Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:51:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27670.47 | 597.37 | 597.37 |
Net Site Energy | 27059.86 | 584.19 | 584.19 |
Total Source Energy | 84616.80 | 1826.77 | 1826.77 |
Net Source Energy | 82682.98 | 1785.02 | 1785.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 705.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2346.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1711.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 263.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2745.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 422.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 681.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6451.53 |
Humidification | 2172.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.06 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 742.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26222.76 | 1447.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9539.76 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 705.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2346.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1711.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 263.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2745.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 422.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 681.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6451.53 |
Humidification | General | 2172.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.06 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 742.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 705.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2346.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1711.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 263.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2745.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 422.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 681.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6451.53 |
Humidification | Unassigned | 2172.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.06 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 742.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.65 | 31.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 566.12 | 31.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.65 | 31.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 566.12 | 31.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 637.148 | 2.43 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -26.53 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 610.615 | 2.33 |
Electricity Coming From Utility | 25612.145 | 97.67 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25612.145 | 97.67 |
Total On-Site and Utility Electric Sources | 26222.760 | 100.00 |
Total Electricity End Uses | 26222.760 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9539.76 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9539.76 | 100.00 |
Total Water End Uses | 9539.76 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 9.00 |
Time Setpoint Not Met During Occupied Cooling | 939.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5840.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-AUG-15:50 | 06-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 21-JUL-16:49 |
Heating | 0.00 | 770394.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 384125.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52589.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 272925.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38907.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 73721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 31055.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1846628.42 | 801450.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 770394.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 384125.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 272925.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 38907.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 73721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 31055.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 764.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7432.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5421.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 833.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8694.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1336.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2157.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6879.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 804.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 83047.48 | 1569.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 160.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 148.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1792.89 | 33.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 160.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 148.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1792.89 | 33.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.92 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.577943 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.54 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.565727 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.88 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.37 | 0.298386 | 0.254000 | 1.62 | 0.795696 | 0.500000 | 0.001277 | 0.000293 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.72 | 0.318519 | 0.271000 | 16.18 | 0.849384 | 0.500000 | 0.001196 | 0.007961 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.03 | 0.315340 | 0.268000 | 1.62 | 0.840907 | 0.500000 | 0.001208 | 0.001697 | 2.81 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.16 | 0.205471 | 0.175000 | 0.203404 | 0.547922 | 0.500000 | 0.001854 | 0.000205 | 0.339722 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.48 | 0.104259 | 0.089000 | 0.131380 | 0.300000 | 0.500000 | 0.003654 | 0.000147 | 0.242993 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.47 | 0.162022 | 0.138000 | 0.203417 | 0.432058 | 0.500000 | 0.002352 | 0.000256 | 0.423222 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.86 | 0.082900 | 0.070000 | 0.129956 | 0.300000 | 0.500000 | 0.004596 | 0.000097 | 0.159866 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.15 | 0.214237 | 0.182000 | 2.03 | 0.571300 | 0.500000 | 0.001778 | 0.004336 | 7.19 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 15.85 | 0.300000 | 0.500000 | 0.003924 | 0.002879 | 4.77 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.45 | 0.165225 | 0.140000 | 2.02 | 0.440600 | 0.500000 | 0.002306 | 0.004298 | 7.13 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 17.14 | 0.089813 | 0.076000 | 1.30 | 0.300000 | 0.500000 | 0.004242 | 0.002714 | 4.50 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.29 | 0.185717 | 0.158000 | 0.203178 | 0.495246 | 0.500000 | 0.002052 | 0.000553 | 0.917467 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.60 | 0.095965 | 0.082000 | 0.131508 | 0.300000 | 0.500000 | 0.003970 | 0.000365 | 0.605469 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.60 | 0.148933 | 0.127000 | 0.203655 | 0.397154 | 0.500000 | 0.002558 | 0.000549 | 0.910725 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.83 | 0.084244 | 0.072000 | 0.131537 | 0.300000 | 0.500000 | 0.004523 | 0.000352 | 0.583332 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 13408.53 | 0.000293 | 374.23 |
CORE_MID VAV BOX REHEAT COIL | 363916.83 | 0.007961 | 12717.65 |
CORE_TOP VAV BOX REHEAT COIL | 77574.37 | 0.001697 | 3018.52 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9384.24 | 0.000205 | 365.09 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6709.85 | 0.000147 | 260.98 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11683.59 | 0.000256 | 454.37 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4421.96 | 0.000097 | 172.19 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 198209.67 | 0.004336 | 7701.72 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 131590.08 | 0.002879 | 5112.93 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 196486.09 | 0.004298 | 7634.83 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 124073.20 | 0.002714 | 4821.16 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 25284.76 | 0.000553 | 982.22 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16685.67 | 0.000365 | 648.16 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25099.20 | 0.000549 | 975.02 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16076.31 | 0.000352 | 624.51 |
VAV_BOT WITH REHEAT HEATING COIL | 44121.63 | 0.000965 | 955.01 |
VAV_MID WITH REHEAT HEATING COIL | 355226.89 | 0.007771 | 7874.72 |
VAV_TOP WITH REHEAT HEATING COIL | 34659.54 | 0.000758 | 779.90 |
CAV_BAS HEATING COIL | 245095.58 | 0.005361 | 7759.17 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.17 | 2.29 | 12.34 | 2.29 | 10.73 | 10.73 | 0.300000 | 0.213248 | 10.73 |
VAV_MID WITH REHEAT | 59.15 | 22.85 | 118.30 | 35.37 | 99.89 | 99.89 | 0.300000 | 0.354135 | 99.89 |
VAV_TOP WITH REHEAT | 6.18 | 2.29 | 12.35 | 5.82 | 11.32 | 11.32 | 0.300000 | 0.514671 | 11.32 |
CAV_BAS | 5.92 | 5.92 | 5.92 | 5.92 | 5.92 | 5.92 | 1.00 | 1.00 | 5.92 |
AIRLOOP DATACENTER BASEMENT | 25.88 | 25.88 | 25.88 | 25.88 | 25.88 | 25.88 | 1.00 | 0.999989 | 25.88 |
AIRLOOP DATACENTER BOT | 0.577943 | 0.577943 | 0.577943 | 0.577943 | 0.577943 | 0.577943 | 1.00 | 1.00 | 0.577943 |
AIRLOOP DATACENTER MID | 5.54 | 5.54 | 5.54 | 5.54 | 5.54 | 5.54 | 1.00 | 1.00 | 5.54 |
AIRLOOP DATACENTER TOP | 0.565727 | 0.565727 | 0.565727 | 0.565727 | 0.565727 | 0.565727 | 1.00 | 1.00 | 0.565727 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.73 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 99.89 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.32 | |
CAV_BAS_OA_CONTROLLER | 5.92 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.88 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.577943 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.54 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.565727 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.16 | 6.67 | 10.67 | 0.007030 | 0.007030 | 167499.31 | 0.004790 | 10.73 |
VAV_MID WITH REHEAT COOLING COIL | 26.37 | 6.67 | 10.66 | 0.007012 | 0.007012 | 1582419.57 | 0.045257 | 99.89 |
VAV_TOP WITH REHEAT COOLING COIL | 26.00 | 6.67 | 10.67 | 0.007017 | 0.007017 | 174904.09 | 0.005002 | 11.32 |
CAV_BAS COOLING COIL | 26.39 | 6.67 | 11.12 | 0.007142 | 0.007142 | 91137.27 | 0.002607 | 5.92 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.73 |
VAV_MID WITH REHEAT FAN | 99.89 |
VAV_TOP WITH REHEAT FAN | 11.32 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004790 | 0.000099 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000965 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.045257 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007771 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005002 | 0.000095 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000758 | |
CAV_BAS_COOLC_CONTROLLER | 0.002607 | 0.000183 |
CAV_BAS_HEATC_CONTROLLER | 0.005361 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.92 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.88 | 473978.23 | 251376.14 | 0.011608 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.577943 | 10309.44 | 5518.02 | 0.000252 |
AIRLOOP DATACENTER MID COOLING COIL | 5.54 | 98848.58 | 52894.24 | 0.002421 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.565727 | 10093.98 | 5402.00 | 0.000247 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.88 | 25.88 | 25.88 | 25.88 | 473978.23 | 473978.23 | 16131.55 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.577943 | 0.577943 | 0.577943 | 0.577943 | 10309.44 | 10309.44 | 745.21 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.54 | 5.54 | 5.54 | 5.54 | 98848.58 | 98848.58 | 7452.11 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.565727 | 0.565727 | 0.565727 | 0.565727 | 10093.98 | 10093.98 | 745.21 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.88 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.577943 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.54 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.565727 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.88 | 473978.23 | 0.011608 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.577943 | 10309.44 | 0.000252 |
AIRLOOP DATACENTER MID HEATING COIL | 5.54 | 98848.58 | 0.002421 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.565727 | 10093.98 | 0.000247 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 16131.55 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 745.21 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7452.11 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 745.21 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000140 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.057656 | 9320.29 | |
HEATSYS1 PUMP | 0.041556 | 12390.98 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.057656 | 6.92 |
HEATSYS1 | 0.041556 | 4.99 |
COOLSYS1_SUPPLY | 0.057656 | 6.92 |
SINGLE WATER PLANT LOOP | 0.014528 | 1.74 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.057656 | 0.057656 | 242012.03 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1899707.98 | 1899707.98 | 0.041556 |
CENTRAL BOILER | 598436.06 | 584736.58 | 0.014528 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.028828 | 3226.38 |
COOLSYS1 CHILLER2 PUMP | 0.028828 | 3226.38 |
PLANT CIRC PUMP | 0.014528 | 3668.72 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.057656 | 0.029254 | 1024011.91 | 1030244.02 | 0.052231 |
COOLSYS1 CHILLER2 | 0.057656 | 0.029254 | 1024011.91 | 1030244.02 | 0.052231 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014528 | 139666.47 | 55202.19 | 69833.23 | 7004.20 | 20982.13 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.104462 | 12.54 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.104462 | 25606.50 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 47.91 | 1223884.72 | 9.58 | 152985.59 |
TOWERWATERSYS COOLTOWER 2 | 47.91 | 1223884.72 | 9.58 | 152985.59 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.052955 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9398 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8967 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9335 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8058 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.29018797E-14 | 0.36812723E-16 | -0.14924019E-09 | 0.48847313E-16 |
51 | 8 | 0.21807402E-07 | 0.12652057E-12 | 0.37708831E-03 | -0.24795767E-09 |
52 | 7 | -0.12220551E-01 | 0.65729479E-08 | -0.23055577E-01 | 0.13895212E-03 |
53 | 6 | 0.40477966 | 0.22909352E-05 | 0.47160541 | -0.47410351E-02 |
54 | 5 | -5.1849947 | 0.85678555E-04 | -4.4375337 | 0.63114796E-01 |
55 | 4 | 32.978226 | 0.70190469E-03 | 21.425779 | -0.42179587 |
56 | 3 | -111.17384 | 0.15317614E-02 | -55.595241 | 1.5144378 |
57 | 2 | 197.07933 | 0.86263138E-03 | 77.848428 | -2.8998938 |
58 | 1 | -171.14541 | 0.92189209E-04 | -55.246988 | 2.7452524 |
59 | 0 | 57.057407 | 0.52547460E-06 | 15.559906 | |
60 | 9 | -0.29188985E-14 | 0.30841220E-16 | -0.15071594E-09 | 0.45756810E-16 |
61 | 8 | 0.22014798E-07 | 0.12246996E-12 | 0.37926559E-03 | -0.25031584E-09 |
62 | 7 | -0.12285514E-01 | 0.63488536E-08 | -0.23149110E-01 | 0.13969077E-03 |
63 | 6 | 0.40654483 | 0.22108485E-05 | 0.47310859 | -0.47618422E-02 |
64 | 5 | -5.2022205 | 0.82619656E-04 | -4.4490782 | 0.63328388E-01 |
65 | 4 | 33.054419 | 0.67637415E-03 | 21.470902 | -0.42280751 |
66 | 3 | -111.33595 | 0.14751306E-02 | -55.684449 | 1.5167798 |
67 | 2 | 197.23999 | 0.83027991E-03 | 77.930247 | -2.9024452 |
68 | 1 | -171.20475 | 0.88686394E-04 | -55.270783 | 2.7462925 |
69 | 0 | 57.057407 | 0.50524406E-06 | 15.555978 | |
70 | 9 | -0.57207635E-15 | 0.35733182E-16 | -0.14510758E-09 | 0.92780423E-20 |
71 | 8 | 0.21226260E-07 | 0.13767829E-12 | 0.37094976E-03 | -0.24134990E-09 |
72 | 7 | -0.12037268E-01 | 0.71989887E-08 | -0.22791647E-01 | 0.13686812E-03 |
73 | 6 | 0.39979937 | 0.25155658E-05 | 0.46736115 | -0.46823295E-02 |
74 | 5 | -5.1363910 | 0.94286903E-04 | -4.4049234 | 0.62512134E-01 |
75 | 4 | 32.763227 | 0.77396227E-03 | 21.298286 | -0.41894130 |
76 | 3 | -110.71637 | 0.16919998E-02 | -55.343173 | 1.5078286 |
77 | 2 | 196.62589 | 0.95437189E-03 | 77.617295 | -2.8926932 |
78 | 1 | -170.97790 | 0.10214201E-03 | -55.179873 | 2.7423166 |
79 | 0 | 57.057407 | 0.58311013E-06 | 15.571069 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1565E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1585E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.6869E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.6886E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5086E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5100E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4917E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4924E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2043E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3466E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7273E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8514E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5430E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6453E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5122E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5645E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1548 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1468E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1740 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9324E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1116 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3459E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5025E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5661E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2064E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3557E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7293E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8606E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5448E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6519E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5127E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5660E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1562E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1584E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.6866E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.6884E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5084E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5098E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4916E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4923E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3648E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6284E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0585E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3416E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8901E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0129E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2602E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2962E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8755E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8662E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3955E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5596E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7605E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3812E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6880E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7537E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2881E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3868E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9600E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0314E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8511E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8785E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2603E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2968E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5559E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5579E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1754E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1770E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9260E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9271E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4917E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6005E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7163E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2115E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3025E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9546E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0182E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5127E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5660E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0491E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1330E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1040E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6144E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7926E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0891E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5025E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5656E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5993E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7134E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2104E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2996E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9533E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0141E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5122E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5645E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5558E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5577E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1753E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1769E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9259E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9270E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4916E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4923E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1946E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2939E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8439E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9156E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7729E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8000E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2604E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2969E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7124E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8027E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1947E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4813E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6162E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3245E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6880E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7537E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2684E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5214E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9391E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2088E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8114E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9320E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2601E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2961E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1507 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.9232E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1637 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1090 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1221 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4473E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5140E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7277E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.0228E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1475E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4857E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7700E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.8525E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5385E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6552E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7590E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0467E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3627E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9753E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6538E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6320E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9949E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5140E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7273E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8383E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0598E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2584E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6616E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6907E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4629E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6552E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7590E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1508 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.9441E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1639 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1092 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1223 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.4634E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5258E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7338E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.0278E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1538E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4914E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7759E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.8632E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5459E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6670E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7650E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0471E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3665E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9760E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6568E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6377E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9985E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5258E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7333E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8430E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0658E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2637E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6672E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.7012E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4701E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6670E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7650E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 67423.62681 | 67423.62681 | 5.91978 | 5.91978 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72603.44573 | 72603.44573 | 6.37444 | 6.37444 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 680317.40813 | 680317.40813 | 59.71520 | 59.71520 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 229899.81055 | 229899.81055 | 11.78504 | 11.78504 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 68093.12898 | 68093.12898 | 6.03172 | 6.03172 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 54323.63540 | 54323.63540 | 2.80757 | 2.80757 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13121.89122 | 13121.89122 | 1.16231 | 1.16231 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6574.88894 | 6574.88894 | 0.33972 | 0.33972 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16665.54753 | 16665.54753 | 1.47618 | 1.47618 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4699.96026 | 4699.96026 | 0.24299 | 0.24299 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16641.17717 | 16641.17717 | 1.47404 | 1.47404 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 34.53750 | 5.69851E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 8181.99967 | 8181.99967 | 0.42322 | 0.42322 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20959.38619 | 20959.38619 | 1.85651 | 1.85651 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3101.20108 | 3101.20108 | 0.15987 | 0.15987 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 125851.54088 | 125851.54088 | 11.14748 | 11.14748 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 138724.39239 | 138724.39239 | 7.18927 | 7.18927 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 178954.45428 | 178954.45428 | 15.85099 | 15.85099 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 92096.05131 | 92096.05131 | 4.77318 | 4.77318 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 163188.03335 | 163188.03335 | 14.45458 | 14.45458 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 137519.43416 | 137519.43416 | 7.12664 | 7.12664 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 193463.92893 | 193463.92893 | 17.13619 | 17.13619 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 86840.69422 | 86840.69422 | 4.50009 | 4.50009 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14517.92538 | 14517.92538 | 1.28594 | 1.28594 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17693.44208 | 17693.44208 | 0.91747 | 0.91747 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18106.22633 | 18106.22633 | 1.60376 | 1.60376 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11675.95168 | 11675.95168 | 0.60547 | 0.60547 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18104.09871 | 18104.09871 | 1.60358 | 1.60358 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 17563.70829 | 17563.70829 | 0.91073 | 0.91073 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20625.42555 | 20625.42555 | 1.82690 | 1.82690 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11249.87230 | 11249.87230 | 0.58333 | 0.58333 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8272.18777 | 8272.18777 | 0.57794 | 0.57794 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 79276.72375 | 79276.72375 | 5.53877 | 5.53877 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8097.31606 | 8097.31606 | 0.56573 | 0.56573 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370471.06515 | 370471.06515 | 25.88281 | 25.88281 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 22.81500 | 5.68069E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 12:20:00 | -7.90000 | 2.34317E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 138773.03 | 10.72584 | 10.72584 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 42241.77 | 2.24363 | 2.24363 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1283562.51 | 99.88904 | 99.88904 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 413766.89 | 35.37422 | 35.37422 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 148083.42 | 11.31706 | 11.31706 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 41776.79 | 5.82457 | 5.82457 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 |
7 | CAV_BAS | Cooling | Sensible | 70860.99 | 5.91978 | 5.91978 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 57212.75 | 1.20016 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368063.12 | 25.88310 | 25.88310 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16131.55 | 0.33839 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8219.44 | 0.57794 | 0.57794 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78772.78 | 5.53877 | 5.53877 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7452.11 | 0.15632 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8048.58 | 0.56573 | 0.56573 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.91978 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.37444 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29839 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61911 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79570 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27687E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.93312E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61911 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13408.53440 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93312E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 374.23354 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.71520 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31852 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27100 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18282 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84938 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19616E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.96069E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18282 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 363916.83064 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.96069E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12717.64532 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.03172 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31534 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61650 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84091 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20822E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69694E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.80757 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 77574.36737 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69694E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3018.52330 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16231 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20547 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17500 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20340 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54792 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85428E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05280E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33972 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9384.23717 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05280E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 365.09204 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47618 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10426 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.90000E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13138 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65437E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46778E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24299 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6709.84553 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46778E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.98476 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47404 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16202 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20342 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43206 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35154E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.55579E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42322 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11683.58994 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.55579E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 454.36718 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.85651 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.29000E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.00000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12996 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.59590E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.67304E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15987 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4421.95723 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.67304E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.18577 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.14748 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21424 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02884 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57130 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77840E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.33584E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.18927 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 198209.66824 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.33584E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7701.72096 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.85099 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92400E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.87854E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.77318 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 131590.07706 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.87854E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5112.93353 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.45458 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16523 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14000 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02364 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44060 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30595E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.29814E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.12664 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 196486.08736 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.29814E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7634.82653 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.13619 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.98129E-002 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.60000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30235 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.24215E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.71410E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.50009 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 124073.19894 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71410E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4821.16188 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28594 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18572 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15800 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20318 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49525 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05150E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.53105E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91747 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25284.75889 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.53105E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 982.22463 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60376 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.59652E-002 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.20000E-002 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13151 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97019E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.65000E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60547 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16685.67090 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.65000E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 648.16443 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60358 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14893 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20365 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39715 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55820E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.49046E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91073 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25099.20279 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.49046E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 975.02281 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82690 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.42439E-002 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.20000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13154 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.52258E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.51670E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58333 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16076.30608 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.51670E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 624.51018 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.57794 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.53877 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56573 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.88281 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.17174 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28726 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.34348 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28726 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.72584 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.72584 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.21325 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 59.15222 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.85328 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 118.30444 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 35.37422 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 99.88904 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 99.88904 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35414 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.17595 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28638 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.35190 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.82457 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.31706 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.31706 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51467 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.91978 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.91978 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.91978 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.91978 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.91978 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.91978 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.88281 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.88281 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.88281 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.88281 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.88310 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.88310 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.57794 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.57794 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.57794 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.57794 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.57794 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.57794 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.53877 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.53877 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.53877 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.53877 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.53877 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.53877 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56573 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56573 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56573 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56573 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56573 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.56573 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.72584 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 99.88904 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.31706 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.91978 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.88310 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.57794 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.53877 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.56573 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.72584 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.15816 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66790 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03016E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03016E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 167499.31229 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.79046E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.72584 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 44121.62607 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.65162E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 955.00779 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.72584 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.79046E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.94039E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.65162E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 99.88904 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.37073 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.65644 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.01215E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.01215E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1582419.56593 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.52570E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 99.88904 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 355226.89120 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.77060E-003 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7874.72236 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 99.88904 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.52570E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.05219E-005 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.77060E-003 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.31706 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.99826 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66785 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.01655E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.01655E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 174904.08895 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.00223E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.31706 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 34659.54418 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.58178E-004 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 779.89876 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.31706 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.00223E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.51955E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.58178E-004 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.91978 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.38626 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.11839 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14157E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14157E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 91137.27304 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60651E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.91978 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 245095.58346 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.36147E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7759.17487 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.91978 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60651E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82692E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.36147E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.88310 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.88310 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 473978.23288 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 251376.13705 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16077E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.88310 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.88310 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.88310 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.88310 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 473978.23288 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 473978.23288 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16131.54879 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.88310 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.88310 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 473978.23288 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16077E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16131.54879 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.39985E-004 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.57794 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57794 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10309.43518 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5518.02198 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.52477E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.57794 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.57794 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.57794 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.57794 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10309.43518 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10309.43518 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.57794 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57794 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10309.43518 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.52477E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.53877 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.53877 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 98848.57909 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 52894.24343 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42080E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.53877 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.53877 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.53877 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.53877 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 98848.57909 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 98848.57909 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7452.10725 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.53877 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.53877 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 98848.57909 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42080E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7452.10725 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56573 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56573 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10093.98420 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5401.99876 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47201E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56573 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56573 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56573 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56573 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10093.98420 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10093.98420 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56573 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56573 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10093.98420 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47201E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.76562E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9320.29399 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.76562E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.91874 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.76562E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.76562E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 242012.03364 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.15562E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.98674 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.15562E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 12390.98208 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1899707.97745 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1899707.98000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.15562E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.76562E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.91874 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.88281E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3226.37692 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.88281E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3226.37692 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.76562E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.92539E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1024011.91146 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1030244.02000 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.22312E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.76562E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.92539E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1024011.91146 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1030244.02000 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.22312E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.45282E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.74338 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.45282E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3668.72269 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.45282E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55202.18961 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20982.12553 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 598436.06088 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 584736.58000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.45282E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10446 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.53548 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10446 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 25606.50166 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 47.91103 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1223884.71523 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.58221 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 152985.58940 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 47.91103 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1223884.71523 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.58221 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 152985.58940 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.29550E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.29550E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18671.09 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 507046.15 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 108036.90 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13069.32 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9344.73 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16271.62 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6158.40 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 276045.07 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 183264.50 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 273644.65 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 172795.77 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35213.91 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23238.02 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34955.48 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22389.36 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 47626.48 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 395537.97 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 39660.66 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 262488.12 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 209095.77 | 140909.81 | 68185.96 | 0.67 | 29037.60 | 294.52 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1962761.40 | 1317852.81 | 644908.60 | 0.67 | 271269.06 | 2751.36 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 219435.64 | 148263.19 | 71172.44 | 0.68 | 30620.63 | 310.57 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 112105.06 | 76219.18 | 35885.88 | 0.68 | 14689.99 | 148.99 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.65 | 22.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.65 | 22.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2626750728 | 0.2401555114 | Pass | Pass | 1.4979102911 | 3.0337925506 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.5588642475E-002 | 0.1534532381 | Pass | Pass | 0.1742595460 | 0.3782180742 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.2104583924E-002 | 0.1151406395 | Pass | Pass | 0.1474716275 | 0.3506947929 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.3159084519E-002 | 5.7402799421E-002 | Pass | Pass | 0.2647047312 | 0.4358500037 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.4724554427E-002 | 0.1091820026 | Pass | Pass | 0.1736986823 | 0.3762781853 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1567045003 | 0.2403110131 | Pass | Pass | 0.1834977744 | 0.3929553540 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3637537461 | 0.6500059253 | Pass | Pass | 0.1898258544 | 0.4082947571 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1532802215 | 0.3247424709 | Pass | Pass | 0.1722796000 | 0.3635368259 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.2208380502E-002 | 6.3238912918E-002 | Pass | Pass | 0.1468877917 | 0.3460661753 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1349202603 | 0.1604876013 | Pass | Pass | 0.1490721052 | 0.3559458420 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4050646586 | 0.7055966259 | Pass | Pass | 0.1574489226 | 0.3799341722 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1258698737 | 0.1578444622 | Pass | Pass | 0.1443206718 | 0.3407095077 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1144426014 | 0.1527078015 | Pass | Pass | 40.2003362830 | 196.3606554640 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1316348217 | 0.1437810520 | Pass | Pass | 18.6090440413 | 110.6104474038 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3135029665 | 0.4559051324 | Pass | Pass | 0.2736837698 | 0.4474034731 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1298135572 | 0.1362311720 | Pass | Pass | 0.2694084731 | 0.4376732981 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3544557712E-002 | 3.0304476225E-002 | Pass | Pass | 0.4252893810 | 1.2762198164 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9317432830E-002 | 5.8017590118E-002 | Pass | Pass | 0.5292733582 | 4.4839995045 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.7901056156E-002 | 8.2330456979E-002 | Pass | Pass | 0.3290243572 | 0.7066044898 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.5100164934E-006 | 6.4968571504E-006 | Pass | Pass | 7.8086932103E-003 | 1.0280129344E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3593556530E-003 | 2.5604913943E-002 | Pass | Pass | 0.3158325357 | 1.5247890227 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5980429664E-002 | 3.1658384317E-002 | Pass | Pass | 0.1929503474 | 1.0113303769 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.5153403280E-005 | 7.6306709437E-005 | Pass | Pass | 9.9133561756E-005 | 1.1105142525E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8505.49 | 146.30 | 0.00 | 24277.75 | 15396.36 | 48325.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.93 | 0.0000 | Y | 7.45 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.88 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.72 | 0.0000 | Y | 7.38 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.71 | 0.0000 | Y | 4.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 74.44 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 47.88 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.70 | 0.0000 | Y | 73.77 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.69 | 0.0000 | Y | 47.52 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.90 | 0.0000 | Y | 7.44 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.86 | 0.0000 | Y | 4.79 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.70 | 0.0000 | Y | 7.38 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 21.69 | 0.0000 | Y | 4.75 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 539.66 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.81 | 41.81 | 101.67 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.71 | 62.76 | 10.84 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.71 | 46.63 | 150.69 | |
Exterior Lighting Total | 31088.59 | 263.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2009750.90 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1899707.98 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1030244.02 | 5.33 | 1055260.77 | 6.30 | 6.65 | 22.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1030244.02 | 5.33 | 1055260.77 | 6.30 | 6.65 | 22.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 584736.58 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1223884.72 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1223884.72 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 167499.31 | 209095.77 | 140909.81 | 68185.96 | 0.67 | - | 29037.60 | 294.52 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1582419.57 | 1962761.40 | 1317852.81 | 644908.60 | 0.67 | - | 271269.06 | 2751.36 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 174904.09 | 219435.64 | 148263.19 | 71172.44 | 0.68 | - | 30620.63 | 310.57 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 91137.27 | 112105.06 | 76219.18 | 35885.88 | 0.68 | - | 14689.99 | 148.99 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 473978.23 | 251376.14 | 222602.10 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10309.44 | 5518.02 | 4791.41 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 98848.58 | 52894.24 | 45954.34 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10093.98 | 5402.00 | 4691.99 | 0.54 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 13408.53 | 18671.09 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 363916.83 | 507046.15 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 77574.37 | 108036.90 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9384.24 | 13069.32 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6709.85 | 9344.73 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11683.59 | 16271.62 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4421.96 | 6158.40 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 198209.67 | 276045.07 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 131590.08 | 183264.50 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 196486.09 | 273644.65 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 124073.20 | 172795.77 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 25284.76 | 35213.91 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16685.67 | 23238.02 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25099.20 | 34955.48 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 16076.31 | 22389.36 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 44121.63 | 47626.48 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 355226.89 | 395537.97 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 34659.54 | 39660.66 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 245095.58 | 262488.12 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 473978.23 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10309.44 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 98848.58 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10093.98 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 16131.55 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7452.11 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.73 | 23054.80 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 99.89 | 215854.90 | 2160.95 | 1.00 | 1.08 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.32 | 24325.62 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.92 | 10037.91 | 1695.65 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.88 | 42687.62 | 1649.25 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 647.36 | 1120.11 | 1.00 | 1.54 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.54 | 6204.02 | 1120.11 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.57 | 633.68 | 1120.11 | 1.00 | 1.55 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.057656 | 9320.29 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.041556 | 12390.98 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028828 | 3226.38 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028828 | 3226.38 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014528 | 3668.72 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.104462 | 25606.50 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 67423.63 | 67423.63 | 24.26 | 5.920 | 5.920 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00752 | 25.11 | 0.00568 | 1.200 | 0.00 |
CORE_BOTTOM | 72603.45 | 72603.45 | 29.09 | 6.374 | 6.374 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 25.11 | 0.00568 | 1.078 | 0.00 |
CORE_MID | 680317.41 | 680317.41 | 272.55 | 59.715 | 59.715 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 25.11 | 0.00568 | 10.778 | 0.00 |
CORE_TOP | 68093.13 | 68093.13 | 27.28 | 6.032 | 6.032 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00745 | 35.10 | 0.00570 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13121.89 | 13121.89 | 41.87 | 1.162 | 1.162 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00726 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16665.55 | 16665.55 | 82.51 | 1.476 | 1.476 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00713 | 27.68 | 0.00569 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16641.18 | 16641.18 | 53.10 | 1.474 | 1.474 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00720 | 34.54 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20959.39 | 20959.39 | 103.77 | 1.857 | 1.857 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00710 | 33.39 | 0.00570 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 125851.54 | 125851.54 | 401.55 | 11.147 | 11.147 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00722 | 35.10 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 178954.45 | 178954.45 | 886.02 | 15.851 | 15.851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00710 | 28.44 | 0.00569 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 163188.03 | 163188.03 | 520.67 | 14.455 | 14.455 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00717 | 34.76 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 193463.93 | 193463.93 | 957.86 | 17.136 | 17.136 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00709 | 33.21 | 0.00570 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14517.93 | 14517.93 | 46.32 | 1.286 | 1.286 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00718 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18106.23 | 18106.23 | 89.65 | 1.604 | 1.604 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00709 | 28.82 | 0.00569 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18104.10 | 18104.10 | 57.76 | 1.604 | 1.604 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00715 | 34.88 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20625.43 | 20625.43 | 102.12 | 1.827 | 1.827 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00708 | 33.21 | 0.00570 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8272.19 | 8272.19 | 228.50 | 0.578 | 0.578 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79276.72 | 79276.72 | 2189.80 | 5.539 | 5.539 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8097.32 | 8097.32 | 223.67 | 0.566 | 0.566 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370471.07 | 370471.07 | 472.73 | 25.883 | 25.883 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 22.82 | 0.00568 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 24.54 | 0.00234 | -7.90 | 0.00234 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 19.60 | 22.06 | 0.00234 | -7.90 | 0.00234 | 1.078 | 0.00 |
CORE_MID | 229899.81 | 229899.81 | 92.10 | 11.785 | 11.785 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 10.778 | 0.00 |
CORE_TOP | 54323.64 | 54323.64 | 21.76 | 2.808 | 2.808 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6574.89 | 6574.89 | 20.98 | 0.340 | 0.340 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00733 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4699.96 | 4699.96 | 23.27 | 0.243 | 0.243 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 8182.00 | 8182.00 | 26.11 | 0.423 | 0.423 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3101.20 | 3101.20 | 15.35 | 0.160 | 0.160 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00683 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 138724.39 | 138724.39 | 442.63 | 7.189 | 7.189 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 92096.05 | 92096.05 | 455.98 | 4.773 | 4.773 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 137519.43 | 137519.43 | 438.77 | 7.127 | 7.127 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 86840.69 | 86840.69 | 429.96 | 4.500 | 4.500 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17693.44 | 17693.44 | 56.45 | 0.917 | 0.917 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11675.95 | 11675.95 | 57.81 | 0.605 | 0.605 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17563.71 | 17563.71 | 56.04 | 0.911 | 0.911 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11249.87 | 11249.87 | 55.70 | 0.583 | 0.583 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.44 | 0.00700 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | 18.00 | 23.19 | 0.00401 | -7.90 | 0.00234 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.45 | 0.00285 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 12:20:00 | 18.00 | 27.00 | 0.00700 | -7.90 | 0.00234 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.73 | 10.73 | 2.24 | 2.24 | 10.7258 | 2.2873 | 10.7258 | 0.2132 | 0.3000 |
VAV_MID WITH REHEAT | 99.89 | 99.89 | 35.37 | 35.37 | 99.8890 | 35.3742 | 99.8890 | 0.3541 | 0.3000 |
VAV_TOP WITH REHEAT | 11.32 | 11.32 | 5.82 | 5.82 | 11.3171 | 5.8246 | 11.3171 | 0.5147 | 0.3000 |
CAV_BAS | 5.92 | 5.92 | 1.20 | 1.20 | 5.9198 | 5.9198 | 5.9198 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.88 | 25.88 | 0.34 | 0.34 | 25.8831 | 25.8828 | 25.8831 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.58 | 0.58 | 0.02 | 0.02 | 0.5779 | 0.5779 | 0.5779 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.54 | 5.54 | 0.16 | 0.16 | 5.5388 | 5.5388 | 5.5388 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.57 | 0.57 | 0.02 | 0.02 | 0.5657 | 0.5657 | 0.5657 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 13408.534 | 13408.534 | 1.619107 | 0.00029331 | 374.234 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 13408.53 | 13408.53 | 1.619107 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 13431.55 | 13431.55 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 363916.831 | 363916.831 | 16.182820 | 0.00796069 | 12717.645 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 363916.83 | 363916.83 | 16.182820 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 229899.81 | 0.00 | 364784.11 | 364784.11 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 77574.367 | 77574.367 | 2.807572 | 0.00169694 | 3018.523 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 77574.37 | 77574.37 | 2.807572 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 54323.64 | 0.00 | 77739.54 | 77739.54 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9384.237 | 9384.237 | 0.339722 | 0.00020528 | 365.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9384.24 | 9384.24 | 0.339722 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00732866 | 39.0129 | 6574.89 | 0.00 | 9404.22 | 9404.22 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6709.846 | 6709.846 | 0.242993 | 0.00014678 | 260.985 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6709.85 | 6709.85 | 0.242993 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00744053 | 39.6010 | 4699.96 | 0.00 | 6724.13 | 6724.13 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11683.590 | 11683.590 | 0.423222 | 0.00025558 | 454.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11683.59 | 11683.59 | 0.423222 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00757198 | 40.2915 | 8182.00 | 0.00 | 11708.47 | 11708.47 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4421.957 | 4421.957 | 0.159866 | 0.00009673 | 172.186 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4421.96 | 4421.96 | 0.159866 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00683356 | 36.4069 | 3101.20 | 0.00 | 4431.37 | 4431.37 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 198209.668 | 198209.668 | 7.189270 | 0.00433584 | 7701.721 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 198209.67 | 198209.67 | 7.189270 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00762491 | 40.5705 | 138724.39 | 0.00 | 198631.83 | 198631.83 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 131590.077 | 131590.077 | 4.773179 | 0.00287854 | 5112.934 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 131590.08 | 131590.08 | 4.773179 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00762524 | 40.5722 | 92096.05 | 0.00 | 131870.35 | 131870.35 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 196486.087 | 196486.087 | 7.126641 | 0.00429814 | 7634.827 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 196486.09 | 196486.09 | 7.126641 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00762127 | 40.5513 | 137519.43 | 0.00 | 196904.57 | 196904.57 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 124073.199 | 124073.199 | 4.500090 | 0.00271410 | 4821.162 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 124073.20 | 124073.20 | 4.500090 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00759987 | 40.4390 | 86840.69 | 0.00 | 124337.46 | 124337.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 25284.759 | 25284.759 | 0.917467 | 0.00055310 | 982.225 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25284.76 | 25284.76 | 0.917467 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764185 | 40.6601 | 17693.44 | 0.00 | 25338.61 | 25338.61 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16685.671 | 16685.671 | 0.605469 | 0.00036500 | 648.164 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16685.67 | 16685.67 | 0.605469 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763857 | 40.6429 | 11675.95 | 0.00 | 16721.21 | 16721.21 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 25099.203 | 25099.203 | 0.910725 | 0.00054905 | 975.023 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25099.20 | 25099.20 | 0.910725 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763932 | 40.6468 | 17563.71 | 0.00 | 25152.66 | 25152.66 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 16076.306 | 16076.306 | 0.583332 | 0.00035167 | 624.510 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16076.31 | 16076.31 | 0.583332 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00762550 | 40.5743 | 11249.87 | 0.00 | 16110.55 | 16110.55 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 167499.312 | -999.000 | 10.725836 | 0.00479046 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 167499.31 | 167499.31 | 10.725836 | 26.16 | 13.90 | 0.00703016 | 10.67 | 8.01 | 0.00703016 | 35.10 | 0.00569938 | 15.77 | 18.9309 | 24.00 | 0.00735153 | 32.6108 | 117844.07 | 0.00 | 141872.69 | 141872.69 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 44121.626 | 44121.626 | 3.217751 | 0.00096516 | 955.008 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44121.63 | 44121.63 | 3.217751 | -0.98 | -2.32 | 0.00330737 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 63.1031 | 21.31 | 0.00595512 | 31.1677 | 22558.05 | 0.00 | 41480.03 | 41480.03 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1582419.566 | -999.000 | 99.889043 | 0.04525700 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1582419.57 | 1582419.56 | 99.889043 | 26.37 | 13.96 | 0.00701215 | 10.66 | 7.99 | 0.00701215 | 35.10 | 0.00569938 | 15.77 | 20.3286 | 24.00 | 0.00736886 | 32.6866 | 1072916.17 | 0.00 | 1340351.45 | 1340351.45 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 355226.891 | 355226.891 | 29.966713 | 0.00777060 | 7874.722 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 355226.89 | 355226.89 | 29.966713 | 0.89 | -0.40 | 0.00398687 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 67.7619 | 18.20 | 0.00731557 | 46.3335 | 213292.01 | 0.00 | 344552.46 | 344552.46 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 174904.089 | -999.000 | 11.317059 | 0.00500223 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 174904.09 | 174904.09 | 11.317059 | 26.00 | 13.84 | 0.00701655 | 10.67 | 8.00 | 0.00701655 | 35.10 | 0.00569938 | 15.77 | 17.9419 | 24.00 | 0.00730589 | 32.4105 | 127275.10 | 0.00 | 147770.44 | 147770.44 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 34659.544 | 34659.544 | 3.395118 | 0.00075818 | 779.899 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34659.54 | 34659.54 | 3.395118 | 2.54 | 1.12 | 0.00441125 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 59.8065 | 17.60 | 0.00706119 | 46.4718 | 26493.01 | 0.00 | 34549.59 | 34549.59 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 91137.273 | -999.000 | 5.919783 | 0.00260651 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 91137.27 | 91137.27 | 5.919783 | 26.39 | 14.07 | 0.00714157 | 11.12 | 8.32 | 0.00714157 | 34.43 | 0.00569833 | 15.56 | 20.2737 | 24.00 | 0.00757025 | 33.5698 | 59162.66 | 0.00 | 77622.73 | 77622.73 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 245095.583 | 245095.583 | 5.919783 | 0.00536147 | 7759.175 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 245095.58 | 245095.58 | 5.919783 | -1.60 | -4.13 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 20.2737 | 24.60 | 0.00234317 | 10.1075 | 0.00 | 0.00 | 188078.01 | 188078.01 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 473978.233 | 251376.137 | 25.883100 | 0.01160770 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 404560.13 | 403468.12 | -999.0 | 28.80 | 14.79 | 0.00702472 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | -999.0000 | 27.00 | 0.00704229 | 26.1562 | 370058.48 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10309.435 | 5518.022 | 0.577943 | 0.00025248 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8756.80 | 8708.55 | -999.0 | 28.24 | 14.62 | 0.00704939 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708712 | 26.3189 | 8270.39 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98848.579 | 52894.243 | 5.538769 | 0.00242080 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 83969.07 | 83488.00 | -999.0 | 28.25 | 14.63 | 0.00705138 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00709087 | 26.3329 | 79237.98 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10093.984 | 5401.999 | 0.565727 | 0.00024720 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8574.18 | 8525.96 | -999.0 | 28.25 | 14.62 | 0.00705043 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708903 | 26.3260 | 8097.32 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 473978.233 | 473978.233 | 25.883100 | 0.01160770 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 473978.23 | 473978.23 | 25.883100 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3074 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10309.435 | 10309.435 | 0.577943 | 0.00025248 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10309.44 | 10309.44 | 0.577943 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7048 | 26.80 | 0.00700000 | 26.3041 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98848.579 | 98848.579 | 5.538769 | 0.00242080 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 98848.58 | 98848.58 | 5.538769 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8223 | 24.36 | 0.00401315 | 17.5113 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10093.984 | 10093.984 | 0.565727 | 0.00024720 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10093.98 | 10093.98 | 0.565727 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7632 | 23.27 | 0.00284683 | 13.2877 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16131.55 | 16131.55 | 25.883100 | -0.10 | -0.10 | 0.00693912 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3074 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.577943 | -0.21 | -0.21 | 0.00687404 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7048 | 26.80 | 0.00700000 | 26.3041 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7452.11 | 7452.11 | 5.538769 | -0.22 | -0.98 | 0.00396602 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8223 | 24.36 | 0.00401315 | 17.5113 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.565727 | -0.22 | -2.62 | 0.00283291 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7632 | 23.27 | 0.00284683 | 13.2877 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 13408.534 | 13408.534 | 1.619107 | 0.00029331 | 374.234 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 0.6919 | 0.705821 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | Sensible | 13408.53 | 13408.53 | 1.0000 | 1.60357803 | 1.619107 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.29328214 | 60.00 | 48.89 | 11.11 | 0.000 | 13408.53 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 13431.55 | 13431.55 | 1.60357803 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 363916.831 | 363916.831 | 16.182820 | 0.00796069 | 12717.645 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 18.7785 | 19.156462 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 363916.83 | 363916.83 | 1.0000 | 16.02760921 | 16.182820 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 7.95987871 | 60.00 | 48.89 | 11.11 | 0.000 | 363916.83 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.82 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 229899.81 | 0.00 | 364784.11 | 364784.11 | 16.02760921 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.12 | 19.69 | 0.00800000 | 55819.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 77574.367 | 77574.367 | 2.807572 | 0.00169694 | 3018.523 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 4.0029 | 4.083489 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 77574.37 | 77574.37 | 1.0000 | 2.78064417 | 2.807572 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.69676834 | 60.00 | 48.89 | 11.11 | 0.000 | 77574.37 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 54323.64 | 0.00 | 77739.54 | 77739.54 | 2.78064417 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9384.237 | 9384.237 | 0.339722 | 0.00020528 | 365.092 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 0.4842 | 0.493983 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9384.24 | 9384.24 | 1.0000 | 0.33646392 | 0.339722 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.20525951 | 60.00 | 48.89 | 11.11 | 0.000 | 9384.24 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00732866 | 21.00 | 0.00732866 | 39.0129 | 6574.89 | 0.00 | 9404.22 | 9404.22 | 0.33646392 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61010.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6709.846 | 6709.846 | 0.242993 | 0.00014678 | 260.985 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 0.3462 | 0.353204 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6709.85 | 6709.85 | 1.0000 | 0.24066194 | 0.242993 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.14676308 | 60.00 | 48.89 | 11.11 | 0.000 | 6709.85 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00744053 | 21.00 | 0.00744053 | 39.6010 | 4699.96 | 0.00 | 6724.13 | 6724.13 | 0.24066194 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11683.590 | 11683.590 | 0.423222 | 0.00025558 | 454.367 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 0.6029 | 0.615020 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11683.59 | 11683.59 | 1.0000 | 0.41916237 | 0.423222 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.25555278 | 60.00 | 48.89 | 11.11 | 0.000 | 11683.59 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00757198 | 21.00 | 0.00757198 | 40.2915 | 8182.00 | 0.00 | 11708.47 | 11708.47 | 0.41916237 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4421.957 | 4421.957 | 0.159866 | 0.00009673 | 172.186 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 0.2282 | 0.232770 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4421.96 | 4421.96 | 1.0000 | 0.15833257 | 0.159866 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09672057 | 60.00 | 48.89 | 11.11 | 0.000 | 4421.96 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.86 | 0.00683356 | 21.00 | 0.00683356 | 36.4069 | 3101.20 | 0.00 | 4431.37 | 4431.37 | 0.15833257 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61047.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 198209.668 | 198209.668 | 7.189270 | 0.00433584 | 7701.721 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 10.2279 | 10.433691 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 198209.67 | 198209.67 | 1.0000 | 7.12031653 | 7.189270 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 4.33539970 | 60.00 | 48.89 | 11.11 | 0.000 | 198209.67 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00762491 | 21.00 | 0.00762491 | 40.5705 | 138724.39 | 0.00 | 198631.83 | 198631.83 | 7.12031653 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60956.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 131590.077 | 131590.077 | 4.773179 | 0.00287854 | 5112.934 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 6.7902 | 6.926858 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 131590.08 | 131590.08 | 1.0000 | 4.72739933 | 4.773179 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.87824295 | 60.00 | 48.89 | 11.11 | 0.000 | 131590.08 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00762524 | 21.00 | 0.00762524 | 40.5722 | 92096.05 | 0.00 | 131870.35 | 131870.35 | 4.72739933 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60954.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 196486.087 | 196486.087 | 7.126641 | 0.00429814 | 7634.827 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 10.1389 | 10.342963 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 196486.09 | 196486.09 | 1.0000 | 7.05828874 | 7.126641 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 4.29770017 | 60.00 | 48.89 | 11.11 | 0.000 | 196486.09 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00762127 | 21.00 | 0.00762127 | 40.5513 | 137519.43 | 0.00 | 196904.57 | 196904.57 | 7.05828874 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60956.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 124073.199 | 124073.199 | 4.500090 | 0.00271410 | 4821.162 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 6.4023 | 6.531172 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 124073.20 | 124073.20 | 1.0000 | 4.45692925 | 4.500090 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.71382781 | 60.00 | 48.89 | 11.11 | 0.000 | 124073.20 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00759987 | 21.00 | 0.00759987 | 40.4390 | 86840.69 | 0.00 | 124337.46 | 124337.46 | 4.45692925 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60957.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25284.759 | 25284.759 | 0.917467 | 0.00055310 | 982.225 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 1.3047 | 1.330981 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25284.76 | 25284.76 | 1.0000 | 0.90866782 | 0.917467 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.55304838 | 60.00 | 48.89 | 11.11 | 0.000 | 25284.76 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00764185 | 21.00 | 0.00764185 | 40.6601 | 17693.44 | 0.00 | 25338.61 | 25338.61 | 0.90866782 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60945.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16685.671 | 16685.671 | 0.605469 | 0.00036500 | 648.164 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 0.8610 | 0.878328 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16685.67 | 16685.67 | 1.0000 | 0.59966162 | 0.605469 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.36496228 | 60.00 | 48.89 | 11.11 | 0.000 | 16685.67 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763857 | 21.00 | 0.00763857 | 40.6429 | 11675.95 | 0.00 | 16721.21 | 16721.21 | 0.59966162 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60944.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25099.203 | 25099.203 | 0.910725 | 0.00054905 | 975.023 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 1.2951 | 1.321214 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25099.20 | 25099.20 | 1.0000 | 0.90199026 | 0.910725 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.54898975 | 60.00 | 48.89 | 11.11 | 0.000 | 25099.20 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763932 | 21.00 | 0.00763932 | 40.6468 | 17563.71 | 0.00 | 25152.66 | 25152.66 | 0.90199026 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60945.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16076.306 | 16076.306 | 0.583332 | 0.00035167 | 624.510 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 0.8296 | 0.846251 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16076.31 | 16076.31 | 1.0000 | 0.57773763 | 0.583332 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.35163377 | 60.00 | 48.89 | 11.11 | 0.000 | 16076.31 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00762550 | 21.00 | 0.00762550 | 40.5743 | 11249.87 | 0.00 | 16110.55 | 16110.55 | 0.57773763 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60945.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 167499.312 | -999.000 | 10.725836 | 0.00479046 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9087 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.725836 | 10.62296346 | 4197.9300 | 999.8980 | 57.65032615 | 15.00 | 6.67 | 8.33 | 2015960.24 | 8.3087 | 8.308661 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 167499.31 | 167499.31 | 1.0000 | 10.62296346 | 10.725836 | 26.16 | 13.90 | 0.00703016 | 44208.6 | 10.67 | 8.01 | 0.00703016 | 28441.0 | 4.78997045 | 6.67 | 15.00 | 8.33 | 23054.805 | 144444.51 | 35.10 | 0.00569938 | 15.77 | 2.03050000 | 18.9309 | 24.00 | 0.00735153 | 24.00 | 0.00735153 | 32.6108 | 117844.07 | 0.00 | 141872.69 | 141872.69 | 10.62296346 | 26.16 | 15.88 | 0.00703016 | 44208.6 | 13.04 | 10.69 | 0.00703016 | 30853.3 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 44121.626 | 44121.626 | 3.217751 | 0.00096516 | 955.008 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.725836 | 10.62296346 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 2.2767 | 2.322548 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 44121.63 | 44121.63 | 1.0000 | 3.18688904 | 3.217751 | -0.98 | -2.32 | 0.00330737 | 7283.0 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.96506334 | 60.00 | 48.89 | 11.11 | 0.000 | 44121.63 | -7.90 | 0.00234317 | -7.90 | 2.03050000 | 63.1031 | 10.86 | 0.00495640 | 21.31 | 0.00595512 | 31.1677 | 22558.05 | 0.00 | 41480.03 | 41480.03 | 3.18688904 | 2.80 | 0.97 | 0.00330737 | 11102.3 | 15.67 | 7.74 | 0.00330737 | 24118.1 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1582419.566 | -999.000 | 99.889043 | 0.04525700 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8752 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 99.889043 | 98.93099687 | 4197.9300 | 999.8980 | 57.65032615 | 15.00 | 6.67 | 8.33 | 2015960.24 | 78.4946 | 78.494582 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1582419.57 | 1582419.56 | 1.0000 | 98.93099687 | 99.889043 | 26.37 | 13.96 | 0.00701215 | 44379.1 | 10.66 | 7.99 | 0.00701215 | 28383.9 | 45.25238259 | 6.67 | 15.00 | 8.33 | 215854.903 | 1366564.66 | 35.10 | 0.00569938 | 15.77 | 20.30600000 | 20.3286 | 24.00 | 0.00736886 | 24.00 | 0.00736886 | 32.6866 | 1072916.17 | 0.00 | 1340351.45 | 1340351.45 | 98.93099687 | 26.37 | 15.94 | 0.00701215 | 44379.1 | 13.06 | 10.68 | 0.00701215 | 30830.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 355226.891 | 355226.891 | 29.966713 | 0.00777060 | 7874.722 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 99.889043 | 98.93099687 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 18.3301 | 18.699026 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 355226.89 | 355226.89 | 1.0000 | 29.67929906 | 29.966713 | 0.89 | -0.40 | 0.00398687 | 10870.8 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 7.76980543 | 60.00 | 48.89 | 11.11 | 0.000 | 355226.89 | -7.90 | 0.00234317 | -7.90 | 20.30600000 | 67.7619 | 19.36 | 0.00744177 | 18.20 | 0.00731557 | 46.3335 | 213292.01 | 0.00 | 344552.46 | 344552.46 | 29.67929906 | 2.80 | 1.93 | 0.00398687 | 12805.2 | 14.27 | 7.87 | 0.00398687 | 24414.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 174904.089 | -999.000 | 11.317059 | 0.00500223 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8834 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.317059 | 11.20851584 | 4197.9300 | 999.8980 | 57.65032615 | 15.00 | 6.67 | 8.33 | 2015960.24 | 8.6760 | 8.675969 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 174904.09 | 174904.09 | 1.0000 | 11.20851584 | 11.317059 | 26.00 | 13.84 | 0.00701655 | 44011.2 | 10.67 | 8.00 | 0.00701655 | 28406.6 | 5.00172452 | 6.67 | 15.00 | 8.33 | 24325.617 | 150578.47 | 35.10 | 0.00569938 | 15.77 | 2.03050000 | 17.9419 | 24.00 | 0.00730589 | 24.00 | 0.00730589 | 32.4105 | 127275.10 | 0.00 | 147770.44 | 147770.44 | 11.20851584 | 26.00 | 15.81 | 0.00701655 | 44011.2 | 13.05 | 10.68 | 0.00701655 | 30827.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 34659.544 | 34659.544 | 3.395118 | 0.00075818 | 779.899 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.317059 | 11.20851584 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 1.7885 | 1.824467 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34659.54 | 34659.54 | 1.0000 | 3.36255475 | 3.395118 | 2.54 | 1.12 | 0.00441125 | 13607.8 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.75810115 | 60.00 | 48.89 | 11.11 | 0.000 | 34659.54 | -7.90 | 0.00234317 | -7.90 | 2.03050000 | 59.8065 | 18.08 | 0.00748847 | 17.60 | 0.00706119 | 46.4718 | 26493.01 | 0.00 | 34549.59 | 34549.59 | 3.36255475 | 2.80 | 2.51 | 0.00441125 | 13868.8 | 12.94 | 7.74 | 0.00441125 | 24143.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91137.273 | -999.000 | 5.919783 | 0.00260651 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1158 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 5.919783 | 5.86300556 | 4197.9300 | 999.8980 | 57.65032615 | 15.00 | 6.67 | 8.33 | 2015960.24 | 4.5208 | 4.520787 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 91137.27 | 91137.27 | 1.0000 | 5.86300556 | 5.919783 | 26.39 | 14.07 | 0.00714157 | 44724.9 | 11.12 | 8.32 | 0.00714157 | 29180.4 | 2.60624858 | 6.67 | 15.00 | 8.33 | 10037.905 | 81099.37 | 34.43 | 0.00569833 | 15.56 | 1.20015641 | 20.2737 | 24.00 | 0.00757025 | 24.00 | 0.00757025 | 33.5698 | 59162.66 | 0.00 | 77622.73 | 77622.73 | 5.86300556 | 26.39 | 16.06 | 0.00714157 | 44724.9 | 13.38 | 10.96 | 0.00714157 | 31485.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 245095.583 | 245095.583 | 5.919783 | 0.00536147 | 7759.175 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 5.919783 | 5.86300556 | 4197.9300 | 999.8980 | 41.55192563 | 48.89 | 60.00 | 11.11 | 1937940.36 | 12.6472 | 12.901750 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 245095.58 | 245095.58 | 1.0000 | 5.86300556 | 5.919783 | -1.60 | -4.13 | 0.00234317 | 4243.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 5.36092577 | 60.00 | 48.89 | 11.11 | 0.000 | 245095.58 | -7.90 | 0.00234317 | -7.90 | 1.20015641 | 20.2737 | 0.00 | 0.00234317 | 24.60 | 0.00234317 | 10.1075 | 0.00 | 0.00 | 188078.01 | 188078.01 | 5.86300556 | 12.80 | 5.14 | 0.00234317 | 18777.8 | 44.59 | 18.27 | 0.00234317 | 50856.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 473978.233 | 251376.137 | 25.883100 | 0.01160770 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8986 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 404560.13 | 403468.12 | 0.8535 | -999.0 | -999.0 | 28.80 | 14.79 | 0.00702472 | 46881.4 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 404560.13 | 35.10 | 0.00569938 | 15.77 | 0.33839277 | -999.0000 | 27.00 | 0.00704229 | 27.00 | 0.00704229 | 26.1562 | 370058.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10309.435 | 5518.022 | 0.577943 | 0.00025248 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9445 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8756.80 | 8708.55 | 0.8494 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704939 | 46381.0 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8756.80 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708712 | 27.00 | 0.00708712 | 26.3189 | 8270.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 98848.579 | 52894.243 | 5.538769 | 0.00242080 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9482 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 83969.07 | 83488.00 | 0.8495 | -999.0 | -999.0 | 28.25 | 14.63 | 0.00705138 | 46390.2 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83969.07 | 30.51 | 0.00569229 | 14.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709087 | 27.00 | 0.00709087 | 26.3329 | 79237.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10093.984 | 5401.999 | 0.565727 | 0.00024720 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9464 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8574.18 | 8525.96 | 0.8494 | -999.0 | -999.0 | 28.25 | 14.62 | 0.00705043 | 46385.7 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8574.18 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708903 | 27.00 | 0.00708903 | 26.3260 | 8097.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 473978.233 | 473978.233 | 25.883100 | 0.01160770 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 473978.23 | 473978.23 | 1.0000 | 25.63485229 | 25.883100 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 473978.23 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.3074 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10309.435 | 10309.435 | 0.577943 | 0.00025248 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10309.44 | 10309.44 | 1.0000 | 0.57239960 | 0.577943 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10309.44 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7048 | 0.00 | 0.00700000 | 26.80 | 0.00700000 | 26.3041 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98848.579 | 98848.579 | 5.538769 | 0.00242080 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 98848.58 | 98848.58 | 1.0000 | 5.48564638 | 5.538769 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98848.58 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.8223 | 0.00 | 0.00401315 | 24.36 | 0.00401315 | 17.5113 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10093.984 | 10093.984 | 0.565727 | 0.00024720 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10093.98 | 10093.98 | 1.0000 | 0.56030107 | 0.565727 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10093.98 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7632 | 0.00 | 0.00284683 | 23.27 | 0.00284683 | 13.2877 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.883100 | 25.63485229 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16131.55 | 16131.55 | 1.0000 | 25.63485229 | 25.883100 | -0.10 | -0.10 | 0.00693912 | 17249.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16131.55 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.3074 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.577943 | 0.57239960 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.57239960 | 0.577943 | -0.21 | -0.21 | 0.00687404 | 16974.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7048 | 0.00 | 0.00700000 | 26.80 | 0.00700000 | 26.3041 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.538769 | 5.48564638 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7452.11 | 7452.11 | 1.0000 | 5.48564638 | 5.538769 | -0.22 | -0.98 | 0.00396602 | 9693.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7452.11 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.8223 | 0.00 | 0.00401315 | 24.36 | 0.00401315 | 17.5113 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.565727 | 0.56030107 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.56030107 | 0.565727 | -0.22 | -2.62 | 0.00283291 | 6864.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7632 | 0.00 | 0.00284683 | 23.27 | 0.00284683 | 13.2877 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.73 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 99.89 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.32 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.92 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 25.88 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2301.00 | 1856.83 | 217.50 |
CORE_BOTTOM | 2103.33 | 1598.50 | 264.17 |
CORE_MID | 1640.67 | 3322.33 | 295.17 |
CORE_TOP | 2071.50 | 3672.83 | 703.67 |
PERIMETER_BOT_ZN_3 | 1943.67 | 3301.67 | 274.67 |
PERIMETER_BOT_ZN_2 | 2554.83 | 2690.00 | 415.83 |
PERIMETER_BOT_ZN_1 | 2971.17 | 2180.00 | 480.50 |
PERIMETER_BOT_ZN_4 | 3155.67 | 1741.33 | 531.00 |
PERIMETER_MID_ZN_3 | 2725.33 | 3813.50 | 1275.00 |
PERIMETER_MID_ZN_2 | 2415.67 | 2692.17 | 809.33 |
PERIMETER_MID_ZN_1 | 3002.50 | 2525.00 | 748.00 |
PERIMETER_MID_ZN_4 | 2836.83 | 3002.83 | 825.50 |
PERIMETER_TOP_ZN_3 | 3346.00 | 3949.67 | 1968.00 |
PERIMETER_TOP_ZN_2 | 3222.17 | 3281.83 | 1359.50 |
PERIMETER_TOP_ZN_1 | 3173.67 | 2763.67 | 1038.83 |
PERIMETER_TOP_ZN_4 | 3252.00 | 3280.50 | 1386.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 538.00 | 538.00 |
DATACENTER_MID_ZN_6 | 5840.50 | 129.17 | 129.17 |
DATACENTER_TOP_ZN_6 | 5286.33 | 347.00 | 232.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5821.33 | 5821.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5933.67 | 5840.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 50.83 | 0.00 | 4.17 |
CORE_BOTTOM | 0.00 | 4.83 | 0.00 | 0.67 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.50 | 0.17 | 0.00 | 0.17 |
PERIMETER_BOT_ZN_3 | 0.00 | 20.17 | 0.00 | 14.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 82.83 | 0.00 | 77.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 264.67 | 0.00 | 257.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 202.00 | 0.00 | 97.67 |
PERIMETER_MID_ZN_3 | 8.67 | 11.83 | 0.33 | 8.50 |
PERIMETER_MID_ZN_2 | 7.00 | 78.83 | 0.00 | 72.17 |
PERIMETER_MID_ZN_1 | 2.50 | 390.17 | 0.17 | 385.33 |
PERIMETER_MID_ZN_4 | 2.50 | 73.33 | 0.00 | 45.00 |
PERIMETER_TOP_ZN_3 | 57.17 | 27.17 | 8.83 | 20.00 |
PERIMETER_TOP_ZN_2 | 39.83 | 79.83 | 1.67 | 68.33 |
PERIMETER_TOP_ZN_1 | 26.67 | 188.67 | 0.17 | 179.67 |
PERIMETER_TOP_ZN_4 | 25.50 | 79.50 | 0.00 | 48.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 79.00 | 0.00 | 64.33 |
DATACENTER_MID_ZN_6 | 0.00 | 52.17 | 0.00 | 41.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 39.67 | 0.00 | 28.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 396.17 | 0.00 | 349.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 64.67 | 1148.67 | 9.00 | 939.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 149.60 | 6779.02 | 1.378 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.32 | 134.35 | 6849.35 | 0.960 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.32 | 134.35 | 6849.35 | 0.716 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.32 | 134.35 | 6849.35 | 0.700 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.95 | 16.87 | 860.00 | 0.944 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 1.675 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.95 | 16.87 | 860.02 | 1.645 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 2.160 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.95 | 16.87 | 860.00 | 0.767 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 1.512 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.95 | 16.87 | 860.02 | 1.566 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 1.391 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.95 | 16.87 | 860.00 | 0.794 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 1.655 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.95 | 16.87 | 860.02 | 1.610 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 1.442 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.37 | 42.18 | 1911.37 | 31.754 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.37 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.60 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.91 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.37 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1020.85 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 57976705.92 | 0.00 | 57976705.92 | 0.00 | 57976705.92 | 37848132.68 | 3860.84 | 1158.89 | 3740.27 | 379.67 |
CORE_BOTTOM | 41957834.30 | 0.00 | 41957834.30 | 0.00 | 41957834.30 | 33990283.35 | 4464.59 | 26.94 | 4268.47 | 613.80 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 5360.63 | 189.16 | 3210.21 | 213.72 |
CORE_TOP | 29087112.67 | 0.00 | 29087112.67 | 0.00 | 29087112.67 | 33990283.35 | 5569.92 | 481.59 | 2708.50 | 317.09 |
PERIMETER_BOT_ZN_3 | 5160164.11 | 0.00 | 5160164.11 | 435989.32 | 5596153.42 | 4267819.30 | 4816.69 | 74.72 | 3868.59 | 613.80 |
PERIMETER_BOT_ZN_2 | 5698337.20 | 0.00 | 5698337.20 | 290659.35 | 5988996.55 | 2750345.05 | 4368.96 | 62.50 | 4328.54 | 613.80 |
PERIMETER_BOT_ZN_1 | 8699549.24 | 0.00 | 8699549.24 | 435989.32 | 9135538.56 | 4267912.63 | 3999.59 | 55.73 | 4704.68 | 613.80 |
PERIMETER_BOT_ZN_4 | 7445199.93 | 0.00 | 7445199.93 | 290659.35 | 7735859.28 | 2750345.05 | 3687.77 | 53.60 | 5018.63 | 613.80 |
PERIMETER_MID_ZN_3 | 39941787.80 | 0.00 | 39941787.80 | 1022509.09 | 40964296.88 | 42678193.03 | 4974.78 | 240.15 | 3545.07 | 213.72 |
PERIMETER_MID_ZN_2 | 51386518.78 | 0.00 | 51386518.78 | 681672.26 | 52068191.04 | 27503450.52 | 4554.92 | 81.13 | 4123.95 | 958.05 |
PERIMETER_MID_ZN_1 | 80137475.99 | 0.00 | 80137475.99 | 1022509.09 | 81159985.08 | 42679126.28 | 4078.22 | 298.78 | 4382.99 | 213.72 |
PERIMETER_MID_ZN_4 | 46328741.92 | 0.00 | 46328741.92 | 681672.26 | 47010414.17 | 27503450.52 | 4597.74 | 383.24 | 3779.03 | 213.72 |
PERIMETER_TOP_ZN_3 | 4137402.56 | 0.00 | 4137402.56 | 1269544.06 | 5406946.63 | 4267819.30 | 4696.94 | 365.86 | 3697.20 | 317.09 |
PERIMETER_TOP_ZN_2 | 5458621.99 | 0.00 | 5458621.99 | 846362.13 | 6304984.12 | 2750345.05 | 4401.25 | 154.82 | 4203.93 | 317.09 |
PERIMETER_TOP_ZN_1 | 8242703.43 | 0.00 | 8242703.43 | 1269544.06 | 9512247.50 | 4267912.63 | 4014.21 | 234.38 | 4511.41 | 317.09 |
PERIMETER_TOP_ZN_4 | 4815092.15 | 0.00 | 4815092.15 | 846362.13 | 5661454.28 | 2750345.05 | 4388.06 | 156.00 | 4215.94 | 317.09 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.52E+09 | 0.00 | 0.52E+09 | 0.00 | 0.52E+09 | 10671554.30 | 137.00 | 578.04 | 8044.96 | 2782.00 |
Total Facility | 0.59E+10 | 0.00 | 0.59E+10 | 39768736.56 | 0.59E+10 | 0.50E+10 | 7230.34 | 4379.37 | 8632.25 | 3526.65 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.5548 | 0.0000 | 2.5548 | 0.0000 | 2.5548 | 1.2002 | 1284.62 | 1156.12 | 3502.25 |
CORE_BOTTOM | 1.7978 | 0.0000 | 1.7978 | 0.0000 | 1.7978 | 1.0778 | 2193.46 | 25.50 | 3724.04 |
CORE_MID | 13.4062 | 0.0000 | 13.4062 | 0.0000 | 13.4062 | 10.7782 | 2696.82 | 188.41 | 3057.77 |
CORE_TOP | 1.3121 | 0.0000 | 1.3121 | 0.0000 | 1.3121 | 1.0778 | 2892.06 | 481.53 | 2569.41 |
PERIMETER_BOT_ZN_3 | 0.2218 | 0.0000 | 0.2218 | 0.0101 | 0.2319 | 0.1353 | 2535.71 | 73.18 | 3334.11 |
PERIMETER_BOT_ZN_2 | 0.2538 | 0.0000 | 0.2538 | 0.0067 | 0.2606 | 0.0872 | 2088.20 | 60.79 | 3794.01 |
PERIMETER_BOT_ZN_1 | 0.3871 | 0.0000 | 0.3871 | 0.0101 | 0.3972 | 0.1353 | 1718.71 | 54.18 | 4170.11 |
PERIMETER_BOT_ZN_4 | 0.3272 | 0.0000 | 0.3272 | 0.0067 | 0.3339 | 0.0872 | 1412.41 | 52.70 | 4477.89 |
PERIMETER_MID_ZN_3 | 1.8072 | 0.0000 | 1.8072 | 0.0237 | 1.8310 | 1.3533 | 2315.31 | 239.40 | 3388.29 |
PERIMETER_MID_ZN_2 | 2.2919 | 0.0000 | 2.2919 | 0.0170 | 2.3090 | 0.8721 | 1604.00 | 77.31 | 3352.68 |
PERIMETER_MID_ZN_1 | 3.6852 | 0.0000 | 3.6852 | 0.0237 | 3.7089 | 1.3533 | 1415.02 | 298.09 | 4229.88 |
PERIMETER_MID_ZN_4 | 2.1082 | 0.0000 | 2.1082 | 0.0158 | 2.1241 | 0.8721 | 1934.96 | 382.56 | 3625.48 |
PERIMETER_TOP_ZN_3 | 0.1872 | 0.0000 | 0.1872 | 0.0295 | 0.2167 | 0.1353 | 2022.16 | 365.52 | 3555.33 |
PERIMETER_TOP_ZN_2 | 0.2509 | 0.0000 | 0.2509 | 0.0197 | 0.2706 | 0.0872 | 1728.40 | 154.65 | 4059.95 |
PERIMETER_TOP_ZN_1 | 0.3790 | 0.0000 | 0.3790 | 0.0295 | 0.4085 | 0.1353 | 1337.78 | 234.06 | 4371.16 |
PERIMETER_TOP_ZN_4 | 0.2187 | 0.0000 | 0.2187 | 0.0197 | 0.2383 | 0.0872 | 1712.86 | 155.84 | 4074.30 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 16.4138 | 0.0000 | 16.4138 | 0.0000 | 16.4138 | 0.3384 | 102.00 | 578.04 | 5262.96 |
Total Facility | 258.4570 | 0.0000 | 258.4570 | 0.9354 | 259.3924 | 158.4706 | 4413.34 | 4372.77 | 5849.93 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 67644628.15 | 0.00 | 67644628.15 | 48026705.38 | 3331.34 | 57.52 | 5371.14 | 613.80 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 3973.01 | 507.28 | 4279.71 | 213.72 |
VAV_TOP WITH REHEAT | 50753191.88 | 0.00 | 50753191.88 | 48026705.38 | 4157.19 | 512.07 | 4090.74 | 317.09 |
CAV_BAS | 56869917.69 | 0.00 | 56869917.69 | 37848132.68 | 5019.51 | 5.53 | 3734.96 | 379.67 |
AIRLOOP DATACENTER BASEMENT | 0.51E+09 | 0.00 | 0.51E+09 | 10671554.30 | 715.04 | 0.00 | 8044.96 | 2782.00 |
AIRLOOP DATACENTER BOT | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2396323.53 | 0.00 | 2396323.53 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.9306 | 0.0000 | 2.9306 | 1.5229 | 1059.29 | 55.18 | 4828.53 |
VAV_MID WITH REHEAT | 22.9229 | 0.0000 | 22.9229 | 15.2292 | 1308.45 | 506.74 | 4127.81 |
VAV_TOP WITH REHEAT | 2.3030 | 0.0000 | 2.3030 | 1.5229 | 1479.31 | 512.07 | 3951.62 |
CAV_BAS | 2.5060 | 0.0000 | 2.5060 | 1.2002 | 2440.67 | 3.13 | 3499.20 |
AIRLOOP DATACENTER BASEMENT | 16.1005 | 0.0000 | 16.1005 | 0.3384 | 680.04 | 0.00 | 5262.96 |
AIRLOOP DATACENTER BOT | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1120 | 0.0000 | 0.1120 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 897.80 | 3356.81 | 0.00 | 0.00 | 0.00 | 1403.70 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 799.83 | 2742.00 | 0.00 | 0.00 | 0.00 | 1600.62 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 435.50 | 2774.19 | 0.00 | 0.00 | 0.00 | 2054.34 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1155.11 | 3906.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 578.04 | 8044.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 1.9854 | 4.8408 | 0.0000 | 0.0000 | 0.0000 | 1.6778 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 19.7365 | 37.1894 | 0.0000 | 0.0000 | 0.0000 | 16.5070 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 1.9709 | 3.8707 | 0.0000 | 0.0000 | 0.0000 | 1.6160 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1774 | 3.8371 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3320 | 18.1477 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1519 |
Defaulted Fields | 1187 |
Fields with Defaults | 3885 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26222.76 | 305346.90 | 09-SEP-02:00 | 1846628.42 | 17-AUG-15:50 |
Electricity:Building | 16388.29 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-17:00 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16388.29 | 215366.33 | 07-MAY-17:10 | 948093.84 | 01-DEC-17:00 |
InteriorLights:Electricity | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1711.90 | 8110.17 | 01-JAN-08:50 | 169722.15 | 13-NOV-17:00 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.82 | 589.50 | 26-MAR-17:10 | 3307.80 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-08:50 | 1147.25 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.45 | 30.32 | 01-JAN-08:50 | 1147.25 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.23 | 379.89 | 09-APR-17:10 | 2131.68 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.75 | 589.50 | 12-MAR-17:10 | 3307.86 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.19 | 379.89 | 12-MAR-17:10 | 2131.67 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.76 | 19.54 | 01-JAN-08:50 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.76 | 19.54 | 01-JAN-08:50 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 438.10 | 5894.96 | 12-MAR-17:10 | 33078.05 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.44 | 303.25 | 01-JAN-08:40 | 11472.53 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 74.44 | 303.25 | 01-JAN-08:40 | 11472.53 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 282.23 | 3798.93 | 26-MAR-17:10 | 21316.76 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-07:40 | 7393.34 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 47.88 | 195.42 | 01-JAN-07:40 | 7393.34 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 437.43 | 5895.05 | 12-MAR-17:10 | 33078.63 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.77 | 303.26 | 01-JAN-07:40 | 11472.78 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 73.77 | 303.26 | 01-JAN-07:40 | 11472.78 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 281.87 | 3798.91 | 12-MAR-17:10 | 21316.66 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.52 | 195.42 | 01-JAN-08:40 | 7393.34 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 47.52 | 195.42 | 01-JAN-08:40 | 7393.34 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.81 | 589.50 | 12-MAR-17:10 | 3307.80 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-08:40 | 1147.25 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.44 | 30.32 | 01-JAN-08:40 | 1147.25 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.22 | 379.89 | 26-MAR-17:10 | 2131.68 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.79 | 19.54 | 01-JAN-07:40 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.74 | 589.50 | 12-MAR-17:10 | 3307.86 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.38 | 30.33 | 01-JAN-07:40 | 1147.28 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.19 | 379.89 | 12-MAR-17:10 | 2131.67 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.75 | 19.54 | 01-JAN-08:40 | 739.33 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.75 | 19.54 | 01-JAN-08:40 | 739.33 | 13-NOV-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2072.57 | 3911.71 | 17-JAN-03:50 | 377645.79 | 05-SEP-13:00 |
HeatRejection:Electricity | 681.21 | 174.53 | 18-JAN-07:30 | 73721.34 | 22-MAY-12:40 |
General:HeatRejection:Electricity | 681.21 | 174.53 | 18-JAN-07:30 | 73721.34 | 22-MAY-12:40 |
ElectricityProduced:Facility | 610.62 | -0.00 | 15-APR-18:30 | 89495.83 | 24-APR-11:10 |
ElectricityProduced:Plant | 610.62 | -0.00 | 15-APR-18:30 | 89495.83 | 24-APR-11:10 |
Photovoltaic:ElectricityProduced | 637.15 | 0.00 | 01-JAN-00:10 | 98401.39 | 09-JUN-12:30 |
PowerConversion:ElectricityProduced | -26.53 | -8905.56 | 09-JUN-12:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 6349.37 | 56287.53 | 25-MAY-04:50 | 558580.98 | 17-AUG-15:50 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73696.94 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3372.05 | 05-DEC-17:00 |
ElectricityPurchased:Facility | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
ElectricityPurchased:Plant | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
Cogeneration:ElectricityPurchased | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
ElectricityNet:Plant | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
Cogeneration:ElectricityNet | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
General:Cogeneration:ElectricityNet | 25612.14 | 289406.93 | 24-SEP-09:20 | 1801866.95 | 17-AUG-15:50 |
Fans:Electricity | 2745.44 | 50172.68 | 01-JAN-19:30 | 323340.61 | 06-JUN-13:00 |
General:Fans:Electricity | 2745.44 | 50172.68 | 01-JAN-19:30 | 323340.61 | 06-JUN-13:00 |
ExteriorLights:Electricity | 263.19 | 0.00 | 01-JAN-07:20 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 263.19 | 0.00 | 01-JAN-07:20 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
Cooling:Electricity | 2346.71 | 1990.87 | 18-JAN-07:30 | 403151.32 | 21-AUG-14:10 |
General:Cooling:Electricity | 2346.71 | 1990.87 | 18-JAN-07:30 | 403151.32 | 21-AUG-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2172.22 | 0.00 | 21-MAY-01:30 | 100000.00 | 01-JAN-11:30 |
General:Humidifier:Electricity | 2172.22 | 0.00 | 21-MAY-01:30 | 100000.00 | 01-JAN-11:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 422.01 | 3668.72 | 23-JAN-05:40 | 45054.80 | 03-JUL-08:30 |
General:Pumps:Electricity | 422.01 | 3668.72 | 23-JAN-05:40 | 45054.80 | 03-JUL-08:30 |
WIRED_LTG_ELECTRICITY | 48.10 | 0.00 | 01-JAN-00:10 | 4769.19 | 13-NOV-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1447.71 | 7280.88 | 01-JAN-14:40 | 801450.05 | 06-FEB-07:10 |
NaturalGas:Plant | 1447.71 | 7280.88 | 01-JAN-14:40 | 801450.05 | 06-FEB-07:10 |
Heating:NaturalGas | 705.17 | 0.00 | 01-JAN-00:10 | 770394.27 | 06-FEB-07:10 |
Boiler:Heating:NaturalGas | 705.17 | 0.00 | 01-JAN-00:10 | 770394.27 | 06-FEB-07:10 |
WaterSystems:NaturalGas | 742.54 | 7280.88 | 01-JAN-14:40 | 83167.29 | 31-JAN-12:40 |
Water Heater:WaterSystems:NaturalGas | 742.54 | 7280.88 | 01-JAN-14:40 | 83167.29 | 31-JAN-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 12666.90 | 6096.60 | 18-JAN-07:30 | 2287823.42 | 07-AUG-15:30 |
PlantLoopCoolingDemand:HVAC | 12666.90 | 6096.60 | 18-JAN-07:30 | 2287823.42 | 07-AUG-15:30 |
CoolingCoils:PlantLoopCoolingDemand | 12666.90 | 6096.60 | 18-JAN-07:30 | 2287823.42 | 07-AUG-15:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9539.76 | 0.00 | 21-MAY-01:30 | 0.00 | 21-JUL-16:50 |
Water:HVAC | 808.06 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-11:20 |
Humidifier:Water | 808.06 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-11:20 |
General:Humidifier:Water | 808.06 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-11:20 |
MainsWater:Facility | 9539.76 | 0.00 | 21-MAY-01:30 | 0.00 | 21-JUL-16:50 |
MainsWater:HVAC | 808.06 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-11:20 |
Humidifier:MainsWater | 808.06 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-11:20 |
General:Humidifier:MainsWater | 808.06 | 0.00 | 21-MAY-01:30 | 0.00 | 01-JAN-11:20 |
Water:Plant | 8731.70 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 8731.70 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 6451.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:50 |
General:HeatRejection:Water | 6451.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:50 |
HeatRejection:MainsWater | 6451.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:50 |
General:HeatRejection:MainsWater | 6451.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 53548.75 | 99825.75 | 19-JAN-04:40 | 8793066.01 | 31-JUL-15:10 |
EnergyTransfer:Building | 19019.89 | 88979.70 | 22-JAN-03:00 | 1608046.01 | 07-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 628.85 | 0.00 | 01-JAN-00:10 | 72641.72 | 10-OCT-05:10 |
Heating:EnergyTransfer | 190.89 | 0.00 | 01-JAN-17:10 | 495601.19 | 17-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.82 | 0.00 | 01-JAN-00:10 | 21785.29 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 190.89 | 0.00 | 01-JAN-17:10 | 495601.19 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.82 | 0.00 | 01-JAN-00:10 | 21785.29 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 18829.00 | 88038.84 | 22-JAN-07:50 | 1608046.01 | 07-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 626.03 | 0.00 | 01-JAN-00:10 | 72641.72 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 18829.00 | 88038.84 | 22-JAN-07:50 | 1608046.01 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 626.03 | 0.00 | 01-JAN-00:10 | 72641.72 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 588.97 | 0.00 | 01-JAN-00:10 | 55563.93 | 21-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 588.97 | 0.00 | 01-JAN-00:10 | 55563.93 | 21-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 588.97 | 0.00 | 01-JAN-00:10 | 55563.93 | 21-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 4107.89 | 0.00 | 01-JAN-00:10 | 392918.31 | 05-SEP-09:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4107.89 | 0.00 | 01-JAN-00:10 | 392918.31 | 05-SEP-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4107.89 | 0.00 | 01-JAN-00:10 | 392918.31 | 05-SEP-09:20 |
EnergyTransfer:Zone:CORE_TOP | 380.20 | 0.00 | 01-JAN-00:10 | 56563.71 | 17-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.78 | 0.00 | 01-JAN-00:10 | 56563.71 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.78 | 0.00 | 01-JAN-00:10 | 56563.71 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 376.42 | 0.00 | 01-JAN-00:10 | 48641.04 | 28-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 376.42 | 0.00 | 01-JAN-00:10 | 48641.04 | 28-JUN-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.92 | 0.00 | 01-JAN-00:10 | 11415.12 | 31-JUL-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1300.85 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1300.85 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.92 | 0.00 | 01-JAN-00:10 | 11415.12 | 31-JUL-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.92 | 0.00 | 01-JAN-00:10 | 11415.12 | 31-JUL-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 79.63 | 0.00 | 01-JAN-00:10 | 16296.68 | 05-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1240.81 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1240.81 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 79.61 | 0.00 | 01-JAN-00:10 | 16296.68 | 05-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 79.61 | 0.00 | 01-JAN-00:10 | 16296.68 | 05-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.45 | 0.00 | 01-JAN-00:10 | 19139.47 | 01-NOV-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 4227.70 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 4227.70 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.40 | 0.00 | 01-JAN-00:10 | 19139.47 | 01-NOV-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.40 | 0.00 | 01-JAN-00:10 | 19139.47 | 01-NOV-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 113.88 | 0.00 | 01-JAN-00:10 | 20244.93 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 113.88 | 0.00 | 01-JAN-00:10 | 20244.93 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 113.88 | 0.00 | 01-JAN-00:10 | 20244.93 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 573.96 | 0.00 | 01-JAN-00:10 | 105020.90 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.64 | 0.00 | 01-JAN-00:10 | 103361.00 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.64 | 0.00 | 01-JAN-00:10 | 103361.00 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 540.33 | 0.00 | 01-JAN-00:10 | 105020.90 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 540.33 | 0.00 | 01-JAN-00:10 | 105020.90 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 730.08 | 0.00 | 01-JAN-00:10 | 170877.15 | 05-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.98 | 0.00 | 01-JAN-00:10 | 76666.07 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.98 | 0.00 | 01-JAN-00:10 | 76666.07 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 716.10 | 0.00 | 01-JAN-00:10 | 170877.15 | 05-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 716.10 | 0.00 | 01-JAN-00:10 | 170877.15 | 05-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1261.09 | 0.00 | 01-JAN-00:10 | 204127.63 | 31-DEC-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 9.69 | 0.00 | 01-JAN-00:10 | 98592.56 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 9.69 | 0.00 | 01-JAN-00:10 | 98592.56 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1251.40 | 0.00 | 01-JAN-00:10 | 204127.63 | 31-DEC-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1251.40 | 0.00 | 01-JAN-00:10 | 204127.63 | 31-DEC-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 738.62 | 0.00 | 01-JAN-00:10 | 194878.39 | 04-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.31 | 0.00 | 01-JAN-00:10 | 66903.93 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.31 | 0.00 | 01-JAN-00:10 | 66903.93 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 729.31 | 0.00 | 01-JAN-00:10 | 194878.39 | 04-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 729.31 | 0.00 | 01-JAN-00:10 | 194878.39 | 04-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 65.76 | 0.00 | 01-JAN-00:10 | 14256.82 | 17-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.38 | 0.00 | 01-JAN-00:10 | 14256.82 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.38 | 0.00 | 01-JAN-00:10 | 14256.82 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 52.38 | 0.00 | 01-JAN-00:10 | 11781.48 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 52.38 | 0.00 | 01-JAN-00:10 | 11781.48 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 76.86 | 0.00 | 01-JAN-00:10 | 17306.81 | 05-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.68 | 0.00 | 01-JAN-00:10 | 13178.09 | 17-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.68 | 0.00 | 01-JAN-00:10 | 13178.09 | 17-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.18 | 0.00 | 01-JAN-00:10 | 17306.81 | 05-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.18 | 0.00 | 01-JAN-00:10 | 17306.81 | 05-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 123.88 | 0.00 | 01-JAN-00:10 | 21345.79 | 01-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.75 | 0.00 | 01-JAN-00:10 | 16631.52 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.75 | 0.00 | 01-JAN-00:10 | 16631.52 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 118.13 | 0.00 | 01-JAN-00:10 | 21345.79 | 01-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 118.13 | 0.00 | 01-JAN-00:10 | 21345.79 | 01-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 75.52 | 0.00 | 01-JAN-00:10 | 21001.14 | 27-JUN-16:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.35 | 0.00 | 01-JAN-00:10 | 11756.19 | 17-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.35 | 0.00 | 01-JAN-00:10 | 11756.19 | 17-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.17 | 0.00 | 01-JAN-00:10 | 21001.14 | 27-JUN-16:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.17 | 0.00 | 01-JAN-00:10 | 21001.14 | 27-JUN-16:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 63.86 | 0.00 | 01-JAN-00:10 | 11776.29 | 21-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.93 | 0.00 | 01-JAN-00:10 | 3720.59 | 15-JAN-13:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.93 | 0.00 | 01-JAN-00:10 | 3720.59 | 15-JAN-13:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.93 | 0.00 | 01-JAN-00:10 | 11776.29 | 21-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.93 | 0.00 | 01-JAN-00:10 | 11776.29 | 21-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 435.15 | 0.00 | 01-JAN-00:10 | 81003.39 | 05-JUL-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 63.68 | 0.00 | 01-JAN-00:10 | 50839.52 | 23-JAN-14:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 63.68 | 0.00 | 01-JAN-00:10 | 50839.52 | 23-JAN-14:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 371.47 | 0.00 | 01-JAN-00:10 | 81003.39 | 05-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 371.47 | 0.00 | 01-JAN-00:10 | 81003.39 | 05-JUL-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 97.30 | 0.00 | 01-JAN-00:10 | 23078.33 | 28-JUN-14:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.83 | 0.00 | 01-JAN-00:10 | 21041.59 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.83 | 0.00 | 01-JAN-00:10 | 21041.59 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.47 | 0.00 | 01-JAN-00:10 | 23078.33 | 28-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.47 | 0.00 | 01-JAN-00:10 | 23078.33 | 28-JUN-14:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.15 | 820.08 | 21-JAN-08:00 | 8291.16 | 15-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.15 | 820.08 | 21-JAN-08:00 | 8291.16 | 15-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.15 | 820.08 | 21-JAN-08:00 | 8291.16 | 15-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1248.30 | 6.51 | 22-JAN-12:00 | 78819.72 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.28 | 0.00 | 01-JAN-00:10 | 4883.75 | 17-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.28 | 0.00 | 01-JAN-00:10 | 4883.75 | 17-JAN-04:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1248.01 | 0.00 | 01-JAN-06:30 | 78819.72 | 16-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1248.01 | 0.00 | 01-JAN-06:30 | 78819.72 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.25 | 1.67 | 07-JAN-12:40 | 8015.78 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.70 | 0.00 | 01-JAN-15:40 | 675.73 | 16-JAN-18:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.70 | 0.00 | 01-JAN-15:40 | 675.73 | 16-JAN-18:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 116.55 | 0.00 | 01-JAN-00:10 | 8015.78 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 116.55 | 0.00 | 01-JAN-00:10 | 8015.78 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.32 | 87183.91 | 22-JAN-09:00 | 374031.47 | 18-AUG-21:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.32 | 87183.91 | 22-JAN-09:00 | 374031.47 | 18-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.32 | 87183.91 | 22-JAN-09:00 | 374031.47 | 18-AUG-21:20 |
PlantLoopHeatingDemand:Facility | 1053.62 | 0.00 | 01-JAN-00:10 | 696136.67 | 17-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 400.27 | 0.00 | 01-JAN-00:10 | 50686.57 | 06-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50686.57 | 06-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50686.57 | 06-FEB-12:50 |
EnergyTransfer:HVAC | 11942.89 | 6923.70 | 17-JAN-03:50 | 2100484.67 | 07-AUG-15:30 |
HeatingCoils:EnergyTransfer | 653.34 | 0.00 | 01-JAN-00:10 | 679429.08 | 17-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 653.34 | 0.00 | 01-JAN-00:10 | 679429.08 | 17-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 653.34 | 0.00 | 01-JAN-00:10 | 679429.08 | 17-JAN-07:10 |
CoolingCoils:EnergyTransfer | 11289.55 | 4105.73 | 18-JAN-07:30 | 2100484.67 | 07-AUG-15:30 |
EnergyTransfer:Plant | 22585.97 | 0.00 | 01-JAN-00:10 | 5616418.90 | 05-SEP-13:00 |
LoopToLoop:EnergyTransfer | 6854.86 | 0.00 | 01-JAN-00:10 | 1774521.54 | 05-SEP-13:00 |
WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50686.57 | 06-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50686.57 | 06-FEB-12:50 |
Boilers:EnergyTransfer | 652.39 | 0.00 | 01-JAN-00:10 | 691192.66 | 06-FEB-07:10 |
Chillers:EnergyTransfer | 6854.54 | 0.00 | 01-JAN-00:10 | 1772345.62 | 05-SEP-13:00 |
HeatRejection:EnergyTransfer | 7823.90 | 0.00 | 01-JAN-00:10 | 2033193.78 | 05-SEP-13:00 |
General:HeatRejection:EnergyTransfer | 7823.90 | 0.00 | 01-JAN-00:10 | 2033193.78 | 05-SEP-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.822 | -626.023 | 0.000 | 0.000 | 92.699 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -9.934 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -588.965 | 0.000 | 0.000 | 83.413 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 111.727 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4107.874 | 0.000 | 0.000 | 838.482 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -668.850 |
CORE_TOP | 0.000 | 0.000 | 3.782 | -376.412 | 0.000 | 0.000 | 86.090 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -107.285 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.005 | -73.915 | 0.000 | 0.000 | 10.651 | 7.453 | 36.365 | 38.274 | 0.000 | 0.183 | 43.385 | 0.000 | -57.543 | 0.000 | -4.858 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.015 | -79.610 | 0.000 | 0.000 | 6.802 | 4.792 | 23.435 | 92.117 | 0.000 | 0.121 | 0.001 | 0.000 | -35.572 | 0.000 | -3.273 | -8.826 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.055 | -135.397 | 0.000 | 0.000 | 10.486 | 7.382 | 36.366 | 165.029 | 0.000 | 0.179 | 0.003 | 0.000 | -54.038 | 0.000 | -5.018 | -25.045 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -113.877 | 0.000 | 0.000 | 6.752 | 4.755 | 23.435 | 83.880 | 0.000 | 0.112 | 40.446 | 0.000 | -41.864 | 0.000 | -3.640 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 33.638 | -540.318 | 0.000 | 0.000 | 110.901 | 74.444 | 363.654 | 396.093 | 0.000 | 4.209 | 182.812 | 0.000 | -523.401 | 0.000 | -102.032 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 13.980 | -716.103 | 0.000 | 0.000 | 50.591 | 47.880 | 234.352 | 918.142 | 0.000 | 2.638 | 0.009 | 0.000 | -338.869 | 0.000 | -72.470 | -140.141 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 9.695 | -1251.377 | 0.000 | 0.000 | 105.158 | 73.770 | 363.660 | 1643.294 | 0.000 | 4.058 | 0.027 | 0.000 | -526.587 | 0.000 | -113.386 | -308.285 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 9.311 | -729.285 | 0.000 | 0.000 | 69.761 | 47.518 | 234.351 | 849.773 | 0.000 | 2.582 | 0.007 | 0.000 | -370.762 | 0.000 | -74.811 | -38.439 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.383 | -52.374 | 0.000 | 0.000 | 11.259 | 7.444 | 36.365 | 40.049 | 0.000 | 0.493 | 4.531 | 0.000 | -49.272 | 0.000 | -11.878 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.682 | -71.179 | 0.000 | 0.000 | 6.983 | 4.788 | 23.435 | 92.340 | 0.000 | 0.320 | 0.003 | 0.000 | -31.974 | 0.000 | -8.449 | -21.946 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.750 | -118.127 | 0.000 | 0.000 | 10.692 | 7.377 | 36.366 | 164.852 | 0.000 | 0.483 | 0.001 | 0.000 | -49.935 | 0.000 | -13.296 | -44.162 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.353 | -71.163 | 0.000 | 0.000 | 7.074 | 4.752 | 23.435 | 85.096 | 0.000 | 0.310 | 0.001 | 0.000 | -35.252 | 0.000 | -8.802 | -9.802 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.153 | 0.000 | 0.000 | 0.949 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.353 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.284 | -1248.011 | 0.000 | 0.000 | 9.495 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -317.332 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.701 | -116.551 | 0.000 | 0.000 | 0.951 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -40.658 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7163.325 | 0.000 | 0.000 | 20.110 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -384.497 |
GROUNDFLOOR_PLENUM | 1.927 | -61.932 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.340 | 70.142 | 0.000 | 0.000 | 0.000 | -10.477 | 0.000 |
MIDFLOOR_PLENUM | 63.680 | -371.465 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.243 | 481.204 | 0.000 | 0.000 | 0.000 | -179.662 | -0.006 |
TOPFLOOR_PLENUM | 21.829 | -75.467 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.512 | 72.114 | 0.000 | 0.000 | 0.000 | -18.989 | -0.002 |
Total Facility | 87.436 | -508.863 | 103.457 | -18320.039 | 0.000 | 0.000 | 1539.299 | 1711.896 | 14676.396 | 4568.940 | 0.000 | 22.783 | 1006.414 | 0.000 | -2115.069 | 0.000 | -631.041 | -2141.565 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-NOV-13:20 | 0.00 | 0.00 | 0.00 | -99962.02 | 0.00 | 0.00 | 404.32 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 85534.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-JUN-04:13 | 0.00 | 0.00 | 0.00 | -86862.47 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 80387.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:13 | 0.00 | 0.00 | 0.00 | -760181.73 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 695431.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-AUG-04:13 | 0.00 | 0.00 | 0.00 | -82277.15 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 75802.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-17:42 | 0.00 | 0.00 | 0.00 | -16974.87 | 0.00 | 0.00 | 0.00 | 30.32 | 559.17 | 6536.20 | 0.00 | 197.42 | 9651.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 18-JUN-08:61 | 0.00 | 0.00 | 0.00 | -25137.12 | 0.00 | 0.00 | 16.99 | 19.54 | 464.11 | 21840.69 | 0.00 | 0.00 | 2831.01 | 0.00 | -0.00 | 0.00 | -35.22 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-11:51 | 0.00 | 0.00 | 0.00 | -24581.60 | 0.00 | 0.00 | 29.97 | 30.33 | 720.19 | 29926.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6125.56 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:21 | 0.00 | 0.00 | 0.00 | -33278.47 | 0.00 | 0.00 | 11.74 | 19.54 | 464.11 | 19736.59 | 0.00 | 0.00 | 13049.61 | 0.00 | -0.00 | 0.00 | -3.12 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-18:52 | 0.00 | 0.00 | 0.00 | -165998.97 | 0.00 | 0.00 | 0.00 | 303.25 | 5591.71 | 53993.43 | 0.00 | 3898.17 | 102212.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -282992.69 | 0.00 | 0.00 | 145.65 | 195.42 | 4641.14 | 198728.20 | 0.00 | 0.00 | 80194.19 | 0.00 | -0.00 | 0.00 | -911.92 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:51 | 0.00 | 0.00 | 0.00 | -244574.69 | 0.00 | 0.00 | 287.81 | 303.26 | 7201.95 | 173408.56 | 0.00 | 0.00 | 66418.13 | 0.00 | -0.00 | 0.00 | -3045.03 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -307656.09 | 0.00 | 0.00 | 128.64 | 195.42 | 4641.11 | 228401.04 | 0.00 | 0.00 | 75070.94 | 0.00 | -0.00 | 0.00 | -781.05 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-15:01 | 0.00 | 0.00 | 0.00 | -19551.35 | 0.00 | 0.00 | 37.10 | 30.32 | 720.18 | 5477.97 | 0.00 | 1089.14 | 12196.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:01 | 0.00 | 0.00 | 0.00 | -28737.29 | 0.00 | 0.00 | 14.31 | 19.54 | 464.11 | 19217.06 | 0.00 | 0.00 | 9135.76 | 0.00 | -0.00 | 0.00 | -113.49 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-11:11 | 0.00 | 0.00 | 0.00 | -27824.40 | 0.00 | 0.00 | 26.78 | 30.33 | 720.19 | 29604.22 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -150.96 | -2406.16 |
PERIMETER_TOP_ZN_4 | 18-JUN-16:31 | 0.00 | 0.00 | 0.00 | -33110.35 | 0.00 | 0.00 | 10.40 | 19.54 | 464.11 | 22833.28 | 0.00 | 36.67 | 9746.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 15-APR-18:10 | 0.00 | 0.00 | 0.00 | -8291.18 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 488.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:20 | 0.00 | 0.00 | 0.00 | -78880.82 | 0.00 | 0.00 | 0.00 | 81.29 | 77944.22 | 0.00 | 0.00 | 0.00 | 855.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 16-APR-18:00 | 0.00 | 0.00 | 0.00 | -8018.78 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 216.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 18-AUG-21:12 | 0.00 | 0.00 | 0.00 | -378072.94 | 0.00 | 0.00 | 112.35 | 318.73 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1990.66 |
GROUNDFLOOR_PLENUM | 21-AUG-05:13 | 0.00 | -13806.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13921.89 | 0.00 | -0.00 | 0.00 | -115.41 | 0.00 |
MIDFLOOR_PLENUM | 17-JAN-04:01 | 0.00 | -99004.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147953.39 | 0.00 | -0.00 | 0.00 | -48948.78 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:00 | 0.00 | -23074.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.31 | 22854.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-04:12 | 0.00 | 45293.38 | 0.00 | -1903178.95 | 0.00 | 0.00 | 0.00 | 10223.35 | 587299.42 | 0.00 | 0.00 | 0.00 | 1304540.94 | 0.00 | -42008.68 | 0.00 | -2169.47 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:01 | 0.00 | 0.00 | 23132.53 | 0.00 | 0.00 | 0.00 | 520.13 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37675.42 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JAN-04:01 | 0.00 | 0.00 | 68283.95 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -74729.18 |
PERIMETER_BOT_ZN_3 | 06-FEB-06:01 | 0.00 | 0.00 | 8184.66 | 0.00 | 0.00 | 0.00 | 142.59 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5553.36 | 0.00 | -232.20 | -3569.40 |
PERIMETER_BOT_ZN_2 | 06-FEB-06:01 | 0.00 | 0.00 | 6162.56 | 0.00 | 0.00 | 0.00 | 92.74 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3604.86 | 0.00 | -154.02 | -3158.72 |
PERIMETER_BOT_ZN_1 | 17-JAN-06:01 | 0.00 | 0.00 | 10879.34 | 0.00 | 0.00 | 0.00 | 148.92 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4813.38 | 0.00 | -292.54 | -6950.07 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JAN-04:01 | 0.00 | 0.00 | 131977.57 | 0.00 | 0.00 | 0.00 | 0.00 | 637.34 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42997.50 | 0.00 | -26129.76 | -70943.27 |
PERIMETER_MID_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 155634.56 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28819.77 | 0.00 | -17929.94 | -114100.27 |
PERIMETER_MID_ZN_1 | 17-JAN-04:01 | 0.00 | 0.00 | 162538.13 | 0.00 | 0.00 | 0.00 | 0.00 | 637.36 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43731.82 | 0.00 | -27637.69 | -99261.71 |
PERIMETER_MID_ZN_4 | 17-JAN-04:01 | 0.00 | 0.00 | 150106.22 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28897.08 | 0.00 | -18548.32 | -107876.19 |
PERIMETER_TOP_ZN_3 | 17-JAN-01:53 | 0.00 | 0.00 | 16259.53 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3846.20 | 0.00 | -2844.35 | -10378.28 |
PERIMETER_TOP_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 18020.40 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2610.34 | 0.00 | -2188.74 | -13742.86 |
PERIMETER_TOP_ZN_1 | 17-JAN-01:53 | 0.00 | 0.00 | 19804.39 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3936.58 | 0.00 | -2935.58 | -13741.55 |
PERIMETER_TOP_ZN_4 | 17-JAN-04:01 | 0.00 | 0.00 | 18812.55 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2581.23 | 0.00 | -2206.96 | -14545.89 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 17-JAN-04:13 | 0.00 | 0.00 | 4883.75 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24451.10 |
DATACENTER_TOP_ZN_6 | 16-JAN-18:20 | 0.00 | 0.00 | 675.73 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2632.46 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 20-AUG-15:41 | 13244.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.99 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13523.49 |
MIDFLOOR_PLENUM | 30-JUL-15:51 | 130163.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5658.63 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -135822.58 |
TOPFLOOR_PLENUM | 06-FEB-05:22 | 24268.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3636.29 | -20632.47 |
Total Facility | 17-JAN-04:01 | -385247.47 | 298213.87 | 745483.69 | -298213.87 | 0.00 | 0.00 | 0.00 | 9428.74 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -174354.25 | 0.00 | -161887.85 | -265848.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.3435 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7258 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 118.3044 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 99.8890 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.3519 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.3171 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9198 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9198 | 0.2027 | 1.0000 | Not calculated | 1.2002 | 0.2027 | ||
AIRLOOP DATACENTER BASEMENT | 25.8828 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.8831 | 0.0131 | 1.0000 | Not calculated | 0.3384 | 0.0131 | ||
AIRLOOP DATACENTER BOT | 0.5779 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5779 | 0.0270 | 1.0000 | Not calculated | 0.0156 | 0.0270 | ||
AIRLOOP DATACENTER MID | 5.5388 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5388 | 0.0282 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5657 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5657 | 0.0276 | 1.0000 | Not calculated | 0.0156 | 0.0276 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.1717 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2873 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 59.1522 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8533 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1759 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2864 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9198 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9198 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2027 | ||
AIRLOOP DATACENTER BASEMENT | 25.8828 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.8828 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0131 | ||
AIRLOOP DATACENTER BOT | 0.5779 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5779 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0270 | ||
AIRLOOP DATACENTER MID | 5.5388 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5388 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5657 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5657 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0276 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9198 | 5.9198 | 5.9198 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3744 | 6.3744 | 1.6191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.7152 | 59.7152 | 16.1828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0317 | 6.0317 | 1.6165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1623 | 1.1623 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4762 | 1.4762 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4740 | 1.4740 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8565 | 1.8565 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1475 | 11.1475 | 2.0288 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.8510 | 15.8510 | 1.3156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.4546 | 14.4546 | 2.0236 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.1362 | 17.1362 | 1.3024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2859 | 1.2859 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6038 | 1.6038 | 0.1315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6036 | 1.6036 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8269 | 1.8269 | 0.1315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5779 | 0.5779 | 0.5779 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5388 | 5.5388 | 5.5388 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5657 | 0.5657 | 0.5657 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.8828 | 25.8828 | 25.8828 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.3435 | 10.7258 | 12.3435 | 2.2873 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 118.3044 | 99.8890 | 118.3044 | 22.8533 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.3519 | 11.3171 | 12.3519 | 2.2864 | 0.0000 | 1.0000 |
CAV_BAS | 5.9198 | 5.9198 | 5.9198 | 5.9198 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.8828 | 25.8831 | 25.8828 | 25.8828 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5779 | 0.5779 | 0.5779 | 0.5779 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5388 | 5.5388 | 5.5388 | 5.5388 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5657 | 0.5657 | 0.5657 | 0.5657 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9198 | 5.9198 | 5.9198 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1872 | 3.1872 | 1.6191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.8576 | 29.8576 | 16.1828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0159 | 3.0159 | 1.6165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5812 | 0.5812 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7381 | 0.7381 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7370 | 0.7370 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9283 | 0.9283 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5737 | 5.5737 | 2.0288 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9255 | 7.9255 | 1.3156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2273 | 7.2273 | 2.0236 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5681 | 8.5681 | 1.3024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6430 | 0.6430 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8019 | 0.8019 | 0.1315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8018 | 0.8018 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9134 | 0.9134 | 0.1315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5779 | 0.5779 | 0.5779 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5388 | 5.5388 | 5.5388 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5657 | 0.5657 | 0.5657 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.8828 | 25.8828 | 25.8828 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.1717 | 2.2873 | 2.2873 | 2.2873 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 59.1522 | 22.8533 | 22.8533 | 22.8533 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1759 | 2.2864 | 2.2864 | 2.2864 | 0.0000 | 1.0000 |
CAV_BAS | 5.9198 | 5.9198 | 5.9198 | 5.9198 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.8828 | 25.8828 | 25.8828 | 25.8828 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5779 | 0.5779 | 0.5779 | 0.5779 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5388 | 5.5388 | 5.5388 | 5.5388 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5657 | 0.5657 | 0.5657 | 0.5657 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 9.00 |
Number of hours cooling loads not met | 939.67 |
Number of hours not met | 948.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 705.17 | 770394.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2346.71 | 403151.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1711.90 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 263.19 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2745.44 | 323340.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 422.01 | 45054.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 681.21 | 73721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2172.22 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 742.54 | 83167.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26222.76 |
Natural Gas | 0.00 | 1447.71 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27670.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 637.15 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 36.96 |
Space Heating | 0.00 |
Space Cooling | 50.66 |
Fans (All) | 59.27 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 566.12 |
Subtotal | 566.12 |
Natural Gas [MJ/m2] | |
Space Heating | 15.22 |
Service Water Heating | 16.03 |
Miscellaneous (All) | 31.25 |
Subtotal | 31.25 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.19 |
Space Heating | 2.55 |
Space Cooling | 8.48 |
Fans (All) | 9.92 |
Service Water Heating | 2.68 |
Receptacle Equipment | 53.04 |
Miscellaneous | 17.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 649. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8607.67 | 152.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8658.00 | 102.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8672.17 | 87.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8456.67 | 303.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8653.50 | 106.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8679.50 | 80.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8655.67 | 104.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8646.83 | 113.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8684.17 | 75.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8648.33 | 111.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8687.00 | 73.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8712.33 | 47.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7977.50 | 778.50 | 4.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8598.83 | 161.17 | 0.00 | 0.00 | 0.00 |
Min | 7977.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 778.50 | 4.00 | 0.00 | 0.00 |
Average | 8654.36 | 105.47 | 0.17 | 0.00 | 0.00 |
Sum | 199050.17 | 2425.83 | 4.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368114.33 | 501.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38923.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2247.00 | 21.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2256.17 | 11.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2261.33 | 6.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92742.50 | 10646.50 | 6.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368114.33 | 10646.50 | 6.00 | 0.00 | 0.00 |
Average | 79848.17 | 486.48 | 0.26 | 0.00 | 0.00 |
Sum | 1836508.00 | 11189.00 | 6.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8486.83 | 273.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8652.17 | 107.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8657.33 | 102.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8666.67 | 93.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8641.83 | 118.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8626.17 | 133.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8621.83 | 138.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8401.17 | 358.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8659.67 | 100.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8587.67 | 172.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8624.50 | 135.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8548.00 | 212.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8651.33 | 108.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8590.17 | 169.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8622.67 | 137.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8565.00 | 195.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8143.00 | 617.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8601.00 | 159.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8681.50 | 78.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8490.83 | 269.17 | 0.00 | 0.00 | 0.00 |
Min | 8143.00 | 1.50 | 0.00 | 0.00 | 0.00 |
Max | 8758.50 | 617.00 | 0.00 | 0.00 | 0.00 |
Average | 8599.64 | 160.36 | 0.00 | 0.00 | 0.00 |
Sum | 197791.67 | 3688.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367802.00 | 814.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330539.00 | 274.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330704.00 | 109.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330686.00 | 127.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 94534.33 | 8860.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367802.00 | 8860.67 | 0.00 | 0.00 | 0.00 |
Average | 79892.10 | 442.81 | 0.00 | 0.00 | 0.00 |
Sum | 1837518.33 | 10184.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458588E+11 | 97611.51 | 02-JAN-04:11 | -1.9 | -3.6 | 0.566283E+10 | 7499.08 | 06-JAN-10:00 | 2.20 | -1.4 |
February | 0.414795E+11 | 95735.29 | 13-FEB-04:12 | 1.10 | -1.6 | 0.513682E+10 | 7499.15 | 15-FEB-10:20 | 11.67 | 5.43 |
March | 0.505095E+11 | 96094.61 | 27-MAR-04:12 | 5.20 | 0.41 | 0.613111E+10 | 7499.20 | 02-MAR-14:20 | 5.20 | 0.41 |
April | 0.491917E+11 | 97417.89 | 24-APR-04:12 | 6.10 | 2.66 | 0.544849E+10 | 7499.21 | 28-APR-13:20 | 24.40 | 9.99 |
May | 0.512600E+11 | 96817.25 | 01-MAY-04:12 | 11.10 | 7.33 | 0.590015E+10 | 7560.01 | 22-MAY-13:30 | 29.70 | 14.16 |
June | 0.534624E+11 | 98310.35 | 12-JUN-04:11 | 14.23 | 8.98 | 0.588307E+10 | 7798.99 | 06-JUN-13:09 | 14.23 | 8.98 |
July | 0.554300E+11 | 85946.47 | 19-JUL-04:12 | 18.87 | 11.61 | 0.547512E+10 | 7529.48 | 10-JUL-09:00 | 18.87 | 11.61 |
August | 0.623077E+11 | 88762.41 | 31-AUG-04:12 | 15.03 | 11.51 | 0.614058E+10 | 7753.06 | 21-AUG-08:09 | 15.03 | 11.51 |
September | 0.550622E+11 | 93246.06 | 25-SEP-05:03 | 10.68 | 9.27 | 0.545330E+10 | 7693.68 | 12-SEP-09:00 | 10.68 | 9.27 |
October | 0.572538E+11 | 95726.95 | 16-OCT-04:12 | 13.30 | 5.33 | 0.567450E+10 | 7855.76 | 02-OCT-09:00 | 13.30 | 5.33 |
November | 0.536463E+11 | 99971.30 | 12-NOV-13:20 | 8.17 | 2.38 | 0.561317E+10 | 7498.98 | 21-NOV-14:20 | 15.37 | 5.87 |
December | 0.505650E+11 | 98253.77 | 11-DEC-05:01 | 1.70 | -2.3 | 0.546928E+10 | 7499.02 | 06-DEC-10:09 | 1.70 | -2.3 |
Annual Sum or Average | 0.626027E+12 | 0.679884E+11 | ||||||||
Minimum of Months | 0.414795E+11 | 85946.47 | -1.9 | -3.6 | 0.513682E+10 | 7498.98 | 1.70 | -2.3 | ||
Maximum of Months | 0.623077E+11 | 99971.30 | 18.87 | 11.61 | 0.614058E+10 | 7855.76 | 29.70 | 14.16 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351318E+11 | 76994.09 | 02-JAN-05:01 | -2.6 | -4.0 | 0.506889E+10 | 6734.77 | 06-JAN-10:00 | 2.20 | -1.4 |
February | 0.351619E+11 | 82834.05 | 21-FEB-05:11 | 2.57 | 0.44 | 0.460257E+10 | 6734.79 | 22-FEB-10:39 | 2.03 | 0.93 |
March | 0.479848E+11 | 80991.19 | 27-MAR-04:12 | 5.20 | 0.41 | 0.549848E+10 | 6734.77 | 02-MAR-14:20 | 5.20 | 0.41 |
April | 0.524244E+11 | 83252.98 | 24-APR-04:12 | 6.10 | 2.66 | 0.488177E+10 | 6734.73 | 17-APR-13:00 | 6.10 | 2.66 |
May | 0.482200E+11 | 86669.13 | 22-MAY-04:13 | 17.43 | 11.95 | 0.528641E+10 | 6734.97 | 11-MAY-09:09 | 17.43 | 11.95 |
June | 0.550576E+11 | 86862.62 | 05-JUN-04:13 | 15.00 | 13.05 | 0.527006E+10 | 7160.36 | 06-JUN-13:09 | 27.98 | 16.29 |
July | 0.607641E+11 | 79004.59 | 08-JUL-04:12 | 16.30 | 14.75 | 0.489641E+10 | 6734.80 | 28-JUL-09:20 | 24.97 | 16.59 |
August | 0.683769E+11 | 84678.13 | 21-AUG-04:23 | 21.70 | 15.53 | 0.549923E+10 | 7070.24 | 03-AUG-09:09 | 21.70 | 15.53 |
September | 0.485452E+11 | 84460.99 | 11-SEP-04:13 | 14.27 | 10.17 | 0.488466E+10 | 6963.79 | 01-SEP-09:00 | 14.27 | 10.17 |
October | 0.491523E+11 | 86188.57 | 10-OCT-04:13 | 13.90 | 10.99 | 0.507982E+10 | 6859.23 | 10-OCT-12:09 | 25.78 | 15.17 |
November | 0.455216E+11 | 82726.95 | 24-NOV-05:11 | 2.40 | -2.3 | 0.502709E+10 | 6734.73 | 30-NOV-10:20 | 6.70 | 0.80 |
December | 0.426270E+11 | 80549.95 | 26-DEC-04:01 | 0.32 | -0.9 | 0.490041E+10 | 6734.76 | 26-DEC-10:20 | 2.57 | 0.95 |
Annual Sum or Average | 0.588967E+12 | 0.608958E+11 | ||||||||
Minimum of Months | 0.351318E+11 | 76994.09 | -2.6 | -4.0 | 0.460257E+10 | 6734.73 | 2.03 | -1.4 | ||
Maximum of Months | 0.683769E+11 | 86862.62 | 21.70 | 15.53 | 0.549923E+10 | 7160.36 | 27.98 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233527E+11 | 30539.95 | 05-JAN-06:02 | 1.83 | -0.7 | 0.494148E+10 | 6734.74 | 06-JAN-10:00 | 2.20 | -1.4 |
February | 0.228912E+11 | 66544.83 | 15-FEB-06:03 | 6.93 | 2.40 | 0.452798E+10 | 6734.76 | 15-FEB-10:20 | 11.67 | 5.43 |
March | 0.312503E+11 | 67044.37 | 17-MAR-05:03 | 7.02 | 1.62 | 0.546872E+10 | 6734.76 | 27-MAR-13:20 | 17.07 | 6.63 |
April | 0.338844E+11 | 71176.99 | 27-APR-04:11 | 11.67 | 4.33 | 0.487115E+10 | 6734.71 | 26-APR-13:20 | 11.67 | 4.33 |
May | 0.392986E+11 | 73334.19 | 30-MAY-04:12 | 14.27 | 10.94 | 0.527937E+10 | 6734.93 | 11-MAY-09:09 | 14.27 | 10.94 |
June | 0.430570E+11 | 73954.59 | 05-JUN-04:12 | 15.00 | 13.05 | 0.526620E+10 | 6999.59 | 06-JUN-13:09 | 27.98 | 16.29 |
July | 0.441054E+11 | 76028.86 | 05-JUL-04:13 | 22.20 | 13.87 | 0.489348E+10 | 6734.80 | 11-JUL-09:20 | 26.67 | 17.63 |
August | 0.462678E+11 | 75083.29 | 28-AUG-05:03 | 16.52 | 13.53 | 0.549591E+10 | 6915.98 | 03-AUG-09:09 | 16.52 | 13.53 |
September | 0.395744E+11 | 74995.06 | 05-SEP-04:13 | 17.23 | 15.17 | 0.487843E+10 | 6881.18 | 01-SEP-09:00 | 17.23 | 15.17 |
October | 0.357096E+11 | 73063.99 | 03-OCT-04:12 | 14.63 | 11.58 | 0.506107E+10 | 6734.76 | 18-OCT-09:20 | 13.00 | 5.98 |
November | 0.280918E+11 | 70235.52 | 01-NOV-05:02 | 7.70 | 5.59 | 0.498911E+10 | 6734.74 | 08-NOV-10:30 | 13.60 | 6.17 |
December | 0.233058E+11 | 56429.31 | 01-DEC-06:03 | 3.90 | -0.5 | 0.478742E+10 | 6734.71 | 06-DEC-10:09 | 0.37 | -2.8 |
Annual Sum or Average | 0.410789E+12 | 0.604603E+11 | ||||||||
Minimum of Months | 0.228912E+11 | 30539.95 | 1.83 | -0.7 | 0.452798E+10 | 6734.71 | 0.37 | -2.8 | ||
Maximum of Months | 0.462678E+11 | 76028.86 | 22.20 | 15.17 | 0.549591E+10 | 6999.59 | 27.98 | 17.63 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159697E+11 | 18979.12 | 05-JAN-17:00 | 13.30 | 5.53 | 0.435114E+10 | 6629.60 | 27-JAN-14:00 | 11.70 | 2.33 |
February | 0.162835E+11 | 30653.04 | 15-FEB-16:20 | 17.03 | 6.28 | 0.414485E+10 | 6734.73 | 15-FEB-10:20 | 17.03 | 6.28 |
March | 0.243997E+11 | 31762.52 | 08-MAR-16:20 | 22.60 | 8.78 | 0.527657E+10 | 6734.71 | 02-MAR-14:20 | 22.60 | 8.78 |
April | 0.306641E+11 | 66900.62 | 27-APR-05:03 | 9.40 | 3.12 | 0.482106E+10 | 6734.68 | 07-APR-09:20 | 9.40 | 3.12 |
May | 0.386670E+11 | 75208.03 | 22-MAY-04:12 | 17.43 | 11.95 | 0.526203E+10 | 6734.87 | 11-MAY-09:09 | 17.43 | 11.95 |
June | 0.462125E+11 | 75107.81 | 19-JUN-04:11 | 12.60 | 5.29 | 0.526656E+10 | 7237.46 | 06-JUN-13:09 | 12.60 | 5.29 |
July | 0.492658E+11 | 81397.22 | 05-JUL-04:13 | 22.20 | 13.87 | 0.489761E+10 | 6734.77 | 03-JUL-09:20 | 22.20 | 13.87 |
August | 0.502910E+11 | 82273.93 | 21-AUG-04:13 | 21.70 | 15.53 | 0.549868E+10 | 6786.83 | 03-AUG-09:09 | 21.70 | 15.53 |
September | 0.392734E+11 | 77586.00 | 05-SEP-04:12 | 17.23 | 15.17 | 0.487391E+10 | 6826.13 | 01-SEP-09:00 | 17.23 | 15.17 |
October | 0.298742E+11 | 73323.01 | 02-OCT-04:12 | 17.60 | 12.86 | 0.495584E+10 | 6734.72 | 18-OCT-09:20 | 13.00 | 5.98 |
November | 0.199551E+11 | 33457.91 | 01-NOV-15:20 | 12.07 | 7.11 | 0.467402E+10 | 6734.75 | 01-NOV-09:20 | 12.07 | 7.11 |
December | 0.155601E+11 | 19988.18 | 01-DEC-17:00 | 12.20 | 4.22 | 0.419576E+10 | 6734.28 | 01-DEC-14:00 | 12.20 | 4.22 |
Annual Sum or Average | 0.376416E+12 | 0.582180E+11 | ||||||||
Minimum of Months | 0.155601E+11 | 18979.12 | 9.40 | 3.12 | 0.414485E+10 | 6629.60 | 9.40 | 2.33 | ||
Maximum of Months | 0.502910E+11 | 82273.93 | 22.60 | 15.53 | 0.549868E+10 | 7237.46 | 22.60 | 15.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226271E+10 | 2885.17 | 02-JAN-13:10 | 12.98 | 5.03 | 0.579484E+09 | 845.61 | 02-JAN-14:09 | 13.98 | 5.50 |
February | 0.244141E+10 | 4312.82 | 21-FEB-13:30 | 12.20 | 6.00 | 0.544433E+09 | 845.62 | 15-FEB-10:20 | 12.20 | 6.00 |
March | 0.426233E+10 | 6698.26 | 27-MAR-14:30 | 18.05 | 6.97 | 0.677350E+09 | 845.63 | 02-MAR-14:20 | 18.05 | 6.97 |
April | 0.629582E+10 | 8346.50 | 14-APR-14:00 | 23.30 | 10.26 | 0.610086E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.703309E+10 | 13740.85 | 14-MAY-16:11 | 28.30 | 10.92 | 0.662813E+09 | 845.65 | 11-MAY-09:09 | 28.30 | 10.92 |
June | 0.103634E+11 | 16974.48 | 25-JUN-17:42 | 32.88 | 15.68 | 0.662626E+09 | 902.91 | 06-JUN-13:09 | 32.88 | 15.68 |
July | 0.115893E+11 | 16800.04 | 02-JUL-18:01 | 31.42 | 16.51 | 0.616328E+09 | 846.21 | 31-JUL-13:30 | 30.00 | 18.38 |
August | 0.118382E+11 | 16521.70 | 13-AUG-16:21 | 30.55 | 17.22 | 0.691196E+09 | 877.15 | 03-AUG-09:09 | 30.55 | 17.22 |
September | 0.706262E+10 | 16235.81 | 04-SEP-16:01 | 26.70 | 16.46 | 0.612926E+09 | 866.55 | 01-SEP-09:00 | 26.70 | 16.46 |
October | 0.501524E+10 | 10286.44 | 02-OCT-05:03 | 17.12 | 12.75 | 0.628580E+09 | 850.69 | 02-OCT-09:00 | 22.20 | 14.48 |
November | 0.328415E+10 | 4788.92 | 08-NOV-13:40 | 15.73 | 6.89 | 0.614244E+09 | 845.62 | 21-NOV-14:20 | 15.37 | 5.87 |
December | 0.246738E+10 | 3560.60 | 01-DEC-13:30 | 11.70 | 4.38 | 0.568620E+09 | 845.61 | 28-DEC-14:09 | 7.80 | 2.55 |
Annual Sum or Average | 0.739157E+11 | 0.746869E+10 | ||||||||
Minimum of Months | 0.226271E+10 | 2885.17 | 11.70 | 4.38 | 0.544433E+09 | 845.61 | 7.80 | 2.55 | ||
Maximum of Months | 0.118382E+11 | 16974.48 | 32.88 | 17.22 | 0.691196E+09 | 902.91 | 32.88 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237215E+10 | 10977.01 | 01-JAN-10:32 | 7.20 | 1.48 | 0.391190E+09 | 544.95 | 24-JAN-10:20 | 8.33 | 2.77 |
February | 0.279459E+10 | 15509.42 | 19-FEB-09:02 | 6.23 | 2.70 | 0.363007E+09 | 544.96 | 15-FEB-10:09 | 6.23 | 2.70 |
March | 0.509943E+10 | 19194.89 | 26-MAR-08:32 | 9.67 | 3.27 | 0.440388E+09 | 544.96 | 02-MAR-14:20 | 9.67 | 3.27 |
April | 0.778359E+10 | 21903.11 | 30-APR-08:22 | 15.30 | 5.02 | 0.394609E+09 | 546.60 | 28-APR-09:00 | 15.30 | 5.02 |
May | 0.854662E+10 | 24125.00 | 14-MAY-08:51 | 21.10 | 9.79 | 0.428270E+09 | 546.28 | 15-MAY-09:00 | 21.10 | 9.23 |
June | 0.107936E+11 | 25136.22 | 18-JUN-08:61 | 23.27 | 11.60 | 0.427419E+09 | 552.58 | 06-JUN-13:09 | 23.27 | 11.60 |
July | 0.112024E+11 | 25002.95 | 30-JUL-08:31 | 25.03 | 16.52 | 0.398016E+09 | 617.37 | 12-JUL-08:09 | 25.03 | 16.52 |
August | 0.112373E+11 | 23761.75 | 13-AUG-07:41 | 19.82 | 16.88 | 0.446148E+09 | 658.38 | 03-AUG-09:09 | 19.82 | 16.88 |
September | 0.798186E+10 | 23863.29 | 03-SEP-07:31 | 22.40 | 13.79 | 0.395710E+09 | 615.14 | 01-SEP-09:00 | 22.40 | 13.79 |
October | 0.586550E+10 | 23498.06 | 01-OCT-08:41 | 17.43 | 11.07 | 0.408179E+09 | 559.96 | 02-OCT-09:00 | 22.20 | 14.48 |
November | 0.355030E+10 | 14412.77 | 05-NOV-09:02 | 5.78 | 2.28 | 0.400951E+09 | 544.95 | 30-NOV-10:20 | 6.70 | 0.80 |
December | 0.238298E+10 | 7329.21 | 29-DEC-09:20 | 1.67 | -0.9 | 0.380995E+09 | 544.95 | 26-DEC-10:20 | 1.67 | -0.9 |
Annual Sum or Average | 0.796103E+11 | 0.487488E+10 | ||||||||
Minimum of Months | 0.237215E+10 | 7329.21 | 1.67 | -0.9 | 0.363007E+09 | 544.95 | 1.67 | -0.9 | ||
Maximum of Months | 0.112373E+11 | 25136.22 | 25.03 | 16.88 | 0.446148E+09 | 658.38 | 25.03 | 16.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.920030E+10 | 24310.00 | 01-JAN-12:31 | 12.40 | 4.46 | 0.619707E+09 | 941.60 | 23-JAN-14:09 | 14.60 | 4.35 |
February | 0.932500E+10 | 22306.01 | 12-FEB-13:32 | 16.67 | 5.61 | 0.570567E+09 | 957.65 | 14-FEB-14:09 | 20.78 | 7.02 |
March | 0.998478E+10 | 21448.40 | 26-MAR-12:32 | 17.80 | 6.78 | 0.682653E+09 | 883.76 | 13-MAR-13:20 | 17.80 | 6.78 |
April | 0.101825E+11 | 20891.85 | 16-APR-13:13 | 16.47 | 6.36 | 0.610486E+09 | 847.59 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.842044E+10 | 20629.86 | 14-MAY-14:11 | 27.23 | 10.89 | 0.662096E+09 | 845.67 | 09-MAY-13:20 | 27.23 | 10.89 |
June | 0.103610E+11 | 20966.48 | 25-JUN-14:21 | 34.15 | 16.76 | 0.662153E+09 | 913.94 | 06-JUN-13:09 | 34.15 | 16.76 |
July | 0.126799E+11 | 22378.71 | 30-JUL-14:31 | 32.93 | 17.88 | 0.616357E+09 | 846.47 | 25-JUL-13:50 | 32.93 | 17.88 |
August | 0.154536E+11 | 22242.22 | 13-AUG-15:01 | 29.50 | 17.42 | 0.692203E+09 | 977.11 | 30-AUG-12:20 | 26.13 | 15.50 |
September | 0.134364E+11 | 23539.71 | 10-SEP-12:01 | 24.68 | 15.87 | 0.619630E+09 | 968.07 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.137947E+11 | 24578.96 | 15-OCT-11:51 | 16.70 | 6.24 | 0.650119E+09 | 1063.99 | 10-OCT-12:09 | 16.70 | 6.24 |
November | 0.115660E+11 | 22528.52 | 12-NOV-12:42 | 7.70 | 2.35 | 0.638552E+09 | 985.71 | 01-NOV-13:09 | 7.70 | 2.35 |
December | 0.109940E+11 | 23006.84 | 31-DEC-13:22 | 9.15 | 1.31 | 0.609428E+09 | 946.89 | 29-DEC-14:09 | 9.15 | 1.31 |
Annual Sum or Average | 0.135399E+12 | 0.763395E+10 | ||||||||
Minimum of Months | 0.842044E+10 | 20629.86 | 7.70 | 1.31 | 0.570567E+09 | 845.67 | 7.70 | 1.31 | ||
Maximum of Months | 0.154536E+11 | 24578.96 | 34.15 | 17.88 | 0.692203E+09 | 1063.99 | 34.15 | 17.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353803E+10 | 26357.94 | 01-JAN-15:11 | 15.93 | 5.82 | 0.399423E+09 | 544.95 | 24-JAN-10:20 | 8.33 | 2.77 |
February | 0.497269E+10 | 18723.56 | 12-FEB-14:52 | 18.30 | 6.40 | 0.369804E+09 | 544.96 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.830641E+10 | 27803.62 | 12-MAR-16:01 | 19.60 | 6.14 | 0.445372E+09 | 544.96 | 28-MAR-13:39 | 15.57 | 7.44 |
April | 0.117395E+11 | 29681.44 | 16-APR-16:31 | 20.20 | 8.02 | 0.396548E+09 | 544.98 | 26-APR-13:30 | 25.00 | 9.94 |
May | 0.955907E+10 | 30724.28 | 14-MAY-16:11 | 28.30 | 10.92 | 0.428825E+09 | 544.98 | 11-MAY-09:09 | 28.30 | 10.92 |
June | 0.130173E+11 | 32923.27 | 25-JUN-16:21 | 34.45 | 14.68 | 0.428371E+09 | 596.64 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.147804E+11 | 32975.78 | 30-JUL-15:51 | 33.90 | 17.47 | 0.398635E+09 | 578.46 | 21-JUL-15:00 | 33.90 | 17.47 |
August | 0.172103E+11 | 33290.91 | 13-AUG-16:21 | 30.55 | 17.22 | 0.446812E+09 | 551.49 | 04-AUG-09:09 | 30.55 | 17.22 |
September | 0.968972E+10 | 29858.81 | 04-SEP-16:41 | 26.70 | 16.19 | 0.396398E+09 | 551.25 | 01-SEP-09:00 | 26.70 | 16.19 |
October | 0.865803E+10 | 30145.44 | 01-OCT-15:21 | 28.60 | 13.08 | 0.411430E+09 | 549.48 | 02-OCT-09:00 | 22.20 | 14.48 |
November | 0.663530E+10 | 24066.49 | 12-NOV-15:22 | 9.40 | 2.60 | 0.406958E+09 | 544.95 | 30-NOV-10:20 | 6.70 | 0.80 |
December | 0.577237E+10 | 23729.80 | 31-DEC-15:22 | 10.55 | 1.85 | 0.396046E+09 | 544.95 | 26-DEC-10:20 | 10.55 | 1.85 |
Annual Sum or Average | 0.113879E+12 | 0.492462E+10 | ||||||||
Minimum of Months | 0.353803E+10 | 18723.56 | 9.40 | 1.85 | 0.369804E+09 | 544.95 | 6.70 | 0.80 | ||
Maximum of Months | 0.172103E+11 | 33290.91 | 34.45 | 17.47 | 0.446812E+09 | 596.64 | 37.80 | 17.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116633E+10 | 2047.73 | 05-JAN-16:00 | 16.10 | 6.84 | 0.495741E+09 | 768.66 | 04-JAN-14:00 | 16.10 | 6.84 |
February | 0.136798E+10 | 2513.51 | 15-FEB-15:00 | 17.20 | 6.67 | 0.470423E+09 | 845.60 | 15-FEB-14:20 | 17.20 | 6.67 |
March | 0.240827E+10 | 4301.42 | 27-MAR-14:40 | 18.13 | 6.99 | 0.626859E+09 | 845.63 | 27-MAR-13:20 | 18.13 | 6.99 |
April | 0.386444E+10 | 7178.32 | 14-APR-14:00 | 23.30 | 10.26 | 0.594036E+09 | 845.63 | 26-APR-13:20 | 24.80 | 9.90 |
May | 0.573666E+10 | 7968.58 | 31-MAY-15:30 | 27.75 | 11.03 | 0.657761E+09 | 845.64 | 09-MAY-13:20 | 27.75 | 11.03 |
June | 0.886965E+10 | 15612.48 | 11-JUN-18:41 | 25.47 | 12.13 | 0.661852E+09 | 884.67 | 06-JUN-13:09 | 25.47 | 12.13 |
July | 0.956606E+10 | 16598.71 | 04-JUL-18:52 | 32.20 | 13.44 | 0.616170E+09 | 846.73 | 31-JUL-13:20 | 29.80 | 18.31 |
August | 0.886709E+10 | 15258.23 | 13-AUG-16:51 | 31.10 | 17.22 | 0.690521E+09 | 856.80 | 03-AUG-09:09 | 31.10 | 17.22 |
September | 0.578664E+10 | 15192.86 | 04-SEP-16:51 | 26.70 | 16.12 | 0.609991E+09 | 855.66 | 01-SEP-09:00 | 26.70 | 16.12 |
October | 0.348168E+10 | 7258.69 | 02-OCT-13:40 | 26.33 | 15.37 | 0.597942E+09 | 845.62 | 24-OCT-13:00 | 7.20 | 3.69 |
November | 0.191121E+10 | 2755.22 | 03-NOV-14:00 | 12.20 | 2.42 | 0.540919E+09 | 845.60 | 09-NOV-14:20 | 19.03 | 9.71 |
December | 0.100668E+10 | 1917.76 | 29-DEC-16:10 | 11.42 | 3.74 | 0.467045E+09 | 806.47 | 01-DEC-14:00 | 11.42 | 3.74 |
Annual Sum or Average | 0.540327E+11 | 0.702926E+10 | ||||||||
Minimum of Months | 0.100668E+10 | 1917.76 | 11.42 | 2.42 | 0.467045E+09 | 768.66 | 7.20 | 3.69 | ||
Maximum of Months | 0.956606E+10 | 16598.71 | 32.20 | 17.22 | 0.690521E+09 | 884.67 | 31.10 | 18.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125071E+10 | 5536.52 | 27-JAN-09:40 | 2.07 | -2.9 | 0.268589E+09 | 548.49 | 30-JAN-11:09 | 7.43 | 1.38 |
February | 0.172882E+10 | 10361.73 | 19-FEB-10:13 | 9.80 | 4.47 | 0.254166E+09 | 548.49 | 15-FEB-11:09 | 9.80 | 4.47 |
March | 0.396711E+10 | 23471.26 | 26-MAR-09:42 | 13.77 | 5.28 | 0.317045E+09 | 548.50 | 10-MAR-11:09 | 13.77 | 5.28 |
April | 0.705237E+10 | 26115.03 | 30-APR-08:11 | 15.20 | 5.08 | 0.290396E+09 | 548.51 | 17-APR-14:09 | 15.20 | 5.08 |
May | 0.839995E+10 | 26443.32 | 29-MAY-07:51 | 16.10 | 12.31 | 0.315714E+09 | 548.52 | 15-MAY-12:09 | 16.10 | 12.31 |
June | 0.108711E+11 | 26691.89 | 11-JUN-09:21 | 21.10 | 11.19 | 0.315399E+09 | 548.55 | 20-JUN-10:09 | 25.28 | 10.81 |
July | 0.112054E+11 | 28284.52 | 04-JUL-08:51 | 26.70 | 18.67 | 0.294970E+09 | 610.32 | 12-JUL-08:09 | 24.68 | 15.73 |
August | 0.109124E+11 | 27073.05 | 06-AUG-09:21 | 25.55 | 15.07 | 0.329157E+09 | 617.78 | 04-AUG-08:00 | 25.55 | 15.07 |
September | 0.773260E+10 | 24843.67 | 17-SEP-08:41 | 17.62 | 12.98 | 0.291962E+09 | 548.83 | 01-SEP-10:09 | 17.62 | 12.98 |
October | 0.507051E+10 | 23030.35 | 09-OCT-09:32 | 13.17 | 6.41 | 0.297504E+09 | 548.51 | 06-OCT-10:09 | 13.17 | 6.41 |
November | 0.230254E+10 | 9848.94 | 01-NOV-10:05 | 12.88 | 7.66 | 0.287181E+09 | 548.49 | 14-NOV-11:09 | 9.60 | 3.34 |
December | 0.111684E+10 | 5207.12 | 29-DEC-09:30 | 1.95 | -0.8 | 0.260550E+09 | 548.49 | 29-DEC-11:09 | 5.97 | 1.69 |
Annual Sum or Average | 0.716104E+11 | 0.352263E+10 | ||||||||
Minimum of Months | 0.111684E+10 | 5207.12 | 1.95 | -2.9 | 0.254166E+09 | 548.49 | 5.97 | 1.38 | ||
Maximum of Months | 0.112054E+11 | 28284.52 | 26.70 | 18.67 | 0.329157E+09 | 617.78 | 25.55 | 15.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.923286E+10 | 22694.68 | 22-JAN-13:51 | 11.10 | 2.36 | 0.613908E+09 | 1019.65 | 23-JAN-14:09 | 14.60 | 4.35 |
February | 0.916952E+10 | 23205.70 | 19-FEB-11:31 | 12.07 | 5.10 | 0.564724E+09 | 1028.73 | 14-FEB-14:09 | 12.07 | 5.10 |
March | 0.908699E+10 | 23396.66 | 12-MAR-13:11 | 17.07 | 5.60 | 0.670235E+09 | 910.35 | 13-MAR-13:50 | 20.32 | 6.92 |
April | 0.854794E+10 | 21449.91 | 30-APR-12:52 | 20.60 | 7.16 | 0.603200E+09 | 846.75 | 17-APR-13:00 | 20.60 | 7.16 |
May | 0.757051E+10 | 20333.21 | 14-MAY-14:51 | 28.30 | 11.31 | 0.658233E+09 | 845.68 | 16-MAY-13:00 | 25.00 | 9.24 |
June | 0.902940E+10 | 19531.00 | 25-JUN-16:31 | 34.07 | 14.58 | 0.660908E+09 | 899.44 | 06-JUN-13:09 | 34.07 | 14.58 |
July | 0.108129E+11 | 22121.41 | 30-JUL-14:31 | 32.93 | 17.88 | 0.616279E+09 | 847.00 | 07-JUL-13:20 | 32.93 | 17.88 |
August | 0.130952E+11 | 21904.56 | 27-AUG-12:52 | 26.70 | 16.55 | 0.692146E+09 | 967.52 | 30-AUG-12:20 | 26.13 | 15.50 |
September | 0.132648E+11 | 23990.07 | 10-SEP-12:51 | 26.10 | 14.65 | 0.624645E+09 | 1039.32 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.137180E+11 | 24461.55 | 09-OCT-14:51 | 22.80 | 12.10 | 0.655613E+09 | 1060.48 | 31-OCT-13:39 | 21.87 | 8.72 |
November | 0.112435E+11 | 24204.10 | 05-NOV-12:11 | 10.57 | 2.77 | 0.640025E+09 | 1051.69 | 01-NOV-13:20 | 10.57 | 2.77 |
December | 0.103682E+11 | 23203.49 | 31-DEC-14:22 | 10.55 | 1.91 | 0.604034E+09 | 1007.09 | 29-DEC-14:09 | 10.55 | 1.91 |
Annual Sum or Average | 0.125140E+12 | 0.760395E+10 | ||||||||
Minimum of Months | 0.757051E+10 | 19531.00 | 10.55 | 1.91 | 0.564724E+09 | 845.68 | 10.55 | 1.91 | ||
Maximum of Months | 0.137180E+11 | 24461.55 | 34.07 | 17.88 | 0.692146E+09 | 1060.48 | 34.07 | 17.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196781E+10 | 9047.04 | 26-JAN-16:30 | 10.30 | 1.40 | 0.352384E+09 | 544.95 | 05-JAN-14:00 | 10.30 | 1.40 |
February | 0.270381E+10 | 13312.24 | 15-FEB-16:30 | 16.95 | 6.18 | 0.331397E+09 | 544.95 | 10-FEB-14:00 | 16.95 | 6.18 |
March | 0.423591E+10 | 25560.77 | 12-MAR-16:31 | 20.20 | 6.28 | 0.420934E+09 | 544.97 | 07-MAR-14:30 | 20.20 | 6.28 |
April | 0.658020E+10 | 26626.51 | 16-APR-16:31 | 20.20 | 8.02 | 0.389989E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.769164E+10 | 28805.15 | 14-MAY-16:11 | 28.30 | 10.92 | 0.425733E+09 | 544.98 | 16-MAY-13:00 | 25.00 | 9.24 |
June | 0.101088E+11 | 30765.87 | 11-JUN-16:41 | 28.22 | 13.16 | 0.427199E+09 | 614.36 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.105246E+11 | 30338.91 | 04-JUL-16:51 | 36.10 | 14.82 | 0.397958E+09 | 590.94 | 21-JUL-15:00 | 37.20 | 15.00 |
August | 0.106471E+11 | 29413.28 | 13-AUG-16:51 | 31.10 | 17.22 | 0.445903E+09 | 547.98 | 04-AUG-09:09 | 31.10 | 17.22 |
September | 0.777847E+10 | 27522.86 | 04-SEP-16:51 | 26.70 | 16.12 | 0.395276E+09 | 549.08 | 01-SEP-09:00 | 26.70 | 16.12 |
October | 0.570978E+10 | 26564.05 | 09-OCT-14:51 | 22.80 | 12.10 | 0.397358E+09 | 544.96 | 04-OCT-13:50 | 22.80 | 12.10 |
November | 0.301642E+10 | 18831.11 | 19-NOV-15:31 | 14.60 | 3.72 | 0.377527E+09 | 544.97 | 14-NOV-14:00 | 14.60 | 3.72 |
December | 0.196659E+10 | 8479.08 | 31-DEC-15:42 | 10.18 | 1.60 | 0.339004E+09 | 544.94 | 28-DEC-14:20 | 10.18 | 1.60 |
Annual Sum or Average | 0.729312E+11 | 0.470066E+10 | ||||||||
Minimum of Months | 0.196659E+10 | 8479.08 | 10.18 | 1.40 | 0.331397E+09 | 544.94 | 10.18 | 1.40 | ||
Maximum of Months | 0.106471E+11 | 30765.87 | 36.10 | 17.22 | 0.445903E+09 | 614.36 | 37.80 | 17.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576865E+09 | 1947.79 | 05-JAN-15:30 | 16.10 | 6.84 | 0.476450E+09 | 731.87 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.853081E+09 | 2277.54 | 15-FEB-16:00 | 17.20 | 6.50 | 0.447897E+09 | 837.44 | 15-FEB-14:00 | 17.20 | 6.50 |
March | 0.192570E+10 | 3591.75 | 27-MAR-15:00 | 18.30 | 7.04 | 0.595760E+09 | 845.62 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.360176E+10 | 7547.47 | 14-APR-14:30 | 23.60 | 10.45 | 0.578375E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.570956E+10 | 17680.65 | 29-MAY-16:01 | 27.02 | 13.03 | 0.650927E+09 | 845.64 | 31-MAY-13:20 | 26.50 | 11.57 |
June | 0.935479E+10 | 18974.43 | 18-JUN-17:51 | 30.00 | 10.70 | 0.660930E+09 | 896.40 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.103333E+11 | 19554.59 | 04-JUL-15:01 | 35.60 | 14.14 | 0.616236E+09 | 845.64 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.946062E+10 | 18785.76 | 06-AUG-16:51 | 30.60 | 16.14 | 0.690187E+09 | 845.69 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.584394E+10 | 15173.93 | 03-SEP-13:41 | 32.52 | 16.77 | 0.606449E+09 | 845.64 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.305928E+10 | 7829.88 | 02-OCT-13:40 | 26.33 | 15.37 | 0.576268E+09 | 845.63 | 02-OCT-13:30 | 26.33 | 15.37 |
November | 0.125516E+10 | 2257.31 | 02-NOV-15:30 | 16.95 | 9.55 | 0.508016E+09 | 845.59 | 09-NOV-14:50 | 18.48 | 9.55 |
December | 0.401107E+09 | 1824.22 | 29-DEC-15:40 | 11.50 | 3.90 | 0.453028E+09 | 753.75 | 01-DEC-14:00 | 11.50 | 3.90 |
Annual Sum or Average | 0.523752E+11 | 0.686052E+10 | ||||||||
Minimum of Months | 0.401107E+09 | 1824.22 | 11.50 | 3.90 | 0.447897E+09 | 731.87 | 11.50 | 3.90 | ||
Maximum of Months | 0.103333E+11 | 19554.59 | 35.60 | 16.77 | 0.690187E+09 | 896.40 | 37.70 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.888070E+09 | 3327.02 | 27-JAN-10:00 | 2.80 | -2.5 | 0.345997E+09 | 544.95 | 02-JAN-10:20 | 2.80 | -2.5 |
February | 0.135723E+10 | 7155.44 | 14-FEB-09:50 | 9.45 | 2.98 | 0.332128E+09 | 544.95 | 15-FEB-10:20 | 11.67 | 5.43 |
March | 0.342298E+10 | 14508.79 | 26-MAR-09:32 | 13.13 | 5.03 | 0.424681E+09 | 544.95 | 10-MAR-10:50 | 13.13 | 5.03 |
April | 0.678261E+10 | 23409.39 | 30-APR-09:02 | 15.78 | 4.89 | 0.392224E+09 | 545.95 | 26-APR-09:00 | 15.78 | 4.89 |
May | 0.849356E+10 | 27064.53 | 29-MAY-08:41 | 17.93 | 12.73 | 0.426941E+09 | 545.94 | 19-MAY-09:00 | 17.93 | 12.73 |
June | 0.114269E+11 | 27968.30 | 18-JUN-08:31 | 24.67 | 11.82 | 0.427230E+09 | 559.16 | 06-JUN-13:09 | 24.67 | 11.82 |
July | 0.119364E+11 | 28746.87 | 04-JUL-09:01 | 26.97 | 18.48 | 0.398154E+09 | 581.80 | 12-JUL-08:09 | 24.68 | 15.73 |
August | 0.116174E+11 | 26019.54 | 27-AUG-08:51 | 21.70 | 15.22 | 0.446022E+09 | 637.09 | 03-AUG-09:09 | 21.70 | 15.22 |
September | 0.796452E+10 | 24616.12 | 03-SEP-09:01 | 25.97 | 15.10 | 0.394522E+09 | 610.54 | 01-SEP-09:00 | 25.97 | 15.10 |
October | 0.470409E+10 | 24755.67 | 01-OCT-09:11 | 18.90 | 11.69 | 0.398603E+09 | 544.97 | 02-OCT-13:30 | 26.15 | 15.30 |
November | 0.174297E+10 | 8598.01 | 01-NOV-09:10 | 10.47 | 6.68 | 0.378970E+09 | 544.96 | 01-NOV-09:20 | 10.93 | 6.89 |
December | 0.842677E+09 | 3152.66 | 29-DEC-09:30 | 1.95 | -0.8 | 0.328477E+09 | 544.95 | 27-DEC-10:20 | 1.95 | -0.8 |
Annual Sum or Average | 0.711794E+11 | 0.469395E+10 | ||||||||
Minimum of Months | 0.842677E+09 | 3152.66 | 1.95 | -2.5 | 0.328477E+09 | 544.95 | 1.95 | -2.5 | ||
Maximum of Months | 0.119364E+11 | 28746.87 | 26.97 | 18.48 | 0.446022E+09 | 637.09 | 26.15 | 15.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.749335E+10 | 24644.29 | 01-JAN-15:11 | 15.93 | 5.82 | 0.585813E+09 | 933.87 | 26-JAN-14:20 | 10.20 | 1.54 |
February | 0.776603E+10 | 24530.02 | 19-FEB-13:21 | 15.55 | 6.46 | 0.542071E+09 | 966.63 | 14-FEB-14:20 | 15.55 | 6.46 |
March | 0.791390E+10 | 24565.39 | 26-MAR-14:52 | 20.60 | 7.74 | 0.649323E+09 | 867.82 | 08-MAR-14:09 | 20.60 | 7.74 |
April | 0.807408E+10 | 22369.76 | 30-APR-14:22 | 21.95 | 7.74 | 0.592849E+09 | 847.01 | 17-APR-13:00 | 21.95 | 7.74 |
May | 0.754843E+10 | 22623.28 | 29-MAY-15:21 | 27.20 | 13.19 | 0.651825E+09 | 845.68 | 08-MAY-13:39 | 27.20 | 13.19 |
June | 0.955306E+10 | 23119.84 | 18-JUN-15:51 | 32.20 | 11.77 | 0.659286E+09 | 912.30 | 06-JUN-13:09 | 32.20 | 11.77 |
July | 0.115886E+11 | 24773.57 | 04-JUL-14:21 | 35.30 | 14.60 | 0.616244E+09 | 845.98 | 07-JUL-13:39 | 33.70 | 18.46 |
August | 0.137561E+11 | 24830.12 | 06-AUG-12:51 | 31.10 | 16.21 | 0.691335E+09 | 973.92 | 30-AUG-12:20 | 26.13 | 15.50 |
September | 0.133991E+11 | 25326.70 | 03-SEP-13:01 | 31.38 | 16.74 | 0.618178E+09 | 1003.68 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.130175E+11 | 27826.75 | 01-OCT-11:11 | 24.47 | 13.95 | 0.632971E+09 | 1000.95 | 31-OCT-13:00 | 22.80 | 8.86 |
November | 0.951231E+10 | 24711.13 | 19-NOV-14:01 | 13.58 | 3.43 | 0.612833E+09 | 990.94 | 01-NOV-13:20 | 13.58 | 3.43 |
December | 0.850676E+10 | 24798.22 | 31-DEC-14:02 | 10.18 | 1.71 | 0.575275E+09 | 927.70 | 29-DEC-14:09 | 10.18 | 1.71 |
Annual Sum or Average | 0.118129E+12 | 0.742800E+10 | ||||||||
Minimum of Months | 0.749335E+10 | 22369.76 | 10.18 | 1.71 | 0.542071E+09 | 845.68 | 10.18 | 1.54 | ||
Maximum of Months | 0.137561E+11 | 27826.75 | 35.30 | 16.74 | 0.691335E+09 | 1003.68 | 33.70 | 18.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148547E+10 | 8365.75 | 26-JAN-16:30 | 10.30 | 1.40 | 0.338959E+09 | 544.94 | 27-JAN-14:20 | 10.97 | 2.02 |
February | 0.225891E+10 | 13244.91 | 15-FEB-16:30 | 16.95 | 6.18 | 0.317906E+09 | 544.94 | 27-FEB-14:20 | 11.47 | 4.37 |
March | 0.376347E+10 | 26250.78 | 26-MAR-15:32 | 20.60 | 7.74 | 0.403604E+09 | 544.95 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.635504E+10 | 31091.58 | 16-APR-17:01 | 20.40 | 8.05 | 0.382423E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.768889E+10 | 30510.32 | 07-MAY-16:21 | 24.40 | 9.02 | 0.422338E+09 | 544.97 | 08-MAY-13:39 | 25.93 | 9.77 |
June | 0.104620E+11 | 33114.48 | 18-JUN-16:31 | 31.87 | 11.82 | 0.426588E+09 | 612.50 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.110159E+11 | 31793.47 | 04-JUL-15:01 | 35.60 | 14.14 | 0.398093E+09 | 598.97 | 21-JUL-15:00 | 37.20 | 15.00 |
August | 0.110696E+11 | 30398.63 | 06-AUG-17:31 | 29.80 | 15.94 | 0.445829E+09 | 545.00 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.783055E+10 | 27635.35 | 24-SEP-16:21 | 25.30 | 15.57 | 0.394047E+09 | 544.99 | 13-SEP-13:30 | 25.30 | 15.57 |
October | 0.534923E+10 | 29453.94 | 01-OCT-15:11 | 28.50 | 13.01 | 0.386484E+09 | 544.97 | 06-OCT-13:39 | 26.33 | 12.75 |
November | 0.245591E+10 | 11182.08 | 02-NOV-15:50 | 16.78 | 9.71 | 0.360586E+09 | 544.94 | 09-NOV-14:20 | 19.03 | 9.71 |
December | 0.143066E+10 | 7172.52 | 29-DEC-16:00 | 11.70 | 3.88 | 0.326223E+09 | 544.94 | 11-DEC-14:39 | 11.70 | 3.88 |
Annual Sum or Average | 0.711657E+11 | 0.460308E+10 | ||||||||
Minimum of Months | 0.143066E+10 | 7172.52 | 10.30 | 1.40 | 0.317906E+09 | 544.94 | 10.97 | 2.02 | ||
Maximum of Months | 0.110696E+11 | 33114.48 | 35.60 | 15.94 | 0.445829E+09 | 612.50 | 37.80 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102445E+10 | 4709.78 | 02-JAN-06:15 | -4.0 | -4.9 | 0.00 | 0.00 | 01-JAN-00:10 | -4.0 | -4.9 |
February | 0.148508E+10 | 4116.66 | 21-FEB-06:15 | 3.50 | 0.93 | 0.00 | 0.00 | 01-FEB-00:10 | 3.50 | 0.93 |
March | 0.347372E+10 | 5454.28 | 27-MAR-05:15 | 5.40 | 0.66 | 0.00 | 0.00 | 01-MAR-00:10 | 5.40 | 0.66 |
April | 0.558007E+10 | 6633.31 | 03-APR-05:08 | 7.85 | 1.31 | 0.00 | 0.00 | 01-APR-00:10 | 7.85 | 1.31 |
May | 0.584469E+10 | 9612.50 | 30-MAY-05:10 | 14.72 | 10.93 | 0.00 | 0.00 | 01-MAY-00:10 | 14.72 | 10.93 |
June | 0.815068E+10 | 11125.02 | 19-JUN-05:15 | 12.93 | 5.33 | 0.00 | 0.00 | 01-JUN-00:10 | 12.93 | 5.33 |
July | 0.933475E+10 | 13501.14 | 05-JUL-05:15 | 22.20 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 13.64 |
August | 0.102096E+11 | 13806.35 | 21-AUG-05:13 | 21.50 | 15.46 | 0.00 | 0.00 | 01-AUG-00:10 | 21.50 | 15.46 |
September | 0.675252E+10 | 12368.89 | 05-SEP-05:10 | 15.92 | 14.88 | 0.00 | 0.00 | 01-SEP-00:10 | 15.92 | 14.88 |
October | 0.516293E+10 | 9791.66 | 10-OCT-05:15 | 13.90 | 11.14 | 0.00 | 0.00 | 01-OCT-00:10 | 13.90 | 11.14 |
November | 0.316551E+10 | 4883.49 | 24-NOV-16:10 | 14.82 | 4.71 | 0.00 | 0.00 | 01-NOV-00:10 | 14.82 | 4.71 |
December | 0.174827E+10 | 2830.96 | 19-DEC-16:10 | 7.62 | -0.7 | 0.00 | 0.00 | 01-DEC-00:10 | 7.62 | -0.7 |
Annual Sum or Average | 0.619323E+11 | 0.00 | ||||||||
Minimum of Months | 0.102445E+10 | 2830.96 | -4.0 | -4.9 | 0.00 | 0.00 | -4.0 | -4.9 | ||
Maximum of Months | 0.102096E+11 | 13806.35 | 22.20 | 15.46 | 0.00 | 0.00 | 22.20 | 15.46 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222160E+09 | 9900.02 | 17-JAN-04:01 | -3.3 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -5.0 |
February | 0.301497E+09 | 8557.43 | 04-FEB-05:01 | -6.2 | -7.7 | 0.00 | 0.00 | 01-FEB-00:10 | -6.2 | -7.7 |
March | 0.798512E+09 | 6665.15 | 04-MAR-05:01 | -1.2 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -1.2 | -4.0 |
April | 0.252175E+10 | 4630.01 | 28-APR-15:00 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.395564E+10 | 5783.21 | 30-MAY-14:20 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.622740E+10 | 7344.59 | 27-JUN-14:30 | 36.65 | 15.31 | 0.00 | 0.00 | 01-JUN-00:10 | 36.65 | 15.31 |
July | 0.729019E+10 | 9036.14 | 05-JUL-05:15 | 22.20 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 13.64 |
August | 0.731017E+10 | 8831.26 | 21-AUG-05:13 | 21.50 | 15.46 | 0.00 | 0.00 | 01-AUG-00:10 | 21.50 | 15.46 |
September | 0.494302E+10 | 8024.23 | 05-SEP-05:15 | 15.73 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 15.73 | 14.76 |
October | 0.269908E+10 | 6428.07 | 26-OCT-05:02 | -2.5 | -4.0 | 0.00 | 0.00 | 01-OCT-00:10 | -2.5 | -4.0 |
November | 0.675337E+09 | 5630.87 | 28-NOV-06:01 | -2.1 | -4.4 | 0.00 | 0.00 | 01-NOV-00:10 | -2.1 | -4.4 |
December | 0.201978E+09 | 8358.76 | 22-DEC-05:01 | -4.7 | -6.6 | 0.00 | 0.00 | 01-DEC-00:10 | -4.7 | -6.6 |
Annual Sum or Average | 0.371467E+11 | 0.00 | ||||||||
Minimum of Months | 0.201978E+09 | 4630.01 | -6.2 | -7.7 | 0.00 | 0.00 | -6.2 | -7.7 | ||
Maximum of Months | 0.731017E+10 | 9900.02 | 36.65 | 15.46 | 0.00 | 0.00 | 36.65 | 15.46 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141455E+09 | 3177.86 | 01-JAN-14:33 | 15.93 | 5.77 | 0.00 | 0.00 | 01-JAN-00:10 | 15.93 | 5.77 |
February | 0.672058E+09 | 6381.57 | 15-FEB-15:20 | 17.20 | 6.61 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 6.61 |
March | 0.241114E+10 | 9584.81 | 08-MAR-15:05 | 22.30 | 9.09 | 0.00 | 0.00 | 01-MAR-00:10 | 22.30 | 9.09 |
April | 0.614337E+10 | 15238.55 | 28-APR-14:20 | 24.60 | 10.33 | 0.00 | 0.00 | 01-APR-00:10 | 24.60 | 10.33 |
May | 0.866693E+10 | 18137.35 | 30-MAY-14:20 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.133682E+11 | 23078.33 | 28-JUN-14:00 | 37.80 | 14.11 | 0.00 | 0.00 | 01-JUN-00:10 | 37.80 | 14.11 |
July | 0.152404E+11 | 22344.29 | 21-JUL-14:40 | 37.80 | 15.30 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.30 |
August | 0.145329E+11 | 20839.90 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.918562E+10 | 20288.50 | 12-SEP-11:40 | 26.83 | 15.69 | 0.00 | 0.00 | 01-SEP-00:10 | 26.83 | 15.69 |
October | 0.432722E+10 | 17290.73 | 02-OCT-12:03 | 25.10 | 14.89 | 0.00 | 0.00 | 01-OCT-00:10 | 25.10 | 14.89 |
November | 0.722955E+09 | 5478.92 | 02-NOV-15:00 | 17.20 | 9.31 | 0.00 | 0.00 | 01-NOV-00:10 | 17.20 | 9.31 |
December | 56557326.10 | 2364.59 | 31-DEC-16:06 | 9.82 | 1.41 | 0.00 | 0.00 | 01-DEC-00:10 | 9.82 | 1.41 |
Annual Sum or Average | 0.754689E+11 | 0.00 | ||||||||
Minimum of Months | 56557326.10 | 2364.59 | 9.82 | 1.41 | 0.00 | 0.00 | 9.82 | 1.41 | ||
Maximum of Months | 0.152404E+11 | 23078.33 | 37.80 | 15.81 | 0.00 | 0.00 | 37.80 | 15.81 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342658E+10 | 2412.01 | 01-JAN-16:47 | 12.35 | 4.14 | 95230033.30 | 126.82 | 20-JAN-14:00 | 5.60 | 2.15 |
February | 0.800784E+10 | 4341.10 | 15-FEB-17:00 | 16.70 | 5.85 | 86396690.56 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.143057E+11 | 7086.74 | 31-MAR-24:00 | 6.90 | 3.36 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.90 | 3.36 |
April | 0.189789E+11 | 8291.16 | 15-APR-18:10 | 7.38 | 3.94 | 91637787.23 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.445887E+10 | 3470.56 | 31-MAY-24:00 | 18.60 | 7.93 | 99235063.60 | 126.85 | 24-MAY-09:00 | 18.60 | 7.93 |
June | 0.940635E+10 | 5329.43 | 30-JUN-24:00 | 22.10 | 13.89 | 98961589.22 | 126.85 | 08-JUN-13:09 | 22.10 | 13.89 |
July | 0.148104E+11 | 7252.97 | 31-JUL-24:00 | 21.00 | 17.53 | 91885747.57 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.198734E+11 | 7959.70 | 27-AUG-18:35 | 24.07 | 15.15 | 0.104217E+09 | 133.47 | 17-AUG-13:00 | 24.07 | 15.15 |
September | 0.445098E+10 | 3477.57 | 30-SEP-24:00 | 17.40 | 10.77 | 91612160.87 | 126.85 | 06-SEP-13:00 | 17.40 | 10.77 |
October | 0.949093E+10 | 5281.22 | 31-OCT-24:00 | 13.00 | 4.55 | 95232897.10 | 126.85 | 03-OCT-09:09 | 13.00 | 4.55 |
November | 0.138188E+11 | 6454.78 | 05-NOV-16:47 | 11.78 | 2.80 | 94300825.82 | 126.83 | 02-NOV-09:50 | 11.78 | 2.80 |
December | 0.191242E+11 | 8202.72 | 31-DEC-16:40 | 9.27 | 1.21 | 91881059.19 | 126.82 | 08-DEC-14:09 | 9.27 | 1.21 |
Annual Sum or Average | 0.140153E+12 | 0.114383E+10 | ||||||||
Minimum of Months | 0.342658E+10 | 2412.01 | 6.90 | 1.21 | 86396690.56 | 126.82 | 5.60 | 1.21 | ||
Maximum of Months | 0.198734E+11 | 8291.16 | 24.07 | 17.53 | 0.104217E+09 | 133.47 | 24.07 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162279E+10 | 2221.59 | 26-JAN-17:00 | 10.00 | 1.21 | 95228674.67 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.635706E+10 | 4122.57 | 15-FEB-17:00 | 16.70 | 5.85 | 86396702.72 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.127392E+11 | 6551.06 | 31-MAR-23:30 | 6.60 | 3.23 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.60 | 3.23 |
April | 0.176870E+11 | 7888.08 | 16-APR-18:20 | 19.03 | 7.42 | 91629457.54 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.389988E+10 | 3280.61 | 31-MAY-24:00 | 18.60 | 7.93 | 99234835.10 | 126.84 | 25-MAY-09:50 | 18.60 | 7.93 |
June | 0.881035E+10 | 5132.74 | 30-JUN-24:00 | 22.10 | 13.89 | 98961433.56 | 126.85 | 08-JUN-13:09 | 22.10 | 13.89 |
July | 0.140742E+11 | 6961.70 | 31-JUL-24:00 | 21.00 | 17.53 | 91885722.88 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.188041E+11 | 7517.49 | 30-AUG-17:40 | 28.50 | 14.73 | 0.103871E+09 | 131.53 | 17-AUG-13:00 | 28.50 | 14.73 |
September | 0.394448E+10 | 3276.96 | 30-SEP-24:00 | 17.40 | 10.77 | 91611405.13 | 126.84 | 08-SEP-13:00 | 17.40 | 10.77 |
October | 0.840812E+10 | 4854.65 | 31-OCT-24:00 | 13.00 | 4.55 | 95232786.98 | 126.84 | 03-OCT-09:09 | 13.00 | 4.55 |
November | 0.120230E+11 | 5906.20 | 02-NOV-16:50 | 16.20 | 9.61 | 94300816.66 | 126.83 | 02-NOV-09:50 | 16.20 | 9.61 |
December | 0.164311E+11 | 7483.38 | 29-DEC-16:50 | 10.28 | 3.14 | 91880789.36 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.124801E+12 | 0.114347E+10 | ||||||||
Minimum of Months | 0.162279E+10 | 2221.59 | 6.60 | 1.21 | 86396702.72 | 126.82 | 6.60 | 1.21 | ||
Maximum of Months | 0.188041E+11 | 7888.08 | 28.50 | 17.53 | 0.103871E+09 | 131.53 | 28.50 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.651443E+09 | 2117.35 | 26-JAN-17:00 | 10.00 | 1.21 | 93831368.99 | 129.23 | 24-JAN-10:09 | 10.00 | 1.21 |
February | 0.489885E+10 | 4143.46 | 15-FEB-17:00 | 16.70 | 5.85 | 86396704.69 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.117208E+11 | 6211.57 | 31-MAR-23:10 | 6.40 | 3.15 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.40 | 3.15 |
April | 0.172301E+11 | 8018.78 | 16-APR-18:00 | 19.40 | 7.60 | 91619872.45 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.369844E+10 | 3205.55 | 31-MAY-23:50 | 18.77 | 8.04 | 99234727.85 | 126.84 | 23-MAY-13:50 | 18.77 | 8.04 |
June | 0.881682E+10 | 5119.42 | 30-JUN-24:00 | 22.10 | 13.89 | 98961545.46 | 126.85 | 08-JUN-13:09 | 22.10 | 13.89 |
July | 0.141870E+11 | 7015.49 | 04-JUL-18:35 | 32.77 | 13.53 | 91885968.95 | 126.84 | 17-JUL-09:09 | 22.77 | 17.51 |
August | 0.188692E+11 | 7677.82 | 27-AUG-18:22 | 24.45 | 15.29 | 0.103694E+09 | 130.22 | 17-AUG-13:00 | 24.45 | 15.29 |
September | 0.383004E+10 | 3220.58 | 30-SEP-23:40 | 17.50 | 10.08 | 91611487.00 | 126.85 | 01-SEP-13:00 | 17.50 | 10.08 |
October | 0.770604E+10 | 4629.08 | 31-OCT-23:30 | 13.50 | 5.10 | 95232817.67 | 126.84 | 03-OCT-09:09 | 13.50 | 5.10 |
November | 0.105475E+11 | 5896.16 | 02-NOV-16:50 | 16.20 | 9.61 | 94300837.37 | 126.83 | 02-NOV-09:50 | 16.20 | 9.61 |
December | 0.143950E+11 | 7398.56 | 29-DEC-16:50 | 10.28 | 3.14 | 91880808.63 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.116551E+12 | 0.114189E+10 | ||||||||
Minimum of Months | 0.651443E+09 | 2117.35 | 6.40 | 1.21 | 86396704.69 | 126.82 | 6.40 | 1.21 | ||
Maximum of Months | 0.188692E+11 | 8018.78 | 32.77 | 15.29 | 0.103694E+09 | 130.22 | 24.45 | 17.51 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237614E+12 | 91673.06 | 02-JAN-17:00 | 11.10 | 4.18 | 0.206153E+10 | 2745.49 | 11-JAN-14:20 | 8.13 | 1.52 |
February | 0.435086E+12 | 182817.82 | 15-FEB-17:00 | 16.70 | 5.85 | 0.187030E+10 | 2745.72 | 22-FEB-14:09 | 8.90 | 2.93 |
March | 0.728066E+12 | 358454.84 | 31-MAR-24:00 | 6.90 | 3.36 | 0.223481E+10 | 2745.68 | 23-MAR-09:09 | 6.90 | 3.36 |
April | 0.942432E+12 | 368455.87 | 29-APR-17:31 | 24.27 | 9.18 | 0.198837E+10 | 2918.53 | 26-APR-13:00 | 24.27 | 9.18 |
May | 0.240148E+12 | 175737.95 | 31-MAY-24:00 | 18.60 | 7.93 | 0.214825E+10 | 2747.23 | 22-MAY-13:09 | 18.60 | 7.93 |
June | 0.469779E+12 | 267410.86 | 30-JUN-24:00 | 22.10 | 13.89 | 0.214301E+10 | 2749.57 | 02-JUN-13:00 | 22.10 | 13.89 |
July | 0.731891E+12 | 356973.92 | 31-JUL-23:20 | 21.13 | 17.19 | 0.199132E+10 | 2839.29 | 10-JUL-13:20 | 21.13 | 17.19 |
August | 0.971563E+12 | 378088.23 | 18-AUG-21:12 | 25.37 | 12.82 | 0.268347E+10 | 4148.73 | 15-AUG-15:00 | 25.37 | 12.82 |
September | 0.235796E+12 | 176434.93 | 30-SEP-24:00 | 17.40 | 10.77 | 0.198342E+10 | 2747.47 | 14-SEP-13:09 | 17.40 | 10.77 |
October | 0.487405E+12 | 268422.46 | 31-OCT-24:00 | 13.00 | 4.55 | 0.206173E+10 | 2748.73 | 02-OCT-09:09 | 13.00 | 4.55 |
November | 0.707849E+12 | 275856.87 | 24-NOV-17:00 | 13.90 | 4.33 | 0.204140E+10 | 2746.84 | 09-NOV-10:00 | 13.90 | 4.33 |
December | 0.975691E+12 | 367046.72 | 26-DEC-17:00 | 6.70 | 3.21 | 0.198897E+10 | 2745.64 | 26-DEC-14:20 | 6.70 | 3.21 |
Annual Sum or Average | 0.716332E+13 | 0.251966E+11 | ||||||||
Minimum of Months | 0.235796E+12 | 91673.06 | 6.70 | 3.21 | 0.187030E+10 | 2745.49 | 6.70 | 1.52 | ||
Maximum of Months | 0.975691E+12 | 378088.23 | 25.37 | 17.19 | 0.268347E+10 | 4148.73 | 25.37 | 17.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185494E+09 | 13408.25 | 01-JAN-08:23 | 0.25 |
February | 0.121094E+09 | 11597.47 | 16-FEB-05:15 | 3.17 |
March | 0.110100E+09 | 11628.81 | 21-MAR-04:15 | 9.47 |
April | 0.128423E+09 | 11608.17 | 19-APR-04:15 | 3.50 |
May | 0.286611E+09 | 13422.66 | 13-MAY-16:01 | 27.80 |
June | 0.320721E+09 | 20029.78 | 17-JUN-16:01 | 33.43 |
July | 0.385055E+09 | 23132.57 | 22-JUL-16:01 | 36.05 |
August | 0.298958E+09 | 17790.73 | 05-AUG-16:01 | 31.52 |
September | 0.306152E+09 | 17328.63 | 02-SEP-16:01 | 31.10 |
October | 0.252971E+09 | 11485.03 | 14-OCT-04:17 | 4.80 |
November | 0.224243E+09 | 11756.84 | 07-NOV-04:35 | 0.73 |
December | 0.202000E+09 | 11396.49 | 05-DEC-04:03 | -5.4 |
Annual Sum or Average | 0.282182E+10 | |||
Minimum of Months | 0.110100E+09 | 11396.49 | -5.4 | |
Maximum of Months | 0.385055E+09 | 23132.57 | 36.05 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156466E+10 | 68284.15 | 17-JAN-04:01 | -3.3 |
February | 0.577004E+09 | 67195.23 | 06-FEB-04:01 | -4.4 |
March | 27298114.40 | 58644.17 | 06-MAR-06:01 | -2.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 2392692.85 | 19939.11 | 26-OCT-05:02 | -2.5 |
November | 0.279453E+09 | 63505.71 | 27-NOV-05:11 | -4.1 |
December | 0.133115E+10 | 67815.03 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.378195E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.156466E+10 | 68284.15 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2640881.80 | 5879.24 | 17-JAN-06:01 | -3.4 |
February | 2285442.79 | 8184.57 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 4926324.59 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 2640881.80 | 8184.57 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6901567.53 | 6115.65 | 20-JAN-06:01 | -4.4 |
February | 3940010.68 | 6162.45 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 4269711.40 | 5857.92 | 23-DEC-06:01 | -5.5 |
Annual Sum or Average | 15111289.61 | |||
Minimum of Months | 0.00 | 0.00 | -5.5 | |
Maximum of Months | 6901567.53 | 6162.45 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34782625.18 | 10879.97 | 17-JAN-06:01 | -3.4 |
February | 12964851.88 | 10846.13 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 7077182.75 | 10239.17 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 54824659.81 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 34782625.18 | 10879.97 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116364E+10 | 13197.68 | 17-JAN-04:01 | -3.3 |
February | 0.680722E+09 | 13157.43 | 06-FEB-04:01 | -4.4 |
March | 0.110720E+09 | 11504.48 | 06-MAR-05:01 | -0.5 |
April | 3858508.09 | 10628.43 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 33531997.31 | 10936.76 | 26-OCT-05:02 | -2.5 |
November | 0.227639E+09 | 12072.49 | 27-NOV-05:01 | -4.0 |
December | 0.114367E+10 | 12243.19 | 14-DEC-05:01 | -2.9 |
Annual Sum or Average | 0.336378E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.116364E+10 | 13197.68 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545521E+09 | 15563.25 | 17-JAN-04:01 | -3.3 |
February | 0.264998E+09 | 15315.42 | 06-FEB-04:01 | -4.4 |
March | 30190175.51 | 13213.15 | 04-MAR-05:01 | -1.2 |
April | 1523585.94 | 5592.18 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 16275395.80 | 12442.39 | 26-OCT-05:02 | -2.5 |
November | 68392557.48 | 13684.61 | 27-NOV-05:01 | -4.0 |
December | 0.471070E+09 | 14308.18 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.139797E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.545521E+09 | 15563.25 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382628E+09 | 16253.69 | 17-JAN-04:01 | -3.3 |
February | 0.210958E+09 | 15532.25 | 06-FEB-05:01 | -4.4 |
March | 23150193.72 | 14529.50 | 04-MAR-05:01 | -1.2 |
April | 1246751.95 | 6142.95 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 13311275.94 | 13934.23 | 26-OCT-05:02 | -2.5 |
November | 17757441.05 | 13918.47 | 28-NOV-06:01 | -2.1 |
December | 0.320440E+09 | 15287.73 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.969492E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.382628E+09 | 16253.69 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367430E+09 | 15010.41 | 17-JAN-04:01 | -3.3 |
February | 0.198179E+09 | 14035.03 | 06-FEB-05:01 | -4.4 |
March | 15006180.86 | 12178.99 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 7801518.54 | 9923.88 | 26-OCT-05:02 | -2.5 |
November | 30621410.33 | 12176.53 | 28-NOV-06:01 | -2.1 |
December | 0.312097E+09 | 13515.13 | 14-DEC-05:01 | -2.9 |
Annual Sum or Average | 0.931135E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.367430E+09 | 15010.41 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402029E+10 | 16259.81 | 17-JAN-01:53 | -3.3 |
February | 0.252684E+10 | 16241.42 | 06-FEB-02:32 | -5.0 |
March | 0.877031E+09 | 14582.57 | 06-MAR-04:02 | 0.50 |
April | 0.118380E+09 | 13471.50 | 08-APR-04:12 | 2.80 |
May | 11237739.91 | 12551.99 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.343697E+09 | 13903.85 | 26-OCT-04:01 | -2.8 |
November | 0.140960E+10 | 15293.82 | 27-NOV-04:01 | -3.9 |
December | 0.407622E+10 | 15555.49 | 14-DEC-04:01 | -1.4 |
Annual Sum or Average | 0.133833E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.407622E+10 | 16259.81 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182937E+10 | 18020.22 | 17-JAN-04:01 | -3.3 |
February | 0.106609E+10 | 17969.29 | 06-FEB-04:01 | -4.4 |
March | 0.331260E+09 | 16009.68 | 04-MAR-05:01 | -1.2 |
April | 35892554.54 | 15184.45 | 08-APR-04:12 | 2.80 |
May | 4914841.77 | 9848.40 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.151325E+09 | 16011.04 | 26-OCT-04:01 | -2.8 |
November | 0.512529E+09 | 17637.41 | 27-NOV-04:01 | -3.9 |
December | 0.175080E+10 | 17946.34 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.568219E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.182937E+10 | 18020.22 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182988E+10 | 19804.51 | 17-JAN-01:53 | -3.3 |
February | 0.113273E+10 | 19670.10 | 06-FEB-03:53 | -4.4 |
March | 0.440815E+09 | 17192.36 | 04-MAR-05:01 | -1.2 |
April | 71010304.16 | 16319.96 | 08-APR-04:12 | 2.80 |
May | 13674216.19 | 15390.87 | 05-MAY-05:02 | 5.68 |
June | 110182.35 | 734.55 | 09-JUN-05:03 | 7.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.163798E+09 | 17180.77 | 26-OCT-04:01 | -2.8 |
November | 0.421922E+09 | 18112.28 | 27-NOV-04:01 | -3.9 |
December | 0.167637E+10 | 18954.21 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.575030E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.182988E+10 | 19804.51 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145465E+10 | 18812.28 | 17-JAN-04:01 | -3.3 |
February | 0.848270E+09 | 18737.36 | 06-FEB-04:01 | -4.4 |
March | 0.243780E+09 | 16587.89 | 04-MAR-05:01 | -1.2 |
April | 17124109.01 | 7757.24 | 08-APR-05:03 | 2.62 |
May | 2319578.29 | 8607.02 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 99253696.83 | 16530.64 | 26-OCT-04:01 | -2.8 |
November | 0.380389E+09 | 17832.40 | 27-NOV-04:01 | -3.9 |
December | 0.130716E+10 | 18531.26 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.435295E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.145465E+10 | 18812.28 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316434E+09 | 11194.08 | 15-JAN-15:12 | 12.03 |
February | 0.171545E+09 | 9953.65 | 12-FEB-14:52 | 18.30 |
March | 0.160724E+09 | 12053.82 | 05-MAR-15:02 | 13.48 |
April | 0.181432E+09 | 10252.86 | 09-APR-15:01 | 18.90 |
May | 95707109.63 | 11722.92 | 14-MAY-16:11 | 28.30 |
June | 97598177.32 | 12216.62 | 25-JUN-16:21 | 34.45 |
July | 0.122342E+09 | 12988.74 | 30-JUL-15:51 | 33.90 |
August | 0.108151E+09 | 13244.50 | 20-AUG-15:41 | 35.00 |
September | 81852393.05 | 12039.34 | 03-SEP-13:31 | 32.23 |
October | 0.139638E+09 | 11284.69 | 01-OCT-14:41 | 28.30 |
November | 0.231971E+09 | 10775.96 | 12-NOV-14:42 | 9.32 |
December | 0.219216E+09 | 11361.46 | 31-DEC-15:22 | 10.55 |
Annual Sum or Average | 0.192661E+10 | |||
Minimum of Months | 81852393.05 | 9953.65 | 9.32 | |
Maximum of Months | 0.316434E+09 | 13244.50 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187790E+10 | 9124.59 | 22-JAN-13:11 | 10.77 |
February | 0.119805E+10 | 8771.14 | 12-FEB-16:12 | 17.93 |
March | 0.310886E+09 | 12491.11 | 12-MAR-15:51 | 19.40 |
April | 85507928.02 | 10143.22 | 30-APR-14:51 | 22.20 |
May | 86832541.59 | 12276.47 | 14-MAY-16:11 | 28.30 |
June | 78970246.89 | 12268.15 | 25-JUN-16:31 | 34.07 |
July | 0.106999E+09 | 13016.37 | 30-JUL-15:51 | 33.90 |
August | 70114691.11 | 12677.81 | 20-AUG-16:01 | 34.90 |
September | 80683110.60 | 11147.09 | 03-SEP-13:41 | 32.52 |
October | 0.186196E+09 | 11603.10 | 15-OCT-15:32 | 20.77 |
November | 0.606424E+09 | 10797.29 | 19-NOV-15:31 | 14.60 |
December | 0.167931E+10 | 8666.62 | 31-DEC-15:42 | 10.18 |
Annual Sum or Average | 0.636787E+10 | |||
Minimum of Months | 70114691.11 | 8666.62 | 10.18 | |
Maximum of Months | 0.187790E+10 | 13016.37 | 34.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522374E+10 | 23250.70 | 17-JAN-05:22 | -3.3 |
February | 0.341076E+10 | 24268.77 | 06-FEB-05:22 | -4.4 |
March | 0.209910E+10 | 10876.47 | 06-MAR-06:01 | -2.9 |
April | 0.866450E+09 | 12636.15 | 12-APR-05:03 | 10.50 |
May | 0.485228E+09 | 13426.85 | 18-MAY-05:03 | 12.20 |
June | 0.181066E+09 | 12060.84 | 20-JUN-05:03 | 12.77 |
July | 74432901.47 | 9902.65 | 05-JUL-04:12 | 22.20 |
August | 78203583.91 | 9933.96 | 31-AUG-05:03 | 13.72 |
September | 0.262518E+09 | 12140.35 | 27-SEP-05:02 | 11.60 |
October | 0.129143E+10 | 11632.73 | 04-OCT-05:03 | 12.80 |
November | 0.256202E+10 | 18855.13 | 27-NOV-06:03 | -4.4 |
December | 0.529394E+10 | 20061.49 | 26-DEC-05:23 | -0.9 |
Annual Sum or Average | 0.218289E+11 | |||
Minimum of Months | 74432901.47 | 9902.65 | -4.4 | |
Maximum of Months | 0.529394E+10 | 24268.77 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28405980.16 | 488.37 | 17-JAN-04:13 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 28405980.16 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 28405980.16 | 488.37 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696805E+09 | 675.73 | 16-JAN-18:20 | -1.5 |
February | 4532536.79 | 340.72 | 06-FEB-04:02 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.701338E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.696805E+09 | 675.73 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668321E+09 | 1004.17 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.585843E+09 | 888.42 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.662769E+09 | 754.15 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571670E+09 | 545.86 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.609563E+09 | 613.47 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.597626E+09 | 624.30 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565637E+09 | 620.65 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.632701E+09 | 545.86 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.584101E+09 | 868.83 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.632863E+09 | 867.48 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.663154E+09 | 1147.25 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.679187E+09 | 1147.25 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.745343E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565637E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.679187E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.426004E+09 | 651.44 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.375358E+09 | 560.06 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.425754E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369633E+09 | 351.77 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.395161E+09 | 384.68 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.387673E+09 | 402.63 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.366143E+09 | 400.37 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.408972E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375883E+09 | 549.64 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.403091E+09 | 519.11 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.425641E+09 | 739.33 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.432552E+09 | 739.33 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.479187E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.366143E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.432552E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648944E+09 | 943.63 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.576143E+09 | 878.01 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.659450E+09 | 733.54 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573471E+09 | 545.88 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.613396E+09 | 615.94 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.602389E+09 | 624.51 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.569382E+09 | 620.71 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.634936E+09 | 545.88 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.583436E+09 | 866.69 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.622303E+09 | 843.47 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.646277E+09 | 1147.28 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.651846E+09 | 1147.28 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.738197E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569382E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.659450E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421780E+09 | 588.60 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.372393E+09 | 573.48 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.424936E+09 | 524.74 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367187E+09 | 351.77 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.391807E+09 | 400.69 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.385527E+09 | 408.57 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.365097E+09 | 396.91 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407429E+09 | 351.77 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.375007E+09 | 562.57 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.403452E+09 | 570.26 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.416723E+09 | 739.33 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.423796E+09 | 739.33 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.475513E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.365097E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.424936E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.666630E+09 | 1002.19 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.584869E+09 | 885.71 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.662007E+09 | 749.67 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571493E+09 | 545.86 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.609296E+09 | 608.21 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.597398E+09 | 619.61 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565347E+09 | 615.76 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.632503E+09 | 545.86 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.583539E+09 | 865.94 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.631639E+09 | 864.30 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.662129E+09 | 1147.25 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.677592E+09 | 1147.25 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744444E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565347E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.677592E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.425514E+09 | 649.21 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.374925E+09 | 555.56 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.425435E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369517E+09 | 351.77 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.394974E+09 | 381.06 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.387367E+09 | 399.74 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.365915E+09 | 397.36 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.408823E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375647E+09 | 545.01 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402769E+09 | 514.08 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.425142E+09 | 739.33 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.431972E+09 | 739.33 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478800E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.365915E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.431972E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648507E+09 | 941.80 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.575677E+09 | 875.24 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.658903E+09 | 640.59 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573284E+09 | 545.88 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.613065E+09 | 610.79 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.601942E+09 | 619.84 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.569068E+09 | 615.82 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.634656E+09 | 545.88 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.583037E+09 | 863.78 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621349E+09 | 840.15 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.645880E+09 | 1147.28 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.651651E+09 | 1147.28 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.737702E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569068E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.658903E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421208E+09 | 585.68 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.371976E+09 | 569.19 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.424639E+09 | 518.79 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367102E+09 | 351.77 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.391649E+09 | 397.70 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.385343E+09 | 405.99 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.364936E+09 | 393.76 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407254E+09 | 351.77 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.374783E+09 | 557.98 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.403000E+09 | 565.87 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.416467E+09 | 739.33 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.423404E+09 | 739.33 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.475176E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.364936E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.424639E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.666579E+09 | 1002.12 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.584846E+09 | 885.15 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.661976E+09 | 748.88 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.571488E+09 | 545.86 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.609284E+09 | 608.00 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.597387E+09 | 619.43 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.565338E+09 | 615.56 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.632490E+09 | 545.86 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.583527E+09 | 865.34 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.631619E+09 | 863.73 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.662106E+09 | 1147.25 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.677573E+09 | 1147.25 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.744421E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.565338E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.677573E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.425502E+09 | 649.05 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.374915E+09 | 555.19 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.425424E+09 | 410.74 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.369510E+09 | 351.77 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.394969E+09 | 380.90 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.387348E+09 | 399.63 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.365908E+09 | 397.24 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.408813E+09 | 351.77 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.375640E+09 | 544.62 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.402764E+09 | 513.67 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.425130E+09 | 739.33 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.431963E+09 | 739.33 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.478789E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.365908E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.431963E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648498E+09 | 941.45 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.575644E+09 | 874.67 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.658867E+09 | 640.45 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.573278E+09 | 545.88 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.613056E+09 | 610.59 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.601924E+09 | 619.65 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.569044E+09 | 615.62 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.634647E+09 | 545.88 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.582999E+09 | 863.18 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.621324E+09 | 839.55 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.645869E+09 | 1147.28 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.651645E+09 | 1147.28 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.737679E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.569044E+09 | 545.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.658867E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.421186E+09 | 585.44 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.371967E+09 | 568.83 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.424629E+09 | 518.42 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.367100E+09 | 351.77 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.391634E+09 | 397.58 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.385337E+09 | 405.90 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.364931E+09 | 393.63 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407246E+09 | 351.77 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.374777E+09 | 557.61 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.402994E+09 | 565.52 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.416479E+09 | 739.33 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.423399E+09 | 739.33 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.475168E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.364931E+09 | 351.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.424629E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.668321E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701125E+09 |
February | 0.136985E+10 | 0.585843E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650392E+09 |
March | 0.163685E+10 | 0.662769E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638204E+09 |
April | 0.145243E+10 | 0.571670E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1068443.03 | 0.455249E+09 |
May | 0.157338E+10 | 0.609563E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9726653.42 | 0.306942E+09 |
June | 0.156900E+10 | 0.597626E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49925269.69 | 0.160470E+09 |
July | 0.145680E+10 | 0.565637E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71268855.97 | 81774279.92 |
August | 0.163685E+10 | 0.632701E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35885498.58 | 0.112096E+09 |
September | 0.145243E+10 | 0.584101E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12007414.75 | 0.183654E+09 |
October | 0.150991E+10 | 0.632863E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2867613.77 | 0.346083E+09 |
November | 0.149516E+10 | 0.663154E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566952E+09 |
December | 0.145680E+10 | 0.679187E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655443E+09 |
Annual Sum or Average | 0.181194E+11 | 0.745343E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182750E+09 | 0.485839E+10 |
Minimum of Months | 0.136985E+10 | 0.565637E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81774279.92 |
Maximum of Months | 0.163685E+10 | 0.679187E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71268855.97 | 0.701125E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.426004E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476011E+09 |
February | 0.882782E+09 | 0.375358E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438256E+09 |
March | 0.105485E+10 | 0.425754E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427081E+09 |
April | 0.936002E+09 | 0.369633E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 708440.62 | 0.308602E+09 |
May | 0.101394E+10 | 0.395161E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6030124.30 | 0.209976E+09 |
June | 0.101113E+10 | 0.387673E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33305387.70 | 0.106525E+09 |
July | 0.938820E+09 | 0.366143E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47139637.55 | 54808361.47 |
August | 0.105485E+10 | 0.408972E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23875083.26 | 73063737.65 |
September | 0.936002E+09 | 0.375883E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7710362.75 | 0.125411E+09 |
October | 0.973041E+09 | 0.403091E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1838581.56 | 0.235179E+09 |
November | 0.963541E+09 | 0.425641E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381671E+09 |
December | 0.938820E+09 | 0.432552E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436277E+09 |
Annual Sum or Average | 0.116768E+11 | 0.479187E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120608E+09 | 0.327286E+10 |
Minimum of Months | 0.882782E+09 | 0.366143E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54808361.47 |
Maximum of Months | 0.105485E+10 | 0.432552E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47139637.55 | 0.476011E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.648944E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727501E+09 |
February | 0.136988E+10 | 0.576143E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673724E+09 |
March | 0.163688E+10 | 0.659450E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650887E+09 |
April | 0.145246E+10 | 0.573471E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1055818.44 | 0.464737E+09 |
May | 0.157341E+10 | 0.613396E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9140807.17 | 0.308055E+09 |
June | 0.156904E+10 | 0.602389E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50398891.27 | 0.157697E+09 |
July | 0.145684E+10 | 0.569382E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70643206.11 | 82452427.63 |
August | 0.163688E+10 | 0.634936E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35089217.46 | 0.116674E+09 |
September | 0.145246E+10 | 0.583436E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10832451.47 | 0.194924E+09 |
October | 0.150994E+10 | 0.622303E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2226510.19 | 0.366375E+09 |
November | 0.149520E+10 | 0.646277E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596741E+09 |
December | 0.145684E+10 | 0.651846E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678045E+09 |
Annual Sum or Average | 0.181198E+11 | 0.738197E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179387E+09 | 0.501781E+10 |
Minimum of Months | 0.136988E+10 | 0.569382E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82452427.63 |
Maximum of Months | 0.163688E+10 | 0.659450E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70643206.11 | 0.727501E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.421780E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499174E+09 |
February | 0.882782E+09 | 0.372393E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472014E+09 |
March | 0.105485E+10 | 0.424936E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471542E+09 |
April | 0.936002E+09 | 0.367187E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 702527.02 | 0.352779E+09 |
May | 0.101394E+10 | 0.391807E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5566292.24 | 0.229819E+09 |
June | 0.101113E+10 | 0.385527E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30587809.26 | 0.127303E+09 |
July | 0.938820E+09 | 0.365097E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43293755.56 | 75067452.88 |
August | 0.105485E+10 | 0.407429E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22486336.14 | 0.100527E+09 |
September | 0.936002E+09 | 0.375007E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7471433.84 | 0.141800E+09 |
October | 0.973041E+09 | 0.403452E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1796463.80 | 0.259316E+09 |
November | 0.963541E+09 | 0.416723E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420809E+09 |
December | 0.938820E+09 | 0.423796E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489623E+09 |
Annual Sum or Average | 0.116768E+11 | 0.475513E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111905E+09 | 0.363977E+10 |
Minimum of Months | 0.882782E+09 | 0.365097E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75067452.88 |
Maximum of Months | 0.105485E+10 | 0.424936E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43293755.56 | 0.499174E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.666630E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143619E+10 |
February | 0.136985E+10 | 0.584869E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134608E+10 |
March | 0.163685E+10 | 0.662007E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133651E+10 |
April | 0.145243E+10 | 0.571493E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2329179.29 | 0.967897E+09 |
May | 0.157338E+10 | 0.609296E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22865389.85 | 0.675115E+09 |
June | 0.156900E+10 | 0.597398E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113672E+09 | 0.365922E+09 |
July | 0.145680E+10 | 0.565347E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163295E+09 | 0.207732E+09 |
August | 0.163685E+10 | 0.632503E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83897256.33 | 0.269994E+09 |
September | 0.145243E+10 | 0.583539E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28087873.09 | 0.401274E+09 |
October | 0.150991E+10 | 0.631639E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6780070.79 | 0.728186E+09 |
November | 0.149516E+10 | 0.662129E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115450E+10 |
December | 0.145680E+10 | 0.677592E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131382E+10 |
Annual Sum or Average | 0.181194E+11 | 0.744444E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420926E+09 | 0.102032E+11 |
Minimum of Months | 0.136985E+10 | 0.565347E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207732E+09 |
Maximum of Months | 0.163685E+10 | 0.677592E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163295E+09 | 0.143619E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.425514E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100787E+10 |
February | 0.649041E+09 | 0.374925E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946282E+09 |
March | 0.773965E+09 | 0.425435E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943698E+09 |
April | 0.688021E+09 | 0.369517E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1377450.74 | 0.707103E+09 |
May | 0.744847E+09 | 0.394974E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12733367.52 | 0.482211E+09 |
June | 0.742030E+09 | 0.387367E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73027018.31 | 0.254383E+09 |
July | 0.690839E+09 | 0.365915E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103768E+09 | 0.152937E+09 |
August | 0.773965E+09 | 0.408823E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52551664.01 | 0.196904E+09 |
September | 0.688021E+09 | 0.375647E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16623591.15 | 0.288213E+09 |
October | 0.715730E+09 | 0.402769E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3761887.50 | 0.526604E+09 |
November | 0.708685E+09 | 0.425142E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822793E+09 |
December | 0.690839E+09 | 0.431972E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918057E+09 |
Annual Sum or Average | 0.858171E+10 | 0.478800E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263843E+09 | 0.724705E+10 |
Minimum of Months | 0.649041E+09 | 0.365915E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152937E+09 |
Maximum of Months | 0.773965E+09 | 0.431972E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103768E+09 | 0.100787E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.648507E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163821E+10 |
February | 0.136988E+10 | 0.575677E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151882E+10 |
March | 0.163688E+10 | 0.658903E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145544E+10 |
April | 0.145246E+10 | 0.573284E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2173732.18 | 0.103928E+10 |
May | 0.157341E+10 | 0.613065E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20149894.32 | 0.693476E+09 |
June | 0.156904E+10 | 0.601942E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114684E+09 | 0.361071E+09 |
July | 0.145684E+10 | 0.569068E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161112E+09 | 0.210481E+09 |
August | 0.163688E+10 | 0.634656E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80306154.45 | 0.288056E+09 |
September | 0.145246E+10 | 0.583037E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23171500.36 | 0.446920E+09 |
October | 0.150994E+10 | 0.621349E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4201879.89 | 0.837312E+09 |
November | 0.149520E+10 | 0.645880E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134159E+10 |
December | 0.145684E+10 | 0.651651E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150790E+10 |
Annual Sum or Average | 0.181198E+11 | 0.737702E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405800E+09 | 0.113386E+11 |
Minimum of Months | 0.136988E+10 | 0.569068E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210481E+09 |
Maximum of Months | 0.163688E+10 | 0.658903E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161112E+09 | 0.163821E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.421208E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103007E+10 |
February | 0.882782E+09 | 0.371976E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971073E+09 |
March | 0.105485E+10 | 0.424639E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969128E+09 |
April | 0.936002E+09 | 0.367102E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1447903.86 | 0.725101E+09 |
May | 0.101394E+10 | 0.391649E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12374775.58 | 0.497797E+09 |
June | 0.101113E+10 | 0.385343E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70715856.67 | 0.274311E+09 |
July | 0.938820E+09 | 0.364936E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100679E+09 | 0.164111E+09 |
August | 0.105485E+10 | 0.407254E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52097443.79 | 0.213053E+09 |
September | 0.936002E+09 | 0.374783E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16941745.96 | 0.304628E+09 |
October | 0.973041E+09 | 0.403000E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3985105.09 | 0.539387E+09 |
November | 0.963541E+09 | 0.416467E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844232E+09 |
December | 0.938820E+09 | 0.423404E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948210E+09 |
Annual Sum or Average | 0.116768E+11 | 0.475176E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258242E+09 | 0.748110E+10 |
Minimum of Months | 0.882782E+09 | 0.364936E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164111E+09 |
Maximum of Months | 0.105485E+10 | 0.424639E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100679E+09 | 0.103007E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.666579E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163649E+10 |
February | 0.136985E+10 | 0.584846E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155643E+10 |
March | 0.163685E+10 | 0.661976E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154644E+10 |
April | 0.145243E+10 | 0.571488E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2464870.84 | 0.114604E+10 |
May | 0.157338E+10 | 0.609284E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24233082.51 | 0.817622E+09 |
June | 0.156900E+10 | 0.597387E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134801E+09 | 0.450865E+09 |
July | 0.145680E+10 | 0.565338E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193385E+09 | 0.265009E+09 |
August | 0.163685E+10 | 0.632490E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98048273.07 | 0.340128E+09 |
September | 0.145243E+10 | 0.583527E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32266472.89 | 0.491453E+09 |
October | 0.150991E+10 | 0.631619E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7507765.18 | 0.845733E+09 |
November | 0.149516E+10 | 0.662106E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129823E+10 |
December | 0.145680E+10 | 0.677573E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148352E+10 |
Annual Sum or Average | 0.181194E+11 | 0.744421E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492707E+09 | 0.118780E+11 |
Minimum of Months | 0.136985E+10 | 0.565338E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265009E+09 |
Maximum of Months | 0.163685E+10 | 0.677573E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193385E+09 | 0.163649E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.425502E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114066E+10 |
February | 0.882782E+09 | 0.374915E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108981E+10 |
March | 0.105485E+10 | 0.425424E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110134E+10 |
April | 0.936002E+09 | 0.369510E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1569133.68 | 0.847902E+09 |
May | 0.101394E+10 | 0.394969E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15120911.47 | 0.586057E+09 |
June | 0.101113E+10 | 0.387348E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88428938.88 | 0.313103E+09 |
July | 0.938820E+09 | 0.365908E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125460E+09 | 0.193709E+09 |
August | 0.105485E+10 | 0.408813E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63957671.23 | 0.246082E+09 |
September | 0.936002E+09 | 0.375640E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20329115.69 | 0.352452E+09 |
October | 0.973041E+09 | 0.402764E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4698132.84 | 0.619293E+09 |
November | 0.963541E+09 | 0.425130E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928939E+09 |
December | 0.938820E+09 | 0.431963E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102923E+10 |
Annual Sum or Average | 0.116768E+11 | 0.478789E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319563E+09 | 0.844858E+10 |
Minimum of Months | 0.882782E+09 | 0.365908E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193709E+09 |
Maximum of Months | 0.105485E+10 | 0.431963E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125460E+09 | 0.114066E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.648498E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187334E+10 |
February | 0.136988E+10 | 0.575644E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176459E+10 |
March | 0.163688E+10 | 0.658867E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170513E+10 |
April | 0.145246E+10 | 0.573278E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2345161.74 | 0.124000E+10 |
May | 0.157341E+10 | 0.613056E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23129810.39 | 0.840187E+09 |
June | 0.156904E+10 | 0.601924E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135763E+09 | 0.444451E+09 |
July | 0.145684E+10 | 0.569044E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191682E+09 | 0.268006E+09 |
August | 0.163688E+10 | 0.634647E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95876792.74 | 0.361268E+09 |
September | 0.145246E+10 | 0.582999E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28311997.84 | 0.546717E+09 |
October | 0.150994E+10 | 0.621324E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5746713.59 | 0.988906E+09 |
November | 0.149520E+10 | 0.645869E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154451E+10 |
December | 0.145684E+10 | 0.651645E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171910E+10 |
Annual Sum or Average | 0.181198E+11 | 0.737679E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482855E+09 | 0.132962E+11 |
Minimum of Months | 0.136988E+10 | 0.569044E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268006E+09 |
Maximum of Months | 0.163688E+10 | 0.658867E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191682E+09 | 0.187334E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.421186E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118028E+10 |
February | 0.882782E+09 | 0.371967E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113317E+10 |
March | 0.105485E+10 | 0.424629E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114017E+10 |
April | 0.936002E+09 | 0.367100E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1563568.73 | 0.869041E+09 |
May | 0.101394E+10 | 0.391634E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14502441.33 | 0.604261E+09 |
June | 0.101113E+10 | 0.385337E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85123637.42 | 0.336947E+09 |
July | 0.938820E+09 | 0.364931E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120985E+09 | 0.206302E+09 |
August | 0.105485E+10 | 0.407246E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62623708.19 | 0.265549E+09 |
September | 0.936002E+09 | 0.374777E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20116278.31 | 0.372579E+09 |
October | 0.973041E+09 | 0.402994E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4625581.52 | 0.638376E+09 |
November | 0.963541E+09 | 0.416479E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970623E+09 |
December | 0.938820E+09 | 0.423399E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108440E+10 |
Annual Sum or Average | 0.116768E+11 | 0.475168E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309541E+09 | 0.880169E+10 |
Minimum of Months | 0.882782E+09 | 0.364931E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206302E+09 |
Maximum of Months | 0.105485E+10 | 0.424629E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120985E+09 | 0.118028E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152775E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140566E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136504E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 804899.96 | 0.969669E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17454317.21 | 0.648607E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95005409.59 | 0.339372E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138417E+09 | 0.181809E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65284002.34 | 0.253138E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19933041.62 | 0.390878E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3591713.06 | 0.747890E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122867E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141897E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340490E+09 | 0.104775E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181809E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138417E+09 | 0.152775E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258152E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239938E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234864E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595834.50 | 0.167043E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33384399.68 | 0.113824E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172844E+09 | 0.597614E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252297E+09 | 0.325745E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120871E+09 | 0.445710E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36494351.78 | 0.682918E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6796201.37 | 0.129633E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209982E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237985E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624282E+09 | 0.179662E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325745E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252297E+09 | 0.258152E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258191E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248212E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250125E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60720.14 | 0.187017E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16421951.90 | 0.129451E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151046E+09 | 0.680188E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216804E+09 | 0.389311E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100762E+09 | 0.522881E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24057780.69 | 0.780092E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3181362.56 | 0.138156E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213915E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236557E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512334E+09 | 0.189887E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389311E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216804E+09 | 0.258191E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1004.17 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2012.87 | 16-JAN-17:53 |
February | 2010.79 | 01-FEB-10:09 | 888.42 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1510.82 | 05-FEB-00:55 |
March | 2010.79 | 01-MAR-10:09 | 754.15 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1340.40 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 545.86 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1467.05 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 613.47 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.68 | 14-MAY-17:00 | 905.86 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 624.30 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.44 | 18-JUN-16:04 | 688.82 | 10-JUN-01:20 |
July | 2010.79 | 03-JUL-09:09 | 620.65 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.92 | 04-JUL-14:52 | 336.75 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 545.86 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.80 | 20-AUG-16:51 | 355.58 | 22-AUG-21:40 |
September | 2010.79 | 01-SEP-09:09 | 868.83 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.76 | 03-SEP-14:54 | 521.52 | 18-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 867.48 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.19 | 11-OCT-13:00 | 831.51 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1519.11 | 26-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2120.57 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.75 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 494.92 | 2120.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 651.44 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1346.85 | 16-JAN-17:53 |
February | 1295.83 | 01-FEB-10:09 | 560.06 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1011.62 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 885.62 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 29-APR-16:00 | 998.37 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 384.68 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.24 | 14-MAY-16:13 | 598.55 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 402.63 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.05 | 18-JUN-16:03 | 450.56 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 400.37 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 04-JUL-14:59 | 228.02 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.25 | 20-AUG-17:04 | 313.08 | 27-AUG-07:40 |
September | 1295.83 | 01-SEP-09:09 | 549.64 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.55 | 03-SEP-14:54 | 358.09 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 519.11 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 11-OCT-13:00 | 549.77 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 995.38 | 26-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1391.72 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.02 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 1391.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 943.63 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2000.75 | 16-JAN-17:53 |
February | 2010.83 | 01-FEB-10:09 | 878.01 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1558.68 | 05-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 733.54 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1351.71 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 545.88 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1479.69 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 615.94 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.82 | 14-MAY-16:54 | 893.99 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 624.51 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.01 | 18-JUN-16:03 | 673.60 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 620.71 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.92 | 04-JUL-14:53 | 346.29 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 545.88 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.04 | 20-AUG-16:51 | 368.67 | 22-AUG-21:40 |
September | 2010.83 | 01-SEP-09:09 | 866.69 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.38 | 03-SEP-14:53 | 554.24 | 18-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 843.47 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.87 | 11-OCT-14:50 | 855.54 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1515.99 | 26-NOV-09:50 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2143.97 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.29 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 494.92 | 2143.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 588.60 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1413.92 | 16-JAN-17:53 |
February | 1295.83 | 01-FEB-10:09 | 573.48 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1107.35 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 524.74 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 997.76 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 29-APR-16:00 | 1105.25 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 400.69 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.49 | 14-MAY-16:53 | 645.72 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 408.57 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.90 | 18-JUN-16:10 | 543.29 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 396.91 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 04-JUL-15:00 | 289.39 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 | 20-AUG-16:45 | 328.17 | 22-AUG-21:40 |
September | 1295.83 | 01-SEP-09:09 | 562.57 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.54 | 03-SEP-14:54 | 399.69 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 570.26 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 11-OCT-13:00 | 610.15 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1110.06 | 26-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1569.74 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.39 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 1569.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1002.19 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3850.91 | 16-JAN-17:53 |
February | 2010.79 | 01-FEB-10:09 | 885.71 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3010.83 | 05-FEB-00:55 |
March | 2010.79 | 01-MAR-10:09 | 749.67 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2660.50 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 545.86 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 29-APR-16:00 | 3090.45 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 608.21 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.59 | 14-MAY-17:00 | 1965.14 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 619.61 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 836.79 | 18-JUN-16:14 | 1455.00 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 615.76 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1162.58 | 04-JUL-14:53 | 811.51 | 15-JUL-18:55 |
August | 2010.79 | 01-AUG-09:09 | 545.86 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.10 | 20-AUG-16:51 | 761.87 | 22-AUG-21:55 |
September | 2010.79 | 01-SEP-09:09 | 865.94 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.25 | 03-SEP-14:40 | 1079.66 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 864.30 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.79 | 01-OCT-16:00 | 1808.61 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3139.40 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4132.15 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.87 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1162.58 | 4132.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 649.21 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2633.58 | 16-JAN-17:53 |
February | 1239.33 | 01-FEB-08:09 | 555.56 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2080.63 | 05-FEB-00:55 |
March | 1239.33 | 01-MAR-08:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1837.89 | 14-MAR-03:00 |
April | 1239.33 | 03-APR-07:10 | 351.77 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 29-APR-16:00 | 2262.62 | 23-APR-09:10 |
May | 1239.33 | 01-MAY-07:10 | 381.06 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.00 | 14-MAY-16:13 | 1319.39 | 03-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 399.74 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.62 | 18-JUN-16:14 | 1021.60 | 04-JUN-16:55 |
July | 1239.33 | 03-JUL-07:10 | 397.36 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 791.25 | 04-JUL-14:53 | 587.72 | 15-JUL-18:55 |
August | 1239.33 | 01-AUG-07:10 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.12 | 20-AUG-16:51 | 739.30 | 27-AUG-08:10 |
September | 1239.33 | 01-SEP-07:10 | 545.01 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.60 | 03-SEP-14:23 | 787.48 | 17-SEP-19:55 |
October | 1239.33 | 02-OCT-07:10 | 514.08 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.30 | 11-OCT-13:00 | 1222.31 | 11-OCT-23:00 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2140.84 | 03-NOV-21:03 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2809.08 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.72 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 791.25 | 2809.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 941.80 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4319.95 | 16-JAN-17:53 |
February | 2010.83 | 01-FEB-10:09 | 875.24 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3378.50 | 05-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 640.59 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2850.41 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 545.88 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 29-APR-16:00 | 3202.52 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 610.79 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.58 | 14-MAY-16:53 | 1953.26 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 619.84 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 850.17 | 18-JUN-16:14 | 1458.12 | 04-JUN-16:55 |
July | 2010.83 | 03-JUL-09:09 | 615.82 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.66 | 04-JUL-14:53 | 835.80 | 15-JUL-18:55 |
August | 2010.83 | 01-AUG-09:09 | 545.88 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.05 | 20-AUG-16:52 | 804.90 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 863.78 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.91 | 03-SEP-14:43 | 1271.03 | 17-SEP-19:55 |
October | 2010.83 | 02-OCT-09:09 | 840.15 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.84 | 01-OCT-15:53 | 1900.71 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3407.01 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4503.13 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 804.90 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.66 | 4503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 585.68 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2754.05 | 16-JAN-17:53 |
February | 1295.83 | 01-FEB-10:09 | 569.19 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2189.92 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 518.79 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1876.99 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 29-APR-16:00 | 2359.94 | 15-APR-17:02 |
May | 1295.83 | 01-MAY-09:09 | 397.70 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.49 | 14-MAY-16:53 | 1353.34 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 405.99 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.12 | 18-JUN-16:00 | 1078.55 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 393.76 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 764.30 | 04-JUL-15:00 | 624.96 | 15-JUL-18:55 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.03 | 20-AUG-17:00 | 592.25 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 557.98 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.11 | 03-SEP-14:23 | 895.45 | 17-SEP-19:55 |
October | 1295.83 | 02-OCT-09:09 | 565.87 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.31 | 11-OCT-13:00 | 1269.18 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2267.45 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2907.68 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.25 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 764.30 | 2907.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1002.12 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4431.54 | 16-JAN-17:57 |
February | 2010.79 | 01-FEB-10:09 | 885.15 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3488.42 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 748.88 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3243.01 | 14-MAR-04:57 |
April | 2010.79 | 03-APR-09:09 | 545.86 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 29-APR-16:00 | 3646.27 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 608.00 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.60 | 14-MAY-16:40 | 2323.02 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 619.43 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1065.11 | 18-JUN-15:54 | 1864.69 | 04-JUN-16:55 |
July | 2010.79 | 03-JUL-09:09 | 615.56 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1365.45 | 04-JUL-14:51 | 1052.86 | 15-JUL-18:55 |
August | 2010.79 | 01-AUG-09:09 | 545.86 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.61 | 20-AUG-16:52 | 941.23 | 10-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 865.34 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 439.24 | 03-SEP-14:25 | 1289.49 | 17-SEP-19:55 |
October | 2010.79 | 02-OCT-09:09 | 863.73 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.03 | 01-OCT-16:00 | 2170.62 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3762.29 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4974.65 | 14-DEC-04:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.23 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1365.45 | 4974.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 649.05 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3007.11 | 16-JAN-17:55 |
February | 1295.83 | 01-FEB-10:09 | 555.19 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2325.71 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 410.74 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2151.59 | 14-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 29-APR-16:00 | 2714.22 | 23-APR-09:10 |
May | 1295.83 | 01-MAY-09:09 | 380.90 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.05 | 14-MAY-16:24 | 1560.79 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 399.63 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 698.52 | 18-JUN-15:53 | 1309.03 | 04-JUN-16:55 |
July | 1295.83 | 03-JUL-09:09 | 397.24 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.01 | 04-JUL-15:03 | 754.10 | 15-JUL-18:55 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.52 | 20-AUG-16:51 | 909.91 | 27-AUG-08:10 |
September | 1295.83 | 01-SEP-09:09 | 544.62 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.96 | 03-SEP-14:23 | 988.18 | 17-SEP-19:55 |
October | 1295.83 | 02-OCT-09:09 | 513.67 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.80 | 01-OCT-15:53 | 1466.45 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2547.84 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3339.66 | 14-DEC-04:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.10 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 937.01 | 3339.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 941.45 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4456.79 | 16-JAN-17:53 |
February | 2010.83 | 01-FEB-10:09 | 874.67 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3756.48 | 05-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 640.45 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3247.01 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 545.88 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 29-APR-16:00 | 3800.36 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 610.59 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.56 | 14-MAY-16:24 | 2307.38 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 619.65 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.73 | 18-JUN-15:53 | 1879.27 | 04-JUN-16:55 |
July | 2010.83 | 03-JUL-09:09 | 615.62 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.59 | 04-JUL-14:51 | 1082.33 | 15-JUL-18:55 |
August | 2010.83 | 01-AUG-09:09 | 545.88 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.61 | 20-AUG-16:55 | 983.71 | 22-AUG-21:55 |
September | 2010.83 | 01-SEP-09:09 | 863.18 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.75 | 03-SEP-14:25 | 1582.50 | 17-SEP-19:55 |
October | 2010.83 | 02-OCT-09:09 | 839.55 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.27 | 11-OCT-15:00 | 2284.49 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4081.55 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4979.44 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 983.71 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.59 | 4979.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 585.44 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2961.38 | 16-JAN-17:55 |
February | 1295.83 | 01-FEB-10:09 | 568.83 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2464.35 | 05-FEB-00:55 |
March | 1295.83 | 01-MAR-10:09 | 518.42 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2149.11 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 351.77 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 29-APR-16:00 | 2926.42 | 15-APR-17:02 |
May | 1295.83 | 01-MAY-09:09 | 397.58 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.67 | 19-MAY-15:00 | 1609.92 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 405.90 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 658.25 | 18-JUN-16:00 | 1309.52 | 04-JUN-16:55 |
July | 1295.83 | 03-JUL-09:09 | 393.63 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 887.55 | 04-JUL-15:10 | 798.71 | 15-JUL-18:55 |
August | 1295.83 | 01-AUG-09:09 | 351.77 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.41 | 20-AUG-17:00 | 725.92 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 557.61 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.44 | 03-SEP-14:23 | 1107.88 | 17-SEP-19:55 |
October | 1295.83 | 02-OCT-09:09 | 565.52 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.11 | 11-OCT-13:00 | 1530.38 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2715.15 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3343.56 | 14-DEC-04:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725.92 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 887.55 | 3343.56 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4358.64 | 16-JAN-17:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3376.20 | 05-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2912.44 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 26-APR-15:00 | 3124.01 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.07 | 14-MAY-17:00 | 1907.96 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.23 | 18-JUN-15:51 | 1468.45 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.54 | 04-JUL-15:00 | 679.91 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.91 | 05-AUG-17:01 | 742.22 | 22-AUG-21:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.18 | 03-SEP-15:00 | 1089.81 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.08 | 01-OCT-15:51 | 1753.86 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3369.51 | 26-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4687.37 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.54 | 4687.37 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7221.27 | 16-JAN-17:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5740.83 | 05-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4928.90 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 | 17-APR-15:00 | 5439.24 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.81 | 14-MAY-17:00 | 3355.11 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.52 | 18-JUN-16:00 | 2550.17 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1831.16 | 04-JUL-15:00 | 1233.97 | 15-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.32 | 05-AUG-17:01 | 1267.12 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.38 | 03-SEP-14:50 | 1861.91 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.54 | 01-OCT-16:00 | 3067.58 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5677.41 | 26-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7907.99 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1831.16 | 7907.99 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6819.96 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5636.89 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4984.55 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 | 13-APR-17:00 | 5870.59 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.70 | 19-MAY-15:00 | 3606.09 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.89 | 18-JUN-16:10 | 2868.40 | 04-JUN-16:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1571.46 | 04-JUL-16:51 | 1654.42 | 15-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 804.90 | 20-AUG-17:00 | 1410.89 | 10-AUG-21:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.25 | 03-SEP-14:10 | 2078.46 | 17-SEP-19:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.16 | 01-OCT-16:00 | 3378.39 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6106.24 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7684.88 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1571.46 | 7684.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 97611.51 | 02-JAN-04:11 | 0.00 | 4521.71 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95735.29 | 13-FEB-04:12 | 0.00 | 2826.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96094.61 | 27-MAR-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97417.89 | 24-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96817.25 | 01-MAY-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98310.35 | 12-JUN-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85946.47 | 19-JUL-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88762.41 | 31-AUG-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93246.06 | 25-SEP-05:03 | 7180.90 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95726.95 | 16-OCT-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99971.30 | 12-NOV-13:20 | 8078.51 | 5086.92 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 98253.77 | 11-DEC-05:01 | 0.00 | 11304.27 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 85946.47 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99971.30 | 8078.51 | 11304.27 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76994.09 | 02-JAN-05:01 | 0.00 | 7106.42 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82834.05 | 21-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80991.19 | 27-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83252.98 | 24-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86669.13 | 22-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86862.62 | 05-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79004.59 | 08-JUL-04:12 | 0.00 | 3045.61 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84678.13 | 21-AUG-04:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84460.99 | 11-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86188.57 | 10-OCT-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82726.95 | 24-NOV-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80549.95 | 26-DEC-04:01 | 0.00 | 3553.21 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 76994.09 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86862.62 | 0.00 | 7106.42 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30539.95 | 05-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66544.83 | 15-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67044.37 | 17-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71176.99 | 27-APR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73334.19 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73954.59 | 05-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76028.86 | 05-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75083.29 | 28-AUG-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74995.06 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73063.99 | 03-OCT-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70235.52 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56429.31 | 01-DEC-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 30539.95 | 0.00 | 2149.44 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76028.86 | 9673.43 | 3761.52 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18979.12 | 05-JAN-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30653.04 | 15-FEB-16:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31762.52 | 08-MAR-16:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66900.62 | 27-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75208.03 | 22-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75107.81 | 19-JUN-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81397.22 | 05-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82273.93 | 21-AUG-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77586.00 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73323.01 | 02-OCT-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33457.91 | 01-NOV-15:20 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19988.18 | 01-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18979.12 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82273.93 | 15316.26 | 9137.09 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2885.17 | 02-JAN-13:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.65 |
February | 4312.82 | 21-FEB-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.09 |
March | 6698.26 | 27-MAR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 |
April | 8346.50 | 14-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
May | 13740.85 | 14-MAY-16:11 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 80.50 | 0.00 |
June | 16974.48 | 25-JUN-17:42 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 197.42 | 0.00 |
July | 16800.04 | 02-JUL-18:01 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 122.21 | 0.00 |
August | 16521.70 | 13-AUG-16:21 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | 0.00 |
September | 16235.81 | 04-SEP-16:01 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
October | 10286.44 | 02-OCT-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 |
November | 4788.92 | 08-NOV-13:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.01 |
December | 3560.60 | 01-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2885.17 | 0.00 | 242.60 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16974.48 | 3846.22 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 197.42 | 112.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10977.01 | 01-JAN-10:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.77 |
February | 15509.42 | 19-FEB-09:02 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.59 |
March | 19194.89 | 26-MAR-08:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.74 |
April | 21903.11 | 30-APR-08:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.99 |
May | 24125.00 | 14-MAY-08:51 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.24 |
June | 25136.22 | 18-JUN-08:61 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.22 |
July | 25002.95 | 30-JUL-08:31 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.06 |
August | 23761.75 | 13-AUG-07:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
September | 23863.29 | 03-SEP-07:31 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.41 |
October | 23498.06 | 01-OCT-08:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.22 |
November | 14412.77 | 05-NOV-09:02 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.36 |
December | 7329.21 | 29-DEC-09:20 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7329.21 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 | |
Maximum of Months | 25136.22 | 1239.33 | 351.77 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24310.00 | 01-JAN-12:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.85 |
February | 22306.01 | 12-FEB-13:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.09 |
March | 21448.40 | 26-MAR-12:32 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.58 |
April | 20891.85 | 16-APR-13:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.63 |
May | 20629.86 | 14-MAY-14:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 | 0.00 |
June | 20966.48 | 25-JUN-14:21 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 79.34 | 0.00 |
July | 22378.71 | 30-JUL-14:31 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 96.12 | 0.00 |
August | 22242.22 | 13-AUG-15:01 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 0.00 |
September | 23539.71 | 10-SEP-12:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 |
October | 24578.96 | 15-OCT-11:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22528.52 | 12-NOV-12:42 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.11 |
December | 23006.84 | 31-DEC-13:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20629.86 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24578.96 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 96.12 | 253.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26357.94 | 01-JAN-15:11 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.13 |
February | 18723.56 | 12-FEB-14:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 |
March | 27803.62 | 12-MAR-16:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.48 |
April | 29681.44 | 16-APR-16:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.26 |
May | 30724.28 | 14-MAY-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.20 |
June | 32923.27 | 25-JUN-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 | 0.00 |
July | 32975.78 | 30-JUL-15:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 42.30 | 0.00 |
August | 33290.91 | 13-AUG-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 |
September | 29858.81 | 04-SEP-16:41 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 |
October | 30145.44 | 01-OCT-15:21 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
November | 24066.49 | 12-NOV-15:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.56 |
December | 23729.80 | 31-DEC-15:22 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18723.56 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33290.91 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 | 244.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2047.73 | 05-JAN-16:00 | 1923.11 | 582.04 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.02 |
February | 2513.51 | 15-FEB-15:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 |
March | 4301.42 | 27-MAR-14:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.35 |
April | 7178.32 | 14-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 |
May | 7968.58 | 31-MAY-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 109.03 | 0.00 |
June | 15612.48 | 11-JUN-18:41 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.45 |
July | 16598.71 | 04-JUL-18:52 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 389.82 | 0.00 |
August | 15258.23 | 13-AUG-16:51 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 115.76 | 0.00 |
September | 15192.86 | 04-SEP-16:51 | 910.95 | 272.92 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 |
October | 7258.69 | 02-OCT-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 0.00 |
November | 2755.22 | 03-NOV-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.06 |
December | 1917.76 | 29-DEC-16:10 | 1923.11 | 843.09 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1917.76 | 0.00 | 272.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16598.71 | 2010.79 | 843.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 389.82 | 176.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5536.52 | 27-JAN-09:40 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10361.73 | 19-FEB-10:13 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.04 |
March | 23471.26 | 26-MAR-09:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.52 |
April | 26115.03 | 30-APR-08:11 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.01 |
May | 26443.32 | 29-MAY-07:51 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.09 |
June | 26691.89 | 11-JUN-09:21 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.92 |
July | 28284.52 | 04-JUL-08:51 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.19 |
August | 27073.05 | 06-AUG-09:21 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.66 |
September | 24843.67 | 17-SEP-08:41 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.18 |
October | 23030.35 | 09-OCT-09:32 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.29 |
November | 9848.94 | 01-NOV-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.06 |
December | 5207.12 | 29-DEC-09:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5207.12 | 260.91 | 78.17 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28284.52 | 2478.65 | 703.55 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22694.68 | 22-JAN-13:51 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.06 |
February | 23205.70 | 19-FEB-11:31 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.45 |
March | 23396.66 | 12-MAR-13:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.40 |
April | 21449.91 | 30-APR-12:52 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.09 |
May | 20333.21 | 14-MAY-14:51 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 90.74 | 0.00 |
June | 19531.00 | 25-JUN-16:31 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 579.65 | 0.00 |
July | 22121.41 | 30-JUL-14:31 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 211.08 | 0.00 |
August | 21904.56 | 27-AUG-12:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 |
September | 23990.07 | 10-SEP-12:51 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 |
October | 24461.55 | 09-OCT-14:51 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.50 |
November | 24204.10 | 05-NOV-12:11 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1516.55 |
December | 23203.49 | 31-DEC-14:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19531.00 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24461.55 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 579.65 | 1516.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9047.04 | 26-JAN-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.55 |
February | 13312.24 | 15-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
March | 25560.77 | 12-MAR-16:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.10 |
April | 26626.51 | 16-APR-16:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.41 |
May | 28805.15 | 14-MAY-16:11 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.42 |
June | 30765.87 | 11-JUN-16:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.11 |
July | 30338.91 | 04-JUL-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 0.00 |
August | 29413.28 | 13-AUG-16:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 0.00 |
September | 27522.86 | 04-SEP-16:51 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.83 |
October | 26564.05 | 09-OCT-14:51 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.54 |
November | 18831.11 | 19-NOV-15:31 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.75 |
December | 8479.08 | 31-DEC-15:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8479.08 | 391.37 | 117.25 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30765.87 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 830.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1947.79 | 05-JAN-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.76 |
February | 2277.54 | 15-FEB-16:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.79 |
March | 3591.75 | 27-MAR-15:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.84 |
April | 7547.47 | 14-APR-14:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
May | 17680.65 | 29-MAY-16:01 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 |
June | 18974.43 | 18-JUN-17:51 | 0.00 | 303.25 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 312.36 | 0.00 |
July | 19554.59 | 04-JUL-15:01 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.14 | 0.00 |
August | 18785.76 | 06-AUG-16:51 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 294.62 | 0.00 |
September | 15173.93 | 03-SEP-13:41 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 330.34 | 0.00 |
October | 7829.88 | 02-OCT-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
November | 2257.31 | 02-NOV-15:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.53 |
December | 1824.22 | 29-DEC-15:40 | 1923.11 | 591.67 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1824.22 | 0.00 | 212.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19554.59 | 2010.79 | 591.67 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1089.14 | 146.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3327.02 | 27-JAN-10:00 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7155.44 | 14-FEB-09:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 |
March | 14508.79 | 26-MAR-09:32 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.29 |
April | 23409.39 | 30-APR-09:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.37 |
May | 27064.53 | 29-MAY-08:41 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.78 |
June | 27968.30 | 18-JUN-08:31 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.58 |
July | 28746.87 | 04-JUL-09:01 | 652.28 | 195.42 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.49 |
August | 26019.54 | 27-AUG-08:51 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.44 |
September | 24616.12 | 03-SEP-09:01 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.01 |
October | 24755.67 | 01-OCT-09:11 | 456.59 | 136.80 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.68 |
November | 8598.01 | 01-NOV-09:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.43 |
December | 3152.66 | 29-DEC-09:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3152.66 | 391.37 | 117.25 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28746.87 | 2591.66 | 703.55 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24644.29 | 01-JAN-15:11 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1186.05 |
February | 24530.02 | 19-FEB-13:21 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1389.43 |
March | 24565.39 | 26-MAR-14:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.96 |
April | 22369.76 | 30-APR-14:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.12 |
May | 22623.28 | 29-MAY-15:21 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 |
June | 23119.84 | 18-JUN-15:51 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 806.54 | 0.00 |
July | 24773.57 | 04-JUL-14:21 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 870.60 | 0.00 |
August | 24830.12 | 06-AUG-12:51 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 116.70 | 0.00 |
September | 25326.70 | 03-SEP-13:01 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 148.62 | 0.00 |
October | 27826.75 | 01-OCT-11:11 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.96 |
November | 24711.13 | 19-NOV-14:01 | 910.97 | 272.93 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 988.32 |
December | 24798.22 | 31-DEC-14:02 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22369.76 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27826.75 | 1012.19 | 303.26 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 870.60 | 1389.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8365.75 | 26-JAN-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.34 |
February | 13244.91 | 15-FEB-16:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.37 |
March | 26250.78 | 26-MAR-15:32 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.35 |
April | 31091.58 | 16-APR-17:01 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.11 |
May | 30510.32 | 07-MAY-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.59 |
June | 33114.48 | 18-JUN-16:31 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 0.00 |
July | 31793.47 | 04-JUL-15:01 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 505.48 | 0.00 |
August | 30398.63 | 06-AUG-17:31 | 0.00 | 195.42 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 |
September | 27635.35 | 24-SEP-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 |
October | 29453.94 | 01-OCT-15:11 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 |
November | 11182.08 | 02-NOV-15:50 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.52 |
December | 7172.52 | 29-DEC-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7172.52 | 0.00 | 117.25 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33114.48 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 505.48 | 411.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4709.78 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.35 |
February | 4116.66 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.70 |
March | 5454.28 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.42 |
April | 6633.31 | 03-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.50 |
May | 9612.50 | 30-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 |
June | 11125.02 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.08 |
July | 13501.14 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
August | 13806.35 | 21-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.41 |
September | 12368.89 | 05-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 |
October | 9791.66 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.91 |
November | 4883.49 | 24-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.65 |
December | 2830.96 | 19-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 | |
Maximum of Months | 13806.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9900.02 | 17-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4894.88 |
February | 8557.43 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2884.83 |
March | 6665.15 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3169.79 |
April | 4630.01 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 | 0.00 |
May | 5783.21 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 | 0.00 |
June | 7344.59 | 27-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.46 | 0.00 |
July | 9036.14 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.74 |
August | 8831.26 | 21-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.56 |
September | 8024.23 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.30 |
October | 6428.07 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.25 |
November | 5630.87 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.11 |
December | 8358.76 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2286.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4630.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9900.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.46 | 4894.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3177.86 | 01-JAN-14:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.73 |
February | 6381.57 | 15-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.32 |
March | 9584.81 | 08-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.43 |
April | 15238.55 | 28-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.73 |
May | 18137.35 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 0.00 |
June | 23078.33 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.31 | 0.00 |
July | 22344.29 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.31 | 0.00 |
August | 20839.90 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 0.00 |
September | 20288.50 | 12-SEP-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 0.00 |
October | 17290.73 | 02-OCT-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
November | 5478.92 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.50 |
December | 2364.59 | 31-DEC-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2364.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23078.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.31 | 706.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2412.01 | 01-JAN-16:47 | 35.07 | 24.39 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4341.10 | 15-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7086.74 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8291.16 | 15-APR-18:10 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3470.56 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5329.43 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7252.97 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7959.70 | 27-AUG-18:35 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3477.57 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5281.22 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6454.78 | 05-NOV-16:47 | 35.07 | 24.39 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8202.72 | 31-DEC-16:40 | 70.15 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2412.01 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8291.16 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2221.59 | 26-JAN-17:00 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4122.57 | 15-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6551.06 | 31-MAR-23:30 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7888.08 | 16-APR-18:20 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3280.61 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5132.74 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6961.70 | 31-JUL-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7517.49 | 30-AUG-17:40 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3276.96 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4854.65 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5906.20 | 02-NOV-16:50 | 70.15 | 81.29 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7483.38 | 29-DEC-16:50 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2221.59 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7888.08 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2117.35 | 26-JAN-17:00 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4143.46 | 15-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6211.57 | 31-MAR-23:10 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8018.78 | 16-APR-18:00 | 0.00 | 56.91 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3205.55 | 31-MAY-23:50 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5119.42 | 30-JUN-24:00 | 0.00 | 16.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7015.49 | 04-JUL-18:35 | 0.00 | 65.03 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7677.82 | 27-AUG-18:22 | 0.00 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3220.58 | 30-SEP-23:40 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4629.08 | 31-OCT-23:30 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5896.16 | 02-NOV-16:50 | 70.15 | 81.29 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7398.56 | 29-DEC-16:50 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2117.35 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8018.78 | 222.14 | 146.32 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91673.06 | 02-JAN-17:00 | 4808.68 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182817.82 | 15-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358454.84 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368455.87 | 29-APR-17:31 | 2277.80 | 1434.29 | 3416692.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175737.95 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267410.86 | 30-JUN-24:00 | 0.00 | 318.73 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356973.92 | 31-JUL-23:20 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 378088.23 | 18-AUG-21:12 | 1518.53 | 1912.39 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176434.93 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268422.46 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275856.87 | 24-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367046.72 | 26-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91673.06 | 0.00 | 159.37 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 378088.23 | 4808.68 | 2868.67 | 3416692.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.148263E+13 | 927966.13 | 05-JAN-16:40 | 0.286199E+12 | 789773.81 | 17-JAN-07:10 |
February | 0.170621E+13 | 1218620.89 | 14-FEB-16:30 | 0.198258E+12 | 801450.05 | 06-FEB-07:10 |
March | 0.230113E+13 | 1406229.54 | 08-MAR-16:19 | 0.115718E+12 | 436780.94 | 02-MAR-14:20 |
April | 0.269137E+13 | 1690172.10 | 26-APR-15:09 | 0.705440E+11 | 261349.24 | 08-APR-06:10 |
May | 0.170172E+13 | 1225322.40 | 09-MAY-15:20 | 0.644588E+11 | 134636.47 | 06-MAY-06:10 |
June | 0.216888E+13 | 1487880.85 | 27-JUN-15:09 | 0.590249E+11 | 75916.53 | 02-JUN-11:30 |
July | 0.269677E+13 | 1657305.87 | 21-JUL-15:50 | 0.558999E+11 | 73115.98 | 03-JUL-11:20 |
August | 0.316677E+13 | 1846628.42 | 17-AUG-15:50 | 0.588241E+11 | 72339.88 | 31-AUG-11:50 |
September | 0.160549E+13 | 1214882.47 | 12-SEP-15:00 | 0.558169E+11 | 74205.63 | 26-SEP-11:39 |
October | 0.199338E+13 | 1346617.73 | 11-OCT-15:00 | 0.848303E+11 | 450064.96 | 26-OCT-06:10 |
November | 0.217675E+13 | 1285349.88 | 02-NOV-15:09 | 0.122788E+12 | 583464.77 | 27-NOV-07:10 |
December | 0.253167E+13 | 1330320.19 | 29-DEC-16:00 | 0.275351E+12 | 756503.12 | 15-DEC-07:10 |
Annual Sum or Average | 0.262228E+14 | 0.144771E+13 | ||||
Minimum of Months | 0.148263E+13 | 927966.13 | 0.558169E+11 | 72339.88 | ||
Maximum of Months | 0.316677E+13 | 1846628.42 | 0.286199E+12 | 801450.05 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.309939E+11 | 62111.19 | 19-JAN-12:30 | 0.00 | 0.00 |
February | 0.372592E+11 | 75039.34 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.502014E+11 | 83372.76 | 25-MAR-12:09 | 0.00 | 0.00 |
April | 0.640648E+11 | 89495.83 | 24-APR-11:09 | 0.00 | 0.00 |
May | 0.689245E+11 | 89495.83 | 01-MAY-12:09 | 0.00 | 0.00 |
June | 0.685975E+11 | 89495.83 | 09-JUN-12:50 | 0.00 | 0.00 |
July | 0.684214E+11 | 86536.08 | 12-JUL-11:30 | 0.00 | 0.00 |
August | 0.649971E+11 | 85841.97 | 07-AUG-12:00 | 0.00 | 0.00 |
September | 0.528672E+11 | 81911.75 | 13-SEP-12:30 | 0.00 | 0.00 |
October | 0.434712E+11 | 72612.81 | 13-OCT-11:39 | 0.00 | 0.00 |
November | 0.322321E+11 | 65151.23 | 01-NOV-11:50 | 0.00 | 0.00 |
December | 0.285848E+11 | 53905.19 | 14-DEC-12:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.610615E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.285848E+11 | 53905.19 | 0.00 | 0.00 | |
Maximum of Months | 0.689245E+11 | 89495.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.144390E+12 | 0.291364E+11 | 0.766053E+12 | 0.102194E+12 | 0.188515E+12 | 0.196607E+11 | 0.00 | 0.252090E+11 | 0.225559E+10 | 0.205218E+12 | 0.00 | 0.00 | 0.00 |
February | 0.130331E+12 | 0.238094E+11 | 0.978954E+12 | 0.923109E+11 | 0.174176E+12 | 0.196431E+11 | 0.00 | 0.426472E+11 | 0.703815E+10 | 0.237303E+12 | 0.00 | 0.00 | 0.00 |
March | 0.153712E+12 | 0.228313E+11 | 0.141687E+13 | 0.102362E+12 | 0.206645E+12 | 0.236768E+11 | 0.00 | 0.846395E+11 | 0.237530E+11 | 0.266635E+12 | 0.00 | 0.00 | 0.00 |
April | 0.136614E+12 | 0.187498E+11 | 0.165903E+13 | 0.988819E+11 | 0.225637E+12 | 0.297889E+11 | 0.00 | 0.203043E+12 | 0.605825E+11 | 0.259050E+12 | 0.00 | 0.00 | 0.00 |
May | 0.147160E+12 | 0.166381E+11 | 0.774844E+12 | 0.102278E+12 | 0.245258E+12 | 0.345844E+11 | 0.00 | 0.130529E+12 | 0.635179E+11 | 0.186913E+12 | 0.00 | 0.00 | 0.00 |
June | 0.146120E+12 | 0.150332E+11 | 0.106252E+13 | 0.990391E+11 | 0.274677E+12 | 0.511173E+11 | 0.00 | 0.314884E+12 | 0.987777E+11 | 0.106712E+12 | 0.00 | 0.00 | 0.00 |
July | 0.137018E+12 | 0.159855E+11 | 0.139340E+13 | 0.102120E+12 | 0.293894E+12 | 0.610826E+11 | 0.00 | 0.527536E+12 | 0.139895E+12 | 0.258306E+11 | 0.00 | 0.00 | 0.00 |
August | 0.152658E+12 | 0.182064E+11 | 0.173200E+13 | 0.102362E+12 | 0.295414E+12 | 0.618728E+11 | 0.00 | 0.585818E+12 | 0.135119E+12 | 0.833174E+11 | 0.00 | 0.00 | 0.00 |
September | 0.137042E+12 | 0.205644E+11 | 0.740713E+12 | 0.988811E+11 | 0.239668E+12 | 0.433543E+11 | 0.00 | 0.177584E+12 | 0.857021E+11 | 0.619768E+11 | 0.00 | 0.00 | 0.00 |
October | 0.143152E+12 | 0.248835E+11 | 0.108340E+13 | 0.102194E+12 | 0.219946E+12 | 0.328982E+11 | 0.00 | 0.125392E+12 | 0.471085E+11 | 0.214409E+12 | 0.00 | 0.00 | 0.00 |
November | 0.142848E+12 | 0.273234E+11 | 0.135889E+13 | 0.989457E+11 | 0.192296E+12 | 0.220298E+11 | 0.00 | 0.669627E+11 | 0.104410E+11 | 0.257011E+12 | 0.00 | 0.00 | 0.00 |
December | 0.140852E+12 | 0.300317E+11 | 0.170972E+13 | 0.102121E+12 | 0.189318E+12 | 0.222986E+11 | 0.00 | 0.624696E+11 | 0.701510E+10 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171190E+13 | 0.263193E+12 | 0.146764E+14 | 0.120369E+13 | 0.274544E+13 | 0.422007E+12 | 0.00 | 0.234671E+13 | 0.681205E+12 | 0.217222E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130331E+12 | 0.150332E+11 | 0.740713E+12 | 0.923109E+11 | 0.174176E+12 | 0.196431E+11 | 0.00 | 0.252090E+11 | 0.225559E+10 | 0.258306E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153712E+12 | 0.300317E+11 | 0.173200E+13 | 0.102362E+12 | 0.295414E+12 | 0.618728E+11 | 0.00 | 0.585818E+12 | 0.139895E+12 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.218214E+12 | 0.00 | 0.679847E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.136249E+12 | 0.00 | 0.620089E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.453352E+11 | 0.00 | 0.703832E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.785307E+10 | 0.00 | 0.626910E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.137558E+10 | 0.00 | 0.630832E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4866146.28 | 0.00 | 0.590200E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.558999E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.588241E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2127.87 | 0.00 | 0.558169E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.247152E+11 | 0.00 | 0.601152E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.610604E+11 | 0.00 | 0.617273E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.210367E+12 | 0.00 | 0.649836E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.705175E+12 | 0.00 | 0.742538E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.558169E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.218214E+12 | 0.00 | 0.703832E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 162474.38 | 04-JAN-16:00 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73690.81 | 03-JAN-08:20 | 121976.88 | 05-JAN-16:40 | 19915.82 | 05-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 159084.56 | 16-FEB-08:09 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73695.05 | 16-FEB-08:20 | 150793.55 | 15-FEB-16:00 | 36996.11 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 152128.77 | 20-MAR-07:10 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73691.41 | 20-MAR-07:19 | 174091.63 | 08-MAR-16:19 | 20786.80 | 08-MAR-14:20 | 0.00 | 01-MAR-00:10 |
April | 145987.23 | 03-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73688.19 | 03-APR-07:19 | 224682.37 | 28-APR-15:09 | 37696.08 | 13-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 148433.29 | 22-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73689.47 | 22-MAY-07:19 | 245908.12 | 30-MAY-14:30 | 38917.73 | 23-MAY-10:30 | 0.00 | 01-MAY-00:10 |
June | 148889.42 | 08-JUN-15:00 | 22480.63 | 01-JUN-19:10 | 541788.89 | 01-JUN-07:10 | 73689.29 | 08-JUN-07:19 | 323340.61 | 06-JUN-12:00 | 45013.03 | 27-JUN-14:39 | 0.00 | 01-JUN-00:10 |
July | 148731.48 | 07-JUL-15:00 | 31088.59 | 19-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 73688.19 | 03-JUL-07:19 | 323340.61 | 21-JUL-15:00 | 45054.80 | 03-JUL-08:30 | 0.00 | 01-JUL-00:10 |
August | 145987.23 | 01-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73688.19 | 01-AUG-07:19 | 319441.79 | 21-AUG-07:00 | 44751.61 | 31-AUG-11:39 | 0.00 | 01-AUG-00:10 |
September | 158449.44 | 08-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73694.72 | 08-SEP-07:19 | 323320.96 | 12-SEP-11:20 | 45027.48 | 25-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 157870.59 | 25-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73694.42 | 25-OCT-07:19 | 250410.29 | 11-OCT-12:09 | 45027.10 | 02-OCT-10:00 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 13-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73696.94 | 02-NOV-07:19 | 153192.47 | 03-NOV-15:00 | 22046.95 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:00 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73693.17 | 08-DEC-08:20 | 123046.80 | 29-DEC-16:49 | 19858.67 | 22-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 145987.23 | 22480.63 | 423497.50 | 73688.19 | 121976.88 | 19858.67 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 73696.94 | 323340.61 | 45054.80 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 73063.47 | 05-JAN-15:39 | 5665.38 | 05-JAN-15:00 | 100000.00 | 01-JAN-11:30 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 191743.95 | 14-FEB-15:50 | 44917.07 | 14-FEB-15:00 | 100000.00 | 01-FEB-04:10 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 218357.11 | 08-MAR-14:20 | 44988.28 | 08-MAR-14:20 | 100000.00 | 01-MAR-05:40 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 324166.35 | 13-APR-16:30 | 46574.50 | 27-APR-13:00 | 100000.00 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 239204.77 | 15-MAY-16:00 | 73721.34 | 22-MAY-12:39 | 100000.00 | 02-MAY-21:19 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 341194.45 | 28-JUN-14:50 | 73721.34 | 06-JUN-13:30 | 100000.00 | 03-JUN-17:40 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 402707.59 | 31-JUL-14:00 | 73721.34 | 03-JUL-08:50 | 100000.00 | 03-JUL-21:19 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 403151.32 | 21-AUG-14:09 | 73721.34 | 01-AUG-09:20 | 100000.00 | 02-AUG-18:10 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 297810.24 | 05-SEP-12:00 | 73721.34 | 01-SEP-10:20 | 100000.00 | 26-SEP-21:19 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 275849.81 | 02-OCT-14:00 | 73721.34 | 02-OCT-13:39 | 100000.00 | 05-OCT-04:19 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 137752.74 | 02-NOV-15:09 | 44573.68 | 02-NOV-15:30 | 100000.00 | 01-NOV-06:00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 81380.14 | 29-DEC-15:00 | 15978.18 | 24-DEC-14:00 | 100000.00 | 01-DEC-05:19 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 73063.47 | 5665.38 | 100000.00 | 0.00 | 0.00 | 0.00 | ||||
Maximum of Months | 403151.32 | 73721.34 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 927966.13 | 05-JAN-16:40 | 151051.69 | 423497.50 | 0.00 | 52591.50 | 121976.88 | 19748.67 | 0.00 | 55384.91 | 3714.99 |
February | 1218620.89 | 14-FEB-16:30 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 124254.64 | 21076.44 | 0.00 | 188143.93 | 44780.15 |
March | 1406229.54 | 08-MAR-16:19 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 174091.63 | 20225.15 | 0.00 | 208536.27 | 44719.36 |
April | 1690172.10 | 26-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 220622.72 | 36615.25 | 0.00 | 311730.24 | 44255.36 |
May | 1225322.40 | 09-MAY-15:20 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 210244.77 | 36477.19 | 0.00 | 209943.16 | 46582.95 |
June | 1487880.85 | 27-JUN-15:09 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 323340.61 | 44442.19 | 0.00 | 332120.83 | 45073.81 |
July | 1657305.87 | 21-JUL-15:50 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 322631.46 | 44429.05 | 0.00 | 384782.58 | 45752.43 |
August | 1846628.42 | 17-AUG-15:50 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 272925.90 | 38907.58 | 0.00 | 384125.07 | 73721.34 |
September | 1214882.47 | 12-SEP-15:00 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 217657.77 | 39175.12 | 0.00 | 207369.25 | 48520.67 |
October | 1346617.73 | 11-OCT-15:00 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 177421.33 | 38859.89 | 0.00 | 239856.02 | 50114.77 |
November | 1285349.88 | 02-NOV-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 124002.01 | 20394.06 | 0.00 | 137752.74 | 44543.94 |
December | 1330320.19 | 29-DEC-16:00 | 169722.15 | 778371.69 | 31088.59 | 52600.74 | 110015.69 | 19729.17 | 0.00 | 63968.65 | 4823.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 927966.13 | 145987.23 | 423497.50 | 0.00 | 52589.61 | 110015.69 | 19729.17 | 0.00 | 55384.91 | 3714.99 | |
Maximum of Months | 1846628.42 | 169722.15 | 778371.69 | 31088.59 | 52600.74 | 323340.61 | 44442.19 | 0.00 | 384782.58 | 73721.34 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 758783.08 | 17-JAN-07:10 | 0.00 | 83167.29 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 770394.27 | 06-FEB-07:10 | 0.00 | 83158.94 | 07-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 399929.40 | 02-MAR-14:20 | 0.00 | 82887.63 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 232287.59 | 08-APR-06:10 | 0.00 | 81170.23 | 05-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 105667.17 | 06-MAY-06:10 | 0.00 | 78737.29 | 04-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 2973.16 | 09-JUN-06:10 | 0.00 | 75916.53 | 02-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 73115.98 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 72339.88 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 3.55 | 09-SEP-06:10 | 0.00 | 74205.63 | 26-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 419775.72 | 26-OCT-06:10 | 0.00 | 77512.49 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 552489.86 | 27-NOV-07:10 | 0.00 | 80342.64 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 725719.70 | 15-DEC-07:10 | 0.00 | 82210.67 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 72339.88 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 770394.27 | 0.00 | 83167.29 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.56 | 0.33 | 26.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.60 | 0.00 | 26.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.90 | 0.00 | 25.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.85 | 0.00 | 25.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.86 | 0.00 | 26.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.86 | 0.00 | 26.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.66 | 0.33 | 26.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.06 | 0.33 | 25.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.96 | 0.50 | 27.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.53 | 1.67 | 26.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.67 | 0.00 | 26.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.49 | 1.00 | 26.64 |
Annual Sum or Average | 0.00 | 0.00 | 50.83 | 26.59 | 4.17 | 26.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.85 | 0.00 | 25.85 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.96 | 1.67 | 27.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.32 | 0.17 | 25.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.66 | 0.00 | 25.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.63 | 0.33 | 25.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.68 | 0.00 | 25.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.39 | 0.17 | 25.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 25.57 | 0.67 | 25.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.68 | 0.33 | 25.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 0.33 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.74 | 0.17 | 24.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
December | 1.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Annual Sum or Average | 2.50 | 18.79 | 0.00 | 18.79 | 0.17 | 19.16 | 0.17 | 19.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 18.88 | 0.00 | 18.88 | 0.17 | 24.74 | 0.17 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.32 | 3.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.37 | 5.83 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.22 | 4.17 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.32 | 1.83 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.17 | 27.31 | 14.83 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.37 | 5.83 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.61 | 0.50 | 27.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 1.00 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.06 | 2.67 | 28.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.13 | 5.50 | 28.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.16 | 11.17 | 28.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.06 | 10.67 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.96 | 17.50 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.70 | 12.33 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.88 | 7.67 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.92 | 6.67 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.68 | 2.00 | 27.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.50 | 0.17 | 27.50 |
Annual Sum or Average | 0.00 | 0.00 | 82.83 | 27.95 | 77.83 | 27.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.50 | 0.17 | 27.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 28.16 | 17.50 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 25.72 | 32.33 | 25.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 25.67 | 22.83 | 25.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.13 | 4.50 | 28.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.71 | 4.50 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.53 | 5.00 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.41 | 4.33 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.60 | 10.00 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.63 | 8.00 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 26.53 | 19.83 | 26.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 25.70 | 59.33 | 25.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 25.59 | 50.17 | 25.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 25.51 | 36.67 | 25.51 |
Annual Sum or Average | 0.00 | 0.00 | 264.67 | 26.03 | 257.50 | 26.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.51 | 4.33 | 25.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 28.13 | 59.33 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.81 | 2.83 | 27.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.02 | 2.50 | 28.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.60 | 3.50 | 28.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.79 | 9.50 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.08 | 6.17 | 28.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.66 | 12.50 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 27.73 | 20.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 | 27.72 | 18.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.04 | 7.67 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.11 | 5.50 | 28.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.12 | 5.67 | 28.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.24 | 3.00 | 28.24 |
Annual Sum or Average | 0.00 | 0.00 | 202.00 | 27.82 | 97.67 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.66 | 2.50 | 27.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 | 28.60 | 20.33 | 28.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.97 | 0.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
February | 2.00 | 18.94 | 0.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.17 | 2.33 | 27.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.50 | 4.33 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.44 | 1.83 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 2.83 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Annual Sum or Average | 8.67 | 19.06 | 0.33 | 19.10 | 11.83 | 23.81 | 8.50 | 24.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.34 | 0.17 | 19.34 | 5.83 | 27.50 | 4.33 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 1.50 | 18.77 | 0.00 | 18.77 | 0.33 | 20.35 | 0.33 | 21.45 |
March | 0.17 | 19.33 | 0.00 | 19.33 | 1.83 | 27.35 | 1.83 | 27.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.13 | 5.00 | 28.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.28 | 11.17 | 28.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.28 | 10.67 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 28.33 | 17.33 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.19 | 11.33 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.91 | 8.50 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.93 | 5.67 | 27.93 |
November | 0.33 | 19.31 | 0.00 | 19.31 | 0.33 | 23.34 | 0.33 | 24.68 |
December | 2.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 7.00 | 19.02 | 0.00 | 19.02 | 78.83 | 27.44 | 72.17 | 27.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 | 18.89 |
Maximum of Months | 2.50 | 19.33 | 0.00 | 19.33 | 20.50 | 28.33 | 17.33 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.83 | 0.17 | 19.02 | 52.50 | 25.63 | 52.50 | 25.71 |
February | 0.67 | 19.00 | 0.00 | 19.00 | 38.50 | 25.52 | 38.50 | 25.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.28 | 10.17 | 26.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.69 | 3.33 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.50 | 4.83 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.38 | 3.83 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.72 | 9.33 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.61 | 8.00 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 25.74 | 41.50 | 25.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 87.00 | 25.76 | 86.33 | 25.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 25.72 | 69.17 | 25.72 |
December | 0.67 | 19.30 | 0.00 | 19.30 | 57.83 | 25.38 | 57.83 | 25.42 |
Annual Sum or Average | 2.50 | 19.00 | 0.17 | 19.09 | 390.17 | 25.82 | 385.33 | 25.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.38 | 3.33 | 25.42 |
Maximum of Months | 1.17 | 19.30 | 0.17 | 19.30 | 87.00 | 27.72 | 86.33 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
February | 0.67 | 18.86 | 0.00 | 18.86 | 0.50 | 22.68 | 0.50 | 24.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.19 | 2.67 | 28.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.55 | 3.00 | 28.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.36 | 4.67 | 28.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.36 | 6.50 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 28.06 | 10.33 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.22 | 5.83 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.29 | 6.00 | 28.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.54 | 3.67 | 28.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.50 | 27.50 |
December | 0.83 | 19.31 | 0.00 | 19.31 | 0.33 | 21.63 | 0.33 | 22.92 |
Annual Sum or Average | 2.50 | 18.90 | 0.00 | 18.90 | 73.33 | 27.94 | 45.00 | 28.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 | 0.00 | 18.58 |
Maximum of Months | 1.00 | 19.31 | 0.00 | 19.31 | 18.17 | 28.55 | 10.33 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.50 | 17.26 | 3.33 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
February | 13.50 | 17.21 | 2.50 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
March | 2.67 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
April | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.50 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.24 | 4.33 | 27.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.63 | 8.50 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.60 | 4.67 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.42 | 2.00 | 27.42 |
October | 0.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
November | 5.17 | 18.38 | 0.33 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
December | 16.67 | 17.58 | 2.67 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
Annual Sum or Average | 57.17 | 17.53 | 8.83 | 17.61 | 27.17 | 20.50 | 20.00 | 21.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 0.00 | 17.29 |
Maximum of Months | 18.50 | 19.20 | 3.33 | 19.20 | 11.67 | 27.63 | 8.50 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 17.05 | 0.67 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
February | 9.00 | 17.12 | 0.67 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
March | 1.83 | 18.83 | 0.00 | 18.83 | 1.17 | 22.26 | 1.17 | 23.77 |
April | 0.17 | 19.24 | 0.00 | 19.24 | 4.50 | 27.57 | 4.50 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.28 | 11.17 | 28.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.38 | 10.33 | 28.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 28.54 | 16.67 | 28.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 28.30 | 11.33 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.94 | 9.00 | 27.95 |
October | 0.67 | 18.63 | 0.00 | 18.63 | 4.17 | 26.57 | 4.17 | 27.16 |
November | 3.50 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
December | 12.00 | 17.27 | 0.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 39.83 | 17.39 | 1.67 | 17.29 | 79.83 | 24.52 | 68.33 | 25.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 0.00 | 16.94 |
Maximum of Months | 12.67 | 19.24 | 0.67 | 19.24 | 21.67 | 28.54 | 16.67 | 28.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 17.82 | 0.00 | 17.82 | 16.00 | 22.92 | 16.00 | 24.11 |
February | 6.17 | 18.13 | 0.17 | 18.19 | 16.17 | 23.50 | 16.17 | 24.37 |
March | 1.17 | 19.00 | 0.00 | 19.00 | 3.67 | 25.87 | 3.67 | 26.82 |
April | 0.17 | 19.32 | 0.00 | 19.32 | 2.83 | 27.19 | 2.83 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.68 | 5.00 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.46 | 4.50 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.89 | 10.33 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.09 | 7.17 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 26.40 | 23.83 | 26.39 |
October | 0.33 | 19.09 | 0.00 | 19.09 | 52.67 | 25.72 | 51.83 | 25.73 |
November | 1.17 | 18.32 | 0.00 | 18.32 | 28.83 | 25.38 | 28.83 | 25.52 |
December | 8.00 | 18.28 | 0.00 | 18.28 | 9.50 | 22.66 | 9.50 | 23.95 |
Annual Sum or Average | 26.67 | 18.13 | 0.17 | 18.14 | 188.67 | 25.30 | 179.67 | 25.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.66 | 2.83 | 23.95 |
Maximum of Months | 9.67 | 19.32 | 0.17 | 19.32 | 52.67 | 28.09 | 51.83 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
February | 5.67 | 17.99 | 0.00 | 17.99 | 0.17 | 18.26 | 0.17 | 18.53 |
March | 0.67 | 18.91 | 0.00 | 18.91 | 2.83 | 26.32 | 2.33 | 27.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.51 | 3.33 | 28.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.39 | 5.50 | 28.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 28.13 | 8.50 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28.02 | 12.50 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.36 | 6.33 | 28.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.35 | 6.50 | 28.43 |
October | 0.33 | 19.22 | 0.00 | 19.22 | 4.33 | 27.87 | 3.50 | 28.21 |
November | 1.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
December | 7.50 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
Annual Sum or Average | 25.50 | 18.03 | 0.00 | 18.03 | 79.50 | 25.76 | 48.67 | 26.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 | 0.00 | 17.70 |
Maximum of Months | 10.17 | 19.22 | 0.00 | 19.22 | 21.33 | 28.51 | 12.50 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.01 | 6.33 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | 28.03 | 58.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 79.00 | 28.03 | 64.33 | 27.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | 28.03 | 58.00 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.02 | 5.83 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 27.97 | 35.67 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 52.17 | 27.97 | 41.50 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 28.02 | 35.67 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.12 | 2.67 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 28.19 | 25.67 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 39.67 | 28.18 | 28.33 | 28.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 28.19 | 25.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.86 | 10.33 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.96 | 0.50 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 384.33 | 29.83 | 339.00 | 29.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 396.17 | 29.77 | 349.83 | 29.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 384.33 | 29.83 | 339.00 | 29.89 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 280.17 | 24.00 | 63.67 | 24.44 | 0.00 | 24.44 |
February | 252.83 | 24.00 | 57.83 | 24.44 | 0.00 | 24.44 |
March | 243.67 | 24.00 | 53.33 | 24.41 | 0.00 | 24.41 |
April | 211.67 | 24.00 | 70.50 | 24.61 | 0.00 | 24.61 |
May | 156.17 | 24.00 | 126.83 | 24.64 | 0.83 | 24.64 |
June | 11.83 | 24.00 | 269.50 | 24.77 | 0.00 | 24.77 |
July | 119.00 | 24.39 | 466.00 | 24.59 | 119.00 | 24.56 |
August | 84.00 | 24.26 | 483.50 | 24.47 | 84.00 | 24.44 |
September | 13.67 | 24.62 | 353.00 | 24.74 | 13.67 | 24.74 |
October | 92.17 | 24.00 | 178.33 | 25.01 | 0.00 | 25.01 |
November | 128.83 | 24.00 | 97.83 | 25.08 | 0.00 | 25.08 |
December | 262.83 | 24.01 | 80.67 | 24.60 | 0.00 | 24.60 |
Annual Sum or Average | 1856.83 | 24.04 | 2301.00 | 24.62 | 217.50 | 24.61 |
Minimum of Months | 11.83 | 24.00 | 53.33 | 24.41 | 0.00 | 24.41 |
Maximum of Months | 280.17 | 24.62 | 483.50 | 25.08 | 119.00 | 25.08 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 24.00 | 15.50 | 24.09 | 0.00 | 24.09 |
February | 185.67 | 24.00 | 18.67 | 24.15 | 0.00 | 24.15 |
March | 162.17 | 24.01 | 30.00 | 24.30 | 0.00 | 24.30 |
April | 142.83 | 24.01 | 32.33 | 24.35 | 0.00 | 24.35 |
May | 116.83 | 24.01 | 119.83 | 24.40 | 1.33 | 24.40 |
June | 5.67 | 24.00 | 291.83 | 24.37 | 0.00 | 24.37 |
July | 169.33 | 24.38 | 475.50 | 24.31 | 169.33 | 24.33 |
August | 76.00 | 24.26 | 506.83 | 24.24 | 76.00 | 24.25 |
September | 17.50 | 24.22 | 364.00 | 24.44 | 17.50 | 24.43 |
October | 82.00 | 24.01 | 160.50 | 24.58 | 0.00 | 24.58 |
November | 130.00 | 24.00 | 50.33 | 24.50 | 0.00 | 24.50 |
December | 210.50 | 24.01 | 38.00 | 24.33 | 0.00 | 24.33 |
Annual Sum or Average | 1598.50 | 24.06 | 2103.33 | 24.33 | 264.17 | 24.33 |
Minimum of Months | 5.67 | 24.00 | 15.50 | 24.09 | 0.00 | 24.09 |
Maximum of Months | 300.00 | 24.38 | 506.83 | 24.58 | 169.33 | 24.58 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.67 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
February | 428.00 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
March | 408.00 | 23.88 | 0.50 | 23.88 | 0.00 | 23.88 |
April | 344.50 | 23.98 | 1.33 | 23.99 | 0.00 | 23.99 |
May | 208.00 | 23.98 | 80.00 | 24.10 | 1.50 | 24.10 |
June | 29.17 | 23.98 | 222.17 | 24.28 | 0.00 | 24.28 |
July | 162.00 | 24.19 | 461.00 | 24.24 | 162.00 | 24.23 |
August | 110.17 | 24.19 | 470.33 | 24.22 | 110.17 | 24.22 |
September | 24.00 | 24.20 | 312.33 | 24.34 | 19.50 | 24.34 |
October | 209.67 | 23.91 | 92.17 | 24.07 | 2.00 | 24.07 |
November | 403.33 | 23.83 | 0.83 | 23.84 | 0.00 | 23.84 |
December | 494.83 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
Annual Sum or Average | 3322.33 | 23.78 | 1640.67 | 23.95 | 295.17 | 23.96 |
Minimum of Months | 24.00 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
Maximum of Months | 500.67 | 24.20 | 470.33 | 24.34 | 162.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.78 | 147.17 | 21.44 | 147.17 | 21.23 |
February | 453.83 | 22.39 | 61.67 | 22.17 | 61.67 | 22.00 |
March | 501.17 | 23.26 | 9.50 | 23.21 | 9.50 | 23.17 |
April | 375.50 | 23.74 | 1.17 | 23.74 | 0.00 | 23.74 |
May | 211.50 | 23.81 | 75.00 | 24.00 | 2.17 | 24.00 |
June | 33.50 | 23.82 | 252.33 | 24.28 | 0.00 | 24.28 |
July | 161.17 | 24.23 | 473.50 | 24.29 | 161.17 | 24.28 |
August | 105.50 | 24.22 | 483.83 | 24.27 | 105.50 | 24.26 |
September | 48.33 | 23.94 | 300.00 | 24.27 | 22.00 | 24.26 |
October | 318.67 | 23.39 | 76.50 | 23.56 | 3.67 | 23.55 |
November | 464.67 | 22.71 | 39.33 | 22.55 | 39.33 | 22.41 |
December | 497.00 | 21.79 | 151.50 | 21.47 | 151.50 | 21.27 |
Annual Sum or Average | 3672.83 | 22.86 | 2071.50 | 23.11 | 703.67 | 22.99 |
Minimum of Months | 33.50 | 21.78 | 1.17 | 21.44 | 0.00 | 21.23 |
Maximum of Months | 502.00 | 24.23 | 483.83 | 24.29 | 161.17 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.48 | 23.17 | 22.41 | 23.17 | 22.35 |
February | 444.00 | 22.91 | 10.83 | 22.86 | 10.83 | 22.82 |
March | 447.17 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
April | 265.83 | 23.89 | 14.83 | 23.98 | 0.00 | 23.98 |
May | 146.33 | 23.90 | 112.33 | 24.30 | 1.33 | 24.30 |
June | 11.67 | 25.71 | 350.00 | 24.50 | 7.00 | 24.55 |
July | 140.17 | 25.07 | 489.83 | 24.61 | 140.17 | 24.70 |
August | 65.83 | 24.99 | 504.67 | 24.41 | 65.83 | 24.47 |
September | 44.50 | 24.34 | 327.33 | 24.43 | 18.50 | 24.46 |
October | 276.17 | 23.59 | 102.83 | 23.81 | 0.00 | 23.81 |
November | 461.00 | 23.35 | 0.00 | 23.35 | 0.00 | 23.35 |
December | 497.00 | 22.76 | 7.83 | 22.74 | 7.83 | 22.71 |
Annual Sum or Average | 3301.67 | 23.31 | 1943.67 | 23.71 | 274.67 | 23.74 |
Minimum of Months | 11.67 | 22.48 | 0.00 | 22.41 | 0.00 | 22.35 |
Maximum of Months | 502.00 | 25.71 | 504.67 | 24.61 | 140.17 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 431.17 | 22.78 | 36.33 | 22.81 | 21.83 | 22.73 |
February | 351.50 | 23.04 | 31.67 | 23.15 | 7.67 | 23.11 |
March | 296.50 | 23.49 | 71.00 | 23.75 | 5.67 | 23.80 |
April | 165.83 | 24.11 | 141.83 | 24.50 | 13.83 | 24.61 |
May | 129.50 | 24.76 | 233.67 | 24.77 | 34.67 | 24.97 |
June | 39.17 | 26.57 | 395.83 | 24.68 | 32.33 | 24.85 |
July | 138.17 | 25.58 | 488.33 | 24.79 | 138.17 | 24.93 |
August | 80.17 | 25.68 | 503.00 | 24.56 | 79.67 | 24.70 |
September | 60.50 | 25.71 | 395.00 | 24.67 | 46.67 | 24.82 |
October | 202.67 | 23.81 | 200.00 | 24.31 | 15.50 | 24.41 |
November | 355.00 | 23.36 | 32.33 | 23.54 | 1.50 | 23.56 |
December | 439.83 | 22.86 | 25.83 | 22.84 | 18.33 | 22.77 |
Annual Sum or Average | 2690.00 | 23.59 | 2554.83 | 24.05 | 415.83 | 24.16 |
Minimum of Months | 39.17 | 22.78 | 25.83 | 22.81 | 1.50 | 22.73 |
Maximum of Months | 439.83 | 26.57 | 503.00 | 24.79 | 138.17 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.00 | 22.99 | 160.17 | 23.47 | 49.67 | 23.51 |
February | 247.00 | 23.19 | 144.17 | 23.70 | 21.83 | 23.75 |
March | 268.33 | 23.57 | 107.67 | 23.89 | 10.00 | 23.96 |
April | 180.17 | 23.83 | 98.67 | 24.22 | 3.00 | 24.25 |
May | 156.33 | 24.02 | 145.83 | 24.40 | 13.50 | 24.50 |
June | 34.17 | 24.80 | 318.00 | 24.49 | 10.83 | 24.57 |
July | 134.00 | 25.20 | 485.00 | 24.64 | 134.00 | 24.74 |
August | 70.83 | 25.43 | 508.67 | 24.51 | 70.83 | 24.61 |
September | 69.17 | 25.76 | 395.17 | 24.79 | 55.17 | 24.95 |
October | 168.83 | 24.37 | 271.67 | 24.74 | 49.67 | 24.93 |
November | 247.00 | 23.88 | 168.50 | 24.40 | 29.17 | 24.56 |
December | 288.17 | 23.19 | 167.67 | 23.69 | 32.83 | 23.74 |
Annual Sum or Average | 2180.00 | 23.79 | 2971.17 | 24.26 | 480.50 | 24.37 |
Minimum of Months | 34.17 | 22.99 | 98.67 | 23.47 | 3.00 | 23.51 |
Maximum of Months | 316.00 | 25.76 | 508.67 | 24.79 | 134.00 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.17 | 23.38 | 51.33 | 23.58 | 2.83 | 23.60 |
February | 245.67 | 23.84 | 92.00 | 24.12 | 5.33 | 24.17 |
March | 114.67 | 24.36 | 128.33 | 24.74 | 13.33 | 24.87 |
April | 40.83 | 25.93 | 234.17 | 25.33 | 24.50 | 25.49 |
May | 65.00 | 25.13 | 287.00 | 24.88 | 24.17 | 25.02 |
June | 38.83 | 26.92 | 454.33 | 24.79 | 38.83 | 24.94 |
July | 184.17 | 25.58 | 497.00 | 24.95 | 184.17 | 25.08 |
August | 149.00 | 25.66 | 514.00 | 24.82 | 149.00 | 24.98 |
September | 49.33 | 26.32 | 429.00 | 24.82 | 49.33 | 24.96 |
October | 90.33 | 24.65 | 263.17 | 24.82 | 19.83 | 24.95 |
November | 141.67 | 24.28 | 114.17 | 24.62 | 12.17 | 24.74 |
December | 236.67 | 24.10 | 91.17 | 24.35 | 7.50 | 24.42 |
Annual Sum or Average | 1741.33 | 24.46 | 3155.67 | 24.66 | 531.00 | 24.80 |
Minimum of Months | 38.83 | 23.38 | 51.33 | 23.58 | 2.83 | 23.60 |
Maximum of Months | 385.17 | 26.92 | 514.00 | 25.33 | 184.17 | 25.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.88 | 306.50 | 20.69 | 306.50 | 20.60 |
February | 454.00 | 21.35 | 170.17 | 21.11 | 170.17 | 20.97 |
March | 512.50 | 22.45 | 55.83 | 22.28 | 55.83 | 22.14 |
April | 411.67 | 23.31 | 5.17 | 23.29 | 5.17 | 23.26 |
May | 232.83 | 23.63 | 82.83 | 23.90 | 1.17 | 23.91 |
June | 27.67 | 23.91 | 313.33 | 24.41 | 2.83 | 24.43 |
July | 141.50 | 24.84 | 486.67 | 24.56 | 141.50 | 24.61 |
August | 80.50 | 24.51 | 480.50 | 24.35 | 78.50 | 24.37 |
September | 90.17 | 23.74 | 270.50 | 24.18 | 17.83 | 24.20 |
October | 378.83 | 22.74 | 82.00 | 22.83 | 23.67 | 22.74 |
November | 484.83 | 21.76 | 126.17 | 21.51 | 126.17 | 21.35 |
December | 497.00 | 20.76 | 345.67 | 20.63 | 345.67 | 20.57 |
Annual Sum or Average | 3813.50 | 22.17 | 2725.33 | 22.48 | 1275.00 | 22.28 |
Minimum of Months | 27.67 | 20.76 | 5.17 | 20.63 | 1.17 | 20.57 |
Maximum of Months | 512.50 | 24.84 | 486.67 | 24.56 | 345.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.17 | 21.80 | 140.83 | 21.48 | 140.83 | 21.28 |
February | 340.83 | 22.11 | 86.83 | 21.89 | 77.67 | 21.68 |
March | 310.33 | 22.86 | 68.83 | 23.04 | 23.17 | 22.97 |
April | 175.67 | 23.76 | 114.33 | 24.29 | 13.00 | 24.39 |
May | 145.17 | 24.60 | 182.50 | 24.81 | 39.00 | 25.05 |
June | 52.17 | 26.03 | 322.67 | 24.85 | 36.33 | 25.04 |
July | 128.83 | 25.77 | 412.17 | 25.00 | 128.83 | 25.15 |
August | 81.17 | 25.73 | 417.17 | 24.74 | 80.50 | 24.88 |
September | 73.00 | 25.29 | 301.83 | 24.74 | 45.00 | 24.92 |
October | 210.17 | 23.32 | 154.00 | 23.89 | 26.83 | 23.94 |
November | 349.33 | 22.55 | 49.00 | 22.52 | 32.83 | 22.38 |
December | 414.33 | 21.70 | 165.50 | 21.34 | 165.33 | 21.15 |
Annual Sum or Average | 2692.17 | 22.93 | 2415.67 | 23.42 | 809.33 | 23.37 |
Minimum of Months | 52.17 | 21.70 | 49.00 | 21.34 | 13.00 | 21.15 |
Maximum of Months | 414.33 | 26.03 | 417.17 | 25.00 | 165.33 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 343.50 | 22.68 | 216.17 | 23.03 | 119.00 | 22.95 |
February | 268.17 | 22.72 | 174.17 | 23.23 | 61.83 | 23.18 |
March | 303.50 | 22.99 | 116.33 | 23.38 | 20.17 | 23.42 |
April | 232.00 | 23.38 | 75.33 | 23.76 | 3.83 | 23.78 |
May | 198.83 | 23.71 | 122.67 | 24.14 | 10.67 | 24.22 |
June | 62.33 | 24.03 | 282.67 | 24.38 | 8.83 | 24.44 |
July | 143.00 | 25.01 | 478.17 | 24.61 | 143.00 | 24.69 |
August | 85.17 | 25.10 | 490.67 | 24.50 | 85.17 | 24.58 |
September | 87.00 | 25.37 | 370.33 | 24.78 | 59.33 | 24.95 |
October | 210.67 | 24.18 | 269.50 | 24.68 | 73.00 | 24.88 |
November | 281.00 | 23.46 | 180.67 | 24.07 | 58.67 | 24.22 |
December | 309.83 | 22.56 | 225.83 | 22.96 | 104.50 | 22.81 |
Annual Sum or Average | 2525.00 | 23.40 | 3002.50 | 23.96 | 748.00 | 24.00 |
Minimum of Months | 62.33 | 22.56 | 75.33 | 22.96 | 3.83 | 22.81 |
Maximum of Months | 343.50 | 25.37 | 490.67 | 24.78 | 143.00 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.17 | 21.66 | 163.67 | 21.46 | 150.83 | 21.27 |
February | 365.50 | 22.07 | 114.00 | 22.03 | 78.17 | 21.84 |
March | 387.00 | 22.96 | 77.00 | 23.14 | 22.17 | 23.13 |
April | 252.00 | 23.79 | 101.00 | 24.07 | 17.33 | 24.22 |
May | 136.50 | 24.10 | 203.50 | 24.44 | 20.17 | 24.59 |
June | 44.17 | 25.53 | 385.67 | 24.66 | 25.67 | 24.79 |
July | 156.33 | 25.10 | 496.17 | 24.71 | 156.33 | 24.78 |
August | 91.83 | 25.05 | 510.67 | 24.54 | 91.83 | 24.61 |
September | 65.00 | 25.19 | 366.00 | 24.63 | 40.83 | 24.76 |
October | 246.17 | 23.29 | 169.50 | 23.77 | 18.33 | 23.85 |
November | 380.00 | 22.49 | 78.33 | 22.53 | 38.83 | 22.38 |
December | 438.17 | 21.66 | 171.33 | 21.41 | 165.00 | 21.24 |
Annual Sum or Average | 3002.83 | 22.82 | 2836.83 | 23.37 | 825.50 | 23.31 |
Minimum of Months | 44.17 | 21.66 | 77.00 | 21.41 | 17.33 | 21.24 |
Maximum of Months | 440.17 | 25.53 | 510.67 | 24.71 | 165.00 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 404.00 | 20.12 | 404.00 | 20.07 |
February | 454.00 | 20.74 | 290.83 | 20.51 | 290.83 | 20.41 |
March | 513.83 | 21.88 | 153.67 | 21.55 | 153.67 | 21.34 |
April | 410.00 | 22.90 | 45.33 | 22.69 | 45.00 | 22.51 |
May | 245.00 | 23.31 | 82.67 | 23.63 | 7.00 | 23.58 |
June | 51.50 | 24.00 | 315.67 | 24.39 | 9.67 | 24.46 |
July | 156.17 | 24.90 | 484.33 | 24.58 | 156.17 | 24.64 |
August | 94.17 | 24.65 | 475.50 | 24.38 | 87.67 | 24.43 |
September | 134.33 | 23.58 | 251.17 | 24.06 | 23.67 | 24.11 |
October | 402.67 | 22.24 | 131.50 | 22.20 | 79.00 | 22.00 |
November | 489.00 | 20.99 | 264.33 | 20.68 | 264.33 | 20.53 |
December | 497.00 | 20.16 | 447.00 | 20.09 | 447.00 | 20.07 |
Annual Sum or Average | 3949.67 | 21.72 | 3346.00 | 21.96 | 1968.00 | 21.72 |
Minimum of Months | 51.50 | 20.16 | 45.33 | 20.09 | 7.00 | 20.07 |
Maximum of Months | 513.83 | 24.90 | 484.33 | 24.58 | 447.00 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.19 | 283.33 | 20.82 | 283.33 | 20.65 |
February | 428.50 | 21.70 | 150.83 | 21.28 | 149.67 | 21.02 |
March | 376.33 | 22.54 | 96.50 | 22.44 | 65.50 | 22.22 |
April | 186.50 | 23.36 | 132.50 | 23.87 | 18.17 | 23.82 |
May | 163.67 | 24.34 | 223.33 | 24.59 | 41.67 | 24.80 |
June | 62.17 | 25.78 | 396.00 | 24.70 | 41.67 | 24.89 |
July | 162.33 | 25.41 | 487.50 | 24.83 | 162.33 | 24.94 |
August | 102.17 | 25.37 | 497.67 | 24.61 | 99.67 | 24.72 |
September | 96.67 | 24.78 | 362.33 | 24.54 | 49.83 | 24.70 |
October | 255.33 | 22.90 | 182.67 | 23.35 | 43.33 | 23.23 |
November | 449.17 | 22.09 | 125.67 | 21.74 | 120.50 | 21.49 |
December | 497.00 | 20.98 | 283.83 | 20.61 | 283.83 | 20.44 |
Annual Sum or Average | 3281.83 | 22.45 | 3222.17 | 22.86 | 1359.50 | 22.69 |
Minimum of Months | 62.17 | 20.98 | 96.50 | 20.61 | 18.17 | 20.44 |
Maximum of Months | 502.00 | 25.78 | 497.67 | 24.83 | 283.83 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 353.83 | 21.72 | 258.17 | 21.89 | 168.67 | 21.64 |
February | 287.67 | 21.90 | 205.67 | 22.15 | 114.00 | 21.90 |
March | 336.67 | 22.47 | 162.33 | 22.57 | 84.00 | 22.38 |
April | 255.67 | 22.96 | 104.33 | 23.20 | 31.17 | 23.05 |
May | 232.33 | 23.47 | 131.33 | 23.88 | 21.83 | 23.93 |
June | 78.17 | 23.81 | 289.83 | 24.32 | 12.00 | 24.41 |
July | 151.67 | 24.98 | 475.67 | 24.61 | 151.67 | 24.68 |
August | 92.50 | 25.01 | 483.83 | 24.49 | 87.50 | 24.57 |
September | 115.67 | 24.72 | 348.17 | 24.62 | 59.17 | 24.79 |
October | 231.17 | 23.42 | 270.00 | 24.00 | 73.50 | 24.06 |
November | 296.17 | 22.50 | 194.50 | 22.90 | 80.50 | 22.75 |
December | 332.17 | 21.61 | 249.83 | 21.74 | 154.83 | 21.45 |
Annual Sum or Average | 2763.67 | 22.78 | 3173.67 | 23.32 | 1038.83 | 23.20 |
Minimum of Months | 78.17 | 21.61 | 104.33 | 21.74 | 12.00 | 21.45 |
Maximum of Months | 353.83 | 25.01 | 483.83 | 24.62 | 168.67 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.50 | 21.00 | 269.17 | 20.67 | 268.83 | 20.52 |
February | 378.17 | 21.45 | 191.50 | 21.27 | 161.83 | 21.05 |
March | 403.00 | 22.39 | 138.00 | 22.37 | 88.17 | 22.19 |
April | 274.00 | 23.33 | 117.83 | 23.60 | 33.67 | 23.63 |
May | 170.17 | 23.76 | 198.67 | 24.20 | 25.33 | 24.33 |
June | 67.00 | 24.90 | 377.00 | 24.61 | 30.83 | 24.75 |
July | 177.83 | 25.02 | 494.17 | 24.70 | 177.83 | 24.77 |
August | 105.33 | 24.98 | 505.67 | 24.54 | 105.33 | 24.60 |
September | 94.00 | 24.59 | 344.33 | 24.53 | 43.33 | 24.66 |
October | 287.33 | 22.79 | 187.17 | 23.19 | 52.00 | 23.12 |
November | 410.50 | 21.84 | 145.33 | 21.62 | 117.83 | 21.37 |
December | 456.67 | 21.02 | 283.17 | 20.71 | 281.50 | 20.57 |
Annual Sum or Average | 3280.50 | 22.35 | 3252.00 | 22.81 | 1386.50 | 22.64 |
Minimum of Months | 67.00 | 21.00 | 117.83 | 20.67 | 25.33 | 20.52 |
Maximum of Months | 456.67 | 25.02 | 505.67 | 24.70 | 281.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 27.00 | 502.00 | 27.00 | 1.00 | 27.00 |
February | 4.83 | 27.00 | 454.00 | 27.00 | 4.83 | 27.00 |
March | 16.50 | 27.00 | 514.00 | 27.00 | 16.50 | 27.00 |
April | 36.67 | 27.25 | 485.00 | 27.04 | 36.67 | 27.05 |
May | 2.50 | 27.00 | 508.00 | 27.00 | 2.50 | 27.00 |
June | 27.33 | 27.00 | 496.00 | 27.00 | 27.33 | 27.00 |
July | 116.67 | 27.00 | 497.00 | 27.00 | 116.67 | 27.00 |
August | 255.50 | 27.28 | 514.00 | 27.18 | 255.50 | 27.21 |
September | 15.17 | 27.00 | 485.00 | 27.00 | 15.17 | 27.00 |
October | 27.00 | 27.00 | 502.00 | 27.00 | 27.00 | 27.00 |
November | 17.83 | 27.00 | 489.00 | 27.00 | 17.83 | 27.00 |
December | 17.00 | 27.01 | 497.00 | 27.00 | 17.00 | 27.00 |
Annual Sum or Average | 538.00 | 27.15 | 5943.00 | 27.02 | 538.00 | 27.03 |
Minimum of Months | 1.00 | 27.00 | 454.00 | 27.00 | 1.00 | 27.00 |
Maximum of Months | 255.50 | 27.28 | 514.00 | 27.18 | 255.50 | 27.21 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 453.83 | 27.00 | 0.00 | 27.00 |
February | 0.17 | 27.00 | 437.33 | 27.00 | 0.17 | 27.00 |
March | 2.17 | 27.00 | 514.00 | 27.00 | 2.17 | 27.00 |
April | 11.83 | 27.55 | 485.00 | 27.03 | 11.83 | 27.04 |
May | 0.67 | 27.00 | 508.00 | 27.00 | 0.67 | 27.00 |
June | 7.67 | 27.00 | 496.00 | 27.00 | 7.67 | 27.00 |
July | 16.17 | 27.00 | 497.00 | 27.00 | 16.17 | 27.00 |
August | 73.67 | 27.59 | 514.00 | 27.15 | 73.67 | 27.20 |
September | 6.50 | 27.00 | 485.00 | 27.00 | 6.50 | 27.00 |
October | 9.33 | 27.00 | 502.00 | 27.00 | 9.33 | 27.00 |
November | 1.00 | 27.00 | 489.00 | 27.00 | 1.00 | 27.00 |
December | 0.00 | 0.00 | 459.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 129.17 | 27.39 | 5840.50 | 27.02 | 129.17 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 437.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 73.67 | 27.59 | 514.00 | 27.15 | 73.67 | 27.20 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 85.33 | 25.49 | 270.83 | 26.64 | 0.00 | 26.64 |
February | 9.17 | 27.00 | 337.00 | 27.00 | 0.50 | 27.00 |
March | 2.67 | 27.00 | 475.00 | 27.00 | 2.67 | 27.00 |
April | 12.67 | 27.39 | 483.00 | 27.02 | 12.67 | 27.03 |
May | 2.33 | 27.00 | 503.17 | 27.00 | 2.33 | 27.00 |
June | 23.50 | 27.00 | 496.00 | 27.00 | 23.50 | 27.00 |
July | 68.17 | 27.00 | 497.00 | 27.00 | 68.17 | 27.00 |
August | 96.00 | 27.43 | 514.00 | 27.14 | 96.00 | 27.17 |
September | 13.50 | 27.00 | 485.00 | 27.00 | 13.50 | 27.00 |
October | 12.50 | 27.00 | 487.00 | 27.00 | 12.50 | 27.00 |
November | 1.00 | 27.00 | 425.33 | 27.00 | 1.00 | 27.00 |
December | 20.17 | 27.00 | 313.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 347.00 | 26.76 | 5286.33 | 26.99 | 232.83 | 27.00 |
Minimum of Months | 1.00 | 25.49 | 270.83 | 26.64 | 0.00 | 26.64 |
Maximum of Months | 96.00 | 27.43 | 514.00 | 27.14 | 96.00 | 27.17 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 27.00 | 502.00 | 27.00 | 493.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.03 | 485.00 | 27.03 | 485.00 | 27.03 |
May | 394.67 | 27.00 | 508.00 | 27.00 | 394.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 28.98 | 514.00 | 28.98 | 514.00 | 28.98 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5821.33 | 27.18 | 5943.00 | 27.18 | 5821.33 | 27.18 |
Minimum of Months | 394.67 | 27.00 | 454.00 | 27.00 | 394.67 | 27.00 |
Maximum of Months | 514.00 | 28.98 | 514.00 | 28.98 | 514.00 | 28.98 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.98893 | 0.72627 | 16.19765 |
February | 454.00000 | 27.00001 | 17.45932 | 0.78262 | 18.00147 |
March | 514.00000 | 27.00001 | 18.13124 | 0.83701 | 19.84894 |
April | 485.00000 | 27.02134 | 16.86534 | 0.88676 | 21.68481 |
May | 508.00000 | 27.00017 | 20.21432 | 0.14914 | 5.57618 |
June | 496.00000 | 27.00037 | 24.39784 | 0.25034 | 6.39263 |
July | 497.00000 | 27.00048 | 27.05875 | 0.32595 | 7.28471 |
August | 514.00000 | 27.13709 | 26.80911 | 0.41038 | 8.86151 |
September | 485.00000 | 27.00070 | 25.59788 | 0.20874 | 6.00396 |
October | 502.00000 | 27.00024 | 21.01191 | 0.85232 | 20.43576 |
November | 489.00000 | 27.00004 | 18.25242 | 0.83756 | 19.87716 |
December | 497.00000 | 27.00034 | 14.81401 | 0.82080 | 19.28899 |
Annual Sum or Average | 5943.00000 | 27.01380 | 20.66353 | 0.58887 | 14.08032 |
Minimum of Months | 454.00000 | 27.00000 | 14.81401 | 0.14914 | 5.57618 |
Maximum of Months | 514.00000 | 27.13709 | 27.05875 | 0.88676 | 21.68481 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99985 | 16.96999 | 0.62093 | 13.24289 |
February | 454.00000 | 27.00001 | 17.44131 | 0.66851 | 14.57516 |
March | 514.00000 | 27.00001 | 18.10513 | 0.72862 | 16.31185 |
April | 485.00000 | 27.01647 | 16.84265 | 0.77992 | 17.95426 |
May | 508.00000 | 27.00015 | 20.22415 | 0.08576 | 5.31203 |
June | 496.00000 | 27.00036 | 24.41038 | 0.17305 | 5.74589 |
July | 497.00000 | 27.00047 | 27.07967 | 0.23168 | 6.20666 |
August | 514.00000 | 27.09201 | 26.86380 | 0.27046 | 6.79817 |
September | 485.00000 | 27.00062 | 25.70006 | 0.14738 | 5.57773 |
October | 502.00000 | 27.00023 | 21.01060 | 0.77302 | 17.75966 |
November | 489.00000 | 27.00004 | 18.23513 | 0.71419 | 15.87613 |
December | 497.00000 | 26.99999 | 14.79008 | 0.64811 | 13.99394 |
Annual Sum or Average | 5943.00000 | 27.00945 | 20.66961 | 0.48501 | 11.58061 |
Minimum of Months | 454.00000 | 26.99985 | 14.79008 | 0.08576 | 5.31203 |
Maximum of Months | 514.00000 | 27.09201 | 27.07967 | 0.77992 | 17.95426 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.70092 | 17.20212 | 0.48028 | 10.73123 |
February | 454.00000 | 27.00002 | 17.45704 | 0.59873 | 12.86099 |
March | 514.00000 | 27.00001 | 18.12145 | 0.68137 | 15.04126 |
April | 485.00000 | 27.01132 | 16.85998 | 0.75886 | 17.37996 |
May | 508.00000 | 27.00014 | 20.24262 | 0.07999 | 5.44258 |
June | 496.00000 | 27.00037 | 24.41846 | 0.18615 | 5.95081 |
July | 497.00000 | 27.00050 | 27.08182 | 0.25392 | 6.51441 |
August | 514.00000 | 27.08072 | 26.87092 | 0.28453 | 7.08002 |
September | 485.00000 | 27.00063 | 25.71116 | 0.14694 | 5.68764 |
October | 502.00000 | 27.00023 | 21.03060 | 0.73984 | 16.84442 |
November | 489.00000 | 27.00004 | 18.24877 | 0.64370 | 13.98815 |
December | 497.00000 | 27.00000 | 14.80234 | 0.55783 | 11.83326 |
Annual Sum or Average | 5943.00000 | 26.98280 | 20.70104 | 0.44948 | 10.75474 |
Minimum of Months | 454.00000 | 26.70092 | 14.80234 | 0.07999 | 5.44258 |
Maximum of Months | 514.00000 | 27.08072 | 27.08182 | 0.75886 | 17.37996 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00050 | 28.95936 | 1.03484 | 27.61760 |
February | 454.00000 | 27.00041 | 24.63601 | 1.15780 | 33.22740 |
March | 514.00000 | 27.00024 | 19.68784 | 1.26602 | 38.54954 |
April | 485.00000 | 27.02762 | 16.45533 | 1.38888 | 44.93144 |
May | 508.00000 | 27.00078 | 25.14353 | 0.43511 | 9.04797 |
June | 496.00000 | 27.00434 | 29.62161 | 0.70552 | 15.49705 |
July | 497.00000 | 27.01212 | 32.50787 | 0.94574 | 23.90839 |
August | 514.00000 | 28.98050 | 30.08804 | 1.67216 | 58.58020 |
September | 485.00000 | 27.00213 | 32.36981 | 0.55088 | 11.42589 |
October | 502.00000 | 27.00149 | 25.13948 | 1.21071 | 35.80871 |
November | 489.00000 | 27.00037 | 20.45292 | 1.30150 | 40.35678 |
December | 497.00000 | 27.00008 | 17.06299 | 1.39199 | 45.09158 |
Annual Sum or Average | 5943.00000 | 27.17542 | 25.19111 | 1.08921 | 32.05344 |
Minimum of Months | 454.00000 | 27.00008 | 16.45533 | 0.43511 | 9.04797 |
Maximum of Months | 514.00000 | 28.98050 | 32.50787 | 1.67216 | 58.58020 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.47166 | 14.64658 | 0.28503 | 7.13464 |
February | 454.00000 | 24.46027 | 15.76181 | 0.29103 | 7.18153 |
March | 514.00000 | 24.38514 | 15.58441 | 0.28066 | 6.92293 |
April | 485.00000 | 24.48853 | 13.93608 | 0.29703 | 7.28808 |
May | 508.00000 | 24.47085 | 21.34812 | -0.5147 | 11.57047 |
June | 496.00000 | 24.44635 | 32.03213 | -0.4352 | 9.81001 |
July | 497.00000 | 24.60381 | 45.79343 | -0.2832 | 7.87299 |
August | 514.00000 | 24.47594 | 45.44246 | -0.3113 | 7.99165 |
September | 485.00000 | 24.54558 | 37.53143 | -0.3549 | 8.93731 |
October | 502.00000 | 24.59467 | 22.84409 | 0.39684 | 9.06734 |
November | 489.00000 | 24.56525 | 16.16483 | 0.33798 | 7.98134 |
December | 497.00000 | 24.54112 | 12.55390 | 0.29775 | 7.38667 |
Annual Sum or Average | 5943.00000 | 24.50386 | 24.55691 | 0.02116 | 8.27187 |
Minimum of Months | 454.00000 | 24.38514 | 12.55390 | -0.5147 | 6.92293 |
Maximum of Months | 514.00000 | 24.60381 | 45.79343 | 0.39684 | 11.57047 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.21309 | 17.28884 | 0.23981 | 6.35032 |
February | 454.00000 | 24.27023 | 17.95989 | 0.26817 | 6.65526 |
March | 514.00000 | 24.26135 | 16.82100 | 0.27815 | 6.76581 |
April | 485.00000 | 24.29774 | 14.53374 | 0.28705 | 6.90027 |
May | 508.00000 | 24.27343 | 22.82555 | -0.5415 | 11.63769 |
June | 496.00000 | 24.24076 | 33.59526 | -0.4548 | 9.64609 |
July | 497.00000 | 24.28052 | 48.04048 | -0.3290 | 7.62468 |
August | 514.00000 | 24.23948 | 46.28176 | -0.3404 | 7.69092 |
September | 485.00000 | 24.34255 | 38.87783 | -0.3961 | 8.88554 |
October | 502.00000 | 24.36225 | 24.14005 | 0.36123 | 8.10772 |
November | 489.00000 | 24.33369 | 17.50972 | 0.30106 | 7.09332 |
December | 497.00000 | 24.35533 | 14.97511 | 0.27639 | 6.83810 |
Annual Sum or Average | 5943.00000 | 24.28891 | 26.15348 | -0.0069 | 7.86124 |
Minimum of Months | 454.00000 | 24.21309 | 14.53374 | -0.5415 | 6.35032 |
Maximum of Months | 514.00000 | 24.36225 | 48.04048 | 0.36123 | 11.63769 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.46149 | 18.55639 | 0.02842 | 5.46618 |
February | 454.00000 | 23.68408 | 19.52729 | 0.09631 | 5.53804 |
March | 514.00000 | 23.97441 | 18.78281 | 0.17920 | 5.84408 |
April | 485.00000 | 24.13118 | 15.62834 | 0.21074 | 6.03703 |
May | 508.00000 | 24.16280 | 23.29817 | -0.6075 | 13.08507 |
June | 496.00000 | 24.17976 | 33.74171 | -0.5116 | 10.71829 |
July | 497.00000 | 24.23847 | 47.82951 | -0.3871 | 8.38690 |
August | 514.00000 | 24.21242 | 46.89664 | -0.4016 | 8.59204 |
September | 485.00000 | 24.23601 | 39.42374 | -0.4604 | 9.79273 |
October | 502.00000 | 24.12715 | 25.33520 | 0.27965 | 6.94069 |
November | 489.00000 | 23.92309 | 19.85701 | 0.17010 | 5.82010 |
December | 497.00000 | 23.52444 | 16.43150 | 0.03151 | 5.40420 |
Annual Sum or Average | 5943.00000 | 23.99001 | 27.18789 | -0.1166 | 7.65671 |
Minimum of Months | 454.00000 | 23.46149 | 15.62834 | -0.6075 | 5.40420 |
Maximum of Months | 514.00000 | 24.23847 | 47.82951 | 0.27965 | 13.08507 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.77921 | 20.38526 | -0.3936 | 10.32856 |
February | 454.00000 | 22.39314 | 21.34847 | -0.2305 | 7.88044 |
March | 514.00000 | 23.27467 | 19.51084 | -0.0082 | 6.03915 |
April | 485.00000 | 23.85551 | 15.85782 | 0.13705 | 5.83812 |
May | 508.00000 | 24.08112 | 23.15172 | -0.6351 | 14.17116 |
June | 496.00000 | 24.19656 | 33.69845 | -0.4893 | 10.38469 |
July | 497.00000 | 24.30322 | 47.81864 | -0.3400 | 7.87352 |
August | 514.00000 | 24.26387 | 46.72953 | -0.3672 | 8.19953 |
September | 485.00000 | 24.20966 | 39.14411 | -0.4687 | 10.04905 |
October | 502.00000 | 23.67887 | 25.71421 | 0.15558 | 6.55822 |
November | 489.00000 | 22.77002 | 21.62118 | -0.1269 | 6.95590 |
December | 497.00000 | 21.78522 | 18.32418 | -0.4044 | 10.20982 |
Annual Sum or Average | 5943.00000 | 23.39022 | 27.84433 | -0.2651 | 8.71907 |
Minimum of Months | 454.00000 | 21.77921 | 15.85782 | -0.6351 | 5.83812 |
Maximum of Months | 514.00000 | 24.30322 | 47.81864 | 0.15558 | 14.17116 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.48143 | 18.61462 | -0.2008 | 6.85915 |
February | 454.00000 | 22.94082 | 19.03677 | -0.0823 | 6.18999 |
March | 514.00000 | 23.59501 | 17.11697 | 0.08258 | 5.69955 |
April | 485.00000 | 24.06507 | 14.14963 | 0.21161 | 6.25709 |
May | 508.00000 | 24.21770 | 22.20924 | -0.5566 | 12.52553 |
June | 496.00000 | 24.34306 | 32.44232 | -0.3691 | 8.66331 |
July | 497.00000 | 24.47441 | 46.50345 | -0.2068 | 7.07095 |
August | 514.00000 | 24.32882 | 45.14852 | -0.2721 | 7.33847 |
September | 485.00000 | 24.31592 | 38.00282 | -0.4066 | 9.40571 |
October | 502.00000 | 23.89706 | 24.17572 | 0.21725 | 6.85827 |
November | 489.00000 | 23.39069 | 18.31911 | 0.02863 | 5.56624 |
December | 497.00000 | 22.76139 | 16.41884 | -0.1467 | 6.22991 |
Annual Sum or Average | 5943.00000 | 23.73982 | 26.08547 | -0.1428 | 7.40145 |
Minimum of Months | 454.00000 | 22.48143 | 14.14963 | -0.5566 | 5.56624 |
Maximum of Months | 514.00000 | 24.47441 | 46.50345 | 0.21725 | 12.52553 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.03642 | 17.66562 | -0.0511 | 6.93021 |
February | 454.00000 | 23.35443 | 18.08246 | 0.04670 | 6.74767 |
March | 514.00000 | 23.81005 | 16.40202 | 0.18874 | 6.99436 |
April | 485.00000 | 24.25678 | 13.52827 | 0.34605 | 8.71163 |
May | 508.00000 | 24.38654 | 21.53860 | -0.3744 | 10.85138 |
June | 496.00000 | 24.40420 | 32.13586 | -0.2231 | 8.10939 |
July | 497.00000 | 24.55917 | 46.09663 | -0.0625 | 7.93521 |
August | 514.00000 | 24.37723 | 44.80613 | -0.1460 | 7.50103 |
September | 485.00000 | 24.43161 | 37.40356 | -0.2553 | 8.42009 |
October | 502.00000 | 24.16586 | 23.35790 | 0.34184 | 9.24716 |
November | 489.00000 | 23.65731 | 17.55737 | 0.12751 | 6.57878 |
December | 497.00000 | 23.03565 | 15.85039 | -0.0612 | 6.65319 |
Annual Sum or Average | 5943.00000 | 23.96037 | 25.44513 | -0.0113 | 7.89941 |
Minimum of Months | 454.00000 | 23.03565 | 13.52827 | -0.3744 | 6.57878 |
Maximum of Months | 514.00000 | 24.55917 | 46.09663 | 0.34605 | 10.85138 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.53144 | 16.32904 | 0.13863 | 9.50742 |
February | 454.00000 | 23.72808 | 16.88025 | 0.20741 | 8.89473 |
March | 514.00000 | 23.88450 | 16.04024 | 0.23128 | 7.66511 |
April | 485.00000 | 24.17123 | 13.65288 | 0.29605 | 7.76339 |
May | 508.00000 | 24.22435 | 22.03368 | -0.5255 | 12.53619 |
June | 496.00000 | 24.30617 | 32.48406 | -0.3832 | 9.09879 |
July | 497.00000 | 24.47377 | 46.45094 | -0.1848 | 7.22997 |
August | 514.00000 | 24.37824 | 44.83034 | -0.1859 | 7.09853 |
September | 485.00000 | 24.50319 | 37.11835 | -0.2102 | 8.33878 |
October | 502.00000 | 24.43301 | 22.63977 | 0.46750 | 12.11554 |
November | 489.00000 | 24.17964 | 16.27856 | 0.33226 | 9.85477 |
December | 497.00000 | 23.69428 | 14.24208 | 0.19025 | 9.28861 |
Annual Sum or Average | 5943.00000 | 24.12755 | 24.99871 | 0.02886 | 9.12016 |
Minimum of Months | 454.00000 | 23.53144 | 13.65288 | -0.5255 | 7.09853 |
Maximum of Months | 514.00000 | 24.50319 | 46.45094 | 0.46750 | 12.53619 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62579 | 16.57309 | 0.10716 | 6.63434 |
February | 454.00000 | 24.09821 | 16.65033 | 0.26386 | 7.53925 |
March | 514.00000 | 24.35704 | 15.43199 | 0.37433 | 8.75000 |
April | 485.00000 | 24.60268 | 13.11491 | 0.49733 | 11.38954 |
May | 508.00000 | 24.48458 | 21.45439 | -0.3200 | 9.38389 |
June | 496.00000 | 24.55433 | 31.81402 | -0.1275 | 7.63902 |
July | 497.00000 | 24.71188 | 45.64105 | 0.06420 | 7.68136 |
August | 514.00000 | 24.58152 | 44.18124 | 0.05257 | 7.21082 |
September | 485.00000 | 24.56840 | 36.99804 | -0.1645 | 7.90754 |
October | 502.00000 | 24.49086 | 22.66195 | 0.46955 | 10.93560 |
November | 489.00000 | 24.37664 | 16.06444 | 0.35514 | 8.41551 |
December | 497.00000 | 24.31973 | 13.62861 | 0.29757 | 7.57291 |
Annual Sum or Average | 5943.00000 | 24.39905 | 24.59908 | 0.15444 | 8.42308 |
Minimum of Months | 454.00000 | 23.62579 | 13.11491 | -0.3200 | 6.63434 |
Maximum of Months | 514.00000 | 24.71188 | 45.64105 | 0.49733 | 11.38954 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.88292 | 19.19493 | -0.6112 | 14.11795 |
February | 454.00000 | 21.34910 | 20.50608 | -0.4777 | 11.29416 |
March | 514.00000 | 22.45352 | 19.57766 | -0.1979 | 7.39561 |
April | 485.00000 | 23.44445 | 15.42886 | 0.04174 | 6.06501 |
May | 508.00000 | 23.96732 | 22.74498 | -0.6618 | 15.58856 |
June | 496.00000 | 24.28048 | 32.34038 | -0.4190 | 9.51702 |
July | 497.00000 | 24.46443 | 46.11543 | -0.2446 | 7.31461 |
August | 514.00000 | 24.29498 | 45.35733 | -0.3293 | 7.96250 |
September | 485.00000 | 24.12436 | 38.51896 | -0.4956 | 11.12662 |
October | 502.00000 | 23.07342 | 25.80758 | 0.01072 | 6.96157 |
November | 489.00000 | 21.77492 | 20.84883 | -0.3593 | 9.34201 |
December | 497.00000 | 20.76136 | 17.10414 | -0.6544 | 14.99145 |
Annual Sum or Average | 5943.00000 | 22.91803 | 27.03227 | -0.3661 | 10.13550 |
Minimum of Months | 454.00000 | 20.76136 | 15.42886 | -0.6618 | 6.06501 |
Maximum of Months | 514.00000 | 24.46443 | 46.11543 | 0.04174 | 15.58856 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.89450 | 17.57847 | -0.3567 | 10.26717 |
February | 385.00000 | 22.37725 | 18.53033 | -0.2100 | 8.90110 |
March | 433.00000 | 23.29236 | 17.32193 | 0.04658 | 7.41425 |
April | 410.00000 | 24.15863 | 13.63937 | 0.30049 | 8.76395 |
May | 430.00000 | 24.37899 | 21.54749 | -0.3937 | 12.30147 |
June | 418.00000 | 24.50169 | 31.21538 | -0.2091 | 8.70349 |
July | 422.00000 | 24.73706 | 44.58553 | -0.0238 | 8.75754 |
August | 433.00000 | 24.52303 | 43.89700 | -0.1233 | 8.03723 |
September | 410.00000 | 24.44516 | 36.89386 | -0.2796 | 9.31913 |
October | 427.00000 | 23.90192 | 23.42745 | 0.25633 | 9.24565 |
November | 417.00000 | 22.86740 | 18.70994 | -0.0765 | 7.45373 |
December | 422.00000 | 21.74604 | 15.79282 | -0.4010 | 10.87742 |
Annual Sum or Average | 5034.00000 | 23.57532 | 25.32087 | -0.1224 | 9.17467 |
Minimum of Months | 385.00000 | 21.74604 | 13.63937 | -0.4010 | 7.41425 |
Maximum of Months | 433.00000 | 24.73706 | 44.58553 | 0.30049 | 12.30147 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.26561 | 15.86532 | 0.07082 | 11.28433 |
February | 454.00000 | 23.41810 | 17.03270 | 0.13394 | 10.21525 |
March | 514.00000 | 23.50411 | 17.26408 | 0.14261 | 8.20135 |
April | 485.00000 | 23.87824 | 14.22150 | 0.21462 | 7.52453 |
May | 508.00000 | 24.05894 | 22.36295 | -0.5926 | 14.59541 |
June | 496.00000 | 24.24043 | 32.37145 | -0.4305 | 10.08199 |
July | 497.00000 | 24.47438 | 46.01814 | -0.2155 | 7.47336 |
August | 514.00000 | 24.37795 | 44.88833 | -0.2187 | 7.47293 |
September | 485.00000 | 24.48236 | 37.07204 | -0.2200 | 9.05778 |
October | 502.00000 | 24.35242 | 23.00190 | 0.45187 | 13.03626 |
November | 489.00000 | 23.90955 | 17.24809 | 0.27565 | 10.99681 |
December | 497.00000 | 23.29476 | 13.81360 | 0.08433 | 10.97480 |
Annual Sum or Average | 5943.00000 | 23.94087 | 25.18176 | -0.0275 | 10.08026 |
Minimum of Months | 454.00000 | 23.26561 | 13.81360 | -0.5926 | 7.47293 |
Maximum of Months | 514.00000 | 24.48236 | 46.01814 | 0.45187 | 14.59541 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.99284 | 17.68794 | -0.3144 | 10.13414 |
February | 454.00000 | 22.50407 | 18.62776 | -0.1570 | 8.78483 |
March | 514.00000 | 23.27324 | 18.02708 | 0.05208 | 7.50182 |
April | 485.00000 | 24.00157 | 14.33968 | 0.26237 | 8.12133 |
May | 508.00000 | 24.22609 | 22.09917 | -0.4579 | 12.19638 |
June | 496.00000 | 24.41385 | 31.97042 | -0.2549 | 8.83040 |
July | 497.00000 | 24.58669 | 45.67183 | -0.0832 | 7.46648 |
August | 514.00000 | 24.44218 | 44.73470 | -0.1422 | 7.27017 |
September | 485.00000 | 24.38982 | 37.44388 | -0.2808 | 9.02918 |
October | 502.00000 | 23.76502 | 24.25309 | 0.24693 | 8.82692 |
November | 489.00000 | 22.90291 | 18.97305 | -0.0524 | 7.65674 |
December | 497.00000 | 21.95912 | 15.62533 | -0.3323 | 10.11880 |
Annual Sum or Average | 5943.00000 | 23.54564 | 25.86441 | -0.1265 | 8.83009 |
Minimum of Months | 454.00000 | 21.95912 | 14.33968 | -0.4579 | 7.27017 |
Maximum of Months | 514.00000 | 24.58669 | 45.67183 | 0.26237 | 12.19638 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25785 | 19.83066 | -0.8102 | 21.29435 |
February | 454.00000 | 20.73531 | 21.08808 | -0.6615 | 16.50719 |
March | 514.00000 | 21.88091 | 19.62362 | -0.3563 | 10.09154 |
April | 485.00000 | 23.09728 | 15.59867 | -0.0452 | 7.00732 |
May | 508.00000 | 23.80998 | 22.76307 | -0.7122 | 18.14166 |
June | 496.00000 | 24.24779 | 32.56864 | -0.4143 | 9.91549 |
July | 497.00000 | 24.46773 | 46.43463 | -0.2197 | 7.37159 |
August | 514.00000 | 24.29142 | 45.50447 | -0.3142 | 8.10449 |
September | 485.00000 | 24.01682 | 38.52263 | -0.5283 | 12.54036 |
October | 502.00000 | 22.61192 | 25.95115 | -0.1132 | 8.43765 |
November | 489.00000 | 20.99491 | 21.45256 | -0.5753 | 14.67884 |
December | 497.00000 | 20.16133 | 17.70219 | -0.8522 | 22.56592 |
Annual Sum or Average | 5943.00000 | 22.56216 | 27.32039 | -0.4658 | 13.03114 |
Minimum of Months | 454.00000 | 20.16133 | 15.59867 | -0.8522 | 7.00732 |
Maximum of Months | 514.00000 | 24.46773 | 46.43463 | -0.0452 | 22.56592 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.18967 | 18.97947 | -0.5569 | 14.88172 |
February | 454.00000 | 21.83396 | 19.73584 | -0.3639 | 11.71959 |
March | 514.00000 | 22.99902 | 17.63349 | -0.0387 | 8.04861 |
April | 485.00000 | 23.97139 | 13.78844 | 0.26433 | 8.54772 |
May | 508.00000 | 24.24062 | 21.43973 | -0.4193 | 12.83212 |
June | 496.00000 | 24.40084 | 31.97629 | -0.2011 | 8.57456 |
July | 497.00000 | 24.62351 | 45.78138 | -0.0083 | 8.43506 |
August | 514.00000 | 24.42870 | 44.79598 | -0.1066 | 7.81186 |
September | 485.00000 | 24.30844 | 37.27582 | -0.2937 | 9.58137 |
October | 502.00000 | 23.61484 | 23.88318 | 0.18440 | 9.17303 |
November | 489.00000 | 22.25872 | 19.92386 | -0.2455 | 9.55667 |
December | 497.00000 | 20.97890 | 17.11341 | -0.6166 | 16.42167 |
Annual Sum or Average | 5943.00000 | 23.24819 | 26.09543 | -0.1993 | 10.45596 |
Minimum of Months | 454.00000 | 20.97890 | 13.78844 | -0.6166 | 7.81186 |
Maximum of Months | 514.00000 | 24.62351 | 45.78138 | 0.26433 | 16.42167 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.53553 | 16.67057 | -0.1476 | 13.12195 |
February | 454.00000 | 22.79636 | 17.72538 | -0.0493 | 11.60947 |
March | 514.00000 | 23.07086 | 17.24628 | 0.01246 | 9.00960 |
April | 485.00000 | 23.59853 | 14.36685 | 0.14160 | 8.02079 |
May | 508.00000 | 23.89660 | 22.37497 | -0.6446 | 17.07331 |
June | 496.00000 | 24.18846 | 32.63915 | -0.4312 | 10.76210 |
July | 497.00000 | 24.47054 | 46.37630 | -0.1931 | 7.63374 |
August | 514.00000 | 24.35981 | 45.09302 | -0.2081 | 7.72566 |
September | 485.00000 | 24.35296 | 37.10579 | -0.2593 | 10.09273 |
October | 502.00000 | 23.95137 | 23.07312 | 0.34037 | 12.21071 |
November | 489.00000 | 23.25761 | 17.79602 | 0.08670 | 10.80230 |
December | 497.00000 | 22.51337 | 14.66790 | -0.1453 | 13.37194 |
Annual Sum or Average | 5943.00000 | 23.58787 | 25.50934 | -0.1263 | 10.95542 |
Minimum of Months | 454.00000 | 22.51337 | 14.36685 | -0.6446 | 7.63374 |
Maximum of Months | 514.00000 | 24.47054 | 46.37630 | 0.34037 | 17.07331 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.28383 | 18.41286 | -0.5164 | 15.18532 |
February | 454.00000 | 21.91170 | 19.23180 | -0.3244 | 11.91573 |
March | 514.00000 | 22.79290 | 18.06061 | -0.0813 | 8.82558 |
April | 485.00000 | 23.71242 | 14.51642 | 0.18984 | 8.48443 |
May | 508.00000 | 24.08269 | 22.09222 | -0.5039 | 14.29081 |
June | 496.00000 | 24.36996 | 32.22810 | -0.2544 | 9.46185 |
July | 497.00000 | 24.58306 | 46.03699 | -0.0624 | 7.77723 |
August | 514.00000 | 24.43413 | 44.91257 | -0.1298 | 7.50584 |
September | 485.00000 | 24.30191 | 37.41802 | -0.3078 | 9.99213 |
October | 502.00000 | 23.39407 | 24.32862 | 0.14568 | 9.35951 |
November | 489.00000 | 22.22563 | 19.52207 | -0.2374 | 10.21832 |
December | 497.00000 | 21.27026 | 16.29744 | -0.5316 | 15.23345 |
Annual Sum or Average | 5943.00000 | 23.20660 | 26.16160 | -0.2175 | 10.68023 |
Minimum of Months | 454.00000 | 21.27026 | 14.51642 | -0.5316 | 7.50584 |
Maximum of Months | 514.00000 | 24.58306 | 46.03699 | 0.18984 | 15.23345 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.107405E+11 | 64835.03 | 05-JAN-15:40 | 168.17 | 0.612307E+11 | 0.00 | 0.719712E+11 | 1.16 | 7.40 | 05-JAN-15:40 | 0.00 | 0.00 |
February | 0.140548E+11 | 141390.26 | 14-FEB-16:30 | 184.46 | 0.874311E+11 | 0.00 | 0.101486E+12 | 1.44 | 7.59 | 13-FEB-14:20 | 0.00 | 0.00 |
March | 0.280620E+11 | 128717.25 | 08-MAR-14:20 | 238.04 | 0.179773E+12 | 0.00 | 0.207835E+12 | 1.81 | 7.59 | 13-MAR-13:20 | 0.00 | 0.00 |
April | 0.485553E+11 | 141570.01 | 26-APR-16:40 | 326.08 | 0.330336E+12 | 0.00 | 0.378891E+12 | 2.71 | 7.59 | 26-APR-18:00 | 0.00 | 0.00 |
May | 0.754516E+11 | 143457.17 | 15-MAY-17:40 | 376.47 | 0.527999E+12 | 0.00 | 0.603451E+12 | 3.26 | 7.59 | 22-MAY-16:20 | 0.00 | 0.00 |
June | 0.115938E+12 | 152452.50 | 24-JUN-10:30 | 527.48 | 0.833682E+12 | 0.00 | 0.949620E+12 | 4.86 | 7.59 | 29-JUN-05:03 | 0.00 | 0.00 |
July | 0.139398E+12 | 151565.78 | 31-JUL-17:10 | 645.84 | 0.993012E+12 | 0.00 | 0.113241E+13 | 5.64 | 7.60 | 21-JUL-04:14 | 0.00 | 0.00 |
August | 0.136059E+12 | 151399.25 | 12-AUG-10:30 | 674.83 | 0.972635E+12 | 0.00 | 0.110869E+13 | 5.80 | 7.60 | 14-AUG-04:13 | 0.00 | 0.00 |
September | 0.961210E+11 | 146881.59 | 12-SEP-11:53 | 452.28 | 0.681875E+12 | 0.00 | 0.777996E+12 | 4.11 | 7.60 | 05-SEP-04:13 | 0.00 | 0.00 |
October | 0.588562E+11 | 143885.08 | 10-OCT-12:07 | 353.71 | 0.405433E+12 | 0.00 | 0.464289E+12 | 2.91 | 7.59 | 03-OCT-10:50 | 0.00 | 0.00 |
November | 0.224380E+11 | 99648.75 | 02-NOV-15:10 | 215.19 | 0.138332E+12 | 0.00 | 0.160770E+12 | 1.66 | 7.58 | 02-NOV-16:00 | 0.00 | 0.00 |
December | 0.656422E+10 | 54956.67 | 29-DEC-15:50 | 214.48 | 0.330275E+11 | 0.00 | 0.395917E+11 | 1.40 | 7.14 | 29-DEC-15:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.752238E+12 | 4377.03 | 0.524477E+13 | 0.00 | 0.599701E+13 | 3.07 | 0.00 | 0.00 | ||||
Minimum of Months | 0.656422E+10 | 54956.67 | 168.17 | 0.330275E+11 | 0.00 | 0.395917E+11 | 1.16 | 7.14 | 0.00 | 0.00 | ||
Maximum of Months | 0.139398E+12 | 152452.50 | 674.83 | 0.993012E+12 | 0.00 | 0.113241E+13 | 5.80 | 7.60 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 3552848.40 | 5921.41 | 14-FEB-16:00 | 0.17 | 19162993.12 | 0.00 | 22715841.52 | 0.00 | 5.39 | 14-FEB-16:00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.545023E+10 | 96288.33 | 13-APR-14:05 | 20.42 | 0.404842E+11 | 0.00 | 0.459344E+11 | 0.21 | 7.59 | 11-APR-14:05 | 0.00 | 0.00 |
May | 0.113889E+11 | 95851.62 | 30-MAY-12:05 | 42.42 | 0.846273E+11 | 0.00 | 0.960162E+11 | 0.42 | 7.59 | 23-MAY-10:10 | 0.00 | 0.00 |
June | 0.461337E+11 | 129237.36 | 06-JUN-13:05 | 156.37 | 0.345270E+12 | 0.00 | 0.391403E+12 | 1.62 | 7.59 | 21-JUN-13:40 | 0.00 | 0.00 |
July | 0.619787E+11 | 126692.62 | 14-JUL-08:12 | 200.92 | 0.455558E+12 | 0.00 | 0.517536E+12 | 1.98 | 7.59 | 03-JUL-13:05 | 0.00 | 0.00 |
August | 0.553882E+11 | 126698.95 | 18-AUG-08:23 | 181.88 | 0.409660E+12 | 0.00 | 0.465048E+12 | 1.80 | 7.59 | 11-AUG-15:00 | 0.00 | 0.00 |
September | 0.279608E+11 | 135465.43 | 06-SEP-12:12 | 97.76 | 0.208182E+12 | 0.00 | 0.236143E+12 | 1.01 | 7.59 | 21-SEP-15:40 | 0.00 | 0.00 |
October | 0.881636E+10 | 122009.03 | 02-OCT-12:03 | 32.76 | 0.659751E+11 | 0.00 | 0.747915E+11 | 0.33 | 7.59 | 04-OCT-14:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.217121E+12 | 732.69 | 0.160977E+13 | 0.00 | 0.182690E+13 | 0.62 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.619787E+11 | 135465.43 | 200.92 | 0.455558E+12 | 0.00 | 0.517536E+12 | 1.98 | 7.59 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.225559E+10 | 744.00 | 5665.38 | 05-JAN-16:00 | 49246.84 | 26-JAN-17:00 | 18.81 | 18.33 | 15.48 |
February | 0.701385E+10 | 672.00 | 43776.24 | 12-FEB-14:21 | 210706.10 | 14-FEB-16:00 | 19.49 | 18.39 | 15.48 |
March | 0.236829E+11 | 744.00 | 43776.24 | 06-MAR-15:00 | 382696.78 | 08-MAR-16:10 | 20.60 | 18.63 | 15.48 |
April | 0.603335E+11 | 720.00 | 43776.24 | 01-APR-09:50 | 614047.27 | 26-APR-17:10 | 25.57 | 20.78 | 15.48 |
May | 0.627610E+11 | 744.00 | 43776.24 | 02-MAY-12:05 | 263348.09 | 22-MAY-14:05 | 22.33 | 21.03 | 15.48 |
June | 0.934138E+11 | 720.00 | 43776.24 | 01-JUN-00:10 | 481670.20 | 30-JUN-14:00 | 30.79 | 26.41 | 15.47 |
July | 0.117218E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 698155.45 | 31-JUL-24:00 | 40.28 | 30.98 | 15.48 |
August | 0.117141E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 731431.25 | 20-AUG-18:01 | 42.47 | 30.80 | 15.48 |
September | 0.809902E+11 | 720.00 | 43776.24 | 01-SEP-00:03 | 267844.55 | 01-SEP-16:40 | 23.90 | 22.27 | 15.48 |
October | 0.459381E+11 | 744.00 | 43776.24 | 01-OCT-08:52 | 417997.97 | 01-OCT-16:21 | 21.70 | 19.83 | 15.48 |
November | 0.104048E+11 | 720.00 | 43776.24 | 02-NOV-14:40 | 259055.31 | 09-NOV-14:05 | 20.01 | 18.34 | 15.48 |
December | 0.701349E+10 | 744.00 | 16083.34 | 24-DEC-15:00 | 181618.25 | 24-DEC-15:00 | 20.37 | 18.33 | 15.48 |
Annual Sum or Average | 0.628166E+12 | 8760.00 | 25.58 | 22.04 | 15.48 | ||||
Minimum of Months | 0.225559E+10 | 672.00 | 5665.38 | 49246.84 | 18.81 | 18.33 | 15.47 | ||
Maximum of Months | 0.117218E+12 | 744.00 | 43776.24 | 731431.25 | 42.47 | 30.98 | 15.48 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 555959.29 | 05-JAN-15:40 | 21.04 | 20.90 | 6.29 |
February | 24303681.79 | 30.50 | 1140.83 | 14-FEB-16:00 | 1174292.01 | 14-FEB-15:50 | 21.16 | 20.96 | 7.24 |
March | 70131982.14 | 126.67 | 1212.04 | 08-MAR-14:20 | 1059687.74 | 08-MAR-14:20 | 21.41 | 21.03 | 12.44 |
April | 0.214589E+09 | 199.10 | 1430.54 | 14-APR-13:05 | 1162209.69 | 27-APR-12:50 | 21.76 | 21.03 | 18.42 |
May | 0.648485E+09 | 312.48 | 14972.55 | 22-MAY-12:10 | 1154388.61 | 15-MAY-16:10 | 22.42 | 21.29 | 24.77 |
June | 0.351626E+10 | 439.75 | 14972.55 | 06-JUN-11:00 | 1147485.92 | 19-JUN-16:10 | 23.08 | 21.19 | 35.22 |
July | 0.140262E+11 | 512.45 | 14972.55 | 01-JUL-09:50 | 1147055.23 | 13-JUL-08:70 | 23.43 | 21.38 | 40.95 |
August | 0.112680E+11 | 499.84 | 14972.55 | 01-AUG-07:45 | 1149651.65 | 21-AUG-18:10 | 23.25 | 21.22 | 41.07 |
September | 0.323436E+10 | 395.30 | 14972.55 | 01-SEP-09:00 | 1177496.04 | 20-SEP-11:10 | 22.90 | 21.35 | 31.01 |
October | 0.879002E+09 | 247.97 | 14972.55 | 02-OCT-10:40 | 1169731.68 | 05-OCT-12:00 | 22.05 | 21.18 | 20.86 |
November | 36234634.56 | 113.08 | 797.44 | 02-NOV-15:30 | 862020.62 | 02-NOV-15:20 | 21.23 | 20.92 | 11.59 |
December | 1610410.63 | 8.00 | 117.76 | 29-DEC-15:50 | 458034.53 | 29-DEC-16:00 | 20.99 | 20.89 | 5.06 |
Annual Sum or Average | 0.339191E+11 | 2885.14 | 22.06 | 21.11 | 21.33 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 458034.53 | 20.99 | 20.89 | 5.06 | ||
Maximum of Months | 0.140262E+11 | 512.45 | 14972.55 | 1177496.04 | 23.43 | 21.38 | 41.07 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.04 | 21.04 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.16 | 21.16 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.41 | 21.41 | 0.00 |
April | 34353447.87 | 16.25 | 1399.13 | 27-APR-14:00 | 1013744.86 | 11-APR-14:30 | 21.76 | 21.67 | 1.17 |
May | 0.108481E+09 | 33.83 | 14972.55 | 22-MAY-12:40 | 1062019.21 | 19-MAY-14:40 | 22.42 | 22.22 | 2.37 |
June | 0.184770E+10 | 145.45 | 14972.55 | 06-JUN-13:05 | 1064073.23 | 07-JUN-14:20 | 23.08 | 22.25 | 10.48 |
July | 0.865103E+10 | 186.14 | 14972.55 | 01-JUL-11:05 | 1064119.93 | 13-JUL-08:12 | 23.43 | 22.50 | 12.96 |
August | 0.670947E+10 | 166.74 | 14972.55 | 01-AUG-08:15 | 1096898.37 | 18-AUG-08:23 | 23.25 | 22.40 | 11.62 |
September | 0.147755E+10 | 86.51 | 14972.55 | 01-SEP-09:57 | 1115271.68 | 06-SEP-12:12 | 22.90 | 22.38 | 6.25 |
October | 0.291403E+09 | 29.01 | 14972.55 | 02-OCT-13:40 | 1061981.01 | 06-OCT-15:30 | 22.05 | 21.88 | 2.03 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.23 | 21.23 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.99 | 20.99 | 0.00 |
Annual Sum or Average | 0.191200E+11 | 663.94 | 22.06 | 21.76 | 3.93 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 20.99 | 0.00 | ||
Maximum of Months | 0.865103E+10 | 186.14 | 14972.55 | 1115271.68 | 23.43 | 22.50 | 12.96 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.200819E+12 | 0.00 | 396.79 | 1229366.37 | 10-JAN-06:01 | 0.00 | 37.46 | 49.05 | 0.98 | 0.00 | 0.04 | 0.65 | 10-JAN-06:01 |
February | 0.126074E+12 | 0.00 | 303.29 | 1192916.36 | 27-FEB-06:01 | 0.00 | 36.39 | 46.56 | 0.64 | 0.00 | 0.03 | 0.63 | 27-FEB-06:01 |
March | 0.425537E+11 | 0.00 | 207.74 | 1145481.60 | 06-MAR-06:01 | 0.00 | 34.42 | 41.46 | 0.16 | 0.00 | 0.01 | 0.60 | 06-MAR-06:01 |
April | 0.740853E+10 | 0.00 | 64.38 | 629936.32 | 08-APR-05:03 | 0.00 | 32.91 | 35.24 | 0.03 | 0.00 | 0.00 | 0.33 | 08-APR-05:03 |
May | 0.131131E+10 | 0.00 | 17.91 | 134716.11 | 05-MAY-05:02 | 0.00 | 31.70 | 32.38 | 0.00 | 0.00 | 0.00 | 0.07 | 05-MAY-05:02 |
June | 4645850.27 | 0.00 | 1.58 | 2838.51 | 09-JUN-06:10 | 0.00 | 31.65 | 31.72 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.63 | 31.63 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 31.63 | 31.63 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2031.77 | 0.00 | 0.08 | 6.77 | 09-SEP-06:10 | 0.00 | 31.63 | 31.64 | 0.00 | 0.00 | 0.00 | 0.00 | 09-SEP-06:10 |
October | 0.231251E+11 | 0.00 | 98.93 | 1065878.44 | 26-OCT-05:02 | 0.00 | 32.76 | 36.12 | 0.09 | 0.00 | 0.00 | 0.56 | 26-OCT-05:02 |
November | 0.571066E+11 | 0.00 | 238.54 | 1066778.21 | 28-NOV-06:01 | 0.00 | 34.36 | 42.56 | 0.24 | 0.00 | 0.01 | 0.56 | 28-NOV-06:01 |
December | 0.193988E+12 | 0.00 | 413.01 | 1174565.01 | 07-DEC-06:01 | 0.00 | 36.97 | 49.41 | 0.93 | 0.00 | 0.04 | 0.62 | 07-DEC-06:01 |
Annual Sum or Average | 0.652391E+12 | 0.00 | 1742.27 | 0.00 | 33.61 | 38.25 | 0.26 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 | 31.63 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.200819E+12 | 0.00 | 413.01 | 1229366.37 | 0.00 | 37.46 | 49.41 | 0.98 | 0.00 | 0.04 | 0.65 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.81 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.49 | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.60 | 20.60 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 25.57 | 25.57 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22.33 | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 30.79 | 30.79 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 40.28 | 40.28 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 42.47 | 42.47 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 23.90 | 23.90 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 21.70 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 20.01 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.37 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 25.58 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.47 | 42.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.136806E+11 | 0.00 | 155.36 | 0.136806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62636.63 | 02-JAN-15:00 | 62636.63 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.132250E+11 | 0.00 | 153.16 | 0.132250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71124.88 | 14-FEB-16:00 | 71124.88 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.153233E+11 | 0.00 | 186.10 | 0.153233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76602.50 | 08-MAR-16:00 | 76602.50 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.360934E+11 | 0.00 | 284.36 | 0.360934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110062.57 | 17-APR-15:20 | 110062.57 | 17-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.540390E+11 | 0.00 | 356.11 | 0.540390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113768.69 | 30-MAY-14:30 | 113768.69 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.105332E+12 | 0.00 | 506.18 | 0.105330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 136600.14 | 26-JUN-15:00 | 136600.14 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.134074E+12 | 0.00 | 621.97 | 0.130892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 145658.68 | 31-JUL-15:00 | 137150.53 | 05-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.136749E+12 | 0.00 | 651.56 | 0.132991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 148895.67 | 21-AUG-10:50 | 143543.60 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.779151E+11 | 0.00 | 432.33 | 0.767706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158339.03 | 05-SEP-13:10 | 113778.46 | 11-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.420163E+11 | 0.00 | 311.69 | 0.420092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127568.32 | 10-OCT-12:15 | 124969.33 | 10-OCT-12:15 | 0.00 | 0.00 | 0.00 |
November | 0.115907E+11 | 0.00 | 144.58 | 0.115907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56745.76 | 24-NOV-11:00 | 56745.76 | 24-NOV-11:00 | 0.00 | 0.00 | 0.00 |
December | 0.169081E+11 | 0.00 | 190.03 | 0.169081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55327.36 | 29-DEC-15:40 | 55327.36 | 29-DEC-15:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.656947E+12 | 0.00 | 3993.45 | 0.648852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.115907E+11 | 0.00 | 144.58 | 0.115907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55327.36 | 55327.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.136749E+12 | 0.00 | 651.56 | 0.132991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 158339.03 | 143543.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.424281E+11 | 0.00 | 92.67 | 0.424281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 411635.42 | 05-JAN-15:40 | 411635.42 | 05-JAN-15:40 | 0.00 | 0.00 | 0.00 |
February | 0.634886E+11 | 0.00 | 108.77 | 0.634886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 658001.66 | 14-FEB-16:00 | 658001.66 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.148008E+12 | 0.00 | 196.25 | 0.148008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 621194.07 | 08-MAR-14:10 | 621194.07 | 08-MAR-14:10 | 0.00 | 0.00 | 0.00 |
April | 0.278717E+12 | 0.00 | 268.90 | 0.278717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 904814.97 | 26-APR-15:10 | 904814.97 | 26-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.469150E+12 | 0.00 | 348.50 | 0.469150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1013259.37 | 19-MAY-15:10 | 1013259.37 | 19-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.904054E+12 | 0.00 | 449.98 | 0.903958E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1289226.45 | 27-JUN-16:02 | 1289226.45 | 27-JUN-16:02 | 0.00 | 0.00 | 0.00 |
July | 0.109121E+13 | 0.00 | 485.03 | 0.107021E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1337885.84 | 16-JUL-14:41 | 1252410.68 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.104038E+13 | 0.00 | 489.77 | 0.101967E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1345523.00 | 13-AUG-16:51 | 1220299.64 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.683815E+12 | 0.00 | 416.10 | 0.674015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1385870.39 | 05-SEP-14:05 | 1042583.36 | 21-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.362449E+12 | 0.00 | 304.50 | 0.362386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 983543.33 | 06-OCT-15:30 | 983543.33 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.117053E+12 | 0.00 | 168.32 | 0.117053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 574197.73 | 02-NOV-15:20 | 574197.73 | 02-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.123027E+11 | 0.00 | 67.43 | 0.123027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 318269.87 | 29-DEC-16:00 | 318269.87 | 29-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.521305E+13 | 0.00 | 3396.22 | 0.516139E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123027E+11 | 0.00 | 67.43 | 0.123027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 318269.87 | 318269.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109121E+13 | 0.00 | 489.77 | 0.107021E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1385870.39 | 1289226.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.354229E+10 | 0.00 | 69.87 | 0.354229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31967.33 | 23-JAN-15:40 | 31967.33 | 23-JAN-15:40 | 0.00 | 0.00 | 0.00 |
February | 0.518650E+10 | 0.00 | 76.95 | 0.518650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67153.17 | 14-FEB-16:00 | 67153.17 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.746871E+10 | 0.00 | 128.20 | 0.746871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62786.56 | 08-MAR-16:00 | 62786.56 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.283005E+11 | 0.00 | 248.28 | 0.283005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110406.32 | 26-APR-15:10 | 110406.32 | 26-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.514938E+11 | 0.00 | 345.00 | 0.514938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123270.27 | 19-MAY-15:10 | 123270.27 | 19-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.102822E+12 | 0.00 | 446.26 | 0.102818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 169441.78 | 28-JUN-13:45 | 169441.78 | 28-JUN-13:45 | 0.00 | 0.00 | 0.00 |
July | 0.124854E+12 | 0.00 | 486.99 | 0.122734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 163003.89 | 16-JUL-14:52 | 159180.81 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 |
August | 0.117512E+12 | 0.00 | 487.86 | 0.115493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 155771.56 | 13-AUG-15:51 | 148406.91 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.740373E+11 | 0.00 | 408.11 | 0.732564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152631.88 | 05-SEP-13:40 | 125868.99 | 21-SEP-15:10 | 0.00 | 0.00 | 0.00 |
October | 0.323835E+11 | 0.00 | 263.30 | 0.323835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111923.64 | 06-OCT-15:20 | 111923.64 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.706422E+10 | 0.00 | 116.46 | 0.706422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52988.34 | 01-NOV-15:00 | 52988.34 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.162538E+10 | 0.00 | 59.28 | 0.162538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24458.62 | 29-DEC-15:40 | 24458.62 | 29-DEC-15:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556290E+12 | 0.00 | 3136.57 | 0.551366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.162538E+10 | 0.00 | 59.28 | 0.162538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24458.62 | 24458.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124854E+12 | 0.00 | 487.86 | 0.122734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 169441.78 | 169441.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 18457435.52 | 0.00 | 2.33 | 18457435.52 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.34 | 02-JAN-15:00 | 3339.34 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.119837E+10 | 0.00 | 16.17 | 0.119837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39196.42 | 13-FEB-16:00 | 39196.42 | 13-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.321518E+10 | 0.00 | 66.12 | 0.321518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39987.98 | 13-MAR-15:00 | 39987.98 | 13-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.174706E+11 | 0.00 | 179.68 | 0.174706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57713.25 | 17-APR-15:00 | 57713.25 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.309356E+11 | 0.00 | 264.14 | 0.309298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94731.19 | 29-MAY-15:50 | 94731.19 | 29-MAY-15:50 | 0.00 | 0.00 | 0.00 |
June | 0.576222E+11 | 0.00 | 366.93 | 0.576030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73030.89 | 26-JUN-13:10 | 73030.89 | 26-JUN-13:10 | 0.00 | 0.00 | 0.00 |
July | 0.701967E+11 | 0.00 | 396.90 | 0.690645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118991.52 | 02-JUL-19:12 | 95073.59 | 04-JUL-15:58 | 0.00 | 0.00 | 0.00 |
August | 0.708198E+11 | 0.00 | 429.40 | 0.697064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99985.31 | 13-AUG-18:55 | 85544.96 | 13-AUG-18:55 | 0.00 | 0.00 | 0.00 |
September | 0.469623E+11 | 0.00 | 345.13 | 0.460654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98256.65 | 05-SEP-13:00 | 83238.05 | 04-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 0.218102E+11 | 0.00 | 199.89 | 0.217962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95075.62 | 01-OCT-15:54 | 95075.62 | 01-OCT-15:54 | 0.00 | 0.00 | 0.00 |
November | 0.564812E+09 | 0.00 | 27.62 | 0.564812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25530.23 | 09-NOV-05:12 | 25530.23 | 09-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320814E+12 | 0.00 | 2294.30 | 0.317633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.708198E+11 | 0.00 | 429.40 | 0.697064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118991.52 | 95075.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.115745E+11 | 0.548796E+10 | 744.00 | 0.100176E+11 | 0.155681E+10 | 0.00 | 0.03 | 02-JAN-11:50 | 0.02 | 20-JAN-13:10 | 5618.33 | 11-JAN-12:40 | 4922.27 | 22-JAN-17:23 | 739.09 | 01-JAN-10:53 | 2386.03 | 11-JAN-12:40 | 0.00 |
February | 0.157505E+11 | 0.672561E+10 | 672.00 | 0.142469E+11 | 0.150353E+10 | 0.00 | 0.35 | 14-FEB-16:00 | 0.02 | 17-FEB-09:00 | 105812.04 | 14-FEB-16:00 | 105812.04 | 14-FEB-16:00 | 1244.36 | 19-FEB-08:15 | 37224.04 | 14-FEB-16:00 | 0.00 |
March | 0.477436E+11 | 0.173199E+11 | 744.00 | 0.468015E+11 | 0.942012E+09 | 0.00 | 0.64 | 08-MAR-16:00 | 0.02 | 28-MAR-17:00 | 212529.09 | 08-MAR-16:00 | 212529.09 | 08-MAR-16:00 | 5386.22 | 16-MAR-12:05 | 72874.65 | 08-MAR-16:00 | 0.00 |
April | 0.278842E+12 | 0.935809E+11 | 720.00 | 0.276783E+12 | 0.205894E+10 | 0.00 | 1.00 | 01-APR-15:00 | 0.03 | 30-APR-24:00 | 354438.82 | 28-APR-14:40 | 354438.82 | 28-APR-14:40 | 35019.13 | 15-APR-01:20 | 128317.36 | 13-APR-17:00 | 0.00 |
May | 0.687179E+11 | 0.255810E+11 | 671.60 | 0.664888E+11 | 0.222910E+10 | 0.00 | 0.43 | 08-MAY-15:30 | 0.00 | 21-MAY-05:53 | 145814.76 | 22-MAY-12:05 | 137424.26 | 30-MAY-12:30 | 14665.45 | 22-MAY-10:20 | 51916.57 | 19-MAY-16:00 | 0.00 |
June | 0.325364E+12 | 0.114690E+12 | 664.46 | 0.302496E+12 | 0.228671E+11 | 0.00 | 0.73 | 30-JUN-14:00 | 0.00 | 04-JUN-06:10 | 305988.88 | 30-JUN-14:00 | 230007.03 | 28-JUN-16:00 | 87006.88 | 30-JUN-14:00 | 105219.65 | 28-JUN-16:00 | 0.00 |
July | 0.821403E+12 | 0.264289E+12 | 744.00 | 0.638836E+12 | 0.182567E+12 | 0.00 | 1.00 | 02-JUL-10:52 | 0.18 | 08-JUL-03:00 | 449591.88 | 31-JUL-24:00 | 342766.28 | 04-JUL-09:21 | 270820.95 | 01-JUL-00:55 | 143247.11 | 22-JUL-15:00 | 0.00 |
August | 0.104110E+13 | 0.317811E+12 | 744.00 | 0.778230E+12 | 0.262871E+12 | 0.00 | 1.00 | 01-AUG-00:05 | 0.07 | 31-AUG-24:00 | 459378.07 | 26-AUG-10:00 | 411853.57 | 21-AUG-14:55 | 283481.70 | 13-AUG-03:00 | 156347.87 | 20-AUG-16:00 | 0.00 |
September | 0.974429E+11 | 0.347296E+11 | 531.88 | 0.876029E+11 | 0.984000E+10 | 0.00 | 0.44 | 01-SEP-12:50 | 0.00 | 08-SEP-02:20 | 169778.89 | 01-SEP-12:40 | 140620.96 | 01-SEP-14:00 | 47918.45 | 05-SEP-14:00 | 54658.56 | 03-SEP-14:00 | 0.00 |
October | 0.824924E+11 | 0.282037E+11 | 712.62 | 0.746700E+11 | 0.782237E+10 | 0.00 | 0.65 | 05-OCT-17:00 | 0.00 | 07-OCT-06:10 | 249340.04 | 10-OCT-13:30 | 228371.31 | 06-OCT-14:10 | 66660.23 | 11-OCT-10:50 | 82860.18 | 01-OCT-16:00 | 0.00 |
November | 0.186745E+11 | 0.792998E+10 | 719.83 | 0.173060E+11 | 0.136858E+10 | 0.00 | 0.39 | 09-NOV-14:00 | 0.01 | 01-NOV-01:10 | 130607.10 | 09-NOV-14:00 | 124468.89 | 09-NOV-14:00 | 13747.04 | 02-NOV-16:00 | 39533.63 | 09-NOV-14:00 | 0.00 |
December | 0.162912E+11 | 0.777972E+10 | 744.00 | 0.158461E+11 | 0.445141E+09 | 0.00 | 0.21 | 24-DEC-14:52 | 0.03 | 04-DEC-13:15 | 56730.98 | 24-DEC-14:52 | 56730.98 | 24-DEC-14:52 | 1931.29 | 25-DEC-09:00 | 18944.25 | 24-DEC-14:52 | 0.00 |
Annual Sum or Average | 0.282540E+13 | 0.924129E+12 | 8412.39 | 0.232932E+13 | 0.496072E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.115745E+11 | 0.548796E+10 | 531.88 | 0.100176E+11 | 0.445141E+09 | 0.00 | 0.03 | 0.00 | 5618.33 | 4922.27 | 739.09 | 2386.03 | 0.00 | ||||||
Maximum of Months | 0.104110E+13 | 0.317811E+12 | 744.00 | 0.778230E+12 | 0.262871E+12 | 0.00 | 1.00 | 0.18 | 459378.07 | 411853.57 | 283481.70 | 156347.87 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.471219E+10 | 0.120332E+10 | 744.00 | 0.471149E+10 | 701863.04 | 0.00 | 0.37 | 22-JAN-16:55 | 0.13 | 21-JAN-07:05 | 3067.73 | 01-JAN-16:43 | 3059.44 | 01-JAN-16:47 | 30.13 | 20-JAN-17:00 | 720.69 | 22-JAN-16:55 | 0.00 |
February | 0.919745E+10 | 0.220102E+10 | 672.00 | 0.919453E+10 | 2919355.47 | 0.00 | 0.59 | 14-FEB-17:00 | 0.38 | 04-FEB-07:25 | 4826.80 | 15-FEB-17:00 | 4826.80 | 15-FEB-17:00 | 80.47 | 17-FEB-11:10 | 1295.90 | 14-FEB-17:00 | 0.00 |
March | 0.157024E+11 | 0.360817E+10 | 744.00 | 0.156968E+11 | 5527527.00 | 0.00 | 0.87 | 12-MAR-17:35 | 0.61 | 04-MAR-07:03 | 7734.10 | 31-MAR-24:00 | 7734.10 | 31-MAR-24:00 | 125.22 | 20-MAR-14:40 | 1940.19 | 12-MAR-17:01 | 0.00 |
April | 0.204424E+11 | 0.490436E+10 | 720.00 | 0.204413E+11 | 1091156.48 | 0.00 | 1.00 | 01-APR-15:00 | 0.33 | 30-APR-24:00 | 8942.59 | 16-APR-18:34 | 8942.59 | 16-APR-18:34 | 75.42 | 15-APR-08:30 | 2712.57 | 13-APR-17:00 | 0.00 |
May | 0.607853E+10 | 0.165761E+10 | 744.00 | 0.603787E+10 | 40666269.16 | 0.00 | 0.50 | 31-MAY-23:30 | 0.20 | 05-MAY-06:03 | 4117.92 | 31-MAY-24:00 | 4117.92 | 31-MAY-24:00 | 261.29 | 24-MAY-15:30 | 1094.06 | 20-MAY-18:10 | 0.00 |
June | 0.111594E+11 | 0.334574E+10 | 720.00 | 0.110705E+11 | 88963339.15 | 0.00 | 0.73 | 18-JUN-18:21 | 0.44 | 09-JUN-06:30 | 5999.20 | 30-JUN-23:55 | 5976.91 | 30-JUN-24:00 | 320.76 | 08-JUN-12:00 | 2173.43 | 28-JUN-16:00 | 0.00 |
July | 0.167853E+11 | 0.538348E+10 | 744.00 | 0.165731E+11 | 0.212225E+09 | 0.00 | 0.95 | 04-JUL-18:21 | 0.67 | 08-JUL-06:10 | 7900.33 | 31-JUL-24:00 | 7900.33 | 31-JUL-24:00 | 464.05 | 07-JUL-17:00 | 2929.76 | 04-JUL-18:11 | 0.00 |
August | 0.218094E+11 | 0.668112E+10 | 744.00 | 0.215886E+11 | 0.220896E+09 | 0.00 | 1.00 | 01-AUG-12:40 | 0.33 | 31-AUG-24:00 | 8637.73 | 23-AUG-18:10 | 8611.65 | 27-AUG-18:35 | 418.78 | 23-AUG-14:00 | 3264.68 | 20-AUG-16:00 | 0.00 |
September | 0.619334E+10 | 0.170074E+10 | 720.00 | 0.604625E+10 | 0.147094E+09 | 0.00 | 0.48 | 30-SEP-24:00 | 0.23 | 09-SEP-06:05 | 4145.93 | 30-SEP-23:40 | 4125.08 | 30-SEP-24:00 | 326.10 | 05-SEP-16:40 | 1164.69 | 02-SEP-17:42 | 0.00 |
October | 0.110533E+11 | 0.271231E+10 | 744.00 | 0.109949E+11 | 58393608.19 | 0.00 | 0.69 | 31-OCT-24:00 | 0.40 | 26-OCT-06:55 | 5928.57 | 31-OCT-24:00 | 5928.57 | 31-OCT-24:00 | 311.75 | 02-OCT-17:00 | 1694.08 | 01-OCT-16:01 | 0.00 |
November | 0.151567E+11 | 0.343279E+10 | 720.00 | 0.151437E+11 | 12999970.47 | 0.00 | 0.82 | 19-NOV-16:35 | 0.62 | 10-NOV-07:50 | 7102.13 | 05-NOV-16:47 | 7102.13 | 05-NOV-16:47 | 181.09 | 09-NOV-16:10 | 1604.00 | 19-NOV-16:35 | 0.00 |
December | 0.203871E+11 | 0.455946E+10 | 744.00 | 0.203870E+11 | 159919.45 | 0.00 | 1.00 | 17-DEC-16:02 | 0.80 | 09-DEC-07:10 | 8850.02 | 31-DEC-16:40 | 8850.02 | 31-DEC-16:40 | 24.88 | 27-DEC-17:05 | 1951.33 | 31-DEC-16:40 | 0.00 |
Annual Sum or Average | 0.158678E+12 | 0.413901E+11 | 8760.00 | 0.157886E+12 | 0.791637E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.471219E+10 | 0.120332E+10 | 672.00 | 0.471149E+10 | 159919.45 | 0.00 | 0.37 | 0.13 | 3067.73 | 3059.44 | 24.88 | 720.69 | 0.00 | ||||||
Maximum of Months | 0.218094E+11 | 0.668112E+10 | 744.00 | 0.215886E+11 | 0.220896E+09 | 0.00 | 1.00 | 0.80 | 8942.59 | 8942.59 | 464.05 | 3264.68 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.280791E+11 | 0.744626E+10 | 742.33 | 0.280720E+11 | 7170883.14 | 0.00 | 0.34 | 26-JAN-17:00 | 0.00 | 01-JAN-06:05 | 25764.90 | 26-JAN-17:00 | 25764.90 | 26-JAN-17:00 | 296.34 | 20-JAN-17:00 | 6418.40 | 26-JAN-17:00 | 0.00 |
February | 0.748152E+11 | 0.181683E+11 | 672.00 | 0.747858E+11 | 29440759.23 | 0.00 | 0.58 | 14-FEB-17:00 | 0.24 | 06-FEB-07:10 | 45813.12 | 15-FEB-17:00 | 45813.12 | 15-FEB-17:00 | 778.05 | 17-FEB-11:10 | 12252.86 | 14-FEB-17:00 | 0.00 |
March | 0.140638E+12 | 0.325877E+11 | 744.00 | 0.140581E+12 | 56616838.10 | 0.00 | 0.85 | 12-MAR-17:22 | 0.53 | 04-MAR-07:03 | 71714.65 | 31-MAR-23:30 | 71714.65 | 31-MAR-23:30 | 1239.12 | 20-MAR-14:40 | 17923.42 | 12-MAR-17:01 | 0.00 |
April | 0.190807E+12 | 0.460173E+11 | 720.00 | 0.190796E+12 | 11195460.17 | 0.00 | 1.00 | 01-APR-15:20 | 0.30 | 30-APR-24:00 | 85261.24 | 16-APR-18:32 | 85261.24 | 16-APR-18:32 | 745.60 | 15-APR-08:30 | 26007.41 | 13-APR-17:00 | 0.00 |
May | 0.544659E+11 | 0.149828E+11 | 744.00 | 0.540668E+11 | 0.399155E+09 | 0.00 | 0.49 | 31-MAY-23:30 | 0.15 | 05-MAY-06:03 | 39010.16 | 31-MAY-24:00 | 39010.16 | 31-MAY-24:00 | 2556.79 | 24-MAY-15:40 | 10651.49 | 20-MAY-18:10 | 0.00 |
June | 0.104926E+12 | 0.315872E+11 | 720.00 | 0.104046E+12 | 0.880385E+09 | 0.00 | 0.74 | 18-JUN-18:31 | 0.39 | 09-JUN-06:10 | 57753.85 | 30-JUN-23:55 | 57532.54 | 30-JUN-24:00 | 3123.99 | 08-JUN-12:00 | 20848.92 | 28-JUN-16:00 | 0.00 |
July | 0.159759E+12 | 0.512948E+11 | 744.00 | 0.157648E+12 | 0.211192E+10 | 0.00 | 0.95 | 04-JUL-18:31 | 0.65 | 08-JUL-06:10 | 75820.97 | 31-JUL-24:00 | 75820.97 | 31-JUL-24:00 | 4533.42 | 07-JUL-17:00 | 28106.91 | 21-JUL-18:10 | 0.00 |
August | 0.206687E+12 | 0.634778E+11 | 744.00 | 0.204480E+12 | 0.220747E+10 | 0.00 | 1.00 | 01-AUG-12:40 | 0.29 | 31-AUG-24:00 | 82447.01 | 11-AUG-18:50 | 81728.50 | 30-AUG-18:20 | 4156.85 | 23-AUG-14:00 | 31290.30 | 20-AUG-16:00 | 0.00 |
September | 0.561411E+11 | 0.155281E+11 | 720.00 | 0.546986E+11 | 0.144258E+10 | 0.00 | 0.48 | 30-SEP-23:30 | 0.20 | 09-SEP-06:05 | 39223.54 | 30-SEP-23:30 | 38975.12 | 30-SEP-24:00 | 3190.81 | 05-SEP-16:30 | 11167.44 | 02-SEP-17:42 | 0.00 |
October | 0.989737E+11 | 0.244937E+11 | 744.00 | 0.983993E+11 | 0.574441E+09 | 0.00 | 0.67 | 31-OCT-24:00 | 0.32 | 26-OCT-06:10 | 54750.51 | 31-OCT-24:00 | 54750.51 | 31-OCT-24:00 | 3063.58 | 02-OCT-17:00 | 15904.61 | 01-OCT-16:01 | 0.00 |
November | 0.132910E+12 | 0.304135E+11 | 720.00 | 0.132781E+12 | 0.128841E+09 | 0.00 | 0.78 | 19-NOV-16:43 | 0.51 | 27-NOV-07:05 | 64833.84 | 02-NOV-16:40 | 63637.04 | 05-NOV-16:47 | 1749.36 | 09-NOV-16:10 | 14575.41 | 19-NOV-16:43 | 0.00 |
December | 0.176220E+12 | 0.399646E+11 | 744.00 | 0.176218E+12 | 1960977.45 | 0.00 | 0.94 | 31-DEC-16:42 | 0.69 | 27-DEC-07:10 | 79225.82 | 31-DEC-16:44 | 79225.82 | 31-DEC-16:44 | 259.80 | 26-DEC-17:05 | 17659.75 | 31-DEC-16:42 | 0.00 |
Annual Sum or Average | 0.142442E+13 | 0.375962E+12 | 8758.33 | 0.141657E+13 | 0.785117E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.280791E+11 | 0.744626E+10 | 672.00 | 0.280720E+11 | 1960977.45 | 0.00 | 0.34 | 0.00 | 25764.90 | 25764.90 | 259.80 | 6418.40 | 0.00 | ||||||
Maximum of Months | 0.206687E+12 | 0.634778E+11 | 744.00 | 0.204480E+12 | 0.220747E+10 | 0.00 | 1.00 | 0.69 | 85261.24 | 85261.24 | 4533.42 | 31290.30 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.120934E+10 | 0.331011E+09 | 463.65 | 0.120879E+10 | 550456.99 | 0.00 | 0.33 | 26-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2485.54 | 26-JAN-17:00 | 2485.54 | 26-JAN-17:00 | 26.60 | 01-JAN-16:22 | 622.30 | 26-JAN-17:00 | 0.00 |
February | 0.605081E+10 | 0.149390E+10 | 672.00 | 0.604799E+10 | 2819934.95 | 0.00 | 0.57 | 14-FEB-17:00 | 0.05 | 06-FEB-04:02 | 4615.49 | 15-FEB-17:00 | 4615.49 | 15-FEB-17:00 | 74.88 | 17-FEB-11:40 | 1234.10 | 14-FEB-17:00 | 0.00 |
March | 0.130809E+11 | 0.306167E+10 | 744.00 | 0.130754E+11 | 5506756.61 | 0.00 | 0.82 | 12-MAR-17:35 | 0.42 | 04-MAR-07:03 | 6845.25 | 31-MAR-23:10 | 6845.25 | 31-MAR-23:10 | 119.94 | 20-MAR-14:40 | 1772.78 | 12-MAR-17:01 | 0.00 |
April | 0.186582E+11 | 0.453480E+10 | 720.00 | 0.186572E+11 | 1081778.78 | 0.00 | 1.00 | 01-APR-16:13 | 0.28 | 30-APR-24:00 | 8674.82 | 16-APR-18:13 | 8674.82 | 16-APR-18:13 | 73.44 | 15-APR-08:30 | 2655.35 | 13-APR-17:00 | 0.00 |
May | 0.528056E+10 | 0.146665E+10 | 744.00 | 0.524079E+10 | 39766965.80 | 0.00 | 0.48 | 31-MAY-23:20 | 0.08 | 05-MAY-06:03 | 3839.22 | 31-MAY-23:50 | 3839.22 | 31-MAY-23:50 | 254.58 | 24-MAY-15:30 | 1121.31 | 20-MAY-18:10 | 0.00 |
June | 0.105334E+11 | 0.318818E+10 | 720.00 | 0.104455E+11 | 87957486.61 | 0.00 | 0.76 | 18-JUN-18:21 | 0.33 | 09-JUN-06:10 | 5775.65 | 30-JUN-23:55 | 5753.21 | 30-JUN-24:00 | 314.41 | 08-JUN-12:00 | 2145.08 | 28-JUN-16:00 | 0.00 |
July | 0.161242E+11 | 0.519195E+10 | 744.00 | 0.159131E+11 | 0.211133E+09 | 0.00 | 0.98 | 04-JUL-18:31 | 0.63 | 08-JUL-06:10 | 7649.16 | 04-JUL-18:35 | 7649.16 | 04-JUL-18:35 | 455.99 | 07-JUL-17:00 | 2964.44 | 04-JUL-18:01 | 0.00 |
August | 0.207702E+11 | 0.640098E+10 | 744.00 | 0.205494E+11 | 0.220795E+09 | 0.00 | 1.00 | 01-AUG-13:05 | 0.29 | 31-AUG-24:00 | 8379.37 | 11-AUG-18:40 | 8311.50 | 27-AUG-18:22 | 416.17 | 23-AUG-14:00 | 3196.51 | 20-AUG-16:00 | 0.00 |
September | 0.553402E+10 | 0.154332E+10 | 720.00 | 0.538983E+10 | 0.144189E+09 | 0.00 | 0.46 | 30-SEP-23:20 | 0.15 | 09-SEP-06:15 | 3885.85 | 30-SEP-23:20 | 3854.45 | 30-SEP-23:40 | 321.49 | 05-SEP-16:30 | 1171.06 | 02-SEP-17:42 | 0.00 |
October | 0.923069E+10 | 0.230947E+10 | 744.00 | 0.917342E+10 | 57274235.87 | 0.00 | 0.63 | 31-OCT-23:30 | 0.20 | 26-OCT-06:10 | 5262.76 | 31-OCT-23:30 | 5262.76 | 31-OCT-23:30 | 307.47 | 02-OCT-17:00 | 1665.84 | 01-OCT-16:01 | 0.00 |
November | 0.118498E+11 | 0.274841E+10 | 720.00 | 0.118371E+11 | 12746014.42 | 0.00 | 0.73 | 03-NOV-16:50 | 0.36 | 27-NOV-04:50 | 6489.22 | 02-NOV-16:40 | 6360.11 | 02-NOV-16:50 | 174.26 | 09-NOV-16:10 | 1404.89 | 02-NOV-16:40 | 0.00 |
December | 0.156214E+11 | 0.360161E+10 | 744.00 | 0.156213E+11 | 173000.58 | 0.00 | 0.88 | 13-DEC-16:40 | 0.52 | 26-DEC-04:03 | 7769.75 | 29-DEC-16:50 | 7769.75 | 29-DEC-16:50 | 24.67 | 27-DEC-17:05 | 1682.70 | 13-DEC-16:40 | 0.00 |
Annual Sum or Average | 0.133944E+12 | 0.358719E+11 | 8479.65 | 0.133160E+12 | 0.783994E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.120934E+10 | 0.331011E+09 | 463.65 | 0.120879E+10 | 173000.58 | 0.00 | 0.33 | 0.00 | 2485.54 | 2485.54 | 24.67 | 622.30 | 0.00 | ||||||
Maximum of Months | 0.207702E+11 | 0.640098E+10 | 744.00 | 0.205494E+11 | 0.220795E+09 | 0.00 | 1.00 | 0.63 | 8674.82 | 8674.82 | 455.99 | 3196.51 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 23.70 | 657.88 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 59.70 | 593.92 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 145.23 | 465.70 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 248.38 | 308.09 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 355.39 | 216.45 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 554.87 | 141.55 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 551.78 | 94.21 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 465.42 | 109.16 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 315.64 | 196.60 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 137.07 | 362.98 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 39.21 | 535.13 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.77 | 710.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 242.74 | 364.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.77 | 94.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 554.87 | 710.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 23.70 | 657.88 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 59.70 | 593.92 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 145.23 | 465.70 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 248.38 | 308.09 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 355.39 | 216.45 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 554.87 | 141.55 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 551.78 | 94.21 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 465.42 | 109.16 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 315.64 | 196.60 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 137.07 | 362.98 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 39.21 | 535.13 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.77 | 710.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 242.74 | 364.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.77 | 94.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 554.87 | 710.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 23.70 | 657.88 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 59.70 | 593.92 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 145.23 | 465.70 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 248.38 | 308.09 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 355.39 | 216.45 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 554.87 | 141.55 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 551.78 | 94.21 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 465.42 | 109.16 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 315.64 | 196.60 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 137.07 | 362.98 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 39.21 | 535.13 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.77 | 710.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 242.74 | 364.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.77 | 94.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 554.87 | 710.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 23.70 | 657.88 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 59.70 | 593.92 | 0.00 | 0.00 | 0.00 |
March | 251.66 | 0.00 | 251.66 | 145.23 | 465.70 | 0.00 | 0.00 | 0.00 |
April | 319.28 | 2.73 | 316.55 | 248.38 | 308.09 | 0.00 | 0.00 | 0.00 |
May | 347.06 | 22.38 | 324.68 | 355.39 | 216.45 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 64.54 | 329.82 | 554.87 | 141.55 | 0.00 | 0.00 | 0.00 |
July | 361.96 | 30.13 | 331.83 | 551.78 | 94.21 | 0.00 | 0.00 | 0.00 |
August | 335.77 | 7.52 | 328.26 | 465.42 | 109.16 | 0.00 | 0.00 | 0.00 |
September | 268.52 | 0.07 | 268.45 | 315.64 | 196.60 | 0.00 | 0.00 | 0.00 |
October | 200.37 | 0.00 | 200.37 | 137.07 | 362.98 | 0.00 | 0.00 | 0.00 |
November | 170.16 | 0.00 | 170.16 | 39.21 | 535.13 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.77 | 710.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.24 | 10.63 | 251.61 | 242.74 | 364.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.77 | 94.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.35 | 64.54 | 331.83 | 554.87 | 710.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.63 | 0.00 | 159.63 | 23.69 | 657.86 | 0.00 | 0.00 | 0.00 |
February | 199.51 | 0.00 | 199.51 | 59.69 | 593.90 | 0.00 | 0.00 | 0.00 |
March | 251.65 | 0.00 | 251.65 | 145.22 | 465.68 | 0.00 | 0.00 | 0.00 |
April | 319.27 | 2.73 | 316.53 | 248.37 | 308.07 | 0.00 | 0.00 | 0.00 |
May | 347.05 | 22.38 | 324.67 | 355.38 | 216.44 | 0.00 | 0.00 | 0.00 |
June | 394.34 | 64.53 | 329.81 | 554.85 | 141.55 | 0.00 | 0.00 | 0.00 |
July | 361.94 | 30.12 | 331.82 | 551.75 | 94.21 | 0.00 | 0.00 | 0.00 |
August | 335.76 | 7.52 | 328.24 | 465.41 | 109.15 | 0.00 | 0.00 | 0.00 |
September | 268.50 | 0.07 | 268.44 | 315.63 | 196.59 | 0.00 | 0.00 | 0.00 |
October | 200.36 | 0.00 | 200.36 | 137.06 | 362.97 | 0.00 | 0.00 | 0.00 |
November | 170.15 | 0.00 | 170.15 | 39.20 | 535.10 | 0.00 | 0.00 | 0.00 |
December | 135.87 | 0.00 | 135.87 | 4.77 | 710.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.23 | 10.63 | 251.60 | 242.73 | 364.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.87 | 0.00 | 135.87 | 4.77 | 94.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.34 | 64.53 | 331.82 | 554.85 | 710.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.21 | 274.63 | 216.58 | 404.66 | 666.39 | 0.00 | 0.00 | 0.00 |
February | 596.81 | 321.74 | 275.06 | 547.67 | 605.25 | 0.00 | 0.00 | 0.00 |
March | 787.28 | 447.55 | 339.72 | 834.10 | 474.76 | 0.00 | 0.00 | 0.00 |
April | 1075.58 | 612.75 | 462.83 | 1268.35 | 323.91 | 0.00 | 0.00 | 0.00 |
May | 1026.33 | 584.90 | 441.43 | 1285.44 | 244.83 | 0.00 | 0.00 | 0.00 |
June | 1106.46 | 681.63 | 424.83 | 1531.54 | 155.04 | 0.00 | 0.00 | 0.00 |
July | 1023.83 | 585.47 | 438.36 | 1480.03 | 102.37 | 0.00 | 0.00 | 0.00 |
August | 1013.15 | 558.57 | 454.58 | 1420.12 | 116.11 | 0.00 | 0.00 | 0.00 |
September | 843.28 | 471.82 | 371.46 | 1112.39 | 209.32 | 0.00 | 0.00 | 0.00 |
October | 733.39 | 465.31 | 268.08 | 842.49 | 371.29 | 0.00 | 0.00 | 0.00 |
November | 573.18 | 336.97 | 236.21 | 544.06 | 544.24 | 0.00 | 0.00 | 0.00 |
December | 464.44 | 282.65 | 181.79 | 390.10 | 711.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.04 | 469.25 | 342.79 | 973.67 | 376.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.44 | 274.63 | 181.79 | 390.10 | 102.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.46 | 681.63 | 462.83 | 1531.54 | 711.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.21 | 274.63 | 216.58 | 404.66 | 666.39 | 0.00 | 0.00 | 0.00 |
February | 596.81 | 321.74 | 275.06 | 547.67 | 605.25 | 0.00 | 0.00 | 0.00 |
March | 787.28 | 447.55 | 339.72 | 834.10 | 474.76 | 0.00 | 0.00 | 0.00 |
April | 1075.58 | 612.75 | 462.83 | 1268.35 | 323.91 | 0.00 | 0.00 | 0.00 |
May | 1026.33 | 584.90 | 441.43 | 1285.44 | 244.83 | 0.00 | 0.00 | 0.00 |
June | 1106.46 | 681.63 | 424.83 | 1531.54 | 155.04 | 0.00 | 0.00 | 0.00 |
July | 1023.83 | 585.47 | 438.36 | 1480.03 | 102.37 | 0.00 | 0.00 | 0.00 |
August | 1013.15 | 558.57 | 454.58 | 1420.12 | 116.11 | 0.00 | 0.00 | 0.00 |
September | 843.28 | 471.82 | 371.46 | 1112.39 | 209.32 | 0.00 | 0.00 | 0.00 |
October | 733.39 | 465.31 | 268.08 | 842.49 | 371.29 | 0.00 | 0.00 | 0.00 |
November | 573.18 | 336.97 | 236.21 | 544.06 | 544.24 | 0.00 | 0.00 | 0.00 |
December | 464.44 | 282.65 | 181.79 | 390.10 | 711.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.04 | 469.25 | 342.79 | 973.67 | 376.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.44 | 274.63 | 181.79 | 390.10 | 102.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.46 | 681.63 | 462.83 | 1531.54 | 711.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 491.20 | 274.63 | 216.57 | 404.66 | 666.38 | 0.00 | 0.00 | 0.00 |
February | 596.79 | 321.74 | 275.06 | 547.66 | 605.24 | 0.00 | 0.00 | 0.00 |
March | 787.26 | 447.54 | 339.72 | 834.08 | 474.75 | 0.00 | 0.00 | 0.00 |
April | 1075.56 | 612.74 | 462.82 | 1268.32 | 323.90 | 0.00 | 0.00 | 0.00 |
May | 1026.31 | 584.89 | 441.43 | 1285.41 | 244.83 | 0.00 | 0.00 | 0.00 |
June | 1106.44 | 681.62 | 424.82 | 1531.51 | 155.04 | 0.00 | 0.00 | 0.00 |
July | 1023.81 | 585.46 | 438.35 | 1480.01 | 102.37 | 0.00 | 0.00 | 0.00 |
August | 1013.13 | 558.56 | 454.57 | 1420.10 | 116.11 | 0.00 | 0.00 | 0.00 |
September | 843.26 | 471.81 | 371.45 | 1112.37 | 209.31 | 0.00 | 0.00 | 0.00 |
October | 733.38 | 465.30 | 268.08 | 842.47 | 371.28 | 0.00 | 0.00 | 0.00 |
November | 573.17 | 336.96 | 236.21 | 544.05 | 544.23 | 0.00 | 0.00 | 0.00 |
December | 464.43 | 282.65 | 181.78 | 390.09 | 711.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 812.02 | 469.24 | 342.78 | 973.65 | 375.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.43 | 274.63 | 181.78 | 390.09 | 102.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.44 | 681.62 | 462.82 | 1531.51 | 711.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1348.66 | 584.08 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1350.41 | 542.59 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1016.78 | 444.36 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.29 | 824.14 | 319.23 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 554.10 | 230.59 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 554.13 | 151.18 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 665.01 | 99.26 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 875.09 | 117.25 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1122.91 | 202.92 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.86 | 284.03 | 1379.10 | 343.20 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1415.65 | 481.39 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1046.62 | 342.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 554.10 | 99.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.29 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1348.65 | 584.08 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1350.41 | 542.59 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1016.78 | 444.36 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.28 | 824.14 | 319.23 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 554.10 | 230.59 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 554.13 | 151.18 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 665.01 | 99.26 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 875.09 | 117.25 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1122.91 | 202.92 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.85 | 284.03 | 1379.10 | 343.20 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1415.64 | 481.39 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1046.62 | 342.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 554.10 | 99.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.28 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1348.66 | 584.08 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1350.41 | 542.59 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1016.78 | 444.36 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.29 | 824.14 | 319.23 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 554.10 | 230.59 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 554.13 | 151.18 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 665.01 | 99.26 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 875.09 | 117.25 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1122.91 | 202.92 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.86 | 284.03 | 1379.10 | 343.20 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1415.65 | 481.39 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1046.62 | 342.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 554.10 | 99.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.29 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.17 | 918.33 | 261.83 | 1348.65 | 584.08 | 0.00 | 0.00 | 0.00 |
February | 1154.96 | 843.66 | 311.30 | 1350.41 | 542.59 | 0.00 | 0.00 | 0.00 |
March | 851.08 | 514.53 | 336.55 | 1016.78 | 444.36 | 0.00 | 0.00 | 0.00 |
April | 663.74 | 272.45 | 391.28 | 824.14 | 319.23 | 0.00 | 0.00 | 0.00 |
May | 442.66 | 97.38 | 345.28 | 554.10 | 230.59 | 0.00 | 0.00 | 0.00 |
June | 374.45 | 46.15 | 328.30 | 554.13 | 151.18 | 0.00 | 0.00 | 0.00 |
July | 414.35 | 66.17 | 348.18 | 665.01 | 99.26 | 0.00 | 0.00 | 0.00 |
August | 569.76 | 185.20 | 384.56 | 875.09 | 117.25 | 0.00 | 0.00 | 0.00 |
September | 787.86 | 439.33 | 348.52 | 1122.91 | 202.92 | 0.00 | 0.00 | 0.00 |
October | 1077.88 | 793.85 | 284.03 | 1379.10 | 343.20 | 0.00 | 0.00 | 0.00 |
November | 1200.56 | 921.42 | 279.13 | 1415.64 | 481.39 | 0.00 | 0.00 | 0.00 |
December | 1280.45 | 1056.24 | 224.21 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.35 | 511.19 | 320.16 | 1046.62 | 342.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.45 | 46.15 | 224.21 | 554.10 | 99.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.45 | 1056.24 | 391.28 | 1474.12 | 608.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1180.12 | 918.30 | 261.82 | 1348.60 | 584.06 | 0.00 | 0.00 | 0.00 |
February | 1154.91 | 843.62 | 311.29 | 1350.35 | 542.57 | 0.00 | 0.00 | 0.00 |
March | 851.05 | 514.51 | 336.54 | 1016.74 | 444.34 | 0.00 | 0.00 | 0.00 |
April | 663.71 | 272.44 | 391.27 | 824.11 | 319.22 | 0.00 | 0.00 | 0.00 |
May | 442.64 | 97.37 | 345.27 | 554.08 | 230.58 | 0.00 | 0.00 | 0.00 |
June | 374.44 | 46.15 | 328.29 | 554.11 | 151.17 | 0.00 | 0.00 | 0.00 |
July | 414.33 | 66.17 | 348.17 | 664.99 | 99.25 | 0.00 | 0.00 | 0.00 |
August | 569.74 | 185.19 | 384.54 | 875.05 | 117.24 | 0.00 | 0.00 | 0.00 |
September | 787.83 | 439.31 | 348.51 | 1122.87 | 202.92 | 0.00 | 0.00 | 0.00 |
October | 1077.84 | 793.82 | 284.02 | 1379.04 | 343.19 | 0.00 | 0.00 | 0.00 |
November | 1200.51 | 921.39 | 279.12 | 1415.59 | 481.37 | 0.00 | 0.00 | 0.00 |
December | 1280.40 | 1056.19 | 224.20 | 1474.06 | 608.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.32 | 511.17 | 320.15 | 1046.57 | 342.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 374.44 | 46.15 | 224.20 | 554.08 | 99.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1280.40 | 1056.19 | 391.27 | 1474.06 | 608.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.66 | 288.93 | 217.73 | 461.66 | 746.06 | 0.00 | 0.00 | 0.00 |
February | 652.24 | 376.78 | 275.46 | 643.31 | 693.24 | 0.00 | 0.00 | 0.00 |
March | 728.48 | 387.78 | 340.70 | 765.14 | 560.61 | 0.00 | 0.00 | 0.00 |
April | 929.76 | 494.82 | 434.94 | 1062.10 | 398.06 | 0.00 | 0.00 | 0.00 |
May | 881.55 | 454.23 | 427.31 | 1084.53 | 279.29 | 0.00 | 0.00 | 0.00 |
June | 945.02 | 527.31 | 417.71 | 1308.68 | 199.75 | 0.00 | 0.00 | 0.00 |
July | 852.37 | 417.14 | 435.23 | 1229.87 | 140.56 | 0.00 | 0.00 | 0.00 |
August | 870.98 | 402.86 | 468.11 | 1211.29 | 166.88 | 0.00 | 0.00 | 0.00 |
September | 786.70 | 414.32 | 372.37 | 1041.59 | 246.43 | 0.00 | 0.00 | 0.00 |
October | 719.72 | 447.33 | 272.39 | 840.85 | 439.60 | 0.00 | 0.00 | 0.00 |
November | 564.98 | 332.39 | 232.59 | 546.16 | 629.18 | 0.00 | 0.00 | 0.00 |
December | 488.59 | 306.40 | 182.19 | 433.93 | 825.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.99 | 404.00 | 339.99 | 886.61 | 442.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.59 | 288.93 | 182.19 | 433.93 | 140.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.02 | 527.31 | 468.11 | 1308.68 | 825.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.66 | 288.93 | 217.73 | 461.66 | 746.06 | 0.00 | 0.00 | 0.00 |
February | 652.24 | 376.78 | 275.46 | 643.31 | 693.24 | 0.00 | 0.00 | 0.00 |
March | 728.48 | 387.78 | 340.70 | 765.14 | 560.61 | 0.00 | 0.00 | 0.00 |
April | 929.76 | 494.82 | 434.94 | 1062.10 | 398.06 | 0.00 | 0.00 | 0.00 |
May | 881.55 | 454.23 | 427.31 | 1084.53 | 279.29 | 0.00 | 0.00 | 0.00 |
June | 945.02 | 527.31 | 417.71 | 1308.68 | 199.75 | 0.00 | 0.00 | 0.00 |
July | 852.37 | 417.14 | 435.23 | 1229.87 | 140.56 | 0.00 | 0.00 | 0.00 |
August | 870.98 | 402.86 | 468.11 | 1211.29 | 166.88 | 0.00 | 0.00 | 0.00 |
September | 786.70 | 414.32 | 372.37 | 1041.59 | 246.43 | 0.00 | 0.00 | 0.00 |
October | 719.72 | 447.33 | 272.39 | 840.85 | 439.60 | 0.00 | 0.00 | 0.00 |
November | 564.98 | 332.39 | 232.59 | 546.16 | 629.18 | 0.00 | 0.00 | 0.00 |
December | 488.59 | 306.40 | 182.19 | 433.93 | 825.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.99 | 404.00 | 339.99 | 886.61 | 442.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.59 | 288.93 | 182.19 | 433.93 | 140.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.02 | 527.31 | 468.11 | 1308.68 | 825.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.65 | 288.93 | 217.72 | 461.65 | 746.05 | 0.00 | 0.00 | 0.00 |
February | 652.23 | 376.77 | 275.46 | 643.30 | 693.23 | 0.00 | 0.00 | 0.00 |
March | 728.47 | 387.78 | 340.69 | 765.13 | 560.60 | 0.00 | 0.00 | 0.00 |
April | 929.74 | 494.81 | 434.93 | 1062.08 | 398.05 | 0.00 | 0.00 | 0.00 |
May | 881.53 | 454.23 | 427.30 | 1084.51 | 279.28 | 0.00 | 0.00 | 0.00 |
June | 945.00 | 527.30 | 417.70 | 1308.66 | 199.75 | 0.00 | 0.00 | 0.00 |
July | 852.36 | 417.13 | 435.23 | 1229.84 | 140.56 | 0.00 | 0.00 | 0.00 |
August | 870.96 | 402.85 | 468.11 | 1211.27 | 166.88 | 0.00 | 0.00 | 0.00 |
September | 786.68 | 414.31 | 372.37 | 1041.57 | 246.42 | 0.00 | 0.00 | 0.00 |
October | 719.71 | 447.32 | 272.38 | 840.84 | 439.59 | 0.00 | 0.00 | 0.00 |
November | 564.97 | 332.38 | 232.58 | 546.15 | 629.17 | 0.00 | 0.00 | 0.00 |
December | 488.58 | 306.39 | 182.19 | 433.92 | 825.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.97 | 403.99 | 339.98 | 886.60 | 442.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.58 | 288.93 | 182.19 | 433.92 | 140.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.00 | 527.30 | 468.11 | 1308.66 | 825.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 798.15 | 0.00 | 798.15 | 182.19 | 2968.52 | 0.00 | 0.00 | 0.00 |
February | 997.56 | 0.00 | 997.56 | 377.61 | 2686.09 | 0.00 | 0.00 | 0.00 |
March | 1258.29 | 0.00 | 1258.29 | 795.59 | 2125.29 | 0.00 | 0.00 | 0.00 |
April | 1596.38 | 13.67 | 1582.72 | 1295.28 | 1416.30 | 0.00 | 0.00 | 0.00 |
May | 1735.28 | 111.88 | 1623.40 | 1800.30 | 1032.43 | 0.00 | 0.00 | 0.00 |
June | 1971.75 | 322.67 | 1649.08 | 2791.08 | 686.34 | 0.00 | 0.00 | 0.00 |
July | 1809.76 | 150.63 | 1659.13 | 2775.61 | 463.08 | 0.00 | 0.00 | 0.00 |
August | 1678.85 | 37.59 | 1641.27 | 2352.16 | 523.28 | 0.00 | 0.00 | 0.00 |
September | 1342.56 | 0.34 | 1342.22 | 1597.78 | 933.01 | 0.00 | 0.00 | 0.00 |
October | 1001.82 | 0.00 | 1001.82 | 733.13 | 1661.22 | 0.00 | 0.00 | 0.00 |
November | 850.78 | 0.00 | 850.78 | 257.07 | 2370.58 | 0.00 | 0.00 | 0.00 |
December | 679.35 | 0.00 | 679.35 | 58.81 | 3109.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.19 | 53.16 | 1258.03 | 1256.00 | 1659.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 679.35 | 0.00 | 679.35 | 58.81 | 463.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1971.75 | 322.67 | 1659.13 | 2791.08 | 3109.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1473.60 | 823.88 | 649.72 | 1241.88 | 1862.12 | 0.00 | 0.00 | 0.00 |
February | 1790.40 | 965.22 | 825.18 | 1659.26 | 1705.34 | 0.00 | 0.00 | 0.00 |
March | 2361.81 | 1342.64 | 1019.16 | 2496.47 | 1360.87 | 0.00 | 0.00 | 0.00 |
April | 3226.71 | 1838.24 | 1388.47 | 3781.58 | 944.62 | 0.00 | 0.00 | 0.00 |
May | 3078.96 | 1754.68 | 1324.29 | 3826.83 | 719.32 | 0.00 | 0.00 | 0.00 |
June | 3319.36 | 2044.88 | 1274.47 | 4564.02 | 465.12 | 0.00 | 0.00 | 0.00 |
July | 3071.46 | 1756.39 | 1315.08 | 4409.04 | 322.00 | 0.00 | 0.00 | 0.00 |
August | 3039.42 | 1675.69 | 1363.73 | 4228.47 | 362.06 | 0.00 | 0.00 | 0.00 |
September | 2529.80 | 1415.45 | 1114.36 | 3314.77 | 615.81 | 0.00 | 0.00 | 0.00 |
October | 2200.15 | 1395.91 | 804.24 | 2517.61 | 1070.19 | 0.00 | 0.00 | 0.00 |
November | 1719.53 | 1010.90 | 708.63 | 1639.94 | 1532.64 | 0.00 | 0.00 | 0.00 |
December | 1393.31 | 847.95 | 545.35 | 1189.24 | 1971.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2436.09 | 1407.73 | 1028.36 | 2911.41 | 1074.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1393.31 | 823.88 | 545.35 | 1189.24 | 322.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3319.36 | 2044.88 | 1388.47 | 4564.02 | 1971.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5900.78 | 4591.62 | 1309.16 | 6700.50 | 2870.90 | 0.00 | 0.00 | 0.00 |
February | 5774.71 | 4218.23 | 1556.48 | 6710.54 | 2652.90 | 0.00 | 0.00 | 0.00 |
March | 4255.37 | 2572.63 | 1682.74 | 5058.77 | 2153.94 | 0.00 | 0.00 | 0.00 |
April | 3318.65 | 1362.24 | 1956.40 | 4109.63 | 1531.12 | 0.00 | 0.00 | 0.00 |
May | 2213.26 | 486.88 | 1726.39 | 2764.60 | 1117.79 | 0.00 | 0.00 | 0.00 |
June | 1872.23 | 230.73 | 1641.50 | 2783.93 | 731.89 | 0.00 | 0.00 | 0.00 |
July | 2071.72 | 330.83 | 1740.89 | 3332.05 | 489.73 | 0.00 | 0.00 | 0.00 |
August | 2848.77 | 926.00 | 1922.78 | 4371.41 | 572.67 | 0.00 | 0.00 | 0.00 |
September | 3939.24 | 2196.64 | 1742.60 | 5576.96 | 997.63 | 0.00 | 0.00 | 0.00 |
October | 5389.35 | 3969.23 | 1420.12 | 6847.91 | 1687.41 | 0.00 | 0.00 | 0.00 |
November | 6002.71 | 4607.07 | 1395.65 | 7038.06 | 2347.16 | 0.00 | 0.00 | 0.00 |
December | 6402.17 | 5281.12 | 1121.05 | 7337.93 | 2944.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4156.72 | 2555.94 | 1600.77 | 5210.85 | 1669.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1872.23 | 230.73 | 1121.05 | 2764.60 | 489.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6402.17 | 5281.12 | 1956.40 | 7337.93 | 2944.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1519.97 | 866.79 | 653.18 | 1427.77 | 2021.37 | 0.00 | 0.00 | 0.00 |
February | 1956.70 | 1130.33 | 826.37 | 1978.93 | 1856.71 | 0.00 | 0.00 | 0.00 |
March | 2185.42 | 1163.34 | 1022.08 | 2341.18 | 1493.32 | 0.00 | 0.00 | 0.00 |
April | 2789.25 | 1484.45 | 1304.80 | 3231.50 | 1050.45 | 0.00 | 0.00 | 0.00 |
May | 2644.61 | 1362.69 | 1281.92 | 3260.93 | 783.97 | 0.00 | 0.00 | 0.00 |
June | 2835.02 | 1581.91 | 1253.11 | 3946.36 | 548.14 | 0.00 | 0.00 | 0.00 |
July | 2557.10 | 1251.41 | 1305.69 | 3720.65 | 369.61 | 0.00 | 0.00 | 0.00 |
August | 2612.90 | 1208.57 | 1404.33 | 3676.57 | 422.46 | 0.00 | 0.00 | 0.00 |
September | 2360.06 | 1242.95 | 1117.11 | 3133.41 | 688.49 | 0.00 | 0.00 | 0.00 |
October | 2159.14 | 1341.98 | 817.15 | 2550.45 | 1188.00 | 0.00 | 0.00 | 0.00 |
November | 1694.91 | 997.16 | 697.76 | 1686.30 | 1638.17 | 0.00 | 0.00 | 0.00 |
December | 1465.76 | 919.19 | 546.57 | 1351.37 | 2088.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2231.94 | 1211.99 | 1019.95 | 2694.61 | 1175.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1465.76 | 866.79 | 546.57 | 1351.37 | 369.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2835.02 | 1581.91 | 1404.33 | 3946.36 | 2088.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 798.15 | 0.00 | 798.15 | 224.38 | 2751.80 | 0.00 | 0.00 | 0.00 |
February | 997.56 | 0.00 | 997.56 | 422.52 | 2507.26 | 0.00 | 0.00 | 0.00 |
March | 1258.29 | 0.00 | 1258.29 | 837.39 | 1996.28 | 0.00 | 0.00 | 0.00 |
April | 1596.38 | 13.67 | 1582.72 | 1315.13 | 1349.42 | 0.00 | 0.00 | 0.00 |
May | 1735.28 | 111.88 | 1623.40 | 1800.65 | 1007.47 | 0.00 | 0.00 | 0.00 |
June | 1971.75 | 322.67 | 1649.08 | 2773.53 | 682.85 | 0.00 | 0.00 | 0.00 |
July | 1809.76 | 150.63 | 1659.13 | 2749.15 | 470.27 | 0.00 | 0.00 | 0.00 |
August | 1678.85 | 37.59 | 1641.27 | 2330.17 | 526.40 | 0.00 | 0.00 | 0.00 |
September | 1342.56 | 0.34 | 1342.22 | 1590.18 | 913.44 | 0.00 | 0.00 | 0.00 |
October | 1001.82 | 0.00 | 1001.82 | 757.24 | 1560.52 | 0.00 | 0.00 | 0.00 |
November | 850.78 | 0.00 | 850.78 | 303.86 | 2169.20 | 0.00 | 0.00 | 0.00 |
December | 679.35 | 0.00 | 679.35 | 82.28 | 2868.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.19 | 53.16 | 1258.03 | 1269.95 | 1562.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 679.35 | 0.00 | 679.35 | 82.28 | 470.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1971.75 | 322.67 | 1659.13 | 2773.53 | 2868.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1473.60 | 823.88 | 649.72 | 1296.88 | 1721.28 | 0.00 | 0.00 | 0.00 |
February | 1790.40 | 965.22 | 825.18 | 1706.01 | 1590.66 | 0.00 | 0.00 | 0.00 |
March | 2361.81 | 1342.64 | 1019.16 | 2524.65 | 1288.30 | 0.00 | 0.00 | 0.00 |
April | 3226.71 | 1838.24 | 1388.47 | 3790.91 | 910.25 | 0.00 | 0.00 | 0.00 |
May | 3078.96 | 1754.68 | 1324.29 | 3824.46 | 703.68 | 0.00 | 0.00 | 0.00 |
June | 3319.36 | 2044.88 | 1274.47 | 4554.47 | 462.05 | 0.00 | 0.00 | 0.00 |
July | 3071.46 | 1756.39 | 1315.08 | 4395.42 | 325.54 | 0.00 | 0.00 | 0.00 |
August | 3039.42 | 1675.69 | 1363.73 | 4217.54 | 362.92 | 0.00 | 0.00 | 0.00 |
September | 2529.80 | 1415.45 | 1114.36 | 3312.20 | 605.01 | 0.00 | 0.00 | 0.00 |
October | 2200.15 | 1395.91 | 804.24 | 2535.24 | 1016.90 | 0.00 | 0.00 | 0.00 |
November | 1719.53 | 1010.90 | 708.63 | 1683.09 | 1410.46 | 0.00 | 0.00 | 0.00 |
December | 1393.31 | 847.95 | 545.35 | 1230.54 | 1803.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2436.09 | 1407.73 | 1028.36 | 2928.10 | 1013.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1393.31 | 823.88 | 545.35 | 1230.54 | 325.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3319.36 | 2044.88 | 1388.47 | 4554.47 | 1803.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5900.78 | 4591.62 | 1309.16 | 6768.07 | 2675.99 | 0.00 | 0.00 | 0.00 |
February | 5774.71 | 4218.23 | 1556.48 | 6759.15 | 2486.99 | 0.00 | 0.00 | 0.00 |
March | 4255.37 | 2572.63 | 1682.74 | 5088.49 | 2042.18 | 0.00 | 0.00 | 0.00 |
April | 3318.65 | 1362.24 | 1956.40 | 4115.52 | 1466.92 | 0.00 | 0.00 | 0.00 |
May | 2213.26 | 486.88 | 1726.39 | 2758.41 | 1088.44 | 0.00 | 0.00 | 0.00 |
June | 1872.23 | 230.73 | 1641.50 | 2765.32 | 725.27 | 0.00 | 0.00 | 0.00 |
July | 2071.72 | 330.83 | 1740.89 | 3304.72 | 496.30 | 0.00 | 0.00 | 0.00 |
August | 2848.77 | 926.00 | 1922.78 | 4346.44 | 574.43 | 0.00 | 0.00 | 0.00 |
September | 3939.24 | 2196.64 | 1742.60 | 5565.03 | 978.67 | 0.00 | 0.00 | 0.00 |
October | 5389.35 | 3969.23 | 1420.12 | 6871.07 | 1606.94 | 0.00 | 0.00 | 0.00 |
November | 6002.71 | 4607.07 | 1395.65 | 7095.80 | 2187.06 | 0.00 | 0.00 | 0.00 |
December | 6402.17 | 5281.12 | 1121.05 | 7395.26 | 2727.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4156.72 | 2555.94 | 1600.77 | 5227.43 | 1583.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1872.23 | 230.73 | 1121.05 | 2758.41 | 496.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6402.17 | 5281.12 | 1956.40 | 7395.26 | 2727.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1519.97 | 866.79 | 653.18 | 1455.49 | 1890.65 | 0.00 | 0.00 | 0.00 |
February | 1956.70 | 1130.33 | 826.37 | 2000.44 | 1751.21 | 0.00 | 0.00 | 0.00 |
March | 2185.42 | 1163.34 | 1022.08 | 2357.28 | 1419.42 | 0.00 | 0.00 | 0.00 |
April | 2789.25 | 1484.45 | 1304.80 | 3233.05 | 1009.65 | 0.00 | 0.00 | 0.00 |
May | 2644.61 | 1362.69 | 1281.92 | 3252.81 | 764.49 | 0.00 | 0.00 | 0.00 |
June | 2835.02 | 1581.91 | 1253.11 | 3931.24 | 542.33 | 0.00 | 0.00 | 0.00 |
July | 2557.10 | 1251.41 | 1305.69 | 3701.32 | 371.94 | 0.00 | 0.00 | 0.00 |
August | 2612.90 | 1208.57 | 1404.33 | 3659.50 | 422.37 | 0.00 | 0.00 | 0.00 |
September | 2360.06 | 1242.95 | 1117.11 | 3123.77 | 675.67 | 0.00 | 0.00 | 0.00 |
October | 2159.14 | 1341.98 | 817.15 | 2556.92 | 1131.13 | 0.00 | 0.00 | 0.00 |
November | 1694.91 | 997.16 | 697.76 | 1710.13 | 1525.73 | 0.00 | 0.00 | 0.00 |
December | 1465.76 | 919.19 | 546.57 | 1369.71 | 1947.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2231.94 | 1211.99 | 1019.95 | 2698.36 | 1117.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1465.76 | 866.79 | 546.57 | 1369.71 | 371.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2835.02 | 1581.91 | 1404.33 | 3931.24 | 1947.39 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427561E+09 | 0.00 | 0.427561E+09 | 63464970.60 | 0.176207E+10 |
February | 0.482665E+09 | 0.00 | 0.482665E+09 | 0.144417E+09 | 0.143682E+10 |
March | 0.674052E+09 | 0.00 | 0.674052E+09 | 0.388983E+09 | 0.124733E+10 |
April | 0.827576E+09 | 7085351.28 | 0.820490E+09 | 0.643810E+09 | 0.798557E+09 |
May | 0.929568E+09 | 59932262.51 | 0.869635E+09 | 0.951889E+09 | 0.579733E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.143822E+10 | 0.366905E+09 |
July | 0.969462E+09 | 80688364.77 | 0.888774E+09 | 0.147788E+10 | 0.252332E+09 |
August | 0.899338E+09 | 20134251.44 | 0.879204E+09 | 0.124659E+10 | 0.292365E+09 |
September | 0.695992E+09 | 178627.27 | 0.695814E+09 | 0.818134E+09 | 0.509581E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.367123E+09 | 0.972209E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.101620E+09 | 0.138705E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767942.24 | 0.190378E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335295E+09 | 0.793472E+10 | 0.765490E+10 | 0.115087E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767942.24 | 0.252332E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888774E+09 | 0.147788E+10 | 0.190378E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427560E+09 | 0.00 | 0.427560E+09 | 63464798.48 | 0.176207E+10 |
February | 0.482664E+09 | 0.00 | 0.482664E+09 | 0.144416E+09 | 0.143682E+10 |
March | 0.674051E+09 | 0.00 | 0.674051E+09 | 0.388983E+09 | 0.124733E+10 |
April | 0.827575E+09 | 7085342.78 | 0.820490E+09 | 0.643810E+09 | 0.798557E+09 |
May | 0.929567E+09 | 59932190.60 | 0.869635E+09 | 0.951889E+09 | 0.579733E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.143822E+10 | 0.366905E+09 |
July | 0.969462E+09 | 80688267.96 | 0.888773E+09 | 0.147788E+10 | 0.252332E+09 |
August | 0.899337E+09 | 20134227.28 | 0.879203E+09 | 0.124659E+10 | 0.292365E+09 |
September | 0.695992E+09 | 178627.05 | 0.695813E+09 | 0.818134E+09 | 0.509581E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.367123E+09 | 0.972209E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.101620E+09 | 0.138705E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767881.70 | 0.190378E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335294E+09 | 0.793471E+10 | 0.765489E+10 | 0.115087E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767881.70 | 0.252332E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888773E+09 | 0.147788E+10 | 0.190378E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427561E+09 | 0.00 | 0.427561E+09 | 63464970.60 | 0.176207E+10 |
February | 0.482665E+09 | 0.00 | 0.482665E+09 | 0.144417E+09 | 0.143682E+10 |
March | 0.674052E+09 | 0.00 | 0.674052E+09 | 0.388983E+09 | 0.124733E+10 |
April | 0.827576E+09 | 7085351.28 | 0.820490E+09 | 0.643810E+09 | 0.798557E+09 |
May | 0.929568E+09 | 59932262.51 | 0.869635E+09 | 0.951889E+09 | 0.579733E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.143822E+10 | 0.366905E+09 |
July | 0.969462E+09 | 80688364.77 | 0.888774E+09 | 0.147788E+10 | 0.252332E+09 |
August | 0.899338E+09 | 20134251.44 | 0.879204E+09 | 0.124659E+10 | 0.292365E+09 |
September | 0.695992E+09 | 178627.27 | 0.695814E+09 | 0.818134E+09 | 0.509581E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.367123E+09 | 0.972209E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.101620E+09 | 0.138705E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767942.24 | 0.190378E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335295E+09 | 0.793472E+10 | 0.765490E+10 | 0.115087E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767942.24 | 0.252332E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888774E+09 | 0.147788E+10 | 0.190378E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427560E+09 | 0.00 | 0.427560E+09 | 63464798.48 | 0.176207E+10 |
February | 0.482664E+09 | 0.00 | 0.482664E+09 | 0.144416E+09 | 0.143682E+10 |
March | 0.674051E+09 | 0.00 | 0.674051E+09 | 0.388983E+09 | 0.124733E+10 |
April | 0.827575E+09 | 7085342.78 | 0.820490E+09 | 0.643810E+09 | 0.798557E+09 |
May | 0.929567E+09 | 59932190.60 | 0.869635E+09 | 0.951889E+09 | 0.579733E+09 |
June | 0.102217E+10 | 0.167276E+09 | 0.854891E+09 | 0.143822E+10 | 0.366905E+09 |
July | 0.969462E+09 | 80688267.96 | 0.888773E+09 | 0.147788E+10 | 0.252332E+09 |
August | 0.899337E+09 | 20134227.28 | 0.879203E+09 | 0.124659E+10 | 0.292365E+09 |
September | 0.695992E+09 | 178627.05 | 0.695813E+09 | 0.818134E+09 | 0.509581E+09 |
October | 0.536661E+09 | 0.00 | 0.536661E+09 | 0.367123E+09 | 0.972209E+09 |
November | 0.441051E+09 | 0.00 | 0.441051E+09 | 0.101620E+09 | 0.138705E+10 |
December | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767881.70 | 0.190378E+10 |
Annual Sum or Average | 0.827001E+10 | 0.335294E+09 | 0.793471E+10 | 0.765489E+10 | 0.115087E+11 |
Minimum of Months | 0.363918E+09 | 0.00 | 0.363918E+09 | 12767881.70 | 0.252332E+09 |
Maximum of Months | 0.102217E+10 | 0.167276E+09 | 0.888773E+09 | 0.147788E+10 | 0.190378E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427544E+09 | 0.00 | 0.427544E+09 | 63462412.68 | 0.176200E+10 |
February | 0.482645E+09 | 0.00 | 0.482645E+09 | 0.144411E+09 | 0.143676E+10 |
March | 0.674024E+09 | 0.00 | 0.674024E+09 | 0.388968E+09 | 0.124728E+10 |
April | 0.827542E+09 | 7085065.71 | 0.820457E+09 | 0.643784E+09 | 0.798525E+09 |
May | 0.929530E+09 | 59929846.98 | 0.869600E+09 | 0.951851E+09 | 0.579709E+09 |
June | 0.102213E+10 | 0.167269E+09 | 0.854857E+09 | 0.143816E+10 | 0.366890E+09 |
July | 0.969423E+09 | 80685112.68 | 0.888738E+09 | 0.147782E+10 | 0.252322E+09 |
August | 0.899302E+09 | 20133439.94 | 0.879168E+09 | 0.124654E+10 | 0.292353E+09 |
September | 0.695964E+09 | 178620.07 | 0.695785E+09 | 0.818101E+09 | 0.509561E+09 |
October | 0.536639E+09 | 0.00 | 0.536639E+09 | 0.367108E+09 | 0.972170E+09 |
November | 0.441033E+09 | 0.00 | 0.441033E+09 | 0.101616E+09 | 0.138699E+10 |
December | 0.363904E+09 | 0.00 | 0.363904E+09 | 12767427.64 | 0.190371E+10 |
Annual Sum or Average | 0.826968E+10 | 0.335281E+09 | 0.793440E+10 | 0.765459E+10 | 0.115083E+11 |
Minimum of Months | 0.363904E+09 | 0.00 | 0.363904E+09 | 12767427.64 | 0.252322E+09 |
Maximum of Months | 0.102213E+10 | 0.167269E+09 | 0.888738E+09 | 0.147782E+10 | 0.190371E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131565E+10 | 0.735570E+09 | 0.580075E+09 | 0.108385E+10 | 0.178485E+10 |
February | 0.144379E+10 | 0.778359E+09 | 0.665433E+09 | 0.132491E+10 | 0.146423E+10 |
March | 0.210864E+10 | 0.119872E+10 | 0.909917E+09 | 0.223405E+10 | 0.127161E+10 |
April | 0.278790E+10 | 0.158825E+10 | 0.119965E+10 | 0.328756E+10 | 0.839565E+09 |
May | 0.274893E+10 | 0.156659E+10 | 0.118234E+10 | 0.344292E+10 | 0.655754E+09 |
June | 0.286795E+10 | 0.176680E+10 | 0.110116E+10 | 0.396974E+10 | 0.401864E+09 |
July | 0.274223E+10 | 0.156812E+10 | 0.117411E+10 | 0.396413E+10 | 0.274186E+09 |
August | 0.271362E+10 | 0.149607E+10 | 0.121755E+10 | 0.380366E+10 | 0.310984E+09 |
September | 0.218577E+10 | 0.122296E+10 | 0.962814E+09 | 0.288331E+10 | 0.542546E+09 |
October | 0.196432E+10 | 0.124628E+10 | 0.718034E+09 | 0.225652E+10 | 0.994455E+09 |
November | 0.148569E+10 | 0.873425E+09 | 0.612263E+09 | 0.141021E+10 | 0.141068E+10 |
December | 0.124396E+10 | 0.757062E+09 | 0.486895E+09 | 0.104484E+10 | 0.190674E+10 |
Annual Sum or Average | 0.256084E+11 | 0.147982E+11 | 0.108102E+11 | 0.307057E+11 | 0.118575E+11 |
Minimum of Months | 0.124396E+10 | 0.735570E+09 | 0.486895E+09 | 0.104484E+10 | 0.274186E+09 |
Maximum of Months | 0.286795E+10 | 0.176680E+10 | 0.121755E+10 | 0.396974E+10 | 0.190674E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131565E+10 | 0.735570E+09 | 0.580075E+09 | 0.108385E+10 | 0.178485E+10 |
February | 0.144379E+10 | 0.778359E+09 | 0.665433E+09 | 0.132491E+10 | 0.146423E+10 |
March | 0.210864E+10 | 0.119872E+10 | 0.909917E+09 | 0.223405E+10 | 0.127161E+10 |
April | 0.278790E+10 | 0.158825E+10 | 0.119965E+10 | 0.328756E+10 | 0.839565E+09 |
May | 0.274893E+10 | 0.156659E+10 | 0.118234E+10 | 0.344292E+10 | 0.655754E+09 |
June | 0.286795E+10 | 0.176680E+10 | 0.110116E+10 | 0.396974E+10 | 0.401864E+09 |
July | 0.274223E+10 | 0.156812E+10 | 0.117411E+10 | 0.396413E+10 | 0.274186E+09 |
August | 0.271362E+10 | 0.149607E+10 | 0.121755E+10 | 0.380366E+10 | 0.310984E+09 |
September | 0.218577E+10 | 0.122296E+10 | 0.962814E+09 | 0.288331E+10 | 0.542546E+09 |
October | 0.196432E+10 | 0.124628E+10 | 0.718034E+09 | 0.225652E+10 | 0.994455E+09 |
November | 0.148569E+10 | 0.873425E+09 | 0.612263E+09 | 0.141021E+10 | 0.141068E+10 |
December | 0.124396E+10 | 0.757062E+09 | 0.486895E+09 | 0.104484E+10 | 0.190674E+10 |
Annual Sum or Average | 0.256084E+11 | 0.147982E+11 | 0.108102E+11 | 0.307057E+11 | 0.118575E+11 |
Minimum of Months | 0.124396E+10 | 0.735570E+09 | 0.486895E+09 | 0.104484E+10 | 0.274186E+09 |
Maximum of Months | 0.286795E+10 | 0.176680E+10 | 0.121755E+10 | 0.396974E+10 | 0.190674E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.131562E+10 | 0.735557E+09 | 0.580065E+09 | 0.108383E+10 | 0.178482E+10 |
February | 0.144376E+10 | 0.778344E+09 | 0.665420E+09 | 0.132489E+10 | 0.146420E+10 |
March | 0.210860E+10 | 0.119870E+10 | 0.909901E+09 | 0.223401E+10 | 0.127158E+10 |
April | 0.278785E+10 | 0.158823E+10 | 0.119963E+10 | 0.328750E+10 | 0.839550E+09 |
May | 0.274888E+10 | 0.156656E+10 | 0.118231E+10 | 0.344285E+10 | 0.655742E+09 |
June | 0.286790E+10 | 0.176677E+10 | 0.110114E+10 | 0.396967E+10 | 0.401856E+09 |
July | 0.274218E+10 | 0.156809E+10 | 0.117409E+10 | 0.396405E+10 | 0.274181E+09 |
August | 0.271357E+10 | 0.149604E+10 | 0.121753E+10 | 0.380359E+10 | 0.310978E+09 |
September | 0.218573E+10 | 0.122294E+10 | 0.962797E+09 | 0.288326E+10 | 0.542536E+09 |
October | 0.196428E+10 | 0.124626E+10 | 0.718021E+09 | 0.225648E+10 | 0.994436E+09 |
November | 0.148566E+10 | 0.873410E+09 | 0.612252E+09 | 0.141019E+10 | 0.141065E+10 |
December | 0.124393E+10 | 0.757048E+09 | 0.486886E+09 | 0.104482E+10 | 0.190671E+10 |
Annual Sum or Average | 0.256080E+11 | 0.147979E+11 | 0.108100E+11 | 0.307051E+11 | 0.118572E+11 |
Minimum of Months | 0.124393E+10 | 0.735557E+09 | 0.486886E+09 | 0.104482E+10 | 0.274181E+09 |
Maximum of Months | 0.286790E+10 | 0.176677E+10 | 0.121753E+10 | 0.396967E+10 | 0.190671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316097E+10 | 0.245967E+10 | 0.701299E+09 | 0.361224E+10 | 0.156441E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753097E+09 | 0.326691E+10 | 0.131263E+10 |
March | 0.227955E+10 | 0.137812E+10 | 0.901420E+09 | 0.272336E+10 | 0.119017E+10 |
April | 0.172041E+10 | 0.706196E+09 | 0.101421E+10 | 0.213617E+10 | 0.827450E+09 |
May | 0.118562E+10 | 0.260814E+09 | 0.924802E+09 | 0.148411E+10 | 0.617617E+09 |
June | 0.970578E+09 | 0.119613E+09 | 0.850965E+09 | 0.143630E+10 | 0.391860E+09 |
July | 0.110979E+10 | 0.177224E+09 | 0.932569E+09 | 0.178117E+10 | 0.265852E+09 |
August | 0.152605E+10 | 0.496044E+09 | 0.103000E+10 | 0.234384E+10 | 0.314037E+09 |
September | 0.204213E+10 | 0.113875E+10 | 0.903376E+09 | 0.291059E+10 | 0.525980E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.369378E+10 | 0.919226E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723513E+09 | 0.366936E+10 | 0.124777E+10 |
December | 0.342956E+10 | 0.282903E+10 | 0.600531E+09 | 0.394828E+10 | 0.163067E+10 |
Annual Sum or Average | 0.262176E+11 | 0.161210E+11 | 0.100965E+11 | 0.330061E+11 | 0.108077E+11 |
Minimum of Months | 0.970578E+09 | 0.119613E+09 | 0.600531E+09 | 0.143630E+10 | 0.265852E+09 |
Maximum of Months | 0.342956E+10 | 0.282903E+10 | 0.103000E+10 | 0.394828E+10 | 0.163067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316096E+10 | 0.245967E+10 | 0.701298E+09 | 0.361224E+10 | 0.156441E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753096E+09 | 0.326690E+10 | 0.131263E+10 |
March | 0.227954E+10 | 0.137812E+10 | 0.901420E+09 | 0.272335E+10 | 0.119017E+10 |
April | 0.172041E+10 | 0.706195E+09 | 0.101421E+10 | 0.213616E+10 | 0.827450E+09 |
May | 0.118561E+10 | 0.260813E+09 | 0.924801E+09 | 0.148411E+10 | 0.617617E+09 |
June | 0.970577E+09 | 0.119613E+09 | 0.850964E+09 | 0.143630E+10 | 0.391860E+09 |
July | 0.110979E+10 | 0.177223E+09 | 0.932569E+09 | 0.178117E+10 | 0.265852E+09 |
August | 0.152605E+10 | 0.496043E+09 | 0.103000E+10 | 0.234384E+10 | 0.314037E+09 |
September | 0.204212E+10 | 0.113875E+10 | 0.903375E+09 | 0.291059E+10 | 0.525979E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.369378E+10 | 0.919226E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723512E+09 | 0.366935E+10 | 0.124777E+10 |
December | 0.342955E+10 | 0.282902E+10 | 0.600530E+09 | 0.394828E+10 | 0.163067E+10 |
Annual Sum or Average | 0.262175E+11 | 0.161210E+11 | 0.100965E+11 | 0.330061E+11 | 0.108077E+11 |
Minimum of Months | 0.970577E+09 | 0.119613E+09 | 0.600530E+09 | 0.143630E+10 | 0.265852E+09 |
Maximum of Months | 0.342955E+10 | 0.282902E+10 | 0.103000E+10 | 0.394828E+10 | 0.163067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316097E+10 | 0.245967E+10 | 0.701299E+09 | 0.361224E+10 | 0.156441E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753097E+09 | 0.326691E+10 | 0.131263E+10 |
March | 0.227955E+10 | 0.137812E+10 | 0.901420E+09 | 0.272336E+10 | 0.119017E+10 |
April | 0.172041E+10 | 0.706196E+09 | 0.101421E+10 | 0.213617E+10 | 0.827450E+09 |
May | 0.118562E+10 | 0.260814E+09 | 0.924802E+09 | 0.148411E+10 | 0.617617E+09 |
June | 0.970578E+09 | 0.119613E+09 | 0.850965E+09 | 0.143630E+10 | 0.391860E+09 |
July | 0.110979E+10 | 0.177224E+09 | 0.932569E+09 | 0.178117E+10 | 0.265852E+09 |
August | 0.152605E+10 | 0.496044E+09 | 0.103000E+10 | 0.234384E+10 | 0.314037E+09 |
September | 0.204213E+10 | 0.113875E+10 | 0.903376E+09 | 0.291059E+10 | 0.525980E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.369378E+10 | 0.919226E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723513E+09 | 0.366936E+10 | 0.124777E+10 |
December | 0.342956E+10 | 0.282903E+10 | 0.600531E+09 | 0.394828E+10 | 0.163067E+10 |
Annual Sum or Average | 0.262176E+11 | 0.161210E+11 | 0.100965E+11 | 0.330061E+11 | 0.108077E+11 |
Minimum of Months | 0.970578E+09 | 0.119613E+09 | 0.600531E+09 | 0.143630E+10 | 0.265852E+09 |
Maximum of Months | 0.342956E+10 | 0.282903E+10 | 0.103000E+10 | 0.394828E+10 | 0.163067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316096E+10 | 0.245967E+10 | 0.701298E+09 | 0.361224E+10 | 0.156441E+10 |
February | 0.279407E+10 | 0.204097E+10 | 0.753096E+09 | 0.326690E+10 | 0.131263E+10 |
March | 0.227954E+10 | 0.137812E+10 | 0.901420E+09 | 0.272335E+10 | 0.119017E+10 |
April | 0.172041E+10 | 0.706195E+09 | 0.101421E+10 | 0.213616E+10 | 0.827450E+09 |
May | 0.118561E+10 | 0.260813E+09 | 0.924801E+09 | 0.148411E+10 | 0.617617E+09 |
June | 0.970577E+09 | 0.119613E+09 | 0.850964E+09 | 0.143630E+10 | 0.391860E+09 |
July | 0.110979E+10 | 0.177223E+09 | 0.932569E+09 | 0.178117E+10 | 0.265852E+09 |
August | 0.152605E+10 | 0.496043E+09 | 0.103000E+10 | 0.234384E+10 | 0.314037E+09 |
September | 0.204212E+10 | 0.113875E+10 | 0.903375E+09 | 0.291059E+10 | 0.525979E+09 |
October | 0.288700E+10 | 0.212626E+10 | 0.760740E+09 | 0.369378E+10 | 0.919226E+09 |
November | 0.311184E+10 | 0.238833E+10 | 0.723512E+09 | 0.366935E+10 | 0.124777E+10 |
December | 0.342955E+10 | 0.282902E+10 | 0.600530E+09 | 0.394828E+10 | 0.163067E+10 |
Annual Sum or Average | 0.262175E+11 | 0.161210E+11 | 0.100965E+11 | 0.330061E+11 | 0.108077E+11 |
Minimum of Months | 0.970577E+09 | 0.119613E+09 | 0.600530E+09 | 0.143630E+10 | 0.265852E+09 |
Maximum of Months | 0.342955E+10 | 0.282902E+10 | 0.103000E+10 | 0.394828E+10 | 0.163067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316084E+10 | 0.245957E+10 | 0.701270E+09 | 0.361210E+10 | 0.156435E+10 |
February | 0.279396E+10 | 0.204089E+10 | 0.753067E+09 | 0.326677E+10 | 0.131258E+10 |
March | 0.227945E+10 | 0.137807E+10 | 0.901384E+09 | 0.272325E+10 | 0.119012E+10 |
April | 0.172034E+10 | 0.706167E+09 | 0.101417E+10 | 0.213608E+10 | 0.827417E+09 |
May | 0.118557E+10 | 0.260803E+09 | 0.924764E+09 | 0.148405E+10 | 0.617592E+09 |
June | 0.970539E+09 | 0.119608E+09 | 0.850930E+09 | 0.143625E+10 | 0.391844E+09 |
July | 0.110975E+10 | 0.177217E+09 | 0.932532E+09 | 0.178110E+10 | 0.265841E+09 |
August | 0.152599E+10 | 0.496024E+09 | 0.102996E+10 | 0.234374E+10 | 0.314024E+09 |
September | 0.204204E+10 | 0.113870E+10 | 0.903340E+09 | 0.291047E+10 | 0.525958E+09 |
October | 0.288689E+10 | 0.212618E+10 | 0.760710E+09 | 0.369363E+10 | 0.919189E+09 |
November | 0.311172E+10 | 0.238824E+10 | 0.723484E+09 | 0.366921E+10 | 0.124772E+10 |
December | 0.342942E+10 | 0.282891E+10 | 0.600507E+09 | 0.394812E+10 | 0.163060E+10 |
Annual Sum or Average | 0.262165E+11 | 0.161204E+11 | 0.100961E+11 | 0.330048E+11 | 0.108072E+11 |
Minimum of Months | 0.970539E+09 | 0.119608E+09 | 0.600507E+09 | 0.143625E+10 | 0.265841E+09 |
Maximum of Months | 0.342942E+10 | 0.282891E+10 | 0.102996E+10 | 0.394812E+10 | 0.163060E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135704E+10 | 0.773876E+09 | 0.583162E+09 | 0.123650E+10 | 0.199826E+10 |
February | 0.157790E+10 | 0.911508E+09 | 0.666395E+09 | 0.155630E+10 | 0.167709E+10 |
March | 0.195116E+10 | 0.103864E+10 | 0.912519E+09 | 0.204936E+10 | 0.150155E+10 |
April | 0.240993E+10 | 0.128258E+10 | 0.112736E+10 | 0.275295E+10 | 0.103176E+10 |
May | 0.236113E+10 | 0.121662E+10 | 0.114451E+10 | 0.290481E+10 | 0.748044E+09 |
June | 0.244948E+10 | 0.136678E+10 | 0.108270E+10 | 0.339210E+10 | 0.517752E+09 |
July | 0.228300E+10 | 0.111727E+10 | 0.116573E+10 | 0.329407E+10 | 0.376473E+09 |
August | 0.233282E+10 | 0.107903E+10 | 0.125380E+10 | 0.324432E+10 | 0.446968E+09 |
September | 0.203911E+10 | 0.107392E+10 | 0.965195E+09 | 0.269981E+10 | 0.638737E+09 |
October | 0.192770E+10 | 0.119813E+10 | 0.729563E+09 | 0.225214E+10 | 0.117742E+10 |
November | 0.146442E+10 | 0.861552E+09 | 0.602869E+09 | 0.141564E+10 | 0.163083E+10 |
December | 0.130864E+10 | 0.820657E+09 | 0.487983E+09 | 0.116224E+10 | 0.220976E+10 |
Annual Sum or Average | 0.234623E+11 | 0.127406E+11 | 0.107218E+11 | 0.279603E+11 | 0.139546E+11 |
Minimum of Months | 0.130864E+10 | 0.773876E+09 | 0.487983E+09 | 0.116224E+10 | 0.376473E+09 |
Maximum of Months | 0.244948E+10 | 0.136678E+10 | 0.125380E+10 | 0.339210E+10 | 0.220976E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135704E+10 | 0.773876E+09 | 0.583162E+09 | 0.123650E+10 | 0.199826E+10 |
February | 0.157790E+10 | 0.911508E+09 | 0.666395E+09 | 0.155630E+10 | 0.167709E+10 |
March | 0.195116E+10 | 0.103864E+10 | 0.912519E+09 | 0.204936E+10 | 0.150155E+10 |
April | 0.240993E+10 | 0.128258E+10 | 0.112736E+10 | 0.275295E+10 | 0.103176E+10 |
May | 0.236113E+10 | 0.121662E+10 | 0.114451E+10 | 0.290481E+10 | 0.748044E+09 |
June | 0.244948E+10 | 0.136678E+10 | 0.108270E+10 | 0.339210E+10 | 0.517752E+09 |
July | 0.228300E+10 | 0.111727E+10 | 0.116573E+10 | 0.329407E+10 | 0.376473E+09 |
August | 0.233282E+10 | 0.107903E+10 | 0.125380E+10 | 0.324432E+10 | 0.446968E+09 |
September | 0.203911E+10 | 0.107392E+10 | 0.965195E+09 | 0.269981E+10 | 0.638737E+09 |
October | 0.192770E+10 | 0.119813E+10 | 0.729563E+09 | 0.225214E+10 | 0.117742E+10 |
November | 0.146442E+10 | 0.861552E+09 | 0.602869E+09 | 0.141564E+10 | 0.163083E+10 |
December | 0.130864E+10 | 0.820657E+09 | 0.487983E+09 | 0.116224E+10 | 0.220976E+10 |
Annual Sum or Average | 0.234623E+11 | 0.127406E+11 | 0.107218E+11 | 0.279603E+11 | 0.139546E+11 |
Minimum of Months | 0.130864E+10 | 0.773876E+09 | 0.487983E+09 | 0.116224E+10 | 0.376473E+09 |
Maximum of Months | 0.244948E+10 | 0.136678E+10 | 0.125380E+10 | 0.339210E+10 | 0.220976E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135701E+10 | 0.773862E+09 | 0.583152E+09 | 0.123648E+10 | 0.199822E+10 |
February | 0.157787E+10 | 0.911491E+09 | 0.666383E+09 | 0.155627E+10 | 0.167706E+10 |
March | 0.195112E+10 | 0.103862E+10 | 0.912502E+09 | 0.204932E+10 | 0.150152E+10 |
April | 0.240989E+10 | 0.128256E+10 | 0.112733E+10 | 0.275290E+10 | 0.103174E+10 |
May | 0.236109E+10 | 0.121660E+10 | 0.114449E+10 | 0.290476E+10 | 0.748030E+09 |
June | 0.244944E+10 | 0.136676E+10 | 0.108268E+10 | 0.339204E+10 | 0.517743E+09 |
July | 0.228296E+10 | 0.111725E+10 | 0.116571E+10 | 0.329401E+10 | 0.376466E+09 |
August | 0.233278E+10 | 0.107901E+10 | 0.125377E+10 | 0.324426E+10 | 0.446960E+09 |
September | 0.203908E+10 | 0.107390E+10 | 0.965177E+09 | 0.269976E+10 | 0.638725E+09 |
October | 0.192766E+10 | 0.119811E+10 | 0.729550E+09 | 0.225210E+10 | 0.117740E+10 |
November | 0.146439E+10 | 0.861536E+09 | 0.602858E+09 | 0.141561E+10 | 0.163080E+10 |
December | 0.130862E+10 | 0.820642E+09 | 0.487974E+09 | 0.116222E+10 | 0.220972E+10 |
Annual Sum or Average | 0.234619E+11 | 0.127403E+11 | 0.107216E+11 | 0.279597E+11 | 0.139544E+11 |
Minimum of Months | 0.130862E+10 | 0.773862E+09 | 0.487974E+09 | 0.116222E+10 | 0.376466E+09 |
Maximum of Months | 0.244944E+10 | 0.136676E+10 | 0.125377E+10 | 0.339204E+10 | 0.220972E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.487976E+09 | 0.795089E+10 |
February | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.913511E+09 | 0.649818E+10 |
March | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.213091E+10 | 0.569239E+10 |
April | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.335736E+10 | 0.367105E+10 |
May | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.482193E+10 | 0.276527E+10 |
June | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.723447E+10 | 0.177898E+10 |
July | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.743419E+10 | 0.124032E+10 |
August | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.630001E+10 | 0.140156E+10 |
September | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.414146E+10 | 0.241837E+10 |
October | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.196362E+10 | 0.444942E+10 |
November | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.666314E+09 | 0.614455E+10 |
December | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.157528E+09 | 0.832914E+10 |
Annual Sum or Average | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.396093E+11 | 0.523401E+11 |
Minimum of Months | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.157528E+09 | 0.124032E+10 |
Maximum of Months | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.743419E+10 | 0.832914E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.332625E+10 | 0.498750E+10 |
February | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.401408E+10 | 0.412556E+10 |
March | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.668656E+10 | 0.364495E+10 |
April | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.980186E+10 | 0.244847E+10 |
May | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.102498E+11 | 0.192663E+10 |
June | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.118299E+11 | 0.120559E+10 |
July | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.118092E+11 | 0.862436E+09 |
August | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.113255E+11 | 0.969739E+09 |
September | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.859188E+10 | 0.159619E+10 |
October | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.674318E+10 | 0.286638E+10 |
November | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.425073E+10 | 0.397262E+10 |
December | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.318527E+10 | 0.528083E+10 |
Annual Sum or Average | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.918142E+11 | 0.338869E+11 |
Minimum of Months | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.318527E+10 | 0.862436E+09 |
Maximum of Months | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.118299E+11 | 0.528083E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.179466E+11 | 0.768941E+10 |
February | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.162341E+11 | 0.641791E+10 |
March | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.135494E+11 | 0.576912E+10 |
April | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.106522E+11 | 0.396867E+10 |
May | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.740471E+10 | 0.299389E+10 |
June | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.721595E+10 | 0.189706E+10 |
July | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.892456E+10 | 0.131169E+10 |
August | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.117084E+11 | 0.153385E+10 |
September | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.144555E+11 | 0.258585E+10 |
October | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.183415E+11 | 0.451956E+10 |
November | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.182427E+11 | 0.608383E+10 |
December | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.196539E+11 | 0.788787E+10 |
Annual Sum or Average | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.164329E+12 | 0.526587E+11 |
Minimum of Months | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.721595E+10 | 0.131169E+10 |
Maximum of Months | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.196539E+11 | 0.788787E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.382415E+10 | 0.541405E+10 |
February | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.478743E+10 | 0.449175E+10 |
March | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.627061E+10 | 0.399970E+10 |
April | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.837605E+10 | 0.272276E+10 |
May | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.873408E+10 | 0.209978E+10 |
June | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.102290E+11 | 0.142079E+10 |
July | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.996539E+10 | 0.989955E+09 |
August | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.984733E+10 | 0.113153E+10 |
September | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.812179E+10 | 0.178457E+10 |
October | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.683114E+10 | 0.318195E+10 |
November | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.437088E+10 | 0.424613E+10 |
December | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.361950E+10 | 0.559323E+10 |
Annual Sum or Average | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.849773E+11 | 0.370762E+11 |
Minimum of Months | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.361950E+10 | 0.989955E+09 |
Maximum of Months | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.102290E+11 | 0.559323E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.600975E+09 | 0.737041E+10 |
February | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.102215E+10 | 0.606557E+10 |
March | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.224285E+10 | 0.534684E+10 |
April | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.340882E+10 | 0.349770E+10 |
May | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.482287E+10 | 0.269842E+10 |
June | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.718900E+10 | 0.176995E+10 |
July | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.736332E+10 | 0.125958E+10 |
August | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.624112E+10 | 0.140992E+10 |
September | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.412174E+10 | 0.236765E+10 |
October | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.202818E+10 | 0.417969E+10 |
November | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.787592E+09 | 0.562258E+10 |
December | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.220377E+09 | 0.768406E+10 |
Annual Sum or Average | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.400490E+11 | 0.492724E+11 |
Minimum of Months | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.220377E+09 | 0.125958E+10 |
Maximum of Months | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.736332E+10 | 0.768406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.347357E+10 | 0.461027E+10 |
February | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.412717E+10 | 0.384813E+10 |
March | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.676203E+10 | 0.345057E+10 |
April | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.982604E+10 | 0.235937E+10 |
May | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.102434E+11 | 0.188475E+10 |
June | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.118052E+11 | 0.119764E+10 |
July | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.117727E+11 | 0.871939E+09 |
August | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.112963E+11 | 0.972032E+09 |
September | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.858523E+10 | 0.156820E+10 |
October | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.679039E+10 | 0.272368E+10 |
November | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.436258E+10 | 0.365591E+10 |
December | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.329587E+10 | 0.483176E+10 |
Annual Sum or Average | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.923405E+11 | 0.319743E+11 |
Minimum of Months | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.329587E+10 | 0.871939E+09 |
Maximum of Months | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.118052E+11 | 0.483176E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.181276E+11 | 0.716738E+10 |
February | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.163517E+11 | 0.601653E+10 |
March | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.136290E+11 | 0.546978E+10 |
April | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.106674E+11 | 0.380226E+10 |
May | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.738812E+10 | 0.291527E+10 |
June | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.716770E+10 | 0.187991E+10 |
July | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.885137E+10 | 0.132928E+10 |
August | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.116415E+11 | 0.153855E+10 |
September | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.144246E+11 | 0.253671E+10 |
October | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.184035E+11 | 0.430403E+10 |
November | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.183923E+11 | 0.566886E+10 |
December | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.198075E+11 | 0.730629E+10 |
Annual Sum or Average | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.164852E+12 | 0.499348E+11 |
Minimum of Months | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.716770E+10 | 0.132928E+10 |
Maximum of Months | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.198075E+11 | 0.730629E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.389840E+10 | 0.506392E+10 |
February | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.483947E+10 | 0.423653E+10 |
March | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.631373E+10 | 0.380178E+10 |
April | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.838005E+10 | 0.261702E+10 |
May | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.871233E+10 | 0.204761E+10 |
June | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.101898E+11 | 0.140573E+10 |
July | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.991362E+10 | 0.996192E+09 |
August | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.980161E+10 | 0.113127E+10 |
September | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.809681E+10 | 0.175135E+10 |
October | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.684845E+10 | 0.302961E+10 |
November | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.443267E+10 | 0.395469E+10 |
December | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.366863E+10 | 0.521590E+10 |
Annual Sum or Average | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.850955E+11 | 0.352516E+11 |
Minimum of Months | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.366863E+10 | 0.996192E+09 |
Maximum of Months | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.101898E+11 | 0.521590E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.47 | 3289.38 | 798.16 | 0.00 | 798.16 | 0.00 | 0.00 |
February | 298.48 | 2969.59 | 997.56 | 0.00 | 997.56 | 0.00 | 0.00 |
March | 726.14 | 2328.49 | 1258.30 | 0.00 | 1258.30 | 0.00 | 0.00 |
April | 1241.91 | 1540.41 | 1596.39 | 13.67 | 1582.72 | 0.00 | 0.00 |
May | 1776.96 | 1082.23 | 1735.29 | 111.88 | 1623.41 | 0.00 | 0.00 |
June | 2774.32 | 707.76 | 1971.76 | 322.67 | 1649.08 | 0.00 | 0.00 |
July | 2758.86 | 471.05 | 1809.76 | 150.63 | 1659.14 | 0.00 | 0.00 |
August | 2327.10 | 545.78 | 1678.86 | 37.59 | 1641.27 | 0.00 | 0.00 |
September | 1578.18 | 982.98 | 1342.57 | 0.34 | 1342.22 | 0.00 | 0.00 |
October | 685.33 | 1814.89 | 1001.82 | 0.00 | 1001.82 | 0.00 | 0.00 |
November | 196.03 | 2675.61 | 850.79 | 0.00 | 850.79 | 0.00 | 0.00 |
December | 23.83 | 3553.93 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Annual Sum or Average | 1213.67 | 1824.68 | 1311.19 | 53.16 | 1258.03 | 0.00 | 0.00 |
Minimum of Months | 23.83 | 471.05 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Maximum of Months | 2774.32 | 3553.93 | 1971.76 | 322.67 | 1659.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1213.98 | 1999.15 | 1473.61 | 823.89 | 649.72 | 0.00 | 0.00 |
February | 1642.99 | 1815.75 | 1790.40 | 965.22 | 825.18 | 0.00 | 0.00 |
March | 2502.28 | 1424.28 | 2361.82 | 1342.65 | 1019.17 | 0.00 | 0.00 |
April | 3805.02 | 971.71 | 3226.72 | 1838.25 | 1388.47 | 0.00 | 0.00 |
May | 3856.29 | 734.49 | 3078.98 | 1754.68 | 1324.29 | 0.00 | 0.00 |
June | 4594.58 | 465.12 | 3319.37 | 2044.89 | 1274.48 | 0.00 | 0.00 |
July | 4440.08 | 307.11 | 3071.47 | 1756.39 | 1315.08 | 0.00 | 0.00 |
August | 4260.34 | 348.32 | 3039.43 | 1675.70 | 1363.73 | 0.00 | 0.00 |
September | 3337.14 | 627.94 | 2529.82 | 1415.45 | 1114.36 | 0.00 | 0.00 |
October | 2527.45 | 1113.85 | 2200.16 | 1395.92 | 804.24 | 0.00 | 0.00 |
November | 1632.18 | 1632.72 | 1719.54 | 1010.90 | 708.63 | 0.00 | 0.00 |
December | 1170.29 | 2135.67 | 1393.31 | 847.96 | 545.35 | 0.00 | 0.00 |
Annual Sum or Average | 2921.00 | 1127.99 | 2436.10 | 1407.74 | 1028.36 | 0.00 | 0.00 |
Minimum of Months | 1170.29 | 307.11 | 1393.31 | 823.89 | 545.35 | 0.00 | 0.00 |
Maximum of Months | 4594.58 | 2135.67 | 3319.37 | 2044.89 | 1388.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6743.22 | 2920.39 | 5900.80 | 4591.64 | 1309.16 | 0.00 | 0.00 |
February | 6751.98 | 2712.92 | 5774.73 | 4218.25 | 1556.49 | 0.00 | 0.00 |
March | 5083.88 | 2221.78 | 4255.39 | 2572.64 | 1682.74 | 0.00 | 0.00 |
April | 4120.66 | 1596.15 | 3318.66 | 1362.25 | 1956.41 | 0.00 | 0.00 |
May | 2770.49 | 1152.95 | 2213.27 | 486.88 | 1726.39 | 0.00 | 0.00 |
June | 2770.62 | 755.90 | 1872.24 | 230.73 | 1641.51 | 0.00 | 0.00 |
July | 3325.03 | 496.28 | 2071.73 | 330.84 | 1740.89 | 0.00 | 0.00 |
August | 4375.41 | 586.23 | 2848.78 | 926.00 | 1922.78 | 0.00 | 0.00 |
September | 5614.51 | 1014.61 | 3939.25 | 2196.64 | 1742.61 | 0.00 | 0.00 |
October | 6895.44 | 1715.98 | 5389.37 | 3969.24 | 1420.13 | 0.00 | 0.00 |
November | 7078.17 | 2406.94 | 6002.74 | 4607.08 | 1395.65 | 0.00 | 0.00 |
December | 7370.53 | 3044.09 | 6402.19 | 5281.14 | 1121.05 | 0.00 | 0.00 |
Annual Sum or Average | 5233.04 | 1713.53 | 4156.73 | 2555.95 | 1600.78 | 0.00 | 0.00 |
Minimum of Months | 2770.49 | 496.28 | 1872.24 | 230.73 | 1121.05 | 0.00 | 0.00 |
Maximum of Months | 7370.53 | 3044.09 | 6402.19 | 5281.14 | 1956.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1384.96 | 2238.18 | 1519.97 | 866.79 | 653.18 | 0.00 | 0.00 |
February | 1929.92 | 2079.71 | 1956.71 | 1130.33 | 826.38 | 0.00 | 0.00 |
March | 2295.42 | 1681.83 | 2185.43 | 1163.35 | 1022.08 | 0.00 | 0.00 |
April | 3186.27 | 1194.16 | 2789.26 | 1484.46 | 1304.80 | 0.00 | 0.00 |
May | 3253.57 | 837.86 | 2644.62 | 1362.69 | 1281.93 | 0.00 | 0.00 |
June | 3926.02 | 599.25 | 2835.03 | 1581.92 | 1253.11 | 0.00 | 0.00 |
July | 3689.58 | 421.67 | 2557.11 | 1251.42 | 1305.69 | 0.00 | 0.00 |
August | 3633.85 | 500.63 | 2612.91 | 1208.58 | 1404.33 | 0.00 | 0.00 |
September | 3124.76 | 739.27 | 2360.07 | 1242.95 | 1117.12 | 0.00 | 0.00 |
October | 2522.54 | 1318.79 | 2159.15 | 1341.99 | 817.16 | 0.00 | 0.00 |
November | 1638.46 | 1887.52 | 1694.92 | 997.16 | 697.76 | 0.00 | 0.00 |
December | 1301.79 | 2475.08 | 1465.76 | 919.19 | 546.57 | 0.00 | 0.00 |
Annual Sum or Average | 2659.83 | 1327.49 | 2231.94 | 1211.99 | 1019.95 | 0.00 | 0.00 |
Minimum of Months | 1301.79 | 421.67 | 1465.76 | 866.79 | 546.57 | 0.00 | 0.00 |
Maximum of Months | 3926.02 | 2475.08 | 2835.03 | 1581.92 | 1404.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 182.19 | 2968.52 | 798.15 | 0.00 | 798.15 | 0.00 | 0.00 |
February | 377.61 | 2686.09 | 997.56 | 0.00 | 997.56 | 0.00 | 0.00 |
March | 795.59 | 2125.29 | 1258.29 | 0.00 | 1258.29 | 0.00 | 0.00 |
April | 1295.28 | 1416.30 | 1596.38 | 13.67 | 1582.72 | 0.00 | 0.00 |
May | 1800.30 | 1032.43 | 1735.28 | 111.88 | 1623.40 | 0.00 | 0.00 |
June | 2791.08 | 686.34 | 1971.75 | 322.67 | 1649.08 | 0.00 | 0.00 |
July | 2775.61 | 463.08 | 1809.76 | 150.63 | 1659.13 | 0.00 | 0.00 |
August | 2352.16 | 523.28 | 1678.85 | 37.59 | 1641.27 | 0.00 | 0.00 |
September | 1597.78 | 933.01 | 1342.56 | 0.34 | 1342.22 | 0.00 | 0.00 |
October | 733.13 | 1661.22 | 1001.82 | 0.00 | 1001.82 | 0.00 | 0.00 |
November | 257.07 | 2370.58 | 850.78 | 0.00 | 850.78 | 0.00 | 0.00 |
December | 58.81 | 3109.74 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Annual Sum or Average | 1256.00 | 1659.69 | 1311.19 | 53.16 | 1258.03 | 0.00 | 0.00 |
Minimum of Months | 58.81 | 463.08 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Maximum of Months | 2791.08 | 3109.74 | 1971.75 | 322.67 | 1659.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1241.88 | 1862.12 | 1473.60 | 823.88 | 649.72 | 0.00 | 0.00 |
February | 1659.26 | 1705.34 | 1790.40 | 965.22 | 825.18 | 0.00 | 0.00 |
March | 2496.47 | 1360.87 | 2361.81 | 1342.64 | 1019.16 | 0.00 | 0.00 |
April | 3781.58 | 944.62 | 3226.71 | 1838.24 | 1388.47 | 0.00 | 0.00 |
May | 3826.83 | 719.32 | 3078.96 | 1754.68 | 1324.29 | 0.00 | 0.00 |
June | 4564.02 | 465.12 | 3319.36 | 2044.88 | 1274.47 | 0.00 | 0.00 |
July | 4409.04 | 322.00 | 3071.46 | 1756.39 | 1315.08 | 0.00 | 0.00 |
August | 4228.47 | 362.06 | 3039.42 | 1675.69 | 1363.73 | 0.00 | 0.00 |
September | 3314.77 | 615.81 | 2529.80 | 1415.45 | 1114.36 | 0.00 | 0.00 |
October | 2517.61 | 1070.19 | 2200.15 | 1395.91 | 804.24 | 0.00 | 0.00 |
November | 1639.94 | 1532.64 | 1719.53 | 1010.90 | 708.63 | 0.00 | 0.00 |
December | 1189.24 | 1971.64 | 1393.31 | 847.95 | 545.35 | 0.00 | 0.00 |
Annual Sum or Average | 2911.41 | 1074.55 | 2436.09 | 1407.73 | 1028.36 | 0.00 | 0.00 |
Minimum of Months | 1189.24 | 322.00 | 1393.31 | 823.88 | 545.35 | 0.00 | 0.00 |
Maximum of Months | 4564.02 | 1971.64 | 3319.36 | 2044.88 | 1388.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6700.50 | 2870.90 | 5900.78 | 4591.62 | 1309.16 | 0.00 | 0.00 |
February | 6710.54 | 2652.90 | 5774.71 | 4218.23 | 1556.48 | 0.00 | 0.00 |
March | 5058.77 | 2153.94 | 4255.37 | 2572.63 | 1682.74 | 0.00 | 0.00 |
April | 4109.63 | 1531.12 | 3318.65 | 1362.24 | 1956.40 | 0.00 | 0.00 |
May | 2764.60 | 1117.79 | 2213.26 | 486.88 | 1726.39 | 0.00 | 0.00 |
June | 2783.93 | 731.89 | 1872.23 | 230.73 | 1641.50 | 0.00 | 0.00 |
July | 3332.05 | 489.73 | 2071.72 | 330.83 | 1740.89 | 0.00 | 0.00 |
August | 4371.41 | 572.67 | 2848.77 | 926.00 | 1922.78 | 0.00 | 0.00 |
September | 5576.96 | 997.63 | 3939.24 | 2196.64 | 1742.60 | 0.00 | 0.00 |
October | 6847.91 | 1687.41 | 5389.35 | 3969.23 | 1420.12 | 0.00 | 0.00 |
November | 7038.06 | 2347.16 | 6002.71 | 4607.07 | 1395.65 | 0.00 | 0.00 |
December | 7337.93 | 2944.99 | 6402.17 | 5281.12 | 1121.05 | 0.00 | 0.00 |
Annual Sum or Average | 5210.85 | 1669.80 | 4156.72 | 2555.94 | 1600.77 | 0.00 | 0.00 |
Minimum of Months | 2764.60 | 489.73 | 1872.23 | 230.73 | 1121.05 | 0.00 | 0.00 |
Maximum of Months | 7337.93 | 2944.99 | 6402.17 | 5281.12 | 1956.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1427.77 | 2021.37 | 1519.97 | 866.79 | 653.18 | 0.00 | 0.00 |
February | 1978.93 | 1856.71 | 1956.70 | 1130.33 | 826.37 | 0.00 | 0.00 |
March | 2341.18 | 1493.32 | 2185.42 | 1163.34 | 1022.08 | 0.00 | 0.00 |
April | 3231.50 | 1050.45 | 2789.25 | 1484.45 | 1304.80 | 0.00 | 0.00 |
May | 3260.93 | 783.97 | 2644.61 | 1362.69 | 1281.92 | 0.00 | 0.00 |
June | 3946.36 | 548.14 | 2835.02 | 1581.91 | 1253.11 | 0.00 | 0.00 |
July | 3720.65 | 369.61 | 2557.10 | 1251.41 | 1305.69 | 0.00 | 0.00 |
August | 3676.57 | 422.46 | 2612.90 | 1208.57 | 1404.33 | 0.00 | 0.00 |
September | 3133.41 | 688.49 | 2360.06 | 1242.95 | 1117.11 | 0.00 | 0.00 |
October | 2550.45 | 1188.00 | 2159.14 | 1341.98 | 817.15 | 0.00 | 0.00 |
November | 1686.30 | 1638.17 | 1694.91 | 997.16 | 697.76 | 0.00 | 0.00 |
December | 1351.37 | 2088.27 | 1465.76 | 919.19 | 546.57 | 0.00 | 0.00 |
Annual Sum or Average | 2694.61 | 1175.68 | 2231.94 | 1211.99 | 1019.95 | 0.00 | 0.00 |
Minimum of Months | 1351.37 | 369.61 | 1465.76 | 866.79 | 546.57 | 0.00 | 0.00 |
Maximum of Months | 3946.36 | 2088.27 | 2835.02 | 1581.91 | 1404.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.38 | 2751.80 | 798.15 | 0.00 | 798.15 | 0.00 | 0.00 |
February | 422.52 | 2507.26 | 997.56 | 0.00 | 997.56 | 0.00 | 0.00 |
March | 837.39 | 1996.28 | 1258.29 | 0.00 | 1258.29 | 0.00 | 0.00 |
April | 1315.13 | 1349.42 | 1596.38 | 13.67 | 1582.72 | 0.00 | 0.00 |
May | 1800.65 | 1007.47 | 1735.28 | 111.88 | 1623.40 | 0.00 | 0.00 |
June | 2773.53 | 682.85 | 1971.75 | 322.67 | 1649.08 | 0.00 | 0.00 |
July | 2749.15 | 470.27 | 1809.76 | 150.63 | 1659.13 | 0.00 | 0.00 |
August | 2330.17 | 526.40 | 1678.85 | 37.59 | 1641.27 | 0.00 | 0.00 |
September | 1590.18 | 913.44 | 1342.56 | 0.34 | 1342.22 | 0.00 | 0.00 |
October | 757.24 | 1560.52 | 1001.82 | 0.00 | 1001.82 | 0.00 | 0.00 |
November | 303.86 | 2169.20 | 850.78 | 0.00 | 850.78 | 0.00 | 0.00 |
December | 82.28 | 2868.90 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Annual Sum or Average | 1269.95 | 1562.42 | 1311.19 | 53.16 | 1258.03 | 0.00 | 0.00 |
Minimum of Months | 82.28 | 470.27 | 679.35 | 0.00 | 679.35 | 0.00 | 0.00 |
Maximum of Months | 2773.53 | 2868.90 | 1971.75 | 322.67 | 1659.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1296.88 | 1721.28 | 1473.60 | 823.88 | 649.72 | 0.00 | 0.00 |
February | 1706.01 | 1590.66 | 1790.40 | 965.22 | 825.18 | 0.00 | 0.00 |
March | 2524.65 | 1288.30 | 2361.81 | 1342.64 | 1019.16 | 0.00 | 0.00 |
April | 3790.91 | 910.25 | 3226.71 | 1838.24 | 1388.47 | 0.00 | 0.00 |
May | 3824.46 | 703.68 | 3078.96 | 1754.68 | 1324.29 | 0.00 | 0.00 |
June | 4554.47 | 462.05 | 3319.36 | 2044.88 | 1274.47 | 0.00 | 0.00 |
July | 4395.42 | 325.54 | 3071.46 | 1756.39 | 1315.08 | 0.00 | 0.00 |
August | 4217.54 | 362.92 | 3039.42 | 1675.69 | 1363.73 | 0.00 | 0.00 |
September | 3312.20 | 605.01 | 2529.80 | 1415.45 | 1114.36 | 0.00 | 0.00 |
October | 2535.24 | 1016.90 | 2200.15 | 1395.91 | 804.24 | 0.00 | 0.00 |
November | 1683.09 | 1410.46 | 1719.53 | 1010.90 | 708.63 | 0.00 | 0.00 |
December | 1230.54 | 1803.97 | 1393.31 | 847.95 | 545.35 | 0.00 | 0.00 |
Annual Sum or Average | 2928.10 | 1013.90 | 2436.09 | 1407.73 | 1028.36 | 0.00 | 0.00 |
Minimum of Months | 1230.54 | 325.54 | 1393.31 | 823.88 | 545.35 | 0.00 | 0.00 |
Maximum of Months | 4554.47 | 1803.97 | 3319.36 | 2044.88 | 1388.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6768.07 | 2675.99 | 5900.78 | 4591.62 | 1309.16 | 0.00 | 0.00 |
February | 6759.15 | 2486.99 | 5774.71 | 4218.23 | 1556.48 | 0.00 | 0.00 |
March | 5088.49 | 2042.18 | 4255.37 | 2572.63 | 1682.74 | 0.00 | 0.00 |
April | 4115.52 | 1466.92 | 3318.65 | 1362.24 | 1956.40 | 0.00 | 0.00 |
May | 2758.41 | 1088.44 | 2213.26 | 486.88 | 1726.39 | 0.00 | 0.00 |
June | 2765.32 | 725.27 | 1872.23 | 230.73 | 1641.50 | 0.00 | 0.00 |
July | 3304.72 | 496.30 | 2071.72 | 330.83 | 1740.89 | 0.00 | 0.00 |
August | 4346.44 | 574.43 | 2848.77 | 926.00 | 1922.78 | 0.00 | 0.00 |
September | 5565.03 | 978.67 | 3939.24 | 2196.64 | 1742.60 | 0.00 | 0.00 |
October | 6871.07 | 1606.94 | 5389.35 | 3969.23 | 1420.12 | 0.00 | 0.00 |
November | 7095.80 | 2187.06 | 6002.71 | 4607.07 | 1395.65 | 0.00 | 0.00 |
December | 7395.26 | 2727.86 | 6402.17 | 5281.12 | 1121.05 | 0.00 | 0.00 |
Annual Sum or Average | 5227.43 | 1583.42 | 4156.72 | 2555.94 | 1600.77 | 0.00 | 0.00 |
Minimum of Months | 2758.41 | 496.30 | 1872.23 | 230.73 | 1121.05 | 0.00 | 0.00 |
Maximum of Months | 7395.26 | 2727.86 | 6402.17 | 5281.12 | 1956.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1455.49 | 1890.65 | 1519.97 | 866.79 | 653.18 | 0.00 | 0.00 |
February | 2000.44 | 1751.21 | 1956.70 | 1130.33 | 826.37 | 0.00 | 0.00 |
March | 2357.28 | 1419.42 | 2185.42 | 1163.34 | 1022.08 | 0.00 | 0.00 |
April | 3233.05 | 1009.65 | 2789.25 | 1484.45 | 1304.80 | 0.00 | 0.00 |
May | 3252.81 | 764.49 | 2644.61 | 1362.69 | 1281.92 | 0.00 | 0.00 |
June | 3931.24 | 542.33 | 2835.02 | 1581.91 | 1253.11 | 0.00 | 0.00 |
July | 3701.32 | 371.94 | 2557.10 | 1251.41 | 1305.69 | 0.00 | 0.00 |
August | 3659.50 | 422.37 | 2612.90 | 1208.57 | 1404.33 | 0.00 | 0.00 |
September | 3123.77 | 675.67 | 2360.06 | 1242.95 | 1117.11 | 0.00 | 0.00 |
October | 2556.92 | 1131.13 | 2159.14 | 1341.98 | 817.15 | 0.00 | 0.00 |
November | 1710.13 | 1525.73 | 1694.91 | 997.16 | 697.76 | 0.00 | 0.00 |
December | 1369.71 | 1947.39 | 1465.76 | 919.19 | 546.57 | 0.00 | 0.00 |
Annual Sum or Average | 2698.36 | 1117.82 | 2231.94 | 1211.99 | 1019.95 | 0.00 | 0.00 |
Minimum of Months | 1369.71 | 371.94 | 1465.76 | 866.79 | 546.57 | 0.00 | 0.00 |
Maximum of Months | 3931.24 | 1947.39 | 2835.02 | 1581.91 | 1404.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.317322E+09 | 0.881028E+10 | 0.213779E+10 | 0.00 | 0.213779E+10 | 0.00 | 0.00 |
February | 0.722077E+09 | 0.718404E+10 | 0.241330E+10 | 0.00 | 0.241330E+10 | 0.00 | 0.00 |
March | 0.194490E+10 | 0.623662E+10 | 0.337023E+10 | 0.00 | 0.337023E+10 | 0.00 | 0.00 |
April | 0.321902E+10 | 0.399275E+10 | 0.413784E+10 | 35426453.82 | 0.410242E+10 | 0.00 | 0.00 |
May | 0.475941E+10 | 0.289864E+10 | 0.464780E+10 | 0.299659E+09 | 0.434814E+10 | 0.00 | 0.00 |
June | 0.719103E+10 | 0.183451E+10 | 0.511079E+10 | 0.836372E+09 | 0.427442E+10 | 0.00 | 0.00 |
July | 0.738933E+10 | 0.126165E+10 | 0.484727E+10 | 0.403438E+09 | 0.444383E+10 | 0.00 | 0.00 |
August | 0.623291E+10 | 0.146181E+10 | 0.449665E+10 | 0.100670E+09 | 0.439598E+10 | 0.00 | 0.00 |
September | 0.409064E+10 | 0.254789E+10 | 0.347993E+10 | 893128.72 | 0.347904E+10 | 0.00 | 0.00 |
October | 0.183560E+10 | 0.486101E+10 | 0.268328E+10 | 0.00 | 0.268328E+10 | 0.00 | 0.00 |
November | 0.508097E+09 | 0.693517E+10 | 0.220524E+10 | 0.00 | 0.220524E+10 | 0.00 | 0.00 |
December | 63839075.51 | 0.951884E+10 | 0.181958E+10 | 0.00 | 0.181958E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.382742E+11 | 0.575432E+11 | 0.413497E+11 | 0.167646E+10 | 0.396733E+11 | 0.00 | 0.00 |
Minimum of Months | 63839075.51 | 0.126165E+10 | 0.181958E+10 | 0.00 | 0.181958E+10 | 0.00 | 0.00 |
Maximum of Months | 0.738933E+10 | 0.951884E+10 | 0.511079E+10 | 0.836372E+09 | 0.444383E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325154E+10 | 0.535453E+10 | 0.394691E+10 | 0.220670E+10 | 0.174021E+10 | 0.00 | 0.00 |
February | 0.397471E+10 | 0.439266E+10 | 0.433135E+10 | 0.233506E+10 | 0.199629E+10 | 0.00 | 0.00 |
March | 0.670212E+10 | 0.381479E+10 | 0.632589E+10 | 0.359615E+10 | 0.272973E+10 | 0.00 | 0.00 |
April | 0.986261E+10 | 0.251868E+10 | 0.836366E+10 | 0.476474E+10 | 0.359893E+10 | 0.00 | 0.00 |
May | 0.103287E+11 | 0.196725E+10 | 0.824673E+10 | 0.469974E+10 | 0.354699E+10 | 0.00 | 0.00 |
June | 0.119092E+11 | 0.120558E+10 | 0.860381E+10 | 0.530036E+10 | 0.330345E+10 | 0.00 | 0.00 |
July | 0.118923E+11 | 0.822553E+09 | 0.822664E+10 | 0.470432E+10 | 0.352231E+10 | 0.00 | 0.00 |
August | 0.114109E+11 | 0.932945E+09 | 0.814081E+10 | 0.448818E+10 | 0.365263E+10 | 0.00 | 0.00 |
September | 0.864988E+10 | 0.162763E+10 | 0.655728E+10 | 0.366886E+10 | 0.288842E+10 | 0.00 | 0.00 |
October | 0.676952E+10 | 0.298335E+10 | 0.589291E+10 | 0.373882E+10 | 0.215409E+10 | 0.00 | 0.00 |
November | 0.423061E+10 | 0.423202E+10 | 0.445704E+10 | 0.262026E+10 | 0.183678E+10 | 0.00 | 0.00 |
December | 0.313449E+10 | 0.572019E+10 | 0.373185E+10 | 0.227117E+10 | 0.146068E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.921165E+11 | 0.355722E+11 | 0.768249E+11 | 0.443944E+11 | 0.324305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.313449E+10 | 0.822553E+09 | 0.373185E+10 | 0.220670E+10 | 0.146068E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119092E+11 | 0.572019E+10 | 0.860381E+10 | 0.530036E+10 | 0.365263E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180611E+11 | 0.782199E+10 | 0.158047E+11 | 0.122982E+11 | 0.350646E+10 | 0.00 | 0.00 |
February | 0.163344E+11 | 0.656311E+10 | 0.139702E+11 | 0.102048E+11 | 0.376545E+10 | 0.00 | 0.00 |
March | 0.136167E+11 | 0.595082E+10 | 0.113976E+11 | 0.689057E+10 | 0.450706E+10 | 0.00 | 0.00 |
April | 0.106807E+11 | 0.413722E+10 | 0.860196E+10 | 0.353095E+10 | 0.507101E+10 | 0.00 | 0.00 |
May | 0.742047E+10 | 0.308806E+10 | 0.592803E+10 | 0.130406E+10 | 0.462397E+10 | 0.00 | 0.00 |
June | 0.718146E+10 | 0.195928E+10 | 0.485285E+10 | 0.598061E+09 | 0.425479E+10 | 0.00 | 0.00 |
July | 0.890577E+10 | 0.132925E+10 | 0.554892E+10 | 0.886111E+09 | 0.466281E+10 | 0.00 | 0.00 |
August | 0.117191E+11 | 0.157017E+10 | 0.763018E+10 | 0.248020E+10 | 0.514998E+10 | 0.00 | 0.00 |
September | 0.145528E+11 | 0.262988E+10 | 0.102105E+11 | 0.569370E+10 | 0.451684E+10 | 0.00 | 0.00 |
October | 0.184688E+11 | 0.459609E+10 | 0.144349E+11 | 0.106312E+11 | 0.380367E+10 | 0.00 | 0.00 |
November | 0.183466E+11 | 0.623878E+10 | 0.155591E+11 | 0.119416E+11 | 0.361754E+10 | 0.00 | 0.00 |
December | 0.197412E+11 | 0.815328E+10 | 0.171476E+11 | 0.141450E+11 | 0.300263E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165029E+12 | 0.540379E+11 | 0.131087E+12 | 0.806044E+11 | 0.504822E+11 | 0.00 | 0.00 |
Minimum of Months | 0.718146E+10 | 0.132925E+10 | 0.485285E+10 | 0.598061E+09 | 0.300263E+10 | 0.00 | 0.00 |
Maximum of Months | 0.197412E+11 | 0.815328E+10 | 0.171476E+11 | 0.141450E+11 | 0.514998E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.370948E+10 | 0.599474E+10 | 0.407109E+10 | 0.232162E+10 | 0.174948E+10 | 0.00 | 0.00 |
February | 0.466886E+10 | 0.503124E+10 | 0.473368E+10 | 0.273451E+10 | 0.199917E+10 | 0.00 | 0.00 |
March | 0.614804E+10 | 0.450461E+10 | 0.585344E+10 | 0.311590E+10 | 0.273754E+10 | 0.00 | 0.00 |
April | 0.825881E+10 | 0.309526E+10 | 0.722976E+10 | 0.384771E+10 | 0.338204E+10 | 0.00 | 0.00 |
May | 0.871438E+10 | 0.224412E+10 | 0.708336E+10 | 0.364984E+10 | 0.343351E+10 | 0.00 | 0.00 |
June | 0.101763E+11 | 0.155325E+10 | 0.734839E+10 | 0.410033E+10 | 0.324807E+10 | 0.00 | 0.00 |
July | 0.988216E+10 | 0.112941E+10 | 0.684896E+10 | 0.335179E+10 | 0.349717E+10 | 0.00 | 0.00 |
August | 0.973290E+10 | 0.134090E+10 | 0.699842E+10 | 0.323706E+10 | 0.376136E+10 | 0.00 | 0.00 |
September | 0.809939E+10 | 0.191620E+10 | 0.611731E+10 | 0.322174E+10 | 0.289557E+10 | 0.00 | 0.00 |
October | 0.675638E+10 | 0.353225E+10 | 0.578306E+10 | 0.359438E+10 | 0.218868E+10 | 0.00 | 0.00 |
November | 0.424688E+10 | 0.489245E+10 | 0.439324E+10 | 0.258464E+10 | 0.180860E+10 | 0.00 | 0.00 |
December | 0.348671E+10 | 0.662924E+10 | 0.392590E+10 | 0.246196E+10 | 0.146394E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.838803E+11 | 0.418637E+11 | 0.703866E+11 | 0.382215E+11 | 0.321651E+11 | 0.00 | 0.00 |
Minimum of Months | 0.348671E+10 | 0.112941E+10 | 0.392590E+10 | 0.232162E+10 | 0.146394E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101763E+11 | 0.662924E+10 | 0.734839E+10 | 0.410033E+10 | 0.376136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.487976E+09 | 0.795089E+10 | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.00 | 0.00 |
February | 0.913511E+09 | 0.649818E+10 | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.00 | 0.00 |
March | 0.213091E+10 | 0.569239E+10 | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.00 | 0.00 |
April | 0.335736E+10 | 0.367105E+10 | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.00 | 0.00 |
May | 0.482193E+10 | 0.276527E+10 | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.00 | 0.00 |
June | 0.723447E+10 | 0.177898E+10 | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.00 | 0.00 |
July | 0.743419E+10 | 0.124032E+10 | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.00 | 0.00 |
August | 0.630001E+10 | 0.140156E+10 | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.00 | 0.00 |
September | 0.414146E+10 | 0.241837E+10 | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.00 | 0.00 |
October | 0.196362E+10 | 0.444942E+10 | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.00 | 0.00 |
November | 0.666314E+09 | 0.614455E+10 | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.00 | 0.00 |
December | 0.157528E+09 | 0.832914E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.396093E+11 | 0.523401E+11 | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.157528E+09 | 0.124032E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.743419E+10 | 0.832914E+10 | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.332625E+10 | 0.498750E+10 | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.00 | 0.00 |
February | 0.401408E+10 | 0.412556E+10 | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.00 | 0.00 |
March | 0.668656E+10 | 0.364495E+10 | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.00 | 0.00 |
April | 0.980186E+10 | 0.244847E+10 | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.00 | 0.00 |
May | 0.102498E+11 | 0.192663E+10 | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.00 | 0.00 |
June | 0.118299E+11 | 0.120559E+10 | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.00 | 0.00 |
July | 0.118092E+11 | 0.862436E+09 | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.00 | 0.00 |
August | 0.113255E+11 | 0.969739E+09 | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.00 | 0.00 |
September | 0.859188E+10 | 0.159619E+10 | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.00 | 0.00 |
October | 0.674318E+10 | 0.286638E+10 | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.00 | 0.00 |
November | 0.425073E+10 | 0.397262E+10 | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.00 | 0.00 |
December | 0.318527E+10 | 0.528083E+10 | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.918142E+11 | 0.338869E+11 | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.318527E+10 | 0.862436E+09 | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118299E+11 | 0.528083E+10 | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179466E+11 | 0.768941E+10 | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.00 | 0.00 |
February | 0.162341E+11 | 0.641791E+10 | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.00 | 0.00 |
March | 0.135494E+11 | 0.576912E+10 | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.00 | 0.00 |
April | 0.106522E+11 | 0.396867E+10 | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.00 | 0.00 |
May | 0.740471E+10 | 0.299389E+10 | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.00 | 0.00 |
June | 0.721595E+10 | 0.189706E+10 | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.00 | 0.00 |
July | 0.892456E+10 | 0.131169E+10 | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.00 | 0.00 |
August | 0.117084E+11 | 0.153385E+10 | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.00 | 0.00 |
September | 0.144555E+11 | 0.258585E+10 | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.00 | 0.00 |
October | 0.183415E+11 | 0.451956E+10 | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.00 | 0.00 |
November | 0.182427E+11 | 0.608383E+10 | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.00 | 0.00 |
December | 0.196539E+11 | 0.788787E+10 | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.164329E+12 | 0.526587E+11 | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.00 | 0.00 |
Minimum of Months | 0.721595E+10 | 0.131169E+10 | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.196539E+11 | 0.788787E+10 | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.382415E+10 | 0.541405E+10 | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.00 | 0.00 |
February | 0.478743E+10 | 0.449175E+10 | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.00 | 0.00 |
March | 0.627061E+10 | 0.399970E+10 | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.00 | 0.00 |
April | 0.837605E+10 | 0.272276E+10 | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.00 | 0.00 |
May | 0.873408E+10 | 0.209978E+10 | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.00 | 0.00 |
June | 0.102290E+11 | 0.142079E+10 | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.00 | 0.00 |
July | 0.996539E+10 | 0.989955E+09 | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.00 | 0.00 |
August | 0.984733E+10 | 0.113153E+10 | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.00 | 0.00 |
September | 0.812179E+10 | 0.178457E+10 | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.00 | 0.00 |
October | 0.683114E+10 | 0.318195E+10 | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.00 | 0.00 |
November | 0.437088E+10 | 0.424613E+10 | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.00 | 0.00 |
December | 0.361950E+10 | 0.559323E+10 | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.849773E+11 | 0.370762E+11 | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.00 | 0.00 |
Minimum of Months | 0.361950E+10 | 0.989955E+09 | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102290E+11 | 0.559323E+10 | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.600975E+09 | 0.737041E+10 | 0.213778E+10 | 0.00 | 0.213778E+10 | 0.00 | 0.00 |
February | 0.102215E+10 | 0.606557E+10 | 0.241329E+10 | 0.00 | 0.241329E+10 | 0.00 | 0.00 |
March | 0.224285E+10 | 0.534684E+10 | 0.337022E+10 | 0.00 | 0.337022E+10 | 0.00 | 0.00 |
April | 0.340882E+10 | 0.349770E+10 | 0.413783E+10 | 35426328.02 | 0.410240E+10 | 0.00 | 0.00 |
May | 0.482287E+10 | 0.269842E+10 | 0.464778E+10 | 0.299658E+09 | 0.434812E+10 | 0.00 | 0.00 |
June | 0.718900E+10 | 0.176995E+10 | 0.511077E+10 | 0.836369E+09 | 0.427441E+10 | 0.00 | 0.00 |
July | 0.736332E+10 | 0.125958E+10 | 0.484725E+10 | 0.403437E+09 | 0.444382E+10 | 0.00 | 0.00 |
August | 0.624112E+10 | 0.140992E+10 | 0.449664E+10 | 0.100670E+09 | 0.439597E+10 | 0.00 | 0.00 |
September | 0.412174E+10 | 0.236765E+10 | 0.347992E+10 | 893125.55 | 0.347903E+10 | 0.00 | 0.00 |
October | 0.202818E+10 | 0.417969E+10 | 0.268327E+10 | 0.00 | 0.268327E+10 | 0.00 | 0.00 |
November | 0.787592E+09 | 0.562258E+10 | 0.220523E+10 | 0.00 | 0.220523E+10 | 0.00 | 0.00 |
December | 0.220377E+09 | 0.768406E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.400490E+11 | 0.492724E+11 | 0.413496E+11 | 0.167645E+10 | 0.396731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220377E+09 | 0.125958E+10 | 0.181957E+10 | 0.00 | 0.181957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.736332E+10 | 0.768406E+10 | 0.511077E+10 | 0.836369E+09 | 0.444382E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.347357E+10 | 0.461027E+10 | 0.394690E+10 | 0.220669E+10 | 0.174021E+10 | 0.00 | 0.00 |
February | 0.412717E+10 | 0.384813E+10 | 0.433133E+10 | 0.233505E+10 | 0.199628E+10 | 0.00 | 0.00 |
March | 0.676203E+10 | 0.345057E+10 | 0.632586E+10 | 0.359614E+10 | 0.272972E+10 | 0.00 | 0.00 |
April | 0.982604E+10 | 0.235937E+10 | 0.836363E+10 | 0.476472E+10 | 0.359891E+10 | 0.00 | 0.00 |
May | 0.102434E+11 | 0.188475E+10 | 0.824670E+10 | 0.469972E+10 | 0.354697E+10 | 0.00 | 0.00 |
June | 0.118052E+11 | 0.119764E+10 | 0.860378E+10 | 0.530034E+10 | 0.330344E+10 | 0.00 | 0.00 |
July | 0.117727E+11 | 0.871939E+09 | 0.822660E+10 | 0.470431E+10 | 0.352230E+10 | 0.00 | 0.00 |
August | 0.112963E+11 | 0.972032E+09 | 0.814078E+10 | 0.448817E+10 | 0.365261E+10 | 0.00 | 0.00 |
September | 0.858523E+10 | 0.156820E+10 | 0.655725E+10 | 0.366884E+10 | 0.288841E+10 | 0.00 | 0.00 |
October | 0.679039E+10 | 0.272368E+10 | 0.589289E+10 | 0.373881E+10 | 0.215408E+10 | 0.00 | 0.00 |
November | 0.436258E+10 | 0.365591E+10 | 0.445702E+10 | 0.262025E+10 | 0.183677E+10 | 0.00 | 0.00 |
December | 0.329587E+10 | 0.483176E+10 | 0.373183E+10 | 0.227116E+10 | 0.146067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.923405E+11 | 0.319743E+11 | 0.768246E+11 | 0.443942E+11 | 0.324304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.329587E+10 | 0.871939E+09 | 0.373183E+10 | 0.220669E+10 | 0.146067E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118052E+11 | 0.483176E+10 | 0.860378E+10 | 0.530034E+10 | 0.365261E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181276E+11 | 0.716738E+10 | 0.158046E+11 | 0.122982E+11 | 0.350645E+10 | 0.00 | 0.00 |
February | 0.163517E+11 | 0.601653E+10 | 0.139702E+11 | 0.102047E+11 | 0.376544E+10 | 0.00 | 0.00 |
March | 0.136290E+11 | 0.546978E+10 | 0.113976E+11 | 0.689054E+10 | 0.450705E+10 | 0.00 | 0.00 |
April | 0.106674E+11 | 0.380226E+10 | 0.860193E+10 | 0.353094E+10 | 0.507100E+10 | 0.00 | 0.00 |
May | 0.738812E+10 | 0.291527E+10 | 0.592800E+10 | 0.130405E+10 | 0.462395E+10 | 0.00 | 0.00 |
June | 0.716770E+10 | 0.187991E+10 | 0.485283E+10 | 0.598059E+09 | 0.425477E+10 | 0.00 | 0.00 |
July | 0.885137E+10 | 0.132928E+10 | 0.554890E+10 | 0.886108E+09 | 0.466279E+10 | 0.00 | 0.00 |
August | 0.116415E+11 | 0.153855E+10 | 0.763015E+10 | 0.248019E+10 | 0.514996E+10 | 0.00 | 0.00 |
September | 0.144246E+11 | 0.253671E+10 | 0.102105E+11 | 0.569368E+10 | 0.451683E+10 | 0.00 | 0.00 |
October | 0.184035E+11 | 0.430403E+10 | 0.144348E+11 | 0.106312E+11 | 0.380366E+10 | 0.00 | 0.00 |
November | 0.183923E+11 | 0.566886E+10 | 0.155590E+11 | 0.119415E+11 | 0.361752E+10 | 0.00 | 0.00 |
December | 0.198075E+11 | 0.730629E+10 | 0.171476E+11 | 0.141450E+11 | 0.300262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.164852E+12 | 0.499348E+11 | 0.131086E+12 | 0.806042E+11 | 0.504820E+11 | 0.00 | 0.00 |
Minimum of Months | 0.716770E+10 | 0.132928E+10 | 0.485283E+10 | 0.598059E+09 | 0.300262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.198075E+11 | 0.730629E+10 | 0.171476E+11 | 0.141450E+11 | 0.514996E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.389840E+10 | 0.506392E+10 | 0.407107E+10 | 0.232161E+10 | 0.174947E+10 | 0.00 | 0.00 |
February | 0.483947E+10 | 0.423653E+10 | 0.473366E+10 | 0.273449E+10 | 0.199917E+10 | 0.00 | 0.00 |
March | 0.631373E+10 | 0.380178E+10 | 0.585342E+10 | 0.311589E+10 | 0.273753E+10 | 0.00 | 0.00 |
April | 0.838005E+10 | 0.261702E+10 | 0.722973E+10 | 0.384770E+10 | 0.338203E+10 | 0.00 | 0.00 |
May | 0.871233E+10 | 0.204761E+10 | 0.708333E+10 | 0.364983E+10 | 0.343350E+10 | 0.00 | 0.00 |
June | 0.101898E+11 | 0.140573E+10 | 0.734836E+10 | 0.410031E+10 | 0.324805E+10 | 0.00 | 0.00 |
July | 0.991362E+10 | 0.996192E+09 | 0.684893E+10 | 0.335178E+10 | 0.349715E+10 | 0.00 | 0.00 |
August | 0.980161E+10 | 0.113127E+10 | 0.699839E+10 | 0.323704E+10 | 0.376135E+10 | 0.00 | 0.00 |
September | 0.809681E+10 | 0.175135E+10 | 0.611728E+10 | 0.322173E+10 | 0.289556E+10 | 0.00 | 0.00 |
October | 0.684845E+10 | 0.302961E+10 | 0.578303E+10 | 0.359437E+10 | 0.218867E+10 | 0.00 | 0.00 |
November | 0.443267E+10 | 0.395469E+10 | 0.439322E+10 | 0.258463E+10 | 0.180859E+10 | 0.00 | 0.00 |
December | 0.366863E+10 | 0.521590E+10 | 0.392588E+10 | 0.246195E+10 | 0.146393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.850955E+11 | 0.352516E+11 | 0.703863E+11 | 0.382213E+11 | 0.321650E+11 | 0.00 | 0.00 |
Minimum of Months | 0.366863E+10 | 0.996192E+09 | 0.392588E+10 | 0.232161E+10 | 0.146393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101898E+11 | 0.521590E+10 | 0.734836E+10 | 0.410031E+10 | 0.376135E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.389843E+11 | -0.379584E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102591E+10 | 58.98 | 0.00 | 0.00 |
February | 0.356867E+11 | -0.347599E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -926798186.9 | 58.98 | 0.00 | 0.00 |
March | 0.409015E+11 | -0.398736E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102796E+10 | 58.98 | 0.00 | 0.00 |
April | 0.352282E+11 | -0.342380E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990271324.7 | 58.98 | 0.00 | 0.00 |
May | 0.350373E+11 | -0.340132E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102410E+10 | 58.97 | 0.00 | 0.00 |
June | 0.322819E+11 | -0.312906E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991270463.1 | 58.97 | 0.00 | 0.00 |
July | 0.292609E+11 | -0.282422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101871E+10 | 58.97 | 0.00 | 0.00 |
August | 0.316145E+11 | -0.305917E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102283E+10 | 58.98 | 0.00 | 0.00 |
September | 0.296968E+11 | -0.287092E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987681086.8 | 58.98 | 0.00 | 0.00 |
October | 0.326456E+11 | -0.316265E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101909E+10 | 58.97 | 0.00 | 0.00 |
November | 0.344519E+11 | -0.334642E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987746430.1 | 58.98 | 0.00 | 0.00 |
December | 0.365705E+11 | -0.355486E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102191E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.412360E+12 | -0.400316E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120443E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.292609E+11 | -0.398736E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102796E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.409015E+11 | -0.282422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -926798186.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 10435.93 | 37.84 | 289.17 | 286.83 | 2693.06 | 28.20 | 207.00 | 276.17 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 12790.87 | 37.90 | 272.83 | 275.17 | 1925.66 | 23.54 | 165.00 | 259.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 2372.78 | 20.28 | 119.50 | 331.17 | 1388.68 | 21.43 | 162.67 | 299.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 1925.93 | 20.44 | 126.67 | 352.83 | 1166.15 | 21.82 | 244.67 | 328.83 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:30 | 1490.06 | 19.76 | 58.83 | 372.67 | 921.30 | 21.19 | 192.67 | 339.83 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:00 | 1189.73 | 18.88 | 40.33 | 375.17 | 745.44 | 20.36 | 118.50 | 327.50 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1439.54 | 19.60 | 68.67 | 376.67 | 881.06 | 21.07 | 170.17 | 337.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:19 | 1791.43 | 20.19 | 142.33 | 373.33 | 1071.12 | 21.60 | 236.33 | 343.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 2329.37 | 20.71 | 118.83 | 330.17 | 1297.93 | 21.46 | 169.17 | 303.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6228.00 | 29.21 | 209.17 | 316.00 | 1730.04 | 21.61 | 132.67 | 303.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:00 | 11795.16 | 38.88 | 280.17 | 284.50 | 2658.97 | 27.85 | 204.00 | 273.00 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 11922.36 | 40.19 | 263.83 | 269.50 | 3923.68 | 31.51 | 191.50 | 261.17 |
Annual Sum or Average | 4149.83 | 0.50 | 4839.61 | 25.80 | 1990.33 | 3944.00 | 1581.73 | 23.06 | 2194.33 | 3652.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1189.73 | 18.88 | 40.33 | 269.50 | 745.44 | 20.36 | 118.50 | 259.50 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 12790.87 | 40.19 | 289.17 | 376.67 | 3923.68 | 31.51 | 244.67 | 343.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 2701.31 | 24.98 | 126.33 | 265.33 | 1502.63 | 24.85 | 144.17 | 237.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:30 | 3433.30 | 24.91 | 116.33 | 266.83 | 1904.16 | 24.88 | 140.00 | 241.00 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:49 | 3482.74 | 24.42 | 130.00 | 327.50 | 1873.42 | 24.46 | 166.17 | 299.33 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 4954.48 | 25.70 | 131.33 | 358.00 | 1979.27 | 24.47 | 179.67 | 339.17 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-05:00 | 3971.82 | 23.52 | 97.00 | 377.33 | 2205.68 | 23.89 | 125.17 | 349.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3791.25 | 23.16 | 116.00 | 393.00 | 2145.59 | 23.55 | 135.83 | 357.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3784.80 | 23.69 | 113.67 | 385.50 | 2016.30 | 23.90 | 146.33 | 356.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 4572.04 | 25.27 | 139.50 | 381.00 | 1865.77 | 24.21 | 184.67 | 359.33 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3900.78 | 24.37 | 126.00 | 333.33 | 2164.96 | 24.59 | 156.33 | 309.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:30 | 3554.94 | 24.82 | 115.67 | 305.50 | 1962.03 | 24.75 | 137.50 | 281.33 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-06:49 | 2891.92 | 24.88 | 106.33 | 266.67 | 1558.68 | 24.74 | 129.00 | 240.83 |
December | 265.67 | 0.52 | 0.48 | 01-DEC-07:49 | 3142.03 | 25.19 | 105.50 | 248.50 | 1816.67 | 24.84 | 108.17 | 210.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3749.01 | 24.53 | 1423.67 | 3908.50 | 1935.59 | 24.37 | 1753.00 | 3581.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2701.31 | 23.16 | 97.00 | 248.50 | 1502.63 | 23.55 | 108.17 | 210.17 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 4954.48 | 25.70 | 139.50 | 393.00 | 2205.68 | 24.88 | 184.67 | 359.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-08:50 | 671.63 | 17.16 | 0.00 | 246.67 | 428.81 | 18.97 | 13.83 | 192.33 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:09 | 792.35 | 17.94 | 0.00 | 254.17 | 520.07 | 19.69 | 62.00 | 209.83 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:19 | 937.39 | 18.61 | 0.17 | 318.83 | 586.70 | 20.12 | 104.50 | 272.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:19 | 1178.90 | 20.06 | 43.50 | 361.17 | 746.99 | 21.44 | 203.33 | 341.00 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:19 | 1367.85 | 20.26 | 84.83 | 389.17 | 795.30 | 21.62 | 193.67 | 356.00 |
June | 412.83 | 0.48 | 0.48 | 01-JUN-05:40 | 1412.86 | 22.41 | 129.50 | 404.00 | 772.29 | 22.22 | 190.33 | 380.00 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 1395.71 | 22.13 | 123.00 | 395.00 | 804.47 | 21.54 | 208.00 | 369.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1246.00 | 20.13 | 89.83 | 383.33 | 787.55 | 21.53 | 226.67 | 366.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 994.22 | 19.11 | 8.83 | 328.33 | 635.22 | 20.61 | 119.50 | 291.67 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:10 | 726.13 | 17.46 | 0.00 | 288.00 | 494.16 | 19.17 | 37.17 | 239.67 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:19 | 714.14 | 17.79 | 0.00 | 254.67 | 471.73 | 19.62 | 17.50 | 208.33 |
December | 265.67 | 0.54 | 0.48 | 01-DEC-08:20 | 595.56 | 16.35 | 0.00 | 230.83 | 407.70 | 18.35 | 4.83 | 169.50 |
Annual Sum or Average | 4149.83 | 0.50 | 1042.02 | 19.36 | 479.67 | 3854.17 | 640.98 | 20.57 | 1381.33 | 3396.33 | ||
Minimum of Months | 265.67 | 0.48 | 0.48 | 595.56 | 16.35 | 0.00 | 230.83 | 407.70 | 18.35 | 4.83 | 169.50 | |
Maximum of Months | 412.83 | 0.54 | 0.48 | 1412.86 | 22.41 | 129.50 | 404.00 | 804.47 | 22.22 | 226.67 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-08:50 | 2333.26 | 23.62 | 107.67 | 271.50 | 1168.56 | 23.37 | 127.50 | 238.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-08:20 | 3410.48 | 25.33 | 117.67 | 264.67 | 1867.19 | 25.18 | 143.50 | 238.00 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:30 | 3599.97 | 23.99 | 129.83 | 329.67 | 1374.94 | 22.74 | 155.83 | 298.50 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:40 | 4446.74 | 24.11 | 113.17 | 361.67 | 1824.99 | 23.33 | 155.83 | 341.17 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:40 | 3292.88 | 20.35 | 50.50 | 386.17 | 1844.52 | 20.66 | 82.67 | 364.50 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-06:10 | 3492.75 | 17.27 | 5.33 | 385.83 | 2017.50 | 19.75 | 92.83 | 357.83 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:00 | 3366.38 | 18.22 | 13.67 | 385.83 | 1849.15 | 20.44 | 129.00 | 359.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:40 | 3335.75 | 21.18 | 71.83 | 377.17 | 1746.78 | 21.16 | 171.50 | 353.83 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:49 | 3755.70 | 24.21 | 127.00 | 334.17 | 1484.87 | 23.12 | 143.67 | 312.33 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3384.19 | 24.29 | 116.00 | 306.00 | 1850.44 | 24.25 | 131.83 | 281.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-07:19 | 3312.66 | 26.00 | 118.00 | 275.83 | 1932.01 | 25.90 | 143.17 | 250.17 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-08:20 | 3047.79 | 26.23 | 111.00 | 253.33 | 1793.09 | 25.92 | 121.67 | 225.83 |
Annual Sum or Average | 4149.83 | 0.50 | 3427.41 | 22.56 | 1081.67 | 3931.83 | 1735.44 | 22.72 | 1599.00 | 3621.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2333.26 | 17.27 | 5.33 | 253.33 | 1168.56 | 19.75 | 82.67 | 225.83 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4446.74 | 26.23 | 129.83 | 386.17 | 2017.50 | 25.92 | 171.50 | 364.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 10528.15 | 37.22 | 288.33 | 287.00 | 2844.35 | 24.36 | 127.17 | 277.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 12890.49 | 37.39 | 271.67 | 275.33 | 2226.91 | 21.31 | 79.17 | 264.17 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:00 | 2436.71 | 13.66 | 10.67 | 331.17 | 1499.59 | 16.96 | 7.83 | 302.67 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 1975.08 | 14.52 | 0.00 | 353.00 | 1252.16 | 18.05 | 5.17 | 330.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1526.62 | 13.96 | 0.00 | 373.67 | 986.76 | 17.50 | 0.00 | 343.00 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:00 | 1219.01 | 12.90 | 0.00 | 375.83 | 797.94 | 16.54 | 0.00 | 333.83 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1472.14 | 13.67 | 0.00 | 377.33 | 942.51 | 17.26 | 0.33 | 342.83 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:19 | 1833.26 | 14.26 | 0.00 | 373.83 | 1147.48 | 17.79 | 0.17 | 347.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:30 | 2393.95 | 14.52 | 16.50 | 330.83 | 1398.52 | 17.21 | 4.50 | 306.17 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6359.23 | 25.58 | 183.50 | 319.00 | 1879.45 | 17.03 | 17.17 | 305.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 11896.79 | 38.44 | 280.17 | 284.83 | 2851.96 | 24.39 | 112.67 | 275.00 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 12049.44 | 39.79 | 263.50 | 269.67 | 4101.89 | 28.14 | 146.67 | 261.83 |
Annual Sum or Average | 4149.83 | 0.50 | 4907.57 | 21.46 | 1314.33 | 3951.50 | 1700.24 | 19.26 | 500.83 | 3689.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1219.01 | 12.90 | 0.00 | 269.67 | 797.94 | 16.54 | 0.00 | 261.83 | |
Maximum of Months | 412.83 | 0.50 | 0.48 | 12890.49 | 39.79 | 288.33 | 377.33 | 4101.89 | 28.14 | 146.67 | 347.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 2747.16 | 22.49 | 106.33 | 266.00 | 1561.26 | 22.97 | 83.33 | 241.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:30 | 3490.95 | 22.32 | 96.83 | 268.00 | 1972.48 | 22.87 | 72.67 | 245.17 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:49 | 3556.82 | 21.40 | 105.33 | 328.50 | 1956.30 | 22.04 | 75.83 | 302.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 4961.89 | 21.62 | 114.83 | 357.67 | 2081.65 | 21.80 | 67.17 | 342.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-05:00 | 4030.68 | 20.19 | 95.50 | 377.67 | 2309.74 | 21.20 | 66.33 | 352.33 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3867.06 | 19.76 | 111.83 | 393.83 | 2240.65 | 20.82 | 82.50 | 360.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3853.35 | 20.34 | 103.83 | 386.17 | 2115.48 | 21.19 | 71.83 | 358.50 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 4629.05 | 22.41 | 134.00 | 381.17 | 1959.75 | 21.62 | 75.00 | 361.67 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:10 | 3970.05 | 21.36 | 109.50 | 333.33 | 2248.47 | 22.20 | 80.83 | 311.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:30 | 3606.67 | 21.71 | 103.00 | 305.83 | 2041.90 | 22.51 | 77.33 | 285.83 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-06:49 | 2897.14 | 21.27 | 80.50 | 267.83 | 1628.27 | 22.70 | 67.33 | 244.17 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-07:49 | 3191.96 | 22.88 | 95.67 | 249.00 | 1877.75 | 23.11 | 74.00 | 216.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3801.91 | 21.39 | 1257.17 | 3915.00 | 2020.81 | 21.99 | 894.17 | 3622.50 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2747.16 | 19.76 | 80.50 | 249.00 | 1561.26 | 20.82 | 66.33 | 216.17 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4961.89 | 22.88 | 134.00 | 393.83 | 2309.74 | 23.11 | 83.33 | 361.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-08:39 | 683.90 | 11.26 | 0.00 | 247.50 | 457.08 | 15.06 | 0.00 | 201.00 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:09 | 808.72 | 12.24 | 0.00 | 254.50 | 554.97 | 15.99 | 0.00 | 216.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:19 | 957.38 | 12.97 | 0.00 | 319.67 | 626.17 | 16.56 | 0.00 | 280.50 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:19 | 1205.20 | 14.86 | 0.00 | 361.33 | 797.03 | 18.40 | 6.67 | 343.33 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:10 | 1399.08 | 14.62 | 1.00 | 389.17 | 850.68 | 18.24 | 15.50 | 359.50 |
June | 412.83 | 0.48 | 0.48 | 01-JUN-05:40 | 1446.21 | 17.39 | 77.17 | 404.00 | 826.93 | 18.73 | 31.00 | 382.33 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1430.45 | 17.07 | 54.00 | 395.50 | 870.32 | 18.82 | 23.50 | 373.17 |
August | 408.83 | 0.49 | 0.48 | 01-AUG-05:00 | 1294.63 | 14.69 | 0.00 | 385.00 | 839.59 | 18.25 | 6.33 | 368.50 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 1016.68 | 13.69 | 0.00 | 328.67 | 678.39 | 17.28 | 0.00 | 297.17 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:10 | 743.83 | 11.88 | 0.00 | 290.00 | 528.23 | 15.64 | 0.00 | 249.17 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:19 | 727.30 | 12.12 | 0.00 | 256.00 | 503.00 | 15.93 | 0.00 | 216.67 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-08:20 | 606.80 | 10.57 | 0.00 | 231.67 | 434.93 | 14.45 | 0.00 | 181.50 |
Annual Sum or Average | 4149.83 | 0.50 | 1067.37 | 13.88 | 132.17 | 3863.00 | 685.55 | 17.15 | 83.00 | 3469.50 | ||
Minimum of Months | 265.67 | 0.48 | 0.48 | 606.80 | 10.57 | 0.00 | 231.67 | 434.93 | 14.45 | 0.00 | 181.50 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 1446.21 | 17.39 | 77.17 | 404.00 | 870.32 | 18.82 | 31.00 | 382.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-08:39 | 2378.04 | 20.81 | 85.33 | 272.17 | 1224.76 | 21.21 | 60.67 | 243.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-08:09 | 3474.89 | 22.64 | 93.17 | 265.67 | 1942.52 | 23.10 | 68.00 | 241.67 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:30 | 3666.09 | 21.03 | 106.00 | 330.50 | 1449.79 | 20.06 | 48.00 | 303.00 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:40 | 4510.59 | 21.02 | 110.33 | 361.83 | 1913.74 | 20.53 | 51.00 | 344.00 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:40 | 3346.56 | 16.32 | 46.67 | 386.33 | 1932.59 | 17.20 | 0.00 | 366.83 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-06:10 | 3532.82 | 12.40 | 0.00 | 385.17 | 2104.69 | 16.18 | 0.00 | 360.83 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 3407.14 | 13.55 | 3.67 | 386.50 | 1935.66 | 16.99 | 0.00 | 362.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:30 | 3377.78 | 17.35 | 62.50 | 377.17 | 1831.01 | 17.84 | 5.17 | 357.00 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:49 | 3804.28 | 21.21 | 110.00 | 333.83 | 1567.39 | 20.42 | 54.33 | 314.50 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3454.41 | 21.41 | 100.00 | 306.83 | 1929.02 | 21.95 | 70.17 | 284.67 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-07:19 | 3363.46 | 23.63 | 105.00 | 276.33 | 1996.93 | 24.09 | 80.33 | 254.33 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-08:20 | 3096.62 | 24.07 | 106.17 | 253.33 | 1852.89 | 24.32 | 84.33 | 230.00 |
Annual Sum or Average | 4149.83 | 0.50 | 3479.79 | 19.18 | 928.83 | 3935.67 | 1814.03 | 19.96 | 522.00 | 3662.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2378.04 | 12.40 | 0.00 | 253.33 | 1224.76 | 16.18 | 0.00 | 230.00 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4510.59 | 24.07 | 110.33 | 386.50 | 2104.69 | 24.32 | 84.33 | 366.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.49 | 0.48 | 01-JAN-07:40 | 10529.66 | 37.21 | 288.33 | 287.00 | 2846.39 | 24.35 | 127.17 | 277.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 12892.78 | 37.38 | 271.67 | 275.50 | 2229.09 | 21.30 | 79.17 | 264.33 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:00 | 2439.54 | 13.63 | 10.67 | 331.17 | 1501.44 | 16.95 | 7.83 | 302.83 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 1977.40 | 14.49 | 0.00 | 353.00 | 1253.71 | 18.04 | 5.17 | 330.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:19 | 1528.22 | 13.93 | 0.00 | 373.83 | 987.91 | 17.49 | 0.00 | 343.00 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:00 | 1220.27 | 12.87 | 0.00 | 375.83 | 798.84 | 16.53 | 0.00 | 333.83 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 1473.76 | 13.64 | 0.00 | 377.33 | 943.64 | 17.25 | 0.33 | 343.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:19 | 1835.43 | 14.23 | 0.00 | 373.83 | 1148.95 | 17.77 | 0.00 | 347.00 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:30 | 2396.44 | 14.49 | 16.50 | 331.17 | 1400.18 | 17.19 | 4.33 | 306.17 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6361.27 | 25.56 | 183.50 | 319.00 | 1881.08 | 17.01 | 17.17 | 305.00 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:49 | 11898.44 | 38.43 | 280.00 | 284.83 | 2854.11 | 24.37 | 112.67 | 275.00 |
December | 265.67 | 0.49 | 0.48 | 01-DEC-07:49 | 12050.41 | 39.78 | 263.50 | 269.67 | 4103.76 | 28.13 | 146.67 | 261.83 |
Annual Sum or Average | 4149.83 | 0.50 | 4909.48 | 21.44 | 1314.17 | 3952.17 | 1701.82 | 19.25 | 500.50 | 3690.17 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 1220.27 | 12.87 | 0.00 | 269.67 | 798.84 | 16.53 | 0.00 | 261.83 | |
Maximum of Months | 412.83 | 0.50 | 0.48 | 12892.78 | 39.78 | 288.33 | 377.33 | 4103.76 | 28.13 | 146.67 | 347.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:40 | 2748.06 | 22.46 | 106.33 | 266.00 | 1562.25 | 22.95 | 83.00 | 241.50 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:30 | 3492.00 | 22.29 | 96.83 | 268.00 | 1973.66 | 22.86 | 72.67 | 245.17 |
March | 351.33 | 0.49 | 0.48 | 01-MAR-06:49 | 3558.26 | 21.37 | 105.33 | 328.50 | 1957.64 | 22.03 | 75.83 | 302.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-05:00 | 4963.38 | 21.59 | 114.83 | 357.67 | 2083.32 | 21.79 | 67.17 | 342.67 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-05:00 | 4032.07 | 20.16 | 95.50 | 377.67 | 2311.31 | 21.18 | 66.33 | 352.83 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:19 | 3868.32 | 19.73 | 111.83 | 393.83 | 2241.88 | 20.80 | 82.50 | 360.83 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3854.72 | 20.31 | 103.83 | 386.33 | 2116.90 | 21.17 | 71.83 | 358.67 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:40 | 4630.56 | 22.39 | 134.00 | 381.17 | 1961.29 | 21.61 | 75.00 | 361.67 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:10 | 3971.39 | 21.33 | 109.50 | 333.33 | 2249.86 | 22.19 | 80.67 | 311.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:30 | 3607.41 | 21.68 | 103.00 | 305.83 | 2042.87 | 22.50 | 77.33 | 285.83 |
November | 284.17 | 0.50 | 0.48 | 01-NOV-06:49 | 2897.87 | 21.24 | 80.50 | 267.83 | 1629.31 | 22.69 | 67.17 | 244.17 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-07:49 | 3192.52 | 22.86 | 95.67 | 249.17 | 1878.56 | 23.10 | 73.83 | 216.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3803.10 | 21.37 | 1257.17 | 3915.33 | 2022.10 | 21.97 | 893.33 | 3623.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2748.06 | 19.73 | 80.50 | 249.17 | 1562.25 | 20.80 | 66.33 | 216.17 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4963.38 | 22.86 | 134.00 | 393.83 | 2311.31 | 23.10 | 83.00 | 361.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-08:39 | 684.39 | 11.22 | 0.00 | 247.50 | 457.59 | 15.05 | 0.00 | 201.00 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:09 | 809.20 | 12.20 | 0.00 | 254.67 | 555.54 | 15.97 | 0.00 | 216.83 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:19 | 958.24 | 12.94 | 0.00 | 319.67 | 626.90 | 16.55 | 0.00 | 280.50 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:19 | 1206.07 | 14.83 | 0.00 | 361.33 | 797.89 | 18.39 | 6.67 | 343.67 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:10 | 1400.12 | 14.59 | 1.00 | 389.17 | 851.63 | 18.23 | 14.83 | 359.50 |
June | 412.83 | 0.48 | 0.48 | 01-JUN-05:40 | 1447.22 | 17.37 | 77.17 | 404.00 | 827.80 | 18.72 | 30.83 | 382.33 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1431.56 | 17.04 | 54.00 | 395.50 | 871.29 | 18.81 | 23.33 | 373.17 |
August | 408.83 | 0.49 | 0.48 | 01-AUG-05:00 | 1295.67 | 14.66 | 0.00 | 385.00 | 840.54 | 18.24 | 5.83 | 368.50 |
September | 359.33 | 0.50 | 0.48 | 01-SEP-06:40 | 1017.45 | 13.66 | 0.00 | 328.67 | 679.13 | 17.26 | 0.00 | 297.17 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:10 | 744.19 | 11.85 | 0.00 | 290.00 | 528.71 | 15.63 | 0.00 | 249.33 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:19 | 727.66 | 12.09 | 0.00 | 256.00 | 503.50 | 15.91 | 0.00 | 216.67 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-08:20 | 607.00 | 10.54 | 0.00 | 231.83 | 435.32 | 14.44 | 0.00 | 181.67 |
Annual Sum or Average | 4149.83 | 0.50 | 1068.13 | 13.85 | 132.17 | 3863.33 | 686.29 | 17.13 | 81.50 | 3470.33 | ||
Minimum of Months | 265.67 | 0.48 | 0.48 | 607.00 | 10.54 | 0.00 | 231.83 | 435.32 | 14.44 | 0.00 | 181.67 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 1447.22 | 17.37 | 77.17 | 404.00 | 871.29 | 18.81 | 30.83 | 382.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-08:39 | 2378.90 | 20.78 | 85.33 | 272.17 | 1225.74 | 21.20 | 60.67 | 243.50 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-08:09 | 3475.83 | 22.61 | 93.17 | 265.67 | 1943.69 | 23.09 | 67.67 | 242.00 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:30 | 3667.63 | 21.00 | 106.00 | 330.67 | 1451.15 | 20.04 | 48.00 | 303.00 |
April | 381.83 | 0.49 | 0.48 | 01-APR-06:40 | 4512.16 | 20.99 | 110.33 | 361.83 | 1915.24 | 20.51 | 51.00 | 344.17 |
May | 378.00 | 0.49 | 0.48 | 01-MAY-06:40 | 3348.01 | 16.29 | 46.67 | 386.33 | 1934.02 | 17.18 | 0.00 | 366.83 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-06:10 | 3534.16 | 12.36 | 0.00 | 385.17 | 2105.91 | 16.16 | 0.00 | 361.00 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:49 | 3408.77 | 13.52 | 3.67 | 386.50 | 1937.14 | 16.98 | 0.00 | 362.83 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-06:30 | 3379.69 | 17.32 | 62.50 | 377.33 | 1832.77 | 17.82 | 5.17 | 357.00 |
September | 359.33 | 0.49 | 0.48 | 01-SEP-06:49 | 3805.76 | 21.18 | 110.00 | 333.83 | 1568.82 | 20.40 | 54.33 | 314.50 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3455.21 | 21.38 | 100.00 | 306.83 | 1930.02 | 21.93 | 70.17 | 284.83 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-07:19 | 3364.24 | 23.60 | 105.00 | 276.33 | 1997.97 | 24.08 | 80.17 | 254.50 |
December | 265.67 | 0.51 | 0.48 | 01-DEC-08:20 | 3097.16 | 24.04 | 106.17 | 253.33 | 1853.66 | 24.31 | 84.00 | 230.17 |
Annual Sum or Average | 4149.83 | 0.50 | 3481.08 | 19.15 | 928.83 | 3936.00 | 1815.33 | 19.95 | 521.17 | 3664.33 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 2378.90 | 12.36 | 0.00 | 253.33 | 1225.74 | 16.16 | 0.00 | 230.17 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 4512.16 | 24.04 | 110.33 | 386.50 | 2105.91 | 24.31 | 84.00 | 366.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.910339E+10 | 29045.55 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.511029E+10 | 27982.22 | 04-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144445E+10 | 20120.45 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114426E+09 | 13163.92 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40142865.92 | 6684.98 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879232E+09 | 22416.84 | 27-OCT-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180846E+10 | 25442.42 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.651180E+10 | 32830.07 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.910339E+10 | 32830.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37346407.54 | 8208.44 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18519175.55 | 12518.64 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5960359.04 | 876.42 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61825942.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37346407.54 | 12518.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 38280648.70 | 11582.40 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16169352.73 | 11578.03 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26697303.52 | 9294.78 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81147304.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38280648.70 | 11582.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 92307491.72 | 16005.62 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36105350.47 | 16023.92 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 515707.18 | 952.80 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1639637.77 | 858.90 | 26-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33834313.56 | 15783.29 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92307491.72 | 16023.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121504E+12 | 303344.90 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793469E+11 | 290812.86 | 06-FEB-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294273E+11 | 275968.52 | 02-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.557757E+10 | 159262.02 | 07-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989020E+09 | 75190.58 | 06-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166944E+11 | 215314.51 | 27-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380975E+11 | 241458.80 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119081E+12 | 310502.22 | 15-DEC-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121504E+12 | 310502.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194521E+11 | 136904.70 | 20-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117285E+11 | 136827.93 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269213E+10 | 147818.88 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128681E+09 | 148010.81 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.865823E+09 | 148255.53 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.445849E+10 | 148428.12 | 04-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203474E+11 | 136912.56 | 09-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.596730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203474E+11 | 148428.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.809299E+10 | 165894.65 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419293E+10 | 165778.01 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.723275E+09 | 165594.41 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35125863.79 | 78011.67 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373061E+09 | 165409.31 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129678E+10 | 165683.04 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.732760E+10 | 166030.06 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.809299E+10 | 166030.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.654100E+10 | 177295.39 | 17-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361231E+10 | 176507.80 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.665072E+09 | 176270.51 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59288934.15 | 85773.29 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.319104E+09 | 176093.36 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462109E+09 | 175509.48 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.551372E+10 | 177293.80 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.654100E+10 | 177295.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.616663E+10 | 166975.68 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344186E+10 | 166691.46 | 25-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.443799E+09 | 166628.13 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223182E+09 | 126597.77 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.685256E+09 | 166638.39 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.542022E+10 | 166672.54 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.616663E+10 | 166975.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144106E+11 | 32673.37 | 30-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977769E+10 | 34212.61 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418996E+10 | 23098.97 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105593E+10 | 16469.63 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206513E+09 | 9518.22 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4201639.70 | 3063.39 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3087.49 | 10.29 | 09-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249706E+10 | 24642.59 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569213E+10 | 30490.02 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149212E+11 | 32659.10 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.527553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149212E+11 | 34212.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.321369E+10 | 74222.50 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136268E+10 | 73823.37 | 06-FEB-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109956E+09 | 72707.92 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25963602.80 | 28605.91 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.621891E+09 | 73862.58 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295850E+10 | 74201.55 | 04-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.321369E+10 | 74222.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550594E+10 | 15875.73 | 03-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352022E+10 | 15880.38 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130975E+10 | 15855.66 | 15-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216551E+09 | 15808.72 | 24-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28236528.38 | 15796.28 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563334E+09 | 15911.92 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212349E+10 | 15879.01 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.570347E+10 | 15880.97 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.570347E+10 | 15911.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246794E+10 | 18713.35 | 18-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143767E+10 | 18706.42 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.490742E+09 | 18647.78 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60106896.23 | 18639.70 | 08-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9636391.37 | 12685.49 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230191E+09 | 18632.02 | 25-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725522E+09 | 18659.16 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236341E+10 | 18711.88 | 11-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.778522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246794E+10 | 18713.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242183E+10 | 19780.99 | 19-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151809E+10 | 19791.83 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710298E+09 | 19770.96 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145438E+09 | 19620.05 | 08-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39294563.36 | 19665.12 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1258458.52 | 1843.09 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268179E+09 | 19642.61 | 26-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649462E+09 | 19771.56 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218969E+10 | 19792.56 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242183E+10 | 19792.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201034E+10 | 19652.68 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119422E+10 | 19716.31 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417945E+09 | 19619.72 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43205725.06 | 9988.52 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9945352.00 | 11092.53 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177267E+09 | 19622.99 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.582009E+09 | 19640.84 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185563E+10 | 19709.13 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201034E+10 | 19716.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 184.69 | 0.62 | 20-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52.00 | 0.69 | 12-NOV-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 184.69 | 0.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.136806E+11 | 0.136806E+11 | 62636.63 | 02-JAN-15:00 | 62636.63 | 0.00 |
February | 0.00 | 0.00 | 0.132250E+11 | 0.132250E+11 | 71124.88 | 14-FEB-16:00 | 71124.88 | 0.00 |
March | 0.00 | 0.00 | 0.153233E+11 | 0.153233E+11 | 76602.50 | 08-MAR-16:00 | 76602.50 | 0.00 |
April | 0.00 | 0.00 | 0.360934E+11 | 0.360934E+11 | 110062.57 | 17-APR-15:20 | 110062.57 | 0.00 |
May | 0.00 | 0.00 | 0.540390E+11 | 0.540390E+11 | 113768.69 | 30-MAY-14:30 | 113768.69 | 0.08 |
June | 0.00 | 0.00 | 0.105332E+12 | 0.105330E+12 | 136600.14 | 26-JUN-15:00 | 136600.14 | 0.32 |
July | 0.00 | 0.00 | 0.134074E+12 | 0.130892E+12 | 145658.68 | 31-JUL-15:00 | 135643.99 | 0.78 |
August | 0.00 | 0.00 | 0.136749E+12 | 0.132991E+12 | 148895.67 | 21-AUG-10:50 | 130889.33 | 0.85 |
September | 0.00 | 0.00 | 0.779151E+11 | 0.767706E+11 | 158339.03 | 05-SEP-13:10 | 96556.82 | 0.44 |
October | 0.00 | 0.00 | 0.420163E+11 | 0.420092E+11 | 127568.32 | 10-OCT-12:15 | 124969.33 | 0.11 |
November | 0.00 | 0.00 | 0.115907E+11 | 0.115907E+11 | 56745.76 | 24-NOV-11:00 | 56745.76 | 0.00 |
December | 0.00 | 0.00 | 0.169081E+11 | 0.169081E+11 | 55327.36 | 29-DEC-15:40 | 55327.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.656947E+12 | 0.648852E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.115907E+11 | 0.115907E+11 | 55327.36 | 55327.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.136749E+12 | 0.132991E+12 | 158339.03 | 136600.14 | 0.85 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424281E+11 | 0.424281E+11 | 411635.42 | 05-JAN-15:40 | 411635.42 | 0.00 |
February | 0.00 | 0.00 | 0.634886E+11 | 0.634886E+11 | 658001.66 | 14-FEB-16:00 | 658001.66 | 0.00 |
March | 0.00 | 0.00 | 0.148008E+12 | 0.148008E+12 | 621194.07 | 08-MAR-14:10 | 621194.07 | 0.00 |
April | 0.00 | 0.00 | 0.278717E+12 | 0.278717E+12 | 904814.97 | 26-APR-15:10 | 904814.97 | 0.00 |
May | 0.00 | 0.00 | 0.469150E+12 | 0.469150E+12 | 1013259.37 | 19-MAY-15:10 | 1013259.37 | 0.08 |
June | 0.00 | 0.00 | 0.904054E+12 | 0.903958E+12 | 1289226.45 | 27-JUN-16:02 | 1289226.45 | 0.29 |
July | 0.00 | 0.00 | 0.109121E+13 | 0.107021E+13 | 1337885.84 | 16-JUL-14:41 | 1037029.46 | 0.61 |
August | 0.00 | 0.00 | 0.104038E+13 | 0.101967E+13 | 1345523.00 | 13-AUG-16:51 | 1049678.75 | 0.63 |
September | 0.00 | 0.00 | 0.683815E+12 | 0.674015E+12 | 1385870.39 | 05-SEP-14:05 | 909054.31 | 0.41 |
October | 0.00 | 0.00 | 0.362449E+12 | 0.362386E+12 | 983543.33 | 06-OCT-15:30 | 983543.33 | 0.10 |
November | 0.00 | 0.00 | 0.117053E+12 | 0.117053E+12 | 574197.73 | 02-NOV-15:20 | 574197.73 | 0.00 |
December | 0.00 | 0.00 | 0.123027E+11 | 0.123027E+11 | 318269.87 | 29-DEC-16:00 | 318269.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.521305E+13 | 0.516139E+13 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.123027E+11 | 0.123027E+11 | 318269.87 | 318269.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109121E+13 | 0.107021E+13 | 1385870.39 | 1289226.45 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.354229E+10 | 0.354229E+10 | 31967.33 | 23-JAN-15:40 | 31967.33 | 0.00 |
February | 0.00 | 0.00 | 0.518650E+10 | 0.518650E+10 | 67153.17 | 14-FEB-16:00 | 67153.17 | 0.00 |
March | 0.00 | 0.00 | 0.746871E+10 | 0.746871E+10 | 62786.56 | 08-MAR-16:00 | 62786.56 | 0.00 |
April | 0.00 | 0.00 | 0.283005E+11 | 0.283005E+11 | 110406.32 | 26-APR-15:10 | 110406.32 | 0.00 |
May | 0.00 | 0.00 | 0.514938E+11 | 0.514938E+11 | 123270.27 | 19-MAY-15:10 | 123270.27 | 0.07 |
June | 0.00 | 0.00 | 0.102822E+12 | 0.102818E+12 | 169441.78 | 28-JUN-13:45 | 169441.78 | 0.29 |
July | 0.00 | 0.00 | 0.124854E+12 | 0.122734E+12 | 163003.89 | 16-JUL-14:52 | 130299.27 | 0.61 |
August | 0.00 | 0.00 | 0.117512E+12 | 0.115493E+12 | 155771.56 | 13-AUG-15:51 | 130518.38 | 0.64 |
September | 0.00 | 0.00 | 0.740373E+11 | 0.732564E+11 | 152631.88 | 05-SEP-13:40 | 97095.72 | 0.40 |
October | 0.00 | 0.00 | 0.323835E+11 | 0.323835E+11 | 111923.64 | 06-OCT-15:20 | 111923.64 | 0.08 |
November | 0.00 | 0.00 | 0.706422E+10 | 0.706422E+10 | 52988.34 | 01-NOV-15:00 | 52988.34 | 0.00 |
December | 0.00 | 0.00 | 0.162538E+10 | 0.162538E+10 | 24458.62 | 29-DEC-15:40 | 24458.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.556290E+12 | 0.551366E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.162538E+10 | 0.162538E+10 | 24458.62 | 24458.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.124854E+12 | 0.122734E+12 | 169441.78 | 169441.78 | 0.64 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 18457435.52 | 18457435.52 | 3339.34 | 02-JAN-15:00 | 3339.34 | 0.00 |
February | 0.00 | 0.00 | 0.119837E+10 | 0.119837E+10 | 39196.42 | 13-FEB-16:00 | 39196.42 | 0.00 |
March | 0.00 | 0.00 | 0.321518E+10 | 0.321518E+10 | 39987.98 | 13-MAR-15:00 | 39987.98 | 0.00 |
April | 0.00 | 0.00 | 0.174706E+11 | 0.174706E+11 | 57713.25 | 17-APR-15:00 | 57713.25 | 0.00 |
May | 0.00 | 0.00 | 0.309356E+11 | 0.309298E+11 | 94731.19 | 29-MAY-15:50 | 94731.19 | 0.05 |
June | 0.00 | 0.00 | 0.576222E+11 | 0.576030E+11 | 73030.89 | 26-JUN-13:10 | 73030.89 | 0.24 |
July | 0.00 | 0.00 | 0.701967E+11 | 0.690645E+11 | 118991.52 | 02-JUL-19:12 | 76163.09 | 0.50 |
August | 0.00 | 0.00 | 0.708198E+11 | 0.697064E+11 | 99985.31 | 13-AUG-18:55 | 85544.96 | 0.55 |
September | 0.00 | 0.00 | 0.469623E+11 | 0.460654E+11 | 98256.65 | 05-SEP-13:00 | 64510.26 | 0.34 |
October | 0.00 | 0.00 | 0.218102E+11 | 0.217962E+11 | 95075.62 | 01-OCT-15:54 | 95075.62 | 0.09 |
November | 0.00 | 0.00 | 0.564812E+09 | 0.564812E+09 | 25530.23 | 09-NOV-05:12 | 25530.23 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.320814E+12 | 0.317633E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.708198E+11 | 0.697064E+11 | 118991.52 | 95075.62 | 0.55 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115745E+11 | 0.100176E+11 | 5618.33 | 11-JAN-12:40 | 4883.34 | 0.00 |
February | 0.00 | 0.00 | 0.157505E+11 | 0.142469E+11 | 105812.04 | 14-FEB-16:00 | 105812.04 | 0.00 |
March | 0.00 | 0.00 | 0.477436E+11 | 0.468015E+11 | 212529.09 | 08-MAR-16:00 | 212529.09 | 0.00 |
April | 0.00 | 0.00 | 0.278842E+12 | 0.276783E+12 | 354438.82 | 28-APR-14:40 | 354438.82 | 0.00 |
May | 0.00 | 0.00 | 0.687179E+11 | 0.664888E+11 | 145814.76 | 22-MAY-12:05 | 134521.58 | 0.00 |
June | 0.00 | 0.00 | 0.325364E+12 | 0.302496E+12 | 305988.88 | 30-JUN-14:00 | 218982.00 | 0.00 |
July | 0.00 | 0.00 | 0.821403E+12 | 0.638836E+12 | 449591.88 | 31-JUL-24:00 | 207613.41 | 0.00 |
August | 0.00 | 0.00 | 0.104110E+13 | 0.778230E+12 | 459378.07 | 26-AUG-10:00 | 196266.99 | 0.00 |
September | 0.00 | 0.00 | 0.974429E+11 | 0.876029E+11 | 169778.89 | 01-SEP-12:40 | 135865.09 | 0.00 |
October | 0.00 | 0.00 | 0.824924E+11 | 0.746700E+11 | 249340.04 | 10-OCT-13:30 | 225937.04 | 0.00 |
November | 0.00 | 0.00 | 0.186745E+11 | 0.173060E+11 | 130607.10 | 09-NOV-14:00 | 124468.89 | 0.00 |
December | 0.00 | 0.00 | 0.162912E+11 | 0.158461E+11 | 56730.98 | 24-DEC-14:52 | 56730.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.282540E+13 | 0.232932E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.115745E+11 | 0.100176E+11 | 5618.33 | 4883.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104110E+13 | 0.778230E+12 | 459378.07 | 354438.82 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.471219E+10 | 0.471149E+10 | 3067.73 | 01-JAN-16:43 | 3059.43 | 0.00 |
February | 0.00 | 0.00 | 0.919745E+10 | 0.919453E+10 | 4826.80 | 15-FEB-17:00 | 4826.80 | 0.00 |
March | 0.00 | 0.00 | 0.157024E+11 | 0.156968E+11 | 7734.10 | 31-MAR-24:00 | 7734.10 | 0.00 |
April | 0.00 | 0.00 | 0.204424E+11 | 0.204413E+11 | 8942.59 | 16-APR-18:34 | 8942.59 | 0.00 |
May | 0.00 | 0.00 | 0.607853E+10 | 0.603787E+10 | 4117.92 | 31-MAY-24:00 | 4117.92 | 0.00 |
June | 0.00 | 0.00 | 0.111594E+11 | 0.110705E+11 | 5999.20 | 30-JUN-23:55 | 5976.77 | 0.00 |
July | 0.00 | 0.00 | 0.167853E+11 | 0.165731E+11 | 7900.33 | 31-JUL-24:00 | 7900.33 | 0.00 |
August | 0.00 | 0.00 | 0.218094E+11 | 0.215886E+11 | 8637.73 | 23-AUG-18:10 | 8486.09 | 0.00 |
September | 0.00 | 0.00 | 0.619334E+10 | 0.604625E+10 | 4145.93 | 30-SEP-23:40 | 4118.18 | 0.00 |
October | 0.00 | 0.00 | 0.110533E+11 | 0.109949E+11 | 5928.57 | 31-OCT-24:00 | 5928.57 | 0.00 |
November | 0.00 | 0.00 | 0.151567E+11 | 0.151437E+11 | 7102.13 | 05-NOV-16:47 | 7102.13 | 0.00 |
December | 0.00 | 0.00 | 0.203871E+11 | 0.203870E+11 | 8850.02 | 31-DEC-16:40 | 8850.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158678E+12 | 0.157886E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.471219E+10 | 0.471149E+10 | 3067.73 | 3059.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218094E+11 | 0.215886E+11 | 8942.59 | 8942.59 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.280791E+11 | 0.280720E+11 | 25764.90 | 26-JAN-17:00 | 25764.90 | 0.00 |
February | 0.00 | 0.00 | 0.748152E+11 | 0.747858E+11 | 45813.12 | 15-FEB-17:00 | 45813.12 | 0.00 |
March | 0.00 | 0.00 | 0.140638E+12 | 0.140581E+12 | 71714.65 | 31-MAR-23:30 | 71714.65 | 0.00 |
April | 0.00 | 0.00 | 0.190807E+12 | 0.190796E+12 | 85261.24 | 16-APR-18:32 | 85261.24 | 0.00 |
May | 0.00 | 0.00 | 0.544659E+11 | 0.540668E+11 | 39010.16 | 31-MAY-24:00 | 39010.16 | 0.00 |
June | 0.00 | 0.00 | 0.104926E+12 | 0.104046E+12 | 57753.85 | 30-JUN-23:55 | 57531.22 | 0.00 |
July | 0.00 | 0.00 | 0.159759E+12 | 0.157648E+12 | 75820.97 | 31-JUL-24:00 | 75820.97 | 0.00 |
August | 0.00 | 0.00 | 0.206687E+12 | 0.204480E+12 | 82447.01 | 11-AUG-18:50 | 80446.09 | 0.00 |
September | 0.00 | 0.00 | 0.561411E+11 | 0.546986E+11 | 39223.54 | 30-SEP-23:30 | 38911.08 | 0.00 |
October | 0.00 | 0.00 | 0.989737E+11 | 0.983993E+11 | 54750.51 | 31-OCT-24:00 | 54750.51 | 0.00 |
November | 0.00 | 0.00 | 0.132910E+12 | 0.132781E+12 | 64833.84 | 02-NOV-16:40 | 63506.03 | 0.00 |
December | 0.00 | 0.00 | 0.176220E+12 | 0.176218E+12 | 79225.82 | 31-DEC-16:44 | 79225.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142442E+13 | 0.141657E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.280791E+11 | 0.280720E+11 | 25764.90 | 25764.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206687E+12 | 0.204480E+12 | 85261.24 | 85261.24 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.120934E+10 | 0.120879E+10 | 2485.54 | 26-JAN-17:00 | 2485.54 | 0.00 |
February | 0.00 | 0.00 | 0.605081E+10 | 0.604799E+10 | 4615.49 | 15-FEB-17:00 | 4615.49 | 0.00 |
March | 0.00 | 0.00 | 0.130809E+11 | 0.130754E+11 | 6845.25 | 31-MAR-23:10 | 6845.25 | 0.00 |
April | 0.00 | 0.00 | 0.186582E+11 | 0.186572E+11 | 8674.82 | 16-APR-18:13 | 8674.82 | 0.00 |
May | 0.00 | 0.00 | 0.528056E+10 | 0.524079E+10 | 3839.22 | 31-MAY-23:50 | 3839.22 | 0.00 |
June | 0.00 | 0.00 | 0.105334E+11 | 0.104455E+11 | 5775.65 | 30-JUN-23:55 | 5753.08 | 0.00 |
July | 0.00 | 0.00 | 0.161242E+11 | 0.159131E+11 | 7649.16 | 04-JUL-18:35 | 7649.16 | 0.00 |
August | 0.00 | 0.00 | 0.207702E+11 | 0.205494E+11 | 8379.37 | 11-AUG-18:40 | 8192.40 | 0.00 |
September | 0.00 | 0.00 | 0.553402E+10 | 0.538983E+10 | 3885.85 | 30-SEP-23:20 | 3851.77 | 0.00 |
October | 0.00 | 0.00 | 0.923069E+10 | 0.917342E+10 | 5262.76 | 31-OCT-23:30 | 5262.76 | 0.00 |
November | 0.00 | 0.00 | 0.118498E+11 | 0.118371E+11 | 6489.22 | 02-NOV-16:40 | 6356.14 | 0.00 |
December | 0.00 | 0.00 | 0.156214E+11 | 0.156213E+11 | 7769.75 | 29-DEC-16:50 | 7769.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133944E+12 | 0.133160E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.120934E+10 | 0.120879E+10 | 2485.54 | 2485.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207702E+11 | 0.205494E+11 | 8674.82 | 8674.82 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 74977.26 | 1229366.37 | 10-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 52113.80 | 1192916.36 | 27-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15887.73 | 1145481.60 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2858.23 | 629936.32 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 489.59 | 134716.11 | 05-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1.79 | 2838.51 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 6.77 | 09-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 8633.94 | 1065878.44 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22031.89 | 1066778.21 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 72426.96 | 1174565.01 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 20687.19 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 74977.26 | 1229366.37 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22860.92 | 479995.28 | 05-JAN-15:40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 36371.86 | 1062182.34 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 67119.52 | 947522.32 | 08-MAR-14:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 145565.40 | 1446973.85 | 13-APR-14:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 236151.94 | 1452098.34 | 30-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 464394.89 | 1850813.53 | 06-JUN-13:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 546297.40 | 1853066.72 | 12-JUL-08:07 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 521872.87 | 1839978.66 | 03-AUG-09:08 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 348444.50 | 1873869.57 | 06-SEP-12:12 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 177899.58 | 1810146.58 | 02-OCT-12:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 53368.97 | 753496.34 | 02-NOV-15:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 12331.06 | 392310.41 | 29-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 220526.46 | 0.00 | ||||
Minimum of Months | 12331.06 | 392310.41 | 0.00 | 0.00 | ||
Maximum of Months | 546297.40 | 1873869.57 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22212.40 | 479617.80 | 05-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 35580.92 | 1044577.88 | 14-FEB-16:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66252.73 | 970402.54 | 08-MAR-14:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 144188.65 | 1322338.95 | 13-APR-13:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 235974.53 | 1474829.95 | 23-MAY-12:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 465702.98 | 2044869.54 | 06-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 552484.96 | 2200110.14 | 12-JUL-08:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 532481.98 | 2341310.86 | 01-AUG-08:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 363023.78 | 2247441.14 | 01-SEP-09:53 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 184448.54 | 2167363.78 | 10-OCT-12:07 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 52556.51 | 757765.74 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 11488.70 | 390270.39 | 29-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 223359.13 | 0.00 | ||||
Minimum of Months | 11488.70 | 390270.39 | 0.00 | 0.00 | ||
Maximum of Months | 552484.96 | 2341310.86 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25763.97 | 49246.84 | 26-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 62136.20 | 538903.62 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 121944.50 | 842947.96 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 392941.65 | 1390265.82 | 13-APR-17:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 216604.12 | 1019301.66 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 680756.67 | 1806184.34 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1203956.00 | 2022089.35 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1325769.31 | 2072883.92 | 20-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 301957.33 | 1168998.30 | 03-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 182384.97 | 1208925.38 | 01-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 90288.83 | 460562.27 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109740.36 | 181618.25 | 24-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 395860.84 | 0.00 | ||||
Minimum of Months | 25763.97 | 49246.84 | 0.00 | 0.00 | ||
Maximum of Months | 1325769.31 | 2072883.92 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15581.27 | 52447.37 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15778.51 | 52458.71 | 08-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16292.89 | 51957.18 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14621.26 | 49724.30 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14109.50 | 46880.35 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13485.02 | 43452.71 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11962.68 | 40713.30 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 12836.86 | 39976.52 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 12495.17 | 41921.77 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13223.47 | 45147.79 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14324.10 | 48422.91 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14685.68 | 51046.98 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 14106.92 | ||||
Minimum of Months | 0.00 | 0.00 | 11962.68 | 39976.52 | ||
Maximum of Months | 0.00 | 0.00 | 16292.89 | 52458.71 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21607.77 | 555959.29 | 05-JAN-15:40 | 3898.01 | 128409.15 | 10-JAN-09:50 |
February | 35469.94 | 1292825.42 | 14-FEB-16:00 | 5002.42 | 128033.09 | 06-FEB-12:30 |
March | 73106.18 | 1059687.74 | 08-MAR-14:20 | 2604.14 | 116181.67 | 04-MAR-12:20 |
April | 174794.81 | 2027489.73 | 11-APR-14:30 | 3029.21 | 126786.43 | 01-APR-05:50 |
May | 290828.63 | 2124038.42 | 19-MAY-14:40 | 620.14 | 77210.93 | 20-MAY-07:10 |
June | 606568.62 | 2379964.36 | 06-JUN-13:05 | 884.77 | 73834.14 | 18-JUN-01:00 |
July | 738327.89 | 3126609.55 | 31-JUL-15:00 | 737.28 | 40345.34 | 19-JUL-00:10 |
August | 681791.27 | 2664131.28 | 18-AUG-08:23 | 1684.01 | 57064.61 | 31-AUG-02:00 |
September | 463172.81 | 3038768.30 | 05-SEP-13:00 | 476.45 | 57608.02 | 11-SEP-05:40 |
October | 224406.73 | 2123962.01 | 06-OCT-15:30 | 2023.72 | 125358.04 | 26-OCT-09:30 |
November | 58097.62 | 862020.62 | 02-NOV-15:20 | 2590.88 | 118831.07 | 25-NOV-09:00 |
December | 5515.06 | 458034.53 | 29-DEC-16:00 | 7532.38 | 129528.54 | 23-DEC-12:50 |
Annual Sum or Average | 282671.96 | 2579.72 | ||||
Minimum of Months | 5515.06 | 458034.53 | 476.45 | 40345.34 | ||
Maximum of Months | 738327.89 | 3126609.55 | 7532.38 | 129528.54 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154422E+11 | 0.97 | 10037.91 | 01-JAN-00:20 | 1.69 |
February | 0.137664E+11 | 0.96 | 10037.91 | 01-FEB-05:01 | 1.70 |
March | 0.158047E+11 | 1.00 | 10037.91 | 01-MAR-05:01 | 1.69 |
April | 0.143341E+11 | 0.93 | 10037.91 | 01-APR-04:13 | 1.70 |
May | 0.155642E+11 | 0.98 | 10037.91 | 01-MAY-01:50 | 1.69 |
June | 0.154042E+11 | 1.00 | 10037.91 | 01-JUN-04:12 | 1.68 |
July | 0.155917E+11 | 0.97 | 10037.91 | 01-JUL-04:11 | 1.67 |
August | 0.169317E+11 | 1.05 | 10037.91 | 01-AUG-04:12 | 1.68 |
September | 0.158132E+11 | 1.02 | 10037.91 | 01-SEP-04:12 | 1.68 |
October | 0.162292E+11 | 1.02 | 10037.91 | 01-OCT-14:58 | 1.68 |
November | 0.149738E+11 | 0.97 | 10037.91 | 01-NOV-04:12 | 1.69 |
December | 0.152062E+11 | 0.96 | 10037.91 | 01-DEC-05:12 | 1.69 |
Annual Sum or Average | 0.185062E+12 | 0.99 | |||
Minimum of Months | 0.137664E+11 | 0.93 | 10037.91 | 1.67 | |
Maximum of Months | 0.169317E+11 | 1.05 | 10037.91 | 1.70 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.446726E+10 | 0.41 | 11547.03 | 17-JAN-06:01 | 1.39 |
February | 0.498824E+10 | 0.43 | 12551.01 | 06-FEB-06:01 | 1.47 |
March | 0.799877E+10 | 0.53 | 13667.29 | 15-MAR-16:00 | 1.55 |
April | 0.112989E+11 | 0.68 | 19013.19 | 17-APR-15:20 | 1.90 |
May | 0.998391E+10 | 0.60 | 23045.58 | 22-MAY-04:12 | 2.13 |
June | 0.133522E+11 | 0.76 | 23045.58 | 06-JUN-12:50 | 2.12 |
July | 0.154452E+11 | 0.86 | 23045.58 | 01-JUL-04:11 | 2.12 |
August | 0.171349E+11 | 0.93 | 23045.58 | 01-AUG-05:02 | 2.12 |
September | 0.975204E+10 | 0.60 | 23045.58 | 01-SEP-09:43 | 2.12 |
October | 0.848389E+10 | 0.54 | 23045.58 | 02-OCT-09:47 | 2.12 |
November | 0.677547E+10 | 0.49 | 13334.38 | 20-NOV-16:20 | 1.52 |
December | 0.582564E+10 | 0.44 | 11277.98 | 26-DEC-16:00 | 1.37 |
Annual Sum or Average | 0.115506E+12 | 0.61 | |||
Minimum of Months | 0.446726E+10 | 0.41 | 11277.98 | 1.37 | |
Maximum of Months | 0.171349E+11 | 0.93 | 23045.58 | 2.13 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.309362E+11 | 0.39 | 51964.98 | 05-JAN-16:40 | 0.91 |
February | 0.310654E+11 | 0.39 | 122251.52 | 17-FEB-06:02 | 1.50 |
March | 0.446403E+11 | 0.43 | 98395.06 | 11-MAR-06:02 | 1.32 |
April | 0.642226E+11 | 0.50 | 133631.87 | 28-APR-15:10 | 1.59 |
May | 0.778650E+11 | 0.54 | 167245.76 | 22-MAY-05:03 | 1.82 |
June | 0.104827E+12 | 0.65 | 215768.56 | 06-JUN-12:45 | 2.13 |
July | 0.115953E+12 | 0.67 | 215768.56 | 01-JUL-05:02 | 2.13 |
August | 0.114866E+12 | 0.67 | 215768.56 | 01-AUG-05:02 | 2.13 |
September | 0.765439E+11 | 0.54 | 215768.56 | 01-SEP-09:43 | 2.13 |
October | 0.560359E+11 | 0.46 | 215768.56 | 10-OCT-12:03 | 2.13 |
November | 0.373209E+11 | 0.40 | 94837.46 | 30-NOV-06:02 | 1.29 |
December | 0.307005E+11 | 0.38 | 86120.62 | 02-DEC-06:02 | 1.22 |
Annual Sum or Average | 0.784977E+12 | 0.50 | |||
Minimum of Months | 0.307005E+11 | 0.38 | 51964.98 | 0.91 | |
Maximum of Months | 0.115953E+12 | 0.67 | 215768.56 | 2.13 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.328712E+10 | 0.45 | 5363.42 | 02-JAN-05:01 | 0.87 |
February | 0.297801E+10 | 0.42 | 7309.60 | 15-FEB-16:50 | 1.03 |
March | 0.381862E+10 | 0.44 | 8432.45 | 08-MAR-16:00 | 1.12 |
April | 0.573428E+10 | 0.46 | 15683.89 | 26-APR-15:10 | 1.63 |
May | 0.746259E+10 | 0.51 | 17661.82 | 30-MAY-14:30 | 1.74 |
June | 0.110461E+11 | 0.63 | 24315.89 | 06-JUN-12:50 | 2.12 |
July | 0.125217E+11 | 0.66 | 24315.89 | 05-JUL-04:12 | 2.13 |
August | 0.120987E+11 | 0.65 | 24315.89 | 14-AUG-04:12 | 2.12 |
September | 0.751084E+10 | 0.51 | 24315.89 | 12-SEP-11:10 | 2.12 |
October | 0.481473E+10 | 0.43 | 20719.28 | 02-OCT-12:03 | 1.92 |
November | 0.317808E+10 | 0.41 | 6579.36 | 03-NOV-15:50 | 0.97 |
December | 0.320340E+10 | 0.43 | 5363.42 | 04-DEC-05:11 | 0.87 |
Annual Sum or Average | 0.776542E+11 | 0.50 | |||
Minimum of Months | 0.297801E+10 | 0.41 | 5363.42 | 0.87 | |
Maximum of Months | 0.125217E+11 | 0.66 | 24315.89 | 2.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114335E+12 | 1.64 | 42687.62 | 01-JAN-00:05 | 1.64 |
February | 0.103270E+12 | 1.64 | 42687.62 | 01-FEB-00:10 | 1.64 |
March | 0.114335E+12 | 1.65 | 42687.62 | 01-MAR-00:10 | 1.64 |
April | 0.110646E+12 | 1.65 | 42687.62 | 01-APR-00:10 | 1.64 |
May | 0.114335E+12 | 1.64 | 42687.62 | 01-MAY-00:10 | 1.65 |
June | 0.110646E+12 | 1.63 | 42687.62 | 01-JUN-00:10 | 1.64 |
July | 0.114335E+12 | 1.63 | 42687.62 | 01-JUL-00:10 | 1.63 |
August | 0.114335E+12 | 1.63 | 42687.62 | 01-AUG-00:05 | 1.62 |
September | 0.110646E+12 | 1.63 | 42687.62 | 01-SEP-00:07 | 1.63 |
October | 0.114335E+12 | 1.64 | 42687.62 | 01-OCT-00:10 | 1.64 |
November | 0.110646E+12 | 1.64 | 42687.62 | 01-NOV-00:10 | 1.65 |
December | 0.114335E+12 | 1.65 | 42687.62 | 01-DEC-00:10 | 1.64 |
Annual Sum or Average | 0.134620E+13 | 1.64 | |||
Minimum of Months | 0.103270E+12 | 1.63 | 42687.62 | 1.62 | |
Maximum of Months | 0.114335E+12 | 1.65 | 42687.62 | 1.65 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173388E+10 | 1.12 | 647.36 | 01-JAN-00:05 | 1.11 |
February | 0.156609E+10 | 1.12 | 647.36 | 01-FEB-00:10 | 1.12 |
March | 0.173388E+10 | 1.12 | 647.36 | 01-MAR-00:10 | 1.12 |
April | 0.167795E+10 | 1.12 | 647.36 | 01-APR-00:10 | 1.12 |
May | 0.173388E+10 | 1.11 | 647.36 | 01-MAY-00:10 | 1.12 |
June | 0.167795E+10 | 1.11 | 647.36 | 01-JUN-00:10 | 1.12 |
July | 0.173388E+10 | 1.11 | 647.36 | 01-JUL-00:10 | 1.11 |
August | 0.173388E+10 | 1.11 | 647.36 | 01-AUG-00:05 | 1.11 |
September | 0.167795E+10 | 1.11 | 647.36 | 01-SEP-00:03 | 1.11 |
October | 0.173388E+10 | 1.11 | 647.36 | 01-OCT-00:10 | 1.11 |
November | 0.167795E+10 | 1.12 | 647.36 | 01-NOV-00:10 | 1.12 |
December | 0.173388E+10 | 1.12 | 647.36 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.204151E+11 | 1.11 | |||
Minimum of Months | 0.156609E+10 | 1.11 | 647.36 | 1.11 | |
Maximum of Months | 0.173388E+10 | 1.12 | 647.36 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166168E+11 | 1.12 | 6204.02 | 01-JAN-00:10 | 1.11 |
February | 0.150088E+11 | 1.12 | 6204.02 | 01-FEB-00:10 | 1.12 |
March | 0.166168E+11 | 1.12 | 6204.02 | 01-MAR-00:10 | 1.12 |
April | 0.160808E+11 | 1.12 | 6204.02 | 01-APR-00:10 | 1.12 |
May | 0.166168E+11 | 1.11 | 6204.02 | 01-MAY-00:10 | 1.12 |
June | 0.160808E+11 | 1.11 | 6204.02 | 01-JUN-00:10 | 1.12 |
July | 0.166168E+11 | 1.11 | 6204.02 | 01-JUL-00:10 | 1.11 |
August | 0.166168E+11 | 1.11 | 6204.02 | 01-AUG-00:05 | 1.11 |
September | 0.160808E+11 | 1.11 | 6204.02 | 01-SEP-00:03 | 1.11 |
October | 0.166168E+11 | 1.11 | 6204.02 | 01-OCT-00:10 | 1.11 |
November | 0.160808E+11 | 1.12 | 6204.02 | 01-NOV-00:10 | 1.12 |
December | 0.166168E+11 | 1.12 | 6204.02 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.195650E+12 | 1.11 | |||
Minimum of Months | 0.150088E+11 | 1.11 | 6204.02 | 1.11 | |
Maximum of Months | 0.166168E+11 | 1.12 | 6204.02 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169724E+10 | 1.12 | 633.68 | 01-JAN-00:05 | 1.11 |
February | 0.153299E+10 | 1.12 | 633.68 | 01-FEB-00:10 | 1.12 |
March | 0.169724E+10 | 1.12 | 633.68 | 01-MAR-00:10 | 1.12 |
April | 0.164249E+10 | 1.12 | 633.68 | 01-APR-00:10 | 1.12 |
May | 0.169724E+10 | 1.11 | 633.68 | 01-MAY-00:10 | 1.12 |
June | 0.164249E+10 | 1.11 | 633.68 | 01-JUN-00:20 | 1.12 |
July | 0.169724E+10 | 1.11 | 633.68 | 01-JUL-00:10 | 1.11 |
August | 0.169724E+10 | 1.11 | 633.68 | 01-AUG-00:05 | 1.11 |
September | 0.164249E+10 | 1.11 | 633.68 | 01-SEP-00:07 | 1.11 |
October | 0.169724E+10 | 1.11 | 633.68 | 01-OCT-00:10 | 1.11 |
November | 0.164249E+10 | 1.12 | 633.68 | 01-NOV-00:10 | 1.12 |
December | 0.169724E+10 | 1.12 | 633.68 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.199836E+11 | 1.11 | |||
Minimum of Months | 0.153299E+10 | 1.11 | 633.68 | 1.11 | |
Maximum of Months | 0.169724E+10 | 1.12 | 633.68 | 1.12 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 55540010.16 | 50485869.23 | 1116.58 | 17-JAN-06:01 | 1014.97 | 1014.97 | 46.15 | 15.01 |
February | 28422642.89 | 25836182.39 | 1120.09 | 06-FEB-06:01 | 1018.16 | 1018.16 | 45.94 | 15.04 |
March | 5115169.30 | 4649688.90 | 904.40 | 06-MAR-06:01 | 822.10 | 822.10 | 39.97 | 13.68 |
April | 686150.84 | 623711.12 | 203.90 | 08-APR-05:03 | 185.34 | 185.34 | 37.41 | 6.67 |
May | 86370.89 | 78511.14 | 10.63 | 05-MAY-05:02 | 9.66 | 9.66 | 30.99 | 1.11 |
June | 242.79 | 220.70 | 0.15 | 09-JUN-06:10 | 0.14 | 0.14 | 31.67 | 0.02 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 31.63 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 31.63 | 0.00 |
September | 0.11 | 0.10 | 0.00 | 09-SEP-06:10 | 0.00 | 0.00 | 31.63 | 0.00 |
October | 3138317.89 | 2852730.96 | 829.90 | 26-OCT-05:02 | 754.38 | 754.38 | 40.61 | 13.15 |
November | 8108855.04 | 7370949.23 | 1018.30 | 28-NOV-06:01 | 925.63 | 925.63 | 42.31 | 14.43 |
December | 50151719.15 | 45587912.71 | 1083.90 | 22-DEC-06:01 | 985.27 | 985.27 | 43.90 | 14.83 |
Annual Sum or Average | 0.151249E+09 | 0.137486E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 | 0.00 | |
Maximum of Months | 55540010.16 | 50485869.23 | 1120.09 | 1018.16 | 1018.16 | 46.15 | 15.04 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 16448623.86 | 14951799.09 | 235.02 | 05-JAN-15:05 | 213.64 | 213.64 | 6.70 | 11.55 |
February | 40935814.88 | 37210655.72 | 1366.49 | 14-FEB-16:30 | 1242.14 | 1242.14 | 6.81 | 26.09 |
March | 68864902.91 | 62598196.75 | 1080.56 | 08-MAR-14:20 | 982.23 | 982.23 | 6.71 | 23.54 |
April | 0.184652E+09 | 0.167848E+09 | 2040.08 | 13-APR-13:40 | 1854.43 | 1854.43 | 9.98 | 30.98 |
May | 0.401231E+09 | 0.364719E+09 | 5328.30 | 29-MAY-16:31 | 4843.42 | 4843.42 | 7.58 | 46.06 |
June | 0.198862E+10 | 0.180766E+10 | 9375.28 | 06-JUN-12:45 | 8522.13 | 8522.13 | 10.59 | 57.65 |
July | 0.234852E+10 | 0.213480E+10 | 9375.28 | 01-JUL-05:02 | 8522.13 | 8522.13 | 9.36 | 57.65 |
August | 0.254081E+10 | 0.230959E+10 | 9375.28 | 03-AUG-08:52 | 8522.13 | 8522.13 | 10.19 | 57.65 |
September | 0.201061E+10 | 0.182765E+10 | 9375.28 | 01-SEP-09:43 | 8522.13 | 8522.13 | 10.43 | 57.65 |
October | 0.731953E+09 | 0.665346E+09 | 9375.28 | 02-OCT-09:47 | 8522.13 | 8522.13 | 9.89 | 57.65 |
November | 52486261.95 | 47710012.11 | 2355.44 | 02-NOV-16:00 | 2141.10 | 2141.10 | 7.27 | 32.93 |
December | 5409315.79 | 4917068.05 | 173.94 | 29-DEC-15:50 | 158.11 | 158.11 | 6.70 | 9.94 |
Annual Sum or Average | 0.103905E+11 | 0.944500E+10 | ||||||
Minimum of Months | 5409315.79 | 4917068.05 | 173.94 | 158.11 | 158.11 | 6.70 | 9.94 | |
Maximum of Months | 0.254081E+10 | 0.230959E+10 | 9375.28 | 8522.13 | 8522.13 | 10.59 | 57.65 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.195331E+10 | 0.177556E+10 | 3226.38 | 01-JAN-12:31 | 2932.78 | 2932.78 | 6.74 | 28.83 |
February | 0.214248E+10 | 0.194752E+10 | 3226.38 | 01-FEB-10:50 | 2932.78 | 2932.78 | 6.75 | 28.83 |
March | 0.276484E+10 | 0.251324E+10 | 3226.38 | 01-MAR-08:10 | 2932.78 | 2932.78 | 6.76 | 28.83 |
April | 0.378746E+10 | 0.344280E+10 | 3226.38 | 01-APR-05:03 | 2932.78 | 2932.78 | 6.72 | 28.83 |
May | 0.437272E+10 | 0.397480E+10 | 3226.38 | 01-MAY-04:12 | 2932.78 | 2932.78 | 6.92 | 28.83 |
June | 0.612664E+10 | 0.556912E+10 | 3226.38 | 01-JUN-04:12 | 2932.78 | 2932.78 | 9.68 | 28.83 |
July | 0.750135E+10 | 0.681873E+10 | 3226.38 | 01-JUL-00:55 | 2932.78 | 2932.78 | 6.91 | 28.83 |
August | 0.783808E+10 | 0.712481E+10 | 3226.38 | 01-AUG-00:05 | 2932.78 | 2932.78 | 6.86 | 28.83 |
September | 0.525323E+10 | 0.477519E+10 | 3226.38 | 01-SEP-00:15 | 2932.78 | 2932.78 | 6.88 | 28.83 |
October | 0.410837E+10 | 0.373451E+10 | 3226.38 | 01-OCT-06:53 | 2932.78 | 2932.78 | 6.91 | 28.83 |
November | 0.249939E+10 | 0.227194E+10 | 3226.38 | 01-NOV-04:12 | 2932.78 | 2932.78 | 6.93 | 28.83 |
December | 0.249118E+10 | 0.226448E+10 | 3226.38 | 01-DEC-06:05 | 2932.78 | 2932.78 | 6.79 | 28.83 |
Annual Sum or Average | 0.508391E+11 | 0.462127E+11 | ||||||
Minimum of Months | 0.195331E+10 | 0.177556E+10 | 3226.38 | 2932.78 | 2932.78 | 6.72 | 28.83 | |
Maximum of Months | 0.783808E+10 | 0.712481E+10 | 3226.38 | 2932.78 | 2932.78 | 9.68 | 28.83 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.74 | 0.00 |
February | 3871652.31 | 3519331.95 | 3226.38 | 14-FEB-16:00 | 2932.78 | 2932.78 | 15.51 | 14.41 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.77 | 0.00 |
April | 0.287470E+09 | 0.261310E+09 | 3226.38 | 11-APR-13:30 | 2932.78 | 2932.78 | 15.46 | 14.41 |
May | 0.642694E+09 | 0.584209E+09 | 3226.38 | 08-MAY-12:20 | 2932.78 | 2932.78 | 15.12 | 14.41 |
June | 0.198364E+10 | 0.180313E+10 | 3226.38 | 02-JUN-14:10 | 2932.78 | 2932.78 | 15.91 | 14.41 |
July | 0.241498E+10 | 0.219521E+10 | 3226.38 | 01-JUL-10:50 | 2932.78 | 2932.78 | 15.11 | 14.41 |
August | 0.220481E+10 | 0.200417E+10 | 3226.38 | 01-AUG-08:07 | 2932.78 | 2932.78 | 14.49 | 14.41 |
September | 0.122457E+10 | 0.111314E+10 | 3226.38 | 01-SEP-09:53 | 2932.78 | 2932.78 | 15.43 | 14.41 |
October | 0.408524E+09 | 0.371348E+09 | 3226.38 | 02-OCT-11:00 | 2932.78 | 2932.78 | 15.28 | 14.41 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 7.03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.84 | 0.00 |
Annual Sum or Average | 0.917056E+10 | 0.833604E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 | |
Maximum of Months | 0.241498E+10 | 0.219521E+10 | 3226.38 | 2932.78 | 2932.78 | 15.91 | 14.41 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.982631E+10 | 0.893211E+10 | 3668.72 | 01-JAN-00:05 | 3334.87 | 3334.87 | 18.78 | 15.48 |
February | 0.887537E+10 | 0.806771E+10 | 3668.72 | 01-FEB-00:10 | 3334.87 | 3334.87 | 19.29 | 15.48 |
March | 0.982631E+10 | 0.893211E+10 | 3668.72 | 01-MAR-00:10 | 3334.87 | 3334.87 | 19.91 | 15.48 |
April | 0.950933E+10 | 0.864398E+10 | 3668.72 | 01-APR-00:10 | 3334.87 | 3334.87 | 20.53 | 15.48 |
May | 0.982631E+10 | 0.893211E+10 | 3668.72 | 01-MAY-00:10 | 3334.87 | 3334.87 | 19.15 | 15.48 |
June | 0.950933E+10 | 0.864398E+10 | 3668.72 | 01-JUN-00:10 | 3334.87 | 3334.87 | 20.47 | 15.48 |
July | 0.982631E+10 | 0.893211E+10 | 3668.72 | 01-JUL-00:10 | 3334.87 | 3334.87 | 34.35 | 15.48 |
August | 0.982631E+10 | 0.893211E+10 | 3668.72 | 01-AUG-00:05 | 3334.87 | 3334.87 | 40.89 | 15.48 |
September | 0.950933E+10 | 0.864398E+10 | 3668.72 | 01-SEP-00:03 | 3334.87 | 3334.87 | 23.91 | 15.48 |
October | 0.982631E+10 | 0.893211E+10 | 3668.72 | 01-OCT-00:10 | 3334.87 | 3334.87 | 19.54 | 15.48 |
November | 0.950933E+10 | 0.864398E+10 | 3668.72 | 01-NOV-00:10 | 3334.87 | 3334.87 | 20.05 | 15.48 |
December | 0.982631E+10 | 0.893211E+10 | 3668.72 | 01-DEC-00:10 | 3334.87 | 3334.87 | 20.41 | 15.48 |
Annual Sum or Average | 0.115697E+12 | 0.105168E+12 | ||||||
Minimum of Months | 0.887537E+10 | 0.806771E+10 | 3668.72 | 3334.87 | 3334.87 | 18.78 | 15.48 | |
Maximum of Months | 0.982631E+10 | 0.893211E+10 | 3668.72 | 3334.87 | 3334.87 | 40.89 | 15.48 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.36 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 55.95 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.47 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 55.68 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 55.72 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 55.92 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.53 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.76 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.27 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.57 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 55.90 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 55.62 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.36 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.76 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.769614E+10 | 0.699580E+10 | 12732.20 | 05-JAN-15:40 | 11573.57 | 11573.57 | 23.66 | 52.02 |
February | 0.845006E+10 | 0.768110E+10 | 25472.14 | 14-FEB-16:00 | 23154.18 | 23154.18 | 24.07 | 104.04 |
March | 0.108988E+11 | 0.990699E+10 | 12754.93 | 08-MAR-14:20 | 11594.24 | 11594.24 | 25.97 | 52.02 |
April | 0.159100E+11 | 0.144622E+11 | 25505.40 | 11-APR-14:30 | 23184.41 | 23184.41 | 25.76 | 104.04 |
May | 0.192285E+11 | 0.174787E+11 | 25510.15 | 19-MAY-14:40 | 23188.72 | 23188.72 | 25.99 | 104.04 |
June | 0.313998E+11 | 0.285424E+11 | 25522.74 | 06-JUN-13:05 | 23200.17 | 23200.17 | 26.57 | 104.04 |
July | 0.388785E+11 | 0.353406E+11 | 25559.54 | 31-JUL-15:00 | 23233.62 | 23233.62 | 28.29 | 104.04 |
August | 0.393499E+11 | 0.357690E+11 | 25536.73 | 18-AUG-08:23 | 23212.89 | 23212.89 | 27.23 | 104.04 |
September | 0.252472E+11 | 0.229497E+11 | 25555.21 | 05-SEP-13:00 | 23229.68 | 23229.68 | 28.09 | 104.04 |
October | 0.177070E+11 | 0.160957E+11 | 25510.14 | 06-OCT-15:30 | 23188.72 | 23188.72 | 25.98 | 104.04 |
November | 0.985123E+10 | 0.895476E+10 | 12745.20 | 02-NOV-15:20 | 11585.39 | 11585.39 | 25.07 | 52.02 |
December | 0.981262E+10 | 0.891967E+10 | 12728.07 | 29-DEC-16:00 | 11569.82 | 11569.82 | 23.21 | 52.02 |
Annual Sum or Average | 0.234430E+12 | 0.213097E+12 | ||||||
Minimum of Months | 0.769614E+10 | 0.699580E+10 | 12728.07 | 11569.82 | 11569.82 | 23.21 | 52.02 | |
Maximum of Months | 0.393499E+11 | 0.357690E+11 | 25559.54 | 23233.62 | 23233.62 | 28.29 | 104.04 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 37.37 | 37.37 | 74977.26 | 1229366.37 | 10-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 42.10 | 42.10 | 52113.80 | 1192916.36 | 27-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 35.94 | 35.94 | 15887.73 | 1145481.60 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34.41 | 34.41 | 2858.23 | 629936.32 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 32.65 | 32.65 | 489.59 | 134716.11 | 05-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 31.71 | 31.71 | 1.79 | 2838.51 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.63 | 31.63 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 31.63 | 31.63 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.63 | 31.63 | 0.00 | 6.77 | 09-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 31.63 | 31.63 | 8633.94 | 1065878.44 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 35.20 | 35.20 | 22031.89 | 1066778.21 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33.21 | 33.21 | 72426.96 | 1174565.01 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 20687.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 31.63 | 31.63 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 42.10 | 42.10 | 74977.26 | 1229366.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22860.92 | 479995.28 | 05-JAN-15:40 | 10.67 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 36371.86 | 1062182.34 | 14-FEB-16:00 | 15.51 | 9.99 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 67119.52 | 947522.32 | 08-MAR-14:20 | 14.55 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 145565.40 | 1446973.85 | 13-APR-14:05 | 12.69 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 236151.94 | 1452098.34 | 30-MAY-12:05 | 12.71 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 464394.89 | 1850813.53 | 06-JUN-13:05 | 14.37 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 546297.40 | 1853066.72 | 12-JUL-08:07 | 14.38 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 521872.87 | 1839978.66 | 03-AUG-09:08 | 14.32 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 348444.50 | 1873869.57 | 06-SEP-12:12 | 14.47 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 177899.58 | 1810146.58 | 02-OCT-12:03 | 14.20 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 53368.97 | 753496.34 | 02-NOV-15:10 | 12.94 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 12331.06 | 392310.41 | 29-DEC-15:50 | 9.95 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 220526.46 | 0.00 | ||||||
Minimum of Months | 12331.06 | 392310.41 | 9.95 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 546297.40 | 1873869.57 | 15.51 | 9.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22212.40 | 479617.80 | 05-JAN-15:05 | 16.62 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 35580.92 | 1044577.88 | 14-FEB-16:30 | 16.27 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66252.73 | 970402.54 | 08-MAR-14:20 | 16.55 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 144188.65 | 1322338.95 | 13-APR-13:40 | 16.90 | 10.20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 235974.53 | 1474829.95 | 23-MAY-12:10 | 14.58 | 10.24 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 465702.98 | 2044869.54 | 06-JUN-13:00 | 15.18 | 12.01 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 552484.96 | 2200110.14 | 12-JUL-08:05 | 15.82 | 11.98 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 532481.98 | 2341310.86 | 01-AUG-08:10 | 16.72 | 13.04 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 363023.78 | 2247441.14 | 01-SEP-09:53 | 16.02 | 12.21 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 184448.54 | 2167363.78 | 10-OCT-12:07 | 15.68 | 11.18 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 52556.51 | 757765.74 | 02-NOV-15:00 | 16.14 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 11488.70 | 390270.39 | 29-DEC-15:50 | 16.09 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 223359.13 | 0.00 | ||||||
Minimum of Months | 11488.70 | 390270.39 | 14.58 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 552484.96 | 2341310.86 | 16.90 | 13.04 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25763.97 | 49246.84 | 26-JAN-17:00 | 19.25 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 62136.20 | 538903.62 | 14-FEB-16:00 | 28.29 | 24.40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 121944.50 | 842947.96 | 08-MAR-16:00 | 33.83 | 26.80 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 392941.65 | 1390265.82 | 13-APR-17:00 | 43.65 | 32.52 | 0.00 | 0.00 | 01-APR-00:10 |
May | 216604.12 | 1019301.66 | 19-MAY-16:00 | 37.02 | 32.55 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 680756.67 | 1806184.34 | 28-JUN-16:00 | 51.00 | 43.36 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1203956.00 | 2022089.35 | 22-JUL-15:00 | 54.78 | 44.39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1325769.31 | 2072883.92 | 20-AUG-16:00 | 55.67 | 42.65 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 301957.33 | 1168998.30 | 03-SEP-14:00 | 39.71 | 35.32 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 182384.97 | 1208925.38 | 01-OCT-16:00 | 40.42 | 33.10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 90288.83 | 460562.27 | 09-NOV-14:00 | 26.85 | 22.08 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109740.36 | 181618.25 | 24-DEC-15:00 | 21.71 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 395860.84 | 0.00 | ||||||
Minimum of Months | 25763.97 | 49246.84 | 19.25 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1325769.31 | 2072883.92 | 55.67 | 44.39 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.74 | 56.74 | 15581.27 | 52447.37 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.39 | 56.39 | 15778.51 | 52458.71 | 08-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.00 | 57.00 | 16292.89 | 51957.18 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.31 | 56.31 | 14621.26 | 49724.30 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.50 | 56.50 | 14109.50 | 46880.35 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.57 | 56.57 | 13485.02 | 43452.71 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.94 | 56.94 | 11962.68 | 40713.30 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.15 | 57.15 | 12836.86 | 39976.52 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.71 | 56.71 | 12495.17 | 41921.77 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.44 | 57.44 | 13223.47 | 45147.79 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.40 | 56.40 | 14324.10 | 48422.91 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.34 | 56.34 | 14685.68 | 51046.98 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 14106.92 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.31 | 56.31 | 11962.68 | 39976.52 | ||
Maximum of Months | 0.00 | 0.00 | 57.44 | 57.44 | 16292.89 | 52458.71 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21607.77 | 555959.29 | 05-JAN-15:40 | 23.66 | 21.10 | 3898.01 | 128409.15 | 10-JAN-09:50 |
February | 35469.94 | 1292825.42 | 14-FEB-16:00 | 24.07 | 22.56 | 5002.42 | 128033.09 | 06-FEB-12:30 |
March | 73106.18 | 1059687.74 | 08-MAR-14:20 | 25.97 | 21.10 | 2604.14 | 116181.67 | 04-MAR-12:20 |
April | 174794.81 | 2027489.73 | 11-APR-14:30 | 25.76 | 21.10 | 3029.21 | 126786.43 | 01-APR-05:50 |
May | 290828.63 | 2124038.42 | 19-MAY-14:40 | 25.99 | 21.10 | 620.14 | 77210.93 | 20-MAY-07:10 |
June | 606568.62 | 2379964.36 | 06-JUN-13:05 | 26.57 | 21.92 | 884.77 | 73834.14 | 18-JUN-01:00 |
July | 738327.89 | 3126609.55 | 31-JUL-15:00 | 28.29 | 23.89 | 737.28 | 40345.34 | 19-JUL-00:10 |
August | 681791.27 | 2664131.28 | 18-AUG-08:23 | 27.23 | 22.18 | 1684.01 | 57064.61 | 31-AUG-02:00 |
September | 463172.81 | 3038768.30 | 05-SEP-13:00 | 28.09 | 23.39 | 476.45 | 57608.02 | 11-SEP-05:40 |
October | 224406.73 | 2123962.01 | 06-OCT-15:30 | 25.98 | 21.10 | 2023.72 | 125358.04 | 26-OCT-09:30 |
November | 58097.62 | 862020.62 | 02-NOV-15:20 | 25.07 | 21.10 | 2590.88 | 118831.07 | 25-NOV-09:00 |
December | 5515.06 | 458034.53 | 29-DEC-16:00 | 23.21 | 21.10 | 7532.38 | 129528.54 | 23-DEC-12:50 |
Annual Sum or Average | 282671.96 | 2579.72 | ||||||
Minimum of Months | 5515.06 | 458034.53 | 23.21 | 21.10 | 476.45 | 40345.34 | ||
Maximum of Months | 738327.89 | 3126609.55 | 28.29 | 23.89 | 7532.38 | 129528.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.927132E+10 | 0.00 | 0.136806E+11 | 0.446726E+10 | 0.00 | 0.00 |
February | 0.518108E+10 | 0.00 | 0.132250E+11 | 0.498824E+10 | 0.00 | 0.00 |
March | 0.144497E+10 | 0.00 | 0.153233E+11 | 0.799877E+10 | 0.00 | 0.00 |
April | 0.114426E+09 | 0.00 | 0.360934E+11 | 0.112989E+11 | 0.00 | 0.00 |
May | 40142865.92 | 0.00 | 0.540390E+11 | 0.998391E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.105332E+12 | 0.133522E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.134074E+12 | 0.154452E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.136749E+12 | 0.171349E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.779151E+11 | 0.975204E+10 | 0.00 | 0.00 |
October | 0.880872E+09 | 0.00 | 0.420163E+11 | 0.848389E+10 | 0.00 | 0.00 |
November | 0.180846E+10 | 0.00 | 0.115907E+11 | 0.677547E+10 | 0.00 | 0.00 |
December | 0.657829E+10 | 0.00 | 0.169081E+11 | 0.582564E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.253196E+11 | 0.00 | 0.656947E+12 | 0.115506E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.115907E+11 | 0.446726E+10 | 0.00 | 0.00 |
Maximum of Months | 0.927132E+10 | 0.00 | 0.136749E+12 | 0.171349E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.161757E+12 | 0.00 | 0.424281E+11 | 0.309362E+11 | 0.00 | 0.00 |
February | 0.102322E+12 | 0.00 | 0.634886E+11 | 0.310654E+11 | 0.00 | 0.00 |
March | 0.339516E+11 | 0.00 | 0.148008E+12 | 0.446403E+11 | 0.00 | 0.00 |
April | 0.580067E+10 | 0.00 | 0.278717E+12 | 0.642226E+11 | 0.00 | 0.00 |
May | 0.989020E+09 | 0.00 | 0.469150E+12 | 0.778650E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.904054E+12 | 0.104827E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109121E+13 | 0.115953E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.104038E+13 | 0.114866E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.683815E+12 | 0.765439E+11 | 0.00 | 0.00 |
October | 0.184755E+11 | 0.00 | 0.362449E+12 | 0.560359E+11 | 0.00 | 0.00 |
November | 0.450001E+11 | 0.00 | 0.117053E+12 | 0.373209E+11 | 0.00 | 0.00 |
December | 0.157690E+12 | 0.00 | 0.123027E+11 | 0.307005E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.525986E+12 | 0.00 | 0.521305E+13 | 0.784977E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.123027E+11 | 0.307005E+11 | 0.00 | 0.00 |
Maximum of Months | 0.161757E+12 | 0.00 | 0.109121E+13 | 0.115953E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.300303E+11 | 0.00 | 0.354229E+10 | 0.328712E+10 | 0.00 | 0.00 |
February | 0.188106E+11 | 0.00 | 0.518650E+10 | 0.297801E+10 | 0.00 | 0.00 |
March | 0.722864E+10 | 0.00 | 0.746871E+10 | 0.381862E+10 | 0.00 | 0.00 |
April | 0.152123E+10 | 0.00 | 0.283005E+11 | 0.573428E+10 | 0.00 | 0.00 |
May | 0.293626E+09 | 0.00 | 0.514938E+11 | 0.746259E+10 | 0.00 | 0.00 |
June | 5460098.22 | 0.00 | 0.102822E+12 | 0.110461E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.124854E+12 | 0.125217E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.117512E+12 | 0.120987E+11 | 0.00 | 0.00 |
September | 3087.49 | 0.00 | 0.740373E+11 | 0.751084E+10 | 0.00 | 0.00 |
October | 0.376199E+10 | 0.00 | 0.323835E+11 | 0.481473E+10 | 0.00 | 0.00 |
November | 0.103945E+11 | 0.00 | 0.706422E+10 | 0.317808E+10 | 0.00 | 0.00 |
December | 0.299919E+11 | 0.00 | 0.162538E+10 | 0.320340E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102038E+12 | 0.00 | 0.556290E+12 | 0.776542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.162538E+10 | 0.297801E+10 | 0.00 | 0.00 |
Maximum of Months | 0.300303E+11 | 0.00 | 0.124854E+12 | 0.125217E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 18457435.52 | 0.154422E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.119837E+10 | 0.137664E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.321518E+10 | 0.158047E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.174706E+11 | 0.143341E+11 | 0.00 | 0.00 |
May | 184.69 | 0.00 | 0.309356E+11 | 0.155642E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.576222E+11 | 0.154042E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.701967E+11 | 0.155917E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.708198E+11 | 0.169317E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.469623E+11 | 0.158132E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.218102E+11 | 0.162292E+11 | 0.00 | 0.00 |
November | 52.00 | 0.00 | 0.564812E+09 | 0.149738E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152062E+11 | 0.00 | 0.00 |
Annual Sum or Average | 236.70 | 0.00 | 0.320814E+12 | 0.185062E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.137664E+11 | 0.00 | 0.00 |
Maximum of Months | 184.69 | 0.00 | 0.708198E+11 | 0.169317E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.170624E+11 | 0.325041E+12 | 0.00 | 76.34 |
February | 0.00 | 0.00 | 0.224761E+11 | 0.347298E+12 | 0.00 | 88.28 |
March | 0.00 | 0.00 | 0.650635E+11 | 0.398290E+12 | 0.00 | 99.19 |
April | 0.00 | 0.00 | 0.372423E+12 | 0.463277E+12 | 0.00 | 96.37 |
May | 0.00 | 0.00 | 0.942989E+11 | 0.326828E+12 | 0.00 | 69.53 |
June | 0.00 | 0.00 | 0.440054E+12 | 0.332049E+12 | 0.00 | 39.70 |
July | 0.00 | 0.00 | 0.108569E+13 | 0.404454E+12 | 0.00 | 9.61 |
August | 0.00 | 0.00 | 0.135891E+13 | 0.515463E+12 | 0.00 | 30.99 |
September | 0.00 | 0.00 | 0.132172E+12 | 0.207353E+12 | 0.00 | 23.06 |
October | 0.00 | 0.00 | 0.110696E+12 | 0.356947E+12 | 0.00 | 79.76 |
November | 0.00 | 0.00 | 0.266045E+11 | 0.375587E+12 | 0.00 | 95.61 |
December | 0.00 | 0.00 | 0.240709E+11 | 0.389954E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.374953E+13 | 0.444254E+13 | 0.00 | 808.06 |
Minimum of Months | 0.00 | 0.00 | 0.170624E+11 | 0.207353E+12 | 0.00 | 9.61 |
Maximum of Months | 0.00 | 0.00 | 0.135891E+13 | 0.515463E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.591550E+10 | 0.293720E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.113985E+11 | 0.376711E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193105E+11 | 0.534206E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.253468E+11 | 0.658231E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.773614E+10 | 0.339149E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.145052E+11 | 0.502369E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.221688E+11 | 0.711737E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.284906E+11 | 0.841501E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.789409E+10 | 0.337870E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.137656E+11 | 0.444619E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.185895E+11 | 0.511074E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.249466E+11 | 0.629334E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200068E+12 | 0.618052E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.591550E+10 | 0.293720E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.284906E+11 | 0.841501E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.355254E+11 | 0.240631E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.929836E+11 | 0.331771E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.173226E+12 | 0.492046E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.236824E+12 | 0.620981E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.694488E+11 | 0.315997E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136514E+12 | 0.476681E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211054E+12 | 0.679117E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.270165E+12 | 0.800947E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.716693E+11 | 0.316090E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123467E+12 | 0.411106E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.163323E+12 | 0.464943E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.216184E+12 | 0.565814E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180038E+13 | 0.571612E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.355254E+11 | 0.240631E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.270165E+12 | 0.800947E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.154035E+10 | 0.202825E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.754470E+10 | 0.302688E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.161426E+11 | 0.475891E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.231930E+11 | 0.617729E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.674721E+10 | 0.316388E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.137216E+11 | 0.483066E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.213161E+11 | 0.688918E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.271711E+11 | 0.809821E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.707734E+10 | 0.318581E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115402E+11 | 0.400670E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.145982E+11 | 0.439090E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.192230E+11 | 0.529884E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169816E+12 | 0.558555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.154035E+10 | 0.202825E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.271711E+11 | 0.809821E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.446726E+10 | 0.136806E+11 | 0.927132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498824E+10 | 0.132250E+11 | 0.518108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.799877E+10 | 0.153233E+11 | 0.144497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112989E+11 | 0.360934E+11 | 0.114426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.998391E+10 | 0.540390E+11 | 40142865.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133522E+11 | 0.105332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154452E+11 | 0.134074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171349E+11 | 0.136749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.975204E+10 | 0.779151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848389E+10 | 0.420163E+11 | 0.880872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.677547E+10 | 0.115907E+11 | 0.180846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582564E+10 | 0.169081E+11 | 0.657829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115506E+12 | 0.656947E+12 | 0.253196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.446726E+10 | 0.115907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171349E+11 | 0.136749E+12 | 0.927132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.309362E+11 | 0.424281E+11 | 0.161757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310654E+11 | 0.634886E+11 | 0.102322E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446403E+11 | 0.148008E+12 | 0.339516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642226E+11 | 0.278717E+12 | 0.580067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.778650E+11 | 0.469150E+12 | 0.989020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104827E+12 | 0.904054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115953E+12 | 0.109121E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114866E+12 | 0.104038E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.765439E+11 | 0.683815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560359E+11 | 0.362449E+12 | 0.184755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373209E+11 | 0.117053E+12 | 0.450001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307005E+11 | 0.123027E+11 | 0.157690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784977E+12 | 0.521305E+13 | 0.525986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307005E+11 | 0.123027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115953E+12 | 0.109121E+13 | 0.161757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.328712E+10 | 0.354229E+10 | 0.300303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297801E+10 | 0.518650E+10 | 0.188106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381862E+10 | 0.746871E+10 | 0.722864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573428E+10 | 0.283005E+11 | 0.152123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746259E+10 | 0.514938E+11 | 0.293626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110461E+11 | 0.102822E+12 | 5460098.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125217E+11 | 0.124854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120987E+11 | 0.117512E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.751084E+10 | 0.740373E+11 | 3087.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481473E+10 | 0.323835E+11 | 0.376199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317808E+10 | 0.706422E+10 | 0.103945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320340E+10 | 0.162538E+10 | 0.299919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776542E+11 | 0.556290E+12 | 0.102038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.297801E+10 | 0.162538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125217E+11 | 0.124854E+12 | 0.300303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154422E+11 | 18457435.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137664E+11 | 0.119837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158047E+11 | 0.321518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143341E+11 | 0.174706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155642E+11 | 0.309356E+11 | 184.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154042E+11 | 0.576222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155917E+11 | 0.701967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169317E+11 | 0.708198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158132E+11 | 0.469623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162292E+11 | 0.218102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149738E+11 | 0.564812E+09 | 52.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185062E+12 | 0.320814E+12 | 236.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169317E+11 | 0.708198E+11 | 184.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114335E+12 | 0.115745E+11 | 0.00 | 0.00 | 0.00 | 0.204299E+12 | 0.00 | 0.00 |
February | 0.103270E+12 | 0.157505E+11 | 0.00 | 0.00 | 0.00 | 0.236239E+12 | 0.00 | 0.00 |
March | 0.114335E+12 | 0.477436E+11 | 0.00 | 0.00 | 0.00 | 0.265440E+12 | 0.00 | 0.00 |
April | 0.110646E+12 | 0.278842E+12 | 0.00 | 0.00 | 0.00 | 0.257889E+12 | 0.00 | 0.00 |
May | 0.114335E+12 | 0.687179E+11 | 0.00 | 0.00 | 0.00 | 0.186075E+12 | 0.00 | 0.00 |
June | 0.110646E+12 | 0.325364E+12 | 0.00 | 0.00 | 0.00 | 0.106234E+12 | 0.00 | 0.00 |
July | 0.114335E+12 | 0.821403E+12 | 0.00 | 0.00 | 0.00 | 0.257148E+11 | 0.00 | 0.00 |
August | 0.114335E+12 | 0.104110E+13 | 0.00 | 0.00 | 0.00 | 0.829440E+11 | 0.00 | 0.00 |
September | 0.110646E+12 | 0.974429E+11 | 0.00 | 0.00 | 0.00 | 0.616991E+11 | 0.00 | 0.00 |
October | 0.114335E+12 | 0.824924E+11 | 0.00 | 0.00 | 0.00 | 0.213448E+12 | 0.00 | 0.00 |
November | 0.110646E+12 | 0.186745E+11 | 0.00 | 0.00 | 0.00 | 0.255859E+12 | 0.00 | 0.00 |
December | 0.114335E+12 | 0.162912E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.134620E+13 | 0.282540E+13 | 0.00 | 0.00 | 0.00 | 0.216248E+13 | 0.00 | 0.00 |
Minimum of Months | 0.103270E+12 | 0.115745E+11 | 0.00 | 0.00 | 0.00 | 0.257148E+11 | 0.00 | 0.00 |
Maximum of Months | 0.114335E+12 | 0.104110E+13 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173388E+10 | 0.471219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156609E+10 | 0.919745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173388E+10 | 0.157024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167795E+10 | 0.204424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173388E+10 | 0.607853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167795E+10 | 0.111594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173388E+10 | 0.167853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173388E+10 | 0.218094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167795E+10 | 0.619334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173388E+10 | 0.110533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167795E+10 | 0.151567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173388E+10 | 0.203871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204151E+11 | 0.158678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156609E+10 | 0.471219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173388E+10 | 0.218094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166168E+11 | 0.280791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150088E+11 | 0.748152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166168E+11 | 0.140638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160808E+11 | 0.190807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166168E+11 | 0.544659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160808E+11 | 0.104926E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166168E+11 | 0.159759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166168E+11 | 0.206687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160808E+11 | 0.561411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166168E+11 | 0.989737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160808E+11 | 0.132910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166168E+11 | 0.176220E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195650E+12 | 0.142442E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150088E+11 | 0.280791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166168E+11 | 0.206687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169724E+10 | 0.120934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153299E+10 | 0.605081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169724E+10 | 0.130809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164249E+10 | 0.186582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169724E+10 | 0.528056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164249E+10 | 0.105334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169724E+10 | 0.161242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169724E+10 | 0.207702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164249E+10 | 0.553402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169724E+10 | 0.923069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164249E+10 | 0.118498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169724E+10 | 0.156214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199836E+11 | 0.133944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153299E+10 | 0.120934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169724E+10 | 0.207702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.446726E+10 | 0.927132E+10 | 0.136806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498824E+10 | 0.518108E+10 | 0.132250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.799877E+10 | 0.144497E+10 | 0.153233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112989E+11 | 0.114426E+09 | 0.360934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.998391E+10 | 40142865.92 | 0.540390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133522E+11 | 0.00 | 0.105332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154452E+11 | 0.00 | 0.134074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171349E+11 | 0.00 | 0.136749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.975204E+10 | 0.00 | 0.779151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848389E+10 | 0.880872E+09 | 0.420163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.677547E+10 | 0.180846E+10 | 0.115907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582564E+10 | 0.657829E+10 | 0.169081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115506E+12 | 0.253196E+11 | 0.656947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.446726E+10 | 0.00 | 0.115907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171349E+11 | 0.927132E+10 | 0.136749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.309362E+11 | 0.161757E+12 | 0.424281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310654E+11 | 0.102322E+12 | 0.634886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446403E+11 | 0.339516E+11 | 0.148008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642226E+11 | 0.580067E+10 | 0.278717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.778650E+11 | 0.989020E+09 | 0.469150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104827E+12 | 0.00 | 0.904054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115953E+12 | 0.00 | 0.109121E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114866E+12 | 0.00 | 0.104038E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.765439E+11 | 0.00 | 0.683815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560359E+11 | 0.184755E+11 | 0.362449E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373209E+11 | 0.450001E+11 | 0.117053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307005E+11 | 0.157690E+12 | 0.123027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784977E+12 | 0.525986E+12 | 0.521305E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307005E+11 | 0.00 | 0.123027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115953E+12 | 0.161757E+12 | 0.109121E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.328712E+10 | 0.300303E+11 | 0.354229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297801E+10 | 0.188106E+11 | 0.518650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381862E+10 | 0.722864E+10 | 0.746871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573428E+10 | 0.152123E+10 | 0.283005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746259E+10 | 0.293626E+09 | 0.514938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110461E+11 | 5460098.22 | 0.102822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125217E+11 | 0.00 | 0.124854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120987E+11 | 0.00 | 0.117512E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.751084E+10 | 3087.49 | 0.740373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481473E+10 | 0.376199E+10 | 0.323835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317808E+10 | 0.103945E+11 | 0.706422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320340E+10 | 0.299919E+11 | 0.162538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776542E+11 | 0.102038E+12 | 0.556290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.297801E+10 | 0.00 | 0.162538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125217E+11 | 0.300303E+11 | 0.124854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154422E+11 | 0.00 | 18457435.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137664E+11 | 0.00 | 0.119837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158047E+11 | 0.00 | 0.321518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143341E+11 | 0.00 | 0.174706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155642E+11 | 184.69 | 0.309356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154042E+11 | 0.00 | 0.576222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155917E+11 | 0.00 | 0.701967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169317E+11 | 0.00 | 0.708198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158132E+11 | 0.00 | 0.469623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162292E+11 | 0.00 | 0.218102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149738E+11 | 52.00 | 0.564812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185062E+12 | 236.70 | 0.320814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169317E+11 | 184.69 | 0.708198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114335E+12 | 0.00 | 0.170624E+11 | 0.00 | 0.548796E+10 | 0.00 | 0.00 | 0.00 | 0.205218E+12 | 0.00 | 0.00 | 0.00 |
February | 0.103270E+12 | 0.00 | 0.224761E+11 | 0.00 | 0.672561E+10 | 0.00 | 0.00 | 0.00 | 0.237303E+12 | 0.00 | 0.00 | 0.00 |
March | 0.114335E+12 | 0.00 | 0.650635E+11 | 0.00 | 0.173199E+11 | 0.00 | 0.00 | 0.00 | 0.266635E+12 | 0.00 | 0.00 | 0.00 |
April | 0.110646E+12 | 0.00 | 0.372423E+12 | 0.00 | 0.935809E+11 | 0.00 | 0.00 | 0.00 | 0.259050E+12 | 0.00 | 0.00 | 0.00 |
May | 0.114335E+12 | 0.00 | 0.942989E+11 | 0.00 | 0.255810E+11 | 0.00 | 0.00 | 0.00 | 0.186913E+12 | 0.00 | 0.00 | 0.00 |
June | 0.110646E+12 | 0.00 | 0.440054E+12 | 0.00 | 0.114690E+12 | 0.00 | 0.00 | 0.00 | 0.106712E+12 | 0.00 | 0.00 | 0.00 |
July | 0.114335E+12 | 0.00 | 0.108569E+13 | 0.00 | 0.264289E+12 | 0.00 | 0.00 | 0.00 | 0.258306E+11 | 0.00 | 0.00 | 0.00 |
August | 0.114335E+12 | 0.00 | 0.135891E+13 | 0.00 | 0.317811E+12 | 0.00 | 0.00 | 0.00 | 0.833174E+11 | 0.00 | 0.00 | 0.00 |
September | 0.110646E+12 | 0.00 | 0.132172E+12 | 0.00 | 0.347296E+11 | 0.00 | 0.00 | 0.00 | 0.619768E+11 | 0.00 | 0.00 | 0.00 |
October | 0.114335E+12 | 0.00 | 0.110696E+12 | 0.00 | 0.282037E+11 | 0.00 | 0.00 | 0.00 | 0.214409E+12 | 0.00 | 0.00 | 0.00 |
November | 0.110646E+12 | 0.00 | 0.266045E+11 | 0.00 | 0.792998E+10 | 0.00 | 0.00 | 0.00 | 0.257011E+12 | 0.00 | 0.00 | 0.00 |
December | 0.114335E+12 | 0.00 | 0.240709E+11 | 0.00 | 0.777972E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134620E+13 | 0.00 | 0.374953E+13 | 0.00 | 0.924129E+12 | 0.00 | 0.00 | 0.00 | 0.217222E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103270E+12 | 0.00 | 0.170624E+11 | 0.00 | 0.548796E+10 | 0.00 | 0.00 | 0.00 | 0.258306E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114335E+12 | 0.00 | 0.135891E+13 | 0.00 | 0.317811E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173388E+10 | 0.00 | 0.591550E+10 | 0.00 | 0.120332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156609E+10 | 0.00 | 0.113985E+11 | 0.00 | 0.220102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173388E+10 | 0.00 | 0.193105E+11 | 0.00 | 0.360817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167795E+10 | 0.00 | 0.253468E+11 | 0.00 | 0.490436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173388E+10 | 0.00 | 0.773614E+10 | 0.00 | 0.165761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167795E+10 | 0.00 | 0.145052E+11 | 0.00 | 0.334574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173388E+10 | 0.00 | 0.221688E+11 | 0.00 | 0.538348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173388E+10 | 0.00 | 0.284906E+11 | 0.00 | 0.668112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167795E+10 | 0.00 | 0.789409E+10 | 0.00 | 0.170074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173388E+10 | 0.00 | 0.137656E+11 | 0.00 | 0.271231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167795E+10 | 0.00 | 0.185895E+11 | 0.00 | 0.343279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173388E+10 | 0.00 | 0.249466E+11 | 0.00 | 0.455946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204151E+11 | 0.00 | 0.200068E+12 | 0.00 | 0.413901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156609E+10 | 0.00 | 0.591550E+10 | 0.00 | 0.120332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173388E+10 | 0.00 | 0.284906E+11 | 0.00 | 0.668112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166168E+11 | 0.00 | 0.355254E+11 | 0.00 | 0.744626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150088E+11 | 0.00 | 0.929836E+11 | 0.00 | 0.181683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166168E+11 | 0.00 | 0.173226E+12 | 0.00 | 0.325877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160808E+11 | 0.00 | 0.236824E+12 | 0.00 | 0.460173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166168E+11 | 0.00 | 0.694488E+11 | 0.00 | 0.149828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160808E+11 | 0.00 | 0.136514E+12 | 0.00 | 0.315872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166168E+11 | 0.00 | 0.211054E+12 | 0.00 | 0.512948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166168E+11 | 0.00 | 0.270165E+12 | 0.00 | 0.634778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160808E+11 | 0.00 | 0.716693E+11 | 0.00 | 0.155281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166168E+11 | 0.00 | 0.123467E+12 | 0.00 | 0.244937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160808E+11 | 0.00 | 0.163323E+12 | 0.00 | 0.304135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166168E+11 | 0.00 | 0.216184E+12 | 0.00 | 0.399646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195650E+12 | 0.00 | 0.180038E+13 | 0.00 | 0.375962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150088E+11 | 0.00 | 0.355254E+11 | 0.00 | 0.744626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166168E+11 | 0.00 | 0.270165E+12 | 0.00 | 0.634778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169724E+10 | 0.00 | 0.154035E+10 | 0.00 | 0.331011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153299E+10 | 0.00 | 0.754470E+10 | 0.00 | 0.149390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169724E+10 | 0.00 | 0.161426E+11 | 0.00 | 0.306167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164249E+10 | 0.00 | 0.231930E+11 | 0.00 | 0.453480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169724E+10 | 0.00 | 0.674721E+10 | 0.00 | 0.146665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164249E+10 | 0.00 | 0.137216E+11 | 0.00 | 0.318818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169724E+10 | 0.00 | 0.213161E+11 | 0.00 | 0.519195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169724E+10 | 0.00 | 0.271711E+11 | 0.00 | 0.640098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164249E+10 | 0.00 | 0.707734E+10 | 0.00 | 0.154332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169724E+10 | 0.00 | 0.115402E+11 | 0.00 | 0.230947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164249E+10 | 0.00 | 0.145982E+11 | 0.00 | 0.274841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169724E+10 | 0.00 | 0.192230E+11 | 0.00 | 0.360161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199836E+11 | 0.00 | 0.169816E+12 | 0.00 | 0.358719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153299E+10 | 0.00 | 0.154035E+10 | 0.00 | 0.331011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169724E+10 | 0.00 | 0.271711E+11 | 0.00 | 0.640098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.419942E+09 | 0.00 | 0.00 | 0.118206E+09 | 0.00 | 0.00 | 0.663469E+11 | 0.00 | 0.69 |
February | 0.320309E+09 | 0.00 | 0.00 | 0.101054E+09 | 0.00 | 0.00 | 0.587514E+11 | 0.00 | 0.75 |
March | 0.202045E+09 | 0.00 | 0.00 | 0.115807E+09 | 0.00 | 0.00 | 0.689486E+11 | 0.00 | 1.11 |
April | 0.138312E+09 | 12010968.59 | 0.00 | 0.107060E+09 | 92380.29 | 0.00 | 0.512622E+11 | 0.00 | 1.23 |
May | 99197827.28 | 0.116953E+09 | 0.00 | 0.105706E+09 | 11282055.77 | 0.00 | 0.415534E+11 | 0.00 | 1.22 |
June | 65359274.94 | 0.246718E+10 | 0.00 | 69316483.44 | 24779392.57 | 0.00 | 0.190659E+11 | 0.00 | 0.94 |
July | 0.121681E+09 | 0.289520E+10 | 0.00 | 64492146.08 | 58631896.69 | 0.00 | 0.851950E+10 | 0.00 | 0.81 |
August | 73651145.40 | 0.174860E+10 | 0.00 | 98708024.02 | 46314257.18 | 0.00 | 0.160740E+11 | 0.00 | 1.02 |
September | 0.144897E+09 | 0.352603E+09 | 0.00 | 0.110632E+09 | 11592704.35 | 0.00 | 0.291933E+11 | 0.00 | 1.22 |
October | 0.217580E+09 | 10204226.89 | 0.00 | 0.134747E+09 | 0.00 | 0.00 | 0.570027E+11 | 0.00 | 1.27 |
November | 0.372063E+09 | 0.00 | 0.00 | 0.130174E+09 | 0.00 | 0.00 | 0.730615E+11 | 0.00 | 0.98 |
December | 0.505999E+09 | 0.00 | 0.00 | 0.133574E+09 | 0.00 | 0.00 | 0.705533E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.268104E+10 | 0.760275E+10 | 0.00 | 0.128948E+10 | 0.152693E+09 | 0.00 | 0.560333E+12 | 0.00 | 0.99 |
Minimum of Months | 65359274.94 | 0.00 | 0.00 | 64492146.08 | 0.00 | 0.00 | 0.851950E+10 | 0.00 | 0.65 |
Maximum of Months | 0.505999E+09 | 0.289520E+10 | 0.00 | 0.134747E+09 | 58631896.69 | 0.00 | 0.730615E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263519E+10 | 0.00 | 0.00 | 74927953.90 | 0.00 | 0.00 | 0.399403E+11 | 0.00 | 0.38 |
February | 0.196044E+10 | 0.00 | 0.00 | 76341951.84 | 0.00 | 0.00 | 0.382813E+11 | 0.00 | 0.47 |
March | 0.252769E+10 | 0.00 | 0.00 | 0.100938E+09 | 0.00 | 0.00 | 0.509365E+11 | 0.00 | 0.79 |
April | 0.559100E+10 | 2143506.79 | 0.00 | 98457167.14 | 0.00 | 0.00 | 0.423967E+11 | 0.00 | 1.04 |
May | 0.183895E+10 | 48507978.19 | 0.00 | 87809122.02 | 16709862.25 | 0.00 | 0.313753E+11 | 0.00 | 0.88 |
June | 0.244581E+10 | 0.988169E+09 | 0.00 | 66232728.07 | 0.116272E+09 | 0.00 | 0.145280E+11 | 0.00 | 0.73 |
July | 0.347066E+10 | 0.130372E+10 | 0.00 | 50840418.20 | 0.334896E+09 | 0.00 | 0.504880E+10 | 0.00 | 0.67 |
August | 0.524003E+10 | 0.843622E+09 | 0.00 | 83441190.23 | 0.114863E+09 | 0.00 | 0.113483E+11 | 0.00 | 0.90 |
September | 0.151027E+10 | 0.281241E+09 | 0.00 | 84969577.30 | 16706009.14 | 0.00 | 0.201202E+11 | 0.00 | 0.79 |
October | 0.319220E+10 | 328962.94 | 0.00 | 99548537.16 | 791731.77 | 0.00 | 0.375237E+11 | 0.00 | 0.80 |
November | 0.327550E+10 | 0.00 | 0.00 | 97370129.11 | 0.00 | 0.00 | 0.484936E+11 | 0.00 | 0.66 |
December | 0.263658E+10 | 0.00 | 0.00 | 0.100145E+09 | 0.00 | 0.00 | 0.449131E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.363243E+11 | 0.346774E+10 | 0.00 | 0.102102E+10 | 0.600239E+09 | 0.00 | 0.384906E+12 | 0.00 | 0.71 |
Minimum of Months | 0.151027E+10 | 0.00 | 0.00 | 50840418.20 | 0.00 | 0.00 | 0.504880E+10 | 0.00 | 0.38 |
Maximum of Months | 0.559100E+10 | 0.130372E+10 | 0.00 | 0.100938E+09 | 0.334896E+09 | 0.00 | 0.509365E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179910E+12 | 0.00 | 0.00 | 0.237746E+09 | 0.00 | 0.00 | 0.170591E+12 | 0.00 | 0.33 |
February | 0.120056E+12 | 0.00 | 0.00 | 0.284473E+09 | 0.00 | 0.00 | 0.184520E+12 | 0.00 | 0.35 |
March | 0.476347E+11 | 0.00 | 0.00 | 0.518299E+09 | 0.00 | 0.00 | 0.289044E+12 | 0.00 | 0.48 |
April | 0.271731E+11 | 18758673.68 | 0.00 | 0.610887E+09 | 0.00 | 0.00 | 0.269646E+12 | 0.00 | 0.66 |
May | 0.164327E+11 | 0.452268E+09 | 0.00 | 0.691555E+09 | 0.184396E+09 | 0.00 | 0.248986E+12 | 0.00 | 0.72 |
June | 0.986832E+10 | 0.110743E+11 | 0.00 | 0.512869E+09 | 0.426294E+09 | 0.00 | 0.111056E+12 | 0.00 | 0.56 |
July | 0.616791E+10 | 0.130167E+11 | 0.00 | 0.419243E+09 | 0.190858E+10 | 0.00 | 0.382626E+11 | 0.00 | 0.45 |
August | 0.772000E+10 | 0.718015E+10 | 0.00 | 0.658571E+09 | 0.926448E+09 | 0.00 | 0.879863E+11 | 0.00 | 0.58 |
September | 0.118151E+11 | 0.237499E+10 | 0.00 | 0.668019E+09 | 0.146196E+09 | 0.00 | 0.155593E+12 | 0.00 | 0.64 |
October | 0.344419E+11 | 0.00 | 0.00 | 0.646907E+09 | 11656163.71 | 0.00 | 0.246605E+12 | 0.00 | 0.56 |
November | 0.641399E+11 | 0.00 | 0.00 | 0.441892E+09 | 0.00 | 0.00 | 0.248359E+12 | 0.00 | 0.38 |
December | 0.167210E+12 | 0.00 | 0.00 | 0.251998E+09 | 0.00 | 0.00 | 0.192095E+12 | 0.00 | 0.32 |
Annual Sum or Average | 0.692570E+12 | 0.341172E+11 | 0.00 | 0.594246E+10 | 0.360357E+10 | 0.00 | 0.224274E+13 | 0.00 | 0.50 |
Minimum of Months | 0.616791E+10 | 0.00 | 0.00 | 0.237746E+09 | 0.00 | 0.00 | 0.382626E+11 | 0.00 | 0.32 |
Maximum of Months | 0.179910E+12 | 0.130167E+11 | 0.00 | 0.691555E+09 | 0.190858E+10 | 0.00 | 0.289044E+12 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250906E+11 | 0.00 | 0.00 | 2325170.66 | 0.00 | 0.116369E+10 | 0.258967E+10 | 0.00 | 0.30 |
February | 0.191487E+11 | 0.00 | 0.00 | 6565748.07 | 0.00 | 0.465096E+09 | 0.530109E+10 | 0.00 | 0.31 |
March | 0.125383E+11 | 0.00 | 0.00 | 24451722.60 | 0.00 | 51456448.77 | 0.180005E+11 | 0.00 | 0.47 |
April | 0.516899E+10 | 0.00 | 0.00 | 45450960.22 | 0.00 | 0.00 | 0.220384E+11 | 0.00 | 0.66 |
May | 0.325342E+10 | 20313737.33 | 0.00 | 60925836.82 | 28236469.70 | 0.00 | 0.218963E+11 | 0.00 | 0.73 |
June | 0.143750E+10 | 0.738392E+09 | 0.00 | 57857578.07 | 39516185.59 | 0.00 | 0.100400E+11 | 0.00 | 0.57 |
July | 0.759924E+09 | 0.822668E+09 | 0.00 | 56789553.30 | 0.176977E+09 | 0.00 | 0.371032E+10 | 0.00 | 0.47 |
August | 0.805172E+09 | 0.436170E+09 | 0.00 | 78076696.12 | 83565703.19 | 0.00 | 0.869846E+10 | 0.00 | 0.60 |
September | 0.142040E+10 | 0.138935E+09 | 0.00 | 65216023.77 | 7365715.64 | 0.00 | 0.135450E+11 | 0.00 | 0.64 |
October | 0.822754E+10 | 216461.46 | 0.00 | 41930591.80 | 0.00 | 734226.49 | 0.160848E+11 | 0.00 | 0.54 |
November | 0.158375E+11 | 0.00 | 0.00 | 13671823.28 | 0.00 | 0.295840E+09 | 0.963754E+10 | 0.00 | 0.33 |
December | 0.255727E+11 | 0.00 | 0.00 | 1678235.10 | 0.00 | 0.138454E+10 | 0.211369E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.119261E+12 | 0.215669E+10 | 0.00 | 0.454940E+09 | 0.335661E+09 | 0.336136E+10 | 0.133656E+12 | 0.00 | 0.49 |
Minimum of Months | 0.759924E+09 | 0.00 | 0.00 | 1678235.10 | 0.00 | 0.00 | 0.211369E+10 | 0.00 | 0.28 |
Maximum of Months | 0.255727E+11 | 0.822668E+09 | 0.00 | 78076696.12 | 0.176977E+09 | 0.138454E+10 | 0.220384E+11 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313118E+10 | 0.00 | 0.00 | 677802.01 | 0.00 | 22512750.47 | 0.396461E+09 | 0.00 | 0.25 |
February | 0.226157E+10 | 0.00 | 0.00 | 1692843.70 | 0.00 | 8767429.81 | 0.976998E+09 | 0.00 | 0.31 |
March | 0.150858E+10 | 0.00 | 0.00 | 5695798.22 | 0.00 | 0.00 | 0.341849E+10 | 0.00 | 0.62 |
April | 0.106389E+10 | 495248.27 | 0.00 | 9584049.04 | 0.00 | 0.00 | 0.421620E+10 | 0.00 | 1.03 |
May | 0.467454E+09 | 12739608.87 | 0.00 | 11180723.21 | 2099214.00 | 0.00 | 0.367643E+10 | 0.00 | 0.98 |
June | 0.367723E+09 | 0.238048E+09 | 0.00 | 10676168.85 | 14106273.35 | 0.00 | 0.208598E+10 | 0.00 | 0.98 |
July | 0.452741E+09 | 0.314264E+09 | 0.00 | 8841077.08 | 42411461.79 | 0.00 | 0.779070E+09 | 0.00 | 0.90 |
August | 0.691564E+09 | 0.182386E+09 | 0.00 | 13471609.68 | 13158779.95 | 0.00 | 0.159443E+10 | 0.00 | 1.10 |
September | 0.310073E+09 | 52069814.03 | 0.00 | 11038344.59 | 2064343.85 | 0.00 | 0.222715E+10 | 0.00 | 0.84 |
October | 0.112606E+10 | 77984.02 | 0.00 | 7535115.16 | 99463.08 | 0.00 | 0.260042E+10 | 0.00 | 0.67 |
November | 0.184534E+10 | 0.00 | 0.00 | 3497605.78 | 0.00 | 0.00 | 0.222634E+10 | 0.00 | 0.42 |
December | 0.284603E+10 | 0.00 | 0.00 | 828462.82 | 0.00 | 0.00 | 0.509904E+09 | 0.00 | 0.23 |
Annual Sum or Average | 0.160722E+11 | 0.800081E+09 | 0.00 | 84719600.12 | 73939536.02 | 31280180.28 | 0.247079E+11 | 0.00 | 0.70 |
Minimum of Months | 0.310073E+09 | 0.00 | 0.00 | 677802.01 | 0.00 | 0.00 | 0.396461E+09 | 0.00 | 0.23 |
Maximum of Months | 0.313118E+10 | 0.314264E+09 | 0.00 | 13471609.68 | 42411461.79 | 22512750.47 | 0.421620E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161789E+10 | 0.00 | 0.00 | 3695042.65 | 0.00 | 24541836.72 | 0.141217E+10 | 0.00 | 0.34 |
February | 0.105047E+10 | 0.00 | 0.00 | 5185945.73 | 0.00 | 10474174.17 | 0.216261E+10 | 0.00 | 0.47 |
March | 0.761578E+09 | 0.00 | 0.00 | 10780926.02 | 0.00 | 0.00 | 0.482064E+10 | 0.00 | 1.00 |
April | 0.569096E+09 | 395762.32 | 0.00 | 15376195.60 | 0.00 | 0.00 | 0.686792E+10 | 0.00 | 1.91 |
May | 0.191083E+09 | 11003151.33 | 0.00 | 19520905.77 | 1335132.27 | 0.00 | 0.589024E+10 | 0.00 | 1.96 |
June | 0.225301E+09 | 0.179467E+09 | 0.00 | 14698965.70 | 8982270.84 | 0.00 | 0.261491E+10 | 0.00 | 1.70 |
July | 0.274176E+09 | 0.272547E+09 | 0.00 | 13192901.52 | 26356486.20 | 0.00 | 0.872258E+09 | 0.00 | 1.40 |
August | 0.434063E+09 | 0.157875E+09 | 0.00 | 17056076.56 | 8486604.37 | 0.00 | 0.189395E+10 | 0.00 | 1.75 |
September | 0.157556E+09 | 39409618.22 | 0.00 | 15107928.78 | 1216450.58 | 0.00 | 0.320462E+10 | 0.00 | 1.65 |
October | 0.546016E+09 | 118283.70 | 0.00 | 12757176.61 | 30269.13 | 0.00 | 0.416123E+10 | 0.00 | 1.19 |
November | 0.982906E+09 | 0.00 | 0.00 | 6792214.87 | 0.00 | 0.00 | 0.303423E+10 | 0.00 | 0.61 |
December | 0.143067E+10 | 0.00 | 0.00 | 3781980.76 | 0.00 | 28032548.67 | 0.143154E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.824081E+10 | 0.660816E+09 | 0.00 | 0.137946E+09 | 46407213.40 | 63048559.56 | 0.383663E+11 | 0.00 | 1.19 |
Minimum of Months | 0.157556E+09 | 0.00 | 0.00 | 3695042.65 | 0.00 | 0.00 | 0.872258E+09 | 0.00 | 0.30 |
Maximum of Months | 0.161789E+10 | 0.272547E+09 | 0.00 | 19520905.77 | 26356486.20 | 28032548.67 | 0.686792E+10 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178874E+10 | 0.00 | 0.00 | 26985925.70 | 0.00 | 83527589.26 | 0.690794E+10 | 0.00 | 0.71 |
February | 0.125699E+10 | 0.00 | 0.00 | 22175713.63 | 0.00 | 27960585.96 | 0.777914E+10 | 0.00 | 0.95 |
March | 0.105868E+10 | 0.00 | 0.00 | 20436056.74 | 0.00 | 0.00 | 0.922675E+10 | 0.00 | 1.37 |
April | 0.100681E+10 | 708142.99 | 0.00 | 17994018.20 | 0.00 | 0.00 | 0.728065E+10 | 0.00 | 1.67 |
May | 0.535583E+09 | 19098476.14 | 0.00 | 13930967.58 | 2067192.64 | 0.00 | 0.419872E+10 | 0.00 | 1.17 |
June | 0.420713E+09 | 0.241930E+09 | 0.00 | 10161189.93 | 14107167.68 | 0.00 | 0.176753E+10 | 0.00 | 0.93 |
July | 0.450175E+09 | 0.362285E+09 | 0.00 | 9193780.90 | 42411832.78 | 0.00 | 0.723795E+09 | 0.00 | 0.91 |
August | 0.675592E+09 | 0.257944E+09 | 0.00 | 18235339.63 | 10839488.52 | 0.00 | 0.181922E+10 | 0.00 | 1.30 |
September | 0.231024E+09 | 0.106251E+09 | 0.00 | 25943879.44 | 1381727.84 | 0.00 | 0.358787E+10 | 0.00 | 1.43 |
October | 0.689616E+09 | 771664.17 | 0.00 | 37397288.56 | 0.00 | 0.00 | 0.845649E+10 | 0.00 | 1.67 |
November | 0.831173E+09 | 0.00 | 0.00 | 30412173.49 | 0.00 | 0.00 | 0.111365E+11 | 0.00 | 1.24 |
December | 0.139761E+10 | 0.00 | 0.00 | 28755354.33 | 0.00 | 22725214.17 | 0.868497E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.103427E+11 | 0.988988E+09 | 0.00 | 0.261622E+09 | 70807409.46 | 0.134213E+09 | 0.715696E+11 | 0.00 | 1.17 |
Minimum of Months | 0.231024E+09 | 0.00 | 0.00 | 9193780.90 | 0.00 | 0.00 | 0.723795E+09 | 0.00 | 0.71 |
Maximum of Months | 0.178874E+10 | 0.362285E+09 | 0.00 | 37397288.56 | 42411832.78 | 83527589.26 | 0.111365E+11 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119010E+10 | 0.00 | 0.00 | 6491184.81 | 0.00 | 0.00 | 0.258228E+10 | 0.00 | 0.47 |
February | 0.499505E+09 | 0.00 | 0.00 | 9893694.81 | 0.00 | 0.00 | 0.456758E+10 | 0.00 | 0.86 |
March | 0.160720E+09 | 0.00 | 0.00 | 18463221.64 | 0.00 | 0.00 | 0.854904E+10 | 0.00 | 1.83 |
April | 0.182554E+09 | 749775.20 | 0.00 | 27334604.30 | 0.00 | 0.00 | 0.901004E+10 | 0.00 | 2.87 |
May | 0.133915E+09 | 29386155.06 | 0.00 | 17667917.80 | 214204.03 | 0.00 | 0.487540E+10 | 0.00 | 1.95 |
June | 0.102412E+09 | 0.345607E+09 | 0.00 | 14780566.40 | 1430564.65 | 0.00 | 0.242318E+10 | 0.00 | 1.71 |
July | 83951974.27 | 0.452990E+09 | 0.00 | 14272919.73 | 4263276.31 | 0.00 | 0.125950E+10 | 0.00 | 1.58 |
August | 64556985.47 | 0.288298E+09 | 0.00 | 25008889.30 | 632108.60 | 0.00 | 0.285975E+10 | 0.00 | 2.27 |
September | 71927094.71 | 70424876.87 | 0.00 | 19187063.34 | 169822.16 | 0.00 | 0.291474E+10 | 0.00 | 1.58 |
October | 0.231948E+09 | 156241.14 | 0.00 | 19764055.95 | 30895.36 | 0.00 | 0.554673E+10 | 0.00 | 1.68 |
November | 0.227637E+09 | 0.00 | 0.00 | 14429060.18 | 0.00 | 0.00 | 0.714088E+10 | 0.00 | 1.25 |
December | 0.301834E+09 | 0.00 | 0.00 | 12656755.79 | 0.00 | 0.00 | 0.541496E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.325106E+10 | 0.118761E+10 | 0.00 | 0.199950E+09 | 6740871.12 | 0.00 | 0.571441E+11 | 0.00 | 1.56 |
Minimum of Months | 64556985.47 | 0.00 | 0.00 | 6491184.81 | 0.00 | 0.00 | 0.125950E+10 | 0.00 | 0.47 |
Maximum of Months | 0.119010E+10 | 0.452990E+09 | 0.00 | 27334604.30 | 4263276.31 | 0.00 | 0.901004E+10 | 0.00 | 2.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160098E+11 | 0.00 | 0.00 | 0.31 |
February | 0.234253E+11 | 0.00 | 0.00 | 975397.05 | 0.00 | 0.969241E+10 | 0.333685E+09 | 0.00 | 0.30 |
March | 0.223673E+11 | 0.00 | 0.00 | 12975637.55 | 0.00 | 0.239846E+10 | 0.812330E+10 | 0.00 | 0.37 |
April | 0.120060E+11 | 5294396.63 | 0.00 | 49899550.64 | 0.00 | 80210238.83 | 0.191706E+11 | 0.00 | 0.64 |
May | 0.686679E+10 | 0.138856E+09 | 0.00 | 84606473.54 | 23117698.74 | 0.00 | 0.248243E+11 | 0.00 | 0.80 |
June | 0.250329E+10 | 0.310266E+10 | 0.00 | 82711954.28 | 45506220.74 | 0.00 | 0.150332E+11 | 0.00 | 0.82 |
July | 0.101530E+10 | 0.367271E+10 | 0.00 | 72604782.27 | 0.244506E+09 | 0.00 | 0.593698E+10 | 0.00 | 0.71 |
August | 0.159142E+10 | 0.184164E+10 | 0.00 | 0.108380E+09 | 0.116706E+09 | 0.00 | 0.117747E+11 | 0.00 | 0.78 |
September | 0.466182E+10 | 0.472035E+09 | 0.00 | 81743082.14 | 18252837.78 | 0.00 | 0.146644E+11 | 0.00 | 0.67 |
October | 0.164038E+11 | 0.00 | 0.00 | 38550847.16 | 1461333.72 | 0.794461E+09 | 0.993462E+10 | 0.00 | 0.47 |
November | 0.250582E+11 | 0.00 | 0.00 | 3573946.19 | 0.00 | 0.400806E+10 | 0.235347E+10 | 0.00 | 0.29 |
December | 0.223416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190267E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.163195E+12 | 0.923320E+10 | 0.00 | 0.536022E+09 | 0.449550E+09 | 0.520101E+11 | 0.112149E+12 | 0.00 | 0.54 |
Minimum of Months | 0.101530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.250582E+11 | 0.367271E+10 | 0.00 | 0.108380E+09 | 0.244506E+09 | 0.190267E+11 | 0.248243E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126899E+11 | 0.00 | 0.00 | 13807054.64 | 0.00 | 0.587385E+10 | 0.777308E+10 | 0.00 | 0.30 |
February | 0.111076E+11 | 0.00 | 0.00 | 26444402.72 | 0.00 | 0.258364E+10 | 0.123679E+11 | 0.00 | 0.37 |
March | 0.831719E+10 | 0.00 | 0.00 | 80934640.21 | 0.00 | 0.458811E+09 | 0.329050E+11 | 0.00 | 0.71 |
April | 0.317850E+10 | 6020362.07 | 0.00 | 0.143895E+09 | 0.00 | 23480594.42 | 0.597679E+11 | 0.00 | 1.68 |
May | 0.209858E+10 | 0.139611E+09 | 0.00 | 0.198656E+09 | 14983390.24 | 0.00 | 0.550035E+11 | 0.00 | 1.90 |
June | 0.114117E+10 | 0.254356E+10 | 0.00 | 0.142455E+09 | 20691141.59 | 0.00 | 0.244001E+11 | 0.00 | 1.69 |
July | 0.431301E+09 | 0.394027E+10 | 0.00 | 0.127456E+09 | 75370313.45 | 0.00 | 0.833814E+10 | 0.00 | 1.35 |
August | 0.633743E+09 | 0.178771E+10 | 0.00 | 0.184614E+09 | 66916324.60 | 0.00 | 0.193843E+11 | 0.00 | 1.64 |
September | 0.170349E+10 | 0.383093E+09 | 0.00 | 0.145492E+09 | 8816471.35 | 0.00 | 0.289076E+11 | 0.00 | 1.56 |
October | 0.574802E+10 | 1718331.82 | 0.00 | 0.108669E+09 | 95245.27 | 0.306193E+09 | 0.321055E+11 | 0.00 | 0.99 |
November | 0.105140E+11 | 0.00 | 0.00 | 37365382.92 | 0.00 | 0.927819E+09 | 0.166596E+11 | 0.00 | 0.40 |
December | 0.137141E+11 | 0.00 | 0.00 | 10163427.22 | 0.00 | 0.524465E+10 | 0.673270E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.712776E+11 | 0.880198E+10 | 0.00 | 0.121995E+10 | 0.186873E+09 | 0.154184E+11 | 0.304345E+12 | 0.00 | 1.08 |
Minimum of Months | 0.431301E+09 | 0.00 | 0.00 | 10163427.22 | 0.00 | 0.00 | 0.673270E+10 | 0.00 | 0.27 |
Maximum of Months | 0.137141E+11 | 0.394027E+10 | 0.00 | 0.198656E+09 | 75370313.45 | 0.587385E+10 | 0.597679E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164795E+11 | 0.00 | 0.00 | 0.298145E+09 | 0.00 | 0.544143E+10 | 0.861767E+11 | 0.00 | 0.96 |
February | 0.129992E+11 | 0.00 | 0.00 | 0.238987E+09 | 0.00 | 0.255068E+10 | 0.858736E+11 | 0.00 | 1.03 |
March | 0.126963E+11 | 0.00 | 0.00 | 0.195982E+09 | 0.00 | 0.329697E+09 | 0.702592E+11 | 0.00 | 1.07 |
April | 0.804521E+10 | 9932731.30 | 0.00 | 0.154593E+09 | 0.00 | 21006460.78 | 0.572098E+11 | 0.00 | 1.37 |
May | 0.647825E+10 | 0.231285E+09 | 0.00 | 0.120336E+09 | 23058446.38 | 0.00 | 0.340085E+11 | 0.00 | 1.04 |
June | 0.306121E+10 | 0.311974E+10 | 0.00 | 81098151.65 | 50236095.19 | 0.00 | 0.132962E+11 | 0.00 | 0.79 |
July | 0.963361E+09 | 0.428005E+10 | 0.00 | 76944209.37 | 0.247607E+09 | 0.00 | 0.563004E+10 | 0.00 | 0.73 |
August | 0.121157E+10 | 0.280896E+10 | 0.00 | 0.164423E+09 | 0.106416E+09 | 0.00 | 0.153199E+11 | 0.00 | 1.04 |
September | 0.268790E+10 | 0.110392E+10 | 0.00 | 0.260396E+09 | 7166981.10 | 0.00 | 0.313670E+11 | 0.00 | 1.37 |
October | 0.682339E+10 | 10399563.53 | 0.00 | 0.402788E+09 | 0.00 | 0.404693E+09 | 0.751370E+11 | 0.00 | 1.53 |
November | 0.107379E+11 | 0.00 | 0.00 | 0.330536E+09 | 0.00 | 0.287760E+09 | 0.942647E+11 | 0.00 | 1.02 |
December | 0.142387E+11 | 0.00 | 0.00 | 0.295017E+09 | 0.00 | 0.442325E+10 | 0.115358E+12 | 0.00 | 1.01 |
Annual Sum or Average | 0.964224E+11 | 0.115643E+11 | 0.00 | 0.261924E+10 | 0.434484E+09 | 0.134585E+11 | 0.683900E+12 | 0.00 | 1.08 |
Minimum of Months | 0.963361E+09 | 0.00 | 0.00 | 76944209.37 | 0.00 | 0.00 | 0.563004E+10 | 0.00 | 0.73 |
Maximum of Months | 0.164795E+11 | 0.428005E+10 | 0.00 | 0.402788E+09 | 0.247607E+09 | 0.544143E+10 | 0.115358E+12 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169106E+11 | 0.00 | 0.00 | 22048987.31 | 0.00 | 0.527523E+10 | 0.110724E+11 | 0.00 | 0.42 |
February | 0.131376E+11 | 0.00 | 0.00 | 38001822.77 | 0.00 | 0.277080E+10 | 0.187909E+11 | 0.00 | 0.54 |
March | 0.100688E+11 | 0.00 | 0.00 | 79123255.87 | 0.00 | 0.249259E+09 | 0.308810E+11 | 0.00 | 0.84 |
April | 0.436518E+10 | 7529557.91 | 0.00 | 0.142167E+09 | 0.00 | 0.00 | 0.408992E+11 | 0.00 | 1.60 |
May | 0.304597E+10 | 0.319440E+09 | 0.00 | 0.128891E+09 | 3841335.15 | 0.00 | 0.320333E+11 | 0.00 | 1.52 |
June | 0.130104E+10 | 0.419784E+10 | 0.00 | 91728708.07 | 9801447.64 | 0.00 | 0.128439E+11 | 0.00 | 1.26 |
July | 0.374146E+09 | 0.456317E+10 | 0.00 | 74162337.17 | 99427584.42 | 0.00 | 0.532666E+10 | 0.00 | 1.05 |
August | 0.590040E+09 | 0.239115E+10 | 0.00 | 0.125879E+09 | 21995834.41 | 0.00 | 0.123001E+11 | 0.00 | 1.28 |
September | 0.152155E+10 | 0.652584E+09 | 0.00 | 0.139015E+09 | 1175706.27 | 0.00 | 0.182874E+11 | 0.00 | 1.18 |
October | 0.696500E+10 | 786889.92 | 0.00 | 0.115464E+09 | 871850.91 | 0.192902E+09 | 0.259650E+11 | 0.00 | 1.03 |
November | 0.130714E+11 | 0.00 | 0.00 | 42912648.77 | 0.00 | 0.443329E+09 | 0.183830E+11 | 0.00 | 0.49 |
December | 0.172865E+11 | 0.00 | 0.00 | 22092639.24 | 0.00 | 0.457234E+10 | 0.135217E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.886377E+11 | 0.121325E+11 | 0.00 | 0.102149E+10 | 0.137114E+09 | 0.135039E+11 | 0.240304E+12 | 0.00 | 0.97 |
Minimum of Months | 0.374146E+09 | 0.00 | 0.00 | 22048987.31 | 0.00 | 0.00 | 0.532666E+10 | 0.00 | 0.40 |
Maximum of Months | 0.172865E+11 | 0.456317E+10 | 0.00 | 0.142167E+09 | 99427584.42 | 0.527523E+10 | 0.408992E+11 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282614E+10 | 0.00 | 0.00 | 0.32 |
February | 0.153182E+10 | 0.00 | 0.00 | 53975.75 | 0.00 | 0.173433E+10 | 38908650.69 | 0.00 | 0.31 |
March | 0.225193E+10 | 0.00 | 0.00 | 747495.80 | 0.00 | 0.609654E+09 | 0.590243E+09 | 0.00 | 0.41 |
April | 0.122216E+10 | 0.00 | 0.00 | 4588496.32 | 0.00 | 0.130967E+09 | 0.176847E+10 | 0.00 | 0.67 |
May | 0.751376E+09 | 5736708.97 | 0.00 | 8529678.39 | 3224966.03 | 10501325.81 | 0.241556E+10 | 0.00 | 0.83 |
June | 0.279681E+09 | 0.187155E+09 | 0.00 | 10495473.51 | 3874028.45 | 0.00 | 0.144074E+10 | 0.00 | 0.81 |
July | 0.108157E+09 | 0.208024E+09 | 0.00 | 10655799.27 | 21374203.87 | 0.00 | 0.607257E+09 | 0.00 | 0.70 |
August | 0.178447E+09 | 0.101272E+09 | 0.00 | 13406206.52 | 10125642.86 | 0.00 | 0.122407E+10 | 0.00 | 0.80 |
September | 0.464415E+09 | 26149993.54 | 0.00 | 8988787.27 | 691989.91 | 0.00 | 0.143715E+10 | 0.00 | 0.70 |
October | 0.159783E+10 | 30726.28 | 0.00 | 3308380.23 | 0.00 | 0.307687E+09 | 0.798972E+09 | 0.00 | 0.49 |
November | 0.193066E+10 | 0.00 | 0.00 | 94659.16 | 0.00 | 0.107205E+10 | 0.107542E+09 | 0.00 | 0.31 |
December | 0.107410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300508E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.126141E+11 | 0.528369E+09 | 0.00 | 60868952.23 | 39290831.12 | 0.969640E+10 | 0.104289E+11 | 0.00 | 0.56 |
Minimum of Months | 0.108157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.225193E+10 | 0.208024E+09 | 0.00 | 13406206.52 | 21374203.87 | 0.300508E+10 | 0.241556E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117932E+10 | 0.00 | 0.00 | 373850.00 | 0.00 | 0.112346E+10 | 0.281763E+09 | 0.00 | 0.32 |
February | 0.111048E+10 | 0.00 | 0.00 | 1509334.03 | 0.00 | 0.555237E+09 | 0.796500E+09 | 0.00 | 0.38 |
March | 0.830700E+09 | 0.00 | 0.00 | 6244566.80 | 0.00 | 0.191604E+09 | 0.339671E+10 | 0.00 | 0.81 |
April | 0.304097E+09 | 0.00 | 0.00 | 13279800.18 | 0.00 | 22081859.50 | 0.606211E+10 | 0.00 | 1.77 |
May | 0.197377E+09 | 7037726.11 | 0.00 | 20161600.36 | 1132279.03 | 3752336.28 | 0.569422E+10 | 0.00 | 2.03 |
June | 0.108485E+09 | 0.157759E+09 | 0.00 | 17511806.27 | 998205.41 | 0.00 | 0.249439E+10 | 0.00 | 1.74 |
July | 41517169.02 | 0.259926E+09 | 0.00 | 16671193.67 | 4773829.46 | 0.00 | 0.876740E+09 | 0.00 | 1.40 |
August | 64775271.60 | 0.107087E+09 | 0.00 | 22252890.30 | 4935709.11 | 0.00 | 0.207180E+10 | 0.00 | 1.76 |
September | 0.163632E+09 | 21536068.06 | 0.00 | 15827234.64 | 368846.76 | 0.00 | 0.292658E+10 | 0.00 | 1.70 |
October | 0.564008E+09 | 26781.97 | 0.00 | 9702990.74 | 0.00 | 0.116156E+09 | 0.311824E+10 | 0.00 | 1.06 |
November | 0.103930E+10 | 0.00 | 0.00 | 2080449.08 | 0.00 | 0.281929E+09 | 0.117529E+10 | 0.00 | 0.39 |
December | 0.139662E+10 | 0.00 | 0.00 | 173281.43 | 0.00 | 0.103731E+10 | 0.142365E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.700031E+10 | 0.553373E+09 | 0.00 | 0.125789E+09 | 12208869.76 | 0.333154E+10 | 0.290367E+11 | 0.00 | 1.14 |
Minimum of Months | 41517169.02 | 0.00 | 0.00 | 173281.43 | 0.00 | 0.00 | 0.142365E+09 | 0.00 | 0.30 |
Maximum of Months | 0.139662E+10 | 0.259926E+09 | 0.00 | 22252890.30 | 4935709.11 | 0.112346E+10 | 0.606211E+10 | 0.00 | 2.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138876E+10 | 0.00 | 0.00 | 20552880.04 | 0.00 | 0.942081E+09 | 0.678641E+10 | 0.00 | 0.85 |
February | 0.113754E+10 | 0.00 | 0.00 | 18170049.78 | 0.00 | 0.525671E+09 | 0.749093E+10 | 0.00 | 0.97 |
March | 0.113031E+10 | 0.00 | 0.00 | 15738207.04 | 0.00 | 0.357810E+09 | 0.804706E+10 | 0.00 | 1.27 |
April | 0.754088E+09 | 0.00 | 0.00 | 14414146.40 | 0.00 | 86018354.33 | 0.592513E+10 | 0.00 | 1.43 |
May | 0.650230E+09 | 9808299.00 | 0.00 | 13163674.97 | 2219719.39 | 26453013.38 | 0.356839E+10 | 0.00 | 1.11 |
June | 0.343252E+09 | 0.181603E+09 | 0.00 | 10702409.29 | 4570716.87 | 304034.11 | 0.136086E+10 | 0.00 | 0.79 |
July | 0.108518E+09 | 0.234571E+09 | 0.00 | 11900713.76 | 21137756.14 | 0.00 | 0.600410E+09 | 0.00 | 0.72 |
August | 0.156671E+09 | 0.147718E+09 | 0.00 | 21296579.92 | 8050851.74 | 0.00 | 0.168456E+10 | 0.00 | 1.08 |
September | 0.294604E+09 | 58115224.99 | 0.00 | 28957370.43 | 248630.44 | 0.00 | 0.339183E+10 | 0.00 | 1.49 |
October | 0.666349E+09 | 69049.16 | 0.00 | 37634612.43 | 0.00 | 0.163008E+09 | 0.827532E+10 | 0.00 | 1.73 |
November | 0.981067E+09 | 0.00 | 0.00 | 23774400.82 | 0.00 | 0.283935E+09 | 0.859454E+10 | 0.00 | 1.00 |
December | 0.131202E+10 | 0.00 | 0.00 | 20231695.09 | 0.00 | 0.770231E+09 | 0.914064E+10 | 0.00 | 0.88 |
Annual Sum or Average | 0.892341E+10 | 0.631884E+09 | 0.00 | 0.236537E+09 | 36227674.58 | 0.315551E+10 | 0.648661E+11 | 0.00 | 1.11 |
Minimum of Months | 0.108518E+09 | 0.00 | 0.00 | 10702409.29 | 0.00 | 0.00 | 0.600410E+09 | 0.00 | 0.72 |
Maximum of Months | 0.138876E+10 | 0.234571E+09 | 0.00 | 37634612.43 | 21137756.14 | 0.942081E+09 | 0.914064E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120391E+10 | 0.00 | 0.00 | 1670298.12 | 0.00 | 0.932822E+09 | 0.936287E+09 | 0.00 | 0.40 |
February | 0.105174E+10 | 0.00 | 0.00 | 3162182.81 | 0.00 | 0.532663E+09 | 0.169890E+10 | 0.00 | 0.54 |
March | 0.101706E+10 | 0.00 | 0.00 | 6595779.92 | 0.00 | 0.228987E+09 | 0.332018E+10 | 0.00 | 0.98 |
April | 0.489449E+09 | 0.00 | 0.00 | 13882795.84 | 0.00 | 21507374.63 | 0.419255E+10 | 0.00 | 1.72 |
May | 0.341936E+09 | 13434279.42 | 0.00 | 15111098.03 | 747439.08 | 4034014.86 | 0.335717E+10 | 0.00 | 1.63 |
June | 0.139055E+09 | 0.233673E+09 | 0.00 | 12641429.65 | 1289171.38 | 0.00 | 0.135254E+10 | 0.00 | 1.25 |
July | 42729704.90 | 0.243289E+09 | 0.00 | 11505453.98 | 9307826.26 | 0.00 | 0.565006E+09 | 0.00 | 1.00 |
August | 55221042.12 | 0.125912E+09 | 0.00 | 16176796.31 | 1316085.18 | 0.00 | 0.132540E+10 | 0.00 | 1.29 |
September | 0.183453E+09 | 34321611.16 | 0.00 | 16588778.18 | 55200.71 | 0.00 | 0.183631E+10 | 0.00 | 1.26 |
October | 0.715707E+09 | 51738.23 | 0.00 | 11135791.31 | 0.00 | 0.115241E+09 | 0.262170E+10 | 0.00 | 1.12 |
November | 0.114785E+10 | 0.00 | 0.00 | 3145311.37 | 0.00 | 0.290219E+09 | 0.160016E+10 | 0.00 | 0.49 |
December | 0.118873E+10 | 0.00 | 0.00 | 1564524.80 | 0.00 | 0.934415E+09 | 0.102145E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.757684E+10 | 0.650682E+09 | 0.00 | 0.113180E+09 | 12715722.61 | 0.305989E+10 | 0.238276E+11 | 0.00 | 1.01 |
Minimum of Months | 42729704.90 | 0.00 | 0.00 | 1564524.80 | 0.00 | 0.00 | 0.565006E+09 | 0.00 | 0.37 |
Maximum of Months | 0.120391E+10 | 0.243289E+09 | 0.00 | 16588778.18 | 9307826.26 | 0.934415E+09 | 0.419255E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3769757.88 | 0.00 | 0.00 | 0.544380E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8644233.32 | 0.00 | 0.00 | 0.454713E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 15639913.50 | 0.00 | 0.00 | 0.427901E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 18199687.48 | 0.00 | 0.00 | 0.290094E+09 | 0.00 | 0.29 |
May | 0.00 | 465176.58 | 0.00 | 4123751.41 | 0.00 | 0.00 | 0.216054E+09 | 0.00 | 0.29 |
June | 0.00 | 24254516.79 | 0.00 | 5410542.84 | 0.00 | 0.00 | 50010322.31 | 0.00 | 0.30 |
July | 0.00 | 0.136968E+09 | 0.00 | 321285.58 | 0.00 | 0.00 | 311679.99 | 0.00 | 0.28 |
August | 0.00 | 0.100879E+09 | 0.00 | 1946293.56 | 0.00 | 0.00 | 1636320.44 | 0.00 | 0.30 |
September | 0.00 | 18037790.72 | 0.00 | 2704694.67 | 0.00 | 0.00 | 56831737.58 | 0.00 | 0.29 |
October | 0.00 | 3811846.71 | 0.00 | 8299491.22 | 0.00 | 0.00 | 0.275254E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13887284.05 | 0.00 | 0.00 | 0.423745E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 20162635.79 | 0.00 | 0.00 | 0.546341E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.284417E+09 | 0.00 | 0.103110E+09 | 0.00 | 0.00 | 0.328727E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 321285.58 | 0.00 | 0.00 | 311679.99 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.136968E+09 | 0.00 | 20162635.79 | 0.00 | 0.00 | 0.546341E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72157625.29 | 0.00 | 0.00 | 22438005.99 | 0.00 | 0.00 | 0.538553E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 71729372.89 | 0.00 | 0.00 | 0.456150E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.141344E+09 | 0.00 | 0.00 | 0.429248E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.171121E+09 | 0.00 | 0.00 | 0.290992E+10 | 0.00 | 0.29 |
May | 0.00 | 4187996.63 | 0.00 | 37035426.18 | 0.00 | 0.00 | 0.216830E+10 | 0.00 | 0.29 |
June | 0.00 | 0.240740E+09 | 0.00 | 51020842.70 | 0.00 | 0.00 | 0.504862E+09 | 0.00 | 0.30 |
July | 0.00 | 0.136523E+10 | 0.00 | 3071379.25 | 0.00 | 0.00 | 3032838.23 | 0.00 | 0.28 |
August | 0.00 | 0.101877E+10 | 0.00 | 17613438.96 | 0.00 | 0.00 | 15815527.11 | 0.00 | 0.30 |
September | 0.00 | 0.171355E+09 | 0.00 | 24897996.22 | 0.00 | 0.00 | 0.578855E+09 | 0.00 | 0.29 |
October | 0.00 | 36871563.08 | 0.00 | 74573623.72 | 0.00 | 0.00 | 0.276130E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.123928E+09 | 0.00 | 0.00 | 0.425156E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.177835E+09 | 0.00 | 0.00 | 0.548587E+10 | 0.00 | 0.28 |
Annual Sum or Average | 72157625.29 | 0.283715E+10 | 0.00 | 0.916609E+09 | 0.00 | 0.00 | 0.329190E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3071379.25 | 0.00 | 0.00 | 3032838.23 | 0.00 | 0.28 |
Maximum of Months | 72157625.29 | 0.136523E+10 | 0.00 | 0.177835E+09 | 0.00 | 0.00 | 0.548587E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194387E+09 | 0.00 | 0.00 | 1194220.30 | 0.00 | 0.00 | 0.348105E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6094780.06 | 0.00 | 0.00 | 0.457354E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 13297961.20 | 0.00 | 0.00 | 0.430223E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16829006.87 | 0.00 | 0.00 | 0.291229E+09 | 0.00 | 0.29 |
May | 0.00 | 425318.46 | 0.00 | 3619154.54 | 0.00 | 0.00 | 0.217102E+09 | 0.00 | 0.29 |
June | 0.00 | 24110373.61 | 0.00 | 5117312.31 | 0.00 | 0.00 | 50565176.89 | 0.00 | 0.30 |
July | 0.00 | 0.136542E+09 | 0.00 | 311957.71 | 0.00 | 0.00 | 310580.87 | 0.00 | 0.28 |
August | 0.00 | 0.102641E+09 | 0.00 | 1688140.19 | 0.00 | 0.00 | 1509420.83 | 0.00 | 0.30 |
September | 0.00 | 17186615.91 | 0.00 | 2434861.83 | 0.00 | 0.00 | 58075059.22 | 0.00 | 0.29 |
October | 0.00 | 3672752.29 | 0.00 | 6929094.11 | 0.00 | 0.00 | 0.276888E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11356476.04 | 0.00 | 0.00 | 0.426313E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16308698.73 | 0.00 | 0.00 | 0.550133E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.194387E+09 | 0.284577E+09 | 0.00 | 85181663.90 | 0.00 | 0.00 | 0.310781E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 311957.71 | 0.00 | 0.00 | 310580.87 | 0.00 | 0.28 |
Maximum of Months | 0.194387E+09 | 0.136542E+09 | 0.00 | 16829006.87 | 0.00 | 0.00 | 0.550133E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.650255E+09 | 0.00 | 0.00 | 0.545953E+12 | 0.00 | 11.08 |
February | 0.00 | 0.00 | 0.00 | 0.110647E+10 | 0.00 | 0.00 | 0.759295E+12 | 0.00 | 20.54 |
March | 0.00 | 0.00 | 0.00 | 0.176048E+10 | 0.00 | 0.00 | 0.106036E+13 | 0.00 | 34.91 |
April | 0.00 | 0.00 | 0.00 | 0.250593E+10 | 0.00 | 0.00 | 0.103174E+13 | 0.00 | 46.77 |
May | 0.00 | 0.00 | 0.00 | 0.600022E+09 | 0.00 | 0.00 | 0.473297E+12 | 0.00 | 28.47 |
June | 0.00 | 0.139719E+10 | 0.00 | 0.102537E+10 | 0.00 | 0.00 | 0.363942E+12 | 0.00 | 31.40 |
July | 0.00 | 0.335153E+11 | 0.00 | 0.900918E+09 | 0.00 | 0.00 | 0.851563E+11 | 0.00 | 30.66 |
August | 0.00 | 0.160662E+11 | 0.00 | 0.253742E+10 | 0.00 | 0.00 | 0.143973E+12 | 0.00 | 45.82 |
September | 0.00 | 0.494408E+09 | 0.00 | 0.561982E+09 | 0.00 | 0.00 | 0.312718E+12 | 0.00 | 30.67 |
October | 0.00 | 0.119245E+09 | 0.00 | 0.128461E+10 | 0.00 | 0.00 | 0.733591E+12 | 0.00 | 34.20 |
November | 0.00 | 0.00 | 0.00 | 0.180882E+10 | 0.00 | 0.00 | 0.105561E+13 | 0.00 | 31.81 |
December | 0.00 | 0.00 | 0.00 | 0.256123E+10 | 0.00 | 0.00 | 0.133973E+13 | 0.00 | 32.43 |
Annual Sum or Average | 0.00 | 0.515924E+11 | 0.00 | 0.173035E+11 | 0.00 | 0.00 | 0.790536E+13 | 0.00 | 31.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.561982E+09 | 0.00 | 0.00 | 0.851563E+11 | 0.00 | 11.08 |
Maximum of Months | 0.00 | 0.335153E+11 | 0.00 | 0.256123E+10 | 0.00 | 0.00 | 0.133973E+13 | 0.00 | 46.77 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:51:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.447553E+12 | 0.212349E+11 | 0.00 | 0.223894E+13 | 0.169334E+12 |
February | 0.553337E+12 | 0.198402E+11 | 0.00 | 0.233960E+13 | 0.267628E+12 |
March | 0.720700E+12 | 0.193356E+11 | 0.00 | 0.283898E+13 | 0.527655E+12 |
April | 0.891473E+12 | 0.139969E+11 | 0.00 | 0.277002E+13 | 0.119702E+13 |
May | 0.952410E+12 | 0.920683E+10 | 0.00 | 0.190600E+13 | 0.102246E+13 |
June | 0.893787E+12 | 0.433789E+10 | 0.00 | 0.114052E+13 | 0.225161E+13 |
July | 0.920034E+12 | 0.174990E+10 | 0.00 | 0.360665E+12 | 0.324017E+13 |
August | 0.900838E+12 | 0.334387E+10 | 0.00 | 0.760662E+12 | 0.352874E+13 |
September | 0.732156E+12 | 0.570154E+10 | 0.00 | 0.149844E+13 | 0.147453E+13 |
October | 0.596963E+12 | 0.108260E+11 | 0.00 | 0.243868E+13 | 0.928457E+12 |
November | 0.478443E+12 | 0.174012E+11 | 0.00 | 0.285365E+13 | 0.418311E+12 |
December | 0.417795E+12 | 0.193229E+11 | 0.00 | 0.313130E+13 | 0.370432E+12 |
Annual Sum or Average | 0.850549E+13 | 0.146298E+12 | 0.00 | 0.242775E+14 | 0.153963E+14 |
Minimum of Months | 0.417795E+12 | 0.174990E+10 | 0.00 | 0.360665E+12 | 0.169334E+12 |
Maximum of Months | 0.952410E+12 | 0.212349E+11 | 0.00 | 0.313130E+13 | 0.352874E+13 |