E+09 | 4440064.28 | 0.756395E+09 | 0.366511E+09 | 0.115627E+10 |
May | 0.103246E+10 | 61179873.98 | 0.971284E+09 | 0.749171E+09 | 0.857595E+09 |
June | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.118417E+10 | 0.519565E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995448E+09 | 0.132815E+10 | 0.444894E+09 |
August | 0.880089E+09 | 23590472.21 | 0.856498E+09 | 0.961360E+09 | 0.514836E+09 |
September | 0.637863E+09 | 228899.82 | 0.637634E+09 | 0.538502E+09 | 0.772128E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.190296E+09 | 0.122768E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 35222736.97 | 0.172115E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310676.99 | 0.240616E+10 |
Annual Sum or Average | 0.799575E+10 | 0.326040E+09 | 0.766971E+10 | 0.560472E+10 | 0.157920E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1310676.99 | 0.444894E+09 |
Maximum of Months | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.132815E+10 | 0.268299E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300611E+09 | 0.00 | 0.300611E+09 | 4638561.63 | 0.268288E+10 |
February | 0.383369E+09 | 0.00 | 0.383369E+09 | 43969950.62 | 0.182876E+10 |
March | 0.689491E+09 | 0.00 | 0.689491E+09 | 0.201415E+09 | 0.165983E+10 |
April | 0.760805E+09 | 4439890.66 | 0.756366E+09 | 0.366497E+09 | 0.115622E+10 |
May | 0.103242E+10 | 61177481.56 | 0.971246E+09 | 0.749141E+09 | 0.857561E+09 |
June | 0.116342E+10 | 0.133725E+09 | 0.102969E+10 | 0.118412E+10 | 0.519544E+09 |
July | 0.109828E+10 | 0.102867E+09 | 0.995409E+09 | 0.132809E+10 | 0.444877E+09 |
August | 0.880054E+09 | 23589549.72 | 0.856464E+09 | 0.961322E+09 | 0.514815E+09 |
September | 0.637838E+09 | 228890.87 | 0.637609E+09 | 0.538480E+09 | 0.772097E+09 |
October | 0.480775E+09 | 0.00 | 0.480775E+09 | 0.190289E+09 | 0.122763E+10 |
November | 0.316292E+09 | 0.00 | 0.316292E+09 | 35221420.02 | 0.172108E+10 |
December | 0.252080E+09 | 0.00 | 0.252080E+09 | 1310632.72 | 0.240606E+10 |
Annual Sum or Average | 0.799543E+10 | 0.326028E+09 | 0.766941E+10 | 0.560450E+10 | 0.157914E+11 |
Minimum of Months | 0.252080E+09 | 0.00 | 0.252080E+09 | 1310632.72 | 0.444877E+09 |
Maximum of Months | 0.116342E+10 | 0.133725E+09 | 0.102969E+10 | 0.132809E+10 | 0.268288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.767004E+09 | 0.351640E+09 | 0.415364E+09 | 0.392775E+09 | 0.273098E+10 |
February | 0.108357E+10 | 0.537965E+09 | 0.545602E+09 | 0.789368E+09 | 0.184966E+10 |
March | 0.161306E+10 | 0.667438E+09 | 0.945619E+09 | 0.128794E+10 | 0.170841E+10 |
April | 0.199171E+10 | 0.987077E+09 | 0.100463E+10 | 0.191528E+10 | 0.119868E+10 |
May | 0.227344E+10 | 0.101154E+10 | 0.126190E+10 | 0.236431E+10 | 0.955920E+09 |
June | 0.284775E+10 | 0.146545E+10 | 0.138230E+10 | 0.342856E+10 | 0.588412E+09 |
July | 0.308842E+10 | 0.174597E+10 | 0.134245E+10 | 0.401306E+10 | 0.488656E+09 |
August | 0.268397E+10 | 0.149543E+10 | 0.118855E+10 | 0.340480E+10 | 0.551364E+09 |
September | 0.183740E+10 | 0.948459E+09 | 0.888942E+09 | 0.210415E+10 | 0.807280E+09 |
October | 0.136218E+10 | 0.691694E+09 | 0.670486E+09 | 0.127184E+10 | 0.126230E+10 |
November | 0.835475E+09 | 0.390057E+09 | 0.445418E+09 | 0.551879E+09 | 0.171488E+10 |
December | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.297515E+09 | 0.240913E+10 |
Annual Sum or Average | 0.210207E+11 | 0.105662E+11 | 0.104545E+11 | 0.218215E+11 | 0.162657E+11 |
Minimum of Months | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.297515E+09 | 0.488656E+09 |
Maximum of Months | 0.308842E+10 | 0.174597E+10 | 0.138230E+10 | 0.401306E+10 | 0.273098E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.767004E+09 | 0.351640E+09 | 0.415364E+09 | 0.392775E+09 | 0.273098E+10 |
February | 0.108357E+10 | 0.537965E+09 | 0.545602E+09 | 0.789368E+09 | 0.184966E+10 |
March | 0.161306E+10 | 0.667438E+09 | 0.945619E+09 | 0.128794E+10 | 0.170841E+10 |
April | 0.199171E+10 | 0.987077E+09 | 0.100463E+10 | 0.191528E+10 | 0.119868E+10 |
May | 0.227344E+10 | 0.101154E+10 | 0.126190E+10 | 0.236431E+10 | 0.955920E+09 |
June | 0.284775E+10 | 0.146545E+10 | 0.138230E+10 | 0.342856E+10 | 0.588412E+09 |
July | 0.308842E+10 | 0.174597E+10 | 0.134245E+10 | 0.401306E+10 | 0.488656E+09 |
August | 0.268397E+10 | 0.149543E+10 | 0.118855E+10 | 0.340480E+10 | 0.551364E+09 |
September | 0.183740E+10 | 0.948459E+09 | 0.888942E+09 | 0.210415E+10 | 0.807280E+09 |
October | 0.136218E+10 | 0.691694E+09 | 0.670486E+09 | 0.127184E+10 | 0.126230E+10 |
November | 0.835475E+09 | 0.390057E+09 | 0.445418E+09 | 0.551879E+09 | 0.171488E+10 |
December | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.297515E+09 | 0.240913E+10 |
Annual Sum or Average | 0.210207E+11 | 0.105662E+11 | 0.104545E+11 | 0.218215E+11 | 0.162657E+11 |
Minimum of Months | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.297515E+09 | 0.488656E+09 |
Maximum of Months | 0.308842E+10 | 0.174597E+10 | 0.138230E+10 | 0.401306E+10 | 0.273098E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.766990E+09 | 0.351634E+09 | 0.415356E+09 | 0.392768E+09 | 0.273093E+10 |
February | 0.108355E+10 | 0.537955E+09 | 0.545592E+09 | 0.789354E+09 | 0.184962E+10 |
March | 0.161303E+10 | 0.667425E+09 | 0.945601E+09 | 0.128792E+10 | 0.170837E+10 |
April | 0.199167E+10 | 0.987059E+09 | 0.100462E+10 | 0.191525E+10 | 0.119866E+10 |
May | 0.227340E+10 | 0.101152E+10 | 0.126188E+10 | 0.236426E+10 | 0.955902E+09 |
June | 0.284770E+10 | 0.146542E+10 | 0.138227E+10 | 0.342850E+10 | 0.588401E+09 |
July | 0.308836E+10 | 0.174593E+10 | 0.134243E+10 | 0.401299E+10 | 0.488647E+09 |
August | 0.268392E+10 | 0.149540E+10 | 0.118853E+10 | 0.340473E+10 | 0.551354E+09 |
September | 0.183737E+10 | 0.948442E+09 | 0.888925E+09 | 0.210411E+10 | 0.807265E+09 |
October | 0.136216E+10 | 0.691681E+09 | 0.670474E+09 | 0.127182E+10 | 0.126227E+10 |
November | 0.835459E+09 | 0.390050E+09 | 0.445410E+09 | 0.551869E+09 | 0.171485E+10 |
December | 0.636740E+09 | 0.273481E+09 | 0.363259E+09 | 0.297509E+09 | 0.240908E+10 |
Annual Sum or Average | 0.210203E+11 | 0.105660E+11 | 0.104543E+11 | 0.218211E+11 | 0.162654E+11 |
Minimum of Months | 0.636740E+09 | 0.273481E+09 | 0.363259E+09 | 0.297509E+09 | 0.488647E+09 |
Maximum of Months | 0.308836E+10 | 0.174593E+10 | 0.138227E+10 | 0.401299E+10 | 0.273093E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605585E+09 | 0.198074E+10 | 0.225623E+10 |
February | 0.243744E+10 | 0.175310E+10 | 0.684341E+09 | 0.251049E+10 | 0.155815E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.247326E+10 | 0.155945E+10 |
April | 0.187645E+10 | 0.897516E+09 | 0.978930E+09 | 0.199491E+10 | 0.114372E+10 |
May | 0.172275E+10 | 0.572172E+09 | 0.115058E+10 | 0.187063E+10 | 0.911777E+09 |
June | 0.165651E+10 | 0.483116E+09 | 0.117339E+10 | 0.205652E+10 | 0.598720E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.255481E+10 | 0.491606E+09 |
August | 0.219315E+10 | 0.110575E+10 | 0.108740E+10 | 0.294753E+10 | 0.557555E+09 |
September | 0.235400E+10 | 0.144237E+10 | 0.911627E+09 | 0.294281E+10 | 0.770765E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290763E+10 | 0.114123E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232529E+10 | 0.143373E+10 |
December | 0.201511E+10 | 0.145511E+10 | 0.559996E+09 | 0.191358E+10 | 0.197949E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146426E+11 | 0.107762E+11 | 0.284782E+11 | 0.144024E+11 |
Minimum of Months | 0.165651E+10 | 0.483116E+09 | 0.559996E+09 | 0.187063E+10 | 0.491606E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294753E+10 | 0.225623E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605584E+09 | 0.198074E+10 | 0.225623E+10 |
February | 0.243743E+10 | 0.175309E+10 | 0.684341E+09 | 0.251049E+10 | 0.155815E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.247325E+10 | 0.155945E+10 |
April | 0.187644E+10 | 0.897515E+09 | 0.978929E+09 | 0.199491E+10 | 0.114372E+10 |
May | 0.172275E+10 | 0.572171E+09 | 0.115057E+10 | 0.187063E+10 | 0.911777E+09 |
June | 0.165650E+10 | 0.483116E+09 | 0.117339E+10 | 0.205652E+10 | 0.598720E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.255481E+10 | 0.491606E+09 |
August | 0.219315E+10 | 0.110574E+10 | 0.108740E+10 | 0.294752E+10 | 0.557555E+09 |
September | 0.235399E+10 | 0.144237E+10 | 0.911626E+09 | 0.294281E+10 | 0.770765E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290763E+10 | 0.114123E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232528E+10 | 0.143373E+10 |
December | 0.201510E+10 | 0.145511E+10 | 0.559995E+09 | 0.191358E+10 | 0.197949E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146425E+11 | 0.107762E+11 | 0.284782E+11 | 0.144024E+11 |
Minimum of Months | 0.165650E+10 | 0.483116E+09 | 0.559995E+09 | 0.187063E+10 | 0.491606E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294752E+10 | 0.225623E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605585E+09 | 0.198074E+10 | 0.225623E+10 |
February | 0.243744E+10 | 0.175310E+10 | 0.684341E+09 | 0.251049E+10 | 0.155815E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.247326E+10 | 0.155945E+10 |
April | 0.187645E+10 | 0.897516E+09 | 0.978930E+09 | 0.199491E+10 | 0.114372E+10 |
May | 0.172275E+10 | 0.572172E+09 | 0.115058E+10 | 0.187063E+10 | 0.911777E+09 |
June | 0.165651E+10 | 0.483116E+09 | 0.117339E+10 | 0.205652E+10 | 0.598720E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.255481E+10 | 0.491606E+09 |
August | 0.219315E+10 | 0.110575E+10 | 0.108740E+10 | 0.294753E+10 | 0.557555E+09 |
September | 0.235400E+10 | 0.144237E+10 | 0.911627E+09 | 0.294281E+10 | 0.770765E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290763E+10 | 0.114123E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232529E+10 | 0.143373E+10 |
December | 0.201511E+10 | 0.145511E+10 | 0.559996E+09 | 0.191358E+10 | 0.197949E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146426E+11 | 0.107762E+11 | 0.284782E+11 | 0.144024E+11 |
Minimum of Months | 0.165651E+10 | 0.483116E+09 | 0.559996E+09 | 0.187063E+10 | 0.491606E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294753E+10 | 0.225623E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605584E+09 | 0.198074E+10 | 0.225623E+10 |
February | 0.243743E+10 | 0.175309E+10 | 0.684341E+09 | 0.251049E+10 | 0.155815E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.247325E+10 | 0.155945E+10 |
April | 0.187644E+10 | 0.897515E+09 | 0.978929E+09 | 0.199491E+10 | 0.114372E+10 |
May | 0.172275E+10 | 0.572171E+09 | 0.115057E+10 | 0.187063E+10 | 0.911777E+09 |
June | 0.165650E+10 | 0.483116E+09 | 0.117339E+10 | 0.205652E+10 | 0.598720E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.255481E+10 | 0.491606E+09 |
August | 0.219315E+10 | 0.110574E+10 | 0.108740E+10 | 0.294752E+10 | 0.557555E+09 |
September | 0.235399E+10 | 0.144237E+10 | 0.911626E+09 | 0.294281E+10 | 0.770765E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290763E+10 | 0.114123E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232528E+10 | 0.143373E+10 |
December | 0.201510E+10 | 0.145511E+10 | 0.559995E+09 | 0.191358E+10 | 0.197949E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146425E+11 | 0.107762E+11 | 0.284782E+11 | 0.144024E+11 |
Minimum of Months | 0.165650E+10 | 0.483116E+09 | 0.559995E+09 | 0.187063E+10 | 0.491606E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294752E+10 | 0.225623E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211897E+10 | 0.151341E+10 | 0.605560E+09 | 0.198066E+10 | 0.225614E+10 |
February | 0.243734E+10 | 0.175302E+10 | 0.684314E+09 | 0.251039E+10 | 0.155809E+10 |
March | 0.241209E+10 | 0.135452E+10 | 0.105757E+10 | 0.247316E+10 | 0.155939E+10 |
April | 0.187637E+10 | 0.897480E+09 | 0.978891E+09 | 0.199483E+10 | 0.114367E+10 |
May | 0.172268E+10 | 0.572149E+09 | 0.115053E+10 | 0.187056E+10 | 0.911740E+09 |
June | 0.165644E+10 | 0.483097E+09 | 0.117334E+10 | 0.205644E+10 | 0.598696E+09 |
July | 0.184533E+10 | 0.681661E+09 | 0.116367E+10 | 0.255471E+10 | 0.491586E+09 |
August | 0.219306E+10 | 0.110570E+10 | 0.108736E+10 | 0.294741E+10 | 0.557532E+09 |
September | 0.235390E+10 | 0.144231E+10 | 0.911590E+09 | 0.294269E+10 | 0.770734E+09 |
October | 0.254291E+10 | 0.175839E+10 | 0.784520E+09 | 0.290752E+10 | 0.114118E+10 |
November | 0.224359E+10 | 0.162517E+10 | 0.618424E+09 | 0.232519E+10 | 0.143367E+10 |
December | 0.201503E+10 | 0.145505E+10 | 0.559973E+09 | 0.191350E+10 | 0.197941E+10 |
Annual Sum or Average | 0.254177E+11 | 0.146420E+11 | 0.107757E+11 | 0.284771E+11 | 0.144018E+11 |
Minimum of Months | 0.165644E+10 | 0.483097E+09 | 0.559973E+09 | 0.187056E+10 | 0.491586E+09 |
Maximum of Months | 0.254291E+10 | 0.175839E+10 | 0.117334E+10 | 0.294741E+10 | 0.225614E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694743E+09 | 0.279987E+09 | 0.414756E+09 | 0.335896E+09 | 0.295492E+10 |
February | 0.107106E+10 | 0.526483E+09 | 0.544582E+09 | 0.774713E+09 | 0.204305E+10 |
March | 0.151756E+10 | 0.556058E+09 | 0.961505E+09 | 0.114498E+10 | 0.195570E+10 |
April | 0.191728E+10 | 0.849443E+09 | 0.106784E+10 | 0.180454E+10 | 0.142750E+10 |
May | 0.245059E+10 | 0.111760E+10 | 0.133299E+10 | 0.259977E+10 | 0.107793E+10 |
June | 0.258014E+10 | 0.118515E+10 | 0.139499E+10 | 0.306927E+10 | 0.719047E+09 |
July | 0.273117E+10 | 0.138010E+10 | 0.135107E+10 | 0.352629E+10 | 0.633225E+09 |
August | 0.231913E+10 | 0.113818E+10 | 0.118095E+10 | 0.289486E+10 | 0.709802E+09 |
September | 0.180541E+10 | 0.912744E+09 | 0.892670E+09 | 0.207705E+10 | 0.926961E+09 |
October | 0.133339E+10 | 0.662489E+09 | 0.670899E+09 | 0.124715E+10 | 0.144826E+10 |
November | 0.913463E+09 | 0.453156E+09 | 0.460307E+09 | 0.667151E+09 | 0.196659E+10 |
December | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.301013E+09 | 0.275713E+10 |
Annual Sum or Average | 0.199684E+11 | 0.932919E+10 | 0.106392E+11 | 0.204427E+11 | 0.186201E+11 |
Minimum of Months | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.301013E+09 | 0.633225E+09 |
Maximum of Months | 0.273117E+10 | 0.138010E+10 | 0.139499E+10 | 0.352629E+10 | 0.295492E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694743E+09 | 0.279987E+09 | 0.414756E+09 | 0.335896E+09 | 0.295492E+10 |
February | 0.107106E+10 | 0.526483E+09 | 0.544582E+09 | 0.774713E+09 | 0.204305E+10 |
March | 0.151756E+10 | 0.556058E+09 | 0.961505E+09 | 0.114498E+10 | 0.195570E+10 |
April | 0.191728E+10 | 0.849443E+09 | 0.106784E+10 | 0.180454E+10 | 0.142750E+10 |
May | 0.245059E+10 | 0.111760E+10 | 0.133299E+10 | 0.259977E+10 | 0.107793E+10 |
June | 0.258014E+10 | 0.118515E+10 | 0.139499E+10 | 0.306927E+10 | 0.719047E+09 |
July | 0.273117E+10 | 0.138010E+10 | 0.135107E+10 | 0.352629E+10 | 0.633225E+09 |
August | 0.231913E+10 | 0.113818E+10 | 0.118095E+10 | 0.289486E+10 | 0.709802E+09 |
September | 0.180541E+10 | 0.912744E+09 | 0.892670E+09 | 0.207705E+10 | 0.926961E+09 |
October | 0.133339E+10 | 0.662489E+09 | 0.670899E+09 | 0.124715E+10 | 0.144826E+10 |
November | 0.913463E+09 | 0.453156E+09 | 0.460307E+09 | 0.667151E+09 | 0.196659E+10 |
December | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.301013E+09 | 0.275713E+10 |
Annual Sum or Average | 0.199684E+11 | 0.932919E+10 | 0.106392E+11 | 0.204427E+11 | 0.186201E+11 |
Minimum of Months | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.301013E+09 | 0.633225E+09 |
Maximum of Months | 0.273117E+10 | 0.138010E+10 | 0.139499E+10 | 0.352629E+10 | 0.295492E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694730E+09 | 0.279982E+09 | 0.414749E+09 | 0.335890E+09 | 0.295487E+10 |
February | 0.107105E+10 | 0.526473E+09 | 0.544572E+09 | 0.774699E+09 | 0.204302E+10 |
March | 0.151754E+10 | 0.556048E+09 | 0.961488E+09 | 0.114496E+10 | 0.195567E+10 |
April | 0.191724E+10 | 0.849427E+09 | 0.106782E+10 | 0.180450E+10 | 0.142747E+10 |
May | 0.245054E+10 | 0.111758E+10 | 0.133296E+10 | 0.259972E+10 | 0.107791E+10 |
June | 0.258009E+10 | 0.118513E+10 | 0.139496E+10 | 0.306922E+10 | 0.719033E+09 |
July | 0.273112E+10 | 0.138007E+10 | 0.135104E+10 | 0.352623E+10 | 0.633214E+09 |
August | 0.231909E+10 | 0.113816E+10 | 0.118093E+10 | 0.289481E+10 | 0.709789E+09 |
September | 0.180538E+10 | 0.912728E+09 | 0.892654E+09 | 0.207702E+10 | 0.926944E+09 |
October | 0.133336E+10 | 0.662477E+09 | 0.670887E+09 | 0.124713E+10 | 0.144824E+10 |
November | 0.913446E+09 | 0.453147E+09 | 0.460299E+09 | 0.667139E+09 | 0.196656E+10 |
December | 0.634470E+09 | 0.267792E+09 | 0.366678E+09 | 0.301007E+09 | 0.275708E+10 |
Annual Sum or Average | 0.199681E+11 | 0.932902E+10 | 0.106390E+11 | 0.204423E+11 | 0.186198E+11 |
Minimum of Months | 0.634470E+09 | 0.267792E+09 | 0.366678E+09 | 0.301007E+09 | 0.633214E+09 |
Maximum of Months | 0.273112E+10 | 0.138007E+10 | 0.139496E+10 | 0.352623E+10 | 0.295487E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150310E+10 | 0.00 | 0.150310E+10 | 53174033.44 | 0.125436E+11 |
February | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.353348E+09 | 0.837459E+10 |
March | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.123767E+10 | 0.751299E+10 |
April | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.203974E+10 | 0.518555E+10 |
May | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.387510E+10 | 0.398529E+10 |
June | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.598926E+10 | 0.248428E+10 |
July | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.672220E+10 | 0.214087E+10 |
August | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.489927E+10 | 0.244360E+10 |
September | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.277920E+10 | 0.359575E+10 |
October | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.112078E+10 | 0.549957E+10 |
November | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.266771E+09 | 0.756342E+10 |
December | 0.126043E+10 | 0.00 | 0.126043E+10 | 27923958.74 | 0.107148E+11 |
Annual Sum or Average | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.293644E+11 | 0.720443E+11 |
Minimum of Months | 0.126043E+10 | 0.00 | 0.126043E+10 | 27923958.74 | 0.214087E+10 |
Maximum of Months | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.672220E+10 | 0.125436E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.124465E+10 | 0.769987E+10 |
February | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.244609E+10 | 0.518351E+10 |
March | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.392940E+10 | 0.479484E+10 |
April | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.576275E+10 | 0.337659E+10 |
May | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.707539E+10 | 0.272255E+10 |
June | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.102175E+11 | 0.173330E+10 |
July | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.119665E+11 | 0.146470E+10 |
August | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.101471E+11 | 0.165293E+10 |
September | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.628069E+10 | 0.232961E+10 |
October | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.384903E+10 | 0.353516E+10 |
November | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.173208E+10 | 0.469317E+10 |
December | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.975296E+09 | 0.658384E+10 |
Annual Sum or Average | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.656264E+11 | 0.457701E+11 |
Minimum of Months | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.975296E+09 | 0.146470E+10 |
Maximum of Months | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.119665E+11 | 0.769987E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.989060E+10 | 0.109971E+11 |
February | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.125058E+11 | 0.754711E+10 |
March | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.123278E+11 | 0.751841E+10 |
April | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.996309E+10 | 0.545303E+10 |
May | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.932090E+10 | 0.440489E+10 |
June | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.102478E+11 | 0.291213E+10 |
July | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.127519E+11 | 0.240231E+10 |
August | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.146936E+11 | 0.272129E+10 |
September | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.146038E+11 | 0.377658E+10 |
October | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.144566E+11 | 0.553399E+10 |
November | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.116239E+11 | 0.686986E+10 |
December | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.963535E+10 | 0.938313E+10 |
Annual Sum or Average | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.142021E+12 | 0.695199E+11 |
Minimum of Months | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.932090E+10 | 0.240231E+10 |
Maximum of Months | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.146936E+11 | 0.109971E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.107172E+10 | 0.816434E+10 |
February | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.246151E+10 | 0.543578E+10 |
March | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.361599E+10 | 0.511228E+10 |
April | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.558014E+10 | 0.368972E+10 |
May | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.784915E+10 | 0.297734E+10 |
June | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.926326E+10 | 0.198319E+10 |
July | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.106661E+11 | 0.172593E+10 |
August | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.880470E+10 | 0.187003E+10 |
September | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.627050E+10 | 0.256209E+10 |
October | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.386539E+10 | 0.381312E+10 |
November | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.213431E+10 | 0.498896E+10 |
December | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.102093E+10 | 0.693812E+10 |
Annual Sum or Average | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.626037E+11 | 0.492609E+11 |
Minimum of Months | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.102093E+10 | 0.172593E+10 |
Maximum of Months | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.106661E+11 | 0.816434E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150310E+10 | 0.00 | 0.150310E+10 | 71462507.47 | 0.121776E+11 |
February | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.413862E+09 | 0.801558E+10 |
March | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.135677E+10 | 0.707933E+10 |
April | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.218198E+10 | 0.480466E+10 |
May | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.396300E+10 | 0.375796E+10 |
June | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.600940E+10 | 0.241693E+10 |
July | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.670393E+10 | 0.211066E+10 |
August | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.490484E+10 | 0.237614E+10 |
September | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.284021E+10 | 0.339208E+10 |
October | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.127187E+10 | 0.501424E+10 |
November | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.334077E+09 | 0.699247E+10 |
December | 0.126043E+10 | 0.00 | 0.126043E+10 | 34840437.50 | 0.102806E+11 |
Annual Sum or Average | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.300862E+11 | 0.684182E+11 |
Minimum of Months | 0.126043E+10 | 0.00 | 0.126043E+10 | 34840437.50 | 0.211066E+10 |
Maximum of Months | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.670393E+10 | 0.121776E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.128204E+10 | 0.749989E+10 |
February | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.252343E+10 | 0.495613E+10 |
March | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.403985E+10 | 0.451714E+10 |
April | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.585907E+10 | 0.314609E+10 |
May | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.712301E+10 | 0.258298E+10 |
June | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.102233E+11 | 0.169367E+10 |
July | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.119547E+11 | 0.144566E+10 |
August | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.101491E+11 | 0.161511E+10 |
September | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.632183E+10 | 0.221669E+10 |
October | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.396575E+10 | 0.324455E+10 |
November | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.183556E+10 | 0.432573E+10 |
December | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.101429E+10 | 0.631829E+10 |
Annual Sum or Average | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.662920E+11 | 0.435619E+11 |
Minimum of Months | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.101429E+10 | 0.144566E+10 |
Maximum of Months | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.119547E+11 | 0.749989E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.998213E+10 | 0.105943E+11 |
February | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.126085E+11 | 0.717959E+10 |
March | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.124470E+11 | 0.708949E+10 |
April | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.100613E+11 | 0.509098E+10 |
May | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.936469E+10 | 0.417654E+10 |
June | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.102354E+11 | 0.283141E+10 |
July | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.127106E+11 | 0.236363E+10 |
August | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.146688E+11 | 0.265200E+10 |
September | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.146256E+11 | 0.359577E+10 |
October | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.145771E+11 | 0.511360E+10 |
November | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.117941E+11 | 0.635840E+10 |
December | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.976205E+10 | 0.892501E+10 |
Annual Sum or Average | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.142837E+12 | 0.659708E+11 |
Minimum of Months | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.936469E+10 | 0.236363E+10 |
Maximum of Months | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.146688E+11 | 0.105943E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.109572E+10 | 0.792179E+10 |
February | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.250243E+10 | 0.521895E+10 |
March | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.368047E+10 | 0.485659E+10 |
April | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.564419E+10 | 0.347045E+10 |
May | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.787311E+10 | 0.283434E+10 |
June | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.924851E+10 | 0.193026E+10 |
July | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.106369E+11 | 0.169842E+10 |
August | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.878770E+10 | 0.182496E+10 |
September | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.628836E+10 | 0.244300E+10 |
October | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.394172E+10 | 0.354088E+10 |
November | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.219618E+10 | 0.465980E+10 |
December | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.104611E+10 | 0.667434E+10 |
Annual Sum or Average | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.629415E+11 | 0.470738E+11 |
Minimum of Months | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.104611E+10 | 0.169842E+10 |
Maximum of Months | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.106369E+11 | 0.792179E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.66 | 5008.53 | 561.19 | 0.00 | 561.19 | 0.00 | 0.00 |
February | 90.88 | 3779.80 | 792.37 | 0.00 | 792.37 | 0.00 | 0.00 |
March | 376.01 | 3098.64 | 1287.17 | 0.00 | 1287.17 | 0.00 | 0.00 |
April | 707.00 | 2230.44 | 1467.65 | 8.56 | 1459.09 | 0.00 | 0.00 |
May | 1398.53 | 1600.93 | 1927.38 | 114.21 | 1813.17 | 0.00 | 0.00 |
June | 2284.26 | 1002.24 | 2244.32 | 257.97 | 1986.36 | 0.00 | 0.00 |
July | 2479.35 | 830.52 | 2050.31 | 192.04 | 1858.27 | 0.00 | 0.00 |
August | 1794.64 | 961.08 | 1642.92 | 44.04 | 1598.89 | 0.00 | 0.00 |
September | 1038.77 | 1489.43 | 1230.44 | 0.44 | 1230.00 | 0.00 | 0.00 |
October | 355.24 | 2291.80 | 897.53 | 0.00 | 897.53 | 0.00 | 0.00 |
November | 67.94 | 3320.09 | 610.15 | 0.00 | 610.15 | 0.00 | 0.00 |
December | 2.45 | 4491.74 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Annual Sum or Average | 888.62 | 2503.78 | 1267.71 | 51.69 | 1216.02 | 0.00 | 0.00 |
Minimum of Months | 2.45 | 830.52 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Maximum of Months | 2479.35 | 5008.53 | 2244.32 | 257.97 | 1986.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 439.93 | 3058.88 | 859.09 | 393.86 | 465.23 | 0.00 | 0.00 |
February | 978.87 | 2293.71 | 1343.70 | 667.12 | 676.59 | 0.00 | 0.00 |
March | 1442.58 | 1913.53 | 1806.73 | 747.57 | 1059.15 | 0.00 | 0.00 |
April | 2216.75 | 1387.35 | 2305.21 | 1142.44 | 1162.76 | 0.00 | 0.00 |
May | 2648.18 | 1070.69 | 2546.40 | 1132.99 | 1413.41 | 0.00 | 0.00 |
June | 3968.22 | 681.03 | 3295.99 | 1696.11 | 1599.87 | 0.00 | 0.00 |
July | 4494.89 | 547.33 | 3459.23 | 1955.60 | 1503.63 | 0.00 | 0.00 |
August | 3813.59 | 617.56 | 3006.22 | 1674.98 | 1331.25 | 0.00 | 0.00 |
September | 2435.34 | 934.35 | 2126.61 | 1097.75 | 1028.86 | 0.00 | 0.00 |
October | 1424.54 | 1413.86 | 1525.73 | 774.74 | 750.99 | 0.00 | 0.00 |
November | 638.75 | 1984.80 | 966.98 | 451.45 | 515.53 | 0.00 | 0.00 |
December | 333.24 | 2698.38 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Annual Sum or Average | 2075.85 | 1547.33 | 1999.68 | 1005.15 | 994.53 | 0.00 | 0.00 |
Minimum of Months | 333.24 | 547.33 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Maximum of Months | 4494.89 | 3058.88 | 3459.23 | 1955.60 | 1599.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3697.59 | 4211.86 | 3955.80 | 2825.31 | 1130.49 | 0.00 | 0.00 |
February | 5188.64 | 3220.36 | 5037.65 | 3623.26 | 1414.38 | 0.00 | 0.00 |
March | 4617.00 | 2911.14 | 4503.00 | 2528.68 | 1974.32 | 0.00 | 0.00 |
April | 3848.18 | 2206.22 | 3619.66 | 1731.31 | 1888.35 | 0.00 | 0.00 |
May | 3492.04 | 1702.08 | 3215.97 | 1068.11 | 2147.86 | 0.00 | 0.00 |
June | 3967.03 | 1154.93 | 3195.39 | 931.93 | 2263.46 | 0.00 | 0.00 |
July | 4769.25 | 917.72 | 3444.95 | 1272.56 | 2172.40 | 0.00 | 0.00 |
August | 5502.36 | 1040.83 | 4094.10 | 2064.17 | 2029.93 | 0.00 | 0.00 |
September | 5676.67 | 1486.80 | 4540.85 | 2782.33 | 1758.52 | 0.00 | 0.00 |
October | 5427.88 | 2130.41 | 4747.22 | 3282.64 | 1464.58 | 0.00 | 0.00 |
November | 4485.47 | 2765.66 | 4328.06 | 3135.07 | 1192.99 | 0.00 | 0.00 |
December | 3572.21 | 3695.25 | 3761.74 | 2716.36 | 1045.38 | 0.00 | 0.00 |
Annual Sum or Average | 4515.15 | 2283.47 | 4030.08 | 2321.54 | 1708.54 | 0.00 | 0.00 |
Minimum of Months | 3492.04 | 917.72 | 3195.39 | 931.93 | 1045.38 | 0.00 | 0.00 |
Maximum of Months | 5676.67 | 4211.86 | 5037.65 | 3623.26 | 2263.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 376.23 | 3309.70 | 778.16 | 313.60 | 464.55 | 0.00 | 0.00 |
February | 960.70 | 2533.53 | 1328.20 | 652.88 | 675.32 | 0.00 | 0.00 |
March | 1282.45 | 2190.52 | 1699.77 | 622.82 | 1076.95 | 0.00 | 0.00 |
April | 2088.57 | 1652.19 | 2219.06 | 983.15 | 1235.91 | 0.00 | 0.00 |
May | 2911.91 | 1207.35 | 2744.82 | 1251.78 | 1493.03 | 0.00 | 0.00 |
June | 3552.38 | 832.22 | 2986.25 | 1371.70 | 1614.56 | 0.00 | 0.00 |
July | 3949.68 | 709.25 | 3059.09 | 1545.80 | 1513.28 | 0.00 | 0.00 |
August | 3242.43 | 795.02 | 2597.58 | 1274.84 | 1322.74 | 0.00 | 0.00 |
September | 2403.98 | 1072.87 | 2089.59 | 1056.41 | 1033.18 | 0.00 | 0.00 |
October | 1396.89 | 1622.15 | 1493.48 | 742.03 | 751.45 | 0.00 | 0.00 |
November | 772.16 | 2276.14 | 1057.24 | 524.48 | 532.76 | 0.00 | 0.00 |
December | 337.15 | 3088.17 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Annual Sum or Average | 1944.69 | 1771.31 | 1899.57 | 887.47 | 1012.10 | 0.00 | 0.00 |
Minimum of Months | 337.15 | 709.25 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Maximum of Months | 3949.68 | 3309.70 | 3059.09 | 1545.80 | 1614.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.85 | 4683.24 | 561.19 | 0.00 | 561.19 | 0.00 | 0.00 |
February | 146.06 | 3461.72 | 792.37 | 0.00 | 792.37 | 0.00 | 0.00 |
March | 462.09 | 2805.03 | 1287.17 | 0.00 | 1287.17 | 0.00 | 0.00 |
April | 786.94 | 2000.60 | 1467.64 | 8.56 | 1459.08 | 0.00 | 0.00 |
May | 1446.80 | 1487.94 | 1927.37 | 114.21 | 1813.16 | 0.00 | 0.00 |
June | 2310.67 | 958.44 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
July | 2509.78 | 799.31 | 2050.30 | 192.04 | 1858.27 | 0.00 | 0.00 |
August | 1829.18 | 912.34 | 1642.92 | 44.04 | 1598.88 | 0.00 | 0.00 |
September | 1072.22 | 1387.25 | 1230.43 | 0.44 | 1229.99 | 0.00 | 0.00 |
October | 418.45 | 2053.30 | 897.53 | 0.00 | 897.53 | 0.00 | 0.00 |
November | 102.92 | 2917.99 | 610.15 | 0.00 | 610.15 | 0.00 | 0.00 |
December | 10.43 | 4000.44 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Annual Sum or Average | 931.14 | 2284.51 | 1267.70 | 51.69 | 1216.01 | 0.00 | 0.00 |
Minimum of Months | 10.43 | 799.31 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Maximum of Months | 2509.78 | 4683.24 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 464.70 | 2874.80 | 859.09 | 393.86 | 465.23 | 0.00 | 0.00 |
February | 1011.12 | 2142.66 | 1343.70 | 667.11 | 676.58 | 0.00 | 0.00 |
March | 1467.07 | 1790.19 | 1806.72 | 747.57 | 1059.15 | 0.00 | 0.00 |
April | 2223.28 | 1302.70 | 2305.20 | 1142.44 | 1162.76 | 0.00 | 0.00 |
May | 2641.65 | 1016.48 | 2546.39 | 1132.98 | 1413.41 | 0.00 | 0.00 |
June | 3941.92 | 668.71 | 3295.97 | 1696.11 | 1599.87 | 0.00 | 0.00 |
July | 4467.79 | 546.86 | 3459.22 | 1955.59 | 1503.63 | 0.00 | 0.00 |
August | 3788.48 | 617.13 | 3006.21 | 1674.97 | 1331.24 | 0.00 | 0.00 |
September | 2423.10 | 898.77 | 2126.60 | 1097.74 | 1028.86 | 0.00 | 0.00 |
October | 1437.06 | 1319.88 | 1525.72 | 774.74 | 750.99 | 0.00 | 0.00 |
November | 668.24 | 1810.64 | 966.97 | 451.45 | 515.52 | 0.00 | 0.00 |
December | 364.13 | 2458.12 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Annual Sum or Average | 2081.00 | 1451.36 | 1999.67 | 1005.15 | 994.52 | 0.00 | 0.00 |
Minimum of Months | 364.13 | 546.86 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Maximum of Months | 4467.79 | 2874.80 | 3459.22 | 1955.59 | 1599.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3692.73 | 4105.86 | 3955.78 | 2825.30 | 1130.48 | 0.00 | 0.00 |
February | 5169.38 | 3119.67 | 5037.63 | 3623.25 | 1414.38 | 0.00 | 0.00 |
March | 4602.68 | 2807.05 | 4502.98 | 2528.67 | 1974.31 | 0.00 | 0.00 |
April | 3843.78 | 2103.79 | 3619.64 | 1731.30 | 1888.35 | 0.00 | 0.00 |
May | 3480.03 | 1644.60 | 3215.96 | 1068.11 | 2147.85 | 0.00 | 0.00 |
June | 3953.64 | 1123.51 | 3195.38 | 931.93 | 2263.46 | 0.00 | 0.00 |
July | 4761.03 | 896.92 | 3444.94 | 1272.55 | 2172.39 | 0.00 | 0.00 |
August | 5485.96 | 1016.01 | 4094.09 | 2064.17 | 2029.92 | 0.00 | 0.00 |
September | 5634.19 | 1457.01 | 4540.83 | 2782.32 | 1758.52 | 0.00 | 0.00 |
October | 5397.48 | 2066.15 | 4747.20 | 3282.63 | 1464.57 | 0.00 | 0.00 |
November | 4484.53 | 2650.41 | 4328.04 | 3135.06 | 1192.98 | 0.00 | 0.00 |
December | 3597.43 | 3503.26 | 3761.73 | 2716.35 | 1045.38 | 0.00 | 0.00 |
Annual Sum or Average | 4503.46 | 2204.46 | 4030.07 | 2321.53 | 1708.53 | 0.00 | 0.00 |
Minimum of Months | 3480.03 | 896.92 | 3195.38 | 931.93 | 1045.38 | 0.00 | 0.00 |
Maximum of Months | 5634.19 | 4105.86 | 5037.63 | 3623.25 | 2263.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 400.14 | 3048.22 | 778.15 | 313.60 | 464.55 | 0.00 | 0.00 |
February | 1017.49 | 2246.93 | 1328.19 | 652.87 | 675.32 | 0.00 | 0.00 |
March | 1350.06 | 1908.71 | 1699.76 | 622.82 | 1076.94 | 0.00 | 0.00 |
April | 2152.83 | 1423.50 | 2219.05 | 983.14 | 1235.91 | 0.00 | 0.00 |
May | 2930.54 | 1111.61 | 2744.81 | 1251.78 | 1493.03 | 0.00 | 0.00 |
June | 3573.79 | 765.12 | 2986.24 | 1371.69 | 1614.55 | 0.00 | 0.00 |
July | 3982.27 | 644.39 | 3059.07 | 1545.79 | 1513.28 | 0.00 | 0.00 |
August | 3287.30 | 698.19 | 2597.57 | 1274.83 | 1322.74 | 0.00 | 0.00 |
September | 2419.17 | 988.46 | 2089.58 | 1056.41 | 1033.17 | 0.00 | 0.00 |
October | 1443.17 | 1423.66 | 1493.48 | 742.03 | 751.45 | 0.00 | 0.00 |
November | 823.42 | 1924.75 | 1057.24 | 524.48 | 532.76 | 0.00 | 0.00 |
December | 381.17 | 2590.40 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Annual Sum or Average | 1985.15 | 1562.05 | 1899.56 | 887.47 | 1012.09 | 0.00 | 0.00 |
Minimum of Months | 381.17 | 644.39 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Maximum of Months | 3982.27 | 3048.22 | 3059.07 | 1545.79 | 1614.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.68 | 4546.60 | 561.19 | 0.00 | 561.19 | 0.00 | 0.00 |
February | 171.07 | 3313.32 | 792.37 | 0.00 | 792.37 | 0.00 | 0.00 |
March | 506.56 | 2643.12 | 1287.17 | 0.00 | 1287.17 | 0.00 | 0.00 |
April | 841.81 | 1853.65 | 1467.64 | 8.56 | 1459.08 | 0.00 | 0.00 |
May | 1479.62 | 1403.06 | 1927.37 | 114.21 | 1813.16 | 0.00 | 0.00 |
June | 2318.44 | 932.46 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
July | 2502.96 | 788.03 | 2050.30 | 192.04 | 1858.27 | 0.00 | 0.00 |
August | 1831.26 | 887.15 | 1642.92 | 44.04 | 1598.88 | 0.00 | 0.00 |
September | 1095.76 | 1308.67 | 1230.43 | 0.44 | 1229.99 | 0.00 | 0.00 |
October | 474.86 | 1872.10 | 897.53 | 0.00 | 897.53 | 0.00 | 0.00 |
November | 128.89 | 2697.71 | 610.15 | 0.00 | 610.15 | 0.00 | 0.00 |
December | 13.01 | 3838.32 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Annual Sum or Average | 954.03 | 2169.53 | 1267.70 | 51.69 | 1216.01 | 0.00 | 0.00 |
Minimum of Months | 13.01 | 788.03 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Maximum of Months | 2502.96 | 4546.60 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 478.66 | 2800.14 | 859.09 | 393.86 | 465.23 | 0.00 | 0.00 |
February | 1043.08 | 2048.66 | 1343.70 | 667.11 | 676.58 | 0.00 | 0.00 |
March | 1508.31 | 1686.51 | 1806.72 | 747.57 | 1059.15 | 0.00 | 0.00 |
April | 2260.44 | 1213.77 | 2305.20 | 1142.44 | 1162.76 | 0.00 | 0.00 |
May | 2659.43 | 964.38 | 2546.39 | 1132.98 | 1413.41 | 0.00 | 0.00 |
June | 3944.17 | 653.42 | 3295.97 | 1696.11 | 1599.87 | 0.00 | 0.00 |
July | 4463.38 | 539.75 | 3459.22 | 1955.59 | 1503.63 | 0.00 | 0.00 |
August | 3789.25 | 603.01 | 3006.21 | 1674.97 | 1331.24 | 0.00 | 0.00 |
September | 2438.98 | 855.21 | 2126.60 | 1097.74 | 1028.86 | 0.00 | 0.00 |
October | 1480.64 | 1211.38 | 1525.72 | 774.74 | 750.99 | 0.00 | 0.00 |
November | 708.16 | 1668.88 | 966.97 | 451.45 | 515.52 | 0.00 | 0.00 |
December | 378.69 | 2358.98 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Annual Sum or Average | 2102.10 | 1381.34 | 1999.67 | 1005.15 | 994.52 | 0.00 | 0.00 |
Minimum of Months | 378.69 | 539.75 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Maximum of Months | 4463.38 | 2800.14 | 3459.22 | 1955.59 | 1599.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3726.90 | 3955.47 | 3955.78 | 2825.30 | 1130.48 | 0.00 | 0.00 |
February | 5211.84 | 2967.75 | 5037.63 | 3623.25 | 1414.38 | 0.00 | 0.00 |
March | 4647.18 | 2646.91 | 4502.98 | 2528.67 | 1974.31 | 0.00 | 0.00 |
April | 3881.69 | 1964.11 | 3619.64 | 1731.30 | 1888.35 | 0.00 | 0.00 |
May | 3496.38 | 1559.34 | 3215.96 | 1068.11 | 2147.85 | 0.00 | 0.00 |
June | 3948.85 | 1092.37 | 3195.38 | 931.93 | 2263.46 | 0.00 | 0.00 |
July | 4745.58 | 882.48 | 3444.94 | 1272.55 | 2172.39 | 0.00 | 0.00 |
August | 5476.72 | 990.14 | 4094.09 | 2064.17 | 2029.92 | 0.00 | 0.00 |
September | 5642.60 | 1387.26 | 4540.83 | 2782.32 | 1758.52 | 0.00 | 0.00 |
October | 5442.47 | 1909.20 | 4747.20 | 3282.63 | 1464.57 | 0.00 | 0.00 |
November | 4550.20 | 2453.09 | 4328.04 | 3135.06 | 1192.98 | 0.00 | 0.00 |
December | 3644.73 | 3332.22 | 3761.73 | 2716.35 | 1045.38 | 0.00 | 0.00 |
Annual Sum or Average | 4529.34 | 2091.92 | 4030.07 | 2321.53 | 1708.53 | 0.00 | 0.00 |
Minimum of Months | 3496.38 | 882.48 | 3195.38 | 931.93 | 1045.38 | 0.00 | 0.00 |
Maximum of Months | 5642.60 | 3955.47 | 5037.63 | 3623.25 | 2263.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 409.10 | 2957.66 | 778.15 | 313.60 | 464.55 | 0.00 | 0.00 |
February | 1034.41 | 2157.31 | 1328.19 | 652.87 | 675.32 | 0.00 | 0.00 |
March | 1374.13 | 1813.24 | 1699.76 | 622.82 | 1076.94 | 0.00 | 0.00 |
April | 2177.54 | 1338.91 | 2219.05 | 983.14 | 1235.91 | 0.00 | 0.00 |
May | 2939.48 | 1058.22 | 2744.81 | 1251.78 | 1493.03 | 0.00 | 0.00 |
June | 3568.10 | 744.70 | 2986.24 | 1371.69 | 1614.55 | 0.00 | 0.00 |
July | 3971.38 | 634.12 | 3059.07 | 1545.79 | 1513.28 | 0.00 | 0.00 |
August | 3280.95 | 681.36 | 2597.57 | 1274.83 | 1322.74 | 0.00 | 0.00 |
September | 2426.07 | 942.51 | 2089.58 | 1056.41 | 1033.17 | 0.00 | 0.00 |
October | 1471.67 | 1322.01 | 1493.48 | 742.03 | 751.45 | 0.00 | 0.00 |
November | 847.29 | 1797.76 | 1057.24 | 524.48 | 532.76 | 0.00 | 0.00 |
December | 390.57 | 2491.91 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Annual Sum or Average | 1995.86 | 1492.70 | 1899.56 | 887.47 | 1012.09 | 0.00 | 0.00 |
Minimum of Months | 390.57 | 634.12 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Maximum of Months | 3971.38 | 2957.66 | 3059.07 | 1545.79 | 1614.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 23193503.73 | 0.134148E+11 | 0.150310E+10 | 0.00 | 0.150310E+10 | 0.00 | 0.00 |
February | 0.219857E+09 | 0.914408E+10 | 0.191691E+10 | 0.00 | 0.191691E+10 | 0.00 | 0.00 |
March | 0.100710E+10 | 0.829941E+10 | 0.344757E+10 | 0.00 | 0.344757E+10 | 0.00 | 0.00 |
April | 0.183254E+10 | 0.578131E+10 | 0.380415E+10 | 22200158.45 | 0.378195E+10 | 0.00 | 0.00 |
May | 0.374583E+10 | 0.428794E+10 | 0.516228E+10 | 0.305897E+09 | 0.485639E+10 | 0.00 | 0.00 |
June | 0.592081E+10 | 0.259781E+10 | 0.581728E+10 | 0.668647E+09 | 0.514864E+10 | 0.00 | 0.00 |
July | 0.664069E+10 | 0.222445E+10 | 0.549155E+10 | 0.514350E+09 | 0.497720E+10 | 0.00 | 0.00 |
August | 0.480676E+10 | 0.257416E+10 | 0.440041E+10 | 0.117951E+09 | 0.428246E+10 | 0.00 | 0.00 |
September | 0.269249E+10 | 0.386061E+10 | 0.318929E+10 | 1144490.71 | 0.318815E+10 | 0.00 | 0.00 |
October | 0.951475E+09 | 0.613836E+10 | 0.240395E+10 | 0.00 | 0.240395E+10 | 0.00 | 0.00 |
November | 0.176113E+09 | 0.860568E+10 | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.00 | 0.00 |
December | 6553357.81 | 0.120307E+11 | 0.126044E+10 | 0.00 | 0.126044E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.280234E+11 | 0.789593E+11 | 0.399784E+11 | 0.163019E+10 | 0.383483E+11 | 0.00 | 0.00 |
Minimum of Months | 6553357.81 | 0.222445E+10 | 0.126044E+10 | 0.00 | 0.126044E+10 | 0.00 | 0.00 |
Maximum of Months | 0.664069E+10 | 0.134148E+11 | 0.581728E+10 | 0.668647E+09 | 0.514864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117832E+10 | 0.819289E+10 | 0.230100E+10 | 0.105492E+10 | 0.124608E+10 | 0.00 | 0.00 |
February | 0.236809E+10 | 0.554894E+10 | 0.325068E+10 | 0.161389E+10 | 0.163679E+10 | 0.00 | 0.00 |
March | 0.386380E+10 | 0.512519E+10 | 0.483914E+10 | 0.200230E+10 | 0.283684E+10 | 0.00 | 0.00 |
April | 0.574581E+10 | 0.359601E+10 | 0.597510E+10 | 0.296121E+10 | 0.301388E+10 | 0.00 | 0.00 |
May | 0.709288E+10 | 0.286774E+10 | 0.682028E+10 | 0.303460E+10 | 0.378568E+10 | 0.00 | 0.00 |
June | 0.102856E+11 | 0.176522E+10 | 0.854320E+10 | 0.439632E+10 | 0.414687E+10 | 0.00 | 0.00 |
July | 0.120391E+11 | 0.146596E+10 | 0.926520E+10 | 0.523787E+10 | 0.402734E+10 | 0.00 | 0.00 |
August | 0.102143E+11 | 0.165408E+10 | 0.805187E+10 | 0.448625E+10 | 0.356562E+10 | 0.00 | 0.00 |
September | 0.631241E+10 | 0.242182E+10 | 0.551217E+10 | 0.284536E+10 | 0.266681E+10 | 0.00 | 0.00 |
October | 0.381550E+10 | 0.378687E+10 | 0.408652E+10 | 0.207507E+10 | 0.201145E+10 | 0.00 | 0.00 |
November | 0.165563E+10 | 0.514460E+10 | 0.250641E+10 | 0.117016E+10 | 0.133625E+10 | 0.00 | 0.00 |
December | 0.892539E+09 | 0.722733E+10 | 0.191024E+10 | 0.820453E+09 | 0.108979E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.654640E+11 | 0.487967E+11 | 0.630618E+11 | 0.316984E+11 | 0.313634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.892539E+09 | 0.146596E+10 | 0.191024E+10 | 0.820453E+09 | 0.108979E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120391E+11 | 0.819289E+10 | 0.926520E+10 | 0.523787E+10 | 0.414687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.990364E+10 | 0.112811E+11 | 0.105952E+11 | 0.756731E+10 | 0.302790E+10 | 0.00 | 0.00 |
February | 0.125524E+11 | 0.779071E+10 | 0.121871E+11 | 0.876540E+10 | 0.342168E+10 | 0.00 | 0.00 |
March | 0.123662E+11 | 0.779721E+10 | 0.120608E+11 | 0.677281E+10 | 0.528802E+10 | 0.00 | 0.00 |
April | 0.997448E+10 | 0.571853E+10 | 0.938215E+10 | 0.448754E+10 | 0.489461E+10 | 0.00 | 0.00 |
May | 0.935308E+10 | 0.455885E+10 | 0.861366E+10 | 0.286083E+10 | 0.575283E+10 | 0.00 | 0.00 |
June | 0.102825E+11 | 0.299358E+10 | 0.828246E+10 | 0.241556E+10 | 0.586690E+10 | 0.00 | 0.00 |
July | 0.127739E+11 | 0.245801E+10 | 0.922697E+10 | 0.340841E+10 | 0.581855E+10 | 0.00 | 0.00 |
August | 0.147375E+11 | 0.278775E+10 | 0.109656E+11 | 0.552868E+10 | 0.543696E+10 | 0.00 | 0.00 |
September | 0.147139E+11 | 0.385380E+10 | 0.117699E+11 | 0.721179E+10 | 0.455810E+10 | 0.00 | 0.00 |
October | 0.145380E+11 | 0.570609E+10 | 0.127149E+11 | 0.879222E+10 | 0.392272E+10 | 0.00 | 0.00 |
November | 0.116263E+11 | 0.716858E+10 | 0.112183E+11 | 0.812610E+10 | 0.309222E+10 | 0.00 | 0.00 |
December | 0.956782E+10 | 0.989737E+10 | 0.100754E+11 | 0.727549E+10 | 0.279996E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142390E+12 | 0.720115E+11 | 0.127093E+12 | 0.732122E+11 | 0.538805E+11 | 0.00 | 0.00 |
Minimum of Months | 0.935308E+10 | 0.245801E+10 | 0.828246E+10 | 0.241556E+10 | 0.279996E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147375E+11 | 0.112811E+11 | 0.127149E+11 | 0.879222E+10 | 0.586690E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100768E+10 | 0.886471E+10 | 0.208422E+10 | 0.839955E+09 | 0.124426E+10 | 0.00 | 0.00 |
February | 0.232412E+10 | 0.612912E+10 | 0.321318E+10 | 0.157944E+10 | 0.163374E+10 | 0.00 | 0.00 |
March | 0.343492E+10 | 0.586708E+10 | 0.455266E+10 | 0.166816E+10 | 0.288450E+10 | 0.00 | 0.00 |
April | 0.541358E+10 | 0.428247E+10 | 0.575180E+10 | 0.254831E+10 | 0.320349E+10 | 0.00 | 0.00 |
May | 0.779926E+10 | 0.323376E+10 | 0.735172E+10 | 0.335278E+10 | 0.399894E+10 | 0.00 | 0.00 |
June | 0.920776E+10 | 0.215713E+10 | 0.774037E+10 | 0.355544E+10 | 0.418493E+10 | 0.00 | 0.00 |
July | 0.105788E+11 | 0.189966E+10 | 0.819346E+10 | 0.414027E+10 | 0.405318E+10 | 0.00 | 0.00 |
August | 0.868452E+10 | 0.212939E+10 | 0.695735E+10 | 0.341452E+10 | 0.354283E+10 | 0.00 | 0.00 |
September | 0.623113E+10 | 0.278087E+10 | 0.541621E+10 | 0.273822E+10 | 0.267799E+10 | 0.00 | 0.00 |
October | 0.374144E+10 | 0.434477E+10 | 0.400014E+10 | 0.198745E+10 | 0.201269E+10 | 0.00 | 0.00 |
November | 0.200144E+10 | 0.589975E+10 | 0.274037E+10 | 0.135946E+10 | 0.138091E+10 | 0.00 | 0.00 |
December | 0.903032E+09 | 0.827135E+10 | 0.190343E+10 | 0.803385E+09 | 0.110005E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.613277E+11 | 0.558601E+11 | 0.599049E+11 | 0.279874E+11 | 0.319175E+11 | 0.00 | 0.00 |
Minimum of Months | 0.903032E+09 | 0.189966E+10 | 0.190343E+10 | 0.803385E+09 | 0.110005E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105788E+11 | 0.886471E+10 | 0.819346E+10 | 0.414027E+10 | 0.418493E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 53174033.44 | 0.125436E+11 | 0.150310E+10 | 0.00 | 0.150310E+10 | 0.00 | 0.00 |
February | 0.353348E+09 | 0.837459E+10 | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.00 | 0.00 |
March | 0.123767E+10 | 0.751299E+10 | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.00 | 0.00 |
April | 0.203974E+10 | 0.518555E+10 | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.00 | 0.00 |
May | 0.387510E+10 | 0.398529E+10 | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.00 | 0.00 |
June | 0.598926E+10 | 0.248428E+10 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
July | 0.672220E+10 | 0.214087E+10 | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.00 | 0.00 |
August | 0.489927E+10 | 0.244360E+10 | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.00 | 0.00 |
September | 0.277920E+10 | 0.359575E+10 | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.00 | 0.00 |
October | 0.112078E+10 | 0.549957E+10 | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.00 | 0.00 |
November | 0.266771E+09 | 0.756342E+10 | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.00 | 0.00 |
December | 27923958.74 | 0.107148E+11 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.293644E+11 | 0.720443E+11 | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.00 | 0.00 |
Minimum of Months | 27923958.74 | 0.214087E+10 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Maximum of Months | 0.672220E+10 | 0.125436E+11 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124465E+10 | 0.769987E+10 | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.00 | 0.00 |
February | 0.244609E+10 | 0.518351E+10 | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.00 | 0.00 |
March | 0.392940E+10 | 0.479484E+10 | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.00 | 0.00 |
April | 0.576275E+10 | 0.337659E+10 | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.00 | 0.00 |
May | 0.707539E+10 | 0.272255E+10 | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.00 | 0.00 |
June | 0.102175E+11 | 0.173330E+10 | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.00 | 0.00 |
July | 0.119665E+11 | 0.146470E+10 | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.00 | 0.00 |
August | 0.101471E+11 | 0.165293E+10 | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.00 | 0.00 |
September | 0.628069E+10 | 0.232961E+10 | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.00 | 0.00 |
October | 0.384903E+10 | 0.353516E+10 | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.00 | 0.00 |
November | 0.173208E+10 | 0.469317E+10 | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.00 | 0.00 |
December | 0.975296E+09 | 0.658384E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.656264E+11 | 0.457701E+11 | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.00 | 0.00 |
Minimum of Months | 0.975296E+09 | 0.146470E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119665E+11 | 0.769987E+10 | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.989060E+10 | 0.109971E+11 | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.00 | 0.00 |
February | 0.125058E+11 | 0.754711E+10 | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.00 | 0.00 |
March | 0.123278E+11 | 0.751841E+10 | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.00 | 0.00 |
April | 0.996309E+10 | 0.545303E+10 | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.00 | 0.00 |
May | 0.932090E+10 | 0.440489E+10 | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.00 | 0.00 |
June | 0.102478E+11 | 0.291213E+10 | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.00 | 0.00 |
July | 0.127519E+11 | 0.240231E+10 | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.00 | 0.00 |
August | 0.146936E+11 | 0.272129E+10 | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.00 | 0.00 |
September | 0.146038E+11 | 0.377658E+10 | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.00 | 0.00 |
October | 0.144566E+11 | 0.553399E+10 | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.00 | 0.00 |
November | 0.116239E+11 | 0.686986E+10 | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.00 | 0.00 |
December | 0.963535E+10 | 0.938313E+10 | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142021E+12 | 0.695199E+11 | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.932090E+10 | 0.240231E+10 | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.146936E+11 | 0.109971E+11 | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107172E+10 | 0.816434E+10 | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.00 | 0.00 |
February | 0.246151E+10 | 0.543578E+10 | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.00 | 0.00 |
March | 0.361599E+10 | 0.511228E+10 | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.00 | 0.00 |
April | 0.558014E+10 | 0.368972E+10 | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.00 | 0.00 |
May | 0.784915E+10 | 0.297734E+10 | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.00 | 0.00 |
June | 0.926326E+10 | 0.198319E+10 | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.00 | 0.00 |
July | 0.106661E+11 | 0.172593E+10 | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.00 | 0.00 |
August | 0.880470E+10 | 0.187003E+10 | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.00 | 0.00 |
September | 0.627050E+10 | 0.256209E+10 | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.00 | 0.00 |
October | 0.386539E+10 | 0.381312E+10 | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.00 | 0.00 |
November | 0.213431E+10 | 0.498896E+10 | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.00 | 0.00 |
December | 0.102093E+10 | 0.693812E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.626037E+11 | 0.492609E+11 | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.00 | 0.00 |
Minimum of Months | 0.102093E+10 | 0.172593E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106661E+11 | 0.816434E+10 | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71462507.47 | 0.121776E+11 | 0.150310E+10 | 0.00 | 0.150310E+10 | 0.00 | 0.00 |
February | 0.413862E+09 | 0.801558E+10 | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.00 | 0.00 |
March | 0.135677E+10 | 0.707933E+10 | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.00 | 0.00 |
April | 0.218198E+10 | 0.480466E+10 | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.00 | 0.00 |
May | 0.396300E+10 | 0.375796E+10 | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.00 | 0.00 |
June | 0.600940E+10 | 0.241693E+10 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
July | 0.670393E+10 | 0.211066E+10 | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.00 | 0.00 |
August | 0.490484E+10 | 0.237614E+10 | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.00 | 0.00 |
September | 0.284021E+10 | 0.339208E+10 | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.00 | 0.00 |
October | 0.127187E+10 | 0.501424E+10 | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.00 | 0.00 |
November | 0.334077E+09 | 0.699247E+10 | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.00 | 0.00 |
December | 34840437.50 | 0.102806E+11 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.300862E+11 | 0.684182E+11 | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.00 | 0.00 |
Minimum of Months | 34840437.50 | 0.211066E+10 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Maximum of Months | 0.670393E+10 | 0.121776E+11 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128204E+10 | 0.749989E+10 | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.00 | 0.00 |
February | 0.252343E+10 | 0.495613E+10 | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.00 | 0.00 |
March | 0.403985E+10 | 0.451714E+10 | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.00 | 0.00 |
April | 0.585907E+10 | 0.314609E+10 | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.00 | 0.00 |
May | 0.712301E+10 | 0.258298E+10 | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.00 | 0.00 |
June | 0.102233E+11 | 0.169367E+10 | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.00 | 0.00 |
July | 0.119547E+11 | 0.144566E+10 | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.00 | 0.00 |
August | 0.101491E+11 | 0.161511E+10 | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.00 | 0.00 |
September | 0.632183E+10 | 0.221669E+10 | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.00 | 0.00 |
October | 0.396575E+10 | 0.324455E+10 | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.00 | 0.00 |
November | 0.183556E+10 | 0.432573E+10 | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.00 | 0.00 |
December | 0.101429E+10 | 0.631829E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662920E+11 | 0.435619E+11 | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.00 | 0.00 |
Minimum of Months | 0.101429E+10 | 0.144566E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119547E+11 | 0.749989E+10 | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.998213E+10 | 0.105943E+11 | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.00 | 0.00 |
February | 0.126085E+11 | 0.717959E+10 | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.00 | 0.00 |
March | 0.124470E+11 | 0.708949E+10 | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.00 | 0.00 |
April | 0.100613E+11 | 0.509098E+10 | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.00 | 0.00 |
May | 0.936469E+10 | 0.417654E+10 | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.00 | 0.00 |
June | 0.102354E+11 | 0.283141E+10 | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.00 | 0.00 |
July | 0.127106E+11 | 0.236363E+10 | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.00 | 0.00 |
August | 0.146688E+11 | 0.265200E+10 | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.00 | 0.00 |
September | 0.146256E+11 | 0.359577E+10 | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.00 | 0.00 |
October | 0.145771E+11 | 0.511360E+10 | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.00 | 0.00 |
November | 0.117941E+11 | 0.635840E+10 | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.00 | 0.00 |
December | 0.976205E+10 | 0.892501E+10 | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142837E+12 | 0.659708E+11 | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.936469E+10 | 0.236363E+10 | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.146688E+11 | 0.105943E+11 | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109572E+10 | 0.792179E+10 | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.00 | 0.00 |
February | 0.250243E+10 | 0.521895E+10 | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.00 | 0.00 |
March | 0.368047E+10 | 0.485659E+10 | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.00 | 0.00 |
April | 0.564419E+10 | 0.347045E+10 | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.00 | 0.00 |
May | 0.787311E+10 | 0.283434E+10 | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.00 | 0.00 |
June | 0.924851E+10 | 0.193026E+10 | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.00 | 0.00 |
July | 0.106369E+11 | 0.169842E+10 | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.00 | 0.00 |
August | 0.878770E+10 | 0.182496E+10 | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.00 | 0.00 |
September | 0.628836E+10 | 0.244300E+10 | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.00 | 0.00 |
October | 0.394172E+10 | 0.354088E+10 | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.00 | 0.00 |
November | 0.219618E+10 | 0.465980E+10 | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.00 | 0.00 |
December | 0.104611E+10 | 0.667434E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.629415E+11 | 0.470738E+11 | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.00 | 0.00 |
Minimum of Months | 0.104611E+10 | 0.169842E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106369E+11 | 0.792179E+10 | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.436971E+11 | -0.426374E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.105967E+10 | 58.98 | 0.00 | 0.00 |
February | 0.403698E+11 | -0.394251E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -944653538.4 | 58.97 | 0.00 | 0.00 |
March | 0.469327E+11 | -0.458978E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103493E+10 | 58.98 | 0.00 | 0.00 |
April | 0.410876E+11 | -0.400940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993596876.9 | 58.98 | 0.00 | 0.00 |
May | 0.414914E+11 | -0.404648E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102659E+10 | 58.98 | 0.00 | 0.00 |
June | 0.386217E+11 | -0.376289E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992780621.5 | 58.99 | 0.00 | 0.00 |
July | 0.349788E+11 | -0.339603E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101849E+10 | 58.97 | 0.00 | 0.00 |
August | 0.373659E+11 | -0.363428E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102317E+10 | 58.98 | 0.00 | 0.00 |
September | 0.344096E+11 | -0.334206E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989037581.9 | 58.97 | 0.00 | 0.00 |
October | 0.371118E+11 | -0.360906E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102124E+10 | 58.98 | 0.00 | 0.00 |
November | 0.386524E+11 | -0.376620E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990454068.1 | 58.98 | 0.00 | 0.00 |
December | 0.408302E+11 | -0.397947E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103550E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.475549E+12 | -0.463419E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.121301E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.344096E+11 | -0.458978E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.105967E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.469327E+11 | -0.334206E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -944653538.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5939.79 | 36.96 | 219.17 | 230.83 | 4966.50 | 37.82 | 223.83 | 213.00 |
February | 275.00 | 0.49 | 0.48 | 01-FEB-08:20 | 8039.44 | 37.30 | 268.33 | 258.50 | 3424.37 | 31.65 | 234.00 | 244.67 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9384.36 | 33.31 | 270.67 | 322.83 | 1937.80 | 23.33 | 251.67 | 295.50 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2382.45 | 20.93 | 149.00 | 348.00 | 1359.49 | 22.37 | 230.83 | 314.17 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2110.05 | 20.66 | 148.17 | 397.00 | 1182.89 | 22.08 | 269.00 | 356.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1812.13 | 20.12 | 152.83 | 411.00 | 1050.83 | 21.56 | 279.17 | 364.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1949.50 | 20.52 | 128.17 | 404.67 | 1162.89 | 21.99 | 264.83 | 369.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:30 | 2078.99 | 20.05 | 145.83 | 383.50 | 1240.93 | 21.48 | 233.83 | 347.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2923.99 | 21.46 | 140.83 | 326.83 | 1452.36 | 21.69 | 208.00 | 297.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 8140.78 | 35.00 | 288.83 | 301.50 | 2226.71 | 24.26 | 210.83 | 280.83 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6063.89 | 37.30 | 262.50 | 249.83 | 5336.88 | 38.48 | 263.83 | 239.50 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4719.31 | 37.66 | 237.17 | 231.67 | 4109.69 | 38.83 | 240.83 | 218.50 |
Annual Sum or Average | 3965.83 | 0.50 | 4247.24 | 26.96 | 2411.50 | 3866.17 | 2181.29 | 25.89 | 2910.67 | 3541.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1812.13 | 20.05 | 128.17 | 230.83 | 1050.83 | 21.48 | 208.00 | 213.00 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9384.36 | 37.66 | 288.83 | 411.00 | 5336.88 | 38.83 | 279.17 | 369.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:39 | 1878.36 | 25.34 | 102.00 | 216.17 | 1064.46 | 25.00 | 132.50 | 182.17 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2104.37 | 24.44 | 116.67 | 246.50 | 1132.73 | 24.35 | 147.67 | 214.83 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:40 | 3305.61 | 25.66 | 148.33 | 319.50 | 1841.32 | 25.84 | 227.33 | 288.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3294.85 | 24.30 | 105.83 | 356.50 | 1827.19 | 24.68 | 178.33 | 321.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3621.31 | 24.45 | 133.17 | 407.00 | 1586.69 | 23.92 | 211.50 | 369.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4406.47 | 25.53 | 149.33 | 423.00 | 1911.33 | 24.85 | 255.00 | 391.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 4778.57 | 25.65 | 144.00 | 421.50 | 2045.32 | 24.77 | 206.17 | 395.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3815.67 | 24.97 | 148.00 | 391.33 | 2190.41 | 25.24 | 209.50 | 360.33 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2875.65 | 24.13 | 136.83 | 327.17 | 1591.39 | 24.43 | 182.17 | 294.83 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-07:00 | 2582.84 | 24.64 | 138.00 | 290.00 | 1466.42 | 24.81 | 172.67 | 254.83 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1673.39 | 24.35 | 113.83 | 232.17 | 920.35 | 24.22 | 138.67 | 200.00 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1461.29 | 25.26 | 107.33 | 210.33 | 862.35 | 25.03 | 126.17 | 168.33 |
Annual Sum or Average | 3965.83 | 0.50 | 3183.09 | 24.91 | 1543.33 | 3841.17 | 1614.77 | 24.76 | 2187.67 | 3440.50 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 1461.29 | 24.13 | 102.00 | 210.33 | 862.35 | 23.92 | 126.17 | 168.33 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4778.57 | 25.66 | 149.33 | 423.00 | 2190.41 | 25.84 | 255.00 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-09:00 | 621.92 | 16.58 | 0.00 | 192.00 | 365.60 | 18.22 | 1.67 | 125.17 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:09 | 684.11 | 17.58 | 0.00 | 231.67 | 418.89 | 19.23 | 10.83 | 174.83 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1073.88 | 19.48 | 0.00 | 311.00 | 628.93 | 20.96 | 141.17 | 269.67 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1120.76 | 20.09 | 14.00 | 351.00 | 666.58 | 21.47 | 161.67 | 311.33 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1381.71 | 21.95 | 99.33 | 411.33 | 806.66 | 23.16 | 273.17 | 377.17 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1446.07 | 24.01 | 189.83 | 440.50 | 810.10 | 23.26 | 333.33 | 412.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1411.97 | 22.97 | 138.83 | 425.50 | 812.74 | 22.24 | 274.83 | 397.83 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1097.85 | 19.72 | 28.33 | 398.83 | 695.36 | 21.12 | 202.83 | 376.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 898.56 | 18.76 | 0.17 | 323.33 | 555.58 | 20.23 | 98.50 | 276.67 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:50 | 739.91 | 17.91 | 0.00 | 274.17 | 448.92 | 19.50 | 29.67 | 212.17 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:39 | 584.69 | 16.72 | 0.00 | 210.50 | 349.66 | 18.37 | 0.33 | 137.50 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:39 | 508.08 | 16.09 | 0.00 | 186.50 | 301.82 | 17.80 | 0.00 | 86.83 |
Annual Sum or Average | 3965.83 | 0.51 | 1024.31 | 19.78 | 470.50 | 3756.33 | 606.47 | 20.79 | 1528.00 | 3158.50 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 508.08 | 16.09 | 0.00 | 186.50 | 301.82 | 17.80 | 0.00 | 86.83 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1446.07 | 24.01 | 189.83 | 440.50 | 812.74 | 23.26 | 333.33 | 412.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-09:00 | 1748.73 | 24.11 | 95.17 | 209.00 | 1013.66 | 24.05 | 127.00 | 172.83 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:09 | 2256.90 | 25.11 | 123.17 | 244.33 | 1223.80 | 24.97 | 149.17 | 215.50 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-08:09 | 3104.10 | 25.42 | 146.00 | 317.33 | 1699.59 | 25.70 | 224.17 | 285.50 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 3210.69 | 23.24 | 108.17 | 348.67 | 1792.61 | 23.77 | 181.33 | 313.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:30 | 3659.12 | 22.40 | 97.17 | 402.50 | 2143.42 | 23.22 | 210.67 | 367.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3748.45 | 20.82 | 62.50 | 424.67 | 1690.80 | 21.19 | 219.00 | 391.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4345.80 | 22.47 | 91.33 | 410.33 | 1962.76 | 21.49 | 185.00 | 382.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3377.81 | 22.30 | 112.50 | 389.50 | 1862.29 | 22.87 | 186.33 | 359.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 3365.91 | 24.94 | 140.67 | 328.50 | 1407.17 | 23.97 | 180.67 | 296.33 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 2262.88 | 24.47 | 137.00 | 287.50 | 1245.30 | 24.58 | 177.83 | 253.00 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:39 | 1948.87 | 25.16 | 118.00 | 230.17 | 1100.98 | 25.00 | 142.33 | 197.00 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-09:30 | 1373.87 | 24.52 | 104.17 | 210.50 | 767.08 | 24.26 | 121.33 | 171.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3034.89 | 23.51 | 1335.83 | 3803.00 | 1563.47 | 23.54 | 2104.83 | 3406.17 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1373.87 | 20.82 | 62.50 | 209.00 | 767.08 | 21.19 | 121.33 | 171.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4345.80 | 25.42 | 146.00 | 424.67 | 2143.42 | 25.70 | 224.17 | 391.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5985.54 | 36.48 | 216.17 | 231.00 | 5091.00 | 37.35 | 215.17 | 214.83 |
February | 275.00 | 0.49 | 0.48 | 01-FEB-08:09 | 8102.63 | 36.82 | 265.83 | 258.67 | 3589.21 | 29.95 | 179.67 | 247.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9441.24 | 32.11 | 254.00 | 323.33 | 2068.46 | 18.60 | 12.33 | 297.50 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 2428.63 | 14.56 | 0.00 | 349.00 | 1457.25 | 18.09 | 4.00 | 318.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2145.01 | 14.52 | 0.00 | 397.67 | 1264.26 | 17.98 | 0.17 | 360.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1846.79 | 14.13 | 0.00 | 411.33 | 1123.84 | 17.67 | 0.00 | 369.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1992.45 | 14.51 | 0.00 | 405.50 | 1246.68 | 18.08 | 0.67 | 374.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 2130.70 | 13.77 | 0.00 | 384.00 | 1333.62 | 17.32 | 1.33 | 351.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2985.83 | 15.35 | 29.50 | 327.00 | 1578.41 | 17.41 | 10.50 | 301.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:09 | 8196.83 | 34.08 | 282.83 | 301.67 | 2449.97 | 21.83 | 80.17 | 285.83 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6114.87 | 36.85 | 261.83 | 250.17 | 5453.50 | 38.12 | 262.83 | 241.00 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4755.25 | 37.23 | 231.33 | 231.67 | 4217.31 | 38.50 | 231.83 | 219.50 |
Annual Sum or Average | 3965.83 | 0.50 | 4295.19 | 23.06 | 1541.50 | 3871.00 | 2295.88 | 22.73 | 998.67 | 3580.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1846.79 | 13.77 | 0.00 | 231.00 | 1123.84 | 17.32 | 0.00 | 214.83 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9441.24 | 37.23 | 282.83 | 411.33 | 5453.50 | 38.50 | 262.83 | 374.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:39 | 1908.52 | 23.19 | 89.67 | 217.00 | 1106.50 | 23.39 | 74.83 | 186.33 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2100.36 | 20.53 | 75.00 | 247.17 | 1187.27 | 22.42 | 71.17 | 218.50 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:40 | 3335.87 | 22.10 | 94.00 | 319.67 | 1916.11 | 23.84 | 85.00 | 291.00 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3356.22 | 21.21 | 85.17 | 356.83 | 1905.85 | 22.26 | 60.17 | 325.33 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3680.88 | 21.49 | 112.67 | 407.17 | 1666.21 | 21.31 | 57.83 | 373.00 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4451.51 | 21.84 | 134.17 | 423.17 | 2002.24 | 22.36 | 89.33 | 393.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 4849.64 | 22.73 | 134.00 | 422.50 | 2145.65 | 22.14 | 75.50 | 397.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3883.05 | 22.07 | 131.33 | 392.33 | 2277.58 | 22.95 | 100.50 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2931.82 | 21.26 | 104.17 | 327.17 | 1660.58 | 22.18 | 77.33 | 299.83 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-07:00 | 2625.95 | 22.12 | 110.50 | 290.50 | 1520.61 | 22.90 | 97.50 | 258.50 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1703.25 | 22.04 | 95.17 | 232.17 | 961.11 | 22.50 | 78.67 | 203.83 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1483.31 | 23.25 | 101.83 | 210.67 | 894.29 | 23.59 | 86.50 | 173.67 |
Annual Sum or Average | 3965.83 | 0.50 | 3229.03 | 21.95 | 1267.67 | 3846.33 | 1685.81 | 22.58 | 954.33 | 3484.00 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 1483.31 | 20.53 | 75.00 | 210.67 | 894.29 | 21.31 | 57.83 | 173.67 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4849.64 | 23.25 | 134.17 | 423.17 | 2277.58 | 23.84 | 100.50 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-09:50 | 629.35 | 10.71 | 0.00 | 192.67 | 388.33 | 14.28 | 0.00 | 135.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-09:00 | 694.15 | 11.79 | 0.00 | 232.33 | 445.64 | 15.43 | 0.00 | 183.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1090.42 | 13.88 | 0.00 | 311.50 | 668.98 | 17.34 | 0.00 | 274.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1140.52 | 14.67 | 0.00 | 351.83 | 710.11 | 18.15 | 2.33 | 316.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1406.66 | 16.80 | 38.50 | 411.67 | 858.16 | 20.01 | 44.00 | 381.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1474.73 | 19.70 | 107.33 | 441.00 | 864.61 | 19.97 | 36.33 | 416.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1441.99 | 18.27 | 72.17 | 425.83 | 868.63 | 18.83 | 17.00 | 401.17 |
August | 421.33 | 0.49 | 0.48 | 01-AUG-05:40 | 1120.22 | 14.23 | 0.00 | 399.00 | 740.08 | 17.80 | 2.83 | 380.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 914.82 | 13.33 | 0.00 | 323.83 | 592.08 | 16.82 | 0.00 | 283.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:39 | 750.99 | 12.24 | 0.00 | 274.83 | 477.68 | 15.83 | 0.00 | 223.17 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:30 | 592.23 | 10.78 | 0.00 | 211.33 | 371.60 | 14.45 | 0.00 | 152.17 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:30 | 513.00 | 9.97 | 0.00 | 187.50 | 320.33 | 13.68 | 0.00 | 105.33 |
Annual Sum or Average | 3965.83 | 0.51 | 1042.56 | 14.41 | 218.00 | 3763.33 | 646.02 | 17.27 | 102.50 | 3251.67 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 513.00 | 9.97 | 0.00 | 187.50 | 320.33 | 13.68 | 0.00 | 105.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1474.73 | 19.70 | 107.33 | 441.00 | 868.63 | 20.01 | 44.00 | 416.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-09:50 | 1776.53 | 22.00 | 85.00 | 210.17 | 1052.60 | 22.47 | 70.33 | 176.33 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-09:00 | 2296.53 | 22.66 | 95.17 | 244.67 | 1276.43 | 23.13 | 84.33 | 219.17 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-08:09 | 3134.09 | 21.81 | 92.50 | 318.00 | 1768.59 | 23.69 | 84.17 | 288.67 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 3270.64 | 19.92 | 75.83 | 349.50 | 1872.31 | 21.13 | 48.00 | 317.83 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:30 | 3716.00 | 18.80 | 75.00 | 403.50 | 2228.38 | 20.35 | 46.00 | 371.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3801.02 | 16.85 | 52.00 | 425.50 | 1773.12 | 17.85 | 0.00 | 394.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4408.61 | 18.90 | 79.67 | 411.17 | 2057.66 | 18.19 | 3.67 | 384.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 3438.60 | 18.88 | 90.83 | 390.50 | 1941.19 | 20.14 | 58.00 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3422.08 | 22.29 | 116.67 | 328.17 | 1476.64 | 21.64 | 66.50 | 300.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 2306.62 | 21.83 | 100.50 | 288.33 | 1300.52 | 22.57 | 87.00 | 257.33 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-08:39 | 1978.30 | 22.68 | 102.67 | 231.00 | 1142.80 | 23.32 | 92.83 | 201.50 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-09:30 | 1358.91 | 20.71 | 78.50 | 210.67 | 799.90 | 22.74 | 83.33 | 176.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3080.40 | 20.31 | 1044.33 | 3811.17 | 1632.21 | 21.10 | 724.17 | 3452.17 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1358.91 | 16.85 | 52.00 | 210.17 | 799.90 | 17.85 | 0.00 | 176.33 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4408.61 | 22.68 | 116.67 | 425.50 | 2228.38 | 23.69 | 92.83 | 394.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5986.66 | 36.48 | 216.17 | 231.00 | 5092.97 | 37.35 | 215.17 | 214.83 |
February | 275.00 | 0.49 | 0.48 | 01-FEB-08:09 | 8104.21 | 36.81 | 265.83 | 258.67 | 3591.55 | 29.94 | 179.67 | 247.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9444.85 | 32.10 | 254.00 | 323.33 | 2071.47 | 18.58 | 12.17 | 297.67 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 2431.98 | 14.53 | 0.00 | 349.00 | 1459.38 | 18.07 | 3.67 | 318.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2148.11 | 14.49 | 0.00 | 397.67 | 1266.15 | 17.97 | 0.17 | 360.67 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1849.19 | 14.10 | 0.00 | 411.33 | 1125.38 | 17.65 | 0.00 | 369.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1994.88 | 14.48 | 0.00 | 405.50 | 1248.28 | 18.07 | 0.50 | 374.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 2133.37 | 13.74 | 0.00 | 384.00 | 1335.35 | 17.30 | 1.33 | 351.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2988.70 | 15.32 | 29.50 | 327.00 | 1580.48 | 17.39 | 10.33 | 301.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:09 | 8198.71 | 34.07 | 282.83 | 301.67 | 2452.27 | 21.82 | 80.17 | 286.00 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6115.87 | 36.84 | 261.83 | 250.33 | 5455.49 | 38.12 | 262.83 | 241.17 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4755.88 | 37.22 | 231.33 | 231.83 | 4218.89 | 38.49 | 231.83 | 219.50 |
Annual Sum or Average | 3965.83 | 0.50 | 4297.53 | 23.04 | 1541.50 | 3871.33 | 2297.86 | 22.72 | 997.83 | 3582.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1849.19 | 13.74 | 0.00 | 231.00 | 1125.38 | 17.30 | 0.00 | 214.83 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9444.85 | 37.22 | 282.83 | 411.33 | 5455.49 | 38.49 | 262.83 | 374.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:39 | 1909.49 | 23.16 | 89.67 | 217.00 | 1107.48 | 23.38 | 74.67 | 186.50 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2101.31 | 20.50 | 75.00 | 247.00 | 1188.36 | 22.40 | 70.67 | 218.50 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:40 | 3337.87 | 22.07 | 94.00 | 319.67 | 1917.88 | 23.83 | 84.67 | 291.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3357.98 | 21.18 | 85.17 | 356.83 | 1907.49 | 22.25 | 60.17 | 325.33 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3683.04 | 21.46 | 112.67 | 407.33 | 1667.95 | 21.29 | 57.83 | 373.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4453.36 | 21.81 | 134.17 | 423.17 | 2003.98 | 22.35 | 89.33 | 394.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 4851.21 | 22.71 | 134.00 | 422.50 | 2147.25 | 22.13 | 75.50 | 397.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3884.58 | 22.04 | 131.33 | 392.50 | 2279.10 | 22.94 | 100.50 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2933.19 | 21.23 | 104.17 | 327.17 | 1661.98 | 22.17 | 77.33 | 300.00 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-07:00 | 2612.56 | 21.74 | 107.00 | 290.33 | 1521.78 | 22.89 | 97.17 | 258.50 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1655.73 | 20.47 | 83.00 | 231.83 | 962.01 | 22.49 | 78.50 | 203.83 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1484.01 | 23.23 | 101.83 | 210.67 | 895.08 | 23.58 | 86.50 | 173.67 |
Annual Sum or Average | 3965.83 | 0.50 | 3226.06 | 21.79 | 1252.00 | 3846.00 | 1687.23 | 22.56 | 952.83 | 3485.33 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 1484.01 | 20.47 | 75.00 | 210.67 | 895.08 | 21.29 | 57.83 | 173.67 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4851.21 | 23.23 | 134.17 | 423.17 | 2279.10 | 23.83 | 100.50 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-09:50 | 629.97 | 10.68 | 0.00 | 192.83 | 388.88 | 14.26 | 0.00 | 135.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-09:00 | 694.71 | 11.75 | 0.00 | 232.33 | 446.20 | 15.42 | 0.00 | 183.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1091.59 | 13.85 | 0.00 | 311.50 | 669.92 | 17.32 | 0.00 | 274.50 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1141.69 | 14.64 | 0.00 | 351.83 | 711.07 | 18.13 | 2.33 | 316.50 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1408.06 | 16.77 | 38.50 | 411.83 | 859.29 | 20.00 | 43.83 | 381.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1475.87 | 19.67 | 107.33 | 441.17 | 865.67 | 19.95 | 35.83 | 416.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1443.01 | 18.24 | 72.17 | 425.83 | 869.63 | 18.81 | 16.17 | 401.17 |
August | 421.33 | 0.49 | 0.48 | 01-AUG-05:40 | 1121.12 | 14.20 | 0.00 | 399.00 | 740.92 | 17.79 | 2.83 | 380.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 915.58 | 13.30 | 0.00 | 323.83 | 592.79 | 16.80 | 0.00 | 283.33 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:39 | 751.65 | 12.21 | 0.00 | 275.00 | 478.29 | 15.81 | 0.00 | 223.17 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:30 | 592.76 | 10.75 | 0.00 | 211.33 | 372.10 | 14.43 | 0.00 | 152.17 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:30 | 513.44 | 9.94 | 0.00 | 187.50 | 320.77 | 13.66 | 0.00 | 105.67 |
Annual Sum or Average | 3965.83 | 0.51 | 1043.47 | 14.38 | 218.00 | 3764.00 | 646.83 | 17.25 | 101.00 | 3252.67 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 513.44 | 9.94 | 0.00 | 187.50 | 320.77 | 13.66 | 0.00 | 105.67 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1475.87 | 19.67 | 107.33 | 441.17 | 869.63 | 20.00 | 43.83 | 416.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-09:50 | 1777.52 | 21.97 | 85.00 | 210.17 | 1053.58 | 22.45 | 70.17 | 176.33 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-09:00 | 2297.51 | 22.63 | 95.17 | 244.67 | 1277.51 | 23.12 | 83.67 | 219.17 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-08:09 | 3136.16 | 21.79 | 92.50 | 318.17 | 1770.37 | 23.68 | 82.67 | 288.83 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 3272.55 | 19.89 | 75.83 | 349.50 | 1874.12 | 21.12 | 48.00 | 318.00 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:30 | 3718.15 | 18.77 | 75.00 | 403.50 | 2230.30 | 20.34 | 46.00 | 372.00 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3802.97 | 16.82 | 52.00 | 425.50 | 1774.85 | 17.84 | 0.00 | 394.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4410.35 | 18.87 | 79.67 | 411.17 | 2059.38 | 18.17 | 3.67 | 384.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 3440.22 | 18.85 | 90.83 | 390.67 | 1942.74 | 20.12 | 58.00 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3423.42 | 22.27 | 116.50 | 328.17 | 1478.02 | 21.63 | 66.50 | 300.33 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 2307.70 | 21.80 | 100.33 | 288.33 | 1301.69 | 22.56 | 86.50 | 257.50 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-08:39 | 1979.14 | 22.66 | 102.67 | 231.00 | 1143.74 | 23.31 | 92.67 | 201.67 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-09:30 | 1359.61 | 20.69 | 78.33 | 210.67 | 800.68 | 22.73 | 83.00 | 176.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3081.92 | 20.28 | 1043.83 | 3811.50 | 1633.67 | 21.09 | 720.83 | 3453.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1359.61 | 16.82 | 52.00 | 210.17 | 800.68 | 17.84 | 0.00 | 176.33 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4410.35 | 22.66 | 116.50 | 425.50 | 2230.30 | 23.68 | 92.67 | 394.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.417822E+11 | 76457.83 | 09-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235133E+11 | 61789.56 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134454E+11 | 51684.47 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331968E+10 | 30401.68 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239279E+10 | 23070.62 | 08-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92441743.28 | 13212.90 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.690867E+09 | 14141.35 | 19-SEP-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.287148E+10 | 30979.38 | 10-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.974628E+10 | 47179.29 | 27-NOV-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254785E+11 | 75103.34 | 29-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.417822E+11 | 76457.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326812E+10 | 13551.84 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102834E+10 | 14600.78 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174884E+09 | 14602.15 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85752.93 | 477.64 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78265062.77 | 13498.50 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.650557E+09 | 14552.59 | 18-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.520024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326812E+10 | 14602.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209884E+10 | 15987.98 | 31-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.707874E+09 | 16407.77 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143380E+09 | 16408.82 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2308044.66 | 9732.71 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1669674.26 | 2432.74 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109214E+09 | 15976.32 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.636589E+09 | 16446.80 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209884E+10 | 16446.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.294749E+10 | 23334.31 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.863568E+09 | 23317.57 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263317E+09 | 23275.21 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10912364.43 | 23330.38 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35757238.23 | 23372.12 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12622260.11 | 15190.84 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216371E+09 | 23351.32 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.843393E+09 | 23337.72 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.294749E+10 | 23372.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.992511E+09 | 15291.09 | 26-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91570626.34 | 15267.19 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7889509.00 | 15266.23 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 868671.09 | 6083.31 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8323749.53 | 7697.50 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.992511E+09 | 15291.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.455801E+12 | 842128.14 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271055E+12 | 728346.62 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190724E+12 | 623329.32 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.733437E+11 | 296573.97 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.452488E+11 | 252394.78 | 03-MAY-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.331603E+10 | 138111.38 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1826836.82 | 3687.30 | 08-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.681775E+09 | 263091.16 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158587E+11 | 279080.03 | 11-SEP-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.512115E+11 | 294284.19 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134169E+12 | 512081.46 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315218E+12 | 796135.20 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155663E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1826836.82 | 3687.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.455801E+12 | 842128.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158913E+11 | 574533.84 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401262E+10 | 574133.52 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105682E+10 | 573400.92 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.887841E+09 | 573897.21 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.525882E+10 | 572206.81 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158913E+11 | 574533.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106274E+12 | 140622.56 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.529510E+11 | 130423.85 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245988E+11 | 130359.29 | 24-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377487E+10 | 140920.31 | 14-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294001E+10 | 140770.68 | 03-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.667959E+09 | 131103.35 | 20-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370519E+10 | 138757.80 | 05-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254778E+11 | 135673.28 | 09-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.676840E+11 | 130456.45 | 18-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106274E+12 | 140920.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.603434E+11 | 200230.97 | 11-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270618E+11 | 200060.21 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123171E+11 | 199991.49 | 09-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174865E+10 | 199455.71 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171287E+10 | 199437.48 | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111512.84 | 929.27 | 18-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256692E+09 | 138891.65 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161774E+10 | 204702.82 | 05-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137496E+11 | 200066.45 | 20-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373776E+11 | 200347.44 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.603434E+11 | 204702.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.681514E+11 | 242425.95 | 27-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264734E+11 | 243191.99 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141705E+11 | 240953.33 | 09-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267881E+10 | 238831.11 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301132E+10 | 239428.37 | 22-MAY-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4394184.88 | 8643.06 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363522E+09 | 167421.08 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157108E+10 | 238819.75 | 10-OCT-04:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141762E+11 | 241096.04 | 29-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381297E+11 | 243150.26 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168730E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.681514E+11 | 243191.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.571987E+11 | 205492.83 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223492E+11 | 205021.07 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100769E+11 | 204854.51 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108432E+10 | 195721.01 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136462E+10 | 204576.52 | 08-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204875E+09 | 108661.54 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115118E+10 | 204565.94 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106781E+11 | 204929.61 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303861E+11 | 205503.68 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.571987E+11 | 205503.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.511151E+11 | 84609.49 | 11-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297890E+11 | 79321.01 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215205E+11 | 70674.18 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879987E+10 | 35900.09 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.547485E+10 | 30233.43 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.629122E+09 | 15579.69 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18562791.35 | 2955.93 | 05-JUL-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198556E+09 | 6551.84 | 28-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227376E+10 | 17784.46 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670889E+10 | 37535.06 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160960E+11 | 52038.41 | 27-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357398E+11 | 81716.56 | 29-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178364E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 18562791.35 | 2955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.511151E+11 | 84609.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172556E+11 | 72604.86 | 02-JAN-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737759E+10 | 72606.53 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393551E+10 | 72305.11 | 07-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466740E+09 | 71981.22 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.918972E+09 | 72571.79 | 01-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14647963.40 | 4103.09 | 19-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621131E+09 | 72605.80 | 10-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466618E+10 | 72575.21 | 20-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108912E+11 | 72584.28 | 01-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172556E+11 | 72606.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173823E+11 | 18307.13 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.956892E+10 | 15845.94 | 13-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.615361E+10 | 15844.79 | 20-MAR-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185650E+10 | 15787.35 | 29-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132605E+10 | 15839.56 | 08-MAY-04:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34849316.13 | 15770.87 | 17-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28226224.79 | 15776.40 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550612E+09 | 15824.94 | 12-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196433E+10 | 15846.65 | 10-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.666941E+10 | 15798.25 | 20-NOV-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132004E+11 | 16900.43 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173823E+11 | 18307.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106254E+11 | 20702.74 | 05-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518385E+10 | 20697.22 | 23-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318054E+10 | 20692.00 | 03-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.872607E+09 | 20670.13 | 21-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.708248E+09 | 20632.56 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16193240.98 | 16169.04 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11550037.29 | 13049.07 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247621E+09 | 20683.62 | 19-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.895224E+09 | 20688.88 | 10-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365802E+10 | 20796.36 | 29-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.784983E+10 | 20708.71 | 19-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106254E+11 | 20796.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122890E+11 | 26083.12 | 12-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.556995E+10 | 25990.34 | 03-FEB-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.408156E+10 | 26079.74 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139559E+10 | 25884.12 | 28-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126560E+10 | 26078.50 | 09-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 63957759.27 | 25960.84 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 218645.66 | 1171.25 | 08-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29352964.86 | 20010.30 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345484E+09 | 25962.37 | 19-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102120E+10 | 26093.29 | 10-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.391019E+10 | 26071.76 | 29-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.853030E+10 | 25996.25 | 14-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 218645.66 | 1171.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122890E+11 | 26093.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.984578E+10 | 23544.48 | 25-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424085E+10 | 23547.02 | 24-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262491E+10 | 23548.45 | 03-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.634172E+09 | 23424.71 | 01-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.579013E+09 | 23526.86 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16207321.67 | 15585.66 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12659116.53 | 12334.92 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.190633E+09 | 23411.01 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674659E+09 | 23519.15 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276332E+10 | 23431.15 | 29-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.616430E+10 | 23546.22 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.984578E+10 | 23548.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.178079E+10 | 34500.76 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48972517.39 | 6307.84 | 04-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 157.27 | 0.79 | 26-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 262.11 | 0.97 | 28-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85.09 | 0.71 | 22-JUL-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 122.41 | 1.02 | 21-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112.35 | 0.94 | 04-NOV-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178079E+10 | 34500.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.648927E+09 | 0.648927E+09 | 30412.55 | 02-JAN-14:10 | 30412.55 | 0.00 |
February | 0.00 | 0.00 | 0.359370E+10 | 0.359370E+10 | 53407.50 | 28-FEB-16:00 | 53407.50 | 0.00 |
March | 0.00 | 0.00 | 0.562545E+10 | 0.562545E+10 | 49925.77 | 01-MAR-16:10 | 49925.77 | 0.00 |
April | 0.00 | 0.00 | 0.808496E+10 | 0.808496E+10 | 78461.25 | 06-APR-16:00 | 78461.25 | 0.00 |
May | 0.00 | 0.00 | 0.175451E+11 | 0.175451E+11 | 105590.39 | 19-MAY-15:20 | 105590.39 | 0.05 |
June | 0.00 | 0.00 | 0.565943E+11 | 0.562972E+11 | 141948.95 | 20-JUN-13:13 | 132552.74 | 0.22 |
July | 0.00 | 0.00 | 0.965038E+11 | 0.960691E+11 | 148523.84 | 25-JUL-16:45 | 148523.84 | 0.38 |
August | 0.00 | 0.00 | 0.881294E+11 | 0.881281E+11 | 146808.68 | 10-AUG-12:35 | 146808.68 | 0.20 |
September | 0.00 | 0.00 | 0.378222E+11 | 0.363333E+11 | 179132.93 | 07-SEP-14:45 | 94656.81 | 0.17 |
October | 0.00 | 0.00 | 0.147715E+11 | 0.147715E+11 | 99290.94 | 18-OCT-14:00 | 99290.94 | 0.00 |
November | 0.00 | 0.00 | 0.897770E+10 | 0.897770E+10 | 61873.25 | 03-NOV-15:00 | 61873.25 | 0.00 |
December | 0.00 | 0.00 | 0.437107E+10 | 0.437107E+10 | 40627.39 | 06-DEC-13:20 | 40627.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.342668E+12 | 0.340446E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.648927E+09 | 0.648927E+09 | 30412.55 | 30412.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.965038E+11 | 0.960691E+11 | 179132.93 | 148523.84 | 0.38 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 18472.87 | 18472.87 | 2.10 | 02-JAN-06:01 | 2.10 | 0.00 |
February | 0.00 | 0.00 | 0.176101E+11 | 0.176101E+11 | 440069.75 | 27-FEB-15:30 | 440069.75 | 0.00 |
March | 0.00 | 0.00 | 0.278900E+11 | 0.278900E+11 | 344213.15 | 28-MAR-16:00 | 344213.15 | 0.00 |
April | 0.00 | 0.00 | 0.790463E+11 | 0.790463E+11 | 639046.49 | 06-APR-14:05 | 639046.49 | 0.00 |
May | 0.00 | 0.00 | 0.156529E+12 | 0.156529E+12 | 1027942.23 | 19-MAY-15:20 | 1027942.23 | 0.04 |
June | 0.00 | 0.00 | 0.482315E+12 | 0.479653E+12 | 1304775.10 | 21-JUN-12:45 | 1188050.27 | 0.20 |
July | 0.00 | 0.00 | 0.806670E+12 | 0.803530E+12 | 1354228.88 | 25-JUL-12:13 | 1354228.88 | 0.32 |
August | 0.00 | 0.00 | 0.698662E+12 | 0.698662E+12 | 1346986.21 | 10-AUG-12:10 | 1346986.21 | 0.17 |
September | 0.00 | 0.00 | 0.337933E+12 | 0.324395E+12 | 1656852.90 | 07-SEP-14:45 | 874149.62 | 0.16 |
October | 0.00 | 0.00 | 0.130250E+12 | 0.130250E+12 | 836728.65 | 18-OCT-15:20 | 836728.65 | 0.00 |
November | 0.00 | 0.00 | 0.238565E+11 | 0.238565E+11 | 432686.42 | 03-NOV-14:05 | 432686.42 | 0.00 |
December | 0.00 | 0.00 | 5706452.74 | 5706452.74 | 8261.28 | 07-DEC-15:30 | 8261.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.276077E+13 | 0.274143E+13 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 18472.87 | 18472.87 | 2.10 | 2.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.806670E+12 | 0.803530E+12 | 1656852.90 | 1354228.88 | 0.32 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7235.46 | 7235.46 | 59.71 | 02-JAN-04:56 | 59.71 | 0.00 |
February | 0.00 | 0.00 | 0.750984E+09 | 0.750984E+09 | 23061.66 | 27-FEB-13:35 | 23061.66 | 0.00 |
March | 0.00 | 0.00 | 0.115081E+10 | 0.115081E+10 | 29177.17 | 28-MAR-15:50 | 29177.17 | 0.00 |
April | 0.00 | 0.00 | 0.451285E+10 | 0.451285E+10 | 62593.36 | 06-APR-16:00 | 62593.36 | 0.00 |
May | 0.00 | 0.00 | 0.150073E+11 | 0.150073E+11 | 129792.49 | 19-MAY-15:10 | 129792.49 | 0.04 |
June | 0.00 | 0.00 | 0.523869E+11 | 0.520945E+11 | 155701.87 | 21-JUN-12:32 | 145396.07 | 0.20 |
July | 0.00 | 0.00 | 0.888580E+11 | 0.885673E+11 | 167488.54 | 25-JUL-16:32 | 167488.54 | 0.32 |
August | 0.00 | 0.00 | 0.748657E+11 | 0.748657E+11 | 155427.61 | 10-AUG-12:23 | 155427.61 | 0.17 |
September | 0.00 | 0.00 | 0.325942E+11 | 0.312685E+11 | 187303.56 | 07-SEP-15:03 | 104410.42 | 0.14 |
October | 0.00 | 0.00 | 0.665796E+10 | 0.665796E+10 | 84982.85 | 18-OCT-15:10 | 84982.85 | 0.00 |
November | 0.00 | 0.00 | 0.422306E+09 | 0.422306E+09 | 10528.46 | 09-NOV-14:50 | 10528.46 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.277207E+12 | 0.275298E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.888580E+11 | 0.885673E+11 | 187303.56 | 167488.54 | 0.32 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 334457.24 | 334457.24 | 3666.49 | 24-JAN-05:11 | 3666.49 | 0.00 |
February | 0.00 | 0.00 | 0.262399E+09 | 0.262399E+09 | 22155.19 | 27-FEB-15:00 | 22155.19 | 0.00 |
March | 0.00 | 0.00 | 55797.28 | 55797.28 | 61.20 | 07-MAR-12:10 | 61.20 | 0.00 |
April | 0.00 | 0.00 | 0.204208E+10 | 0.204208E+10 | 41674.39 | 07-APR-14:00 | 41674.39 | 0.00 |
May | 0.00 | 0.00 | 0.773335E+10 | 0.773335E+10 | 61626.12 | 29-MAY-18:37 | 61626.12 | 0.03 |
June | 0.00 | 0.00 | 0.277385E+11 | 0.277015E+11 | 69873.85 | 20-JUN-13:13 | 64631.60 | 0.15 |
July | 0.00 | 0.00 | 0.474299E+11 | 0.473710E+11 | 80161.41 | 16-JUL-18:51 | 80161.41 | 0.26 |
August | 0.00 | 0.00 | 0.438544E+11 | 0.438544E+11 | 76329.09 | 07-AUG-18:00 | 76329.09 | 0.15 |
September | 0.00 | 0.00 | 0.181207E+11 | 0.176542E+11 | 87803.53 | 07-SEP-14:50 | 48002.63 | 0.13 |
October | 0.00 | 0.00 | 0.518394E+10 | 0.518394E+10 | 50959.88 | 18-OCT-14:00 | 50959.88 | 0.00 |
November | 0.00 | 0.00 | 63463694.89 | 63463694.89 | 22384.12 | 17-NOV-06:03 | 22384.12 | 0.00 |
December | 0.00 | 0.00 | 11486.92 | 11486.92 | 19.14 | 26-DEC-19:20 | 19.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152429E+12 | 0.151867E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 11486.92 | 11486.92 | 19.14 | 19.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.474299E+11 | 0.473710E+11 | 87803.53 | 80161.41 | 0.26 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.889853E+10 | 0.774860E+10 | 5163.07 | 03-JAN-15:00 | 4689.52 | 0.00 |
February | 0.00 | 0.00 | 0.135512E+11 | 0.119748E+11 | 17662.38 | 27-FEB-16:00 | 17662.38 | 0.00 |
March | 0.00 | 0.00 | 0.151137E+11 | 0.143703E+11 | 7051.77 | 14-MAR-13:05 | 7051.77 | 0.00 |
April | 0.00 | 0.00 | 0.757828E+11 | 0.726815E+11 | 314513.23 | 07-APR-14:00 | 314513.23 | 0.00 |
May | 0.00 | 0.00 | 0.179629E+11 | 0.167730E+11 | 137228.90 | 19-MAY-13:50 | 131102.99 | 0.00 |
June | 0.00 | 0.00 | 0.136129E+12 | 0.122882E+12 | 323560.09 | 20-JUN-18:50 | 219750.99 | 0.00 |
July | 0.00 | 0.00 | 0.448109E+12 | 0.400325E+12 | 413514.14 | 19-JUL-10:50 | 313504.36 | 0.00 |
August | 0.00 | 0.00 | 0.571233E+12 | 0.519635E+12 | 413207.05 | 05-AUG-19:07 | 394711.02 | 0.00 |
September | 0.00 | 0.00 | 0.450197E+11 | 0.410304E+11 | 212544.73 | 07-SEP-16:00 | 124885.57 | 0.00 |
October | 0.00 | 0.00 | 0.246686E+11 | 0.230531E+11 | 176407.85 | 18-OCT-15:00 | 176407.85 | 0.00 |
November | 0.00 | 0.00 | 0.166347E+11 | 0.157252E+11 | 67900.68 | 17-NOV-17:00 | 64759.63 | 0.00 |
December | 0.00 | 0.00 | 0.167490E+11 | 0.164012E+11 | 68185.89 | 10-DEC-02:00 | 68185.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138985E+13 | 0.126260E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.889853E+10 | 0.774860E+10 | 5163.07 | 4689.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.571233E+12 | 0.519635E+12 | 413514.14 | 394711.02 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.274882E+10 | 0.274849E+10 | 2251.34 | 01-JAN-16:05 | 2244.69 | 0.00 |
February | 0.00 | 0.00 | 0.812256E+10 | 0.812256E+10 | 5194.02 | 26-FEB-17:17 | 5194.02 | 0.00 |
March | 0.00 | 0.00 | 0.148683E+11 | 0.148683E+11 | 7480.35 | 31-MAR-24:00 | 7480.35 | 0.00 |
April | 0.00 | 0.00 | 0.199386E+11 | 0.199297E+11 | 9038.20 | 22-APR-18:15 | 9038.20 | 0.00 |
May | 0.00 | 0.00 | 0.551760E+10 | 0.549061E+10 | 4080.12 | 31-MAY-24:00 | 4080.12 | 0.00 |
June | 0.00 | 0.00 | 0.108206E+11 | 0.107265E+11 | 6007.78 | 30-JUN-23:55 | 5994.07 | 0.00 |
July | 0.00 | 0.00 | 0.165424E+11 | 0.164397E+11 | 7928.54 | 31-JUL-24:00 | 7928.54 | 0.00 |
August | 0.00 | 0.00 | 0.214075E+11 | 0.213296E+11 | 8869.36 | 05-AUG-20:23 | 8827.28 | 0.00 |
September | 0.00 | 0.00 | 0.563123E+10 | 0.554151E+10 | 3917.57 | 30-SEP-24:00 | 3917.57 | 0.00 |
October | 0.00 | 0.00 | 0.104489E+11 | 0.104360E+11 | 5595.92 | 31-OCT-24:00 | 5595.92 | 0.00 |
November | 0.00 | 0.00 | 0.145606E+11 | 0.145579E+11 | 6762.83 | 12-NOV-16:30 | 6762.83 | 0.00 |
December | 0.00 | 0.00 | 0.194532E+11 | 0.194529E+11 | 8424.26 | 10-DEC-16:10 | 8424.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150060E+12 | 0.149644E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.274882E+10 | 0.274849E+10 | 2251.34 | 2244.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214075E+11 | 0.213296E+11 | 9038.20 | 9038.20 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.493682E+10 | 0.493431E+10 | 16874.07 | 13-JAN-16:30 | 16874.07 | 0.00 |
February | 0.00 | 0.00 | 0.563373E+11 | 0.563373E+11 | 45490.91 | 26-FEB-17:25 | 45490.91 | 0.00 |
March | 0.00 | 0.00 | 0.123310E+12 | 0.123310E+12 | 64921.56 | 31-MAR-23:30 | 64921.56 | 0.00 |
April | 0.00 | 0.00 | 0.179779E+12 | 0.179689E+12 | 84626.25 | 22-APR-18:17 | 84626.25 | 0.00 |
May | 0.00 | 0.00 | 0.449368E+11 | 0.446752E+11 | 38649.78 | 31-MAY-24:00 | 38649.78 | 0.00 |
June | 0.00 | 0.00 | 0.999470E+11 | 0.990170E+11 | 58286.30 | 30-JUN-23:55 | 58150.74 | 0.00 |
July | 0.00 | 0.00 | 0.156148E+12 | 0.155128E+12 | 76553.13 | 31-JUL-24:00 | 76553.13 | 0.00 |
August | 0.00 | 0.00 | 0.202004E+12 | 0.201229E+12 | 84857.76 | 05-AUG-20:05 | 84857.76 | 0.00 |
September | 0.00 | 0.00 | 0.480174E+11 | 0.471439E+11 | 35333.61 | 30-SEP-23:30 | 35333.61 | 0.00 |
October | 0.00 | 0.00 | 0.877869E+11 | 0.876587E+11 | 48414.27 | 15-OCT-17:03 | 48414.27 | 0.00 |
November | 0.00 | 0.00 | 0.119199E+12 | 0.119171E+12 | 59839.07 | 03-NOV-16:00 | 59177.05 | 0.00 |
December | 0.00 | 0.00 | 0.155165E+12 | 0.155161E+12 | 74352.69 | 06-DEC-16:10 | 74033.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127757E+13 | 0.127345E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.493682E+10 | 0.493431E+10 | 16874.07 | 16874.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202004E+12 | 0.201229E+12 | 84857.76 | 84857.76 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.138862E+09 | 0.138803E+09 | 1647.68 | 13-JAN-16:30 | 1647.68 | 0.00 |
February | 0.00 | 0.00 | 0.407281E+10 | 0.407281E+10 | 4194.06 | 26-FEB-17:40 | 4194.06 | 0.00 |
March | 0.00 | 0.00 | 0.106160E+11 | 0.106160E+11 | 6273.10 | 28-MAR-17:50 | 6273.10 | 0.00 |
April | 0.00 | 0.00 | 0.167685E+11 | 0.167596E+11 | 8410.95 | 22-APR-18:10 | 8410.95 | 0.00 |
May | 0.00 | 0.00 | 0.380983E+10 | 0.378399E+10 | 3785.26 | 31-MAY-23:30 | 3785.26 | 0.00 |
June | 0.00 | 0.00 | 0.978982E+10 | 0.969694E+10 | 5829.92 | 30-JUN-23:55 | 5816.23 | 0.00 |
July | 0.00 | 0.00 | 0.155754E+11 | 0.154735E+11 | 7642.70 | 31-JUL-24:00 | 7642.70 | 0.00 |
August | 0.00 | 0.00 | 0.200627E+11 | 0.199854E+11 | 8647.45 | 05-AUG-20:05 | 8647.45 | 0.00 |
September | 0.00 | 0.00 | 0.422405E+10 | 0.413822E+10 | 3662.80 | 04-SEP-17:51 | 3662.80 | 0.00 |
October | 0.00 | 0.00 | 0.731036E+10 | 0.729785E+10 | 4645.97 | 15-OCT-17:05 | 4645.97 | 0.00 |
November | 0.00 | 0.00 | 0.994023E+10 | 0.993757E+10 | 5884.58 | 03-NOV-16:00 | 5818.51 | 0.00 |
December | 0.00 | 0.00 | 0.135261E+11 | 0.135257E+11 | 7343.55 | 06-DEC-16:10 | 7312.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115835E+12 | 0.115426E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.138862E+09 | 0.138803E+09 | 1647.68 | 1647.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200627E+11 | 0.199854E+11 | 8647.45 | 8647.45 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 347266.38 | 2060137.74 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 202249.87 | 1717391.72 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 114578.85 | 1635490.26 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 38365.78 | 1289943.93 | 01-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24875.37 | 1373556.12 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1602.08 | 173815.93 | 16-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 7.21 | 5914.80 | 08-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 356.76 | 298961.19 | 17-AUG-14:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8311.25 | 879185.54 | 19-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27514.18 | 1196868.69 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 94832.70 | 1593802.57 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 224381.05 | 1738826.95 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 90040.34 | ||||
Minimum of Months | 0.00 | 0.00 | 7.21 | 5914.80 | ||
Maximum of Months | 0.00 | 0.00 | 347266.38 | 2060137.74 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 269.87 | 29676.77 | 02-JAN-14:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9472.63 | 521954.04 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13398.26 | 366120.28 | 28-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36813.73 | 865820.51 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74846.09 | 1324833.22 | 19-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 245084.04 | 1941678.68 | 21-JUN-12:23 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 395942.81 | 1864594.33 | 20-JUL-08:53 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 345176.95 | 1955239.90 | 08-AUG-18:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 166997.44 | 2253390.94 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 59474.29 | 1469700.35 | 18-OCT-14:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 13369.61 | 499257.02 | 03-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1942.38 | 45246.72 | 07-DEC-15:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 114399.31 | 0.00 | ||||
Minimum of Months | 269.87 | 29676.77 | 0.00 | 0.00 | ||
Maximum of Months | 395942.81 | 2253390.94 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 191.51 | 26851.49 | 02-JAN-14:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9160.87 | 523669.21 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 12910.01 | 363881.91 | 28-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36122.79 | 871438.86 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75238.87 | 1573823.54 | 19-MAY-16:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 261294.17 | 2141523.97 | 20-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 421640.26 | 2215939.99 | 13-JUL-16:25 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 358613.36 | 2154498.29 | 06-AUG-16:01 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 175184.33 | 2255373.07 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 60762.61 | 1949827.55 | 18-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 12839.74 | 502814.51 | 03-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1617.64 | 44093.26 | 07-DEC-15:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 119671.06 | 0.00 | ||||
Minimum of Months | 191.51 | 26851.49 | 0.00 | 0.00 | ||
Maximum of Months | 421640.26 | 2255373.07 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11992.72 | 33727.24 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 46467.12 | 160217.29 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 79291.43 | 107339.26 | 31-MAR-23:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 160621.39 | 1096566.85 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 70847.71 | 956733.01 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 283864.74 | 1340433.07 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 677055.52 | 1904801.50 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 735123.63 | 1996163.64 | 05-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 153846.91 | 1224630.69 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 77988.41 | 823022.03 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80074.96 | 206425.50 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 97971.15 | 184101.81 | 10-DEC-02:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 207977.28 | 0.00 | ||||
Minimum of Months | 11992.72 | 33727.24 | 0.00 | 0.00 | ||
Maximum of Months | 735123.63 | 1996163.64 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17319.22 | 58863.90 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17697.04 | 59153.24 | 23-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18535.81 | 59051.36 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16872.37 | 57461.46 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16515.47 | 54960.15 | 01-MAY-11:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15923.12 | 51655.97 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 14088.29 | 48666.11 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14975.21 | 46957.09 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14303.50 | 48055.31 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14890.06 | 50863.83 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15937.68 | 54089.46 | 30-NOV-12:55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 16262.26 | 56851.38 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 16100.80 | ||||
Minimum of Months | 0.00 | 0.00 | 14088.29 | 46957.09 | ||
Maximum of Months | 0.00 | 0.00 | 18535.81 | 59153.24 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.20 | 19075.07 | 02-JAN-15:10 | 928.89 | 115796.68 | 03-JAN-16:00 |
February | 9868.81 | 596108.09 | 27-FEB-15:30 | 2562.53 | 117195.33 | 23-FEB-13:40 |
March | 12398.91 | 426346.88 | 28-MAR-16:00 | 3349.42 | 123973.43 | 16-MAR-11:40 |
April | 39174.32 | 974912.66 | 07-APR-14:00 | 3486.46 | 125985.72 | 28-APR-10:50 |
May | 86403.49 | 2085039.98 | 19-MAY-15:40 | 1875.60 | 114470.17 | 10-MAY-08:70 |
June | 313194.94 | 2767829.42 | 20-JUN-13:05 | 1210.24 | 98554.42 | 16-JUN-09:40 |
July | 511479.60 | 2733231.49 | 19-JUL-12:10 | 1303.12 | 68198.15 | 05-JUL-11:00 |
August | 432659.72 | 2145826.75 | 31-AUG-12:03 | 2156.44 | 76378.66 | 30-AUG-07:50 |
September | 217075.56 | 4217875.30 | 07-SEP-15:03 | 1564.14 | 101306.54 | 19-SEP-08:30 |
October | 66311.86 | 1797195.16 | 18-OCT-15:20 | 2608.20 | 115800.67 | 10-OCT-11:50 |
November | 11808.67 | 571663.34 | 03-NOV-14:10 | 3656.34 | 131535.83 | 26-NOV-07:52 |
December | 188.01 | 47296.87 | 07-DEC-13:40 | 3964.46 | 124493.26 | 08-DEC-15:20 |
Annual Sum or Average | 142759.24 | 2386.40 | ||||
Minimum of Months | 16.20 | 19075.07 | 928.89 | 68198.15 | ||
Maximum of Months | 511479.60 | 4217875.30 | 3964.46 | 131535.83 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136899E+11 | 0.87 | 9352.60 | 01-JAN-00:05 | 1.59 |
February | 0.121486E+11 | 0.86 | 9352.60 | 01-FEB-06:03 | 1.60 |
March | 0.146344E+11 | 0.93 | 9352.60 | 01-MAR-05:03 | 1.59 |
April | 0.134224E+11 | 0.88 | 9352.60 | 01-APR-04:11 | 1.60 |
May | 0.144067E+11 | 0.91 | 9352.60 | 01-MAY-03:01 | 1.59 |
June | 0.140962E+11 | 0.92 | 9352.60 | 01-JUN-04:12 | 1.58 |
July | 0.142390E+11 | 0.90 | 9352.60 | 01-JUL-04:12 | 1.58 |
August | 0.153597E+11 | 0.97 | 9352.60 | 01-AUG-04:12 | 1.58 |
September | 0.143057E+11 | 0.93 | 9352.60 | 01-SEP-04:12 | 1.58 |
October | 0.140336E+11 | 0.89 | 9352.60 | 02-OCT-04:11 | 1.59 |
November | 0.135392E+11 | 0.89 | 9352.60 | 01-NOV-04:11 | 1.59 |
December | 0.134261E+11 | 0.85 | 9352.60 | 01-DEC-05:01 | 1.60 |
Annual Sum or Average | 0.167301E+12 | 0.90 | |||
Minimum of Months | 0.121486E+11 | 0.85 | 9352.60 | 1.58 | |
Maximum of Months | 0.153597E+11 | 0.97 | 9352.60 | 1.60 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.305350E+10 | 0.37 | 10649.99 | 05-JAN-06:01 | 1.33 |
February | 0.365330E+10 | 0.40 | 13446.57 | 24-FEB-06:01 | 1.53 |
March | 0.579970E+10 | 0.45 | 14085.82 | 28-MAR-15:50 | 1.58 |
April | 0.792999E+10 | 0.53 | 19927.75 | 24-APR-15:10 | 1.95 |
May | 0.726889E+10 | 0.50 | 16671.96 | 30-MAY-05:03 | 1.73 |
June | 0.124587E+11 | 0.69 | 22815.49 | 06-JUN-13:50 | 2.11 |
July | 0.168906E+11 | 0.84 | 22815.49 | 03-JUL-08:37 | 2.11 |
August | 0.176094E+11 | 0.89 | 22815.49 | 01-AUG-10:30 | 2.11 |
September | 0.840156E+10 | 0.55 | 22815.49 | 01-SEP-10:00 | 2.12 |
October | 0.687804E+10 | 0.47 | 19054.29 | 18-OCT-14:00 | 1.90 |
November | 0.526285E+10 | 0.42 | 13053.84 | 06-NOV-15:00 | 1.50 |
December | 0.427480E+10 | 0.38 | 13446.57 | 16-DEC-06:01 | 1.53 |
Annual Sum or Average | 0.994814E+11 | 0.54 | |||
Minimum of Months | 0.305350E+10 | 0.37 | 10649.99 | 1.33 | |
Maximum of Months | 0.176094E+11 | 0.89 | 22815.49 | 2.12 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.311268E+11 | 0.42 | 64980.61 | 02-JAN-06:01 | 1.04 |
February | 0.272609E+11 | 0.40 | 69034.99 | 28-FEB-16:20 | 1.08 |
March | 0.338830E+11 | 0.40 | 85041.81 | 24-MAR-05:02 | 1.22 |
April | 0.398198E+11 | 0.39 | 144925.94 | 19-APR-05:02 | 1.68 |
May | 0.515741E+11 | 0.44 | 162435.28 | 19-MAY-15:20 | 1.80 |
June | 0.936837E+11 | 0.60 | 211049.23 | 06-JUN-13:50 | 2.12 |
July | 0.123090E+12 | 0.68 | 211049.23 | 03-JUL-08:45 | 2.12 |
August | 0.116055E+12 | 0.66 | 211049.23 | 01-AUG-12:40 | 2.12 |
September | 0.630733E+11 | 0.49 | 211049.23 | 01-SEP-10:25 | 2.13 |
October | 0.402720E+11 | 0.38 | 130573.17 | 05-OCT-05:02 | 1.58 |
November | 0.297379E+11 | 0.37 | 122832.96 | 09-NOV-06:02 | 1.52 |
December | 0.283353E+11 | 0.40 | 64980.61 | 26-DEC-05:01 | 1.04 |
Annual Sum or Average | 0.677912E+12 | 0.47 | |||
Minimum of Months | 0.272609E+11 | 0.37 | 64980.61 | 1.04 | |
Maximum of Months | 0.123090E+12 | 0.68 | 211049.23 | 2.13 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.424627E+10 | 0.53 | 5755.60 | 02-JAN-04:11 | 0.89 |
February | 0.325485E+10 | 0.47 | 5755.60 | 01-FEB-05:01 | 0.89 |
March | 0.348446E+10 | 0.45 | 5755.60 | 03-MAR-06:01 | 0.89 |
April | 0.339623E+10 | 0.40 | 11492.79 | 25-APR-15:40 | 1.33 |
May | 0.461913E+10 | 0.43 | 24461.60 | 19-MAY-15:10 | 2.11 |
June | 0.875740E+10 | 0.55 | 24461.60 | 06-JUN-13:50 | 2.11 |
July | 0.122202E+11 | 0.62 | 24461.60 | 03-JUL-13:50 | 2.11 |
August | 0.107165E+11 | 0.59 | 24461.60 | 01-AUG-12:55 | 2.11 |
September | 0.529774E+10 | 0.45 | 24461.60 | 01-SEP-14:05 | 2.11 |
October | 0.324711E+10 | 0.38 | 8989.92 | 18-OCT-16:00 | 1.15 |
November | 0.318227E+10 | 0.44 | 5755.60 | 06-NOV-06:01 | 0.89 |
December | 0.379643E+10 | 0.51 | 5755.60 | 01-DEC-05:01 | 0.89 |
Annual Sum or Average | 0.662185E+11 | 0.49 | |||
Minimum of Months | 0.318227E+10 | 0.38 | 5755.60 | 0.89 | |
Maximum of Months | 0.122202E+11 | 0.62 | 24461.60 | 2.11 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107480E+12 | 1.54 | 40128.55 | 01-JAN-00:05 | 1.54 |
February | 0.970790E+11 | 1.54 | 40128.55 | 01-FEB-00:10 | 1.54 |
March | 0.107480E+12 | 1.55 | 40128.55 | 01-MAR-00:10 | 1.54 |
April | 0.104013E+12 | 1.55 | 40128.55 | 01-APR-00:10 | 1.55 |
May | 0.107480E+12 | 1.54 | 40128.55 | 01-MAY-00:05 | 1.54 |
June | 0.104013E+12 | 1.54 | 40128.55 | 01-JUN-00:10 | 1.54 |
July | 0.107480E+12 | 1.54 | 40128.55 | 01-JUL-00:05 | 1.53 |
August | 0.107480E+12 | 1.54 | 40128.55 | 01-AUG-00:10 | 1.54 |
September | 0.104013E+12 | 1.54 | 40128.55 | 01-SEP-00:05 | 1.54 |
October | 0.107480E+12 | 1.54 | 40128.55 | 01-OCT-00:10 | 1.54 |
November | 0.104013E+12 | 1.55 | 40128.55 | 01-NOV-00:10 | 1.55 |
December | 0.107480E+12 | 1.55 | 40128.55 | 01-DEC-00:10 | 1.55 |
Annual Sum or Average | 0.126549E+13 | 1.54 | |||
Minimum of Months | 0.970790E+11 | 1.54 | 40128.55 | 1.53 | |
Maximum of Months | 0.107480E+12 | 1.55 | 40128.55 | 1.55 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167566E+10 | 1.05 | 625.62 | 01-JAN-00:05 | 1.05 |
February | 0.151350E+10 | 1.05 | 625.62 | 01-FEB-00:10 | 1.05 |
March | 0.167566E+10 | 1.05 | 625.62 | 01-MAR-00:10 | 1.05 |
April | 0.162161E+10 | 1.05 | 625.62 | 01-APR-00:10 | 1.05 |
May | 0.167566E+10 | 1.05 | 625.62 | 01-MAY-00:05 | 1.05 |
June | 0.162161E+10 | 1.05 | 625.62 | 01-JUN-00:10 | 1.05 |
July | 0.167566E+10 | 1.05 | 625.62 | 01-JUL-00:05 | 1.05 |
August | 0.167566E+10 | 1.05 | 625.62 | 01-AUG-00:10 | 1.05 |
September | 0.162161E+10 | 1.05 | 625.62 | 01-SEP-00:05 | 1.05 |
October | 0.167566E+10 | 1.05 | 625.62 | 01-OCT-00:10 | 1.05 |
November | 0.162161E+10 | 1.05 | 625.62 | 01-NOV-00:10 | 1.05 |
December | 0.167566E+10 | 1.05 | 625.62 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.197295E+11 | 1.05 | |||
Minimum of Months | 0.151350E+10 | 1.05 | 625.62 | 1.05 | |
Maximum of Months | 0.167566E+10 | 1.05 | 625.62 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161072E+11 | 1.05 | 6013.74 | 01-JAN-00:05 | 1.05 |
February | 0.145484E+11 | 1.05 | 6013.74 | 01-FEB-00:10 | 1.05 |
March | 0.161072E+11 | 1.05 | 6013.74 | 01-MAR-00:10 | 1.05 |
April | 0.155876E+11 | 1.05 | 6013.74 | 01-APR-00:10 | 1.05 |
May | 0.161072E+11 | 1.05 | 6013.74 | 01-MAY-00:05 | 1.05 |
June | 0.155876E+11 | 1.05 | 6013.74 | 01-JUN-00:10 | 1.05 |
July | 0.161072E+11 | 1.05 | 6013.74 | 01-JUL-00:05 | 1.05 |
August | 0.161072E+11 | 1.05 | 6013.74 | 01-AUG-00:10 | 1.05 |
September | 0.155876E+11 | 1.05 | 6013.74 | 01-SEP-00:05 | 1.05 |
October | 0.161072E+11 | 1.05 | 6013.74 | 01-OCT-00:10 | 1.05 |
November | 0.155876E+11 | 1.05 | 6013.74 | 01-NOV-00:10 | 1.05 |
December | 0.161072E+11 | 1.05 | 6013.74 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.189649E+12 | 1.05 | |||
Minimum of Months | 0.145484E+11 | 1.05 | 6013.74 | 1.05 | |
Maximum of Months | 0.161072E+11 | 1.05 | 6013.74 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163972E+10 | 1.05 | 612.20 | 01-JAN-00:05 | 1.04 |
February | 0.148104E+10 | 1.05 | 612.20 | 01-FEB-00:10 | 1.05 |
March | 0.163972E+10 | 1.05 | 612.20 | 01-MAR-00:10 | 1.05 |
April | 0.158683E+10 | 1.05 | 612.20 | 01-APR-00:10 | 1.05 |
May | 0.163972E+10 | 1.05 | 612.20 | 01-MAY-00:05 | 1.05 |
June | 0.158683E+10 | 1.05 | 612.20 | 01-JUN-00:10 | 1.05 |
July | 0.163972E+10 | 1.05 | 612.20 | 01-JUL-00:05 | 1.05 |
August | 0.163972E+10 | 1.05 | 612.20 | 01-AUG-00:10 | 1.05 |
September | 0.158683E+10 | 1.05 | 612.20 | 01-SEP-00:05 | 1.05 |
October | 0.163972E+10 | 1.05 | 612.20 | 01-OCT-00:10 | 1.05 |
November | 0.158683E+10 | 1.05 | 612.20 | 01-NOV-00:10 | 1.05 |
December | 0.163972E+10 | 1.05 | 612.20 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.193064E+11 | 1.05 | |||
Minimum of Months | 0.148104E+10 | 1.05 | 612.20 | 1.04 | |
Maximum of Months | 0.163972E+10 | 1.05 | 612.20 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.290813E+09 | 0.264349E+09 | 2076.29 | 09-JAN-07:10 | 1887.35 | 1887.35 | 49.30 | 14.93 |
February | 83006135.77 | 75452577.41 | 1123.42 | 04-FEB-06:01 | 1021.19 | 1021.19 | 47.90 | 11.50 |
March | 32539672.64 | 29578562.43 | 1128.91 | 06-MAR-06:01 | 1026.18 | 1026.18 | 48.04 | 11.52 |
April | 4979987.65 | 4526808.78 | 409.26 | 29-APR-05:01 | 372.02 | 372.02 | 42.75 | 7.32 |
May | 3738441.08 | 3398242.94 | 400.72 | 09-MAY-05:01 | 364.25 | 364.25 | 42.23 | 7.25 |
June | 138024.22 | 125464.02 | 7.51 | 16-JUN-07:00 | 6.83 | 6.83 | 27.09 | 0.76 |
July | 494.49 | 449.50 | 0.15 | 08-JUL-06:10 | 0.14 | 0.14 | 24.11 | 0.02 |
August | 30641.08 | 27852.74 | 15.65 | 17-AUG-14:00 | 14.23 | 14.23 | 24.75 | 1.25 |
September | 824300.43 | 749289.09 | 145.21 | 19-SEP-05:02 | 131.99 | 131.99 | 34.58 | 4.44 |
October | 3833866.09 | 3484984.27 | 332.93 | 11-OCT-05:01 | 302.63 | 302.63 | 39.70 | 6.65 |
November | 23414451.95 | 21283736.83 | 1114.96 | 27-NOV-06:02 | 1013.50 | 1013.50 | 48.72 | 11.45 |
December | 0.111346E+09 | 0.101214E+09 | 1221.31 | 29-DEC-08:00 | 1110.17 | 1110.17 | 51.54 | 11.90 |
Annual Sum or Average | 0.554665E+09 | 0.504191E+09 | ||||||
Minimum of Months | 494.49 | 449.50 | 0.15 | 0.14 | 0.14 | 24.11 | 0.02 | |
Maximum of Months | 0.290813E+09 | 0.264349E+09 | 2076.29 | 1887.35 | 1887.35 | 51.54 | 14.93 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 61722.82 | 56106.04 | 3.02 | 02-JAN-14:10 | 2.75 | 2.75 | 6.70 | 0.72 |
February | 9399586.24 | 8544223.89 | 388.29 | 27-FEB-14:00 | 352.96 | 352.96 | 6.71 | 14.67 |
March | 10436164.55 | 9486473.57 | 246.98 | 01-MAR-15:10 | 224.50 | 224.50 | 6.70 | 11.79 |
April | 38150891.20 | 34679160.10 | 857.76 | 06-APR-14:05 | 779.70 | 779.70 | 6.71 | 21.14 |
May | 0.256774E+09 | 0.233408E+09 | 8569.12 | 19-MAY-15:30 | 7789.33 | 7789.33 | 6.73 | 55.34 |
June | 0.157466E+10 | 0.143137E+10 | 9289.23 | 06-JUN-13:45 | 8443.91 | 8443.91 | 9.65 | 57.12 |
July | 0.359429E+10 | 0.326721E+10 | 9289.23 | 03-JUL-08:30 | 8443.91 | 8443.91 | 9.35 | 57.12 |
August | 0.324146E+10 | 0.294649E+10 | 9289.23 | 01-AUG-12:40 | 8443.91 | 8443.91 | 9.89 | 57.12 |
September | 0.126472E+10 | 0.114963E+10 | 9289.23 | 05-SEP-12:05 | 8443.91 | 8443.91 | 10.49 | 57.12 |
October | 0.155551E+09 | 0.141396E+09 | 9113.61 | 18-OCT-14:00 | 8284.27 | 8284.27 | 10.79 | 56.68 |
November | 11038130.94 | 10033661.02 | 509.45 | 03-NOV-14:05 | 463.09 | 463.09 | 6.71 | 16.66 |
December | 413175.37 | 375576.41 | 4.81 | 07-DEC-15:30 | 4.37 | 4.37 | 6.70 | 1.05 |
Annual Sum or Average | 0.101570E+11 | 0.923268E+10 | ||||||
Minimum of Months | 61722.82 | 56106.04 | 3.02 | 2.75 | 2.75 | 6.70 | 0.72 | |
Maximum of Months | 0.359429E+10 | 0.326721E+10 | 9289.23 | 8443.91 | 8443.91 | 10.79 | 57.12 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.231318E+09 | 0.210268E+09 | 3196.76 | 02-JAN-10:05 | 2905.86 | 2905.86 | 6.72 | 28.56 |
February | 0.850083E+09 | 0.772725E+09 | 3196.76 | 01-FEB-02:17 | 2905.86 | 2905.86 | 6.72 | 28.56 |
March | 0.146067E+10 | 0.132775E+10 | 3196.76 | 01-MAR-06:20 | 2905.86 | 2905.86 | 6.73 | 28.56 |
April | 0.207194E+10 | 0.188339E+10 | 3196.76 | 01-APR-12:23 | 2905.86 | 2905.86 | 6.73 | 28.56 |
May | 0.270614E+10 | 0.245988E+10 | 3196.76 | 01-MAY-07:13 | 2905.86 | 2905.86 | 6.73 | 28.56 |
June | 0.434876E+10 | 0.395302E+10 | 3196.76 | 01-JUN-04:12 | 2905.86 | 2905.86 | 7.90 | 28.56 |
July | 0.598889E+10 | 0.544390E+10 | 3196.76 | 01-JUL-00:25 | 2905.86 | 2905.86 | 6.86 | 28.56 |
August | 0.571979E+10 | 0.519929E+10 | 3196.76 | 01-AUG-00:10 | 2905.86 | 2905.86 | 6.86 | 28.56 |
September | 0.366029E+10 | 0.332721E+10 | 3196.76 | 01-SEP-00:15 | 2905.86 | 2905.86 | 6.80 | 28.56 |
October | 0.258229E+10 | 0.234730E+10 | 3196.76 | 02-OCT-05:10 | 2905.86 | 2905.86 | 6.78 | 28.56 |
November | 0.153157E+10 | 0.139220E+10 | 3196.76 | 01-NOV-04:11 | 2905.86 | 2905.86 | 7.03 | 28.56 |
December | 0.957111E+09 | 0.870014E+09 | 3196.76 | 01-DEC-10:10 | 2905.86 | 2905.86 | 6.73 | 28.56 |
Annual Sum or Average | 0.321089E+11 | 0.291869E+11 | ||||||
Minimum of Months | 0.231318E+09 | 0.210268E+09 | 3196.76 | 2905.86 | 2905.86 | 6.72 | 28.56 | |
Maximum of Months | 0.598889E+10 | 0.544390E+10 | 3196.76 | 2905.86 | 2905.86 | 7.90 | 28.56 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.76 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 79599380.15 | 72355836.55 | 3196.76 | 19-MAY-12:10 | 2905.86 | 2905.86 | 15.23 | 14.28 |
June | 0.736534E+09 | 0.669509E+09 | 3196.76 | 05-JUN-12:40 | 2905.86 | 2905.86 | 15.52 | 14.28 |
July | 0.153282E+10 | 0.139333E+10 | 3196.76 | 03-JUL-09:55 | 2905.86 | 2905.86 | 12.92 | 28.56 |
August | 0.134296E+10 | 0.122075E+10 | 3196.76 | 03-AUG-13:50 | 2905.86 | 2905.86 | 15.22 | 14.28 |
September | 0.390325E+09 | 0.354805E+09 | 3196.76 | 01-SEP-09:50 | 2905.86 | 2905.86 | 15.42 | 14.28 |
October | 23016688.23 | 20922169.61 | 3196.76 | 18-OCT-14:05 | 2905.86 | 2905.86 | 12.84 | 28.56 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.80 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
Annual Sum or Average | 0.410525E+10 | 0.373167E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.153282E+10 | 0.139333E+10 | 3196.76 | 2905.86 | 2905.86 | 15.52 | 28.56 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.964223E+10 | 0.876479E+10 | 3600.00 | 01-JAN-00:05 | 3272.40 | 3272.40 | 18.54 | 15.19 |
February | 0.870911E+10 | 0.791658E+10 | 3600.00 | 01-FEB-00:10 | 3272.40 | 3272.40 | 19.04 | 15.19 |
March | 0.964223E+10 | 0.876479E+10 | 3600.00 | 01-MAR-00:10 | 3272.40 | 3272.40 | 19.89 | 15.19 |
April | 0.933119E+10 | 0.848205E+10 | 3600.00 | 01-APR-00:10 | 3272.40 | 3272.40 | 20.36 | 15.19 |
May | 0.964223E+10 | 0.876479E+10 | 3600.00 | 01-MAY-00:05 | 3272.40 | 3272.40 | 18.80 | 15.19 |
June | 0.933119E+10 | 0.848205E+10 | 3600.00 | 01-JUN-00:10 | 3272.40 | 3272.40 | 19.54 | 15.19 |
July | 0.964223E+10 | 0.876479E+10 | 3600.00 | 01-JUL-00:05 | 3272.40 | 3272.40 | 27.81 | 15.19 |
August | 0.964223E+10 | 0.876479E+10 | 3600.00 | 01-AUG-00:10 | 3272.40 | 3272.40 | 31.37 | 15.19 |
September | 0.933119E+10 | 0.848205E+10 | 3600.00 | 01-SEP-00:05 | 3272.40 | 3272.40 | 19.57 | 15.19 |
October | 0.964223E+10 | 0.876479E+10 | 3600.00 | 01-OCT-00:10 | 3272.40 | 3272.40 | 19.51 | 15.19 |
November | 0.933119E+10 | 0.848205E+10 | 3600.00 | 01-NOV-00:10 | 3272.40 | 3272.40 | 19.87 | 15.19 |
December | 0.964223E+10 | 0.876479E+10 | 3600.00 | 01-DEC-00:10 | 3272.40 | 3272.40 | 20.17 | 15.19 |
Annual Sum or Average | 0.113530E+12 | 0.103198E+12 | ||||||
Minimum of Months | 0.870911E+10 | 0.791658E+10 | 3600.00 | 3272.40 | 3272.40 | 18.54 | 15.19 | |
Maximum of Months | 0.964223E+10 | 0.876479E+10 | 3600.00 | 3272.40 | 3272.40 | 31.37 | 15.19 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 55.36 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.05 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.89 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 55.94 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 55.88 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.36 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.77 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.49 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.66 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.05 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.60 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.24 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.36 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.77 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.897195E+09 | 0.815551E+09 | 12401.27 | 02-JAN-15:10 | 11272.76 | 11272.76 | 21.19 | 50.76 |
February | 0.329828E+10 | 0.299813E+10 | 12425.56 | 27-FEB-15:30 | 11294.83 | 11294.83 | 23.91 | 50.76 |
March | 0.566708E+10 | 0.515137E+10 | 12418.40 | 28-MAR-16:00 | 11288.33 | 11288.33 | 23.11 | 50.76 |
April | 0.804109E+10 | 0.730935E+10 | 12442.57 | 07-APR-14:00 | 11310.30 | 11310.30 | 25.70 | 50.76 |
May | 0.108156E+11 | 0.983141E+10 | 24891.85 | 19-MAY-15:40 | 22626.69 | 22626.69 | 26.01 | 101.51 |
June | 0.196975E+11 | 0.179050E+11 | 24925.47 | 20-JUN-13:05 | 22657.26 | 22657.26 | 27.62 | 101.51 |
July | 0.291129E+11 | 0.264636E+11 | 24923.77 | 19-JUL-12:10 | 22655.71 | 22655.71 | 27.54 | 101.51 |
August | 0.273306E+11 | 0.248436E+11 | 24894.84 | 31-AUG-12:03 | 22629.41 | 22629.41 | 26.16 | 101.51 |
September | 0.156992E+11 | 0.142706E+11 | 24950.27 | 07-SEP-14:30 | 22679.80 | 22679.80 | 29.40 | 101.51 |
October | 0.101134E+11 | 0.919305E+10 | 24877.70 | 18-OCT-15:20 | 22613.83 | 22613.83 | 25.34 | 101.51 |
November | 0.594195E+10 | 0.540124E+10 | 12424.53 | 03-NOV-14:10 | 11293.89 | 11293.89 | 23.79 | 50.76 |
December | 0.371228E+10 | 0.337446E+10 | 12402.46 | 07-DEC-13:40 | 11273.83 | 11273.83 | 21.32 | 50.76 |
Annual Sum or Average | 0.140327E+12 | 0.127557E+12 | ||||||
Minimum of Months | 0.897195E+09 | 0.815551E+09 | 12401.27 | 11272.76 | 11272.76 | 21.19 | 50.76 | |
Maximum of Months | 0.291129E+11 | 0.264636E+11 | 24950.27 | 22679.80 | 22679.80 | 29.40 | 101.51 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 43.98 | 82.00 | 347266.38 | 2060137.74 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 36.79 | 36.79 | 202249.87 | 1717391.72 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29.19 | 29.19 | 114578.85 | 1635490.26 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.92 | 29.92 | 38365.78 | 1289943.93 | 01-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25.52 | 82.00 | 24875.37 | 1373556.12 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.08 | 24.08 | 1602.08 | 173815.93 | 16-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 24.25 | 24.25 | 7.21 | 5914.80 | 08-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24.07 | 24.07 | 356.76 | 298961.19 | 17-AUG-14:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.81 | 23.81 | 8311.25 | 879185.54 | 19-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.36 | 22.36 | 27514.18 | 1196868.69 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 30.30 | 30.30 | 94832.70 | 1593802.57 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 34.43 | 34.43 | 224381.05 | 1738826.95 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 90040.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.36 | 22.36 | 7.21 | 5914.80 | ||
Maximum of Months | 0.00 | 0.00 | 43.98 | 82.00 | 347266.38 | 2060137.74 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 269.87 | 29676.77 | 02-JAN-14:20 | 6.95 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9472.63 | 521954.04 | 27-FEB-15:30 | 11.06 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13398.26 | 366120.28 | 28-MAR-16:00 | 9.76 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36813.73 | 865820.51 | 07-APR-14:00 | 13.94 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74846.09 | 1324833.22 | 19-MAY-12:20 | 12.24 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 245084.04 | 1941678.68 | 21-JUN-12:23 | 14.82 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 395942.81 | 1864594.33 | 20-JUL-08:53 | 14.50 | 6.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 345176.95 | 1955239.90 | 08-AUG-18:10 | 14.88 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 166997.44 | 2253390.94 | 07-SEP-15:00 | 16.13 | 7.65 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 59474.29 | 1469700.35 | 18-OCT-14:05 | 12.84 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 13369.61 | 499257.02 | 03-NOV-14:10 | 10.87 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1942.38 | 45246.72 | 07-DEC-15:30 | 7.08 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 114399.31 | 0.00 | ||||||
Minimum of Months | 269.87 | 29676.77 | 6.95 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 395942.81 | 2253390.94 | 16.13 | 7.65 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 191.51 | 26851.49 | 02-JAN-14:20 | 15.58 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9160.87 | 523669.21 | 27-FEB-15:30 | 15.86 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 12910.01 | 363881.91 | 28-MAR-16:00 | 16.48 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36122.79 | 871438.86 | 07-APR-14:00 | 16.67 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75238.87 | 1573823.54 | 19-MAY-16:30 | 15.76 | 9.51 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 261294.17 | 2141523.97 | 20-JUN-11:00 | 15.73 | 11.17 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 421640.26 | 2215939.99 | 13-JUL-16:25 | 15.97 | 11.32 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 358613.36 | 2154498.29 | 06-AUG-16:01 | 16.27 | 11.18 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 175184.33 | 2255373.07 | 07-SEP-15:00 | 16.28 | 7.62 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 60762.61 | 1949827.55 | 18-OCT-14:00 | 14.92 | 10.77 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 12839.74 | 502814.51 | 03-NOV-14:05 | 13.91 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1617.64 | 44093.26 | 07-DEC-15:30 | 16.71 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 119671.06 | 0.00 | ||||||
Minimum of Months | 191.51 | 26851.49 | 13.91 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 421640.26 | 2255373.07 | 16.71 | 11.32 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11992.72 | 33727.24 | 13-JAN-16:30 | 18.97 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 46467.12 | 160217.29 | 27-FEB-16:00 | 21.37 | 19.75 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 79291.43 | 107339.26 | 31-MAR-23:30 | 20.37 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 160621.39 | 1096566.85 | 07-APR-14:00 | 38.78 | 28.75 | 0.00 | 0.00 | 01-APR-00:10 |
May | 70847.71 | 956733.01 | 20-MAY-16:00 | 36.22 | 32.18 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 283864.74 | 1340433.07 | 29-JUN-15:00 | 43.22 | 36.10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 677055.52 | 1904801.50 | 17-JUL-16:00 | 53.37 | 42.98 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 735123.63 | 1996163.64 | 05-AUG-16:00 | 55.00 | 42.54 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 153846.91 | 1224630.69 | 02-SEP-17:00 | 41.12 | 36.77 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 77988.41 | 823022.03 | 18-OCT-15:00 | 33.75 | 28.07 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80074.96 | 206425.50 | 17-NOV-17:00 | 22.24 | 18.95 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 97971.15 | 184101.81 | 10-DEC-02:00 | 21.82 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 207977.28 | 0.00 | ||||||
Minimum of Months | 11992.72 | 33727.24 | 18.97 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 735123.63 | 1996163.64 | 55.00 | 42.98 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.82 | 56.82 | 17319.22 | 58863.90 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.72 | 56.72 | 17697.04 | 59153.24 | 23-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.61 | 56.61 | 18535.81 | 59051.36 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.26 | 56.26 | 16872.37 | 57461.46 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 56.88 | 56.88 | 16515.47 | 54960.15 | 01-MAY-11:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.97 | 56.97 | 15923.12 | 51655.97 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.17 | 57.17 | 14088.29 | 48666.11 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.07 | 57.07 | 14975.21 | 46957.09 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.21 | 57.21 | 14303.50 | 48055.31 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.10 | 57.10 | 14890.06 | 50863.83 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.17 | 57.17 | 15937.68 | 54089.46 | 30-NOV-12:55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.73 | 56.73 | 16262.26 | 56851.38 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 16100.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.26 | 56.26 | 14088.29 | 46957.09 | ||
Maximum of Months | 0.00 | 0.00 | 57.21 | 57.21 | 18535.81 | 59153.24 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.20 | 19075.07 | 02-JAN-15:10 | 21.19 | 20.32 | 928.89 | 115796.68 | 03-JAN-16:00 |
February | 9868.81 | 596108.09 | 27-FEB-15:30 | 23.91 | 21.10 | 2562.53 | 117195.33 | 23-FEB-13:40 |
March | 12398.91 | 426346.88 | 28-MAR-16:00 | 23.11 | 21.10 | 3349.42 | 123973.43 | 16-MAR-11:40 |
April | 39174.32 | 974912.66 | 07-APR-14:00 | 25.70 | 21.10 | 3486.46 | 125985.72 | 28-APR-10:50 |
May | 86403.49 | 2085039.98 | 19-MAY-15:40 | 26.01 | 21.10 | 1875.60 | 114470.17 | 10-MAY-08:70 |
June | 313194.94 | 2767829.42 | 20-JUN-13:05 | 27.62 | 23.09 | 1210.24 | 98554.42 | 16-JUN-09:40 |
July | 511479.60 | 2733231.49 | 19-JUL-12:10 | 27.54 | 23.44 | 1303.12 | 68198.15 | 05-JUL-11:00 |
August | 432659.72 | 2145826.75 | 31-AUG-12:03 | 26.16 | 21.30 | 2156.44 | 76378.66 | 30-AUG-07:50 |
September | 217075.56 | 4217875.30 | 07-SEP-15:03 | 31.04 | 25.50 | 1564.14 | 101306.54 | 19-SEP-08:30 |
October | 66311.86 | 1797195.16 | 18-OCT-15:20 | 25.34 | 21.10 | 2608.20 | 115800.67 | 10-OCT-11:50 |
November | 11808.67 | 571663.34 | 03-NOV-14:10 | 23.79 | 21.10 | 3656.34 | 131535.83 | 26-NOV-07:52 |
December | 188.01 | 47296.87 | 07-DEC-13:40 | 21.32 | 20.51 | 3964.46 | 124493.26 | 08-DEC-15:20 |
Annual Sum or Average | 142759.24 | 2386.40 | ||||||
Minimum of Months | 16.20 | 19075.07 | 21.19 | 20.32 | 928.89 | 68198.15 | ||
Maximum of Months | 511479.60 | 4217875.30 | 31.04 | 25.50 | 3964.46 | 131535.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.510892E+11 | 0.00 | 0.648927E+09 | 0.305350E+10 | 0.00 | 0.00 |
February | 0.262046E+11 | 0.00 | 0.359370E+10 | 0.365330E+10 | 0.00 | 0.00 |
March | 0.140349E+11 | 0.00 | 0.562545E+10 | 0.579970E+10 | 0.00 | 0.00 |
April | 0.333290E+10 | 0.00 | 0.808496E+10 | 0.792999E+10 | 0.00 | 0.00 |
May | 0.243030E+10 | 0.00 | 0.175451E+11 | 0.726889E+10 | 0.00 | 0.00 |
June | 92441743.28 | 0.00 | 0.565943E+11 | 0.124587E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.965038E+11 | 0.168906E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.881294E+11 | 0.176094E+11 | 0.00 | 0.00 |
September | 0.690867E+09 | 0.00 | 0.378222E+11 | 0.840156E+10 | 0.00 | 0.00 |
October | 0.288410E+10 | 0.00 | 0.147715E+11 | 0.687804E+10 | 0.00 | 0.00 |
November | 0.101510E+11 | 0.00 | 0.897770E+10 | 0.526285E+10 | 0.00 | 0.00 |
December | 0.276174E+11 | 0.00 | 0.437107E+10 | 0.427480E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138528E+12 | 0.00 | 0.342668E+12 | 0.994814E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.648927E+09 | 0.305350E+10 | 0.00 | 0.00 |
Maximum of Months | 0.510892E+11 | 0.00 | 0.965038E+11 | 0.176094E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.763660E+12 | 0.00 | 18472.87 | 0.311268E+11 | 0.00 | 0.00 |
February | 0.403903E+12 | 0.00 | 0.176101E+11 | 0.272609E+11 | 0.00 | 0.00 |
March | 0.252944E+12 | 0.00 | 0.278900E+11 | 0.338830E+11 | 0.00 | 0.00 |
April | 0.826304E+11 | 0.00 | 0.790463E+11 | 0.398198E+11 | 0.00 | 0.00 |
May | 0.542776E+11 | 0.00 | 0.156529E+12 | 0.515741E+11 | 0.00 | 0.00 |
June | 0.332042E+10 | 0.00 | 0.482315E+12 | 0.936837E+11 | 0.00 | 0.00 |
July | 1826836.82 | 0.00 | 0.806670E+12 | 0.123090E+12 | 0.00 | 0.00 |
August | 0.681887E+09 | 0.00 | 0.698662E+12 | 0.116055E+12 | 0.00 | 0.00 |
September | 0.173517E+11 | 0.00 | 0.337933E+12 | 0.630733E+11 | 0.00 | 0.00 |
October | 0.592567E+11 | 0.00 | 0.130250E+12 | 0.402720E+11 | 0.00 | 0.00 |
November | 0.199138E+12 | 0.00 | 0.238565E+11 | 0.297379E+11 | 0.00 | 0.00 |
December | 0.494054E+12 | 0.00 | 5706452.74 | 0.283353E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.233122E+13 | 0.00 | 0.276077E+13 | 0.677912E+12 | 0.00 | 0.00 |
Minimum of Months | 1826836.82 | 0.00 | 18472.87 | 0.272609E+11 | 0.00 | 0.00 |
Maximum of Months | 0.763660E+12 | 0.00 | 0.806670E+12 | 0.123090E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.118513E+12 | 0.00 | 7235.46 | 0.424627E+10 | 0.00 | 0.00 |
February | 0.617302E+11 | 0.00 | 0.750984E+09 | 0.325485E+10 | 0.00 | 0.00 |
March | 0.414966E+11 | 0.00 | 0.115081E+10 | 0.348446E+10 | 0.00 | 0.00 |
April | 0.140255E+11 | 0.00 | 0.451285E+10 | 0.339623E+10 | 0.00 | 0.00 |
May | 0.102727E+11 | 0.00 | 0.150073E+11 | 0.461913E+10 | 0.00 | 0.00 |
June | 0.760330E+09 | 0.00 | 0.523869E+11 | 0.875740E+10 | 0.00 | 0.00 |
July | 18781437.01 | 0.00 | 0.888580E+11 | 0.122202E+11 | 0.00 | 0.00 |
August | 0.280345E+09 | 0.00 | 0.748657E+11 | 0.107165E+11 | 0.00 | 0.00 |
September | 0.362276E+10 | 0.00 | 0.325942E+11 | 0.529774E+10 | 0.00 | 0.00 |
October | 0.118854E+11 | 0.00 | 0.665796E+10 | 0.324711E+10 | 0.00 | 0.00 |
November | 0.377631E+11 | 0.00 | 0.422306E+09 | 0.318227E+10 | 0.00 | 0.00 |
December | 0.823758E+11 | 0.00 | 0.00 | 0.379643E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.382745E+12 | 0.00 | 0.277207E+12 | 0.662185E+11 | 0.00 | 0.00 |
Minimum of Months | 18781437.01 | 0.00 | 0.00 | 0.318227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118513E+12 | 0.00 | 0.888580E+11 | 0.122202E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.178079E+10 | 0.00 | 334457.24 | 0.136899E+11 | 0.00 | 0.00 |
February | 48972517.39 | 0.00 | 0.262399E+09 | 0.121486E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 55797.28 | 0.146344E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.204208E+10 | 0.134224E+11 | 0.00 | 0.00 |
May | 157.27 | 0.00 | 0.773335E+10 | 0.144067E+11 | 0.00 | 0.00 |
June | 262.11 | 0.00 | 0.277385E+11 | 0.140962E+11 | 0.00 | 0.00 |
July | 85.09 | 0.00 | 0.474299E+11 | 0.142390E+11 | 0.00 | 0.00 |
August | 122.41 | 0.00 | 0.438544E+11 | 0.153597E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.181207E+11 | 0.143057E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.518394E+10 | 0.140336E+11 | 0.00 | 0.00 |
November | 112.35 | 0.00 | 63463694.89 | 0.135392E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 11486.92 | 0.134261E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.182976E+10 | 0.00 | 0.152429E+12 | 0.167301E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 11486.92 | 0.121486E+11 | 0.00 | 0.00 |
Maximum of Months | 0.178079E+10 | 0.00 | 0.474299E+11 | 0.153597E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.133751E+11 | 0.270834E+12 | 0.00 | 59.10 |
February | 0.00 | 0.00 | 0.191336E+11 | 0.335322E+12 | 0.00 | 86.55 |
March | 0.00 | 0.00 | 0.216433E+11 | 0.381850E+12 | 0.00 | 99.64 |
April | 0.00 | 0.00 | 0.995208E+11 | 0.385783E+12 | 0.00 | 95.99 |
May | 0.00 | 0.00 | 0.254205E+11 | 0.273580E+12 | 0.00 | 59.01 |
June | 0.00 | 0.00 | 0.179211E+12 | 0.285000E+12 | 0.00 | 51.30 |
July | 0.00 | 0.00 | 0.585671E+12 | 0.357476E+12 | 0.00 | 41.83 |
August | 0.00 | 0.00 | 0.741972E+12 | 0.502681E+12 | 0.00 | 83.50 |
September | 0.00 | 0.00 | 0.613251E+11 | 0.228346E+12 | 0.00 | 40.19 |
October | 0.00 | 0.00 | 0.338107E+11 | 0.362550E+12 | 0.00 | 91.49 |
November | 0.00 | 0.00 | 0.234819E+11 | 0.370059E+12 | 0.00 | 96.42 |
December | 0.00 | 0.00 | 0.240885E+11 | 0.382660E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.182865E+13 | 0.413614E+13 | 0.00 | 904.65 |
Minimum of Months | 0.00 | 0.00 | 0.133751E+11 | 0.228346E+12 | 0.00 | 40.19 |
Maximum of Months | 0.00 | 0.00 | 0.741972E+12 | 0.502681E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.344441E+10 | 0.237125E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100002E+11 | 0.339113E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.181045E+11 | 0.491189E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.240845E+11 | 0.576755E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.682790E+10 | 0.298595E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133943E+11 | 0.419530E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.207995E+11 | 0.593276E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.266569E+11 | 0.692508E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.701075E+10 | 0.300112E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127592E+11 | 0.398589E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.176901E+11 | 0.475106E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.235942E+11 | 0.581663E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184366E+12 | 0.540356E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.344441E+10 | 0.237125E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266569E+11 | 0.692508E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.635206E+10 | 0.175224E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.696995E+11 | 0.279107E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.150565E+12 | 0.433623E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.217496E+12 | 0.533043E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.557503E+11 | 0.269206E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123856E+12 | 0.394964E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.196461E+12 | 0.564194E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.251732E+12 | 0.658351E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.599427E+11 | 0.275129E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.107450E+12 | 0.357702E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.145254E+12 | 0.416425E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.188970E+12 | 0.499125E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157353E+13 | 0.485609E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.635206E+10 | 0.175224E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.251732E+12 | 0.658351E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.178813E+09 | 0.167967E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.505830E+10 | 0.246654E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.129961E+11 | 0.401986E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.203245E+11 | 0.514279E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.473506E+10 | 0.256496E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.121473E+11 | 0.394435E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.196176E+11 | 0.568185E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.250287E+11 | 0.660572E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.529340E+10 | 0.265618E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.897525E+10 | 0.330461E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.121519E+11 | 0.379851E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.165213E+11 | 0.463491E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143028E+12 | 0.465000E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.178813E+09 | 0.167967E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.250287E+11 | 0.660572E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.305350E+10 | 0.648927E+09 | 0.510892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365330E+10 | 0.359370E+10 | 0.262046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.579970E+10 | 0.562545E+10 | 0.140349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792999E+10 | 0.808496E+10 | 0.333290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.726889E+10 | 0.175451E+11 | 0.243030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124587E+11 | 0.565943E+11 | 92441743.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168906E+11 | 0.965038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176094E+11 | 0.881294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.840156E+10 | 0.378222E+11 | 0.690867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687804E+10 | 0.147715E+11 | 0.288410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.526285E+10 | 0.897770E+10 | 0.101510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427480E+10 | 0.437107E+10 | 0.276174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994814E+11 | 0.342668E+12 | 0.138528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305350E+10 | 0.648927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176094E+11 | 0.965038E+11 | 0.510892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.311268E+11 | 18472.87 | 0.763660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272609E+11 | 0.176101E+11 | 0.403903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338830E+11 | 0.278900E+11 | 0.252944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398198E+11 | 0.790463E+11 | 0.826304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.515741E+11 | 0.156529E+12 | 0.542776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.936837E+11 | 0.482315E+12 | 0.332042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123090E+12 | 0.806670E+12 | 1826836.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116055E+12 | 0.698662E+12 | 0.681887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.630733E+11 | 0.337933E+12 | 0.173517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402720E+11 | 0.130250E+12 | 0.592567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297379E+11 | 0.238565E+11 | 0.199138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283353E+11 | 5706452.74 | 0.494054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677912E+12 | 0.276077E+13 | 0.233122E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272609E+11 | 18472.87 | 1826836.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123090E+12 | 0.806670E+12 | 0.763660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.424627E+10 | 7235.46 | 0.118513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325485E+10 | 0.750984E+09 | 0.617302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348446E+10 | 0.115081E+10 | 0.414966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339623E+10 | 0.451285E+10 | 0.140255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.461913E+10 | 0.150073E+11 | 0.102727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875740E+10 | 0.523869E+11 | 0.760330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122202E+11 | 0.888580E+11 | 18781437.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107165E+11 | 0.748657E+11 | 0.280345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529774E+10 | 0.325942E+11 | 0.362276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324711E+10 | 0.665796E+10 | 0.118854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318227E+10 | 0.422306E+09 | 0.377631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379643E+10 | 0.00 | 0.823758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.662185E+11 | 0.277207E+12 | 0.382745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318227E+10 | 0.00 | 18781437.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122202E+11 | 0.888580E+11 | 0.118513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136899E+11 | 334457.24 | 0.178079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121486E+11 | 0.262399E+09 | 48972517.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146344E+11 | 55797.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134224E+11 | 0.204208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144067E+11 | 0.773335E+10 | 157.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140962E+11 | 0.277385E+11 | 262.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142390E+11 | 0.474299E+11 | 85.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153597E+11 | 0.438544E+11 | 122.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143057E+11 | 0.181207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140336E+11 | 0.518394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135392E+11 | 63463694.89 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134261E+11 | 11486.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167301E+12 | 0.152429E+12 | 0.182976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121486E+11 | 11486.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153597E+11 | 0.474299E+11 | 0.178079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107480E+12 | 0.889853E+10 | 0.00 | 0.00 | 0.00 | 0.158165E+12 | 0.00 | 0.00 |
February | 0.970790E+11 | 0.135512E+11 | 0.00 | 0.00 | 0.00 | 0.231618E+12 | 0.00 | 0.00 |
March | 0.107480E+12 | 0.151137E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
April | 0.104013E+12 | 0.757828E+11 | 0.00 | 0.00 | 0.00 | 0.256875E+12 | 0.00 | 0.00 |
May | 0.107480E+12 | 0.179629E+11 | 0.00 | 0.00 | 0.00 | 0.157931E+12 | 0.00 | 0.00 |
June | 0.104013E+12 | 0.136129E+12 | 0.00 | 0.00 | 0.00 | 0.137287E+12 | 0.00 | 0.00 |
July | 0.107480E+12 | 0.448109E+12 | 0.00 | 0.00 | 0.00 | 0.111929E+12 | 0.00 | 0.00 |
August | 0.107480E+12 | 0.571233E+12 | 0.00 | 0.00 | 0.00 | 0.223456E+12 | 0.00 | 0.00 |
September | 0.104013E+12 | 0.450197E+11 | 0.00 | 0.00 | 0.00 | 0.107544E+12 | 0.00 | 0.00 |
October | 0.107480E+12 | 0.246686E+11 | 0.00 | 0.00 | 0.00 | 0.244826E+12 | 0.00 | 0.00 |
November | 0.104013E+12 | 0.166347E+11 | 0.00 | 0.00 | 0.00 | 0.258037E+12 | 0.00 | 0.00 |
December | 0.107480E+12 | 0.167490E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.126549E+13 | 0.138985E+13 | 0.00 | 0.00 | 0.00 | 0.242095E+13 | 0.00 | 0.00 |
Minimum of Months | 0.970790E+11 | 0.889853E+10 | 0.00 | 0.00 | 0.00 | 0.107544E+12 | 0.00 | 0.00 |
Maximum of Months | 0.107480E+12 | 0.571233E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167566E+10 | 0.274882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151350E+10 | 0.812256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167566E+10 | 0.148683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162161E+10 | 0.199386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167566E+10 | 0.551760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162161E+10 | 0.108206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167566E+10 | 0.165424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167566E+10 | 0.214075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162161E+10 | 0.563123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167566E+10 | 0.104489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162161E+10 | 0.145606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167566E+10 | 0.194532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197295E+11 | 0.150060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151350E+10 | 0.274882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167566E+10 | 0.214075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161072E+11 | 0.493682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145484E+11 | 0.563373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161072E+11 | 0.123310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155876E+11 | 0.179779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161072E+11 | 0.449368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155876E+11 | 0.999470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161072E+11 | 0.156148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161072E+11 | 0.202004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155876E+11 | 0.480174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161072E+11 | 0.877869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155876E+11 | 0.119199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161072E+11 | 0.155165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189649E+12 | 0.127757E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145484E+11 | 0.493682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161072E+11 | 0.202004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163972E+10 | 0.138862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148104E+10 | 0.407281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163972E+10 | 0.106160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158683E+10 | 0.167685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163972E+10 | 0.380983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158683E+10 | 0.978982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163972E+10 | 0.155754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163972E+10 | 0.200627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158683E+10 | 0.422405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163972E+10 | 0.731036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158683E+10 | 0.994023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163972E+10 | 0.135261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193064E+11 | 0.115835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148104E+10 | 0.138862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163972E+10 | 0.200627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.305350E+10 | 0.510892E+11 | 0.648927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365330E+10 | 0.262046E+11 | 0.359370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.579970E+10 | 0.140349E+11 | 0.562545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792999E+10 | 0.333290E+10 | 0.808496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.726889E+10 | 0.243030E+10 | 0.175451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124587E+11 | 92441743.28 | 0.565943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168906E+11 | 0.00 | 0.965038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176094E+11 | 0.00 | 0.881294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.840156E+10 | 0.690867E+09 | 0.378222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687804E+10 | 0.288410E+10 | 0.147715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.526285E+10 | 0.101510E+11 | 0.897770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427480E+10 | 0.276174E+11 | 0.437107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994814E+11 | 0.138528E+12 | 0.342668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305350E+10 | 0.00 | 0.648927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176094E+11 | 0.510892E+11 | 0.965038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.311268E+11 | 0.763660E+12 | 18472.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272609E+11 | 0.403903E+12 | 0.176101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338830E+11 | 0.252944E+12 | 0.278900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398198E+11 | 0.826304E+11 | 0.790463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.515741E+11 | 0.542776E+11 | 0.156529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.936837E+11 | 0.332042E+10 | 0.482315E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123090E+12 | 1826836.82 | 0.806670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116055E+12 | 0.681887E+09 | 0.698662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.630733E+11 | 0.173517E+11 | 0.337933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402720E+11 | 0.592567E+11 | 0.130250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297379E+11 | 0.199138E+12 | 0.238565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283353E+11 | 0.494054E+12 | 5706452.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677912E+12 | 0.233122E+13 | 0.276077E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272609E+11 | 1826836.82 | 18472.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123090E+12 | 0.763660E+12 | 0.806670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.424627E+10 | 0.118513E+12 | 7235.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325485E+10 | 0.617302E+11 | 0.750984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348446E+10 | 0.414966E+11 | 0.115081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339623E+10 | 0.140255E+11 | 0.451285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.461913E+10 | 0.102727E+11 | 0.150073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875740E+10 | 0.760330E+09 | 0.523869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122202E+11 | 18781437.01 | 0.888580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107165E+11 | 0.280345E+09 | 0.748657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529774E+10 | 0.362276E+10 | 0.325942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324711E+10 | 0.118854E+11 | 0.665796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318227E+10 | 0.377631E+11 | 0.422306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379643E+10 | 0.823758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.662185E+11 | 0.382745E+12 | 0.277207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318227E+10 | 18781437.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122202E+11 | 0.118513E+12 | 0.888580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136899E+11 | 0.178079E+10 | 334457.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121486E+11 | 48972517.39 | 0.262399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146344E+11 | 0.00 | 55797.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134224E+11 | 0.00 | 0.204208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144067E+11 | 157.27 | 0.773335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140962E+11 | 262.11 | 0.277385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142390E+11 | 85.09 | 0.474299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153597E+11 | 122.41 | 0.438544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143057E+11 | 0.00 | 0.181207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140336E+11 | 0.00 | 0.518394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135392E+11 | 112.35 | 63463694.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134261E+11 | 0.00 | 11486.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167301E+12 | 0.182976E+10 | 0.152429E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121486E+11 | 0.00 | 11486.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153597E+11 | 0.178079E+10 | 0.474299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107480E+12 | 0.00 | 0.133751E+11 | 0.00 | 0.447660E+10 | 0.00 | 0.00 | 0.00 | 0.158877E+12 | 0.00 | 0.00 | 0.00 |
February | 0.970790E+11 | 0.00 | 0.191336E+11 | 0.00 | 0.558241E+10 | 0.00 | 0.00 | 0.00 | 0.232661E+12 | 0.00 | 0.00 | 0.00 |
March | 0.107480E+12 | 0.00 | 0.216433E+11 | 0.00 | 0.652954E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
April | 0.104013E+12 | 0.00 | 0.995208E+11 | 0.00 | 0.237380E+11 | 0.00 | 0.00 | 0.00 | 0.258032E+12 | 0.00 | 0.00 | 0.00 |
May | 0.107480E+12 | 0.00 | 0.254205E+11 | 0.00 | 0.745753E+10 | 0.00 | 0.00 | 0.00 | 0.158642E+12 | 0.00 | 0.00 | 0.00 |
June | 0.104013E+12 | 0.00 | 0.179211E+12 | 0.00 | 0.430823E+11 | 0.00 | 0.00 | 0.00 | 0.137905E+12 | 0.00 | 0.00 | 0.00 |
July | 0.107480E+12 | 0.00 | 0.585671E+12 | 0.00 | 0.137562E+12 | 0.00 | 0.00 | 0.00 | 0.112433E+12 | 0.00 | 0.00 | 0.00 |
August | 0.107480E+12 | 0.00 | 0.741972E+12 | 0.00 | 0.170738E+12 | 0.00 | 0.00 | 0.00 | 0.224462E+12 | 0.00 | 0.00 | 0.00 |
September | 0.104013E+12 | 0.00 | 0.613251E+11 | 0.00 | 0.163054E+11 | 0.00 | 0.00 | 0.00 | 0.108028E+12 | 0.00 | 0.00 | 0.00 |
October | 0.107480E+12 | 0.00 | 0.338107E+11 | 0.00 | 0.914209E+10 | 0.00 | 0.00 | 0.00 | 0.245928E+12 | 0.00 | 0.00 | 0.00 |
November | 0.104013E+12 | 0.00 | 0.234819E+11 | 0.00 | 0.684722E+10 | 0.00 | 0.00 | 0.00 | 0.259199E+12 | 0.00 | 0.00 | 0.00 |
December | 0.107480E+12 | 0.00 | 0.240885E+11 | 0.00 | 0.733950E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126549E+13 | 0.00 | 0.182865E+13 | 0.00 | 0.438801E+12 | 0.00 | 0.00 | 0.00 | 0.243185E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.970790E+11 | 0.00 | 0.133751E+11 | 0.00 | 0.447660E+10 | 0.00 | 0.00 | 0.00 | 0.108028E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107480E+12 | 0.00 | 0.741972E+12 | 0.00 | 0.170738E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167566E+10 | 0.00 | 0.344441E+10 | 0.00 | 0.695587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151350E+10 | 0.00 | 0.100002E+11 | 0.00 | 0.187763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167566E+10 | 0.00 | 0.181045E+11 | 0.00 | 0.323623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162161E+10 | 0.00 | 0.240845E+11 | 0.00 | 0.414595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167566E+10 | 0.00 | 0.682790E+10 | 0.00 | 0.131029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162161E+10 | 0.00 | 0.133943E+11 | 0.00 | 0.257369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167566E+10 | 0.00 | 0.207995E+11 | 0.00 | 0.425710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167566E+10 | 0.00 | 0.266569E+11 | 0.00 | 0.524942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162161E+10 | 0.00 | 0.701075E+10 | 0.00 | 0.137952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167566E+10 | 0.00 | 0.127592E+11 | 0.00 | 0.231023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162161E+10 | 0.00 | 0.176901E+11 | 0.00 | 0.312945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167566E+10 | 0.00 | 0.235942E+11 | 0.00 | 0.414097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197295E+11 | 0.00 | 0.184366E+12 | 0.00 | 0.343061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151350E+10 | 0.00 | 0.344441E+10 | 0.00 | 0.695587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167566E+10 | 0.00 | 0.266569E+11 | 0.00 | 0.524942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161072E+11 | 0.00 | 0.635206E+10 | 0.00 | 0.141525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145484E+11 | 0.00 | 0.696995E+11 | 0.00 | 0.133622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161072E+11 | 0.00 | 0.150565E+12 | 0.00 | 0.272551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155876E+11 | 0.00 | 0.217496E+12 | 0.00 | 0.377167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161072E+11 | 0.00 | 0.557503E+11 | 0.00 | 0.108134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155876E+11 | 0.00 | 0.123856E+12 | 0.00 | 0.239088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161072E+11 | 0.00 | 0.196461E+12 | 0.00 | 0.403123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161072E+11 | 0.00 | 0.251732E+12 | 0.00 | 0.497279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155876E+11 | 0.00 | 0.599427E+11 | 0.00 | 0.119253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161072E+11 | 0.00 | 0.107450E+12 | 0.00 | 0.196630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155876E+11 | 0.00 | 0.145254E+12 | 0.00 | 0.260549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161072E+11 | 0.00 | 0.188970E+12 | 0.00 | 0.338053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189649E+12 | 0.00 | 0.157353E+13 | 0.00 | 0.295960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145484E+11 | 0.00 | 0.635206E+10 | 0.00 | 0.141525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161072E+11 | 0.00 | 0.251732E+12 | 0.00 | 0.497279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163972E+10 | 0.00 | 0.178813E+09 | 0.00 | 39950510.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148104E+10 | 0.00 | 0.505830E+10 | 0.00 | 0.985498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163972E+10 | 0.00 | 0.129961E+11 | 0.00 | 0.238014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158683E+10 | 0.00 | 0.203245E+11 | 0.00 | 0.355596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163972E+10 | 0.00 | 0.473506E+10 | 0.00 | 0.925234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158683E+10 | 0.00 | 0.121473E+11 | 0.00 | 0.235752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163972E+10 | 0.00 | 0.196176E+11 | 0.00 | 0.404212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163972E+10 | 0.00 | 0.250287E+11 | 0.00 | 0.496600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158683E+10 | 0.00 | 0.529340E+10 | 0.00 | 0.106935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163972E+10 | 0.00 | 0.897525E+10 | 0.00 | 0.166489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158683E+10 | 0.00 | 0.121519E+11 | 0.00 | 0.221168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163972E+10 | 0.00 | 0.165213E+11 | 0.00 | 0.299518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193064E+11 | 0.00 | 0.143028E+12 | 0.00 | 0.271935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148104E+10 | 0.00 | 0.178813E+09 | 0.00 | 39950510.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163972E+10 | 0.00 | 0.250287E+11 | 0.00 | 0.496600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343028E+11 | 0.00 | 0.00 | 41520715.52 | 0.00 | 0.00 | 0.298485E+11 | 0.00 | 0.38 |
February | 0.188284E+11 | 0.00 | 0.00 | 58135366.52 | 0.00 | 0.00 | 0.362047E+11 | 0.00 | 0.47 |
March | 0.379223E+10 | 0.00 | 0.00 | 99736490.55 | 0.00 | 0.00 | 0.633745E+11 | 0.00 | 0.58 |
April | 0.311326E+09 | 0.00 | 0.00 | 0.101222E+09 | 0.00 | 0.00 | 0.614821E+11 | 0.00 | 0.81 |
May | 0.157665E+09 | 38318535.09 | 0.00 | 0.104657E+09 | 7083420.50 | 0.00 | 0.590715E+11 | 0.00 | 0.97 |
June | 74500240.46 | 0.405249E+09 | 0.00 | 98095249.49 | 233525.81 | 0.00 | 0.436467E+11 | 0.00 | 1.15 |
July | 0.163169E+09 | 0.128434E+10 | 0.00 | 0.100720E+09 | 30255478.98 | 0.00 | 0.271273E+11 | 0.00 | 0.98 |
August | 0.130743E+09 | 0.894207E+09 | 0.00 | 0.114052E+09 | 51313244.86 | 0.00 | 0.377690E+11 | 0.00 | 1.17 |
September | 0.163178E+09 | 0.424797E+09 | 0.00 | 0.106092E+09 | 38865328.03 | 0.00 | 0.526027E+11 | 0.00 | 1.14 |
October | 0.344812E+09 | 0.00 | 0.00 | 0.119858E+09 | 0.00 | 0.00 | 0.660970E+11 | 0.00 | 0.95 |
November | 0.305759E+09 | 0.00 | 0.00 | 0.116843E+09 | 0.00 | 0.00 | 0.665697E+11 | 0.00 | 0.70 |
December | 0.104397E+11 | 0.00 | 0.00 | 90146667.83 | 0.00 | 0.00 | 0.555598E+11 | 0.00 | 0.47 |
Annual Sum or Average | 0.690143E+11 | 0.304691E+10 | 0.00 | 0.115108E+10 | 0.127751E+09 | 0.00 | 0.599353E+12 | 0.00 | 0.81 |
Minimum of Months | 74500240.46 | 0.00 | 0.00 | 41520715.52 | 0.00 | 0.00 | 0.271273E+11 | 0.00 | 0.38 |
Maximum of Months | 0.343028E+11 | 0.128434E+10 | 0.00 | 0.119858E+09 | 51313244.86 | 0.00 | 0.665697E+11 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263865E+11 | 0.00 | 0.00 | 32938889.05 | 0.00 | 0.00 | 0.326701E+11 | 0.00 | 0.33 |
February | 0.110895E+11 | 0.00 | 0.00 | 50272453.57 | 0.00 | 0.00 | 0.375641E+11 | 0.00 | 0.39 |
March | 0.332396E+10 | 0.00 | 0.00 | 84659453.50 | 0.00 | 0.00 | 0.539549E+11 | 0.00 | 0.47 |
April | 0.315965E+10 | 0.00 | 0.00 | 92228955.36 | 0.00 | 0.00 | 0.521884E+11 | 0.00 | 0.68 |
May | 0.208636E+10 | 16568777.85 | 0.00 | 81360882.03 | 7937250.70 | 0.00 | 0.439565E+11 | 0.00 | 0.69 |
June | 0.294555E+10 | 0.261353E+09 | 0.00 | 89513811.31 | 11618764.17 | 0.00 | 0.347800E+11 | 0.00 | 0.91 |
July | 0.608676E+10 | 0.567783E+09 | 0.00 | 85546499.83 | 69359796.42 | 0.00 | 0.203816E+11 | 0.00 | 0.85 |
August | 0.787061E+10 | 0.361023E+09 | 0.00 | 0.104166E+09 | 51938513.16 | 0.00 | 0.303572E+11 | 0.00 | 1.02 |
September | 0.201857E+10 | 0.419972E+09 | 0.00 | 79288890.61 | 37183708.31 | 0.00 | 0.364935E+11 | 0.00 | 0.76 |
October | 0.191072E+10 | 0.00 | 0.00 | 89833981.75 | 0.00 | 0.00 | 0.465674E+11 | 0.00 | 0.65 |
November | 0.195092E+10 | 0.00 | 0.00 | 82447296.51 | 0.00 | 0.00 | 0.484635E+11 | 0.00 | 0.48 |
December | 0.457421E+10 | 0.00 | 0.00 | 74791732.99 | 0.00 | 0.00 | 0.545048E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.734033E+11 | 0.162670E+10 | 0.00 | 0.947049E+09 | 0.178038E+09 | 0.00 | 0.491882E+12 | 0.00 | 0.63 |
Minimum of Months | 0.191072E+10 | 0.00 | 0.00 | 32938889.05 | 0.00 | 0.00 | 0.203816E+11 | 0.00 | 0.33 |
Maximum of Months | 0.263865E+11 | 0.567783E+09 | 0.00 | 0.104166E+09 | 69359796.42 | 0.00 | 0.545048E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.477812E+12 | 0.00 | 0.00 | 1003347.04 | 0.00 | 0.833610E+10 | 0.955694E+10 | 0.00 | 0.29 |
February | 0.323590E+12 | 0.00 | 0.00 | 64521549.67 | 0.00 | 0.110625E+10 | 0.631313E+11 | 0.00 | 0.31 |
March | 0.217069E+12 | 0.00 | 0.00 | 0.237702E+09 | 0.00 | 0.776880E+09 | 0.205516E+12 | 0.00 | 0.34 |
April | 0.809577E+11 | 0.00 | 0.00 | 0.390043E+09 | 0.00 | 0.00 | 0.273898E+12 | 0.00 | 0.42 |
May | 0.526120E+11 | 0.189533E+09 | 0.00 | 0.484300E+09 | 86539181.48 | 0.00 | 0.293172E+12 | 0.00 | 0.52 |
June | 0.208420E+11 | 0.267706E+10 | 0.00 | 0.650902E+09 | 62956374.69 | 0.00 | 0.261874E+12 | 0.00 | 0.69 |
July | 0.203179E+11 | 0.622101E+10 | 0.00 | 0.618863E+09 | 0.268251E+09 | 0.00 | 0.146581E+12 | 0.00 | 0.59 |
August | 0.180876E+11 | 0.388863E+10 | 0.00 | 0.722945E+09 | 0.499445E+09 | 0.00 | 0.217308E+12 | 0.00 | 0.68 |
September | 0.254582E+11 | 0.385936E+10 | 0.00 | 0.548434E+09 | 0.385908E+09 | 0.00 | 0.265495E+12 | 0.00 | 0.58 |
October | 0.647645E+11 | 0.00 | 0.00 | 0.436718E+09 | 0.00 | 0.00 | 0.259699E+12 | 0.00 | 0.42 |
November | 0.190929E+12 | 0.00 | 0.00 | 0.221261E+09 | 0.00 | 0.108920E+09 | 0.165551E+12 | 0.00 | 0.34 |
December | 0.353245E+12 | 0.00 | 0.00 | 57291454.39 | 0.00 | 0.193583E+10 | 0.841030E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.184568E+13 | 0.168356E+11 | 0.00 | 0.443399E+10 | 0.130310E+10 | 0.122640E+11 | 0.224588E+13 | 0.00 | 0.46 |
Minimum of Months | 0.180876E+11 | 0.00 | 0.00 | 1003347.04 | 0.00 | 0.00 | 0.955694E+10 | 0.00 | 0.29 |
Maximum of Months | 0.477812E+12 | 0.622101E+10 | 0.00 | 0.722945E+09 | 0.499445E+09 | 0.833610E+10 | 0.293172E+12 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.270217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151539E+11 | 0.00 | 0.00 | 0.27 |
February | 0.285699E+11 | 0.00 | 0.00 | 338267.01 | 0.00 | 0.512345E+10 | 0.299777E+09 | 0.00 | 0.29 |
March | 0.292665E+11 | 0.00 | 0.00 | 3133467.15 | 0.00 | 0.265045E+10 | 0.344267E+10 | 0.00 | 0.31 |
April | 0.178413E+11 | 0.00 | 0.00 | 15203897.00 | 0.00 | 0.147055E+09 | 0.121251E+11 | 0.00 | 0.39 |
May | 0.116075E+11 | 9430214.71 | 0.00 | 30139388.14 | 5156790.32 | 0.329203E+09 | 0.192537E+11 | 0.00 | 0.49 |
June | 0.399267E+10 | 0.178070E+09 | 0.00 | 58776355.25 | 6990437.66 | 0.00 | 0.225415E+11 | 0.00 | 0.70 |
July | 0.263670E+10 | 0.389121E+09 | 0.00 | 62095469.48 | 19576864.63 | 0.00 | 0.129150E+11 | 0.00 | 0.60 |
August | 0.280491E+10 | 0.249283E+09 | 0.00 | 68058993.97 | 39793235.97 | 0.00 | 0.177870E+11 | 0.00 | 0.65 |
September | 0.810895E+10 | 0.339103E+09 | 0.00 | 34974362.38 | 28600364.58 | 0.00 | 0.162245E+11 | 0.00 | 0.53 |
October | 0.168263E+11 | 0.00 | 0.00 | 13256726.13 | 0.00 | 0.307995E+09 | 0.965744E+10 | 0.00 | 0.38 |
November | 0.242520E+11 | 0.00 | 0.00 | 2004918.40 | 0.00 | 0.248918E+10 | 0.209482E+10 | 0.00 | 0.30 |
December | 0.280246E+11 | 0.00 | 0.00 | 46458.91 | 0.00 | 0.865480E+10 | 0.215498E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.200953E+12 | 0.116501E+10 | 0.00 | 0.288028E+09 | 0.100118E+09 | 0.348560E+11 | 0.116557E+12 | 0.00 | 0.43 |
Minimum of Months | 0.263670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.292665E+11 | 0.389121E+09 | 0.00 | 68058993.97 | 39793235.97 | 0.151539E+11 | 0.225415E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264275E+10 | 0.00 | 0.00 | 3193.84 | 0.00 | 0.396669E+10 | 12031568.10 | 0.00 | 0.28 |
February | 0.303822E+10 | 0.00 | 0.00 | 382675.87 | 0.00 | 0.141790E+10 | 0.248870E+09 | 0.00 | 0.29 |
March | 0.304008E+10 | 0.00 | 0.00 | 2136118.50 | 0.00 | 0.219688E+09 | 0.154414E+10 | 0.00 | 0.31 |
April | 0.173070E+10 | 0.00 | 0.00 | 5235067.52 | 0.00 | 0.00 | 0.338234E+10 | 0.00 | 0.55 |
May | 0.116347E+10 | 5442042.26 | 0.00 | 7229109.55 | 998818.36 | 0.00 | 0.389534E+10 | 0.00 | 0.69 |
June | 0.538747E+09 | 54894784.40 | 0.00 | 12777910.74 | 1388370.81 | 0.00 | 0.468968E+10 | 0.00 | 1.12 |
July | 0.837000E+09 | 0.119813E+09 | 0.00 | 13854733.37 | 6772770.82 | 0.00 | 0.285914E+10 | 0.00 | 1.05 |
August | 0.112912E+10 | 84086443.30 | 0.00 | 13728701.36 | 6535908.01 | 0.00 | 0.353556E+10 | 0.00 | 1.13 |
September | 0.103323E+10 | 81500777.55 | 0.00 | 6560382.98 | 4679173.16 | 0.00 | 0.279878E+10 | 0.00 | 0.69 |
October | 0.185165E+10 | 0.00 | 0.00 | 3919412.56 | 0.00 | 0.00 | 0.224981E+10 | 0.00 | 0.47 |
November | 0.290342E+10 | 0.00 | 0.00 | 1291841.12 | 0.00 | 89773071.57 | 0.903852E+09 | 0.00 | 0.30 |
December | 0.355286E+10 | 0.00 | 0.00 | 234198.52 | 0.00 | 0.102805E+10 | 0.171340E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.234613E+11 | 0.345737E+09 | 0.00 | 67353345.91 | 20375041.15 | 0.672209E+10 | 0.262909E+11 | 0.00 | 0.60 |
Minimum of Months | 0.538747E+09 | 0.00 | 0.00 | 3193.84 | 0.00 | 0.00 | 12031568.10 | 0.00 | 0.24 |
Maximum of Months | 0.355286E+10 | 0.119813E+09 | 0.00 | 13854733.37 | 6772770.82 | 0.396669E+10 | 0.468968E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183987E+10 | 0.00 | 0.00 | 264772.57 | 0.00 | 0.238898E+10 | 0.165119E+09 | 0.00 | 0.29 |
February | 0.176054E+10 | 0.00 | 0.00 | 1837825.72 | 0.00 | 0.816587E+09 | 0.955939E+09 | 0.00 | 0.36 |
March | 0.172733E+10 | 0.00 | 0.00 | 4792081.19 | 0.00 | 0.189325E+09 | 0.226334E+10 | 0.00 | 0.43 |
April | 0.103683E+10 | 0.00 | 0.00 | 8204508.52 | 0.00 | 1815733.97 | 0.441178E+10 | 0.00 | 0.89 |
May | 0.654226E+09 | 3768911.79 | 0.00 | 10011840.32 | 643900.84 | 461298.20 | 0.532737E+10 | 0.00 | 1.19 |
June | 0.310347E+09 | 45749063.20 | 0.00 | 17987408.94 | 898482.10 | 0.00 | 0.554081E+10 | 0.00 | 1.91 |
July | 0.499858E+09 | 0.105343E+09 | 0.00 | 21172652.41 | 4347633.14 | 0.00 | 0.386872E+10 | 0.00 | 1.88 |
August | 0.730614E+09 | 74928232.54 | 0.00 | 15059993.84 | 4075963.15 | 0.00 | 0.434123E+10 | 0.00 | 1.87 |
September | 0.531507E+09 | 64385495.54 | 0.00 | 9711286.85 | 2958387.44 | 0.00 | 0.372189E+10 | 0.00 | 1.18 |
October | 0.100673E+10 | 0.00 | 0.00 | 6269110.59 | 0.00 | 0.00 | 0.286722E+10 | 0.00 | 0.69 |
November | 0.165812E+10 | 0.00 | 0.00 | 2123385.44 | 0.00 | 0.123553E+09 | 0.102543E+10 | 0.00 | 0.33 |
December | 0.199362E+10 | 0.00 | 0.00 | 434921.80 | 0.00 | 0.911064E+09 | 0.243302E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.137496E+11 | 0.294175E+09 | 0.00 | 97869788.20 | 12924366.68 | 0.443178E+10 | 0.347322E+11 | 0.00 | 0.94 |
Minimum of Months | 0.310347E+09 | 0.00 | 0.00 | 264772.57 | 0.00 | 0.00 | 0.165119E+09 | 0.00 | 0.24 |
Maximum of Months | 0.199362E+10 | 0.105343E+09 | 0.00 | 21172652.41 | 4347633.14 | 0.238898E+10 | 0.554081E+10 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261520E+10 | 0.00 | 0.00 | 5752597.21 | 0.00 | 0.307390E+10 | 0.399220E+10 | 0.00 | 0.43 |
February | 0.221555E+10 | 0.00 | 0.00 | 12251253.74 | 0.00 | 0.958207E+09 | 0.565052E+10 | 0.00 | 0.65 |
March | 0.237562E+10 | 0.00 | 0.00 | 13215071.69 | 0.00 | 0.297181E+09 | 0.707836E+10 | 0.00 | 0.71 |
April | 0.162828E+10 | 0.00 | 0.00 | 13879994.97 | 0.00 | 7054198.22 | 0.733218E+10 | 0.00 | 1.07 |
May | 0.121084E+10 | 7803519.70 | 0.00 | 12800164.61 | 1000254.68 | 33963601.19 | 0.633351E+10 | 0.00 | 1.09 |
June | 0.657077E+09 | 79932706.43 | 0.00 | 18146529.61 | 1377446.50 | 0.00 | 0.538898E+10 | 0.00 | 1.40 |
July | 0.831718E+09 | 0.178397E+09 | 0.00 | 20794859.42 | 5957240.24 | 0.00 | 0.335836E+10 | 0.00 | 1.33 |
August | 0.109360E+10 | 0.169297E+09 | 0.00 | 26593841.80 | 3835696.56 | 0.00 | 0.519252E+10 | 0.00 | 1.71 |
September | 0.818953E+09 | 0.211735E+09 | 0.00 | 19889471.89 | 1089507.96 | 0.00 | 0.663732E+10 | 0.00 | 1.51 |
October | 0.123512E+10 | 0.00 | 0.00 | 20989389.33 | 0.00 | 19174925.93 | 0.817815E+10 | 0.00 | 1.22 |
November | 0.200221E+10 | 0.00 | 0.00 | 12639918.22 | 0.00 | 0.249178E+09 | 0.521331E+10 | 0.00 | 0.61 |
December | 0.257441E+10 | 0.00 | 0.00 | 6618166.90 | 0.00 | 0.109251E+10 | 0.382731E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.192586E+11 | 0.647165E+09 | 0.00 | 0.183571E+09 | 13260145.95 | 0.573117E+10 | 0.681827E+11 | 0.00 | 1.01 |
Minimum of Months | 0.657077E+09 | 0.00 | 0.00 | 5752597.21 | 0.00 | 0.00 | 0.335836E+10 | 0.00 | 0.41 |
Maximum of Months | 0.261520E+10 | 0.211735E+09 | 0.00 | 26593841.80 | 5957240.24 | 0.307390E+10 | 0.817815E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236581E+10 | 0.00 | 0.00 | 657404.76 | 0.00 | 0.144616E+10 | 0.546065E+09 | 0.00 | 0.30 |
February | 0.184312E+10 | 0.00 | 0.00 | 4552041.34 | 0.00 | 0.121697E+09 | 0.250905E+10 | 0.00 | 0.49 |
March | 0.687472E+09 | 0.00 | 0.00 | 9764978.23 | 0.00 | 8697613.29 | 0.631768E+10 | 0.00 | 0.79 |
April | 0.145593E+09 | 0.00 | 0.00 | 18572143.16 | 0.00 | 0.00 | 0.938828E+10 | 0.00 | 1.67 |
May | 0.314859E+09 | 6322218.20 | 0.00 | 15733687.04 | 502132.40 | 0.00 | 0.698243E+10 | 0.00 | 1.58 |
June | 0.134601E+09 | 84065907.37 | 0.00 | 23061216.95 | 66629.13 | 0.00 | 0.637258E+10 | 0.00 | 2.26 |
July | 0.192868E+09 | 0.198824E+09 | 0.00 | 27660695.43 | 3087095.65 | 0.00 | 0.441225E+10 | 0.00 | 2.13 |
August | 0.210460E+09 | 0.146687E+09 | 0.00 | 28007347.52 | 353439.77 | 0.00 | 0.643145E+10 | 0.00 | 2.56 |
September | 0.255281E+09 | 0.149957E+09 | 0.00 | 12034661.00 | 192789.18 | 0.00 | 0.459072E+10 | 0.00 | 1.46 |
October | 0.285350E+09 | 0.00 | 0.00 | 11357025.60 | 0.00 | 0.00 | 0.557203E+10 | 0.00 | 1.12 |
November | 0.594089E+09 | 0.00 | 0.00 | 7565668.41 | 0.00 | 214430.48 | 0.438182E+10 | 0.00 | 0.66 |
December | 0.145140E+10 | 0.00 | 0.00 | 4900895.96 | 0.00 | 963958.43 | 0.333976E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.848091E+10 | 0.585855E+09 | 0.00 | 0.163868E+09 | 4202086.14 | 0.157774E+10 | 0.608441E+11 | 0.00 | 1.29 |
Minimum of Months | 0.134601E+09 | 0.00 | 0.00 | 657404.76 | 0.00 | 0.00 | 0.546065E+09 | 0.00 | 0.30 |
Maximum of Months | 0.236581E+10 | 0.198824E+09 | 0.00 | 28007347.52 | 3087095.65 | 0.144616E+10 | 0.938828E+10 | 0.00 | 2.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841560E+11 | 0.00 | 0.00 | 0.38 |
February | 0.121426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427177E+11 | 0.00 | 0.00 | 0.33 |
March | 0.295351E+11 | 0.00 | 0.00 | 196659.59 | 0.00 | 0.198582E+11 | 0.304581E+09 | 0.00 | 0.31 |
April | 0.254327E+11 | 0.00 | 0.00 | 11163314.75 | 0.00 | 0.363058E+10 | 0.695702E+10 | 0.00 | 0.35 |
May | 0.186811E+11 | 61012374.48 | 0.00 | 38048000.58 | 12213824.22 | 0.203701E+10 | 0.182822E+11 | 0.00 | 0.53 |
June | 0.688257E+10 | 0.623685E+09 | 0.00 | 91554763.24 | 7925225.52 | 0.00 | 0.313730E+11 | 0.00 | 0.86 |
July | 0.390331E+10 | 0.151666E+10 | 0.00 | 98189730.34 | 33768586.58 | 0.00 | 0.193190E+11 | 0.00 | 0.77 |
August | 0.729882E+10 | 0.105160E+10 | 0.00 | 86941123.03 | 62872282.93 | 0.00 | 0.201542E+11 | 0.00 | 0.75 |
September | 0.164706E+11 | 0.773499E+09 | 0.00 | 36087611.90 | 46551670.31 | 0.526818E+09 | 0.123395E+11 | 0.00 | 0.52 |
October | 0.255644E+11 | 0.00 | 0.00 | 7551166.10 | 0.00 | 0.338337E+10 | 0.350651E+10 | 0.00 | 0.33 |
November | 0.208206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212799E+11 | 0.00 | 0.00 | 0.31 |
December | 0.811460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551553E+11 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.177743E+12 | 0.402646E+10 | 0.00 | 0.369732E+09 | 0.163332E+09 | 0.232745E+12 | 0.112236E+12 | 0.00 | 0.48 |
Minimum of Months | 0.289628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.295351E+11 | 0.151666E+10 | 0.00 | 98189730.34 | 62872282.93 | 0.841560E+11 | 0.313730E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.485471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425572E+11 | 0.00 | 0.00 | 0.32 |
February | 0.825819E+10 | 0.00 | 0.00 | 5726025.10 | 0.00 | 0.201790E+11 | 0.291200E+10 | 0.00 | 0.30 |
March | 0.134243E+11 | 0.00 | 0.00 | 23743734.72 | 0.00 | 0.905369E+10 | 0.128425E+11 | 0.00 | 0.36 |
April | 0.102187E+11 | 0.00 | 0.00 | 59788210.37 | 0.00 | 0.140570E+10 | 0.285367E+11 | 0.00 | 0.65 |
May | 0.661750E+10 | 52650252.67 | 0.00 | 81939742.67 | 7031143.81 | 0.110254E+10 | 0.422578E+11 | 0.00 | 1.03 |
June | 0.256212E+10 | 0.583479E+09 | 0.00 | 0.174689E+09 | 2657288.54 | 0.00 | 0.503608E+11 | 0.00 | 1.80 |
July | 0.174408E+10 | 0.140541E+10 | 0.00 | 0.218888E+09 | 8858779.90 | 0.00 | 0.366984E+11 | 0.00 | 1.78 |
August | 0.287868E+10 | 0.108555E+10 | 0.00 | 0.143569E+09 | 40396921.25 | 0.00 | 0.396477E+11 | 0.00 | 1.68 |
September | 0.649082E+10 | 0.709602E+09 | 0.00 | 80185198.39 | 25790635.12 | 0.186414E+09 | 0.278615E+11 | 0.00 | 0.99 |
October | 0.106881E+11 | 0.00 | 0.00 | 34721840.44 | 0.00 | 0.126310E+10 | 0.153049E+11 | 0.00 | 0.48 |
November | 0.110831E+11 | 0.00 | 0.00 | 5037027.71 | 0.00 | 0.978883E+10 | 0.311913E+10 | 0.00 | 0.27 |
December | 0.726651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276122E+11 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.860867E+11 | 0.383668E+10 | 0.00 | 0.828288E+09 | 84734768.63 | 0.113149E+12 | 0.259541E+12 | 0.00 | 0.83 |
Minimum of Months | 0.174408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.134243E+11 | 0.140541E+10 | 0.00 | 0.218888E+09 | 40396921.25 | 0.425572E+11 | 0.503608E+11 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166403E+11 | 0.00 | 0.00 | 45859811.77 | 0.00 | 0.503015E+11 | 0.354022E+11 | 0.00 | 0.48 |
February | 0.174245E+11 | 0.00 | 0.00 | 0.114340E+09 | 0.00 | 0.206321E+11 | 0.531444E+11 | 0.00 | 0.67 |
March | 0.235615E+11 | 0.00 | 0.00 | 0.115223E+09 | 0.00 | 0.111979E+11 | 0.621735E+11 | 0.00 | 0.70 |
April | 0.186054E+11 | 0.00 | 0.00 | 0.116252E+09 | 0.00 | 0.224176E+10 | 0.510520E+11 | 0.00 | 0.84 |
May | 0.140258E+11 | 0.114944E+09 | 0.00 | 0.112447E+09 | 10890484.38 | 0.198907E+10 | 0.525298E+11 | 0.00 | 1.00 |
June | 0.720073E+10 | 0.999490E+09 | 0.00 | 0.153002E+09 | 4650575.05 | 0.00 | 0.438976E+11 | 0.00 | 1.23 |
July | 0.436005E+10 | 0.241460E+10 | 0.00 | 0.178523E+09 | 5534054.96 | 0.00 | 0.267930E+11 | 0.00 | 1.11 |
August | 0.580686E+10 | 0.244497E+10 | 0.00 | 0.231195E+09 | 27298096.66 | 0.00 | 0.421004E+11 | 0.00 | 1.48 |
September | 0.966947E+10 | 0.246215E+10 | 0.00 | 0.194261E+09 | 6031511.85 | 0.340106E+09 | 0.577853E+11 | 0.00 | 1.42 |
October | 0.139329E+11 | 0.00 | 0.00 | 0.206414E+09 | 0.00 | 0.156895E+10 | 0.678011E+11 | 0.00 | 1.05 |
November | 0.175180E+11 | 0.00 | 0.00 | 0.113714E+09 | 0.00 | 0.104942E+11 | 0.542169E+11 | 0.00 | 0.65 |
December | 0.204640E+11 | 0.00 | 0.00 | 39342560.19 | 0.00 | 0.292204E+11 | 0.349887E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.169210E+12 | 0.843615E+10 | 0.00 | 0.162057E+10 | 54404722.90 | 0.127986E+12 | 0.581885E+12 | 0.00 | 0.93 |
Minimum of Months | 0.436005E+10 | 0.00 | 0.00 | 39342560.19 | 0.00 | 0.00 | 0.267930E+11 | 0.00 | 0.48 |
Maximum of Months | 0.235615E+11 | 0.246215E+10 | 0.00 | 0.231195E+09 | 27298096.66 | 0.503015E+11 | 0.678011E+11 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.774908E+10 | 0.00 | 0.00 | 479006.30 | 0.00 | 0.444350E+11 | 0.499282E+09 | 0.00 | 0.36 |
February | 0.126712E+11 | 0.00 | 0.00 | 9752403.03 | 0.00 | 0.189892E+11 | 0.462960E+10 | 0.00 | 0.36 |
March | 0.191441E+11 | 0.00 | 0.00 | 20590749.31 | 0.00 | 0.861167E+10 | 0.125721E+11 | 0.00 | 0.42 |
April | 0.127148E+11 | 0.00 | 0.00 | 61683887.75 | 0.00 | 0.899032E+09 | 0.285987E+11 | 0.00 | 0.79 |
May | 0.805711E+10 | 64311414.41 | 0.00 | 0.109554E+09 | 7041465.53 | 0.103540E+10 | 0.426488E+11 | 0.00 | 1.16 |
June | 0.323918E+10 | 0.892570E+09 | 0.00 | 0.136381E+09 | 1019216.76 | 0.00 | 0.373663E+11 | 0.00 | 1.55 |
July | 0.151641E+10 | 0.235578E+10 | 0.00 | 0.168334E+09 | 1233296.27 | 0.00 | 0.224422E+11 | 0.00 | 1.35 |
August | 0.281800E+10 | 0.154056E+10 | 0.00 | 0.134492E+09 | 8943240.29 | 0.00 | 0.266322E+11 | 0.00 | 1.42 |
September | 0.734519E+10 | 0.144242E+10 | 0.00 | 71760664.79 | 1659941.47 | 0.164137E+09 | 0.233816E+11 | 0.00 | 0.99 |
October | 0.129532E+11 | 0.00 | 0.00 | 38264004.23 | 0.00 | 0.109683E+10 | 0.157421E+11 | 0.00 | 0.54 |
November | 0.150398E+11 | 0.00 | 0.00 | 10879421.24 | 0.00 | 0.865725E+10 | 0.695177E+10 | 0.00 | 0.36 |
December | 0.115585E+11 | 0.00 | 0.00 | 1203594.16 | 0.00 | 0.262168E+11 | 0.131318E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.114807E+12 | 0.629565E+10 | 0.00 | 0.763375E+09 | 19897160.33 | 0.110105E+12 | 0.222778E+12 | 0.00 | 0.81 |
Minimum of Months | 0.151641E+10 | 0.00 | 0.00 | 479006.30 | 0.00 | 0.00 | 0.499282E+09 | 0.00 | 0.32 |
Maximum of Months | 0.191441E+11 | 0.235578E+10 | 0.00 | 0.168334E+09 | 8943240.29 | 0.444350E+11 | 0.426488E+11 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942517E+10 | 0.00 | 0.00 | 0.44 |
February | 0.673761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524216E+10 | 0.00 | 0.00 | 0.38 |
March | 0.190383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329979E+10 | 0.00 | 0.00 | 0.35 |
April | 0.230175E+10 | 0.00 | 0.00 | 679171.85 | 0.00 | 0.106604E+10 | 0.464532E+09 | 0.00 | 0.38 |
May | 0.180807E+10 | 3217450.21 | 0.00 | 3279300.46 | 688202.68 | 0.653431E+09 | 0.163447E+10 | 0.00 | 0.55 |
June | 0.861393E+09 | 38704067.31 | 0.00 | 9108404.03 | 932913.23 | 25360648.52 | 0.291255E+10 | 0.00 | 0.90 |
July | 0.481144E+09 | 90546708.69 | 0.00 | 10774614.86 | 1147324.73 | 0.00 | 0.180742E+10 | 0.00 | 0.79 |
August | 0.812205E+09 | 66224165.65 | 0.00 | 9104170.24 | 5310631.20 | 16144074.17 | 0.182782E+10 | 0.00 | 0.75 |
September | 0.162131E+10 | 65847376.77 | 0.00 | 2978609.10 | 3826789.32 | 0.325229E+09 | 0.973541E+09 | 0.00 | 0.53 |
October | 0.213627E+10 | 0.00 | 0.00 | 295598.83 | 0.00 | 0.115004E+10 | 0.170295E+09 | 0.00 | 0.38 |
November | 0.109987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319899E+10 | 0.00 | 0.00 | 0.35 |
December | 0.319987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650509E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.141333E+11 | 0.264540E+09 | 0.00 | 36219869.36 | 11905861.15 | 0.309074E+11 | 0.979063E+10 | 0.00 | 0.52 |
Minimum of Months | 0.113688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.230175E+10 | 90546708.69 | 0.00 | 10774614.86 | 5310631.20 | 0.942517E+10 | 0.291255E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523903E+10 | 0.00 | 0.00 | 0.40 |
February | 0.768320E+09 | 0.00 | 0.00 | 216816.41 | 0.00 | 0.264134E+10 | 0.135205E+09 | 0.00 | 0.36 |
March | 0.131932E+10 | 0.00 | 0.00 | 1495899.76 | 0.00 | 0.140606E+10 | 0.874208E+09 | 0.00 | 0.39 |
April | 0.102427E+10 | 0.00 | 0.00 | 4709711.79 | 0.00 | 0.440268E+09 | 0.267107E+10 | 0.00 | 0.69 |
May | 0.681459E+09 | 2428814.38 | 0.00 | 7547647.73 | 419049.23 | 0.301749E+09 | 0.416670E+10 | 0.00 | 1.08 |
June | 0.301884E+09 | 35564665.18 | 0.00 | 18144811.11 | 544951.79 | 12895127.76 | 0.504331E+10 | 0.00 | 1.90 |
July | 0.173832E+09 | 85656895.35 | 0.00 | 22939813.58 | 413095.44 | 0.00 | 0.374620E+10 | 0.00 | 1.89 |
August | 0.300098E+09 | 72415000.83 | 0.00 | 15168906.19 | 2312952.34 | 3865284.79 | 0.389955E+10 | 0.00 | 1.73 |
September | 0.689450E+09 | 63427266.15 | 0.00 | 7018354.29 | 1610104.33 | 0.117057E+09 | 0.253437E+10 | 0.00 | 1.00 |
October | 0.106665E+10 | 0.00 | 0.00 | 2145110.04 | 0.00 | 0.437314E+09 | 0.109360E+10 | 0.00 | 0.49 |
November | 0.958263E+09 | 0.00 | 0.00 | 95753.76 | 0.00 | 0.157115E+10 | 85313053.13 | 0.00 | 0.33 |
December | 0.419960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369956E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.800723E+10 | 0.259493E+09 | 0.00 | 79482824.67 | 5300153.13 | 0.158703E+11 | 0.242495E+11 | 0.00 | 0.89 |
Minimum of Months | 0.173832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.131932E+10 | 85656895.35 | 0.00 | 22939813.58 | 2312952.34 | 0.523903E+10 | 0.504331E+10 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100707E+10 | 0.00 | 0.00 | 2991795.19 | 0.00 | 0.576198E+10 | 0.241249E+10 | 0.00 | 0.45 |
February | 0.127453E+10 | 0.00 | 0.00 | 8584327.83 | 0.00 | 0.264988E+10 | 0.422750E+10 | 0.00 | 0.66 |
March | 0.175233E+10 | 0.00 | 0.00 | 8863831.33 | 0.00 | 0.182612E+10 | 0.553073E+10 | 0.00 | 0.68 |
April | 0.151330E+10 | 0.00 | 0.00 | 9343173.88 | 0.00 | 0.745776E+09 | 0.513350E+10 | 0.00 | 0.86 |
May | 0.118106E+10 | 4820856.09 | 0.00 | 10257940.56 | 646122.50 | 0.571113E+09 | 0.530558E+10 | 0.00 | 1.01 |
June | 0.758163E+09 | 58619122.31 | 0.00 | 16727386.79 | 840248.81 | 32495607.82 | 0.448321E+10 | 0.00 | 1.28 |
July | 0.435633E+09 | 0.134814E+09 | 0.00 | 20552213.05 | 437603.60 | 202280.24 | 0.288446E+10 | 0.00 | 1.18 |
August | 0.570662E+09 | 0.151957E+09 | 0.00 | 24864103.43 | 1841140.72 | 15150621.45 | 0.431629E+10 | 0.00 | 1.50 |
September | 0.953476E+09 | 0.206308E+09 | 0.00 | 17737224.28 | 490690.33 | 0.196510E+09 | 0.572967E+10 | 0.00 | 1.44 |
October | 0.126187E+10 | 0.00 | 0.00 | 15905182.69 | 0.00 | 0.479920E+09 | 0.674644E+10 | 0.00 | 1.15 |
November | 0.131126E+10 | 0.00 | 0.00 | 6912155.86 | 0.00 | 0.157587E+10 | 0.418543E+10 | 0.00 | 0.61 |
December | 0.133965E+10 | 0.00 | 0.00 | 2526106.99 | 0.00 | 0.372941E+10 | 0.221822E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.133590E+11 | 0.556519E+09 | 0.00 | 0.145265E+09 | 4255805.95 | 0.175844E+11 | 0.531735E+11 | 0.00 | 0.94 |
Minimum of Months | 0.435633E+09 | 0.00 | 0.00 | 2526106.99 | 0.00 | 202280.24 | 0.221822E+10 | 0.00 | 0.43 |
Maximum of Months | 0.175233E+10 | 0.206308E+09 | 0.00 | 24864103.43 | 1841140.72 | 0.576198E+10 | 0.674644E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.383651E+09 | 0.00 | 0.00 | 22873.66 | 0.00 | 0.507810E+10 | 24012411.72 | 0.00 | 0.40 |
February | 0.827511E+09 | 0.00 | 0.00 | 680987.72 | 0.00 | 0.231353E+10 | 0.415474E+09 | 0.00 | 0.38 |
March | 0.135828E+10 | 0.00 | 0.00 | 1667448.88 | 0.00 | 0.130785E+10 | 0.120025E+10 | 0.00 | 0.42 |
April | 0.119109E+10 | 0.00 | 0.00 | 5274243.91 | 0.00 | 0.333958E+09 | 0.272749E+10 | 0.00 | 0.79 |
May | 0.758752E+09 | 3210069.25 | 0.00 | 10418148.45 | 419895.73 | 0.264064E+09 | 0.435054E+10 | 0.00 | 1.21 |
June | 0.382400E+09 | 52692142.12 | 0.00 | 16646485.54 | 31804.80 | 9668242.70 | 0.382149E+10 | 0.00 | 1.66 |
July | 0.185835E+09 | 0.130426E+09 | 0.00 | 18350670.75 | 10149.48 | 0.00 | 0.228557E+10 | 0.00 | 1.40 |
August | 0.333997E+09 | 90552114.35 | 0.00 | 14490638.87 | 703871.23 | 8834570.10 | 0.256861E+10 | 0.00 | 1.42 |
September | 0.769822E+09 | 0.120528E+09 | 0.00 | 6502734.34 | 144344.89 | 0.106387E+09 | 0.220058E+10 | 0.00 | 1.00 |
October | 0.115888E+10 | 0.00 | 0.00 | 2896810.06 | 0.00 | 0.373778E+09 | 0.152441E+10 | 0.00 | 0.60 |
November | 0.979105E+09 | 0.00 | 0.00 | 657781.30 | 0.00 | 0.128902E+10 | 0.514821E+09 | 0.00 | 0.36 |
December | 0.662783E+09 | 0.00 | 0.00 | 46722.42 | 0.00 | 0.308965E+10 | 42732372.16 | 0.00 | 0.33 |
Annual Sum or Average | 0.899211E+10 | 0.397409E+09 | 0.00 | 77655545.90 | 1310066.13 | 0.141748E+11 | 0.216760E+11 | 0.00 | 0.83 |
Minimum of Months | 0.185835E+09 | 0.00 | 0.00 | 22873.66 | 0.00 | 0.00 | 24012411.72 | 0.00 | 0.33 |
Maximum of Months | 0.135828E+10 | 0.130426E+09 | 0.00 | 18350670.75 | 703871.23 | 0.507810E+10 | 0.435054E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 41429787.45 | 0.00 | 0.00 | 2488841.54 | 0.00 | 0.00 | 0.809250E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7998940.25 | 0.00 | 0.00 | 0.645717E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14768675.67 | 0.00 | 0.00 | 0.661541E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18615797.36 | 0.00 | 0.00 | 0.461161E+09 | 0.00 | 0.29 |
May | 0.00 | 141993.32 | 0.00 | 4030760.92 | 0.00 | 0.00 | 0.408965E+09 | 0.00 | 0.29 |
June | 0.00 | 13354145.10 | 0.00 | 7755458.33 | 0.00 | 0.00 | 0.199502E+09 | 0.00 | 0.30 |
July | 0.00 | 21593278.80 | 0.00 | 9683502.20 | 0.00 | 0.00 | 78557807.39 | 0.00 | 0.28 |
August | 0.00 | 5656640.20 | 0.00 | 18301684.66 | 0.00 | 0.00 | 0.145714E+09 | 0.00 | 0.31 |
September | 0.00 | 11176585.03 | 0.00 | 3635474.55 | 0.00 | 0.00 | 0.258265E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 9003519.96 | 0.00 | 0.00 | 0.439488E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13091925.28 | 0.00 | 0.00 | 0.543622E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 19144093.59 | 0.00 | 0.00 | 0.715099E+09 | 0.00 | 0.28 |
Annual Sum or Average | 41429787.45 | 51922642.44 | 0.00 | 0.128519E+09 | 0.00 | 0.00 | 0.536688E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2488841.54 | 0.00 | 0.00 | 78557807.39 | 0.00 | 0.28 |
Maximum of Months | 41429787.45 | 21593278.80 | 0.00 | 19144093.59 | 0.00 | 0.00 | 0.809250E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.454134E+10 | 0.00 | 0.00 | 4999572.60 | 0.00 | 0.00 | 0.387285E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 58458527.53 | 0.00 | 0.00 | 0.647865E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.125556E+09 | 0.00 | 0.00 | 0.663697E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.170065E+09 | 0.00 | 0.00 | 0.462534E+10 | 0.00 | 0.29 |
May | 6200428.45 | 1358792.38 | 0.00 | 32239533.83 | 0.00 | 0.00 | 0.409562E+10 | 0.00 | 0.29 |
June | 0.00 | 0.132156E+09 | 0.00 | 72089375.28 | 0.00 | 0.00 | 0.200269E+10 | 0.00 | 0.30 |
July | 0.00 | 0.214947E+09 | 0.00 | 91850970.44 | 0.00 | 0.00 | 0.791182E+09 | 0.00 | 0.28 |
August | 0.00 | 59187537.76 | 0.00 | 0.172258E+09 | 0.00 | 0.00 | 0.146296E+10 | 0.00 | 0.31 |
September | 0.00 | 0.109136E+09 | 0.00 | 30052394.42 | 0.00 | 0.00 | 0.260311E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 76976772.95 | 0.00 | 0.00 | 0.440723E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.110182E+09 | 0.00 | 0.00 | 0.545576E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.159290E+09 | 0.00 | 0.00 | 0.718092E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.454754E+10 | 0.516785E+09 | 0.00 | 0.110402E+10 | 0.00 | 0.00 | 0.496133E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4999572.60 | 0.00 | 0.00 | 0.791182E+09 | 0.00 | 0.28 |
Maximum of Months | 0.454134E+10 | 0.214947E+09 | 0.00 | 0.172258E+09 | 0.00 | 0.00 | 0.718092E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.717508E+09 | 0.00 | 0.00 | 173146.31 | 0.00 | 0.00 | 0.103923E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4721493.77 | 0.00 | 0.00 | 0.648935E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 11282337.21 | 0.00 | 0.00 | 0.664996E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16102518.07 | 0.00 | 0.00 | 0.463611E+09 | 0.00 | 0.29 |
May | 40771384.42 | 137949.21 | 0.00 | 2737212.37 | 0.00 | 0.00 | 0.368881E+09 | 0.00 | 0.29 |
June | 0.00 | 13259394.66 | 0.00 | 7075143.48 | 0.00 | 0.00 | 0.200589E+09 | 0.00 | 0.30 |
July | 0.00 | 21504561.05 | 0.00 | 9170950.57 | 0.00 | 0.00 | 79241331.77 | 0.00 | 0.28 |
August | 0.00 | 5933472.28 | 0.00 | 17102719.91 | 0.00 | 0.00 | 0.146460E+09 | 0.00 | 0.31 |
September | 10685203.79 | 10915778.62 | 0.00 | 2517703.61 | 0.00 | 0.00 | 0.251609E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6624787.41 | 0.00 | 0.00 | 0.442103E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9719550.87 | 0.00 | 0.00 | 0.546954E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14613977.98 | 0.00 | 0.00 | 0.719514E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.768964E+09 | 51751155.81 | 0.00 | 0.101842E+09 | 0.00 | 0.00 | 0.463682E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 173146.31 | 0.00 | 0.00 | 79241331.77 | 0.00 | 0.28 |
Maximum of Months | 0.717508E+09 | 21504561.05 | 0.00 | 17102719.91 | 0.00 | 0.00 | 0.719514E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.871685E+09 | 0.00 | 0.00 | 0.490473E+12 | 0.00 | 7.33 |
February | 0.00 | 0.00 | 0.00 | 0.131482E+10 | 0.00 | 0.00 | 0.747525E+12 | 0.00 | 15.41 |
March | 0.00 | 0.00 | 0.00 | 0.184658E+10 | 0.00 | 0.00 | 0.108510E+13 | 0.00 | 22.82 |
April | 0.00 | 0.00 | 0.00 | 0.224179E+10 | 0.00 | 0.00 | 0.122520E+13 | 0.00 | 36.22 |
May | 0.00 | 0.00 | 0.00 | 0.547775E+09 | 0.00 | 0.00 | 0.487807E+12 | 0.00 | 17.23 |
June | 0.00 | 0.231076E+10 | 0.00 | 0.119151E+10 | 0.00 | 0.00 | 0.577298E+12 | 0.00 | 32.85 |
July | 0.00 | 0.270096E+10 | 0.00 | 0.192463E+10 | 0.00 | 0.00 | 0.505808E+12 | 0.00 | 37.04 |
August | 0.00 | 84580135.72 | 0.00 | 0.304779E+10 | 0.00 | 0.00 | 0.733927E+12 | 0.00 | 45.63 |
September | 0.00 | 0.897738E+09 | 0.00 | 0.528108E+09 | 0.00 | 0.00 | 0.402933E+12 | 0.00 | 21.03 |
October | 0.00 | 0.00 | 0.00 | 0.110029E+10 | 0.00 | 0.00 | 0.813804E+12 | 0.00 | 24.35 |
November | 0.00 | 0.00 | 0.00 | 0.184586E+10 | 0.00 | 0.00 | 0.105106E+13 | 0.00 | 25.95 |
December | 0.00 | 0.00 | 0.00 | 0.312432E+10 | 0.00 | 0.00 | 0.132836E+13 | 0.00 | 25.78 |
Annual Sum or Average | 0.00 | 0.599403E+10 | 0.00 | 0.195852E+11 | 0.00 | 0.00 | 0.944929E+13 | 0.00 | 26.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.528108E+09 | 0.00 | 0.00 | 0.402933E+12 | 0.00 | 7.33 |
Maximum of Months | 0.00 | 0.270096E+10 | 0.00 | 0.312432E+10 | 0.00 | 0.00 | 0.132836E+13 | 0.00 | 45.63 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.240196E+12 | 0.463864E+11 | 0.00 | 0.201151E+13 | 0.202121E+12 |
February | 0.336221E+12 | 0.364376E+11 | 0.00 | 0.215347E+13 | 0.248309E+12 |
March | 0.594725E+12 | 0.343547E+11 | 0.00 | 0.278395E+13 | 0.351277E+12 |
April | 0.644782E+12 | 0.246919E+11 | 0.00 | 0.302972E+13 | 0.547977E+12 |
May | 0.858154E+12 | 0.242972E+11 | 0.00 | 0.226642E+13 | 0.395842E+12 |
June | 0.942716E+12 | 0.125168E+11 | 0.00 | 0.209583E+13 | 0.116957E+13 |
July | 0.936358E+12 | 0.832132E+10 | 0.00 | 0.173560E+13 | 0.222964E+13 |
August | 0.775860E+12 | 0.906964E+10 | 0.00 | 0.211555E+13 | 0.229571E+13 |
September | 0.578407E+12 | 0.163556E+11 | 0.00 | 0.196107E+13 | 0.728758E+12 |
October | 0.370167E+12 | 0.238930E+11 | 0.00 | 0.267157E+13 | 0.412765E+12 |
November | 0.191895E+12 | 0.330611E+11 | 0.00 | 0.269805E+13 | 0.325623E+12 |
December | 0.149881E+12 | 0.416357E+11 | 0.00 | 0.284068E+13 | 0.401278E+12 |
Annual Sum or Average | 0.661936E+13 | 0.311021E+12 | 0.00 | 0.283634E+14 | 0.930888E+13 |
Minimum of Months | 0.149881E+12 | 0.832132E+10 | 0.00 | 0.173560E+13 | 0.202121E+12 |
Maximum of Months | 0.942716E+12 | 0.463864E+11 | 0.00 | 0.302972E+13 | 0.229571E+13 |