Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:56:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 28056.73 | 605.71 | 605.71 |
Net Site Energy | 27537.13 | 594.49 | 594.49 |
Total Source Energy | 83696.45 | 1806.90 | 1806.90 |
Net Source Energy | 82050.88 | 1771.38 | 1771.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1690.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1777.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1715.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 265.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2681.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 366.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.80 |
Humidification | 2373.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.01 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 786.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25579.91 | 2476.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8088.98 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1690.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1777.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1715.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 265.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2681.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 366.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.80 |
Humidification | General | 2373.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.01 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 786.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1690.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1777.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1715.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 265.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2681.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 366.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.80 |
Humidification | Unassigned | 2373.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.01 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 786.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.66 | 53.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 552.24 | 53.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.66 | 53.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 552.24 | 53.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 542.752 | 2.12 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -23.15 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 519.599 | 2.03 |
Electricity Coming From Utility | 25060.312 | 97.97 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25060.312 | 97.97 |
Total On-Site and Utility Electric Sources | 25579.911 | 100.00 |
Total Electricity End Uses | 25579.911 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8088.98 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8088.98 | 100.00 |
Total Water End Uses | 8088.98 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 62.67 |
Time Setpoint Not Met During Occupied Cooling | 666.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5877.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:39 | 23-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 26-JUN-15:09 |
Heating | 0.00 | 1525895.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 362394.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 325428.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 43915.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 45911.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29437.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1854599.31 | 1555332.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1525895.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 362394.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 325428.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 43915.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 45911.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 29437.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1832.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5629.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5431.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 839.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8493.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1161.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1646.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7517.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 852.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 81011.58 | 2684.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 39.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 35.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 162.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1748.94 | 57.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 39.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 35.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 162.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1748.94 | 57.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.88 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.594265 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.71 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.582147 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 26.19 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.42 | 0.296124 | 0.252000 | 1.62 | 0.789663 | 0.500000 | 0.001287 | 0.000289 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 60.27 | 0.315606 | 0.268000 | 16.15 | 0.841616 | 0.500000 | 0.001207 | 0.008628 | 16.15 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.05 | 0.314259 | 0.267000 | 1.62 | 0.838024 | 0.500000 | 0.001212 | 0.002038 | 3.42 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.14 | 0.209429 | 0.178000 | 0.202981 | 0.558476 | 0.500000 | 0.001819 | 0.000300 | 0.503203 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.54 | 0.099710 | 0.085000 | 0.131200 | 0.300000 | 0.500000 | 0.003821 | 0.000213 | 0.358129 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.66 | 0.143534 | 0.122000 | 0.202995 | 0.382759 | 0.500000 | 0.002654 | 0.000356 | 0.597098 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.95 | 0.078844 | 0.067000 | 0.130785 | 0.300000 | 0.500000 | 0.004832 | 0.000163 | 0.273744 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.84 | 0.220224 | 0.187000 | 2.03 | 0.587263 | 0.500000 | 0.001730 | 0.005108 | 8.58 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.58 | 0.300000 | 0.500000 | 0.004104 | 0.003430 | 5.76 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.56 | 0.144201 | 0.123000 | 2.04 | 0.384535 | 0.500000 | 0.002642 | 0.005166 | 8.68 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.21 | 0.084531 | 0.072000 | 1.31 | 0.300000 | 0.500000 | 0.004507 | 0.003281 | 5.51 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.25 | 0.191345 | 0.163000 | 0.203443 | 0.510253 | 0.500000 | 0.001991 | 0.000656 | 1.10 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.66 | 0.092538 | 0.079000 | 0.131389 | 0.300000 | 0.500000 | 0.004117 | 0.000437 | 0.734102 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.81 | 0.132147 | 0.112000 | 0.202415 | 0.352391 | 0.500000 | 0.002883 | 0.000662 | 1.11 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.93 | 0.079718 | 0.068000 | 0.131283 | 0.300000 | 0.500000 | 0.004779 | 0.000426 | 0.716010 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 13229.03 | 0.000289 | 369.22 |
CORE_MID VAV BOX REHEAT COIL | 394424.21 | 0.008628 | 14405.75 |
CORE_TOP VAV BOX REHEAT COIL | 93158.64 | 0.002038 | 3623.42 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13703.18 | 0.000300 | 532.75 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9750.23 | 0.000213 | 379.01 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16254.36 | 0.000356 | 631.78 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7457.74 | 0.000163 | 290.02 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 233508.74 | 0.005108 | 9071.64 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 156805.12 | 0.003430 | 6091.51 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 236142.72 | 0.005166 | 9173.87 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 149973.80 | 0.003281 | 5826.34 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29975.43 | 0.000656 | 1164.27 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19961.07 | 0.000437 | 775.28 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30255.24 | 0.000662 | 1175.13 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19469.51 | 0.000426 | 756.20 |
VAV_BOT WITH REHEAT HEATING COIL | 63059.34 | 0.001379 | 1275.31 |
VAV_MID WITH REHEAT HEATING COIL | 553140.19 | 0.012100 | 11325.84 |
VAV_TOP WITH REHEAT HEATING COIL | 53396.06 | 0.001168 | 1127.85 |
CAV_BAS HEATING COIL | 251976.46 | 0.005512 | 7805.51 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.36 | 2.29 | 12.72 | 2.81 | 10.82 | 10.82 | 0.300000 | 0.259705 | 10.82 |
VAV_MID WITH REHEAT | 61.23 | 22.84 | 122.46 | 42.20 | 100.93 | 100.93 | 0.300000 | 0.418139 | 100.93 |
VAV_TOP WITH REHEAT | 6.35 | 2.28 | 12.70 | 7.08 | 11.47 | 11.47 | 0.300000 | 0.617814 | 11.47 |
CAV_BAS | 5.88 | 5.88 | 5.88 | 5.88 | 5.88 | 5.88 | 1.00 | 1.00 | 5.88 |
AIRLOOP DATACENTER BASEMENT | 26.19 | 26.19 | 26.19 | 26.19 | 26.19 | 26.19 | 1.00 | 0.999989 | 26.19 |
AIRLOOP DATACENTER BOT | 0.594265 | 0.594265 | 0.594265 | 0.594265 | 0.594265 | 0.594265 | 1.00 | 1.00 | 0.594265 |
AIRLOOP DATACENTER MID | 5.71 | 5.71 | 5.71 | 5.71 | 5.71 | 5.71 | 1.00 | 1.00 | 5.71 |
AIRLOOP DATACENTER TOP | 0.582147 | 0.582147 | 0.582147 | 0.582147 | 0.582147 | 0.582147 | 1.00 | 1.00 | 0.582147 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.82 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 100.93 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.47 | |
CAV_BAS_OA_CONTROLLER | 5.88 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 26.19 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.594265 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.71 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.582147 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.89 | 6.67 | 10.64 | 0.006993 | 0.006993 | 164128.65 | 0.004694 | 10.82 |
VAV_MID WITH REHEAT COOLING COIL | 26.07 | 6.67 | 10.64 | 0.006972 | 0.006972 | 1548975.49 | 0.044301 | 100.93 |
VAV_TOP WITH REHEAT COOLING COIL | 25.76 | 6.67 | 10.64 | 0.006982 | 0.006982 | 172422.02 | 0.004931 | 11.47 |
CAV_BAS COOLING COIL | 26.11 | 6.67 | 11.10 | 0.007096 | 0.007096 | 87791.53 | 0.002511 | 5.88 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.82 |
VAV_MID WITH REHEAT FAN | 100.93 |
VAV_TOP WITH REHEAT FAN | 11.47 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004694 | 0.000101 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001379 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.044301 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.012100 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004931 | 0.000097 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001168 | |
CAV_BAS_COOLC_CONTROLLER | 0.002511 | 0.000190 |
CAV_BAS_HEATC_CONTROLLER | 0.005512 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.88 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 26.19 | 475103.24 | 248977.69 | 0.011635 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.594265 | 10475.10 | 5545.47 | 0.000257 |
AIRLOOP DATACENTER MID COOLING COIL | 5.71 | 100636.68 | 53267.20 | 0.002465 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.582147 | 10268.14 | 5434.38 | 0.000251 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 26.19 | 26.19 | 26.19 | 26.19 | 475103.24 | 475103.24 | 19243.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.594265 | 0.594265 | 0.594265 | 0.594265 | 10475.10 | 10475.10 | 888.99 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.71 | 5.71 | 5.71 | 5.71 | 100636.68 | 100636.68 | 8889.90 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.582147 | 0.582147 | 0.582147 | 0.582147 | 10268.14 | 10268.14 | 888.99 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 26.19 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.594265 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.71 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.582147 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 26.19 | 475103.24 | 0.011635 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.594265 | 10475.10 | 0.000257 |
AIRLOOP DATACENTER MID HEATING COIL | 5.71 | 100636.68 | 0.002465 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.582147 | 10268.14 | 0.000251 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 19243.92 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 888.99 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8889.90 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 888.99 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000174 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.056437 | 9123.15 | |
HEATSYS1 PUMP | 0.051311 | 15299.61 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.056437 | 6.77 |
HEATSYS1 | 0.051311 | 6.16 |
COOLSYS1_SUPPLY | 0.056437 | 6.77 |
SINGLE WATER PLANT LOOP | 0.014608 | 1.75 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.056437 | 0.056437 | 236892.88 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2345641.07 | 2345641.07 | 0.051311 |
CENTRAL BOILER | 601717.54 | 587978.86 | 0.014608 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.028218 | 3158.13 |
COOLSYS1 CHILLER2 PUMP | 0.028218 | 3158.13 |
PLANT CIRC PUMP | 0.014608 | 3688.84 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.056437 | 0.028664 | 1003368.13 | 1009474.58 | 0.050793 |
COOLSYS1 CHILLER2 | 0.056437 | 0.028664 | 1003368.13 | 1009474.58 | 0.050793 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014608 | 139666.47 | 54987.15 | 69833.23 | 7004.20 | 20957.47 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.101586 | 12.19 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.101586 | 24901.53 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 45.60 | 1199212.88 | 9.12 | 149901.61 |
TOWERWATERSYS COOLTOWER 2 | 45.60 | 1199212.88 | 9.12 | 149901.61 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.051888 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8378 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.8072 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 0.9232 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.026 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.072 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9158 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.24829308E-14 | 0.29135133E-16 | -0.15401821E-09 | 0.38773647E-16 |
51 | 8 | 0.22478683E-07 | 0.11333425E-12 | 0.38411067E-03 | -0.25559038E-09 |
52 | 7 | -0.12429992E-01 | 0.58464112E-08 | -0.23357103E-01 | 0.14133354E-03 |
53 | 6 | 0.41047043 | 0.20318695E-05 | 0.47644950 | -0.48081157E-02 |
54 | 5 | -5.2405281 | 0.75802388E-04 | -4.4747275 | 0.63803387E-01 |
55 | 4 | 33.223854 | 0.61961214E-03 | 21.571135 | -0.42505714 |
56 | 3 | -111.69641 | 0.13494874E-02 | -55.882598 | 1.5219877 |
57 | 2 | 197.59721 | 0.75863434E-03 | 78.112020 | -2.9081180 |
58 | 1 | -171.33669 | 0.80942272E-04 | -55.323717 | 2.7486048 |
59 | 0 | 57.057407 | 0.46049242E-06 | 15.547298 | |
60 | 9 | -0.15339349E-14 | 0.29979511E-16 | -0.15544574E-09 | 0.39943344E-16 |
61 | 8 | 0.22679133E-07 | 0.10934645E-12 | 0.38619381E-03 | -0.25786952E-09 |
62 | 7 | -0.12492075E-01 | 0.56288006E-08 | -0.23446467E-01 | 0.14203945E-03 |
63 | 6 | 0.41215724 | 0.19545976E-05 | 0.47788421 | -0.48279991E-02 |
64 | 5 | -5.2569880 | 0.72866980E-04 | -4.4857383 | 0.64007484E-01 |
65 | 4 | 33.296652 | 0.59522869E-03 | 21.614155 | -0.42602372 |
66 | 3 | -111.85128 | 0.12956249E-02 | -55.967640 | 1.5242251 |
67 | 2 | 197.75067 | 0.72797512E-03 | 78.190049 | -2.9105550 |
68 | 1 | -171.39336 | 0.77633808E-04 | -55.346469 | 2.7495981 |
69 | 0 | 57.057407 | 0.44138471E-06 | 15.543591 | |
70 | 9 | -0.23125622E-14 | 0.35111754E-16 | -0.15002006E-09 | 0.46457589E-16 |
71 | 8 | 0.21917045E-07 | 0.12438460E-12 | 0.37824022E-03 | -0.24920433E-09 |
72 | 7 | -0.12254923E-01 | 0.64545218E-08 | -0.23105067E-01 | 0.13934294E-03 |
73 | 6 | 0.40571362 | 0.22485912E-05 | 0.47240083 | -0.47520443E-02 |
74 | 5 | -5.1941091 | 0.84060576E-04 | -4.4436429 | 0.63227810E-01 |
75 | 4 | 33.018541 | 0.68839572E-03 | 21.449658 | -0.42233114 |
76 | 3 | -111.25962 | 0.15017871E-02 | -55.642450 | 1.5156770 |
77 | 2 | 197.16434 | 0.84550337E-03 | 77.891725 | -2.9012438 |
78 | 1 | -171.17681 | 0.90334265E-04 | -55.259577 | 2.7458027 |
79 | 0 | 57.057407 | 0.51475124E-06 | 15.557826 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9150E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9173E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6176E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6195E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7668E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7683E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6225E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6233E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9678E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1271E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6627E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8041E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8055E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9201E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6441E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6991E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1699 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5683E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1928 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7298E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1168 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7096E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7407E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6489E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9681E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1265E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6627E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8024E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8056E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9201E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6446E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7007E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9147E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9170E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6173E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6192E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7666E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7681E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6224E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6232E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6847E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9937E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3569E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6956E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1630E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2961E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4838E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5217E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2004E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0611E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6770E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7327E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0938E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5379E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9359E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8463E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5847E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6949E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2265E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3061E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1201E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1499E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4839E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5223E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7666E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7687E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3455E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3472E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0736E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0749E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6225E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6233E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8146E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9409E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3843E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4835E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1045E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1734E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6447E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7008E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4630E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3583E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4141E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7820E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0836E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1996E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7407E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6484E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8137E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9372E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3838E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4812E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1045E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1735E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6441E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6992E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7665E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7686E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3454E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3471E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0736E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0748E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6224E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6232E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6710E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7806E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3351E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4144E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1869E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2171E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4840E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5224E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3503E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1211E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8645E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8079E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2170E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5874E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9359E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8463E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7742E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0962E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4697E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8249E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2301E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3652E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4837E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5217E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1641 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1151 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1797 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1288 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1285 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9161E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8052E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8715E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.4114E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4212E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.8258E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0172E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2447E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7599E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9539E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9044E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5358E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.6906E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.3483E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9041E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9878E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1763E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8053E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8710E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.5811E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5041E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0381E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.1213E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3828E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8255E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9539E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9044E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1641 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1153 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1798 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1291 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1287 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9330E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8177E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8779E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.4161E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4278E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.8311E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0234E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2558E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7679E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9663E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9108E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5361E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.6948E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.3491E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9074E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9941E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1804E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8177E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8774E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.5860E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5109E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0437E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.1278E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3942E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8336E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9663E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9108E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 66056.07220 | 66056.07220 | 5.87659 | 5.87659 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72198.41656 | 72198.41656 | 6.42314 | 6.42314 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 677584.73957 | 677584.73957 | 60.26638 | 60.26638 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 262419.27323 | 262419.27323 | 13.65798 | 13.65798 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67432.40533 | 67432.40533 | 6.05247 | 6.05247 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 65219.09276 | 65219.09276 | 3.41853 | 3.41853 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12705.28702 | 12705.28702 | 1.14034 | 1.14034 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 9593.48285 | 9593.48285 | 0.50320 | 0.50320 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17197.66463 | 17197.66463 | 1.54353 | 1.54353 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 24.82267 | 5.46148E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 6825.06869 | 6825.06869 | 0.35813 | 0.35813 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18538.54614 | 18538.54614 | 1.66389 | 1.66389 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.16000 | 5.47412E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 11376.86212 | 11376.86212 | 0.59710 | 0.59710 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21748.84955 | 21748.84955 | 1.95201 | 1.95201 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5222.81901 | 5222.81901 | 0.27374 | 0.27374 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 120826.71226 | 120826.71226 | 10.84445 | 10.84445 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 163402.22953 | 163402.22953 | 8.58446 | 8.58446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 184704.53640 | 184704.53640 | 16.57744 | 16.57744 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 109724.31153 | 109724.31153 | 5.76498 | 5.76498 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 184531.79731 | 184531.79731 | 16.56205 | 16.56205 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 165243.74866 | 165243.74866 | 8.68144 | 8.68144 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 202860.17187 | 202860.17187 | 18.20694 | 18.20694 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 104948.01989 | 104948.01989 | 5.51351 | 5.51351 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13906.36509 | 13906.36509 | 1.24812 | 1.24812 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 20972.97068 | 20972.97068 | 1.10235 | 1.10235 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18530.80898 | 18530.80898 | 1.66315 | 1.66315 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.17933 | 5.46350E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 13965.99410 | 13965.99410 | 0.73410 | 0.73410 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20136.55944 | 20136.55944 | 1.80728 | 1.80728 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 21168.60539 | 21168.60539 | 1.11265 | 1.11265 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 21511.00438 | 21511.00438 | 1.93063 | 1.93063 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13622.27685 | 13622.27685 | 0.71601 | 0.71601 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8394.41491 | 8394.41491 | 0.59426 | 0.59426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 80622.07001 | 80622.07001 | 5.70750 | 5.70750 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8223.22076 | 8223.22076 | 0.58215 | 0.58215 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369966.33289 | 369966.33289 | 26.19058 | 26.19058 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 20.43200 | 5.45503E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -17.90000 | 9.55238E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 136876.64 | 10.81997 | 10.81997 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 61883.34 | 2.81000 | 2.81000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1267144.35 | 100.92896 | 100.92896 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 610740.48 | 42.20238 | 42.20238 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 145644.09 | 11.46567 | 11.46567 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 61194.40 | 7.08365 | 7.08365 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 02:50:00 |
7 | CAV_BAS | Cooling | Sensible | 68094.56 | 5.87659 | 5.87659 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 68251.22 | 1.20016 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367167.94 | 26.19088 | 26.19088 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 19243.92 | 0.33839 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8310.28 | 0.59426 | 0.59426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79823.11 | 5.70750 | 5.70750 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8889.90 | 0.15632 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8144.79 | 0.58215 | 0.58215 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.87659 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.42314 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29612 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61863 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78966 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28662E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.89385E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61863 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13229.03234 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.89385E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 369.22362 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 60.26638 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31561 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.15139 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84162 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20720E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.62804E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.15139 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 394424.20679 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.62804E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 14405.75210 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.05247 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31426 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26700 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61601 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83802 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21238E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03785E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.41853 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 93158.63621 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03785E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3623.42453 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14034 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20943 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17800 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20298 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55848 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81924E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.99758E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50320 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13703.18420 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.99758E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 532.74521 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.54353 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.97098E-002 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.50000E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13120 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.82109E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.13287E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35813 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9750.23151 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13287E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 379.00635 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.66389 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14353 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12200 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20299 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38276 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65441E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55565E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59710 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16254.36448 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55565E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 631.78351 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.95201 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.88445E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 6.70000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13078 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.83230E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63138E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27374 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7457.73933 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63138E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 290.01798 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.84445 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22022 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02791 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58726 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73006E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.10801E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.58446 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 233508.74066 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.10801E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9071.63571 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.57744 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.10383E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43012E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.76498 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 156805.11690 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43012E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6091.50776 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.56205 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14420 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03713 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38453 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64215E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.16563E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.68144 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 236142.72298 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16563E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9173.86616 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.20694 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.45310E-002 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.20000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31090 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.50722E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28068E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.51351 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 149973.79683 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28068E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5826.34404 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24812 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19134 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16300 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20344 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51025 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99117E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.55713E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10235 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29975.42681 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.55713E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1164.27159 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.66315 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.25382E-002 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.90000E-002 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13139 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.11722E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.36649E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73410 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19961.06773 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.36649E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 775.28479 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80728 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13215 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20242 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35239 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88316E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.61834E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.11265 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30255.23832 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.61834E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1175.13177 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.93063 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.97177E-002 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 6.80000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13128 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.77937E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.25896E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71601 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19469.51184 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.25896E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 756.20274 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.59426 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.70750 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58215 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 26.19058 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.36146 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28659 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.72291 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.81000 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.81997 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.81997 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.25970 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 61.22864 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.83695 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 122.45728 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 42.20238 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 100.92896 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 100.92896 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.41814 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.35082 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28454 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.70165 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.08365 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.46567 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.46567 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.61781 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.87659 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.87659 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.87659 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.87659 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.87659 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.87659 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.19058 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.19058 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.19058 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.19058 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.19088 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 26.19088 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.59426 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.59426 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.59426 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.59426 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.59426 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.59426 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.70750 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.70750 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.70750 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.70750 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.70750 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.70750 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58215 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58215 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58215 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58215 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58215 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.58215 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.81997 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 100.92896 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.46567 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.87659 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 26.19088 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.59426 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.70750 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.58215 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.81997 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.88667 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63946 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.99259E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.99259E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 164128.65349 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.69406E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.81997 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 63059.33671 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37942E-003 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1275.30942 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.81997 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.69406E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.01445E-004 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37942E-003 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 100.92896 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.06621 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63938 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.97222E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.97222E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1548975.48617 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.43005E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 100.92896 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 553140.19065 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21000E-002 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11325.83889 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 100.92896 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.43005E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.07491E-005 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.21000E-002 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.46567 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.75530 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63942 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.98225E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.98225E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 172422.01832 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.93125E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.46567 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53396.06464 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16804E-003 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1127.85446 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.46567 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.93125E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.65659E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.16804E-003 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.87659 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.10927 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09593 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09582E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09582E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 87791.53247 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.51083E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.87659 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 251976.45986 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.51199E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7805.51402 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.87659 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51083E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.89655E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.51199E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.19088 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.19088 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 475103.23858 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 248977.68790 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16352E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 26.19088 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 26.19088 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 26.19088 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 26.19088 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 475103.23858 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 475103.23858 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 19243.92393 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 26.19088 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.19088 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 475103.23858 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16352E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 19243.92393 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.74126E-004 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.59426 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59426 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10475.10338 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5545.46508 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.56535E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.59426 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.59426 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.59426 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.59426 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10475.10338 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10475.10338 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.59426 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59426 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10475.10338 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.56535E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.70750 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.70750 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 100636.68189 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 53267.20119 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.46459E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.70750 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.70750 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.70750 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.70750 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 100636.68189 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 100636.68189 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8889.89563 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.70750 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.70750 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 100636.68189 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.46459E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8889.89563 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58215 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58215 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10268.13864 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5434.38189 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51466E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.58215 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.58215 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.58215 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.58215 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10268.13864 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10268.13864 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58215 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58215 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10268.13864 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51466E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.64366E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9123.14670 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.64366E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.77240 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.64366E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.64366E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 236892.88001 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.13110E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.15732 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.13110E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 15299.61278 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2345641.06880 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2345641.07000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.13110E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.64366E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.77240 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.82183E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3158.13106 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.82183E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3158.13106 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.64366E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.86642E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1003368.13320 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1009474.58000 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.07932E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.64366E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.86642E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1003368.13320 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1009474.58000 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.07932E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.46078E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.75294 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.46078E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3688.83984 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.46078E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 54987.15067 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20957.47468 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 601717.53779 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 587978.86000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.46078E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10159 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.19037 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10159 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 24901.53346 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 45.59533 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1199212.88191 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.11907 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 149901.61024 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 45.59533 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1199212.88191 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.11907 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 149901.61024 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.18875E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.18875E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18421.53 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 549459.94 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 129748.89 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19085.45 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13579.88 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 22638.68 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10386.95 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 325225.57 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 218394.56 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 328894.13 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 208880.04 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 41749.10 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 27801.33 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 42138.81 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 27116.70 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 61979.60 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 553343.03 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 55778.73 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 261473.27 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 207412.19 | 139405.07 | 68007.12 | 0.67 | 29052.94 | 294.67 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1946615.75 | 1304463.41 | 642152.34 | 0.67 | 271154.49 | 2750.20 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 218784.70 | 147378.57 | 71406.13 | 0.67 | 30774.46 | 312.13 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 109334.28 | 74169.25 | 35165.03 | 0.68 | 14424.64 | 146.30 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.90 | 23.54 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.90 | 23.54 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.838 | 0.744 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.807 | 0.720 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.923 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2493277900 | 0.1981905938 | Pass | Pass | 40.8570986339 | 438.4116343495 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.0781792789E-002 | 0.1591540189 | Pass | Pass | 0.1609202078 | 0.3666590118 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.6227682831E-002 | 0.1006376072 | Pass | Pass | 0.1327532082 | 0.3380962421 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.5791968958E-002 | 4.3067704401E-002 | Pass | Pass | 0.4382996814 | 0.4876167021 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.6740446616E-002 | 9.7363999395E-002 | Pass | Pass | 0.1602734305 | 0.3647957805 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1405886659 | 0.2172314942 | Pass | Pass | 0.1873407915 | 0.4392766713 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3245357251 | 0.6010644998 | Pass | Pass | 0.1921494068 | 0.4307672115 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1186883738 | 0.1986503170 | Pass | Pass | 0.1694424023 | 0.3915324149 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.3216964006E-002 | 4.1219107945E-002 | Pass | Pass | 0.1329959202 | 0.3348826643 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1226853755 | 0.1757722199 | Pass | Pass | 0.1360698749 | 0.3464368758 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3591739780 | 0.6233148909 | Pass | Pass | 0.1762984139 | 0.4418490093 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1046869720 | 0.1217482908 | Pass | Pass | 0.1296618676 | 0.3262994230 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2574252011 | 0.3146745171 | Pass | Pass | 25.8949300268 | 106.1284703569 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2025919900 | 0.2447658341 | Pass | Pass | 19.3485293663 | 136.8499654499 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2600162749 | 0.2926965309 | Pass | Pass | 0.7700091937 | 3.3060381234 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1500883928 | 0.1551965569 | Pass | Pass | 2.1914040193 | 14.4227562013 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.5370587708E-002 | 3.7236012616E-002 | Pass | Pass | 0.2846395572 | 0.7657960433 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9445465485E-002 | 6.5958206435E-002 | Pass | Pass | 0.2180964264 | 0.5687704013 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1000733171 | 8.1860050361E-002 | Pass | Pass | 0.5205652159 | 0.8005322339 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7501178367E-006 | 9.3903300453E-006 | Pass | Pass | 8.1759734887E-003 | 1.0331999269E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2157931299E-006 | 8.8394242501E-006 | Pass | Pass | 0.1426238335 | 0.3298763662 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.5180454006E-002 | 4.8256371004E-002 | Pass | Pass | 3.6329085112E-002 | 0.1246393248 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.6992455461E-005 | 4.4625137703E-005 | Pass | Pass | 9.0793733624E-005 | 1.0980297768E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7811.78 | 198.95 | 0.00 | 26630.62 | 12452.56 | 47093.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.744 | 0.838 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.720 | 0.807 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.811 | 0.923 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.19 | 0.0000 | Y | 7.54 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.16 | 0.0000 | Y | 4.85 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.93 | 0.0000 | Y | 7.45 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.91 | 0.0000 | Y | 4.80 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.16 | 0.0000 | Y | 75.34 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.13 | 0.0000 | Y | 48.48 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.91 | 0.0000 | Y | 74.48 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 47.96 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.16 | 0.0000 | Y | 7.53 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.13 | 0.0000 | Y | 4.85 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.91 | 0.0000 | Y | 7.45 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.89 | 0.0000 | Y | 4.80 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 540.46 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.26 | 42.26 | 102.76 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.67 | 62.97 | 10.87 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.67 | 46.88 | 151.50 | |
Exterior Lighting Total | 31088.59 | 265.13 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1967239.70 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2345641.07 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1009474.58 | 5.60 | 978058.60 | 4.71 | 6.90 | 23.54 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1009474.58 | 5.60 | 978058.60 | 4.71 | 6.90 | 23.54 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 587978.86 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1199212.88 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1199212.88 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 164128.65 | 207412.19 | 139405.07 | 68007.12 | 0.67 | - | 29052.94 | 294.67 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1548975.49 | 1946615.75 | 1304463.41 | 642152.34 | 0.67 | - | 271154.49 | 2750.20 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 172422.02 | 218784.70 | 147378.57 | 71406.13 | 0.67 | - | 30774.46 | 312.13 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 87791.53 | 109334.28 | 74169.25 | 35165.03 | 0.68 | - | 14424.64 | 146.30 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 475103.24 | 248977.69 | 226125.55 | 0.52 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10475.10 | 5545.47 | 4929.64 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 100636.68 | 53267.20 | 47369.48 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10268.14 | 5434.38 | 4833.76 | 0.53 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 13229.03 | 18421.53 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 394424.21 | 549459.94 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 93158.64 | 129748.89 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13703.18 | 19085.45 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9750.23 | 13579.88 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16254.36 | 22638.68 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7457.74 | 10386.95 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 233508.74 | 325225.57 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 156805.12 | 218394.56 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 236142.72 | 328894.13 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 149973.80 | 208880.04 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 29975.43 | 41749.10 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19961.07 | 27801.33 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30255.24 | 42138.81 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19469.51 | 27116.70 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 63059.34 | 61979.60 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 553140.19 | 553343.03 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 53396.06 | 55778.73 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 251976.46 | 261473.27 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 475103.24 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10475.10 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 100636.68 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10268.14 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 19243.92 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8889.90 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.82 | 23257.14 | 2149.46 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 100.93 | 216943.22 | 2149.46 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.47 | 24645.05 | 2149.46 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.88 | 9964.67 | 1695.65 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 26.19 | 43014.11 | 1642.33 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.59 | 665.64 | 1120.11 | 1.00 | 1.53 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.71 | 6393.02 | 1120.11 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 652.07 | 1120.11 | 1.00 | 1.54 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.056437 | 9123.15 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.051311 | 15299.61 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028218 | 3158.13 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028218 | 3158.13 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014608 | 3688.84 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.101586 | 24901.53 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 66056.07 | 66056.07 | 23.77 | 5.877 | 5.877 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00753 | 22.95 | 0.00546 | 1.200 | 0.00 |
CORE_BOTTOM | 72198.42 | 72198.42 | 28.92 | 6.423 | 6.423 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 22.95 | 0.00546 | 1.078 | 0.00 |
CORE_MID | 677584.74 | 677584.74 | 271.46 | 60.266 | 60.266 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 22.95 | 0.00546 | 10.778 | 0.00 |
CORE_TOP | 67432.41 | 67432.41 | 27.01 | 6.052 | 6.052 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00745 | 33.90 | 0.00548 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12705.29 | 12705.29 | 40.54 | 1.140 | 1.140 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00727 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17197.66 | 17197.66 | 85.15 | 1.544 | 1.544 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 24.00 | 24.00 | 0.00713 | 24.82 | 0.00546 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18538.55 | 18538.55 | 59.15 | 1.664 | 1.664 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00718 | 33.16 | 0.00547 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21748.85 | 21748.85 | 107.68 | 1.952 | 1.952 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00710 | 32.03 | 0.00547 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 120826.71 | 120826.71 | 385.52 | 10.844 | 10.844 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00724 | 33.90 | 0.00548 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 184704.54 | 184704.54 | 914.49 | 16.577 | 16.577 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00710 | 25.76 | 0.00546 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 184531.80 | 184531.80 | 588.77 | 16.562 | 16.562 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00716 | 33.41 | 0.00547 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 202860.17 | 202860.17 | 1004.38 | 18.207 | 18.207 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00709 | 31.83 | 0.00547 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13906.37 | 13906.37 | 44.37 | 1.248 | 1.248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00719 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18530.81 | 18530.81 | 91.75 | 1.663 | 1.663 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00709 | 26.18 | 0.00546 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20136.56 | 20136.56 | 64.25 | 1.807 | 1.807 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00713 | 33.53 | 0.00547 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 21511.00 | 21511.00 | 106.50 | 1.931 | 1.931 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00708 | 31.83 | 0.00547 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8394.41 | 8394.41 | 231.87 | 0.594 | 0.594 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80622.07 | 80622.07 | 2226.96 | 5.708 | 5.708 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8223.22 | 8223.22 | 227.14 | 0.582 | 0.582 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369966.33 | 369966.33 | 472.09 | 26.191 | 26.191 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 20.43 | 0.00546 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 23.98 | 0.00096 | -17.90 | 0.00096 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 17.60 | 21.43 | 0.00096 | -17.90 | 0.00096 | 1.078 | 0.00 |
CORE_MID | 262419.27 | 262419.27 | 105.13 | 13.658 | 13.658 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 10.778 | 0.00 |
CORE_TOP | 65219.09 | 65219.09 | 26.13 | 3.419 | 3.419 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 9593.48 | 9593.48 | 30.61 | 0.503 | 0.503 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 6825.07 | 6825.07 | 33.79 | 0.358 | 0.358 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 11376.86 | 11376.86 | 36.30 | 0.597 | 0.597 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5222.82 | 5222.82 | 25.86 | 0.274 | 0.274 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 163402.23 | 163402.23 | 521.36 | 8.584 | 8.584 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 109724.31 | 109724.31 | 543.26 | 5.765 | 5.765 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 165243.75 | 165243.75 | 527.23 | 8.681 | 8.681 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 104948.02 | 104948.02 | 519.61 | 5.514 | 5.514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 20972.97 | 20972.97 | 66.92 | 1.102 | 1.102 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13965.99 | 13965.99 | 69.15 | 0.734 | 0.734 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21168.61 | 21168.61 | 67.54 | 1.113 | 1.113 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13622.28 | 13622.28 | 67.45 | 0.716 | 0.716 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -17.90 | 0.00096 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 18.00 | 25.57 | 0.00596 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 22.83 | 0.00166 | -17.90 | 0.00096 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 20.66 | 0.00163 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 18.00 | 27.00 | 0.00700 | -17.90 | 0.00096 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.82 | 10.82 | 2.81 | 2.81 | 10.8200 | 2.8100 | 10.8200 | 0.2597 | 0.3000 |
VAV_MID WITH REHEAT | 100.93 | 100.93 | 42.20 | 42.20 | 100.9290 | 42.2024 | 100.9290 | 0.4181 | 0.3000 |
VAV_TOP WITH REHEAT | 11.47 | 11.47 | 7.08 | 7.08 | 11.4657 | 7.0836 | 11.4657 | 0.6178 | 0.3000 |
CAV_BAS | 5.88 | 5.88 | 1.20 | 1.20 | 5.8766 | 5.8766 | 5.8766 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.19 | 26.19 | 0.34 | 0.34 | 26.1909 | 26.1906 | 26.1909 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.59 | 0.59 | 0.02 | 0.02 | 0.5943 | 0.5943 | 0.5943 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.71 | 5.71 | 0.16 | 0.16 | 5.7075 | 5.7075 | 5.7075 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.58 | 0.58 | 0.02 | 0.02 | 0.5821 | 0.5821 | 0.5821 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 13229.032 | 13229.032 | 1.618631 | 0.00028939 | 369.224 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 13229.03 | 13229.03 | 1.618631 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 13251.74 | 13251.74 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 394424.207 | 394424.207 | 16.151390 | 0.00862804 | 14405.752 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 394424.21 | 394424.21 | 16.151390 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 262419.27 | 0.00 | 395309.14 | 395309.14 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 93158.636 | 93158.636 | 3.418527 | 0.00203785 | 3623.425 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 93158.64 | 93158.64 | 3.418527 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 65219.09 | 0.00 | 93357.01 | 93357.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13703.184 | 13703.184 | 0.503203 | 0.00029976 | 532.745 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13703.18 | 13703.18 | 0.503203 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768128 | 40.3304 | 9593.48 | 0.00 | 13732.37 | 13732.37 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9750.232 | 9750.232 | 0.358129 | 0.00021329 | 379.006 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9750.23 | 9750.23 | 0.358129 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00772830 | 40.5740 | 6825.07 | 0.00 | 9771.00 | 9771.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16254.364 | 16254.364 | 0.597098 | 0.00035556 | 631.784 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16254.36 | 16254.36 | 0.597098 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777090 | 40.7946 | 11376.86 | 0.00 | 16288.98 | 16288.98 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7457.739 | 7457.739 | 0.273744 | 0.00016314 | 290.018 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7457.74 | 7457.74 | 0.273744 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00751730 | 39.4806 | 5222.82 | 0.00 | 7473.62 | 7473.62 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 233508.741 | 233508.741 | 8.584465 | 0.00510801 | 9071.636 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 233508.74 | 233508.74 | 8.584465 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768045 | 40.3271 | 163402.23 | 0.00 | 234006.10 | 234006.10 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 156805.117 | 156805.117 | 5.764983 | 0.00343012 | 6091.508 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 156805.12 | 156805.12 | 5.764983 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768331 | 40.3420 | 109724.31 | 0.00 | 157139.11 | 157139.11 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 236142.723 | 236142.723 | 8.681441 | 0.00516563 | 9173.866 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 236142.72 | 236142.72 | 8.681441 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768405 | 40.3458 | 165243.75 | 0.00 | 236645.70 | 236645.70 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 149973.797 | 149973.797 | 5.513510 | 0.00328068 | 5826.344 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 149973.80 | 149973.80 | 5.513510 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00766880 | 40.2668 | 104948.02 | 0.00 | 150293.23 | 150293.23 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 29975.427 | 29975.427 | 1.102352 | 0.00065571 | 1164.272 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29975.43 | 29975.43 | 1.102352 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769188 | 40.3870 | 20972.97 | 0.00 | 30039.28 | 30039.28 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 19961.068 | 19961.068 | 0.734102 | 0.00043665 | 775.285 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19961.07 | 19961.07 | 0.734102 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769149 | 40.3851 | 13965.99 | 0.00 | 20003.59 | 20003.59 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 30255.238 | 30255.238 | 1.112654 | 0.00066183 | 1175.132 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30255.24 | 30255.24 | 1.112654 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769461 | 40.4012 | 21168.61 | 0.00 | 30319.68 | 30319.68 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 19469.512 | 19469.512 | 0.716010 | 0.00042590 | 756.203 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19469.51 | 19469.51 | 0.716010 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768423 | 40.3475 | 13622.28 | 0.00 | 19510.98 | 19510.98 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 164128.653 | -999.000 | 10.819967 | 0.00469406 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 164128.65 | 164128.65 | 10.819967 | 25.89 | 13.65 | 0.00699259 | 10.64 | 7.85 | 0.00699259 | 33.90 | 0.00547527 | 15.07 | 18.7662 | 24.00 | 0.00735007 | 32.1774 | 118644.89 | 0.00 | 138286.29 | 138286.29 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 63059.337 | 63059.337 | 3.245990 | 0.00137942 | 1275.309 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 63059.34 | 63059.34 | 3.245990 | -6.98 | -7.39 | 0.00233711 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 62.5541 | 21.13 | 0.00562149 | 29.3665 | 27619.64 | 0.00 | 53952.73 | 53952.73 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1548975.486 | -999.000 | 100.928959 | 0.04430050 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1548975.49 | 1548975.49 | 100.928959 | 26.07 | 13.69 | 0.00697222 | 10.64 | 7.83 | 0.00697222 | 33.90 | 0.00547527 | 15.07 | 20.1191 | 24.00 | 0.00736728 | 32.2517 | 1083504.29 | 0.00 | 1304337.89 | 1304337.89 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 553140.191 | 553140.191 | 30.278688 | 0.01209996 | 11325.839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 553140.19 | 553140.19 | 30.278688 | -5.80 | -5.80 | 0.00311536 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 67.0637 | 18.16 | 0.00745135 | 46.6835 | 227510.81 | 0.00 | 481802.25 | 481802.25 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 172422.018 | -999.000 | 11.465668 | 0.00493125 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 172422.02 | 172422.02 | 11.465668 | 25.76 | 13.59 | 0.00698225 | 10.64 | 7.84 | 0.00698225 | 33.90 | 0.00547527 | 15.07 | 17.7094 | 24.00 | 0.00730723 | 31.9918 | 127525.94 | 0.00 | 144972.24 | 144972.24 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 53396.065 | 53396.065 | 3.439700 | 0.00116804 | 1127.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 02:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 53396.06 | 53396.06 | 3.439700 | -3.01 | -3.01 | 0.00363152 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 59.0313 | 16.29 | 0.00756084 | 53.3173 | 23309.51 | 0.00 | 48578.34 | 48578.34 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 87791.532 | -999.000 | 5.876591 | 0.00251083 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 87791.53 | 87791.53 | 5.876591 | 26.11 | 13.81 | 0.00709582 | 11.10 | 8.15 | 0.00709582 | 33.16 | 0.00547412 | 14.83 | 20.4227 | 24.00 | 0.00758131 | 33.1780 | 58036.09 | 0.00 | 74333.97 | 74333.97 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 251976.460 | 251976.460 | 5.876591 | 0.00551199 | 7805.514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 251976.46 | 251976.46 | 5.876591 | -3.66 | -7.74 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.4227 | 24.08 | 0.00095524 | 4.2037 | 0.00 | 0.00 | 187103.08 | 187103.08 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 475103.239 | 248977.688 | 26.190875 | 0.01163525 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 403826.51 | 402860.46 | -999.0 | 28.80 | 14.65 | 0.00702208 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | -999.0000 | 27.00 | 0.00704235 | 25.8139 | 369591.91 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10475.103 | 5545.465 | 0.594265 | 0.00025653 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8856.18 | 8813.59 | -999.0 | 28.20 | 14.47 | 0.00704337 | 12.80 | 8.76 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | -999.0000 | 27.00 | 0.00708596 | 25.9700 | 8394.41 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100636.682 | 53267.201 | 5.707505 | 0.00246459 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 85088.05 | 84663.37 | -999.0 | 28.21 | 14.47 | 0.00704503 | 12.80 | 8.76 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | -999.0000 | 27.00 | 0.00708946 | 25.9828 | 80622.07 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10268.139 | 5434.382 | 0.582147 | 0.00025147 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8682.28 | 8639.87 | -999.0 | 28.21 | 14.47 | 0.00704408 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708759 | 25.9760 | 8221.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 475103.239 | 475103.239 | 26.190875 | 0.01163525 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 475103.24 | 475103.24 | 26.190875 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2920 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10475.103 | 10475.103 | 0.594265 | 0.00025653 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10475.10 | 10475.10 | 0.594265 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6305 | 26.13 | 0.00596249 | 23.0362 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100636.682 | 100636.682 | 5.707505 | 0.00246459 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100636.68 | 100636.68 | 5.707505 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7389 | 23.97 | 0.00166086 | 7.3494 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10268.139 | 10268.139 | 0.582147 | 0.00025147 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10268.14 | 10268.14 | 0.582147 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6853 | 22.67 | 0.00162697 | 7.7871 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 19243.92 | 19243.92 | 26.190875 | -0.23 | -0.23 | 0.00692190 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2920 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.594265 | -0.47 | -0.47 | 0.00583077 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6305 | 26.13 | 0.00596249 | 23.0362 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8889.90 | 8889.90 | 5.707505 | -0.49 | -4.69 | 0.00164154 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7389 | 23.97 | 0.00166086 | 7.3494 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.582147 | -0.48 | -4.73 | 0.00160893 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6853 | 22.67 | 0.00162697 | 7.7871 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 13229.032 | 13229.032 | 1.618631 | 0.00028939 | 369.224 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 0.5529 | 0.563984 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | Sensible | 13229.03 | 13229.03 | 1.0000 | 1.58211069 | 1.618631 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.28935593 | 60.00 | 48.89 | 11.11 | 0.000 | 13229.03 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 13251.74 | 13251.74 | 1.58211069 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 394424.207 | 394424.207 | 16.151390 | 0.00862804 | 14405.752 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 16.4835 | 16.815199 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 394424.21 | 394424.21 | 1.0000 | 15.78697607 | 16.151390 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 8.62716033 | 60.00 | 48.89 | 11.11 | 0.000 | 394424.21 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 262419.27 | 0.00 | 395309.14 | 395309.14 | 15.78697607 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.36 | 20.39 | 0.00800000 | 58100.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 93158.636 | 93158.636 | 3.418527 | 0.00203785 | 3623.425 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 3.8932 | 3.971564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 93158.64 | 93158.64 | 1.0000 | 3.34139711 | 3.418527 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.03763987 | 60.00 | 48.89 | 11.11 | 0.000 | 93158.64 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 65219.09 | 0.00 | 93357.01 | 93357.01 | 3.34139711 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13703.184 | 13703.184 | 0.503203 | 0.00029976 | 532.745 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 0.5727 | 0.584198 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13703.18 | 13703.18 | 1.0000 | 0.49184954 | 0.503203 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.29972696 | 60.00 | 48.89 | 11.11 | 0.000 | 13703.18 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768128 | 21.00 | 0.00768128 | 40.3304 | 9593.48 | 0.00 | 13732.37 | 13732.37 | 0.49184954 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9750.232 | 9750.232 | 0.358129 | 0.00021329 | 379.006 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 0.4075 | 0.415674 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9750.23 | 9750.23 | 1.0000 | 0.35004872 | 0.358129 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.21326483 | 60.00 | 48.89 | 11.11 | 0.000 | 9750.23 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00772830 | 21.00 | 0.00772830 | 40.5740 | 6825.07 | 0.00 | 9771.00 | 9771.00 | 0.35004872 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16254.364 | 16254.364 | 0.597098 | 0.00035556 | 631.784 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 0.6793 | 0.692960 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16254.36 | 16254.36 | 1.0000 | 0.58362650 | 0.597098 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.35552840 | 60.00 | 48.89 | 11.11 | 0.000 | 16254.36 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00777090 | 21.00 | 0.00777090 | 40.7946 | 11376.86 | 0.00 | 16288.98 | 16288.98 | 0.58362650 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7457.739 | 7457.739 | 0.273744 | 0.00016314 | 290.018 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 0.3117 | 0.317940 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7457.74 | 7457.74 | 1.0000 | 0.26756736 | 0.273744 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.16312161 | 60.00 | 48.89 | 11.11 | 0.000 | 7457.74 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00751730 | 21.00 | 0.00751730 | 39.4806 | 5222.82 | 0.00 | 7473.62 | 7473.62 | 0.26756736 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 233508.741 | 233508.741 | 8.584465 | 0.00510801 | 9071.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 9.7586 | 9.955007 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 233508.74 | 233508.74 | 1.0000 | 8.39077885 | 8.584465 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 5.10748912 | 60.00 | 48.89 | 11.11 | 0.000 | 233508.74 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768045 | 21.00 | 0.00768045 | 40.3271 | 163402.23 | 0.00 | 234006.10 | 234006.10 | 8.39077885 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60948.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 156805.117 | 156805.117 | 5.764983 | 0.00343012 | 6091.508 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 6.5531 | 6.684958 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 156805.12 | 156805.12 | 1.0000 | 5.63491130 | 5.764983 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 3.42976638 | 60.00 | 48.89 | 11.11 | 0.000 | 156805.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768331 | 21.00 | 0.00768331 | 40.3420 | 109724.31 | 0.00 | 157139.11 | 157139.11 | 5.63491130 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60946.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 236142.723 | 236142.723 | 8.681441 | 0.00516563 | 9173.866 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 9.8687 | 10.067300 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 236142.72 | 236142.72 | 1.0000 | 8.48556706 | 8.681441 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 5.16510168 | 60.00 | 48.89 | 11.11 | 0.000 | 236142.72 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768405 | 21.00 | 0.00768405 | 40.3458 | 165243.75 | 0.00 | 236645.70 | 236645.70 | 8.48556706 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60947.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 149973.797 | 149973.797 | 5.513510 | 0.00328068 | 5826.344 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 6.2676 | 6.393723 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 149973.80 | 149973.80 | 1.0000 | 5.38911171 | 5.513510 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 3.28034631 | 60.00 | 48.89 | 11.11 | 0.000 | 149973.80 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00766880 | 21.00 | 0.00766880 | 40.2668 | 104948.02 | 0.00 | 150293.23 | 150293.23 | 5.38911171 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60948.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29975.427 | 29975.427 | 1.102352 | 0.00065571 | 1164.272 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 1.2527 | 1.277920 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29975.43 | 29975.43 | 1.0000 | 1.07748069 | 1.102352 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.65564640 | 60.00 | 48.89 | 11.11 | 0.000 | 29975.43 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00769188 | 21.00 | 0.00769188 | 40.3870 | 20972.97 | 0.00 | 30039.28 | 30039.28 | 1.07748069 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60939.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19961.068 | 19961.068 | 0.734102 | 0.00043665 | 775.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 0.8342 | 0.850986 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19961.07 | 19961.07 | 1.0000 | 0.71753916 | 0.734102 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.43660437 | 60.00 | 48.89 | 11.11 | 0.000 | 19961.07 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00769149 | 21.00 | 0.00769149 | 40.3851 | 13965.99 | 0.00 | 20003.59 | 20003.59 | 0.71753916 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60937.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30255.238 | 30255.238 | 1.112654 | 0.00066183 | 1175.132 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 1.2644 | 1.289849 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 30255.24 | 30255.24 | 1.0000 | 1.08755004 | 1.112654 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.66176667 | 60.00 | 48.89 | 11.11 | 0.000 | 30255.24 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00769461 | 21.00 | 0.00769461 | 40.4012 | 21168.61 | 0.00 | 30319.68 | 30319.68 | 1.08755004 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60938.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19469.512 | 19469.512 | 0.716010 | 0.00042590 | 756.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 0.8137 | 0.830029 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19469.51 | 19469.51 | 1.0000 | 0.69985502 | 0.716010 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.42585267 | 60.00 | 48.89 | 11.11 | 0.000 | 19469.51 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768423 | 21.00 | 0.00768423 | 40.3475 | 13622.28 | 0.00 | 19510.98 | 19510.98 | 0.69985502 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60938.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 164128.653 | -999.000 | 10.819967 | 0.00469406 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8389 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.819967 | 10.57584276 | 4197.9300 | 999.8980 | 56.43087903 | 15.00 | 6.67 | 8.33 | 1973317.69 | 8.3174 | 8.317396 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 164128.65 | 164128.65 | 1.0000 | 10.57584276 | 10.819967 | 25.89 | 13.65 | 0.00699259 | 43836.5 | 10.64 | 7.85 | 0.00699259 | 28317.3 | 4.69357987 | 6.67 | 15.00 | 8.33 | 23257.136 | 140871.52 | 33.90 | 0.00547527 | 15.07 | 2.03050000 | 18.7662 | 24.00 | 0.00735007 | 24.00 | 0.00735007 | 32.1774 | 118644.89 | 0.00 | 138286.29 | 138286.29 | 10.57584276 | 25.89 | 15.75 | 0.00699259 | 43836.5 | 13.04 | 10.65 | 0.00699259 | 30760.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 63059.337 | 63059.337 | 3.245990 | 0.00137942 | 1275.309 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.819967 | 10.57584276 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 2.6353 | 2.688363 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 63059.34 | 63059.34 | 1.0000 | 3.17275283 | 3.245990 | -6.98 | -7.39 | 0.00233711 | -1198.3 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 1.37928403 | 60.00 | 48.89 | 11.11 | 0.000 | 63059.34 | -17.90 | 0.00095524 | -17.90 | 2.03050000 | 62.5541 | 11.26 | 0.00464557 | 21.13 | 0.00562149 | 29.3665 | 27619.64 | 0.00 | 53952.73 | 53952.73 | 3.17275283 | 2.80 | -0.66 | 0.00233711 | 8670.7 | 19.65 | 8.49 | 0.00233711 | 25675.7 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1548975.486 | -999.000 | 100.928959 | 0.04430050 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8010 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.928959 | 98.65176070 | 4197.9300 | 999.8980 | 56.43087903 | 15.00 | 6.67 | 8.33 | 1973317.69 | 78.4960 | 78.496002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1548975.49 | 1548975.49 | 1.0000 | 98.65176070 | 100.928959 | 26.07 | 13.69 | 0.00697222 | 43967.3 | 10.64 | 7.83 | 0.00697222 | 28265.9 | 44.29598371 | 6.67 | 15.00 | 8.33 | 216943.221 | 1332032.27 | 33.90 | 0.00547527 | 15.07 | 20.30600000 | 20.1191 | 24.00 | 0.00736728 | 24.00 | 0.00736728 | 32.2517 | 1083504.29 | 0.00 | 1304337.89 | 1304337.89 | 98.65176070 | 26.07 | 15.80 | 0.00697222 | 43967.3 | 13.08 | 10.65 | 0.00697222 | 30745.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 553140.191 | 553140.191 | 30.278688 | 0.01209996 | 11325.839 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.928959 | 98.65176070 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 23.1164 | 23.581621 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 553140.19 | 553140.19 | 1.0000 | 29.59552821 | 30.278688 | -5.80 | -5.80 | 0.00311536 | 1930.0 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 12.09872272 | 60.00 | 48.89 | 11.11 | 0.000 | 553140.19 | -17.90 | 0.00095524 | -17.90 | 20.30600000 | 67.0637 | 18.84 | 0.00751371 | 18.16 | 0.00745135 | 46.6835 | 227510.81 | 0.00 | 481802.25 | 481802.25 | 29.59552821 | 2.80 | 0.69 | 0.00311536 | 10621.1 | 18.91 | 9.03 | 0.00311536 | 26900.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 172422.018 | -999.000 | 11.465668 | 0.00493125 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8196 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.465668 | 11.20697468 | 4197.9300 | 999.8980 | 56.43087903 | 15.00 | 6.67 | 8.33 | 1973317.69 | 8.7377 | 8.737672 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 172422.02 | 172422.02 | 1.0000 | 11.20697468 | 11.465668 | 25.76 | 13.59 | 0.00698225 | 43676.4 | 10.64 | 7.84 | 0.00698225 | 28291.2 | 4.93074486 | 6.67 | 15.00 | 8.33 | 24645.046 | 147776.97 | 33.90 | 0.00547527 | 15.07 | 2.03050000 | 17.7094 | 24.00 | 0.00730723 | 24.00 | 0.00730723 | 31.9918 | 127525.94 | 0.00 | 144972.24 | 144972.24 | 11.20697468 | 25.76 | 15.69 | 0.00698225 | 43676.4 | 13.05 | 10.64 | 0.00698225 | 30740.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53396.065 | 53396.065 | 3.439700 | 0.00116804 | 1127.854 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.465668 | 11.20697468 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 2.2315 | 2.276395 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 02:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 53396.06 | 53396.06 | 1.0000 | 3.36209240 | 3.439700 | -3.01 | -3.01 | 0.00363152 | 6042.4 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 1.16792125 | 60.00 | 48.89 | 11.11 | 0.000 | 53396.06 | -17.90 | 0.00095524 | -17.90 | 2.03050000 | 59.0313 | 18.46 | 0.00748774 | 16.29 | 0.00756084 | 53.3173 | 23309.51 | 0.00 | 48578.34 | 48578.34 | 3.36209240 | 2.80 | 1.43 | 0.00363152 | 11914.7 | 17.08 | 8.78 | 0.00363152 | 26363.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87791.532 | -999.000 | 5.876591 | 0.00251083 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0308 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 5.876591 | 5.74400081 | 4197.9300 | 999.8980 | 56.43087903 | 15.00 | 6.67 | 8.33 | 1973317.69 | 4.4489 | 4.448930 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 87791.53 | 87791.53 | 1.0000 | 5.74400081 | 5.876591 | 26.11 | 13.81 | 0.00709582 | 44326.3 | 11.10 | 8.15 | 0.00709582 | 29042.2 | 2.51057059 | 6.67 | 15.00 | 8.33 | 9964.667 | 77826.87 | 33.16 | 0.00547412 | 14.83 | 1.20015641 | 20.4227 | 24.00 | 0.00758131 | 24.00 | 0.00758131 | 33.1780 | 58036.09 | 0.00 | 74333.97 | 74333.97 | 5.74400081 | 26.11 | 15.92 | 0.00709582 | 44326.3 | 13.40 | 10.92 | 0.00709582 | 31385.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 251976.460 | 251976.460 | 5.876591 | 0.00551199 | 7805.514 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 5.876591 | 5.74400081 | 4197.9300 | 999.8980 | 51.30572931 | 48.89 | 60.00 | 11.11 | 2392848.03 | 10.5304 | 10.742328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 251976.46 | 251976.46 | 1.0000 | 5.74400081 | 5.876591 | -3.66 | -7.74 | 0.00095524 | -1290.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 5.51142978 | 60.00 | 48.89 | 11.11 | 0.000 | 251976.46 | -17.90 | 0.00095524 | -17.90 | 1.20015641 | 20.4227 | 0.00 | 0.00095524 | 24.08 | 0.00095524 | 4.2037 | 0.00 | 0.00 | 187103.08 | 187103.08 | 5.74400081 | 12.80 | 3.31 | 0.00095524 | 15273.7 | 45.16 | 17.30 | 0.00095524 | 47847.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 475103.239 | 248977.688 | 26.190875 | 0.01163525 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8937 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 403826.51 | 402860.46 | 0.8500 | -999.0 | -999.0 | 28.80 | 14.65 | 0.00702208 | 46873.1 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 403826.51 | 33.90 | 0.00547527 | 15.07 | 0.33839277 | -999.0000 | 27.00 | 0.00704235 | 27.00 | 0.00704235 | 25.8139 | 369591.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10475.103 | 5545.465 | 0.594265 | 0.00025653 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9333 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8856.18 | 8813.59 | 0.8455 | -999.0 | -999.0 | 28.20 | 14.47 | 0.00704337 | 46324.4 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8856.18 | 28.50 | 0.00546700 | 13.26 | 0.01563234 | -999.0000 | 27.00 | 0.00708596 | 27.00 | 0.00708596 | 25.9700 | 8394.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 100636.682 | 53267.201 | 5.707505 | 0.00246459 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9364 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 85088.05 | 84663.37 | 0.8455 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704503 | 46330.2 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85088.05 | 28.50 | 0.00546700 | 13.26 | 0.15632344 | -999.0000 | 27.00 | 0.00708946 | 27.00 | 0.00708946 | 25.9828 | 80622.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10268.139 | 5434.382 | 0.582147 | 0.00025147 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9346 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8682.28 | 8639.87 | 0.8456 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704408 | 46337.2 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8682.28 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | -999.0000 | 27.00 | 0.00708759 | 27.00 | 0.00708759 | 25.9760 | 8221.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 475103.239 | 475103.239 | 26.190875 | 0.01163525 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 475103.24 | 475103.24 | 1.0000 | 25.59994675 | 26.190875 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 475103.24 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2920 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10475.103 | 10475.103 | 0.594265 | 0.00025653 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10475.10 | 10475.10 | 1.0000 | 0.58085666 | 0.594265 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10475.10 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6305 | 0.00 | 0.00596249 | 26.13 | 0.00596249 | 23.0362 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 100636.682 | 100636.682 | 5.707505 | 0.00246459 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100636.68 | 100636.68 | 1.0000 | 5.57872986 | 5.707505 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100636.68 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7389 | 0.00 | 0.00166086 | 23.97 | 0.00166086 | 7.3494 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10268.139 | 10268.139 | 0.582147 | 0.00025147 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10268.14 | 10268.14 | 1.0000 | 0.56901211 | 0.582147 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10268.14 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6853 | 0.00 | 0.00162697 | 22.67 | 0.00162697 | 7.7871 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 26.190875 | 25.59994675 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 19243.92 | 19243.92 | 1.0000 | 25.59994675 | 26.190875 | -0.23 | -0.23 | 0.00692190 | 17075.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19243.92 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2920 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.594265 | 0.58085666 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.58085666 | 0.594265 | -0.47 | -0.47 | 0.00583077 | 14104.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6305 | 0.00 | 0.00596249 | 26.13 | 0.00596249 | 23.0362 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.707505 | 5.57872986 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8889.90 | 8889.90 | 1.0000 | 5.57872986 | 5.707505 | -0.49 | -4.69 | 0.00164154 | 3611.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8889.90 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7389 | 0.00 | 0.00166086 | 23.97 | 0.00166086 | 7.3494 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.582147 | 0.56901211 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.56901211 | 0.582147 | -0.48 | -4.73 | 0.00160893 | 3539.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6853 | 0.00 | 0.00162697 | 22.67 | 0.00162697 | 7.7871 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.82 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 100.93 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.47 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.88 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 26.19 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1722.67 | 1862.83 | 153.83 |
CORE_BOTTOM | 1617.83 | 1730.50 | 161.67 |
CORE_MID | 1009.00 | 3512.83 | 215.00 |
CORE_TOP | 1728.67 | 3971.17 | 910.50 |
PERIMETER_BOT_ZN_3 | 1742.50 | 3670.33 | 471.83 |
PERIMETER_BOT_ZN_2 | 2299.17 | 3050.33 | 573.67 |
PERIMETER_BOT_ZN_1 | 2825.00 | 2541.67 | 633.00 |
PERIMETER_BOT_ZN_4 | 2791.17 | 2022.00 | 446.83 |
PERIMETER_MID_ZN_3 | 2641.33 | 4098.67 | 1647.83 |
PERIMETER_MID_ZN_2 | 2435.83 | 3004.50 | 1170.33 |
PERIMETER_MID_ZN_1 | 3006.33 | 2874.83 | 1036.83 |
PERIMETER_MID_ZN_4 | 2780.00 | 3396.67 | 1166.33 |
PERIMETER_TOP_ZN_3 | 3292.00 | 4227.17 | 2316.67 |
PERIMETER_TOP_ZN_2 | 3241.17 | 3623.17 | 1755.17 |
PERIMETER_TOP_ZN_1 | 3255.83 | 3124.67 | 1417.83 |
PERIMETER_TOP_ZN_4 | 3231.00 | 3612.83 | 1723.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 326.17 | 326.17 |
DATACENTER_MID_ZN_6 | 5669.83 | 72.50 | 62.83 |
DATACENTER_TOP_ZN_6 | 5010.00 | 317.33 | 120.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5808.00 | 5808.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5941.83 | 5877.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 45.00 | 0.00 | 1.83 |
CORE_BOTTOM | 0.00 | 3.67 | 0.00 | 1.17 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.17 |
CORE_TOP | 8.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_3 | 0.83 | 19.67 | 0.00 | 17.00 |
PERIMETER_BOT_ZN_2 | 1.00 | 58.67 | 0.00 | 56.83 |
PERIMETER_BOT_ZN_1 | 1.83 | 183.17 | 0.00 | 179.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 145.50 | 0.00 | 79.33 |
PERIMETER_MID_ZN_3 | 45.50 | 9.67 | 10.33 | 8.17 |
PERIMETER_MID_ZN_2 | 56.33 | 54.67 | 2.67 | 51.33 |
PERIMETER_MID_ZN_1 | 21.17 | 272.83 | 1.83 | 269.50 |
PERIMETER_MID_ZN_4 | 20.00 | 55.50 | 1.83 | 37.17 |
PERIMETER_TOP_ZN_3 | 193.50 | 22.17 | 60.17 | 17.67 |
PERIMETER_TOP_ZN_2 | 117.83 | 54.67 | 15.83 | 49.17 |
PERIMETER_TOP_ZN_1 | 97.67 | 132.67 | 15.17 | 127.00 |
PERIMETER_TOP_ZN_4 | 80.83 | 57.83 | 11.83 | 37.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 46.67 | 0.00 | 42.67 |
DATACENTER_MID_ZN_6 | 0.00 | 34.17 | 0.00 | 31.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 30.33 | 0.00 | 26.83 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 248.17 | 0.00 | 236.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 240.83 | 805.67 | 62.67 | 666.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.286 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.908 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.668 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.655 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.871 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.487 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.611 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.973 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.721 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.342 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.526 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.246 | 0.105 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.761 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.453 | 0.130 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.617 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.316 | 0.130 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 30.253 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 53328085.92 | 0.00 | 53328085.92 | 0.00 | 53328085.92 | 37848132.68 | 3959.01 | 1099.61 | 3701.37 | 318.97 |
CORE_BOTTOM | 39081853.09 | 0.00 | 39081853.09 | 0.00 | 39081853.09 | 33990283.35 | 4471.98 | 129.20 | 4158.82 | 487.36 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 5497.84 | 688.97 | 2573.19 | 282.45 |
CORE_TOP | 27104096.86 | 0.00 | 27104096.86 | 0.00 | 27104096.86 | 33990283.35 | 5665.01 | 725.70 | 2369.29 | 382.94 |
PERIMETER_BOT_ZN_3 | 4706332.59 | 0.00 | 4706332.59 | 451114.65 | 5157447.24 | 4267819.30 | 5373.29 | 163.53 | 3223.18 | 487.36 |
PERIMETER_BOT_ZN_2 | 5038696.38 | 0.00 | 5038696.38 | 300742.89 | 5339439.27 | 2750345.05 | 4985.79 | 134.13 | 3640.07 | 487.36 |
PERIMETER_BOT_ZN_1 | 8444508.67 | 0.00 | 8444508.67 | 451114.65 | 8895623.32 | 4267912.63 | 4570.07 | 150.91 | 4039.02 | 487.36 |
PERIMETER_BOT_ZN_4 | 6746650.04 | 0.00 | 6746650.04 | 300742.89 | 7047392.93 | 2750345.05 | 4169.21 | 153.20 | 4437.59 | 487.36 |
PERIMETER_MID_ZN_3 | 37649613.98 | 0.00 | 37649613.98 | 1057988.21 | 38707602.19 | 42678193.03 | 5176.34 | 649.05 | 2934.61 | 282.45 |
PERIMETER_MID_ZN_2 | 45134150.48 | 0.00 | 45134150.48 | 705324.99 | 45839475.47 | 27503450.52 | 4886.29 | 539.12 | 3334.59 | 924.68 |
PERIMETER_MID_ZN_1 | 78229805.30 | 0.00 | 78229805.30 | 1057988.21 | 79287793.51 | 42679126.28 | 4248.17 | 405.22 | 4106.61 | 282.45 |
PERIMETER_MID_ZN_4 | 41684831.38 | 0.00 | 41684831.38 | 705324.99 | 42390156.37 | 27503450.52 | 4750.86 | 515.38 | 3493.76 | 282.45 |
PERIMETER_TOP_ZN_3 | 3958623.68 | 0.00 | 3958623.68 | 1313602.61 | 5272226.29 | 4267819.30 | 4735.37 | 463.59 | 3561.04 | 382.94 |
PERIMETER_TOP_ZN_2 | 4803824.31 | 0.00 | 4803824.31 | 875734.47 | 5679558.78 | 2750345.05 | 4544.35 | 379.64 | 3836.01 | 382.94 |
PERIMETER_TOP_ZN_1 | 8275879.49 | 0.00 | 8275879.49 | 1313602.61 | 9589482.10 | 4267912.63 | 4263.39 | 750.83 | 3745.78 | 382.94 |
PERIMETER_TOP_ZN_4 | 4401257.91 | 0.00 | 4401257.91 | 875734.47 | 5276992.39 | 2750345.05 | 4536.15 | 504.99 | 3718.86 | 382.94 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.48E+09 | 0.00 | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 91.45 | 373.86 | 8294.69 | 2800.13 |
Total Facility | 0.55E+10 | 0.00 | 0.55E+10 | 41148653.23 | 0.55E+10 | 0.50E+10 | 7309.03 | 4365.81 | 8673.97 | 3443.59 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3896 | 0.0000 | 2.3896 | 0.0000 | 2.3896 | 1.2002 | 1320.84 | 1097.22 | 3524.94 |
CORE_BOTTOM | 1.7027 | 0.0000 | 1.7027 | 0.0000 | 1.7027 | 1.0778 | 2055.60 | 127.89 | 3759.50 |
CORE_MID | 12.5418 | 0.0000 | 12.5418 | 0.0000 | 12.5418 | 10.7782 | 2801.34 | 688.07 | 2453.59 |
CORE_TOP | 1.2310 | 0.0000 | 1.2310 | 0.0000 | 1.2310 | 1.0778 | 2946.89 | 725.67 | 2270.44 |
PERIMETER_BOT_ZN_3 | 0.2054 | 0.0000 | 0.2054 | 0.0102 | 0.2156 | 0.1353 | 2948.35 | 162.18 | 2832.47 |
PERIMETER_BOT_ZN_2 | 0.2261 | 0.0000 | 0.2261 | 0.0068 | 0.2329 | 0.0872 | 2561.46 | 132.74 | 3248.81 |
PERIMETER_BOT_ZN_1 | 0.3801 | 0.0000 | 0.3801 | 0.0102 | 0.3903 | 0.1353 | 2145.85 | 149.45 | 3647.70 |
PERIMETER_BOT_ZN_4 | 0.2999 | 0.0000 | 0.2999 | 0.0068 | 0.3066 | 0.0872 | 1749.51 | 151.63 | 4041.86 |
PERIMETER_MID_ZN_3 | 1.7030 | 0.0000 | 1.7030 | 0.0239 | 1.7269 | 1.3533 | 2486.00 | 647.79 | 2809.22 |
PERIMETER_MID_ZN_2 | 2.0418 | 0.0000 | 2.0418 | 0.0171 | 2.0588 | 0.8721 | 1820.24 | 536.47 | 2677.29 |
PERIMETER_MID_ZN_1 | 3.5997 | 0.0000 | 3.5997 | 0.0239 | 3.6236 | 1.3533 | 1555.56 | 404.50 | 3982.95 |
PERIMETER_MID_ZN_4 | 1.8963 | 0.0000 | 1.8963 | 0.0159 | 1.9122 | 0.8721 | 2058.31 | 514.76 | 3369.93 |
PERIMETER_TOP_ZN_3 | 0.1800 | 0.0000 | 0.1800 | 0.0297 | 0.2097 | 0.1353 | 2020.49 | 463.10 | 3459.41 |
PERIMETER_TOP_ZN_2 | 0.2212 | 0.0000 | 0.2212 | 0.0198 | 0.2410 | 0.0872 | 1831.68 | 379.62 | 3731.71 |
PERIMETER_TOP_ZN_1 | 0.3819 | 0.0000 | 0.3819 | 0.0297 | 0.4115 | 0.1353 | 1547.75 | 750.63 | 3644.63 |
PERIMETER_TOP_ZN_4 | 0.2004 | 0.0000 | 0.2004 | 0.0198 | 0.2201 | 0.0872 | 1821.35 | 504.80 | 3616.85 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 15.6508 | 0.0000 | 15.6508 | 0.0000 | 15.6508 | 0.3384 | 74.58 | 373.86 | 5494.56 |
Total Facility | 242.0593 | 0.0000 | 242.0593 | 0.9407 | 243.0000 | 158.4706 | 4492.03 | 4359.00 | 5872.61 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 61161853.17 | 0.00 | 61161853.17 | 48026705.38 | 3781.48 | 146.92 | 4831.60 | 487.36 |
VAV_MID WITH REHEAT | 0.46E+09 | 0.00 | 0.46E+09 | 0.48E+09 | 4951.06 | 81.53 | 3727.41 | 282.45 |
VAV_TOP WITH REHEAT | 46377876.55 | 0.00 | 46377876.55 | 48026705.38 | 5055.81 | 131.69 | 3572.49 | 382.77 |
CAV_BAS | 50948815.29 | 0.00 | 50948815.29 | 37848132.68 | 5077.49 | 16.85 | 3665.66 | 318.91 |
AIRLOOP DATACENTER BASEMENT | 0.46E+09 | 0.00 | 0.46E+09 | 10671554.30 | 465.31 | 0.00 | 8294.69 | 2800.13 |
AIRLOOP DATACENTER BOT | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2333965.77 | 0.00 | 2333965.77 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.6886 | 0.0000 | 2.6886 | 1.5229 | 1361.83 | 146.01 | 4435.16 |
VAV_MID WITH REHEAT | 20.8396 | 0.0000 | 20.8396 | 15.2292 | 2253.59 | 81.24 | 3608.17 |
VAV_TOP WITH REHEAT | 2.1156 | 0.0000 | 2.1156 | 1.5229 | 2337.36 | 131.12 | 3474.52 |
CAV_BAS | 2.2830 | 0.0000 | 2.2830 | 1.2002 | 2432.30 | 13.68 | 3497.02 |
AIRLOOP DATACENTER BASEMENT | 14.9525 | 0.0000 | 14.9525 | 0.3384 | 448.44 | 0.00 | 5494.56 |
AIRLOOP DATACENTER BOT | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1091 | 0.0000 | 0.1091 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 1003.48 | 3012.30 | 0.00 | 0.00 | 0.00 | 1439.51 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 800.96 | 2780.88 | 0.00 | 0.00 | 0.00 | 1587.22 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 340.55 | 2664.90 | 0.00 | 0.00 | 0.00 | 2293.81 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1091.41 | 3892.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 373.86 | 8294.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 1.9345 | 4.6281 | 0.0000 | 0.0000 | 0.0000 | 1.6338 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 19.2470 | 33.3607 | 0.0000 | 0.0000 | 0.0000 | 15.7969 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 1.9170 | 3.6476 | 0.0000 | 0.0000 | 0.0000 | 1.5674 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1470 | 3.4471 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3240 | 16.1525 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1494 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1187 |
Fields with Defaults | 3885 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25579.91 | 304426.58 | 21-MAY-02:00 | 1854599.31 | 02-AUG-15:40 |
Electricity:Building | 16391.48 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16391.48 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-16:30 |
InteriorLights:Electricity | 1715.08 | 8110.17 | 01-JAN-08:50 | 169722.15 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1715.08 | 8110.17 | 01-JAN-08:50 | 169722.15 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 1715.08 | 8110.17 | 01-JAN-08:50 | 169722.15 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1715.08 | 8110.17 | 01-JAN-08:50 | 169722.15 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.91 | 589.50 | 26-MAR-17:10 | 3307.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.54 | 30.32 | 01-JAN-08:50 | 1147.25 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.54 | 30.32 | 01-JAN-08:50 | 1147.25 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.29 | 379.89 | 26-MAR-17:10 | 2131.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.85 | 19.54 | 01-JAN-07:40 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.85 | 19.54 | 01-JAN-07:40 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.82 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.45 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.45 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.24 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.80 | 19.54 | 01-JAN-08:50 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.80 | 19.54 | 01-JAN-08:50 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 438.99 | 5894.96 | 26-MAR-17:10 | 33078.05 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.34 | 303.25 | 01-JAN-08:50 | 11472.53 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.34 | 303.25 | 01-JAN-08:50 | 11472.53 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.83 | 3798.93 | 26-MAR-17:10 | 21316.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.48 | 195.42 | 01-JAN-07:40 | 7393.34 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.48 | 195.42 | 01-JAN-07:40 | 7393.34 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 438.14 | 5895.05 | 12-MAR-17:10 | 33078.63 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.48 | 303.26 | 01-JAN-07:50 | 11472.78 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 74.48 | 303.26 | 01-JAN-07:50 | 11472.78 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.31 | 3798.91 | 12-MAR-17:10 | 21316.66 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.96 | 195.42 | 01-JAN-08:40 | 7393.34 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.96 | 195.42 | 01-JAN-08:40 | 7393.34 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.90 | 589.50 | 26-MAR-17:10 | 3307.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.53 | 30.32 | 01-JAN-08:50 | 1147.25 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.53 | 30.32 | 01-JAN-08:50 | 1147.25 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.28 | 379.89 | 26-MAR-17:10 | 2131.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.85 | 19.54 | 01-JAN-07:40 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.85 | 19.54 | 01-JAN-07:40 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.81 | 589.50 | 12-MAR-17:10 | 3307.86 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.45 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.45 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.23 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.80 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.80 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1606.90 | 3833.34 | 05-JAN-05:20 | 327207.95 | 26-JUN-15:00 |
HeatRejection:Electricity | 519.76 | 103.88 | 05-JAN-07:20 | 71900.76 | 15-JUN-13:40 |
General:HeatRejection:Electricity | 519.76 | 103.88 | 05-JAN-07:20 | 71900.76 | 15-JUN-13:40 |
ElectricityProduced:Facility | 519.60 | -0.00 | 18-JAN-07:30 | 89487.60 | 26-APR-12:30 |
ElectricityProduced:Plant | 519.60 | -0.00 | 18-JAN-07:30 | 89487.60 | 26-APR-12:30 |
Photovoltaic:ElectricityProduced | 542.75 | 0.00 | 01-JAN-00:10 | 93216.16 | 26-APR-12:30 |
PowerConversion:ElectricityProduced | -23.15 | -3728.56 | 26-APR-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 6167.07 | 56595.71 | 21-MAY-02:30 | 599744.77 | 02-AUG-16:00 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73696.92 | 21-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3372.05 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
ElectricityPurchased:Plant | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
Cogeneration:ElectricityPurchased | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
ElectricityNet:Plant | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
Cogeneration:ElectricityNet | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
General:Cogeneration:ElectricityNet | 25060.31 | 273073.40 | 29-MAY-14:50 | 1808820.51 | 02-AUG-15:40 |
Fans:Electricity | 2681.93 | 50724.84 | 03-JAN-00:50 | 325428.97 | 20-JUN-12:00 |
General:Fans:Electricity | 2681.93 | 50724.84 | 03-JAN-00:50 | 325428.97 | 20-JUN-12:00 |
ExteriorLights:Electricity | 265.13 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 265.13 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 1777.61 | 1864.13 | 05-JAN-07:10 | 394287.21 | 16-AUG-15:10 |
General:Cooling:Electricity | 1777.61 | 1864.13 | 05-JAN-07:10 | 394287.21 | 16-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2373.69 | 0.00 | 13-APR-19:00 | 100000.00 | 01-JAN-10:10 |
General:Humidifier:Electricity | 2373.69 | 0.00 | 13-APR-19:00 | 100000.00 | 01-JAN-10:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 366.63 | 3688.84 | 13-FEB-04:30 | 44031.50 | 26-JUN-12:40 |
General:Pumps:Electricity | 366.63 | 3688.84 | 13-FEB-04:30 | 44031.50 | 26-JUN-12:40 |
WIRED_LTG_ELECTRICITY | 48.19 | 0.00 | 01-JAN-00:10 | 4769.19 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2476.81 | 7280.88 | 22-JAN-12:10 | 1555332.63 | 23-DEC-07:10 |
NaturalGas:Plant | 2476.81 | 7280.88 | 22-JAN-12:10 | 1555332.63 | 23-DEC-07:10 |
Heating:NaturalGas | 1690.42 | 0.00 | 01-JAN-00:40 | 1525895.19 | 23-DEC-07:10 |
Boiler:Heating:NaturalGas | 1690.42 | 0.00 | 01-JAN-00:40 | 1525895.19 | 23-DEC-07:10 |
WaterSystems:NaturalGas | 786.40 | 7280.88 | 02-JAN-05:10 | 85112.84 | 08-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 786.40 | 7280.88 | 02-JAN-05:10 | 85112.84 | 08-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10072.84 | 5778.80 | 05-JAN-07:10 | 2271690.23 | 16-AUG-15:10 |
PlantLoopCoolingDemand:HVAC | 10072.84 | 5778.80 | 05-JAN-07:10 | 2271690.23 | 16-AUG-15:10 |
CoolingCoils:PlantLoopCoolingDemand | 10072.84 | 5778.80 | 05-JAN-07:10 | 2271690.23 | 16-AUG-15:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8088.98 | 0.00 | 20-MAY-24:00 | 0.00 | 26-JUN-15:10 |
Water:HVAC | 883.01 | 0.00 | 13-APR-19:00 | 0.00 | 03-FEB-04:10 |
Humidifier:Water | 883.01 | 0.00 | 13-APR-19:00 | 0.00 | 03-FEB-04:10 |
General:Humidifier:Water | 883.01 | 0.00 | 13-APR-19:00 | 0.00 | 03-FEB-04:10 |
MainsWater:Facility | 8088.98 | 0.00 | 20-MAY-24:00 | 0.00 | 26-JUN-15:10 |
MainsWater:HVAC | 883.01 | 0.00 | 13-APR-19:00 | 0.00 | 03-FEB-04:10 |
Humidifier:MainsWater | 883.01 | 0.00 | 13-APR-19:00 | 0.00 | 03-FEB-04:10 |
General:Humidifier:MainsWater | 883.01 | 0.00 | 13-APR-19:00 | 0.00 | 03-FEB-04:10 |
Water:Plant | 7205.97 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 7205.97 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4925.80 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
General:HeatRejection:Water | 4925.80 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
HeatRejection:MainsWater | 4925.80 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
General:HeatRejection:MainsWater | 4925.80 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 47493.61 | 98624.69 | 06-JAN-03:40 | 8722212.57 | 16-AUG-15:10 |
EnergyTransfer:Building | 18083.75 | 88080.51 | 07-JAN-21:50 | 1595505.92 | 31-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 595.27 | 0.00 | 01-JAN-00:10 | 69986.36 | 05-SEP-05:10 |
Heating:EnergyTransfer | 505.14 | 0.00 | 09-JAN-22:10 | 783923.01 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.36 | 0.00 | 01-JAN-00:10 | 19277.95 | 15-JUL-16:10 |
General:Heating:EnergyTransfer | 505.14 | 0.00 | 09-JAN-22:10 | 783923.01 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.36 | 0.00 | 01-JAN-00:10 | 19277.95 | 15-JUL-16:10 |
Cooling:EnergyTransfer | 17578.61 | 86818.16 | 08-JAN-05:40 | 1595505.92 | 31-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 592.90 | 0.00 | 01-JAN-00:10 | 69986.36 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 17578.61 | 86818.16 | 08-JAN-05:40 | 1595505.92 | 31-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 592.90 | 0.00 | 01-JAN-00:10 | 69986.36 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 544.14 | 0.00 | 01-JAN-00:10 | 51292.49 | 21-AUG-09:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 544.14 | 0.00 | 01-JAN-00:10 | 51292.49 | 21-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 544.14 | 0.00 | 01-JAN-00:10 | 51292.49 | 21-AUG-09:00 |
EnergyTransfer:Zone:CORE_MID | 3722.12 | 0.00 | 01-JAN-00:10 | 400981.29 | 19-JUL-09:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.18 | 0.00 | 01-JAN-00:10 | 226358.23 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.18 | 0.00 | 01-JAN-00:10 | 226358.23 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3720.95 | 0.00 | 01-JAN-00:10 | 400981.29 | 19-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3720.95 | 0.00 | 01-JAN-00:10 | 400981.29 | 19-JUL-09:40 |
EnergyTransfer:Zone:CORE_TOP | 338.32 | 0.00 | 01-JAN-00:40 | 64724.69 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 12.72 | 0.00 | 01-JAN-00:10 | 64724.69 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 12.72 | 0.00 | 01-JAN-00:10 | 64724.69 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 325.61 | 0.00 | 01-JAN-00:40 | 53371.19 | 26-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 325.61 | 0.00 | 01-JAN-00:40 | 53371.19 | 26-JUN-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.40 | 0.00 | 01-JAN-00:10 | 11730.56 | 26-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.69 | 0.00 | 01-JAN-00:10 | 7691.50 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.69 | 0.00 | 01-JAN-00:10 | 7691.50 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.72 | 0.00 | 01-JAN-00:10 | 11730.56 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.72 | 0.00 | 01-JAN-00:10 | 11730.56 | 26-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.88 | 0.00 | 01-JAN-00:10 | 16400.75 | 07-AUG-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.64 | 0.00 | 01-JAN-00:10 | 6158.02 | 21-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.64 | 0.00 | 01-JAN-00:10 | 6158.02 | 21-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.24 | 0.00 | 01-JAN-00:10 | 16400.75 | 07-AUG-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.24 | 0.00 | 01-JAN-00:10 | 16400.75 | 07-AUG-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 126.79 | 0.00 | 01-JAN-00:10 | 21156.07 | 07-NOV-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.09 | 0.00 | 01-JAN-00:10 | 9995.44 | 21-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.09 | 0.00 | 01-JAN-00:10 | 9995.44 | 21-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 125.70 | 0.00 | 01-JAN-00:10 | 21156.07 | 07-NOV-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 125.70 | 0.00 | 01-JAN-00:10 | 21156.07 | 07-NOV-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.56 | 0.00 | 01-JAN-00:10 | 21482.85 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1937.13 | 05-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1937.13 | 05-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.54 | 0.00 | 01-JAN-00:10 | 21482.85 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.54 | 0.00 | 01-JAN-00:10 | 21482.85 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 554.77 | 0.00 | 01-JAN-00:10 | 119442.20 | 23-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 104.93 | 0.00 | 01-JAN-00:10 | 119442.20 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 104.93 | 0.00 | 01-JAN-00:10 | 119442.20 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 449.84 | 0.00 | 01-JAN-00:10 | 109376.92 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 449.84 | 0.00 | 01-JAN-00:10 | 109376.92 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 636.63 | 0.00 | 01-JAN-00:10 | 170404.44 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 53.51 | 0.00 | 01-JAN-00:10 | 124075.36 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 53.51 | 0.00 | 01-JAN-00:10 | 124075.36 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 583.12 | 0.00 | 01-JAN-00:10 | 170404.44 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 583.12 | 0.00 | 01-JAN-00:10 | 170404.44 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1226.47 | 0.00 | 01-JAN-00:10 | 245995.48 | 05-NOV-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.63 | 0.00 | 01-JAN-00:10 | 164031.05 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.63 | 0.00 | 01-JAN-00:10 | 164031.05 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1171.84 | 0.00 | 01-JAN-00:10 | 245995.48 | 05-NOV-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1171.84 | 0.00 | 01-JAN-00:10 | 245995.48 | 05-NOV-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 635.05 | 0.00 | 01-JAN-00:10 | 186924.11 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.33 | 0.00 | 01-JAN-00:10 | 113673.08 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.33 | 0.00 | 01-JAN-00:10 | 113673.08 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 595.72 | 0.00 | 01-JAN-00:10 | 186924.11 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 595.72 | 0.00 | 01-JAN-00:10 | 186924.11 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 71.75 | 0.00 | 01-JAN-00:40 | 14774.00 | 23-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.31 | 0.00 | 01-JAN-00:40 | 14774.00 | 23-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.31 | 0.00 | 01-JAN-00:40 | 14774.00 | 23-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.44 | 0.00 | 01-JAN-00:10 | 12643.24 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.44 | 0.00 | 01-JAN-00:10 | 12643.24 | 26-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.62 | 0.00 | 01-JAN-00:40 | 17206.94 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.39 | 0.00 | 01-JAN-00:40 | 16405.33 | 23-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.39 | 0.00 | 01-JAN-00:40 | 16405.33 | 23-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.23 | 0.00 | 01-JAN-00:10 | 17206.94 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.23 | 0.00 | 01-JAN-00:10 | 17206.94 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 126.43 | 0.00 | 01-JAN-00:40 | 23810.43 | 05-NOV-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.62 | 0.00 | 01-JAN-00:10 | 19917.91 | 23-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.62 | 0.00 | 01-JAN-00:10 | 19917.91 | 23-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 108.81 | 0.00 | 01-JAN-00:40 | 23810.43 | 05-NOV-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 108.81 | 0.00 | 01-JAN-00:40 | 23810.43 | 05-NOV-13:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 68.93 | 0.00 | 01-JAN-00:40 | 19526.89 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 11.68 | 0.00 | 01-JAN-00:20 | 15492.69 | 23-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 11.68 | 0.00 | 01-JAN-00:20 | 15492.69 | 23-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.25 | 0.00 | 01-JAN-00:10 | 19526.89 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.25 | 0.00 | 01-JAN-00:10 | 19526.89 | 16-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.75 | 0.00 | 01-JAN-00:10 | 9440.69 | 17-JUL-09:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.31 | 0.00 | 01-JAN-00:10 | 4578.36 | 25-DEC-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.31 | 0.00 | 01-JAN-00:10 | 4578.36 | 25-DEC-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.43 | 0.00 | 01-JAN-00:10 | 9440.69 | 17-JUL-09:50 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.43 | 0.00 | 01-JAN-00:10 | 9440.69 | 17-JUL-09:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 402.99 | 0.00 | 01-JAN-00:10 | 78609.68 | 17-JUL-10:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 116.84 | 0.00 | 01-JAN-00:10 | 65920.59 | 13-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 116.84 | 0.00 | 01-JAN-00:10 | 65920.59 | 13-FEB-11:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 286.16 | 0.00 | 01-JAN-00:10 | 78609.68 | 17-JUL-10:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 286.16 | 0.00 | 01-JAN-00:10 | 78609.68 | 17-JUL-10:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.64 | 0.00 | 01-JAN-00:40 | 25606.63 | 22-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.22 | 0.00 | 01-JAN-00:40 | 25606.63 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.22 | 0.00 | 01-JAN-00:40 | 25606.63 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 57.43 | 0.00 | 01-JAN-00:10 | 22024.47 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 57.43 | 0.00 | 01-JAN-00:10 | 22024.47 | 26-JUN-15:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.50 | 456.35 | 06-JAN-06:20 | 8487.04 | 05-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.50 | 456.35 | 06-JAN-06:20 | 8487.04 | 05-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.50 | 456.35 | 06-JAN-06:20 | 8487.04 | 05-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1189.08 | 10.38 | 15-JAN-01:50 | 81121.76 | 05-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.86 | 0.00 | 01-JAN-13:50 | 4454.82 | 06-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.86 | 0.00 | 01-JAN-13:50 | 4454.82 | 06-JAN-05:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1188.22 | 0.00 | 01-JAN-00:10 | 81121.76 | 05-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1188.22 | 0.00 | 01-JAN-00:10 | 81121.76 | 05-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.86 | 2.31 | 05-JAN-12:20 | 8228.47 | 05-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.82 | 0.00 | 02-JAN-14:00 | 699.70 | 01-JAN-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.82 | 0.00 | 02-JAN-14:00 | 699.70 | 01-JAN-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.03 | 0.00 | 01-JAN-00:10 | 8228.47 | 05-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.03 | 0.00 | 01-JAN-00:10 | 8228.47 | 05-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7147.79 | 86169.75 | 08-JAN-06:00 | 377456.64 | 16-AUG-21:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7147.79 | 86169.75 | 08-JAN-06:00 | 377456.64 | 16-AUG-21:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7147.79 | 86169.75 | 08-JAN-06:00 | 377456.64 | 16-AUG-21:30 |
PlantLoopHeatingDemand:Facility | 1993.80 | 0.00 | 01-JAN-00:40 | 1341226.39 | 23-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 435.47 | 0.00 | 01-JAN-00:10 | 53786.94 | 13-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53786.94 | 13-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53786.94 | 13-FEB-12:40 |
EnergyTransfer:HVAC | 10574.08 | 6771.10 | 05-JAN-04:40 | 2084555.23 | 16-AUG-15:10 |
HeatingCoils:EnergyTransfer | 1558.33 | 0.00 | 01-JAN-00:40 | 1331322.72 | 23-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 1558.33 | 0.00 | 01-JAN-00:40 | 1331322.72 | 23-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1558.33 | 0.00 | 01-JAN-00:40 | 1331322.72 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 9015.75 | 3914.66 | 05-JAN-07:10 | 2084555.23 | 16-AUG-15:10 |
EnergyTransfer:Plant | 18835.78 | 0.00 | 01-JAN-00:40 | 5327209.76 | 26-JUN-15:10 |
LoopToLoop:EnergyTransfer | 5386.49 | 0.00 | 01-JAN-00:10 | 1693960.71 | 26-JUN-15:10 |
WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53786.94 | 13-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53786.94 | 13-FEB-12:40 |
Boilers:EnergyTransfer | 1555.90 | 0.00 | 01-JAN-00:40 | 1358158.32 | 23-DEC-07:10 |
Chillers:EnergyTransfer | 5368.70 | 0.00 | 01-JAN-00:10 | 1695503.25 | 26-JUN-15:00 |
HeatRejection:EnergyTransfer | 6089.22 | 0.00 | 01-JAN-00:10 | 1913243.46 | 26-JUN-15:00 |
General:HeatRejection:EnergyTransfer | 6089.22 | 0.00 | 01-JAN-00:10 | 1913243.46 | 26-JUN-15:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.363 | -592.902 | 0.000 | 0.000 | 92.827 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -42.724 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -544.138 | 0.000 | 0.000 | 83.428 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 66.884 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_MID | 0.000 | 0.000 | 1.175 | -3720.934 | 0.000 | 0.000 | 844.663 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1063.147 |
CORE_TOP | 0.000 | 0.000 | 12.717 | -325.604 | 0.000 | 0.000 | 87.600 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -168.537 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.685 | -63.716 | 0.000 | 0.000 | 10.794 | 7.544 | 36.365 | 34.810 | 0.000 | 0.121 | 52.579 | 0.000 | -72.630 | 0.000 | -6.553 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.644 | -67.237 | 0.000 | 0.000 | 6.892 | 4.853 | 23.435 | 80.983 | 0.000 | 0.080 | 0.511 | 0.000 | -45.785 | 0.000 | -4.377 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.093 | -125.700 | 0.000 | 0.000 | 10.627 | 7.453 | 36.366 | 168.466 | 0.000 | 0.119 | 0.002 | 0.000 | -68.239 | 0.000 | -6.657 | -23.527 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.014 | -97.545 | 0.000 | 0.000 | 6.787 | 4.800 | 23.435 | 73.001 | 0.000 | 0.077 | 45.964 | 0.000 | -51.715 | 0.000 | -4.818 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 104.926 | -449.839 | 0.000 | 0.000 | 113.031 | 75.337 | 363.654 | 360.964 | 0.000 | 2.825 | 228.682 | 0.000 | -661.570 | 0.000 | -138.010 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 53.511 | -583.120 | 0.000 | 0.000 | 51.632 | 48.481 | 234.352 | 808.121 | 0.000 | 1.770 | 0.095 | 0.000 | -432.986 | 0.000 | -96.007 | -85.754 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 54.626 | -1171.832 | 0.000 | 0.000 | 107.197 | 74.484 | 363.660 | 1677.766 | 0.000 | 2.715 | 0.027 | 0.000 | -662.876 | 0.000 | -149.080 | -296.661 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 39.330 | -595.712 | 0.000 | 0.000 | 71.009 | 47.961 | 234.351 | 742.265 | 0.000 | 1.784 | 14.113 | 0.000 | -456.604 | 0.000 | -98.497 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 29.313 | -42.440 | 0.000 | 0.000 | 11.457 | 7.533 | 36.365 | 36.561 | 0.000 | 0.335 | 0.001 | 0.000 | -62.572 | 0.000 | -16.276 | -0.278 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 15.392 | -57.229 | 0.000 | 0.000 | 7.118 | 4.848 | 23.435 | 81.309 | 0.000 | 0.217 | 0.001 | 0.000 | -40.997 | 0.000 | -11.326 | -22.767 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 17.620 | -108.804 | 0.000 | 0.000 | 10.880 | 7.448 | 36.366 | 168.349 | 0.000 | 0.326 | 0.001 | 0.000 | -62.869 | 0.000 | -17.595 | -51.721 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 11.683 | -57.250 | 0.000 | 0.000 | 7.196 | 4.796 | 23.435 | 74.431 | 0.000 | 0.215 | 0.000 | 0.000 | -43.494 | 0.000 | -11.676 | -9.336 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.501 | 0.000 | 0.000 | 0.949 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.004 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.859 | -1188.218 | 0.000 | 0.000 | 9.494 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -377.699 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.823 | -108.033 | 0.000 | 0.000 | 0.951 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.297 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7147.799 | 0.000 | 0.000 | 20.150 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -400.062 |
GROUNDFLOOR_PLENUM | 3.311 | -49.435 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.228 | 59.978 | 0.000 | 0.000 | 0.000 | -14.082 | 0.000 |
MIDFLOOR_PLENUM | 116.839 | -286.156 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.198 | 405.485 | 0.000 | 0.000 | 0.000 | -240.366 | -0.000 |
TOPFLOOR_PLENUM | 38.217 | -57.424 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.349 | 44.162 | 0.000 | 0.000 | 0.000 | -25.303 | -0.002 |
Total Facility | 158.367 | -393.015 | 346.773 | -17185.552 | 0.000 | 0.000 | 1554.683 | 1715.081 | 14676.396 | 4307.026 | 0.000 | 15.359 | 918.490 | 0.000 | -2662.337 | 0.000 | -840.623 | -2610.529 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-NOV-04:01 | 0.00 | 0.00 | 0.00 | -98403.51 | 0.00 | 0.00 | 0.00 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 84380.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-SEP-04:13 | 0.00 | 0.00 | 0.00 | -87718.51 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 81243.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-AUG-04:11 | 0.00 | 0.00 | 0.00 | -760453.14 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 695703.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:13 | 0.00 | 0.00 | 0.00 | -79851.88 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 73376.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-18:12 | 0.00 | 0.00 | 0.00 | -16355.84 | 0.00 | 0.00 | 0.00 | 30.32 | 559.17 | 6307.26 | 0.00 | 177.62 | 9281.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-07:41 | 0.00 | 0.00 | 0.00 | -24537.07 | 0.00 | 0.00 | 19.10 | 19.54 | 464.11 | 20831.63 | 0.00 | 0.00 | 3523.31 | 0.00 | -0.00 | 0.00 | -320.62 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-13:11 | 0.00 | 0.00 | 0.00 | -28379.02 | 0.00 | 0.00 | 25.63 | 30.33 | 720.19 | 29951.40 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -83.31 | -2265.22 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -33292.63 | 0.00 | 0.00 | 12.72 | 19.54 | 464.11 | 21921.60 | 0.00 | 0.00 | 11012.93 | 0.00 | -0.00 | 0.00 | -138.28 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:12 | 0.00 | 0.00 | 0.00 | -158632.00 | 0.00 | 0.00 | 0.00 | 303.25 | 5591.71 | 62968.51 | 0.00 | 3887.56 | 85880.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:51 | 0.00 | 0.00 | 0.00 | -283410.59 | 0.00 | 0.00 | 161.21 | 195.42 | 4641.14 | 200956.21 | 0.00 | 0.00 | 78424.78 | 0.00 | -0.00 | 0.00 | -968.17 | 0.00 |
PERIMETER_MID_ZN_1 | 05-NOV-13:21 | 0.00 | 0.00 | 0.00 | -301196.79 | 0.00 | 0.00 | 205.44 | 303.26 | 7201.95 | 340093.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1079.12 | -45528.60 |
PERIMETER_MID_ZN_4 | 25-JUN-16:11 | 0.00 | 0.00 | 0.00 | -311725.12 | 0.00 | 0.00 | 129.45 | 195.42 | 4641.11 | 213145.70 | 0.00 | 713.65 | 92899.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-14:43 | 0.00 | 0.00 | 0.00 | -18265.78 | 0.00 | 0.00 | 37.07 | 30.32 | 720.18 | 7647.49 | 0.00 | 557.38 | 9273.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-08:21 | 0.00 | 0.00 | 0.00 | -27719.69 | 0.00 | 0.00 | 17.32 | 19.54 | 464.11 | 22041.37 | 0.00 | 0.00 | 5361.26 | 0.00 | -0.00 | 0.00 | -183.91 | 0.00 |
PERIMETER_TOP_ZN_1 | 05-NOV-13:31 | 0.00 | 0.00 | 0.00 | -32048.78 | 0.00 | 0.00 | 22.59 | 30.33 | 720.19 | 32957.28 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -143.81 | -1537.80 |
PERIMETER_TOP_ZN_4 | 10-SEP-16:31 | 0.00 | 0.00 | 0.00 | -33097.49 | 0.00 | 0.00 | 12.70 | 19.54 | 464.11 | 20064.77 | 0.00 | 6.20 | 12530.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 05-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8486.94 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 684.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 05-AUG-18:40 | 0.00 | 0.00 | 0.00 | -81120.59 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 3095.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 13-AUG-19:00 | 0.00 | 0.00 | 0.00 | -8233.37 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 430.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 16-AUG-21:12 | 0.00 | 0.00 | 0.00 | -383052.58 | 0.00 | 0.00 | 103.51 | 318.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 2997.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-SEP-05:10 | 0.00 | -12231.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12396.93 | 0.00 | -0.00 | 0.00 | -165.67 | 0.00 |
MIDFLOOR_PLENUM | 20-DEC-04:01 | 0.00 | -141068.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183592.36 | 0.00 | -0.00 | 0.00 | -42523.49 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-14:50 | 0.00 | -25453.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.72 | 25124.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:02 | 0.00 | -68179.24 | 0.00 | -1799919.84 | 0.00 | 0.00 | 16231.42 | 10223.35 | 616289.16 | 0.00 | 0.00 | 0.00 | 1291400.56 | 0.00 | -63037.82 | 0.00 | -3007.58 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUL-16:01 | 0.00 | 0.00 | 20523.07 | 0.00 | 0.00 | 0.00 | 520.13 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35065.96 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-DEC-05:11 | 0.00 | 0.00 | 404494.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -469244.71 |
CORE_TOP | 06-FEB-04:01 | 0.00 | 0.00 | 71655.84 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78101.07 |
PERIMETER_BOT_ZN_3 | 23-DEC-05:01 | 0.00 | 0.00 | 12191.75 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8150.97 | 0.00 | -1264.29 | -3399.39 |
PERIMETER_BOT_ZN_2 | 21-DEC-05:11 | 0.00 | 0.00 | 11887.95 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6115.16 | 0.00 | -587.32 | -5709.42 |
PERIMETER_BOT_ZN_1 | 21-DEC-05:11 | 0.00 | 0.00 | 16714.12 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9076.44 | 0.00 | -875.09 | -7575.63 |
PERIMETER_BOT_ZN_4 | 05-JAN-06:01 | 0.00 | 0.00 | 8476.28 | 0.00 | 0.00 | 0.00 | 94.15 | 43.48 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5008.72 | 0.00 | -58.79 | -4165.21 |
PERIMETER_MID_ZN_3 | 24-DEC-06:41 | 0.00 | 0.00 | 134694.52 | 0.00 | 0.00 | 0.00 | 903.70 | 637.34 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70686.30 | 0.00 | -31607.26 | -41143.84 |
PERIMETER_MID_ZN_2 | 24-DEC-06:41 | 0.00 | 0.00 | 185799.09 | 0.00 | 0.00 | 0.00 | 583.90 | 410.73 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48549.82 | 0.00 | -21416.12 | -121468.93 |
PERIMETER_MID_ZN_1 | 24-DEC-06:41 | 0.00 | 0.00 | 201790.93 | 0.00 | 0.00 | 0.00 | 898.21 | 637.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74047.90 | 0.00 | -32071.28 | -104409.26 |
PERIMETER_MID_ZN_4 | 20-DEC-04:01 | 0.00 | 0.00 | 180815.24 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49308.04 | 0.00 | -16530.74 | -120191.83 |
PERIMETER_TOP_ZN_3 | 24-DEC-04:11 | 0.00 | 0.00 | 16683.37 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6809.85 | 0.00 | -3189.57 | -7306.86 |
PERIMETER_TOP_ZN_2 | 24-DEC-04:11 | 0.00 | 0.00 | 21605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4683.55 | 0.00 | -2174.06 | -15149.56 |
PERIMETER_TOP_ZN_1 | 24-DEC-04:11 | 0.00 | 0.00 | 23502.51 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7131.88 | 0.00 | -3258.91 | -13734.63 |
PERIMETER_TOP_ZN_4 | 24-DEC-04:11 | 0.00 | 0.00 | 23129.64 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4640.12 | 0.00 | -2225.55 | -16665.40 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 15-JAN-23:33 | 0.00 | 0.00 | 4584.13 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24151.48 |
DATACENTER_TOP_ZN_6 | 01-JAN-18:25 | 0.00 | 0.00 | 709.01 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2665.75 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 11-JUN-15:51 | 13532.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13617.79 |
MIDFLOOR_PLENUM | 26-MAR-16:01 | 160820.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7514.78 | -153306.02 |
TOPFLOOR_PLENUM | 22-DEC-05:22 | 29696.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2183.19 | -27513.01 |
Total Facility | 26-DEC-05:11 | -525414.37 | 503928.56 | 1221373.87 | -503928.56 | 0.00 | 0.00 | 0.00 | 10223.35 | 587299.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -108352.88 | 0.00 | -71305.77 | -1113823.62 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.7229 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.8200 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 122.4573 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 100.9290 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.7016 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.4657 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8766 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8766 | 0.2042 | 1.0000 | Not calculated | 1.2002 | 0.2042 | ||
AIRLOOP DATACENTER BASEMENT | 26.1906 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.1909 | 0.0129 | 1.0000 | Not calculated | 0.3384 | 0.0129 | ||
AIRLOOP DATACENTER BOT | 0.5943 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5943 | 0.0263 | 1.0000 | Not calculated | 0.0156 | 0.0263 | ||
AIRLOOP DATACENTER MID | 5.7075 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.7075 | 0.0274 | 1.0000 | Not calculated | 0.1563 | 0.0274 | ||
AIRLOOP DATACENTER TOP | 0.5821 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5821 | 0.0269 | 1.0000 | Not calculated | 0.0156 | 0.0269 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.3615 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2866 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 61.2286 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8370 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.3508 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2845 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8766 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8766 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2042 | ||
AIRLOOP DATACENTER BASEMENT | 26.1906 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.1906 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0129 | ||
AIRLOOP DATACENTER BOT | 0.5943 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5943 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0263 | ||
AIRLOOP DATACENTER MID | 5.7075 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.7075 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0274 | ||
AIRLOOP DATACENTER TOP | 0.5821 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5821 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0269 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8766 | 5.8766 | 5.8766 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4231 | 6.4231 | 1.6186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 60.2664 | 60.2664 | 16.1514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0525 | 6.0525 | 1.6160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1403 | 1.1403 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5435 | 1.5435 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6639 | 1.6639 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9520 | 1.9520 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.8445 | 10.8445 | 2.0279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.5774 | 16.5774 | 1.3096 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.5621 | 16.5621 | 2.0371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.2069 | 18.2069 | 1.3109 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2481 | 1.2481 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6632 | 1.6632 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8073 | 1.8073 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9306 | 1.9306 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5943 | 0.5943 | 0.5943 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7075 | 5.7075 | 5.7075 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5821 | 0.5821 | 0.5821 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.1906 | 26.1906 | 26.1906 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.7229 | 10.8200 | 12.7229 | 2.2866 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 122.4573 | 100.9290 | 122.4573 | 22.8370 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.7016 | 11.4657 | 12.7016 | 2.2845 | 0.0000 | 1.0000 |
CAV_BAS | 5.8766 | 5.8766 | 5.8766 | 5.8766 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.1906 | 26.1909 | 26.1906 | 26.1906 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5943 | 0.5943 | 0.5943 | 0.5943 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.7075 | 5.7075 | 5.7075 | 5.7075 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5821 | 0.5821 | 0.5821 | 0.5821 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.8766 | 5.8766 | 5.8766 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2116 | 3.2116 | 1.6186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 30.1332 | 30.1332 | 16.1514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0262 | 3.0262 | 1.6160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5702 | 0.5702 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7718 | 0.7718 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8319 | 0.8319 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9760 | 0.9760 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4222 | 5.4222 | 2.0279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.2887 | 8.2887 | 1.3096 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.2810 | 8.2810 | 2.0371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.1035 | 9.1035 | 1.3109 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6241 | 0.6241 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8316 | 0.8316 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9036 | 0.9036 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9653 | 0.9653 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5943 | 0.5943 | 0.5943 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7075 | 5.7075 | 5.7075 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5821 | 0.5821 | 0.5821 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.1906 | 26.1906 | 26.1906 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.3615 | 2.2866 | 2.2866 | 2.2866 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 61.2286 | 22.8370 | 22.8370 | 22.8370 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.3508 | 2.2845 | 2.2845 | 2.2845 | 0.0000 | 1.0000 |
CAV_BAS | 5.8766 | 5.8766 | 5.8766 | 5.8766 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.1906 | 26.1906 | 26.1906 | 26.1906 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5943 | 0.5943 | 0.5943 | 0.5943 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.7075 | 5.7075 | 5.7075 | 5.7075 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5821 | 0.5821 | 0.5821 | 0.5821 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 62.67 |
Number of hours cooling loads not met | 666.50 |
Number of hours not met | 728.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1690.42 | 1525895.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1777.61 | 394287.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1715.08 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 265.13 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2681.93 | 325428.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 366.63 | 44031.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 519.76 | 71900.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2373.69 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 786.40 | 85112.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 25579.91 |
Natural Gas | 0.00 | 2476.81 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 28056.73 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 542.75 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.03 |
Space Heating | 0.00 |
Space Cooling | 38.38 |
Fans (All) | 57.90 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 552.24 |
Subtotal | 552.24 |
Natural Gas [MJ/m2] | |
Space Heating | 36.49 |
Service Water Heating | 16.98 |
Miscellaneous (All) | 53.47 |
Subtotal | 53.47 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.11 |
Space Heating | 6.03 |
Space Cooling | 6.34 |
Fans (All) | 9.56 |
Service Water Heating | 2.80 |
Receptacle Equipment | 52.31 |
Miscellaneous | 16.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 618. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8681.67 | 78.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8705.33 | 54.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8568.17 | 191.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8709.83 | 50.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8704.00 | 56.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8702.33 | 57.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8707.17 | 52.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8711.83 | 48.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8701.33 | 58.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8215.17 | 534.50 | 10.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8682.50 | 77.50 | 0.00 | 0.00 | 0.00 |
Min | 8215.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 534.50 | 10.33 | 0.00 | 0.00 |
Average | 8698.42 | 61.13 | 0.45 | 0.00 | 0.00 |
Sum | 200063.67 | 1406.00 | 10.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368424.67 | 191.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2254.33 | 13.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2258.33 | 9.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2259.50 | 8.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 95817.67 | 7250.17 | 327.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368424.67 | 7250.17 | 327.17 | 0.00 | 0.00 |
Average | 79995.76 | 324.93 | 14.22 | 0.00 | 0.00 |
Sum | 1839902.50 | 7473.33 | 327.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8556.00 | 204.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8657.67 | 102.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8684.00 | 76.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8694.17 | 65.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8703.17 | 56.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8696.00 | 64.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8531.83 | 228.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8702.83 | 57.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8712.17 | 47.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8681.17 | 78.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8722.67 | 37.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8706.83 | 53.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8714.33 | 45.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8690.83 | 69.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8363.33 | 396.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8673.50 | 86.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8722.67 | 37.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
Min | 8363.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 396.67 | 0.00 | 0.00 | 0.00 |
Average | 8679.23 | 80.77 | 0.00 | 0.00 | 0.00 |
Sum | 199622.33 | 1857.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368105.17 | 510.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330655.00 | 158.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330728.00 | 85.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330720.00 | 93.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 98061.67 | 5333.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368105.17 | 5333.33 | 0.00 | 0.00 | 0.00 |
Average | 80066.21 | 268.70 | 0.00 | 0.00 | 0.00 |
Sum | 1841522.83 | 6180.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438860E+11 | 97490.82 | 01-JAN-14:00 | 6.00 | 1.45 | 0.563614E+10 | 7499.27 | 10-JAN-10:20 | 2.33 | 2.33 |
February | 0.381270E+11 | 96822.54 | 21-FEB-04:01 | -1.0 | -1.0 | 0.512736E+10 | 7499.17 | 06-FEB-14:20 | -1.0 | -1.0 |
March | 0.470389E+11 | 94109.82 | 13-MAR-04:12 | 6.67 | 1.13 | 0.612538E+10 | 7499.17 | 20-MAR-09:20 | 2.67 | 2.67 |
April | 0.449528E+11 | 96153.75 | 10-APR-04:11 | 2.67 | -3.2 | 0.544422E+10 | 7499.26 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.479227E+11 | 95635.60 | 01-MAY-04:11 | 6.00 | 2.17 | 0.589860E+10 | 7499.24 | 26-MAY-13:20 | 12.67 | 7.73 |
June | 0.525266E+11 | 95799.35 | 05-JUN-04:12 | 12.37 | 8.77 | 0.588546E+10 | 7715.16 | 22-JUN-09:30 | 24.65 | 15.33 |
July | 0.529808E+11 | 91481.47 | 05-JUL-04:12 | 15.00 | 8.93 | 0.547371E+10 | 7740.74 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.600127E+11 | 90920.52 | 19-AUG-04:12 | 12.33 | 5.72 | 0.614221E+10 | 7674.08 | 21-AUG-13:20 | 29.00 | 14.21 |
September | 0.539534E+11 | 94097.52 | 18-SEP-04:12 | 12.53 | 6.74 | 0.545207E+10 | 7632.73 | 05-SEP-13:00 | 12.53 | 6.74 |
October | 0.528801E+11 | 96628.73 | 23-OCT-03:01 | -2.2 | -2.2 | 0.566854E+10 | 7499.33 | 03-OCT-13:20 | -2.2 | -2.2 |
November | 0.502367E+11 | 98404.58 | 13-NOV-04:01 | 1.00 | 0.92 | 0.561066E+10 | 7499.16 | 29-NOV-10:39 | -9.0 | -9.0 |
December | 0.483871E+11 | 94109.08 | 11-DEC-04:01 | -6.8 | -8.8 | 0.539556E+10 | 7499.09 | 19-DEC-10:20 | -15.7 | -16.0 |
Annual Sum or Average | 0.592905E+12 | 0.678599E+11 | ||||||||
Minimum of Months | 0.381270E+11 | 90920.52 | -6.8 | -8.8 | 0.512736E+10 | 7499.09 | -15.7 | -16.0 | ||
Maximum of Months | 0.600127E+11 | 98404.58 | 15.00 | 8.93 | 0.614221E+10 | 7740.74 | 29.00 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339673E+11 | 79072.03 | 02-JAN-05:01 | -2.2 | -3.4 | 0.506538E+10 | 6734.80 | 10-JAN-10:20 | 2.33 | 2.33 |
February | 0.316457E+11 | 80020.93 | 21-FEB-04:01 | -1.0 | -1.0 | 0.459542E+10 | 6734.77 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.437155E+11 | 80825.76 | 13-MAR-04:12 | 6.67 | 1.13 | 0.549537E+10 | 6734.79 | 20-MAR-09:20 | 2.67 | 2.67 |
April | 0.422668E+11 | 82874.23 | 10-APR-04:11 | 2.67 | -3.2 | 0.488537E+10 | 6735.04 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.444306E+11 | 81658.30 | 30-MAY-04:12 | 8.67 | 7.88 | 0.528717E+10 | 6734.80 | 26-MAY-13:09 | 8.67 | 7.88 |
June | 0.541159E+11 | 85696.74 | 12-JUN-04:13 | 15.33 | 8.97 | 0.527389E+10 | 7212.81 | 22-JUN-09:39 | 24.37 | 15.23 |
July | 0.577798E+11 | 81644.00 | 07-JUL-04:13 | 15.67 | 8.47 | 0.490028E+10 | 7204.28 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.656663E+11 | 82747.08 | 22-AUG-04:13 | 14.93 | 11.73 | 0.549834E+10 | 6784.77 | 16-AUG-09:30 | 14.93 | 11.73 |
September | 0.469877E+11 | 87723.31 | 05-SEP-04:13 | 14.40 | 9.51 | 0.488330E+10 | 6743.00 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.431821E+11 | 85520.93 | 10-OCT-04:12 | 9.00 | 5.09 | 0.507789E+10 | 6734.90 | 03-OCT-13:09 | 9.00 | 5.09 |
November | 0.416420E+11 | 81545.89 | 13-NOV-04:01 | 1.00 | 0.92 | 0.502618E+10 | 6734.80 | 29-NOV-10:39 | -9.0 | -9.0 |
December | 0.387392E+11 | 82635.28 | 18-DEC-05:12 | 2.00 | -2.3 | 0.489159E+10 | 6734.81 | 20-DEC-10:20 | -18.0 | -18.4 |
Annual Sum or Average | 0.544139E+12 | 0.608802E+11 | ||||||||
Minimum of Months | 0.316457E+11 | 79072.03 | -2.2 | -3.4 | 0.459542E+10 | 6734.77 | -18.0 | -18.4 | ||
Maximum of Months | 0.656663E+11 | 87723.31 | 15.67 | 11.73 | 0.549834E+10 | 7212.81 | 29.40 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230843E+11 | 64686.84 | 21-JAN-06:02 | 8.17 | 1.79 | 0.493172E+10 | 6734.80 | 10-JAN-10:20 | 8.17 | 1.79 |
February | 0.206458E+11 | 54278.06 | 28-FEB-06:03 | -3.0 | -3.4 | 0.437151E+10 | 6734.74 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.277289E+11 | 70431.63 | 16-MAR-05:02 | 7.83 | 0.85 | 0.536393E+10 | 6734.77 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.242961E+11 | 67958.30 | 21-APR-05:03 | 5.83 | 3.87 | 0.480118E+10 | 6734.95 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.345792E+11 | 71334.28 | 31-MAY-05:02 | 12.17 | 9.76 | 0.527594E+10 | 6734.78 | 23-MAY-13:20 | 12.17 | 9.76 |
June | 0.427739E+11 | 72762.16 | 19-JUN-04:12 | 16.97 | 11.72 | 0.526791E+10 | 7027.00 | 22-JUN-09:39 | 24.37 | 15.23 |
July | 0.422280E+11 | 75580.94 | 24-JUL-04:13 | 18.00 | 14.77 | 0.489389E+10 | 7041.79 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.439140E+11 | 76038.50 | 28-AUG-04:11 | 14.33 | 14.13 | 0.549575E+10 | 6734.77 | 21-AUG-09:20 | 14.33 | 14.13 |
September | 0.377144E+11 | 75517.92 | 05-SEP-04:12 | 14.40 | 9.51 | 0.487531E+10 | 6735.32 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.293660E+11 | 70559.24 | 02-OCT-05:02 | 3.00 | 3.00 | 0.502043E+10 | 6734.76 | 03-OCT-09:20 | 9.00 | 7.34 |
November | 0.244595E+11 | 67419.88 | 09-NOV-06:03 | 9.17 | 4.69 | 0.492741E+10 | 6734.74 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.213045E+11 | 25917.42 | 15-DEC-16:20 | 4.67 | 1.42 | 0.461724E+10 | 6734.74 | 19-DEC-10:20 | -15.7 | -16.0 |
Annual Sum or Average | 0.372095E+12 | 0.598422E+11 | ||||||||
Minimum of Months | 0.206458E+11 | 25917.42 | -3.0 | -3.4 | 0.437151E+10 | 6734.74 | -15.7 | -16.0 | ||
Maximum of Months | 0.439140E+11 | 76038.50 | 18.00 | 14.77 | 0.549575E+10 | 7041.79 | 27.00 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154979E+11 | 26305.75 | 20-JAN-16:20 | 16.00 | 6.84 | 0.433728E+10 | 6734.56 | 26-JAN-14:20 | 9.00 | 2.97 |
February | 0.140538E+11 | 20907.43 | 23-FEB-17:00 | 5.00 | 2.11 | 0.395442E+10 | 6734.43 | 22-FEB-14:00 | 5.00 | 2.11 |
March | 0.216470E+11 | 50587.38 | 15-MAR-05:02 | 10.83 | 3.07 | 0.502623E+10 | 6734.76 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.207233E+11 | 43876.21 | 21-APR-05:03 | 5.83 | 3.87 | 0.451630E+10 | 6734.95 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.311928E+11 | 66627.05 | 11-MAY-05:02 | 8.00 | 4.11 | 0.518763E+10 | 6734.75 | 17-MAY-09:20 | 25.67 | 11.70 |
June | 0.453422E+11 | 75062.68 | 19-JUN-04:12 | 16.97 | 11.72 | 0.526986E+10 | 7037.00 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.444360E+11 | 79870.59 | 24-JUL-04:13 | 18.00 | 14.77 | 0.489572E+10 | 6971.35 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.453982E+11 | 75111.10 | 28-AUG-04:11 | 14.33 | 14.13 | 0.549463E+10 | 6734.77 | 21-AUG-09:20 | 14.33 | 14.13 |
September | 0.354077E+11 | 75248.27 | 05-SEP-04:12 | 14.40 | 9.51 | 0.484615E+10 | 6739.41 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.215840E+11 | 37953.98 | 11-OCT-15:20 | 25.33 | 9.18 | 0.468447E+10 | 6734.70 | 19-OCT-09:20 | 9.67 | 2.68 |
November | 0.167907E+11 | 29026.06 | 08-NOV-15:50 | 18.17 | 7.79 | 0.442104E+10 | 6734.56 | 17-NOV-14:20 | 13.33 | 5.89 |
December | 0.135325E+11 | 18112.94 | 14-DEC-15:40 | 14.00 | 4.66 | 0.407466E+10 | 6646.21 | 05-DEC-14:00 | 14.00 | 4.66 |
Annual Sum or Average | 0.325606E+12 | 0.567084E+11 | ||||||||
Minimum of Months | 0.135325E+11 | 18112.94 | 5.00 | 2.11 | 0.395442E+10 | 6646.21 | 5.00 | 2.11 | ||
Maximum of Months | 0.453982E+11 | 79870.59 | 25.33 | 14.77 | 0.549463E+10 | 7037.00 | 37.70 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209281E+10 | 3480.86 | 23-JAN-13:40 | 19.33 | 5.70 | 0.569553E+09 | 845.62 | 18-JAN-14:09 | 19.33 | 5.70 |
February | 0.194061E+10 | 4126.83 | 27-FEB-15:30 | 13.50 | 4.54 | 0.512686E+09 | 845.62 | 28-FEB-10:50 | 3.67 | 1.94 |
March | 0.346582E+10 | 6629.27 | 14-MAR-13:40 | 23.33 | 7.70 | 0.659840E+09 | 845.63 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.394340E+10 | 7373.46 | 20-APR-13:30 | 21.50 | 8.83 | 0.597314E+09 | 845.66 | 13-APR-13:50 | 21.50 | 8.83 |
May | 0.608101E+10 | 8760.69 | 17-MAY-13:30 | 29.00 | 11.78 | 0.660917E+09 | 845.64 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.102471E+11 | 16355.65 | 25-JUN-18:12 | 30.87 | 13.85 | 0.663499E+09 | 924.40 | 22-JUN-09:39 | 30.87 | 13.85 |
July | 0.105594E+11 | 15861.23 | 02-JUL-18:21 | 27.00 | 12.28 | 0.617294E+09 | 914.40 | 19-JUL-09:39 | 24.67 | 15.72 |
August | 0.105566E+11 | 13426.07 | 20-AUG-15:41 | 28.00 | 14.08 | 0.690906E+09 | 875.50 | 21-AUG-13:20 | 29.00 | 14.21 |
September | 0.654180E+10 | 14449.13 | 03-SEP-15:12 | 26.27 | 13.95 | 0.610715E+09 | 847.06 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.352379E+10 | 7106.13 | 10-OCT-14:30 | 25.00 | 8.59 | 0.607060E+09 | 845.64 | 03-OCT-13:09 | 25.00 | 8.59 |
November | 0.272727E+10 | 5476.49 | 09-NOV-13:20 | 20.00 | 8.84 | 0.586490E+09 | 845.61 | 08-NOV-14:20 | 20.00 | 8.84 |
December | 0.203684E+10 | 4669.01 | 04-DEC-12:00 | 20.00 | 6.71 | 0.549188E+09 | 845.62 | 12-DEC-14:30 | 8.00 | 1.97 |
Annual Sum or Average | 0.637164E+11 | 0.732546E+10 | ||||||||
Minimum of Months | 0.194061E+10 | 3480.86 | 13.50 | 4.54 | 0.512686E+09 | 845.61 | 3.67 | 1.94 | ||
Maximum of Months | 0.105594E+11 | 16355.65 | 30.87 | 14.08 | 0.690906E+09 | 924.40 | 30.87 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228905E+10 | 8624.86 | 20-JAN-09:30 | 12.00 | 3.86 | 0.387129E+09 | 544.96 | 10-JAN-10:09 | 12.00 | 3.86 |
February | 0.263554E+10 | 16152.59 | 26-FEB-10:12 | 13.33 | 3.27 | 0.348230E+09 | 544.96 | 23-FEB-10:09 | 13.33 | 3.27 |
March | 0.451618E+10 | 19830.85 | 12-MAR-08:32 | 13.00 | 4.70 | 0.429109E+09 | 546.33 | 15-MAR-09:09 | 14.17 | 4.19 |
April | 0.457548E+10 | 16571.56 | 09-APR-08:62 | 10.17 | 4.69 | 0.385384E+09 | 546.13 | 19-APR-09:09 | 18.17 | 8.45 |
May | 0.656969E+10 | 21443.58 | 28-MAY-09:52 | 14.00 | 9.00 | 0.427169E+09 | 545.93 | 16-MAY-09:09 | 14.00 | 9.00 |
June | 0.103743E+11 | 24329.04 | 11-JUN-07:51 | 17.20 | 10.73 | 0.427818E+09 | 634.61 | 22-JUN-09:09 | 25.22 | 15.51 |
July | 0.984799E+10 | 24533.47 | 02-JUL-07:41 | 17.50 | 8.14 | 0.398098E+09 | 657.77 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.104298E+11 | 22929.76 | 06-AUG-08:32 | 24.00 | 15.32 | 0.445506E+09 | 606.02 | 16-AUG-09:30 | 31.00 | 13.20 |
September | 0.737122E+10 | 22226.04 | 04-SEP-08:52 | 24.40 | 13.41 | 0.394771E+09 | 546.54 | 18-SEP-09:30 | 23.85 | 10.92 |
October | 0.404497E+10 | 18705.38 | 09-OCT-11:11 | 18.67 | 9.12 | 0.392297E+09 | 544.97 | 03-OCT-13:09 | 18.67 | 9.12 |
November | 0.272956E+10 | 15783.29 | 05-NOV-08:23 | 11.00 | 3.10 | 0.385615E+09 | 544.95 | 03-NOV-09:20 | 11.00 | 3.10 |
December | 0.185316E+10 | 7439.87 | 17-DEC-09:43 | 11.17 | 3.25 | 0.363658E+09 | 544.95 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.672370E+11 | 0.478478E+10 | ||||||||
Minimum of Months | 0.185316E+10 | 7439.87 | 10.17 | 3.10 | 0.348230E+09 | 544.95 | 3.33 | -0.7 | ||
Maximum of Months | 0.104298E+11 | 24533.47 | 24.40 | 15.32 | 0.445506E+09 | 657.77 | 31.00 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.997397E+10 | 25400.53 | 22-JAN-12:41 | 6.83 | 3.54 | 0.617395E+09 | 958.26 | 20-JAN-14:09 | 6.83 | 3.54 |
February | 0.916355E+10 | 26112.47 | 26-FEB-12:51 | 18.00 | 4.84 | 0.552613E+09 | 907.38 | 17-FEB-14:09 | 18.00 | 4.84 |
March | 0.964347E+10 | 27347.23 | 12-MAR-12:31 | 18.67 | 6.04 | 0.665463E+09 | 926.05 | 13-MAR-13:20 | 22.33 | 6.86 |
April | 0.675936E+10 | 22717.99 | 09-APR-12:02 | 15.83 | 5.03 | 0.591686E+09 | 849.15 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.766214E+10 | 12808.16 | 16-MAY-13:10 | 27.17 | 12.14 | 0.658644E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.114128E+11 | 23732.39 | 25-JUN-12:52 | 32.70 | 13.05 | 0.663337E+09 | 920.37 | 20-JUN-12:30 | 32.70 | 13.05 |
July | 0.121803E+11 | 23374.01 | 30-JUL-12:43 | 27.50 | 19.54 | 0.616902E+09 | 879.35 | 27-JUL-09:09 | 27.50 | 19.54 |
August | 0.151139E+11 | 23662.00 | 20-AUG-13:42 | 27.83 | 14.68 | 0.693399E+09 | 929.94 | 31-AUG-10:00 | 29.00 | 12.53 |
September | 0.129798E+11 | 24926.05 | 10-SEP-12:42 | 32.25 | 13.24 | 0.615004E+09 | 974.08 | 28-SEP-13:09 | 30.50 | 11.31 |
October | 0.111773E+11 | 28373.89 | 09-OCT-13:11 | 22.00 | 8.98 | 0.613170E+09 | 975.48 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.107835E+11 | 26938.17 | 19-NOV-10:51 | 10.00 | 4.18 | 0.617222E+09 | 967.40 | 07-NOV-14:09 | 10.00 | 4.18 |
December | 0.885086E+10 | 25729.71 | 17-DEC-13:01 | 18.00 | 5.78 | 0.588127E+09 | 927.29 | 14-DEC-14:09 | 18.00 | 5.78 |
Annual Sum or Average | 0.125701E+12 | 0.749296E+10 | ||||||||
Minimum of Months | 0.675936E+10 | 12808.16 | 6.83 | 3.54 | 0.552613E+09 | 845.68 | 6.83 | 3.54 | ||
Maximum of Months | 0.151139E+11 | 28373.89 | 32.70 | 19.54 | 0.693399E+09 | 975.48 | 32.70 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347921E+10 | 19056.10 | 22-JAN-16:02 | 8.50 | 4.50 | 0.394993E+09 | 544.96 | 10-JAN-10:20 | 8.50 | 4.50 |
February | 0.408791E+10 | 28542.47 | 26-FEB-15:31 | 17.67 | 4.94 | 0.361122E+09 | 544.96 | 08-FEB-14:09 | 17.67 | 4.94 |
March | 0.725493E+10 | 29703.44 | 12-MAR-14:31 | 17.67 | 5.67 | 0.443036E+09 | 544.95 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.783608E+10 | 26013.63 | 08-APR-17:42 | 14.33 | 4.60 | 0.394816E+09 | 544.99 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.783586E+10 | 27446.91 | 28-MAY-17:12 | 19.00 | 9.80 | 0.428372E+09 | 544.97 | 26-MAY-13:09 | 19.00 | 9.80 |
June | 0.130017E+11 | 33248.08 | 11-JUN-15:51 | 28.90 | 12.69 | 0.428385E+09 | 582.74 | 26-JUN-14:50 | 39.12 | 15.57 |
July | 0.130968E+11 | 33292.50 | 02-JUL-16:21 | 28.00 | 12.40 | 0.398669E+09 | 557.91 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.155726E+11 | 30545.49 | 13-AUG-16:31 | 22.33 | 9.94 | 0.447036E+09 | 576.72 | 02-AUG-15:00 | 22.33 | 9.94 |
September | 0.867881E+10 | 29078.67 | 10-SEP-16:01 | 31.92 | 12.68 | 0.395945E+09 | 556.96 | 12-SEP-15:00 | 31.10 | 14.26 |
October | 0.650624E+10 | 29810.72 | 09-OCT-13:51 | 22.00 | 8.58 | 0.405572E+09 | 544.98 | 03-OCT-13:09 | 22.00 | 8.58 |
November | 0.545241E+10 | 26905.34 | 05-NOV-15:02 | 20.67 | 6.59 | 0.403868E+09 | 544.95 | 16-NOV-14:09 | 16.00 | 6.65 |
December | 0.474242E+10 | 23283.97 | 03-DEC-15:02 | 17.67 | 6.57 | 0.388313E+09 | 544.96 | 21-DEC-14:30 | -16.0 | -16.7 |
Annual Sum or Average | 0.975450E+11 | 0.489013E+10 | ||||||||
Minimum of Months | 0.347921E+10 | 19056.10 | 8.50 | 4.50 | 0.361122E+09 | 544.95 | -16.0 | -16.7 | ||
Maximum of Months | 0.155726E+11 | 33292.50 | 31.92 | 12.69 | 0.447036E+09 | 582.74 | 39.12 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108730E+10 | 2152.60 | 20-JAN-15:10 | 19.67 | 6.93 | 0.497612E+09 | 805.79 | 20-JAN-14:00 | 19.67 | 6.93 |
February | 0.885650E+09 | 2128.66 | 27-FEB-15:30 | 13.50 | 4.54 | 0.444305E+09 | 792.43 | 27-FEB-14:00 | 13.50 | 4.54 |
March | 0.184047E+10 | 4952.11 | 14-MAR-14:40 | 23.00 | 7.59 | 0.584214E+09 | 845.61 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.204175E+10 | 5371.31 | 20-APR-13:30 | 21.50 | 8.83 | 0.542287E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.465788E+10 | 8324.26 | 17-MAY-13:30 | 29.00 | 11.78 | 0.647896E+09 | 845.63 | 10-MAY-13:39 | 29.00 | 11.78 |
June | 0.880801E+10 | 15862.94 | 25-JUN-18:12 | 30.87 | 13.85 | 0.662363E+09 | 909.09 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.860586E+10 | 15335.41 | 16-JUL-11:31 | 36.00 | 14.29 | 0.615777E+09 | 894.34 | 19-JUL-09:39 | 24.67 | 15.72 |
August | 0.759616E+10 | 12844.60 | 20-AUG-15:31 | 28.00 | 14.04 | 0.689198E+09 | 846.64 | 18-AUG-13:20 | 28.00 | 14.04 |
September | 0.525259E+10 | 14567.11 | 10-SEP-15:01 | 31.70 | 12.51 | 0.603522E+09 | 845.69 | 05-SEP-09:09 | 31.70 | 12.51 |
October | 0.214260E+10 | 5400.61 | 11-OCT-14:00 | 27.00 | 9.73 | 0.557817E+09 | 845.62 | 11-OCT-13:20 | 27.00 | 9.73 |
November | 0.132674E+10 | 3506.17 | 09-NOV-13:30 | 20.00 | 8.78 | 0.507646E+09 | 845.62 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.739136E+09 | 2067.05 | 04-DEC-14:30 | 19.50 | 6.42 | 0.463601E+09 | 782.62 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.449841E+11 | 0.681624E+10 | ||||||||
Minimum of Months | 0.739136E+09 | 2067.05 | 13.50 | 4.54 | 0.444305E+09 | 782.62 | 13.50 | 4.54 | ||
Maximum of Months | 0.880801E+10 | 15862.94 | 36.00 | 14.29 | 0.689198E+09 | 909.09 | 37.70 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125305E+10 | 7045.79 | 20-JAN-09:40 | 12.67 | 4.18 | 0.266974E+09 | 548.50 | 10-JAN-11:09 | 12.67 | 4.18 |
February | 0.158733E+10 | 9355.75 | 27-FEB-09:10 | 9.17 | 2.67 | 0.243828E+09 | 548.50 | 17-FEB-11:09 | 9.17 | 2.67 |
March | 0.339662E+10 | 17840.27 | 12-MAR-08:52 | 14.00 | 5.04 | 0.303071E+09 | 548.51 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.349092E+10 | 14146.90 | 21-APR-08:40 | 11.67 | 5.95 | 0.274146E+09 | 548.52 | 13-APR-10:09 | 11.67 | 5.95 |
May | 0.596559E+10 | 17457.62 | 28-MAY-09:32 | 13.33 | 8.91 | 0.313267E+09 | 548.54 | 31-MAY-10:09 | 25.17 | 13.22 |
June | 0.104413E+11 | 26321.78 | 11-JUN-08:61 | 17.67 | 10.77 | 0.315403E+09 | 603.85 | 22-JUN-08:00 | 25.50 | 15.60 |
July | 0.973646E+10 | 27097.00 | 09-JUL-09:11 | 25.33 | 12.97 | 0.294665E+09 | 617.74 | 27-JUL-08:00 | 27.00 | 15.92 |
August | 0.999291E+10 | 28333.69 | 06-AUG-08:51 | 25.00 | 15.42 | 0.328456E+09 | 548.56 | 30-AUG-10:09 | 25.17 | 12.29 |
September | 0.701221E+10 | 23887.91 | 17-SEP-08:51 | 17.20 | 10.18 | 0.290396E+09 | 548.53 | 01-SEP-14:09 | 17.20 | 10.18 |
October | 0.310737E+10 | 16947.38 | 01-OCT-09:12 | 13.33 | 7.78 | 0.278198E+09 | 548.51 | 10-OCT-14:09 | 25.00 | 8.67 |
November | 0.158854E+10 | 9138.38 | 05-NOV-09:23 | 15.00 | 5.03 | 0.266188E+09 | 548.50 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.740026E+09 | 3913.37 | 14-DEC-09:25 | 9.00 | 1.12 | 0.243941E+09 | 548.49 | 15-DEC-13:09 | 11.17 | 2.99 |
Annual Sum or Average | 0.583123E+11 | 0.341853E+10 | ||||||||
Minimum of Months | 0.740026E+09 | 3913.37 | 9.00 | 1.12 | 0.243828E+09 | 548.49 | 0.33 | -0.4 | ||
Maximum of Months | 0.104413E+11 | 28333.69 | 25.33 | 15.42 | 0.328456E+09 | 617.74 | 27.00 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103137E+11 | 25449.22 | 22-JAN-12:52 | 7.00 | 3.62 | 0.614813E+09 | 1039.33 | 20-JAN-14:09 | 7.00 | 3.62 |
February | 0.908668E+10 | 26333.98 | 26-FEB-13:01 | 17.83 | 4.74 | 0.549919E+09 | 968.80 | 17-FEB-14:09 | 17.83 | 4.74 |
March | 0.894045E+10 | 25262.75 | 12-MAR-12:12 | 18.33 | 6.09 | 0.646532E+09 | 963.40 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.546126E+10 | 16428.58 | 12-APR-13:05 | 21.00 | 7.79 | 0.569117E+09 | 847.61 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.685717E+10 | 13947.16 | 28-MAY-14:13 | 20.00 | 9.85 | 0.650859E+09 | 845.68 | 10-MAY-13:39 | 20.00 | 9.85 |
June | 0.103265E+11 | 23649.45 | 25-JUN-12:52 | 32.70 | 13.05 | 0.662160E+09 | 910.31 | 20-JUN-12:30 | 32.70 | 13.05 |
July | 0.106095E+11 | 24105.28 | 30-JUL-11:42 | 24.83 | 19.27 | 0.615785E+09 | 858.76 | 19-JUL-09:39 | 24.83 | 19.27 |
August | 0.130629E+11 | 24981.32 | 20-AUG-10:51 | 29.00 | 14.54 | 0.692006E+09 | 928.22 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.129846E+11 | 27152.20 | 17-SEP-12:11 | 24.97 | 10.63 | 0.614515E+09 | 1043.78 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.111568E+11 | 29469.60 | 08-OCT-12:51 | 21.00 | 8.56 | 0.604866E+09 | 1021.81 | 10-OCT-13:30 | 24.50 | 8.32 |
November | 0.104939E+11 | 30118.75 | 05-NOV-13:21 | 21.00 | 6.47 | 0.608500E+09 | 1035.53 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.789051E+10 | 27826.67 | 03-DEC-12:11 | 16.40 | 5.87 | 0.570952E+09 | 971.13 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.117184E+12 | 0.740002E+10 | ||||||||
Minimum of Months | 0.546126E+10 | 13947.16 | 7.00 | 3.62 | 0.549919E+09 | 845.68 | 7.00 | 3.62 | ||
Maximum of Months | 0.130629E+11 | 30118.75 | 32.70 | 19.27 | 0.692006E+09 | 1043.78 | 32.70 | 19.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198898E+10 | 9755.26 | 20-JAN-15:40 | 18.67 | 7.30 | 0.353119E+09 | 544.96 | 20-JAN-14:20 | 18.67 | 7.30 |
February | 0.203422E+10 | 10847.63 | 26-FEB-15:42 | 17.83 | 5.06 | 0.318298E+09 | 544.95 | 17-FEB-14:20 | 17.83 | 5.06 |
March | 0.367162E+10 | 25601.64 | 12-MAR-16:12 | 18.00 | 5.71 | 0.399284E+09 | 544.95 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.349476E+10 | 24475.28 | 08-APR-17:03 | 15.67 | 5.07 | 0.363856E+09 | 544.98 | 13-APR-13:50 | 15.50 | 9.79 |
May | 0.579299E+10 | 17391.04 | 07-MAY-15:42 | 22.17 | 8.70 | 0.420948E+09 | 544.97 | 10-MAY-13:39 | 24.67 | 8.89 |
June | 0.101442E+11 | 31173.36 | 25-JUN-16:11 | 32.70 | 13.79 | 0.427288E+09 | 557.46 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.885240E+10 | 28178.17 | 01-JUL-17:41 | 28.17 | 10.55 | 0.397376E+09 | 553.01 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.927523E+10 | 29017.15 | 20-AUG-15:32 | 28.00 | 14.04 | 0.445480E+09 | 547.65 | 02-AUG-15:00 | 28.00 | 14.04 |
September | 0.672801E+10 | 30753.42 | 10-SEP-16:21 | 31.35 | 12.48 | 0.392122E+09 | 545.00 | 05-SEP-09:09 | 31.35 | 12.48 |
October | 0.389911E+10 | 28847.21 | 08-OCT-16:11 | 17.67 | 8.51 | 0.373792E+09 | 544.95 | 06-OCT-13:20 | 17.67 | 8.51 |
November | 0.233112E+10 | 22796.53 | 05-NOV-15:21 | 20.00 | 6.21 | 0.355757E+09 | 544.99 | 07-NOV-14:30 | 22.00 | 7.34 |
December | 0.135926E+10 | 16955.57 | 03-DEC-15:31 | 16.67 | 6.40 | 0.328549E+09 | 544.96 | 14-DEC-14:00 | 16.00 | 4.43 |
Annual Sum or Average | 0.595719E+11 | 0.457587E+10 | ||||||||
Minimum of Months | 0.135926E+10 | 9755.26 | 15.67 | 5.06 | 0.318298E+09 | 544.95 | 11.67 | 3.37 | ||
Maximum of Months | 0.101442E+11 | 31173.36 | 32.70 | 14.04 | 0.445480E+09 | 557.46 | 37.70 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574186E+09 | 2130.40 | 20-JAN-15:50 | 18.33 | 7.40 | 0.478906E+09 | 795.12 | 20-JAN-14:00 | 18.33 | 7.40 |
February | 0.517272E+09 | 1988.60 | 27-FEB-14:50 | 14.00 | 4.75 | 0.431777E+09 | 745.26 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.142124E+10 | 5075.68 | 14-MAR-14:30 | 23.00 | 7.59 | 0.564165E+09 | 845.61 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.170962E+10 | 5982.92 | 20-APR-13:30 | 21.50 | 8.83 | 0.522038E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.433145E+10 | 8792.32 | 17-MAY-13:30 | 29.00 | 11.78 | 0.631986E+09 | 845.63 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.916921E+10 | 17389.12 | 04-JUN-16:51 | 29.40 | 12.14 | 0.662013E+09 | 915.49 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.894444E+10 | 18265.51 | 23-JUL-14:43 | 33.33 | 16.42 | 0.615291E+09 | 874.26 | 19-JUL-09:39 | 33.33 | 16.42 |
August | 0.783503E+10 | 16949.74 | 06-AUG-13:01 | 30.17 | 15.84 | 0.687508E+09 | 845.64 | 09-AUG-13:09 | 26.17 | 14.42 |
September | 0.509788E+10 | 17340.36 | 10-SEP-15:11 | 31.80 | 12.56 | 0.595459E+09 | 846.27 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.165346E+10 | 5626.50 | 11-OCT-14:30 | 26.50 | 9.60 | 0.530725E+09 | 845.62 | 11-OCT-13:20 | 26.50 | 9.60 |
November | 0.796277E+09 | 2919.63 | 09-NOV-13:40 | 20.00 | 8.72 | 0.489437E+09 | 845.60 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.390063E+09 | 1948.39 | 01-DEC-15:00 | 21.00 | 7.36 | 0.452949E+09 | 743.90 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.424401E+11 | 0.666225E+10 | ||||||||
Minimum of Months | 0.390063E+09 | 1948.39 | 14.00 | 4.75 | 0.431777E+09 | 743.90 | 14.00 | 4.75 | ||
Maximum of Months | 0.916921E+10 | 18265.51 | 33.33 | 16.42 | 0.687508E+09 | 915.49 | 37.70 | 16.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.962128E+09 | 5350.63 | 20-JAN-09:50 | 13.33 | 4.49 | 0.345765E+09 | 544.96 | 10-JAN-10:20 | 13.33 | 4.49 |
February | 0.122814E+10 | 6640.58 | 27-FEB-09:20 | 9.33 | 2.70 | 0.323175E+09 | 544.96 | 23-FEB-10:09 | 9.33 | 2.70 |
March | 0.299504E+10 | 15689.70 | 12-MAR-09:22 | 14.50 | 5.32 | 0.405653E+09 | 544.96 | 27-MAR-09:39 | 0.67 | -0.6 |
April | 0.323682E+10 | 13612.85 | 21-APR-08:50 | 11.83 | 5.97 | 0.366167E+09 | 544.98 | 13-APR-13:50 | 11.83 | 5.97 |
May | 0.578174E+10 | 16661.42 | 28-MAY-09:22 | 13.00 | 8.85 | 0.421190E+09 | 545.60 | 16-MAY-09:09 | 13.00 | 8.85 |
June | 0.109148E+11 | 23997.38 | 11-JUN-08:52 | 20.00 | 10.75 | 0.427433E+09 | 622.48 | 22-JUN-09:30 | 24.65 | 15.33 |
July | 0.101817E+11 | 26430.81 | 09-JUL-08:41 | 23.67 | 12.69 | 0.397810E+09 | 634.00 | 27-JUL-09:09 | 27.00 | 15.85 |
August | 0.103914E+11 | 27715.51 | 06-AUG-08:21 | 23.50 | 15.25 | 0.445064E+09 | 546.33 | 31-AUG-09:50 | 26.67 | 13.56 |
September | 0.701005E+10 | 23825.39 | 04-SEP-09:12 | 24.97 | 13.41 | 0.392143E+09 | 545.69 | 18-SEP-09:09 | 23.08 | 10.77 |
October | 0.264688E+10 | 14682.00 | 09-OCT-08:42 | 11.33 | 7.95 | 0.369713E+09 | 544.97 | 03-OCT-13:09 | 11.33 | 7.95 |
November | 0.126871E+10 | 6791.22 | 07-NOV-09:10 | 14.00 | 4.09 | 0.347497E+09 | 544.95 | 14-NOV-10:20 | 3.33 | 2.24 |
December | 0.611832E+09 | 2197.20 | 14-DEC-09:50 | 9.67 | 1.34 | 0.317486E+09 | 544.95 | 15-DEC-10:20 | 6.00 | 0.55 |
Annual Sum or Average | 0.572292E+11 | 0.455910E+10 | ||||||||
Minimum of Months | 0.611832E+09 | 2197.20 | 9.33 | 1.34 | 0.317486E+09 | 544.95 | 0.67 | -0.6 | ||
Maximum of Months | 0.109148E+11 | 27715.51 | 24.97 | 15.25 | 0.445064E+09 | 634.00 | 27.00 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844761E+10 | 28362.83 | 22-JAN-13:51 | 8.00 | 4.11 | 0.589625E+09 | 985.74 | 20-JAN-14:09 | 8.00 | 4.11 |
February | 0.786483E+10 | 27687.73 | 26-FEB-13:01 | 17.83 | 4.74 | 0.532572E+09 | 910.37 | 17-FEB-14:09 | 17.83 | 4.74 |
March | 0.802856E+10 | 29737.15 | 12-MAR-12:41 | 18.83 | 6.01 | 0.629370E+09 | 930.84 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.490104E+10 | 16893.09 | 21-APR-13:05 | 15.83 | 6.37 | 0.553067E+09 | 847.36 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.643750E+10 | 13550.94 | 16-MAY-13:20 | 27.33 | 12.20 | 0.637863E+09 | 845.67 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.107309E+11 | 25161.73 | 04-JUN-15:31 | 30.00 | 12.76 | 0.661269E+09 | 920.73 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.109788E+11 | 26815.37 | 30-JUL-13:12 | 28.33 | 19.61 | 0.615101E+09 | 871.66 | 12-JUL-13:00 | 28.33 | 19.61 |
August | 0.133272E+11 | 27625.05 | 06-AUG-13:01 | 30.17 | 15.84 | 0.689883E+09 | 908.58 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.127200E+11 | 29451.17 | 17-SEP-12:11 | 24.97 | 10.63 | 0.609249E+09 | 1008.93 | 28-SEP-13:39 | 30.50 | 11.31 |
October | 0.100700E+11 | 31782.83 | 09-OCT-13:21 | 22.00 | 8.88 | 0.582798E+09 | 978.17 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.881646E+10 | 32047.33 | 05-NOV-13:31 | 21.00 | 6.43 | 0.586953E+09 | 983.17 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.648217E+10 | 28745.14 | 03-DEC-12:11 | 16.40 | 5.87 | 0.552438E+09 | 908.15 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.108805E+12 | 0.724019E+10 | ||||||||
Minimum of Months | 0.490104E+10 | 13550.94 | 8.00 | 4.11 | 0.532572E+09 | 845.67 | 8.00 | 4.11 | ||
Maximum of Months | 0.133272E+11 | 32047.33 | 30.17 | 19.61 | 0.689883E+09 | 1008.93 | 37.70 | 19.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151576E+10 | 9671.14 | 20-JAN-15:40 | 18.67 | 7.30 | 0.340328E+09 | 544.94 | 09-JAN-14:20 | 18.67 | 7.30 |
February | 0.168712E+10 | 10438.58 | 17-FEB-16:30 | 13.50 | 6.66 | 0.309664E+09 | 544.94 | 28-FEB-14:20 | 4.67 | 2.76 |
March | 0.334099E+10 | 29609.84 | 12-MAR-16:41 | 18.00 | 5.62 | 0.386131E+09 | 544.94 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.326525E+10 | 25846.97 | 08-APR-17:03 | 15.67 | 5.07 | 0.351641E+09 | 544.98 | 13-APR-13:50 | 15.50 | 9.79 |
May | 0.555568E+10 | 27311.87 | 28-MAY-16:02 | 20.00 | 9.73 | 0.413556E+09 | 544.96 | 26-MAY-13:09 | 20.00 | 9.73 |
June | 0.103995E+11 | 32495.43 | 04-JUN-16:11 | 29.80 | 12.74 | 0.427096E+09 | 577.63 | 26-JUN-14:50 | 39.12 | 15.57 |
July | 0.909563E+10 | 33019.05 | 02-JUL-16:51 | 28.00 | 12.40 | 0.397075E+09 | 548.24 | 12-JUL-13:00 | 34.00 | 14.71 |
August | 0.943188E+10 | 29632.64 | 13-AUG-17:11 | 22.33 | 10.08 | 0.444865E+09 | 553.70 | 02-AUG-15:00 | 22.33 | 10.08 |
September | 0.661986E+10 | 33099.00 | 10-SEP-16:31 | 31.07 | 12.39 | 0.388671E+09 | 565.87 | 12-SEP-15:00 | 31.10 | 14.26 |
October | 0.344715E+10 | 30677.59 | 09-OCT-16:01 | 21.83 | 8.61 | 0.359120E+09 | 544.96 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.185881E+10 | 22869.63 | 05-NOV-15:31 | 19.67 | 6.02 | 0.343541E+09 | 544.94 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.103274E+10 | 7756.50 | 01-DEC-15:30 | 19.50 | 7.14 | 0.319369E+09 | 544.94 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.572503E+11 | 0.448106E+10 | ||||||||
Minimum of Months | 0.103274E+10 | 7756.50 | 13.50 | 5.07 | 0.309664E+09 | 544.94 | 4.67 | 2.76 | ||
Maximum of Months | 0.103995E+11 | 33099.00 | 31.07 | 12.74 | 0.444865E+09 | 577.63 | 39.12 | 15.57 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105646E+10 | 7268.54 | 05-JAN-06:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 0.963112E+09 | 4610.29 | 06-FEB-05:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-FEB-00:10 | -10.0 | -10.0 |
March | 0.248338E+10 | 6260.42 | 13-MAR-16:00 | 23.00 | 6.97 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 6.97 |
April | 0.270124E+10 | 5150.47 | 21-APR-13:50 | 15.17 | 5.71 | 0.00 | 0.00 | 01-APR-00:10 | 15.17 | 5.71 |
May | 0.431088E+10 | 6045.02 | 30-MAY-05:15 | 8.33 | 7.37 | 0.00 | 0.00 | 01-MAY-00:10 | 8.33 | 7.37 |
June | 0.813525E+10 | 11528.08 | 26-JUN-05:15 | 17.53 | 11.60 | 0.00 | 0.00 | 01-JUN-00:10 | 17.53 | 11.60 |
July | 0.839876E+10 | 10736.86 | 17-JUL-05:25 | 20.50 | 10.33 | 0.00 | 0.00 | 01-JUL-00:10 | 20.50 | 10.33 |
August | 0.891249E+10 | 11686.94 | 21-AUG-05:15 | 19.83 | 12.23 | 0.00 | 0.00 | 01-AUG-00:10 | 19.83 | 12.23 |
September | 0.607975E+10 | 12232.46 | 05-SEP-05:10 | 14.30 | 8.64 | 0.00 | 0.00 | 01-SEP-00:10 | 14.30 | 8.64 |
October | 0.316311E+10 | 9596.20 | 10-OCT-05:08 | 8.83 | 5.14 | 0.00 | 0.00 | 01-OCT-00:10 | 8.83 | 5.14 |
November | 0.212831E+10 | 5179.88 | 07-NOV-16:10 | 20.00 | 7.03 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 7.03 |
December | 0.110214E+10 | 7118.50 | 21-DEC-05:11 | -18.3 | -18.5 | 0.00 | 0.00 | 01-DEC-00:10 | -18.3 | -18.5 |
Annual Sum or Average | 0.494349E+11 | 0.00 | ||||||||
Minimum of Months | 0.963112E+09 | 4610.29 | -18.3 | -18.5 | 0.00 | 0.00 | -18.3 | -18.5 | ||
Maximum of Months | 0.891249E+10 | 12232.46 | 23.00 | 12.23 | 0.00 | 0.00 | 23.00 | 12.23 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265723E+09 | 11255.80 | 05-JAN-04:01 | -16.2 | -16.2 | 0.00 | 0.00 | 01-JAN-00:10 | -16.2 | -16.2 |
February | 0.232797E+09 | 9714.35 | 13-FEB-04:01 | -11.8 | -12.9 | 0.00 | 0.00 | 01-FEB-00:10 | -11.8 | -12.9 |
March | 0.835477E+09 | 12640.39 | 19-MAR-07:11 | -14.7 | -14.7 | 0.00 | 0.00 | 01-MAR-00:10 | -14.7 | -14.7 |
April | 0.536995E+09 | 10789.76 | 17-APR-03:01 | -8.0 | -8.4 | 0.00 | 0.00 | 01-APR-00:10 | -8.0 | -8.4 |
May | 0.242322E+10 | 4977.52 | 01-MAY-04:11 | 6.00 | 2.17 | 0.00 | 0.00 | 01-MAY-00:10 | 6.00 | 2.17 |
June | 0.610576E+10 | 8916.63 | 26-JUN-14:10 | 37.98 | 15.29 | 0.00 | 0.00 | 01-JUN-00:10 | 37.98 | 15.29 |
July | 0.614517E+10 | 8257.31 | 17-JUL-10:10 | 34.17 | 14.38 | 0.00 | 0.00 | 01-JUL-00:10 | 34.17 | 14.38 |
August | 0.603314E+10 | 7721.94 | 21-AUG-05:08 | 19.92 | 12.21 | 0.00 | 0.00 | 01-AUG-00:10 | 19.92 | 12.21 |
September | 0.419933E+10 | 6771.10 | 05-SEP-15:50 | 24.50 | 14.00 | 0.00 | 0.00 | 01-SEP-00:10 | 24.50 | 14.00 |
October | 0.123025E+10 | 12724.61 | 30-OCT-03:01 | -9.2 | -9.2 | 0.00 | 0.00 | 01-OCT-00:10 | -9.2 | -9.2 |
November | 0.411271E+09 | 11446.62 | 30-NOV-04:01 | -13.8 | -14.3 | 0.00 | 0.00 | 01-NOV-00:10 | -13.8 | -14.3 |
December | 0.196567E+09 | 14107.06 | 20-DEC-04:01 | -19.0 | -19.2 | 0.00 | 0.00 | 01-DEC-00:10 | -19.0 | -19.2 |
Annual Sum or Average | 0.286157E+11 | 0.00 | ||||||||
Minimum of Months | 0.196567E+09 | 4977.52 | -19.0 | -19.2 | 0.00 | 0.00 | -19.0 | -19.2 | ||
Maximum of Months | 0.614517E+10 | 14107.06 | 37.98 | 15.29 | 0.00 | 0.00 | 37.98 | 15.29 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215471E+09 | 4259.33 | 20-JAN-15:05 | 19.67 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 19.67 | 6.93 |
February | 0.355529E+09 | 4752.40 | 18-FEB-14:50 | 19.17 | 7.95 | 0.00 | 0.00 | 01-FEB-00:10 | 19.17 | 7.95 |
March | 0.194797E+10 | 11576.09 | 14-MAR-14:15 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.231711E+10 | 12056.37 | 21-APR-13:50 | 15.17 | 5.71 | 0.00 | 0.00 | 01-APR-00:10 | 15.17 | 5.71 |
May | 0.553754E+10 | 15883.30 | 31-MAY-14:20 | 28.00 | 14.79 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.79 |
June | 0.129831E+11 | 25455.10 | 26-JUN-14:50 | 39.12 | 15.57 | 0.00 | 0.00 | 01-JUN-00:10 | 39.12 | 15.57 |
July | 0.118837E+11 | 19341.63 | 12-JUL-13:20 | 32.67 | 14.39 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 14.39 |
August | 0.119597E+11 | 20699.62 | 16-AUG-15:00 | 36.00 | 16.15 | 0.00 | 0.00 | 01-AUG-00:10 | 36.00 | 16.15 |
September | 0.733922E+10 | 20537.00 | 12-SEP-13:32 | 29.40 | 13.70 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.70 |
October | 0.219929E+10 | 10803.70 | 11-OCT-14:40 | 26.33 | 9.55 | 0.00 | 0.00 | 01-OCT-00:10 | 26.33 | 9.55 |
November | 0.582856E+09 | 6767.36 | 09-NOV-13:05 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.103925E+09 | 2494.50 | 17-DEC-15:24 | 16.75 | 5.34 | 0.00 | 0.00 | 01-DEC-00:10 | 16.75 | 5.34 |
Annual Sum or Average | 0.574255E+11 | 0.00 | ||||||||
Minimum of Months | 0.103925E+09 | 2494.50 | 15.17 | 5.34 | 0.00 | 0.00 | 15.17 | 5.34 | ||
Maximum of Months | 0.129831E+11 | 25455.10 | 39.12 | 16.15 | 0.00 | 0.00 | 39.12 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330757E+10 | 2407.26 | 23-JAN-16:40 | 15.67 | 5.76 | 95230870.96 | 126.83 | 10-JAN-14:00 | 15.67 | 5.76 |
February | 0.765384E+10 | 4384.45 | 21-FEB-17:00 | 8.00 | 2.80 | 86396800.72 | 126.83 | 23-FEB-10:00 | 6.00 | 3.52 |
March | 0.140123E+11 | 7117.34 | 31-MAR-24:00 | 6.10 | 2.00 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.10 | 2.00 |
April | 0.185672E+11 | 8338.54 | 08-APR-18:00 | 14.00 | 4.47 | 91605700.58 | 126.83 | 28-APR-09:00 | 11.00 | 8.15 |
May | 0.423710E+10 | 3443.27 | 31-MAY-24:00 | 16.00 | 10.67 | 99237240.82 | 126.85 | 22-MAY-09:00 | 16.00 | 10.67 |
June | 0.940489E+10 | 5359.76 | 30-JUN-23:55 | 22.50 | 11.08 | 98962439.25 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.147467E+11 | 7236.60 | 31-JUL-24:00 | 18.90 | 16.75 | 91884656.85 | 126.85 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.197902E+11 | 8487.04 | 05-AUG-18:40 | 19.33 | 15.14 | 0.104260E+09 | 144.91 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.434251E+10 | 3305.50 | 30-SEP-24:00 | 10.40 | 8.79 | 91608059.45 | 126.85 | 01-SEP-13:00 | 10.40 | 8.79 |
October | 0.910904E+10 | 4976.98 | 09-OCT-16:42 | 21.17 | 8.73 | 95231480.95 | 126.84 | 03-OCT-13:00 | 21.17 | 8.73 |
November | 0.135888E+11 | 6503.65 | 05-NOV-16:13 | 17.67 | 5.18 | 94301054.01 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.187415E+11 | 8219.79 | 03-DEC-16:00 | 16.00 | 6.27 | 91880765.49 | 126.82 | 07-DEC-14:09 | 1.00 | -4.2 |
Annual Sum or Average | 0.137502E+12 | 0.114384E+10 | ||||||||
Minimum of Months | 0.330757E+10 | 2407.26 | 6.10 | 2.00 | 86396800.72 | 126.82 | 1.00 | -4.2 | ||
Maximum of Months | 0.197902E+11 | 8487.04 | 22.50 | 16.75 | 0.104260E+09 | 144.91 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161886E+10 | 2220.48 | 23-JAN-16:40 | 15.67 | 5.76 | 95216118.20 | 126.83 | 10-JAN-14:00 | 15.67 | 5.76 |
February | 0.564385E+10 | 4101.68 | 23-FEB-17:00 | 5.00 | 2.11 | 86396802.41 | 126.83 | 23-FEB-10:00 | 5.00 | 2.11 |
March | 0.119136E+11 | 6605.71 | 31-MAR-23:30 | 6.75 | 2.17 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.75 | 2.17 |
April | 0.163849E+11 | 7905.79 | 08-APR-18:00 | 14.00 | 4.47 | 91605719.27 | 126.83 | 28-APR-13:09 | 15.50 | 11.11 |
May | 0.351638E+10 | 3238.25 | 31-MAY-24:00 | 16.00 | 10.67 | 99236708.28 | 126.84 | 30-MAY-09:00 | 16.00 | 10.67 |
June | 0.879478E+10 | 5198.24 | 30-JUN-23:55 | 22.50 | 11.08 | 98962257.84 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.139366E+11 | 6830.27 | 31-JUL-24:00 | 18.90 | 16.75 | 91884627.82 | 126.84 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.187026E+11 | 8112.18 | 05-AUG-18:40 | 19.33 | 15.14 | 0.103989E+09 | 141.48 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.374256E+10 | 2973.53 | 30-SEP-23:50 | 10.50 | 8.84 | 91607740.66 | 126.84 | 01-SEP-13:09 | 10.50 | 8.84 |
October | 0.759426E+10 | 4485.75 | 08-OCT-16:42 | 17.17 | 8.30 | 95231426.81 | 126.83 | 03-OCT-13:00 | 17.17 | 8.30 |
November | 0.114336E+11 | 5912.40 | 07-NOV-16:20 | 19.00 | 6.82 | 94301064.78 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.155401E+11 | 7395.20 | 14-DEC-16:00 | 13.00 | 4.65 | 91880805.79 | 126.82 | 07-DEC-14:09 | 13.00 | 4.65 |
Annual Sum or Average | 0.118822E+12 | 0.114355E+10 | ||||||||
Minimum of Months | 0.161886E+10 | 2220.48 | 5.00 | 2.11 | 86396802.41 | 126.82 | 5.00 | 2.11 | ||
Maximum of Months | 0.187026E+11 | 8112.18 | 22.50 | 16.75 | 0.103989E+09 | 141.48 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700568E+09 | 2197.54 | 20-JAN-16:40 | 14.00 | 6.06 | 93325493.07 | 126.83 | 10-JAN-14:00 | 14.00 | 6.06 |
February | 0.415471E+10 | 4058.28 | 17-FEB-17:00 | 13.00 | 6.46 | 86396799.94 | 126.83 | 23-FEB-14:00 | 9.00 | 4.54 |
March | 0.105790E+11 | 6417.66 | 31-MAR-23:20 | 6.97 | 2.22 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.97 | 2.22 |
April | 0.150466E+11 | 7963.26 | 08-APR-18:00 | 14.00 | 4.47 | 91605799.74 | 126.83 | 28-APR-13:09 | 15.50 | 11.11 |
May | 0.304952E+10 | 3169.81 | 31-MAY-23:40 | 16.23 | 10.60 | 99202433.26 | 126.84 | 30-MAY-13:00 | 16.23 | 10.60 |
June | 0.878434E+10 | 5189.06 | 30-JUN-23:55 | 22.50 | 11.08 | 98962457.87 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.139426E+11 | 6733.78 | 31-JUL-24:00 | 18.90 | 16.75 | 91884795.44 | 126.84 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.186676E+11 | 8233.37 | 13-AUG-19:00 | 21.00 | 9.52 | 0.103883E+09 | 141.73 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.345971E+10 | 3123.16 | 10-SEP-17:32 | 29.77 | 11.98 | 91607538.47 | 126.85 | 01-SEP-13:00 | 29.77 | 11.98 |
October | 0.627716E+10 | 4490.38 | 08-OCT-16:42 | 17.17 | 8.30 | 95231408.94 | 126.83 | 03-OCT-13:00 | 17.17 | 8.30 |
November | 0.973958E+10 | 5923.92 | 07-NOV-16:20 | 19.00 | 6.82 | 94301096.92 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.136318E+11 | 7333.45 | 14-DEC-16:00 | 13.00 | 4.65 | 91880816.98 | 126.82 | 07-DEC-14:09 | 13.00 | 4.65 |
Annual Sum or Average | 0.108033E+12 | 0.114152E+10 | ||||||||
Minimum of Months | 0.700568E+09 | 2197.54 | 6.97 | 2.22 | 86396799.94 | 126.82 | 5.00 | 2.22 | ||
Maximum of Months | 0.186676E+11 | 8233.37 | 29.77 | 16.75 | 0.103883E+09 | 141.73 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236264E+12 | 90962.49 | 24-JAN-17:00 | 12.00 | 4.41 | 0.206152E+10 | 2745.53 | 09-JAN-10:09 | 12.00 | 4.41 |
February | 0.433309E+12 | 182540.21 | 27-FEB-17:00 | 13.00 | 4.60 | 0.187031E+10 | 2745.78 | 02-FEB-10:09 | 13.00 | 4.60 |
March | 0.726310E+12 | 358419.07 | 31-MAR-24:00 | 6.10 | 2.00 | 0.223484E+10 | 2746.17 | 30-MAR-09:09 | 6.10 | 2.00 |
April | 0.940283E+12 | 366125.63 | 10-APR-16:00 | 11.00 | 2.07 | 0.198324E+10 | 2751.07 | 28-APR-13:00 | 18.00 | 12.50 |
May | 0.238807E+12 | 175430.59 | 31-MAY-24:00 | 16.00 | 10.67 | 0.214821E+10 | 2746.96 | 17-MAY-13:00 | 16.00 | 10.67 |
June | 0.469236E+12 | 267554.22 | 30-JUN-23:55 | 22.50 | 11.08 | 0.214291E+10 | 2749.58 | 02-JUN-09:00 | 22.50 | 11.08 |
July | 0.730422E+12 | 358662.96 | 31-JUL-24:00 | 18.90 | 16.75 | 0.199010E+10 | 2750.25 | 26-JUL-09:09 | 18.90 | 16.75 |
August | 0.972162E+12 | 382756.13 | 16-AUG-21:12 | 25.33 | 11.70 | 0.265060E+10 | 5027.92 | 16-AUG-13:09 | 25.33 | 11.70 |
September | 0.235297E+12 | 175966.69 | 30-SEP-24:00 | 10.40 | 8.79 | 0.198336E+10 | 2747.70 | 13-SEP-13:09 | 10.40 | 8.79 |
October | 0.485559E+12 | 265714.77 | 31-OCT-23:55 | -5.8 | -5.8 | 0.206153E+10 | 2745.68 | 26-OCT-09:09 | -5.8 | -5.8 |
November | 0.706459E+12 | 275743.93 | 06-NOV-17:00 | 18.00 | 5.24 | 0.204142E+10 | 2745.87 | 09-NOV-10:09 | 18.33 | 8.73 |
December | 0.973682E+12 | 367170.71 | 04-DEC-17:00 | 12.00 | 4.76 | 0.198896E+10 | 2745.54 | 06-DEC-10:50 | -2.0 | -3.7 |
Annual Sum or Average | 0.714779E+13 | 0.251570E+11 | ||||||||
Minimum of Months | 0.235297E+12 | 90962.49 | -5.8 | -5.8 | 0.187031E+10 | 2745.53 | -5.8 | -5.8 | ||
Maximum of Months | 0.973682E+12 | 382756.13 | 25.33 | 16.75 | 0.265060E+10 | 5027.92 | 25.33 | 16.75 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191947E+09 | 11920.81 | 17-JAN-04:52 | -1.0 |
February | 0.125784E+09 | 11657.16 | 21-FEB-04:45 | -1.0 |
March | 89225594.69 | 11465.74 | 15-MAR-04:15 | 11.67 |
April | 64686281.36 | 11479.01 | 14-APR-04:15 | 5.67 |
May | 0.197403E+09 | 11508.65 | 16-MAY-04:15 | 10.00 |
June | 0.223043E+09 | 17630.17 | 24-JUN-16:01 | 31.60 |
July | 0.437022E+09 | 20523.12 | 15-JUL-16:01 | 34.00 |
August | 0.282238E+09 | 18758.48 | 26-AUG-16:01 | 32.67 |
September | 0.305580E+09 | 15443.43 | 02-SEP-16:01 | 29.62 |
October | 0.191076E+09 | 11561.35 | 17-OCT-03:15 | 1.33 |
November | 0.147196E+09 | 11559.09 | 27-NOV-04:07 | -7.0 |
December | 0.107385E+09 | 11362.43 | 04-DEC-04:25 | 1.50 |
Annual Sum or Average | 0.236259E+10 | |||
Minimum of Months | 64686281.36 | 11362.43 | -7.0 | |
Maximum of Months | 0.437022E+09 | 20523.12 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 18583375.41 | 37827.30 | 06-FEB-06:02 | -10.0 |
March | 2231245.49 | 26031.20 | 20-MAR-05:01 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 96727657.91 | 40449.43 | 26-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.117542E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 96727657.91 | 40449.43 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229408E+10 | 68332.85 | 17-JAN-04:11 | -1.7 |
February | 0.242017E+10 | 71656.08 | 06-FEB-04:01 | -10.0 |
March | 0.109885E+10 | 70294.09 | 20-MAR-03:11 | -1.0 |
April | 0.140246E+10 | 68241.51 | 17-APR-03:01 | -8.0 |
May | 82243416.51 | 61241.25 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.892449E+09 | 67115.11 | 30-OCT-03:01 | -9.2 |
November | 0.122944E+10 | 63689.16 | 27-NOV-05:01 | -7.0 |
December | 0.329716E+10 | 71465.98 | 26-DEC-04:11 | 1.00 |
Annual Sum or Average | 0.127169E+11 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.329716E+10 | 71656.08 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126958E+09 | 11588.53 | 06-JAN-05:01 | -7.8 |
February | 0.103189E+09 | 11406.45 | 13-FEB-05:01 | -11.0 |
March | 1591900.51 | 10731.60 | 20-MAR-05:01 | 0.00 |
April | 1111062.90 | 9501.12 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 13585706.44 | 10936.11 | 31-OCT-05:01 | -8.2 |
November | 40728678.32 | 11017.87 | 30-NOV-06:01 | -12.0 |
December | 0.397854E+09 | 12191.69 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.685019E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.397854E+09 | 12191.69 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94768545.43 | 11089.68 | 06-JAN-05:01 | -7.8 |
February | 0.115976E+09 | 10963.94 | 06-FEB-05:01 | -10.0 |
March | 6172609.23 | 9873.62 | 20-MAR-05:01 | 0.00 |
April | 6869449.50 | 9079.69 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 30048527.95 | 9903.69 | 31-OCT-05:01 | -8.2 |
November | 58279357.21 | 10603.49 | 30-NOV-05:01 | -12.8 |
December | 0.331483E+09 | 11887.82 | 21-DEC-05:11 | -18.3 |
Annual Sum or Average | 0.643597E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.3 | |
Maximum of Months | 0.331483E+09 | 11887.82 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151063E+09 | 15898.92 | 06-JAN-05:01 | -7.8 |
February | 0.253278E+09 | 16667.61 | 06-FEB-05:01 | -10.0 |
March | 34395311.92 | 15246.20 | 20-MAR-04:01 | 0.83 |
April | 55462870.37 | 14481.12 | 17-APR-04:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.102958E+09 | 15282.60 | 31-OCT-04:01 | -8.0 |
November | 96838457.17 | 15401.09 | 01-NOV-04:01 | -3.0 |
December | 0.398939E+09 | 16714.00 | 21-DEC-05:11 | -18.3 |
Annual Sum or Average | 0.109294E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.3 | |
Maximum of Months | 0.398939E+09 | 16714.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8107712.71 | 8476.21 | 05-JAN-06:01 | -17.0 |
February | 2097846.08 | 6979.35 | 06-FEB-06:02 | -10.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 3451971.38 | 8225.70 | 21-DEC-06:01 | -19.0 |
Annual Sum or Average | 13657530.17 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 8107712.71 | 8476.21 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150466E+10 | 12300.00 | 05-JAN-04:01 | -16.2 |
February | 0.215376E+10 | 13412.99 | 12-FEB-05:12 | -19.7 |
March | 0.101310E+10 | 13392.83 | 19-MAR-07:11 | -14.7 |
April | 0.496527E+09 | 12549.29 | 17-APR-03:01 | -8.0 |
May | 18848369.52 | 10884.19 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 6418653.83 | 10337.85 | 22-SEP-05:02 | -1.7 |
October | 0.638552E+09 | 12645.35 | 30-OCT-03:01 | -9.2 |
November | 0.112572E+10 | 12584.49 | 30-NOV-04:01 | -13.8 |
December | 0.353508E+10 | 13469.43 | 24-DEC-06:41 | -19.7 |
Annual Sum or Average | 0.104927E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.353508E+10 | 13469.43 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.667570E+09 | 16931.76 | 05-JAN-04:01 | -16.2 |
February | 0.104519E+10 | 17376.17 | 06-FEB-04:01 | -10.0 |
March | 0.536842E+09 | 17858.56 | 19-MAR-07:51 | -12.9 |
April | 0.272474E+09 | 16898.32 | 03-APR-03:01 | -8.0 |
May | 9285069.50 | 14295.42 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 2951078.34 | 8302.33 | 22-SEP-05:02 | -1.7 |
October | 0.409272E+09 | 17204.22 | 30-OCT-03:01 | -9.2 |
November | 0.600669E+09 | 17433.36 | 30-NOV-04:01 | -13.8 |
December | 0.180688E+10 | 18579.81 | 24-DEC-06:41 | -19.7 |
Annual Sum or Average | 0.535113E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.180688E+10 | 18579.81 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508818E+09 | 18394.03 | 05-JAN-04:01 | -16.2 |
February | 0.111135E+10 | 19232.40 | 06-FEB-04:01 | -10.0 |
March | 0.688026E+09 | 20124.01 | 19-MAR-07:51 | -12.9 |
April | 0.430135E+09 | 18833.81 | 17-APR-03:01 | -8.0 |
May | 22409722.10 | 16503.17 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 4795431.62 | 10948.75 | 22-SEP-05:02 | -1.7 |
October | 0.537780E+09 | 18723.79 | 30-OCT-03:01 | -9.2 |
November | 0.540285E+09 | 18703.39 | 01-NOV-03:02 | -3.5 |
December | 0.161900E+10 | 20179.01 | 24-DEC-06:41 | -19.7 |
Annual Sum or Average | 0.546260E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.161900E+10 | 20179.01 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498724E+09 | 16148.72 | 06-JAN-05:01 | -7.8 |
February | 0.749216E+09 | 17737.13 | 06-FEB-04:01 | -10.0 |
March | 0.361268E+09 | 16000.27 | 20-MAR-04:01 | 0.83 |
April | 0.213229E+09 | 16504.66 | 17-APR-03:01 | -8.0 |
May | 5850239.29 | 7101.91 | 01-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 3907449.25 | 8231.48 | 22-SEP-05:02 | -1.7 |
October | 0.312571E+09 | 17161.37 | 30-OCT-03:01 | -9.2 |
November | 0.410331E+09 | 17171.44 | 30-NOV-04:01 | -13.8 |
December | 0.137792E+10 | 18081.10 | 20-DEC-04:01 | -19.0 |
Annual Sum or Average | 0.393302E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 0.137792E+10 | 18081.10 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488911E+10 | 15497.93 | 16-JAN-03:02 | -10.0 |
February | 0.523638E+10 | 16364.37 | 12-FEB-05:12 | -19.7 |
March | 0.325823E+10 | 16336.24 | 19-MAR-03:12 | -8.9 |
April | 0.209518E+10 | 15614.81 | 17-APR-02:42 | -7.8 |
May | 0.182150E+09 | 14604.11 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 72256054.91 | 13005.15 | 22-SEP-04:02 | -0.3 |
October | 0.227258E+10 | 15624.49 | 29-OCT-19:23 | -6.5 |
November | 0.349385E+10 | 15449.43 | 30-NOV-03:23 | -14.0 |
December | 0.781335E+10 | 16683.69 | 24-DEC-04:11 | -19.7 |
Annual Sum or Average | 0.293131E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.781335E+10 | 16683.69 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229870E+10 | 19773.93 | 17-JAN-04:11 | -1.7 |
February | 0.265157E+10 | 21069.87 | 12-FEB-05:12 | -19.7 |
March | 0.172059E+10 | 21129.13 | 19-MAR-03:12 | -8.9 |
April | 0.116701E+10 | 19297.13 | 04-APR-03:01 | -2.0 |
May | 82623176.20 | 19095.42 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 34201625.14 | 16682.37 | 22-SEP-04:02 | -0.3 |
October | 0.138871E+10 | 19139.22 | 30-OCT-04:01 | -10.0 |
November | 0.180234E+10 | 20033.55 | 30-NOV-04:01 | -13.8 |
December | 0.424620E+10 | 21606.20 | 24-DEC-04:11 | -19.7 |
Annual Sum or Average | 0.153919E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.424620E+10 | 21606.20 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205647E+10 | 21597.47 | 05-JAN-04:01 | -16.2 |
February | 0.309919E+10 | 22904.77 | 12-FEB-05:12 | -19.7 |
March | 0.242468E+10 | 23304.33 | 19-MAR-03:12 | -8.9 |
April | 0.183217E+10 | 22144.89 | 17-APR-02:42 | -7.8 |
May | 0.187615E+09 | 20931.41 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 54235392.86 | 18342.31 | 22-SEP-04:02 | -0.3 |
October | 0.183442E+10 | 22028.46 | 29-OCT-19:23 | -6.5 |
November | 0.186803E+10 | 21962.94 | 01-NOV-03:11 | -3.4 |
December | 0.426338E+10 | 23503.06 | 24-DEC-04:11 | -19.7 |
Annual Sum or Average | 0.176202E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.426338E+10 | 23503.06 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180015E+10 | 21325.76 | 17-JAN-04:11 | -1.7 |
February | 0.205167E+10 | 22406.91 | 12-FEB-05:12 | -19.7 |
March | 0.130576E+10 | 22682.79 | 19-MAR-03:12 | -8.9 |
April | 0.827802E+09 | 20786.03 | 17-APR-03:01 | -8.0 |
May | 79649788.81 | 19913.46 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 31552623.20 | 15949.96 | 22-SEP-04:02 | -0.3 |
October | 0.999919E+09 | 20774.59 | 30-OCT-03:01 | -9.2 |
November | 0.133586E+10 | 21543.92 | 30-NOV-04:01 | -13.8 |
December | 0.325081E+10 | 23129.99 | 24-DEC-04:11 | -19.7 |
Annual Sum or Average | 0.116832E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.325081E+10 | 23129.99 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379288E+09 | 9214.71 | 22-JAN-16:02 | 8.50 |
February | 0.662211E+09 | 12962.86 | 26-FEB-15:31 | 17.67 |
March | 0.302043E+09 | 12968.15 | 26-MAR-15:22 | 11.00 |
April | 0.112237E+09 | 10754.06 | 05-APR-04:01 | 0.00 |
May | 82854133.48 | 10026.58 | 01-MAY-04:11 | 6.00 |
June | 0.101234E+09 | 13532.84 | 11-JUN-15:51 | 28.90 |
July | 0.143016E+09 | 12343.99 | 02-JUL-16:21 | 28.00 |
August | 0.122476E+09 | 12376.25 | 20-AUG-15:01 | 28.00 |
September | 0.104604E+09 | 11388.50 | 10-SEP-14:41 | 31.78 |
October | 0.202765E+09 | 12157.21 | 08-OCT-15:11 | 19.33 |
November | 0.410735E+09 | 13515.40 | 05-NOV-14:22 | 21.00 |
December | 0.687842E+09 | 12255.25 | 17-DEC-14:22 | 17.75 |
Annual Sum or Average | 0.331130E+10 | |||
Minimum of Months | 82854133.48 | 9214.71 | 0.00 | |
Maximum of Months | 0.687842E+09 | 13532.84 | 31.78 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188387E+10 | 11298.69 | 01-JAN-12:42 | 4.00 |
February | 0.217662E+10 | 10750.80 | 12-FEB-13:02 | -6.8 |
March | 0.136451E+10 | 16082.12 | 26-MAR-16:01 | 11.33 |
April | 0.101776E+10 | 7421.56 | 08-APR-17:42 | 14.33 |
May | 0.194910E+09 | 8257.48 | 28-MAY-14:13 | 20.00 |
June | 87131979.27 | 14326.94 | 11-JUN-16:01 | 28.72 |
July | 0.101944E+09 | 12491.66 | 04-JUL-14:51 | 27.00 |
August | 68558314.79 | 13745.99 | 20-AUG-15:31 | 28.00 |
September | 0.112360E+09 | 14165.67 | 10-SEP-15:01 | 31.70 |
October | 0.569347E+09 | 13336.47 | 08-OCT-14:51 | 20.00 |
November | 0.148859E+10 | 15315.23 | 05-NOV-14:41 | 21.00 |
December | 0.261807E+10 | 12568.29 | 03-DEC-15:31 | 16.67 |
Annual Sum or Average | 0.116837E+11 | |||
Minimum of Months | 68558314.79 | 7421.56 | -6.8 | |
Maximum of Months | 0.261807E+10 | 16082.12 | 31.70 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.623697E+10 | 25309.45 | 05-JAN-06:12 | -17.0 |
February | 0.602645E+10 | 27984.11 | 13-FEB-05:23 | -11.0 |
March | 0.431152E+10 | 21774.90 | 20-MAR-04:12 | 0.67 |
April | 0.310571E+10 | 25268.97 | 17-APR-04:12 | -8.0 |
May | 0.789846E+09 | 13351.09 | 11-MAY-05:02 | 8.00 |
June | 0.140840E+09 | 13782.41 | 09-JUN-05:03 | 6.97 |
July | 0.116462E+09 | 12544.91 | 03-JUL-04:12 | 11.00 |
August | 0.148081E+09 | 11071.05 | 14-AUG-05:03 | 15.33 |
September | 0.542914E+09 | 11773.25 | 06-SEP-05:03 | 13.30 |
October | 0.349091E+10 | 24383.29 | 30-OCT-04:12 | -10.0 |
November | 0.462441E+10 | 25754.38 | 30-NOV-06:12 | -12.0 |
December | 0.868239E+10 | 29696.19 | 22-DEC-05:22 | -21.0 |
Annual Sum or Average | 0.382165E+11 | |||
Minimum of Months | 0.116462E+09 | 11071.05 | -21.0 | |
Maximum of Months | 0.868239E+10 | 29696.19 | 15.33 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85876452.38 | 458.41 | 15-JAN-23:33 | -11.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 85876452.38 | |||
Minimum of Months | 0.00 | 0.00 | -11.0 | |
Maximum of Months | 85876452.38 | 458.41 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.702944E+09 | 709.01 | 01-JAN-18:25 | -1.0 |
February | 73191521.72 | 659.73 | 05-FEB-22:50 | -6.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 2475562.52 | 697.00 | 30-APR-23:20 | 5.33 |
May | 28299599.89 | 679.99 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 5209743.63 | 433.54 | 22-SEP-01:05 | -1.2 |
October | 10482063.36 | 546.75 | 30-OCT-05:01 | -10.0 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.822603E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.702944E+09 | 709.01 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.705438E+09 | 1147.25 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.599799E+09 | 1069.54 | 06-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.666096E+09 | 839.41 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.575650E+09 | 643.08 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.602923E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.592136E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.559345E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.634139E+09 | 595.13 | 28-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.582722E+09 | 601.42 | 21-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.642322E+09 | 967.51 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.690420E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.692861E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.754385E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.559345E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.705438E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.449209E+09 | 739.33 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.384524E+09 | 689.56 | 06-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.428410E+09 | 516.38 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.371775E+09 | 407.12 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.390944E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.384239E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.362824E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.410477E+09 | 387.96 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375801E+09 | 392.68 | 21-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.411383E+09 | 612.64 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.441784E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.442082E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.485345E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.362824E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.449209E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674687E+09 | 1147.28 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.586821E+09 | 1067.79 | 06-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.662500E+09 | 829.34 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.576968E+09 | 642.16 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.605657E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.595922E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.562767E+09 | 545.88 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.636445E+09 | 590.97 | 28-AUG-15:00 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.581929E+09 | 590.64 | 21-SEP-15:00 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.634542E+09 | 957.88 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.667129E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.668018E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.745338E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.562767E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.674687E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.439021E+09 | 739.33 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.379023E+09 | 686.57 | 06-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.425933E+09 | 548.86 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.369828E+09 | 484.86 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.388141E+09 | 351.77 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.381654E+09 | 372.93 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.360446E+09 | 351.77 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.406843E+09 | 381.95 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.374234E+09 | 397.17 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.409847E+09 | 624.89 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.431240E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.433724E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.479993E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.360446E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.439021E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.703831E+09 | 1147.25 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.598547E+09 | 1068.75 | 06-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.665234E+09 | 836.10 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.575340E+09 | 639.52 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.602741E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.592043E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.559000E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633704E+09 | 588.76 | 28-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.582205E+09 | 595.44 | 21-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.641074E+09 | 965.61 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.688882E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.691150E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.753375E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.559000E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.703831E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.448317E+09 | 739.33 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.383891E+09 | 688.28 | 06-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.427987E+09 | 511.14 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.371548E+09 | 404.73 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.390714E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.384029E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.362621E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.410221E+09 | 384.25 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375555E+09 | 389.25 | 21-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.410909E+09 | 609.54 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.440938E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.441350E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.484808E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.362621E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.448317E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674356E+09 | 1147.28 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.586429E+09 | 1066.99 | 06-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.661710E+09 | 825.97 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.576679E+09 | 638.55 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.605415E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.595674E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.562487E+09 | 545.88 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.636083E+09 | 584.41 | 28-AUG-15:00 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.581543E+09 | 584.14 | 21-SEP-15:00 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.633675E+09 | 955.97 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.666546E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.667845E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.744844E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.562487E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.674356E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.438439E+09 | 739.33 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.378559E+09 | 685.25 | 06-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.425656E+09 | 543.92 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.369625E+09 | 478.21 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.388015E+09 | 351.77 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.381559E+09 | 351.77 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.360366E+09 | 351.77 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.406718E+09 | 377.82 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.374036E+09 | 393.96 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.409412E+09 | 621.94 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.430486E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.433260E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.479613E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.360366E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.438439E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.703803E+09 | 1147.25 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.598517E+09 | 1068.58 | 06-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.665215E+09 | 835.46 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.575311E+09 | 639.37 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.602731E+09 | 545.86 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.592039E+09 | 545.86 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.558995E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633697E+09 | 588.51 | 28-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.582193E+09 | 595.20 | 21-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.640992E+09 | 965.23 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.688822E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.691082E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.753340E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.558995E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.703803E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.448305E+09 | 739.33 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.383877E+09 | 688.17 | 06-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.427976E+09 | 510.69 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.371541E+09 | 404.62 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.390707E+09 | 351.77 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.384012E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.362611E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.410216E+09 | 384.10 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375548E+09 | 389.11 | 21-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.410895E+09 | 609.29 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.440921E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.441335E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.484794E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.362611E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.448305E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674347E+09 | 1147.28 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.586414E+09 | 1066.82 | 06-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.661679E+09 | 825.31 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.576646E+09 | 638.40 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.605404E+09 | 545.88 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.595663E+09 | 545.88 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.562477E+09 | 545.88 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.636072E+09 | 584.15 | 28-AUG-15:00 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.581532E+09 | 583.88 | 21-SEP-15:00 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.633601E+09 | 955.58 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.666529E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.667836E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.744820E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.562477E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.674347E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.438417E+09 | 739.33 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.378539E+09 | 685.14 | 06-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.425649E+09 | 543.51 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.369606E+09 | 477.68 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.388010E+09 | 351.77 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.381546E+09 | 351.77 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.360359E+09 | 351.77 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.406717E+09 | 377.68 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.374032E+09 | 393.85 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.409397E+09 | 621.69 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.430473E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.433251E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.479600E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.360359E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.438417E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.705438E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491236E+09 |
February | 0.136985E+10 | 0.599799E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763717E+09 |
March | 0.163685E+10 | 0.666096E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | 0.839235E+09 |
April | 0.145243E+10 | 0.575650E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911729E+09 |
May | 0.157338E+10 | 0.602923E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1759332.54 | 0.455154E+09 |
June | 0.156900E+10 | 0.592136E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36054632.51 | 0.189922E+09 |
July | 0.145680E+10 | 0.559345E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45570420.79 | 0.185483E+09 |
August | 0.163685E+10 | 0.634139E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24525366.61 | 0.181767E+09 |
September | 0.145243E+10 | 0.582722E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13202114.31 | 0.286025E+09 |
October | 0.150991E+10 | 0.642322E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250133.64 | 0.638212E+09 |
November | 0.149516E+10 | 0.690420E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558350E+09 |
December | 0.145680E+10 | 0.692861E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105218E+10 |
Annual Sum or Average | 0.181194E+11 | 0.754385E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121362E+09 | 0.655301E+10 |
Minimum of Months | 0.136985E+10 | 0.559345E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181767E+09 |
Maximum of Months | 0.163685E+10 | 0.705438E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45570420.79 | 0.105218E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.449209E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333615E+09 |
February | 0.882782E+09 | 0.384524E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514342E+09 |
March | 0.105485E+10 | 0.428410E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.559454E+09 |
April | 0.936002E+09 | 0.371775E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602429E+09 |
May | 0.101394E+10 | 0.390944E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1172433.10 | 0.305208E+09 |
June | 0.101113E+10 | 0.384239E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23916676.84 | 0.125960E+09 |
July | 0.938820E+09 | 0.362824E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30231585.03 | 0.123201E+09 |
August | 0.105485E+10 | 0.410477E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16169161.49 | 0.118580E+09 |
September | 0.936002E+09 | 0.375801E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8369169.33 | 0.194822E+09 |
October | 0.973041E+09 | 0.411383E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166748.27 | 0.429663E+09 |
November | 0.963541E+09 | 0.441784E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372047E+09 |
December | 0.938820E+09 | 0.442082E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697773E+09 |
Annual Sum or Average | 0.116768E+11 | 0.485345E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80025776.92 | 0.437709E+10 |
Minimum of Months | 0.882782E+09 | 0.362824E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118580E+09 |
Maximum of Months | 0.105485E+10 | 0.449209E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30231585.03 | 0.697773E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.674687E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512879E+09 |
February | 0.136988E+10 | 0.586821E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784537E+09 |
March | 0.163688E+10 | 0.662500E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845131E+09 |
April | 0.145246E+10 | 0.576968E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895479E+09 |
May | 0.157341E+10 | 0.605657E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1758256.99 | 0.452785E+09 |
June | 0.156904E+10 | 0.595922E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35923735.42 | 0.188983E+09 |
July | 0.145684E+10 | 0.562767E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45371969.68 | 0.185835E+09 |
August | 0.163688E+10 | 0.636445E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23910359.72 | 0.188239E+09 |
September | 0.145246E+10 | 0.581929E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11840334.66 | 0.299376E+09 |
October | 0.150994E+10 | 0.634542E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132381.30 | 0.653161E+09 |
November | 0.149520E+10 | 0.667129E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573914E+09 |
December | 0.145684E+10 | 0.668018E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107676E+10 |
Annual Sum or Average | 0.181198E+11 | 0.745338E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118937E+09 | 0.665707E+10 |
Minimum of Months | 0.136988E+10 | 0.562767E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185835E+09 |
Maximum of Months | 0.163688E+10 | 0.674687E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45371969.68 | 0.107676E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.439021E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349888E+09 |
February | 0.882782E+09 | 0.379023E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549214E+09 |
March | 0.105485E+10 | 0.425933E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.612425E+09 |
April | 0.936002E+09 | 0.369828E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671677E+09 |
May | 0.101394E+10 | 0.388141E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171696.07 | 0.328281E+09 |
June | 0.101113E+10 | 0.381654E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23203009.57 | 0.149120E+09 |
July | 0.938820E+09 | 0.360446E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28824040.92 | 0.149654E+09 |
August | 0.105485E+10 | 0.406843E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15840068.74 | 0.151812E+09 |
September | 0.936002E+09 | 0.374234E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7914742.23 | 0.215126E+09 |
October | 0.973041E+09 | 0.409847E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166749.14 | 0.461223E+09 |
November | 0.963541E+09 | 0.431240E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406750E+09 |
December | 0.938820E+09 | 0.433724E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772374E+09 |
Annual Sum or Average | 0.116768E+11 | 0.479993E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77120309.73 | 0.481754E+10 |
Minimum of Months | 0.882782E+09 | 0.360446E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149120E+09 |
Maximum of Months | 0.105485E+10 | 0.439021E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28824040.92 | 0.772374E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.703831E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102715E+10 |
February | 0.136985E+10 | 0.598547E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160589E+10 |
March | 0.163685E+10 | 0.665234E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174333E+10 |
April | 0.145243E+10 | 0.575340E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186701E+10 |
May | 0.157338E+10 | 0.602741E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3924457.51 | 0.997384E+09 |
June | 0.156900E+10 | 0.592043E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83449563.16 | 0.429743E+09 |
July | 0.145680E+10 | 0.559000E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105918E+09 | 0.426906E+09 |
August | 0.163685E+10 | 0.633704E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57054821.49 | 0.417404E+09 |
September | 0.145243E+10 | 0.582205E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31587936.62 | 0.619212E+09 |
October | 0.150991E+10 | 0.641074E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540153.59 | 0.133973E+10 |
November | 0.149516E+10 | 0.688882E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116518E+10 |
December | 0.145680E+10 | 0.691150E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2724.76 | 0.216210E+10 |
Annual Sum or Average | 0.181194E+11 | 0.753375E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282478E+09 | 0.138010E+11 |
Minimum of Months | 0.136985E+10 | 0.559000E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417404E+09 |
Maximum of Months | 0.163685E+10 | 0.703831E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105918E+09 | 0.216210E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.448317E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718945E+09 |
February | 0.649041E+09 | 0.383891E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111667E+10 |
March | 0.773965E+09 | 0.427987E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121499E+10 |
April | 0.688021E+09 | 0.371548E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129287E+10 |
May | 0.744847E+09 | 0.390714E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2448182.29 | 0.688694E+09 |
June | 0.742030E+09 | 0.384029E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53469550.42 | 0.297178E+09 |
July | 0.690839E+09 | 0.362621E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66837302.52 | 0.301783E+09 |
August | 0.773965E+09 | 0.410221E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35766957.30 | 0.296211E+09 |
September | 0.688021E+09 | 0.375555E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18186336.39 | 0.441996E+09 |
October | 0.715730E+09 | 0.410909E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 314363.69 | 0.940792E+09 |
November | 0.708685E+09 | 0.440938E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806760E+09 |
December | 0.690839E+09 | 0.441350E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148383E+10 |
Annual Sum or Average | 0.858171E+10 | 0.484808E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177023E+09 | 0.960072E+10 |
Minimum of Months | 0.649041E+09 | 0.362621E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296211E+09 |
Maximum of Months | 0.773965E+09 | 0.448317E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66837302.52 | 0.148383E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.674356E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117196E+10 |
February | 0.136988E+10 | 0.586429E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176408E+10 |
March | 0.163688E+10 | 0.661710E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187535E+10 |
April | 0.145246E+10 | 0.576679E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193743E+10 |
May | 0.157341E+10 | 0.605415E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3920728.38 | 0.102079E+10 |
June | 0.156904E+10 | 0.595674E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82547990.65 | 0.431419E+09 |
July | 0.145684E+10 | 0.562487E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104005E+09 | 0.434148E+09 |
August | 0.163688E+10 | 0.636083E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54634183.91 | 0.447656E+09 |
September | 0.145246E+10 | 0.581543E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26285984.17 | 0.681553E+09 |
October | 0.150994E+10 | 0.633675E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 136361.23 | 0.146974E+10 |
November | 0.149520E+10 | 0.666546E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129341E+10 |
December | 0.145684E+10 | 0.667845E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238046E+10 |
Annual Sum or Average | 0.181198E+11 | 0.744844E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271530E+09 | 0.149080E+11 |
Minimum of Months | 0.136988E+10 | 0.562487E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431419E+09 |
Maximum of Months | 0.163688E+10 | 0.674356E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104005E+09 | 0.238046E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.438439E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734048E+09 |
February | 0.882782E+09 | 0.378559E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113681E+10 |
March | 0.105485E+10 | 0.425656E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123942E+10 |
April | 0.936002E+09 | 0.369625E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131725E+10 |
May | 0.101394E+10 | 0.388015E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2612961.48 | 0.711478E+09 |
June | 0.101113E+10 | 0.381559E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53538865.09 | 0.318822E+09 |
July | 0.938820E+09 | 0.360366E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66908959.43 | 0.316085E+09 |
August | 0.105485E+10 | 0.406718E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36683860.78 | 0.320556E+09 |
September | 0.936002E+09 | 0.374036E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18264541.57 | 0.459801E+09 |
October | 0.973041E+09 | 0.409412E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360076.66 | 0.953311E+09 |
November | 0.963541E+09 | 0.430486E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825648E+09 |
December | 0.938820E+09 | 0.433260E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151651E+10 |
Annual Sum or Average | 0.116768E+11 | 0.479613E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178369E+09 | 0.984973E+10 |
Minimum of Months | 0.882782E+09 | 0.360366E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316085E+09 |
Maximum of Months | 0.105485E+10 | 0.438439E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66908959.43 | 0.151651E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.703803E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118233E+10 |
February | 0.136985E+10 | 0.598517E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190269E+10 |
March | 0.163685E+10 | 0.665215E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206508E+10 |
April | 0.145243E+10 | 0.575311E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216379E+10 |
May | 0.157338E+10 | 0.602731E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4621985.70 | 0.118275E+10 |
June | 0.156900E+10 | 0.592039E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99995336.37 | 0.529684E+09 |
July | 0.145680E+10 | 0.558995E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125274E+09 | 0.528343E+09 |
August | 0.163685E+10 | 0.633697E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68178749.60 | 0.513969E+09 |
September | 0.145243E+10 | 0.582193E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36407635.40 | 0.738717E+09 |
October | 0.150991E+10 | 0.640992E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 616148.96 | 0.154726E+10 |
November | 0.149516E+10 | 0.688822E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2542.67 | 0.134881E+10 |
December | 0.145680E+10 | 0.691082E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12153.92 | 0.257242E+10 |
Annual Sum or Average | 0.181194E+11 | 0.753340E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335109E+09 | 0.162758E+11 |
Minimum of Months | 0.136985E+10 | 0.558995E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513969E+09 |
Maximum of Months | 0.163685E+10 | 0.703803E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125274E+09 | 0.257242E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.448305E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819520E+09 |
February | 0.882782E+09 | 0.383877E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132202E+10 |
March | 0.105485E+10 | 0.427976E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144152E+10 |
April | 0.936002E+09 | 0.371541E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150360E+10 |
May | 0.101394E+10 | 0.390707E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3080515.58 | 0.820455E+09 |
June | 0.101113E+10 | 0.384012E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65562879.99 | 0.365894E+09 |
July | 0.938820E+09 | 0.362611E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81384804.27 | 0.373052E+09 |
August | 0.105485E+10 | 0.410216E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44219708.09 | 0.364040E+09 |
September | 0.936002E+09 | 0.375548E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22247467.15 | 0.531420E+09 |
October | 0.973041E+09 | 0.410895E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409488.80 | 0.109582E+10 |
November | 0.963541E+09 | 0.440921E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933413E+09 |
December | 0.938820E+09 | 0.441335E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175475E+10 |
Annual Sum or Average | 0.116768E+11 | 0.484794E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216905E+09 | 0.113255E+11 |
Minimum of Months | 0.882782E+09 | 0.362611E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364040E+09 |
Maximum of Months | 0.105485E+10 | 0.448305E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81384804.27 | 0.175475E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.674347E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134442E+10 |
February | 0.136988E+10 | 0.586414E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208930E+10 |
March | 0.163688E+10 | 0.661679E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222674E+10 |
April | 0.145246E+10 | 0.576646E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224960E+10 |
May | 0.157341E+10 | 0.605404E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4620721.95 | 0.121480E+10 |
June | 0.156904E+10 | 0.595663E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99347625.59 | 0.531217E+09 |
July | 0.145684E+10 | 0.562477E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123906E+09 | 0.536164E+09 |
August | 0.163688E+10 | 0.636072E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65948184.95 | 0.550042E+09 |
September | 0.145246E+10 | 0.581532E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31471209.10 | 0.820164E+09 |
October | 0.150994E+10 | 0.633601E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 243403.43 | 0.171506E+10 |
November | 0.149520E+10 | 0.666529E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151450E+10 |
December | 0.145684E+10 | 0.667836E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280308E+10 |
Annual Sum or Average | 0.181198E+11 | 0.744820E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325537E+09 | 0.175951E+11 |
Minimum of Months | 0.136988E+10 | 0.562477E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531217E+09 |
Maximum of Months | 0.163688E+10 | 0.674347E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123906E+09 | 0.280308E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.438417E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844553E+09 |
February | 0.882782E+09 | 0.378539E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135221E+10 |
March | 0.105485E+10 | 0.425649E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147519E+10 |
April | 0.936002E+09 | 0.369606E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153611E+10 |
May | 0.101394E+10 | 0.388010E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3079996.04 | 0.852993E+09 |
June | 0.101113E+10 | 0.381546E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64708262.74 | 0.391626E+09 |
July | 0.938820E+09 | 0.360359E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80541602.07 | 0.389126E+09 |
August | 0.105485E+10 | 0.406717E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44254154.58 | 0.393514E+09 |
September | 0.936002E+09 | 0.374032E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21756314.70 | 0.553457E+09 |
October | 0.973041E+09 | 0.409397E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409533.97 | 0.111626E+10 |
November | 0.963541E+09 | 0.430473E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968465E+09 |
December | 0.938820E+09 | 0.433251E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180224E+10 |
Annual Sum or Average | 0.116768E+11 | 0.479600E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214750E+09 | 0.116758E+11 |
Minimum of Months | 0.882782E+09 | 0.360359E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389126E+09 |
Maximum of Months | 0.105485E+10 | 0.438417E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80541602.07 | 0.180224E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106968E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165499E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181029E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193887E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2601476.82 | 0.954039E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67471918.63 | 0.397805E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90697315.76 | 0.393942E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43593631.36 | 0.397879E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23390869.82 | 0.612804E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199103.60 | 0.137593E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120331E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227275E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227954E+09 | 0.140823E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393942E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90697315.76 | 0.227275E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182582E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281514E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307892E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328258E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4739437.91 | 0.166691E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123479E+09 | 0.699667E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167425E+09 | 0.692329E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79726827.91 | 0.698621E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44030713.95 | 0.107165E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385928.11 | 0.237774E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205054E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377667E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419787E+09 | 0.240366E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692329E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167425E+09 | 0.377667E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184073E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293858E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322411E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341705E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3116170.61 | 0.184752E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108388E+09 | 0.795611E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137446E+09 | 0.796678E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68227381.06 | 0.798824E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31942759.43 | 0.116881E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96635.44 | 0.246501E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211267E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389777E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349217E+09 | 0.253034E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795611E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137446E+09 | 0.389777E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 947.36 | 13-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1069.54 | 06-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1182.40 | 05-FEB-22:53 |
March | 2010.79 | 01-MAR-10:09 | 839.41 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 2444.03 | 19-MAR-07:00 |
April | 2010.79 | 03-APR-09:09 | 643.08 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1733.08 | 16-APR-15:00 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 970.40 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.15 | 25-JUN-17:34 | 554.71 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 16-JUL-12:00 | 538.08 | 03-JUL-03:10 |
August | 2010.79 | 01-AUG-09:09 | 595.13 | 28-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.53 | 02-AUG-15:10 | 642.29 | 27-AUG-17:43 |
September | 2010.79 | 01-SEP-09:09 | 601.42 | 21-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.43 | 10-SEP-14:46 | 611.38 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 967.51 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 11-OCT-14:00 | 1467.89 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1417.67 | 01-NOV-03:52 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2034.13 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.08 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 2444.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 646.14 | 08-JAN-09:00 |
February | 1295.83 | 01-FEB-10:09 | 689.56 | 06-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 774.08 | 05-FEB-22:53 |
March | 1295.83 | 01-MAR-10:09 | 516.38 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1601.23 | 19-MAR-07:00 |
April | 1295.83 | 03-APR-09:09 | 407.12 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1151.74 | 16-APR-15:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-MAY-14:50 | 640.65 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.02 | 25-JUN-17:33 | 365.48 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.28 | 16-JUL-12:00 | 393.73 | 02-JUL-09:00 |
August | 1295.83 | 01-AUG-09:09 | 387.96 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 02-AUG-15:10 | 413.76 | 27-AUG-17:43 |
September | 1295.83 | 01-SEP-09:09 | 392.68 | 21-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.20 | 10-SEP-14:44 | 404.78 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 612.64 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 970.83 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 925.51 | 01-NOV-03:52 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1334.03 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.48 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 253.28 | 1601.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 953.06 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 1067.79 | 06-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1194.10 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 829.34 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2345.36 | 19-MAR-07:00 |
April | 2010.83 | 03-APR-09:09 | 642.16 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1628.62 | 16-APR-15:00 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 950.52 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.98 | 25-JUN-18:00 | 551.70 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 545.88 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 16-JUL-12:00 | 536.83 | 03-JUL-03:10 |
August | 2010.83 | 01-AUG-09:09 | 590.97 | 28-AUG-15:00 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.52 | 02-AUG-15:10 | 701.26 | 27-AUG-17:43 |
September | 2010.83 | 01-SEP-09:09 | 590.64 | 21-SEP-15:00 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.81 | 10-SEP-14:55 | 603.53 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 957.88 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 11-OCT-14:00 | 1435.00 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1375.20 | 01-NOV-04:04 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2042.20 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.83 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 2345.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 668.77 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 686.57 | 06-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 837.30 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 548.86 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 1713.59 | 19-MAR-07:00 |
April | 1295.83 | 03-APR-09:09 | 484.86 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1261.68 | 16-APR-15:00 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 17-MAY-14:50 | 690.00 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 372.93 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.75 | 25-JUN-17:33 | 437.30 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.28 | 16-JUL-12:00 | 408.46 | 03-JUL-03:10 |
August | 1295.83 | 01-AUG-09:09 | 381.95 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 | 02-AUG-15:00 | 546.90 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 397.17 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.20 | 10-SEP-15:00 | 423.00 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 624.89 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 1036.57 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1007.89 | 01-NOV-03:52 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1444.09 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.46 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 253.28 | 1713.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1979.39 | 13-JAN-05:06 |
February | 2010.79 | 01-FEB-10:09 | 1068.75 | 06-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2391.39 | 23-FEB-24:00 |
March | 2010.79 | 01-MAR-10:09 | 836.10 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5275.57 | 19-MAR-07:00 |
April | 2010.79 | 03-APR-09:09 | 639.52 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.24 | 15-APR-04:59 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 2018.29 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 529.04 | 25-JUN-17:34 | 1207.92 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 16-JUL-12:00 | 1183.69 | 03-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 588.76 | 28-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.59 | 02-AUG-15:30 | 1448.93 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 595.44 | 21-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.65 | 10-SEP-14:41 | 1330.59 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 965.61 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 11-OCT-14:00 | 2902.23 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3238.79 | 01-NOV-04:09 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 02-DEC-15:00 | 4403.50 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.69 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 5275.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 739.33 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1327.76 | 13-JAN-05:04 |
February | 1239.33 | 01-FEB-08:09 | 688.28 | 06-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1649.74 | 23-FEB-24:00 |
March | 1239.33 | 01-MAR-08:09 | 511.14 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3516.65 | 19-MAR-07:00 |
April | 1239.33 | 03-APR-07:10 | 404.73 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.21 | 15-APR-05:00 |
May | 1239.33 | 01-MAY-07:10 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1355.94 | 03-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.47 | 25-JUN-17:33 | 815.96 | 08-JUN-23:00 |
July | 1239.33 | 03-JUL-07:10 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.03 | 16-JUL-12:00 | 917.28 | 02-JUL-08:30 |
August | 1239.33 | 01-AUG-07:10 | 384.25 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.06 | 02-AUG-15:30 | 1033.78 | 27-AUG-17:55 |
September | 1239.33 | 01-SEP-07:10 | 389.25 | 21-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.70 | 10-SEP-15:03 | 891.75 | 22-SEP-02:00 |
October | 1239.33 | 02-OCT-07:10 | 609.54 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 | 11-OCT-14:10 | 1968.25 | 29-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2169.85 | 01-NOV-04:04 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2914.74 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.96 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 587.03 | 3516.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2086.24 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 1066.99 | 06-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2695.73 | 19-FEB-16:55 |
March | 2010.83 | 01-MAR-10:09 | 825.97 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5275.30 | 19-MAR-07:00 |
April | 2010.83 | 03-APR-09:09 | 638.55 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.28 | 15-APR-04:53 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 2057.73 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.35 | 25-JUN-18:00 | 1206.29 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 545.88 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 16-JUL-12:00 | 1192.33 | 03-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 584.41 | 28-AUG-15:00 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.59 | 02-AUG-15:30 | 1687.49 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 584.14 | 21-SEP-15:00 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.19 | 10-SEP-14:46 | 1346.88 | 21-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 955.97 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 11-OCT-14:00 | 3043.42 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3238.80 | 01-NOV-04:09 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4518.39 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1192.33 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 880.55 | 5275.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1347.77 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 685.25 | 06-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1710.42 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 543.92 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3516.98 | 19-MAR-07:00 |
April | 1295.83 | 03-APR-09:09 | 478.21 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.18 | 15-APR-04:56 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1419.01 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.57 | 25-JUN-18:00 | 896.99 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.03 | 16-JUL-12:00 | 865.68 | 03-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 377.82 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.06 | 02-AUG-15:30 | 1168.76 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 393.96 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.46 | 10-SEP-14:50 | 890.99 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 621.94 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 11-OCT-14:00 | 1985.98 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2172.17 | 01-NOV-04:04 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2985.37 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.68 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 587.03 | 3516.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2469.41 | 13-JAN-05:09 |
February | 2010.79 | 01-FEB-10:09 | 1068.58 | 06-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2956.14 | 05-FEB-22:57 |
March | 2010.79 | 01-MAR-10:09 | 835.46 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6572.31 | 19-MAR-07:00 |
April | 2010.79 | 03-APR-09:09 | 639.37 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4549.86 | 15-APR-04:51 |
May | 2010.79 | 01-MAY-09:09 | 545.86 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2368.09 | 02-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 545.86 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 647.10 | 25-JUN-17:44 | 1462.30 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.29 | 16-JUL-12:00 | 1450.05 | 03-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 588.51 | 28-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.51 | 02-AUG-15:15 | 1865.38 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 595.20 | 21-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.47 | 10-SEP-14:33 | 1549.95 | 21-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 965.23 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 | 11-OCT-14:00 | 3358.31 | 29-OCT-19:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 05-NOV-13:11 | 3852.14 | 01-NOV-04:10 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 02-DEC-15:00 | 5461.60 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.05 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.29 | 6572.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1646.35 | 13-JAN-05:05 |
February | 1295.83 | 01-FEB-10:09 | 688.17 | 06-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1970.88 | 05-FEB-22:53 |
March | 1295.83 | 01-MAR-10:09 | 510.69 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4381.47 | 19-MAR-07:00 |
April | 1295.83 | 03-APR-09:09 | 404.62 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3036.61 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1605.08 | 02-MAY-04:55 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 471.80 | 25-JUN-17:44 | 986.33 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 720.19 | 16-JUL-12:00 | 1169.92 | 02-JUL-08:50 |
August | 1295.83 | 01-AUG-09:09 | 384.10 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.01 | 02-AUG-15:15 | 1313.71 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 389.11 | 21-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.65 | 10-SEP-14:33 | 1042.53 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 609.29 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2239.04 | 29-OCT-19:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2693.61 | 01-NOV-04:10 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3641.01 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.33 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 720.19 | 4381.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2469.52 | 13-JAN-05:06 |
February | 2010.83 | 01-FEB-10:09 | 1066.82 | 06-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3141.50 | 19-FEB-16:55 |
March | 2010.83 | 01-MAR-10:09 | 825.31 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6572.98 | 19-MAR-07:00 |
April | 2010.83 | 03-APR-09:09 | 638.40 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4559.26 | 15-APR-04:51 |
May | 2010.83 | 01-MAY-09:09 | 545.88 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2368.04 | 02-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 545.88 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 699.50 | 25-JUN-17:44 | 1459.78 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 545.88 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.29 | 16-JUL-12:00 | 1459.70 | 03-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 584.15 | 28-AUG-15:00 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.51 | 02-AUG-15:20 | 2127.12 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 583.88 | 21-SEP-15:00 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.32 | 10-SEP-14:54 | 1578.31 | 21-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 955.58 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.46 | 11-OCT-14:00 | 3358.62 | 29-OCT-19:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4040.41 | 01-NOV-04:09 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5461.80 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.70 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.29 | 6572.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1647.55 | 13-JAN-05:04 |
February | 1295.83 | 01-FEB-10:09 | 685.14 | 06-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1996.87 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 543.51 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4381.85 | 19-MAR-07:00 |
April | 1295.83 | 03-APR-09:09 | 477.68 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3042.39 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 351.77 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1624.62 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.57 | 25-JUN-18:00 | 1088.78 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 720.19 | 16-JUL-12:00 | 1053.82 | 03-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 377.68 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.01 | 02-AUG-15:15 | 1465.27 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 393.85 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.88 | 10-SEP-15:00 | 1046.83 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 621.69 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2239.05 | 29-OCT-19:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2693.64 | 01-NOV-04:09 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3641.05 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.83 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 720.19 | 4381.85 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2124.82 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2607.73 | 05-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5433.08 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3638.21 | 16-APR-15:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.38 | 17-MAY-14:40 | 2118.08 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.93 | 25-JUN-18:00 | 1136.71 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.74 | 16-JUL-12:00 | 1121.95 | 03-JUL-03:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.48 | 06-AUG-12:00 | 1327.62 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.32 | 10-SEP-15:00 | 1333.58 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 | 11-OCT-14:00 | 3172.64 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3139.40 | 01-NOV-03:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4424.76 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.95 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.74 | 5433.08 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3684.56 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4331.92 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9252.67 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6240.93 | 15-APR-04:59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.21 | 17-MAY-14:40 | 3637.48 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 930.78 | 25-JUN-18:00 | 1998.86 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.15 | 16-JUL-12:00 | 1950.36 | 03-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.71 | 06-AUG-12:00 | 2241.26 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.33 | 10-SEP-15:00 | 2370.15 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.29 | 11-OCT-14:00 | 5380.16 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5220.16 | 01-NOV-03:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7620.42 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1950.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.15 | 9252.67 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3541.11 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4488.59 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9299.36 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6391.06 | 15-APR-04:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.95 | 17-MAY-13:00 | 3594.86 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.29 | 25-JUN-18:00 | 2185.86 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.27 | 16-JUL-12:00 | 2163.73 | 03-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.14 | 02-AUG-15:30 | 2963.29 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.83 | 10-SEP-15:00 | 2414.05 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.55 | 11-OCT-14:00 | 5276.45 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5185.81 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8227.27 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2163.73 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.27 | 9299.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 97490.82 | 01-JAN-14:00 | 7180.90 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96822.54 | 21-FEB-04:01 | 0.00 | 5086.92 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94109.82 | 13-MAR-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96153.75 | 10-APR-04:11 | 0.00 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95635.60 | 01-MAY-04:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95799.35 | 05-JUN-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 91481.47 | 05-JUL-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90920.52 | 19-AUG-04:12 | 0.00 | 3391.28 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94097.52 | 18-SEP-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96628.73 | 23-OCT-03:01 | 0.00 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98404.58 | 13-NOV-04:01 | 0.00 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94109.08 | 11-DEC-04:01 | 0.00 | 5652.14 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90920.52 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98404.58 | 7180.90 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79072.03 | 02-JAN-05:01 | 0.00 | 10152.03 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80020.93 | 21-FEB-04:01 | 0.00 | 4568.41 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80825.76 | 13-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82874.23 | 10-APR-04:11 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81658.30 | 30-MAY-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85696.74 | 12-JUN-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81644.00 | 07-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82747.08 | 22-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87723.31 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85520.93 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81545.89 | 13-NOV-04:01 | 0.00 | 4060.81 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82635.28 | 18-DEC-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79072.03 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87723.31 | 0.00 | 10152.03 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 64686.84 | 21-JAN-06:02 | 9673.43 | 6091.22 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54278.06 | 28-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70431.63 | 16-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67958.30 | 21-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71334.28 | 31-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72762.16 | 19-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 75580.94 | 24-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76038.50 | 28-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75517.92 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70559.24 | 02-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67419.88 | 09-NOV-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25917.42 | 15-DEC-16:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 25917.42 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76038.50 | 15316.26 | 9137.09 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26305.75 | 20-JAN-16:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20907.43 | 23-FEB-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50587.38 | 15-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43876.21 | 21-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66627.05 | 11-MAY-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75062.68 | 19-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79870.59 | 24-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75111.10 | 28-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75248.27 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37953.98 | 11-OCT-15:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29026.06 | 08-NOV-15:50 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18112.94 | 14-DEC-15:40 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18112.94 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79870.59 | 15316.26 | 9137.09 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3480.86 | 23-JAN-13:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 |
February | 4126.83 | 27-FEB-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.36 |
March | 6629.27 | 14-MAR-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
April | 7373.46 | 20-APR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
May | 8760.69 | 17-MAY-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
June | 16355.65 | 25-JUN-18:12 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 177.62 | 0.00 |
July | 15861.23 | 02-JUL-18:21 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 |
August | 13426.07 | 20-AUG-15:41 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 | 0.00 |
September | 14449.13 | 03-SEP-15:12 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 |
October | 7106.13 | 10-OCT-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 0.00 |
November | 5476.49 | 09-NOV-13:20 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 |
December | 4669.01 | 04-DEC-12:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3480.86 | 0.00 | 181.95 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16355.65 | 2010.79 | 545.86 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 177.62 | 149.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8624.86 | 20-JAN-09:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
February | 16152.59 | 26-FEB-10:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.60 |
March | 19830.85 | 12-MAR-08:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.61 |
April | 16571.56 | 09-APR-08:62 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.05 |
May | 21443.58 | 28-MAY-09:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.19 |
June | 24329.04 | 11-JUN-07:51 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.32 |
July | 24533.47 | 02-JUL-07:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.62 |
August | 22929.76 | 06-AUG-08:32 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 |
September | 22226.04 | 04-SEP-08:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.36 |
October | 18705.38 | 09-OCT-11:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 |
November | 15783.29 | 05-NOV-08:23 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.23 |
December | 7439.87 | 17-DEC-09:43 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7439.87 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 | |
Maximum of Months | 24533.47 | 1239.33 | 351.77 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25400.53 | 22-JAN-12:41 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.54 |
February | 26112.47 | 26-FEB-12:51 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.40 |
March | 27347.23 | 12-MAR-12:31 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.13 |
April | 22717.99 | 09-APR-12:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 909.68 |
May | 12808.16 | 16-MAY-13:10 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 22.71 | 0.00 |
June | 23732.39 | 25-JUN-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 71.00 | 0.00 |
July | 23374.01 | 30-JUL-12:43 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 | 0.00 |
August | 23662.00 | 20-AUG-13:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 0.00 |
September | 24926.05 | 10-SEP-12:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 | 0.00 |
October | 28373.89 | 09-OCT-13:11 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.31 |
November | 26938.17 | 19-NOV-10:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.53 |
December | 25729.71 | 17-DEC-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12808.16 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28373.89 | 4021.67 | 1091.75 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 | 909.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19056.10 | 22-JAN-16:02 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.47 |
February | 28542.47 | 26-FEB-15:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.81 |
March | 29703.44 | 12-MAR-14:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.31 |
April | 26013.63 | 08-APR-17:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.89 |
May | 27446.91 | 28-MAY-17:12 | 0.00 | 117.25 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.81 |
June | 33248.08 | 11-JUN-15:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 |
July | 33292.50 | 02-JUL-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.28 |
August | 30545.49 | 13-AUG-16:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.74 |
September | 29078.67 | 10-SEP-16:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 31.78 | 0.00 |
October | 29810.72 | 09-OCT-13:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.47 |
November | 26905.34 | 05-NOV-15:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 |
December | 23283.97 | 03-DEC-15:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19056.10 | 0.00 | 97.71 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33292.50 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 31.78 | 333.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2152.60 | 20-JAN-15:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.94 |
February | 2128.66 | 27-FEB-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.07 |
March | 4952.11 | 14-MAR-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 |
April | 5371.31 | 20-APR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 |
May | 8324.26 | 17-MAY-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 | 0.00 |
June | 15862.94 | 25-JUN-18:12 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 388.76 | 0.00 |
July | 15335.41 | 16-JUL-11:31 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 632.31 | 0.00 |
August | 12844.60 | 20-AUG-15:31 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 0.00 |
September | 14567.11 | 10-SEP-15:01 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 285.72 | 0.00 |
October | 5400.61 | 11-OCT-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 0.00 |
November | 3506.17 | 09-NOV-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 |
December | 2067.05 | 04-DEC-14:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2067.05 | 0.00 | 212.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15862.94 | 3846.22 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 632.31 | 334.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7045.79 | 20-JAN-09:40 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 |
February | 9355.75 | 27-FEB-09:10 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.68 |
March | 17840.27 | 12-MAR-08:52 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.33 |
April | 14146.90 | 21-APR-08:40 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.34 |
May | 17457.62 | 28-MAY-09:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.09 |
June | 26321.78 | 11-JUN-08:61 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.32 |
July | 27097.00 | 09-JUL-09:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.66 |
August | 28333.69 | 06-AUG-08:51 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.82 |
September | 23887.91 | 17-SEP-08:51 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.13 |
October | 16947.38 | 01-OCT-09:12 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.72 |
November | 9138.38 | 05-NOV-09:23 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.44 |
December | 3913.37 | 14-DEC-09:25 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3913.37 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.66 | |
Maximum of Months | 28333.69 | 2478.65 | 703.55 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25449.22 | 22-JAN-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1589.09 |
February | 26333.98 | 26-FEB-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.72 |
March | 25262.75 | 12-MAR-12:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.33 |
April | 16428.58 | 12-APR-13:05 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 |
May | 13947.16 | 28-MAY-14:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.15 |
June | 23649.45 | 25-JUN-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 158.93 | 0.00 |
July | 24105.28 | 30-JUL-11:42 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 |
August | 24981.32 | 20-AUG-10:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 12.78 | 0.00 |
September | 27152.20 | 17-SEP-12:11 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.88 |
October | 29469.60 | 08-OCT-12:51 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.62 |
November | 30118.75 | 05-NOV-13:21 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.91 |
December | 27826.67 | 03-DEC-12:11 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1134.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13947.16 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30118.75 | 4021.67 | 1091.75 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 158.93 | 1589.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9755.26 | 20-JAN-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 |
February | 10847.63 | 26-FEB-15:42 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.35 |
March | 25601.64 | 12-MAR-16:12 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.47 |
April | 24475.28 | 08-APR-17:03 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.83 |
May | 17391.04 | 07-MAY-15:42 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.23 |
June | 31173.36 | 25-JUN-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 71.37 | 0.00 |
July | 28178.17 | 01-JUL-17:41 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 |
August | 29017.15 | 20-AUG-15:32 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
September | 30753.42 | 10-SEP-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 0.00 |
October | 28847.21 | 08-OCT-16:11 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.19 |
November | 22796.53 | 05-NOV-15:21 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.11 |
December | 16955.57 | 03-DEC-15:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9755.26 | 326.14 | 97.71 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31173.36 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 71.37 | 533.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2130.40 | 20-JAN-15:50 | 1923.11 | 702.97 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 |
February | 1988.60 | 27-FEB-14:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.31 |
March | 5075.68 | 14-MAR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
April | 5982.92 | 20-APR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 |
May | 8792.32 | 17-MAY-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 97.03 | 0.00 |
June | 17389.12 | 04-JUN-16:51 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 149.69 | 0.00 |
July | 18265.51 | 23-JUL-14:43 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 557.38 | 0.00 |
August | 16949.74 | 06-AUG-13:01 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 164.45 | 0.00 |
September | 17340.36 | 10-SEP-15:11 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 288.81 | 0.00 |
October | 5626.50 | 11-OCT-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
November | 2919.63 | 09-NOV-13:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 |
December | 1948.39 | 01-DEC-15:00 | 2010.79 | 579.99 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1948.39 | 708.51 | 212.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18265.51 | 2010.79 | 702.97 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 557.38 | 412.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5350.63 | 20-JAN-09:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 |
February | 6640.58 | 27-FEB-09:20 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.91 |
March | 15689.70 | 12-MAR-09:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 972.40 |
April | 13612.85 | 21-APR-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.69 |
May | 16661.42 | 28-MAY-09:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.52 |
June | 23997.38 | 11-JUN-08:52 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.54 |
July | 26430.81 | 09-JUL-08:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.59 |
August | 27715.51 | 06-AUG-08:21 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.91 |
September | 23825.39 | 04-SEP-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.69 |
October | 14682.00 | 09-OCT-08:42 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.58 |
November | 6791.22 | 07-NOV-09:10 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.08 |
December | 2197.20 | 14-DEC-09:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2197.20 | 326.14 | 97.71 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.69 | |
Maximum of Months | 27715.51 | 1239.33 | 351.77 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 972.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28362.83 | 22-JAN-13:51 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1727.65 |
February | 27687.73 | 26-FEB-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961.08 |
March | 29737.15 | 12-MAR-12:41 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1654.76 |
April | 16893.09 | 21-APR-13:05 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.92 |
May | 13550.94 | 16-MAY-13:20 | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 0.00 |
June | 25161.73 | 04-JUN-15:31 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 209.15 | 0.00 |
July | 26815.37 | 30-JUL-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 |
August | 27625.05 | 06-AUG-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 70.78 | 0.00 |
September | 29451.17 | 17-SEP-12:11 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.93 |
October | 31782.83 | 09-OCT-13:21 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.29 |
November | 32047.33 | 05-NOV-13:31 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.81 |
December | 28745.14 | 03-DEC-12:11 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13550.94 | 607.31 | 181.95 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32047.33 | 4021.67 | 1091.75 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 209.15 | 1727.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9671.14 | 20-JAN-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
February | 10438.58 | 17-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 |
March | 29609.84 | 12-MAR-16:41 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.93 |
April | 25846.97 | 08-APR-17:03 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.11 |
May | 27311.87 | 28-MAY-16:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.59 |
June | 32495.43 | 04-JUN-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 |
July | 33019.05 | 02-JUL-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.57 |
August | 29632.64 | 13-AUG-17:11 | 0.00 | 156.34 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.30 |
September | 33099.00 | 10-SEP-16:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 0.00 |
October | 30677.59 | 09-OCT-16:01 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.16 |
November | 22869.63 | 05-NOV-15:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.69 |
December | 7756.50 | 01-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7756.50 | 0.00 | 117.25 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33099.00 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 662.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7268.54 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.22 |
February | 4610.29 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.54 |
March | 6260.42 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 |
April | 5150.47 | 21-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.57 |
May | 6045.02 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.71 |
June | 11528.08 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.54 |
July | 10736.86 | 17-JUL-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.13 |
August | 11686.94 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.46 |
September | 12232.46 | 05-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.67 |
October | 9596.20 | 10-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.50 |
November | 5179.88 | 07-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.76 |
December | 7118.50 | 21-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1948.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4610.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | |
Maximum of Months | 12232.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1948.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11255.80 | 05-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 895.15 |
February | 9714.35 | 13-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2733.89 |
March | 12640.39 | 19-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8963.79 |
April | 10789.76 | 17-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2772.34 |
May | 4977.52 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2162.20 |
June | 8916.63 | 26-JUN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 0.00 |
July | 8257.31 | 17-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.35 | 0.00 |
August | 7721.94 | 21-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.13 |
September | 6771.10 | 05-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 |
October | 12724.61 | 30-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2145.38 |
November | 11446.62 | 30-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2909.59 |
December | 14107.06 | 20-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4252.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4977.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14107.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.35 | 8963.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4259.33 | 20-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.39 |
February | 4752.40 | 18-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.71 |
March | 11576.09 | 14-MAR-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.88 |
April | 12056.37 | 21-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.73 |
May | 15883.30 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.12 | 0.00 |
June | 25455.10 | 26-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.72 | 0.00 |
July | 19341.63 | 12-JUL-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.07 | 0.00 |
August | 20699.62 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 | 0.00 |
September | 20537.00 | 12-SEP-13:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 0.00 |
October | 10803.70 | 11-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
November | 6767.36 | 09-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 |
December | 2494.50 | 17-DEC-15:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2494.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25455.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.72 | 319.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2407.26 | 23-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4384.45 | 21-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7117.34 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8338.54 | 08-APR-18:00 | 11.69 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3443.27 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5359.76 | 30-JUN-23:55 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7236.60 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8487.04 | 05-AUG-18:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3305.50 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4976.98 | 09-OCT-16:42 | 93.53 | 65.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6503.65 | 05-NOV-16:13 | 81.84 | 56.91 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8219.79 | 03-DEC-16:00 | 11.69 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2407.26 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8487.04 | 222.14 | 146.32 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2220.48 | 23-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4101.68 | 23-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6605.71 | 31-MAR-23:30 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7905.79 | 08-APR-18:00 | 11.69 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3238.25 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5198.24 | 30-JUN-23:55 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6830.27 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8112.18 | 05-AUG-18:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2973.53 | 30-SEP-23:50 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4485.75 | 08-OCT-16:42 | 93.53 | 65.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5912.40 | 07-NOV-16:20 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7395.20 | 14-DEC-16:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2220.48 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8112.18 | 222.14 | 146.32 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2197.54 | 20-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4058.28 | 17-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6417.66 | 31-MAR-23:20 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7963.26 | 08-APR-18:00 | 11.69 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3169.81 | 31-MAY-23:40 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5189.06 | 30-JUN-23:55 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6733.78 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8233.37 | 13-AUG-19:00 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3123.16 | 10-SEP-17:32 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4490.38 | 08-OCT-16:42 | 93.53 | 65.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5923.92 | 07-NOV-16:20 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7333.45 | 14-DEC-16:00 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2197.54 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8233.37 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90962.49 | 24-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182540.21 | 27-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358419.07 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366125.63 | 10-APR-16:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175430.59 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267554.22 | 30-JUN-23:55 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358662.96 | 31-JUL-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 382756.13 | 16-AUG-21:12 | 1012.35 | 1274.93 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175966.69 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265714.77 | 31-OCT-23:55 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275743.93 | 06-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367170.71 | 04-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90962.49 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 382756.13 | 4808.68 | 2868.67 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.145729E+13 | 995386.87 | 23-JAN-16:10 | 0.341779E+12 | 1205679.32 | 05-JAN-07:10 |
February | 0.169259E+13 | 1069868.23 | 17-FEB-16:40 | 0.360965E+12 | 1234738.22 | 06-FEB-07:10 |
March | 0.227420E+13 | 1448555.59 | 14-MAR-15:30 | 0.261452E+12 | 740893.34 | 20-MAR-06:19 |
April | 0.248747E+13 | 1514164.27 | 07-APR-15:20 | 0.181653E+12 | 859974.36 | 03-APR-06:10 |
May | 0.156849E+13 | 1209437.96 | 16-MAY-15:09 | 0.778291E+11 | 364966.11 | 01-MAY-05:10 |
June | 0.212868E+13 | 1454009.62 | 26-JUN-15:20 | 0.637429E+11 | 80068.48 | 02-JUN-11:50 |
July | 0.260112E+13 | 1626318.22 | 18-JUL-15:09 | 0.603741E+11 | 77847.83 | 05-JUL-11:20 |
August | 0.308636E+13 | 1854599.31 | 02-AUG-15:39 | 0.634360E+11 | 76877.62 | 31-AUG-11:50 |
September | 0.165463E+13 | 1217548.77 | 12-SEP-15:00 | 0.662577E+11 | 352419.68 | 22-SEP-06:10 |
October | 0.191597E+13 | 1320745.15 | 11-OCT-15:09 | 0.201900E+12 | 990818.67 | 30-OCT-06:10 |
November | 0.216940E+13 | 1385137.31 | 07-NOV-15:30 | 0.282224E+12 | 986526.87 | 30-NOV-07:10 |
December | 0.254372E+13 | 1410591.76 | 01-DEC-13:00 | 0.515202E+12 | 1555332.63 | 23-DEC-07:10 |
Annual Sum or Average | 0.255799E+14 | 0.247681E+13 | ||||
Minimum of Months | 0.145729E+13 | 995386.87 | 0.603741E+11 | 76877.62 | ||
Maximum of Months | 0.308636E+13 | 1854599.31 | 0.515202E+12 | 1555332.63 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.253975E+11 | 56740.98 | 31-JAN-12:30 | 0.00 | 0.00 |
February | 0.320773E+11 | 67618.62 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.432585E+11 | 85590.75 | 28-MAR-12:09 | 0.00 | 0.00 |
April | 0.454083E+11 | 89487.60 | 26-APR-12:30 | 0.00 | 0.00 |
May | 0.575251E+11 | 82245.53 | 27-MAY-11:30 | 0.00 | 0.00 |
June | 0.660107E+11 | 86348.72 | 16-JUN-11:00 | 0.00 | 0.00 |
July | 0.598008E+11 | 87524.71 | 01-JUL-11:50 | 0.00 | 0.00 |
August | 0.588925E+11 | 80203.22 | 04-AUG-11:50 | 0.00 | 0.00 |
September | 0.463988E+11 | 73825.64 | 05-SEP-11:00 | 0.00 | 0.00 |
October | 0.360840E+11 | 70841.98 | 01-OCT-11:30 | 0.00 | 0.00 |
November | 0.268788E+11 | 60660.51 | 01-NOV-11:30 | 0.00 | 0.00 |
December | 0.218666E+11 | 47005.55 | 22-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.519599E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.218666E+11 | 47005.55 | 0.00 | 0.00 | |
Maximum of Months | 0.660107E+11 | 89487.60 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.145627E+12 | 0.306100E+11 | 0.766053E+12 | 0.102195E+12 | 0.191723E+12 | 0.197966E+11 | 0.00 | 0.248390E+11 | 0.404963E+10 | 0.172400E+12 | 0.00 | 0.00 | 0.00 |
February | 0.130811E+12 | 0.245742E+11 | 0.978954E+12 | 0.923111E+11 | 0.175070E+12 | 0.186922E+11 | 0.00 | 0.351987E+11 | 0.461661E+10 | 0.232363E+12 | 0.00 | 0.00 | 0.00 |
March | 0.153827E+12 | 0.229051E+11 | 0.141687E+13 | 0.102362E+12 | 0.206343E+12 | 0.217520E+11 | 0.00 | 0.694325E+11 | 0.163736E+11 | 0.264333E+12 | 0.00 | 0.00 | 0.00 |
April | 0.136756E+12 | 0.181540E+11 | 0.165903E+13 | 0.988819E+11 | 0.195675E+12 | 0.195261E+11 | 0.00 | 0.880402E+11 | 0.236681E+11 | 0.247745E+12 | 0.00 | 0.00 | 0.00 |
May | 0.146895E+12 | 0.160188E+11 | 0.774844E+12 | 0.102278E+12 | 0.228313E+12 | 0.278927E+11 | 0.00 | 0.742055E+11 | 0.374505E+11 | 0.160598E+12 | 0.00 | 0.00 | 0.00 |
June | 0.145894E+12 | 0.144100E+11 | 0.106252E+13 | 0.990390E+11 | 0.286417E+12 | 0.491470E+11 | 0.00 | 0.281605E+12 | 0.922996E+11 | 0.973466E+11 | 0.00 | 0.00 | 0.00 |
July | 0.136769E+12 | 0.151931E+11 | 0.139340E+13 | 0.102120E+12 | 0.283639E+12 | 0.529004E+11 | 0.00 | 0.392692E+12 | 0.114477E+12 | 0.109923E+12 | 0.00 | 0.00 | 0.00 |
August | 0.152700E+12 | 0.173567E+11 | 0.173200E+13 | 0.102362E+12 | 0.286544E+12 | 0.545913E+11 | 0.00 | 0.459723E+12 | 0.116649E+12 | 0.164432E+12 | 0.00 | 0.00 | 0.00 |
September | 0.136998E+12 | 0.203095E+11 | 0.740713E+12 | 0.988811E+11 | 0.241933E+12 | 0.387444E+11 | 0.00 | 0.150106E+12 | 0.675962E+11 | 0.159347E+12 | 0.00 | 0.00 | 0.00 |
October | 0.143588E+12 | 0.254244E+11 | 0.108340E+13 | 0.102194E+12 | 0.205840E+12 | 0.235452E+11 | 0.00 | 0.708523E+11 | 0.191761E+11 | 0.241945E+12 | 0.00 | 0.00 | 0.00 |
November | 0.143776E+12 | 0.284799E+11 | 0.135889E+13 | 0.989461E+11 | 0.189772E+12 | 0.209366E+11 | 0.00 | 0.618003E+11 | 0.113737E+11 | 0.255421E+12 | 0.00 | 0.00 | 0.00 |
December | 0.141440E+12 | 0.316919E+11 | 0.170972E+13 | 0.102121E+12 | 0.190662E+12 | 0.191023E+11 | 0.00 | 0.691161E+11 | 0.120247E+11 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171508E+13 | 0.265128E+12 | 0.146764E+14 | 0.120369E+13 | 0.268193E+13 | 0.366627E+12 | 0.00 | 0.177761E+13 | 0.519755E+12 | 0.237369E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130811E+12 | 0.144100E+11 | 0.740713E+12 | 0.923111E+11 | 0.175070E+12 | 0.186922E+11 | 0.00 | 0.248390E+11 | 0.404963E+10 | 0.973466E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153827E+12 | 0.316919E+11 | 0.173200E+13 | 0.102362E+12 | 0.286544E+12 | 0.545913E+11 | 0.00 | 0.459723E+12 | 0.116649E+12 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.271053E+12 | 0.00 | 0.707257E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.296245E+12 | 0.00 | 0.647200E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187422E+12 | 0.00 | 0.740306E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.115154E+12 | 0.00 | 0.664992E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.102561E+11 | 0.00 | 0.675730E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2017254.84 | 0.00 | 0.637409E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.603741E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.634360E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.670100E+10 | 0.00 | 0.595567E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.138422E+12 | 0.00 | 0.634776E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.217603E+12 | 0.00 | 0.646216E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.447561E+12 | 0.00 | 0.676411E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169042E+13 | 0.00 | 0.786396E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.595567E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.447561E+12 | 0.00 | 0.740306E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 169722.15 | 02-JAN-16:49 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73694.97 | 31-JAN-08:20 | 140574.93 | 20-JAN-16:49 | 20000.21 | 20-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 166558.59 | 06-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73695.12 | 08-FEB-08:20 | 140871.37 | 23-FEB-16:30 | 20426.87 | 06-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 157063.97 | 21-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73693.99 | 21-MAR-07:19 | 188829.26 | 10-MAR-16:19 | 36851.16 | 13-MAR-14:20 | 0.00 | 01-MAR-00:10 |
April | 150391.18 | 03-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73690.50 | 03-APR-07:19 | 184506.50 | 07-APR-15:20 | 19749.54 | 19-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 145987.23 | 01-MAY-07:10 | 22480.63 | 01-MAY-18:49 | 423497.50 | 01-MAY-07:10 | 73688.19 | 01-MAY-07:19 | 219437.42 | 18-MAY-14:30 | 38730.36 | 31-MAY-14:30 | 0.00 | 01-MAY-00:10 |
June | 146008.38 | 16-JUN-07:10 | 22480.63 | 01-JUN-19:19 | 541788.89 | 01-JUN-07:10 | 73688.20 | 16-JUN-07:19 | 325428.97 | 20-JUN-11:00 | 44031.50 | 26-JUN-12:39 | 0.00 | 01-JUN-00:10 |
July | 145987.23 | 03-JUL-07:10 | 22480.63 | 01-JUL-19:30 | 660080.29 | 03-JUL-07:10 | 73688.19 | 03-JUL-07:19 | 325428.97 | 18-JUL-10:20 | 44026.19 | 18-JUL-10:00 | 0.00 | 01-JUL-00:10 |
August | 147370.12 | 28-AUG-15:00 | 31088.59 | 10-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73688.35 | 21-AUG-07:19 | 325428.97 | 02-AUG-15:39 | 43915.88 | 02-AUG-15:39 | 0.00 | 01-AUG-00:10 |
September | 147506.26 | 21-SEP-15:00 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73688.66 | 22-SEP-07:19 | 268200.44 | 05-SEP-15:50 | 43014.02 | 05-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 162289.10 | 30-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73696.74 | 30-OCT-07:19 | 184995.26 | 20-OCT-15:50 | 37229.12 | 11-OCT-10:20 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 06-NOV-16:49 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73695.33 | 01-NOV-07:19 | 162482.13 | 08-NOV-15:50 | 36780.58 | 07-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:30 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73696.92 | 21-DEC-08:20 | 129813.77 | 04-DEC-15:39 | 19770.41 | 19-DEC-15:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 145987.23 | 22480.63 | 423497.50 | 73688.19 | 129813.77 | 19749.54 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 73696.92 | 325428.97 | 44031.50 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 107119.28 | 20-JAN-14:00 | 44212.05 | 20-JAN-15:39 | 100000.00 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 89704.83 | 18-FEB-13:00 | 43998.13 | 18-FEB-14:30 | 100000.00 | 01-FEB-10:00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 249603.25 | 14-MAR-14:39 | 45749.86 | 14-MAR-12:39 | 100000.00 | 01-MAR-05:19 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 210741.72 | 19-APR-13:30 | 44465.33 | 20-APR-12:00 | 100000.00 | 01-APR-04:10 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 223275.86 | 31-MAY-13:30 | 57838.50 | 31-MAY-16:19 | 100000.00 | 01-MAY-21:10 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 343183.24 | 26-JUN-14:00 | 71900.76 | 15-JUN-13:39 | 100000.00 | 04-JUN-09:39 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 355879.43 | 17-JUL-10:30 | 71900.76 | 19-JUL-10:09 | 100000.00 | 01-JUL-04:19 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 394287.21 | 16-AUG-15:09 | 71900.76 | 03-AUG-13:20 | 100000.00 | 01-AUG-04:19 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 243578.56 | 12-SEP-15:00 | 57838.50 | 01-SEP-12:09 | 100000.00 | 04-SEP-09:39 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 248037.93 | 11-OCT-14:09 | 46121.81 | 10-OCT-10:50 | 100000.00 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 242163.94 | 07-NOV-15:30 | 45761.27 | 07-NOV-14:39 | 100000.00 | 01-NOV-01:10 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 199117.86 | 01-DEC-13:00 | 44090.45 | 01-DEC-13:00 | 100000.00 | 01-DEC-07:00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 89704.83 | 43998.13 | 100000.00 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 394287.21 | 71900.76 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 995386.87 | 23-JAN-16:10 | 151943.86 | 423497.50 | 0.00 | 52591.59 | 121135.81 | 19578.36 | 0.00 | 82642.64 | 43997.11 |
February | 1069868.23 | 17-FEB-16:40 | 147262.86 | 541788.89 | 0.00 | 52590.08 | 139228.56 | 19386.79 | 0.00 | 64674.64 | 4936.41 |
March | 1448555.59 | 14-MAR-15:30 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 176896.00 | 35785.22 | 0.00 | 233216.01 | 44001.24 |
April | 1514164.27 | 07-APR-15:20 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 184506.50 | 19597.09 | 0.00 | 188956.43 | 44155.73 |
May | 1209437.96 | 16-MAY-15:09 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 206845.23 | 35663.00 | 0.00 | 199233.87 | 45621.54 |
June | 1454009.62 | 26-JUN-15:20 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 259938.84 | 37388.32 | 0.00 | 342926.40 | 71900.76 |
July | 1626318.22 | 18-JUL-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 325428.97 | 43968.30 | 0.00 | 338295.80 | 44915.60 |
August | 1854599.31 | 02-AUG-15:39 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 325428.97 | 43915.88 | 0.00 | 362394.67 | 45911.28 |
September | 1217548.77 | 12-SEP-15:00 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 260586.31 | 37262.20 | 0.00 | 243578.56 | 45031.42 |
October | 1320745.15 | 11-OCT-15:09 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 161455.79 | 36458.88 | 0.00 | 236412.28 | 46052.48 |
November | 1385137.31 | 07-NOV-15:30 | 146711.21 | 660080.29 | 0.00 | 24458.19 | 131085.67 | 36636.78 | 0.00 | 242163.94 | 44001.24 |
December | 1410591.76 | 01-DEC-13:00 | 145987.23 | 778371.69 | 0.00 | 24458.17 | 98856.95 | 19709.41 | 0.00 | 199117.86 | 44090.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 995386.87 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 98856.95 | 19386.79 | 0.00 | 64674.64 | 4936.41 | |
Maximum of Months | 1854599.31 | 151943.86 | 778371.69 | 0.00 | 52591.59 | 325428.97 | 43968.30 | 0.00 | 362394.67 | 71900.76 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1174700.52 | 05-JAN-07:10 | 0.00 | 85023.36 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 1203361.59 | 06-FEB-07:10 | 0.00 | 85112.84 | 08-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 709257.02 | 20-MAR-06:19 | 0.00 | 84977.23 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 828796.24 | 03-APR-06:10 | 0.00 | 83943.38 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 336534.40 | 01-MAY-05:10 | 0.00 | 82358.95 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 2243.17 | 09-JUN-06:10 | 0.00 | 80068.48 | 02-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 77847.83 | 05-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 76877.62 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 322080.62 | 22-SEP-06:10 | 0.00 | 78161.26 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 960190.53 | 30-OCT-06:10 | 0.00 | 80256.89 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 961756.97 | 30-NOV-07:10 | 0.00 | 82394.39 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 1525895.19 | 23-DEC-07:10 | 0.00 | 84057.37 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76877.62 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1525895.19 | 0.00 | 85112.84 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.83 | 0.83 | 26.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.64 | 0.00 | 26.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.78 | 0.00 | 25.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.82 | 0.00 | 25.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.34 | 0.00 | 26.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.79 | 0.00 | 26.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.93 | 0.00 | 26.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.85 | 0.00 | 26.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.95 | 0.33 | 26.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.72 | 0.33 | 26.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.61 | 0.33 | 26.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.28 | 0.00 | 26.28 |
Annual Sum or Average | 0.00 | 0.00 | 45.00 | 26.68 | 1.83 | 26.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.78 | 0.00 | 25.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.95 | 0.83 | 26.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.75 | 0.83 | 24.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.38 | 0.33 | 25.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.77 | 0.00 | 25.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.68 | 0.00 | 25.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 25.38 | 1.17 | 25.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.77 | 0.83 | 25.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.62 | 0.17 | 24.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.62 | 0.17 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.62 | 0.17 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
February | 1.83 | 18.68 | 0.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
March | 0.83 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
April | 0.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.69 | 1.00 | 24.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
November | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
December | 2.83 | 18.81 | 0.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 8.00 | 18.79 | 1.00 | 18.94 | 1.00 | 19.52 | 1.00 | 19.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.37 | 0.50 | 19.37 | 1.00 | 24.69 | 1.00 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.32 | 6.17 | 26.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.64 | 9.00 | 26.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.13 | 1.33 | 27.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Annual Sum or Average | 0.83 | 18.97 | 0.00 | 18.97 | 19.67 | 26.26 | 17.00 | 26.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 18.97 | 0.00 | 18.97 | 10.33 | 27.31 | 9.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
February | 0.17 | 19.42 | 0.00 | 19.42 | 0.83 | 26.36 | 0.83 | 26.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.35 | 1.83 | 28.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.21 | 1.00 | 28.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.73 | 2.67 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.62 | 12.00 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.93 | 16.83 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.95 | 8.17 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.97 | 7.17 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.04 | 4.00 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 1.50 | 27.64 |
December | 0.83 | 18.64 | 0.00 | 18.64 | 0.33 | 21.11 | 0.33 | 22.48 |
Annual Sum or Average | 1.00 | 18.77 | 0.00 | 18.77 | 58.67 | 27.72 | 56.83 | 27.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.11 | 0.33 | 22.48 |
Maximum of Months | 0.83 | 19.42 | 0.00 | 19.42 | 17.83 | 28.35 | 16.83 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.31 | 0.00 | 19.31 | 21.00 | 25.90 | 21.00 | 25.95 |
February | 0.50 | 19.19 | 0.00 | 19.19 | 14.33 | 25.71 | 14.33 | 25.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.06 | 12.17 | 26.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.66 | 0.83 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.37 | 1.50 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.84 | 9.83 | 26.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.63 | 11.50 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.84 | 11.33 | 26.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 26.92 | 16.17 | 26.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 26.19 | 25.67 | 26.18 |
November | 0.17 | 19.40 | 0.00 | 19.40 | 30.17 | 25.90 | 30.17 | 25.92 |
December | 0.83 | 18.60 | 0.00 | 18.60 | 25.17 | 25.39 | 25.17 | 25.50 |
Annual Sum or Average | 1.83 | 18.96 | 0.00 | 18.96 | 183.17 | 26.21 | 179.67 | 26.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.39 | 0.83 | 25.50 |
Maximum of Months | 0.83 | 19.40 | 0.00 | 19.40 | 30.17 | 27.66 | 30.17 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.62 | 1.50 | 27.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.99 | 3.00 | 27.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.63 | 3.17 | 28.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.03 | 1.33 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.89 | 5.67 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.72 | 10.83 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 27.76 | 17.33 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.51 | 16.33 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.01 | 8.67 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.57 | 4.50 | 28.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.10 | 4.17 | 28.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.11 | 2.83 | 28.11 |
Annual Sum or Average | 0.00 | 0.00 | 145.50 | 27.79 | 79.33 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.51 | 1.33 | 27.58 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 28.63 | 17.33 | 28.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.66 | 0.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
February | 10.33 | 17.66 | 2.00 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
March | 4.67 | 16.99 | 1.50 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
April | 1.83 | 18.48 | 0.17 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.31 | 3.00 | 26.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.14 | 5.17 | 27.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.83 | 18.64 | 0.17 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
November | 3.33 | 18.69 | 0.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 20.00 | 17.55 | 5.67 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
Annual Sum or Average | 45.50 | 17.77 | 10.33 | 17.91 | 9.67 | 19.23 | 8.17 | 20.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.00 | 18.69 | 5.67 | 18.87 | 6.17 | 27.14 | 5.17 | 27.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 12.00 | 18.25 | 0.33 | 18.16 | 0.33 | 18.40 | 0.33 | 18.63 |
March | 5.17 | 17.21 | 1.33 | 16.67 | 1.67 | 19.00 | 1.67 | 20.54 |
April | 2.50 | 18.69 | 0.00 | 18.69 | 0.83 | 20.97 | 0.83 | 22.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.90 | 2.00 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.81 | 11.00 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 28.20 | 16.17 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.27 | 8.17 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.98 | 7.67 | 27.99 |
October | 6.50 | 19.15 | 0.00 | 19.15 | 3.17 | 22.03 | 3.17 | 23.49 |
November | 3.17 | 18.53 | 0.17 | 18.63 | 0.33 | 19.42 | 0.33 | 20.09 |
December | 22.50 | 17.72 | 0.83 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
Annual Sum or Average | 56.33 | 18.14 | 2.67 | 18.00 | 54.67 | 22.83 | 51.33 | 24.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 | 17.61 |
Maximum of Months | 22.50 | 19.15 | 1.33 | 19.15 | 17.67 | 28.27 | 16.17 | 28.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.63 | 0.00 | 18.63 | 43.67 | 25.49 | 43.67 | 25.61 |
February | 4.00 | 17.74 | 0.00 | 17.74 | 39.33 | 24.68 | 39.33 | 25.01 |
March | 3.67 | 16.84 | 1.17 | 16.31 | 20.33 | 23.84 | 20.17 | 24.63 |
April | 1.67 | 18.35 | 0.00 | 18.35 | 0.17 | 19.17 | 0.17 | 19.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.38 | 1.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.09 | 7.83 | 27.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.82 | 9.83 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.72 | 11.33 | 26.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.28 | 15.17 | 27.27 |
October | 1.33 | 18.63 | 0.00 | 18.63 | 46.17 | 25.65 | 45.83 | 25.75 |
November | 2.33 | 18.55 | 0.17 | 18.67 | 46.17 | 25.48 | 46.17 | 25.66 |
December | 6.67 | 17.20 | 0.50 | 17.14 | 29.00 | 23.95 | 29.00 | 24.69 |
Annual Sum or Average | 21.17 | 17.67 | 1.83 | 17.51 | 272.83 | 25.31 | 269.50 | 25.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 19.17 | 0.17 | 19.86 |
Maximum of Months | 6.67 | 18.63 | 1.17 | 18.67 | 46.17 | 27.82 | 46.17 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 18.89 | 0.00 | 18.89 | 0.17 | 19.53 | 0.17 | 20.09 |
February | 3.17 | 18.15 | 0.00 | 18.15 | 0.83 | 20.12 | 0.83 | 21.41 |
March | 2.83 | 17.10 | 1.17 | 16.42 | 2.00 | 20.45 | 1.33 | 21.93 |
April | 1.33 | 18.53 | 0.00 | 18.53 | 0.50 | 21.15 | 0.33 | 22.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.89 | 3.83 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.55 | 6.67 | 28.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.22 | 9.17 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.29 | 4.83 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.44 | 5.67 | 28.52 |
October | 1.17 | 18.56 | 0.00 | 18.56 | 3.67 | 26.06 | 3.33 | 27.06 |
November | 2.17 | 18.44 | 0.00 | 18.44 | 0.67 | 20.70 | 0.67 | 22.10 |
December | 7.33 | 16.86 | 0.67 | 16.68 | 0.33 | 17.11 | 0.33 | 17.51 |
Annual Sum or Average | 20.00 | 17.68 | 1.83 | 17.43 | 55.50 | 25.24 | 37.17 | 26.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 17.11 | 0.17 | 17.51 |
Maximum of Months | 7.33 | 18.89 | 1.17 | 18.89 | 14.50 | 28.55 | 9.17 | 28.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.50 | 16.88 | 7.17 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
February | 35.83 | 16.57 | 11.17 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
March | 22.33 | 16.33 | 6.33 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
April | 19.00 | 16.62 | 6.00 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
May | 0.67 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.89 | 7.00 | 26.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.50 | 7.00 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.37 | 2.00 | 27.37 |
September | 0.17 | 19.12 | 0.00 | 19.12 | 1.83 | 26.69 | 1.67 | 27.00 |
October | 11.33 | 17.39 | 3.50 | 17.66 | 0.00 | 17.66 | 0.00 | 17.66 |
November | 16.50 | 17.92 | 3.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
December | 58.17 | 16.55 | 23.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
Annual Sum or Average | 193.50 | 16.76 | 60.17 | 16.97 | 22.17 | 17.79 | 17.67 | 18.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 | 0.00 | 16.30 |
Maximum of Months | 58.17 | 19.12 | 23.00 | 19.12 | 9.17 | 27.50 | 7.00 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.83 | 16.12 | 1.00 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
February | 22.67 | 15.66 | 3.50 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
March | 17.00 | 15.73 | 3.33 | 15.47 | 0.83 | 15.96 | 0.83 | 16.41 |
April | 14.17 | 15.60 | 3.33 | 15.47 | 0.50 | 15.80 | 0.50 | 16.11 |
May | 0.50 | 18.75 | 0.00 | 18.75 | 1.33 | 25.32 | 1.33 | 26.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.93 | 11.33 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 28.16 | 16.83 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.27 | 8.50 | 28.30 |
September | 0.17 | 19.13 | 0.00 | 19.13 | 8.67 | 27.75 | 8.00 | 27.84 |
October | 7.33 | 16.27 | 0.67 | 16.15 | 1.83 | 18.31 | 1.83 | 19.80 |
November | 9.17 | 16.88 | 0.33 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
December | 30.00 | 15.39 | 3.67 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 117.83 | 15.81 | 15.83 | 15.67 | 54.67 | 19.27 | 49.17 | 21.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 0.00 | 15.34 |
Maximum of Months | 30.00 | 19.13 | 3.67 | 19.13 | 19.33 | 28.27 | 16.83 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 17.55 | 0.50 | 17.50 | 16.00 | 22.91 | 16.00 | 24.06 |
February | 20.00 | 16.15 | 4.00 | 15.98 | 6.17 | 18.06 | 6.17 | 19.43 |
March | 16.67 | 15.88 | 3.50 | 15.59 | 10.33 | 19.10 | 10.17 | 20.81 |
April | 13.50 | 15.83 | 2.83 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
May | 0.67 | 18.92 | 0.00 | 18.92 | 1.00 | 23.98 | 1.00 | 25.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.10 | 9.33 | 27.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.96 | 10.50 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.40 | 8.50 | 27.40 |
September | 0.17 | 19.20 | 0.00 | 19.20 | 17.00 | 27.08 | 15.67 | 27.10 |
October | 5.83 | 16.08 | 0.33 | 16.02 | 22.83 | 24.12 | 22.67 | 25.08 |
November | 7.17 | 17.47 | 0.17 | 17.52 | 19.83 | 23.74 | 19.83 | 24.71 |
December | 25.50 | 16.18 | 3.83 | 16.21 | 7.17 | 18.20 | 7.17 | 19.55 |
Annual Sum or Average | 97.67 | 16.30 | 15.17 | 16.17 | 132.67 | 21.80 | 127.00 | 23.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 0.00 | 15.67 |
Maximum of Months | 25.50 | 19.20 | 4.00 | 19.20 | 22.83 | 27.96 | 22.67 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 17.00 | 1.50 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
February | 18.33 | 16.05 | 4.17 | 15.81 | 0.33 | 15.98 | 0.33 | 16.14 |
March | 12.50 | 16.24 | 2.50 | 15.90 | 1.83 | 17.27 | 1.17 | 18.00 |
April | 6.17 | 16.44 | 0.00 | 16.44 | 0.50 | 17.30 | 0.33 | 17.82 |
May | 0.33 | 18.95 | 0.00 | 18.95 | 4.50 | 27.23 | 3.50 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.56 | 7.00 | 28.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 28.34 | 9.67 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.25 | 5.50 | 28.25 |
September | 0.17 | 19.24 | 0.00 | 19.24 | 9.67 | 28.07 | 6.50 | 28.14 |
October | 5.00 | 16.06 | 0.17 | 16.03 | 3.17 | 20.75 | 2.67 | 22.65 |
November | 6.50 | 17.67 | 0.17 | 17.73 | 0.50 | 18.45 | 0.50 | 19.07 |
December | 23.33 | 15.67 | 3.33 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
Annual Sum or Average | 80.83 | 16.25 | 11.83 | 16.07 | 57.83 | 20.77 | 37.17 | 22.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 | 15.60 |
Maximum of Months | 23.33 | 19.24 | 4.17 | 19.24 | 15.67 | 28.56 | 9.67 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 28.23 | 42.67 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.67 | 28.23 | 42.67 | 28.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 28.23 | 42.67 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 28.18 | 31.33 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.17 | 28.18 | 31.33 | 28.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 28.18 | 31.33 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 28.18 | 26.83 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 30.33 | 28.18 | 26.83 | 28.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 28.18 | 26.83 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.43 | 3.17 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 245.00 | 30.27 | 233.00 | 30.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 248.17 | 30.25 | 236.17 | 30.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 245.00 | 30.27 | 233.00 | 30.33 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.00 | 23.88 | 64.17 | 24.38 | 0.00 | 24.38 |
February | 260.17 | 23.94 | 46.50 | 24.30 | 0.00 | 24.30 |
March | 309.50 | 23.99 | 41.83 | 24.22 | 0.00 | 24.22 |
April | 166.33 | 24.00 | 81.67 | 24.64 | 0.00 | 24.64 |
May | 111.33 | 24.00 | 139.33 | 24.79 | 0.00 | 24.79 |
June | 48.17 | 24.34 | 277.00 | 24.71 | 34.00 | 24.68 |
July | 93.33 | 24.55 | 336.17 | 24.78 | 80.00 | 24.76 |
August | 43.17 | 24.99 | 312.00 | 24.79 | 39.83 | 24.82 |
September | 42.17 | 24.00 | 166.00 | 25.18 | 0.00 | 25.18 |
October | 129.00 | 23.99 | 102.83 | 25.06 | 0.00 | 25.06 |
November | 108.33 | 23.97 | 100.50 | 25.14 | 0.00 | 25.14 |
December | 319.33 | 23.82 | 54.67 | 24.20 | 0.00 | 24.20 |
Annual Sum or Average | 1862.83 | 24.00 | 1722.67 | 24.64 | 153.83 | 24.64 |
Minimum of Months | 42.17 | 23.82 | 41.83 | 24.20 | 0.00 | 24.20 |
Maximum of Months | 319.33 | 24.99 | 336.17 | 25.18 | 80.00 | 25.18 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.00 | 23.99 | 22.00 | 24.11 | 0.00 | 24.11 |
February | 270.50 | 23.99 | 30.17 | 24.16 | 0.00 | 24.16 |
March | 247.83 | 24.00 | 24.33 | 24.12 | 0.00 | 24.12 |
April | 102.33 | 24.00 | 82.83 | 24.72 | 0.00 | 24.72 |
May | 82.50 | 24.00 | 137.67 | 24.52 | 0.00 | 24.52 |
June | 42.00 | 24.34 | 295.50 | 24.41 | 40.50 | 24.41 |
July | 94.33 | 24.37 | 354.67 | 24.42 | 89.17 | 24.41 |
August | 32.50 | 24.20 | 345.33 | 24.33 | 32.00 | 24.32 |
September | 44.50 | 24.00 | 146.83 | 24.68 | 0.00 | 24.68 |
October | 152.50 | 24.00 | 83.00 | 24.55 | 0.00 | 24.55 |
November | 113.50 | 24.00 | 71.17 | 24.62 | 0.00 | 24.62 |
December | 292.00 | 24.01 | 24.33 | 24.15 | 0.00 | 24.15 |
Annual Sum or Average | 1730.50 | 24.03 | 1617.83 | 24.37 | 161.67 | 24.37 |
Minimum of Months | 32.50 | 23.99 | 22.00 | 24.11 | 0.00 | 24.11 |
Maximum of Months | 292.00 | 24.37 | 354.67 | 24.72 | 89.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 464.00 | 23.39 | 0.00 | 23.39 | 0.00 | 23.39 |
February | 420.00 | 23.16 | 6.33 | 23.13 | 6.33 | 23.10 |
March | 482.00 | 23.50 | 3.17 | 23.50 | 0.33 | 23.50 |
April | 378.50 | 23.65 | 8.83 | 23.67 | 0.00 | 23.67 |
May | 177.83 | 23.93 | 69.17 | 24.16 | 0.00 | 24.16 |
June | 66.83 | 24.14 | 240.50 | 24.29 | 41.67 | 24.28 |
July | 109.33 | 24.20 | 272.67 | 24.30 | 91.83 | 24.29 |
August | 51.50 | 24.05 | 269.50 | 24.31 | 36.17 | 24.29 |
September | 119.17 | 23.94 | 93.33 | 24.30 | 0.00 | 24.30 |
October | 335.67 | 23.76 | 5.50 | 23.78 | 0.00 | 23.78 |
November | 411.00 | 23.57 | 1.33 | 23.57 | 0.00 | 23.57 |
December | 497.00 | 22.98 | 38.67 | 22.80 | 38.67 | 22.65 |
Annual Sum or Average | 3512.83 | 23.50 | 1009.00 | 23.67 | 215.00 | 23.66 |
Minimum of Months | 51.50 | 22.98 | 0.00 | 22.80 | 0.00 | 22.65 |
Maximum of Months | 497.00 | 24.20 | 272.67 | 24.31 | 91.83 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.17 | 21.70 | 143.17 | 21.32 | 143.17 | 21.08 |
February | 452.00 | 21.87 | 133.33 | 21.52 | 133.33 | 21.29 |
March | 504.33 | 22.53 | 65.50 | 22.21 | 65.50 | 21.96 |
April | 421.83 | 22.50 | 76.33 | 22.15 | 72.17 | 21.88 |
May | 256.33 | 23.54 | 40.67 | 23.63 | 1.67 | 23.61 |
June | 66.00 | 24.13 | 260.67 | 24.31 | 39.33 | 24.31 |
July | 102.67 | 24.22 | 305.00 | 24.34 | 90.17 | 24.32 |
August | 59.00 | 24.01 | 282.17 | 24.28 | 35.17 | 24.26 |
September | 165.33 | 23.62 | 91.83 | 24.01 | 0.00 | 24.01 |
October | 465.50 | 22.85 | 51.67 | 22.64 | 51.67 | 22.46 |
November | 481.00 | 22.20 | 71.67 | 22.02 | 71.67 | 21.88 |
December | 497.00 | 21.42 | 206.67 | 21.05 | 206.67 | 20.85 |
Annual Sum or Average | 3971.17 | 22.41 | 1728.67 | 22.46 | 910.50 | 22.25 |
Minimum of Months | 59.00 | 21.42 | 40.67 | 21.05 | 0.00 | 20.85 |
Maximum of Months | 504.33 | 24.22 | 305.00 | 24.34 | 206.67 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.31 | 72.50 | 22.12 | 72.50 | 21.97 |
February | 454.00 | 22.27 | 77.50 | 22.02 | 77.50 | 21.84 |
March | 487.00 | 23.01 | 16.17 | 22.91 | 16.17 | 22.82 |
April | 364.17 | 23.25 | 7.67 | 23.26 | 1.67 | 23.24 |
May | 169.83 | 23.74 | 112.83 | 24.12 | 0.00 | 24.12 |
June | 41.33 | 24.83 | 370.83 | 24.50 | 41.00 | 24.53 |
July | 88.67 | 24.78 | 420.17 | 24.59 | 88.67 | 24.62 |
August | 39.50 | 24.69 | 378.67 | 24.39 | 32.50 | 24.42 |
September | 131.33 | 23.75 | 132.00 | 24.28 | 1.00 | 24.29 |
October | 418.00 | 23.14 | 28.67 | 23.13 | 15.33 | 23.06 |
November | 477.50 | 22.89 | 19.00 | 22.82 | 19.00 | 22.75 |
December | 497.00 | 22.31 | 106.50 | 22.01 | 106.50 | 21.80 |
Annual Sum or Average | 3670.33 | 22.89 | 1742.50 | 23.19 | 471.83 | 23.11 |
Minimum of Months | 39.50 | 22.27 | 7.67 | 22.01 | 0.00 | 21.80 |
Maximum of Months | 502.00 | 24.83 | 420.17 | 24.59 | 106.50 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.83 | 22.61 | 57.00 | 22.53 | 42.83 | 22.39 |
February | 347.17 | 22.28 | 102.33 | 22.17 | 72.50 | 21.96 |
March | 369.83 | 22.82 | 85.67 | 22.96 | 27.00 | 22.87 |
April | 285.83 | 22.95 | 75.67 | 23.17 | 11.33 | 23.15 |
May | 114.83 | 23.89 | 208.17 | 24.38 | 6.50 | 24.43 |
June | 64.00 | 25.75 | 420.50 | 24.63 | 63.67 | 24.76 |
July | 121.83 | 25.53 | 445.17 | 24.80 | 121.83 | 24.93 |
August | 59.00 | 25.52 | 409.83 | 24.52 | 51.00 | 24.64 |
September | 100.50 | 24.45 | 237.00 | 24.64 | 22.17 | 24.79 |
October | 326.50 | 23.03 | 98.17 | 23.34 | 30.17 | 23.32 |
November | 374.17 | 22.75 | 54.00 | 22.82 | 24.67 | 22.73 |
December | 451.83 | 22.30 | 105.67 | 22.04 | 100.00 | 21.82 |
Annual Sum or Average | 3050.33 | 22.99 | 2299.17 | 23.47 | 573.67 | 23.45 |
Minimum of Months | 59.00 | 22.28 | 54.00 | 22.04 | 6.50 | 21.82 |
Maximum of Months | 451.83 | 25.75 | 445.17 | 24.80 | 121.83 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 302.17 | 22.85 | 188.33 | 23.31 | 54.33 | 23.28 |
February | 265.50 | 22.39 | 196.83 | 22.77 | 77.50 | 22.58 |
March | 315.00 | 22.70 | 137.00 | 23.00 | 36.83 | 22.90 |
April | 288.83 | 22.71 | 96.17 | 22.83 | 29.00 | 22.68 |
May | 165.50 | 23.53 | 150.17 | 24.05 | 0.67 | 24.06 |
June | 61.50 | 25.17 | 371.83 | 24.56 | 53.17 | 24.65 |
July | 103.00 | 25.16 | 412.00 | 24.68 | 100.33 | 24.76 |
August | 58.17 | 25.50 | 419.83 | 24.56 | 51.00 | 24.67 |
September | 105.17 | 24.67 | 279.50 | 24.70 | 34.17 | 24.89 |
October | 280.17 | 23.19 | 199.17 | 23.63 | 62.00 | 23.66 |
November | 269.83 | 23.19 | 192.17 | 23.74 | 50.17 | 23.81 |
December | 326.83 | 22.60 | 182.00 | 22.86 | 83.83 | 22.70 |
Annual Sum or Average | 2541.67 | 23.14 | 2825.00 | 23.71 | 633.00 | 23.71 |
Minimum of Months | 58.17 | 22.39 | 96.17 | 22.77 | 0.67 | 22.58 |
Maximum of Months | 326.83 | 25.50 | 419.83 | 24.70 | 100.33 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 363.17 | 23.13 | 79.00 | 23.25 | 21.50 | 23.16 |
February | 283.83 | 23.23 | 79.83 | 23.50 | 14.17 | 23.49 |
March | 202.00 | 23.81 | 114.17 | 24.13 | 15.67 | 24.18 |
April | 79.83 | 24.12 | 195.33 | 24.53 | 5.33 | 24.58 |
May | 69.83 | 24.78 | 263.67 | 24.77 | 18.83 | 24.90 |
June | 72.83 | 25.87 | 457.00 | 24.78 | 72.83 | 24.91 |
July | 125.50 | 25.76 | 486.83 | 24.93 | 125.50 | 25.07 |
August | 94.00 | 26.06 | 498.00 | 24.82 | 94.00 | 24.99 |
September | 69.67 | 25.32 | 285.00 | 24.93 | 32.00 | 25.11 |
October | 183.33 | 23.78 | 128.00 | 24.30 | 16.00 | 24.44 |
November | 182.00 | 23.85 | 121.00 | 24.34 | 10.50 | 24.44 |
December | 296.00 | 23.53 | 83.33 | 23.72 | 20.50 | 23.67 |
Annual Sum or Average | 2022.00 | 23.96 | 2791.17 | 24.38 | 446.83 | 24.49 |
Minimum of Months | 69.67 | 23.13 | 79.00 | 23.25 | 5.33 | 23.16 |
Maximum of Months | 363.17 | 26.06 | 498.00 | 24.93 | 125.50 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.87 | 261.67 | 20.62 | 261.67 | 20.50 |
February | 454.00 | 20.78 | 279.67 | 20.57 | 279.67 | 20.48 |
March | 512.33 | 21.63 | 161.50 | 21.27 | 161.50 | 21.04 |
April | 460.50 | 21.87 | 107.67 | 21.52 | 104.83 | 21.26 |
May | 270.67 | 23.26 | 75.17 | 23.47 | 4.67 | 23.44 |
June | 49.00 | 24.35 | 330.67 | 24.39 | 37.17 | 24.40 |
July | 93.83 | 24.47 | 369.33 | 24.49 | 89.00 | 24.49 |
August | 69.67 | 23.84 | 285.33 | 24.24 | 28.50 | 24.24 |
September | 209.83 | 23.33 | 91.50 | 23.73 | 2.00 | 23.71 |
October | 490.83 | 22.13 | 95.00 | 21.84 | 95.00 | 21.63 |
November | 489.00 | 21.29 | 216.67 | 21.06 | 216.67 | 20.93 |
December | 497.00 | 20.46 | 367.17 | 20.30 | 367.17 | 20.23 |
Annual Sum or Average | 4098.67 | 21.68 | 2641.33 | 21.82 | 1647.83 | 21.58 |
Minimum of Months | 49.00 | 20.46 | 75.17 | 20.30 | 2.00 | 20.23 |
Maximum of Months | 512.33 | 24.47 | 369.33 | 24.49 | 367.17 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.83 | 21.65 | 152.33 | 21.32 | 150.67 | 21.13 |
February | 342.33 | 21.44 | 165.17 | 21.11 | 150.67 | 20.85 |
March | 341.83 | 21.92 | 135.83 | 21.73 | 103.00 | 21.46 |
April | 298.33 | 21.89 | 116.50 | 21.76 | 76.50 | 21.49 |
May | 143.33 | 23.48 | 159.50 | 24.12 | 7.83 | 24.17 |
June | 61.50 | 26.00 | 342.83 | 24.79 | 60.17 | 24.95 |
July | 116.50 | 25.67 | 367.83 | 24.97 | 116.00 | 25.10 |
August | 67.33 | 25.35 | 330.67 | 24.68 | 53.00 | 24.81 |
September | 119.33 | 24.11 | 178.50 | 24.56 | 22.83 | 24.73 |
October | 317.00 | 22.29 | 125.00 | 22.38 | 78.33 | 22.17 |
November | 374.50 | 21.86 | 120.17 | 21.64 | 109.83 | 21.45 |
December | 413.67 | 21.06 | 241.50 | 20.68 | 241.50 | 20.51 |
Annual Sum or Average | 3004.50 | 22.20 | 2435.83 | 22.57 | 1170.33 | 22.38 |
Minimum of Months | 61.50 | 21.06 | 116.50 | 20.68 | 7.83 | 20.51 |
Maximum of Months | 413.67 | 26.00 | 367.83 | 24.97 | 241.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 323.00 | 22.60 | 223.83 | 23.01 | 106.17 | 22.94 |
February | 285.17 | 21.93 | 234.33 | 22.27 | 124.00 | 22.02 |
March | 340.33 | 22.06 | 197.83 | 22.25 | 100.67 | 22.01 |
April | 337.50 | 21.80 | 135.00 | 21.75 | 79.00 | 21.46 |
May | 208.83 | 23.16 | 136.00 | 23.68 | 5.17 | 23.65 |
June | 76.50 | 24.69 | 333.17 | 24.48 | 50.33 | 24.56 |
July | 119.67 | 24.80 | 382.67 | 24.60 | 100.00 | 24.67 |
August | 77.33 | 24.95 | 381.33 | 24.52 | 49.83 | 24.64 |
September | 137.17 | 24.36 | 262.67 | 24.57 | 37.50 | 24.77 |
October | 310.67 | 22.78 | 233.00 | 23.19 | 103.67 | 23.12 |
November | 306.50 | 22.77 | 229.00 | 23.26 | 105.67 | 23.22 |
December | 352.17 | 21.87 | 257.50 | 22.00 | 174.83 | 21.78 |
Annual Sum or Average | 2874.83 | 22.66 | 3006.33 | 23.21 | 1036.83 | 23.10 |
Minimum of Months | 76.50 | 21.80 | 135.00 | 21.75 | 5.17 | 21.46 |
Maximum of Months | 352.17 | 24.95 | 382.67 | 24.60 | 174.83 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.17 | 21.64 | 169.33 | 21.42 | 149.83 | 21.21 |
February | 381.67 | 21.43 | 189.50 | 21.24 | 162.17 | 21.01 |
March | 419.00 | 22.10 | 145.67 | 21.97 | 99.67 | 21.72 |
April | 348.17 | 22.07 | 117.17 | 21.97 | 69.83 | 21.71 |
May | 185.33 | 23.56 | 181.00 | 24.06 | 14.83 | 24.14 |
June | 67.33 | 25.33 | 400.17 | 24.63 | 57.33 | 24.74 |
July | 110.33 | 25.19 | 423.17 | 24.71 | 109.67 | 24.80 |
August | 56.67 | 25.18 | 409.50 | 24.57 | 45.33 | 24.65 |
September | 141.33 | 24.05 | 212.17 | 24.44 | 26.67 | 24.60 |
October | 380.00 | 22.49 | 138.50 | 22.55 | 75.17 | 22.39 |
November | 408.33 | 21.95 | 139.00 | 21.87 | 106.00 | 21.69 |
December | 461.33 | 21.17 | 254.83 | 20.87 | 249.83 | 20.69 |
Annual Sum or Average | 3396.67 | 22.24 | 2780.00 | 22.66 | 1166.33 | 22.48 |
Minimum of Months | 56.67 | 21.17 | 117.17 | 20.87 | 14.83 | 20.69 |
Maximum of Months | 461.33 | 25.33 | 423.17 | 24.71 | 249.83 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 373.67 | 20.06 | 373.67 | 19.99 |
February | 454.00 | 20.36 | 352.50 | 20.22 | 352.50 | 20.16 |
March | 514.00 | 21.24 | 250.83 | 20.86 | 250.83 | 20.66 |
April | 456.33 | 21.24 | 186.67 | 20.74 | 183.83 | 20.46 |
May | 298.67 | 22.79 | 83.17 | 22.94 | 19.67 | 22.84 |
June | 69.00 | 24.41 | 329.67 | 24.39 | 39.50 | 24.45 |
July | 116.50 | 24.48 | 368.50 | 24.48 | 94.83 | 24.51 |
August | 97.17 | 23.72 | 289.67 | 24.17 | 34.83 | 24.18 |
September | 236.33 | 23.01 | 106.83 | 23.37 | 16.50 | 23.27 |
October | 497.17 | 21.53 | 186.33 | 21.14 | 186.33 | 20.91 |
November | 489.00 | 20.67 | 322.83 | 20.42 | 322.83 | 20.32 |
December | 497.00 | 20.04 | 441.33 | 19.95 | 441.33 | 19.92 |
Annual Sum or Average | 4227.17 | 21.26 | 3292.00 | 21.36 | 2316.67 | 21.11 |
Minimum of Months | 69.00 | 20.04 | 83.17 | 19.95 | 16.50 | 19.92 |
Maximum of Months | 514.00 | 24.48 | 441.33 | 24.48 | 441.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.17 | 21.04 | 260.83 | 20.63 | 260.83 | 20.43 |
February | 424.33 | 21.23 | 216.33 | 20.77 | 216.00 | 20.54 |
March | 408.67 | 21.64 | 191.50 | 21.32 | 166.50 | 21.03 |
April | 346.00 | 21.31 | 186.00 | 21.01 | 141.33 | 20.64 |
May | 173.00 | 23.01 | 188.50 | 23.70 | 13.50 | 23.65 |
June | 72.00 | 25.78 | 412.00 | 24.65 | 64.33 | 24.81 |
July | 135.00 | 25.47 | 439.17 | 24.81 | 129.33 | 24.95 |
August | 81.00 | 25.07 | 405.50 | 24.53 | 55.67 | 24.66 |
September | 146.17 | 23.81 | 222.50 | 24.26 | 30.33 | 24.37 |
October | 380.67 | 21.87 | 176.00 | 21.75 | 135.00 | 21.47 |
November | 465.17 | 21.39 | 209.17 | 21.01 | 208.67 | 20.81 |
December | 497.00 | 20.66 | 333.67 | 20.32 | 333.67 | 20.17 |
Annual Sum or Average | 3623.17 | 21.79 | 3241.17 | 22.09 | 1755.17 | 21.84 |
Minimum of Months | 72.00 | 20.66 | 176.00 | 20.32 | 13.50 | 20.17 |
Maximum of Months | 497.00 | 25.78 | 439.17 | 24.81 | 333.67 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 338.33 | 21.62 | 266.17 | 21.82 | 165.17 | 21.55 |
February | 300.17 | 21.35 | 254.83 | 21.58 | 156.83 | 21.28 |
March | 358.83 | 21.64 | 242.50 | 21.67 | 161.33 | 21.41 |
April | 351.17 | 21.11 | 193.17 | 20.90 | 143.00 | 20.54 |
May | 240.67 | 22.70 | 141.00 | 23.20 | 19.00 | 23.09 |
June | 101.50 | 24.41 | 331.33 | 24.42 | 48.83 | 24.52 |
July | 138.83 | 24.69 | 381.33 | 24.57 | 106.67 | 24.66 |
August | 100.17 | 24.55 | 372.00 | 24.45 | 52.00 | 24.57 |
September | 161.83 | 23.93 | 253.50 | 24.30 | 45.83 | 24.45 |
October | 329.83 | 22.13 | 267.00 | 22.41 | 149.00 | 22.22 |
November | 318.83 | 21.97 | 264.00 | 22.28 | 149.17 | 22.06 |
December | 384.50 | 21.32 | 289.00 | 21.28 | 221.00 | 21.02 |
Annual Sum or Average | 3124.67 | 22.12 | 3255.83 | 22.58 | 1417.83 | 22.36 |
Minimum of Months | 100.17 | 21.11 | 141.00 | 20.90 | 19.00 | 20.54 |
Maximum of Months | 384.50 | 24.69 | 381.33 | 24.57 | 221.00 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.83 | 21.00 | 265.83 | 20.70 | 255.33 | 20.52 |
February | 396.00 | 21.02 | 253.00 | 20.82 | 230.50 | 20.63 |
March | 425.67 | 21.65 | 206.17 | 21.45 | 165.17 | 21.19 |
April | 360.17 | 21.36 | 174.33 | 21.14 | 127.17 | 20.80 |
May | 218.33 | 23.11 | 173.83 | 23.66 | 24.33 | 23.69 |
June | 78.67 | 25.08 | 392.33 | 24.60 | 56.50 | 24.71 |
July | 129.83 | 25.04 | 416.17 | 24.68 | 114.00 | 24.78 |
August | 79.33 | 24.84 | 399.67 | 24.53 | 51.67 | 24.63 |
September | 172.83 | 23.69 | 203.67 | 24.17 | 33.83 | 24.30 |
October | 398.17 | 21.89 | 198.50 | 21.83 | 141.83 | 21.59 |
November | 426.00 | 21.39 | 224.67 | 21.17 | 202.83 | 20.97 |
December | 471.00 | 20.72 | 322.83 | 20.42 | 320.33 | 20.29 |
Annual Sum or Average | 3612.83 | 21.80 | 3231.00 | 22.14 | 1723.50 | 21.90 |
Minimum of Months | 78.67 | 20.72 | 173.83 | 20.42 | 24.33 | 20.29 |
Maximum of Months | 471.00 | 25.08 | 416.17 | 24.68 | 320.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 8.00 | 27.00 | 454.00 | 27.00 | 8.00 | 27.00 |
March | 13.83 | 27.00 | 514.00 | 27.00 | 13.83 | 27.00 |
April | 15.50 | 27.00 | 485.00 | 27.00 | 15.50 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 26.17 | 27.00 | 496.00 | 27.00 | 26.17 | 27.00 |
July | 48.67 | 27.00 | 497.00 | 27.00 | 48.67 | 27.00 |
August | 165.00 | 27.37 | 514.00 | 27.18 | 165.00 | 27.22 |
September | 4.67 | 27.00 | 485.00 | 27.00 | 4.67 | 27.00 |
October | 13.67 | 27.00 | 502.00 | 27.00 | 13.67 | 27.00 |
November | 19.67 | 27.00 | 489.00 | 27.00 | 19.67 | 27.00 |
December | 11.00 | 27.00 | 497.00 | 27.00 | 11.00 | 27.00 |
Annual Sum or Average | 326.17 | 27.19 | 5943.00 | 27.02 | 326.17 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 165.00 | 27.37 | 514.00 | 27.18 | 165.00 | 27.22 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 442.50 | 27.00 | 0.00 | 27.00 |
February | 0.17 | 27.00 | 390.50 | 27.00 | 0.17 | 27.00 |
March | 1.33 | 27.00 | 490.17 | 27.00 | 1.33 | 27.00 |
April | 2.50 | 27.00 | 471.17 | 27.00 | 2.50 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 5.33 | 27.00 | 496.00 | 27.00 | 5.33 | 27.00 |
July | 1.17 | 27.00 | 497.00 | 27.00 | 1.17 | 27.00 |
August | 45.17 | 27.85 | 514.00 | 27.15 | 45.17 | 27.20 |
September | 3.33 | 27.00 | 485.00 | 27.00 | 3.33 | 27.00 |
October | 3.83 | 27.00 | 492.83 | 27.00 | 3.83 | 27.00 |
November | 0.00 | 0.00 | 482.00 | 27.00 | 0.00 | 27.00 |
December | 9.67 | 27.00 | 400.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 72.50 | 27.53 | 5669.83 | 27.01 | 62.83 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 390.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 45.17 | 27.85 | 514.00 | 27.15 | 45.17 | 27.20 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.50 | 25.08 | 305.17 | 26.49 | 3.33 | 26.47 |
February | 24.67 | 27.00 | 278.50 | 27.00 | 0.00 | 27.00 |
March | 21.00 | 27.00 | 437.00 | 27.00 | 1.50 | 27.00 |
April | 17.33 | 27.00 | 417.50 | 27.00 | 4.50 | 27.00 |
May | 2.00 | 25.98 | 499.83 | 27.00 | 0.00 | 27.00 |
June | 21.33 | 27.00 | 496.00 | 27.00 | 21.33 | 27.00 |
July | 20.17 | 27.00 | 497.00 | 27.00 | 20.17 | 27.00 |
August | 60.50 | 27.59 | 514.00 | 27.13 | 60.50 | 27.18 |
September | 5.33 | 27.00 | 485.00 | 27.00 | 5.33 | 27.00 |
October | 5.67 | 27.00 | 417.00 | 27.00 | 3.50 | 27.00 |
November | 0.50 | 27.00 | 399.50 | 27.00 | 0.00 | 27.00 |
December | 39.33 | 27.00 | 263.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 317.33 | 26.50 | 5010.00 | 26.98 | 120.17 | 26.98 |
Minimum of Months | 0.50 | 25.08 | 263.50 | 26.49 | 0.00 | 26.47 |
Maximum of Months | 99.50 | 27.59 | 514.00 | 27.13 | 60.50 | 27.18 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.17 | 27.00 | 502.00 | 27.00 | 427.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 453.67 | 27.00 | 508.00 | 27.00 | 453.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.02 | 497.00 | 27.02 | 497.00 | 27.02 |
August | 514.00 | 28.56 | 514.00 | 28.56 | 514.00 | 28.56 |
September | 479.17 | 27.00 | 485.00 | 27.00 | 479.17 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5808.00 | 27.14 | 5943.00 | 27.14 | 5808.00 | 27.14 |
Minimum of Months | 427.17 | 27.00 | 454.00 | 27.00 | 427.17 | 27.00 |
Maximum of Months | 514.00 | 28.56 | 514.00 | 28.56 | 514.00 | 28.56 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00006 | 18.44507 | 0.73311 | 16.44792 |
February | 454.00000 | 27.00002 | 17.22614 | 0.75810 | 17.25138 |
March | 514.00000 | 27.00004 | 17.51202 | 0.81454 | 19.07583 |
April | 485.00000 | 27.00009 | 19.53982 | 0.86935 | 21.01840 |
May | 508.00000 | 27.00036 | 22.06507 | 0.14233 | 5.50305 |
June | 496.00000 | 27.00055 | 23.98620 | 0.24903 | 6.36953 |
July | 497.00000 | 27.00039 | 24.51061 | 0.29612 | 6.88590 |
August | 514.00000 | 27.12094 | 24.22940 | 0.37343 | 8.25658 |
September | 485.00000 | 27.00028 | 21.99266 | 0.16651 | 5.70375 |
October | 502.00000 | 27.00010 | 19.05153 | 0.80867 | 18.89394 |
November | 489.00000 | 27.00005 | 19.79416 | 0.83387 | 19.76592 |
December | 497.00000 | 26.99999 | 14.67769 | 0.79492 | 18.46229 |
Annual Sum or Average | 5943.00000 | 27.01062 | 20.27670 | 0.56823 | 13.59604 |
Minimum of Months | 454.00000 | 26.99999 | 14.67769 | 0.14233 | 5.50305 |
Maximum of Months | 514.00000 | 27.12094 | 24.51061 | 0.86935 | 21.01840 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99843 | 18.46541 | 0.63315 | 13.62931 |
February | 454.00000 | 27.00002 | 17.21278 | 0.62866 | 13.57072 |
March | 514.00000 | 27.00004 | 17.50181 | 0.68340 | 15.02002 |
April | 485.00000 | 27.00006 | 19.52778 | 0.72210 | 16.17062 |
May | 508.00000 | 27.00033 | 22.09962 | 0.06770 | 5.24155 |
June | 496.00000 | 27.00053 | 24.00521 | 0.17141 | 5.72096 |
July | 497.00000 | 27.00039 | 24.52406 | 0.19380 | 5.86315 |
August | 514.00000 | 27.08807 | 24.26251 | 0.23443 | 6.45757 |
September | 485.00000 | 27.00025 | 22.01739 | 0.09677 | 5.36924 |
October | 502.00000 | 27.00010 | 19.04011 | 0.70957 | 15.79234 |
November | 489.00000 | 27.00005 | 19.78221 | 0.69207 | 15.24221 |
December | 497.00000 | 26.99999 | 14.66390 | 0.60474 | 12.93869 |
Annual Sum or Average | 5943.00000 | 27.00763 | 20.28298 | 0.45147 | 10.88934 |
Minimum of Months | 454.00000 | 26.99843 | 14.66390 | 0.06770 | 5.24155 |
Maximum of Months | 514.00000 | 27.08807 | 24.52406 | 0.72210 | 16.17062 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.58505 | 18.95765 | 0.46947 | 11.15642 |
February | 454.00000 | 27.00002 | 17.22563 | 0.55958 | 11.97515 |
March | 514.00000 | 27.00004 | 17.51846 | 0.62916 | 13.70087 |
April | 485.00000 | 27.00006 | 19.53838 | 0.66777 | 14.83752 |
May | 508.00000 | 26.99515 | 22.12690 | 0.03697 | 5.39675 |
June | 496.00000 | 27.00055 | 24.00446 | 0.18308 | 5.90152 |
July | 497.00000 | 27.00041 | 24.52310 | 0.20487 | 6.04378 |
August | 514.00000 | 27.07701 | 24.27336 | 0.23851 | 6.59205 |
September | 485.00000 | 27.00019 | 22.02735 | 0.08168 | 5.48461 |
October | 502.00000 | 27.00012 | 19.07241 | 0.64920 | 14.24265 |
November | 489.00000 | 27.00005 | 19.80024 | 0.61490 | 13.23568 |
December | 497.00000 | 27.00000 | 14.67072 | 0.52610 | 11.18890 |
Annual Sum or Average | 5943.00000 | 26.97131 | 20.33657 | 0.40361 | 9.95784 |
Minimum of Months | 454.00000 | 26.58505 | 14.67072 | 0.03697 | 5.39675 |
Maximum of Months | 514.00000 | 27.07701 | 24.52310 | 0.66777 | 14.83752 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00050 | 29.14149 | 1.01942 | 26.95896 |
February | 454.00000 | 27.00058 | 26.52184 | 1.15401 | 33.05490 |
March | 514.00000 | 27.00040 | 20.69868 | 1.25986 | 38.24188 |
April | 485.00000 | 27.00148 | 21.96230 | 1.41186 | 46.15756 |
May | 508.00000 | 27.00052 | 27.78874 | 0.43380 | 8.98168 |
June | 496.00000 | 27.00388 | 30.90779 | 0.70959 | 15.64229 |
July | 497.00000 | 27.01550 | 31.32983 | 0.92036 | 22.95364 |
August | 514.00000 | 28.56359 | 25.75543 | 1.49359 | 48.85891 |
September | 485.00000 | 27.00180 | 27.16082 | 0.49867 | 10.29640 |
October | 502.00000 | 27.00047 | 24.49048 | 1.18718 | 34.64668 |
November | 489.00000 | 27.00061 | 23.98352 | 1.31798 | 41.21387 |
December | 497.00000 | 27.00007 | 17.83960 | 1.38258 | 44.59353 |
Annual Sum or Average | 5943.00000 | 27.13738 | 25.62315 | 1.06594 | 30.98245 |
Minimum of Months | 454.00000 | 27.00007 | 17.83960 | 0.43380 | 8.98168 |
Maximum of Months | 514.00000 | 28.56359 | 31.32983 | 1.49359 | 48.85891 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36703 | 17.69811 | 0.27812 | 7.10747 |
February | 454.00000 | 24.36850 | 16.59842 | 0.26686 | 6.93422 |
March | 514.00000 | 24.31844 | 16.30341 | 0.26284 | 6.70453 |
April | 485.00000 | 24.42262 | 20.20085 | 0.31616 | 7.47531 |
May | 508.00000 | 24.44671 | 24.59295 | -0.5100 | 11.35798 |
June | 496.00000 | 24.43841 | 34.00484 | -0.4257 | 9.72069 |
July | 497.00000 | 24.58069 | 36.53358 | -0.3637 | 8.88309 |
August | 514.00000 | 24.46992 | 34.60570 | -0.3966 | 9.35461 |
September | 485.00000 | 24.53467 | 24.52310 | -0.4551 | 10.54674 |
October | 502.00000 | 24.55603 | 18.52421 | 0.34833 | 8.23422 |
November | 489.00000 | 24.53607 | 19.21742 | 0.34565 | 8.14758 |
December | 497.00000 | 24.29906 | 12.99821 | 0.24092 | 6.89857 |
Annual Sum or Average | 5943.00000 | 24.44488 | 23.04424 | -0.0106 | 8.45764 |
Minimum of Months | 454.00000 | 24.29906 | 12.99821 | -0.5100 | 6.70453 |
Maximum of Months | 514.00000 | 24.58069 | 36.53358 | 0.34833 | 11.35798 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18427 | 20.01973 | 0.24815 | 6.49025 |
February | 454.00000 | 24.19481 | 18.53109 | 0.24108 | 6.44976 |
March | 514.00000 | 24.21444 | 17.72411 | 0.26096 | 6.55137 |
April | 485.00000 | 24.35817 | 21.50779 | 0.32464 | 7.52661 |
May | 508.00000 | 24.28431 | 25.83626 | -0.5311 | 11.37404 |
June | 496.00000 | 24.26317 | 35.37794 | -0.4362 | 9.41667 |
July | 497.00000 | 24.31532 | 37.79600 | -0.3958 | 8.72502 |
August | 514.00000 | 24.24386 | 36.38858 | -0.4155 | 9.00836 |
September | 485.00000 | 24.31748 | 26.13157 | -0.4992 | 10.80936 |
October | 502.00000 | 24.34906 | 19.82346 | 0.31114 | 7.33291 |
November | 489.00000 | 24.32497 | 20.87327 | 0.31002 | 7.24975 |
December | 497.00000 | 24.24134 | 14.63826 | 0.23498 | 6.42597 |
Annual Sum or Average | 5943.00000 | 24.27427 | 24.61258 | -0.0317 | 8.12416 |
Minimum of Months | 454.00000 | 24.18427 | 14.63826 | -0.5311 | 6.42597 |
Maximum of Months | 514.00000 | 24.35817 | 37.79600 | 0.32464 | 11.37404 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45140 | 21.62897 | 0.04564 | 5.74497 |
February | 454.00000 | 23.23563 | 20.12599 | -0.0194 | 6.06329 |
March | 514.00000 | 23.56669 | 19.38834 | 0.06948 | 5.74061 |
April | 485.00000 | 23.77239 | 23.79504 | 0.14579 | 5.86438 |
May | 508.00000 | 24.15659 | 26.67260 | -0.6067 | 13.06726 |
June | 496.00000 | 24.19113 | 35.70710 | -0.4951 | 10.42727 |
July | 497.00000 | 24.22874 | 38.07127 | -0.4656 | 9.84837 |
August | 514.00000 | 24.21492 | 36.30074 | -0.4835 | 10.21488 |
September | 485.00000 | 24.19498 | 26.65986 | -0.5717 | 12.24915 |
October | 502.00000 | 23.95183 | 21.76665 | 0.19022 | 6.12840 |
November | 489.00000 | 23.66248 | 22.83414 | 0.11157 | 5.67599 |
December | 497.00000 | 22.97762 | 16.68828 | -0.1088 | 6.67413 |
Annual Sum or Average | 5943.00000 | 23.80484 | 25.85536 | -0.1842 | 8.16030 |
Minimum of Months | 454.00000 | 22.97762 | 16.68828 | -0.6067 | 5.67599 |
Maximum of Months | 514.00000 | 24.22874 | 38.07127 | 0.19022 | 13.06726 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.70918 | 23.35652 | -0.3957 | 11.33510 |
February | 454.00000 | 21.88129 | 21.52971 | -0.3659 | 10.52616 |
March | 514.00000 | 22.55793 | 20.64997 | -0.1886 | 8.65767 |
April | 485.00000 | 22.71481 | 24.80741 | -0.1184 | 8.38581 |
May | 508.00000 | 23.84969 | 27.26478 | -0.7210 | 17.02202 |
June | 496.00000 | 24.20548 | 35.48303 | -0.4765 | 10.11591 |
July | 497.00000 | 24.26341 | 37.94779 | -0.4420 | 9.52340 |
August | 514.00000 | 24.21354 | 36.29453 | -0.4739 | 10.05370 |
September | 485.00000 | 24.05582 | 26.81869 | -0.6256 | 14.22718 |
October | 502.00000 | 22.94049 | 22.81087 | -0.0760 | 7.03968 |
November | 489.00000 | 22.22607 | 24.97809 | -0.2539 | 8.05169 |
December | 497.00000 | 21.42078 | 17.96612 | -0.5054 | 13.30653 |
Annual Sum or Average | 5943.00000 | 23.01324 | 26.70574 | -0.3873 | 10.69096 |
Minimum of Months | 454.00000 | 21.42078 | 17.96612 | -0.7210 | 7.03968 |
Maximum of Months | 514.00000 | 24.26341 | 37.94779 | -0.0760 | 17.02202 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.31359 | 21.68837 | -0.2277 | 7.57786 |
February | 454.00000 | 22.27064 | 19.77236 | -0.2461 | 8.12885 |
March | 514.00000 | 23.07097 | 18.36980 | -0.0456 | 6.46521 |
April | 485.00000 | 23.45602 | 21.62571 | 0.08279 | 6.09102 |
May | 508.00000 | 24.10200 | 25.33621 | -0.5952 | 13.41197 |
June | 496.00000 | 24.35528 | 34.17658 | -0.3524 | 8.47561 |
July | 497.00000 | 24.46947 | 36.64595 | -0.2958 | 7.93454 |
August | 514.00000 | 24.28264 | 35.46662 | -0.3816 | 8.79176 |
September | 485.00000 | 24.18358 | 25.54106 | -0.5499 | 12.75611 |
October | 502.00000 | 23.33919 | 20.70352 | 0.03652 | 6.29530 |
November | 489.00000 | 22.91917 | 22.52188 | -0.0669 | 6.20247 |
December | 497.00000 | 22.30997 | 15.81765 | -0.2665 | 8.65827 |
Annual Sum or Average | 5943.00000 | 23.43167 | 24.85532 | -0.2428 | 8.40225 |
Minimum of Months | 454.00000 | 22.27064 | 15.81765 | -0.5952 | 6.09102 |
Maximum of Months | 514.00000 | 24.46947 | 36.64595 | 0.08279 | 13.41197 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.85292 | 20.69853 | -0.0806 | 7.34913 |
February | 454.00000 | 22.75664 | 18.78303 | -0.0976 | 8.53804 |
March | 514.00000 | 23.21941 | 17.66515 | 0.04221 | 7.76526 |
April | 485.00000 | 23.42176 | 21.26590 | 0.12636 | 7.30890 |
May | 508.00000 | 24.22862 | 24.71818 | -0.4671 | 11.37169 |
June | 496.00000 | 24.40399 | 33.79855 | -0.2208 | 7.79508 |
July | 497.00000 | 24.54301 | 36.37726 | -0.1736 | 8.00214 |
August | 514.00000 | 24.31755 | 35.04382 | -0.2598 | 8.30748 |
September | 485.00000 | 24.33246 | 24.95716 | -0.3951 | 10.78297 |
October | 502.00000 | 23.51409 | 19.97934 | 0.11965 | 8.09107 |
November | 489.00000 | 23.13071 | 21.84487 | 0.00695 | 7.12105 |
December | 497.00000 | 22.49661 | 15.44852 | -0.2085 | 8.85553 |
Annual Sum or Average | 5943.00000 | 23.60839 | 24.26701 | -0.1346 | 8.44133 |
Minimum of Months | 454.00000 | 22.49661 | 15.44852 | -0.4671 | 7.12105 |
Maximum of Months | 514.00000 | 24.54301 | 36.37726 | 0.12636 | 11.37169 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.43860 | 19.23101 | 0.14349 | 9.85401 |
February | 454.00000 | 23.20413 | 17.50764 | 0.07710 | 10.64614 |
March | 514.00000 | 23.30701 | 17.32666 | 0.09346 | 9.10038 |
April | 485.00000 | 23.28508 | 21.41011 | 0.08421 | 7.55361 |
May | 508.00000 | 24.06573 | 25.19726 | -0.5737 | 13.73131 |
June | 496.00000 | 24.35123 | 34.11953 | -0.3308 | 8.52948 |
July | 497.00000 | 24.47486 | 36.54506 | -0.2605 | 8.05357 |
August | 514.00000 | 24.36062 | 35.05989 | -0.2670 | 8.04675 |
September | 485.00000 | 24.37494 | 24.79218 | -0.3496 | 10.67714 |
October | 502.00000 | 23.68783 | 19.38799 | 0.22272 | 10.43813 |
November | 489.00000 | 23.73337 | 20.31423 | 0.23603 | 10.41892 |
December | 497.00000 | 23.21896 | 14.03196 | 0.04164 | 10.29192 |
Annual Sum or Average | 5943.00000 | 23.79631 | 23.80346 | -0.0754 | 9.77524 |
Minimum of Months | 454.00000 | 23.20413 | 14.03196 | -0.5737 | 7.55361 |
Maximum of Months | 514.00000 | 24.47486 | 36.54506 | 0.23603 | 13.73131 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.46651 | 19.49677 | 0.08563 | 7.03501 |
February | 454.00000 | 23.64969 | 17.40239 | 0.13936 | 7.58680 |
March | 514.00000 | 24.09402 | 16.15739 | 0.29215 | 8.09746 |
April | 485.00000 | 24.30508 | 19.75479 | 0.39305 | 8.96112 |
May | 508.00000 | 24.42021 | 24.42207 | -0.3688 | 9.71014 |
June | 496.00000 | 24.56130 | 33.49257 | -0.1078 | 7.60931 |
July | 497.00000 | 24.70628 | 35.91092 | -0.0444 | 7.39987 |
August | 514.00000 | 24.57170 | 34.43339 | -0.0563 | 7.27178 |
September | 485.00000 | 24.49583 | 24.67654 | -0.3056 | 9.60873 |
October | 502.00000 | 24.15091 | 18.88080 | 0.31441 | 8.74677 |
November | 489.00000 | 24.21331 | 19.78576 | 0.31093 | 8.28330 |
December | 497.00000 | 23.90770 | 13.39386 | 0.17805 | 7.51950 |
Annual Sum or Average | 5943.00000 | 24.21552 | 23.20672 | 0.06822 | 8.15168 |
Minimum of Months | 454.00000 | 23.46651 | 13.39386 | -0.3688 | 7.03501 |
Maximum of Months | 514.00000 | 24.70628 | 35.91092 | 0.39305 | 9.71014 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87374 | 22.83335 | -0.6046 | 14.77796 |
February | 454.00000 | 20.78251 | 20.60839 | -0.6444 | 15.98757 |
March | 514.00000 | 21.64227 | 20.07399 | -0.4104 | 11.48444 |
April | 485.00000 | 21.97718 | 24.08405 | -0.2859 | 9.94287 |
May | 508.00000 | 23.69029 | 26.42039 | -0.7548 | 18.79603 |
June | 496.00000 | 24.28228 | 34.12595 | -0.4049 | 9.19952 |
July | 497.00000 | 24.38094 | 36.66704 | -0.3583 | 8.68763 |
August | 514.00000 | 24.18366 | 35.51986 | -0.4634 | 10.19717 |
September | 485.00000 | 23.87072 | 26.12689 | -0.6789 | 16.81091 |
October | 502.00000 | 22.16945 | 23.05044 | -0.2560 | 8.80460 |
November | 489.00000 | 21.28822 | 24.26262 | -0.4851 | 11.47037 |
December | 497.00000 | 20.46351 | 16.56253 | -0.7607 | 19.52584 |
Annual Sum or Average | 5943.00000 | 22.48191 | 25.91031 | -0.5080 | 12.94955 |
Minimum of Months | 454.00000 | 20.46351 | 16.56253 | -0.7607 | 8.68763 |
Maximum of Months | 514.00000 | 24.38094 | 36.66704 | -0.2560 | 19.52584 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.75516 | 21.14542 | -0.3765 | 10.98445 |
February | 385.00000 | 21.76006 | 18.96144 | -0.3775 | 13.35913 |
March | 433.00000 | 22.41926 | 18.22762 | -0.1800 | 10.91085 |
April | 410.00000 | 22.49067 | 22.54842 | -0.1142 | 10.24925 |
May | 430.00000 | 24.07139 | 25.20472 | -0.5432 | 14.11510 |
June | 418.00000 | 24.47487 | 33.28238 | -0.2123 | 8.19518 |
July | 422.00000 | 24.65742 | 35.70128 | -0.1534 | 8.58529 |
August | 433.00000 | 24.42222 | 34.55841 | -0.2545 | 8.82053 |
September | 410.00000 | 24.27680 | 24.89391 | -0.4419 | 12.67824 |
October | 427.00000 | 22.88139 | 21.03583 | -0.0560 | 9.98961 |
November | 417.00000 | 22.12327 | 22.43695 | -0.2681 | 9.67657 |
December | 422.00000 | 21.12132 | 15.48944 | -0.5868 | 16.22538 |
Annual Sum or Average | 5034.00000 | 23.04721 | 24.49901 | -0.2965 | 11.13299 |
Minimum of Months | 385.00000 | 21.12132 | 15.48944 | -0.5868 | 8.19518 |
Maximum of Months | 433.00000 | 24.65742 | 35.70128 | -0.0560 | 16.22538 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23117 | 19.00539 | 0.09267 | 11.57138 |
February | 454.00000 | 22.86425 | 17.33441 | -0.0145 | 13.35749 |
March | 514.00000 | 22.81260 | 17.89239 | -0.0344 | 11.30005 |
April | 485.00000 | 22.50626 | 22.65089 | -0.1078 | 9.86811 |
May | 508.00000 | 23.82416 | 25.81185 | -0.6629 | 16.91830 |
June | 496.00000 | 24.28460 | 34.02487 | -0.3737 | 9.26025 |
July | 497.00000 | 24.41369 | 36.46960 | -0.3058 | 8.71703 |
August | 514.00000 | 24.32385 | 34.87029 | -0.3094 | 8.77785 |
September | 485.00000 | 24.28107 | 24.87229 | -0.3802 | 12.07112 |
October | 502.00000 | 23.38002 | 20.31054 | 0.15245 | 12.15587 |
November | 489.00000 | 23.39543 | 20.33002 | 0.14819 | 11.92173 |
December | 497.00000 | 22.61632 | 13.94525 | -0.1249 | 13.12156 |
Annual Sum or Average | 5943.00000 | 23.50013 | 24.02179 | -0.1616 | 11.57783 |
Minimum of Months | 454.00000 | 22.50626 | 13.94525 | -0.6629 | 8.71703 |
Maximum of Months | 514.00000 | 24.41369 | 36.46960 | 0.15245 | 16.91830 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.96164 | 21.03891 | -0.3082 | 10.57604 |
February | 454.00000 | 21.88647 | 18.97807 | -0.3321 | 12.34683 |
March | 514.00000 | 22.49653 | 18.68477 | -0.1503 | 10.27035 |
April | 485.00000 | 22.63168 | 22.73753 | -0.0794 | 9.36312 |
May | 508.00000 | 24.00488 | 25.56286 | -0.5623 | 14.70994 |
June | 496.00000 | 24.41124 | 33.71338 | -0.2369 | 8.48249 |
July | 497.00000 | 24.50596 | 36.24511 | -0.2200 | 8.05885 |
August | 514.00000 | 24.38328 | 34.86018 | -0.2707 | 8.45264 |
September | 485.00000 | 24.20114 | 25.27103 | -0.4622 | 13.00950 |
October | 502.00000 | 22.91549 | 21.45750 | -0.0244 | 9.37496 |
November | 489.00000 | 22.33179 | 22.37836 | -0.1980 | 9.06851 |
December | 497.00000 | 21.40060 | 15.50139 | -0.4982 | 14.54261 |
Annual Sum or Average | 5943.00000 | 23.10503 | 24.75590 | -0.2783 | 10.67518 |
Minimum of Months | 454.00000 | 21.40060 | 15.50139 | -0.5623 | 8.05885 |
Maximum of Months | 514.00000 | 24.50596 | 36.24511 | -0.0244 | 14.70994 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25232 | 23.22477 | -0.8073 | 21.73432 |
February | 454.00000 | 20.35746 | 20.93667 | -0.7940 | 20.81998 |
March | 514.00000 | 21.24025 | 20.23630 | -0.5421 | 14.96650 |
April | 485.00000 | 21.40072 | 24.68675 | -0.4467 | 14.69627 |
May | 508.00000 | 23.34856 | 26.94148 | -0.8762 | 24.12956 |
June | 496.00000 | 24.25462 | 34.09898 | -0.4026 | 9.48943 |
July | 497.00000 | 24.35373 | 36.76485 | -0.3557 | 9.08125 |
August | 514.00000 | 24.12329 | 35.77905 | -0.4734 | 10.82949 |
September | 485.00000 | 23.66130 | 26.35073 | -0.7523 | 20.28188 |
October | 502.00000 | 21.54914 | 23.13469 | -0.4378 | 12.55577 |
November | 489.00000 | 20.66547 | 24.80110 | -0.6789 | 17.36712 |
December | 497.00000 | 20.03552 | 16.61779 | -0.9192 | 25.56042 |
Annual Sum or Average | 5943.00000 | 22.11960 | 26.17887 | -0.6225 | 16.75306 |
Minimum of Months | 454.00000 | 20.03552 | 16.61779 | -0.9192 | 9.08125 |
Maximum of Months | 514.00000 | 24.35373 | 36.76485 | -0.3557 | 25.56042 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.08156 | 22.21609 | -0.5743 | 16.21952 |
February | 454.00000 | 21.42056 | 19.68152 | -0.4944 | 15.88217 |
March | 514.00000 | 22.17637 | 18.65582 | -0.2635 | 12.58301 |
April | 485.00000 | 22.11445 | 23.09650 | -0.2202 | 13.66757 |
May | 508.00000 | 23.83910 | 25.43305 | -0.6156 | 16.47487 |
June | 496.00000 | 24.38181 | 33.43170 | -0.2086 | 8.02549 |
July | 497.00000 | 24.53833 | 36.12966 | -0.1576 | 8.47178 |
August | 514.00000 | 24.31710 | 34.74198 | -0.2509 | 8.72265 |
September | 485.00000 | 24.11370 | 25.06769 | -0.4776 | 13.72544 |
October | 502.00000 | 22.49506 | 21.20920 | -0.1772 | 11.67196 |
November | 489.00000 | 21.52140 | 23.39663 | -0.4445 | 13.09436 |
December | 497.00000 | 20.65529 | 16.19660 | -0.7365 | 20.80973 |
Annual Sum or Average | 5943.00000 | 22.73389 | 24.98573 | -0.3841 | 13.25167 |
Minimum of Months | 454.00000 | 20.65529 | 16.19660 | -0.7365 | 8.02549 |
Maximum of Months | 514.00000 | 24.53833 | 36.12966 | -0.1576 | 20.80973 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.50538 | 19.56716 | -0.1310 | 13.32530 |
February | 454.00000 | 22.35231 | 17.86509 | -0.1799 | 14.81552 |
March | 514.00000 | 22.41267 | 18.14937 | -0.1646 | 13.03889 |
April | 485.00000 | 21.93928 | 23.33365 | -0.2650 | 14.19806 |
May | 508.00000 | 23.52480 | 26.28766 | -0.7723 | 21.57171 |
June | 496.00000 | 24.23359 | 34.05305 | -0.3782 | 9.81875 |
July | 497.00000 | 24.37192 | 36.60756 | -0.3077 | 9.29238 |
August | 514.00000 | 24.25740 | 35.14321 | -0.3215 | 9.42029 |
September | 485.00000 | 24.11908 | 25.00762 | -0.4401 | 14.41332 |
October | 502.00000 | 22.86217 | 20.29663 | -0.0079 | 13.62935 |
November | 489.00000 | 22.80999 | 20.87346 | -0.0370 | 12.77427 |
December | 497.00000 | 21.99482 | 14.32206 | -0.3186 | 16.08646 |
Annual Sum or Average | 5943.00000 | 23.12266 | 24.35199 | -0.2781 | 13.52288 |
Minimum of Months | 454.00000 | 21.93928 | 14.32206 | -0.7723 | 9.29238 |
Maximum of Months | 514.00000 | 24.37192 | 36.60756 | -0.0079 | 21.57171 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.27244 | 21.57669 | -0.5129 | 15.57346 |
February | 454.00000 | 21.43468 | 19.42314 | -0.4746 | 15.46604 |
March | 514.00000 | 22.08446 | 18.94774 | -0.2748 | 12.54859 |
April | 485.00000 | 22.05794 | 23.36610 | -0.2300 | 13.12229 |
May | 508.00000 | 23.74333 | 25.97047 | -0.6572 | 18.60247 |
June | 496.00000 | 24.37671 | 33.70823 | -0.2376 | 8.91687 |
July | 497.00000 | 24.47157 | 36.35346 | -0.2207 | 8.51132 |
August | 514.00000 | 24.33430 | 35.07754 | -0.2784 | 8.91376 |
September | 485.00000 | 24.03376 | 25.44486 | -0.5217 | 15.56642 |
October | 502.00000 | 22.38745 | 21.55706 | -0.1781 | 11.66334 |
November | 489.00000 | 21.74623 | 22.91655 | -0.3717 | 12.25918 |
December | 497.00000 | 20.90132 | 15.71840 | -0.6562 | 19.12670 |
Annual Sum or Average | 5943.00000 | 22.74929 | 25.05666 | -0.3837 | 13.33397 |
Minimum of Months | 454.00000 | 20.90132 | 15.71840 | -0.6572 | 8.51132 |
Maximum of Months | 514.00000 | 24.47157 | 36.35346 | -0.1781 | 19.12670 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.115965E+11 | 98263.59 | 20-JAN-15:00 | 173.21 | 0.804173E+11 | 0.00 | 0.920138E+11 | 1.32 | 7.96 | 24-JAN-14:00 | 0.00 | 0.00 |
February | 0.103518E+11 | 65237.22 | 17-FEB-15:10 | 171.26 | 0.645654E+11 | 0.00 | 0.749172E+11 | 1.40 | 7.86 | 17-FEB-15:10 | 0.00 | 0.00 |
March | 0.188727E+11 | 132813.38 | 14-MAR-15:10 | 205.09 | 0.129578E+12 | 0.00 | 0.148450E+12 | 1.59 | 7.96 | 15-MAR-13:30 | 0.00 | 0.00 |
April | 0.151649E+11 | 94431.07 | 19-APR-13:30 | 175.43 | 0.103012E+12 | 0.00 | 0.118177E+12 | 1.41 | 7.96 | 07-APR-15:40 | 0.00 | 0.00 |
May | 0.430652E+11 | 132575.56 | 18-MAY-14:40 | 292.44 | 0.305768E+12 | 0.00 | 0.348833E+12 | 2.47 | 7.96 | 04-MAY-11:30 | 0.00 | 0.00 |
June | 0.106385E+12 | 138352.59 | 20-JUN-12:10 | 513.79 | 0.802433E+12 | 0.00 | 0.908818E+12 | 4.96 | 8.01 | 14-JUN-04:13 | 0.00 | 0.00 |
July | 0.111344E+12 | 139214.00 | 27-JUL-09:00 | 583.72 | 0.833542E+12 | 0.00 | 0.944886E+12 | 5.31 | 8.00 | 18-JUL-04:13 | 0.00 | 0.00 |
August | 0.104554E+12 | 141335.98 | 05-AUG-12:20 | 607.75 | 0.787283E+12 | 0.00 | 0.891837E+12 | 5.42 | 7.96 | 26-AUG-08:30 | 0.00 | 0.00 |
September | 0.793110E+11 | 133734.46 | 20-SEP-14:50 | 411.42 | 0.588785E+12 | 0.00 | 0.668096E+12 | 3.90 | 7.96 | 13-SEP-15:00 | 0.00 | 0.00 |
October | 0.318254E+11 | 129086.44 | 10-OCT-10:30 | 229.32 | 0.229683E+12 | 0.00 | 0.261509E+12 | 1.96 | 7.96 | 10-OCT-09:50 | 0.00 | 0.00 |
November | 0.166597E+11 | 131677.32 | 07-NOV-14:20 | 198.45 | 0.111871E+12 | 0.00 | 0.128531E+12 | 1.58 | 7.96 | 06-NOV-12:50 | 0.00 | 0.00 |
December | 0.985101E+10 | 82762.65 | 01-DEC-14:30 | 157.09 | 0.624226E+11 | 0.00 | 0.722736E+11 | 1.16 | 7.96 | 01-DEC-14:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.558981E+12 | 3718.96 | 0.409936E+13 | 0.00 | 0.465834E+13 | 2.71 | 0.00 | 0.00 | ||||
Minimum of Months | 0.985101E+10 | 65237.22 | 157.09 | 0.624226E+11 | 0.00 | 0.722736E+11 | 1.16 | 7.86 | 0.00 | 0.00 | ||
Maximum of Months | 0.111344E+12 | 141335.98 | 607.75 | 0.833542E+12 | 0.00 | 0.944886E+12 | 5.42 | 8.01 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.649400E+09 | 82337.19 | 14-MAR-13:05 | 2.83 | 0.495607E+10 | 0.00 | 0.560547E+10 | 0.03 | 7.96 | 14-MAR-13:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.524618E+10 | 86922.60 | 16-MAY-12:05 | 20.83 | 0.410047E+11 | 0.00 | 0.462509E+11 | 0.22 | 7.96 | 04-MAY-14:05 | 0.00 | 0.00 |
June | 0.439550E+11 | 129274.87 | 22-JUN-09:32 | 157.31 | 0.345595E+12 | 0.00 | 0.389550E+12 | 1.71 | 7.96 | 07-JUN-16:00 | 0.00 | 0.00 |
July | 0.420562E+11 | 134416.26 | 27-JUL-09:02 | 152.38 | 0.329856E+12 | 0.00 | 0.371913E+12 | 1.60 | 7.96 | 10-JUL-12:05 | 0.00 | 0.00 |
August | 0.433910E+11 | 119449.32 | 07-AUG-08:05 | 155.82 | 0.341858E+12 | 0.00 | 0.385249E+12 | 1.65 | 7.96 | 25-AUG-14:00 | 0.00 | 0.00 |
September | 0.236039E+11 | 90197.48 | 12-SEP-16:00 | 90.04 | 0.185447E+12 | 0.00 | 0.209051E+12 | 0.98 | 7.96 | 13-SEP-15:00 | 0.00 | 0.00 |
October | 0.239493E+10 | 83011.98 | 11-OCT-10:05 | 9.50 | 0.187874E+11 | 0.00 | 0.211823E+11 | 0.10 | 7.96 | 11-OCT-12:05 | 0.00 | 0.00 |
November | 0.242999E+09 | 81060.12 | 07-NOV-15:30 | 1.08 | 0.183519E+10 | 0.00 | 0.207819E+10 | 0.01 | 7.86 | 07-NOV-15:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.161540E+12 | 589.79 | 0.126934E+13 | 0.00 | 0.143088E+13 | 0.53 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.439550E+11 | 134416.26 | 157.31 | 0.345595E+12 | 0.00 | 0.389550E+12 | 1.71 | 7.96 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.402820E+10 | 744.00 | 43776.24 | 19-JAN-14:00 | 56966.18 | 23-JAN-16:10 | 18.81 | 18.35 | 15.56 |
February | 0.460370E+10 | 672.00 | 43776.24 | 18-FEB-11:50 | 117467.63 | 18-FEB-14:00 | 19.33 | 18.34 | 15.56 |
March | 0.163290E+11 | 744.00 | 43776.24 | 08-MAR-13:00 | 424877.19 | 14-MAR-13:05 | 20.36 | 18.58 | 15.56 |
April | 0.236275E+11 | 720.00 | 43776.24 | 06-APR-12:30 | 499789.67 | 19-APR-13:50 | 21.51 | 18.77 | 15.56 |
May | 0.370903E+11 | 744.00 | 43776.24 | 04-MAY-08:20 | 242285.08 | 31-MAY-16:00 | 20.28 | 19.43 | 15.56 |
June | 0.886815E+11 | 720.00 | 43776.24 | 01-JUN-07:50 | 501092.33 | 18-JUN-10:50 | 29.15 | 25.19 | 15.56 |
July | 0.108042E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 713167.82 | 30-JUL-14:02 | 34.41 | 27.23 | 15.56 |
August | 0.112505E+12 | 744.00 | 43776.24 | 01-AUG-00:10 | 731780.14 | 05-AUG-14:25 | 37.07 | 27.52 | 15.56 |
September | 0.666739E+11 | 720.00 | 43776.24 | 01-SEP-00:10 | 261057.15 | 10-SEP-18:02 | 23.26 | 21.79 | 15.56 |
October | 0.190262E+11 | 744.00 | 43776.24 | 01-OCT-14:32 | 387473.09 | 11-OCT-14:05 | 20.01 | 18.73 | 15.56 |
November | 0.113365E+11 | 720.00 | 43776.24 | 05-NOV-09:42 | 357381.18 | 07-NOV-15:00 | 20.20 | 18.50 | 15.56 |
December | 0.120108E+11 | 744.00 | 43776.24 | 01-DEC-10:30 | 495017.16 | 01-DEC-14:05 | 20.65 | 18.49 | 15.56 |
Annual Sum or Average | 0.503955E+12 | 8760.00 | 23.79 | 20.93 | 15.56 | ||||
Minimum of Months | 0.402820E+10 | 672.00 | 43776.24 | 56966.18 | 18.81 | 18.34 | 15.56 | ||
Maximum of Months | 0.112505E+12 | 744.00 | 43776.24 | 731780.14 | 37.07 | 27.52 | 15.56 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 21424658.14 | 44.50 | 435.81 | 20-JAN-15:40 | 885989.21 | 20-JAN-15:00 | 21.15 | 20.97 | 5.43 |
February | 12915294.03 | 46.13 | 221.89 | 18-FEB-14:30 | 586959.92 | 17-FEB-15:10 | 21.16 | 20.99 | 6.47 |
March | 42454227.50 | 80.62 | 1051.66 | 14-MAR-14:05 | 1140452.32 | 13-MAR-13:40 | 21.22 | 20.94 | 8.24 |
April | 40592036.14 | 73.42 | 689.09 | 20-APR-13:00 | 850160.41 | 19-APR-13:30 | 21.22 | 20.99 | 7.41 |
May | 0.315692E+09 | 196.01 | 14062.26 | 31-MAY-16:20 | 1108197.59 | 18-MAY-14:40 | 21.81 | 21.14 | 16.92 |
June | 0.261581E+10 | 435.38 | 14062.26 | 15-JUN-13:40 | 1153882.60 | 22-JUN-09:30 | 23.06 | 21.21 | 33.32 |
July | 0.445367E+10 | 462.89 | 14062.26 | 08-JUL-11:05 | 1145313.98 | 27-JUL-09:00 | 23.03 | 21.17 | 35.47 |
August | 0.279694E+10 | 427.15 | 14062.26 | 02-AUG-17:30 | 1109653.92 | 31-AUG-08:40 | 22.88 | 21.11 | 34.18 |
September | 0.724379E+09 | 340.48 | 14062.26 | 01-SEP-12:05 | 1137857.14 | 25-SEP-13:30 | 22.58 | 21.21 | 26.78 |
October | 0.122004E+09 | 143.96 | 1196.05 | 11-OCT-11:30 | 1107060.91 | 10-OCT-10:30 | 21.47 | 20.98 | 12.25 |
November | 36484374.04 | 74.64 | 992.51 | 07-NOV-14:30 | 1107186.81 | 07-NOV-14:20 | 21.22 | 20.97 | 8.07 |
December | 13956706.95 | 38.80 | 314.21 | 01-DEC-14:00 | 750963.19 | 01-DEC-14:40 | 21.07 | 20.93 | 5.42 |
Annual Sum or Average | 0.111963E+11 | 2363.99 | 21.83 | 21.05 | 16.72 | ||||
Minimum of Months | 12915294.03 | 38.80 | 221.89 | 586959.92 | 21.07 | 20.93 | 5.42 | ||
Maximum of Months | 0.445367E+10 | 462.89 | 14062.26 | 1153882.60 | 23.06 | 21.21 | 35.47 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.15 | 21.15 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.16 | 21.16 | 0.00 |
March | 2134763.33 | 1.17 | 986.81 | 14-MAR-12:40 | 973746.32 | 14-MAR-13:05 | 21.22 | 21.22 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.22 | 21.22 | 0.00 |
May | 44511584.51 | 17.17 | 1452.49 | 17-MAY-09:00 | 1017645.98 | 31-MAY-10:00 | 21.81 | 21.71 | 1.17 |
June | 0.100232E+10 | 146.11 | 14062.26 | 15-JUN-13:40 | 1138289.74 | 22-JUN-09:32 | 23.06 | 22.22 | 10.27 |
July | 0.198147E+10 | 140.13 | 14062.26 | 19-JUL-10:05 | 1142842.96 | 27-JUL-09:02 | 23.03 | 22.26 | 9.53 |
August | 0.134759E+10 | 145.51 | 14062.26 | 03-AUG-13:10 | 1045039.06 | 25-AUG-12:50 | 22.88 | 22.07 | 9.88 |
September | 0.197946E+09 | 80.12 | 2746.93 | 01-SEP-11:40 | 1040082.16 | 08-SEP-14:30 | 22.58 | 22.10 | 5.63 |
October | 27861405.77 | 8.00 | 1172.79 | 10-OCT-10:50 | 1002020.47 | 11-OCT-15:00 | 21.47 | 21.42 | 0.54 |
November | 666872.96 | 0.25 | 992.51 | 07-NOV-14:40 | 958205.57 | 07-NOV-15:05 | 21.22 | 21.21 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.07 | 21.07 | 0.00 |
Annual Sum or Average | 0.460450E+10 | 538.45 | 21.83 | 21.57 | 3.11 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.07 | 21.07 | 0.00 | ||
Maximum of Months | 0.198147E+10 | 146.11 | 14062.26 | 1142842.96 | 23.06 | 22.26 | 10.27 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.249517E+12 | 0.00 | 415.05 | 1371586.15 | 30-JAN-06:01 | 0.00 | 37.06 | 49.31 | 1.25 | 0.00 | 0.04 | 0.58 | 30-JAN-06:01 |
February | 0.273261E+12 | 0.00 | 387.80 | 1441028.92 | 13-FEB-06:02 | 0.00 | 37.22 | 49.68 | 1.43 | 0.00 | 0.05 | 0.61 | 13-FEB-06:02 |
March | 0.174255E+12 | 0.00 | 339.50 | 1402667.64 | 21-MAR-04:01 | 0.00 | 34.91 | 45.50 | 0.75 | 0.00 | 0.03 | 0.60 | 21-MAR-04:01 |
April | 0.107381E+12 | 0.00 | 272.43 | 1311071.60 | 24-APR-04:01 | 0.00 | 33.84 | 43.10 | 0.46 | 0.00 | 0.02 | 0.56 | 24-APR-04:01 |
May | 0.970297E+10 | 0.00 | 64.34 | 1666619.34 | 01-MAY-04:11 | 0.00 | 31.69 | 34.06 | 0.03 | 0.00 | 0.00 | 0.71 | 01-MAY-04:11 |
June | 1935758.94 | 0.00 | 0.50 | 2152.53 | 09-JUN-06:10 | 0.00 | 29.75 | 29.77 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 29.74 | 29.74 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 29.74 | 29.74 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.628959E+10 | 0.00 | 24.43 | 906639.18 | 22-SEP-05:02 | 0.00 | 30.41 | 31.30 | 0.02 | 0.00 | 0.00 | 0.39 | 22-SEP-05:02 |
October | 0.127724E+12 | 0.00 | 238.89 | 1452354.14 | 23-OCT-04:01 | 0.00 | 33.63 | 41.34 | 0.60 | 0.00 | 0.02 | 0.62 | 23-OCT-04:01 |
November | 0.201166E+12 | 0.00 | 328.31 | 1522356.43 | 27-NOV-05:01 | 0.00 | 35.43 | 46.00 | 0.96 | 0.00 | 0.03 | 0.65 | 27-NOV-05:01 |
December | 0.406604E+12 | 0.00 | 473.18 | 1604925.36 | 27-DEC-06:01 | 0.00 | 38.42 | 51.43 | 2.46 | 0.00 | 0.06 | 0.68 | 27-DEC-06:01 |
Annual Sum or Average | 0.155590E+13 | 0.00 | 2544.44 | 0.00 | 33.47 | 40.03 | 0.66 | 0.00 | 0.02 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.74 | 29.74 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.406604E+12 | 0.00 | 473.18 | 1666619.34 | 0.00 | 38.42 | 51.43 | 2.46 | 0.00 | 0.06 | 0.71 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.81 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.33 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.36 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.51 | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.28 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.15 | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 34.41 | 34.41 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 37.07 | 37.07 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 23.26 | 23.26 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 20.01 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 20.20 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.65 | 20.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 | 23.79 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.07 | 37.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.116365E+11 | 0.00 | 139.64 | 0.116365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64806.10 | 24-JAN-14:50 | 64806.10 | 24-JAN-14:50 | 0.00 | 0.00 | 0.00 |
February | 0.103866E+11 | 0.00 | 125.58 | 0.103866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60136.94 | 17-FEB-15:00 | 60136.94 | 17-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.148699E+11 | 0.00 | 161.99 | 0.148699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92628.46 | 13-MAR-16:00 | 92628.46 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.108664E+11 | 0.00 | 132.56 | 0.108664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74734.27 | 19-APR-13:30 | 74734.27 | 19-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.312399E+11 | 0.00 | 259.79 | 0.312399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100360.82 | 31-MAY-14:50 | 100360.82 | 31-MAY-14:50 | 0.00 | 0.00 | 0.00 |
June | 0.102542E+12 | 0.00 | 492.00 | 0.102380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 172058.19 | 26-JUN-14:43 | 172058.19 | 26-JUN-14:43 | 0.00 | 0.00 | 0.00 |
July | 0.108714E+12 | 0.00 | 559.54 | 0.106394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 143505.00 | 27-JUL-09:05 | 141167.77 | 27-JUL-09:05 | 0.00 | 0.00 | 0.00 |
August | 0.110530E+12 | 0.00 | 590.68 | 0.109877E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 141062.90 | 14-AUG-14:50 | 141062.90 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 |
September | 0.676609E+11 | 0.00 | 383.24 | 0.676609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120448.66 | 12-SEP-16:00 | 120448.66 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.187059E+11 | 0.00 | 172.18 | 0.187059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110894.75 | 10-OCT-15:00 | 110894.75 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.160894E+11 | 0.00 | 167.01 | 0.160894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77956.43 | 06-NOV-14:00 | 77956.43 | 06-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.135532E+11 | 0.00 | 139.57 | 0.135532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63805.20 | 13-DEC-14:50 | 63805.20 | 13-DEC-14:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516794E+12 | 0.00 | 3323.78 | 0.513659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103866E+11 | 0.00 | 125.58 | 0.103866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60136.94 | 60136.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.110530E+12 | 0.00 | 590.68 | 0.109877E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 172058.19 | 172058.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.624285E+11 | 0.00 | 107.86 | 0.624285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 576457.36 | 20-JAN-15:05 | 576457.36 | 20-JAN-15:05 | 0.00 | 0.00 | 0.00 |
February | 0.491432E+11 | 0.00 | 120.01 | 0.491432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 437481.19 | 27-FEB-15:05 | 437481.19 | 27-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.102915E+12 | 0.00 | 148.60 | 0.102915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 746907.59 | 13-MAR-15:50 | 746907.59 | 13-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.809565E+11 | 0.00 | 134.12 | 0.809565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 539276.85 | 20-APR-13:00 | 539276.85 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.270001E+12 | 0.00 | 268.32 | 0.270001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 932020.66 | 16-MAY-14:05 | 932020.66 | 16-MAY-14:05 | 0.00 | 0.00 | 0.00 |
June | 0.882532E+12 | 0.00 | 454.08 | 0.881398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1450673.62 | 26-JUN-14:03 | 1450673.62 | 26-JUN-14:03 | 0.00 | 0.00 | 0.00 |
July | 0.887302E+12 | 0.00 | 464.14 | 0.871946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1252292.35 | 30-JUL-15:41 | 1230443.40 | 17-JUL-10:30 | 0.00 | 0.00 | 0.00 |
August | 0.853399E+12 | 0.00 | 450.41 | 0.850879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1254952.68 | 16-AUG-15:10 | 1254952.68 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.592200E+12 | 0.00 | 377.85 | 0.592200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1122467.66 | 12-SEP-16:00 | 1122467.66 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.200885E+12 | 0.00 | 198.43 | 0.200885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 932295.74 | 11-OCT-14:05 | 932295.74 | 11-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.848728E+11 | 0.00 | 125.46 | 0.848728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 697360.14 | 07-NOV-15:05 | 697360.14 | 07-NOV-15:05 | 0.00 | 0.00 | 0.00 |
December | 0.422401E+11 | 0.00 | 84.17 | 0.422401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 472269.65 | 01-DEC-15:05 | 472269.65 | 01-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410888E+13 | 0.00 | 2933.45 | 0.408986E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.422401E+11 | 0.00 | 84.17 | 0.422401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 437481.19 | 437481.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.887302E+12 | 0.00 | 464.14 | 0.881398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1450673.62 | 1450673.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.249133E+10 | 0.00 | 53.52 | 0.249133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42016.45 | 20-JAN-14:10 | 42016.45 | 20-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.323271E+10 | 0.00 | 73.32 | 0.323271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38580.97 | 17-FEB-15:30 | 38580.97 | 17-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.789115E+10 | 0.00 | 99.03 | 0.789115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77455.96 | 13-MAR-15:30 | 77455.96 | 13-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.613926E+10 | 0.00 | 89.35 | 0.613926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60410.73 | 20-APR-13:00 | 60410.73 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.273888E+11 | 0.00 | 245.77 | 0.273888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111449.33 | 31-MAY-15:20 | 111449.33 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.992608E+11 | 0.00 | 449.01 | 0.991861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194378.21 | 26-JUN-14:43 | 194378.21 | 26-JUN-14:43 | 0.00 | 0.00 | 0.00 |
July | 0.980496E+11 | 0.00 | 461.67 | 0.965201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147787.37 | 12-JUL-14:45 | 147787.37 | 12-JUL-14:45 | 0.00 | 0.00 | 0.00 |
August | 0.946481E+11 | 0.00 | 443.41 | 0.944276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153174.80 | 16-AUG-15:10 | 153174.80 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.614433E+11 | 0.00 | 364.36 | 0.614433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134273.98 | 10-SEP-15:11 | 134273.98 | 10-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.123743E+11 | 0.00 | 131.45 | 0.123743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103839.67 | 11-OCT-15:00 | 103839.67 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.585095E+10 | 0.00 | 85.80 | 0.585095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57682.25 | 07-NOV-15:00 | 57682.25 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.308651E+10 | 0.00 | 59.44 | 0.308651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40634.36 | 01-DEC-14:00 | 40634.36 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421857E+12 | 0.00 | 2556.13 | 0.420032E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.249133E+10 | 0.00 | 53.52 | 0.249133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38580.97 | 38580.97 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.992608E+11 | 0.00 | 461.67 | 0.991861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194378.21 | 194378.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.967799E+09 | 0.00 | 18.33 | 0.967799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27976.30 | 23-JAN-13:10 | 27976.30 | 23-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 90192108.48 | 0.00 | 4.17 | 90192108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10763.35 | 18-FEB-13:00 | 10763.35 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.325668E+10 | 0.00 | 46.82 | 0.325668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50600.92 | 13-MAR-14:00 | 50600.92 | 13-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.349720E+10 | 0.00 | 59.33 | 0.349720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35528.87 | 20-APR-13:00 | 35528.87 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.166351E+11 | 0.00 | 170.88 | 0.166287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53270.73 | 31-MAY-14:00 | 53270.73 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.544890E+11 | 0.00 | 360.32 | 0.544492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90056.08 | 26-JUN-12:45 | 90056.08 | 26-JUN-12:45 | 0.00 | 0.00 | 0.00 |
July | 0.556007E+11 | 0.00 | 363.16 | 0.550035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76373.64 | 17-JUL-10:00 | 76373.64 | 17-JUL-10:00 | 0.00 | 0.00 | 0.00 |
August | 0.577966E+11 | 0.00 | 383.94 | 0.575187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92979.80 | 20-AUG-16:08 | 92979.80 | 20-AUG-16:08 | 0.00 | 0.00 | 0.00 |
September | 0.401096E+11 | 0.00 | 304.66 | 0.401059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93060.73 | 10-SEP-18:15 | 93060.73 | 10-SEP-18:15 | 0.00 | 0.00 | 0.00 |
October | 0.691819E+10 | 0.00 | 76.94 | 0.691819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67829.66 | 09-OCT-15:41 | 67829.66 | 09-OCT-15:41 | 0.00 | 0.00 | 0.00 |
November | 0.259547E+10 | 0.00 | 32.75 | 0.259547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49899.05 | 06-NOV-13:10 | 49899.05 | 06-NOV-13:10 | 0.00 | 0.00 | 0.00 |
December | 0.134702E+10 | 0.00 | 20.73 | 0.134702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37903.86 | 04-DEC-12:00 | 37903.86 | 04-DEC-12:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243304E+12 | 0.00 | 1842.02 | 0.242379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 90192108.48 | 0.00 | 4.17 | 90192108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10763.35 | 10763.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.577966E+11 | 0.00 | 383.94 | 0.575187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93060.73 | 93060.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.992638E+10 | 0.482699E+10 | 744.00 | 0.841438E+10 | 0.151199E+10 | 0.00 | 0.03 | 20-JAN-14:00 | 0.01 | 28-JAN-10:55 | 5646.73 | 19-JAN-11:40 | 4960.52 | 23-JAN-17:15 | 772.25 | 19-JAN-11:30 | 2489.88 | 20-JAN-14:00 | 0.00 |
February | 0.142982E+11 | 0.587527E+10 | 672.00 | 0.122162E+11 | 0.208196E+10 | 0.00 | 0.16 | 18-FEB-14:00 | 0.02 | 19-FEB-14:23 | 45834.43 | 18-FEB-14:00 | 45834.43 | 18-FEB-14:00 | 1310.09 | 11-FEB-05:52 | 14859.36 | 18-FEB-14:00 | 0.00 |
March | 0.393274E+11 | 0.143429E+11 | 744.00 | 0.376969E+11 | 0.163046E+10 | 0.00 | 0.76 | 14-MAR-13:00 | 0.02 | 17-MAR-15:00 | 244077.89 | 14-MAR-13:00 | 244077.89 | 14-MAR-13:00 | 2985.89 | 31-MAR-17:50 | 85112.07 | 14-MAR-13:00 | 0.00 |
April | 0.862114E+11 | 0.272870E+11 | 718.83 | 0.805003E+11 | 0.571111E+10 | 0.00 | 0.84 | 19-APR-13:00 | 0.01 | 13-APR-19:10 | 283899.70 | 19-APR-14:00 | 283899.70 | 19-APR-14:00 | 93039.19 | 28-APR-14:00 | 92010.16 | 19-APR-13:10 | 0.00 |
May | 0.277977E+11 | 0.108900E+11 | 670.94 | 0.264495E+11 | 0.134818E+10 | 0.00 | 0.41 | 17-MAY-11:00 | 0.00 | 20-MAY-23:50 | 146530.76 | 31-MAY-13:40 | 138514.39 | 16-MAY-16:00 | 12120.20 | 31-MAY-13:40 | 48311.93 | 17-MAY-14:00 | 0.00 |
June | 0.290028E+12 | 0.959994E+11 | 631.61 | 0.260824E+12 | 0.292036E+11 | 0.00 | 0.77 | 18-JUN-10:50 | 0.00 | 08-JUN-23:10 | 334776.40 | 18-JUN-10:42 | 230542.75 | 26-JUN-14:43 | 118611.11 | 18-JUN-10:31 | 101670.06 | 26-JUN-15:00 | 0.00 |
July | 0.604821E+12 | 0.185821E+12 | 739.96 | 0.494023E+12 | 0.110798E+12 | 0.00 | 1.00 | 29-JUL-12:30 | 0.01 | 20-JUL-03:00 | 459663.70 | 31-JUL-23:05 | 322187.84 | 17-JUL-07:40 | 286204.94 | 31-JUL-23:05 | 133873.29 | 30-JUL-14:00 | 0.00 |
August | 0.822575E+12 | 0.244472E+12 | 744.00 | 0.651515E+12 | 0.171060E+12 | 0.00 | 1.00 | 02-AUG-10:40 | 0.02 | 23-AUG-05:20 | 466744.32 | 04-AUG-02:00 | 408704.20 | 06-AUG-12:08 | 327856.03 | 04-AUG-02:00 | 152282.71 | 16-AUG-16:00 | 0.00 |
September | 0.858736E+11 | 0.300117E+11 | 678.71 | 0.811800E+11 | 0.469361E+10 | 0.00 | 0.43 | 18-SEP-12:40 | 0.00 | 03-SEP-01:10 | 148161.93 | 13-SEP-13:05 | 139959.02 | 18-SEP-12:40 | 19632.65 | 01-SEP-12:00 | 52832.71 | 09-SEP-13:00 | 0.00 |
October | 0.310516E+11 | 0.116714E+11 | 744.00 | 0.292218E+11 | 0.182972E+10 | 0.00 | 0.70 | 11-OCT-14:00 | 0.01 | 03-OCT-13:00 | 231651.67 | 11-OCT-14:00 | 231651.67 | 11-OCT-14:00 | 1567.23 | 31-OCT-23:10 | 83727.51 | 11-OCT-14:00 | 0.00 |
November | 0.312182E+11 | 0.114121E+11 | 720.00 | 0.286938E+11 | 0.252447E+10 | 0.00 | 0.62 | 06-NOV-14:00 | 0.02 | 09-NOV-24:00 | 194154.93 | 07-NOV-15:00 | 194154.93 | 07-NOV-15:00 | 3788.32 | 09-NOV-09:30 | 65476.49 | 06-NOV-14:00 | 0.00 |
December | 0.411774E+11 | 0.149049E+11 | 744.00 | 0.406568E+11 | 0.520583E+09 | 0.00 | 0.85 | 01-DEC-14:00 | 0.03 | 26-DEC-12:15 | 282869.92 | 01-DEC-14:00 | 282869.92 | 01-DEC-14:00 | 1546.88 | 30-DEC-17:10 | 92975.47 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.208431E+13 | 0.657515E+12 | 8552.05 | 0.175139E+13 | 0.332914E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.992638E+10 | 0.482699E+10 | 631.61 | 0.841438E+10 | 0.520583E+09 | 0.00 | 0.03 | 0.00 | 5646.73 | 4960.52 | 772.25 | 2489.88 | 0.00 | ||||||
Maximum of Months | 0.822575E+12 | 0.244472E+12 | 744.00 | 0.651515E+12 | 0.171060E+12 | 0.00 | 1.00 | 0.03 | 466744.32 | 408704.20 | 327856.03 | 152282.71 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.461978E+10 | 0.112069E+10 | 744.00 | 0.461060E+10 | 9180820.33 | 0.00 | 0.37 | 22-JAN-16:33 | 0.08 | 05-JAN-07:05 | 3042.82 | 22-JAN-16:35 | 3042.82 | 22-JAN-16:35 | 109.73 | 10-JAN-16:20 | 709.13 | 22-JAN-16:33 | 0.00 |
February | 0.880968E+10 | 0.201890E+10 | 672.00 | 0.880561E+10 | 4067872.61 | 0.00 | 0.58 | 26-FEB-16:52 | 0.32 | 06-FEB-07:10 | 4981.51 | 20-FEB-16:55 | 4981.51 | 20-FEB-16:55 | 89.09 | 28-FEB-16:50 | 1103.43 | 26-FEB-16:52 | 0.00 |
March | 0.153768E+11 | 0.338760E+10 | 744.00 | 0.153652E+11 | 11566670.55 | 0.00 | 0.85 | 31-MAR-24:00 | 0.56 | 20-MAR-06:10 | 7782.98 | 31-MAR-24:00 | 7782.98 | 31-MAR-24:00 | 155.62 | 17-MAR-15:10 | 1883.23 | 13-MAR-17:00 | 0.00 |
April | 0.199722E+11 | 0.421643E+10 | 720.00 | 0.199428E+11 | 29402265.86 | 0.00 | 1.00 | 08-APR-17:42 | 0.30 | 30-APR-24:00 | 8991.88 | 08-APR-18:10 | 8991.88 | 08-APR-18:10 | 258.62 | 28-APR-16:00 | 2177.09 | 19-APR-14:00 | 0.00 |
May | 0.586221E+10 | 0.142365E+10 | 744.00 | 0.580101E+10 | 61199777.86 | 0.00 | 0.47 | 31-MAY-24:00 | 0.19 | 03-MAY-06:10 | 4132.14 | 31-MAY-24:00 | 4109.11 | 31-MAY-24:00 | 220.99 | 22-MAY-14:05 | 902.15 | 31-MAY-24:00 | 0.00 |
June | 0.112183E+11 | 0.309828E+10 | 720.00 | 0.110983E+11 | 0.120053E+09 | 0.00 | 0.72 | 30-JUN-23:15 | 0.44 | 10-JUN-06:40 | 6025.40 | 30-JUN-23:55 | 6025.40 | 30-JUN-23:55 | 413.06 | 20-JUN-17:00 | 2103.84 | 26-JUN-18:00 | 0.00 |
July | 0.166541E+11 | 0.466930E+10 | 744.00 | 0.165018E+11 | 0.152339E+09 | 0.00 | 0.95 | 01-JUL-18:40 | 0.66 | 13-JUL-06:30 | 7902.24 | 31-JUL-24:00 | 7902.24 | 31-JUL-24:00 | 561.69 | 19-JUL-16:00 | 2796.24 | 16-JUL-13:00 | 0.00 |
August | 0.216410E+11 | 0.587797E+10 | 744.00 | 0.215200E+11 | 0.120974E+09 | 0.00 | 1.00 | 02-AUG-15:00 | 0.32 | 31-AUG-24:00 | 9192.87 | 05-AUG-18:53 | 9162.99 | 05-AUG-18:50 | 499.05 | 29-AUG-14:55 | 3236.47 | 16-AUG-16:00 | 0.00 |
September | 0.600000E+10 | 0.158452E+10 | 720.00 | 0.595248E+10 | 47527524.88 | 0.00 | 0.48 | 10-SEP-17:31 | 0.17 | 22-SEP-06:10 | 3971.14 | 30-SEP-24:00 | 3971.14 | 30-SEP-24:00 | 237.49 | 01-SEP-14:40 | 1257.53 | 10-SEP-17:31 | 0.00 |
October | 0.105580E+11 | 0.241256E+10 | 744.00 | 0.105366E+11 | 21457465.26 | 0.00 | 0.66 | 09-OCT-16:41 | 0.35 | 31-OCT-06:10 | 5642.62 | 09-OCT-16:42 | 5642.62 | 09-OCT-16:42 | 141.40 | 03-OCT-11:00 | 1469.49 | 11-OCT-14:00 | 0.00 |
November | 0.148988E+11 | 0.322380E+10 | 720.00 | 0.148840E+11 | 14832313.34 | 0.00 | 0.80 | 07-NOV-16:00 | 0.56 | 01-NOV-06:10 | 7169.29 | 05-NOV-16:13 | 7169.29 | 05-NOV-16:13 | 136.33 | 10-NOV-11:00 | 1775.55 | 07-NOV-16:00 | 0.00 |
December | 0.200011E+11 | 0.431463E+10 | 744.00 | 0.200011E+11 | -0.0 | 0.00 | 0.99 | 03-DEC-16:00 | 0.75 | 23-DEC-07:03 | 8885.43 | 03-DEC-16:00 | 8885.43 | 03-DEC-16:00 | 0.00 | 03-DEC-13:37 | 2251.62 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.155612E+12 | 0.373483E+11 | 8760.00 | 0.155019E+12 | 0.592600E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.461978E+10 | 0.112069E+10 | 672.00 | 0.461060E+10 | -0.0 | 0.00 | 0.37 | 0.08 | 3042.82 | 3042.82 | 0.00 | 709.13 | 0.00 | ||||||
Maximum of Months | 0.216410E+11 | 0.587797E+10 | 744.00 | 0.215200E+11 | 0.152339E+09 | 0.00 | 1.00 | 0.75 | 9192.87 | 9162.99 | 561.69 | 3236.47 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.277421E+11 | 0.696642E+10 | 738.89 | 0.276556E+11 | 86490751.48 | 0.00 | 0.35 | 23-JAN-16:40 | 0.00 | 02-JAN-07:10 | 26846.32 | 23-JAN-16:40 | 26846.32 | 23-JAN-16:40 | 1109.75 | 10-JAN-16:20 | 6276.89 | 23-JAN-16:40 | 0.00 |
February | 0.673604E+11 | 0.157180E+11 | 672.00 | 0.673196E+11 | 40799533.77 | 0.00 | 0.55 | 26-FEB-16:52 | 0.16 | 06-FEB-07:10 | 45223.60 | 17-FEB-17:00 | 44969.26 | 17-FEB-17:00 | 894.26 | 28-FEB-16:50 | 9916.53 | 26-FEB-16:52 | 0.00 |
March | 0.132075E+12 | 0.294889E+11 | 744.00 | 0.131960E+12 | 0.115055E+09 | 0.00 | 0.83 | 31-MAR-23:30 | 0.41 | 20-MAR-06:10 | 72450.11 | 31-MAR-23:30 | 72450.11 | 31-MAR-23:30 | 1550.65 | 17-MAR-15:10 | 17913.28 | 13-MAR-17:00 | 0.00 |
April | 0.177216E+12 | 0.378272E+11 | 720.00 | 0.176922E+12 | 0.293995E+09 | 0.00 | 0.99 | 08-APR-18:00 | 0.15 | 30-APR-24:00 | 85450.95 | 08-APR-18:00 | 85450.95 | 08-APR-18:00 | 2565.07 | 28-APR-16:00 | 20548.44 | 19-APR-14:00 | 0.00 |
May | 0.506960E+11 | 0.124372E+11 | 744.00 | 0.500976E+11 | 0.598482E+09 | 0.00 | 0.47 | 31-MAY-23:30 | 0.09 | 01-MAY-06:10 | 39129.63 | 31-MAY-23:20 | 38777.54 | 31-MAY-24:00 | 2191.38 | 22-MAY-14:05 | 8539.76 | 31-MAY-23:30 | 0.00 |
June | 0.105389E+12 | 0.292236E+11 | 720.00 | 0.104199E+12 | 0.118961E+10 | 0.00 | 0.73 | 30-JUN-23:15 | 0.42 | 10-JUN-06:10 | 58375.40 | 30-JUN-23:55 | 58375.40 | 30-JUN-23:55 | 4033.01 | 20-JUN-17:00 | 20243.55 | 26-JUN-18:10 | 0.00 |
July | 0.157724E+12 | 0.443371E+11 | 744.00 | 0.156211E+12 | 0.151267E+10 | 0.00 | 0.96 | 01-JUL-18:40 | 0.63 | 29-JUL-06:10 | 74695.76 | 31-JUL-24:00 | 74695.76 | 31-JUL-24:00 | 5509.41 | 19-JUL-16:00 | 26554.24 | 16-JUL-13:00 | 0.00 |
August | 0.204834E+12 | 0.558204E+11 | 744.00 | 0.203629E+12 | 0.120470E+10 | 0.00 | 1.00 | 02-AUG-15:50 | 0.28 | 31-AUG-24:00 | 87888.55 | 05-AUG-18:50 | 87609.38 | 05-AUG-18:50 | 4928.57 | 29-AUG-14:55 | 31086.36 | 16-AUG-16:00 | 0.00 |
September | 0.533062E+11 | 0.142227E+11 | 720.00 | 0.528426E+11 | 0.463556E+09 | 0.00 | 0.48 | 10-SEP-17:21 | 0.11 | 22-SEP-06:10 | 36128.31 | 30-SEP-23:50 | 36128.31 | 30-SEP-23:50 | 2327.98 | 01-SEP-14:40 | 12169.73 | 10-SEP-17:21 | 0.00 |
October | 0.897242E+11 | 0.207469E+11 | 744.00 | 0.895129E+11 | 0.211249E+09 | 0.00 | 0.63 | 09-OCT-16:41 | 0.21 | 30-OCT-06:10 | 51250.56 | 08-OCT-16:42 | 51250.56 | 08-OCT-16:42 | 1407.77 | 03-OCT-11:00 | 13861.30 | 11-OCT-14:00 | 0.00 |
November | 0.126754E+12 | 0.278066E+11 | 720.00 | 0.126605E+12 | 0.148703E+09 | 0.00 | 0.79 | 07-NOV-16:00 | 0.45 | 02-NOV-06:10 | 64335.85 | 05-NOV-16:30 | 64276.39 | 07-NOV-16:20 | 1342.96 | 10-NOV-11:00 | 16742.03 | 07-NOV-16:00 | 0.00 |
December | 0.167293E+12 | 0.367329E+11 | 744.00 | 0.167293E+12 | 15686.40 | 0.00 | 0.93 | 03-DEC-16:00 | 0.61 | 26-DEC-04:12 | 79385.82 | 03-DEC-16:05 | 79385.82 | 03-DEC-16:05 | 52.29 | 29-DEC-17:05 | 20833.15 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.136011E+13 | 0.331328E+12 | 8754.89 | 0.135425E+13 | 0.586532E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.277421E+11 | 0.696642E+10 | 672.00 | 0.276556E+11 | 15686.40 | 0.00 | 0.35 | 0.00 | 26846.32 | 26846.32 | 52.29 | 6276.89 | 0.00 | ||||||
Maximum of Months | 0.204834E+12 | 0.558204E+11 | 744.00 | 0.203629E+12 | 0.151267E+10 | 0.00 | 1.00 | 0.63 | 87888.55 | 87609.38 | 5509.41 | 31086.36 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.127862E+10 | 0.328362E+09 | 446.46 | 0.127131E+10 | 7312223.03 | 0.00 | 0.33 | 20-JAN-16:30 | 0.00 | 01-JAN-00:03 | 2653.31 | 20-JAN-16:30 | 2653.31 | 20-JAN-16:30 | 110.89 | 10-JAN-16:20 | 614.54 | 20-JAN-16:30 | 0.00 |
February | 0.520467E+10 | 0.123464E+10 | 660.08 | 0.520068E+10 | 3988353.98 | 0.00 | 0.53 | 17-FEB-17:00 | 0.00 | 05-FEB-01:53 | 4515.86 | 17-FEB-17:00 | 4493.38 | 17-FEB-17:00 | 88.51 | 28-FEB-16:50 | 980.07 | 17-FEB-17:00 | 0.00 |
March | 0.119070E+11 | 0.269103E+10 | 744.00 | 0.118956E+11 | 11329614.80 | 0.00 | 0.81 | 13-MAR-17:10 | 0.23 | 20-MAR-03:11 | 7069.73 | 31-MAR-23:20 | 7069.73 | 31-MAR-23:20 | 155.06 | 17-MAR-15:10 | 1812.82 | 13-MAR-17:00 | 0.00 |
April | 0.164140E+11 | 0.354470E+10 | 719.00 | 0.163847E+11 | 29297713.15 | 0.00 | 0.98 | 08-APR-18:00 | 0.00 | 30-APR-23:10 | 8615.33 | 08-APR-18:00 | 8615.33 | 08-APR-18:00 | 257.17 | 28-APR-16:00 | 2087.60 | 19-APR-14:00 | 0.00 |
May | 0.460847E+10 | 0.114324E+10 | 734.69 | 0.454888E+10 | 59585879.05 | 0.00 | 0.45 | 31-MAY-23:20 | 0.00 | 01-MAY-00:10 | 3869.09 | 31-MAY-23:20 | 3822.17 | 31-MAY-23:40 | 219.29 | 22-MAY-14:00 | 881.94 | 31-MAY-16:00 | 0.00 |
June | 0.105616E+11 | 0.294391E+10 | 720.00 | 0.104425E+11 | 0.119075E+09 | 0.00 | 0.72 | 30-JUN-23:15 | 0.38 | 10-JUN-06:10 | 5841.13 | 30-JUN-23:55 | 5841.13 | 30-JUN-23:55 | 406.95 | 20-JUN-17:00 | 2079.84 | 26-JUN-18:00 | 0.00 |
July | 0.158126E+11 | 0.446423E+10 | 744.00 | 0.156613E+11 | 0.151252E+09 | 0.00 | 0.96 | 01-JUL-18:40 | 0.60 | 29-JUL-06:10 | 7385.85 | 31-JUL-24:00 | 7385.85 | 31-JUL-24:00 | 553.52 | 19-JUL-16:00 | 2746.44 | 16-JUL-15:00 | 0.00 |
August | 0.204828E+11 | 0.560758E+10 | 744.00 | 0.203625E+11 | 0.120346E+09 | 0.00 | 1.00 | 05-AUG-18:11 | 0.27 | 31-AUG-24:00 | 8914.53 | 13-AUG-19:02 | 8914.53 | 13-AUG-19:02 | 493.82 | 29-AUG-14:55 | 3171.69 | 16-AUG-16:00 | 0.00 |
September | 0.507558E+10 | 0.137157E+10 | 719.08 | 0.502932E+10 | 46251368.28 | 0.00 | 0.51 | 10-SEP-17:21 | 0.00 | 22-SEP-01:05 | 3775.22 | 10-SEP-17:32 | 3775.22 | 10-SEP-17:32 | 234.93 | 01-SEP-14:40 | 1318.47 | 10-SEP-17:21 | 0.00 |
October | 0.767870E+10 | 0.180120E+10 | 743.92 | 0.765796E+10 | 20741265.90 | 0.00 | 0.62 | 09-OCT-16:52 | 0.00 | 29-OCT-18:33 | 5142.45 | 08-OCT-16:42 | 5142.45 | 08-OCT-16:42 | 143.62 | 03-OCT-11:00 | 1408.46 | 11-OCT-14:00 | 0.00 |
November | 0.110144E+11 | 0.245516E+10 | 720.00 | 0.109997E+11 | 14646163.25 | 0.00 | 0.78 | 07-NOV-16:00 | 0.33 | 30-NOV-04:20 | 6451.93 | 07-NOV-16:20 | 6451.93 | 07-NOV-16:20 | 132.24 | 10-NOV-11:00 | 1684.59 | 07-NOV-16:00 | 0.00 |
December | 0.148553E+11 | 0.331258E+10 | 744.00 | 0.148553E+11 | 146.91 | 0.00 | 0.90 | 01-DEC-15:50 | 0.46 | 25-DEC-07:10 | 7827.57 | 01-DEC-16:00 | 7827.57 | 01-DEC-16:00 | 0.49 | 29-DEC-17:05 | 2056.49 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.124894E+12 | 0.308982E+11 | 8439.23 | 0.124310E+12 | 0.583825E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.127862E+10 | 0.328362E+09 | 446.46 | 0.127131E+10 | 146.91 | 0.00 | 0.33 | 0.00 | 2653.31 | 2653.31 | 0.49 | 614.54 | 0.00 | ||||||
Maximum of Months | 0.204828E+11 | 0.560758E+10 | 744.00 | 0.203625E+11 | 0.151252E+09 | 0.00 | 1.00 | 0.60 | 8914.53 | 8914.53 | 553.52 | 3171.69 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.60 | 729.93 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 24.35 | 732.94 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 92.47 | 563.91 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 145.62 | 496.12 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 351.87 | 275.26 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 578.01 | 149.24 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 552.38 | 140.77 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 417.94 | 162.86 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 308.10 | 254.44 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 99.67 | 545.47 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.63 | 667.78 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.42 | 826.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 220.77 | 460.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.42 | 140.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 578.01 | 826.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.60 | 729.93 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 24.35 | 732.94 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 92.47 | 563.91 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 145.62 | 496.12 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 351.87 | 275.26 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 578.01 | 149.24 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 552.38 | 140.77 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 417.94 | 162.86 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 308.10 | 254.44 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 99.67 | 545.47 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.63 | 667.78 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.42 | 826.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 220.77 | 460.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.42 | 140.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 578.01 | 826.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.60 | 729.93 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 24.35 | 732.94 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 92.47 | 563.91 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 145.62 | 496.12 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 351.87 | 275.26 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 578.01 | 149.24 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 552.38 | 140.77 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 417.94 | 162.86 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 308.10 | 254.44 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 99.67 | 545.47 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.63 | 667.78 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.42 | 826.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 220.77 | 460.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.42 | 140.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 578.01 | 826.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.60 | 729.93 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 24.35 | 732.94 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 92.47 | 563.91 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 145.62 | 496.12 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 351.87 | 275.26 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 578.01 | 149.24 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 552.38 | 140.77 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 417.94 | 162.86 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 308.10 | 254.44 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 99.67 | 545.47 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.63 | 667.78 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.42 | 826.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 220.77 | 460.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.42 | 140.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 578.01 | 826.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.60 | 729.90 | 0.00 | 0.00 | 0.00 |
February | 171.62 | 0.00 | 171.62 | 24.35 | 732.91 | 0.00 | 0.00 | 0.00 |
March | 233.52 | 0.00 | 233.52 | 92.47 | 563.89 | 0.00 | 0.00 | 0.00 |
April | 293.27 | 1.63 | 291.64 | 145.61 | 496.10 | 0.00 | 0.00 | 0.00 |
May | 400.62 | 13.24 | 387.38 | 351.86 | 275.25 | 0.00 | 0.00 | 0.00 |
June | 439.31 | 48.70 | 390.60 | 577.98 | 149.23 | 0.00 | 0.00 | 0.00 |
July | 415.47 | 26.89 | 388.57 | 552.35 | 140.76 | 0.00 | 0.00 | 0.00 |
August | 330.68 | 7.82 | 322.86 | 417.92 | 162.86 | 0.00 | 0.00 | 0.00 |
September | 277.77 | 0.07 | 277.71 | 308.09 | 254.43 | 0.00 | 0.00 | 0.00 |
October | 198.95 | 0.00 | 198.95 | 99.66 | 545.44 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.62 | 667.76 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.42 | 826.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.20 | 8.22 | 256.98 | 220.76 | 460.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.42 | 140.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.31 | 48.70 | 390.60 | 577.98 | 826.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.09 | 291.15 | 183.94 | 407.10 | 751.90 | 0.00 | 0.00 | 0.00 |
February | 631.10 | 398.41 | 232.69 | 582.23 | 767.43 | 0.00 | 0.00 | 0.00 |
March | 761.72 | 444.31 | 317.42 | 759.80 | 588.56 | 0.00 | 0.00 | 0.00 |
April | 781.19 | 380.53 | 400.66 | 761.95 | 520.51 | 0.00 | 0.00 | 0.00 |
May | 913.20 | 381.45 | 531.75 | 1025.15 | 305.56 | 0.00 | 0.00 | 0.00 |
June | 1114.19 | 584.92 | 529.27 | 1491.32 | 164.61 | 0.00 | 0.00 | 0.00 |
July | 1012.89 | 482.31 | 530.58 | 1367.60 | 153.36 | 0.00 | 0.00 | 0.00 |
August | 1021.64 | 562.68 | 458.96 | 1370.89 | 175.17 | 0.00 | 0.00 | 0.00 |
September | 850.05 | 461.77 | 388.28 | 1078.37 | 269.34 | 0.00 | 0.00 | 0.00 |
October | 615.61 | 337.32 | 278.29 | 637.75 | 582.91 | 0.00 | 0.00 | 0.00 |
November | 479.17 | 270.55 | 208.63 | 436.07 | 697.50 | 0.00 | 0.00 | 0.00 |
December | 414.84 | 238.97 | 175.86 | 338.25 | 848.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.37 | 402.66 | 353.70 | 855.99 | 483.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.84 | 238.97 | 175.86 | 338.25 | 153.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1114.19 | 584.92 | 531.75 | 1491.32 | 848.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.09 | 291.15 | 183.94 | 407.10 | 751.90 | 0.00 | 0.00 | 0.00 |
February | 631.10 | 398.41 | 232.69 | 582.23 | 767.43 | 0.00 | 0.00 | 0.00 |
March | 761.72 | 444.31 | 317.42 | 759.80 | 588.56 | 0.00 | 0.00 | 0.00 |
April | 781.19 | 380.53 | 400.66 | 761.95 | 520.51 | 0.00 | 0.00 | 0.00 |
May | 913.20 | 381.45 | 531.75 | 1025.15 | 305.56 | 0.00 | 0.00 | 0.00 |
June | 1114.19 | 584.92 | 529.27 | 1491.32 | 164.61 | 0.00 | 0.00 | 0.00 |
July | 1012.89 | 482.31 | 530.58 | 1367.60 | 153.36 | 0.00 | 0.00 | 0.00 |
August | 1021.64 | 562.68 | 458.96 | 1370.89 | 175.17 | 0.00 | 0.00 | 0.00 |
September | 850.05 | 461.77 | 388.28 | 1078.37 | 269.34 | 0.00 | 0.00 | 0.00 |
October | 615.61 | 337.32 | 278.29 | 637.75 | 582.91 | 0.00 | 0.00 | 0.00 |
November | 479.17 | 270.55 | 208.63 | 436.07 | 697.50 | 0.00 | 0.00 | 0.00 |
December | 414.84 | 238.97 | 175.86 | 338.25 | 848.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.37 | 402.66 | 353.70 | 855.99 | 483.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.84 | 238.97 | 175.86 | 338.25 | 153.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1114.19 | 584.92 | 531.75 | 1491.32 | 848.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.08 | 291.14 | 183.94 | 407.10 | 751.88 | 0.00 | 0.00 | 0.00 |
February | 631.09 | 398.40 | 232.69 | 582.22 | 767.42 | 0.00 | 0.00 | 0.00 |
March | 761.71 | 444.30 | 317.41 | 759.79 | 588.55 | 0.00 | 0.00 | 0.00 |
April | 781.17 | 380.52 | 400.65 | 761.93 | 520.51 | 0.00 | 0.00 | 0.00 |
May | 913.18 | 381.44 | 531.74 | 1025.13 | 305.55 | 0.00 | 0.00 | 0.00 |
June | 1114.17 | 584.91 | 529.26 | 1491.29 | 164.61 | 0.00 | 0.00 | 0.00 |
July | 1012.87 | 482.30 | 530.57 | 1367.58 | 153.36 | 0.00 | 0.00 | 0.00 |
August | 1021.62 | 562.67 | 458.95 | 1370.87 | 175.17 | 0.00 | 0.00 | 0.00 |
September | 850.04 | 461.77 | 388.27 | 1078.35 | 269.33 | 0.00 | 0.00 | 0.00 |
October | 615.60 | 337.31 | 278.29 | 637.74 | 582.90 | 0.00 | 0.00 | 0.00 |
November | 479.16 | 270.54 | 208.62 | 436.06 | 697.48 | 0.00 | 0.00 | 0.00 |
December | 414.83 | 238.97 | 175.86 | 338.24 | 848.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.35 | 402.66 | 353.69 | 855.97 | 483.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.83 | 238.97 | 175.86 | 338.24 | 153.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1114.17 | 584.91 | 531.74 | 1491.29 | 848.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1483.99 | 635.78 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1413.22 | 659.70 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1053.08 | 532.05 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 617.48 | 487.18 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 620.60 | 296.88 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 724.79 | 163.61 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 755.85 | 151.08 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 968.52 | 172.05 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1170.60 | 259.34 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1243.70 | 524.14 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1458.92 | 608.99 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.32 | 1333.85 | 717.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1068.41 | 432.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.32 | 617.48 | 151.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1483.99 | 717.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1483.99 | 635.78 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1413.21 | 659.70 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1053.08 | 532.05 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 617.48 | 487.18 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 620.60 | 296.88 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 724.79 | 163.61 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 755.85 | 151.08 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 968.52 | 172.05 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1170.60 | 259.34 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1243.70 | 524.14 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1458.92 | 608.99 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.31 | 1333.84 | 717.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1068.41 | 432.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.31 | 617.48 | 151.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1483.99 | 717.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1483.99 | 635.78 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1413.22 | 659.70 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1053.08 | 532.05 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 617.48 | 487.18 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 620.60 | 296.88 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 724.79 | 163.61 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 755.85 | 151.08 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 968.52 | 172.05 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1170.60 | 259.34 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1243.70 | 524.14 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1458.92 | 608.99 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.32 | 1333.85 | 717.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1068.41 | 432.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.32 | 617.48 | 151.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1483.99 | 717.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1483.99 | 635.78 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1413.21 | 659.70 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1053.08 | 532.05 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 617.48 | 487.18 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 620.60 | 296.88 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 724.79 | 163.61 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 755.85 | 151.08 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 968.52 | 172.05 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1170.60 | 259.34 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1243.70 | 524.14 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1458.92 | 608.99 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.31 | 1333.84 | 717.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1068.41 | 432.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.31 | 617.48 | 151.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1483.99 | 717.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.63 | 1076.49 | 232.14 | 1483.93 | 635.76 | 0.00 | 0.00 | 0.00 |
February | 1255.22 | 1000.74 | 254.48 | 1413.16 | 659.67 | 0.00 | 0.00 | 0.00 |
March | 925.44 | 608.89 | 316.55 | 1053.04 | 532.03 | 0.00 | 0.00 | 0.00 |
April | 599.39 | 241.02 | 358.37 | 617.46 | 487.16 | 0.00 | 0.00 | 0.00 |
May | 549.27 | 100.68 | 448.59 | 620.57 | 296.87 | 0.00 | 0.00 | 0.00 |
June | 506.41 | 92.56 | 413.85 | 724.76 | 163.61 | 0.00 | 0.00 | 0.00 |
July | 527.16 | 94.40 | 432.76 | 755.82 | 151.07 | 0.00 | 0.00 | 0.00 |
August | 671.18 | 280.58 | 390.60 | 968.48 | 172.04 | 0.00 | 0.00 | 0.00 |
September | 863.54 | 481.85 | 381.69 | 1170.55 | 259.33 | 0.00 | 0.00 | 0.00 |
October | 1032.55 | 732.61 | 299.93 | 1243.65 | 524.12 | 0.00 | 0.00 | 0.00 |
November | 1258.01 | 1002.82 | 255.19 | 1458.86 | 608.97 | 0.00 | 0.00 | 0.00 |
December | 1202.99 | 973.68 | 229.31 | 1333.79 | 717.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.59 | 554.67 | 334.92 | 1068.37 | 432.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.41 | 92.56 | 229.31 | 617.46 | 151.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.63 | 1076.49 | 448.59 | 1483.93 | 717.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.39 | 320.24 | 185.15 | 462.44 | 808.89 | 0.00 | 0.00 | 0.00 |
February | 609.43 | 377.66 | 231.76 | 555.00 | 835.58 | 0.00 | 0.00 | 0.00 |
March | 713.60 | 393.71 | 319.89 | 689.48 | 665.82 | 0.00 | 0.00 | 0.00 |
April | 671.88 | 284.46 | 387.42 | 612.82 | 608.38 | 0.00 | 0.00 | 0.00 |
May | 821.22 | 289.51 | 531.71 | 910.95 | 347.92 | 0.00 | 0.00 | 0.00 |
June | 1004.40 | 483.25 | 521.14 | 1345.78 | 209.59 | 0.00 | 0.00 | 0.00 |
July | 818.35 | 299.74 | 518.60 | 1091.75 | 198.10 | 0.00 | 0.00 | 0.00 |
August | 854.12 | 421.95 | 432.17 | 1121.24 | 227.50 | 0.00 | 0.00 | 0.00 |
September | 757.35 | 363.20 | 394.15 | 957.74 | 310.59 | 0.00 | 0.00 | 0.00 |
October | 637.13 | 364.17 | 272.96 | 671.09 | 642.12 | 0.00 | 0.00 | 0.00 |
November | 522.80 | 317.40 | 205.40 | 487.31 | 776.26 | 0.00 | 0.00 | 0.00 |
December | 422.28 | 249.45 | 172.83 | 343.11 | 947.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.04 | 346.65 | 348.40 | 771.62 | 546.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 422.28 | 249.45 | 172.83 | 343.11 | 198.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1004.40 | 483.25 | 531.71 | 1345.78 | 947.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.39 | 320.24 | 185.15 | 462.44 | 808.89 | 0.00 | 0.00 | 0.00 |
February | 609.43 | 377.66 | 231.76 | 555.00 | 835.58 | 0.00 | 0.00 | 0.00 |
March | 713.60 | 393.71 | 319.89 | 689.48 | 665.82 | 0.00 | 0.00 | 0.00 |
April | 671.88 | 284.46 | 387.42 | 612.82 | 608.38 | 0.00 | 0.00 | 0.00 |
May | 821.22 | 289.51 | 531.71 | 910.95 | 347.92 | 0.00 | 0.00 | 0.00 |
June | 1004.40 | 483.25 | 521.14 | 1345.78 | 209.59 | 0.00 | 0.00 | 0.00 |
July | 818.35 | 299.74 | 518.60 | 1091.75 | 198.10 | 0.00 | 0.00 | 0.00 |
August | 854.12 | 421.95 | 432.17 | 1121.24 | 227.50 | 0.00 | 0.00 | 0.00 |
September | 757.35 | 363.20 | 394.15 | 957.74 | 310.59 | 0.00 | 0.00 | 0.00 |
October | 637.13 | 364.17 | 272.96 | 671.09 | 642.12 | 0.00 | 0.00 | 0.00 |
November | 522.80 | 317.40 | 205.40 | 487.31 | 776.26 | 0.00 | 0.00 | 0.00 |
December | 422.28 | 249.45 | 172.83 | 343.11 | 947.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.04 | 346.65 | 348.40 | 771.62 | 546.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 422.28 | 249.45 | 172.83 | 343.11 | 198.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1004.40 | 483.25 | 531.71 | 1345.78 | 947.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.38 | 320.23 | 185.14 | 462.43 | 808.87 | 0.00 | 0.00 | 0.00 |
February | 609.41 | 377.66 | 231.76 | 554.99 | 835.57 | 0.00 | 0.00 | 0.00 |
March | 713.58 | 393.70 | 319.88 | 689.47 | 665.81 | 0.00 | 0.00 | 0.00 |
April | 671.87 | 284.46 | 387.41 | 612.81 | 608.36 | 0.00 | 0.00 | 0.00 |
May | 821.20 | 289.50 | 531.70 | 910.93 | 347.92 | 0.00 | 0.00 | 0.00 |
June | 1004.38 | 483.25 | 521.13 | 1345.75 | 209.58 | 0.00 | 0.00 | 0.00 |
July | 818.33 | 299.74 | 518.59 | 1091.73 | 198.10 | 0.00 | 0.00 | 0.00 |
August | 854.10 | 421.94 | 432.16 | 1121.22 | 227.50 | 0.00 | 0.00 | 0.00 |
September | 757.34 | 363.19 | 394.14 | 957.73 | 310.58 | 0.00 | 0.00 | 0.00 |
October | 637.12 | 364.16 | 272.96 | 671.08 | 642.11 | 0.00 | 0.00 | 0.00 |
November | 522.79 | 317.40 | 205.39 | 487.30 | 776.25 | 0.00 | 0.00 | 0.00 |
December | 422.27 | 249.45 | 172.82 | 343.10 | 947.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.03 | 346.64 | 348.39 | 771.61 | 546.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 422.27 | 249.45 | 172.82 | 343.10 | 198.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1004.38 | 483.25 | 531.70 | 1345.75 | 947.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 682.75 | 0.00 | 682.75 | 127.61 | 3322.53 | 0.00 | 0.00 | 0.00 |
February | 858.13 | 0.00 | 858.13 | 168.19 | 3328.40 | 0.00 | 0.00 | 0.00 |
March | 1167.63 | 0.00 | 1167.63 | 532.17 | 2535.85 | 0.00 | 0.00 | 0.00 |
April | 1466.38 | 8.13 | 1458.24 | 799.03 | 2186.98 | 0.00 | 0.00 | 0.00 |
May | 2003.16 | 66.22 | 1936.94 | 1790.65 | 1308.16 | 0.00 | 0.00 | 0.00 |
June | 2196.60 | 243.53 | 1953.07 | 2906.25 | 722.33 | 0.00 | 0.00 | 0.00 |
July | 2077.39 | 134.47 | 1942.92 | 2781.32 | 683.12 | 0.00 | 0.00 | 0.00 |
August | 1653.44 | 39.11 | 1614.33 | 2118.19 | 779.02 | 0.00 | 0.00 | 0.00 |
September | 1388.89 | 0.33 | 1388.57 | 1569.21 | 1203.42 | 0.00 | 0.00 | 0.00 |
October | 994.78 | 0.00 | 994.78 | 548.28 | 2500.82 | 0.00 | 0.00 | 0.00 |
November | 755.17 | 0.00 | 755.17 | 214.48 | 2993.90 | 0.00 | 0.00 | 0.00 |
December | 638.79 | 0.00 | 638.79 | 114.79 | 3687.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1326.01 | 41.08 | 1284.94 | 1144.61 | 2097.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 638.79 | 0.00 | 638.79 | 114.79 | 683.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2196.60 | 243.53 | 1953.07 | 2906.25 | 3687.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1425.25 | 873.44 | 551.81 | 1241.33 | 2119.23 | 0.00 | 0.00 | 0.00 |
February | 1893.28 | 1195.22 | 698.06 | 1751.84 | 2162.78 | 0.00 | 0.00 | 0.00 |
March | 2285.14 | 1332.90 | 952.24 | 2279.04 | 1653.68 | 0.00 | 0.00 | 0.00 |
April | 2343.54 | 1141.58 | 1201.96 | 2286.86 | 1441.09 | 0.00 | 0.00 | 0.00 |
May | 2739.56 | 1144.32 | 1595.23 | 3056.87 | 892.68 | 0.00 | 0.00 | 0.00 |
June | 3342.54 | 1754.75 | 1587.80 | 4444.06 | 491.64 | 0.00 | 0.00 | 0.00 |
July | 3038.64 | 1446.92 | 1591.71 | 4073.15 | 466.87 | 0.00 | 0.00 | 0.00 |
August | 3064.88 | 1688.03 | 1376.85 | 4084.15 | 533.16 | 0.00 | 0.00 | 0.00 |
September | 2550.14 | 1385.31 | 1164.83 | 3216.13 | 787.95 | 0.00 | 0.00 | 0.00 |
October | 1846.81 | 1011.94 | 834.86 | 1908.23 | 1658.41 | 0.00 | 0.00 | 0.00 |
November | 1437.50 | 811.63 | 625.87 | 1323.16 | 1960.53 | 0.00 | 0.00 | 0.00 |
December | 1244.49 | 716.92 | 527.58 | 1040.06 | 2358.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.07 | 1207.98 | 1061.09 | 2562.53 | 1372.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1244.49 | 716.92 | 527.58 | 1040.06 | 466.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3342.54 | 1754.75 | 1595.23 | 4444.06 | 2358.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6543.34 | 5382.60 | 1160.74 | 7372.75 | 3147.40 | 0.00 | 0.00 | 0.00 |
February | 6276.27 | 5003.84 | 1272.43 | 7012.50 | 3220.38 | 0.00 | 0.00 | 0.00 |
March | 4627.35 | 3044.54 | 1582.82 | 5240.86 | 2554.94 | 0.00 | 0.00 | 0.00 |
April | 2997.02 | 1205.11 | 1791.90 | 3093.15 | 2285.31 | 0.00 | 0.00 | 0.00 |
May | 2746.44 | 503.40 | 2243.03 | 3096.87 | 1448.27 | 0.00 | 0.00 | 0.00 |
June | 2532.12 | 462.80 | 2069.32 | 3624.71 | 794.99 | 0.00 | 0.00 | 0.00 |
July | 2635.88 | 472.01 | 2163.87 | 3780.91 | 739.11 | 0.00 | 0.00 | 0.00 |
August | 3356.01 | 1402.94 | 1953.07 | 4833.82 | 840.77 | 0.00 | 0.00 | 0.00 |
September | 4317.84 | 2409.33 | 1908.51 | 5821.22 | 1273.70 | 0.00 | 0.00 | 0.00 |
October | 5162.87 | 3663.18 | 1499.70 | 6181.14 | 2561.38 | 0.00 | 0.00 | 0.00 |
November | 6290.24 | 5014.23 | 1276.01 | 7251.80 | 2975.44 | 0.00 | 0.00 | 0.00 |
December | 6015.11 | 4868.55 | 1146.56 | 6647.93 | 3455.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4448.08 | 2773.44 | 1674.64 | 5320.16 | 2101.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2532.12 | 462.80 | 1146.56 | 3093.15 | 739.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6543.34 | 5382.60 | 2243.03 | 7372.75 | 3455.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1516.15 | 960.71 | 555.43 | 1421.49 | 2211.74 | 0.00 | 0.00 | 0.00 |
February | 1828.26 | 1132.98 | 695.28 | 1705.61 | 2236.62 | 0.00 | 0.00 | 0.00 |
March | 2140.77 | 1181.11 | 959.66 | 2119.07 | 1734.61 | 0.00 | 0.00 | 0.00 |
April | 2015.63 | 853.39 | 1162.25 | 1899.42 | 1523.42 | 0.00 | 0.00 | 0.00 |
May | 2463.62 | 868.52 | 1595.10 | 2752.33 | 974.06 | 0.00 | 0.00 | 0.00 |
June | 3013.16 | 1449.75 | 1563.41 | 4058.28 | 575.59 | 0.00 | 0.00 | 0.00 |
July | 2455.01 | 899.23 | 1555.79 | 3311.92 | 528.09 | 0.00 | 0.00 | 0.00 |
August | 2562.34 | 1265.83 | 1296.51 | 3410.38 | 591.90 | 0.00 | 0.00 | 0.00 |
September | 2272.02 | 1089.59 | 1182.44 | 2889.46 | 867.53 | 0.00 | 0.00 | 0.00 |
October | 1911.37 | 1092.49 | 818.88 | 2044.72 | 1727.65 | 0.00 | 0.00 | 0.00 |
November | 1568.38 | 952.20 | 616.18 | 1512.79 | 2031.94 | 0.00 | 0.00 | 0.00 |
December | 1266.83 | 748.35 | 518.48 | 1086.77 | 2422.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2085.11 | 1039.93 | 1045.18 | 2353.71 | 1447.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1266.83 | 748.35 | 518.48 | 1086.77 | 528.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3013.16 | 1449.75 | 1595.10 | 4058.28 | 2422.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 682.75 | 0.00 | 682.75 | 155.37 | 3093.61 | 0.00 | 0.00 | 0.00 |
February | 858.13 | 0.00 | 858.13 | 191.35 | 3156.84 | 0.00 | 0.00 | 0.00 |
March | 1167.63 | 0.00 | 1167.63 | 558.23 | 2397.69 | 0.00 | 0.00 | 0.00 |
April | 1466.38 | 8.13 | 1458.24 | 830.58 | 2024.83 | 0.00 | 0.00 | 0.00 |
May | 2003.16 | 66.22 | 1936.94 | 1818.58 | 1253.62 | 0.00 | 0.00 | 0.00 |
June | 2196.60 | 243.53 | 1953.07 | 2888.63 | 716.54 | 0.00 | 0.00 | 0.00 |
July | 2077.39 | 134.47 | 1942.92 | 2763.11 | 680.78 | 0.00 | 0.00 | 0.00 |
August | 1653.44 | 39.11 | 1614.33 | 2105.84 | 769.31 | 0.00 | 0.00 | 0.00 |
September | 1388.89 | 0.33 | 1388.57 | 1574.29 | 1161.94 | 0.00 | 0.00 | 0.00 |
October | 994.78 | 0.00 | 994.78 | 582.06 | 2337.16 | 0.00 | 0.00 | 0.00 |
November | 755.17 | 0.00 | 755.17 | 248.21 | 2787.46 | 0.00 | 0.00 | 0.00 |
December | 638.79 | 0.00 | 638.79 | 131.29 | 3503.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1326.01 | 41.08 | 1284.94 | 1159.34 | 1984.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 638.79 | 0.00 | 638.79 | 131.29 | 680.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2196.60 | 243.53 | 1953.07 | 2888.63 | 3503.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1425.25 | 873.44 | 551.81 | 1281.85 | 1962.91 | 0.00 | 0.00 | 0.00 |
February | 1893.28 | 1195.22 | 698.06 | 1777.61 | 2051.11 | 0.00 | 0.00 | 0.00 |
March | 2285.14 | 1332.90 | 952.24 | 2300.31 | 1568.28 | 0.00 | 0.00 | 0.00 |
April | 2343.54 | 1141.58 | 1201.96 | 2308.95 | 1338.37 | 0.00 | 0.00 | 0.00 |
May | 2739.56 | 1144.32 | 1595.23 | 3072.15 | 859.99 | 0.00 | 0.00 | 0.00 |
June | 3342.54 | 1754.75 | 1587.80 | 4435.34 | 487.69 | 0.00 | 0.00 | 0.00 |
July | 3038.64 | 1446.92 | 1591.71 | 4064.27 | 464.59 | 0.00 | 0.00 | 0.00 |
August | 3064.88 | 1688.03 | 1376.85 | 4078.33 | 526.77 | 0.00 | 0.00 | 0.00 |
September | 2550.14 | 1385.31 | 1164.83 | 3219.86 | 765.17 | 0.00 | 0.00 | 0.00 |
October | 1846.81 | 1011.94 | 834.86 | 1928.60 | 1560.33 | 0.00 | 0.00 | 0.00 |
November | 1437.50 | 811.63 | 625.87 | 1358.32 | 1825.40 | 0.00 | 0.00 | 0.00 |
December | 1244.49 | 716.92 | 527.58 | 1069.15 | 2237.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.07 | 1207.98 | 1061.09 | 2578.31 | 1300.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1244.49 | 716.92 | 527.58 | 1069.15 | 464.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3342.54 | 1754.75 | 1595.23 | 4435.34 | 2237.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6543.34 | 5382.60 | 1160.74 | 7438.84 | 2934.39 | 0.00 | 0.00 | 0.00 |
February | 6276.27 | 5003.84 | 1272.43 | 7048.53 | 3055.89 | 0.00 | 0.00 | 0.00 |
March | 4627.35 | 3044.54 | 1582.82 | 5264.25 | 2421.13 | 0.00 | 0.00 | 0.00 |
April | 2997.02 | 1205.11 | 1791.90 | 3117.89 | 2122.69 | 0.00 | 0.00 | 0.00 |
May | 2746.44 | 503.40 | 2243.03 | 3111.84 | 1388.18 | 0.00 | 0.00 | 0.00 |
June | 2532.12 | 462.80 | 2069.32 | 3605.95 | 786.69 | 0.00 | 0.00 | 0.00 |
July | 2635.88 | 472.01 | 2163.87 | 3761.52 | 734.78 | 0.00 | 0.00 | 0.00 |
August | 3356.01 | 1402.94 | 1953.07 | 4817.16 | 830.08 | 0.00 | 0.00 | 0.00 |
September | 4317.84 | 2409.33 | 1908.51 | 5816.35 | 1236.03 | 0.00 | 0.00 | 0.00 |
October | 5162.87 | 3663.18 | 1499.70 | 6206.02 | 2413.25 | 0.00 | 0.00 | 0.00 |
November | 6290.24 | 5014.23 | 1276.01 | 7295.82 | 2797.02 | 0.00 | 0.00 | 0.00 |
December | 6015.11 | 4868.55 | 1146.56 | 6692.10 | 3272.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4448.08 | 2773.44 | 1674.64 | 5338.31 | 1993.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2532.12 | 462.80 | 1146.56 | 3111.84 | 734.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6543.34 | 5382.60 | 2243.03 | 7438.84 | 3272.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1516.15 | 960.71 | 555.43 | 1446.96 | 2070.11 | 0.00 | 0.00 | 0.00 |
February | 1828.26 | 1132.98 | 695.28 | 1719.53 | 2133.77 | 0.00 | 0.00 | 0.00 |
March | 2140.77 | 1181.11 | 959.66 | 2130.86 | 1649.93 | 0.00 | 0.00 | 0.00 |
April | 2015.63 | 853.39 | 1162.25 | 1913.80 | 1424.00 | 0.00 | 0.00 | 0.00 |
May | 2463.62 | 868.52 | 1595.10 | 2757.93 | 938.68 | 0.00 | 0.00 | 0.00 |
June | 3013.16 | 1449.75 | 1563.41 | 4043.39 | 568.56 | 0.00 | 0.00 | 0.00 |
July | 2455.01 | 899.23 | 1555.79 | 3297.90 | 523.47 | 0.00 | 0.00 | 0.00 |
August | 2562.34 | 1265.83 | 1296.51 | 3398.54 | 584.05 | 0.00 | 0.00 | 0.00 |
September | 2272.02 | 1089.59 | 1182.44 | 2887.11 | 842.30 | 0.00 | 0.00 | 0.00 |
October | 1911.37 | 1092.49 | 818.88 | 2059.72 | 1635.06 | 0.00 | 0.00 | 0.00 |
November | 1568.38 | 952.20 | 616.18 | 1533.33 | 1916.80 | 0.00 | 0.00 | 0.00 |
December | 1266.83 | 748.35 | 518.48 | 1101.36 | 2311.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2085.11 | 1039.93 | 1045.18 | 2360.18 | 1379.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1266.83 | 748.35 | 518.48 | 1101.36 | 523.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3013.16 | 1449.75 | 1595.10 | 4043.39 | 2311.88 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 49829812.40 | 0.195505E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 58915069.91 | 0.177313E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.247671E+09 | 0.151038E+10 |
April | 0.760179E+09 | 4217145.19 | 0.755962E+09 | 0.377448E+09 | 0.128595E+10 |
May | 0.107307E+10 | 35471222.39 | 0.103759E+10 | 0.942460E+09 | 0.737266E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101249E+10 | 0.149819E+10 | 0.386820E+09 |
July | 0.111283E+10 | 72035381.25 | 0.104079E+10 | 0.147948E+10 | 0.377038E+09 |
August | 0.885727E+09 | 20953327.99 | 0.864774E+09 | 0.111941E+10 | 0.436210E+09 |
September | 0.720011E+09 | 169117.77 | 0.719842E+09 | 0.798600E+09 | 0.659498E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.266948E+09 | 0.146098E+10 |
November | 0.391483E+09 | 0.00 | 0.391483E+09 | 84565694.70 | 0.173089E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611928.01 | 0.221287E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.696213E+10 | 0.145261E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611928.01 | 0.377038E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.149819E+10 | 0.221287E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 49829710.08 | 0.195505E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 58914965.84 | 0.177313E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.247671E+09 | 0.151038E+10 |
April | 0.760178E+09 | 4217140.13 | 0.755961E+09 | 0.377448E+09 | 0.128595E+10 |
May | 0.107306E+10 | 35471179.83 | 0.103759E+10 | 0.942459E+09 | 0.737266E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101248E+10 | 0.149819E+10 | 0.386820E+09 |
July | 0.111283E+10 | 72035294.82 | 0.104079E+10 | 0.147948E+10 | 0.377038E+09 |
August | 0.885727E+09 | 20953302.84 | 0.864773E+09 | 0.111941E+10 | 0.436210E+09 |
September | 0.720010E+09 | 169117.57 | 0.719841E+09 | 0.798599E+09 | 0.659498E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.266948E+09 | 0.146098E+10 |
November | 0.391482E+09 | 0.00 | 0.391482E+09 | 84565575.44 | 0.173089E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611867.45 | 0.221287E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.696213E+10 | 0.145261E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611867.45 | 0.377038E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.149819E+10 | 0.221287E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 49829812.40 | 0.195505E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 58915069.91 | 0.177313E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.247671E+09 | 0.151038E+10 |
April | 0.760179E+09 | 4217145.19 | 0.755962E+09 | 0.377448E+09 | 0.128595E+10 |
May | 0.107307E+10 | 35471222.39 | 0.103759E+10 | 0.942460E+09 | 0.737266E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101249E+10 | 0.149819E+10 | 0.386820E+09 |
July | 0.111283E+10 | 72035381.25 | 0.104079E+10 | 0.147948E+10 | 0.377038E+09 |
August | 0.885727E+09 | 20953327.99 | 0.864774E+09 | 0.111941E+10 | 0.436210E+09 |
September | 0.720011E+09 | 169117.77 | 0.719842E+09 | 0.798600E+09 | 0.659498E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.266948E+09 | 0.146098E+10 |
November | 0.391483E+09 | 0.00 | 0.391483E+09 | 84565694.70 | 0.173089E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611928.01 | 0.221287E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.696213E+10 | 0.145261E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611928.01 | 0.377038E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.149819E+10 | 0.221287E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 49829710.08 | 0.195505E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 58914965.84 | 0.177313E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.247671E+09 | 0.151038E+10 |
April | 0.760178E+09 | 4217140.13 | 0.755961E+09 | 0.377448E+09 | 0.128595E+10 |
May | 0.107306E+10 | 35471179.83 | 0.103759E+10 | 0.942459E+09 | 0.737266E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101248E+10 | 0.149819E+10 | 0.386820E+09 |
July | 0.111283E+10 | 72035294.82 | 0.104079E+10 | 0.147948E+10 | 0.377038E+09 |
August | 0.885727E+09 | 20953302.84 | 0.864773E+09 | 0.111941E+10 | 0.436210E+09 |
September | 0.720010E+09 | 169117.57 | 0.719841E+09 | 0.798599E+09 | 0.659498E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.266948E+09 | 0.146098E+10 |
November | 0.391482E+09 | 0.00 | 0.391482E+09 | 84565575.44 | 0.173089E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611867.45 | 0.221287E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.696213E+10 | 0.145261E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 38611867.45 | 0.377038E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.149819E+10 | 0.221287E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365723E+09 | 0.00 | 0.365723E+09 | 49827804.03 | 0.195497E+10 |
February | 0.415185E+09 | 0.00 | 0.415185E+09 | 58912695.37 | 0.177306E+10 |
March | 0.625459E+09 | 0.00 | 0.625459E+09 | 0.247661E+09 | 0.151032E+10 |
April | 0.760148E+09 | 4216975.22 | 0.755931E+09 | 0.377433E+09 | 0.128590E+10 |
May | 0.107302E+10 | 35469792.75 | 0.103755E+10 | 0.942422E+09 | 0.737236E+09 |
June | 0.113869E+10 | 0.126242E+09 | 0.101244E+10 | 0.149813E+10 | 0.386804E+09 |
July | 0.111278E+10 | 72032477.91 | 0.104075E+10 | 0.147942E+10 | 0.377023E+09 |
August | 0.885692E+09 | 20952483.47 | 0.864739E+09 | 0.111936E+10 | 0.436193E+09 |
September | 0.719982E+09 | 169110.95 | 0.719813E+09 | 0.798568E+09 | 0.659472E+09 |
October | 0.532870E+09 | 0.00 | 0.532870E+09 | 0.266937E+09 | 0.146092E+10 |
November | 0.391467E+09 | 0.00 | 0.391467E+09 | 84562286.33 | 0.173082E+10 |
December | 0.342179E+09 | 0.00 | 0.342179E+09 | 38610371.78 | 0.221278E+10 |
Annual Sum or Average | 0.836320E+10 | 0.259083E+09 | 0.810411E+10 | 0.696185E+10 | 0.145255E+11 |
Minimum of Months | 0.342179E+09 | 0.00 | 0.342179E+09 | 38610371.78 | 0.377023E+09 |
Maximum of Months | 0.113869E+10 | 0.126242E+09 | 0.104075E+10 | 0.149813E+10 | 0.221278E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127247E+10 | 0.779811E+09 | 0.492664E+09 | 0.109039E+10 | 0.201388E+10 |
February | 0.152676E+10 | 0.963838E+09 | 0.562922E+09 | 0.140853E+10 | 0.185657E+10 |
March | 0.204020E+10 | 0.119003E+10 | 0.850167E+09 | 0.203505E+10 | 0.157640E+10 |
April | 0.202484E+10 | 0.986334E+09 | 0.103850E+10 | 0.197497E+10 | 0.134917E+10 |
May | 0.244590E+10 | 0.102166E+10 | 0.142424E+10 | 0.274577E+10 | 0.818413E+09 |
June | 0.288799E+10 | 0.151612E+10 | 0.137187E+10 | 0.386550E+10 | 0.426672E+09 |
July | 0.271292E+10 | 0.129183E+10 | 0.142110E+10 | 0.366299E+10 | 0.410762E+09 |
August | 0.273635E+10 | 0.150709E+10 | 0.122927E+10 | 0.367179E+10 | 0.469181E+09 |
September | 0.220334E+10 | 0.119692E+10 | 0.100642E+10 | 0.279513E+10 | 0.698125E+09 |
October | 0.164885E+10 | 0.903473E+09 | 0.745374E+09 | 0.170816E+10 | 0.156128E+10 |
November | 0.124202E+10 | 0.701254E+09 | 0.540761E+09 | 0.113029E+10 | 0.180791E+10 |
December | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.905960E+09 | 0.227328E+10 |
Annual Sum or Average | 0.238527E+11 | 0.126984E+11 | 0.111543E+11 | 0.269945E+11 | 0.152617E+11 |
Minimum of Months | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.905960E+09 | 0.410762E+09 |
Maximum of Months | 0.288799E+10 | 0.151612E+10 | 0.142424E+10 | 0.386550E+10 | 0.227328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127247E+10 | 0.779811E+09 | 0.492664E+09 | 0.109039E+10 | 0.201388E+10 |
February | 0.152676E+10 | 0.963838E+09 | 0.562922E+09 | 0.140853E+10 | 0.185657E+10 |
March | 0.204020E+10 | 0.119003E+10 | 0.850167E+09 | 0.203505E+10 | 0.157640E+10 |
April | 0.202484E+10 | 0.986334E+09 | 0.103850E+10 | 0.197497E+10 | 0.134917E+10 |
May | 0.244590E+10 | 0.102166E+10 | 0.142424E+10 | 0.274577E+10 | 0.818413E+09 |
June | 0.288799E+10 | 0.151612E+10 | 0.137187E+10 | 0.386550E+10 | 0.426672E+09 |
July | 0.271292E+10 | 0.129183E+10 | 0.142110E+10 | 0.366299E+10 | 0.410762E+09 |
August | 0.273635E+10 | 0.150709E+10 | 0.122927E+10 | 0.367179E+10 | 0.469181E+09 |
September | 0.220334E+10 | 0.119692E+10 | 0.100642E+10 | 0.279513E+10 | 0.698125E+09 |
October | 0.164885E+10 | 0.903473E+09 | 0.745374E+09 | 0.170816E+10 | 0.156128E+10 |
November | 0.124202E+10 | 0.701254E+09 | 0.540761E+09 | 0.113029E+10 | 0.180791E+10 |
December | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.905960E+09 | 0.227328E+10 |
Annual Sum or Average | 0.238527E+11 | 0.126984E+11 | 0.111543E+11 | 0.269945E+11 | 0.152617E+11 |
Minimum of Months | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.905960E+09 | 0.410762E+09 |
Maximum of Months | 0.288799E+10 | 0.151612E+10 | 0.142424E+10 | 0.386550E+10 | 0.227328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127245E+10 | 0.779797E+09 | 0.492655E+09 | 0.109037E+10 | 0.201385E+10 |
February | 0.152673E+10 | 0.963820E+09 | 0.562912E+09 | 0.140850E+10 | 0.185654E+10 |
March | 0.204016E+10 | 0.119001E+10 | 0.850152E+09 | 0.203502E+10 | 0.157637E+10 |
April | 0.202480E+10 | 0.986315E+09 | 0.103848E+10 | 0.197493E+10 | 0.134915E+10 |
May | 0.244586E+10 | 0.102164E+10 | 0.142421E+10 | 0.274572E+10 | 0.818398E+09 |
June | 0.288793E+10 | 0.151609E+10 | 0.137184E+10 | 0.386543E+10 | 0.426664E+09 |
July | 0.271287E+10 | 0.129180E+10 | 0.142107E+10 | 0.366292E+10 | 0.410754E+09 |
August | 0.273630E+10 | 0.150706E+10 | 0.122925E+10 | 0.367173E+10 | 0.469172E+09 |
September | 0.220330E+10 | 0.119690E+10 | 0.100641E+10 | 0.279508E+10 | 0.698112E+09 |
October | 0.164882E+10 | 0.903456E+09 | 0.745361E+09 | 0.170813E+10 | 0.156125E+10 |
November | 0.124199E+10 | 0.701242E+09 | 0.540751E+09 | 0.113026E+10 | 0.180788E+10 |
December | 0.111108E+10 | 0.640058E+09 | 0.471017E+09 | 0.905944E+09 | 0.227324E+10 |
Annual Sum or Average | 0.238523E+11 | 0.126982E+11 | 0.111541E+11 | 0.269940E+11 | 0.152614E+11 |
Minimum of Months | 0.111108E+10 | 0.640058E+09 | 0.471017E+09 | 0.905944E+09 | 0.410754E+09 |
Maximum of Months | 0.288793E+10 | 0.151609E+10 | 0.142421E+10 | 0.386543E+10 | 0.227324E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350518E+10 | 0.288339E+10 | 0.621791E+09 | 0.397471E+10 | 0.170288E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615661E+09 | 0.341885E+10 | 0.159593E+10 |
March | 0.247881E+10 | 0.163092E+10 | 0.847893E+09 | 0.282057E+10 | 0.142503E+10 |
April | 0.155367E+10 | 0.624738E+09 | 0.928935E+09 | 0.160051E+10 | 0.126278E+10 |
May | 0.147123E+10 | 0.269666E+09 | 0.120156E+10 | 0.166221E+10 | 0.795157E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187865E+10 | 0.424087E+09 |
July | 0.141201E+10 | 0.252851E+09 | 0.115915E+10 | 0.202448E+10 | 0.404653E+09 |
August | 0.179777E+10 | 0.751536E+09 | 0.104623E+10 | 0.259407E+10 | 0.460819E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989383E+09 | 0.303420E+10 | 0.672211E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.333112E+10 | 0.140387E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661490E+09 | 0.378153E+10 | 0.157851E+10 |
December | 0.322221E+10 | 0.260802E+10 | 0.614198E+09 | 0.357258E+10 | 0.192204E+10 |
Annual Sum or Average | 0.280553E+11 | 0.174929E+11 | 0.105624E+11 | 0.336935E+11 | 0.136480E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614198E+09 | 0.160051E+10 | 0.404653E+09 |
Maximum of Months | 0.350518E+10 | 0.288339E+10 | 0.120156E+10 | 0.397471E+10 | 0.192204E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350517E+10 | 0.288338E+10 | 0.621791E+09 | 0.397471E+10 | 0.170288E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615660E+09 | 0.341885E+10 | 0.159593E+10 |
March | 0.247881E+10 | 0.163091E+10 | 0.847893E+09 | 0.282057E+10 | 0.142503E+10 |
April | 0.155367E+10 | 0.624737E+09 | 0.928934E+09 | 0.160051E+10 | 0.126278E+10 |
May | 0.147123E+10 | 0.269665E+09 | 0.120156E+10 | 0.166221E+10 | 0.795157E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187865E+10 | 0.424087E+09 |
July | 0.141200E+10 | 0.252851E+09 | 0.115915E+10 | 0.202448E+10 | 0.404653E+09 |
August | 0.179777E+10 | 0.751535E+09 | 0.104623E+10 | 0.259407E+10 | 0.460819E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989382E+09 | 0.303419E+10 | 0.672211E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.333112E+10 | 0.140387E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661489E+09 | 0.378152E+10 | 0.157851E+10 |
December | 0.322221E+10 | 0.260801E+10 | 0.614197E+09 | 0.357257E+10 | 0.192204E+10 |
Annual Sum or Average | 0.280552E+11 | 0.174928E+11 | 0.105624E+11 | 0.336934E+11 | 0.136480E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614197E+09 | 0.160051E+10 | 0.404653E+09 |
Maximum of Months | 0.350517E+10 | 0.288338E+10 | 0.120156E+10 | 0.397471E+10 | 0.192204E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350518E+10 | 0.288339E+10 | 0.621791E+09 | 0.397471E+10 | 0.170288E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615661E+09 | 0.341885E+10 | 0.159593E+10 |
March | 0.247881E+10 | 0.163092E+10 | 0.847893E+09 | 0.282057E+10 | 0.142503E+10 |
April | 0.155367E+10 | 0.624738E+09 | 0.928935E+09 | 0.160051E+10 | 0.126278E+10 |
May | 0.147123E+10 | 0.269666E+09 | 0.120156E+10 | 0.166221E+10 | 0.795157E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187865E+10 | 0.424087E+09 |
July | 0.141201E+10 | 0.252851E+09 | 0.115915E+10 | 0.202448E+10 | 0.404653E+09 |
August | 0.179777E+10 | 0.751536E+09 | 0.104623E+10 | 0.259407E+10 | 0.460819E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989383E+09 | 0.303420E+10 | 0.672211E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.333112E+10 | 0.140387E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661490E+09 | 0.378153E+10 | 0.157851E+10 |
December | 0.322221E+10 | 0.260802E+10 | 0.614198E+09 | 0.357258E+10 | 0.192204E+10 |
Annual Sum or Average | 0.280553E+11 | 0.174929E+11 | 0.105624E+11 | 0.336935E+11 | 0.136480E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614198E+09 | 0.160051E+10 | 0.404653E+09 |
Maximum of Months | 0.350518E+10 | 0.288339E+10 | 0.120156E+10 | 0.397471E+10 | 0.192204E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350517E+10 | 0.288338E+10 | 0.621791E+09 | 0.397471E+10 | 0.170288E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615660E+09 | 0.341885E+10 | 0.159593E+10 |
March | 0.247881E+10 | 0.163091E+10 | 0.847893E+09 | 0.282057E+10 | 0.142503E+10 |
April | 0.155367E+10 | 0.624737E+09 | 0.928934E+09 | 0.160051E+10 | 0.126278E+10 |
May | 0.147123E+10 | 0.269665E+09 | 0.120156E+10 | 0.166221E+10 | 0.795157E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187865E+10 | 0.424087E+09 |
July | 0.141200E+10 | 0.252851E+09 | 0.115915E+10 | 0.202448E+10 | 0.404653E+09 |
August | 0.179777E+10 | 0.751535E+09 | 0.104623E+10 | 0.259407E+10 | 0.460819E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989382E+09 | 0.303419E+10 | 0.672211E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.333112E+10 | 0.140387E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661489E+09 | 0.378152E+10 | 0.157851E+10 |
December | 0.322221E+10 | 0.260801E+10 | 0.614197E+09 | 0.357257E+10 | 0.192204E+10 |
Annual Sum or Average | 0.280552E+11 | 0.174928E+11 | 0.105624E+11 | 0.336934E+11 | 0.136480E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614197E+09 | 0.160051E+10 | 0.404653E+09 |
Maximum of Months | 0.350517E+10 | 0.288338E+10 | 0.120156E+10 | 0.397471E+10 | 0.192204E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350504E+10 | 0.288327E+10 | 0.621766E+09 | 0.397455E+10 | 0.170281E+10 |
February | 0.303663E+10 | 0.242099E+10 | 0.615636E+09 | 0.341871E+10 | 0.159587E+10 |
March | 0.247871E+10 | 0.163085E+10 | 0.847859E+09 | 0.282046E+10 | 0.142498E+10 |
April | 0.155361E+10 | 0.624713E+09 | 0.928897E+09 | 0.160044E+10 | 0.126273E+10 |
May | 0.147117E+10 | 0.269655E+09 | 0.120151E+10 | 0.166215E+10 | 0.795125E+09 |
June | 0.131262E+10 | 0.239909E+09 | 0.107271E+10 | 0.187858E+10 | 0.424070E+09 |
July | 0.141195E+10 | 0.252841E+09 | 0.115911E+10 | 0.202440E+10 | 0.404636E+09 |
August | 0.179770E+10 | 0.751506E+09 | 0.104619E+10 | 0.259397E+10 | 0.460800E+09 |
September | 0.223830E+10 | 0.124896E+10 | 0.989343E+09 | 0.303407E+10 | 0.672184E+09 |
October | 0.276557E+10 | 0.196223E+10 | 0.803335E+09 | 0.333099E+10 | 0.140381E+10 |
November | 0.326077E+10 | 0.259931E+10 | 0.661463E+09 | 0.378138E+10 | 0.157844E+10 |
December | 0.322208E+10 | 0.260791E+10 | 0.614173E+09 | 0.357243E+10 | 0.192196E+10 |
Annual Sum or Average | 0.280541E+11 | 0.174921E+11 | 0.105620E+11 | 0.336921E+11 | 0.136474E+11 |
Minimum of Months | 0.131262E+10 | 0.239909E+09 | 0.614173E+09 | 0.160044E+10 | 0.404636E+09 |
Maximum of Months | 0.350504E+10 | 0.288327E+10 | 0.120151E+10 | 0.397455E+10 | 0.192196E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135363E+10 | 0.857733E+09 | 0.495896E+09 | 0.123860E+10 | 0.216652E+10 |
February | 0.147432E+10 | 0.913643E+09 | 0.560678E+09 | 0.134265E+10 | 0.202144E+10 |
March | 0.191130E+10 | 0.105451E+10 | 0.856793E+09 | 0.184670E+10 | 0.178334E+10 |
April | 0.174153E+10 | 0.737332E+09 | 0.100419E+10 | 0.158843E+10 | 0.157691E+10 |
May | 0.219954E+10 | 0.775421E+09 | 0.142412E+10 | 0.243988E+10 | 0.931880E+09 |
June | 0.260340E+10 | 0.125259E+10 | 0.135080E+10 | 0.348825E+10 | 0.543252E+09 |
July | 0.219186E+10 | 0.802837E+09 | 0.138902E+10 | 0.292414E+10 | 0.530603E+09 |
August | 0.228768E+10 | 0.113014E+10 | 0.115753E+10 | 0.300314E+10 | 0.609347E+09 |
September | 0.196305E+10 | 0.941413E+09 | 0.102164E+10 | 0.248247E+10 | 0.805046E+09 |
October | 0.170649E+10 | 0.975388E+09 | 0.731105E+09 | 0.179746E+10 | 0.171985E+10 |
November | 0.135510E+10 | 0.822712E+09 | 0.532385E+09 | 0.126311E+10 | 0.201207E+10 |
December | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918979E+09 | 0.253827E+10 |
Annual Sum or Average | 0.219189E+11 | 0.109319E+11 | 0.109871E+11 | 0.243338E+11 | 0.172385E+11 |
Minimum of Months | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918979E+09 | 0.530603E+09 |
Maximum of Months | 0.260340E+10 | 0.125259E+10 | 0.142412E+10 | 0.348825E+10 | 0.253827E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135363E+10 | 0.857733E+09 | 0.495896E+09 | 0.123860E+10 | 0.216652E+10 |
February | 0.147432E+10 | 0.913643E+09 | 0.560678E+09 | 0.134265E+10 | 0.202144E+10 |
March | 0.191130E+10 | 0.105451E+10 | 0.856793E+09 | 0.184670E+10 | 0.178334E+10 |
April | 0.174153E+10 | 0.737332E+09 | 0.100419E+10 | 0.158843E+10 | 0.157691E+10 |
May | 0.219954E+10 | 0.775421E+09 | 0.142412E+10 | 0.243988E+10 | 0.931880E+09 |
June | 0.260340E+10 | 0.125259E+10 | 0.135080E+10 | 0.348825E+10 | 0.543252E+09 |
July | 0.219186E+10 | 0.802837E+09 | 0.138902E+10 | 0.292414E+10 | 0.530603E+09 |
August | 0.228768E+10 | 0.113014E+10 | 0.115753E+10 | 0.300314E+10 | 0.609347E+09 |
September | 0.196305E+10 | 0.941413E+09 | 0.102164E+10 | 0.248247E+10 | 0.805046E+09 |
October | 0.170649E+10 | 0.975388E+09 | 0.731105E+09 | 0.179746E+10 | 0.171985E+10 |
November | 0.135510E+10 | 0.822712E+09 | 0.532385E+09 | 0.126311E+10 | 0.201207E+10 |
December | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918979E+09 | 0.253827E+10 |
Annual Sum or Average | 0.219189E+11 | 0.109319E+11 | 0.109871E+11 | 0.243338E+11 | 0.172385E+11 |
Minimum of Months | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918979E+09 | 0.530603E+09 |
Maximum of Months | 0.260340E+10 | 0.125259E+10 | 0.142412E+10 | 0.348825E+10 | 0.253827E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135360E+10 | 0.857717E+09 | 0.495887E+09 | 0.123857E+10 | 0.216648E+10 |
February | 0.147429E+10 | 0.913626E+09 | 0.560668E+09 | 0.134262E+10 | 0.202141E+10 |
March | 0.191126E+10 | 0.105449E+10 | 0.856777E+09 | 0.184667E+10 | 0.178331E+10 |
April | 0.174149E+10 | 0.737319E+09 | 0.100418E+10 | 0.158840E+10 | 0.157688E+10 |
May | 0.219950E+10 | 0.775407E+09 | 0.142410E+10 | 0.243983E+10 | 0.931863E+09 |
June | 0.260335E+10 | 0.125257E+10 | 0.135078E+10 | 0.348819E+10 | 0.543242E+09 |
July | 0.219182E+10 | 0.802822E+09 | 0.138899E+10 | 0.292409E+10 | 0.530593E+09 |
August | 0.228763E+10 | 0.113012E+10 | 0.115751E+10 | 0.300309E+10 | 0.609336E+09 |
September | 0.196301E+10 | 0.941396E+09 | 0.102162E+10 | 0.248242E+10 | 0.805031E+09 |
October | 0.170646E+10 | 0.975370E+09 | 0.731092E+09 | 0.179743E+10 | 0.171982E+10 |
November | 0.135507E+10 | 0.822697E+09 | 0.532376E+09 | 0.126309E+10 | 0.201204E+10 |
December | 0.113101E+10 | 0.668119E+09 | 0.462893E+09 | 0.918963E+09 | 0.253823E+10 |
Annual Sum or Average | 0.219185E+11 | 0.109317E+11 | 0.109869E+11 | 0.243334E+11 | 0.172382E+11 |
Minimum of Months | 0.113101E+10 | 0.668119E+09 | 0.462893E+09 | 0.918963E+09 | 0.530593E+09 |
Maximum of Months | 0.260335E+10 | 0.125257E+10 | 0.142410E+10 | 0.348819E+10 | 0.253823E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.341799E+09 | 0.889906E+10 |
February | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.406879E+09 | 0.805206E+10 |
March | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.142536E+10 | 0.679202E+10 |
April | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.207109E+10 | 0.566865E+10 |
May | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.479609E+10 | 0.350378E+10 |
June | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.753301E+10 | 0.187227E+10 |
July | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.744948E+10 | 0.182968E+10 |
August | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.567337E+10 | 0.208653E+10 |
September | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.406740E+10 | 0.311926E+10 |
October | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.146851E+10 | 0.669820E+10 |
November | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.555941E+09 | 0.776018E+10 |
December | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.307466E+09 | 0.987536E+10 |
Annual Sum or Average | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.360964E+11 | 0.661570E+11 |
Minimum of Months | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.307466E+09 | 0.182968E+10 |
Maximum of Months | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.753301E+10 | 0.987536E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.332478E+10 | 0.567614E+10 |
February | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.423806E+10 | 0.523221E+10 |
March | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.610417E+10 | 0.442922E+10 |
April | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.592754E+10 | 0.373530E+10 |
May | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.818751E+10 | 0.239096E+10 |
June | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.115190E+11 | 0.127433E+10 |
July | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.109095E+11 | 0.125047E+10 |
August | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.109390E+11 | 0.142803E+10 |
September | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.833621E+10 | 0.204236E+10 |
October | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.511099E+10 | 0.444188E+10 |
November | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.342962E+10 | 0.508169E+10 |
December | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.278569E+10 | 0.631597E+10 |
Annual Sum or Average | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.808121E+11 | 0.432986E+11 |
Minimum of Months | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.278569E+10 | 0.125047E+10 |
Maximum of Months | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.115190E+11 | 0.631597E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.197472E+11 | 0.842999E+10 |
February | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.169646E+11 | 0.779074E+10 |
March | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.140371E+11 | 0.684315E+10 |
April | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.801745E+10 | 0.592353E+10 |
May | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.829467E+10 | 0.387904E+10 |
June | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.939524E+10 | 0.206061E+10 |
July | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.101268E+11 | 0.197962E+10 |
August | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.129469E+11 | 0.225191E+10 |
September | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.150886E+11 | 0.330144E+10 |
October | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.165556E+11 | 0.686039E+10 |
November | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.187967E+11 | 0.771234E+10 |
December | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.178058E+11 | 0.925482E+10 |
Annual Sum or Average | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.167777E+12 | 0.662876E+11 |
Minimum of Months | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.801745E+10 | 0.197962E+10 |
Maximum of Months | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.197472E+11 | 0.925482E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.380732E+10 | 0.592391E+10 |
February | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.412621E+10 | 0.541084E+10 |
March | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.567573E+10 | 0.464599E+10 |
April | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.492329E+10 | 0.394870E+10 |
May | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.737185E+10 | 0.260892E+10 |
June | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.105191E+11 | 0.149192E+10 |
July | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.887066E+10 | 0.141443E+10 |
August | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.913436E+10 | 0.158535E+10 |
September | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.748947E+10 | 0.224863E+10 |
October | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.547657E+10 | 0.462735E+10 |
November | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.392116E+10 | 0.526678E+10 |
December | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.291080E+10 | 0.648761E+10 |
Annual Sum or Average | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.742265E+11 | 0.456604E+11 |
Minimum of Months | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.291080E+10 | 0.141443E+10 |
Maximum of Months | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.105191E+11 | 0.648761E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.416139E+09 | 0.828593E+10 |
February | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.462915E+09 | 0.763704E+10 |
March | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.149515E+10 | 0.642198E+10 |
April | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.215286E+10 | 0.524836E+10 |
May | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.487089E+10 | 0.335769E+10 |
June | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.748733E+10 | 0.185728E+10 |
July | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.740070E+10 | 0.182340E+10 |
August | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.564028E+10 | 0.206053E+10 |
September | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.408055E+10 | 0.301175E+10 |
October | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.155899E+10 | 0.625984E+10 |
November | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.643372E+09 | 0.722510E+10 |
December | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.351642E+09 | 0.938270E+10 |
Annual Sum or Average | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.365608E+11 | 0.625716E+11 |
Minimum of Months | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.351642E+09 | 0.182340E+10 |
Maximum of Months | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.748733E+10 | 0.938270E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.343331E+10 | 0.525746E+10 |
February | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.430041E+10 | 0.496206E+10 |
March | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.616115E+10 | 0.420048E+10 |
April | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.598480E+10 | 0.346906E+10 |
May | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.822843E+10 | 0.230339E+10 |
June | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.114964E+11 | 0.126408E+10 |
July | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.108857E+11 | 0.124436E+10 |
August | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.109234E+11 | 0.141090E+10 |
September | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.834589E+10 | 0.198331E+10 |
October | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.516556E+10 | 0.417919E+10 |
November | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.352077E+10 | 0.473144E+10 |
December | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.286362E+10 | 0.599172E+10 |
Annual Sum or Average | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.813095E+11 | 0.409974E+11 |
Minimum of Months | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.286362E+10 | 0.124436E+10 |
Maximum of Months | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.114964E+11 | 0.599172E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.199242E+11 | 0.785947E+10 |
February | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.170518E+11 | 0.739280E+10 |
March | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.140998E+11 | 0.648475E+10 |
April | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.808157E+10 | 0.550200E+10 |
May | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.833476E+10 | 0.371810E+10 |
June | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.934661E+10 | 0.203911E+10 |
July | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.100749E+11 | 0.196803E+10 |
August | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.129023E+11 | 0.222329E+10 |
September | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.150760E+11 | 0.320380E+10 |
October | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.166222E+11 | 0.646365E+10 |
November | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.189108E+11 | 0.724987E+10 |
December | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.179241E+11 | 0.876398E+10 |
Annual Sum or Average | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.168349E+12 | 0.628689E+11 |
Minimum of Months | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.808157E+10 | 0.196803E+10 |
Maximum of Months | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.199242E+11 | 0.876398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.387554E+10 | 0.554457E+10 |
February | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.415989E+10 | 0.516201E+10 |
March | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.570728E+10 | 0.441916E+10 |
April | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.496056E+10 | 0.369101E+10 |
May | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.738684E+10 | 0.251415E+10 |
June | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.104805E+11 | 0.147370E+10 |
July | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.883310E+10 | 0.140206E+10 |
August | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.910264E+10 | 0.156431E+10 |
September | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.748339E+10 | 0.218323E+10 |
October | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.551676E+10 | 0.437935E+10 |
November | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.397440E+10 | 0.496834E+10 |
December | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.294989E+10 | 0.619213E+10 |
Annual Sum or Average | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.744307E+11 | 0.434940E+11 |
Minimum of Months | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.294989E+10 | 0.140206E+10 |
Maximum of Months | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.104805E+11 | 0.619213E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 93.02 | 3649.62 | 682.75 | 0.00 | 682.75 | 0.00 | 0.00 |
February | 121.76 | 3664.67 | 858.13 | 0.00 | 858.13 | 0.00 | 0.00 |
March | 462.35 | 2819.53 | 1167.64 | 0.00 | 1167.64 | 0.00 | 0.00 |
April | 728.10 | 2480.59 | 1466.38 | 8.13 | 1458.25 | 0.00 | 0.00 |
May | 1759.36 | 1376.31 | 2003.17 | 66.22 | 1936.95 | 0.00 | 0.00 |
June | 2890.01 | 746.17 | 2196.61 | 243.53 | 1953.08 | 0.00 | 0.00 |
July | 2761.85 | 703.84 | 2077.40 | 134.47 | 1942.92 | 0.00 | 0.00 |
August | 2089.68 | 814.30 | 1653.45 | 39.12 | 1614.33 | 0.00 | 0.00 |
September | 1540.50 | 1272.17 | 1388.90 | 0.33 | 1388.57 | 0.00 | 0.00 |
October | 498.33 | 2727.31 | 994.79 | 0.00 | 994.79 | 0.00 | 0.00 |
November | 163.13 | 3338.89 | 755.17 | 0.00 | 755.17 | 0.00 | 0.00 |
December | 72.08 | 4130.92 | 638.80 | 0.00 | 638.80 | 0.00 | 0.00 |
Annual Sum or Average | 1103.83 | 2303.07 | 1326.02 | 41.08 | 1284.94 | 0.00 | 0.00 |
Minimum of Months | 72.08 | 703.84 | 638.80 | 0.00 | 638.80 | 0.00 | 0.00 |
Maximum of Months | 2890.01 | 4130.92 | 2196.61 | 243.53 | 1953.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1221.31 | 2255.68 | 1425.25 | 873.44 | 551.82 | 0.00 | 0.00 |
February | 1746.67 | 2302.28 | 1893.29 | 1195.23 | 698.06 | 0.00 | 0.00 |
March | 2279.39 | 1765.67 | 2285.15 | 1332.91 | 952.24 | 0.00 | 0.00 |
April | 2285.83 | 1561.53 | 2343.55 | 1141.58 | 1201.96 | 0.00 | 0.00 |
May | 3075.44 | 916.68 | 2739.57 | 1144.33 | 1595.24 | 0.00 | 0.00 |
June | 4473.93 | 493.83 | 3342.56 | 1754.75 | 1587.80 | 0.00 | 0.00 |
July | 4102.78 | 460.08 | 3038.65 | 1446.93 | 1591.72 | 0.00 | 0.00 |
August | 4112.65 | 525.51 | 3064.89 | 1688.03 | 1376.86 | 0.00 | 0.00 |
September | 3235.08 | 808.01 | 2550.15 | 1385.31 | 1164.84 | 0.00 | 0.00 |
October | 1913.25 | 1748.73 | 1846.82 | 1011.95 | 834.87 | 0.00 | 0.00 |
November | 1308.19 | 2092.48 | 1437.51 | 811.63 | 625.88 | 0.00 | 0.00 |
December | 1014.73 | 2546.22 | 1244.50 | 716.92 | 527.58 | 0.00 | 0.00 |
Annual Sum or Average | 2567.96 | 1451.82 | 2269.08 | 1207.98 | 1061.10 | 0.00 | 0.00 |
Minimum of Months | 1014.73 | 460.08 | 1244.50 | 716.92 | 527.58 | 0.00 | 0.00 |
Maximum of Months | 4473.93 | 2546.22 | 3342.56 | 1754.75 | 1595.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7419.87 | 3178.88 | 6543.36 | 5382.62 | 1160.74 | 0.00 | 0.00 |
February | 7066.02 | 3298.45 | 6276.30 | 5003.86 | 1272.44 | 0.00 | 0.00 |
March | 5265.36 | 2660.21 | 4627.37 | 3044.55 | 1582.82 | 0.00 | 0.00 |
April | 3087.38 | 2435.90 | 2997.03 | 1205.12 | 1791.91 | 0.00 | 0.00 |
May | 3102.97 | 1484.38 | 2746.45 | 503.40 | 2243.04 | 0.00 | 0.00 |
June | 3623.91 | 818.06 | 2532.13 | 462.80 | 2069.33 | 0.00 | 0.00 |
July | 3779.24 | 755.39 | 2635.89 | 472.01 | 2163.88 | 0.00 | 0.00 |
August | 4842.54 | 860.24 | 3356.02 | 1402.94 | 1953.08 | 0.00 | 0.00 |
September | 5852.95 | 1296.69 | 4317.85 | 2409.34 | 1908.52 | 0.00 | 0.00 |
October | 6218.44 | 2620.70 | 5162.89 | 3663.19 | 1499.70 | 0.00 | 0.00 |
November | 7294.55 | 3044.93 | 6290.26 | 5014.25 | 1276.01 | 0.00 | 0.00 |
December | 6669.18 | 3588.01 | 6015.13 | 4868.57 | 1146.57 | 0.00 | 0.00 |
Annual Sum or Average | 5342.02 | 2163.85 | 4448.10 | 2773.45 | 1674.65 | 0.00 | 0.00 |
Minimum of Months | 3087.38 | 755.39 | 2532.13 | 462.80 | 1146.57 | 0.00 | 0.00 |
Maximum of Months | 7419.87 | 3588.01 | 6543.36 | 5382.62 | 2243.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1387.31 | 2426.64 | 1516.15 | 960.72 | 555.44 | 0.00 | 0.00 |
February | 1664.98 | 2506.73 | 1828.26 | 1132.98 | 695.28 | 0.00 | 0.00 |
March | 2068.43 | 1997.45 | 2140.78 | 1181.12 | 959.66 | 0.00 | 0.00 |
April | 1838.45 | 1825.12 | 2015.64 | 853.39 | 1162.25 | 0.00 | 0.00 |
May | 2732.82 | 1043.77 | 2463.63 | 868.52 | 1595.11 | 0.00 | 0.00 |
June | 4037.30 | 628.76 | 3013.17 | 1449.75 | 1563.42 | 0.00 | 0.00 |
July | 3275.22 | 594.31 | 2455.02 | 899.23 | 1555.79 | 0.00 | 0.00 |
August | 3363.71 | 682.51 | 2562.35 | 1265.84 | 1296.51 | 0.00 | 0.00 |
September | 2873.21 | 931.76 | 2272.03 | 1089.59 | 1182.44 | 0.00 | 0.00 |
October | 2013.27 | 1926.35 | 1911.38 | 1092.50 | 818.88 | 0.00 | 0.00 |
November | 1461.93 | 2328.77 | 1568.39 | 952.21 | 616.18 | 0.00 | 0.00 |
December | 1029.32 | 2843.03 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Annual Sum or Average | 2314.85 | 1639.88 | 2085.12 | 1039.93 | 1045.19 | 0.00 | 0.00 |
Minimum of Months | 1029.32 | 594.31 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Maximum of Months | 4037.30 | 2843.03 | 3013.17 | 1449.75 | 1595.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 127.61 | 3322.53 | 682.75 | 0.00 | 682.75 | 0.00 | 0.00 |
February | 168.19 | 3328.40 | 858.13 | 0.00 | 858.13 | 0.00 | 0.00 |
March | 532.17 | 2535.85 | 1167.63 | 0.00 | 1167.63 | 0.00 | 0.00 |
April | 799.03 | 2186.98 | 1466.38 | 8.13 | 1458.24 | 0.00 | 0.00 |
May | 1790.65 | 1308.16 | 2003.16 | 66.22 | 1936.94 | 0.00 | 0.00 |
June | 2906.25 | 722.33 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
July | 2781.32 | 683.12 | 2077.39 | 134.47 | 1942.92 | 0.00 | 0.00 |
August | 2118.19 | 779.02 | 1653.44 | 39.11 | 1614.33 | 0.00 | 0.00 |
September | 1569.21 | 1203.42 | 1388.89 | 0.33 | 1388.57 | 0.00 | 0.00 |
October | 548.28 | 2500.82 | 994.78 | 0.00 | 994.78 | 0.00 | 0.00 |
November | 214.48 | 2993.90 | 755.17 | 0.00 | 755.17 | 0.00 | 0.00 |
December | 114.79 | 3687.04 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Annual Sum or Average | 1144.61 | 2097.83 | 1326.01 | 41.08 | 1284.94 | 0.00 | 0.00 |
Minimum of Months | 114.79 | 683.12 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Maximum of Months | 2906.25 | 3687.04 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1241.33 | 2119.23 | 1425.25 | 873.44 | 551.81 | 0.00 | 0.00 |
February | 1751.84 | 2162.78 | 1893.28 | 1195.22 | 698.06 | 0.00 | 0.00 |
March | 2279.04 | 1653.68 | 2285.14 | 1332.90 | 952.24 | 0.00 | 0.00 |
April | 2286.86 | 1441.09 | 2343.54 | 1141.58 | 1201.96 | 0.00 | 0.00 |
May | 3056.87 | 892.68 | 2739.56 | 1144.32 | 1595.23 | 0.00 | 0.00 |
June | 4444.06 | 491.64 | 3342.54 | 1754.75 | 1587.80 | 0.00 | 0.00 |
July | 4073.15 | 466.87 | 3038.64 | 1446.92 | 1591.71 | 0.00 | 0.00 |
August | 4084.15 | 533.16 | 3064.88 | 1688.03 | 1376.85 | 0.00 | 0.00 |
September | 3216.13 | 787.95 | 2550.14 | 1385.31 | 1164.83 | 0.00 | 0.00 |
October | 1908.23 | 1658.41 | 1846.81 | 1011.94 | 834.86 | 0.00 | 0.00 |
November | 1323.16 | 1960.53 | 1437.50 | 811.63 | 625.87 | 0.00 | 0.00 |
December | 1040.06 | 2358.11 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Annual Sum or Average | 2562.53 | 1372.99 | 2269.07 | 1207.98 | 1061.09 | 0.00 | 0.00 |
Minimum of Months | 1040.06 | 466.87 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Maximum of Months | 4444.06 | 2358.11 | 3342.54 | 1754.75 | 1595.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7372.75 | 3147.40 | 6543.34 | 5382.60 | 1160.74 | 0.00 | 0.00 |
February | 7012.50 | 3220.38 | 6276.27 | 5003.84 | 1272.43 | 0.00 | 0.00 |
March | 5240.86 | 2554.94 | 4627.35 | 3044.54 | 1582.82 | 0.00 | 0.00 |
April | 3093.15 | 2285.31 | 2997.02 | 1205.11 | 1791.90 | 0.00 | 0.00 |
May | 3096.87 | 1448.27 | 2746.44 | 503.40 | 2243.03 | 0.00 | 0.00 |
June | 3624.71 | 794.99 | 2532.12 | 462.80 | 2069.32 | 0.00 | 0.00 |
July | 3780.91 | 739.11 | 2635.88 | 472.01 | 2163.87 | 0.00 | 0.00 |
August | 4833.82 | 840.77 | 3356.01 | 1402.94 | 1953.07 | 0.00 | 0.00 |
September | 5821.22 | 1273.70 | 4317.84 | 2409.33 | 1908.51 | 0.00 | 0.00 |
October | 6181.14 | 2561.38 | 5162.87 | 3663.18 | 1499.70 | 0.00 | 0.00 |
November | 7251.80 | 2975.44 | 6290.24 | 5014.23 | 1276.01 | 0.00 | 0.00 |
December | 6647.93 | 3455.35 | 6015.11 | 4868.55 | 1146.56 | 0.00 | 0.00 |
Annual Sum or Average | 5320.16 | 2101.97 | 4448.08 | 2773.44 | 1674.64 | 0.00 | 0.00 |
Minimum of Months | 3093.15 | 739.11 | 2532.12 | 462.80 | 1146.56 | 0.00 | 0.00 |
Maximum of Months | 7372.75 | 3455.35 | 6543.34 | 5382.60 | 2243.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1421.49 | 2211.74 | 1516.15 | 960.71 | 555.43 | 0.00 | 0.00 |
February | 1705.61 | 2236.62 | 1828.26 | 1132.98 | 695.28 | 0.00 | 0.00 |
March | 2119.07 | 1734.61 | 2140.77 | 1181.11 | 959.66 | 0.00 | 0.00 |
April | 1899.42 | 1523.42 | 2015.63 | 853.39 | 1162.25 | 0.00 | 0.00 |
May | 2752.33 | 974.06 | 2463.62 | 868.52 | 1595.10 | 0.00 | 0.00 |
June | 4058.28 | 575.59 | 3013.16 | 1449.75 | 1563.41 | 0.00 | 0.00 |
July | 3311.92 | 528.09 | 2455.01 | 899.23 | 1555.79 | 0.00 | 0.00 |
August | 3410.38 | 591.90 | 2562.34 | 1265.83 | 1296.51 | 0.00 | 0.00 |
September | 2889.46 | 867.53 | 2272.02 | 1089.59 | 1182.44 | 0.00 | 0.00 |
October | 2044.72 | 1727.65 | 1911.37 | 1092.49 | 818.88 | 0.00 | 0.00 |
November | 1512.79 | 2031.94 | 1568.38 | 952.20 | 616.18 | 0.00 | 0.00 |
December | 1086.77 | 2422.19 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Annual Sum or Average | 2353.71 | 1447.88 | 2085.11 | 1039.93 | 1045.18 | 0.00 | 0.00 |
Minimum of Months | 1086.77 | 528.09 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Maximum of Months | 4058.28 | 2422.19 | 3013.16 | 1449.75 | 1595.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.37 | 3093.61 | 682.75 | 0.00 | 682.75 | 0.00 | 0.00 |
February | 191.35 | 3156.84 | 858.13 | 0.00 | 858.13 | 0.00 | 0.00 |
March | 558.23 | 2397.69 | 1167.63 | 0.00 | 1167.63 | 0.00 | 0.00 |
April | 830.58 | 2024.83 | 1466.38 | 8.13 | 1458.24 | 0.00 | 0.00 |
May | 1818.58 | 1253.62 | 2003.16 | 66.22 | 1936.94 | 0.00 | 0.00 |
June | 2888.63 | 716.54 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
July | 2763.11 | 680.78 | 2077.39 | 134.47 | 1942.92 | 0.00 | 0.00 |
August | 2105.84 | 769.31 | 1653.44 | 39.11 | 1614.33 | 0.00 | 0.00 |
September | 1574.29 | 1161.94 | 1388.89 | 0.33 | 1388.57 | 0.00 | 0.00 |
October | 582.06 | 2337.16 | 994.78 | 0.00 | 994.78 | 0.00 | 0.00 |
November | 248.21 | 2787.46 | 755.17 | 0.00 | 755.17 | 0.00 | 0.00 |
December | 131.29 | 3503.10 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Annual Sum or Average | 1159.34 | 1984.13 | 1326.01 | 41.08 | 1284.94 | 0.00 | 0.00 |
Minimum of Months | 131.29 | 680.78 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Maximum of Months | 2888.63 | 3503.10 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1281.85 | 1962.91 | 1425.25 | 873.44 | 551.81 | 0.00 | 0.00 |
February | 1777.61 | 2051.11 | 1893.28 | 1195.22 | 698.06 | 0.00 | 0.00 |
March | 2300.31 | 1568.28 | 2285.14 | 1332.90 | 952.24 | 0.00 | 0.00 |
April | 2308.95 | 1338.37 | 2343.54 | 1141.58 | 1201.96 | 0.00 | 0.00 |
May | 3072.15 | 859.99 | 2739.56 | 1144.32 | 1595.23 | 0.00 | 0.00 |
June | 4435.34 | 487.69 | 3342.54 | 1754.75 | 1587.80 | 0.00 | 0.00 |
July | 4064.27 | 464.59 | 3038.64 | 1446.92 | 1591.71 | 0.00 | 0.00 |
August | 4078.33 | 526.77 | 3064.88 | 1688.03 | 1376.85 | 0.00 | 0.00 |
September | 3219.86 | 765.17 | 2550.14 | 1385.31 | 1164.83 | 0.00 | 0.00 |
October | 1928.60 | 1560.33 | 1846.81 | 1011.94 | 834.86 | 0.00 | 0.00 |
November | 1358.32 | 1825.40 | 1437.50 | 811.63 | 625.87 | 0.00 | 0.00 |
December | 1069.15 | 2237.05 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Annual Sum or Average | 2578.31 | 1300.02 | 2269.07 | 1207.98 | 1061.09 | 0.00 | 0.00 |
Minimum of Months | 1069.15 | 464.59 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Maximum of Months | 4435.34 | 2237.05 | 3342.54 | 1754.75 | 1595.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7438.84 | 2934.39 | 6543.34 | 5382.60 | 1160.74 | 0.00 | 0.00 |
February | 7048.53 | 3055.89 | 6276.27 | 5003.84 | 1272.43 | 0.00 | 0.00 |
March | 5264.25 | 2421.13 | 4627.35 | 3044.54 | 1582.82 | 0.00 | 0.00 |
April | 3117.89 | 2122.69 | 2997.02 | 1205.11 | 1791.90 | 0.00 | 0.00 |
May | 3111.84 | 1388.18 | 2746.44 | 503.40 | 2243.03 | 0.00 | 0.00 |
June | 3605.95 | 786.69 | 2532.12 | 462.80 | 2069.32 | 0.00 | 0.00 |
July | 3761.52 | 734.78 | 2635.88 | 472.01 | 2163.87 | 0.00 | 0.00 |
August | 4817.16 | 830.08 | 3356.01 | 1402.94 | 1953.07 | 0.00 | 0.00 |
September | 5816.35 | 1236.03 | 4317.84 | 2409.33 | 1908.51 | 0.00 | 0.00 |
October | 6206.02 | 2413.25 | 5162.87 | 3663.18 | 1499.70 | 0.00 | 0.00 |
November | 7295.82 | 2797.02 | 6290.24 | 5014.23 | 1276.01 | 0.00 | 0.00 |
December | 6692.10 | 3272.09 | 6015.11 | 4868.55 | 1146.56 | 0.00 | 0.00 |
Annual Sum or Average | 5338.31 | 1993.56 | 4448.08 | 2773.44 | 1674.64 | 0.00 | 0.00 |
Minimum of Months | 3111.84 | 734.78 | 2532.12 | 462.80 | 1146.56 | 0.00 | 0.00 |
Maximum of Months | 7438.84 | 3272.09 | 6543.34 | 5382.60 | 2243.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1446.96 | 2070.11 | 1516.15 | 960.71 | 555.43 | 0.00 | 0.00 |
February | 1719.53 | 2133.77 | 1828.26 | 1132.98 | 695.28 | 0.00 | 0.00 |
March | 2130.86 | 1649.93 | 2140.77 | 1181.11 | 959.66 | 0.00 | 0.00 |
April | 1913.80 | 1424.00 | 2015.63 | 853.39 | 1162.25 | 0.00 | 0.00 |
May | 2757.93 | 938.68 | 2463.62 | 868.52 | 1595.10 | 0.00 | 0.00 |
June | 4043.39 | 568.56 | 3013.16 | 1449.75 | 1563.41 | 0.00 | 0.00 |
July | 3297.90 | 523.47 | 2455.01 | 899.23 | 1555.79 | 0.00 | 0.00 |
August | 3398.54 | 584.05 | 2562.34 | 1265.83 | 1296.51 | 0.00 | 0.00 |
September | 2887.11 | 842.30 | 2272.02 | 1089.59 | 1182.44 | 0.00 | 0.00 |
October | 2059.72 | 1635.06 | 1911.37 | 1092.49 | 818.88 | 0.00 | 0.00 |
November | 1533.33 | 1916.80 | 1568.38 | 952.20 | 616.18 | 0.00 | 0.00 |
December | 1101.36 | 2311.88 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Annual Sum or Average | 2360.18 | 1379.19 | 2085.11 | 1039.93 | 1045.18 | 0.00 | 0.00 |
Minimum of Months | 1101.36 | 523.47 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Maximum of Months | 4043.39 | 2311.88 | 3013.16 | 1449.75 | 1595.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249147E+09 | 0.977515E+10 | 0.182867E+10 | 0.00 | 0.182867E+10 | 0.00 | 0.00 |
February | 0.294573E+09 | 0.886556E+10 | 0.207599E+10 | 0.00 | 0.207599E+10 | 0.00 | 0.00 |
March | 0.123835E+10 | 0.755183E+10 | 0.312739E+10 | 0.00 | 0.312739E+10 | 0.00 | 0.00 |
April | 0.188722E+10 | 0.642969E+10 | 0.380086E+10 | 21085545.88 | 0.377978E+10 | 0.00 | 0.00 |
May | 0.471226E+10 | 0.368630E+10 | 0.536528E+10 | 0.177355E+09 | 0.518793E+10 | 0.00 | 0.00 |
June | 0.749090E+10 | 0.193408E+10 | 0.569361E+10 | 0.631229E+09 | 0.506239E+10 | 0.00 | 0.00 |
July | 0.739735E+10 | 0.188517E+10 | 0.556410E+10 | 0.360174E+09 | 0.520392E+10 | 0.00 | 0.00 |
August | 0.559699E+10 | 0.218103E+10 | 0.442860E+10 | 0.104766E+09 | 0.432383E+10 | 0.00 | 0.00 |
September | 0.399297E+10 | 0.329746E+10 | 0.360002E+10 | 845581.62 | 0.359918E+10 | 0.00 | 0.00 |
October | 0.133473E+10 | 0.730482E+10 | 0.266443E+10 | 0.00 | 0.266443E+10 | 0.00 | 0.00 |
November | 0.422825E+09 | 0.865440E+10 | 0.195740E+10 | 0.00 | 0.195740E+10 | 0.00 | 0.00 |
December | 0.193058E+09 | 0.110643E+11 | 0.171095E+10 | 0.00 | 0.171095E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.348104E+11 | 0.726298E+11 | 0.418173E+11 | 0.129545E+10 | 0.405219E+11 | 0.00 | 0.00 |
Minimum of Months | 0.193058E+09 | 0.188517E+10 | 0.171095E+10 | 0.00 | 0.171095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.749090E+10 | 0.110643E+11 | 0.569361E+10 | 0.631229E+09 | 0.520392E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327114E+10 | 0.604161E+10 | 0.381740E+10 | 0.233942E+10 | 0.147798E+10 | 0.00 | 0.00 |
February | 0.422555E+10 | 0.556968E+10 | 0.458025E+10 | 0.289150E+10 | 0.168876E+10 | 0.00 | 0.00 |
March | 0.610513E+10 | 0.472918E+10 | 0.612055E+10 | 0.357006E+10 | 0.255049E+10 | 0.00 | 0.00 |
April | 0.592486E+10 | 0.404750E+10 | 0.607447E+10 | 0.295898E+10 | 0.311549E+10 | 0.00 | 0.00 |
May | 0.823726E+10 | 0.245523E+10 | 0.733766E+10 | 0.306497E+10 | 0.427269E+10 | 0.00 | 0.00 |
June | 0.115964E+11 | 0.128001E+10 | 0.866390E+10 | 0.454832E+10 | 0.411558E+10 | 0.00 | 0.00 |
July | 0.109889E+11 | 0.123228E+10 | 0.813872E+10 | 0.387546E+10 | 0.426326E+10 | 0.00 | 0.00 |
August | 0.110153E+11 | 0.140753E+10 | 0.820901E+10 | 0.452123E+10 | 0.368778E+10 | 0.00 | 0.00 |
September | 0.838533E+10 | 0.209436E+10 | 0.660998E+10 | 0.359073E+10 | 0.301925E+10 | 0.00 | 0.00 |
October | 0.512445E+10 | 0.468381E+10 | 0.494651E+10 | 0.271040E+10 | 0.223611E+10 | 0.00 | 0.00 |
November | 0.339084E+10 | 0.542370E+10 | 0.372602E+10 | 0.210375E+10 | 0.162227E+10 | 0.00 | 0.00 |
December | 0.271786E+10 | 0.681979E+10 | 0.333327E+10 | 0.192020E+10 | 0.141307E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.809831E+11 | 0.457847E+11 | 0.715578E+11 | 0.380950E+11 | 0.334627E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271786E+10 | 0.123228E+10 | 0.333327E+10 | 0.192020E+10 | 0.141307E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115964E+11 | 0.681979E+10 | 0.866390E+10 | 0.454832E+10 | 0.427269E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198734E+11 | 0.851432E+10 | 0.175257E+11 | 0.144168E+11 | 0.310893E+10 | 0.00 | 0.00 |
February | 0.170941E+11 | 0.797961E+10 | 0.151836E+11 | 0.121053E+11 | 0.307828E+10 | 0.00 | 0.00 |
March | 0.141027E+11 | 0.712511E+10 | 0.123939E+11 | 0.815451E+10 | 0.423943E+10 | 0.00 | 0.00 |
April | 0.800248E+10 | 0.631385E+10 | 0.776830E+10 | 0.312366E+10 | 0.464463E+10 | 0.00 | 0.00 |
May | 0.831100E+10 | 0.397575E+10 | 0.735608E+10 | 0.134832E+10 | 0.600776E+10 | 0.00 | 0.00 |
June | 0.939319E+10 | 0.212042E+10 | 0.656328E+10 | 0.119958E+10 | 0.536370E+10 | 0.00 | 0.00 |
July | 0.101223E+11 | 0.202325E+10 | 0.705997E+10 | 0.126424E+10 | 0.579573E+10 | 0.00 | 0.00 |
August | 0.129703E+11 | 0.230408E+10 | 0.898878E+10 | 0.375765E+10 | 0.523113E+10 | 0.00 | 0.00 |
September | 0.151708E+11 | 0.336103E+10 | 0.111919E+11 | 0.624500E+10 | 0.494687E+10 | 0.00 | 0.00 |
October | 0.166555E+11 | 0.701927E+10 | 0.138283E+11 | 0.981148E+10 | 0.401680E+10 | 0.00 | 0.00 |
November | 0.189075E+11 | 0.789246E+10 | 0.163044E+11 | 0.129969E+11 | 0.330742E+10 | 0.00 | 0.00 |
December | 0.178627E+11 | 0.961012E+10 | 0.161109E+11 | 0.130400E+11 | 0.307096E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.168466E+12 | 0.682393E+11 | 0.140275E+12 | 0.874635E+11 | 0.528117E+11 | 0.00 | 0.00 |
Minimum of Months | 0.800248E+10 | 0.202325E+10 | 0.656328E+10 | 0.119958E+10 | 0.307096E+10 | 0.00 | 0.00 |
Maximum of Months | 0.198734E+11 | 0.961012E+10 | 0.175257E+11 | 0.144168E+11 | 0.600776E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.371576E+10 | 0.649952E+10 | 0.406086E+10 | 0.257318E+10 | 0.148768E+10 | 0.00 | 0.00 |
February | 0.402791E+10 | 0.606429E+10 | 0.442294E+10 | 0.274091E+10 | 0.168202E+10 | 0.00 | 0.00 |
March | 0.554008E+10 | 0.534998E+10 | 0.573386E+10 | 0.316350E+10 | 0.257036E+10 | 0.00 | 0.00 |
April | 0.476526E+10 | 0.473070E+10 | 0.522455E+10 | 0.221198E+10 | 0.301256E+10 | 0.00 | 0.00 |
May | 0.731959E+10 | 0.279562E+10 | 0.659859E+10 | 0.232625E+10 | 0.427234E+10 | 0.00 | 0.00 |
June | 0.104647E+11 | 0.162975E+10 | 0.781014E+10 | 0.375776E+10 | 0.405238E+10 | 0.00 | 0.00 |
July | 0.877236E+10 | 0.159180E+10 | 0.657553E+10 | 0.240850E+10 | 0.416703E+10 | 0.00 | 0.00 |
August | 0.900937E+10 | 0.182803E+10 | 0.686299E+10 | 0.339041E+10 | 0.347257E+10 | 0.00 | 0.00 |
September | 0.744736E+10 | 0.241512E+10 | 0.588911E+10 | 0.282422E+10 | 0.306489E+10 | 0.00 | 0.00 |
October | 0.539234E+10 | 0.515953E+10 | 0.511945E+10 | 0.292615E+10 | 0.219330E+10 | 0.00 | 0.00 |
November | 0.378932E+10 | 0.603618E+10 | 0.406527E+10 | 0.246812E+10 | 0.159715E+10 | 0.00 | 0.00 |
December | 0.275692E+10 | 0.761477E+10 | 0.339308E+10 | 0.200438E+10 | 0.138870E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.730010E+11 | 0.517153E+11 | 0.657564E+11 | 0.327954E+11 | 0.329610E+11 | 0.00 | 0.00 |
Minimum of Months | 0.275692E+10 | 0.159180E+10 | 0.339308E+10 | 0.200438E+10 | 0.138870E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104647E+11 | 0.761477E+10 | 0.781014E+10 | 0.375776E+10 | 0.427234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.341799E+09 | 0.889906E+10 | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.00 | 0.00 |
February | 0.406879E+09 | 0.805206E+10 | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.00 | 0.00 |
March | 0.142536E+10 | 0.679202E+10 | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.00 | 0.00 |
April | 0.207109E+10 | 0.566865E+10 | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.00 | 0.00 |
May | 0.479609E+10 | 0.350378E+10 | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.00 | 0.00 |
June | 0.753301E+10 | 0.187227E+10 | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.00 | 0.00 |
July | 0.744948E+10 | 0.182968E+10 | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.00 | 0.00 |
August | 0.567337E+10 | 0.208653E+10 | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.00 | 0.00 |
September | 0.406740E+10 | 0.311926E+10 | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.00 | 0.00 |
October | 0.146851E+10 | 0.669820E+10 | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.00 | 0.00 |
November | 0.555941E+09 | 0.776018E+10 | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.00 | 0.00 |
December | 0.307466E+09 | 0.987536E+10 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.360964E+11 | 0.661570E+11 | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.307466E+09 | 0.182968E+10 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Maximum of Months | 0.753301E+10 | 0.987536E+10 | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.332478E+10 | 0.567614E+10 | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.00 | 0.00 |
February | 0.423806E+10 | 0.523221E+10 | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.00 | 0.00 |
March | 0.610417E+10 | 0.442922E+10 | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.00 | 0.00 |
April | 0.592754E+10 | 0.373530E+10 | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.00 | 0.00 |
May | 0.818751E+10 | 0.239096E+10 | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.00 | 0.00 |
June | 0.115190E+11 | 0.127433E+10 | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.00 | 0.00 |
July | 0.109095E+11 | 0.125047E+10 | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.00 | 0.00 |
August | 0.109390E+11 | 0.142803E+10 | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.00 | 0.00 |
September | 0.833621E+10 | 0.204236E+10 | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.00 | 0.00 |
October | 0.511099E+10 | 0.444188E+10 | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.00 | 0.00 |
November | 0.342962E+10 | 0.508169E+10 | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.00 | 0.00 |
December | 0.278569E+10 | 0.631597E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.808121E+11 | 0.432986E+11 | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.00 | 0.00 |
Minimum of Months | 0.278569E+10 | 0.125047E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115190E+11 | 0.631597E+10 | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197472E+11 | 0.842999E+10 | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.00 | 0.00 |
February | 0.169646E+11 | 0.779074E+10 | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.00 | 0.00 |
March | 0.140371E+11 | 0.684315E+10 | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.00 | 0.00 |
April | 0.801745E+10 | 0.592353E+10 | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.00 | 0.00 |
May | 0.829467E+10 | 0.387904E+10 | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.00 | 0.00 |
June | 0.939524E+10 | 0.206061E+10 | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.00 | 0.00 |
July | 0.101268E+11 | 0.197962E+10 | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.00 | 0.00 |
August | 0.129469E+11 | 0.225191E+10 | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.00 | 0.00 |
September | 0.150886E+11 | 0.330144E+10 | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.00 | 0.00 |
October | 0.165556E+11 | 0.686039E+10 | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.00 | 0.00 |
November | 0.187967E+11 | 0.771234E+10 | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.00 | 0.00 |
December | 0.178058E+11 | 0.925482E+10 | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.167777E+12 | 0.662876E+11 | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.00 | 0.00 |
Minimum of Months | 0.801745E+10 | 0.197962E+10 | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.197472E+11 | 0.925482E+10 | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.380732E+10 | 0.592391E+10 | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.00 | 0.00 |
February | 0.412621E+10 | 0.541084E+10 | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.00 | 0.00 |
March | 0.567573E+10 | 0.464599E+10 | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.00 | 0.00 |
April | 0.492329E+10 | 0.394870E+10 | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.00 | 0.00 |
May | 0.737185E+10 | 0.260892E+10 | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.00 | 0.00 |
June | 0.105191E+11 | 0.149192E+10 | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.00 | 0.00 |
July | 0.887066E+10 | 0.141443E+10 | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.00 | 0.00 |
August | 0.913436E+10 | 0.158535E+10 | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.00 | 0.00 |
September | 0.748947E+10 | 0.224863E+10 | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.00 | 0.00 |
October | 0.547657E+10 | 0.462735E+10 | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.00 | 0.00 |
November | 0.392116E+10 | 0.526678E+10 | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.00 | 0.00 |
December | 0.291080E+10 | 0.648761E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.742265E+11 | 0.456604E+11 | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.291080E+10 | 0.141443E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105191E+11 | 0.648761E+10 | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416139E+09 | 0.828593E+10 | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.00 | 0.00 |
February | 0.462915E+09 | 0.763704E+10 | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.00 | 0.00 |
March | 0.149515E+10 | 0.642198E+10 | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.00 | 0.00 |
April | 0.215286E+10 | 0.524836E+10 | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.00 | 0.00 |
May | 0.487089E+10 | 0.335769E+10 | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.00 | 0.00 |
June | 0.748733E+10 | 0.185728E+10 | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.00 | 0.00 |
July | 0.740070E+10 | 0.182340E+10 | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.00 | 0.00 |
August | 0.564028E+10 | 0.206053E+10 | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.00 | 0.00 |
September | 0.408055E+10 | 0.301175E+10 | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.00 | 0.00 |
October | 0.155899E+10 | 0.625984E+10 | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.00 | 0.00 |
November | 0.643372E+09 | 0.722510E+10 | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.00 | 0.00 |
December | 0.351642E+09 | 0.938270E+10 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.365608E+11 | 0.625716E+11 | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.351642E+09 | 0.182340E+10 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Maximum of Months | 0.748733E+10 | 0.938270E+10 | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.343331E+10 | 0.525746E+10 | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.00 | 0.00 |
February | 0.430041E+10 | 0.496206E+10 | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.00 | 0.00 |
March | 0.616115E+10 | 0.420048E+10 | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.00 | 0.00 |
April | 0.598480E+10 | 0.346906E+10 | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.00 | 0.00 |
May | 0.822843E+10 | 0.230339E+10 | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.00 | 0.00 |
June | 0.114964E+11 | 0.126408E+10 | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.00 | 0.00 |
July | 0.108857E+11 | 0.124436E+10 | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.00 | 0.00 |
August | 0.109234E+11 | 0.141090E+10 | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.00 | 0.00 |
September | 0.834589E+10 | 0.198331E+10 | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.00 | 0.00 |
October | 0.516556E+10 | 0.417919E+10 | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.00 | 0.00 |
November | 0.352077E+10 | 0.473144E+10 | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.00 | 0.00 |
December | 0.286362E+10 | 0.599172E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.813095E+11 | 0.409974E+11 | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.00 | 0.00 |
Minimum of Months | 0.286362E+10 | 0.124436E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114964E+11 | 0.599172E+10 | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199242E+11 | 0.785947E+10 | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.00 | 0.00 |
February | 0.170518E+11 | 0.739280E+10 | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.00 | 0.00 |
March | 0.140998E+11 | 0.648475E+10 | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.00 | 0.00 |
April | 0.808157E+10 | 0.550200E+10 | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.00 | 0.00 |
May | 0.833476E+10 | 0.371810E+10 | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.00 | 0.00 |
June | 0.934661E+10 | 0.203911E+10 | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.00 | 0.00 |
July | 0.100749E+11 | 0.196803E+10 | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.00 | 0.00 |
August | 0.129023E+11 | 0.222329E+10 | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.00 | 0.00 |
September | 0.150760E+11 | 0.320380E+10 | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.00 | 0.00 |
October | 0.166222E+11 | 0.646365E+10 | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.00 | 0.00 |
November | 0.189108E+11 | 0.724987E+10 | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.00 | 0.00 |
December | 0.179241E+11 | 0.876398E+10 | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.168349E+12 | 0.628689E+11 | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.00 | 0.00 |
Minimum of Months | 0.808157E+10 | 0.196803E+10 | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.199242E+11 | 0.876398E+10 | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.387554E+10 | 0.554457E+10 | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.00 | 0.00 |
February | 0.415989E+10 | 0.516201E+10 | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.00 | 0.00 |
March | 0.570728E+10 | 0.441916E+10 | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.00 | 0.00 |
April | 0.496056E+10 | 0.369101E+10 | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.00 | 0.00 |
May | 0.738684E+10 | 0.251415E+10 | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.00 | 0.00 |
June | 0.104805E+11 | 0.147370E+10 | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.00 | 0.00 |
July | 0.883310E+10 | 0.140206E+10 | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.00 | 0.00 |
August | 0.910264E+10 | 0.156431E+10 | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.00 | 0.00 |
September | 0.748339E+10 | 0.218323E+10 | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.00 | 0.00 |
October | 0.551676E+10 | 0.437935E+10 | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.00 | 0.00 |
November | 0.397440E+10 | 0.496834E+10 | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.00 | 0.00 |
December | 0.294989E+10 | 0.619213E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.744307E+11 | 0.434940E+11 | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294989E+10 | 0.140206E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104805E+11 | 0.619213E+10 | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.411821E+11 | -0.401525E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102954E+10 | 58.98 | 0.00 | 0.00 |
February | 0.378693E+11 | -0.369392E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -930091095.4 | 58.97 | 0.00 | 0.00 |
March | 0.438429E+11 | -0.428115E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103136E+10 | 58.98 | 0.00 | 0.00 |
April | 0.382831E+11 | -0.372893E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993803096.6 | 58.98 | 0.00 | 0.00 |
May | 0.386468E+11 | -0.376209E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102583E+10 | 58.97 | 0.00 | 0.00 |
June | 0.360738E+11 | -0.350818E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991969809.1 | 58.98 | 0.00 | 0.00 |
July | 0.328563E+11 | -0.318369E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101943E+10 | 58.97 | 0.00 | 0.00 |
August | 0.353229E+11 | -0.342995E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102337E+10 | 58.98 | 0.00 | 0.00 |
September | 0.327062E+11 | -0.317182E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988061384.4 | 58.97 | 0.00 | 0.00 |
October | 0.353534E+11 | -0.343324E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102100E+10 | 58.97 | 0.00 | 0.00 |
November | 0.367772E+11 | -0.357879E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989332192.4 | 58.98 | 0.00 | 0.00 |
December | 0.387064E+11 | -0.376768E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102957E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.447620E+12 | -0.435547E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120733E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.327062E+11 | -0.428115E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103136E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.438429E+11 | -0.317182E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -930091095.4 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10579.33 | 39.79 | 274.33 | 267.83 | 5649.13 | 35.45 | 240.67 | 259.83 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14143.61 | 39.57 | 241.00 | 264.50 | 2329.15 | 25.66 | 134.00 | 244.00 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-06:00 | 2819.79 | 20.91 | 99.83 | 327.83 | 1599.18 | 21.97 | 169.33 | 293.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2173.24 | 20.61 | 114.67 | 341.67 | 1250.58 | 22.00 | 204.67 | 303.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1954.72 | 20.68 | 184.33 | 395.17 | 1069.48 | 22.08 | 306.50 | 358.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1601.36 | 20.16 | 102.67 | 394.33 | 953.05 | 21.62 | 260.17 | 353.67 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 1786.69 | 20.31 | 158.50 | 397.83 | 1004.26 | 21.73 | 293.50 | 359.50 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1910.74 | 20.07 | 113.83 | 371.83 | 1154.38 | 21.48 | 232.00 | 337.83 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3058.92 | 21.84 | 150.00 | 333.83 | 1415.75 | 21.95 | 218.50 | 305.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13774.22 | 37.07 | 241.50 | 299.33 | 1956.38 | 22.56 | 175.67 | 277.33 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12102.80 | 39.90 | 256.00 | 265.67 | 3589.39 | 30.19 | 183.67 | 242.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9916.11 | 40.21 | 250.67 | 258.50 | 7966.35 | 40.75 | 251.00 | 248.17 |
Annual Sum or Average | 3902.00 | 0.50 | 5432.28 | 26.81 | 2187.33 | 3918.33 | 2217.50 | 24.85 | 2669.67 | 3583.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1601.36 | 20.07 | 99.83 | 258.50 | 953.05 | 21.48 | 134.00 | 242.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14143.61 | 40.21 | 274.33 | 397.83 | 7966.35 | 40.75 | 306.50 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2639.58 | 24.99 | 116.17 | 242.33 | 1497.01 | 24.65 | 126.50 | 211.50 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3974.32 | 25.33 | 90.17 | 253.67 | 2351.51 | 25.19 | 91.00 | 209.00 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3811.52 | 24.69 | 99.50 | 322.00 | 2115.51 | 24.82 | 124.67 | 283.67 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4226.70 | 25.34 | 105.83 | 343.67 | 1836.08 | 24.48 | 158.33 | 305.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3346.77 | 24.25 | 130.67 | 402.50 | 1808.78 | 24.72 | 265.33 | 369.50 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 3997.92 | 24.73 | 126.83 | 407.17 | 2270.52 | 25.22 | 195.17 | 378.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3579.04 | 24.10 | 126.83 | 408.83 | 1920.67 | 24.47 | 247.83 | 376.33 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:40 | 4909.29 | 25.30 | 136.17 | 375.50 | 1954.29 | 24.08 | 179.33 | 342.17 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 4031.21 | 25.55 | 132.33 | 334.50 | 1591.84 | 24.26 | 178.83 | 310.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3703.23 | 25.16 | 89.17 | 291.33 | 2066.10 | 25.21 | 136.33 | 254.67 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:39 | 2555.42 | 24.17 | 98.67 | 245.17 | 1338.87 | 23.86 | 112.17 | 206.17 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-07:40 | 2664.96 | 25.60 | 109.17 | 236.33 | 1550.19 | 25.28 | 115.00 | 199.67 |
Annual Sum or Average | 3902.00 | 0.50 | 3682.19 | 24.89 | 1361.50 | 3863.00 | 1873.08 | 24.67 | 1930.50 | 3447.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2555.42 | 24.10 | 89.17 | 236.33 | 1338.87 | 23.86 | 91.00 | 199.67 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4909.29 | 25.60 | 136.17 | 408.83 | 2351.51 | 25.28 | 265.33 | 378.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-08:50 | 595.47 | 16.25 | 0.00 | 224.33 | 393.82 | 18.18 | 11.67 | 167.67 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 713.80 | 17.69 | 0.00 | 243.67 | 488.79 | 19.55 | 22.50 | 182.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 918.74 | 18.90 | 0.33 | 317.33 | 592.96 | 20.47 | 71.00 | 264.33 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1213.87 | 20.07 | 27.83 | 346.33 | 717.50 | 21.43 | 162.67 | 303.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1423.02 | 20.80 | 122.17 | 409.33 | 810.28 | 22.18 | 309.50 | 381.17 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1602.22 | 23.20 | 187.67 | 418.17 | 891.42 | 24.57 | 330.17 | 404.50 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1507.30 | 21.71 | 150.17 | 420.50 | 822.86 | 22.09 | 310.33 | 391.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1188.66 | 19.92 | 56.33 | 380.67 | 732.37 | 21.30 | 198.50 | 347.33 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 1002.45 | 19.37 | 5.83 | 332.17 | 630.13 | 20.85 | 129.83 | 291.67 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 862.02 | 18.69 | 0.00 | 283.83 | 575.96 | 20.42 | 45.50 | 221.67 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:50 | 670.09 | 17.22 | 0.00 | 232.33 | 451.43 | 19.12 | 22.67 | 174.50 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:30 | 613.94 | 16.88 | 0.00 | 220.50 | 402.67 | 18.83 | 9.00 | 158.17 |
Annual Sum or Average | 3902.00 | 0.50 | 1092.82 | 19.59 | 550.33 | 3829.17 | 657.22 | 21.05 | 1623.33 | 3288.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 595.47 | 16.25 | 0.00 | 220.50 | 393.82 | 18.18 | 9.00 | 158.17 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 1602.22 | 23.20 | 187.67 | 420.50 | 891.42 | 24.57 | 330.17 | 404.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:50 | 2984.48 | 26.02 | 126.83 | 253.83 | 1770.90 | 25.65 | 133.50 | 224.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3172.19 | 25.66 | 93.00 | 257.67 | 1734.92 | 25.39 | 95.67 | 218.17 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:19 | 3608.81 | 25.18 | 118.33 | 330.50 | 2034.70 | 25.33 | 141.67 | 297.17 |
April | 296.67 | 0.49 | 0.48 | 03-APR-09:39 | 3431.61 | 23.90 | 96.00 | 349.33 | 1528.21 | 23.39 | 153.83 | 314.50 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2940.01 | 21.32 | 78.33 | 400.17 | 1535.44 | 21.42 | 232.50 | 369.50 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:49 | 3496.73 | 18.83 | 12.67 | 405.17 | 1951.98 | 21.15 | 168.83 | 380.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 3001.71 | 21.01 | 72.83 | 408.00 | 1610.09 | 21.23 | 213.83 | 380.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:10 | 3872.10 | 21.95 | 85.67 | 381.17 | 1723.36 | 21.18 | 141.00 | 358.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 3390.09 | 24.80 | 134.33 | 337.17 | 1823.84 | 24.99 | 184.00 | 312.50 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:00 | 4392.26 | 27.03 | 109.17 | 296.50 | 1699.80 | 25.21 | 133.33 | 262.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 3033.33 | 26.56 | 116.00 | 255.17 | 1718.15 | 26.23 | 130.00 | 218.00 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-08:30 | 2499.97 | 26.36 | 113.50 | 245.17 | 1423.68 | 25.93 | 125.00 | 218.00 |
Annual Sum or Average | 3902.00 | 0.50 | 3323.52 | 23.55 | 1156.67 | 3919.83 | 1716.35 | 23.53 | 1853.17 | 3554.50 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2499.97 | 18.83 | 12.67 | 245.17 | 1423.68 | 21.15 | 95.67 | 218.00 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4392.26 | 27.03 | 134.33 | 408.00 | 2034.70 | 26.23 | 232.50 | 380.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.49 | 0.48 | 01-JAN-07:49 | 10685.00 | 39.40 | 274.17 | 267.83 | 5820.47 | 33.44 | 205.33 | 261.50 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14277.76 | 39.10 | 241.00 | 264.83 | 2507.54 | 21.18 | 69.33 | 246.33 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-06:00 | 2974.27 | 14.41 | 10.33 | 330.00 | 1728.54 | 17.52 | 10.00 | 296.83 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2216.62 | 14.45 | 0.00 | 341.83 | 1340.08 | 17.94 | 6.50 | 307.17 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:00 | 1982.31 | 14.59 | 0.00 | 395.50 | 1139.40 | 18.05 | 0.00 | 363.83 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1633.90 | 14.36 | 0.00 | 394.67 | 1018.56 | 17.91 | 0.00 | 358.67 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 1815.30 | 14.32 | 0.00 | 398.33 | 1071.00 | 17.79 | 0.00 | 363.33 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1957.77 | 14.05 | 0.00 | 372.00 | 1239.49 | 17.58 | 4.50 | 342.17 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3122.01 | 15.92 | 29.50 | 334.33 | 1523.05 | 17.64 | 3.00 | 308.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13902.78 | 36.28 | 240.33 | 300.67 | 2120.24 | 17.73 | 6.83 | 280.17 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12219.63 | 39.50 | 256.00 | 265.83 | 3793.12 | 27.15 | 131.83 | 246.67 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 10027.02 | 39.81 | 250.67 | 258.50 | 8141.75 | 40.34 | 247.17 | 249.67 |
Annual Sum or Average | 3902.00 | 0.50 | 5506.83 | 22.61 | 1302.00 | 3924.33 | 2333.48 | 21.17 | 684.50 | 3624.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1633.90 | 14.05 | 0.00 | 258.50 | 1018.56 | 17.52 | 0.00 | 246.33 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14277.76 | 39.81 | 274.17 | 398.33 | 8141.75 | 40.34 | 247.17 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2685.90 | 22.69 | 99.83 | 244.33 | 1554.80 | 22.93 | 82.67 | 215.83 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 4038.64 | 22.76 | 84.33 | 254.33 | 2428.35 | 23.21 | 64.17 | 215.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3892.10 | 21.69 | 83.50 | 322.50 | 2204.36 | 22.48 | 61.67 | 288.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4288.56 | 22.48 | 96.17 | 343.83 | 1924.28 | 21.93 | 52.50 | 311.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:40 | 3391.03 | 21.05 | 111.67 | 403.00 | 1889.40 | 22.26 | 83.83 | 372.50 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 4035.22 | 20.66 | 109.00 | 407.33 | 2366.78 | 22.74 | 91.67 | 381.00 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-04:00 | 3630.30 | 20.90 | 116.33 | 409.17 | 2008.16 | 21.94 | 84.67 | 380.33 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:40 | 4967.40 | 22.32 | 131.00 | 375.67 | 2050.25 | 21.48 | 70.83 | 346.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 4074.79 | 21.87 | 108.33 | 334.50 | 1676.92 | 21.75 | 61.50 | 314.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3767.37 | 22.31 | 79.83 | 292.33 | 2150.51 | 23.08 | 56.17 | 260.67 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:39 | 2571.46 | 20.75 | 70.50 | 246.00 | 1403.86 | 21.89 | 66.00 | 209.33 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-07:40 | 2708.57 | 23.38 | 93.17 | 237.17 | 1605.38 | 23.65 | 85.33 | 204.00 |
Annual Sum or Average | 3902.00 | 0.50 | 3732.74 | 21.79 | 1183.67 | 3870.17 | 1955.04 | 22.37 | 861.00 | 3500.17 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2571.46 | 20.66 | 70.50 | 237.17 | 1403.86 | 21.48 | 52.50 | 204.00 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4967.40 | 23.38 | 131.00 | 409.17 | 2428.35 | 23.65 | 91.67 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-08:50 | 605.89 | 10.47 | 0.00 | 225.50 | 419.79 | 14.30 | 0.00 | 179.00 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 729.56 | 12.04 | 0.00 | 243.83 | 522.05 | 15.89 | 0.00 | 190.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 938.16 | 13.54 | 0.00 | 317.67 | 632.94 | 17.13 | 0.00 | 271.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1236.42 | 14.68 | 0.00 | 346.67 | 764.94 | 18.15 | 4.83 | 307.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1489.72 | 15.07 | 2.33 | 410.00 | 862.95 | 18.58 | 9.17 | 384.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1635.23 | 18.38 | 64.83 | 418.50 | 951.74 | 21.60 | 74.67 | 407.17 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:19 | 1536.54 | 16.36 | 29.33 | 420.83 | 885.87 | 19.74 | 39.50 | 396.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1239.66 | 14.52 | 0.00 | 383.00 | 782.14 | 18.08 | 12.83 | 352.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 1023.06 | 14.04 | 0.00 | 332.67 | 672.18 | 17.58 | 0.00 | 298.33 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:49 | 879.28 | 13.32 | 0.00 | 285.17 | 614.60 | 17.02 | 0.00 | 231.33 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 682.05 | 11.52 | 0.00 | 232.83 | 481.30 | 15.35 | 0.00 | 181.67 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:20 | 622.87 | 11.09 | 0.00 | 221.33 | 428.69 | 14.94 | 0.00 | 170.17 |
Annual Sum or Average | 3902.00 | 0.50 | 1121.18 | 14.15 | 96.50 | 3838.00 | 701.96 | 17.72 | 141.00 | 3370.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 605.89 | 10.47 | 0.00 | 221.33 | 419.79 | 14.30 | 0.00 | 170.17 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 1635.23 | 18.38 | 64.83 | 420.83 | 951.74 | 21.60 | 74.67 | 407.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:39 | 3033.29 | 23.85 | 109.00 | 254.17 | 1829.71 | 24.04 | 95.83 | 227.83 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3239.31 | 23.03 | 81.50 | 258.83 | 1813.74 | 23.35 | 62.50 | 224.33 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:19 | 3678.14 | 22.44 | 99.83 | 330.50 | 2114.56 | 23.14 | 74.17 | 300.83 |
April | 296.67 | 0.49 | 0.48 | 03-APR-09:39 | 3489.66 | 20.84 | 85.17 | 349.67 | 1605.43 | 20.66 | 38.33 | 318.00 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-06:19 | 3653.94 | 18.84 | 82.17 | 401.17 | 1611.57 | 18.17 | 0.00 | 372.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:49 | 3533.70 | 14.20 | 1.83 | 405.50 | 2040.72 | 17.76 | 0.00 | 383.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 3034.76 | 17.12 | 56.83 | 408.00 | 1685.48 | 17.94 | 0.17 | 383.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:10 | 3927.49 | 18.44 | 79.17 | 381.17 | 1803.89 | 17.92 | 7.83 | 361.67 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 3447.31 | 21.70 | 109.83 | 336.83 | 1899.40 | 22.69 | 80.17 | 314.50 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:00 | 4403.67 | 23.44 | 93.83 | 296.67 | 1784.34 | 23.02 | 54.50 | 268.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 3084.97 | 24.31 | 98.50 | 255.67 | 1784.70 | 24.54 | 86.00 | 221.00 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-08:20 | 2544.89 | 24.22 | 96.50 | 245.17 | 1480.43 | 24.36 | 86.00 | 223.00 |
Annual Sum or Average | 3902.00 | 0.50 | 3442.36 | 20.43 | 994.17 | 3923.33 | 1792.15 | 20.94 | 585.50 | 3599.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2544.89 | 14.20 | 1.83 | 245.17 | 1480.43 | 17.76 | 0.00 | 221.00 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4403.67 | 24.31 | 109.83 | 408.00 | 2114.56 | 24.54 | 95.83 | 383.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.49 | 0.48 | 01-JAN-07:49 | 10686.07 | 39.39 | 274.17 | 267.83 | 5822.39 | 33.43 | 205.33 | 261.50 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14279.23 | 39.09 | 241.00 | 264.83 | 2509.42 | 21.16 | 69.33 | 246.33 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-06:00 | 2976.87 | 14.38 | 10.33 | 330.00 | 1730.45 | 17.51 | 9.67 | 297.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2219.65 | 14.43 | 0.00 | 341.83 | 1341.97 | 17.93 | 6.33 | 307.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:00 | 1985.27 | 14.56 | 0.00 | 395.50 | 1141.19 | 18.03 | 0.00 | 363.83 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1635.82 | 14.33 | 0.00 | 394.67 | 1019.87 | 17.90 | 0.00 | 358.67 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 1817.83 | 14.29 | 0.00 | 398.33 | 1072.58 | 17.78 | 0.00 | 363.33 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1960.10 | 14.02 | 0.00 | 372.00 | 1241.02 | 17.56 | 4.50 | 342.17 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3124.95 | 15.89 | 29.50 | 334.33 | 1525.02 | 17.62 | 2.83 | 308.67 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13905.13 | 36.27 | 240.33 | 300.67 | 2122.44 | 17.71 | 6.83 | 280.50 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12220.73 | 39.49 | 256.00 | 265.83 | 3795.33 | 27.14 | 131.83 | 246.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 10027.92 | 39.80 | 250.67 | 258.50 | 8143.87 | 40.34 | 247.17 | 249.83 |
Annual Sum or Average | 3902.00 | 0.50 | 5509.02 | 22.58 | 1302.00 | 3924.33 | 2335.29 | 21.16 | 683.83 | 3626.00 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1635.82 | 14.02 | 0.00 | 258.50 | 1019.87 | 17.51 | 0.00 | 246.33 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14279.23 | 39.80 | 274.17 | 398.33 | 8143.87 | 40.34 | 247.17 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2686.48 | 22.67 | 99.83 | 244.33 | 1555.61 | 22.91 | 82.50 | 215.83 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 4039.16 | 22.73 | 84.33 | 254.33 | 2429.31 | 23.20 | 64.17 | 215.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3893.04 | 21.66 | 83.50 | 322.50 | 2205.64 | 22.47 | 61.67 | 288.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4290.43 | 22.45 | 96.17 | 344.00 | 1926.03 | 21.92 | 52.50 | 311.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:40 | 3393.45 | 21.02 | 111.67 | 403.00 | 1891.34 | 22.25 | 83.83 | 372.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 4037.00 | 20.63 | 109.00 | 407.33 | 2368.51 | 22.73 | 91.67 | 381.00 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-04:00 | 3632.51 | 20.87 | 116.33 | 409.17 | 2010.02 | 21.93 | 84.67 | 380.33 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:40 | 4969.13 | 22.29 | 131.00 | 375.83 | 2151.09 | 21.65 | 73.83 | 346.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 4076.27 | 21.84 | 108.33 | 334.50 | 2330.39 | 23.42 | 86.83 | 314.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3768.21 | 22.28 | 79.83 | 292.50 | 2151.88 | 23.06 | 56.17 | 260.83 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:39 | 2572.09 | 20.72 | 70.50 | 246.17 | 1404.83 | 21.87 | 65.50 | 209.83 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-07:40 | 2709.14 | 23.35 | 93.17 | 237.17 | 1606.27 | 23.63 | 85.17 | 204.17 |
Annual Sum or Average | 3902.00 | 0.50 | 3734.17 | 21.76 | 1183.67 | 3870.83 | 2025.68 | 22.53 | 888.50 | 3501.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2572.09 | 20.63 | 70.50 | 237.17 | 1404.83 | 21.65 | 52.50 | 204.17 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4969.13 | 23.35 | 131.00 | 409.17 | 2429.31 | 23.63 | 91.67 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-08:50 | 606.19 | 10.44 | 0.00 | 225.50 | 420.21 | 14.28 | 0.00 | 179.17 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 729.85 | 12.01 | 0.00 | 244.00 | 522.52 | 15.87 | 0.00 | 190.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 938.81 | 13.50 | 0.00 | 317.67 | 633.62 | 17.11 | 0.00 | 271.83 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1237.62 | 14.65 | 0.00 | 346.67 | 765.93 | 18.14 | 4.50 | 307.83 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1491.35 | 15.04 | 2.33 | 410.00 | 864.18 | 18.57 | 8.67 | 384.83 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1636.46 | 18.35 | 64.83 | 418.50 | 952.84 | 21.58 | 73.83 | 407.33 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:19 | 1538.06 | 16.33 | 29.33 | 420.83 | 887.06 | 19.72 | 39.00 | 396.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1240.60 | 14.49 | 0.00 | 383.00 | 783.04 | 18.06 | 12.83 | 352.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 1023.86 | 14.01 | 0.00 | 332.83 | 672.96 | 17.57 | 0.00 | 298.33 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:49 | 879.67 | 13.29 | 0.00 | 285.50 | 615.19 | 17.00 | 0.00 | 232.00 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 682.30 | 11.48 | 0.00 | 232.83 | 481.75 | 15.33 | 0.00 | 181.83 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:20 | 623.15 | 11.06 | 0.00 | 221.33 | 429.13 | 14.92 | 0.00 | 170.17 |
Annual Sum or Average | 3902.00 | 0.50 | 1122.06 | 14.12 | 96.50 | 3838.67 | 702.79 | 17.71 | 138.83 | 3372.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 606.19 | 10.44 | 0.00 | 221.33 | 420.21 | 14.28 | 0.00 | 170.17 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 1636.46 | 18.35 | 64.83 | 420.83 | 952.84 | 21.58 | 73.83 | 407.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:39 | 3033.94 | 23.82 | 109.00 | 254.17 | 1830.53 | 24.03 | 95.67 | 228.17 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3239.90 | 23.00 | 81.50 | 258.83 | 1814.69 | 23.33 | 62.33 | 224.67 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:19 | 3679.33 | 22.41 | 99.83 | 330.50 | 2115.92 | 23.13 | 74.17 | 301.33 |
April | 296.67 | 0.49 | 0.48 | 03-APR-09:39 | 3491.63 | 20.81 | 85.17 | 349.67 | 1607.10 | 20.65 | 38.33 | 318.00 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-06:19 | 3656.58 | 18.81 | 82.17 | 401.17 | 1613.54 | 18.15 | 0.00 | 372.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:49 | 3535.53 | 14.16 | 1.83 | 405.50 | 2042.40 | 17.74 | 0.00 | 383.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 3037.12 | 17.09 | 56.83 | 408.17 | 1687.31 | 17.93 | 0.00 | 383.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:10 | 3929.02 | 18.41 | 79.17 | 381.17 | 1805.37 | 17.91 | 7.83 | 361.67 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 3448.94 | 21.67 | 109.83 | 337.00 | 1900.97 | 22.68 | 80.17 | 314.67 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:00 | 4404.62 | 23.41 | 93.83 | 296.83 | 1785.56 | 23.00 | 54.50 | 269.00 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 3085.56 | 24.28 | 98.50 | 255.67 | 1785.62 | 24.53 | 85.67 | 221.17 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-08:20 | 2545.45 | 24.20 | 96.50 | 245.17 | 1481.28 | 24.34 | 86.00 | 223.17 |
Annual Sum or Average | 3902.00 | 0.50 | 3443.87 | 20.40 | 994.17 | 3923.83 | 1793.58 | 20.92 | 584.67 | 3601.17 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2545.45 | 14.16 | 1.83 | 245.17 | 1481.28 | 17.74 | 0.00 | 221.17 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4404.62 | 24.28 | 109.83 | 408.17 | 2115.92 | 24.53 | 95.67 | 383.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121565E+11 | 50697.68 | 05-JAN-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115279E+11 | 35116.39 | 11-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.672653E+10 | 34222.11 | 04-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.359205E+10 | 31177.56 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.313139E+09 | 15985.50 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8632.93 | 1.02 | 19-JUN-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8433.14 | 1.04 | 05-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6544.68 | 1.01 | 18-AUG-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.358610E+09 | 19290.16 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.548196E+10 | 38032.96 | 30-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.788829E+10 | 40666.26 | 29-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175287E+11 | 58052.97 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.655737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6544.68 | 1.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175287E+11 | 58052.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263578E+09 | 14571.56 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251699E+09 | 14540.72 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12270745.78 | 13800.70 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5971726.74 | 13170.55 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58087889.31 | 14268.11 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97922309.73 | 14554.59 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648024E+09 | 14584.20 | 19-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648024E+09 | 14584.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160991E+09 | 14254.92 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223223E+09 | 14447.42 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27084707.04 | 13902.99 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17906286.37 | 14467.85 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73108718.72 | 14170.93 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113757E+09 | 14459.14 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.511246E+09 | 14494.30 | 19-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.511246E+09 | 14494.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.268530E+09 | 19554.85 | 31-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.428844E+09 | 19497.47 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95780485.30 | 18724.32 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97710755.97 | 19576.62 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204131E+09 | 19600.79 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181682E+09 | 19569.33 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.610877E+09 | 19488.15 | 19-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610877E+09 | 19600.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25247649.45 | 13129.49 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7941289.79 | 9368.80 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8586.68 | 114.49 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15582723.66 | 13122.88 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48780249.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25247649.45 | 13129.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151139E+12 | 490395.12 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150690E+12 | 400504.17 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102337E+12 | 317276.82 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647223E+11 | 327076.10 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.628291E+10 | 163464.28 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457732E+10 | 184865.25 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.742081E+11 | 374244.45 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123310E+12 | 404175.79 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216592E+12 | 571675.10 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893859E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216592E+12 | 571675.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110214E+10 | 514367.05 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221801E+09 | 345016.84 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241729E+10 | 520672.32 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241729E+10 | 520672.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233720E+11 | 142803.15 | 27-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307073E+11 | 134164.32 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155436E+11 | 139439.83 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786512E+10 | 131631.47 | 15-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416444E+09 | 131577.02 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143984E+09 | 141865.68 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.962928E+10 | 142666.27 | 17-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180402E+11 | 131667.39 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479180E+11 | 143590.33 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479180E+11 | 143590.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.990942E+10 | 183202.41 | 06-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140302E+11 | 183368.33 | 07-FEB-11:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758816E+10 | 183176.98 | 23-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394612E+10 | 183501.02 | 24-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157584E+09 | 176701.84 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65346117.39 | 115271.35 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.582034E+10 | 183399.55 | 30-OCT-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.876010E+10 | 183343.36 | 01-NOV-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239411E+11 | 184048.31 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.239411E+11 | 184048.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.772853E+10 | 200187.43 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152453E+11 | 202244.91 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104764E+11 | 200752.50 | 22-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.641042E+10 | 200732.49 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.465086E+09 | 200427.20 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127511E+09 | 152078.31 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782995E+10 | 200689.49 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.802260E+10 | 200690.00 | 01-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219721E+11 | 202208.29 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.782779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.219721E+11 | 202244.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.794128E+10 | 188240.21 | 06-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109581E+11 | 188346.41 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.579346E+10 | 188006.92 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322317E+10 | 188394.01 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166117E+09 | 91346.83 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90815975.55 | 114283.38 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468665E+10 | 188364.86 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656243E+10 | 188366.79 | 02-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191281E+11 | 189245.67 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.585502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191281E+11 | 189245.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179788E+11 | 53742.66 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176236E+11 | 41806.82 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122881E+11 | 36577.28 | 29-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771611E+10 | 35157.93 | 03-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.959147E+09 | 18988.62 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2108156.36 | 2296.70 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.622701E+09 | 21635.97 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.938344E+10 | 43438.01 | 30-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146119E+11 | 47130.42 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244043E+11 | 57662.00 | 23-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.244043E+11 | 57662.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.440819E+10 | 73888.43 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.452011E+10 | 73583.98 | 09-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225141E+10 | 73933.20 | 21-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224886E+10 | 73568.06 | 24-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176502E+09 | 73088.33 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179160E+10 | 73526.56 | 30-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249625E+10 | 73950.62 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.685859E+10 | 73247.26 | 26-DEC-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.685859E+10 | 73950.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.641168E+10 | 15832.85 | 05-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666906E+10 | 15231.30 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.423907E+10 | 15255.48 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274944E+10 | 15249.57 | 24-APR-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264048E+09 | 15236.72 | 01-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116316E+09 | 15134.67 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.301347E+10 | 15246.74 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.474738E+10 | 15254.94 | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.987253E+10 | 17138.83 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.987253E+10 | 17138.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297278E+10 | 20219.05 | 28-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328547E+10 | 20182.17 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217053E+10 | 20246.36 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149770E+10 | 20157.69 | 24-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112282E+09 | 20257.19 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49273765.52 | 20043.76 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180955E+10 | 20137.05 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237387E+10 | 20210.30 | 13-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.534911E+10 | 20121.50 | 22-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.534911E+10 | 20257.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272199E+10 | 22044.13 | 03-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381168E+10 | 21985.47 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306487E+10 | 22109.96 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237139E+10 | 22101.27 | 24-APR-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274853E+09 | 21979.76 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80193463.05 | 21766.12 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240336E+10 | 22097.13 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246910E+10 | 22094.57 | 27-NOV-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.538764E+10 | 23069.12 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.538764E+10 | 23069.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242136E+10 | 21970.23 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263175E+10 | 22039.95 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170923E+10 | 21949.85 | 18-MAR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110791E+10 | 21974.35 | 24-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116219E+09 | 22063.91 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47657895.42 | 19342.34 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135028E+10 | 21969.95 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184124E+10 | 22043.17 | 02-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.421783E+10 | 22023.48 | 08-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.421783E+10 | 22063.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97.85 | 0.82 | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 124.07 | 1.03 | 15-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94.37 | 0.63 | 09-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 316.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 124.07 | 1.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.116365E+11 | 0.116365E+11 | 64806.10 | 24-JAN-14:50 | 64806.10 | 0.00 |
February | 0.00 | 0.00 | 0.103866E+11 | 0.103866E+11 | 60136.94 | 17-FEB-15:00 | 60136.94 | 0.00 |
March | 0.00 | 0.00 | 0.148699E+11 | 0.148699E+11 | 92628.46 | 13-MAR-16:00 | 92628.46 | 0.00 |
April | 0.00 | 0.00 | 0.108664E+11 | 0.108664E+11 | 74734.27 | 19-APR-13:30 | 74734.27 | 0.01 |
May | 0.00 | 0.00 | 0.312399E+11 | 0.312399E+11 | 100360.82 | 31-MAY-14:50 | 100360.82 | 0.06 |
June | 0.00 | 0.00 | 0.102542E+12 | 0.102380E+12 | 172058.19 | 26-JUN-14:43 | 172058.19 | 0.32 |
July | 0.00 | 0.00 | 0.108714E+12 | 0.106394E+12 | 143505.00 | 27-JUL-09:05 | 141167.77 | 0.37 |
August | 0.00 | 0.00 | 0.110530E+12 | 0.109877E+12 | 141062.90 | 14-AUG-14:50 | 141062.90 | 0.47 |
September | 0.00 | 0.00 | 0.676609E+11 | 0.676609E+11 | 120448.66 | 12-SEP-16:00 | 120448.66 | 0.09 |
October | 0.00 | 0.00 | 0.187059E+11 | 0.187059E+11 | 110894.75 | 10-OCT-15:00 | 110894.75 | 0.00 |
November | 0.00 | 0.00 | 0.160894E+11 | 0.160894E+11 | 77956.43 | 06-NOV-14:00 | 77956.43 | 0.00 |
December | 0.00 | 0.00 | 0.135532E+11 | 0.135532E+11 | 63805.20 | 13-DEC-14:50 | 63805.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.516794E+12 | 0.513659E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.103866E+11 | 0.103866E+11 | 60136.94 | 60136.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110530E+12 | 0.109877E+12 | 172058.19 | 172058.19 | 0.47 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.624285E+11 | 0.624285E+11 | 576457.36 | 20-JAN-15:05 | 576457.36 | 0.00 |
February | 0.00 | 0.00 | 0.491432E+11 | 0.491432E+11 | 437481.19 | 27-FEB-15:05 | 437481.19 | 0.00 |
March | 0.00 | 0.00 | 0.102915E+12 | 0.102915E+12 | 746907.59 | 13-MAR-15:50 | 746907.59 | 0.01 |
April | 0.00 | 0.00 | 0.809565E+11 | 0.809565E+11 | 539276.85 | 20-APR-13:00 | 539276.85 | 0.01 |
May | 0.00 | 0.00 | 0.270001E+12 | 0.270001E+12 | 932020.66 | 16-MAY-14:05 | 932020.66 | 0.06 |
June | 0.00 | 0.00 | 0.882532E+12 | 0.881398E+12 | 1450673.62 | 26-JUN-14:03 | 1450673.62 | 0.30 |
July | 0.00 | 0.00 | 0.887302E+12 | 0.871946E+12 | 1252292.35 | 30-JUL-15:41 | 643162.73 | 0.31 |
August | 0.00 | 0.00 | 0.853399E+12 | 0.850879E+12 | 1254952.68 | 16-AUG-15:10 | 1254952.68 | 0.33 |
September | 0.00 | 0.00 | 0.592200E+12 | 0.592200E+12 | 1122467.66 | 12-SEP-16:00 | 1122467.66 | 0.07 |
October | 0.00 | 0.00 | 0.200885E+12 | 0.200885E+12 | 932295.74 | 11-OCT-14:05 | 932295.74 | 0.01 |
November | 0.00 | 0.00 | 0.848728E+11 | 0.848728E+11 | 697360.14 | 07-NOV-15:05 | 697360.14 | 0.00 |
December | 0.00 | 0.00 | 0.422401E+11 | 0.422401E+11 | 472269.65 | 01-DEC-15:05 | 472269.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.410888E+13 | 0.408986E+13 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.422401E+11 | 0.422401E+11 | 437481.19 | 437481.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.887302E+12 | 0.881398E+12 | 1450673.62 | 1450673.62 | 0.33 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.249133E+10 | 0.249133E+10 | 42016.45 | 20-JAN-14:10 | 42016.45 | 0.00 |
February | 0.00 | 0.00 | 0.323271E+10 | 0.323271E+10 | 38580.97 | 17-FEB-15:30 | 38580.97 | 0.00 |
March | 0.00 | 0.00 | 0.789115E+10 | 0.789115E+10 | 77455.96 | 13-MAR-15:30 | 77455.96 | 0.00 |
April | 0.00 | 0.00 | 0.613926E+10 | 0.613926E+10 | 60410.73 | 20-APR-13:00 | 60410.73 | 0.00 |
May | 0.00 | 0.00 | 0.273888E+11 | 0.273888E+11 | 111449.33 | 31-MAY-15:20 | 111449.33 | 0.06 |
June | 0.00 | 0.00 | 0.992608E+11 | 0.991861E+11 | 194378.21 | 26-JUN-14:43 | 194378.21 | 0.29 |
July | 0.00 | 0.00 | 0.980496E+11 | 0.965201E+11 | 147787.37 | 12-JUL-14:45 | 147787.37 | 0.31 |
August | 0.00 | 0.00 | 0.946481E+11 | 0.944276E+11 | 153174.80 | 16-AUG-15:10 | 153174.80 | 0.31 |
September | 0.00 | 0.00 | 0.614433E+11 | 0.614433E+11 | 134273.98 | 10-SEP-15:11 | 134273.98 | 0.07 |
October | 0.00 | 0.00 | 0.123743E+11 | 0.123743E+11 | 103839.67 | 11-OCT-15:00 | 103839.67 | 0.00 |
November | 0.00 | 0.00 | 0.585095E+10 | 0.585095E+10 | 57682.25 | 07-NOV-15:00 | 57682.25 | 0.00 |
December | 0.00 | 0.00 | 0.308651E+10 | 0.308651E+10 | 40634.36 | 01-DEC-14:00 | 40634.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.421857E+12 | 0.420032E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.249133E+10 | 0.249133E+10 | 38580.97 | 38580.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.992608E+11 | 0.991861E+11 | 194378.21 | 194378.21 | 0.31 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.967799E+09 | 0.967799E+09 | 27976.30 | 23-JAN-13:10 | 27976.30 | 0.00 |
February | 0.00 | 0.00 | 90192108.48 | 90192108.48 | 10763.35 | 18-FEB-13:00 | 10763.35 | 0.00 |
March | 0.00 | 0.00 | 0.325668E+10 | 0.325668E+10 | 50600.92 | 13-MAR-14:00 | 50600.92 | 0.00 |
April | 0.00 | 0.00 | 0.349720E+10 | 0.349720E+10 | 35528.87 | 20-APR-13:00 | 35528.87 | 0.00 |
May | 0.00 | 0.00 | 0.166351E+11 | 0.166287E+11 | 53270.73 | 31-MAY-14:00 | 53270.73 | 0.04 |
June | 0.00 | 0.00 | 0.544890E+11 | 0.544492E+11 | 90056.08 | 26-JUN-12:45 | 90056.08 | 0.23 |
July | 0.00 | 0.00 | 0.556007E+11 | 0.550035E+11 | 76373.64 | 17-JUL-10:00 | 76373.64 | 0.26 |
August | 0.00 | 0.00 | 0.577966E+11 | 0.575187E+11 | 92979.80 | 20-AUG-16:08 | 92979.80 | 0.26 |
September | 0.00 | 0.00 | 0.401096E+11 | 0.401059E+11 | 93060.73 | 10-SEP-18:15 | 93060.73 | 0.06 |
October | 0.00 | 0.00 | 0.691819E+10 | 0.691819E+10 | 67829.66 | 09-OCT-15:41 | 67829.66 | 0.00 |
November | 0.00 | 0.00 | 0.259547E+10 | 0.259547E+10 | 49899.05 | 06-NOV-13:10 | 49899.05 | 0.00 |
December | 0.00 | 0.00 | 0.134702E+10 | 0.134702E+10 | 37903.86 | 04-DEC-12:00 | 37903.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.243304E+12 | 0.242379E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 90192108.48 | 90192108.48 | 10763.35 | 10763.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.577966E+11 | 0.575187E+11 | 93060.73 | 93060.73 | 0.26 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.992638E+10 | 0.841438E+10 | 5646.73 | 19-JAN-11:40 | 4887.19 | 0.00 |
February | 0.00 | 0.00 | 0.142982E+11 | 0.122162E+11 | 45834.43 | 18-FEB-14:00 | 45834.43 | 0.00 |
March | 0.00 | 0.00 | 0.393274E+11 | 0.376969E+11 | 244077.89 | 14-MAR-13:00 | 244077.89 | 0.00 |
April | 0.00 | 0.00 | 0.862114E+11 | 0.805003E+11 | 283899.70 | 19-APR-14:00 | 283899.70 | 0.00 |
May | 0.00 | 0.00 | 0.277977E+11 | 0.264495E+11 | 146530.76 | 31-MAY-13:40 | 134410.57 | 0.00 |
June | 0.00 | 0.00 | 0.290028E+12 | 0.260824E+12 | 334776.40 | 18-JUN-10:42 | 216934.50 | 0.00 |
July | 0.00 | 0.00 | 0.604821E+12 | 0.494023E+12 | 459663.70 | 31-JUL-23:05 | 173458.76 | 0.00 |
August | 0.00 | 0.00 | 0.822575E+12 | 0.651515E+12 | 466744.32 | 04-AUG-02:00 | 138888.28 | 0.00 |
September | 0.00 | 0.00 | 0.858736E+11 | 0.811800E+11 | 148161.93 | 13-SEP-13:05 | 136131.94 | 0.00 |
October | 0.00 | 0.00 | 0.310516E+11 | 0.292218E+11 | 231651.67 | 11-OCT-14:00 | 231651.67 | 0.00 |
November | 0.00 | 0.00 | 0.312182E+11 | 0.286938E+11 | 194154.93 | 07-NOV-15:00 | 194154.93 | 0.00 |
December | 0.00 | 0.00 | 0.411774E+11 | 0.406568E+11 | 282869.92 | 01-DEC-14:00 | 282869.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208431E+13 | 0.175139E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.992638E+10 | 0.841438E+10 | 5646.73 | 4887.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.822575E+12 | 0.651515E+12 | 466744.32 | 283899.70 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.461978E+10 | 0.461060E+10 | 3042.82 | 22-JAN-16:35 | 3042.82 | 0.00 |
February | 0.00 | 0.00 | 0.880968E+10 | 0.880561E+10 | 4981.51 | 20-FEB-16:55 | 4981.51 | 0.00 |
March | 0.00 | 0.00 | 0.153768E+11 | 0.153652E+11 | 7782.98 | 31-MAR-24:00 | 7782.98 | 0.00 |
April | 0.00 | 0.00 | 0.199722E+11 | 0.199428E+11 | 8991.88 | 08-APR-18:10 | 8991.88 | 0.00 |
May | 0.00 | 0.00 | 0.586221E+10 | 0.580101E+10 | 4132.14 | 31-MAY-24:00 | 4109.11 | 0.00 |
June | 0.00 | 0.00 | 0.112183E+11 | 0.110983E+11 | 6025.40 | 30-JUN-23:55 | 6025.40 | 0.00 |
July | 0.00 | 0.00 | 0.166541E+11 | 0.165018E+11 | 7902.24 | 31-JUL-24:00 | 7902.24 | 0.00 |
August | 0.00 | 0.00 | 0.216410E+11 | 0.215200E+11 | 9192.87 | 05-AUG-18:53 | 9153.10 | 0.00 |
September | 0.00 | 0.00 | 0.600000E+10 | 0.595248E+10 | 3971.14 | 30-SEP-24:00 | 3971.14 | 0.00 |
October | 0.00 | 0.00 | 0.105580E+11 | 0.105366E+11 | 5642.62 | 09-OCT-16:42 | 5642.62 | 0.00 |
November | 0.00 | 0.00 | 0.148988E+11 | 0.148840E+11 | 7169.29 | 05-NOV-16:13 | 7169.29 | 0.00 |
December | 0.00 | 0.00 | 0.200011E+11 | 0.200011E+11 | 8885.43 | 03-DEC-16:00 | 8885.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155612E+12 | 0.155019E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.461978E+10 | 0.461060E+10 | 3042.82 | 3042.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216410E+11 | 0.215200E+11 | 9192.87 | 9153.10 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.277421E+11 | 0.276556E+11 | 26846.32 | 23-JAN-16:40 | 26846.32 | 0.00 |
February | 0.00 | 0.00 | 0.673604E+11 | 0.673196E+11 | 45223.60 | 17-FEB-17:00 | 44969.26 | 0.00 |
March | 0.00 | 0.00 | 0.132075E+12 | 0.131960E+12 | 72450.11 | 31-MAR-23:30 | 72450.11 | 0.00 |
April | 0.00 | 0.00 | 0.177216E+12 | 0.176922E+12 | 85450.95 | 08-APR-18:00 | 85450.95 | 0.00 |
May | 0.00 | 0.00 | 0.506960E+11 | 0.500976E+11 | 39129.63 | 31-MAY-23:20 | 38614.75 | 0.00 |
June | 0.00 | 0.00 | 0.105389E+12 | 0.104199E+12 | 58375.40 | 30-JUN-23:55 | 58375.40 | 0.00 |
July | 0.00 | 0.00 | 0.157724E+12 | 0.156211E+12 | 74695.76 | 31-JUL-24:00 | 74695.76 | 0.00 |
August | 0.00 | 0.00 | 0.204834E+12 | 0.203629E+12 | 87888.55 | 05-AUG-18:50 | 87609.38 | 0.00 |
September | 0.00 | 0.00 | 0.533062E+11 | 0.528426E+11 | 36128.31 | 30-SEP-23:50 | 36128.31 | 0.00 |
October | 0.00 | 0.00 | 0.897242E+11 | 0.895129E+11 | 51250.56 | 08-OCT-16:42 | 51250.56 | 0.00 |
November | 0.00 | 0.00 | 0.126754E+12 | 0.126605E+12 | 64335.85 | 05-NOV-16:30 | 64231.91 | 0.00 |
December | 0.00 | 0.00 | 0.167293E+12 | 0.167293E+12 | 79385.82 | 03-DEC-16:05 | 79385.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136011E+13 | 0.135425E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.277421E+11 | 0.276556E+11 | 26846.32 | 26846.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204834E+12 | 0.203629E+12 | 87888.55 | 87609.38 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127862E+10 | 0.127131E+10 | 2653.31 | 20-JAN-16:30 | 2653.31 | 0.00 |
February | 0.00 | 0.00 | 0.520467E+10 | 0.520068E+10 | 4515.86 | 17-FEB-17:00 | 4493.38 | 0.00 |
March | 0.00 | 0.00 | 0.119070E+11 | 0.118956E+11 | 7069.73 | 31-MAR-23:20 | 7069.73 | 0.00 |
April | 0.00 | 0.00 | 0.164140E+11 | 0.163847E+11 | 8615.33 | 08-APR-18:00 | 8615.33 | 0.00 |
May | 0.00 | 0.00 | 0.460847E+10 | 0.454888E+10 | 3869.09 | 31-MAY-23:20 | 3817.40 | 0.00 |
June | 0.00 | 0.00 | 0.105616E+11 | 0.104425E+11 | 5841.13 | 30-JUN-23:55 | 5841.13 | 0.00 |
July | 0.00 | 0.00 | 0.158126E+11 | 0.156613E+11 | 7385.85 | 31-JUL-24:00 | 7385.85 | 0.00 |
August | 0.00 | 0.00 | 0.204828E+11 | 0.203625E+11 | 8914.53 | 13-AUG-19:02 | 8914.53 | 0.00 |
September | 0.00 | 0.00 | 0.507558E+10 | 0.502932E+10 | 3775.22 | 10-SEP-17:32 | 3775.22 | 0.00 |
October | 0.00 | 0.00 | 0.767870E+10 | 0.765796E+10 | 5142.45 | 08-OCT-16:42 | 5142.45 | 0.00 |
November | 0.00 | 0.00 | 0.110144E+11 | 0.109997E+11 | 6451.93 | 07-NOV-16:20 | 6451.93 | 0.00 |
December | 0.00 | 0.00 | 0.148553E+11 | 0.148553E+11 | 7827.57 | 01-DEC-16:00 | 7827.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124894E+12 | 0.124310E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127862E+10 | 0.127131E+10 | 2653.31 | 2653.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204828E+11 | 0.203625E+11 | 8914.53 | 8914.53 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 93158.83 | 1371586.15 | 30-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 112955.24 | 1441028.92 | 13-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 65059.39 | 1402667.64 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 41427.77 | 1311071.60 | 24-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 3622.67 | 1666619.34 | 01-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.75 | 2152.53 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.69 | 05-JUL-15:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.67 | 18-AUG-10:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2426.54 | 906639.18 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 47686.54 | 1452354.14 | 23-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 77610.21 | 1522356.43 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 151808.45 | 1604925.36 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 49337.31 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.67 | ||
Maximum of Months | 0.00 | 0.00 | 151808.45 | 1666619.34 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 30024.37 | 777160.55 | 20-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 26688.73 | 512480.72 | 17-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 50859.05 | 1311326.77 | 14-MAR-13:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39742.33 | 748876.55 | 19-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 134486.93 | 1383476.42 | 16-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 451099.92 | 1923730.70 | 22-JUN-09:32 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 443264.48 | 1959355.92 | 27-JUL-09:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 427139.74 | 1847539.36 | 07-AUG-08:05 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 305440.34 | 1433895.15 | 12-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 92856.08 | 1292648.07 | 11-OCT-12:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 44053.50 | 1218706.59 | 07-NOV-15:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23305.92 | 659049.64 | 01-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 173198.36 | 0.00 | ||||
Minimum of Months | 23305.92 | 512480.72 | 0.00 | 0.00 | ||
Maximum of Months | 451099.92 | 1959355.92 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 29388.33 | 777989.84 | 20-JAN-14:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 25976.32 | 517011.23 | 17-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 50847.62 | 1968496.03 | 14-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39083.76 | 748780.31 | 19-APR-13:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 133618.32 | 1389934.75 | 31-MAY-16:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 456739.26 | 2285064.69 | 20-JUN-09:27 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 445776.84 | 2212586.96 | 19-JUL-09:35 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 427723.09 | 2071858.16 | 24-AUG-12:28 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 306499.63 | 1897615.34 | 01-SEP-12:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 92115.12 | 1246881.92 | 11-OCT-10:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43310.82 | 1156183.99 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 22719.16 | 661690.97 | 01-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 173600.50 | 0.00 | ||||
Minimum of Months | 22719.16 | 517011.23 | 0.00 | 0.00 | ||
Maximum of Months | 456739.26 | 2285064.69 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25758.39 | 208479.52 | 20-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 53860.18 | 274611.31 | 18-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 109882.48 | 975729.43 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 172154.40 | 990473.69 | 19-APR-13:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 105902.33 | 958251.58 | 17-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 593773.00 | 1835140.13 | 26-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 884449.88 | 1943766.37 | 16-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1032245.16 | 2113577.79 | 16-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 268978.44 | 1169482.91 | 10-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 90945.04 | 1087512.31 | 11-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 101147.12 | 763566.30 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 125275.86 | 980141.99 | 01-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 299172.35 | 0.00 | ||||
Minimum of Months | 25758.39 | 208479.52 | 0.00 | 0.00 | ||
Maximum of Months | 1032245.16 | 2113577.79 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 16397.83 | 55393.41 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16672.74 | 55560.22 | 16-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17385.30 | 55366.39 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15795.93 | 53635.51 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15455.29 | 51232.29 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14943.78 | 48217.10 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 13299.01 | 45602.23 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14215.83 | 44381.22 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13651.80 | 45813.63 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14230.04 | 48472.70 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15218.74 | 51380.12 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15473.41 | 53829.08 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15220.01 | ||||
Minimum of Months | 0.00 | 0.00 | 13299.01 | 44381.22 | ||
Maximum of Months | 0.00 | 0.00 | 17385.30 | 55560.22 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31214.24 | 885989.21 | 20-JAN-15:00 | 4730.44 | 125944.92 | 10-JAN-06:30 |
February | 25505.02 | 586959.92 | 17-FEB-15:10 | 4354.04 | 130876.47 | 01-FEB-05:01 |
March | 55292.69 | 1947492.64 | 14-MAR-13:05 | 3885.53 | 123152.28 | 02-MAR-10:40 |
April | 43066.85 | 850160.41 | 19-APR-13:30 | 3262.41 | 116863.10 | 03-APR-15:30 |
May | 160282.32 | 2035291.96 | 31-MAY-10:00 | 1349.98 | 105981.13 | 02-MAY-12:40 |
June | 580390.55 | 2587332.33 | 22-JUN-09:32 | 1109.66 | 97875.46 | 09-JUN-05:03 |
July | 573378.66 | 2791026.44 | 27-JUL-09:02 | 1260.93 | 66230.96 | 05-JUL-04:00 |
August | 551708.61 | 2322475.06 | 28-AUG-13:13 | 2553.75 | 78174.27 | 18-AUG-24:00 |
September | 398227.33 | 2080164.31 | 08-SEP-14:30 | 943.21 | 109583.24 | 22-SEP-08:30 |
October | 110612.26 | 2004040.94 | 11-OCT-15:00 | 1883.71 | 115164.60 | 25-OCT-05:50 |
November | 46630.07 | 1916411.15 | 07-NOV-15:05 | 4278.97 | 126124.94 | 21-NOV-10:30 |
December | 22131.32 | 750963.19 | 01-DEC-14:40 | 3817.60 | 124086.18 | 07-DEC-16:00 |
Annual Sum or Average | 217552.90 | 2777.21 | ||||
Minimum of Months | 22131.32 | 586959.92 | 943.21 | 66230.96 | ||
Maximum of Months | 580390.55 | 2791026.44 | 4730.44 | 130876.47 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150224E+11 | 0.96 | 9964.67 | 01-JAN-00:25 | 1.72 |
February | 0.132939E+11 | 0.95 | 9964.67 | 01-FEB-05:01 | 1.72 |
March | 0.156091E+11 | 1.00 | 9964.67 | 01-MAR-05:01 | 1.71 |
April | 0.143690E+11 | 0.95 | 9964.67 | 01-APR-04:03 | 1.71 |
May | 0.151044E+11 | 0.97 | 9964.67 | 01-MAY-04:11 | 1.71 |
June | 0.150726E+11 | 0.99 | 9964.67 | 01-JUN-04:12 | 1.70 |
July | 0.149859E+11 | 0.95 | 9964.67 | 01-JUL-04:12 | 1.72 |
August | 0.164640E+11 | 1.05 | 9964.67 | 01-AUG-04:12 | 1.70 |
September | 0.155377E+11 | 1.03 | 9964.67 | 01-SEP-04:12 | 1.70 |
October | 0.156560E+11 | 1.01 | 9964.67 | 01-OCT-20:30 | 1.69 |
November | 0.146625E+11 | 0.97 | 9964.67 | 01-NOV-04:01 | 1.72 |
December | 0.144901E+11 | 0.93 | 9964.67 | 01-DEC-05:11 | 1.72 |
Annual Sum or Average | 0.180268E+12 | 0.98 | |||
Minimum of Months | 0.132939E+11 | 0.93 | 9964.67 | 1.69 | |
Maximum of Months | 0.164640E+11 | 1.05 | 9964.67 | 1.72 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.459651E+10 | 0.41 | 13015.95 | 07-JAN-06:01 | 1.51 |
February | 0.457072E+10 | 0.43 | 13015.95 | 02-FEB-06:01 | 1.51 |
March | 0.725304E+10 | 0.51 | 17766.42 | 13-MAR-09:20 | 1.84 |
April | 0.783181E+10 | 0.51 | 16570.83 | 07-APR-14:40 | 1.76 |
May | 0.855575E+10 | 0.55 | 14067.66 | 31-MAY-14:50 | 1.57 |
June | 0.145572E+11 | 0.78 | 23247.83 | 05-JUN-10:05 | 2.16 |
July | 0.150542E+11 | 0.82 | 23247.83 | 05-JUL-10:05 | 2.16 |
August | 0.167228E+11 | 0.91 | 23247.83 | 02-AUG-15:20 | 2.16 |
September | 0.102128E+11 | 0.62 | 23247.83 | 05-SEP-15:30 | 2.16 |
October | 0.681675E+10 | 0.49 | 19901.39 | 10-OCT-08:40 | 1.97 |
November | 0.607855E+10 | 0.47 | 15021.08 | 06-NOV-08:30 | 1.65 |
December | 0.529577E+10 | 0.43 | 14649.52 | 04-DEC-15:40 | 1.63 |
Annual Sum or Average | 0.107546E+12 | 0.58 | |||
Minimum of Months | 0.457072E+10 | 0.41 | 13015.95 | 1.51 | |
Maximum of Months | 0.167228E+11 | 0.91 | 23247.83 | 2.16 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.326826E+11 | 0.39 | 90160.30 | 26-JAN-06:03 | 1.26 |
February | 0.311895E+11 | 0.42 | 87999.71 | 28-FEB-06:03 | 1.24 |
March | 0.433720E+11 | 0.45 | 105599.42 | 10-MAR-16:20 | 1.39 |
April | 0.380201E+11 | 0.40 | 100219.68 | 07-APR-15:30 | 1.34 |
May | 0.631721E+11 | 0.49 | 133228.44 | 18-MAY-14:05 | 1.59 |
June | 0.113516E+12 | 0.68 | 216856.44 | 20-JUN-09:23 | 2.15 |
July | 0.106902E+12 | 0.64 | 216856.44 | 18-JUL-10:10 | 2.16 |
August | 0.106788E+12 | 0.64 | 216856.44 | 02-AUG-15:35 | 2.16 |
September | 0.774514E+11 | 0.55 | 182041.71 | 11-SEP-05:02 | 1.94 |
October | 0.435804E+11 | 0.42 | 103853.81 | 20-OCT-15:50 | 1.38 |
November | 0.342636E+11 | 0.40 | 88960.80 | 16-NOV-06:03 | 1.25 |
December | 0.313820E+11 | 0.42 | 60320.92 | 26-DEC-05:11 | 1.00 |
Annual Sum or Average | 0.722319E+12 | 0.49 | |||
Minimum of Months | 0.311895E+11 | 0.39 | 60320.92 | 1.00 | |
Maximum of Months | 0.113516E+12 | 0.68 | 216856.44 | 2.16 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.356035E+10 | 0.48 | 5607.93 | 02-JAN-04:01 | 0.89 |
February | 0.330194E+10 | 0.47 | 5607.93 | 01-FEB-06:01 | 0.89 |
March | 0.424732E+10 | 0.50 | 10560.62 | 15-MAR-16:00 | 1.29 |
April | 0.397512E+10 | 0.46 | 10966.50 | 21-APR-13:50 | 1.31 |
May | 0.561909E+10 | 0.46 | 14075.58 | 31-MAY-15:20 | 1.51 |
June | 0.117925E+11 | 0.65 | 24635.19 | 05-JUN-13:50 | 2.16 |
July | 0.108361E+11 | 0.61 | 24635.19 | 12-JUL-13:30 | 2.16 |
August | 0.107081E+11 | 0.60 | 24635.19 | 02-AUG-15:30 | 2.16 |
September | 0.725260E+10 | 0.51 | 24635.19 | 12-SEP-13:35 | 2.16 |
October | 0.392590E+10 | 0.44 | 9915.15 | 10-OCT-16:00 | 1.24 |
November | 0.328879E+10 | 0.43 | 6866.04 | 07-NOV-16:20 | 1.00 |
December | 0.363238E+10 | 0.49 | 5607.93 | 06-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.721402E+11 | 0.51 | |||
Minimum of Months | 0.328879E+10 | 0.43 | 5607.93 | 0.89 | |
Maximum of Months | 0.117925E+11 | 0.65 | 24635.19 | 2.16 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115209E+12 | 1.65 | 43014.11 | 01-JAN-00:03 | 1.65 |
February | 0.104060E+12 | 1.65 | 43014.11 | 01-FEB-00:10 | 1.65 |
March | 0.115209E+12 | 1.66 | 43014.11 | 01-MAR-00:10 | 1.65 |
April | 0.111493E+12 | 1.66 | 43014.11 | 01-APR-00:10 | 1.66 |
May | 0.115209E+12 | 1.65 | 43014.11 | 01-MAY-00:10 | 1.65 |
June | 0.111493E+12 | 1.65 | 43014.11 | 01-JUN-00:10 | 1.65 |
July | 0.115209E+12 | 1.65 | 43014.11 | 01-JUL-00:05 | 1.66 |
August | 0.115209E+12 | 1.65 | 43014.11 | 01-AUG-00:20 | 1.64 |
September | 0.111493E+12 | 1.65 | 43014.11 | 01-SEP-00:10 | 1.65 |
October | 0.115209E+12 | 1.66 | 43014.11 | 01-OCT-00:10 | 1.65 |
November | 0.111493E+12 | 1.66 | 43014.11 | 01-NOV-00:10 | 1.66 |
December | 0.115209E+12 | 1.66 | 43014.11 | 01-DEC-00:10 | 1.66 |
Annual Sum or Average | 0.135649E+13 | 1.65 | |||
Minimum of Months | 0.104060E+12 | 1.65 | 43014.11 | 1.64 | |
Maximum of Months | 0.115209E+12 | 1.66 | 43014.11 | 1.66 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178285E+10 | 1.13 | 665.64 | 01-JAN-00:03 | 1.13 |
February | 0.161032E+10 | 1.13 | 665.64 | 01-FEB-00:10 | 1.13 |
March | 0.178285E+10 | 1.13 | 665.64 | 01-MAR-00:10 | 1.13 |
April | 0.172534E+10 | 1.13 | 665.64 | 01-APR-00:10 | 1.13 |
May | 0.178285E+10 | 1.13 | 665.64 | 01-MAY-00:10 | 1.13 |
June | 0.172534E+10 | 1.13 | 665.64 | 01-JUN-00:10 | 1.13 |
July | 0.178285E+10 | 1.13 | 665.64 | 01-JUL-00:05 | 1.13 |
August | 0.178285E+10 | 1.13 | 665.64 | 01-AUG-00:10 | 1.13 |
September | 0.172534E+10 | 1.13 | 665.64 | 01-SEP-00:10 | 1.13 |
October | 0.178285E+10 | 1.13 | 665.64 | 01-OCT-00:10 | 1.13 |
November | 0.172534E+10 | 1.13 | 665.64 | 01-NOV-00:10 | 1.13 |
December | 0.178285E+10 | 1.13 | 665.64 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.209916E+11 | 1.13 | |||
Minimum of Months | 0.161032E+10 | 1.13 | 665.64 | 1.13 | |
Maximum of Months | 0.178285E+10 | 1.13 | 665.64 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171231E+11 | 1.13 | 6393.02 | 01-JAN-00:03 | 1.13 |
February | 0.154660E+11 | 1.13 | 6393.02 | 01-FEB-00:10 | 1.13 |
March | 0.171231E+11 | 1.13 | 6393.02 | 01-MAR-00:10 | 1.13 |
April | 0.165707E+11 | 1.13 | 6393.02 | 01-APR-00:10 | 1.13 |
May | 0.171231E+11 | 1.13 | 6393.02 | 01-MAY-00:10 | 1.13 |
June | 0.165707E+11 | 1.13 | 6393.02 | 01-JUN-00:10 | 1.13 |
July | 0.171231E+11 | 1.13 | 6393.02 | 01-JUL-00:05 | 1.13 |
August | 0.171231E+11 | 1.13 | 6393.02 | 01-AUG-00:10 | 1.13 |
September | 0.165707E+11 | 1.13 | 6393.02 | 01-SEP-00:10 | 1.13 |
October | 0.171231E+11 | 1.13 | 6393.02 | 01-OCT-00:10 | 1.13 |
November | 0.165707E+11 | 1.13 | 6393.02 | 01-NOV-00:10 | 1.13 |
December | 0.171231E+11 | 1.13 | 6393.02 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.201610E+12 | 1.13 | |||
Minimum of Months | 0.154660E+11 | 1.13 | 6393.02 | 1.13 | |
Maximum of Months | 0.171231E+11 | 1.13 | 6393.02 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174650E+10 | 1.13 | 652.07 | 01-JAN-00:03 | 1.13 |
February | 0.157748E+10 | 1.13 | 652.07 | 01-FEB-00:10 | 1.13 |
March | 0.174650E+10 | 1.13 | 652.07 | 01-MAR-00:10 | 1.13 |
April | 0.169016E+10 | 1.13 | 652.07 | 01-APR-00:10 | 1.13 |
May | 0.174650E+10 | 1.13 | 652.07 | 01-MAY-00:10 | 1.13 |
June | 0.169016E+10 | 1.13 | 652.07 | 01-JUN-00:10 | 1.13 |
July | 0.174650E+10 | 1.13 | 652.07 | 01-JUL-00:05 | 1.13 |
August | 0.174650E+10 | 1.13 | 652.07 | 01-AUG-00:10 | 1.13 |
September | 0.169016E+10 | 1.13 | 652.07 | 01-SEP-00:10 | 1.13 |
October | 0.174650E+10 | 1.13 | 652.07 | 01-OCT-00:10 | 1.13 |
November | 0.169016E+10 | 1.13 | 652.07 | 01-NOV-00:10 | 1.13 |
December | 0.174650E+10 | 1.13 | 652.07 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.205636E+11 | 1.13 | |||
Minimum of Months | 0.157748E+10 | 1.13 | 652.07 | 1.13 | |
Maximum of Months | 0.174650E+10 | 1.13 | 652.07 | 1.13 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 91134455.75 | 82841220.27 | 1537.58 | 05-JAN-07:05 | 1397.66 | 1397.66 | 46.58 | 19.46 |
February | 77798127.06 | 70718497.50 | 2804.30 | 06-FEB-06:02 | 2549.11 | 2549.11 | 46.61 | 25.30 |
March | 33754578.52 | 30682911.88 | 2351.81 | 20-MAR-05:01 | 2137.79 | 2137.79 | 46.16 | 23.46 |
April | 20146400.02 | 18313077.61 | 1078.02 | 17-APR-05:01 | 979.92 | 979.92 | 46.03 | 16.58 |
May | 953214.37 | 866471.86 | 720.03 | 01-MAY-04:11 | 654.51 | 654.51 | 31.17 | 13.83 |
June | 94.79 | 86.16 | 0.11 | 09-JUN-06:10 | 0.10 | 0.10 | 29.75 | 0.02 |
July | 0.27 | 0.25 | 0.00 | 05-JUL-15:30 | 0.00 | 0.00 | 29.74 | 0.00 |
August | 0.21 | 0.19 | 0.00 | 18-AUG-10:20 | 0.00 | 0.00 | 29.74 | 0.00 |
September | 737469.72 | 670359.98 | 447.76 | 22-SEP-05:02 | 407.02 | 407.02 | 40.24 | 10.98 |
October | 37959642.61 | 34505315.13 | 1084.84 | 30-OCT-05:01 | 986.12 | 986.12 | 45.76 | 16.63 |
November | 52669745.13 | 47876798.32 | 1085.35 | 02-NOV-05:01 | 986.58 | 986.58 | 44.84 | 16.64 |
December | 0.311948E+09 | 0.283560E+09 | 3036.59 | 23-DEC-07:07 | 2760.26 | 2760.26 | 47.69 | 26.17 |
Annual Sum or Average | 0.627101E+09 | 0.570035E+09 | ||||||
Minimum of Months | 0.21 | 0.19 | 0.00 | 0.00 | 0.00 | 29.74 | 0.00 | |
Maximum of Months | 0.311948E+09 | 0.283560E+09 | 3036.59 | 2760.26 | 2760.26 | 47.69 | 26.17 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 33684404.85 | 30619124.01 | 700.96 | 20-JAN-15:30 | 637.18 | 637.18 | 6.71 | 19.17 |
February | 19409271.28 | 17643027.59 | 283.80 | 17-FEB-15:05 | 257.97 | 257.97 | 6.70 | 12.54 |
March | 94959868.15 | 86318520.15 | 8797.56 | 14-MAR-13:45 | 7996.98 | 7996.98 | 11.21 | 55.48 |
April | 31243116.27 | 28399992.69 | 451.46 | 19-APR-13:30 | 410.38 | 410.38 | 6.71 | 15.65 |
May | 0.253529E+09 | 0.230457E+09 | 5612.26 | 31-MAY-16:50 | 5101.55 | 5101.55 | 9.13 | 46.43 |
June | 0.174406E+10 | 0.158535E+10 | 9176.97 | 05-JUN-15:40 | 8341.87 | 8341.87 | 6.74 | 56.43 |
July | 0.153292E+10 | 0.139342E+10 | 9176.97 | 18-JUL-10:50 | 8341.87 | 8341.87 | 6.74 | 56.43 |
August | 0.175761E+10 | 0.159767E+10 | 9176.97 | 24-AUG-12:25 | 8341.87 | 8341.87 | 10.55 | 56.43 |
September | 0.814153E+09 | 0.740065E+09 | 8731.73 | 01-SEP-12:10 | 7937.15 | 7937.15 | 10.73 | 55.32 |
October | 0.160877E+09 | 0.146237E+09 | 2395.00 | 11-OCT-10:20 | 2177.06 | 2177.06 | 9.77 | 32.75 |
November | 53117433.62 | 48283747.16 | 1946.18 | 07-NOV-15:00 | 1769.08 | 1769.08 | 9.43 | 30.00 |
December | 19778897.65 | 17979017.96 | 438.91 | 01-DEC-15:00 | 398.97 | 398.97 | 6.71 | 15.44 |
Annual Sum or Average | 0.651534E+10 | 0.592245E+10 | ||||||
Minimum of Months | 19409271.28 | 17643027.59 | 283.80 | 257.97 | 257.97 | 6.70 | 12.54 | |
Maximum of Months | 0.175761E+10 | 0.159767E+10 | 9176.97 | 8341.87 | 8341.87 | 11.21 | 56.43 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.196925E+10 | 0.179005E+10 | 3158.13 | 02-JAN-08:27 | 2870.74 | 2870.74 | 6.71 | 28.22 |
February | 0.194710E+10 | 0.176991E+10 | 3158.13 | 01-FEB-05:01 | 2870.74 | 2870.74 | 6.72 | 28.22 |
March | 0.233172E+10 | 0.211953E+10 | 3158.13 | 01-MAR-05:01 | 2870.74 | 2870.74 | 6.76 | 28.22 |
April | 0.199449E+10 | 0.181299E+10 | 3158.13 | 03-APR-03:07 | 2870.74 | 2870.74 | 6.75 | 28.22 |
May | 0.332479E+10 | 0.302223E+10 | 3158.13 | 01-MAY-04:11 | 2870.74 | 2870.74 | 6.75 | 28.22 |
June | 0.584137E+10 | 0.530981E+10 | 3158.13 | 01-JUN-04:12 | 2870.74 | 2870.74 | 7.47 | 28.22 |
July | 0.663643E+10 | 0.603252E+10 | 3158.13 | 01-JUL-00:05 | 2870.74 | 2870.74 | 6.88 | 28.22 |
August | 0.690967E+10 | 0.628089E+10 | 3158.13 | 01-AUG-01:15 | 2870.74 | 2870.74 | 7.34 | 28.22 |
September | 0.467754E+10 | 0.425188E+10 | 3158.13 | 01-SEP-00:10 | 2870.74 | 2870.74 | 6.80 | 28.22 |
October | 0.260722E+10 | 0.236996E+10 | 3158.13 | 01-OCT-07:20 | 2870.74 | 2870.74 | 6.77 | 28.22 |
November | 0.225621E+10 | 0.205089E+10 | 3158.13 | 01-NOV-14:00 | 2870.74 | 2870.74 | 6.74 | 28.22 |
December | 0.178602E+10 | 0.162349E+10 | 3158.13 | 01-DEC-05:11 | 2870.74 | 2870.74 | 6.80 | 28.22 |
Annual Sum or Average | 0.422818E+11 | 0.384342E+11 | ||||||
Minimum of Months | 0.178602E+10 | 0.162349E+10 | 3158.13 | 2870.74 | 2870.74 | 6.71 | 28.22 | |
Maximum of Months | 0.690967E+10 | 0.628089E+10 | 3158.13 | 2870.74 | 2870.74 | 7.47 | 28.22 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 41687330.05 | 37893783.02 | 3158.13 | 13-MAR-13:50 | 2870.74 | 2870.74 | 15.69 | 14.11 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.76 | 0.00 |
May | 0.342026E+09 | 0.310901E+09 | 3158.13 | 04-MAY-14:00 | 2870.74 | 2870.74 | 15.10 | 14.11 |
June | 0.193151E+10 | 0.175575E+10 | 3158.13 | 01-JUN-11:00 | 2870.74 | 2870.74 | 14.15 | 14.11 |
July | 0.190009E+10 | 0.172718E+10 | 3158.13 | 01-JUL-09:30 | 2870.74 | 2870.74 | 14.74 | 14.11 |
August | 0.187325E+10 | 0.170278E+10 | 3158.13 | 02-AUG-09:50 | 2870.74 | 2870.74 | 16.19 | 14.11 |
September | 0.114493E+10 | 0.104074E+10 | 3158.13 | 01-SEP-10:30 | 2870.74 | 2870.74 | 13.21 | 14.11 |
October | 0.108008E+09 | 98179346.91 | 3158.13 | 10-OCT-10:40 | 2870.74 | 2870.74 | 15.47 | 14.11 |
November | 14211589.79 | 12918335.12 | 3158.13 | 07-NOV-14:30 | 2870.74 | 2870.74 | 15.63 | 14.11 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
Annual Sum or Average | 0.735571E+10 | 0.668634E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.193151E+10 | 0.175575E+10 | 3158.13 | 2870.74 | 2870.74 | 16.19 | 14.11 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.988019E+10 | 0.898109E+10 | 3688.84 | 01-JAN-00:03 | 3353.16 | 3353.16 | 18.66 | 15.56 |
February | 0.892404E+10 | 0.811195E+10 | 3688.84 | 01-FEB-00:10 | 3353.16 | 3353.16 | 19.27 | 15.56 |
March | 0.988019E+10 | 0.898109E+10 | 3688.84 | 01-MAR-00:10 | 3353.16 | 3353.16 | 19.85 | 15.56 |
April | 0.956147E+10 | 0.869138E+10 | 3688.84 | 01-APR-00:10 | 3353.16 | 3353.16 | 20.51 | 15.56 |
May | 0.988019E+10 | 0.898109E+10 | 3688.84 | 01-MAY-00:10 | 3353.16 | 3353.16 | 18.76 | 15.56 |
June | 0.956147E+10 | 0.869138E+10 | 3688.84 | 01-JUN-00:10 | 3353.16 | 3353.16 | 19.46 | 15.56 |
July | 0.988019E+10 | 0.898109E+10 | 3688.84 | 01-JUL-00:05 | 3353.16 | 3353.16 | 32.49 | 15.56 |
August | 0.988019E+10 | 0.898109E+10 | 3688.84 | 01-AUG-00:10 | 3353.16 | 3353.16 | 36.63 | 15.56 |
September | 0.956147E+10 | 0.869138E+10 | 3688.84 | 01-SEP-00:10 | 3353.16 | 3353.16 | 19.51 | 15.56 |
October | 0.988019E+10 | 0.898109E+10 | 3688.84 | 01-OCT-00:10 | 3353.16 | 3353.16 | 19.44 | 15.56 |
November | 0.956147E+10 | 0.869138E+10 | 3688.84 | 01-NOV-00:10 | 3353.16 | 3353.16 | 19.66 | 15.56 |
December | 0.988019E+10 | 0.898109E+10 | 3688.84 | 01-DEC-00:10 | 3353.16 | 3353.16 | 20.23 | 15.56 |
Annual Sum or Average | 0.116331E+12 | 0.105745E+12 | ||||||
Minimum of Months | 0.892404E+10 | 0.811195E+10 | 3688.84 | 3353.16 | 3353.16 | 18.66 | 15.56 | |
Maximum of Months | 0.988019E+10 | 0.898109E+10 | 3688.84 | 3353.16 | 3353.16 | 36.63 | 15.56 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 55.89 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.07 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 55.77 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.13 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 55.59 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 55.53 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.99 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 55.76 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.10 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.58 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 56.52 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.09 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.53 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.10 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.770939E+10 | 0.700784E+10 | 12396.66 | 20-JAN-15:00 | 11268.57 | 11268.57 | 25.29 | 50.59 |
February | 0.762186E+10 | 0.692827E+10 | 12383.62 | 17-FEB-15:10 | 11256.71 | 11256.71 | 23.88 | 50.59 |
March | 0.925676E+10 | 0.841440E+10 | 24802.03 | 14-MAR-13:05 | 22545.04 | 22545.04 | 25.71 | 101.17 |
April | 0.780951E+10 | 0.709884E+10 | 12394.90 | 19-APR-13:30 | 11266.96 | 11266.96 | 25.12 | 50.59 |
May | 0.139783E+11 | 0.127063E+11 | 24806.34 | 31-MAY-10:00 | 22548.97 | 22548.97 | 25.91 | 101.17 |
June | 0.299594E+11 | 0.272330E+11 | 24833.52 | 22-JUN-09:32 | 22573.67 | 22573.67 | 27.22 | 101.17 |
July | 0.328379E+11 | 0.298496E+11 | 24843.56 | 27-JUL-09:02 | 22582.79 | 22582.79 | 27.70 | 101.17 |
August | 0.340577E+11 | 0.309584E+11 | 24820.47 | 28-AUG-13:13 | 22561.81 | 22561.81 | 26.59 | 101.17 |
September | 0.224363E+11 | 0.203946E+11 | 24808.55 | 08-SEP-14:30 | 22550.97 | 22550.97 | 26.02 | 101.17 |
October | 0.106380E+11 | 0.966997E+10 | 24804.81 | 11-OCT-15:00 | 22547.57 | 22547.57 | 25.84 | 101.17 |
November | 0.888962E+10 | 0.808066E+10 | 24800.50 | 07-NOV-15:05 | 22543.65 | 22543.65 | 25.63 | 101.17 |
December | 0.699142E+10 | 0.635520E+10 | 12390.54 | 01-DEC-14:40 | 11263.00 | 11263.00 | 24.65 | 50.59 |
Annual Sum or Average | 0.192186E+12 | 0.174697E+12 | ||||||
Minimum of Months | 0.699142E+10 | 0.635520E+10 | 12383.62 | 11256.71 | 11256.71 | 23.88 | 50.59 | |
Maximum of Months | 0.340577E+11 | 0.309584E+11 | 24843.56 | 22582.79 | 22582.79 | 27.70 | 101.17 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 39.79 | 39.79 | 93158.83 | 1371586.15 | 30-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 40.70 | 40.70 | 112955.24 | 1441028.92 | 13-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 36.37 | 36.37 | 65059.39 | 1402667.64 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32.37 | 32.37 | 41427.77 | 1311071.60 | 24-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.89 | 28.89 | 3622.67 | 1666619.34 | 01-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 29.76 | 29.76 | 0.75 | 2152.53 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 29.74 | 29.74 | 0.00 | 0.69 | 05-JUL-15:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.74 | 29.74 | 0.00 | 0.67 | 18-AUG-10:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 29.74 | 29.74 | 2426.54 | 906639.18 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 31.14 | 31.14 | 47686.54 | 1452354.14 | 23-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 44.09 | 60.00 | 77610.21 | 1522356.43 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 39.17 | 39.17 | 151808.45 | 1604925.36 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 49337.31 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.89 | 28.89 | 0.00 | 0.67 | ||
Maximum of Months | 0.00 | 0.00 | 44.09 | 60.00 | 151808.45 | 1666619.34 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 30024.37 | 777160.55 | 20-JAN-15:00 | 13.28 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 26688.73 | 512480.72 | 17-FEB-15:10 | 11.04 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 50859.05 | 1311326.77 | 14-MAR-13:05 | 12.25 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39742.33 | 748876.55 | 19-APR-13:30 | 13.04 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 134486.93 | 1383476.42 | 16-MAY-12:05 | 12.55 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 451099.92 | 1923730.70 | 22-JUN-09:32 | 14.85 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 443264.48 | 1959355.92 | 27-JUL-09:02 | 15.00 | 6.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 427139.74 | 1847539.36 | 07-AUG-08:05 | 14.52 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 305440.34 | 1433895.15 | 12-SEP-16:00 | 12.77 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 92856.08 | 1292648.07 | 11-OCT-12:05 | 12.17 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 44053.50 | 1218706.59 | 07-NOV-15:30 | 11.86 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23305.92 | 659049.64 | 01-DEC-14:30 | 12.28 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 173198.36 | 0.00 | ||||||
Minimum of Months | 23305.92 | 512480.72 | 11.04 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 451099.92 | 1959355.92 | 15.00 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 29388.33 | 777989.84 | 20-JAN-14:20 | 16.78 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 25976.32 | 517011.23 | 17-FEB-15:05 | 16.56 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 50847.62 | 1968496.03 | 14-MAR-13:50 | 15.18 | 11.44 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39083.76 | 748780.31 | 19-APR-13:20 | 18.30 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 133618.32 | 1389934.75 | 31-MAY-16:30 | 13.93 | 9.48 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 456739.26 | 2285064.69 | 20-JUN-09:27 | 16.62 | 11.65 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 445776.84 | 2212586.96 | 19-JUL-09:35 | 16.12 | 12.41 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 427723.09 | 2071858.16 | 24-AUG-12:28 | 15.47 | 11.08 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 306499.63 | 1897615.34 | 01-SEP-12:10 | 14.90 | 10.71 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 92115.12 | 1246881.92 | 11-OCT-10:20 | 15.80 | 10.10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43310.82 | 1156183.99 | 07-NOV-15:00 | 15.91 | 9.68 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 22719.16 | 661690.97 | 01-DEC-14:20 | 17.16 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 173600.50 | 0.00 | ||||||
Minimum of Months | 22719.16 | 517011.23 | 13.93 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 456739.26 | 2285064.69 | 18.30 | 12.41 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25758.39 | 208479.52 | 20-JAN-14:00 | 22.19 | 21.43 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 53860.18 | 274611.31 | 18-FEB-14:00 | 23.40 | 21.23 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 109882.48 | 975729.43 | 14-MAR-13:00 | 36.14 | 28.45 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 172154.40 | 990473.69 | 19-APR-13:50 | 36.40 | 27.28 | 0.00 | 0.00 | 01-APR-00:10 |
May | 105902.33 | 958251.58 | 17-MAY-14:00 | 35.82 | 31.50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 593773.00 | 1835140.13 | 26-JUN-15:00 | 51.34 | 43.84 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 884449.88 | 1943766.37 | 16-JUL-13:00 | 53.23 | 43.05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1032245.16 | 2113577.79 | 16-AUG-16:00 | 56.18 | 44.17 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 268978.44 | 1169482.91 | 10-SEP-14:00 | 39.60 | 35.24 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 90945.04 | 1087512.31 | 11-OCT-14:00 | 38.14 | 31.09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 101147.12 | 763566.30 | 07-NOV-15:00 | 32.31 | 25.77 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 125275.86 | 980141.99 | 01-DEC-14:00 | 36.21 | 27.21 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 299172.35 | 0.00 | ||||||
Minimum of Months | 25758.39 | 208479.52 | 22.19 | 21.23 | 0.00 | 0.00 | ||
Maximum of Months | 1032245.16 | 2113577.79 | 56.18 | 44.17 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.60 | 57.60 | 16397.83 | 55393.41 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.33 | 56.33 | 16672.74 | 55560.22 | 16-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.26 | 56.26 | 17385.30 | 55366.39 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.73 | 56.73 | 15795.93 | 53635.51 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.50 | 56.50 | 15455.29 | 51232.29 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.13 | 56.13 | 14943.78 | 48217.10 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.50 | 57.50 | 13299.01 | 45602.23 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.30 | 56.30 | 14215.83 | 44381.22 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.51 | 57.51 | 13651.80 | 45813.63 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.96 | 56.96 | 14230.04 | 48472.70 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.73 | 56.73 | 15218.74 | 51380.12 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.46 | 56.46 | 15473.41 | 53829.08 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15220.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.13 | 56.13 | 13299.01 | 44381.22 | ||
Maximum of Months | 0.00 | 0.00 | 57.60 | 57.60 | 17385.30 | 55560.22 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31214.24 | 885989.21 | 20-JAN-15:00 | 25.29 | 21.10 | 4730.44 | 125944.92 | 10-JAN-06:30 |
February | 25505.02 | 586959.92 | 17-FEB-15:10 | 23.88 | 21.10 | 4354.04 | 130876.47 | 01-FEB-05:01 |
March | 55292.69 | 1947492.64 | 14-MAR-13:05 | 25.71 | 21.10 | 3885.53 | 123152.28 | 02-MAR-10:40 |
April | 43066.85 | 850160.41 | 19-APR-13:30 | 25.12 | 21.10 | 3262.41 | 116863.10 | 03-APR-15:30 |
May | 160282.32 | 2035291.96 | 31-MAY-10:00 | 25.91 | 21.10 | 1349.98 | 105981.13 | 02-MAY-12:40 |
June | 580390.55 | 2587332.33 | 22-JUN-09:32 | 27.22 | 21.83 | 1109.66 | 97875.46 | 09-JUN-05:03 |
July | 573378.66 | 2791026.44 | 27-JUL-09:02 | 27.70 | 22.30 | 1260.93 | 66230.96 | 05-JUL-04:00 |
August | 551708.61 | 2322475.06 | 28-AUG-13:13 | 26.59 | 21.86 | 2553.75 | 78174.27 | 18-AUG-24:00 |
September | 398227.33 | 2080164.31 | 08-SEP-14:30 | 26.02 | 21.10 | 943.21 | 109583.24 | 22-SEP-08:30 |
October | 110612.26 | 2004040.94 | 11-OCT-15:00 | 25.84 | 21.10 | 1883.71 | 115164.60 | 25-OCT-05:50 |
November | 46630.07 | 1916411.15 | 07-NOV-15:05 | 25.63 | 21.10 | 4278.97 | 126124.94 | 21-NOV-10:30 |
December | 22131.32 | 750963.19 | 01-DEC-14:40 | 24.65 | 21.10 | 3817.60 | 124086.18 | 07-DEC-16:00 |
Annual Sum or Average | 217552.90 | 2777.21 | ||||||
Minimum of Months | 22131.32 | 586959.92 | 23.88 | 21.10 | 943.21 | 66230.96 | ||
Maximum of Months | 580390.55 | 2791026.44 | 27.70 | 22.30 | 4730.44 | 130876.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.128749E+11 | 0.00 | 0.116365E+11 | 0.459651E+10 | 0.00 | 0.00 |
February | 0.124396E+11 | 0.00 | 0.103866E+11 | 0.457072E+10 | 0.00 | 0.00 |
March | 0.686167E+10 | 0.00 | 0.148699E+11 | 0.725304E+10 | 0.00 | 0.00 |
April | 0.371364E+10 | 0.00 | 0.108664E+11 | 0.783181E+10 | 0.00 | 0.00 |
May | 0.313139E+09 | 0.00 | 0.312399E+11 | 0.855575E+10 | 0.00 | 0.00 |
June | 8632.93 | 0.00 | 0.102542E+12 | 0.145572E+11 | 0.00 | 0.00 |
July | 8433.14 | 0.00 | 0.108714E+12 | 0.150542E+11 | 0.00 | 0.00 |
August | 6544.68 | 0.00 | 0.110530E+12 | 0.167228E+11 | 0.00 | 0.00 |
September | 0.358610E+09 | 0.00 | 0.676609E+11 | 0.102128E+11 | 0.00 | 0.00 |
October | 0.581729E+10 | 0.00 | 0.187059E+11 | 0.681675E+10 | 0.00 | 0.00 |
November | 0.828166E+10 | 0.00 | 0.160894E+11 | 0.607855E+10 | 0.00 | 0.00 |
December | 0.193145E+11 | 0.00 | 0.135532E+11 | 0.529577E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.699749E+11 | 0.00 | 0.516794E+12 | 0.107546E+12 | 0.00 | 0.00 |
Minimum of Months | 6544.68 | 0.00 | 0.103866E+11 | 0.457072E+10 | 0.00 | 0.00 |
Maximum of Months | 0.193145E+11 | 0.00 | 0.110530E+12 | 0.167228E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.200090E+12 | 0.00 | 0.624285E+11 | 0.326826E+11 | 0.00 | 0.00 |
February | 0.222733E+12 | 0.00 | 0.491432E+11 | 0.311895E+11 | 0.00 | 0.00 |
March | 0.141961E+12 | 0.00 | 0.102915E+12 | 0.433720E+11 | 0.00 | 0.00 |
April | 0.861671E+11 | 0.00 | 0.809565E+11 | 0.380201E+11 | 0.00 | 0.00 |
May | 0.748814E+10 | 0.00 | 0.270001E+12 | 0.631721E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.882532E+12 | 0.113516E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.887302E+12 | 0.106902E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.853399E+12 | 0.106788E+12 | 0.00 | 0.00 |
September | 0.500497E+10 | 0.00 | 0.592200E+12 | 0.774514E+11 | 0.00 | 0.00 |
October | 0.102174E+12 | 0.00 | 0.200885E+12 | 0.435804E+11 | 0.00 | 0.00 |
November | 0.164696E+12 | 0.00 | 0.848728E+11 | 0.342636E+11 | 0.00 | 0.00 |
December | 0.331968E+12 | 0.00 | 0.422401E+11 | 0.313820E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.126228E+13 | 0.00 | 0.410888E+13 | 0.722319E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.422401E+11 | 0.311895E+11 | 0.00 | 0.00 |
Maximum of Months | 0.331968E+12 | 0.00 | 0.887302E+12 | 0.113516E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.369148E+11 | 0.00 | 0.249133E+10 | 0.356035E+10 | 0.00 | 0.00 |
February | 0.385417E+11 | 0.00 | 0.323271E+10 | 0.330194E+10 | 0.00 | 0.00 |
March | 0.257232E+11 | 0.00 | 0.789115E+10 | 0.424732E+10 | 0.00 | 0.00 |
April | 0.176914E+11 | 0.00 | 0.613926E+10 | 0.397512E+10 | 0.00 | 0.00 |
May | 0.190305E+10 | 0.00 | 0.273888E+11 | 0.561909E+10 | 0.00 | 0.00 |
June | 2108156.36 | 0.00 | 0.992608E+11 | 0.117925E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.980496E+11 | 0.108361E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.946481E+11 | 0.107081E+11 | 0.00 | 0.00 |
September | 0.916142E+09 | 0.00 | 0.614433E+11 | 0.725260E+10 | 0.00 | 0.00 |
October | 0.197517E+11 | 0.00 | 0.123743E+11 | 0.392590E+10 | 0.00 | 0.00 |
November | 0.285398E+11 | 0.00 | 0.585095E+10 | 0.328879E+10 | 0.00 | 0.00 |
December | 0.560900E+11 | 0.00 | 0.308651E+10 | 0.363238E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.226074E+12 | 0.00 | 0.421857E+12 | 0.721402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.249133E+10 | 0.328879E+10 | 0.00 | 0.00 |
Maximum of Months | 0.560900E+11 | 0.00 | 0.992608E+11 | 0.117925E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.967799E+09 | 0.150224E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 90192108.48 | 0.132939E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.325668E+10 | 0.156091E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.349720E+10 | 0.143690E+11 | 0.00 | 0.00 |
May | 97.85 | 0.00 | 0.166351E+11 | 0.151044E+11 | 0.00 | 0.00 |
June | 124.07 | 0.00 | 0.544890E+11 | 0.150726E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.556007E+11 | 0.149859E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.577966E+11 | 0.164640E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.401096E+11 | 0.155377E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.691819E+10 | 0.156560E+11 | 0.00 | 0.00 |
November | 94.37 | 0.00 | 0.259547E+10 | 0.146625E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.134702E+10 | 0.144901E+11 | 0.00 | 0.00 |
Annual Sum or Average | 316.28 | 0.00 | 0.243304E+12 | 0.180268E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 90192108.48 | 0.132939E+11 | 0.00 | 0.00 |
Maximum of Months | 124.07 | 0.00 | 0.577966E+11 | 0.164640E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.147534E+11 | 0.292436E+12 | 0.00 | 64.13 |
February | 0.00 | 0.00 | 0.201734E+11 | 0.342298E+12 | 0.00 | 86.44 |
March | 0.00 | 0.00 | 0.536703E+11 | 0.393885E+12 | 0.00 | 98.33 |
April | 0.00 | 0.00 | 0.113498E+12 | 0.386524E+12 | 0.00 | 92.16 |
May | 0.00 | 0.00 | 0.386877E+11 | 0.286697E+12 | 0.00 | 59.74 |
June | 0.00 | 0.00 | 0.386027E+12 | 0.304839E+12 | 0.00 | 36.21 |
July | 0.00 | 0.00 | 0.790642E+12 | 0.410953E+12 | 0.00 | 40.89 |
August | 0.00 | 0.00 | 0.106705E+13 | 0.524113E+12 | 0.00 | 61.17 |
September | 0.00 | 0.00 | 0.115885E+12 | 0.300851E+12 | 0.00 | 59.28 |
October | 0.00 | 0.00 | 0.427229E+11 | 0.368825E+12 | 0.00 | 90.00 |
November | 0.00 | 0.00 | 0.426303E+11 | 0.378326E+12 | 0.00 | 95.02 |
December | 0.00 | 0.00 | 0.560823E+11 | 0.397954E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.274182E+13 | 0.438770E+13 | 0.00 | 883.01 |
Minimum of Months | 0.00 | 0.00 | 0.147534E+11 | 0.286697E+12 | 0.00 | 36.21 |
Maximum of Months | 0.00 | 0.00 | 0.106705E+13 | 0.524113E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.574048E+10 | 0.290355E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108286E+11 | 0.362922E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187644E+11 | 0.517045E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241886E+11 | 0.594177E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.728587E+10 | 0.320651E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143166E+11 | 0.482362E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.213234E+11 | 0.645215E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.275190E+11 | 0.766082E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.758452E+10 | 0.330986E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129706E+11 | 0.419541E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181226E+11 | 0.494914E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.243158E+11 | 0.609748E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192960E+12 | 0.583400E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.574048E+10 | 0.290355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.275190E+11 | 0.766082E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.347085E+11 | 0.240895E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.830784E+11 | 0.311840E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.161564E+12 | 0.466120E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.215043E+12 | 0.543979E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.631333E+11 | 0.295603E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.134612E+12 | 0.457943E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202061E+12 | 0.614602E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260654E+12 | 0.729434E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.675289E+11 | 0.307934E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.110471E+12 | 0.378700E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.154561E+12 | 0.443773E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.204026E+12 | 0.538560E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169144E+13 | 0.532938E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.347085E+11 | 0.240895E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260654E+12 | 0.729434E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.160699E+10 | 0.207486E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.643930E+10 | 0.281212E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.145980E+11 | 0.443752E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.199587E+11 | 0.523485E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.575171E+10 | 0.288974E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135055E+11 | 0.463407E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202768E+11 | 0.621073E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260904E+11 | 0.735408E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.644714E+10 | 0.306173E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.947990E+10 | 0.354770E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.134695E+11 | 0.414532E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.181679E+11 | 0.505907E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155792E+12 | 0.514618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.160699E+10 | 0.207486E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260904E+11 | 0.735408E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.459651E+10 | 0.116365E+11 | 0.128749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.457072E+10 | 0.103866E+11 | 0.124396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725304E+10 | 0.148699E+11 | 0.686167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783181E+10 | 0.108664E+11 | 0.371364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.855575E+10 | 0.312399E+11 | 0.313139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145572E+11 | 0.102542E+12 | 8632.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150542E+11 | 0.108714E+12 | 8433.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167228E+11 | 0.110530E+12 | 6544.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102128E+11 | 0.676609E+11 | 0.358610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681675E+10 | 0.187059E+11 | 0.581729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.607855E+10 | 0.160894E+11 | 0.828166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.529577E+10 | 0.135532E+11 | 0.193145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107546E+12 | 0.516794E+12 | 0.699749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.457072E+10 | 0.103866E+11 | 6544.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167228E+11 | 0.110530E+12 | 0.193145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.326826E+11 | 0.624285E+11 | 0.200090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311895E+11 | 0.491432E+11 | 0.222733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433720E+11 | 0.102915E+12 | 0.141961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.380201E+11 | 0.809565E+11 | 0.861671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.631721E+11 | 0.270001E+12 | 0.748814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113516E+12 | 0.882532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106902E+12 | 0.887302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106788E+12 | 0.853399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.774514E+11 | 0.592200E+12 | 0.500497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435804E+11 | 0.200885E+12 | 0.102174E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342636E+11 | 0.848728E+11 | 0.164696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313820E+11 | 0.422401E+11 | 0.331968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722319E+12 | 0.410888E+13 | 0.126228E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311895E+11 | 0.422401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113516E+12 | 0.887302E+12 | 0.331968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.356035E+10 | 0.249133E+10 | 0.369148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330194E+10 | 0.323271E+10 | 0.385417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424732E+10 | 0.789115E+10 | 0.257232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397512E+10 | 0.613926E+10 | 0.176914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.561909E+10 | 0.273888E+11 | 0.190305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117925E+11 | 0.992608E+11 | 2108156.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108361E+11 | 0.980496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107081E+11 | 0.946481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.725260E+10 | 0.614433E+11 | 0.916142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.392590E+10 | 0.123743E+11 | 0.197517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328879E+10 | 0.585095E+10 | 0.285398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363238E+10 | 0.308651E+10 | 0.560900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721402E+11 | 0.421857E+12 | 0.226074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328879E+10 | 0.249133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117925E+11 | 0.992608E+11 | 0.560900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150224E+11 | 0.967799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132939E+11 | 90192108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156091E+11 | 0.325668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143690E+11 | 0.349720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151044E+11 | 0.166351E+11 | 97.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150726E+11 | 0.544890E+11 | 124.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149859E+11 | 0.556007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164640E+11 | 0.577966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155377E+11 | 0.401096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156560E+11 | 0.691819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146625E+11 | 0.259547E+10 | 94.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144901E+11 | 0.134702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180268E+12 | 0.243304E+12 | 316.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132939E+11 | 90192108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164640E+11 | 0.577966E+11 | 124.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.115209E+12 | 0.992638E+10 | 0.00 | 0.00 | 0.00 | 0.171627E+12 | 0.00 | 0.00 |
February | 0.104060E+12 | 0.142982E+11 | 0.00 | 0.00 | 0.00 | 0.231321E+12 | 0.00 | 0.00 |
March | 0.115209E+12 | 0.393274E+11 | 0.00 | 0.00 | 0.00 | 0.263148E+12 | 0.00 | 0.00 |
April | 0.111493E+12 | 0.862114E+11 | 0.00 | 0.00 | 0.00 | 0.246634E+12 | 0.00 | 0.00 |
May | 0.115209E+12 | 0.277977E+11 | 0.00 | 0.00 | 0.00 | 0.159879E+12 | 0.00 | 0.00 |
June | 0.111493E+12 | 0.290028E+12 | 0.00 | 0.00 | 0.00 | 0.969103E+11 | 0.00 | 0.00 |
July | 0.115209E+12 | 0.604821E+12 | 0.00 | 0.00 | 0.00 | 0.109431E+12 | 0.00 | 0.00 |
August | 0.115209E+12 | 0.822575E+12 | 0.00 | 0.00 | 0.00 | 0.163695E+12 | 0.00 | 0.00 |
September | 0.111493E+12 | 0.858736E+11 | 0.00 | 0.00 | 0.00 | 0.158633E+12 | 0.00 | 0.00 |
October | 0.115209E+12 | 0.310516E+11 | 0.00 | 0.00 | 0.00 | 0.240860E+12 | 0.00 | 0.00 |
November | 0.111493E+12 | 0.312182E+11 | 0.00 | 0.00 | 0.00 | 0.254276E+12 | 0.00 | 0.00 |
December | 0.115209E+12 | 0.411774E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.135649E+13 | 0.208431E+13 | 0.00 | 0.00 | 0.00 | 0.236306E+13 | 0.00 | 0.00 |
Minimum of Months | 0.104060E+12 | 0.992638E+10 | 0.00 | 0.00 | 0.00 | 0.969103E+11 | 0.00 | 0.00 |
Maximum of Months | 0.115209E+12 | 0.822575E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178285E+10 | 0.461978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161032E+10 | 0.880968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178285E+10 | 0.153768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172534E+10 | 0.199722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178285E+10 | 0.586221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172534E+10 | 0.112183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178285E+10 | 0.166541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178285E+10 | 0.216410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172534E+10 | 0.600000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178285E+10 | 0.105580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172534E+10 | 0.148988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178285E+10 | 0.200011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209916E+11 | 0.155612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161032E+10 | 0.461978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178285E+10 | 0.216410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.171231E+11 | 0.277421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154660E+11 | 0.673604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171231E+11 | 0.132075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165707E+11 | 0.177216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171231E+11 | 0.506960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165707E+11 | 0.105389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171231E+11 | 0.157724E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171231E+11 | 0.204834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165707E+11 | 0.533062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171231E+11 | 0.897242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165707E+11 | 0.126754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171231E+11 | 0.167293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201610E+12 | 0.136011E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154660E+11 | 0.277421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171231E+11 | 0.204834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174650E+10 | 0.127862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157748E+10 | 0.520467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174650E+10 | 0.119070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169016E+10 | 0.164140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174650E+10 | 0.460847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169016E+10 | 0.105616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174650E+10 | 0.158126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174650E+10 | 0.204828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169016E+10 | 0.507558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174650E+10 | 0.767870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169016E+10 | 0.110144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174650E+10 | 0.148553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205636E+11 | 0.124894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157748E+10 | 0.127862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174650E+10 | 0.204828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.459651E+10 | 0.128749E+11 | 0.116365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.457072E+10 | 0.124396E+11 | 0.103866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725304E+10 | 0.686167E+10 | 0.148699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783181E+10 | 0.371364E+10 | 0.108664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.855575E+10 | 0.313139E+09 | 0.312399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145572E+11 | 8632.93 | 0.102542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150542E+11 | 8433.14 | 0.108714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167228E+11 | 6544.68 | 0.110530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102128E+11 | 0.358610E+09 | 0.676609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681675E+10 | 0.581729E+10 | 0.187059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.607855E+10 | 0.828166E+10 | 0.160894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.529577E+10 | 0.193145E+11 | 0.135532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107546E+12 | 0.699749E+11 | 0.516794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.457072E+10 | 6544.68 | 0.103866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167228E+11 | 0.193145E+11 | 0.110530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.326826E+11 | 0.200090E+12 | 0.624285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311895E+11 | 0.222733E+12 | 0.491432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433720E+11 | 0.141961E+12 | 0.102915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.380201E+11 | 0.861671E+11 | 0.809565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.631721E+11 | 0.748814E+10 | 0.270001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113516E+12 | 0.00 | 0.882532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106902E+12 | 0.00 | 0.887302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106788E+12 | 0.00 | 0.853399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.774514E+11 | 0.500497E+10 | 0.592200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435804E+11 | 0.102174E+12 | 0.200885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342636E+11 | 0.164696E+12 | 0.848728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313820E+11 | 0.331968E+12 | 0.422401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.722319E+12 | 0.126228E+13 | 0.410888E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311895E+11 | 0.00 | 0.422401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113516E+12 | 0.331968E+12 | 0.887302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.356035E+10 | 0.369148E+11 | 0.249133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330194E+10 | 0.385417E+11 | 0.323271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424732E+10 | 0.257232E+11 | 0.789115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397512E+10 | 0.176914E+11 | 0.613926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.561909E+10 | 0.190305E+10 | 0.273888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117925E+11 | 2108156.36 | 0.992608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108361E+11 | 0.00 | 0.980496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107081E+11 | 0.00 | 0.946481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.725260E+10 | 0.916142E+09 | 0.614433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.392590E+10 | 0.197517E+11 | 0.123743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328879E+10 | 0.285398E+11 | 0.585095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363238E+10 | 0.560900E+11 | 0.308651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721402E+11 | 0.226074E+12 | 0.421857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328879E+10 | 0.00 | 0.249133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117925E+11 | 0.560900E+11 | 0.992608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150224E+11 | 0.00 | 0.967799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132939E+11 | 0.00 | 90192108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156091E+11 | 0.00 | 0.325668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143690E+11 | 0.00 | 0.349720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151044E+11 | 97.85 | 0.166351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150726E+11 | 124.07 | 0.544890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149859E+11 | 0.00 | 0.556007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164640E+11 | 0.00 | 0.577966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155377E+11 | 0.00 | 0.401096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156560E+11 | 0.00 | 0.691819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146625E+11 | 94.37 | 0.259547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144901E+11 | 0.00 | 0.134702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180268E+12 | 316.28 | 0.243304E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132939E+11 | 0.00 | 90192108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164640E+11 | 124.07 | 0.577966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.115209E+12 | 0.00 | 0.147534E+11 | 0.00 | 0.482699E+10 | 0.00 | 0.00 | 0.00 | 0.172400E+12 | 0.00 | 0.00 | 0.00 |
February | 0.104060E+12 | 0.00 | 0.201734E+11 | 0.00 | 0.587527E+10 | 0.00 | 0.00 | 0.00 | 0.232363E+12 | 0.00 | 0.00 | 0.00 |
March | 0.115209E+12 | 0.00 | 0.536703E+11 | 0.00 | 0.143429E+11 | 0.00 | 0.00 | 0.00 | 0.264333E+12 | 0.00 | 0.00 | 0.00 |
April | 0.111493E+12 | 0.00 | 0.113498E+12 | 0.00 | 0.272870E+11 | 0.00 | 0.00 | 0.00 | 0.247745E+12 | 0.00 | 0.00 | 0.00 |
May | 0.115209E+12 | 0.00 | 0.386877E+11 | 0.00 | 0.108900E+11 | 0.00 | 0.00 | 0.00 | 0.160598E+12 | 0.00 | 0.00 | 0.00 |
June | 0.111493E+12 | 0.00 | 0.386027E+12 | 0.00 | 0.959994E+11 | 0.00 | 0.00 | 0.00 | 0.973466E+11 | 0.00 | 0.00 | 0.00 |
July | 0.115209E+12 | 0.00 | 0.790642E+12 | 0.00 | 0.185821E+12 | 0.00 | 0.00 | 0.00 | 0.109923E+12 | 0.00 | 0.00 | 0.00 |
August | 0.115209E+12 | 0.00 | 0.106705E+13 | 0.00 | 0.244472E+12 | 0.00 | 0.00 | 0.00 | 0.164432E+12 | 0.00 | 0.00 | 0.00 |
September | 0.111493E+12 | 0.00 | 0.115885E+12 | 0.00 | 0.300117E+11 | 0.00 | 0.00 | 0.00 | 0.159347E+12 | 0.00 | 0.00 | 0.00 |
October | 0.115209E+12 | 0.00 | 0.427229E+11 | 0.00 | 0.116714E+11 | 0.00 | 0.00 | 0.00 | 0.241945E+12 | 0.00 | 0.00 | 0.00 |
November | 0.111493E+12 | 0.00 | 0.426303E+11 | 0.00 | 0.114121E+11 | 0.00 | 0.00 | 0.00 | 0.255421E+12 | 0.00 | 0.00 | 0.00 |
December | 0.115209E+12 | 0.00 | 0.560823E+11 | 0.00 | 0.149049E+11 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135649E+13 | 0.00 | 0.274182E+13 | 0.00 | 0.657515E+12 | 0.00 | 0.00 | 0.00 | 0.237369E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104060E+12 | 0.00 | 0.147534E+11 | 0.00 | 0.482699E+10 | 0.00 | 0.00 | 0.00 | 0.973466E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115209E+12 | 0.00 | 0.106705E+13 | 0.00 | 0.244472E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.178285E+10 | 0.00 | 0.574048E+10 | 0.00 | 0.112069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161032E+10 | 0.00 | 0.108286E+11 | 0.00 | 0.201890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178285E+10 | 0.00 | 0.187644E+11 | 0.00 | 0.338760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172534E+10 | 0.00 | 0.241886E+11 | 0.00 | 0.421643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178285E+10 | 0.00 | 0.728587E+10 | 0.00 | 0.142365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172534E+10 | 0.00 | 0.143166E+11 | 0.00 | 0.309828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178285E+10 | 0.00 | 0.213234E+11 | 0.00 | 0.466930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178285E+10 | 0.00 | 0.275190E+11 | 0.00 | 0.587797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172534E+10 | 0.00 | 0.758452E+10 | 0.00 | 0.158452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178285E+10 | 0.00 | 0.129706E+11 | 0.00 | 0.241256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172534E+10 | 0.00 | 0.181226E+11 | 0.00 | 0.322380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178285E+10 | 0.00 | 0.243158E+11 | 0.00 | 0.431463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209916E+11 | 0.00 | 0.192960E+12 | 0.00 | 0.373483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161032E+10 | 0.00 | 0.574048E+10 | 0.00 | 0.112069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178285E+10 | 0.00 | 0.275190E+11 | 0.00 | 0.587797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.171231E+11 | 0.00 | 0.347085E+11 | 0.00 | 0.696642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154660E+11 | 0.00 | 0.830784E+11 | 0.00 | 0.157180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171231E+11 | 0.00 | 0.161564E+12 | 0.00 | 0.294889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165707E+11 | 0.00 | 0.215043E+12 | 0.00 | 0.378272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171231E+11 | 0.00 | 0.631333E+11 | 0.00 | 0.124372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165707E+11 | 0.00 | 0.134612E+12 | 0.00 | 0.292236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171231E+11 | 0.00 | 0.202061E+12 | 0.00 | 0.443371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171231E+11 | 0.00 | 0.260654E+12 | 0.00 | 0.558204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165707E+11 | 0.00 | 0.675289E+11 | 0.00 | 0.142227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171231E+11 | 0.00 | 0.110471E+12 | 0.00 | 0.207469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165707E+11 | 0.00 | 0.154561E+12 | 0.00 | 0.278066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171231E+11 | 0.00 | 0.204026E+12 | 0.00 | 0.367329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201610E+12 | 0.00 | 0.169144E+13 | 0.00 | 0.331328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154660E+11 | 0.00 | 0.347085E+11 | 0.00 | 0.696642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171231E+11 | 0.00 | 0.260654E+12 | 0.00 | 0.558204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174650E+10 | 0.00 | 0.160699E+10 | 0.00 | 0.328362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157748E+10 | 0.00 | 0.643930E+10 | 0.00 | 0.123464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174650E+10 | 0.00 | 0.145980E+11 | 0.00 | 0.269103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169016E+10 | 0.00 | 0.199587E+11 | 0.00 | 0.354470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174650E+10 | 0.00 | 0.575171E+10 | 0.00 | 0.114324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169016E+10 | 0.00 | 0.135055E+11 | 0.00 | 0.294391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174650E+10 | 0.00 | 0.202768E+11 | 0.00 | 0.446423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174650E+10 | 0.00 | 0.260904E+11 | 0.00 | 0.560758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169016E+10 | 0.00 | 0.644714E+10 | 0.00 | 0.137157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174650E+10 | 0.00 | 0.947990E+10 | 0.00 | 0.180120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169016E+10 | 0.00 | 0.134695E+11 | 0.00 | 0.245516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174650E+10 | 0.00 | 0.181679E+11 | 0.00 | 0.331258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205636E+11 | 0.00 | 0.155792E+12 | 0.00 | 0.308982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157748E+10 | 0.00 | 0.160699E+10 | 0.00 | 0.328362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174650E+10 | 0.00 | 0.260904E+11 | 0.00 | 0.560758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343258E+10 | 0.00 | 0.00 | 0.101272E+09 | 0.00 | 0.00 | 0.599774E+11 | 0.00 | 0.66 |
February | 0.610812E+09 | 0.00 | 0.00 | 93697840.64 | 0.00 | 0.00 | 0.556968E+11 | 0.00 | 0.58 |
March | 0.450125E+09 | 0.00 | 0.00 | 0.112299E+09 | 0.00 | 0.00 | 0.649799E+11 | 0.00 | 0.88 |
April | 0.420644E+09 | 0.00 | 0.00 | 0.103777E+09 | 0.00 | 0.00 | 0.607272E+11 | 0.00 | 0.94 |
May | 0.106328E+09 | 14037711.44 | 0.00 | 0.101538E+09 | 222007.47 | 0.00 | 0.520762E+11 | 0.00 | 1.21 |
June | 38472441.12 | 0.164465E+10 | 0.00 | 74792831.56 | 21300186.79 | 0.00 | 0.205489E+11 | 0.00 | 0.99 |
July | 0.112179E+09 | 0.158395E+10 | 0.00 | 80759668.53 | 61557931.77 | 0.00 | 0.186516E+11 | 0.00 | 0.94 |
August | 0.105058E+09 | 0.156727E+10 | 0.00 | 0.109867E+09 | 27986557.34 | 0.00 | 0.262816E+11 | 0.00 | 1.08 |
September | 0.151348E+09 | 0.305477E+09 | 0.00 | 0.107448E+09 | 20635418.06 | 0.00 | 0.346640E+11 | 0.00 | 1.20 |
October | 0.262234E+09 | 0.00 | 0.00 | 0.128353E+09 | 0.00 | 0.00 | 0.670335E+11 | 0.00 | 0.99 |
November | 0.337920E+09 | 0.00 | 0.00 | 0.124841E+09 | 0.00 | 0.00 | 0.674383E+11 | 0.00 | 0.80 |
December | 0.780065E+10 | 0.00 | 0.00 | 0.108099E+09 | 0.00 | 0.00 | 0.589288E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.138284E+11 | 0.511539E+10 | 0.00 | 0.124674E+10 | 0.131702E+09 | 0.00 | 0.587004E+12 | 0.00 | 0.91 |
Minimum of Months | 38472441.12 | 0.00 | 0.00 | 74792831.56 | 0.00 | 0.00 | 0.186516E+11 | 0.00 | 0.58 |
Maximum of Months | 0.780065E+10 | 0.164465E+10 | 0.00 | 0.128353E+09 | 61557931.77 | 0.00 | 0.674383E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.350671E+10 | 0.00 | 0.00 | 71916970.64 | 0.00 | 0.00 | 0.412121E+11 | 0.00 | 0.40 |
February | 0.333879E+10 | 0.00 | 0.00 | 69621490.16 | 0.00 | 0.00 | 0.381904E+11 | 0.00 | 0.39 |
March | 0.240307E+10 | 0.00 | 0.00 | 94882402.69 | 0.00 | 0.00 | 0.496361E+11 | 0.00 | 0.64 |
April | 0.159565E+10 | 0.00 | 0.00 | 89472970.42 | 0.00 | 0.00 | 0.487327E+11 | 0.00 | 0.73 |
May | 0.221447E+10 | 6605129.51 | 0.00 | 84162830.14 | 794611.60 | 0.00 | 0.387938E+11 | 0.00 | 0.86 |
June | 0.277527E+10 | 0.708361E+09 | 0.00 | 73542467.29 | 50090788.92 | 0.00 | 0.155701E+11 | 0.00 | 0.75 |
July | 0.452084E+10 | 0.691824E+09 | 0.00 | 72024920.36 | 0.159544E+09 | 0.00 | 0.132107E+11 | 0.00 | 0.79 |
August | 0.722419E+10 | 0.695023E+09 | 0.00 | 96853851.84 | 0.249873E+09 | 0.00 | 0.204166E+11 | 0.00 | 0.94 |
September | 0.157134E+10 | 0.137163E+09 | 0.00 | 84675066.88 | 68622320.48 | 0.00 | 0.240958E+11 | 0.00 | 0.78 |
October | 0.278919E+10 | 0.00 | 0.00 | 89591049.52 | 0.00 | 0.00 | 0.464524E+11 | 0.00 | 0.66 |
November | 0.288829E+10 | 0.00 | 0.00 | 90525042.28 | 0.00 | 0.00 | 0.460539E+11 | 0.00 | 0.53 |
December | 0.382631E+10 | 0.00 | 0.00 | 89336610.98 | 0.00 | 0.00 | 0.487444E+11 | 0.00 | 0.44 |
Annual Sum or Average | 0.386541E+11 | 0.223898E+10 | 0.00 | 0.100661E+10 | 0.528925E+09 | 0.00 | 0.431109E+12 | 0.00 | 0.66 |
Minimum of Months | 0.157134E+10 | 0.00 | 0.00 | 69621490.16 | 0.00 | 0.00 | 0.132107E+11 | 0.00 | 0.39 |
Maximum of Months | 0.722419E+10 | 0.708361E+09 | 0.00 | 96853851.84 | 0.249873E+09 | 0.00 | 0.496361E+11 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175235E+12 | 0.00 | 0.00 | 0.255731E+09 | 0.00 | 0.00 | 0.180194E+12 | 0.00 | 0.32 |
February | 0.199177E+12 | 0.00 | 0.00 | 0.179117E+09 | 0.00 | 0.143911E+09 | 0.126597E+12 | 0.00 | 0.31 |
March | 0.146238E+12 | 0.00 | 0.00 | 0.373054E+09 | 0.00 | 6364394.10 | 0.219183E+12 | 0.00 | 0.44 |
April | 0.941314E+11 | 0.00 | 0.00 | 0.327668E+09 | 0.00 | 0.00 | 0.213859E+12 | 0.00 | 0.44 |
May | 0.236362E+11 | 46712941.31 | 0.00 | 0.620261E+09 | 17792984.70 | 0.00 | 0.286841E+12 | 0.00 | 0.67 |
June | 0.128191E+11 | 0.763511E+10 | 0.00 | 0.563265E+09 | 0.606594E+09 | 0.00 | 0.120698E+12 | 0.00 | 0.59 |
July | 0.102065E+11 | 0.714298E+10 | 0.00 | 0.557693E+09 | 0.127122E+10 | 0.00 | 0.998568E+11 | 0.00 | 0.55 |
August | 0.142455E+11 | 0.709205E+10 | 0.00 | 0.718416E+09 | 0.951539E+09 | 0.00 | 0.149429E+12 | 0.00 | 0.61 |
September | 0.135418E+11 | 0.129642E+10 | 0.00 | 0.642235E+09 | 0.501535E+09 | 0.00 | 0.181585E+12 | 0.00 | 0.61 |
October | 0.841987E+11 | 0.00 | 0.00 | 0.469653E+09 | 0.00 | 0.00 | 0.241029E+12 | 0.00 | 0.42 |
November | 0.137306E+12 | 0.00 | 0.00 | 0.300873E+09 | 0.00 | 0.00 | 0.207881E+12 | 0.00 | 0.36 |
December | 0.252885E+12 | 0.00 | 0.00 | 0.156196E+09 | 0.00 | 0.860771E+09 | 0.125028E+12 | 0.00 | 0.32 |
Annual Sum or Average | 0.116362E+13 | 0.232133E+11 | 0.00 | 0.516416E+10 | 0.334868E+10 | 0.101105E+10 | 0.215218E+13 | 0.00 | 0.47 |
Minimum of Months | 0.102065E+11 | 0.00 | 0.00 | 0.156196E+09 | 0.00 | 0.00 | 0.998568E+11 | 0.00 | 0.31 |
Maximum of Months | 0.252885E+12 | 0.763511E+10 | 0.00 | 0.718416E+09 | 0.127122E+10 | 0.860771E+09 | 0.286841E+12 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251579E+11 | 0.00 | 0.00 | 3791592.99 | 0.00 | 0.224741E+10 | 0.322381E+10 | 0.00 | 0.31 |
February | 0.223610E+11 | 0.00 | 0.00 | 3157096.18 | 0.00 | 0.263171E+10 | 0.283978E+10 | 0.00 | 0.28 |
March | 0.197311E+11 | 0.00 | 0.00 | 18334170.01 | 0.00 | 0.781495E+09 | 0.116994E+11 | 0.00 | 0.42 |
April | 0.139495E+11 | 0.00 | 0.00 | 20230849.71 | 0.00 | 0.773306E+09 | 0.142734E+11 | 0.00 | 0.44 |
May | 0.591905E+10 | 420552.64 | 0.00 | 45223805.88 | 108488.44 | 0.106422E+09 | 0.223143E+11 | 0.00 | 0.63 |
June | 0.150437E+10 | 0.537070E+09 | 0.00 | 60661833.40 | 44531632.95 | 0.00 | 0.112514E+11 | 0.00 | 0.61 |
July | 0.106479E+10 | 0.479243E+09 | 0.00 | 60034032.35 | 87940864.70 | 0.00 | 0.940981E+10 | 0.00 | 0.57 |
August | 0.140145E+10 | 0.530550E+09 | 0.00 | 75192678.23 | 80317904.00 | 0.00 | 0.135464E+11 | 0.00 | 0.60 |
September | 0.295492E+10 | 92114925.81 | 0.00 | 54828147.47 | 41895053.64 | 0.00 | 0.138933E+11 | 0.00 | 0.58 |
October | 0.152905E+11 | 0.00 | 0.00 | 19432770.08 | 0.00 | 0.135214E+10 | 0.117430E+11 | 0.00 | 0.42 |
November | 0.221097E+11 | 0.00 | 0.00 | 7943524.67 | 0.00 | 0.119061E+10 | 0.536100E+10 | 0.00 | 0.33 |
December | 0.249084E+11 | 0.00 | 0.00 | 1594669.51 | 0.00 | 0.508363E+10 | 0.138463E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.156353E+12 | 0.163940E+10 | 0.00 | 0.370425E+09 | 0.254794E+09 | 0.141667E+11 | 0.120940E+12 | 0.00 | 0.46 |
Minimum of Months | 0.106479E+10 | 0.00 | 0.00 | 1594669.51 | 0.00 | 0.00 | 0.138463E+10 | 0.00 | 0.28 |
Maximum of Months | 0.251579E+11 | 0.537070E+09 | 0.00 | 75192678.23 | 87940864.70 | 0.508363E+10 | 0.223143E+11 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301232E+10 | 0.00 | 0.00 | 821702.88 | 0.00 | 0.371756E+09 | 0.394512E+09 | 0.00 | 0.26 |
February | 0.281712E+10 | 0.00 | 0.00 | 802929.16 | 0.00 | 0.288202E+09 | 0.460718E+09 | 0.00 | 0.26 |
March | 0.236703E+10 | 0.00 | 0.00 | 3811494.37 | 0.00 | 4326816.55 | 0.205222E+10 | 0.00 | 0.47 |
April | 0.145117E+10 | 0.00 | 0.00 | 5603918.18 | 0.00 | 736929.59 | 0.324213E+10 | 0.00 | 0.61 |
May | 0.676200E+09 | 1886675.13 | 0.00 | 9781263.23 | 99646.67 | 0.00 | 0.432785E+10 | 0.00 | 0.94 |
June | 0.416132E+09 | 0.170420E+09 | 0.00 | 12179185.44 | 5926333.54 | 0.00 | 0.235587E+10 | 0.00 | 1.02 |
July | 0.623302E+09 | 0.173099E+09 | 0.00 | 11711115.41 | 19103907.04 | 0.00 | 0.190864E+10 | 0.00 | 1.03 |
August | 0.976986E+09 | 0.150938E+09 | 0.00 | 14629115.19 | 31334760.99 | 0.00 | 0.261630E+10 | 0.00 | 1.08 |
September | 0.523063E+09 | 33475133.06 | 0.00 | 9860833.89 | 8603930.38 | 0.00 | 0.227129E+10 | 0.00 | 0.79 |
October | 0.193745E+10 | 0.00 | 0.00 | 4107321.63 | 0.00 | 0.115035E+09 | 0.204067E+10 | 0.00 | 0.48 |
November | 0.257785E+10 | 0.00 | 0.00 | 2032015.95 | 0.00 | 0.154291E+09 | 0.985271E+09 | 0.00 | 0.34 |
December | 0.260836E+10 | 0.00 | 0.00 | 954215.66 | 0.00 | 0.881493E+09 | 0.505358E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.199870E+11 | 0.529818E+09 | 0.00 | 76295110.99 | 65068578.61 | 0.181584E+10 | 0.231608E+11 | 0.00 | 0.63 |
Minimum of Months | 0.416132E+09 | 0.00 | 0.00 | 802929.16 | 0.00 | 0.00 | 0.394512E+09 | 0.00 | 0.26 |
Maximum of Months | 0.301232E+10 | 0.173099E+09 | 0.00 | 14629115.19 | 31334760.99 | 0.881493E+09 | 0.432785E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157712E+10 | 0.00 | 0.00 | 3607428.87 | 0.00 | 0.195680E+09 | 0.144317E+10 | 0.00 | 0.37 |
February | 0.132886E+10 | 0.00 | 0.00 | 5186742.87 | 0.00 | 0.263770E+09 | 0.208903E+10 | 0.00 | 0.45 |
March | 0.127027E+10 | 0.00 | 0.00 | 9562329.56 | 0.00 | 21324437.37 | 0.393693E+10 | 0.00 | 0.87 |
April | 0.827689E+09 | 0.00 | 0.00 | 8823999.74 | 0.00 | 21356494.28 | 0.451774E+10 | 0.00 | 1.05 |
May | 0.320285E+09 | 1398633.31 | 0.00 | 12275595.71 | 64408.21 | 0.00 | 0.540265E+10 | 0.00 | 1.58 |
June | 0.231406E+09 | 0.122485E+09 | 0.00 | 15436786.15 | 3942988.81 | 0.00 | 0.318052E+10 | 0.00 | 1.79 |
July | 0.365896E+09 | 0.135626E+09 | 0.00 | 15242382.83 | 9737234.31 | 0.00 | 0.205464E+10 | 0.00 | 1.52 |
August | 0.611428E+09 | 0.111235E+09 | 0.00 | 18062723.94 | 20253720.78 | 0.00 | 0.361929E+10 | 0.00 | 1.81 |
September | 0.253609E+09 | 28544369.43 | 0.00 | 13869756.43 | 5561287.14 | 0.00 | 0.339524E+10 | 0.00 | 1.51 |
October | 0.103664E+10 | 0.00 | 0.00 | 8546791.15 | 0.00 | 0.126612E+09 | 0.315961E+10 | 0.00 | 0.81 |
November | 0.140765E+10 | 0.00 | 0.00 | 4697350.95 | 0.00 | 0.140947E+09 | 0.177531E+10 | 0.00 | 0.49 |
December | 0.146772E+10 | 0.00 | 0.00 | 2726372.16 | 0.00 | 0.615470E+09 | 0.965134E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.106986E+11 | 0.399289E+09 | 0.00 | 0.118038E+09 | 39559639.25 | 0.138516E+10 | 0.355393E+11 | 0.00 | 1.05 |
Minimum of Months | 0.231406E+09 | 0.00 | 0.00 | 2726372.16 | 0.00 | 0.00 | 0.965134E+09 | 0.00 | 0.33 |
Maximum of Months | 0.157712E+10 | 0.135626E+09 | 0.00 | 18062723.94 | 20253720.78 | 0.615470E+09 | 0.540265E+10 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166085E+10 | 0.00 | 0.00 | 25555563.98 | 0.00 | 0.333619E+09 | 0.851082E+10 | 0.00 | 0.87 |
February | 0.145230E+10 | 0.00 | 0.00 | 22271808.53 | 0.00 | 0.439680E+09 | 0.808485E+10 | 0.00 | 0.84 |
March | 0.178823E+10 | 0.00 | 0.00 | 21206010.40 | 0.00 | 61404761.40 | 0.812779E+10 | 0.00 | 1.21 |
April | 0.134519E+10 | 0.00 | 0.00 | 11390640.69 | 0.00 | 80607293.59 | 0.631456E+10 | 0.00 | 1.09 |
May | 0.759534E+09 | 2707455.62 | 0.00 | 12839964.64 | 99653.35 | 0.00 | 0.535998E+10 | 0.00 | 1.20 |
June | 0.439315E+09 | 0.186475E+09 | 0.00 | 13388614.45 | 6139653.79 | 0.00 | 0.219093E+10 | 0.00 | 1.06 |
July | 0.618293E+09 | 0.226046E+09 | 0.00 | 13393461.02 | 13766789.94 | 0.00 | 0.187624E+10 | 0.00 | 1.09 |
August | 0.948625E+09 | 0.226916E+09 | 0.00 | 23800934.65 | 31249756.63 | 0.00 | 0.342007E+10 | 0.00 | 1.40 |
September | 0.434104E+09 | 68067150.15 | 0.00 | 23122107.63 | 8452152.65 | 0.00 | 0.436957E+10 | 0.00 | 1.48 |
October | 0.120423E+10 | 0.00 | 0.00 | 32823232.36 | 0.00 | 0.274126E+09 | 0.910750E+10 | 0.00 | 1.47 |
November | 0.146481E+10 | 0.00 | 0.00 | 31293106.49 | 0.00 | 0.184374E+09 | 0.859653E+10 | 0.00 | 1.07 |
December | 0.166460E+10 | 0.00 | 0.00 | 23200140.83 | 0.00 | 0.707346E+09 | 0.711844E+10 | 0.00 | 0.81 |
Annual Sum or Average | 0.137801E+11 | 0.710212E+09 | 0.00 | 0.254286E+09 | 59708006.36 | 0.208116E+10 | 0.730773E+11 | 0.00 | 1.14 |
Minimum of Months | 0.434104E+09 | 0.00 | 0.00 | 11390640.69 | 0.00 | 0.00 | 0.187624E+10 | 0.00 | 0.81 |
Maximum of Months | 0.178823E+10 | 0.226916E+09 | 0.00 | 32823232.36 | 31249756.63 | 0.707346E+09 | 0.910750E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135806E+10 | 0.00 | 0.00 | 5913503.54 | 0.00 | 26944964.03 | 0.275293E+10 | 0.00 | 0.53 |
February | 0.105792E+10 | 0.00 | 0.00 | 7928443.79 | 0.00 | 3897877.38 | 0.366095E+10 | 0.00 | 0.61 |
March | 0.472819E+09 | 0.00 | 0.00 | 16107947.85 | 0.00 | 0.00 | 0.728643E+10 | 0.00 | 1.46 |
April | 0.152133E+09 | 0.00 | 0.00 | 15541337.56 | 0.00 | 0.00 | 0.860719E+10 | 0.00 | 1.82 |
May | 0.167253E+09 | 3143264.07 | 0.00 | 15225407.98 | 59396.30 | 0.00 | 0.601400E+10 | 0.00 | 1.87 |
June | 0.115293E+09 | 0.264241E+09 | 0.00 | 17343801.38 | 370200.13 | 0.00 | 0.287973E+10 | 0.00 | 1.83 |
July | 0.170665E+09 | 0.268024E+09 | 0.00 | 17276566.07 | 1792042.67 | 0.00 | 0.271667E+10 | 0.00 | 1.88 |
August | 0.151650E+09 | 0.297309E+09 | 0.00 | 28978037.67 | 2388119.25 | 0.00 | 0.468556E+10 | 0.00 | 2.33 |
September | 0.148810E+09 | 55129783.72 | 0.00 | 15584891.64 | 1045994.48 | 0.00 | 0.333936E+10 | 0.00 | 1.60 |
October | 0.615151E+09 | 0.00 | 0.00 | 15946467.99 | 0.00 | 0.00 | 0.570372E+10 | 0.00 | 1.35 |
November | 0.579123E+09 | 0.00 | 0.00 | 12118652.98 | 0.00 | 0.00 | 0.485712E+10 | 0.00 | 0.87 |
December | 0.944002E+09 | 0.00 | 0.00 | 10378317.58 | 0.00 | 12012698.31 | 0.444134E+10 | 0.00 | 0.69 |
Annual Sum or Average | 0.593289E+10 | 0.887846E+09 | 0.00 | 0.178343E+09 | 5655752.83 | 42855539.72 | 0.569450E+11 | 0.00 | 1.41 |
Minimum of Months | 0.115293E+09 | 0.00 | 0.00 | 5913503.54 | 0.00 | 0.00 | 0.271667E+10 | 0.00 | 0.53 |
Maximum of Months | 0.135806E+10 | 0.297309E+09 | 0.00 | 28978037.67 | 2388119.25 | 26944964.03 | 0.860719E+10 | 0.00 | 2.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200714E+11 | 0.00 | 0.00 | 10255.60 | 0.00 | 0.223007E+11 | 27433666.62 | 0.00 | 0.29 |
February | 0.169766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232623E+11 | 0.00 | 0.00 | 0.29 |
March | 0.223989E+11 | 0.00 | 0.00 | 10042087.42 | 0.00 | 0.130329E+11 | 0.465427E+10 | 0.00 | 0.38 |
April | 0.210970E+11 | 0.00 | 0.00 | 15684203.85 | 0.00 | 0.549334E+10 | 0.801836E+10 | 0.00 | 0.40 |
May | 0.104763E+11 | 13556707.45 | 0.00 | 66926115.29 | 2234025.76 | 0.378687E+09 | 0.265391E+11 | 0.00 | 0.73 |
June | 0.231280E+10 | 0.213002E+10 | 0.00 | 96127725.36 | 75140834.26 | 0.00 | 0.180447E+11 | 0.00 | 0.86 |
July | 0.192270E+10 | 0.215773E+10 | 0.00 | 92491788.51 | 0.149663E+09 | 0.00 | 0.142649E+11 | 0.00 | 0.79 |
August | 0.356220E+10 | 0.179713E+10 | 0.00 | 0.104732E+09 | 0.119472E+09 | 0.00 | 0.171736E+11 | 0.00 | 0.73 |
September | 0.718923E+10 | 0.361496E+09 | 0.00 | 70298825.25 | 62970971.58 | 0.201635E+09 | 0.137927E+11 | 0.00 | 0.61 |
October | 0.199142E+11 | 0.00 | 0.00 | 12164337.52 | 0.00 | 0.924813E+10 | 0.425068E+10 | 0.00 | 0.34 |
November | 0.205973E+11 | 0.00 | 0.00 | 3097684.36 | 0.00 | 0.170509E+11 | 0.126459E+10 | 0.00 | 0.31 |
December | 0.140051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385892E+11 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.160524E+12 | 0.645993E+10 | 0.00 | 0.471575E+09 | 0.409480E+09 | 0.129558E+12 | 0.108030E+12 | 0.00 | 0.51 |
Minimum of Months | 0.192270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.223989E+11 | 0.215773E+10 | 0.00 | 0.104732E+09 | 0.149663E+09 | 0.385892E+11 | 0.265391E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112829E+11 | 0.00 | 0.00 | 15889988.34 | 0.00 | 0.913950E+10 | 0.708564E+10 | 0.00 | 0.30 |
February | 0.858642E+10 | 0.00 | 0.00 | 27863599.84 | 0.00 | 0.953905E+10 | 0.137332E+11 | 0.00 | 0.38 |
March | 0.939091E+10 | 0.00 | 0.00 | 70851253.70 | 0.00 | 0.493105E+10 | 0.314797E+11 | 0.00 | 0.75 |
April | 0.771721E+10 | 0.00 | 0.00 | 63759856.75 | 0.00 | 0.241215E+10 | 0.323768E+11 | 0.00 | 0.84 |
May | 0.347517E+10 | 11603433.53 | 0.00 | 0.110416E+09 | 1442724.92 | 99277528.17 | 0.460585E+11 | 0.00 | 1.42 |
June | 0.989925E+09 | 0.165023E+10 | 0.00 | 0.154408E+09 | 46672468.63 | 0.00 | 0.310494E+11 | 0.00 | 1.78 |
July | 0.817501E+09 | 0.193316E+10 | 0.00 | 0.154014E+09 | 47897882.12 | 0.00 | 0.196218E+11 | 0.00 | 1.44 |
August | 0.132060E+10 | 0.161862E+10 | 0.00 | 0.181407E+09 | 75318936.31 | 0.00 | 0.356191E+11 | 0.00 | 1.68 |
September | 0.264334E+10 | 0.358267E+09 | 0.00 | 0.129064E+09 | 40666401.99 | 48506464.63 | 0.294344E+11 | 0.00 | 1.39 |
October | 0.799355E+10 | 0.00 | 0.00 | 64821249.97 | 0.00 | 0.501573E+10 | 0.201207E+11 | 0.00 | 0.60 |
November | 0.105675E+11 | 0.00 | 0.00 | 23110246.95 | 0.00 | 0.728357E+10 | 0.972202E+10 | 0.00 | 0.38 |
December | 0.913314E+10 | 0.00 | 0.00 | 6358603.38 | 0.00 | 0.180264E+11 | 0.329758E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.739182E+11 | 0.557189E+10 | 0.00 | 0.100196E+10 | 0.211998E+09 | 0.564952E+11 | 0.279599E+12 | 0.00 | 0.94 |
Minimum of Months | 0.817501E+09 | 0.00 | 0.00 | 6358603.38 | 0.00 | 0.00 | 0.329758E+10 | 0.00 | 0.30 |
Maximum of Months | 0.112829E+11 | 0.193316E+10 | 0.00 | 0.181407E+09 | 75318936.31 | 0.180264E+11 | 0.460585E+11 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162243E+11 | 0.00 | 0.00 | 0.285548E+09 | 0.00 | 0.657351E+10 | 0.969477E+11 | 0.00 | 0.99 |
February | 0.125476E+11 | 0.00 | 0.00 | 0.231924E+09 | 0.00 | 0.102878E+11 | 0.899036E+11 | 0.00 | 0.94 |
March | 0.146551E+11 | 0.00 | 0.00 | 0.203047E+09 | 0.00 | 0.837595E+10 | 0.763666E+11 | 0.00 | 1.16 |
April | 0.157488E+11 | 0.00 | 0.00 | 87785200.94 | 0.00 | 0.447716E+10 | 0.439043E+11 | 0.00 | 0.88 |
May | 0.889302E+10 | 21841626.68 | 0.00 | 0.112294E+09 | 2244182.79 | 0.412838E+09 | 0.439380E+11 | 0.00 | 1.06 |
June | 0.285400E+10 | 0.238659E+10 | 0.00 | 0.113384E+09 | 75429343.35 | 0.00 | 0.177762E+11 | 0.00 | 0.94 |
July | 0.209203E+10 | 0.290367E+10 | 0.00 | 0.111710E+09 | 92176705.85 | 0.00 | 0.150445E+11 | 0.00 | 0.90 |
August | 0.283459E+10 | 0.312143E+10 | 0.00 | 0.200505E+09 | 0.112039E+09 | 0.00 | 0.278562E+11 | 0.00 | 1.14 |
September | 0.456200E+10 | 0.883554E+09 | 0.00 | 0.229949E+09 | 52254355.10 | 0.206710E+09 | 0.385672E+11 | 0.00 | 1.40 |
October | 0.104601E+11 | 0.00 | 0.00 | 0.364736E+09 | 0.00 | 0.783693E+10 | 0.709526E+11 | 0.00 | 1.19 |
November | 0.140571E+11 | 0.00 | 0.00 | 0.336231E+09 | 0.00 | 0.627390E+10 | 0.931089E+11 | 0.00 | 1.11 |
December | 0.161616E+11 | 0.00 | 0.00 | 0.222335E+09 | 0.00 | 0.161292E+11 | 0.756737E+11 | 0.00 | 0.89 |
Annual Sum or Average | 0.121090E+12 | 0.931708E+10 | 0.00 | 0.249945E+10 | 0.334144E+09 | 0.605740E+11 | 0.690040E+12 | 0.00 | 1.05 |
Minimum of Months | 0.209203E+10 | 0.00 | 0.00 | 87785200.94 | 0.00 | 0.00 | 0.150445E+11 | 0.00 | 0.88 |
Maximum of Months | 0.162243E+11 | 0.312143E+10 | 0.00 | 0.364736E+09 | 0.112039E+09 | 0.161292E+11 | 0.969477E+11 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150035E+11 | 0.00 | 0.00 | 23841158.62 | 0.00 | 0.772131E+10 | 0.114764E+11 | 0.00 | 0.40 |
February | 0.127696E+11 | 0.00 | 0.00 | 28190617.90 | 0.00 | 0.831729E+10 | 0.146766E+11 | 0.00 | 0.43 |
March | 0.128218E+11 | 0.00 | 0.00 | 66835957.85 | 0.00 | 0.504737E+10 | 0.260912E+11 | 0.00 | 0.83 |
April | 0.105270E+11 | 0.00 | 0.00 | 54107101.21 | 0.00 | 0.226587E+10 | 0.272572E+11 | 0.00 | 0.86 |
May | 0.452723E+10 | 22696009.52 | 0.00 | 0.105483E+09 | 1352347.31 | 0.128716E+09 | 0.376703E+11 | 0.00 | 1.37 |
June | 0.117137E+10 | 0.318369E+10 | 0.00 | 0.113049E+09 | 5448564.43 | 0.00 | 0.162809E+11 | 0.00 | 1.34 |
July | 0.101202E+10 | 0.282970E+10 | 0.00 | 88844695.10 | 39494034.68 | 0.00 | 0.130923E+11 | 0.00 | 1.17 |
August | 0.126880E+10 | 0.290284E+10 | 0.00 | 0.143948E+09 | 23794455.91 | 0.00 | 0.188140E+11 | 0.00 | 1.26 |
September | 0.314456E+10 | 0.542006E+09 | 0.00 | 0.109230E+09 | 14487222.46 | 0.133994E+09 | 0.196997E+11 | 0.00 | 1.14 |
October | 0.949084E+10 | 0.00 | 0.00 | 85236195.77 | 0.00 | 0.481888E+10 | 0.216740E+11 | 0.00 | 0.72 |
November | 0.142274E+11 | 0.00 | 0.00 | 33951545.14 | 0.00 | 0.579616E+10 | 0.135793E+11 | 0.00 | 0.48 |
December | 0.134111E+11 | 0.00 | 0.00 | 14725154.64 | 0.00 | 0.158219E+11 | 0.655965E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.993754E+11 | 0.948093E+10 | 0.00 | 0.867442E+09 | 84576624.80 | 0.500515E+11 | 0.226871E+12 | 0.00 | 0.87 |
Minimum of Months | 0.101202E+10 | 0.00 | 0.00 | 14725154.64 | 0.00 | 0.00 | 0.655965E+10 | 0.00 | 0.39 |
Maximum of Months | 0.150035E+11 | 0.318369E+10 | 0.00 | 0.143948E+09 | 39494034.68 | 0.158219E+11 | 0.376703E+11 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329649E+10 | 0.00 | 0.00 | 0.34 |
February | 0.104159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308041E+10 | 0.00 | 0.00 | 0.33 |
March | 0.171430E+10 | 0.00 | 0.00 | 831396.02 | 0.00 | 0.192933E+10 | 0.418255E+09 | 0.00 | 0.40 |
April | 0.156119E+10 | 0.00 | 0.00 | 1470915.38 | 0.00 | 0.119768E+10 | 0.862596E+09 | 0.00 | 0.43 |
May | 0.113478E+10 | 98941.71 | 0.00 | 6066438.24 | 13657.84 | 93853313.65 | 0.244947E+10 | 0.00 | 0.72 |
June | 0.231186E+09 | 0.137667E+09 | 0.00 | 11723280.57 | 4793352.70 | 0.00 | 0.180580E+10 | 0.00 | 0.89 |
July | 0.214126E+09 | 0.131954E+09 | 0.00 | 10697720.01 | 9315106.97 | 0.00 | 0.139425E+10 | 0.00 | 0.80 |
August | 0.402506E+09 | 0.120517E+09 | 0.00 | 11841672.45 | 10111394.05 | 0.00 | 0.162570E+10 | 0.00 | 0.72 |
September | 0.735357E+09 | 23687634.12 | 0.00 | 7062517.73 | 5274258.60 | 54174538.01 | 0.125153E+10 | 0.00 | 0.61 |
October | 0.178569E+10 | 0.00 | 0.00 | 809227.26 | 0.00 | 0.157097E+10 | 0.324327E+09 | 0.00 | 0.40 |
November | 0.120594E+10 | 0.00 | 0.00 | 174617.34 | 0.00 | 0.266691E+10 | 0.104120E+09 | 0.00 | 0.34 |
December | 0.754943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504613E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.120073E+11 | 0.413925E+09 | 0.00 | 50677784.99 | 29507770.17 | 0.189359E+11 | 0.102361E+11 | 0.00 | 0.53 |
Minimum of Months | 0.214126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.178569E+10 | 0.137667E+09 | 0.00 | 11841672.45 | 10111394.05 | 0.504613E+10 | 0.244947E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107662E+10 | 0.00 | 0.00 | 766655.75 | 0.00 | 0.140842E+10 | 0.461512E+09 | 0.00 | 0.36 |
February | 0.938245E+09 | 0.00 | 0.00 | 1599947.17 | 0.00 | 0.120484E+10 | 0.917731E+09 | 0.00 | 0.40 |
March | 0.873364E+09 | 0.00 | 0.00 | 5631629.93 | 0.00 | 0.805141E+09 | 0.286065E+10 | 0.00 | 0.79 |
April | 0.668238E+09 | 0.00 | 0.00 | 5648912.93 | 0.00 | 0.574892E+09 | 0.331147E+10 | 0.00 | 0.91 |
May | 0.428228E+09 | 96106.45 | 0.00 | 10463463.44 | 8820.61 | 28176062.15 | 0.450679E+10 | 0.00 | 1.45 |
June | 79058601.68 | 0.107855E+09 | 0.00 | 17871066.01 | 2319711.69 | 0.00 | 0.324575E+10 | 0.00 | 1.90 |
July | 77590510.32 | 0.120804E+09 | 0.00 | 17852500.47 | 2479827.68 | 0.00 | 0.199090E+10 | 0.00 | 1.50 |
August | 0.121953E+09 | 0.109008E+09 | 0.00 | 20655348.29 | 6530213.86 | 0.00 | 0.364938E+10 | 0.00 | 1.74 |
September | 0.251202E+09 | 23455769.83 | 0.00 | 13255752.83 | 3388497.27 | 20582507.62 | 0.281170E+10 | 0.00 | 1.43 |
October | 0.707207E+09 | 0.00 | 0.00 | 4898294.61 | 0.00 | 0.927372E+09 | 0.207090E+10 | 0.00 | 0.71 |
November | 0.979958E+09 | 0.00 | 0.00 | 1454310.25 | 0.00 | 0.118593E+10 | 0.713512E+09 | 0.00 | 0.42 |
December | 0.887970E+09 | 0.00 | 0.00 | 174404.71 | 0.00 | 0.244256E+10 | 0.124738E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.708964E+10 | 0.361219E+09 | 0.00 | 0.100272E+09 | 14727071.10 | 0.859790E+10 | 0.266650E+11 | 0.00 | 1.00 |
Minimum of Months | 77590510.32 | 0.00 | 0.00 | 174404.71 | 0.00 | 0.00 | 0.124738E+09 | 0.00 | 0.36 |
Maximum of Months | 0.107662E+10 | 0.120804E+09 | 0.00 | 20655348.29 | 6530213.86 | 0.244256E+10 | 0.450679E+10 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121253E+10 | 0.00 | 0.00 | 20182219.27 | 0.00 | 0.128988E+10 | 0.884884E+10 | 0.00 | 1.07 |
February | 0.107090E+10 | 0.00 | 0.00 | 17548985.35 | 0.00 | 0.127253E+10 | 0.838603E+10 | 0.00 | 0.96 |
March | 0.115396E+10 | 0.00 | 0.00 | 17878403.22 | 0.00 | 0.114629E+10 | 0.801017E+10 | 0.00 | 1.23 |
April | 0.117406E+10 | 0.00 | 0.00 | 7950560.09 | 0.00 | 0.885928E+09 | 0.495020E+10 | 0.00 | 0.95 |
May | 0.907922E+09 | 148651.95 | 0.00 | 10518345.89 | 13588.85 | 98087817.93 | 0.438570E+10 | 0.00 | 1.06 |
June | 0.319315E+09 | 0.148271E+09 | 0.00 | 13984005.32 | 4784237.71 | 0.00 | 0.191254E+10 | 0.00 | 1.00 |
July | 0.232067E+09 | 0.170549E+09 | 0.00 | 14008885.51 | 5030979.87 | 0.00 | 0.157532E+10 | 0.00 | 0.94 |
August | 0.320602E+09 | 0.195338E+09 | 0.00 | 24040110.16 | 10060318.28 | 0.00 | 0.286754E+10 | 0.00 | 1.15 |
September | 0.439726E+09 | 54876327.65 | 0.00 | 25056159.63 | 4096572.88 | 39342994.34 | 0.403780E+10 | 0.00 | 1.46 |
October | 0.794897E+09 | 0.00 | 0.00 | 31774142.55 | 0.00 | 0.125775E+10 | 0.872433E+10 | 0.00 | 1.51 |
November | 0.969810E+09 | 0.00 | 0.00 | 25638638.18 | 0.00 | 0.119744E+10 | 0.828429E+10 | 0.00 | 1.13 |
December | 0.118585E+10 | 0.00 | 0.00 | 15883569.52 | 0.00 | 0.222941E+10 | 0.617909E+10 | 0.00 | 0.89 |
Annual Sum or Average | 0.978163E+10 | 0.569184E+09 | 0.00 | 0.224464E+09 | 23985697.60 | 0.941666E+10 | 0.681618E+11 | 0.00 | 1.11 |
Minimum of Months | 0.232067E+09 | 0.00 | 0.00 | 7950560.09 | 0.00 | 0.00 | 0.157532E+10 | 0.00 | 0.89 |
Maximum of Months | 0.121253E+10 | 0.195338E+09 | 0.00 | 31774142.55 | 10060318.28 | 0.222941E+10 | 0.884884E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105354E+10 | 0.00 | 0.00 | 1809872.74 | 0.00 | 0.127114E+10 | 0.114240E+10 | 0.00 | 0.46 |
February | 0.955661E+09 | 0.00 | 0.00 | 2296996.76 | 0.00 | 0.109902E+10 | 0.138083E+10 | 0.00 | 0.45 |
March | 0.108073E+10 | 0.00 | 0.00 | 6329319.68 | 0.00 | 0.712391E+09 | 0.277674E+10 | 0.00 | 0.88 |
April | 0.870679E+09 | 0.00 | 0.00 | 5114705.25 | 0.00 | 0.442840E+09 | 0.308502E+10 | 0.00 | 0.94 |
May | 0.476906E+09 | 150259.45 | 0.00 | 10198060.46 | 8813.46 | 39489994.20 | 0.383815E+10 | 0.00 | 1.39 |
June | 0.114760E+09 | 0.195576E+09 | 0.00 | 14808278.22 | 358172.25 | 0.00 | 0.173111E+10 | 0.00 | 1.39 |
July | 96431507.03 | 0.166221E+09 | 0.00 | 11867646.71 | 2840480.46 | 0.00 | 0.135418E+10 | 0.00 | 1.21 |
August | 0.128931E+09 | 0.183325E+09 | 0.00 | 17595219.83 | 1766709.45 | 0.00 | 0.189592E+10 | 0.00 | 1.25 |
September | 0.314623E+09 | 36413683.63 | 0.00 | 12387093.77 | 1148783.67 | 23725492.88 | 0.199349E+10 | 0.00 | 1.20 |
October | 0.849448E+09 | 0.00 | 0.00 | 7700565.09 | 0.00 | 0.750431E+09 | 0.244835E+10 | 0.00 | 0.88 |
November | 0.954430E+09 | 0.00 | 0.00 | 2763345.38 | 0.00 | 0.102912E+10 | 0.123446E+10 | 0.00 | 0.50 |
December | 0.934310E+09 | 0.00 | 0.00 | 1078606.24 | 0.00 | 0.205581E+10 | 0.560561E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.783044E+10 | 0.581686E+09 | 0.00 | 93949710.14 | 6122959.30 | 0.742397E+10 | 0.234412E+11 | 0.00 | 0.92 |
Minimum of Months | 96431507.03 | 0.00 | 0.00 | 1078606.24 | 0.00 | 0.00 | 0.560561E+09 | 0.00 | 0.41 |
Maximum of Months | 0.108073E+10 | 0.195576E+09 | 0.00 | 17595219.83 | 2840480.46 | 0.205581E+10 | 0.383815E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3785758.12 | 0.00 | 0.00 | 0.566276E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8844566.28 | 0.00 | 0.00 | 0.532368E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 15632831.96 | 0.00 | 0.00 | 0.508010E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18338452.78 | 0.00 | 0.00 | 0.394999E+09 | 0.00 | 0.29 |
May | 0.00 | 152698.48 | 0.00 | 4001351.83 | 0.00 | 0.00 | 0.263397E+09 | 0.00 | 0.29 |
June | 0.00 | 27907058.86 | 0.00 | 5160010.80 | 0.00 | 0.00 | 45663558.06 | 0.00 | 0.30 |
July | 0.00 | 52598204.09 | 0.00 | 5508500.85 | 0.00 | 0.00 | 28962334.38 | 0.00 | 0.28 |
August | 0.00 | 27645409.20 | 0.00 | 13948739.08 | 0.00 | 0.00 | 53937657.73 | 0.00 | 0.30 |
September | 0.00 | 714762.10 | 0.00 | 3923723.19 | 0.00 | 0.00 | 0.165613E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 9137609.25 | 0.00 | 0.00 | 0.427525E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 14048651.76 | 0.00 | 0.00 | 0.498525E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 20764316.24 | 0.00 | 0.00 | 0.595569E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.109018E+09 | 0.00 | 0.123095E+09 | 0.00 | 0.00 | 0.408085E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3785758.12 | 0.00 | 0.00 | 28962334.38 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 52598204.09 | 0.00 | 20764316.24 | 0.00 | 0.00 | 0.595569E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203121E+09 | 0.00 | 0.00 | 23051758.39 | 0.00 | 0.00 | 0.547794E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 69531418.40 | 0.00 | 0.00 | 0.534219E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.136783E+09 | 0.00 | 0.00 | 0.509955E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.166230E+09 | 0.00 | 0.00 | 0.396681E+10 | 0.00 | 0.29 |
May | 0.00 | 1369947.22 | 0.00 | 34555569.99 | 0.00 | 0.00 | 0.264643E+10 | 0.00 | 0.29 |
June | 0.00 | 0.275512E+09 | 0.00 | 48833040.59 | 0.00 | 0.00 | 0.460261E+09 | 0.00 | 0.30 |
July | 0.00 | 0.522756E+09 | 0.00 | 52642528.71 | 0.00 | 0.00 | 0.292381E+09 | 0.00 | 0.28 |
August | 0.00 | 0.277305E+09 | 0.00 | 0.131920E+09 | 0.00 | 0.00 | 0.539198E+09 | 0.00 | 0.30 |
September | 0.00 | 6970260.48 | 0.00 | 34641380.92 | 0.00 | 0.00 | 0.166564E+10 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 78180240.84 | 0.00 | 0.00 | 0.428893E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.121581E+09 | 0.00 | 0.00 | 0.500334E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.179080E+09 | 0.00 | 0.00 | 0.598363E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.203121E+09 | 0.108391E+10 | 0.00 | 0.107703E+10 | 0.00 | 0.00 | 0.407663E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23051758.39 | 0.00 | 0.00 | 0.292381E+09 | 0.00 | 0.28 |
Maximum of Months | 0.203121E+09 | 0.522756E+09 | 0.00 | 0.179080E+09 | 0.00 | 0.00 | 0.598363E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236634E+09 | 0.00 | 0.00 | 1252599.79 | 0.00 | 0.00 | 0.328335E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5797565.06 | 0.00 | 0.00 | 0.535498E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12672920.49 | 0.00 | 0.00 | 0.511177E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 15907442.18 | 0.00 | 0.00 | 0.397501E+09 | 0.00 | 0.29 |
May | 8297030.88 | 149220.32 | 0.00 | 3184726.58 | 0.00 | 0.00 | 0.256835E+09 | 0.00 | 0.29 |
June | 0.00 | 27630351.83 | 0.00 | 4910536.12 | 0.00 | 0.00 | 45998099.31 | 0.00 | 0.30 |
July | 0.00 | 52312119.83 | 0.00 | 5275353.95 | 0.00 | 0.00 | 29198285.11 | 0.00 | 0.28 |
August | 0.00 | 27800049.64 | 0.00 | 13140075.13 | 0.00 | 0.00 | 53605706.21 | 0.00 | 0.30 |
September | 2970515.30 | 688363.71 | 0.00 | 3282848.91 | 0.00 | 0.00 | 0.163862E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 6787224.07 | 0.00 | 0.00 | 0.430379E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10924902.66 | 0.00 | 0.00 | 0.501803E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16500542.02 | 0.00 | 0.00 | 0.599802E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.247902E+09 | 0.108580E+09 | 0.00 | 99636736.97 | 0.00 | 0.00 | 0.385400E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1252599.79 | 0.00 | 0.00 | 29198285.11 | 0.00 | 0.28 |
Maximum of Months | 0.236634E+09 | 52312119.83 | 0.00 | 16500542.02 | 0.00 | 0.00 | 0.599802E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.646842E+09 | 0.00 | 0.00 | 0.514548E+12 | 0.00 | 11.00 |
February | 0.00 | 0.00 | 0.00 | 0.127390E+10 | 0.00 | 0.00 | 0.754809E+12 | 0.00 | 17.44 |
March | 0.00 | 0.00 | 0.00 | 0.196204E+10 | 0.00 | 0.00 | 0.106546E+13 | 0.00 | 30.36 |
April | 0.00 | 0.00 | 0.00 | 0.219517E+10 | 0.00 | 0.00 | 0.121183E+13 | 0.00 | 38.33 |
May | 0.00 | 0.00 | 0.00 | 0.527614E+09 | 0.00 | 0.00 | 0.487813E+12 | 0.00 | 23.08 |
June | 0.00 | 0.291286E+10 | 0.00 | 0.105675E+10 | 0.00 | 0.00 | 0.391856E+12 | 0.00 | 34.49 |
July | 0.00 | 0.135099E+11 | 0.00 | 0.158877E+10 | 0.00 | 0.00 | 0.364345E+12 | 0.00 | 37.32 |
August | 0.00 | 0.571021E+10 | 0.00 | 0.291179E+10 | 0.00 | 0.00 | 0.434223E+12 | 0.00 | 50.39 |
September | 0.00 | 0.00 | 0.00 | 0.561033E+09 | 0.00 | 0.00 | 0.421090E+12 | 0.00 | 26.73 |
October | 0.00 | 0.00 | 0.00 | 0.132253E+10 | 0.00 | 0.00 | 0.811105E+12 | 0.00 | 25.39 |
November | 0.00 | 0.00 | 0.00 | 0.193409E+10 | 0.00 | 0.00 | 0.104096E+13 | 0.00 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.308472E+10 | 0.00 | 0.00 | 0.131318E+13 | 0.00 | 31.03 |
Annual Sum or Average | 0.00 | 0.221330E+11 | 0.00 | 0.190653E+11 | 0.00 | 0.00 | 0.881122E+13 | 0.00 | 29.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.527614E+09 | 0.00 | 0.00 | 0.364345E+12 | 0.00 | 11.00 |
Maximum of Months | 0.00 | 0.135099E+11 | 0.00 | 0.308472E+10 | 0.00 | 0.00 | 0.131318E+13 | 0.00 | 50.39 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.427168E+12 | 0.151323E+11 | 0.00 | 0.225426E+13 | 0.191134E+12 |
February | 0.546275E+12 | 0.237428E+11 | 0.00 | 0.226120E+13 | 0.239003E+12 |
March | 0.682205E+12 | 0.257146E+11 | 0.00 | 0.275427E+13 | 0.451203E+12 |
April | 0.737468E+12 | 0.269941E+11 | 0.00 | 0.292774E+13 | 0.539124E+12 |
May | 0.853732E+12 | 0.139126E+11 | 0.00 | 0.223040E+13 | 0.599730E+12 |
June | 0.904238E+12 | 0.615405E+10 | 0.00 | 0.147566E+13 | 0.213016E+13 |
July | 0.853247E+12 | 0.508497E+10 | 0.00 | 0.127544E+13 | 0.265766E+13 |
August | 0.835225E+12 | 0.521529E+10 | 0.00 | 0.138688E+13 | 0.297980E+13 |
September | 0.625705E+12 | 0.896593E+10 | 0.00 | 0.173712E+13 | 0.129425E+13 |
October | 0.540369E+12 | 0.192785E+11 | 0.00 | 0.262155E+13 | 0.521777E+12 |
November | 0.455683E+12 | 0.172072E+11 | 0.00 | 0.279585E+13 | 0.403446E+12 |
December | 0.350469E+12 | 0.315505E+11 | 0.00 | 0.291007E+13 | 0.445264E+12 |
Annual Sum or Average | 0.781178E+13 | 0.198953E+12 | 0.00 | 0.266304E+14 | 0.124526E+14 |