Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:56:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27753.28 | 599.16 | 599.16 |
Net Site Energy | 27121.11 | 585.51 | 585.51 |
Total Source Energy | 85733.41 | 1850.88 | 1850.88 |
Net Source Energy | 83731.31 | 1807.66 | 1807.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 346.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2936.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1767.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2643.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 487.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 950.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8474.32 |
Humidification | 1787.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.07 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 691.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26715.72 | 1037.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11419.55 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 346.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2936.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1767.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2643.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 487.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 950.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8474.32 |
Humidification | General | 1787.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.07 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 691.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 346.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2936.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1767.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2643.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 487.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 950.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8474.32 |
Humidification | Unassigned | 1787.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.07 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 691.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 43.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.10 | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 576.76 | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 43.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.10 | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 576.76 | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 659.306 | 2.47 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -27.13 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 632.175 | 2.37 |
Electricity Coming From Utility | 26083.546 | 97.63 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26083.546 | 97.63 |
Total On-Site and Utility Electric Sources | 26715.721 | 100.00 |
Total Electricity End Uses | 26715.721 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 11419.55 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 11419.55 | 100.00 |
Total Water End Uses | 11419.55 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.67 |
Time Setpoint Not Met During Occupied Cooling | 1042.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5820.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 23-AUG-15:20 | 27-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 15-JUN-12:50 |
Heating | 0.00 | 702923.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 357946.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 150591.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52592.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 287800.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46910.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 47691.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30502.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1821904.85 | 733426.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 702923.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 357946.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 150591.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3362.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 287800.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 46910.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 47691.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 30502.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 375.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9300.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5597.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8371.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1544.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3009.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5662.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 749.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84608.69 | 1124.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 200.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 120.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 122.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1826.60 | 24.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 200.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 120.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 122.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1826.60 | 24.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.56 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.526211 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.02 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.513579 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.49 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.04 | 0.314687 | 0.267000 | 1.61 | 0.839167 | 0.500000 | 0.001211 | 0.000308 | 1.61 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.83 | 0.334662 | 0.284000 | 16.14 | 0.892432 | 0.500000 | 0.001138 | 0.008088 | 16.14 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.71 | 0.333176 | 0.283000 | 1.62 | 0.888470 | 0.500000 | 0.001144 | 0.001764 | 2.77 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.13 | 0.211609 | 0.180000 | 0.203147 | 0.564291 | 0.500000 | 0.001800 | 0.000210 | 0.329378 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.12 | 0.137049 | 0.116000 | 0.130267 | 0.365464 | 0.500000 | 0.002780 | 0.000150 | 0.234969 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.27 | 0.187800 | 0.160000 | 0.203473 | 0.500799 | 0.500000 | 0.002029 | 0.000260 | 0.408763 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.47 | 0.104627 | 0.089000 | 0.130918 | 0.300000 | 0.500000 | 0.003641 | 0.000099 | 0.155216 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.91 | 0.218977 | 0.186000 | 2.03 | 0.583940 | 0.500000 | 0.001740 | 0.004274 | 6.72 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.85 | 0.346451 | 0.500000 | 0.002933 | 0.002838 | 4.46 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.32 | 0.193870 | 0.165000 | 2.03 | 0.516986 | 0.500000 | 0.001965 | 0.004234 | 6.66 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.91 | 0.119254 | 0.101000 | 1.30 | 0.318011 | 0.500000 | 0.003195 | 0.002645 | 4.16 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.25 | 0.190372 | 0.162000 | 0.203228 | 0.507658 | 0.500000 | 0.002001 | 0.000553 | 0.869466 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.21 | 0.126866 | 0.108000 | 0.131018 | 0.338309 | 0.500000 | 0.003003 | 0.000365 | 0.573518 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.38 | 0.172624 | 0.147000 | 0.203375 | 0.460331 | 0.500000 | 0.002207 | 0.000548 | 0.862489 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.40 | 0.109938 | 0.093000 | 0.130193 | 0.300000 | 0.500000 | 0.003466 | 0.000349 | 0.548454 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 14092.30 | 0.000308 | 393.32 |
CORE_MID VAV BOX REHEAT COIL | 369723.75 | 0.008088 | 12739.58 |
CORE_TOP VAV BOX REHEAT COIL | 80641.78 | 0.001764 | 3138.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9596.20 | 0.000210 | 373.40 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6842.94 | 0.000150 | 266.20 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11900.84 | 0.000260 | 462.87 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4528.88 | 0.000099 | 176.39 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 195373.86 | 0.004274 | 7592.54 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 129722.85 | 0.002838 | 5041.04 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 193534.41 | 0.004234 | 7521.14 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 120919.77 | 0.002645 | 4699.34 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 25270.32 | 0.000553 | 981.76 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16668.19 | 0.000365 | 647.55 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25067.86 | 0.000548 | 973.90 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15940.70 | 0.000349 | 619.31 |
VAV_BOT WITH REHEAT HEATING COIL | 40450.75 | 0.000885 | 884.74 |
VAV_MID WITH REHEAT HEATING COIL | 332336.88 | 0.007270 | 7418.74 |
VAV_TOP WITH REHEAT HEATING COIL | 28733.30 | 0.000629 | 652.47 |
CAV_BAS HEATING COIL | 239916.27 | 0.005248 | 7633.01 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.52 | 2.28 | 11.04 | 2.28 | 9.93 | 9.93 | 0.300000 | 0.229885 | 9.93 |
VAV_MID WITH REHEAT | 52.41 | 22.81 | 104.81 | 33.11 | 92.65 | 92.65 | 0.300000 | 0.357383 | 92.65 |
VAV_TOP WITH REHEAT | 5.48 | 2.28 | 10.96 | 5.62 | 10.50 | 10.50 | 0.300000 | 0.535618 | 10.50 |
CAV_BAS | 5.56 | 5.56 | 5.56 | 5.56 | 5.56 | 5.56 | 1.00 | 1.00 | 5.56 |
AIRLOOP DATACENTER BASEMENT | 24.49 | 24.49 | 24.49 | 24.49 | 24.49 | 24.49 | 1.00 | 0.999986 | 24.49 |
AIRLOOP DATACENTER BOT | 0.526211 | 0.526211 | 0.526211 | 0.526211 | 0.526211 | 0.526211 | 1.00 | 1.00 | 0.526211 |
AIRLOOP DATACENTER MID | 5.02 | 5.02 | 5.02 | 5.02 | 5.02 | 5.02 | 1.00 | 1.00 | 5.02 |
AIRLOOP DATACENTER TOP | 0.513579 | 0.513579 | 0.513579 | 0.513579 | 0.513579 | 0.513579 | 1.00 | 1.00 | 0.513579 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.93 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 92.65 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.50 | |
CAV_BAS_OA_CONTROLLER | 5.56 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.49 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.526211 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.02 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.513579 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.94 | 6.67 | 10.77 | 0.007264 | 0.007000 | 177642.69 | 0.005081 | 9.93 |
VAV_MID WITH REHEAT COOLING COIL | 27.24 | 6.67 | 10.77 | 0.007279 | 0.007000 | 1690975.73 | 0.048362 | 92.65 |
VAV_TOP WITH REHEAT COOLING COIL | 26.73 | 6.67 | 10.78 | 0.007247 | 0.007000 | 184915.42 | 0.005289 | 10.50 |
CAV_BAS COOLING COIL | 27.29 | 6.67 | 11.21 | 0.007405 | 0.007000 | 101043.49 | 0.002890 | 5.56 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.93 |
VAV_MID WITH REHEAT FAN | 92.65 |
VAV_TOP WITH REHEAT FAN | 10.50 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005081 | 0.000094 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000885 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.048362 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007270 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005289 | 0.000090 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000629 | |
CAV_BAS_COOLC_CONTROLLER | 0.002890 | 0.000165 |
CAV_BAS_HEATC_CONTROLLER | 0.005248 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.56 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.49 | 465160.61 | 259116.56 | 0.011392 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.526211 | 9817.97 | 5499.74 | 0.000240 |
AIRLOOP DATACENTER MID COOLING COIL | 5.02 | 93744.20 | 52495.52 | 0.002296 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.513579 | 9592.40 | 5370.75 | 0.000235 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.49 | 24.49 | 24.49 | 24.49 | 465160.61 | 465160.61 | 16051.03 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.526211 | 0.526211 | 0.526211 | 0.526211 | 9817.97 | 9817.97 | 741.49 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.02 | 5.02 | 5.02 | 5.02 | 93744.20 | 93744.20 | 7414.91 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.513579 | 0.513579 | 0.513579 | 0.513579 | 9592.40 | 9592.40 | 741.49 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.49 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.526211 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.02 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.513579 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.49 | 465160.61 | 0.011392 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.526211 | 9817.97 | 0.000240 |
AIRLOOP DATACENTER MID HEATING COIL | 5.02 | 93744.20 | 0.002296 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.513579 | 9592.40 | 0.000235 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 16051.03 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 741.49 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7414.91 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 741.49 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000128 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.061621 | 9961.16 | |
HEATSYS1 PUMP | 0.040715 | 12140.21 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.061621 | 7.39 |
HEATSYS1 | 0.040715 | 4.89 |
COOLSYS1_SUPPLY | 0.061621 | 7.39 |
SINGLE WATER PLANT LOOP | 0.014163 | 1.70 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.061621 | 0.061621 | 258652.74 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1861261.86 | 1861261.86 | 0.040715 |
CENTRAL BOILER | 583390.13 | 570636.93 | 0.014163 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.030810 | 3448.22 |
COOLSYS1 CHILLER2 PUMP | 0.030810 | 3448.22 |
PLANT CIRC PUMP | 0.014163 | 3576.48 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.061621 | 0.031204 | 1093733.92 | 1098921.17 | 0.054026 |
COOLSYS1 CHILLER2 | 0.061621 | 0.031204 | 1093733.92 | 1098921.17 | 0.054026 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014163 | 139666.47 | 56247.09 | 69833.23 | 7004.20 | 21099.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.108052 | 12.97 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.108052 | 26486.33 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 46.16 | 1304923.66 | 9.23 | 163115.46 |
TOWERWATERSYS COOLTOWER 2 | 46.16 | 1304923.66 | 9.23 | 163115.46 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.056485 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.223 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.421 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6505 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6842 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5363 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.12806887E-14 | 0.42271709E-16 | -0.13586671E-09 | -0.40936836E-17 |
51 | 8 | 0.19922932E-07 | 0.16187222E-12 | 0.35697139E-03 | -0.22653060E-09 |
52 | 7 | -0.11619186E-01 | 0.85920355E-08 | -0.22189363E-01 | 0.13211437E-03 |
53 | 6 | 0.38843793 | 0.30204786E-05 | 0.45766083 | -0.45484060E-02 |
54 | 5 | -5.0254998 | 0.11379910E-03 | -4.3303126 | 0.61137149E-01 |
55 | 4 | 32.272621 | 0.93848507E-03 | 21.006408 | -0.41242756 |
56 | 3 | -109.67225 | 0.20601564E-02 | -54.766020 | 1.4927443 |
57 | 2 | 195.59070 | 0.11662962E-02 | 77.088399 | -2.8762550 |
58 | 1 | -170.59539 | 0.12524661E-03 | -55.026900 | 2.7356126 |
59 | 0 | 57.057407 | 0.71759292E-06 | 15.597005 | |
60 | 9 | 0.14110139E-14 | 0.39742576E-16 | -0.13817129E-09 | -0.60843190E-17 |
61 | 8 | 0.20247994E-07 | 0.15595569E-12 | 0.36048606E-03 | -0.23022666E-09 |
62 | 7 | -0.11724403E-01 | 0.82461052E-08 | -0.22340970E-01 | 0.13331073E-03 |
63 | 6 | 0.39129736 | 0.28944083E-05 | 0.46010459 | -0.45821116E-02 |
64 | 5 | -5.0534104 | 0.10890513E-03 | -4.3491197 | 0.61483222E-01 |
65 | 4 | 32.396114 | 0.89705981E-03 | 21.080005 | -0.41406715 |
66 | 3 | -109.93510 | 0.19671505E-02 | -54.911560 | 1.4965416 |
67 | 2 | 195.85133 | 0.11126060E-02 | 77.221727 | -2.8803937 |
68 | 1 | -170.69171 | 0.11937799E-03 | -55.065382 | 2.7373008 |
69 | 0 | 57.057407 | 0.68337402E-06 | 15.590414 | |
70 | 9 | 0.11953810E-14 | 0.45347951E-16 | -0.12637851E-09 | -0.31580148E-17 |
71 | 8 | 0.18583176E-07 | 0.18541820E-12 | 0.34227377E-03 | -0.21129711E-09 |
72 | 7 | -0.11178467E-01 | 0.10005971E-07 | -0.21554080E-01 | 0.12710323E-03 |
73 | 6 | 0.37645972 | 0.35409928E-05 | 0.44740546 | -0.44072130E-02 |
74 | 5 | -4.9085688 | 0.13417224E-03 | -4.2513079 | 0.59687292E-01 |
75 | 4 | 31.755172 | 0.11121548E-02 | 20.697061 | -0.40555762 |
76 | 3 | -108.57065 | 0.24524110E-02 | -54.154201 | 1.4768303 |
77 | 2 | 194.49811 | 0.13939007E-02 | 76.528253 | -2.8589059 |
78 | 1 | -170.19150 | 0.15023953E-03 | -54.865849 | 2.7285341 |
79 | 0 | 57.057407 | 0.86422455E-06 | 15.625098 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1008E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1023E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4070E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4082E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1304E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1314E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7516E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1348E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2336E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4355E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5212E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1544E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2247E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7664E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1041 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5262E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1162 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9386E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7491E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9321E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1496E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0924E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1361E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2394E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4368E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5271E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1556E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2291E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7668E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8046E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1007E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1022E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4068E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4081E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1303E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1313E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7515E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7082E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8765E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4859E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6629E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3856E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4693E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9952E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0209E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0256E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9504E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6793E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7320E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9347E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6143E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2799E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2243E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6620E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7297E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4269E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4759E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3589E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3778E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9953E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0213E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7617E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7631E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5046E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5057E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3340E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3348E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7516E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7522E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7933E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8740E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5301E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5933E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3539E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3973E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7668E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8046E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7491E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4395E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1127E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0919E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8930E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.3711E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1496E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0921E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7925E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8719E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5293E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5913E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3530E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3946E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7664E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7617E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7630E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5046E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5057E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3339E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3347E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7515E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7521E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6050E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6730E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3568E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4061E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3090E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3277E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9954E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0213E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9268E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9127E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5588E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6860E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8432E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5790E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2799E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2243E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6498E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8127E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4142E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5845E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3354E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4178E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9952E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0208E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1020 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4139E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1100 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9427E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.4586E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.3948E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8633E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9092E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8208E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8348E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4330E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5643E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6919E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4154E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9603E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9312E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4424E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2869E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7194E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8106E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4752E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3640E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8633E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9088E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7089E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7825E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2965E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5005E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5892E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3680E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9603E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9312E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1021 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.4277E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1101 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9585E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.4725E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4058E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8716E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9134E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8245E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8391E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4371E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5683E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6995E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4205E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9686E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9354E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4428E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2895E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7200E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8126E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4792E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3664E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8716E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9131E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7124E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7867E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3004E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5043E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5967E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3730E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9686E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9354E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 66783.92665 | 66783.92665 | 5.55951 | 5.55951 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72604.07609 | 72604.07609 | 6.04423 | 6.04423 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 682881.34702 | 682881.34702 | 56.83474 | 56.83474 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 228774.76354 | 228774.76354 | 11.11568 | 11.11568 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67956.97559 | 67956.97559 | 5.70882 | 5.70882 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 56473.18933 | 56473.18933 | 2.76772 | 2.76772 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13434.86121 | 13434.86121 | 1.12859 | 1.12859 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6722.91004 | 6722.91004 | 0.32938 | 0.32938 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13368.27290 | 13368.27290 | 1.12299 | 1.12299 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 32.05500 | 6.86186E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4792.88730 | 4792.88730 | 0.23497 | 0.23497 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15138.51168 | 15138.51168 | 1.27171 | 1.27171 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 37.66667 | 6.87079E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 8333.75951 | 8333.75951 | 0.40876 | 0.40876 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17510.88536 | 17510.88536 | 1.47098 | 1.47098 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3175.82273 | 3175.82273 | 0.15522 | 0.15522 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 129828.44673 | 129828.44673 | 10.90617 | 10.90617 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 136735.60731 | 136735.60731 | 6.71914 | 6.71914 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 141019.72779 | 141019.72779 | 11.84621 | 11.84621 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 32.42333 | 6.86244E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 90786.28966 | 90786.28966 | 4.46159 | 4.46159 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 146645.64782 | 146645.64782 | 12.31888 | 12.31888 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 37.77500 | 6.87096E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 135449.70536 | 135449.70536 | 6.65575 | 6.65575 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 153631.19903 | 153631.19903 | 12.90562 | 12.90562 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 84632.03969 | 84632.03969 | 4.15829 | 4.15829 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14933.72698 | 14933.72698 | 1.25450 | 1.25450 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17682.29502 | 17682.29502 | 0.86947 | 0.86947 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14441.40841 | 14441.40841 | 1.21313 | 1.21313 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 33.16000 | 6.86360E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11663.00746 | 11663.00746 | 0.57352 | 0.57352 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 16469.43540 | 16469.43540 | 1.38350 | 1.38350 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10000 | 6.87148E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 17540.74362 | 17540.74362 | 0.86249 | 0.86249 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16665.06386 | 16665.06386 | 1.39993 | 1.39993 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11154.36087 | 11154.36087 | 0.54845 | 0.54845 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 7941.78419 | 7941.78419 | 0.52621 | 0.52621 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 34.33000 | 6.86546E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 75788.02792 | 75788.02792 | 5.02166 | 5.02166 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 34.00500 | 6.86494E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7751.11304 | 7751.11304 | 0.51358 | 0.51358 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 34.33000 | 6.86546E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369645.37478 | 369645.37478 | 24.49162 | 24.49162 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 26.27000 | 6.85284E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -5.20000 | 2.80840E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 144263.06 | 9.92504 | 9.92504 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 38743.50 | 2.20615 | 2.20615 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1338551.71 | 92.64690 | 92.64690 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 380607.77 | 33.11045 | 33.11045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 153033.86 | 10.49563 | 10.49563 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 38351.39 | 5.62164 | 5.62164 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 |
7 | CAV_BAS | Cooling | Sensible | 74581.82 | 5.55951 | 5.55951 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 56927.18 | 1.20016 | 1.20016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368445.38 | 24.49197 | 24.49197 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16051.03 | 0.33839 | 0.33839 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7961.61 | 0.52621 | 0.52621 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 741.49 | 1.56323E-002 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76012.53 | 5.02166 | 5.02166 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7414.91 | 0.15632 | 0.15632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7777.95 | 0.51358 | 0.51358 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 741.49 | 1.56323E-002 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.55951 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.04423 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31469 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26700 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61381 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83917 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21073E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.08270E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61381 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14092.30373 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08270E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.31761 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.83474 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33466 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.14107 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89243 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13846E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.08772E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.14107 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 369723.74679 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.08772E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12739.58408 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.70882 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33318 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61560 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88847 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14354E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76404E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.76772 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 80641.77906 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76404E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3138.00791 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12859 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21161 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20315 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56429 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80049E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.09917E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32938 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9596.20339 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09917E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 373.39762 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12299 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13705 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13027 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36546 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78002E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49690E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23497 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6842.94457 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49690E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 266.19702 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27171 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18780 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20347 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50080 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02876E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.60331E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40876 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11900.84357 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.60331E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 462.86672 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47098 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10463 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.90000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13092 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64150E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.90694E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15522 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4528.87992 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.90694E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 176.39447 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.90617 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21898 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02855 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58394 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73991E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.27381E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.71914 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 195373.85767 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.27381E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7592.53503 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.84621 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34645 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93259E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.83769E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.46159 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 129722.85410 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83769E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5041.03574 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.31888 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19387 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16500 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03262 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51699 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96524E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.23357E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.65575 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 193534.41066 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.23357E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7521.14346 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.90562 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11925 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10100 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30347 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31801 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19485E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64512E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.15829 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120919.76983 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64512E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4699.34233 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25450 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19037 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16200 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20323 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50766 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.00135E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.52789E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86947 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25270.32364 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.52789E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 981.76045 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21313 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12687 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10800 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13102 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33831 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00317E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.64617E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57352 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16668.19031 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.64617E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 647.54875 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38350 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17262 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20337 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46033 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20711E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.48360E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86249 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25067.85599 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.48360E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 973.90228 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39993 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10994 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.30000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13019 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46559E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.48703E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54845 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15940.70023 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48703E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 619.30989 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.52621 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.02166 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51358 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.49162 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.51925 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28161 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.03850 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28161 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.92504 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.92504 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22988 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.40581 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.80878 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 104.81162 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 33.11045 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 92.64690 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 92.64690 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35738 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.47994 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28341 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.95988 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.62164 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.49563 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.49563 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53562 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.55951 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.55951 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.55951 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.55951 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.55951 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.55951 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.49162 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.49162 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.49162 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.49162 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.49197 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.49197 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.52621 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.52621 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.52621 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.52621 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.52621 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.52621 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.02166 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.02166 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.02166 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.02166 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.02166 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.02166 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51358 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51358 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51358 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51358 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51358 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.51358 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.92504 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 92.64690 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.49563 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.55951 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.49197 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.52621 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.02166 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.51358 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.92504 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.94482 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.76806 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.26385E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 177642.69393 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.08056E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.92504 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 40450.75184 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.84861E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 884.73549 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.92504 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.08056E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.37280E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.84861E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 92.64690 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.24041 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.76811 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.27852E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1690975.72987 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.83617E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 92.64690 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 332336.88342 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.26988E-003 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7418.73739 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 92.64690 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.83617E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.84644E-006 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.26988E-003 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.49563 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.73474 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.77879 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.24685E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 184915.42056 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.28856E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.49563 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 28733.29562 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.28542E-004 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 652.46921 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.49563 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.28856E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.00417E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.28542E-004 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.55951 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.28999 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.20598 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.40453E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 101043.48516 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.88983E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.55951 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 239916.26524 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.24817E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7633.01341 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.55951 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.88983E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.64781E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.24817E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.49197 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.49197 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 465160.61317 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 259116.56071 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13918E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.49197 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.49197 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.49197 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.49197 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 465160.61317 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 465160.61317 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16051.03087 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.49197 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.49197 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 465160.61317 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13918E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16051.03087 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.28178E-004 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.52621 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52621 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9817.96531 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5499.74269 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40441E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.52621 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.52621 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.52621 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.52621 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9817.96531 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9817.96531 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 741.49113 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.52621 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52621 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9817.96531 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40441E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 741.49113 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.02166 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.02166 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93744.20483 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 52495.52088 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29579E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.02166 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.02166 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.02166 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.02166 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93744.20483 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93744.20483 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7414.91130 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.02166 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.02166 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93744.20483 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29579E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7414.91130 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51358 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51358 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9592.39803 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5370.74750 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34917E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51358 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51358 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51358 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51358 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9592.39803 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9592.39803 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 741.49113 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51358 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51358 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9592.39803 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34917E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 741.49113 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.16206E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9961.15585 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.16206E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.39448 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.16206E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.16206E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 258652.74064 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.07152E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.88582 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.07152E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 12140.21451 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1861261.85958 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1861261.86000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.07152E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.16206E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.39448 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.08103E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3448.22206 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.08103E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3448.22206 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.16206E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.12040E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1093733.91979 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1098921.16500 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.40258E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.16206E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.12040E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1093733.91979 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1098921.16500 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.40258E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.41629E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.69955 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.41629E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3576.48332 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.41629E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 56247.09497 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21099.86094 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 583390.12542 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 570636.93000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.41629E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10805 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.96620 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10805 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 26486.33295 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 46.15815 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1304923.65545 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.23163 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 163115.45693 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 46.15815 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1304923.65545 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.23163 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 163115.45693 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.64850E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.64850E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 19621.57 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 515064.99 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 112282.37 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13361.37 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9527.85 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16570.28 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6305.82 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 272031.65 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 180621.53 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 269470.46 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 168364.39 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35185.53 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23208.22 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34903.62 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22195.28 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 44264.42 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 373299.50 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 33795.40 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 258778.74 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 183252.80 | 127655.37 | 55597.42 | 0.70 | 18594.36 | 188.59 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1725853.22 | 1197866.81 | 527986.41 | 0.69 | 174471.32 | 1769.58 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 192225.55 | 134323.87 | 57901.67 | 0.70 | 19536.85 | 198.15 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 101526.57 | 70699.03 | 30827.55 | 0.70 | 9973.27 | 101.15 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.80 | 23.21 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.80 | 23.21 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2889660463 | 0.2508141593 | Pass | Pass | 1.5639701470 | 4.5819966864 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.2055801046E-002 | 0.1571361608 | Pass | Pass | 0.1473977758 | 0.3542911922 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.2894221811E-002 | 0.1155845920 | Pass | Pass | 0.1195226896 | 0.3245262809 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.0940062531E-002 | 5.3054420251E-002 | Pass | Pass | 6.3013709606E-002 | 0.2423828774 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 8.3830864006E-002 | 0.1135205861 | Pass | Pass | 0.1469319997 | 0.3542069229 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1197937858 | 0.1472363645 | Pass | Pass | 0.1483842970 | 0.3567066161 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2249599223 | 0.4015326937 | Pass | Pass | 0.2100930816 | 0.4894379726 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1265592964 | 0.2355681939 | Pass | Pass | 0.1688725800 | 0.4142160500 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.8487286424E-002 | 6.3355011575E-002 | Pass | Pass | 0.1189765362 | 0.3237776199 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.8146780331E-002 | 0.1160057163 | Pass | Pass | 0.1205106285 | 0.3269097106 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2148781470 | 0.3590876744 | Pass | Pass | 0.1775096907 | 0.4633750488 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.8241392412E-002 | 0.1237150933 | Pass | Pass | 0.1166339739 | 0.3171052707 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.8437858669E-002 | 3.8519625364E-002 | Pass | Pass | 6.2108001946E-002 | 0.2396960809 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.4378612345E-002 | 9.3670175000E-002 | Pass | Pass | 6.3111942680E-002 | 0.2431857166 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1643400618 | 0.1730755642 | Pass | Pass | 6.8844837207E-002 | 0.2591231973 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.4149316066E-002 | 0.1064073450 | Pass | Pass | 6.0119606863E-002 | 0.2296928740 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6455394287E-002 | 2.1179771354E-002 | Pass | Pass | 0.4215927838 | 1.5512912449 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9944697043E-002 | 2.5451479321E-002 | Pass | Pass | 0.3572198505 | 1.1355016730 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.4699408181E-002 | 5.9930901626E-002 | Pass | Pass | 6.4838724213E-002 | 0.2332728892 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.3951166380E-006 | 1.1170068121E-005 | Pass | Pass | 4.9969428836E-003 | 6.6331216379E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.2500755734E-006 | 9.3322871001E-006 | Pass | Pass | 2.0913667201E-002 | 1.4436794627E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4383582296E-002 | 1.8142041619E-002 | Pass | Pass | 0.1407076896 | 0.4020697349 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.8437464018E-005 | 1.0746982215E-004 | Pass | Pass | 6.8855433624E-005 | 1.0809135342E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5937.08 | 85.39 | 0.00 | 18177.78 | 19346.10 | 43546.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 1390.74 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.49 | 0.0000 | Y | 119.03 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.49 | 0.0000 | Y | 106.89 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.49 | 0.0000 | Y | 1068.94 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.49 | 0.0000 | Y | 106.89 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.69 | 0.0000 | Y | 7.71 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.64 | 0.0000 | Y | 4.96 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.40 | 0.0000 | Y | 7.61 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.37 | 0.0000 | Y | 4.90 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.65 | 0.0000 | Y | 76.98 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.61 | 0.0000 | Y | 49.53 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.38 | 0.0000 | Y | 76.06 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.35 | 0.0000 | Y | 48.96 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.65 | 0.0000 | Y | 7.70 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.61 | 0.0000 | Y | 4.95 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.38 | 0.0000 | Y | 7.61 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.35 | 0.0000 | Y | 4.90 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.66 | 0.0000 | Y | 33.70 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 52.86 | 168.00 | 51.50 | 0.0000 | Y | 2.51 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 52.86 | 168.00 | 51.50 | 0.0000 | Y | 25.11 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 52.86 | 168.00 | 51.50 | 0.0000 | Y | 2.51 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 556.43 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.77 | 41.77 | 101.55 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.77 | 62.77 | 10.84 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.77 | 46.49 | 150.23 | |
Exterior Lighting Total | 31088.59 | 262.62 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2147941.04 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1861261.86 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1098921.17 | 6.59 | 964004.50 | 5.87 | 6.80 | 23.21 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1098921.17 | 6.59 | 964004.50 | 5.87 | 6.80 | 23.21 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 570636.93 | 0.90 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1304923.66 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1304923.66 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 177642.69 | 183252.80 | 127655.37 | 55597.42 | 0.70 | - | 18594.36 | 188.59 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1690975.73 | 1725853.22 | 1197866.81 | 527986.41 | 0.69 | - | 174471.32 | 1769.58 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 184915.42 | 192225.55 | 134323.87 | 57901.67 | 0.70 | - | 19536.85 | 198.15 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 101043.49 | 101526.57 | 70699.03 | 30827.55 | 0.70 | - | 9973.27 | 101.15 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 465160.61 | 259116.56 | 206044.05 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9817.97 | 5499.74 | 4318.22 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93744.20 | 52495.52 | 41248.68 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9592.40 | 5370.75 | 4221.65 | 0.56 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 14092.30 | 19621.57 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 369723.75 | 515064.99 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 80641.78 | 112282.37 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9596.20 | 13361.37 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6842.94 | 9527.85 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11900.84 | 16570.28 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4528.88 | 6305.82 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 195373.86 | 272031.65 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 129722.85 | 180621.53 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 193534.41 | 269470.46 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 120919.77 | 168364.39 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 25270.32 | 35185.53 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16668.19 | 23208.22 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25067.86 | 34903.62 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15940.70 | 22195.28 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 40450.75 | 44264.42 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 332336.88 | 373299.50 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 28733.30 | 33795.40 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 239916.27 | 258778.74 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 465160.61 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9817.97 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93744.20 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9592.40 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 16051.03 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 741.49 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7414.91 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 741.49 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.93 | 21447.47 | 2160.95 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 92.65 | 200205.01 | 2160.95 | 1.00 | 1.08 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.50 | 22559.98 | 2149.46 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.56 | 9427.00 | 1695.65 | 1.00 | 1.16 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.49 | 40393.30 | 1649.25 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 589.41 | 1120.11 | 1.00 | 1.58 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.02 | 5624.80 | 1120.11 | 1.00 | 1.15 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 575.26 | 1120.11 | 1.00 | 1.59 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.061621 | 9961.16 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.040715 | 12140.21 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030810 | 3448.22 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030810 | 3448.22 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014163 | 3576.48 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.108052 | 26486.33 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 66783.93 | 66783.93 | 24.03 | 5.560 | 5.560 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00752 | 28.48 | 0.00686 | 1.200 | 0.00 |
CORE_BOTTOM | 72604.08 | 72604.08 | 29.09 | 6.044 | 6.044 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 28.48 | 0.00686 | 1.078 | 0.00 |
CORE_MID | 682881.35 | 682881.35 | 273.58 | 56.835 | 56.835 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 28.48 | 0.00686 | 10.778 | 0.00 |
CORE_TOP | 67956.98 | 67956.98 | 27.23 | 5.709 | 5.709 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00745 | 38.10 | 0.00687 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13434.86 | 13434.86 | 42.87 | 1.129 | 1.129 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00728 | 38.10 | 0.00687 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13368.27 | 13368.27 | 66.19 | 1.123 | 1.123 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00718 | 32.05 | 0.00686 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15138.51 | 15138.51 | 48.30 | 1.272 | 1.272 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00725 | 37.67 | 0.00687 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17510.89 | 17510.89 | 86.70 | 1.471 | 1.471 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00714 | 36.80 | 0.00687 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 129828.45 | 129828.45 | 414.24 | 10.906 | 10.906 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00727 | 38.10 | 0.00687 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 141019.73 | 141019.73 | 698.20 | 11.846 | 11.846 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00716 | 32.42 | 0.00686 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 146645.65 | 146645.65 | 467.89 | 12.319 | 12.319 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00724 | 37.77 | 0.00687 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 153631.20 | 153631.20 | 760.64 | 12.906 | 12.906 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00715 | 36.63 | 0.00687 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14933.73 | 14933.73 | 47.65 | 1.254 | 1.254 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00724 | 37.97 | 0.00687 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14441.41 | 14441.41 | 71.50 | 1.213 | 1.213 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00716 | 33.16 | 0.00686 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16469.44 | 16469.44 | 52.55 | 1.384 | 1.384 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00722 | 38.10 | 0.00687 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16665.06 | 16665.06 | 82.51 | 1.400 | 1.400 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00714 | 36.63 | 0.00687 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 7941.78 | 7941.78 | 219.37 | 0.526 | 0.526 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 27.00 | 27.00 | 0.00709 | 34.33 | 0.00687 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 75788.03 | 75788.03 | 2093.43 | 5.022 | 5.022 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00710 | 34.01 | 0.00686 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7751.11 | 7751.11 | 214.10 | 0.514 | 0.514 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 27.00 | 27.00 | 0.00709 | 34.33 | 0.00687 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369645.37 | 369645.37 | 471.68 | 24.492 | 24.492 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 26.27 | 0.00685 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 24.55 | 0.00281 | -5.20 | 0.00281 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 19.60 | 22.01 | 0.00281 | -5.20 | 0.00281 | 1.078 | 0.00 |
CORE_MID | 228774.76 | 228774.76 | 91.65 | 11.116 | 11.116 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 10.778 | 0.00 |
CORE_TOP | 56473.19 | 56473.19 | 22.62 | 2.768 | 2.768 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6722.91 | 6722.91 | 21.45 | 0.329 | 0.329 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4792.89 | 4792.89 | 23.73 | 0.235 | 0.235 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 8333.76 | 8333.76 | 26.59 | 0.409 | 0.409 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3175.82 | 3175.82 | 15.72 | 0.155 | 0.155 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00716 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 136735.61 | 136735.61 | 436.28 | 6.719 | 6.719 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -5.20 | 0.00281 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 90786.29 | 90786.29 | 449.49 | 4.462 | 4.462 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -5.20 | 0.00281 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 135449.71 | 135449.71 | 432.17 | 6.656 | 6.656 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -5.20 | 0.00281 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 84632.04 | 84632.04 | 419.02 | 4.158 | 4.158 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -5.20 | 0.00281 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17682.30 | 17682.30 | 56.42 | 0.869 | 0.869 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11663.01 | 11663.01 | 57.74 | 0.574 | 0.574 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17540.74 | 17540.74 | 55.97 | 0.862 | 0.862 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11154.36 | 11154.36 | 55.23 | 0.548 | 0.548 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -5.20 | 0.00281 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.38 | 0.00700 | -5.20 | 0.00281 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.19 | 0.00433 | -5.20 | 0.00281 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.32 | 0.00321 | -5.20 | 0.00281 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 27.00 | 0.00700 | -5.20 | 0.00281 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.93 | 9.93 | 2.21 | 2.21 | 9.9250 | 2.2816 | 9.9250 | 0.2299 | 0.3000 |
VAV_MID WITH REHEAT | 92.65 | 92.65 | 33.11 | 33.11 | 92.6469 | 33.1104 | 92.6469 | 0.3574 | 0.3000 |
VAV_TOP WITH REHEAT | 10.50 | 10.50 | 5.62 | 5.62 | 10.4956 | 5.6216 | 10.4956 | 0.5356 | 0.3000 |
CAV_BAS | 5.56 | 5.56 | 1.20 | 1.20 | 5.5595 | 5.5595 | 5.5595 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.49 | 24.49 | 0.34 | 0.34 | 24.4920 | 24.4916 | 24.4920 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.53 | 0.53 | 0.02 | 0.02 | 0.5262 | 0.5262 | 0.5262 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.02 | 5.02 | 0.16 | 0.16 | 5.0217 | 5.0217 | 5.0217 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.51 | 0.51 | 0.02 | 0.02 | 0.5136 | 0.5136 | 0.5136 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 14092.304 | 14092.304 | 1.613810 | 0.00030827 | 393.318 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 14092.30 | 14092.30 | 1.613810 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 14116.49 | 14116.49 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 369723.747 | 369723.747 | 16.141066 | 0.00808772 | 12739.584 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 369723.75 | 369723.75 | 16.141066 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 228774.76 | 0.00 | 370605.01 | 370605.01 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 80641.779 | 80641.779 | 2.767717 | 0.00176404 | 3138.008 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 80641.78 | 80641.78 | 2.767717 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 56473.19 | 0.00 | 80813.48 | 80813.48 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9596.203 | 9596.203 | 0.329378 | 0.00020992 | 373.398 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9596.20 | 9596.20 | 0.329378 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00752135 | 42.2043 | 6722.91 | 0.00 | 9616.64 | 9616.64 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6842.945 | 6842.945 | 0.234969 | 0.00014969 | 266.197 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6842.94 | 6842.94 | 0.234969 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00760223 | 42.6524 | 4792.89 | 0.00 | 6857.52 | 6857.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11900.844 | 11900.844 | 0.408763 | 0.00026033 | 462.867 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11900.84 | 11900.84 | 0.408763 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00769751 | 43.1799 | 8333.76 | 0.00 | 11926.19 | 11926.19 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4528.880 | 4528.880 | 0.155216 | 0.00009907 | 176.394 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4528.88 | 4528.88 | 0.155216 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00715594 | 40.1780 | 3175.82 | 0.00 | 4538.52 | 4538.52 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 195373.858 | 195373.858 | 6.719138 | 0.00427381 | 7592.535 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 195373.86 | 195373.86 | 6.719138 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00774023 | 43.4170 | 136735.61 | 0.00 | 195789.96 | 195789.96 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 129722.854 | 129722.854 | 4.461594 | 0.00283769 | 5041.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 129722.85 | 129722.85 | 4.461594 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00774127 | 43.4228 | 90786.29 | 0.00 | 129999.14 | 129999.14 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 193534.411 | 193534.411 | 6.655751 | 0.00423357 | 7521.143 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 193534.41 | 193534.41 | 6.655751 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00773715 | 43.3999 | 135449.71 | 0.00 | 193946.60 | 193946.60 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 120919.770 | 120919.770 | 4.158286 | 0.00264512 | 4699.342 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 120919.77 | 120919.77 | 4.158286 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00771689 | 43.2878 | 84632.04 | 0.00 | 121177.30 | 121177.30 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 25270.324 | 25270.324 | 0.869466 | 0.00055279 | 981.760 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25270.32 | 25270.32 | 0.869466 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775945 | 43.5238 | 17682.30 | 0.00 | 25324.15 | 25324.15 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16668.190 | 16668.190 | 0.573518 | 0.00036462 | 647.549 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16668.19 | 16668.19 | 0.573518 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775718 | 43.5113 | 11663.01 | 0.00 | 16703.69 | 16703.69 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 25067.856 | 25067.856 | 0.862489 | 0.00054836 | 973.902 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25067.86 | 25067.86 | 0.862489 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775753 | 43.5131 | 17540.74 | 0.00 | 25121.25 | 25121.25 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15940.700 | 15940.700 | 0.548454 | 0.00034870 | 619.310 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15940.70 | 15940.70 | 0.548454 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00774609 | 43.4499 | 11154.36 | 0.00 | 15974.65 | 15974.65 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 177642.694 | -999.000 | 9.925036 | 0.00508056 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 177642.69 | 172038.10 | 9.925036 | 26.94 | 14.91 | 0.00726385 | 10.77 | 8.47 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 20.4584 | 24.00 | 0.00736748 | 34.4601 | 115692.75 | 0.00 | 131400.76 | 131400.76 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 40450.752 | 40450.752 | 2.977511 | 0.00088486 | 884.735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 40450.75 | 40450.75 | 2.977511 | -0.15 | -1.18 | 0.00357998 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 68.1945 | 21.30 | 0.00618583 | 34.1384 | 23025.38 | 0.00 | 38557.15 | 38557.15 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1690975.730 | -999.000 | 92.646898 | 0.04836169 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1690975.73 | 1635526.92 | 92.646898 | 27.24 | 15.02 | 0.00727852 | 10.77 | 8.47 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 21.9176 | 24.00 | 0.00740003 | 34.6105 | 1051487.77 | 0.00 | 1253299.81 | 1253299.81 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 332336.883 | 332336.883 | 27.794070 | 0.00726988 | 7418.737 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 332336.88 | 332336.88 | 27.794070 | 1.41 | 0.44 | 0.00410608 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 73.0588 | 19.37 | 0.00729445 | 45.2798 | 257337.18 | 0.00 | 325207.11 | 325207.11 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 184915.421 | -999.000 | 10.495626 | 0.00528856 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 184915.42 | 179391.56 | 10.495626 | 26.73 | 14.82 | 0.00724685 | 10.78 | 8.48 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 19.3462 | 24.00 | 0.00733722 | 34.3201 | 124577.02 | 0.00 | 136511.15 | 136511.15 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 28733.296 | 28733.296 | 3.148688 | 0.00062854 | 652.469 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28733.30 | 28733.30 | 3.148688 | 4.10 | 2.48 | 0.00455607 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 64.4872 | 17.94 | 0.00766274 | 52.0031 | 32940.38 | 0.00 | 29445.29 | 29445.29 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 101043.485 | -999.000 | 5.559507 | 0.00288983 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 101043.49 | 96312.24 | 5.559507 | 27.29 | 15.14 | 0.00740453 | 11.21 | 8.66 | 0.00700000 | 37.45 | 0.00687043 | 17.97 | 21.5875 | 24.00 | 0.00757756 | 35.4312 | 58385.74 | 0.00 | 74699.98 | 74699.98 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 239916.265 | 239916.265 | 5.559507 | 0.00524817 | 7633.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 239916.27 | 239916.27 | 5.559507 | -1.12 | -2.86 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 21.5875 | 24.61 | 0.00280840 | 12.7542 | 0.00 | 0.00 | 185548.11 | 185548.11 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 465160.613 | 259116.561 | 24.491967 | 0.01139175 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 403554.30 | 401729.28 | -999.0 | 28.76 | 15.34 | 0.00704003 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | -999.0000 | 27.00 | 0.00704239 | 27.5805 | 369216.10 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9817.965 | 5499.743 | 0.526211 | 0.00024044 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 8489.86 | 8407.83 | -999.0 | 28.32 | 15.23 | 0.00708428 | 12.80 | 9.33 | 0.00700000 | 34.66 | 0.00686598 | 17.11 | -999.0000 | 27.00 | 0.00709096 | 27.7668 | 7937.33 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93744.205 | 52495.521 | 5.021655 | 0.00229579 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 81071.12 | 80252.33 | -999.0 | 28.32 | 15.23 | 0.00708814 | 12.80 | 9.33 | 0.00700000 | 34.33 | 0.00686546 | 17.01 | -999.0000 | 27.00 | 0.00709529 | 27.7838 | 75777.13 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9592.398 | 5370.747 | 0.513579 | 0.00023492 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 8296.49 | 8214.46 | -999.0 | 28.33 | 15.23 | 0.00708632 | 12.80 | 9.33 | 0.00700000 | 34.98 | 0.00686649 | 17.21 | -999.0000 | 27.00 | 0.00709323 | 27.7757 | 7745.90 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 465160.613 | 465160.613 | 24.491967 | 0.01139175 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 465160.61 | 465160.61 | 24.491967 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 1.3816 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9817.965 | 9817.965 | 0.526211 | 0.00024044 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9817.97 | 9817.97 | 0.526211 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.9707 | 26.75 | 0.00699994 | 27.8158 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93744.205 | 93744.205 | 5.021655 | 0.00229579 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 93744.20 | 93744.20 | 5.021655 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 3.1130 | 24.37 | 0.00433374 | 19.9177 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9592.398 | 9592.398 | 0.513579 | 0.00023492 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9592.40 | 9592.40 | 0.513579 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 3.0438 | 23.17 | 0.00320690 | 15.8759 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16051.031 | 16051.031 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16051.03 | 16051.03 | 24.491967 | -0.07 | -0.07 | 0.00694209 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 1.3816 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 741.49 | 741.49 | 0.526211 | -0.15 | -0.15 | 0.00687543 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.9707 | 26.75 | 0.00699994 | 27.8158 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7414.911 | 7414.911 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7414.91 | 7414.91 | 5.021655 | -0.16 | -0.18 | 0.00428626 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 3.1130 | 24.37 | 0.00433374 | 19.9177 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 741.49 | 741.49 | 0.513579 | -0.16 | -1.75 | 0.00319477 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 3.0438 | 23.17 | 0.00320690 | 15.8759 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 14092.304 | 14092.304 | 1.613810 | 0.00030827 | 393.318 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 0.7422 | 0.757137 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | Sensible | 14092.30 | 14092.30 | 1.0000 | 1.68535263 | 1.613810 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.30823809 | 60.00 | 48.89 | 11.11 | 0.000 | 14092.30 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 14116.49 | 14116.49 | 1.68535263 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 369723.747 | 369723.747 | 16.141066 | 0.00808772 | 12739.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 19.4723 | 19.864145 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 369723.75 | 369723.75 | 1.0000 | 16.85662774 | 16.141066 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 8.08689220 | 60.00 | 48.89 | 11.11 | 0.000 | 369723.75 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.84 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 228774.76 | 0.00 | 370605.01 | 370605.01 | 16.85662774 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.36 | 19.46 | 0.00800000 | 55045.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 80641.779 | 80641.779 | 2.767717 | 0.00176404 | 3138.008 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 4.2472 | 4.332640 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 80641.78 | 80641.78 | 1.0000 | 2.89041430 | 2.767717 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 1.76386121 | 60.00 | 48.89 | 11.11 | 0.000 | 80641.78 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 56473.19 | 0.00 | 80813.48 | 80813.48 | 2.89041430 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61019.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9596.203 | 9596.203 | 0.329378 | 0.00020992 | 373.398 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 0.5054 | 0.515575 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9596.20 | 9596.20 | 1.0000 | 0.34397990 | 0.329378 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.20989580 | 60.00 | 48.89 | 11.11 | 0.000 | 9596.20 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00752135 | 21.00 | 0.00752135 | 42.2043 | 6722.91 | 0.00 | 9616.64 | 9616.64 | 0.34397990 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6842.945 | 6842.945 | 0.234969 | 0.00014969 | 266.197 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 0.3604 | 0.367651 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6842.94 | 6842.94 | 1.0000 | 0.24538566 | 0.234969 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.14967433 | 60.00 | 48.89 | 11.11 | 0.000 | 6842.94 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00760223 | 21.00 | 0.00760223 | 42.6524 | 4792.89 | 0.00 | 6857.52 | 6857.52 | 0.24538566 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61005.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11900.844 | 11900.844 | 0.408763 | 0.00026033 | 462.867 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 0.6268 | 0.639397 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11900.84 | 11900.84 | 1.0000 | 0.42688444 | 0.408763 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.26030473 | 60.00 | 48.89 | 11.11 | 0.000 | 11900.84 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00769751 | 21.00 | 0.00769751 | 43.1799 | 8333.76 | 0.00 | 11926.19 | 11926.19 | 0.42688444 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4528.880 | 4528.880 | 0.155216 | 0.00009907 | 176.394 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 0.2385 | 0.243323 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4528.88 | 4528.88 | 1.0000 | 0.16209715 | 0.155216 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09905927 | 60.00 | 48.89 | 11.11 | 0.000 | 4528.88 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.86 | 0.00715594 | 21.00 | 0.00715594 | 40.1780 | 3175.82 | 0.00 | 4538.52 | 4538.52 | 0.16209715 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61058.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 195373.858 | 195373.858 | 6.719138 | 0.00427381 | 7592.535 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 10.2898 | 10.496850 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 195373.86 | 195373.86 | 1.0000 | 7.01700923 | 6.719138 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 4.27337259 | 60.00 | 48.89 | 11.11 | 0.000 | 195373.86 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774023 | 21.00 | 0.00774023 | 43.4170 | 136735.61 | 0.00 | 195789.96 | 195789.96 | 7.01700923 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 129722.854 | 129722.854 | 4.461594 | 0.00283769 | 5041.036 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 6.8321 | 6.969619 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 129722.85 | 129722.85 | 1.0000 | 4.65938410 | 4.461594 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 2.83740156 | 60.00 | 48.89 | 11.11 | 0.000 | 129722.85 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774127 | 21.00 | 0.00774127 | 43.4228 | 90786.29 | 0.00 | 129999.14 | 129999.14 | 4.65938410 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60960.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 193534.411 | 193534.411 | 6.655751 | 0.00423357 | 7521.143 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 10.1929 | 10.398022 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 193534.41 | 193534.41 | 1.0000 | 6.95081208 | 6.655751 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 4.23313874 | 60.00 | 48.89 | 11.11 | 0.000 | 193534.41 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773715 | 21.00 | 0.00773715 | 43.3999 | 135449.71 | 0.00 | 193946.60 | 193946.60 | 6.95081208 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 120919.770 | 120919.770 | 4.158286 | 0.00264512 | 4699.342 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 6.3685 | 6.496655 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 120919.77 | 120919.77 | 1.0000 | 4.34263027 | 4.158286 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 2.64485349 | 60.00 | 48.89 | 11.11 | 0.000 | 120919.77 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771689 | 21.00 | 0.00771689 | 43.2878 | 84632.04 | 0.00 | 121177.30 | 121177.30 | 4.34263027 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60964.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25270.324 | 25270.324 | 0.869466 | 0.00055279 | 981.760 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 1.3309 | 1.357698 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25270.32 | 25270.32 | 1.0000 | 0.90801062 | 0.869466 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.55273264 | 60.00 | 48.89 | 11.11 | 0.000 | 25270.32 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775945 | 21.00 | 0.00775945 | 43.5238 | 17682.30 | 0.00 | 25324.15 | 25324.15 | 0.90801062 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60949.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16668.190 | 16668.190 | 0.573518 | 0.00036462 | 647.549 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 0.8779 | 0.895532 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16668.19 | 16668.19 | 1.0000 | 0.59894255 | 0.573518 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.36457993 | 60.00 | 48.89 | 11.11 | 0.000 | 16668.19 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775718 | 21.00 | 0.00775718 | 43.5113 | 11663.01 | 0.00 | 16703.69 | 16703.69 | 0.59894255 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60948.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25067.856 | 25067.856 | 0.862489 | 0.00054836 | 973.902 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 1.3202 | 1.346820 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25067.86 | 25067.86 | 1.0000 | 0.90072445 | 0.862489 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.54830411 | 60.00 | 48.89 | 11.11 | 0.000 | 25067.86 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775753 | 21.00 | 0.00775753 | 43.5131 | 17540.74 | 0.00 | 25121.25 | 25121.25 | 0.90072445 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60949.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15940.700 | 15940.700 | 0.548454 | 0.00034870 | 619.310 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 0.8395 | 0.856446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15940.70 | 15940.70 | 1.0000 | 0.57276753 | 0.548454 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.34866769 | 60.00 | 48.89 | 11.11 | 0.000 | 15940.70 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774609 | 21.00 | 0.00774609 | 43.4499 | 11154.36 | 0.00 | 15974.65 | 15974.65 | 0.57276753 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60950.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 177642.694 | -999.000 | 9.925036 | 0.00508056 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3431 | 1004.8586 | 1.0443 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.925036 | 10.36502994 | 4197.9300 | 999.8980 | 61.61435294 | 15.00 | 6.67 | 8.33 | 2154577.33 | 8.2449 | 8.244898 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 177642.69 | 172038.10 | 1.0000 | 10.36502994 | 9.925036 | 26.94 | 14.91 | 0.00726385 | 45605.5 | 10.77 | 8.47 | 0.00700000 | 28466.9 | 5.08004029 | 6.67 | 15.00 | 8.33 | 21447.474 | 156195.22 | 38.10 | 0.00687148 | 18.17 | 2.03050000 | 20.4584 | 24.00 | 0.00736748 | 24.00 | 0.00736748 | 34.4601 | 115692.75 | 0.00 | 131400.76 | 131400.76 | 10.36502994 | 26.94 | 16.37 | 0.00726385 | 45605.5 | 14.50 | 11.56 | 0.00726385 | 32928.2 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 40450.752 | 40450.752 | 2.977511 | 0.00088486 | 884.735 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.925036 | 10.36502994 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 2.1304 | 2.173297 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 40450.75 | 40450.75 | 1.0000 | 3.10950898 | 2.977511 | -0.15 | -1.18 | 0.00357998 | 8805.8 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 0.88477106 | 60.00 | 48.89 | 11.11 | 0.000 | 40450.75 | -5.20 | 0.00280840 | -5.20 | 2.03050000 | 68.1945 | 10.69 | 0.00523436 | 21.30 | 0.00618583 | 34.1384 | 23025.38 | 0.00 | 38557.15 | 38557.15 | 3.10950898 | 2.80 | 1.36 | 0.00357998 | 11785.5 | 15.06 | 7.77 | 0.00357998 | 24185.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1690975.730 | -999.000 | 92.646898 | 0.04836169 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3704 | 1004.8586 | 1.0443 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.646898 | 96.75409589 | 4197.9300 | 999.8980 | 61.61435294 | 15.00 | 6.67 | 8.33 | 2154577.33 | 78.4829 | 78.482945 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1690975.73 | 1635526.92 | 1.0000 | 96.75409589 | 92.646898 | 27.24 | 15.02 | 0.00727852 | 45944.0 | 10.77 | 8.47 | 0.00700000 | 28466.9 | 48.35675843 | 6.67 | 15.00 | 8.33 | 200205.014 | 1490770.72 | 38.10 | 0.00687148 | 18.17 | 20.30600000 | 21.9176 | 24.00 | 0.00740003 | 24.00 | 0.00740003 | 34.6105 | 1051487.77 | 0.00 | 1253299.81 | 1253299.81 | 96.75409589 | 27.24 | 16.49 | 0.00727852 | 45944.0 | 14.52 | 11.58 | 0.00727852 | 32990.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 332336.883 | 332336.883 | 27.794070 | 0.00726988 | 7418.737 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.646898 | 96.75409589 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 17.5032 | 17.855461 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 332336.88 | 332336.88 | 1.0000 | 29.02622877 | 27.794070 | 1.41 | 0.44 | 0.00410608 | 11692.4 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 7.26913696 | 60.00 | 48.89 | 11.11 | 0.000 | 332336.88 | -5.20 | 0.00280840 | -5.20 | 20.30600000 | 73.0588 | 19.32 | 0.00762510 | 19.37 | 0.00729445 | 45.2798 | 257337.18 | 0.00 | 325207.11 | 325207.11 | 29.02622877 | 2.80 | 2.09 | 0.00410608 | 13104.0 | 13.87 | 7.82 | 0.00410608 | 24307.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 184915.421 | -999.000 | 10.495626 | 0.00528856 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3115 | 1004.8586 | 1.0443 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.495626 | 10.96091516 | 4197.9300 | 999.8980 | 61.61435294 | 15.00 | 6.67 | 8.33 | 2154577.33 | 8.5824 | 8.582445 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 184915.42 | 179391.56 | 1.0000 | 10.96091516 | 10.495626 | 26.73 | 14.82 | 0.00724685 | 45348.2 | 10.78 | 8.48 | 0.00700000 | 28477.8 | 5.28801813 | 6.67 | 15.00 | 8.33 | 22559.976 | 162355.44 | 38.10 | 0.00687148 | 18.17 | 2.03050000 | 19.3462 | 24.00 | 0.00733722 | 24.00 | 0.00733722 | 34.3201 | 124577.02 | 0.00 | 136511.15 | 136511.15 | 10.96091516 | 26.73 | 16.28 | 0.00724685 | 45348.2 | 14.50 | 11.54 | 0.00724685 | 32893.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28733.296 | 28733.296 | 3.148688 | 0.00062854 | 652.469 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.495626 | 10.96091516 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 1.5133 | 1.543754 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 28733.30 | 28733.30 | 1.0000 | 3.28827455 | 3.148688 | 4.10 | 2.48 | 0.00455607 | 15553.2 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 0.62847752 | 60.00 | 48.89 | 11.11 | 0.000 | 28733.30 | -5.20 | 0.00280840 | -5.20 | 2.03050000 | 64.4872 | 21.00 | 0.00772966 | 17.94 | 0.00766274 | 52.0031 | 32940.38 | 0.00 | 29445.29 | 29445.29 | 3.28827455 | 2.80 | 2.71 | 0.00455607 | 14231.7 | 11.64 | 7.28 | 0.00455607 | 23186.4 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 101043.485 | -999.000 | 5.559507 | 0.00288983 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6047 | 1004.8586 | 1.0443 | CAV_BAS FAN | Fan:ConstantVolume | 5.559507 | 5.80596918 | 4197.9300 | 999.8980 | 61.61435294 | 15.00 | 6.67 | 8.33 | 2154577.33 | 4.6897 | 4.689713 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 101043.49 | 96312.24 | 1.0000 | 5.80596918 | 5.559507 | 27.29 | 15.14 | 0.00740453 | 46316.0 | 11.21 | 8.66 | 0.00700000 | 28912.6 | 2.88953609 | 6.67 | 15.00 | 8.33 | 9427.002 | 91616.48 | 37.45 | 0.00687043 | 17.97 | 1.20015641 | 21.5875 | 24.00 | 0.00757756 | 24.00 | 0.00757756 | 35.4312 | 58385.74 | 0.00 | 74699.98 | 74699.98 | 5.80596918 | 27.29 | 16.61 | 0.00740453 | 46316.0 | 14.66 | 11.77 | 0.00740453 | 33449.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 239916.265 | 239916.265 | 5.559507 | 0.00524817 | 7633.013 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | CAV_BAS FAN | Fan:ConstantVolume | 5.559507 | 5.80596918 | 4197.9300 | 999.8980 | 40.71100153 | 48.89 | 60.00 | 11.11 | 1898720.49 | 12.6357 | 12.889979 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 239916.27 | 239916.27 | 1.0000 | 5.80596918 | 5.559507 | -1.12 | -2.86 | 0.00280840 | 5889.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 5.24763960 | 60.00 | 48.89 | 11.11 | 0.000 | 239916.27 | -5.20 | 0.00280840 | -5.20 | 1.20015641 | 21.5875 | 0.00 | 0.00280840 | 24.61 | 0.00280840 | 12.7542 | 0.00 | 0.00 | 185548.11 | 185548.11 | 5.80596918 | 12.80 | 5.73 | 0.00280840 | 19952.4 | 44.44 | 18.60 | 0.00280840 | 51910.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 465160.613 | 259116.561 | 24.491967 | 0.01139175 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9271 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 403554.30 | 401729.28 | 0.8676 | -999.0 | -999.0 | 28.76 | 15.34 | 0.00704003 | 46880.2 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 403554.30 | 38.10 | 0.00687148 | 18.17 | 0.33839277 | -999.0000 | 27.00 | 0.00704239 | 27.00 | 0.00704239 | 27.5805 | 369216.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9817.965 | 5499.743 | 0.526211 | 0.00024044 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0093 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 8489.86 | 8407.83 | 0.8647 | -999.0 | -999.0 | 28.32 | 15.23 | 0.00708428 | 46545.0 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8489.86 | 34.66 | 0.00686598 | 17.11 | 0.01563234 | -999.0000 | 27.00 | 0.00709096 | 27.00 | 0.00709096 | 27.7668 | 7937.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93744.205 | 52495.521 | 5.021655 | 0.00229579 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0165 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 81071.12 | 80252.33 | 0.8648 | -999.0 | -999.0 | 28.32 | 15.23 | 0.00708814 | 46555.4 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81071.12 | 34.33 | 0.00686546 | 17.01 | 0.15632344 | -999.0000 | 27.00 | 0.00709529 | 27.00 | 0.00709529 | 27.7838 | 75777.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9592.398 | 5370.747 | 0.513579 | 0.00023492 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0131 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 8296.49 | 8214.46 | 0.8649 | -999.0 | -999.0 | 28.33 | 15.23 | 0.00708632 | 46566.0 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8296.49 | 34.98 | 0.00686649 | 17.21 | 0.01563234 | -999.0000 | 27.00 | 0.00709323 | 27.00 | 0.00709323 | 27.7757 | 7745.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 465160.613 | 465160.613 | 24.491967 | 0.01139175 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 465160.61 | 465160.61 | 1.0000 | 25.57773827 | 24.491967 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 465160.61 | -5.20 | 0.00280840 | -5.20 | 0.33839277 | 1.3816 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9817.965 | 9817.965 | 0.526211 | 0.00024044 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9817.97 | 9817.97 | 1.0000 | 0.54953889 | 0.526211 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9817.97 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 2.9707 | 0.00 | 0.00699994 | 26.75 | 0.00699994 | 27.8158 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93744.205 | 93744.205 | 5.021655 | 0.00229579 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 93744.20 | 93744.20 | 1.0000 | 5.24427414 | 5.021655 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93744.20 | -5.20 | 0.00280840 | -5.20 | 0.15632344 | 3.1130 | 0.00 | 0.00433374 | 24.37 | 0.00433374 | 19.9177 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9592.398 | 9592.398 | 0.513579 | 0.00023492 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9592.40 | 9592.40 | 1.0000 | 0.53634719 | 0.513579 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9592.40 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 3.0438 | 0.00 | 0.00320690 | 23.17 | 0.00320690 | 15.8759 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16051.031 | 16051.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.491967 | 25.57773827 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16051.03 | 16051.03 | 1.0000 | 25.57773827 | 24.491967 | -0.07 | -0.07 | 0.00694209 | 17288.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16051.03 | -5.20 | 0.00280840 | -5.20 | 0.33839277 | 1.3816 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.526211 | 0.54953889 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 741.49 | 741.49 | 1.0000 | 0.54953889 | 0.526211 | -0.15 | -0.15 | 0.00687543 | 17037.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 741.49 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 2.9707 | 0.00 | 0.00699994 | 26.75 | 0.00699994 | 27.8158 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7414.911 | 7414.911 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.021655 | 5.24427414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7414.91 | 7414.91 | 1.0000 | 5.24427414 | 5.021655 | -0.16 | -0.18 | 0.00428626 | 10555.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7414.91 | -5.20 | 0.00280840 | -5.20 | 0.15632344 | 3.1130 | 0.00 | 0.00433374 | 24.37 | 0.00433374 | 19.9177 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.513579 | 0.53634719 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 741.49 | 741.49 | 1.0000 | 0.53634719 | 0.513579 | -0.16 | -1.75 | 0.00319477 | 7830.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 741.49 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 3.0438 | 0.00 | 0.00320690 | 23.17 | 0.00320690 | 15.8759 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.93 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 92.65 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.50 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.56 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.49 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2685.83 | 1871.67 | 551.00 |
CORE_BOTTOM | 2555.00 | 1206.83 | 171.00 |
CORE_MID | 2074.33 | 2779.00 | 268.83 |
CORE_TOP | 2302.00 | 3296.50 | 585.33 |
PERIMETER_BOT_ZN_3 | 2325.00 | 2925.00 | 247.17 |
PERIMETER_BOT_ZN_2 | 2765.17 | 2469.33 | 395.00 |
PERIMETER_BOT_ZN_1 | 3030.83 | 1927.17 | 394.50 |
PERIMETER_BOT_ZN_4 | 3452.50 | 1507.50 | 546.33 |
PERIMETER_MID_ZN_3 | 2751.00 | 3463.00 | 969.83 |
PERIMETER_MID_ZN_2 | 2484.33 | 2573.33 | 690.83 |
PERIMETER_MID_ZN_1 | 2974.33 | 2258.17 | 562.67 |
PERIMETER_MID_ZN_4 | 2913.17 | 2809.00 | 677.83 |
PERIMETER_TOP_ZN_3 | 3434.67 | 3648.00 | 1716.00 |
PERIMETER_TOP_ZN_2 | 3321.17 | 3145.83 | 1196.00 |
PERIMETER_TOP_ZN_1 | 3158.83 | 2600.17 | 927.67 |
PERIMETER_TOP_ZN_4 | 3348.67 | 3105.83 | 1236.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 562.50 | 562.50 |
DATACENTER_MID_ZN_6 | 5918.00 | 163.83 | 163.83 |
DATACENTER_TOP_ZN_6 | 5462.83 | 294.83 | 226.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5775.33 | 5775.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5903.33 | 5820.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 83.17 | 0.00 | 23.67 |
CORE_BOTTOM | 0.00 | 40.17 | 0.00 | 35.67 |
CORE_MID | 0.00 | 19.50 | 0.00 | 19.50 |
CORE_TOP | 0.50 | 30.50 | 0.00 | 30.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 69.67 | 0.00 | 61.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 132.17 | 0.00 | 126.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 183.33 | 0.00 | 173.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 302.00 | 0.00 | 160.50 |
PERIMETER_MID_ZN_3 | 3.50 | 43.33 | 0.00 | 38.83 |
PERIMETER_MID_ZN_2 | 2.67 | 114.00 | 0.00 | 97.17 |
PERIMETER_MID_ZN_1 | 0.33 | 169.67 | 0.00 | 164.67 |
PERIMETER_MID_ZN_4 | 0.50 | 123.50 | 0.00 | 80.67 |
PERIMETER_TOP_ZN_3 | 24.83 | 68.00 | 1.67 | 56.33 |
PERIMETER_TOP_ZN_2 | 19.83 | 128.67 | 0.17 | 110.00 |
PERIMETER_TOP_ZN_1 | 13.83 | 134.67 | 0.00 | 120.00 |
PERIMETER_TOP_ZN_4 | 11.83 | 144.67 | 0.00 | 94.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 272.17 | 0.00 | 220.00 |
DATACENTER_MID_ZN_6 | 0.00 | 207.83 | 0.00 | 170.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 161.33 | 0.00 | 126.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 845.83 | 0.00 | 670.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 27.50 | 1407.33 | 1.67 | 1042.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.296 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.907 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.684 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.649 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.846 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.298 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.378 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.886 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.709 | 0.094 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.168 | 0.103 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.274 | 0.094 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.160 | 0.097 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.712 | 0.116 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.213 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.276 | 0.117 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.158 | 0.120 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 30.827 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 54485400.63 | 0.00 | 54485400.63 | 0.00 | 54485400.63 | 37848132.68 | 3885.89 | 1682.00 | 3192.11 | 317.96 |
CORE_BOTTOM | 39665948.63 | 0.00 | 39665948.63 | 0.00 | 39665948.63 | 33990283.35 | 4904.91 | 24.47 | 3830.62 | 586.05 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 5512.94 | 184.09 | 3062.97 | 174.62 |
CORE_TOP | 26966514.52 | 0.00 | 26966514.52 | 0.00 | 26966514.52 | 33990283.35 | 5664.92 | 305.83 | 2789.25 | 240.82 |
PERIMETER_BOT_ZN_3 | 4651483.74 | 0.00 | 4651483.74 | 398322.03 | 5049805.78 | 4267819.30 | 4336.74 | 77.01 | 4346.25 | 586.05 |
PERIMETER_BOT_ZN_2 | 4454894.88 | 0.00 | 4454894.88 | 265547.84 | 4720442.72 | 2750345.05 | 4091.67 | 70.28 | 4598.04 | 586.05 |
PERIMETER_BOT_ZN_1 | 7329235.39 | 0.00 | 7329235.39 | 398322.03 | 7727557.42 | 4267912.63 | 3831.07 | 59.43 | 4869.50 | 586.05 |
PERIMETER_BOT_ZN_4 | 6518485.54 | 0.00 | 6518485.54 | 265547.84 | 6784033.38 | 2750345.05 | 3604.39 | 48.99 | 5106.62 | 586.05 |
PERIMETER_MID_ZN_3 | 36757363.42 | 0.00 | 36757363.42 | 934163.77 | 37691527.19 | 42678193.03 | 4579.61 | 181.48 | 3998.91 | 174.62 |
PERIMETER_MID_ZN_2 | 38538714.75 | 0.00 | 38538714.75 | 622775.42 | 39161490.17 | 27503450.52 | 4471.52 | 251.31 | 4037.17 | 898.03 |
PERIMETER_MID_ZN_1 | 65138027.90 | 0.00 | 65138027.90 | 934163.77 | 66072191.67 | 42679126.28 | 4015.42 | 106.62 | 4637.96 | 174.62 |
PERIMETER_MID_ZN_4 | 38433210.27 | 0.00 | 38433210.27 | 622775.42 | 39055985.69 | 27503450.52 | 4282.29 | 251.15 | 4226.56 | 174.62 |
PERIMETER_TOP_ZN_3 | 3707122.61 | 0.00 | 3707122.61 | 1159847.75 | 4866970.35 | 4267819.30 | 4229.61 | 222.00 | 4308.38 | 240.82 |
PERIMETER_TOP_ZN_2 | 4005851.16 | 0.00 | 4005851.16 | 773231.30 | 4779082.46 | 2750345.05 | 4107.41 | 200.83 | 4451.76 | 240.82 |
PERIMETER_TOP_ZN_1 | 6537275.94 | 0.00 | 6537275.94 | 1159847.75 | 7697123.68 | 4267912.63 | 3999.97 | 189.29 | 4570.74 | 240.82 |
PERIMETER_TOP_ZN_4 | 3851590.58 | 0.00 | 3851590.58 | 773231.30 | 4624821.88 | 2750345.05 | 4123.46 | 469.21 | 4167.33 | 240.82 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.51E+09 | 0.00 | 0.51E+09 | 0.00 | 0.51E+09 | 10671554.30 | 380.58 | 944.61 | 7434.81 | 2655.14 |
Total Facility | 0.53E+10 | 0.00 | 0.53E+10 | 36332681.67 | 0.54E+10 | 0.50E+10 | 7186.84 | 4363.93 | 8378.83 | 3378.87 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3958 | 0.0000 | 2.3958 | 0.0000 | 2.3958 | 1.2002 | 1292.64 | 1680.15 | 2970.20 |
CORE_BOTTOM | 1.6932 | 0.0000 | 1.6932 | 0.0000 | 1.6932 | 1.0778 | 2628.58 | 23.66 | 3290.76 |
CORE_MID | 12.7679 | 0.0000 | 12.7679 | 0.0000 | 12.7679 | 10.7782 | 2837.43 | 183.98 | 2921.60 |
CORE_TOP | 1.2132 | 0.0000 | 1.2132 | 0.0000 | 1.2132 | 1.0778 | 2990.08 | 305.83 | 2647.09 |
PERIMETER_BOT_ZN_3 | 0.1981 | 0.0000 | 0.1981 | 0.0094 | 0.2075 | 0.1353 | 2053.74 | 76.11 | 3813.15 |
PERIMETER_BOT_ZN_2 | 0.1959 | 0.0000 | 0.1959 | 0.0063 | 0.2022 | 0.0872 | 1808.18 | 69.29 | 4065.53 |
PERIMETER_BOT_ZN_1 | 0.3231 | 0.0000 | 0.3231 | 0.0094 | 0.3325 | 0.1353 | 1548.36 | 58.29 | 4336.35 |
PERIMETER_BOT_ZN_4 | 0.2847 | 0.0000 | 0.2847 | 0.0063 | 0.2910 | 0.0872 | 1323.66 | 48.14 | 4571.19 |
PERIMETER_MID_ZN_3 | 1.6634 | 0.0000 | 1.6634 | 0.0220 | 1.6854 | 1.3533 | 1906.36 | 181.37 | 3855.27 |
PERIMETER_MID_ZN_2 | 1.7633 | 0.0000 | 1.7633 | 0.0156 | 1.7789 | 0.8721 | 1472.27 | 247.61 | 3314.12 |
PERIMETER_MID_ZN_1 | 2.9891 | 0.0000 | 2.9891 | 0.0220 | 3.0111 | 1.3533 | 1340.17 | 106.48 | 4496.34 |
PERIMETER_MID_ZN_4 | 1.7510 | 0.0000 | 1.7510 | 0.0147 | 1.7656 | 0.8721 | 1607.25 | 250.80 | 4084.94 |
PERIMETER_TOP_ZN_3 | 0.1672 | 0.0000 | 0.1672 | 0.0273 | 0.1945 | 0.1353 | 1559.43 | 221.79 | 4161.77 |
PERIMETER_TOP_ZN_2 | 0.1831 | 0.0000 | 0.1831 | 0.0182 | 0.2014 | 0.0872 | 1437.81 | 200.49 | 4304.71 |
PERIMETER_TOP_ZN_1 | 0.2995 | 0.0000 | 0.2995 | 0.0273 | 0.3268 | 0.1353 | 1326.87 | 189.10 | 4427.03 |
PERIMETER_TOP_ZN_4 | 0.1750 | 0.0000 | 0.1750 | 0.0182 | 0.1932 | 0.0872 | 1450.79 | 469.08 | 4023.13 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 15.8749 | 0.0000 | 15.8749 | 0.0000 | 15.8749 | 0.3384 | 218.72 | 944.61 | 4779.67 |
Total Facility | 233.5149 | 0.0000 | 233.5149 | 0.8655 | 234.3804 | 158.4706 | 4369.84 | 4358.82 | 5723.38 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 68295329.76 | 0.00 | 68295329.76 | 48026705.38 | 3347.94 | 5.28 | 5406.78 | 586.05 |
VAV_MID WITH REHEAT | 0.50E+09 | 0.00 | 0.50E+09 | 0.48E+09 | 3899.64 | 3.04 | 4857.32 | 174.62 |
VAV_TOP WITH REHEAT | 49152867.53 | 0.00 | 49152867.53 | 48026705.38 | 3941.28 | 2.80 | 4815.92 | 240.82 |
CAV_BAS | 59423345.25 | 0.00 | 59423345.25 | 37848132.68 | 3872.92 | 3.14 | 4883.94 | 317.96 |
AIRLOOP DATACENTER BASEMENT | 0.56E+09 | 0.00 | 0.56E+09 | 10671554.30 | 380.58 | 0.00 | 8379.42 | 2655.14 |
AIRLOOP DATACENTER BOT | 266436.27 | 0.00 | 266436.27 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2664362.65 | 0.00 | 2664362.65 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 266436.27 | 0.00 | 266436.27 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.9393 | 0.0000 | 2.9393 | 1.5229 | 1078.41 | 3.68 | 4860.91 |
VAV_MID WITH REHEAT | 22.8336 | 0.0000 | 22.8336 | 15.2292 | 1225.40 | 3.02 | 4714.58 |
VAV_TOP WITH REHEAT | 2.2226 | 0.0000 | 2.2226 | 1.5229 | 1266.58 | 2.77 | 4673.65 |
CAV_BAS | 2.6130 | 0.0000 | 2.6130 | 1.2002 | 1288.10 | 0.75 | 4654.15 |
AIRLOOP DATACENTER BASEMENT | 17.3136 | 0.0000 | 17.3136 | 0.3384 | 218.72 | 0.00 | 5724.28 |
AIRLOOP DATACENTER BOT | 0.0125 | 0.0000 | 0.0125 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1245 | 0.0000 | 0.1245 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0125 | 0.0000 | 0.0125 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 572.24 | 3193.04 | 0.00 | 0.00 | 0.00 | 1752.19 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 535.98 | 2569.10 | 0.00 | 0.00 | 0.00 | 1903.09 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 65.60 | 2724.40 | 0.00 | 0.00 | 0.00 | 2263.22 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1677.86 | 3308.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 944.61 | 7434.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.2148 | 4.9865 | 0.0000 | 0.0000 | 0.0000 | 1.8193 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 22.0016 | 37.2232 | 0.0000 | 0.0000 | 0.0000 | 18.2523 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.0223 | 3.6355 | 0.0000 | 0.0000 | 0.0000 | 1.7871 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3096 | 4.4591 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3693 | 21.4576 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0171 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1705 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0171 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1187 |
Fields with Defaults | 3885 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26715.72 | 297259.65 | 16-JAN-04:00 | 1821904.85 | 23-AUG-15:20 |
Electricity:Building | 16443.85 | 215622.15 | 07-MAY-17:10 | 953312.41 | 01-DEC-17:00 |
Electricity:Zone:BASEMENT | 543.42 | 14037.38 | 01-JAN-00:10 | 23894.81 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16443.85 | 215622.15 | 07-MAY-17:10 | 953312.41 | 01-DEC-17:00 |
InteriorLights:Electricity | 1767.45 | 8365.99 | 01-JAN-09:00 | 174940.73 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 119.03 | 579.83 | 01-JAN-00:10 | 10437.26 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1767.45 | 8365.99 | 01-JAN-09:00 | 174940.73 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 1767.45 | 8365.99 | 01-JAN-09:00 | 174940.73 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 119.03 | 579.83 | 01-JAN-00:10 | 10437.26 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1767.45 | 8365.99 | 01-JAN-09:00 | 174940.73 | 22-NOV-17:00 |
Electricity:Zone:CORE_BOTTOM | 396.51 | 4973.96 | 01-JAN-00:10 | 26580.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 106.89 | 520.73 | 01-JAN-00:10 | 9373.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 106.89 | 520.73 | 01-JAN-00:10 | 9373.40 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3965.07 | 49739.46 | 01-JAN-00:10 | 265799.59 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1068.94 | 5207.29 | 01-JAN-00:10 | 93733.96 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1068.94 | 5207.29 | 01-JAN-00:10 | 93733.96 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 396.51 | 4973.95 | 01-JAN-00:10 | 26579.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 106.89 | 520.73 | 01-JAN-00:10 | 9373.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 106.89 | 520.73 | 01-JAN-00:10 | 9373.40 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 44.08 | 590.28 | 02-APR-17:10 | 3337.48 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.71 | 31.11 | 01-JAN-09:00 | 1176.92 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.71 | 31.11 | 01-JAN-09:00 | 1176.92 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.39 | 380.40 | 30-APR-17:10 | 2150.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.96 | 20.05 | 01-JAN-08:10 | 758.45 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.96 | 20.05 | 01-JAN-08:10 | 758.45 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.98 | 590.29 | 12-MAR-17:10 | 3337.53 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.61 | 31.11 | 01-JAN-08:10 | 1176.95 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.61 | 31.11 | 01-JAN-08:10 | 1176.95 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.34 | 380.40 | 12-MAR-17:10 | 2150.79 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.90 | 20.05 | 01-JAN-09:00 | 758.45 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.90 | 20.05 | 01-JAN-09:00 | 758.45 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 440.63 | 5902.80 | 19-MAR-17:10 | 33374.75 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 76.98 | 311.09 | 01-JAN-08:50 | 11769.23 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 76.98 | 311.09 | 01-JAN-08:50 | 11769.23 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 283.88 | 3803.99 | 30-APR-17:10 | 21507.96 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 49.53 | 200.48 | 01-JAN-08:10 | 7584.54 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 49.53 | 200.48 | 01-JAN-08:10 | 7584.54 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 439.72 | 5902.89 | 12-MAR-17:10 | 33375.34 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 76.06 | 311.10 | 01-JAN-08:10 | 11769.49 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 76.06 | 311.10 | 01-JAN-08:10 | 11769.49 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 283.31 | 3803.96 | 12-MAR-17:10 | 21507.87 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.96 | 200.48 | 01-JAN-08:50 | 7584.54 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.96 | 200.48 | 01-JAN-08:50 | 7584.54 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 44.06 | 590.28 | 19-MAR-17:10 | 3337.48 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.70 | 31.11 | 01-JAN-08:50 | 1176.92 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.70 | 31.11 | 01-JAN-08:50 | 1176.92 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.39 | 380.40 | 23-APR-17:10 | 2150.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.95 | 20.05 | 01-JAN-08:00 | 758.45 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.95 | 20.05 | 01-JAN-08:00 | 758.45 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.97 | 590.29 | 12-MAR-17:10 | 3337.53 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.61 | 31.11 | 01-JAN-08:10 | 1176.95 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.61 | 31.11 | 01-JAN-08:10 | 1176.95 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.33 | 380.40 | 12-MAR-17:10 | 2150.79 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.90 | 20.05 | 01-JAN-08:50 | 758.45 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.90 | 20.05 | 01-JAN-08:50 | 758.45 | 22-NOV-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7528.56 | 95071.62 | 01-JAN-00:10 | 382575.38 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 33.70 | 163.49 | 01-JAN-00:10 | 2942.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 33.70 | 163.49 | 01-JAN-00:10 | 2942.86 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.39 | 1960.78 | 01-JAN-00:10 | 8013.63 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.51 | 12.18 | 01-JAN-00:10 | 219.21 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.51 | 12.18 | 01-JAN-00:10 | 219.21 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1563.91 | 19607.84 | 01-JAN-00:10 | 80136.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 25.11 | 121.79 | 01-JAN-00:10 | 2192.06 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 25.11 | 121.79 | 01-JAN-00:10 | 2192.06 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.39 | 1960.78 | 01-JAN-00:10 | 8013.63 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.51 | 12.18 | 01-JAN-00:10 | 219.21 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.51 | 12.18 | 01-JAN-00:10 | 219.21 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2701.35 | 3986.05 | 28-JAN-04:40 | 425892.56 | 21-JUL-10:00 |
HeatRejection:Electricity | 950.18 | 257.27 | 27-JAN-07:20 | 74196.48 | 19-MAY-12:00 |
General:HeatRejection:Electricity | 950.18 | 257.27 | 27-JAN-07:20 | 74196.48 | 19-MAY-12:00 |
ElectricityProduced:Facility | 632.17 | -0.00 | 18-JAN-17:20 | 89495.83 | 22-APR-12:00 |
ElectricityProduced:Plant | 632.17 | -0.00 | 18-JAN-17:20 | 89495.83 | 22-APR-12:00 |
Photovoltaic:ElectricityProduced | 659.31 | 0.00 | 01-JAN-00:10 | 97048.19 | 22-APR-12:30 |
PowerConversion:ElectricityProduced | -27.13 | -7552.35 | 22-APR-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 6158.56 | 50251.58 | 16-JAN-04:50 | 573081.88 | 07-AUG-18:40 |
ExteriorEquipment:Electricity | 1203.71 | 17814.45 | 01-JAN-00:10 | 73699.54 | 13-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.38 | 979.82 | 01-JAN-00:10 | 3374.42 | 11-DEC-17:00 |
ElectricityPurchased:Facility | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
ElectricityPurchased:Plant | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
Cogeneration:ElectricityPurchased | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
ElectricityNet:Plant | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
Cogeneration:ElectricityNet | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
General:Cogeneration:ElectricityNet | 26083.55 | 278619.97 | 16-JAN-11:00 | 1772947.51 | 23-AUG-15:30 |
Fans:Electricity | 2643.32 | 47182.78 | 03-JAN-00:40 | 300724.56 | 08-MAY-14:50 |
General:Fans:Electricity | 2643.32 | 47182.78 | 03-JAN-00:40 | 300724.56 | 08-MAY-14:50 |
ExteriorLights:Electricity | 262.62 | 0.00 | 01-JAN-07:20 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 262.62 | 0.00 | 01-JAN-07:20 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 2936.69 | 2072.64 | 16-JAN-09:00 | 445801.43 | 21-JUL-10:00 |
General:Cooling:Electricity | 2936.69 | 2072.64 | 16-JAN-09:00 | 445801.43 | 21-JUL-10:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1787.82 | 0.00 | 15-JAN-13:20 | 100000.00 | 01-JAN-01:50 |
General:Humidifier:Electricity | 1787.82 | 0.00 | 15-JAN-13:20 | 100000.00 | 01-JAN-01:50 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 487.53 | 3576.48 | 01-JAN-00:10 | 46977.00 | 12-SEP-14:30 |
General:Pumps:Electricity | 487.53 | 3576.48 | 01-JAN-00:10 | 46977.00 | 12-SEP-14:30 |
WIRED_LTG_ELECTRICITY | 49.67 | 0.00 | 01-JAN-00:10 | 4915.83 | 22-NOV-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1037.56 | 7280.88 | 02-JAN-05:20 | 733426.38 | 27-DEC-07:10 |
NaturalGas:Plant | 1037.56 | 7280.88 | 02-JAN-05:20 | 733426.38 | 27-DEC-07:10 |
Heating:NaturalGas | 346.26 | 0.00 | 01-JAN-00:10 | 702923.44 | 27-DEC-07:10 |
Boiler:Heating:NaturalGas | 346.26 | 0.00 | 01-JAN-00:10 | 702923.44 | 27-DEC-07:10 |
WaterSystems:NaturalGas | 691.30 | 7280.88 | 02-JAN-05:20 | 80096.15 | 27-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 691.30 | 7280.88 | 02-JAN-05:20 | 80096.15 | 27-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16253.39 | 9412.37 | 17-JAN-08:00 | 3053549.93 | 21-JUL-10:10 |
PlantLoopCoolingDemand:HVAC | 16253.39 | 9412.37 | 17-JAN-08:00 | 3053549.93 | 21-JUL-10:10 |
CoolingCoils:PlantLoopCoolingDemand | 16253.39 | 9412.37 | 17-JAN-08:00 | 3053549.93 | 21-JUL-10:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 11419.55 | 0.00 | 16-JAN-00:10 | 0.00 | 15-JUN-12:50 |
Water:HVAC | 665.07 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
Humidifier:Water | 665.07 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
General:Humidifier:Water | 665.07 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
MainsWater:Facility | 11419.55 | 0.00 | 16-JAN-00:10 | 0.00 | 15-JUN-12:50 |
MainsWater:HVAC | 665.07 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
Humidifier:MainsWater | 665.07 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
General:Humidifier:MainsWater | 665.07 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
Water:Plant | 10754.48 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-12:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 10754.48 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-12:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 8474.32 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:30 |
General:HeatRejection:Water | 8474.32 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:30 |
HeatRejection:MainsWater | 8474.32 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:30 |
General:HeatRejection:MainsWater | 8474.32 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 62926.16 | 98179.11 | 16-JAN-05:50 | 11035640.99 | 21-JUL-10:10 |
EnergyTransfer:Building | 18897.64 | 89689.27 | 16-JAN-08:20 | 1548596.15 | 07-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 616.99 | 0.00 | 01-JAN-00:10 | 72927.20 | 10-OCT-05:10 |
Heating:EnergyTransfer | 113.25 | 0.00 | 01-JAN-15:10 | 286973.18 | 04-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.59 | 0.00 | 01-JAN-00:10 | 23517.42 | 01-JUL-16:40 |
General:Heating:EnergyTransfer | 113.25 | 0.00 | 01-JAN-15:10 | 286973.18 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.59 | 0.00 | 01-JAN-00:10 | 23517.42 | 01-JUL-16:40 |
Cooling:EnergyTransfer | 18784.39 | 89107.12 | 16-JAN-08:20 | 1548596.15 | 07-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 613.40 | 0.00 | 01-JAN-00:10 | 72927.20 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 18784.39 | 89107.12 | 16-JAN-08:20 | 1548596.15 | 07-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 613.40 | 0.00 | 01-JAN-00:10 | 72927.20 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 603.31 | 0.00 | 01-JAN-00:10 | 55673.32 | 28-AUG-11:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 603.31 | 0.00 | 01-JAN-00:10 | 55673.32 | 28-AUG-11:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 603.31 | 0.00 | 01-JAN-00:10 | 55673.32 | 28-AUG-11:00 |
EnergyTransfer:Zone:CORE_MID | 4291.11 | 0.00 | 01-JAN-00:10 | 496084.24 | 19-SEP-13:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4291.11 | 0.00 | 01-JAN-00:10 | 496084.24 | 19-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4291.11 | 0.00 | 01-JAN-00:10 | 496084.24 | 19-SEP-13:20 |
EnergyTransfer:Zone:CORE_TOP | 403.53 | 0.00 | 01-JAN-00:10 | 55832.50 | 09-JUN-12:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 1.93 | 0.00 | 01-JAN-00:10 | 46271.86 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 1.93 | 0.00 | 01-JAN-00:10 | 46271.86 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 401.60 | 0.00 | 01-JAN-00:10 | 55832.50 | 09-JUN-12:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 401.60 | 0.00 | 01-JAN-00:10 | 55832.50 | 09-JUN-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.67 | 0.00 | 01-JAN-00:10 | 11148.09 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1416.59 | 28-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1416.59 | 28-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.67 | 0.00 | 01-JAN-00:10 | 11148.09 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.67 | 0.00 | 01-JAN-00:10 | 11148.09 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.57 | 0.00 | 01-JAN-00:10 | 13292.65 | 30-MAY-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1078.24 | 28-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1078.24 | 28-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.56 | 0.00 | 01-JAN-00:10 | 13292.65 | 30-MAY-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.56 | 0.00 | 01-JAN-00:10 | 13292.65 | 30-MAY-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 119.30 | 0.00 | 01-JAN-00:10 | 16784.77 | 29-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1906.25 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1906.25 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 119.29 | 0.00 | 01-JAN-00:10 | 16784.77 | 29-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 119.29 | 0.00 | 01-JAN-00:10 | 16784.77 | 29-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 111.77 | 0.00 | 01-JAN-00:10 | 17297.28 | 04-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 111.77 | 0.00 | 01-JAN-00:10 | 17297.28 | 04-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 111.77 | 0.00 | 01-JAN-00:10 | 17297.28 | 04-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 603.32 | 0.00 | 01-JAN-00:10 | 102281.91 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 18.38 | 0.00 | 01-JAN-00:10 | 71152.01 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 18.38 | 0.00 | 01-JAN-00:10 | 71152.01 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 584.94 | 0.00 | 01-JAN-00:10 | 102281.91 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 584.94 | 0.00 | 01-JAN-00:10 | 102281.91 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 633.72 | 0.00 | 01-JAN-00:10 | 136542.84 | 21-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.76 | 0.00 | 01-JAN-00:10 | 46470.29 | 28-NOV-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.76 | 0.00 | 01-JAN-00:10 | 46470.29 | 28-NOV-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 625.97 | 0.00 | 01-JAN-00:10 | 136542.84 | 21-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 625.97 | 0.00 | 01-JAN-00:10 | 136542.84 | 21-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1055.08 | 0.00 | 01-JAN-00:10 | 168928.58 | 29-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 4.81 | 0.00 | 01-JAN-00:10 | 55592.49 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 4.81 | 0.00 | 01-JAN-00:10 | 55592.49 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1050.27 | 0.00 | 01-JAN-00:10 | 168928.58 | 29-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1050.27 | 0.00 | 01-JAN-00:10 | 168928.58 | 29-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 697.00 | 0.00 | 01-JAN-00:10 | 155227.46 | 22-AUG-16:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 4.65 | 0.00 | 01-JAN-00:10 | 33871.95 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 4.65 | 0.00 | 01-JAN-00:10 | 33871.95 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 692.35 | 0.00 | 01-JAN-00:10 | 155227.46 | 22-AUG-16:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 692.35 | 0.00 | 01-JAN-00:10 | 155227.46 | 22-AUG-16:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 66.95 | 0.00 | 01-JAN-00:10 | 14336.52 | 18-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 9.09 | 0.00 | 01-JAN-00:10 | 14336.52 | 18-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 9.09 | 0.00 | 01-JAN-00:10 | 14336.52 | 18-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 57.86 | 0.00 | 01-JAN-00:10 | 11622.89 | 27-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 57.86 | 0.00 | 01-JAN-00:10 | 11622.89 | 27-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.09 | 0.00 | 01-JAN-00:10 | 14546.02 | 21-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.85 | 0.00 | 01-JAN-00:10 | 10952.39 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.85 | 0.00 | 01-JAN-00:10 | 10952.39 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.24 | 0.00 | 01-JAN-00:10 | 14546.02 | 21-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.24 | 0.00 | 01-JAN-00:10 | 14546.02 | 21-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 103.63 | 0.00 | 01-JAN-00:10 | 18349.91 | 29-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 3.84 | 0.00 | 01-JAN-00:10 | 13809.82 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 3.84 | 0.00 | 01-JAN-00:10 | 13809.82 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 99.80 | 0.00 | 01-JAN-00:10 | 18349.91 | 29-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 99.80 | 0.00 | 01-JAN-00:10 | 18349.91 | 29-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.45 | 0.00 | 01-JAN-00:10 | 15689.64 | 22-AUG-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.86 | 0.00 | 01-JAN-00:10 | 7901.00 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.86 | 0.00 | 01-JAN-00:10 | 7901.00 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 68.59 | 0.00 | 01-JAN-00:10 | 15689.64 | 22-AUG-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 68.59 | 0.00 | 01-JAN-00:10 | 15689.64 | 22-AUG-16:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 70.10 | 0.00 | 01-JAN-00:10 | 11980.28 | 07-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.17 | 0.00 | 01-JAN-00:10 | 3085.14 | 24-DEC-11:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.17 | 0.00 | 01-JAN-00:10 | 3085.14 | 24-DEC-11:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.92 | 0.00 | 01-JAN-00:10 | 11980.28 | 07-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.92 | 0.00 | 01-JAN-00:10 | 11980.28 | 07-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 477.77 | 0.00 | 01-JAN-00:10 | 83952.82 | 03-JUL-17:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 34.03 | 0.00 | 01-JAN-00:10 | 33666.72 | 27-DEC-15:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 34.03 | 0.00 | 01-JAN-00:10 | 33666.72 | 27-DEC-15:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 443.74 | 0.00 | 01-JAN-00:10 | 83952.82 | 03-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 443.74 | 0.00 | 01-JAN-00:10 | 83952.82 | 03-JUL-17:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 97.85 | 0.00 | 01-JAN-00:10 | 23320.02 | 27-JUN-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.77 | 0.00 | 01-JAN-00:10 | 17094.11 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.77 | 0.00 | 01-JAN-00:10 | 17094.11 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 81.08 | 0.00 | 01-JAN-00:10 | 23320.02 | 27-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 81.08 | 0.00 | 01-JAN-00:10 | 23320.02 | 27-JUN-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.22 | 853.58 | 28-JAN-08:00 | 7793.91 | 22-APR-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.22 | 853.58 | 28-JAN-08:00 | 7793.91 | 22-APR-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.22 | 853.58 | 28-JAN-08:00 | 7793.91 | 22-APR-18:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1262.54 | 990.45 | 16-JAN-08:20 | 74109.63 | 22-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1262.54 | 990.45 | 16-JAN-08:20 | 74109.63 | 22-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1262.54 | 990.45 | 16-JAN-08:20 | 74109.63 | 22-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.57 | 2.56 | 14-JAN-09:40 | 7468.00 | 27-AUG-21:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.52 | 0.00 | 01-JAN-14:50 | 599.34 | 28-JAN-04:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.52 | 0.00 | 01-JAN-14:50 | 599.34 | 28-JAN-04:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.05 | 0.00 | 01-JAN-00:10 | 7468.00 | 27-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.05 | 0.00 | 01-JAN-00:10 | 7468.00 | 27-AUG-21:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7135.10 | 86948.06 | 16-JAN-05:50 | 374227.33 | 13-AUG-24:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7135.10 | 86948.06 | 16-JAN-05:50 | 374227.33 | 13-AUG-24:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7135.10 | 86948.06 | 16-JAN-05:50 | 374227.33 | 13-AUG-24:00 |
PlantLoopHeatingDemand:Facility | 669.75 | 0.00 | 01-JAN-00:10 | 583870.36 | 27-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 359.12 | 0.00 | 01-JAN-00:10 | 46363.00 | 30-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 359.12 | 0.00 | 01-JAN-00:10 | 46363.00 | 30-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 359.12 | 0.00 | 01-JAN-00:10 | 46363.00 | 30-JAN-13:00 |
EnergyTransfer:HVAC | 14890.98 | 8373.36 | 16-JAN-09:00 | 2912423.41 | 21-JUL-10:10 |
HeatingCoils:EnergyTransfer | 310.63 | 0.00 | 01-JAN-00:10 | 568854.00 | 27-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 310.63 | 0.00 | 01-JAN-00:10 | 568854.00 | 27-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 310.63 | 0.00 | 01-JAN-00:10 | 568854.00 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 14580.34 | 6786.68 | 17-JAN-08:00 | 2912423.41 | 21-JUL-10:10 |
EnergyTransfer:Plant | 29137.54 | 0.00 | 01-JAN-00:10 | 6994598.32 | 21-JUL-10:10 |
LoopToLoop:EnergyTransfer | 9053.61 | 0.00 | 01-JAN-00:10 | 2272988.71 | 21-JUL-10:10 |
WaterSystems:EnergyTransfer | 359.12 | 0.00 | 01-JAN-00:10 | 46363.00 | 30-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 359.12 | 0.00 | 01-JAN-00:10 | 46363.00 | 30-JAN-13:00 |
Boilers:EnergyTransfer | 307.16 | 0.00 | 01-JAN-00:10 | 602954.24 | 27-DEC-07:10 |
Chillers:EnergyTransfer | 9077.00 | 0.00 | 01-JAN-00:10 | 2197842.33 | 21-JUL-10:10 |
HeatRejection:EnergyTransfer | 10340.65 | 0.00 | 01-JAN-00:10 | 2496549.09 | 21-JUL-10:10 |
General:HeatRejection:EnergyTransfer | 10340.65 | 0.00 | 01-JAN-00:10 | 2496549.09 | 21-JUL-10:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.586 | -613.398 | 0.000 | 0.000 | 92.611 | 119.026 | 424.397 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -26.222 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -603.311 | 0.000 | 0.000 | 83.315 | 106.894 | 289.614 | 0.000 | 0.000 | 0.000 | 123.488 | 0.000 | 0.000 | 0.000 | 0.000 | -0.006 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4291.099 | 0.000 | 0.000 | 836.742 | 1068.940 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -510.710 |
CORE_TOP | 0.000 | 0.000 | 1.926 | -401.601 | 0.000 | 0.000 | 85.638 | 106.894 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -82.469 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.004 | -77.667 | 0.000 | 0.000 | 10.600 | 7.711 | 36.365 | 32.249 | 0.000 | 0.396 | 42.882 | 0.000 | -49.456 | 0.000 | -3.084 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.007 | -71.565 | 0.000 | 0.000 | 6.775 | 4.959 | 23.435 | 66.619 | 0.000 | 0.261 | 1.624 | 0.000 | -30.045 | 0.000 | -2.070 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.008 | -119.291 | 0.000 | 0.000 | 10.489 | 7.613 | 36.366 | 114.048 | 0.000 | 0.387 | 0.002 | 0.000 | -45.536 | 0.000 | -3.198 | -0.886 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -111.772 | 0.000 | 0.000 | 6.737 | 4.901 | 23.435 | 65.659 | 0.000 | 0.230 | 49.729 | 0.000 | -36.539 | 0.000 | -2.379 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 18.377 | -584.935 | 0.000 | 0.000 | 109.907 | 76.980 | 363.654 | 335.857 | 0.000 | 9.104 | 177.317 | 0.000 | -442.712 | 0.000 | -63.549 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 7.757 | -625.966 | 0.000 | 0.000 | 50.373 | 49.529 | 234.352 | 663.378 | 0.000 | 5.615 | 0.014 | 0.000 | -284.397 | 0.000 | -45.580 | -55.061 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 4.810 | -1050.258 | 0.000 | 0.000 | 105.569 | 76.059 | 363.660 | 1137.680 | 0.000 | 8.731 | 0.022 | 0.000 | -441.051 | 0.000 | -72.048 | -133.151 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 4.647 | -692.338 | 0.000 | 0.000 | 69.321 | 48.962 | 234.351 | 669.022 | 0.000 | 5.366 | 23.792 | 0.000 | -315.472 | 0.000 | -47.651 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 9.088 | -57.859 | 0.000 | 0.000 | 11.164 | 7.698 | 36.365 | 33.876 | 0.000 | 1.069 | 6.869 | 0.000 | -41.044 | 0.000 | -7.227 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.853 | -64.236 | 0.000 | 0.000 | 6.970 | 4.953 | 23.435 | 66.837 | 0.000 | 0.675 | 0.000 | 0.000 | -26.465 | 0.000 | -5.203 | -10.819 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 3.840 | -99.793 | 0.000 | 0.000 | 10.687 | 7.606 | 36.366 | 114.129 | 0.000 | 1.031 | 0.006 | 0.000 | -41.473 | 0.000 | -8.348 | -24.042 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 2.861 | -68.591 | 0.000 | 0.000 | 7.028 | 4.896 | 23.435 | 66.938 | 0.000 | 0.644 | 0.000 | 0.000 | -29.733 | 0.000 | -5.546 | -1.931 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.217 | 0.000 | 0.000 | 0.946 | 2.511 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.120 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1262.538 | 0.000 | 0.000 | 9.468 | 25.105 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -310.841 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.517 | -119.054 | 0.000 | 0.000 | 0.948 | 2.511 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -38.802 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7135.109 | 0.000 | 0.000 | 19.727 | 33.704 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -413.179 |
GROUNDFLOOR_PLENUM | 1.173 | -68.922 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.737 | 73.785 | 0.000 | 0.000 | 0.000 | -6.772 | 0.000 |
MIDFLOOR_PLENUM | 34.030 | -443.737 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.557 | 511.297 | 0.000 | 0.000 | 0.000 | -115.147 | 0.000 |
TOPFLOOR_PLENUM | 16.766 | -81.078 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.252 | 74.711 | 0.000 | 0.000 | 0.000 | -11.652 | -0.001 |
Total Facility | 51.969 | -593.738 | 61.279 | -18190.599 | 0.000 | 0.000 | 1535.014 | 1767.450 | 14676.396 | 3366.292 | 0.000 | 49.054 | 1085.545 | 0.000 | -1783.923 | 0.000 | -399.454 | -1625.243 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 18-DEC-05:11 | 0.00 | 0.00 | 0.00 | -97083.15 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 83027.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-05:11 | 0.00 | 0.00 | 0.00 | -87248.29 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 80773.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-JUN-04:12 | 0.00 | 0.00 | 0.00 | -745009.64 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 680259.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-04:12 | 0.00 | 0.00 | 0.00 | -77202.68 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 70727.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-18:01 | 0.00 | 0.00 | 0.00 | -16987.36 | 0.00 | 0.00 | 0.00 | 31.11 | 559.17 | 5668.31 | 0.00 | 48.34 | 10680.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-08:11 | 0.00 | 0.00 | 0.00 | -18949.48 | 0.00 | 0.00 | 21.26 | 20.05 | 464.11 | 14447.39 | 0.00 | 0.00 | 4078.94 | 0.00 | -0.00 | 0.00 | -82.26 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-13:21 | 0.00 | 0.00 | 0.00 | -21768.09 | 0.00 | 0.00 | 32.36 | 31.11 | 720.19 | 19076.83 | 0.00 | 31.49 | 1876.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 20-AUG-16:21 | 0.00 | 0.00 | 0.00 | -26739.49 | 0.00 | 0.00 | 15.60 | 20.05 | 464.11 | 12874.58 | 0.00 | 63.81 | 13301.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUN-16:51 | 0.00 | 0.00 | 0.00 | -162367.65 | 0.00 | 0.00 | 421.58 | 311.09 | 7201.84 | 49462.66 | 0.00 | 4498.34 | 100472.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -199521.08 | 0.00 | 0.00 | 210.93 | 200.48 | 4641.14 | 140163.68 | 0.00 | 0.00 | 54972.82 | 0.00 | -0.00 | 0.00 | -667.97 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-11:41 | 0.00 | 0.00 | 0.00 | -212605.42 | 0.00 | 0.00 | 323.54 | 311.10 | 7201.95 | 225551.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4770.77 | -16012.35 |
PERIMETER_MID_ZN_4 | 11-JUN-16:51 | 0.00 | 0.00 | 0.00 | -228104.56 | 0.00 | 0.00 | 171.07 | 200.48 | 4641.11 | 143945.90 | 0.00 | 1342.65 | 77803.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 21-MAY-14:51 | 0.00 | 0.00 | 0.00 | -18754.21 | 0.00 | 0.00 | 41.35 | 31.11 | 720.18 | 4990.35 | 0.00 | 553.74 | 12417.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-08:11 | 0.00 | 0.00 | 0.00 | -20529.84 | 0.00 | 0.00 | 20.78 | 20.05 | 464.11 | 14012.00 | 0.00 | 0.00 | 6091.41 | 0.00 | -0.00 | 0.00 | -78.51 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-12:41 | 0.00 | 0.00 | 0.00 | -24234.18 | 0.00 | 0.00 | 30.74 | 31.11 | 720.19 | 20098.12 | 0.00 | 39.61 | 3314.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-APR-16:31 | 0.00 | 0.00 | 0.00 | -24858.52 | 0.00 | 0.00 | 16.96 | 20.05 | 464.11 | 15273.97 | 0.00 | 3.84 | 9079.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 22-APR-18:35 | 0.00 | 0.00 | 0.00 | -7803.45 | 0.00 | 0.00 | 0.00 | 12.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3.15 |
DATACENTER_MID_ZN_6 | 22-APR-18:20 | 0.00 | 0.00 | 0.00 | -74149.98 | 0.00 | 0.00 | 0.00 | 121.79 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3916.03 |
DATACENTER_TOP_ZN_6 | 27-AUG-21:03 | 0.00 | 0.00 | 0.00 | -7481.68 | 0.00 | 0.00 | 0.00 | 12.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -324.92 |
DATACENTER_BASEMENT_ZN_6 | 27-AUG-20:52 | 0.00 | 0.00 | 0.00 | -377732.32 | 0.00 | 0.00 | 0.00 | 163.49 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2063.68 |
GROUNDFLOOR_PLENUM | 07-AUG-05:25 | 0.00 | -13820.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13821.39 | 0.00 | -0.00 | 0.00 | -1.26 | 0.00 |
MIDFLOOR_PLENUM | 22-AUG-16:22 | 0.00 | -108399.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1634.16 | 106765.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 01-JUL-14:43 | 0.00 | -23822.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.24 | 23691.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-APR-05:02 | 0.00 | 10910.64 | 0.00 | -1775106.55 | 0.00 | 0.00 | 15836.33 | 10328.77 | 616289.16 | 0.00 | 0.00 | 0.00 | 1194317.62 | 0.00 | -68214.56 | 0.00 | -4361.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-JUL-16:25 | 0.00 | 0.00 | 24591.89 | 0.00 | 0.00 | 0.00 | 419.44 | 579.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39048.70 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 04-DEC-05:11 | 0.00 | 0.00 | 66014.99 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -72489.98 |
PERIMETER_BOT_ZN_3 | 28-JAN-06:01 | 0.00 | 0.00 | 8448.08 | 0.00 | 0.00 | 0.00 | 143.28 | 130.77 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6054.09 | 0.00 | -185.27 | -3443.02 |
PERIMETER_BOT_ZN_2 | 28-JAN-06:01 | 0.00 | 0.00 | 6273.72 | 0.00 | 0.00 | 0.00 | 92.57 | 84.27 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4033.15 | 0.00 | -123.51 | -2912.71 |
PERIMETER_BOT_ZN_1 | 27-DEC-06:01 | 0.00 | 0.00 | 10114.79 | 0.00 | 0.00 | 0.00 | 144.64 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5917.67 | 0.00 | -104.63 | -5264.86 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-DEC-05:01 | 0.00 | 0.00 | 125092.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.65 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46467.64 | 0.00 | -12656.85 | -74730.89 |
PERIMETER_MID_ZN_2 | 26-DEC-05:01 | 0.00 | 0.00 | 125720.47 | 0.00 | 0.00 | 0.00 | 0.00 | 842.70 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31307.28 | 0.00 | -8614.69 | -91445.89 |
PERIMETER_MID_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 134445.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.68 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47306.20 | 0.00 | -13322.94 | -82579.93 |
PERIMETER_MID_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 121630.34 | 0.00 | 0.00 | 0.00 | 0.00 | 842.70 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31335.12 | 0.00 | -8903.01 | -87039.55 |
PERIMETER_TOP_ZN_3 | 18-DEC-05:11 | 0.00 | 0.00 | 15964.82 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3401.64 | 0.00 | -2253.62 | -11122.60 |
PERIMETER_TOP_ZN_2 | 27-NOV-05:11 | 0.00 | 0.00 | 15104.62 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2052.62 | 0.00 | -566.14 | -13009.81 |
PERIMETER_TOP_ZN_1 | 27-NOV-05:11 | 0.00 | 0.00 | 17399.20 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3060.34 | 0.00 | -834.70 | -14317.20 |
PERIMETER_TOP_ZN_4 | 26-DEC-04:01 | 0.00 | 0.00 | 16411.61 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2603.26 | 0.00 | -927.62 | -13403.33 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 28-JAN-04:00 | 0.00 | 0.00 | 599.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2560.12 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:11 | 11052.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2638.01 | -8414.94 |
MIDFLOOR_PLENUM | 06-AUG-14:51 | 84901.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7709.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -92610.51 |
TOPFLOOR_PLENUM | 04-DEC-06:03 | 19923.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -233.40 | -19689.71 |
Total Facility | 26-DEC-05:01 | -785273.68 | 738398.08 | 634859.04 | -738398.08 | 0.00 | 0.00 | 0.00 | 19437.29 | 587299.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -188113.35 | 0.00 | -77062.68 | -191146.04 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.0385 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.9250 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 104.8116 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 92.6469 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.9599 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.4956 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5595 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5595 | 0.2159 | 1.0000 | Not calculated | 1.2002 | 0.2159 | ||
AIRLOOP DATACENTER BASEMENT | 24.4916 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4920 | 0.0138 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5262 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5262 | 0.0297 | 1.0000 | Not calculated | 0.0156 | 0.0297 | ||
AIRLOOP DATACENTER MID | 5.0217 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0217 | 0.0311 | 1.0000 | Not calculated | 0.1563 | 0.0311 | ||
AIRLOOP DATACENTER TOP | 0.5136 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5136 | 0.0304 | 1.0000 | Not calculated | 0.0156 | 0.0304 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5193 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2816 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.4058 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8088 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4799 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2834 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5595 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5595 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2159 | ||
AIRLOOP DATACENTER BASEMENT | 24.4916 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4916 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5262 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5262 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0297 | ||
AIRLOOP DATACENTER MID | 5.0217 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0217 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0311 | ||
AIRLOOP DATACENTER TOP | 0.5136 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5136 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0304 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5595 | 5.5595 | 5.5595 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0442 | 6.0442 | 1.6138 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.8347 | 56.8347 | 16.1411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7088 | 5.7088 | 1.6156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1286 | 1.1286 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1230 | 1.1230 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2717 | 1.2717 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4710 | 1.4710 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.9062 | 10.9062 | 2.0285 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.8462 | 11.8462 | 1.3031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3189 | 12.3189 | 2.0326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.9056 | 12.9056 | 1.3035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2545 | 1.2545 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2131 | 1.2131 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3835 | 1.3835 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3999 | 1.3999 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5262 | 0.5262 | 0.5262 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0217 | 5.0217 | 5.0217 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5136 | 0.5136 | 0.5136 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4916 | 24.4916 | 24.4916 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.0385 | 9.9250 | 11.0385 | 2.2816 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 104.8116 | 92.6469 | 104.8116 | 22.8088 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.9599 | 10.4956 | 10.9599 | 2.2834 | 0.0000 | 1.0000 |
CAV_BAS | 5.5595 | 5.5595 | 5.5595 | 5.5595 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4916 | 24.4920 | 24.4916 | 24.4916 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5262 | 0.5262 | 0.5262 | 0.5262 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0217 | 5.0217 | 5.0217 | 5.0217 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5136 | 0.5136 | 0.5136 | 0.5136 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5595 | 5.5595 | 5.5595 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0221 | 3.0221 | 1.6138 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.4174 | 28.4174 | 16.1411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8544 | 2.8544 | 1.6156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5643 | 0.5643 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5615 | 0.5615 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6359 | 0.6359 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7355 | 0.7355 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4531 | 5.4531 | 2.0285 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9231 | 5.9231 | 1.3031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1594 | 6.1594 | 2.0326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4528 | 6.4528 | 1.3035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6272 | 0.6272 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6066 | 0.6066 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6918 | 0.6918 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7000 | 0.7000 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5262 | 0.5262 | 0.5262 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0217 | 5.0217 | 5.0217 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5136 | 0.5136 | 0.5136 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4916 | 24.4916 | 24.4916 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5193 | 2.2816 | 2.2816 | 2.2816 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.4058 | 22.8088 | 22.8088 | 22.8088 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4799 | 2.2834 | 2.2834 | 2.2834 | 0.0000 | 1.0000 |
CAV_BAS | 5.5595 | 5.5595 | 5.5595 | 5.5595 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4916 | 24.4916 | 24.4916 | 24.4916 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5262 | 0.5262 | 0.5262 | 0.5262 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0217 | 5.0217 | 5.0217 | 5.0217 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5136 | 0.5136 | 0.5136 | 0.5136 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 1.67 |
Number of hours cooling loads not met | 1042.83 |
Number of hours not met | 1044.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 346.26 | 702923.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2936.69 | 445801.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1767.45 | 174940.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.62 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.38 | 3374.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2643.32 | 300724.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 487.53 | 46977.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 950.18 | 74196.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1787.82 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 691.30 | 80096.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26715.72 |
Natural Gas | 0.00 | 1037.56 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27753.28 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 659.31 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 38.16 |
Space Heating | 0.00 |
Space Cooling | 63.40 |
Fans (All) | 57.07 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 576.76 |
Subtotal | 576.76 |
Natural Gas [MJ/m2] | |
Space Heating | 7.48 |
Service Water Heating | 14.92 |
Miscellaneous (All) | 22.40 |
Subtotal | 22.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.37 |
Space Heating | 1.25 |
Space Cooling | 10.58 |
Fans (All) | 9.52 |
Service Water Heating | 2.49 |
Receptacle Equipment | 52.88 |
Miscellaneous | 16.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2123. | 8760. |
LTG_SCH_DATACENTER | 2757. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 861. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8448.17 | 311.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8707.50 | 52.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8611.67 | 148.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8637.83 | 122.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8156.50 | 603.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8603.33 | 156.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8655.83 | 104.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8472.50 | 287.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8690.33 | 69.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8579.67 | 180.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8633.67 | 126.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8461.67 | 298.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8511.83 | 248.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8570.33 | 189.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8608.00 | 152.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6925.00 | 1821.17 | 13.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8532.67 | 227.33 | 0.00 | 0.00 | 0.00 |
Min | 6925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1821.17 | 13.83 | 0.00 | 0.00 |
Average | 8535.75 | 223.64 | 0.60 | 0.00 | 0.00 |
Sum | 196322.33 | 5143.83 | 13.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367529.83 | 1086.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330782.00 | 31.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38909.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24890.17 | 18.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38887.67 | 37.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24899.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38903.67 | 21.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24896.83 | 12.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2184.17 | 83.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2198.00 | 70.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2215.00 | 53.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82575.50 | 20392.83 | 426.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367529.83 | 20392.83 | 426.67 | 0.00 | 0.00 |
Average | 79367.12 | 949.24 | 18.55 | 0.00 | 0.00 |
Sum | 1825443.83 | 21832.50 | 426.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8041.67 | 718.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8457.83 | 302.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8438.00 | 322.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8406.83 | 353.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8391.83 | 368.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8401.00 | 359.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8325.67 | 434.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7862.33 | 897.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8350.00 | 410.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8234.00 | 526.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8257.17 | 502.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8098.50 | 661.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8324.50 | 435.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8229.17 | 530.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8247.00 | 513.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8116.17 | 643.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8698.83 | 61.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8727.17 | 32.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8731.17 | 28.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7196.67 | 1563.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8279.17 | 480.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8390.33 | 369.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8168.50 | 591.50 | 0.00 | 0.00 | 0.00 |
Min | 7196.67 | 28.83 | 0.00 | 0.00 | 0.00 |
Max | 8731.17 | 1563.33 | 0.00 | 0.00 | 0.00 |
Average | 8277.11 | 482.89 | 0.00 | 0.00 | 0.00 |
Sum | 190373.50 | 11106.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 366217.33 | 2398.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330200.67 | 612.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330442.00 | 371.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330273.83 | 539.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24907.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38826.33 | 98.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24886.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38922.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18350.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38867.00 | 58.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24896.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38920.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24905.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38888.33 | 36.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24891.67 | 17.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2241.67 | 26.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2253.00 | 15.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2257.00 | 11.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85273.17 | 18121.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366217.33 | 18121.83 | 0.00 | 0.00 | 0.00 |
Average | 79362.73 | 972.18 | 0.00 | 0.00 | 0.00 |
Sum | 1825342.83 | 22360.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455138E+11 | 96939.03 | 17-JAN-05:11 | 5.20 | 3.69 | 0.566256E+10 | 7499.17 | 02-JAN-10:20 | 5.20 | 3.69 |
February | 0.392305E+11 | 96301.89 | 21-FEB-05:12 | 4.80 | 0.06 | 0.513533E+10 | 7499.38 | 13-FEB-10:20 | 4.80 | 0.06 |
March | 0.456707E+11 | 93300.28 | 20-MAR-04:12 | 8.30 | 3.03 | 0.612881E+10 | 7499.12 | 22-MAR-13:20 | 24.80 | 9.22 |
April | 0.453739E+11 | 90927.74 | 18-APR-04:12 | 8.13 | 5.36 | 0.544665E+10 | 7499.27 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.486502E+11 | 91464.39 | 08-MAY-04:12 | 12.93 | 4.38 | 0.590400E+10 | 7781.64 | 25-MAY-13:09 | 30.60 | 14.84 |
June | 0.502398E+11 | 86043.57 | 12-JUN-04:12 | 17.57 | 6.60 | 0.590107E+10 | 8076.48 | 26-JUN-09:00 | 27.80 | 16.72 |
July | 0.540149E+11 | 71251.44 | 10-JUL-03:02 | 24.40 | 16.39 | 0.548715E+10 | 7865.99 | 17-JUL-09:20 | 23.67 | 20.03 |
August | 0.635975E+11 | 80115.62 | 23-AUG-04:12 | 20.00 | 11.86 | 0.617146E+10 | 8348.42 | 22-AUG-13:50 | 20.00 | 11.86 |
September | 0.571615E+11 | 92795.77 | 25-SEP-05:03 | 9.08 | 8.55 | 0.547872E+10 | 8248.15 | 19-SEP-13:09 | 9.08 | 8.55 |
October | 0.586062E+11 | 96459.45 | 30-OCT-04:12 | 10.93 | 6.49 | 0.567666E+10 | 7934.28 | 02-OCT-09:00 | 10.93 | 6.49 |
November | 0.546066E+11 | 97008.37 | 06-NOV-05:11 | 3.50 | -0.5 | 0.561418E+10 | 7499.09 | 30-NOV-14:20 | 17.80 | 10.39 |
December | 0.507355E+11 | 97089.11 | 18-DEC-05:11 | 4.03 | -3.0 | 0.546940E+10 | 7499.04 | 06-DEC-10:20 | 4.03 | -3.0 |
Annual Sum or Average | 0.613401E+12 | 0.680760E+11 | ||||||||
Minimum of Months | 0.392305E+11 | 71251.44 | 3.50 | -3.0 | 0.513533E+10 | 7499.04 | 4.03 | -3.0 | ||
Maximum of Months | 0.635975E+11 | 97089.11 | 24.40 | 16.39 | 0.617146E+10 | 8348.42 | 30.60 | 20.03 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355703E+11 | 84336.13 | 02-JAN-05:11 | 2.40 | 1.50 | 0.507267E+10 | 6734.81 | 02-JAN-10:20 | 11.33 | 7.33 |
February | 0.362081E+11 | 82158.12 | 21-FEB-05:12 | 4.80 | 0.06 | 0.460246E+10 | 6735.08 | 13-FEB-10:09 | 4.80 | 0.06 |
March | 0.474535E+11 | 79367.02 | 20-MAR-04:12 | 8.30 | 3.03 | 0.549731E+10 | 6734.75 | 17-MAR-09:39 | 8.30 | 3.03 |
April | 0.545151E+11 | 80309.02 | 25-APR-04:13 | 13.13 | 5.30 | 0.488094E+10 | 6784.54 | 27-APR-13:30 | 27.25 | 13.82 |
May | 0.507234E+11 | 86302.99 | 22-MAY-04:13 | 18.13 | 13.85 | 0.529415E+10 | 7196.78 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.572761E+11 | 79551.22 | 28-JUN-04:12 | 17.57 | 15.76 | 0.529968E+10 | 7453.41 | 27-JUN-13:00 | 17.57 | 15.76 |
July | 0.619096E+11 | 74260.48 | 05-JUL-04:32 | 19.63 | 16.41 | 0.489782E+10 | 6874.60 | 03-JUL-07:19 | 19.63 | 16.41 |
August | 0.697204E+11 | 76636.21 | 14-AUG-04:23 | 17.50 | 16.39 | 0.553760E+10 | 7719.70 | 22-AUG-13:50 | 31.78 | 16.32 |
September | 0.503844E+11 | 87090.82 | 11-SEP-04:13 | 16.33 | 11.04 | 0.489834E+10 | 7513.07 | 19-SEP-13:20 | 33.17 | 16.78 |
October | 0.507352E+11 | 86763.61 | 10-OCT-04:12 | 13.17 | 8.78 | 0.508140E+10 | 6864.15 | 02-OCT-09:00 | 13.17 | 8.78 |
November | 0.458592E+11 | 87251.70 | 13-NOV-05:11 | 2.93 | 0.58 | 0.502952E+10 | 6734.75 | 13-NOV-10:20 | 11.13 | 5.62 |
December | 0.429568E+11 | 83234.93 | 18-DEC-05:11 | 4.03 | -3.0 | 0.490117E+10 | 6734.77 | 04-DEC-10:09 | 4.03 | -3.0 |
Annual Sum or Average | 0.603312E+12 | 0.609931E+11 | ||||||||
Minimum of Months | 0.355703E+11 | 74260.48 | 2.40 | -3.0 | 0.460246E+10 | 6734.75 | 4.03 | -3.0 | ||
Maximum of Months | 0.697204E+11 | 87251.70 | 19.63 | 16.41 | 0.553760E+10 | 7719.70 | 33.17 | 16.78 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240749E+11 | 65012.09 | 14-JAN-06:02 | 8.90 | 2.74 | 0.499273E+10 | 6734.72 | 12-JAN-10:20 | 8.90 | 2.74 |
February | 0.248675E+11 | 69086.64 | 23-FEB-06:02 | 10.60 | 5.29 | 0.455692E+10 | 6734.98 | 13-FEB-10:09 | 10.60 | 5.29 |
March | 0.323871E+11 | 70957.03 | 16-MAR-05:02 | 14.43 | 5.41 | 0.546969E+10 | 6734.78 | 22-MAR-09:20 | 15.90 | 6.06 |
April | 0.363140E+11 | 72241.42 | 21-APR-04:11 | 17.60 | 6.24 | 0.487239E+10 | 6734.84 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.430157E+11 | 74035.94 | 17-MAY-05:03 | 14.08 | 5.19 | 0.528706E+10 | 7176.62 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.459768E+11 | 74490.36 | 28-JUN-04:12 | 17.57 | 15.76 | 0.529081E+10 | 7417.44 | 27-JUN-13:00 | 17.57 | 15.76 |
July | 0.450732E+11 | 68359.23 | 05-JUL-04:12 | 19.27 | 16.16 | 0.489302E+10 | 6734.86 | 11-JUL-09:20 | 29.47 | 18.61 |
August | 0.467508E+11 | 74030.88 | 30-AUG-04:12 | 18.50 | 14.17 | 0.551077E+10 | 7408.97 | 22-AUG-13:50 | 18.50 | 14.17 |
September | 0.409955E+11 | 74142.81 | 06-SEP-04:12 | 16.50 | 15.71 | 0.488781E+10 | 7408.17 | 19-SEP-13:20 | 33.17 | 16.78 |
October | 0.372633E+11 | 73437.13 | 03-OCT-04:12 | 19.23 | 14.46 | 0.506646E+10 | 6734.98 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.288651E+11 | 71610.97 | 10-NOV-06:02 | 17.87 | 11.05 | 0.499402E+10 | 6734.76 | 22-NOV-10:20 | 14.63 | 5.67 |
December | 0.235268E+11 | 47319.62 | 14-DEC-06:02 | 2.70 | 1.71 | 0.481264E+10 | 6734.72 | 14-DEC-10:20 | 8.33 | 5.14 |
Annual Sum or Average | 0.429111E+12 | 0.606343E+11 | ||||||||
Minimum of Months | 0.235268E+11 | 47319.62 | 2.70 | 1.71 | 0.455692E+10 | 6734.72 | 8.33 | 2.74 | ||
Maximum of Months | 0.467508E+11 | 74490.36 | 19.27 | 16.16 | 0.551077E+10 | 7417.44 | 33.17 | 18.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162967E+11 | 23264.40 | 12-JAN-17:00 | 17.80 | 9.80 | 0.447154E+10 | 6734.60 | 13-JAN-14:20 | 17.97 | 8.78 |
February | 0.177778E+11 | 27473.23 | 08-FEB-15:00 | 11.70 | 2.53 | 0.423788E+10 | 6734.64 | 08-FEB-10:20 | 11.70 | 2.53 |
March | 0.252848E+11 | 65808.69 | 16-MAR-05:02 | 14.43 | 5.41 | 0.527234E+10 | 6734.71 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.340309E+11 | 69778.69 | 28-APR-05:02 | 14.22 | 8.86 | 0.483881E+10 | 6796.41 | 28-APR-13:00 | 28.90 | 14.04 |
May | 0.446412E+11 | 75021.70 | 22-MAY-04:12 | 18.13 | 13.85 | 0.529122E+10 | 7356.91 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.514160E+11 | 76892.51 | 26-JUN-04:13 | 21.50 | 14.53 | 0.531266E+10 | 7790.77 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.509074E+11 | 73727.50 | 05-JUL-04:12 | 19.27 | 16.16 | 0.489917E+10 | 6734.65 | 07-JUL-09:20 | 23.50 | 18.85 |
August | 0.507195E+11 | 77211.21 | 14-AUG-04:12 | 17.60 | 16.48 | 0.551927E+10 | 7642.62 | 22-AUG-15:39 | 32.60 | 16.06 |
September | 0.414969E+11 | 75287.83 | 05-SEP-04:12 | 16.50 | 15.67 | 0.488613E+10 | 7515.22 | 12-SEP-13:00 | 31.70 | 17.62 |
October | 0.330294E+11 | 72513.89 | 04-OCT-05:02 | 17.80 | 15.98 | 0.501909E+10 | 6734.87 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.206848E+11 | 56401.09 | 10-NOV-06:02 | 17.87 | 11.05 | 0.468070E+10 | 6734.68 | 09-NOV-10:20 | 17.87 | 11.05 |
December | 0.153186E+11 | 18635.64 | 01-DEC-17:00 | 10.60 | 4.87 | 0.424150E+10 | 6734.62 | 01-DEC-14:30 | 10.60 | 4.87 |
Annual Sum or Average | 0.401604E+12 | 0.586703E+11 | ||||||||
Minimum of Months | 0.153186E+11 | 18635.64 | 10.60 | 2.53 | 0.423788E+10 | 6734.60 | 10.60 | 2.53 | ||
Maximum of Months | 0.514160E+11 | 77211.21 | 21.50 | 16.48 | 0.551927E+10 | 7790.77 | 32.60 | 18.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236706E+10 | 3197.05 | 02-JAN-15:00 | 17.80 | 9.34 | 0.590673E+09 | 845.62 | 02-JAN-10:50 | 17.80 | 9.34 |
February | 0.270798E+10 | 5221.34 | 21-FEB-15:00 | 22.80 | 8.17 | 0.550356E+09 | 845.62 | 07-FEB-10:20 | 22.80 | 8.17 |
March | 0.418168E+10 | 6102.18 | 15-MAR-13:40 | 23.13 | 9.64 | 0.675333E+09 | 845.62 | 22-MAR-13:20 | 24.80 | 9.22 |
April | 0.682580E+10 | 8376.40 | 21-APR-14:00 | 32.20 | 15.21 | 0.610960E+09 | 853.13 | 27-APR-13:30 | 27.25 | 13.82 |
May | 0.836247E+10 | 16381.76 | 21-MAY-15:41 | 34.40 | 18.24 | 0.665600E+09 | 909.98 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.111184E+11 | 16988.54 | 25-JUN-18:01 | 31.02 | 16.46 | 0.668569E+09 | 955.28 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.114102E+11 | 16473.21 | 02-JUL-16:22 | 38.05 | 18.71 | 0.616810E+09 | 889.81 | 03-JUL-07:19 | 28.17 | 16.54 |
August | 0.114909E+11 | 16944.35 | 20-AUG-16:21 | 32.50 | 16.00 | 0.696213E+09 | 986.54 | 22-AUG-13:50 | 31.78 | 16.32 |
September | 0.748836E+10 | 15817.01 | 10-SEP-16:11 | 30.93 | 16.66 | 0.614540E+09 | 947.12 | 19-SEP-13:20 | 33.17 | 16.78 |
October | 0.564375E+10 | 11734.04 | 03-OCT-05:02 | 18.90 | 14.34 | 0.634369E+09 | 861.16 | 02-OCT-09:00 | 18.90 | 14.34 |
November | 0.346929E+10 | 5171.06 | 08-NOV-14:30 | 23.60 | 11.30 | 0.616619E+09 | 845.62 | 13-NOV-10:20 | 11.13 | 5.62 |
December | 0.260127E+10 | 3611.74 | 11-DEC-12:00 | 14.40 | 7.20 | 0.579235E+09 | 845.61 | 11-DEC-14:09 | 13.90 | 7.45 |
Annual Sum or Average | 0.776672E+11 | 0.751928E+10 | ||||||||
Minimum of Months | 0.236706E+10 | 3197.05 | 14.40 | 7.20 | 0.550356E+09 | 845.61 | 11.13 | 5.62 | ||
Maximum of Months | 0.114909E+11 | 16988.54 | 38.05 | 18.71 | 0.696213E+09 | 986.54 | 33.17 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222656E+10 | 5888.30 | 31-JAN-09:05 | 10.78 | 4.13 | 0.398311E+09 | 544.96 | 02-JAN-10:09 | 10.78 | 4.13 |
February | 0.278052E+10 | 9346.85 | 20-FEB-09:43 | 13.77 | 5.47 | 0.365986E+09 | 544.95 | 17-FEB-10:20 | 13.77 | 5.47 |
March | 0.441857E+10 | 9961.88 | 26-MAR-08:13 | 10.73 | 3.82 | 0.440088E+09 | 544.96 | 06-MAR-10:09 | 10.73 | 3.82 |
April | 0.673040E+10 | 17297.54 | 16-APR-09:42 | 22.43 | 10.69 | 0.394827E+09 | 550.49 | 27-APR-13:30 | 27.25 | 13.82 |
May | 0.841569E+10 | 18373.17 | 28-MAY-08:12 | 22.57 | 16.77 | 0.430088E+09 | 649.20 | 19-MAY-09:39 | 22.57 | 16.77 |
June | 0.986881E+10 | 18253.90 | 11-JUN-08:51 | 26.10 | 11.59 | 0.433848E+09 | 678.69 | 26-JUN-09:09 | 26.38 | 16.01 |
July | 0.951062E+10 | 17171.61 | 04-JUL-08:22 | 25.55 | 18.36 | 0.398266E+09 | 623.23 | 11-JUL-08:30 | 28.05 | 18.05 |
August | 0.936735E+10 | 18112.16 | 20-AUG-08:22 | 24.45 | 16.43 | 0.449350E+09 | 651.17 | 28-AUG-09:50 | 26.42 | 16.65 |
September | 0.757253E+10 | 18959.27 | 04-SEP-08:11 | 21.83 | 17.83 | 0.397360E+09 | 638.00 | 18-SEP-09:09 | 25.37 | 17.15 |
October | 0.525793E+10 | 17452.40 | 01-OCT-08:42 | 21.55 | 12.56 | 0.409672E+09 | 563.28 | 02-OCT-09:00 | 25.60 | 16.62 |
November | 0.328288E+10 | 8994.02 | 10-NOV-08:40 | 18.13 | 11.62 | 0.400626E+09 | 544.95 | 13-NOV-10:20 | 11.13 | 5.62 |
December | 0.213275E+10 | 4816.62 | 07-DEC-09:20 | 4.83 | 0.28 | 0.383480E+09 | 544.95 | 04-DEC-10:09 | 4.83 | 0.28 |
Annual Sum or Average | 0.715646E+11 | 0.490190E+10 | ||||||||
Minimum of Months | 0.213275E+10 | 4816.62 | 4.83 | 0.28 | 0.365986E+09 | 544.95 | 4.83 | 0.28 | ||
Maximum of Months | 0.986881E+10 | 18959.27 | 26.10 | 18.36 | 0.449350E+09 | 678.69 | 28.05 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.756998E+10 | 18922.89 | 01-JAN-13:32 | 15.40 | 9.21 | 0.621041E+09 | 861.17 | 12-JAN-14:09 | 18.40 | 9.78 |
February | 0.721186E+10 | 20903.42 | 20-FEB-13:42 | 22.02 | 8.45 | 0.568442E+09 | 847.73 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.839726E+10 | 18984.83 | 26-MAR-13:32 | 21.13 | 8.46 | 0.681238E+09 | 846.93 | 07-MAR-14:00 | 21.13 | 8.46 |
April | 0.934278E+10 | 19333.23 | 30-APR-12:43 | 28.95 | 12.43 | 0.611714E+09 | 915.95 | 28-APR-13:00 | 28.95 | 12.43 |
May | 0.904047E+10 | 18691.64 | 21-MAY-15:01 | 34.40 | 17.86 | 0.665800E+09 | 936.58 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.109804E+11 | 18571.91 | 11-JUN-16:11 | 32.60 | 15.18 | 0.667304E+09 | 956.41 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.116742E+11 | 18652.22 | 30-JUL-14:22 | 31.70 | 19.83 | 0.616602E+09 | 853.43 | 03-JUL-07:19 | 31.70 | 19.83 |
August | 0.133875E+11 | 19384.69 | 20-AUG-16:21 | 32.50 | 16.00 | 0.700830E+09 | 1053.94 | 31-AUG-13:30 | 28.05 | 17.53 |
September | 0.120146E+11 | 20630.09 | 17-SEP-13:12 | 31.87 | 15.88 | 0.622050E+09 | 1108.41 | 19-SEP-13:20 | 33.17 | 16.78 |
October | 0.117837E+11 | 21768.19 | 01-OCT-13:21 | 31.65 | 14.91 | 0.645972E+09 | 1002.11 | 17-OCT-13:00 | 26.10 | 16.24 |
November | 0.989363E+10 | 20701.95 | 05-NOV-13:12 | 16.30 | 8.42 | 0.627742E+09 | 906.82 | 09-NOV-14:09 | 23.30 | 12.48 |
December | 0.799584E+10 | 19924.39 | 31-DEC-13:32 | 12.57 | 4.88 | 0.602396E+09 | 848.83 | 07-DEC-14:09 | 12.57 | 4.88 |
Annual Sum or Average | 0.119292E+12 | 0.763113E+10 | ||||||||
Minimum of Months | 0.721186E+10 | 18571.91 | 12.57 | 4.88 | 0.568442E+09 | 846.93 | 12.57 | 4.88 | ||
Maximum of Months | 0.133875E+11 | 21768.19 | 34.40 | 19.83 | 0.700830E+09 | 1108.41 | 33.17 | 19.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336760E+10 | 9436.57 | 22-JAN-16:23 | 12.75 | 7.03 | 0.402356E+09 | 544.95 | 02-JAN-10:20 | 12.75 | 7.03 |
February | 0.435447E+10 | 22863.72 | 20-FEB-15:02 | 23.30 | 8.84 | 0.370446E+09 | 544.98 | 13-FEB-10:09 | 23.30 | 8.84 |
March | 0.787930E+10 | 22505.85 | 26-MAR-16:12 | 22.40 | 8.95 | 0.445256E+09 | 544.95 | 17-MAR-09:39 | 22.40 | 8.95 |
April | 0.117118E+11 | 24631.28 | 16-APR-16:21 | 30.00 | 11.59 | 0.397211E+09 | 594.70 | 27-APR-15:00 | 28.30 | 12.67 |
May | 0.103872E+11 | 24852.56 | 07-MAY-15:51 | 29.40 | 14.34 | 0.430184E+09 | 589.73 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.131447E+11 | 26264.72 | 25-JUN-16:41 | 31.60 | 16.82 | 0.431008E+09 | 623.70 | 23-JUN-15:09 | 31.60 | 16.82 |
July | 0.141024E+11 | 23949.51 | 09-JUL-16:41 | 32.88 | 19.22 | 0.398767E+09 | 549.20 | 21-JUL-09:00 | 23.90 | 21.52 |
August | 0.165962E+11 | 26742.34 | 20-AUG-16:21 | 32.50 | 16.00 | 0.451765E+09 | 734.77 | 22-AUG-15:00 | 32.80 | 15.90 |
September | 0.970062E+10 | 25470.39 | 17-SEP-15:51 | 32.80 | 15.88 | 0.397239E+09 | 619.83 | 12-SEP-13:00 | 32.80 | 15.88 |
October | 0.852519E+10 | 24101.58 | 22-OCT-14:41 | 26.70 | 14.67 | 0.412525E+09 | 593.45 | 17-OCT-15:00 | 26.70 | 14.67 |
November | 0.655505E+10 | 22183.94 | 05-NOV-14:32 | 17.43 | 8.78 | 0.407147E+09 | 544.95 | 13-NOV-10:20 | 11.13 | 5.62 |
December | 0.544834E+10 | 15776.92 | 31-DEC-14:53 | 14.40 | 5.20 | 0.396351E+09 | 544.95 | 04-DEC-10:09 | 14.40 | 5.20 |
Annual Sum or Average | 0.111773E+12 | 0.494025E+10 | ||||||||
Minimum of Months | 0.336760E+10 | 9436.57 | 12.75 | 5.20 | 0.370446E+09 | 544.95 | 11.13 | 5.20 | ||
Maximum of Months | 0.165962E+11 | 26742.34 | 32.88 | 19.22 | 0.451765E+09 | 734.77 | 32.80 | 21.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140073E+10 | 2215.34 | 12-JAN-15:40 | 18.90 | 10.12 | 0.508195E+09 | 815.75 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.165414E+10 | 3026.70 | 23-FEB-14:30 | 21.65 | 7.41 | 0.490581E+09 | 845.60 | 23-FEB-14:20 | 21.65 | 7.41 |
March | 0.256982E+10 | 4429.94 | 22-MAR-14:30 | 24.15 | 9.01 | 0.626556E+09 | 845.62 | 16-MAR-13:20 | 24.15 | 9.01 |
April | 0.441538E+10 | 7591.79 | 20-APR-05:02 | 20.10 | 9.51 | 0.598614E+09 | 845.64 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.735461E+10 | 11520.10 | 21-MAY-15:52 | 34.40 | 18.34 | 0.663858E+09 | 907.73 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.986250E+10 | 16236.40 | 11-JUN-16:51 | 32.20 | 14.93 | 0.668097E+09 | 953.44 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.935442E+10 | 15499.94 | 02-JUL-18:42 | 35.68 | 16.89 | 0.616571E+09 | 846.76 | 03-JUL-13:20 | 37.07 | 18.70 |
August | 0.839580E+10 | 15973.16 | 06-AUG-17:31 | 35.77 | 18.42 | 0.692907E+09 | 952.55 | 22-AUG-13:50 | 31.78 | 16.32 |
September | 0.617729E+10 | 10006.69 | 19-SEP-13:23 | 33.35 | 16.80 | 0.612015E+09 | 933.82 | 19-SEP-13:20 | 33.35 | 16.80 |
October | 0.396913E+10 | 7763.96 | 05-OCT-05:03 | 21.32 | 16.10 | 0.619521E+09 | 845.64 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.210876E+10 | 3381.66 | 09-NOV-15:00 | 23.30 | 12.64 | 0.549760E+09 | 845.62 | 09-NOV-14:20 | 23.30 | 12.64 |
December | 0.123152E+10 | 2051.63 | 01-DEC-13:30 | 14.70 | 6.53 | 0.482024E+09 | 782.78 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.584941E+11 | 0.712870E+10 | ||||||||
Minimum of Months | 0.123152E+10 | 2051.63 | 14.70 | 6.53 | 0.482024E+09 | 782.78 | 17.20 | 7.41 | ||
Maximum of Months | 0.986250E+10 | 16236.40 | 35.77 | 18.42 | 0.692907E+09 | 953.44 | 37.07 | 18.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113942E+10 | 4412.93 | 12-JAN-11:05 | 14.18 | 7.39 | 0.275257E+09 | 548.49 | 12-JAN-11:09 | 14.18 | 7.39 |
February | 0.176756E+10 | 6758.36 | 21-FEB-11:05 | 20.00 | 7.35 | 0.260508E+09 | 548.49 | 17-FEB-11:09 | 20.00 | 7.35 |
March | 0.332659E+10 | 9643.26 | 19-MAR-09:53 | 17.20 | 6.41 | 0.317503E+09 | 548.50 | 22-MAR-12:09 | 24.50 | 9.37 |
April | 0.587395E+10 | 19882.07 | 30-APR-09:01 | 20.37 | 12.82 | 0.290974E+09 | 548.52 | 14-APR-10:09 | 20.37 | 12.82 |
May | 0.824063E+10 | 18222.11 | 29-MAY-08:52 | 22.20 | 15.42 | 0.317225E+09 | 619.55 | 19-MAY-10:30 | 22.20 | 15.42 |
June | 0.983714E+10 | 19680.95 | 11-JUN-09:31 | 26.83 | 11.88 | 0.319402E+09 | 662.69 | 21-JUN-08:00 | 31.10 | 14.59 |
July | 0.915464E+10 | 19963.72 | 04-JUL-08:61 | 25.18 | 18.51 | 0.295052E+09 | 617.36 | 11-JUL-08:30 | 28.05 | 18.05 |
August | 0.865648E+10 | 19949.36 | 06-AUG-08:11 | 27.23 | 17.51 | 0.330385E+09 | 606.65 | 07-AUG-08:39 | 29.03 | 17.47 |
September | 0.713176E+10 | 19819.72 | 17-SEP-09:21 | 25.55 | 16.11 | 0.292950E+09 | 595.23 | 18-SEP-08:00 | 25.00 | 17.03 |
October | 0.435075E+10 | 12969.60 | 22-OCT-10:23 | 21.95 | 12.92 | 0.299823E+09 | 548.52 | 17-OCT-10:09 | 21.95 | 12.92 |
November | 0.214553E+10 | 8064.52 | 10-NOV-08:50 | 18.22 | 11.69 | 0.284627E+09 | 548.50 | 09-NOV-11:09 | 18.22 | 11.69 |
December | 0.972199E+09 | 3530.65 | 01-DEC-11:05 | 13.98 | 5.75 | 0.260749E+09 | 548.49 | 07-DEC-11:09 | 10.55 | 4.08 |
Annual Sum or Average | 0.625966E+11 | 0.354446E+10 | ||||||||
Minimum of Months | 0.972199E+09 | 3530.65 | 13.98 | 5.75 | 0.260508E+09 | 548.49 | 10.55 | 4.08 | ||
Maximum of Months | 0.983714E+10 | 19963.72 | 27.23 | 18.51 | 0.330385E+09 | 662.69 | 31.10 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.716958E+10 | 18935.90 | 29-JAN-14:13 | 13.50 | 6.05 | 0.611483E+09 | 898.51 | 12-JAN-14:30 | 13.50 | 6.05 |
February | 0.666267E+10 | 19109.77 | 20-FEB-13:52 | 22.20 | 8.45 | 0.558404E+09 | 862.90 | 07-FEB-14:09 | 22.20 | 8.45 |
March | 0.723297E+10 | 16277.95 | 19-MAR-12:43 | 22.12 | 8.32 | 0.668820E+09 | 846.58 | 08-MAR-14:20 | 22.12 | 8.32 |
April | 0.735349E+10 | 18625.28 | 30-APR-12:23 | 28.05 | 12.68 | 0.605472E+09 | 852.69 | 28-APR-13:00 | 28.05 | 12.68 |
May | 0.822728E+10 | 15580.25 | 14-MAY-13:02 | 30.10 | 13.13 | 0.664186E+09 | 940.12 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.969352E+10 | 18104.62 | 11-JUN-16:11 | 32.60 | 15.18 | 0.666769E+09 | 953.51 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.964147E+10 | 18047.95 | 30-JUL-12:02 | 30.10 | 20.05 | 0.616473E+09 | 846.76 | 31-JUL-13:20 | 32.60 | 19.85 |
August | 0.106708E+11 | 18528.30 | 06-AUG-15:31 | 36.10 | 18.34 | 0.696642E+09 | 1049.63 | 31-AUG-13:09 | 27.88 | 17.41 |
September | 0.113903E+11 | 20365.01 | 17-SEP-12:42 | 31.60 | 15.76 | 0.621853E+09 | 1132.15 | 19-SEP-13:20 | 33.17 | 16.78 |
October | 0.110332E+11 | 21251.81 | 29-OCT-11:41 | 23.12 | 11.79 | 0.643784E+09 | 973.56 | 17-OCT-14:00 | 23.12 | 11.79 |
November | 0.909273E+10 | 20557.09 | 11-NOV-14:22 | 18.60 | 8.18 | 0.619931E+09 | 979.44 | 03-NOV-13:50 | 18.60 | 8.18 |
December | 0.685919E+10 | 19632.57 | 17-DEC-13:52 | 15.00 | 4.30 | 0.589095E+09 | 864.45 | 07-DEC-14:09 | 15.00 | 4.30 |
Annual Sum or Average | 0.105027E+12 | 0.756291E+10 | ||||||||
Minimum of Months | 0.666267E+10 | 15580.25 | 13.50 | 4.30 | 0.558404E+09 | 846.58 | 13.50 | 4.30 | ||
Maximum of Months | 0.113903E+11 | 21251.81 | 36.10 | 20.05 | 0.696642E+09 | 1132.15 | 33.17 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182759E+10 | 6504.49 | 12-JAN-15:30 | 18.90 | 10.10 | 0.359188E+09 | 544.94 | 13-JAN-14:30 | 18.05 | 8.79 |
February | 0.209059E+10 | 10893.78 | 20-FEB-15:53 | 23.30 | 8.66 | 0.338793E+09 | 544.95 | 21-FEB-14:20 | 22.07 | 8.04 |
March | 0.387703E+10 | 16964.94 | 05-MAR-16:21 | 20.30 | 8.86 | 0.422792E+09 | 544.97 | 07-MAR-14:30 | 21.95 | 8.94 |
April | 0.622310E+10 | 22521.38 | 30-APR-17:01 | 30.00 | 12.62 | 0.391635E+09 | 544.96 | 24-APR-13:20 | 30.00 | 12.62 |
May | 0.858608E+10 | 21056.30 | 29-MAY-16:51 | 32.80 | 16.44 | 0.429104E+09 | 586.02 | 25-MAY-13:50 | 32.80 | 16.44 |
June | 0.102144E+11 | 22809.86 | 11-JUN-16:51 | 32.20 | 14.93 | 0.430347E+09 | 621.14 | 23-JUN-15:09 | 30.45 | 16.21 |
July | 0.956506E+10 | 21144.49 | 04-JUL-16:01 | 33.18 | 18.80 | 0.398078E+09 | 544.97 | 11-JUL-09:20 | 29.47 | 18.61 |
August | 0.930097E+10 | 22765.56 | 06-AUG-16:51 | 36.10 | 18.82 | 0.447916E+09 | 697.63 | 22-AUG-15:00 | 32.80 | 15.90 |
September | 0.765771E+10 | 22610.98 | 17-SEP-16:01 | 32.62 | 15.82 | 0.396101E+09 | 609.81 | 12-SEP-13:00 | 32.62 | 15.82 |
October | 0.528959E+10 | 19879.61 | 29-OCT-15:42 | 23.40 | 11.36 | 0.407082E+09 | 584.29 | 17-OCT-15:00 | 23.40 | 11.36 |
November | 0.293773E+10 | 13961.09 | 11-NOV-15:02 | 18.80 | 8.34 | 0.379337E+09 | 544.96 | 10-NOV-14:20 | 18.80 | 8.34 |
December | 0.166538E+10 | 5594.05 | 15-DEC-15:40 | 15.60 | 6.10 | 0.344333E+09 | 544.95 | 01-DEC-14:00 | 15.60 | 6.10 |
Annual Sum or Average | 0.692353E+11 | 0.474471E+10 | ||||||||
Minimum of Months | 0.166538E+10 | 5594.05 | 15.60 | 6.10 | 0.338793E+09 | 544.94 | 15.60 | 6.10 | ||
Maximum of Months | 0.102144E+11 | 22809.86 | 36.10 | 18.82 | 0.447916E+09 | 697.63 | 32.80 | 18.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.721264E+09 | 2097.97 | 12-JAN-14:40 | 18.70 | 9.92 | 0.482745E+09 | 773.23 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.105918E+10 | 2270.21 | 23-FEB-14:30 | 21.65 | 7.41 | 0.462302E+09 | 845.58 | 22-FEB-14:00 | 21.65 | 7.41 |
March | 0.207063E+10 | 4390.22 | 22-MAR-14:30 | 24.15 | 9.01 | 0.595308E+09 | 845.62 | 31-MAR-13:20 | 22.60 | 8.22 |
April | 0.427922E+10 | 14263.25 | 30-APR-16:31 | 30.20 | 12.69 | 0.586824E+09 | 846.15 | 28-APR-13:00 | 30.20 | 12.69 |
May | 0.767587E+10 | 18753.18 | 21-MAY-14:51 | 34.40 | 17.76 | 0.661897E+09 | 906.57 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.107415E+11 | 18417.40 | 25-JUN-17:31 | 31.30 | 16.59 | 0.668193E+09 | 969.65 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.103046E+11 | 18384.99 | 02-JUL-22:03 | 34.72 | 16.91 | 0.616777E+09 | 845.62 | 03-JUL-13:20 | 37.07 | 18.70 |
August | 0.903008E+10 | 18685.28 | 06-AUG-18:11 | 35.40 | 18.00 | 0.692370E+09 | 954.94 | 22-AUG-15:39 | 32.60 | 16.06 |
September | 0.633997E+10 | 11518.17 | 19-SEP-13:23 | 33.35 | 16.80 | 0.609214E+09 | 924.77 | 12-SEP-13:00 | 33.35 | 16.80 |
October | 0.366445E+10 | 9272.75 | 02-OCT-05:02 | 23.72 | 15.10 | 0.602421E+09 | 845.63 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.144245E+10 | 3306.71 | 09-NOV-15:00 | 23.30 | 12.64 | 0.517756E+09 | 845.62 | 09-NOV-14:20 | 23.30 | 12.64 |
December | 0.530698E+09 | 1561.06 | 07-DEC-14:30 | 15.85 | 6.83 | 0.459194E+09 | 726.39 | 01-DEC-14:00 | 15.85 | 6.83 |
Annual Sum or Average | 0.578599E+11 | 0.695500E+10 | ||||||||
Minimum of Months | 0.530698E+09 | 1561.06 | 15.85 | 6.83 | 0.459194E+09 | 726.39 | 15.85 | 6.83 | ||
Maximum of Months | 0.107415E+11 | 18753.18 | 35.40 | 18.00 | 0.692370E+09 | 969.65 | 37.07 | 18.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.914831E+09 | 2164.30 | 04-JAN-09:50 | 9.32 | 3.11 | 0.347470E+09 | 544.95 | 20-JAN-10:20 | 9.47 | 5.64 |
February | 0.136964E+10 | 4512.20 | 21-FEB-10:30 | 18.35 | 7.04 | 0.339601E+09 | 544.95 | 24-FEB-10:20 | 7.77 | 2.42 |
March | 0.289799E+10 | 6960.77 | 16-MAR-09:50 | 18.72 | 7.59 | 0.423665E+09 | 544.95 | 17-MAR-09:00 | 8.30 | 1.95 |
April | 0.585462E+10 | 19820.56 | 30-APR-08:32 | 19.43 | 12.60 | 0.392990E+09 | 545.53 | 28-APR-13:00 | 19.43 | 12.60 |
May | 0.873919E+10 | 19677.24 | 21-MAY-09:32 | 26.47 | 12.74 | 0.429394E+09 | 642.94 | 19-MAY-09:00 | 26.47 | 12.74 |
June | 0.107154E+11 | 19097.23 | 18-JUN-09:32 | 30.57 | 16.80 | 0.433684E+09 | 666.56 | 09-JUN-09:00 | 30.57 | 16.80 |
July | 0.101124E+11 | 20542.70 | 04-JUL-08:11 | 25.37 | 18.43 | 0.398233E+09 | 590.48 | 11-JUL-08:30 | 28.05 | 18.05 |
August | 0.941794E+10 | 20521.98 | 06-AUG-08:11 | 27.23 | 17.51 | 0.447780E+09 | 621.48 | 28-AUG-09:00 | 26.70 | 16.71 |
September | 0.747057E+10 | 18530.17 | 04-SEP-09:02 | 23.77 | 18.19 | 0.396048E+09 | 597.38 | 19-SEP-13:20 | 33.17 | 16.78 |
October | 0.425303E+10 | 18280.62 | 01-OCT-09:22 | 23.30 | 13.21 | 0.402409E+09 | 544.99 | 17-OCT-09:50 | 20.63 | 15.93 |
November | 0.171724E+10 | 7123.32 | 10-NOV-09:10 | 18.48 | 11.84 | 0.372827E+09 | 544.95 | 09-NOV-10:39 | 18.48 | 11.84 |
December | 0.773483E+09 | 1202.25 | 07-DEC-14:20 | 15.77 | 6.80 | 0.322865E+09 | 542.12 | 01-DEC-10:39 | 15.77 | 6.80 |
Annual Sum or Average | 0.642364E+11 | 0.470697E+10 | ||||||||
Minimum of Months | 0.773483E+09 | 1202.25 | 9.32 | 3.11 | 0.322865E+09 | 542.12 | 7.77 | 1.95 | ||
Maximum of Months | 0.107154E+11 | 20542.70 | 30.57 | 18.43 | 0.447780E+09 | 666.56 | 33.17 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541185E+10 | 16444.42 | 12-JAN-14:20 | 18.50 | 9.82 | 0.591011E+09 | 847.37 | 12-JAN-14:39 | 18.70 | 9.92 |
February | 0.522759E+10 | 20900.35 | 20-FEB-14:32 | 22.93 | 8.74 | 0.539748E+09 | 846.41 | 07-FEB-14:00 | 22.93 | 8.74 |
March | 0.607374E+10 | 14160.45 | 16-MAR-13:30 | 22.50 | 9.16 | 0.649492E+09 | 846.36 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.714314E+10 | 20987.84 | 30-APR-16:31 | 30.20 | 12.69 | 0.597457E+09 | 898.64 | 28-APR-13:00 | 30.20 | 12.69 |
May | 0.857982E+10 | 21147.47 | 21-MAY-14:51 | 34.40 | 17.76 | 0.662108E+09 | 938.60 | 25-MAY-13:50 | 30.60 | 14.84 |
June | 0.105691E+11 | 18452.46 | 04-JUN-16:11 | 35.40 | 17.17 | 0.667221E+09 | 972.38 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.106079E+11 | 20119.79 | 04-JUL-16:11 | 31.97 | 18.88 | 0.616676E+09 | 846.23 | 31-JUL-13:00 | 32.20 | 19.72 |
August | 0.113859E+11 | 21015.48 | 06-AUG-15:31 | 36.10 | 18.34 | 0.695937E+09 | 1043.50 | 31-AUG-13:30 | 28.05 | 17.53 |
September | 0.116344E+11 | 21502.48 | 17-SEP-13:32 | 32.03 | 15.98 | 0.618222E+09 | 1103.68 | 19-SEP-13:20 | 33.17 | 16.78 |
October | 0.106102E+11 | 24234.48 | 01-OCT-12:41 | 30.92 | 14.35 | 0.630749E+09 | 949.86 | 17-OCT-14:00 | 26.10 | 15.66 |
November | 0.756867E+10 | 22495.12 | 11-NOV-14:12 | 18.50 | 8.11 | 0.597231E+09 | 895.35 | 09-NOV-14:09 | 18.50 | 8.11 |
December | 0.498281E+10 | 14011.10 | 07-DEC-14:10 | 15.68 | 6.76 | 0.567221E+09 | 845.66 | 01-DEC-14:09 | 15.68 | 6.76 |
Annual Sum or Average | 0.997952E+11 | 0.743307E+10 | ||||||||
Minimum of Months | 0.498281E+10 | 14011.10 | 15.68 | 6.76 | 0.539748E+09 | 845.66 | 15.68 | 6.76 | ||
Maximum of Months | 0.116344E+11 | 24234.48 | 36.10 | 18.88 | 0.695937E+09 | 1103.68 | 33.17 | 19.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130473E+10 | 6142.64 | 12-JAN-15:30 | 18.90 | 10.10 | 0.342934E+09 | 544.94 | 11-JAN-14:30 | 18.90 | 10.10 |
February | 0.165639E+10 | 12200.22 | 19-FEB-16:42 | 22.30 | 8.28 | 0.322500E+09 | 544.94 | 14-FEB-14:20 | 22.30 | 8.28 |
March | 0.338130E+10 | 16238.03 | 26-MAR-15:53 | 22.20 | 8.76 | 0.405756E+09 | 544.95 | 09-MAR-14:20 | 22.20 | 8.76 |
April | 0.613286E+10 | 24860.69 | 30-APR-16:31 | 30.20 | 12.69 | 0.386646E+09 | 568.41 | 27-APR-15:50 | 30.20 | 12.69 |
May | 0.886739E+10 | 23895.00 | 07-MAY-17:11 | 28.70 | 13.88 | 0.428471E+09 | 588.08 | 08-MAY-15:00 | 32.20 | 15.81 |
June | 0.108299E+11 | 22971.49 | 25-JUN-16:51 | 31.70 | 16.84 | 0.430533E+09 | 621.89 | 27-JUN-13:00 | 31.70 | 16.85 |
July | 0.102733E+11 | 23349.59 | 04-JUL-16:11 | 31.97 | 18.88 | 0.398168E+09 | 544.95 | 03-JUL-09:00 | 31.97 | 18.88 |
August | 0.978402E+10 | 24796.18 | 06-AUG-16:51 | 36.10 | 18.82 | 0.447851E+09 | 697.31 | 22-AUG-15:00 | 32.80 | 15.90 |
September | 0.780693E+10 | 22262.06 | 17-SEP-15:32 | 32.80 | 15.98 | 0.395279E+09 | 609.79 | 12-SEP-13:00 | 32.80 | 15.98 |
October | 0.504625E+10 | 22941.32 | 22-OCT-15:31 | 27.03 | 14.73 | 0.400090E+09 | 568.55 | 17-OCT-15:00 | 27.03 | 14.73 |
November | 0.239522E+10 | 9631.89 | 09-NOV-15:30 | 23.30 | 12.82 | 0.362100E+09 | 544.94 | 09-NOV-14:20 | 23.30 | 12.82 |
December | 0.111472E+10 | 4776.95 | 15-DEC-15:50 | 15.60 | 6.12 | 0.328100E+09 | 544.94 | 01-DEC-14:30 | 15.60 | 6.12 |
Annual Sum or Average | 0.685930E+11 | 0.464843E+10 | ||||||||
Minimum of Months | 0.111472E+10 | 4776.95 | 15.60 | 6.12 | 0.322500E+09 | 544.94 | 15.60 | 6.12 | ||
Maximum of Months | 0.108299E+11 | 24860.69 | 36.10 | 18.88 | 0.447851E+09 | 697.31 | 32.80 | 18.88 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144715E+10 | 5775.34 | 02-JAN-06:15 | -0.2 | -1.0 | 0.00 | 0.00 | 01-JAN-00:10 | -0.2 | -1.0 |
February | 0.200565E+10 | 5707.80 | 21-FEB-06:15 | 5.20 | 0.40 | 0.00 | 0.00 | 01-FEB-00:10 | 5.20 | 0.40 |
March | 0.365163E+10 | 4688.89 | 16-MAR-15:40 | 22.40 | 8.49 | 0.00 | 0.00 | 01-MAR-00:10 | 22.40 | 8.49 |
April | 0.603429E+10 | 8155.37 | 17-APR-05:15 | 13.53 | 9.19 | 0.00 | 0.00 | 01-APR-00:10 | 13.53 | 9.19 |
May | 0.736111E+10 | 11420.39 | 30-MAY-05:15 | 25.00 | 11.65 | 0.00 | 0.00 | 01-MAY-00:10 | 25.00 | 11.65 |
June | 0.925388E+10 | 11826.41 | 19-JUN-05:15 | 22.80 | 15.92 | 0.00 | 0.00 | 01-JUN-00:10 | 22.80 | 15.92 |
July | 0.953605E+10 | 12017.67 | 03-JUL-05:15 | 27.43 | 17.31 | 0.00 | 0.00 | 01-JUL-00:10 | 27.43 | 17.31 |
August | 0.104469E+11 | 13820.64 | 07-AUG-05:25 | 25.55 | 16.20 | 0.00 | 0.00 | 01-AUG-00:10 | 25.55 | 16.20 |
September | 0.758623E+10 | 12290.16 | 05-SEP-05:15 | 16.30 | 15.51 | 0.00 | 0.00 | 01-SEP-00:10 | 16.30 | 15.51 |
October | 0.596651E+10 | 10284.54 | 02-OCT-05:15 | 23.53 | 15.10 | 0.00 | 0.00 | 01-OCT-00:10 | 23.53 | 15.10 |
November | 0.357881E+10 | 7084.66 | 13-NOV-06:15 | 2.40 | 0.12 | 0.00 | 0.00 | 01-NOV-00:10 | 2.40 | 0.12 |
December | 0.205449E+10 | 4887.06 | 11-DEC-06:15 | 10.77 | 5.99 | 0.00 | 0.00 | 01-DEC-00:10 | 10.77 | 5.99 |
Annual Sum or Average | 0.689227E+11 | 0.00 | ||||||||
Minimum of Months | 0.144715E+10 | 4688.89 | -0.2 | -1.0 | 0.00 | 0.00 | -0.2 | -1.0 | ||
Maximum of Months | 0.104469E+11 | 13820.64 | 27.43 | 17.31 | 0.00 | 0.00 | 27.43 | 17.31 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347753E+09 | 6068.73 | 06-JAN-06:01 | 0.10 | -3.8 | 0.00 | 0.00 | 01-JAN-00:10 | 0.10 | -3.8 |
February | 0.547002E+09 | 6760.94 | 09-FEB-06:02 | 0.60 | -2.3 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -2.3 |
March | 0.120936E+10 | 5760.84 | 02-MAR-06:01 | -3.5 | -6.2 | 0.00 | 0.00 | 01-MAR-00:10 | -3.5 | -6.2 |
April | 0.335516E+10 | 5158.90 | 21-APR-15:00 | 32.20 | 15.49 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 15.49 |
May | 0.585536E+10 | 8322.34 | 30-MAY-16:23 | 33.05 | 16.76 | 0.00 | 0.00 | 01-MAY-00:10 | 33.05 | 16.76 |
June | 0.773429E+10 | 8901.31 | 05-JUN-07:03 | 25.28 | 15.14 | 0.00 | 0.00 | 01-JUN-00:10 | 25.28 | 15.14 |
July | 0.738290E+10 | 10208.20 | 03-JUL-05:05 | 27.62 | 17.62 | 0.00 | 0.00 | 01-JUL-00:10 | 27.62 | 17.62 |
August | 0.722212E+10 | 10840.23 | 22-AUG-16:22 | 32.80 | 15.74 | 0.00 | 0.00 | 01-AUG-00:10 | 32.80 | 15.74 |
September | 0.583681E+10 | 8347.78 | 05-SEP-05:02 | 16.20 | 15.65 | 0.00 | 0.00 | 01-SEP-00:10 | 16.20 | 15.65 |
October | 0.345080E+10 | 6427.25 | 05-OCT-16:15 | 30.17 | 17.52 | 0.00 | 0.00 | 01-OCT-00:10 | 30.17 | 17.52 |
November | 0.110025E+10 | 6040.47 | 28-NOV-05:01 | -0.3 | -1.6 | 0.00 | 0.00 | 01-NOV-00:10 | -0.3 | -1.6 |
December | 0.332073E+09 | 5939.99 | 27-DEC-05:01 | -3.8 | -4.9 | 0.00 | 0.00 | 01-DEC-00:10 | -3.8 | -4.9 |
Annual Sum or Average | 0.443739E+11 | 0.00 | ||||||||
Minimum of Months | 0.332073E+09 | 5158.90 | -3.8 | -6.2 | 0.00 | 0.00 | -3.8 | -6.2 | ||
Maximum of Months | 0.773429E+10 | 10840.23 | 33.05 | 17.62 | 0.00 | 0.00 | 33.05 | 17.62 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170910E+09 | 3487.78 | 12-JAN-15:40 | 18.90 | 10.12 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.12 |
February | 0.754628E+09 | 6369.09 | 22-FEB-14:30 | 21.95 | 7.96 | 0.00 | 0.00 | 01-FEB-00:10 | 21.95 | 7.96 |
March | 0.245633E+10 | 9399.10 | 16-MAR-15:20 | 22.60 | 8.60 | 0.00 | 0.00 | 01-MAR-00:10 | 22.60 | 8.60 |
April | 0.660935E+10 | 18141.95 | 28-APR-13:45 | 28.72 | 14.13 | 0.00 | 0.00 | 01-APR-00:10 | 28.72 | 14.13 |
May | 0.111710E+11 | 20576.42 | 30-MAY-12:35 | 31.50 | 15.68 | 0.00 | 0.00 | 01-MAY-00:10 | 31.50 | 15.68 |
June | 0.155616E+11 | 23821.73 | 27-JUN-14:35 | 32.03 | 16.90 | 0.00 | 0.00 | 01-JUN-00:10 | 32.03 | 16.90 |
July | 0.144838E+11 | 23823.11 | 01-JUL-14:43 | 37.20 | 19.33 | 0.00 | 0.00 | 01-JUL-00:10 | 37.20 | 19.33 |
August | 0.133904E+11 | 21813.93 | 22-AUG-16:30 | 32.80 | 15.74 | 0.00 | 0.00 | 01-AUG-00:10 | 32.80 | 15.74 |
September | 0.101186E+11 | 20689.92 | 12-SEP-14:43 | 32.12 | 17.90 | 0.00 | 0.00 | 01-SEP-00:10 | 32.12 | 17.90 |
October | 0.505901E+10 | 16161.95 | 05-OCT-16:15 | 30.17 | 17.52 | 0.00 | 0.00 | 01-OCT-00:10 | 30.17 | 17.52 |
November | 0.123483E+10 | 7242.88 | 09-NOV-15:05 | 23.30 | 12.70 | 0.00 | 0.00 | 01-NOV-00:10 | 23.30 | 12.70 |
December | 69112147.51 | 1369.04 | 17-DEC-14:26 | 15.30 | 4.48 | 0.00 | 0.00 | 01-DEC-00:10 | 15.30 | 4.48 |
Annual Sum or Average | 0.810794E+11 | 0.00 | ||||||||
Minimum of Months | 69112147.51 | 1369.04 | 15.30 | 4.48 | 0.00 | 0.00 | 15.30 | 4.48 | ||
Maximum of Months | 0.155616E+11 | 23823.11 | 37.20 | 19.33 | 0.00 | 0.00 | 37.20 | 19.33 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353850E+10 | 2101.79 | 01-JAN-16:57 | 14.40 | 8.48 | 95231164.39 | 126.83 | 17-JAN-10:00 | 8.90 | 5.56 |
February | 0.804737E+10 | 4172.04 | 20-FEB-17:30 | 21.65 | 8.03 | 86397300.82 | 126.84 | 13-FEB-14:00 | 21.65 | 8.03 |
March | 0.142645E+11 | 7086.40 | 31-MAR-24:00 | 11.20 | 2.36 | 0.103236E+09 | 126.82 | 13-MAR-09:09 | 11.20 | 2.36 |
April | 0.188590E+11 | 7803.45 | 22-APR-18:35 | 17.23 | 6.31 | 92402699.30 | 139.49 | 21-APR-13:00 | 17.23 | 6.31 |
May | 0.455694E+10 | 3462.92 | 31-MAY-24:00 | 25.20 | 11.70 | 99236652.69 | 126.85 | 24-MAY-13:09 | 25.20 | 11.70 |
June | 0.938127E+10 | 5340.70 | 30-JUN-23:55 | 27.70 | 17.05 | 98962233.75 | 126.85 | 28-JUN-09:00 | 27.70 | 17.05 |
July | 0.147896E+11 | 7300.44 | 31-JUL-24:00 | 27.50 | 18.10 | 91888013.91 | 126.85 | 19-JUL-09:09 | 27.50 | 18.10 |
August | 0.197881E+11 | 7799.68 | 13-AUG-23:15 | 22.67 | 17.41 | 0.106858E+09 | 143.49 | 07-AUG-13:00 | 22.67 | 17.41 |
September | 0.448956E+10 | 3463.23 | 30-SEP-24:00 | 16.10 | 8.62 | 91614049.18 | 126.85 | 01-SEP-13:00 | 16.10 | 8.62 |
October | 0.953429E+10 | 5252.57 | 31-OCT-24:00 | 10.60 | 4.98 | 95237345.89 | 126.85 | 04-OCT-09:00 | 10.60 | 4.98 |
November | 0.138457E+11 | 6101.96 | 12-NOV-16:35 | 14.60 | 6.96 | 94301791.07 | 126.84 | 01-NOV-13:00 | 14.60 | 6.96 |
December | 0.191218E+11 | 7780.09 | 17-DEC-16:47 | 14.18 | 4.01 | 91880913.50 | 126.82 | 14-DEC-14:00 | 14.18 | 4.01 |
Annual Sum or Average | 0.140217E+12 | 0.114725E+10 | ||||||||
Minimum of Months | 0.353850E+10 | 2101.79 | 10.60 | 2.36 | 86397300.82 | 126.82 | 8.90 | 2.36 | ||
Maximum of Months | 0.197881E+11 | 7803.45 | 27.70 | 18.10 | 0.106858E+09 | 143.49 | 27.70 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190919E+10 | 1764.44 | 30-JAN-17:00 | 15.60 | 6.12 | 95231010.23 | 126.83 | 02-JAN-14:00 | 15.60 | 6.12 |
February | 0.664206E+10 | 3679.71 | 19-FEB-17:24 | 21.65 | 7.91 | 86397277.31 | 126.84 | 13-FEB-14:00 | 21.65 | 7.91 |
March | 0.128313E+11 | 6576.60 | 31-MAR-23:40 | 11.27 | 2.40 | 0.103236E+09 | 126.82 | 13-MAR-09:09 | 11.27 | 2.40 |
April | 0.177365E+11 | 7415.00 | 22-APR-18:20 | 17.77 | 6.48 | 92269888.71 | 138.12 | 21-APR-13:00 | 17.77 | 6.48 |
May | 0.415393E+10 | 3379.02 | 31-MAY-24:00 | 25.20 | 11.70 | 99235967.59 | 126.84 | 23-MAY-13:09 | 25.20 | 11.70 |
June | 0.891210E+10 | 5191.27 | 30-JUN-23:55 | 27.70 | 17.05 | 98962035.86 | 126.85 | 28-JUN-09:00 | 27.70 | 17.05 |
July | 0.140481E+11 | 7013.57 | 31-JUL-24:00 | 27.50 | 18.10 | 91887735.95 | 126.84 | 19-JUL-09:09 | 27.50 | 18.10 |
August | 0.186380E+11 | 7299.59 | 27-AUG-20:52 | 26.10 | 14.02 | 0.105915E+09 | 139.20 | 04-AUG-13:00 | 26.10 | 14.02 |
September | 0.402369E+10 | 3244.44 | 30-SEP-23:50 | 16.20 | 8.79 | 91611479.21 | 126.85 | 05-SEP-13:00 | 16.20 | 8.79 |
October | 0.859417E+10 | 4819.07 | 31-OCT-24:00 | 10.60 | 4.98 | 95237011.39 | 126.85 | 04-OCT-09:00 | 10.60 | 4.98 |
November | 0.121647E+11 | 5621.61 | 09-NOV-16:50 | 22.88 | 12.85 | 94301739.28 | 126.83 | 01-NOV-13:00 | 22.88 | 12.85 |
December | 0.166000E+11 | 7217.05 | 15-DEC-16:50 | 15.10 | 5.92 | 91880966.71 | 126.82 | 14-DEC-14:00 | 15.10 | 5.92 |
Annual Sum or Average | 0.126254E+12 | 0.114617E+10 | ||||||||
Minimum of Months | 0.190919E+10 | 1764.44 | 10.60 | 2.40 | 86397277.31 | 126.82 | 10.60 | 2.40 | ||
Maximum of Months | 0.186380E+11 | 7415.00 | 27.70 | 18.10 | 0.105915E+09 | 139.20 | 27.70 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763130E+09 | 1662.42 | 12-JAN-16:50 | 17.98 | 9.87 | 94523256.81 | 129.27 | 02-JAN-10:00 | 17.98 | 9.87 |
February | 0.534006E+10 | 3645.80 | 21-FEB-17:30 | 21.40 | 7.38 | 86397263.62 | 126.84 | 13-FEB-14:00 | 21.40 | 7.38 |
March | 0.118795E+11 | 6283.87 | 31-MAR-23:20 | 11.33 | 2.45 | 0.103236E+09 | 126.82 | 13-MAR-09:09 | 11.33 | 2.45 |
April | 0.174846E+11 | 7465.14 | 26-APR-18:00 | 25.60 | 12.63 | 91988284.66 | 136.77 | 21-APR-13:00 | 25.60 | 12.63 |
May | 0.413672E+10 | 3411.93 | 31-MAY-24:00 | 25.20 | 11.70 | 99236321.85 | 126.84 | 24-MAY-13:39 | 25.20 | 11.70 |
June | 0.903038E+10 | 5207.32 | 30-JUN-23:55 | 27.70 | 17.05 | 98962226.71 | 126.85 | 28-JUN-09:00 | 27.70 | 17.05 |
July | 0.142042E+11 | 7017.38 | 31-JUL-24:00 | 27.50 | 18.10 | 91888260.72 | 126.85 | 19-JUL-09:09 | 27.50 | 18.10 |
August | 0.187466E+11 | 7481.68 | 27-AUG-21:03 | 26.20 | 14.02 | 0.105262E+09 | 138.44 | 04-AUG-13:00 | 26.20 | 14.02 |
September | 0.397004E+10 | 3104.94 | 30-SEP-23:20 | 16.50 | 9.30 | 91612224.05 | 126.85 | 01-SEP-13:00 | 16.50 | 9.30 |
October | 0.811459E+10 | 4499.34 | 31-OCT-23:20 | 10.60 | 4.70 | 95237128.04 | 126.85 | 04-OCT-09:00 | 10.60 | 4.70 |
November | 0.107960E+11 | 5647.08 | 09-NOV-16:50 | 22.88 | 12.85 | 94301806.41 | 126.83 | 01-NOV-13:00 | 22.88 | 12.85 |
December | 0.145886E+11 | 7106.93 | 15-DEC-16:50 | 15.10 | 5.92 | 91881016.42 | 126.82 | 04-DEC-14:00 | 15.10 | 5.92 |
Annual Sum or Average | 0.119054E+12 | 0.114453E+10 | ||||||||
Minimum of Months | 0.763130E+09 | 1662.42 | 10.60 | 2.45 | 86397263.62 | 126.82 | 10.60 | 2.45 | ||
Maximum of Months | 0.187466E+11 | 7481.68 | 27.70 | 18.10 | 0.105262E+09 | 138.44 | 27.70 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236848E+12 | 91226.23 | 02-JAN-17:00 | 16.70 | 8.66 | 0.206150E+10 | 2745.44 | 06-JAN-10:00 | 6.10 | 0.48 |
February | 0.432761E+12 | 181834.91 | 21-FEB-17:00 | 22.20 | 7.81 | 0.187026E+10 | 2745.56 | 16-FEB-10:09 | 22.20 | 7.81 |
March | 0.724009E+12 | 356817.90 | 31-MAR-24:00 | 11.20 | 2.36 | 0.223477E+10 | 2745.59 | 27-MAR-09:09 | 11.20 | 2.36 |
April | 0.936473E+12 | 371632.40 | 16-APR-19:32 | 24.63 | 9.91 | 0.209700E+10 | 4151.78 | 21-APR-13:00 | 32.20 | 15.21 |
May | 0.238508E+12 | 174911.65 | 31-MAY-24:00 | 25.20 | 11.70 | 0.214844E+10 | 2748.06 | 18-MAY-13:09 | 25.20 | 11.70 |
June | 0.467157E+12 | 266484.58 | 30-JUN-24:00 | 27.70 | 17.05 | 0.214287E+10 | 2749.31 | 27-JUN-13:20 | 27.70 | 17.05 |
July | 0.728804E+12 | 354742.89 | 31-JUL-23:20 | 28.17 | 17.81 | 0.207926E+10 | 3629.90 | 17-JUL-13:00 | 28.17 | 17.81 |
August | 0.965475E+12 | 377781.33 | 27-AUG-20:52 | 26.10 | 14.02 | 0.286981E+10 | 4501.21 | 03-AUG-13:09 | 26.10 | 14.02 |
September | 0.236306E+12 | 176597.60 | 30-SEP-24:00 | 16.10 | 8.62 | 0.198335E+10 | 2747.97 | 07-SEP-13:00 | 16.10 | 8.62 |
October | 0.487240E+12 | 268251.11 | 31-OCT-24:00 | 10.60 | 4.98 | 0.206182E+10 | 2749.39 | 19-OCT-09:50 | 10.60 | 4.98 |
November | 0.707250E+12 | 275615.59 | 13-NOV-17:00 | 18.30 | 9.24 | 0.204158E+10 | 2749.84 | 03-NOV-13:09 | 18.30 | 9.24 |
December | 0.974270E+12 | 366539.31 | 18-DEC-17:00 | 8.90 | -0.7 | 0.198907E+10 | 2746.84 | 04-DEC-14:00 | 8.90 | -0.7 |
Annual Sum or Average | 0.713510E+13 | 0.255797E+11 | ||||||||
Minimum of Months | 0.236306E+12 | 91226.23 | 8.90 | -0.7 | 0.187026E+10 | 2745.44 | 6.10 | -0.7 | ||
Maximum of Months | 0.974270E+12 | 377781.33 | 28.17 | 17.81 | 0.286981E+10 | 4501.21 | 32.20 | 17.81 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221821E+09 | 10989.71 | 04-JAN-05:15 | 8.53 |
February | 0.116855E+09 | 10918.94 | 28-FEB-05:14 | 6.83 |
March | 0.146011E+09 | 10997.24 | 28-MAR-04:15 | 7.60 |
April | 0.249135E+09 | 17126.54 | 29-APR-16:01 | 31.02 |
May | 0.328962E+09 | 18732.71 | 20-MAY-16:01 | 32.20 |
June | 0.296599E+09 | 23023.41 | 17-JUN-16:01 | 35.68 |
July | 0.439558E+09 | 24592.11 | 01-JUL-16:25 | 38.05 |
August | 0.393263E+09 | 20823.68 | 05-AUG-16:01 | 33.98 |
September | 0.469249E+09 | 18537.39 | 02-SEP-16:01 | 32.23 |
October | 0.327223E+09 | 12543.09 | 01-OCT-16:42 | 31.20 |
November | 0.327735E+09 | 12888.32 | 12-NOV-10:33 | 11.33 |
December | 0.269453E+09 | 10850.50 | 12-DEC-05:55 | 1.70 |
Annual Sum or Average | 0.358586E+10 | |||
Minimum of Months | 0.116855E+09 | 10850.50 | 1.70 | |
Maximum of Months | 0.469249E+09 | 24592.11 | 38.05 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.647495E+09 | 64801.03 | 17-JAN-05:11 | 5.20 |
February | 45737571.41 | 57882.31 | 27-FEB-06:02 | 8.80 |
March | 5440016.76 | 52746.90 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.284367E+09 | 63808.34 | 27-NOV-05:11 | 3.30 |
December | 0.942633E+09 | 66015.00 | 04-DEC-05:11 | -0.8 |
Annual Sum or Average | 0.192567E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.942633E+09 | 66015.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3562938.87 | 8448.11 | 28-JAN-06:01 | -3.3 |
February | 124132.14 | 1384.49 | 02-FEB-06:01 | -3.5 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 3687071.01 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 3562938.87 | 8448.11 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3484798.90 | 6273.76 | 28-JAN-06:01 | -3.3 |
February | 1676083.95 | 3513.97 | 02-FEB-06:01 | -3.5 |
March | 264973.53 | 2503.95 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 1189382.10 | 3856.67 | 30-DEC-06:01 | -2.9 |
Annual Sum or Average | 6615238.48 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 3484798.90 | 6273.76 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1821682.75 | 7564.11 | 28-JAN-06:01 | -3.3 |
February | 314183.81 | 2408.32 | 02-FEB-06:01 | -3.5 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 400815.18 | 5108.42 | 28-NOV-06:01 | 1.02 |
December | 5720029.64 | 10114.88 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 8256711.38 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 5720029.64 | 10114.88 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564539E+09 | 12225.57 | 28-JAN-05:01 | -2.9 |
February | 0.297073E+09 | 12120.53 | 02-FEB-05:01 | -2.4 |
March | 91890886.50 | 11886.39 | 02-MAR-05:01 | -3.9 |
April | 784953.47 | 4832.24 | 11-APR-05:03 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.156829E+09 | 12222.63 | 28-NOV-05:01 | -0.3 |
December | 0.726626E+09 | 12509.51 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.183774E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.726626E+09 | 12509.51 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253268E+09 | 12188.73 | 28-JAN-05:01 | -2.9 |
February | 0.112052E+09 | 12100.75 | 02-FEB-05:01 | -2.4 |
March | 32685508.95 | 11866.04 | 02-MAR-05:01 | -3.9 |
April | 315330.74 | 2102.20 | 11-APR-05:03 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 60674021.49 | 12408.78 | 28-NOV-05:01 | -0.3 |
December | 0.316718E+09 | 12572.52 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.775712E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.316718E+09 | 12572.52 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132284E+09 | 13212.04 | 26-JAN-05:01 | 1.20 |
February | 83374401.24 | 13042.01 | 09-FEB-05:01 | -0.4 |
March | 23131538.16 | 12573.87 | 02-MAR-06:01 | -3.5 |
April | 313961.33 | 2093.08 | 11-APR-05:03 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 41108500.72 | 13368.22 | 28-NOV-05:01 | -0.3 |
December | 0.200787E+09 | 13444.93 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.481000E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.200787E+09 | 13444.93 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150540E+09 | 11877.27 | 26-JAN-05:01 | 1.20 |
February | 82006415.84 | 11209.64 | 02-FEB-06:01 | -3.5 |
March | 17661597.55 | 11197.62 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 29590347.18 | 11817.60 | 28-NOV-05:01 | -0.3 |
December | 0.184862E+09 | 12163.52 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.464660E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.184862E+09 | 12163.52 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255471E+10 | 15916.97 | 09-JAN-04:01 | 0.55 |
February | 0.145895E+10 | 15132.87 | 02-FEB-04:02 | -1.3 |
March | 0.732189E+09 | 14719.90 | 02-MAR-04:03 | -3.0 |
April | 51451418.10 | 13559.21 | 11-APR-04:12 | 5.40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 9722096.53 | 10757.08 | 25-OCT-05:03 | 7.12 |
November | 0.112211E+10 | 15823.20 | 27-NOV-05:11 | 3.30 |
December | 0.315855E+10 | 15964.81 | 18-DEC-05:11 | 4.03 |
Annual Sum or Average | 0.908769E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 0.315855E+10 | 15964.81 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112906E+10 | 15009.82 | 09-JAN-04:01 | 0.55 |
February | 0.552088E+09 | 13846.73 | 01-FEB-05:01 | -0.6 |
March | 0.285537E+09 | 13894.38 | 01-MAR-05:01 | 1.20 |
April | 18268485.63 | 11673.29 | 11-APR-04:12 | 5.40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 4640577.86 | 6938.89 | 25-OCT-05:03 | 7.12 |
November | 0.473286E+09 | 15104.31 | 27-NOV-05:11 | 3.30 |
December | 0.139012E+10 | 15001.21 | 04-DEC-04:01 | -0.1 |
Annual Sum or Average | 0.385300E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.139012E+10 | 15104.31 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107143E+10 | 16630.69 | 17-JAN-05:11 | 5.20 |
February | 0.627943E+09 | 15756.22 | 01-FEB-05:01 | -0.6 |
March | 0.337838E+09 | 15745.80 | 01-MAR-05:01 | 1.20 |
April | 36648346.20 | 14701.07 | 11-APR-04:12 | 5.40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 3428.52 | 5.71 | 25-OCT-06:00 | 6.70 |
November | 0.464891E+09 | 17398.98 | 27-NOV-05:11 | 3.30 |
December | 0.130074E+10 | 17310.00 | 26-DEC-04:01 | -0.1 |
Annual Sum or Average | 0.383949E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.130074E+10 | 17398.98 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.869072E+09 | 15996.27 | 09-JAN-05:11 | 3.13 |
February | 0.484954E+09 | 15168.83 | 01-FEB-05:01 | -0.6 |
March | 0.168223E+09 | 15128.41 | 01-MAR-05:01 | 1.20 |
April | 10441701.53 | 8132.34 | 11-APR-05:03 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.319631E+09 | 16399.40 | 27-NOV-05:11 | 3.30 |
December | 0.100829E+10 | 16411.35 | 26-DEC-04:01 | -0.1 |
Annual Sum or Average | 0.286061E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.100829E+10 | 16411.35 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82605015.27 | 8496.46 | 09-JAN-05:11 | 3.13 |
February | 0.115056E+09 | 8650.81 | 19-FEB-14:52 | 22.80 |
March | 0.119569E+09 | 8188.59 | 01-MAR-05:01 | 1.20 |
April | 0.121376E+09 | 8636.43 | 14-APR-04:12 | 14.43 |
May | 63847098.69 | 8252.26 | 28-MAY-15:31 | 32.20 |
June | 60401448.45 | 8657.18 | 25-JUN-16:41 | 31.60 |
July | 81855370.66 | 7941.42 | 02-JUL-15:42 | 38.22 |
August | 92300441.51 | 9002.86 | 20-AUG-16:21 | 32.50 |
September | 65101215.40 | 7921.83 | 17-SEP-15:11 | 32.80 |
October | 0.102654E+09 | 8080.38 | 01-OCT-14:01 | 32.30 |
November | 0.122109E+09 | 9949.12 | 27-NOV-05:11 | 3.30 |
December | 0.145665E+09 | 11052.57 | 18-DEC-05:11 | 4.03 |
Annual Sum or Average | 0.117254E+10 | |||
Minimum of Months | 60401448.45 | 7921.83 | 1.20 | |
Maximum of Months | 0.145665E+09 | 11052.57 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103704E+10 | 6116.36 | 29-JAN-12:53 | 12.80 |
February | 0.473910E+09 | 6991.48 | 19-FEB-16:23 | 22.50 |
March | 0.172838E+09 | 7684.19 | 05-MAR-15:41 | 19.90 |
April | 53810310.91 | 7588.63 | 16-APR-15:31 | 29.80 |
May | 54718395.24 | 6653.61 | 21-MAY-15:12 | 34.40 |
June | 48085022.08 | 8187.64 | 18-JUN-15:31 | 37.03 |
July | 63468065.26 | 8202.40 | 02-JUL-16:01 | 38.22 |
August | 50122748.41 | 8490.18 | 06-AUG-14:51 | 36.10 |
September | 49173495.70 | 7441.93 | 17-SEP-16:01 | 32.62 |
October | 68488944.35 | 7704.46 | 08-OCT-15:22 | 26.40 |
November | 0.306014E+09 | 6028.32 | 11-NOV-15:02 | 18.80 |
December | 0.102533E+10 | 6255.88 | 31-DEC-13:02 | 11.47 |
Annual Sum or Average | 0.340300E+10 | |||
Minimum of Months | 48085022.08 | 6028.32 | 11.47 | |
Maximum of Months | 0.103704E+10 | 8490.18 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364535E+10 | 16403.34 | 09-JAN-06:02 | 2.98 |
February | 0.251079E+10 | 12815.94 | 03-FEB-06:01 | -3.7 |
March | 0.195196E+10 | 11829.80 | 16-MAR-05:02 | 14.43 |
April | 0.678560E+09 | 14250.22 | 22-APR-05:02 | 8.80 |
May | 0.243593E+09 | 13551.67 | 06-MAY-05:02 | 10.50 |
June | 66717863.25 | 10336.16 | 05-JUN-04:12 | 22.57 |
July | 42968710.00 | 10767.88 | 05-JUL-04:12 | 19.27 |
August | 63035539.73 | 9966.65 | 28-AUG-04:12 | 22.03 |
September | 0.219901E+09 | 14154.32 | 25-SEP-05:03 | 9.08 |
October | 0.718619E+09 | 12470.25 | 23-OCT-05:03 | 12.80 |
November | 0.220416E+10 | 15614.33 | 27-NOV-06:03 | 3.30 |
December | 0.442030E+10 | 19923.13 | 04-DEC-06:03 | -1.0 |
Annual Sum or Average | 0.167660E+11 | |||
Minimum of Months | 42968710.00 | 9966.65 | -3.7 | |
Maximum of Months | 0.442030E+10 | 19923.13 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516695E+09 | 599.34 | 28-JAN-04:00 | -2.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.516695E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.2 | |
Maximum of Months | 0.516695E+09 | 599.34 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.993138E+10 | 10437.26 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.900860E+10 | 10437.26 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.107039E+11 | 10437.26 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.956184E+10 | 10437.26 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.103176E+11 | 10437.26 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.102675E+11 | 10437.26 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.961194E+10 | 10437.26 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.107039E+11 | 10437.26 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.956184E+10 | 10437.26 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.993138E+10 | 10437.26 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.981449E+10 | 10437.26 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.961194E+10 | 10437.26 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.119026E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.900860E+10 | 10437.26 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.107039E+11 | 10437.26 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.891908E+10 | 9373.40 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.809036E+10 | 9373.40 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.961283E+10 | 9373.40 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.858720E+10 | 9373.40 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.926596E+10 | 9373.40 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.922097E+10 | 9373.40 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.863220E+10 | 9373.40 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.961283E+10 | 9373.40 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.858720E+10 | 9373.40 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.891908E+10 | 9373.40 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.881410E+10 | 9373.40 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.863220E+10 | 9373.40 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.106894E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.809036E+10 | 9373.40 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.961283E+10 | 9373.40 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.891908E+10 | 9373.40 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.809036E+10 | 9373.40 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.961283E+10 | 9373.40 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.858720E+10 | 9373.40 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.926596E+10 | 9373.40 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.922097E+10 | 9373.40 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.863220E+10 | 9373.40 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.961283E+10 | 9373.40 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.858720E+10 | 9373.40 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.891908E+10 | 9373.40 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.881410E+10 | 9373.40 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.863220E+10 | 9373.40 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.106894E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.809036E+10 | 9373.40 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.961283E+10 | 9373.40 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.891908E+10 | 9373.40 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.809036E+10 | 9373.40 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.961283E+10 | 9373.40 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.858720E+10 | 9373.40 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.926596E+10 | 9373.40 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.922097E+10 | 9373.40 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.863220E+10 | 9373.40 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.961283E+10 | 9373.40 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.858720E+10 | 9373.40 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.891908E+10 | 9373.40 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.881410E+10 | 9373.40 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.863220E+10 | 9373.40 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.106894E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.809036E+10 | 9373.40 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.961283E+10 | 9373.40 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.701055E+09 | 1096.10 | 17-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.612832E+09 | 950.41 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.684294E+09 | 921.86 | 10-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.591027E+09 | 648.81 | 20-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.627659E+09 | 593.54 | 23-MAY-12:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.616507E+09 | 559.98 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.582834E+09 | 644.37 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.659432E+09 | 641.38 | 17-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.601739E+09 | 630.26 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.654927E+09 | 999.54 | 13-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.686857E+09 | 1176.92 | 22-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.692212E+09 | 1176.92 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.771138E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.582834E+09 | 559.98 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.701055E+09 | 1176.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.445741E+09 | 707.28 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.391927E+09 | 635.12 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.439211E+09 | 604.21 | 10-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.382439E+09 | 403.22 | 20-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.407385E+09 | 391.19 | 24-MAY-15:39 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.400852E+09 | 360.87 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.379435E+09 | 406.89 | 03-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.426532E+09 | 411.76 | 16-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.386248E+09 | 360.87 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.418831E+09 | 631.32 | 13-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.438660E+09 | 758.45 | 22-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.441680E+09 | 758.45 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.495894E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.379435E+09 | 360.87 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.445741E+09 | 758.45 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669989E+09 | 1090.52 | 17-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.595018E+09 | 910.77 | 23-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.678584E+09 | 909.56 | 10-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.593568E+09 | 648.71 | 20-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.632890E+09 | 599.41 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.622902E+09 | 559.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.589624E+09 | 648.17 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.662518E+09 | 644.59 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.599873E+09 | 608.30 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.644568E+09 | 992.38 | 13-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.659592E+09 | 1176.95 | 22-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.663760E+09 | 1176.95 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.761289E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.589624E+09 | 559.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.678584E+09 | 1176.95 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.436171E+09 | 700.19 | 17-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.385303E+09 | 580.19 | 13-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.437702E+09 | 563.30 | 10-MAR-16:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.380400E+09 | 424.85 | 20-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.403787E+09 | 402.40 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.397282E+09 | 360.87 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.375591E+09 | 421.44 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.424743E+09 | 483.88 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.386325E+09 | 410.13 | 28-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.416286E+09 | 647.20 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.426364E+09 | 758.45 | 22-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.430965E+09 | 758.45 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.490092E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.375591E+09 | 360.87 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.437702E+09 | 758.45 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.698956E+09 | 1095.20 | 17-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.610887E+09 | 945.01 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.683011E+09 | 918.92 | 10-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.590584E+09 | 644.54 | 20-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.627446E+09 | 559.98 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.616304E+09 | 559.98 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.582250E+09 | 639.83 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.658756E+09 | 636.68 | 17-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.600727E+09 | 624.04 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.653720E+09 | 997.53 | 13-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.684870E+09 | 1176.92 | 22-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.690511E+09 | 1176.92 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.769802E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.582250E+09 | 559.98 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.698956E+09 | 1176.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.444904E+09 | 705.96 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.391120E+09 | 631.84 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.438632E+09 | 600.16 | 10-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.382135E+09 | 400.22 | 20-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.407112E+09 | 386.77 | 24-MAY-15:39 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.400599E+09 | 360.87 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.379005E+09 | 403.55 | 03-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.426122E+09 | 408.70 | 16-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.385913E+09 | 360.87 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.418340E+09 | 628.21 | 13-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.437903E+09 | 758.45 | 22-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.441077E+09 | 758.45 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.495286E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.379005E+09 | 360.87 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.444904E+09 | 758.45 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669609E+09 | 1089.62 | 17-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.594568E+09 | 907.90 | 23-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.678024E+09 | 906.55 | 10-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.593046E+09 | 644.43 | 20-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.632439E+09 | 559.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.622439E+09 | 559.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.588882E+09 | 643.82 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.661824E+09 | 640.07 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.599144E+09 | 600.00 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.643294E+09 | 990.33 | 13-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.659048E+09 | 1176.95 | 22-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.663544E+09 | 1176.95 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.760586E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.588882E+09 | 559.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.678024E+09 | 1176.95 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435912E+09 | 698.78 | 17-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.384561E+09 | 575.53 | 13-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.437165E+09 | 558.92 | 10-MAR-16:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.380151E+09 | 422.54 | 20-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.403611E+09 | 398.82 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.397174E+09 | 360.87 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.375218E+09 | 418.94 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.424295E+09 | 420.49 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.385893E+09 | 407.00 | 28-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.415836E+09 | 644.29 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.425850E+09 | 758.45 | 22-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.430514E+09 | 758.45 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.489618E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.375218E+09 | 360.87 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.437165E+09 | 758.45 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.698869E+09 | 1095.03 | 17-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.610829E+09 | 944.91 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.682981E+09 | 918.39 | 10-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.590573E+09 | 644.37 | 20-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.627441E+09 | 559.98 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.616297E+09 | 559.98 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.582237E+09 | 639.65 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.658738E+09 | 636.50 | 17-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.600710E+09 | 623.93 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.653679E+09 | 997.16 | 13-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.684812E+09 | 1176.92 | 22-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.690486E+09 | 1176.92 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.769765E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.582237E+09 | 559.98 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.698869E+09 | 1176.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.444877E+09 | 705.85 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.391089E+09 | 631.62 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.438622E+09 | 599.83 | 10-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.382128E+09 | 400.07 | 20-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.407097E+09 | 386.64 | 24-MAY-15:39 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.400590E+09 | 360.87 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.378982E+09 | 403.42 | 03-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.426112E+09 | 408.58 | 16-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.385909E+09 | 360.87 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.418369E+09 | 627.95 | 13-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.437937E+09 | 758.45 | 22-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.441031E+09 | 758.45 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.495274E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.378982E+09 | 360.87 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.444877E+09 | 758.45 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669601E+09 | 1089.44 | 17-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.594549E+09 | 907.36 | 23-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.678008E+09 | 906.00 | 10-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.593027E+09 | 644.26 | 20-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.632430E+09 | 559.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.622417E+09 | 559.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.588844E+09 | 643.64 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.661778E+09 | 639.89 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.599117E+09 | 599.87 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.643272E+09 | 989.94 | 13-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.659039E+09 | 1176.95 | 22-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.663537E+09 | 1176.95 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.760562E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.588844E+09 | 559.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.678008E+09 | 1176.95 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435902E+09 | 698.66 | 17-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.384548E+09 | 575.16 | 13-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.437139E+09 | 558.55 | 10-MAR-16:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.380145E+09 | 422.45 | 20-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.403608E+09 | 398.68 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.397172E+09 | 360.87 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.375196E+09 | 418.84 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.424283E+09 | 420.39 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.385886E+09 | 406.89 | 28-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.415827E+09 | 644.05 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.425842E+09 | 758.45 | 22-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.430483E+09 | 758.45 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.489603E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.375196E+09 | 360.87 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.437139E+09 | 758.45 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.209474E+09 | 219.21 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.190008E+09 | 219.21 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.225783E+09 | 219.21 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.201670E+09 | 219.21 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.217628E+09 | 219.21 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.216576E+09 | 219.21 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.202722E+09 | 219.21 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.225783E+09 | 219.21 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.201670E+09 | 219.21 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.209474E+09 | 219.21 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.207019E+09 | 219.21 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.202722E+09 | 219.21 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.251053E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.190008E+09 | 219.21 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.225783E+09 | 219.21 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.209474E+09 | 219.21 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.190008E+09 | 219.21 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.225783E+09 | 219.21 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.201670E+09 | 219.21 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.217628E+09 | 219.21 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.216576E+09 | 219.21 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.202722E+09 | 219.21 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.225783E+09 | 219.21 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.201670E+09 | 219.21 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.209474E+09 | 219.21 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.207019E+09 | 219.21 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.202722E+09 | 219.21 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.251053E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.190008E+09 | 219.21 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.225783E+09 | 219.21 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.209474E+09 | 219.21 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.190008E+09 | 219.21 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.225783E+09 | 219.21 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.201670E+09 | 219.21 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.217628E+09 | 219.21 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.216576E+09 | 219.21 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.202722E+09 | 219.21 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.225783E+09 | 219.21 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.201670E+09 | 219.21 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.209474E+09 | 219.21 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.207019E+09 | 219.21 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.202722E+09 | 219.21 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.251053E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.190008E+09 | 219.21 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.225783E+09 | 219.21 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281219E+10 | 2942.86 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.255087E+10 | 2942.86 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.303114E+10 | 2942.86 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.270743E+10 | 2942.86 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.292167E+10 | 2942.86 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.290754E+10 | 2942.86 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.272155E+10 | 2942.86 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.303114E+10 | 2942.86 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.270743E+10 | 2942.86 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.281219E+10 | 2942.86 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.277923E+10 | 2942.86 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.272155E+10 | 2942.86 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.337039E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.255087E+10 | 2942.86 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.303114E+10 | 2942.86 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.993138E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.900860E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.107039E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.956184E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.103176E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.102675E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.961194E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.107039E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.956184E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.993138E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.981449E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.961194E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.119026E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.900860E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.107039E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.891908E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.809036E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.961283E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.858720E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.926596E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.922097E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.863220E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.961283E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.858720E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.891908E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.881410E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.863220E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.106894E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.809036E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.961283E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.891908E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.809036E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.961283E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.858720E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.926596E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.922097E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.863220E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.961283E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.858720E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.891908E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.881410E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.863220E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.106894E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.809036E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.961283E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.891908E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.809036E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.961283E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.858720E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.926596E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.922097E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.863220E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.961283E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.858720E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.891908E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.881410E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.863220E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.106894E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.809036E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.961283E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.701055E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519534E+09 |
February | 0.136985E+10 | 0.612832E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438894E+09 |
March | 0.163685E+10 | 0.684294E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140777.57 | 0.460951E+09 |
April | 0.145243E+10 | 0.591027E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22276839.54 | 0.239424E+09 |
May | 0.157338E+10 | 0.627659E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69322226.58 | 0.132238E+09 |
June | 0.156900E+10 | 0.616507E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110934E+09 | 41977780.21 |
July | 0.145680E+10 | 0.582834E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90912511.48 | 28060498.38 |
August | 0.163685E+10 | 0.659432E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71214049.32 | 42455068.07 |
September | 0.145243E+10 | 0.601739E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22468104.40 | 66383810.76 |
October | 0.150991E+10 | 0.654927E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8490630.36 | 0.219739E+09 |
November | 0.149516E+10 | 0.686857E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430343E+09 |
December | 0.145680E+10 | 0.692212E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464260E+09 |
Annual Sum or Average | 0.181194E+11 | 0.771138E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395759E+09 | 0.308426E+10 |
Minimum of Months | 0.136985E+10 | 0.582834E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28060498.38 |
Maximum of Months | 0.163685E+10 | 0.701055E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110934E+09 | 0.519534E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.445741E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350651E+09 |
February | 0.882782E+09 | 0.391927E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295247E+09 |
March | 0.105485E+10 | 0.439211E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93841.08 | 0.311513E+09 |
April | 0.936002E+09 | 0.382439E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14118048.83 | 0.158978E+09 |
May | 0.101394E+10 | 0.407385E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44855868.15 | 90854648.22 |
June | 0.101113E+10 | 0.400852E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73469337.64 | 27735206.46 |
July | 0.938820E+09 | 0.379435E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61043948.25 | 17872629.68 |
August | 0.105485E+10 | 0.426532E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48439065.92 | 26462351.61 |
September | 0.936002E+09 | 0.386248E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14211282.36 | 46555057.99 |
October | 0.973041E+09 | 0.418831E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5141181.53 | 0.148347E+09 |
November | 0.963541E+09 | 0.438660E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288890E+09 |
December | 0.938820E+09 | 0.441680E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307130E+09 |
Annual Sum or Average | 0.116768E+11 | 0.495894E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261373E+09 | 0.207024E+10 |
Minimum of Months | 0.882782E+09 | 0.379435E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17872629.68 |
Maximum of Months | 0.105485E+10 | 0.445741E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73469337.64 | 0.350651E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.669989E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538339E+09 |
February | 0.136988E+10 | 0.595018E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454633E+09 |
March | 0.163688E+10 | 0.678584E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139772.06 | 0.479803E+09 |
April | 0.145246E+10 | 0.593568E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20167362.29 | 0.245633E+09 |
May | 0.157341E+10 | 0.632890E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68263344.21 | 0.132023E+09 |
June | 0.156904E+10 | 0.622902E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111517E+09 | 41453473.85 |
July | 0.145684E+10 | 0.589624E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90935842.40 | 27765091.66 |
August | 0.163688E+10 | 0.662518E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69317279.12 | 43848722.20 |
September | 0.145246E+10 | 0.599873E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20139737.30 | 72598048.99 |
October | 0.150994E+10 | 0.644568E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6471147.67 | 0.235377E+09 |
November | 0.149520E+10 | 0.659592E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450236E+09 |
December | 0.145684E+10 | 0.663760E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475977E+09 |
Annual Sum or Average | 0.181198E+11 | 0.761289E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386952E+09 | 0.319769E+10 |
Minimum of Months | 0.136988E+10 | 0.589624E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27765091.66 |
Maximum of Months | 0.163688E+10 | 0.678584E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111517E+09 | 0.538339E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.436171E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375221E+09 |
February | 0.882782E+09 | 0.385303E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325697E+09 |
March | 0.105485E+10 | 0.437702E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93837.70 | 0.354699E+09 |
April | 0.936002E+09 | 0.380400E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12098512.70 | 0.197789E+09 |
May | 0.101394E+10 | 0.403787E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40550580.73 | 0.107969E+09 |
June | 0.101113E+10 | 0.397282E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65494559.81 | 39783221.57 |
July | 0.938820E+09 | 0.375591E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52884283.03 | 31686049.96 |
August | 0.105485E+10 | 0.424743E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40875616.43 | 42574355.16 |
September | 0.936002E+09 | 0.386325E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13284919.54 | 54940246.87 |
October | 0.973041E+09 | 0.416286E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4381245.41 | 0.171970E+09 |
November | 0.963541E+09 | 0.426364E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326257E+09 |
December | 0.938820E+09 | 0.430965E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350895E+09 |
Annual Sum or Average | 0.116768E+11 | 0.490092E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229664E+09 | 0.237948E+10 |
Minimum of Months | 0.882782E+09 | 0.375591E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31686049.96 |
Maximum of Months | 0.105485E+10 | 0.437702E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65494559.81 | 0.375221E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.698956E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104609E+10 |
February | 0.136985E+10 | 0.610887E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 335790.74 | 0.893767E+09 |
March | 0.163685E+10 | 0.683011E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 404516.60 | 0.938503E+09 |
April | 0.145243E+10 | 0.590584E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58168765.15 | 0.515038E+09 |
May | 0.157338E+10 | 0.627446E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158349E+09 | 0.294179E+09 |
June | 0.156900E+10 | 0.616304E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245870E+09 | 0.107223E+09 |
July | 0.145680E+10 | 0.582250E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203866E+09 | 81671465.22 |
August | 0.163685E+10 | 0.658756E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167091E+09 | 0.107132E+09 |
September | 0.145243E+10 | 0.600727E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53724942.55 | 0.146419E+09 |
October | 0.150991E+10 | 0.653720E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22562615.29 | 0.453570E+09 |
November | 0.149516E+10 | 0.684870E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856946E+09 |
December | 0.145680E+10 | 0.690511E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914368E+09 |
Annual Sum or Average | 0.181194E+11 | 0.769802E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910373E+09 | 0.635490E+10 |
Minimum of Months | 0.136985E+10 | 0.582250E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81671465.22 |
Maximum of Months | 0.163685E+10 | 0.698956E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245870E+09 | 0.104609E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.444904E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735328E+09 |
February | 0.649041E+09 | 0.391120E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636559E+09 |
March | 0.773965E+09 | 0.438632E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135295.16 | 0.685348E+09 |
April | 0.688021E+09 | 0.382135E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30268796.46 | 0.374045E+09 |
May | 0.744847E+09 | 0.407112E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97876243.10 | 0.213098E+09 |
June | 0.742030E+09 | 0.400599E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157046E+09 | 77452172.23 |
July | 0.690839E+09 | 0.379005E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129718E+09 | 60049948.14 |
August | 0.773965E+09 | 0.426122E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103996E+09 | 78521021.49 |
September | 0.688021E+09 | 0.385913E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31307077.62 | 0.110199E+09 |
October | 0.715730E+09 | 0.418340E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11126954.96 | 0.329424E+09 |
November | 0.708685E+09 | 0.437903E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615246E+09 |
December | 0.690839E+09 | 0.441077E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642715E+09 |
Annual Sum or Average | 0.858171E+10 | 0.495286E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561475E+09 | 0.455798E+10 |
Minimum of Months | 0.649041E+09 | 0.379005E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60049948.14 |
Maximum of Months | 0.773965E+09 | 0.444904E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157046E+09 | 0.735328E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.669609E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120651E+10 |
February | 0.136988E+10 | 0.594568E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101769E+10 |
March | 0.163688E+10 | 0.678024E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259754.82 | 0.106935E+10 |
April | 0.145246E+10 | 0.593046E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45983184.71 | 0.555370E+09 |
May | 0.157341E+10 | 0.632439E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154904E+09 | 0.298198E+09 |
June | 0.156904E+10 | 0.622439E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248332E+09 | 0.105278E+09 |
July | 0.145684E+10 | 0.588882E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204384E+09 | 80531985.98 |
August | 0.163688E+10 | 0.661824E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159725E+09 | 0.113893E+09 |
September | 0.145246E+10 | 0.599144E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45439813.98 | 0.169240E+09 |
October | 0.150994E+10 | 0.643294E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14023651.66 | 0.533901E+09 |
November | 0.149520E+10 | 0.659048E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100300E+10 |
December | 0.145684E+10 | 0.663544E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105180E+10 |
Annual Sum or Average | 0.181198E+11 | 0.760586E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873051E+09 | 0.720477E+10 |
Minimum of Months | 0.136988E+10 | 0.588882E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80531985.98 |
Maximum of Months | 0.163688E+10 | 0.678024E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248332E+09 | 0.120651E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.435912E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757231E+09 |
February | 0.882782E+09 | 0.384561E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655343E+09 |
March | 0.105485E+10 | 0.437165E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174262.05 | 0.710519E+09 |
April | 0.936002E+09 | 0.380151E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28187814.24 | 0.398762E+09 |
May | 0.101394E+10 | 0.403611E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93122473.02 | 0.228866E+09 |
June | 0.101113E+10 | 0.397174E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151951E+09 | 88385492.58 |
July | 0.938820E+09 | 0.375218E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123893E+09 | 71259839.81 |
August | 0.105485E+10 | 0.424295E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97954183.72 | 88999550.81 |
September | 0.936002E+09 | 0.385893E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31018552.69 | 0.116762E+09 |
October | 0.973041E+09 | 0.415836E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10284956.33 | 0.350217E+09 |
November | 0.963541E+09 | 0.425850E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635783E+09 |
December | 0.938820E+09 | 0.430514E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662953E+09 |
Annual Sum or Average | 0.116768E+11 | 0.489618E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536585E+09 | 0.476508E+10 |
Minimum of Months | 0.882782E+09 | 0.375218E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71259839.81 |
Maximum of Months | 0.105485E+10 | 0.437165E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151951E+09 | 0.757231E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.698869E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115136E+10 |
February | 0.136985E+10 | 0.610829E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1567604.42 | 0.100480E+10 |
March | 0.163685E+10 | 0.682981E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1255807.74 | 0.106648E+10 |
April | 0.145243E+10 | 0.590573E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66059312.26 | 0.610091E+09 |
May | 0.157338E+10 | 0.627441E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184436E+09 | 0.359821E+09 |
June | 0.156900E+10 | 0.616297E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293264E+09 | 0.138251E+09 |
July | 0.145680E+10 | 0.582237E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238544E+09 | 0.108033E+09 |
August | 0.163685E+10 | 0.658738E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195698E+09 | 0.136239E+09 |
September | 0.145243E+10 | 0.600710E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61371986.58 | 0.180556E+09 |
October | 0.150991E+10 | 0.653679E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26858597.86 | 0.522733E+09 |
November | 0.149516E+10 | 0.684812E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939666E+09 |
December | 0.145680E+10 | 0.690486E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100849E+10 |
Annual Sum or Average | 0.181194E+11 | 0.769765E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106905E+10 | 0.722652E+10 |
Minimum of Months | 0.136985E+10 | 0.582237E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108033E+09 |
Maximum of Months | 0.163685E+10 | 0.698869E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293264E+09 | 0.115136E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.444877E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805755E+09 |
February | 0.882782E+09 | 0.391089E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716924E+09 |
March | 0.105485E+10 | 0.438622E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164789.19 | 0.788051E+09 |
April | 0.936002E+09 | 0.382128E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36369316.57 | 0.449372E+09 |
May | 0.101394E+10 | 0.407097E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117718E+09 | 0.261134E+09 |
June | 0.101113E+10 | 0.400590E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190087E+09 | 99271959.51 |
July | 0.938820E+09 | 0.378982E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155242E+09 | 78508226.67 |
August | 0.105485E+10 | 0.426112E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124592E+09 | 99226494.96 |
September | 0.936002E+09 | 0.385909E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37765152.79 | 0.136317E+09 |
October | 0.973041E+09 | 0.418369E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13441900.84 | 0.384112E+09 |
November | 0.963541E+09 | 0.437937E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680699E+09 |
December | 0.938820E+09 | 0.441031E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703970E+09 |
Annual Sum or Average | 0.116768E+11 | 0.495274E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675380E+09 | 0.520334E+10 |
Minimum of Months | 0.882782E+09 | 0.378982E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78508226.67 |
Maximum of Months | 0.105485E+10 | 0.444877E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190087E+09 | 0.805755E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.669601E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135780E+10 |
February | 0.136988E+10 | 0.594549E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116835E+10 |
March | 0.163688E+10 | 0.678008E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 246135.39 | 0.124550E+10 |
April | 0.145246E+10 | 0.593027E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53994035.64 | 0.664977E+09 |
May | 0.157341E+10 | 0.632430E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181640E+09 | 0.364792E+09 |
June | 0.156904E+10 | 0.622417E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295598E+09 | 0.135895E+09 |
July | 0.145684E+10 | 0.588844E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239347E+09 | 0.106726E+09 |
August | 0.163688E+10 | 0.661778E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188769E+09 | 0.144935E+09 |
September | 0.145246E+10 | 0.599117E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54207459.04 | 0.209508E+09 |
October | 0.150994E+10 | 0.643272E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17106926.92 | 0.631354E+09 |
November | 0.149520E+10 | 0.659039E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113699E+10 |
December | 0.145684E+10 | 0.663537E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118168E+10 |
Annual Sum or Average | 0.181198E+11 | 0.760562E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103091E+10 | 0.834850E+10 |
Minimum of Months | 0.136988E+10 | 0.588844E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106726E+09 |
Maximum of Months | 0.163688E+10 | 0.678008E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295598E+09 | 0.135780E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.435902E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855500E+09 |
February | 0.882782E+09 | 0.384548E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753699E+09 |
March | 0.105485E+10 | 0.437139E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164817.52 | 0.829701E+09 |
April | 0.936002E+09 | 0.380145E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33436610.21 | 0.479369E+09 |
May | 0.101394E+10 | 0.403608E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111111E+09 | 0.280426E+09 |
June | 0.101113E+10 | 0.397172E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183608E+09 | 0.112523E+09 |
July | 0.938820E+09 | 0.375196E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148504E+09 | 91745534.98 |
August | 0.105485E+10 | 0.424283E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117705E+09 | 0.112338E+09 |
September | 0.936002E+09 | 0.385886E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36947075.89 | 0.144342E+09 |
October | 0.973041E+09 | 0.415827E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12280721.03 | 0.415354E+09 |
November | 0.963541E+09 | 0.425842E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721446E+09 |
December | 0.938820E+09 | 0.430483E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749651E+09 |
Annual Sum or Average | 0.116768E+11 | 0.489603E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643757E+09 | 0.554609E+10 |
Minimum of Months | 0.882782E+09 | 0.375196E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91745534.98 |
Maximum of Months | 0.105485E+10 | 0.437139E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183608E+09 | 0.855500E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.209474E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.190008E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.225783E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.201670E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.217628E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.216576E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.202722E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.225783E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.201670E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.209474E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.207019E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.202722E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.251053E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.190008E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.225783E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.209474E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.190008E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.225783E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.201670E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.217628E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.216576E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.202722E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.225783E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.201670E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.209474E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.207019E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.202722E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.251053E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.190008E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.225783E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.209474E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.190008E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.225783E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.201670E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.217628E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.216576E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.202722E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.225783E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.201670E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.209474E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.207019E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.202722E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.251053E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.190008E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.225783E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.281219E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.255087E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.303114E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.270743E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.292167E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.290754E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.272155E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.303114E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.270743E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.281219E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.277923E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.272155E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.337039E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.255087E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.303114E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114178E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962251E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59339.52 | 0.100599E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38752062.72 | 0.528810E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129111E+09 | 0.284913E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208856E+09 | 95001565.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173412E+09 | 67917068.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132670E+09 | 0.101973E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39792842.96 | 0.144735E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14027327.28 | 0.480960E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944299E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101307E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736679E+09 | 0.677171E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67917068.79 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208856E+09 | 0.114178E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192118E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163652E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192386.22 | 0.170990E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77702869.46 | 0.912449E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236161E+09 | 0.499698E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373757E+09 | 0.172173E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316178E+09 | 0.124137E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249604E+09 | 0.177456E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74117073.05 | 0.253356E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27999315.08 | 0.821741E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160025E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168585E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135571E+10 | 0.115147E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124137E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373757E+09 | 0.192118E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185699E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163398E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177796E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56418885.07 | 0.981266E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205073E+09 | 0.535909E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374473E+09 | 0.197544E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294018E+09 | 0.152914E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239034E+09 | 0.201940E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59471368.40 | 0.283374E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23832497.53 | 0.864755E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155817E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160678E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125232E+10 | 0.116516E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152914E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374473E+09 | 0.185699E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10437.26 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10437.26 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10437.26 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10437.26 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10437.26 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10437.26 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10437.26 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10437.26 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10437.26 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10437.26 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10437.26 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10437.26 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10437.26 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10437.26 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9373.40 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9373.40 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9373.40 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9373.40 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9373.40 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9373.40 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9373.40 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9373.40 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9373.40 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9373.40 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9373.40 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9373.40 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9373.40 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9373.40 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9373.40 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9373.40 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9373.40 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9373.40 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9373.40 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9373.40 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9373.40 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9373.40 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9373.40 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9373.40 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9373.40 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9373.40 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9373.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9373.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9373.40 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9373.40 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9373.40 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9373.40 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9373.40 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9373.40 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9373.40 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9373.40 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9373.40 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9373.40 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9373.40 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9373.40 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9373.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9373.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1096.10 | 17-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1384.26 | 25-JAN-23:00 |
February | 2010.79 | 01-FEB-10:09 | 950.41 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1701.50 | 09-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 921.86 | 10-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 22-MAR-13:00 | 1369.75 | 19-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 648.81 | 20-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.61 | 01-APR-17:02 | 1390.00 | 10-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 593.54 | 23-MAY-12:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.51 | 14-MAY-15:34 | 637.36 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 559.98 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.07 | 04-JUN-19:00 | 475.89 | 28-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 644.37 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.88 | 02-JUL-21:08 | 245.80 | 04-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 641.38 | 17-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.63 | 26-AUG-17:01 | 404.37 | 14-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 630.26 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.42 | 10-SEP-14:54 | 241.68 | 24-SEP-07:00 |
October | 2010.79 | 02-OCT-09:09 | 999.54 | 13-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.61 | 01-OCT-15:00 | 632.18 | 24-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1176.92 | 22-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 886.00 | 26-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 1176.92 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1191.75 | 18-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.68 | |||||
Maximum of Months | 2010.79 | 1176.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 476.88 | 1701.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 707.28 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 913.60 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 635.12 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1124.77 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 604.21 | 10-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 22-MAR-13:00 | 923.30 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 403.22 | 20-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.67 | 01-APR-17:02 | 909.89 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 391.19 | 24-MAY-15:39 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.89 | 14-MAY-15:33 | 413.99 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 360.87 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.03 | 04-JUN-19:00 | 311.61 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 406.89 | 03-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.92 | 02-JUL-21:10 | 158.60 | 04-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 411.76 | 16-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.01 | 26-AUG-18:00 | 260.39 | 14-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 360.87 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.33 | 10-SEP-14:54 | 186.33 | 24-SEP-10:10 |
October | 1295.83 | 02-OCT-09:09 | 631.32 | 13-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.12 | 01-OCT-14:52 | 418.19 | 24-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 758.45 | 22-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 666.14 | 26-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 758.45 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 780.70 | 18-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.60 | |||||
Maximum of Months | 1295.83 | 758.45 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 320.92 | 1124.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1090.52 | 17-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1366.06 | 25-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 910.77 | 23-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1714.01 | 09-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 909.56 | 10-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 22-MAR-13:00 | 1401.98 | 19-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 648.71 | 20-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.08 | 21-APR-15:00 | 1383.37 | 10-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 599.41 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.42 | 14-MAY-15:33 | 630.72 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 559.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.75 | 04-JUN-19:00 | 473.52 | 28-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 648.17 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.32 | 02-JUL-21:08 | 235.37 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 644.59 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.73 | 26-AUG-18:00 | 412.95 | 14-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 608.30 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.29 | 10-SEP-14:54 | 273.18 | 24-SEP-10:50 |
October | 2010.83 | 02-OCT-09:09 | 992.38 | 13-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.68 | 01-OCT-15:00 | 649.46 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1176.95 | 22-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 969.12 | 26-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1176.95 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1181.54 | 18-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 559.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.37 | |||||
Maximum of Months | 2010.83 | 1176.95 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 477.32 | 1714.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 700.19 | 17-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 977.07 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 580.19 | 13-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1218.89 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 563.30 | 10-MAR-16:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 22-MAR-13:00 | 1056.86 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 424.85 | 20-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.03 | 21-APR-15:00 | 1036.58 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 402.40 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.40 | 14-MAY-16:00 | 493.71 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 360.87 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.25 | 04-JUN-18:55 | 381.45 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 421.44 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.73 | 02-JUL-21:05 | 250.47 | 04-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 483.88 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.30 | 26-AUG-17:44 | 333.44 | 14-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 410.13 | 28-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.32 | 10-SEP-14:54 | 178.23 | 24-SEP-16:10 |
October | 1295.83 | 02-OCT-09:09 | 647.20 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.79 | 01-OCT-15:00 | 469.57 | 24-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 758.45 | 22-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 667.94 | 26-NOV-16:55 |
December | 1295.83 | 01-DEC-10:09 | 758.45 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 900.65 | 18-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.23 | |||||
Maximum of Months | 1295.83 | 758.45 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 313.73 | 1218.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1095.20 | 17-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2800.75 | 25-JAN-23:00 |
February | 2010.79 | 01-FEB-10:09 | 945.01 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 20-FEB-16:00 | 3506.98 | 09-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 918.92 | 10-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.62 | 19-MAR-14:10 | 2572.27 | 19-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 644.54 | 20-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.91 | 01-APR-17:02 | 2863.13 | 10-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 559.98 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 952.48 | 14-MAY-16:00 | 1300.79 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 559.98 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 907.90 | 04-JUN-19:00 | 1057.97 | 28-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 639.83 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.65 | 02-JUL-21:27 | 521.21 | 18-JUL-21:10 |
August | 2010.79 | 01-AUG-09:09 | 636.68 | 17-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 721.58 | 26-AUG-17:01 | 863.56 | 14-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 624.04 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.27 | 10-SEP-14:51 | 509.50 | 24-SEP-07:00 |
October | 2010.79 | 02-OCT-09:09 | 997.53 | 13-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.17 | 01-OCT-15:00 | 1325.02 | 23-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 1176.92 | 22-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1687.74 | 26-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 1176.92 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2454.41 | 18-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.50 | |||||
Maximum of Months | 2010.79 | 1176.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.65 | 3506.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 705.96 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1879.06 | 25-JAN-23:00 |
February | 1239.33 | 01-FEB-08:09 | 631.84 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2371.88 | 09-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 600.16 | 10-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 22-MAR-13:00 | 1855.75 | 19-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 400.22 | 20-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.56 | 01-APR-17:02 | 1939.35 | 10-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 386.77 | 24-MAY-15:39 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 626.92 | 14-MAY-15:45 | 871.17 | 04-MAY-02:00 |
June | 1239.33 | 01-JUN-07:10 | 360.87 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.18 | 04-JUN-18:57 | 717.18 | 28-JUN-02:00 |
July | 1239.33 | 03-JUL-07:10 | 403.55 | 03-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 707.75 | 02-JUL-21:25 | 363.89 | 04-JUL-19:20 |
August | 1239.33 | 01-AUG-07:10 | 408.70 | 16-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.68 | 26-AUG-17:01 | 605.92 | 14-AUG-00:53 |
September | 1239.33 | 01-SEP-07:10 | 360.87 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.48 | 10-SEP-15:06 | 439.23 | 24-SEP-10:30 |
October | 1239.33 | 02-OCT-07:10 | 628.21 | 13-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.57 | 01-OCT-14:56 | 917.01 | 23-OCT-21:10 |
November | 1239.33 | 01-NOV-07:10 | 758.45 | 22-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1340.60 | 26-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 758.45 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1641.13 | 18-DEC-05:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.89 | |||||
Maximum of Months | 1239.33 | 758.45 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 707.75 | 2371.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1089.62 | 17-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2904.05 | 25-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 907.90 | 23-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3674.30 | 09-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 906.55 | 10-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 | 22-MAR-13:00 | 2919.44 | 19-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 644.43 | 20-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.11 | 21-APR-15:00 | 2926.47 | 10-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 559.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.74 | 14-MAY-16:00 | 1319.03 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 559.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 905.39 | 04-JUN-19:00 | 1048.37 | 28-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 643.82 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1064.69 | 02-JUL-21:27 | 525.54 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 640.07 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 682.53 | 26-AUG-17:01 | 905.45 | 14-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 600.00 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.77 | 10-SEP-15:04 | 603.34 | 24-SEP-10:30 |
October | 2010.83 | 02-OCT-09:09 | 990.33 | 13-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.96 | 01-OCT-15:00 | 1464.24 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1176.95 | 22-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2054.76 | 26-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1176.95 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2476.30 | 18-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 559.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.54 | |||||
Maximum of Months | 2010.83 | 1176.95 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1064.69 | 3674.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 698.78 | 17-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1912.07 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 575.53 | 13-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2427.80 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 558.92 | 10-MAR-16:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 22-MAR-13:00 | 1929.03 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 422.54 | 20-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.45 | 21-APR-15:00 | 1985.55 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 398.82 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.59 | 14-MAY-16:00 | 932.00 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 360.87 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 608.06 | 04-JUN-18:55 | 777.63 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 418.94 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.46 | 02-JUL-21:25 | 453.54 | 04-JUL-19:20 |
August | 1295.83 | 01-AUG-09:09 | 420.49 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.62 | 26-AUG-17:44 | 665.78 | 14-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 407.00 | 28-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.76 | 10-SEP-15:04 | 392.28 | 24-SEP-15:50 |
October | 1295.83 | 02-OCT-09:09 | 644.29 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.24 | 01-OCT-14:54 | 974.31 | 23-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 758.45 | 22-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1215.32 | 26-NOV-16:55 |
December | 1295.83 | 01-DEC-10:09 | 758.45 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1636.28 | 18-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.28 | |||||
Maximum of Months | 1295.83 | 758.45 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 710.46 | 2427.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1095.03 | 17-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3294.20 | 25-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 944.91 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.69 | 20-FEB-16:00 | 3991.25 | 09-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 918.39 | 10-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.44 | 19-MAR-13:53 | 2851.03 | 01-MAR-22:03 |
April | 2010.79 | 03-APR-09:09 | 644.37 | 20-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.60 | 01-APR-17:02 | 3295.97 | 10-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 559.98 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142.50 | 14-MAY-15:45 | 1493.88 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 559.98 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.79 | 04-JUN-18:57 | 1320.78 | 28-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 639.65 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.96 | 02-JUL-21:25 | 707.13 | 04-JUL-18:52 |
August | 2010.79 | 01-AUG-09:09 | 636.50 | 17-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 840.07 | 26-AUG-17:01 | 1139.92 | 14-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 623.93 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.85 | 10-SEP-15:06 | 635.36 | 23-SEP-17:10 |
October | 2010.79 | 02-OCT-09:09 | 997.16 | 13-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.04 | 01-OCT-14:54 | 1579.93 | 23-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1176.92 | 22-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1840.50 | 28-NOV-05:09 |
December | 2010.79 | 01-DEC-10:09 | 1176.92 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3067.09 | 18-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.36 | |||||
Maximum of Months | 2010.79 | 1176.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.96 | 3991.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 705.85 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2196.61 | 25-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 631.62 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2704.14 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 599.83 | 10-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 22-MAR-13:00 | 2018.10 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 400.07 | 20-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.41 | 01-APR-17:02 | 2234.89 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 386.64 | 24-MAY-15:39 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.58 | 14-MAY-15:45 | 999.45 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 360.87 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 745.14 | 04-JUN-18:55 | 895.43 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 403.42 | 03-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 864.94 | 02-JUL-21:25 | 498.70 | 04-JUL-19:30 |
August | 1295.83 | 01-AUG-09:09 | 408.58 | 16-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.20 | 26-AUG-18:00 | 787.66 | 14-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 360.87 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.47 | 10-SEP-15:06 | 535.18 | 24-SEP-10:30 |
October | 1295.83 | 02-OCT-09:09 | 627.95 | 13-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.29 | 01-OCT-14:52 | 1096.96 | 23-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 758.45 | 22-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1379.15 | 26-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 758.45 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2044.75 | 18-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.70 | |||||
Maximum of Months | 1295.83 | 758.45 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 864.94 | 2704.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1089.44 | 17-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3306.55 | 25-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 907.36 | 23-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4193.18 | 09-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 906.00 | 10-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 | 22-MAR-13:00 | 3209.34 | 19-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 644.26 | 20-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.91 | 21-APR-15:00 | 3377.04 | 10-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 559.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.90 | 14-MAY-15:45 | 1516.71 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 559.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.20 | 04-JUN-18:55 | 1308.69 | 28-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 643.64 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298.03 | 02-JUL-21:25 | 675.34 | 04-JUL-19:30 |
August | 2010.83 | 01-AUG-09:09 | 639.89 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 799.96 | 26-AUG-18:00 | 1179.96 | 14-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 599.87 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.86 | 10-SEP-16:25 | 743.40 | 24-SEP-10:50 |
October | 2010.83 | 02-OCT-09:09 | 989.94 | 13-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.72 | 01-OCT-15:00 | 1761.74 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1176.95 | 22-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2143.61 | 26-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1176.95 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3067.11 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 559.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.34 | |||||
Maximum of Months | 2010.83 | 1176.95 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1298.03 | 4193.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 698.66 | 17-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2204.53 | 25-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 575.16 | 13-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2781.25 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 558.55 | 10-MAR-16:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 22-MAR-13:00 | 2143.26 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 422.45 | 20-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.96 | 21-APR-15:00 | 2301.19 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 398.68 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 728.18 | 14-MAY-16:00 | 1080.68 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 360.87 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.52 | 04-JUN-18:55 | 971.44 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 418.84 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 866.75 | 02-JUL-21:25 | 577.98 | 04-JUL-19:30 |
August | 1295.83 | 01-AUG-09:09 | 420.39 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 523.30 | 27-AUG-13:04 | 847.02 | 14-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 406.89 | 28-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.11 | 10-SEP-15:04 | 502.13 | 24-SEP-15:50 |
October | 1295.83 | 02-OCT-09:09 | 644.05 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.48 | 01-OCT-15:00 | 1174.86 | 23-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 758.45 | 22-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1284.08 | 26-NOV-16:55 |
December | 1295.83 | 01-DEC-10:09 | 758.45 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2049.83 | 18-DEC-05:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.13 | |||||
Maximum of Months | 1295.83 | 758.45 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 866.75 | 2781.25 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 219.21 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 219.21 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 219.21 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 219.21 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 219.21 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 219.21 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 219.21 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 219.21 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 219.21 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 219.21 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 219.21 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 219.21 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 219.21 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 219.21 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 219.21 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 219.21 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 219.21 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 219.21 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 219.21 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 219.21 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 219.21 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 219.21 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 219.21 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 219.21 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 219.21 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 219.21 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 219.21 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 219.21 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 219.21 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 219.21 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 219.21 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 219.21 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 219.21 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 219.21 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 219.21 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 219.21 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 219.21 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 219.21 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 219.21 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 219.21 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 219.21 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 219.21 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2942.86 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2942.86 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2942.86 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2942.86 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2942.86 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2942.86 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2942.86 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2942.86 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2942.86 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2942.86 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2942.86 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2942.86 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2942.86 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2942.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3038.97 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3779.56 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 | 22-MAR-13:00 | 3027.07 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.60 | 01-APR-17:02 | 3035.25 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.34 | 14-MAY-16:00 | 1364.09 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.47 | 04-JUN-19:00 | 1005.03 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.13 | 02-JUL-20:52 | 485.44 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.55 | 26-AUG-17:01 | 827.97 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.74 | 10-SEP-15:00 | 509.47 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.64 | 01-OCT-15:00 | 1385.90 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1915.80 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2658.85 | 18-DEC-05:14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.44 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.13 | 3779.56 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5141.92 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6549.29 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.92 | 22-MAR-13:00 | 5005.27 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.30 | 01-APR-17:02 | 5245.37 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.92 | 14-MAY-16:00 | 2347.31 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1497.53 | 04-JUN-19:00 | 1774.04 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1778.05 | 02-JUL-21:00 | 868.08 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1134.08 | 27-AUG-12:52 | 1385.10 | 14-AUG-00:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.89 | 10-SEP-14:51 | 892.81 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.57 | 01-OCT-15:00 | 2404.24 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3207.76 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4267.69 | 18-DEC-05:42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1778.05 | 6549.29 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5123.61 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6531.80 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4651.11 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.00 | 01-APR-17:02 | 5236.18 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.28 | 14-MAY-16:00 | 2339.07 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1380.22 | 10-JUN-17:01 | 2090.55 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1738.92 | 02-JUL-21:10 | 1134.64 | 04-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.68 | 26-AUG-17:01 | 1766.37 | 14-AUG-00:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.53 | 10-SEP-14:51 | 1026.51 | 23-SEP-17:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.09 | 01-OCT-15:00 | 2579.83 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2852.17 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3940.52 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1738.92 | 6531.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96939.03 | 17-JAN-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96301.89 | 21-FEB-05:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93300.28 | 20-MAR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90927.74 | 18-APR-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91464.39 | 08-MAY-04:12 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86043.57 | 12-JUN-04:12 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71251.44 | 10-JUL-03:02 | 0.00 | 2899.16 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80115.62 | 23-AUG-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92795.77 | 25-SEP-05:03 | 7180.90 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96459.45 | 30-OCT-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97008.37 | 06-NOV-05:11 | 0.00 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 97089.11 | 18-DEC-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 71251.44 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97089.11 | 7180.90 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84336.13 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82158.12 | 21-FEB-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79367.02 | 20-MAR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80309.02 | 25-APR-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86302.99 | 22-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79551.22 | 28-JUN-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74260.48 | 05-JUL-04:32 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76636.21 | 14-AUG-04:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87090.82 | 11-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86763.61 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87251.70 | 13-NOV-05:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83234.93 | 18-DEC-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 74260.48 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87251.70 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 65012.09 | 14-JAN-06:02 | 9673.43 | 6248.75 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69086.64 | 23-FEB-06:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70957.03 | 16-MAR-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72241.42 | 21-APR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74035.94 | 17-MAY-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74490.36 | 28-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68359.23 | 05-JUL-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74030.88 | 30-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74142.81 | 06-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73437.13 | 03-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71610.97 | 10-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47319.62 | 14-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 47319.62 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74490.36 | 9673.43 | 6248.75 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23264.40 | 12-JAN-17:00 | 15316.26 | 9373.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27473.23 | 08-FEB-15:00 | 16014.58 | 9373.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65808.69 | 16-MAR-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69778.69 | 28-APR-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75021.70 | 22-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76892.51 | 26-JUN-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73727.50 | 05-JUL-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77211.21 | 14-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75287.83 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72513.89 | 04-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56401.09 | 10-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18635.64 | 01-DEC-17:00 | 15316.26 | 9373.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18635.64 | 0.00 | 2686.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 77211.21 | 16014.58 | 9373.40 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3197.05 | 02-JAN-15:00 | 2010.79 | 596.73 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.27 |
February | 5221.34 | 21-FEB-15:00 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 |
March | 6102.18 | 15-MAR-13:40 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
April | 8376.40 | 21-APR-14:00 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 170.99 | 0.00 |
May | 16381.76 | 21-MAY-15:41 | 809.73 | 248.87 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 283.23 | 0.00 |
June | 16988.54 | 25-JUN-18:01 | 0.00 | 279.98 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 48.34 | 0.00 |
July | 16473.21 | 02-JUL-16:22 | 607.30 | 186.65 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.59 | 0.00 |
August | 16944.35 | 20-AUG-16:21 | 1012.16 | 311.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 219.82 | 0.00 |
September | 15817.01 | 10-SEP-16:11 | 809.73 | 248.87 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 136.46 | 0.00 |
October | 11734.04 | 03-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 |
November | 5171.06 | 08-NOV-14:30 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 |
December | 3611.74 | 11-DEC-12:00 | 1923.11 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3197.05 | 0.00 | 186.65 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16988.54 | 2010.79 | 596.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 283.23 | 165.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5888.30 | 31-JAN-09:05 | 2478.65 | 721.75 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 |
February | 9346.85 | 20-FEB-09:43 | 195.68 | 60.14 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9961.88 | 26-MAR-08:13 | 195.68 | 60.14 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.66 |
April | 17297.54 | 16-APR-09:42 | 326.14 | 100.24 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.64 |
May | 18373.17 | 28-MAY-08:12 | 391.37 | 120.29 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.20 |
June | 18253.90 | 11-JUN-08:51 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 |
July | 17171.61 | 04-JUL-08:22 | 326.14 | 100.24 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 |
August | 18112.16 | 20-AUG-08:22 | 391.37 | 120.29 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 |
September | 18959.27 | 04-SEP-08:11 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.26 |
October | 17452.40 | 01-OCT-08:42 | 326.14 | 100.24 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 |
November | 8994.02 | 10-NOV-08:40 | 1239.33 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.90 |
December | 4816.62 | 07-DEC-09:20 | 1239.33 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4816.62 | 195.68 | 60.14 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18959.27 | 2478.65 | 721.75 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18922.89 | 01-JAN-13:32 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.65 |
February | 20903.42 | 20-FEB-13:42 | 607.31 | 186.66 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.08 |
March | 18984.83 | 26-MAR-13:32 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.48 |
April | 19333.23 | 30-APR-12:43 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
May | 18691.64 | 21-MAY-15:01 | 809.75 | 248.88 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 215.72 | 0.00 |
June | 18571.91 | 11-JUN-16:11 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 257.46 | 0.00 |
July | 18652.22 | 30-JUL-14:22 | 607.31 | 186.66 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 | 0.00 |
August | 19384.69 | 20-AUG-16:21 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 210.87 | 0.00 |
September | 20630.09 | 17-SEP-13:12 | 607.31 | 186.66 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 | 0.00 |
October | 21768.19 | 01-OCT-13:21 | 809.75 | 248.88 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 0.00 |
November | 20701.95 | 05-NOV-13:12 | 607.31 | 186.66 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.33 |
December | 19924.39 | 31-DEC-13:32 | 506.09 | 155.55 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18571.91 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21768.19 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 257.46 | 337.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9436.57 | 22-JAN-16:23 | 195.68 | 60.14 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.17 |
February | 22863.72 | 20-FEB-15:02 | 391.37 | 120.29 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.97 |
March | 22505.85 | 26-MAR-16:12 | 391.37 | 120.29 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.77 |
April | 24631.28 | 16-APR-16:21 | 587.05 | 180.43 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 0.00 |
May | 24852.56 | 07-MAY-15:51 | 521.82 | 160.38 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 0.00 |
June | 26264.72 | 25-JUN-16:41 | 652.28 | 200.48 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 29.05 | 0.00 |
July | 23949.51 | 09-JUL-16:41 | 456.59 | 140.34 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 44.41 | 0.00 |
August | 26742.34 | 20-AUG-16:21 | 652.28 | 200.48 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 63.81 | 0.00 |
September | 25470.39 | 17-SEP-15:51 | 587.05 | 180.43 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.77 | 0.00 |
October | 24101.58 | 22-OCT-14:41 | 456.59 | 140.34 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
November | 22183.94 | 05-NOV-14:32 | 326.14 | 100.24 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.42 |
December | 15776.92 | 31-DEC-14:53 | 260.91 | 80.19 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9436.57 | 195.68 | 60.14 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26742.34 | 652.28 | 200.48 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 63.81 | 330.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2215.34 | 12-JAN-15:40 | 1923.11 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 |
February | 3026.70 | 23-FEB-14:30 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 |
March | 4429.94 | 22-MAR-14:30 | 1923.11 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
April | 7591.79 | 20-APR-05:02 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.82 |
May | 11520.10 | 21-MAY-15:52 | 607.30 | 186.65 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 711.76 | 0.00 |
June | 16236.40 | 11-JUN-16:51 | 1012.16 | 311.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 449.83 | 0.00 |
July | 15499.94 | 02-JUL-18:42 | 0.00 | 212.19 | 3355.02 | 0.00 | 0.00 | 0.00 | 0.00 | 508.76 | 0.00 |
August | 15973.16 | 06-AUG-17:31 | 0.00 | 311.09 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 475.89 | 0.00 |
September | 10006.69 | 19-SEP-13:23 | 8043.16 | 2239.92 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 106.80 | 0.00 |
October | 7763.96 | 05-OCT-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 |
November | 3381.66 | 09-NOV-15:00 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 |
December | 2051.63 | 01-DEC-13:30 | 1923.11 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2051.63 | 0.00 | 186.65 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16236.40 | 8043.16 | 2239.92 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 711.76 | 186.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4412.93 | 12-JAN-11:05 | 2478.65 | 721.75 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
February | 6758.36 | 21-FEB-11:05 | 2478.65 | 721.75 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.25 |
March | 9643.26 | 19-MAR-09:53 | 195.68 | 60.14 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.90 |
April | 19882.07 | 30-APR-09:01 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 |
May | 18222.11 | 29-MAY-08:52 | 326.14 | 100.24 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.23 |
June | 19680.95 | 11-JUN-09:31 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 |
July | 19963.72 | 04-JUL-08:61 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.80 |
August | 19949.36 | 06-AUG-08:11 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 |
September | 19819.72 | 17-SEP-09:21 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.03 |
October | 12969.60 | 22-OCT-10:23 | 260.91 | 80.19 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.44 |
November | 8064.52 | 10-NOV-08:50 | 1239.33 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.61 |
December | 3530.65 | 01-DEC-11:05 | 2478.65 | 721.75 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3530.65 | 195.68 | 60.14 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | |
Maximum of Months | 19963.72 | 2478.65 | 721.75 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18935.90 | 29-JAN-14:13 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.20 |
February | 19109.77 | 20-FEB-13:52 | 506.09 | 155.55 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.52 |
March | 16277.95 | 19-MAR-12:43 | 303.66 | 93.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.84 |
April | 18625.28 | 30-APR-12:23 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 0.00 |
May | 15580.25 | 14-MAY-13:02 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 410.51 | 0.00 |
June | 18104.62 | 11-JUN-16:11 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 582.07 | 0.00 |
July | 18047.95 | 30-JUL-12:02 | 404.87 | 124.44 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 114.70 | 0.00 |
August | 18528.30 | 06-AUG-15:31 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 253.31 | 0.00 |
September | 20365.01 | 17-SEP-12:42 | 607.31 | 186.66 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 91.79 | 0.00 |
October | 21251.81 | 29-OCT-11:41 | 708.53 | 217.77 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.08 |
November | 20557.09 | 11-NOV-14:22 | 607.31 | 186.66 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.22 |
December | 19632.57 | 17-DEC-13:52 | 506.09 | 155.55 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15580.25 | 303.66 | 93.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21251.81 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 582.07 | 1008.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6504.49 | 12-JAN-15:30 | 1239.33 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 |
February | 10893.78 | 20-FEB-15:53 | 260.91 | 80.19 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.34 |
March | 16964.94 | 05-MAR-16:21 | 456.59 | 140.34 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.83 |
April | 22521.38 | 30-APR-17:01 | 0.00 | 180.43 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 | 0.00 |
May | 21056.30 | 29-MAY-16:51 | 456.59 | 140.34 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 298.36 | 0.00 |
June | 22809.86 | 11-JUN-16:51 | 652.28 | 200.48 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 134.27 | 0.00 |
July | 21144.49 | 04-JUL-16:01 | 587.05 | 180.43 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.58 | 0.00 |
August | 22765.56 | 06-AUG-16:51 | 652.28 | 200.48 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 221.82 | 0.00 |
September | 22610.98 | 17-SEP-16:01 | 587.05 | 180.43 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.09 | 0.00 |
October | 19879.61 | 29-OCT-15:42 | 391.37 | 120.29 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.20 |
November | 13961.09 | 11-NOV-15:02 | 391.37 | 120.29 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.02 |
December | 5594.05 | 15-DEC-15:40 | 1239.33 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5594.05 | 0.00 | 80.19 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22809.86 | 1239.33 | 360.87 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 298.36 | 386.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2097.97 | 12-JAN-14:40 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 |
February | 2270.21 | 23-FEB-14:30 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.80 |
March | 4390.22 | 22-MAR-14:30 | 1923.11 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
April | 14263.25 | 30-APR-16:31 | 1012.16 | 311.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 239.50 | 0.00 |
May | 18753.18 | 21-MAY-14:51 | 809.73 | 248.87 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 553.74 | 0.00 |
June | 18417.40 | 25-JUN-17:31 | 0.00 | 217.76 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 221.83 | 0.00 |
July | 18384.99 | 02-JUL-22:03 | 0.00 | 261.53 | 2236.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1135.24 | 0.00 |
August | 18685.28 | 06-AUG-18:11 | 0.00 | 367.45 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 461.44 | 0.00 |
September | 11518.17 | 19-SEP-13:23 | 8043.16 | 2239.92 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 133.50 | 0.00 |
October | 9272.75 | 02-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 |
November | 3306.71 | 09-NOV-15:00 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 |
December | 1561.06 | 07-DEC-14:30 | 2010.79 | 559.98 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1561.06 | 0.00 | 217.76 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18753.18 | 8043.16 | 2239.92 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1135.24 | 146.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2164.30 | 04-JAN-09:50 | 1239.33 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.64 |
February | 4512.20 | 21-FEB-10:30 | 1295.83 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.66 |
March | 6960.77 | 16-MAR-09:50 | 1295.83 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.09 |
April | 19820.56 | 30-APR-08:32 | 391.37 | 120.29 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.68 |
May | 19677.24 | 21-MAY-09:32 | 391.37 | 120.29 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19097.23 | 18-JUN-09:32 | 391.37 | 120.29 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | 0.00 |
July | 20542.70 | 04-JUL-08:11 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 |
August | 20521.98 | 06-AUG-08:11 | 456.59 | 140.34 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 |
September | 18530.17 | 04-SEP-09:02 | 326.14 | 100.24 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.60 |
October | 18280.62 | 01-OCT-09:22 | 326.14 | 100.24 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7123.32 | 10-NOV-09:10 | 1239.33 | 360.87 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.63 |
December | 1202.25 | 07-DEC-14:20 | 2591.66 | 721.75 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1202.25 | 326.14 | 100.24 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20542.70 | 2591.66 | 721.75 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | 303.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16444.42 | 12-JAN-14:20 | 2010.83 | 559.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
February | 20900.35 | 20-FEB-14:32 | 506.09 | 155.55 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.75 |
March | 14160.45 | 16-MAR-13:30 | 2010.83 | 559.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.79 |
April | 20987.84 | 30-APR-16:31 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 183.76 | 0.00 |
May | 21147.47 | 21-MAY-14:51 | 809.75 | 248.88 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 528.06 | 0.00 |
June | 18452.46 | 04-JUN-16:11 | 708.53 | 217.77 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 299.40 | 0.00 |
July | 20119.79 | 04-JUL-16:11 | 910.97 | 279.99 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 325.40 | 0.00 |
August | 21015.48 | 06-AUG-15:31 | 1012.19 | 311.10 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 290.12 | 0.00 |
September | 21502.48 | 17-SEP-13:32 | 506.09 | 155.55 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 240.13 | 0.00 |
October | 24234.48 | 01-OCT-12:41 | 809.75 | 248.88 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 39.61 | 0.00 |
November | 22495.12 | 11-NOV-14:12 | 607.31 | 186.66 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 949.21 |
December | 14011.10 | 07-DEC-14:10 | 4021.67 | 1119.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14011.10 | 506.09 | 155.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24234.48 | 4021.67 | 1119.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 528.06 | 949.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6142.64 | 12-JAN-15:30 | 1239.33 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 |
February | 12200.22 | 19-FEB-16:42 | 391.37 | 120.29 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.34 |
March | 16238.03 | 26-MAR-15:53 | 260.91 | 80.19 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.64 |
April | 24860.69 | 30-APR-16:31 | 652.28 | 200.48 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 0.00 |
May | 23895.00 | 07-MAY-17:11 | 0.00 | 160.38 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
June | 22971.49 | 25-JUN-16:51 | 456.59 | 140.34 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 164.15 | 0.00 |
July | 23349.59 | 04-JUL-16:11 | 587.05 | 180.43 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.61 | 0.00 |
August | 24796.18 | 06-AUG-16:51 | 652.28 | 200.48 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 250.86 | 0.00 |
September | 22262.06 | 17-SEP-15:32 | 391.37 | 120.29 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 180.22 | 0.00 |
October | 22941.32 | 22-OCT-15:31 | 456.59 | 140.34 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 |
November | 9631.89 | 09-NOV-15:30 | 1239.33 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.68 |
December | 4776.95 | 15-DEC-15:50 | 1239.33 | 360.87 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4776.95 | 0.00 | 80.19 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24860.69 | 1239.33 | 360.87 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 250.86 | 362.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5775.34 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.13 |
February | 5707.80 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.50 |
March | 4688.89 | 16-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 |
April | 8155.37 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.02 |
May | 11420.39 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
June | 11826.41 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 |
July | 12017.67 | 03-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 0.00 |
August | 13820.64 | 07-AUG-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
September | 12290.16 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.63 |
October | 10284.54 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 |
November | 7084.66 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.84 |
December | 4887.06 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4688.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13820.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 269.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6068.73 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.27 |
February | 6760.94 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.62 |
March | 5760.84 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.66 |
April | 5158.90 | 21-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.59 | 0.00 |
May | 8322.34 | 30-MAY-16:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.24 | 0.00 |
June | 8901.31 | 05-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 |
July | 10208.20 | 03-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 0.00 |
August | 10840.23 | 22-AUG-16:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.42 | 0.00 |
September | 8347.78 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.42 |
October | 6427.25 | 05-OCT-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.53 | 0.00 |
November | 6040.47 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2496.54 |
December | 5939.99 | 27-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5158.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.59 | 2496.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3487.78 | 12-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.45 |
February | 6369.09 | 22-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9399.10 | 16-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.27 |
April | 18141.95 | 28-APR-13:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.30 | 0.00 |
May | 20576.42 | 30-MAY-12:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.21 | 0.00 |
June | 23821.73 | 27-JUN-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.25 | 0.00 |
July | 23823.11 | 01-JUL-14:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.24 | 0.00 |
August | 21813.93 | 22-AUG-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.22 | 0.00 |
September | 20689.92 | 12-SEP-14:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 0.00 |
October | 16161.95 | 05-OCT-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.80 | 0.00 |
November | 7242.88 | 09-NOV-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.76 |
December | 1369.04 | 17-DEC-14:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1369.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23823.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.80 | 855.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2101.79 | 01-JAN-16:57 | 35.07 | 36.54 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4172.04 | 20-FEB-17:30 | 23.38 | 24.36 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7086.40 | 31-MAR-24:00 | 0.00 | 12.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7803.45 | 22-APR-18:35 | 0.00 | 24.36 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3462.92 | 31-MAY-24:00 | 0.00 | 12.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5340.70 | 30-JUN-23:55 | 0.00 | 24.36 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7300.44 | 31-JUL-24:00 | 0.00 | 24.36 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7799.68 | 13-AUG-23:15 | 0.00 | 24.36 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3463.23 | 30-SEP-24:00 | 0.00 | 12.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5252.57 | 31-OCT-24:00 | 0.00 | 12.18 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6101.96 | 12-NOV-16:35 | 23.38 | 24.36 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7780.09 | 17-DEC-16:47 | 35.07 | 36.54 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2101.79 | 0.00 | 12.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7803.45 | 35.07 | 36.54 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1764.44 | 30-JAN-17:00 | 222.14 | 219.21 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3679.71 | 19-FEB-17:24 | 58.46 | 60.89 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6576.60 | 31-MAR-23:40 | 0.00 | 12.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7415.00 | 22-APR-18:20 | 0.00 | 48.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3379.02 | 31-MAY-24:00 | 0.00 | 12.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5191.27 | 30-JUN-23:55 | 0.00 | 24.36 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7013.57 | 31-JUL-24:00 | 0.00 | 24.36 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7299.59 | 27-AUG-20:52 | 0.00 | 60.89 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3244.44 | 30-SEP-23:50 | 0.00 | 12.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4819.07 | 31-OCT-24:00 | 0.00 | 12.18 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5621.61 | 09-NOV-16:50 | 222.14 | 219.21 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7217.05 | 15-DEC-16:50 | 222.14 | 219.21 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1764.44 | 0.00 | 12.18 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7415.00 | 222.14 | 219.21 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1662.42 | 12-JAN-16:50 | 222.14 | 219.21 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3645.80 | 21-FEB-17:30 | 70.15 | 121.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6283.87 | 31-MAR-23:20 | 0.00 | 12.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7465.14 | 26-APR-18:00 | 23.38 | 73.07 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3411.93 | 31-MAY-24:00 | 0.00 | 12.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5207.32 | 30-JUN-23:55 | 0.00 | 24.36 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7017.38 | 31-JUL-24:00 | 0.00 | 24.36 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7481.68 | 27-AUG-21:03 | 0.00 | 48.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3104.94 | 30-SEP-23:20 | 0.00 | 12.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4499.34 | 31-OCT-23:20 | 0.00 | 12.18 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5647.08 | 09-NOV-16:50 | 222.14 | 219.21 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7106.93 | 15-DEC-16:50 | 222.14 | 219.21 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1662.42 | 0.00 | 12.18 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7481.68 | 222.14 | 219.21 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91226.23 | 02-JAN-17:00 | 4808.68 | 2942.86 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181834.91 | 21-FEB-17:00 | 4808.68 | 2942.86 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 356817.90 | 31-MAR-24:00 | 0.00 | 163.49 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371632.40 | 16-APR-19:32 | 0.00 | 817.44 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 174911.65 | 31-MAY-24:00 | 0.00 | 163.49 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266484.58 | 30-JUN-24:00 | 0.00 | 326.98 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 354742.89 | 31-JUL-23:20 | 0.00 | 326.98 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377781.33 | 27-AUG-20:52 | 0.00 | 817.44 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176597.60 | 30-SEP-24:00 | 0.00 | 163.49 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268251.11 | 31-OCT-24:00 | 0.00 | 163.49 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275615.59 | 13-NOV-17:00 | 4808.68 | 2942.86 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366539.31 | 18-DEC-17:00 | 4808.68 | 2942.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91226.23 | 0.00 | 163.49 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 377781.33 | 4808.68 | 2942.86 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.146043E+13 | 969536.37 | 12-JAN-16:10 | 0.159093E+12 | 669878.79 | 27-JAN-07:10 |
February | 0.171528E+13 | 1187264.10 | 21-FEB-16:30 | 0.115118E+12 | 700425.58 | 03-FEB-07:10 |
March | 0.234583E+13 | 1424006.57 | 21-MAR-15:00 | 0.958801E+11 | 540444.47 | 02-MAR-07:10 |
April | 0.283414E+13 | 1742448.25 | 21-APR-15:20 | 0.603275E+11 | 175993.18 | 12-APR-06:19 |
May | 0.182620E+13 | 1307368.06 | 30-MAY-15:09 | 0.577989E+11 | 73074.49 | 08-MAY-11:39 |
June | 0.225525E+13 | 1482904.00 | 27-JUN-14:20 | 0.538874E+11 | 69987.34 | 01-JUN-11:00 |
July | 0.274641E+13 | 1686334.46 | 21-JUL-10:20 | 0.513068E+11 | 66577.49 | 03-JUL-11:30 |
August | 0.314966E+13 | 1821904.85 | 23-AUG-15:20 | 0.542379E+11 | 66531.92 | 28-AUG-11:39 |
September | 0.167775E+13 | 1328808.95 | 12-SEP-14:30 | 0.520970E+11 | 69821.59 | 28-SEP-11:30 |
October | 0.196041E+13 | 1366265.59 | 03-OCT-10:39 | 0.574674E+11 | 231011.05 | 24-OCT-09:00 |
November | 0.219977E+13 | 1363278.76 | 09-NOV-16:49 | 0.925686E+11 | 431999.93 | 28-NOV-07:10 |
December | 0.254458E+13 | 1387240.04 | 08-DEC-16:00 | 0.187781E+12 | 733426.38 | 27-DEC-07:10 |
Annual Sum or Average | 0.267157E+14 | 0.103756E+13 | ||||
Minimum of Months | 0.146043E+13 | 969536.37 | 0.513068E+11 | 66531.92 | ||
Maximum of Months | 0.314966E+13 | 1821904.85 | 0.187781E+12 | 733426.38 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.337311E+11 | 64526.68 | 27-JAN-12:30 | 0.00 | 0.00 |
February | 0.382416E+11 | 75776.68 | 24-FEB-11:39 | 0.00 | 0.00 |
March | 0.568903E+11 | 88783.39 | 29-MAR-12:20 | 0.00 | 0.00 |
April | 0.655244E+11 | 89495.83 | 22-APR-11:00 | 0.00 | 0.00 |
May | 0.725623E+11 | 89495.83 | 05-MAY-11:30 | 0.00 | 0.00 |
June | 0.719362E+11 | 86875.10 | 10-JUN-11:00 | 0.00 | 0.00 |
July | 0.648419E+11 | 83244.12 | 22-JUL-11:00 | 0.00 | 0.00 |
August | 0.608177E+11 | 81652.58 | 09-AUG-12:30 | 0.00 | 0.00 |
September | 0.549201E+11 | 81923.04 | 09-SEP-12:30 | 0.00 | 0.00 |
October | 0.449422E+11 | 74099.16 | 05-OCT-11:30 | 0.00 | 0.00 |
November | 0.360176E+11 | 65760.13 | 05-NOV-11:39 | 0.00 | 0.00 |
December | 0.317493E+11 | 57287.34 | 29-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632175E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.317493E+11 | 57287.34 | 0.00 | 0.00 | |
Maximum of Months | 0.725623E+11 | 89495.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.149282E+12 | 0.284649E+11 | 0.766053E+12 | 0.102196E+12 | 0.176101E+12 | 0.223581E+11 | 0.00 | 0.246830E+11 | 0.564058E+10 | 0.185655E+12 | 0.00 | 0.00 | 0.00 |
February | 0.134701E+12 | 0.234177E+11 | 0.978954E+12 | 0.923127E+11 | 0.164321E+12 | 0.224806E+11 | 0.00 | 0.529746E+11 | 0.211471E+11 | 0.224969E+12 | 0.00 | 0.00 | 0.00 |
March | 0.158643E+12 | 0.227464E+11 | 0.141687E+13 | 0.102364E+12 | 0.195587E+12 | 0.282033E+11 | 0.00 | 0.117735E+12 | 0.430136E+11 | 0.260668E+12 | 0.00 | 0.00 | 0.00 |
April | 0.141088E+12 | 0.190474E+11 | 0.165903E+13 | 0.988837E+11 | 0.213111E+12 | 0.406726E+11 | 0.00 | 0.321781E+12 | 0.928417E+11 | 0.247692E+12 | 0.00 | 0.00 | 0.00 |
May | 0.151891E+12 | 0.171908E+11 | 0.774844E+12 | 0.102280E+12 | 0.251694E+12 | 0.481447E+11 | 0.00 | 0.233866E+12 | 0.110239E+12 | 0.136048E+12 | 0.00 | 0.00 | 0.00 |
June | 0.150865E+12 | 0.154797E+11 | 0.106252E+13 | 0.990410E+11 | 0.284427E+12 | 0.606665E+11 | 0.00 | 0.410414E+12 | 0.130288E+12 | 0.415508E+11 | 0.00 | 0.00 | 0.00 |
July | 0.141459E+12 | 0.166200E+11 | 0.139340E+13 | 0.102122E+12 | 0.267624E+12 | 0.668448E+11 | 0.00 | 0.596343E+12 | 0.156335E+12 | 0.566210E+10 | 0.00 | 0.00 | 0.00 |
August | 0.157853E+12 | 0.186595E+11 | 0.173200E+13 | 0.102364E+12 | 0.281024E+12 | 0.633468E+11 | 0.00 | 0.603975E+12 | 0.144326E+12 | 0.461146E+11 | 0.00 | 0.00 | 0.00 |
September | 0.141398E+12 | 0.205862E+11 | 0.740713E+12 | 0.988829E+11 | 0.239603E+12 | 0.489264E+11 | 0.00 | 0.238457E+12 | 0.118482E+12 | 0.306958E+11 | 0.00 | 0.00 | 0.00 |
October | 0.147864E+12 | 0.245850E+11 | 0.108340E+13 | 0.102196E+12 | 0.211948E+12 | 0.369930E+11 | 0.00 | 0.171513E+12 | 0.756647E+11 | 0.106248E+12 | 0.00 | 0.00 | 0.00 |
November | 0.147343E+12 | 0.266519E+11 | 0.135889E+13 | 0.989476E+11 | 0.181143E+12 | 0.252688E+11 | 0.00 | 0.934762E+11 | 0.330854E+11 | 0.234962E+12 | 0.00 | 0.00 | 0.00 |
December | 0.145063E+12 | 0.291737E+11 | 0.170972E+13 | 0.102122E+12 | 0.176737E+12 | 0.236210E+11 | 0.00 | 0.714683E+11 | 0.191224E+11 | 0.267556E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176745E+13 | 0.262623E+12 | 0.146764E+14 | 0.120371E+13 | 0.264332E+13 | 0.487527E+12 | 0.00 | 0.293669E+13 | 0.950185E+12 | 0.178782E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134701E+12 | 0.154797E+11 | 0.740713E+12 | 0.923127E+11 | 0.164321E+12 | 0.223581E+11 | 0.00 | 0.246830E+11 | 0.564058E+10 | 0.566210E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158643E+12 | 0.291737E+11 | 0.173200E+13 | 0.102364E+12 | 0.284427E+12 | 0.668448E+11 | 0.00 | 0.603975E+12 | 0.156335E+12 | 0.267556E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.949597E+11 | 0.00 | 0.641328E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.569753E+11 | 0.00 | 0.581423E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.304921E+11 | 0.00 | 0.653880E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245591E+10 | 0.00 | 0.578715E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 4560281.28 | 0.00 | 0.577944E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.538874E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.513068E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.542379E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 16183646.76 | 0.00 | 0.520808E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.906565E+09 | 0.00 | 0.565608E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.342135E+11 | 0.00 | 0.583552E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.126238E+12 | 0.00 | 0.615429E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.346261E+12 | 0.00 | 0.691301E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.513068E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.126238E+12 | 0.00 | 0.653880E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 171569.92 | 17-JAN-16:00 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73693.77 | 09-JAN-08:20 | 114031.17 | 12-JAN-16:19 | 23633.79 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 164645.13 | 23-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73696.89 | 13-FEB-08:20 | 140417.07 | 21-FEB-16:40 | 22167.52 | 02-FEB-10:20 | 0.00 | 01-FEB-00:10 |
March | 164318.52 | 10-MAR-16:00 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73694.95 | 22-MAR-07:19 | 168311.01 | 16-MAR-15:50 | 21856.88 | 01-MAR-08:39 | 0.00 | 01-MAR-00:10 |
April | 153845.38 | 20-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73692.31 | 20-APR-07:19 | 218888.47 | 27-APR-15:30 | 46685.59 | 27-APR-15:09 | 0.00 | 01-APR-00:10 |
May | 151090.15 | 03-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73690.86 | 03-MAY-07:19 | 300724.56 | 08-MAY-14:39 | 46938.65 | 30-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 150591.97 | 01-JUN-07:10 | 22480.63 | 01-JUN-19:10 | 541788.89 | 01-JUN-07:10 | 73690.60 | 01-JUN-07:19 | 300724.56 | 05-JUN-14:09 | 46937.25 | 06-JUN-10:30 | 0.00 | 01-JUN-00:10 |
July | 153754.78 | 07-JUL-07:30 | 31088.59 | 06-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 73692.26 | 07-JUL-07:40 | 300724.56 | 03-JUL-17:19 | 46965.99 | 18-JUL-07:10 | 0.00 | 01-JUL-00:10 |
August | 153539.67 | 17-AUG-07:30 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73692.15 | 17-AUG-07:40 | 300724.56 | 07-AUG-07:49 | 46919.90 | 22-AUG-09:30 | 0.00 | 01-AUG-00:10 |
September | 152241.18 | 18-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73691.47 | 18-SEP-07:19 | 300724.56 | 01-SEP-16:40 | 46977.00 | 12-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 167624.49 | 13-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73699.54 | 13-OCT-07:19 | 300724.56 | 05-OCT-16:30 | 46605.81 | 03-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 174940.73 | 22-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73699.11 | 01-NOV-07:19 | 150057.81 | 09-NOV-16:49 | 29416.80 | 03-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 174940.73 | 01-DEC-16:00 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73692.52 | 13-DEC-08:20 | 113355.57 | 15-DEC-15:39 | 24314.35 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 150591.97 | 22480.63 | 423497.50 | 73690.60 | 113355.57 | 21856.88 | 0.00 | |||||||
Maximum of Months | 174940.73 | 31088.59 | 778371.69 | 73699.54 | 300724.56 | 46977.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 80594.74 | 12-JAN-15:09 | 44337.07 | 12-JAN-15:39 | 100000.00 | 01-JAN-01:49 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 143671.61 | 21-FEB-15:09 | 44395.94 | 21-FEB-14:00 | 100000.00 | 01-FEB-05:40 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 244969.37 | 21-MAR-15:00 | 45427.43 | 14-MAR-15:00 | 100000.00 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 340306.16 | 21-APR-15:09 | 74196.48 | 21-APR-13:50 | 100000.00 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 292869.14 | 19-MAY-10:00 | 74196.48 | 19-MAY-11:00 | 100000.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 347890.00 | 09-JUN-12:39 | 74196.48 | 06-JUN-16:10 | 100000.00 | 01-JUN-04:19 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 445801.43 | 21-JUL-09:00 | 74196.48 | 01-JUL-14:00 | 41086.30 | 22-JUL-19:00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 416180.35 | 02-AUG-08:20 | 74196.48 | 02-AUG-08:30 | 100000.00 | 05-AUG-19:10 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 312420.43 | 12-SEP-14:30 | 74196.48 | 06-SEP-08:00 | 100000.00 | 17-SEP-18:00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 302197.55 | 03-OCT-14:09 | 74196.48 | 02-OCT-10:20 | 100000.00 | 09-OCT-14:50 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 209064.19 | 03-NOV-15:00 | 46183.59 | 03-NOV-15:00 | 100000.00 | 05-NOV-06:49 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 116754.05 | 20-DEC-14:00 | 43943.37 | 07-DEC-15:09 | 100000.00 | 01-DEC-05:19 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 80594.74 | 43943.37 | 41086.30 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 445801.43 | 74196.48 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 969536.37 | 12-JAN-16:10 | 151693.83 | 423497.50 | 0.00 | 52592.47 | 111475.49 | 20437.29 | 0.00 | 71519.26 | 44065.71 |
February | 1187264.10 | 21-FEB-16:30 | 150591.97 | 541788.89 | 0.00 | 52592.02 | 139990.05 | 20671.43 | 0.00 | 137352.20 | 44277.54 |
March | 1424006.57 | 21-MAR-15:00 | 150591.97 | 660080.29 | 0.00 | 52592.02 | 148976.28 | 21485.99 | 0.00 | 244969.37 | 45310.65 |
April | 1742448.25 | 21-APR-15:20 | 150591.97 | 778371.69 | 0.00 | 52592.02 | 212238.62 | 39004.98 | 0.00 | 335452.49 | 74196.48 |
May | 1307368.06 | 30-MAY-15:09 | 150591.97 | 423497.50 | 0.00 | 52592.02 | 300724.56 | 46909.02 | 0.00 | 258856.52 | 74196.48 |
June | 1482904.00 | 27-JUN-14:20 | 150591.97 | 541788.89 | 0.00 | 24460.58 | 297638.42 | 46867.34 | 0.00 | 345669.20 | 74196.48 |
July | 1686334.46 | 21-JUL-10:20 | 150591.97 | 660080.29 | 0.00 | 24460.58 | 297528.75 | 46756.85 | 0.00 | 432719.54 | 74196.48 |
August | 1821904.85 | 23-AUG-15:20 | 150591.97 | 778371.69 | 0.00 | 52592.02 | 287800.97 | 46910.26 | 0.00 | 357946.76 | 47691.18 |
September | 1328808.95 | 12-SEP-14:30 | 150591.97 | 423497.50 | 0.00 | 24460.58 | 296601.67 | 46977.00 | 0.00 | 312420.43 | 74196.48 |
October | 1366265.59 | 03-OCT-10:39 | 150591.97 | 541788.89 | 0.00 | 24460.58 | 299357.57 | 38624.31 | 0.00 | 244850.85 | 66591.42 |
November | 1363278.76 | 09-NOV-16:49 | 163820.01 | 660080.29 | 0.00 | 52596.47 | 150057.81 | 20765.19 | 0.00 | 181164.62 | 45574.59 |
December | 1387240.04 | 08-DEC-16:00 | 174940.73 | 778371.69 | 31088.59 | 52604.38 | 89534.05 | 20276.52 | 0.00 | 96574.57 | 43849.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 969536.37 | 150591.97 | 423497.50 | 0.00 | 24460.58 | 89534.05 | 20276.52 | 0.00 | 71519.26 | 43849.51 | |
Maximum of Months | 1821904.85 | 174940.73 | 778371.69 | 31088.59 | 52604.38 | 300724.56 | 46977.00 | 0.00 | 432719.54 | 74196.48 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 639392.60 | 27-JAN-07:10 | 0.00 | 80096.15 | 27-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 669825.13 | 03-FEB-07:10 | 0.00 | 80091.19 | 02-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 509933.09 | 02-MAR-07:10 | 0.00 | 79364.24 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 167434.64 | 12-APR-06:10 | 0.00 | 77042.26 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 2720.48 | 02-MAY-06:10 | 0.00 | 73074.49 | 08-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 69987.34 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 66577.49 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 66531.92 | 28-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 17160.21 | 30-SEP-06:10 | 0.00 | 69821.59 | 28-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 195779.19 | 24-OCT-09:00 | 0.00 | 73539.05 | 27-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 402994.05 | 27-NOV-05:19 | 0.00 | 77177.68 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 702923.44 | 27-DEC-07:10 | 0.00 | 79306.00 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 66531.92 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 702923.44 | 0.00 | 80096.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.95 | 0.83 | 27.02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.29 | 0.00 | 26.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.74 | 0.00 | 25.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.80 | 0.00 | 25.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.93 | 0.17 | 25.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.88 | 4.17 | 24.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.22 | 2.00 | 25.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 25.46 | 7.50 | 25.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 26.25 | 5.67 | 25.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.91 | 1.17 | 26.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.06 | 0.67 | 27.09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.05 | 1.50 | 27.10 |
Annual Sum or Average | 0.00 | 0.00 | 83.17 | 26.28 | 23.67 | 26.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.88 | 0.00 | 24.81 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.06 | 7.50 | 27.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.72 | 2.67 | 24.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 24.85 | 12.83 | 24.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.26 | 0.83 | 25.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 25.15 | 15.17 | 25.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.02 | 4.17 | 25.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.64 | 0.00 | 25.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.17 | 25.03 | 35.67 | 24.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 25.64 | 15.17 | 25.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.64 | 1.83 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.76 | 9.33 | 24.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.99 | 5.00 | 24.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.89 | 3.33 | 24.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.50 | 24.83 | 19.50 | 24.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.99 | 9.33 | 24.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.75 | 2.00 | 24.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 24.88 | 17.83 | 24.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 25.17 | 6.83 | 25.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.01 | 3.67 | 25.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
December | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
Annual Sum or Average | 0.50 | 18.85 | 0.00 | 18.85 | 30.50 | 24.85 | 30.33 | 24.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.33 | 0.00 | 19.33 | 17.83 | 25.17 | 17.83 | 25.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.74 | 2.33 | 24.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 25.20 | 24.50 | 25.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.19 | 10.33 | 26.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 25.76 | 20.83 | 25.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.06 | 3.83 | 25.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.67 | 25.56 | 61.83 | 25.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 26.19 | 24.50 | 26.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.61 | 1.83 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.80 | 6.17 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.24 | 15.50 | 27.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 26.19 | 33.67 | 26.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.36 | 17.83 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 26.19 | 27.00 | 26.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 26.43 | 18.00 | 26.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.52 | 4.33 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 132.17 | 26.69 | 126.00 | 26.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.80 | 33.67 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.74 | 3.83 | 27.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.84 | 6.00 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.55 | 4.00 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.40 | 6.33 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.08 | 10.00 | 26.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 25.35 | 19.33 | 25.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.82 | 11.50 | 26.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 25.92 | 33.67 | 25.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 26.54 | 23.67 | 26.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 25.92 | 35.67 | 25.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 26.38 | 16.33 | 26.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.76 | 3.50 | 27.76 |
Annual Sum or Average | 0.00 | 0.00 | 183.33 | 26.28 | 173.83 | 26.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.35 | 3.50 | 25.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 27.84 | 35.67 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.51 | 1.50 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.05 | 4.00 | 28.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.24 | 4.33 | 28.25 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.52 | 14.17 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.30 | 10.67 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 | 26.77 | 24.50 | 26.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 27.43 | 27.50 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 | 27.20 | 45.50 | 27.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.10 | 11.00 | 27.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.32 | 9.50 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.05 | 4.83 | 28.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.70 | 3.00 | 27.70 |
Annual Sum or Average | 0.00 | 0.00 | 302.00 | 27.28 | 160.50 | 27.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.77 | 1.50 | 26.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 | 28.24 | 45.50 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.11 | 2.00 | 25.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 25.25 | 21.50 | 25.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.44 | 5.17 | 26.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25.60 | 6.83 | 25.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.91 | 3.33 | 24.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
December | 1.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 3.50 | 19.30 | 0.00 | 19.30 | 43.33 | 25.04 | 38.83 | 25.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.41 | 0.00 | 19.41 | 22.67 | 26.44 | 21.50 | 26.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.33 | 19.35 | 0.00 | 19.35 | 0.33 | 23.31 | 0.33 | 24.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 1.00 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.81 | 7.17 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.46 | 13.67 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 26.56 | 22.50 | 26.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.70 | 17.50 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 26.72 | 17.83 | 26.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.99 | 13.33 | 27.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.59 | 3.83 | 27.59 |
November | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 1.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 2.67 | 19.30 | 0.00 | 19.30 | 114.00 | 26.92 | 97.17 | 27.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 0.00 | 19.22 |
Maximum of Months | 1.50 | 19.35 | 0.00 | 19.35 | 30.67 | 27.81 | 22.50 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.88 | 5.33 | 26.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.96 | 5.83 | 27.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.49 | 3.83 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.53 | 4.33 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.17 | 8.17 | 26.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 25.35 | 18.50 | 25.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.11 | 8.17 | 27.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 26.37 | 18.17 | 26.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 26.52 | 24.17 | 26.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 25.72 | 41.50 | 25.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 25.97 | 23.67 | 25.97 |
December | 0.33 | 19.34 | 0.00 | 19.34 | 3.00 | 26.97 | 3.00 | 27.37 |
Annual Sum or Average | 0.33 | 19.34 | 0.00 | 19.34 | 169.67 | 26.24 | 164.67 | 26.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.35 | 3.00 | 25.35 |
Maximum of Months | 0.33 | 19.34 | 0.00 | 19.34 | 42.17 | 27.96 | 41.50 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.75 | 1.50 | 27.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.92 | 1.67 | 27.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.25 | 4.83 | 28.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.61 | 8.00 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 26.66 | 17.17 | 26.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.31 | 13.17 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 26.91 | 17.67 | 26.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.32 | 8.50 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.10 | 6.83 | 27.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.46 | 1.33 | 27.46 |
December | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 0.50 | 19.40 | 0.00 | 19.40 | 123.50 | 27.15 | 80.67 | 27.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | 0.00 | 19.38 |
Maximum of Months | 0.33 | 19.44 | 0.00 | 19.44 | 27.17 | 28.25 | 17.67 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 18.56 | 0.33 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
February | 4.33 | 18.58 | 0.17 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
March | 1.50 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
April | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.05 | 4.67 | 27.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 25.71 | 23.83 | 25.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 26.84 | 13.33 | 26.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.41 | 10.67 | 26.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.36 | 3.83 | 25.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.83 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
December | 9.17 | 18.28 | 1.17 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
Annual Sum or Average | 24.83 | 18.49 | 1.67 | 18.54 | 68.00 | 24.09 | 56.33 | 24.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 19.40 | 1.17 | 19.40 | 26.83 | 27.05 | 23.83 | 27.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
February | 3.83 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
March | 1.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.72 | 7.00 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.51 | 16.00 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 26.49 | 32.33 | 26.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.76 | 18.17 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 26.89 | 19.33 | 26.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.07 | 14.17 | 27.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.49 | 3.00 | 27.49 |
November | 2.50 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
December | 7.00 | 18.20 | 0.17 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
Annual Sum or Average | 19.83 | 18.48 | 0.17 | 18.45 | 128.67 | 25.95 | 110.00 | 26.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 0.00 | 18.13 |
Maximum of Months | 7.00 | 18.97 | 0.17 | 18.97 | 36.67 | 27.76 | 32.33 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.98 | 0.00 | 18.98 | 0.50 | 19.88 | 0.50 | 20.60 |
February | 2.50 | 18.93 | 0.00 | 18.93 | 4.17 | 24.43 | 4.17 | 25.70 |
March | 0.50 | 18.79 | 0.00 | 18.79 | 1.33 | 25.01 | 1.33 | 26.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.41 | 5.00 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.47 | 9.67 | 26.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 25.81 | 20.33 | 25.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.27 | 11.50 | 27.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 26.51 | 18.83 | 26.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 26.74 | 20.50 | 26.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 26.23 | 20.83 | 26.21 |
November | 1.33 | 18.45 | 0.00 | 18.45 | 7.00 | 25.88 | 7.00 | 26.53 |
December | 5.33 | 18.54 | 0.00 | 18.54 | 0.33 | 19.07 | 0.33 | 19.53 |
Annual Sum or Average | 13.83 | 18.74 | 0.00 | 18.74 | 134.67 | 25.87 | 120.00 | 26.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 19.07 | 0.33 | 19.53 |
Maximum of Months | 5.33 | 18.98 | 0.00 | 18.98 | 22.67 | 27.41 | 20.83 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 2.33 | 18.91 | 0.00 | 18.91 | 1.17 | 21.82 | 1.17 | 23.27 |
March | 0.50 | 18.86 | 0.00 | 18.86 | 1.67 | 25.73 | 1.33 | 26.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.00 | 5.67 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.34 | 11.17 | 27.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 26.61 | 22.17 | 26.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 27.50 | 16.50 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 26.95 | 21.50 | 26.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.41 | 9.17 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.16 | 5.83 | 27.17 |
November | 0.67 | 18.52 | 0.00 | 18.52 | 0.17 | 20.30 | 0.17 | 21.48 |
December | 4.67 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
Annual Sum or Average | 11.83 | 18.78 | 0.00 | 18.78 | 144.67 | 26.53 | 94.67 | 26.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 0.00 | 18.66 |
Maximum of Months | 4.67 | 18.91 | 0.00 | 18.91 | 33.17 | 28.00 | 22.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 | 28.18 | 57.50 | 28.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 192.33 | 28.23 | 162.50 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 272.17 | 28.22 | 220.00 | 28.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 192.33 | 28.23 | 162.50 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 63.33 | 28.06 | 44.67 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 144.50 | 28.08 | 126.17 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 207.83 | 28.08 | 170.83 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 144.50 | 28.08 | 126.17 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 28.12 | 27.33 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 118.50 | 28.16 | 99.00 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 161.33 | 28.15 | 126.33 | 28.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 118.50 | 28.16 | 99.00 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 137.50 | 29.41 | 124.83 | 29.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 119.50 | 28.69 | 101.00 | 28.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 588.83 | 30.31 | 444.83 | 30.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 845.83 | 29.94 | 670.67 | 30.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 588.83 | 30.31 | 444.83 | 30.41 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 223.00 | 24.00 | 82.00 | 24.59 | 0.00 | 24.59 |
February | 254.83 | 24.00 | 62.00 | 24.36 | 0.00 | 24.36 |
March | 342.00 | 24.00 | 50.33 | 24.26 | 0.00 | 24.26 |
April | 165.33 | 24.00 | 77.33 | 24.69 | 0.00 | 24.69 |
May | 64.00 | 24.00 | 191.17 | 24.83 | 14.00 | 24.79 |
June | 50.83 | 24.40 | 283.50 | 24.68 | 33.00 | 24.68 |
July | 226.50 | 24.50 | 491.50 | 24.58 | 226.50 | 24.56 |
August | 97.50 | 24.31 | 496.17 | 24.50 | 97.50 | 24.47 |
September | 144.67 | 24.88 | 433.00 | 24.71 | 144.67 | 24.74 |
October | 41.83 | 24.52 | 294.33 | 24.96 | 35.33 | 24.92 |
November | 69.50 | 24.00 | 136.67 | 25.27 | 0.00 | 25.27 |
December | 191.67 | 24.00 | 87.83 | 24.78 | 0.00 | 24.78 |
Annual Sum or Average | 1871.67 | 24.17 | 2685.83 | 24.64 | 551.00 | 24.63 |
Minimum of Months | 41.83 | 24.00 | 50.33 | 24.26 | 0.00 | 24.26 |
Maximum of Months | 342.00 | 24.88 | 496.17 | 25.27 | 226.50 | 25.27 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 231.67 | 23.99 | 49.67 | 24.25 | 0.00 | 24.25 |
February | 212.17 | 24.00 | 23.50 | 24.09 | 0.00 | 24.09 |
March | 213.17 | 24.00 | 30.00 | 24.22 | 0.00 | 24.22 |
April | 100.17 | 24.00 | 70.50 | 24.39 | 0.00 | 24.39 |
May | 30.67 | 24.00 | 184.83 | 24.54 | 1.50 | 24.54 |
June | 9.50 | 24.00 | 309.33 | 24.32 | 4.33 | 24.31 |
July | 65.67 | 24.36 | 495.00 | 24.27 | 65.67 | 24.28 |
August | 28.33 | 24.18 | 504.17 | 24.28 | 28.33 | 24.27 |
September | 54.17 | 24.85 | 423.83 | 24.45 | 54.17 | 24.50 |
October | 22.83 | 24.71 | 290.17 | 24.63 | 17.00 | 24.65 |
November | 77.33 | 24.00 | 117.50 | 24.72 | 0.00 | 24.72 |
December | 161.17 | 24.01 | 56.50 | 24.51 | 0.00 | 24.51 |
Annual Sum or Average | 1206.83 | 24.08 | 2555.00 | 24.37 | 171.00 | 24.38 |
Minimum of Months | 9.50 | 23.99 | 23.50 | 24.09 | 0.00 | 24.09 |
Maximum of Months | 231.67 | 24.85 | 504.17 | 24.72 | 65.67 | 24.72 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.00 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
February | 394.83 | 23.77 | 4.67 | 23.78 | 0.00 | 23.78 |
March | 451.33 | 23.89 | 1.67 | 23.90 | 0.00 | 23.90 |
April | 228.33 | 23.98 | 21.17 | 24.07 | 0.00 | 24.07 |
May | 71.67 | 23.99 | 153.83 | 24.31 | 2.17 | 24.31 |
June | 26.50 | 24.08 | 282.17 | 24.29 | 8.33 | 24.29 |
July | 92.50 | 24.28 | 491.33 | 24.23 | 92.50 | 24.24 |
August | 72.50 | 24.24 | 472.83 | 24.22 | 72.50 | 24.22 |
September | 73.83 | 24.42 | 398.00 | 24.32 | 67.33 | 24.34 |
October | 74.00 | 24.05 | 217.83 | 24.26 | 26.00 | 24.27 |
November | 320.00 | 23.85 | 30.83 | 23.90 | 0.00 | 23.90 |
December | 487.50 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
Annual Sum or Average | 2779.00 | 23.84 | 2074.33 | 24.03 | 268.83 | 24.04 |
Minimum of Months | 26.50 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
Maximum of Months | 487.50 | 24.42 | 491.33 | 24.32 | 92.50 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.00 | 22.10 | 95.83 | 21.84 | 95.83 | 21.65 |
February | 451.50 | 22.66 | 34.00 | 22.55 | 34.00 | 22.44 |
March | 509.50 | 23.31 | 2.17 | 23.30 | 2.17 | 23.29 |
April | 267.17 | 23.80 | 23.00 | 23.86 | 0.00 | 23.86 |
May | 92.83 | 23.93 | 170.50 | 24.30 | 6.00 | 24.29 |
June | 27.50 | 24.02 | 308.33 | 24.37 | 10.33 | 24.36 |
July | 98.33 | 24.24 | 492.17 | 24.31 | 98.33 | 24.30 |
August | 91.33 | 24.18 | 487.17 | 24.26 | 91.33 | 24.25 |
September | 99.00 | 24.23 | 389.83 | 24.29 | 77.50 | 24.30 |
October | 231.50 | 23.57 | 153.83 | 23.79 | 30.00 | 23.81 |
November | 430.83 | 22.75 | 26.17 | 22.69 | 20.83 | 22.61 |
December | 497.00 | 21.92 | 119.00 | 21.64 | 119.00 | 21.45 |
Annual Sum or Average | 3296.50 | 22.92 | 2302.00 | 23.31 | 585.33 | 23.24 |
Minimum of Months | 27.50 | 21.92 | 2.17 | 21.64 | 0.00 | 21.45 |
Maximum of Months | 509.50 | 24.24 | 492.17 | 24.37 | 119.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.17 | 22.80 | 11.83 | 22.76 | 11.83 | 22.72 |
February | 428.17 | 23.14 | 6.00 | 23.11 | 6.00 | 23.08 |
March | 471.83 | 23.58 | 1.50 | 23.57 | 1.50 | 23.57 |
April | 196.83 | 23.90 | 75.50 | 24.15 | 0.00 | 24.15 |
May | 55.33 | 24.07 | 229.17 | 24.57 | 2.00 | 24.58 |
June | 15.17 | 25.81 | 387.00 | 24.58 | 11.17 | 24.63 |
July | 101.50 | 25.46 | 496.00 | 24.66 | 101.50 | 24.77 |
August | 42.00 | 25.48 | 508.67 | 24.48 | 42.00 | 24.56 |
September | 72.50 | 24.90 | 397.67 | 24.49 | 59.33 | 24.57 |
October | 134.67 | 23.82 | 206.00 | 24.16 | 11.83 | 24.17 |
November | 414.50 | 23.45 | 5.67 | 23.45 | 0.00 | 23.45 |
December | 495.33 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
Annual Sum or Average | 2925.00 | 23.45 | 2325.00 | 23.89 | 247.17 | 23.95 |
Minimum of Months | 15.17 | 22.80 | 0.00 | 22.76 | 0.00 | 22.72 |
Maximum of Months | 497.17 | 25.81 | 508.67 | 24.66 | 101.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 431.67 | 23.02 | 17.00 | 23.02 | 9.33 | 22.98 |
February | 334.33 | 23.28 | 28.67 | 23.42 | 4.50 | 23.39 |
March | 317.33 | 23.51 | 47.50 | 23.72 | 2.67 | 23.71 |
April | 132.33 | 24.12 | 155.33 | 24.56 | 11.33 | 24.66 |
May | 60.00 | 25.64 | 328.17 | 24.84 | 33.50 | 25.01 |
June | 49.00 | 26.54 | 439.67 | 24.75 | 45.50 | 24.92 |
July | 112.17 | 25.84 | 496.17 | 24.78 | 112.17 | 24.95 |
August | 68.83 | 25.84 | 506.83 | 24.58 | 68.83 | 24.72 |
September | 77.83 | 25.87 | 431.50 | 24.73 | 71.50 | 24.89 |
October | 135.33 | 24.10 | 260.67 | 24.41 | 25.00 | 24.51 |
November | 305.00 | 23.36 | 37.67 | 23.57 | 0.00 | 23.57 |
December | 445.50 | 23.04 | 16.00 | 23.03 | 10.67 | 22.98 |
Annual Sum or Average | 2469.33 | 23.71 | 2765.17 | 24.16 | 395.00 | 24.28 |
Minimum of Months | 49.00 | 23.02 | 16.00 | 23.02 | 0.00 | 22.98 |
Maximum of Months | 445.50 | 26.54 | 506.83 | 24.84 | 112.17 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 294.17 | 22.94 | 98.33 | 23.34 | 16.33 | 23.35 |
February | 250.50 | 23.31 | 76.67 | 23.70 | 12.67 | 23.73 |
March | 276.33 | 23.53 | 50.67 | 23.82 | 3.83 | 23.83 |
April | 143.67 | 23.94 | 133.83 | 24.42 | 6.00 | 24.48 |
May | 73.17 | 24.32 | 244.83 | 24.61 | 11.00 | 24.68 |
June | 25.83 | 25.55 | 386.33 | 24.56 | 16.50 | 24.63 |
July | 103.83 | 25.45 | 495.50 | 24.65 | 103.83 | 24.77 |
August | 59.00 | 25.82 | 509.33 | 24.60 | 59.00 | 24.72 |
September | 91.50 | 25.72 | 437.83 | 24.79 | 83.83 | 24.94 |
October | 109.67 | 25.03 | 338.33 | 24.78 | 54.33 | 24.97 |
November | 222.17 | 23.73 | 167.00 | 24.23 | 19.17 | 24.37 |
December | 277.33 | 23.08 | 92.17 | 23.47 | 8.00 | 23.46 |
Annual Sum or Average | 1927.17 | 23.82 | 3030.83 | 24.31 | 394.50 | 24.41 |
Minimum of Months | 25.83 | 22.94 | 50.67 | 23.34 | 3.83 | 23.35 |
Maximum of Months | 294.17 | 25.82 | 509.33 | 24.79 | 103.83 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.50 | 23.55 | 41.67 | 23.71 | 1.83 | 23.73 |
February | 222.67 | 23.95 | 62.50 | 24.28 | 7.00 | 24.35 |
March | 120.17 | 24.28 | 136.50 | 24.68 | 12.17 | 24.80 |
April | 41.83 | 26.39 | 298.50 | 25.19 | 32.00 | 25.36 |
May | 42.50 | 26.31 | 358.50 | 24.95 | 32.17 | 25.11 |
June | 50.50 | 26.83 | 461.67 | 24.86 | 50.50 | 25.04 |
July | 143.17 | 26.39 | 497.00 | 25.10 | 143.17 | 25.34 |
August | 126.00 | 26.52 | 514.00 | 25.05 | 126.00 | 25.29 |
September | 84.00 | 26.16 | 449.33 | 24.88 | 83.83 | 25.06 |
October | 45.50 | 26.51 | 365.00 | 24.98 | 43.67 | 25.14 |
November | 104.50 | 24.36 | 177.33 | 24.70 | 12.17 | 24.80 |
December | 181.17 | 24.04 | 90.50 | 24.49 | 1.83 | 24.51 |
Annual Sum or Average | 1507.50 | 24.80 | 3452.50 | 24.80 | 546.33 | 24.97 |
Minimum of Months | 41.83 | 23.55 | 41.67 | 23.71 | 1.83 | 23.73 |
Maximum of Months | 345.50 | 26.83 | 514.00 | 25.19 | 143.17 | 25.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.24 | 208.67 | 21.06 | 208.67 | 20.96 |
February | 454.00 | 21.85 | 110.17 | 21.64 | 110.17 | 21.50 |
March | 514.00 | 22.59 | 49.00 | 22.44 | 49.00 | 22.32 |
April | 306.67 | 23.44 | 24.00 | 23.50 | 2.33 | 23.48 |
May | 99.67 | 23.85 | 193.67 | 24.36 | 1.50 | 24.36 |
June | 16.50 | 25.05 | 366.83 | 24.59 | 10.17 | 24.62 |
July | 121.33 | 25.21 | 495.83 | 24.64 | 121.33 | 24.74 |
August | 59.83 | 24.42 | 492.00 | 24.37 | 59.83 | 24.37 |
September | 102.83 | 24.08 | 368.00 | 24.26 | 65.00 | 24.28 |
October | 320.50 | 23.23 | 122.67 | 23.47 | 21.67 | 23.49 |
November | 468.67 | 21.98 | 68.50 | 21.80 | 68.50 | 21.66 |
December | 497.00 | 21.10 | 251.67 | 20.92 | 251.67 | 20.84 |
Annual Sum or Average | 3463.00 | 22.35 | 2751.00 | 22.85 | 969.83 | 22.72 |
Minimum of Months | 16.50 | 21.10 | 24.00 | 20.92 | 1.50 | 20.84 |
Maximum of Months | 514.00 | 25.21 | 495.83 | 24.64 | 251.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.33 | 22.02 | 85.33 | 21.77 | 85.33 | 21.60 |
February | 334.33 | 22.59 | 50.67 | 22.50 | 39.83 | 22.34 |
March | 319.17 | 22.99 | 39.17 | 23.07 | 17.50 | 22.97 |
April | 139.67 | 23.87 | 125.50 | 24.49 | 12.17 | 24.60 |
May | 69.83 | 25.50 | 272.67 | 24.96 | 35.83 | 25.16 |
June | 50.17 | 26.62 | 363.67 | 24.95 | 46.67 | 25.14 |
July | 124.00 | 25.84 | 421.33 | 24.98 | 124.00 | 25.14 |
August | 85.67 | 25.60 | 423.17 | 24.73 | 85.67 | 24.85 |
September | 88.67 | 25.56 | 351.83 | 24.79 | 77.67 | 24.95 |
October | 182.33 | 23.57 | 190.50 | 24.12 | 25.00 | 24.22 |
November | 338.83 | 22.64 | 45.33 | 22.63 | 26.00 | 22.50 |
December | 420.33 | 21.93 | 115.17 | 21.64 | 115.17 | 21.46 |
Annual Sum or Average | 2573.33 | 23.10 | 2484.33 | 23.67 | 690.83 | 23.69 |
Minimum of Months | 50.17 | 21.93 | 39.17 | 21.64 | 12.17 | 21.46 |
Maximum of Months | 420.33 | 26.62 | 423.17 | 24.98 | 124.00 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.83 | 22.49 | 119.33 | 22.79 | 45.67 | 22.68 |
February | 272.00 | 22.84 | 90.33 | 23.20 | 30.17 | 23.16 |
March | 307.50 | 23.04 | 57.00 | 23.31 | 11.83 | 23.26 |
April | 193.17 | 23.55 | 104.67 | 24.03 | 5.50 | 24.07 |
May | 99.33 | 24.02 | 219.33 | 24.46 | 8.83 | 24.51 |
June | 27.67 | 25.11 | 363.67 | 24.57 | 15.50 | 24.63 |
July | 126.83 | 25.22 | 494.33 | 24.64 | 126.83 | 24.74 |
August | 81.00 | 25.17 | 498.33 | 24.54 | 81.00 | 24.62 |
September | 106.33 | 25.37 | 425.83 | 24.73 | 93.00 | 24.86 |
October | 160.00 | 24.35 | 310.33 | 24.58 | 55.50 | 24.76 |
November | 259.00 | 23.17 | 169.67 | 23.77 | 32.00 | 23.86 |
December | 310.50 | 22.46 | 121.50 | 22.63 | 56.83 | 22.44 |
Annual Sum or Average | 2258.17 | 23.39 | 2974.33 | 24.00 | 562.67 | 24.05 |
Minimum of Months | 27.67 | 22.46 | 57.00 | 22.63 | 5.50 | 22.44 |
Maximum of Months | 314.83 | 25.37 | 498.33 | 24.73 | 126.83 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 446.67 | 22.00 | 80.83 | 21.86 | 74.50 | 21.72 |
February | 384.00 | 22.51 | 55.00 | 22.48 | 42.33 | 22.36 |
March | 383.67 | 23.11 | 60.00 | 23.26 | 14.00 | 23.22 |
April | 180.17 | 23.94 | 142.67 | 24.34 | 14.50 | 24.47 |
May | 76.50 | 24.98 | 304.33 | 24.76 | 26.17 | 24.91 |
June | 35.50 | 26.45 | 421.83 | 24.77 | 32.83 | 24.90 |
July | 134.50 | 25.75 | 496.00 | 24.87 | 134.50 | 25.03 |
August | 89.67 | 25.45 | 508.50 | 24.66 | 89.67 | 24.76 |
September | 98.50 | 25.22 | 424.00 | 24.65 | 86.83 | 24.76 |
October | 167.33 | 23.90 | 243.83 | 24.25 | 35.33 | 24.36 |
November | 354.33 | 22.61 | 71.00 | 22.77 | 22.00 | 22.68 |
December | 458.17 | 21.99 | 105.17 | 21.74 | 105.17 | 21.57 |
Annual Sum or Average | 2809.00 | 23.07 | 2913.17 | 23.69 | 677.83 | 23.71 |
Minimum of Months | 35.50 | 21.99 | 55.00 | 21.74 | 14.00 | 21.57 |
Maximum of Months | 458.17 | 26.45 | 508.50 | 24.87 | 134.50 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 344.17 | 20.35 | 344.17 | 20.27 |
February | 454.00 | 21.17 | 245.83 | 20.93 | 245.83 | 20.81 |
March | 514.00 | 22.03 | 137.83 | 21.73 | 137.83 | 21.54 |
April | 319.00 | 23.09 | 51.50 | 23.15 | 16.33 | 23.06 |
May | 122.17 | 23.83 | 208.67 | 24.33 | 10.33 | 24.39 |
June | 30.50 | 25.62 | 391.83 | 24.63 | 22.83 | 24.71 |
July | 141.67 | 25.28 | 495.83 | 24.70 | 141.67 | 24.81 |
August | 88.17 | 24.64 | 490.33 | 24.41 | 83.83 | 24.45 |
September | 145.83 | 24.06 | 361.50 | 24.24 | 91.33 | 24.28 |
October | 356.33 | 22.75 | 111.17 | 23.06 | 25.83 | 23.10 |
November | 477.33 | 21.25 | 201.00 | 20.94 | 201.00 | 20.77 |
December | 497.00 | 20.38 | 395.00 | 20.26 | 395.00 | 20.21 |
Annual Sum or Average | 3648.00 | 21.91 | 3434.67 | 22.35 | 1716.00 | 22.14 |
Minimum of Months | 30.50 | 20.38 | 51.50 | 20.26 | 10.33 | 20.21 |
Maximum of Months | 514.00 | 25.62 | 495.83 | 24.70 | 395.00 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.26 | 219.00 | 20.88 | 219.00 | 20.68 |
February | 434.33 | 22.16 | 108.33 | 21.82 | 106.67 | 21.58 |
March | 398.83 | 22.70 | 65.00 | 22.51 | 57.33 | 22.31 |
April | 164.00 | 23.61 | 147.33 | 24.22 | 16.00 | 24.26 |
May | 84.00 | 25.26 | 339.33 | 24.78 | 39.50 | 24.97 |
June | 56.50 | 26.54 | 447.33 | 24.83 | 52.17 | 25.01 |
July | 139.83 | 25.70 | 496.33 | 24.86 | 139.83 | 25.01 |
August | 99.83 | 25.40 | 504.33 | 24.62 | 99.17 | 24.73 |
September | 106.00 | 25.20 | 422.33 | 24.63 | 88.83 | 24.77 |
October | 220.67 | 22.95 | 208.67 | 23.71 | 26.83 | 23.77 |
November | 442.83 | 22.15 | 101.50 | 21.88 | 89.00 | 21.65 |
December | 497.00 | 21.03 | 261.67 | 20.71 | 261.67 | 20.55 |
Annual Sum or Average | 3145.83 | 22.56 | 3321.17 | 23.10 | 1196.00 | 22.98 |
Minimum of Months | 56.50 | 21.03 | 65.00 | 20.71 | 16.00 | 20.55 |
Maximum of Months | 502.00 | 26.54 | 504.33 | 24.86 | 261.67 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.50 | 21.77 | 168.17 | 21.65 | 120.83 | 21.35 |
February | 307.83 | 22.16 | 117.17 | 22.21 | 79.00 | 21.98 |
March | 338.83 | 22.55 | 95.17 | 22.51 | 65.00 | 22.28 |
April | 220.33 | 23.23 | 118.67 | 23.68 | 19.50 | 23.64 |
May | 121.50 | 23.94 | 235.67 | 24.39 | 16.33 | 24.49 |
June | 39.67 | 25.40 | 387.83 | 24.61 | 25.00 | 24.70 |
July | 140.33 | 25.23 | 495.17 | 24.68 | 140.33 | 24.78 |
August | 95.67 | 25.07 | 495.17 | 24.54 | 94.50 | 24.62 |
September | 126.83 | 24.99 | 416.50 | 24.63 | 105.67 | 24.75 |
October | 196.17 | 23.64 | 283.00 | 24.22 | 49.67 | 24.40 |
November | 289.33 | 22.30 | 179.50 | 22.66 | 74.50 | 22.45 |
December | 364.17 | 21.74 | 166.83 | 21.53 | 137.33 | 21.26 |
Annual Sum or Average | 2600.17 | 22.86 | 3158.83 | 23.46 | 927.67 | 23.38 |
Minimum of Months | 39.67 | 21.74 | 95.17 | 21.53 | 16.33 | 21.26 |
Maximum of Months | 364.17 | 25.40 | 495.17 | 24.68 | 140.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.17 | 21.39 | 209.33 | 21.05 | 208.50 | 20.86 |
February | 402.67 | 21.90 | 135.83 | 21.69 | 125.83 | 21.50 |
March | 396.17 | 22.54 | 105.00 | 22.48 | 73.00 | 22.28 |
April | 207.17 | 23.59 | 148.17 | 24.04 | 21.67 | 24.12 |
May | 100.83 | 24.69 | 307.67 | 24.69 | 31.00 | 24.85 |
June | 47.50 | 26.22 | 432.33 | 24.78 | 42.67 | 24.92 |
July | 152.00 | 25.63 | 496.17 | 24.88 | 152.00 | 25.02 |
August | 105.67 | 25.40 | 505.33 | 24.68 | 105.67 | 24.79 |
September | 124.67 | 24.89 | 414.67 | 24.58 | 103.00 | 24.68 |
October | 227.33 | 23.38 | 224.83 | 23.92 | 35.00 | 24.03 |
November | 387.33 | 21.96 | 129.00 | 21.83 | 97.67 | 21.59 |
December | 481.33 | 21.33 | 240.33 | 20.99 | 240.33 | 20.82 |
Annual Sum or Average | 3105.83 | 22.62 | 3348.67 | 23.17 | 1236.33 | 23.06 |
Minimum of Months | 47.50 | 21.33 | 105.00 | 20.99 | 21.67 | 20.82 |
Maximum of Months | 481.33 | 26.22 | 505.33 | 24.88 | 240.33 | 25.02 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.33 | 27.00 | 454.00 | 27.00 | 0.33 | 27.00 |
March | 1.33 | 27.00 | 514.00 | 27.00 | 1.33 | 27.00 |
April | 90.67 | 27.74 | 485.00 | 27.25 | 90.67 | 27.32 |
May | 0.17 | 27.00 | 508.00 | 27.00 | 0.17 | 27.00 |
June | 17.33 | 27.00 | 496.00 | 27.00 | 17.33 | 27.00 |
July | 109.50 | 27.00 | 497.00 | 27.00 | 109.50 | 27.00 |
August | 313.50 | 27.69 | 514.00 | 27.53 | 313.50 | 27.57 |
September | 4.83 | 27.00 | 485.00 | 27.00 | 4.83 | 27.00 |
October | 10.83 | 27.00 | 502.00 | 27.00 | 10.83 | 27.00 |
November | 13.17 | 27.00 | 489.00 | 27.00 | 13.17 | 27.00 |
December | 0.83 | 27.00 | 497.00 | 27.00 | 0.83 | 27.00 |
Annual Sum or Average | 562.50 | 27.50 | 5943.00 | 27.09 | 562.50 | 27.12 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 313.50 | 27.74 | 514.00 | 27.53 | 313.50 | 27.57 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 481.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 452.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 25.67 | 27.99 | 485.00 | 27.16 | 25.67 | 27.20 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 5.17 | 27.00 | 497.00 | 27.00 | 5.17 | 27.00 |
August | 132.17 | 28.00 | 514.00 | 27.45 | 132.17 | 27.54 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.83 | 27.00 | 502.00 | 27.00 | 0.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 494.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 163.83 | 27.96 | 5918.00 | 27.06 | 163.83 | 27.09 |
Minimum of Months | 0.00 | 0.00 | 452.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 132.17 | 28.00 | 514.00 | 27.45 | 132.17 | 27.54 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.83 | 25.96 | 330.83 | 26.83 | 0.00 | 26.83 |
February | 0.00 | 0.00 | 352.33 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 490.50 | 27.00 | 0.00 | 27.00 |
April | 27.17 | 27.84 | 485.00 | 27.12 | 27.17 | 27.16 |
May | 3.67 | 27.00 | 508.00 | 27.00 | 3.67 | 27.00 |
June | 19.67 | 27.00 | 496.00 | 27.00 | 19.67 | 27.00 |
July | 35.50 | 27.00 | 497.00 | 27.00 | 35.50 | 27.00 |
August | 134.50 | 27.89 | 514.00 | 27.38 | 134.50 | 27.47 |
September | 3.83 | 27.00 | 485.00 | 27.00 | 3.83 | 27.00 |
October | 2.17 | 27.00 | 502.00 | 27.00 | 2.17 | 27.00 |
November | 0.00 | 0.00 | 444.50 | 27.00 | 0.00 | 27.00 |
December | 2.50 | 27.00 | 357.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 294.83 | 27.25 | 5462.83 | 27.04 | 226.50 | 27.06 |
Minimum of Months | 0.00 | 0.00 | 330.83 | 26.83 | 0.00 | 26.83 |
Maximum of Months | 134.50 | 27.89 | 514.00 | 27.38 | 134.50 | 27.47 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 447.00 | 27.00 | 502.00 | 27.00 | 447.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.64 | 485.00 | 27.64 | 485.00 | 27.64 |
May | 395.33 | 27.00 | 508.00 | 27.00 | 395.33 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.40 | 497.00 | 27.40 | 497.00 | 27.40 |
August | 514.00 | 30.07 | 514.00 | 30.07 | 514.00 | 30.07 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5775.33 | 27.36 | 5943.00 | 27.36 | 5775.33 | 27.36 |
Minimum of Months | 395.33 | 27.00 | 454.00 | 27.00 | 395.33 | 27.00 |
Maximum of Months | 514.00 | 30.07 | 514.00 | 30.07 | 514.00 | 30.07 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00008 | 19.51953 | 0.75017 | 16.93620 |
February | 454.00000 | 27.00008 | 17.64743 | 0.77994 | 17.88742 |
March | 514.00000 | 27.00001 | 18.47783 | 0.83477 | 19.75213 |
April | 485.00000 | 27.16069 | 20.14186 | 0.93387 | 23.58969 |
May | 508.00000 | 27.00030 | 25.31009 | 0.19808 | 5.89514 |
June | 496.00000 | 27.00041 | 26.58469 | 0.26816 | 6.55866 |
July | 497.00000 | 27.00066 | 29.36083 | 0.34027 | 7.45842 |
August | 514.00000 | 27.42296 | 28.31119 | 0.49746 | 10.95655 |
September | 485.00000 | 27.00092 | 28.37098 | 0.23470 | 6.21686 |
October | 502.00000 | 27.00066 | 25.51665 | 0.89061 | 21.79149 |
November | 489.00000 | 27.00012 | 21.04181 | 0.86097 | 20.71256 |
December | 497.00000 | 27.00000 | 17.83471 | 0.84297 | 20.05040 |
Annual Sum or Average | 5943.00000 | 27.04996 | 23.21850 | 0.61787 | 14.78223 |
Minimum of Months | 454.00000 | 27.00000 | 17.64743 | 0.19808 | 5.89514 |
Maximum of Months | 514.00000 | 27.42296 | 29.36083 | 0.93387 | 23.58969 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00007 | 19.56483 | 0.65391 | 14.09779 |
February | 454.00000 | 27.00008 | 17.63785 | 0.67824 | 14.78266 |
March | 514.00000 | 27.00001 | 18.45455 | 0.73314 | 16.40380 |
April | 485.00000 | 27.11992 | 20.14741 | 0.82829 | 19.65638 |
May | 508.00000 | 27.00025 | 25.32414 | 0.14704 | 5.55133 |
June | 496.00000 | 27.00040 | 26.59815 | 0.20134 | 5.91146 |
July | 497.00000 | 27.00064 | 29.40183 | 0.24410 | 6.29122 |
August | 514.00000 | 27.30412 | 28.43109 | 0.32384 | 7.72451 |
September | 485.00000 | 27.00070 | 28.51012 | 0.17515 | 5.72737 |
October | 502.00000 | 27.00063 | 25.55789 | 0.81756 | 19.16035 |
November | 489.00000 | 27.00012 | 21.03240 | 0.74144 | 16.70340 |
December | 497.00000 | 27.00000 | 17.80291 | 0.67650 | 14.74709 |
Annual Sum or Average | 5943.00000 | 27.03633 | 23.24756 | 0.51678 | 12.19858 |
Minimum of Months | 454.00000 | 27.00000 | 17.63785 | 0.14704 | 5.55133 |
Maximum of Months | 514.00000 | 27.30412 | 29.40183 | 0.82829 | 19.65638 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.83350 | 19.96506 | 0.54353 | 11.68542 |
February | 454.00000 | 27.00008 | 17.67096 | 0.61065 | 13.05453 |
March | 514.00000 | 27.00001 | 18.46777 | 0.68690 | 15.12686 |
April | 485.00000 | 27.08320 | 20.18022 | 0.81022 | 19.11738 |
May | 508.00000 | 27.00027 | 25.32034 | 0.15506 | 5.69984 |
June | 496.00000 | 27.00041 | 26.58926 | 0.22436 | 6.18099 |
July | 497.00000 | 27.00068 | 29.38744 | 0.26952 | 6.62628 |
August | 514.00000 | 27.25052 | 28.45008 | 0.32764 | 7.91386 |
September | 485.00000 | 27.00076 | 28.48755 | 0.17892 | 5.84488 |
October | 502.00000 | 27.00064 | 25.58757 | 0.79436 | 18.44758 |
November | 489.00000 | 27.00012 | 21.04828 | 0.67419 | 14.83106 |
December | 497.00000 | 27.00001 | 17.81867 | 0.58405 | 12.40939 |
Annual Sum or Average | 5943.00000 | 27.01464 | 23.29038 | 0.48696 | 11.38778 |
Minimum of Months | 454.00000 | 26.83350 | 17.67096 | 0.15506 | 5.69984 |
Maximum of Months | 514.00000 | 27.25052 | 29.38744 | 0.81022 | 19.11738 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00034 | 28.91685 | 1.02573 | 27.22402 |
February | 454.00000 | 27.00013 | 22.55012 | 1.11640 | 31.30068 |
March | 514.00000 | 27.00004 | 18.92318 | 1.22566 | 36.52195 |
April | 485.00000 | 27.64071 | 19.79208 | 1.50038 | 50.77355 |
May | 508.00000 | 27.00200 | 28.35867 | 0.43081 | 8.94828 |
June | 496.00000 | 27.00418 | 31.13960 | 0.68421 | 14.88500 |
July | 497.00000 | 27.40183 | 34.97768 | 1.05663 | 29.33935 |
August | 514.00000 | 30.07145 | 30.86759 | 1.99573 | 72.71059 |
September | 485.00000 | 27.00216 | 36.27141 | 0.59045 | 12.45217 |
October | 502.00000 | 27.00187 | 31.62796 | 1.26338 | 38.43755 |
November | 489.00000 | 27.00122 | 23.15952 | 1.31900 | 41.26908 |
December | 497.00000 | 27.00060 | 19.48094 | 1.40177 | 45.61635 |
Annual Sum or Average | 5943.00000 | 27.35258 | 27.20122 | 1.13594 | 34.21586 |
Minimum of Months | 454.00000 | 27.00004 | 18.92318 | 0.43081 | 8.94828 |
Maximum of Months | 514.00000 | 30.07145 | 36.27141 | 1.99573 | 72.71059 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46754 | 18.71634 | 0.31382 | 7.64079 |
February | 454.00000 | 24.43602 | 16.62285 | 0.28559 | 7.11363 |
March | 514.00000 | 24.34394 | 16.05539 | 0.26426 | 6.75612 |
April | 485.00000 | 24.45529 | 20.51102 | 0.32630 | 7.63650 |
May | 508.00000 | 24.46184 | 30.25408 | -0.4631 | 10.47721 |
June | 496.00000 | 24.44054 | 36.88604 | -0.4130 | 9.44783 |
July | 497.00000 | 24.61066 | 53.06643 | -0.2325 | 7.31785 |
August | 514.00000 | 24.51540 | 48.70968 | -0.2724 | 7.45528 |
September | 485.00000 | 24.58399 | 46.59105 | -0.2708 | 8.00653 |
October | 502.00000 | 24.60322 | 35.82561 | 0.49486 | 10.96582 |
November | 489.00000 | 24.57892 | 21.13575 | 0.37866 | 8.64400 |
December | 497.00000 | 24.54402 | 16.00012 | 0.32375 | 7.73955 |
Annual Sum or Average | 5943.00000 | 24.50333 | 30.13404 | 0.05868 | 8.27539 |
Minimum of Months | 454.00000 | 24.34394 | 16.00012 | -0.4631 | 6.75612 |
Maximum of Months | 514.00000 | 24.61066 | 53.06643 | 0.49486 | 10.96582 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.26700 | 21.76895 | 0.28546 | 6.99216 |
February | 454.00000 | 24.26468 | 18.24290 | 0.27228 | 6.71949 |
March | 514.00000 | 24.24385 | 16.95567 | 0.27386 | 6.72631 |
April | 485.00000 | 24.28025 | 21.22766 | 0.32970 | 7.47800 |
May | 508.00000 | 24.27926 | 31.21311 | -0.4751 | 10.22421 |
June | 496.00000 | 24.23970 | 38.10076 | -0.4218 | 9.10305 |
July | 497.00000 | 24.25644 | 51.74923 | -0.3105 | 7.26948 |
August | 514.00000 | 24.27862 | 48.62935 | -0.3072 | 7.27672 |
September | 485.00000 | 24.35689 | 46.19263 | -0.3346 | 7.98904 |
October | 502.00000 | 24.37156 | 36.78391 | 0.45680 | 9.81687 |
November | 489.00000 | 24.37395 | 22.45936 | 0.34615 | 7.80915 |
December | 497.00000 | 24.37019 | 18.30907 | 0.30431 | 7.19857 |
Annual Sum or Average | 5943.00000 | 24.29839 | 31.06869 | 0.03237 | 7.89267 |
Minimum of Months | 454.00000 | 24.23970 | 16.95567 | -0.4751 | 6.71949 |
Maximum of Months | 514.00000 | 24.37395 | 51.74923 | 0.45680 | 10.22421 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.65673 | 23.09422 | 0.10951 | 5.51621 |
February | 454.00000 | 23.82246 | 19.56747 | 0.13959 | 5.66079 |
March | 514.00000 | 23.97919 | 18.71123 | 0.18376 | 5.83605 |
April | 485.00000 | 24.14013 | 22.08967 | 0.26544 | 6.63509 |
May | 508.00000 | 24.19166 | 31.51970 | -0.5266 | 11.17396 |
June | 496.00000 | 24.21087 | 38.14719 | -0.4613 | 9.79647 |
July | 497.00000 | 24.22079 | 52.42845 | -0.3622 | 7.95722 |
August | 514.00000 | 24.20318 | 49.76027 | -0.3867 | 8.32833 |
September | 485.00000 | 24.24916 | 46.65733 | -0.3985 | 8.72841 |
October | 502.00000 | 24.16508 | 37.88003 | 0.38107 | 8.27192 |
November | 489.00000 | 23.99107 | 24.74263 | 0.22244 | 6.28684 |
December | 497.00000 | 23.65520 | 20.10910 | 0.08853 | 5.45681 |
Annual Sum or Average | 5943.00000 | 24.04180 | 32.15761 | -0.0644 | 7.48778 |
Minimum of Months | 454.00000 | 23.65520 | 18.71123 | -0.5266 | 5.45681 |
Maximum of Months | 514.00000 | 24.24916 | 52.42845 | 0.38107 | 11.17396 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.11051 | 25.82605 | -0.2796 | 8.15471 |
February | 454.00000 | 22.67226 | 21.19672 | -0.1565 | 6.80958 |
March | 514.00000 | 23.31723 | 19.56825 | 0.00508 | 5.83069 |
April | 485.00000 | 23.98185 | 22.21579 | 0.22228 | 6.43395 |
May | 508.00000 | 24.21353 | 31.47532 | -0.5102 | 11.02383 |
June | 496.00000 | 24.28070 | 38.03423 | -0.4140 | 9.10682 |
July | 497.00000 | 24.32344 | 52.04430 | -0.3047 | 7.40949 |
August | 514.00000 | 24.26679 | 49.69280 | -0.3488 | 7.88058 |
September | 485.00000 | 24.24816 | 46.91949 | -0.3920 | 8.74411 |
October | 502.00000 | 23.86681 | 38.82288 | 0.30040 | 7.33359 |
November | 489.00000 | 22.90923 | 26.24203 | -0.0605 | 6.64015 |
December | 497.00000 | 21.92170 | 22.47351 | -0.3471 | 9.24652 |
Annual Sum or Average | 5943.00000 | 23.51568 | 32.96820 | -0.1914 | 7.89463 |
Minimum of Months | 454.00000 | 21.92170 | 19.56825 | -0.5102 | 5.83069 |
Maximum of Months | 514.00000 | 24.32344 | 52.04430 | 0.30040 | 11.02383 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.80994 | 23.05863 | -0.0952 | 6.13818 |
February | 454.00000 | 23.19574 | 19.24888 | -0.0184 | 5.93055 |
March | 514.00000 | 23.62520 | 17.22202 | 0.08728 | 5.69134 |
April | 485.00000 | 24.15954 | 20.70465 | 0.28132 | 7.09645 |
May | 508.00000 | 24.35101 | 29.88359 | -0.4333 | 9.94416 |
June | 496.00000 | 24.42327 | 36.62766 | -0.3035 | 7.83954 |
July | 497.00000 | 24.49248 | 50.33204 | -0.1826 | 6.81461 |
August | 514.00000 | 24.39822 | 47.51239 | -0.2434 | 7.10469 |
September | 485.00000 | 24.35444 | 45.34336 | -0.3342 | 8.33327 |
October | 502.00000 | 24.11101 | 36.72105 | 0.36501 | 8.29352 |
November | 489.00000 | 23.53662 | 23.30456 | 0.09870 | 5.76300 |
December | 497.00000 | 23.02470 | 19.97064 | -0.0625 | 5.83331 |
Annual Sum or Average | 5943.00000 | 23.87821 | 30.91700 | -0.0712 | 7.07419 |
Minimum of Months | 454.00000 | 22.80994 | 17.22202 | -0.4333 | 5.69134 |
Maximum of Months | 514.00000 | 24.49248 | 50.33204 | 0.36501 | 9.94416 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19378 | 22.17948 | 0.01138 | 6.27619 |
February | 454.00000 | 23.58797 | 18.37017 | 0.10188 | 6.57018 |
March | 514.00000 | 23.83344 | 16.44945 | 0.17822 | 6.77643 |
April | 485.00000 | 24.30275 | 20.24239 | 0.37383 | 8.97093 |
May | 508.00000 | 24.47674 | 29.45098 | -0.2953 | 8.86304 |
June | 496.00000 | 24.49800 | 36.28286 | -0.1942 | 7.62790 |
July | 497.00000 | 24.53803 | 49.96775 | -0.0983 | 7.19681 |
August | 514.00000 | 24.40531 | 47.32468 | -0.1774 | 7.22161 |
September | 485.00000 | 24.47615 | 44.57840 | -0.2027 | 7.82290 |
October | 502.00000 | 24.23317 | 36.11510 | 0.43253 | 10.00737 |
November | 489.00000 | 23.74136 | 22.68001 | 0.17434 | 6.67397 |
December | 497.00000 | 23.18695 | 19.50790 | -0.0103 | 6.25165 |
Annual Sum or Average | 5943.00000 | 24.04237 | 30.35491 | 0.02313 | 7.52659 |
Minimum of Months | 454.00000 | 23.18695 | 16.44945 | -0.2953 | 6.25165 |
Maximum of Months | 514.00000 | 24.53803 | 49.96775 | 0.43253 | 10.00737 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.51715 | 20.92872 | 0.14419 | 7.89400 |
February | 454.00000 | 23.79322 | 17.48469 | 0.19246 | 7.76854 |
March | 514.00000 | 23.90783 | 16.07405 | 0.21427 | 7.26780 |
April | 485.00000 | 24.26114 | 20.31628 | 0.34431 | 8.41024 |
May | 508.00000 | 24.35962 | 29.80169 | -0.4167 | 9.97403 |
June | 496.00000 | 24.39703 | 36.68332 | -0.3159 | 8.05946 |
July | 497.00000 | 24.47923 | 50.33797 | -0.1816 | 6.93111 |
August | 514.00000 | 24.45787 | 47.24370 | -0.1864 | 6.97804 |
September | 485.00000 | 24.53813 | 44.42263 | -0.1772 | 7.66232 |
October | 502.00000 | 24.45191 | 35.31187 | 0.53354 | 12.47585 |
November | 489.00000 | 24.08075 | 21.53244 | 0.32000 | 9.12790 |
December | 497.00000 | 23.65590 | 17.96908 | 0.16194 | 7.68566 |
Annual Sum or Average | 5943.00000 | 24.16027 | 29.93887 | 0.05070 | 8.35647 |
Minimum of Months | 454.00000 | 23.51715 | 16.07405 | -0.4167 | 6.93111 |
Maximum of Months | 514.00000 | 24.53813 | 50.33797 | 0.53354 | 12.47585 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.79170 | 20.83414 | 0.17087 | 6.58171 |
February | 454.00000 | 24.19760 | 17.09473 | 0.27535 | 7.49848 |
March | 514.00000 | 24.35760 | 15.40601 | 0.36682 | 8.58195 |
April | 485.00000 | 24.63621 | 19.55022 | 0.54308 | 12.47665 |
May | 508.00000 | 24.56764 | 29.18993 | -0.2166 | 8.26780 |
June | 496.00000 | 24.60386 | 35.99183 | -0.0798 | 7.26696 |
July | 497.00000 | 24.73116 | 49.31593 | 0.07352 | 7.56859 |
August | 514.00000 | 24.68613 | 46.39154 | 0.08003 | 7.61911 |
September | 485.00000 | 24.59550 | 44.30040 | -0.1040 | 7.34307 |
October | 502.00000 | 24.58015 | 35.03060 | 0.57950 | 13.23565 |
November | 489.00000 | 24.41914 | 20.93743 | 0.39804 | 9.09230 |
December | 497.00000 | 24.37158 | 17.03593 | 0.32621 | 7.85937 |
Annual Sum or Average | 5943.00000 | 24.46292 | 29.35089 | 0.19990 | 8.61700 |
Minimum of Months | 454.00000 | 23.79170 | 15.40601 | -0.2166 | 6.58171 |
Maximum of Months | 514.00000 | 24.73116 | 49.31593 | 0.57950 | 13.23565 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.23926 | 24.18884 | -0.4887 | 10.85242 |
February | 454.00000 | 21.84617 | 20.91388 | -0.3509 | 8.89377 |
March | 514.00000 | 22.58668 | 19.18776 | -0.1704 | 6.91110 |
April | 485.00000 | 23.72093 | 21.49903 | 0.15212 | 6.38464 |
May | 508.00000 | 24.25058 | 29.79504 | -0.4883 | 11.09852 |
June | 496.00000 | 24.43096 | 36.28604 | -0.3252 | 8.11927 |
July | 497.00000 | 24.50171 | 51.10132 | -0.2079 | 7.00549 |
August | 514.00000 | 24.34310 | 48.39875 | -0.3101 | 7.71230 |
September | 485.00000 | 24.21028 | 45.90390 | -0.4076 | 9.43942 |
October | 502.00000 | 23.53274 | 38.65466 | 0.21194 | 6.79280 |
November | 489.00000 | 22.06404 | 26.00177 | -0.2581 | 7.99220 |
December | 497.00000 | 21.09854 | 21.31793 | -0.5456 | 12.19717 |
Annual Sum or Average | 5943.00000 | 23.16203 | 32.02309 | -0.2657 | 8.61583 |
Minimum of Months | 454.00000 | 21.09854 | 19.18776 | -0.5456 | 6.38464 |
Maximum of Months | 514.00000 | 24.50171 | 51.10132 | 0.21194 | 12.19717 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.05359 | 22.85283 | -0.2840 | 8.52553 |
February | 385.00000 | 22.85922 | 18.82639 | -0.0930 | 7.37858 |
March | 433.00000 | 23.38394 | 17.11474 | 0.05151 | 7.00035 |
April | 410.00000 | 24.28909 | 19.89821 | 0.34774 | 9.11008 |
May | 430.00000 | 24.54221 | 28.74411 | -0.2921 | 9.40752 |
June | 418.00000 | 24.62723 | 35.25818 | -0.1682 | 7.88049 |
July | 422.00000 | 24.72353 | 49.97669 | -0.0497 | 7.66525 |
August | 433.00000 | 24.53541 | 47.23082 | -0.1610 | 7.49258 |
September | 410.00000 | 24.52108 | 44.30220 | -0.2139 | 8.43919 |
October | 427.00000 | 24.00700 | 36.64243 | 0.35747 | 9.28154 |
November | 417.00000 | 22.96337 | 23.84437 | -0.0274 | 7.14294 |
December | 422.00000 | 21.94480 | 20.00882 | -0.3344 | 9.30514 |
Annual Sum or Average | 5034.00000 | 23.70819 | 30.47503 | -0.0728 | 8.22296 |
Minimum of Months | 385.00000 | 21.94480 | 17.11474 | -0.3344 | 7.00035 |
Maximum of Months | 433.00000 | 24.72353 | 49.97669 | 0.35747 | 9.40752 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17810 | 20.64504 | 0.05667 | 8.59175 |
February | 454.00000 | 23.46509 | 17.98684 | 0.11240 | 8.21213 |
March | 514.00000 | 23.56758 | 17.01868 | 0.12856 | 7.44293 |
April | 485.00000 | 24.04960 | 20.61722 | 0.27542 | 7.89560 |
May | 508.00000 | 24.27814 | 29.65903 | -0.4602 | 10.87938 |
June | 496.00000 | 24.40262 | 36.35141 | -0.3391 | 8.36816 |
July | 497.00000 | 24.49275 | 51.09249 | -0.2051 | 7.11163 |
August | 514.00000 | 24.42224 | 47.99988 | -0.2371 | 7.34722 |
September | 485.00000 | 24.49277 | 44.53832 | -0.2019 | 8.03468 |
October | 502.00000 | 24.30151 | 35.82363 | 0.49280 | 12.03039 |
November | 489.00000 | 23.74372 | 22.58673 | 0.23962 | 9.51763 |
December | 497.00000 | 23.17973 | 17.95311 | 0.03317 | 8.48417 |
Annual Sum or Average | 5943.00000 | 23.96746 | 30.28621 | -0.0107 | 8.66423 |
Minimum of Months | 454.00000 | 23.17810 | 17.01868 | -0.4602 | 7.11163 |
Maximum of Months | 514.00000 | 24.49277 | 51.09249 | 0.49280 | 12.03039 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.24226 | 22.51242 | -0.2267 | 8.14009 |
February | 454.00000 | 22.82099 | 19.42156 | -0.0944 | 7.48054 |
March | 514.00000 | 23.41224 | 17.58031 | 0.07277 | 7.01268 |
April | 485.00000 | 24.19149 | 20.41114 | 0.33851 | 8.84910 |
May | 508.00000 | 24.43225 | 29.22115 | -0.3134 | 9.42478 |
June | 496.00000 | 24.53511 | 35.89153 | -0.1804 | 7.67495 |
July | 497.00000 | 24.63652 | 50.48671 | -0.0632 | 7.27331 |
August | 514.00000 | 24.51703 | 47.67713 | -0.1399 | 7.36158 |
September | 485.00000 | 24.43834 | 44.86368 | -0.2140 | 7.92037 |
October | 502.00000 | 24.10770 | 36.69617 | 0.40716 | 9.76270 |
November | 489.00000 | 23.07930 | 24.01220 | 0.01745 | 7.39848 |
December | 497.00000 | 22.15404 | 19.80697 | -0.2707 | 8.62134 |
Annual Sum or Average | 5943.00000 | 23.72055 | 30.80350 | -0.0559 | 8.07959 |
Minimum of Months | 454.00000 | 22.15404 | 17.58031 | -0.3134 | 7.01268 |
Maximum of Months | 514.00000 | 24.63652 | 50.48671 | 0.40716 | 9.76270 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.53060 | 25.17252 | -0.7027 | 17.24003 |
February | 454.00000 | 21.17382 | 21.28083 | -0.5467 | 13.13770 |
March | 514.00000 | 22.02834 | 19.17697 | -0.3261 | 9.26899 |
April | 485.00000 | 23.48827 | 21.58210 | 0.09376 | 6.88938 |
May | 508.00000 | 24.20773 | 29.84277 | -0.4929 | 11.86446 |
June | 496.00000 | 24.44583 | 36.44896 | -0.2972 | 8.00929 |
July | 497.00000 | 24.53412 | 51.11319 | -0.1737 | 7.09594 |
August | 514.00000 | 24.35046 | 48.61064 | -0.2909 | 7.81458 |
September | 485.00000 | 24.14937 | 46.43262 | -0.4192 | 10.30292 |
October | 502.00000 | 23.13547 | 39.58345 | 0.11289 | 6.98324 |
November | 489.00000 | 21.31477 | 26.41201 | -0.4685 | 12.32905 |
December | 497.00000 | 20.37886 | 22.15893 | -0.7687 | 19.49089 |
Annual Sum or Average | 5943.00000 | 22.82409 | 32.40274 | -0.3558 | 10.85077 |
Minimum of Months | 454.00000 | 20.37886 | 19.17697 | -0.7687 | 6.88938 |
Maximum of Months | 514.00000 | 24.53412 | 51.11319 | 0.11289 | 19.49089 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25657 | 24.33582 | -0.5031 | 13.13177 |
February | 454.00000 | 22.26019 | 19.97802 | -0.2598 | 9.31026 |
March | 514.00000 | 23.04237 | 17.35492 | -0.0465 | 7.46581 |
April | 485.00000 | 24.13740 | 20.16469 | 0.32109 | 8.96021 |
May | 508.00000 | 24.43875 | 29.16542 | -0.2951 | 9.46830 |
June | 496.00000 | 24.55823 | 35.98139 | -0.1438 | 7.60854 |
July | 497.00000 | 24.62348 | 50.44016 | -0.0386 | 7.56053 |
August | 514.00000 | 24.45459 | 48.01593 | -0.1467 | 7.40249 |
September | 485.00000 | 24.40797 | 45.08574 | -0.2191 | 8.47847 |
October | 502.00000 | 23.70564 | 37.52499 | 0.28969 | 8.91912 |
November | 489.00000 | 22.33517 | 24.91847 | -0.2024 | 9.02518 |
December | 497.00000 | 21.02740 | 21.49800 | -0.5841 | 14.81844 |
Annual Sum or Average | 5943.00000 | 23.36215 | 31.29269 | -0.1522 | 9.34139 |
Minimum of Months | 454.00000 | 21.02740 | 17.35492 | -0.5841 | 7.40249 |
Maximum of Months | 514.00000 | 24.62348 | 50.44016 | 0.32109 | 14.81844 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.49771 | 21.72592 | -0.1481 | 10.74104 |
February | 454.00000 | 22.90564 | 18.39493 | -0.0581 | 9.48835 |
March | 514.00000 | 23.16765 | 16.95083 | 0.00529 | 8.21150 |
April | 485.00000 | 23.85777 | 20.69666 | 0.22631 | 8.18225 |
May | 508.00000 | 24.22645 | 29.73305 | -0.4671 | 11.73699 |
June | 496.00000 | 24.41651 | 36.52073 | -0.3114 | 8.27624 |
July | 497.00000 | 24.51933 | 51.13586 | -0.1726 | 7.20400 |
August | 514.00000 | 24.42110 | 48.25760 | -0.2199 | 7.51102 |
September | 485.00000 | 24.42592 | 45.12870 | -0.2135 | 8.63701 |
October | 502.00000 | 24.00255 | 36.53188 | 0.41488 | 11.36973 |
November | 489.00000 | 23.16467 | 22.85974 | 0.06556 | 10.04176 |
December | 497.00000 | 22.41378 | 19.00317 | -0.1943 | 11.00898 |
Annual Sum or Average | 5943.00000 | 23.67347 | 30.67396 | -0.0906 | 9.36828 |
Minimum of Months | 454.00000 | 22.41378 | 16.95083 | -0.4671 | 7.20400 |
Maximum of Months | 514.00000 | 24.51933 | 51.13586 | 0.41488 | 11.73699 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.54577 | 23.46011 | -0.4247 | 12.01131 |
February | 454.00000 | 22.19882 | 19.81136 | -0.2688 | 9.74000 |
March | 514.00000 | 22.95365 | 17.57241 | -0.0561 | 8.08161 |
April | 485.00000 | 24.00741 | 20.49806 | 0.29239 | 9.02291 |
May | 508.00000 | 24.39566 | 29.29949 | -0.3164 | 10.10424 |
June | 496.00000 | 24.54638 | 36.09552 | -0.1545 | 7.80846 |
July | 497.00000 | 24.65134 | 50.56898 | -0.0356 | 7.54971 |
August | 514.00000 | 24.52101 | 47.91741 | -0.1226 | 7.60624 |
September | 485.00000 | 24.39463 | 45.37089 | -0.2195 | 8.48981 |
October | 502.00000 | 23.83165 | 37.38856 | 0.33566 | 9.42874 |
November | 489.00000 | 22.44415 | 24.30495 | -0.1600 | 9.31809 |
December | 497.00000 | 21.41034 | 20.73348 | -0.4825 | 13.12944 |
Annual Sum or Average | 5943.00000 | 23.41756 | 31.17257 | -0.1340 | 9.35254 |
Minimum of Months | 454.00000 | 21.41034 | 17.57241 | -0.4825 | 7.54971 |
Maximum of Months | 514.00000 | 24.65134 | 50.56898 | 0.33566 | 13.12944 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.109282E+11 | 72812.25 | 12-JAN-15:05 | 197.77 | 0.577107E+11 | 0.00 | 0.686389E+11 | 1.25 | 7.44 | 12-JAN-15:05 | 0.00 | 0.00 |
February | 0.217543E+11 | 91554.45 | 21-FEB-15:05 | 220.41 | 0.124339E+12 | 0.00 | 0.146093E+12 | 1.65 | 7.80 | 21-FEB-15:05 | 0.00 | 0.00 |
March | 0.431540E+11 | 133464.15 | 21-MAR-16:00 | 303.28 | 0.271998E+12 | 0.00 | 0.315152E+12 | 2.25 | 7.95 | 22-MAR-13:50 | 0.00 | 0.00 |
April | 0.830727E+11 | 138979.37 | 28-APR-13:30 | 472.84 | 0.576696E+12 | 0.00 | 0.659769E+12 | 3.94 | 7.95 | 24-APR-13:05 | 0.00 | 0.00 |
May | 0.126864E+12 | 143570.80 | 18-MAY-13:05 | 511.50 | 0.925254E+12 | 0.00 | 0.105212E+13 | 4.65 | 7.95 | 09-MAY-13:05 | 0.00 | 0.00 |
June | 0.152703E+12 | 143534.30 | 20-JUN-10:00 | 612.51 | 0.112612E+13 | 0.00 | 0.127882E+13 | 5.74 | 7.95 | 15-JUN-05:04 | 0.00 | 0.00 |
July | 0.167226E+12 | 157050.32 | 21-JUL-10:25 | 679.48 | 0.121036E+13 | 0.00 | 0.137758E+13 | 5.99 | 7.94 | 01-JUL-05:04 | 0.00 | 0.00 |
August | 0.158714E+12 | 145905.16 | 05-AUG-14:20 | 679.29 | 0.115788E+13 | 0.00 | 0.131660E+13 | 5.96 | 7.95 | 22-AUG-18:05 | 0.00 | 0.00 |
September | 0.126604E+12 | 145078.95 | 16-SEP-14:30 | 482.58 | 0.926392E+12 | 0.00 | 0.105300E+13 | 4.57 | 7.95 | 28-SEP-11:30 | 0.00 | 0.00 |
October | 0.817486E+11 | 143565.60 | 03-OCT-10:35 | 401.37 | 0.569381E+12 | 0.00 | 0.651130E+12 | 3.32 | 7.95 | 30-OCT-15:20 | 0.00 | 0.00 |
November | 0.343431E+11 | 114827.31 | 09-NOV-16:00 | 257.28 | 0.220923E+12 | 0.00 | 0.255266E+12 | 1.98 | 7.94 | 09-NOV-16:00 | 0.00 | 0.00 |
December | 0.843681E+10 | 57588.34 | 07-DEC-15:10 | 213.75 | 0.396794E+11 | 0.00 | 0.481162E+11 | 1.30 | 6.81 | 07-DEC-15:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101555E+13 | 5032.07 | 0.720673E+13 | 0.00 | 0.822228E+13 | 3.56 | 0.00 | 0.00 | ||||
Minimum of Months | 0.843681E+10 | 57588.34 | 197.77 | 0.396794E+11 | 0.00 | 0.481162E+11 | 1.25 | 6.81 | 0.00 | 0.00 | ||
Maximum of Months | 0.167226E+12 | 157050.32 | 679.48 | 0.121036E+13 | 0.00 | 0.137758E+13 | 5.99 | 7.95 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.100848E+11 | 103787.41 | 27-APR-13:35 | 36.25 | 0.760520E+11 | 0.00 | 0.861368E+11 | 0.38 | 7.87 | 27-APR-15:55 | 0.00 | 0.00 |
May | 0.265581E+11 | 134250.41 | 18-MAY-13:13 | 93.33 | 0.200896E+12 | 0.00 | 0.227454E+12 | 0.94 | 7.94 | 30-MAY-08:13 | 0.00 | 0.00 |
June | 0.514449E+11 | 136263.01 | 20-JUN-09:43 | 170.13 | 0.392061E+12 | 0.00 | 0.443506E+12 | 1.79 | 7.93 | 13-JUN-08:53 | 0.00 | 0.00 |
July | 0.692461E+11 | 157050.32 | 21-JUL-10:25 | 211.43 | 0.516017E+12 | 0.00 | 0.585263E+12 | 2.11 | 7.81 | 20-JUL-05:02 | 0.00 | 0.00 |
August | 0.469755E+11 | 137476.38 | 03-AUG-05:05 | 148.04 | 0.354144E+12 | 0.00 | 0.401120E+12 | 1.49 | 7.95 | 22-AUG-17:40 | 0.00 | 0.00 |
September | 0.362846E+11 | 139912.06 | 29-SEP-12:52 | 117.66 | 0.274325E+12 | 0.00 | 0.310610E+12 | 1.23 | 7.94 | 25-SEP-15:53 | 0.00 | 0.00 |
October | 0.749971E+10 | 130121.95 | 03-OCT-10:43 | 23.86 | 0.567825E+11 | 0.00 | 0.642822E+11 | 0.24 | 7.86 | 02-OCT-10:13 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.248094E+12 | 800.70 | 0.187028E+13 | 0.00 | 0.211837E+13 | 0.69 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.692461E+11 | 157050.32 | 211.43 | 0.516017E+12 | 0.00 | 0.585263E+12 | 2.11 | 7.95 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.562511E+10 | 744.00 | 43776.24 | 03-JAN-12:40 | 44835.88 | 12-JAN-16:30 | 18.85 | 18.35 | 15.09 |
February | 0.211013E+11 | 672.00 | 43776.24 | 04-FEB-14:40 | 235727.01 | 20-FEB-16:00 | 19.96 | 18.71 | 15.09 |
March | 0.428538E+11 | 744.00 | 43776.24 | 03-MAR-12:10 | 453846.50 | 21-MAR-16:00 | 22.11 | 19.50 | 15.09 |
April | 0.915876E+11 | 720.00 | 43776.24 | 01-APR-08:00 | 684055.57 | 29-APR-17:03 | 32.01 | 24.62 | 15.09 |
May | 0.102981E+12 | 744.00 | 43776.24 | 01-MAY-00:03 | 321728.36 | 31-MAY-23:20 | 27.86 | 25.47 | 15.09 |
June | 0.112779E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 520202.51 | 30-JUN-23:55 | 37.29 | 31.15 | 15.09 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:03 | 729955.48 | 20-JUL-15:00 | 44.53 | 33.49 | 15.09 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 734112.58 | 01-AUG-20:45 | 45.41 | 32.98 | 15.09 |
September | 0.992046E+11 | 720.00 | 43776.24 | 01-SEP-00:10 | 341773.42 | 01-SEP-10:30 | 27.43 | 25.04 | 15.09 |
October | 0.701118E+11 | 744.00 | 43776.24 | 01-OCT-07:53 | 484233.74 | 04-OCT-11:30 | 24.41 | 21.66 | 15.09 |
November | 0.328860E+11 | 720.00 | 43776.24 | 02-NOV-13:20 | 428085.81 | 03-NOV-16:00 | 21.22 | 18.96 | 15.09 |
December | 0.191183E+11 | 744.00 | 43776.24 | 07-DEC-14:15 | 345022.31 | 10-DEC-15:00 | 20.82 | 18.38 | 15.09 |
Annual Sum or Average | 0.832749E+12 | 8760.00 | 28.55 | 24.06 | 15.09 | ||||
Minimum of Months | 0.562511E+10 | 672.00 | 43776.24 | 44835.88 | 18.85 | 18.35 | 15.09 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 734112.58 | 45.41 | 33.49 | 15.09 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 15467685.98 | 35.33 | 560.83 | 12-JAN-15:40 | 625244.46 | 12-JAN-15:10 | 21.07 | 20.94 | 6.94 |
February | 45841578.73 | 98.03 | 619.70 | 21-FEB-15:00 | 812408.20 | 21-FEB-15:10 | 21.25 | 20.97 | 12.29 |
March | 0.159767E+09 | 187.62 | 1651.19 | 14-MAR-16:00 | 1202264.45 | 21-MAR-16:00 | 21.57 | 21.02 | 17.95 |
April | 0.103711E+10 | 326.53 | 15210.12 | 18-APR-15:40 | 1236452.43 | 26-APR-16:00 | 22.30 | 21.09 | 29.33 |
May | 0.546963E+10 | 458.51 | 15210.12 | 08-MAY-11:40 | 1236016.37 | 08-MAY-09:30 | 23.36 | 21.50 | 35.62 |
June | 0.121408E+11 | 529.22 | 15210.12 | 01-JUN-15:30 | 1241997.12 | 23-JUN-13:50 | 23.74 | 21.39 | 42.96 |
July | 0.253384E+11 | 648.81 | 15210.12 | 01-JUL-05:06 | 1256773.81 | 21-JUL-10:25 | 24.72 | 22.39 | 47.42 |
August | 0.188508E+11 | 581.24 | 15210.12 | 01-AUG-05:07 | 1198022.73 | 25-AUG-12:00 | 24.00 | 21.76 | 45.96 |
September | 0.132764E+11 | 452.31 | 15210.12 | 01-SEP-06:50 | 1237492.20 | 25-SEP-15:00 | 23.70 | 21.82 | 35.21 |
October | 0.418701E+10 | 332.27 | 15210.12 | 02-OCT-09:05 | 1242260.40 | 17-OCT-15:00 | 22.41 | 21.30 | 26.94 |
November | 0.199467E+09 | 152.13 | 2407.35 | 03-NOV-16:00 | 1034558.57 | 09-NOV-15:00 | 21.47 | 21.01 | 14.52 |
December | 4136274.71 | 19.92 | 167.92 | 07-DEC-15:10 | 460925.18 | 07-DEC-15:10 | 21.01 | 20.91 | 6.50 |
Annual Sum or Average | 0.807248E+11 | 3821.93 | 22.56 | 21.34 | 26.88 | ||||
Minimum of Months | 4136274.71 | 19.92 | 167.92 | 460925.18 | 21.01 | 20.91 | 6.50 | ||
Maximum of Months | 0.253384E+11 | 648.81 | 15210.12 | 1256773.81 | 24.72 | 22.39 | 47.42 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.07 | 21.07 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.25 | 21.25 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.57 | 21.57 | 0.00 |
April | 0.216961E+09 | 24.33 | 15210.12 | 21-APR-13:50 | 1114440.84 | 28-APR-12:50 | 22.30 | 22.15 | 1.82 |
May | 0.178893E+10 | 72.83 | 15210.12 | 08-MAY-12:30 | 1096686.63 | 25-MAY-13:45 | 23.36 | 22.96 | 5.25 |
June | 0.536823E+10 | 154.99 | 15210.12 | 01-JUN-15:30 | 1160039.04 | 22-JUN-15:33 | 23.74 | 22.89 | 11.42 |
July | 0.137463E+11 | 251.19 | 15210.12 | 01-JUL-09:40 | 1256773.81 | 21-JUL-10:25 | 24.72 | 23.43 | 16.68 |
August | 0.822457E+10 | 155.10 | 15210.12 | 01-AUG-07:25 | 1121353.09 | 02-AUG-08:20 | 24.00 | 23.22 | 10.81 |
September | 0.600051E+10 | 123.33 | 15210.12 | 01-SEP-07:20 | 1159705.67 | 20-SEP-16:53 | 23.70 | 23.05 | 8.85 |
October | 0.136587E+10 | 24.94 | 15210.12 | 02-OCT-10:10 | 1065861.48 | 18-OCT-12:32 | 22.41 | 22.28 | 1.73 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.47 | 21.47 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.01 | 21.01 | 0.00 |
Annual Sum or Average | 0.367114E+11 | 806.72 | 22.56 | 22.20 | 4.74 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 21.01 | 0.00 | ||
Maximum of Months | 0.137463E+11 | 251.19 | 15210.12 | 1256773.81 | 24.72 | 23.43 | 16.68 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.843286E+11 | 0.00 | 299.24 | 1274289.81 | 26-JAN-05:01 | 0.00 | 34.60 | 44.63 | 0.35 | 0.00 | 0.02 | 0.68 | 26-JAN-05:01 |
February | 0.505204E+11 | 0.00 | 215.15 | 1131863.19 | 17-FEB-06:01 | 0.00 | 33.78 | 41.78 | 0.24 | 0.00 | 0.01 | 0.61 | 17-FEB-06:01 |
March | 0.271363E+11 | 0.00 | 137.96 | 1045115.01 | 02-MAR-06:01 | 0.00 | 33.77 | 38.40 | 0.11 | 0.00 | 0.01 | 0.56 | 02-MAR-06:01 |
April | 0.221277E+10 | 0.00 | 27.12 | 302091.17 | 11-APR-05:03 | 0.00 | 32.67 | 33.66 | 0.01 | 0.00 | 0.00 | 0.16 | 11-APR-05:03 |
May | 4148772.43 | 0.00 | 1.00 | 2479.96 | 02-MAY-06:10 | 0.00 | 31.45 | 31.49 | 0.00 | 0.00 | 0.00 | 0.00 | 02-MAY-06:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 31.44 | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 31.44 | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 31.44 | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 14726803.95 | 0.00 | 1.00 | 15613.82 | 30-SEP-06:10 | 0.00 | 31.44 | 31.48 | 0.00 | 0.00 | 0.00 | 0.01 | 30-SEP-06:10 |
October | 0.824351E+09 | 0.00 | 28.81 | 178103.78 | 24-OCT-10:00 | 0.00 | 31.11 | 32.23 | 0.00 | 0.00 | 0.00 | 0.10 | 24-OCT-10:00 |
November | 0.305665E+11 | 0.00 | 175.39 | 1497639.98 | 27-NOV-05:11 | 0.00 | 33.38 | 39.65 | 0.12 | 0.00 | 0.01 | 0.80 | 27-NOV-05:11 |
December | 0.111552E+12 | 0.00 | 343.19 | 1273360.12 | 26-DEC-05:01 | 0.00 | 34.56 | 45.71 | 0.49 | 0.00 | 0.02 | 0.68 | 26-DEC-05:01 |
Annual Sum or Average | 0.307160E+12 | 0.00 | 1228.86 | 0.00 | 32.58 | 36.09 | 0.11 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.111552E+12 | 0.00 | 343.19 | 1497639.98 | 0.00 | 34.60 | 45.71 | 0.49 | 0.00 | 0.02 | 0.80 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.96 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 22.11 | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 32.01 | 32.01 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 27.86 | 27.86 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 37.29 | 37.29 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 44.53 | 44.53 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 45.41 | 45.41 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 27.43 | 27.43 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.41 | 24.41 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 21.22 | 21.22 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.82 | 20.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 28.55 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.41 | 45.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.142286E+11 | 0.00 | 173.99 | 0.142286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60758.45 | 03-JAN-14:05 | 60758.45 | 03-JAN-14:05 | 0.00 | 0.00 | 0.00 |
February | 0.155526E+11 | 0.00 | 193.67 | 0.155526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73726.74 | 21-FEB-16:00 | 73726.74 | 21-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.264681E+11 | 0.00 | 271.93 | 0.264681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87241.75 | 21-MAR-15:30 | 87241.75 | 21-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.654378E+11 | 0.00 | 450.13 | 0.654378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116277.72 | 21-APR-14:50 | 116277.72 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.955172E+11 | 0.00 | 491.14 | 0.950325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131374.00 | 18-MAY-13:55 | 126762.71 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.134090E+12 | 0.00 | 585.87 | 0.132723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 146247.39 | 09-JUN-12:43 | 141013.96 | 27-JUN-14:23 | 0.00 | 0.00 | 0.00 |
July | 0.166229E+12 | 0.00 | 640.87 | 0.136849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 210738.67 | 21-JUL-10:00 | 139316.87 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.158421E+12 | 0.00 | 655.06 | 0.142893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 198590.04 | 02-AUG-08:30 | 146518.69 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.106334E+12 | 0.00 | 462.11 | 0.963089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180347.16 | 14-SEP-09:50 | 143046.98 | 19-SEP-13:23 | 0.00 | 0.00 | 0.00 |
October | 0.592378E+11 | 0.00 | 372.05 | 0.563729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143832.62 | 02-OCT-10:17 | 121388.57 | 02-OCT-10:17 | 0.00 | 0.00 | 0.00 |
November | 0.211404E+11 | 0.00 | 220.24 | 0.211404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80748.18 | 03-NOV-16:00 | 80748.18 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.144029E+11 | 0.00 | 180.90 | 0.144029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58750.74 | 20-DEC-15:00 | 58750.74 | 20-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877060E+12 | 0.00 | 4697.96 | 0.817409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.142286E+11 | 0.00 | 173.99 | 0.142286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58750.74 | 58750.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.166229E+12 | 0.00 | 655.06 | 0.142893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 210738.67 | 146518.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.389778E+11 | 0.00 | 106.05 | 0.389778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 450849.94 | 12-JAN-15:05 | 450849.94 | 12-JAN-15:05 | 0.00 | 0.00 | 0.00 |
February | 0.971860E+11 | 0.00 | 162.75 | 0.971860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 570237.30 | 21-FEB-15:05 | 570237.30 | 21-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.215336E+12 | 0.00 | 264.38 | 0.215336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 672026.81 | 21-MAR-16:00 | 672026.81 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.475894E+12 | 0.00 | 366.93 | 0.475894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1015469.86 | 21-APR-15:00 | 1015469.86 | 21-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.844993E+12 | 0.00 | 471.15 | 0.841084E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1230948.14 | 18-MAY-13:55 | 1171732.19 | 18-MAY-13:55 | 0.00 | 0.00 | 0.00 |
June | 0.115439E+13 | 0.00 | 502.30 | 0.114489E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1368972.85 | 09-JUN-12:43 | 1330415.39 | 09-JUN-12:43 | 0.00 | 0.00 | 0.00 |
July | 0.129295E+13 | 0.00 | 511.20 | 0.108419E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1893185.34 | 21-JUL-10:10 | 1229870.27 | 03-JUL-14:05 | 0.00 | 0.00 | 0.00 |
August | 0.112849E+13 | 0.00 | 512.76 | 0.103609E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1716832.35 | 03-AUG-05:03 | 1298456.58 | 22-AUG-16:22 | 0.00 | 0.00 | 0.00 |
September | 0.911260E+12 | 0.00 | 433.84 | 0.827154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1509527.87 | 14-SEP-09:50 | 1339739.08 | 19-SEP-13:23 | 0.00 | 0.00 | 0.00 |
October | 0.474743E+12 | 0.00 | 355.32 | 0.451973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1177815.66 | 03-OCT-14:05 | 1015393.71 | 03-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.177075E+12 | 0.00 | 209.14 | 0.177075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 658041.12 | 09-NOV-15:05 | 658041.12 | 09-NOV-15:05 | 0.00 | 0.00 | 0.00 |
December | 0.222774E+11 | 0.00 | 88.73 | 0.222774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339195.24 | 07-DEC-15:05 | 339195.24 | 07-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.683356E+13 | 0.00 | 3984.56 | 0.641212E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.222774E+11 | 0.00 | 88.73 | 0.222774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 339195.24 | 339195.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129295E+13 | 0.00 | 512.76 | 0.114489E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1893185.34 | 1339739.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.132960E+10 | 0.00 | 50.33 | 0.132960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27187.72 | 12-JAN-15:00 | 27187.72 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.554194E+10 | 0.00 | 111.00 | 0.554194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44195.18 | 21-FEB-16:20 | 44195.18 | 21-FEB-16:20 | 0.00 | 0.00 | 0.00 |
March | 0.147487E+11 | 0.00 | 214.52 | 0.147487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69177.67 | 21-MAR-16:00 | 69177.67 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.502089E+11 | 0.00 | 355.48 | 0.502089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119627.39 | 28-APR-14:00 | 119627.39 | 28-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.938672E+11 | 0.00 | 467.69 | 0.934738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141551.08 | 18-MAY-13:55 | 137820.87 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.132122E+12 | 0.00 | 510.74 | 0.131154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 159493.73 | 27-JUN-14:23 | 159493.73 | 27-JUN-14:23 | 0.00 | 0.00 | 0.00 |
July | 0.146506E+12 | 0.00 | 519.37 | 0.124736E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243243.79 | 20-JUL-15:20 | 149629.59 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.125785E+12 | 0.00 | 516.78 | 0.116676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 189571.68 | 03-AUG-05:03 | 153118.91 | 22-AUG-16:22 | 0.00 | 0.00 | 0.00 |
September | 0.977019E+11 | 0.00 | 432.70 | 0.898605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163889.96 | 14-SEP-10:00 | 157519.29 | 19-SEP-13:23 | 0.00 | 0.00 | 0.00 |
October | 0.466181E+11 | 0.00 | 344.11 | 0.445965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133597.61 | 03-OCT-14:00 | 116670.00 | 03-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.991722E+10 | 0.00 | 162.54 | 0.991722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66585.84 | 09-NOV-15:20 | 66585.84 | 09-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.456439E+09 | 0.00 | 32.06 | 0.456439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10132.50 | 20-DEC-15:00 | 10132.50 | 20-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724803E+12 | 0.00 | 3717.32 | 0.682700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.456439E+09 | 0.00 | 32.06 | 0.456439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10132.50 | 10132.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.146506E+12 | 0.00 | 519.37 | 0.131154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243243.79 | 159493.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.113956E+10 | 0.00 | 26.76 | 0.113956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28386.17 | 03-JAN-15:00 | 28386.17 | 03-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.397658E+10 | 0.00 | 56.88 | 0.397658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49384.43 | 21-FEB-15:00 | 49384.43 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.101668E+11 | 0.00 | 139.14 | 0.101668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45398.77 | 21-MAR-16:00 | 45398.77 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.315507E+11 | 0.00 | 268.13 | 0.315507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56495.91 | 10-APR-12:10 | 56495.91 | 10-APR-12:10 | 0.00 | 0.00 | 0.00 |
May | 0.550326E+11 | 0.00 | 378.38 | 0.549733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79036.72 | 31-MAY-03:02 | 79036.72 | 31-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.707180E+11 | 0.00 | 407.48 | 0.705391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79805.34 | 26-JUN-10:43 | 79314.97 | 15-JUN-04:03 | 0.00 | 0.00 | 0.00 |
July | 0.860818E+11 | 0.00 | 407.42 | 0.731545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116793.29 | 21-JUL-10:00 | 80158.31 | 03-JUL-03:13 | 0.00 | 0.00 | 0.00 |
August | 0.847099E+11 | 0.00 | 455.89 | 0.780174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107340.75 | 02-AUG-08:00 | 82380.92 | 07-AUG-02:12 | 0.00 | 0.00 | 0.00 |
September | 0.668446E+11 | 0.00 | 388.74 | 0.624786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100896.82 | 10-SEP-15:30 | 80114.93 | 03-SEP-14:42 | 0.00 | 0.00 | 0.00 |
October | 0.370750E+11 | 0.00 | 294.42 | 0.358037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85477.66 | 01-OCT-15:52 | 85477.66 | 01-OCT-15:52 | 0.00 | 0.00 | 0.00 |
November | 0.965938E+10 | 0.00 | 130.32 | 0.965725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50528.73 | 08-NOV-15:00 | 50528.73 | 08-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.226141E+09 | 0.00 | 14.20 | 0.226141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14926.14 | 11-DEC-05:11 | 14926.14 | 11-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457181E+12 | 0.00 | 2967.77 | 0.431684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.226141E+09 | 0.00 | 14.20 | 0.226141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14926.14 | 14926.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.860818E+11 | 0.00 | 455.89 | 0.780174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116793.29 | 85477.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100974E+11 | 0.475704E+10 | 729.00 | 0.906317E+10 | 0.103427E+10 | 0.00 | 0.03 | 03-JAN-17:00 | 0.00 | 15-JAN-11:00 | 5407.46 | 09-JAN-10:40 | 4913.09 | 01-JAN-03:43 | 541.65 | 09-JAN-23:00 | 2423.07 | 03-JAN-17:00 | 0.00 |
February | 0.257215E+11 | 0.977409E+10 | 658.33 | 0.250881E+11 | 0.633333E+09 | 0.00 | 0.42 | 20-FEB-16:00 | 0.00 | 28-FEB-01:00 | 128815.61 | 20-FEB-16:00 | 128815.61 | 20-FEB-16:00 | 1009.80 | 17-FEB-05:01 | 43030.07 | 20-FEB-16:00 | 0.00 |
March | 0.112791E+12 | 0.366062E+11 | 733.59 | 0.112474E+12 | 0.317471E+09 | 0.00 | 0.81 | 22-MAR-13:00 | 0.00 | 11-MAR-06:02 | 265852.02 | 21-MAR-16:00 | 265852.02 | 21-MAR-16:00 | 5558.59 | 11-MAR-16:00 | 90972.78 | 22-MAR-13:00 | 0.00 |
April | 0.540006E+12 | 0.170577E+12 | 720.00 | 0.522615E+12 | 0.173914E+11 | 0.00 | 1.00 | 01-APR-11:40 | 0.03 | 30-APR-23:53 | 410813.74 | 29-APR-17:08 | 394259.99 | 29-APR-12:30 | 105076.76 | 17-APR-02:00 | 135941.53 | 21-APR-15:00 | 0.00 |
May | 0.178689E+12 | 0.604691E+11 | 690.22 | 0.170561E+12 | 0.812766E+10 | 0.00 | 0.56 | 31-MAY-23:10 | 0.01 | 26-MAY-04:30 | 194312.70 | 31-MAY-23:10 | 194312.70 | 31-MAY-23:10 | 57259.52 | 24-MAY-12:05 | 63061.39 | 31-MAY-23:10 | 0.00 |
June | 0.497609E+12 | 0.165621E+12 | 711.84 | 0.454782E+12 | 0.428273E+11 | 0.00 | 0.82 | 30-JUN-23:55 | 0.01 | 25-JUN-04:30 | 352125.49 | 03-JUN-17:43 | 307525.45 | 30-JUN-24:00 | 137766.12 | 19-JUN-18:10 | 101034.40 | 30-JUN-23:20 | 0.00 |
July | 0.100517E+13 | 0.298734E+12 | 744.00 | 0.711929E+12 | 0.293240E+12 | 0.00 | 1.00 | 02-JUL-07:23 | 0.42 | 05-JUL-06:00 | 491126.63 | 20-JUL-15:00 | 390058.57 | 31-JUL-23:22 | 354292.50 | 20-JUL-21:55 | 136214.40 | 21-JUL-18:00 | 0.00 |
August | 0.111058E+13 | 0.323686E+12 | 744.00 | 0.827770E+12 | 0.282814E+12 | 0.00 | 1.00 | 01-AUG-00:05 | 0.14 | 31-AUG-23:07 | 465737.79 | 01-AUG-21:12 | 410838.05 | 27-AUG-12:33 | 297277.14 | 02-AUG-05:00 | 149460.29 | 07-AUG-16:05 | 0.00 |
September | 0.173029E+12 | 0.562813E+11 | 588.52 | 0.147632E+12 | 0.253975E+11 | 0.00 | 0.55 | 01-SEP-10:30 | 0.00 | 11-SEP-04:53 | 235921.74 | 01-SEP-10:30 | 139365.40 | 01-SEP-13:05 | 97864.58 | 01-SEP-10:30 | 64709.92 | 01-SEP-10:30 | 0.00 |
October | 0.172793E+12 | 0.527341E+11 | 611.41 | 0.144351E+12 | 0.284423E+11 | 0.00 | 0.76 | 04-OCT-11:30 | 0.00 | 06-OCT-20:20 | 322777.54 | 04-OCT-11:30 | 226504.20 | 03-OCT-14:00 | 133339.06 | 03-OCT-20:00 | 90632.28 | 04-OCT-11:30 | 0.00 |
November | 0.768754E+11 | 0.241547E+11 | 693.99 | 0.722122E+11 | 0.466314E+10 | 0.00 | 0.68 | 08-NOV-15:00 | 0.01 | 03-NOV-05:00 | 253170.62 | 03-NOV-16:00 | 239803.32 | 08-NOV-15:00 | 49067.52 | 03-NOV-11:50 | 75209.13 | 03-NOV-16:00 | 0.00 |
December | 0.556462E+11 | 0.182666E+11 | 744.00 | 0.538135E+11 | 0.183268E+10 | 0.00 | 0.58 | 20-DEC-15:00 | 0.02 | 13-DEC-01:00 | 183561.32 | 10-DEC-15:00 | 183561.32 | 10-DEC-15:00 | 12773.78 | 25-DEC-14:53 | 54314.70 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.395901E+13 | 0.122166E+13 | 8368.91 | 0.325229E+13 | 0.706721E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.100974E+11 | 0.475704E+10 | 588.52 | 0.906317E+10 | 0.317471E+09 | 0.00 | 0.03 | 0.00 | 5407.46 | 4913.09 | 541.65 | 2423.07 | 0.00 | ||||||
Maximum of Months | 0.111058E+13 | 0.323686E+12 | 744.00 | 0.827770E+12 | 0.293240E+12 | 0.00 | 1.00 | 0.42 | 491126.63 | 410838.05 | 354292.50 | 149460.29 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.476666E+10 | 0.113019E+10 | 744.00 | 0.475311E+10 | 13556591.88 | 0.00 | 0.34 | 01-JAN-16:53 | 0.15 | 28-JAN-07:40 | 2698.30 | 01-JAN-16:53 | 2691.27 | 01-JAN-16:57 | 92.77 | 12-JAN-17:00 | 600.64 | 01-JAN-16:53 | 0.00 |
February | 0.919311E+10 | 0.209621E+10 | 672.00 | 0.917754E+10 | 15571059.35 | 0.00 | 0.61 | 20-FEB-17:13 | 0.40 | 01-FEB-07:40 | 4761.46 | 20-FEB-17:25 | 4761.46 | 20-FEB-17:25 | 219.02 | 13-FEB-16:10 | 1244.48 | 20-FEB-16:52 | 0.00 |
March | 0.155634E+11 | 0.346295E+10 | 744.00 | 0.155598E+11 | 3597977.95 | 0.00 | 0.91 | 31-MAR-24:00 | 0.61 | 01-MAR-07:03 | 7675.81 | 31-MAR-24:00 | 7675.81 | 31-MAR-24:00 | 112.53 | 11-MAR-10:15 | 1846.44 | 21-MAR-16:00 | 0.00 |
April | 0.202763E+11 | 0.509499E+10 | 720.00 | 0.202586E+11 | 17673444.66 | 0.00 | 1.00 | 01-APR-11:40 | 0.34 | 30-APR-24:00 | 8425.33 | 22-APR-18:35 | 8425.33 | 22-APR-18:35 | 155.42 | 18-APR-11:00 | 2771.16 | 21-APR-15:00 | 0.00 |
May | 0.617236E+10 | 0.178038E+10 | 744.00 | 0.611132E+10 | 61040315.73 | 0.00 | 0.52 | 31-MAY-23:20 | 0.23 | 06-MAY-06:05 | 4059.54 | 31-MAY-24:00 | 4052.33 | 31-MAY-24:00 | 266.33 | 24-MAY-13:10 | 1203.39 | 31-MAY-23:20 | 0.00 |
June | 0.110927E+11 | 0.353766E+10 | 720.00 | 0.109822E+11 | 0.110556E+09 | 0.00 | 0.76 | 30-JUN-23:55 | 0.47 | 13-JUN-06:10 | 5930.12 | 30-JUN-23:55 | 5930.12 | 30-JUN-23:55 | 321.32 | 19-JUN-18:00 | 1979.04 | 02-JUN-16:00 | 0.00 |
July | 0.167502E+11 | 0.532424E+10 | 744.00 | 0.164236E+11 | 0.326575E+09 | 0.00 | 0.97 | 31-JUL-23:35 | 0.70 | 05-JUL-06:10 | 7902.28 | 31-JUL-23:55 | 7889.86 | 31-JUL-24:00 | 614.78 | 20-JUL-15:00 | 2706.86 | 02-JUL-16:01 | 0.00 |
August | 0.216445E+11 | 0.652775E+10 | 744.00 | 0.213733E+11 | 0.271138E+09 | 0.00 | 1.00 | 01-AUG-09:05 | 0.34 | 31-AUG-24:00 | 8497.90 | 13-AUG-23:15 | 8407.75 | 13-AUG-23:15 | 472.69 | 01-AUG-20:55 | 3040.27 | 07-AUG-16:05 | 0.00 |
September | 0.621264E+10 | 0.173657E+10 | 720.00 | 0.600044E+10 | 0.212201E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.23 | 30-SEP-06:30 | 4052.64 | 30-SEP-24:00 | 4052.64 | 30-SEP-24:00 | 361.88 | 22-SEP-09:05 | 1042.21 | 01-SEP-17:40 | 0.00 |
October | 0.111225E+11 | 0.267554E+10 | 744.00 | 0.109627E+11 | 0.159787E+09 | 0.00 | 0.70 | 31-OCT-24:00 | 0.44 | 25-OCT-07:00 | 5841.98 | 31-OCT-24:00 | 5841.98 | 31-OCT-24:00 | 384.21 | 04-OCT-09:50 | 1655.40 | 01-OCT-15:05 | 0.00 |
November | 0.151373E+11 | 0.325486E+10 | 720.00 | 0.150968E+11 | 40506804.25 | 0.00 | 0.81 | 19-NOV-16:45 | 0.62 | 28-NOV-07:05 | 6698.80 | 12-NOV-16:40 | 6691.34 | 12-NOV-16:35 | 243.74 | 02-NOV-15:50 | 1751.77 | 03-NOV-16:00 | 0.00 |
December | 0.203213E+11 | 0.421082E+10 | 744.00 | 0.203150E+11 | 6385498.64 | 0.00 | 0.99 | 17-DEC-16:43 | 0.82 | 05-DEC-07:03 | 8369.50 | 17-DEC-16:47 | 8369.50 | 17-DEC-16:47 | 91.34 | 14-DEC-15:05 | 1827.35 | 10-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.158253E+12 | 0.408322E+11 | 8760.00 | 0.157014E+12 | 0.123859E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.476666E+10 | 0.113019E+10 | 672.00 | 0.475311E+10 | 3597977.95 | 0.00 | 0.34 | 0.15 | 2698.30 | 2691.27 | 91.34 | 600.64 | 0.00 | ||||||
Maximum of Months | 0.216445E+11 | 0.652775E+10 | 744.00 | 0.213733E+11 | 0.326575E+09 | 0.00 | 1.00 | 0.82 | 8497.90 | 8425.33 | 614.78 | 3040.27 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.306414E+11 | 0.750209E+10 | 744.00 | 0.305171E+11 | 0.124254E+09 | 0.00 | 0.29 | 30-JAN-17:00 | 0.05 | 28-JAN-07:10 | 21787.00 | 12-JAN-16:50 | 21387.04 | 30-JAN-17:00 | 898.44 | 12-JAN-17:00 | 5049.13 | 03-JAN-17:00 | 0.00 |
February | 0.772245E+11 | 0.178338E+11 | 672.00 | 0.770710E+11 | 0.153514E+09 | 0.00 | 0.57 | 19-FEB-17:22 | 0.31 | 02-FEB-07:10 | 42421.93 | 19-FEB-17:24 | 42421.93 | 19-FEB-17:24 | 2154.32 | 13-FEB-16:20 | 11153.58 | 19-FEB-17:13 | 0.00 |
March | 0.140582E+12 | 0.315296E+11 | 744.00 | 0.140545E+12 | 36501070.43 | 0.00 | 0.89 | 31-MAR-23:40 | 0.54 | 01-MAR-07:03 | 71390.76 | 31-MAR-23:40 | 71390.76 | 31-MAR-23:40 | 1117.36 | 11-MAR-10:15 | 17470.04 | 21-MAR-16:00 | 0.00 |
April | 0.190844E+12 | 0.481520E+11 | 720.00 | 0.190667E+12 | 0.177827E+09 | 0.00 | 1.00 | 01-APR-12:05 | 0.30 | 30-APR-24:00 | 80040.42 | 22-APR-18:23 | 80040.42 | 22-APR-18:23 | 1554.11 | 18-APR-11:00 | 26458.39 | 21-APR-15:00 | 0.00 |
May | 0.569633E+11 | 0.165252E+11 | 744.00 | 0.563615E+11 | 0.601744E+09 | 0.00 | 0.53 | 31-MAY-24:00 | 0.20 | 02-MAY-06:05 | 39461.55 | 31-MAY-24:00 | 39415.02 | 31-MAY-24:00 | 2636.59 | 24-MAY-13:10 | 11633.38 | 31-MAY-23:20 | 0.00 |
June | 0.105529E+12 | 0.336826E+11 | 720.00 | 0.104432E+12 | 0.109705E+10 | 0.00 | 0.77 | 30-JUN-23:55 | 0.46 | 29-JUN-06:10 | 57537.54 | 30-JUN-23:55 | 57537.54 | 30-JUN-23:55 | 3161.74 | 19-JUN-18:00 | 18937.44 | 02-JUN-16:00 | 0.00 |
July | 0.159356E+12 | 0.506721E+11 | 744.00 | 0.156100E+12 | 0.325601E+10 | 0.00 | 0.98 | 31-JUL-23:43 | 0.70 | 05-JUL-06:10 | 75885.92 | 31-JUL-23:55 | 75760.49 | 31-JUL-24:00 | 6112.29 | 20-JUL-15:00 | 25549.84 | 02-JUL-16:11 | 0.00 |
August | 0.204257E+12 | 0.618215E+11 | 744.00 | 0.201540E+12 | 0.271739E+10 | 0.00 | 1.00 | 01-AUG-09:00 | 0.30 | 31-AUG-24:00 | 80339.74 | 08-AUG-17:00 | 78784.27 | 27-AUG-20:52 | 4653.96 | 01-AUG-20:55 | 29015.89 | 07-AUG-16:05 | 0.00 |
September | 0.567332E+11 | 0.159494E+11 | 720.00 | 0.546465E+11 | 0.208668E+10 | 0.00 | 0.49 | 30-SEP-23:50 | 0.20 | 30-SEP-06:30 | 38069.16 | 30-SEP-23:50 | 38069.16 | 30-SEP-23:50 | 3528.81 | 22-SEP-09:05 | 9805.74 | 01-SEP-17:40 | 0.00 |
October | 0.101080E+12 | 0.244878E+11 | 744.00 | 0.995042E+11 | 0.157575E+10 | 0.00 | 0.68 | 31-OCT-24:00 | 0.39 | 25-OCT-07:00 | 53815.49 | 31-OCT-24:00 | 53815.49 | 31-OCT-24:00 | 3797.98 | 04-OCT-09:50 | 15484.73 | 03-OCT-14:05 | 0.00 |
November | 0.133862E+12 | 0.290679E+11 | 720.00 | 0.133461E+12 | 0.401476E+09 | 0.00 | 0.78 | 09-NOV-16:50 | 0.52 | 28-NOV-07:05 | 62241.80 | 09-NOV-16:50 | 61159.05 | 09-NOV-16:50 | 2404.57 | 02-NOV-15:50 | 16597.71 | 03-NOV-16:00 | 0.00 |
December | 0.177276E+12 | 0.371930E+11 | 744.00 | 0.177211E+12 | 65061280.57 | 0.00 | 0.93 | 20-DEC-16:30 | 0.71 | 27-DEC-07:10 | 75820.56 | 15-DEC-16:50 | 75820.56 | 15-DEC-16:50 | 912.25 | 14-DEC-16:00 | 16739.23 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.143435E+13 | 0.374417E+12 | 8760.00 | 0.142206E+13 | 0.122933E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.306414E+11 | 0.750209E+10 | 672.00 | 0.305171E+11 | 36501070.43 | 0.00 | 0.29 | 0.05 | 21787.00 | 21387.04 | 898.44 | 5049.13 | 0.00 | ||||||
Maximum of Months | 0.204257E+12 | 0.618215E+11 | 744.00 | 0.201540E+12 | 0.325601E+10 | 0.00 | 1.00 | 0.71 | 80339.74 | 80040.42 | 6112.29 | 29015.89 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.143635E+10 | 0.365422E+09 | 539.19 | 0.142645E+10 | 9909015.19 | 0.00 | 0.28 | 12-JAN-16:40 | 0.00 | 01-JAN-00:45 | 2176.46 | 12-JAN-16:50 | 2089.89 | 12-JAN-16:40 | 89.39 | 12-JAN-17:00 | 496.41 | 12-JAN-16:30 | 0.00 |
February | 0.645093E+10 | 0.151615E+10 | 672.00 | 0.643607E+10 | 14859894.40 | 0.00 | 0.55 | 21-FEB-17:00 | 0.18 | 02-FEB-07:10 | 4128.30 | 21-FEB-17:30 | 4128.30 | 21-FEB-17:30 | 211.35 | 13-FEB-17:00 | 1108.37 | 21-FEB-17:00 | 0.00 |
March | 0.131406E+11 | 0.298241E+10 | 744.00 | 0.131370E+11 | 3568671.87 | 0.00 | 0.84 | 31-MAR-23:20 | 0.43 | 02-MAR-07:10 | 6859.13 | 31-MAR-23:20 | 6859.13 | 31-MAR-23:20 | 110.11 | 11-MAR-10:15 | 1765.05 | 21-MAR-16:00 | 0.00 |
April | 0.188665E+11 | 0.479921E+10 | 720.00 | 0.188488E+11 | 17725385.64 | 0.00 | 1.00 | 01-APR-13:20 | 0.30 | 30-APR-24:00 | 8039.68 | 22-APR-18:00 | 8039.68 | 22-APR-18:00 | 156.07 | 18-APR-11:00 | 2706.97 | 21-APR-15:00 | 0.00 |
May | 0.571355E+10 | 0.166990E+10 | 744.00 | 0.565321E+10 | 60346784.90 | 0.00 | 0.52 | 31-MAY-24:00 | 0.14 | 02-MAY-06:05 | 3993.10 | 31-MAY-24:00 | 3987.19 | 31-MAY-24:00 | 268.49 | 24-MAY-13:10 | 1178.07 | 31-MAY-23:20 | 0.00 |
June | 0.107045E+11 | 0.342599E+10 | 720.00 | 0.105946E+11 | 0.109903E+09 | 0.00 | 0.76 | 30-JUN-23:55 | 0.44 | 29-JUN-06:10 | 5782.58 | 30-JUN-23:55 | 5782.58 | 30-JUN-23:55 | 317.36 | 19-JUN-18:00 | 1944.61 | 18-JUN-16:00 | 0.00 |
July | 0.161261E+11 | 0.513960E+10 | 744.00 | 0.158003E+11 | 0.325765E+09 | 0.00 | 0.96 | 31-JUL-23:55 | 0.68 | 05-JUL-06:10 | 7605.34 | 31-JUL-23:55 | 7592.65 | 31-JUL-24:00 | 611.47 | 20-JUL-15:00 | 2715.22 | 02-JUL-16:11 | 0.00 |
August | 0.205712E+11 | 0.625077E+10 | 744.00 | 0.202988E+11 | 0.272472E+09 | 0.00 | 1.00 | 01-AUG-10:20 | 0.29 | 31-AUG-24:00 | 8193.08 | 08-AUG-17:00 | 8078.67 | 27-AUG-20:54 | 464.69 | 01-AUG-20:55 | 2968.81 | 07-AUG-16:05 | 0.00 |
September | 0.565328E+10 | 0.160150E+10 | 720.00 | 0.544417E+10 | 0.209102E+09 | 0.00 | 0.46 | 30-SEP-23:20 | 0.15 | 30-SEP-06:50 | 3680.20 | 30-SEP-23:20 | 3680.20 | 30-SEP-23:20 | 351.26 | 22-SEP-09:05 | 1037.89 | 17-SEP-17:11 | 0.00 |
October | 0.966198E+10 | 0.236680E+10 | 744.00 | 0.950509E+10 | 0.156891E+09 | 0.00 | 0.63 | 31-OCT-23:20 | 0.31 | 25-OCT-07:00 | 5074.60 | 31-OCT-23:20 | 5074.60 | 31-OCT-23:20 | 379.70 | 04-OCT-09:50 | 1581.94 | 01-OCT-15:05 | 0.00 |
November | 0.120503E+11 | 0.265563E+10 | 720.00 | 0.120105E+11 | 39855125.17 | 0.00 | 0.77 | 09-NOV-16:50 | 0.35 | 27-NOV-05:11 | 6262.54 | 09-NOV-16:50 | 6154.18 | 09-NOV-16:50 | 240.46 | 02-NOV-15:40 | 1671.92 | 03-NOV-16:00 | 0.00 |
December | 0.157504E+11 | 0.336109E+10 | 744.00 | 0.157440E+11 | 6423057.60 | 0.00 | 0.90 | 20-DEC-16:40 | 0.57 | 04-DEC-04:15 | 7484.77 | 15-DEC-16:50 | 7484.77 | 15-DEC-16:50 | 91.12 | 14-DEC-16:00 | 1626.90 | 20-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.136126E+12 | 0.361345E+11 | 8555.19 | 0.134899E+12 | 0.122682E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.143635E+10 | 0.365422E+09 | 539.19 | 0.142645E+10 | 3568671.87 | 0.00 | 0.28 | 0.00 | 2176.46 | 2089.89 | 89.39 | 496.41 | 0.00 | ||||||
Maximum of Months | 0.205712E+11 | 0.625077E+10 | 744.00 | 0.202988E+11 | 0.325765E+09 | 0.00 | 1.00 | 0.68 | 8193.08 | 8078.67 | 611.47 | 2968.81 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.17 | 0.00 | 102.17 | 12.43 | 585.66 | 0.00 | 0.00 | 0.00 |
February | 124.76 | 0.00 | 124.76 | 43.59 | 520.13 | 0.00 | 0.00 | 0.00 |
March | 163.27 | 0.00 | 163.27 | 100.03 | 437.13 | 0.00 | 0.00 | 0.00 |
April | 188.52 | 1.49 | 187.03 | 205.99 | 250.69 | 0.00 | 0.00 | 0.00 |
May | 223.59 | 16.17 | 207.42 | 354.95 | 141.15 | 0.00 | 0.00 | 0.00 |
June | 237.75 | 29.27 | 208.48 | 493.64 | 72.32 | 0.00 | 0.00 | 0.00 |
July | 219.72 | 21.39 | 198.34 | 453.06 | 57.74 | 0.00 | 0.00 | 0.00 |
August | 185.28 | 3.79 | 181.49 | 347.45 | 83.46 | 0.00 | 0.00 | 0.00 |
September | 161.67 | 0.06 | 161.60 | 265.90 | 168.48 | 0.00 | 0.00 | 0.00 |
October | 134.23 | 0.00 | 134.23 | 132.65 | 283.99 | 0.00 | 0.00 | 0.00 |
November | 108.36 | 0.00 | 108.36 | 27.52 | 508.11 | 0.00 | 0.00 | 0.00 |
December | 101.38 | 0.00 | 101.38 | 7.14 | 666.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.74 | 6.04 | 156.70 | 204.52 | 313.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.38 | 0.00 | 101.38 | 7.14 | 57.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.75 | 29.27 | 208.48 | 493.64 | 666.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.17 | 0.00 | 102.17 | 12.43 | 585.66 | 0.00 | 0.00 | 0.00 |
February | 124.76 | 0.00 | 124.76 | 43.59 | 520.13 | 0.00 | 0.00 | 0.00 |
March | 163.27 | 0.00 | 163.27 | 100.03 | 437.13 | 0.00 | 0.00 | 0.00 |
April | 188.52 | 1.49 | 187.03 | 205.99 | 250.69 | 0.00 | 0.00 | 0.00 |
May | 223.59 | 16.17 | 207.42 | 354.95 | 141.15 | 0.00 | 0.00 | 0.00 |
June | 237.75 | 29.27 | 208.48 | 493.64 | 72.32 | 0.00 | 0.00 | 0.00 |
July | 219.72 | 21.39 | 198.34 | 453.06 | 57.74 | 0.00 | 0.00 | 0.00 |
August | 185.28 | 3.79 | 181.49 | 347.45 | 83.46 | 0.00 | 0.00 | 0.00 |
September | 161.67 | 0.06 | 161.60 | 265.90 | 168.48 | 0.00 | 0.00 | 0.00 |
October | 134.23 | 0.00 | 134.23 | 132.65 | 283.99 | 0.00 | 0.00 | 0.00 |
November | 108.36 | 0.00 | 108.36 | 27.52 | 508.11 | 0.00 | 0.00 | 0.00 |
December | 101.38 | 0.00 | 101.38 | 7.14 | 666.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.74 | 6.04 | 156.70 | 204.52 | 313.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.38 | 0.00 | 101.38 | 7.14 | 57.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.75 | 29.27 | 208.48 | 493.64 | 666.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.17 | 0.00 | 102.17 | 12.43 | 585.66 | 0.00 | 0.00 | 0.00 |
February | 124.76 | 0.00 | 124.76 | 43.59 | 520.13 | 0.00 | 0.00 | 0.00 |
March | 163.27 | 0.00 | 163.27 | 100.03 | 437.13 | 0.00 | 0.00 | 0.00 |
April | 188.52 | 1.49 | 187.03 | 205.99 | 250.69 | 0.00 | 0.00 | 0.00 |
May | 223.59 | 16.17 | 207.42 | 354.95 | 141.15 | 0.00 | 0.00 | 0.00 |
June | 237.75 | 29.27 | 208.48 | 493.64 | 72.32 | 0.00 | 0.00 | 0.00 |
July | 219.72 | 21.39 | 198.34 | 453.06 | 57.74 | 0.00 | 0.00 | 0.00 |
August | 185.28 | 3.79 | 181.49 | 347.45 | 83.46 | 0.00 | 0.00 | 0.00 |
September | 161.67 | 0.06 | 161.60 | 265.90 | 168.48 | 0.00 | 0.00 | 0.00 |
October | 134.23 | 0.00 | 134.23 | 132.65 | 283.99 | 0.00 | 0.00 | 0.00 |
November | 108.36 | 0.00 | 108.36 | 27.52 | 508.11 | 0.00 | 0.00 | 0.00 |
December | 101.38 | 0.00 | 101.38 | 7.14 | 666.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.74 | 6.04 | 156.70 | 204.52 | 313.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.38 | 0.00 | 101.38 | 7.14 | 57.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.75 | 29.27 | 208.48 | 493.64 | 666.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.17 | 0.00 | 102.17 | 12.43 | 585.66 | 0.00 | 0.00 | 0.00 |
February | 124.76 | 0.00 | 124.76 | 43.59 | 520.13 | 0.00 | 0.00 | 0.00 |
March | 163.27 | 0.00 | 163.27 | 100.03 | 437.13 | 0.00 | 0.00 | 0.00 |
April | 188.52 | 1.49 | 187.03 | 205.99 | 250.69 | 0.00 | 0.00 | 0.00 |
May | 223.59 | 16.17 | 207.42 | 354.95 | 141.15 | 0.00 | 0.00 | 0.00 |
June | 237.75 | 29.27 | 208.48 | 493.64 | 72.32 | 0.00 | 0.00 | 0.00 |
July | 219.72 | 21.39 | 198.34 | 453.06 | 57.74 | 0.00 | 0.00 | 0.00 |
August | 185.28 | 3.79 | 181.49 | 347.45 | 83.46 | 0.00 | 0.00 | 0.00 |
September | 161.67 | 0.06 | 161.60 | 265.90 | 168.48 | 0.00 | 0.00 | 0.00 |
October | 134.23 | 0.00 | 134.23 | 132.65 | 283.99 | 0.00 | 0.00 | 0.00 |
November | 108.36 | 0.00 | 108.36 | 27.52 | 508.11 | 0.00 | 0.00 | 0.00 |
December | 101.38 | 0.00 | 101.38 | 7.14 | 666.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.74 | 6.04 | 156.70 | 204.52 | 313.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.38 | 0.00 | 101.38 | 7.14 | 57.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.75 | 29.27 | 208.48 | 493.64 | 666.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.17 | 0.00 | 102.17 | 12.43 | 585.64 | 0.00 | 0.00 | 0.00 |
February | 124.76 | 0.00 | 124.76 | 43.59 | 520.11 | 0.00 | 0.00 | 0.00 |
March | 163.27 | 0.00 | 163.27 | 100.03 | 437.11 | 0.00 | 0.00 | 0.00 |
April | 188.51 | 1.49 | 187.02 | 205.98 | 250.68 | 0.00 | 0.00 | 0.00 |
May | 223.58 | 16.17 | 207.41 | 354.93 | 141.15 | 0.00 | 0.00 | 0.00 |
June | 237.74 | 29.27 | 208.47 | 493.62 | 72.32 | 0.00 | 0.00 | 0.00 |
July | 219.72 | 21.39 | 198.33 | 453.04 | 57.73 | 0.00 | 0.00 | 0.00 |
August | 185.27 | 3.79 | 181.48 | 347.44 | 83.46 | 0.00 | 0.00 | 0.00 |
September | 161.66 | 0.06 | 161.60 | 265.89 | 168.47 | 0.00 | 0.00 | 0.00 |
October | 134.22 | 0.00 | 134.22 | 132.64 | 283.98 | 0.00 | 0.00 | 0.00 |
November | 108.36 | 0.00 | 108.36 | 27.52 | 508.09 | 0.00 | 0.00 | 0.00 |
December | 101.38 | 0.00 | 101.38 | 7.14 | 666.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.74 | 6.04 | 156.69 | 204.52 | 313.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.38 | 0.00 | 101.38 | 7.14 | 57.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.74 | 29.27 | 208.47 | 493.62 | 666.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 303.63 | 164.71 | 138.92 | 279.49 | 594.48 | 0.00 | 0.00 | 0.00 |
February | 406.23 | 231.55 | 174.68 | 443.13 | 523.09 | 0.00 | 0.00 | 0.00 |
March | 501.56 | 276.34 | 225.22 | 605.08 | 437.24 | 0.00 | 0.00 | 0.00 |
April | 604.36 | 335.28 | 269.07 | 875.60 | 255.19 | 0.00 | 0.00 | 0.00 |
May | 623.66 | 338.94 | 284.73 | 1017.77 | 156.85 | 0.00 | 0.00 | 0.00 |
June | 624.01 | 347.15 | 276.86 | 1146.85 | 77.51 | 0.00 | 0.00 | 0.00 |
July | 559.61 | 292.55 | 267.05 | 1033.66 | 60.82 | 0.00 | 0.00 | 0.00 |
August | 532.49 | 272.53 | 259.97 | 946.80 | 85.46 | 0.00 | 0.00 | 0.00 |
September | 527.56 | 301.01 | 226.55 | 876.00 | 175.61 | 0.00 | 0.00 | 0.00 |
October | 405.73 | 218.97 | 186.76 | 565.20 | 295.26 | 0.00 | 0.00 | 0.00 |
November | 363.70 | 211.73 | 151.96 | 388.93 | 504.39 | 0.00 | 0.00 | 0.00 |
December | 303.37 | 160.73 | 142.64 | 261.37 | 656.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 479.71 | 262.48 | 217.23 | 704.16 | 317.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.37 | 160.73 | 138.92 | 261.37 | 60.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 624.01 | 347.15 | 284.73 | 1146.85 | 656.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 303.63 | 164.71 | 138.92 | 279.49 | 594.48 | 0.00 | 0.00 | 0.00 |
February | 406.23 | 231.55 | 174.68 | 443.13 | 523.09 | 0.00 | 0.00 | 0.00 |
March | 501.56 | 276.34 | 225.22 | 605.08 | 437.24 | 0.00 | 0.00 | 0.00 |
April | 604.36 | 335.28 | 269.07 | 875.60 | 255.19 | 0.00 | 0.00 | 0.00 |
May | 623.66 | 338.94 | 284.73 | 1017.77 | 156.85 | 0.00 | 0.00 | 0.00 |
June | 624.01 | 347.15 | 276.86 | 1146.85 | 77.51 | 0.00 | 0.00 | 0.00 |
July | 559.61 | 292.55 | 267.05 | 1033.66 | 60.82 | 0.00 | 0.00 | 0.00 |
August | 532.49 | 272.53 | 259.97 | 946.80 | 85.46 | 0.00 | 0.00 | 0.00 |
September | 527.56 | 301.01 | 226.55 | 876.00 | 175.61 | 0.00 | 0.00 | 0.00 |
October | 405.73 | 218.97 | 186.76 | 565.20 | 295.26 | 0.00 | 0.00 | 0.00 |
November | 363.70 | 211.73 | 151.96 | 388.93 | 504.39 | 0.00 | 0.00 | 0.00 |
December | 303.37 | 160.73 | 142.64 | 261.37 | 656.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 479.71 | 262.48 | 217.23 | 704.16 | 317.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.37 | 160.73 | 138.92 | 261.37 | 60.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 624.01 | 347.15 | 284.73 | 1146.85 | 656.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 303.63 | 164.71 | 138.92 | 279.48 | 594.46 | 0.00 | 0.00 | 0.00 |
February | 406.22 | 231.54 | 174.68 | 443.12 | 523.08 | 0.00 | 0.00 | 0.00 |
March | 501.55 | 276.34 | 225.21 | 605.07 | 437.23 | 0.00 | 0.00 | 0.00 |
April | 604.35 | 335.28 | 269.07 | 875.59 | 255.19 | 0.00 | 0.00 | 0.00 |
May | 623.65 | 338.93 | 284.72 | 1017.75 | 156.85 | 0.00 | 0.00 | 0.00 |
June | 624.00 | 347.15 | 276.86 | 1146.83 | 77.51 | 0.00 | 0.00 | 0.00 |
July | 559.60 | 292.55 | 267.05 | 1033.64 | 60.81 | 0.00 | 0.00 | 0.00 |
August | 532.49 | 272.52 | 259.96 | 946.78 | 85.46 | 0.00 | 0.00 | 0.00 |
September | 527.55 | 301.00 | 226.54 | 875.99 | 175.61 | 0.00 | 0.00 | 0.00 |
October | 405.72 | 218.96 | 186.76 | 565.19 | 295.26 | 0.00 | 0.00 | 0.00 |
November | 363.69 | 211.73 | 151.96 | 388.92 | 504.38 | 0.00 | 0.00 | 0.00 |
December | 303.37 | 160.73 | 142.64 | 261.36 | 656.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 479.70 | 262.48 | 217.22 | 704.15 | 317.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.37 | 160.73 | 138.92 | 261.36 | 60.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 624.00 | 347.15 | 284.72 | 1146.83 | 656.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.95 | 529.52 | 169.42 | 925.60 | 511.93 | 0.00 | 0.00 | 0.00 |
February | 648.35 | 457.08 | 191.27 | 872.72 | 464.14 | 0.00 | 0.00 | 0.00 |
March | 526.92 | 303.82 | 223.10 | 730.29 | 411.36 | 0.00 | 0.00 | 0.00 |
April | 357.25 | 133.30 | 223.95 | 558.47 | 257.42 | 0.00 | 0.00 | 0.00 |
May | 252.46 | 35.34 | 217.13 | 439.38 | 151.18 | 0.00 | 0.00 | 0.00 |
June | 217.81 | 13.82 | 203.99 | 465.56 | 74.55 | 0.00 | 0.00 | 0.00 |
July | 222.04 | 20.58 | 201.45 | 470.80 | 60.39 | 0.00 | 0.00 | 0.00 |
August | 283.04 | 74.92 | 208.11 | 562.70 | 88.38 | 0.00 | 0.00 | 0.00 |
September | 441.79 | 229.52 | 212.26 | 805.93 | 173.42 | 0.00 | 0.00 | 0.00 |
October | 600.26 | 405.81 | 194.44 | 936.54 | 276.39 | 0.00 | 0.00 | 0.00 |
November | 722.35 | 550.71 | 171.65 | 1000.05 | 446.20 | 0.00 | 0.00 | 0.00 |
December | 715.88 | 537.37 | 178.51 | 923.94 | 560.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 472.92 | 273.28 | 199.64 | 723.30 | 288.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.81 | 13.82 | 169.42 | 439.38 | 60.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 722.35 | 550.71 | 223.95 | 1000.05 | 560.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.95 | 529.52 | 169.42 | 925.59 | 511.93 | 0.00 | 0.00 | 0.00 |
February | 648.35 | 457.08 | 191.27 | 872.72 | 464.14 | 0.00 | 0.00 | 0.00 |
March | 526.92 | 303.82 | 223.10 | 730.29 | 411.36 | 0.00 | 0.00 | 0.00 |
April | 357.25 | 133.30 | 223.95 | 558.47 | 257.42 | 0.00 | 0.00 | 0.00 |
May | 252.46 | 35.34 | 217.13 | 439.38 | 151.18 | 0.00 | 0.00 | 0.00 |
June | 217.81 | 13.82 | 203.99 | 465.56 | 74.55 | 0.00 | 0.00 | 0.00 |
July | 222.04 | 20.58 | 201.45 | 470.80 | 60.39 | 0.00 | 0.00 | 0.00 |
August | 283.03 | 74.92 | 208.11 | 562.70 | 88.38 | 0.00 | 0.00 | 0.00 |
September | 441.79 | 229.52 | 212.26 | 805.92 | 173.42 | 0.00 | 0.00 | 0.00 |
October | 600.26 | 405.81 | 194.44 | 936.54 | 276.39 | 0.00 | 0.00 | 0.00 |
November | 722.35 | 550.71 | 171.65 | 1000.05 | 446.20 | 0.00 | 0.00 | 0.00 |
December | 715.88 | 537.37 | 178.51 | 923.94 | 560.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 472.92 | 273.28 | 199.64 | 723.29 | 288.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.81 | 13.82 | 169.42 | 439.38 | 60.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 722.35 | 550.71 | 223.95 | 1000.05 | 560.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.95 | 529.52 | 169.42 | 925.60 | 511.93 | 0.00 | 0.00 | 0.00 |
February | 648.35 | 457.08 | 191.27 | 872.72 | 464.14 | 0.00 | 0.00 | 0.00 |
March | 526.92 | 303.82 | 223.10 | 730.29 | 411.36 | 0.00 | 0.00 | 0.00 |
April | 357.25 | 133.30 | 223.95 | 558.47 | 257.42 | 0.00 | 0.00 | 0.00 |
May | 252.46 | 35.34 | 217.13 | 439.38 | 151.18 | 0.00 | 0.00 | 0.00 |
June | 217.81 | 13.82 | 203.99 | 465.56 | 74.55 | 0.00 | 0.00 | 0.00 |
July | 222.04 | 20.58 | 201.45 | 470.80 | 60.39 | 0.00 | 0.00 | 0.00 |
August | 283.04 | 74.92 | 208.11 | 562.70 | 88.38 | 0.00 | 0.00 | 0.00 |
September | 441.79 | 229.52 | 212.26 | 805.93 | 173.42 | 0.00 | 0.00 | 0.00 |
October | 600.26 | 405.81 | 194.44 | 936.54 | 276.39 | 0.00 | 0.00 | 0.00 |
November | 722.35 | 550.71 | 171.65 | 1000.05 | 446.20 | 0.00 | 0.00 | 0.00 |
December | 715.88 | 537.37 | 178.51 | 923.94 | 560.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 472.92 | 273.28 | 199.64 | 723.30 | 288.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.81 | 13.82 | 169.42 | 439.38 | 60.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 722.35 | 550.71 | 223.95 | 1000.05 | 560.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.95 | 529.52 | 169.42 | 925.59 | 511.93 | 0.00 | 0.00 | 0.00 |
February | 648.35 | 457.08 | 191.27 | 872.72 | 464.14 | 0.00 | 0.00 | 0.00 |
March | 526.92 | 303.82 | 223.10 | 730.29 | 411.36 | 0.00 | 0.00 | 0.00 |
April | 357.25 | 133.30 | 223.95 | 558.47 | 257.42 | 0.00 | 0.00 | 0.00 |
May | 252.46 | 35.34 | 217.13 | 439.38 | 151.18 | 0.00 | 0.00 | 0.00 |
June | 217.81 | 13.82 | 203.99 | 465.56 | 74.55 | 0.00 | 0.00 | 0.00 |
July | 222.04 | 20.58 | 201.45 | 470.80 | 60.39 | 0.00 | 0.00 | 0.00 |
August | 283.03 | 74.92 | 208.11 | 562.70 | 88.38 | 0.00 | 0.00 | 0.00 |
September | 441.79 | 229.52 | 212.26 | 805.92 | 173.42 | 0.00 | 0.00 | 0.00 |
October | 600.26 | 405.81 | 194.44 | 936.54 | 276.39 | 0.00 | 0.00 | 0.00 |
November | 722.35 | 550.71 | 171.65 | 1000.05 | 446.20 | 0.00 | 0.00 | 0.00 |
December | 715.88 | 537.37 | 178.51 | 923.94 | 560.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 472.92 | 273.28 | 199.64 | 723.29 | 288.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.81 | 13.82 | 169.42 | 439.38 | 60.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 722.35 | 550.71 | 223.95 | 1000.05 | 560.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.92 | 529.50 | 169.41 | 925.56 | 511.91 | 0.00 | 0.00 | 0.00 |
February | 648.32 | 457.06 | 191.27 | 872.69 | 464.12 | 0.00 | 0.00 | 0.00 |
March | 526.90 | 303.81 | 223.09 | 730.26 | 411.35 | 0.00 | 0.00 | 0.00 |
April | 357.24 | 133.29 | 223.94 | 558.45 | 257.41 | 0.00 | 0.00 | 0.00 |
May | 252.45 | 35.34 | 217.12 | 439.36 | 151.17 | 0.00 | 0.00 | 0.00 |
June | 217.80 | 13.82 | 203.98 | 465.54 | 74.55 | 0.00 | 0.00 | 0.00 |
July | 222.03 | 20.58 | 201.45 | 470.78 | 60.39 | 0.00 | 0.00 | 0.00 |
August | 283.02 | 74.92 | 208.11 | 562.68 | 88.38 | 0.00 | 0.00 | 0.00 |
September | 441.77 | 229.51 | 212.25 | 805.89 | 173.41 | 0.00 | 0.00 | 0.00 |
October | 600.23 | 405.80 | 194.44 | 936.50 | 276.38 | 0.00 | 0.00 | 0.00 |
November | 722.33 | 550.68 | 171.64 | 1000.01 | 446.18 | 0.00 | 0.00 | 0.00 |
December | 715.85 | 537.35 | 178.50 | 923.90 | 560.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 472.90 | 273.27 | 199.63 | 723.27 | 288.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.80 | 13.82 | 169.41 | 439.36 | 60.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 722.33 | 550.68 | 223.94 | 1000.01 | 560.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 319.84 | 180.13 | 139.72 | 328.82 | 666.07 | 0.00 | 0.00 | 0.00 |
February | 360.91 | 191.83 | 169.08 | 395.79 | 614.64 | 0.00 | 0.00 | 0.00 |
March | 491.82 | 263.60 | 228.22 | 603.17 | 530.52 | 0.00 | 0.00 | 0.00 |
April | 565.30 | 305.33 | 259.97 | 813.94 | 336.93 | 0.00 | 0.00 | 0.00 |
May | 608.88 | 325.78 | 283.10 | 998.34 | 194.99 | 0.00 | 0.00 | 0.00 |
June | 592.70 | 318.35 | 274.36 | 1085.42 | 110.42 | 0.00 | 0.00 | 0.00 |
July | 525.98 | 261.37 | 264.61 | 958.02 | 97.16 | 0.00 | 0.00 | 0.00 |
August | 509.39 | 259.60 | 249.78 | 883.40 | 138.06 | 0.00 | 0.00 | 0.00 |
September | 520.93 | 290.21 | 230.72 | 876.87 | 217.64 | 0.00 | 0.00 | 0.00 |
October | 448.43 | 261.72 | 186.71 | 646.70 | 353.88 | 0.00 | 0.00 | 0.00 |
November | 376.39 | 229.18 | 147.21 | 437.86 | 604.34 | 0.00 | 0.00 | 0.00 |
December | 303.32 | 164.77 | 138.55 | 285.13 | 783.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 469.05 | 254.49 | 214.56 | 694.02 | 386.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.32 | 164.77 | 138.55 | 285.13 | 97.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.88 | 325.78 | 283.10 | 1085.42 | 783.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 319.84 | 180.13 | 139.72 | 328.82 | 666.07 | 0.00 | 0.00 | 0.00 |
February | 360.91 | 191.83 | 169.08 | 395.79 | 614.64 | 0.00 | 0.00 | 0.00 |
March | 491.82 | 263.60 | 228.22 | 603.17 | 530.52 | 0.00 | 0.00 | 0.00 |
April | 565.30 | 305.33 | 259.97 | 813.94 | 336.93 | 0.00 | 0.00 | 0.00 |
May | 608.88 | 325.78 | 283.10 | 998.34 | 194.99 | 0.00 | 0.00 | 0.00 |
June | 592.70 | 318.35 | 274.36 | 1085.42 | 110.42 | 0.00 | 0.00 | 0.00 |
July | 525.98 | 261.37 | 264.61 | 958.02 | 97.16 | 0.00 | 0.00 | 0.00 |
August | 509.39 | 259.60 | 249.78 | 883.40 | 138.06 | 0.00 | 0.00 | 0.00 |
September | 520.93 | 290.21 | 230.72 | 876.87 | 217.64 | 0.00 | 0.00 | 0.00 |
October | 448.43 | 261.72 | 186.71 | 646.70 | 353.88 | 0.00 | 0.00 | 0.00 |
November | 376.39 | 229.18 | 147.21 | 437.86 | 604.34 | 0.00 | 0.00 | 0.00 |
December | 303.32 | 164.77 | 138.55 | 285.13 | 783.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 469.05 | 254.49 | 214.56 | 694.02 | 386.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.32 | 164.77 | 138.55 | 285.13 | 97.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.88 | 325.78 | 283.10 | 1085.42 | 783.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 319.84 | 180.12 | 139.71 | 328.82 | 666.06 | 0.00 | 0.00 | 0.00 |
February | 360.90 | 191.83 | 169.08 | 395.79 | 614.63 | 0.00 | 0.00 | 0.00 |
March | 491.81 | 263.59 | 228.22 | 603.16 | 530.51 | 0.00 | 0.00 | 0.00 |
April | 565.29 | 305.32 | 259.97 | 813.92 | 336.92 | 0.00 | 0.00 | 0.00 |
May | 608.87 | 325.77 | 283.10 | 998.32 | 194.99 | 0.00 | 0.00 | 0.00 |
June | 592.69 | 318.34 | 274.35 | 1085.40 | 110.42 | 0.00 | 0.00 | 0.00 |
July | 525.97 | 261.37 | 264.61 | 958.00 | 97.16 | 0.00 | 0.00 | 0.00 |
August | 509.38 | 259.60 | 249.78 | 883.39 | 138.06 | 0.00 | 0.00 | 0.00 |
September | 520.92 | 290.20 | 230.71 | 876.85 | 217.63 | 0.00 | 0.00 | 0.00 |
October | 448.42 | 261.71 | 186.71 | 646.69 | 353.87 | 0.00 | 0.00 | 0.00 |
November | 376.39 | 229.18 | 147.21 | 437.86 | 604.33 | 0.00 | 0.00 | 0.00 |
December | 303.31 | 164.77 | 138.54 | 285.12 | 783.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 469.04 | 254.49 | 214.55 | 694.00 | 386.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.31 | 164.77 | 138.54 | 285.12 | 97.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.87 | 325.77 | 283.10 | 1085.40 | 783.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.85 | 0.00 | 510.85 | 112.63 | 2578.09 | 0.00 | 0.00 | 0.00 |
February | 623.80 | 0.00 | 623.80 | 282.48 | 2319.91 | 0.00 | 0.00 | 0.00 |
March | 816.35 | 0.00 | 816.35 | 564.88 | 1968.51 | 0.00 | 0.00 | 0.00 |
April | 942.57 | 7.43 | 935.14 | 1080.71 | 1152.26 | 0.00 | 0.00 | 0.00 |
May | 1117.92 | 80.84 | 1037.08 | 1794.52 | 674.29 | 0.00 | 0.00 | 0.00 |
June | 1188.72 | 146.35 | 1042.37 | 2487.04 | 361.60 | 0.00 | 0.00 | 0.00 |
July | 1098.61 | 106.94 | 991.67 | 2288.48 | 287.76 | 0.00 | 0.00 | 0.00 |
August | 926.37 | 18.94 | 907.42 | 1785.00 | 389.02 | 0.00 | 0.00 | 0.00 |
September | 808.34 | 0.32 | 808.01 | 1353.54 | 800.90 | 0.00 | 0.00 | 0.00 |
October | 671.14 | 0.00 | 671.14 | 710.86 | 1289.76 | 0.00 | 0.00 | 0.00 |
November | 541.81 | 0.00 | 541.81 | 196.25 | 2215.22 | 0.00 | 0.00 | 0.00 |
December | 506.89 | 0.00 | 506.89 | 75.48 | 2862.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 813.70 | 30.22 | 783.48 | 1064.99 | 1403.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.89 | 0.00 | 506.89 | 75.48 | 287.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1188.72 | 146.35 | 1042.37 | 2487.04 | 2862.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 910.89 | 494.12 | 416.76 | 858.81 | 1633.51 | 0.00 | 0.00 | 0.00 |
February | 1218.68 | 694.64 | 524.04 | 1337.42 | 1471.18 | 0.00 | 0.00 | 0.00 |
March | 1504.67 | 829.03 | 675.65 | 1809.71 | 1249.79 | 0.00 | 0.00 | 0.00 |
April | 1813.05 | 1005.84 | 807.21 | 2600.75 | 754.02 | 0.00 | 0.00 | 0.00 |
May | 1870.97 | 1016.80 | 854.17 | 3024.48 | 464.83 | 0.00 | 0.00 | 0.00 |
June | 1872.03 | 1041.44 | 830.58 | 3410.48 | 245.64 | 0.00 | 0.00 | 0.00 |
July | 1678.80 | 877.65 | 801.15 | 3071.85 | 200.04 | 0.00 | 0.00 | 0.00 |
August | 1597.47 | 817.57 | 779.90 | 2818.37 | 268.51 | 0.00 | 0.00 | 0.00 |
September | 1582.66 | 903.02 | 679.64 | 2606.34 | 521.26 | 0.00 | 0.00 | 0.00 |
October | 1217.16 | 656.89 | 560.27 | 1686.66 | 845.58 | 0.00 | 0.00 | 0.00 |
November | 1091.08 | 635.19 | 455.89 | 1178.51 | 1403.20 | 0.00 | 0.00 | 0.00 |
December | 910.11 | 482.19 | 427.91 | 809.74 | 1797.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1439.12 | 787.44 | 651.68 | 2103.56 | 901.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 910.11 | 482.19 | 416.76 | 809.74 | 200.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1872.03 | 1041.44 | 854.17 | 3410.48 | 1797.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3494.69 | 2647.59 | 847.10 | 4590.28 | 2494.23 | 0.00 | 0.00 | 0.00 |
February | 3241.71 | 2285.36 | 956.36 | 4330.03 | 2257.80 | 0.00 | 0.00 | 0.00 |
March | 2634.57 | 1519.08 | 1115.48 | 3625.57 | 1984.48 | 0.00 | 0.00 | 0.00 |
April | 1786.23 | 666.49 | 1119.74 | 2789.84 | 1232.86 | 0.00 | 0.00 | 0.00 |
May | 1262.31 | 176.68 | 1085.62 | 2204.26 | 729.11 | 0.00 | 0.00 | 0.00 |
June | 1089.05 | 69.10 | 1019.95 | 2353.55 | 368.73 | 0.00 | 0.00 | 0.00 |
July | 1110.17 | 102.91 | 1007.25 | 2377.61 | 299.06 | 0.00 | 0.00 | 0.00 |
August | 1415.16 | 374.60 | 1040.56 | 2838.90 | 421.57 | 0.00 | 0.00 | 0.00 |
September | 2208.90 | 1147.60 | 1061.30 | 4008.24 | 853.15 | 0.00 | 0.00 | 0.00 |
October | 3001.25 | 2029.04 | 972.20 | 4650.73 | 1346.67 | 0.00 | 0.00 | 0.00 |
November | 3611.73 | 2753.50 | 858.23 | 4972.48 | 2156.50 | 0.00 | 0.00 | 0.00 |
December | 3579.36 | 2686.83 | 892.53 | 4609.26 | 2690.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2364.57 | 1366.38 | 998.19 | 3607.56 | 1398.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1089.05 | 69.10 | 847.10 | 2204.26 | 299.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3611.73 | 2753.50 | 1119.74 | 4972.48 | 2690.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 959.52 | 540.37 | 419.14 | 1023.24 | 1759.11 | 0.00 | 0.00 | 0.00 |
February | 1082.72 | 575.49 | 507.23 | 1230.74 | 1608.59 | 0.00 | 0.00 | 0.00 |
March | 1475.43 | 790.78 | 684.65 | 1853.04 | 1387.78 | 0.00 | 0.00 | 0.00 |
April | 1695.89 | 915.98 | 779.91 | 2490.43 | 869.43 | 0.00 | 0.00 | 0.00 |
May | 1826.63 | 977.33 | 849.30 | 2999.69 | 540.06 | 0.00 | 0.00 | 0.00 |
June | 1778.08 | 955.03 | 823.06 | 3284.87 | 294.98 | 0.00 | 0.00 | 0.00 |
July | 1577.92 | 784.10 | 793.82 | 2919.13 | 242.90 | 0.00 | 0.00 | 0.00 |
August | 1528.14 | 778.80 | 749.34 | 2717.69 | 321.00 | 0.00 | 0.00 | 0.00 |
September | 1562.76 | 870.62 | 692.14 | 2643.54 | 603.18 | 0.00 | 0.00 | 0.00 |
October | 1345.28 | 785.15 | 560.13 | 1971.76 | 941.35 | 0.00 | 0.00 | 0.00 |
November | 1129.17 | 687.54 | 441.62 | 1361.67 | 1540.29 | 0.00 | 0.00 | 0.00 |
December | 909.94 | 494.31 | 415.63 | 917.23 | 1932.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1407.13 | 763.47 | 643.66 | 2121.46 | 1000.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 909.94 | 494.31 | 415.63 | 917.23 | 242.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1826.63 | 977.33 | 849.30 | 3284.87 | 1932.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.85 | 0.00 | 510.85 | 154.64 | 2320.21 | 0.00 | 0.00 | 0.00 |
February | 623.80 | 0.00 | 623.80 | 328.97 | 2116.93 | 0.00 | 0.00 | 0.00 |
March | 816.35 | 0.00 | 816.35 | 608.65 | 1826.44 | 0.00 | 0.00 | 0.00 |
April | 942.57 | 7.43 | 935.14 | 1087.32 | 1102.31 | 0.00 | 0.00 | 0.00 |
May | 1117.92 | 80.84 | 1037.08 | 1778.44 | 667.49 | 0.00 | 0.00 | 0.00 |
June | 1188.72 | 146.35 | 1042.37 | 2454.87 | 369.58 | 0.00 | 0.00 | 0.00 |
July | 1098.61 | 106.94 | 991.67 | 2249.57 | 300.70 | 0.00 | 0.00 | 0.00 |
August | 926.37 | 18.94 | 907.42 | 1755.50 | 394.20 | 0.00 | 0.00 | 0.00 |
September | 808.34 | 0.32 | 808.01 | 1340.52 | 789.01 | 0.00 | 0.00 | 0.00 |
October | 671.14 | 0.00 | 671.14 | 732.37 | 1206.40 | 0.00 | 0.00 | 0.00 |
November | 541.81 | 0.00 | 541.81 | 240.26 | 1990.50 | 0.00 | 0.00 | 0.00 |
December | 506.89 | 0.00 | 506.89 | 114.00 | 2582.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 813.70 | 30.22 | 783.48 | 1074.22 | 1301.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.89 | 0.00 | 506.89 | 114.00 | 300.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1188.72 | 146.35 | 1042.37 | 2454.87 | 2582.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 910.89 | 494.12 | 416.76 | 911.82 | 1461.84 | 0.00 | 0.00 | 0.00 |
February | 1218.68 | 694.64 | 524.04 | 1384.78 | 1345.20 | 0.00 | 0.00 | 0.00 |
March | 1504.67 | 829.03 | 675.65 | 1844.50 | 1173.23 | 0.00 | 0.00 | 0.00 |
April | 1813.05 | 1005.84 | 807.21 | 2604.02 | 731.12 | 0.00 | 0.00 | 0.00 |
May | 1870.97 | 1016.80 | 854.17 | 3015.06 | 460.99 | 0.00 | 0.00 | 0.00 |
June | 1872.03 | 1041.44 | 830.58 | 3392.70 | 250.14 | 0.00 | 0.00 | 0.00 |
July | 1678.80 | 877.65 | 801.15 | 3050.98 | 207.31 | 0.00 | 0.00 | 0.00 |
August | 1597.47 | 817.57 | 779.90 | 2803.66 | 271.89 | 0.00 | 0.00 | 0.00 |
September | 1582.66 | 903.02 | 679.64 | 2600.78 | 515.89 | 0.00 | 0.00 | 0.00 |
October | 1217.16 | 656.89 | 560.27 | 1702.48 | 799.86 | 0.00 | 0.00 | 0.00 |
November | 1091.08 | 635.19 | 455.89 | 1225.11 | 1272.20 | 0.00 | 0.00 | 0.00 |
December | 910.11 | 482.19 | 427.91 | 869.19 | 1610.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1439.12 | 787.44 | 651.68 | 2119.40 | 839.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 910.11 | 482.19 | 416.76 | 869.19 | 207.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1872.03 | 1041.44 | 854.17 | 3392.70 | 1610.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3494.69 | 2647.59 | 847.10 | 4648.98 | 2275.26 | 0.00 | 0.00 | 0.00 |
February | 3241.71 | 2285.36 | 956.36 | 4376.58 | 2087.56 | 0.00 | 0.00 | 0.00 |
March | 2634.57 | 1519.08 | 1115.48 | 3656.32 | 1867.84 | 0.00 | 0.00 | 0.00 |
April | 1786.23 | 666.49 | 1119.74 | 2786.21 | 1187.48 | 0.00 | 0.00 | 0.00 |
May | 1262.31 | 176.68 | 1085.62 | 2184.32 | 719.53 | 0.00 | 0.00 | 0.00 |
June | 1089.05 | 69.10 | 1019.95 | 2322.00 | 376.26 | 0.00 | 0.00 | 0.00 |
July | 1110.17 | 102.91 | 1007.25 | 2338.46 | 311.66 | 0.00 | 0.00 | 0.00 |
August | 1415.16 | 374.60 | 1040.56 | 2808.45 | 427.40 | 0.00 | 0.00 | 0.00 |
September | 2208.90 | 1147.60 | 1061.30 | 3990.13 | 843.56 | 0.00 | 0.00 | 0.00 |
October | 3001.25 | 2029.04 | 972.20 | 4662.09 | 1282.94 | 0.00 | 0.00 | 0.00 |
November | 3611.73 | 2753.50 | 858.23 | 5028.73 | 1990.42 | 0.00 | 0.00 | 0.00 |
December | 3579.36 | 2686.83 | 892.53 | 4687.77 | 2458.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2364.57 | 1366.38 | 998.19 | 3619.00 | 1315.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1089.05 | 69.10 | 847.10 | 2184.32 | 311.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3611.73 | 2753.50 | 1119.74 | 5028.73 | 2458.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 959.52 | 540.37 | 419.14 | 1049.32 | 1614.41 | 0.00 | 0.00 | 0.00 |
February | 1082.72 | 575.49 | 507.23 | 1253.21 | 1492.72 | 0.00 | 0.00 | 0.00 |
March | 1475.43 | 790.78 | 684.65 | 1868.02 | 1307.19 | 0.00 | 0.00 | 0.00 |
April | 1695.89 | 915.98 | 779.91 | 2484.84 | 839.35 | 0.00 | 0.00 | 0.00 |
May | 1826.63 | 977.33 | 849.30 | 2981.95 | 532.69 | 0.00 | 0.00 | 0.00 |
June | 1778.08 | 955.03 | 823.06 | 3262.05 | 299.30 | 0.00 | 0.00 | 0.00 |
July | 1577.92 | 784.10 | 793.82 | 2894.90 | 249.57 | 0.00 | 0.00 | 0.00 |
August | 1528.14 | 778.80 | 749.34 | 2697.77 | 323.88 | 0.00 | 0.00 | 0.00 |
September | 1562.76 | 870.62 | 692.14 | 2630.56 | 596.35 | 0.00 | 0.00 | 0.00 |
October | 1345.28 | 785.15 | 560.13 | 1975.38 | 897.66 | 0.00 | 0.00 | 0.00 |
November | 1129.17 | 687.54 | 441.62 | 1384.61 | 1419.60 | 0.00 | 0.00 | 0.00 |
December | 909.94 | 494.31 | 415.63 | 945.20 | 1774.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1407.13 | 763.47 | 643.66 | 2122.58 | 942.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 909.94 | 494.31 | 415.63 | 945.20 | 249.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1826.63 | 977.33 | 849.30 | 3262.05 | 1774.58 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273655E+09 | 0.00 | 0.273655E+09 | 33292388.44 | 0.156864E+10 |
February | 0.301823E+09 | 0.00 | 0.301823E+09 | 0.105460E+09 | 0.125829E+10 |
March | 0.437309E+09 | 0.00 | 0.437309E+09 | 0.267925E+09 | 0.117080E+10 |
April | 0.488634E+09 | 3849732.07 | 0.484785E+09 | 0.533922E+09 | 0.649777E+09 |
May | 0.598856E+09 | 43305658.60 | 0.555551E+09 | 0.950696E+09 | 0.378069E+09 |
June | 0.616240E+09 | 75866320.30 | 0.540373E+09 | 0.127951E+10 | 0.187465E+09 |
July | 0.588509E+09 | 57286879.27 | 0.531223E+09 | 0.121347E+10 | 0.154643E+09 |
August | 0.496241E+09 | 10146852.27 | 0.486095E+09 | 0.930620E+09 | 0.223541E+09 |
September | 0.419047E+09 | 167214.87 | 0.418880E+09 | 0.689214E+09 | 0.436703E+09 |
October | 0.359522E+09 | 0.00 | 0.359522E+09 | 0.355288E+09 | 0.760649E+09 |
November | 0.280878E+09 | 0.00 | 0.280878E+09 | 71338334.80 | 0.131702E+10 |
December | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123754.32 | 0.178575E+10 |
Annual Sum or Average | 0.513225E+10 | 0.190623E+09 | 0.494163E+10 | 0.644987E+10 | 0.989135E+10 |
Minimum of Months | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123754.32 | 0.154643E+09 |
Maximum of Months | 0.616240E+09 | 75866320.30 | 0.555551E+09 | 0.127951E+10 | 0.178575E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273654E+09 | 0.00 | 0.273654E+09 | 33292292.93 | 0.156864E+10 |
February | 0.301823E+09 | 0.00 | 0.301823E+09 | 0.105460E+09 | 0.125829E+10 |
March | 0.437309E+09 | 0.00 | 0.437309E+09 | 0.267925E+09 | 0.117080E+10 |
April | 0.488634E+09 | 3849727.45 | 0.484784E+09 | 0.533922E+09 | 0.649777E+09 |
May | 0.598856E+09 | 43305606.64 | 0.555550E+09 | 0.950695E+09 | 0.378069E+09 |
June | 0.616239E+09 | 75866229.27 | 0.540373E+09 | 0.127951E+10 | 0.187465E+09 |
July | 0.588509E+09 | 57286810.53 | 0.531222E+09 | 0.121347E+10 | 0.154643E+09 |
August | 0.496241E+09 | 10146840.09 | 0.486094E+09 | 0.930620E+09 | 0.223540E+09 |
September | 0.419047E+09 | 167214.67 | 0.418880E+09 | 0.689214E+09 | 0.436703E+09 |
October | 0.359522E+09 | 0.00 | 0.359522E+09 | 0.355288E+09 | 0.760649E+09 |
November | 0.280878E+09 | 0.00 | 0.280878E+09 | 71338248.04 | 0.131702E+10 |
December | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123697.97 | 0.178575E+10 |
Annual Sum or Average | 0.513225E+10 | 0.190622E+09 | 0.494162E+10 | 0.644986E+10 | 0.989135E+10 |
Minimum of Months | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123697.97 | 0.154643E+09 |
Maximum of Months | 0.616239E+09 | 75866229.27 | 0.555550E+09 | 0.127951E+10 | 0.178575E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273655E+09 | 0.00 | 0.273655E+09 | 33292388.44 | 0.156864E+10 |
February | 0.301823E+09 | 0.00 | 0.301823E+09 | 0.105460E+09 | 0.125829E+10 |
March | 0.437309E+09 | 0.00 | 0.437309E+09 | 0.267925E+09 | 0.117080E+10 |
April | 0.488634E+09 | 3849732.07 | 0.484785E+09 | 0.533922E+09 | 0.649777E+09 |
May | 0.598856E+09 | 43305658.60 | 0.555551E+09 | 0.950696E+09 | 0.378069E+09 |
June | 0.616240E+09 | 75866320.30 | 0.540373E+09 | 0.127951E+10 | 0.187465E+09 |
July | 0.588509E+09 | 57286879.27 | 0.531223E+09 | 0.121347E+10 | 0.154643E+09 |
August | 0.496241E+09 | 10146852.27 | 0.486095E+09 | 0.930620E+09 | 0.223541E+09 |
September | 0.419047E+09 | 167214.87 | 0.418880E+09 | 0.689214E+09 | 0.436703E+09 |
October | 0.359522E+09 | 0.00 | 0.359522E+09 | 0.355288E+09 | 0.760649E+09 |
November | 0.280878E+09 | 0.00 | 0.280878E+09 | 71338334.80 | 0.131702E+10 |
December | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123754.32 | 0.178575E+10 |
Annual Sum or Average | 0.513225E+10 | 0.190623E+09 | 0.494163E+10 | 0.644987E+10 | 0.989135E+10 |
Minimum of Months | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123754.32 | 0.154643E+09 |
Maximum of Months | 0.616240E+09 | 75866320.30 | 0.555551E+09 | 0.127951E+10 | 0.178575E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273654E+09 | 0.00 | 0.273654E+09 | 33292292.93 | 0.156864E+10 |
February | 0.301823E+09 | 0.00 | 0.301823E+09 | 0.105460E+09 | 0.125829E+10 |
March | 0.437309E+09 | 0.00 | 0.437309E+09 | 0.267925E+09 | 0.117080E+10 |
April | 0.488634E+09 | 3849727.45 | 0.484784E+09 | 0.533922E+09 | 0.649777E+09 |
May | 0.598856E+09 | 43305606.64 | 0.555550E+09 | 0.950695E+09 | 0.378069E+09 |
June | 0.616239E+09 | 75866229.27 | 0.540373E+09 | 0.127951E+10 | 0.187465E+09 |
July | 0.588509E+09 | 57286810.53 | 0.531222E+09 | 0.121347E+10 | 0.154643E+09 |
August | 0.496241E+09 | 10146840.09 | 0.486094E+09 | 0.930620E+09 | 0.223540E+09 |
September | 0.419047E+09 | 167214.67 | 0.418880E+09 | 0.689214E+09 | 0.436703E+09 |
October | 0.359522E+09 | 0.00 | 0.359522E+09 | 0.355288E+09 | 0.760649E+09 |
November | 0.280878E+09 | 0.00 | 0.280878E+09 | 71338248.04 | 0.131702E+10 |
December | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123697.97 | 0.178575E+10 |
Annual Sum or Average | 0.513225E+10 | 0.190622E+09 | 0.494162E+10 | 0.644986E+10 | 0.989135E+10 |
Minimum of Months | 0.271535E+09 | 0.00 | 0.271535E+09 | 19123697.97 | 0.154643E+09 |
Maximum of Months | 0.616239E+09 | 75866229.27 | 0.555550E+09 | 0.127951E+10 | 0.178575E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273644E+09 | 0.00 | 0.273644E+09 | 33291046.61 | 0.156858E+10 |
February | 0.301811E+09 | 0.00 | 0.301811E+09 | 0.105456E+09 | 0.125824E+10 |
March | 0.437292E+09 | 0.00 | 0.437292E+09 | 0.267914E+09 | 0.117076E+10 |
April | 0.488615E+09 | 3849576.90 | 0.484765E+09 | 0.533901E+09 | 0.649751E+09 |
May | 0.598832E+09 | 43303913.19 | 0.555528E+09 | 0.950658E+09 | 0.378054E+09 |
June | 0.616215E+09 | 75863262.55 | 0.540352E+09 | 0.127946E+10 | 0.187458E+09 |
July | 0.588486E+09 | 57284570.36 | 0.531201E+09 | 0.121342E+10 | 0.154637E+09 |
August | 0.496221E+09 | 10146443.30 | 0.486075E+09 | 0.930583E+09 | 0.223532E+09 |
September | 0.419030E+09 | 167208.13 | 0.418863E+09 | 0.689187E+09 | 0.436685E+09 |
October | 0.359508E+09 | 0.00 | 0.359508E+09 | 0.355274E+09 | 0.760618E+09 |
November | 0.280867E+09 | 0.00 | 0.280867E+09 | 71335459.55 | 0.131696E+10 |
December | 0.271524E+09 | 0.00 | 0.271524E+09 | 19122983.55 | 0.178568E+10 |
Annual Sum or Average | 0.513204E+10 | 0.190615E+09 | 0.494143E+10 | 0.644961E+10 | 0.989095E+10 |
Minimum of Months | 0.271524E+09 | 0.00 | 0.271524E+09 | 19122983.55 | 0.154637E+09 |
Maximum of Months | 0.616215E+09 | 75863262.55 | 0.555528E+09 | 0.127946E+10 | 0.178568E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.813249E+09 | 0.441158E+09 | 0.372091E+09 | 0.748581E+09 | 0.159224E+10 |
February | 0.982754E+09 | 0.560164E+09 | 0.422590E+09 | 0.107202E+10 | 0.126545E+10 |
March | 0.134338E+10 | 0.740162E+09 | 0.603222E+09 | 0.162064E+10 | 0.117109E+10 |
April | 0.156649E+10 | 0.869054E+09 | 0.697440E+09 | 0.226956E+10 | 0.661459E+09 |
May | 0.167042E+10 | 0.907812E+09 | 0.762609E+09 | 0.272600E+10 | 0.420112E+09 |
June | 0.161745E+10 | 0.899817E+09 | 0.717630E+09 | 0.297264E+10 | 0.200906E+09 |
July | 0.149885E+10 | 0.783572E+09 | 0.715276E+09 | 0.276855E+10 | 0.162889E+09 |
August | 0.142623E+10 | 0.729934E+09 | 0.696301E+09 | 0.253591E+10 | 0.228893E+09 |
September | 0.136743E+10 | 0.780219E+09 | 0.587211E+09 | 0.227060E+10 | 0.455181E+09 |
October | 0.108669E+10 | 0.586479E+09 | 0.500216E+09 | 0.151383E+10 | 0.790835E+09 |
November | 0.942702E+09 | 0.548811E+09 | 0.393891E+09 | 0.100811E+10 | 0.130738E+10 |
December | 0.812550E+09 | 0.430507E+09 | 0.382043E+09 | 0.700046E+09 | 0.175869E+10 |
Annual Sum or Average | 0.151282E+11 | 0.827769E+10 | 0.685052E+10 | 0.222065E+11 | 0.100151E+11 |
Minimum of Months | 0.812550E+09 | 0.430507E+09 | 0.372091E+09 | 0.700046E+09 | 0.162889E+09 |
Maximum of Months | 0.167042E+10 | 0.907812E+09 | 0.762609E+09 | 0.297264E+10 | 0.175869E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.813249E+09 | 0.441158E+09 | 0.372091E+09 | 0.748581E+09 | 0.159224E+10 |
February | 0.982754E+09 | 0.560164E+09 | 0.422590E+09 | 0.107202E+10 | 0.126545E+10 |
March | 0.134338E+10 | 0.740162E+09 | 0.603222E+09 | 0.162064E+10 | 0.117109E+10 |
April | 0.156649E+10 | 0.869054E+09 | 0.697440E+09 | 0.226956E+10 | 0.661459E+09 |
May | 0.167042E+10 | 0.907812E+09 | 0.762609E+09 | 0.272600E+10 | 0.420112E+09 |
June | 0.161745E+10 | 0.899817E+09 | 0.717630E+09 | 0.297264E+10 | 0.200906E+09 |
July | 0.149885E+10 | 0.783572E+09 | 0.715276E+09 | 0.276855E+10 | 0.162889E+09 |
August | 0.142623E+10 | 0.729934E+09 | 0.696301E+09 | 0.253591E+10 | 0.228893E+09 |
September | 0.136743E+10 | 0.780219E+09 | 0.587211E+09 | 0.227060E+10 | 0.455181E+09 |
October | 0.108669E+10 | 0.586479E+09 | 0.500216E+09 | 0.151383E+10 | 0.790835E+09 |
November | 0.942702E+09 | 0.548811E+09 | 0.393891E+09 | 0.100811E+10 | 0.130738E+10 |
December | 0.812550E+09 | 0.430507E+09 | 0.382043E+09 | 0.700046E+09 | 0.175869E+10 |
Annual Sum or Average | 0.151282E+11 | 0.827769E+10 | 0.685052E+10 | 0.222065E+11 | 0.100151E+11 |
Minimum of Months | 0.812550E+09 | 0.430507E+09 | 0.372091E+09 | 0.700046E+09 | 0.162889E+09 |
Maximum of Months | 0.167042E+10 | 0.907812E+09 | 0.762609E+09 | 0.297264E+10 | 0.175869E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.813234E+09 | 0.441150E+09 | 0.372084E+09 | 0.748568E+09 | 0.159221E+10 |
February | 0.982736E+09 | 0.560153E+09 | 0.422583E+09 | 0.107200E+10 | 0.126543E+10 |
March | 0.134336E+10 | 0.740148E+09 | 0.603211E+09 | 0.162061E+10 | 0.117107E+10 |
April | 0.156647E+10 | 0.869038E+09 | 0.697427E+09 | 0.226952E+10 | 0.661447E+09 |
May | 0.167039E+10 | 0.907795E+09 | 0.762595E+09 | 0.272595E+10 | 0.420105E+09 |
June | 0.161742E+10 | 0.899800E+09 | 0.717617E+09 | 0.297258E+10 | 0.200902E+09 |
July | 0.149882E+10 | 0.783557E+09 | 0.715263E+09 | 0.276850E+10 | 0.162886E+09 |
August | 0.142621E+10 | 0.729920E+09 | 0.696288E+09 | 0.253586E+10 | 0.228889E+09 |
September | 0.136740E+10 | 0.780204E+09 | 0.587200E+09 | 0.227056E+10 | 0.455173E+09 |
October | 0.108667E+10 | 0.586468E+09 | 0.500207E+09 | 0.151380E+10 | 0.790821E+09 |
November | 0.942685E+09 | 0.548801E+09 | 0.393884E+09 | 0.100809E+10 | 0.130735E+10 |
December | 0.812536E+09 | 0.430500E+09 | 0.382036E+09 | 0.700033E+09 | 0.175866E+10 |
Annual Sum or Average | 0.151279E+11 | 0.827754E+10 | 0.685039E+10 | 0.222061E+11 | 0.100149E+11 |
Minimum of Months | 0.812536E+09 | 0.430500E+09 | 0.372084E+09 | 0.700033E+09 | 0.162886E+09 |
Maximum of Months | 0.167039E+10 | 0.907795E+09 | 0.762595E+09 | 0.297258E+10 | 0.175866E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187206E+10 | 0.141828E+10 | 0.453779E+09 | 0.247911E+10 | 0.137116E+10 |
February | 0.156849E+10 | 0.110576E+10 | 0.462729E+09 | 0.211129E+10 | 0.112285E+10 |
March | 0.141130E+10 | 0.813752E+09 | 0.597549E+09 | 0.195601E+10 | 0.110179E+10 |
April | 0.925990E+09 | 0.345510E+09 | 0.580480E+09 | 0.144756E+10 | 0.667224E+09 |
May | 0.676200E+09 | 94645863.76 | 0.581554E+09 | 0.117683E+10 | 0.404911E+09 |
June | 0.564571E+09 | 35822221.82 | 0.528749E+09 | 0.120673E+10 | 0.193243E+09 |
July | 0.594702E+09 | 55129926.46 | 0.539572E+09 | 0.126099E+10 | 0.161750E+09 |
August | 0.758082E+09 | 0.200669E+09 | 0.557413E+09 | 0.150713E+10 | 0.236719E+09 |
September | 0.114511E+10 | 0.594924E+09 | 0.550185E+09 | 0.208896E+10 | 0.449494E+09 |
October | 0.160773E+10 | 0.108693E+10 | 0.520797E+09 | 0.250843E+10 | 0.740293E+09 |
November | 0.187234E+10 | 0.142743E+10 | 0.444911E+09 | 0.259214E+10 | 0.115654E+10 |
December | 0.191742E+10 | 0.143930E+10 | 0.478116E+09 | 0.247468E+10 | 0.150132E+10 |
Annual Sum or Average | 0.149140E+11 | 0.861816E+10 | 0.629583E+10 | 0.228098E+11 | 0.910729E+10 |
Minimum of Months | 0.564571E+09 | 35822221.82 | 0.444911E+09 | 0.117683E+10 | 0.161750E+09 |
Maximum of Months | 0.191742E+10 | 0.143930E+10 | 0.597549E+09 | 0.259214E+10 | 0.150132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187206E+10 | 0.141828E+10 | 0.453778E+09 | 0.247911E+10 | 0.137116E+10 |
February | 0.156849E+10 | 0.110576E+10 | 0.462729E+09 | 0.211129E+10 | 0.112285E+10 |
March | 0.141130E+10 | 0.813751E+09 | 0.597549E+09 | 0.195601E+10 | 0.110179E+10 |
April | 0.925990E+09 | 0.345510E+09 | 0.580480E+09 | 0.144755E+10 | 0.667224E+09 |
May | 0.676200E+09 | 94645750.20 | 0.581554E+09 | 0.117683E+10 | 0.404911E+09 |
June | 0.564571E+09 | 35822178.84 | 0.528749E+09 | 0.120672E+10 | 0.193243E+09 |
July | 0.594702E+09 | 55129860.31 | 0.539572E+09 | 0.126099E+10 | 0.161750E+09 |
August | 0.758081E+09 | 0.200669E+09 | 0.557412E+09 | 0.150713E+10 | 0.236719E+09 |
September | 0.114511E+10 | 0.594923E+09 | 0.550185E+09 | 0.208896E+10 | 0.449493E+09 |
October | 0.160773E+10 | 0.108693E+10 | 0.520796E+09 | 0.250843E+10 | 0.740293E+09 |
November | 0.187234E+10 | 0.142743E+10 | 0.444911E+09 | 0.259213E+10 | 0.115654E+10 |
December | 0.191741E+10 | 0.143930E+10 | 0.478116E+09 | 0.247467E+10 | 0.150132E+10 |
Annual Sum or Average | 0.149140E+11 | 0.861815E+10 | 0.629583E+10 | 0.228098E+11 | 0.910729E+10 |
Minimum of Months | 0.564571E+09 | 35822178.84 | 0.444911E+09 | 0.117683E+10 | 0.161750E+09 |
Maximum of Months | 0.191741E+10 | 0.143930E+10 | 0.597549E+09 | 0.259213E+10 | 0.150132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187206E+10 | 0.141828E+10 | 0.453779E+09 | 0.247911E+10 | 0.137116E+10 |
February | 0.156849E+10 | 0.110576E+10 | 0.462729E+09 | 0.211129E+10 | 0.112285E+10 |
March | 0.141130E+10 | 0.813752E+09 | 0.597549E+09 | 0.195601E+10 | 0.110179E+10 |
April | 0.925990E+09 | 0.345510E+09 | 0.580480E+09 | 0.144756E+10 | 0.667224E+09 |
May | 0.676200E+09 | 94645863.76 | 0.581554E+09 | 0.117683E+10 | 0.404911E+09 |
June | 0.564571E+09 | 35822221.82 | 0.528749E+09 | 0.120673E+10 | 0.193243E+09 |
July | 0.594702E+09 | 55129926.46 | 0.539572E+09 | 0.126099E+10 | 0.161750E+09 |
August | 0.758082E+09 | 0.200669E+09 | 0.557413E+09 | 0.150713E+10 | 0.236719E+09 |
September | 0.114511E+10 | 0.594924E+09 | 0.550185E+09 | 0.208896E+10 | 0.449494E+09 |
October | 0.160773E+10 | 0.108693E+10 | 0.520797E+09 | 0.250843E+10 | 0.740293E+09 |
November | 0.187234E+10 | 0.142743E+10 | 0.444911E+09 | 0.259214E+10 | 0.115654E+10 |
December | 0.191742E+10 | 0.143930E+10 | 0.478116E+09 | 0.247468E+10 | 0.150132E+10 |
Annual Sum or Average | 0.149140E+11 | 0.861816E+10 | 0.629583E+10 | 0.228098E+11 | 0.910729E+10 |
Minimum of Months | 0.564571E+09 | 35822221.82 | 0.444911E+09 | 0.117683E+10 | 0.161750E+09 |
Maximum of Months | 0.191742E+10 | 0.143930E+10 | 0.597549E+09 | 0.259214E+10 | 0.150132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187206E+10 | 0.141828E+10 | 0.453778E+09 | 0.247911E+10 | 0.137116E+10 |
February | 0.156849E+10 | 0.110576E+10 | 0.462729E+09 | 0.211129E+10 | 0.112285E+10 |
March | 0.141130E+10 | 0.813751E+09 | 0.597549E+09 | 0.195601E+10 | 0.110179E+10 |
April | 0.925990E+09 | 0.345510E+09 | 0.580480E+09 | 0.144755E+10 | 0.667224E+09 |
May | 0.676200E+09 | 94645750.20 | 0.581554E+09 | 0.117683E+10 | 0.404911E+09 |
June | 0.564571E+09 | 35822178.84 | 0.528749E+09 | 0.120672E+10 | 0.193243E+09 |
July | 0.594702E+09 | 55129860.31 | 0.539572E+09 | 0.126099E+10 | 0.161750E+09 |
August | 0.758081E+09 | 0.200669E+09 | 0.557412E+09 | 0.150713E+10 | 0.236719E+09 |
September | 0.114511E+10 | 0.594923E+09 | 0.550185E+09 | 0.208896E+10 | 0.449493E+09 |
October | 0.160773E+10 | 0.108693E+10 | 0.520796E+09 | 0.250843E+10 | 0.740293E+09 |
November | 0.187234E+10 | 0.142743E+10 | 0.444911E+09 | 0.259213E+10 | 0.115654E+10 |
December | 0.191741E+10 | 0.143930E+10 | 0.478116E+09 | 0.247467E+10 | 0.150132E+10 |
Annual Sum or Average | 0.149140E+11 | 0.861815E+10 | 0.629583E+10 | 0.228098E+11 | 0.910729E+10 |
Minimum of Months | 0.564571E+09 | 35822178.84 | 0.444911E+09 | 0.117683E+10 | 0.161750E+09 |
Maximum of Months | 0.191741E+10 | 0.143930E+10 | 0.597549E+09 | 0.259213E+10 | 0.150132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187198E+10 | 0.141822E+10 | 0.453760E+09 | 0.247902E+10 | 0.137110E+10 |
February | 0.156843E+10 | 0.110572E+10 | 0.462710E+09 | 0.211121E+10 | 0.112280E+10 |
March | 0.141124E+10 | 0.813719E+09 | 0.597525E+09 | 0.195593E+10 | 0.110175E+10 |
April | 0.925953E+09 | 0.345496E+09 | 0.580457E+09 | 0.144750E+10 | 0.667197E+09 |
May | 0.676173E+09 | 94642049.12 | 0.581531E+09 | 0.117678E+10 | 0.404895E+09 |
June | 0.564549E+09 | 35820778.03 | 0.528728E+09 | 0.120668E+10 | 0.193235E+09 |
July | 0.594678E+09 | 55127704.48 | 0.539551E+09 | 0.126094E+10 | 0.161744E+09 |
August | 0.758051E+09 | 0.200661E+09 | 0.557390E+09 | 0.150707E+10 | 0.236709E+09 |
September | 0.114506E+10 | 0.594900E+09 | 0.550163E+09 | 0.208887E+10 | 0.449475E+09 |
October | 0.160766E+10 | 0.108689E+10 | 0.520776E+09 | 0.250833E+10 | 0.740264E+09 |
November | 0.187227E+10 | 0.142737E+10 | 0.444893E+09 | 0.259203E+10 | 0.115649E+10 |
December | 0.191734E+10 | 0.143924E+10 | 0.478097E+09 | 0.247458E+10 | 0.150126E+10 |
Annual Sum or Average | 0.149134E+11 | 0.861781E+10 | 0.629558E+10 | 0.228089E+11 | 0.910693E+10 |
Minimum of Months | 0.564549E+09 | 35820778.03 | 0.444893E+09 | 0.117678E+10 | 0.161744E+09 |
Maximum of Months | 0.191734E+10 | 0.143924E+10 | 0.597525E+09 | 0.259203E+10 | 0.150126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.856666E+09 | 0.482450E+09 | 0.374216E+09 | 0.880718E+09 | 0.178400E+10 |
February | 0.873112E+09 | 0.464078E+09 | 0.409034E+09 | 0.957506E+09 | 0.148695E+10 |
March | 0.131728E+10 | 0.706016E+09 | 0.611263E+09 | 0.161554E+10 | 0.142095E+10 |
April | 0.146526E+10 | 0.791414E+09 | 0.673847E+09 | 0.210973E+10 | 0.873313E+09 |
May | 0.163083E+10 | 0.872570E+09 | 0.758264E+09 | 0.267395E+10 | 0.522261E+09 |
June | 0.153628E+10 | 0.825152E+09 | 0.711129E+09 | 0.281342E+10 | 0.286221E+09 |
July | 0.140879E+10 | 0.700054E+09 | 0.708732E+09 | 0.256596E+10 | 0.260239E+09 |
August | 0.136434E+10 | 0.695318E+09 | 0.669018E+09 | 0.236611E+10 | 0.369779E+09 |
September | 0.135024E+10 | 0.752219E+09 | 0.598019E+09 | 0.227285E+10 | 0.564112E+09 |
October | 0.120108E+10 | 0.700989E+09 | 0.500090E+09 | 0.173212E+10 | 0.947824E+09 |
November | 0.975609E+09 | 0.594042E+09 | 0.381567E+09 | 0.113494E+10 | 0.156646E+10 |
December | 0.812404E+09 | 0.441324E+09 | 0.371080E+09 | 0.763686E+09 | 0.209773E+10 |
Annual Sum or Average | 0.147919E+11 | 0.802563E+10 | 0.676626E+10 | 0.218865E+11 | 0.121798E+11 |
Minimum of Months | 0.812404E+09 | 0.441324E+09 | 0.371080E+09 | 0.763686E+09 | 0.260239E+09 |
Maximum of Months | 0.163083E+10 | 0.872570E+09 | 0.758264E+09 | 0.281342E+10 | 0.209773E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.856666E+09 | 0.482450E+09 | 0.374216E+09 | 0.880718E+09 | 0.178400E+10 |
February | 0.873112E+09 | 0.464078E+09 | 0.409034E+09 | 0.957506E+09 | 0.148695E+10 |
March | 0.131728E+10 | 0.706016E+09 | 0.611263E+09 | 0.161554E+10 | 0.142095E+10 |
April | 0.146526E+10 | 0.791414E+09 | 0.673847E+09 | 0.210973E+10 | 0.873313E+09 |
May | 0.163083E+10 | 0.872570E+09 | 0.758264E+09 | 0.267395E+10 | 0.522261E+09 |
June | 0.153628E+10 | 0.825152E+09 | 0.711129E+09 | 0.281342E+10 | 0.286221E+09 |
July | 0.140879E+10 | 0.700054E+09 | 0.708732E+09 | 0.256596E+10 | 0.260239E+09 |
August | 0.136434E+10 | 0.695318E+09 | 0.669018E+09 | 0.236611E+10 | 0.369779E+09 |
September | 0.135024E+10 | 0.752219E+09 | 0.598019E+09 | 0.227285E+10 | 0.564112E+09 |
October | 0.120108E+10 | 0.700989E+09 | 0.500090E+09 | 0.173212E+10 | 0.947824E+09 |
November | 0.975609E+09 | 0.594042E+09 | 0.381567E+09 | 0.113494E+10 | 0.156646E+10 |
December | 0.812404E+09 | 0.441324E+09 | 0.371080E+09 | 0.763686E+09 | 0.209773E+10 |
Annual Sum or Average | 0.147919E+11 | 0.802563E+10 | 0.676626E+10 | 0.218865E+11 | 0.121798E+11 |
Minimum of Months | 0.812404E+09 | 0.441324E+09 | 0.371080E+09 | 0.763686E+09 | 0.260239E+09 |
Maximum of Months | 0.163083E+10 | 0.872570E+09 | 0.758264E+09 | 0.281342E+10 | 0.209773E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.856651E+09 | 0.482441E+09 | 0.374209E+09 | 0.880702E+09 | 0.178397E+10 |
February | 0.873096E+09 | 0.464069E+09 | 0.409026E+09 | 0.957489E+09 | 0.148692E+10 |
March | 0.131725E+10 | 0.706003E+09 | 0.611251E+09 | 0.161551E+10 | 0.142092E+10 |
April | 0.146523E+10 | 0.791400E+09 | 0.673835E+09 | 0.210969E+10 | 0.873297E+09 |
May | 0.163080E+10 | 0.872554E+09 | 0.758250E+09 | 0.267390E+10 | 0.522252E+09 |
June | 0.153625E+10 | 0.825137E+09 | 0.711116E+09 | 0.281337E+10 | 0.286216E+09 |
July | 0.140876E+10 | 0.700041E+09 | 0.708719E+09 | 0.256591E+10 | 0.260234E+09 |
August | 0.136431E+10 | 0.695306E+09 | 0.669006E+09 | 0.236606E+10 | 0.369772E+09 |
September | 0.135021E+10 | 0.752206E+09 | 0.598008E+09 | 0.227281E+10 | 0.564101E+09 |
October | 0.120106E+10 | 0.700976E+09 | 0.500081E+09 | 0.173209E+10 | 0.947807E+09 |
November | 0.975591E+09 | 0.594031E+09 | 0.381560E+09 | 0.113492E+10 | 0.156643E+10 |
December | 0.812389E+09 | 0.441316E+09 | 0.371073E+09 | 0.763673E+09 | 0.209769E+10 |
Annual Sum or Average | 0.147916E+11 | 0.802548E+10 | 0.676614E+10 | 0.218861E+11 | 0.121796E+11 |
Minimum of Months | 0.812389E+09 | 0.441316E+09 | 0.371073E+09 | 0.763673E+09 | 0.260234E+09 |
Maximum of Months | 0.163080E+10 | 0.872554E+09 | 0.758250E+09 | 0.281337E+10 | 0.209769E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136826E+10 | 0.00 | 0.136826E+10 | 0.301658E+09 | 0.690516E+10 |
February | 0.150910E+10 | 0.00 | 0.150910E+10 | 0.683386E+09 | 0.561232E+10 |
March | 0.218652E+10 | 0.00 | 0.218652E+10 | 0.151298E+10 | 0.527247E+10 |
April | 0.244314E+10 | 19248427.58 | 0.242389E+10 | 0.280120E+10 | 0.298667E+10 |
May | 0.299424E+10 | 0.216526E+09 | 0.277772E+10 | 0.480643E+10 | 0.180601E+10 |
June | 0.308116E+10 | 0.379327E+09 | 0.270183E+10 | 0.644640E+10 | 0.937279E+09 |
July | 0.294251E+10 | 0.286431E+09 | 0.265608E+10 | 0.612946E+10 | 0.770749E+09 |
August | 0.248118E+10 | 50733647.87 | 0.243044E+10 | 0.478095E+10 | 0.104195E+10 |
September | 0.209521E+10 | 836064.26 | 0.209437E+10 | 0.350837E+10 | 0.207592E+10 |
October | 0.179759E+10 | 0.00 | 0.179759E+10 | 0.190395E+10 | 0.345450E+10 |
November | 0.140437E+10 | 0.00 | 0.140437E+10 | 0.508683E+09 | 0.574186E+10 |
December | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.202177E+09 | 0.766626E+10 |
Annual Sum or Average | 0.256609E+11 | 0.953102E+09 | 0.247078E+11 | 0.335857E+11 | 0.442712E+11 |
Minimum of Months | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.202177E+09 | 0.770749E+09 |
Maximum of Months | 0.308116E+10 | 0.379327E+09 | 0.277772E+10 | 0.644640E+10 | 0.766626E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.243972E+10 | 0.132346E+10 | 0.111626E+10 | 0.230025E+10 | 0.437521E+10 |
February | 0.294823E+10 | 0.168047E+10 | 0.126776E+10 | 0.323548E+10 | 0.355908E+10 |
March | 0.403011E+10 | 0.222046E+10 | 0.180965E+10 | 0.484713E+10 | 0.334744E+10 |
April | 0.469943E+10 | 0.260714E+10 | 0.209230E+10 | 0.674114E+10 | 0.195442E+10 |
May | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.810077E+10 | 0.124501E+10 |
June | 0.485229E+10 | 0.269942E+10 | 0.215287E+10 | 0.883997E+10 | 0.636690E+09 |
July | 0.449650E+10 | 0.235069E+10 | 0.214580E+10 | 0.822764E+10 | 0.535775E+09 |
August | 0.427866E+10 | 0.218978E+10 | 0.208888E+10 | 0.754873E+10 | 0.719182E+09 |
September | 0.410225E+10 | 0.234063E+10 | 0.176162E+10 | 0.675564E+10 | 0.135111E+10 |
October | 0.326005E+10 | 0.175942E+10 | 0.150063E+10 | 0.451755E+10 | 0.226480E+10 |
November | 0.282808E+10 | 0.164642E+10 | 0.118166E+10 | 0.305471E+10 | 0.363710E+10 |
December | 0.243763E+10 | 0.129151E+10 | 0.114612E+10 | 0.216880E+10 | 0.481386E+10 |
Annual Sum or Average | 0.453842E+11 | 0.248328E+11 | 0.205513E+11 | 0.663378E+11 | 0.284397E+11 |
Minimum of Months | 0.243763E+10 | 0.129151E+10 | 0.111626E+10 | 0.216880E+10 | 0.535775E+09 |
Maximum of Months | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.883997E+10 | 0.481386E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936018E+10 | 0.709131E+10 | 0.226887E+10 | 0.122946E+11 | 0.668053E+10 |
February | 0.784236E+10 | 0.552874E+10 | 0.231362E+10 | 0.104752E+11 | 0.546206E+10 |
March | 0.705642E+10 | 0.406871E+10 | 0.298771E+10 | 0.971072E+10 | 0.531524E+10 |
April | 0.462990E+10 | 0.172753E+10 | 0.290237E+10 | 0.723128E+10 | 0.319557E+10 |
May | 0.338096E+10 | 0.473224E+09 | 0.290774E+10 | 0.590388E+10 | 0.195285E+10 |
June | 0.282282E+10 | 0.179109E+09 | 0.264371E+10 | 0.610040E+10 | 0.955755E+09 |
July | 0.297348E+10 | 0.275646E+09 | 0.269783E+10 | 0.636820E+10 | 0.800989E+09 |
August | 0.379036E+10 | 0.100333E+10 | 0.278703E+10 | 0.760371E+10 | 0.112913E+10 |
September | 0.572548E+10 | 0.297458E+10 | 0.275089E+10 | 0.103894E+11 | 0.221136E+10 |
October | 0.803855E+10 | 0.543459E+10 | 0.260395E+10 | 0.124565E+11 | 0.360693E+10 |
November | 0.936160E+10 | 0.713707E+10 | 0.222453E+10 | 0.128887E+11 | 0.558964E+10 |
December | 0.958696E+10 | 0.719641E+10 | 0.239055E+10 | 0.123454E+11 | 0.720500E+10 |
Annual Sum or Average | 0.745691E+11 | 0.430903E+11 | 0.314788E+11 | 0.113768E+12 | 0.441051E+11 |
Minimum of Months | 0.282282E+10 | 0.179109E+09 | 0.222453E+10 | 0.590388E+10 | 0.800989E+09 |
Maximum of Months | 0.958696E+10 | 0.719641E+10 | 0.298771E+10 | 0.128887E+11 | 0.720500E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256997E+10 | 0.144734E+10 | 0.112264E+10 | 0.274065E+10 | 0.471160E+10 |
February | 0.261931E+10 | 0.139222E+10 | 0.122709E+10 | 0.297741E+10 | 0.389151E+10 |
March | 0.395180E+10 | 0.211803E+10 | 0.183377E+10 | 0.496318E+10 | 0.371702E+10 |
April | 0.439574E+10 | 0.237422E+10 | 0.202152E+10 | 0.645520E+10 | 0.225357E+10 |
May | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.803437E+10 | 0.144649E+10 |
June | 0.460880E+10 | 0.247543E+10 | 0.213336E+10 | 0.851440E+10 | 0.764598E+09 |
July | 0.422631E+10 | 0.210014E+10 | 0.212617E+10 | 0.781860E+10 | 0.650596E+09 |
August | 0.409297E+10 | 0.208593E+10 | 0.200703E+10 | 0.727907E+10 | 0.859771E+09 |
September | 0.405067E+10 | 0.225664E+10 | 0.179404E+10 | 0.685205E+10 | 0.156345E+10 |
October | 0.360320E+10 | 0.210295E+10 | 0.150025E+10 | 0.528115E+10 | 0.252132E+10 |
November | 0.292680E+10 | 0.178211E+10 | 0.114469E+10 | 0.352946E+10 | 0.399243E+10 |
December | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.245671E+10 | 0.517482E+10 |
Annual Sum or Average | 0.443752E+11 | 0.240766E+11 | 0.202986E+11 | 0.669022E+11 | 0.315472E+11 |
Minimum of Months | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.245671E+10 | 0.650596E+09 |
Maximum of Months | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.851440E+10 | 0.517482E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136826E+10 | 0.00 | 0.136826E+10 | 0.414192E+09 | 0.621446E+10 |
February | 0.150910E+10 | 0.00 | 0.150910E+10 | 0.795853E+09 | 0.512127E+10 |
March | 0.218652E+10 | 0.00 | 0.218652E+10 | 0.163022E+10 | 0.489193E+10 |
April | 0.244314E+10 | 19248427.58 | 0.242389E+10 | 0.281833E+10 | 0.285720E+10 |
May | 0.299424E+10 | 0.216526E+09 | 0.277772E+10 | 0.476337E+10 | 0.178782E+10 |
June | 0.308116E+10 | 0.379327E+09 | 0.270183E+10 | 0.636302E+10 | 0.957958E+09 |
July | 0.294251E+10 | 0.286431E+09 | 0.265608E+10 | 0.602524E+10 | 0.805391E+09 |
August | 0.248118E+10 | 50733647.87 | 0.243044E+10 | 0.470193E+10 | 0.105583E+10 |
September | 0.209521E+10 | 836064.26 | 0.209437E+10 | 0.347463E+10 | 0.204512E+10 |
October | 0.179759E+10 | 0.00 | 0.179759E+10 | 0.196159E+10 | 0.323121E+10 |
November | 0.140437E+10 | 0.00 | 0.140437E+10 | 0.622749E+09 | 0.515938E+10 |
December | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.305337E+09 | 0.691655E+10 |
Annual Sum or Average | 0.256609E+11 | 0.953102E+09 | 0.247078E+11 | 0.338764E+11 | 0.410441E+11 |
Minimum of Months | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.305337E+09 | 0.805391E+09 |
Maximum of Months | 0.308116E+10 | 0.379327E+09 | 0.277772E+10 | 0.636302E+10 | 0.691655E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.243972E+10 | 0.132346E+10 | 0.111626E+10 | 0.244221E+10 | 0.391539E+10 |
February | 0.294823E+10 | 0.168047E+10 | 0.126776E+10 | 0.335007E+10 | 0.325432E+10 |
March | 0.403011E+10 | 0.222046E+10 | 0.180965E+10 | 0.494030E+10 | 0.314237E+10 |
April | 0.469943E+10 | 0.260714E+10 | 0.209230E+10 | 0.674961E+10 | 0.189507E+10 |
May | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.807553E+10 | 0.123472E+10 |
June | 0.485229E+10 | 0.269942E+10 | 0.215287E+10 | 0.879389E+10 | 0.648372E+09 |
July | 0.449650E+10 | 0.235069E+10 | 0.214580E+10 | 0.817174E+10 | 0.555272E+09 |
August | 0.427866E+10 | 0.218978E+10 | 0.208888E+10 | 0.750933E+10 | 0.728240E+09 |
September | 0.410225E+10 | 0.234063E+10 | 0.176162E+10 | 0.674122E+10 | 0.133719E+10 |
October | 0.326005E+10 | 0.175942E+10 | 0.150063E+10 | 0.455992E+10 | 0.214234E+10 |
November | 0.282808E+10 | 0.164642E+10 | 0.118166E+10 | 0.317549E+10 | 0.329755E+10 |
December | 0.243763E+10 | 0.129151E+10 | 0.114612E+10 | 0.232805E+10 | 0.431418E+10 |
Annual Sum or Average | 0.453842E+11 | 0.248328E+11 | 0.205513E+11 | 0.668373E+11 | 0.264650E+11 |
Minimum of Months | 0.243763E+10 | 0.129151E+10 | 0.111626E+10 | 0.232805E+10 | 0.555272E+09 |
Maximum of Months | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.879389E+10 | 0.431418E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936018E+10 | 0.709131E+10 | 0.226887E+10 | 0.124518E+11 | 0.609404E+10 |
February | 0.784236E+10 | 0.552874E+10 | 0.231362E+10 | 0.105878E+11 | 0.505022E+10 |
March | 0.705642E+10 | 0.406871E+10 | 0.298771E+10 | 0.979309E+10 | 0.500283E+10 |
April | 0.462990E+10 | 0.172753E+10 | 0.290237E+10 | 0.722185E+10 | 0.307794E+10 |
May | 0.338096E+10 | 0.473224E+09 | 0.290774E+10 | 0.585048E+10 | 0.192719E+10 |
June | 0.282282E+10 | 0.179109E+09 | 0.264371E+10 | 0.601862E+10 | 0.975264E+09 |
July | 0.297348E+10 | 0.275646E+09 | 0.269783E+10 | 0.626333E+10 | 0.834758E+09 |
August | 0.379036E+10 | 0.100333E+10 | 0.278703E+10 | 0.752215E+10 | 0.114475E+10 |
September | 0.572548E+10 | 0.297458E+10 | 0.275089E+10 | 0.103424E+11 | 0.218652E+10 |
October | 0.803855E+10 | 0.543459E+10 | 0.260395E+10 | 0.124869E+11 | 0.343624E+10 |
November | 0.936160E+10 | 0.713707E+10 | 0.222453E+10 | 0.130345E+11 | 0.515917E+10 |
December | 0.958696E+10 | 0.719641E+10 | 0.239055E+10 | 0.125557E+11 | 0.658436E+10 |
Annual Sum or Average | 0.745691E+11 | 0.430903E+11 | 0.314788E+11 | 0.114129E+12 | 0.414733E+11 |
Minimum of Months | 0.282282E+10 | 0.179109E+09 | 0.222453E+10 | 0.585048E+10 | 0.834758E+09 |
Maximum of Months | 0.958696E+10 | 0.719641E+10 | 0.298771E+10 | 0.130345E+11 | 0.658436E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256997E+10 | 0.144734E+10 | 0.112264E+10 | 0.281050E+10 | 0.432404E+10 |
February | 0.261931E+10 | 0.139222E+10 | 0.122709E+10 | 0.303176E+10 | 0.361120E+10 |
March | 0.395180E+10 | 0.211803E+10 | 0.183377E+10 | 0.500330E+10 | 0.350117E+10 |
April | 0.439574E+10 | 0.237422E+10 | 0.202152E+10 | 0.644070E+10 | 0.217560E+10 |
May | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.798685E+10 | 0.142676E+10 |
June | 0.460880E+10 | 0.247543E+10 | 0.213336E+10 | 0.845525E+10 | 0.775795E+09 |
July | 0.422631E+10 | 0.210014E+10 | 0.212617E+10 | 0.775369E+10 | 0.668458E+09 |
August | 0.409297E+10 | 0.208593E+10 | 0.200703E+10 | 0.722570E+10 | 0.867489E+09 |
September | 0.405067E+10 | 0.225664E+10 | 0.179404E+10 | 0.681842E+10 | 0.154574E+10 |
October | 0.360320E+10 | 0.210295E+10 | 0.150025E+10 | 0.529085E+10 | 0.240430E+10 |
November | 0.292680E+10 | 0.178211E+10 | 0.114469E+10 | 0.358891E+10 | 0.367960E+10 |
December | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.253163E+10 | 0.475304E+10 |
Annual Sum or Average | 0.443752E+11 | 0.240766E+11 | 0.202986E+11 | 0.669375E+11 | 0.297332E+11 |
Minimum of Months | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.253163E+10 | 0.668458E+09 |
Maximum of Months | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.845525E+10 | 0.475304E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 62.15 | 2928.30 | 510.85 | 0.00 | 510.85 | 0.00 | 0.00 |
February | 217.96 | 2600.61 | 623.80 | 0.00 | 623.80 | 0.00 | 0.00 |
March | 500.15 | 2185.62 | 816.36 | 0.00 | 816.36 | 0.00 | 0.00 |
April | 1029.93 | 1253.42 | 942.57 | 7.43 | 935.15 | 0.00 | 0.00 |
May | 1774.73 | 705.77 | 1117.93 | 80.84 | 1037.09 | 0.00 | 0.00 |
June | 2468.18 | 361.62 | 1188.72 | 146.35 | 1042.38 | 0.00 | 0.00 |
July | 2265.27 | 288.68 | 1098.61 | 106.94 | 991.67 | 0.00 | 0.00 |
August | 1737.26 | 417.30 | 926.37 | 18.94 | 907.43 | 0.00 | 0.00 |
September | 1329.49 | 842.40 | 808.34 | 0.32 | 808.02 | 0.00 | 0.00 |
October | 663.24 | 1419.96 | 671.15 | 0.00 | 671.15 | 0.00 | 0.00 |
November | 137.61 | 2540.52 | 541.81 | 0.00 | 541.81 | 0.00 | 0.00 |
December | 35.70 | 3333.58 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
Annual Sum or Average | 1022.61 | 1568.25 | 813.71 | 30.22 | 783.48 | 0.00 | 0.00 |
Minimum of Months | 35.70 | 288.68 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
Maximum of Months | 2468.18 | 3333.58 | 1188.72 | 146.35 | 1042.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 838.46 | 1783.41 | 910.89 | 494.13 | 416.77 | 0.00 | 0.00 |
February | 1329.38 | 1569.25 | 1218.69 | 694.64 | 524.04 | 0.00 | 0.00 |
March | 1815.22 | 1311.70 | 1504.68 | 829.03 | 675.65 | 0.00 | 0.00 |
April | 2626.79 | 765.57 | 1813.06 | 1005.84 | 807.22 | 0.00 | 0.00 |
May | 3053.30 | 470.55 | 1870.98 | 1016.81 | 854.17 | 0.00 | 0.00 |
June | 3440.53 | 232.53 | 1872.03 | 1041.45 | 830.59 | 0.00 | 0.00 |
July | 3100.95 | 182.45 | 1678.81 | 877.65 | 801.16 | 0.00 | 0.00 |
August | 2840.38 | 256.38 | 1597.47 | 817.57 | 779.90 | 0.00 | 0.00 |
September | 2628.00 | 526.83 | 1582.66 | 903.03 | 679.64 | 0.00 | 0.00 |
October | 1695.58 | 885.79 | 1217.17 | 656.89 | 560.27 | 0.00 | 0.00 |
November | 1166.79 | 1513.16 | 1091.08 | 635.19 | 455.89 | 0.00 | 0.00 |
December | 784.10 | 1969.85 | 910.11 | 482.20 | 427.91 | 0.00 | 0.00 |
Annual Sum or Average | 2112.48 | 952.73 | 1439.13 | 787.45 | 651.68 | 0.00 | 0.00 |
Minimum of Months | 784.10 | 182.45 | 910.11 | 482.20 | 416.77 | 0.00 | 0.00 |
Maximum of Months | 3440.53 | 1969.85 | 1872.03 | 1041.45 | 854.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4627.94 | 2559.64 | 3494.70 | 2647.60 | 847.10 | 0.00 | 0.00 |
February | 4363.58 | 2320.68 | 3241.73 | 2285.37 | 956.36 | 0.00 | 0.00 |
March | 3651.43 | 2056.79 | 2634.58 | 1519.09 | 1115.49 | 0.00 | 0.00 |
April | 2792.33 | 1287.07 | 1786.23 | 666.49 | 1119.74 | 0.00 | 0.00 |
May | 2196.86 | 755.88 | 1262.31 | 176.68 | 1085.63 | 0.00 | 0.00 |
June | 2327.77 | 372.77 | 1089.06 | 69.10 | 1019.96 | 0.00 | 0.00 |
July | 2353.97 | 301.95 | 1110.17 | 102.91 | 1007.26 | 0.00 | 0.00 |
August | 2813.47 | 441.90 | 1415.16 | 374.60 | 1040.56 | 0.00 | 0.00 |
September | 4029.59 | 867.07 | 2208.91 | 1147.61 | 1061.30 | 0.00 | 0.00 |
October | 4682.66 | 1381.96 | 3001.26 | 2029.05 | 972.21 | 0.00 | 0.00 |
November | 5000.22 | 2230.96 | 3611.74 | 2753.51 | 858.23 | 0.00 | 0.00 |
December | 4619.65 | 2802.63 | 3579.37 | 2686.84 | 892.53 | 0.00 | 0.00 |
Annual Sum or Average | 3616.45 | 1443.94 | 2364.58 | 1366.39 | 998.19 | 0.00 | 0.00 |
Minimum of Months | 2196.86 | 301.95 | 1089.06 | 69.10 | 847.10 | 0.00 | 0.00 |
Maximum of Months | 5000.22 | 2802.63 | 3611.74 | 2753.51 | 1119.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 986.46 | 1998.20 | 959.52 | 540.38 | 419.15 | 0.00 | 0.00 |
February | 1187.38 | 1843.92 | 1082.72 | 575.49 | 507.23 | 0.00 | 0.00 |
March | 1809.51 | 1591.55 | 1475.44 | 790.78 | 684.65 | 0.00 | 0.00 |
April | 2441.80 | 1010.77 | 1695.89 | 915.98 | 779.91 | 0.00 | 0.00 |
May | 2994.99 | 584.97 | 1826.64 | 977.34 | 849.30 | 0.00 | 0.00 |
June | 3256.25 | 331.27 | 1778.09 | 955.03 | 823.06 | 0.00 | 0.00 |
July | 2874.04 | 291.48 | 1577.93 | 784.11 | 793.83 | 0.00 | 0.00 |
August | 2650.19 | 414.18 | 1528.15 | 778.80 | 749.34 | 0.00 | 0.00 |
September | 2630.59 | 652.90 | 1562.77 | 870.62 | 692.15 | 0.00 | 0.00 |
October | 1940.09 | 1061.62 | 1345.29 | 785.15 | 560.13 | 0.00 | 0.00 |
November | 1313.59 | 1813.02 | 1129.17 | 687.54 | 441.63 | 0.00 | 0.00 |
December | 855.38 | 2349.59 | 909.95 | 494.31 | 415.63 | 0.00 | 0.00 |
Annual Sum or Average | 2082.04 | 1158.65 | 1407.13 | 763.47 | 643.67 | 0.00 | 0.00 |
Minimum of Months | 855.38 | 291.48 | 909.95 | 494.31 | 415.63 | 0.00 | 0.00 |
Maximum of Months | 3256.25 | 2349.59 | 1826.64 | 977.34 | 849.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 112.63 | 2578.09 | 510.85 | 0.00 | 510.85 | 0.00 | 0.00 |
February | 282.48 | 2319.91 | 623.80 | 0.00 | 623.80 | 0.00 | 0.00 |
March | 564.88 | 1968.51 | 816.35 | 0.00 | 816.35 | 0.00 | 0.00 |
April | 1080.71 | 1152.26 | 942.57 | 7.43 | 935.14 | 0.00 | 0.00 |
May | 1794.52 | 674.29 | 1117.92 | 80.84 | 1037.08 | 0.00 | 0.00 |
June | 2487.04 | 361.60 | 1188.72 | 146.35 | 1042.37 | 0.00 | 0.00 |
July | 2288.48 | 287.76 | 1098.61 | 106.94 | 991.67 | 0.00 | 0.00 |
August | 1785.00 | 389.02 | 926.37 | 18.94 | 907.42 | 0.00 | 0.00 |
September | 1353.54 | 800.90 | 808.34 | 0.32 | 808.01 | 0.00 | 0.00 |
October | 710.86 | 1289.76 | 671.14 | 0.00 | 671.14 | 0.00 | 0.00 |
November | 196.25 | 2215.22 | 541.81 | 0.00 | 541.81 | 0.00 | 0.00 |
December | 75.48 | 2862.25 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
Annual Sum or Average | 1064.99 | 1403.83 | 813.70 | 30.22 | 783.48 | 0.00 | 0.00 |
Minimum of Months | 75.48 | 287.76 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
Maximum of Months | 2487.04 | 2862.25 | 1188.72 | 146.35 | 1042.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 858.81 | 1633.51 | 910.89 | 494.12 | 416.76 | 0.00 | 0.00 |
February | 1337.42 | 1471.18 | 1218.68 | 694.64 | 524.04 | 0.00 | 0.00 |
March | 1809.71 | 1249.79 | 1504.67 | 829.03 | 675.65 | 0.00 | 0.00 |
April | 2600.75 | 754.02 | 1813.05 | 1005.84 | 807.21 | 0.00 | 0.00 |
May | 3024.48 | 464.83 | 1870.97 | 1016.80 | 854.17 | 0.00 | 0.00 |
June | 3410.48 | 245.64 | 1872.03 | 1041.44 | 830.58 | 0.00 | 0.00 |
July | 3071.85 | 200.04 | 1678.80 | 877.65 | 801.15 | 0.00 | 0.00 |
August | 2818.37 | 268.51 | 1597.47 | 817.57 | 779.90 | 0.00 | 0.00 |
September | 2606.34 | 521.26 | 1582.66 | 903.02 | 679.64 | 0.00 | 0.00 |
October | 1686.66 | 845.58 | 1217.16 | 656.89 | 560.27 | 0.00 | 0.00 |
November | 1178.51 | 1403.20 | 1091.08 | 635.19 | 455.89 | 0.00 | 0.00 |
December | 809.74 | 1797.29 | 910.11 | 482.19 | 427.91 | 0.00 | 0.00 |
Annual Sum or Average | 2103.56 | 901.82 | 1439.12 | 787.44 | 651.68 | 0.00 | 0.00 |
Minimum of Months | 809.74 | 200.04 | 910.11 | 482.19 | 416.76 | 0.00 | 0.00 |
Maximum of Months | 3410.48 | 1797.29 | 1872.03 | 1041.44 | 854.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4590.28 | 2494.23 | 3494.69 | 2647.59 | 847.10 | 0.00 | 0.00 |
February | 4330.03 | 2257.80 | 3241.71 | 2285.36 | 956.36 | 0.00 | 0.00 |
March | 3625.57 | 1984.48 | 2634.57 | 1519.08 | 1115.48 | 0.00 | 0.00 |
April | 2789.84 | 1232.86 | 1786.23 | 666.49 | 1119.74 | 0.00 | 0.00 |
May | 2204.26 | 729.11 | 1262.31 | 176.68 | 1085.62 | 0.00 | 0.00 |
June | 2353.55 | 368.73 | 1089.05 | 69.10 | 1019.95 | 0.00 | 0.00 |
July | 2377.61 | 299.06 | 1110.17 | 102.91 | 1007.25 | 0.00 | 0.00 |
August | 2838.90 | 421.57 | 1415.16 | 374.60 | 1040.56 | 0.00 | 0.00 |
September | 4008.24 | 853.15 | 2208.90 | 1147.60 | 1061.30 | 0.00 | 0.00 |
October | 4650.73 | 1346.67 | 3001.25 | 2029.04 | 972.20 | 0.00 | 0.00 |
November | 4972.48 | 2156.50 | 3611.73 | 2753.50 | 858.23 | 0.00 | 0.00 |
December | 4609.26 | 2690.04 | 3579.36 | 2686.83 | 892.53 | 0.00 | 0.00 |
Annual Sum or Average | 3607.56 | 1398.56 | 2364.57 | 1366.38 | 998.19 | 0.00 | 0.00 |
Minimum of Months | 2204.26 | 299.06 | 1089.05 | 69.10 | 847.10 | 0.00 | 0.00 |
Maximum of Months | 4972.48 | 2690.04 | 3611.73 | 2753.50 | 1119.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1023.24 | 1759.11 | 959.52 | 540.37 | 419.14 | 0.00 | 0.00 |
February | 1230.74 | 1608.59 | 1082.72 | 575.49 | 507.23 | 0.00 | 0.00 |
March | 1853.04 | 1387.78 | 1475.43 | 790.78 | 684.65 | 0.00 | 0.00 |
April | 2490.43 | 869.43 | 1695.89 | 915.98 | 779.91 | 0.00 | 0.00 |
May | 2999.69 | 540.06 | 1826.63 | 977.33 | 849.30 | 0.00 | 0.00 |
June | 3284.87 | 294.98 | 1778.08 | 955.03 | 823.06 | 0.00 | 0.00 |
July | 2919.13 | 242.90 | 1577.92 | 784.10 | 793.82 | 0.00 | 0.00 |
August | 2717.69 | 321.00 | 1528.14 | 778.80 | 749.34 | 0.00 | 0.00 |
September | 2643.54 | 603.18 | 1562.76 | 870.62 | 692.14 | 0.00 | 0.00 |
October | 1971.76 | 941.35 | 1345.28 | 785.15 | 560.13 | 0.00 | 0.00 |
November | 1361.67 | 1540.29 | 1129.17 | 687.54 | 441.62 | 0.00 | 0.00 |
December | 917.23 | 1932.06 | 909.94 | 494.31 | 415.63 | 0.00 | 0.00 |
Annual Sum or Average | 2121.46 | 1000.35 | 1407.13 | 763.47 | 643.66 | 0.00 | 0.00 |
Minimum of Months | 917.23 | 242.90 | 909.94 | 494.31 | 415.63 | 0.00 | 0.00 |
Maximum of Months | 3284.87 | 1932.06 | 1826.63 | 977.33 | 849.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 154.64 | 2320.21 | 510.85 | 0.00 | 510.85 | 0.00 | 0.00 |
February | 328.97 | 2116.93 | 623.80 | 0.00 | 623.80 | 0.00 | 0.00 |
March | 608.65 | 1826.44 | 816.35 | 0.00 | 816.35 | 0.00 | 0.00 |
April | 1087.32 | 1102.31 | 942.57 | 7.43 | 935.14 | 0.00 | 0.00 |
May | 1778.44 | 667.49 | 1117.92 | 80.84 | 1037.08 | 0.00 | 0.00 |
June | 2454.87 | 369.58 | 1188.72 | 146.35 | 1042.37 | 0.00 | 0.00 |
July | 2249.57 | 300.70 | 1098.61 | 106.94 | 991.67 | 0.00 | 0.00 |
August | 1755.50 | 394.20 | 926.37 | 18.94 | 907.42 | 0.00 | 0.00 |
September | 1340.52 | 789.01 | 808.34 | 0.32 | 808.01 | 0.00 | 0.00 |
October | 732.37 | 1206.40 | 671.14 | 0.00 | 671.14 | 0.00 | 0.00 |
November | 240.26 | 1990.50 | 541.81 | 0.00 | 541.81 | 0.00 | 0.00 |
December | 114.00 | 2582.34 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
Annual Sum or Average | 1074.22 | 1301.50 | 813.70 | 30.22 | 783.48 | 0.00 | 0.00 |
Minimum of Months | 114.00 | 300.70 | 506.89 | 0.00 | 506.89 | 0.00 | 0.00 |
Maximum of Months | 2454.87 | 2582.34 | 1188.72 | 146.35 | 1042.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 911.82 | 1461.84 | 910.89 | 494.12 | 416.76 | 0.00 | 0.00 |
February | 1384.78 | 1345.20 | 1218.68 | 694.64 | 524.04 | 0.00 | 0.00 |
March | 1844.50 | 1173.23 | 1504.67 | 829.03 | 675.65 | 0.00 | 0.00 |
April | 2604.02 | 731.12 | 1813.05 | 1005.84 | 807.21 | 0.00 | 0.00 |
May | 3015.06 | 460.99 | 1870.97 | 1016.80 | 854.17 | 0.00 | 0.00 |
June | 3392.70 | 250.14 | 1872.03 | 1041.44 | 830.58 | 0.00 | 0.00 |
July | 3050.98 | 207.31 | 1678.80 | 877.65 | 801.15 | 0.00 | 0.00 |
August | 2803.66 | 271.89 | 1597.47 | 817.57 | 779.90 | 0.00 | 0.00 |
September | 2600.78 | 515.89 | 1582.66 | 903.02 | 679.64 | 0.00 | 0.00 |
October | 1702.48 | 799.86 | 1217.16 | 656.89 | 560.27 | 0.00 | 0.00 |
November | 1225.11 | 1272.20 | 1091.08 | 635.19 | 455.89 | 0.00 | 0.00 |
December | 869.19 | 1610.73 | 910.11 | 482.19 | 427.91 | 0.00 | 0.00 |
Annual Sum or Average | 2119.40 | 839.20 | 1439.12 | 787.44 | 651.68 | 0.00 | 0.00 |
Minimum of Months | 869.19 | 207.31 | 910.11 | 482.19 | 416.76 | 0.00 | 0.00 |
Maximum of Months | 3392.70 | 1610.73 | 1872.03 | 1041.44 | 854.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4648.98 | 2275.26 | 3494.69 | 2647.59 | 847.10 | 0.00 | 0.00 |
February | 4376.58 | 2087.56 | 3241.71 | 2285.36 | 956.36 | 0.00 | 0.00 |
March | 3656.32 | 1867.84 | 2634.57 | 1519.08 | 1115.48 | 0.00 | 0.00 |
April | 2786.21 | 1187.48 | 1786.23 | 666.49 | 1119.74 | 0.00 | 0.00 |
May | 2184.32 | 719.53 | 1262.31 | 176.68 | 1085.62 | 0.00 | 0.00 |
June | 2322.00 | 376.26 | 1089.05 | 69.10 | 1019.95 | 0.00 | 0.00 |
July | 2338.46 | 311.66 | 1110.17 | 102.91 | 1007.25 | 0.00 | 0.00 |
August | 2808.45 | 427.40 | 1415.16 | 374.60 | 1040.56 | 0.00 | 0.00 |
September | 3990.13 | 843.56 | 2208.90 | 1147.60 | 1061.30 | 0.00 | 0.00 |
October | 4662.09 | 1282.94 | 3001.25 | 2029.04 | 972.20 | 0.00 | 0.00 |
November | 5028.73 | 1990.42 | 3611.73 | 2753.50 | 858.23 | 0.00 | 0.00 |
December | 4687.77 | 2458.32 | 3579.36 | 2686.83 | 892.53 | 0.00 | 0.00 |
Annual Sum or Average | 3619.00 | 1315.11 | 2364.57 | 1366.38 | 998.19 | 0.00 | 0.00 |
Minimum of Months | 2184.32 | 311.66 | 1089.05 | 69.10 | 847.10 | 0.00 | 0.00 |
Maximum of Months | 5028.73 | 2458.32 | 3611.73 | 2753.50 | 1119.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1049.32 | 1614.41 | 959.52 | 540.37 | 419.14 | 0.00 | 0.00 |
February | 1253.21 | 1492.72 | 1082.72 | 575.49 | 507.23 | 0.00 | 0.00 |
March | 1868.02 | 1307.19 | 1475.43 | 790.78 | 684.65 | 0.00 | 0.00 |
April | 2484.84 | 839.35 | 1695.89 | 915.98 | 779.91 | 0.00 | 0.00 |
May | 2981.95 | 532.69 | 1826.63 | 977.33 | 849.30 | 0.00 | 0.00 |
June | 3262.05 | 299.30 | 1778.08 | 955.03 | 823.06 | 0.00 | 0.00 |
July | 2894.90 | 249.57 | 1577.92 | 784.10 | 793.82 | 0.00 | 0.00 |
August | 2697.77 | 323.88 | 1528.14 | 778.80 | 749.34 | 0.00 | 0.00 |
September | 2630.56 | 596.35 | 1562.76 | 870.62 | 692.14 | 0.00 | 0.00 |
October | 1975.38 | 897.66 | 1345.28 | 785.15 | 560.13 | 0.00 | 0.00 |
November | 1384.61 | 1419.60 | 1129.17 | 687.54 | 441.62 | 0.00 | 0.00 |
December | 945.20 | 1774.58 | 909.94 | 494.31 | 415.63 | 0.00 | 0.00 |
Annual Sum or Average | 2122.58 | 942.83 | 1407.13 | 763.47 | 643.66 | 0.00 | 0.00 |
Minimum of Months | 945.20 | 249.57 | 909.94 | 494.31 | 415.63 | 0.00 | 0.00 |
Maximum of Months | 3262.05 | 1774.58 | 1826.63 | 977.33 | 849.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166460E+09 | 0.784315E+10 | 0.136826E+10 | 0.00 | 0.136826E+10 | 0.00 | 0.00 |
February | 0.527297E+09 | 0.629140E+10 | 0.150910E+10 | 0.00 | 0.150910E+10 | 0.00 | 0.00 |
March | 0.133961E+10 | 0.585397E+10 | 0.218653E+10 | 0.00 | 0.218653E+10 | 0.00 | 0.00 |
April | 0.266959E+10 | 0.324886E+10 | 0.244315E+10 | 19248495.93 | 0.242390E+10 | 0.00 | 0.00 |
May | 0.475344E+10 | 0.189033E+10 | 0.299426E+10 | 0.216526E+09 | 0.277773E+10 | 0.00 | 0.00 |
June | 0.639752E+10 | 0.937319E+09 | 0.308117E+10 | 0.379328E+09 | 0.270184E+10 | 0.00 | 0.00 |
July | 0.606730E+10 | 0.773209E+09 | 0.294252E+10 | 0.286432E+09 | 0.265609E+10 | 0.00 | 0.00 |
August | 0.465306E+10 | 0.111769E+10 | 0.248119E+10 | 50733828.02 | 0.243045E+10 | 0.00 | 0.00 |
September | 0.344604E+10 | 0.218350E+10 | 0.209522E+10 | 836067.23 | 0.209438E+10 | 0.00 | 0.00 |
October | 0.177643E+10 | 0.380321E+10 | 0.179760E+10 | 0.00 | 0.179760E+10 | 0.00 | 0.00 |
November | 0.356689E+09 | 0.658502E+10 | 0.140438E+10 | 0.00 | 0.140438E+10 | 0.00 | 0.00 |
December | 95617888.13 | 0.892867E+10 | 0.135767E+10 | 0.00 | 0.135767E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.322491E+11 | 0.494563E+11 | 0.256610E+11 | 0.953105E+09 | 0.247079E+11 | 0.00 | 0.00 |
Minimum of Months | 95617888.13 | 0.773209E+09 | 0.135767E+10 | 0.00 | 0.135767E+10 | 0.00 | 0.00 |
Maximum of Months | 0.639752E+10 | 0.892867E+10 | 0.308117E+10 | 0.379328E+09 | 0.277773E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.224573E+10 | 0.477670E+10 | 0.243973E+10 | 0.132347E+10 | 0.111626E+10 | 0.00 | 0.00 |
February | 0.321604E+10 | 0.379633E+10 | 0.294824E+10 | 0.168048E+10 | 0.126776E+10 | 0.00 | 0.00 |
March | 0.486189E+10 | 0.351326E+10 | 0.403013E+10 | 0.222047E+10 | 0.180966E+10 | 0.00 | 0.00 |
April | 0.680863E+10 | 0.198437E+10 | 0.469945E+10 | 0.260715E+10 | 0.209231E+10 | 0.00 | 0.00 |
May | 0.817796E+10 | 0.126033E+10 | 0.501123E+10 | 0.272342E+10 | 0.228781E+10 | 0.00 | 0.00 |
June | 0.891786E+10 | 0.602713E+09 | 0.485231E+10 | 0.269943E+10 | 0.215288E+10 | 0.00 | 0.00 |
July | 0.830559E+10 | 0.488664E+09 | 0.449651E+10 | 0.235070E+10 | 0.214581E+10 | 0.00 | 0.00 |
August | 0.760767E+10 | 0.686675E+09 | 0.427868E+10 | 0.218979E+10 | 0.208889E+10 | 0.00 | 0.00 |
September | 0.681177E+10 | 0.136553E+10 | 0.410226E+10 | 0.234064E+10 | 0.176162E+10 | 0.00 | 0.00 |
October | 0.454145E+10 | 0.237249E+10 | 0.326006E+10 | 0.175943E+10 | 0.150064E+10 | 0.00 | 0.00 |
November | 0.302431E+10 | 0.392211E+10 | 0.282809E+10 | 0.164642E+10 | 0.118167E+10 | 0.00 | 0.00 |
December | 0.210012E+10 | 0.527604E+10 | 0.243764E+10 | 0.129151E+10 | 0.114612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.666190E+11 | 0.300452E+11 | 0.453843E+11 | 0.248329E+11 | 0.205514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.210012E+10 | 0.488664E+09 | 0.243764E+10 | 0.129151E+10 | 0.111626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.891786E+10 | 0.527604E+10 | 0.501123E+10 | 0.272342E+10 | 0.228781E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123955E+11 | 0.685574E+10 | 0.936021E+10 | 0.709134E+10 | 0.226887E+10 | 0.00 | 0.00 |
February | 0.105564E+11 | 0.561419E+10 | 0.784238E+10 | 0.552876E+10 | 0.231363E+10 | 0.00 | 0.00 |
March | 0.977998E+10 | 0.550891E+10 | 0.705645E+10 | 0.406873E+10 | 0.298772E+10 | 0.00 | 0.00 |
April | 0.723772E+10 | 0.333609E+10 | 0.462991E+10 | 0.172754E+10 | 0.290238E+10 | 0.00 | 0.00 |
May | 0.588408E+10 | 0.202454E+10 | 0.338097E+10 | 0.473225E+09 | 0.290775E+10 | 0.00 | 0.00 |
June | 0.603358E+10 | 0.966208E+09 | 0.282283E+10 | 0.179110E+09 | 0.264372E+10 | 0.00 | 0.00 |
July | 0.630489E+10 | 0.808745E+09 | 0.297349E+10 | 0.275647E+09 | 0.269784E+10 | 0.00 | 0.00 |
August | 0.753560E+10 | 0.118358E+10 | 0.379038E+10 | 0.100334E+10 | 0.278704E+10 | 0.00 | 0.00 |
September | 0.104447E+11 | 0.224745E+10 | 0.572550E+10 | 0.297459E+10 | 0.275090E+10 | 0.00 | 0.00 |
October | 0.125420E+11 | 0.370144E+10 | 0.803857E+10 | 0.543461E+10 | 0.260396E+10 | 0.00 | 0.00 |
November | 0.129606E+11 | 0.578265E+10 | 0.936163E+10 | 0.713710E+10 | 0.222454E+10 | 0.00 | 0.00 |
December | 0.123733E+11 | 0.750655E+10 | 0.958700E+10 | 0.719644E+10 | 0.239056E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114048E+12 | 0.455361E+11 | 0.745693E+11 | 0.430904E+11 | 0.314789E+11 | 0.00 | 0.00 |
Minimum of Months | 0.588408E+10 | 0.808745E+09 | 0.282283E+10 | 0.179110E+09 | 0.222454E+10 | 0.00 | 0.00 |
Maximum of Months | 0.129606E+11 | 0.750655E+10 | 0.958700E+10 | 0.719644E+10 | 0.298772E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264214E+10 | 0.535197E+10 | 0.256998E+10 | 0.144734E+10 | 0.112264E+10 | 0.00 | 0.00 |
February | 0.287250E+10 | 0.446081E+10 | 0.261932E+10 | 0.139222E+10 | 0.122709E+10 | 0.00 | 0.00 |
March | 0.484660E+10 | 0.426282E+10 | 0.395181E+10 | 0.211803E+10 | 0.183378E+10 | 0.00 | 0.00 |
April | 0.632914E+10 | 0.261992E+10 | 0.439576E+10 | 0.237423E+10 | 0.202153E+10 | 0.00 | 0.00 |
May | 0.802179E+10 | 0.156677E+10 | 0.489247E+10 | 0.261769E+10 | 0.227478E+10 | 0.00 | 0.00 |
June | 0.844020E+10 | 0.858657E+09 | 0.460881E+10 | 0.247544E+10 | 0.213337E+10 | 0.00 | 0.00 |
July | 0.769782E+10 | 0.780713E+09 | 0.422633E+10 | 0.210015E+10 | 0.212618E+10 | 0.00 | 0.00 |
August | 0.709828E+10 | 0.110933E+10 | 0.409299E+10 | 0.208594E+10 | 0.200704E+10 | 0.00 | 0.00 |
September | 0.681850E+10 | 0.169232E+10 | 0.405069E+10 | 0.225664E+10 | 0.179405E+10 | 0.00 | 0.00 |
October | 0.519633E+10 | 0.284346E+10 | 0.360321E+10 | 0.210295E+10 | 0.150026E+10 | 0.00 | 0.00 |
November | 0.340481E+10 | 0.469935E+10 | 0.292681E+10 | 0.178211E+10 | 0.114469E+10 | 0.00 | 0.00 |
December | 0.229105E+10 | 0.629315E+10 | 0.243720E+10 | 0.132396E+10 | 0.111323E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.656592E+11 | 0.365393E+11 | 0.443754E+11 | 0.240767E+11 | 0.202987E+11 | 0.00 | 0.00 |
Minimum of Months | 0.229105E+10 | 0.780713E+09 | 0.243720E+10 | 0.132396E+10 | 0.111323E+10 | 0.00 | 0.00 |
Maximum of Months | 0.844020E+10 | 0.629315E+10 | 0.489247E+10 | 0.261769E+10 | 0.227478E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.301658E+09 | 0.690516E+10 | 0.136826E+10 | 0.00 | 0.136826E+10 | 0.00 | 0.00 |
February | 0.683386E+09 | 0.561232E+10 | 0.150910E+10 | 0.00 | 0.150910E+10 | 0.00 | 0.00 |
March | 0.151298E+10 | 0.527247E+10 | 0.218652E+10 | 0.00 | 0.218652E+10 | 0.00 | 0.00 |
April | 0.280120E+10 | 0.298667E+10 | 0.244314E+10 | 19248427.58 | 0.242389E+10 | 0.00 | 0.00 |
May | 0.480643E+10 | 0.180601E+10 | 0.299424E+10 | 0.216526E+09 | 0.277772E+10 | 0.00 | 0.00 |
June | 0.644640E+10 | 0.937279E+09 | 0.308116E+10 | 0.379327E+09 | 0.270183E+10 | 0.00 | 0.00 |
July | 0.612946E+10 | 0.770749E+09 | 0.294251E+10 | 0.286431E+09 | 0.265608E+10 | 0.00 | 0.00 |
August | 0.478095E+10 | 0.104195E+10 | 0.248118E+10 | 50733647.87 | 0.243044E+10 | 0.00 | 0.00 |
September | 0.350837E+10 | 0.207592E+10 | 0.209521E+10 | 836064.26 | 0.209437E+10 | 0.00 | 0.00 |
October | 0.190395E+10 | 0.345450E+10 | 0.179759E+10 | 0.00 | 0.179759E+10 | 0.00 | 0.00 |
November | 0.508683E+09 | 0.574186E+10 | 0.140437E+10 | 0.00 | 0.140437E+10 | 0.00 | 0.00 |
December | 0.202177E+09 | 0.766626E+10 | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.335857E+11 | 0.442712E+11 | 0.256609E+11 | 0.953102E+09 | 0.247078E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202177E+09 | 0.770749E+09 | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.00 | 0.00 |
Maximum of Months | 0.644640E+10 | 0.766626E+10 | 0.308116E+10 | 0.379327E+09 | 0.277772E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.230025E+10 | 0.437521E+10 | 0.243972E+10 | 0.132346E+10 | 0.111626E+10 | 0.00 | 0.00 |
February | 0.323548E+10 | 0.355908E+10 | 0.294823E+10 | 0.168047E+10 | 0.126776E+10 | 0.00 | 0.00 |
March | 0.484713E+10 | 0.334744E+10 | 0.403011E+10 | 0.222046E+10 | 0.180965E+10 | 0.00 | 0.00 |
April | 0.674114E+10 | 0.195442E+10 | 0.469943E+10 | 0.260714E+10 | 0.209230E+10 | 0.00 | 0.00 |
May | 0.810077E+10 | 0.124501E+10 | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.00 | 0.00 |
June | 0.883997E+10 | 0.636690E+09 | 0.485229E+10 | 0.269942E+10 | 0.215287E+10 | 0.00 | 0.00 |
July | 0.822764E+10 | 0.535775E+09 | 0.449650E+10 | 0.235069E+10 | 0.214580E+10 | 0.00 | 0.00 |
August | 0.754873E+10 | 0.719182E+09 | 0.427866E+10 | 0.218978E+10 | 0.208888E+10 | 0.00 | 0.00 |
September | 0.675564E+10 | 0.135111E+10 | 0.410225E+10 | 0.234063E+10 | 0.176162E+10 | 0.00 | 0.00 |
October | 0.451755E+10 | 0.226480E+10 | 0.326005E+10 | 0.175942E+10 | 0.150063E+10 | 0.00 | 0.00 |
November | 0.305471E+10 | 0.363710E+10 | 0.282808E+10 | 0.164642E+10 | 0.118166E+10 | 0.00 | 0.00 |
December | 0.216880E+10 | 0.481386E+10 | 0.243763E+10 | 0.129151E+10 | 0.114612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.663378E+11 | 0.284397E+11 | 0.453842E+11 | 0.248328E+11 | 0.205513E+11 | 0.00 | 0.00 |
Minimum of Months | 0.216880E+10 | 0.535775E+09 | 0.243763E+10 | 0.129151E+10 | 0.111626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.883997E+10 | 0.481386E+10 | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122946E+11 | 0.668053E+10 | 0.936018E+10 | 0.709131E+10 | 0.226887E+10 | 0.00 | 0.00 |
February | 0.104752E+11 | 0.546206E+10 | 0.784236E+10 | 0.552874E+10 | 0.231362E+10 | 0.00 | 0.00 |
March | 0.971072E+10 | 0.531524E+10 | 0.705642E+10 | 0.406871E+10 | 0.298771E+10 | 0.00 | 0.00 |
April | 0.723128E+10 | 0.319557E+10 | 0.462990E+10 | 0.172753E+10 | 0.290237E+10 | 0.00 | 0.00 |
May | 0.590388E+10 | 0.195285E+10 | 0.338096E+10 | 0.473224E+09 | 0.290774E+10 | 0.00 | 0.00 |
June | 0.610040E+10 | 0.955755E+09 | 0.282282E+10 | 0.179109E+09 | 0.264371E+10 | 0.00 | 0.00 |
July | 0.636820E+10 | 0.800989E+09 | 0.297348E+10 | 0.275646E+09 | 0.269783E+10 | 0.00 | 0.00 |
August | 0.760371E+10 | 0.112913E+10 | 0.379036E+10 | 0.100333E+10 | 0.278703E+10 | 0.00 | 0.00 |
September | 0.103894E+11 | 0.221136E+10 | 0.572548E+10 | 0.297458E+10 | 0.275089E+10 | 0.00 | 0.00 |
October | 0.124565E+11 | 0.360693E+10 | 0.803855E+10 | 0.543459E+10 | 0.260395E+10 | 0.00 | 0.00 |
November | 0.128887E+11 | 0.558964E+10 | 0.936160E+10 | 0.713707E+10 | 0.222453E+10 | 0.00 | 0.00 |
December | 0.123454E+11 | 0.720500E+10 | 0.958696E+10 | 0.719641E+10 | 0.239055E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113768E+12 | 0.441051E+11 | 0.745691E+11 | 0.430903E+11 | 0.314788E+11 | 0.00 | 0.00 |
Minimum of Months | 0.590388E+10 | 0.800989E+09 | 0.282282E+10 | 0.179109E+09 | 0.222453E+10 | 0.00 | 0.00 |
Maximum of Months | 0.128887E+11 | 0.720500E+10 | 0.958696E+10 | 0.719641E+10 | 0.298771E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.274065E+10 | 0.471160E+10 | 0.256997E+10 | 0.144734E+10 | 0.112264E+10 | 0.00 | 0.00 |
February | 0.297741E+10 | 0.389151E+10 | 0.261931E+10 | 0.139222E+10 | 0.122709E+10 | 0.00 | 0.00 |
March | 0.496318E+10 | 0.371702E+10 | 0.395180E+10 | 0.211803E+10 | 0.183377E+10 | 0.00 | 0.00 |
April | 0.645520E+10 | 0.225357E+10 | 0.439574E+10 | 0.237422E+10 | 0.202152E+10 | 0.00 | 0.00 |
May | 0.803437E+10 | 0.144649E+10 | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.00 | 0.00 |
June | 0.851440E+10 | 0.764598E+09 | 0.460880E+10 | 0.247543E+10 | 0.213336E+10 | 0.00 | 0.00 |
July | 0.781860E+10 | 0.650596E+09 | 0.422631E+10 | 0.210014E+10 | 0.212617E+10 | 0.00 | 0.00 |
August | 0.727907E+10 | 0.859771E+09 | 0.409297E+10 | 0.208593E+10 | 0.200703E+10 | 0.00 | 0.00 |
September | 0.685205E+10 | 0.156345E+10 | 0.405067E+10 | 0.225664E+10 | 0.179404E+10 | 0.00 | 0.00 |
October | 0.528115E+10 | 0.252132E+10 | 0.360320E+10 | 0.210295E+10 | 0.150025E+10 | 0.00 | 0.00 |
November | 0.352946E+10 | 0.399243E+10 | 0.292680E+10 | 0.178211E+10 | 0.114469E+10 | 0.00 | 0.00 |
December | 0.245671E+10 | 0.517482E+10 | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.669022E+11 | 0.315472E+11 | 0.443752E+11 | 0.240766E+11 | 0.202986E+11 | 0.00 | 0.00 |
Minimum of Months | 0.245671E+10 | 0.650596E+09 | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.00 | 0.00 |
Maximum of Months | 0.851440E+10 | 0.517482E+10 | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.414192E+09 | 0.621446E+10 | 0.136826E+10 | 0.00 | 0.136826E+10 | 0.00 | 0.00 |
February | 0.795853E+09 | 0.512127E+10 | 0.150910E+10 | 0.00 | 0.150910E+10 | 0.00 | 0.00 |
March | 0.163022E+10 | 0.489193E+10 | 0.218652E+10 | 0.00 | 0.218652E+10 | 0.00 | 0.00 |
April | 0.281833E+10 | 0.285720E+10 | 0.244314E+10 | 19248427.58 | 0.242389E+10 | 0.00 | 0.00 |
May | 0.476337E+10 | 0.178782E+10 | 0.299424E+10 | 0.216526E+09 | 0.277772E+10 | 0.00 | 0.00 |
June | 0.636302E+10 | 0.957958E+09 | 0.308116E+10 | 0.379327E+09 | 0.270183E+10 | 0.00 | 0.00 |
July | 0.602524E+10 | 0.805391E+09 | 0.294251E+10 | 0.286431E+09 | 0.265608E+10 | 0.00 | 0.00 |
August | 0.470193E+10 | 0.105583E+10 | 0.248118E+10 | 50733647.87 | 0.243044E+10 | 0.00 | 0.00 |
September | 0.347463E+10 | 0.204512E+10 | 0.209521E+10 | 836064.26 | 0.209437E+10 | 0.00 | 0.00 |
October | 0.196159E+10 | 0.323121E+10 | 0.179759E+10 | 0.00 | 0.179759E+10 | 0.00 | 0.00 |
November | 0.622749E+09 | 0.515938E+10 | 0.140437E+10 | 0.00 | 0.140437E+10 | 0.00 | 0.00 |
December | 0.305337E+09 | 0.691655E+10 | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.338764E+11 | 0.410441E+11 | 0.256609E+11 | 0.953102E+09 | 0.247078E+11 | 0.00 | 0.00 |
Minimum of Months | 0.305337E+09 | 0.805391E+09 | 0.135766E+10 | 0.00 | 0.135766E+10 | 0.00 | 0.00 |
Maximum of Months | 0.636302E+10 | 0.691655E+10 | 0.308116E+10 | 0.379327E+09 | 0.277772E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244221E+10 | 0.391539E+10 | 0.243972E+10 | 0.132346E+10 | 0.111626E+10 | 0.00 | 0.00 |
February | 0.335007E+10 | 0.325432E+10 | 0.294823E+10 | 0.168047E+10 | 0.126776E+10 | 0.00 | 0.00 |
March | 0.494030E+10 | 0.314237E+10 | 0.403011E+10 | 0.222046E+10 | 0.180965E+10 | 0.00 | 0.00 |
April | 0.674961E+10 | 0.189507E+10 | 0.469943E+10 | 0.260714E+10 | 0.209230E+10 | 0.00 | 0.00 |
May | 0.807553E+10 | 0.123472E+10 | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.00 | 0.00 |
June | 0.879389E+10 | 0.648372E+09 | 0.485229E+10 | 0.269942E+10 | 0.215287E+10 | 0.00 | 0.00 |
July | 0.817174E+10 | 0.555272E+09 | 0.449650E+10 | 0.235069E+10 | 0.214580E+10 | 0.00 | 0.00 |
August | 0.750933E+10 | 0.728240E+09 | 0.427866E+10 | 0.218978E+10 | 0.208888E+10 | 0.00 | 0.00 |
September | 0.674122E+10 | 0.133719E+10 | 0.410225E+10 | 0.234063E+10 | 0.176162E+10 | 0.00 | 0.00 |
October | 0.455992E+10 | 0.214234E+10 | 0.326005E+10 | 0.175942E+10 | 0.150063E+10 | 0.00 | 0.00 |
November | 0.317549E+10 | 0.329755E+10 | 0.282808E+10 | 0.164642E+10 | 0.118166E+10 | 0.00 | 0.00 |
December | 0.232805E+10 | 0.431418E+10 | 0.243763E+10 | 0.129151E+10 | 0.114612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.668373E+11 | 0.264650E+11 | 0.453842E+11 | 0.248328E+11 | 0.205513E+11 | 0.00 | 0.00 |
Minimum of Months | 0.232805E+10 | 0.555272E+09 | 0.243763E+10 | 0.129151E+10 | 0.111626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.879389E+10 | 0.431418E+10 | 0.501121E+10 | 0.272341E+10 | 0.228780E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124518E+11 | 0.609404E+10 | 0.936018E+10 | 0.709131E+10 | 0.226887E+10 | 0.00 | 0.00 |
February | 0.105878E+11 | 0.505022E+10 | 0.784236E+10 | 0.552874E+10 | 0.231362E+10 | 0.00 | 0.00 |
March | 0.979309E+10 | 0.500283E+10 | 0.705642E+10 | 0.406871E+10 | 0.298771E+10 | 0.00 | 0.00 |
April | 0.722185E+10 | 0.307794E+10 | 0.462990E+10 | 0.172753E+10 | 0.290237E+10 | 0.00 | 0.00 |
May | 0.585048E+10 | 0.192719E+10 | 0.338096E+10 | 0.473224E+09 | 0.290774E+10 | 0.00 | 0.00 |
June | 0.601862E+10 | 0.975264E+09 | 0.282282E+10 | 0.179109E+09 | 0.264371E+10 | 0.00 | 0.00 |
July | 0.626333E+10 | 0.834758E+09 | 0.297348E+10 | 0.275646E+09 | 0.269783E+10 | 0.00 | 0.00 |
August | 0.752215E+10 | 0.114475E+10 | 0.379036E+10 | 0.100333E+10 | 0.278703E+10 | 0.00 | 0.00 |
September | 0.103424E+11 | 0.218652E+10 | 0.572548E+10 | 0.297458E+10 | 0.275089E+10 | 0.00 | 0.00 |
October | 0.124869E+11 | 0.343624E+10 | 0.803855E+10 | 0.543459E+10 | 0.260395E+10 | 0.00 | 0.00 |
November | 0.130345E+11 | 0.515917E+10 | 0.936160E+10 | 0.713707E+10 | 0.222453E+10 | 0.00 | 0.00 |
December | 0.125557E+11 | 0.658436E+10 | 0.958696E+10 | 0.719641E+10 | 0.239055E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114129E+12 | 0.414733E+11 | 0.745691E+11 | 0.430903E+11 | 0.314788E+11 | 0.00 | 0.00 |
Minimum of Months | 0.585048E+10 | 0.834758E+09 | 0.282282E+10 | 0.179109E+09 | 0.222453E+10 | 0.00 | 0.00 |
Maximum of Months | 0.130345E+11 | 0.658436E+10 | 0.958696E+10 | 0.719641E+10 | 0.298771E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.281050E+10 | 0.432404E+10 | 0.256997E+10 | 0.144734E+10 | 0.112264E+10 | 0.00 | 0.00 |
February | 0.303176E+10 | 0.361120E+10 | 0.261931E+10 | 0.139222E+10 | 0.122709E+10 | 0.00 | 0.00 |
March | 0.500330E+10 | 0.350117E+10 | 0.395180E+10 | 0.211803E+10 | 0.183377E+10 | 0.00 | 0.00 |
April | 0.644070E+10 | 0.217560E+10 | 0.439574E+10 | 0.237422E+10 | 0.202152E+10 | 0.00 | 0.00 |
May | 0.798685E+10 | 0.142676E+10 | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.00 | 0.00 |
June | 0.845525E+10 | 0.775795E+09 | 0.460880E+10 | 0.247543E+10 | 0.213336E+10 | 0.00 | 0.00 |
July | 0.775369E+10 | 0.668458E+09 | 0.422631E+10 | 0.210014E+10 | 0.212617E+10 | 0.00 | 0.00 |
August | 0.722570E+10 | 0.867489E+09 | 0.409297E+10 | 0.208593E+10 | 0.200703E+10 | 0.00 | 0.00 |
September | 0.681842E+10 | 0.154574E+10 | 0.405067E+10 | 0.225664E+10 | 0.179404E+10 | 0.00 | 0.00 |
October | 0.529085E+10 | 0.240430E+10 | 0.360320E+10 | 0.210295E+10 | 0.150025E+10 | 0.00 | 0.00 |
November | 0.358891E+10 | 0.367960E+10 | 0.292680E+10 | 0.178211E+10 | 0.114469E+10 | 0.00 | 0.00 |
December | 0.253163E+10 | 0.475304E+10 | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.669375E+11 | 0.297332E+11 | 0.443752E+11 | 0.240766E+11 | 0.202986E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253163E+10 | 0.668458E+09 | 0.243719E+10 | 0.132396E+10 | 0.111323E+10 | 0.00 | 0.00 |
Maximum of Months | 0.845525E+10 | 0.475304E+10 | 0.489245E+10 | 0.261768E+10 | 0.227477E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.358871E+11 | -0.348613E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102585E+10 | 58.98 | 0.00 | 0.00 |
February | 0.325813E+11 | -0.316536E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -927767301.3 | 58.98 | 0.00 | 0.00 |
March | 0.368912E+11 | -0.358606E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103054E+10 | 58.98 | 0.00 | 0.00 |
April | 0.313460E+11 | -0.303538E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992195235.5 | 58.97 | 0.00 | 0.00 |
May | 0.307888E+11 | -0.297635E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102525E+10 | 58.97 | 0.00 | 0.00 |
June | 0.281482E+11 | -0.271557E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992428955.3 | 58.98 | 0.00 | 0.00 |
July | 0.255673E+11 | -0.245484E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101891E+10 | 58.97 | 0.00 | 0.00 |
August | 0.279298E+11 | -0.269080E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102183E+10 | 58.98 | 0.00 | 0.00 |
September | 0.266919E+11 | -0.257056E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986238869.8 | 58.97 | 0.00 | 0.00 |
October | 0.297926E+11 | -0.287737E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101890E+10 | 58.98 | 0.00 | 0.00 |
November | 0.317435E+11 | -0.307568E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986667671.1 | 58.97 | 0.00 | 0.00 |
December | 0.337943E+11 | -0.327728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102150E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.371162E+12 | -0.359114E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120481E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.255673E+11 | -0.358606E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103054E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.368912E+11 | -0.245484E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -927767301.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8778.99 | 38.76 | 276.17 | 279.33 | 1861.95 | 27.22 | 182.00 | 263.00 |
February | 268.33 | 0.49 | 0.48 | 01-FEB-07:00 | 9451.74 | 37.13 | 262.00 | 269.50 | 1364.99 | 23.16 | 154.50 | 246.50 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:19 | 2000.78 | 19.99 | 67.83 | 322.83 | 1034.84 | 20.86 | 145.83 | 291.83 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:49 | 1276.25 | 19.35 | 27.00 | 337.17 | 781.63 | 20.68 | 134.50 | 297.00 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-06:30 | 1053.86 | 19.01 | 0.17 | 362.67 | 643.26 | 20.37 | 110.50 | 324.50 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-06:30 | 948.68 | 18.93 | 0.00 | 355.50 | 594.51 | 20.37 | 57.67 | 316.50 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-06:30 | 1006.17 | 18.96 | 0.83 | 360.67 | 606.51 | 20.34 | 109.67 | 305.33 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1183.57 | 19.30 | 15.33 | 348.50 | 710.64 | 20.64 | 143.83 | 299.67 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1494.11 | 19.74 | 50.33 | 319.50 | 878.33 | 20.63 | 130.50 | 282.50 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3578.69 | 26.01 | 152.83 | 308.67 | 1208.98 | 21.41 | 138.83 | 285.50 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8947.59 | 37.66 | 288.50 | 288.00 | 1485.71 | 24.06 | 142.00 | 270.17 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 7949.12 | 38.02 | 284.17 | 276.33 | 1834.37 | 27.25 | 207.67 | 269.33 |
Annual Sum or Average | 4125.67 | 0.50 | 3500.45 | 24.92 | 1425.17 | 3828.67 | 1024.36 | 21.95 | 1657.50 | 3451.83 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 948.68 | 18.93 | 0.00 | 269.50 | 594.51 | 20.34 | 57.67 | 246.50 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 9451.74 | 38.76 | 288.50 | 362.67 | 1861.95 | 27.25 | 207.67 | 324.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:09 | 2424.66 | 24.30 | 94.67 | 250.17 | 1322.50 | 24.05 | 106.00 | 205.00 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2913.99 | 24.24 | 90.00 | 253.17 | 1082.67 | 22.56 | 92.17 | 213.83 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-06:00 | 2654.38 | 23.40 | 103.00 | 313.33 | 1415.59 | 23.49 | 126.33 | 279.83 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:10 | 3390.97 | 24.20 | 119.67 | 340.00 | 1321.16 | 22.98 | 106.50 | 311.17 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:49 | 2697.09 | 22.62 | 103.67 | 369.00 | 1475.60 | 23.10 | 96.67 | 338.83 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:49 | 2750.50 | 22.73 | 100.00 | 360.83 | 1512.01 | 23.19 | 83.00 | 331.33 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2441.54 | 22.68 | 100.67 | 367.67 | 1314.27 | 23.14 | 101.50 | 325.00 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:49 | 3061.95 | 23.87 | 120.67 | 352.00 | 1215.68 | 22.99 | 109.67 | 318.17 |
September | 365.83 | 0.50 | 0.48 | 01-SEP-05:00 | 2922.70 | 23.70 | 115.33 | 323.00 | 1136.79 | 22.49 | 108.83 | 289.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2550.38 | 23.45 | 94.17 | 292.33 | 1383.00 | 23.57 | 102.67 | 256.33 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 2083.37 | 23.39 | 89.00 | 261.00 | 1108.29 | 23.37 | 90.00 | 218.00 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1841.17 | 23.20 | 86.67 | 252.50 | 944.55 | 22.90 | 118.17 | 215.50 |
Annual Sum or Average | 4125.67 | 0.51 | 2670.53 | 23.43 | 1217.50 | 3735.00 | 1283.92 | 23.14 | 1241.50 | 3302.33 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1841.17 | 22.62 | 86.67 | 250.17 | 944.55 | 22.49 | 83.00 | 205.00 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3390.97 | 24.30 | 120.67 | 369.00 | 1512.01 | 24.05 | 126.33 | 338.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-08:00 | 534.00 | 16.44 | 0.00 | 231.83 | 353.02 | 18.26 | 0.00 | 147.33 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-08:50 | 608.17 | 17.14 | 0.00 | 235.00 | 401.87 | 18.83 | 0.00 | 171.50 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:49 | 713.84 | 17.91 | 0.00 | 306.00 | 457.11 | 19.38 | 7.33 | 243.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 845.00 | 19.03 | 0.00 | 349.83 | 537.95 | 20.37 | 52.67 | 310.17 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 1033.52 | 19.78 | 40.17 | 385.17 | 598.39 | 20.96 | 145.67 | 359.17 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1107.56 | 22.66 | 106.67 | 381.67 | 629.09 | 21.36 | 135.83 | 356.83 |
July | 400.17 | 0.49 | 0.48 | 01-JUL-05:49 | 1048.25 | 21.10 | 63.00 | 391.17 | 629.75 | 22.38 | 163.67 | 352.67 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 892.54 | 19.31 | 1.00 | 360.67 | 557.76 | 20.62 | 91.17 | 323.33 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:19 | 711.62 | 18.28 | 0.00 | 312.17 | 463.28 | 19.70 | 18.50 | 249.83 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:30 | 638.90 | 17.44 | 0.00 | 282.00 | 419.04 | 19.03 | 1.83 | 216.00 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 518.83 | 16.44 | 0.00 | 240.83 | 347.04 | 18.21 | 0.00 | 148.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-08:20 | 532.82 | 16.40 | 0.00 | 231.33 | 345.79 | 18.18 | 0.00 | 153.50 |
Annual Sum or Average | 4125.67 | 0.51 | 792.57 | 18.73 | 210.83 | 3707.67 | 492.31 | 19.94 | 616.67 | 3032.33 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 518.83 | 16.40 | 0.00 | 231.33 | 345.79 | 18.18 | 0.00 | 147.33 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 1107.56 | 22.66 | 106.67 | 391.17 | 629.75 | 22.38 | 163.67 | 359.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:00 | 2043.25 | 24.75 | 99.00 | 264.50 | 1100.78 | 24.45 | 109.17 | 217.33 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:50 | 2343.73 | 24.41 | 89.83 | 254.83 | 1263.13 | 24.33 | 102.33 | 215.83 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:00 | 2956.50 | 23.79 | 113.00 | 323.17 | 1126.47 | 22.38 | 123.33 | 287.00 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:19 | 3338.20 | 23.33 | 111.83 | 346.50 | 1309.00 | 22.33 | 100.67 | 313.17 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:40 | 2588.50 | 17.41 | 0.00 | 376.83 | 1436.00 | 19.91 | 50.33 | 350.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:30 | 2686.60 | 17.53 | 0.00 | 372.50 | 1474.07 | 20.00 | 45.00 | 342.67 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:40 | 2406.72 | 17.78 | 3.67 | 382.00 | 1319.07 | 20.02 | 65.33 | 337.17 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-06:49 | 2457.56 | 20.33 | 57.17 | 353.83 | 1274.84 | 20.09 | 56.67 | 314.50 |
September | 365.83 | 0.50 | 0.48 | 01-SEP-07:30 | 2913.63 | 23.55 | 112.83 | 321.83 | 1145.71 | 22.42 | 122.67 | 287.00 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:30 | 2518.85 | 24.40 | 100.17 | 303.00 | 1335.99 | 24.23 | 104.67 | 265.17 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 1882.57 | 23.28 | 86.83 | 269.33 | 939.21 | 22.91 | 81.17 | 224.17 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:20 | 2065.89 | 24.93 | 107.00 | 257.50 | 841.39 | 23.37 | 111.17 | 223.83 |
Annual Sum or Average | 4125.67 | 0.50 | 2551.30 | 21.79 | 881.33 | 3825.83 | 1231.11 | 21.98 | 1072.50 | 3378.33 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 1882.57 | 17.41 | 0.00 | 254.83 | 841.39 | 19.91 | 45.00 | 215.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3338.20 | 24.93 | 113.00 | 382.00 | 1474.07 | 24.45 | 123.33 | 350.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8860.13 | 38.36 | 275.83 | 279.33 | 1981.78 | 22.95 | 97.17 | 263.83 |
February | 268.33 | 0.49 | 0.48 | 01-FEB-07:00 | 9525.61 | 36.66 | 261.50 | 269.83 | 1471.58 | 18.66 | 34.83 | 249.67 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:10 | 2050.52 | 13.60 | 10.67 | 323.33 | 1115.68 | 16.57 | 1.83 | 297.33 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 1310.20 | 13.46 | 0.00 | 337.83 | 839.24 | 17.00 | 0.00 | 302.50 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-06:30 | 1077.68 | 13.46 | 0.00 | 363.33 | 687.86 | 16.94 | 0.00 | 331.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:19 | 970.75 | 13.27 | 0.00 | 356.33 | 635.51 | 16.86 | 0.00 | 324.67 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-06:30 | 1026.90 | 13.33 | 0.00 | 361.67 | 647.74 | 16.85 | 0.00 | 314.00 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1211.09 | 13.55 | 0.00 | 349.67 | 760.90 | 17.04 | 0.00 | 306.83 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1542.26 | 13.66 | 11.00 | 321.00 | 946.00 | 16.68 | 0.00 | 287.50 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3669.02 | 21.48 | 131.00 | 312.17 | 1314.98 | 17.19 | 13.33 | 288.67 |
November | 295.83 | 0.49 | 0.48 | 01-NOV-12:39 | 9020.74 | 37.15 | 288.33 | 288.17 | 1631.25 | 21.26 | 90.00 | 275.33 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 8018.64 | 37.57 | 284.00 | 276.33 | 1950.42 | 23.02 | 101.33 | 270.00 |
Annual Sum or Average | 4125.67 | 0.50 | 3548.41 | 20.66 | 1262.33 | 3839.00 | 1101.20 | 18.15 | 338.50 | 3512.00 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 970.75 | 13.27 | 0.00 | 269.83 | 635.51 | 16.57 | 0.00 | 249.67 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 9525.61 | 38.36 | 288.33 | 363.33 | 1981.78 | 23.02 | 101.33 | 331.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:09 | 2461.72 | 21.79 | 92.50 | 251.00 | 1371.04 | 22.16 | 63.33 | 212.17 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2961.66 | 21.64 | 89.67 | 254.17 | 1137.87 | 20.20 | 41.00 | 218.67 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-06:00 | 2711.16 | 20.39 | 101.33 | 314.33 | 1478.73 | 21.09 | 71.00 | 285.50 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:10 | 3401.43 | 20.25 | 109.83 | 340.50 | 1391.64 | 20.29 | 60.67 | 315.17 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:40 | 2734.40 | 19.38 | 103.67 | 370.00 | 1547.67 | 20.48 | 72.67 | 343.33 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:40 | 2802.73 | 19.37 | 100.00 | 364.00 | 1582.07 | 20.53 | 70.00 | 335.67 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2482.43 | 19.35 | 100.67 | 369.33 | 1377.79 | 20.51 | 70.33 | 330.33 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:49 | 3093.39 | 20.98 | 120.50 | 352.50 | 1279.84 | 20.35 | 63.33 | 322.33 |
September | 365.83 | 0.50 | 0.48 | 01-SEP-05:00 | 2973.18 | 20.74 | 114.50 | 323.83 | 1197.96 | 19.81 | 57.67 | 294.00 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2601.73 | 20.58 | 92.50 | 293.50 | 1439.46 | 21.32 | 63.50 | 263.67 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 2124.08 | 20.61 | 87.83 | 262.33 | 1158.47 | 21.27 | 61.00 | 226.33 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1874.80 | 20.56 | 81.33 | 253.17 | 989.50 | 20.90 | 50.33 | 220.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2711.21 | 20.38 | 1194.33 | 3748.67 | 1345.01 | 20.70 | 744.83 | 3367.83 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1874.80 | 19.35 | 81.33 | 251.00 | 989.50 | 19.81 | 41.00 | 212.17 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3401.43 | 21.79 | 120.50 | 370.00 | 1582.07 | 22.16 | 72.67 | 343.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-08:50 | 543.96 | 10.68 | 0.00 | 233.33 | 376.44 | 14.52 | 0.00 | 164.67 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-08:30 | 620.71 | 11.65 | 0.00 | 236.50 | 428.88 | 15.36 | 0.00 | 181.17 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:49 | 730.01 | 12.47 | 0.00 | 307.33 | 488.15 | 16.06 | 0.00 | 254.17 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 864.98 | 13.78 | 0.00 | 349.83 | 574.47 | 17.34 | 0.00 | 315.83 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-05:00 | 1057.01 | 14.28 | 3.00 | 385.33 | 640.03 | 17.75 | 0.00 | 362.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1133.57 | 17.99 | 83.17 | 381.67 | 673.36 | 17.86 | 1.33 | 360.83 |
July | 400.17 | 0.49 | 0.48 | 01-JUL-05:49 | 1072.12 | 15.88 | 37.33 | 391.50 | 670.98 | 19.30 | 37.50 | 355.67 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 921.35 | 13.94 | 0.00 | 361.83 | 595.25 | 17.49 | 0.00 | 327.67 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:19 | 728.37 | 13.02 | 0.00 | 314.33 | 495.00 | 16.61 | 0.00 | 262.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:19 | 652.72 | 12.05 | 0.00 | 283.17 | 447.38 | 15.70 | 0.00 | 229.83 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 529.36 | 10.74 | 0.00 | 242.67 | 370.35 | 14.57 | 0.00 | 167.17 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-08:20 | 541.69 | 10.69 | 0.00 | 232.00 | 368.40 | 14.45 | 0.00 | 171.83 |
Annual Sum or Average | 4125.67 | 0.51 | 810.97 | 13.36 | 123.50 | 3719.50 | 525.69 | 16.61 | 38.83 | 3153.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 529.36 | 10.68 | 0.00 | 232.00 | 368.40 | 14.45 | 0.00 | 164.67 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 1133.57 | 17.99 | 83.17 | 391.50 | 673.36 | 19.30 | 37.50 | 362.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:50 | 2028.81 | 20.70 | 81.83 | 264.50 | 1151.38 | 22.54 | 63.50 | 222.67 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2387.63 | 21.78 | 88.33 | 255.83 | 1315.52 | 22.28 | 61.33 | 220.67 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:49 | 3010.66 | 20.92 | 111.33 | 323.67 | 1186.49 | 19.75 | 52.50 | 290.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:10 | 3382.58 | 20.28 | 111.83 | 347.17 | 1374.47 | 19.53 | 51.83 | 316.83 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:40 | 2627.33 | 12.72 | 0.00 | 377.17 | 1504.31 | 16.43 | 0.00 | 354.67 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:30 | 2735.22 | 12.82 | 0.00 | 372.67 | 1540.47 | 16.56 | 0.00 | 348.33 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:30 | 2445.23 | 13.20 | 3.67 | 382.67 | 1379.14 | 16.64 | 0.00 | 342.17 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-06:40 | 2490.93 | 16.53 | 57.17 | 354.67 | 1336.88 | 16.75 | 3.67 | 317.67 |
September | 365.83 | 0.50 | 0.48 | 01-SEP-07:19 | 2963.72 | 20.57 | 112.67 | 322.67 | 1206.32 | 19.74 | 56.00 | 292.17 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:30 | 2708.93 | 21.92 | 104.00 | 303.83 | 1395.58 | 22.01 | 69.00 | 270.83 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 2704.97 | 22.54 | 112.00 | 270.67 | 988.06 | 20.69 | 54.00 | 230.67 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:20 | 2098.54 | 22.62 | 105.67 | 257.83 | 884.41 | 21.40 | 52.00 | 229.83 |
Annual Sum or Average | 4125.67 | 0.50 | 2657.55 | 18.44 | 888.50 | 3833.33 | 1290.15 | 19.23 | 463.83 | 3437.17 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 2028.81 | 12.72 | 0.00 | 255.83 | 884.41 | 16.43 | 0.00 | 220.67 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3382.58 | 22.62 | 112.67 | 382.67 | 1540.47 | 22.54 | 69.00 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8861.60 | 38.35 | 275.83 | 279.33 | 1983.46 | 22.94 | 97.17 | 263.83 |
February | 268.33 | 0.49 | 0.48 | 01-FEB-07:00 | 9527.61 | 36.65 | 261.50 | 269.83 | 1473.16 | 18.65 | 34.83 | 249.83 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:10 | 2052.58 | 13.57 | 10.67 | 323.33 | 1117.01 | 16.56 | 1.83 | 297.33 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 1311.67 | 13.43 | 0.00 | 338.00 | 840.25 | 16.99 | 0.00 | 302.50 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-06:30 | 1078.81 | 13.43 | 0.00 | 363.50 | 688.69 | 16.92 | 0.00 | 332.00 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:19 | 971.65 | 13.24 | 0.00 | 356.33 | 636.22 | 16.84 | 0.00 | 324.67 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-06:30 | 1028.02 | 13.30 | 0.00 | 361.67 | 648.55 | 16.83 | 0.00 | 314.17 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1212.48 | 13.52 | 0.00 | 349.67 | 761.85 | 17.03 | 0.00 | 307.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1543.93 | 13.63 | 11.00 | 321.00 | 947.10 | 16.67 | 0.00 | 287.67 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3670.91 | 21.46 | 131.00 | 312.17 | 1316.37 | 17.17 | 13.33 | 288.67 |
November | 295.83 | 0.49 | 0.48 | 01-NOV-12:39 | 9022.00 | 37.14 | 288.33 | 288.17 | 1632.63 | 21.25 | 90.00 | 275.33 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 8019.81 | 37.57 | 284.00 | 276.33 | 1952.24 | 23.01 | 101.33 | 270.00 |
Annual Sum or Average | 4125.67 | 0.50 | 3549.85 | 20.63 | 1262.33 | 3839.33 | 1102.37 | 18.14 | 338.50 | 3513.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 971.65 | 13.24 | 0.00 | 269.83 | 636.22 | 16.56 | 0.00 | 249.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 9527.61 | 38.35 | 288.33 | 363.50 | 1983.46 | 23.01 | 101.33 | 332.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-07:00 | 2462.36 | 21.76 | 92.50 | 251.00 | 1371.84 | 22.15 | 63.33 | 212.50 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2962.43 | 21.62 | 89.67 | 254.17 | 1138.80 | 20.18 | 41.00 | 218.67 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-06:00 | 2712.16 | 20.36 | 101.33 | 314.33 | 1479.74 | 21.08 | 71.00 | 285.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:10 | 3402.50 | 20.22 | 109.83 | 340.50 | 1392.76 | 20.27 | 60.67 | 315.17 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-05:40 | 2735.45 | 19.35 | 103.50 | 370.00 | 1548.84 | 20.46 | 72.67 | 343.33 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:40 | 2803.65 | 19.34 | 100.00 | 364.17 | 1583.17 | 20.51 | 70.00 | 335.67 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2483.47 | 19.33 | 100.67 | 369.33 | 1378.91 | 20.49 | 70.33 | 330.50 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:49 | 3094.53 | 20.96 | 120.50 | 353.00 | 1281.01 | 20.34 | 63.33 | 322.33 |
September | 365.83 | 0.50 | 0.48 | 01-SEP-05:00 | 2974.11 | 20.71 | 114.50 | 323.83 | 1198.93 | 19.80 | 57.67 | 294.00 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2587.98 | 20.25 | 89.67 | 293.00 | 1440.42 | 21.31 | 63.50 | 263.67 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 2100.49 | 19.47 | 80.50 | 261.50 | 1159.21 | 21.25 | 61.00 | 226.50 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 2384.59 | 22.31 | 106.83 | 253.17 | 990.35 | 20.89 | 50.33 | 220.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2744.98 | 20.37 | 1209.50 | 3748.00 | 1346.03 | 20.68 | 744.83 | 3368.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 2100.49 | 19.33 | 80.50 | 251.00 | 990.35 | 19.80 | 41.00 | 212.50 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3402.50 | 22.31 | 120.50 | 370.00 | 1583.17 | 22.15 | 72.67 | 343.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-08:50 | 544.23 | 10.64 | 0.00 | 233.67 | 376.82 | 14.50 | 0.00 | 165.00 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-08:30 | 621.05 | 11.61 | 0.00 | 236.50 | 429.31 | 15.34 | 0.00 | 181.17 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:49 | 730.57 | 12.44 | 0.00 | 307.50 | 488.68 | 16.04 | 0.00 | 254.50 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 865.61 | 13.75 | 0.00 | 349.83 | 575.08 | 17.33 | 0.00 | 316.00 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-05:00 | 1057.83 | 14.25 | 3.00 | 385.33 | 640.77 | 17.73 | 0.00 | 362.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1134.41 | 17.97 | 83.17 | 381.67 | 674.12 | 17.84 | 1.33 | 360.83 |
July | 400.17 | 0.49 | 0.48 | 01-JUL-05:49 | 1073.02 | 15.85 | 37.33 | 391.50 | 671.76 | 19.28 | 37.50 | 355.83 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 922.08 | 13.90 | 0.00 | 362.00 | 595.92 | 17.48 | 0.00 | 327.67 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:19 | 728.84 | 12.99 | 0.00 | 314.67 | 495.51 | 16.59 | 0.00 | 262.33 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:19 | 653.12 | 12.02 | 0.00 | 283.17 | 447.83 | 15.68 | 0.00 | 230.17 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 529.61 | 10.70 | 0.00 | 242.83 | 370.71 | 14.55 | 0.00 | 167.50 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-08:20 | 541.99 | 10.66 | 0.00 | 232.17 | 368.79 | 14.43 | 0.00 | 172.17 |
Annual Sum or Average | 4125.67 | 0.51 | 811.54 | 13.33 | 123.50 | 3720.83 | 526.26 | 16.60 | 38.83 | 3155.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 529.61 | 10.64 | 0.00 | 232.17 | 368.79 | 14.43 | 0.00 | 165.00 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 1134.41 | 17.97 | 83.17 | 391.50 | 674.12 | 19.28 | 37.50 | 362.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:50 | 2029.40 | 20.68 | 81.83 | 264.50 | 1152.16 | 22.52 | 63.50 | 222.67 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2388.38 | 21.75 | 88.33 | 255.83 | 1316.40 | 22.27 | 61.33 | 220.67 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:49 | 3011.78 | 20.89 | 111.33 | 323.67 | 1187.53 | 19.73 | 52.50 | 290.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:10 | 3383.70 | 20.25 | 111.83 | 347.33 | 1375.54 | 19.51 | 51.83 | 317.00 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:40 | 2628.41 | 12.68 | 0.00 | 377.17 | 1505.45 | 16.42 | 0.00 | 354.83 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:30 | 2736.29 | 12.78 | 0.00 | 372.67 | 1541.54 | 16.54 | 0.00 | 348.50 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:30 | 2446.41 | 13.16 | 3.67 | 382.67 | 1380.24 | 16.62 | 0.00 | 342.33 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-06:40 | 2492.08 | 16.50 | 57.17 | 354.67 | 1337.99 | 16.73 | 3.67 | 317.67 |
September | 365.83 | 0.50 | 0.48 | 01-SEP-07:19 | 2964.68 | 20.54 | 112.67 | 322.67 | 1207.33 | 19.72 | 56.00 | 292.17 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:30 | 2709.65 | 21.90 | 104.00 | 303.83 | 1396.50 | 22.00 | 69.00 | 270.83 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 2705.51 | 22.52 | 112.00 | 270.67 | 988.77 | 20.68 | 54.00 | 230.67 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:20 | 2099.20 | 22.59 | 105.67 | 257.83 | 885.19 | 21.39 | 52.00 | 229.83 |
Annual Sum or Average | 4125.67 | 0.50 | 2658.49 | 18.41 | 888.50 | 3833.50 | 1291.14 | 19.21 | 463.83 | 3437.83 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 2029.40 | 12.68 | 0.00 | 255.83 | 885.19 | 16.42 | 0.00 | 220.67 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3383.70 | 22.59 | 112.67 | 382.67 | 1541.54 | 22.52 | 69.00 | 354.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.273761E+10 | 26294.30 | 27-JAN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179605E+10 | 26191.35 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.973705E+09 | 21140.76 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36445715.51 | 8405.16 | 12-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7410071.37 | 2899.63 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568096E+09 | 16873.09 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298295E+10 | 26707.75 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298295E+10 | 26707.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 26155918.54 | 12816.84 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14164587.51 | 3075.36 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 760540.68 | 1186.34 | 02-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 606843.47 | 177.47 | 30-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41687890.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26155918.54 | 12816.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17295447.84 | 10621.67 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11432094.75 | 4974.92 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2447027.02 | 3579.30 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 652361.30 | 804.19 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17250286.95 | 5449.38 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49077217.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17295447.84 | 10621.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 27359356.73 | 10551.06 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15787772.40 | 4101.62 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2342193.97 | 1339.80 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3717180.68 | 7237.54 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21103133.13 | 15241.36 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70309636.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27359356.73 | 15241.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453237E+11 | 254179.28 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289381E+11 | 266026.49 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172409E+11 | 210851.53 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153991E+10 | 110461.63 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10073541.42 | 13651.44 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.577240E+09 | 141872.63 | 24-OCT-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173265E+11 | 173588.32 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633546E+11 | 263218.27 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.633546E+11 | 266026.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109646E+11 | 141175.47 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583824E+10 | 152606.73 | 25-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239714E+10 | 153340.06 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42797554.21 | 68295.07 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327712E+10 | 153588.41 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135095E+11 | 140826.25 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135095E+11 | 153588.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.427974E+10 | 145164.21 | 23-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192884E+10 | 144909.08 | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744253E+09 | 144928.24 | 02-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13113576.98 | 31835.79 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118887E+10 | 144857.37 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527174E+10 | 145194.56 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527174E+10 | 145194.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298218E+10 | 159077.99 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173197E+10 | 158247.17 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.603760E+09 | 157518.49 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20316025.51 | 37797.94 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.777657E+09 | 158364.44 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383137E+10 | 158940.91 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383137E+10 | 159077.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.308555E+10 | 146922.50 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166315E+10 | 146904.66 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369332E+09 | 146779.44 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1252166.22 | 7401.09 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.658125E+09 | 146924.76 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359378E+10 | 146993.30 | 05-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.937119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359378E+10 | 146993.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.612242E+10 | 27242.04 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400875E+10 | 27162.56 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256985E+10 | 25819.21 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.361161E+09 | 13581.95 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4677375.36 | 2644.20 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6663217.67 | 3869.69 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148871E+09 | 8423.01 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269386E+10 | 21668.30 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.815275E+10 | 28643.78 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.815275E+10 | 28643.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171602E+10 | 74552.73 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394425E+09 | 73260.93 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51836540.55 | 67246.79 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.684727E+09 | 73614.30 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227119E+10 | 73956.24 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.511820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227119E+10 | 74552.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.377543E+10 | 16333.99 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224526E+10 | 16303.78 | 28-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114009E+10 | 16242.66 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104595E+09 | 16247.07 | 07-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58658795.63 | 13839.18 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174289E+10 | 16322.00 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454913E+10 | 16322.43 | 04-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454913E+10 | 16333.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160233E+10 | 15761.46 | 26-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805387E+09 | 15745.83 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.431724E+09 | 15690.91 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32342188.35 | 14214.18 | 11-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22727408.02 | 8925.65 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.697222E+09 | 15767.75 | 27-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193719E+10 | 15749.76 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193719E+10 | 15767.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151206E+10 | 17994.28 | 17-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.910572E+09 | 17965.78 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.564978E+09 | 17916.66 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76076237.16 | 17850.12 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7163419.78 | 1171.05 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713223E+09 | 17997.60 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179255E+10 | 17994.21 | 26-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.557662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179255E+10 | 17997.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130354E+10 | 17483.71 | 09-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737633E+09 | 17437.46 | 27-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307147E+09 | 17433.63 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22648753.52 | 10456.04 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1644113.24 | 371.76 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.509983E+09 | 17437.58 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149227E+10 | 17448.50 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149227E+10 | 17483.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83.49 | 0.83 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 143.74 | 0.96 | 27-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 221.67 | 0.93 | 22-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 111.64 | 0.93 | 14-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 89.54 | 0.90 | 16-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 221.67 | 0.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.142286E+11 | 0.142286E+11 | 60758.45 | 03-JAN-14:05 | 60758.45 | 0.00 |
February | 0.00 | 0.00 | 0.155526E+11 | 0.155526E+11 | 73726.74 | 21-FEB-16:00 | 73726.74 | 0.00 |
March | 0.00 | 0.00 | 0.264681E+11 | 0.264681E+11 | 87241.75 | 21-MAR-15:30 | 87241.75 | 0.00 |
April | 0.00 | 0.00 | 0.654378E+11 | 0.654378E+11 | 116277.72 | 21-APR-14:50 | 116277.72 | 0.09 |
May | 0.00 | 0.00 | 0.955172E+11 | 0.950325E+11 | 131374.00 | 18-MAY-13:55 | 124247.38 | 0.21 |
June | 0.00 | 0.00 | 0.134090E+12 | 0.132723E+12 | 146247.39 | 09-JUN-12:43 | 140665.31 | 0.47 |
July | 0.00 | 0.00 | 0.166229E+12 | 0.136849E+12 | 210738.67 | 21-JUL-10:00 | 85411.41 | 0.85 |
August | 0.00 | 0.00 | 0.158421E+12 | 0.142893E+12 | 198590.04 | 02-AUG-08:30 | 100221.37 | 0.84 |
September | 0.00 | 0.00 | 0.106334E+12 | 0.963089E+11 | 180347.16 | 14-SEP-09:50 | 92276.56 | 0.55 |
October | 0.00 | 0.00 | 0.592378E+11 | 0.563729E+11 | 143832.62 | 02-OCT-10:17 | 121388.57 | 0.26 |
November | 0.00 | 0.00 | 0.211404E+11 | 0.211404E+11 | 80748.18 | 03-NOV-16:00 | 80748.18 | 0.02 |
December | 0.00 | 0.00 | 0.144029E+11 | 0.144029E+11 | 58750.74 | 20-DEC-15:00 | 58750.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.877060E+12 | 0.817409E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.142286E+11 | 0.142286E+11 | 58750.74 | 58750.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166229E+12 | 0.142893E+12 | 210738.67 | 140665.31 | 0.85 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.389778E+11 | 0.389778E+11 | 450849.94 | 12-JAN-15:05 | 450849.94 | 0.00 |
February | 0.00 | 0.00 | 0.971860E+11 | 0.971860E+11 | 570237.30 | 21-FEB-15:05 | 570237.30 | 0.00 |
March | 0.00 | 0.00 | 0.215336E+12 | 0.215336E+12 | 672026.81 | 21-MAR-16:00 | 672026.81 | 0.00 |
April | 0.00 | 0.00 | 0.475894E+12 | 0.475894E+12 | 1015469.86 | 21-APR-15:00 | 1015469.86 | 0.06 |
May | 0.00 | 0.00 | 0.844993E+12 | 0.841084E+12 | 1230948.14 | 18-MAY-13:55 | 1171732.19 | 0.20 |
June | 0.00 | 0.00 | 0.115439E+13 | 0.114489E+13 | 1368972.85 | 09-JUN-12:43 | 1330415.39 | 0.40 |
July | 0.00 | 0.00 | 0.129295E+13 | 0.108419E+13 | 1893185.34 | 21-JUL-10:10 | 783017.60 | 0.68 |
August | 0.00 | 0.00 | 0.112849E+13 | 0.103609E+13 | 1716832.35 | 03-AUG-05:03 | 809924.12 | 0.65 |
September | 0.00 | 0.00 | 0.911260E+12 | 0.827154E+12 | 1509527.87 | 14-SEP-09:50 | 768425.78 | 0.51 |
October | 0.00 | 0.00 | 0.474743E+12 | 0.451973E+12 | 1177815.66 | 03-OCT-14:05 | 1015393.71 | 0.25 |
November | 0.00 | 0.00 | 0.177075E+12 | 0.177075E+12 | 658041.12 | 09-NOV-15:05 | 658041.12 | 0.03 |
December | 0.00 | 0.00 | 0.222774E+11 | 0.222774E+11 | 339195.24 | 07-DEC-15:05 | 339195.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.683356E+13 | 0.641212E+13 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.222774E+11 | 0.222774E+11 | 339195.24 | 339195.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129295E+13 | 0.114489E+13 | 1893185.34 | 1330415.39 | 0.68 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.132960E+10 | 0.132960E+10 | 27187.72 | 12-JAN-15:00 | 27187.72 | 0.00 |
February | 0.00 | 0.00 | 0.554194E+10 | 0.554194E+10 | 44195.18 | 21-FEB-16:20 | 44195.18 | 0.00 |
March | 0.00 | 0.00 | 0.147487E+11 | 0.147487E+11 | 69177.67 | 21-MAR-16:00 | 69177.67 | 0.00 |
April | 0.00 | 0.00 | 0.502089E+11 | 0.502089E+11 | 119627.39 | 28-APR-14:00 | 119627.39 | 0.05 |
May | 0.00 | 0.00 | 0.938672E+11 | 0.934738E+11 | 141551.08 | 18-MAY-13:55 | 136662.69 | 0.20 |
June | 0.00 | 0.00 | 0.132122E+12 | 0.131154E+12 | 159493.73 | 27-JUN-14:23 | 159493.73 | 0.41 |
July | 0.00 | 0.00 | 0.146506E+12 | 0.124736E+12 | 243243.79 | 20-JUL-15:20 | 89875.75 | 0.69 |
August | 0.00 | 0.00 | 0.125785E+12 | 0.116676E+12 | 189571.68 | 03-AUG-05:03 | 89506.96 | 0.66 |
September | 0.00 | 0.00 | 0.977019E+11 | 0.898605E+11 | 163889.96 | 14-SEP-10:00 | 82095.17 | 0.51 |
October | 0.00 | 0.00 | 0.466181E+11 | 0.445965E+11 | 133597.61 | 03-OCT-14:00 | 116670.00 | 0.24 |
November | 0.00 | 0.00 | 0.991722E+10 | 0.991722E+10 | 66585.84 | 09-NOV-15:20 | 66585.84 | 0.02 |
December | 0.00 | 0.00 | 0.456439E+09 | 0.456439E+09 | 10132.50 | 20-DEC-15:00 | 10132.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.724803E+12 | 0.682700E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.456439E+09 | 0.456439E+09 | 10132.50 | 10132.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.146506E+12 | 0.131154E+12 | 243243.79 | 159493.73 | 0.69 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113956E+10 | 0.113956E+10 | 28386.17 | 03-JAN-15:00 | 28386.17 | 0.00 |
February | 0.00 | 0.00 | 0.397658E+10 | 0.397658E+10 | 49384.43 | 21-FEB-15:00 | 49384.43 | 0.00 |
March | 0.00 | 0.00 | 0.101668E+11 | 0.101668E+11 | 45398.77 | 21-MAR-16:00 | 45398.77 | 0.00 |
April | 0.00 | 0.00 | 0.315507E+11 | 0.315507E+11 | 56495.91 | 10-APR-12:10 | 56495.91 | 0.05 |
May | 0.00 | 0.00 | 0.550326E+11 | 0.549733E+11 | 79036.72 | 31-MAY-03:02 | 79036.72 | 0.17 |
June | 0.00 | 0.00 | 0.707180E+11 | 0.705391E+11 | 79805.34 | 26-JUN-10:43 | 71426.48 | 0.32 |
July | 0.00 | 0.00 | 0.860818E+11 | 0.731545E+11 | 116793.29 | 21-JUL-10:00 | 47321.00 | 0.54 |
August | 0.00 | 0.00 | 0.847099E+11 | 0.780174E+11 | 107340.75 | 02-AUG-08:00 | 51763.72 | 0.59 |
September | 0.00 | 0.00 | 0.668446E+11 | 0.624786E+11 | 100896.82 | 10-SEP-15:30 | 73977.26 | 0.46 |
October | 0.00 | 0.00 | 0.370750E+11 | 0.358037E+11 | 85477.66 | 01-OCT-15:52 | 85477.66 | 0.19 |
November | 0.00 | 0.00 | 0.965938E+10 | 0.965725E+10 | 50528.73 | 08-NOV-15:00 | 50528.73 | 0.02 |
December | 0.00 | 0.00 | 0.226141E+09 | 0.226141E+09 | 14926.14 | 11-DEC-05:11 | 14926.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.457181E+12 | 0.431684E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.226141E+09 | 0.226141E+09 | 14926.14 | 14926.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.860818E+11 | 0.780174E+11 | 116793.29 | 85477.66 | 0.59 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100974E+11 | 0.906317E+10 | 5407.46 | 09-JAN-10:40 | 4882.41 | 0.00 |
February | 0.00 | 0.00 | 0.257215E+11 | 0.250881E+11 | 128815.61 | 20-FEB-16:00 | 128815.61 | 0.00 |
March | 0.00 | 0.00 | 0.112791E+12 | 0.112474E+12 | 265852.02 | 21-MAR-16:00 | 265852.02 | 0.00 |
April | 0.00 | 0.00 | 0.540006E+12 | 0.522615E+12 | 410813.74 | 29-APR-17:08 | 392450.82 | 0.00 |
May | 0.00 | 0.00 | 0.178689E+12 | 0.170561E+12 | 194312.70 | 31-MAY-23:10 | 194312.70 | 0.00 |
June | 0.00 | 0.00 | 0.497609E+12 | 0.454782E+12 | 352125.49 | 03-JUN-17:43 | 218300.31 | 0.00 |
July | 0.00 | 0.00 | 0.100517E+13 | 0.711929E+12 | 491126.63 | 20-JUL-15:00 | 152315.78 | 0.00 |
August | 0.00 | 0.00 | 0.111058E+13 | 0.827770E+12 | 465737.79 | 01-AUG-21:12 | 182019.17 | 0.00 |
September | 0.00 | 0.00 | 0.173029E+12 | 0.147632E+12 | 235921.74 | 01-SEP-10:30 | 138057.16 | 0.00 |
October | 0.00 | 0.00 | 0.172793E+12 | 0.144351E+12 | 322777.54 | 04-OCT-11:30 | 216056.47 | 0.00 |
November | 0.00 | 0.00 | 0.768754E+11 | 0.722122E+11 | 253170.62 | 03-NOV-16:00 | 238203.19 | 0.00 |
December | 0.00 | 0.00 | 0.556462E+11 | 0.538135E+11 | 183561.32 | 10-DEC-15:00 | 183561.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.395901E+13 | 0.325229E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.100974E+11 | 0.906317E+10 | 5407.46 | 4882.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111058E+13 | 0.827770E+12 | 491126.63 | 392450.82 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.476666E+10 | 0.475311E+10 | 2698.30 | 01-JAN-16:53 | 2691.27 | 0.00 |
February | 0.00 | 0.00 | 0.919311E+10 | 0.917754E+10 | 4761.46 | 20-FEB-17:25 | 4761.46 | 0.00 |
March | 0.00 | 0.00 | 0.155634E+11 | 0.155598E+11 | 7675.81 | 31-MAR-24:00 | 7675.81 | 0.00 |
April | 0.00 | 0.00 | 0.202763E+11 | 0.202586E+11 | 8425.33 | 22-APR-18:35 | 8425.33 | 0.00 |
May | 0.00 | 0.00 | 0.617236E+10 | 0.611132E+10 | 4059.54 | 31-MAY-24:00 | 4052.33 | 0.00 |
June | 0.00 | 0.00 | 0.110927E+11 | 0.109822E+11 | 5930.12 | 30-JUN-23:55 | 5930.12 | 0.00 |
July | 0.00 | 0.00 | 0.167502E+11 | 0.164236E+11 | 7902.28 | 31-JUL-23:55 | 7889.85 | 0.00 |
August | 0.00 | 0.00 | 0.216445E+11 | 0.213733E+11 | 8497.90 | 13-AUG-23:15 | 8407.75 | 0.00 |
September | 0.00 | 0.00 | 0.621264E+10 | 0.600044E+10 | 4052.64 | 30-SEP-24:00 | 4052.64 | 0.00 |
October | 0.00 | 0.00 | 0.111225E+11 | 0.109627E+11 | 5841.98 | 31-OCT-24:00 | 5841.98 | 0.00 |
November | 0.00 | 0.00 | 0.151373E+11 | 0.150968E+11 | 6698.80 | 12-NOV-16:40 | 6691.31 | 0.00 |
December | 0.00 | 0.00 | 0.203213E+11 | 0.203150E+11 | 8369.50 | 17-DEC-16:47 | 8369.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158253E+12 | 0.157014E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.476666E+10 | 0.475311E+10 | 2698.30 | 2691.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216445E+11 | 0.213733E+11 | 8497.90 | 8425.33 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.306414E+11 | 0.305171E+11 | 21787.00 | 12-JAN-16:50 | 20905.50 | 0.00 |
February | 0.00 | 0.00 | 0.772245E+11 | 0.770710E+11 | 42421.93 | 19-FEB-17:24 | 42421.93 | 0.00 |
March | 0.00 | 0.00 | 0.140582E+12 | 0.140545E+12 | 71390.76 | 31-MAR-23:40 | 71390.76 | 0.00 |
April | 0.00 | 0.00 | 0.190844E+12 | 0.190667E+12 | 80040.42 | 22-APR-18:23 | 80040.42 | 0.00 |
May | 0.00 | 0.00 | 0.569633E+11 | 0.563615E+11 | 39461.55 | 31-MAY-24:00 | 39415.02 | 0.00 |
June | 0.00 | 0.00 | 0.105529E+12 | 0.104432E+12 | 57537.54 | 30-JUN-23:55 | 57537.54 | 0.00 |
July | 0.00 | 0.00 | 0.159356E+12 | 0.156100E+12 | 75885.92 | 31-JUL-23:55 | 75760.47 | 0.00 |
August | 0.00 | 0.00 | 0.204257E+12 | 0.201540E+12 | 80339.74 | 08-AUG-17:00 | 76299.50 | 0.00 |
September | 0.00 | 0.00 | 0.567332E+11 | 0.546465E+11 | 38069.16 | 30-SEP-23:50 | 38069.16 | 0.00 |
October | 0.00 | 0.00 | 0.101080E+12 | 0.995042E+11 | 53815.49 | 31-OCT-24:00 | 53815.49 | 0.00 |
November | 0.00 | 0.00 | 0.133862E+12 | 0.133461E+12 | 62241.80 | 09-NOV-16:50 | 61159.05 | 0.00 |
December | 0.00 | 0.00 | 0.177276E+12 | 0.177211E+12 | 75820.56 | 15-DEC-16:50 | 75820.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143435E+13 | 0.142206E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.306414E+11 | 0.305171E+11 | 21787.00 | 20905.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204257E+12 | 0.201540E+12 | 80339.74 | 80040.42 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143635E+10 | 0.142645E+10 | 2176.46 | 12-JAN-16:50 | 2088.70 | 0.00 |
February | 0.00 | 0.00 | 0.645093E+10 | 0.643607E+10 | 4128.30 | 21-FEB-17:30 | 4128.30 | 0.00 |
March | 0.00 | 0.00 | 0.131406E+11 | 0.131370E+11 | 6859.13 | 31-MAR-23:20 | 6859.13 | 0.00 |
April | 0.00 | 0.00 | 0.188665E+11 | 0.188488E+11 | 8039.68 | 22-APR-18:00 | 8039.68 | 0.00 |
May | 0.00 | 0.00 | 0.571355E+10 | 0.565321E+10 | 3993.10 | 31-MAY-24:00 | 3987.19 | 0.00 |
June | 0.00 | 0.00 | 0.107045E+11 | 0.105946E+11 | 5782.58 | 30-JUN-23:55 | 5782.58 | 0.00 |
July | 0.00 | 0.00 | 0.161261E+11 | 0.158003E+11 | 7605.34 | 31-JUL-23:55 | 7592.64 | 0.00 |
August | 0.00 | 0.00 | 0.205712E+11 | 0.202988E+11 | 8193.08 | 08-AUG-17:00 | 7779.15 | 0.00 |
September | 0.00 | 0.00 | 0.565328E+10 | 0.544417E+10 | 3680.20 | 30-SEP-23:20 | 3680.20 | 0.00 |
October | 0.00 | 0.00 | 0.966198E+10 | 0.950509E+10 | 5074.60 | 31-OCT-23:20 | 5074.60 | 0.00 |
November | 0.00 | 0.00 | 0.120503E+11 | 0.120105E+11 | 6262.54 | 09-NOV-16:50 | 6154.18 | 0.00 |
December | 0.00 | 0.00 | 0.157504E+11 | 0.157440E+11 | 7484.77 | 15-DEC-16:50 | 7484.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136126E+12 | 0.134899E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.143635E+10 | 0.142645E+10 | 2176.46 | 2088.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205712E+11 | 0.202988E+11 | 8193.08 | 8039.68 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14.54 | 187779.49 | 02-JAN-05:11 | 31484.69 | 1274289.81 | 26-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 20883.12 | 1131863.19 | 17-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10131.54 | 1045115.01 | 02-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 853.69 | 302091.17 | 11-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1.55 | 2479.96 | 02-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 5.68 | 15613.82 | 30-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 307.78 | 178103.78 | 24-OCT-10:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11792.62 | 1497639.98 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 41648.86 | 1273360.12 | 26-DEC-05:01 |
Annual Sum or Average | 1.23 | 9739.98 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 14.54 | 187779.49 | 41648.86 | 1497639.98 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21546.70 | 541385.83 | 12-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 51396.74 | 714158.16 | 21-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 101552.38 | 1057875.23 | 21-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 254314.62 | 1633392.14 | 27-APR-13:35 | 0.00 | 0.00 | 01-APR-00:10 |
May | 427444.92 | 2083470.25 | 18-MAY-13:13 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 593079.14 | 2109860.19 | 20-JUN-09:43 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 649220.64 | 2716779.00 | 21-JUL-10:20 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 568890.70 | 2103987.55 | 25-AUG-12:43 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 465677.88 | 2263285.92 | 29-SEP-13:22 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 234098.68 | 2024870.33 | 03-OCT-10:43 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 85232.67 | 912057.14 | 09-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14814.58 | 392148.00 | 07-DEC-15:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 290227.03 | 0.00 | ||||
Minimum of Months | 14814.58 | 392148.00 | 0.00 | 0.00 | ||
Maximum of Months | 649220.64 | 2716779.00 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 20726.13 | 548568.29 | 12-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50412.06 | 723892.98 | 21-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 100386.07 | 1057769.56 | 21-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 255964.03 | 2185286.49 | 27-APR-15:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 444157.73 | 2666075.11 | 26-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 637481.07 | 2658662.94 | 08-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 671523.47 | 2726271.33 | 21-JUL-10:20 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 617012.50 | 2556835.55 | 03-AUG-04:12 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 508883.32 | 2488151.07 | 29-SEP-13:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 266507.24 | 2283089.35 | 02-OCT-10:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 86231.12 | 1512017.37 | 03-NOV-14:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13918.73 | 392912.31 | 07-DEC-15:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 307478.11 | 0.00 | ||||
Minimum of Months | 13918.73 | 392912.31 | 0.00 | 0.00 | ||
Maximum of Months | 671523.47 | 2726271.33 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 26938.41 | 180399.30 | 03-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 85434.95 | 622466.91 | 20-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 199204.97 | 1050796.39 | 21-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 728258.01 | 1749517.88 | 21-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 505090.46 | 1254793.67 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1011444.48 | 1732424.67 | 02-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1404312.21 | 1956442.36 | 03-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1453214.69 | 2090366.38 | 07-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 481794.58 | 1195148.65 | 19-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 321535.39 | 1373574.60 | 03-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 151796.69 | 951574.69 | 03-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 130350.84 | 524611.26 | 10-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 544797.39 | 0.00 | ||||
Minimum of Months | 26938.41 | 180399.30 | 0.00 | 0.00 | ||
Maximum of Months | 1453214.69 | 2090366.38 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14431.88 | 48125.65 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14496.20 | 48122.90 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 14799.18 | 47236.59 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13125.19 | 44548.63 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 12531.31 | 41458.14 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11897.61 | 38049.99 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 10589.77 | 35552.69 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11469.04 | 35711.21 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 11342.04 | 37999.27 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12163.96 | 41504.47 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13284.41 | 44781.88 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13654.34 | 47152.41 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12806.01 | ||||
Minimum of Months | 0.00 | 0.00 | 10589.77 | 35552.69 | ||
Maximum of Months | 0.00 | 0.00 | 14799.18 | 48125.65 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 20106.19 | 625244.46 | 12-JAN-15:10 | 5131.48 | 129641.29 | 02-JAN-06:40 |
February | 54941.55 | 812408.20 | 21-FEB-15:10 | 3412.24 | 118805.86 | 03-FEB-09:40 |
March | 114130.13 | 1202264.45 | 21-MAR-16:00 | 2221.84 | 121620.04 | 29-MAR-05:40 |
April | 309283.50 | 2234052.86 | 28-APR-12:50 | 2708.03 | 98893.10 | 14-APR-07:00 |
May | 549608.72 | 3348480.93 | 19-MAY-11:53 | 627.97 | 93400.22 | 01-MAY-06:20 |
June | 798822.72 | 3183442.05 | 20-JUN-10:03 | 478.83 | 64613.97 | 13-JUN-03:00 |
July | 1169016.83 | 5188557.48 | 21-JUL-10:25 | 20.31 | 12117.96 | 16-JUL-05:20 |
August | 867534.35 | 4256485.24 | 02-AUG-08:20 | 500.12 | 44101.70 | 27-AUG-04:50 |
September | 687771.19 | 3957503.72 | 14-SEP-09:50 | 88.45 | 30563.97 | 25-SEP-07:10 |
October | 305797.14 | 3268753.89 | 18-OCT-12:32 | 631.13 | 71368.83 | 31-OCT-18:30 |
November | 96251.35 | 1034558.57 | 09-NOV-15:00 | 2508.72 | 114052.99 | 27-NOV-10:30 |
December | 9690.29 | 460925.18 | 07-DEC-15:10 | 6050.96 | 131398.32 | 18-DEC-06:20 |
Annual Sum or Average | 417574.30 | 2026.74 | ||||
Minimum of Months | 9690.29 | 460925.18 | 20.31 | 12117.96 | ||
Maximum of Months | 1169016.83 | 5188557.48 | 6050.96 | 131398.32 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143317E+11 | 0.91 | 9427.00 | 01-JAN-00:20 | 1.60 |
February | 0.125186E+11 | 0.88 | 9427.00 | 01-FEB-05:01 | 1.61 |
March | 0.146840E+11 | 0.93 | 9427.00 | 01-MAR-05:01 | 1.61 |
April | 0.134420E+11 | 0.88 | 9427.00 | 01-APR-04:13 | 1.61 |
May | 0.144223E+11 | 0.91 | 9427.00 | 01-MAY-04:12 | 1.61 |
June | 0.142348E+11 | 0.93 | 9427.00 | 01-JUN-04:12 | 1.60 |
July | 0.144980E+11 | 0.91 | 9427.00 | 01-JUL-04:05 | 1.60 |
August | 0.160939E+11 | 1.01 | 9427.00 | 01-AUG-03:02 | 1.59 |
September | 0.151412E+11 | 0.98 | 9427.00 | 01-SEP-04:12 | 1.59 |
October | 0.152850E+11 | 0.96 | 9427.00 | 01-OCT-14:39 | 1.60 |
November | 0.143762E+11 | 0.94 | 9427.00 | 01-NOV-04:12 | 1.59 |
December | 0.142536E+11 | 0.91 | 9427.00 | 01-DEC-05:12 | 1.60 |
Annual Sum or Average | 0.173281E+12 | 0.93 | |||
Minimum of Months | 0.125186E+11 | 0.88 | 9427.00 | 1.59 | |
Maximum of Months | 0.160939E+11 | 1.01 | 9427.00 | 1.61 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.442607E+10 | 0.38 | 10772.35 | 28-JAN-06:01 | 1.33 |
February | 0.492295E+10 | 0.43 | 12834.93 | 21-FEB-16:30 | 1.48 |
March | 0.764436E+10 | 0.51 | 12759.42 | 16-MAR-15:40 | 1.48 |
April | 0.106642E+11 | 0.68 | 21438.90 | 27-APR-13:20 | 2.03 |
May | 0.109691E+11 | 0.63 | 21438.90 | 08-MAY-14:35 | 2.03 |
June | 0.145212E+11 | 0.81 | 21438.90 | 02-JUN-05:02 | 2.04 |
July | 0.143424E+11 | 0.82 | 21438.90 | 01-JUL-14:50 | 2.02 |
August | 0.177524E+11 | 0.92 | 21438.90 | 01-AUG-05:03 | 2.02 |
September | 0.107747E+11 | 0.62 | 21438.90 | 01-SEP-16:24 | 2.02 |
October | 0.899314E+10 | 0.55 | 21438.90 | 02-OCT-04:03 | 2.03 |
November | 0.651942E+10 | 0.46 | 12942.26 | 13-NOV-16:00 | 1.48 |
December | 0.578228E+10 | 0.43 | 10948.30 | 11-DEC-05:11 | 1.34 |
Annual Sum or Average | 0.117312E+12 | 0.60 | |||
Minimum of Months | 0.442607E+10 | 0.38 | 10772.35 | 1.33 | |
Maximum of Months | 0.177524E+11 | 0.92 | 21438.90 | 2.04 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.283201E+11 | 0.34 | 84728.62 | 13-JAN-06:03 | 1.20 |
February | 0.301538E+11 | 0.36 | 87595.02 | 25-FEB-06:02 | 1.22 |
March | 0.433504E+11 | 0.41 | 91237.08 | 16-MAR-15:50 | 1.25 |
April | 0.610357E+11 | 0.48 | 200124.93 | 20-APR-05:02 | 2.04 |
May | 0.906748E+11 | 0.58 | 200124.93 | 08-MAY-14:35 | 2.03 |
June | 0.119988E+12 | 0.70 | 200124.93 | 02-JUN-05:02 | 2.04 |
July | 0.101186E+12 | 0.62 | 200124.93 | 01-JUL-05:02 | 2.03 |
August | 0.109040E+12 | 0.65 | 200124.93 | 01-AUG-05:03 | 2.02 |
September | 0.831162E+11 | 0.55 | 200124.93 | 01-SEP-16:26 | 2.02 |
October | 0.562833E+11 | 0.44 | 200124.93 | 02-OCT-05:02 | 2.03 |
November | 0.349777E+11 | 0.37 | 91523.71 | 21-NOV-06:03 | 1.26 |
December | 0.276804E+11 | 0.34 | 116930.97 | 01-DEC-06:02 | 1.46 |
Annual Sum or Average | 0.785807E+12 | 0.49 | |||
Minimum of Months | 0.276804E+11 | 0.34 | 84728.62 | 1.20 | |
Maximum of Months | 0.119988E+12 | 0.70 | 200124.93 | 2.04 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264852E+10 | 0.36 | 4538.89 | 07-JAN-06:01 | 0.79 |
February | 0.258098E+10 | 0.37 | 4582.79 | 23-FEB-14:40 | 0.79 |
March | 0.353428E+10 | 0.40 | 9188.45 | 16-MAR-15:30 | 1.17 |
April | 0.567183E+10 | 0.45 | 22550.95 | 28-APR-13:45 | 2.02 |
May | 0.925337E+10 | 0.55 | 22550.95 | 08-MAY-14:35 | 2.02 |
June | 0.133846E+11 | 0.71 | 22550.95 | 05-JUN-04:12 | 2.02 |
July | 0.112231E+11 | 0.63 | 22550.95 | 01-JUL-14:43 | 2.01 |
August | 0.117637E+11 | 0.64 | 22550.95 | 02-AUG-05:03 | 2.00 |
September | 0.827355E+10 | 0.52 | 22550.95 | 01-SEP-16:24 | 2.01 |
October | 0.501248E+10 | 0.41 | 22550.95 | 02-OCT-05:02 | 2.01 |
November | 0.297154E+10 | 0.37 | 7336.71 | 09-NOV-16:20 | 1.01 |
December | 0.264645E+10 | 0.36 | 4538.89 | 04-DEC-05:11 | 0.78 |
Annual Sum or Average | 0.789644E+11 | 0.48 | |||
Minimum of Months | 0.258098E+10 | 0.36 | 4538.89 | 0.78 | |
Maximum of Months | 0.133846E+11 | 0.71 | 22550.95 | 2.02 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108189E+12 | 1.55 | 40393.30 | 01-JAN-00:05 | 1.55 |
February | 0.977195E+11 | 1.56 | 40393.30 | 01-FEB-00:20 | 1.56 |
March | 0.108189E+12 | 1.56 | 40393.30 | 01-MAR-00:10 | 1.56 |
April | 0.104699E+12 | 1.56 | 40393.30 | 01-APR-00:10 | 1.57 |
May | 0.108189E+12 | 1.55 | 40393.30 | 01-MAY-00:03 | 1.56 |
June | 0.104699E+12 | 1.55 | 40393.30 | 01-JUN-00:20 | 1.56 |
July | 0.108189E+12 | 1.54 | 40393.30 | 01-JUL-00:03 | 1.55 |
August | 0.108189E+12 | 1.54 | 40393.30 | 01-AUG-00:05 | 1.54 |
September | 0.104699E+12 | 1.54 | 40393.30 | 01-SEP-00:10 | 1.54 |
October | 0.108189E+12 | 1.55 | 40393.30 | 01-OCT-00:10 | 1.56 |
November | 0.104699E+12 | 1.56 | 40393.30 | 01-NOV-00:10 | 1.56 |
December | 0.108189E+12 | 1.56 | 40393.30 | 01-DEC-00:10 | 1.56 |
Annual Sum or Average | 0.127384E+13 | 1.55 | |||
Minimum of Months | 0.977195E+11 | 1.54 | 40393.30 | 1.54 | |
Maximum of Months | 0.108189E+12 | 1.56 | 40393.30 | 1.57 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157868E+10 | 1.06 | 589.41 | 01-JAN-00:05 | 1.06 |
February | 0.142591E+10 | 1.06 | 589.41 | 01-FEB-00:10 | 1.06 |
March | 0.157868E+10 | 1.06 | 589.41 | 01-MAR-00:10 | 1.06 |
April | 0.152776E+10 | 1.06 | 589.41 | 01-APR-00:10 | 1.06 |
May | 0.157868E+10 | 1.06 | 589.41 | 01-MAY-00:03 | 1.05 |
June | 0.152776E+10 | 1.05 | 589.41 | 01-JUN-00:10 | 1.05 |
July | 0.157868E+10 | 1.05 | 589.41 | 01-JUL-00:03 | 1.05 |
August | 0.157868E+10 | 1.05 | 589.41 | 01-AUG-00:05 | 1.05 |
September | 0.152776E+10 | 1.05 | 589.41 | 01-SEP-00:10 | 1.05 |
October | 0.157868E+10 | 1.05 | 589.41 | 01-OCT-00:10 | 1.06 |
November | 0.152776E+10 | 1.06 | 589.41 | 01-NOV-00:10 | 1.06 |
December | 0.157868E+10 | 1.06 | 589.41 | 01-DEC-00:10 | 1.06 |
Annual Sum or Average | 0.185877E+11 | 1.06 | |||
Minimum of Months | 0.142591E+10 | 1.05 | 589.41 | 1.05 | |
Maximum of Months | 0.157868E+10 | 1.06 | 589.41 | 1.06 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150655E+11 | 1.06 | 5624.80 | 01-JAN-00:05 | 1.06 |
February | 0.136075E+11 | 1.06 | 5624.80 | 01-FEB-00:10 | 1.06 |
March | 0.150655E+11 | 1.06 | 5624.80 | 01-MAR-00:10 | 1.06 |
April | 0.145795E+11 | 1.06 | 5624.80 | 01-APR-00:10 | 1.06 |
May | 0.150655E+11 | 1.06 | 5624.80 | 01-MAY-00:03 | 1.05 |
June | 0.145795E+11 | 1.05 | 5624.80 | 01-JUN-00:10 | 1.05 |
July | 0.150655E+11 | 1.05 | 5624.80 | 01-JUL-00:03 | 1.05 |
August | 0.150655E+11 | 1.05 | 5624.80 | 01-AUG-00:05 | 1.05 |
September | 0.145795E+11 | 1.05 | 5624.80 | 01-SEP-00:10 | 1.05 |
October | 0.150655E+11 | 1.05 | 5624.80 | 01-OCT-00:10 | 1.06 |
November | 0.145795E+11 | 1.06 | 5624.80 | 01-NOV-00:10 | 1.06 |
December | 0.150655E+11 | 1.06 | 5624.80 | 01-DEC-00:10 | 1.06 |
Annual Sum or Average | 0.177384E+12 | 1.06 | |||
Minimum of Months | 0.136075E+11 | 1.05 | 5624.80 | 1.05 | |
Maximum of Months | 0.150655E+11 | 1.06 | 5624.80 | 1.06 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154079E+10 | 1.06 | 575.26 | 01-JAN-00:05 | 1.06 |
February | 0.139168E+10 | 1.06 | 575.26 | 01-FEB-00:10 | 1.06 |
March | 0.154079E+10 | 1.06 | 575.26 | 01-MAR-00:30 | 1.06 |
April | 0.149109E+10 | 1.06 | 575.26 | 01-APR-00:10 | 1.06 |
May | 0.154079E+10 | 1.06 | 575.26 | 01-MAY-00:07 | 1.05 |
June | 0.149109E+10 | 1.05 | 575.26 | 01-JUN-00:10 | 1.05 |
July | 0.154079E+10 | 1.05 | 575.26 | 01-JUL-00:03 | 1.05 |
August | 0.154079E+10 | 1.05 | 575.26 | 01-AUG-00:05 | 1.05 |
September | 0.149109E+10 | 1.05 | 575.26 | 01-SEP-00:10 | 1.05 |
October | 0.154079E+10 | 1.05 | 575.26 | 01-OCT-00:10 | 1.06 |
November | 0.149109E+10 | 1.06 | 575.26 | 01-NOV-00:10 | 1.06 |
December | 0.154079E+10 | 1.06 | 575.26 | 01-DEC-00:10 | 1.06 |
Annual Sum or Average | 0.181415E+11 | 1.06 | |||
Minimum of Months | 0.139168E+10 | 1.05 | 575.26 | 1.05 | |
Maximum of Months | 0.154079E+10 | 1.06 | 575.26 | 1.06 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.833303E+09 | 0.757472E+09 | 8141.35 | 28-JAN-06:01 | 7400.49 | 7400.49 | 43.33 | 14.43 |
February | 0.508493E+09 | 0.462220E+09 | 8037.91 | 02-FEB-06:01 | 7306.46 | 7306.46 | 43.02 | 14.02 |
March | 0.266159E+09 | 0.241939E+09 | 7974.24 | 02-MAR-06:01 | 7248.59 | 7248.59 | 41.86 | 13.79 |
April | 19608307.90 | 17823951.88 | 2495.38 | 11-APR-05:03 | 2268.30 | 2268.30 | 34.57 | 2.84 |
May | 33849.04 | 30768.78 | 20.24 | 02-MAY-06:10 | 18.40 | 18.40 | 31.49 | 0.02 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 31.44 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 31.44 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 31.44 | 0.00 |
September | 119302.68 | 108446.14 | 126.42 | 30-SEP-06:10 | 114.91 | 114.91 | 31.38 | 0.13 |
October | 6599262.36 | 5998729.49 | 1352.78 | 24-OCT-10:00 | 1229.68 | 1229.68 | 30.94 | 1.47 |
November | 0.287989E+09 | 0.261782E+09 | 8046.78 | 28-NOV-06:01 | 7314.52 | 7314.52 | 43.20 | 14.05 |
December | 0.115249E+10 | 0.104761E+10 | 8104.29 | 27-DEC-06:01 | 7366.80 | 7366.80 | 44.17 | 14.27 |
Annual Sum or Average | 0.307479E+10 | 0.279498E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 | 0.00 | |
Maximum of Months | 0.115249E+10 | 0.104761E+10 | 8141.35 | 7400.49 | 7400.49 | 44.17 | 14.43 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 16538727.65 | 15033703.44 | 489.16 | 12-JAN-15:05 | 444.65 | 444.65 | 6.71 | 17.02 |
February | 46050024.19 | 41859471.98 | 732.08 | 21-FEB-14:10 | 665.46 | 665.46 | 6.71 | 20.51 |
March | 0.115146E+09 | 0.104668E+09 | 1206.66 | 21-MAR-16:00 | 1096.85 | 1096.85 | 6.71 | 25.65 |
April | 0.742254E+09 | 0.674709E+09 | 9842.87 | 27-APR-13:45 | 8947.17 | 8947.17 | 8.70 | 61.18 |
May | 0.202968E+10 | 0.184498E+10 | 10019.93 | 08-MAY-14:35 | 9108.11 | 9108.11 | 6.73 | 61.61 |
June | 0.422724E+10 | 0.384256E+10 | 10019.93 | 05-JUN-04:12 | 9108.11 | 9108.11 | 8.23 | 61.61 |
July | 0.369361E+10 | 0.335749E+10 | 10019.93 | 01-JUL-05:02 | 9108.11 | 9108.11 | 9.49 | 61.61 |
August | 0.404997E+10 | 0.368142E+10 | 10019.93 | 02-AUG-04:11 | 9108.11 | 9108.11 | 9.02 | 61.61 |
September | 0.357595E+10 | 0.325054E+10 | 10019.93 | 01-SEP-05:03 | 9108.11 | 9108.11 | 9.25 | 61.61 |
October | 0.185466E+10 | 0.168588E+10 | 10019.93 | 02-OCT-05:02 | 9108.11 | 9108.11 | 8.55 | 61.61 |
November | 0.221745E+09 | 0.201566E+09 | 9152.06 | 03-NOV-14:50 | 8319.22 | 8319.22 | 9.61 | 59.45 |
December | 7083090.29 | 6438529.07 | 235.48 | 07-DEC-14:50 | 214.05 | 214.05 | 6.70 | 11.96 |
Annual Sum or Average | 0.205799E+11 | 0.187072E+11 | ||||||
Minimum of Months | 7083090.29 | 6438529.07 | 235.48 | 214.05 | 214.05 | 6.70 | 11.96 | |
Maximum of Months | 0.422724E+10 | 0.384256E+10 | 10019.93 | 9108.11 | 9108.11 | 9.61 | 61.61 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.245507E+10 | 0.223166E+10 | 3448.22 | 01-JAN-12:13 | 3134.43 | 3134.43 | 6.82 | 30.81 |
February | 0.273606E+10 | 0.248708E+10 | 3448.22 | 01-FEB-09:35 | 3134.43 | 3134.43 | 6.73 | 30.81 |
March | 0.376480E+10 | 0.342221E+10 | 3448.22 | 01-MAR-06:15 | 3134.43 | 3134.43 | 6.78 | 30.81 |
April | 0.586969E+10 | 0.533555E+10 | 3448.22 | 01-APR-05:02 | 3134.43 | 3134.43 | 6.95 | 30.81 |
May | 0.634953E+10 | 0.577173E+10 | 3448.22 | 01-MAY-00:03 | 3134.43 | 3134.43 | 6.85 | 30.81 |
June | 0.760349E+10 | 0.691158E+10 | 3448.22 | 01-JUN-04:12 | 3134.43 | 3134.43 | 10.05 | 30.81 |
July | 0.843479E+10 | 0.766723E+10 | 3448.22 | 01-JUL-00:20 | 3134.43 | 3134.43 | 6.90 | 30.81 |
August | 0.843246E+10 | 0.766510E+10 | 3448.22 | 01-AUG-00:05 | 3134.43 | 3134.43 | 7.80 | 30.81 |
September | 0.599056E+10 | 0.544542E+10 | 3448.22 | 01-SEP-00:10 | 3134.43 | 3134.43 | 6.86 | 30.81 |
October | 0.498247E+10 | 0.452907E+10 | 3448.22 | 01-OCT-07:23 | 3134.43 | 3134.43 | 6.81 | 30.81 |
November | 0.319380E+10 | 0.290316E+10 | 3448.22 | 01-NOV-04:12 | 3134.43 | 3134.43 | 7.14 | 30.81 |
December | 0.265341E+10 | 0.241195E+10 | 3448.22 | 01-DEC-06:55 | 3134.43 | 3134.43 | 6.78 | 30.81 |
Annual Sum or Average | 0.624662E+11 | 0.567817E+11 | ||||||
Minimum of Months | 0.245507E+10 | 0.223166E+10 | 3448.22 | 3134.43 | 3134.43 | 6.73 | 30.81 | |
Maximum of Months | 0.843479E+10 | 0.766723E+10 | 3448.22 | 3134.43 | 3134.43 | 10.05 | 30.81 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.73 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.88 | 0.00 |
April | 0.488268E+09 | 0.443836E+09 | 3448.22 | 03-APR-12:05 | 3134.43 | 3134.43 | 11.27 | 30.81 |
May | 0.126929E+10 | 0.115379E+10 | 3448.22 | 02-MAY-15:10 | 3134.43 | 3134.43 | 15.63 | 15.40 |
June | 0.223503E+10 | 0.203165E+10 | 3448.22 | 01-JUN-08:00 | 3134.43 | 3134.43 | 15.64 | 15.40 |
July | 0.267910E+10 | 0.243530E+10 | 3448.22 | 01-JUL-13:50 | 3134.43 | 3134.43 | 15.26 | 15.40 |
August | 0.189476E+10 | 0.172234E+10 | 3448.22 | 01-AUG-07:40 | 3134.43 | 3134.43 | 15.22 | 15.40 |
September | 0.148949E+10 | 0.135395E+10 | 3448.22 | 01-SEP-07:20 | 3134.43 | 3134.43 | 15.48 | 15.40 |
October | 0.298271E+09 | 0.271129E+09 | 3448.22 | 02-OCT-10:10 | 3134.43 | 3134.43 | 15.43 | 15.40 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.83 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.88 | 0.00 |
Annual Sum or Average | 0.103542E+11 | 0.941198E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 0.00 | |
Maximum of Months | 0.267910E+10 | 0.243530E+10 | 3448.22 | 3134.43 | 3134.43 | 15.64 | 30.81 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.957925E+10 | 0.870754E+10 | 3576.48 | 01-JAN-00:05 | 3251.02 | 3251.02 | 18.79 | 15.09 |
February | 0.865223E+10 | 0.786488E+10 | 3576.48 | 01-FEB-00:10 | 3251.02 | 3251.02 | 19.35 | 15.09 |
March | 0.957925E+10 | 0.870754E+10 | 3576.48 | 01-MAR-00:10 | 3251.02 | 3251.02 | 19.87 | 15.09 |
April | 0.927024E+10 | 0.842665E+10 | 3576.48 | 01-APR-00:10 | 3251.02 | 3251.02 | 20.54 | 15.09 |
May | 0.957925E+10 | 0.870754E+10 | 3576.48 | 01-MAY-00:03 | 3251.02 | 3251.02 | 21.83 | 15.09 |
June | 0.927024E+10 | 0.842665E+10 | 3576.48 | 01-JUN-00:10 | 3251.02 | 3251.02 | 33.55 | 15.09 |
July | 0.957925E+10 | 0.870754E+10 | 3576.48 | 01-JUL-00:03 | 3251.02 | 3251.02 | 42.59 | 15.09 |
August | 0.957925E+10 | 0.870754E+10 | 3576.48 | 01-AUG-00:05 | 3251.02 | 3251.02 | 47.05 | 15.09 |
September | 0.927024E+10 | 0.842665E+10 | 3576.48 | 01-SEP-00:10 | 3251.02 | 3251.02 | 25.82 | 15.09 |
October | 0.957925E+10 | 0.870754E+10 | 3576.48 | 01-OCT-00:10 | 3251.02 | 3251.02 | 19.61 | 15.09 |
November | 0.927024E+10 | 0.842665E+10 | 3576.48 | 01-NOV-00:10 | 3251.02 | 3251.02 | 20.06 | 15.09 |
December | 0.957925E+10 | 0.870754E+10 | 3576.48 | 01-DEC-00:10 | 3251.02 | 3251.02 | 20.41 | 15.09 |
Annual Sum or Average | 0.112788E+12 | 0.102524E+12 | ||||||
Minimum of Months | 0.865223E+10 | 0.786488E+10 | 3576.48 | 3251.02 | 3251.02 | 18.79 | 15.09 | |
Maximum of Months | 0.957925E+10 | 0.870754E+10 | 3576.48 | 3251.02 | 3251.02 | 47.05 | 15.09 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.87 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.08 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.08 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.21 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.28 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.94 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 57.38 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.68 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.84 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.18 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.59 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 56.66 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.87 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.68 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.936102E+10 | 0.850917E+10 | 13171.79 | 12-JAN-15:10 | 11973.15 | 11973.15 | 23.88 | 53.81 |
February | 0.104358E+11 | 0.948613E+10 | 13179.68 | 21-FEB-15:10 | 11980.33 | 11980.33 | 24.71 | 53.81 |
March | 0.143650E+11 | 0.130578E+11 | 13198.42 | 21-MAR-16:00 | 11997.36 | 11997.36 | 26.45 | 53.81 |
April | 0.241733E+11 | 0.219735E+11 | 26388.49 | 28-APR-12:50 | 23987.14 | 23987.14 | 26.07 | 107.61 |
May | 0.288040E+11 | 0.261829E+11 | 26443.41 | 19-MAY-11:53 | 24037.06 | 24037.06 | 28.54 | 107.61 |
June | 0.372212E+11 | 0.338341E+11 | 26435.26 | 20-JUN-10:03 | 24029.65 | 24029.65 | 28.18 | 107.61 |
July | 0.423452E+11 | 0.384918E+11 | 26449.25 | 17-JUL-05:04 | 24042.37 | 24042.37 | 29.15 | 107.61 |
August | 0.392774E+11 | 0.357032E+11 | 26449.25 | 02-AUG-07:30 | 24042.37 | 24042.37 | 28.97 | 107.61 |
September | 0.284908E+11 | 0.258981E+11 | 26449.25 | 14-SEP-09:40 | 24042.37 | 24042.37 | 29.04 | 107.61 |
October | 0.201588E+11 | 0.183243E+11 | 26439.47 | 18-OCT-12:32 | 24033.48 | 24033.48 | 28.37 | 107.61 |
November | 0.121858E+11 | 0.110769E+11 | 13190.16 | 09-NOV-15:00 | 11989.85 | 11989.85 | 25.70 | 53.81 |
December | 0.101159E+11 | 0.919533E+10 | 13164.86 | 07-DEC-15:10 | 11966.86 | 11966.86 | 23.15 | 53.81 |
Annual Sum or Average | 0.276934E+12 | 0.251733E+12 | ||||||
Minimum of Months | 0.936102E+10 | 0.850917E+10 | 13164.86 | 11966.86 | 11966.86 | 23.15 | 53.81 | |
Maximum of Months | 0.423452E+11 | 0.384918E+11 | 26449.25 | 24042.37 | 24042.37 | 29.15 | 107.61 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14.54 | 187779.49 | 02-JAN-05:11 | 59.11 | 59.11 | 31484.69 | 1274289.81 | 26-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 31.77 | 31.77 | 20883.12 | 1131863.19 | 17-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 32.14 | 32.14 | 10131.54 | 1045115.01 | 02-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33.19 | 33.19 | 853.69 | 302091.17 | 11-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 31.49 | 31.49 | 1.55 | 2479.96 | 02-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 31.44 | 31.44 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.44 | 31.44 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 31.44 | 31.44 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.44 | 31.44 | 5.68 | 15613.82 | 30-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 31.26 | 31.26 | 307.78 | 178103.78 | 24-OCT-10:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32.01 | 32.01 | 11792.62 | 1497639.98 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 34.20 | 34.20 | 41648.86 | 1273360.12 | 26-DEC-05:01 |
Annual Sum or Average | 1.23 | 9739.98 | ||||||
Minimum of Months | 0.00 | 0.00 | 31.26 | 31.26 | 0.00 | 0.00 | ||
Maximum of Months | 14.54 | 187779.49 | 59.11 | 59.11 | 41648.86 | 1497639.98 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21546.70 | 541385.83 | 12-JAN-15:05 | 10.89 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 51396.74 | 714158.16 | 21-FEB-15:05 | 12.23 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 101552.38 | 1057875.23 | 21-MAR-16:00 | 14.90 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 254314.62 | 1633392.14 | 27-APR-13:35 | 13.03 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 427444.92 | 2083470.25 | 18-MAY-13:13 | 14.78 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 593079.14 | 2109860.19 | 20-JUN-09:43 | 14.88 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 649220.64 | 2716779.00 | 21-JUL-10:20 | 17.24 | 8.71 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 568890.70 | 2103987.55 | 25-AUG-12:43 | 14.86 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 465677.88 | 2263285.92 | 29-SEP-13:22 | 15.48 | 6.95 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 234098.68 | 2024870.33 | 03-OCT-10:43 | 14.55 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 85232.67 | 912057.14 | 09-NOV-16:00 | 13.77 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14814.58 | 392148.00 | 07-DEC-15:10 | 9.74 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 290227.03 | 0.00 | ||||||
Minimum of Months | 14814.58 | 392148.00 | 9.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 649220.64 | 2716779.00 | 17.24 | 8.71 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 20726.13 | 548568.29 | 12-JAN-15:05 | 14.40 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50412.06 | 723892.98 | 21-FEB-15:05 | 16.07 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 100386.07 | 1057769.56 | 21-MAR-16:00 | 16.56 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 255964.03 | 2185286.49 | 27-APR-15:50 | 15.32 | 11.14 | 0.00 | 0.00 | 01-APR-00:10 |
May | 444157.73 | 2666075.11 | 26-MAY-13:00 | 17.04 | 11.86 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 637481.07 | 2658662.94 | 08-JUN-05:02 | 17.01 | 11.84 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 671523.47 | 2726271.33 | 21-JUL-10:20 | 17.38 | 8.64 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 617012.50 | 2556835.55 | 03-AUG-04:12 | 16.62 | 11.65 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 508883.32 | 2488151.07 | 29-SEP-13:20 | 16.35 | 11.51 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 266507.24 | 2283089.35 | 02-OCT-10:10 | 15.56 | 11.12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 86231.12 | 1512017.37 | 03-NOV-14:50 | 12.77 | 9.62 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13918.73 | 392912.31 | 07-DEC-15:05 | 14.69 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 307478.11 | 0.00 | ||||||
Minimum of Months | 13918.73 | 392912.31 | 12.77 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 671523.47 | 2726271.33 | 17.38 | 11.86 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 26938.41 | 180399.30 | 03-JAN-17:00 | 21.77 | 21.00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 85434.95 | 622466.91 | 20-FEB-16:00 | 30.11 | 25.65 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 199204.97 | 1050796.39 | 21-MAR-16:00 | 38.07 | 29.54 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 728258.01 | 1749517.88 | 21-APR-15:00 | 50.80 | 38.75 | 0.00 | 0.00 | 01-APR-00:10 |
May | 505090.46 | 1254793.67 | 19-MAY-16:00 | 41.82 | 37.38 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1011444.48 | 1732424.67 | 02-JUN-16:00 | 50.49 | 42.98 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1404312.21 | 1956442.36 | 03-JUL-16:00 | 54.52 | 44.03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1453214.69 | 2090366.38 | 07-AUG-16:10 | 56.91 | 44.13 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 481794.58 | 1195148.65 | 19-SEP-16:00 | 40.72 | 36.28 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 321535.39 | 1373574.60 | 03-OCT-14:00 | 43.99 | 36.71 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 151796.69 | 951574.69 | 03-NOV-16:00 | 36.24 | 28.18 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 130350.84 | 524611.26 | 10-DEC-15:00 | 28.28 | 21.73 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 544797.39 | 0.00 | ||||||
Minimum of Months | 26938.41 | 180399.30 | 21.77 | 21.00 | 0.00 | 0.00 | ||
Maximum of Months | 1453214.69 | 2090366.38 | 56.91 | 44.13 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.66 | 57.66 | 14431.88 | 48125.65 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.63 | 56.63 | 14496.20 | 48122.90 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.68 | 56.68 | 14799.18 | 47236.59 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.70 | 56.70 | 13125.19 | 44548.63 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.21 | 57.21 | 12531.31 | 41458.14 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.36 | 57.36 | 11897.61 | 38049.99 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.74 | 57.74 | 10589.77 | 35552.69 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.08 | 58.08 | 11469.04 | 35711.21 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.26 | 57.26 | 11342.04 | 37999.27 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.29 | 57.29 | 12163.96 | 41504.47 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.01 | 57.01 | 13284.41 | 44781.88 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.17 | 57.17 | 13654.34 | 47152.41 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12806.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.63 | 56.63 | 10589.77 | 35552.69 | ||
Maximum of Months | 0.00 | 0.00 | 58.08 | 58.08 | 14799.18 | 48125.65 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 20106.19 | 625244.46 | 12-JAN-15:10 | 23.88 | 21.10 | 5131.48 | 129641.29 | 02-JAN-06:40 |
February | 54941.55 | 812408.20 | 21-FEB-15:10 | 24.71 | 21.10 | 3412.24 | 118805.86 | 03-FEB-09:40 |
March | 114130.13 | 1202264.45 | 21-MAR-16:00 | 26.45 | 21.10 | 2221.84 | 121620.04 | 29-MAR-05:40 |
April | 309283.50 | 2234052.86 | 28-APR-12:50 | 26.07 | 21.11 | 2708.03 | 98893.10 | 14-APR-07:00 |
May | 549608.72 | 3348480.93 | 19-MAY-11:53 | 28.54 | 23.69 | 627.97 | 93400.22 | 01-MAY-06:20 |
June | 798822.72 | 3183442.05 | 20-JUN-10:03 | 28.18 | 23.14 | 478.83 | 64613.97 | 13-JUN-03:00 |
July | 1169016.83 | 5188557.48 | 21-JUL-10:25 | 32.63 | 27.05 | 20.31 | 12117.96 | 16-JUL-05:20 |
August | 867534.35 | 4256485.24 | 02-AUG-08:20 | 30.56 | 25.58 | 500.12 | 44101.70 | 27-AUG-04:50 |
September | 687771.19 | 3957503.72 | 14-SEP-09:50 | 29.90 | 25.17 | 88.45 | 30563.97 | 25-SEP-07:10 |
October | 305797.14 | 3268753.89 | 18-OCT-12:32 | 28.37 | 23.63 | 631.13 | 71368.83 | 31-OCT-18:30 |
November | 96251.35 | 1034558.57 | 09-NOV-15:00 | 25.70 | 21.10 | 2508.72 | 114052.99 | 27-NOV-10:30 |
December | 9690.29 | 460925.18 | 07-DEC-15:10 | 23.15 | 21.10 | 6050.96 | 131398.32 | 18-DEC-06:20 |
Annual Sum or Average | 417574.30 | 2026.74 | ||||||
Minimum of Months | 9690.29 | 460925.18 | 23.15 | 21.10 | 20.31 | 12117.96 | ||
Maximum of Months | 1169016.83 | 5188557.48 | 32.63 | 27.05 | 6050.96 | 131398.32 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.280842E+10 | 0.00 | 0.142286E+11 | 0.442607E+10 | 0.00 | 0.00 |
February | 0.183744E+10 | 0.00 | 0.155526E+11 | 0.492295E+10 | 0.00 | 0.00 |
March | 0.979255E+09 | 0.00 | 0.264681E+11 | 0.764436E+10 | 0.00 | 0.00 |
April | 36445715.51 | 0.00 | 0.654378E+11 | 0.106642E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.955172E+11 | 0.109691E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.134090E+12 | 0.145212E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.166229E+12 | 0.143424E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.158421E+12 | 0.177524E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.106334E+12 | 0.107747E+11 | 0.00 | 0.00 |
October | 7410071.37 | 0.00 | 0.592378E+11 | 0.899314E+10 | 0.00 | 0.00 |
November | 0.572466E+09 | 0.00 | 0.211404E+11 | 0.651942E+10 | 0.00 | 0.00 |
December | 0.302191E+10 | 0.00 | 0.144029E+11 | 0.578228E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.926335E+10 | 0.00 | 0.877060E+12 | 0.117312E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.142286E+11 | 0.442607E+10 | 0.00 | 0.00 |
Maximum of Months | 0.302191E+10 | 0.00 | 0.166229E+12 | 0.177524E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.666358E+11 | 0.00 | 0.389778E+11 | 0.283201E+11 | 0.00 | 0.00 |
February | 0.401003E+11 | 0.00 | 0.971860E+11 | 0.301538E+11 | 0.00 | 0.00 |
March | 0.213554E+11 | 0.00 | 0.215336E+12 | 0.433504E+11 | 0.00 | 0.00 |
April | 0.161739E+10 | 0.00 | 0.475894E+12 | 0.610357E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.844993E+12 | 0.906748E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115439E+13 | 0.119988E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.129295E+13 | 0.101186E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.112849E+13 | 0.109040E+12 | 0.00 | 0.00 |
September | 10073541.42 | 0.00 | 0.911260E+12 | 0.831162E+11 | 0.00 | 0.00 |
October | 0.577240E+09 | 0.00 | 0.474743E+12 | 0.562833E+11 | 0.00 | 0.00 |
November | 0.232283E+11 | 0.00 | 0.177075E+12 | 0.349777E+11 | 0.00 | 0.00 |
December | 0.895610E+11 | 0.00 | 0.222774E+11 | 0.276804E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.243085E+12 | 0.00 | 0.683356E+13 | 0.785807E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.222774E+11 | 0.276804E+11 | 0.00 | 0.00 |
Maximum of Months | 0.895610E+11 | 0.00 | 0.129295E+13 | 0.119988E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.160318E+11 | 0.00 | 0.132960E+10 | 0.264852E+10 | 0.00 | 0.00 |
February | 0.910203E+10 | 0.00 | 0.554194E+10 | 0.258098E+10 | 0.00 | 0.00 |
March | 0.506563E+10 | 0.00 | 0.147487E+11 | 0.353428E+10 | 0.00 | 0.00 |
April | 0.596824E+09 | 0.00 | 0.502089E+11 | 0.567183E+10 | 0.00 | 0.00 |
May | 4677375.36 | 0.00 | 0.938672E+11 | 0.925337E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132122E+12 | 0.133846E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.146506E+12 | 0.112231E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.125785E+12 | 0.117637E+11 | 0.00 | 0.00 |
September | 6663217.67 | 0.00 | 0.977019E+11 | 0.827355E+10 | 0.00 | 0.00 |
October | 0.239065E+09 | 0.00 | 0.466181E+11 | 0.501248E+10 | 0.00 | 0.00 |
November | 0.704190E+10 | 0.00 | 0.991722E+10 | 0.297154E+10 | 0.00 | 0.00 |
December | 0.201951E+11 | 0.00 | 0.456439E+09 | 0.264645E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.582837E+11 | 0.00 | 0.724803E+12 | 0.789644E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.456439E+09 | 0.258098E+10 | 0.00 | 0.00 |
Maximum of Months | 0.201951E+11 | 0.00 | 0.146506E+12 | 0.133846E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.113956E+10 | 0.143317E+11 | 0.00 | 0.00 |
February | 83.49 | 0.00 | 0.397658E+10 | 0.125186E+11 | 0.00 | 0.00 |
March | 143.74 | 0.00 | 0.101668E+11 | 0.146840E+11 | 0.00 | 0.00 |
April | 221.67 | 0.00 | 0.315507E+11 | 0.134420E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.550326E+11 | 0.144223E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.707180E+11 | 0.142348E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.860818E+11 | 0.144980E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.847099E+11 | 0.160939E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.668446E+11 | 0.151412E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.370750E+11 | 0.152850E+11 | 0.00 | 0.00 |
November | 111.64 | 0.00 | 0.965938E+10 | 0.143762E+11 | 0.00 | 0.00 |
December | 89.54 | 0.00 | 0.226141E+09 | 0.142536E+11 | 0.00 | 0.00 |
Annual Sum or Average | 650.09 | 0.00 | 0.457181E+12 | 0.173281E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.226141E+09 | 0.125186E+11 | 0.00 | 0.00 |
Maximum of Months | 221.67 | 0.00 | 0.860818E+11 | 0.160939E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.148545E+11 | 0.298601E+12 | 0.00 | 69.06 |
February | 0.00 | 0.00 | 0.354956E+11 | 0.332463E+12 | 0.00 | 83.69 |
March | 0.00 | 0.00 | 0.149398E+12 | 0.405463E+12 | 0.00 | 96.97 |
April | 0.00 | 0.00 | 0.710584E+12 | 0.522968E+12 | 0.00 | 92.14 |
May | 0.00 | 0.00 | 0.239158E+12 | 0.304706E+12 | 0.00 | 50.61 |
June | 0.00 | 0.00 | 0.663230E+12 | 0.311871E+12 | 0.00 | 15.46 |
July | 0.00 | 0.00 | 0.130390E+13 | 0.412586E+12 | 0.00 | 2.11 |
August | 0.00 | 0.00 | 0.143427E+13 | 0.477990E+12 | 0.00 | 17.15 |
September | 0.00 | 0.00 | 0.229310E+12 | 0.191677E+12 | 0.00 | 11.42 |
October | 0.00 | 0.00 | 0.225527E+12 | 0.267171E+12 | 0.00 | 39.52 |
November | 0.00 | 0.00 | 0.101030E+12 | 0.363816E+12 | 0.00 | 87.41 |
December | 0.00 | 0.00 | 0.739128E+11 | 0.394012E+12 | 0.00 | 99.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.518067E+13 | 0.428332E+13 | 0.00 | 665.07 |
Minimum of Months | 0.00 | 0.00 | 0.148545E+11 | 0.191677E+12 | 0.00 | 2.11 |
Maximum of Months | 0.00 | 0.00 | 0.143427E+13 | 0.522968E+12 | 0.00 | 99.53 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.589685E+10 | 0.270887E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112893E+11 | 0.352212E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.190264E+11 | 0.504164E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.253713E+11 | 0.662275E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.795274E+10 | 0.335907E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.146304E+11 | 0.506541E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220744E+11 | 0.690293E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.281722E+11 | 0.810643E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.794921E+10 | 0.326433E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.137980E+11 | 0.425422E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.183922E+11 | 0.478262E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.245322E+11 | 0.578950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199085E+12 | 0.594199E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.589685E+10 | 0.270887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.281722E+11 | 0.810643E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.381435E+11 | 0.225675E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.950583E+11 | 0.314413E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172111E+12 | 0.465951E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238996E+12 | 0.627314E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.734885E+11 | 0.315907E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139212E+12 | 0.482620E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210028E+12 | 0.657375E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.266079E+12 | 0.768870E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.726826E+11 | 0.305289E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125568E+12 | 0.395533E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.162930E+12 | 0.436473E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.214469E+12 | 0.522584E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180877E+13 | 0.551800E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.381435E+11 | 0.225675E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266079E+12 | 0.768870E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.180178E+10 | 0.190621E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.796708E+10 | 0.290783E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.161230E+11 | 0.452320E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.236657E+11 | 0.629029E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.738345E+10 | 0.321069E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141305E+11 | 0.491708E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212657E+11 | 0.668039E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.268220E+11 | 0.779155E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.725478E+10 | 0.309258E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120288E+11 | 0.390759E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.147059E+11 | 0.414671E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.191115E+11 | 0.490188E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172260E+12 | 0.542760E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.180178E+10 | 0.190621E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.268220E+11 | 0.779155E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.442607E+10 | 0.142286E+11 | 0.280842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492295E+10 | 0.155526E+11 | 0.183744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.764436E+10 | 0.264681E+11 | 0.979255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106642E+11 | 0.654378E+11 | 36445715.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109691E+11 | 0.955172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145212E+11 | 0.134090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143424E+11 | 0.166229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177524E+11 | 0.158421E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107747E+11 | 0.106334E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.899314E+10 | 0.592378E+11 | 7410071.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.651942E+10 | 0.211404E+11 | 0.572466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.578228E+10 | 0.144029E+11 | 0.302191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117312E+12 | 0.877060E+12 | 0.926335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.442607E+10 | 0.142286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177524E+11 | 0.166229E+12 | 0.302191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.283201E+11 | 0.389778E+11 | 0.666358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301538E+11 | 0.971860E+11 | 0.401003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433504E+11 | 0.215336E+12 | 0.213554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.610357E+11 | 0.475894E+12 | 0.161739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.906748E+11 | 0.844993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119988E+12 | 0.115439E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101186E+12 | 0.129295E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109040E+12 | 0.112849E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.831162E+11 | 0.911260E+12 | 10073541.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.562833E+11 | 0.474743E+12 | 0.577240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349777E+11 | 0.177075E+12 | 0.232283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276804E+11 | 0.222774E+11 | 0.895610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785807E+12 | 0.683356E+13 | 0.243085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276804E+11 | 0.222774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119988E+12 | 0.129295E+13 | 0.895610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.264852E+10 | 0.132960E+10 | 0.160318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258098E+10 | 0.554194E+10 | 0.910203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353428E+10 | 0.147487E+11 | 0.506563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.567183E+10 | 0.502089E+11 | 0.596824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.925337E+10 | 0.938672E+11 | 4677375.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133846E+11 | 0.132122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112231E+11 | 0.146506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117637E+11 | 0.125785E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.827355E+10 | 0.977019E+11 | 6663217.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.501248E+10 | 0.466181E+11 | 0.239065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297154E+10 | 0.991722E+10 | 0.704190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264645E+10 | 0.456439E+09 | 0.201951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789644E+11 | 0.724803E+12 | 0.582837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258098E+10 | 0.456439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133846E+11 | 0.146506E+12 | 0.201951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143317E+11 | 0.113956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125186E+11 | 0.397658E+10 | 83.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146840E+11 | 0.101668E+11 | 143.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134420E+11 | 0.315507E+11 | 221.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144223E+11 | 0.550326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142348E+11 | 0.707180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144980E+11 | 0.860818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160939E+11 | 0.847099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151412E+11 | 0.668446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152850E+11 | 0.370750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143762E+11 | 0.965938E+10 | 111.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142536E+11 | 0.226141E+09 | 89.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173281E+12 | 0.457181E+12 | 650.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125186E+11 | 0.226141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160939E+11 | 0.860818E+11 | 221.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108189E+12 | 0.100974E+11 | 0.00 | 0.00 | 0.00 | 0.184823E+12 | 0.00 | 0.00 |
February | 0.977195E+11 | 0.257215E+11 | 0.00 | 0.00 | 0.00 | 0.223961E+12 | 0.00 | 0.00 |
March | 0.108189E+12 | 0.112791E+12 | 0.00 | 0.00 | 0.00 | 0.259500E+12 | 0.00 | 0.00 |
April | 0.104699E+12 | 0.540006E+12 | 0.00 | 0.00 | 0.00 | 0.246582E+12 | 0.00 | 0.00 |
May | 0.108189E+12 | 0.178689E+12 | 0.00 | 0.00 | 0.00 | 0.135438E+12 | 0.00 | 0.00 |
June | 0.104699E+12 | 0.497609E+12 | 0.00 | 0.00 | 0.00 | 0.413646E+11 | 0.00 | 0.00 |
July | 0.108189E+12 | 0.100517E+13 | 0.00 | 0.00 | 0.00 | 0.563673E+10 | 0.00 | 0.00 |
August | 0.108189E+12 | 0.111058E+13 | 0.00 | 0.00 | 0.00 | 0.459080E+11 | 0.00 | 0.00 |
September | 0.104699E+12 | 0.173029E+12 | 0.00 | 0.00 | 0.00 | 0.305583E+11 | 0.00 | 0.00 |
October | 0.108189E+12 | 0.172793E+12 | 0.00 | 0.00 | 0.00 | 0.105772E+12 | 0.00 | 0.00 |
November | 0.104699E+12 | 0.768754E+11 | 0.00 | 0.00 | 0.00 | 0.233909E+12 | 0.00 | 0.00 |
December | 0.108189E+12 | 0.556462E+11 | 0.00 | 0.00 | 0.00 | 0.266357E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.127384E+13 | 0.395901E+13 | 0.00 | 0.00 | 0.00 | 0.177981E+13 | 0.00 | 0.00 |
Minimum of Months | 0.977195E+11 | 0.100974E+11 | 0.00 | 0.00 | 0.00 | 0.563673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108189E+12 | 0.111058E+13 | 0.00 | 0.00 | 0.00 | 0.266357E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157868E+10 | 0.476666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142591E+10 | 0.919311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157868E+10 | 0.155634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152776E+10 | 0.202763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157868E+10 | 0.617236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152776E+10 | 0.110927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157868E+10 | 0.167502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157868E+10 | 0.216445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152776E+10 | 0.621264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157868E+10 | 0.111225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152776E+10 | 0.151373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157868E+10 | 0.203213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185877E+11 | 0.158253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142591E+10 | 0.476666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157868E+10 | 0.216445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150655E+11 | 0.306414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136075E+11 | 0.772245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150655E+11 | 0.140582E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145795E+11 | 0.190844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150655E+11 | 0.569633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145795E+11 | 0.105529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150655E+11 | 0.159356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150655E+11 | 0.204257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145795E+11 | 0.567332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150655E+11 | 0.101080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145795E+11 | 0.133862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150655E+11 | 0.177276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177384E+12 | 0.143435E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136075E+11 | 0.306414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150655E+11 | 0.204257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154079E+10 | 0.143635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139168E+10 | 0.645093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154079E+10 | 0.131406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149109E+10 | 0.188665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154079E+10 | 0.571355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149109E+10 | 0.107045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154079E+10 | 0.161261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154079E+10 | 0.205712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149109E+10 | 0.565328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154079E+10 | 0.966198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149109E+10 | 0.120503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154079E+10 | 0.157504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181415E+11 | 0.136126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139168E+10 | 0.143635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154079E+10 | 0.205712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.442607E+10 | 0.280842E+10 | 0.142286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492295E+10 | 0.183744E+10 | 0.155526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.764436E+10 | 0.979255E+09 | 0.264681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106642E+11 | 36445715.51 | 0.654378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109691E+11 | 0.00 | 0.955172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145212E+11 | 0.00 | 0.134090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143424E+11 | 0.00 | 0.166229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177524E+11 | 0.00 | 0.158421E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107747E+11 | 0.00 | 0.106334E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.899314E+10 | 7410071.37 | 0.592378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.651942E+10 | 0.572466E+09 | 0.211404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.578228E+10 | 0.302191E+10 | 0.144029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117312E+12 | 0.926335E+10 | 0.877060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.442607E+10 | 0.00 | 0.142286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177524E+11 | 0.302191E+10 | 0.166229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.283201E+11 | 0.666358E+11 | 0.389778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301538E+11 | 0.401003E+11 | 0.971860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433504E+11 | 0.213554E+11 | 0.215336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.610357E+11 | 0.161739E+10 | 0.475894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.906748E+11 | 0.00 | 0.844993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119988E+12 | 0.00 | 0.115439E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101186E+12 | 0.00 | 0.129295E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109040E+12 | 0.00 | 0.112849E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.831162E+11 | 10073541.42 | 0.911260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.562833E+11 | 0.577240E+09 | 0.474743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349777E+11 | 0.232283E+11 | 0.177075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276804E+11 | 0.895610E+11 | 0.222774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785807E+12 | 0.243085E+12 | 0.683356E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276804E+11 | 0.00 | 0.222774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119988E+12 | 0.895610E+11 | 0.129295E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.264852E+10 | 0.160318E+11 | 0.132960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258098E+10 | 0.910203E+10 | 0.554194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353428E+10 | 0.506563E+10 | 0.147487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.567183E+10 | 0.596824E+09 | 0.502089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.925337E+10 | 4677375.36 | 0.938672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133846E+11 | 0.00 | 0.132122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112231E+11 | 0.00 | 0.146506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117637E+11 | 0.00 | 0.125785E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.827355E+10 | 6663217.67 | 0.977019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.501248E+10 | 0.239065E+09 | 0.466181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297154E+10 | 0.704190E+10 | 0.991722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264645E+10 | 0.201951E+11 | 0.456439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789644E+11 | 0.582837E+11 | 0.724803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258098E+10 | 0.00 | 0.456439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133846E+11 | 0.201951E+11 | 0.146506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143317E+11 | 0.00 | 0.113956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125186E+11 | 83.49 | 0.397658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146840E+11 | 143.74 | 0.101668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134420E+11 | 221.67 | 0.315507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144223E+11 | 0.00 | 0.550326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142348E+11 | 0.00 | 0.707180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144980E+11 | 0.00 | 0.860818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160939E+11 | 0.00 | 0.847099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151412E+11 | 0.00 | 0.668446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152850E+11 | 0.00 | 0.370750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143762E+11 | 111.64 | 0.965938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142536E+11 | 89.54 | 0.226141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173281E+12 | 650.09 | 0.457181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125186E+11 | 0.00 | 0.226141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160939E+11 | 221.67 | 0.860818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108189E+12 | 0.00 | 0.148545E+11 | 0.00 | 0.475704E+10 | 0.00 | 0.00 | 0.00 | 0.185655E+12 | 0.00 | 0.00 | 0.00 |
February | 0.977195E+11 | 0.00 | 0.354956E+11 | 0.00 | 0.977409E+10 | 0.00 | 0.00 | 0.00 | 0.224969E+12 | 0.00 | 0.00 | 0.00 |
March | 0.108189E+12 | 0.00 | 0.149398E+12 | 0.00 | 0.366062E+11 | 0.00 | 0.00 | 0.00 | 0.260668E+12 | 0.00 | 0.00 | 0.00 |
April | 0.104699E+12 | 0.00 | 0.710584E+12 | 0.00 | 0.170577E+12 | 0.00 | 0.00 | 0.00 | 0.247692E+12 | 0.00 | 0.00 | 0.00 |
May | 0.108189E+12 | 0.00 | 0.239158E+12 | 0.00 | 0.604691E+11 | 0.00 | 0.00 | 0.00 | 0.136048E+12 | 0.00 | 0.00 | 0.00 |
June | 0.104699E+12 | 0.00 | 0.663230E+12 | 0.00 | 0.165621E+12 | 0.00 | 0.00 | 0.00 | 0.415508E+11 | 0.00 | 0.00 | 0.00 |
July | 0.108189E+12 | 0.00 | 0.130390E+13 | 0.00 | 0.298734E+12 | 0.00 | 0.00 | 0.00 | 0.566210E+10 | 0.00 | 0.00 | 0.00 |
August | 0.108189E+12 | 0.00 | 0.143427E+13 | 0.00 | 0.323686E+12 | 0.00 | 0.00 | 0.00 | 0.461146E+11 | 0.00 | 0.00 | 0.00 |
September | 0.104699E+12 | 0.00 | 0.229310E+12 | 0.00 | 0.562813E+11 | 0.00 | 0.00 | 0.00 | 0.306958E+11 | 0.00 | 0.00 | 0.00 |
October | 0.108189E+12 | 0.00 | 0.225527E+12 | 0.00 | 0.527341E+11 | 0.00 | 0.00 | 0.00 | 0.106248E+12 | 0.00 | 0.00 | 0.00 |
November | 0.104699E+12 | 0.00 | 0.101030E+12 | 0.00 | 0.241547E+11 | 0.00 | 0.00 | 0.00 | 0.234962E+12 | 0.00 | 0.00 | 0.00 |
December | 0.108189E+12 | 0.00 | 0.739128E+11 | 0.00 | 0.182666E+11 | 0.00 | 0.00 | 0.00 | 0.267556E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127384E+13 | 0.00 | 0.518067E+13 | 0.00 | 0.122166E+13 | 0.00 | 0.00 | 0.00 | 0.178782E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.977195E+11 | 0.00 | 0.148545E+11 | 0.00 | 0.475704E+10 | 0.00 | 0.00 | 0.00 | 0.566210E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108189E+12 | 0.00 | 0.143427E+13 | 0.00 | 0.323686E+12 | 0.00 | 0.00 | 0.00 | 0.267556E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157868E+10 | 0.00 | 0.589685E+10 | 0.00 | 0.113019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142591E+10 | 0.00 | 0.112893E+11 | 0.00 | 0.209621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157868E+10 | 0.00 | 0.190264E+11 | 0.00 | 0.346295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152776E+10 | 0.00 | 0.253713E+11 | 0.00 | 0.509499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157868E+10 | 0.00 | 0.795274E+10 | 0.00 | 0.178038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152776E+10 | 0.00 | 0.146304E+11 | 0.00 | 0.353766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157868E+10 | 0.00 | 0.220744E+11 | 0.00 | 0.532424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157868E+10 | 0.00 | 0.281722E+11 | 0.00 | 0.652775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152776E+10 | 0.00 | 0.794921E+10 | 0.00 | 0.173657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157868E+10 | 0.00 | 0.137980E+11 | 0.00 | 0.267554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152776E+10 | 0.00 | 0.183922E+11 | 0.00 | 0.325486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157868E+10 | 0.00 | 0.245322E+11 | 0.00 | 0.421082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185877E+11 | 0.00 | 0.199085E+12 | 0.00 | 0.408322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142591E+10 | 0.00 | 0.589685E+10 | 0.00 | 0.113019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157868E+10 | 0.00 | 0.281722E+11 | 0.00 | 0.652775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150655E+11 | 0.00 | 0.381435E+11 | 0.00 | 0.750209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136075E+11 | 0.00 | 0.950583E+11 | 0.00 | 0.178338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150655E+11 | 0.00 | 0.172111E+12 | 0.00 | 0.315296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145795E+11 | 0.00 | 0.238996E+12 | 0.00 | 0.481520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150655E+11 | 0.00 | 0.734885E+11 | 0.00 | 0.165252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145795E+11 | 0.00 | 0.139212E+12 | 0.00 | 0.336826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150655E+11 | 0.00 | 0.210028E+12 | 0.00 | 0.506721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150655E+11 | 0.00 | 0.266079E+12 | 0.00 | 0.618215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145795E+11 | 0.00 | 0.726826E+11 | 0.00 | 0.159494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150655E+11 | 0.00 | 0.125568E+12 | 0.00 | 0.244878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145795E+11 | 0.00 | 0.162930E+12 | 0.00 | 0.290679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150655E+11 | 0.00 | 0.214469E+12 | 0.00 | 0.371930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177384E+12 | 0.00 | 0.180877E+13 | 0.00 | 0.374417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136075E+11 | 0.00 | 0.381435E+11 | 0.00 | 0.750209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150655E+11 | 0.00 | 0.266079E+12 | 0.00 | 0.618215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154079E+10 | 0.00 | 0.180178E+10 | 0.00 | 0.365422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139168E+10 | 0.00 | 0.796708E+10 | 0.00 | 0.151615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154079E+10 | 0.00 | 0.161230E+11 | 0.00 | 0.298241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149109E+10 | 0.00 | 0.236657E+11 | 0.00 | 0.479921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154079E+10 | 0.00 | 0.738345E+10 | 0.00 | 0.166990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149109E+10 | 0.00 | 0.141305E+11 | 0.00 | 0.342599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154079E+10 | 0.00 | 0.212657E+11 | 0.00 | 0.513960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154079E+10 | 0.00 | 0.268220E+11 | 0.00 | 0.625077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149109E+10 | 0.00 | 0.725478E+10 | 0.00 | 0.160150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154079E+10 | 0.00 | 0.120288E+11 | 0.00 | 0.236680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149109E+10 | 0.00 | 0.147059E+11 | 0.00 | 0.265563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154079E+10 | 0.00 | 0.191115E+11 | 0.00 | 0.336109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181415E+11 | 0.00 | 0.172260E+12 | 0.00 | 0.361345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139168E+10 | 0.00 | 0.180178E+10 | 0.00 | 0.365422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154079E+10 | 0.00 | 0.268220E+11 | 0.00 | 0.625077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.386415E+09 | 0.00 | 0.00 | 0.112241E+09 | 0.00 | 0.00 | 0.638467E+11 | 0.00 | 0.85 |
February | 0.185327E+09 | 0.00 | 0.00 | 92014349.54 | 0.00 | 0.00 | 0.525932E+11 | 0.00 | 0.94 |
March | 0.136902E+09 | 0.00 | 0.00 | 0.102089E+09 | 0.00 | 0.00 | 0.561117E+11 | 0.00 | 1.17 |
April | 35478882.95 | 0.533126E+09 | 0.00 | 89530025.25 | 31655022.15 | 0.00 | 0.327971E+11 | 0.00 | 1.03 |
May | 68016722.19 | 0.190614E+10 | 0.00 | 67460155.31 | 87685927.33 | 0.00 | 0.155798E+11 | 0.00 | 0.83 |
June | 13278450.35 | 0.635994E+10 | 0.00 | 46125106.38 | 0.118177E+09 | 0.00 | 0.576489E+10 | 0.00 | 0.65 |
July | 91456847.21 | 0.142201E+11 | 0.00 | 18447343.77 | 0.106551E+09 | 0.00 | 0.144005E+10 | 0.00 | 0.66 |
August | 23883539.89 | 0.643264E+10 | 0.00 | 61767964.35 | 84206135.12 | 0.00 | 0.713717E+10 | 0.00 | 0.84 |
September | 0.134542E+09 | 0.326439E+10 | 0.00 | 75439676.24 | 38837832.82 | 0.00 | 0.136108E+11 | 0.00 | 0.89 |
October | 0.188911E+09 | 0.652975E+09 | 0.00 | 0.117966E+09 | 2730965.87 | 0.00 | 0.427650E+11 | 0.00 | 1.32 |
November | 0.356253E+09 | 0.00 | 0.00 | 0.126346E+09 | 0.00 | 0.00 | 0.642299E+11 | 0.00 | 1.20 |
December | 0.445819E+09 | 0.00 | 0.00 | 0.124419E+09 | 0.00 | 0.00 | 0.695562E+11 | 0.00 | 0.85 |
Annual Sum or Average | 0.206628E+10 | 0.333693E+11 | 0.00 | 0.103385E+10 | 0.469844E+09 | 0.00 | 0.425433E+12 | 0.00 | 0.94 |
Minimum of Months | 13278450.35 | 0.00 | 0.00 | 18447343.77 | 0.00 | 0.00 | 0.144005E+10 | 0.00 | 0.65 |
Maximum of Months | 0.445819E+09 | 0.142201E+11 | 0.00 | 0.126346E+09 | 0.118177E+09 | 0.00 | 0.695562E+11 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159408E+10 | 0.00 | 0.00 | 76420738.51 | 0.00 | 0.00 | 0.362423E+11 | 0.00 | 0.44 |
February | 0.175052E+10 | 0.00 | 0.00 | 75773461.06 | 0.00 | 0.00 | 0.357944E+11 | 0.00 | 0.62 |
March | 0.236977E+10 | 0.00 | 0.00 | 96100761.51 | 0.00 | 0.00 | 0.431555E+11 | 0.00 | 0.86 |
April | 0.474373E+10 | 0.282231E+09 | 0.00 | 86432113.76 | 98252772.78 | 0.00 | 0.276376E+11 | 0.00 | 0.91 |
May | 0.151980E+10 | 0.106678E+10 | 0.00 | 62290474.62 | 0.199627E+09 | 0.00 | 0.118888E+11 | 0.00 | 0.61 |
June | 0.152388E+10 | 0.362144E+10 | 0.00 | 43149722.88 | 0.266490E+09 | 0.00 | 0.408867E+10 | 0.00 | 0.53 |
July | 0.403824E+09 | 0.125389E+11 | 0.00 | 8296694.85 | 0.245820E+10 | 0.00 | 0.503711E+09 | 0.00 | 0.56 |
August | 0.199864E+10 | 0.527442E+10 | 0.00 | 53418940.97 | 0.781885E+09 | 0.00 | 0.526508E+10 | 0.00 | 0.76 |
September | 0.124224E+10 | 0.291973E+10 | 0.00 | 55702141.23 | 0.221202E+09 | 0.00 | 0.816436E+10 | 0.00 | 0.62 |
October | 0.201467E+10 | 0.727719E+09 | 0.00 | 87636470.23 | 22192774.43 | 0.00 | 0.301864E+11 | 0.00 | 0.88 |
November | 0.272436E+10 | 0.00 | 0.00 | 95421270.81 | 0.00 | 0.00 | 0.429013E+11 | 0.00 | 0.78 |
December | 0.225835E+10 | 0.00 | 0.00 | 94449244.05 | 0.00 | 0.00 | 0.443992E+11 | 0.00 | 0.52 |
Annual Sum or Average | 0.241439E+11 | 0.264312E+11 | 0.00 | 0.835092E+09 | 0.404785E+10 | 0.00 | 0.290227E+12 | 0.00 | 0.67 |
Minimum of Months | 0.403824E+09 | 0.00 | 0.00 | 8296694.85 | 0.00 | 0.00 | 0.503711E+09 | 0.00 | 0.44 |
Maximum of Months | 0.474373E+10 | 0.125389E+11 | 0.00 | 96100761.51 | 0.245820E+10 | 0.00 | 0.443992E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118420E+12 | 0.00 | 0.00 | 0.292959E+09 | 0.00 | 0.00 | 0.190142E+12 | 0.00 | 0.37 |
February | 0.761386E+11 | 0.00 | 0.00 | 0.339530E+09 | 0.00 | 0.00 | 0.199248E+12 | 0.00 | 0.44 |
March | 0.447831E+11 | 0.00 | 0.00 | 0.533574E+09 | 0.00 | 0.00 | 0.251893E+12 | 0.00 | 0.54 |
April | 0.137646E+11 | 0.286878E+10 | 0.00 | 0.599159E+09 | 0.494737E+09 | 0.00 | 0.188221E+12 | 0.00 | 0.59 |
May | 0.112250E+11 | 0.110487E+11 | 0.00 | 0.507812E+09 | 0.131134E+10 | 0.00 | 0.958213E+11 | 0.00 | 0.53 |
June | 0.513045E+10 | 0.366826E+11 | 0.00 | 0.364701E+09 | 0.195036E+10 | 0.00 | 0.360881E+11 | 0.00 | 0.43 |
July | 0.107510E+10 | 0.108468E+12 | 0.00 | 54409103.81 | 0.497292E+10 | 0.00 | 0.384198E+10 | 0.00 | 0.40 |
August | 0.232492E+10 | 0.416345E+11 | 0.00 | 0.377523E+09 | 0.245752E+10 | 0.00 | 0.439872E+11 | 0.00 | 0.50 |
September | 0.882514E+10 | 0.270498E+11 | 0.00 | 0.436146E+09 | 0.147695E+10 | 0.00 | 0.625245E+11 | 0.00 | 0.51 |
October | 0.157210E+11 | 0.629783E+10 | 0.00 | 0.599473E+09 | 0.331947E+09 | 0.00 | 0.206106E+12 | 0.00 | 0.63 |
November | 0.533343E+11 | 0.00 | 0.00 | 0.454089E+09 | 0.00 | 0.00 | 0.220194E+12 | 0.00 | 0.45 |
December | 0.132940E+12 | 0.00 | 0.00 | 0.266513E+09 | 0.00 | 0.00 | 0.190890E+12 | 0.00 | 0.37 |
Annual Sum or Average | 0.483683E+12 | 0.234050E+12 | 0.00 | 0.482589E+10 | 0.129958E+11 | 0.00 | 0.168896E+13 | 0.00 | 0.48 |
Minimum of Months | 0.107510E+10 | 0.00 | 0.00 | 54409103.81 | 0.00 | 0.00 | 0.384198E+10 | 0.00 | 0.37 |
Maximum of Months | 0.132940E+12 | 0.108468E+12 | 0.00 | 0.599473E+09 | 0.497292E+10 | 0.00 | 0.251893E+12 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197993E+11 | 0.00 | 0.00 | 4134372.54 | 0.00 | 0.700136E+09 | 0.416164E+10 | 0.00 | 0.33 |
February | 0.148241E+11 | 0.00 | 0.00 | 10302347.45 | 0.00 | 46685610.74 | 0.754806E+10 | 0.00 | 0.40 |
March | 0.110779E+11 | 0.00 | 0.00 | 25920245.00 | 0.00 | 5844774.36 | 0.150145E+11 | 0.00 | 0.52 |
April | 0.297326E+10 | 0.145829E+09 | 0.00 | 48803418.54 | 53825281.98 | 0.00 | 0.144781E+11 | 0.00 | 0.57 |
May | 0.128209E+10 | 0.748513E+09 | 0.00 | 51426570.35 | 0.144909E+09 | 0.00 | 0.795819E+10 | 0.00 | 0.51 |
June | 0.593122E+09 | 0.305092E+10 | 0.00 | 43122581.75 | 0.183537E+09 | 0.00 | 0.332552E+10 | 0.00 | 0.44 |
July | 0.134509E+09 | 0.105052E+11 | 0.00 | 7055949.95 | 0.564574E+09 | 0.00 | 0.335902E+09 | 0.00 | 0.41 |
August | 0.243703E+09 | 0.364745E+10 | 0.00 | 42959549.96 | 0.239904E+09 | 0.00 | 0.417486E+10 | 0.00 | 0.50 |
September | 0.111359E+10 | 0.218097E+10 | 0.00 | 42293030.65 | 0.139362E+09 | 0.00 | 0.447159E+10 | 0.00 | 0.48 |
October | 0.418736E+10 | 0.503954E+09 | 0.00 | 40897813.70 | 40302495.85 | 0.00 | 0.142254E+11 | 0.00 | 0.58 |
November | 0.133512E+11 | 0.00 | 0.00 | 16527439.69 | 0.00 | 0.237206E+09 | 0.957474E+10 | 0.00 | 0.44 |
December | 0.214049E+11 | 0.00 | 0.00 | 2597859.73 | 0.00 | 0.990340E+09 | 0.278265E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.909851E+11 | 0.207828E+11 | 0.00 | 0.336041E+09 | 0.136641E+10 | 0.198021E+10 | 0.880511E+11 | 0.00 | 0.46 |
Minimum of Months | 0.134509E+09 | 0.00 | 0.00 | 2597859.73 | 0.00 | 0.00 | 0.335902E+09 | 0.00 | 0.32 |
Maximum of Months | 0.214049E+11 | 0.105052E+11 | 0.00 | 51426570.35 | 0.564574E+09 | 0.990340E+09 | 0.150145E+11 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245521E+10 | 0.00 | 0.00 | 1022576.87 | 0.00 | 31011404.31 | 0.611105E+09 | 0.00 | 0.29 |
February | 0.186516E+10 | 0.00 | 0.00 | 2261312.55 | 0.00 | 406267.12 | 0.121559E+10 | 0.00 | 0.43 |
March | 0.146593E+10 | 0.00 | 0.00 | 5316317.88 | 0.00 | 0.00 | 0.249600E+10 | 0.00 | 0.66 |
April | 0.883433E+09 | 54745354.89 | 0.00 | 8573736.44 | 12368075.46 | 0.00 | 0.244972E+10 | 0.00 | 0.85 |
May | 0.285840E+09 | 0.233170E+09 | 0.00 | 8066479.25 | 25319344.53 | 0.00 | 0.134392E+10 | 0.00 | 0.72 |
June | 0.208401E+09 | 0.859464E+09 | 0.00 | 6973460.41 | 31266214.63 | 0.00 | 0.604849E+09 | 0.00 | 0.75 |
July | 49510667.08 | 0.238571E+10 | 0.00 | 1250945.93 | 0.308461E+09 | 0.00 | 76029914.56 | 0.00 | 0.75 |
August | 0.270174E+09 | 0.952396E+09 | 0.00 | 7393902.62 | 95583563.83 | 0.00 | 0.660978E+09 | 0.00 | 0.90 |
September | 0.239183E+09 | 0.502095E+09 | 0.00 | 5944726.95 | 28225441.34 | 0.00 | 0.736942E+09 | 0.00 | 0.65 |
October | 0.691395E+09 | 0.118573E+09 | 0.00 | 7123949.53 | 2585361.03 | 0.00 | 0.231046E+10 | 0.00 | 0.75 |
November | 0.163647E+10 | 0.00 | 0.00 | 3886028.77 | 0.00 | 0.00 | 0.189073E+10 | 0.00 | 0.51 |
December | 0.244784E+10 | 0.00 | 0.00 | 1273551.90 | 0.00 | 0.00 | 0.868557E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.124985E+11 | 0.510615E+10 | 0.00 | 59086989.11 | 0.503809E+09 | 31417671.43 | 0.152649E+11 | 0.00 | 0.63 |
Minimum of Months | 49510667.08 | 0.00 | 0.00 | 1022576.87 | 0.00 | 0.00 | 76029914.56 | 0.00 | 0.29 |
Maximum of Months | 0.245521E+10 | 0.238571E+10 | 0.00 | 8573736.44 | 0.308461E+09 | 31011404.31 | 0.249600E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118006E+10 | 0.00 | 0.00 | 3206545.99 | 0.00 | 17768454.74 | 0.139224E+10 | 0.00 | 0.37 |
February | 0.809586E+09 | 0.00 | 0.00 | 4574251.93 | 0.00 | 17371877.57 | 0.218554E+10 | 0.00 | 0.61 |
March | 0.717974E+09 | 0.00 | 0.00 | 7804016.63 | 0.00 | 654578.83 | 0.353073E+10 | 0.00 | 1.00 |
April | 0.516664E+09 | 42984478.40 | 0.00 | 11103550.42 | 7360268.97 | 0.00 | 0.338886E+10 | 0.00 | 1.40 |
May | 0.140356E+09 | 0.198996E+09 | 0.00 | 10658443.05 | 15396231.59 | 0.00 | 0.201131E+10 | 0.00 | 1.30 |
June | 0.125558E+09 | 0.668669E+09 | 0.00 | 7914804.32 | 21109600.38 | 0.00 | 0.631685E+09 | 0.00 | 1.08 |
July | 34084577.52 | 0.197587E+10 | 0.00 | 1226334.37 | 0.195048E+09 | 0.00 | 64930653.23 | 0.00 | 0.97 |
August | 0.171743E+09 | 0.790494E+09 | 0.00 | 6172747.85 | 66416831.08 | 0.00 | 0.603732E+09 | 0.00 | 1.15 |
September | 0.124247E+09 | 0.517864E+09 | 0.00 | 7937446.19 | 15066023.30 | 0.00 | 0.110614E+10 | 0.00 | 1.15 |
October | 0.413935E+09 | 87933172.84 | 0.00 | 8364840.83 | 1445351.02 | 0.00 | 0.271022E+10 | 0.00 | 1.12 |
November | 0.880065E+09 | 0.00 | 0.00 | 5400183.67 | 0.00 | 0.00 | 0.241398E+10 | 0.00 | 0.72 |
December | 0.126864E+10 | 0.00 | 0.00 | 2777418.57 | 0.00 | 10712285.89 | 0.132108E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.638291E+10 | 0.428281E+10 | 0.00 | 77140583.82 | 0.321842E+09 | 46507197.03 | 0.213604E+11 | 0.00 | 0.94 |
Minimum of Months | 34084577.52 | 0.00 | 0.00 | 1226334.37 | 0.00 | 0.00 | 64930653.23 | 0.00 | 0.36 |
Maximum of Months | 0.126864E+10 | 0.197587E+10 | 0.00 | 11103550.42 | 0.195048E+09 | 17768454.74 | 0.353073E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133739E+10 | 0.00 | 0.00 | 14404592.89 | 0.00 | 24263522.16 | 0.595885E+10 | 0.00 | 0.72 |
February | 0.109216E+10 | 0.00 | 0.00 | 14820630.34 | 0.00 | 4711148.94 | 0.569872E+10 | 0.00 | 1.00 |
March | 0.105037E+10 | 0.00 | 0.00 | 14854205.94 | 0.00 | 0.00 | 0.630653E+10 | 0.00 | 1.28 |
April | 0.884856E+09 | 90255814.73 | 0.00 | 12503169.61 | 12267208.85 | 0.00 | 0.336550E+10 | 0.00 | 1.12 |
May | 0.337679E+09 | 0.270715E+09 | 0.00 | 8430703.15 | 25385730.13 | 0.00 | 0.128693E+10 | 0.00 | 0.75 |
June | 0.210493E+09 | 0.861059E+09 | 0.00 | 6494398.00 | 33012096.79 | 0.00 | 0.537117E+09 | 0.00 | 0.72 |
July | 49152642.72 | 0.239197E+10 | 0.00 | 1196442.32 | 0.310184E+09 | 0.00 | 67876541.42 | 0.00 | 0.74 |
August | 0.267914E+09 | 0.112657E+10 | 0.00 | 8431968.79 | 94510662.15 | 0.00 | 0.695078E+09 | 0.00 | 0.98 |
September | 0.171759E+09 | 0.831028E+09 | 0.00 | 11578466.19 | 24268351.18 | 0.00 | 0.115475E+10 | 0.00 | 0.94 |
October | 0.485167E+09 | 0.216437E+09 | 0.00 | 21751272.52 | 977153.34 | 0.00 | 0.520658E+10 | 0.00 | 1.51 |
November | 0.850823E+09 | 0.00 | 0.00 | 22317134.13 | 0.00 | 1061621.34 | 0.789016E+10 | 0.00 | 1.38 |
December | 0.140022E+10 | 0.00 | 0.00 | 14903988.57 | 0.00 | 19574949.57 | 0.654586E+10 | 0.00 | 0.77 |
Annual Sum or Average | 0.813798E+10 | 0.578804E+10 | 0.00 | 0.151687E+09 | 0.500605E+09 | 49611242.01 | 0.447139E+11 | 0.00 | 0.99 |
Minimum of Months | 49152642.72 | 0.00 | 0.00 | 1196442.32 | 0.00 | 0.00 | 67876541.42 | 0.00 | 0.72 |
Maximum of Months | 0.140022E+10 | 0.239197E+10 | 0.00 | 22317134.13 | 0.310184E+09 | 24263522.16 | 0.789016E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.843163E+09 | 0.00 | 0.00 | 5419568.72 | 0.00 | 0.00 | 0.255987E+10 | 0.00 | 0.54 |
February | 0.369859E+09 | 0.00 | 0.00 | 8780981.28 | 0.00 | 0.00 | 0.372691E+10 | 0.00 | 0.96 |
March | 0.187470E+09 | 0.00 | 0.00 | 16256375.40 | 0.00 | 0.00 | 0.662281E+10 | 0.00 | 1.86 |
April | 0.145905E+09 | 0.114335E+09 | 0.00 | 20049767.02 | 436100.00 | 0.00 | 0.531110E+10 | 0.00 | 2.11 |
May | 94803208.68 | 0.328073E+09 | 0.00 | 10254683.68 | 6707331.47 | 0.00 | 0.166777E+10 | 0.00 | 1.28 |
June | 68473040.52 | 0.110673E+10 | 0.00 | 8896990.79 | 6260861.60 | 0.00 | 0.773173E+09 | 0.00 | 1.28 |
July | 6995467.97 | 0.315628E+10 | 0.00 | 2620873.20 | 36191708.00 | 0.00 | 0.130932E+09 | 0.00 | 1.32 |
August | 20120752.93 | 0.144834E+10 | 0.00 | 13700478.66 | 5389718.30 | 0.00 | 0.118415E+10 | 0.00 | 1.87 |
September | 57207072.47 | 0.616922E+09 | 0.00 | 9062647.63 | 11265050.95 | 0.00 | 0.111222E+10 | 0.00 | 1.19 |
October | 0.103943E+09 | 0.164206E+09 | 0.00 | 14663941.54 | 434978.81 | 0.00 | 0.423645E+10 | 0.00 | 1.72 |
November | 0.198895E+09 | 0.00 | 0.00 | 13828524.15 | 0.00 | 0.00 | 0.580972E+10 | 0.00 | 1.46 |
December | 0.252903E+09 | 0.00 | 0.00 | 10689482.84 | 0.00 | 0.00 | 0.524446E+10 | 0.00 | 0.83 |
Annual Sum or Average | 0.234974E+10 | 0.693488E+10 | 0.00 | 0.134224E+09 | 66685749.12 | 0.00 | 0.383796E+11 | 0.00 | 1.37 |
Minimum of Months | 6995467.97 | 0.00 | 0.00 | 2620873.20 | 0.00 | 0.00 | 0.130932E+09 | 0.00 | 0.54 |
Maximum of Months | 0.843163E+09 | 0.315628E+10 | 0.00 | 20049767.02 | 36191708.00 | 0.00 | 0.662281E+10 | 0.00 | 2.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.260398E+11 | 0.00 | 0.00 | 5826.19 | 0.00 | 0.806634E+10 | 19060879.69 | 0.00 | 0.32 |
February | 0.223765E+11 | 0.00 | 0.00 | 2378508.43 | 0.00 | 0.447940E+10 | 0.102176E+10 | 0.00 | 0.35 |
March | 0.215094E+11 | 0.00 | 0.00 | 15560864.31 | 0.00 | 0.196058E+10 | 0.549278E+10 | 0.00 | 0.43 |
April | 0.937309E+10 | 0.564084E+09 | 0.00 | 47563923.32 | 57931777.06 | 21921196.23 | 0.105131E+11 | 0.00 | 0.53 |
May | 0.314766E+10 | 0.266315E+10 | 0.00 | 62926583.52 | 0.165441E+09 | 0.00 | 0.937490E+10 | 0.00 | 0.63 |
June | 0.876170E+09 | 0.984238E+10 | 0.00 | 59594050.44 | 0.229688E+09 | 0.00 | 0.524349E+10 | 0.00 | 0.69 |
July | 0.144354E+09 | 0.228123E+11 | 0.00 | 8122458.92 | 0.645420E+09 | 0.00 | 0.567405E+09 | 0.00 | 0.62 |
August | 0.657789E+09 | 0.834493E+10 | 0.00 | 52391852.74 | 0.323772E+09 | 0.00 | 0.510294E+10 | 0.00 | 0.64 |
September | 0.261444E+10 | 0.484512E+10 | 0.00 | 42040790.51 | 0.203183E+09 | 0.00 | 0.455330E+10 | 0.00 | 0.53 |
October | 0.114538E+11 | 0.107622E+10 | 0.00 | 35122304.30 | 38351719.83 | 0.00 | 0.933810E+10 | 0.00 | 0.52 |
November | 0.227507E+11 | 0.00 | 0.00 | 5170293.48 | 0.00 | 0.309944E+10 | 0.189118E+10 | 0.00 | 0.36 |
December | 0.248105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110563E+11 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.145754E+12 | 0.501482E+11 | 0.00 | 0.330877E+09 | 0.166379E+10 | 0.286839E+11 | 0.531180E+11 | 0.00 | 0.50 |
Minimum of Months | 0.144354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.260398E+11 | 0.228123E+11 | 0.00 | 62926583.52 | 0.645420E+09 | 0.110563E+11 | 0.105131E+11 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119424E+11 | 0.00 | 0.00 | 8787944.11 | 0.00 | 0.278278E+10 | 0.510888E+10 | 0.00 | 0.29 |
February | 0.880778E+10 | 0.00 | 0.00 | 23450298.63 | 0.00 | 0.119422E+10 | 0.119350E+11 | 0.00 | 0.44 |
March | 0.797280E+10 | 0.00 | 0.00 | 53702699.09 | 0.00 | 0.500341E+09 | 0.219930E+11 | 0.00 | 0.70 |
April | 0.270834E+10 | 0.557806E+09 | 0.00 | 0.104086E+09 | 30954034.33 | 2422558.12 | 0.284418E+11 | 0.00 | 1.18 |
May | 0.114625E+10 | 0.240137E+10 | 0.00 | 98991278.89 | 99957896.05 | 0.00 | 0.184886E+11 | 0.00 | 1.27 |
June | 0.393034E+09 | 0.826487E+10 | 0.00 | 78376254.62 | 0.117008E+09 | 0.00 | 0.648036E+10 | 0.00 | 1.10 |
July | 69217369.00 | 0.211182E+11 | 0.00 | 10524716.88 | 0.327378E+09 | 0.00 | 0.689363E+09 | 0.00 | 0.94 |
August | 0.352371E+09 | 0.841190E+10 | 0.00 | 57435856.65 | 0.171816E+09 | 0.00 | 0.603910E+10 | 0.00 | 1.06 |
September | 0.107627E+10 | 0.537128E+10 | 0.00 | 70769927.37 | 87126862.18 | 0.00 | 0.968996E+10 | 0.00 | 1.08 |
October | 0.470880E+10 | 0.887039E+09 | 0.00 | 65061877.91 | 10826327.62 | 0.00 | 0.195662E+11 | 0.00 | 0.90 |
November | 0.966101E+10 | 0.00 | 0.00 | 30030731.45 | 0.00 | 0.876872E+09 | 0.117275E+11 | 0.00 | 0.47 |
December | 0.126000E+11 | 0.00 | 0.00 | 5170501.23 | 0.00 | 0.386240E+10 | 0.342787E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.614383E+11 | 0.470125E+11 | 0.00 | 0.606388E+09 | 0.845066E+09 | 0.921904E+10 | 0.143588E+12 | 0.00 | 0.81 |
Minimum of Months | 69217369.00 | 0.00 | 0.00 | 5170501.23 | 0.00 | 0.00 | 0.689363E+09 | 0.00 | 0.27 |
Maximum of Months | 0.126000E+11 | 0.211182E+11 | 0.00 | 0.104086E+09 | 0.327378E+09 | 0.386240E+10 | 0.284418E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128912E+11 | 0.00 | 0.00 | 0.137069E+09 | 0.00 | 0.272433E+10 | 0.711491E+11 | 0.00 | 0.90 |
February | 0.117316E+11 | 0.00 | 0.00 | 0.137070E+09 | 0.00 | 0.132390E+10 | 0.539104E+11 | 0.00 | 0.95 |
March | 0.118869E+11 | 0.00 | 0.00 | 0.125281E+09 | 0.00 | 0.389503E+09 | 0.455799E+11 | 0.00 | 0.95 |
April | 0.704996E+10 | 0.118839E+10 | 0.00 | 95713850.09 | 48403289.05 | 3778828.34 | 0.229876E+11 | 0.00 | 0.86 |
May | 0.335594E+10 | 0.316422E+10 | 0.00 | 69944443.27 | 0.165773E+09 | 0.00 | 0.999744E+10 | 0.00 | 0.69 |
June | 0.875795E+09 | 0.980769E+10 | 0.00 | 55399041.11 | 0.239033E+09 | 0.00 | 0.466580E+10 | 0.00 | 0.65 |
July | 0.145897E+09 | 0.231339E+11 | 0.00 | 7741492.22 | 0.662483E+09 | 0.00 | 0.488913E+09 | 0.00 | 0.61 |
August | 0.556720E+09 | 0.107616E+11 | 0.00 | 67491840.48 | 0.309628E+09 | 0.00 | 0.593495E+10 | 0.00 | 0.77 |
September | 0.155652E+10 | 0.909709E+10 | 0.00 | 0.107768E+09 | 0.166033E+09 | 0.00 | 0.971970E+10 | 0.00 | 0.89 |
October | 0.570347E+10 | 0.237949E+10 | 0.00 | 0.202611E+09 | 6520837.50 | 0.00 | 0.427710E+11 | 0.00 | 1.34 |
November | 0.101407E+11 | 0.00 | 0.00 | 0.213425E+09 | 0.00 | 0.563362E+09 | 0.593640E+11 | 0.00 | 1.06 |
December | 0.143864E+11 | 0.00 | 0.00 | 0.126887E+09 | 0.00 | 0.319412E+10 | 0.724441E+11 | 0.00 | 0.88 |
Annual Sum or Average | 0.802811E+11 | 0.595323E+11 | 0.00 | 0.134640E+10 | 0.159787E+10 | 0.819900E+10 | 0.399013E+12 | 0.00 | 0.88 |
Minimum of Months | 0.145897E+09 | 0.00 | 0.00 | 7741492.22 | 0.00 | 0.00 | 0.488913E+09 | 0.00 | 0.61 |
Maximum of Months | 0.143864E+11 | 0.231339E+11 | 0.00 | 0.213425E+09 | 0.662483E+09 | 0.319412E+10 | 0.724441E+11 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149073E+11 | 0.00 | 0.00 | 17103720.16 | 0.00 | 0.283368E+10 | 0.983750E+10 | 0.00 | 0.43 |
February | 0.119180E+11 | 0.00 | 0.00 | 27011791.30 | 0.00 | 0.130202E+10 | 0.104155E+11 | 0.00 | 0.51 |
March | 0.916869E+10 | 0.00 | 0.00 | 62131226.59 | 0.00 | 0.317070E+09 | 0.209779E+11 | 0.00 | 0.81 |
April | 0.328792E+10 | 0.101466E+10 | 0.00 | 85118874.18 | 4608688.81 | 0.00 | 0.199125E+11 | 0.00 | 1.06 |
May | 0.147416E+10 | 0.348688E+10 | 0.00 | 70035627.75 | 34689889.44 | 0.00 | 0.982474E+10 | 0.00 | 1.03 |
June | 0.355671E+09 | 0.112378E+11 | 0.00 | 56396008.45 | 66470390.44 | 0.00 | 0.466019E+10 | 0.00 | 1.01 |
July | 45467625.75 | 0.230649E+11 | 0.00 | 9160578.69 | 0.208756E+09 | 0.00 | 0.531502E+09 | 0.00 | 0.90 |
August | 0.260110E+09 | 0.934157E+10 | 0.00 | 59383575.29 | 72233434.80 | 0.00 | 0.480501E+10 | 0.00 | 1.01 |
September | 0.968781E+09 | 0.566740E+10 | 0.00 | 61967800.68 | 75083593.25 | 0.00 | 0.649028E+10 | 0.00 | 0.92 |
October | 0.415009E+10 | 0.142847E+10 | 0.00 | 73880850.78 | 3950168.39 | 0.00 | 0.184961E+11 | 0.00 | 1.01 |
November | 0.111005E+11 | 0.00 | 0.00 | 40795534.00 | 0.00 | 0.429379E+09 | 0.132258E+11 | 0.00 | 0.57 |
December | 0.158211E+11 | 0.00 | 0.00 | 14000464.82 | 0.00 | 0.314278E+10 | 0.944998E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.734579E+11 | 0.552417E+11 | 0.00 | 0.576986E+09 | 0.465792E+09 | 0.802493E+10 | 0.128627E+12 | 0.00 | 0.81 |
Minimum of Months | 45467625.75 | 0.00 | 0.00 | 9160578.69 | 0.00 | 0.00 | 0.531502E+09 | 0.00 | 0.42 |
Maximum of Months | 0.158211E+11 | 0.230649E+11 | 0.00 | 85118874.18 | 0.208756E+09 | 0.314278E+10 | 0.209779E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177868E+10 | 0.00 | 0.00 | 0.34 |
February | 0.164739E+10 | 0.00 | 0.00 | 136166.02 | 0.00 | 0.104358E+10 | 69202936.11 | 0.00 | 0.38 |
March | 0.197755E+10 | 0.00 | 0.00 | 1033295.17 | 0.00 | 0.527970E+09 | 0.443508E+09 | 0.00 | 0.46 |
April | 0.922325E+09 | 30580222.26 | 0.00 | 4925857.30 | 4795078.77 | 58655874.75 | 0.923545E+09 | 0.00 | 0.54 |
May | 0.323843E+09 | 0.167882E+09 | 0.00 | 7088388.64 | 19590372.57 | 0.00 | 0.830419E+09 | 0.00 | 0.62 |
June | 93868109.72 | 0.757439E+09 | 0.00 | 7135375.85 | 19997655.89 | 0.00 | 0.503024E+09 | 0.00 | 0.66 |
July | 17966264.76 | 0.208445E+10 | 0.00 | 1126250.32 | 68943918.63 | 0.00 | 47177179.14 | 0.00 | 0.60 |
August | 86191808.16 | 0.685837E+09 | 0.00 | 5981415.45 | 31666642.94 | 0.00 | 0.496876E+09 | 0.00 | 0.63 |
September | 0.260060E+09 | 0.359450E+09 | 0.00 | 4837890.33 | 22224279.37 | 0.00 | 0.376030E+09 | 0.00 | 0.51 |
October | 0.115230E+10 | 83943303.16 | 0.00 | 2891204.14 | 4696399.69 | 14881997.33 | 0.757862E+09 | 0.00 | 0.51 |
November | 0.184305E+10 | 0.00 | 0.00 | 295627.67 | 0.00 | 0.783588E+09 | 0.132853E+09 | 0.00 | 0.40 |
December | 0.125314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217514E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.110897E+11 | 0.416958E+10 | 0.00 | 35451470.89 | 0.171914E+09 | 0.638250E+10 | 0.458050E+10 | 0.00 | 0.50 |
Minimum of Months | 17966264.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.197755E+10 | 0.208445E+10 | 0.00 | 7135375.85 | 68943918.63 | 0.217514E+10 | 0.923545E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132883E+10 | 0.00 | 0.00 | 179067.17 | 0.00 | 0.623978E+09 | 0.145144E+09 | 0.00 | 0.34 |
February | 0.968462E+09 | 0.00 | 0.00 | 1225222.65 | 0.00 | 0.282072E+09 | 0.759124E+09 | 0.00 | 0.45 |
March | 0.795853E+09 | 0.00 | 0.00 | 4240107.97 | 0.00 | 0.180802E+09 | 0.215431E+10 | 0.00 | 0.78 |
April | 0.253216E+09 | 33235444.65 | 0.00 | 10587152.59 | 1951306.45 | 11967408.28 | 0.271123E+10 | 0.00 | 1.23 |
May | 95171161.03 | 0.164694E+09 | 0.00 | 11220000.38 | 9490134.52 | 0.00 | 0.179548E+10 | 0.00 | 1.31 |
June | 42271863.49 | 0.660421E+09 | 0.00 | 9169711.42 | 9824365.86 | 0.00 | 0.649378E+09 | 0.00 | 1.09 |
July | 8323822.77 | 0.202729E+10 | 0.00 | 1490565.47 | 33889706.79 | 0.00 | 59455111.67 | 0.00 | 0.95 |
August | 40863382.31 | 0.728465E+09 | 0.00 | 6965121.05 | 15775008.15 | 0.00 | 0.619117E+09 | 0.00 | 1.08 |
September | 0.101957E+09 | 0.457573E+09 | 0.00 | 7985594.05 | 7907452.02 | 0.00 | 0.843095E+09 | 0.00 | 1.09 |
October | 0.473022E+09 | 72929704.33 | 0.00 | 5874822.67 | 1217754.66 | 5091860.59 | 0.183017E+10 | 0.00 | 0.92 |
November | 0.982110E+09 | 0.00 | 0.00 | 1844902.54 | 0.00 | 0.270599E+09 | 0.865147E+09 | 0.00 | 0.51 |
December | 0.134345E+10 | 0.00 | 0.00 | 12356.69 | 0.00 | 0.785923E+09 | 19724854.74 | 0.00 | 0.33 |
Annual Sum or Average | 0.643352E+10 | 0.414461E+10 | 0.00 | 60794624.66 | 80055728.46 | 0.216043E+10 | 0.124514E+11 | 0.00 | 0.84 |
Minimum of Months | 8323822.77 | 0.00 | 0.00 | 12356.69 | 0.00 | 0.00 | 19724854.74 | 0.00 | 0.33 |
Maximum of Months | 0.134345E+10 | 0.202729E+10 | 0.00 | 11220000.38 | 33889706.79 | 0.785923E+09 | 0.271123E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112870E+10 | 0.00 | 0.00 | 9340668.22 | 0.00 | 0.550538E+09 | 0.565814E+10 | 0.00 | 0.83 |
February | 0.101386E+10 | 0.00 | 0.00 | 10100795.17 | 0.00 | 0.319608E+09 | 0.487850E+10 | 0.00 | 0.93 |
March | 0.103457E+10 | 0.00 | 0.00 | 9977480.95 | 0.00 | 0.288883E+09 | 0.486353E+10 | 0.00 | 1.06 |
April | 0.636657E+09 | 63939077.19 | 0.00 | 10543623.82 | 3039977.14 | 42951466.93 | 0.229424E+10 | 0.00 | 0.87 |
May | 0.335281E+09 | 0.196182E+09 | 0.00 | 8028169.03 | 19548357.73 | 0.00 | 0.938077E+09 | 0.00 | 0.68 |
June | 0.101018E+09 | 0.749906E+09 | 0.00 | 6772967.32 | 20747935.14 | 0.00 | 0.455334E+09 | 0.00 | 0.63 |
July | 17649695.02 | 0.209198E+10 | 0.00 | 1152773.47 | 71481686.38 | 0.00 | 42414760.92 | 0.00 | 0.60 |
August | 67180469.54 | 0.857067E+09 | 0.00 | 7914019.42 | 29052358.39 | 0.00 | 0.608073E+09 | 0.00 | 0.75 |
September | 0.153291E+09 | 0.656895E+09 | 0.00 | 12438375.14 | 13298683.62 | 0.00 | 0.899727E+09 | 0.00 | 0.87 |
October | 0.564068E+09 | 0.184970E+09 | 0.00 | 18803523.17 | 446520.76 | 887752.95 | 0.432538E+10 | 0.00 | 1.39 |
November | 0.912948E+09 | 0.00 | 0.00 | 15994173.30 | 0.00 | 0.301028E+09 | 0.621979E+10 | 0.00 | 1.24 |
December | 0.123002E+10 | 0.00 | 0.00 | 8274510.61 | 0.00 | 0.625949E+09 | 0.531219E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.719524E+10 | 0.480094E+10 | 0.00 | 0.119341E+09 | 0.157616E+09 | 0.212984E+10 | 0.364954E+11 | 0.00 | 0.88 |
Minimum of Months | 17649695.02 | 0.00 | 0.00 | 1152773.47 | 0.00 | 0.00 | 42414760.92 | 0.00 | 0.60 |
Maximum of Months | 0.123002E+10 | 0.209198E+10 | 0.00 | 18803523.17 | 71481686.38 | 0.625949E+09 | 0.621979E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108574E+10 | 0.00 | 0.00 | 1211122.59 | 0.00 | 0.582587E+09 | 0.834015E+09 | 0.00 | 0.42 |
February | 0.102183E+10 | 0.00 | 0.00 | 1950910.17 | 0.00 | 0.307128E+09 | 0.993590E+09 | 0.00 | 0.53 |
March | 0.879472E+09 | 0.00 | 0.00 | 5221473.43 | 0.00 | 0.178547E+09 | 0.226307E+10 | 0.00 | 0.94 |
April | 0.367966E+09 | 53988677.80 | 0.00 | 9553884.32 | 264792.25 | 10692012.66 | 0.194841E+10 | 0.00 | 1.09 |
May | 0.130818E+09 | 0.213645E+09 | 0.00 | 8156279.64 | 3930589.95 | 0.00 | 0.937817E+09 | 0.00 | 1.00 |
June | 34753262.04 | 0.818710E+09 | 0.00 | 6908831.75 | 6294641.60 | 0.00 | 0.457496E+09 | 0.00 | 0.94 |
July | 5289819.22 | 0.201696E+10 | 0.00 | 1352275.35 | 23050449.60 | 0.00 | 47728181.48 | 0.00 | 0.85 |
August | 26105425.82 | 0.729003E+09 | 0.00 | 7110019.68 | 8393524.59 | 0.00 | 0.488654E+09 | 0.00 | 0.97 |
September | 90341562.66 | 0.406627E+09 | 0.00 | 7257063.48 | 7462926.88 | 0.00 | 0.589145E+09 | 0.00 | 0.87 |
October | 0.447721E+09 | 0.109478E+09 | 0.00 | 7040989.51 | 1076167.63 | 0.00 | 0.173064E+10 | 0.00 | 1.01 |
November | 0.977630E+09 | 0.00 | 0.00 | 3093979.65 | 0.00 | 0.230471E+09 | 0.144934E+10 | 0.00 | 0.68 |
December | 0.106943E+10 | 0.00 | 0.00 | 912579.03 | 0.00 | 0.694904E+09 | 0.687881E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.613709E+10 | 0.434842E+10 | 0.00 | 59769408.61 | 50473092.49 | 0.200433E+10 | 0.124278E+11 | 0.00 | 0.81 |
Minimum of Months | 5289819.22 | 0.00 | 0.00 | 912579.03 | 0.00 | 0.00 | 47728181.48 | 0.00 | 0.38 |
Maximum of Months | 0.108574E+10 | 0.201696E+10 | 0.00 | 9553884.32 | 23050449.60 | 0.694904E+09 | 0.226307E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3739489.44 | 0.00 | 0.00 | 0.448271E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8238418.26 | 0.00 | 0.00 | 0.359495E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14862544.71 | 0.00 | 0.00 | 0.371893E+09 | 0.00 | 0.31 |
April | 0.00 | 670365.38 | 0.00 | 17319296.28 | 0.00 | 0.00 | 0.185344E+09 | 0.00 | 0.29 |
May | 0.00 | 29482482.93 | 0.00 | 2828101.74 | 0.00 | 0.00 | 96071925.44 | 0.00 | 0.29 |
June | 0.00 | 88238932.05 | 0.00 | 1250406.34 | 0.00 | 0.00 | 11695852.60 | 0.00 | 0.30 |
July | 0.00 | 0.285733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.175611E+09 | 0.00 | 715803.39 | 0.00 | 0.00 | 1098355.45 | 0.00 | 0.31 |
September | 0.00 | 0.116259E+09 | 0.00 | 1167364.60 | 0.00 | 0.00 | 26313162.96 | 0.00 | 0.29 |
October | 0.00 | 39048303.79 | 0.00 | 6435251.95 | 0.00 | 0.00 | 0.139054E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13268793.60 | 0.00 | 0.00 | 0.321267E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18784768.17 | 0.00 | 0.00 | 0.455589E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.735043E+09 | 0.00 | 88610238.48 | 0.00 | 0.00 | 0.241609E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.285733E+09 | 0.00 | 18784768.17 | 0.00 | 0.00 | 0.455589E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 24103445.03 | 0.00 | 0.00 | 0.450421E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 70100660.81 | 0.00 | 0.00 | 0.360806E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.135636E+09 | 0.00 | 0.00 | 0.373010E+10 | 0.00 | 0.31 |
April | 0.00 | 7234058.06 | 0.00 | 0.163322E+09 | 0.00 | 0.00 | 0.185689E+10 | 0.00 | 0.29 |
May | 0.00 | 0.290180E+09 | 0.00 | 26004121.08 | 0.00 | 0.00 | 0.962120E+09 | 0.00 | 0.29 |
June | 0.00 | 0.878132E+09 | 0.00 | 11888773.15 | 0.00 | 0.00 | 0.116857E+09 | 0.00 | 0.30 |
July | 0.00 | 0.284955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.179465E+10 | 0.00 | 5761000.25 | 0.00 | 0.00 | 10244669.34 | 0.00 | 0.30 |
September | 0.00 | 0.114136E+10 | 0.00 | 10628809.50 | 0.00 | 0.00 | 0.266609E+09 | 0.00 | 0.29 |
October | 0.00 | 0.385673E+09 | 0.00 | 58747569.75 | 0.00 | 0.00 | 0.139968E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.119276E+09 | 0.00 | 0.00 | 0.322635E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.167011E+09 | 0.00 | 0.00 | 0.457430E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.734677E+10 | 0.00 | 0.792480E+09 | 0.00 | 0.00 | 0.242554E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.284955E+10 | 0.00 | 0.167011E+09 | 0.00 | 0.00 | 0.457430E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122758E+09 | 0.00 | 0.00 | 1299691.53 | 0.00 | 0.00 | 0.328781E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5983249.69 | 0.00 | 0.00 | 0.362238E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12791550.05 | 0.00 | 0.00 | 0.373912E+09 | 0.00 | 0.31 |
April | 0.00 | 819965.51 | 0.00 | 16046675.71 | 0.00 | 0.00 | 0.184961E+09 | 0.00 | 0.29 |
May | 0.00 | 29182038.97 | 0.00 | 2598381.40 | 0.00 | 0.00 | 96240553.96 | 0.00 | 0.29 |
June | 0.00 | 88030489.85 | 0.00 | 1186947.95 | 0.00 | 0.00 | 11710092.00 | 0.00 | 0.30 |
July | 0.00 | 0.285172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.182732E+09 | 0.00 | 535617.92 | 0.00 | 0.00 | 986042.71 | 0.00 | 0.30 |
September | 0.00 | 0.114613E+09 | 0.00 | 1025773.98 | 0.00 | 0.00 | 26768152.90 | 0.00 | 0.29 |
October | 0.00 | 38534533.45 | 0.00 | 5575454.26 | 0.00 | 0.00 | 0.140719E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10992186.34 | 0.00 | 0.00 | 0.323771E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15300737.98 | 0.00 | 0.00 | 0.458962E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.122758E+09 | 0.739085E+09 | 0.00 | 73336266.79 | 0.00 | 0.00 | 0.230905E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.122758E+09 | 0.285172E+09 | 0.00 | 16046675.71 | 0.00 | 0.00 | 0.458962E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.541756E+09 | 0.00 | 0.00 | 0.521252E+12 | 0.00 | 13.44 |
February | 0.00 | 0.00 | 0.00 | 0.101213E+10 | 0.00 | 0.00 | 0.729315E+12 | 0.00 | 26.81 |
March | 0.00 | 0.00 | 0.00 | 0.163294E+10 | 0.00 | 0.00 | 0.979459E+12 | 0.00 | 38.23 |
April | 0.00 | 0.00 | 0.00 | 0.280749E+10 | 0.00 | 0.00 | 0.746933E+12 | 0.00 | 46.42 |
May | 0.00 | 0.137016E+10 | 0.00 | 0.446753E+09 | 0.00 | 0.00 | 0.306491E+12 | 0.00 | 25.87 |
June | 0.00 | 0.757757E+10 | 0.00 | 0.624384E+09 | 0.00 | 0.00 | 0.124986E+12 | 0.00 | 22.11 |
July | 0.00 | 0.162229E+12 | 0.00 | 43453116.04 | 0.00 | 0.00 | 0.237218E+10 | 0.00 | 25.96 |
August | 0.00 | 0.457223E+11 | 0.00 | 0.132278E+10 | 0.00 | 0.00 | 0.556175E+11 | 0.00 | 40.63 |
September | 0.00 | 0.797439E+10 | 0.00 | 0.397888E+09 | 0.00 | 0.00 | 0.208404E+12 | 0.00 | 27.29 |
October | 0.00 | 0.442922E+10 | 0.00 | 0.108276E+10 | 0.00 | 0.00 | 0.533951E+12 | 0.00 | 37.04 |
November | 0.00 | 0.00 | 0.00 | 0.170297E+10 | 0.00 | 0.00 | 0.969195E+12 | 0.00 | 36.42 |
December | 0.00 | 0.00 | 0.00 | 0.227884E+10 | 0.00 | 0.00 | 0.129284E+13 | 0.00 | 37.07 |
Annual Sum or Average | 0.00 | 0.229302E+12 | 0.00 | 0.138941E+11 | 0.00 | 0.00 | 0.647081E+13 | 0.00 | 31.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 43453116.04 | 0.00 | 0.00 | 0.237218E+10 | 0.00 | 13.44 |
Maximum of Months | 0.00 | 0.162229E+12 | 0.00 | 0.280749E+10 | 0.00 | 0.00 | 0.129284E+13 | 0.00 | 46.42 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.364210E+12 | 0.157642E+11 | 0.00 | 0.223048E+13 | 0.165803E+12 |
February | 0.378976E+12 | 0.130728E+11 | 0.00 | 0.218646E+13 | 0.341418E+12 |
March | 0.556260E+12 | 0.143571E+11 | 0.00 | 0.264688E+13 | 0.742608E+12 |
April | 0.585906E+12 | 0.773348E+10 | 0.00 | 0.194912E+13 | 0.190316E+13 |
May | 0.619922E+12 | 0.413708E+10 | 0.00 | 0.113494E+13 | 0.181085E+13 |
June | 0.611038E+12 | -539841230.9 | 0.00 | 0.310352E+12 | 0.283125E+13 |
July | 0.605356E+12 | -0.341987E+10 | 0.00 | -0.576197E+12 | 0.374445E+13 |
August | 0.564149E+12 | -598221130.3 | 0.00 | 0.842767E+11 | 0.369093E+13 |
September | 0.509858E+12 | 0.138551E+10 | 0.00 | 0.590463E+12 | 0.187049E+13 |
October | 0.464578E+12 | 0.676389E+10 | 0.00 | 0.191439E+13 | 0.119905E+13 |
November | 0.368728E+12 | 0.131528E+11 | 0.00 | 0.270281E+13 | 0.609851E+12 |
December | 0.308095E+12 | 0.135765E+11 | 0.00 | 0.300348E+13 | 0.436228E+12 |
Annual Sum or Average | 0.593708E+13 | 0.853855E+11 | 0.00 | 0.181774E+14 | 0.193461E+14 |
Minimum of Months | 0.308095E+12 | -0.341987E+10 | 0.00 | -0.576197E+12 | 0.165803E+12 |
Maximum of Months | 0.619922E+12 | 0.157642E+11 | 0.00 | 0.300348E+13 | 0.374445E+13 |