Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885

Simulation Timestamp: 2023-10-16 08:56:55


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 24159.55 521.57 521.57
Net Site Energy 23756.57 512.88 512.88
Total Source Energy 72438.11 1563.85 1563.85
Net Source Energy 71161.87 1536.30 1536.30


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1161.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 681.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1722.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 269.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1203.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2083.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 201.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 238.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 826.84
Humidification 1125.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 418.68
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 794.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 22203.15 1956.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3525.69
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1161.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 681.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1722.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 269.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1144.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 4.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2083.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 201.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 238.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 826.84
Humidification General 1125.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 418.68
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 794.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1161.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 681.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1722.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 269.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1203.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2083.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 201.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 238.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 826.84
Humidification Unassigned 1125.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 418.68
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 794.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 43.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 93.50 42.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08
Other 342.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 479.34 42.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 43.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 93.50 42.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08
Other 342.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 479.34 42.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 422.379 1.90
Wind Power 0.000 0.00
Power Conversion -19.40 -0.1
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 402.980 1.81
     
Electricity Coming From Utility 21800.169 98.19
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 21800.169 98.19
     
Total On-Site and Utility Electric Sources 22203.149 100.00
Total Electricity End Uses 22203.149 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 3525.69 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 3525.69 100.00
Total Water End Uses 3525.69 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 19.67
Time Setpoint Not Met During Occupied Cooling 146.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5917.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionElectricityGeneratedPropaneMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
RunPeriod RUNPERIOD 1
Weather File William R Fairchild WA USA TMY3 WMO#=727885
Latitude [deg] 48.12
Longitude [deg] -123.5
Elevation [m] 91.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 5.7776 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.7776 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 5.7776 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.7776 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 7.1736 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 7.1736 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 7.1736 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 5.7776 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 5.7907 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 5.7907 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.7776 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 5.7776 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 5.7776 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 5.7776 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 5.7776 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 5.7776 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 5.7776 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 5.7776 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 5.7776 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 5.7776 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 5.7776 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 5.7776 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 5.7776 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 5.7776 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 5.7776 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 5.7776 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 7.1736 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 7.1736 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 7.1736 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 5.7776 18.58 484.4232  
Total 46320.38             5.7907 9.29 17.8789  
Conditioned Total 46320.38             5.7907 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 1.7810 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 14-AUG-15:30 10-JAN-07:10 - - - - - - - - - - 21-JUL-16:19
Heating 0.00 702189.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 280213.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 145987.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 52589.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 214677.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 32989.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 46402.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 28615.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1551231.39 730805.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 702189.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 280213.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 145987.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3359.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 49008.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 221.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 214677.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 32989.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 46402.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 28615.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1258.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2159.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5456.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 852.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 3812.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6597.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 638.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 756.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 3564.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 861.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 70317.37 2120.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 27.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 46.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 117.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 142.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 13.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 16.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 76.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 18.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1518.07 45.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 27.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 46.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 117.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 142.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 13.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 16.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 76.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 18.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1518.07 45.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 4.84
DATACENTER_BOT_ZN_6 DIRECT AIR 0.498796
DATACENTER_MID_ZN_6 DIRECT AIR 4.79
DATACENTER_TOP_ZN_6 DIRECT AIR 0.485858
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.44
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.22 0.364662 0.310000 1.62 0.972433 0.500000 0.001045 0.000352 1.62 12.80 0.008000
CORE_MID VAV BOX COMPONENT 48.64 0.391038 0.332000 16.15 1.00 0.500000 0.000974 0.007550 16.15 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 4.59 0.414424 0.352000 1.62 1.00 0.500000 0.000919 0.001484 2.04 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.771917 0.309387 0.263000 0.203014 0.825031 0.500000 0.001231 0.000141 0.203014 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.24 0.124027 0.105000 0.130295 0.330738 0.500000 0.003072 0.000104 0.142701 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.73 0.137668 0.117000 0.202971 0.367115 0.500000 0.002768 0.000197 0.270971 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.51 0.101746 0.086000 0.130087 0.300000 0.500000 0.003745 0.000067 0.130087 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 6.95 0.343447 0.292000 2.03 0.915858 0.500000 0.001109 0.003513 4.84 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 13.05       0.314509 0.500000 0.003230 0.002354 3.24 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 18.06 0.132221 0.112000 2.02 0.352589 0.500000 0.002882 0.003535 4.87 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 13.90 0.110719 0.094000 1.31 0.300000 0.500000 0.003441 0.002129 2.93 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.782339 0.305265 0.259000 0.202626 0.814040 0.500000 0.001248 0.000463 0.637950 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.29 0.119491 0.102000 0.131376 0.318644 0.500000 0.003189 0.000307 0.423077 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.89 0.126282 0.107000 0.202359 0.336752 0.500000 0.003017 0.000465 0.641085 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.45 0.106094 0.090000 0.130558 0.300000 0.500000 0.003591 0.000290 0.399758 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 16107.57 0.000352 449.56
CORE_MID VAV BOX REHEAT COIL 345134.58 0.007550 11133.03
CORE_TOP VAV BOX REHEAT COIL 67847.83 0.001484 2643.00
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6437.49 0.000141 243.36
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4752.89 0.000104 185.19
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9015.61 0.000197 351.05
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3076.48 0.000067 102.28
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 160574.07 0.003513 6243.39
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 107596.14 0.002354 4183.24
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 161606.24 0.003535 6283.46
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 97310.80 0.002129 3783.92
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 21165.16 0.000463 822.60
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 14035.48 0.000307 545.48
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 21268.94 0.000465 826.63
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 13263.27 0.000290 515.50
VAV_BOT WITH REHEAT HEATING COIL 44651.52 0.000977 958.80
VAV_MID WITH REHEAT HEATING COIL 389828.66 0.008528 8433.00
VAV_TOP WITH REHEAT HEATING COIL 38031.81 0.000832 842.55
CAV_BAS HEATING COIL 237871.61 0.005203 7574.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.24 2.28 10.48 2.28 8.61 8.61 0.300000 0.265057 8.61
VAV_MID WITH REHEAT 50.30 22.81 100.61 26.66 78.52 78.52 0.300000 0.339460 78.52
VAV_TOP WITH REHEAT 5.00 2.28 10.00 4.14 8.85 8.85 0.300000 0.467617 8.85
CAV_BAS 4.84 4.84 4.84 4.84 4.84 4.84 1.00 1.00 4.84
AIRLOOP DATACENTER BASEMENT 21.44 21.44 21.44 21.44 21.44 21.44 1.00 0.999997 21.44
AIRLOOP DATACENTER BOT 0.498796 0.498796 0.498796 0.498796 0.498796 0.498796 1.00 1.00 0.498796
AIRLOOP DATACENTER MID 4.79 4.79 4.79 4.79 4.79 4.79 1.00 1.00 4.79
AIRLOOP DATACENTER TOP 0.485858 0.485858 0.485858 0.485858 0.485858 0.485858 1.00 1.00 0.485858
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 8.61  
VAV_MID WITH REHEAT_OA_CONTROLLER 78.52  
VAV_TOP WITH REHEAT_OA_CONTROLLER 8.85  
CAV_BAS_OA_CONTROLLER 4.84 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.44 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.498796 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.79 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.485858 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 24.56 6.67 11.02 0.008757 0.008500 148545.81 0.004248 8.61
VAV_MID WITH REHEAT COOLING COIL 24.62 6.67 11.02 0.008770 0.008500 1362567.92 0.038969 78.52
VAV_TOP WITH REHEAT COOLING COIL 24.55 6.67 11.02 0.008750 0.008500 152324.23 0.004356 8.85
CAV_BAS COOLING COIL 24.33 6.67 11.41 0.008885 0.008500 81703.01 0.002337 4.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 8.61
VAV_MID WITH REHEAT FAN 78.52
VAV_TOP WITH REHEAT FAN 8.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.004248 0.000112
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000977  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.038969 0.000012
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.008528  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.004356 0.000109
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000832  
CAV_BAS_COOLC_CONTROLLER 0.002337 0.000204
CAV_BAS_HEATC_CONTROLLER 0.005203  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 4.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.44 423788.46 305280.69 0.010379
AIRLOOP DATACENTER BOT COOLING COIL 0.498796 9605.67 7011.55 0.000235
AIRLOOP DATACENTER MID COOLING COIL 4.79 92302.84 67368.91 0.002260
AIRLOOP DATACENTER TOP COOLING COIL 0.485858 9357.62 6830.01 0.000229
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.44 21.44 21.44 21.44 423788.46 423788.46 17946.39 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.498796 0.498796 0.498796 0.498796 9605.67 9605.67 829.05 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.79 4.79 4.79 4.79 92302.84 92302.84 8290.49 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.485858 0.485858 0.485858 0.485858 9357.62 9357.62 829.05 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.44
AIRLOOP DATACENTER BOT SUPPLY FAN 0.498796
AIRLOOP DATACENTER MID SUPPLY FAN 4.79
AIRLOOP DATACENTER TOP SUPPLY FAN 0.485858
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.44 423788.46 0.010379
AIRLOOP DATACENTER BOT HEATING COIL 0.498796 9605.67 0.000235
AIRLOOP DATACENTER MID HEATING COIL 4.79 92302.84 0.002260
AIRLOOP DATACENTER TOP HEATING COIL 0.485858 9357.62 0.000229
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 17946.39
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 829.05
AIRLOOP DATACENTER MID_SUPPHEATCOIL 8290.49
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 829.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000144 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.049911 8068.23  
HEATSYS1 PUMP 0.038491 11476.96 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.049911 5.99
HEATSYS1 0.038491 4.62
COOLSYS1_SUPPLY 0.049911 5.99
SINGLE WATER PLANT LOOP 0.013103 1.57
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.049911 0.049911 209500.71 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1759576.16 1759576.16 0.038491
CENTRAL BOILER 539749.91 529000.48 0.013103
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.024955 2792.95
COOLSYS1 CHILLER2 PUMP 0.024955 2792.95
PLANT CIRC PUMP 0.013103 3308.95
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.049911 0.025289 885233.92 890621.69 0.044813
COOLSYS1 CHILLER2 0.049911 0.025289 885233.92 890621.69 0.044813
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013103 139666.47 60065.15 69833.23 7004.20 21491.70
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.089626 10.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.089626 21969.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 33.00 1057999.86 6.60 132249.98
TOWERWATERSYS COOLTOWER 2 33.00 1057999.86 6.60 132249.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.045777
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.30 6.70 4.10 4.20 4.20 5.90 9.00 10.00 13.30 15.00 15.70 13.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 William R Fairchild WA USA TMY3 WMO#=727885 48.12 -123.50 -8.00 91.00 100237 1.1914


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.23 11.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 5.778 4.842 0.000 0.000 0.000 0.000 10.619 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.847 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.847 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.847 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 7.174 215.299 0.000 0.000 0.000 0.000 222.473 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 7.174 215.299 0.000 0.000 0.000 0.000 222.473 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 7.174 215.299 0.000 0.000 0.000 0.000 222.473 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 5.778 484.423 0.000 0.000 0.000 0.000 490.201 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 16058.301 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16058.301
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 14421.483 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14421.483
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 14421.483 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14421.483
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 14421.483 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14421.483
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 1810.761 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.761
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 1810.801 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.801
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 1810.761 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.761
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 1810.801 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.801
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 1810.761 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.761
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 1810.801 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.801
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 4527.754 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4527.754
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 259.704 7.174 133.277 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 259.704
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 259.704 7.174 133.277 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 259.704
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 259.704 7.174 133.277 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 259.704


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 0.8378 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 0.8072 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 0.9232 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.026
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.072
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.9158
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 -0.24829308E-14 0.29135133E-16 -0.15401821E-09 0.38773647E-16
51 8 0.22478683E-07 0.11333425E-12 0.38411067E-03 -0.25559038E-09
52 7 -0.12429992E-01 0.58464112E-08 -0.23357103E-01 0.14133354E-03
53 6 0.41047043 0.20318695E-05 0.47644950 -0.48081157E-02
54 5 -5.2405281 0.75802388E-04 -4.4747275 0.63803387E-01
55 4 33.223854 0.61961214E-03 21.571135 -0.42505714
56 3 -111.69641 0.13494874E-02 -55.882598 1.5219877
57 2 197.59721 0.75863434E-03 78.112020 -2.9081180
58 1 -171.33669 0.80942272E-04 -55.323717 2.7486048
59 0 57.057407 0.46049242E-06 15.547298  
60 9 -0.15339349E-14 0.29979511E-16 -0.15544574E-09 0.39943344E-16
61 8 0.22679133E-07 0.10934645E-12 0.38619381E-03 -0.25786952E-09
62 7 -0.12492075E-01 0.56288006E-08 -0.23446467E-01 0.14203945E-03
63 6 0.41215724 0.19545976E-05 0.47788421 -0.48279991E-02
64 5 -5.2569880 0.72866980E-04 -4.4857383 0.64007484E-01
65 4 33.296652 0.59522869E-03 21.614155 -0.42602372
66 3 -111.85128 0.12956249E-02 -55.967640 1.5242251
67 2 197.75067 0.72797512E-03 78.190049 -2.9105550
68 1 -171.39336 0.77633808E-04 -55.346469 2.7495981
69 0 57.057407 0.44138471E-06 15.543591  
70 9 -0.23125622E-14 0.35111754E-16 -0.15002006E-09 0.46457589E-16
71 8 0.21917045E-07 0.12438460E-12 0.37824022E-03 -0.24920433E-09
72 7 -0.12254923E-01 0.64545218E-08 -0.23105067E-01 0.13934294E-03
73 6 0.40571362 0.22485912E-05 0.47240083 -0.47520443E-02
74 5 -5.1941091 0.84060576E-04 -4.4436429 0.63227810E-01
75 4 33.018541 0.68839572E-03 21.449658 -0.42233114
76 3 -111.25962 0.15017871E-02 -55.642450 1.5156770
77 2 197.16434 0.84550337E-03 77.891725 -2.9012438
78 1 -171.17681 0.90334265E-04 -55.259577 2.7458027
79 0 57.057407 0.51475124E-06 15.557826  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.363_SHGC_EAST_0.378 35 1 VerySmooth 2.062 2.062 1.000 0.379    
2 WINDOW_U_0.363_SHGC_SOUTH_0.378 36 1 VerySmooth 2.062 2.062 1.000 0.379    
3 WINDOW_U_0.363_SHGC_WEST_0.378 37 1 VerySmooth 2.062 2.062 1.000 0.379    
4 WINDOW_U_0.363_SHGC_NORTH_0.378 38 1 VerySmooth 2.062 2.062 1.000 0.379    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.486 6.0748E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.3512E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.3535E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.2399E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.2418E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7066E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7081E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6225E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6233E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.4033E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.5557E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.2841E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.4180E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7437E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.8528E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6441E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6991E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1730
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.5157E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1984
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1105
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1132
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.6955E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7407E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.6489E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.4116E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.5995E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.2932E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.4666E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7505E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.8791E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6446E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7007E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.3510E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.3535E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.2397E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.2419E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7065E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7082E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6224E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6232E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.3412E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.7873E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1769E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.6968E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.5200E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.6658E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.4838E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.5217E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.2220E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5358E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.9483E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3145E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.7446E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8212E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.9359E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.8463E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1901E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.3059E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.9768E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.0617E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.4742E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.5075E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.4839E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.5223E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8898E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8920E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4472E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4491E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1370E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1384E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6225E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6233E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9411E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0726E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4900E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5963E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1721E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2507E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6447E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7008E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.7868E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5303E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.6805E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9228E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.2741E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2692E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.7407E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6484E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9390E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0722E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4870E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5915E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1667E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2339E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6441E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6992E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8896E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8918E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4470E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4488E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1368E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1380E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6224E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6232E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5263E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.6468E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.1215E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.2090E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.0126E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.0430E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4840E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.5224E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.0646E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0562E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.4656E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.6982E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.8918E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4714E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9359E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.8463E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.6381E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.9501E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2705E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.6152E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.0549E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.1847E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4837E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.5217E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1737
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1289
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1936
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1479
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1267
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.9085E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.8052E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.8715E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.5691E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 5.0666E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.2673E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.8132E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.9722E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.1291E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.9539E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.9044E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.8990E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.9244E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.6487E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0962E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.2063E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.2773E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.8053E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.8710E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.2591E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.4039E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.5883E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.9601E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.0173E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.6672E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.9539E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.9044E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1737
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1291
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1936
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1482
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1269
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.9249E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.8177E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.8779E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.5745E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 5.0744E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.2736E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.8209E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.9842E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.1379E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.9663E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.9108E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.8994E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.9289E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.6494E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0998E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.2130E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.2816E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.8177E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.8774E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.2628E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.4102E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.5924E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.9659E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.0278E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.6748E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.9663E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.9108E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 66526.04640 66526.04640 4.83840 4.83840 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.39663E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:10:00 -4.30000 2.65759E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 71713.05656 71713.05656 5.21591 5.21591 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.39663E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:40:00 -4.30000 2.65759E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 668981.26483 668981.26483 48.64091 48.64091 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.39663E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 184263.36608 184263.36608 7.80132 10.77825 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 63136.11743 63136.11743 4.58960 4.58960 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 19.66600 8.39663E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 47547.28722 47547.28722 2.03784 2.03784 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 10511.50142 10511.50142 0.77192 0.77192 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 26.40000 8.40708E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 4418.23195 4418.23195 0.18887 0.18887 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 16898.06149 16898.06149 1.24090 1.24090 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 21.10683 8.39884E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 3333.28669 3333.28669 0.14270 0.14270 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 23623.60327 23623.60327 1.73479 1.73479 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 26.09667 8.40660E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 6319.16639 6319.16639 0.27097 0.27097 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 20598.57729 20598.57729 1.51264 1.51264 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 25.12600 8.40508E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 1783.70245 1783.70245 7.58446E-002 8.72129E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 94690.70592 94690.70592 6.95364 6.95364 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 26.40000 8.40708E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 112425.85369 112425.85369 4.83689 4.83689 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 177700.63528 177700.63528 13.04935 13.04935 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.65283 8.39969E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 75328.76507 75328.76507 3.24139 3.24139 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 245968.82669 245968.82669 18.06262 18.06262 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 113147.20934 113147.20934 4.86806 4.86806 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 189292.14528 189292.14528 13.90056 13.90056 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.97433 8.40484E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 68139.67063 68139.67063 2.93087 2.93087 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 10653.46647 10653.46647 0.78234 0.78234 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 26.40000 8.40708E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 14813.23187 14813.23187 0.63795 0.63795 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 17539.49305 17539.49305 1.28800 1.28800 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:20:00 21.91067 8.40008E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 9822.97599 9822.97599 0.42308 0.42308 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 25753.69835 25753.69835 1.89121 1.89121 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 14885.77784 14885.77784 0.64108 0.64108 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 19754.36864 19754.36864 1.45065 1.45065 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.97433 8.40484E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 9283.17246 9283.17246 0.39976 0.39976 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -4.30000 2.65759E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8611.61008 8611.61008 0.49880 0.49880 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 23.07850 8.40189E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 07:20:00 -4.30000 2.65759E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 82737.02871 82737.02871 4.79226 4.79226 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 23.07850 8.40189E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -4.30000 2.65759E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8388.22590 8388.22590 0.48586 0.48586 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 23.07850 8.40189E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -4.30000 2.65759E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370135.52774 370135.52774 21.43844 21.43844 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 18.11900 8.39428E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 03:20:00 -4.30000 2.65759E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 121327.70 8.61436 8.61436 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 36184.92 1.76758 1.76758 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1111112.03 78.52302 78.52302 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 410948.23 26.65546 26.65546 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:50:00
5 VAV_TOP WITH REHEAT Cooling Sensible 124477.13 8.85276 8.85276 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 40928.61 4.13970 4.13970 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00
7 CAV_BAS Cooling Sensible 60472.96 4.83840 4.83840 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CAV_BAS Heating Sensible 63649.34 1.20016 1.20016 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 363852.27 21.43852 21.43852 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 17946.39 0.33839 0.33839 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8405.09 0.49880 0.49880 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 829.05 1.56323E-002 1.56323E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 80724.06 4.79226 4.79226 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 8290.49 0.15632 0.15632 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8185.16 0.48586 0.48586 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 829.05 1.56323E-002 1.56323E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.83840
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.21591
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36466
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61693
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.97243
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.04480E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.52354E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.61693
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16107.56992
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.52354E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 449.56389
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 48.64091
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.39104
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33200
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.14878
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.74330E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.54983E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.14878
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 345134.58467
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.54983E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 11133.03320
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.58960
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41442
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35200
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61554
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.19347E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48417E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.03784
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 67847.83054
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48417E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2643.00475
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.77192
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30939
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26300
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20301
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82503
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23147E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40820E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20301
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6437.48554
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40820E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 243.35927
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.24090
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12403
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10500
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13029
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33074
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.07192E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03970E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.14270
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4752.89290
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03970E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 185.19413
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.73479
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13767
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11700
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20297
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36712
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.76752E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.97217E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27097
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9015.61068
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.97217E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 351.04736
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.51264
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10175
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.60000E-002
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13009
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.74463E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.72980E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13009
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3076.47552
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.72980E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 102.28170
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.95364
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34345
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29200
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03046
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91586
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10934E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.51256E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.83689
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 160574.06910
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.51256E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6243.38941
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.04935
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31451
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.23043E-003
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.35367E-003
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.24139
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
122 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 107596.14412
123 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.35367E-003
124 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4183.24397
125 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 18.06262
126 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13222
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11200
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02301
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35259
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.88154E-003
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.53514E-003
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.86806
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
136 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 161606.23698
137 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.53514E-003
138 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6283.45533
139 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.90056
140 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11072
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.40000E-002
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30665
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.44116E-003
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.12868E-003
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.93087
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
150 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 97310.79693
151 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.12868E-003
152 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3783.92325
153 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.78234
154 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30526
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25900
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20263
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.81404
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.24810E-003
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.62989E-004
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63795
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
164 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21165.16446
165 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.62989E-004
166 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 822.60082
167 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.28800
168 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11949
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10200
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13138
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31864
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.18852E-003
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.07027E-004
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42308
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
178 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14035.47949
179 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.07027E-004
180 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 545.47829
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.89121
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12628
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10700
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20236
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33675
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.01706E-003
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.65259E-004
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.64108
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
192 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21268.94343
193 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.65259E-004
194 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 826.62888
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.45065
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10609
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.00000E-002
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13056
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.59116E-003
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.90134E-004
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.39976
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
206 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13263.27141
207 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.90134E-004
208 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 515.50218
209 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49880
210 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.79226
211 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48586
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.43844
213 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.23808
214 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28330
215 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.47616
216 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.28330
217 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.61436
218 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.61436
219 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
220 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.26506
221 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 50.30354
222 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.81384
223 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 100.60707
224 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 26.65546
225 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 78.52302
226 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 78.52302
227 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
228 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.33946
229 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.00090
230 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28246
231 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.00180
232 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 4.13970
233 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.85276
234 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.85276
235 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
236 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.46762
237 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.83840
238 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.83840
239 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 4.83840
240 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 4.83840
241 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 4.83840
242 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 4.83840
243 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.43844
246 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.43844
247 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.43844
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.43844
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.43852
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.43852
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 1.00000
253 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49880
254 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49880
255 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49880
256 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.49880
257 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.49880
258 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.49880
259 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
260 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
261 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.79226
262 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.79226
263 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.79226
264 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.79226
265 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.79226
266 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.79226
267 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
268 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
269 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48586
270 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48586
271 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48586
272 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.48586
273 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.48586
274 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.48586
275 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
276 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
277 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.61436
278 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 78.52302
279 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.85276
280 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 4.83840
281 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.43852
282 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.49880
283 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.79226
284 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.48586
285 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.61436
286 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 24.56480
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.02368
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75659E-003
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 148545.80679
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.24839E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.61436
294 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 44651.52048
295 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.76753E-004
296 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 958.79723
297 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.61436
298 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.24839E-003
299 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.12087E-004
300 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.76753E-004
301 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 78.52302
302 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 24.61976
303 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.02373
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.77033E-003
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1362567.91550
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.89693E-002
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 78.52302
310 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 389828.65840
311 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.52751E-003
312 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 8432.99738
313 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 78.52302
314 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.89693E-002
315 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.22196E-005
316 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.52751E-003
317 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.85276
318 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 24.54978
319 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
320 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.02366
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.75022E-003
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 152324.22543
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.35645E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.85276
326 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 38031.81396
327 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.31947E-004
328 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 842.54593
329 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.85276
330 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.35645E-003
331 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.09307E-004
332 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.31947E-004
333 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.83840
334 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
335 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.33248
336 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
337 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.40648
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.88532E-003
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 81703.00567
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.33670E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 4.83840
343 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 237871.60839
344 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.20345E-003
345 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 7574.98384
346 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 4.83840
347 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.33670E-003
348 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.03788E-004
349 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.20345E-003
350 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.43852
351 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
352 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.43852
353 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 423788.46397
354 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 305280.69362
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.03786E-002
356 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.43852
357 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.43852
358 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.43852
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.43852
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 423788.46397
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 423788.46397
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 17946.39161
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
364 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.43852
365 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.43852
366 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 423788.46397
367 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.03786E-002
368 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 17946.39161
369 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.43777E-004
370 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
371 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
373 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49880
374 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
375 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49880
376 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9605.67242
377 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 7011.55072
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.35242E-004
379 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49880
380 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49880
381 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49880
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49880
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9605.67242
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9605.67242
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 829.04894
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
387 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49880
388 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49880
389 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9605.67242
390 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.35242E-004
391 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 829.04894
392 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.79226
393 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
394 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.79226
395 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 92302.83647
396 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 67368.90731
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.26049E-003
398 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.79226
399 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.79226
400 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.79226
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.79226
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 92302.83647
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 92302.83647
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 8290.48945
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
406 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.79226
407 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.79226
408 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 92302.83647
409 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.26049E-003
410 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 8290.48945
411 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48586
412 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
413 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.48586
414 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9357.62254
415 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6830.01264
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.29168E-004
417 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48586
418 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48586
419 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48586
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48586
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9357.62254
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9357.62254
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 829.04894
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
425 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48586
426 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.48586
427 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9357.62254
428 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.29168E-004
429 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 829.04894
430 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 4.99108E-002
431 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 8068.22794
432 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 4.99108E-002
433 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 5.98930
434 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 4.99108E-002
435 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 4.99108E-002
436 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 209500.71469
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 8.33000
438 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.84908E-002
439 PlantLoop HEATSYS1 Plant Loop Volume [m3] 4.61889
440 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.84908E-002
441 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 11476.96219
442 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
443 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1759576.15691
444 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1759576.16000
445 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.84908E-002
446 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 4.99108E-002
447 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 5.98930
448 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 2.49554E-002
449 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 2792.95315
450 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 2.49554E-002
451 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 2792.95315
452 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 4.99108E-002
453 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 2.52893E-002
454 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 885233.91522
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 890621.69500
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 4.48129E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 4.99108E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 2.52893E-002
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 885233.91522
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 890621.69500
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 4.48129E-002
462 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.31035E-002
463 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.57241
464 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.31035E-002
465 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3308.94622
466 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.31035E-002
467 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
468 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 60065.15319
469 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
470 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7004.19857
471 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21491.69756
472 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 539749.91076
473 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 529000.48000
474 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.31035E-002
475 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
476 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
477 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
478 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
479 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
480 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 8.96259E-002
481 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 10.75511
482 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 8.96259E-002
483 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 21969.69233
484 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 33.00284
485 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1057999.85935
486 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 6.60057
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 132249.98242
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 33.00284
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1057999.85935
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 6.60057
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 132249.98242
492 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 4.57775E-002
493 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 4.57775E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 22423.26
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 480853.12
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 94417.72
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 8959.87
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6614.17
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 12546.24
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4285.24
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 223458.10
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 149732.99
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 224894.49
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 135419.61
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 29453.91
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 19532.09
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 29598.34
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 18457.46
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 47677.73
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 420392.97
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 42304.79
19 Coil:Heating:Water CAV_BAS HEATING COIL 256668.12


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 192282.41 142477.34 49805.07 0.74 33219.77 336.93
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 1758066.13 1300795.49 457270.64 0.74 302454.92 3067.67
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 197388.64 146336.67 51051.97 0.74 34148.82 346.36
4 Coil:Cooling:Water CAV_BAS COOLING COIL 105579.47 78914.14 26665.33 0.75 17639.72 178.91


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.90 23.54
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.90 23.54


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.838 0.744   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.807 0.720   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.923 0.811   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.3234148922 0.2349495799 Pass Pass 1.0496650339 6.8311455393 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 2.3720505164E-002 9.1953790399E-002 Pass Pass 7.6721337261E-003 8.7471970740E-002 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 6.6127745801E-003 6.9588866995E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 3.9054626514E-002 2.3974502013E-002 Pass Pass 0.5526123226 0.6968593024 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.7279977064E-002 5.1089236379E-002 Pass Pass 7.2314900392E-003 8.4764630427E-002 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 6.0895714732E-002 0.1091842864 Pass Pass 7.5123975733E-003 8.6469205950E-002 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 9.5247443153E-002 0.1337462738 Pass Pass 7.1200314785E-003 8.4090639948E-002 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 5.2219380742E-002 7.5872170795E-002 Pass Pass 7.2093728842E-003 8.4631037885E-002 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.3968380667E-002 2.0012493608E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 5.9313508598E-002 8.3245694266E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 9.6923373278E-002 0.1155926927 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 4.7898553419E-002 5.5346182865E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.2238896593 0.2074266443 Pass Pass 155.8944360320 1642.1235187252 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.1590402668 0.1678306259 Pass Pass 17.2695412351 42.2192890907 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.1297861388 0.1244045804 Pass Pass 21.2831629739 158.0148409905 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 8.5714329354E-002 8.5762876684E-002 Pass Pass 20.5503934885 75.1438251733 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 9.7099827590E-003 1.5849208706E-002 Pass Pass 0.1026723637 0.9339934682 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 9.4850351225E-003 9.2253906776E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.1360211624E-002 5.4509863477E-002 Pass Pass 0.4906709049 0.4791038855 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 3.9025961219E-006 5.1728303292E-006 Pass Pass 4.2653529734E-003 4.6424053325E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 4.4870448273E-006 8.3889862628E-006 Pass Pass 0.2631414259 1.9888194703 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 2.5885883221E-002 2.4089951059E-002 Pass Pass 4.3186239171E-003 6.0101741640E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.2810682779E-006 1.1072376459E-006 Pass Pass 5.9858316808E-005 1.0733456047E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5794.11 133.72 0.00 31048.59 4611.53 41587.96



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB -4.30 0.00 -4.30 Wetbulb [C] 1.20 110.00
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 26.40 9.10 17.00 Wetbulb [C] 2.10 90.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 42.00 35      
Mar 0.00 0      
Apr 0.00 0      
May 40.00 22      
Jun 4.00 8      
Jul 5.00 4      
Aug 7.00 8      
Sep 17.00 10      
Oct 50.00 49      
Nov 69.00 59      
Dec 95.00 53      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.744 0.838 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.744 0.838 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.744 0.838 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.744 0.838 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.720 0.807 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.720 0.807 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.720 0.807 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.720 0.807 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.811 0.923 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.811 0.923 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.811 0.923 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.811 0.923 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.744 0.838 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.744 0.838 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.744 0.838 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.744 0.838 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.720 0.807 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.720 0.807 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.720 0.807 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.720 0.807 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.811 0.923 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.811 0.923 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.811 0.923 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.811 0.923 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.363_SHGC_EAST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.363_SHGC_EAST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.363_SHGC_EAST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.363_SHGC_WEST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.363_SHGC_WEST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.363_SHGC_WEST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.378   115.90 0.00 0.00 115.90 1158.95 2.062 0.379 0.417             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.378   77.26 0.00 0.00 77.26 772.63 2.062 0.379 0.417             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.378   115.90 0.00 0.00 115.90 1158.95 2.062 0.379 0.417             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.378   77.26 0.00 0.00 77.26 772.63 2.062 0.379 0.417             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.378   115.90 0.00 0.00 115.90 115.90 2.062 0.379 0.417             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.378   77.26 0.00 0.00 77.26 77.26 2.062 0.379 0.417             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.378   115.90 0.00 0.00 115.90 115.90 2.062 0.379 0.417             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.378   77.26 0.00 0.00 77.26 77.26 2.062 0.379 0.417             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.062 0.379 0.417                      
North Total or Average             1390.74 2.062 0.379 0.417                      
Non-North Total or Average             3245.06 2.062 0.379 0.417                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.7776 2779.43 16058.30 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 116.04
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 5.7776 2496.12 14421.48 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 104.21
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 5.7776 24961.20 144214.83 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 1042.11
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 5.7776 2496.12 14421.48 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 104.21
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 5.7776 313.41 1810.76 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.84 0.0000 Y 7.76
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.60 0.0000 Y 4.95
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 5.7776 313.42 1810.80 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.47 0.0000 Y 7.64
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.67 0.0000 Y 4.97
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 5.7776 3134.13 18107.61 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.80 0.0000 Y 77.48
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 5.7776 2019.75 11669.23 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.57 0.0000 Y 49.43
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 5.7776 3134.20 18108.01 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.45 0.0000 Y 76.31
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 5.7776 2019.75 11669.23 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.64 0.0000 Y 49.59
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 5.7776 313.41 1810.76 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.79 0.0000 Y 7.75
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.56 0.0000 Y 4.94
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 5.7776 313.42 1810.80 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.45 0.0000 Y 7.63
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.64 0.0000 Y 4.96
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 5.7776 783.68 4527.75 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.66 0.0000 Y 32.85
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 7.1736 36.20 259.70 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 1.68
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 7.1736 362.03 2597.04 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 16.76
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 7.1736 36.20 259.70 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 1.68
Interior Lighting Total       5.7907 46320.38 268225.21               542.43


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.80 698.43
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.80 250.80
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.76 698.41
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.76 250.79
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.80 698.43
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.80 250.80
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.76 698.41
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.76 250.79
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.80 698.43
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.80 250.80
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.76 698.41
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.76 250.79
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 12952.94 AstronomicalClock -   42.50 42.50 103.33
EXTERIOR_LIGHTS_B 919.74 AstronomicalClock -   83.54 63.02 10.88
EXTERIOR_LIGHTS_C 17215.91 AstronomicalClock -   83.54 47.95 154.95
Exterior Lighting Total 31088.59           269.16



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 1739765.76          
HEATSYS1 BOILER Boiler:HotWater 1759576.16 0.94        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 890621.69 5.60 862904.53 4.71 6.90 23.54
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 890621.69 5.60 862904.53 4.71 6.90 23.54
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 529000.48 0.94        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1057999.86          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1057999.86          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 148545.81 192282.41 142477.34 49805.07 0.74 - 33219.77 336.93
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1362567.92 1758066.13 1300795.49 457270.64 0.74 - 302454.92 3067.67
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 152324.23 197388.64 146336.67 51051.97 0.74 - 34148.82 346.36
CAV_BAS COOLING COIL Coil:Cooling:Water 81703.01 105579.47 78914.14 26665.33 0.75 - 17639.72 178.91
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   423788.46 305280.69 118507.77 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9605.67 7011.55 2594.12 0.73 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   92302.84 67368.91 24933.93 0.73 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9357.62 6830.01 2527.61 0.73 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 16107.57 22423.26 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 345134.58 480853.12 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 67847.83 94417.72 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 6437.49 8959.87 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 4752.89 6614.17 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 9015.61 12546.24 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 3076.48 4285.24 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 160574.07 223458.10 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 107596.14 149732.99 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 161606.24 224894.49 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 97310.80 135419.61 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 21165.16 29453.91 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 14035.48 19532.09 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 21268.94 29598.34 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 13263.27 18457.46 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 44651.52 47677.73 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 389828.66 420392.97 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 38031.81 42304.79 -
CAV_BAS HEATING COIL Coil:Heating:Water 237871.61 256668.12 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   423788.46 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9605.67 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   92302.84 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9357.62 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   17946.39 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   829.05 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   8290.49 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   829.05 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.61 18615.18 2160.95 1.00 1.12 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 78.52 169684.06 2160.95 1.00 1.08 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.85 19130.34 2160.95 1.00 1.12 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 4.84 8204.25 1695.65 1.00 1.17 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.44 35544.49 1657.97 1.00 1.13 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 558.70 1120.11 1.00 1.61 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.79 5367.85 1120.11 1.00 1.16 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 544.21 1120.11 1.00 1.62 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.049911 8068.23 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.038491 11476.96 298174.34 0.91 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.024955 2792.95 111917.77 0.91 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.024955 2792.95 111917.77 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013103 3308.95 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.089626 21969.69 245126.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.49 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 66526.05 66526.05 23.94 4.838 4.838 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00903 19.67 0.00840 1.200 0.00
CORE_BOTTOM 71713.06 71713.06 28.73 5.216 5.216 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00894 19.67 0.00840 1.078 0.00
CORE_MID 668981.26 668981.26 268.01 48.641 48.641 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00897 19.67 0.00840 10.778 0.00
CORE_TOP 63136.12 63136.12 25.29 4.590 4.590 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00900 19.67 0.00840 1.078 0.00
PERIMETER_BOT_ZN_3 10511.50 10511.50 33.54 0.772 0.772 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00886 26.40 0.00841 0.135 0.00
PERIMETER_BOT_ZN_2 16898.06 16898.06 83.66 1.241 1.241 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 24.00 24.00 0.00864 21.11 0.00840 0.087 0.00
PERIMETER_BOT_ZN_1 23623.60 23623.60 75.37 1.735 1.735 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 24.00 0.00866 26.10 0.00841 0.135 0.00
PERIMETER_BOT_ZN_4 20598.58 20598.58 101.99 1.513 1.513 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00862 25.13 0.00841 0.087 0.00
PERIMETER_MID_ZN_3 94690.71 94690.71 302.13 6.954 6.954 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 24.00 0.00888 26.40 0.00841 1.353 0.00
PERIMETER_MID_ZN_2 177700.64 177700.64 879.81 13.049 13.049 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 24.00 24.00 0.00863 21.65 0.00840 0.872 0.00
PERIMETER_MID_ZN_1 245968.83 245968.83 784.79 18.063 18.063 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00865 26.17 0.00841 1.353 0.00
PERIMETER_MID_ZN_4 189292.15 189292.15 937.21 13.901 13.901 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00863 24.97 0.00840 0.872 0.00
PERIMETER_TOP_ZN_3 10653.47 10653.47 33.99 0.782 0.782 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00884 26.40 0.00841 0.135 0.00
PERIMETER_TOP_ZN_2 17539.49 17539.49 86.84 1.288 1.288 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:20:00 24.00 24.00 0.00864 21.91 0.00840 0.087 0.00
PERIMETER_TOP_ZN_1 25753.70 25753.70 82.17 1.891 1.891 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 24.00 0.00864 26.25 0.00841 0.135 0.00
PERIMETER_TOP_ZN_4 19754.37 19754.37 97.81 1.451 1.451 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00862 24.97 0.00840 0.087 0.00
DATACENTER_BOT_ZN_6 8611.61 8611.61 237.87 0.499 0.499 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 27.00 27.00 0.00858 23.08 0.00840 0.016 0.00
DATACENTER_MID_ZN_6 82737.03 82737.03 2285.38 4.792 4.792 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 27.00 27.00 0.00859 23.08 0.00840 0.156 0.00
DATACENTER_TOP_ZN_6 8388.23 8388.23 231.70 0.486 0.486 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 27.00 27.00 0.00859 23.08 0.00840 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370135.53 370135.53 472.30 21.438 21.438 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 27.00 27.00 0.00854 18.12 0.00839 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:10:00 21.00 24.57 0.00266 -4.30 0.00266 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:40:00 19.60 22.41 0.00266 -4.30 0.00266 1.078 0.00
CORE_MID 184263.37 184263.37 73.82 7.801 10.778 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -4.30 0.00266 10.778 0.00
CORE_TOP 47547.29 47547.29 19.05 2.038 2.038 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -4.30 0.00266 1.078 0.00
PERIMETER_BOT_ZN_3 4418.23 4418.23 14.10 0.189 0.189 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00723 -4.30 0.00266 0.135 0.00
PERIMETER_BOT_ZN_2 3333.29 3333.29 16.50 0.143 0.143 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00733 -4.30 0.00266 0.087 0.00
PERIMETER_BOT_ZN_1 6319.17 6319.17 20.16 0.271 0.271 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00748 -4.30 0.00266 0.135 0.00
PERIMETER_BOT_ZN_4 1783.70 1783.70 8.83 0.076 0.087 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00675 -4.30 0.00266 0.087 0.00
PERIMETER_MID_ZN_3 112425.85 112425.85 358.71 4.837 4.837 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -4.30 0.00266 1.353 0.00
PERIMETER_MID_ZN_2 75328.77 75328.77 372.96 3.241 3.241 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00769 -4.30 0.00266 0.872 0.00
PERIMETER_MID_ZN_1 113147.21 113147.21 361.01 4.868 4.868 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -4.30 0.00266 1.353 0.00
PERIMETER_MID_ZN_4 68139.67 68139.67 337.37 2.931 2.931 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00761 -4.30 0.00266 0.872 0.00
PERIMETER_TOP_ZN_3 14813.23 14813.23 47.26 0.638 0.638 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 -4.30 0.00266 0.135 0.00
PERIMETER_TOP_ZN_2 9822.98 9822.98 48.63 0.423 0.423 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00779 -4.30 0.00266 0.087 0.00
PERIMETER_TOP_ZN_1 14885.78 14885.78 47.49 0.641 0.641 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 -4.30 0.00266 0.135 0.00
PERIMETER_TOP_ZN_4 9283.17 9283.17 45.96 0.400 0.400 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -4.30 0.00266 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 07:20:00 18.00 26.98 0.00850 -4.30 0.00266 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 23.70 0.00664 -4.30 0.00266 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 21.93 0.00299 -4.30 0.00266 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 03:20:00 18.00 27.00 0.00850 -4.30 0.00266 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 8.61 8.61 1.77 1.77 8.6144 2.2833 8.6144 0.2651 0.3000
VAV_MID WITH REHEAT 78.52 78.52 26.66 26.66 78.5230 26.6555 78.5230 0.3395 0.3000
VAV_TOP WITH REHEAT 8.85 8.85 4.14 4.14 8.8528 4.1397 8.8528 0.4676 0.3000
CAV_BAS 4.84 4.84 1.20 1.20 4.8384 4.8384 4.8384 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.44 21.44 0.34 0.34 21.4385 21.4384 21.4385 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.50 0.50 0.02 0.02 0.4988 0.4988 0.4988 1.0000 1.0000
AIRLOOP DATACENTER MID 4.79 4.79 0.16 0.16 4.7923 4.7923 4.7923 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.49 0.49 0.02 0.02 0.4859 0.4859 0.4859 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 16107.570 16107.570 1.616931 0.00035235 449.564 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:40:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:40:00 16107.57 16107.57 1.616931 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00800000 51.1678 0.00 0.00 16135.22 16135.22
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 345134.585 345134.585 16.148781 0.00754983 11133.033 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 345134.58 345134.58 16.148781 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00800000 51.1678 184263.37 0.00 346025.81 346025.81
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 67847.831 67847.831 2.037835 0.00148417 2643.005 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 67847.83 67847.83 2.037835 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00800000 51.1678 47547.29 0.00 67992.26 67992.26
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 6437.486 6437.486 0.203014 0.00014082 243.359 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6437.49 6437.49 0.203014 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00723152 46.3127 4418.23 0.00 6451.53 6451.53
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 4752.893 4752.893 0.142701 0.00010397 185.194 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4752.89 4752.89 0.142701 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00732858 46.9271 3333.29 0.00 4763.01 4763.01
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 9015.611 9015.611 0.270971 0.00019722 351.047 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9015.61 9015.61 0.270971 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00748196 47.8971 6319.17 0.00 9034.80 9034.80
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 3076.476 3076.476 0.130087 0.00006730 102.282 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3076.48 3076.48 0.130087 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00674572 43.2345 1783.70 0.00 3084.09 3084.09
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 160574.069 160574.069 4.836890 0.00351256 6243.389 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 160574.07 160574.07 4.836890 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00766876 49.0786 112425.85 0.00 160916.02 160916.02
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 107596.144 107596.144 3.241392 0.00235367 4183.244 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 107596.14 107596.14 3.241392 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00768866 49.2043 75328.77 0.00 107825.28 107825.28
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 161606.237 161606.237 4.868061 0.00353514 6283.455 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 161606.24 161606.24 4.868061 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00767386 49.1108 113147.21 0.00 161950.38 161950.38
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 97310.797 97310.797 2.930865 0.00212868 3783.923 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 97310.80 97310.80 2.930865 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00760768 48.6929 68139.67 0.00 97518.02 97518.02
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 21165.164 21165.164 0.637950 0.00046299 822.601 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21165.16 21165.16 0.637950 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00778320 49.8011 14813.23 0.00 21210.24 21210.24
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 14035.479 14035.479 0.423077 0.00030703 545.478 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14035.48 14035.48 0.423077 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00778593 49.8184 9822.98 0.00 14065.37 14065.37
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 21268.943 21268.943 0.641085 0.00046526 826.629 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21268.94 21268.94 0.641085 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00778493 49.8120 14885.78 0.00 21314.24 21314.24
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 13263.271 13263.271 0.399758 0.00029013 515.502 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13263.27 13263.27 0.399758 12.80 11.50 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00776096 49.6608 9283.17 0.00 13291.52 13291.52
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 148545.807 -999.000 8.614364 0.00424839 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 148545.81 141638.42 8.614364 24.56 16.70 0.00875659 11.02 11.02 0.00850000 26.40 0.00840708 17.04 23.5711 24.00 0.00886438 47.1868 117304.72 0.00 149965.53 137678.77
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 44651.520 44651.520 2.584309 0.00097675 958.797 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 44651.52 44651.52 2.584309 -1.63 -2.08 0.00304485 12.80 11.50 0.00800000 -4.30 0.00265759 -4.30 78.5703 21.58 0.00543084 33.6598 15854.39 0.00 41530.62 41530.62
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1362567.916 -999.000 78.523019 0.03896927 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 1362567.92 1296242.76 78.523019 24.62 16.73 0.00877033 11.02 11.02 0.00850000 26.40 0.00840708 17.04 25.8599 24.00 0.00889703 47.3581 1069274.76 0.00 1375500.49 1260185.77
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 389828.658 389828.658 23.556906 0.00852751 8432.997 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:50:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 389828.66 389828.66 23.556906 -1.02 -1.27 0.00334259 12.80 11.50 0.00800000 -4.30 0.00265759 -4.30 86.1998 19.60 0.00727439 50.7962 276002.70 0.00 366216.61 366216.61
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 152324.225 -999.000 8.852760 0.00435645 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 152324.23 145401.43 8.852760 24.55 16.69 0.00875022 11.02 11.02 0.00850000 26.40 0.00840708 17.04 22.9363 24.00 0.00885240 47.1239 120503.65 0.00 153783.46 141327.65
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 38031.814 38031.814 2.655828 0.00083195 842.546 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 38031.81 38031.81 2.655828 0.84 0.53 0.00384290 12.80 11.50 0.00800000 -4.30 0.00265759 -4.30 76.4545 17.60 0.00743777 58.8497 30172.03 0.00 36857.16 36857.16
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 81703.006 -999.000 4.838396 0.00233670 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 81703.01 76035.20 4.838396 24.33 16.72 0.00888532 11.41 11.41 0.00850000 25.22 0.00840522 16.63 24.8048 24.00 0.00906651 48.2478 59644.77 0.00 82472.79 74879.20
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 237871.608 237871.608 4.838396 0.00520345 7574.984 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 237871.61 237871.61 4.838396 -1.07 -2.38 0.00265759 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 24.8048 24.61 0.00265759 13.7722 0.00 0.00 184135.57 184135.57
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 423788.464 305280.694 21.438518 0.01037855 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 394433.80 392103.39 -999.0 28.40 17.83 0.00854030 12.80 12.00 0.00850000 26.40 0.00840708 17.04 -999.0000 27.00 0.00854244 38.0744 369812.80 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9605.672 7011.551 0.498796 0.00023524 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 8901.11 8796.13 -999.0 27.83 17.67 0.00857823 12.80 12.00 0.00850000 23.08 0.00840189 15.87 -999.0000 27.00 0.00858394 38.2544 8611.61 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92302.836 67368.907 4.792260 0.00226049 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 85534.41 84486.15 -999.0 27.83 17.67 0.00858130 12.80 12.00 0.00850000 23.08 0.00840189 15.87 -999.0000 27.00 0.00858735 38.2695 82737.03 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9357.623 6830.013 0.485858 0.00022917 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 8671.39 8566.40 -999.0 27.83 17.67 0.00858032 12.80 12.00 0.00850000 23.08 0.00840189 15.87 -999.0000 27.00 0.00858625 38.2646 8388.23 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 423788.464 423788.464 21.438518 0.01037855 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 423788.46 423788.46 21.438518 -4.30 -4.30 0.00265759 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 1.5784 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9605.672 9605.672 0.498796 0.00023524 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9605.67 9605.67 0.498796 -4.30 -4.30 0.00265759 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 3.1340 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92302.836 92302.836 4.792260 0.00226049 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 92302.84 92302.84 4.792260 -4.30 -4.30 0.00265759 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 3.2620 24.82 0.00664384 33.7944 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9357.623 9357.623 0.485858 0.00022917 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9357.62 9357.62 0.485858 -4.30 -4.30 0.00265759 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 3.2175 23.75 0.00298867 16.3024 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 17946.392 17946.392 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 17946.39 17946.39 21.438518 -0.07 -0.07 0.00840778 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 1.5784 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 829.049 829.049 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 829.05 829.05 0.498796 -0.13 -0.13 0.00831690 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 3.1340 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 8290.489 8290.489 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8290.49 8290.49 4.792260 -0.14 -0.14 0.00651381 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 3.2620 24.82 0.00664384 33.7944 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 829.049 829.049 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 829.05 829.05 0.485858 -0.14 -1.35 0.00297802 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 3.2175 23.75 0.00298867 16.3024 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 16107.570 16107.570 1.616931 0.00035235 449.564 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 0.8974 0.915423 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:40:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:40:00 Sensible 16107.57 16107.57 1.0000 1.92636604 1.616931 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.35231760 60.00 48.89 11.11 0.000 16107.57 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.1678 0.00 0.00 16135.22 16135.22 1.92636604 12.80 11.60 0.00800000 33059.8 21.01 14.86 0.00800000 41435.8
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 345134.585 345134.585 16.148781 0.00754983 11133.033 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 19.2277 19.614643 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 345134.58 345134.58 1.0000 19.23920570 16.148781 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 7.54905847 60.00 48.89 11.11 0.000 345134.58 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.57 0.00800000 21.00 0.00800000 51.1678 184263.37 0.00 346025.81 346025.81 19.23920570 12.80 11.60 0.00800000 33059.8 30.44 18.18 0.00800000 51045.3
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 67847.831 67847.831 2.037835 0.00148417 2643.005 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 3.7798 3.855919 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 67847.83 67847.83 1.0000 2.42781980 2.037835 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 1.48402178 60.00 48.89 11.11 0.000 67847.83 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.92 0.00800000 21.00 0.00800000 51.1678 47547.29 0.00 67992.26 67992.26 2.42781980 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61065.3
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 6437.486 6437.486 0.203014 0.00014082 243.359 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 0.3586 0.365854 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6437.49 6437.49 1.0000 0.24186526 0.203014 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.14080581 60.00 48.89 11.11 0.000 6437.49 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.87 0.00723152 21.00 0.00723152 46.3127 4418.23 0.00 6451.53 6451.53 0.24186526 12.80 11.60 0.00800000 33059.8 38.96 20.87 0.00800000 59733.9
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 4752.893 4752.893 0.142701 0.00010397 185.194 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 0.2648 0.270116 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4752.89 4752.89 1.0000 0.17000985 0.142701 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.10395906 60.00 48.89 11.11 0.000 4752.89 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.86 0.00732858 21.00 0.00732858 46.9271 3333.29 0.00 4763.01 4763.01 0.17000985 12.80 11.60 0.00800000 33059.8 40.27 21.26 0.00800000 61075.9
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 9015.611 9015.611 0.270971 0.00019722 351.047 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 0.5023 0.512374 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9015.61 9015.61 1.0000 0.32282679 0.270971 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.19719662 60.00 48.89 11.11 0.000 9015.61 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.91 0.00748196 21.00 0.00748196 47.8971 6319.17 0.00 9034.80 9034.80 0.32282679 12.80 11.60 0.00800000 33059.8 40.25 21.25 0.00800000 61046.4
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 3076.476 3076.476 0.130087 0.00006730 102.282 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 0.1714 0.174842 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3076.48 3076.48 1.0000 0.15498257 0.130087 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.06729112 60.00 48.89 11.11 0.000 3076.48 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.83 0.00674572 21.00 0.00674572 43.2345 1783.70 0.00 3084.09 3084.09 0.15498257 12.80 11.60 0.00800000 33059.8 32.31 18.80 0.00800000 52959.4
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 160574.069 160574.069 4.836890 0.00351256 6243.389 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 8.9457 9.125724 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 160574.07 160574.07 1.0000 5.76253577 4.836890 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 3.51220391 60.00 48.89 11.11 0.000 160574.07 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00766876 21.00 0.00766876 49.0786 112425.85 0.00 160916.02 160916.02 5.76253577 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60984.3
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 107596.144 107596.144 3.241392 0.00235367 4183.244 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 5.9943 6.114890 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 107596.14 107596.14 1.0000 3.86170416 3.241392 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 2.35342854 60.00 48.89 11.11 0.000 107596.14 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00768866 21.00 0.00768866 49.2043 75328.77 0.00 107825.28 107825.28 3.86170416 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60981.5
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 161606.237 161606.237 4.868061 0.00353514 6283.455 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 9.0032 9.184384 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 161606.24 161606.24 1.0000 5.79967210 4.868061 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 3.53478030 60.00 48.89 11.11 0.000 161606.24 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00767386 21.00 0.00767386 49.1108 113147.21 0.00 161950.38 161950.38 5.79967210 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60983.9
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 97310.797 97310.797 2.930865 0.00212868 3783.923 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 5.4212 5.530354 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 97310.80 97310.80 1.0000 3.49175060 2.930865 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 2.12845924 60.00 48.89 11.11 0.000 97310.80 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.91 0.00760768 21.00 0.00760768 48.6929 68139.67 0.00 97518.02 97518.02 3.49175060 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.9
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 21165.164 21165.164 0.637950 0.00046299 822.601 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 1.1791 1.202856 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 21165.16 21165.16 1.0000 0.76003624 0.637950 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.46294133 60.00 48.89 11.11 0.000 21165.16 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00778320 21.00 0.00778320 49.8011 14813.23 0.00 21210.24 21210.24 0.76003624 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60966.7
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 14035.479 14035.479 0.423077 0.00030703 545.478 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 0.7819 0.797663 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 14035.48 14035.48 1.0000 0.50404189 0.423077 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.30699518 60.00 48.89 11.11 0.000 14035.48 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00778593 21.00 0.00778593 49.8184 9822.98 0.00 14065.37 14065.37 0.50404189 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60965.0
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 21268.943 21268.943 0.641085 0.00046526 826.629 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 1.1849 1.208754 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 21268.94 21268.94 1.0000 0.76377062 0.641085 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.46521127 60.00 48.89 11.11 0.000 21268.94 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00778493 21.00 0.00778493 49.8120 14885.78 0.00 21314.24 21314.24 0.76377062 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60966.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 13263.271 13263.271 0.399758 0.00029013 515.502 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 0.7389 0.753776 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13263.27 13263.27 1.0000 0.47626009 0.399758 12.80 11.50 0.00800000 33059.8 40.00 21.06 0.00800000 60796.0 0.29010483 60.00 48.89 11.11 0.000 13263.27 -4.30 0.00265759 -4.30 0.00000000 0.0000 20.95 0.00776096 21.00 0.00776096 49.6608 9283.17 0.00 13291.52 13291.52 0.47626009 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60967.9
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 148545.807 -999.000 8.614364 0.00424839 -999.000 -999.0000 1.00000 1.00000 1021.1181 1004.8586 1.1914 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.614364 10.26291185   4197.9300 999.8980 49.90571894 15.00 6.67 8.33 1745140.95 8.5120 8.511966 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 Sensible 148545.81 141638.42 1.0000 10.26291185 8.614364 24.56 16.70 0.00875659 46983.3 11.02 11.02 0.00850000 32509.2 4.24795789 6.67 15.00 8.33 18615.181 129930.63 26.40 0.00840708 17.04 2.03050000 23.5711 24.00 0.00886438 24.00 0.00886438 47.1868 117304.72 0.00 149965.53 137678.77 10.26291185 24.56 16.81 0.00875659 46983.3 11.43 11.30 0.00828192 32370.9
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 44651.520 44651.520 2.584309 0.00097675 958.797 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.614364 10.26291185   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 2.4876 2.537629 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 44651.52 44651.52 1.0000 3.07887356 2.584309 -1.63 -2.08 0.00304485 5965.4 12.80 11.50 0.00800000 33059.8 0.97665361 60.00 48.89 11.11 0.000 44651.52 -4.30 0.00265759 -4.30 2.03050000 78.5703 8.15 0.00446471 21.58 0.00543084 33.6598 15854.39 0.00 41530.62 41530.62 3.07887356 2.80 0.59 0.00304485 10444.4 16.15 7.66 0.00304485 23933.3
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1362567.916 -999.000 78.523019 0.03896927 -999.000 -999.0000 1.00000 1.00000 1021.1436 1004.8586 1.1914 VAV_MID WITH REHEAT FAN Fan:VariableVolume 78.523019 93.55012744   4197.9300 999.8980 49.90571894 15.00 6.67 8.33 1745140.95 78.0778 78.077814 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 1362567.92 1296242.76 1.0000 93.55012744 78.523019 24.62 16.73 0.00877033 47074.4 11.02 11.02 0.00850000 32509.3 38.96529463 6.67 15.00 8.33 169684.063 1192883.85 26.40 0.00840708 17.04 20.30600000 25.8599 24.00 0.00889703 24.00 0.00889703 47.3581 1069274.76 0.00 1375500.49 1260185.77 93.55012744 24.62 16.84 0.00877033 47074.4 11.43 11.30 0.00828160 32371.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 389828.658 389828.658 23.556906 0.00852751 8432.997 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV_MID WITH REHEAT FAN Fan:VariableVolume 78.523019 93.55012744   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 21.7176 22.154691 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:50:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 389828.66 389828.66 1.0000 28.06503823 23.556906 -1.02 -1.27 0.00334259 7325.3 12.80 11.50 0.00800000 33059.8 8.52664284 60.00 48.89 11.11 0.000 389828.66 -4.30 0.00265759 -4.30 20.30600000 86.1998 19.45 0.00762131 19.60 0.00727439 50.7962 276002.70 0.00 366216.61 366216.61 28.06503823 2.80 1.02 0.00334259 11190.6 15.71 7.80 0.00334259 24239.4
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 152324.225 -999.000 8.852760 0.00435645 -999.000 -999.0000 1.00000 1.00000 1021.1062 1004.8586 1.1914 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.852760 10.54693057   4197.9300 999.8980 49.90571894 15.00 6.67 8.33 1745140.95 8.7285 8.728477 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 152324.23 145401.43 1.0000 10.54693057 8.852760 24.55 16.69 0.00875022 46951.7 11.02 11.02 0.00850000 32509.2 4.35600916 6.67 15.00 8.33 19130.343 133193.88 26.40 0.00840708 17.04 2.03050000 22.9363 24.00 0.00885240 24.00 0.00885240 47.1239 120503.65 0.00 153783.46 141327.65 10.54693057 24.55 16.80 0.00875022 46951.7 11.43 11.30 0.00828198 32370.8
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 38031.814 38031.814 2.655828 0.00083195 842.546 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.852760 10.54693057   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 2.1188 2.161419 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 38031.81 38031.81 1.0000 3.16407917 2.655828 0.84 0.53 0.00384290 10459.2 12.80 11.50 0.00800000 33059.8 0.83186212 60.00 48.89 11.11 0.000 38031.81 -4.30 0.00265759 -4.30 2.03050000 76.4545 17.52 0.00769174 17.60 0.00743777 58.8497 30172.03 0.00 36857.16 36857.16 3.16407917 2.80 1.73 0.00384290 12444.4 14.31 7.72 0.00384290 24093.0
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 81703.006 -999.000 4.838396 0.00233670 -999.000 -999.0000 1.00000 1.00000 1021.3574 1004.8586 1.1914 CAV_BAS FAN Fan:ConstantVolume 4.838396 5.76432988   4197.9300 999.8980 49.90571894 15.00 6.67 8.33 1745140.95 4.6817 4.681742 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 81703.01 76035.20 1.0000 5.76432988 4.838396 24.33 16.72 0.00888532 47073.8 11.41 11.41 0.00850000 32899.9 2.33645725 6.67 15.00 8.33 8204.248 73498.76 25.22 0.00840522 16.63 1.20015641 24.8048 24.00 0.00906651 24.00 0.00906651 48.2478 59644.77 0.00 82472.79 74879.20 5.76432988 24.33 16.84 0.00888532 47073.8 11.61 11.47 0.00836309 32766.4
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 237871.608 237871.608 4.838396 0.00520345 7574.984 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 CAV_BAS FAN Fan:ConstantVolume 4.838396 5.76432988   4197.9300 999.8980 38.48685087 48.89 60.00 11.11 1794988.33 13.2520 13.518688 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 237871.61 237871.61 1.0000 5.76432988 4.838396 -1.07 -2.38 0.00265759 5569.4 40.00 21.06 0.00800000 60796.0 5.20291724 60.00 48.89 11.11 0.000 237871.61 -4.30 0.00265759 -4.30 1.20015641 24.8048 0.00 0.00265759 24.61 0.00265759 13.7722 0.00 0.00 184135.57 184135.57 5.76432988 12.80 5.54 0.00265759 19571.7 44.43 18.47 0.00265759 51515.6
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 423788.464 305280.694 21.438518 0.01037855 -999.000 -999.0000 -999.00000 -999.00000 1020.7160 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 Sensible 394433.80 392103.39 0.9307 -999.0 -999.0 28.40 17.83 0.00854030 50350.2 12.80 12.00 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 394433.80 26.40 0.00840708 17.04 0.33839277 -999.0000 27.00 0.00854244 27.00 0.00854244 38.0744 369812.80 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9605.672 7011.551 0.498796 0.00023524 -999.000 -999.0000 -999.00000 -999.00000 1020.7865 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 8901.11 8796.13 0.9267 -999.0 -999.0 27.83 17.67 0.00857823 49863.4 12.80 12.00 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8901.11 23.08 0.00840189 15.87 0.01563234 -999.0000 27.00 0.00858394 27.00 0.00858394 38.2544 8611.61 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 92302.836 67368.907 4.792260 0.00226049 -999.000 -999.0000 -999.00000 -999.00000 1020.7922 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 85534.41 84486.15 0.9267 -999.0 -999.0 27.83 17.67 0.00858130 49866.0 12.80 12.00 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 85534.41 23.08 0.00840189 15.87 0.15632344 -999.0000 27.00 0.00858735 27.00 0.00858735 38.2695 82737.03 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9357.623 6830.013 0.485858 0.00022917 -999.000 -999.0000 -999.00000 -999.00000 1020.7904 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 8671.39 8566.40 0.9267 -999.0 -999.0 27.83 17.67 0.00858032 49865.3 12.80 12.00 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8671.39 23.08 0.00840189 15.87 0.01563234 -999.0000 27.00 0.00858625 27.00 0.00858625 38.2646 8388.23 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 423788.464 423788.464 21.438518 0.01037855 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 423788.46 423788.46 1.0000 25.54125045 21.438518 -4.30 -4.30 0.00265759 2304.4 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 423788.46 -4.30 0.00265759 -4.30 0.33839277 1.5784 0.00 0.00850000 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9605.672 9605.672 0.498796 0.00023524 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9605.67 9605.67 1.0000 0.59425115 0.498796 -4.30 -4.30 0.00265759 2304.4 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9605.67 -4.30 0.00265759 -4.30 0.01563234 3.1340 0.00 0.00850000 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 92302.836 92302.836 4.792260 0.00226049 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 92302.84 92302.84 1.0000 5.70936456 4.792260 -4.30 -4.30 0.00265759 2304.4 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 92302.84 -4.30 0.00265759 -4.30 0.15632344 3.2620 0.00 0.00664384 24.82 0.00664384 33.7944 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9357.623 9357.623 0.485858 0.00022917 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9357.62 9357.62 1.0000 0.57883786 0.485858 -4.30 -4.30 0.00265759 2304.4 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9357.62 -4.30 0.00265759 -4.30 0.01563234 3.2175 0.00 0.00298867 23.75 0.00298867 16.3024 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 17946.392 17946.392 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.438518 25.54125045   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 17946.39 17946.39 1.0000 25.54125045 21.438518 -0.07 -0.07 0.00840778 20958.1 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 17946.39 -4.30 0.00265759 -4.30 0.33839277 1.5784 0.00 0.00850000 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 829.049 829.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.498796 0.59425115   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 829.05 829.05 1.0000 0.59425115 0.498796 -0.13 -0.13 0.00831690 20662.6 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 829.05 -4.30 0.00265759 -4.30 0.01563234 3.1340 0.00 0.00850000 27.00 0.00850000 37.8820 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 8290.489 8290.489 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.792260 5.70936456   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 8290.49 8290.49 1.0000 5.70936456 4.792260 -0.14 -0.14 0.00651381 16148.0 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8290.49 -4.30 0.00265759 -4.30 0.15632344 3.2620 0.00 0.00664384 24.82 0.00664384 33.7944 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 829.049 829.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.485858 0.57883786   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 829.05 829.05 1.0000 0.57883786 0.485858 -0.14 -1.35 0.00297802 7308.1 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 829.05 -4.30 0.00265759 -4.30 0.01563234 3.2175 0.00 0.00298867 23.75 0.00298867 16.3024 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 8.61 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 78.52 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 8.85 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 4.84 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 21.44 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2182.00 422.17 0.00
CORE_BOTTOM 2163.33 546.17 12.00
CORE_MID 938.67 2944.17 12.50
CORE_TOP 1158.17 4220.00 458.83
PERIMETER_BOT_ZN_3 1170.00 3311.00 17.83
PERIMETER_BOT_ZN_2 1696.33 3160.67 121.17
PERIMETER_BOT_ZN_1 1969.50 2934.67 153.83
PERIMETER_BOT_ZN_4 2741.83 1353.33 160.67
PERIMETER_MID_ZN_3 1468.50 4504.50 866.17
PERIMETER_MID_ZN_2 1759.67 3289.67 736.50
PERIMETER_MID_ZN_1 2050.83 3482.00 525.50
PERIMETER_MID_ZN_4 1911.33 3717.17 587.83
PERIMETER_TOP_ZN_3 2380.33 4810.33 1827.67
PERIMETER_TOP_ZN_2 2853.00 4008.83 1634.17
PERIMETER_TOP_ZN_1 2594.67 3943.67 1292.00
PERIMETER_TOP_ZN_4 2493.50 4120.50 1329.33
DATACENTER_BOT_ZN_6 5943.00 473.33 473.33
DATACENTER_MID_ZN_6 5910.33 52.50 52.50
DATACENTER_TOP_ZN_6 5450.67 207.67 101.17
DATACENTER_BASEMENT_ZN_6 5943.00 5638.67 5638.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5917.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 44.50 0.00 6.50
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 3.83 0.00 0.50 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 0.00 25.67 0.00 25.67
PERIMETER_BOT_ZN_1 0.00 35.00 0.00 34.50
PERIMETER_BOT_ZN_4 0.00 72.00 0.00 41.17
PERIMETER_MID_ZN_3 3.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 3.83 24.50 0.00 24.50
PERIMETER_MID_ZN_1 1.17 32.17 0.00 31.33
PERIMETER_MID_ZN_4 1.33 29.17 0.00 16.00
PERIMETER_TOP_ZN_3 65.00 0.00 19.17 0.00
PERIMETER_TOP_ZN_2 26.67 20.83 0.50 20.50
PERIMETER_TOP_ZN_1 18.67 27.00 0.00 25.67
PERIMETER_TOP_ZN_4 14.50 27.67 0.00 16.17
DATACENTER_BOT_ZN_6 0.00 0.33 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 2.00 0.00 2.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 68.17 229.17 19.67 146.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.19 149.60 6779.02 1.168 0.000 0.000 0.000
CORE_BOTTOM 54.95 134.35 6849.35 0.911 0.000 0.000 0.000
CORE_MID 54.95 134.35 6849.35 0.681 0.000 0.000 0.000
CORE_TOP 54.95 134.35 6849.35 0.631 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.90 16.87 860.00 0.833 0.025 0.000 0.000
PERIMETER_BOT_ZN_2 4.45 10.87 554.22 1.226 0.026 0.000 0.000
PERIMETER_BOT_ZN_1 6.90 16.87 860.02 1.383 0.025 0.000 0.000
PERIMETER_BOT_ZN_4 4.45 10.87 554.22 1.865 0.026 0.000 0.000
PERIMETER_MID_ZN_3 6.90 16.87 860.00 0.665 0.059 0.000 0.000
PERIMETER_MID_ZN_2 3.88 10.87 554.22 1.035 0.064 0.000 0.000
PERIMETER_MID_ZN_1 6.90 16.87 860.02 1.300 0.059 0.000 0.000
PERIMETER_MID_ZN_4 4.45 10.87 554.22 1.179 0.061 0.000 0.000
PERIMETER_TOP_ZN_3 6.90 16.87 860.00 0.651 0.073 0.000 0.000
PERIMETER_TOP_ZN_2 4.45 10.87 554.22 1.106 0.075 0.000 0.000
PERIMETER_TOP_ZN_1 6.90 16.87 860.02 1.242 0.073 0.000 0.000
PERIMETER_TOP_ZN_4 4.45 10.87 554.22 1.153 0.075 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.25 42.18 1911.37 25.171 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.19 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 54.95 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 54.95 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 54.95 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.90 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.90 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.90 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.88 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.90 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.90 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.90 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.45 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.25 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 61.19 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 54.95 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 54.95 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 54.95 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.90 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.90 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.90 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.88 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.90 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.90 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.90 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.80 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.25 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1014.08 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 47243935.77 0.00 47243935.77 0.00 47243935.77 37848132.68 4043.51 221.04 4495.45 221.61
CORE_BOTTOM 37778974.07 0.00 37778974.07 0.00 37778974.07 33990283.35 3906.46 127.06 4726.48 295.39
CORE_MID 0.28E+09 0.00 0.28E+09 0.00 0.28E+09 0.34E+09 4329.45 846.14 3584.41 117.83
CORE_TOP 25706200.70 0.00 25706200.70 0.00 25706200.70 33990283.35 4545.17 1365.26 2849.57 216.40
PERIMETER_BOT_ZN_3 4338383.21 0.00 4338383.21 255127.48 4593510.69 4267819.30 5483.17 268.52 3008.31 295.39
PERIMETER_BOT_ZN_2 4063433.04 0.00 4063433.04 170084.87 4233517.91 2750345.05 5367.87 312.20 3079.93 295.39
PERIMETER_BOT_ZN_1 7096373.53 0.00 7096373.53 255127.48 7351501.01 4267912.63 5155.94 263.11 3340.95 295.39
PERIMETER_BOT_ZN_4 6209100.06 0.00 6209100.06 170084.87 6379184.93 2750345.05 4164.79 250.49 4344.72 295.39
PERIMETER_MID_ZN_3 34023939.31 0.00 34023939.31 598343.38 34622282.68 42678193.03 4782.58 797.94 3179.48 117.83
PERIMETER_MID_ZN_2 34964663.36 0.00 34964663.36 398895.31 35363558.67 27503450.52 4957.22 957.92 2844.87 621.25
PERIMETER_MID_ZN_1 65823151.50 0.00 65823151.50 598343.38 66421494.88 42679126.28 4424.04 1064.29 3271.67 117.83
PERIMETER_MID_ZN_4 38868400.59 0.00 38868400.59 398895.31 39267295.90 27503450.52 4609.17 879.99 3270.84 117.83
PERIMETER_TOP_ZN_3 3336930.22 0.00 3336930.22 742904.54 4079834.76 4267819.30 4516.99 1458.11 2784.90 216.40
PERIMETER_TOP_ZN_2 3620391.74 0.00 3620391.74 495269.35 4115661.09 2750345.05 4348.99 710.02 3700.99 216.40
PERIMETER_TOP_ZN_1 6297239.85 0.00 6297239.85 742904.54 7040144.39 4267912.63 4314.93 1586.01 2859.05 216.40
PERIMETER_TOP_ZN_4 3807515.24 0.00 3807515.24 495269.35 4302784.59 2750345.05 4447.33 1459.31 2853.37 216.40
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.39E+09 0.00 0.39E+09 0.00 0.39E+09 10671554.30 2.50 7.17 8750.33 2815.50
Total Facility 0.51E+10 0.00 0.51E+10 23271546.24 0.51E+10 0.50E+10 6544.98 4382.25 8757.44 3318.92


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.1559 0.0000 2.1559 0.0000 2.1559 1.2002 1322.41 219.37 4401.22
CORE_BOTTOM 1.6992 0.0000 1.6992 0.0000 1.6992 1.0778 1289.93 121.02 4532.05
CORE_MID 12.6999 0.0000 12.6999 0.0000 12.6999 10.7782 1588.09 844.60 3510.31
CORE_TOP 1.1800 0.0000 1.1800 0.0000 1.1800 1.0778 1780.67 1364.76 2797.57
PERIMETER_BOT_ZN_3 0.1953 0.0000 0.1953 0.0059 0.2012 0.1353 2856.19 261.91 2824.90
PERIMETER_BOT_ZN_2 0.1851 0.0000 0.1851 0.0039 0.1891 0.0872 2739.49 306.06 2897.45
PERIMETER_BOT_ZN_1 0.3242 0.0000 0.3242 0.0059 0.3301 0.1353 2528.96 256.41 3157.63
PERIMETER_BOT_ZN_4 0.2814 0.0000 0.2814 0.0039 0.2853 0.0872 1549.83 245.99 4147.18
PERIMETER_MID_ZN_3 1.5616 0.0000 1.5616 0.0138 1.5754 1.3533 2041.52 796.27 3105.21
PERIMETER_MID_ZN_2 1.5639 0.0000 1.5639 0.0098 1.5737 0.8721 1733.07 954.72 2346.21
PERIMETER_MID_ZN_1 3.0475 0.0000 3.0475 0.0138 3.0613 1.3533 1683.84 1062.58 3196.58
PERIMETER_MID_ZN_4 1.7804 0.0000 1.7804 0.0092 1.7896 0.8721 1869.19 878.40 3195.41
PERIMETER_TOP_ZN_3 0.1530 0.0000 0.1530 0.0172 0.1702 0.1353 1753.38 1457.62 2732.00
PERIMETER_TOP_ZN_2 0.1672 0.0000 0.1672 0.0115 0.1787 0.0872 1592.59 708.94 3641.47
PERIMETER_TOP_ZN_1 0.2913 0.0000 0.2913 0.0172 0.3085 0.1353 1555.52 1585.50 2801.98
PERIMETER_TOP_ZN_4 0.1743 0.0000 0.1743 0.0115 0.1857 0.0872 1686.70 1458.96 2797.34
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 12.9713 0.0000 12.9713 0.0000 12.9713 0.3384 1.00 7.17 5934.83
Total Facility 227.4755 0.0000 227.4755 0.5438 228.0193 158.4706 3727.98 4369.47 5941.94


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 84432859.98 0.00 84432859.98 48026705.38 3649.02 7.22 5103.77 295.39
VAV_MID WITH REHEAT 0.64E+09 0.00 0.64E+09 0.48E+09 3971.08 9.57 4779.35 117.83
VAV_TOP WITH REHEAT 60703893.23 0.00 60703893.23 48026705.38 4090.59 4.66 4664.75 216.32
CAV_BAS 67056496.09 0.00 67056496.09 37848132.68 3980.16 3.58 4776.26 221.61
AIRLOOP DATACENTER BASEMENT 0.56E+09 0.00 0.56E+09 10671554.30 2.50 0.00 8757.50 2815.50
AIRLOOP DATACENTER BOT 346745.77 0.00 346745.77 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3467457.73 0.00 3467457.73 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 346745.77 0.00 346745.77 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.8113 0.0000 3.8113 1.5229 1095.32 5.45 4842.23
VAV_MID WITH REHEAT 29.3877 0.0000 29.3877 15.2292 1235.41 9.15 4698.44
VAV_TOP WITH REHEAT 2.7902 0.0000 2.7902 1.5229 1331.11 4.01 4607.88
CAV_BAS 3.0601 0.0000 3.0601 1.2002 1305.57 0.64 4636.80
AIRLOOP DATACENTER BASEMENT 18.4110 0.0000 18.4110 0.3384 1.00 0.00 5942.00
AIRLOOP DATACENTER BOT 0.0162 0.0000 0.0162 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1621 0.0000 0.1621 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0162 0.0000 0.0162 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 646.16 3520.54 0.00 0.00 0.00 1030.87 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 183.69 3171.44 0.00 0.00 0.00 1595.63 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 12.85 2730.30 0.00 0.00 0.00 2286.56 0.00 0.00 0.00
CAV_BAS 0.00 208.25 4670.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 7.17 8750.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.8931 5.6828 0.0000 0.0000 0.0000 2.3859 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 28.8991 43.7102 0.0000 0.0000 0.0000 22.5175 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.9911 4.5687 0.0000 0.0000 0.0000 2.2137 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.7055 4.0088 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4917 18.4384 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0222 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2219 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0222 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1519
Defaulted Fields 1187
Fields with Defaults 3885
Autosized Fields 333
Autosizable Fields 411
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 22203.15 292523.84 29-JAN-01:30 1551231.39 14-AUG-15:30
Electricity:Building 16399.35 215366.33 06-MAY-18:10 948093.84 01-DEC-15:30
Electricity:Zone:BASEMENT 540.44 14022.76 01-JAN-00:10 23631.68 02-JAN-08:10
Electricity:SpaceType:GENERAL 16399.35 215366.33 06-MAY-18:10 948093.84 01-DEC-15:30
InteriorLights:Electricity 1722.95 8110.17 01-JAN-09:50 169722.15 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 116.04 565.21 01-JAN-00:10 10174.14 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 1722.95 8110.17 01-JAN-09:50 169722.15 02-JAN-08:10
LightsWired:InteriorLights:Electricity 1722.95 8110.17 01-JAN-09:50 169722.15 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 116.04 565.21 01-JAN-00:10 10174.14 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 1722.95 8110.17 01-JAN-09:50 169722.15 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 393.83 4960.84 01-JAN-00:10 26343.72 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
Electricity:Zone:CORE_MID 3938.24 49608.19 01-JAN-00:10 263436.56 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1042.12 5076.02 01-JAN-00:10 91370.93 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1042.12 5076.02 01-JAN-00:10 91370.93 02-JAN-08:10
Electricity:Zone:CORE_TOP 393.82 4960.82 01-JAN-00:10 26343.66 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 44.13 589.50 02-APR-17:10 3307.80 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 7.76 30.32 01-JAN-09:50 1147.25 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 7.76 30.32 01-JAN-09:50 1147.25 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 28.39 379.89 02-APR-17:10 2131.68 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.95 19.54 01-JAN-08:40 739.33 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.95 19.54 01-JAN-08:40 739.33 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 44.00 589.50 02-APR-17:10 3307.86 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 7.64 30.33 01-JAN-08:40 1147.28 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 7.64 30.33 01-JAN-08:40 1147.28 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 28.40 379.89 12-MAR-17:10 2131.67 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.97 19.54 01-JAN-09:50 739.33 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.97 19.54 01-JAN-09:50 739.33 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 441.14 5894.96 02-APR-17:10 33078.05 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 77.48 303.25 01-JAN-09:40 11472.53 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 77.48 303.25 01-JAN-09:40 11472.53 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 283.78 3798.93 02-APR-17:10 21316.76 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 49.43 195.42 01-JAN-08:40 7393.34 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 49.43 195.42 01-JAN-08:40 7393.34 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 439.97 5895.05 02-APR-17:10 33078.63 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 76.31 303.26 01-JAN-08:40 11472.78 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 76.31 303.26 01-JAN-08:40 11472.78 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 283.94 3798.91 12-MAR-17:10 21316.66 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 49.59 195.42 01-JAN-09:40 7393.34 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 49.59 195.42 01-JAN-09:40 7393.34 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 44.11 589.50 02-APR-17:10 3307.80 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 7.75 30.32 01-JAN-09:40 1147.25 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 7.75 30.32 01-JAN-09:40 1147.25 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 28.38 379.89 02-APR-17:10 2131.68 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.94 19.54 01-JAN-08:40 739.33 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.94 19.54 01-JAN-08:40 739.33 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 44.00 589.50 02-APR-17:10 3307.86 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 7.63 30.33 01-JAN-08:40 1147.28 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 7.63 30.33 01-JAN-08:40 1147.28 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 28.39 379.89 12-MAR-17:10 2131.67 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.96 19.54 01-JAN-09:40 739.33 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.96 19.54 01-JAN-09:40 739.33 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7527.71 95067.50 01-JAN-00:10 382501.19 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 32.85 159.37 01-JAN-00:10 2868.67 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 32.85 159.37 01-JAN-00:10 2868.67 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 155.56 1956.73 01-JAN-00:10 7940.74 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1555.56 19567.35 01-JAN-00:10 79407.42 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 16.76 81.29 01-JAN-00:10 1463.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 16.76 81.29 01-JAN-00:10 1463.20 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 155.56 1956.73 01-JAN-00:10 7940.74 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 617.73 3536.27 02-JAN-04:40 275820.95 13-JUN-16:00
HeatRejection:Electricity 238.82 126.42 10-JAN-08:00 68588.97 22-MAY-14:20
General:HeatRejection:Electricity 238.82 126.42 10-JAN-08:00 68588.97 22-MAY-14:20
ElectricityProduced:Facility 402.98 -0.00 08-FEB-07:50 84379.95 18-JUN-12:30
ElectricityProduced:Plant 402.98 -0.00 08-FEB-07:50 84379.95 18-JUN-12:30
Photovoltaic:ElectricityProduced 422.38 0.00 01-JAN-00:10 87843.49 18-JUN-12:30
PowerConversion:ElectricityProduced -19.40 -3463.54 18-JUN-12:30 0.00 01-JAN-00:10
Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
DCtoACInverter Ancillary:Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 3767.57 46030.53 29-JAN-01:30 361094.91 27-APR-15:00
ExteriorEquipment:Electricity 1203.69 17814.45 01-JAN-00:10 73700.64 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 54.36 979.82 01-JAN-00:10 3372.05 01-DEC-15:40
ElectricityPurchased:Facility 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
ElectricityPurchased:Plant 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
Cogeneration:ElectricityPurchased 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
General:Cogeneration:ElectricityPurchased 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
ElectricityNet:Plant 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
Cogeneration:ElectricityNet 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
General:Cogeneration:ElectricityNet 21800.17 231630.04 28-MAY-11:10 1501716.25 14-AUG-15:40
Fans:Electricity 2083.18 42015.25 02-JAN-22:20 254179.13 12-SEP-15:30
General:Fans:Electricity 2083.18 42015.25 02-JAN-22:20 254179.13 12-SEP-15:30
ExteriorLights:Electricity 269.16 0.00 01-JAN-08:20 31088.59 01-JAN-06:10
General:ExteriorLights:Electricity 269.16 0.00 01-JAN-08:20 31088.59 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1144.44 16803.04 01-JAN-00:10 70012.65 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 4.90 31.59 01-JAN-00:10 315.94 01-JAN-07:10
Cooling:Electricity 681.75 1420.64 04-JAN-07:40 283212.20 14-AUG-16:00
General:Cooling:Electricity 681.75 1420.64 04-JAN-07:40 283212.20 14-AUG-16:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 1125.48 0.00 17-JAN-11:30 100000.00 03-MAR-22:10
General:Humidifier:Electricity 1125.48 0.00 17-JAN-11:30 100000.00 03-MAR-22:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 201.71 3308.95 06-JAN-05:50 34641.16 21-JUL-17:20
General:Pumps:Electricity 201.71 3308.95 06-JAN-05:50 34641.16 21-JUL-17:20
WIRED_LTG_ELECTRICITY 48.41 0.00 01-JAN-00:10 4769.19 02-JAN-08:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1956.40 7280.88 29-APR-16:10 730805.15 10-JAN-07:10
NaturalGas:Plant 1956.40 7280.88 29-APR-16:10 730805.15 10-JAN-07:10
Heating:NaturalGas 1161.41 0.00 01-JAN-00:40 702189.62 10-JAN-07:10
Boiler:Heating:NaturalGas 1161.41 0.00 01-JAN-00:40 702189.62 10-JAN-07:10
WaterSystems:NaturalGas 794.99 7280.88 04-JAN-05:20 83758.20 15-FEB-12:50
Water Heater:WaterSystems:NaturalGas 794.99 7280.88 04-JAN-05:20 83758.20 15-FEB-12:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 3919.68 4046.72 04-JAN-07:40 1806307.00 14-AUG-15:40
PlantLoopCoolingDemand:HVAC 3919.68 4046.72 04-JAN-07:40 1806307.00 14-AUG-15:40
CoolingCoils:PlantLoopCoolingDemand 3919.68 4046.72 04-JAN-07:40 1806307.00 14-AUG-15:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 3525.69 0.00 29-JAN-01:30 0.00 21-JUL-16:20
Water:HVAC 418.68 0.00 17-JAN-11:30 0.00 08-MAR-05:10
Humidifier:Water 418.68 0.00 17-JAN-11:30 0.00 08-MAR-05:10
General:Humidifier:Water 418.68 0.00 17-JAN-11:30 0.00 08-MAR-05:10
MainsWater:Facility 3525.69 0.00 29-JAN-01:30 0.00 21-JUL-16:20
MainsWater:HVAC 418.68 0.00 17-JAN-11:30 0.00 08-MAR-05:10
Humidifier:MainsWater 418.68 0.00 17-JAN-11:30 0.00 08-MAR-05:10
General:Humidifier:MainsWater 418.68 0.00 17-JAN-11:30 0.00 08-MAR-05:10
Water:Plant 3107.01 0.00 01-JAN-00:10 0.00 21-JUL-16:20
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 3107.01 0.00 01-JAN-00:10 0.00 21-JUL-16:20
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 826.84 0.00 01-JAN-00:10 0.00 21-JUL-16:20
General:HeatRejection:Water 826.84 0.00 01-JAN-00:10 0.00 21-JUL-16:20
HeatRejection:MainsWater 826.84 0.00 01-JAN-00:10 0.00 21-JUL-16:20
General:HeatRejection:MainsWater 826.84 0.00 01-JAN-00:10 0.00 21-JUL-16:20


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 26244.41 96068.42 15-JAN-05:00 6985981.33 14-AUG-15:40
EnergyTransfer:Building 16368.49 88111.91 15-JAN-03:00 1473363.76 14-AUG-15:30
EnergyTransfer:Zone:BASEMENT 578.07 0.00 01-JAN-00:40 71508.83 10-OCT-05:10
Heating:EnergyTransfer 217.51 0.00 15-JAN-16:10 372164.54 26-DEC-06:10
Heating:EnergyTransfer:Zone:BASEMENT 1.73 0.00 01-JAN-00:40 13245.37 22-JUL-16:10
General:Heating:EnergyTransfer 217.51 0.00 15-JAN-16:10 372164.54 26-DEC-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 1.73 0.00 01-JAN-00:40 13245.37 22-JUL-16:10
Cooling:EnergyTransfer 16150.98 87499.14 15-JAN-06:00 1473363.76 14-AUG-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 576.34 0.00 01-JAN-00:10 71508.83 10-OCT-05:10
General:Cooling:EnergyTransfer 16150.98 87499.14 15-JAN-06:00 1473363.76 14-AUG-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 576.34 0.00 01-JAN-00:10 71508.83 10-OCT-05:10
EnergyTransfer:Zone:CORE_BOTTOM 523.64 0.00 01-JAN-00:10 48501.43 10-OCT-05:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 523.64 0.00 01-JAN-00:10 48501.43 10-OCT-05:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 523.64 0.00 01-JAN-00:10 48501.43 10-OCT-05:10
EnergyTransfer:Zone:CORE_MID 3539.70 0.00 01-JAN-00:10 375522.57 26-SEP-05:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 3539.70 0.00 01-JAN-00:10 375522.57 26-SEP-05:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 3539.70 0.00 01-JAN-00:10 375522.57 26-SEP-05:10
EnergyTransfer:Zone:CORE_TOP 295.01 0.00 01-JAN-00:40 58283.02 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 5.95 0.00 01-JAN-00:10 58283.02 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 5.95 0.00 01-JAN-00:10 58283.02 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 289.06 0.00 01-JAN-00:40 40885.60 13-JUN-16:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 289.06 0.00 01-JAN-00:40 40885.60 13-JUN-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 53.98 0.00 01-JAN-00:10 8541.22 10-JUL-14:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 933.61 11-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 933.61 11-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 53.98 0.00 01-JAN-00:10 8541.22 10-JUL-14:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 53.98 0.00 01-JAN-00:10 8541.22 10-JUL-14:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 50.20 0.00 01-JAN-00:10 13717.55 13-JUN-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.01 0.00 01-JAN-00:10 1083.44 10-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.01 0.00 01-JAN-00:10 1083.44 10-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 50.19 0.00 01-JAN-00:10 13717.55 13-JUN-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 50.19 0.00 01-JAN-00:10 13717.55 13-JUN-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 88.65 0.00 01-JAN-00:10 21362.83 11-SEP-12:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.03 0.00 01-JAN-00:10 3054.47 10-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.03 0.00 01-JAN-00:10 3054.47 10-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 88.61 0.00 01-JAN-00:10 21362.83 11-SEP-12:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 88.61 0.00 01-JAN-00:10 21362.83 11-SEP-12:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 80.24 0.00 01-JAN-00:10 17436.40 28-APR-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 80.24 0.00 01-JAN-00:10 17436.40 28-APR-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 80.24 0.00 01-JAN-00:10 17436.40 28-APR-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 371.43 0.00 01-JAN-00:10 89317.37 26-DEC-05:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 30.81 0.00 01-JAN-00:10 89317.37 26-DEC-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 30.81 0.00 01-JAN-00:10 89317.37 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 340.62 0.00 01-JAN-00:10 72741.61 13-JUN-15:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 340.62 0.00 01-JAN-00:10 72741.61 13-JUN-15:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 413.62 0.00 01-JAN-00:10 144216.85 13-JUN-08:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 18.18 0.00 01-JAN-00:10 71308.86 26-DEC-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 18.18 0.00 01-JAN-00:10 71308.86 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 395.44 0.00 01-JAN-00:10 144216.85 13-JUN-08:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 395.44 0.00 01-JAN-00:10 144216.85 13-JUN-08:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 792.13 0.00 01-JAN-00:10 231388.44 11-SEP-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 16.50 0.00 01-JAN-00:10 81232.01 26-DEC-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 16.50 0.00 01-JAN-00:10 81232.01 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 775.63 0.00 01-JAN-00:10 231388.44 11-SEP-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 775.63 0.00 01-JAN-00:10 231388.44 11-SEP-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 453.12 0.00 01-JAN-00:10 165483.88 13-JUN-17:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 9.84 0.00 01-JAN-00:10 53573.56 26-DEC-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 9.84 0.00 01-JAN-00:10 53573.56 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 443.28 0.00 01-JAN-00:10 165483.88 13-JUN-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 443.28 0.00 01-JAN-00:10 165483.88 13-JUN-17:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 42.42 0.00 01-JAN-00:40 11048.51 26-DEC-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 15.01 0.00 01-JAN-00:40 11048.51 26-DEC-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 15.01 0.00 01-JAN-00:40 11048.51 26-DEC-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 27.40 0.00 01-JAN-00:20 8129.11 13-JUN-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 27.40 0.00 01-JAN-00:20 8129.11 13-JUN-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 45.00 0.00 01-JAN-00:40 14317.54 13-JUN-08:50
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 8.56 0.00 01-JAN-00:40 12446.87 26-DEC-05:40
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 8.56 0.00 01-JAN-00:40 12446.87 26-DEC-05:40
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 36.45 0.00 01-JAN-00:20 14317.54 13-JUN-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 36.45 0.00 01-JAN-00:20 14317.54 13-JUN-08:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 76.73 0.00 01-JAN-00:40 23335.19 11-SEP-13:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 9.79 0.00 01-JAN-00:40 17668.17 26-DEC-05:40
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 9.79 0.00 01-JAN-00:40 17668.17 26-DEC-05:40
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 66.94 0.00 01-JAN-00:20 23335.19 11-SEP-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 66.94 0.00 01-JAN-00:20 23335.19 11-SEP-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 45.10 0.00 01-JAN-00:40 17174.78 13-JUN-17:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 5.41 0.00 01-JAN-00:40 10711.29 26-DEC-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 5.41 0.00 01-JAN-00:40 10711.29 26-DEC-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 39.69 0.00 01-JAN-00:20 17174.78 13-JUN-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 39.69 0.00 01-JAN-00:20 17174.78 13-JUN-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 42.69 0.00 01-JAN-00:10 7443.41 24-JUL-15:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.17 0.00 01-JAN-00:10 3756.63 17-DEC-12:50
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.17 0.00 01-JAN-00:10 3756.63 17-DEC-12:50
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 41.53 0.00 01-JAN-00:10 7443.41 24-JUL-15:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 41.53 0.00 01-JAN-00:10 7443.41 24-JUL-15:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 260.88 0.00 01-JAN-00:10 51180.92 24-JUL-15:40
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 64.08 0.00 01-JAN-00:10 46034.08 18-DEC-13:40
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 64.08 0.00 01-JAN-00:10 46034.08 18-DEC-13:40
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 196.80 0.00 01-JAN-00:10 51180.92 24-JUL-15:40
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 196.80 0.00 01-JAN-00:10 51180.92 24-JUL-15:40
EnergyTransfer:Zone:TOPFLOOR_PLENUM 60.23 0.00 01-JAN-00:40 18547.31 26-DEC-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 29.22 0.00 01-JAN-00:40 18547.31 26-DEC-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 29.22 0.00 01-JAN-00:40 18547.31 26-DEC-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 31.01 0.00 01-JAN-00:10 15728.85 13-JUN-14:20
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 31.01 0.00 01-JAN-00:10 15728.85 13-JUN-14:20
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.79 793.54 11-JAN-08:00 8267.81 13-AUG-18:10
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.79 793.54 11-JAN-08:00 8267.81 13-AUG-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.79 793.54 11-JAN-08:00 8267.81 13-AUG-18:10
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1167.34 8.02 05-JAN-03:40 78749.82 30-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.52 0.00 01-JAN-15:00 4230.39 02-JAN-05:00
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.52 0.00 01-JAN-15:00 4230.39 02-JAN-05:00
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1166.82 0.00 01-JAN-00:10 78749.82 30-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1166.82 0.00 01-JAN-00:10 78749.82 30-APR-18:10
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 104.26 0.11 11-JAN-21:30 7992.70 30-APR-18:00
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.69 0.00 02-JAN-15:20 580.91 08-JAN-18:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.69 0.00 02-JAN-15:20 580.91 08-JAN-18:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 103.57 0.00 01-JAN-00:10 7992.70 30-APR-18:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 103.57 0.00 01-JAN-00:10 7992.70 30-APR-18:00
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7147.24 86580.27 15-JAN-06:00 367075.99 28-AUG-16:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7147.24 86580.27 15-JAN-06:00 367075.99 28-AUG-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7147.24 86580.27 15-JAN-06:00 367075.99 28-AUG-16:00
PlantLoopHeatingDemand:Facility 1530.55 0.00 01-JAN-00:40 636567.79 10-JAN-08:00
PlantLoopHeatingDemand:Plant 442.36 0.00 01-JAN-00:10 51546.91 15-FEB-13:00
WaterSystems:PlantLoopHeatingDemand 442.36 0.00 01-JAN-00:10 51546.91 15-FEB-13:00
General:WaterSystems:PlantLoopHeatingDemand 442.36 0.00 01-JAN-00:10 51546.91 15-FEB-13:00
EnergyTransfer:HVAC 4503.31 4198.10 01-JAN-06:00 1676982.64 14-AUG-15:40
HeatingCoils:EnergyTransfer 1088.19 0.00 01-JAN-00:40 619597.95 10-JAN-08:00
PlantLoopHeatingDemand:HVAC 1088.19 0.00 01-JAN-00:40 619597.95 10-JAN-08:00
HeatingCoils:PlantLoopHeatingDemand 1088.19 0.00 01-JAN-00:40 619597.95 10-JAN-08:00
CoolingCoils:EnergyTransfer 3415.13 2626.08 04-JAN-07:40 1676982.64 14-AUG-15:40
EnergyTransfer:Plant 5372.61 0.00 01-JAN-00:40 4157352.47 13-JUN-16:00
LoopToLoop:EnergyTransfer 1213.88 0.00 01-JAN-00:10 1314633.95 13-JUN-16:00
WaterSystems:EnergyTransfer 442.36 0.00 01-JAN-00:10 51546.91 15-FEB-13:00
WaterUse:WaterSystems:EnergyTransfer 442.36 0.00 01-JAN-00:10 51546.91 15-FEB-13:00
Boilers:EnergyTransfer 1086.74 0.00 01-JAN-00:40 634376.04 10-JAN-07:10
Chillers:EnergyTransfer 1226.21 0.00 01-JAN-00:10 1315966.87 13-JUN-16:00
HeatRejection:EnergyTransfer 1403.41 0.00 01-JAN-00:10 1490127.86 13-JUN-16:00
General:HeatRejection:EnergyTransfer 1403.41 0.00 01-JAN-00:10 1490127.86 13-JUN-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 1.730 -576.342 0.000 0.000 92.761 116.039 424.397 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 -58.586
CORE_BOTTOM 0.000 0.000 0.000 -523.643 0.000 0.000 83.428 104.212 289.614 0.000 0.000 0.000 46.390 0.000 0.000 0.000 0.000 -0.002
CORE_MID 0.000 0.000 0.000 -3539.694 0.000 0.000 845.558 1042.115 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1244.107
CORE_TOP 0.000 0.000 5.950 -289.061 0.000 0.000 88.644 104.212 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -199.356
PERIMETER_BOT_ZN_3 0.000 0.000 0.002 -53.981 0.000 0.000 10.734 7.762 36.365 22.967 0.000 0.002 48.045 0.000 -67.595 0.000 -4.302 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.007 -50.193 0.000 0.000 6.918 4.950 23.435 52.578 0.000 0.001 7.726 0.000 -42.564 0.000 -2.859 -0.001
PERIMETER_BOT_ZN_1 0.000 0.000 0.034 -88.611 0.000 0.000 10.740 7.639 36.366 106.016 0.000 0.002 0.001 0.000 -64.264 0.000 -4.310 -3.612
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -80.243 0.000 0.000 6.766 4.966 23.435 50.214 0.000 0.001 47.234 0.000 -49.206 0.000 -3.167 0.000
PERIMETER_MID_ZN_3 0.000 0.000 30.814 -340.618 0.000 0.000 113.509 77.483 363.654 241.649 0.000 0.036 205.379 0.000 -601.977 0.000 -89.928 0.000
PERIMETER_MID_ZN_2 0.000 0.000 18.182 -395.445 0.000 0.000 52.674 49.430 234.352 526.823 0.000 0.022 0.020 0.000 -393.713 0.000 -62.330 -29.996
PERIMETER_MID_ZN_1 0.000 0.000 16.502 -775.625 0.000 0.000 109.816 76.314 363.660 1060.246 0.000 0.034 0.005 0.000 -614.600 0.000 -95.873 -140.473
PERIMETER_MID_ZN_4 0.000 0.000 9.843 -443.274 0.000 0.000 71.708 49.588 234.351 513.949 0.000 0.021 49.221 0.000 -421.229 0.000 -64.177 -0.007
PERIMETER_TOP_ZN_3 0.000 0.000 15.013 -27.403 0.000 0.000 11.634 7.748 36.365 25.137 0.000 0.004 0.000 0.000 -55.512 0.000 -10.383 -2.602
PERIMETER_TOP_ZN_2 0.000 0.000 8.557 -36.447 0.000 0.000 7.331 4.943 23.435 53.503 0.000 0.003 0.000 0.000 -36.389 0.000 -7.220 -17.715
PERIMETER_TOP_ZN_1 0.000 0.000 9.787 -66.942 0.000 0.000 11.249 7.631 36.366 107.089 0.000 0.004 0.003 0.000 -56.981 0.000 -11.133 -37.070
PERIMETER_TOP_ZN_4 0.000 0.000 5.406 -39.691 0.000 0.000 7.342 4.958 23.435 51.849 0.000 0.002 0.000 0.000 -39.408 0.000 -7.521 -6.372
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -136.790 0.000 0.000 0.950 1.676 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -19.717
DATACENTER_MID_ZN_6 0.000 0.000 0.522 -1166.814 0.000 0.000 9.502 16.758 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -398.774
DATACENTER_TOP_ZN_6 0.000 0.000 0.694 -103.569 0.000 0.000 0.953 1.676 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -53.634
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7147.233 0.000 0.000 20.565 32.854 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -401.043
GROUNDFLOOR_PLENUM 1.166 -41.528 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.002 49.507 0.000 0.000 0.000 -9.147 0.000
MIDFLOOR_PLENUM 64.086 -196.798 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 288.147 0.000 0.000 0.000 -155.482 -0.001
TOPFLOOR_PLENUM 29.220 -31.006 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 18.187 0.000 0.000 0.000 -16.404 -0.001
Total Facility 94.472 -269.332 123.044 -15881.617 0.000 0.000 1562.780 1722.953 14676.396 2812.020 0.000 0.184 759.868 0.000 -2443.438 0.000 -544.237 -2613.069


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 07-AUG-04:11 0.00 0.00 0.00 -99839.46 0.00 0.00 0.00 598.35 13457.54 0.00 0.00 0.00 85783.56 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 10-OCT-04:12 0.00 0.00 0.00 -84926.93 0.00 0.00 0.00 537.36 5937.65 0.00 0.00 0.00 78451.93 0.00 -0.00 0.00 0.00 0.00
CORE_MID 16-JUN-05:02 0.00 0.00 0.00 -719116.22 0.00 0.00 8384.40 5373.60 76473.61 0.00 0.00 0.00 628884.61 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 24-JUL-04:12 0.00 0.00 0.00 -67069.86 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 60594.88 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 25-JUN-16:21 0.00 0.00 0.00 -11124.01 0.00 0.00 45.79 30.32 720.18 3698.15 0.00 0.00 6676.86 0.00 -0.00 0.00 -47.30 0.00
PERIMETER_BOT_ZN_2 23-JUL-08:41 0.00 0.00 0.00 -24211.85 0.00 0.00 19.87 19.54 464.11 18768.36 0.00 0.00 5071.31 0.00 -0.00 0.00 -131.35 0.00
PERIMETER_BOT_ZN_1 30-APR-12:21 0.00 0.00 0.00 -33709.88 0.00 0.00 30.16 30.33 720.19 28777.83 0.00 0.00 4284.84 0.00 -0.00 0.00 -133.46 0.00
PERIMETER_BOT_ZN_4 11-JUN-16:11 0.00 0.00 0.00 -30568.35 0.00 0.00 17.31 19.54 464.11 19680.19 0.00 0.00 10578.77 0.00 -0.00 0.00 -191.57 0.00
PERIMETER_MID_ZN_3 13-JUN-15:10 0.00 0.00 0.00 -72741.45 0.00 0.00 11142.01 5458.63 21605.52 53218.58 0.00 400.43 0.00 0.00 -0.00 0.00 0.00 -19083.72
PERIMETER_MID_ZN_2 23-JUL-08:31 0.00 0.00 0.00 -261429.70 0.00 0.00 185.29 195.42 4641.14 191045.74 0.00 0.00 68560.78 0.00 -0.00 0.00 -3198.67 0.00
PERIMETER_MID_ZN_1 06-AUG-13:52 0.00 0.00 0.00 -334001.79 0.00 0.00 336.14 303.26 7201.95 191525.10 0.00 0.00 140047.25 0.00 -0.00 0.00 -5411.90 0.00
PERIMETER_MID_ZN_4 09-JUL-17:21 0.00 0.00 0.00 -288948.01 0.00 0.00 0.00 195.42 3603.49 202330.20 0.00 0.00 85990.02 0.00 -0.00 0.00 -3171.11 0.00
PERIMETER_TOP_ZN_3 13-JUN-15:00 0.00 0.00 0.00 -8130.32 0.00 0.00 1114.33 545.86 2160.55 5370.08 0.00 46.40 0.00 0.00 -0.00 0.00 0.00 -1106.91
PERIMETER_TOP_ZN_2 30-APR-09:31 0.00 0.00 0.00 -24316.31 0.00 0.00 21.02 19.54 464.11 16130.70 0.00 0.00 8164.99 0.00 -0.00 0.00 -484.06 0.00
PERIMETER_TOP_ZN_1 30-APR-12:11 0.00 0.00 0.00 -37216.64 0.00 0.00 29.65 30.33 720.19 28607.99 0.00 0.00 8228.29 0.00 -0.00 0.00 -399.81 0.00
PERIMETER_TOP_ZN_4 09-JUL-17:31 0.00 0.00 0.00 -30126.19 0.00 0.00 0.00 19.54 360.35 19171.49 0.00 0.00 10950.04 0.00 -0.00 0.00 -375.23 0.00
DATACENTER_BOT_ZN_6 30-APR-19:12 0.00 0.00 0.00 -8281.70 0.00 0.00 0.00 8.13 7794.42 0.00 0.00 0.00 479.15 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 30-APR-18:02 0.00 0.00 0.00 -78771.05 0.00 0.00 0.00 81.29 77944.22 0.00 0.00 0.00 745.54 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 30-APR-17:53 0.00 0.00 0.00 -7997.64 0.00 0.00 0.00 8.13 7794.42 0.00 0.00 0.00 195.09 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 28-AUG-16:00 0.00 0.00 0.00 -367078.42 0.00 0.00 2182.91 2868.67 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17605.69
GROUNDFLOOR_PLENUM 26-JUN-05:15 0.00 -8905.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9054.13 0.00 -0.00 0.00 -148.65 0.00
MIDFLOOR_PLENUM 30-DEC-05:01 0.00 -74341.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93830.53 0.00 -0.00 0.00 -19489.38 0.00
TOPFLOOR_PLENUM 13-JUN-14:20 0.00 -15728.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15743.67 0.00 -0.00 0.00 -14.77 0.00
Total Facility 14-AUG-05:02 0.00 39185.97 0.00 -1549645.13 0.00 0.00 16109.34 10223.35 616289.16 0.00 0.00 0.00 987867.32 0.00 -120030.01 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-JUL-16:01 0.00 0.00 14498.99 0.00 0.00 0.00 520.13 565.21 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -29041.88
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 02-JAN-04:01 0.00 0.00 64831.38 0.00 0.00 0.00 0.00 507.60 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -71276.60
PERIMETER_BOT_ZN_3 11-JAN-06:01 0.00 0.00 5547.20 0.00 0.00 0.00 141.64 67.47 960.25 0.00 0.00 0.00 0.00 0.00 -4865.89 0.00 -107.79 -1742.88
PERIMETER_BOT_ZN_2 10-JAN-06:01 0.00 0.00 4067.96 0.00 0.00 0.00 92.34 43.48 618.82 0.00 0.00 0.00 0.00 0.00 -3548.03 0.00 -93.50 -1181.06
PERIMETER_BOT_ZN_1 10-JAN-06:01 0.00 0.00 8763.48 0.00 0.00 0.00 146.00 67.47 960.26 0.00 0.00 0.00 0.00 0.00 -5132.12 0.00 -138.42 -4666.67
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 26-DEC-05:11 0.00 0.00 95854.66 0.00 0.00 0.00 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 -33517.21 0.00 -11211.18 -59256.58
PERIMETER_MID_ZN_2 26-DEC-05:11 0.00 0.00 134245.16 0.00 0.00 0.00 0.00 434.81 4804.68 0.00 0.00 0.00 0.00 0.00 -22438.49 0.00 -7657.21 -109388.94
PERIMETER_MID_ZN_1 26-DEC-05:11 0.00 0.00 185872.89 0.00 0.00 0.00 0.00 674.72 7455.72 0.00 0.00 0.00 0.00 0.00 -36331.10 0.00 -12103.25 -145568.99
PERIMETER_MID_ZN_4 26-DEC-05:11 0.00 0.00 122376.88 0.00 0.00 0.00 0.00 434.81 4804.65 0.00 0.00 0.00 0.00 0.00 -24100.32 0.00 -8041.23 -95474.79
PERIMETER_TOP_ZN_3 26-DEC-05:21 0.00 0.00 11882.52 0.00 0.00 0.00 0.00 67.47 745.56 0.00 0.00 0.00 0.00 0.00 -2838.40 0.00 -1187.56 -8669.59
PERIMETER_TOP_ZN_2 26-DEC-05:21 0.00 0.00 17220.88 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -1894.71 0.00 -818.21 -15031.91
PERIMETER_TOP_ZN_1 26-DEC-05:21 0.00 0.00 25418.11 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -2964.22 0.00 -1246.40 -22020.53
PERIMETER_TOP_ZN_4 26-DEC-05:21 0.00 0.00 17251.52 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -2041.51 0.00 -856.61 -14877.34
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 02-JAN-04:55 0.00 0.00 4230.39 0.00 0.00 0.00 0.00 81.29 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -23797.74
DATACENTER_TOP_ZN_6 08-JAN-18:10 0.00 0.00 580.91 0.00 0.00 0.00 0.00 8.13 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2537.65
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 30-APR-14:21 12584.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -71.81 -12512.22
MIDFLOOR_PLENUM 30-APR-14:32 124698.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -874.09 -123824.03
TOPFLOOR_PLENUM 26-DEC-06:12 22249.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -508.46 -21740.75
Total Facility 18-DEC-05:01 -768423.44 727671.39 647967.41 -727671.39 0.00 0.00 0.00 18857.47 587299.42 0.00 0.00 0.00 0.00 0.00 -153097.15 0.00 -47554.82 -285048.88



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.4762 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.6144 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 100.6071 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 78.5230 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.0018 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.8528 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 4.8384 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 4.8384 0.2480 1.0000 Not calculated 1.2002 0.2480    
AIRLOOP DATACENTER BASEMENT 21.4384 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.4385 0.0158 1.0000 Not calculated 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4988 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4988 0.0313 1.0000 Not calculated 0.0156 0.0313    
AIRLOOP DATACENTER MID 4.7923 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7923 0.0326 1.0000 Not calculated 0.1563 0.0326    
AIRLOOP DATACENTER TOP 0.4859 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4859 0.0322 1.0000 Not calculated 0.0156 0.0322    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.2381 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2833 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 50.3035 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.8138 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.0009 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2825 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 4.8384 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 4.8384 1.0000 1.0000 Not calculated 1.2002 0.2480    
AIRLOOP DATACENTER BASEMENT 21.4384 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.4384 1.0000 1.0000 Not calculated 0.3384 0.0158    
AIRLOOP DATACENTER BOT 0.4988 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4988 1.0000 1.0000 Not calculated 0.0156 0.0313    
AIRLOOP DATACENTER MID 4.7923 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7923 1.0000 1.0000 Not calculated 0.1563 0.0326    
AIRLOOP DATACENTER TOP 0.4859 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4859 1.0000 1.0000 Not calculated 0.0156 0.0322    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.8384 4.8384 4.8384 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2159 5.2159 1.6169 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 48.6409 48.6409 16.1488 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.5896 4.5896 1.6155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7719 0.7719 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2409 1.2409 0.1303 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7348 1.7348 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5126 1.5126 0.1301 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.9536 6.9536 2.0305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.0493 13.0493 1.3049 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 18.0626 18.0626 2.0230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.9006 13.9006 1.3067 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7823 0.7823 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2880 1.2880 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8912 1.8912 0.2024 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4506 1.4506 0.1306 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4988 0.4988 0.4988 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7923 4.7923 4.7923 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4859 0.4859 0.4859 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.4384 21.4384 21.4384 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.4762 8.6144 10.4762 2.2833 0.0000 1.0000
VAV_MID WITH REHEAT 100.6071 78.5230 100.6071 22.8138 0.0000 1.0000
VAV_TOP WITH REHEAT 10.0018 8.8528 10.0018 2.2825 0.0000 1.0000
CAV_BAS 4.8384 4.8384 4.8384 4.8384 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.4384 21.4385 21.4384 21.4384 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4988 0.4988 0.4988 0.4988 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7923 4.7923 4.7923 4.7923 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4859 0.4859 0.4859 0.4859 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.8384 4.8384 4.8384 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6080 2.6080 1.6169 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 24.3205 24.3205 16.1488 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2948 2.2948 1.6155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3860 0.3860 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6205 0.6205 0.1303 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8674 0.8674 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7563 0.7563 0.1301 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.4768 3.4768 2.0305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.5247 6.5247 1.3049 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.0313 9.0313 2.0230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.9503 6.9503 1.3067 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3912 0.3912 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6440 0.6440 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9456 0.9456 0.2024 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7253 0.7253 0.1306 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4988 0.4988 0.4988 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7923 4.7923 4.7923 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4859 0.4859 0.4859 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.4384 21.4384 21.4384 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.2381 2.2833 2.2833 2.2833 0.0000 1.0000
VAV_MID WITH REHEAT 50.3035 22.8138 22.8138 22.8138 0.0000 1.0000
VAV_TOP WITH REHEAT 5.0009 2.2825 2.2825 2.2825 0.0000 1.0000
CAV_BAS 4.8384 4.8384 4.8384 4.8384 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.4384 21.4384 21.4384 21.4384 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4988 0.4988 0.4988 0.4988 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7923 4.7923 4.7923 4.7923 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4859 0.4859 0.4859 0.4859 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 19.67
Number of hours cooling loads not met 146.83
Number of hours not met 166.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1161.41 702189.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 681.75 283212.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 1722.95 169722.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 269.16 31088.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.36 3372.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1144.44 70012.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 4.90 315.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2083.18 254179.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 201.71 34641.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 238.82 68588.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1125.48 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 794.99 83758.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 22203.15
Natural Gas 0.00 1956.40
Additional 0.00 0.00
Total 14676.40 24159.55


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 422.38
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 37.20
Space Heating 0.00
Space Cooling 14.72
Fans (All) 44.97
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 479.34
Subtotal 479.34


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 25.07
Service Water Heating 17.16
Miscellaneous (All) 42.24
Subtotal 42.24


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.13
Space Heating 4.81
Space Cooling 2.82
Fans (All) 8.62
Service Water Heating 3.29
Receptacle Equipment 60.75
Miscellaneous 12.58


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
PV_SCH 8760. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2069. 8760.
LTG_SCH_DATACENTER 1840. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 782. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8538.67 221.33 0.00 0.00 0.00
CORE_BOTTOM 8750.67 9.33 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8759.83 0.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8724.67 35.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8720.33 39.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8510.50 249.50 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8723.50 36.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8719.33 40.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8710.50 49.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8728.83 31.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8723.67 36.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8711.33 48.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7949.50 810.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7908.50 851.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7880.67 879.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7650.50 1109.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8751.83 8.17 0.00 0.00 0.00
Min 7650.50 0.00 0.00 0.00 0.00
Max 8760.00 1109.50 0.00 0.00 0.00
Average 8566.21 193.79 0.00 0.00 0.00
Sum 197022.83 4457.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368220.50 395.50 0.00 0.00 0.00
CORE_BOTTOM 330758.00 55.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1675.00 593.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1645.33 622.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1626.67 641.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 87415.33 15979.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368220.50 15979.67 0.00 0.00 0.00
Average 79539.82 795.09 0.00 0.00 0.00
Sum 1829415.83 18287.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8481.67 278.33 0.00 0.00 0.00
CORE_BOTTOM 8638.50 121.50 0.00 0.00 0.00
CORE_MID 8711.00 49.00 0.00 0.00 0.00
CORE_TOP 8752.67 7.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8754.33 5.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8721.17 38.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8712.00 48.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8540.00 220.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8759.67 0.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8723.00 37.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8716.00 44.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8707.00 53.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8755.00 5.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8725.83 34.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8719.33 40.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8710.83 49.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8612.00 148.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8598.00 162.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8593.67 166.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8141.83 618.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8750.50 9.50 0.00 0.00 0.00
MIDFLOOR_PLENUM 8759.50 0.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8724.83 35.17 0.00 0.00 0.00
Min 8141.83 0.33 0.00 0.00 0.00
Max 8759.67 618.17 0.00 0.00 0.00
Average 8665.58 94.42 0.00 0.00 0.00
Sum 199308.33 2171.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 367921.83 694.17 0.00 0.00 0.00
CORE_BOTTOM 330640.00 173.00 0.00 0.00 0.00
CORE_MID 330718.00 95.00 0.00 0.00 0.00
CORE_TOP 330805.00 8.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2148.67 119.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2139.00 129.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2136.00 132.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 94310.83 9084.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367921.83 9084.17 0.00 0.00 0.00
Average 79881.23 453.68 0.00 0.00 0.00
Sum 1837268.33 10434.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.422973E+11 96435.44 02-JAN-04:01 1.17 0.70 0.565073E+10 7499.20 13-JAN-10:09 2.17 1.78
February 0.389605E+11 96866.38 21-FEB-05:11 5.37 4.72 0.513172E+10 7499.20 17-FEB-10:20 5.37 4.72
March 0.474661E+11 95096.09 13-MAR-04:11 2.17 1.63 0.612836E+10 7499.16 31-MAR-13:20 9.00 5.71
April 0.486581E+11 96917.10 24-APR-04:12 7.00 5.73 0.544759E+10 7499.34 14-APR-13:20 7.00 5.73
May 0.486179E+11 95902.88 01-MAY-04:12 4.67 3.91 0.589797E+10 7499.18 16-MAY-13:20 9.67 8.29
June 0.507352E+11 96171.14 12-JUN-04:12 8.33 8.33 0.587888E+10 7499.34 08-JUN-13:20 8.33 8.33
July 0.521793E+11 97264.71 31-JUL-04:12 8.33 5.83 0.546978E+10 7528.78 10-JUL-09:30 8.33 5.83
August 0.575263E+11 99844.72 07-AUG-04:11 10.67 9.54 0.613466E+10 7499.32 08-AUG-13:09 17.83 16.43
September 0.491048E+11 96787.15 25-SEP-04:12 11.00 9.41 0.544847E+10 7499.36 06-SEP-09:20 11.00 9.41
October 0.490762E+11 96189.94 10-OCT-04:12 10.33 10.33 0.566572E+10 7499.30 17-OCT-09:20 11.67 11.31
November 0.469000E+11 96509.53 06-NOV-05:11 8.00 7.45 0.560932E+10 7499.14 10-NOV-10:09 11.00 9.41
December 0.448211E+11 97692.12 26-DEC-05:21 1.95 0.29 0.546283E+10 7499.21 20-DEC-10:09 1.95 0.29
                     
Annual Sum or Average 0.576343E+12         0.679260E+11        
Minimum of Months 0.389605E+11 95096.09   1.17 0.29 0.513172E+10 7499.14   1.95 0.29
Maximum of Months 0.575263E+11 99844.72   11.00 10.33 0.613466E+10 7528.78   17.83 16.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.325483E+11 80681.54 02-JAN-04:01 1.17 0.70 0.506086E+10 6734.80 20-JAN-10:20 4.67 4.23
February 0.324098E+11 78089.84 21-FEB-05:11 5.37 4.72 0.459911E+10 6734.81 21-FEB-10:09 8.17 7.45
March 0.423690E+11 79692.41 20-MAR-04:12 5.33 4.89 0.549988E+10 6734.78 06-MAR-10:20 5.33 4.89
April 0.491999E+11 84028.96 24-APR-04:12 7.00 5.73 0.488352E+10 6735.05 14-APR-13:00 7.00 5.73
May 0.441335E+11 83331.93 01-MAY-04:12 4.67 3.91 0.528474E+10 6734.80 04-MAY-09:20 9.00 8.10
June 0.490143E+11 81775.52 26-JUN-04:12 12.67 11.59 0.527025E+10 6734.90 20-JUN-09:09 12.67 11.59
July 0.531753E+11 83997.23 05-JUL-04:12 7.67 6.81 0.489755E+10 6734.83 03-JUL-09:09 7.67 6.81
August 0.596032E+11 83238.41 28-AUG-04:13 9.00 8.43 0.549877E+10 6735.64 14-AUG-13:00 9.00 8.43
September 0.435970E+11 82593.49 05-SEP-04:12 6.67 6.14 0.487879E+10 6734.95 06-SEP-09:09 13.33 11.45
October 0.407490E+11 84927.16 10-OCT-04:12 10.33 10.33 0.507935E+10 6734.92 17-OCT-09:09 12.33 11.88
November 0.391695E+11 83974.69 13-NOV-05:11 3.33 3.18 0.502911E+10 6734.79 10-NOV-10:09 3.33 3.18
December 0.376733E+11 81122.34 26-DEC-05:11 1.97 0.30 0.489899E+10 6734.82 20-DEC-10:09 1.97 0.30
                     
Annual Sum or Average 0.523642E+12         0.608809E+11        
Minimum of Months 0.324098E+11 78089.84   1.17 0.30 0.459911E+10 6734.78   1.97 0.30
Maximum of Months 0.596032E+11 84927.16   12.67 11.59 0.549988E+10 6735.64   13.33 11.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.218142E+11 38778.29 26-JAN-06:02 5.00 4.51 0.482413E+10 6734.78 20-JAN-10:20 5.00 4.51
February 0.209319E+11 30010.92 10-FEB-06:02 5.00 4.51 0.446052E+10 6734.76 09-FEB-10:09 5.00 4.51
March 0.262100E+11 64423.62 24-MAR-05:02 4.00 3.12 0.540182E+10 6734.76 31-MAR-09:20 6.33 3.98
April 0.312655E+11 71076.82 28-APR-05:02 6.17 4.37 0.485508E+10 6734.84 25-APR-13:09 6.17 4.37
May 0.341812E+11 71861.56 24-MAY-05:02 8.42 8.35 0.525928E+10 6734.80 04-MAY-09:20 8.42 8.35
June 0.369936E+11 71914.10 16-JUN-05:02 10.33 9.14 0.525786E+10 6734.87 09-JUN-13:00 10.33 9.14
July 0.373057E+11 71168.46 25-JUL-04:12 13.00 12.63 0.488427E+10 6734.81 13-JUL-13:20 13.00 12.63
August 0.402543E+11 71670.30 23-AUG-05:02 9.33 7.24 0.548740E+10 6734.82 23-AUG-09:20 16.33 12.16
September 0.343402E+11 71729.23 26-SEP-05:02 8.97 7.42 0.486068E+10 6734.86 06-SEP-09:09 8.97 7.42
October 0.275123E+11 67564.02 05-OCT-05:02 4.00 4.00 0.501892E+10 6734.84 17-OCT-09:09 12.33 11.88
November 0.228655E+11 60833.68 01-NOV-05:02 5.00 4.51 0.488674E+10 6734.76 13-NOV-10:20 8.33 7.62
December 0.202957E+11 20328.34 22-DEC-17:00 5.00 4.08 0.455601E+10 6734.67 22-DEC-14:39 5.00 4.08
                     
Annual Sum or Average 0.353970E+12         0.597527E+11        
Minimum of Months 0.202957E+11 20328.34   4.00 3.12 0.446052E+10 6734.67   5.00 3.98
Maximum of Months 0.402543E+11 71914.10   13.00 12.63 0.548740E+10 6734.87   16.33 12.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.146960E+11 16133.62 19-JAN-17:00 6.00 6.00 0.413872E+10 6506.61 20-JAN-14:00 8.00 6.49
February 0.146827E+11 16092.39 09-FEB-17:00 6.00 4.60 0.385120E+10 6452.64 24-FEB-14:00 6.00 4.60
March 0.192706E+11 19093.29 31-MAR-16:00 9.00 4.96 0.478498E+10 6647.53 31-MAR-13:00 9.00 4.96
April 0.255626E+11 36971.58 28-APR-16:00 20.00 12.32 0.469820E+10 6734.87 14-APR-13:00 20.00 12.32
May 0.292116E+11 53940.88 24-MAY-05:02 8.42 8.35 0.514294E+10 6734.75 12-MAY-09:20 8.42 8.35
June 0.345526E+11 65284.40 27-JUN-05:03 14.17 14.17 0.521917E+10 6734.87 09-JUN-13:00 14.17 14.17
July 0.355735E+11 67074.81 24-JUL-04:12 13.00 13.00 0.485414E+10 6734.77 31-JUL-09:20 14.33 10.86
August 0.371489E+11 63059.38 15-AUG-05:03 14.50 11.07 0.545447E+10 6734.79 23-AUG-09:20 16.33 12.16
September 0.289519E+11 59990.29 13-SEP-05:03 9.33 9.25 0.477453E+10 6734.80 19-SEP-13:00 14.00 14.00
October 0.199310E+11 26695.71 06-OCT-16:00 17.00 9.21 0.457432E+10 6734.68 13-OCT-13:30 11.50 11.24
November 0.160648E+11 17835.86 10-NOV-16:50 7.67 6.84 0.423607E+10 6723.49 10-NOV-14:00 7.67 6.84
December 0.134172E+11 15106.59 21-DEC-17:00 6.00 5.49 0.393604E+10 6249.51 21-DEC-14:00 6.00 5.49
                     
Annual Sum or Average 0.289063E+12         0.556648E+11        
Minimum of Months 0.134172E+11 15106.59   6.00 4.60 0.385120E+10 6249.51   6.00 4.60
Maximum of Months 0.371489E+11 67074.81   20.00 14.17 0.545447E+10 6734.87   20.00 14.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.231363E+10 2441.09 18-JAN-06:02 6.17 5.66 0.567750E+09 845.61 23-JAN-14:09 11.00 9.85
February 0.235480E+10 2992.50 21-FEB-13:40 9.00 7.76 0.536540E+09 845.63 21-FEB-10:30 9.00 7.76
March 0.335702E+10 4792.68 20-MAR-12:30 10.10 6.57 0.666379E+09 845.63 28-MAR-13:09 10.17 6.99
April 0.517424E+10 6830.78 28-APR-14:00 20.00 12.76 0.607140E+09 845.66 14-APR-13:00 20.00 12.76
May 0.511986E+10 6876.53 22-MAY-15:00 24.00 16.08 0.657579E+09 845.63 22-MAY-13:00 24.00 16.08
June 0.687734E+10 11123.86 25-JUN-16:21 23.00 14.48 0.660443E+09 845.83 26-JUN-13:39 22.00 16.85
July 0.762308E+10 9916.99 24-JUL-05:02 13.00 13.00 0.614400E+09 845.93 10-JUL-13:09 13.00 13.00
August 0.777787E+10 7901.41 14-AUG-15:10 25.17 16.00 0.689331E+09 845.77 14-AUG-13:00 25.17 16.00
September 0.480328E+10 6178.11 13-SEP-14:20 23.00 16.22 0.606148E+09 845.64 19-SEP-13:00 14.00 14.00
October 0.338771E+10 5256.98 10-OCT-13:10 13.00 11.87 0.619630E+09 845.63 04-OCT-09:20 13.00 11.87
November 0.273155E+10 3346.24 08-NOV-14:30 12.00 11.73 0.598938E+09 845.62 13-NOV-10:20 8.33 7.62
December 0.246018E+10 2421.86 11-DEC-05:12 3.00 3.00 0.561240E+09 843.03 21-DEC-14:50 8.00 6.98
                     
Annual Sum or Average 0.539806E+11         0.738552E+10        
Minimum of Months 0.231363E+10 2421.86   3.00 3.00 0.536540E+09 843.03   8.00 6.98
Maximum of Months 0.777787E+10 11123.86   25.17 16.22 0.689331E+09 845.93   25.17 16.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159643E+10 4374.10 20-JAN-10:10 4.33 3.91 0.372241E+09 544.95 20-JAN-10:20 4.67 4.23
February 0.172462E+10 5669.69 17-FEB-09:45 2.67 1.90 0.348063E+09 544.96 17-FEB-10:20 4.00 2.99
March 0.223075E+10 5286.14 25-MAR-09:25 10.00 7.02 0.426411E+09 544.96 28-MAR-13:09 10.17 6.99
April 0.567471E+10 23682.96 30-APR-08:21 17.70 12.30 0.392448E+09 544.98 14-APR-13:50 17.70 12.30
May 0.580640E+10 21960.94 07-MAY-08:32 10.67 8.56 0.425542E+09 545.66 23-MAY-09:30 19.50 14.70
June 0.661861E+10 22342.65 25-JUN-09:02 16.33 12.18 0.425882E+09 545.79 13-JUN-09:39 16.33 12.18
July 0.714279E+10 24215.72 23-JUL-08:41 19.83 15.59 0.396568E+09 546.17 10-JUL-09:00 19.83 15.59
August 0.750097E+10 21865.20 27-AUG-09:02 16.17 13.20 0.444546E+09 545.72 14-AUG-09:39 16.17 13.20
September 0.565953E+10 19353.96 04-SEP-08:52 14.00 10.69 0.393597E+09 544.99 06-SEP-09:09 13.33 11.45
October 0.291942E+10 10703.42 01-OCT-08:33 11.00 8.32 0.398033E+09 544.96 17-OCT-09:09 12.33 11.88
November 0.178019E+10 5025.62 13-NOV-09:25 8.00 7.22 0.381052E+09 544.95 13-NOV-10:20 8.33 7.62
December 0.153828E+10 3149.26 06-DEC-09:55 4.00 3.12 0.354151E+09 544.95 20-DEC-10:09 8.17 7.53
                     
Annual Sum or Average 0.501927E+11         0.475853E+10        
Minimum of Months 0.153828E+10 3149.26   2.67 1.90 0.348063E+09 544.95   4.00 2.99
Maximum of Months 0.750097E+10 24215.72   19.83 15.59 0.444546E+09 546.17   19.83 15.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.396424E+10 19054.26 15-JAN-12:32 9.67 6.66 0.581682E+09 845.65 20-JAN-10:00 6.00 5.49
February 0.464471E+10 27650.92 19-FEB-14:53 6.00 4.14 0.541367E+09 845.65 17-FEB-10:00 6.00 4.14
March 0.416905E+10 12197.79 28-MAR-12:05 11.67 7.18 0.655914E+09 845.66 28-MAR-13:09 10.17 6.99
April 0.985447E+10 33708.63 30-APR-12:21 22.00 13.54 0.606799E+09 846.80 27-APR-13:00 22.00 13.54
May 0.785378E+10 28082.99 21-MAY-12:43 16.83 10.10 0.655286E+09 845.66 22-MAY-13:00 23.00 15.76
June 0.888451E+10 28202.59 25-JUN-16:21 23.00 14.48 0.659464E+09 845.69 08-JUN-13:09 23.00 14.48
July 0.104781E+11 30357.73 23-JUL-14:02 21.00 15.99 0.614528E+09 845.66 18-JUL-13:09 21.00 15.99
August 0.129298E+11 30720.18 27-AUG-13:02 19.00 14.78 0.690155E+09 846.99 21-AUG-13:09 19.00 14.78
September 0.112903E+11 30666.24 10-SEP-12:42 21.00 15.44 0.609620E+09 847.01 29-SEP-13:00 16.00 9.47
October 0.698925E+10 29408.85 01-OCT-11:13 14.00 9.83 0.614589E+09 846.84 04-OCT-13:00 14.00 10.28
November 0.423838E+10 21988.90 11-NOV-13:13 9.00 7.29 0.592388E+09 845.64 13-NOV-10:20 8.33 7.62
December 0.331452E+10 15691.56 18-DEC-13:30 8.00 5.46 0.557507E+09 845.64 20-DEC-10:09 8.17 7.53
                     
Annual Sum or Average 0.886111E+11         0.737930E+10        
Minimum of Months 0.331452E+10 12197.79   6.00 4.14 0.541367E+09 845.64   6.00 4.14
Maximum of Months 0.129298E+11 33708.63   23.00 15.99 0.690155E+09 847.01   23.00 15.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222958E+10 8048.45 30-JAN-16:35 7.37 6.68 0.394288E+09 544.95 23-JAN-10:20 7.37 6.68
February 0.328193E+10 13542.54 19-FEB-14:53 6.00 4.14 0.369028E+09 544.96 21-FEB-10:09 8.17 7.45
March 0.496464E+10 13932.23 24-MAR-05:02 4.00 3.12 0.444816E+09 544.96 28-MAR-13:09 10.17 6.99
April 0.952712E+10 29057.74 30-APR-14:21 23.50 12.96 0.396301E+09 544.99 14-APR-13:50 23.50 12.96
May 0.736063E+10 26929.26 21-MAY-16:42 19.67 12.38 0.427617E+09 544.96 22-MAY-13:00 23.00 15.76
June 0.997542E+10 30565.24 11-JUN-16:11 15.33 13.15 0.427462E+09 544.98 08-JUN-13:09 15.33 13.15
July 0.117093E+11 30071.20 23-JUL-17:21 21.00 16.54 0.398032E+09 544.96 03-JUL-09:09 21.00 16.54
August 0.126185E+11 28047.11 20-AUG-16:41 22.33 14.82 0.446430E+09 545.14 14-AUG-13:00 22.33 14.82
September 0.665610E+10 21182.28 10-SEP-16:02 20.67 16.45 0.395099E+09 544.97 06-SEP-09:09 20.67 16.45
October 0.466644E+10 17162.02 01-OCT-16:33 12.00 9.04 0.410379E+09 544.97 17-OCT-09:09 12.33 11.88
November 0.382317E+10 17538.49 09-NOV-06:02 9.00 9.00 0.406057E+09 544.96 07-NOV-14:09 9.00 9.00
December 0.343067E+10 11351.79 16-DEC-06:02 5.17 4.60 0.395630E+09 544.96 20-DEC-10:09 8.17 7.53
                     
Annual Sum or Average 0.802435E+11         0.491114E+10        
Minimum of Months 0.222958E+10 8048.45   4.00 3.12 0.369028E+09 544.95   7.37 6.68
Maximum of Months 0.126185E+11 30565.24   23.50 16.54 0.446430E+09 545.14   23.50 16.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.975159E+09 1762.40 15-JAN-13:02 9.83 6.75 0.488999E+09 747.24 19-JAN-14:00 9.00 7.43
February 0.115577E+10 1761.06 19-FEB-13:13 6.00 4.14 0.452325E+09 734.44 22-FEB-14:00 9.00 6.99
March 0.196758E+10 2012.13 30-MAR-14:10 12.83 7.23 0.576292E+09 827.39 30-MAR-13:00 12.83 7.23
April 0.303729E+10 5272.86 28-APR-14:00 20.00 12.76 0.575792E+09 845.64 25-APR-13:09 20.00 12.76
May 0.364998E+10 5732.68 22-MAY-15:00 24.00 16.08 0.635609E+09 845.63 24-MAY-13:20 16.00 12.90
June 0.503304E+10 7274.16 13-JUN-15:10 26.08 17.81 0.653923E+09 845.65 09-JUN-13:00 26.08 17.81
July 0.535518E+10 7201.18 10-JUL-15:00 23.00 16.69 0.608783E+09 845.63 18-JUL-13:09 19.00 15.79
August 0.514219E+10 6186.04 14-AUG-16:00 26.00 15.86 0.680699E+09 845.63 16-AUG-13:20 20.33 15.79
September 0.354341E+10 5394.60 13-SEP-15:30 23.00 16.22 0.588085E+09 845.63 19-SEP-13:00 14.00 14.00
October 0.217567E+10 2778.50 11-OCT-15:00 17.00 11.04 0.553581E+09 845.62 10-OCT-13:20 17.00 11.04
November 0.139354E+10 1996.71 11-NOV-12:22 9.00 7.22 0.498965E+09 776.51 10-NOV-14:00 9.00 7.22
December 0.632958E+09 1540.58 21-DEC-14:40 8.00 6.98 0.455429E+09 684.91 21-DEC-14:50 8.00 6.98
                     
Annual Sum or Average 0.340618E+11         0.676848E+10        
Minimum of Months 0.632958E+09 1540.58   6.00 4.14 0.452325E+09 684.91   8.00 6.98
Maximum of Months 0.535518E+10 7274.16   26.08 17.81 0.680699E+09 845.65   26.08 17.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.630620E+09 4105.50 20-JAN-11:05 6.33 5.61 0.240779E+09 548.49 20-JAN-11:09 6.33 5.61
February 0.784273E+09 4987.14 24-FEB-11:05 6.00 4.60 0.229454E+09 548.49 17-FEB-11:09 6.00 4.60
March 0.115701E+10 5498.10 25-MAR-10:05 11.08 8.00 0.285938E+09 548.49 28-MAR-12:09 11.67 7.18
April 0.473996E+10 22578.70 30-APR-09:12 18.67 12.24 0.285379E+09 548.51 14-APR-14:09 18.67 12.24
May 0.502755E+10 24014.99 21-MAY-08:32 13.00 9.47 0.309750E+09 548.50 22-MAY-14:09 23.17 15.81
June 0.596650E+10 23860.76 11-JUN-09:22 16.00 13.04 0.312465E+09 548.51 09-JUN-14:09 16.00 13.04
July 0.640729E+10 26147.15 23-JUL-08:31 19.67 15.53 0.292587E+09 548.50 24-JUL-12:09 19.00 15.90
August 0.670737E+10 22822.61 06-AUG-09:52 16.00 13.59 0.326379E+09 548.51 14-AUG-10:09 22.00 16.44
September 0.500682E+10 22672.01 24-SEP-09:02 18.00 14.39 0.288181E+09 548.51 07-SEP-10:09 18.00 14.39
October 0.192267E+10 11886.10 01-OCT-09:02 12.17 8.55 0.275107E+09 548.49 03-OCT-12:09 13.00 9.72
November 0.805656E+09 4150.72 03-NOV-10:05 7.33 5.22 0.246164E+09 548.49 13-NOV-11:09 9.33 8.19
December 0.388320E+09 1271.85 08-DEC-11:10 6.17 4.24 0.222117E+09 519.67 08-DEC-11:09 6.17 4.24
                     
Annual Sum or Average 0.395441E+11         0.331430E+10        
Minimum of Months 0.388320E+09 1271.85   6.00 4.24 0.222117E+09 519.67   6.00 4.24
Maximum of Months 0.670737E+10 26147.15   19.67 15.53 0.326379E+09 548.51   23.17 16.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.322392E+10 31532.31 15-JAN-13:02 9.83 6.75 0.554071E+09 845.65 20-JAN-10:00 6.00 5.49
February 0.400492E+10 30494.45 19-FEB-13:13 6.00 4.14 0.516631E+09 845.65 17-FEB-10:00 6.00 4.14
March 0.311937E+10 11157.51 28-MAR-12:05 11.67 7.18 0.620173E+09 845.65 28-MAR-13:09 10.17 6.99
April 0.870107E+10 32928.31 30-APR-13:12 22.33 12.98 0.594945E+09 847.28 26-APR-13:20 22.33 12.98
May 0.717825E+10 28615.45 21-MAY-13:53 17.00 10.30 0.644447E+09 845.68 02-MAY-13:30 17.00 10.30
June 0.777802E+10 26292.98 11-JUN-13:23 18.00 14.39 0.653846E+09 845.69 08-JUN-13:09 18.00 14.39
July 0.905240E+10 31997.26 30-JUL-13:32 17.00 12.42 0.610462E+09 845.67 25-JUL-13:30 17.00 12.42
August 0.114165E+11 33399.84 06-AUG-13:52 18.00 13.90 0.685938E+09 847.28 29-AUG-13:20 17.33 13.63
September 0.114193E+11 33120.52 24-SEP-11:42 19.00 14.78 0.605006E+09 847.46 01-SEP-13:20 19.00 14.78
October 0.658637E+10 31679.46 01-OCT-11:42 14.00 9.83 0.591929E+09 846.92 11-OCT-13:20 16.00 10.47
November 0.325699E+10 31674.88 11-NOV-12:22 9.00 7.22 0.552576E+09 845.64 13-NOV-10:20 8.33 7.62
December 0.182584E+10 14187.72 18-DEC-13:30 8.00 5.46 0.508147E+09 845.64 18-DEC-14:09 8.00 5.67
                     
Annual Sum or Average 0.775630E+11         0.713817E+10        
Minimum of Months 0.182584E+10 11157.51   6.00 4.14 0.508147E+09 845.64   6.00 4.14
Maximum of Months 0.114193E+11 33399.84   22.33 14.78 0.685938E+09 847.46   22.33 14.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101647E+10 4294.71 19-JAN-15:40 8.33 7.46 0.333030E+09 544.95 25-JAN-14:39 11.00 9.22
February 0.145922E+10 7254.26 27-FEB-16:30 8.00 6.72 0.314838E+09 544.94 27-FEB-14:20 8.00 6.72
March 0.176521E+10 7812.34 23-MAR-16:40 10.00 6.65 0.392001E+09 544.94 10-MAR-14:20 10.00 6.65
April 0.462101E+10 24847.96 30-APR-17:12 24.00 12.77 0.382641E+09 544.97 14-APR-13:00 24.00 12.77
May 0.529901E+10 27645.65 21-MAY-16:31 19.33 11.98 0.416930E+09 544.96 22-MAY-13:00 23.00 15.76
June 0.683755E+10 27979.78 11-JUN-17:21 14.00 12.24 0.424033E+09 544.97 09-JUN-13:00 14.00 12.24
July 0.745780E+10 28894.59 09-JUL-17:21 21.00 15.03 0.394873E+09 544.96 18-JUL-13:09 19.00 15.79
August 0.696108E+10 26620.00 06-AUG-16:31 18.33 13.35 0.443123E+09 544.96 16-AUG-13:20 20.33 15.79
September 0.470587E+10 23771.12 24-SEP-15:02 22.00 15.41 0.386904E+09 544.96 19-SEP-13:00 22.00 15.41
October 0.229616E+10 9996.28 03-OCT-15:40 14.00 8.96 0.372456E+09 544.95 02-OCT-13:20 14.00 8.96
November 0.125314E+10 4404.48 10-NOV-15:30 11.50 8.42 0.340234E+09 544.94 08-NOV-14:00 11.50 8.42
December 0.655462E+09 1641.26 21-DEC-14:40 8.00 6.98 0.304974E+09 544.94 21-DEC-14:00 8.00 6.98
                     
Annual Sum or Average 0.443280E+11         0.450604E+10        
Minimum of Months 0.655462E+09 1641.26   8.00 6.65 0.304974E+09 544.94   8.00 6.65
Maximum of Months 0.745780E+10 28894.59   24.00 15.41 0.443123E+09 544.97   24.00 15.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.365225E+09 1586.16 19-JAN-15:40 8.33 7.46 0.468975E+09 694.20 19-JAN-14:00 8.33 7.46
February 0.497847E+09 1521.42 24-FEB-16:10 6.00 4.60 0.427550E+09 674.74 22-FEB-14:00 6.00 4.60
March 0.112116E+10 1829.86 30-MAR-15:30 12.00 6.19 0.531947E+09 766.11 30-MAR-13:00 12.00 6.19
April 0.249672E+10 5504.01 28-APR-15:20 20.07 13.24 0.546692E+09 845.64 14-APR-13:00 20.07 13.24
May 0.317045E+10 6365.00 22-MAY-15:00 24.00 16.08 0.606656E+09 845.63 22-MAY-13:00 24.00 16.08
June 0.472451E+10 8129.11 13-JUN-15:00 26.00 17.83 0.642210E+09 845.65 09-JUN-13:00 26.00 17.83
July 0.512800E+10 7913.40 10-JUL-15:00 23.00 16.69 0.601519E+09 845.63 18-JUL-13:09 19.00 15.79
August 0.480009E+10 6748.16 14-AUG-16:00 26.00 15.86 0.669343E+09 845.63 21-AUG-13:00 21.00 15.01
September 0.301948E+10 5623.75 13-SEP-15:30 23.00 16.22 0.566246E+09 845.63 19-SEP-13:00 14.00 14.00
October 0.138488E+10 2130.43 01-OCT-15:02 12.83 9.72 0.507211E+09 814.86 06-OCT-13:00 16.00 9.11
November 0.546933E+09 1689.84 10-NOV-15:30 11.50 8.42 0.469202E+09 727.95 10-NOV-14:00 11.50 8.42
December 0.147965E+09 1367.64 21-DEC-14:50 8.00 6.98 0.447974E+09 637.03 21-DEC-14:00 8.00 6.98
                     
Annual Sum or Average 0.274033E+11         0.648553E+10        
Minimum of Months 0.147965E+09 1367.64   6.00 4.60 0.427550E+09 637.03   6.00 4.60
Maximum of Months 0.512800E+10 8129.11   26.00 17.83 0.669343E+09 845.65   26.00 17.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.396423E+09 1287.89 20-JAN-10:40 5.33 4.86 0.308316E+09 530.12 20-JAN-10:50 5.67 5.18
February 0.540692E+09 2096.33 24-FEB-10:30 5.50 4.13 0.290138E+09 544.95 17-FEB-10:20 5.50 4.13
March 0.922144E+09 1827.03 25-MAR-09:30 10.00 7.02 0.357021E+09 538.88 31-MAR-09:00 9.00 5.32
April 0.428493E+10 24314.69 30-APR-09:31 19.33 12.50 0.381837E+09 544.98 14-APR-13:50 19.33 12.50
May 0.464608E+10 22895.31 21-MAY-08:32 13.00 9.47 0.414161E+09 545.74 23-MAY-09:50 19.83 14.63
June 0.587791E+10 23662.02 25-JUN-09:32 17.33 12.62 0.421773E+09 545.71 13-JUN-09:00 17.33 12.62
July 0.636044E+10 23309.91 23-JUL-08:52 20.00 15.65 0.394391E+09 545.66 10-JUL-09:00 20.00 15.65
August 0.661422E+10 22198.77 06-AUG-10:02 16.17 13.65 0.440845E+09 544.98 23-AUG-09:09 16.17 12.09
September 0.461729E+10 13147.95 10-SEP-09:12 17.33 14.10 0.386673E+09 544.98 06-SEP-09:09 17.33 14.10
October 0.148700E+10 5963.42 04-OCT-10:00 13.00 9.81 0.350120E+09 544.95 11-OCT-13:20 16.00 10.47
November 0.491878E+09 1236.49 03-NOV-10:00 7.00 5.17 0.309366E+09 512.28 03-NOV-09:00 7.00 5.17
December 0.207349E+09 1071.48 06-DEC-10:20 5.00 3.82 0.291242E+09 463.95 06-DEC-10:30 5.50 4.16
                     
Annual Sum or Average 0.364464E+11         0.434588E+10        
Minimum of Months 0.207349E+09 1071.48   5.00 3.82 0.290138E+09 463.95   5.50 4.13
Maximum of Months 0.661422E+10 24314.69   20.00 15.65 0.440845E+09 545.74   20.00 15.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.203629E+10 13212.30 11-JAN-13:40 -1.3 -2.8 0.522615E+09 845.64 17-JAN-14:39 10.67 7.88
February 0.274942E+10 17161.05 17-FEB-13:40 6.00 3.25 0.489066E+09 845.64 27-FEB-14:09 8.83 7.77
March 0.202185E+10 8510.87 28-MAR-12:20 11.33 7.17 0.578520E+09 845.65 28-MAR-13:09 10.17 6.99
April 0.774706E+10 37218.33 30-APR-12:11 22.00 13.70 0.577267E+09 846.55 28-APR-13:39 22.00 13.70
May 0.642721E+10 26160.24 21-MAY-13:53 17.00 10.30 0.624316E+09 845.66 22-MAY-13:00 23.00 15.76
June 0.743188E+10 31450.87 25-JUN-16:11 23.67 14.60 0.643308E+09 845.69 08-JUN-13:09 23.67 14.60
July 0.877456E+10 27505.00 23-JUL-12:52 22.00 16.43 0.604226E+09 845.68 21-JUL-13:09 22.00 16.43
August 0.110000E+11 34690.92 06-AUG-12:42 17.00 13.49 0.678484E+09 846.45 29-AUG-13:50 17.83 13.84
September 0.105298E+11 37213.57 10-SEP-13:11 21.00 15.63 0.593364E+09 846.57 29-SEP-13:00 16.00 9.47
October 0.518582E+10 32056.73 01-OCT-15:02 12.83 9.72 0.557739E+09 846.19 04-OCT-13:50 14.00 10.28
November 0.197247E+10 22807.20 11-NOV-12:22 9.00 7.22 0.516740E+09 845.64 17-NOV-14:09 8.00 6.02
December 0.106617E+10 11431.07 18-DEC-13:30 8.00 5.46 0.485354E+09 845.64 18-DEC-14:09 8.00 5.67
                     
Annual Sum or Average 0.669425E+11         0.687100E+10        
Minimum of Months 0.106617E+10 8510.87   -1.3 -2.8 0.485354E+09 845.64   8.00 5.67
Maximum of Months 0.110000E+11 37218.33   23.67 16.43 0.678484E+09 846.57   23.67 16.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.561752E+09 3497.06 19-JAN-15:50 8.17 7.46 0.316304E+09 544.93 19-JAN-14:00 8.17 7.46
February 0.941582E+09 6260.29 27-FEB-16:30 8.00 6.72 0.297796E+09 544.93 27-FEB-14:50 8.00 6.72
March 0.127818E+10 7007.76 23-MAR-16:40 10.00 6.65 0.364076E+09 544.92 10-MAR-14:39 10.00 6.65
April 0.422302E+10 29407.57 30-APR-16:11 24.00 12.95 0.367641E+09 544.97 14-APR-13:00 24.00 12.95
May 0.490238E+10 28822.91 21-MAY-16:31 19.33 11.98 0.403632E+09 544.96 22-MAY-13:00 23.00 15.76
June 0.661391E+10 28230.81 25-JUN-16:11 23.67 14.60 0.419017E+09 544.98 09-JUN-13:00 23.67 14.60
July 0.728301E+10 30126.01 09-JUL-17:31 21.00 15.03 0.392101E+09 544.96 18-JUL-13:09 19.00 15.79
August 0.671166E+10 26700.49 13-AUG-16:51 19.00 14.78 0.439328E+09 544.96 21-AUG-13:00 21.00 15.01
September 0.433516E+10 26119.75 10-SEP-16:32 19.67 16.13 0.376308E+09 544.96 28-SEP-13:00 16.00 13.03
October 0.177080E+10 9513.33 03-OCT-15:40 14.00 8.96 0.346378E+09 544.95 02-OCT-13:20 14.00 8.96
November 0.761077E+09 3669.07 10-NOV-15:30 11.50 8.42 0.317650E+09 544.93 15-NOV-14:00 12.00 8.90
December 0.308657E+09 1262.18 21-DEC-14:50 8.00 6.98 0.295077E+09 523.39 21-DEC-14:00 8.00 6.98
                     
Annual Sum or Average 0.396912E+11         0.433531E+10        
Minimum of Months 0.308657E+09 1262.18   8.00 6.65 0.295077E+09 523.39   8.00 6.65
Maximum of Months 0.728301E+10 30126.01   24.00 16.13 0.439328E+09 544.98   24.00 15.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.989256E+09 4024.47 02-JAN-06:13 1.33 0.92 0.00 0.00 01-JAN-00:10 1.33 0.92
February 0.104311E+10 2829.67 24-FEB-06:10 -0.3 -0.3 0.00 0.00 01-FEB-00:10 -0.3 -0.3
March 0.200934E+10 3834.77 20-MAR-05:15 5.00 4.51 0.00 0.00 01-MAR-00:10 5.00 4.51
April 0.466665E+10 6609.88 24-APR-05:15 7.00 5.00 0.00 0.00 01-APR-00:10 7.00 5.00
May 0.382600E+10 7913.05 01-MAY-05:15 4.67 3.91 0.00 0.00 01-MAY-00:10 4.67 3.91
June 0.540488E+10 8905.79 26-JUN-05:15 14.67 12.18 0.00 0.00 01-JUN-00:10 14.67 12.18
July 0.638023E+10 7443.41 24-JUL-15:20 19.33 16.00 0.00 0.00 01-JUL-00:10 19.33 16.00
August 0.717887E+10 8032.95 28-AUG-05:15 9.33 8.59 0.00 0.00 01-AUG-00:10 9.33 8.59
September 0.448061E+10 6408.64 05-SEP-05:15 6.67 5.99 0.00 0.00 01-SEP-00:10 6.67 5.99
October 0.276526E+10 6947.83 10-OCT-05:15 11.00 11.00 0.00 0.00 01-OCT-00:10 11.00 11.00
November 0.174399E+10 5188.09 13-NOV-06:13 4.33 3.86 0.00 0.00 01-NOV-00:10 4.33 3.86
December 0.104004E+10 2549.87 27-DEC-06:07 -2.0 -2.0 0.00 0.00 01-DEC-00:10 -2.0 -2.0
                     
Annual Sum or Average 0.415283E+11         0.00        
Minimum of Months 0.989256E+09 2549.87   -2.0 -2.0 0.00 0.00   -2.0 -2.0
Maximum of Months 0.717887E+10 8905.79   19.33 16.00 0.00 0.00   19.33 16.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.310966E+09 6678.19 10-JAN-05:01 -4.0 -4.8 0.00 0.00 01-JAN-00:10 -4.0 -4.8
February 0.375044E+09 6793.75 24-FEB-06:02 -0.3 -0.3 0.00 0.00 01-FEB-00:10 -0.3 -0.3
March 0.601630E+09 6303.72 04-MAR-06:02 3.00 0.90 0.00 0.00 01-MAR-00:10 3.00 0.90
April 0.176958E+10 3853.52 28-APR-15:30 20.05 13.01 0.00 0.00 01-APR-00:10 20.05 13.01
May 0.186566E+10 3483.00 23-MAY-15:30 18.00 14.38 0.00 0.00 01-MAY-00:10 18.00 14.38
June 0.305180E+10 4649.01 26-JUN-15:30 22.50 17.36 0.00 0.00 01-JUN-00:10 22.50 17.36
July 0.356246E+10 5118.09 24-JUL-15:40 19.67 16.09 0.00 0.00 01-JUL-00:10 19.67 16.09
August 0.387119E+10 4382.64 21-AUG-15:30 21.00 15.01 0.00 0.00 01-AUG-00:10 21.00 15.01
September 0.267630E+10 4340.16 12-SEP-15:30 21.50 15.72 0.00 0.00 01-SEP-00:10 21.50 15.72
October 0.101996E+10 2791.23 06-OCT-05:10 3.00 3.00 0.00 0.00 01-OCT-00:10 3.00 3.00
November 0.416139E+09 6320.08 20-NOV-05:01 0.67 -0.1 0.00 0.00 01-NOV-00:10 0.67 -0.1
December 0.159216E+09 7434.16 30-DEC-05:01 -1.8 -3.4 0.00 0.00 01-DEC-00:10 -1.8 -3.4
                     
Annual Sum or Average 0.196799E+11         0.00        
Minimum of Months 0.159216E+09 2791.23   -4.0 -4.8 0.00 0.00   -4.0 -4.8
Maximum of Months 0.387119E+10 7434.16   22.50 17.36 0.00 0.00   22.50 17.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4663726.14 759.74 21-JAN-13:05 7.83 6.08 0.00 0.00 01-JAN-00:10 7.83 6.08
February 8417763.15 926.87 19-FEB-15:00 6.00 4.14 0.00 0.00 01-FEB-00:10 6.00 4.14
March 97192227.69 2433.82 25-MAR-12:30 13.00 10.05 0.00 0.00 01-MAR-00:10 13.00 10.05
April 0.324354E+10 13081.00 28-APR-14:50 20.08 13.54 0.00 0.00 01-APR-00:10 20.08 13.54
May 0.377814E+10 13909.81 22-MAY-14:30 23.50 15.92 0.00 0.00 01-MAY-00:10 23.50 15.92
June 0.593563E+10 15728.85 13-JUN-14:20 25.40 17.58 0.00 0.00 01-JUN-00:10 25.40 17.58
July 0.696672E+10 15413.34 21-JUL-14:30 27.00 16.02 0.00 0.00 01-JUL-00:10 27.00 16.02
August 0.659817E+10 13724.24 14-AUG-14:50 24.83 16.12 0.00 0.00 01-AUG-00:10 24.83 16.12
September 0.378365E+10 11690.70 12-SEP-15:30 21.50 15.72 0.00 0.00 01-SEP-00:10 21.50 15.72
October 0.587095E+09 4735.42 03-OCT-14:40 14.00 9.11 0.00 0.00 01-OCT-00:10 14.00 9.11
November 2908169.20 971.61 11-NOV-13:46 9.00 7.08 0.00 0.00 01-NOV-00:10 9.00 7.08
December 0.00 0.00 01-DEC-00:10 4.00 3.53 0.00 0.00 01-DEC-00:10 4.00 3.53
                     
Annual Sum or Average 0.310061E+11         0.00        
Minimum of Months 0.00 0.00   4.00 3.53 0.00 0.00   4.00 3.53
Maximum of Months 0.696672E+10 15728.85   27.00 17.58 0.00 0.00   27.00 17.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.318398E+10 1904.92 19-JAN-16:20 7.33 6.98 95230135.38 126.83 18-JAN-14:00 7.33 6.98
February 0.778098E+10 4103.25 27-FEB-17:00 8.00 6.97 86396549.23 126.83 08-FEB-14:00 8.00 6.97
March 0.139709E+11 6999.61 31-MAR-24:00 4.30 1.71 0.103236E+09 126.82 23-MAR-13:09 4.30 1.71
April 0.188425E+11 8281.70 30-APR-19:12 21.67 13.25 91605078.69 126.82 28-APR-09:09 21.67 13.25
May 0.416715E+10 3327.17 31-MAY-24:00 9.40 7.45 99234876.90 126.84 23-MAY-13:00 9.40 7.45
June 0.917980E+10 5168.31 30-JUN-24:00 11.00 9.86 98962868.80 126.84 27-JUN-09:09 11.00 9.86
July 0.146635E+11 7230.99 31-JUL-24:00 11.40 9.79 91885260.05 126.83 24-JUL-09:09 11.40 9.79
August 0.196398E+11 8267.81 13-AUG-18:03 17.83 13.92 0.103238E+09 126.83 08-AUG-13:00 17.83 13.92
September 0.406968E+10 3225.84 30-SEP-24:00 7.60 5.71 91609685.84 126.84 12-SEP-13:00 7.60 5.71
October 0.900663E+10 5068.91 31-OCT-24:00 6.60 4.32 95231983.00 126.83 10-OCT-13:00 6.60 4.32
November 0.134753E+11 5672.17 03-NOV-16:00 8.00 4.84 94301137.62 126.83 08-NOV-14:00 12.00 12.00
December 0.188095E+11 7427.70 25-DEC-15:13 5.80 4.26 91880817.93 126.82 26-DEC-10:09 3.17 1.00
                     
Annual Sum or Average 0.136790E+12         0.114281E+10        
Minimum of Months 0.318398E+10 1904.92   4.30 1.71 86396549.23 126.82   3.17 1.00
Maximum of Months 0.196398E+11 8281.70   21.67 13.92 0.103238E+09 126.84   21.67 13.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112213E+10 1661.46 19-JAN-16:30 7.00 6.74 95211315.51 126.82 18-JAN-14:00 7.00 6.74
February 0.581449E+10 3704.66 27-FEB-17:00 8.00 6.97 86396564.17 126.82 08-FEB-14:00 8.00 6.97
March 0.118172E+11 6290.28 31-MAR-23:30 4.50 1.74 0.103236E+09 126.82 23-MAR-13:09 4.50 1.74
April 0.173221E+11 7877.11 30-APR-18:02 24.00 13.14 91605090.00 126.82 28-APR-09:09 24.00 13.14
May 0.333062E+10 3032.85 31-MAY-23:40 9.70 8.23 99234817.95 126.84 23-MAY-13:00 9.70 8.23
June 0.833170E+10 4712.95 30-JUN-23:40 11.00 10.07 98962615.13 126.84 27-JUN-09:09 11.00 10.07
July 0.135920E+11 6790.10 31-JUL-23:50 11.38 9.85 91885074.83 126.83 24-JUL-13:00 11.38 9.85
August 0.184035E+11 7703.16 13-AUG-18:03 17.83 13.92 0.103238E+09 126.83 08-AUG-13:00 17.83 13.92
September 0.329132E+10 2850.61 30-SEP-23:30 7.65 5.76 91609439.58 126.84 12-SEP-13:00 7.65 5.76
October 0.733809E+10 4338.71 31-OCT-23:50 6.62 4.28 95231899.88 126.83 10-OCT-13:00 6.62 4.28
November 0.110113E+11 5265.46 03-NOV-16:00 8.00 4.84 94301113.81 126.83 08-NOV-14:00 12.00 12.00
December 0.153070E+11 6731.63 21-DEC-15:20 7.67 6.81 91880841.21 126.82 26-DEC-10:09 3.17 1.00
                     
Annual Sum or Average 0.116682E+12         0.114279E+10        
Minimum of Months 0.112213E+10 1661.46   4.50 1.74 86396564.17 126.82   3.17 1.00
Maximum of Months 0.184035E+11 7877.11   24.00 13.92 0.103238E+09 126.84   24.00 13.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.246273E+09 1523.28 19-JAN-16:30 7.00 6.74 92844827.49 127.44 03-JAN-14:50 7.00 6.74
February 0.398066E+10 3492.25 24-FEB-17:00 6.00 4.60 86396564.49 126.82 08-FEB-14:00 6.00 4.60
March 0.100969E+11 5798.76 31-MAR-23:20 4.57 1.75 0.103236E+09 126.82 23-MAR-13:09 4.57 1.75
April 0.164960E+11 7997.64 30-APR-17:53 24.00 13.13 91605094.11 126.82 28-APR-09:09 24.00 13.13
May 0.259926E+10 2878.49 31-MAY-23:20 10.00 9.01 99235584.44 126.84 23-MAY-13:00 10.00 9.01
June 0.798202E+10 4487.29 30-JUN-23:20 11.00 10.27 98962681.22 126.84 27-JUN-09:09 11.00 10.27
July 0.132951E+11 6628.55 31-JUL-23:20 11.33 10.03 91885189.20 126.83 24-JUL-13:00 11.33 10.03
August 0.180914E+11 7818.58 13-AUG-17:55 18.00 13.90 0.103239E+09 126.83 08-AUG-13:00 18.00 13.90
September 0.261804E+10 2313.06 30-SEP-23:10 7.68 5.79 91609379.66 126.84 12-SEP-13:00 7.68 5.79
October 0.574568E+10 3794.79 03-OCT-16:50 13.17 8.54 95231832.60 126.83 10-OCT-13:00 13.00 11.87
November 0.910949E+10 5159.43 10-NOV-16:20 9.67 7.83 94301133.60 126.83 08-NOV-14:00 9.67 7.83
December 0.133088E+11 6456.35 21-DEC-15:20 7.67 6.81 91880847.90 126.82 26-DEC-10:09 3.17 1.00
                     
Annual Sum or Average 0.103570E+12         0.114043E+10        
Minimum of Months 0.246273E+09 1523.28   4.57 1.75 86396564.49 126.82   3.17 1.00
Maximum of Months 0.180914E+11 7997.64   24.00 13.90 0.103239E+09 127.44   24.00 13.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235997E+12 90599.31 02-JAN-17:00 3.00 1.77 0.206144E+10 2745.86 25-JAN-14:39 11.00 9.22
February 0.433945E+12 181906.45 09-FEB-17:00 6.00 4.60 0.187027E+10 2746.00 08-FEB-14:30 6.00 4.60
March 0.726857E+12 358093.97 31-MAR-24:00 4.30 1.71 0.223480E+10 2745.44 31-MAR-09:50 4.30 1.71
April 0.942196E+12 366506.37 28-APR-16:00 20.00 12.32 0.198317E+10 2749.24 28-APR-09:09 20.00 12.32
May 0.239200E+12 175411.82 31-MAY-24:00 9.40 7.45 0.214808E+10 2745.84 04-MAY-09:39 9.40 7.45
June 0.468546E+12 266685.65 30-JUN-24:00 11.00 9.86 0.214224E+10 2748.57 12-JUN-13:09 11.00 9.86
July 0.730503E+12 359595.20 31-JUL-24:00 11.40 9.79 0.199007E+10 2750.45 24-JUL-13:09 11.40 9.79
August 0.975714E+12 367075.99 28-AUG-16:00 24.00 15.59 0.223754E+10 2750.67 16-AUG-09:09 24.00 15.59
September 0.232953E+12 175315.53 30-SEP-24:00 7.60 5.71 0.198293E+10 2745.67 13-SEP-13:00 7.60 5.71
October 0.483677E+12 266922.40 31-OCT-24:00 6.60 4.32 0.206140E+10 2746.09 30-OCT-13:30 6.60 4.32
November 0.704828E+12 274503.51 13-NOV-15:00 8.00 7.45 0.204131E+10 2746.62 06-NOV-10:50 8.00 7.45
December 0.972822E+12 366018.41 26-DEC-17:00 1.00 0.17 0.198902E+10 2745.45 13-DEC-14:30 1.00 0.17
                     
Annual Sum or Average 0.714724E+13         0.247423E+11        
Minimum of Months 0.232953E+12 90599.31   1.00 0.17 0.187027E+10 2745.44   1.00 0.17
Maximum of Months 0.975714E+12 367075.99   24.00 15.59 0.223754E+10 2750.67   24.00 15.59



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.306090E+09 9760.14 18-JAN-05:15 6.67
February 60408367.77 9748.10 08-FEB-05:15 6.00
March 0.110003E+09 9967.40 27-MAR-03:07 1.65
April 46445192.15 9814.96 20-APR-04:07 1.00
May 0.209243E+09 9885.28 31-MAY-04:17 7.00
June 61280561.82 9795.03 01-JUN-04:17 6.00
July 0.153703E+09 14499.04 22-JUL-16:01 29.00
August 0.162047E+09 9505.29 22-AUG-04:57 13.00
September 0.102159E+09 9881.07 19-SEP-04:17 11.00
October 0.192314E+09 9848.96 12-OCT-04:17 4.33
November 0.232372E+09 9833.29 15-NOV-05:17 11.00
December 94309003.42 9772.86 18-DEC-05:27 0.50
         
Annual Sum or Average 0.173037E+10      
Minimum of Months 46445192.15 9505.29   0.50
Maximum of Months 0.306090E+09 14499.04   29.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.192046E+10 64831.41 02-JAN-04:01 1.17
February 0.857308E+09 58875.59 27-FEB-05:11 6.00
March 0.324549E+09 57967.62 06-MAR-05:11 3.87
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 87253945.37 54329.03 23-OCT-05:03 3.17
November 0.842811E+09 60585.43 27-NOV-05:21 4.00
December 0.191729E+10 63482.36 26-DEC-05:21 1.95
         
Annual Sum or Average 0.594967E+10      
Minimum of Months 0.00 0.00   1.17
Maximum of Months 0.192046E+10 64831.41   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2452977.10 5547.14 11-JAN-06:01 -2.9
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 2452977.10      
Minimum of Months 0.00 0.00   -2.9
Maximum of Months 2452977.10 5547.14   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6764693.02 4067.95 10-JAN-06:01 -4.0
February 51801.05 604.35 17-FEB-06:01 -3.1
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 391111.40 3738.51 30-DEC-06:01 -1.0
         
Annual Sum or Average 7207605.47      
Minimum of Months 0.00 0.00   -4.0
Maximum of Months 6764693.02 4067.95   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 26983830.90 8763.47 10-JAN-06:01 -4.0
February 1221112.35 5088.56 17-FEB-06:01 -3.1
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 1059435.76 5216.15 27-NOV-06:01 4.00
December 5006539.38 8018.75 30-DEC-06:01 -1.0
         
Annual Sum or Average 34270918.40      
Minimum of Months 0.00 0.00   -4.0
Maximum of Months 26983830.90 8763.47   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.836679E+09 9230.30 02-JAN-05:01 1.00
February 0.411874E+09 8822.53 13-FEB-05:01 -1.0
March 0.127630E+09 8423.77 04-MAR-05:11 3.00
April 731135.75 3759.01 01-APR-05:02 2.17
May 1590015.42 8013.66 05-MAY-05:02 6.00
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 27498007.32 8125.05 28-OCT-05:02 7.00
November 0.372954E+09 9060.63 20-NOV-05:01 0.67
December 0.130246E+10 9585.40 26-DEC-05:11 1.97
         
Annual Sum or Average 0.308142E+10      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 0.130246E+10 9585.40   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.474289E+09 12596.41 10-JAN-05:01 -4.0
February 0.223240E+09 11973.22 17-FEB-05:01 -2.1
March 72334647.42 11024.68 06-MAR-06:02 4.00
April 75533.43 715.67 01-APR-05:02 2.17
May 600703.96 5005.87 05-MAY-05:02 6.00
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 17514071.28 9957.14 21-OCT-05:02 7.00
November 0.222748E+09 12453.30 20-NOV-05:01 0.67
December 0.807429E+09 13424.27 26-DEC-05:11 1.97
         
Annual Sum or Average 0.181823E+10      
Minimum of Months 0.00 0.00   -4.0
Maximum of Months 0.807429E+09 13424.27   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.373637E+09 17672.33 04-JAN-05:11 2.00
February 0.166827E+09 16948.73 27-FEB-05:11 6.00
March 63444766.61 16062.25 06-MAR-06:02 4.00
April 0.00 0.00 01-APR-00:10 4.23
May 1723846.36 10716.06 05-MAY-05:02 6.00
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 8442996.63 11788.85 28-OCT-05:02 7.00
November 0.194427E+09 17393.80 27-NOV-05:12 4.00
December 0.841712E+09 18587.00 26-DEC-05:11 1.97
         
Annual Sum or Average 0.165021E+10      
Minimum of Months 0.00 0.00   1.97
Maximum of Months 0.841712E+09 18587.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.270803E+09 11495.76 10-JAN-05:01 -4.0
February 0.102150E+09 10861.57 13-FEB-05:01 -1.0
March 20124193.06 10033.51 04-MAR-06:02 3.00
April 0.00 0.00 01-APR-00:10 4.23
May 482853.28 4023.78 05-MAY-05:02 6.00
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 1699257.20 4776.06 28-OCT-05:02 7.00
November 0.122578E+09 11325.29 29-NOV-05:01 -0.2
December 0.466506E+09 12237.45 26-DEC-05:11 1.97
         
Annual Sum or Average 0.984344E+09      
Minimum of Months 0.00 0.00   -4.0
Maximum of Months 0.466506E+09 12237.45   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355047E+10 11536.66 02-JAN-04:01 1.17
February 0.239059E+10 11485.63 27-FEB-05:11 6.00
March 0.144019E+10 11072.44 06-MAR-05:11 3.87
April 0.210502E+09 9571.06 11-APR-04:12 6.00
May 84845331.93 9897.15 05-MAY-04:12 5.33
June 2071005.78 6500.68 07-JUN-05:03 6.33
July 736401.46 4524.59 31-JUL-05:03 7.50
August 0.00 0.00 01-AUG-00:10 11.43
September 33141091.79 9342.37 18-SEP-05:02 12.00
October 0.808780E+09 10563.35 23-OCT-04:11 3.00
November 0.218471E+10 11497.20 20-NOV-04:21 1.50
December 0.430670E+10 11883.07 26-DEC-05:21 1.95
         
Annual Sum or Average 0.150127E+11      
Minimum of Months 0.00 0.00   1.17
Maximum of Months 0.430670E+10 11883.07   12.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.198345E+10 16626.90 09-JAN-04:01 -1.9
February 0.130009E+10 16413.05 27-FEB-05:11 6.00
March 0.835319E+09 16049.65 06-MAR-05:11 3.87
April 68433761.46 13048.16 01-APR-05:02 2.17
May 33031293.91 13853.01 05-MAY-04:12 5.33
June 668881.89 3710.32 07-JUN-05:03 6.33
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 6335720.12 6336.98 18-SEP-05:02 12.00
October 0.446293E+09 14900.50 23-OCT-04:11 3.00
November 0.125841E+10 16573.01 27-NOV-05:21 4.00
December 0.262463E+10 17222.95 26-DEC-05:21 1.95
         
Annual Sum or Average 0.855666E+10      
Minimum of Months 0.00 0.00   -1.9
Maximum of Months 0.262463E+10 17222.95   12.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207796E+10 24597.99 09-JAN-04:01 -1.9
February 0.139024E+10 24317.76 27-FEB-05:11 6.00
March 0.107950E+10 23768.24 06-MAR-05:11 3.87
April 0.108062E+09 19416.83 11-APR-05:02 5.83
May 97708063.06 20613.29 05-MAY-04:12 5.33
June 4070550.91 14625.36 08-JUN-05:02 6.17
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 2036944.57 5048.29 07-SEP-05:03 8.83
October 0.497855E+09 21385.33 30-OCT-04:11 7.00
November 0.138524E+10 24682.42 27-NOV-05:21 4.00
December 0.314415E+10 25421.09 26-DEC-05:21 1.95
         
Annual Sum or Average 0.978681E+10      
Minimum of Months 0.00 0.00   -1.9
Maximum of Months 0.314415E+10 25421.09   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138244E+10 16923.35 02-JAN-04:01 1.17
February 0.768198E+09 15905.34 27-FEB-05:11 6.00
March 0.458588E+09 15217.01 06-MAR-05:11 3.87
April 24784990.55 12238.18 01-APR-05:02 2.17
May 27192737.46 12924.85 16-MAY-05:02 6.33
June 80690.96 672.42 08-JUN-05:02 6.17
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 1029404.38 3888.82 07-SEP-05:03 8.83
October 0.231627E+09 14207.84 30-OCT-04:11 7.00
November 0.778488E+09 16503.42 27-NOV-05:21 4.00
December 0.173309E+10 17253.66 26-DEC-05:21 1.95
         
Annual Sum or Average 0.540552E+10      
Minimum of Months 0.00 0.00   1.17
Maximum of Months 0.173309E+10 17253.66   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.169032E+09 8031.62 17-JAN-05:11 6.00
February 75094121.99 10575.22 19-FEB-14:53 6.00
March 51967695.41 8618.11 06-MAR-05:11 3.87
April 0.120739E+09 12582.88 30-APR-14:21 23.50
May 98730549.91 8510.49 21-MAY-14:42 18.67
June 96312305.38 11546.77 25-JUN-16:21 23.00
July 0.132589E+09 10471.78 23-JUL-16:01 21.83
August 0.127596E+09 10557.77 20-AUG-14:42 23.00
September 94721497.11 10351.97 10-SEP-15:22 21.50
October 65606665.72 8451.15 30-OCT-04:11 7.00
November 68109726.71 9606.88 20-NOV-05:01 0.67
December 65757247.54 11080.80 26-DEC-05:11 1.97
         
Annual Sum or Average 0.116626E+10      
Minimum of Months 51967695.41 8031.62   0.67
Maximum of Months 0.169032E+09 12582.88   23.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135325E+10 12104.14 15-JAN-13:02 9.83
February 0.107649E+10 11112.24 19-FEB-13:13 6.00
March 0.794115E+09 5515.04 23-MAR-05:02 6.67
April 60238311.07 12470.21 30-APR-14:32 23.67
May 84760566.58 10486.16 21-MAY-16:31 19.33
June 56513499.45 9450.98 11-JUN-14:41 17.17
July 91372117.72 11644.59 30-JUL-15:31 16.33
August 71356523.91 10960.11 20-AUG-15:22 23.50
September 82863981.74 11393.22 24-SEP-15:02 22.00
October 0.329810E+09 8531.70 01-OCT-15:02 12.83
November 0.904819E+09 9273.82 11-NOV-13:02 9.00
December 0.150280E+10 4628.14 18-DEC-13:35 8.00
         
Annual Sum or Average 0.640839E+10      
Minimum of Months 56513499.45 4628.14   6.00
Maximum of Months 0.150280E+10 12470.21   23.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.538052E+10 20556.62 09-JAN-06:13 -2.0
February 0.386619E+10 17037.23 13-FEB-06:13 -1.0
March 0.315667E+10 14440.63 06-MAR-06:02 4.00
April 0.116681E+10 7938.29 30-APR-07:32 16.93
May 0.932300E+09 13548.84 24-MAY-05:02 8.42
June 0.396079E+09 12116.71 16-JUN-05:02 10.33
July 0.319928E+09 11440.79 21-JUL-05:03 11.83
August 0.486206E+09 12020.26 01-AUG-05:02 13.00
September 0.845911E+09 11708.15 12-SEP-05:03 11.83
October 0.235252E+10 10049.57 23-OCT-05:03 3.17
November 0.397623E+10 18273.63 27-NOV-06:13 4.00
December 0.633985E+10 22249.32 26-DEC-06:12 1.93
         
Annual Sum or Average 0.292192E+11      
Minimum of Months 0.319928E+09 7938.29   -2.0
Maximum of Months 0.633985E+10 22249.32   16.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 52170716.85 423.04 02-JAN-04:55 1.00
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 52170716.85      
Minimum of Months 0.00 0.00   1.00
Maximum of Months 52170716.85 423.04   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.691697E+09 580.91 08-JAN-18:10 -1.0
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 1902665.44 400.46 15-MAY-04:50 7.17
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 866823.46 370.23 17-SEP-04:35 7.67
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.694467E+09      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 0.691697E+09 580.91   11.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:10 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.968216E+10 10174.14 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.878253E+10 10174.14 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.104353E+11 10174.14 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.932187E+10 10174.14 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.100587E+11 10174.14 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.100099E+11 10174.14 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.937071E+10 10174.14 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.104353E+11 10174.14 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.932187E+10 10174.14 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.968216E+10 10174.14 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.956821E+10 10174.14 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.937071E+10 10174.14 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.116039E+12     0.424397E+12    
Minimum of Months 0.878253E+10 10174.14   0.325565E+11 13457.54  
Maximum of Months 0.104353E+11 10174.14   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.869526E+10 9137.09 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.788732E+10 9137.09 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.937162E+10 9137.09 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.837170E+10 9137.09 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.903344E+10 9137.09 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.898958E+10 9137.09 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.841555E+10 9137.09 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.937162E+10 9137.09 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.837170E+10 9137.09 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.869526E+10 9137.09 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.859292E+10 9137.09 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.841555E+10 9137.09 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.104212E+12     0.289614E+12    
Minimum of Months 0.788732E+10 9137.09   0.220609E+11 17206.63  
Maximum of Months 0.937162E+10 9137.09   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.869526E+10 9137.09 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.788732E+10 9137.09 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.937162E+10 9137.09 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.837170E+10 9137.09 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.903344E+10 9137.09 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.898958E+10 9137.09 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.841555E+10 9137.09 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.937162E+10 9137.09 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.837170E+10 9137.09 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.869526E+10 9137.09 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.859292E+10 9137.09 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.841555E+10 9137.09 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.104212E+12     0.289613E+12    
Minimum of Months 0.788732E+10 9137.09   0.220609E+11 17206.56  
Maximum of Months 0.937162E+10 9137.09   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.869526E+10 9137.09 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.788732E+10 9137.09 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.937162E+10 9137.09 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.837170E+10 9137.09 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.903344E+10 9137.09 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.898958E+10 9137.09 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.841555E+10 9137.09 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.937162E+10 9137.09 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.837170E+10 9137.09 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.869526E+10 9137.09 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.859292E+10 9137.09 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.841555E+10 9137.09 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.104212E+12     0.289613E+12    
Minimum of Months 0.788732E+10 9137.09   0.220609E+11 17206.56  
Maximum of Months 0.937162E+10 9137.09   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.756052E+09 1147.25 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.615792E+09 1077.10 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.673995E+09 957.38 15-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.571792E+09 805.23 10-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.595566E+09 545.86 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.585043E+09 545.86 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.551581E+09 545.86 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.628289E+09 631.46 22-AUG-07:30 0.318369E+10 2160.55 01-AUG-07:10
September 0.586375E+09 643.09 08-SEP-07:30 0.295328E+10 2160.55 01-SEP-07:10
October 0.670965E+09 1140.87 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.742109E+09 1147.25 06-NOV-16:49 0.299314E+10 2160.55 01-NOV-07:10
December 0.784635E+09 1147.25 01-DEC-15:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.776219E+10     0.363654E+11    
Minimum of Months 0.551581E+09 545.86   0.277008E+10 2160.55  
Maximum of Months 0.784635E+09 1147.25   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.473686E+09 739.33 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.390038E+09 690.32 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.432211E+09 594.04 15-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.368342E+09 481.39 10-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.385154E+09 351.77 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.378594E+09 351.77 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.356970E+09 351.77 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.405060E+09 395.86 22-AUG-07:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.376026E+09 405.24 08-SEP-07:30 0.190321E+10 1392.34 01-SEP-07:10
October 0.426092E+09 734.96 31-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.468514E+09 739.33 06-NOV-16:49 0.192889E+10 1392.34 01-NOV-07:10
December 0.489192E+09 739.33 01-DEC-15:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.494988E+10     0.234352E+11    
Minimum of Months 0.356970E+09 351.77   0.178515E+10 1392.34  
Maximum of Months 0.489192E+09 739.33   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.722772E+09 1147.28 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.599801E+09 1073.72 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.668155E+09 948.51 15-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.572619E+09 799.59 10-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.597832E+09 545.88 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.587275E+09 545.88 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.554259E+09 545.88 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.630025E+09 630.19 22-AUG-07:30 0.318374E+10 2160.58 01-AUG-07:10
September 0.584976E+09 639.45 08-SEP-07:30 0.295333E+10 2160.58 01-SEP-07:10
October 0.657172E+09 1140.63 31-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.715305E+09 1147.28 06-NOV-16:49 0.299318E+10 2160.58 01-NOV-07:10
December 0.748389E+09 1147.28 01-DEC-15:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.763858E+10     0.363660E+11    
Minimum of Months 0.554259E+09 545.88   0.277013E+10 2160.58  
Maximum of Months 0.748389E+09 1147.28   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.477508E+09 739.33 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.391766E+09 694.51 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.433422E+09 626.20 15-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.368495E+09 534.91 10-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.384208E+09 386.54 04-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.377129E+09 351.77 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.355962E+09 381.80 07-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.405585E+09 410.95 22-AUG-07:30 0.205168E+10 1392.33 01-AUG-07:10
September 0.377913E+09 536.12 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.428895E+09 735.22 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.469088E+09 739.33 06-NOV-16:49 0.192888E+10 1392.33 01-NOV-07:10
December 0.496159E+09 739.33 01-DEC-15:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.496613E+10     0.234351E+11    
Minimum of Months 0.355962E+09 351.77   0.178514E+10 1392.33  
Maximum of Months 0.496159E+09 739.33   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.753738E+09 1147.25 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.613897E+09 1076.36 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.672707E+09 955.29 15-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.571546E+09 801.41 10-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.595402E+09 545.86 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.584868E+09 545.86 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.551471E+09 545.86 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.627789E+09 627.23 22-AUG-07:30 0.318369E+10 2160.55 01-AUG-07:10
September 0.585749E+09 639.53 08-SEP-07:30 0.295328E+10 2160.55 01-SEP-07:10
October 0.669172E+09 1140.80 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.739770E+09 1147.25 06-NOV-16:49 0.299314E+10 2160.55 01-NOV-07:10
December 0.782237E+09 1147.25 01-DEC-15:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.774835E+10     0.363654E+11    
Minimum of Months 0.551471E+09 545.86   0.277008E+10 2160.55  
Maximum of Months 0.782237E+09 1147.25   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.472770E+09 739.33 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.389394E+09 689.12 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.431567E+09 590.84 15-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.368259E+09 475.97 10-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.384955E+09 351.77 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.378404E+09 351.77 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.356818E+09 351.77 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.404803E+09 392.93 22-AUG-07:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.375808E+09 402.77 08-SEP-07:30 0.190321E+10 1392.34 01-SEP-07:10
October 0.425295E+09 734.85 31-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.467184E+09 739.33 06-NOV-16:49 0.192889E+10 1392.34 01-NOV-07:10
December 0.487762E+09 739.33 01-DEC-15:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.494302E+10     0.234352E+11    
Minimum of Months 0.356818E+09 351.77   0.178515E+10 1392.34  
Maximum of Months 0.487762E+09 739.33   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.722041E+09 1147.28 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.598725E+09 1072.98 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.667434E+09 946.38 15-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.572396E+09 795.72 10-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.597573E+09 545.88 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.587049E+09 545.88 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.553971E+09 545.88 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.629641E+09 625.90 22-AUG-07:30 0.318374E+10 2160.58 01-AUG-07:10
September 0.584560E+09 635.71 08-SEP-07:30 0.295333E+10 2160.58 01-SEP-07:10
October 0.656541E+09 1140.56 31-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.714083E+09 1147.28 06-NOV-16:49 0.299318E+10 2160.58 01-NOV-07:10
December 0.747407E+09 1147.28 01-DEC-15:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.763142E+10     0.363660E+11    
Minimum of Months 0.553971E+09 545.88   0.277013E+10 2160.58  
Maximum of Months 0.747407E+09 1147.28   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.476633E+09 739.33 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.390906E+09 693.35 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.432634E+09 623.26 15-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.368321E+09 529.58 10-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.383995E+09 382.75 04-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.376978E+09 351.77 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.355843E+09 377.75 07-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.405330E+09 408.53 22-AUG-07:30 0.205168E+10 1392.33 01-AUG-07:10
September 0.377716E+09 530.41 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.427727E+09 735.11 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.467918E+09 739.33 06-NOV-16:49 0.192888E+10 1392.33 01-NOV-07:10
December 0.494753E+09 739.33 01-DEC-15:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.495875E+10     0.234351E+11    
Minimum of Months 0.355843E+09 351.77   0.178514E+10 1392.33  
Maximum of Months 0.494753E+09 739.33   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.753650E+09 1147.25 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.613820E+09 1076.21 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.672665E+09 954.91 15-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.571538E+09 800.70 10-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.595390E+09 545.86 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.584857E+09 545.86 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.551458E+09 545.86 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.627779E+09 627.06 22-AUG-07:30 0.318369E+10 2160.55 01-AUG-07:10
September 0.585736E+09 639.38 08-SEP-07:30 0.295328E+10 2160.55 01-SEP-07:10
October 0.669054E+09 1140.79 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.739592E+09 1147.25 06-NOV-16:49 0.299314E+10 2160.55 01-NOV-07:10
December 0.782136E+09 1147.25 01-DEC-15:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.774767E+10     0.363654E+11    
Minimum of Months 0.551458E+09 545.86   0.277008E+10 2160.55  
Maximum of Months 0.782136E+09 1147.25   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.472715E+09 739.33 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.389372E+09 689.02 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.431540E+09 590.57 15-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.368253E+09 475.48 10-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.384949E+09 351.77 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.378385E+09 351.77 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.356809E+09 351.77 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.404794E+09 392.79 22-AUG-07:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.375803E+09 402.66 08-SEP-07:30 0.190321E+10 1392.34 01-SEP-07:10
October 0.425267E+09 734.84 31-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.467088E+09 739.33 06-NOV-16:49 0.192889E+10 1392.34 01-NOV-07:10
December 0.487695E+09 739.33 01-DEC-15:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.494267E+10     0.234352E+11    
Minimum of Months 0.356809E+09 351.77   0.178515E+10 1392.34  
Maximum of Months 0.487695E+09 739.33   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.722013E+09 1147.28 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.598700E+09 1072.82 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.667399E+09 945.98 15-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.572365E+09 795.00 10-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.597565E+09 545.88 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.587028E+09 545.88 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.553964E+09 545.88 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.629629E+09 625.73 22-AUG-07:30 0.318374E+10 2160.58 01-AUG-07:10
September 0.584550E+09 635.56 08-SEP-07:30 0.295333E+10 2160.58 01-SEP-07:10
October 0.656487E+09 1140.54 31-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.714005E+09 1147.28 06-NOV-16:49 0.299318E+10 2160.58 01-NOV-07:10
December 0.747288E+09 1147.28 01-DEC-15:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.763099E+10     0.363660E+11    
Minimum of Months 0.553964E+09 545.88   0.277013E+10 2160.58  
Maximum of Months 0.747288E+09 1147.28   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.476569E+09 739.33 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.390882E+09 693.26 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.432609E+09 623.02 15-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.368316E+09 529.15 10-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.383989E+09 382.60 04-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.376969E+09 351.77 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.355840E+09 377.59 07-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.405315E+09 408.44 22-AUG-07:30 0.205168E+10 1392.33 01-AUG-07:10
September 0.377710E+09 530.07 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.427687E+09 735.11 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.467787E+09 739.33 06-NOV-16:49 0.192888E+10 1392.33 01-NOV-07:10
December 0.494707E+09 739.33 01-DEC-15:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.495838E+10     0.234351E+11    
Minimum of Months 0.355840E+09 351.77   0.178514E+10 1392.33  
Maximum of Months 0.494707E+09 739.33   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.139824E+09 146.32 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.126830E+09 146.32 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.150710E+09 146.32 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.134615E+09 146.32 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.145267E+09 146.32 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.144564E+09 146.32 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.135317E+09 146.32 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.150710E+09 146.32 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.134615E+09 146.32 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.139824E+09 146.32 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.138185E+09 146.32 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.135317E+09 146.32 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.167578E+10     0.153881E+12    
Minimum of Months 0.126830E+09 146.32   0.505780E+10 1948.61  
Maximum of Months 0.150710E+09 146.32   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.139824E+09 146.32 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.126830E+09 146.32 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.150710E+09 146.32 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.134615E+09 146.32 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.145267E+09 146.32 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.144564E+09 146.32 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.135317E+09 146.32 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.150710E+09 146.32 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.134615E+09 146.32 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.139824E+09 146.32 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.138185E+09 146.32 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.135317E+09 146.32 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.167578E+10     0.153881E+12    
Minimum of Months 0.126830E+09 146.32   0.505780E+10 1948.61  
Maximum of Months 0.150710E+09 146.32   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.139824E+09 146.32 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.126830E+09 146.32 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.150710E+09 146.32 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.134615E+09 146.32 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.145267E+09 146.32 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.144564E+09 146.32 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.135317E+09 146.32 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.150710E+09 146.32 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.134615E+09 146.32 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.139824E+09 146.32 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.138185E+09 146.32 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.135317E+09 146.32 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.167578E+10     0.153881E+12    
Minimum of Months 0.126830E+09 146.32   0.505780E+10 1948.61  
Maximum of Months 0.150710E+09 146.32   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.274130E+10 2868.67 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.248656E+10 2868.67 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.295472E+10 2868.67 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.263917E+10 2868.67 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.284801E+10 2868.67 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.283424E+10 2868.67 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.265294E+10 2868.67 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.295472E+10 2868.67 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.263917E+10 2868.67 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.274130E+10 2868.67 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.270917E+10 2868.67 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.265294E+10 2868.67 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.328542E+11     0.749486E+13    
Minimum of Months 0.248656E+10 2868.67   0.246344E+12 94908.13  
Maximum of Months 0.295472E+10 2868.67   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.968216E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.878253E+10 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.104353E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.932187E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.100587E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.100099E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.937071E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.104353E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.932187E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.968216E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.956821E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.937071E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.116039E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.878253E+10 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.104353E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.869526E+10 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.937162E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.837170E+10 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.903344E+10 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.898958E+10 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.841555E+10 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.937162E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.837170E+10 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.869526E+10 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.859292E+10 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.841555E+10 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.104212E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.937162E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.869526E+10 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.837170E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.903344E+10 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.898958E+10 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.841555E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.837170E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.869526E+10 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.859292E+10 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.841555E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.104212E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.869526E+10 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.837170E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.903344E+10 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.898958E+10 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.841555E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.837170E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.869526E+10 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.859292E+10 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.841555E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.104212E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.756052E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.223689E+09
February 0.136985E+10 0.615792E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.315212E+09
March 0.163685E+10 0.673995E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.187554E+09
April 0.145243E+10 0.571792E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.233607E+09
May 0.157338E+10 0.595566E+09 0.312174E+10 0.00 0.00 0.00 0.00 3.44 0.555058E+09
June 0.156900E+10 0.585043E+09 0.306580E+10 0.00 0.00 0.00 0.00 249700.23 0.427268E+09
July 0.145680E+10 0.551581E+09 0.300989E+10 0.00 0.00 0.00 0.00 1155374.21 0.414205E+09
August 0.163685E+10 0.628289E+09 0.318369E+10 0.00 0.00 0.00 0.00 161239.12 0.298632E+09
September 0.145243E+10 0.586375E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.00 0.311584E+09
October 0.150991E+10 0.670965E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.339740E+09
November 0.149516E+10 0.742109E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.419890E+09
December 0.145680E+10 0.784635E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.575241E+09
                   
Annual Sum or Average 0.181194E+11 0.776219E+10 0.363654E+11 0.00 0.00 0.00 0.00 1566317.01 0.430168E+10
Minimum of Months 0.136985E+10 0.551581E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.187554E+09
Maximum of Months 0.163685E+10 0.784635E+09 0.318369E+10 0.00 0.00 0.00 0.00 1155374.21 0.575241E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.473686E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.149744E+09
February 0.882782E+09 0.390038E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.209091E+09
March 0.105485E+10 0.432211E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.123646E+09
April 0.936002E+09 0.368342E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.155690E+09
May 0.101394E+10 0.385154E+09 0.201177E+10 0.00 0.00 0.00 0.00 2.28 0.374235E+09
June 0.101113E+10 0.378594E+09 0.197572E+10 0.00 0.00 0.00 0.00 166478.33 0.284660E+09
July 0.938820E+09 0.356970E+09 0.193969E+10 0.00 0.00 0.00 0.00 790831.85 0.276519E+09
August 0.105485E+10 0.405060E+09 0.205169E+10 0.00 0.00 0.00 0.00 107435.97 0.198599E+09
September 0.936002E+09 0.376026E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.00 0.213971E+09
October 0.973041E+09 0.426092E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.225353E+09
November 0.963541E+09 0.468514E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.275017E+09
December 0.938820E+09 0.489192E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.372573E+09
                   
Annual Sum or Average 0.116768E+11 0.494988E+10 0.234352E+11 0.00 0.00 0.00 0.00 1064748.44 0.285910E+10
Minimum of Months 0.882782E+09 0.356970E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.123646E+09
Maximum of Months 0.105485E+10 0.489192E+09 0.205169E+10 0.00 0.00 0.00 0.00 790831.85 0.374235E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.722772E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.224481E+09
February 0.136988E+10 0.599801E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.314968E+09
March 0.163688E+10 0.668155E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.183881E+09
April 0.145246E+10 0.572619E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.237041E+09
May 0.157341E+10 0.597832E+09 0.312179E+10 0.00 0.00 0.00 0.00 3.40 0.558253E+09
June 0.156904E+10 0.587275E+09 0.306585E+10 0.00 0.00 0.00 0.00 249713.92 0.428412E+09
July 0.145684E+10 0.554259E+09 0.300994E+10 0.00 0.00 0.00 0.00 1115291.69 0.418760E+09
August 0.163688E+10 0.630025E+09 0.318374E+10 0.00 0.00 0.00 0.00 160565.51 0.307204E+09
September 0.145246E+10 0.584976E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.00 0.324838E+09
October 0.150994E+10 0.657172E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.341909E+09
November 0.149520E+10 0.715305E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.414124E+09
December 0.145684E+10 0.748389E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.556465E+09
                   
Annual Sum or Average 0.181198E+11 0.763858E+10 0.363660E+11 0.00 0.00 0.00 0.00 1525574.52 0.431034E+10
Minimum of Months 0.136988E+10 0.554259E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.183881E+09
Maximum of Months 0.163688E+10 0.748389E+09 0.318374E+10 0.00 0.00 0.00 0.00 1115291.69 0.558253E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.477508E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.157974E+09
February 0.882782E+09 0.391766E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.227985E+09
March 0.105485E+10 0.433422E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.134931E+09
April 0.936002E+09 0.368495E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.173623E+09
May 0.101394E+10 0.384208E+09 0.201175E+10 0.00 0.00 0.00 0.00 2.34 0.398335E+09
June 0.101113E+10 0.377129E+09 0.197570E+10 0.00 0.00 0.00 0.00 166427.52 0.314338E+09
July 0.938820E+09 0.355962E+09 0.193968E+10 0.00 0.00 0.00 0.00 657046.34 0.314602E+09
August 0.105485E+10 0.405585E+09 0.205168E+10 0.00 0.00 0.00 0.00 106736.35 0.231748E+09
September 0.936002E+09 0.377913E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.00 0.227896E+09
October 0.973041E+09 0.428895E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.248302E+09
November 0.963541E+09 0.469088E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.309085E+09
December 0.938820E+09 0.496159E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.427727E+09
                   
Annual Sum or Average 0.116768E+11 0.496613E+10 0.234351E+11 0.00 0.00 0.00 0.00 930212.55 0.316655E+10
Minimum of Months 0.882782E+09 0.355962E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.134931E+09
Maximum of Months 0.105485E+10 0.496159E+09 0.205168E+10 0.00 0.00 0.00 0.00 657046.34 0.427727E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.753738E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.453753E+09
February 0.136985E+10 0.613897E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.646577E+09
March 0.163685E+10 0.672707E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.389484E+09
April 0.145243E+10 0.571546E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.499024E+09
May 0.157338E+10 0.595402E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.00 0.120942E+10
June 0.156900E+10 0.584868E+09 0.306580E+10 0.00 0.00 0.00 0.00 545992.45 0.939503E+09
July 0.145680E+10 0.551471E+09 0.300989E+10 0.00 0.00 0.00 0.00 2692306.71 0.895115E+09
August 0.163685E+10 0.627789E+09 0.318369E+10 0.00 0.00 0.00 0.00 356975.05 0.642869E+09
September 0.145243E+10 0.585749E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.00 0.666588E+09
October 0.150991E+10 0.669172E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.697279E+09
November 0.149516E+10 0.739770E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.833283E+09
December 0.145680E+10 0.782237E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.111995E+10
                   
Annual Sum or Average 0.181194E+11 0.774835E+10 0.363654E+11 0.00 0.00 0.00 0.00 3595274.21 0.899285E+10
Minimum of Months 0.136985E+10 0.551471E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.389484E+09
Maximum of Months 0.163685E+10 0.782237E+09 0.318369E+10 0.00 0.00 0.00 0.00 2692306.71 0.120942E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.472770E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.310096E+09
February 0.649041E+09 0.389394E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.442786E+09
March 0.773965E+09 0.431567E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.268339E+09
April 0.688021E+09 0.368259E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.351750E+09
May 0.744847E+09 0.384955E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.00 0.841952E+09
June 0.742030E+09 0.378404E+09 0.197572E+10 0.00 0.00 0.00 0.00 349648.51 0.647286E+09
July 0.690839E+09 0.356818E+09 0.193969E+10 0.00 0.00 0.00 0.00 1637473.25 0.630600E+09
August 0.773965E+09 0.404803E+09 0.205169E+10 0.00 0.00 0.00 0.00 237801.39 0.456758E+09
September 0.688021E+09 0.375808E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.00 0.482090E+09
October 0.715730E+09 0.425295E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.484133E+09
November 0.708685E+09 0.467184E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.566482E+09
December 0.690839E+09 0.487762E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.750767E+09
                   
Annual Sum or Average 0.858171E+10 0.494302E+10 0.234352E+11 0.00 0.00 0.00 0.00 2224923.16 0.623304E+10
Minimum of Months 0.649041E+09 0.356818E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.268339E+09
Maximum of Months 0.773965E+09 0.487762E+09 0.205169E+10 0.00 0.00 0.00 0.00 1637473.25 0.841952E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.722041E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.498251E+09
February 0.136988E+10 0.598725E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.702389E+09
March 0.163688E+10 0.667434E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.408518E+09
April 0.145246E+10 0.572396E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.537334E+09
May 0.157341E+10 0.597573E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.00 0.126414E+10
June 0.156904E+10 0.587049E+09 0.306585E+10 0.00 0.00 0.00 0.00 546201.67 0.965252E+09
July 0.145684E+10 0.553971E+09 0.300994E+10 0.00 0.00 0.00 0.00 2516974.67 0.940691E+09
August 0.163688E+10 0.629641E+09 0.318374E+10 0.00 0.00 0.00 0.00 356970.52 0.695405E+09
September 0.145246E+10 0.584560E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.00 0.741575E+09
October 0.150994E+10 0.656541E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.763180E+09
November 0.149520E+10 0.714083E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.896725E+09
December 0.145684E+10 0.747407E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.117388E+10
                   
Annual Sum or Average 0.181198E+11 0.763142E+10 0.363660E+11 0.00 0.00 0.00 0.00 3420146.86 0.958734E+10
Minimum of Months 0.136988E+10 0.553971E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.408518E+09
Maximum of Months 0.163688E+10 0.747407E+09 0.318374E+10 0.00 0.00 0.00 0.00 2516974.67 0.126414E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.476633E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.316599E+09
February 0.882782E+09 0.390906E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.455473E+09
March 0.105485E+10 0.432634E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.270692E+09
April 0.936002E+09 0.368321E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.358062E+09
May 0.101394E+10 0.383995E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.00 0.868075E+09
June 0.101113E+10 0.376978E+09 0.197570E+10 0.00 0.00 0.00 0.00 364101.97 0.674744E+09
July 0.938820E+09 0.355843E+09 0.193968E+10 0.00 0.00 0.00 0.00 1472805.10 0.659384E+09
August 0.105485E+10 0.405330E+09 0.205168E+10 0.00 0.00 0.00 0.00 237961.73 0.477712E+09
September 0.936002E+09 0.377716E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.00 0.486644E+09
October 0.973041E+09 0.427727E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.497124E+09
November 0.963541E+09 0.467918E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.580745E+09
December 0.938820E+09 0.494753E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.772459E+09
                   
Annual Sum or Average 0.116768E+11 0.495875E+10 0.234351E+11 0.00 0.00 0.00 0.00 2074868.80 0.641771E+10
Minimum of Months 0.882782E+09 0.355843E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.270692E+09
Maximum of Months 0.105485E+10 0.494753E+09 0.205168E+10 0.00 0.00 0.00 0.00 1472805.10 0.868075E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.753650E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.509525E+09
February 0.136985E+10 0.613820E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.724389E+09
March 0.163685E+10 0.672665E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.442829E+09
April 0.145243E+10 0.571538E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.580155E+09
May 0.157338E+10 0.595390E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.00 0.141740E+10
June 0.156900E+10 0.584857E+09 0.306580E+10 0.00 0.00 0.00 0.00 629987.61 0.112759E+10
July 0.145680E+10 0.551458E+09 0.300989E+10 0.00 0.00 0.00 0.00 3005498.72 0.107491E+10
August 0.163685E+10 0.627779E+09 0.318369E+10 0.00 0.00 0.00 0.00 415507.97 0.772020E+09
September 0.145243E+10 0.585736E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.00 0.767801E+09
October 0.150991E+10 0.669054E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.773648E+09
November 0.149516E+10 0.739592E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.925028E+09
December 0.145680E+10 0.782136E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.126816E+10
                   
Annual Sum or Average 0.181194E+11 0.774767E+10 0.363654E+11 0.00 0.00 0.00 0.00 4050994.31 0.103835E+11
Minimum of Months 0.136985E+10 0.551458E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.442829E+09
Maximum of Months 0.163685E+10 0.782136E+09 0.318369E+10 0.00 0.00 0.00 0.00 3005498.72 0.141740E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.472715E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.344654E+09
February 0.882782E+09 0.389372E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.494481E+09
March 0.105485E+10 0.431540E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.303593E+09
April 0.936002E+09 0.368253E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.412753E+09
May 0.101394E+10 0.384949E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.00 0.994860E+09
June 0.101113E+10 0.378385E+09 0.197572E+10 0.00 0.00 0.00 0.00 420025.31 0.779516E+09
July 0.938820E+09 0.356809E+09 0.193969E+10 0.00 0.00 0.00 0.00 1949928.91 0.760418E+09
August 0.105485E+10 0.404794E+09 0.205169E+10 0.00 0.00 0.00 0.00 277002.97 0.551022E+09
September 0.936002E+09 0.375803E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.00 0.563755E+09
October 0.973041E+09 0.425267E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.539615E+09
November 0.963541E+09 0.467088E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.626283E+09
December 0.938820E+09 0.487695E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.849334E+09
                   
Annual Sum or Average 0.116768E+11 0.494267E+10 0.234352E+11 0.00 0.00 0.00 0.00 2646957.19 0.722028E+10
Minimum of Months 0.882782E+09 0.356809E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.303593E+09
Maximum of Months 0.105485E+10 0.487695E+09 0.205169E+10 0.00 0.00 0.00 0.00 1949928.91 0.994860E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.722013E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.554397E+09
February 0.136988E+10 0.598700E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.792121E+09
March 0.163688E+10 0.667399E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.468099E+09
April 0.145246E+10 0.572365E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.634420E+09
May 0.157341E+10 0.597565E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.00 0.149520E+10
June 0.156904E+10 0.587028E+09 0.306585E+10 0.00 0.00 0.00 0.00 630029.28 0.116142E+10
July 0.145684E+10 0.553964E+09 0.300994E+10 0.00 0.00 0.00 0.00 2828139.47 0.113349E+10
August 0.163688E+10 0.629629E+09 0.318374E+10 0.00 0.00 0.00 0.00 415505.97 0.840263E+09
September 0.145246E+10 0.584550E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.00 0.872047E+09
October 0.150994E+10 0.656487E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.863944E+09
November 0.149520E+10 0.714005E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.999268E+09
December 0.145684E+10 0.747288E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.131830E+10
                   
Annual Sum or Average 0.181198E+11 0.763099E+10 0.363660E+11 0.00 0.00 0.00 0.00 3873674.73 0.111330E+11
Minimum of Months 0.136988E+10 0.553964E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.468099E+09
Maximum of Months 0.163688E+10 0.747288E+09 0.318374E+10 0.00 0.00 0.00 0.00 2828139.47 0.149520E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.476569E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.357469E+09
February 0.882782E+09 0.390882E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.521230E+09
March 0.105485E+10 0.432609E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.313140E+09
April 0.936002E+09 0.368316E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.423630E+09
May 0.101394E+10 0.383989E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.00 0.103355E+10
June 0.101113E+10 0.376969E+09 0.197570E+10 0.00 0.00 0.00 0.00 419967.92 0.816027E+09
July 0.938820E+09 0.355840E+09 0.193968E+10 0.00 0.00 0.00 0.00 1740601.84 0.797906E+09
August 0.105485E+10 0.405315E+09 0.205168E+10 0.00 0.00 0.00 0.00 276969.08 0.578692E+09
September 0.936002E+09 0.377710E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.00 0.572848E+09
October 0.973041E+09 0.427687E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.566365E+09
November 0.963541E+09 0.467787E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.657120E+09
December 0.938820E+09 0.494707E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.883065E+09
                   
Annual Sum or Average 0.116768E+11 0.495838E+10 0.234351E+11 0.00 0.00 0.00 0.00 2437538.84 0.752104E+10
Minimum of Months 0.882782E+09 0.355840E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.313140E+09
Maximum of Months 0.105485E+10 0.494707E+09 0.205168E+10 0.00 0.00 0.00 0.00 1740601.84 0.103355E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.139824E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.126830E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.150710E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.134615E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.145267E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.144564E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.135317E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.150710E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.134615E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.139824E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.138185E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.135317E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.167578E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.126830E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.150710E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.139824E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.126830E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.150710E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.134615E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.145267E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.144564E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.135317E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.150710E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.134615E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.139824E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.138185E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.135317E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.167578E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.126830E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.150710E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.139824E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.126830E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.150710E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.134615E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.145267E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.144564E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.135317E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.150710E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.134615E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.139824E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.138185E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.135317E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.167578E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.126830E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.150710E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.274130E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.248656E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.295472E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.263917E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.284801E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.283424E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.265294E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.295472E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.263917E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.274130E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.270917E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.265294E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.328542E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.248656E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.295472E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.481427E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.675924E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.392915E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.490995E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.117188E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 293185.63 0.893742E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2006628.53 0.867170E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 196515.53 0.636616E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.671491E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.726386E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.904366E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.123448E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2496329.69 0.914739E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.392915E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2006628.53 0.123448E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.793736E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.113931E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.665544E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.847113E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.204796E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 551851.94 0.156263E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3760095.23 0.149807E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 389972.27 0.110239E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.116904E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.123752E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.149854E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.198631E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4701919.45 0.155482E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.665544E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3760095.23 0.204796E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.782840E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.113278E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.691477E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.937302E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.225085E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 174350.55 0.177285E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2424090.35 0.170693E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 214421.51 0.124005E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124870E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.123921E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.145272E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.194804E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2812862.41 0.164037E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.691477E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2424090.35 0.225085E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 10174.14 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 10174.14 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 10174.14 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 10174.14 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 10174.14 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 10174.14 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 10174.14 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 10174.14 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 10174.14 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 10174.14 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 10174.14 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 10174.14 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   10174.14   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   10174.14   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9137.09 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9137.09 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9137.09 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9137.09 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9137.09 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9137.09 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9137.09 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9137.09 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9137.09 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9137.09 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9137.09 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9137.09 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9137.09   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9137.09   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9137.09 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9137.09 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9137.09 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9137.09 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9137.09 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9137.09 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9137.09 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9137.09 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9137.09 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9137.09 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9137.09 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9137.09 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9137.09 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9137.09 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9137.09 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9137.09 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9137.09 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9137.09 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9137.09 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9137.09 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9137.09 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9137.09 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9137.09 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9137.09 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1147.25 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 740.88 08-JAN-08:00
February 2010.79 01-FEB-10:09 1077.10 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 667.89 08-FEB-22:10
March 2010.79 01-MAR-10:09 957.38 15-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 692.26 27-MAR-22:00
April 2010.79 03-APR-09:09 805.23 10-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 750.72 23-APR-22:00
May 2010.79 01-MAY-09:09 545.86 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 0.01 22-MAY-15:00 1086.03 04-MAY-23:00
June 2010.79 01-JUN-09:09 545.86 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 18.13 13-JUN-15:30 750.89 05-JUN-22:00
July 2010.79 03-JUL-09:09 545.86 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 52.90 22-JUL-17:10 748.38 30-JUL-19:00
August 2010.79 01-AUG-09:09 631.46 22-AUG-07:30 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 13.74 14-AUG-16:50 515.02 22-AUG-21:10
September 2010.79 01-SEP-09:09 643.09 08-SEP-07:30 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 674.54 06-SEP-04:00
October 2010.79 02-OCT-09:09 1140.87 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 848.78 20-OCT-22:00
November 2010.79 01-NOV-09:09 1147.25 06-NOV-16:49 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 898.37 25-NOV-05:00
December 2010.79 01-DEC-10:09 1147.25 01-DEC-15:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1332.66 02-DEC-18:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   545.86   2160.55   0.00 0.00 0.00 0.00 0.00   515.02  
Maximum of Months 2010.79   1147.25   2160.55   0.00 0.00 0.00 0.00 52.90   1332.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 739.33 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 489.86 08-JAN-08:00
February 1295.83 01-FEB-10:09 690.32 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 436.14 08-FEB-22:10
March 1295.83 01-MAR-10:09 594.04 15-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 450.09 27-MAR-22:00
April 1295.83 03-APR-09:09 481.39 10-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 483.61 23-APR-22:00
May 1295.83 01-MAY-09:09 351.77 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 22-MAY-15:00 712.28 04-MAY-23:00
June 1295.83 01-JUN-09:09 351.77 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 12.09 13-JUN-15:30 561.25 18-JUN-09:50
July 1295.83 03-JUL-09:09 351.77 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 41.08 22-JUL-18:51 494.32 30-JUL-19:00
August 1295.83 01-AUG-09:09 395.86 22-AUG-07:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 9.16 14-AUG-16:50 331.09 22-AUG-21:10
September 1295.83 01-SEP-09:09 405.24 08-SEP-07:30 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 449.43 06-SEP-04:00
October 1295.83 02-OCT-09:09 734.96 31-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 549.50 20-OCT-22:00
November 1295.83 01-NOV-09:09 739.33 06-NOV-16:49 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 576.44 25-NOV-05:00
December 1295.83 01-DEC-10:09 739.33 01-DEC-15:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 859.18 02-DEC-18:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   351.77   1392.34   0.00 0.00 0.00 0.00 0.00   331.09  
Maximum of Months 1295.83   739.33   1392.34   0.00 0.00 0.00 0.00 41.08   859.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1147.28 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 726.16 01-JAN-14:55
February 2010.83 01-FEB-10:09 1073.72 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 712.51 05-FEB-14:00
March 2010.83 01-MAR-10:09 948.51 15-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 665.34 27-MAR-22:00
April 2010.83 03-APR-09:09 799.59 10-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 721.27 23-APR-22:00
May 2010.83 01-MAY-09:09 545.88 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 0.01 22-MAY-15:00 1065.23 04-MAY-23:00
June 2010.83 01-JUN-09:09 545.88 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 18.13 13-JUN-15:30 821.18 18-JUN-12:00
July 2010.83 03-JUL-09:09 545.88 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 53.68 22-JUL-18:51 776.58 30-JUL-19:00
August 2010.83 01-AUG-09:09 630.19 22-AUG-07:30 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 13.74 14-AUG-16:50 528.39 22-AUG-21:10
September 2010.83 01-SEP-09:09 639.45 08-SEP-07:30 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 665.11 06-SEP-04:00
October 2010.83 02-OCT-09:09 1140.63 31-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 836.89 20-OCT-22:00
November 2010.83 01-NOV-09:09 1147.28 06-NOV-16:49 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 839.07 25-NOV-05:00
December 2010.83 01-DEC-10:09 1147.28 01-DEC-15:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1305.37 02-DEC-18:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   545.88   2160.58   0.00 0.00 0.00 0.00 0.00   528.39  
Maximum of Months 2010.83   1147.28   2160.58   0.00 0.00 0.00 0.00 53.68   1305.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 739.33 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 520.60 08-JAN-08:00
February 1295.83 01-FEB-10:09 694.51 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 486.78 08-FEB-22:10
March 1295.83 01-MAR-10:09 626.20 15-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 503.25 27-MAR-22:00
April 1295.83 03-APR-09:09 534.91 10-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 567.88 23-APR-22:00
May 1295.83 01-MAY-09:09 386.54 04-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 22-MAY-15:00 766.55 04-MAY-23:00
June 1295.83 01-JUN-09:09 351.77 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 12.09 13-JUN-15:30 647.35 18-JUN-16:00
July 1295.83 03-JUL-09:09 381.80 07-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 26.59 22-JUL-19:04 646.22 30-JUL-19:00
August 1295.83 01-AUG-09:09 410.95 22-AUG-07:30 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 9.14 14-AUG-16:50 396.57 18-AUG-03:00
September 1295.83 01-SEP-09:09 536.12 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 479.60 06-SEP-04:00
October 1295.83 02-OCT-09:09 735.22 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 628.14 20-OCT-22:00
November 1295.83 01-NOV-09:09 739.33 06-NOV-16:49 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 668.09 25-NOV-05:00
December 1295.83 01-DEC-10:09 739.33 01-DEC-15:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1000.97 02-DEC-18:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   351.77   1392.33   0.00 0.00 0.00 0.00 0.00   396.57  
Maximum of Months 1295.83   739.33   1392.33   0.00 0.00 0.00 0.00 26.59   1000.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1147.25 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1459.38 08-JAN-08:00
February 2010.79 01-FEB-10:09 1076.36 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1445.21 08-FEB-22:03
March 2010.79 01-MAR-10:09 955.29 15-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1443.04 27-MAR-21:03
April 2010.79 03-APR-09:09 801.41 10-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1493.60 23-APR-22:00
May 2010.79 01-MAY-09:09 545.86 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2309.22 04-MAY-23:00
June 2010.79 01-JUN-09:09 545.86 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 40.51 13-JUN-15:40 1650.88 05-JUN-21:13
July 2010.79 03-JUL-09:09 545.86 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 131.26 22-JUL-18:51 1495.27 30-JUL-18:50
August 2010.79 01-AUG-09:09 627.23 22-AUG-07:30 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 30.98 14-AUG-16:50 1098.37 22-AUG-21:10
September 2010.79 01-SEP-09:09 639.53 08-SEP-07:30 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1379.70 06-SEP-04:00
October 2010.79 02-OCT-09:09 1140.80 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1704.19 20-OCT-22:00
November 2010.79 01-NOV-09:09 1147.25 06-NOV-16:49 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1673.79 25-NOV-05:14
December 2010.79 01-DEC-10:09 1147.25 01-DEC-15:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2680.03 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   545.86   2160.55   0.00 0.00 0.00 0.00 0.00   1098.37  
Maximum of Months 2010.79   1147.25   2160.55   0.00 0.00 0.00 0.00 131.26   2680.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 739.33 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 981.94 08-JAN-08:00
February 1239.33 01-FEB-08:09 689.12 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 963.80 08-FEB-22:03
March 1239.33 01-MAR-08:09 590.84 15-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 962.53 27-MAR-21:03
April 1239.33 03-APR-07:10 475.97 10-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 999.03 23-APR-22:00
May 1239.33 01-MAY-07:10 351.77 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1533.61 04-MAY-23:00
June 1239.33 01-JUN-07:10 351.77 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 27.01 13-JUN-15:40 1339.94 18-JUN-10:10
July 1239.33 03-JUL-07:10 351.77 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 88.59 22-JUL-18:51 1073.73 30-JUL-18:50
August 1239.33 01-AUG-07:10 392.93 22-AUG-07:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 20.65 14-AUG-16:50 739.28 22-AUG-21:10
September 1239.33 01-SEP-07:10 402.77 08-SEP-07:30 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 943.10 06-SEP-04:00
October 1239.33 02-OCT-07:10 734.85 31-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1132.77 20-OCT-22:00
November 1239.33 01-NOV-07:10 739.33 06-NOV-16:49 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1137.18 25-NOV-05:12
December 1239.33 01-DEC-08:09 739.33 01-DEC-15:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1788.82 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   351.77   1392.34   0.00 0.00 0.00 0.00 0.00   739.28  
Maximum of Months 1239.33   739.33   1392.34   0.00 0.00 0.00 0.00 88.59   1788.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1147.28 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1625.44 01-JAN-14:55
February 2010.83 01-FEB-10:09 1072.98 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1639.75 05-FEB-14:00
March 2010.83 01-MAR-10:09 946.38 15-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1445.05 27-MAR-21:03
April 2010.83 03-APR-09:09 795.72 10-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1600.78 16-APR-12:20
May 2010.83 01-MAY-09:09 545.88 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2318.05 04-MAY-23:00
June 2010.83 01-JUN-09:09 545.88 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 40.51 13-JUN-15:40 1810.93 18-JUN-15:52
July 2010.83 03-JUL-09:09 545.88 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 123.71 22-JUL-18:51 1733.93 30-JUL-18:50
August 2010.83 01-AUG-09:09 625.90 22-AUG-07:30 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 30.98 14-AUG-16:50 1167.45 22-AUG-21:10
September 2010.83 01-SEP-09:09 635.71 08-SEP-07:30 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1425.62 06-SEP-04:00
October 2010.83 02-OCT-09:09 1140.56 31-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1817.70 01-OCT-24:00
November 2010.83 01-NOV-09:09 1147.28 06-NOV-16:49 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1700.99 25-NOV-05:12
December 2010.83 01-DEC-10:09 1147.28 01-DEC-15:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2771.40 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   545.88   2160.58   0.00 0.00 0.00 0.00 0.00   1167.45  
Maximum of Months 2010.83   1147.28   2160.58   0.00 0.00 0.00 0.00 123.71   2771.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 739.33 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1008.62 08-JAN-08:00
February 1295.83 01-FEB-10:09 693.35 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 978.85 08-FEB-22:03
March 1295.83 01-MAR-10:09 623.26 15-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 977.08 27-MAR-21:03
April 1295.83 03-APR-09:09 529.58 10-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1022.49 23-APR-22:00
May 1295.83 01-MAY-09:09 382.75 04-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1586.79 04-MAY-23:00
June 1295.83 01-JUN-09:09 351.77 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 27.01 13-JUN-15:40 1405.86 18-JUN-16:20
July 1295.83 03-JUL-09:09 377.75 07-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 60.88 22-JUL-19:04 1431.02 30-JUL-18:50
August 1295.83 01-AUG-09:09 408.53 22-AUG-07:30 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 20.66 14-AUG-16:50 825.28 22-AUG-21:10
September 1295.83 01-SEP-09:09 530.41 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 953.24 06-SEP-04:00
October 1295.83 02-OCT-09:09 735.11 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1206.48 20-OCT-22:00
November 1295.83 01-NOV-09:09 739.33 06-NOV-16:49 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1137.56 25-NOV-05:00
December 1295.83 01-DEC-10:09 739.33 01-DEC-15:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1841.88 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   351.77   1392.33   0.00 0.00 0.00 0.00 0.00   825.28  
Maximum of Months 1295.83   739.33   1392.33   0.00 0.00 0.00 0.00 60.88   1841.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1147.25 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1629.89 10-JAN-05:52
February 2010.79 01-FEB-10:09 1076.21 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1786.16 08-FEB-22:03
March 2010.79 01-MAR-10:09 954.91 15-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1777.90 27-MAR-21:03
April 2010.79 03-APR-09:09 800.70 10-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1621.53 23-APR-22:00
May 2010.79 01-MAY-09:09 545.86 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2632.69 04-MAY-23:00
June 2010.79 01-JUN-09:09 545.86 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 47.84 13-JUN-15:50 2004.66 05-JUN-21:03
July 2010.79 03-JUL-09:09 545.86 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 141.47 22-JUL-17:01 1832.38 30-JUL-19:00
August 2010.79 01-AUG-09:09 627.06 22-AUG-07:30 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 36.92 14-AUG-16:50 1320.30 22-AUG-21:10
September 2010.79 01-SEP-09:09 639.38 08-SEP-07:30 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1529.46 06-SEP-04:00
October 2010.79 02-OCT-09:09 1140.79 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1923.96 20-OCT-22:00
November 2010.79 01-NOV-09:09 1147.25 06-NOV-16:49 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2095.15 25-NOV-05:20
December 2010.79 01-DEC-10:09 1147.25 01-DEC-15:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3141.72 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   545.86   2160.55   0.00 0.00 0.00 0.00 0.00   1320.30  
Maximum of Months 2010.79   1147.25   2160.55   0.00 0.00 0.00 0.00 141.47   3141.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 739.33 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1106.15 10-JAN-05:52
February 1295.83 01-FEB-10:09 689.02 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1190.45 08-FEB-22:03
March 1295.83 01-MAR-10:09 590.57 15-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1184.92 27-MAR-21:03
April 1295.83 03-APR-09:09 475.48 10-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1112.59 16-APR-11:53
May 1295.83 01-MAY-09:09 351.77 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1751.19 04-MAY-23:00
June 1295.83 01-JUN-09:09 351.77 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 31.89 13-JUN-15:50 1618.12 18-JUN-10:20
July 1295.83 03-JUL-09:09 351.77 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 91.95 22-JUL-18:51 1320.35 30-JUL-19:00
August 1295.83 01-AUG-09:09 392.79 22-AUG-07:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 24.62 14-AUG-16:50 887.36 22-AUG-21:10
September 1295.83 01-SEP-09:09 402.66 08-SEP-07:30 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1052.48 06-SEP-04:00
October 1295.83 02-OCT-09:09 734.84 31-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1276.36 20-OCT-22:00
November 1295.83 01-NOV-09:09 739.33 06-NOV-16:49 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1396.79 25-NOV-05:17
December 1295.83 01-DEC-10:09 739.33 01-DEC-15:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2094.09 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   351.77   1392.34   0.00 0.00 0.00 0.00 0.00   887.36  
Maximum of Months 1295.83   739.33   1392.34   0.00 0.00 0.00 0.00 91.95   2094.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1147.28 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1663.52 10-JAN-05:52
February 2010.83 01-FEB-10:09 1072.82 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1794.77 08-FEB-22:03
March 2010.83 01-MAR-10:09 945.98 15-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1778.92 27-MAR-21:03
April 2010.83 03-APR-09:09 795.00 10-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2011.38 16-APR-12:00
May 2010.83 01-MAY-09:09 545.88 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2653.13 04-MAY-23:00
June 2010.83 01-JUN-09:09 545.88 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 47.84 13-JUN-15:50 2238.22 18-JUN-15:52
July 2010.83 03-JUL-09:09 545.88 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 126.75 22-JUL-18:51 2131.89 30-JUL-19:00
August 2010.83 01-AUG-09:09 625.73 22-AUG-07:30 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 36.93 14-AUG-16:50 1410.01 22-AUG-21:10
September 2010.83 01-SEP-09:09 635.56 08-SEP-07:30 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1593.44 06-SEP-04:00
October 2010.83 02-OCT-09:09 1140.54 31-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2014.51 01-OCT-24:00
November 2010.83 01-NOV-09:09 1147.28 06-NOV-16:49 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2095.20 25-NOV-05:19
December 2010.83 01-DEC-10:09 1147.28 01-DEC-15:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3230.90 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   545.88   2160.58   0.00 0.00 0.00 0.00 0.00   1410.01  
Maximum of Months 2010.83   1147.28   2160.58   0.00 0.00 0.00 0.00 126.75   3230.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 739.33 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1109.84 10-JAN-05:52
February 1295.83 01-FEB-10:09 693.26 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1200.53 08-FEB-22:03
March 1295.83 01-MAR-10:09 623.02 15-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1191.12 27-MAR-21:03
April 1295.83 03-APR-09:09 529.15 10-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1226.68 15-APR-17:40
May 1295.83 01-MAY-09:09 382.60 04-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1834.80 04-MAY-23:00
June 1295.83 01-JUN-09:09 351.77 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 31.90 13-JUN-15:50 1741.68 18-JUN-16:20
July 1295.83 03-JUL-09:09 377.59 07-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 71.12 22-JUL-19:04 1775.82 30-JUL-19:00
August 1295.83 01-AUG-09:09 408.44 22-AUG-07:30 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 24.62 14-AUG-16:50 1008.59 22-AUG-21:10
September 1295.83 01-SEP-09:09 530.07 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1076.56 06-SEP-04:00
October 1295.83 02-OCT-09:09 735.11 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1374.85 20-OCT-22:00
November 1295.83 01-NOV-09:09 739.33 06-NOV-16:49 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1419.90 25-NOV-05:14
December 1295.83 01-DEC-10:09 739.33 01-DEC-15:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2180.63 02-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   351.77   1392.33   0.00 0.00 0.00 0.00 0.00   1008.59  
Maximum of Months 1295.83   739.33   1392.33   0.00 0.00 0.00 0.00 71.12   2180.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 146.32 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 146.32 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 146.32 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 146.32 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 146.32 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 146.32 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 146.32 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 146.32 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 146.32 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 146.32 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 146.32 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 146.32 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   146.32   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   146.32   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 146.32 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 146.32 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 146.32 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 146.32 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 146.32 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 146.32 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 146.32 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 146.32 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 146.32 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 146.32 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 146.32 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 146.32 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   146.32   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   146.32   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 146.32 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 146.32 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 146.32 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 146.32 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 146.32 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 146.32 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 146.32 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 146.32 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 146.32 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 146.32 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 146.32 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 146.32 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   146.32   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   146.32   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 2868.67 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 2868.67 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 2868.67 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 2868.67 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 2868.67 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 2868.67 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 2868.67 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 2868.67 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 2868.67 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 2868.67 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 2868.67 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 2868.67 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   2868.67   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   2868.67   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1630.94 08-JAN-08:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1460.84 08-FEB-22:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1467.36 27-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1589.60 23-APR-22:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2359.59 04-MAY-23:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.52 13-JUN-16:00 1578.92 05-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125.38 22-JUL-18:51 1490.29 30-JUL-18:52
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.19 14-AUG-17:00 1085.63 22-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1473.48 06-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1814.03 20-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1954.09 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2935.05 02-DEC-18:05
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1085.63  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125.38   2935.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2715.79 08-JAN-08:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2490.52 08-FEB-22:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2475.91 27-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2688.06 23-APR-22:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 4126.87 04-MAY-23:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.00 13-JUN-16:00 2766.26 05-JUN-21:03
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 241.22 22-JUL-18:51 2494.67 30-JUL-18:52
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.38 14-AUG-17:00 1903.79 22-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2516.16 06-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3068.44 20-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3129.72 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4778.90 02-DEC-18:05
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1903.79  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 241.22   4778.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2431.89 08-JAN-08:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2631.62 08-FEB-22:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2597.31 27-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2631.69 23-APR-22:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 4259.56 04-MAY-23:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.11 13-JUN-17:00 3302.53 18-JUN-15:52
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.47 22-JUL-18:51 3054.44 30-JUL-18:52
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.52 14-AUG-18:00 2090.78 22-AUG-21:03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2443.34 06-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3056.82 20-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2880.97 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5109.26 02-DEC-18:05
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2090.78  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.47   5109.26  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 96435.44 02-JAN-04:01 0.00 4521.71 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
February 96866.38 21-FEB-05:11 0.00 5983.50 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
March 95096.09 13-MAR-04:11 0.00 5385.15 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
April 96917.10 24-APR-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 95902.88 01-MAY-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
June 96171.14 12-JUN-04:12 0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 97264.71 31-JUL-04:12 0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 99844.72 07-AUG-04:11 0.00 4786.80 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
September 96787.15 25-SEP-04:12 0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 96189.94 10-OCT-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
November 96509.53 06-NOV-05:11 0.00 4786.80 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
December 97692.12 26-DEC-05:21 0.00 5983.50 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 95096.09   0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 99844.72   0.00 5983.50 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 80681.54 02-JAN-04:01 0.00 4060.81 47501.16 0.00 0.00 0.00 0.00 0.00 0.00
February 78089.84 21-FEB-05:11 0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
March 79692.41 20-MAR-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
April 84028.96 24-APR-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
May 83331.93 01-MAY-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 81775.52 26-JUN-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
July 83997.23 05-JUL-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
August 83238.41 28-AUG-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
September 82593.49 05-SEP-04:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
October 84927.16 10-OCT-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
November 83974.69 13-NOV-05:11 0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
December 81122.34 26-DEC-05:11 0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 78089.84   0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 84927.16   0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 38778.29 26-JAN-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
February 30010.92 10-FEB-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 64423.62 24-MAR-05:02 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
April 71076.82 28-APR-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 71861.56 24-MAY-05:02 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
June 71914.10 16-JUN-05:02 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
July 71168.46 25-JUL-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 71670.30 23-AUG-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
September 71729.23 26-SEP-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
October 67564.02 05-OCT-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 60833.68 01-NOV-05:02 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
December 20328.34 22-DEC-17:00 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 20328.34   0.00 2686.80 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 71914.10   15316.26 9137.09 45884.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16133.62 19-JAN-17:00 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 16092.39 09-FEB-17:00 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 19093.29 31-MAR-16:00 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
April 36971.58 28-APR-16:00 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
May 53940.88 24-MAY-05:02 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
June 65284.40 27-JUN-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
July 67074.81 24-JUL-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
August 63059.38 15-AUG-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
September 59990.29 13-SEP-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
October 26695.71 06-OCT-16:00 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
November 17835.86 10-NOV-16:50 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 15106.59 21-DEC-17:00 15316.26 9137.09 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 15106.59   0.00 2149.44 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 67074.81   15316.26 9137.09 45884.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2441.09 18-JAN-06:02 1214.60 404.83 5761.47 0.00 0.00 0.00 0.00 0.00 0.00
February 2992.50 21-FEB-13:40 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 46.97
March 4792.68 20-MAR-12:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 80.53
April 6830.78 28-APR-14:00 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 18.56
May 6876.53 22-MAY-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.01 0.00
June 11123.86 25-JUN-16:21 910.95 272.92 6481.66 0.00 0.00 0.00 0.00 0.00 47.30
July 9916.99 24-JUL-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 63.42
August 7901.41 14-AUG-15:10 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 6.49 0.00
September 6178.11 13-SEP-14:20 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 6.37
October 5256.98 10-OCT-13:10 4021.58 1091.73 4321.10 0.00 0.00 0.00 0.00 0.00 50.50
November 3346.24 08-NOV-14:30 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 16.53
December 2421.86 11-DEC-05:12 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2421.86   0.00 272.92 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11123.86   4021.58 1091.73 7455.61 0.00 0.00 0.00 0.00 6.49 80.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4374.10 20-JAN-10:10 2591.66 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 0.00
February 5669.69 17-FEB-09:45 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 0.00
March 5286.14 25-MAR-09:25 818.42 234.52 1547.05 0.00 0.00 0.00 0.00 0.00 0.00
April 23682.96 30-APR-08:21 456.59 136.80 3248.80 0.00 0.00 0.00 0.00 0.00 161.63
May 21960.94 07-MAY-08:32 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 186.80
June 22342.65 25-JUN-09:02 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 96.43
July 24215.72 23-JUL-08:41 521.82 156.34 3712.91 0.00 0.00 0.00 0.00 0.00 131.35
August 21865.20 27-AUG-09:02 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 182.39
September 19353.96 04-SEP-08:52 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 132.37
October 10703.42 01-OCT-08:33 195.68 58.63 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
November 5025.62 13-NOV-09:25 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 41.23
December 3149.26 06-DEC-09:55 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3149.26   195.68 58.63 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24215.72   2591.66 703.55 3712.91 0.00 0.00 0.00 0.00 0.00 186.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19054.26 15-JAN-12:32 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
February 27650.92 19-FEB-14:53 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 329.54
March 12197.79 28-MAR-12:05 3846.30 1091.75 4321.17 0.00 0.00 0.00 0.00 0.00 97.35
April 33708.63 30-APR-12:21 809.75 242.60 5761.56 0.00 0.00 0.00 0.00 0.00 133.46
May 28082.99 21-MAY-12:43 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 227.07
June 28202.59 25-JUN-16:21 910.97 272.93 6481.75 0.00 0.00 0.00 0.00 0.00 48.54
July 30357.73 23-JUL-14:02 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 209.66
August 30720.18 27-AUG-13:02 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 176.61
September 30666.24 10-SEP-12:42 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 153.08
October 29408.85 01-OCT-11:13 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 480.79
November 21988.90 11-NOV-13:13 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 348.19
December 15691.56 18-DEC-13:30 1923.15 545.88 2160.58 0.00 0.00 0.00 0.00 0.00 69.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12197.79   404.87 121.30 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33708.63   3846.30 1091.75 6481.75 0.00 0.00 0.00 0.00 0.00 480.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8048.45 30-JAN-16:35 4957.30 1612.17 5569.33 0.00 0.00 0.00 0.00 0.00 0.00
February 13542.54 19-FEB-14:53 260.91 78.17 1856.44 0.00 0.00 0.00 0.00 0.00 218.75
March 13932.23 24-MAR-05:02 782.73 260.89 3712.89 0.00 0.00 0.00 0.00 0.00 0.00
April 29057.74 30-APR-14:21 521.82 156.34 3712.89 0.00 0.00 0.00 0.00 0.00 53.38
May 26929.26 21-MAY-16:42 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 124.30
June 30565.24 11-JUN-16:11 587.05 175.88 4177.00 0.00 0.00 0.00 0.00 0.00 191.57
July 30071.20 23-JUL-17:21 0.00 175.88 3243.14 0.00 0.00 0.00 0.00 0.00 145.42
August 28047.11 20-AUG-16:41 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 0.00 70.40
September 21182.28 10-SEP-16:02 326.14 97.71 2320.55 0.00 0.00 0.00 0.00 0.00 106.87
October 17162.02 01-OCT-16:33 260.91 78.17 1856.44 0.00 0.00 0.00 0.00 0.00 402.30
November 17538.49 09-NOV-06:02 782.73 260.89 3712.89 0.00 0.00 0.00 0.00 0.00 0.00
December 11351.79 16-DEC-06:02 652.28 410.73 3094.07 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8048.45   0.00 78.17 1856.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30565.24   4957.30 1612.17 5569.33 0.00 0.00 0.00 0.00 0.00 402.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1762.40 15-JAN-13:02 506.08 151.62 3600.92 0.00 0.00 0.00 0.00 0.00 64.18
February 1761.06 19-FEB-13:13 404.87 121.30 2880.74 0.00 0.00 0.00 0.00 0.00 250.90
March 2012.13 30-MAR-14:10 3846.22 1091.73 4321.10 0.00 0.00 0.00 0.00 0.00 115.63
April 5272.86 28-APR-14:00 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 44.72
May 5732.68 22-MAY-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 1.16
June 7274.16 13-JUN-15:10 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 40.04 0.00
July 7201.18 10-JUL-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 18.94
August 6186.04 14-AUG-16:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 28.10 0.00
September 5394.60 13-SEP-15:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 15.41
October 2778.50 11-OCT-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 45.14
November 1996.71 11-NOV-12:22 506.08 151.62 3600.92 0.00 0.00 0.00 0.00 0.00 554.60
December 1540.58 21-DEC-14:40 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 149.92
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1540.58   404.87 121.30 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7274.16   3846.22 1091.73 4321.10 0.00 0.00 0.00 0.00 40.04 554.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4105.50 20-JAN-11:05 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 0.00
February 4987.14 24-FEB-11:05 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 85.33
March 5498.10 25-MAR-10:05 782.73 234.52 1547.05 0.00 0.00 0.00 0.00 0.00 0.00
April 22578.70 30-APR-09:12 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 375.55
May 24014.99 21-MAY-08:32 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 369.44
June 23860.76 11-JUN-09:22 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 390.21
July 26147.15 23-JUL-08:31 521.82 156.34 3712.91 0.00 0.00 0.00 0.00 0.00 319.87
August 22822.61 06-AUG-09:52 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 335.78
September 22672.01 24-SEP-09:02 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 359.62
October 11886.10 01-OCT-09:02 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 101.57
November 4150.72 03-NOV-10:05 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 97.03
December 1271.85 08-DEC-11:10 1239.33 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 104.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1271.85   260.91 78.17 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26147.15   2478.65 703.55 3712.91 0.00 0.00 0.00 0.00 0.00 390.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 31532.31 15-JAN-13:02 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 109.15
February 30494.45 19-FEB-13:13 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 371.03
March 11157.51 28-MAR-12:05 3846.30 1091.75 4321.17 0.00 0.00 0.00 0.00 0.00 230.32
April 32928.31 30-APR-13:12 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 246.48
May 28615.45 21-MAY-13:53 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 701.21
June 26292.98 11-JUN-13:23 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 510.77
July 31997.26 30-JUL-13:32 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 1025.79
August 33399.84 06-AUG-13:52 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 541.19
September 33120.52 24-SEP-11:42 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 583.06
October 31679.46 01-OCT-11:42 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 1182.34
November 31674.88 11-NOV-12:22 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 845.37
December 14187.72 18-DEC-13:30 1923.15 545.88 2160.58 0.00 0.00 0.00 0.00 0.00 162.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11157.51   404.87 121.30 2160.58 0.00 0.00 0.00 0.00 0.00 109.15
Maximum of Months 33399.84   3846.30 1091.75 4321.17 0.00 0.00 0.00 0.00 0.00 1182.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4294.71 19-JAN-15:40 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
February 7254.26 27-FEB-16:30 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
March 7812.34 23-MAR-16:40 391.37 195.43 773.52 0.00 0.00 0.00 0.00 0.00 126.77
April 24847.96 30-APR-17:12 0.00 117.25 2162.09 0.00 0.00 0.00 0.00 0.00 64.54
May 27645.65 21-MAY-16:31 587.05 175.88 4177.00 0.00 0.00 0.00 0.00 0.00 396.77
June 27979.78 11-JUN-17:21 0.00 175.88 3243.14 0.00 0.00 0.00 0.00 0.00 551.29
July 28894.59 09-JUL-17:21 0.00 195.42 3603.49 0.00 0.00 0.00 0.00 0.00 317.11
August 26620.00 06-AUG-16:31 521.82 156.34 3712.89 0.00 0.00 0.00 0.00 0.00 332.70
September 23771.12 24-SEP-15:02 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 157.63
October 9996.28 03-OCT-15:40 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 85.43
November 4404.48 10-NOV-15:30 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 85.93
December 1641.26 21-DEC-14:40 1295.83 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 115.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1641.26   0.00 117.25 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28894.59   1295.83 351.77 4177.00 0.00 0.00 0.00 0.00 0.00 551.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1586.16 19-JAN-15:40 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
February 1521.42 24-FEB-16:10 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 153.14
March 1829.86 30-MAR-15:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 280.05
April 5504.01 28-APR-15:20 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 45.30
May 6365.00 22-MAY-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 2.90
June 8129.11 13-JUN-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 46.40 0.00
July 7913.40 10-JUL-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 25.83
August 6748.16 14-AUG-16:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 32.87 0.00
September 5623.75 13-SEP-15:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 21.02
October 2130.43 01-OCT-15:02 506.08 151.62 3600.92 0.00 0.00 0.00 0.00 0.00 978.09
November 1689.84 10-NOV-15:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 142.07
December 1367.64 21-DEC-14:50 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 0.00 184.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1367.64   506.08 151.62 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8129.11   2010.79 545.86 3600.92 0.00 0.00 0.00 0.00 46.40 978.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1287.89 20-JAN-10:40 1295.83 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
February 2096.33 24-FEB-10:30 1295.83 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 51.27
March 1827.03 25-MAR-09:30 818.42 234.52 1547.05 0.00 0.00 0.00 0.00 0.00 0.00
April 24314.69 30-APR-09:31 456.59 136.80 3248.80 0.00 0.00 0.00 0.00 0.00 484.06
May 22895.31 21-MAY-08:32 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 445.78
June 23662.02 25-JUN-09:32 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 106.98
July 23309.91 23-JUL-08:52 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 340.36
August 22198.77 06-AUG-10:02 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 405.52
September 13147.95 10-SEP-09:12 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 95.52
October 5963.42 04-OCT-10:00 1295.83 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
November 1236.49 03-NOV-10:00 1295.83 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 92.31
December 1071.48 06-DEC-10:20 1295.83 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 55.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1071.48   326.14 97.71 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24314.69   1295.83 351.77 3248.80 0.00 0.00 0.00 0.00 0.00 484.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13212.30 11-JAN-13:40 1923.15 545.88 2160.58 0.00 0.00 0.00 0.00 0.00 266.38
February 17161.05 17-FEB-13:40 3846.30 1091.75 4321.17 0.00 0.00 0.00 0.00 0.00 294.76
March 8510.87 28-MAR-12:20 1923.15 545.88 2160.58 0.00 0.00 0.00 0.00 0.00 308.11
April 37218.33 30-APR-12:11 809.75 242.60 5761.56 0.00 0.00 0.00 0.00 0.00 399.81
May 26160.24 21-MAY-13:53 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 878.98
June 31450.87 25-JUN-16:11 910.97 272.93 6481.75 0.00 0.00 0.00 0.00 0.00 127.36
July 27505.00 23-JUL-12:52 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 384.46
August 34690.92 06-AUG-12:42 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 634.41
September 37213.57 10-SEP-13:11 809.75 242.60 5761.56 0.00 0.00 0.00 0.00 0.00 676.12
October 32056.73 01-OCT-15:02 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 1558.77
November 22807.20 11-NOV-12:22 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 1020.29
December 11431.07 18-DEC-13:30 1923.15 545.88 2160.58 0.00 0.00 0.00 0.00 0.00 203.72
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8510.87   404.87 121.30 2160.58 0.00 0.00 0.00 0.00 0.00 127.36
Maximum of Months 37218.33   3846.30 1091.75 6481.75 0.00 0.00 0.00 0.00 0.00 1558.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3497.06 19-JAN-15:50 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
February 6260.29 27-FEB-16:30 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
March 7007.76 23-MAR-16:40 391.37 195.43 773.52 0.00 0.00 0.00 0.00 0.00 158.61
April 29407.57 30-APR-16:11 652.28 195.42 4641.11 0.00 0.00 0.00 0.00 0.00 42.67
May 28822.91 21-MAY-16:31 587.05 175.88 4177.00 0.00 0.00 0.00 0.00 0.00 494.27
June 28230.81 25-JUN-16:11 587.05 175.88 4177.00 0.00 0.00 0.00 0.00 0.00 139.58
July 30126.01 09-JUL-17:31 0.00 195.42 3603.49 0.00 0.00 0.00 0.00 0.00 375.23
August 26700.49 13-AUG-16:51 652.28 195.42 4641.11 0.00 0.00 0.00 0.00 0.00 340.12
September 26119.75 10-SEP-16:32 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 382.33
October 9513.33 03-OCT-15:40 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 107.21
November 3669.07 10-NOV-15:30 1239.33 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 107.61
December 1262.18 21-DEC-14:50 1295.83 351.77 1392.33 0.00 0.00 0.00 0.00 0.00 145.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1262.18   0.00 117.25 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30126.01   1295.83 351.77 4641.11 0.00 0.00 0.00 0.00 0.00 494.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4024.47 02-JAN-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 2829.67 24-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 264.21
March 3834.77 20-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.83
April 6609.88 24-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.18
May 7913.05 01-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 343.09
June 8905.79 26-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 148.65
July 7443.41 24-JUL-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.40
August 8032.95 28-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99.61
September 6408.64 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 189.23
October 6947.83 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 5188.09 13-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.88
December 2549.87 27-DEC-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.82
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2549.87   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8905.79   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 343.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6678.19 10-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1251.46
February 6793.75 24-FEB-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 451.27
March 6303.72 04-MAR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 450.44
April 3853.52 28-APR-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.75
May 3483.00 23-MAY-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 142.16
June 4649.01 26-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95.61
July 5118.09 24-JUL-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.17
August 4382.64 21-AUG-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.71
September 4340.16 12-SEP-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.83
October 2791.23 06-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.21
November 6320.08 20-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1678.97
December 7434.16 30-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1948.94
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2791.23   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.21
Maximum of Months 7434.16   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1948.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 759.74 21-JAN-13:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 195.33
February 926.87 19-FEB-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1036.74
March 2433.82 25-MAR-12:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 105.64
April 13081.00 28-APR-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 94.99
May 13909.81 22-MAY-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.05
June 15728.85 13-JUN-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.77
July 15413.34 21-JUL-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.02 0.00
August 13724.24 14-AUG-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.22
September 11690.70 12-SEP-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 132.72
October 4735.42 03-OCT-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 303.60
November 971.61 11-NOV-13:46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1138.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 595.66
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15728.85   0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.02 1138.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1904.92 19-JAN-16:20 222.14 146.32 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4103.25 27-FEB-17:00 222.14 146.32 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6999.61 31-MAR-24:00 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8281.70 30-APR-19:12 0.00 32.52 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3327.17 31-MAY-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5168.31 30-JUN-24:00 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7230.99 31-JUL-24:00 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8267.81 13-AUG-18:03 0.00 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3225.84 30-SEP-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5068.91 31-OCT-24:00 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5672.17 03-NOV-16:00 222.14 146.32 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7427.70 25-DEC-15:13 35.07 24.39 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1904.92   0.00 8.13 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8281.70   222.14 146.32 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1661.46 19-JAN-16:30 222.14 146.32 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3704.66 27-FEB-17:00 222.14 146.32 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6290.28 31-MAR-23:30 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7877.11 30-APR-18:02 0.00 65.03 62355.38 0.00 0.00 0.00 0.00 0.00 0.00
May 3032.85 31-MAY-23:40 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 4712.95 30-JUN-23:40 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6790.10 31-JUL-23:50 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7703.16 13-AUG-18:03 0.00 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 2850.61 30-SEP-23:30 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4338.71 31-OCT-23:50 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5265.46 03-NOV-16:00 222.14 146.32 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6731.63 21-DEC-15:20 222.14 146.32 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1661.46   0.00 8.13 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7877.11   222.14 146.32 62355.38 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1523.28 19-JAN-16:30 222.14 146.32 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3492.25 24-FEB-17:00 222.14 146.32 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5798.76 31-MAR-23:20 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7997.64 30-APR-17:53 0.00 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
May 2878.49 31-MAY-23:20 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 4487.29 30-JUN-23:20 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6628.55 31-JUL-23:20 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7818.58 13-AUG-17:55 0.00 16.26 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 2313.06 30-SEP-23:10 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 3794.79 03-OCT-16:50 70.15 81.29 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5159.43 10-NOV-16:20 222.14 146.32 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6456.35 21-DEC-15:20 222.14 146.32 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1523.28   0.00 8.13 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7997.64   222.14 146.32 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 90599.31 02-JAN-17:00 4808.68 2868.67 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 181906.45 09-FEB-17:00 4808.68 2868.67 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358093.97 31-MAR-24:00 0.00 159.37 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 366506.37 28-APR-16:00 4808.68 2868.67 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175411.82 31-MAY-24:00 0.00 159.37 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 266685.65 30-JUN-24:00 0.00 159.37 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359595.20 31-JUL-24:00 0.00 159.37 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
August 367075.99 28-AUG-16:00 4808.68 2868.67 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 175315.53 30-SEP-24:00 0.00 159.37 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 266922.40 31-OCT-24:00 0.00 159.37 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 274503.51 13-NOV-15:00 5027.92 2868.67 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 366018.41 26-DEC-17:00 4808.68 2868.67 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 90599.31   0.00 159.37 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 367075.99   5027.92 2868.67 379632.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.129925E+13 812707.93 10-JAN-16:00 0.340131E+12 730805.15 10-JAN-07:10
February 0.152169E+13 948830.45 17-FEB-16:10 0.254345E+12 672781.20 17-FEB-07:10
March 0.210523E+13 1110214.00 31-MAR-15:39 0.225991E+12 499666.84 10-MAR-14:20
April 0.241087E+13 1446674.27 27-APR-15:09 0.975297E+11 342211.36 08-APR-06:10
May 0.130821E+13 1061771.98 22-MAY-15:09 0.882165E+11 396580.55 03-MAY-13:20
June 0.162925E+13 1292313.68 13-JUN-15:30 0.677575E+11 184048.39 05-JUN-11:09
July 0.205121E+13 1420753.10 21-JUL-15:20 0.637241E+11 84332.91 25-JUL-09:09
August 0.254250E+13 1551231.39 14-AUG-15:30 0.672734E+11 111875.50 31-AUG-09:09
September 0.128726E+13 1080540.61 12-SEP-15:30 0.663190E+11 326370.44 08-SEP-09:00
October 0.162980E+13 1085206.28 05-OCT-15:30 0.110242E+12 306042.83 23-OCT-06:10
November 0.196792E+13 1100577.77 17-NOV-16:00 0.211904E+12 571277.46 29-NOV-07:10
December 0.244995E+13 1243367.14 29-DEC-08:09 0.362967E+12 617147.72 27-DEC-07:10
             
Annual Sum or Average 0.222031E+14     0.195640E+13    
Minimum of Months 0.128726E+13 812707.93   0.637241E+11 84332.91  
Maximum of Months 0.254250E+13 1551231.39   0.362967E+12 730805.15  



Table of Contents

Report: EnergyConsumptionElectricityGeneratedPropaneMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ELECTRICITYPRODUCED:FACILITY [J] ELECTRICITYPRODUCED:FACILITY {Maximum} [W] ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} PROPANE:FACILITY [] PROPANE:FACILITY []
January 0.104074E+11 28975.78 11-JAN-12:30 0.00 0.00
February 0.161777E+11 48050.76 27-FEB-12:30 0.00 0.00
March 0.212400E+11 58603.90 28-MAR-11:30 0.00 0.00
April 0.475247E+11 75524.54 26-APR-12:30 0.00 0.00
May 0.576993E+11 83281.86 19-MAY-12:09 0.00 0.00
June 0.588975E+11 84379.95 18-JUN-12:30 0.00 0.00
July 0.610402E+11 82110.52 01-JUL-11:00 0.00 0.00
August 0.524820E+11 74243.67 05-AUG-12:30 0.00 0.00
September 0.388050E+11 63790.06 09-SEP-12:09 0.00 0.00
October 0.209619E+11 52194.76 03-OCT-12:09 0.00 0.00
November 0.106173E+11 35535.26 03-NOV-12:20 0.00 0.00
December 0.712654E+10 27599.41 03-DEC-12:30 0.00 0.00
           
Annual Sum or Average 0.402980E+12     0.00 0.00
Minimum of Months 0.712654E+10 27599.41   0.00 0.00
Maximum of Months 0.610402E+11 84379.95   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY [J]
January 0.147551E+12 0.337437E+11 0.766053E+12 0.102196E+12 0.152150E+12 0.116575E+11 0.00 0.917264E+10 0.136730E+10 0.753626E+11 0.00 0.00 0.00
February 0.131358E+12 0.261970E+11 0.978954E+12 0.923113E+11 0.139590E+12 0.123772E+11 0.00 0.216303E+11 0.316419E+10 0.116110E+12 0.00 0.00 0.00
March 0.154113E+12 0.233057E+11 0.141687E+13 0.102362E+12 0.156338E+12 0.132844E+11 0.00 0.371408E+11 0.626627E+10 0.195546E+12 0.00 0.00 0.00
April 0.136604E+12 0.172750E+11 0.165903E+13 0.988819E+11 0.180099E+12 0.135169E+11 0.00 0.695985E+11 0.194950E+11 0.216372E+12 0.00 0.00 0.00
May 0.146595E+12 0.142667E+11 0.774844E+12 0.102278E+12 0.183977E+12 0.141427E+11 0.00 0.238299E+11 0.884419E+10 0.394380E+11 0.00 0.00 0.00
June 0.145582E+12 0.122931E+11 0.106252E+13 0.990389E+11 0.194835E+12 0.192289E+11 0.00 0.582426E+11 0.244647E+11 0.130491E+11 0.00 0.00 0.00
July 0.136452E+12 0.132085E+11 0.139340E+13 0.102120E+12 0.205945E+12 0.264772E+11 0.00 0.112047E+12 0.514977E+11 0.100606E+11 0.00 0.00 0.00
August 0.152470E+12 0.159806E+11 0.173200E+13 0.102362E+12 0.216843E+12 0.293495E+11 0.00 0.196342E+12 0.824741E+11 0.146800E+11 0.00 0.00 0.00
September 0.137124E+12 0.201109E+11 0.740713E+12 0.988811E+11 0.189203E+12 0.214879E+11 0.00 0.435443E+11 0.216697E+11 0.145289E+11 0.00 0.00 0.00
October 0.144593E+12 0.265623E+11 0.108340E+13 0.102195E+12 0.164306E+12 0.133846E+11 0.00 0.299456E+11 0.663560E+10 0.587735E+11 0.00 0.00 0.00
November 0.145724E+12 0.310354E+11 0.135889E+13 0.989470E+11 0.148807E+12 0.119066E+11 0.00 0.339728E+11 0.620245E+10 0.132432E+12 0.00 0.00 0.00
December 0.144786E+12 0.351800E+11 0.170972E+13 0.102123E+12 0.151089E+12 0.148954E+11 0.00 0.462851E+11 0.674124E+10 0.239129E+12 0.00 0.00 0.00
                           
Annual Sum or Average 0.172295E+13 0.269159E+12 0.146764E+14 0.120369E+13 0.208318E+13 0.201709E+12 0.00 0.681752E+12 0.238823E+12 0.112548E+13 0.00 0.00 0.00
Minimum of Months 0.131358E+12 0.122931E+11 0.740713E+12 0.923113E+11 0.139590E+12 0.116575E+11 0.00 0.917264E+10 0.136730E+10 0.100606E+11 0.00 0.00 0.00
Maximum of Months 0.154113E+12 0.351800E+11 0.173200E+13 0.102362E+12 0.216843E+12 0.293495E+11 0.00 0.196342E+12 0.824741E+11 0.239129E+12 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.271206E+12 0.00 0.689255E+11 0.00 0.00
February 0.00 0.00 0.191524E+12 0.00 0.628205E+11 0.00 0.00
March 0.00 0.00 0.153724E+12 0.00 0.722667E+11 0.00 0.00
April 0.00 0.00 0.316479E+11 0.00 0.658817E+11 0.00 0.00
May 0.00 0.00 0.198521E+11 0.00 0.683644E+11 0.00 0.00
June 0.00 0.00 0.174712E+10 0.00 0.660103E+11 0.00 0.00
July 0.00 0.00 0.237789E+09 0.00 0.634863E+11 0.00 0.00
August 0.00 0.00 94627947.49 0.00 0.671788E+11 0.00 0.00
September 0.00 0.00 0.379551E+10 0.00 0.625235E+11 0.00 0.00
October 0.00 0.00 0.447774E+11 0.00 0.654643E+11 0.00 0.00
November 0.00 0.00 0.146712E+12 0.00 0.651917E+11 0.00 0.00
December 0.00 0.00 0.296095E+12 0.00 0.668720E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.116141E+13 0.00 0.794986E+12 0.00 0.00
Minimum of Months 0.00 0.00 94627947.49 0.00 0.625235E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.296095E+12 0.00 0.722667E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 169722.15 02-JAN-08:09 31088.59 01-JAN-06:10 423497.50 02-JAN-08:09 73700.64 02-JAN-08:20 94127.51 20-JAN-11:00 17295.18 09-JAN-06:10 0.00 01-JAN-00:10
February 166828.82 01-FEB-08:09 31088.59 01-FEB-06:10 541788.89 01-FEB-08:09 73699.12 01-FEB-08:20 101859.86 17-FEB-15:09 17221.95 02-FEB-06:10 0.00 01-FEB-00:10
March 161842.07 15-MAR-07:10 31088.59 01-MAR-06:10 660080.29 01-MAR-08:09 73696.50 15-MAR-07:19 99664.51 23-MAR-15:00 17221.25 07-MAR-06:10 0.00 01-MAR-00:10
April 155692.03 10-APR-07:10 31088.59 01-APR-05:10 778371.69 03-APR-07:10 73693.27 10-APR-07:19 219468.27 28-APR-14:00 20099.07 28-APR-15:20 0.00 01-APR-00:10
May 146362.56 04-MAY-07:10 22480.63 01-MAY-19:19 423497.50 01-MAY-07:10 73688.38 04-MAY-07:19 188730.09 22-MAY-15:20 33130.30 22-MAY-14:09 0.00 01-MAY-00:10
June 145987.23 01-JUN-07:10 22480.63 01-JUN-19:00 541788.89 01-JUN-07:10 73688.19 01-JUN-07:19 209082.13 13-JUN-15:20 33883.00 21-JUN-14:50 0.00 01-JUN-00:10
July 146302.82 07-JUL-07:10 22480.63 01-JUL-20:19 660080.29 03-JUL-07:10 73688.35 07-JUL-07:19 213084.37 21-JUL-15:20 34641.16 21-JUL-17:19 0.00 01-JUL-00:10
August 149112.14 22-AUG-07:30 31088.59 14-AUG-05:10 778371.69 01-AUG-07:10 73689.82 22-AUG-07:40 216655.89 14-AUG-15:09 33517.51 14-AUG-12:30 0.00 01-AUG-00:10
September 150340.85 08-SEP-07:30 31088.59 01-SEP-05:10 423497.50 01-SEP-07:10 73690.47 08-SEP-07:40 254179.13 12-SEP-15:30 33808.25 12-SEP-15:50 0.00 01-SEP-00:10
October 169459.99 31-OCT-07:10 31088.59 01-OCT-05:10 541788.89 02-OCT-07:10 73700.50 31-OCT-07:19 156212.00 03-OCT-15:09 17875.30 03-OCT-14:09 0.00 01-OCT-00:10
November 169722.15 06-NOV-16:49 31088.59 01-NOV-05:10 660080.29 01-NOV-07:10 73700.53 02-NOV-07:19 100103.78 03-NOV-14:30 17318.76 20-NOV-06:10 0.00 01-NOV-00:10
December 169722.15 01-DEC-15:30 31088.59 01-DEC-06:10 778371.69 01-DEC-08:09 73700.64 27-DEC-08:20 85424.89 18-DEC-13:30 17408.89 26-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 145987.23   22480.63   423497.50   73688.19   85424.89   17221.25   0.00  
Maximum of Months 169722.15   31088.59   778371.69   73700.64   254179.13   34641.16   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY {Maximum} [W] COGENERATION:ELECTRICITY {TIMESTAMP}
January 18887.46 20-JAN-11:00 1554.28 29-JAN-05:00 59817.65 10-JAN-17:00 0.00 0.00 0.00 01-JAN-00:10
February 35781.32 09-FEB-15:30 2395.53 07-FEB-14:00 100000.00 20-FEB-15:50 0.00 0.00 0.00 01-FEB-00:10
March 35924.64 30-MAR-14:09 5060.08 25-MAR-12:00 100000.00 03-MAR-22:10 0.00 0.00 0.00 01-MAR-00:10
April 175905.46 30-APR-15:20 45541.76 28-APR-14:00 100000.00 01-APR-04:19 0.00 0.00 0.00 01-APR-00:10
May 161333.12 22-MAY-14:09 68588.97 22-MAY-14:20 93822.71 21-MAY-14:00 0.00 0.00 0.00 01-MAY-00:10
June 250228.97 13-JUN-15:00 68588.97 12-JUN-13:39 100000.00 08-JUN-11:00 0.00 0.00 0.00 01-JUN-00:10
July 270575.04 21-JUL-15:30 68588.97 10-JUL-08:50 100000.00 05-JUL-15:00 0.00 0.00 0.00 01-JUL-00:10
August 283212.20 14-AUG-15:00 68588.97 14-AUG-10:30 100000.00 14-AUG-16:49 0.00 0.00 0.00 01-AUG-00:10
September 152492.20 12-SEP-15:00 68588.97 11-SEP-14:00 67881.23 29-SEP-16:00 0.00 0.00 0.00 01-SEP-00:10
October 76859.45 06-OCT-14:30 43974.74 07-OCT-14:30 100000.00 07-OCT-16:10 0.00 0.00 0.00 01-OCT-00:10
November 27900.69 24-NOV-11:00 21133.82 24-NOV-11:00 100000.00 19-NOV-12:20 0.00 0.00 0.00 01-NOV-00:10
December 26828.65 23-DEC-10:00 7000.91 23-DEC-10:00 100000.00 03-DEC-12:09 0.00 0.00 0.00 01-DEC-00:10
                     
Annual Sum or Average             0.00 0.00    
Minimum of Months 18887.46   1554.28   59817.65   0.00 0.00 0.00  
Maximum of Months 283212.20   68588.97   100000.00   0.00 0.00 0.00  



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 812707.93 10-JAN-16:00 169722.15 423497.50 31088.59 52602.06 68298.58 3501.74 0.00 5018.35 473.57
February 948830.45 17-FEB-16:10 145987.23 541788.89 0.00 52589.61 95226.21 17063.88 0.00 18724.78 1786.21
March 1110214.00 31-MAR-15:39 145987.23 660080.29 0.00 52589.61 97581.58 17077.09 0.00 33896.25 3001.95
April 1446674.27 27-APR-15:09 145987.23 778371.69 0.00 52589.61 192440.52 17249.87 0.00 117645.64 44099.69
May 1061771.98 22-MAY-15:09 145987.23 423497.50 0.00 52589.61 188111.15 32608.28 0.00 150389.26 68588.97
June 1292313.68 13-JUN-15:30 145987.23 541788.89 0.00 52589.61 208202.15 32738.54 0.00 242418.30 68588.97
July 1420753.10 21-JUL-15:20 145987.23 660080.29 0.00 52589.61 213084.37 33314.05 0.00 269474.31 46223.25
August 1551231.39 14-AUG-15:30 145987.23 778371.69 0.00 52589.61 214677.24 32989.27 0.00 280213.49 46402.87
September 1080540.61 12-SEP-15:30 145987.23 423497.50 0.00 52589.61 254179.13 25083.65 0.00 123020.90 56182.60
October 1085206.28 05-OCT-15:30 145987.23 541788.89 0.00 52589.61 145971.79 17267.03 0.00 74959.78 6641.95
November 1100577.77 17-NOV-16:00 169722.15 660080.29 31088.59 52602.06 74886.89 17064.33 0.00 15962.09 2530.81
December 1243367.14 29-DEC-08:09 169722.15 778371.69 31088.59 73641.61 68330.74 3433.34 0.00 16693.33 2085.69
                       
Annual Sum or Average                      
Minimum of Months 812707.93   145987.23 423497.50 0.00 52589.61 68298.58 3433.34 0.00 5018.35 473.57
Maximum of Months 1551231.39   169722.15 778371.69 31088.59 73641.61 254179.13 33314.05 0.00 280213.49 68588.97



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 702189.62 10-JAN-07:10 0.00 83681.97 30-JAN-12:39 0.00
February 0.00 0.00 641640.73 17-FEB-07:10 0.00 83758.20 15-FEB-12:50 0.00
March 0.00 0.00 438159.90 10-MAR-14:20 0.00 83711.26 01-MAR-12:30 0.00
April 0.00 0.00 313001.99 08-APR-06:10 0.00 83157.01 03-APR-11:39 0.00
May 0.00 0.00 342516.62 03-MAY-13:20 0.00 82439.66 01-MAY-11:30 0.00
June 0.00 0.00 117611.13 28-JUN-09:09 0.00 81423.81 01-JUN-11:39 0.00
July 0.00 0.00 37209.50 08-JUL-11:20 0.00 80426.75 05-JUL-11:50 0.00
August 0.00 0.00 48876.76 31-AUG-09:09 0.00 79956.37 31-AUG-11:30 0.00
September 0.00 0.00 288639.39 08-SEP-09:00 0.00 80441.87 29-SEP-11:39 0.00
October 0.00 0.00 275298.84 23-OCT-06:10 0.00 81399.43 30-OCT-11:39 0.00
November 0.00 0.00 540368.29 29-NOV-07:10 0.00 82373.63 30-NOV-12:39 0.00
December 0.00 0.00 586103.05 27-DEC-07:10 0.00 83165.97 29-DEC-12:20 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 37209.50   0.00 79956.37   0.00
Maximum of Months 0.00 0.00 702189.62   0.00 83758.20   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 8.33 26.99 2.33 27.07
February 0.00 0.00 0.00 0.00 0.83 25.67 0.00 25.67
March 0.00 0.00 0.00 0.00 3.00 25.75 0.00 25.75
April 0.00 0.00 0.00 0.00 1.50 25.96 0.00 25.96
May 0.00 0.00 0.00 0.00 6.33 26.50 0.00 26.50
June 0.00 0.00 0.00 0.00 2.50 25.80 0.00 25.80
July 0.00 0.00 0.00 0.00 2.50 26.77 0.00 26.77
August 0.00 0.00 0.00 0.00 3.83 27.04 0.00 27.04
September 0.00 0.00 0.00 0.00 2.50 26.06 0.00 26.06
October 0.00 0.00 0.00 0.00 5.33 26.72 2.83 26.97
November 0.00 0.00 0.00 0.00 6.50 26.89 1.33 26.92
December 0.00 0.00 0.00 0.00 1.33 26.38 0.00 26.38
                 
Annual Sum or Average 0.00   0.00   44.50 26.58 6.50 26.68
Minimum of Months 0.00 0.00 0.00 0.00 0.83 25.67 0.00 25.67
Maximum of Months 0.00 0.00 0.00 0.00 8.33 27.04 2.83 27.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 19.24 0.33 19.41 0.00 19.41 0.00 19.41
February 0.17 19.39 0.00 19.39 0.00 19.39 0.00 19.39
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 18.67 0.00 18.67 0.00 18.67 0.00 18.67
December 1.83 19.01 0.17 19.10 0.00 19.10 0.00 19.10
                 
Annual Sum or Average 3.83 19.09 0.50 19.21 0.00 19.21 0.00 19.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.83 19.39 0.33 19.41 0.00 19.41 0.00 19.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.67 28.16 1.67 28.16
May 0.00 0.00 0.00 0.00 2.67 27.90 2.67 27.90
June 0.00 0.00 0.00 0.00 4.33 27.88 4.33 27.88
July 0.00 0.00 0.00 0.00 7.17 27.91 7.17 27.91
August 0.00 0.00 0.00 0.00 4.50 27.95 4.50 27.95
September 0.00 0.00 0.00 0.00 4.67 27.86 4.67 27.86
October 0.00 0.00 0.00 0.00 0.67 27.49 0.67 27.49
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   25.67 27.91 25.67 27.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.17 28.16 7.17 28.16



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.83 27.79 0.83 27.79
February 0.00 0.00 0.00 0.00 1.33 27.71 1.33 27.71
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.17 28.15 2.83 28.19
May 0.00 0.00 0.00 0.00 3.00 27.54 3.00 27.54
June 0.00 0.00 0.00 0.00 3.17 27.62 3.17 27.62
July 0.00 0.00 0.00 0.00 6.00 27.84 5.83 27.84
August 0.00 0.00 0.00 0.00 7.00 28.03 7.00 28.03
September 0.00 0.00 0.00 0.00 6.83 28.07 6.83 28.07
October 0.00 0.00 0.00 0.00 2.00 27.87 2.00 27.87
November 0.00 0.00 0.00 0.00 1.67 27.79 1.67 27.79
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   35.00 27.90 34.50 27.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.00 28.15 7.00 28.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.00 27.64 1.00 27.64
March 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
April 0.00 0.00 0.00 0.00 9.83 27.73 5.83 27.81
May 0.00 0.00 0.00 0.00 6.83 28.16 3.83 28.18
June 0.00 0.00 0.00 0.00 8.67 27.96 5.17 28.03
July 0.00 0.00 0.00 0.00 19.00 27.87 9.83 27.98
August 0.00 0.00 0.00 0.00 18.67 27.59 9.00 27.81
September 0.00 0.00 0.00 0.00 5.67 28.00 4.33 28.05
October 0.00 0.00 0.00 0.00 1.00 27.81 0.83 27.83
November 0.00 0.00 0.00 0.00 1.00 27.38 1.00 27.38
December 0.00 0.00 0.00 0.00 0.17 27.35 0.17 27.35
                 
Annual Sum or Average 0.00   0.00   72.00 27.81 41.17 27.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 19.00 28.16 9.83 28.18



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 19.29 0.00 19.29 0.00 19.29 0.00 19.29
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 19.36 0.00 19.36 0.00 19.36 0.00 19.36
December 1.83 19.14 0.00 19.14 0.00 19.14 0.00 19.14
                 
Annual Sum or Average 3.67 19.22 0.00 19.22 0.00 19.22 0.00 19.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.83 19.36 0.00 19.36 0.00 19.36 0.00 19.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 19.26 0.00 19.26 0.00 19.26 0.00 19.26
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.33 28.02 2.33 28.02
May 0.00 0.00 0.00 0.00 2.17 28.03 2.17 28.03
June 0.00 0.00 0.00 0.00 4.50 27.90 4.50 27.90
July 0.00 0.00 0.00 0.00 6.33 28.06 6.33 28.06
August 0.00 0.00 0.00 0.00 4.83 27.95 4.83 27.95
September 0.00 0.00 0.00 0.00 4.00 27.84 4.00 27.84
October 0.00 0.00 0.00 0.00 0.33 27.40 0.33 27.40
November 0.50 19.37 0.00 19.37 0.00 19.37 0.00 19.37
December 2.50 19.46 0.00 19.46 0.00 19.46 0.00 19.46
                 
Annual Sum or Average 3.83 19.40 0.00 19.40 24.50 26.80 24.50 27.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.50 19.46 0.00 19.46 6.33 28.06 6.33 28.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.34 0.00 19.34 0.83 26.40 0.83 27.04
February 0.00 0.00 0.00 0.00 1.00 27.91 1.00 27.91
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.00 28.24 2.50 28.31
May 0.00 0.00 0.00 0.00 2.50 27.59 2.50 27.59
June 0.00 0.00 0.00 0.00 2.50 27.64 2.50 27.64
July 0.00 0.00 0.00 0.00 5.50 27.82 5.33 27.83
August 0.00 0.00 0.00 0.00 6.67 28.06 6.50 28.07
September 0.00 0.00 0.00 0.00 6.67 28.29 6.67 28.29
October 0.00 0.00 0.00 0.00 1.83 28.08 1.83 28.08
November 0.00 0.00 0.00 0.00 1.67 27.76 1.67 27.76
December 1.00 19.32 0.00 19.32 0.00 19.32 0.00 19.32
                 
Annual Sum or Average 1.17 19.33 0.00 19.33 32.17 27.68 31.33 27.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.34 0.00 19.34 6.67 28.29 6.67 28.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 19.37 0.00 19.37 0.00 19.37 0.00 19.37
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.17 28.60 1.17 28.63
May 0.00 0.00 0.00 0.00 5.33 28.10 2.50 28.12
June 0.00 0.00 0.00 0.00 4.33 28.34 2.17 28.34
July 0.00 0.00 0.00 0.00 7.67 28.48 3.50 28.52
August 0.00 0.00 0.00 0.00 5.83 28.32 3.50 28.36
September 0.00 0.00 0.00 0.00 3.50 27.94 2.83 27.99
October 0.00 0.00 0.00 0.00 0.33 27.38 0.33 27.38
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 19.34 0.00 19.34 0.00 19.34 0.00 19.34
                 
Annual Sum or Average 1.33 19.35 0.00 19.35 29.17 27.90 16.00 28.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.37 0.00 19.37 7.67 28.60 3.50 28.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 16.67 18.99 6.33 19.23 0.00 19.23 0.00 19.23
February 10.50 19.11 2.33 19.29 0.00 19.29 0.00 19.29
March 3.33 19.28 0.50 19.41 0.00 19.41 0.00 19.41
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.17 19.35 0.00 19.35 0.00 19.35 0.00 19.35
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 1.17 19.26 0.00 19.26 0.00 19.26 0.00 19.26
November 10.33 18.65 2.67 18.92 0.00 18.92 0.00 18.92
December 22.83 18.37 7.33 18.67 0.00 18.67 0.00 18.67
                 
Annual Sum or Average 65.00 18.76 19.17 19.00 0.00 19.00 0.00 19.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22.83 19.35 7.33 19.41 0.00 19.41 0.00 19.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.17 18.22 0.00 18.22 0.00 18.22 0.00 18.22
February 4.67 18.89 0.00 18.89 0.00 18.89 0.00 18.89
March 2.00 19.17 0.00 19.17 0.00 19.17 0.00 19.17
April 0.00 0.00 0.00 0.00 2.50 27.90 2.50 27.90
May 0.17 19.32 0.00 19.32 1.50 27.03 1.50 27.43
June 0.00 0.00 0.00 0.00 4.17 27.84 4.00 27.85
July 0.00 0.00 0.00 0.00 5.50 28.06 5.33 28.07
August 0.00 0.00 0.00 0.00 4.67 27.76 4.67 27.76
September 0.00 0.00 0.00 0.00 2.50 27.57 2.50 27.57
October 0.83 19.27 0.00 19.27 0.00 19.27 0.00 19.27
November 3.83 18.33 0.00 18.33 0.00 18.33 0.00 18.33
December 10.00 17.11 0.50 17.01 0.00 17.01 0.00 17.01
                 
Annual Sum or Average 26.67 18.05 0.50 17.99 20.83 22.27 20.50 23.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.01 0.00 17.01
Maximum of Months 10.00 19.32 0.50 19.32 5.50 28.06 5.33 28.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 18.55 0.00 18.55 0.17 18.87 0.17 19.17
February 3.33 19.05 0.00 19.05 0.33 19.81 0.33 20.45
March 1.50 19.19 0.00 19.19 0.00 19.19 0.00 19.19
April 0.00 0.00 0.00 0.00 2.33 28.49 1.83 28.61
May 0.17 19.36 0.00 19.36 1.50 26.73 1.50 27.12
June 0.00 0.00 0.00 0.00 2.83 27.63 2.67 27.64
July 0.00 0.00 0.00 0.00 5.33 27.84 5.00 27.85
August 0.00 0.00 0.00 0.00 6.33 28.06 6.17 28.07
September 0.00 0.00 0.00 0.00 6.17 28.13 6.00 28.14
October 0.33 19.42 0.00 19.42 1.33 26.19 1.33 26.94
November 2.83 18.65 0.00 18.65 0.67 20.36 0.67 21.52
December 6.17 18.45 0.00 18.45 0.00 18.45 0.00 18.45
                 
Annual Sum or Average 18.67 18.70 0.00 18.70 27.00 24.18 25.67 25.55
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.45 0.00 18.45
Maximum of Months 6.17 19.42 0.00 19.42 6.33 28.49 6.17 28.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.83 18.51 0.00 18.51 0.00 18.51 0.00 18.51
February 2.50 19.08 0.00 19.08 0.00 19.08 0.00 19.08
March 0.67 19.24 0.00 19.24 0.00 19.24 0.00 19.24
April 0.00 0.00 0.00 0.00 2.33 28.58 1.33 28.62
May 0.00 0.00 0.00 0.00 4.67 28.10 2.50 28.09
June 0.00 0.00 0.00 0.00 4.33 28.39 2.33 28.43
July 0.00 0.00 0.00 0.00 7.67 28.51 3.67 28.56
August 0.00 0.00 0.00 0.00 5.83 28.35 3.67 28.40
September 0.00 0.00 0.00 0.00 2.83 27.94 2.67 27.94
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.50 18.74 0.00 18.74 0.00 18.74 0.00 18.74
December 5.00 18.58 0.00 18.58 0.00 18.58 0.00 18.58
                 
Annual Sum or Average 14.50 18.70 0.00 18.70 27.67 25.02 16.17 25.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.00 19.24 0.00 19.24 7.67 28.58 3.67 28.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.57 0.00 27.57
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.33 27.57 0.00 27.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 27.57 0.00 27.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 2.00 28.49 2.00 28.49
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.00 28.49 2.00 28.49
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 28.49 2.00 28.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 133.67 23.89 86.00 24.71 0.00 24.71
February 91.50 23.95 75.17 24.86 0.00 24.86
March 73.83 24.00 74.67 24.98 0.00 24.98
April 24.17 24.00 99.83 25.76 0.00 25.76
May 6.33 24.00 142.83 25.42 0.00 25.42
June 0.00 0.00 270.50 24.74 0.00 24.74
July 0.00 0.00 371.50 24.74 0.00 24.74
August 0.00 0.00 396.67 24.56 0.00 24.56
September 0.00 0.00 270.17 24.86 0.00 24.86
October 3.50 24.00 166.83 25.46 0.00 25.46
November 21.33 23.99 132.83 25.52 0.00 25.52
December 67.83 23.96 95.00 25.20 0.00 25.20
             
Annual Sum or Average 422.17 23.95 2182.00 24.95 0.00 24.95
Minimum of Months 0.00 0.00 74.67 24.56 0.00 24.56
Maximum of Months 133.67 24.00 396.67 25.76 0.00 25.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 213.33 23.97 46.33 24.25 12.00 24.34
February 111.50 23.90 44.50 24.35 0.00 24.35
March 59.67 23.98 72.33 24.94 0.00 24.94
April 5.00 23.99 91.33 25.54 0.00 25.54
May 11.83 23.91 124.67 24.82 0.00 24.82
June 0.00 0.00 307.00 24.41 0.00 24.41
July 0.00 0.00 402.33 24.38 0.00 24.38
August 0.00 0.00 435.33 24.32 0.00 24.32
September 0.00 0.00 268.83 24.43 0.00 24.43
October 9.67 23.93 165.83 25.03 0.00 25.03
November 42.67 23.97 124.17 24.95 0.00 24.95
December 92.50 23.95 80.67 24.75 0.00 24.75
             
Annual Sum or Average 546.17 23.95 2163.33 24.56 12.00 24.56
Minimum of Months 0.00 0.00 44.50 24.25 0.00 24.32
Maximum of Months 213.33 23.99 435.33 25.54 12.00 25.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 463.67 23.10 12.50 23.07 12.50 23.04
February 419.17 23.34 0.00 23.34 0.00 23.34
March 449.83 23.58 0.00 23.58 0.00 23.58
April 202.83 23.75 17.50 23.87 0.00 23.87
May 162.00 23.63 48.17 23.87 0.00 23.87
June 28.17 23.66 190.33 24.27 0.00 24.27
July 19.67 23.58 252.33 24.24 0.00 24.24
August 3.17 23.59 258.33 24.25 0.00 24.25
September 67.33 23.64 136.17 24.13 0.00 24.13
October 239.83 23.52 23.33 23.61 0.00 23.61
November 393.33 23.38 0.00 23.38 0.00 23.38
December 495.17 22.85 0.00 22.85 0.00 22.85
             
Annual Sum or Average 2944.17 23.33 938.67 23.57 12.50 23.57
Minimum of Months 3.17 22.85 0.00 22.85 0.00 22.85
Maximum of Months 495.17 23.75 258.33 24.27 12.50 24.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.35 137.33 21.09 137.33 20.92
February 454.00 21.60 81.33 21.37 81.33 21.20
March 514.00 22.15 28.67 22.06 28.67 21.98
April 369.17 23.22 0.00 23.22 0.00 23.22
May 317.67 23.23 36.83 23.32 0.00 23.32
June 132.67 23.37 151.50 23.80 0.00 23.80
July 122.17 23.34 225.33 23.92 0.00 23.92
August 98.83 23.41 208.33 23.91 0.00 23.91
September 248.33 23.16 77.33 23.38 0.00 23.38
October 475.17 22.46 3.00 22.44 3.00 22.43
November 489.00 21.77 59.50 21.62 59.50 21.49
December 497.00 21.17 149.00 20.90 149.00 20.73
             
Annual Sum or Average 4220.00 22.21 1158.17 22.29 458.83 22.12
Minimum of Months 98.83 21.17 0.00 20.90 0.00 20.73
Maximum of Months 514.00 23.41 225.33 23.92 149.00 23.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 495.33 22.43 17.83 22.38 17.83 22.34
February 438.17 22.72 0.00 22.72 0.00 22.72
March 450.83 23.24 6.33 23.27 0.00 23.27
April 226.00 23.61 15.83 23.72 0.00 23.72
May 198.33 23.50 60.00 23.70 0.00 23.70
June 45.17 23.73 250.83 24.20 0.00 24.20
July 6.33 23.72 351.67 24.34 0.00 24.34
August 18.33 23.71 334.50 24.21 0.00 24.21
September 169.67 23.42 114.50 23.75 0.00 23.75
October 335.67 23.20 18.50 23.28 0.00 23.28
November 430.17 23.02 0.00 23.02 0.00 23.02
December 497.00 22.66 0.00 22.66 0.00 22.66
             
Annual Sum or Average 3311.00 22.99 1170.00 23.32 17.83 23.31
Minimum of Months 6.33 22.43 0.00 22.38 0.00 22.34
Maximum of Months 497.00 23.73 351.67 24.34 17.83 24.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 471.50 22.44 21.17 22.42 17.17 22.37
February 410.17 22.66 5.17 22.69 0.00 22.69
March 439.17 23.01 2.67 23.03 0.00 23.03
April 178.50 23.59 115.50 24.00 5.17 24.05
May 140.33 23.59 184.00 24.18 7.67 24.25
June 69.67 24.30 311.17 24.35 13.83 24.45
July 44.00 25.89 376.17 24.65 30.00 24.81
August 49.67 24.86 353.17 24.43 18.67 24.54
September 123.00 23.93 255.00 24.33 17.67 24.45
October 303.67 23.03 59.50 23.28 0.67 23.29
November 440.67 22.82 2.50 22.83 0.00 22.83
December 490.33 22.28 10.33 22.25 10.33 22.22
             
Annual Sum or Average 3160.67 22.93 1696.33 23.46 121.17 23.51
Minimum of Months 44.00 22.28 2.50 22.25 0.00 22.22
Maximum of Months 490.33 25.89 376.17 24.65 30.00 24.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 402.17 22.24 67.67 22.50 17.00 22.48
February 334.67 22.50 66.17 22.83 5.17 22.84
March 403.83 22.87 11.17 22.91 0.00 22.91
April 182.00 23.65 158.83 24.05 9.00 24.13
May 189.17 23.34 155.17 23.88 4.67 23.92
June 84.67 24.01 279.17 24.25 12.50 24.34
July 57.00 25.00 356.50 24.53 24.17 24.67
August 51.50 25.46 376.33 24.52 28.00 24.68
September 121.50 24.16 274.17 24.40 27.00 24.57
October 293.33 23.08 129.33 23.50 6.00 23.55
November 381.33 22.74 49.67 22.99 4.17 23.03
December 433.50 22.16 45.33 22.28 16.17 22.23
             
Annual Sum or Average 2934.67 22.89 1969.50 23.50 153.83 23.57
Minimum of Months 51.50 22.16 11.17 22.28 0.00 22.23
Maximum of Months 433.50 25.46 376.33 24.53 28.00 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 397.67 23.21 19.33 23.29 0.00 23.29
February 238.33 23.71 54.00 23.90 1.67 23.92
March 120.67 23.96 75.17 24.50 0.00 24.50
April 18.50 26.43 281.83 25.05 14.33 25.14
May 55.83 24.61 234.33 24.62 15.17 24.74
June 25.50 26.81 438.50 24.64 25.33 24.76
July 42.83 27.04 481.83 24.86 42.83 25.03
August 38.33 27.07 505.33 24.73 38.33 24.89
September 40.50 25.28 326.33 24.59 19.00 24.71
October 70.33 23.96 172.33 24.59 3.33 24.62
November 111.00 23.89 110.83 24.46 0.67 24.47
December 193.83 23.96 42.00 24.23 0.00 24.23
             
Annual Sum or Average 1353.33 24.03 2741.83 24.47 160.67 24.57
Minimum of Months 18.50 23.21 19.33 23.29 0.00 23.29
Maximum of Months 397.67 27.07 505.33 25.05 42.83 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.91 241.17 20.74 241.17 20.66
February 454.00 21.05 154.67 20.87 154.67 20.77
March 514.00 21.74 51.50 21.65 51.50 21.57
April 408.50 22.79 6.67 22.80 2.83 22.78
May 364.17 22.93 26.17 23.01 0.00 23.01
June 156.67 23.23 140.50 23.67 0.00 23.67
July 129.50 23.31 205.00 23.84 0.00 23.84
August 173.33 23.24 177.33 23.64 0.00 23.64
September 321.67 22.88 49.50 23.03 0.00 23.03
October 494.67 22.06 12.67 22.02 12.67 21.98
November 489.00 21.20 108.33 21.04 108.33 20.93
December 497.00 20.58 295.00 20.45 295.00 20.38
             
Annual Sum or Average 4504.50 21.85 1468.50 21.86 866.17 21.67
Minimum of Months 129.50 20.58 6.67 20.45 0.00 20.38
Maximum of Months 514.00 23.31 295.00 23.84 295.00 23.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 21.14 164.67 20.95 164.67 20.84
February 380.50 21.45 92.83 21.27 92.83 21.14
March 428.33 22.00 40.17 21.89 40.17 21.80
April 210.00 23.06 72.67 23.47 6.83 23.54
May 182.50 23.09 126.83 23.76 7.00 23.83
June 121.00 23.79 218.83 24.23 16.67 24.36
July 83.83 24.59 266.00 24.66 28.17 24.84
August 99.50 24.08 246.83 24.37 19.67 24.51
September 163.00 23.43 167.00 24.09 16.50 24.22
October 356.00 22.19 26.17 22.29 6.33 22.26
November 416.00 21.42 81.33 21.26 81.33 21.15
December 422.00 20.66 256.33 20.50 256.33 20.42
             
Annual Sum or Average 3289.67 21.99 1759.67 22.37 736.50 22.22
Minimum of Months 83.83 20.66 26.17 20.50 6.33 20.42
Maximum of Months 428.33 24.59 266.00 24.66 256.33 24.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 425.00 21.69 147.00 21.73 105.00 21.58
February 356.67 21.88 100.67 22.09 48.00 21.98
March 449.83 22.19 31.67 22.13 26.17 22.06
April 234.00 23.05 147.50 23.63 7.83 23.70
May 241.17 22.92 141.17 23.50 5.83 23.56
June 165.17 23.45 239.67 23.96 11.33 24.04
July 121.17 23.86 280.83 24.27 22.33 24.41
August 120.67 24.08 311.67 24.27 26.17 24.43
September 162.50 23.69 252.00 24.19 26.67 24.37
October 327.50 22.42 112.83 22.91 8.83 22.95
November 411.33 21.84 81.50 21.98 46.17 21.90
December 467.00 21.21 204.33 21.03 191.17 20.88
             
Annual Sum or Average 3482.00 22.31 2050.83 22.81 525.50 22.73
Minimum of Months 120.67 21.21 31.67 21.03 5.83 20.88
Maximum of Months 467.00 24.08 311.67 24.27 191.17 24.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 490.33 21.37 142.33 21.19 142.33 21.07
February 416.50 21.64 71.17 21.54 62.67 21.42
March 487.33 22.25 22.83 22.21 18.67 22.16
April 259.83 23.25 88.00 23.55 7.00 23.62
May 232.00 23.26 132.17 23.68 10.50 23.78
June 94.17 23.81 278.00 24.21 12.83 24.30
July 78.00 24.20 345.67 24.38 18.67 24.49
August 77.17 24.18 340.00 24.27 17.33 24.38
September 194.67 23.36 173.67 23.86 14.00 23.97
October 415.83 22.43 35.83 22.58 2.17 22.58
November 474.33 21.69 60.00 21.55 60.00 21.43
December 497.00 20.91 221.67 20.74 221.67 20.65
             
Annual Sum or Average 3717.17 22.15 1911.33 22.55 587.83 22.44
Minimum of Months 77.17 20.91 22.83 20.74 2.17 20.65
Maximum of Months 497.00 24.20 345.67 24.38 221.67 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.25 374.17 20.12 374.17 20.07
February 454.00 20.34 297.33 20.17 297.33 20.10
March 514.00 20.95 235.83 20.78 235.83 20.69
April 435.50 22.21 55.50 22.06 51.67 21.91
May 413.67 22.37 43.00 22.41 15.00 22.34
June 213.50 22.83 125.33 23.31 0.00 23.31
July 195.67 22.94 195.00 23.56 0.00 23.56
August 227.67 22.88 162.67 23.37 0.00 23.37
September 366.33 22.34 46.00 22.45 8.17 22.40
October 502.00 21.18 130.00 20.95 130.00 20.80
November 489.00 20.44 286.17 20.26 286.17 20.17
December 497.00 20.04 429.33 19.97 429.33 19.94
             
Annual Sum or Average 4810.33 21.30 2380.33 21.19 1827.67 20.95
Minimum of Months 195.67 20.04 43.00 19.97 0.00 19.94
Maximum of Months 514.00 22.94 429.33 23.56 429.33 23.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.45 338.33 20.28 338.33 20.20
February 454.00 20.73 250.83 20.48 250.83 20.37
March 514.00 21.25 198.83 21.03 198.83 20.91
April 260.17 22.58 89.00 22.86 24.33 22.82
May 239.00 22.65 136.50 23.24 8.50 23.25
June 147.00 23.34 257.83 23.99 16.67 24.10
July 121.67 23.89 320.17 24.35 25.67 24.49
August 137.33 23.59 308.33 24.13 18.83 24.24
September 205.50 22.78 204.83 23.60 11.00 23.65
October 442.17 21.47 108.00 21.28 100.83 21.11
November 489.00 20.66 241.00 20.43 241.00 20.31
December 497.00 20.14 399.33 20.03 399.33 19.99
             
Annual Sum or Average 4008.83 21.39 2853.00 21.66 1634.17 21.42
Minimum of Months 121.67 20.14 89.00 20.03 8.50 19.99
Maximum of Months 514.00 23.89 399.33 24.35 399.33 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 454.50 20.95 262.33 20.76 247.33 20.61
February 389.67 21.15 201.67 21.04 170.33 20.84
March 487.17 21.48 165.00 21.22 165.00 21.07
April 267.17 22.45 151.00 22.92 34.33 22.85
May 294.67 22.40 137.83 22.93 16.50 22.88
June 198.67 22.97 218.83 23.66 12.00 23.75
July 165.33 23.32 263.50 24.01 22.00 24.15
August 160.67 23.53 285.83 24.05 25.17 24.21
September 213.50 22.99 235.50 23.73 27.33 23.86
October 386.17 21.70 140.83 21.94 63.17 21.81
November 445.33 21.09 200.83 20.94 180.67 20.77
December 480.83 20.58 331.50 20.37 328.17 20.27
             
Annual Sum or Average 3943.67 21.71 2594.67 22.01 1292.00 21.79
Minimum of Months 160.67 20.58 137.83 20.37 12.00 20.27
Maximum of Months 487.17 23.53 331.50 24.05 328.17 24.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.00 20.70 291.67 20.48 291.67 20.38
February 428.83 20.96 192.00 20.71 190.00 20.58
March 498.00 21.49 144.00 21.29 141.17 21.16
April 312.33 22.67 98.17 22.92 25.17 22.90
May 298.83 22.74 127.83 23.22 12.00 23.29
June 152.50 23.33 248.83 23.95 13.83 24.04
July 120.33 23.56 308.17 24.17 18.67 24.29
August 127.67 23.61 298.50 24.08 17.67 24.20
September 259.33 22.80 154.00 23.37 15.33 23.46
October 445.83 21.64 80.83 21.63 54.33 21.49
November 481.83 20.94 190.50 20.71 190.50 20.58
December 497.00 20.37 359.00 20.23 359.00 20.17
             
Annual Sum or Average 4120.50 21.61 2493.50 21.85 1329.33 21.64
Minimum of Months 120.33 20.37 80.83 20.23 12.00 20.17
Maximum of Months 498.00 23.61 359.00 24.17 359.00 24.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 1.67 27.00 454.00 27.00 1.67 27.00
March 2.67 27.00 514.00 27.00 2.67 27.00
April 53.67 27.00 485.00 27.00 53.67 27.00
May 5.83 27.00 508.00 27.00 5.83 27.00
June 42.83 27.00 496.00 27.00 42.83 27.00
July 124.00 27.00 497.00 27.00 124.00 27.00
August 225.50 27.00 514.00 27.00 225.50 27.00
September 10.67 27.00 485.00 27.00 10.67 27.00
October 6.00 27.00 502.00 27.00 6.00 27.00
November 0.50 27.00 489.00 27.00 0.50 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 473.33 27.00 5943.00 27.00 473.33 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 225.50 27.00 514.00 27.00 225.50 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 480.83 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 7.67 27.00 485.00 27.00 7.67 27.00
May 1.50 27.00 508.00 27.00 1.50 27.00
June 5.83 27.00 496.00 27.00 5.83 27.00
July 12.67 27.00 497.00 27.00 12.67 27.00
August 22.50 27.00 514.00 27.00 22.50 27.00
September 2.33 27.00 485.00 27.00 2.33 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 485.50 27.00 0.00 27.00
             
Annual Sum or Average 52.50 27.00 5910.33 27.00 52.50 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 22.50 27.00 514.00 27.00 22.50 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 97.83 25.24 291.50 26.55 0.00 26.55
February 2.83 27.00 373.33 27.00 0.00 27.00
March 0.00 0.00 480.17 27.00 0.00 27.00
April 11.17 27.00 485.00 27.00 11.17 27.00
May 4.50 27.00 508.00 27.00 4.50 27.00
June 16.33 27.00 496.00 27.00 16.33 27.00
July 27.83 27.00 497.00 27.00 27.83 27.00
August 37.50 27.00 514.00 27.00 37.50 27.00
September 3.83 27.00 485.00 27.00 3.83 27.00
October 0.00 0.00 498.17 27.00 0.00 27.00
November 0.00 0.00 442.17 27.00 0.00 27.00
December 5.83 27.00 380.33 27.00 0.00 27.00
             
Annual Sum or Average 207.67 26.17 5450.67 26.97 101.17 26.97
Minimum of Months 0.00 0.00 291.50 26.55 0.00 26.55
Maximum of Months 97.83 27.00 514.00 27.00 37.50 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 216.50 27.00 502.00 27.00 216.50 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 489.17 27.00 508.00 27.00 489.17 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.01 497.00 27.01 497.00 27.01
August 514.00 27.02 514.00 27.02 514.00 27.02
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5638.67 27.00 5943.00 27.00 5638.67 27.00
Minimum of Months 216.50 27.00 454.00 27.00 216.50 27.00
Maximum of Months 514.00 27.02 514.00 27.02 514.00 27.02



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00001 27.65544 0.79202 18.32851
February 454.00000 27.00000 27.94197 0.84748 20.22213
March 514.00000 27.00000 27.83813 0.88703 21.65613
April 485.00000 27.00000 28.44533 0.96502 24.72603
May 508.00000 27.00013 32.82575 0.22236 6.12755
June 496.00000 27.00043 35.87633 0.31811 7.17709
July 497.00000 27.00035 36.13618 0.37889 8.05647
August 514.00000 27.00016 36.29921 0.41601 8.67031
September 485.00000 27.00042 36.14559 0.25256 6.41207
October 502.00000 27.00014 32.71622 0.90896 22.48376
November 489.00000 27.00006 30.55961 0.90559 22.36859
December 497.00000 26.99999 26.76266 0.88752 21.67275
           
Annual Sum or Average 5943.00000 27.00014 31.62711 0.64646 15.60570
Minimum of Months 454.00000 26.99999 26.76266 0.22236 6.12755
Maximum of Months 514.00000 27.00043 36.29921 0.96502 24.72603



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99797 27.66712 0.67287 14.65650
February 454.00000 27.00001 27.92695 0.71463 15.87634
March 514.00000 27.00000 27.82678 0.74906 16.90435
April 485.00000 27.00000 28.43498 0.84604 20.22187
May 508.00000 27.00013 32.82746 0.13766 5.56584
June 496.00000 27.00041 35.89739 0.22156 6.13305
July 497.00000 27.00034 36.14390 0.25407 6.45567
August 514.00000 27.00017 36.29970 0.27216 6.63659
September 485.00000 27.00040 36.22713 0.17051 5.73803
October 502.00000 27.00013 32.71994 0.80039 18.59093
November 489.00000 27.00006 30.54241 0.74596 16.82418
December 497.00000 27.00000 26.74593 0.67568 14.68493
           
Annual Sum or Average 5943.00000 26.99997 31.63187 0.51971 12.31567
Minimum of Months 454.00000 26.99797 26.74593 0.13766 5.56584
Maximum of Months 514.00000 27.00041 36.29970 0.84604 20.22187



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.56124 28.48036 0.50367 11.28501
February 454.00000 27.00001 27.93642 0.62561 13.44391
March 514.00000 27.00000 27.83175 0.66667 14.49543
April 485.00000 27.00000 28.43861 0.80335 18.86455
May 508.00000 27.00018 32.84065 0.09001 5.53871
June 496.00000 27.00042 35.91075 0.20091 6.08726
July 497.00000 27.00035 36.15483 0.23813 6.43345
August 514.00000 27.00018 36.31027 0.25217 6.53571
September 485.00000 27.00039 36.29502 0.12392 5.61596
October 502.00000 27.00013 32.76854 0.72319 16.18173
November 489.00000 27.00006 30.56723 0.65590 14.20460
December 497.00000 27.00000 26.75202 0.59257 12.52368
           
Annual Sum or Average 5943.00000 26.96308 31.71828 0.45447 10.89948
Minimum of Months 454.00000 26.56124 26.75202 0.09001 5.53871
Maximum of Months 514.00000 27.00042 36.31027 0.80335 18.86455



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00001 30.07495 1.02290 27.10025
February 454.00000 27.00046 30.01296 1.19002 34.76568
March 514.00000 27.00025 29.87753 1.33955 42.32249
April 485.00000 27.00104 28.56960 1.48133 49.88937
May 508.00000 27.00000 30.98071 0.46632 9.59741
June 496.00000 27.00060 35.12579 0.73343 16.36536
July 497.00000 27.00522 36.00822 0.95654 24.36215
August 514.00000 27.01906 33.85428 1.13568 32.18012
September 485.00000 26.99987 34.71794 0.52384 10.82243
October 502.00000 27.00015 31.39264 1.22849 36.66311
November 489.00000 27.00021 30.49709 1.35851 43.31803
December 497.00000 27.00046 28.70249 1.46657 49.09045
           
Annual Sum or Average 5943.00000 27.00234 31.66248 1.07429 31.33326
Minimum of Months 454.00000 26.99987 28.56960 0.46632 9.59741
Maximum of Months 514.00000 27.01906 36.00822 1.48133 49.88937



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.38669 28.41701 0.35476 8.09111
February 454.00000 24.39127 29.18070 0.36376 8.08024
March 514.00000 24.34120 28.41661 0.35509 7.94556
April 485.00000 24.47383 28.35164 0.39541 8.72677
May 508.00000 24.43463 34.60542 -0.4402 9.85074
June 496.00000 24.40594 42.36807 -0.3828 8.81471
July 497.00000 24.55176 43.89833 -0.3207 8.14202
August 514.00000 24.43570 44.74806 -0.3417 8.34289
September 485.00000 24.48175 41.62469 -0.3638 8.85441
October 502.00000 24.50918 35.14810 0.44825 9.69624
November 489.00000 24.50459 32.05858 0.42198 9.21560
December 497.00000 24.45214 27.47243 0.37106 8.31498
           
Annual Sum or Average 5943.00000 24.44724 34.73749 0.06871 8.67553
Minimum of Months 454.00000 24.34120 27.47243 -0.4402 7.94556
Maximum of Months 514.00000 24.55176 44.74806 0.44825 9.85074



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.18186 31.72410 0.32473 7.67575
February 454.00000 24.23264 31.22286 0.34211 7.59380
March 514.00000 24.29005 30.23794 0.36223 8.00533
April 485.00000 24.32979 29.38229 0.39223 8.46688
May 508.00000 24.24877 35.90472 -0.4758 10.07507
June 496.00000 24.25721 43.44766 -0.3980 8.65412
July 497.00000 24.31167 45.21689 -0.3554 8.01364
August 514.00000 24.27235 45.58526 -0.3550 7.99381
September 485.00000 24.24268 42.84628 -0.4184 8.98279
October 502.00000 24.37312 37.00561 0.43036 9.18870
November 489.00000 24.36749 34.07689 0.40490 8.72748
December 497.00000 24.33858 29.54673 0.35920 7.97002
           
Annual Sum or Average 5943.00000 24.28736 36.39445 0.04816 8.45068
Minimum of Months 454.00000 24.18186 29.38229 -0.4758 7.59380
Maximum of Months 514.00000 24.37312 45.58526 0.43036 10.07507



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.16722 35.13987 0.06079 5.68001
February 454.00000 23.39199 33.75995 0.11308 5.65959
March 514.00000 23.64230 32.93411 0.17750 5.94087
April 485.00000 24.03408 31.37407 0.28844 6.89543
May 508.00000 24.00984 37.19232 -0.5849 12.52636
June 496.00000 24.10181 44.58975 -0.4867 10.19462
July 497.00000 24.11882 46.46161 -0.4662 9.76961
August 514.00000 24.10500 46.93375 -0.4612 9.63356
September 485.00000 24.02976 44.00463 -0.5190 10.88165
October 502.00000 23.86545 39.52401 0.28589 6.96162
November 489.00000 23.50365 37.26883 0.16496 6.02229
December 497.00000 22.85727 33.49210 -0.0304 5.57080
           
Annual Sum or Average 5943.00000 23.73807 38.59847 -0.1240 7.99793
Minimum of Months 454.00000 22.85727 31.37407 -0.5849 5.57080
Maximum of Months 514.00000 24.11882 46.93375 0.28844 12.52636



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.34935 36.73393 -0.4057 10.22475
February 454.00000 21.60375 37.16920 -0.3328 8.79886
March 514.00000 22.14653 36.16021 -0.1980 6.85869
April 485.00000 23.41889 33.13193 0.13013 6.15110
May 508.00000 23.53636 38.77059 -0.7589 18.30828
June 496.00000 23.90294 45.36301 -0.5583 12.06858
July 497.00000 23.94069 47.16946 -0.5264 11.40792
August 514.00000 23.93582 47.61656 -0.5249 11.13116
September 485.00000 23.58877 45.84728 -0.6833 15.75449
October 502.00000 22.53640 43.18962 -0.0491 6.13852
November 489.00000 21.77210 41.27325 -0.2667 7.76116
December 497.00000 21.16617 35.92233 -0.4606 10.98218
           
Annual Sum or Average 5943.00000 22.74959 40.72646 -0.3875 10.48120
Minimum of Months 454.00000 21.16617 33.13193 -0.7589 6.13852
Maximum of Months 514.00000 23.94069 47.61656 0.13013 18.30828



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.45292 32.83352 -0.1194 6.29312
February 454.00000 22.76587 33.15061 -0.0368 5.80326
March 514.00000 23.35857 31.47113 0.10292 5.84648
April 485.00000 23.90831 29.49516 0.26061 6.79536
May 508.00000 23.87648 35.72815 -0.6229 13.83168
June 496.00000 24.13106 42.71737 -0.4426 9.58266
July 497.00000 24.25400 44.39601 -0.3749 8.40921
August 514.00000 24.16096 45.05338 -0.4107 8.89372
September 485.00000 23.85457 42.84119 -0.5840 12.87717
October 502.00000 23.50641 38.32892 0.18910 6.29114
November 489.00000 23.13712 35.88217 0.07210 5.81269
December 497.00000 22.66140 31.55193 -0.0754 5.69518
           
Annual Sum or Average 5943.00000 23.51112 36.98820 -0.1718 8.02649
Minimum of Months 454.00000 22.45292 29.49516 -0.6229 5.69518
Maximum of Months 514.00000 24.25400 45.05338 0.26061 13.83168



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.55804 32.65632 -0.0924 6.49881
February 454.00000 22.81126 32.98428 -0.0193 6.19805
March 514.00000 23.18755 31.78807 0.06813 6.02640
April 485.00000 23.98592 28.91077 0.33682 8.36020
May 508.00000 24.07856 34.91915 -0.4743 11.78917
June 496.00000 24.18719 42.33890 -0.3528 9.27784
July 497.00000 24.37864 43.92698 -0.2601 8.43618
August 514.00000 24.23716 44.66206 -0.3050 8.68808
September 485.00000 24.14554 41.66428 -0.3995 10.68042
October 502.00000 23.49310 38.15694 0.20545 6.82197
November 489.00000 22.94706 36.29618 0.03123 5.94082
December 497.00000 22.30212 32.11760 -0.1561 6.44769
           
Annual Sum or Average 5943.00000 23.53092 36.73724 -0.1197 7.94076
Minimum of Months 454.00000 22.30212 28.91077 -0.4743 5.94082
Maximum of Months 514.00000 24.37864 44.66206 0.33682 11.78917



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.67394 32.04123 -0.0472 7.56777
February 454.00000 22.98464 32.07555 0.04697 7.37417
March 514.00000 23.12566 31.57527 0.05873 6.21972
April 485.00000 24.00988 28.81018 0.35359 8.87381
May 508.00000 23.90268 35.29697 -0.5571 13.84583
June 496.00000 24.12576 42.53110 -0.4028 9.79306
July 497.00000 24.30617 44.05772 -0.2993 8.62379
August 514.00000 24.27455 44.37044 -0.2715 8.40249
September 485.00000 24.16742 41.42427 -0.3433 10.48219
October 502.00000 23.55571 37.65951 0.25027 7.90371
November 489.00000 23.08660 35.63102 0.08088 6.93684
December 497.00000 22.45857 31.56612 -0.1131 7.32921
           
Annual Sum or Average 5943.00000 23.55921 36.46084 -0.1059 8.62020
Minimum of Months 454.00000 22.45857 28.81018 -0.5571 6.21972
Maximum of Months 514.00000 24.30617 44.37044 0.35359 13.84583



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.42509 30.70654 0.11806 6.18902
February 454.00000 23.97786 29.97531 0.28036 7.23883
March 514.00000 24.27074 28.58790 0.36780 8.23356
April 485.00000 24.55975 27.50291 0.54181 12.11327
May 508.00000 24.30032 34.19365 -0.3618 9.39710
June 496.00000 24.45537 41.36669 -0.1727 7.39848
July 497.00000 24.65044 42.95737 -0.0530 7.31271
August 514.00000 24.54683 43.45825 -0.0729 7.19523
September 485.00000 24.33852 41.00840 -0.3092 8.67029
October 502.00000 24.31488 35.63144 0.42710 9.33938
November 489.00000 24.26775 32.52416 0.37289 8.35944
December 497.00000 24.22508 27.83860 0.31631 7.35850
           
Annual Sum or Average 5943.00000 24.27929 34.68759 0.11932 8.23067
Minimum of Months 454.00000 23.42509 27.50291 -0.3618 6.18902
Maximum of Months 514.00000 24.65044 43.45825 0.54181 12.11327



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.90930 35.18247 -0.5228 11.87115
February 454.00000 21.05375 35.76483 -0.4669 10.45998
March 514.00000 21.74221 34.63525 -0.2919 7.68350
April 485.00000 22.99504 32.10128 0.02687 6.20395
May 508.00000 23.23529 37.54930 -0.8532 21.99792
June 496.00000 23.79919 43.95749 -0.5829 13.03754
July 497.00000 23.88141 45.64847 -0.5361 11.81806
August 514.00000 23.74742 46.62583 -0.5891 13.06574
September 485.00000 23.24683 44.59420 -0.8063 20.24915
October 502.00000 22.09148 42.24653 -0.1498 6.58800
November 489.00000 21.19576 39.59595 -0.4064 9.46045
December 497.00000 20.57942 34.45902 -0.6197 13.98558
           
Annual Sum or Average 5943.00000 22.38322 39.39524 -0.4840 12.21644
Minimum of Months 454.00000 20.57942 32.10128 -0.8532 6.20395
Maximum of Months 514.00000 23.88141 46.62583 0.02687 21.99792



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 21.14491 34.12941 -0.4644 10.86497
February 385.00000 21.47931 34.24803 -0.3641 9.18638
March 433.00000 22.02160 33.61247 -0.2258 7.43493
April 410.00000 23.63033 29.78998 0.23044 7.91815
May 430.00000 23.78414 35.34227 -0.5961 15.82868
June 418.00000 24.06626 42.45162 -0.4164 11.22475
July 422.00000 24.34225 43.77065 -0.3034 9.92019
August 433.00000 24.15794 44.61969 -0.3639 10.33765
September 410.00000 23.94035 41.84133 -0.4975 13.77297
October 427.00000 22.51901 40.38526 -0.0396 6.86165
November 417.00000 21.42539 38.51261 -0.3524 8.82700
December 422.00000 20.66027 33.73756 -0.5992 13.63528
           
Annual Sum or Average 5034.00000 22.77038 37.73476 -0.3334 10.49155
Minimum of Months 385.00000 20.66027 29.78998 -0.5992 6.86165
Maximum of Months 433.00000 24.34225 44.61969 0.23044 15.82868



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.10359 32.71832 -0.1996 9.11932
February 454.00000 22.41481 32.76836 -0.0983 8.65783
March 514.00000 22.42020 33.08384 -0.1150 7.11976
April 485.00000 23.66570 29.85328 0.26565 8.68385
May 508.00000 23.60133 36.12138 -0.6593 17.71871
June 496.00000 23.89846 43.28449 -0.4918 12.25042
July 497.00000 24.08518 44.70808 -0.3921 10.82926
August 514.00000 24.08572 45.01363 -0.3523 10.24233
September 485.00000 23.99382 41.72869 -0.3948 12.54477
October 502.00000 23.04331 39.34460 0.13358 8.07322
November 489.00000 22.24604 37.27092 -0.1282 8.20360
December 497.00000 21.39827 32.88677 -0.3987 11.02988
           
Annual Sum or Average 5943.00000 23.08357 37.44248 -0.2381 10.38771
Minimum of Months 454.00000 21.39827 29.85328 -0.6593 7.11976
Maximum of Months 514.00000 24.08572 45.01363 0.26565 17.71871



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.43337 34.11996 -0.3815 9.59509
February 454.00000 21.84969 33.97824 -0.2570 8.31606
March 514.00000 22.34206 33.33606 -0.1395 6.74759
April 485.00000 23.66488 30.26363 0.24129 7.82808
May 508.00000 23.72560 35.97950 -0.6037 15.91709
June 496.00000 24.08995 42.74022 -0.3793 10.22495
July 497.00000 24.20739 44.37507 -0.3112 9.46908
August 514.00000 24.13020 45.02548 -0.3537 9.54921
September 485.00000 23.80674 42.61575 -0.5421 14.11912
October 502.00000 22.72817 40.45648 0.01838 6.65332
November 489.00000 21.75651 38.34047 -0.2628 7.89375
December 497.00000 20.91047 33.84217 -0.5230 11.63017
           
Annual Sum or Average 5943.00000 22.89468 37.95844 -0.2922 9.83627
Minimum of Months 454.00000 20.91047 30.26363 -0.6037 6.65332
Maximum of Months 514.00000 24.20739 45.02548 0.24129 15.91709



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.24524 36.40845 -0.7378 18.72103
February 454.00000 20.33824 37.11175 -0.6905 17.14858
March 514.00000 20.95199 36.07456 -0.5207 11.86679
April 485.00000 22.40838 33.26016 -0.1248 7.51020
May 508.00000 22.67068 38.84553 -1.0497 30.80416
June 496.00000 23.52529 44.72915 -0.6767 16.59337
July 497.00000 23.64760 46.28008 -0.6144 14.80824
August 514.00000 23.50787 47.31696 -0.6735 16.25895
September 485.00000 22.74253 45.98110 -0.9865 28.13823
October 502.00000 21.17781 44.38265 -0.3977 9.87579
November 489.00000 20.44477 41.18158 -0.6366 15.44291
December 497.00000 20.03640 35.58401 -0.8049 21.13082
           
Annual Sum or Average 5943.00000 21.81931 40.62671 -0.6599 17.36148
Minimum of Months 454.00000 20.03640 33.26016 -1.0497 7.51020
Maximum of Months 514.00000 23.64760 47.31696 -0.1248 30.80416



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.45128 35.96874 -0.6745 16.75558
February 454.00000 20.73023 36.36074 -0.5824 14.35384
March 514.00000 21.25408 35.53394 -0.4406 10.65793
April 485.00000 23.27906 30.68244 0.14395 8.12381
May 508.00000 23.45414 36.55823 -0.7076 19.65729
June 496.00000 23.88740 43.25099 -0.4662 12.66991
July 497.00000 24.14885 44.50734 -0.3515 10.81653
August 514.00000 23.99643 45.32754 -0.4020 11.33558
September 485.00000 23.62841 42.90500 -0.6022 16.84633
October 502.00000 21.78073 42.77359 -0.2396 8.89855
November 489.00000 20.65550 40.75360 -0.5769 13.85548
December 497.00000 20.14060 35.36012 -0.7700 19.90106
           
Annual Sum or Average 5943.00000 22.29449 39.19499 -0.4726 13.65007
Minimum of Months 454.00000 20.14060 30.68244 -0.7700 8.12381
Maximum of Months 514.00000 24.14885 45.32754 0.14395 19.90106



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.26116 34.23611 -0.4484 13.33889
February 454.00000 21.58903 34.33692 -0.3406 11.97123
March 514.00000 21.60878 34.75245 -0.3456 10.04085
April 485.00000 23.22718 30.74681 0.14500 9.00215
May 508.00000 23.16838 37.21620 -0.8190 24.32260
June 496.00000 23.64672 43.96910 -0.5790 15.55545
July 497.00000 23.87118 45.28841 -0.4645 13.52561
August 514.00000 23.89634 45.53765 -0.4218 12.59397
September 485.00000 23.64283 42.65842 -0.5308 17.23491
October 502.00000 22.25186 41.24658 -0.0872 9.18640
November 489.00000 21.38444 39.13365 -0.3776 11.73841
December 497.00000 20.69192 34.25163 -0.6157 16.44767
           
Annual Sum or Average 5943.00000 22.52561 38.65626 -0.4089 13.76579
Minimum of Months 454.00000 20.69192 30.74681 -0.8190 9.00215
Maximum of Months 514.00000 23.89634 45.53765 0.14500 24.32260



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.72332 35.39227 -0.5932 14.80232
February 454.00000 21.13117 35.31311 -0.4641 12.39150
March 514.00000 21.56699 34.76677 -0.3506 9.35651
April 485.00000 23.17724 31.23780 0.11595 8.19821
May 508.00000 23.30525 37.02046 -0.7543 22.11099
June 496.00000 23.88336 43.33565 -0.4525 12.73820
July 497.00000 24.03258 44.85532 -0.3715 11.53915
August 514.00000 23.96230 45.53045 -0.4162 11.53275
September 485.00000 23.41021 43.68963 -0.6863 19.66288
October 502.00000 21.92310 42.32241 -0.1952 8.17857
November 489.00000 20.98070 39.94228 -0.4818 11.83524
December 497.00000 20.37376 34.87028 -0.6939 17.07996
           
Annual Sum or Average 5943.00000 22.38158 39.05667 -0.4459 13.28849
Minimum of Months 454.00000 20.37376 31.23780 -0.7543 8.17857
Maximum of Months 514.00000 24.03258 45.53045 0.11595 22.11099



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.367504E+09 14648.76 20-JAN-12:00 53.17 0.185423E+10 0.00 0.222174E+10 0.36 5.17 10-JAN-06:40 0.00 0.00
February 0.998233E+09 25760.00 09-FEB-15:30 86.03 0.501564E+10 0.00 0.601387E+10 0.65 5.15 13-FEB-12:00 0.00 0.00
March 0.835073E+09 21333.60 30-MAR-14:05 87.03 0.420239E+10 0.00 0.503747E+10 0.59 5.15 21-MAR-05:40 0.00 0.00
April 0.831379E+10 88985.83 28-APR-14:30 97.17 0.553950E+11 0.00 0.637088E+11 0.79 7.96 28-APR-15:50 0.00 0.00
May 0.897339E+10 116622.24 22-MAY-13:40 101.51 0.600849E+11 0.00 0.690583E+11 0.79 7.96 31-MAY-15:40 0.00 0.00
June 0.229787E+11 121636.74 26-JUN-16:20 194.35 0.160145E+12 0.00 0.183124E+12 1.64 7.96 21-JUN-11:40 0.00 0.00
July 0.379815E+11 120412.34 22-JUL-09:40 331.77 0.263408E+12 0.00 0.301389E+12 2.72 7.96 21-JUL-13:40 0.00 0.00
August 0.497659E+11 118794.10 28-AUG-13:30 396.02 0.347065E+12 0.00 0.396831E+12 3.33 7.96 28-AUG-10:30 0.00 0.00
September 0.271310E+11 119197.45 12-SEP-12:20 245.67 0.186540E+12 0.00 0.213671E+12 2.05 7.96 13-SEP-12:00 0.00 0.00
October 0.592913E+10 65504.59 06-OCT-14:30 88.92 0.398612E+11 0.00 0.457903E+11 0.68 7.94 06-OCT-14:30 0.00 0.00
November 0.637650E+09 8305.96 24-NOV-12:00 64.91 0.321693E+10 0.00 0.385458E+10 0.45 5.16 20-NOV-06:30 0.00 0.00
December 0.937721E+09 6966.60 18-DEC-14:10 118.96 0.473281E+10 0.00 0.567053E+10 0.81 5.16 26-DEC-16:20 0.00 0.00
                         
Annual Sum or Average 0.164850E+12     1865.51 0.113152E+13 0.00 0.129637E+13 1.24     0.00 0.00
Minimum of Months 0.367504E+09 6966.60   53.17 0.185423E+10 0.00 0.222174E+10 0.36 5.15   0.00 0.00
Maximum of Months 0.497659E+11 121636.74   396.02 0.347065E+12 0.00 0.396831E+12 3.33 7.96   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.458930E+09 83662.20 22-MAY-14:05 2.00 0.356924E+10 0.00 0.402817E+10 0.02 7.93 22-MAY-14:05 0.00 0.00
June 0.344951E+10 87080.50 13-JUN-16:00 14.83 0.263046E+11 0.00 0.297541E+11 0.16 7.92 13-JUN-12:05 0.00 0.00
July 0.394300E+10 79875.21 21-JUL-12:05 16.83 0.302685E+11 0.00 0.342115E+11 0.17 7.96 21-JUL-13:40 0.00 0.00
August 0.248293E+10 92020.57 28-AUG-14:05 10.58 0.192012E+11 0.00 0.216841E+11 0.11 7.96 14-AUG-14:40 0.00 0.00
September 0.201873E+10 72526.54 12-SEP-16:00 9.17 0.153441E+11 0.00 0.173629E+11 0.10 7.96 27-SEP-14:05 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.123531E+11     53.42 0.946878E+11 0.00 0.107041E+12 0.05     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.394300E+10 92020.57   16.83 0.302685E+11 0.00 0.342115E+11 0.17 7.96   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.136730E+10 744.00 1554.28 29-JAN-06:00 31024.35 19-JAN-16:30 18.68 18.33 13.96
February 0.316419E+10 672.00 2395.53 07-FEB-15:00 63937.41 19-FEB-17:10 19.30 18.33 13.96
March 0.626627E+10 744.00 5060.08 25-MAR-13:00 109715.28 31-MAR-23:40 19.94 18.33 13.96
April 0.194446E+11 720.00 43776.24 22-APR-11:05 569242.38 30-APR-19:02 21.37 18.57 13.96
May 0.861037E+10 744.00 43776.24 11-MAY-16:00 103178.54 22-MAY-15:00 18.99 18.39 13.96
June 0.228070E+11 720.00 43776.24 09-JUN-11:00 354706.05 13-JUN-17:00 20.16 18.77 13.96
July 0.498988E+11 744.00 43776.24 05-JUL-13:30 522475.57 22-JUL-19:02 22.31 19.38 13.96
August 0.809852E+11 744.00 43776.24 01-AUG-07:00 609388.64 14-AUG-16:00 26.17 20.07 13.96
September 0.208211E+11 720.00 43776.24 09-SEP-12:40 74225.74 13-SEP-16:00 19.20 18.60 13.96
October 0.661584E+10 744.00 43776.24 07-OCT-14:30 81270.56 31-OCT-23:30 19.38 18.33 13.96
November 0.620245E+10 720.00 21133.82 24-NOV-12:00 110034.75 24-NOV-12:00 19.87 18.33 13.96
December 0.674124E+10 744.00 7000.91 23-DEC-11:00 144025.92 23-DEC-11:00 20.37 18.33 13.96
                   
Annual Sum or Average 0.232924E+12 8760.00         20.49 18.65 13.96
Minimum of Months 0.136730E+10 672.00 1554.28   31024.35   18.68 18.33 13.96
Maximum of Months 0.809852E+11 744.00 43776.24   609388.64   26.17 20.07 13.96



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 174609.59 09-JAN-05:21 20.93 20.92 0.55
February 0.00 0.00 0.00 01-FEB-00:10 174600.86 24-FEB-07:00 20.97 20.95 1.20
March 0.00 0.00 0.00 01-MAR-00:10 174543.01 08-MAR-06:20 20.99 20.98 0.97
April 50476649.83 42.76 1765.52 28-APR-15:00 791042.33 28-APR-15:00 21.58 21.44 4.54
May 0.178383E+09 53.59 12406.36 22-MAY-13:20 964071.96 22-MAY-13:40 21.72 21.57 4.79
June 0.118446E+10 133.42 12406.36 12-JUN-12:20 942062.84 21-JUN-13:20 21.70 21.30 10.62
July 0.125285E+10 245.60 12406.36 10-JUL-08:20 955438.57 22-JUL-09:40 21.75 21.12 17.67
August 0.130898E+10 322.98 12406.36 14-AUG-09:40 994719.41 28-AUG-13:40 21.92 21.09 22.16
September 0.728974E+09 169.16 12406.36 11-SEP-13:10 964744.50 25-SEP-12:40 21.55 21.08 13.17
October 19763994.78 33.54 363.81 06-OCT-14:30 591135.98 05-OCT-14:10 21.24 21.14 3.29
November 0.00 0.00 0.00 01-NOV-00:10 148217.06 27-NOV-10:05 20.98 20.97 0.74
December 0.00 0.00 0.00 01-DEC-00:10 171566.25 15-DEC-05:40 20.93 20.91 1.28
                   
Annual Sum or Average 0.472389E+10 1001.06         21.36 21.12 6.79
Minimum of Months 0.00 0.00 0.00   148217.06   20.93 20.91 0.55
Maximum of Months 0.130898E+10 322.98 12406.36   994719.41   21.92 21.57 22.16



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 20.93 20.93 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 20.97 20.97 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 20.99 20.99 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 21.58 21.58 0.00
May 55435699.79 1.67 12406.36 22-MAY-14:20 824196.51 22-MAY-15:20 21.72 21.71 0.10
June 0.473242E+09 11.00 12406.36 12-JUN-13:40 798418.21 21-JUN-15:00 21.70 21.64 0.67
July 0.346120E+09 12.67 12406.36 10-JUL-08:50 830061.74 21-JUL-10:50 21.75 21.69 0.76
August 0.179940E+09 8.50 12406.36 14-AUG-10:30 855337.35 21-AUG-12:50 21.92 21.88 0.51
September 0.119543E+09 4.25 12406.36 11-SEP-14:05 856953.90 27-SEP-14:40 21.55 21.53 0.26
October 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 21.24 21.24 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 20.98 20.98 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.93 20.93 0.00
                   
Annual Sum or Average 0.117428E+10 38.08         21.36 21.34 0.19
Minimum of Months 0.00 0.00 0.00   0.00   20.93 20.93 0.00
Maximum of Months 0.473242E+09 12.67 12406.36   856953.90   21.92 21.88 0.76



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.251729E+12 0.00 426.72 1071416.10 30-JAN-06:02 0.00 36.51 49.92 1.10 0.00 0.05 0.61 30-JAN-06:02
February 0.179262E+12 0.00 375.93 1113465.68 27-FEB-05:11 0.00 36.16 49.78 0.78 0.00 0.04 0.63 27-FEB-05:11
March 0.144622E+12 0.00 418.13 1049045.70 07-MAR-06:02 0.00 34.45 48.85 0.54 0.00 0.03 0.60 07-MAR-06:02
April 0.299842E+11 0.00 172.99 465223.81 07-APR-13:05 0.00 32.62 39.10 0.11 0.00 0.01 0.26 07-APR-13:05
May 0.188958E+11 0.00 171.75 789477.52 05-MAY-05:02 0.00 31.47 37.94 0.06 0.00 0.00 0.45 05-MAY-05:02
June 0.166895E+10 0.00 27.35 223543.03 28-JUN-09:10 0.00 31.93 33.03 0.01 0.00 0.00 0.13 28-JUN-09:10
July 0.226885E+09 0.00 7.54 44245.16 25-JUL-09:05 0.00 31.28 31.57 0.00 0.00 0.00 0.03 25-JUL-09:05
August 90573537.72 0.00 2.58 93551.31 31-AUG-09:05 0.00 30.73 30.84 0.00 0.00 0.00 0.05 31-AUG-09:05
September 0.362006E+10 0.00 54.02 274657.01 08-SEP-10:00 0.00 31.56 33.71 0.01 0.00 0.00 0.16 08-SEP-10:00
October 0.425035E+11 0.00 265.80 939808.00 28-OCT-05:02 0.00 32.11 42.09 0.14 0.00 0.01 0.53 28-OCT-05:02
November 0.137832E+12 0.00 381.70 1265984.13 25-NOV-05:11 0.00 33.57 47.58 0.54 0.00 0.03 0.72 25-NOV-05:11
December 0.276309E+12 0.00 436.75 1152764.40 12-DEC-05:11 0.00 36.41 50.30 1.12 0.00 0.06 0.66 12-DEC-05:11
                           
Annual Sum or Average 0.108674E+13 0.00 2741.27     0.00 33.22 41.19 0.37 0.00 0.02    
Minimum of Months 90573537.72 0.00 2.58 44245.16   0.00 30.73 30.84 0.00 0.00 0.00 0.03  
Maximum of Months 0.276309E+12 0.00 436.75 1265984.13   0.00 36.51 50.30 1.12 0.00 0.06 0.72  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 18.68 18.68 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 19.30 19.30 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 19.94 19.94 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 21.37 21.37 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 18.99 18.99 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 20.16 20.16 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 22.31 22.31 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:10 0.00 26.17 26.17 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 19.20 19.20 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 19.38 19.38 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 19.87 19.87 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 20.37 20.37 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 20.49 20.49 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 18.68 18.68 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 26.17 26.17 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.130785E+10 0.00 44.50 0.130785E+10 0.00 0.00 0.00 0.00 32750.66 17-JAN-13:30 32750.66 17-JAN-13:30 0.00 0.00 0.00
February 0.329405E+10 0.00 77.36 0.329405E+10 0.00 0.00 0.00 0.00 31501.36 27-FEB-14:40 31501.36 27-FEB-14:40 0.00 0.00 0.00
March 0.210367E+10 0.00 70.94 0.210367E+10 0.00 0.00 0.00 0.00 23357.70 28-MAR-10:00 23357.70 28-MAR-10:00 0.00 0.00 0.00
April 0.487220E+10 0.00 67.90 0.486711E+10 0.00 0.00 0.00 0.00 82353.27 30-APR-14:21 82353.27 30-APR-14:21 0.00 0.00 0.00
May 0.528758E+10 0.00 71.86 0.528758E+10 0.00 0.00 0.00 0.00 92092.14 22-MAY-15:00 92092.14 22-MAY-15:00 0.00 0.00 0.00
June 0.168488E+11 0.00 168.17 0.165882E+11 0.00 0.00 0.00 0.00 124353.15 25-JUN-17:41 106741.02 13-JUN-15:20 0.00 0.00 0.00
July 0.285907E+11 0.00 303.42 0.285318E+11 0.00 0.00 0.00 0.00 109790.69 21-JUL-15:10 109790.69 21-JUL-15:10 0.00 0.00 0.00
August 0.379601E+11 0.00 375.56 0.378197E+11 0.00 0.00 0.00 0.00 117458.75 14-AUG-15:10 117458.75 14-AUG-15:10 0.00 0.00 0.00
September 0.176311E+11 0.00 212.83 0.175489E+11 0.00 0.00 0.00 0.00 81527.24 13-SEP-14:20 81527.24 13-SEP-14:20 0.00 0.00 0.00
October 0.317749E+10 0.00 59.21 0.317749E+10 0.00 0.00 0.00 0.00 49499.89 06-OCT-10:00 49499.89 06-OCT-10:00 0.00 0.00 0.00
November 0.254749E+10 0.00 56.33 0.254749E+10 0.00 0.00 0.00 0.00 33154.49 03-NOV-14:30 33154.49 03-NOV-14:30 0.00 0.00 0.00
December 0.365459E+10 0.00 108.67 0.365459E+10 0.00 0.00 0.00 0.00 33659.73 18-DEC-14:10 33659.73 18-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.127276E+12 0.00 1616.76 0.126728E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.130785E+10 0.00 44.50 0.130785E+10 0.00 0.00 0.00 0.00 23357.70   23357.70   0.00 0.00 0.00
Maximum of Months 0.379601E+11 0.00 375.56 0.378197E+11 0.00 0.00 0.00 0.00 124353.15   117458.75   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.143477E+09 0.00 10.38 0.143477E+09 0.00 0.00 0.00 0.00 57893.56 20-JAN-12:00 57893.56 20-JAN-12:00 0.00 0.00 0.00
February 0.960991E+09 0.00 17.33 0.960991E+09 0.00 0.00 0.00 0.00 97341.37 09-FEB-15:20 97341.37 09-FEB-15:20 0.00 0.00 0.00
March 0.134972E+10 0.00 15.89 0.134972E+10 0.00 0.00 0.00 0.00 105077.83 30-MAR-14:05 105077.83 30-MAR-14:05 0.00 0.00 0.00
April 0.458518E+11 0.00 78.49 0.458363E+11 0.00 0.00 0.00 0.00 788459.24 30-APR-15:52 788459.24 30-APR-15:52 0.00 0.00 0.00
May 0.512857E+11 0.00 92.75 0.512857E+11 0.00 0.00 0.00 0.00 800885.20 22-MAY-15:00 800885.20 22-MAY-15:00 0.00 0.00 0.00
June 0.143263E+12 0.00 182.47 0.141361E+12 0.00 0.00 0.00 0.00 1027102.67 13-JUN-16:00 951285.34 13-JUN-15:30 0.00 0.00 0.00
July 0.223910E+12 0.00 295.89 0.223592E+12 0.00 0.00 0.00 0.00 975260.51 21-JUL-15:30 975260.51 21-JUL-15:30 0.00 0.00 0.00
August 0.281427E+12 0.00 374.19 0.280905E+12 0.00 0.00 0.00 0.00 936285.63 14-AUG-15:30 936285.63 14-AUG-15:30 0.00 0.00 0.00
September 0.157902E+12 0.00 230.22 0.156656E+12 0.00 0.00 0.00 0.00 774312.12 13-SEP-14:05 774312.12 13-SEP-14:05 0.00 0.00 0.00
October 0.352475E+11 0.00 54.99 0.352475E+11 0.00 0.00 0.00 0.00 508676.92 05-OCT-14:05 508676.92 05-OCT-14:05 0.00 0.00 0.00
November 0.100418E+09 0.00 9.18 0.100418E+09 0.00 0.00 0.00 0.00 33112.90 10-NOV-11:05 33112.90 10-NOV-11:05 0.00 0.00 0.00
December 26057.36 0.00 10.29 26057.36 0.00 0.00 0.00 0.00 1.83 26-DEC-06:01 1.83 26-DEC-06:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.941442E+12 0.00 1372.09 0.937439E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 26057.36 0.00 9.18 26057.36 0.00 0.00 0.00 0.00 1.83   1.83   0.00 0.00 0.00
Maximum of Months 0.281427E+12 0.00 374.19 0.280905E+12 0.00 0.00 0.00 0.00 1027102.67   975260.51   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00
April 0.335265E+10 0.00 52.12 0.335265E+10 0.00 0.00 0.00 0.00 92110.46 30-APR-16:11 92110.46 30-APR-16:11 0.00 0.00 0.00
May 0.448560E+10 0.00 64.61 0.448560E+10 0.00 0.00 0.00 0.00 88391.48 22-MAY-15:00 88391.48 22-MAY-15:00 0.00 0.00 0.00
June 0.144884E+11 0.00 157.10 0.142906E+11 0.00 0.00 0.00 0.00 121382.97 13-JUN-16:00 114955.06 13-JUN-15:30 0.00 0.00 0.00
July 0.229075E+11 0.00 279.84 0.228899E+11 0.00 0.00 0.00 0.00 114790.59 21-JUL-15:30 114790.59 21-JUL-15:30 0.00 0.00 0.00
August 0.269787E+11 0.00 362.14 0.269525E+11 0.00 0.00 0.00 0.00 108197.36 14-AUG-15:40 108197.36 14-AUG-15:40 0.00 0.00 0.00
September 0.138531E+11 0.00 201.97 0.137973E+11 0.00 0.00 0.00 0.00 78760.34 13-SEP-14:40 78760.34 13-SEP-14:40 0.00 0.00 0.00
October 0.533048E+09 0.00 22.37 0.533048E+09 0.00 0.00 0.00 0.00 19494.56 07-OCT-15:00 19494.56 07-OCT-15:00 0.00 0.00 0.00
November 3323788.29 0.00 0.67 3323788.29 0.00 0.00 0.00 0.00 2538.47 24-NOV-12:00 2538.47 24-NOV-12:00 0.00 0.00 0.00
December 4841.28 0.00 0.02 4841.28 0.00 0.00 0.00 0.00 80.69 26-DEC-05:24 80.69 26-DEC-05:24 0.00 0.00 0.00
                               
Annual Sum or Average 0.866022E+11 0.00 1140.83 0.863049E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.269787E+11 0.00 362.14 0.269525E+11 0.00 0.00 0.00 0.00 121382.97   114955.06   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 16401.68 0.00 0.33 16401.68 0.00 0.00 0.00 0.00 18.65 19-JAN-21:10 18.65 19-JAN-21:10 0.00 0.00 0.00
February 5125.69 0.00 0.17 5125.69 0.00 0.00 0.00 0.00 8.54 24-FEB-18:40 8.54 24-FEB-18:40 0.00 0.00 0.00
March 635186.87 0.00 0.20 296944.35 0.00 0.00 0.00 0.00 5162.93 18-MAR-05:02 2344.24 18-MAR-05:02 0.00 0.00 0.00
April 0.638597E+09 0.00 19.40 0.638597E+09 0.00 0.00 0.00 0.00 23728.67 28-APR-15:00 23728.67 28-APR-15:00 0.00 0.00 0.00
May 0.201997E+10 0.00 32.43 0.201997E+10 0.00 0.00 0.00 0.00 50582.08 22-MAY-15:00 50582.08 22-MAY-15:00 0.00 0.00 0.00
June 0.734464E+10 0.00 88.26 0.726994E+10 0.00 0.00 0.00 0.00 56623.09 27-JUN-05:03 53420.51 12-JUN-15:00 0.00 0.00 0.00
July 0.122366E+11 0.00 185.53 0.121040E+11 0.00 0.00 0.00 0.00 60217.83 10-JUL-10:00 60217.83 10-JUL-10:00 0.00 0.00 0.00
August 0.159113E+11 0.00 264.29 0.158372E+11 0.00 0.00 0.00 0.00 58355.48 14-AUG-16:00 58355.48 14-AUG-16:00 0.00 0.00 0.00
September 0.758485E+10 0.00 121.61 0.753744E+10 0.00 0.00 0.00 0.00 50916.76 16-SEP-05:02 44104.71 25-SEP-13:00 0.00 0.00 0.00
October 0.153262E+09 0.00 9.09 0.132455E+09 0.00 0.00 0.00 0.00 31879.04 20-OCT-05:02 13945.94 10-OCT-05:15 0.00 0.00 0.00
November 21014559.01 0.00 1.06 18824850.88 0.00 0.00 0.00 0.00 14077.80 15-NOV-05:13 14077.80 15-NOV-05:13 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.459109E+11 0.00 722.37 0.455587E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.159113E+11 0.00 264.29 0.158372E+11 0.00 0.00 0.00 0.00 60217.83   60217.83   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.367622E+10 0.300732E+10 717.08 0.367603E+10 189832.59 0.00 0.02 10-JAN-18:00 0.01 29-JAN-05:10 2918.87 10-JAN-18:00 2918.87 10-JAN-18:00 56.29 29-JAN-05:50 1495.31 10-JAN-18:00 0.00
February 0.606086E+10 0.341839E+10 661.67 0.594919E+10 0.111668E+09 0.00 0.03 20-FEB-16:00 0.01 07-FEB-14:15 5133.31 20-FEB-15:50 5133.31 20-FEB-15:50 94.71 06-FEB-19:10 2088.94 20-FEB-16:00 0.00
March 0.110060E+11 0.499577E+10 704.53 0.104866E+11 0.519427E+09 0.00 0.03 31-MAR-23:30 0.01 25-MAR-16:20 5615.81 31-MAR-23:10 5615.81 31-MAR-23:10 331.84 26-MAR-12:10 2398.66 31-MAR-23:30 0.00
April 0.611624E+11 0.180156E+11 718.11 0.574295E+11 0.373283E+10 0.00 0.95 30-APR-17:00 0.01 23-APR-14:00 327196.97 30-APR-17:52 327196.97 30-APR-17:52 120176.94 28-APR-08:00 96280.11 30-APR-17:00 0.00
May 0.224903E+10 0.273062E+10 564.04 0.222053E+10 28495513.08 0.00 0.16 22-MAY-15:00 0.01 25-MAY-06:15 52422.07 22-MAY-15:00 48436.16 22-MAY-15:00 3985.91 22-MAY-15:00 15183.75 22-MAY-15:00 0.00
June 0.219388E+11 0.820831E+10 301.07 0.185280E+11 0.341073E+10 0.00 0.60 13-JUN-17:00 0.01 03-JUN-05:03 220056.54 13-JUN-17:00 217227.99 13-JUN-17:00 93751.18 25-JUN-17:52 63069.05 13-JUN-17:00 0.00
July 0.123882E+12 0.339567E+11 470.19 0.981437E+11 0.257386E+11 0.00 0.86 21-JUL-17:00 0.01 02-JUL-16:17 310862.68 21-JUL-16:00 310862.68 21-JUL-16:00 66781.38 23-JUL-16:40 96587.04 22-JUL-18:00 0.00
August 0.399893E+12 0.968681E+11 712.69 0.289281E+12 0.110612E+12 0.00 1.00 14-AUG-16:00 0.01 28-AUG-03:25 385129.47 14-AUG-13:00 374911.37 14-AUG-16:00 167802.74 08-AUG-13:00 109036.89 14-AUG-17:10 0.00
September 0.117022E+10 0.266467E+10 348.50 0.110705E+10 63174809.20 0.00 0.09 27-SEP-16:00 0.01 17-SEP-13:23 27123.97 13-SEP-16:00 26145.18 27-SEP-16:00 4195.27 13-SEP-16:00 8291.60 27-SEP-16:00 0.00
October 0.312596E+10 0.293138E+10 533.88 0.301427E+10 0.111692E+09 0.00 0.05 07-OCT-15:00 0.01 29-OCT-09:55 13311.27 07-OCT-15:00 13311.27 07-OCT-15:00 152.80 31-OCT-24:00 4426.53 07-OCT-15:00 0.00
November 0.761263E+10 0.413121E+10 610.58 0.712606E+10 0.486570E+09 0.00 0.10 24-NOV-12:00 0.01 08-NOV-00:10 29520.16 24-NOV-12:00 23257.14 24-NOV-12:00 6263.01 24-NOV-12:00 7999.44 24-NOV-12:00 0.00
December 0.146531E+11 0.616733E+10 744.00 0.134757E+11 0.117738E+10 0.00 0.15 23-DEC-11:00 0.02 20-DEC-18:00 40953.19 23-DEC-11:00 40953.19 23-DEC-11:00 721.17 21-DEC-20:00 11968.55 23-DEC-11:00 0.00
                                       
Annual Sum or Average 0.656430E+12 0.187095E+12 7086.33 0.510437E+12 0.145993E+12 0.00                         0.00
Minimum of Months 0.117022E+10 0.266467E+10 301.07 0.110705E+10 189832.59 0.00 0.02   0.01   2918.87   2918.87   56.29   1495.31   0.00
Maximum of Months 0.399893E+12 0.968681E+11 744.00 0.289281E+12 0.110612E+12 0.00 1.00   0.02   385129.47   374911.37   167802.74   109036.89   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.413802E+10 0.937960E+09 744.00 0.413646E+10 1559736.07 0.00 0.28 16-JAN-16:25 0.11 10-JAN-08:00 2316.85 01-JAN-16:10 2311.13 01-JAN-16:05 51.90 18-JAN-16:20 492.91 16-JAN-16:25 0.00
February 0.865022E+10 0.183100E+10 672.00 0.864891E+10 1306697.34 0.00 0.55 19-FEB-16:53 0.37 17-FEB-07:30 4580.93 19-FEB-16:57 4580.93 19-FEB-16:57 56.91 07-FEB-16:00 965.11 19-FEB-16:53 0.00
March 0.149352E+11 0.301227E+10 744.00 0.149349E+11 332844.74 0.00 0.85 31-MAR-24:00 0.59 01-MAR-07:10 7558.32 31-MAR-24:00 7558.32 31-MAR-24:00 66.77 20-MAR-06:10 1488.29 31-MAR-24:00 0.00
April 0.198963E+11 0.387913E+10 720.00 0.198956E+11 632941.22 0.00 1.00 30-APR-17:01 0.31 30-APR-24:00 8894.53 30-APR-19:12 8894.53 30-APR-19:12 68.47 28-APR-11:00 2245.03 30-APR-18:10 0.00
May 0.528664E+10 0.115338E+10 744.00 0.526672E+10 19914925.54 0.00 0.45 31-MAY-24:00 0.17 05-MAY-06:05 3885.87 31-MAY-24:00 3885.87 31-MAY-24:00 137.42 23-MAY-16:00 785.34 31-MAY-24:00 0.00
June 0.104010E+11 0.213296E+10 720.00 0.103151E+11 85936471.27 0.00 0.63 30-JUN-24:00 0.41 01-JUN-06:30 5727.02 30-JUN-24:00 5727.02 30-JUN-24:00 225.28 26-JUN-17:50 1255.63 13-JUN-16:00 0.00
July 0.160308E+11 0.321333E+10 744.00 0.159128E+11 0.117936E+09 0.00 0.83 31-JUL-24:00 0.61 01-JUL-06:40 7789.70 31-JUL-24:00 7789.70 31-JUL-24:00 250.12 18-JUL-16:00 2022.31 22-JUL-18:40 0.00
August 0.210197E+11 0.416095E+10 744.00 0.208850E+11 0.134648E+09 0.00 0.96 14-AUG-18:00 0.30 31-AUG-24:00 8855.32 13-AUG-18:03 8826.53 13-AUG-18:03 267.99 08-AUG-13:40 2304.56 14-AUG-18:00 0.00
September 0.529844E+10 0.114443E+10 720.00 0.523414E+10 64303374.83 0.00 0.45 30-SEP-24:00 0.18 21-SEP-06:10 3784.54 30-SEP-24:00 3784.54 30-SEP-24:00 154.66 19-SEP-16:00 792.88 30-SEP-24:00 0.00
October 0.101291E+11 0.208727E+10 744.00 0.101025E+11 26604789.98 0.00 0.65 31-OCT-24:00 0.38 28-OCT-07:00 5627.62 31-OCT-24:00 5627.62 31-OCT-24:00 128.11 17-OCT-15:30 1129.33 31-OCT-24:00 0.00
November 0.144760E+11 0.288688E+10 720.00 0.144602E+11 15823408.31 0.00 0.71 19-NOV-15:55 0.59 25-NOV-07:40 6218.55 19-NOV-15:55 6218.55 19-NOV-15:55 142.75 08-NOV-15:10 1239.93 19-NOV-15:55 0.00
December 0.197722E+11 0.387321E+10 744.00 0.197720E+11 157909.02 0.00 0.91 31-DEC-15:15 0.78 21-DEC-07:10 7986.37 25-DEC-15:20 7986.37 25-DEC-15:20 40.88 20-DEC-17:05 1584.34 31-DEC-15:15 0.00
                                       
Annual Sum or Average 0.150034E+12 0.303128E+11 8760.00 0.149564E+12 0.469157E+09 0.00                         0.00
Minimum of Months 0.413802E+10 0.937960E+09 672.00 0.413646E+10 157909.02 0.00 0.28   0.11   2316.85   2311.13   40.88   492.91   0.00
Maximum of Months 0.210197E+11 0.416095E+10 744.00 0.208850E+11 0.134648E+09 0.00 1.00   0.78   8894.53   8894.53   267.99   2304.56   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.196547E+11 0.473523E+10 736.42 0.196398E+11 14980059.24 0.00 0.23 19-JAN-16:20 0.00 02-JAN-07:10 18216.13 19-JAN-16:20 18216.13 19-JAN-16:20 492.04 18-JAN-16:30 3950.03 19-JAN-16:20 0.00
February 0.663079E+11 0.143173E+11 672.00 0.662945E+11 13410814.45 0.00 0.49 19-FEB-17:05 0.26 13-FEB-07:10 38816.08 27-FEB-17:00 38816.08 27-FEB-17:00 557.04 07-FEB-16:00 8281.47 19-FEB-17:05 0.00
March 0.127229E+12 0.260089E+11 744.00 0.127225E+12 3341443.07 0.00 0.81 31-MAR-23:30 0.50 27-MAR-06:10 68270.64 31-MAR-23:30 68270.64 31-MAR-23:30 556.58 20-MAR-06:10 13561.62 31-MAR-23:30 0.00
April 0.183191E+12 0.359291E+11 720.00 0.183184E+12 6560757.49 0.00 1.00 30-APR-17:31 0.27 30-APR-24:00 84084.70 30-APR-18:10 84084.70 30-APR-18:10 669.17 28-APR-11:00 21565.26 30-APR-18:10 0.00
May 0.439110E+11 0.969085E+10 744.00 0.437149E+11 0.196095E+09 0.00 0.43 31-MAY-23:40 0.11 05-MAY-06:05 35696.32 31-MAY-23:40 35696.32 31-MAY-23:40 1362.13 23-MAY-16:00 7244.84 31-MAY-23:40 0.00
June 0.949536E+11 0.195744E+11 720.00 0.941020E+11 0.851601E+09 0.00 0.61 30-JUN-23:40 0.37 08-JUN-06:05 52497.37 30-JUN-23:40 52497.37 30-JUN-23:40 2223.60 26-JUN-17:50 11986.28 13-JUN-17:00 0.00
July 0.148993E+12 0.299959E+11 744.00 0.147827E+12 0.116632E+10 0.00 0.82 31-JUL-23:50 0.57 01-JUL-06:40 73268.86 31-JUL-23:50 73268.86 31-JUL-23:50 2469.61 18-JUL-16:00 19264.54 22-JUL-18:40 0.00
August 0.197234E+12 0.391865E+11 744.00 0.195900E+12 0.133398E+10 0.00 0.95 14-AUG-18:00 0.24 31-AUG-24:00 82675.85 13-AUG-18:03 82399.66 13-AUG-18:03 2657.34 08-AUG-13:40 22002.83 14-AUG-18:00 0.00
September 0.446166E+11 0.974287E+10 720.00 0.439896E+11 0.626984E+09 0.00 0.43 30-SEP-23:30 0.13 07-SEP-06:05 33873.91 30-SEP-23:30 33873.91 30-SEP-23:30 1538.53 19-SEP-16:00 7146.40 30-SEP-23:30 0.00
October 0.840157E+11 0.175465E+11 744.00 0.837526E+11 0.263129E+09 0.00 0.59 31-OCT-23:50 0.30 30-OCT-07:00 48754.99 31-OCT-23:50 48754.99 31-OCT-23:50 1269.20 17-OCT-15:30 9905.58 31-OCT-23:50 0.00
November 0.119552E+12 0.242385E+11 720.00 0.119394E+12 0.157880E+09 0.00 0.65 03-NOV-16:00 0.47 27-NOV-07:10 54927.36 10-NOV-16:10 54739.66 10-NOV-16:00 1421.90 08-NOV-15:10 10863.89 03-NOV-16:00 0.00
December 0.162111E+12 0.324142E+11 744.00 0.162109E+12 1836880.77 0.00 0.80 29-DEC-15:50 0.64 26-DEC-07:10 69021.05 21-DEC-15:20 69021.05 21-DEC-15:20 408.06 20-DEC-17:05 13449.15 29-DEC-15:50 0.00
                                       
Annual Sum or Average 0.129177E+13 0.263380E+12 8752.42 0.128713E+13 0.463612E+10 0.00                         0.00
Minimum of Months 0.196547E+11 0.473523E+10 672.00 0.196398E+11 1836880.77 0.00 0.23   0.00   18216.13   18216.13   408.06   3950.03   0.00
Maximum of Months 0.197234E+12 0.391865E+11 744.00 0.195900E+12 0.133398E+10 0.00 1.00   0.64   84084.70   84084.70   2657.34   22002.83   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.477263E+09 0.124632E+09 341.93 0.476376E+09 886897.39 0.00 0.22 19-JAN-16:30 0.00 01-JAN-00:05 1688.90 19-JAN-16:30 1688.90 19-JAN-16:30 43.37 18-JAN-16:40 368.78 19-JAN-16:30 0.00
February 0.481490E+10 0.106532E+10 672.00 0.481365E+10 1248853.62 0.00 0.45 17-FEB-17:00 0.10 20-FEB-08:20 3639.62 24-FEB-17:00 3639.62 24-FEB-17:00 52.49 08-FEB-16:40 762.57 17-FEB-17:00 0.00
March 0.110225E+11 0.228870E+10 744.00 0.110222E+11 318731.35 0.00 0.75 31-MAR-23:20 0.38 06-MAR-05:13 6342.98 31-MAR-23:20 6342.98 31-MAR-23:20 43.90 20-MAR-06:10 1274.16 31-MAR-23:20 0.00
April 0.175122E+11 0.346077E+10 720.00 0.175116E+11 645239.06 0.00 1.00 30-APR-17:21 0.26 30-APR-23:55 8532.17 30-APR-18:10 8532.17 30-APR-18:10 66.90 28-APR-11:00 2186.47 30-APR-18:10 0.00
May 0.367762E+10 0.822725E+09 743.61 0.365815E+10 19474079.95 0.00 0.41 31-MAY-23:20 0.00 05-MAY-02:45 3422.70 31-MAY-23:20 3422.70 31-MAY-23:20 137.36 23-MAY-16:00 698.29 31-MAY-23:20 0.00
June 0.916481E+10 0.189864E+10 720.00 0.907979E+10 85020441.57 0.00 0.58 30-JUN-23:20 0.30 08-JUN-06:05 5031.50 30-JUN-23:20 5031.50 30-JUN-23:20 223.30 26-JUN-17:50 1225.29 13-JUN-17:00 0.00
July 0.146222E+11 0.295683E+10 744.00 0.145057E+11 0.116538E+09 0.00 0.82 22-JUL-18:50 0.52 01-JUL-06:30 7172.77 31-JUL-23:20 7172.77 31-JUL-23:20 247.30 18-JUL-16:00 1978.76 22-JUL-18:40 0.00
August 0.194310E+11 0.387789E+10 744.00 0.192978E+11 0.133162E+09 0.00 0.95 14-AUG-18:00 0.21 31-AUG-24:00 8388.59 13-AUG-18:03 8362.80 13-AUG-17:55 265.57 08-AUG-13:40 2222.90 14-AUG-18:00 0.00
September 0.380586E+10 0.842621E+09 719.92 0.374408E+10 61775485.77 0.00 0.36 30-SEP-23:10 0.00 17-SEP-04:35 2857.27 30-SEP-23:10 2857.27 30-SEP-23:10 154.57 19-SEP-16:00 623.92 13-SEP-17:00 0.00
October 0.682829E+10 0.145141E+10 744.00 0.680279E+10 25501047.57 0.00 0.52 31-OCT-23:20 0.18 23-OCT-06:10 4280.90 31-OCT-23:20 4280.90 31-OCT-23:20 126.76 17-OCT-15:40 883.04 31-OCT-23:20 0.00
November 0.100724E+11 0.207849E+10 720.00 0.100569E+11 15480248.09 0.00 0.62 03-NOV-16:00 0.32 27-NOV-05:21 5407.37 10-NOV-16:10 5387.55 10-NOV-16:00 141.24 08-NOV-15:10 1062.95 03-NOV-16:00 0.00
December 0.142328E+11 0.289267E+10 744.00 0.142327E+11 168305.97 0.00 0.76 29-DEC-15:50 0.48 26-DEC-05:22 6634.29 21-DEC-15:20 6634.29 21-DEC-15:20 39.75 20-DEC-17:05 1287.24 29-DEC-15:50 0.00
                                       
Annual Sum or Average 0.115662E+12 0.237607E+11 8357.46 0.115202E+12 0.460219E+09 0.00                         0.00
Minimum of Months 0.477263E+09 0.124632E+09 341.93 0.476376E+09 168305.97 0.00 0.22   0.00   1688.90   1688.90   39.75   368.78   0.00
Maximum of Months 0.194310E+11 0.387789E+10 744.00 0.192978E+11 0.133162E+09 0.00 1.00   0.52   8532.17   8532.17   265.57   2222.90   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.31 0.00 91.31 2.84 628.82 0.00 0.00 0.00
February 142.59 0.00 142.59 11.10 588.58 0.00 0.00 0.00
March 197.32 0.00 197.32 48.93 493.69 0.00 0.00 0.00
April 321.26 1.44 319.82 188.73 388.05 0.00 0.00 0.00
May 401.66 19.38 382.28 246.59 300.29 0.00 0.00 0.00
June 444.01 27.84 416.17 361.21 235.53 0.00 0.00 0.00
July 421.17 24.01 397.15 363.77 218.98 0.00 0.00 0.00
August 331.06 5.19 325.87 277.99 247.35 0.00 0.00 0.00
September 251.98 0.06 251.93 179.34 327.53 0.00 0.00 0.00
October 161.47 0.00 161.47 54.45 456.50 0.00 0.00 0.00
November 97.02 0.00 97.02 4.80 574.01 0.00 0.00 0.00
December 66.07 0.00 66.07 0.00 694.29 0.00 0.00 0.00
                 
Annual Sum or Average 244.36 6.54 237.83 145.66 428.69 0.00 0.00 0.00
Minimum of Months 66.07 0.00 66.07 0.00 218.98 0.00 0.00 0.00
Maximum of Months 444.01 27.84 416.17 363.77 694.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.31 0.00 91.31 2.84 628.82 0.00 0.00 0.00
February 142.59 0.00 142.59 11.10 588.58 0.00 0.00 0.00
March 197.32 0.00 197.32 48.93 493.69 0.00 0.00 0.00
April 321.26 1.44 319.82 188.73 388.05 0.00 0.00 0.00
May 401.66 19.38 382.28 246.59 300.29 0.00 0.00 0.00
June 444.01 27.84 416.17 361.21 235.53 0.00 0.00 0.00
July 421.17 24.01 397.15 363.77 218.98 0.00 0.00 0.00
August 331.06 5.19 325.87 277.99 247.35 0.00 0.00 0.00
September 251.98 0.06 251.93 179.34 327.53 0.00 0.00 0.00
October 161.47 0.00 161.47 54.45 456.50 0.00 0.00 0.00
November 97.02 0.00 97.02 4.80 574.01 0.00 0.00 0.00
December 66.07 0.00 66.07 0.00 694.29 0.00 0.00 0.00
                 
Annual Sum or Average 244.36 6.54 237.82 145.66 428.69 0.00 0.00 0.00
Minimum of Months 66.07 0.00 66.07 0.00 218.98 0.00 0.00 0.00
Maximum of Months 444.01 27.84 416.17 363.77 694.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.31 0.00 91.31 2.84 628.82 0.00 0.00 0.00
February 142.59 0.00 142.59 11.10 588.58 0.00 0.00 0.00
March 197.32 0.00 197.32 48.93 493.69 0.00 0.00 0.00
April 321.26 1.44 319.82 188.73 388.05 0.00 0.00 0.00
May 401.66 19.38 382.28 246.59 300.29 0.00 0.00 0.00
June 444.01 27.84 416.17 361.21 235.53 0.00 0.00 0.00
July 421.17 24.01 397.15 363.77 218.98 0.00 0.00 0.00
August 331.06 5.19 325.87 277.99 247.35 0.00 0.00 0.00
September 251.98 0.06 251.93 179.34 327.53 0.00 0.00 0.00
October 161.47 0.00 161.47 54.45 456.50 0.00 0.00 0.00
November 97.02 0.00 97.02 4.80 574.01 0.00 0.00 0.00
December 66.07 0.00 66.07 0.00 694.29 0.00 0.00 0.00
                 
Annual Sum or Average 244.36 6.54 237.83 145.66 428.69 0.00 0.00 0.00
Minimum of Months 66.07 0.00 66.07 0.00 218.98 0.00 0.00 0.00
Maximum of Months 444.01 27.84 416.17 363.77 694.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.31 0.00 91.31 2.84 628.82 0.00 0.00 0.00
February 142.59 0.00 142.59 11.10 588.58 0.00 0.00 0.00
March 197.32 0.00 197.32 48.93 493.69 0.00 0.00 0.00
April 321.26 1.44 319.82 188.73 388.05 0.00 0.00 0.00
May 401.66 19.38 382.28 246.59 300.29 0.00 0.00 0.00
June 444.01 27.84 416.17 361.21 235.53 0.00 0.00 0.00
July 421.17 24.01 397.15 363.77 218.98 0.00 0.00 0.00
August 331.06 5.19 325.87 277.99 247.35 0.00 0.00 0.00
September 251.98 0.06 251.93 179.34 327.53 0.00 0.00 0.00
October 161.47 0.00 161.47 54.45 456.50 0.00 0.00 0.00
November 97.02 0.00 97.02 4.80 574.01 0.00 0.00 0.00
December 66.07 0.00 66.07 0.00 694.29 0.00 0.00 0.00
                 
Annual Sum or Average 244.36 6.54 237.82 145.66 428.69 0.00 0.00 0.00
Minimum of Months 66.07 0.00 66.07 0.00 218.98 0.00 0.00 0.00
Maximum of Months 444.01 27.84 416.17 363.77 694.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.31 0.00 91.31 2.84 628.79 0.00 0.00 0.00
February 142.58 0.00 142.58 11.10 588.56 0.00 0.00 0.00
March 197.31 0.00 197.31 48.93 493.67 0.00 0.00 0.00
April 321.25 1.44 319.81 188.72 388.03 0.00 0.00 0.00
May 401.64 19.38 382.27 246.58 300.28 0.00 0.00 0.00
June 443.99 27.84 416.15 361.20 235.52 0.00 0.00 0.00
July 421.15 24.01 397.14 363.76 218.97 0.00 0.00 0.00
August 331.05 5.19 325.86 277.97 247.34 0.00 0.00 0.00
September 251.97 0.06 251.92 179.33 327.52 0.00 0.00 0.00
October 161.46 0.00 161.46 54.44 456.48 0.00 0.00 0.00
November 97.01 0.00 97.01 4.80 573.98 0.00 0.00 0.00
December 66.07 0.00 66.07 0.00 694.26 0.00 0.00 0.00
                 
Annual Sum or Average 244.35 6.54 237.82 145.65 428.67 0.00 0.00 0.00
Minimum of Months 66.07 0.00 66.07 0.00 218.97 0.00 0.00 0.00
Maximum of Months 443.99 27.84 416.15 363.76 694.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 207.38 83.30 124.07 109.79 649.63 0.00 0.00 0.00
February 309.23 114.23 195.00 185.42 609.51 0.00 0.00 0.00
March 323.15 63.68 259.47 175.78 507.88 0.00 0.00 0.00
April 867.70 407.74 459.96 891.42 400.04 0.00 0.00 0.00
May 912.36 397.86 514.49 914.98 340.68 0.00 0.00 0.00
June 903.07 360.68 542.39 969.40 264.74 0.00 0.00 0.00
July 921.85 391.79 530.06 1032.88 245.20 0.00 0.00 0.00
August 873.25 417.23 456.02 1008.04 266.32 0.00 0.00 0.00
September 786.39 418.17 368.23 874.56 343.74 0.00 0.00 0.00
October 379.60 157.32 222.29 321.15 479.68 0.00 0.00 0.00
November 197.90 67.45 130.45 103.38 591.47 0.00 0.00 0.00
December 146.67 54.53 92.14 66.23 708.92 0.00 0.00 0.00
                 
Annual Sum or Average 569.87 244.81 325.06 555.75 449.90 0.00 0.00 0.00
Minimum of Months 146.67 54.53 92.14 66.23 245.20 0.00 0.00 0.00
Maximum of Months 921.85 418.17 542.39 1032.88 708.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 207.38 83.30 124.07 109.79 649.63 0.00 0.00 0.00
February 309.23 114.23 195.00 185.42 609.51 0.00 0.00 0.00
March 323.15 63.68 259.47 175.78 507.88 0.00 0.00 0.00
April 867.70 407.74 459.96 891.42 400.04 0.00 0.00 0.00
May 912.36 397.86 514.49 914.98 340.68 0.00 0.00 0.00
June 903.07 360.68 542.39 969.40 264.74 0.00 0.00 0.00
July 921.85 391.79 530.06 1032.88 245.20 0.00 0.00 0.00
August 873.25 417.23 456.02 1008.04 266.32 0.00 0.00 0.00
September 786.39 418.17 368.23 874.56 343.74 0.00 0.00 0.00
October 379.60 157.32 222.29 321.15 479.68 0.00 0.00 0.00
November 197.90 67.45 130.45 103.38 591.47 0.00 0.00 0.00
December 146.67 54.53 92.14 66.23 708.92 0.00 0.00 0.00
                 
Annual Sum or Average 569.87 244.81 325.06 555.75 449.90 0.00 0.00 0.00
Minimum of Months 146.67 54.53 92.14 66.23 245.20 0.00 0.00 0.00
Maximum of Months 921.85 418.17 542.39 1032.88 708.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 207.37 83.30 124.07 109.79 649.62 0.00 0.00 0.00
February 309.23 114.23 195.00 185.42 609.50 0.00 0.00 0.00
March 323.15 63.68 259.47 175.78 507.87 0.00 0.00 0.00
April 867.68 407.73 459.95 891.41 400.03 0.00 0.00 0.00
May 912.34 397.86 514.48 914.96 340.67 0.00 0.00 0.00
June 903.05 360.67 542.38 969.38 264.73 0.00 0.00 0.00
July 921.83 391.78 530.05 1032.86 245.19 0.00 0.00 0.00
August 873.24 417.22 456.01 1008.02 266.31 0.00 0.00 0.00
September 786.38 418.16 368.22 874.55 343.74 0.00 0.00 0.00
October 379.60 157.31 222.28 321.14 479.67 0.00 0.00 0.00
November 197.89 67.45 130.45 103.38 591.46 0.00 0.00 0.00
December 146.66 54.53 92.14 66.22 708.91 0.00 0.00 0.00
                 
Annual Sum or Average 569.86 244.81 325.05 555.74 449.89 0.00 0.00 0.00
Minimum of Months 146.66 54.53 92.14 66.22 245.19 0.00 0.00 0.00
Maximum of Months 921.83 418.16 542.38 1032.86 708.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 518.41 335.59 182.82 501.32 539.47 0.00 0.00 0.00
February 633.14 386.35 246.79 630.52 529.52 0.00 0.00 0.00
March 391.45 113.97 277.48 302.20 454.61 0.00 0.00 0.00
April 812.88 367.41 445.47 912.95 392.27 0.00 0.00 0.00
May 672.33 218.89 453.44 698.46 332.32 0.00 0.00 0.00
June 619.36 149.92 469.44 670.18 257.89 0.00 0.00 0.00
July 671.06 210.15 460.91 781.86 241.41 0.00 0.00 0.00
August 786.33 353.72 432.61 972.74 264.08 0.00 0.00 0.00
September 929.24 544.37 384.88 1140.89 329.79 0.00 0.00 0.00
October 638.43 373.13 265.30 694.08 429.89 0.00 0.00 0.00
November 452.65 275.36 177.29 439.85 513.16 0.00 0.00 0.00
December 358.76 229.86 128.90 334.46 613.71 0.00 0.00 0.00
                 
Annual Sum or Average 622.72 295.41 327.31 672.35 407.56 0.00 0.00 0.00
Minimum of Months 358.76 113.97 128.90 302.20 241.41 0.00 0.00 0.00
Maximum of Months 929.24 544.37 469.44 1140.89 613.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 518.41 335.59 182.82 501.32 539.47 0.00 0.00 0.00
February 633.14 386.35 246.79 630.51 529.52 0.00 0.00 0.00
March 391.45 113.97 277.48 302.20 454.61 0.00 0.00 0.00
April 812.88 367.41 445.47 912.95 392.27 0.00 0.00 0.00
May 672.32 218.89 453.44 698.46 332.32 0.00 0.00 0.00
June 619.35 149.92 469.43 670.18 257.89 0.00 0.00 0.00
July 671.06 210.15 460.91 781.86 241.41 0.00 0.00 0.00
August 786.33 353.72 432.61 972.74 264.08 0.00 0.00 0.00
September 929.24 544.37 384.88 1140.89 329.79 0.00 0.00 0.00
October 638.43 373.13 265.30 694.08 429.89 0.00 0.00 0.00
November 452.64 275.36 177.29 439.85 513.16 0.00 0.00 0.00
December 358.76 229.86 128.90 334.46 613.71 0.00 0.00 0.00
                 
Annual Sum or Average 622.72 295.41 327.31 672.35 407.56 0.00 0.00 0.00
Minimum of Months 358.76 113.97 128.90 302.20 241.41 0.00 0.00 0.00
Maximum of Months 929.24 544.37 469.43 1140.89 613.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 518.41 335.59 182.82 501.32 539.47 0.00 0.00 0.00
February 633.14 386.35 246.79 630.52 529.52 0.00 0.00 0.00
March 391.45 113.97 277.48 302.20 454.61 0.00 0.00 0.00
April 812.88 367.41 445.47 912.95 392.27 0.00 0.00 0.00
May 672.33 218.89 453.44 698.46 332.32 0.00 0.00 0.00
June 619.36 149.92 469.44 670.18 257.89 0.00 0.00 0.00
July 671.06 210.15 460.91 781.86 241.41 0.00 0.00 0.00
August 786.33 353.72 432.61 972.74 264.08 0.00 0.00 0.00
September 929.24 544.37 384.88 1140.89 329.79 0.00 0.00 0.00
October 638.43 373.13 265.30 694.08 429.89 0.00 0.00 0.00
November 452.65 275.36 177.29 439.85 513.16 0.00 0.00 0.00
December 358.76 229.86 128.90 334.46 613.71 0.00 0.00 0.00
                 
Annual Sum or Average 622.72 295.41 327.31 672.35 407.56 0.00 0.00 0.00
Minimum of Months 358.76 113.97 128.90 302.20 241.41 0.00 0.00 0.00
Maximum of Months 929.24 544.37 469.44 1140.89 613.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 518.41 335.59 182.82 501.32 539.47 0.00 0.00 0.00
February 633.14 386.35 246.79 630.51 529.52 0.00 0.00 0.00
March 391.45 113.97 277.48 302.20 454.61 0.00 0.00 0.00
April 812.88 367.41 445.47 912.95 392.27 0.00 0.00 0.00
May 672.32 218.89 453.44 698.46 332.32 0.00 0.00 0.00
June 619.35 149.92 469.43 670.18 257.89 0.00 0.00 0.00
July 671.06 210.15 460.91 781.86 241.41 0.00 0.00 0.00
August 786.33 353.72 432.61 972.74 264.08 0.00 0.00 0.00
September 929.24 544.37 384.88 1140.89 329.79 0.00 0.00 0.00
October 638.43 373.13 265.30 694.08 429.89 0.00 0.00 0.00
November 452.64 275.36 177.29 439.85 513.16 0.00 0.00 0.00
December 358.76 229.86 128.90 334.46 613.71 0.00 0.00 0.00
                 
Annual Sum or Average 622.72 295.41 327.31 672.35 407.56 0.00 0.00 0.00
Minimum of Months 358.76 113.97 128.90 302.20 241.41 0.00 0.00 0.00
Maximum of Months 929.24 544.37 469.43 1140.89 613.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 518.39 335.57 182.81 501.30 539.45 0.00 0.00 0.00
February 633.12 386.34 246.78 630.49 529.50 0.00 0.00 0.00
March 391.43 113.97 277.47 302.19 454.59 0.00 0.00 0.00
April 812.85 367.40 445.45 912.91 392.25 0.00 0.00 0.00
May 672.30 218.88 453.42 698.43 332.31 0.00 0.00 0.00
June 619.33 149.91 469.42 670.15 257.88 0.00 0.00 0.00
July 671.03 210.14 460.89 781.83 241.40 0.00 0.00 0.00
August 786.30 353.71 432.59 972.70 264.07 0.00 0.00 0.00
September 929.21 544.34 384.86 1140.84 329.78 0.00 0.00 0.00
October 638.40 373.12 265.28 694.05 429.87 0.00 0.00 0.00
November 452.63 275.34 177.28 439.83 513.14 0.00 0.00 0.00
December 358.75 229.85 128.90 334.44 613.68 0.00 0.00 0.00
                 
Annual Sum or Average 622.69 295.40 327.29 672.33 407.55 0.00 0.00 0.00
Minimum of Months 358.75 113.97 128.90 302.19 241.40 0.00 0.00 0.00
Maximum of Months 929.21 544.34 469.42 1140.84 613.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 201.66 66.63 135.03 106.20 704.27 0.00 0.00 0.00
February 357.05 150.76 206.29 258.48 687.75 0.00 0.00 0.00
March 322.85 61.76 261.09 163.42 583.78 0.00 0.00 0.00
April 761.78 302.59 459.20 742.95 479.98 0.00 0.00 0.00
May 893.75 363.43 530.32 886.39 382.90 0.00 0.00 0.00
June 965.15 397.32 567.83 1038.53 309.61 0.00 0.00 0.00
July 982.96 433.39 549.57 1099.62 297.22 0.00 0.00 0.00
August 825.62 357.47 468.15 929.11 330.63 0.00 0.00 0.00
September 662.37 297.02 365.35 718.49 392.02 0.00 0.00 0.00
October 353.35 127.06 226.29 285.16 545.89 0.00 0.00 0.00
November 191.22 55.82 135.40 99.52 688.27 0.00 0.00 0.00
December 108.24 22.84 85.40 30.36 848.41 0.00 0.00 0.00
                 
Annual Sum or Average 552.75 219.76 332.99 530.77 520.11 0.00 0.00 0.00
Minimum of Months 108.24 22.84 85.40 30.36 297.22 0.00 0.00 0.00
Maximum of Months 982.96 433.39 567.83 1099.62 848.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 201.66 66.63 135.03 106.20 704.27 0.00 0.00 0.00
February 357.05 150.76 206.29 258.48 687.75 0.00 0.00 0.00
March 322.85 61.76 261.09 163.42 583.78 0.00 0.00 0.00
April 761.78 302.59 459.20 742.95 479.98 0.00 0.00 0.00
May 893.75 363.43 530.32 886.39 382.90 0.00 0.00 0.00
June 965.15 397.32 567.83 1038.53 309.61 0.00 0.00 0.00
July 982.96 433.39 549.57 1099.62 297.22 0.00 0.00 0.00
August 825.62 357.47 468.15 929.11 330.63 0.00 0.00 0.00
September 662.37 297.02 365.35 718.49 392.02 0.00 0.00 0.00
October 353.35 127.06 226.29 285.16 545.89 0.00 0.00 0.00
November 191.22 55.82 135.40 99.52 688.27 0.00 0.00 0.00
December 108.24 22.84 85.40 30.36 848.41 0.00 0.00 0.00
                 
Annual Sum or Average 552.75 219.76 332.99 530.77 520.11 0.00 0.00 0.00
Minimum of Months 108.24 22.84 85.40 30.36 297.22 0.00 0.00 0.00
Maximum of Months 982.96 433.39 567.83 1099.62 848.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 201.66 66.63 135.03 106.20 704.26 0.00 0.00 0.00
February 357.05 150.76 206.29 258.47 687.74 0.00 0.00 0.00
March 322.85 61.76 261.09 163.41 583.77 0.00 0.00 0.00
April 761.77 302.58 459.19 742.93 479.97 0.00 0.00 0.00
May 893.73 363.42 530.31 886.38 382.89 0.00 0.00 0.00
June 965.13 397.31 567.82 1038.51 309.60 0.00 0.00 0.00
July 982.94 433.38 549.56 1099.60 297.21 0.00 0.00 0.00
August 825.61 357.47 468.14 929.09 330.63 0.00 0.00 0.00
September 662.36 297.02 365.34 718.47 392.01 0.00 0.00 0.00
October 353.34 127.06 226.28 285.15 545.88 0.00 0.00 0.00
November 191.22 55.82 135.40 99.51 688.26 0.00 0.00 0.00
December 108.23 22.84 85.39 30.36 848.39 0.00 0.00 0.00
                 
Annual Sum or Average 552.74 219.76 332.98 530.76 520.10 0.00 0.00 0.00
Minimum of Months 108.23 22.84 85.39 30.36 297.21 0.00 0.00 0.00
Maximum of Months 982.94 433.38 567.82 1099.60 848.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 456.56 0.00 456.56 30.28 2770.27 0.00 0.00 0.00
February 712.93 0.00 712.93 101.01 2591.35 0.00 0.00 0.00
March 986.57 0.00 986.57 312.59 2177.34 0.00 0.00 0.00
April 1606.29 7.19 1599.10 998.94 1775.56 0.00 0.00 0.00
May 2008.27 96.89 1911.38 1277.90 1412.00 0.00 0.00 0.00
June 2220.02 139.21 2080.81 1828.84 1116.55 0.00 0.00 0.00
July 2105.81 120.06 1985.74 1859.74 1027.34 0.00 0.00 0.00
August 1655.27 25.93 1629.34 1430.27 1148.82 0.00 0.00 0.00
September 1259.89 0.28 1259.61 935.09 1530.35 0.00 0.00 0.00
October 807.33 0.00 807.33 327.55 2024.24 0.00 0.00 0.00
November 485.08 0.00 485.08 50.42 2445.11 0.00 0.00 0.00
December 330.34 0.00 330.34 2.28 2928.64 0.00 0.00 0.00
                 
Annual Sum or Average 1221.80 32.68 1189.11 766.26 1908.86 0.00 0.00 0.00
Minimum of Months 330.34 0.00 330.34 2.28 1027.34 0.00 0.00 0.00
Maximum of Months 2220.02 139.21 2080.81 1859.74 2928.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 622.12 249.91 372.21 352.58 1756.79 0.00 0.00 0.00
February 927.69 342.69 584.99 583.68 1668.04 0.00 0.00 0.00
March 969.45 191.04 778.41 558.00 1398.81 0.00 0.00 0.00
April 2603.06 1223.20 1379.87 2665.97 1155.22 0.00 0.00 0.00
May 2737.04 1193.58 1543.46 2728.77 985.85 0.00 0.00 0.00
June 2709.17 1082.02 1627.15 2887.29 772.61 0.00 0.00 0.00
July 2765.53 1175.35 1590.18 3078.00 716.00 0.00 0.00 0.00
August 2619.73 1251.68 1368.05 3005.02 780.63 0.00 0.00 0.00
September 2359.16 1254.49 1104.67 2609.32 998.24 0.00 0.00 0.00
October 1138.80 471.95 666.85 978.20 1327.38 0.00 0.00 0.00
November 593.69 202.34 391.35 331.62 1576.17 0.00 0.00 0.00
December 440.00 163.58 276.41 221.35 1870.49 0.00 0.00 0.00
                 
Annual Sum or Average 1709.59 734.43 975.16 1670.54 1248.46 0.00 0.00 0.00
Minimum of Months 440.00 163.58 276.41 221.35 716.00 0.00 0.00 0.00
Maximum of Months 2765.53 1254.49 1627.15 3078.00 1870.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2592.02 1677.92 914.10 2517.74 2588.23 0.00 0.00 0.00
February 3165.67 1931.74 1233.94 3158.31 2551.11 0.00 0.00 0.00
March 1957.23 569.86 1387.37 1533.65 2153.03 0.00 0.00 0.00
April 4064.34 1837.03 2227.31 4555.38 1895.37 0.00 0.00 0.00
May 3361.59 1094.42 2267.16 3477.70 1621.07 0.00 0.00 0.00
June 3096.74 749.59 2347.15 3343.08 1249.65 0.00 0.00 0.00
July 3355.26 1050.74 2304.52 3905.81 1163.29 0.00 0.00 0.00
August 3931.63 1768.59 2163.04 4852.67 1276.30 0.00 0.00 0.00
September 4646.16 2721.80 1924.36 5674.63 1625.43 0.00 0.00 0.00
October 3192.10 1865.64 1326.46 3466.92 2066.23 0.00 0.00 0.00
November 2263.20 1376.76 886.44 2212.71 2405.66 0.00 0.00 0.00
December 1793.79 1149.29 644.50 1701.31 2829.54 0.00 0.00 0.00
                 
Annual Sum or Average 3113.54 1477.03 1636.52 3362.02 1948.88 0.00 0.00 0.00
Minimum of Months 1793.79 569.86 644.50 1533.65 1163.29 0.00 0.00 0.00
Maximum of Months 4646.16 2721.80 2347.15 5674.63 2829.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 604.98 199.89 405.09 349.10 1828.75 0.00 0.00 0.00
February 1071.15 452.27 618.87 822.94 1763.06 0.00 0.00 0.00
March 968.55 185.28 783.26 552.51 1459.79 0.00 0.00 0.00
April 2285.32 907.75 1377.57 2288.96 1259.61 0.00 0.00 0.00
May 2681.21 1090.27 1590.94 2677.83 1071.72 0.00 0.00 0.00
June 2895.42 1191.93 1703.48 3135.38 849.86 0.00 0.00 0.00
July 2948.86 1300.16 1648.70 3337.96 794.83 0.00 0.00 0.00
August 2476.84 1072.40 1404.44 2831.51 869.02 0.00 0.00 0.00
September 1987.09 891.05 1096.03 2177.92 1090.21 0.00 0.00 0.00
October 1060.03 381.18 678.85 901.14 1404.10 0.00 0.00 0.00
November 573.65 167.46 406.20 335.36 1668.58 0.00 0.00 0.00
December 324.70 68.52 256.19 113.75 1995.02 0.00 0.00 0.00
                 
Annual Sum or Average 1658.24 659.28 998.95 1629.72 1335.71 0.00 0.00 0.00
Minimum of Months 324.70 68.52 256.19 113.75 794.83 0.00 0.00 0.00
Maximum of Months 2948.86 1300.16 1703.48 3337.96 1995.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 456.56 0.00 456.56 48.39 2519.80 0.00 0.00 0.00
February 712.93 0.00 712.93 142.55 2353.66 0.00 0.00 0.00
March 986.57 0.00 986.57 369.25 1979.70 0.00 0.00 0.00
April 1606.29 7.19 1599.10 1041.30 1664.94 0.00 0.00 0.00
May 2008.27 96.89 1911.38 1329.51 1330.53 0.00 0.00 0.00
June 2220.02 139.21 2080.81 1844.50 1076.30 0.00 0.00 0.00
July 2105.81 120.06 1985.74 1871.21 993.91 0.00 0.00 0.00
August 1655.27 25.93 1629.34 1441.78 1107.63 0.00 0.00 0.00
September 1259.89 0.28 1259.61 969.85 1438.33 0.00 0.00 0.00
October 807.33 0.00 807.33 382.31 1813.34 0.00 0.00 0.00
November 485.08 0.00 485.08 75.15 2191.00 0.00 0.00 0.00
December 330.34 0.00 330.34 9.95 2689.86 0.00 0.00 0.00
                 
Annual Sum or Average 1221.80 32.68 1189.11 797.10 1760.27 0.00 0.00 0.00
Minimum of Months 330.34 0.00 330.34 9.95 993.91 0.00 0.00 0.00
Maximum of Months 2220.02 139.21 2080.81 1871.21 2689.86 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 622.12 249.91 372.21 381.62 1592.18 0.00 0.00 0.00
February 927.69 342.69 584.99 627.83 1510.17 0.00 0.00 0.00
March 969.45 191.04 778.41 611.20 1269.18 0.00 0.00 0.00
April 2603.06 1223.20 1379.87 2692.99 1093.22 0.00 0.00 0.00
May 2737.04 1193.58 1543.46 2754.76 936.71 0.00 0.00 0.00
June 2709.17 1082.02 1627.15 2896.44 747.83 0.00 0.00 0.00
July 2765.53 1175.35 1590.18 3084.34 695.17 0.00 0.00 0.00
August 2619.73 1251.68 1368.05 3011.88 756.95 0.00 0.00 0.00
September 2359.16 1254.49 1104.67 2630.71 948.16 0.00 0.00 0.00
October 1138.80 471.95 666.85 1019.94 1193.08 0.00 0.00 0.00
November 593.69 202.34 391.35 362.33 1407.50 0.00 0.00 0.00
December 440.00 163.58 276.41 239.27 1717.37 0.00 0.00 0.00
                 
Annual Sum or Average 1709.59 734.43 975.16 1696.57 1153.88 0.00 0.00 0.00
Minimum of Months 440.00 163.58 276.41 239.27 695.17 0.00 0.00 0.00
Maximum of Months 2765.53 1254.49 1627.15 3084.34 1717.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2592.02 1677.92 914.10 2577.29 2353.12 0.00 0.00 0.00
February 3165.67 1931.74 1233.94 3222.87 2328.41 0.00 0.00 0.00
March 1957.23 569.86 1387.37 1598.21 1962.33 0.00 0.00 0.00
April 4064.34 1837.03 2227.31 4581.76 1794.26 0.00 0.00 0.00
May 3361.59 1094.42 2267.16 3505.47 1534.87 0.00 0.00 0.00
June 3096.74 749.59 2347.15 3350.70 1205.42 0.00 0.00 0.00
July 3355.26 1050.74 2304.52 3908.65 1125.34 0.00 0.00 0.00
August 3931.63 1768.59 2163.04 4852.39 1234.60 0.00 0.00 0.00
September 4646.16 2721.80 1924.36 5691.93 1545.04 0.00 0.00 0.00
October 3192.10 1865.64 1326.46 3516.21 1872.32 0.00 0.00 0.00
November 2263.20 1376.76 886.44 2260.80 2163.36 0.00 0.00 0.00
December 1793.79 1149.29 644.50 1740.59 2596.83 0.00 0.00 0.00
                 
Annual Sum or Average 3113.54 1477.03 1636.52 3395.78 1806.85 0.00 0.00 0.00
Minimum of Months 1793.79 569.86 644.50 1598.21 1125.34 0.00 0.00 0.00
Maximum of Months 4646.16 2721.80 2347.15 5691.93 2596.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 604.98 199.89 405.09 369.19 1682.06 0.00 0.00 0.00
February 1071.15 452.27 618.87 849.85 1630.55 0.00 0.00 0.00
March 968.55 185.28 783.26 586.68 1346.68 0.00 0.00 0.00
April 2285.32 907.75 1377.57 2306.82 1197.05 0.00 0.00 0.00
May 2681.21 1090.27 1590.94 2692.92 1021.47 0.00 0.00 0.00
June 2895.42 1191.93 1703.48 3133.37 822.57 0.00 0.00 0.00
July 2948.86 1300.16 1648.70 3333.99 771.10 0.00 0.00 0.00
August 2476.84 1072.40 1404.44 2828.42 842.55 0.00 0.00 0.00
September 1987.09 891.05 1096.03 2190.72 1038.19 0.00 0.00 0.00
October 1060.03 381.18 678.85 930.09 1285.92 0.00 0.00 0.00
November 573.65 167.46 406.20 353.60 1522.60 0.00 0.00 0.00
December 324.70 68.52 256.19 122.38 1858.08 0.00 0.00 0.00
                 
Annual Sum or Average 1658.24 659.28 998.95 1644.12 1249.62 0.00 0.00 0.00
Minimum of Months 324.70 68.52 256.19 122.38 771.10 0.00 0.00 0.00
Maximum of Months 2948.86 1300.16 1703.48 3333.99 1858.08 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244571E+09 0.00 0.244571E+09 7605057.56 0.168422E+10
February 0.344949E+09 0.00 0.344949E+09 26853993.43 0.142390E+10
March 0.528493E+09 0.00 0.528493E+09 0.131048E+09 0.132229E+10
April 0.832711E+09 3726864.40 0.828984E+09 0.489181E+09 0.100583E+10
May 0.107580E+10 51902359.29 0.102390E+10 0.660477E+09 0.804289E+09
June 0.115087E+10 72167087.81 0.107870E+10 0.936259E+09 0.610483E+09
July 0.112805E+10 64316260.84 0.106374E+10 0.974324E+09 0.586503E+09
August 0.886707E+09 13892506.25 0.872815E+09 0.744556E+09 0.662515E+09
September 0.653135E+09 144525.63 0.652990E+09 0.464852E+09 0.848967E+09
October 0.432475E+09 0.00 0.432475E+09 0.145829E+09 0.122269E+10
November 0.251471E+09 0.00 0.251471E+09 12446119.94 0.148782E+10
December 0.176959E+09 0.00 0.176959E+09 7410.88 0.185959E+10
           
Annual Sum or Average 0.770620E+10 0.206150E+09 0.750005E+10 0.459344E+10 0.135191E+11
Minimum of Months 0.176959E+09 0.00 0.176959E+09 7410.88 0.586503E+09
Maximum of Months 0.115087E+10 72167087.81 0.107870E+10 0.974324E+09 0.185959E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244571E+09 0.00 0.244571E+09 7605011.51 0.168422E+10
February 0.344949E+09 0.00 0.344949E+09 26853856.39 0.142390E+10
March 0.528493E+09 0.00 0.528493E+09 0.131047E+09 0.132229E+10
April 0.832710E+09 3726859.92 0.828983E+09 0.489180E+09 0.100583E+10
May 0.107580E+10 51902297.01 0.102390E+10 0.660476E+09 0.804290E+09
June 0.115087E+10 72167001.21 0.107870E+10 0.936258E+09 0.610483E+09
July 0.112805E+10 64316183.67 0.106374E+10 0.974322E+09 0.586503E+09
August 0.886707E+09 13892489.58 0.872814E+09 0.744556E+09 0.662515E+09
September 0.653134E+09 144525.46 0.652990E+09 0.464851E+09 0.848967E+09
October 0.432475E+09 0.00 0.432475E+09 0.145829E+09 0.122269E+10
November 0.251471E+09 0.00 0.251471E+09 12446052.19 0.148782E+10
December 0.176959E+09 0.00 0.176959E+09 7410.56 0.185959E+10
           
Annual Sum or Average 0.770619E+10 0.206149E+09 0.750004E+10 0.459343E+10 0.135191E+11
Minimum of Months 0.176959E+09 0.00 0.176959E+09 7410.56 0.586503E+09
Maximum of Months 0.115087E+10 72167001.21 0.107870E+10 0.974322E+09 0.185959E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244571E+09 0.00 0.244571E+09 7605057.56 0.168422E+10
February 0.344949E+09 0.00 0.344949E+09 26853993.43 0.142390E+10
March 0.528493E+09 0.00 0.528493E+09 0.131048E+09 0.132229E+10
April 0.832711E+09 3726864.40 0.828984E+09 0.489181E+09 0.100583E+10
May 0.107580E+10 51902359.29 0.102390E+10 0.660477E+09 0.804289E+09
June 0.115087E+10 72167087.81 0.107870E+10 0.936259E+09 0.610483E+09
July 0.112805E+10 64316260.84 0.106374E+10 0.974324E+09 0.586503E+09
August 0.886707E+09 13892506.25 0.872815E+09 0.744556E+09 0.662515E+09
September 0.653135E+09 144525.63 0.652990E+09 0.464852E+09 0.848967E+09
October 0.432475E+09 0.00 0.432475E+09 0.145829E+09 0.122269E+10
November 0.251471E+09 0.00 0.251471E+09 12446119.94 0.148782E+10
December 0.176959E+09 0.00 0.176959E+09 7410.88 0.185959E+10
           
Annual Sum or Average 0.770620E+10 0.206150E+09 0.750005E+10 0.459344E+10 0.135191E+11
Minimum of Months 0.176959E+09 0.00 0.176959E+09 7410.88 0.586503E+09
Maximum of Months 0.115087E+10 72167087.81 0.107870E+10 0.974324E+09 0.185959E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244571E+09 0.00 0.244571E+09 7605011.51 0.168422E+10
February 0.344949E+09 0.00 0.344949E+09 26853856.39 0.142390E+10
March 0.528493E+09 0.00 0.528493E+09 0.131047E+09 0.132229E+10
April 0.832710E+09 3726859.92 0.828983E+09 0.489180E+09 0.100583E+10
May 0.107580E+10 51902297.01 0.102390E+10 0.660476E+09 0.804290E+09
June 0.115087E+10 72167001.21 0.107870E+10 0.936258E+09 0.610483E+09
July 0.112805E+10 64316183.67 0.106374E+10 0.974322E+09 0.586503E+09
August 0.886707E+09 13892489.58 0.872814E+09 0.744556E+09 0.662515E+09
September 0.653134E+09 144525.46 0.652990E+09 0.464851E+09 0.848967E+09
October 0.432475E+09 0.00 0.432475E+09 0.145829E+09 0.122269E+10
November 0.251471E+09 0.00 0.251471E+09 12446052.19 0.148782E+10
December 0.176959E+09 0.00 0.176959E+09 7410.56 0.185959E+10
           
Annual Sum or Average 0.770619E+10 0.206149E+09 0.750004E+10 0.459343E+10 0.135191E+11
Minimum of Months 0.176959E+09 0.00 0.176959E+09 7410.56 0.586503E+09
Maximum of Months 0.115087E+10 72167001.21 0.107870E+10 0.974322E+09 0.185959E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244561E+09 0.00 0.244561E+09 7604751.04 0.168416E+10
February 0.344935E+09 0.00 0.344935E+09 26852911.10 0.142385E+10
March 0.528472E+09 0.00 0.528472E+09 0.131042E+09 0.132223E+10
April 0.832677E+09 3726714.19 0.828950E+09 0.489161E+09 0.100579E+10
May 0.107576E+10 51900267.39 0.102386E+10 0.660450E+09 0.804257E+09
June 0.115083E+10 72164179.15 0.107866E+10 0.936221E+09 0.610458E+09
July 0.112801E+10 64313668.61 0.106369E+10 0.974284E+09 0.586480E+09
August 0.886672E+09 13891946.32 0.872780E+09 0.744526E+09 0.662488E+09
September 0.653109E+09 144519.81 0.652964E+09 0.464833E+09 0.848933E+09
October 0.432458E+09 0.00 0.432458E+09 0.145823E+09 0.122264E+10
November 0.251461E+09 0.00 0.251461E+09 12445618.31 0.148776E+10
December 0.176952E+09 0.00 0.176952E+09 7410.58 0.185952E+10
           
Annual Sum or Average 0.770589E+10 0.206141E+09 0.749975E+10 0.459325E+10 0.135186E+11
Minimum of Months 0.176952E+09 0.00 0.176952E+09 7410.58 0.586480E+09
Maximum of Months 0.115083E+10 72164179.15 0.107866E+10 0.974284E+09 0.185952E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555434E+09 0.223119E+09 0.332315E+09 0.294070E+09 0.173997E+10
February 0.748095E+09 0.276352E+09 0.471743E+09 0.448578E+09 0.147452E+10
March 0.865537E+09 0.170566E+09 0.694972E+09 0.470814E+09 0.136029E+10
April 0.224907E+10 0.105685E+10 0.119222E+10 0.231057E+10 0.103691E+10
May 0.244365E+10 0.106564E+10 0.137802E+10 0.245068E+10 0.912465E+09
June 0.234075E+10 0.934871E+09 0.140587E+10 0.251268E+10 0.686196E+09
July 0.246909E+10 0.104936E+10 0.141973E+10 0.276646E+10 0.656738E+09
August 0.233892E+10 0.111751E+10 0.122141E+10 0.269992E+10 0.713308E+09
September 0.203833E+10 0.108389E+10 0.954440E+09 0.226687E+10 0.890979E+09
October 0.101673E+10 0.421358E+09 0.595369E+09 0.860159E+09 0.128477E+10
November 0.512952E+09 0.174821E+09 0.338130E+09 0.267959E+09 0.153310E+10
December 0.392832E+09 0.146049E+09 0.246782E+09 0.177380E+09 0.189877E+10
           
Annual Sum or Average 0.179714E+11 0.772039E+10 0.102510E+11 0.175261E+11 0.141880E+11
Minimum of Months 0.392832E+09 0.146049E+09 0.246782E+09 0.177380E+09 0.656738E+09
Maximum of Months 0.246909E+10 0.111751E+10 0.141973E+10 0.276646E+10 0.189877E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555434E+09 0.223119E+09 0.332315E+09 0.294070E+09 0.173997E+10
February 0.748095E+09 0.276352E+09 0.471743E+09 0.448578E+09 0.147452E+10
March 0.865537E+09 0.170566E+09 0.694972E+09 0.470814E+09 0.136029E+10
April 0.224907E+10 0.105685E+10 0.119222E+10 0.231057E+10 0.103691E+10
May 0.244365E+10 0.106564E+10 0.137802E+10 0.245068E+10 0.912465E+09
June 0.234075E+10 0.934871E+09 0.140587E+10 0.251268E+10 0.686196E+09
July 0.246909E+10 0.104936E+10 0.141973E+10 0.276646E+10 0.656738E+09
August 0.233892E+10 0.111751E+10 0.122141E+10 0.269992E+10 0.713308E+09
September 0.203833E+10 0.108389E+10 0.954440E+09 0.226687E+10 0.890979E+09
October 0.101673E+10 0.421358E+09 0.595369E+09 0.860159E+09 0.128477E+10
November 0.512952E+09 0.174821E+09 0.338130E+09 0.267959E+09 0.153310E+10
December 0.392832E+09 0.146049E+09 0.246782E+09 0.177380E+09 0.189877E+10
           
Annual Sum or Average 0.179714E+11 0.772039E+10 0.102510E+11 0.175261E+11 0.141880E+11
Minimum of Months 0.392832E+09 0.146049E+09 0.246782E+09 0.177380E+09 0.656738E+09
Maximum of Months 0.246909E+10 0.111751E+10 0.141973E+10 0.276646E+10 0.189877E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555423E+09 0.223114E+09 0.332309E+09 0.294065E+09 0.173994E+10
February 0.748081E+09 0.276347E+09 0.471735E+09 0.448570E+09 0.147450E+10
March 0.865522E+09 0.170563E+09 0.694959E+09 0.470805E+09 0.136027E+10
April 0.224903E+10 0.105683E+10 0.119220E+10 0.231053E+10 0.103689E+10
May 0.244361E+10 0.106562E+10 0.137799E+10 0.245064E+10 0.912448E+09
June 0.234070E+10 0.934854E+09 0.140585E+10 0.251263E+10 0.686183E+09
July 0.246904E+10 0.104934E+10 0.141970E+10 0.276641E+10 0.656726E+09
August 0.233888E+10 0.111749E+10 0.122138E+10 0.269988E+10 0.713295E+09
September 0.203830E+10 0.108387E+10 0.954423E+09 0.226683E+10 0.890963E+09
October 0.101671E+10 0.421350E+09 0.595359E+09 0.860144E+09 0.128475E+10
November 0.512943E+09 0.174818E+09 0.338124E+09 0.267954E+09 0.153307E+10
December 0.392825E+09 0.146047E+09 0.246778E+09 0.177376E+09 0.189873E+10
           
Annual Sum or Average 0.179711E+11 0.772025E+10 0.102508E+11 0.175258E+11 0.141878E+11
Minimum of Months 0.392825E+09 0.146047E+09 0.246778E+09 0.177376E+09 0.656726E+09
Maximum of Months 0.246904E+10 0.111749E+10 0.141970E+10 0.276641E+10 0.189873E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138851E+10 0.898838E+09 0.489670E+09 0.134273E+10 0.144493E+10
February 0.153170E+10 0.934662E+09 0.597034E+09 0.152534E+10 0.128101E+10
March 0.104846E+10 0.305264E+09 0.743195E+09 0.809407E+09 0.121764E+10
April 0.210698E+10 0.952330E+09 0.115465E+10 0.236636E+10 0.101676E+10
May 0.180076E+10 0.586268E+09 0.121449E+10 0.187076E+10 0.890088E+09
June 0.160537E+10 0.388593E+09 0.121678E+10 0.173710E+10 0.668445E+09
July 0.179737E+10 0.562865E+09 0.123450E+10 0.209413E+10 0.646599E+09
August 0.210612E+10 0.947411E+09 0.115871E+10 0.260539E+10 0.707312E+09
September 0.240860E+10 0.141100E+10 0.997601E+09 0.295718E+10 0.854816E+09
October 0.170997E+10 0.999398E+09 0.710568E+09 0.185902E+10 0.115142E+10
November 0.117326E+10 0.713722E+09 0.459535E+09 0.114008E+10 0.133010E+10
December 0.960911E+09 0.615660E+09 0.345251E+09 0.895809E+09 0.164375E+10
           
Annual Sum or Average 0.196380E+11 0.931601E+10 0.103220E+11 0.212033E+11 0.128529E+11
Minimum of Months 0.960911E+09 0.305264E+09 0.345251E+09 0.809407E+09 0.646599E+09
Maximum of Months 0.240860E+10 0.141100E+10 0.123450E+10 0.295718E+10 0.164375E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138851E+10 0.898837E+09 0.489669E+09 0.134273E+10 0.144493E+10
February 0.153170E+10 0.934661E+09 0.597034E+09 0.152534E+10 0.128101E+10
March 0.104846E+10 0.305264E+09 0.743195E+09 0.809405E+09 0.121764E+10
April 0.210698E+10 0.952329E+09 0.115465E+10 0.236636E+10 0.101676E+10
May 0.180075E+10 0.586267E+09 0.121449E+10 0.187075E+10 0.890088E+09
June 0.160537E+10 0.388592E+09 0.121678E+10 0.173710E+10 0.668445E+09
July 0.179737E+10 0.562865E+09 0.123450E+10 0.209413E+10 0.646599E+09
August 0.210612E+10 0.947410E+09 0.115871E+10 0.260539E+10 0.707312E+09
September 0.240859E+10 0.141099E+10 0.997600E+09 0.295718E+10 0.854816E+09
October 0.170996E+10 0.999397E+09 0.710567E+09 0.185902E+10 0.115142E+10
November 0.117326E+10 0.713721E+09 0.459534E+09 0.114008E+10 0.133010E+10
December 0.960910E+09 0.615659E+09 0.345250E+09 0.895807E+09 0.164375E+10
           
Annual Sum or Average 0.196380E+11 0.931600E+10 0.103220E+11 0.212033E+11 0.128529E+11
Minimum of Months 0.960910E+09 0.305264E+09 0.345250E+09 0.809405E+09 0.646599E+09
Maximum of Months 0.240859E+10 0.141099E+10 0.123450E+10 0.295718E+10 0.164375E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138851E+10 0.898838E+09 0.489670E+09 0.134273E+10 0.144493E+10
February 0.153170E+10 0.934662E+09 0.597034E+09 0.152534E+10 0.128101E+10
March 0.104846E+10 0.305264E+09 0.743195E+09 0.809407E+09 0.121764E+10
April 0.210698E+10 0.952330E+09 0.115465E+10 0.236636E+10 0.101676E+10
May 0.180076E+10 0.586268E+09 0.121449E+10 0.187076E+10 0.890088E+09
June 0.160537E+10 0.388593E+09 0.121678E+10 0.173710E+10 0.668445E+09
July 0.179737E+10 0.562865E+09 0.123450E+10 0.209413E+10 0.646599E+09
August 0.210612E+10 0.947411E+09 0.115871E+10 0.260539E+10 0.707312E+09
September 0.240860E+10 0.141100E+10 0.997601E+09 0.295718E+10 0.854816E+09
October 0.170997E+10 0.999398E+09 0.710568E+09 0.185902E+10 0.115142E+10
November 0.117326E+10 0.713722E+09 0.459535E+09 0.114008E+10 0.133010E+10
December 0.960911E+09 0.615660E+09 0.345251E+09 0.895809E+09 0.164375E+10
           
Annual Sum or Average 0.196380E+11 0.931601E+10 0.103220E+11 0.212033E+11 0.128529E+11
Minimum of Months 0.960911E+09 0.305264E+09 0.345251E+09 0.809407E+09 0.646599E+09
Maximum of Months 0.240860E+10 0.141100E+10 0.123450E+10 0.295718E+10 0.164375E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138851E+10 0.898837E+09 0.489669E+09 0.134273E+10 0.144493E+10
February 0.153170E+10 0.934661E+09 0.597034E+09 0.152534E+10 0.128101E+10
March 0.104846E+10 0.305264E+09 0.743195E+09 0.809405E+09 0.121764E+10
April 0.210698E+10 0.952329E+09 0.115465E+10 0.236636E+10 0.101676E+10
May 0.180075E+10 0.586267E+09 0.121449E+10 0.187075E+10 0.890088E+09
June 0.160537E+10 0.388592E+09 0.121678E+10 0.173710E+10 0.668445E+09
July 0.179737E+10 0.562865E+09 0.123450E+10 0.209413E+10 0.646599E+09
August 0.210612E+10 0.947410E+09 0.115871E+10 0.260539E+10 0.707312E+09
September 0.240859E+10 0.141099E+10 0.997600E+09 0.295718E+10 0.854816E+09
October 0.170996E+10 0.999397E+09 0.710567E+09 0.185902E+10 0.115142E+10
November 0.117326E+10 0.713721E+09 0.459534E+09 0.114008E+10 0.133010E+10
December 0.960910E+09 0.615659E+09 0.345250E+09 0.895807E+09 0.164375E+10
           
Annual Sum or Average 0.196380E+11 0.931600E+10 0.103220E+11 0.212033E+11 0.128529E+11
Minimum of Months 0.960910E+09 0.305264E+09 0.345250E+09 0.809405E+09 0.646599E+09
Maximum of Months 0.240859E+10 0.141099E+10 0.123450E+10 0.295718E+10 0.164375E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138845E+10 0.898802E+09 0.489650E+09 0.134268E+10 0.144487E+10
February 0.153164E+10 0.934625E+09 0.597010E+09 0.152528E+10 0.128096E+10
March 0.104842E+10 0.305252E+09 0.743165E+09 0.809374E+09 0.121759E+10
April 0.210689E+10 0.952292E+09 0.115460E+10 0.236627E+10 0.101671E+10
May 0.180068E+10 0.586244E+09 0.121444E+10 0.187068E+10 0.890053E+09
June 0.160530E+10 0.388577E+09 0.121673E+10 0.173703E+10 0.668418E+09
July 0.179729E+10 0.562843E+09 0.123445E+10 0.209405E+10 0.646573E+09
August 0.210603E+10 0.947373E+09 0.115866E+10 0.260529E+10 0.707284E+09
September 0.240850E+10 0.141094E+10 0.997560E+09 0.295706E+10 0.854782E+09
October 0.170990E+10 0.999358E+09 0.710539E+09 0.185894E+10 0.115138E+10
November 0.117321E+10 0.713693E+09 0.459516E+09 0.114004E+10 0.133005E+10
December 0.960872E+09 0.615635E+09 0.345237E+09 0.895772E+09 0.164369E+10
           
Annual Sum or Average 0.196372E+11 0.931563E+10 0.103216E+11 0.212025E+11 0.128524E+11
Minimum of Months 0.960872E+09 0.305252E+09 0.345237E+09 0.809374E+09 0.646573E+09
Maximum of Months 0.240850E+10 0.141094E+10 0.123445E+10 0.295706E+10 0.164369E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.540132E+09 0.178462E+09 0.361670E+09 0.284442E+09 0.188631E+10
February 0.863783E+09 0.364717E+09 0.499066E+09 0.625304E+09 0.166381E+10
March 0.864728E+09 0.165422E+09 0.699306E+09 0.437698E+09 0.156361E+10
April 0.197454E+10 0.784303E+09 0.119023E+10 0.192572E+10 0.124410E+10
May 0.239381E+10 0.973405E+09 0.142040E+10 0.237412E+10 0.102556E+10
June 0.250167E+10 0.102984E+10 0.147183E+10 0.269186E+10 0.802499E+09
July 0.263277E+10 0.116079E+10 0.147197E+10 0.294522E+10 0.796071E+09
August 0.221135E+10 0.957452E+09 0.125390E+10 0.248853E+10 0.885569E+09
September 0.171686E+10 0.769879E+09 0.946981E+09 0.186232E+10 0.101611E+10
October 0.946408E+09 0.340324E+09 0.606084E+09 0.763772E+09 0.146212E+10
November 0.495642E+09 0.144684E+09 0.350958E+09 0.257944E+09 0.178401E+10
December 0.289899E+09 61175108.52 0.228724E+09 81310841.42 0.227238E+10
           
Annual Sum or Average 0.174316E+11 0.693046E+10 0.105011E+11 0.167382E+11 0.164021E+11
Minimum of Months 0.289899E+09 61175108.52 0.228724E+09 81310841.42 0.796071E+09
Maximum of Months 0.263277E+10 0.116079E+10 0.147197E+10 0.294522E+10 0.227238E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.540132E+09 0.178462E+09 0.361670E+09 0.284442E+09 0.188631E+10
February 0.863783E+09 0.364717E+09 0.499066E+09 0.625304E+09 0.166381E+10
March 0.864728E+09 0.165422E+09 0.699306E+09 0.437698E+09 0.156361E+10
April 0.197454E+10 0.784303E+09 0.119023E+10 0.192572E+10 0.124410E+10
May 0.239381E+10 0.973405E+09 0.142040E+10 0.237412E+10 0.102556E+10
June 0.250167E+10 0.102984E+10 0.147183E+10 0.269186E+10 0.802499E+09
July 0.263277E+10 0.116079E+10 0.147197E+10 0.294522E+10 0.796071E+09
August 0.221135E+10 0.957452E+09 0.125390E+10 0.248853E+10 0.885569E+09
September 0.171686E+10 0.769879E+09 0.946981E+09 0.186232E+10 0.101611E+10
October 0.946408E+09 0.340324E+09 0.606084E+09 0.763772E+09 0.146212E+10
November 0.495642E+09 0.144684E+09 0.350958E+09 0.257944E+09 0.178401E+10
December 0.289899E+09 61175108.52 0.228724E+09 81310841.42 0.227238E+10
           
Annual Sum or Average 0.174316E+11 0.693046E+10 0.105011E+11 0.167382E+11 0.164021E+11
Minimum of Months 0.289899E+09 61175108.52 0.228724E+09 81310841.42 0.796071E+09
Maximum of Months 0.263277E+10 0.116079E+10 0.147197E+10 0.294522E+10 0.227238E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.540122E+09 0.178459E+09 0.361664E+09 0.284436E+09 0.188628E+10
February 0.863767E+09 0.364710E+09 0.499057E+09 0.625293E+09 0.166378E+10
March 0.864712E+09 0.165419E+09 0.699293E+09 0.437690E+09 0.156358E+10
April 0.197450E+10 0.784289E+09 0.119021E+10 0.192568E+10 0.124408E+10
May 0.239376E+10 0.973387E+09 0.142038E+10 0.237408E+10 0.102554E+10
June 0.250162E+10 0.102982E+10 0.147180E+10 0.269181E+10 0.802484E+09
July 0.263272E+10 0.116077E+10 0.147195E+10 0.294516E+10 0.796057E+09
August 0.221131E+10 0.957434E+09 0.125387E+10 0.248848E+10 0.885553E+09
September 0.171683E+10 0.769865E+09 0.946964E+09 0.186228E+10 0.101609E+10
October 0.946390E+09 0.340318E+09 0.606073E+09 0.763758E+09 0.146209E+10
November 0.495633E+09 0.144681E+09 0.350951E+09 0.257940E+09 0.178397E+10
December 0.289894E+09 61173990.71 0.228720E+09 81309355.69 0.227234E+10
           
Annual Sum or Average 0.174313E+11 0.693033E+10 0.105009E+11 0.167379E+11 0.164018E+11
Minimum of Months 0.289894E+09 61173990.71 0.228720E+09 81309355.69 0.796057E+09
Maximum of Months 0.263272E+10 0.116077E+10 0.147195E+10 0.294516E+10 0.227234E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122284E+10 0.00 0.122284E+10 81111456.43 0.741988E+10
February 0.172472E+10 0.00 0.172472E+10 0.244370E+09 0.626898E+10
March 0.264243E+10 0.00 0.264243E+10 0.837237E+09 0.583178E+10
April 0.416350E+10 18634096.65 0.414487E+10 0.258925E+10 0.460226E+10
May 0.537895E+10 0.259509E+09 0.511945E+10 0.342274E+10 0.378190E+10
June 0.575429E+10 0.360831E+09 0.539346E+10 0.474034E+10 0.289411E+10
July 0.564019E+10 0.321577E+09 0.531862E+10 0.498113E+10 0.275163E+10
August 0.443348E+10 69461691.30 0.436402E+10 0.383083E+10 0.307700E+10
September 0.326564E+10 722619.41 0.326491E+10 0.242374E+10 0.396666E+10
October 0.216235E+10 0.00 0.216235E+10 0.877308E+09 0.542172E+10
November 0.125734E+10 0.00 0.125734E+10 0.130677E+09 0.633773E+10
December 0.884787E+09 0.00 0.884787E+09 6111285.81 0.784408E+10
           
Annual Sum or Average 0.385305E+11 0.103074E+10 0.374998E+11 0.241649E+11 0.601977E+11
Minimum of Months 0.884787E+09 0.00 0.884787E+09 6111285.81 0.275163E+10
Maximum of Months 0.575429E+10 0.360831E+09 0.539346E+10 0.498113E+10 0.784408E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166628E+10 0.669349E+09 0.996935E+09 0.944357E+09 0.470538E+10
February 0.224426E+10 0.829047E+09 0.141522E+10 0.141203E+10 0.403532E+10
March 0.259659E+10 0.511692E+09 0.208489E+10 0.149455E+10 0.374656E+10
April 0.674714E+10 0.317053E+10 0.357661E+10 0.691019E+10 0.299432E+10
May 0.733089E+10 0.319687E+10 0.413401E+10 0.730873E+10 0.264050E+10
June 0.702217E+10 0.280458E+10 0.421758E+10 0.748385E+10 0.200261E+10
July 0.740718E+10 0.314805E+10 0.425913E+10 0.824411E+10 0.191773E+10
August 0.701669E+10 0.335251E+10 0.366418E+10 0.804866E+10 0.209083E+10
September 0.611494E+10 0.325164E+10 0.286329E+10 0.676336E+10 0.258743E+10
October 0.305015E+10 0.126406E+10 0.178609E+10 0.262001E+10 0.355524E+10
November 0.153884E+10 0.524459E+09 0.101438E+10 0.859570E+09 0.408544E+10
December 0.117848E+10 0.438144E+09 0.740340E+09 0.592857E+09 0.500992E+10
           
Annual Sum or Average 0.539136E+11 0.231609E+11 0.307527E+11 0.526823E+11 0.393713E+11
Minimum of Months 0.117848E+10 0.438144E+09 0.740340E+09 0.592857E+09 0.191773E+10
Maximum of Months 0.740718E+10 0.335251E+10 0.425913E+10 0.824411E+10 0.500992E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.694246E+10 0.449414E+10 0.244832E+10 0.674350E+10 0.693232E+10
February 0.765839E+10 0.467326E+10 0.298514E+10 0.764059E+10 0.617165E+10
March 0.524223E+10 0.152630E+10 0.371593E+10 0.410772E+10 0.576667E+10
April 0.105348E+11 0.476159E+10 0.577318E+10 0.118075E+11 0.491279E+10
May 0.900367E+10 0.293130E+10 0.607237E+10 0.931468E+10 0.434188E+10
June 0.802675E+10 0.194294E+10 0.608381E+10 0.866526E+10 0.323910E+10
July 0.898673E+10 0.281429E+10 0.617243E+10 0.104613E+11 0.311575E+10
August 0.105305E+11 0.473700E+10 0.579347E+10 0.129974E+11 0.341844E+10
September 0.120428E+11 0.705490E+10 0.498794E+10 0.147086E+11 0.421311E+10
October 0.854973E+10 0.499693E+10 0.355280E+10 0.928581E+10 0.553418E+10
November 0.586621E+10 0.356857E+10 0.229765E+10 0.573534E+10 0.623546E+10
December 0.480450E+10 0.307826E+10 0.172623E+10 0.455679E+10 0.757864E+10
           
Annual Sum or Average 0.981887E+11 0.465795E+11 0.516093E+11 0.106025E+12 0.614600E+11
Minimum of Months 0.480450E+10 0.152630E+10 0.172623E+10 0.410772E+10 0.311575E+10
Maximum of Months 0.120428E+11 0.705490E+10 0.617243E+10 0.147086E+11 0.757864E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.162038E+10 0.535380E+09 0.108500E+10 0.935021E+09 0.489813E+10
February 0.259132E+10 0.109414E+10 0.149718E+10 0.199086E+10 0.426518E+10
March 0.259416E+10 0.496262E+09 0.209790E+10 0.147985E+10 0.390991E+10
April 0.592355E+10 0.235289E+10 0.357067E+10 0.593298E+10 0.326491E+10
May 0.718135E+10 0.292019E+10 0.426117E+10 0.717231E+10 0.287051E+10
June 0.750492E+10 0.308949E+10 0.441543E+10 0.812690E+10 0.220283E+10
July 0.789822E+10 0.348235E+10 0.441587E+10 0.894038E+10 0.212888E+10
August 0.663398E+10 0.287233E+10 0.376165E+10 0.758392E+10 0.232759E+10
September 0.515053E+10 0.230961E+10 0.284091E+10 0.564516E+10 0.282581E+10
October 0.283919E+10 0.102096E+10 0.181823E+10 0.241361E+10 0.376075E+10
November 0.148691E+10 0.434048E+09 0.105286E+10 0.869255E+09 0.432495E+10
December 0.869689E+09 0.183523E+09 0.686166E+09 0.304661E+09 0.534347E+10
           
Annual Sum or Average 0.522942E+11 0.207912E+11 0.315030E+11 0.513949E+11 0.421229E+11
Minimum of Months 0.869689E+09 0.183523E+09 0.686166E+09 0.304661E+09 0.212888E+10
Maximum of Months 0.789822E+10 0.348235E+10 0.441587E+10 0.894038E+10 0.534347E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122284E+10 0.00 0.122284E+10 0.129606E+09 0.674904E+10
February 0.172472E+10 0.00 0.172472E+10 0.344861E+09 0.569398E+10
March 0.264243E+10 0.00 0.264243E+10 0.989009E+09 0.530242E+10
April 0.416350E+10 18634096.65 0.414487E+10 0.269904E+10 0.431554E+10
May 0.537895E+10 0.259509E+09 0.511945E+10 0.356096E+10 0.356370E+10
June 0.575429E+10 0.360831E+09 0.539346E+10 0.478095E+10 0.278978E+10
July 0.564019E+10 0.321577E+09 0.531862E+10 0.501185E+10 0.266210E+10
August 0.443348E+10 69461691.30 0.436402E+10 0.386165E+10 0.296668E+10
September 0.326564E+10 722619.41 0.326491E+10 0.251385E+10 0.372814E+10
October 0.216235E+10 0.00 0.216235E+10 0.102398E+10 0.485685E+10
November 0.125734E+10 0.00 0.125734E+10 0.194783E+09 0.567906E+10
December 0.884787E+09 0.00 0.884787E+09 26646718.63 0.720451E+10
           
Annual Sum or Average 0.385305E+11 0.103074E+10 0.374998E+11 0.251372E+11 0.555118E+11
Minimum of Months 0.884787E+09 0.00 0.884787E+09 26646718.63 0.266210E+10
Maximum of Months 0.575429E+10 0.360831E+09 0.539346E+10 0.501185E+10 0.720451E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166628E+10 0.669349E+09 0.996935E+09 0.102213E+10 0.426450E+10
February 0.224426E+10 0.829047E+09 0.141522E+10 0.151885E+10 0.365340E+10
March 0.259659E+10 0.511692E+09 0.208489E+10 0.163704E+10 0.339936E+10
April 0.674714E+10 0.317053E+10 0.357661E+10 0.698023E+10 0.283362E+10
May 0.733089E+10 0.319687E+10 0.413401E+10 0.737836E+10 0.250888E+10
June 0.702217E+10 0.280458E+10 0.421758E+10 0.750757E+10 0.193838E+10
July 0.740718E+10 0.314805E+10 0.425913E+10 0.826109E+10 0.186194E+10
August 0.701669E+10 0.335251E+10 0.366418E+10 0.806702E+10 0.202742E+10
September 0.611494E+10 0.325164E+10 0.286329E+10 0.681881E+10 0.245764E+10
October 0.305015E+10 0.126406E+10 0.178609E+10 0.273180E+10 0.319553E+10
November 0.153884E+10 0.524459E+09 0.101438E+10 0.939156E+09 0.364824E+10
December 0.117848E+10 0.438144E+09 0.740340E+09 0.640856E+09 0.459980E+10
           
Annual Sum or Average 0.539136E+11 0.231609E+11 0.307527E+11 0.535029E+11 0.363887E+11
Minimum of Months 0.117848E+10 0.438144E+09 0.740340E+09 0.640856E+09 0.186194E+10
Maximum of Months 0.740718E+10 0.335251E+10 0.425913E+10 0.826109E+10 0.459980E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.694246E+10 0.449414E+10 0.244832E+10 0.690302E+10 0.630260E+10
February 0.765839E+10 0.467326E+10 0.298514E+10 0.779676E+10 0.563290E+10
March 0.524223E+10 0.152630E+10 0.371593E+10 0.428064E+10 0.525591E+10
April 0.105348E+11 0.476159E+10 0.577318E+10 0.118759E+11 0.465073E+10
May 0.900367E+10 0.293130E+10 0.607237E+10 0.938905E+10 0.411099E+10
June 0.802675E+10 0.194294E+10 0.608381E+10 0.868500E+10 0.312446E+10
July 0.898673E+10 0.281429E+10 0.617243E+10 0.104689E+11 0.301411E+10
August 0.105305E+11 0.473700E+10 0.579347E+10 0.129966E+11 0.330675E+10
September 0.120428E+11 0.705490E+10 0.498794E+10 0.147535E+11 0.400473E+10
October 0.854973E+10 0.499693E+10 0.355280E+10 0.941782E+10 0.501482E+10
November 0.586621E+10 0.356857E+10 0.229765E+10 0.586000E+10 0.560744E+10
December 0.480450E+10 0.307826E+10 0.172623E+10 0.466200E+10 0.695534E+10
           
Annual Sum or Average 0.981887E+11 0.465795E+11 0.516093E+11 0.107089E+12 0.569808E+11
Minimum of Months 0.480450E+10 0.152630E+10 0.172623E+10 0.428064E+10 0.301411E+10
Maximum of Months 0.120428E+11 0.705490E+10 0.617243E+10 0.147535E+11 0.695534E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.162038E+10 0.535380E+09 0.108500E+10 0.988852E+09 0.450524E+10
February 0.259132E+10 0.109414E+10 0.149718E+10 0.205597E+10 0.394462E+10
March 0.259416E+10 0.496262E+09 0.209790E+10 0.157136E+10 0.360696E+10
April 0.592355E+10 0.235289E+10 0.357067E+10 0.597927E+10 0.310275E+10
May 0.718135E+10 0.292019E+10 0.426117E+10 0.721271E+10 0.273591E+10
June 0.750492E+10 0.308949E+10 0.441543E+10 0.812170E+10 0.213210E+10
July 0.789822E+10 0.348235E+10 0.441587E+10 0.892976E+10 0.206531E+10
August 0.663398E+10 0.287233E+10 0.376165E+10 0.757564E+10 0.225670E+10
September 0.515053E+10 0.230961E+10 0.284091E+10 0.567834E+10 0.269100E+10
October 0.283919E+10 0.102096E+10 0.181823E+10 0.249116E+10 0.344420E+10
November 0.148691E+10 0.434048E+09 0.105286E+10 0.916525E+09 0.394658E+10
December 0.869689E+09 0.183523E+09 0.686166E+09 0.327787E+09 0.497669E+10
           
Annual Sum or Average 0.522942E+11 0.207912E+11 0.315030E+11 0.518491E+11 0.394081E+11
Minimum of Months 0.869689E+09 0.183523E+09 0.686166E+09 0.327787E+09 0.206531E+10
Maximum of Months 0.789822E+10 0.348235E+10 0.441587E+10 0.892976E+10 0.497669E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 14.20 3144.06 456.56 0.00 456.56 0.00 0.00
February 55.50 2942.90 712.93 0.00 712.93 0.00 0.00
March 244.64 2468.41 986.58 0.00 986.58 0.00 0.00
April 943.63 1940.24 1606.30 7.19 1599.11 0.00 0.00
May 1232.96 1501.42 2008.28 96.89 1911.39 0.00 0.00
June 1806.04 1177.62 2220.03 139.21 2080.82 0.00 0.00
July 1818.84 1094.87 2105.82 120.06 1985.75 0.00 0.00
August 1389.92 1236.76 1655.28 25.93 1629.34 0.00 0.00
September 896.70 1637.65 1259.89 0.28 1259.62 0.00 0.00
October 272.23 2282.47 807.33 0.00 807.33 0.00 0.00
November 24.01 2870.01 485.09 0.00 485.09 0.00 0.00
December 0.01 3471.44 330.34 0.00 330.34 0.00 0.00
               
Annual Sum or Average 728.28 2143.42 1221.80 32.68 1189.12 0.00 0.00
Minimum of Months 0.01 1094.87 330.34 0.00 330.34 0.00 0.00
Maximum of Months 1818.84 3471.44 2220.03 139.21 2080.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 329.38 1948.88 622.12 249.91 372.21 0.00 0.00
February 556.27 1828.52 927.69 342.70 585.00 0.00 0.00
March 527.34 1523.62 969.46 191.04 778.41 0.00 0.00
April 2674.25 1200.12 2603.07 1223.20 1379.87 0.00 0.00
May 2744.92 1022.02 2737.05 1193.58 1543.47 0.00 0.00
June 2908.17 794.20 2709.18 1082.02 1627.16 0.00 0.00
July 3098.62 735.59 2765.54 1175.35 1590.18 0.00 0.00
August 3024.09 798.95 2619.74 1251.69 1368.05 0.00 0.00
September 2623.67 1031.22 2359.17 1254.50 1104.67 0.00 0.00
October 963.43 1439.03 1138.80 471.95 666.85 0.00 0.00
November 310.14 1774.41 593.69 202.34 391.35 0.00 0.00
December 198.68 2126.74 440.00 163.58 276.41 0.00 0.00
               
Annual Sum or Average 1667.24 1349.69 1709.60 734.43 975.16 0.00 0.00
Minimum of Months 198.68 735.59 440.00 163.58 276.41 0.00 0.00
Maximum of Months 3098.62 2126.74 2765.54 1254.50 1627.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2506.57 2697.35 2592.03 1677.92 914.10 0.00 0.00
February 3152.55 2647.58 3165.68 1931.74 1233.94 0.00 0.00
March 1510.98 2273.05 1957.23 569.86 1387.37 0.00 0.00
April 4564.70 1961.32 4064.36 1837.04 2227.31 0.00 0.00
May 3492.27 1661.59 3361.60 1094.43 2267.17 0.00 0.00
June 3350.87 1289.43 3096.75 749.59 2347.16 0.00 0.00
July 3909.26 1207.05 3355.27 1050.74 2304.53 0.00 0.00
August 4863.67 1320.39 3931.64 1768.60 2163.04 0.00 0.00
September 5704.39 1648.94 4646.17 2721.81 1924.37 0.00 0.00
October 3470.36 2149.44 3192.11 1865.65 1326.47 0.00 0.00
November 2199.22 2565.76 2263.21 1376.77 886.44 0.00 0.00
December 1672.27 3068.51 1793.80 1149.30 644.50 0.00 0.00
               
Annual Sum or Average 3361.74 2037.79 3113.56 1477.03 1636.53 0.00 0.00
Minimum of Months 1510.98 1207.05 1793.80 569.86 644.50 0.00 0.00
Maximum of Months 5704.39 3068.51 4646.17 2721.81 2347.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 318.59 2112.79 604.98 199.89 405.09 0.00 0.00
February 775.42 2063.24 1071.15 452.27 618.88 0.00 0.00
March 490.25 1751.34 968.55 185.28 783.27 0.00 0.00
April 2228.83 1439.92 2285.33 907.75 1377.58 0.00 0.00
May 2659.17 1148.69 2681.22 1090.28 1590.94 0.00 0.00
June 3115.56 928.81 2895.43 1191.94 1703.49 0.00 0.00
July 3298.83 891.65 2948.87 1300.16 1648.70 0.00 0.00
August 2787.31 991.89 2476.85 1072.41 1404.45 0.00 0.00
September 2155.44 1176.04 1987.09 891.06 1096.04 0.00 0.00
October 855.47 1637.67 1060.04 381.19 678.85 0.00 0.00
November 298.54 2064.81 573.66 167.46 406.20 0.00 0.00
December 91.07 2545.21 324.71 68.52 256.19 0.00 0.00
               
Annual Sum or Average 1592.29 1560.32 1658.25 659.29 998.96 0.00 0.00
Minimum of Months 91.07 891.65 324.71 68.52 256.19 0.00 0.00
Maximum of Months 3298.83 2545.21 2948.87 1300.16 1703.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 30.28 2770.27 456.56 0.00 456.56 0.00 0.00
February 101.01 2591.35 712.93 0.00 712.93 0.00 0.00
March 312.59 2177.34 986.57 0.00 986.57 0.00 0.00
April 998.94 1775.56 1606.29 7.19 1599.10 0.00 0.00
May 1277.90 1412.00 2008.27 96.89 1911.38 0.00 0.00
June 1828.84 1116.55 2220.02 139.21 2080.81 0.00 0.00
July 1859.74 1027.34 2105.81 120.06 1985.74 0.00 0.00
August 1430.27 1148.82 1655.27 25.93 1629.34 0.00 0.00
September 935.09 1530.35 1259.89 0.28 1259.61 0.00 0.00
October 327.55 2024.24 807.33 0.00 807.33 0.00 0.00
November 50.42 2445.11 485.08 0.00 485.08 0.00 0.00
December 2.28 2928.64 330.34 0.00 330.34 0.00 0.00
               
Annual Sum or Average 766.26 1908.86 1221.80 32.68 1189.11 0.00 0.00
Minimum of Months 2.28 1027.34 330.34 0.00 330.34 0.00 0.00
Maximum of Months 1859.74 2928.64 2220.02 139.21 2080.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 352.58 1756.79 622.12 249.91 372.21 0.00 0.00
February 583.68 1668.04 927.69 342.69 584.99 0.00 0.00
March 558.00 1398.81 969.45 191.04 778.41 0.00 0.00
April 2665.97 1155.22 2603.06 1223.20 1379.87 0.00 0.00
May 2728.77 985.85 2737.04 1193.58 1543.46 0.00 0.00
June 2887.29 772.61 2709.17 1082.02 1627.15 0.00 0.00
July 3078.00 716.00 2765.53 1175.35 1590.18 0.00 0.00
August 3005.02 780.63 2619.73 1251.68 1368.05 0.00 0.00
September 2609.32 998.24 2359.16 1254.49 1104.67 0.00 0.00
October 978.20 1327.38 1138.80 471.95 666.85 0.00 0.00
November 331.62 1576.17 593.69 202.34 391.35 0.00 0.00
December 221.35 1870.49 440.00 163.58 276.41 0.00 0.00
               
Annual Sum or Average 1670.54 1248.46 1709.59 734.43 975.16 0.00 0.00
Minimum of Months 221.35 716.00 440.00 163.58 276.41 0.00 0.00
Maximum of Months 3078.00 1870.49 2765.53 1254.49 1627.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2517.74 2588.23 2592.02 1677.92 914.10 0.00 0.00
February 3158.31 2551.11 3165.67 1931.74 1233.94 0.00 0.00
March 1533.65 2153.03 1957.23 569.86 1387.37 0.00 0.00
April 4555.38 1895.37 4064.34 1837.03 2227.31 0.00 0.00
May 3477.70 1621.07 3361.59 1094.42 2267.16 0.00 0.00
June 3343.08 1249.65 3096.74 749.59 2347.15 0.00 0.00
July 3905.81 1163.29 3355.26 1050.74 2304.52 0.00 0.00
August 4852.67 1276.30 3931.63 1768.59 2163.04 0.00 0.00
September 5674.63 1625.43 4646.16 2721.80 1924.36 0.00 0.00
October 3466.92 2066.23 3192.10 1865.64 1326.46 0.00 0.00
November 2212.71 2405.66 2263.20 1376.76 886.44 0.00 0.00
December 1701.31 2829.54 1793.79 1149.29 644.50 0.00 0.00
               
Annual Sum or Average 3362.02 1948.88 3113.54 1477.03 1636.52 0.00 0.00
Minimum of Months 1533.65 1163.29 1793.79 569.86 644.50 0.00 0.00
Maximum of Months 5674.63 2829.54 4646.16 2721.80 2347.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 349.10 1828.75 604.98 199.89 405.09 0.00 0.00
February 822.94 1763.06 1071.15 452.27 618.87 0.00 0.00
March 552.51 1459.79 968.55 185.28 783.26 0.00 0.00
April 2288.96 1259.61 2285.32 907.75 1377.57 0.00 0.00
May 2677.83 1071.72 2681.21 1090.27 1590.94 0.00 0.00
June 3135.38 849.86 2895.42 1191.93 1703.48 0.00 0.00
July 3337.96 794.83 2948.86 1300.16 1648.70 0.00 0.00
August 2831.51 869.02 2476.84 1072.40 1404.44 0.00 0.00
September 2177.92 1090.21 1987.09 891.05 1096.03 0.00 0.00
October 901.14 1404.10 1060.03 381.18 678.85 0.00 0.00
November 335.36 1668.58 573.65 167.46 406.20 0.00 0.00
December 113.75 1995.02 324.70 68.52 256.19 0.00 0.00
               
Annual Sum or Average 1629.72 1335.71 1658.24 659.28 998.95 0.00 0.00
Minimum of Months 113.75 794.83 324.70 68.52 256.19 0.00 0.00
Maximum of Months 3337.96 1995.02 2948.86 1300.16 1703.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 48.39 2519.80 456.56 0.00 456.56 0.00 0.00
February 142.55 2353.66 712.93 0.00 712.93 0.00 0.00
March 369.25 1979.70 986.57 0.00 986.57 0.00 0.00
April 1041.30 1664.94 1606.29 7.19 1599.10 0.00 0.00
May 1329.51 1330.53 2008.27 96.89 1911.38 0.00 0.00
June 1844.50 1076.30 2220.02 139.21 2080.81 0.00 0.00
July 1871.21 993.91 2105.81 120.06 1985.74 0.00 0.00
August 1441.78 1107.63 1655.27 25.93 1629.34 0.00 0.00
September 969.85 1438.33 1259.89 0.28 1259.61 0.00 0.00
October 382.31 1813.34 807.33 0.00 807.33 0.00 0.00
November 75.15 2191.00 485.08 0.00 485.08 0.00 0.00
December 9.95 2689.86 330.34 0.00 330.34 0.00 0.00
               
Annual Sum or Average 797.10 1760.27 1221.80 32.68 1189.11 0.00 0.00
Minimum of Months 9.95 993.91 330.34 0.00 330.34 0.00 0.00
Maximum of Months 1871.21 2689.86 2220.02 139.21 2080.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 381.62 1592.18 622.12 249.91 372.21 0.00 0.00
February 627.83 1510.17 927.69 342.69 584.99 0.00 0.00
March 611.20 1269.18 969.45 191.04 778.41 0.00 0.00
April 2692.99 1093.22 2603.06 1223.20 1379.87 0.00 0.00
May 2754.76 936.71 2737.04 1193.58 1543.46 0.00 0.00
June 2896.44 747.83 2709.17 1082.02 1627.15 0.00 0.00
July 3084.34 695.17 2765.53 1175.35 1590.18 0.00 0.00
August 3011.88 756.95 2619.73 1251.68 1368.05 0.00 0.00
September 2630.71 948.16 2359.16 1254.49 1104.67 0.00 0.00
October 1019.94 1193.08 1138.80 471.95 666.85 0.00 0.00
November 362.33 1407.50 593.69 202.34 391.35 0.00 0.00
December 239.27 1717.37 440.00 163.58 276.41 0.00 0.00
               
Annual Sum or Average 1696.57 1153.88 1709.59 734.43 975.16 0.00 0.00
Minimum of Months 239.27 695.17 440.00 163.58 276.41 0.00 0.00
Maximum of Months 3084.34 1717.37 2765.53 1254.49 1627.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2577.29 2353.12 2592.02 1677.92 914.10 0.00 0.00
February 3222.87 2328.41 3165.67 1931.74 1233.94 0.00 0.00
March 1598.21 1962.33 1957.23 569.86 1387.37 0.00 0.00
April 4581.76 1794.26 4064.34 1837.03 2227.31 0.00 0.00
May 3505.47 1534.87 3361.59 1094.42 2267.16 0.00 0.00
June 3350.70 1205.42 3096.74 749.59 2347.15 0.00 0.00
July 3908.65 1125.34 3355.26 1050.74 2304.52 0.00 0.00
August 4852.39 1234.60 3931.63 1768.59 2163.04 0.00 0.00
September 5691.93 1545.04 4646.16 2721.80 1924.36 0.00 0.00
October 3516.21 1872.32 3192.10 1865.64 1326.46 0.00 0.00
November 2260.80 2163.36 2263.20 1376.76 886.44 0.00 0.00
December 1740.59 2596.83 1793.79 1149.29 644.50 0.00 0.00
               
Annual Sum or Average 3395.78 1806.85 3113.54 1477.03 1636.52 0.00 0.00
Minimum of Months 1598.21 1125.34 1793.79 569.86 644.50 0.00 0.00
Maximum of Months 5691.93 2596.83 4646.16 2721.80 2347.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 369.19 1682.06 604.98 199.89 405.09 0.00 0.00
February 849.85 1630.55 1071.15 452.27 618.87 0.00 0.00
March 586.68 1346.68 968.55 185.28 783.26 0.00 0.00
April 2306.82 1197.05 2285.32 907.75 1377.57 0.00 0.00
May 2692.92 1021.47 2681.21 1090.27 1590.94 0.00 0.00
June 3133.37 822.57 2895.42 1191.93 1703.48 0.00 0.00
July 3333.99 771.10 2948.86 1300.16 1648.70 0.00 0.00
August 2828.42 842.55 2476.84 1072.40 1404.44 0.00 0.00
September 2190.72 1038.19 1987.09 891.05 1096.03 0.00 0.00
October 930.09 1285.92 1060.03 381.18 678.85 0.00 0.00
November 353.60 1522.60 573.65 167.46 406.20 0.00 0.00
December 122.38 1858.08 324.70 68.52 256.19 0.00 0.00
               
Annual Sum or Average 1644.12 1249.62 1658.24 659.28 998.95 0.00 0.00
Minimum of Months 122.38 771.10 324.70 68.52 256.19 0.00 0.00
Maximum of Months 3333.99 1858.08 2948.86 1300.16 1703.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 38024889.17 0.842105E+10 0.122284E+10 0.00 0.122284E+10 0.00 0.00
February 0.134269E+09 0.711946E+10 0.172473E+10 0.00 0.172473E+10 0.00 0.00
March 0.655232E+09 0.661138E+10 0.264244E+10 0.00 0.264244E+10 0.00 0.00
April 0.244588E+10 0.502909E+10 0.416352E+10 18634162.82 0.414488E+10 0.00 0.00
May 0.330235E+10 0.402142E+10 0.537897E+10 0.259510E+09 0.511947E+10 0.00 0.00
June 0.468125E+10 0.305239E+10 0.575431E+10 0.360832E+09 0.539348E+10 0.00 0.00
July 0.487158E+10 0.293249E+10 0.564022E+10 0.321579E+09 0.531864E+10 0.00 0.00
August 0.372275E+10 0.331255E+10 0.443350E+10 69461937.96 0.436404E+10 0.00 0.00
September 0.232424E+10 0.424480E+10 0.326565E+10 722621.98 0.326492E+10 0.00 0.00
October 0.729138E+09 0.611338E+10 0.216236E+10 0.00 0.216236E+10 0.00 0.00
November 62229962.58 0.743906E+10 0.125734E+10 0.00 0.125734E+10 0.00 0.00
December 37053.45 0.929789E+10 0.884790E+09 0.00 0.884790E+09 0.00 0.00
               
Annual Sum or Average 0.229670E+11 0.675950E+11 0.385307E+11 0.103074E+10 0.374999E+11 0.00 0.00
Minimum of Months 37053.45 0.293249E+10 0.884790E+09 0.00 0.884790E+09 0.00 0.00
Maximum of Months 0.487158E+10 0.929789E+10 0.575431E+10 0.360832E+09 0.539348E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.882205E+09 0.521987E+10 0.166629E+10 0.669352E+09 0.996939E+09 0.00 0.00
February 0.134573E+10 0.442354E+10 0.224427E+10 0.829051E+09 0.141522E+10 0.00 0.00
March 0.141243E+10 0.408085E+10 0.259660E+10 0.511694E+09 0.208490E+10 0.00 0.00
April 0.693167E+10 0.311070E+10 0.674717E+10 0.317054E+10 0.357663E+10 0.00 0.00
May 0.735201E+10 0.273738E+10 0.733092E+10 0.319689E+10 0.413403E+10 0.00 0.00
June 0.753799E+10 0.205857E+10 0.702219E+10 0.280459E+10 0.421760E+10 0.00 0.00
July 0.829933E+10 0.197020E+10 0.740721E+10 0.314806E+10 0.425915E+10 0.00 0.00
August 0.809972E+10 0.213991E+10 0.701672E+10 0.335252E+10 0.366420E+10 0.00 0.00
September 0.680057E+10 0.267292E+10 0.611496E+10 0.325166E+10 0.286330E+10 0.00 0.00
October 0.258046E+10 0.385429E+10 0.305016E+10 0.126407E+10 0.178610E+10 0.00 0.00
November 0.803871E+09 0.459926E+10 0.153885E+10 0.524461E+09 0.101439E+10 0.00 0.00
December 0.532136E+09 0.569627E+10 0.117849E+10 0.438145E+09 0.740343E+09 0.00 0.00
               
Annual Sum or Average 0.525781E+11 0.425638E+11 0.539138E+11 0.231610E+11 0.307528E+11 0.00 0.00
Minimum of Months 0.532136E+09 0.197020E+10 0.117849E+10 0.438145E+09 0.740343E+09 0.00 0.00
Maximum of Months 0.829933E+10 0.569627E+10 0.740721E+10 0.335252E+10 0.425915E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.671359E+10 0.722459E+10 0.694248E+10 0.449415E+10 0.244833E+10 0.00 0.00
February 0.762665E+10 0.640501E+10 0.765842E+10 0.467327E+10 0.298515E+10 0.00 0.00
March 0.404700E+10 0.608813E+10 0.524225E+10 0.152631E+10 0.371595E+10 0.00 0.00
April 0.118317E+11 0.508374E+10 0.105348E+11 0.476161E+10 0.577320E+10 0.00 0.00
May 0.935370E+10 0.445041E+10 0.900371E+10 0.293131E+10 0.607239E+10 0.00 0.00
June 0.868545E+10 0.334220E+10 0.802678E+10 0.194295E+10 0.608383E+10 0.00 0.00
July 0.104706E+11 0.323297E+10 0.898676E+10 0.281430E+10 0.617245E+10 0.00 0.00
August 0.130269E+11 0.353653E+10 0.105305E+11 0.473701E+10 0.579350E+10 0.00 0.00
September 0.147858E+11 0.427405E+10 0.120429E+11 0.705492E+10 0.498796E+10 0.00 0.00
October 0.929501E+10 0.575707E+10 0.854976E+10 0.499695E+10 0.355281E+10 0.00 0.00
November 0.570037E+10 0.665045E+10 0.586623E+10 0.356858E+10 0.229765E+10 0.00 0.00
December 0.447900E+10 0.821869E+10 0.480451E+10 0.307827E+10 0.172624E+10 0.00 0.00
               
Annual Sum or Average 0.106016E+12 0.642638E+11 0.981891E+11 0.465796E+11 0.516095E+11 0.00 0.00
Minimum of Months 0.404700E+10 0.323297E+10 0.480451E+10 0.152631E+10 0.172624E+10 0.00 0.00
Maximum of Months 0.147858E+11 0.821869E+10 0.120429E+11 0.705492E+10 0.617245E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.853320E+09 0.565890E+10 0.162039E+10 0.535382E+09 0.108500E+10 0.00 0.00
February 0.187590E+10 0.499139E+10 0.259133E+10 0.109414E+10 0.149719E+10 0.00 0.00
March 0.131309E+10 0.469080E+10 0.259417E+10 0.496264E+09 0.209790E+10 0.00 0.00
April 0.577712E+10 0.373228E+10 0.592358E+10 0.235290E+10 0.357068E+10 0.00 0.00
May 0.712231E+10 0.307665E+10 0.718138E+10 0.292020E+10 0.426118E+10 0.00 0.00
June 0.807552E+10 0.240748E+10 0.750496E+10 0.308950E+10 0.441545E+10 0.00 0.00
July 0.883560E+10 0.238820E+10 0.789825E+10 0.348236E+10 0.441589E+10 0.00 0.00
August 0.746554E+10 0.265669E+10 0.663400E+10 0.287234E+10 0.376167E+10 0.00 0.00
September 0.558691E+10 0.304830E+10 0.515055E+10 0.230962E+10 0.284093E+10 0.00 0.00
October 0.229130E+10 0.438633E+10 0.283921E+10 0.102097E+10 0.181824E+10 0.00 0.00
November 0.773828E+09 0.535199E+10 0.148692E+10 0.434049E+09 0.105287E+10 0.00 0.00
December 0.243931E+09 0.681709E+10 0.869693E+09 0.183524E+09 0.686169E+09 0.00 0.00
               
Annual Sum or Average 0.502144E+11 0.492061E+11 0.522944E+11 0.207912E+11 0.315032E+11 0.00 0.00
Minimum of Months 0.243931E+09 0.238820E+10 0.869693E+09 0.183524E+09 0.686169E+09 0.00 0.00
Maximum of Months 0.883560E+10 0.681709E+10 0.789825E+10 0.348236E+10 0.441589E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 81111456.43 0.741988E+10 0.122284E+10 0.00 0.122284E+10 0.00 0.00
February 0.244370E+09 0.626898E+10 0.172472E+10 0.00 0.172472E+10 0.00 0.00
March 0.837237E+09 0.583178E+10 0.264243E+10 0.00 0.264243E+10 0.00 0.00
April 0.258925E+10 0.460226E+10 0.416350E+10 18634096.65 0.414487E+10 0.00 0.00
May 0.342274E+10 0.378190E+10 0.537895E+10 0.259509E+09 0.511945E+10 0.00 0.00
June 0.474034E+10 0.289411E+10 0.575429E+10 0.360831E+09 0.539346E+10 0.00 0.00
July 0.498113E+10 0.275163E+10 0.564019E+10 0.321577E+09 0.531862E+10 0.00 0.00
August 0.383083E+10 0.307700E+10 0.443348E+10 69461691.30 0.436402E+10 0.00 0.00
September 0.242374E+10 0.396666E+10 0.326564E+10 722619.41 0.326491E+10 0.00 0.00
October 0.877308E+09 0.542172E+10 0.216235E+10 0.00 0.216235E+10 0.00 0.00
November 0.130677E+09 0.633773E+10 0.125734E+10 0.00 0.125734E+10 0.00 0.00
December 6111285.81 0.784408E+10 0.884787E+09 0.00 0.884787E+09 0.00 0.00
               
Annual Sum or Average 0.241649E+11 0.601977E+11 0.385305E+11 0.103074E+10 0.374998E+11 0.00 0.00
Minimum of Months 6111285.81 0.275163E+10 0.884787E+09 0.00 0.884787E+09 0.00 0.00
Maximum of Months 0.498113E+10 0.784408E+10 0.575429E+10 0.360831E+09 0.539346E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.944357E+09 0.470538E+10 0.166628E+10 0.669349E+09 0.996935E+09 0.00 0.00
February 0.141203E+10 0.403532E+10 0.224426E+10 0.829047E+09 0.141522E+10 0.00 0.00
March 0.149455E+10 0.374656E+10 0.259659E+10 0.511692E+09 0.208489E+10 0.00 0.00
April 0.691019E+10 0.299432E+10 0.674714E+10 0.317053E+10 0.357661E+10 0.00 0.00
May 0.730873E+10 0.264050E+10 0.733089E+10 0.319687E+10 0.413401E+10 0.00 0.00
June 0.748385E+10 0.200261E+10 0.702217E+10 0.280458E+10 0.421758E+10 0.00 0.00
July 0.824411E+10 0.191773E+10 0.740718E+10 0.314805E+10 0.425913E+10 0.00 0.00
August 0.804866E+10 0.209083E+10 0.701669E+10 0.335251E+10 0.366418E+10 0.00 0.00
September 0.676336E+10 0.258743E+10 0.611494E+10 0.325164E+10 0.286329E+10 0.00 0.00
October 0.262001E+10 0.355524E+10 0.305015E+10 0.126406E+10 0.178609E+10 0.00 0.00
November 0.859570E+09 0.408544E+10 0.153884E+10 0.524459E+09 0.101438E+10 0.00 0.00
December 0.592857E+09 0.500992E+10 0.117848E+10 0.438144E+09 0.740340E+09 0.00 0.00
               
Annual Sum or Average 0.526823E+11 0.393713E+11 0.539136E+11 0.231609E+11 0.307527E+11 0.00 0.00
Minimum of Months 0.592857E+09 0.191773E+10 0.117848E+10 0.438144E+09 0.740340E+09 0.00 0.00
Maximum of Months 0.824411E+10 0.500992E+10 0.740718E+10 0.335251E+10 0.425913E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.674350E+10 0.693232E+10 0.694246E+10 0.449414E+10 0.244832E+10 0.00 0.00
February 0.764059E+10 0.617165E+10 0.765839E+10 0.467326E+10 0.298514E+10 0.00 0.00
March 0.410772E+10 0.576667E+10 0.524223E+10 0.152630E+10 0.371593E+10 0.00 0.00
April 0.118075E+11 0.491279E+10 0.105348E+11 0.476159E+10 0.577318E+10 0.00 0.00
May 0.931468E+10 0.434188E+10 0.900367E+10 0.293130E+10 0.607237E+10 0.00 0.00
June 0.866526E+10 0.323910E+10 0.802675E+10 0.194294E+10 0.608381E+10 0.00 0.00
July 0.104613E+11 0.311575E+10 0.898673E+10 0.281429E+10 0.617243E+10 0.00 0.00
August 0.129974E+11 0.341844E+10 0.105305E+11 0.473700E+10 0.579347E+10 0.00 0.00
September 0.147086E+11 0.421311E+10 0.120428E+11 0.705490E+10 0.498794E+10 0.00 0.00
October 0.928581E+10 0.553418E+10 0.854973E+10 0.499693E+10 0.355280E+10 0.00 0.00
November 0.573534E+10 0.623546E+10 0.586621E+10 0.356857E+10 0.229765E+10 0.00 0.00
December 0.455679E+10 0.757864E+10 0.480450E+10 0.307826E+10 0.172623E+10 0.00 0.00
               
Annual Sum or Average 0.106025E+12 0.614600E+11 0.981887E+11 0.465795E+11 0.516093E+11 0.00 0.00
Minimum of Months 0.410772E+10 0.311575E+10 0.480450E+10 0.152630E+10 0.172623E+10 0.00 0.00
Maximum of Months 0.147086E+11 0.757864E+10 0.120428E+11 0.705490E+10 0.617243E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.935021E+09 0.489813E+10 0.162038E+10 0.535380E+09 0.108500E+10 0.00 0.00
February 0.199086E+10 0.426518E+10 0.259132E+10 0.109414E+10 0.149718E+10 0.00 0.00
March 0.147985E+10 0.390991E+10 0.259416E+10 0.496262E+09 0.209790E+10 0.00 0.00
April 0.593298E+10 0.326491E+10 0.592355E+10 0.235289E+10 0.357067E+10 0.00 0.00
May 0.717231E+10 0.287051E+10 0.718135E+10 0.292019E+10 0.426117E+10 0.00 0.00
June 0.812690E+10 0.220283E+10 0.750492E+10 0.308949E+10 0.441543E+10 0.00 0.00
July 0.894038E+10 0.212888E+10 0.789822E+10 0.348235E+10 0.441587E+10 0.00 0.00
August 0.758392E+10 0.232759E+10 0.663398E+10 0.287233E+10 0.376165E+10 0.00 0.00
September 0.564516E+10 0.282581E+10 0.515053E+10 0.230961E+10 0.284091E+10 0.00 0.00
October 0.241361E+10 0.376075E+10 0.283919E+10 0.102096E+10 0.181823E+10 0.00 0.00
November 0.869255E+09 0.432495E+10 0.148691E+10 0.434048E+09 0.105286E+10 0.00 0.00
December 0.304661E+09 0.534347E+10 0.869689E+09 0.183523E+09 0.686166E+09 0.00 0.00
               
Annual Sum or Average 0.513949E+11 0.421229E+11 0.522942E+11 0.207912E+11 0.315030E+11 0.00 0.00
Minimum of Months 0.304661E+09 0.212888E+10 0.869689E+09 0.183523E+09 0.686166E+09 0.00 0.00
Maximum of Months 0.894038E+10 0.534347E+10 0.789822E+10 0.348235E+10 0.441587E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.129606E+09 0.674904E+10 0.122284E+10 0.00 0.122284E+10 0.00 0.00
February 0.344861E+09 0.569398E+10 0.172472E+10 0.00 0.172472E+10 0.00 0.00
March 0.989009E+09 0.530242E+10 0.264243E+10 0.00 0.264243E+10 0.00 0.00
April 0.269904E+10 0.431554E+10 0.416350E+10 18634096.65 0.414487E+10 0.00 0.00
May 0.356096E+10 0.356370E+10 0.537895E+10 0.259509E+09 0.511945E+10 0.00 0.00
June 0.478095E+10 0.278978E+10 0.575429E+10 0.360831E+09 0.539346E+10 0.00 0.00
July 0.501185E+10 0.266210E+10 0.564019E+10 0.321577E+09 0.531862E+10 0.00 0.00
August 0.386165E+10 0.296668E+10 0.443348E+10 69461691.30 0.436402E+10 0.00 0.00
September 0.251385E+10 0.372814E+10 0.326564E+10 722619.41 0.326491E+10 0.00 0.00
October 0.102398E+10 0.485685E+10 0.216235E+10 0.00 0.216235E+10 0.00 0.00
November 0.194783E+09 0.567906E+10 0.125734E+10 0.00 0.125734E+10 0.00 0.00
December 26646718.63 0.720451E+10 0.884787E+09 0.00 0.884787E+09 0.00 0.00
               
Annual Sum or Average 0.251372E+11 0.555118E+11 0.385305E+11 0.103074E+10 0.374998E+11 0.00 0.00
Minimum of Months 26646718.63 0.266210E+10 0.884787E+09 0.00 0.884787E+09 0.00 0.00
Maximum of Months 0.501185E+10 0.720451E+10 0.575429E+10 0.360831E+09 0.539346E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.102213E+10 0.426450E+10 0.166628E+10 0.669349E+09 0.996935E+09 0.00 0.00
February 0.151885E+10 0.365340E+10 0.224426E+10 0.829047E+09 0.141522E+10 0.00 0.00
March 0.163704E+10 0.339936E+10 0.259659E+10 0.511692E+09 0.208489E+10 0.00 0.00
April 0.698023E+10 0.283362E+10 0.674714E+10 0.317053E+10 0.357661E+10 0.00 0.00
May 0.737836E+10 0.250888E+10 0.733089E+10 0.319687E+10 0.413401E+10 0.00 0.00
June 0.750757E+10 0.193838E+10 0.702217E+10 0.280458E+10 0.421758E+10 0.00 0.00
July 0.826109E+10 0.186194E+10 0.740718E+10 0.314805E+10 0.425913E+10 0.00 0.00
August 0.806702E+10 0.202742E+10 0.701669E+10 0.335251E+10 0.366418E+10 0.00 0.00
September 0.681881E+10 0.245764E+10 0.611494E+10 0.325164E+10 0.286329E+10 0.00 0.00
October 0.273180E+10 0.319553E+10 0.305015E+10 0.126406E+10 0.178609E+10 0.00 0.00
November 0.939156E+09 0.364824E+10 0.153884E+10 0.524459E+09 0.101438E+10 0.00 0.00
December 0.640856E+09 0.459980E+10 0.117848E+10 0.438144E+09 0.740340E+09 0.00 0.00
               
Annual Sum or Average 0.535029E+11 0.363887E+11 0.539136E+11 0.231609E+11 0.307527E+11 0.00 0.00
Minimum of Months 0.640856E+09 0.186194E+10 0.117848E+10 0.438144E+09 0.740340E+09 0.00 0.00
Maximum of Months 0.826109E+10 0.459980E+10 0.740718E+10 0.335251E+10 0.425913E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.690302E+10 0.630260E+10 0.694246E+10 0.449414E+10 0.244832E+10 0.00 0.00
February 0.779676E+10 0.563290E+10 0.765839E+10 0.467326E+10 0.298514E+10 0.00 0.00
March 0.428064E+10 0.525591E+10 0.524223E+10 0.152630E+10 0.371593E+10 0.00 0.00
April 0.118759E+11 0.465073E+10 0.105348E+11 0.476159E+10 0.577318E+10 0.00 0.00
May 0.938905E+10 0.411099E+10 0.900367E+10 0.293130E+10 0.607237E+10 0.00 0.00
June 0.868500E+10 0.312446E+10 0.802675E+10 0.194294E+10 0.608381E+10 0.00 0.00
July 0.104689E+11 0.301411E+10 0.898673E+10 0.281429E+10 0.617243E+10 0.00 0.00
August 0.129966E+11 0.330675E+10 0.105305E+11 0.473700E+10 0.579347E+10 0.00 0.00
September 0.147535E+11 0.400473E+10 0.120428E+11 0.705490E+10 0.498794E+10 0.00 0.00
October 0.941782E+10 0.501482E+10 0.854973E+10 0.499693E+10 0.355280E+10 0.00 0.00
November 0.586000E+10 0.560744E+10 0.586621E+10 0.356857E+10 0.229765E+10 0.00 0.00
December 0.466200E+10 0.695534E+10 0.480450E+10 0.307826E+10 0.172623E+10 0.00 0.00
               
Annual Sum or Average 0.107089E+12 0.569808E+11 0.981887E+11 0.465795E+11 0.516093E+11 0.00 0.00
Minimum of Months 0.428064E+10 0.301411E+10 0.480450E+10 0.152630E+10 0.172623E+10 0.00 0.00
Maximum of Months 0.147535E+11 0.695534E+10 0.120428E+11 0.705490E+10 0.617243E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.988852E+09 0.450524E+10 0.162038E+10 0.535380E+09 0.108500E+10 0.00 0.00
February 0.205597E+10 0.394462E+10 0.259132E+10 0.109414E+10 0.149718E+10 0.00 0.00
March 0.157136E+10 0.360696E+10 0.259416E+10 0.496262E+09 0.209790E+10 0.00 0.00
April 0.597927E+10 0.310275E+10 0.592355E+10 0.235289E+10 0.357067E+10 0.00 0.00
May 0.721271E+10 0.273591E+10 0.718135E+10 0.292019E+10 0.426117E+10 0.00 0.00
June 0.812170E+10 0.213210E+10 0.750492E+10 0.308949E+10 0.441543E+10 0.00 0.00
July 0.892976E+10 0.206531E+10 0.789822E+10 0.348235E+10 0.441587E+10 0.00 0.00
August 0.757564E+10 0.225670E+10 0.663398E+10 0.287233E+10 0.376165E+10 0.00 0.00
September 0.567834E+10 0.269100E+10 0.515053E+10 0.230961E+10 0.284091E+10 0.00 0.00
October 0.249116E+10 0.344420E+10 0.283919E+10 0.102096E+10 0.181823E+10 0.00 0.00
November 0.916525E+09 0.394658E+10 0.148691E+10 0.434048E+09 0.105286E+10 0.00 0.00
December 0.327787E+09 0.497669E+10 0.869689E+09 0.183523E+09 0.686166E+09 0.00 0.00
               
Annual Sum or Average 0.518491E+11 0.394081E+11 0.522942E+11 0.207912E+11 0.315030E+11 0.00 0.00
Minimum of Months 0.327787E+09 0.206531E+10 0.869689E+09 0.183523E+09 0.686166E+09 0.00 0.00
Maximum of Months 0.892976E+10 0.497669E+10 0.789822E+10 0.348235E+10 0.441587E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.18 3.23 2.03 1.05 -4.0 28.28 62.93 0.00
February 4.25 3.55 2.74 1.60 -5.0 43.80 86.73 0.02
March 5.90 4.45 2.76 1.18 -1.9 68.95 35.00 0.00
April 8.96 6.24 3.38 1.56 -0.7 96.13 186.12 0.00
May 9.99 8.07 6.28 3.35 -0.9 110.92 199.68 0.02
June 13.31 11.27 9.70 3.33 3.35 121.69 199.28 0.00
July 15.02 12.39 10.49 3.21 4.49 111.91 220.83 0.00
August 15.65 12.75 10.65 2.92 3.95 91.47 211.91 0.00
September 13.43 11.01 9.10 2.64 1.43 68.72 198.32 0.01
October 9.33 8.03 6.81 1.97 -1.0 48.92 91.86 0.04
November 6.66 5.66 4.54 2.05 -2.3 30.27 53.24 0.04
December 4.10 3.14 1.95 2.36 -5.1 20.52 40.74 0.04
                 
Annual Sum or Average 9.26 7.50 5.89 2.27 -0.6 70.25 132.30 0.02
Minimum of Months 4.10 3.14 1.95 1.05 -5.1 20.52 35.00 0.00
Maximum of Months 15.65 12.75 10.65 3.35 4.49 121.69 220.83 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 29-JAN-05:00 9.37 5.00 3.60 8.35 0.00 0.00
February 11.00 07-FEB-14:00 9.86 9.00 2.10 6.35 138.00 225.00
March 14.00 25-MAR-12:00 11.22 9.00 2.60 7.35 287.00 93.00
April 24.00 30-APR-14:00 13.13 4.00 1.50 7.75 167.50 716.00
May 24.00 22-MAY-14:00 16.08 11.00 2.60 9.33 159.00 769.00
June 27.00 13-JUN-16:00 17.53 12.00 3.10 12.41 141.50 652.50
July 30.00 22-JUL-17:00 16.80 8.00 0.00 14.28 122.00 407.00
August 27.00 14-AUG-17:19 14.18 3.33 2.60 10.37 133.00 358.83
September 23.00 11-SEP-16:00 16.22 12.00 2.60 8.74 108.00 325.50
October 19.00 07-OCT-14:00 10.10 1.00 1.50 2.22 131.00 540.50
November 16.00 24-NOV-11:00 12.01 9.00 4.10 9.33 61.50 0.00
December 13.00 23-DEC-10:00 7.64 2.00 7.70 6.75 70.50 0.00
                 
Annual Sum or Average                
Minimum of Months 11.00   7.64 1.00 0.00 2.22 0.00 0.00
Maximum of Months 30.00   17.53 12.00 7.70 14.28 287.00 769.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.0 10-JAN-07:00 -7.0 -9.0 0.00 -20.0 0.00 0.00
February -4.0 17-FEB-06:00 -4.0 -4.0 0.00 -20.5 0.00 0.00
March -1.0 08-MAR-06:00 -1.4 -2.0 0.00 -14.4 17.50 184.50
April 0.00 08-APR-04:00 -0.9 -2.0 0.00 -12.7 0.00 0.00
May 2.00 06-MAY-04:00 1.57 1.00 3.60 -13.7 12.50 117.00
June 6.00 01-JUN-03:00 5.05 4.00 0.00 -9.2 0.00 0.00
July 7.00 05-JUL-04:00 6.47 6.00 3.10 -7.8 28.00 155.00
August 8.00 20-AUG-04:00 7.45 7.00 0.00 -6.6 0.00 0.00
September 5.00 20-SEP-03:00 5.00 5.00 2.60 -10.0 0.00 0.00
October 2.00 07-OCT-03:00 2.00 2.00 0.00 -13.4 0.00 0.00
November -2.0 29-NOV-01:00 -2.0 -2.0 3.10 -10.7 0.00 0.00
December -3.0 29-DEC-20:00 -4.5 -7.0 3.60 -20.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -6.0   -7.0 -9.0 0.00 -20.5 0.00 0.00
Maximum of Months 8.00   7.45 7.00 3.60 -6.6 28.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.44 29-JAN-04:00 13.00 12.00 0.00 9.13 0.00 0.00
February 9.86 07-FEB-14:00 11.00 9.00 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.39 28-APR-07:00 16.00 15.00 0.00 5.54 119.50 626.00
May 16.08 22-MAY-14:00 24.00 11.00 2.60 9.33 159.00 769.00
June 19.93 25-JUN-17:00 22.00 19.00 0.00 15.94 136.50 360.50
July 17.31 22-JUL-09:00 26.00 12.00 4.60 11.46 224.50 619.50
August 17.06 14-AUG-12:00 24.00 13.00 2.60 9.91 205.50 669.50
September 16.54 10-SEP-15:00 21.00 14.00 3.60 8.54 160.50 483.00
October 13.58 17-OCT-14:00 16.00 12.00 0.00 12.03 144.00 44.50
November 12.01 24-NOV-11:00 16.00 9.00 4.10 9.33 61.50 0.00
December 7.93 02-DEC-12:00 9.00 7.00 0.00 2.01 135.50 84.00
                 
Annual Sum or Average                
Minimum of Months 7.93   9.00 7.00 0.00 2.01 0.00 0.00
Maximum of Months 19.93   26.00 19.00 4.60 15.94 224.50 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.00 29-JAN-04:00 13.00 12.44 0.00 9.13 0.00 0.00
February 9.00 07-FEB-14:00 11.00 9.86 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.00 28-APR-07:00 16.00 15.39 0.00 5.54 119.50 626.00
May 12.00 23-MAY-07:00 17.00 13.95 3.10 5.13 112.00 719.50
June 19.00 25-JUN-17:00 22.00 19.93 0.00 15.94 136.50 360.50
July 14.00 17-JUL-17:00 18.00 15.45 3.60 9.91 120.00 0.00
August 16.00 08-AUG-12:00 18.00 16.70 1.50 11.46 154.00 0.00
September 14.00 10-SEP-15:00 21.00 16.54 3.60 8.54 160.50 483.00
October 13.00 17-OCT-18:00 13.00 13.00 2.60 9.33 0.00 0.00
November 12.00 08-NOV-14:00 12.00 12.00 0.00 8.15 93.00 106.00
December 7.00 02-DEC-11:00 8.00 7.45 3.10 1.16 144.50 146.50
                 
Annual Sum or Average                
Minimum of Months 7.00   8.00 7.45 0.00 1.16 0.00 0.00
Maximum of Months 19.00   22.00 19.93 3.60 15.94 160.50 719.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.33 8.85 0.00
February 18.00 13.00 16.00 10.00 14.79 0.00
March 18.00 13.00 16.00 10.33 17.09 0.00
April 18.00 13.00 16.00 11.26 40.86 0.00
May 18.00 13.00 16.00 12.54 47.73 0.00
June 18.00 13.00 16.00 13.82 50.98 0.00
July 18.00 13.00 16.00 14.77 51.67 0.00
August 18.00 13.00 16.00 15.12 44.67 0.00
September 18.00 13.00 16.00 14.78 34.25 0.00
October 18.00 13.00 16.00 13.84 17.71 0.00
November 18.00 13.00 16.00 12.55 9.34 0.00
December 18.00 13.00 16.00 11.27 6.14 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.57 28.73 0.00
Minimum of Months 18.00 13.00 16.00 10.00 6.14 0.00
Maximum of Months 18.00 13.00 16.00 15.12 51.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.397423E+11 -0.387131E+11 0.00 0.00 744.00 0.00 -0.102918E+10 58.98 0.00 0.00
February 0.363428E+11 -0.354136E+11 0.00 0.00 672.00 0.00 -929229996.7 58.98 0.00 0.00
March 0.424120E+11 -0.413819E+11 0.00 0.00 744.00 0.00 -0.103012E+10 58.97 0.00 0.00
April 0.377990E+11 -0.368081E+11 0.00 0.00 720.00 0.00 -990906266.9 58.98 0.00 0.00
May 0.392827E+11 -0.382567E+11 0.00 0.00 744.00 0.00 -0.102604E+10 58.97 0.00 0.00
June 0.378901E+11 -0.368968E+11 0.00 0.00 720.00 0.00 -993302564.7 58.98 0.00 0.00
July 0.353635E+11 -0.343429E+11 0.00 0.00 744.00 0.00 -0.102066E+10 58.98 0.00 0.00
August 0.383326E+11 -0.373081E+11 0.00 0.00 744.00 0.00 -0.102447E+10 58.98 0.00 0.00
September 0.350872E+11 -0.340967E+11 0.00 0.00 720.00 0.00 -990586899.4 58.98 0.00 0.00
October 0.369492E+11 -0.359264E+11 0.00 0.00 744.00 0.00 -0.102286E+10 58.97 0.00 0.00
November 0.372392E+11 -0.362484E+11 0.00 0.00 720.00 0.00 -990870069.1 58.98 0.00 0.00
December 0.380864E+11 -0.370603E+11 0.00 0.00 744.00 0.00 -0.102609E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.454527E+12 -0.442453E+12 0.00 0.00 8760.00 0.00 -0.120743E+11 58.98 0.00 0.00
Minimum of Months 0.350872E+11 -0.413819E+11 0.00 0.00 672.00 0.00 -0.103012E+10 58.97 0.00 0.00
Maximum of Months 0.424120E+11 -0.340967E+11 0.00 0.00 744.00 0.00 -929229996.7 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.51 0.48 01-JAN-08:39 3988.50 36.43 191.17 222.00 3311.15 37.56 193.67 194.33
February 217.00 0.50 0.48 01-FEB-11:39 5720.09 36.13 213.67 246.00 2639.36 30.38 199.33 218.50
March 215.50 0.50 0.48 01-MAR-11:39 4231.79 31.40 190.83 310.50 1194.52 22.34 210.50 266.67
April 359.67 0.50 0.48 01-APR-06:00 2680.93 21.22 218.17 355.50 1493.33 22.64 292.50 329.33
May 417.17 0.50 0.48 01-MAY-06:49 2142.01 20.81 197.33 410.33 1188.78 22.22 313.50 373.33
June 410.67 0.49 0.48 01-JUN-05:49 2088.26 21.09 202.83 412.67 1147.62 22.50 318.83 372.00
July 429.00 0.50 0.48 01-JUL-05:40 2081.01 20.86 198.83 421.33 1171.44 22.28 326.83 382.83
August 396.33 0.50 0.48 01-AUG-06:10 2400.65 20.87 193.17 382.33 1365.49 22.29 309.50 348.33
September 337.67 0.50 0.48 01-SEP-07:40 3525.37 22.82 184.83 331.17 1643.85 22.86 271.00 304.17
October 234.00 0.50 0.48 01-OCT-06:49 7236.20 35.35 217.17 279.83 2119.24 25.34 206.33 239.00
November 171.33 0.50 0.48 01-NOV-11:39 4598.84 36.28 167.17 216.67 3796.47 37.46 170.83 173.00
December 131.67 0.49 0.48 02-DEC-08:50 3869.13 37.33 128.67 183.17 3213.09 38.53 128.67 132.67
                         
Annual Sum or Average 3515.67 0.50     3320.64 25.89 2303.83 3771.50 1749.48 25.30 2941.50 3334.17
Minimum of Months 131.67 0.49 0.48   2081.01 20.81 128.67 183.17 1147.62 22.22 128.67 132.67
Maximum of Months 429.00 0.51 0.48   7236.20 37.33 218.17 421.33 3796.47 38.53 326.83 382.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.52 0.48 01-JAN-08:39 1472.24 24.85 88.00 210.33 866.76 24.84 101.67 145.17
February 217.00 0.50 0.48 01-FEB-11:39 1794.87 25.04 93.67 239.33 989.45 25.16 125.00 195.00
March 215.50 0.51 0.48 01-MAR-11:39 2026.10 25.10 98.67 304.67 1065.38 25.33 166.67 252.00
April 359.67 0.50 0.48 01-APR-06:10 3769.30 26.19 167.00 364.67 2168.68 26.44 258.67 339.50
May 417.17 0.49 0.48 01-MAY-06:40 3864.86 25.08 151.67 422.83 1729.00 24.47 253.00 382.33
June 410.67 0.48 0.48 01-JUN-04:49 3897.86 25.61 150.83 420.83 1771.45 25.19 269.83 389.00
July 429.00 0.49 0.48 01-JUL-04:49 3811.42 25.76 167.50 432.00 1724.48 25.24 272.67 401.67
August 396.33 0.50 0.48 01-AUG-05:30 3666.45 25.45 146.83 390.50 1610.98 24.71 267.67 361.17
September 337.67 0.49 0.48 01-SEP-07:40 3470.83 25.86 152.17 338.17 1900.41 25.88 235.83 308.00
October 234.00 0.50 0.48 01-OCT-06:40 2744.86 26.30 118.50 273.83 1233.69 25.12 157.67 215.33
November 171.33 0.51 0.48 01-NOV-11:39 1508.21 24.78 82.33 204.67 854.93 24.85 96.50 136.00
December 131.67 0.50 0.48 02-DEC-08:50 1273.61 25.45 65.33 165.33 875.78 26.77 79.33 99.33
                         
Annual Sum or Average 3515.67 0.50     3132.12 25.52 1482.50 3767.17 1539.71 25.27 2284.50 3224.50
Minimum of Months 131.67 0.48 0.48   1273.61 24.78 65.33 165.33 854.93 24.47 79.33 99.33
Maximum of Months 429.00 0.52 0.48   3897.86 26.30 167.50 432.00 2168.68 26.77 272.67 401.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.55 0.48 01-JAN-09:50 544.38 16.17 0.00 188.17 313.45 17.74 0.00 76.17
February 217.00 0.52 0.48 01-FEB-11:39 722.57 17.88 0.00 224.33 419.43 19.36 15.67 142.50
March 215.50 0.51 0.48 01-MAR-11:39 886.35 18.61 0.17 300.33 478.76 19.87 39.67 220.00
April 359.67 0.50 0.48 01-APR-06:00 1185.48 20.23 27.33 360.83 702.30 21.57 247.00 329.00
May 417.17 0.49 0.48 01-MAY-06:49 1399.79 22.03 132.83 425.50 799.36 23.25 320.17 398.00
June 410.67 0.48 0.48 01-JUN-04:00 1590.43 23.10 160.33 427.83 876.97 23.49 339.00 401.00
July 429.00 0.49 0.48 01-JUL-04:49 1478.74 22.86 170.00 438.83 864.31 24.15 357.33 416.33
August 396.33 0.50 0.48 01-AUG-05:49 1191.45 20.29 57.00 389.83 724.57 21.67 287.17 359.67
September 337.67 0.50 0.48 01-SEP-07:49 974.66 19.63 0.50 326.00 605.35 21.11 161.83 283.67
October 234.00 0.51 0.48 01-OCT-07:30 820.96 18.52 0.00 263.17 487.62 20.00 40.50 178.17
November 171.33 0.54 0.48 01-NOV-11:00 604.12 16.94 0.00 181.67 350.11 18.46 0.00 78.83
December 131.67 0.55 0.48 02-DEC-10:20 511.35 16.42 0.00 134.33 298.01 18.04 0.00 41.33
                         
Annual Sum or Average 3515.67 0.50     1113.99 20.16 548.17 3660.83 647.79 21.43 1808.33 2924.67
Minimum of Months 131.67 0.48 0.48   511.35 16.17 0.00 134.33 298.01 17.74 0.00 41.33
Maximum of Months 429.00 0.55 0.48   1590.43 23.10 170.00 438.83 876.97 24.15 357.33 416.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.53 0.48 01-JAN-09:50 1330.67 24.10 85.17 203.17 756.19 24.12 99.17 145.83
February 217.00 0.51 0.48 01-FEB-11:39 2077.06 24.31 90.83 234.00 1111.10 24.25 124.67 182.33
March 215.50 0.51 0.48 01-MAR-11:39 1911.27 24.00 98.33 303.67 1026.45 24.24 157.67 250.83
April 359.67 0.50 0.48 01-APR-07:49 3607.08 24.06 138.67 355.17 1625.22 23.65 233.83 328.17
May 417.17 0.50 0.48 01-MAY-06:00 3268.84 22.28 94.17 413.33 1801.90 23.13 248.50 383.17
June 410.67 0.49 0.48 01-JUN-05:49 3778.83 21.56 72.33 418.83 1682.64 21.83 246.67 380.33
July 429.00 0.49 0.48 01-JUL-05:40 3753.53 21.46 64.33 428.00 1710.80 21.77 240.50 394.50
August 396.33 0.50 0.48 01-AUG-06:10 3348.90 22.97 115.17 382.83 1856.31 23.59 237.83 350.50
September 337.67 0.50 0.48 01-SEP-07:00 3248.27 24.60 128.67 325.83 1768.38 24.96 204.33 297.50
October 234.00 0.51 0.48 01-OCT-07:30 2583.24 25.52 113.33 269.17 1153.07 24.50 147.83 211.50
November 171.33 0.52 0.48 01-NOV-11:39 1461.89 23.95 76.83 197.50 778.57 23.91 90.67 132.50
December 131.67 0.53 0.48 02-DEC-09:39 1054.55 22.32 46.17 160.83 546.27 22.08 53.33 82.33
                         
Annual Sum or Average 3515.67 0.50     2947.94 23.21 1124.00 3692.33 1473.24 23.38 2085.00 3139.50
Minimum of Months 131.67 0.49 0.48   1054.55 21.46 46.17 160.83 546.27 21.77 53.33 82.33
Maximum of Months 429.00 0.53 0.48   3778.83 25.52 138.67 428.00 1856.31 24.96 248.50 394.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.51 0.48 01-JAN-08:39 4013.00 36.01 190.67 222.17 3401.29 37.18 189.83 196.33
February 217.00 0.50 0.48 01-FEB-11:39 5757.80 35.71 213.33 246.17 2802.69 29.97 141.83 224.50
March 215.50 0.50 0.48 01-MAR-11:39 4244.79 30.11 181.17 310.67 1267.18 17.59 4.67 271.83
April 359.67 0.50 0.48 01-APR-06:49 2726.38 15.02 0.00 355.50 1597.46 18.50 16.83 333.17
May 417.17 0.50 0.48 01-MAY-06:49 2176.38 14.72 0.00 410.67 1269.58 18.16 0.00 378.67
June 410.67 0.49 0.48 01-JUN-05:40 2118.59 15.05 0.00 413.50 1223.75 18.46 0.00 376.33
July 429.00 0.50 0.48 01-JUL-05:40 2116.53 14.85 0.00 421.50 1251.54 18.30 2.50 386.33
August 396.33 0.50 0.48 01-AUG-05:00 2581.84 15.03 5.50 382.50 1462.13 18.18 8.17 351.50
September 337.67 0.50 0.48 01-SEP-07:40 4602.34 19.97 76.17 331.33 1763.54 18.53 12.00 306.83
October 234.00 0.50 0.48 01-OCT-06:49 7271.70 34.60 216.17 280.00 2237.33 21.05 33.67 244.33
November 171.33 0.50 0.48 01-NOV-11:39 4617.22 35.83 166.83 216.67 3894.82 37.11 167.17 176.17
December 131.67 0.49 0.48 02-DEC-08:39 3878.98 36.83 128.50 183.67 3305.08 38.15 128.67 135.67
                         
Annual Sum or Average 3515.67 0.50     3469.23 21.95 1178.33 3774.33 1846.43 21.90 705.33 3381.67
Minimum of Months 131.67 0.49 0.48   2116.53 14.72 0.00 183.67 1223.75 17.59 0.00 135.67
Maximum of Months 429.00 0.51 0.48   7271.70 36.83 216.17 421.50 3894.82 38.15 189.83 386.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.52 0.48 01-JAN-08:39 1493.91 22.77 82.50 211.00 899.14 23.29 73.33 149.50
February 217.00 0.50 0.48 01-FEB-11:39 1826.01 22.64 75.33 239.67 1033.20 23.31 69.83 201.33
March 215.50 0.50 0.48 01-MAR-11:39 2050.95 21.19 71.33 305.17 1110.52 23.37 65.00 256.83
April 359.67 0.50 0.48 01-APR-06:10 3787.78 22.14 107.17 364.33 2254.41 24.33 92.83 344.67
May 417.17 0.49 0.48 01-MAY-06:40 3921.68 22.23 134.00 423.17 1808.60 21.93 72.17 388.33
June 410.67 0.48 0.48 01-JUN-04:49 3948.70 22.80 139.17 421.17 1853.02 22.76 81.50 392.33
July 429.00 0.49 0.48 01-JUL-04:49 3855.87 22.33 139.67 432.67 1807.12 22.81 87.17 404.17
August 396.33 0.49 0.48 01-AUG-05:30 3727.64 22.69 127.83 391.33 1691.61 22.27 72.00 364.67
September 337.67 0.49 0.48 01-SEP-07:40 3527.76 23.00 109.33 338.67 1978.30 23.77 85.00 311.33
October 234.00 0.50 0.48 01-OCT-06:40 2753.93 22.88 85.00 274.17 1291.58 23.12 68.67 220.50
November 171.33 0.51 0.48 01-NOV-11:39 1532.50 22.54 64.83 205.83 890.30 23.20 68.33 140.00
December 131.67 0.50 0.48 02-DEC-08:39 1294.99 23.32 52.67 167.00 907.15 25.47 65.33 102.50
                         
Annual Sum or Average 3515.67 0.50     3171.72 22.52 1188.83 3774.17 1608.13 23.12 901.17 3276.17
Minimum of Months 131.67 0.48 0.48   1294.99 21.19 52.67 167.00 890.30 21.93 65.00 102.50
Maximum of Months 429.00 0.52 0.48   3948.70 23.32 139.67 432.67 2254.41 25.47 92.83 404.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.55 0.48 01-JAN-09:39 549.60 10.28 0.00 188.83 332.54 13.79 0.00 88.50
February 217.00 0.52 0.48 01-FEB-11:39 731.17 12.16 0.00 224.50 445.48 15.64 0.00 152.00
March 215.50 0.51 0.48 01-MAR-11:39 898.17 12.67 0.00 300.67 508.24 15.98 0.00 232.17
April 359.67 0.50 0.48 01-APR-06:49 1206.26 15.02 0.00 360.83 748.04 18.44 5.17 334.67
May 417.17 0.49 0.48 01-MAY-06:49 1423.54 16.94 38.00 425.67 851.49 20.19 53.50 402.50
June 410.67 0.48 0.48 01-JUN-04:49 1617.43 18.20 58.17 428.00 963.95 21.31 79.67 405.67
July 429.00 0.49 0.48 01-JUL-04:49 1507.87 18.06 58.83 439.17 919.17 21.21 79.50 419.00
August 396.33 0.50 0.48 01-AUG-05:49 1228.64 14.93 0.00 391.83 771.93 18.44 6.67 362.67
September 337.67 0.50 0.48 01-SEP-07:40 991.00 14.53 0.00 326.33 644.79 18.01 0.00 288.67
October 234.00 0.51 0.48 01-OCT-07:19 831.84 13.04 0.00 263.83 518.31 16.50 0.00 185.83
November 171.33 0.53 0.48 01-NOV-11:50 610.31 11.03 0.00 182.33 371.56 14.56 0.00 87.33
December 131.67 0.55 0.48 02-DEC-09:50 515.92 10.23 0.00 135.17 316.08 13.93 0.00 49.50
                         
Annual Sum or Average 3515.67 0.50     1134.15 14.84 155.00 3667.17 692.88 18.21 224.50 3008.50
Minimum of Months 131.67 0.48 0.48   515.92 10.23 0.00 135.17 316.08 13.79 0.00 49.50
Maximum of Months 429.00 0.55 0.48   1617.43 18.20 58.83 439.17 963.95 21.31 79.67 419.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.53 0.48 01-JAN-09:39 1350.67 22.00 78.00 204.67 787.36 22.54 68.67 153.00
February 217.00 0.51 0.48 01-FEB-11:39 2074.48 20.33 58.33 234.17 1160.54 22.23 60.83 188.00
March 215.50 0.51 0.48 01-MAR-11:39 1943.89 21.16 72.33 304.83 1070.71 22.14 54.00 255.50
April 359.67 0.50 0.48 01-APR-07:40 3664.17 21.11 101.83 355.67 1701.85 21.08 50.00 332.17
May 417.17 0.50 0.48 01-MAY-06:00 3318.98 18.71 73.83 414.00 1879.56 20.33 45.50 386.00
June 410.67 0.49 0.48 01-JUN-05:49 3830.00 17.72 50.33 420.00 1766.58 18.61 0.00 384.50
July 429.00 0.49 0.48 01-JUL-05:40 3802.20 17.61 53.17 428.67 1795.48 18.57 3.67 398.50
August 396.33 0.50 0.48 01-AUG-06:10 3392.42 19.70 86.83 383.17 1935.78 21.00 57.00 353.83
September 337.67 0.50 0.48 01-SEP-07:49 3284.75 21.50 96.83 325.33 1838.78 22.76 76.17 302.17
October 234.00 0.51 0.48 01-OCT-07:30 2599.56 22.25 81.67 270.17 1207.62 22.47 64.67 216.50
November 171.33 0.52 0.48 01-NOV-11:39 1485.08 21.59 59.50 199.17 813.04 22.17 65.00 136.67
December 131.67 0.53 0.48 02-DEC-09:30 1071.63 19.78 37.67 161.17 572.36 20.28 36.83 88.00
                         
Annual Sum or Average 3515.67 0.50     2985.87 19.93 850.33 3701.00 1539.94 20.88 582.33 3194.83
Minimum of Months 131.67 0.49 0.48   1071.63 17.61 37.67 161.17 572.36 18.57 0.00 88.00
Maximum of Months 429.00 0.53 0.48   3830.00 22.25 101.83 428.67 1935.78 22.76 76.17 398.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.51 0.48 01-JAN-08:39 4013.86 36.00 190.67 222.17 3403.04 37.18 189.83 196.50
February 217.00 0.50 0.48 01-FEB-11:39 5759.58 35.70 213.33 246.17 2805.21 29.97 141.83 224.67
March 215.50 0.50 0.48 01-MAR-11:39 4248.11 30.10 181.17 310.67 1269.70 17.57 4.67 272.33
April 359.67 0.50 0.48 01-APR-06:49 2730.25 14.99 0.00 355.50 1599.94 18.48 16.17 333.17
May 417.17 0.50 0.48 01-MAY-06:49 2179.55 14.69 0.00 410.67 1271.54 18.15 0.00 378.83
June 410.67 0.49 0.48 01-JUN-05:40 2121.74 15.02 0.00 413.50 1225.66 18.45 0.00 376.67
July 429.00 0.50 0.48 01-JUL-05:40 2119.50 14.82 0.00 421.50 1253.40 18.28 2.33 386.50
August 396.33 0.50 0.48 01-AUG-05:00 2585.16 15.00 5.50 382.50 1464.26 18.17 7.83 351.50
September 337.67 0.50 0.48 01-SEP-07:40 4605.62 19.94 76.17 331.33 1766.05 18.51 11.33 307.00
October 234.00 0.50 0.48 01-OCT-06:49 7273.99 34.59 216.17 280.00 2240.18 21.03 33.50 244.33
November 171.33 0.50 0.48 01-NOV-11:39 4618.21 35.82 166.83 216.67 3897.09 37.10 167.17 176.17
December 131.67 0.49 0.48 02-DEC-08:39 3879.75 36.82 128.50 183.67 3306.74 38.14 128.67 135.67
                         
Annual Sum or Average 3515.67 0.50     3472.01 21.93 1178.33 3774.33 1848.61 21.89 703.33 3383.33
Minimum of Months 131.67 0.49 0.48   2119.50 14.69 0.00 183.67 1225.66 17.57 0.00 135.67
Maximum of Months 429.00 0.51 0.48   7273.99 36.82 216.17 421.50 3897.09 38.14 189.83 386.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.52 0.48 01-JAN-08:39 1494.74 22.75 82.50 211.00 900.01 23.28 73.17 149.50
February 217.00 0.50 0.48 01-FEB-11:39 1827.14 22.61 75.33 239.67 1034.39 23.30 69.67 201.50
March 215.50 0.50 0.48 01-MAR-11:39 2052.99 21.17 71.33 305.33 1112.08 23.35 64.83 257.00
April 359.67 0.50 0.48 01-APR-06:10 3789.79 22.11 107.17 364.33 2256.36 24.32 92.83 344.67
May 417.17 0.49 0.48 01-MAY-06:40 3924.08 22.20 134.00 423.17 1810.55 21.92 72.17 388.83
June 410.67 0.48 0.48 01-JUN-04:49 3951.28 22.78 139.17 421.17 1855.06 22.74 81.50 392.33
July 429.00 0.49 0.48 01-JUL-04:49 3858.18 22.31 139.67 432.67 1809.07 22.80 87.17 404.33
August 396.33 0.49 0.48 01-AUG-05:30 3729.44 22.66 127.83 391.33 1693.41 22.26 72.00 365.00
September 337.67 0.49 0.48 01-SEP-07:40 3529.04 22.97 109.33 338.83 1979.94 23.76 84.83 311.50
October 234.00 0.50 0.48 01-OCT-06:40 2755.21 22.86 85.00 274.33 1292.98 23.11 68.17 220.67
November 171.33 0.51 0.48 01-NOV-11:39 1533.44 22.51 64.83 206.17 891.30 23.19 68.17 140.00
December 131.67 0.50 0.48 02-DEC-08:39 1295.71 23.29 52.67 167.00 908.02 25.46 65.17 102.50
                         
Annual Sum or Average 3515.67 0.50     3173.52 22.49 1188.83 3775.00 1609.79 23.11 899.67 3277.83
Minimum of Months 131.67 0.48 0.48   1295.71 21.17 52.67 167.00 891.30 21.92 64.83 102.50
Maximum of Months 429.00 0.52 0.48   3951.28 23.29 139.67 432.67 2256.36 25.46 92.83 404.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.55 0.48 01-JAN-09:39 550.15 10.25 0.00 189.00 333.03 13.77 0.00 88.67
February 217.00 0.52 0.48 01-FEB-11:39 731.92 12.13 0.00 224.83 446.12 15.63 0.00 152.17
March 215.50 0.51 0.48 01-MAR-11:39 899.44 12.64 0.00 300.67 509.11 15.97 0.00 232.33
April 359.67 0.50 0.48 01-APR-06:49 1207.40 14.99 0.00 360.83 749.04 18.43 5.00 334.67
May 417.17 0.49 0.48 01-MAY-06:49 1425.01 16.91 38.00 425.67 852.67 20.18 52.83 402.67
June 410.67 0.48 0.48 01-JUN-04:49 1619.14 18.17 58.17 428.17 965.27 21.29 78.67 405.67
July 429.00 0.49 0.48 01-JUL-04:49 1509.32 18.04 58.83 439.17 920.38 21.20 78.17 419.17
August 396.33 0.50 0.48 01-AUG-05:49 1229.70 14.90 0.00 391.83 772.91 18.42 6.17 362.83
September 337.67 0.50 0.48 01-SEP-07:40 991.73 14.50 0.00 326.33 645.56 18.00 0.00 288.67
October 234.00 0.51 0.48 01-OCT-07:19 832.61 13.01 0.00 263.83 519.01 16.48 0.00 186.00
November 171.33 0.53 0.48 01-NOV-11:50 610.91 11.00 0.00 182.67 372.10 14.55 0.00 87.67
December 131.67 0.55 0.48 02-DEC-09:50 516.39 10.20 0.00 135.33 316.53 13.91 0.00 49.67
                         
Annual Sum or Average 3515.67 0.50     1135.26 14.81 155.00 3668.33 693.82 18.20 220.83 3010.17
Minimum of Months 131.67 0.48 0.48   516.39 10.20 0.00 135.33 316.53 13.77 0.00 49.67
Maximum of Months 429.00 0.55 0.48   1619.14 18.17 58.83 439.17 965.27 21.29 78.67 419.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.53 0.48 01-JAN-09:39 1351.53 21.97 78.00 204.67 788.27 22.53 68.00 153.17
February 217.00 0.51 0.48 01-FEB-11:39 2075.62 20.30 58.33 234.17 1161.80 22.22 60.67 188.33
March 215.50 0.51 0.48 01-MAR-11:39 1945.93 21.14 72.33 304.83 1072.29 22.12 53.83 255.67
April 359.67 0.50 0.48 01-APR-07:40 3666.19 21.08 101.83 355.67 1703.74 21.07 50.00 332.33
May 417.17 0.50 0.48 01-MAY-06:00 3321.25 18.68 73.83 414.00 1881.49 20.32 45.50 386.00
June 410.67 0.49 0.48 01-JUN-05:49 3832.57 17.69 50.33 420.17 1768.69 18.59 0.00 384.50
July 429.00 0.49 0.48 01-JUL-05:40 3804.39 17.58 53.17 428.67 1797.45 18.56 3.67 398.67
August 396.33 0.50 0.48 01-AUG-06:10 3394.44 19.67 86.83 383.17 1937.70 20.99 57.00 353.83
September 337.67 0.50 0.48 01-SEP-07:49 3286.27 21.47 96.83 325.33 1840.42 22.75 76.17 302.67
October 234.00 0.51 0.48 01-OCT-07:30 2600.91 22.22 81.67 270.33 1209.05 22.45 64.00 216.67
November 171.33 0.52 0.48 01-NOV-11:39 1486.07 21.56 59.50 199.17 814.06 22.16 65.00 136.67
December 131.67 0.53 0.48 02-DEC-09:30 1072.41 19.76 37.67 161.50 573.16 20.26 36.67 88.17
                         
Annual Sum or Average 3515.67 0.50     2987.69 19.91 850.33 3701.67 1541.62 20.87 580.50 3196.67
Minimum of Months 131.67 0.49 0.48   1072.41 17.58 37.67 161.50 573.16 18.56 0.00 88.17
Maximum of Months 429.00 0.53 0.48   3832.57 22.22 101.83 428.67 1937.70 22.75 76.17 398.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.124831E+11 34553.47 10-JAN-08:15 0.00 0.00 0.00 0.00 0.00
February 0.805339E+10 27753.66 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.556989E+10 21641.87 08-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.941385E+09 19571.29 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.794923E+09 13719.43 06-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 24002947.26 5764.82 07-JUN-21:00 0.00 0.00 0.00 0.00 0.00
July 6058.46 1.08 24-JUL-09:30 0.00 0.00 0.00 0.00 0.00
August 16304.25 1.03 22-AUG-15:40 0.00 0.00 0.00 0.00 0.00
September 0.152410E+09 9730.33 21-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.159240E+10 14291.12 06-OCT-06:45 0.00 0.00 0.00 0.00 0.00
November 0.461878E+10 23192.28 29-NOV-08:65 0.00 0.00 0.00 0.00 0.00
December 0.897638E+10 25967.94 29-DEC-21:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.432067E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6058.46 1.03   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124831E+11 34553.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 56175590.61 8966.48 10-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 321094.36 230.75 17-FEB-06:50 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 56496684.97     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 56175590.61 8966.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 47606103.97 9411.74 12-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 4378992.46 1852.80 17-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 987114.49 223.60 29-NOV-06:10 0.00 0.00 0.00 0.00 0.00
December 14410891.51 9461.68 30-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 67383102.43     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 47606103.97 9461.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.127320E+09 16145.35 10-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 19992884.63 7213.48 17-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 723269.91 582.94 06-MAR-06:08 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 14463688.41 7441.09 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 61227682.57 16072.69 26-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.223728E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127320E+09 16145.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.159865E+12 329775.68 10-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.121094E+12 287291.85 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.107316E+12 309975.55 10-MAR-14:20 0.00 0.00 0.00 0.00 0.00
April 0.243402E+11 341234.62 07-APR-13:05 0.00 0.00 0.00 0.00 0.00
May 0.150044E+11 261241.93 05-MAY-13:05 0.00 0.00 0.00 0.00 0.00
June 0.141481E+10 180583.91 28-JUN-09:10 0.00 0.00 0.00 0.00 0.00
July 0.230665E+09 45096.40 25-JUL-09:05 0.00 0.00 0.00 0.00 0.00
August 76029155.69 85373.92 31-AUG-09:05 0.00 0.00 0.00 0.00 0.00
September 0.278104E+10 201771.45 08-SEP-10:00 0.00 0.00 0.00 0.00 0.00
October 0.285139E+11 182218.02 02-OCT-11:05 0.00 0.00 0.00 0.00 0.00
November 0.878571E+11 239736.31 29-NOV-07:20 0.00 0.00 0.00 0.00 0.00
December 0.158414E+12 272887.10 29-DEC-21:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.706907E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 76029155.69 45096.40   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159865E+12 341234.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 44772577.40 21029.22 02-JAN-06:09 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 44772577.40     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 44772577.40 21029.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.183479E+11 103295.90 06-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.110105E+11 103310.82 03-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.466796E+10 111854.96 31-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.186679E+09 56474.10 01-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 24612465.33 111819.10 05-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.174733E+10 111872.44 19-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.961243E+10 103280.40 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.257498E+11 103616.94 05-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.713473E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.257498E+11 111872.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.924883E+10 149166.80 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.529600E+10 148605.64 06-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.246593E+10 148300.61 07-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 35210204.24 19288.91 01-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 8409607.39 70080.06 05-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.896551E+09 131794.73 21-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.507939E+10 149146.97 28-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.144811E+11 149193.68 18-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.375114E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144811E+11 149193.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.851989E+10 214510.16 30-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.458628E+10 214418.82 27-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.269855E+10 214508.21 07-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 42379735.16 8938.69 01-APR-05:08 0.00 0.00 0.00 0.00 0.00
May 79938806.65 150018.08 05-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.769514E+09 150695.47 28-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.478916E+10 214172.02 30-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.169947E+11 215434.04 11-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.384804E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.169947E+11 215434.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.665535E+10 143768.94 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.299318E+10 143962.78 13-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.114761E+10 142864.32 04-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 16284021.28 56357.32 05-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.378236E+09 61115.95 28-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.326405E+10 143666.01 30-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.108601E+11 144248.55 18-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.253148E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108601E+11 144248.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185184E+11 37123.08 10-JAN-07:40 0.00 0.00 0.00 0.00 0.00
February 0.145689E+11 33655.59 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.130969E+11 25115.81 08-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.352922E+10 22595.74 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.236079E+10 16912.97 06-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.199355E+09 8575.78 08-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 19873581.66 3964.86 05-JUL-06:10 0.00 0.00 0.00 0.00 0.00
August 16488851.31 5517.29 24-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.460774E+09 12886.37 21-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.439314E+10 17672.78 06-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.111522E+11 28201.62 29-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.180818E+11 29973.37 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.863978E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 16488851.31 3964.86   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.185184E+11 37123.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.468034E+10 68523.64 30-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.257890E+10 68321.77 27-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.123444E+10 68266.36 06-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.433187E+09 67522.19 16-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.230104E+10 68268.75 20-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.574713E+10 68269.18 18-DEC-06:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169750E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.574713E+10 68523.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.521384E+10 11668.27 23-JAN-05:54 0.00 0.00 0.00 0.00 0.00
February 0.373292E+10 11667.59 27-FEB-05:54 0.00 0.00 0.00 0.00 0.00
March 0.251618E+10 11656.10 20-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.449511E+09 11597.16 11-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 0.227621E+09 11608.65 16-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 5176363.80 8351.43 07-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 1902965.31 5847.06 31-JUL-05:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.141551E+09 11582.41 20-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.152968E+10 11657.23 20-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.357381E+10 11663.02 13-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.616336E+10 11666.96 05-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.235556E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.616336E+10 11668.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.296050E+10 17001.87 17-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.203046E+10 16979.34 06-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.141720E+10 16946.43 07-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.145366E+09 16891.26 11-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 73532107.26 16899.40 02-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 2105864.71 4767.34 07-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 15963.93 106.43 31-JUL-05:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 32310775.19 8130.95 18-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.821931E+09 16964.97 30-OCT-04:12 0.00 0.00 0.00 0.00 0.00
November 0.207260E+10 16959.55 13-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.377539E+10 16955.72 23-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.133314E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.377539E+10 17001.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.316791E+10 25321.85 30-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.217494E+10 25304.56 06-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.183855E+10 25255.65 07-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.293142E+09 25173.60 11-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.240970E+09 25166.31 05-MAY-04:12 0.00 0.00 0.00 0.00 0.00
June 14863902.13 18758.50 08-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 458253.16 1133.46 01-JUL-05:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 34817492.20 6482.72 07-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.951280E+09 25208.18 10-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.229145E+10 25275.26 13-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.458627E+10 25267.16 27-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155946E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.458627E+10 25321.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.220174E+10 17478.63 11-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.131406E+10 17467.01 27-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.854619E+09 17457.89 06-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 95712816.00 16203.74 01-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 79198379.26 17423.17 16-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 736444.89 1525.02 08-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 15473256.67 4993.74 07-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.508409E+09 17436.30 20-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.136580E+10 17494.27 28-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.273663E+10 17478.18 30-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.917237E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.273663E+10 17494.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 91.27 0.76 18-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 261.87 0.83 12-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 302.23 1.02 15-AUG-04:12 0.00 0.00 0.00 0.00 0.00
September 180.22 0.90 11-SEP-04:12 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 195.33 0.90 07-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1030.91     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 302.23 1.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.130785E+10 0.130785E+10 32750.66 17-JAN-13:30 32750.66 0.03
February 0.00 0.00 0.329405E+10 0.329405E+10 31501.36 27-FEB-14:40 31501.36 0.03
March 0.00 0.00 0.210367E+10 0.210367E+10 23357.70 28-MAR-10:00 23357.70 0.01
April 0.00 0.00 0.487220E+10 0.486711E+10 82353.27 30-APR-14:21 82353.27 0.03
May 0.00 0.00 0.528758E+10 0.528758E+10 92092.14 22-MAY-15:00 92092.14 0.07
June 0.00 0.00 0.168488E+11 0.165882E+11 124353.15 25-JUN-17:41 62723.84 0.23
July 0.00 0.00 0.285907E+11 0.285318E+11 109790.69 21-JUL-15:10 109790.69 0.40
August 0.00 0.00 0.379601E+11 0.378197E+11 117458.75 14-AUG-15:10 117458.75 0.48
September 0.00 0.00 0.176311E+11 0.175489E+11 81527.24 13-SEP-14:20 81527.24 0.27
October 0.00 0.00 0.317749E+10 0.317749E+10 49499.89 06-OCT-10:00 49499.89 0.04
November 0.00 0.00 0.254749E+10 0.254749E+10 33154.49 03-NOV-14:30 33154.49 0.02
December 0.00 0.00 0.365459E+10 0.365459E+10 33659.73 18-DEC-14:10 33659.73 0.02
                 
Annual Sum or Average 0.00 0.00 0.127276E+12 0.126728E+12       0.14
Minimum of Months 0.00 0.00 0.130785E+10 0.130785E+10 23357.70   23357.70 0.01
Maximum of Months 0.00 0.00 0.379601E+11 0.378197E+11 124353.15   117458.75 0.48



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.143477E+09 0.143477E+09 57893.56 20-JAN-12:00 57893.56 0.00
February 0.00 0.00 0.960991E+09 0.960991E+09 97341.37 09-FEB-15:20 97341.37 0.00
March 0.00 0.00 0.134972E+10 0.134972E+10 105077.83 30-MAR-14:05 105077.83 0.00
April 0.00 0.00 0.458518E+11 0.458363E+11 788459.24 30-APR-15:52 788459.24 0.03
May 0.00 0.00 0.512857E+11 0.512857E+11 800885.20 22-MAY-15:00 800885.20 0.09
June 0.00 0.00 0.143263E+12 0.141361E+12 1027102.67 13-JUN-16:00 926728.03 0.24
July 0.00 0.00 0.223910E+12 0.223592E+12 975260.51 21-JUL-15:30 975260.51 0.39
August 0.00 0.00 0.281427E+12 0.280905E+12 936285.63 14-AUG-15:30 936285.63 0.48
September 0.00 0.00 0.157902E+12 0.156656E+12 774312.12 13-SEP-14:05 774312.12 0.29
October 0.00 0.00 0.352475E+11 0.352475E+11 508676.92 05-OCT-14:05 508676.92 0.03
November 0.00 0.00 0.100418E+09 0.100418E+09 33112.90 10-NOV-11:05 33112.90 0.01
December 0.00 0.00 26057.36 26057.36 1.83 26-DEC-06:01 1.83 0.00
                 
Annual Sum or Average 0.00 0.00 0.941442E+12 0.937439E+12       0.13
Minimum of Months 0.00 0.00 26057.36 26057.36 1.83   1.83 0.00
Maximum of Months 0.00 0.00 0.281427E+12 0.280905E+12 1027102.67   975260.51 0.48



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.335265E+10 0.335265E+10 92110.46 30-APR-16:11 92110.46 0.03
May 0.00 0.00 0.448560E+10 0.448560E+10 88391.48 22-MAY-15:00 88391.48 0.07
June 0.00 0.00 0.144884E+11 0.142906E+11 121382.97 13-JUN-16:00 110842.25 0.21
July 0.00 0.00 0.229075E+11 0.228899E+11 114790.59 21-JUL-15:30 114790.59 0.37
August 0.00 0.00 0.269787E+11 0.269525E+11 108197.36 14-AUG-15:40 108197.36 0.47
September 0.00 0.00 0.138531E+11 0.137973E+11 78760.34 13-SEP-14:40 78760.34 0.26
October 0.00 0.00 0.533048E+09 0.533048E+09 19494.56 07-OCT-15:00 19494.56 0.00
November 0.00 0.00 3323788.29 3323788.29 2538.47 24-NOV-12:00 2538.47 0.00
December 0.00 0.00 4841.28 4841.28 80.69 26-DEC-05:24 80.69 0.00
                 
Annual Sum or Average 0.00 0.00 0.866022E+11 0.863049E+11       0.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.269787E+11 0.269525E+11 121382.97   114790.59 0.47



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 16401.68 16401.68 18.65 19-JAN-21:10 18.65 0.00
February 0.00 0.00 5125.69 5125.69 8.54 24-FEB-18:40 8.54 0.00
March 0.00 0.00 635186.87 296944.35 5162.93 18-MAR-05:02 2344.24 0.00
April 0.00 0.00 0.638597E+09 0.638597E+09 23728.67 28-APR-15:00 23728.67 0.01
May 0.00 0.00 0.201997E+10 0.201997E+10 50582.08 22-MAY-15:00 50582.08 0.04
June 0.00 0.00 0.734464E+10 0.726994E+10 56623.09 27-JUN-05:03 22919.33 0.12
July 0.00 0.00 0.122366E+11 0.121040E+11 60217.83 10-JUL-10:00 60217.83 0.24
August 0.00 0.00 0.159113E+11 0.158372E+11 58355.48 14-AUG-16:00 58355.48 0.34
September 0.00 0.00 0.758485E+10 0.753744E+10 50916.76 16-SEP-05:02 24329.82 0.16
October 0.00 0.00 0.153262E+09 0.132455E+09 31879.04 20-OCT-05:02 13902.71 0.00
November 0.00 0.00 21014559.01 18824850.88 14077.80 15-NOV-05:13 14077.80 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.459109E+11 0.455587E+11       0.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.159113E+11 0.158372E+11 60217.83   60217.83 0.34



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.367622E+10 0.367603E+10 2918.87 10-JAN-18:00 2918.87 0.00
February 0.00 0.00 0.606086E+10 0.594919E+10 5133.31 20-FEB-15:50 5133.31 0.00
March 0.00 0.00 0.110060E+11 0.104866E+11 5615.81 31-MAR-23:10 5615.81 0.00
April 0.00 0.00 0.611624E+11 0.574295E+11 327196.97 30-APR-17:52 327196.97 0.00
May 0.00 0.00 0.224903E+10 0.222053E+10 52422.07 22-MAY-15:00 48436.16 0.00
June 0.00 0.00 0.219388E+11 0.185280E+11 220056.54 13-JUN-17:00 217227.99 0.00
July 0.00 0.00 0.123882E+12 0.981437E+11 310862.68 21-JUL-16:00 310862.68 0.00
August 0.00 0.00 0.399893E+12 0.289281E+12 385129.47 14-AUG-13:00 324456.39 0.00
September 0.00 0.00 0.117022E+10 0.110705E+10 27123.97 13-SEP-16:00 22928.70 0.00
October 0.00 0.00 0.312596E+10 0.301427E+10 13311.27 07-OCT-15:00 13311.27 0.00
November 0.00 0.00 0.761263E+10 0.712606E+10 29520.16 24-NOV-12:00 23257.14 0.00
December 0.00 0.00 0.146531E+11 0.134757E+11 40953.19 23-DEC-11:00 40953.19 0.00
                 
Annual Sum or Average 0.00 0.00 0.656430E+12 0.510437E+12       0.00
Minimum of Months 0.00 0.00 0.117022E+10 0.110705E+10 2918.87   2918.87 0.00
Maximum of Months 0.00 0.00 0.399893E+12 0.289281E+12 385129.47   327196.97 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.413802E+10 0.413646E+10 2316.85 01-JAN-16:10 2311.12 0.00
February 0.00 0.00 0.865022E+10 0.864891E+10 4580.93 19-FEB-16:57 4580.93 0.00
March 0.00 0.00 0.149352E+11 0.149349E+11 7558.32 31-MAR-24:00 7558.32 0.00
April 0.00 0.00 0.198963E+11 0.198956E+11 8894.53 30-APR-19:12 8894.53 0.00
May 0.00 0.00 0.528664E+10 0.526672E+10 3885.87 31-MAY-24:00 3885.87 0.00
June 0.00 0.00 0.104010E+11 0.103151E+11 5727.02 30-JUN-24:00 5727.02 0.00
July 0.00 0.00 0.160308E+11 0.159128E+11 7789.70 31-JUL-24:00 7789.70 0.00
August 0.00 0.00 0.210197E+11 0.208850E+11 8855.32 13-AUG-18:03 8826.53 0.00
September 0.00 0.00 0.529844E+10 0.523414E+10 3784.54 30-SEP-24:00 3784.54 0.00
October 0.00 0.00 0.101291E+11 0.101025E+11 5627.62 31-OCT-24:00 5627.62 0.00
November 0.00 0.00 0.144760E+11 0.144602E+11 6218.55 19-NOV-15:55 6218.55 0.00
December 0.00 0.00 0.197722E+11 0.197720E+11 7986.37 25-DEC-15:20 7986.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.150034E+12 0.149564E+12       0.00
Minimum of Months 0.00 0.00 0.413802E+10 0.413646E+10 2316.85   2311.12 0.00
Maximum of Months 0.00 0.00 0.210197E+11 0.208850E+11 8894.53   8894.53 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.196547E+11 0.196398E+11 18216.13 19-JAN-16:20 18216.13 0.00
February 0.00 0.00 0.663079E+11 0.662945E+11 38816.08 27-FEB-17:00 38816.08 0.00
March 0.00 0.00 0.127229E+12 0.127225E+12 68270.64 31-MAR-23:30 68270.64 0.00
April 0.00 0.00 0.183191E+12 0.183184E+12 84084.70 30-APR-18:10 84084.70 0.00
May 0.00 0.00 0.439110E+11 0.437149E+11 35696.32 31-MAY-23:40 35696.32 0.00
June 0.00 0.00 0.949536E+11 0.941020E+11 52497.37 30-JUN-23:40 52497.37 0.00
July 0.00 0.00 0.148993E+12 0.147827E+12 73268.86 31-JUL-23:50 73268.86 0.00
August 0.00 0.00 0.197234E+12 0.195900E+12 82675.85 13-AUG-18:03 82399.66 0.00
September 0.00 0.00 0.446166E+11 0.439896E+11 33873.91 30-SEP-23:30 33873.91 0.00
October 0.00 0.00 0.840157E+11 0.837526E+11 48754.99 31-OCT-23:50 48754.99 0.00
November 0.00 0.00 0.119552E+12 0.119394E+12 54927.36 10-NOV-16:10 54708.90 0.00
December 0.00 0.00 0.162111E+12 0.162109E+12 69021.05 21-DEC-15:20 69021.05 0.00
                 
Annual Sum or Average 0.00 0.00 0.129177E+13 0.128713E+13       0.00
Minimum of Months 0.00 0.00 0.196547E+11 0.196398E+11 18216.13   18216.13 0.00
Maximum of Months 0.00 0.00 0.197234E+12 0.195900E+12 84084.70   84084.70 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.477263E+09 0.476376E+09 1688.90 19-JAN-16:30 1688.90 0.00
February 0.00 0.00 0.481490E+10 0.481365E+10 3639.62 24-FEB-17:00 3639.62 0.00
March 0.00 0.00 0.110225E+11 0.110222E+11 6342.98 31-MAR-23:20 6342.98 0.00
April 0.00 0.00 0.175122E+11 0.175116E+11 8532.17 30-APR-18:10 8532.17 0.00
May 0.00 0.00 0.367762E+10 0.365815E+10 3422.70 31-MAY-23:20 3422.70 0.00
June 0.00 0.00 0.916481E+10 0.907979E+10 5031.50 30-JUN-23:20 5031.50 0.00
July 0.00 0.00 0.146222E+11 0.145057E+11 7172.77 31-JUL-23:20 7172.77 0.00
August 0.00 0.00 0.194310E+11 0.192978E+11 8388.59 13-AUG-18:03 8360.73 0.00
September 0.00 0.00 0.380586E+10 0.374408E+10 2857.27 30-SEP-23:10 2857.27 0.00
October 0.00 0.00 0.682829E+10 0.680279E+10 4280.90 31-OCT-23:20 4280.90 0.00
November 0.00 0.00 0.100724E+11 0.100569E+11 5407.37 10-NOV-16:10 5385.70 0.00
December 0.00 0.00 0.142328E+11 0.142327E+11 6634.29 21-DEC-15:20 6634.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.115662E+12 0.115202E+12       0.00
Minimum of Months 0.00 0.00 0.477263E+09 0.476376E+09 1688.90   1688.90 0.00
Maximum of Months 0.00 0.00 0.194310E+11 0.192978E+11 8532.17   8532.17 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 93984.81 1071416.10 30-JAN-06:02
February 0.00 0.00 01-FEB-00:10 74099.71 1113465.68 27-FEB-05:11
March 0.00 0.00 01-MAR-00:10 53995.84 1049045.70 07-MAR-06:02
April 0.00 0.00 01-APR-00:10 11567.97 465223.81 07-APR-13:05
May 0.00 0.00 01-MAY-00:10 7054.89 789477.52 05-MAY-05:02
June 0.00 0.00 01-JUN-00:10 643.89 223543.03 28-JUN-09:10
July 0.00 0.00 01-JUL-00:10 84.71 44245.16 25-JUL-09:05
August 0.00 0.00 01-AUG-00:10 33.82 93551.31 31-AUG-09:05
September 0.00 0.00 01-SEP-00:10 1396.64 274657.01 08-SEP-10:00
October 0.00 0.00 01-OCT-00:10 15868.98 939808.00 28-OCT-05:02
November 0.00 0.00 01-NOV-00:10 53176.12 1265984.13 25-NOV-05:11
December 0.00 0.00 01-DEC-00:10 103161.85 1152764.40 12-DEC-05:11
             
Annual Sum or Average 0.00     34460.44    
Minimum of Months 0.00 0.00   33.82 44245.16  
Maximum of Months 0.00 0.00   103161.85 1265984.13  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 692.29 73176.02 20-JAN-12:00 0.00 0.00 01-JAN-00:05
February 2073.26 125034.79 09-FEB-15:30 0.00 0.00 01-FEB-00:10
March 1568.99 104389.40 30-MAR-14:05 0.00 0.00 01-MAR-00:10
April 21371.53 702285.10 28-APR-14:30 0.00 0.00 01-APR-00:10
May 23917.73 1326612.94 22-MAY-14:05 0.00 0.00 01-MAY-00:10
June 72938.60 1315966.87 13-JUN-16:00 0.00 0.00 01-JUN-00:10
July 110276.77 1257351.82 21-JUL-12:05 0.00 0.00 01-JUL-00:10
August 137466.25 1447914.17 28-AUG-14:05 0.00 0.00 01-AUG-00:10
September 78379.83 1151223.60 27-SEP-14:05 0.00 0.00 01-SEP-00:10
October 14882.47 520255.88 06-OCT-14:30 0.00 0.00 01-OCT-00:10
November 1241.10 41264.36 24-NOV-12:00 0.00 0.00 01-NOV-00:10
December 1767.03 35034.98 18-DEC-14:20 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 39133.43     0.00    
Minimum of Months 692.29 35034.98   0.00 0.00  
Maximum of Months 137466.25 1447914.17   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 511.08 73266.00 20-JAN-12:00 0.00 0.00 01-JAN-00:05
February 1749.02 122812.98 09-FEB-15:20 0.00 0.00 01-FEB-00:10
March 1274.40 103746.22 30-MAR-14:05 0.00 0.00 01-MAR-00:10
April 21337.83 1024220.11 30-APR-15:52 0.00 0.00 01-APR-00:10
May 23820.78 1485467.93 22-MAY-14:00 0.00 0.00 01-MAY-00:10
June 72850.43 1314633.95 13-JUN-16:00 0.00 0.00 01-JUN-00:10
July 110278.46 1473377.04 21-JUL-10:30 0.00 0.00 01-JUL-00:10
August 136655.25 1356150.45 21-AUG-12:30 0.00 0.00 01-AUG-00:10
September 79125.80 1726319.56 12-SEP-15:40 0.00 0.00 01-SEP-00:10
October 14590.76 526518.74 05-OCT-14:05 0.00 0.00 01-OCT-00:10
November 1010.69 41475.11 24-NOV-12:00 0.00 0.00 01-NOV-00:10
December 1361.18 32548.59 18-DEC-14:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 38964.29     0.00    
Minimum of Months 511.08 32548.59   0.00 0.00  
Maximum of Months 136655.25 1726319.56   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 16696.42 31024.35 19-JAN-16:30 0.00 0.00 01-JAN-00:05
February 47041.22 63937.41 19-FEB-17:10 0.00 0.00 01-FEB-00:10
March 77927.67 109715.28 31-MAR-23:40 0.00 0.00 01-MAR-00:10
April 147668.94 1073476.21 30-APR-17:40 0.00 0.00 01-APR-00:10
May 31780.32 421997.78 22-MAY-15:00 0.00 0.00 01-MAY-00:10
June 88774.10 929849.15 13-JUN-17:00 0.00 0.00 01-JUN-00:10
July 194020.89 1302727.63 22-JUL-18:00 0.00 0.00 01-JUL-00:10
August 382673.48 1275154.28 14-AUG-17:10 0.00 0.00 01-AUG-00:10
September 42290.27 331885.44 13-SEP-16:00 0.00 0.00 01-SEP-00:10
October 50664.31 128109.59 07-OCT-15:00 0.00 0.00 01-OCT-00:10
November 74311.44 110034.75 24-NOV-12:00 0.00 0.00 01-NOV-00:10
December 98822.20 144025.92 23-DEC-11:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 105037.37     0.00    
Minimum of Months 16696.42 31024.35   0.00 0.00  
Maximum of Months 382673.48 1302727.63   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 15864.95 53217.75 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 16048.11 53302.66 24-FEB-12:10
March 0.00 0.00 01-MAR-00:10 16857.68 53240.51 01-MAR-12:15
April 0.00 0.00 01-APR-00:10 15609.42 52438.00 03-APR-11:30
May 0.00 0.00 01-MAY-00:10 15691.24 51305.71 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 15641.57 49909.71 01-JUN-11:10
July 0.00 0.00 01-JUL-00:10 14234.88 48612.93 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 15335.71 48008.43 01-AUG-11:10
September 0.00 0.00 01-SEP-00:10 14566.16 48663.06 29-SEP-11:10
October 0.00 0.00 01-OCT-00:10 14826.84 49880.81 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 15399.27 51262.81 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 15250.43 52461.64 29-DEC-12:40
             
Annual Sum or Average 0.00     15440.42    
Minimum of Months 0.00 0.00   14234.88 48008.43  
Maximum of Months 0.00 0.00   16857.68 53302.66  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 113.58 42293.93 20-JAN-12:10 1536.68 92485.09 07-JAN-06:50
February 488.34 158379.59 09-FEB-15:40 3027.23 110925.83 17-FEB-06:40
March 392.25 124710.98 30-MAR-14:10 2743.01 99859.53 27-MAR-05:40
April 23866.70 791042.33 28-APR-15:00 768.61 76077.56 15-APR-07:50
May 27471.67 1738583.21 22-MAY-14:50 575.49 75517.71 05-MAY-08:70
June 90045.94 1968417.14 13-JUN-16:00 446.95 52603.75 23-JUN-18:30
July 133012.20 1789703.76 21-JUL-10:50 681.63 53791.11 03-JUL-09:50
August 163126.39 1767484.52 28-AUG-15:10 475.04 67482.86 30-AUG-05:50
September 93630.98 1742505.80 13-SEP-14:00 754.28 77323.35 21-SEP-05:50
October 15854.19 591135.98 05-OCT-14:10 1055.19 90880.44 23-OCT-05:40
November 152.61 31760.23 27-NOV-14:30 2236.11 97315.72 17-NOV-06:40
December 228.45 37654.62 26-DEC-12:00 4144.02 94909.94 04-DEC-07:00
             
Annual Sum or Average 46001.97     1530.09    
Minimum of Months 113.58 31760.23   446.95 52603.75  
Maximum of Months 163126.39 1968417.14   4144.02 110925.83  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.122785E+11 0.78 8204.25 01-JAN-00:10 1.41
February 0.108530E+11 0.77 8204.25 01-FEB-05:12 1.40
March 0.128310E+11 0.82 8204.25 01-MAR-05:12 1.40
April 0.117230E+11 0.77 8204.25 01-APR-04:13 1.41
May 0.124819E+11 0.80 8204.25 01-MAY-00:10 1.40
June 0.122941E+11 0.81 8204.25 01-JUN-04:13 1.40
July 0.119191E+11 0.76 8204.25 01-JUL-04:13 1.40
August 0.131924E+11 0.84 8204.25 01-AUG-04:12 1.40
September 0.119905E+11 0.79 8204.25 01-SEP-04:12 1.40
October 0.122153E+11 0.78 8204.25 02-OCT-04:12 1.40
November 0.117633E+11 0.78 8204.25 01-NOV-04:13 1.40
December 0.118359E+11 0.76 8204.25 01-DEC-05:11 1.40
           
Annual Sum or Average 0.145378E+12 0.79      
Minimum of Months 0.108530E+11 0.76 8204.25   1.40
Maximum of Months 0.131924E+11 0.84 8204.25   1.41



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.309532E+10 0.30 11521.27 10-JAN-06:01 1.33
February 0.342633E+10 0.33 7460.94 27-FEB-14:50 1.01
March 0.449940E+10 0.36 9822.59 24-MAR-05:02 1.20
April 0.878042E+10 0.52 17703.33 28-APR-14:50 1.73
May 0.667433E+10 0.44 13644.91 22-MAY-14:50 1.46
June 0.870881E+10 0.52 16020.91 26-JUN-14:50 1.61
July 0.103658E+11 0.57 18607.74 24-JUL-05:02 1.78
August 0.122569E+11 0.64 18607.74 14-AUG-13:50 1.78
September 0.741836E+10 0.47 18607.74 12-SEP-15:40 1.77
October 0.523120E+10 0.37 12096.62 03-OCT-14:50 1.36
November 0.407440E+10 0.34 10822.84 09-NOV-06:02 1.26
December 0.373438E+10 0.32 10767.75 30-DEC-06:01 1.27
           
Annual Sum or Average 0.782657E+11 0.43      
Minimum of Months 0.309532E+10 0.30 7460.94   1.01
Maximum of Months 0.122569E+11 0.64 18607.74   1.78



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.218981E+11 0.28 43558.56 26-JAN-06:02 0.78
February 0.215706E+11 0.29 42202.63 17-FEB-15:10 0.77
March 0.241866E+11 0.29 74883.25 31-MAR-05:02 1.07
April 0.470997E+11 0.38 139000.59 28-APR-15:00 1.57
May 0.483165E+11 0.38 116995.03 23-MAY-14:05 1.40
June 0.596900E+11 0.44 134466.38 13-JUN-14:05 1.53
July 0.652784E+11 0.45 133590.48 21-JUL-15:20 1.53
August 0.727314E+11 0.48 135124.87 14-AUG-15:20 1.54
September 0.565410E+11 0.42 169616.19 12-SEP-15:30 1.78
October 0.318463E+11 0.31 88718.84 03-OCT-15:10 1.19
November 0.219267E+11 0.28 67253.81 01-NOV-05:02 1.01
December 0.206035E+11 0.27 36109.09 01-DEC-06:02 0.71
           
Annual Sum or Average 0.491689E+12 0.36      
Minimum of Months 0.206035E+11 0.27 36109.09   0.71
Maximum of Months 0.727314E+11 0.48 169616.19   1.78



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.234478E+10 0.30 4540.83 02-JAN-04:01 0.75
February 0.209638E+10 0.29 4540.83 06-FEB-05:11 0.75
March 0.228706E+10 0.30 4540.83 06-MAR-05:11 0.75
April 0.359200E+10 0.33 13204.65 28-APR-15:20 1.41
May 0.397058E+10 0.34 12221.17 22-MAY-15:20 1.34
June 0.523877E+10 0.39 14774.35 13-JUN-15:30 1.50
July 0.584772E+10 0.40 14339.32 21-JUL-15:30 1.48
August 0.612865E+10 0.42 13911.25 14-AUG-15:20 1.45
September 0.434969E+10 0.36 15735.70 12-SEP-15:30 1.57
October 0.247959E+10 0.29 5779.10 03-OCT-14:50 0.86
November 0.213872E+10 0.29 4540.83 13-NOV-05:11 0.75
December 0.238177E+10 0.31 4540.83 01-DEC-06:02 0.75
           
Annual Sum or Average 0.428557E+11 0.33      
Minimum of Months 0.209638E+10 0.29 4540.83   0.75
Maximum of Months 0.612865E+10 0.42 15735.70   1.57



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.952024E+11 1.37 35544.49 01-JAN-00:05 1.37
February 0.859892E+11 1.37 35544.49 01-FEB-00:10 1.37
March 0.952024E+11 1.37 35544.49 01-MAR-00:30 1.37
April 0.921313E+11 1.37 35544.49 01-APR-00:10 1.37
May 0.952024E+11 1.37 35544.49 01-MAY-00:10 1.37
June 0.921313E+11 1.37 35544.49 01-JUN-00:10 1.37
July 0.952024E+11 1.36 35544.49 01-JUL-00:10 1.37
August 0.952024E+11 1.36 35544.49 01-AUG-00:10 1.37
September 0.921313E+11 1.37 35544.49 01-SEP-00:10 1.37
October 0.952024E+11 1.37 35544.49 01-OCT-00:10 1.37
November 0.921313E+11 1.37 35544.49 01-NOV-00:10 1.37
December 0.952024E+11 1.37 35544.49 01-DEC-00:10 1.37
           
Annual Sum or Average 0.112093E+13 1.37      
Minimum of Months 0.859892E+11 1.36 35544.49   1.37
Maximum of Months 0.952024E+11 1.37 35544.49   1.37



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.149644E+10 0.93 558.70 01-JAN-00:05 0.92
February 0.135162E+10 0.93 558.70 01-FEB-00:10 0.93
March 0.149644E+10 0.93 558.70 01-MAR-00:10 0.92
April 0.144816E+10 0.93 558.70 01-APR-00:10 0.93
May 0.149644E+10 0.92 558.70 01-MAY-00:10 0.92
June 0.144816E+10 0.92 558.70 01-JUN-00:10 0.92
July 0.149644E+10 0.92 558.70 01-JUL-00:10 0.92
August 0.149644E+10 0.92 558.70 01-AUG-00:10 0.92
September 0.144816E+10 0.92 558.70 01-SEP-00:10 0.92
October 0.149644E+10 0.92 558.70 01-OCT-00:10 0.93
November 0.144816E+10 0.92 558.70 01-NOV-00:10 0.93
December 0.149644E+10 0.93 558.70 01-DEC-00:10 0.93
           
Annual Sum or Average 0.176193E+11 0.92      
Minimum of Months 0.135162E+10 0.92 558.70   0.92
Maximum of Months 0.149644E+10 0.93 558.70   0.93



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.143772E+11 0.93 5367.85 01-JAN-00:05 0.92
February 0.129859E+11 0.93 5367.85 01-FEB-00:10 0.93
March 0.143772E+11 0.93 5367.85 01-MAR-00:10 0.92
April 0.139135E+11 0.93 5367.85 01-APR-00:10 0.93
May 0.143772E+11 0.92 5367.85 01-MAY-00:10 0.92
June 0.139135E+11 0.92 5367.85 01-JUN-00:10 0.92
July 0.143772E+11 0.92 5367.85 01-JUL-00:10 0.92
August 0.143772E+11 0.92 5367.85 01-AUG-00:10 0.92
September 0.139135E+11 0.92 5367.85 01-SEP-00:10 0.92
October 0.143772E+11 0.92 5367.85 01-OCT-00:10 0.93
November 0.139135E+11 0.92 5367.85 01-NOV-00:10 0.93
December 0.143772E+11 0.93 5367.85 01-DEC-00:10 0.93
           
Annual Sum or Average 0.169280E+12 0.92      
Minimum of Months 0.129859E+11 0.92 5367.85   0.92
Maximum of Months 0.143772E+11 0.93 5367.85   0.93



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.145762E+10 0.93 544.21 01-JAN-00:05 0.92
February 0.131656E+10 0.93 544.21 01-FEB-00:10 0.93
March 0.145762E+10 0.93 544.21 01-MAR-00:10 0.92
April 0.141060E+10 0.93 544.21 01-APR-00:10 0.93
May 0.145762E+10 0.92 544.21 01-MAY-00:10 0.92
June 0.141060E+10 0.92 544.21 01-JUN-00:10 0.92
July 0.145762E+10 0.92 544.21 01-JUL-00:10 0.92
August 0.145762E+10 0.92 544.21 01-AUG-00:10 0.92
September 0.141060E+10 0.92 544.21 01-SEP-00:10 0.92
October 0.145762E+10 0.92 544.21 01-OCT-00:10 0.93
November 0.141060E+10 0.92 544.21 01-NOV-00:10 0.93
December 0.145762E+10 0.93 544.21 01-DEC-00:10 0.93
           
Annual Sum or Average 0.171623E+11 0.92      
Minimum of Months 0.131656E+10 0.92 544.21   0.92
Maximum of Months 0.145762E+10 0.93 544.21   0.93



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 60340542.80 54849553.40 875.46 10-JAN-06:01 795.79 795.79 43.74 12.91
February 28064324.38 25510470.86 831.87 17-FEB-06:01 756.17 756.17 41.45 12.63
March 17166809.85 15604630.16 808.95 04-MAR-06:02 735.33 735.33 40.87 12.47
April 2611101.66 2373491.41 102.71 07-APR-13:05 93.36 93.36 35.16 4.48
May 1431567.50 1301294.86 379.29 05-MAY-05:02 344.77 344.77 38.40 8.74
June 112435.66 102204.01 24.98 28-JUN-09:10 22.71 22.71 32.52 1.95
July 13064.23 11875.38 2.65 25-JUL-09:05 2.41 2.41 30.80 0.36
August 5424.10 4930.50 6.55 31-AUG-09:05 5.95 5.95 30.47 0.76
September 253756.43 230664.59 33.55 08-SEP-10:00 30.50 30.50 31.97 2.34
October 3694088.87 3357926.78 465.66 28-OCT-05:02 423.29 423.29 36.71 9.65
November 20102552.84 18273220.53 835.70 27-NOV-06:01 759.65 759.65 43.11 12.64
December 54204696.33 49272068.97 854.20 30-DEC-06:01 776.47 776.47 43.22 12.77
                 
Annual Sum or Average 0.188000E+09 0.170892E+09            
Minimum of Months 5424.10 4930.50 2.65   2.41 2.41 30.47 0.36
Maximum of Months 60340542.80 54849553.40 875.46   795.79 795.79 43.74 12.91



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 208524.60 189548.86 11.78 20-JAN-12:00 10.71 10.71 6.70 1.95
February 546448.84 496722.00 22.12 09-FEB-15:20 20.10 20.10 6.70 2.93
March 395984.76 359950.15 15.84 30-MAR-14:05 14.40 14.40 6.70 2.37
April 34183167.87 31072499.59 3005.18 28-APR-15:20 2731.71 2731.71 8.18 33.49
May 55419408.73 50376242.54 5934.11 22-MAY-14:00 5394.11 5394.11 11.65 44.09
June 0.185198E+09 0.168345E+09 3347.02 20-JUN-15:10 3042.44 3042.44 8.68 35.01
July 0.282731E+09 0.257002E+09 5718.50 21-JUL-10:30 5198.12 5198.12 9.94 43.45
August 0.294741E+09 0.267920E+09 6586.86 21-AUG-12:30 5987.46 5987.46 10.00 45.96
September 0.212721E+09 0.193363E+09 7978.00 12-SEP-15:30 7252.01 7252.01 11.19 49.55
October 19142899.39 17400895.55 825.13 03-OCT-14:05 750.05 750.05 6.71 19.28
November 280441.36 254921.20 10.01 24-NOV-12:00 9.10 9.10 6.70 1.74
December 380760.04 346110.87 5.31 21-DEC-14:10 4.82 4.82 6.70 1.10
                 
Annual Sum or Average 0.108595E+10 0.987126E+09            
Minimum of Months 208524.60 189548.86 5.31   4.82 4.82 6.70 1.10
Maximum of Months 0.294741E+09 0.267920E+09 7978.00   7252.01 7252.01 11.65 49.55



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.534571E+09 0.485925E+09 2792.95 02-JAN-10:20 2538.79 2538.79 6.72 24.95
February 0.864978E+09 0.786265E+09 2792.95 02-FEB-05:11 2538.79 2538.79 6.73 24.95
March 0.875088E+09 0.795455E+09 2792.95 01-MAR-11:00 2538.79 2538.79 6.75 24.95
April 0.977055E+09 0.888143E+09 2792.95 03-APR-08:40 2538.79 2538.79 6.85 24.95
May 0.102064E+10 0.927766E+09 2792.95 01-MAY-06:20 2538.79 2538.79 6.76 24.95
June 0.195415E+10 0.177633E+10 2792.95 01-JUN-05:02 2538.79 2538.79 6.73 24.95
July 0.333581E+10 0.303225E+10 2792.95 01-JUL-04:13 2538.79 2538.79 8.17 24.95
August 0.398185E+10 0.361950E+10 2792.95 01-AUG-04:12 2538.79 2538.79 7.01 24.95
September 0.247009E+10 0.224531E+10 2792.95 01-SEP-04:12 2538.79 2538.79 6.97 24.95
October 0.894052E+09 0.812693E+09 2792.95 01-OCT-11:02 2538.79 2538.79 7.59 24.95
November 0.652605E+09 0.593218E+09 2792.95 01-NOV-08:00 2538.79 2538.79 6.80 24.95
December 0.119608E+10 0.108724E+10 2792.95 01-DEC-13:20 2538.79 2538.79 6.73 24.95
                 
Annual Sum or Average 0.187570E+11 0.170501E+11            
Minimum of Months 0.534571E+09 0.485925E+09 2792.95   2538.79 2538.79 6.72 24.95
Maximum of Months 0.398185E+10 0.361950E+10 2792.95   2538.79 2538.79 8.17 24.95



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00 6.70 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 6.74 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 6.84 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 7.32 0.00
May 23460806.45 21325873.06 2792.95 22-MAY-13:50 2538.79 2538.79 14.97 12.48
June 0.162550E+09 0.147758E+09 2792.95 12-JUN-12:40 2538.79 2538.79 15.67 12.48
July 0.177632E+09 0.161467E+09 2792.95 10-JUL-08:40 2538.79 2538.79 15.64 12.48
August 0.118142E+09 0.107391E+09 2792.95 14-AUG-10:05 2538.79 2538.79 11.37 24.95
September 98870541.46 89873322.19 2792.95 11-SEP-14:00 2538.79 2538.79 15.58 12.48
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 7.60 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 7.07 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.74 0.00
                 
Annual Sum or Average 0.580655E+09 0.527815E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.70 0.00
Maximum of Months 0.177632E+09 0.161467E+09 2792.95   2538.79 2538.79 15.67 24.95



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.886268E+10 0.805618E+10 3308.95 01-JAN-00:05 3007.83 3007.83 18.54 13.96
February 0.800500E+10 0.727655E+10 3308.95 01-FEB-00:10 3007.83 3007.83 19.21 13.96
March 0.886268E+10 0.805618E+10 3308.95 01-MAR-00:10 3007.83 3007.83 19.86 13.96
April 0.857679E+10 0.779630E+10 3308.95 01-APR-00:10 3007.83 3007.83 20.59 13.96
May 0.886268E+10 0.805618E+10 3308.95 01-MAY-00:10 3007.83 3007.83 19.08 13.96
June 0.857679E+10 0.779630E+10 3308.95 01-JUN-00:10 3007.83 3007.83 19.53 13.96
July 0.886268E+10 0.805618E+10 3308.95 01-JUL-00:10 3007.83 3007.83 19.95 13.96
August 0.886268E+10 0.805618E+10 3308.95 01-AUG-00:10 3007.83 3007.83 20.56 13.96
September 0.857679E+10 0.779630E+10 3308.95 01-SEP-00:10 3007.83 3007.83 18.97 13.96
October 0.886268E+10 0.805618E+10 3308.95 01-OCT-00:10 3007.83 3007.83 19.48 13.96
November 0.857679E+10 0.779630E+10 3308.95 01-NOV-00:10 3007.83 3007.83 20.01 13.96
December 0.886268E+10 0.805618E+10 3308.95 01-DEC-00:10 3007.83 3007.83 20.38 13.96
                 
Annual Sum or Average 0.104351E+12 0.948550E+11            
Minimum of Months 0.800500E+10 0.727655E+10 3308.95   3007.83 3007.83 18.54 13.96
Maximum of Months 0.886268E+10 0.805618E+10 3308.95   3007.83 3007.83 20.59 13.96



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 55.51 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:02 16.86 16.86 55.45 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:02 16.86 16.86 55.46 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:02 16.86 16.86 55.54 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 55.95 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:02 16.86 16.86 56.12 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 55.61 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 56.80 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 56.04 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.41 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:02 16.86 16.86 55.61 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:02 16.86 16.86 56.66 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.45 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 56.80 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.208683E+10 0.189693E+10 10905.59 20-JAN-12:10 9913.18 9913.18 21.33 44.63
February 0.337665E+10 0.306938E+10 10910.47 09-FEB-15:40 9917.62 9917.62 21.95 44.63
March 0.341612E+10 0.310525E+10 10909.06 30-MAR-14:10 9916.33 9916.33 21.77 44.63
April 0.381699E+10 0.346964E+10 10937.57 28-APR-15:00 9942.26 9942.26 25.34 44.63
May 0.406619E+10 0.369617E+10 21882.90 22-MAY-14:50 19891.56 19891.56 25.76 89.26
June 0.824087E+10 0.749095E+10 21894.21 13-JUN-16:00 19901.83 19901.83 26.38 89.26
July 0.137054E+11 0.124582E+11 21885.42 21-JUL-10:50 19893.84 19893.84 25.90 89.26
August 0.159792E+11 0.145251E+11 21884.32 28-AUG-15:10 19892.85 19892.85 25.84 89.26
September 0.100199E+11 0.910809E+10 21883.10 13-SEP-14:00 19891.73 19891.73 25.77 89.26
October 0.349209E+10 0.317431E+10 10928.69 05-OCT-14:10 9934.18 9934.18 24.27 44.63
November 0.254757E+10 0.231574E+10 10905.15 27-NOV-14:30 9912.78 9912.78 21.27 44.63
December 0.466912E+10 0.424423E+10 10905.40 26-DEC-12:00 9913.01 9913.01 21.30 44.63
                 
Annual Sum or Average 0.754169E+11 0.685540E+11            
Minimum of Months 0.208683E+10 0.189693E+10 10905.15   9912.78 9912.78 21.27 44.63
Maximum of Months 0.159792E+11 0.145251E+11 21894.21   19901.83 19901.83 26.38 89.26



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 37.78 60.00 93984.81 1071416.10 30-JAN-06:02
February 0.00 0.00 01-FEB-00:10 32.06 32.06 74099.71 1113465.68 27-FEB-05:11
March 0.00 0.00 01-MAR-00:10 36.59 36.59 53995.84 1049045.70 07-MAR-06:02
April 0.00 0.00 01-APR-00:10 35.25 35.25 11567.97 465223.81 07-APR-13:05
May 0.00 0.00 01-MAY-00:10 31.49 31.49 7054.89 789477.52 05-MAY-05:02
June 0.00 0.00 01-JUN-00:10 32.42 32.42 643.89 223543.03 28-JUN-09:10
July 0.00 0.00 01-JUL-00:10 33.45 33.45 84.71 44245.16 25-JUL-09:05
August 0.00 0.00 01-AUG-00:10 30.79 30.79 33.82 93551.31 31-AUG-09:05
September 0.00 0.00 01-SEP-00:10 30.60 30.60 1396.64 274657.01 08-SEP-10:00
October 0.00 0.00 01-OCT-00:10 31.24 31.24 15868.98 939808.00 28-OCT-05:02
November 0.00 0.00 01-NOV-00:10 33.54 33.54 53176.12 1265984.13 25-NOV-05:11
December 0.00 0.00 01-DEC-00:10 35.87 35.87 103161.85 1152764.40 12-DEC-05:11
                 
Annual Sum or Average 0.00         34460.44    
Minimum of Months 0.00 0.00   30.60 30.60 33.82 44245.16  
Maximum of Months 0.00 0.00   37.78 60.00 103161.85 1265984.13  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 692.29 73176.02 20-JAN-12:00 7.40 6.70 0.00 0.00 01-JAN-00:05
February 2073.26 125034.79 09-FEB-15:30 7.89 6.70 0.00 0.00 01-FEB-00:10
March 1568.99 104389.40 30-MAR-14:05 7.70 6.70 0.00 0.00 01-MAR-00:10
April 21371.53 702285.10 28-APR-14:30 13.42 6.70 0.00 0.00 01-APR-00:10
May 23917.73 1326612.94 22-MAY-14:05 13.05 6.70 0.00 0.00 01-MAY-00:10
June 72938.60 1315966.87 13-JUN-16:00 13.00 6.70 0.00 0.00 01-JUN-00:10
July 110276.77 1257351.82 21-JUL-12:05 12.72 6.70 0.00 0.00 01-JUL-00:10
August 137466.25 1447914.17 28-AUG-14:05 13.63 6.70 0.00 0.00 01-AUG-00:10
September 78379.83 1151223.60 27-SEP-14:05 12.21 6.70 0.00 0.00 01-SEP-00:10
October 14882.47 520255.88 06-OCT-14:30 11.68 6.70 0.00 0.00 01-OCT-00:10
November 1241.10 41264.36 24-NOV-12:00 7.09 6.70 0.00 0.00 01-NOV-00:10
December 1767.03 35034.98 18-DEC-14:20 7.03 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 39133.43         0.00    
Minimum of Months 692.29 35034.98   7.03 6.70 0.00 0.00  
Maximum of Months 137466.25 1447914.17   13.63 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 511.08 73266.00 20-JAN-12:00 15.69 6.70 0.00 0.00 01-JAN-00:05
February 1749.02 122812.98 09-FEB-15:20 16.70 6.70 0.00 0.00 01-FEB-00:10
March 1274.40 103746.22 30-MAR-14:05 17.16 6.70 0.00 0.00 01-MAR-00:10
April 21337.83 1024220.11 30-APR-15:52 20.78 6.70 0.00 0.00 01-APR-00:10
May 23820.78 1485467.93 22-MAY-14:00 14.75 11.67 0.00 0.00 01-MAY-00:10
June 72850.43 1314633.95 13-JUN-16:00 17.33 6.70 0.00 0.00 01-JUN-00:10
July 110278.46 1473377.04 21-JUL-10:30 14.80 10.14 0.00 0.00 01-JUL-00:10
August 136655.25 1356150.45 21-AUG-12:30 13.75 10.14 0.00 0.00 01-AUG-00:10
September 79125.80 1726319.56 12-SEP-15:40 15.05 12.20 0.00 0.00 01-SEP-00:10
October 14590.76 526518.74 05-OCT-14:05 18.89 6.70 0.00 0.00 01-OCT-00:10
November 1010.69 41475.11 24-NOV-12:00 12.38 6.70 0.00 0.00 01-NOV-00:10
December 1361.18 32548.59 18-DEC-14:10 17.92 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 38964.29         0.00    
Minimum of Months 511.08 32548.59   12.38 6.70 0.00 0.00  
Maximum of Months 136655.25 1726319.56   20.78 12.20 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 16696.42 31024.35 19-JAN-16:30 18.97 18.33 0.00 0.00 01-JAN-00:05
February 47041.22 63937.41 19-FEB-17:10 19.65 18.33 0.00 0.00 01-FEB-00:10
March 77927.67 109715.28 31-MAR-23:40 20.60 18.33 0.00 0.00 01-MAR-00:10
April 147668.94 1073476.21 30-APR-17:40 40.08 28.76 0.00 0.00 01-APR-00:10
May 31780.32 421997.78 22-MAY-15:00 26.99 24.87 0.00 0.00 01-MAY-00:10
June 88774.10 929849.15 13-JUN-17:00 37.23 30.02 0.00 0.00 01-JUN-00:10
July 194020.89 1302727.63 22-JUL-18:00 44.62 34.35 0.00 0.00 01-JUL-00:10
August 382673.48 1275154.28 14-AUG-17:10 44.07 32.08 0.00 0.00 01-AUG-00:10
September 42290.27 331885.44 13-SEP-16:00 25.15 23.63 0.00 0.00 01-SEP-00:10
October 50664.31 128109.59 07-OCT-15:00 20.97 19.57 0.00 0.00 01-OCT-00:10
November 74311.44 110034.75 24-NOV-12:00 20.60 18.33 0.00 0.00 01-NOV-00:10
December 98822.20 144025.92 23-DEC-11:00 21.30 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 105037.37         0.00    
Minimum of Months 16696.42 31024.35   18.97 18.33 0.00 0.00  
Maximum of Months 382673.48 1302727.63   44.62 34.35 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.37 57.37 15864.95 53217.75 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 56.06 56.06 16048.11 53302.66 24-FEB-12:10
March 0.00 0.00 01-MAR-00:10 56.07 56.07 16857.68 53240.51 01-MAR-12:15
April 0.00 0.00 01-APR-00:10 56.08 56.08 15609.42 52438.00 03-APR-11:30
May 0.00 0.00 01-MAY-00:10 56.92 56.92 15691.24 51305.71 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 56.69 56.69 15641.57 49909.71 01-JUN-11:10
July 0.00 0.00 01-JUL-00:10 56.33 56.33 14234.88 48612.93 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 57.27 57.27 15335.71 48008.43 01-AUG-11:10
September 0.00 0.00 01-SEP-00:10 56.75 56.75 14566.16 48663.06 29-SEP-11:10
October 0.00 0.00 01-OCT-00:10 56.65 56.65 14826.84 49880.81 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 56.11 56.11 15399.27 51262.81 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 57.14 57.14 15250.43 52461.64 29-DEC-12:40
                 
Annual Sum or Average 0.00         15440.42    
Minimum of Months 0.00 0.00   56.06 56.06 14234.88 48008.43  
Maximum of Months 0.00 0.00   57.37 57.37 16857.68 53302.66  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 113.58 42293.93 20-JAN-12:10 21.33 20.62 1536.68 92485.09 07-JAN-06:50
February 488.34 158379.59 09-FEB-15:40 21.95 21.10 3027.23 110925.83 17-FEB-06:40
March 392.25 124710.98 30-MAR-14:10 21.77 21.09 2743.01 99859.53 27-MAR-05:40
April 23866.70 791042.33 28-APR-15:00 25.34 21.10 768.61 76077.56 15-APR-07:50
May 27471.67 1738583.21 22-MAY-14:50 25.76 21.39 575.49 75517.71 05-MAY-08:70
June 90045.94 1968417.14 13-JUN-16:00 26.38 22.33 446.95 52603.75 23-JUN-18:30
July 133012.20 1789703.76 21-JUL-10:50 25.90 21.45 681.63 53791.11 03-JUL-09:50
August 163126.39 1767484.52 28-AUG-15:10 25.84 21.27 475.04 67482.86 30-AUG-05:50
September 93630.98 1742505.80 13-SEP-14:00 25.77 21.47 754.28 77323.35 21-SEP-05:50
October 15854.19 591135.98 05-OCT-14:10 24.27 21.10 1055.19 90880.44 23-OCT-05:40
November 152.61 31760.23 27-NOV-14:30 21.27 20.54 2236.11 97315.72 17-NOV-06:40
December 228.45 37654.62 26-DEC-12:00 21.30 20.46 4144.02 94909.94 04-DEC-07:00
                 
Annual Sum or Average 46001.97         1530.09    
Minimum of Months 113.58 31760.23   21.27 20.46 446.95 52603.75  
Maximum of Months 163126.39 1968417.14   26.38 22.33 4144.02 110925.83  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.127142E+11 0.00 0.130785E+10 0.309532E+10 0.00 0.00
February 0.807808E+10 0.00 0.329405E+10 0.342633E+10 0.00 0.00
March 0.557062E+10 0.00 0.210367E+10 0.449940E+10 0.00 0.00
April 0.941385E+09 0.00 0.487220E+10 0.878042E+10 0.00 0.00
May 0.794923E+09 0.00 0.528758E+10 0.667433E+10 0.00 0.00
June 24002947.26 0.00 0.168488E+11 0.870881E+10 0.00 0.00
July 6058.46 0.00 0.285907E+11 0.103658E+11 0.00 0.00
August 16304.25 0.00 0.379601E+11 0.122569E+11 0.00 0.00
September 0.152410E+09 0.00 0.176311E+11 0.741836E+10 0.00 0.00
October 0.159240E+10 0.00 0.317749E+10 0.523120E+10 0.00 0.00
November 0.463423E+10 0.00 0.254749E+10 0.407440E+10 0.00 0.00
December 0.905202E+10 0.00 0.365459E+10 0.373438E+10 0.00 0.00
             
Annual Sum or Average 0.435543E+11 0.00 0.127276E+12 0.782657E+11 0.00 0.00
Minimum of Months 6058.46 0.00 0.130785E+10 0.309532E+10 0.00 0.00
Maximum of Months 0.127142E+11 0.00 0.379601E+11 0.122569E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.202682E+12 0.00 0.143477E+09 0.218981E+11 0.00 0.00
February 0.144980E+12 0.00 0.960991E+09 0.215706E+11 0.00 0.00
March 0.118296E+12 0.00 0.134972E+10 0.241866E+11 0.00 0.00
April 0.246044E+11 0.00 0.458518E+11 0.470997E+11 0.00 0.00
May 0.151337E+11 0.00 0.512857E+11 0.483165E+11 0.00 0.00
June 0.141481E+10 0.00 0.143263E+12 0.596900E+11 0.00 0.00
July 0.230665E+09 0.00 0.223910E+12 0.652784E+11 0.00 0.00
August 76029155.69 0.00 0.281427E+12 0.727314E+11 0.00 0.00
September 0.278104E+10 0.00 0.157902E+12 0.565410E+11 0.00 0.00
October 0.323056E+11 0.00 0.352475E+11 0.318463E+11 0.00 0.00
November 0.110602E+12 0.00 0.100418E+09 0.219267E+11 0.00 0.00
December 0.226500E+12 0.00 26057.36 0.206035E+11 0.00 0.00
             
Annual Sum or Average 0.879606E+12 0.00 0.941442E+12 0.491689E+12 0.00 0.00
Minimum of Months 76029155.69 0.00 26057.36 0.206035E+11 0.00 0.00
Maximum of Months 0.226500E+12 0.00 0.281427E+12 0.727314E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.367428E+11 0.00 0.00 0.234478E+10 0.00 0.00
February 0.264002E+11 0.00 0.00 0.209638E+10 0.00 0.00
March 0.209579E+11 0.00 0.00 0.228706E+10 0.00 0.00
April 0.451295E+10 0.00 0.335265E+10 0.359200E+10 0.00 0.00
May 0.298211E+10 0.00 0.448560E+10 0.397058E+10 0.00 0.00
June 0.222237E+09 0.00 0.144884E+11 0.523877E+10 0.00 0.00
July 22250764.06 0.00 0.229075E+11 0.584772E+10 0.00 0.00
August 16488851.31 0.00 0.269787E+11 0.612865E+10 0.00 0.00
September 0.684927E+09 0.00 0.138531E+11 0.434969E+10 0.00 0.00
October 0.863763E+10 0.00 0.533048E+09 0.247959E+10 0.00 0.00
November 0.227569E+11 0.00 3323788.29 0.213872E+10 0.00 0.00
December 0.410906E+11 0.00 4841.28 0.238177E+10 0.00 0.00
             
Annual Sum or Average 0.165027E+12 0.00 0.866022E+11 0.428557E+11 0.00 0.00
Minimum of Months 16488851.31 0.00 0.00 0.209638E+10 0.00 0.00
Maximum of Months 0.410906E+11 0.00 0.269787E+11 0.612865E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 16401.68 0.122785E+11 0.00 0.00
February 0.00 0.00 5125.69 0.108530E+11 0.00 0.00
March 91.27 0.00 635186.87 0.128310E+11 0.00 0.00
April 0.00 0.00 0.638597E+09 0.117230E+11 0.00 0.00
May 261.87 0.00 0.201997E+10 0.124819E+11 0.00 0.00
June 0.00 0.00 0.734464E+10 0.122941E+11 0.00 0.00
July 0.00 0.00 0.122366E+11 0.119191E+11 0.00 0.00
August 302.23 0.00 0.159113E+11 0.131924E+11 0.00 0.00
September 180.22 0.00 0.758485E+10 0.119905E+11 0.00 0.00
October 0.00 0.00 0.153262E+09 0.122153E+11 0.00 0.00
November 195.33 0.00 21014559.01 0.117633E+11 0.00 0.00
December 0.00 0.00 0.00 0.118359E+11 0.00 0.00
             
Annual Sum or Average 1030.91 0.00 0.459109E+11 0.145378E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.108530E+11 0.00 0.00
Maximum of Months 302.23 0.00 0.159113E+11 0.131924E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.668354E+10 0.173572E+12 0.00 28.03
February 0.00 0.00 0.947925E+10 0.205518E+12 0.00 43.19
March 0.00 0.00 0.160018E+11 0.295744E+12 0.00 72.74
April 0.00 0.00 0.791780E+11 0.326519E+12 0.00 80.49
May 0.00 0.00 0.497965E+10 0.137371E+12 0.00 14.67
June 0.00 0.00 0.301471E+11 0.113389E+12 0.00 4.85
July 0.00 0.00 0.157839E+12 0.139220E+12 0.00 3.74
August 0.00 0.00 0.496761E+12 0.206750E+12 0.00 5.46
September 0.00 0.00 0.383490E+10 0.109325E+12 0.00 5.40
October 0.00 0.00 0.605734E+10 0.156907E+12 0.00 21.86
November 0.00 0.00 0.117438E+11 0.228695E+12 0.00 49.26
December 0.00 0.00 0.208204E+11 0.340499E+12 0.00 88.96
             
Annual Sum or Average 0.00 0.00 0.843526E+12 0.243351E+13 0.00 418.68
Minimum of Months 0.00 0.00 0.383490E+10 0.109325E+12 0.00 3.74
Maximum of Months 0.00 0.00 0.496761E+12 0.340499E+12 0.00 88.96



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.507598E+10 0.243439E+10 0.00 0.00
February 0.00 0.00 0.104812E+11 0.318262E+10 0.00 0.00
March 0.00 0.00 0.179475E+11 0.450870E+10 0.00 0.00
April 0.00 0.00 0.237754E+11 0.532730E+10 0.00 0.00
May 0.00 0.00 0.644002E+10 0.264981E+10 0.00 0.00
June 0.00 0.00 0.125340E+11 0.358112E+10 0.00 0.00
July 0.00 0.00 0.192441E+11 0.470976E+10 0.00 0.00
August 0.00 0.00 0.251806E+11 0.565738E+10 0.00 0.00
September 0.00 0.00 0.644287E+10 0.259259E+10 0.00 0.00
October 0.00 0.00 0.122163E+11 0.358371E+10 0.00 0.00
November 0.00 0.00 0.173629E+11 0.433504E+10 0.00 0.00
December 0.00 0.00 0.236454E+11 0.536964E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.180346E+12 0.479321E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.507598E+10 0.243439E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.251806E+11 0.565738E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.243900E+11 0.191125E+11 0.00 0.00
February 0.00 0.00 0.806252E+11 0.273032E+11 0.00 0.00
March 0.00 0.00 0.153238E+12 0.403862E+11 0.00 0.00
April 0.00 0.00 0.219120E+12 0.498426E+11 0.00 0.00
May 0.00 0.00 0.536019E+11 0.240681E+11 0.00 0.00
June 0.00 0.00 0.114528E+12 0.334879E+11 0.00 0.00
July 0.00 0.00 0.178989E+12 0.443732E+11 0.00 0.00
August 0.00 0.00 0.236421E+12 0.535638E+11 0.00 0.00
September 0.00 0.00 0.543594E+11 0.236563E+11 0.00 0.00
October 0.00 0.00 0.101562E+12 0.319237E+11 0.00 0.00
November 0.00 0.00 0.143790E+12 0.381520E+11 0.00 0.00
December 0.00 0.00 0.194525E+12 0.467915E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.155515E+13 0.432661E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.243900E+11 0.191125E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.236421E+12 0.535638E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.601895E+09 0.158225E+10 0.00 0.00
February 0.00 0.00 0.588022E+10 0.238188E+10 0.00 0.00
March 0.00 0.00 0.133113E+11 0.374632E+10 0.00 0.00
April 0.00 0.00 0.209730E+11 0.487137E+10 0.00 0.00
May 0.00 0.00 0.450035E+10 0.228035E+10 0.00 0.00
June 0.00 0.00 0.110634E+11 0.330924E+10 0.00 0.00
July 0.00 0.00 0.175790E+11 0.441445E+10 0.00 0.00
August 0.00 0.00 0.233089E+11 0.533552E+10 0.00 0.00
September 0.00 0.00 0.464848E+10 0.225322E+10 0.00 0.00
October 0.00 0.00 0.827970E+10 0.290903E+10 0.00 0.00
November 0.00 0.00 0.121509E+11 0.348909E+10 0.00 0.00
December 0.00 0.00 0.171255E+11 0.435029E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.139423E+12 0.409230E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.601895E+09 0.158225E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.233089E+11 0.533552E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.309532E+10 0.130785E+10 0.127142E+11 0.00 0.00 0.00 0.00 0.00
February 0.342633E+10 0.329405E+10 0.807808E+10 0.00 0.00 0.00 0.00 0.00
March 0.449940E+10 0.210367E+10 0.557062E+10 0.00 0.00 0.00 0.00 0.00
April 0.878042E+10 0.487220E+10 0.941385E+09 0.00 0.00 0.00 0.00 0.00
May 0.667433E+10 0.528758E+10 0.794923E+09 0.00 0.00 0.00 0.00 0.00
June 0.870881E+10 0.168488E+11 24002947.26 0.00 0.00 0.00 0.00 0.00
July 0.103658E+11 0.285907E+11 6058.46 0.00 0.00 0.00 0.00 0.00
August 0.122569E+11 0.379601E+11 16304.25 0.00 0.00 0.00 0.00 0.00
September 0.741836E+10 0.176311E+11 0.152410E+09 0.00 0.00 0.00 0.00 0.00
October 0.523120E+10 0.317749E+10 0.159240E+10 0.00 0.00 0.00 0.00 0.00
November 0.407440E+10 0.254749E+10 0.463423E+10 0.00 0.00 0.00 0.00 0.00
December 0.373438E+10 0.365459E+10 0.905202E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.782657E+11 0.127276E+12 0.435543E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.309532E+10 0.130785E+10 6058.46 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122569E+11 0.379601E+11 0.127142E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.218981E+11 0.143477E+09 0.202682E+12 0.00 0.00 0.00 0.00 0.00
February 0.215706E+11 0.960991E+09 0.144980E+12 0.00 0.00 0.00 0.00 0.00
March 0.241866E+11 0.134972E+10 0.118296E+12 0.00 0.00 0.00 0.00 0.00
April 0.470997E+11 0.458518E+11 0.246044E+11 0.00 0.00 0.00 0.00 0.00
May 0.483165E+11 0.512857E+11 0.151337E+11 0.00 0.00 0.00 0.00 0.00
June 0.596900E+11 0.143263E+12 0.141481E+10 0.00 0.00 0.00 0.00 0.00
July 0.652784E+11 0.223910E+12 0.230665E+09 0.00 0.00 0.00 0.00 0.00
August 0.727314E+11 0.281427E+12 76029155.69 0.00 0.00 0.00 0.00 0.00
September 0.565410E+11 0.157902E+12 0.278104E+10 0.00 0.00 0.00 0.00 0.00
October 0.318463E+11 0.352475E+11 0.323056E+11 0.00 0.00 0.00 0.00 0.00
November 0.219267E+11 0.100418E+09 0.110602E+12 0.00 0.00 0.00 0.00 0.00
December 0.206035E+11 26057.36 0.226500E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.491689E+12 0.941442E+12 0.879606E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.206035E+11 26057.36 76029155.69 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.727314E+11 0.281427E+12 0.226500E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.234478E+10 0.00 0.367428E+11 0.00 0.00 0.00 0.00 0.00
February 0.209638E+10 0.00 0.264002E+11 0.00 0.00 0.00 0.00 0.00
March 0.228706E+10 0.00 0.209579E+11 0.00 0.00 0.00 0.00 0.00
April 0.359200E+10 0.335265E+10 0.451295E+10 0.00 0.00 0.00 0.00 0.00
May 0.397058E+10 0.448560E+10 0.298211E+10 0.00 0.00 0.00 0.00 0.00
June 0.523877E+10 0.144884E+11 0.222237E+09 0.00 0.00 0.00 0.00 0.00
July 0.584772E+10 0.229075E+11 22250764.06 0.00 0.00 0.00 0.00 0.00
August 0.612865E+10 0.269787E+11 16488851.31 0.00 0.00 0.00 0.00 0.00
September 0.434969E+10 0.138531E+11 0.684927E+09 0.00 0.00 0.00 0.00 0.00
October 0.247959E+10 0.533048E+09 0.863763E+10 0.00 0.00 0.00 0.00 0.00
November 0.213872E+10 3323788.29 0.227569E+11 0.00 0.00 0.00 0.00 0.00
December 0.238177E+10 4841.28 0.410906E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.428557E+11 0.866022E+11 0.165027E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.209638E+10 0.00 16488851.31 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.612865E+10 0.269787E+11 0.410906E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.122785E+11 16401.68 0.00 0.00 0.00 0.00 0.00 0.00
February 0.108530E+11 5125.69 0.00 0.00 0.00 0.00 0.00 0.00
March 0.128310E+11 635186.87 91.27 0.00 0.00 0.00 0.00 0.00
April 0.117230E+11 0.638597E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.124819E+11 0.201997E+10 261.87 0.00 0.00 0.00 0.00 0.00
June 0.122941E+11 0.734464E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.119191E+11 0.122366E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.131924E+11 0.159113E+11 302.23 0.00 0.00 0.00 0.00 0.00
September 0.119905E+11 0.758485E+10 180.22 0.00 0.00 0.00 0.00 0.00
October 0.122153E+11 0.153262E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.117633E+11 21014559.01 195.33 0.00 0.00 0.00 0.00 0.00
December 0.118359E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.145378E+12 0.459109E+11 1030.91 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.108530E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131924E+11 0.159113E+11 302.23 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.952024E+11 0.367622E+10 0.00 0.00 0.00 0.750248E+11 0.00 0.00
February 0.859892E+11 0.606086E+10 0.00 0.00 0.00 0.115590E+12 0.00 0.00
March 0.952024E+11 0.110060E+11 0.00 0.00 0.00 0.194670E+12 0.00 0.00
April 0.921313E+11 0.611624E+11 0.00 0.00 0.00 0.215402E+12 0.00 0.00
May 0.952024E+11 0.224903E+10 0.00 0.00 0.00 0.392613E+11 0.00 0.00
June 0.921313E+11 0.219388E+11 0.00 0.00 0.00 0.129907E+11 0.00 0.00
July 0.952024E+11 0.123882E+12 0.00 0.00 0.00 0.100155E+11 0.00 0.00
August 0.952024E+11 0.399893E+12 0.00 0.00 0.00 0.146142E+11 0.00 0.00
September 0.921313E+11 0.117022E+10 0.00 0.00 0.00 0.144638E+11 0.00 0.00
October 0.952024E+11 0.312596E+10 0.00 0.00 0.00 0.585102E+11 0.00 0.00
November 0.921313E+11 0.761263E+10 0.00 0.00 0.00 0.131839E+12 0.00 0.00
December 0.952024E+11 0.146531E+11 0.00 0.00 0.00 0.238058E+12 0.00 0.00
                 
Annual Sum or Average 0.112093E+13 0.656430E+12 0.00 0.00 0.00 0.112044E+13 0.00 0.00
Minimum of Months 0.859892E+11 0.117022E+10 0.00 0.00 0.00 0.100155E+11 0.00 0.00
Maximum of Months 0.952024E+11 0.399893E+12 0.00 0.00 0.00 0.238058E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.149644E+10 0.413802E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.135162E+10 0.865022E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149644E+10 0.149352E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144816E+10 0.198963E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149644E+10 0.528664E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.144816E+10 0.104010E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.149644E+10 0.160308E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.149644E+10 0.210197E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.144816E+10 0.529844E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149644E+10 0.101291E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144816E+10 0.144760E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149644E+10 0.197722E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176193E+11 0.150034E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.135162E+10 0.413802E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149644E+10 0.210197E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.143772E+11 0.196547E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129859E+11 0.663079E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143772E+11 0.127229E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139135E+11 0.183191E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143772E+11 0.439110E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139135E+11 0.949536E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143772E+11 0.148993E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143772E+11 0.197234E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139135E+11 0.446166E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143772E+11 0.840157E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139135E+11 0.119552E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143772E+11 0.162111E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169280E+12 0.129177E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129859E+11 0.196547E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143772E+11 0.197234E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.145762E+10 0.477263E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.131656E+10 0.481490E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145762E+10 0.110225E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.141060E+10 0.175122E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.145762E+10 0.367762E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141060E+10 0.916481E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.145762E+10 0.146222E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145762E+10 0.194310E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.141060E+10 0.380586E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145762E+10 0.682829E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.141060E+10 0.100724E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.145762E+10 0.142328E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.171623E+11 0.115662E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.131656E+10 0.477263E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145762E+10 0.194310E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.309532E+10 0.127142E+11 0.130785E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342633E+10 0.807808E+10 0.329405E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.449940E+10 0.557062E+10 0.210367E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.878042E+10 0.941385E+09 0.487220E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.667433E+10 0.794923E+09 0.528758E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.870881E+10 24002947.26 0.168488E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.103658E+11 6058.46 0.285907E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.122569E+11 16304.25 0.379601E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.741836E+10 0.152410E+09 0.176311E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.523120E+10 0.159240E+10 0.317749E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.407440E+10 0.463423E+10 0.254749E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.373438E+10 0.905202E+10 0.365459E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.782657E+11 0.435543E+11 0.127276E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.309532E+10 6058.46 0.130785E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122569E+11 0.127142E+11 0.379601E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.218981E+11 0.202682E+12 0.143477E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.215706E+11 0.144980E+12 0.960991E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.241866E+11 0.118296E+12 0.134972E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.470997E+11 0.246044E+11 0.458518E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.483165E+11 0.151337E+11 0.512857E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.596900E+11 0.141481E+10 0.143263E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.652784E+11 0.230665E+09 0.223910E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.727314E+11 76029155.69 0.281427E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.565410E+11 0.278104E+10 0.157902E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.318463E+11 0.323056E+11 0.352475E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.219267E+11 0.110602E+12 0.100418E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.206035E+11 0.226500E+12 26057.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.491689E+12 0.879606E+12 0.941442E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.206035E+11 76029155.69 26057.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.727314E+11 0.226500E+12 0.281427E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.234478E+10 0.367428E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.209638E+10 0.264002E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.228706E+10 0.209579E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.359200E+10 0.451295E+10 0.335265E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.397058E+10 0.298211E+10 0.448560E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.523877E+10 0.222237E+09 0.144884E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.584772E+10 22250764.06 0.229075E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.612865E+10 16488851.31 0.269787E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.434969E+10 0.684927E+09 0.138531E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.247959E+10 0.863763E+10 0.533048E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.213872E+10 0.227569E+11 3323788.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.238177E+10 0.410906E+11 4841.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.428557E+11 0.165027E+12 0.866022E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.209638E+10 16488851.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.612865E+10 0.410906E+11 0.269787E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.122785E+11 0.00 16401.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.108530E+11 0.00 5125.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.128310E+11 91.27 635186.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.117230E+11 0.00 0.638597E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.124819E+11 261.87 0.201997E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.122941E+11 0.00 0.734464E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.119191E+11 0.00 0.122366E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.131924E+11 302.23 0.159113E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.119905E+11 180.22 0.758485E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.122153E+11 0.00 0.153262E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.117633E+11 195.33 21014559.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.118359E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.145378E+12 1030.91 0.459109E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.108530E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131924E+11 302.23 0.159113E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.952024E+11 0.00 0.668354E+10 0.00 0.300732E+10 0.00 0.00 0.00 0.753626E+11 0.00 0.00 0.00
February 0.859892E+11 0.00 0.947925E+10 0.00 0.341839E+10 0.00 0.00 0.00 0.116110E+12 0.00 0.00 0.00
March 0.952024E+11 0.00 0.160018E+11 0.00 0.499577E+10 0.00 0.00 0.00 0.195546E+12 0.00 0.00 0.00
April 0.921313E+11 0.00 0.791780E+11 0.00 0.180156E+11 0.00 0.00 0.00 0.216372E+12 0.00 0.00 0.00
May 0.952024E+11 0.00 0.497965E+10 0.00 0.273062E+10 0.00 0.00 0.00 0.394380E+11 0.00 0.00 0.00
June 0.921313E+11 0.00 0.301471E+11 0.00 0.820831E+10 0.00 0.00 0.00 0.130491E+11 0.00 0.00 0.00
July 0.952024E+11 0.00 0.157839E+12 0.00 0.339567E+11 0.00 0.00 0.00 0.100606E+11 0.00 0.00 0.00
August 0.952024E+11 0.00 0.496761E+12 0.00 0.968681E+11 0.00 0.00 0.00 0.146800E+11 0.00 0.00 0.00
September 0.921313E+11 0.00 0.383490E+10 0.00 0.266467E+10 0.00 0.00 0.00 0.145289E+11 0.00 0.00 0.00
October 0.952024E+11 0.00 0.605734E+10 0.00 0.293138E+10 0.00 0.00 0.00 0.587735E+11 0.00 0.00 0.00
November 0.921313E+11 0.00 0.117438E+11 0.00 0.413121E+10 0.00 0.00 0.00 0.132432E+12 0.00 0.00 0.00
December 0.952024E+11 0.00 0.208204E+11 0.00 0.616733E+10 0.00 0.00 0.00 0.239129E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.112093E+13 0.00 0.843526E+12 0.00 0.187095E+12 0.00 0.00 0.00 0.112548E+13 0.00 0.00 0.00
Minimum of Months 0.859892E+11 0.00 0.383490E+10 0.00 0.266467E+10 0.00 0.00 0.00 0.100606E+11 0.00 0.00 0.00
Maximum of Months 0.952024E+11 0.00 0.496761E+12 0.00 0.968681E+11 0.00 0.00 0.00 0.239129E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.149644E+10 0.00 0.507598E+10 0.00 0.937960E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.135162E+10 0.00 0.104812E+11 0.00 0.183100E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149644E+10 0.00 0.179475E+11 0.00 0.301227E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144816E+10 0.00 0.237754E+11 0.00 0.387913E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149644E+10 0.00 0.644002E+10 0.00 0.115338E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.144816E+10 0.00 0.125340E+11 0.00 0.213296E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.149644E+10 0.00 0.192441E+11 0.00 0.321333E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.149644E+10 0.00 0.251806E+11 0.00 0.416095E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.144816E+10 0.00 0.644287E+10 0.00 0.114443E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149644E+10 0.00 0.122163E+11 0.00 0.208727E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144816E+10 0.00 0.173629E+11 0.00 0.288688E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149644E+10 0.00 0.236454E+11 0.00 0.387321E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.176193E+11 0.00 0.180346E+12 0.00 0.303128E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.135162E+10 0.00 0.507598E+10 0.00 0.937960E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149644E+10 0.00 0.251806E+11 0.00 0.416095E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.143772E+11 0.00 0.243900E+11 0.00 0.473523E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129859E+11 0.00 0.806252E+11 0.00 0.143173E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143772E+11 0.00 0.153238E+12 0.00 0.260089E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139135E+11 0.00 0.219120E+12 0.00 0.359291E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143772E+11 0.00 0.536019E+11 0.00 0.969085E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139135E+11 0.00 0.114528E+12 0.00 0.195744E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143772E+11 0.00 0.178989E+12 0.00 0.299959E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143772E+11 0.00 0.236421E+12 0.00 0.391865E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139135E+11 0.00 0.543594E+11 0.00 0.974287E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143772E+11 0.00 0.101562E+12 0.00 0.175465E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139135E+11 0.00 0.143790E+12 0.00 0.242385E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143772E+11 0.00 0.194525E+12 0.00 0.324142E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.169280E+12 0.00 0.155515E+13 0.00 0.263380E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129859E+11 0.00 0.243900E+11 0.00 0.473523E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143772E+11 0.00 0.236421E+12 0.00 0.391865E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.145762E+10 0.00 0.601895E+09 0.00 0.124632E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.131656E+10 0.00 0.588022E+10 0.00 0.106532E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145762E+10 0.00 0.133113E+11 0.00 0.228870E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.141060E+10 0.00 0.209730E+11 0.00 0.346077E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.145762E+10 0.00 0.450035E+10 0.00 0.822725E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141060E+10 0.00 0.110634E+11 0.00 0.189864E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.145762E+10 0.00 0.175790E+11 0.00 0.295683E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145762E+10 0.00 0.233089E+11 0.00 0.387789E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.141060E+10 0.00 0.464848E+10 0.00 0.842621E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145762E+10 0.00 0.827970E+10 0.00 0.145141E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.141060E+10 0.00 0.121509E+11 0.00 0.207849E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.145762E+10 0.00 0.171255E+11 0.00 0.289267E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.171623E+11 0.00 0.139423E+12 0.00 0.237607E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.131656E+10 0.00 0.601895E+09 0.00 0.124632E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145762E+10 0.00 0.233089E+11 0.00 0.387789E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.120306E+10 0.00 0.00 91691429.17 0.00 0.00 0.587769E+11 0.00 0.48
February 0.420314E+09 0.00 0.00 89247946.00 0.00 0.00 0.545049E+11 0.00 0.50
March 0.357062E+09 0.00 0.00 0.101331E+09 0.00 0.00 0.660840E+11 0.00 0.59
April 0.337271E+09 0.00 0.00 0.108699E+09 0.00 0.00 0.647992E+11 0.00 0.80
May 0.297107E+09 0.00 0.00 0.106934E+09 0.00 0.00 0.644282E+11 0.00 0.81
June 0.222753E+09 1639448.19 0.00 0.108520E+09 0.00 0.00 0.612851E+11 0.00 1.06
July 0.270734E+09 53536792.36 0.00 0.109937E+09 6932314.29 0.00 0.570448E+11 0.00 1.13
August 0.240574E+09 0.00 0.00 0.125657E+09 0.00 0.00 0.605520E+11 0.00 1.35
September 0.316921E+09 0.00 0.00 0.110653E+09 0.00 0.00 0.586662E+11 0.00 1.09
October 0.317523E+09 0.00 0.00 0.110252E+09 0.00 0.00 0.664466E+11 0.00 0.78
November 0.312806E+09 0.00 0.00 0.105924E+09 0.00 0.00 0.637377E+11 0.00 0.62
December 0.566059E+09 0.00 0.00 0.103466E+09 0.00 0.00 0.615762E+11 0.00 0.50
                   
Annual Sum or Average 0.486219E+10 55176240.54 0.00 0.127231E+10 6932314.29 0.00 0.737902E+12 0.00 0.81
Minimum of Months 0.222753E+09 0.00 0.00 89247946.00 0.00 0.00 0.545049E+11 0.00 0.48
Maximum of Months 0.120306E+10 53536792.36 0.00 0.125657E+09 6932314.29 0.00 0.664466E+11 0.00 1.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.338604E+10 0.00 0.00 56659861.48 0.00 0.00 0.459295E+11 0.00 0.37
February 0.160917E+10 0.00 0.00 64600020.22 0.00 0.00 0.425980E+11 0.00 0.38
March 0.130733E+10 0.00 0.00 83022575.23 0.00 0.00 0.547071E+11 0.00 0.47
April 0.414938E+10 0.00 0.00 97923280.35 0.00 0.00 0.566176E+11 0.00 0.71
May 0.386707E+10 0.00 0.00 84484858.10 0.00 0.00 0.499663E+11 0.00 0.64
June 0.365053E+10 3817385.41 0.00 92835848.63 58661273.78 0.00 0.504306E+11 0.00 0.86
July 0.663045E+10 22040138.74 0.00 94085538.45 9266926.61 0.00 0.462747E+11 0.00 0.95
August 0.706104E+10 0.00 0.00 0.111299E+09 0.00 0.00 0.487103E+11 0.00 1.10
September 0.380642E+10 0.00 0.00 85062303.22 0.00 0.00 0.427895E+11 0.00 0.80
October 0.177948E+10 0.00 0.00 82967920.78 0.00 0.00 0.492746E+11 0.00 0.56
November 0.163190E+10 0.00 0.00 79240548.32 0.00 0.00 0.491234E+11 0.00 0.46
December 0.152527E+10 0.00 0.00 76866297.04 0.00 0.00 0.489514E+11 0.00 0.39
                   
Annual Sum or Average 0.404041E+11 25857524.16 0.00 0.100905E+10 67928200.39 0.00 0.585373E+12 0.00 0.64
Minimum of Months 0.130733E+10 0.00 0.00 56659861.48 0.00 0.00 0.425980E+11 0.00 0.37
Maximum of Months 0.706104E+10 22040138.74 0.00 0.111299E+09 58661273.78 0.00 0.566176E+11 0.00 1.10



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.250316E+12 0.00 0.00 0.120801E+09 0.00 0.00 0.133878E+12 0.00 0.30
February 0.187265E+12 0.00 0.00 0.162875E+09 0.00 0.00 0.156472E+12 0.00 0.31
March 0.164496E+12 0.00 0.00 0.273362E+09 0.00 0.00 0.244163E+12 0.00 0.35
April 0.511437E+11 0.00 0.00 0.489602E+09 0.00 0.00 0.340914E+12 0.00 0.46
May 0.639429E+11 0.00 0.00 0.534753E+09 0.00 0.00 0.353481E+12 0.00 0.50
June 0.301282E+11 32345311.82 0.00 0.638674E+09 0.616502E+09 0.00 0.373276E+12 0.00 0.65
July 0.426187E+11 0.221498E+09 0.00 0.612449E+09 0.106241E+09 0.00 0.322140E+12 0.00 0.68
August 0.323763E+11 0.00 0.00 0.711152E+09 0.00 0.00 0.336912E+12 0.00 0.76
September 0.439002E+11 0.00 0.00 0.576817E+09 0.00 0.00 0.316463E+12 0.00 0.63
October 0.994036E+11 0.00 0.00 0.367178E+09 0.00 0.00 0.250698E+12 0.00 0.38
November 0.170216E+12 0.00 0.00 0.196354E+09 0.00 0.00 0.176632E+12 0.00 0.32
December 0.275364E+12 0.00 0.00 51139356.01 0.00 0.00 0.852294E+11 0.00 0.29
                   
Annual Sum or Average 0.141117E+13 0.253844E+09 0.00 0.473516E+10 0.722743E+09 0.00 0.309026E+13 0.00 0.47
Minimum of Months 0.301282E+11 0.00 0.00 51139356.01 0.00 0.00 0.852294E+11 0.00 0.29
Maximum of Months 0.275364E+12 0.221498E+09 0.00 0.711152E+09 0.616502E+09 0.00 0.373276E+12 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.305699E+11 0.00 0.00 217765.13 0.00 0.183932E+10 0.524711E+09 0.00 0.29
February 0.279916E+11 0.00 0.00 245451.00 0.00 0.673443E+09 0.849272E+09 0.00 0.29
March 0.307876E+11 0.00 0.00 1600422.31 0.00 0.441799E+09 0.292702E+10 0.00 0.32
April 0.132028E+11 3453082.58 0.00 24757750.51 0.00 0.00 0.206031E+11 0.00 0.41
May 0.124007E+11 0.00 0.00 32005285.57 0.00 0.00 0.248967E+11 0.00 0.46
June 0.696189E+10 775971.04 0.00 49096585.76 45924321.22 0.00 0.315431E+11 0.00 0.62
July 0.703634E+10 12777864.76 0.00 50820540.11 4977665.66 0.00 0.284502E+11 0.00 0.66
August 0.653760E+10 0.00 0.00 53676657.48 0.00 0.00 0.282538E+11 0.00 0.71
September 0.104553E+11 0.00 0.00 33155730.66 0.00 0.00 0.203405E+11 0.00 0.55
October 0.211435E+11 0.00 0.00 6355509.92 0.00 0.258036E+09 0.657069E+10 0.00 0.33
November 0.266097E+11 0.00 0.00 655733.67 0.00 0.779043E+09 0.117593E+10 0.00 0.30
December 0.294705E+11 0.00 0.00 0.00 0.00 0.190402E+10 0.00 0.00 0.29
                   
Annual Sum or Average 0.223167E+12 17006918.39 0.00 0.252587E+09 50901986.88 0.589566E+10 0.166135E+12 0.00 0.44
Minimum of Months 0.653760E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.307876E+11 12777864.76 0.00 53676657.48 45924321.22 0.190402E+10 0.315431E+11 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.409145E+10 0.00 0.00 313036.22 0.00 16471820.82 0.395031E+09 0.00 0.27
February 0.327640E+10 0.00 0.00 737254.23 0.00 0.00 0.641781E+09 0.00 0.27
March 0.267255E+10 0.00 0.00 2831332.84 0.00 0.00 0.222024E+10 0.00 0.33
April 0.150472E+10 0.00 0.00 7216534.58 0.00 0.00 0.498047E+10 0.00 0.63
May 0.136458E+10 0.00 0.00 7350956.27 0.00 0.00 0.491527E+10 0.00 0.62
June 0.707401E+09 1863933.78 0.00 11341062.09 7063518.94 0.00 0.662712E+10 0.00 0.98
July 0.977351E+09 5136493.21 0.00 12054359.84 1163510.78 0.00 0.629225E+10 0.00 1.09
August 0.107861E+10 0.00 0.00 12488087.61 0.00 0.00 0.594313E+10 0.00 1.16
September 0.148742E+10 0.00 0.00 6483580.22 0.00 0.00 0.359882E+10 0.00 0.73
October 0.208686E+10 0.00 0.00 3287763.90 0.00 0.00 0.248567E+10 0.00 0.41
November 0.278414E+10 0.00 0.00 1426889.78 0.00 0.00 0.127078E+10 0.00 0.29
December 0.383806E+10 0.00 0.00 151724.27 0.00 0.00 0.278218E+09 0.00 0.25
                   
Annual Sum or Average 0.258695E+11 7000426.99 0.00 65682581.82 8227029.72 16471820.82 0.396488E+11 0.00 0.59
Minimum of Months 0.707401E+09 0.00 0.00 151724.27 0.00 0.00 0.278218E+09 0.00 0.25
Maximum of Months 0.409145E+10 5136493.21 0.00 12488087.61 7063518.94 16471820.82 0.662712E+10 0.00 1.16



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.244280E+10 0.00 0.00 749913.96 0.00 46889147.06 0.521035E+09 0.00 0.28
February 0.194274E+10 0.00 0.00 1421019.75 0.00 174369.70 0.809762E+09 0.00 0.29
March 0.175896E+10 0.00 0.00 2204818.00 0.00 0.00 0.150793E+10 0.00 0.34
April 0.830866E+09 0.00 0.00 10991422.74 0.00 0.00 0.615696E+10 0.00 1.06
May 0.690040E+09 0.00 0.00 10728999.78 0.00 0.00 0.628222E+10 0.00 1.07
June 0.448457E+09 1233325.11 0.00 12886975.62 4533378.75 0.00 0.654305E+10 0.00 1.47
July 0.560434E+09 6740829.32 0.00 14511811.45 746743.24 0.00 0.617880E+10 0.00 1.57
August 0.693337E+09 0.00 0.00 14060959.84 0.00 0.00 0.615263E+10 0.00 1.74
September 0.654969E+09 0.00 0.00 11100007.22 0.00 0.00 0.522174E+10 0.00 1.31
October 0.133068E+10 0.00 0.00 4210056.67 0.00 0.00 0.239377E+10 0.00 0.52
November 0.191379E+10 0.00 0.00 1058901.39 0.00 0.00 0.759839E+09 0.00 0.30
December 0.246872E+10 0.00 0.00 401828.72 0.00 1623304.29 0.224493E+09 0.00 0.25
                   
Annual Sum or Average 0.157358E+11 7974154.43 0.00 84326715.12 5280122.00 48686821.04 0.427522E+11 0.00 0.85
Minimum of Months 0.448457E+09 0.00 0.00 401828.72 0.00 0.00 0.224493E+09 0.00 0.25
Maximum of Months 0.246872E+10 6740829.32 0.00 14511811.45 4533378.75 46889147.06 0.654305E+10 0.00 1.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.326401E+10 0.00 0.00 4736729.20 0.00 0.123641E+09 0.316688E+10 0.00 0.40
February 0.270310E+10 0.00 0.00 7247341.65 0.00 7996521.01 0.355240E+10 0.00 0.44
March 0.270214E+10 0.00 0.00 4711979.54 0.00 0.00 0.333202E+10 0.00 0.42
April 0.128837E+10 0.00 0.00 19610043.28 0.00 0.00 0.106569E+11 0.00 1.24
May 0.132911E+10 0.00 0.00 13031733.84 0.00 0.00 0.814978E+10 0.00 0.98
June 0.905828E+09 2137131.04 0.00 15634639.92 7062011.76 0.00 0.827124E+10 0.00 1.29
July 0.102627E+10 7978067.76 0.00 19653645.20 929091.74 0.00 0.845864E+10 0.00 1.49
August 0.100691E+10 0.00 0.00 25952847.26 0.00 0.00 0.994617E+10 0.00 1.93
September 0.941975E+09 0.00 0.00 23080980.01 0.00 0.00 0.996401E+10 0.00 1.71
October 0.192804E+10 0.00 0.00 11432105.73 0.00 0.00 0.700823E+10 0.00 0.87
November 0.273675E+10 0.00 0.00 5393675.29 0.00 654914.73 0.300733E+10 0.00 0.42
December 0.339297E+10 0.00 0.00 3033065.55 0.00 14619300.73 0.163509E+10 0.00 0.31
                   
Annual Sum or Average 0.232255E+11 10115198.81 0.00 0.153519E+09 7991103.50 0.146911E+09 0.771487E+11 0.00 0.96
Minimum of Months 0.905828E+09 0.00 0.00 3033065.55 0.00 0.00 0.163509E+10 0.00 0.31
Maximum of Months 0.339297E+10 7978067.76 0.00 25952847.26 7062011.76 0.123641E+09 0.106569E+11 0.00 1.93



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.185172E+10 0.00 0.00 2082148.69 0.00 0.00 0.168521E+10 0.00 0.34
February 0.736497E+09 0.00 0.00 5544220.51 0.00 0.00 0.355792E+10 0.00 0.46
March 0.153392E+09 0.00 0.00 8945038.55 0.00 0.00 0.638425E+10 0.00 0.70
April 0.136941E+09 0.00 0.00 21722607.03 0.00 0.00 0.111822E+11 0.00 1.77
May 0.307536E+09 0.00 0.00 14772758.98 0.00 0.00 0.831643E+10 0.00 1.38
June 0.155370E+09 28040524.74 0.00 21374757.83 184697.66 0.00 0.100158E+11 0.00 2.17
July 0.213574E+09 11378240.22 0.00 28319442.15 84239.10 0.00 0.104111E+11 0.00 2.54
August 0.240304E+09 0.00 0.00 29708464.93 0.00 0.00 0.107772E+11 0.00 2.86
September 0.301967E+09 0.00 0.00 13449269.01 0.00 0.00 0.619259E+10 0.00 1.54
October 0.217403E+09 0.00 0.00 8535865.28 0.00 0.00 0.562821E+10 0.00 0.85
November 0.289420E+09 0.00 0.00 6843901.87 0.00 0.00 0.459940E+10 0.00 0.57
December 0.202799E+09 0.00 0.00 6080000.91 0.00 0.00 0.428020E+10 0.00 0.43
                   
Annual Sum or Average 0.480692E+10 39418764.96 0.00 0.167378E+09 268936.76 0.00 0.830306E+11 0.00 1.30
Minimum of Months 0.136941E+09 0.00 0.00 2082148.69 0.00 0.00 0.168521E+10 0.00 0.34
Maximum of Months 0.185172E+10 28040524.74 0.00 29708464.93 184697.66 0.00 0.111822E+11 0.00 2.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.284367E+11 0.00 0.00 0.00 0.00 0.186255E+11 0.00 0.00 0.29
February 0.308492E+11 0.00 0.00 0.00 0.00 0.105919E+11 0.00 0.00 0.29
March 0.414496E+11 0.00 0.00 105524.55 0.00 0.449762E+10 0.283561E+09 0.00 0.31
April 0.230035E+11 0.00 0.00 24819463.94 0.00 49960318.76 0.184541E+11 0.00 0.40
May 0.218263E+11 0.00 0.00 35133379.31 0.00 10824376.06 0.245363E+11 0.00 0.47
June 0.106621E+11 9545746.80 0.00 72733114.20 77515667.36 0.00 0.420060E+11 0.00 0.72
July 0.112841E+11 58859448.13 0.00 73984499.89 13358211.42 0.00 0.386996E+11 0.00 0.77
August 0.129232E+11 0.00 0.00 71514377.95 0.00 0.00 0.335721E+11 0.00 0.79
September 0.207930E+11 0.00 0.00 33506766.00 0.00 0.00 0.180445E+11 0.00 0.55
October 0.332754E+11 0.00 0.00 3459479.45 0.00 0.989118E+09 0.248231E+10 0.00 0.31
November 0.320698E+11 0.00 0.00 0.00 0.00 0.871686E+10 0.00 0.00 0.30
December 0.210019E+11 0.00 0.00 0.00 0.00 0.244286E+11 0.00 0.00 0.29
                   
Annual Sum or Average 0.287575E+12 68405194.94 0.00 0.315257E+09 90873878.78 0.679104E+11 0.178079E+12 0.00 0.46
Minimum of Months 0.106621E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.414496E+11 58859448.13 0.00 73984499.89 77515667.36 0.244286E+11 0.420060E+11 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.156243E+11 0.00 0.00 543859.61 0.00 0.884750E+10 0.451725E+09 0.00 0.24
February 0.159818E+11 0.00 0.00 2799167.91 0.00 0.471911E+10 0.196841E+10 0.00 0.25
March 0.191056E+11 0.00 0.00 4492080.40 0.00 0.225473E+10 0.365580E+10 0.00 0.26
April 0.770742E+10 0.00 0.00 93277755.77 0.00 3125366.41 0.494409E+11 0.00 0.88
May 0.778244E+10 0.00 0.00 90232908.21 0.00 4172325.80 0.503273E+11 0.00 0.93
June 0.465461E+10 11413809.75 0.00 0.116257E+09 46563114.61 0.00 0.556009E+11 0.00 1.31
July 0.393870E+10 93221055.34 0.00 0.136057E+09 8585033.72 0.00 0.533623E+11 0.00 1.38
August 0.467209E+10 0.00 0.00 0.129804E+09 0.00 0.00 0.543667E+11 0.00 1.54
September 0.727833E+10 0.00 0.00 95549617.67 0.00 0.00 0.426452E+11 0.00 1.14
October 0.138186E+11 0.00 0.00 23204455.33 0.00 0.644915E+09 0.127194E+11 0.00 0.38
November 0.165189E+11 0.00 0.00 879008.82 0.00 0.438566E+10 0.745416E+09 0.00 0.24
December 0.109739E+11 0.00 0.00 2350.65 0.00 0.130293E+11 11517998.48 0.00 0.24
                   
Annual Sum or Average 0.128057E+12 0.104635E+09 0.00 0.693100E+09 55148148.34 0.338885E+11 0.325296E+12 0.00 0.73
Minimum of Months 0.393870E+10 0.00 0.00 2350.65 0.00 0.00 11517998.48 0.00 0.24
Maximum of Months 0.191056E+11 93221055.34 0.00 0.136057E+09 46563114.61 0.130293E+11 0.556009E+11 0.00 1.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.293067E+11 0.00 0.00 39702634.24 0.00 0.726437E+10 0.306280E+11 0.00 0.42
February 0.262428E+11 0.00 0.00 63562436.74 0.00 0.412288E+10 0.375020E+11 0.00 0.50
March 0.316334E+11 0.00 0.00 28355324.12 0.00 0.230724E+10 0.225675E+11 0.00 0.39
April 0.137480E+11 0.00 0.00 0.176271E+09 0.00 0.00 0.899161E+11 0.00 1.09
May 0.151384E+11 0.00 0.00 0.116552E+09 0.00 30565994.10 0.700594E+11 0.00 0.90
June 0.103260E+11 18968923.65 0.00 0.133642E+09 70324755.89 0.00 0.678576E+11 0.00 1.13
July 0.929408E+10 0.114799E+09 0.00 0.171231E+09 10289026.99 0.00 0.700119E+11 0.00 1.29
August 0.848278E+10 0.00 0.00 0.236609E+09 0.00 0.00 0.853128E+11 0.00 1.71
September 0.104149E+11 0.00 0.00 0.238680E+09 0.00 0.00 0.949216E+11 0.00 1.71
October 0.209311E+11 0.00 0.00 0.107475E+09 0.00 0.382852E+09 0.579989E+11 0.00 0.76
November 0.277412E+11 0.00 0.00 39974898.60 0.00 0.407824E+10 0.249722E+11 0.00 0.43
December 0.258460E+11 0.00 0.00 15671613.26 0.00 0.148769E+11 0.125146E+11 0.00 0.35
                   
Annual Sum or Average 0.229105E+12 0.133768E+09 0.00 0.136773E+10 80613782.88 0.330630E+11 0.664263E+12 0.00 0.89
Minimum of Months 0.848278E+10 0.00 0.00 15671613.26 0.00 0.00 0.125146E+11 0.00 0.35
Maximum of Months 0.316334E+11 0.114799E+09 0.00 0.238680E+09 70324755.89 0.148769E+11 0.949216E+11 0.00 1.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.218300E+11 0.00 0.00 2552816.51 0.00 0.677809E+10 0.230531E+10 0.00 0.30
February 0.208783E+11 0.00 0.00 9808068.97 0.00 0.284946E+10 0.723737E+10 0.00 0.34
March 0.242055E+11 0.00 0.00 8709269.92 0.00 0.888724E+09 0.790774E+10 0.00 0.35
April 0.865939E+10 0.00 0.00 89374292.36 0.00 0.00 0.460990E+11 0.00 0.91
May 0.806643E+10 0.00 0.00 99169194.78 0.00 3356955.58 0.530025E+11 0.00 1.02
June 0.420430E+10 0.289369E+09 0.00 0.136564E+09 811665.77 0.00 0.618950E+11 0.00 1.49
July 0.437299E+10 0.118201E+09 0.00 0.175577E+09 1194471.38 0.00 0.597241E+11 0.00 1.63
August 0.453331E+10 0.00 0.00 0.149672E+09 0.00 0.00 0.534004E+11 0.00 1.60
September 0.816940E+10 0.00 0.00 81266605.99 0.00 0.00 0.358969E+11 0.00 1.10
October 0.174470E+11 0.00 0.00 21183640.77 0.00 88829814.19 0.130746E+11 0.00 0.43
November 0.216605E+11 0.00 0.00 2905408.22 0.00 0.305818E+10 0.253997E+10 0.00 0.31
December 0.184893E+11 0.00 0.00 136401.41 0.00 0.106365E+11 0.152295E+09 0.00 0.29
                   
Annual Sum or Average 0.162516E+12 0.407570E+09 0.00 0.776919E+09 2006137.15 0.243031E+11 0.343235E+12 0.00 0.82
Minimum of Months 0.420430E+10 0.00 0.00 136401.41 0.00 0.00 0.152295E+09 0.00 0.29
Maximum of Months 0.242055E+11 0.289369E+09 0.00 0.175577E+09 1194471.38 0.106365E+11 0.618950E+11 0.00 1.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.991986E+09 0.00 0.00 0.00 0.00 0.330616E+10 0.00 0.00 0.30
February 0.143145E+10 0.00 0.00 0.00 0.00 0.236737E+10 0.00 0.00 0.30
March 0.275782E+10 0.00 0.00 0.00 0.00 0.156922E+10 0.00 0.00 0.32
April 0.229703E+10 0.00 0.00 1605892.46 390426.36 0.329659E+09 0.131683E+10 0.00 0.38
May 0.253435E+10 0.00 0.00 2465104.26 0.00 0.132187E+09 0.181055E+10 0.00 0.45
June 0.131266E+10 360825.63 0.00 6296425.06 5609999.06 2431400.38 0.380245E+10 0.00 0.70
July 0.115504E+10 2414892.56 0.00 6988257.98 624313.30 589320.90 0.379873E+10 0.00 0.76
August 0.133494E+10 0.00 0.00 6287696.09 0.00 0.00 0.318416E+10 0.00 0.75
September 0.205560E+10 0.00 0.00 2439871.53 0.00 91023795.97 0.140442E+10 0.00 0.51
October 0.244928E+10 0.00 0.00 40860.30 0.00 0.893524E+09 94818392.35 0.00 0.32
November 0.147903E+10 0.00 0.00 0.00 0.00 0.218974E+10 0.00 0.00 0.30
December 0.666650E+09 0.00 0.00 0.00 0.00 0.346201E+10 0.00 0.00 0.30
                   
Annual Sum or Average 0.204658E+11 2775718.20 0.00 26124107.68 6624738.72 0.143439E+11 0.154120E+11 0.00 0.45
Minimum of Months 0.666650E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.275782E+10 2414892.56 0.00 6988257.98 5609999.06 0.346201E+10 0.380245E+10 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.984811E+09 0.00 0.00 848.70 0.00 0.179580E+10 3958083.37 0.00 0.30
February 0.116830E+10 0.00 0.00 48041.34 0.00 0.125267E+10 45196902.52 0.00 0.30
March 0.195447E+10 0.00 0.00 40413.25 0.00 0.809858E+09 47500134.78 0.00 0.32
April 0.774844E+09 1817868.21 0.00 8375436.51 0.00 64478734.91 0.462633E+10 0.00 0.86
May 0.910867E+09 0.00 0.00 7805604.61 0.00 43421971.26 0.470231E+10 0.00 0.91
June 0.509136E+09 2454520.76 0.00 11216115.99 2007502.70 1219474.18 0.565139E+10 0.00 1.32
July 0.440758E+09 6503877.54 0.00 13227925.63 392244.21 0.00 0.548376E+10 0.00 1.42
August 0.481844E+09 0.00 0.00 12599252.06 0.00 0.00 0.554035E+10 0.00 1.56
September 0.811829E+09 0.00 0.00 8054870.21 0.00 15368682.16 0.385279E+10 0.00 1.10
October 0.135710E+10 0.00 0.00 1375927.07 0.00 0.452523E+09 0.852322E+09 0.00 0.40
November 0.119001E+10 0.00 0.00 0.00 0.00 0.119548E+10 0.00 0.00 0.30
December 0.661120E+09 0.00 0.00 0.00 0.00 0.202844E+10 0.00 0.00 0.30
                   
Annual Sum or Average 0.112451E+11 10776266.51 0.00 62744435.38 2399746.91 0.765926E+10 0.308059E+11 0.00 0.76
Minimum of Months 0.440758E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.195447E+10 6503877.54 0.00 13227925.63 2007502.70 0.202844E+10 0.565139E+10 0.00 1.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.184879E+10 0.00 0.00 2197997.98 0.00 0.178760E+10 0.179350E+10 0.00 0.37
February 0.181613E+10 0.00 0.00 4041507.72 0.00 0.115658E+10 0.260010E+10 0.00 0.44
March 0.266097E+10 0.00 0.00 1314968.50 0.00 0.102323E+10 0.109330E+10 0.00 0.35
April 0.124859E+10 286933.69 0.00 16274098.97 102979.46 0.206439E+09 0.873130E+10 0.00 1.04
May 0.165386E+10 0.00 0.00 9859911.43 0.00 0.146609E+09 0.656169E+10 0.00 0.86
June 0.114938E+10 3296878.17 0.00 12551069.35 3362322.51 7432972.57 0.677014E+10 0.00 1.10
July 0.916120E+09 3247362.38 0.00 16674997.29 845293.83 0.00 0.726972E+10 0.00 1.28
August 0.809525E+09 0.00 0.00 22823505.87 0.00 0.00 0.890911E+10 0.00 1.68
September 0.110201E+10 0.00 0.00 21724515.62 0.00 9369143.24 0.922942E+10 0.00 1.62
October 0.174512E+10 0.00 0.00 8142761.39 0.00 0.538462E+09 0.516835E+10 0.00 0.76
November 0.191119E+10 0.00 0.00 2111785.92 0.00 0.123051E+10 0.137894E+10 0.00 0.37
December 0.138201E+10 0.00 0.00 881806.15 0.00 0.243692E+10 0.692877E+09 0.00 0.33
                   
Annual Sum or Average 0.182437E+11 6831174.24 0.00 0.118599E+09 4310595.80 0.854316E+10 0.601984E+11 0.00 0.85
Minimum of Months 0.809525E+09 0.00 0.00 881806.15 0.00 0.00 0.692877E+09 0.00 0.33
Maximum of Months 0.266097E+10 3296878.17 0.00 22823505.87 3362322.51 0.243692E+10 0.922942E+10 0.00 1.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.126934E+10 0.00 0.00 88130.03 0.00 0.139172E+10 83344247.90 0.00 0.30
February 0.140491E+10 0.00 0.00 625102.97 0.00 0.773003E+09 0.526250E+09 0.00 0.33
March 0.205575E+10 0.00 0.00 460582.05 0.00 0.488065E+09 0.438387E+09 0.00 0.34
April 0.985563E+09 185124.11 0.00 8458666.39 66440.37 56842388.90 0.435438E+10 0.00 0.87
May 0.101091E+10 0.00 0.00 8779830.16 0.00 35646447.23 0.498206E+10 0.00 0.99
June 0.504786E+09 21285114.56 0.00 13121165.08 59456.60 120631.60 0.622495E+10 0.00 1.47
July 0.445398E+09 4179363.80 0.00 16878388.14 45745.66 0.00 0.615596E+10 0.00 1.61
August 0.440007E+09 0.00 0.00 14608748.96 0.00 0.00 0.545280E+10 0.00 1.56
September 0.907443E+09 0.00 0.00 7201965.72 0.00 3751903.43 0.334862E+10 0.00 1.04
October 0.151383E+10 0.00 0.00 1440872.93 0.00 0.315475E+09 0.110696E+10 0.00 0.45
November 0.147231E+10 0.00 0.00 146900.43 0.00 0.789040E+09 0.127561E+09 0.00 0.30
December 0.898897E+09 0.00 0.00 0.00 0.00 0.170063E+10 0.00 0.00 0.29
                   
Annual Sum or Average 0.129091E+11 25649602.47 0.00 71810352.86 171642.63 0.555429E+10 0.328013E+11 0.00 0.80
Minimum of Months 0.440007E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.205575E+10 21285114.56 0.00 16878388.14 66440.37 0.170063E+10 0.622495E+10 0.00 1.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 3036798.30 0.00 0.00 0.638137E+09 0.00 0.28
February 0.00 0.00 0.00 7679705.16 0.00 0.00 0.562285E+09 0.00 0.29
March 0.00 0.00 0.00 13444673.67 0.00 0.00 0.623677E+09 0.00 0.30
April 0.00 0.00 0.00 18231275.87 0.00 0.00 0.465658E+09 0.00 0.29
May 0.00 0.00 0.00 4047992.78 0.00 0.00 0.472996E+09 0.00 0.29
June 0.00 103138.11 0.00 8734711.15 0.00 0.00 0.323136E+09 0.00 0.30
July 0.00 0.00 0.00 12981862.76 0.00 0.00 0.228471E+09 0.00 0.28
August 0.00 0.00 0.00 19139255.84 0.00 0.00 0.222815E+09 0.00 0.31
September 0.00 0.00 0.00 4008676.40 0.00 0.00 0.312069E+09 0.00 0.29
October 0.00 0.00 0.00 8448845.35 0.00 0.00 0.462623E+09 0.00 0.28
November 0.00 0.00 0.00 12205898.41 0.00 0.00 0.530175E+09 0.00 0.28
December 0.00 0.00 0.00 16878962.76 0.00 0.00 0.612303E+09 0.00 0.28
                   
Annual Sum or Average 0.00 103138.11 0.00 0.128839E+09 0.00 0.00 0.545435E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 3036798.30 0.00 0.00 0.222815E+09 0.00 0.28
Maximum of Months 0.00 103138.11 0.00 19139255.84 0.00 0.00 0.638137E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.187044E+09 0.00 0.00 14487319.60 0.00 0.00 0.621032E+10 0.00 0.28
February 0.00 0.00 0.00 60856557.28 0.00 0.00 0.563824E+10 0.00 0.29
March 0.00 0.00 0.00 0.117005E+09 0.00 0.00 0.625375E+10 0.00 0.30
April 0.00 0.00 0.00 0.169681E+09 0.00 0.00 0.466904E+10 0.00 0.29
May 0.00 0.00 0.00 33950614.40 0.00 0.00 0.473893E+10 0.00 0.29
June 0.00 941707.05 0.00 80802196.46 0.00 0.00 0.324240E+10 0.00 0.30
July 0.00 0.00 0.00 0.121935E+09 0.00 0.00 0.229483E+10 0.00 0.28
August 0.00 0.00 0.00 0.181059E+09 0.00 0.00 0.223923E+10 0.00 0.31
September 0.00 0.00 0.00 33864243.63 0.00 0.00 0.314107E+10 0.00 0.29
October 0.00 0.00 0.00 71303264.30 0.00 0.00 0.464207E+10 0.00 0.28
November 0.00 0.00 0.00 0.103052E+09 0.00 0.00 0.532070E+10 0.00 0.28
December 0.00 0.00 0.00 0.141939E+09 0.00 0.00 0.614863E+10 0.00 0.28
                   
Annual Sum or Average 0.187044E+09 941707.05 0.00 0.112994E+10 0.00 0.00 0.545392E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 14487319.60 0.00 0.00 0.223923E+10 0.00 0.28
Maximum of Months 0.187044E+09 941707.05 0.00 0.181059E+09 0.00 0.00 0.625375E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.329275E+09 0.00 0.00 438379.72 0.00 0.00 0.304319E+09 0.00 0.28
February 0.00 0.00 0.00 4839588.46 0.00 0.00 0.565154E+09 0.00 0.29
March 0.00 0.00 0.00 10422601.24 0.00 0.00 0.626683E+09 0.00 0.30
April 0.00 0.00 0.00 16392965.52 0.00 0.00 0.467487E+09 0.00 0.29
May 1558257.61 0.00 0.00 2939159.93 0.00 0.00 0.472956E+09 0.00 0.29
June 0.00 98019.74 0.00 7900409.70 0.00 0.00 0.324634E+09 0.00 0.30
July 0.00 0.00 0.00 12078053.50 0.00 0.00 0.229760E+09 0.00 0.28
August 0.00 0.00 0.00 17941919.78 0.00 0.00 0.224262E+09 0.00 0.31
September 0.00 0.00 0.00 2915887.56 0.00 0.00 0.315589E+09 0.00 0.29
October 0.00 0.00 0.00 5981698.61 0.00 0.00 0.466160E+09 0.00 0.28
November 0.00 0.00 0.00 9007735.48 0.00 0.00 0.533683E+09 0.00 0.28
December 0.00 0.00 0.00 12998526.85 0.00 0.00 0.616107E+09 0.00 0.28
                   
Annual Sum or Average 0.330834E+09 98019.74 0.00 0.103857E+09 0.00 0.00 0.514679E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 438379.72 0.00 0.00 0.224262E+09 0.00 0.28
Maximum of Months 0.329275E+09 98019.74 0.00 17941919.78 0.00 0.00 0.626683E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.501196E+09 0.00 0.00 0.404100E+12 0.00 8.92
February 0.00 0.00 0.00 0.933788E+09 0.00 0.00 0.630403E+12 0.00 15.45
March 0.00 0.00 0.00 0.141497E+10 0.00 0.00 0.100662E+13 0.00 23.74
April 0.00 0.00 0.00 0.221924E+10 0.00 0.00 0.118833E+13 0.00 34.96
May 0.00 0.00 0.00 0.536551E+09 0.00 0.00 0.373062E+12 0.00 12.44
June 0.00 2614927.01 0.00 0.109528E+10 0.00 0.00 0.552955E+12 0.00 26.19
July 0.00 18161618.37 0.00 0.194224E+10 0.00 0.00 0.712169E+12 0.00 36.83
August 0.00 0.00 0.00 0.257536E+10 0.00 0.00 0.685553E+12 0.00 41.26
September 0.00 0.00 0.00 0.552762E+09 0.00 0.00 0.340001E+12 0.00 16.41
October 0.00 0.00 0.00 0.997614E+09 0.00 0.00 0.635368E+12 0.00 20.22
November 0.00 0.00 0.00 0.146485E+10 0.00 0.00 0.921764E+12 0.00 24.63
December 0.00 0.00 0.00 0.211493E+10 0.00 0.00 0.129132E+13 0.00 28.41
                   
Annual Sum or Average 0.00 20776545.38 0.00 0.163488E+11 0.00 0.00 0.874165E+13 0.00 24.18
Minimum of Months 0.00 0.00 0.00 0.501196E+09 0.00 0.00 0.340001E+12 0.00 8.92
Maximum of Months 0.00 18161618.37 0.00 0.257536E+10 0.00 0.00 0.129132E+13 0.00 41.26



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.140906E+12 0.670522E+10 0.00 0.213661E+13 0.695694E+11
February 0.230495E+12 0.949074E+10 0.00 0.221222E+13 0.138039E+12
March 0.279137E+12 0.597876E+10 0.00 0.284584E+13 0.231876E+12
April 0.728156E+12 0.740916E+10 0.00 0.323741E+13 0.440738E+12
May 0.898765E+12 0.176011E+11 0.00 0.236951E+13 0.166304E+12
June 0.903394E+12 0.138144E+11 0.00 0.254276E+13 0.419335E+12
July 0.911596E+12 0.131961E+11 0.00 0.270416E+13 0.784726E+12
August 0.744695E+12 0.977608E+10 0.00 0.263710E+13 0.131650E+13
September 0.549987E+12 0.104470E+11 0.00 0.236262E+13 0.336325E+12
October 0.250001E+12 0.103071E+11 0.00 0.249735E+13 0.193279E+12
November 0.108506E+12 0.123710E+11 0.00 0.262201E+13 0.213060E+12
December 0.484698E+11 0.166236E+11 0.00 0.288076E+13 0.301774E+12
           
Annual Sum or Average 0.579411E+13 0.133720E+12 0.00 0.310484E+14 0.461153E+13
Minimum of Months 0.484698E+11 0.597876E+10 0.00 0.213661E+13 0.695694E+11
Maximum of Months 0.911596E+12 0.176011E+11 0.00 0.323741E+13 0.131650E+13