Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:56:52
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 25925.34 | 559.70 | 559.70 |
Net Site Energy | 25471.16 | 549.89 | 549.89 |
Total Source Energy | 79011.86 | 1705.77 | 1705.77 |
Net Source Energy | 77573.47 | 1674.72 | 1674.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 728.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2006.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 265.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2157.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 391.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 716.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4756.55 |
Humidification | 1261.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.23 |
Heat Recovery | 43.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 756.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 24440.13 | 1485.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7505.95 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 728.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2006.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 265.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2157.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 391.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 716.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4756.55 |
Humidification | General | 1261.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.23 |
Heat Recovery | General | 43.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 756.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 728.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2006.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 265.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2157.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 391.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 716.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4756.55 |
Humidification | Unassigned | 1261.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.23 |
Heat Recovery | Unassigned | 43.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 756.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 141.05 | 32.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 343.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 527.63 | 32.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 141.05 | 32.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 343.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 527.63 | 32.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 475.327 | 1.94 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -21.15 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 454.180 | 1.86 |
Electricity Coming From Utility | 23985.946 | 98.14 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 23985.946 | 98.14 |
Total On-Site and Utility Electric Sources | 24440.126 | 100.00 |
Total Electricity End Uses | 24440.126 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 471.98 | 27.33 |
Air to Air Heat Recovery for Heating | 1255.30 | 72.67 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1727.28 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7505.95 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7505.95 | 100.00 |
Total Water End Uses | 7505.95 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 48.67 |
Time Setpoint Not Met During Occupied Cooling | 455.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5928.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.7776 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.7776 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 5.7776 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 5.7776 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.1736 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.7776 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 5.7907 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.7776 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.7776 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.7776 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.7776 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.7776 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.7776 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.7776 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.1736 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.7776 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.7907 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.7810 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-AUG-14:50 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 30-AUG-15:00 |
Heating | 0.00 | 1623882.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 415081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 24458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 266963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 48363.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79575.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 51074.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1809875.36 | 1631163.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1623882.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 415081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 145987.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3359.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 21003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 94.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 266963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 48363.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 79575.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 51074.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 789.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6355.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5438.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 841.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6833.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1240.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2267.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3994.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 138.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 820.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 77401.88 | 1609.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 137.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 48.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 86.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1671.01 | 34.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 137.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 117.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 48.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 86.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1671.01 | 34.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 4.82 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.469166 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.49 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.457675 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.23 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.23 | 0.363599 | 0.309000 | 1.62 | 0.969599 | 0.500000 | 0.001048 | 0.000356 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.05 | 0.387764 | 0.330000 | 16.19 | 1.00 | 0.500000 | 0.000983 | 0.010040 | 16.19 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.00 | 0.380603 | 0.324000 | 1.62 | 1.00 | 0.500000 | 0.001001 | 0.001927 | 2.62 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.937216 | 0.254819 | 0.217000 | 0.203376 | 0.679518 | 0.500000 | 0.001495 | 0.000320 | 0.436538 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.17 | 0.131066 | 0.111000 | 0.130342 | 0.349510 | 0.500000 | 0.002907 | 0.000220 | 0.300588 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.36 | 0.176159 | 0.150000 | 0.203361 | 0.469757 | 0.500000 | 0.002163 | 0.000362 | 0.492982 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.45 | 0.106343 | 0.090000 | 0.130252 | 0.300000 | 0.500000 | 0.003583 | 0.000173 | 0.235171 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.02 | 0.264909 | 0.225000 | 2.03 | 0.706424 | 0.500000 | 0.001438 | 0.005806 | 7.92 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.62 | 0.325143 | 0.500000 | 0.003125 | 0.003815 | 5.21 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.55 | 0.176275 | 0.150000 | 2.03 | 0.470065 | 0.500000 | 0.002161 | 0.005748 | 7.85 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.22 | 0.116401 | 0.099000 | 1.31 | 0.310404 | 0.500000 | 0.003273 | 0.003701 | 5.05 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.03 | 0.231250 | 0.197000 | 0.203449 | 0.616667 | 0.500000 | 0.001648 | 0.000727 | 0.992217 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.29 | 0.119634 | 0.102000 | 0.131220 | 0.319024 | 0.500000 | 0.003185 | 0.000476 | 0.650088 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.48 | 0.161609 | 0.137000 | 0.202458 | 0.430958 | 0.500000 | 0.002358 | 0.000721 | 0.984016 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.41 | 0.109271 | 0.093000 | 0.130987 | 0.300000 | 0.500000 | 0.003487 | 0.000468 | 0.639319 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16267.74 | 0.000356 | 454.03 |
CORE_MID VAV BOX REHEAT COIL | 458955.50 | 0.010040 | 16297.03 |
CORE_TOP VAV BOX REHEAT COIL | 88094.47 | 0.001927 | 3428.55 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14638.95 | 0.000320 | 569.14 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10078.85 | 0.000220 | 391.82 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16528.81 | 0.000362 | 642.54 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7889.84 | 0.000173 | 306.83 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 265396.46 | 0.005806 | 10309.29 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 174398.45 | 0.003815 | 6774.31 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 262775.57 | 0.005748 | 10207.57 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 169177.53 | 0.003701 | 6571.66 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33217.32 | 0.000727 | 1290.04 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21762.91 | 0.000476 | 845.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32943.05 | 0.000721 | 1279.40 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21402.61 | 0.000468 | 831.19 |
VAV_BOT WITH REHEAT HEATING COIL | 59234.79 | 0.001296 | 1216.64 |
VAV_MID WITH REHEAT HEATING COIL | 542473.91 | 0.011867 | 11192.50 |
VAV_TOP WITH REHEAT HEATING COIL | 52639.37 | 0.001151 | 1113.38 |
CAV_BAS HEATING COIL | 248626.71 | 0.005439 | 7783.12 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.07 | 2.28 | 10.15 | 2.54 | 8.90 | 8.90 | 0.300000 | 0.285684 | 8.90 |
VAV_MID WITH REHEAT | 48.73 | 22.87 | 97.46 | 38.53 | 83.46 | 83.46 | 0.300000 | 0.461595 | 83.46 |
VAV_TOP WITH REHEAT | 5.10 | 2.29 | 10.20 | 5.89 | 9.24 | 9.24 | 0.300000 | 0.637390 | 9.24 |
CAV_BAS | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 1.00 | 1.00 | 4.82 |
AIRLOOP DATACENTER BASEMENT | 21.23 | 21.23 | 21.23 | 21.23 | 21.23 | 21.23 | 1.00 | 0.999988 | 21.23 |
AIRLOOP DATACENTER BOT | 0.469166 | 0.469166 | 0.469166 | 0.469166 | 0.469166 | 0.469166 | 1.00 | 1.00 | 0.469166 |
AIRLOOP DATACENTER MID | 4.49 | 4.49 | 4.49 | 4.49 | 4.49 | 4.49 | 1.00 | 1.00 | 4.49 |
AIRLOOP DATACENTER TOP | 0.457675 | 0.457675 | 0.457675 | 0.457675 | 0.457675 | 0.457675 | 1.00 | 1.00 | 0.457675 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.90 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 83.46 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.24 | |
CAV_BAS_OA_CONTROLLER | 4.82 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.23 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.469166 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.49 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.457675 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.91 | 6.67 | 11.05 | 0.010150 | 0.008500 | 207567.52 | 0.005936 | 8.90 |
VAV_MID WITH REHEAT COOLING COIL | 26.08 | 6.67 | 11.05 | 0.010356 | 0.008500 | 2017078.92 | 0.057688 | 83.46 |
VAV_TOP WITH REHEAT COOLING COIL | 25.78 | 6.67 | 11.05 | 0.010128 | 0.008500 | 213336.08 | 0.006101 | 9.24 |
CAV_BAS COOLING COIL | 24.77 | 6.67 | 11.42 | 0.010293 | 0.008500 | 105483.61 | 0.003017 | 4.82 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.90 |
VAV_MID WITH REHEAT FAN | 83.46 |
VAV_TOP WITH REHEAT FAN | 9.24 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005936 | 0.000080 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001296 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.057688 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011867 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006101 | 0.000078 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001151 | |
CAV_BAS_COOLC_CONTROLLER | 0.003017 | 0.000158 |
CAV_BAS_HEATC_CONTROLLER | 0.005439 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 4.82 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.23 | 429556.05 | 310090.67 | 0.010520 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.469166 | 9443.33 | 6831.79 | 0.000231 |
AIRLOOP DATACENTER MID COOLING COIL | 4.49 | 90573.67 | 65463.15 | 0.002218 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.457675 | 9224.18 | 6668.53 | 0.000226 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.23 | 21.23 | 21.23 | 21.23 | 429556.05 | 429556.05 | 20749.82 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.469166 | 0.469166 | 0.469166 | 0.469166 | 9443.33 | 9443.33 | 958.56 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.49 | 4.49 | 4.49 | 4.49 | 90573.67 | 90573.67 | 9585.56 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.457675 | 0.457675 | 0.457675 | 0.457675 | 9224.18 | 9224.18 | 958.56 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.23 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.469166 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.49 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.457675 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.23 | 429556.05 | 0.010520 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.469166 | 9443.33 | 0.000231 |
AIRLOOP DATACENTER MID HEATING COIL | 4.49 | 90573.67 | 0.002218 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.457675 | 9224.18 | 0.000226 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 20749.82 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 958.56 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 9585.56 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 958.56 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000172 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.072743 | 11759.09 | |
HEATSYS1 PUMP | 0.054611 | 16283.62 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.072743 | 8.73 |
HEATSYS1 | 0.054611 | 6.55 |
COOLSYS1_SUPPLY | 0.072743 | 8.73 |
SINGLE WATER PLANT LOOP | 0.013195 | 1.58 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.072743 | 0.072743 | 305338.07 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2496502.84 | 2496502.84 | 0.054611 |
CENTRAL BOILER | 543525.39 | 532964.22 | 0.013195 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.036371 | 4070.61 |
COOLSYS1 CHILLER2 PUMP | 0.036371 | 4070.61 |
PLANT CIRC PUMP | 0.013195 | 3332.09 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.072743 | 0.036721 | 1287108.98 | 1293213.38 | 0.063578 |
COOLSYS1 CHILLER2 | 0.072743 | 0.036721 | 1287108.98 | 1293213.38 | 0.063578 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013195 | 139666.47 | 59676.14 | 69833.23 | 7004.20 | 21454.36 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.127155 | 15.26 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.127155 | 31169.19 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 47.13 | 1534377.33 | 9.43 | 191797.17 |
TOWERWATERSYS COOLTOWER 2 | 47.13 | 1534377.33 | 9.43 | 191797.17 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.066473 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.778 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.619 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.847 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.778 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.848 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.174 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.473 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.778 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.201 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16058.301 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16058.301 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14421.483 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14421.483 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1810.761 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.761 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1810.801 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1810.801 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1166.923 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1166.923 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4527.754 | 5.778 | 107.340 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4527.754 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 259.704 | 7.174 | 133.277 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 259.704 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9398 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8967 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9335 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8058 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.29018797E-14 | 0.36812723E-16 | -0.14924019E-09 | 0.48847313E-16 |
51 | 8 | 0.21807402E-07 | 0.12652057E-12 | 0.37708831E-03 | -0.24795767E-09 |
52 | 7 | -0.12220551E-01 | 0.65729479E-08 | -0.23055577E-01 | 0.13895212E-03 |
53 | 6 | 0.40477966 | 0.22909352E-05 | 0.47160541 | -0.47410351E-02 |
54 | 5 | -5.1849947 | 0.85678555E-04 | -4.4375337 | 0.63114796E-01 |
55 | 4 | 32.978226 | 0.70190469E-03 | 21.425779 | -0.42179587 |
56 | 3 | -111.17384 | 0.15317614E-02 | -55.595241 | 1.5144378 |
57 | 2 | 197.07933 | 0.86263138E-03 | 77.848428 | -2.8998938 |
58 | 1 | -171.14541 | 0.92189209E-04 | -55.246988 | 2.7452524 |
59 | 0 | 57.057407 | 0.52547460E-06 | 15.559906 | |
60 | 9 | -0.29188985E-14 | 0.30841220E-16 | -0.15071594E-09 | 0.45756810E-16 |
61 | 8 | 0.22014798E-07 | 0.12246996E-12 | 0.37926559E-03 | -0.25031584E-09 |
62 | 7 | -0.12285514E-01 | 0.63488536E-08 | -0.23149110E-01 | 0.13969077E-03 |
63 | 6 | 0.40654483 | 0.22108485E-05 | 0.47310859 | -0.47618422E-02 |
64 | 5 | -5.2022205 | 0.82619656E-04 | -4.4490782 | 0.63328388E-01 |
65 | 4 | 33.054419 | 0.67637415E-03 | 21.470902 | -0.42280751 |
66 | 3 | -111.33595 | 0.14751306E-02 | -55.684449 | 1.5167798 |
67 | 2 | 197.23999 | 0.83027991E-03 | 77.930247 | -2.9024452 |
68 | 1 | -171.20475 | 0.88686394E-04 | -55.270783 | 2.7462925 |
69 | 0 | 57.057407 | 0.50524406E-06 | 15.555978 | |
70 | 9 | -0.57207635E-15 | 0.35733182E-16 | -0.14510758E-09 | 0.92780423E-20 |
71 | 8 | 0.21226260E-07 | 0.13767829E-12 | 0.37094976E-03 | -0.24134990E-09 |
72 | 7 | -0.12037268E-01 | 0.71989887E-08 | -0.22791647E-01 | 0.13686812E-03 |
73 | 6 | 0.39979937 | 0.25155658E-05 | 0.46736115 | -0.46823295E-02 |
74 | 5 | -5.1363910 | 0.94286903E-04 | -4.4049234 | 0.62512134E-01 |
75 | 4 | 32.763227 | 0.77396227E-03 | 21.298286 | -0.41894130 |
76 | 3 | -110.71637 | 0.16919998E-02 | -55.343173 | 1.5078286 |
77 | 2 | 196.62589 | 0.95437189E-03 | 77.617295 | -2.8926932 |
78 | 1 | -170.97790 | 0.10214201E-03 | -55.179873 | 2.7423166 |
79 | 0 | 57.057407 | 0.58311013E-06 | 15.571069 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3569E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3590E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9511E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9529E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5254E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5268E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4917E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4924E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4051E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5483E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9918E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1170E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5603E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6638E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5122E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5645E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1579 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5943E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1783 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5187E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1115 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4149E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5025E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5661E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4078E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5608E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9945E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1301E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5626E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6727E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5127E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5660E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3567E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3588E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9509E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9527E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5252E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5267E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4916E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4923E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4525E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7393E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1616E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4743E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9559E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0822E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2602E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2962E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0027E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9330E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5444E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6356E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8814E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4384E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6880E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7537E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3654E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4663E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0490E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1220E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9156E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9438E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2603E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2968E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5875E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5895E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1978E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1994E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9464E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9475E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4917E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6326E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7498E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2344E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3268E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9759E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0415E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5127E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5660E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1313E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1799E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1624E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6479E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8556E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1125E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5025E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5656E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6313E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7471E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2331E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3237E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9741E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0360E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5122E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5645E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5873E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5893E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1977E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1993E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9463E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9474E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4916E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4923E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2128E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3147E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8585E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9320E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7924E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8200E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2604E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2969E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7369E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8281E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2150E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5054E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6540E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3481E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6880E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7537E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2947E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5617E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9646E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2522E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8319E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9547E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2601E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2961E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1536 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1041 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1676 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1154 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1224 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5201E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5140E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7277E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1673E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2374E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6549E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8733E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.9870E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6115E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6552E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7590E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.1380E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4253E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0404E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6986E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7042E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0286E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5140E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7273E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8666E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0927E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2819E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6932E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.7321E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4915E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6552E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7590E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1537 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1043 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1677 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1156 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1225 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5363E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5258E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7338E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1723E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2439E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6605E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8794E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.9979E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6191E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6670E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7650E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.1384E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4292E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0411E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7016E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7101E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0323E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5258E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7333E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8711E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0987E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2870E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6988E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.7426E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4988E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6670E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7650E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 66929.87981 | 66929.87981 | 4.81824 | 4.81824 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72660.16196 | 72660.16196 | 5.23115 | 5.23115 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 681530.76051 | 681530.76051 | 49.05155 | 49.05155 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 296049.07243 | 296049.07243 | 12.49617 | 12.49617 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 69426.17557 | 69426.17557 | 4.99745 | 4.99745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 61698.63585 | 61698.63585 | 2.62279 | 2.62279 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12892.66286 | 12892.66286 | 0.93722 | 0.93722 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 10254.69531 | 10254.69531 | 0.43654 | 0.43654 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16153.56395 | 16153.56395 | 1.17425 | 1.17425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 27.79567 | 1.41119E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7059.53098 | 7059.53098 | 0.30059 | 0.30059 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18650.14777 | 18650.14777 | 1.35574 | 1.35574 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 11575.93631 | 11575.93631 | 0.49298 | 0.49298 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19909.09841 | 19909.09841 | 1.44725 | 1.44725 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5529.62821 | 5529.62821 | 0.23517 | 0.23517 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 124007.13532 | 124007.13532 | 9.01520 | 9.01520 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 185805.64604 | 185805.64604 | 7.92482 | 7.92482 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 173629.03197 | 173629.03197 | 12.62254 | 12.62254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 122096.85969 | 122096.85969 | 5.20780 | 5.20780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 186365.55197 | 186365.55197 | 13.54851 | 13.54851 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 183972.99720 | 183972.99720 | 7.84645 | 7.84645 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 181874.04774 | 181874.04774 | 13.22193 | 13.22193 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 118445.92820 | 118445.92820 | 5.05172 | 5.05172 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14205.28628 | 14205.28628 | 1.03274 | 1.03274 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 23252.93402 | 23252.93402 | 0.99222 | 0.99222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 17695.45148 | 17695.45148 | 1.28647 | 1.28647 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15234.61838 | 15234.61838 | 0.65009 | 0.65009 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20327.18284 | 20327.18284 | 1.47780 | 1.47780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 23061.13888 | 23061.13888 | 0.98402 | 0.98402 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19373.62537 | 19373.62537 | 1.40847 | 1.40847 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 14982.62958 | 14982.62958 | 0.63932 | 0.63932 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8183.13415 | 8183.13415 | 0.46917 | 0.46917 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 78346.34301 | 78346.34301 | 4.49189 | 4.49189 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7982.67620 | 7982.67620 | 0.45767 | 0.45767 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.41154E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370278.20547 | 370278.20547 | 21.22890 | 21.22890 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.36600 | 1.41076E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -10.70000 | 1.50390E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 136593.09 | 8.90180 | 8.90180 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 58403.26 | 2.54310 | 2.54310 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1267420.74 | 83.46495 | 83.46495 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 576248.11 | 38.52697 | 38.52697 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 145014.67 | 9.23835 | 9.23835 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 57688.22 | 5.88843 | 5.88843 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 02:50:00 |
7 | CAV_BAS | Cooling | Sensible | 69625.62 | 4.81824 | 4.81824 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 73592.09 | 1.20016 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366274.50 | 21.22915 | 21.22915 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20749.82 | 0.33839 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8105.48 | 0.46917 | 0.46917 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77623.71 | 4.49189 | 4.49189 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9585.56 | 0.15632 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7911.62 | 0.45767 | 0.45767 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.81824 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.23115 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36360 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61643 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96960 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04786E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55857E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61643 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16267.74382 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55857E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 454.03436 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.05155 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38776 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18701 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.82556E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00397E-002 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18701 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 458955.49815 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00397E-002 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 16297.03124 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.99745 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38060 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61917 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00104E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92707E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.62279 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 88094.47026 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92707E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3428.54948 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93722 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25482 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20338 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67952 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49518E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.20228E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43654 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14638.95357 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20228E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 569.14127 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17425 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13107 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13034 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34951 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90692E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20475E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30059 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10078.84883 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20475E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 391.82210 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35574 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17616 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20336 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46976 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16282E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.61568E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49298 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16528.81257 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.61568E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 642.54179 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44725 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10634 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.00000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13025 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58274E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72590E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23517 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7889.83577 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72590E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.83479 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.01520 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26491 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02842 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70642 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43823E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.80555E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.92482 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 265396.46475 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.80555E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10309.28947 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.62254 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32514 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12477E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.81497E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.20780 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 174398.45205 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.81497E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6774.31281 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.54851 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17627 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15000 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03228 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47007 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16140E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.74822E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.84645 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 262775.56941 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.74822E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10207.57345 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.22193 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11640 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.90000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30897 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31040 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27316E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.70076E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.05172 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 169177.53029 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.70076E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6571.65764 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03274 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23125 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19700 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20345 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61667 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64757E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.26630E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.99222 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33217.31584 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.26630E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1290.03928 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28647 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11963 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13122 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31902 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18471E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.76064E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65009 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21762.91031 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.76064E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 845.17549 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47780 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16161 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20246 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43096 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35754E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.20630E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.98402 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32943.04923 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.20630E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1279.39504 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40847 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10927 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.30000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13099 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48673E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.68183E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63932 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21402.60898 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.68183E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 831.18854 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46917 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.49189 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45767 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.22890 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.07281 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28376 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.14561 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.54310 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.90180 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.90180 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28568 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.72986 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.86942 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 97.45972 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 38.52697 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 83.46495 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 83.46495 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46159 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.10146 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28729 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.20291 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.88843 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.23835 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.23835 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.63739 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.81824 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.81824 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.81824 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 4.81824 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.81824 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.81824 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.22890 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.22890 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.22890 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.22890 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.22915 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.22915 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46917 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46917 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46917 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46917 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46917 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46917 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.49189 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.49189 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.49189 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.49189 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.49189 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.49189 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45767 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45767 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45767 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45767 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45767 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45767 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.90180 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 83.46495 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.23835 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.81824 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.22915 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46917 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.49189 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45767 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.90180 |
286 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.90771 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04617 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01496E-002 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 207567.51752 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.93640E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.90180 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 59234.79223 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29576E-003 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1216.63818 |
298 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.90180 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.93640E-003 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.02153E-005 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.29576E-003 |
302 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 83.46495 |
303 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.08347 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04683 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.03560E-002 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2017078.91718 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.76882E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 83.46495 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 542473.91172 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18666E-002 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11192.50159 |
315 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 83.46495 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.76882E-002 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.25456E-006 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.18666E-002 |
319 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.23835 |
320 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.77873 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04610 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01280E-002 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 213336.07998 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.10138E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.23835 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 52639.36870 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15149E-003 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1113.37571 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.23835 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.10138E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.80463E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.15149E-003 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.81824 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.77075 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42416 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02932E-002 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 105483.61450 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.01682E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.81824 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 248626.70553 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.43872E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7783.12346 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.81824 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.01682E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.57845E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.43872E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.22915 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.22915 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 429556.05050 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 310090.67244 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.05198E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.22915 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.22915 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.22915 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.22915 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 429556.05050 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 429556.05050 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 20749.82071 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.22915 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.22915 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 429556.05050 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.05198E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 20749.82071 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.72118E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46917 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46917 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9443.33404 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6831.78507 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31267E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46917 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46917 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46917 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46917 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9443.33404 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9443.33404 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46917 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46917 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9443.33404 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31267E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.49189 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.49189 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 90573.67091 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65463.15295 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21814E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.49189 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.49189 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.49189 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.49189 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90573.67091 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90573.67091 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 9585.55755 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.49189 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.49189 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 90573.67091 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21814E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9585.55755 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45767 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45767 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9224.17626 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6668.53395 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25899E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45767 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45767 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45767 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45767 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9224.17626 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9224.17626 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45767 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45767 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9224.17626 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25899E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.27428E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11759.08711 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.27428E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 8.72914 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.27428E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.27428E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 305338.07073 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.46111E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.55333 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.46111E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 16283.61956 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2496502.84201 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2496502.84000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.46111E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.27428E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 8.72914 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.63714E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4070.60629 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.63714E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4070.60629 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.27428E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.67210E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1287108.97903 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1293213.37500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.35777E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.27428E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.67210E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1287108.97903 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1293213.37500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.35777E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.31951E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.58341 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.31951E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3332.09187 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.31951E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59676.13656 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21454.36073 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 543525.39018 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 532964.22000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31951E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12716 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 15.25866 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12716 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31169.18767 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 47.13195 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1534377.33167 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.42639 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 191797.16646 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 47.13195 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1534377.33167 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.42639 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 191797.16646 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.64725E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.64725E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22645.93 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 638992.38 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 122588.85 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 20371.08 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 14025.40 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23000.96 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10979.22 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 369318.22 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 242687.98 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 365671.04 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 235422.67 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 46224.32 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 30284.68 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 45842.65 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 29783.29 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 59485.66 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 548290.80 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 55069.06 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 261656.26 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 228386.95 | 160372.60 | 68014.35 | 0.70 | 34879.30 | 353.77 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2174627.70 | 1517838.94 | 656788.75 | 0.70 | 330013.52 | 3347.18 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 236121.40 | 166060.56 | 70060.84 | 0.70 | 36174.81 | 366.91 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 119407.19 | 84965.34 | 34441.85 | 0.71 | 18125.72 | 183.84 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.80 | 23.21 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.80 | 23.21 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.940 | 0.824 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.908 | 0.800 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8989693273E-003 | 1.4598536207E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.2005017965E-003 | 6.1826574864E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.6269699332E-002 | 1.0021021094E-002 | Pass | Pass | 0.4878888932 | 0.4947100689 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.7529367403E-002 | 9.8106062448E-002 | Pass | Pass | 1.6900189449 | 7.3271535850 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.3697106506E-002 | 2.3641697575E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.5643123350E-002 | 8.2572443774E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1079208655 | 0.1202344302 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9364587201E-002 | 4.4045390161E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6354455854 | 0.5710479248 | Pass | Pass | 0.7250921048 | 0.6361217301 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5431906596 | 0.6184523727 | Pass | Pass | 0.9618537625 | 2.7028064224 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4433171681 | 0.5184726918 | Pass | Pass | 0.6965783931 | 0.7006358772 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5439672688 | 0.5724181618 | Pass | Pass | 0.7499397842 | 0.7307740649 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.8131956273 | 0.7101689395 | Pass | Pass | 0.6823990502 | 0.6065162671 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7259648898 | 0.7772208533 | Pass | Pass | 0.7365335724 | 0.6971198262 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5779261838 | 0.6869331832 | Pass | Pass | 4.6062337785 | 37.8986361919 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7298603909 | 0.7615531736 | Pass | Pass | 0.7351328403 | 0.7010360723 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0433970118E-002 | 7.0353158336E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7632770127E-002 | 4.9986522261E-002 | Pass | Pass | 0.4975331453 | 0.4900299375 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1525624392 | 0.1155663479 | Pass | Pass | 0.5257654530 | 0.4998831152 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.9700532208E-003 | 2.9296048243E-002 | Pass | Pass | 0.4937675180 | 2.3221742384 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2546273081E-002 | 1.0145522409E-002 | Pass | Pass | 4.7271941072E-003 | 5.6229278987E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7452987254E-002 | 1.3751760469E-002 | Pass | Pass | 6.3753895169E-003 | 7.3138373589E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4632256409E-005 | 1.0291198868E-005 | Pass | Pass | 9.2652362004E-005 | 1.1245138042E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6722.65 | 230.21 | 0.00 | 21164.82 | 13767.92 | 41885.60 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.824 | 0.940 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.800 | 0.908 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.7776 | 2779.43 | 16058.30 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 116.04 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.7776 | 24961.20 | 144214.83 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 1042.11 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.7776 | 2496.12 | 14421.48 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.50 | 0.0000 | Y | 104.21 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.34 | 0.0000 | Y | 7.60 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.29 | 0.0000 | Y | 4.88 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.09 | 0.0000 | Y | 7.51 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.11 | 0.0000 | Y | 4.84 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.7776 | 3134.13 | 18107.61 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.31 | 0.0000 | Y | 75.84 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.26 | 0.0000 | Y | 48.76 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.7776 | 3134.20 | 18108.01 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.07 | 0.0000 | Y | 75.03 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.7776 | 2019.75 | 11669.23 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.09 | 0.0000 | Y | 48.39 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.7776 | 313.41 | 1810.76 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.31 | 0.0000 | Y | 7.58 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.26 | 0.0000 | Y | 4.88 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.7776 | 313.42 | 1810.80 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.07 | 0.0000 | Y | 7.50 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.7776 | 201.98 | 1166.92 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 22.09 | 0.0000 | Y | 4.84 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.7776 | 783.68 | 4527.75 | LightsWired | LTG_SCH_OFFICE | 39.68 | 168.00 | 38.66 | 0.0000 | Y | 32.85 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.1736 | 362.03 | 2597.04 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 16.76 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.1736 | 36.20 | 259.70 | LightsWired | LTG_SCH_DATACENTER | 35.29 | 168.00 | 34.37 | 0.0000 | Y | 1.68 |
Interior Lighting Total | 5.7907 | 46320.38 | 268225.21 | 540.99 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.80 | 698.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.80 | 250.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1810.76 | 698.41 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1810.76 | 250.79 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1166.92 | 450.08 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1166.92 | 161.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 42.43 | 42.43 | 103.18 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.64 | 63.04 | 10.88 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.64 | 46.90 | 151.57 | |
Exterior Lighting Total | 31088.59 | 265.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2535632.03 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2496502.84 | 0.94 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1293213.38 | 6.59 | 1134443.07 | 5.87 | 6.80 | 23.21 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1293213.38 | 6.59 | 1134443.07 | 5.87 | 6.80 | 23.21 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 532964.22 | 0.94 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1534377.33 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1534377.33 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 207567.52 | 228386.95 | 160372.60 | 68014.35 | 0.70 | - | 34879.30 | 353.77 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2017078.92 | 2174627.70 | 1517838.94 | 656788.75 | 0.70 | - | 330013.52 | 3347.18 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 213336.08 | 236121.40 | 166060.56 | 70060.84 | 0.70 | - | 36174.81 | 366.91 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 105483.61 | 119407.19 | 84965.34 | 34441.85 | 0.71 | - | 18125.72 | 183.84 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 429556.05 | 310090.67 | 119465.38 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9443.33 | 6831.79 | 2611.55 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90573.67 | 65463.15 | 25110.52 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9224.18 | 6668.53 | 2555.64 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16267.74 | 22645.93 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 458955.50 | 638992.38 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 88094.47 | 122588.85 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14638.95 | 20371.08 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10078.85 | 14025.40 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16528.81 | 23000.96 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7889.84 | 10979.22 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 265396.46 | 369318.22 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 174398.45 | 242687.98 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 262775.57 | 365671.04 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 169177.53 | 235422.67 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 33217.32 | 46224.32 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 21762.91 | 30284.68 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32943.05 | 45842.65 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 21402.61 | 29783.29 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 59234.79 | 59485.66 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 542473.91 | 548290.80 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 52639.37 | 55069.06 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 248626.71 | 261656.26 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 429556.05 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9443.33 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 90573.67 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9224.18 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 20749.82 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 9585.56 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.90 | 19236.31 | 2160.95 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 83.46 | 180363.32 | 2160.95 | 1.00 | 1.08 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.24 | 19963.59 | 2160.95 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 4.82 | 8170.07 | 1695.65 | 1.00 | 1.17 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.23 | 35197.36 | 1657.97 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 525.52 | 1120.11 | 1.00 | 1.64 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.49 | 5031.40 | 1120.11 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 512.65 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.072743 | 11759.09 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.054611 | 16283.62 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.036371 | 4070.61 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.036371 | 4070.61 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013195 | 3332.09 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.127155 | 31169.19 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 66929.88 | 66929.88 | 24.08 | 4.818 | 4.818 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00903 | 26.62 | 0.01411 | 1.200 | 0.00 |
CORE_BOTTOM | 72660.16 | 72660.16 | 29.11 | 5.231 | 5.231 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 26.62 | 0.01411 | 1.078 | 0.00 |
CORE_MID | 681530.76 | 681530.76 | 273.04 | 49.052 | 49.052 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 26.62 | 0.01411 | 10.778 | 0.00 |
CORE_TOP | 69426.18 | 69426.18 | 27.81 | 4.997 | 4.997 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 26.62 | 0.01411 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12892.66 | 12892.66 | 41.14 | 0.937 | 0.937 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00897 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16153.56 | 16153.56 | 79.98 | 1.174 | 1.174 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00875 | 27.80 | 0.01411 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18650.15 | 18650.15 | 59.51 | 1.356 | 1.356 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00883 | 31.73 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19909.10 | 19909.10 | 98.57 | 1.447 | 1.447 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00870 | 31.36 | 0.01412 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 124007.14 | 124007.14 | 395.67 | 9.015 | 9.015 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00921 | 32.10 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 173629.03 | 173629.03 | 859.66 | 12.623 | 12.623 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00885 | 28.24 | 0.01411 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 186365.55 | 186365.55 | 594.62 | 13.549 | 13.549 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00898 | 31.79 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 181874.05 | 181874.05 | 900.48 | 13.222 | 13.222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00883 | 31.26 | 0.01412 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14205.29 | 14205.29 | 45.32 | 1.033 | 1.033 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00920 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17695.45 | 17695.45 | 87.61 | 1.286 | 1.286 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00889 | 28.45 | 0.01411 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20327.18 | 20327.18 | 64.86 | 1.478 | 1.478 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00900 | 31.85 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19373.63 | 19373.63 | 95.92 | 1.408 | 1.408 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00885 | 31.26 | 0.01412 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8183.13 | 8183.13 | 226.04 | 0.469 | 0.469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78346.34 | 78346.34 | 2164.10 | 4.492 | 4.492 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7982.68 | 7982.68 | 220.50 | 0.458 | 0.458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00859 | 29.77 | 0.01412 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370278.21 | 370278.21 | 472.49 | 21.229 | 21.229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 25.37 | 0.01411 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 23.76 | 0.00150 | -10.70 | 0.00150 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 17.60 | 21.22 | 0.00150 | -10.70 | 0.00150 | 1.078 | 0.00 |
CORE_MID | 296049.07 | 296049.07 | 118.60 | 12.496 | 12.496 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 61698.64 | 61698.64 | 24.72 | 2.623 | 2.623 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10254.70 | 10254.70 | 32.72 | 0.437 | 0.437 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00708 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7059.53 | 7059.53 | 34.95 | 0.301 | 0.301 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00715 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 11575.94 | 11575.94 | 36.93 | 0.493 | 0.493 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00724 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5529.63 | 5529.63 | 27.38 | 0.235 | 0.235 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00672 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 185805.65 | 185805.65 | 592.85 | 7.925 | 7.925 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00715 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 122096.86 | 122096.86 | 604.51 | 5.208 | 5.208 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00714 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 183973.00 | 183973.00 | 586.99 | 7.846 | 7.846 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00714 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 118445.93 | 118445.93 | 586.44 | 5.052 | 5.052 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00712 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 23252.93 | 23252.93 | 74.19 | 0.992 | 0.992 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15234.62 | 15234.62 | 75.43 | 0.650 | 0.650 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 20.99 | 0.00715 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23061.14 | 23061.14 | 73.58 | 0.984 | 0.984 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14982.63 | 14982.63 | 74.18 | 0.639 | 0.639 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 20.99 | 0.00714 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 25.48 | 0.00777 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.78 | 0.00200 | -10.70 | 0.00150 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.99 | 0.00199 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 18.00 | 27.00 | 0.00850 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.90 | 8.90 | 2.54 | 2.54 | 8.9018 | 2.5431 | 8.9018 | 0.2857 | 0.3000 |
VAV_MID WITH REHEAT | 83.46 | 83.46 | 38.53 | 38.53 | 83.4650 | 38.5270 | 83.4650 | 0.4616 | 0.3000 |
VAV_TOP WITH REHEAT | 9.24 | 9.24 | 5.89 | 5.89 | 9.2384 | 5.8884 | 9.2384 | 0.6374 | 0.3000 |
CAV_BAS | 4.82 | 4.82 | 1.20 | 1.20 | 4.8182 | 4.8182 | 4.8182 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.23 | 21.23 | 0.34 | 0.34 | 21.2291 | 21.2289 | 21.2291 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4692 | 0.4692 | 0.4692 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.49 | 4.49 | 0.16 | 0.16 | 4.4919 | 4.4919 | 4.4919 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4577 | 0.4577 | 0.4577 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16267.744 | 16267.744 | 1.616426 | 0.00035586 | 454.034 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 16267.74 | 16267.74 | 1.616426 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16295.66 | 16295.66 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 458955.498 | 458955.498 | 16.187010 | 0.01003966 | 16297.031 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 458955.50 | 458955.50 | 16.187010 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 296049.07 | 0.00 | 460014.93 | 460014.93 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 88094.470 | 88094.470 | 2.622792 | 0.00192707 | 3428.549 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 88094.47 | 88094.47 | 2.622792 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 61698.64 | 0.00 | 88282.03 | 88282.03 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14638.954 | 14638.954 | 0.436538 | 0.00032023 | 569.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14638.95 | 14638.95 | 0.436538 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00707771 | 45.8092 | 10254.70 | 0.00 | 14670.13 | 14670.13 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10078.849 | 10078.849 | 0.300588 | 0.00022048 | 391.822 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10078.85 | 10078.85 | 0.300588 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00714828 | 46.2605 | 7059.53 | 0.00 | 10100.31 | 10100.31 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16528.813 | 16528.813 | 0.492982 | 0.00036157 | 642.542 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16528.81 | 16528.81 | 0.492982 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00724447 | 46.8751 | 11575.94 | 0.00 | 16564.01 | 16564.01 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7889.836 | 7889.836 | 0.235171 | 0.00017259 | 306.835 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7889.84 | 7889.84 | 0.235171 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00672444 | 43.5486 | 5529.63 | 0.00 | 7906.64 | 7906.64 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 265396.465 | 265396.465 | 7.924824 | 0.00580555 | 10309.289 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 265396.46 | 265396.46 | 7.924824 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00715012 | 46.2757 | 185805.65 | 0.00 | 265961.76 | 265961.76 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 174398.452 | 174398.452 | 5.207798 | 0.00381497 | 6774.313 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 174398.45 | 174398.45 | 5.207798 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00714044 | 46.2140 | 122096.86 | 0.00 | 174769.92 | 174769.92 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 262775.569 | 262775.569 | 7.846453 | 0.00574822 | 10207.573 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 262775.57 | 262775.57 | 7.846453 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00714233 | 46.2259 | 183973.00 | 0.00 | 263335.28 | 263335.28 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 169177.530 | 169177.530 | 5.051720 | 0.00370076 | 6571.658 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 169177.53 | 169177.53 | 5.051720 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00711614 | 46.0587 | 118445.93 | 0.00 | 169537.88 | 169537.88 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 33217.316 | 33217.316 | 0.992217 | 0.00072663 | 1290.039 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33217.32 | 33217.32 | 0.992217 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716151 | 46.3507 | 23252.93 | 0.00 | 33288.07 | 33288.07 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 21762.910 | 21762.910 | 0.650088 | 0.00047606 | 845.175 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21762.91 | 21762.91 | 0.650088 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 20.99 | 0.00714878 | 46.2696 | 15234.62 | 0.00 | 21809.27 | 21809.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 32943.049 | 32943.049 | 0.984016 | 0.00072063 | 1279.395 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32943.05 | 32943.05 | 0.984016 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00715537 | 46.3113 | 23061.14 | 0.00 | 33013.22 | 33013.22 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 21402.609 | 21402.609 | 0.639319 | 0.00046818 | 831.189 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21402.61 | 21402.61 | 0.639319 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 20.99 | 0.00713658 | 46.1916 | 14982.63 | 0.00 | 21448.20 | 21448.20 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 207567.518 | -999.000 | 8.901796 | 0.00593640 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 207567.52 | 161183.44 | 8.901796 | 25.91 | 18.40 | 0.01014956 | 11.05 | 11.05 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 22.8100 | 24.00 | 0.00892552 | 47.9959 | 118530.53 | 0.00 | 207835.82 | 158345.90 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 59234.792 | 59234.792 | 2.670539 | 0.00129576 | 1216.638 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59234.79 | 59234.79 | 2.670539 | -5.54 | -5.90 | 0.00216588 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 76.0333 | 21.07 | 0.00516330 | 33.3697 | 30076.19 | 0.00 | 51800.41 | 51800.41 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2017078.917 | -999.000 | 83.464953 | 0.05768820 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2017078.92 | 1528201.15 | 83.464953 | 26.08 | 18.62 | 0.01035603 | 11.05 | 11.05 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 24.3288 | 24.00 | 0.00905152 | 48.6650 | 1085227.32 | 0.00 | 2020176.22 | 1504099.28 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 542473.912 | 542473.912 | 25.039486 | 0.01186663 | 11192.502 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 542473.91 | 542473.91 | 25.039486 | -5.11 | -5.11 | 0.00255773 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 81.0959 | 18.04 | 0.00691538 | 53.8085 | 277069.42 | 0.00 | 477505.99 | 477505.99 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 213336.080 | -999.000 | 9.238352 | 0.00610138 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 213336.08 | 165818.79 | 9.238352 | 25.78 | 18.34 | 0.01012798 | 11.05 | 11.05 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 21.9790 | 24.00 | 0.00900350 | 48.4108 | 127083.08 | 0.00 | 213618.11 | 162866.35 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 52639.369 | 52639.369 | 2.771506 | 0.00115149 | 1113.376 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 02:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52639.37 | 52639.37 | 2.771506 | -2.90 | -2.90 | 0.00296220 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 73.2634 | 16.37 | 0.00700699 | 60.5972 | 28635.48 | 0.00 | 47967.07 | 47967.07 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 105483.615 | -999.000 | 4.818240 | 0.00301682 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 105483.61 | 78746.58 | 4.818240 | 24.77 | 18.14 | 0.01029319 | 11.42 | 11.42 | 0.00850000 | 27.09 | 0.01411064 | 21.71 | 24.9086 | 24.00 | 0.00902369 | 48.5158 | 66157.53 | 0.00 | 105627.89 | 78013.55 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 248626.706 | 248626.706 | 4.818240 | 0.00543872 | 7783.123 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 248626.71 | 248626.71 | 4.818240 | -2.67 | -5.25 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 24.9086 | 23.86 | 0.00150390 | 8.2513 | 0.00 | 0.00 | 187537.27 | 187537.27 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 429556.050 | 310090.672 | 21.229150 | 0.01051980 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 402069.73 | 394390.91 | -999.0 | 28.48 | 18.04 | 0.00863141 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | -999.0000 | 27.00 | 0.00854243 | 38.4650 | 369906.15 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9443.334 | 6831.785 | 0.469166 | 0.00023127 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8830.56 | 8478.82 | -999.0 | 28.03 | 18.00 | 0.00877264 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | -999.0000 | 27.00 | 0.00858850 | 38.6673 | 8183.13 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90573.671 | 65463.153 | 4.491886 | 0.00221814 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 84721.47 | 81205.86 | -999.0 | 28.03 | 18.01 | 0.00878459 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | -999.0000 | 27.00 | 0.00859239 | 38.6847 | 78346.34 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9224.176 | 6668.534 | 0.457675 | 0.00022590 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 8627.55 | 8276.00 | -999.0 | 28.04 | 18.01 | 0.00877931 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01411544 | 22.48 | -999.0000 | 27.00 | 0.00859061 | 38.6767 | 7982.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 429556.050 | 429556.050 | 21.229150 | 0.01051980 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 429556.05 | 429556.05 | 21.229150 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5940 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9443.334 | 9443.334 | 0.469166 | 0.00023127 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9443.33 | 9443.33 | 0.469166 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3319 | 26.06 | 0.00776501 | 36.9981 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90573.671 | 90573.671 | 4.491886 | 0.00221814 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 90573.67 | 90573.67 | 4.491886 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4801 | 23.91 | 0.00199517 | 10.9048 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9224.176 | 9224.176 | 0.457675 | 0.00022590 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9224.18 | 9224.18 | 0.457675 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4156 | 22.89 | 0.00199486 | 11.5933 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20749.82 | 20749.82 | 21.229150 | -0.17 | -0.17 | 0.00838848 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5940 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.469166 | -0.36 | -0.36 | 0.00755639 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3319 | 26.06 | 0.00776501 | 36.9981 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9585.56 | 9585.56 | 4.491886 | -0.37 | -3.04 | 0.00197807 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4801 | 23.91 | 0.00199517 | 10.9048 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.457675 | -0.37 | -3.03 | 0.00197809 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4156 | 22.89 | 0.00199486 | 11.5933 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16267.744 | 16267.744 | 1.616426 | 0.00035586 | 454.034 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 0.6388 | 0.651621 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 16267.74 | 16267.74 | 1.0000 | 1.94552185 | 1.616426 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.35582105 | 60.00 | 48.89 | 11.11 | 0.000 | 16267.74 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16295.66 | 16295.66 | 1.94552185 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 458955.498 | 458955.498 | 16.187010 | 0.01003966 | 16297.031 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 18.0213 | 18.383937 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 458955.50 | 458955.50 | 1.0000 | 19.48260399 | 16.187010 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 10.03864013 | 60.00 | 48.89 | 11.11 | 0.000 | 458955.50 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 296049.07 | 0.00 | 460014.93 | 460014.93 | 19.48260399 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.96 | 19.96 | 0.00800000 | 56671.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 88094.470 | 88094.470 | 2.622792 | 0.00192707 | 3428.549 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 3.4591 | 3.528715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 88094.47 | 88094.47 | 1.0000 | 3.15677903 | 2.622792 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.92687240 | 60.00 | 48.89 | 11.11 | 0.000 | 88094.47 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 61698.64 | 0.00 | 88282.03 | 88282.03 | 3.15677903 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61025.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14638.954 | 14638.954 | 0.436538 | 0.00032023 | 569.141 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 0.5748 | 0.586378 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14638.95 | 14638.95 | 1.0000 | 0.52541477 | 0.436538 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.32019485 | 60.00 | 48.89 | 11.11 | 0.000 | 14638.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00707771 | 21.00 | 0.00707771 | 45.8092 | 10254.70 | 0.00 | 14670.13 | 14670.13 | 0.52541477 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10078.849 | 10078.849 | 0.300588 | 0.00022048 | 391.822 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 0.3958 | 0.403719 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10078.85 | 10078.85 | 1.0000 | 0.36178679 | 0.300588 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.22045261 | 60.00 | 48.89 | 11.11 | 0.000 | 10078.85 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.90 | 0.00714828 | 21.00 | 0.00714828 | 46.2605 | 7059.53 | 0.00 | 10100.31 | 10100.31 | 0.36178679 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16528.813 | 16528.813 | 0.492982 | 0.00036157 | 642.542 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 0.6490 | 0.662079 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16528.81 | 16528.81 | 1.0000 | 0.59335099 | 0.492982 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.36153135 | 60.00 | 48.89 | 11.11 | 0.000 | 16528.81 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00724447 | 21.00 | 0.00724447 | 46.8751 | 11575.94 | 0.00 | 16564.01 | 16564.01 | 0.59335099 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7889.836 | 7889.836 | 0.235171 | 0.00017259 | 306.835 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 0.3098 | 0.316036 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7889.84 | 7889.84 | 1.0000 | 0.28305101 | 0.235171 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.17257277 | 60.00 | 48.89 | 11.11 | 0.000 | 7889.84 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00672444 | 21.00 | 0.00672444 | 43.5486 | 5529.63 | 0.00 | 7906.64 | 7906.64 | 0.28305101 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 265396.465 | 265396.465 | 7.924824 | 0.00580555 | 10309.289 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 10.4210 | 10.630730 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 265396.46 | 265396.46 | 1.0000 | 9.53827828 | 7.924824 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 5.80496281 | 60.00 | 48.89 | 11.11 | 0.000 | 265396.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00715012 | 21.00 | 0.00715012 | 46.2757 | 185805.65 | 0.00 | 265961.76 | 265961.76 | 9.53827828 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.23 | 0.00800000 | 60943.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 174398.452 | 174398.452 | 5.207798 | 0.00381497 | 6774.313 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 6.8479 | 6.985710 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 174398.45 | 174398.45 | 1.0000 | 6.26807959 | 5.207798 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 3.81458182 | 60.00 | 48.89 | 11.11 | 0.000 | 174398.45 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00714044 | 21.00 | 0.00714044 | 46.2140 | 122096.86 | 0.00 | 174769.92 | 174769.92 | 6.26807959 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60942.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 262775.569 | 262775.569 | 7.846453 | 0.00574822 | 10207.573 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 10.3181 | 10.525747 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 262775.57 | 262775.57 | 1.0000 | 9.44395162 | 7.846453 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 5.74763650 | 60.00 | 48.89 | 11.11 | 0.000 | 262775.57 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00714233 | 21.00 | 0.00714233 | 46.2259 | 183973.00 | 0.00 | 263335.28 | 263335.28 | 9.44395162 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.15 | 21.23 | 0.00800000 | 60943.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 169177.530 | 169177.530 | 5.051720 | 0.00370076 | 6571.658 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 6.6429 | 6.776581 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 169177.53 | 169177.53 | 1.0000 | 6.08022473 | 5.051720 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 3.70038566 | 60.00 | 48.89 | 11.11 | 0.000 | 169177.53 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00711614 | 21.00 | 0.00711614 | 46.0587 | 118445.93 | 0.00 | 169537.88 | 169537.88 | 6.08022473 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.23 | 0.00800000 | 60943.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33217.316 | 33217.316 | 0.992217 | 0.00072663 | 1290.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 1.3043 | 1.330554 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33217.32 | 33217.32 | 1.0000 | 1.19422738 | 0.992217 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.72655558 | 60.00 | 48.89 | 11.11 | 0.000 | 33217.32 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00716151 | 21.00 | 0.00716151 | 46.3507 | 23252.93 | 0.00 | 33288.07 | 33288.07 | 1.19422738 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60934.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21762.910 | 21762.910 | 0.650088 | 0.00047606 | 845.175 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 0.8545 | 0.871736 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21762.91 | 21762.91 | 1.0000 | 0.78244283 | 0.650088 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.47601570 | 60.00 | 48.89 | 11.11 | 0.000 | 21762.91 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00714878 | 20.99 | 0.00714878 | 46.2696 | 15234.62 | 0.00 | 21809.27 | 21809.27 | 0.78244283 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.13 | 21.22 | 0.00800000 | 60933.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32943.049 | 32943.049 | 0.984016 | 0.00072063 | 1279.395 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 1.2935 | 1.319568 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32943.05 | 32943.05 | 1.0000 | 1.18435651 | 0.984016 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.72055661 | 60.00 | 48.89 | 11.11 | 0.000 | 32943.05 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00715537 | 21.00 | 0.00715537 | 46.3113 | 23061.14 | 0.00 | 33013.22 | 33013.22 | 1.18435651 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.14 | 21.22 | 0.00800000 | 60934.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21402.609 | 21402.609 | 0.639319 | 0.00046818 | 831.189 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 0.8404 | 0.857304 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21402.61 | 21402.61 | 1.0000 | 0.76948090 | 0.639319 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.46813491 | 60.00 | 48.89 | 11.11 | 0.000 | 21402.61 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00713658 | 20.99 | 0.00713658 | 46.1916 | 14982.63 | 0.00 | 21448.20 | 21448.20 | 0.76948090 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.13 | 21.22 | 0.00800000 | 60933.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 207567.518 | -999.000 | 8.901796 | 0.00593640 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7075 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.901796 | 10.71415653 | 4197.9300 | 999.8980 | 72.73538881 | 15.00 | 6.67 | 8.33 | 2543466.13 | 8.1608 | 8.160813 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 207567.52 | 161183.44 | 1.0000 | 10.71415653 | 8.901796 | 25.91 | 18.40 | 0.01014956 | 51905.4 | 11.05 | 11.05 | 0.00850000 | 32532.2 | 5.93579915 | 6.67 | 15.00 | 8.33 | 19236.306 | 188331.21 | 32.10 | 0.01411964 | 23.13 | 2.03050000 | 22.8100 | 24.00 | 0.00892552 | 24.00 | 0.00892552 | 47.9959 | 118530.53 | 0.00 | 207835.82 | 158345.90 | 10.71415653 | 25.91 | 18.41 | 0.01014956 | 51905.4 | 11.47 | 11.36 | 0.00831823 | 32507.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 59234.792 | 59234.792 | 2.670539 | 0.00129576 | 1216.638 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.901796 | 10.71415653 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 2.3259 | 2.372711 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59234.79 | 59234.79 | 1.0000 | 3.21424696 | 2.670539 | -5.54 | -5.90 | 0.00216588 | -172.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.29563054 | 60.00 | 48.89 | 11.11 | 0.000 | 59234.79 | -10.70 | 0.00150390 | -10.70 | 2.03050000 | 76.0333 | 10.83 | 0.00426600 | 21.07 | 0.00516330 | 33.3697 | 30076.19 | 0.00 | 51800.41 | 51800.41 | 3.21424696 | 2.80 | -0.92 | 0.00216588 | 8241.6 | 18.77 | 7.88 | 0.00216588 | 24357.4 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2017078.917 | -999.000 | 83.464953 | 0.05768820 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0913 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.464953 | 100.45799829 | 4197.9300 | 999.8980 | 72.73538881 | 15.00 | 6.67 | 8.33 | 2543466.13 | 79.3043 | 79.304336 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2017078.92 | 1528201.15 | 1.0000 | 100.45799829 | 83.464953 | 26.08 | 18.62 | 0.01035603 | 52611.7 | 11.05 | 11.05 | 0.00850000 | 32532.8 | 57.68231690 | 6.67 | 15.00 | 8.33 | 180363.318 | 1836715.60 | 32.10 | 0.01411964 | 23.13 | 20.30600000 | 24.3288 | 24.00 | 0.00905152 | 24.00 | 0.00905152 | 48.6650 | 1085227.32 | 0.00 | 2020176.22 | 1504099.28 | 100.45799829 | 26.08 | 18.63 | 0.01035603 | 52611.7 | 11.46 | 11.36 | 0.00831926 | 32502.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 542473.912 | 542473.912 | 25.039486 | 0.01186663 | 11192.502 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.464953 | 100.45799829 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 21.3007 | 21.729353 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 542473.91 | 542473.91 | 1.0000 | 30.13739949 | 25.039486 | -5.11 | -5.11 | 0.00255773 | 1234.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 11.86542137 | 60.00 | 48.89 | 11.11 | 0.000 | 542473.91 | -10.70 | 0.00150390 | -10.70 | 20.30600000 | 81.0959 | 18.85 | 0.00707854 | 18.04 | 0.00691538 | 53.8085 | 277069.42 | 0.00 | 477505.99 | 477505.99 | 30.13739949 | 2.80 | -0.33 | 0.00255773 | 9223.6 | 18.49 | 8.20 | 0.00255773 | 25067.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 213336.080 | -999.000 | 9.238352 | 0.00610138 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6674 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.238352 | 11.11923407 | 4197.9300 | 999.8980 | 72.73538881 | 15.00 | 6.67 | 8.33 | 2543466.13 | 8.3876 | 8.387612 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 213336.08 | 165818.79 | 1.0000 | 11.11923407 | 9.238352 | 25.78 | 18.34 | 0.01012798 | 51718.3 | 11.05 | 11.05 | 0.00850000 | 32532.1 | 6.10076248 | 6.67 | 15.00 | 8.33 | 19963.587 | 193372.49 | 32.10 | 0.01411964 | 23.13 | 2.03050000 | 21.9790 | 24.00 | 0.00900350 | 24.00 | 0.00900350 | 48.4108 | 127083.08 | 0.00 | 213618.11 | 162866.35 | 11.11923407 | 25.78 | 18.35 | 0.01012798 | 51718.3 | 11.47 | 11.36 | 0.00831837 | 32506.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52639.369 | 52639.369 | 2.771506 | 0.00115149 | 1113.376 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.238352 | 11.11923407 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 2.0669 | 2.108524 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 02:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52639.37 | 52639.37 | 1.0000 | 3.33577022 | 2.771506 | -2.90 | -2.90 | 0.00296220 | 4474.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.15137019 | 60.00 | 48.89 | 11.11 | 0.000 | 52639.37 | -10.70 | 0.00150390 | -10.70 | 2.03050000 | 73.2634 | 18.46 | 0.00695823 | 16.37 | 0.00700699 | 60.5972 | 28635.48 | 0.00 | 47967.07 | 47967.07 | 3.33577022 | 2.80 | 0.47 | 0.00296220 | 10237.3 | 17.03 | 7.98 | 0.00296220 | 24616.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 105483.615 | -999.000 | 4.818240 | 0.00301682 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9745 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 4.818240 | 5.79920993 | 4197.9300 | 999.8980 | 72.73538881 | 15.00 | 6.67 | 8.33 | 2543466.13 | 4.1472 | 4.147239 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 105483.61 | 78746.58 | 1.0000 | 5.79920993 | 4.818240 | 24.77 | 18.14 | 0.01029319 | 51107.3 | 11.42 | 11.42 | 0.00850000 | 32918.0 | 3.01651028 | 6.67 | 15.00 | 8.33 | 8170.070 | 97313.54 | 27.09 | 0.01411064 | 21.71 | 1.20015641 | 24.9086 | 24.00 | 0.00902369 | 24.00 | 0.00902369 | 48.5158 | 66157.53 | 0.00 | 105627.89 | 78013.55 | 5.79920993 | 24.77 | 18.14 | 0.01029319 | 51107.3 | 11.63 | 11.52 | 0.00840553 | 32893.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 248626.706 | 248626.706 | 4.818240 | 0.00543872 | 7783.123 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 4.818240 | 5.79920993 | 4197.9300 | 999.8980 | 54.60549814 | 48.89 | 60.00 | 11.11 | 2546745.95 | 9.7625 | 9.958999 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 248626.71 | 248626.71 | 1.0000 | 5.79920993 | 4.818240 | -2.67 | -5.25 | 0.00150390 | 1075.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 5.43816129 | 60.00 | 48.89 | 11.11 | 0.000 | 248626.71 | -10.70 | 0.00150390 | -10.70 | 1.20015641 | 24.9086 | 0.00 | 0.00150390 | 23.86 | 0.00150390 | 8.2513 | 0.00 | 0.00 | 187537.27 | 187537.27 | 5.79920993 | 12.80 | 4.04 | 0.00150390 | 16658.9 | 44.89 | 17.67 | 0.00150390 | 48997.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 429556.050 | 310090.672 | 21.229150 | 0.01051980 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8854 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 402069.73 | 394390.91 | 0.9360 | -999.0 | -999.0 | 28.48 | 18.04 | 0.00863141 | 50661.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 402069.73 | 32.10 | 0.01411964 | 23.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854243 | 27.00 | 0.00854243 | 38.4650 | 369906.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9443.334 | 6831.785 | 0.469166 | 0.00023127 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1479 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8830.56 | 8478.82 | 0.9351 | -999.0 | -999.0 | 28.03 | 18.00 | 0.00877264 | 50563.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8830.56 | 29.58 | 0.01411511 | 22.43 | 0.01563234 | -999.0000 | 27.00 | 0.00858850 | 27.00 | 0.00858850 | 38.6673 | 8183.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90573.671 | 65463.153 | 4.491886 | 0.00221814 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1701 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 84721.47 | 81205.86 | 0.9354 | -999.0 | -999.0 | 28.03 | 18.01 | 0.00878459 | 50598.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84721.47 | 29.58 | 0.01411511 | 22.43 | 0.15632344 | -999.0000 | 27.00 | 0.00859239 | 27.00 | 0.00859239 | 38.6847 | 78346.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9224.176 | 6668.534 | 0.457675 | 0.00022590 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1603 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 8627.55 | 8276.00 | 0.9353 | -999.0 | -999.0 | 28.04 | 18.01 | 0.00877931 | 50589.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8627.55 | 29.77 | 0.01411544 | 22.48 | 0.01563234 | -999.0000 | 27.00 | 0.00859061 | 27.00 | 0.00859061 | 38.6767 | 7982.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 429556.050 | 429556.050 | 21.229150 | 0.01051980 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 429556.05 | 429556.05 | 1.0000 | 25.55129792 | 21.229150 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 429556.05 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.5940 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9443.334 | 9443.334 | 0.469166 | 0.00023127 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9443.33 | 9443.33 | 1.0000 | 0.56468604 | 0.469166 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9443.33 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3319 | 0.00 | 0.00776501 | 26.06 | 0.00776501 | 36.9981 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90573.671 | 90573.671 | 4.491886 | 0.00221814 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 90573.67 | 90573.67 | 1.0000 | 5.40641105 | 4.491886 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90573.67 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.4801 | 0.00 | 0.00199517 | 23.91 | 0.00199517 | 10.9048 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9224.176 | 9224.176 | 0.457675 | 0.00022590 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9224.18 | 9224.18 | 1.0000 | 0.55085506 | 0.457675 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9224.18 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.4156 | 0.00 | 0.00199486 | 22.89 | 0.00199486 | 11.5933 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.229150 | 25.55129792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 20749.82 | 20749.82 | 1.0000 | 25.55129792 | 21.229150 | -0.17 | -0.17 | 0.00838848 | 20805.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20749.82 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.5940 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.469166 | 0.56468604 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.56468604 | 0.469166 | -0.36 | -0.36 | 0.00755639 | 18534.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3319 | 0.00 | 0.00776501 | 26.06 | 0.00776501 | 36.9981 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.491886 | 5.40641105 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9585.56 | 9585.56 | 1.0000 | 5.40641105 | 4.491886 | -0.37 | -3.04 | 0.00197807 | 4571.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9585.56 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.4801 | 0.00 | 0.00199517 | 23.91 | 0.00199517 | 10.9048 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.457675 | 0.55085506 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.55085506 | 0.457675 | -0.37 | -3.03 | 0.00197809 | 4578.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.4156 | 0.00 | 0.00199486 | 22.89 | 0.00199486 | 11.5933 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.90 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 83.46 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 9.24 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 4.82 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialEnthalpy | 0.34 | 21.23 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2860.50 | 1949.50 | 655.00 |
CORE_BOTTOM | 2719.50 | 1328.67 | 12.00 |
CORE_MID | 2290.83 | 2877.50 | 130.83 |
CORE_TOP | 2746.33 | 3334.17 | 751.50 |
PERIMETER_BOT_ZN_3 | 2584.50 | 2975.17 | 348.67 |
PERIMETER_BOT_ZN_2 | 2808.50 | 2845.00 | 415.67 |
PERIMETER_BOT_ZN_1 | 3051.17 | 2461.17 | 422.83 |
PERIMETER_BOT_ZN_4 | 3288.67 | 1884.00 | 432.17 |
PERIMETER_MID_ZN_3 | 3510.33 | 3697.33 | 1739.33 |
PERIMETER_MID_ZN_2 | 3021.50 | 2948.67 | 1346.67 |
PERIMETER_MID_ZN_1 | 3386.50 | 2944.17 | 1054.00 |
PERIMETER_MID_ZN_4 | 3487.00 | 3244.33 | 1298.33 |
PERIMETER_TOP_ZN_3 | 3933.83 | 3882.17 | 2272.17 |
PERIMETER_TOP_ZN_2 | 3910.83 | 3564.17 | 1924.67 |
PERIMETER_TOP_ZN_1 | 3661.00 | 3195.67 | 1503.67 |
PERIMETER_TOP_ZN_4 | 3825.17 | 3456.33 | 1770.67 |
DATACENTER_BOT_ZN_6 | 5909.33 | 816.17 | 816.17 |
DATACENTER_MID_ZN_6 | 5404.50 | 244.33 | 157.50 |
DATACENTER_TOP_ZN_6 | 4883.33 | 583.67 | 335.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5527.67 | 5527.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5928.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 49.00 | 0.00 | 5.50 |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_MID | 2.83 | 0.00 | 1.67 | 0.00 |
CORE_TOP | 10.17 | 0.00 | 2.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.83 | 3.83 | 0.17 | 3.33 |
PERIMETER_BOT_ZN_2 | 0.83 | 39.83 | 0.00 | 39.17 |
PERIMETER_BOT_ZN_1 | 1.50 | 51.50 | 0.17 | 49.50 |
PERIMETER_BOT_ZN_4 | 0.17 | 141.50 | 0.00 | 67.50 |
PERIMETER_MID_ZN_3 | 64.17 | 2.83 | 15.33 | 2.50 |
PERIMETER_MID_ZN_2 | 56.00 | 42.33 | 2.67 | 41.50 |
PERIMETER_MID_ZN_1 | 28.17 | 61.50 | 2.17 | 60.00 |
PERIMETER_MID_ZN_4 | 27.83 | 43.67 | 3.00 | 27.17 |
PERIMETER_TOP_ZN_3 | 169.83 | 11.17 | 45.67 | 9.33 |
PERIMETER_TOP_ZN_2 | 104.00 | 44.67 | 16.33 | 41.50 |
PERIMETER_TOP_ZN_1 | 83.50 | 45.00 | 9.33 | 41.00 |
PERIMETER_TOP_ZN_4 | 72.00 | 47.83 | 12.83 | 29.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 5.50 | 0.00 | 5.50 |
DATACENTER_MID_ZN_6 | 0.00 | 2.50 | 0.00 | 2.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 1.00 | 0.00 | 1.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 309.17 | 0.00 | 272.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 213.17 | 615.17 | 48.67 | 455.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.020 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.748 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.586 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.578 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.747 | 0.055 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.016 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.174 | 0.055 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.536 | 0.057 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.661 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.923 | 0.142 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.124 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.050 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.676 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.002 | 0.165 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.121 | 0.160 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.060 | 0.165 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 19.992 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41649163.70 | 0.00 | 41649163.70 | 0.00 | 41649163.70 | 37848132.68 | 4099.90 | 1499.22 | 3160.88 | 202.50 |
CORE_BOTTOM | 31191160.96 | 0.00 | 31191160.96 | 0.00 | 31191160.96 | 33990283.35 | 5002.41 | 178.07 | 3579.52 | 256.14 |
CORE_MID | 0.24E+09 | 0.00 | 0.24E+09 | 0.00 | 0.24E+09 | 0.34E+09 | 5545.36 | 757.31 | 2457.32 | 209.05 |
CORE_TOP | 23559209.52 | 0.00 | 23559209.52 | 0.00 | 23559209.52 | 33990283.35 | 5632.29 | 884.00 | 2243.71 | 309.95 |
PERIMETER_BOT_ZN_3 | 3897404.98 | 0.00 | 3897404.98 | 542909.24 | 4440314.22 | 4267819.30 | 5205.80 | 237.95 | 3316.25 | 256.14 |
PERIMETER_BOT_ZN_2 | 3381961.96 | 0.00 | 3381961.96 | 361939.24 | 3743901.20 | 2750345.05 | 5116.67 | 336.49 | 3306.84 | 256.14 |
PERIMETER_BOT_ZN_1 | 6045100.88 | 0.00 | 6045100.88 | 542909.24 | 6588010.12 | 4267912.63 | 4705.77 | 228.61 | 3825.62 | 256.14 |
PERIMETER_BOT_ZN_4 | 5105719.67 | 0.00 | 5105719.67 | 361939.24 | 5467658.92 | 2750345.05 | 4262.34 | 285.35 | 4212.31 | 256.14 |
PERIMETER_MID_ZN_3 | 33915765.62 | 0.00 | 33915765.62 | 1273269.14 | 35189034.77 | 42678193.03 | 4804.90 | 831.03 | 3124.07 | 209.05 |
PERIMETER_MID_ZN_2 | 30564660.06 | 0.00 | 30564660.06 | 848845.52 | 31413505.58 | 27503450.52 | 4902.55 | 552.49 | 3304.96 | 762.91 |
PERIMETER_MID_ZN_1 | 57095706.48 | 0.00 | 57095706.48 | 1273269.14 | 58368975.63 | 42679126.28 | 4297.52 | 716.65 | 3745.83 | 209.05 |
PERIMETER_MID_ZN_4 | 34455094.50 | 0.00 | 34455094.50 | 848845.52 | 35303940.02 | 27503450.52 | 4562.14 | 782.15 | 3415.70 | 209.05 |
PERIMETER_TOP_ZN_3 | 3461335.94 | 0.00 | 3461335.94 | 1580892.99 | 5042228.93 | 4267819.30 | 4568.80 | 745.22 | 3445.99 | 309.95 |
PERIMETER_TOP_ZN_2 | 3281835.12 | 0.00 | 3281835.12 | 1053927.94 | 4335763.06 | 2750345.05 | 4482.78 | 715.06 | 3562.17 | 309.95 |
PERIMETER_TOP_ZN_1 | 5686725.72 | 0.00 | 5686725.72 | 1580892.99 | 7267618.71 | 4267912.63 | 4343.73 | 1036.42 | 3379.85 | 309.95 |
PERIMETER_TOP_ZN_4 | 3479491.91 | 0.00 | 3479491.91 | 1053927.94 | 4533419.85 | 2750345.05 | 4467.50 | 868.41 | 3424.10 | 309.95 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 10671554.30 | 890.06 | 974.29 | 6895.65 | 2249.83 |
Total Facility | 0.44E+10 | 0.00 | 0.44E+10 | 49521632.03 | 0.45E+10 | 0.50E+10 | 7152.47 | 4364.39 | 7975.52 | 2878.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.8810 | 0.0000 | 1.8810 | 0.0000 | 1.8810 | 1.2002 | 1391.78 | 1497.68 | 3053.54 |
CORE_BOTTOM | 1.3945 | 0.0000 | 1.3945 | 0.0000 | 1.3945 | 1.0778 | 2382.67 | 176.48 | 3383.85 |
CORE_MID | 10.9336 | 0.0000 | 10.9336 | 0.0000 | 10.9336 | 10.7782 | 2783.95 | 757.31 | 2401.74 |
CORE_TOP | 1.0799 | 0.0000 | 1.0799 | 0.0000 | 1.0799 | 1.0778 | 2861.48 | 884.00 | 2197.52 |
PERIMETER_BOT_ZN_3 | 0.1748 | 0.0000 | 0.1748 | 0.0129 | 0.1877 | 0.1353 | 2583.14 | 236.00 | 3123.86 |
PERIMETER_BOT_ZN_2 | 0.1533 | 0.0000 | 0.1533 | 0.0086 | 0.1620 | 0.0872 | 2493.86 | 334.44 | 3114.70 |
PERIMETER_BOT_ZN_1 | 0.2751 | 0.0000 | 0.2751 | 0.0129 | 0.2881 | 0.1353 | 2083.60 | 226.66 | 3632.74 |
PERIMETER_BOT_ZN_4 | 0.2316 | 0.0000 | 0.2316 | 0.0086 | 0.2402 | 0.0872 | 1642.14 | 283.89 | 4016.96 |
PERIMETER_MID_ZN_3 | 1.5507 | 0.0000 | 1.5507 | 0.0303 | 1.5810 | 1.3533 | 2048.56 | 830.14 | 3064.30 |
PERIMETER_MID_ZN_2 | 1.3942 | 0.0000 | 1.3942 | 0.0215 | 1.4157 | 0.8721 | 1685.30 | 549.13 | 2799.56 |
PERIMETER_MID_ZN_1 | 2.6344 | 0.0000 | 2.6344 | 0.0303 | 2.6647 | 1.3533 | 1541.59 | 716.56 | 3684.85 |
PERIMETER_MID_ZN_4 | 1.5835 | 0.0000 | 1.5835 | 0.0202 | 1.6037 | 0.8721 | 1806.53 | 781.90 | 3354.57 |
PERIMETER_TOP_ZN_3 | 0.1587 | 0.0000 | 0.1587 | 0.0377 | 0.1964 | 0.1353 | 1801.09 | 745.07 | 3396.84 |
PERIMETER_TOP_ZN_2 | 0.1513 | 0.0000 | 0.1513 | 0.0251 | 0.1764 | 0.0872 | 1718.74 | 714.95 | 3509.31 |
PERIMETER_TOP_ZN_1 | 0.2627 | 0.0000 | 0.2627 | 0.0377 | 0.3004 | 0.1353 | 1576.82 | 1036.31 | 3329.88 |
PERIMETER_TOP_ZN_4 | 0.1600 | 0.0000 | 0.1600 | 0.0251 | 0.1851 | 0.0872 | 1700.75 | 868.08 | 3374.18 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.2914 | 0.0000 | 10.2914 | 0.0000 | 10.2914 | 0.3384 | 322.89 | 974.29 | 4645.82 |
Total Facility | 198.3430 | 0.0000 | 198.3430 | 1.1927 | 199.5356 | 158.4706 | 4335.47 | 4357.82 | 5652.16 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 71884656.64 | 0.00 | 71884656.64 | 48026705.38 | 3825.92 | 5.18 | 4928.91 | 256.14 |
VAV_MID WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.48E+09 | 4086.24 | 1.96 | 4671.81 | 209.05 |
VAV_TOP WITH REHEAT | 57168227.37 | 0.00 | 57168227.37 | 48026705.38 | 4133.84 | 1.56 | 4624.60 | 309.83 |
CAV_BAS | 60334681.14 | 0.00 | 60334681.14 | 37848132.68 | 4048.16 | 2.15 | 4709.69 | 202.50 |
AIRLOOP DATACENTER BASEMENT | 0.45E+09 | 0.00 | 0.45E+09 | 10671554.30 | 890.06 | 0.00 | 7869.94 | 2249.83 |
AIRLOOP DATACENTER BOT | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3538971.99 | 0.00 | 3538971.99 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.2296 | 0.0000 | 3.2296 | 1.5229 | 1233.78 | 4.28 | 4704.95 |
VAV_MID WITH REHEAT | 26.2298 | 0.0000 | 26.2298 | 15.2292 | 1330.43 | 1.69 | 4610.87 |
VAV_TOP WITH REHEAT | 2.6256 | 0.0000 | 2.6256 | 1.5229 | 1367.17 | 1.33 | 4574.50 |
CAV_BAS | 2.7250 | 0.0000 | 2.7250 | 1.2002 | 1364.29 | 0.95 | 4577.76 |
AIRLOOP DATACENTER BASEMENT | 14.9086 | 0.0000 | 14.9086 | 0.3384 | 322.89 | 0.00 | 5620.11 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1654 | 0.0000 | 0.1654 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 605.96 | 2440.86 | 0.00 | 0.00 | 0.00 | 1997.66 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 287.60 | 2097.70 | 0.00 | 0.00 | 0.00 | 2573.33 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 54.78 | 2243.04 | 0.00 | 0.00 | 0.00 | 2785.18 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1485.47 | 3320.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 974.29 | 6895.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.9287 | 5.7602 | 0.0000 | 0.0000 | 0.0000 | 2.4188 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 29.2111 | 45.8437 | 0.0000 | 0.0000 | 0.0000 | 23.6807 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8353 | 4.6157 | 0.0000 | 0.0000 | 0.0000 | 2.3442 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7391 | 4.3655 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4904 | 18.9718 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1525 |
Defaulted Fields | 1187 |
Fields with Defaults | 3945 |
Autosized Fields | 336 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 24440.13 | 294113.36 | 07-MAY-03:00 | 1809875.36 | 22-AUG-14:50 |
Electricity:Building | 16393.59 | 215366.33 | 14-MAY-17:10 | 948093.84 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 540.44 | 14022.76 | 01-JAN-00:10 | 23631.68 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16393.59 | 215366.33 | 14-MAY-17:10 | 948093.84 | 01-DEC-16:30 |
InteriorLights:Electricity | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 116.04 | 565.21 | 01-JAN-00:10 | 10174.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1717.19 | 8110.17 | 01-JAN-08:40 | 169722.15 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 393.83 | 4960.84 | 01-JAN-00:10 | 26343.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 3938.24 | 49608.19 | 01-JAN-00:10 | 263436.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1042.12 | 5076.02 | 01-JAN-00:10 | 91370.93 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 393.82 | 4960.82 | 01-JAN-00:10 | 26343.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 104.21 | 507.60 | 01-JAN-00:10 | 9137.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 43.96 | 589.50 | 02-APR-17:10 | 3307.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.60 | 30.32 | 01-JAN-08:40 | 1147.25 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.60 | 30.32 | 01-JAN-08:40 | 1147.25 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.32 | 379.89 | 09-APR-17:10 | 2131.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 43.88 | 589.50 | 19-MAR-17:10 | 3307.86 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.51 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.51 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.28 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.84 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.84 | 19.54 | 01-JAN-08:40 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 439.49 | 5894.96 | 26-MAR-17:10 | 33078.05 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.84 | 303.25 | 01-JAN-08:30 | 11472.53 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 75.84 | 303.25 | 01-JAN-08:30 | 11472.53 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 283.12 | 3798.93 | 02-APR-17:10 | 21316.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.76 | 195.42 | 01-JAN-07:50 | 7393.34 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 48.76 | 195.42 | 01-JAN-07:50 | 7393.34 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 438.69 | 5895.05 | 19-MAR-17:10 | 33078.63 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.03 | 303.26 | 01-JAN-07:50 | 11472.78 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 75.03 | 303.26 | 01-JAN-07:50 | 11472.78 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 282.74 | 3798.91 | 12-MAR-17:10 | 21316.66 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.39 | 195.42 | 01-JAN-08:30 | 7393.34 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 48.39 | 195.42 | 01-JAN-08:30 | 7393.34 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 43.95 | 589.50 | 26-MAR-17:10 | 3307.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.58 | 30.32 | 01-JAN-08:30 | 1147.25 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.58 | 30.32 | 01-JAN-08:30 | 1147.25 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.31 | 379.89 | 02-APR-17:10 | 2131.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.88 | 19.54 | 01-JAN-07:50 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 43.87 | 589.50 | 19-MAR-17:10 | 3307.86 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.50 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.50 | 30.33 | 01-JAN-07:50 | 1147.28 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.27 | 379.89 | 12-MAR-17:10 | 2131.67 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.84 | 19.54 | 01-JAN-08:30 | 739.33 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.84 | 19.54 | 01-JAN-08:30 | 739.33 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7527.71 | 95067.50 | 01-JAN-00:10 | 382501.19 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 32.85 | 159.37 | 01-JAN-00:10 | 2868.67 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1555.56 | 19567.35 | 01-JAN-00:10 | 79407.42 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 16.76 | 81.29 | 01-JAN-00:10 | 1463.20 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 155.56 | 1956.73 | 01-JAN-00:10 | 7940.74 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 1.68 | 8.13 | 01-JAN-00:10 | 146.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2046.39 | 3428.59 | 02-JAN-05:20 | 394883.77 | 22-AUG-14:50 |
HeatRejection:Electricity | 716.05 | 90.58 | 02-JAN-07:20 | 79575.29 | 30-MAY-14:10 |
General:HeatRejection:Electricity | 716.05 | 90.58 | 02-JAN-07:20 | 79575.29 | 30-MAY-14:10 |
ElectricityProduced:Facility | 454.18 | -0.00 | 01-JAN-16:30 | 87214.16 | 02-JUN-11:50 |
ElectricityProduced:Plant | 454.18 | -0.00 | 01-JAN-16:30 | 87214.16 | 02-JUN-11:50 |
Photovoltaic:ElectricityProduced | 475.33 | 0.00 | 01-JAN-00:10 | 90823.46 | 02-JUN-11:50 |
PowerConversion:ElectricityProduced | -21.15 | -3609.30 | 02-JUN-11:50 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 4585.18 | 43433.03 | 15-JAN-10:30 | 469534.10 | 22-AUG-14:50 |
ExteriorEquipment:Electricity | 1203.69 | 17814.45 | 01-JAN-00:10 | 73697.12 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.35 | 979.82 | 01-JAN-00:10 | 3372.05 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
ElectricityPurchased:Plant | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
Cogeneration:ElectricityPurchased | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
General:Cogeneration:ElectricityPurchased | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
ElectricityNet:Plant | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
Cogeneration:ElectricityNet | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
General:Cogeneration:ElectricityNet | 23985.95 | 281484.12 | 14-MAY-14:00 | 1757159.65 | 22-AUG-14:50 |
Fans:Electricity | 2157.60 | 41266.92 | 02-JAN-23:50 | 266963.99 | 22-AUG-14:50 |
General:Fans:Electricity | 2157.60 | 41266.92 | 02-JAN-23:50 | 266963.99 | 22-AUG-14:50 |
ExteriorLights:Electricity | 265.63 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 265.63 | 0.00 | 01-JAN-07:30 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
HeatRecovery:Electricity | 43.67 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 43.67 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
Cooling:Electricity | 2006.67 | 1034.28 | 03-JAN-08:30 | 423492.26 | 24-AUG-17:00 |
General:Cooling:Electricity | 2006.67 | 1034.28 | 03-JAN-08:30 | 423492.26 | 24-AUG-17:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1261.37 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-FEB-06:10 |
General:Humidifier:Electricity | 1261.37 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-FEB-06:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 391.85 | 3332.09 | 02-JAN-04:40 | 53728.82 | 30-AUG-13:00 |
General:Pumps:Electricity | 391.85 | 3332.09 | 02-JAN-04:40 | 53728.82 | 30-AUG-13:00 |
WIRED_LTG_ELECTRICITY | 48.25 | 0.00 | 01-JAN-00:10 | 4769.19 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1485.22 | 7280.88 | 02-JAN-06:00 | 1631163.45 | 02-JAN-05:10 |
NaturalGas:Plant | 1485.22 | 7280.88 | 02-JAN-06:00 | 1631163.45 | 02-JAN-05:10 |
Heating:NaturalGas | 728.76 | 0.00 | 01-JAN-00:40 | 1623882.57 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 728.76 | 0.00 | 01-JAN-00:40 | 1623882.57 | 02-JAN-05:10 |
WaterSystems:NaturalGas | 756.46 | 7280.88 | 02-JAN-04:10 | 84093.47 | 13-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 756.46 | 7280.88 | 02-JAN-04:10 | 84093.47 | 13-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 11537.91 | 1854.79 | 03-JAN-09:10 | 2701231.79 | 22-AUG-14:50 |
PlantLoopCoolingDemand:HVAC | 11537.91 | 1854.79 | 03-JAN-09:10 | 2701231.79 | 22-AUG-14:50 |
CoolingCoils:PlantLoopCoolingDemand | 11537.91 | 1854.79 | 03-JAN-09:10 | 2701231.79 | 22-AUG-14:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7505.95 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Water:HVAC | 469.23 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Humidifier:Water | 469.23 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
General:Humidifier:Water | 469.23 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
MainsWater:Facility | 7505.95 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-16:00 |
MainsWater:HVAC | 469.23 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Humidifier:MainsWater | 469.23 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
General:Humidifier:MainsWater | 469.23 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Water:Plant | 7036.72 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 7036.72 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4756.55 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
General:HeatRejection:Water | 4756.55 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
HeatRejection:MainsWater | 4756.55 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
General:HeatRejection:MainsWater | 4756.55 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 52250.30 | 92857.59 | 02-JAN-06:00 | 10748836.23 | 22-AUG-14:50 |
EnergyTransfer:Building | 17792.16 | 88530.18 | 28-JAN-19:10 | 1597525.22 | 14-AUG-14:10 |
EnergyTransfer:Zone:BASEMENT | 592.64 | 0.00 | 01-JAN-00:10 | 71807.97 | 10-OCT-05:10 |
Heating:EnergyTransfer | 598.00 | 0.00 | 19-JAN-22:10 | 1365193.75 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.33 | 0.00 | 01-JAN-00:10 | 11513.77 | 12-AUG-16:10 |
General:Heating:EnergyTransfer | 598.00 | 0.00 | 19-JAN-22:10 | 1365193.75 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.33 | 0.00 | 01-JAN-00:10 | 11513.77 | 12-AUG-16:10 |
Cooling:EnergyTransfer | 17194.16 | 84559.65 | 02-JAN-06:00 | 1597525.22 | 14-AUG-14:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 590.31 | 0.00 | 01-JAN-00:10 | 71807.97 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 17194.16 | 84559.65 | 02-JAN-06:00 | 1597525.22 | 14-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 590.31 | 0.00 | 01-JAN-00:10 | 71807.97 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 547.58 | 0.00 | 01-JAN-00:10 | 50237.21 | 14-AUG-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 547.58 | 0.00 | 01-JAN-00:10 | 50237.21 | 14-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 547.58 | 0.00 | 01-JAN-00:10 | 50237.21 | 14-AUG-09:20 |
EnergyTransfer:Zone:CORE_MID | 3775.12 | 0.00 | 01-JAN-00:40 | 456153.65 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 13.44 | 0.00 | 01-JAN-00:20 | 456153.65 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 13.44 | 0.00 | 01-JAN-00:20 | 456153.65 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3761.68 | 0.00 | 01-JAN-00:40 | 428776.40 | 07-AUG-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3761.68 | 0.00 | 01-JAN-00:40 | 428776.40 | 07-AUG-05:10 |
EnergyTransfer:Zone:CORE_TOP | 358.13 | 0.00 | 01-JAN-00:40 | 66001.38 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 12.83 | 0.00 | 01-JAN-00:40 | 66001.38 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 12.83 | 0.00 | 01-JAN-00:40 | 66001.38 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 345.30 | 0.00 | 01-JAN-00:10 | 46086.14 | 30-MAY-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 345.30 | 0.00 | 01-JAN-00:10 | 46086.14 | 30-MAY-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 68.75 | 0.00 | 01-JAN-00:10 | 10906.73 | 19-JUN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.58 | 0.00 | 01-JAN-00:10 | 8481.42 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.58 | 0.00 | 01-JAN-00:10 | 8481.42 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 68.16 | 0.00 | 01-JAN-00:10 | 10906.73 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 68.16 | 0.00 | 01-JAN-00:10 | 10906.73 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.91 | 0.00 | 01-JAN-00:10 | 14611.26 | 26-JUN-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.40 | 0.00 | 01-JAN-00:10 | 6051.51 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.40 | 0.00 | 01-JAN-00:10 | 6051.51 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.52 | 0.00 | 01-JAN-00:10 | 14611.26 | 26-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.52 | 0.00 | 01-JAN-00:10 | 14611.26 | 26-JUN-08:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 106.83 | 0.00 | 01-JAN-00:10 | 20419.49 | 04-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.80 | 0.00 | 01-JAN-00:10 | 10589.96 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.80 | 0.00 | 01-JAN-00:10 | 10589.96 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 106.04 | 0.00 | 01-JAN-00:10 | 20419.49 | 04-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 106.04 | 0.00 | 01-JAN-00:10 | 20419.49 | 04-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 93.48 | 0.00 | 01-JAN-00:10 | 18881.39 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 4259.06 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 4259.06 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 93.43 | 0.00 | 01-JAN-00:10 | 18881.39 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 93.43 | 0.00 | 01-JAN-00:10 | 18881.39 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 596.66 | 0.00 | 01-JAN-00:40 | 129760.23 | 02-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 128.62 | 0.00 | 01-JAN-00:40 | 129760.23 | 02-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 128.62 | 0.00 | 01-JAN-00:40 | 129760.23 | 02-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 468.03 | 0.00 | 01-JAN-00:10 | 103768.62 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 468.03 | 0.00 | 01-JAN-00:10 | 103768.62 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 543.91 | 0.00 | 01-JAN-00:40 | 156877.33 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 64.79 | 0.00 | 01-JAN-00:40 | 145754.17 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 64.79 | 0.00 | 01-JAN-00:40 | 145754.17 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 479.12 | 0.00 | 01-JAN-00:10 | 156877.33 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 479.12 | 0.00 | 01-JAN-00:10 | 156877.33 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 981.27 | 0.00 | 01-JAN-00:40 | 208803.77 | 04-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 68.43 | 0.00 | 01-JAN-00:40 | 178883.84 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 68.43 | 0.00 | 01-JAN-00:40 | 178883.84 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 912.84 | 0.00 | 01-JAN-00:10 | 208803.77 | 04-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 912.84 | 0.00 | 01-JAN-00:10 | 208803.77 | 04-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 602.28 | 0.00 | 01-JAN-00:40 | 166562.02 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.78 | 0.00 | 01-JAN-00:40 | 140562.07 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.78 | 0.00 | 01-JAN-00:40 | 140562.07 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 550.50 | 0.00 | 01-JAN-00:20 | 166562.02 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 550.50 | 0.00 | 01-JAN-00:20 | 166562.02 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.59 | 0.00 | 01-JAN-00:40 | 15821.78 | 06-FEB-01:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.35 | 0.00 | 01-JAN-00:40 | 15821.78 | 06-FEB-01:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.35 | 0.00 | 01-JAN-00:40 | 15821.78 | 06-FEB-01:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.23 | 0.00 | 01-JAN-00:10 | 11692.14 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.23 | 0.00 | 01-JAN-00:10 | 11692.14 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.47 | 0.00 | 01-JAN-00:40 | 16700.53 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.02 | 0.00 | 01-JAN-00:40 | 16700.53 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.02 | 0.00 | 01-JAN-00:40 | 16700.53 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 48.45 | 0.00 | 01-JAN-00:10 | 15925.32 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 48.45 | 0.00 | 01-JAN-00:10 | 15925.32 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 103.19 | 0.00 | 01-JAN-00:40 | 22217.76 | 04-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.32 | 0.00 | 01-JAN-00:40 | 21140.03 | 06-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.32 | 0.00 | 01-JAN-00:40 | 21140.03 | 06-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.87 | 0.00 | 01-JAN-00:10 | 22217.76 | 04-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.87 | 0.00 | 01-JAN-00:10 | 22217.76 | 04-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 65.62 | 0.00 | 01-JAN-00:40 | 17268.15 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 11.99 | 0.00 | 01-JAN-00:40 | 16919.66 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 11.99 | 0.00 | 01-JAN-00:40 | 16919.66 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.63 | 0.00 | 01-JAN-00:10 | 17268.15 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.63 | 0.00 | 01-JAN-00:10 | 17268.15 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.94 | 0.00 | 01-JAN-00:10 | 10024.34 | 14-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.49 | 0.00 | 01-JAN-00:10 | 4480.46 | 02-JAN-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.49 | 0.00 | 01-JAN-00:10 | 4480.46 | 02-JAN-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 50.45 | 0.00 | 01-JAN-00:10 | 10024.34 | 14-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 50.45 | 0.00 | 01-JAN-00:10 | 10024.34 | 14-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 448.43 | 0.00 | 01-JAN-00:40 | 176555.98 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 135.37 | 0.00 | 01-JAN-00:40 | 176555.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 135.37 | 0.00 | 01-JAN-00:40 | 176555.98 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 313.06 | 0.00 | 01-JAN-00:10 | 75484.46 | 10-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 313.06 | 0.00 | 01-JAN-00:10 | 75484.46 | 10-JUL-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 93.03 | 0.00 | 01-JAN-00:40 | 28152.31 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.68 | 0.00 | 01-JAN-00:40 | 28152.31 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.68 | 0.00 | 01-JAN-00:40 | 28152.31 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 56.35 | 0.00 | 01-JAN-00:10 | 20805.30 | 19-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 56.35 | 0.00 | 01-JAN-00:10 | 20805.30 | 19-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.43 | 8.43 | 01-JAN-01:40 | 8314.04 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-02:20 | 181.52 | 01-JAN-01:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-02:20 | 181.52 | 01-JAN-01:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.43 | 0.00 | 01-JAN-00:20 | 8314.04 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.43 | 0.00 | 01-JAN-00:20 | 8314.04 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1170.35 | 5.08 | 27-JAN-07:50 | 76877.29 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.92 | 0.00 | 02-JAN-07:10 | 5448.97 | 16-JAN-18:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.92 | 0.00 | 02-JAN-07:10 | 5448.97 | 16-JAN-18:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1165.43 | 0.00 | 01-JAN-00:10 | 76877.29 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1165.43 | 0.00 | 01-JAN-00:10 | 76877.29 | 10-AUG-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.70 | 0.21 | 30-JAN-20:00 | 7802.36 | 13-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.81 | 0.00 | 02-JAN-07:20 | 579.79 | 16-JAN-17:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.81 | 0.00 | 02-JAN-07:20 | 579.79 | 16-JAN-17:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.89 | 0.00 | 01-JAN-00:10 | 7802.36 | 13-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.89 | 0.00 | 01-JAN-00:10 | 7802.36 | 13-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7149.85 | 84559.65 | 02-JAN-06:00 | 370090.20 | 24-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7149.85 | 84559.65 | 02-JAN-06:00 | 370090.20 | 24-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7149.85 | 84559.65 | 02-JAN-06:00 | 370090.20 | 24-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 1088.63 | 0.00 | 01-JAN-00:40 | 1407098.41 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 411.41 | 0.00 | 01-JAN-00:10 | 52084.56 | 13-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 411.41 | 0.00 | 01-JAN-00:10 | 52084.56 | 13-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 411.41 | 0.00 | 01-JAN-00:10 | 52084.56 | 13-FEB-12:40 |
EnergyTransfer:HVAC | 12874.23 | 951.67 | 15-JAN-10:30 | 2690827.12 | 16-AUG-12:30 |
HeatingCoils:EnergyTransfer | 677.22 | 0.00 | 01-JAN-00:40 | 1400900.49 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 677.22 | 0.00 | 01-JAN-00:40 | 1400900.49 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 677.22 | 0.00 | 01-JAN-00:40 | 1400900.49 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 10469.73 | 815.38 | 03-JAN-09:10 | 2553095.92 | 22-AUG-14:50 |
HeatRecoveryForHeating:EnergyTransfer | 1255.30 | 0.00 | 01-JAN-00:10 | 626180.10 | 06-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 471.98 | 0.00 | 01-JAN-00:10 | 515517.85 | 08-JUL-12:20 |
EnergyTransfer:Plant | 21583.90 | 0.00 | 01-JAN-00:40 | 6567313.42 | 22-AUG-14:50 |
LoopToLoop:EnergyTransfer | 6541.91 | 0.00 | 01-JAN-00:10 | 2081624.53 | 22-AUG-14:50 |
WaterSystems:EnergyTransfer | 411.41 | 0.00 | 01-JAN-00:10 | 52084.56 | 13-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 411.41 | 0.00 | 01-JAN-00:10 | 52084.56 | 13-FEB-12:40 |
Boilers:EnergyTransfer | 676.22 | 0.00 | 01-JAN-00:40 | 1450579.42 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 6507.94 | 0.00 | 01-JAN-00:10 | 2064839.76 | 22-AUG-14:50 |
HeatRejection:EnergyTransfer | 7446.43 | 0.00 | 01-JAN-00:10 | 2331785.20 | 22-AUG-14:50 |
General:HeatRejection:EnergyTransfer | 7446.43 | 0.00 | 01-JAN-00:10 | 2331785.20 | 22-AUG-14:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.331 | -590.308 | 0.000 | 0.000 | 92.964 | 116.039 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -45.424 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -547.579 | 0.000 | 0.000 | 83.519 | 104.212 | 289.614 | 0.000 | 0.000 | 0.000 | 70.234 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 13.444 | -3761.666 | 0.000 | 0.000 | 856.273 | 1042.115 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1046.294 |
CORE_TOP | 0.000 | 0.000 | 12.835 | -345.295 | 0.000 | 0.000 | 88.266 | 104.212 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -149.630 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.583 | -68.164 | 0.000 | 0.000 | 10.835 | 7.595 | 36.365 | 31.811 | 0.000 | 0.115 | 47.928 | 0.000 | -58.550 | 0.000 | -8.517 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.397 | -58.517 | 0.000 | 0.000 | 6.929 | 4.882 | 23.435 | 58.122 | 0.000 | 0.077 | 6.556 | 0.000 | -36.225 | 0.000 | -5.656 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.797 | -106.036 | 0.000 | 0.000 | 10.704 | 7.509 | 36.366 | 119.019 | 0.000 | 0.111 | 0.007 | 0.000 | -53.315 | 0.000 | -8.575 | -6.581 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.050 | -93.427 | 0.000 | 0.000 | 6.802 | 4.844 | 23.435 | 57.961 | 0.000 | 0.068 | 48.549 | 0.000 | -41.979 | 0.000 | -6.304 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 128.624 | -468.027 | 0.000 | 0.000 | 113.405 | 75.840 | 363.654 | 329.011 | 0.000 | 2.515 | 143.601 | 0.000 | -515.295 | 0.000 | -173.327 | -0.008 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 64.787 | -479.113 | 0.000 | 0.000 | 52.549 | 48.764 | 234.352 | 581.569 | 0.000 | 1.547 | 0.041 | 0.000 | -330.650 | 0.000 | -119.356 | -54.449 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 68.431 | -912.829 | 0.000 | 0.000 | 109.001 | 75.031 | 363.660 | 1188.070 | 0.000 | 2.394 | 0.006 | 0.000 | -502.554 | 0.000 | -186.267 | -204.936 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 51.783 | -550.496 | 0.000 | 0.000 | 71.704 | 48.387 | 234.351 | 591.722 | 0.000 | 1.551 | 26.753 | 0.000 | -352.470 | 0.000 | -123.285 | -0.009 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 28.355 | -45.230 | 0.000 | 0.000 | 11.462 | 7.583 | 36.365 | 33.217 | 0.000 | 0.293 | 0.000 | 0.000 | -48.633 | 0.000 | -20.376 | -3.035 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 15.020 | -48.453 | 0.000 | 0.000 | 7.240 | 4.876 | 23.435 | 58.583 | 0.000 | 0.189 | 0.000 | 0.000 | -31.207 | 0.000 | -14.005 | -15.678 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 17.317 | -85.873 | 0.000 | 0.000 | 11.039 | 7.503 | 36.366 | 119.190 | 0.000 | 0.283 | 0.000 | 0.000 | -47.417 | 0.000 | -21.822 | -36.586 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 11.988 | -53.630 | 0.000 | 0.000 | 7.254 | 4.839 | 23.435 | 59.282 | 0.000 | 0.185 | 0.000 | 0.000 | -33.494 | 0.000 | -14.557 | -5.301 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.002 | -136.432 | 0.000 | 0.000 | 0.950 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.076 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 4.919 | -1165.429 | 0.000 | 0.000 | 9.520 | 16.758 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -404.574 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.806 | -107.894 | 0.000 | 0.000 | 0.955 | 1.676 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.424 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7149.855 | 0.000 | 0.000 | 20.336 | 32.854 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -398.192 |
GROUNDFLOOR_PLENUM | 3.489 | -50.448 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.194 | 65.142 | 0.000 | 0.000 | 0.000 | -18.377 | 0.000 |
MIDFLOOR_PLENUM | 135.372 | -313.061 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.500 | 476.811 | 0.000 | 0.000 | 0.000 | -302.622 | -0.004 |
TOPFLOOR_PLENUM | 36.677 | -56.353 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.284 | 51.199 | 0.000 | 0.000 | 0.000 | -31.807 | -0.001 |
Total Facility | 175.538 | -419.862 | 422.469 | -16774.252 | 0.000 | 0.000 | 1571.704 | 1717.194 | 14676.396 | 3227.557 | 0.000 | 13.305 | 936.828 | 0.000 | -2051.789 | 0.000 | -1054.854 | -2440.202 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-NOV-05:11 | 0.00 | 0.00 | 0.00 | -100997.85 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 86941.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-MAY-04:13 | 0.00 | 0.00 | 0.00 | -88053.68 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 81578.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-04:13 | 0.00 | 0.00 | 0.00 | -807452.36 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 742702.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 26-JUN-04:13 | 0.00 | 0.00 | 0.00 | -80647.95 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 74172.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-AUG-15:01 | 0.00 | 0.00 | 0.00 | -16516.18 | 0.00 | 0.00 | 41.59 | 30.32 | 720.18 | 5457.14 | 0.00 | 76.74 | 10190.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-08:41 | 0.00 | 0.00 | 0.00 | -23367.42 | 0.00 | 0.00 | 19.56 | 19.54 | 464.11 | 17650.23 | 0.00 | 0.00 | 5270.29 | 0.00 | -0.00 | 0.00 | -56.33 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-12:41 | 0.00 | 0.00 | 0.00 | -26852.99 | 0.00 | 0.00 | 30.99 | 30.33 | 720.19 | 22538.45 | 0.00 | 0.00 | 3625.39 | 0.00 | -0.00 | 0.00 | -92.37 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-15:41 | 0.00 | 0.00 | 0.00 | -30377.48 | 0.00 | 0.00 | 15.46 | 19.54 | 464.11 | 15478.65 | 0.00 | 0.00 | 14402.73 | 0.00 | -0.00 | 0.00 | -3.01 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-14:31 | 0.00 | 0.00 | 0.00 | -157202.45 | 0.00 | 0.00 | 417.81 | 303.25 | 7201.84 | 65122.40 | 0.00 | 1195.96 | 82961.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-08:31 | 0.00 | 0.00 | 0.00 | -258869.11 | 0.00 | 0.00 | 183.32 | 195.42 | 4641.14 | 182918.41 | 0.00 | 0.00 | 72639.73 | 0.00 | -0.00 | 0.00 | -1708.91 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:31 | 0.00 | 0.00 | 0.00 | -274900.01 | 0.00 | 0.00 | 303.23 | 303.26 | 7201.95 | 239449.21 | 0.00 | 0.00 | 29838.61 | 0.00 | -0.00 | 0.00 | -2196.25 | 0.00 |
PERIMETER_MID_ZN_4 | 18-JUN-15:51 | 0.00 | 0.00 | 0.00 | -273648.85 | 0.00 | 0.00 | 174.29 | 195.42 | 4641.11 | 185240.76 | 0.00 | 0.00 | 86621.90 | 0.00 | -0.00 | 0.00 | -3224.62 | 0.00 |
PERIMETER_TOP_ZN_3 | 09-JUL-14:31 | 0.00 | 0.00 | 0.00 | -18630.89 | 0.00 | 0.00 | 39.37 | 30.32 | 720.18 | 6362.16 | 0.00 | 82.93 | 11395.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -25862.70 | 0.00 | 0.00 | 19.05 | 19.54 | 464.11 | 19165.12 | 0.00 | 0.00 | 6397.85 | 0.00 | -0.00 | 0.00 | -202.97 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-11:41 | 0.00 | 0.00 | 0.00 | -29168.44 | 0.00 | 0.00 | 31.52 | 30.33 | 720.19 | 23123.61 | 0.00 | 0.00 | 5595.27 | 0.00 | -0.00 | 0.00 | -332.47 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -29343.48 | 0.00 | 0.00 | 15.84 | 19.54 | 464.11 | 17729.11 | 0.00 | 0.00 | 11703.56 | 0.00 | -0.00 | 0.00 | -588.68 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:47 | 0.00 | 0.00 | 0.00 | -8314.04 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 511.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -76875.55 | 0.00 | 0.00 | 106.16 | 487.73 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1662.56 |
DATACENTER_TOP_ZN_6 | 13-AUG-18:33 | 0.00 | 0.00 | 0.00 | -7808.22 | 0.00 | 0.00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 20-AUG-15:31 | 0.00 | 0.00 | 0.00 | -374727.67 | 0.00 | 0.00 | 110.53 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5174.75 |
GROUNDFLOOR_PLENUM | 05-SEP-05:15 | 0.00 | -12557.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12603.37 | 0.00 | -0.00 | 0.00 | -45.46 | 0.00 |
MIDFLOOR_PLENUM | 14-JAN-04:01 | 0.00 | -89373.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164095.29 | 0.00 | -0.00 | 0.00 | -74721.58 | 0.00 |
TOPFLOOR_PLENUM | 30-MAY-13:40 | 0.00 | -20880.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.71 | 20750.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | -86365.04 | 0.00 | -1807751.02 | 0.00 | 0.00 | 16555.06 | 10223.35 | 616289.16 | 0.00 | 0.00 | 0.00 | 1293940.21 | 0.00 | -38753.32 | 0.00 | -4138.39 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-AUG-16:01 | 0.00 | 0.00 | 12747.05 | 0.00 | 0.00 | 0.00 | 520.12 | 565.21 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27289.93 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 524400.56 | 0.00 | 0.00 | 0.00 | 0.00 | 5076.02 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -588852.80 |
CORE_TOP | 01-JAN-00:42 | 0.00 | 0.00 | 73887.61 | 0.00 | 0.00 | 0.00 | 0.00 | 507.60 | 4453.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78848.43 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 12347.52 | 0.00 | 0.00 | 0.00 | 0.00 | 127.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6875.36 | 0.00 | -2037.43 | -4307.77 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 11762.11 | 0.00 | 0.00 | 0.00 | 0.00 | 82.15 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4462.31 | 0.00 | -1365.92 | -6496.50 |
PERIMETER_BOT_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 17480.12 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6040.83 | 0.00 | -623.85 | -11624.74 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 9972.27 | 0.00 | 0.00 | 0.00 | 0.00 | 82.15 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4413.27 | 0.00 | -477.78 | -5643.83 |
PERIMETER_MID_ZN_3 | 06-FEB-00:22 | 0.00 | 0.00 | 143409.56 | 0.00 | 0.00 | 0.00 | 0.00 | 637.34 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61817.21 | 0.00 | -49028.50 | -40656.81 |
PERIMETER_MID_ZN_2 | 01-JAN-00:42 | 0.00 | 0.00 | 193493.64 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27661.90 | 0.00 | -18631.57 | -151214.41 |
PERIMETER_MID_ZN_1 | 01-JAN-00:42 | 0.00 | 0.00 | 210241.61 | 0.00 | 0.00 | 0.00 | 0.00 | 637.36 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43346.96 | 0.00 | -27727.88 | -145395.93 |
PERIMETER_MID_ZN_4 | 01-JAN-00:42 | 0.00 | 0.00 | 194832.85 | 0.00 | 0.00 | 0.00 | 0.00 | 410.73 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28822.28 | 0.00 | -18823.32 | -151201.46 |
PERIMETER_TOP_ZN_3 | 31-DEC-22:42 | 0.00 | 0.00 | 16800.89 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4814.62 | 0.00 | -4639.30 | -7969.88 |
PERIMETER_TOP_ZN_2 | 31-DEC-22:42 | 0.00 | 0.00 | 20405.38 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3134.33 | 0.00 | -3193.42 | -14479.05 |
PERIMETER_TOP_ZN_1 | 01-JAN-00:42 | 0.00 | 0.00 | 23452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4237.10 | 0.00 | -3361.83 | -16476.98 |
PERIMETER_TOP_ZN_4 | 01-JAN-00:42 | 0.00 | 0.00 | 22039.60 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2816.58 | 0.00 | -2285.35 | -17339.08 |
DATACENTER_BOT_ZN_6 | 01-JAN-23:16 | 0.00 | 0.00 | 444.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2401.28 |
DATACENTER_MID_ZN_6 | 16-JAN-18:20 | 0.00 | 0.00 | 5448.97 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25016.32 |
DATACENTER_TOP_ZN_6 | 16-JAN-17:40 | 0.00 | 0.00 | 579.79 | 0.00 | 0.00 | 0.00 | 6.35 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2542.87 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:11 | 11845.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1042.09 | -10803.23 |
MIDFLOOR_PLENUM | 02-JAN-06:23 | 182330.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5969.57 | -176360.97 |
TOPFLOOR_PLENUM | 06-FEB-05:07 | 29208.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7795.44 | -21413.51 |
Total Facility | 02-JAN-06:01 | -37806.31 | 186290.46 | 1365130.69 | -186290.46 | 0.00 | 0.00 | 23107.27 | 10223.35 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -233672.88 | 0.00 | -25564.56 | -1362832.51 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.1456 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.9018 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 97.4597 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 83.4650 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.2029 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2384 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.8182 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.8182 | 0.2491 | 1.0000 | Not calculated | 1.2002 | 0.2491 | ||
AIRLOOP DATACENTER BASEMENT | 21.2289 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2291 | 0.0159 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4692 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4692 | 0.0333 | 1.0000 | Not calculated | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4919 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4919 | 0.0348 | 1.0000 | Not calculated | 0.1563 | 0.0348 | ||
AIRLOOP DATACENTER TOP | 0.4577 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4577 | 0.0342 | 1.0000 | Not calculated | 0.0156 | 0.0342 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.0728 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2838 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.7299 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8694 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1015 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2873 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.8182 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.8182 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2491 | ||
AIRLOOP DATACENTER BASEMENT | 21.2289 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2289 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4692 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4692 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0333 | ||
AIRLOOP DATACENTER MID | 4.4919 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4919 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0348 | ||
AIRLOOP DATACENTER TOP | 0.4577 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4577 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0342 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8182 | 4.8182 | 4.8182 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2312 | 5.2312 | 1.6164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.0515 | 49.0515 | 16.1870 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9974 | 4.9974 | 1.6192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9372 | 0.9372 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1743 | 1.1743 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3557 | 1.3557 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4472 | 1.4472 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0152 | 9.0152 | 2.0284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.6225 | 12.6225 | 1.3127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.5485 | 13.5485 | 2.0323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2219 | 13.2219 | 1.3090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0327 | 1.0327 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2865 | 1.2865 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4778 | 1.4778 | 0.2025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4085 | 1.4085 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4692 | 0.4692 | 0.4692 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4919 | 4.4919 | 4.4919 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4577 | 0.4577 | 0.4577 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2289 | 21.2289 | 21.2289 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.1456 | 8.9018 | 10.1456 | 2.2838 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 97.4597 | 83.4650 | 97.4597 | 22.8694 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.2029 | 9.2384 | 10.2029 | 2.2873 | 0.0000 | 1.0000 |
CAV_BAS | 4.8182 | 4.8182 | 4.8182 | 4.8182 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2289 | 21.2291 | 21.2289 | 21.2289 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4692 | 0.4692 | 0.4692 | 0.4692 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4919 | 4.4919 | 4.4919 | 4.4919 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4577 | 0.4577 | 0.4577 | 0.4577 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8182 | 4.8182 | 4.8182 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6156 | 2.6156 | 1.6164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.5258 | 24.5258 | 16.1870 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4987 | 2.4987 | 1.6192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4686 | 0.4686 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5871 | 0.5871 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6779 | 0.6779 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7236 | 0.7236 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5076 | 4.5076 | 2.0284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3113 | 6.3113 | 1.3127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7743 | 6.7743 | 2.0323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6110 | 6.6110 | 1.3090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5164 | 0.5164 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6432 | 0.6432 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7389 | 0.7389 | 0.2025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7042 | 0.7042 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4692 | 0.4692 | 0.4692 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4919 | 4.4919 | 4.4919 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4577 | 0.4577 | 0.4577 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2289 | 21.2289 | 21.2289 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.0728 | 2.2838 | 2.2838 | 2.2838 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.7299 | 22.8694 | 22.8694 | 22.8694 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1015 | 2.2873 | 2.2873 | 2.2873 | 0.0000 | 1.0000 |
CAV_BAS | 4.8182 | 4.8182 | 4.8182 | 4.8182 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2289 | 21.2289 | 21.2289 | 21.2289 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4692 | 0.4692 | 0.4692 | 0.4692 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4919 | 4.4919 | 4.4919 | 4.4919 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4577 | 0.4577 | 0.4577 | 0.4577 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 48.67 |
Number of hours cooling loads not met | 455.83 |
Number of hours not met | 504.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 728.76 | 1623882.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2006.67 | 423492.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1717.19 | 169722.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 265.63 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.35 | 3372.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2157.60 | 266963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 391.85 | 53728.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 716.05 | 79575.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1261.37 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 43.67 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 756.46 | 84093.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 24440.13 |
Natural Gas | 0.00 | 1485.22 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 25925.34 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 475.33 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 37.07 |
Space Heating | 0.00 |
Space Cooling | 43.32 |
Fans (All) | 46.58 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 527.63 |
Subtotal | 527.63 |
Natural Gas [MJ/m2] | |
Space Heating | 15.73 |
Service Water Heating | 16.33 |
Miscellaneous (All) | 32.06 |
Subtotal | 32.06 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.62 |
Space Heating | 2.81 |
Space Cooling | 7.74 |
Fans (All) | 8.32 |
Service Water Heating | 2.92 |
Receptacle Equipment | 56.61 |
Miscellaneous | 14.97 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2069. | 8760. |
LTG_SCH_DATACENTER | 1840. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 814. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8298.50 | 461.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8735.83 | 24.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8668.17 | 91.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8669.33 | 90.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8099.17 | 660.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8724.33 | 35.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8600.83 | 159.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8615.50 | 144.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8362.33 | 397.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8682.67 | 77.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8572.33 | 187.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8584.67 | 175.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8371.67 | 388.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6272.67 | 2487.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6276.17 | 2483.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6251.17 | 2508.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5574.67 | 3184.83 | 0.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8634.83 | 125.17 | 0.00 | 0.00 | 0.00 |
Min | 5574.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3184.83 | 0.50 | 0.00 | 0.00 |
Average | 8163.91 | 596.07 | 0.02 | 0.00 | 0.00 |
Sum | 187770.00 | 13709.50 | 0.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367239.33 | 1376.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330801.00 | 12.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1319.83 | 948.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1313.00 | 955.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1309.17 | 958.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 63706.50 | 39682.50 | 6.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367239.33 | 39682.50 | 6.00 | 0.00 | 0.00 |
Average | 78424.04 | 1910.62 | 0.26 | 0.00 | 0.00 |
Sum | 1803752.83 | 43944.17 | 6.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6890.83 | 1869.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7966.67 | 793.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7877.83 | 882.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7893.67 | 866.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7851.67 | 908.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7921.50 | 838.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7777.33 | 982.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7491.67 | 1268.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7855.00 | 905.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7779.17 | 980.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7741.83 | 1018.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7703.67 | 1056.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7844.00 | 916.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7797.83 | 962.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7770.67 | 989.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7742.00 | 1018.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7374.83 | 1385.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7342.67 | 1417.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7327.00 | 1433.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6451.50 | 2308.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7554.83 | 1205.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7475.50 | 1284.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7082.17 | 1677.83 | 0.00 | 0.00 | 0.00 |
Min | 6451.50 | 793.33 | 0.00 | 0.00 | 0.00 |
Max | 7966.67 | 2308.50 | 0.00 | 0.00 | 0.00 |
Average | 7587.56 | 1172.44 | 0.00 | 0.00 | 0.00 |
Sum | 174513.83 | 26966.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 335963.00 | 32653.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329408.00 | 1405.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329585.00 | 1228.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 328527.50 | 2285.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38923.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24907.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38924.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38889.33 | 35.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18329.17 | 24.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38895.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24892.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38869.83 | 55.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24866.83 | 42.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38867.50 | 57.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24879.83 | 29.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1483.50 | 784.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1464.50 | 803.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1456.00 | 812.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 67172.00 | 36223.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 335963.00 | 36223.00 | 0.00 | 0.00 | 0.00 |
Average | 77009.30 | 3325.61 | 0.00 | 0.00 | 0.00 |
Sum | 1771214.00 | 76489.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:52
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384267E+11 | 92792.00 | 23-JAN-05:11 | 5.60 | 5.60 | 0.554103E+10 | 7499.40 | 03-JAN-10:39 | 5.60 | 5.60 |
February | 0.372759E+11 | 96498.27 | 21-FEB-05:11 | 2.20 | 1.34 | 0.503238E+10 | 7499.27 | 28-FEB-10:20 | 7.03 | 6.58 |
March | 0.473944E+11 | 95766.13 | 06-MAR-05:11 | 8.70 | 8.70 | 0.612447E+10 | 7499.17 | 02-MAR-10:20 | 8.70 | 8.70 |
April | 0.461943E+11 | 96216.76 | 17-APR-04:11 | 12.43 | 10.77 | 0.544505E+10 | 7499.24 | 07-APR-13:20 | 12.43 | 10.77 |
May | 0.483733E+11 | 95813.22 | 01-MAY-04:12 | 6.50 | 4.55 | 0.589833E+10 | 7503.93 | 30-MAY-09:20 | 26.67 | 17.22 |
June | 0.518780E+11 | 97820.07 | 05-JUN-04:12 | 14.40 | 11.39 | 0.587948E+10 | 7499.22 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.531018E+11 | 85363.44 | 11-JUL-04:12 | 19.80 | 15.19 | 0.547115E+10 | 7499.11 | 12-JUL-09:30 | 27.50 | 18.52 |
August | 0.602594E+11 | 91704.21 | 08-AUG-04:12 | 15.40 | 12.62 | 0.613635E+10 | 7499.28 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.535494E+11 | 97437.80 | 25-SEP-04:12 | 14.40 | 11.46 | 0.545071E+10 | 7499.40 | 19-SEP-09:20 | 14.40 | 11.46 |
October | 0.561208E+11 | 97647.03 | 02-OCT-04:12 | 9.80 | 9.58 | 0.566935E+10 | 7503.44 | 11-OCT-13:50 | 20.60 | 17.27 |
November | 0.505770E+11 | 101005.68 | 06-NOV-05:11 | 5.00 | 2.64 | 0.561086E+10 | 7499.14 | 08-NOV-14:20 | 14.83 | 11.30 |
December | 0.471567E+11 | 97062.62 | 04-DEC-05:11 | 5.60 | 5.31 | 0.546454E+10 | 7499.20 | 29-DEC-14:50 | 3.80 | 2.84 |
Annual Sum or Average | 0.590308E+12 | 0.677237E+11 | ||||||||
Minimum of Months | 0.372759E+11 | 85363.44 | 2.20 | 1.34 | 0.503238E+10 | 7499.11 | 3.80 | 2.84 | ||
Maximum of Months | 0.602594E+11 | 101005.68 | 19.80 | 15.19 | 0.613635E+10 | 7503.93 | 27.50 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273173E+11 | 73145.86 | 30-JAN-06:02 | -5.0 | -6.1 | 0.500642E+10 | 6741.91 | 18-JAN-10:20 | -5.0 | -6.1 |
February | 0.281667E+11 | 77892.06 | 21-FEB-05:11 | 2.20 | 1.34 | 0.457717E+10 | 6734.82 | 27-FEB-10:20 | -0.9 | -1.5 |
March | 0.419957E+11 | 80621.70 | 06-MAR-05:11 | 8.70 | 8.70 | 0.549708E+10 | 6734.83 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.468609E+11 | 81179.76 | 17-APR-04:13 | 12.43 | 10.77 | 0.488091E+10 | 6734.84 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.460318E+11 | 88071.92 | 30-MAY-04:13 | 17.80 | 14.10 | 0.528502E+10 | 6735.03 | 25-MAY-09:09 | 17.80 | 14.10 |
June | 0.538255E+11 | 87520.15 | 12-JUN-04:13 | 18.70 | 17.72 | 0.526888E+10 | 6798.65 | 22-JUN-13:20 | 28.87 | 17.36 |
July | 0.613904E+11 | 78255.79 | 01-JUL-04:12 | 20.00 | 19.55 | 0.489282E+10 | 6785.11 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.686296E+11 | 78954.55 | 07-AUG-05:04 | 19.40 | 16.74 | 0.549400E+10 | 6753.54 | 14-AUG-09:00 | 27.80 | 23.03 |
September | 0.471233E+11 | 84497.54 | 18-SEP-04:12 | 17.07 | 16.12 | 0.488232E+10 | 6734.98 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.475461E+11 | 84962.75 | 16-OCT-04:12 | 8.50 | 7.95 | 0.507778E+10 | 6735.12 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.400772E+11 | 86878.29 | 13-NOV-05:11 | 5.60 | 4.52 | 0.503010E+10 | 6734.87 | 09-NOV-14:00 | 5.60 | 4.52 |
December | 0.386148E+11 | 80748.07 | 26-DEC-05:11 | 5.77 | 4.97 | 0.489704E+10 | 6734.80 | 22-DEC-10:09 | 5.77 | 4.97 |
Annual Sum or Average | 0.547579E+12 | 0.607895E+11 | ||||||||
Minimum of Months | 0.273173E+11 | 73145.86 | -5.0 | -6.1 | 0.457717E+10 | 6734.80 | -5.0 | -6.1 | ||
Maximum of Months | 0.686296E+11 | 88071.92 | 20.00 | 19.55 | 0.549708E+10 | 6798.65 | 28.90 | 23.03 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182518E+11 | 20865.45 | 31-JAN-13:45 | -2.5 | -6.6 | 0.432233E+10 | 6605.08 | 27-JAN-14:00 | -2.5 | -6.6 |
February | 0.190703E+11 | 22391.66 | 02-FEB-08:00 | 3.90 | 0.41 | 0.407939E+10 | 6734.56 | 24-FEB-14:39 | 8.67 | 2.61 |
March | 0.251530E+11 | 49674.49 | 29-MAR-05:03 | 2.12 | 0.18 | 0.530298E+10 | 6790.89 | 30-MAR-09:50 | 3.72 | 2.56 |
April | 0.281822E+11 | 71297.99 | 10-APR-05:02 | 15.10 | 13.73 | 0.480757E+10 | 6734.80 | 05-APR-09:20 | 15.10 | 13.73 |
May | 0.369120E+11 | 73654.88 | 19-MAY-05:02 | 16.02 | 16.02 | 0.526767E+10 | 6736.63 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.420390E+11 | 75791.40 | 12-JUN-04:12 | 18.70 | 17.72 | 0.526534E+10 | 6753.76 | 22-JUN-13:20 | 28.87 | 17.36 |
July | 0.436113E+11 | 73686.41 | 11-JUL-04:12 | 19.80 | 15.19 | 0.489148E+10 | 6734.86 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.462883E+11 | 80766.48 | 07-AUG-04:13 | 18.67 | 17.05 | 0.549552E+10 | 6752.47 | 22-AUG-09:50 | 28.22 | 18.40 |
September | 0.381606E+11 | 74885.82 | 18-SEP-04:12 | 17.07 | 16.12 | 0.487243E+10 | 6734.95 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.339453E+11 | 72843.67 | 13-OCT-05:02 | 14.82 | 14.82 | 0.505023E+10 | 6735.05 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.234388E+11 | 66891.60 | 03-NOV-05:02 | 9.22 | 6.42 | 0.481722E+10 | 6734.80 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.211155E+11 | 21014.60 | 21-DEC-16:30 | 2.25 | -2.5 | 0.450895E+10 | 6734.61 | 21-DEC-14:30 | 2.25 | -2.5 |
Annual Sum or Average | 0.376168E+12 | 0.586811E+11 | ||||||||
Minimum of Months | 0.182518E+11 | 20865.45 | -2.5 | -6.6 | 0.407939E+10 | 6605.08 | -2.5 | -6.6 | ||
Maximum of Months | 0.462883E+11 | 80766.48 | 19.80 | 17.72 | 0.549552E+10 | 6790.89 | 29.50 | 21.33 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132851E+11 | 15655.88 | 20-JAN-17:00 | 5.60 | 3.19 | 0.399991E+10 | 6270.14 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.130114E+11 | 15757.96 | 17-FEB-17:00 | 5.60 | 1.58 | 0.367992E+10 | 6323.99 | 17-FEB-14:00 | 5.60 | 1.58 |
March | 0.202846E+11 | 26104.18 | 29-MAR-16:00 | 7.20 | 4.88 | 0.483562E+10 | 6734.68 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.243533E+11 | 67630.53 | 08-APR-05:03 | 14.32 | 11.97 | 0.459419E+10 | 6734.77 | 07-APR-13:20 | 14.32 | 11.97 |
May | 0.351315E+11 | 79023.15 | 30-MAY-04:13 | 17.80 | 14.10 | 0.521509E+10 | 6809.33 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.441733E+11 | 80667.16 | 26-JUN-04:13 | 20.60 | 16.81 | 0.526307E+10 | 6778.05 | 22-JUN-13:09 | 20.60 | 16.81 |
July | 0.480547E+11 | 75550.08 | 11-JUL-04:12 | 19.80 | 15.19 | 0.489644E+10 | 6734.79 | 12-JUL-13:20 | 28.70 | 18.81 |
August | 0.499243E+11 | 80538.33 | 07-AUG-04:11 | 18.67 | 17.05 | 0.549609E+10 | 6734.82 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.368288E+11 | 74382.09 | 06-SEP-04:12 | 21.30 | 18.82 | 0.485089E+10 | 6772.16 | 01-SEP-13:00 | 21.30 | 18.82 |
October | 0.285836E+11 | 68748.55 | 06-OCT-05:03 | 19.40 | 18.22 | 0.490771E+10 | 6734.99 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.172475E+11 | 25793.39 | 03-NOV-16:00 | 15.00 | 10.26 | 0.435136E+10 | 6734.71 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.144190E+11 | 15355.96 | 20-DEC-17:00 | 6.70 | 3.52 | 0.395245E+10 | 6286.14 | 20-DEC-14:00 | 6.70 | 3.52 |
Annual Sum or Average | 0.345297E+12 | 0.560427E+11 | ||||||||
Minimum of Months | 0.130114E+11 | 15355.96 | 5.60 | 1.58 | 0.367992E+10 | 6270.14 | 5.60 | 1.58 | ||
Maximum of Months | 0.499243E+11 | 80667.16 | 21.30 | 18.82 | 0.549609E+10 | 6809.33 | 29.50 | 18.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169027E+10 | 2203.93 | 24-JAN-06:02 | 11.10 | 11.10 | 0.522499E+09 | 809.41 | 20-JAN-14:50 | 11.10 | 11.10 |
February | 0.173431E+10 | 2626.82 | 20-FEB-13:23 | 9.15 | 4.45 | 0.482812E+09 | 830.28 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.327789E+10 | 6026.56 | 27-MAR-13:30 | 20.85 | 16.76 | 0.652663E+09 | 845.63 | 27-MAR-09:09 | 20.85 | 16.76 |
April | 0.485239E+10 | 7240.98 | 26-APR-13:40 | 18.30 | 12.75 | 0.601866E+09 | 845.64 | 26-APR-09:00 | 18.30 | 12.75 |
May | 0.651460E+10 | 12364.65 | 30-MAY-04:12 | 17.80 | 14.10 | 0.661662E+09 | 845.67 | 15-MAY-13:50 | 17.80 | 14.10 |
June | 0.949853E+10 | 13153.24 | 12-JUN-04:12 | 18.70 | 17.72 | 0.662111E+09 | 860.83 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.113726E+11 | 15970.93 | 30-JUL-14:31 | 26.13 | 22.93 | 0.615976E+09 | 872.03 | 11-JUL-13:00 | 26.13 | 22.93 |
August | 0.119820E+11 | 16518.01 | 13-AUG-15:01 | 30.50 | 20.85 | 0.690589E+09 | 848.79 | 14-AUG-09:00 | 27.80 | 23.03 |
September | 0.666895E+10 | 12040.34 | 02-SEP-04:12 | 22.60 | 16.46 | 0.611752E+09 | 845.65 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.511753E+10 | 6829.21 | 04-OCT-13:10 | 24.90 | 18.61 | 0.630560E+09 | 845.67 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.298447E+10 | 4651.95 | 03-NOV-13:30 | 17.50 | 10.63 | 0.600068E+09 | 845.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.247068E+10 | 2930.80 | 26-DEC-13:30 | 9.45 | 5.02 | 0.552281E+09 | 845.61 | 20-DEC-14:09 | 9.45 | 5.02 |
Annual Sum or Average | 0.681642E+11 | 0.728484E+10 | ||||||||
Minimum of Months | 0.169027E+10 | 2203.93 | 9.15 | 4.45 | 0.482812E+09 | 809.41 | 9.03 | 2.95 | ||
Maximum of Months | 0.119820E+11 | 16518.01 | 30.50 | 22.93 | 0.690589E+09 | 872.03 | 28.58 | 23.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126230E+10 | 4310.24 | 19-JAN-09:30 | 6.10 | 3.63 | 0.352795E+09 | 544.95 | 31-JAN-10:20 | -6.3 | -9.2 |
February | 0.137401E+10 | 5801.26 | 22-FEB-09:20 | 0.20 | -3.3 | 0.331529E+09 | 544.96 | 08-FEB-10:50 | 0.20 | -3.3 |
March | 0.312203E+10 | 11271.95 | 26-MAR-08:23 | 9.45 | 8.46 | 0.426422E+09 | 544.95 | 20-MAR-13:30 | 9.45 | 8.46 |
April | 0.447879E+10 | 19286.00 | 23-APR-07:33 | 10.20 | 6.90 | 0.387076E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.640004E+10 | 21402.19 | 29-MAY-08:12 | 24.63 | 16.73 | 0.427013E+09 | 546.29 | 30-MAY-09:09 | 26.38 | 17.06 |
June | 0.773242E+10 | 20509.08 | 25-JUN-08:22 | 25.00 | 23.26 | 0.426872E+09 | 553.32 | 22-JUN-13:20 | 25.00 | 23.26 |
July | 0.894351E+10 | 21019.02 | 02-JUL-08:32 | 25.20 | 21.54 | 0.397158E+09 | 551.10 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.101840E+11 | 20853.74 | 13-AUG-09:01 | 27.98 | 19.16 | 0.445128E+09 | 548.42 | 14-AUG-09:00 | 27.80 | 23.03 |
September | 0.616693E+10 | 23379.90 | 04-SEP-08:41 | 23.72 | 18.57 | 0.394996E+09 | 545.76 | 06-SEP-09:30 | 26.15 | 19.35 |
October | 0.484038E+10 | 11122.34 | 09-OCT-09:03 | 10.78 | 6.18 | 0.407920E+09 | 545.00 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.231973E+10 | 6592.93 | 02-NOV-08:50 | 10.82 | 5.71 | 0.391225E+09 | 544.96 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.169349E+10 | 4952.32 | 20-DEC-09:30 | 7.20 | 4.58 | 0.359437E+09 | 544.95 | 20-DEC-10:20 | 8.50 | 5.06 |
Annual Sum or Average | 0.585176E+11 | 0.474757E+10 | ||||||||
Minimum of Months | 0.126230E+10 | 4310.24 | 0.20 | -3.3 | 0.331529E+09 | 544.95 | -6.3 | -9.2 | ||
Maximum of Months | 0.101840E+11 | 23379.90 | 27.98 | 23.26 | 0.445128E+09 | 553.32 | 28.90 | 23.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365708E+10 | 14699.72 | 17-JAN-13:05 | 10.18 | 5.51 | 0.564493E+09 | 845.67 | 19-JAN-14:09 | 9.32 | 3.68 |
February | 0.431358E+10 | 23603.53 | 20-FEB-13:23 | 9.15 | 4.45 | 0.529860E+09 | 846.12 | 22-FEB-14:39 | 4.60 | -1.0 |
March | 0.711575E+10 | 18066.86 | 01-MAR-13:05 | 13.90 | 6.68 | 0.659112E+09 | 847.43 | 28-MAR-13:09 | 13.80 | 8.65 |
April | 0.730235E+10 | 18777.07 | 16-APR-13:32 | 21.50 | 13.46 | 0.598511E+09 | 849.84 | 07-APR-13:50 | 21.50 | 13.46 |
May | 0.803247E+10 | 22946.04 | 28-MAY-13:23 | 25.30 | 14.63 | 0.660404E+09 | 852.20 | 30-MAY-13:30 | 29.70 | 17.47 |
June | 0.106540E+11 | 23324.51 | 18-JUN-13:52 | 26.10 | 22.26 | 0.662234E+09 | 865.57 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.131411E+11 | 24638.54 | 30-JUL-14:31 | 26.13 | 22.93 | 0.616332E+09 | 880.15 | 11-JUL-13:00 | 26.13 | 22.93 |
August | 0.166018E+11 | 26011.98 | 13-AUG-13:41 | 31.60 | 19.81 | 0.691665E+09 | 882.53 | 30-AUG-13:09 | 27.48 | 15.59 |
September | 0.117126E+11 | 26860.92 | 04-SEP-12:41 | 26.10 | 18.22 | 0.614102E+09 | 904.39 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.122263E+11 | 24548.07 | 08-OCT-12:02 | 10.68 | 5.13 | 0.636342E+09 | 944.95 | 04-OCT-13:39 | 10.68 | 5.13 |
November | 0.619317E+10 | 19093.25 | 02-NOV-12:40 | 15.40 | 8.14 | 0.611431E+09 | 873.52 | 02-NOV-13:09 | 15.68 | 8.29 |
December | 0.508688E+10 | 23272.18 | 17-DEC-13:02 | 12.20 | 5.01 | 0.571342E+09 | 846.35 | 21-DEC-14:20 | 3.30 | -1.7 |
Annual Sum or Average | 0.106037E+12 | 0.741583E+10 | ||||||||
Minimum of Months | 0.365708E+10 | 14699.72 | 9.15 | 4.45 | 0.529860E+09 | 845.67 | 3.30 | -1.7 | ||
Maximum of Months | 0.166018E+11 | 26860.92 | 31.60 | 22.93 | 0.691665E+09 | 944.95 | 29.70 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187702E+10 | 6811.10 | 20-JAN-15:30 | 7.50 | 3.89 | 0.373098E+09 | 544.95 | 26-JAN-14:39 | 4.40 | 1.05 |
February | 0.248471E+10 | 10044.95 | 20-FEB-16:03 | 7.12 | 4.40 | 0.352738E+09 | 544.95 | 15-FEB-14:09 | 7.12 | 4.40 |
March | 0.609305E+10 | 17418.39 | 26-MAR-17:42 | 10.10 | 9.17 | 0.443674E+09 | 544.96 | 01-MAR-14:00 | 10.10 | 9.17 |
April | 0.858752E+10 | 26420.84 | 09-APR-16:02 | 17.02 | 14.08 | 0.395960E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.808912E+10 | 24272.99 | 14-MAY-15:52 | 13.30 | 9.05 | 0.428531E+09 | 545.00 | 15-MAY-13:50 | 18.27 | 11.33 |
June | 0.116375E+11 | 30139.22 | 18-JUN-15:51 | 25.60 | 22.09 | 0.427966E+09 | 556.29 | 22-JUN-13:20 | 28.87 | 17.36 |
July | 0.138015E+11 | 28237.64 | 30-JUL-15:11 | 25.77 | 22.82 | 0.398410E+09 | 554.75 | 11-JUL-13:00 | 25.77 | 22.82 |
August | 0.168284E+11 | 30384.53 | 13-AUG-15:41 | 30.10 | 20.54 | 0.446708E+09 | 547.76 | 14-AUG-09:00 | 27.80 | 23.03 |
September | 0.815393E+10 | 29146.82 | 10-SEP-15:31 | 23.67 | 13.25 | 0.395971E+09 | 544.97 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.770885E+10 | 22245.67 | 15-OCT-15:12 | 20.20 | 12.62 | 0.411318E+09 | 545.00 | 04-OCT-13:39 | 20.20 | 12.62 |
November | 0.434358E+10 | 12296.63 | 04-NOV-05:03 | 10.50 | 9.29 | 0.405286E+09 | 544.97 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.382161E+10 | 11742.45 | 04-DEC-05:11 | 5.60 | 5.31 | 0.394765E+09 | 544.96 | 29-DEC-14:50 | 3.80 | 2.84 |
Annual Sum or Average | 0.934268E+11 | 0.487443E+10 | ||||||||
Minimum of Months | 0.187702E+10 | 6811.10 | 5.60 | 3.89 | 0.352738E+09 | 544.95 | 3.80 | 1.05 | ||
Maximum of Months | 0.168284E+11 | 30384.53 | 30.10 | 22.82 | 0.446708E+09 | 556.29 | 28.87 | 23.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279573E+09 | 1566.14 | 13-JAN-13:10 | 9.08 | 6.15 | 0.465831E+09 | 672.52 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.351256E+09 | 1700.58 | 17-FEB-13:25 | 6.70 | 1.90 | 0.425261E+09 | 687.69 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.155741E+10 | 2586.60 | 27-MAR-16:00 | 22.20 | 16.34 | 0.550975E+09 | 845.61 | 28-MAR-13:39 | 13.50 | 8.51 |
April | 0.267658E+10 | 5398.96 | 07-APR-14:00 | 26.10 | 15.95 | 0.550342E+09 | 845.64 | 10-APR-13:20 | 20.20 | 10.17 |
May | 0.511888E+10 | 11667.20 | 30-MAY-05:03 | 18.17 | 14.31 | 0.651476E+09 | 847.58 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.790048E+10 | 12102.03 | 22-JUN-05:03 | 22.88 | 15.44 | 0.661338E+09 | 862.72 | 22-JUN-13:50 | 29.72 | 17.64 |
July | 0.918169E+10 | 15720.65 | 09-JUL-14:31 | 28.70 | 24.38 | 0.616032E+09 | 846.63 | 25-JUL-13:20 | 28.53 | 24.38 |
August | 0.903998E+10 | 14691.50 | 13-AUG-15:51 | 30.00 | 20.46 | 0.690612E+09 | 848.55 | 22-AUG-09:50 | 28.22 | 18.40 |
September | 0.543624E+10 | 11547.33 | 02-SEP-05:03 | 22.12 | 16.30 | 0.606079E+09 | 845.65 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.345186E+10 | 5685.86 | 05-OCT-14:00 | 23.30 | 18.86 | 0.601698E+09 | 845.64 | 04-OCT-13:39 | 23.30 | 18.86 |
November | 0.137212E+10 | 2559.61 | 02-NOV-14:10 | 16.20 | 8.76 | 0.507295E+09 | 843.73 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.437180E+09 | 1616.24 | 20-DEC-13:30 | 9.70 | 5.75 | 0.451967E+09 | 690.55 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.468032E+11 | 0.677890E+10 | ||||||||
Minimum of Months | 0.279573E+09 | 1566.14 | 6.70 | 1.90 | 0.425261E+09 | 672.52 | 7.80 | 2.27 | ||
Maximum of Months | 0.918169E+10 | 15720.65 | 30.00 | 24.38 | 0.690612E+09 | 862.72 | 29.72 | 24.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294587E+09 | 1541.76 | 27-JAN-11:05 | 5.00 | 1.60 | 0.227507E+09 | 534.05 | 27-JAN-11:09 | 5.00 | 1.60 |
February | 0.437147E+09 | 3609.04 | 22-FEB-11:05 | 2.38 | -2.1 | 0.213245E+09 | 548.49 | 02-FEB-11:09 | 2.38 | -2.1 |
March | 0.168917E+10 | 9287.62 | 29-MAR-10:05 | 7.07 | 3.67 | 0.289823E+09 | 548.49 | 22-MAR-10:09 | 7.07 | 3.67 |
April | 0.323230E+10 | 12033.07 | 07-APR-10:05 | 21.97 | 14.06 | 0.274912E+09 | 548.52 | 06-APR-12:09 | 21.97 | 14.06 |
May | 0.583386E+10 | 25881.56 | 29-MAY-08:31 | 25.37 | 16.74 | 0.312191E+09 | 548.52 | 15-MAY-14:09 | 25.37 | 16.74 |
June | 0.732704E+10 | 23386.80 | 04-JUN-10:02 | 24.60 | 13.01 | 0.314818E+09 | 548.55 | 22-JUN-14:09 | 30.10 | 17.77 |
July | 0.849233E+10 | 25464.86 | 02-JUL-07:41 | 24.13 | 21.14 | 0.294347E+09 | 551.01 | 11-JUL-14:09 | 28.80 | 17.79 |
August | 0.953812E+10 | 23408.17 | 20-AUG-09:12 | 22.43 | 14.98 | 0.328750E+09 | 551.24 | 22-AUG-10:09 | 28.48 | 18.44 |
September | 0.567052E+10 | 25301.86 | 04-SEP-08:51 | 23.90 | 18.54 | 0.290319E+09 | 548.51 | 19-SEP-10:09 | 20.00 | 15.38 |
October | 0.382900E+10 | 12372.29 | 15-OCT-10:22 | 18.85 | 13.18 | 0.295809E+09 | 548.50 | 02-OCT-10:09 | 18.85 | 13.18 |
November | 0.111526E+10 | 6381.12 | 02-NOV-10:05 | 12.48 | 6.40 | 0.258509E+09 | 548.49 | 03-NOV-12:09 | 16.28 | 9.98 |
December | 0.452590E+09 | 3166.20 | 20-DEC-11:05 | 8.90 | 5.16 | 0.226594E+09 | 548.49 | 20-DEC-11:09 | 8.90 | 5.16 |
Annual Sum or Average | 0.479119E+11 | 0.332682E+10 | ||||||||
Minimum of Months | 0.294587E+09 | 1541.76 | 2.38 | -2.1 | 0.213245E+09 | 534.05 | 2.38 | -2.1 | ||
Maximum of Months | 0.953812E+10 | 25881.56 | 25.37 | 21.14 | 0.328750E+09 | 551.24 | 30.10 | 18.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261317E+10 | 18769.20 | 31-JAN-13:45 | -2.5 | -6.6 | 0.532218E+09 | 864.04 | 31-JAN-13:50 | -2.5 | -6.6 |
February | 0.339101E+10 | 18384.59 | 20-FEB-13:43 | 8.98 | 4.49 | 0.501402E+09 | 879.92 | 08-FEB-10:30 | 8.98 | 4.49 |
March | 0.585868E+10 | 18494.98 | 01-MAR-13:20 | 13.90 | 6.52 | 0.623704E+09 | 846.66 | 23-MAR-13:09 | 5.50 | 0.16 |
April | 0.567975E+10 | 17192.69 | 07-APR-12:30 | 26.15 | 15.90 | 0.574839E+09 | 846.69 | 10-APR-13:20 | 20.20 | 10.17 |
May | 0.720174E+10 | 24376.69 | 29-MAY-11:12 | 28.17 | 18.16 | 0.653129E+09 | 865.43 | 30-MAY-14:39 | 28.67 | 17.12 |
June | 0.937863E+10 | 23322.59 | 18-JUN-13:52 | 26.10 | 22.26 | 0.661462E+09 | 865.18 | 22-JUN-13:50 | 29.72 | 17.64 |
July | 0.112287E+11 | 24764.05 | 09-JUL-13:12 | 31.70 | 25.23 | 0.616452E+09 | 852.15 | 11-JUL-13:30 | 28.35 | 17.93 |
August | 0.143143E+11 | 25404.38 | 20-AUG-12:32 | 27.43 | 15.69 | 0.692547E+09 | 901.91 | 30-AUG-13:39 | 28.33 | 15.54 |
September | 0.114320E+11 | 27490.88 | 04-SEP-11:31 | 25.93 | 17.72 | 0.613490E+09 | 949.89 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.117838E+11 | 26730.75 | 15-OCT-12:21 | 20.30 | 13.25 | 0.632468E+09 | 965.07 | 04-OCT-13:39 | 20.30 | 13.25 |
November | 0.499121E+10 | 19610.60 | 02-NOV-13:05 | 15.68 | 8.29 | 0.583251E+09 | 900.58 | 02-NOV-13:20 | 15.77 | 8.37 |
December | 0.341112E+10 | 23488.05 | 03-DEC-14:13 | 8.70 | 3.85 | 0.534745E+09 | 855.52 | 14-DEC-10:39 | 5.03 | 0.96 |
Annual Sum or Average | 0.912840E+11 | 0.721971E+10 | ||||||||
Minimum of Months | 0.261317E+10 | 17192.69 | -2.5 | -6.6 | 0.501402E+09 | 846.66 | -2.5 | -6.6 | ||
Maximum of Months | 0.143143E+11 | 27490.88 | 31.70 | 25.23 | 0.692547E+09 | 965.07 | 29.72 | 17.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.543397E+09 | 3654.63 | 31-JAN-16:00 | -1.1 | -5.7 | 0.315868E+09 | 544.94 | 20-JAN-14:00 | -1.1 | -5.7 |
February | 0.762199E+09 | 5611.07 | 24-FEB-15:40 | 7.97 | 1.96 | 0.292742E+09 | 544.94 | 24-FEB-14:39 | 7.97 | 1.96 |
March | 0.250483E+10 | 10614.32 | 29-MAR-16:00 | 7.20 | 4.88 | 0.384477E+09 | 544.95 | 28-MAR-13:20 | 7.20 | 4.88 |
April | 0.379569E+10 | 24121.34 | 09-APR-16:31 | 16.47 | 13.91 | 0.370461E+09 | 544.97 | 10-APR-13:30 | 20.30 | 10.24 |
May | 0.602273E+10 | 23484.77 | 28-MAY-15:42 | 24.37 | 15.55 | 0.423550E+09 | 556.43 | 30-MAY-14:39 | 28.67 | 17.12 |
June | 0.857596E+10 | 27370.34 | 18-JUN-15:51 | 25.60 | 22.09 | 0.427159E+09 | 548.75 | 01-JUN-15:09 | 25.60 | 22.09 |
July | 0.937611E+10 | 27365.02 | 02-JUL-16:21 | 24.70 | 20.69 | 0.397792E+09 | 544.97 | 14-JUL-09:30 | 29.75 | 21.24 |
August | 0.105850E+11 | 25633.15 | 20-AUG-16:31 | 25.20 | 17.51 | 0.446072E+09 | 547.06 | 22-AUG-09:50 | 28.22 | 18.40 |
September | 0.616004E+10 | 26682.34 | 10-SEP-16:21 | 23.05 | 12.79 | 0.393317E+09 | 544.97 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.458314E+10 | 22443.76 | 15-OCT-15:41 | 19.60 | 12.30 | 0.398741E+09 | 544.98 | 04-OCT-13:39 | 19.60 | 12.30 |
November | 0.139992E+10 | 6956.41 | 03-NOV-15:30 | 16.10 | 10.65 | 0.346632E+09 | 544.96 | 08-NOV-14:30 | 14.45 | 11.27 |
December | 0.740887E+09 | 3327.53 | 08-DEC-15:30 | 6.40 | 2.12 | 0.309622E+09 | 544.95 | 18-DEC-14:39 | 6.67 | 2.71 |
Annual Sum or Average | 0.550499E+11 | 0.450643E+10 | ||||||||
Minimum of Months | 0.543397E+09 | 3327.53 | -1.1 | -5.7 | 0.292742E+09 | 544.94 | -1.1 | -5.7 | ||
Maximum of Months | 0.105850E+11 | 27370.34 | 25.60 | 22.09 | 0.446072E+09 | 556.43 | 29.75 | 22.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126836E+09 | 1410.29 | 20-JAN-15:10 | 7.70 | 3.95 | 0.463570E+09 | 643.82 | 20-JAN-14:00 | 7.70 | 3.95 |
February | 0.147673E+09 | 1431.97 | 17-FEB-15:40 | 6.10 | 1.74 | 0.421081E+09 | 650.73 | 17-FEB-14:00 | 6.10 | 1.74 |
March | 0.985118E+09 | 2255.94 | 28-MAR-13:50 | 13.40 | 8.46 | 0.532410E+09 | 845.60 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.227718E+10 | 6184.34 | 07-APR-14:00 | 26.10 | 15.95 | 0.527776E+09 | 845.63 | 07-APR-13:20 | 26.10 | 15.95 |
May | 0.494855E+10 | 17421.84 | 29-MAY-14:02 | 26.02 | 17.36 | 0.638428E+09 | 862.11 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.816721E+10 | 13172.06 | 20-JUN-04:11 | 20.93 | 18.14 | 0.660492E+09 | 850.93 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.983399E+10 | 18631.52 | 09-JUL-14:31 | 28.70 | 24.38 | 0.616225E+09 | 846.02 | 10-JUL-13:00 | 32.80 | 20.89 |
August | 0.954847E+10 | 17544.89 | 13-AUG-15:51 | 30.00 | 20.46 | 0.690178E+09 | 845.64 | 08-AUG-13:00 | 30.00 | 20.46 |
September | 0.531532E+10 | 12268.29 | 02-SEP-05:03 | 22.12 | 16.30 | 0.599607E+09 | 852.12 | 01-SEP-13:00 | 22.12 | 16.30 |
October | 0.295807E+10 | 6054.02 | 04-OCT-13:40 | 24.60 | 18.82 | 0.577026E+09 | 845.64 | 04-OCT-13:39 | 24.60 | 18.82 |
November | 0.832178E+09 | 2388.94 | 02-NOV-13:30 | 15.85 | 8.46 | 0.483052E+09 | 821.40 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 90491380.05 | 1406.11 | 20-DEC-13:40 | 9.80 | 5.81 | 0.447841E+09 | 642.51 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.452311E+11 | 0.665769E+10 | ||||||||
Minimum of Months | 90491380.05 | 1406.11 | 6.10 | 1.74 | 0.421081E+09 | 642.51 | 6.10 | 1.74 | ||
Maximum of Months | 0.983399E+10 | 18631.52 | 30.00 | 24.38 | 0.690178E+09 | 862.11 | 32.80 | 20.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240078E+09 | 1254.98 | 19-JAN-10:20 | 7.80 | 4.36 | 0.305180E+09 | 516.12 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.352786E+09 | 1315.71 | 22-FEB-10:20 | 1.13 | -2.8 | 0.281154E+09 | 536.35 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.139765E+10 | 6741.17 | 29-MAR-09:30 | 6.15 | 3.19 | 0.381847E+09 | 544.95 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.300456E+10 | 11209.54 | 28-APR-08:50 | 15.82 | 8.80 | 0.366117E+09 | 544.97 | 26-APR-09:50 | 15.82 | 8.80 |
May | 0.588615E+10 | 25860.32 | 29-MAY-08:61 | 24.27 | 16.71 | 0.418950E+09 | 551.20 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.773569E+10 | 23279.22 | 25-JUN-08:42 | 25.40 | 23.51 | 0.426558E+09 | 546.74 | 22-JUN-13:09 | 25.40 | 23.51 |
July | 0.920771E+10 | 25815.62 | 02-JUL-07:41 | 24.13 | 21.14 | 0.397629E+09 | 546.83 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.101588E+11 | 23068.13 | 13-AUG-09:12 | 28.17 | 19.21 | 0.445620E+09 | 555.28 | 22-AUG-09:50 | 28.22 | 18.40 |
September | 0.576727E+10 | 23586.61 | 03-SEP-08:22 | 21.95 | 15.03 | 0.391277E+09 | 549.94 | 01-SEP-13:00 | 21.95 | 15.03 |
October | 0.350874E+10 | 9446.73 | 05-OCT-09:10 | 19.08 | 16.88 | 0.395724E+09 | 546.09 | 18-OCT-09:00 | 10.00 | 4.89 |
November | 0.880601E+09 | 3371.60 | 03-NOV-09:30 | 13.05 | 8.24 | 0.332427E+09 | 544.95 | 08-NOV-10:20 | 11.67 | 9.14 |
December | 0.313770E+09 | 1264.06 | 20-DEC-10:00 | 8.30 | 5.00 | 0.294465E+09 | 519.34 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.484538E+11 | 0.443695E+10 | ||||||||
Minimum of Months | 0.240078E+09 | 1254.98 | 1.13 | -2.8 | 0.281154E+09 | 516.12 | 1.13 | -2.8 | ||
Maximum of Months | 0.101588E+11 | 25860.32 | 28.17 | 23.51 | 0.445620E+09 | 555.28 | 30.60 | 23.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201686E+10 | 13675.49 | 19-JAN-13:30 | 9.40 | 3.94 | 0.522847E+09 | 845.65 | 11-JAN-14:20 | 9.40 | 3.94 |
February | 0.257534E+10 | 14345.70 | 22-FEB-13:40 | 4.63 | -1.0 | 0.486797E+09 | 845.64 | 17-FEB-14:09 | 4.63 | -1.0 |
March | 0.478925E+10 | 18569.02 | 01-MAR-13:30 | 13.90 | 6.36 | 0.602972E+09 | 846.27 | 03-MAR-14:50 | 15.00 | 8.43 |
April | 0.506931E+10 | 17981.55 | 07-APR-12:40 | 26.33 | 16.06 | 0.556841E+09 | 846.32 | 07-APR-13:39 | 26.30 | 16.10 |
May | 0.700564E+10 | 27074.85 | 29-MAY-13:22 | 26.65 | 17.22 | 0.641780E+09 | 880.29 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.964261E+10 | 20010.36 | 25-JUN-11:23 | 25.55 | 22.82 | 0.660423E+09 | 861.68 | 22-JUN-13:09 | 25.55 | 22.82 |
July | 0.119227E+11 | 27729.98 | 09-JUL-14:31 | 28.70 | 24.38 | 0.616515E+09 | 849.46 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.148688E+11 | 26679.67 | 13-AUG-13:12 | 31.30 | 19.70 | 0.691684E+09 | 883.04 | 30-AUG-13:09 | 27.48 | 15.59 |
September | 0.112612E+11 | 29171.62 | 03-SEP-11:41 | 24.60 | 15.78 | 0.608185E+09 | 920.94 | 28-SEP-13:30 | 23.35 | 13.54 |
October | 0.106444E+11 | 28657.86 | 15-OCT-12:21 | 20.30 | 13.25 | 0.618598E+09 | 942.11 | 04-OCT-13:39 | 20.30 | 13.25 |
November | 0.378145E+10 | 20209.78 | 02-NOV-13:05 | 15.68 | 8.29 | 0.559482E+09 | 847.85 | 02-NOV-13:20 | 15.77 | 8.37 |
December | 0.229666E+10 | 19475.76 | 17-DEC-13:12 | 12.20 | 5.06 | 0.515016E+09 | 845.64 | 14-DEC-14:09 | 12.20 | 5.06 |
Annual Sum or Average | 0.858743E+11 | 0.708114E+10 | ||||||||
Minimum of Months | 0.201686E+10 | 13675.49 | 4.63 | -1.0 | 0.486797E+09 | 845.64 | 4.63 | -1.0 | ||
Maximum of Months | 0.148688E+11 | 29171.62 | 31.30 | 24.38 | 0.691684E+09 | 942.11 | 29.50 | 22.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383030E+09 | 3133.89 | 19-JAN-15:30 | 8.60 | 3.27 | 0.311347E+09 | 544.92 | 17-JAN-14:00 | 8.60 | 3.27 |
February | 0.543080E+09 | 4912.48 | 24-FEB-15:30 | 8.05 | 2.04 | 0.287496E+09 | 544.93 | 17-FEB-14:50 | 8.05 | 2.04 |
March | 0.209396E+10 | 10418.65 | 29-MAR-16:00 | 7.20 | 4.88 | 0.369801E+09 | 544.95 | 27-MAR-13:20 | 7.20 | 4.88 |
April | 0.350632E+10 | 26882.53 | 09-APR-16:21 | 16.65 | 13.97 | 0.357425E+09 | 544.96 | 07-APR-13:20 | 16.65 | 13.97 |
May | 0.593187E+10 | 25906.66 | 28-MAY-15:11 | 25.77 | 15.53 | 0.417498E+09 | 552.94 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.872947E+10 | 26499.27 | 18-JUN-16:01 | 25.50 | 22.07 | 0.426712E+09 | 546.76 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.983237E+10 | 29355.59 | 02-JUL-16:21 | 24.70 | 20.69 | 0.397861E+09 | 549.85 | 11-JUL-14:30 | 28.60 | 17.71 |
August | 0.109350E+11 | 25974.27 | 13-AUG-15:51 | 30.00 | 20.46 | 0.445955E+09 | 544.97 | 08-AUG-13:00 | 30.00 | 20.46 |
September | 0.607631E+10 | 26551.91 | 03-SEP-15:01 | 25.00 | 16.71 | 0.390560E+09 | 551.70 | 01-SEP-13:00 | 25.00 | 16.71 |
October | 0.416975E+10 | 21640.87 | 15-OCT-15:41 | 19.60 | 12.30 | 0.386978E+09 | 544.98 | 04-OCT-13:39 | 19.60 | 12.30 |
November | 0.102698E+10 | 6591.84 | 03-NOV-15:30 | 16.10 | 10.65 | 0.330136E+09 | 544.96 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.401950E+09 | 2602.39 | 08-DEC-15:30 | 6.40 | 2.12 | 0.301394E+09 | 544.90 | 21-DEC-14:00 | 3.30 | -1.8 |
Annual Sum or Average | 0.536301E+11 | 0.442316E+10 | ||||||||
Minimum of Months | 0.383030E+09 | 2602.39 | 6.40 | 2.04 | 0.287496E+09 | 544.90 | 3.30 | -1.8 | ||
Maximum of Months | 0.109350E+11 | 29355.59 | 30.00 | 22.07 | 0.445955E+09 | 552.94 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201864E+09 | 5709.77 | 31-JAN-06:01 | -8.4 | -10.7 | 0.00 | 0.00 | 01-JAN-00:10 | -8.4 | -10.7 |
February | 0.290110E+09 | 6977.41 | 06-FEB-05:01 | -13.2 | -14.5 | 0.00 | 0.00 | 01-FEB-00:10 | -13.2 | -14.5 |
March | 0.157396E+10 | 3476.28 | 28-MAR-05:15 | 9.60 | 7.49 | 0.00 | 0.00 | 01-MAR-00:10 | 9.60 | 7.49 |
April | 0.356303E+10 | 7465.06 | 10-APR-05:15 | 15.20 | 13.76 | 0.00 | 0.00 | 01-APR-00:10 | 15.20 | 13.76 |
May | 0.478709E+10 | 12092.49 | 30-MAY-05:15 | 18.53 | 14.51 | 0.00 | 0.00 | 01-MAY-00:10 | 18.53 | 14.51 |
June | 0.748955E+10 | 9934.29 | 19-JUN-05:15 | 24.27 | 22.23 | 0.00 | 0.00 | 01-JUN-00:10 | 24.27 | 22.23 |
July | 0.875130E+10 | 11757.93 | 10-JUL-05:15 | 26.10 | 20.74 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 20.74 |
August | 0.100046E+11 | 11671.82 | 14-AUG-05:15 | 22.57 | 20.98 | 0.00 | 0.00 | 01-AUG-00:10 | 22.57 | 20.98 |
September | 0.606128E+10 | 12558.89 | 05-SEP-05:15 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20.60 | 18.00 |
October | 0.493276E+10 | 7595.74 | 23-OCT-05:15 | 13.13 | 11.01 | 0.00 | 0.00 | 01-OCT-00:10 | 13.13 | 11.01 |
November | 0.192854E+10 | 5567.17 | 13-NOV-06:15 | 5.77 | 4.71 | 0.00 | 0.00 | 01-NOV-00:10 | 5.77 | 4.71 |
December | 0.863702E+09 | 2761.34 | 18-DEC-06:10 | 0.60 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | 0.60 | -1.3 |
Annual Sum or Average | 0.504478E+11 | 0.00 | ||||||||
Minimum of Months | 0.201864E+09 | 2761.34 | -13.2 | -14.5 | 0.00 | 0.00 | -13.2 | -14.5 | ||
Maximum of Months | 0.100046E+11 | 12558.89 | 26.10 | 22.23 | 0.00 | 0.00 | 26.10 | 22.23 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100570E+09 | 8937.38 | 14-JAN-04:01 | -6.8 | -7.5 | 0.00 | 0.00 | 01-JAN-00:10 | -6.8 | -7.5 |
February | 99735558.27 | 8373.62 | 05-FEB-23:02 | -12.4 | -14.1 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -14.1 |
March | 0.312506E+09 | 8152.69 | 17-MAR-04:01 | -1.6 | -2.4 | 0.00 | 0.00 | 01-MAR-00:10 | -1.6 | -2.4 |
April | 0.109598E+10 | 5789.97 | 01-APR-05:02 | 2.70 | 1.16 | 0.00 | 0.00 | 01-APR-00:10 | 2.70 | 1.16 |
May | 0.282350E+10 | 6980.61 | 30-MAY-13:35 | 29.60 | 17.29 | 0.00 | 0.00 | 01-MAY-00:10 | 29.60 | 17.29 |
June | 0.551752E+10 | 6980.70 | 20-JUN-15:10 | 26.93 | 17.32 | 0.00 | 0.00 | 01-JUN-00:10 | 26.93 | 17.32 |
July | 0.674738E+10 | 8746.50 | 10-JUL-05:02 | 26.10 | 20.74 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 20.74 |
August | 0.747903E+10 | 8095.58 | 07-AUG-05:02 | 19.40 | 16.74 | 0.00 | 0.00 | 01-AUG-00:10 | 19.40 | 16.74 |
September | 0.433353E+10 | 7956.18 | 05-SEP-05:15 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20.60 | 18.00 |
October | 0.230645E+10 | 4400.17 | 05-OCT-15:50 | 21.78 | 19.16 | 0.00 | 0.00 | 01-OCT-00:10 | 21.78 | 19.16 |
November | 0.395525E+09 | 7665.28 | 20-NOV-05:01 | 0.50 | -0.9 | 0.00 | 0.00 | 01-NOV-00:10 | 0.50 | -0.9 |
December | 94637837.77 | 7470.74 | 02-DEC-05:01 | 1.10 | -2.4 | 0.00 | 0.00 | 01-DEC-00:10 | 1.10 | -2.4 |
Annual Sum or Average | 0.313064E+11 | 0.00 | ||||||||
Minimum of Months | 94637837.77 | 4400.17 | -12.4 | -14.1 | 0.00 | 0.00 | -12.4 | -14.1 | ||
Maximum of Months | 0.747903E+10 | 8937.38 | 29.60 | 20.74 | 0.00 | 0.00 | 29.60 | 20.74 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 |
February | 2745987.58 | 462.43 | 18-FEB-15:15 | 6.70 | 3.09 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 3.09 |
March | 0.598291E+09 | 5734.29 | 03-MAR-14:40 | 15.00 | 8.47 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.47 |
April | 0.252578E+10 | 13225.78 | 07-APR-14:40 | 25.77 | 15.95 | 0.00 | 0.00 | 01-APR-00:10 | 25.77 | 15.95 |
May | 0.599465E+10 | 20887.10 | 30-MAY-13:40 | 29.60 | 17.29 | 0.00 | 0.00 | 01-MAY-00:10 | 29.60 | 17.29 |
June | 0.105245E+11 | 20805.30 | 19-JUN-13:30 | 34.70 | 23.81 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 23.81 |
July | 0.129063E+11 | 19767.85 | 10-JUL-13:50 | 32.70 | 20.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 20.82 |
August | 0.137347E+11 | 19806.88 | 30-AUG-14:40 | 29.23 | 15.23 | 0.00 | 0.00 | 01-AUG-00:10 | 29.23 | 15.23 |
September | 0.663363E+10 | 18479.44 | 01-SEP-12:05 | 30.10 | 18.38 | 0.00 | 0.00 | 01-SEP-00:10 | 30.10 | 18.38 |
October | 0.323833E+10 | 11620.34 | 04-OCT-13:25 | 24.70 | 18.75 | 0.00 | 0.00 | 01-OCT-00:10 | 24.70 | 18.75 |
November | 0.192976E+09 | 3540.92 | 03-NOV-14:10 | 17.70 | 10.72 | 0.00 | 0.00 | 01-NOV-00:10 | 17.70 | 10.72 |
December | 1936498.66 | 1081.59 | 17-DEC-13:56 | 12.20 | 5.29 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.29 |
Annual Sum or Average | 0.563539E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.00 | 0.00 | -9.6 | -11.5 | ||
Maximum of Months | 0.137347E+11 | 20887.10 | 34.70 | 23.81 | 0.00 | 0.00 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235434E+10 | 1928.64 | 20-JAN-16:30 | 6.40 | 3.51 | 95228853.20 | 126.83 | 24-JAN-14:00 | 11.00 | 11.00 |
February | 0.725369E+10 | 4022.03 | 14-FEB-17:00 | 0.00 | -4.1 | 86396466.90 | 126.82 | 02-FEB-14:20 | 0.00 | -4.1 |
March | 0.139947E+11 | 6934.68 | 31-MAR-24:00 | 5.40 | 5.40 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.40 | 5.40 |
April | 0.187040E+11 | 8314.04 | 23-APR-17:47 | 12.38 | 8.83 | 91605494.03 | 126.83 | 17-APR-09:00 | 12.38 | 8.83 |
May | 0.429328E+10 | 3486.50 | 31-MAY-24:00 | 18.50 | 16.73 | 99236910.37 | 126.85 | 31-MAY-09:00 | 18.50 | 16.73 |
June | 0.930669E+10 | 5313.40 | 30-JUN-24:00 | 20.00 | 19.21 | 98972222.23 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.147036E+11 | 7223.60 | 31-JUL-24:00 | 23.90 | 22.01 | 91892008.57 | 126.85 | 18-JUL-09:09 | 23.90 | 22.01 |
August | 0.198137E+11 | 8032.11 | 10-AUG-18:10 | 24.22 | 20.66 | 0.103659E+09 | 132.28 | 16-AUG-13:00 | 32.20 | 25.36 |
September | 0.430584E+10 | 3375.66 | 30-SEP-24:00 | 12.60 | 11.96 | 91610234.92 | 126.85 | 06-SEP-13:00 | 12.60 | 11.96 |
October | 0.939006E+10 | 5120.46 | 31-OCT-24:00 | 10.60 | 9.48 | 95237219.14 | 126.85 | 06-OCT-09:00 | 10.60 | 9.48 |
November | 0.134897E+11 | 5803.45 | 06-NOV-16:10 | 13.03 | 7.67 | 94301111.31 | 126.84 | 10-NOV-10:00 | 15.60 | 14.59 |
December | 0.188221E+11 | 7737.85 | 17-DEC-16:00 | 10.00 | 4.16 | 91880791.50 | 126.82 | 21-DEC-14:09 | 3.30 | -1.7 |
Annual Sum or Average | 0.136432E+12 | 0.114326E+10 | ||||||||
Minimum of Months | 0.235434E+10 | 1928.64 | 0.00 | -4.1 | 86396466.90 | 126.82 | 0.00 | -4.1 | ||
Maximum of Months | 0.198137E+11 | 8314.04 | 24.22 | 22.01 | 0.103659E+09 | 132.28 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389595E+09 | 1548.41 | 20-JAN-16:40 | 6.13 | 3.40 | 93077368.73 | 126.82 | 18-JAN-14:00 | 6.13 | 3.40 |
February | 0.458331E+10 | 3559.74 | 22-FEB-17:00 | 3.30 | -0.7 | 86396476.34 | 126.82 | 02-FEB-14:20 | 3.30 | -0.7 |
March | 0.116162E+11 | 6030.29 | 31-MAR-23:40 | 5.67 | 5.67 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.67 | 5.67 |
April | 0.167854E+11 | 7636.27 | 09-APR-17:36 | 15.37 | 13.32 | 91605531.83 | 126.83 | 17-APR-09:00 | 13.30 | 12.36 |
May | 0.360422E+10 | 3306.56 | 31-MAY-24:00 | 18.50 | 16.73 | 99235167.06 | 126.84 | 18-MAY-09:09 | 18.50 | 16.73 |
June | 0.869010E+10 | 4999.86 | 30-JUN-24:00 | 20.00 | 19.21 | 98971720.12 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.139888E+11 | 6932.65 | 31-JUL-24:00 | 23.90 | 22.01 | 91891877.87 | 126.85 | 18-JUL-09:00 | 23.90 | 22.01 |
August | 0.188452E+11 | 7687.73 | 10-AUG-18:10 | 24.22 | 20.66 | 0.103537E+09 | 131.66 | 16-AUG-13:00 | 32.20 | 25.36 |
September | 0.371539E+10 | 3070.59 | 30-SEP-23:30 | 13.00 | 12.21 | 91608591.77 | 126.84 | 06-SEP-09:00 | 13.00 | 12.21 |
October | 0.817496E+10 | 4422.19 | 31-OCT-23:50 | 10.78 | 9.69 | 95237002.11 | 126.85 | 06-OCT-09:00 | 10.78 | 9.69 |
November | 0.109076E+11 | 5453.06 | 03-NOV-16:00 | 15.00 | 10.26 | 94301093.63 | 126.84 | 10-NOV-10:00 | 15.60 | 14.59 |
December | 0.152422E+11 | 7049.24 | 21-DEC-16:10 | 2.62 | -2.3 | 91880822.50 | 126.82 | 21-DEC-14:09 | 2.62 | -2.3 |
Annual Sum or Average | 0.116543E+12 | 0.114098E+10 | ||||||||
Minimum of Months | 0.389595E+09 | 1548.41 | 2.62 | -2.3 | 86396476.34 | 126.82 | 2.62 | -2.3 | ||
Maximum of Months | 0.188452E+11 | 7687.73 | 24.22 | 22.01 | 0.103537E+09 | 131.66 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190516E+09 | 1484.89 | 20-JAN-16:40 | 6.13 | 3.40 | 90083597.59 | 128.22 | 24-JAN-10:50 | 10.60 | 10.60 |
February | 0.314862E+10 | 3446.70 | 22-FEB-17:00 | 3.30 | -0.7 | 86395285.77 | 126.82 | 02-FEB-14:20 | 3.30 | -0.7 |
March | 0.102605E+11 | 5648.09 | 29-MAR-17:20 | 5.73 | 4.14 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.73 | 4.14 |
April | 0.158821E+11 | 7736.48 | 09-APR-17:30 | 15.55 | 13.44 | 91605575.58 | 126.83 | 17-APR-09:00 | 13.30 | 12.36 |
May | 0.326800E+10 | 3253.85 | 31-MAY-24:00 | 18.50 | 16.73 | 99235173.00 | 126.85 | 31-MAY-09:00 | 18.50 | 16.73 |
June | 0.867462E+10 | 4924.40 | 30-JUN-24:00 | 20.00 | 19.21 | 98972147.55 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.140880E+11 | 6925.84 | 31-JUL-24:00 | 23.90 | 22.01 | 91892411.60 | 126.85 | 28-JUL-13:00 | 23.90 | 22.01 |
August | 0.188910E+11 | 7808.36 | 13-AUG-18:33 | 26.70 | 20.45 | 0.103425E+09 | 130.48 | 16-AUG-13:00 | 32.20 | 25.36 |
September | 0.349037E+10 | 2774.07 | 30-SEP-23:20 | 13.13 | 12.30 | 91608575.54 | 126.84 | 06-SEP-09:00 | 13.13 | 12.30 |
October | 0.732029E+10 | 3974.45 | 15-OCT-16:32 | 18.67 | 11.89 | 95237075.40 | 126.85 | 06-OCT-09:00 | 18.67 | 11.89 |
November | 0.932085E+10 | 5428.51 | 03-NOV-16:00 | 15.00 | 10.26 | 94301118.33 | 126.84 | 10-NOV-10:00 | 15.60 | 14.59 |
December | 0.133587E+11 | 6864.33 | 08-DEC-16:10 | 5.92 | 1.77 | 91880831.08 | 126.82 | 21-DEC-14:09 | 3.30 | -1.7 |
Annual Sum or Average | 0.107894E+12 | 0.113787E+10 | ||||||||
Minimum of Months | 0.190516E+09 | 1484.89 | 3.30 | -0.7 | 86395285.77 | 126.82 | 3.30 | -1.7 | ||
Maximum of Months | 0.188910E+11 | 7808.36 | 26.70 | 22.01 | 0.103425E+09 | 130.48 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234205E+12 | 90475.08 | 20-JAN-16:55 | 5.60 | 3.19 | 0.206143E+10 | 2745.29 | 19-JAN-14:00 | 5.60 | 3.19 |
February | 0.432461E+12 | 181917.35 | 22-FEB-17:00 | 3.30 | -0.7 | 0.187024E+10 | 2745.44 | 16-FEB-14:00 | 3.30 | -0.7 |
March | 0.726811E+12 | 357695.16 | 31-MAR-24:00 | 5.40 | 5.40 | 0.223481E+10 | 2749.34 | 27-MAR-13:00 | 5.40 | 5.40 |
April | 0.940960E+12 | 366440.34 | 10-APR-16:00 | 20.00 | 11.13 | 0.198377E+10 | 2818.31 | 07-APR-13:09 | 20.00 | 11.13 |
May | 0.238953E+12 | 175592.58 | 31-MAY-24:00 | 18.50 | 16.73 | 0.214808E+10 | 2746.39 | 31-MAY-13:09 | 18.50 | 16.73 |
June | 0.469020E+12 | 267121.56 | 30-JUN-24:00 | 20.00 | 19.21 | 0.214261E+10 | 2748.48 | 08-JUN-13:00 | 20.00 | 19.21 |
July | 0.730978E+12 | 359508.88 | 31-JUL-24:00 | 23.90 | 22.01 | 0.198921E+10 | 2747.56 | 11-JUL-09:09 | 23.90 | 22.01 |
August | 0.973880E+12 | 374672.22 | 20-AUG-15:31 | 26.33 | 16.51 | 0.246592E+10 | 3705.44 | 22-AUG-13:00 | 31.10 | 18.52 |
September | 0.234983E+12 | 176144.43 | 30-SEP-24:00 | 12.60 | 11.96 | 0.198315E+10 | 2746.85 | 14-SEP-09:09 | 12.60 | 11.96 |
October | 0.486902E+12 | 267568.21 | 31-OCT-24:00 | 10.60 | 9.48 | 0.206167E+10 | 2748.60 | 11-OCT-13:09 | 10.60 | 9.48 |
November | 0.706568E+12 | 275516.14 | 06-NOV-17:00 | 11.70 | 7.36 | 0.204134E+10 | 2747.68 | 08-NOV-14:09 | 15.22 | 11.33 |
December | 0.974130E+12 | 366641.11 | 18-DEC-17:00 | 3.30 | 0.83 | 0.198896E+10 | 2745.40 | 12-DEC-14:30 | 3.30 | 0.83 |
Annual Sum or Average | 0.714985E+13 | 0.249712E+11 | ||||||||
Minimum of Months | 0.234205E+12 | 90475.08 | 3.30 | -0.7 | 0.187024E+10 | 2745.29 | 3.30 | -0.7 | ||
Maximum of Months | 0.974130E+12 | 374672.22 | 26.33 | 22.01 | 0.246592E+10 | 3705.44 | 31.10 | 22.01 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32847144.69 | 9318.43 | 27-JAN-05:03 | 0.00 |
February | 35506794.48 | 9571.75 | 23-FEB-06:00 | 3.90 |
March | 78674280.46 | 11411.76 | 13-MAR-03:52 | 0.00 |
April | 63348347.94 | 9745.53 | 06-APR-04:15 | 10.00 |
May | 0.137304E+09 | 9847.04 | 16-MAY-04:17 | 8.90 |
June | 91070837.92 | 9295.70 | 20-JUN-04:57 | 20.60 |
July | 0.281179E+09 | 12380.73 | 15-JUL-16:01 | 27.52 |
August | 0.305880E+09 | 12746.15 | 12-AUG-16:01 | 27.80 |
September | 0.363020E+09 | 9867.35 | 23-SEP-04:17 | 14.23 |
October | 0.488062E+09 | 11263.36 | 09-OCT-10:33 | 12.43 |
November | 0.376534E+09 | 9830.37 | 04-NOV-04:17 | 10.60 |
December | 78042589.29 | 9626.14 | 27-DEC-05:55 | 3.90 |
Annual Sum or Average | 0.233147E+10 | |||
Minimum of Months | 32847144.69 | 9295.70 | 0.00 | |
Maximum of Months | 0.488062E+09 | 12746.15 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124194E+10 | 52440.12 | 02-JAN-04:01 | -11.8 |
February | 0.102283E+09 | 42234.32 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 146976.91 | 979.85 | 27-NOV-06:03 | 6.78 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.134437E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.124194E+10 | 52440.12 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.519007E+10 | 73887.17 | 01-JAN-00:42 | -5.4 |
February | 0.350220E+10 | 73090.50 | 06-FEB-04:01 | -13.3 |
March | 0.712573E+09 | 66154.58 | 20-MAR-04:01 | -0.8 |
April | 0.125847E+09 | 62842.35 | 03-APR-04:11 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.133841E+10 | 68300.52 | 24-NOV-04:11 | -3.5 |
December | 0.196574E+10 | 69521.99 | 26-DEC-05:11 | 5.77 |
Annual Sum or Average | 0.128348E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.519007E+10 | 73887.17 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344210E+09 | 12270.22 | 02-JAN-05:01 | -12.1 |
February | 0.237717E+09 | 12347.12 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 611278.81 | 7131.59 | 22-NOV-06:01 | -2.2 |
December | 25458.05 | 297.01 | 02-DEC-06:01 | 1.10 |
Annual Sum or Average | 0.582564E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.344210E+09 | 12347.12 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240561E+09 | 11634.18 | 02-JAN-05:01 | -12.1 |
February | 0.145738E+09 | 11761.28 | 06-FEB-05:01 | -13.2 |
March | 2061798.89 | 8873.72 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 3051500.14 | 8916.95 | 22-NOV-06:01 | -2.2 |
December | 5255874.60 | 8897.86 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.396669E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.240561E+09 | 11761.28 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484671E+09 | 17480.04 | 02-JAN-04:01 | -11.8 |
February | 0.268660E+09 | 17181.81 | 06-FEB-04:01 | -13.3 |
March | 10663498.20 | 13626.73 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 13065397.19 | 13612.87 | 22-NOV-06:01 | -2.2 |
December | 20366324.10 | 13707.67 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.797426E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.484671E+09 | 17480.04 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34067420.06 | 9969.74 | 02-JAN-05:01 | -12.1 |
February | 16191145.94 | 9716.43 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 50258565.99 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 34067420.06 | 9969.74 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493442E+10 | 14328.38 | 01-JAN-00:42 | -5.4 |
February | 0.379463E+10 | 14341.59 | 06-FEB-00:22 | -13.3 |
March | 0.833560E+09 | 12334.15 | 13-MAR-03:02 | 0.50 |
April | 0.125121E+09 | 11640.24 | 03-APR-04:11 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 9839249.35 | 10575.08 | 28-OCT-05:03 | 3.90 |
November | 0.907627E+09 | 13043.53 | 24-NOV-04:01 | -3.4 |
December | 0.225708E+10 | 14015.67 | 31-DEC-21:42 | -7.1 |
Annual Sum or Average | 0.128623E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.493442E+10 | 14341.59 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266345E+10 | 19349.98 | 01-JAN-00:42 | -5.4 |
February | 0.173447E+10 | 19328.06 | 05-FEB-23:42 | -13.1 |
March | 0.391678E+09 | 16498.32 | 17-MAR-04:01 | -1.6 |
April | 65370646.05 | 15573.83 | 03-APR-04:11 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 3598242.26 | 6570.46 | 28-OCT-05:03 | 3.90 |
November | 0.446609E+09 | 17479.53 | 24-NOV-04:01 | -3.4 |
December | 0.117351E+10 | 18670.57 | 31-DEC-23:42 | -8.2 |
Annual Sum or Average | 0.647868E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.266345E+10 | 19349.98 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295541E+10 | 21024.89 | 01-JAN-00:42 | -5.4 |
February | 0.173701E+10 | 20674.17 | 06-FEB-01:42 | -13.3 |
March | 0.446233E+09 | 17895.59 | 17-MAR-04:01 | -1.6 |
April | 88334878.69 | 16803.72 | 22-APR-04:11 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 262901.51 | 1752.68 | 28-OCT-05:03 | 3.90 |
November | 0.412028E+09 | 17808.38 | 27-NOV-05:11 | 6.30 |
December | 0.120376E+10 | 18465.44 | 11-DEC-04:51 | 1.70 |
Annual Sum or Average | 0.684304E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.295541E+10 | 21024.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225003E+10 | 19483.89 | 01-JAN-00:42 | -5.4 |
February | 0.149687E+10 | 19448.87 | 06-FEB-01:42 | -13.3 |
March | 0.246089E+09 | 16314.81 | 13-MAR-04:01 | -0.1 |
April | 29953758.18 | 10685.99 | 22-APR-05:02 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 753670.22 | 2884.71 | 28-OCT-05:03 | 3.90 |
November | 0.335385E+09 | 16365.90 | 20-NOV-05:01 | 0.50 |
December | 0.819173E+09 | 16452.19 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.517825E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.225003E+10 | 19483.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854797E+10 | 16746.36 | 01-JAN-00:42 | -5.4 |
February | 0.744955E+10 | 16473.09 | 06-FEB-01:21 | -13.3 |
March | 0.259207E+10 | 15507.98 | 13-MAR-03:11 | 0.40 |
April | 0.740905E+09 | 15200.16 | 03-APR-04:11 | 2.80 |
May | 22142363.21 | 12137.96 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.235077E+09 | 13362.25 | 28-OCT-04:12 | 4.23 |
November | 0.290181E+10 | 15908.44 | 24-NOV-00:12 | -3.3 |
December | 0.586532E+10 | 16801.62 | 31-DEC-22:42 | -7.7 |
Annual Sum or Average | 0.283548E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.854797E+10 | 16801.62 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484638E+10 | 20325.87 | 01-JAN-00:42 | -5.4 |
February | 0.377441E+10 | 20109.02 | 06-FEB-04:01 | -13.3 |
March | 0.123708E+10 | 18917.08 | 13-MAR-03:11 | 0.40 |
April | 0.390989E+09 | 18393.10 | 03-APR-04:11 | 2.80 |
May | 10493425.67 | 9147.98 | 01-MAY-04:12 | 6.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.108837E+09 | 15969.73 | 28-OCT-04:12 | 4.23 |
November | 0.148158E+10 | 19083.45 | 23-NOV-23:33 | -3.1 |
December | 0.317040E+10 | 20406.32 | 31-DEC-22:42 | -7.7 |
Annual Sum or Average | 0.150202E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.484638E+10 | 20406.32 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564290E+10 | 23453.81 | 01-JAN-00:42 | -5.4 |
February | 0.424050E+10 | 23140.48 | 06-FEB-04:01 | -13.3 |
March | 0.159389E+10 | 21799.32 | 13-MAR-03:11 | 0.40 |
April | 0.580741E+09 | 20848.17 | 03-APR-04:11 | 2.80 |
May | 24365264.82 | 14654.08 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 83991385.34 | 17995.61 | 28-OCT-04:12 | 4.23 |
November | 0.159926E+10 | 21862.68 | 24-NOV-04:11 | -3.5 |
December | 0.355089E+10 | 23427.33 | 31-DEC-22:42 | -7.7 |
Annual Sum or Average | 0.173165E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.564290E+10 | 23453.81 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417709E+10 | 22040.33 | 01-JAN-00:42 | -5.4 |
February | 0.319496E+10 | 21701.95 | 06-FEB-04:01 | -13.3 |
March | 0.876829E+09 | 20274.82 | 13-MAR-03:11 | 0.40 |
April | 0.232978E+09 | 18571.25 | 03-APR-04:11 | 2.80 |
May | 3363882.23 | 8483.58 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 56745507.89 | 12310.91 | 28-OCT-04:12 | 4.23 |
November | 0.114569E+10 | 20494.85 | 24-NOV-04:11 | -3.5 |
December | 0.230037E+10 | 21743.69 | 31-DEC-22:42 | -7.7 |
Annual Sum or Average | 0.119880E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.417709E+10 | 22040.33 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143420E+10 | 9595.73 | 18-JAN-06:03 | 7.38 |
February | 0.943985E+09 | 9266.70 | 02-FEB-06:02 | 4.32 |
March | 0.122662E+09 | 10828.61 | 13-MAR-04:01 | -0.1 |
April | 0.177331E+09 | 10907.26 | 17-APR-04:11 | 12.43 |
May | 82846920.01 | 8409.64 | 01-MAY-04:12 | 6.50 |
June | 81721049.30 | 8362.79 | 12-JUN-04:12 | 18.70 |
July | 0.111243E+09 | 10659.02 | 30-JUL-14:31 | 26.13 |
August | 71294650.26 | 11411.87 | 13-AUG-14:21 | 31.15 |
September | 77396140.27 | 8937.38 | 10-SEP-15:31 | 23.67 |
October | 0.112768E+09 | 8691.61 | 10-OCT-04:12 | 10.40 |
November | 0.100911E+09 | 10796.64 | 27-NOV-05:11 | 6.30 |
December | 0.172373E+09 | 11844.77 | 26-DEC-05:11 | 5.77 |
Annual Sum or Average | 0.348873E+10 | |||
Minimum of Months | 71294650.26 | 8362.79 | -0.1 | |
Maximum of Months | 0.143420E+10 | 11844.77 | 31.15 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463105E+10 | 18233.04 | 02-JAN-06:23 | -11.7 |
February | 0.290913E+10 | 9416.09 | 06-FEB-06:12 | -13.0 |
March | 0.171586E+10 | 6113.79 | 26-MAR-12:27 | 13.05 |
April | 0.545792E+09 | 8152.14 | 23-APR-16:12 | 13.30 |
May | 71124028.78 | 9462.97 | 28-MAY-14:21 | 26.15 |
June | 49026922.71 | 8176.48 | 18-JUN-15:51 | 25.60 |
July | 77487826.26 | 10040.06 | 02-JUL-15:41 | 25.00 |
August | 49105562.45 | 9720.92 | 13-AUG-14:32 | 30.97 |
September | 64547217.32 | 9647.09 | 10-SEP-14:21 | 24.40 |
October | 0.109124E+09 | 8806.64 | 15-OCT-15:01 | 20.40 |
November | 0.117539E+10 | 5734.19 | 10-NOV-06:03 | 14.60 |
December | 0.213923E+10 | 9448.05 | 03-DEC-12:53 | 8.30 |
Annual Sum or Average | 0.135369E+11 | |||
Minimum of Months | 49026922.71 | 5734.19 | -13.0 | |
Maximum of Months | 0.463105E+10 | 18233.04 | 30.97 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.995343E+10 | 27481.05 | 02-JAN-05:33 | -11.9 |
February | 0.822939E+10 | 29208.95 | 06-FEB-05:07 | -13.2 |
March | 0.369577E+10 | 19742.75 | 20-MAR-05:13 | -1.3 |
April | 0.162535E+10 | 14443.00 | 03-APR-05:02 | 2.70 |
May | 0.363766E+09 | 12530.73 | 11-MAY-05:02 | 10.78 |
June | 68500419.10 | 12111.57 | 03-JUN-05:03 | 13.48 |
July | 38944586.95 | 9992.19 | 03-JUL-04:12 | 22.60 |
August | 49636809.59 | 10513.02 | 08-AUG-05:03 | 15.37 |
September | 0.233680E+09 | 12637.55 | 29-SEP-05:03 | 11.78 |
October | 0.968688E+09 | 10184.54 | 05-OCT-05:03 | 15.60 |
November | 0.422716E+10 | 21779.11 | 24-NOV-05:13 | -4.1 |
December | 0.722248E+10 | 20962.35 | 11-DEC-06:12 | 1.70 |
Annual Sum or Average | 0.366768E+11 | |||
Minimum of Months | 38944586.95 | 9992.19 | -13.2 | |
Maximum of Months | 0.995343E+10 | 29208.95 | 22.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1724799.70 | 444.55 | 01-JAN-23:16 | -10.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 1724799.70 | |||
Minimum of Months | 0.00 | 0.00 | -10.2 | |
Maximum of Months | 1724799.70 | 444.55 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491893E+09 | 544.90 | 16-JAN-18:20 | 3.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.491893E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.491893E+09 | 544.90 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.743983E+09 | 579.79 | 16-JAN-17:40 | 4.07 |
February | 60987761.18 | 524.73 | 05-FEB-23:42 | -13.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 855192.22 | 417.72 | 01-MAY-04:16 | 6.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.805826E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.743983E+09 | 579.79 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.968216E+10 | 10174.14 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.878253E+10 | 10174.14 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.104353E+11 | 10174.14 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.932187E+10 | 10174.14 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.100587E+11 | 10174.14 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.100099E+11 | 10174.14 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.937071E+10 | 10174.14 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.104353E+11 | 10174.14 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.932187E+10 | 10174.14 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.968216E+10 | 10174.14 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.956821E+10 | 10174.14 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.937071E+10 | 10174.14 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.116039E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.878253E+10 | 10174.14 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.104353E+11 | 10174.14 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869526E+10 | 9137.09 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.788732E+10 | 9137.09 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.937162E+10 | 9137.09 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.837170E+10 | 9137.09 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.903344E+10 | 9137.09 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.898958E+10 | 9137.09 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.841555E+10 | 9137.09 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.937162E+10 | 9137.09 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.837170E+10 | 9137.09 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.869526E+10 | 9137.09 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.859292E+10 | 9137.09 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.841555E+10 | 9137.09 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.104212E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.788732E+10 | 9137.09 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.937162E+10 | 9137.09 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.718471E+09 | 1147.25 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.604189E+09 | 1034.33 | 15-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.674284E+09 | 807.19 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.576599E+09 | 603.91 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.607969E+09 | 603.16 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595309E+09 | 588.24 | 29-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.561877E+09 | 583.74 | 24-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633830E+09 | 614.36 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587828E+09 | 640.19 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.636255E+09 | 895.25 | 31-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.689708E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.708849E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.759517E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.561877E+09 | 583.74 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.718471E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457675E+09 | 739.33 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.386781E+09 | 674.54 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.433597E+09 | 587.08 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.372067E+09 | 377.92 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.394018E+09 | 389.37 | 19-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.386192E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.364157E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.409703E+09 | 378.16 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.378484E+09 | 398.70 | 26-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.408462E+09 | 582.73 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.442381E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.448631E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.488215E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.364157E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.457675E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.694641E+09 | 1147.28 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.590323E+09 | 1027.23 | 15-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.668852E+09 | 730.41 | 02-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.577363E+09 | 600.21 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.610469E+09 | 604.61 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.598701E+09 | 593.59 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.564852E+09 | 589.61 | 24-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.635799E+09 | 614.34 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.586308E+09 | 635.71 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.628825E+09 | 858.81 | 31-OCT-15:00 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.674510E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.678444E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.750909E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.564852E+09 | 589.61 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.694641E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451714E+09 | 739.33 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.382425E+09 | 656.63 | 15-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.430201E+09 | 514.25 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.371435E+09 | 402.31 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.390817E+09 | 397.37 | 08-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.383538E+09 | 390.75 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.362326E+09 | 390.29 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407910E+09 | 403.57 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377783E+09 | 488.59 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.406328E+09 | 559.69 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.436103E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.443162E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.484374E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.362326E+09 | 390.29 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.451714E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.716582E+09 | 1147.25 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.602743E+09 | 1033.14 | 15-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.673278E+09 | 802.47 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.576119E+09 | 598.12 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.607646E+09 | 597.32 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595062E+09 | 581.56 | 29-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.561510E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633591E+09 | 609.17 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587232E+09 | 636.47 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.635440E+09 | 892.45 | 31-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.688367E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.706426E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.758400E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.561510E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.716582E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456518E+09 | 739.33 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.386141E+09 | 672.87 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.433068E+09 | 582.93 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.371825E+09 | 373.65 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.393756E+09 | 385.74 | 19-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.385974E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.363947E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.409549E+09 | 374.57 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.378111E+09 | 395.77 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.408116E+09 | 578.70 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.441761E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.447616E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.487638E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.363947E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.456518E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693741E+09 | 1147.28 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.589742E+09 | 1026.03 | 15-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.667920E+09 | 637.90 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.576957E+09 | 594.24 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.610107E+09 | 598.83 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.598397E+09 | 587.16 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.564493E+09 | 582.97 | 24-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.635548E+09 | 609.14 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585866E+09 | 631.78 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.628378E+09 | 855.98 | 31-OCT-15:00 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.674085E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.677838E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.750307E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.564493E+09 | 582.97 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.693741E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.450753E+09 | 739.33 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381804E+09 | 654.67 | 15-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429794E+09 | 508.36 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.371088E+09 | 399.37 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.390583E+09 | 394.19 | 08-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.383360E+09 | 387.20 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.362103E+09 | 386.70 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407736E+09 | 400.74 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377416E+09 | 482.01 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.406081E+09 | 555.03 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.435630E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.442390E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.483874E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.362103E+09 | 386.70 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.450753E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.716422E+09 | 1147.25 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.602618E+09 | 1032.91 | 15-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.673252E+09 | 801.91 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.576079E+09 | 597.88 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.607637E+09 | 597.08 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.595052E+09 | 581.28 | 29-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.561500E+09 | 545.86 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.633581E+09 | 608.96 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.587210E+09 | 636.33 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.635399E+09 | 891.93 | 31-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.688324E+09 | 1147.25 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.706297E+09 | 1147.25 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.758337E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.561500E+09 | 545.86 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.716422E+09 | 1147.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456479E+09 | 739.33 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.386119E+09 | 672.75 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.433056E+09 | 582.67 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.371804E+09 | 373.48 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.393748E+09 | 385.59 | 19-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.385961E+09 | 351.77 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.363938E+09 | 351.77 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.409544E+09 | 374.39 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.378100E+09 | 395.63 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.408106E+09 | 578.38 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.441739E+09 | 739.33 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.447584E+09 | 739.33 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.487618E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.363938E+09 | 351.77 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.456479E+09 | 739.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.693698E+09 | 1147.28 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.589718E+09 | 1025.79 | 15-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.667903E+09 | 637.75 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.576934E+09 | 594.00 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.610094E+09 | 598.60 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.598382E+09 | 586.91 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.564470E+09 | 582.70 | 24-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.635515E+09 | 608.93 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.585848E+09 | 631.62 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.628367E+09 | 855.41 | 31-OCT-15:00 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.674065E+09 | 1147.28 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.677811E+09 | 1147.28 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.750281E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.564470E+09 | 582.70 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.693698E+09 | 1147.28 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.450722E+09 | 739.33 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.381786E+09 | 654.51 | 15-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.429783E+09 | 507.91 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.371082E+09 | 399.26 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.390578E+09 | 394.06 | 08-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.383354E+09 | 387.06 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.362075E+09 | 386.56 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.407732E+09 | 400.63 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.377400E+09 | 481.50 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.406071E+09 | 554.65 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.435614E+09 | 739.33 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.442351E+09 | 739.33 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.483855E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.362075E+09 | 386.56 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.450722E+09 | 739.33 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.139824E+09 | 146.32 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.126830E+09 | 146.32 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.150710E+09 | 146.32 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.134615E+09 | 146.32 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.145267E+09 | 146.32 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.144564E+09 | 146.32 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.135317E+09 | 146.32 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.150710E+09 | 146.32 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.134615E+09 | 146.32 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.139824E+09 | 146.32 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.138185E+09 | 146.32 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.135317E+09 | 146.32 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.167578E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.126830E+09 | 146.32 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.150710E+09 | 146.32 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274130E+10 | 2868.67 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.248656E+10 | 2868.67 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.295472E+10 | 2868.67 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.263917E+10 | 2868.67 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.284801E+10 | 2868.67 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.283424E+10 | 2868.67 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.265294E+10 | 2868.67 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.295472E+10 | 2868.67 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.263917E+10 | 2868.67 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.274130E+10 | 2868.67 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.270917E+10 | 2868.67 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.265294E+10 | 2868.67 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.328542E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.248656E+10 | 2868.67 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.295472E+10 | 2868.67 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.100587E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.100099E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.932187E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.968216E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.956821E+10 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.937071E+10 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.116039E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.878253E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.104353E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.869526E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.837170E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.903344E+10 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.898958E+10 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.841555E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.837170E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.869526E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.859292E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.841555E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.104212E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.788732E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.937162E+10 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.718471E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147209E+10 |
February | 0.136985E+10 | 0.604189E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129267E+10 |
March | 0.163685E+10 | 0.674284E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108526E+10 |
April | 0.145243E+10 | 0.576599E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 504814.48 | 0.728932E+09 |
May | 0.157338E+10 | 0.607969E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2048474.96 | 0.409958E+09 |
June | 0.156900E+10 | 0.595309E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16280279.22 | 0.204262E+09 |
July | 0.145680E+10 | 0.561877E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40296036.95 | 57805873.95 |
August | 0.163685E+10 | 0.633830E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49710764.82 | 76278259.45 |
September | 0.145243E+10 | 0.587828E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5780374.91 | 0.223610E+09 |
October | 0.150991E+10 | 0.636255E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95389.26 | 0.568366E+09 |
November | 0.149516E+10 | 0.689708E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109177E+10 |
December | 0.145680E+10 | 0.708849E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130636E+10 |
Annual Sum or Average | 0.181194E+11 | 0.759517E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114716E+09 | 0.851736E+10 |
Minimum of Months | 0.136985E+10 | 0.561877E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57805873.95 |
Maximum of Months | 0.163685E+10 | 0.718471E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49710764.82 | 0.147209E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.457675E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980273E+09 |
February | 0.882782E+09 | 0.386781E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868938E+09 |
March | 0.105485E+10 | 0.433597E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717682E+09 |
April | 0.936002E+09 | 0.372067E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336900.72 | 0.482554E+09 |
May | 0.101394E+10 | 0.394018E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1238855.27 | 0.276155E+09 |
June | 0.101113E+10 | 0.386192E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10718263.55 | 0.134280E+09 |
July | 0.938820E+09 | 0.364157E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27003048.36 | 35989723.67 |
August | 0.105485E+10 | 0.409703E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33966159.48 | 48528519.23 |
September | 0.936002E+09 | 0.378484E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3848874.49 | 0.152771E+09 |
October | 0.973041E+09 | 0.408462E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63576.30 | 0.381866E+09 |
November | 0.963541E+09 | 0.442381E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721030E+09 |
December | 0.938820E+09 | 0.448631E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856425E+09 |
Annual Sum or Average | 0.116768E+11 | 0.488215E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77175678.16 | 0.565649E+10 |
Minimum of Months | 0.882782E+09 | 0.364157E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35989723.67 |
Maximum of Months | 0.105485E+10 | 0.457675E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33966159.48 | 0.980273E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.694641E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146436E+10 |
February | 0.136988E+10 | 0.590323E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132120E+10 |
March | 0.163688E+10 | 0.668852E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108422E+10 |
April | 0.145246E+10 | 0.577363E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503187.50 | 0.725578E+09 |
May | 0.157341E+10 | 0.610469E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1833271.04 | 0.409252E+09 |
June | 0.156904E+10 | 0.598701E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15861662.52 | 0.204888E+09 |
July | 0.145684E+10 | 0.564852E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38924889.38 | 60870926.45 |
August | 0.163688E+10 | 0.635799E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47767351.79 | 82495104.55 |
September | 0.145246E+10 | 0.586308E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5669532.70 | 0.236536E+09 |
October | 0.150994E+10 | 0.628825E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52697.40 | 0.596810E+09 |
November | 0.149520E+10 | 0.674510E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108909E+10 |
December | 0.145684E+10 | 0.678444E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129931E+10 |
Annual Sum or Average | 0.181198E+11 | 0.750909E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110613E+09 | 0.857462E+10 |
Minimum of Months | 0.136988E+10 | 0.564852E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60870926.45 |
Maximum of Months | 0.163688E+10 | 0.694641E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47767351.79 | 0.146436E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.451714E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103690E+10 |
February | 0.882782E+09 | 0.382425E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928082E+09 |
March | 0.105485E+10 | 0.430201E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798572E+09 |
April | 0.936002E+09 | 0.371435E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 334520.64 | 0.553520E+09 |
May | 0.101394E+10 | 0.390817E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1253756.35 | 0.300819E+09 |
June | 0.101113E+10 | 0.383538E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10109897.38 | 0.166563E+09 |
July | 0.938820E+09 | 0.362326E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23492214.93 | 64534580.27 |
August | 0.105485E+10 | 0.407910E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28834865.35 | 78597838.72 |
September | 0.936002E+09 | 0.377783E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3790539.77 | 0.172847E+09 |
October | 0.973041E+09 | 0.406328E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63608.60 | 0.425877E+09 |
November | 0.963541E+09 | 0.436103E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803503E+09 |
December | 0.938820E+09 | 0.443162E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973743E+09 |
Annual Sum or Average | 0.116768E+11 | 0.484374E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67879403.00 | 0.630355E+10 |
Minimum of Months | 0.882782E+09 | 0.362326E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64534580.27 |
Maximum of Months | 0.105485E+10 | 0.451714E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28834865.35 | 0.103690E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.716582E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299736E+10 |
February | 0.136985E+10 | 0.602743E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267638E+10 |
March | 0.163685E+10 | 0.673278E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218104E+10 |
April | 0.145243E+10 | 0.576119E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1103432.72 | 0.146051E+10 |
May | 0.157338E+10 | 0.607646E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5161639.05 | 0.887581E+09 |
June | 0.156900E+10 | 0.595062E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36826464.57 | 0.459333E+09 |
July | 0.145680E+10 | 0.561510E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87371906.95 | 0.159703E+09 |
August | 0.163685E+10 | 0.633591E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107875E+09 | 0.203079E+09 |
September | 0.145243E+10 | 0.587232E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13004559.84 | 0.475762E+09 |
October | 0.150991E+10 | 0.635440E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173065.69 | 0.115974E+10 |
November | 0.149516E+10 | 0.688367E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212305E+10 |
December | 0.145680E+10 | 0.706426E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254921E+10 |
Annual Sum or Average | 0.181194E+11 | 0.758400E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251516E+09 | 0.173327E+11 |
Minimum of Months | 0.136985E+10 | 0.561510E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159703E+09 |
Maximum of Months | 0.163685E+10 | 0.716582E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107875E+09 | 0.299736E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.456518E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200830E+10 |
February | 0.649041E+09 | 0.386141E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182302E+10 |
March | 0.773965E+09 | 0.433068E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150671E+10 |
April | 0.688021E+09 | 0.371825E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 661108.49 | 0.103228E+10 |
May | 0.744847E+09 | 0.393756E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2587910.86 | 0.619941E+09 |
June | 0.742030E+09 | 0.385974E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22606874.64 | 0.320879E+09 |
July | 0.690839E+09 | 0.363947E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54039301.85 | 0.115659E+09 |
August | 0.773965E+09 | 0.409549E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66648027.02 | 0.148061E+09 |
September | 0.688021E+09 | 0.378111E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8057437.52 | 0.345960E+09 |
October | 0.715730E+09 | 0.408116E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63677.70 | 0.826057E+09 |
November | 0.708685E+09 | 0.441761E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146321E+10 |
December | 0.690839E+09 | 0.447616E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172550E+10 |
Annual Sum or Average | 0.858171E+10 | 0.487638E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154664E+09 | 0.119356E+11 |
Minimum of Months | 0.649041E+09 | 0.363947E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115659E+09 |
Maximum of Months | 0.773965E+09 | 0.456518E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66648027.02 | 0.200830E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.693741E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313079E+10 |
February | 0.136988E+10 | 0.589742E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288369E+10 |
March | 0.163688E+10 | 0.667920E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234120E+10 |
April | 0.145246E+10 | 0.576957E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101323.02 | 0.156167E+10 |
May | 0.157341E+10 | 0.610107E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4026945.30 | 0.913704E+09 |
June | 0.156904E+10 | 0.598397E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35526630.73 | 0.469070E+09 |
July | 0.145684E+10 | 0.564493E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84358287.57 | 0.170385E+09 |
August | 0.163688E+10 | 0.635548E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101869E+09 | 0.225334E+09 |
September | 0.145246E+10 | 0.585866E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12476342.68 | 0.537745E+09 |
October | 0.150994E+10 | 0.628378E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80368.12 | 0.133323E+10 |
November | 0.149520E+10 | 0.674085E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231236E+10 |
December | 0.145684E+10 | 0.677838E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274749E+10 |
Annual Sum or Average | 0.181198E+11 | 0.750307E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239439E+09 | 0.186267E+11 |
Minimum of Months | 0.136988E+10 | 0.564493E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170385E+09 |
Maximum of Months | 0.163688E+10 | 0.693741E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101869E+09 | 0.313079E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.450753E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205801E+10 |
February | 0.882782E+09 | 0.381804E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185600E+10 |
March | 0.105485E+10 | 0.429794E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156760E+10 |
April | 0.936002E+09 | 0.371088E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724179.12 | 0.106831E+10 |
May | 0.101394E+10 | 0.390583E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2984333.45 | 0.642198E+09 |
June | 0.101113E+10 | 0.383360E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22968074.62 | 0.348698E+09 |
July | 0.938820E+09 | 0.362103E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53905618.57 | 0.141596E+09 |
August | 0.105485E+10 | 0.407736E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65906673.90 | 0.170202E+09 |
September | 0.936002E+09 | 0.377416E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8523362.97 | 0.358099E+09 |
October | 0.973041E+09 | 0.406081E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115417.70 | 0.858898E+09 |
November | 0.963541E+09 | 0.435630E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148070E+10 |
December | 0.938820E+09 | 0.442390E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177823E+10 |
Annual Sum or Average | 0.116768E+11 | 0.483874E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155128E+09 | 0.123285E+11 |
Minimum of Months | 0.882782E+09 | 0.362103E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141596E+09 |
Maximum of Months | 0.105485E+10 | 0.450753E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65906673.90 | 0.205801E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.716422E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361911E+10 |
February | 0.136985E+10 | 0.602618E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321297E+10 |
March | 0.163685E+10 | 0.673252E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252970E+10 |
April | 0.145243E+10 | 0.576079E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1278396.16 | 0.167342E+10 |
May | 0.157338E+10 | 0.607637E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5465970.51 | 0.105511E+10 |
June | 0.156900E+10 | 0.595052E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42891182.07 | 0.570424E+09 |
July | 0.145680E+10 | 0.561500E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100502E+09 | 0.211881E+09 |
August | 0.163685E+10 | 0.633581E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127094E+09 | 0.256244E+09 |
September | 0.145243E+10 | 0.587210E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15216912.06 | 0.567180E+09 |
October | 0.150991E+10 | 0.635399E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160849.59 | 0.131122E+10 |
November | 0.149516E+10 | 0.688324E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239834E+10 |
December | 0.145680E+10 | 0.706297E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297061E+10 |
Annual Sum or Average | 0.181194E+11 | 0.758337E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292610E+09 | 0.203762E+11 |
Minimum of Months | 0.136985E+10 | 0.561500E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211881E+09 |
Maximum of Months | 0.163685E+10 | 0.716422E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127094E+09 | 0.361911E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.456479E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242659E+10 |
February | 0.882782E+09 | 0.386119E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217470E+10 |
March | 0.105485E+10 | 0.433056E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174113E+10 |
April | 0.936002E+09 | 0.371804E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 850329.63 | 0.119068E+10 |
May | 0.101394E+10 | 0.393748E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3192764.36 | 0.736969E+09 |
June | 0.101113E+10 | 0.385961E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27936466.19 | 0.395365E+09 |
July | 0.938820E+09 | 0.363938E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65240390.86 | 0.150154E+09 |
August | 0.105485E+10 | 0.409544E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81704605.10 | 0.185649E+09 |
September | 0.936002E+09 | 0.378100E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10101948.19 | 0.412709E+09 |
October | 0.973041E+09 | 0.408106E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107168.46 | 0.943824E+09 |
November | 0.963541E+09 | 0.441739E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164571E+10 |
December | 0.938820E+09 | 0.447584E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200200E+10 |
Annual Sum or Average | 0.116768E+11 | 0.487618E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189134E+09 | 0.140055E+11 |
Minimum of Months | 0.882782E+09 | 0.363938E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150154E+09 |
Maximum of Months | 0.105485E+10 | 0.456479E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81704605.10 | 0.242659E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.693698E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373927E+10 |
February | 0.136988E+10 | 0.589718E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341218E+10 |
March | 0.163688E+10 | 0.667903E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271770E+10 |
April | 0.145246E+10 | 0.576934E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1272521.92 | 0.180078E+10 |
May | 0.157341E+10 | 0.610094E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4739989.33 | 0.108772E+10 |
June | 0.156904E+10 | 0.598382E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42029348.05 | 0.580301E+09 |
July | 0.145684E+10 | 0.564470E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98445156.46 | 0.222320E+09 |
August | 0.163688E+10 | 0.635515E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121475E+09 | 0.283099E+09 |
September | 0.145246E+10 | 0.585848E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14917964.18 | 0.643815E+09 |
October | 0.150994E+10 | 0.628367E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70841.86 | 0.155393E+10 |
November | 0.149520E+10 | 0.674065E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260758E+10 |
December | 0.145684E+10 | 0.677811E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317325E+10 |
Annual Sum or Average | 0.181198E+11 | 0.750281E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282950E+09 | 0.218220E+11 |
Minimum of Months | 0.136988E+10 | 0.564470E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222320E+09 |
Maximum of Months | 0.163688E+10 | 0.693698E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121475E+09 | 0.373927E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.450722E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246878E+10 |
February | 0.882782E+09 | 0.381786E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222425E+10 |
March | 0.105485E+10 | 0.429783E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183427E+10 |
April | 0.936002E+09 | 0.371082E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 850331.92 | 0.124505E+10 |
May | 0.101394E+10 | 0.390578E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3394564.74 | 0.769424E+09 |
June | 0.101113E+10 | 0.383354E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27522376.79 | 0.430431E+09 |
July | 0.938820E+09 | 0.362075E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63729835.02 | 0.180173E+09 |
August | 0.105485E+10 | 0.407732E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78968770.92 | 0.212573E+09 |
September | 0.936002E+09 | 0.377400E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10079296.10 | 0.430243E+09 |
October | 0.973041E+09 | 0.406071E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107282.42 | 0.996726E+09 |
November | 0.963541E+09 | 0.435614E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169237E+10 |
December | 0.938820E+09 | 0.442351E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207321E+10 |
Annual Sum or Average | 0.116768E+11 | 0.483855E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184652E+09 | 0.145575E+11 |
Minimum of Months | 0.882782E+09 | 0.362075E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180173E+09 |
Maximum of Months | 0.105485E+10 | 0.450722E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78968770.92 | 0.246878E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.139824E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.126830E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.150710E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.134615E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.145267E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.144564E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.135317E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.150710E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.134615E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.139824E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.138185E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.135317E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.167578E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.126830E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.150710E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.274130E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.248656E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.295472E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.263917E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.284801E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.283424E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.265294E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.295472E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.263917E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.274130E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.270917E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.265294E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.328542E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.248656E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.295472E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319783E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281474E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232073E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662625.37 | 0.155051E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4078849.64 | 0.863621E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27892855.39 | 0.430504E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71055002.22 | 0.131408E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82629048.18 | 0.180169E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8056186.48 | 0.477691E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13153.37 | 0.122797E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234730E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283498E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194388E+09 | 0.183775E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131408E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82629048.18 | 0.319783E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507536E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463863E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384779E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1357374.80 | 0.257568E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8876853.94 | 0.149748E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51103609.06 | 0.752712E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127783E+09 | 0.237177E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146695E+09 | 0.330481E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14136617.49 | 0.826497E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29839.81 | 0.209844E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383402E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454795E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349982E+09 | 0.302622E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237177E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146695E+09 | 0.507536E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536661E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485077E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403963E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295989.56 | 0.272009E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2886069.85 | 0.170098E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39582996.25 | 0.905096E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97011919.44 | 0.325656E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132117E+09 | 0.391193E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11721820.95 | 0.926131E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219368E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382455E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456213E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283616E+09 | 0.318065E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325656E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132117E+09 | 0.536661E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 10174.14 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 10174.14 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 10174.14 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 10174.14 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 10174.14 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 10174.14 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 10174.14 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 10174.14 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 10174.14 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 10174.14 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 10174.14 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 10174.14 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 10174.14 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 9137.09 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 9137.09 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 9137.09 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 9137.09 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 9137.09 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 9137.09 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 9137.09 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 9137.09 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 9137.09 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 9137.09 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 9137.09 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 9137.09 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2472.67 | 31-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 1034.33 | 15-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2469.53 | 05-FEB-07:52 |
March | 2010.79 | 01-MAR-10:09 | 807.19 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1981.35 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 603.91 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 07-APR-13:00 | 1536.52 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 603.16 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.06 | 29-MAY-12:00 | 908.18 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 588.24 | 29-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.16 | 19-JUN-21:02 | 514.59 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 583.74 | 24-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.96 | 09-JUL-13:41 | 226.85 | 02-JUL-18:33 |
August | 2010.79 | 01-AUG-09:09 | 614.36 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.31 | 04-AUG-21:02 | 307.92 | 20-AUG-05:55 |
September | 2010.79 | 01-SEP-09:09 | 640.19 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.01 | 14-SEP-14:00 | 476.07 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 895.25 | 31-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 25-OCT-11:00 | 1332.69 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2053.76 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2664.25 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 583.74 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.85 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 276.31 | 2664.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1647.28 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 674.54 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1776.78 | 05-FEB-08:50 |
March | 1295.83 | 01-MAR-10:09 | 587.08 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1484.96 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 377.92 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 07-APR-13:00 | 999.27 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 389.37 | 19-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.99 | 29-MAY-11:52 | 600.79 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.84 | 19-JUN-21:02 | 339.14 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.64 | 09-JUL-13:51 | 158.76 | 02-JUL-18:33 |
August | 1295.83 | 01-AUG-09:09 | 378.16 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.67 | 04-AUG-21:02 | 206.29 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 398.70 | 26-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 14-SEP-14:00 | 315.69 | 10-SEP-08:10 |
October | 1295.83 | 02-OCT-09:09 | 582.73 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 25-OCT-11:00 | 999.14 | 08-OCT-08:20 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1353.21 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1749.15 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.76 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 184.67 | 1776.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2490.33 | 31-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 1027.23 | 15-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2526.92 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 730.41 | 02-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2165.36 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 600.21 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 07-APR-13:00 | 1525.01 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 604.61 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.48 | 29-MAY-11:52 | 899.24 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 593.59 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.71 | 19-JUN-21:02 | 516.79 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 589.61 | 24-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.31 | 09-JUL-13:50 | 241.38 | 02-JUL-18:33 |
August | 2010.83 | 01-AUG-09:09 | 614.34 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.33 | 04-AUG-21:02 | 310.25 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 635.71 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.90 | 14-SEP-14:00 | 470.34 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 858.81 | 31-OCT-15:00 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 25-OCT-11:00 | 1389.08 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2035.39 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2623.80 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 589.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.38 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 275.33 | 2623.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1726.91 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 656.63 | 15-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1742.79 | 05-FEB-07:52 |
March | 1295.83 | 01-MAR-10:09 | 514.25 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1479.21 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 402.31 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 07-APR-13:00 | 1160.98 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 397.37 | 08-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.99 | 29-MAY-11:52 | 669.83 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 390.75 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.89 | 19-JUN-21:02 | 403.20 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 390.29 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.20 | 09-JUL-13:50 | 242.42 | 02-JUL-17:50 |
August | 1295.83 | 01-AUG-09:09 | 403.57 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.73 | 04-AUG-21:02 | 258.73 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 488.59 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 14-SEP-14:00 | 353.10 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 559.69 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 25-OCT-11:00 | 964.55 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1487.49 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1949.68 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 390.29 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.42 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 177.73 | 1949.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5063.69 | 14-JAN-05:51 |
February | 2010.79 | 01-FEB-10:09 | 1033.14 | 15-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5334.61 | 06-FEB-00:49 |
March | 2010.79 | 01-MAR-10:09 | 802.47 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4082.56 | 21-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 598.12 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.46 | 07-APR-13:00 | 3072.36 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 597.32 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.54 | 29-MAY-12:00 | 1830.90 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 581.56 | 29-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 457.73 | 19-JUN-21:02 | 1119.50 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.02 | 09-JUL-13:54 | 518.72 | 11-JUL-04:57 |
August | 2010.79 | 01-AUG-09:09 | 609.17 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.11 | 04-AUG-21:02 | 739.97 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 636.47 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.63 | 14-SEP-14:00 | 950.44 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 892.45 | 31-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 25-OCT-11:00 | 2559.54 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4001.82 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5347.24 | 31-DEC-21:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.72 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 641.11 | 5347.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 739.33 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3429.80 | 14-JAN-05:51 |
February | 1239.33 | 01-FEB-08:09 | 672.87 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3556.38 | 06-FEB-00:47 |
March | 1239.33 | 01-MAR-08:09 | 582.93 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2857.11 | 12-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 373.65 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.30 | 07-APR-13:00 | 2062.22 | 11-APR-04:00 |
May | 1239.33 | 01-MAY-07:10 | 385.74 | 19-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.34 | 29-MAY-11:53 | 1239.87 | 03-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.45 | 19-JUN-21:02 | 759.17 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.59 | 09-JUL-13:54 | 394.26 | 02-JUL-19:00 |
August | 1239.33 | 01-AUG-07:10 | 374.57 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.65 | 04-AUG-21:02 | 532.91 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 395.77 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.08 | 14-SEP-14:10 | 715.98 | 10-SEP-08:20 |
October | 1239.33 | 02-OCT-07:10 | 578.70 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 25-OCT-11:00 | 2017.60 | 08-OCT-08:30 |
November | 1239.33 | 01-NOV-07:10 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2692.83 | 23-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3564.93 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.26 | |||||
Maximum of Months | 1239.33 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 425.65 | 3564.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5247.53 | 31-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 1026.03 | 15-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5334.61 | 06-FEB-00:44 |
March | 2010.83 | 01-MAR-10:09 | 637.90 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4336.39 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 594.24 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.35 | 07-APR-13:00 | 3165.42 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 598.83 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.23 | 29-MAY-11:58 | 1882.70 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 587.16 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.73 | 19-JUN-21:02 | 1130.17 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 582.97 | 24-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 469.24 | 09-JUL-13:54 | 553.54 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 609.14 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.48 | 04-AUG-21:02 | 766.19 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 631.78 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.44 | 14-SEP-14:00 | 1068.67 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 855.98 | 31-OCT-15:00 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.73 | 25-OCT-11:00 | 2901.52 | 08-OCT-09:40 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4196.74 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5347.25 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 582.97 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.54 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 638.48 | 5347.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3434.69 | 14-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 654.67 | 15-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3556.41 | 06-FEB-00:44 |
March | 1295.83 | 01-MAR-10:09 | 508.36 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2809.21 | 21-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 399.37 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.31 | 07-APR-13:00 | 2160.74 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 394.19 | 08-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.65 | 29-MAY-12:00 | 1312.59 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 387.20 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.13 | 19-JUN-21:02 | 910.82 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 386.70 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.73 | 09-JUL-13:55 | 553.48 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 400.74 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.27 | 04-AUG-21:02 | 550.91 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 482.01 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.41 | 14-SEP-14:00 | 714.48 | 10-SEP-19:55 |
October | 1295.83 | 02-OCT-09:09 | 555.03 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 25-OCT-11:00 | 1820.84 | 17-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2741.32 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3564.88 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 386.70 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.91 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 422.27 | 3564.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1147.25 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6165.58 | 01-JAN-21:00 |
February | 2010.79 | 01-FEB-10:09 | 1032.91 | 15-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6701.40 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 801.91 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5066.46 | 21-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 597.88 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.04 | 07-APR-13:00 | 3490.38 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 597.08 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.71 | 29-MAY-12:10 | 2075.76 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 581.28 | 29-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.29 | 19-JUN-21:02 | 1348.07 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 545.86 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.07 | 09-JUL-13:54 | 737.55 | 02-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 608.96 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 782.13 | 04-AUG-21:02 | 864.15 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 636.33 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.83 | 14-SEP-14:00 | 1102.49 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 891.93 | 31-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 | 25-OCT-11:00 | 2918.28 | 17-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1147.25 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4955.87 | 22-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 1147.25 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6539.52 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.55 | |||||
Maximum of Months | 2010.79 | 1147.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 782.13 | 6701.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4249.13 | 14-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 672.75 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4470.32 | 06-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 582.67 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3384.73 | 21-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 373.48 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.69 | 07-APR-13:00 | 2342.71 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 385.59 | 19-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.54 | 29-MAY-12:04 | 1408.68 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 351.77 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.58 | 19-JUN-21:02 | 913.72 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 351.77 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.55 | 09-JUL-13:54 | 547.90 | 02-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 374.39 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.35 | 04-AUG-21:02 | 622.91 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 395.63 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.55 | 14-SEP-14:00 | 886.36 | 10-SEP-07:50 |
October | 1295.83 | 02-OCT-09:09 | 578.38 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | 25-OCT-11:00 | 2144.76 | 08-OCT-08:30 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3305.59 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4360.54 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.90 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 519.35 | 4470.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1147.28 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6356.24 | 14-JAN-05:51 |
February | 2010.83 | 01-FEB-10:09 | 1025.79 | 15-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6705.57 | 06-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 637.75 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5096.31 | 21-MAR-21:02 |
April | 2010.83 | 03-APR-09:09 | 594.00 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 07-APR-13:00 | 3605.47 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 598.60 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.35 | 29-MAY-12:04 | 2142.58 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 586.91 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.03 | 19-JUN-21:02 | 1362.63 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 582.70 | 24-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 577.47 | 09-JUL-13:54 | 779.60 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 608.93 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.87 | 04-AUG-21:02 | 898.09 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 631.62 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 14-SEP-14:00 | 1241.49 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 855.41 | 31-OCT-15:00 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.06 | 25-OCT-11:00 | 3206.51 | 17-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1147.28 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4977.51 | 22-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 1147.28 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6565.23 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 582.70 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.60 | |||||
Maximum of Months | 2010.83 | 1147.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 778.87 | 6705.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 739.33 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4256.41 | 14-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 654.51 | 15-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4470.45 | 06-FEB-00:58 |
March | 1295.83 | 01-MAR-10:09 | 507.91 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3407.79 | 21-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 399.26 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.69 | 07-APR-13:00 | 2477.39 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 394.06 | 08-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.09 | 29-MAY-12:08 | 1509.62 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 387.06 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.62 | 19-JUN-21:02 | 1141.89 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 386.56 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.70 | 09-JUL-13:55 | 728.23 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 400.63 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.06 | 04-AUG-21:02 | 648.47 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 481.50 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.55 | 14-SEP-14:00 | 881.85 | 10-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 554.65 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 25-OCT-11:00 | 2123.41 | 17-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 739.33 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3312.04 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 739.33 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4377.75 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 386.56 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.47 | |||||
Maximum of Months | 1295.83 | 739.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 515.06 | 4470.45 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 146.32 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 146.32 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 146.32 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 146.32 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 146.32 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 146.32 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 146.32 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 146.32 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 146.32 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 146.32 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 146.32 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 146.32 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 2868.67 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 2868.67 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 2868.67 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 2868.67 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 2868.67 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 2868.67 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 2868.67 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 2868.67 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 2868.67 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 2868.67 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 2868.67 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 2868.67 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 2868.67 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5504.14 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5504.00 | 06-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4110.53 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.06 | 07-APR-13:00 | 3341.61 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.15 | 29-MAY-12:00 | 1969.12 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.02 | 19-JUN-21:02 | 1069.07 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.60 | 09-JUL-13:51 | 457.23 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.01 | 12-AUG-18:53 | 706.73 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.46 | 14-SEP-14:00 | 958.75 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 | 25-OCT-11:00 | 2875.43 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4575.45 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5893.87 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.23 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.01 | 5893.87 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9131.83 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9017.70 | 05-FEB-07:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6760.98 | 21-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.71 | 07-APR-13:00 | 5698.87 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.75 | 29-MAY-12:00 | 3346.08 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.46 | 19-JUN-21:02 | 1883.15 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.57 | 09-JUL-14:00 | 838.55 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.05 | 12-AUG-18:53 | 1260.20 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.85 | 14-SEP-14:00 | 1677.07 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 25-OCT-11:00 | 4885.70 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7577.10 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9240.05 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 838.55 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.05 | 9240.05 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9356.41 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9051.47 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7574.65 | 21-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.41 | 08-APR-10:00 | 5731.00 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.87 | 30-MAY-13:00 | 3419.50 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.03 | 19-JUN-21:02 | 1980.12 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.17 | 07-JUL-22:00 | 1148.47 | 02-JUL-18:23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.58 | 04-AUG-21:02 | 1274.49 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.70 | 14-SEP-14:00 | 1746.91 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4775.46 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7610.73 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9141.57 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.47 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.58 | 9356.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92792.00 | 23-JAN-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96498.27 | 21-FEB-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95766.13 | 06-MAR-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96216.76 | 17-APR-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95813.22 | 01-MAY-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97820.07 | 05-JUN-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85363.44 | 11-JUL-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91704.21 | 08-AUG-04:12 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97437.80 | 25-SEP-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97647.03 | 02-OCT-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 101005.68 | 06-NOV-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 97062.62 | 04-DEC-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 85363.44 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 101005.68 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 73145.86 | 30-JAN-06:02 | 14510.15 | 4836.24 | 68826.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77892.06 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80621.70 | 06-MAR-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81179.76 | 17-APR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88071.92 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87520.15 | 12-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78255.79 | 01-JUL-04:12 | 0.00 | 3045.61 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78954.55 | 07-AUG-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84497.54 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84962.75 | 16-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86878.29 | 13-NOV-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80748.07 | 26-DEC-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 73145.86 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88071.92 | 14510.15 | 5373.60 | 68826.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20865.45 | 31-JAN-13:45 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22391.66 | 02-FEB-08:00 | 3224.48 | 3045.74 | 7647.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49674.49 | 29-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71297.99 | 10-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73654.88 | 19-MAY-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75791.40 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73686.41 | 11-JUL-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80766.48 | 07-AUG-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74885.82 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72843.67 | 13-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66891.60 | 03-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21014.60 | 21-DEC-16:30 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20865.45 | 0.00 | 2149.44 | 7647.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80766.48 | 30632.53 | 18274.19 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15655.88 | 20-JAN-17:00 | 30632.53 | 18274.19 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15757.96 | 17-FEB-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26104.18 | 29-MAR-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67630.53 | 08-APR-05:03 | 6448.95 | 4060.81 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79023.15 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80667.16 | 26-JUN-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 75550.08 | 11-JUL-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80538.33 | 07-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74382.09 | 06-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68748.55 | 06-OCT-05:03 | 4836.72 | 1612.08 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25793.39 | 03-NOV-16:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15355.96 | 20-DEC-17:00 | 15316.26 | 9137.09 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15355.96 | 0.00 | 1612.08 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80667.16 | 30632.53 | 18274.19 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2203.93 | 24-JAN-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.57 |
February | 2626.82 | 20-FEB-13:23 | 404.87 | 121.30 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.78 |
March | 6026.56 | 27-MAR-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
April | 7240.98 | 26-APR-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.12 |
May | 12364.65 | 30-MAY-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.69 |
June | 13153.24 | 12-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.63 |
July | 15970.93 | 30-JUL-14:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
August | 16518.01 | 13-AUG-15:01 | 1012.16 | 303.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 76.74 | 0.00 |
September | 12040.34 | 02-SEP-04:12 | 0.00 | 382.41 | 3355.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.70 |
October | 6829.21 | 04-OCT-13:10 | 4021.58 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | 0.00 |
November | 4651.95 | 03-NOV-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 |
December | 2930.80 | 26-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2203.93 | 0.00 | 121.30 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16518.01 | 4021.58 | 1091.73 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 76.74 | 463.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4310.24 | 19-JAN-09:30 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.68 |
February | 5801.26 | 22-FEB-09:20 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.49 |
March | 11271.95 | 26-MAR-08:23 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.73 |
April | 19286.00 | 23-APR-07:33 | 260.91 | 78.17 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.68 |
May | 21402.19 | 29-MAY-08:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 |
June | 20509.08 | 25-JUN-08:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.28 |
July | 21019.02 | 02-JUL-08:32 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 |
August | 20853.74 | 13-AUG-09:01 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 0.00 |
September | 23379.90 | 04-SEP-08:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 |
October | 11122.34 | 09-OCT-09:03 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6592.93 | 02-NOV-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
December | 4952.32 | 20-DEC-09:30 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4310.24 | 195.68 | 58.63 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23379.90 | 2478.65 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 382.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14699.72 | 17-JAN-13:05 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.87 |
February | 23603.53 | 20-FEB-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.58 |
March | 18066.86 | 01-MAR-13:05 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 |
April | 18777.07 | 16-APR-13:32 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.19 |
May | 22946.04 | 28-MAY-13:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.08 |
June | 23324.51 | 18-JUN-13:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.95 |
July | 24638.54 | 30-JUL-14:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.43 |
August | 26011.98 | 13-AUG-13:41 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 63.97 | 0.00 |
September | 26860.92 | 04-SEP-12:41 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.37 |
October | 24548.07 | 08-OCT-12:02 | 506.09 | 151.63 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.30 |
November | 19093.25 | 02-NOV-12:40 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.82 |
December | 23272.18 | 17-DEC-13:02 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14699.72 | 404.87 | 121.30 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26860.92 | 3846.30 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 63.97 | 778.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6811.10 | 20-JAN-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.18 |
February | 10044.95 | 20-FEB-16:03 | 195.68 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.01 |
March | 17418.39 | 26-MAR-17:42 | 0.00 | 132.06 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.95 |
April | 26420.84 | 09-APR-16:02 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.80 |
May | 24272.99 | 14-MAY-15:52 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.10 |
June | 30139.22 | 18-JUN-15:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 |
July | 28237.64 | 30-JUL-15:11 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.86 |
August | 30384.53 | 13-AUG-15:41 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 |
September | 29146.82 | 10-SEP-15:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.09 |
October | 22245.67 | 15-OCT-15:12 | 326.14 | 97.71 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.32 |
November | 12296.63 | 04-NOV-05:03 | 521.82 | 328.58 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 |
December | 11742.45 | 04-DEC-05:11 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6811.10 | 0.00 | 58.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | |
Maximum of Months | 30384.53 | 1239.33 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1566.14 | 13-JAN-13:10 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.68 |
February | 1700.58 | 17-FEB-13:25 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.04 |
March | 2586.60 | 27-MAR-16:00 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.99 |
April | 5398.96 | 07-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 | 0.00 |
May | 11667.20 | 30-MAY-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.62 |
June | 12102.03 | 22-JUN-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 |
July | 15720.65 | 09-JUL-14:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 119.60 | 0.00 |
August | 14691.50 | 13-AUG-15:51 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 212.22 | 0.00 |
September | 11547.33 | 02-SEP-05:03 | 809.73 | 509.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 |
October | 5685.86 | 05-OCT-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 |
November | 2559.61 | 02-NOV-14:10 | 3846.22 | 1091.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.80 |
December | 1616.24 | 20-DEC-13:30 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1566.14 | 708.51 | 212.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15720.65 | 3846.22 | 1091.73 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 212.22 | 240.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1541.76 | 27-JAN-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.12 |
February | 3609.04 | 22-FEB-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.87 |
March | 9287.62 | 29-MAR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.36 |
April | 12033.07 | 07-APR-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 |
May | 25881.56 | 29-MAY-08:31 | 587.05 | 175.88 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.89 |
June | 23386.80 | 04-JUN-10:02 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.37 |
July | 25464.86 | 02-JUL-07:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.40 |
August | 23408.17 | 20-AUG-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.70 |
September | 25301.86 | 04-SEP-08:51 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.21 |
October | 12372.29 | 15-OCT-10:22 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.96 |
November | 6381.12 | 02-NOV-10:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.18 |
December | 3166.20 | 20-DEC-11:05 | 2478.65 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1541.76 | 326.14 | 97.71 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | |
Maximum of Months | 25881.56 | 2478.65 | 703.55 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18769.20 | 31-JAN-13:45 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.28 |
February | 18384.59 | 20-FEB-13:43 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.81 |
March | 18494.98 | 01-MAR-13:20 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.40 |
April | 17192.69 | 07-APR-12:30 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 52.40 | 0.00 |
May | 24376.69 | 29-MAY-11:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 36.21 | 0.00 |
June | 23322.59 | 18-JUN-13:52 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 |
July | 24764.05 | 09-JUL-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 263.24 | 0.00 |
August | 25404.38 | 20-AUG-12:32 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 |
September | 27490.88 | 04-SEP-11:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.62 |
October | 26730.75 | 15-OCT-12:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.95 |
November | 19610.60 | 02-NOV-13:05 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.67 |
December | 23488.05 | 03-DEC-14:13 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17192.69 | 303.66 | 90.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27490.88 | 4021.67 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 263.24 | 1417.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3654.63 | 31-JAN-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5611.07 | 24-FEB-15:40 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.39 |
March | 10614.32 | 29-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.09 |
April | 24121.34 | 09-APR-16:31 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.64 |
May | 23484.77 | 28-MAY-15:42 | 391.37 | 117.25 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.42 |
June | 27370.34 | 18-JUN-15:51 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.46 |
July | 27365.02 | 02-JUL-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.13 |
August | 25633.15 | 20-AUG-16:31 | 521.82 | 156.34 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.39 |
September | 26682.34 | 10-SEP-16:21 | 587.05 | 175.88 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.24 |
October | 22443.76 | 15-OCT-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.17 |
November | 6956.41 | 03-NOV-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.24 |
December | 3327.53 | 08-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3327.53 | 391.37 | 117.25 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27370.34 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1410.29 | 20-JAN-15:10 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.70 |
February | 1431.97 | 17-FEB-15:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.74 |
March | 2255.94 | 28-MAR-13:50 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.96 |
April | 6184.34 | 07-APR-14:00 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 0.00 |
May | 17421.84 | 29-MAY-14:02 | 607.30 | 181.95 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.31 |
June | 13172.06 | 20-JUN-04:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.69 |
July | 18631.52 | 09-JUL-14:31 | 809.73 | 242.60 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 82.93 | 0.00 |
August | 17544.89 | 13-AUG-15:51 | 708.51 | 212.27 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 234.19 | 0.00 |
September | 12268.29 | 02-SEP-05:03 | 809.73 | 509.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 |
October | 6054.02 | 04-OCT-13:40 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 0.00 |
November | 2388.94 | 02-NOV-13:30 | 2010.79 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.53 |
December | 1406.11 | 20-DEC-13:40 | 1923.11 | 545.86 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1406.11 | 0.00 | 181.95 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18631.52 | 2010.79 | 545.86 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 234.19 | 440.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1254.98 | 19-JAN-10:20 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.04 |
February | 1315.71 | 22-FEB-10:20 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.52 |
March | 6741.17 | 29-MAR-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.35 |
April | 11209.54 | 28-APR-08:50 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.21 |
May | 25860.32 | 29-MAY-08:61 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.97 |
June | 23279.22 | 25-JUN-08:42 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.83 |
July | 25815.62 | 02-JUL-07:41 | 521.82 | 156.34 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.49 |
August | 23068.13 | 13-AUG-09:12 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 0.00 |
September | 23586.61 | 03-SEP-08:22 | 391.37 | 117.25 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.70 |
October | 9446.73 | 05-OCT-09:10 | 2591.66 | 703.55 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 |
November | 3371.60 | 03-NOV-09:30 | 1295.83 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.31 |
December | 1264.06 | 20-DEC-10:00 | 1239.33 | 351.77 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1254.98 | 391.37 | 117.25 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25860.32 | 2591.66 | 703.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 533.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13675.49 | 19-JAN-13:30 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 705.70 |
February | 14345.70 | 22-FEB-13:40 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.34 |
March | 18569.02 | 01-MAR-13:30 | 3846.30 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.41 |
April | 17981.55 | 07-APR-12:40 | 1923.15 | 545.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 66.99 | 0.00 |
May | 27074.85 | 29-MAY-13:22 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.22 |
June | 20010.36 | 25-JUN-11:23 | 404.87 | 121.30 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.40 |
July | 27729.98 | 09-JUL-14:31 | 809.75 | 242.60 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 0.00 |
August | 26679.67 | 13-AUG-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 249.39 | 0.00 |
September | 29171.62 | 03-SEP-11:41 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.47 |
October | 28657.86 | 15-OCT-12:21 | 708.53 | 212.28 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1443.18 |
November | 20209.78 | 02-NOV-13:05 | 4021.67 | 1091.75 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.80 |
December | 19475.76 | 17-DEC-13:12 | 607.31 | 181.95 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13675.49 | 404.87 | 121.30 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29171.62 | 4021.67 | 1091.75 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 249.39 | 1443.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3133.89 | 19-JAN-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.55 |
February | 4912.48 | 24-FEB-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.20 |
March | 10418.65 | 29-MAR-16:00 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.49 |
April | 26882.53 | 09-APR-16:21 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.46 |
May | 25906.66 | 28-MAY-15:11 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.84 |
June | 26499.27 | 18-JUN-16:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.97 |
July | 29355.59 | 02-JUL-16:21 | 652.28 | 195.42 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.68 |
August | 25974.27 | 13-AUG-15:51 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 0.00 |
September | 26551.91 | 03-SEP-15:01 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.09 |
October | 21640.87 | 15-OCT-15:41 | 456.59 | 136.80 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.04 |
November | 6591.84 | 03-NOV-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 |
December | 2602.39 | 08-DEC-15:30 | 1239.33 | 351.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2602.39 | 456.59 | 136.80 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29355.59 | 1239.33 | 351.77 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 750.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5709.77 | 31-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 763.57 |
February | 6977.41 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.54 |
March | 3476.28 | 28-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.26 |
April | 7465.06 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.38 |
May | 12092.49 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.00 |
June | 9934.29 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 |
July | 11757.93 | 10-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 0.00 |
August | 11671.82 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 |
September | 12558.89 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.46 |
October | 7595.74 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.38 |
November | 5567.17 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.74 |
December | 2761.34 | 18-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2761.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12558.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 4486.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8937.38 | 14-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7472.16 |
February | 8373.62 | 05-FEB-23:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8665.47 |
March | 8152.69 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3993.66 |
April | 5789.97 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.54 |
May | 6980.61 | 30-MAY-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.94 | 0.00 |
June | 6980.70 | 20-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.47 | 0.00 |
July | 8746.50 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 |
August | 8095.58 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.77 |
September | 7956.18 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.79 |
October | 4400.17 | 05-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.64 |
November | 7665.28 | 20-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1844.07 |
December | 7470.74 | 02-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5311.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8937.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.94 | 8665.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6725.65 |
February | 462.43 | 18-FEB-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.03 |
March | 5734.29 | 03-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.67 |
April | 13225.78 | 07-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
May | 20887.10 | 30-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.71 | 0.00 |
June | 20805.30 | 19-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.13 | 0.00 |
July | 19767.85 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.70 | 0.00 |
August | 19806.88 | 30-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 | 0.00 |
September | 18479.44 | 01-SEP-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.08 | 0.00 |
October | 11620.34 | 04-OCT-13:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 |
November | 3540.92 | 03-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.75 |
December | 1081.59 | 17-DEC-13:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20887.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.70 | 6725.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1928.64 | 20-JAN-16:30 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4022.03 | 14-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6934.68 | 31-MAR-24:00 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8314.04 | 23-APR-17:47 | 0.00 | 24.39 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3486.50 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5313.40 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7223.60 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8032.11 | 10-AUG-18:10 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3375.66 | 30-SEP-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5120.46 | 31-OCT-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5803.45 | 06-NOV-16:10 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7737.85 | 17-DEC-16:00 | 23.38 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1928.64 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8314.04 | 222.14 | 146.32 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1548.41 | 20-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3559.74 | 22-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6030.29 | 31-MAR-23:40 | 0.00 | 8.13 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7636.27 | 09-APR-17:36 | 0.00 | 40.65 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3306.56 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4999.86 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6932.65 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7687.73 | 10-AUG-18:10 | 23.38 | 48.77 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3070.59 | 30-SEP-23:30 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4422.19 | 31-OCT-23:50 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5453.06 | 03-NOV-16:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7049.24 | 21-DEC-16:10 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1548.41 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7687.73 | 222.14 | 146.32 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1484.89 | 20-JAN-16:40 | 222.14 | 146.32 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3446.70 | 22-FEB-17:00 | 222.14 | 146.32 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5648.09 | 29-MAR-17:20 | 23.38 | 48.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7736.48 | 09-APR-17:30 | 0.00 | 48.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3253.85 | 31-MAY-24:00 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4924.40 | 30-JUN-24:00 | 0.00 | 8.13 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6925.84 | 31-JUL-24:00 | 0.00 | 16.26 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7808.36 | 13-AUG-18:33 | 0.00 | 32.52 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2774.07 | 30-SEP-23:20 | 0.00 | 8.13 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3974.45 | 15-OCT-16:32 | 58.46 | 40.65 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5428.51 | 03-NOV-16:00 | 222.14 | 146.32 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6864.33 | 08-DEC-16:10 | 222.14 | 146.32 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1484.89 | 0.00 | 8.13 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7808.36 | 222.14 | 146.32 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90475.08 | 20-JAN-16:55 | 9617.36 | 5737.34 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181917.35 | 22-FEB-17:00 | 4808.68 | 2868.67 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357695.16 | 31-MAR-24:00 | 0.00 | 159.37 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366440.34 | 10-APR-16:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175592.58 | 31-MAY-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267121.56 | 30-JUN-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359508.88 | 31-JUL-24:00 | 0.00 | 318.73 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 374672.22 | 20-AUG-15:31 | 2277.80 | 1434.29 | 3416692.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176144.43 | 30-SEP-24:00 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267568.21 | 31-OCT-24:00 | 0.00 | 159.37 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275516.14 | 06-NOV-17:00 | 4808.68 | 2868.67 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366641.11 | 18-DEC-17:00 | 4808.68 | 2868.67 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90475.08 | 0.00 | 159.37 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 374672.22 | 9617.36 | 5737.34 | 3416692.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.133480E+13 | 853810.11 | 19-JAN-16:00 | 0.344996E+12 | 1631163.45 | 02-JAN-05:10 |
February | 0.161213E+13 | 966730.84 | 02-FEB-08:00 | 0.249721E+12 | 1330215.08 | 13-FEB-07:10 |
March | 0.212296E+13 | 1178692.26 | 27-MAR-15:00 | 0.127512E+12 | 713399.82 | 13-MAR-04:10 |
April | 0.236773E+13 | 1524762.12 | 07-APR-15:09 | 0.788660E+11 | 441308.21 | 03-APR-04:19 |
May | 0.143255E+13 | 1268859.89 | 30-MAY-14:30 | 0.653992E+11 | 203643.50 | 30-MAY-11:30 |
June | 0.204514E+13 | 1424230.69 | 22-JUN-13:30 | 0.616108E+11 | 171122.64 | 01-JUN-14:39 |
July | 0.264208E+13 | 1566499.66 | 11-JUL-15:09 | 0.575034E+11 | 122057.58 | 11-JUL-15:50 |
August | 0.306843E+13 | 1809875.36 | 22-AUG-14:50 | 0.613544E+11 | 193470.63 | 24-AUG-17:10 |
September | 0.151386E+13 | 1203322.97 | 01-SEP-14:00 | 0.569547E+11 | 116408.59 | 01-SEP-16:40 |
October | 0.180188E+13 | 1283822.09 | 04-OCT-15:50 | 0.633975E+11 | 271493.11 | 28-OCT-06:10 |
November | 0.203164E+13 | 1214677.42 | 02-NOV-15:09 | 0.121306E+12 | 808138.11 | 24-NOV-07:10 |
December | 0.246693E+13 | 1256380.69 | 21-DEC-16:30 | 0.196595E+12 | 706704.23 | 22-DEC-07:10 |
Annual Sum or Average | 0.244401E+14 | 0.148522E+13 | ||||
Minimum of Months | 0.133480E+13 | 853810.11 | 0.569547E+11 | 116408.59 | ||
Maximum of Months | 0.306843E+13 | 1809875.36 | 0.344996E+12 | 1631163.45 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.166977E+11 | 50558.75 | 31-JAN-11:50 | 0.00 | 0.00 |
February | 0.242189E+11 | 59827.92 | 22-FEB-11:30 | 0.00 | 0.00 |
March | 0.377002E+11 | 78039.49 | 29-MAR-11:00 | 0.00 | 0.00 |
April | 0.434918E+11 | 83049.85 | 12-APR-11:00 | 0.00 | 0.00 |
May | 0.545554E+11 | 84444.02 | 11-MAY-11:00 | 0.00 | 0.00 |
June | 0.562411E+11 | 87214.16 | 02-JUN-11:50 | 0.00 | 0.00 |
July | 0.554138E+11 | 82701.55 | 02-JUL-11:00 | 0.00 | 0.00 |
August | 0.567860E+11 | 77936.84 | 10-AUG-11:30 | 0.00 | 0.00 |
September | 0.391282E+11 | 72835.72 | 10-SEP-11:30 | 0.00 | 0.00 |
October | 0.352911E+11 | 63020.77 | 08-OCT-11:30 | 0.00 | 0.00 |
November | 0.198609E+11 | 49815.93 | 02-NOV-11:30 | 0.00 | 0.00 |
December | 0.147946E+11 | 40859.46 | 02-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.454180E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.147946E+11 | 40859.46 | 0.00 | 0.00 | |
Maximum of Months | 0.567860E+11 | 87214.16 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.146260E+12 | 0.309644E+11 | 0.766053E+12 | 0.102195E+12 | 0.153388E+12 | 0.113456E+11 | 0.00 | 0.616672E+10 | 0.775485E+09 | 0.112065E+12 | 0.558249E+10 | 0.00 | 0.00 |
February | 0.130967E+12 | 0.247047E+11 | 0.978954E+12 | 0.923111E+11 | 0.138956E+12 | 0.118655E+11 | 0.00 | 0.197077E+11 | 0.230961E+10 | 0.207150E+12 | 0.520480E+10 | 0.00 | 0.00 |
March | 0.154109E+12 | 0.228844E+11 | 0.141687E+13 | 0.102362E+12 | 0.158136E+12 | 0.180475E+11 | 0.00 | 0.428310E+11 | 0.780214E+10 | 0.195408E+12 | 0.450581E+10 | 0.00 | 0.00 |
April | 0.136790E+12 | 0.180143E+11 | 0.165903E+13 | 0.988819E+11 | 0.162694E+12 | 0.206549E+11 | 0.00 | 0.101066E+12 | 0.348414E+11 | 0.133538E+12 | 0.222616E+10 | 0.00 | 0.00 |
May | 0.147077E+12 | 0.159828E+11 | 0.774844E+12 | 0.102278E+12 | 0.187037E+12 | 0.335613E+11 | 0.00 | 0.816442E+11 | 0.434537E+11 | 0.462534E+11 | 0.414853E+09 | 0.00 | 0.00 |
June | 0.146008E+12 | 0.143201E+11 | 0.106252E+13 | 0.990390E+11 | 0.212695E+12 | 0.522366E+11 | 0.00 | 0.304961E+12 | 0.133625E+12 | 0.160917E+11 | 0.364536E+10 | 0.00 | 0.00 |
July | 0.136860E+12 | 0.151248E+11 | 0.139340E+13 | 0.102120E+12 | 0.230745E+12 | 0.678483E+11 | 0.00 | 0.517615E+12 | 0.172798E+12 | 0.00 | 0.556802E+10 | 0.00 | 0.00 |
August | 0.152696E+12 | 0.171731E+11 | 0.173200E+13 | 0.102362E+12 | 0.243745E+12 | 0.696364E+11 | 0.00 | 0.576049E+12 | 0.161073E+12 | 0.930348E+10 | 0.439464E+10 | 0.00 | 0.00 |
September | 0.137182E+12 | 0.202329E+11 | 0.740713E+12 | 0.988811E+11 | 0.190335E+12 | 0.435790E+11 | 0.00 | 0.167106E+12 | 0.985724E+11 | 0.150561E+11 | 0.220286E+10 | 0.00 | 0.00 |
October | 0.143382E+12 | 0.254990E+11 | 0.108340E+13 | 0.102194E+12 | 0.177959E+12 | 0.310552E+11 | 0.00 | 0.100269E+12 | 0.449268E+11 | 0.920392E+11 | 0.115716E+10 | 0.00 | 0.00 |
November | 0.143932E+12 | 0.287784E+11 | 0.135889E+13 | 0.989462E+11 | 0.150242E+12 | 0.166656E+11 | 0.00 | 0.418620E+11 | 0.937044E+10 | 0.179594E+12 | 0.335288E+10 | 0.00 | 0.00 |
December | 0.141930E+12 | 0.319530E+11 | 0.170972E+13 | 0.102121E+12 | 0.151666E+12 | 0.153557E+11 | 0.00 | 0.473915E+11 | 0.650422E+10 | 0.254873E+12 | 0.541417E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171719E+13 | 0.265632E+12 | 0.146764E+14 | 0.120369E+13 | 0.215760E+13 | 0.391852E+12 | 0.00 | 0.200667E+13 | 0.716052E+12 | 0.126137E+13 | 0.436692E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130967E+12 | 0.143201E+11 | 0.740713E+12 | 0.923111E+11 | 0.138956E+12 | 0.113456E+11 | 0.00 | 0.616672E+10 | 0.775485E+09 | 0.00 | 0.414853E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154109E+12 | 0.319530E+11 | 0.173200E+13 | 0.102362E+12 | 0.243745E+12 | 0.696364E+11 | 0.00 | 0.576049E+12 | 0.172798E+12 | 0.254873E+12 | 0.558249E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.275751E+12 | 0.00 | 0.692450E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.186467E+12 | 0.00 | 0.632544E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.556059E+11 | 0.00 | 0.719064E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.147830E+11 | 0.00 | 0.640830E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.901009E+09 | 0.00 | 0.644982E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.131961E+10 | 0.00 | 0.602912E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.555592E+09 | 0.00 | 0.569478E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.150476E+10 | 0.00 | 0.598497E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.286006E+09 | 0.00 | 0.566686E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.240384E+10 | 0.00 | 0.609937E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.586485E+11 | 0.00 | 0.626576E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.130535E+12 | 0.00 | 0.660603E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.728761E+12 | 0.00 | 0.756456E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.286006E+09 | 0.00 | 0.566686E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.275751E+12 | 0.00 | 0.719064E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 169722.15 | 02-JAN-16:40 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73697.12 | 03-JAN-08:20 | 99204.12 | 02-JAN-06:19 | 23072.35 | 31-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 165021.06 | 15-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73690.94 | 28-FEB-08:20 | 86652.32 | 06-FEB-05:10 | 23390.02 | 09-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 153037.31 | 02-MAR-16:00 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73691.35 | 16-MAR-07:19 | 118148.31 | 29-MAR-15:09 | 23198.71 | 27-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 147723.13 | 21-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73689.10 | 21-APR-07:19 | 180676.52 | 07-APR-15:09 | 26038.14 | 07-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 147763.35 | 08-MAY-07:10 | 22480.63 | 01-MAY-18:49 | 423497.50 | 01-MAY-07:10 | 73689.12 | 08-MAY-07:19 | 266478.46 | 30-MAY-14:30 | 48421.42 | 30-MAY-14:09 | 0.00 | 01-MAY-00:10 |
June | 147352.07 | 29-JUN-07:10 | 22480.63 | 01-JUN-19:19 | 541788.89 | 01-JUN-07:10 | 73688.90 | 29-JUN-07:19 | 258089.87 | 01-JUN-14:39 | 48435.43 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 146899.19 | 24-JUL-07:10 | 22480.63 | 01-JUL-19:30 | 660080.29 | 03-JUL-07:10 | 73688.67 | 24-JUL-07:19 | 247259.18 | 11-JUL-15:09 | 46336.10 | 17-JUL-07:19 | 0.00 | 01-JUL-00:10 |
August | 148383.33 | 16-AUG-07:10 | 31088.59 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73689.44 | 16-AUG-07:19 | 266963.99 | 22-AUG-14:50 | 53728.82 | 30-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 150212.06 | 27-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73690.40 | 27-SEP-07:19 | 203679.86 | 01-SEP-15:30 | 50300.31 | 01-SEP-12:09 | 0.00 | 01-SEP-00:10 |
October | 158804.52 | 31-OCT-15:00 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73694.19 | 06-OCT-07:19 | 167041.05 | 05-OCT-15:50 | 47530.48 | 24-OCT-11:50 | 0.00 | 01-OCT-00:10 |
November | 169722.15 | 06-NOV-16:49 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73695.12 | 30-NOV-08:20 | 116678.64 | 03-NOV-14:39 | 23334.99 | 03-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 169722.15 | 01-DEC-16:30 | 31088.59 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 73695.38 | 11-DEC-08:20 | 85306.03 | 21-DEC-14:30 | 23102.39 | 27-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 146899.19 | 22480.63 | 423497.50 | 73688.67 | 85306.03 | 23072.35 | 0.00 | |||||||
Maximum of Months | 169722.15 | 31088.59 | 778371.69 | 73697.12 | 266963.99 | 53728.82 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 9128.00 | 19-JAN-15:09 | 2503.25 | 12-JAN-15:39 | 73617.84 | 20-JAN-05:00 | 4520.72 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 18626.23 | 24-FEB-15:50 | 2884.26 | 01-FEB-12:30 | 100000.00 | 02-FEB-06:10 | 4520.72 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 150843.23 | 27-MAR-15:00 | 45962.17 | 27-MAR-15:00 | 100000.00 | 01-MAR-07:10 | 4520.72 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 285611.64 | 07-APR-14:20 | 61675.77 | 07-APR-12:39 | 100000.00 | 01-APR-04:49 | 4520.72 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 290417.00 | 30-MAY-14:09 | 79575.29 | 30-MAY-14:09 | 100000.00 | 20-MAY-16:19 | 4520.72 | 01-MAY-20:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 336468.67 | 22-JUN-13:30 | 79575.29 | 01-JUN-09:00 | 100000.00 | 04-JUN-06:30 | 4520.72 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 371963.41 | 13-JUL-12:09 | 79575.29 | 11-JUL-15:39 | 0.00 | 01-JUL-00:10 | 4520.72 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 423492.26 | 24-AUG-16:00 | 79575.29 | 04-AUG-05:10 | 100000.00 | 20-AUG-13:30 | 4520.72 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 284726.98 | 01-SEP-14:00 | 79575.29 | 01-SEP-07:10 | 100000.00 | 10-SEP-15:00 | 4520.72 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 285796.05 | 04-OCT-13:39 | 79575.29 | 03-OCT-10:30 | 100000.00 | 07-OCT-16:19 | 4520.72 | 03-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 107186.64 | 03-NOV-15:09 | 44072.40 | 04-NOV-12:39 | 100000.00 | 01-NOV-21:10 | 4520.72 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26911.80 | 20-DEC-10:30 | 5940.72 | 17-DEC-14:00 | 100000.00 | 01-DEC-05:19 | 4520.72 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 9128.00 | 2503.25 | 0.00 | 4520.72 | 0.00 | 0.00 | |||||
Maximum of Months | 423492.26 | 79575.29 | 100000.00 | 4520.72 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 853810.11 | 19-JAN-16:00 | 169722.15 | 423497.50 | 31088.59 | 52601.12 | 68054.84 | 22927.57 | 0.00 | 7267.33 | 1123.55 |
February | 966730.84 | 02-FEB-08:00 | 145987.23 | 541788.89 | 0.00 | 73688.19 | 67444.26 | 22936.60 | 0.00 | 9220.44 | 1144.51 |
March | 1178692.26 | 27-MAR-15:00 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 100031.03 | 23198.71 | 0.00 | 150843.23 | 45962.17 |
April | 1524762.12 | 07-APR-15:09 | 145987.23 | 778371.69 | 0.00 | 52589.61 | 180676.52 | 24791.84 | 0.00 | 280669.48 | 61675.77 |
May | 1268859.89 | 30-MAY-14:30 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 266478.46 | 46872.57 | 0.00 | 278976.91 | 79575.29 |
June | 1424230.69 | 22-JUN-13:30 | 145987.23 | 541788.89 | 0.00 | 24458.17 | 246220.46 | 46718.21 | 0.00 | 336468.67 | 79575.29 |
July | 1566499.66 | 11-JUL-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 247259.18 | 45741.10 | 0.00 | 334513.53 | 79575.29 |
August | 1809875.36 | 22-AUG-14:50 | 145987.23 | 778371.69 | 0.00 | 24458.17 | 266963.99 | 48363.04 | 0.00 | 415081.32 | 79575.29 |
September | 1203322.97 | 01-SEP-14:00 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 193243.82 | 48066.73 | 0.00 | 284726.98 | 79575.29 |
October | 1283822.09 | 04-OCT-15:50 | 145987.23 | 541788.89 | 0.00 | 52589.61 | 150582.70 | 43923.68 | 0.00 | 264853.97 | 79575.29 |
November | 1214677.42 | 02-NOV-15:09 | 145987.23 | 660080.29 | 0.00 | 52589.61 | 109144.90 | 23037.20 | 0.00 | 87980.70 | 35857.51 |
December | 1256380.69 | 21-DEC-16:30 | 169722.15 | 778371.69 | 31088.59 | 52598.55 | 73314.68 | 22927.03 | 0.00 | 21347.53 | 2489.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 853810.11 | 145987.23 | 423497.50 | 0.00 | 24458.17 | 67444.26 | 22927.03 | 0.00 | 7267.33 | 1123.55 | |
Maximum of Months | 1809875.36 | 169722.15 | 778371.69 | 31088.59 | 73688.19 | 266963.99 | 48363.04 | 0.00 | 415081.32 | 79575.29 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1623882.57 | 02-JAN-05:10 | 0.00 | 84071.01 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 1315335.46 | 13-FEB-07:10 | 0.00 | 84093.47 | 13-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 706118.94 | 13-MAR-04:10 | 0.00 | 83809.79 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 434027.33 | 03-APR-04:19 | 0.00 | 82374.94 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 145042.62 | 30-MAY-14:20 | 0.00 | 80244.65 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 136688.29 | 01-JUN-14:39 | 0.00 | 77275.89 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 78689.70 | 12-JUL-12:20 | 0.00 | 74246.16 | 06-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 162773.13 | 24-AUG-17:10 | 0.00 | 73037.39 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 84677.34 | 01-SEP-16:40 | 0.00 | 75393.36 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 242811.45 | 28-OCT-06:10 | 0.00 | 78351.95 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 777462.67 | 24-NOV-07:10 | 0.00 | 81095.74 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 675749.38 | 22-DEC-07:10 | 0.00 | 83022.16 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 78689.70 | 0.00 | 73037.39 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1623882.57 | 0.00 | 84093.47 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.74 | 0.00 | 25.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.79 | 0.00 | 25.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.80 | 0.00 | 25.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.61 | 0.17 | 25.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.30 | 0.50 | 26.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.84 | 0.17 | 26.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.25 | 0.33 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.33 | 0.83 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.25 | 3.50 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.17 | 0.00 | 26.17 |
Annual Sum or Average | 0.00 | 0.00 | 49.00 | 26.90 | 5.50 | 26.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.33 | 3.50 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.70 | 0.00 | 25.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.69 | 0.00 | 25.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.70 | 0.00 | 25.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.34 | 1.67 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 19.34 | 1.67 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.34 | 1.67 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.87 | 1.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 3.17 | 18.81 | 0.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
March | 0.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
December | 0.83 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 10.17 | 18.87 | 2.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.07 | 1.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.42 | 0.17 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
February | 0.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.18 | 1.67 | 27.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.13 | 1.67 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.21 | 0.17 | 19.41 | 3.83 | 25.55 | 3.33 | 26.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.42 | 0.17 | 19.68 | 2.00 | 27.18 | 1.67 | 27.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 0.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.56 | 0.17 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.90 | 2.17 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.91 | 7.67 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.77 | 4.50 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.77 | 10.00 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.71 | 6.00 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.94 | 6.83 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.53 | 1.83 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 18.98 | 0.00 | 18.98 | 39.83 | 27.63 | 39.17 | 27.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.03 | 0.00 | 19.03 | 10.33 | 27.94 | 10.00 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.26 | 0.17 | 19.45 | 0.17 | 20.57 | 0.17 | 21.41 |
February | 0.67 | 19.00 | 0.00 | 19.00 | 1.50 | 24.93 | 1.50 | 26.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.33 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.49 | 2.67 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.67 | 4.33 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.54 | 3.50 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.62 | 8.83 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.78 | 6.17 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.46 | 8.83 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.19 | 10.17 | 27.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.96 | 2.67 | 27.96 |
Annual Sum or Average | 1.50 | 19.14 | 0.17 | 19.27 | 51.50 | 27.27 | 49.50 | 27.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 20.57 | 0.17 | 21.41 |
Maximum of Months | 0.83 | 19.26 | 0.17 | 19.45 | 10.17 | 27.96 | 10.17 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.60 | 0.50 | 27.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.87 | 1.67 | 27.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.77 | 6.17 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.95 | 5.67 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.50 | 8.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 27.55 | 16.33 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.43 | 17.00 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.81 | 5.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.86 | 5.00 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.57 | 1.33 | 27.57 |
Annual Sum or Average | 0.17 | 19.34 | 0.00 | 19.34 | 141.50 | 27.56 | 67.50 | 27.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 0.00 | 19.34 |
Maximum of Months | 0.17 | 19.34 | 0.00 | 19.34 | 51.67 | 27.95 | 17.00 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.67 | 17.19 | 9.17 | 17.30 | 0.00 | 17.30 | 0.00 | 17.30 |
February | 22.67 | 17.51 | 5.33 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
March | 2.33 | 19.15 | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.21 | 1.67 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.83 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 18.94 | 0.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
December | 7.33 | 18.21 | 0.33 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
Annual Sum or Average | 64.17 | 17.58 | 15.33 | 17.72 | 2.83 | 18.05 | 2.50 | 18.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.67 | 19.15 | 9.17 | 19.23 | 2.00 | 27.37 | 1.67 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 17.18 | 2.67 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
February | 15.50 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
March | 1.67 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 1.50 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.06 | 7.50 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.81 | 5.67 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.87 | 12.50 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.91 | 6.33 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.00 | 7.17 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.45 | 0.83 | 27.45 |
November | 2.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
December | 10.33 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
Annual Sum or Average | 56.00 | 17.79 | 2.67 | 17.66 | 42.33 | 21.96 | 41.50 | 23.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 0.00 | 16.98 |
Maximum of Months | 26.17 | 19.01 | 2.67 | 19.01 | 13.17 | 28.06 | 12.50 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.17 | 16.68 | 2.17 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
February | 7.50 | 17.67 | 0.00 | 17.67 | 1.33 | 19.15 | 1.33 | 20.24 |
March | 1.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.46 | 4.00 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.53 | 3.33 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.69 | 8.33 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.27 | 7.17 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.67 | 13.50 | 26.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 26.17 | 17.83 | 26.17 |
November | 1.50 | 19.05 | 0.00 | 19.05 | 1.33 | 21.69 | 1.33 | 22.64 |
December | 3.00 | 18.91 | 0.00 | 18.91 | 2.17 | 22.67 | 2.17 | 24.21 |
Annual Sum or Average | 28.17 | 17.39 | 2.17 | 17.34 | 61.50 | 23.73 | 60.00 | 24.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 | 0.00 | 16.68 |
Maximum of Months | 15.17 | 19.05 | 2.17 | 19.05 | 17.83 | 27.69 | 17.83 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 16.20 | 3.00 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
February | 7.67 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
March | 1.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.00 | 1.50 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.85 | 4.50 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.07 | 3.83 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.79 | 8.17 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.71 | 4.67 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.39 | 3.33 | 28.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.76 | 1.17 | 27.76 |
November | 1.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
December | 3.67 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
Annual Sum or Average | 27.83 | 16.96 | 3.00 | 16.77 | 43.67 | 23.29 | 27.17 | 24.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 | 0.00 | 15.99 |
Maximum of Months | 14.33 | 18.97 | 3.00 | 18.97 | 14.50 | 28.39 | 8.17 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.83 | 16.40 | 18.50 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
February | 51.50 | 16.55 | 17.67 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
March | 11.17 | 18.28 | 1.50 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
April | 2.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.83 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.34 | 1.17 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.39 | 5.83 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.60 | 1.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
November | 15.83 | 17.41 | 2.67 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
December | 26.00 | 17.05 | 5.33 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
Annual Sum or Average | 169.83 | 16.80 | 45.67 | 16.91 | 11.17 | 17.43 | 9.33 | 17.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.83 | 19.34 | 18.50 | 19.34 | 7.33 | 27.60 | 5.83 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.83 | 15.40 | 8.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
February | 27.67 | 15.69 | 4.83 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
March | 6.50 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
April | 1.50 | 19.06 | 0.00 | 19.06 | 0.17 | 19.89 | 0.17 | 20.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.02 | 7.83 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.80 | 6.33 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.98 | 12.67 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.02 | 7.00 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.98 | 7.33 | 27.98 |
October | 0.33 | 19.37 | 0.00 | 19.37 | 0.17 | 22.02 | 0.17 | 23.34 |
November | 8.83 | 16.51 | 0.67 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
December | 18.33 | 16.30 | 2.83 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
Annual Sum or Average | 104.00 | 15.96 | 16.33 | 15.82 | 44.67 | 19.11 | 41.50 | 20.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 | 0.00 | 15.31 |
Maximum of Months | 40.83 | 19.37 | 8.00 | 19.37 | 14.67 | 28.02 | 12.67 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.83 | 15.89 | 5.67 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 24.67 | 16.34 | 2.50 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
March | 5.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
April | 1.33 | 19.10 | 0.00 | 19.10 | 0.33 | 20.77 | 0.33 | 21.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.80 | 4.33 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.63 | 4.17 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.79 | 9.33 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.13 | 5.50 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.24 | 9.50 | 27.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.93 | 7.17 | 26.93 |
November | 6.17 | 17.77 | 0.33 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
December | 14.50 | 16.90 | 0.83 | 16.83 | 0.67 | 17.27 | 0.67 | 17.68 |
Annual Sum or Average | 83.50 | 16.54 | 9.33 | 16.46 | 45.00 | 20.09 | 41.00 | 21.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 0.00 | 15.82 |
Maximum of Months | 31.83 | 19.10 | 5.67 | 19.10 | 11.33 | 28.13 | 9.50 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 15.49 | 7.33 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
February | 21.17 | 15.91 | 3.67 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
March | 4.17 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
April | 0.83 | 19.20 | 0.00 | 19.20 | 2.33 | 25.60 | 1.50 | 26.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.03 | 4.50 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.19 | 4.17 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.85 | 9.83 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.68 | 5.00 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.44 | 3.50 | 28.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.86 | 0.83 | 27.86 |
November | 4.50 | 17.36 | 0.17 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
December | 11.17 | 16.94 | 1.67 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
Annual Sum or Average | 72.00 | 16.17 | 12.83 | 15.96 | 47.83 | 20.29 | 29.33 | 21.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | 0.00 | 15.35 |
Maximum of Months | 30.17 | 19.20 | 7.33 | 19.20 | 17.00 | 28.44 | 9.83 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.65 | 5.50 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 27.65 | 5.50 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.65 | 5.50 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.62 | 2.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 27.62 | 2.50 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.62 | 2.50 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.57 | 1.00 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 27.57 | 1.00 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.57 | 1.00 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 309.17 | 28.74 | 272.00 | 28.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 309.17 | 28.74 | 272.00 | 28.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 309.17 | 28.74 | 272.00 | 28.79 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 354.00 | 23.77 | 41.83 | 23.95 | 0.00 | 23.95 |
February | 313.33 | 23.73 | 22.83 | 23.91 | 0.00 | 23.91 |
March | 190.50 | 23.97 | 81.33 | 24.41 | 0.00 | 24.41 |
April | 63.00 | 24.01 | 125.83 | 25.01 | 0.00 | 25.01 |
May | 42.17 | 24.00 | 259.83 | 24.71 | 25.67 | 24.66 |
June | 180.17 | 24.64 | 434.67 | 24.53 | 180.17 | 24.55 |
July | 251.00 | 25.10 | 496.83 | 24.75 | 251.00 | 24.84 |
August | 113.50 | 25.05 | 473.83 | 24.61 | 113.50 | 24.68 |
September | 66.50 | 24.96 | 380.83 | 24.71 | 63.67 | 24.74 |
October | 63.00 | 24.23 | 333.33 | 24.73 | 21.00 | 24.72 |
November | 68.50 | 24.00 | 128.50 | 25.17 | 0.00 | 25.17 |
December | 243.83 | 24.00 | 80.83 | 24.57 | 0.00 | 24.57 |
Annual Sum or Average | 1949.50 | 24.21 | 2860.50 | 24.57 | 655.00 | 24.61 |
Minimum of Months | 42.17 | 23.73 | 22.83 | 23.91 | 0.00 | 23.91 |
Maximum of Months | 354.00 | 25.10 | 496.83 | 25.17 | 251.00 | 25.17 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 406.17 | 23.67 | 19.67 | 23.67 | 12.00 | 23.66 |
February | 343.83 | 23.87 | 2.83 | 23.89 | 0.00 | 23.89 |
March | 157.83 | 23.98 | 71.17 | 24.35 | 0.00 | 24.35 |
April | 49.33 | 23.98 | 141.67 | 24.61 | 0.00 | 24.61 |
May | 13.33 | 23.98 | 242.00 | 24.44 | 0.00 | 24.44 |
June | 0.00 | 0.00 | 434.00 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 497.00 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 476.50 | 24.20 | 0.00 | 24.20 |
September | 7.67 | 23.99 | 376.67 | 24.38 | 0.00 | 24.38 |
October | 49.67 | 24.00 | 307.17 | 24.41 | 0.00 | 24.41 |
November | 97.67 | 23.98 | 106.50 | 24.69 | 0.00 | 24.69 |
December | 203.17 | 23.99 | 44.33 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 1328.67 | 23.86 | 2719.50 | 24.23 | 12.00 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 2.83 | 23.67 | 0.00 | 23.66 |
Maximum of Months | 406.17 | 24.00 | 497.00 | 24.69 | 12.00 | 24.69 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.83 | 91.67 | 21.55 | 91.67 | 21.34 |
February | 454.00 | 22.38 | 32.83 | 22.29 | 32.83 | 22.20 |
March | 474.67 | 23.31 | 4.00 | 23.32 | 0.00 | 23.32 |
April | 291.50 | 23.44 | 26.83 | 23.54 | 0.00 | 23.54 |
May | 103.50 | 23.77 | 184.00 | 24.09 | 0.00 | 24.09 |
June | 4.83 | 23.74 | 416.67 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 494.50 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 457.17 | 24.24 | 0.00 | 24.24 |
September | 30.00 | 23.68 | 329.17 | 24.22 | 0.00 | 24.22 |
October | 148.00 | 23.79 | 222.83 | 24.04 | 0.00 | 24.04 |
November | 372.00 | 23.11 | 24.83 | 23.19 | 0.00 | 23.19 |
December | 497.00 | 22.70 | 6.33 | 22.68 | 6.33 | 22.65 |
Annual Sum or Average | 2877.50 | 22.83 | 2290.83 | 23.36 | 130.83 | 23.28 |
Minimum of Months | 0.00 | 0.00 | 4.00 | 21.55 | 0.00 | 21.34 |
Maximum of Months | 502.00 | 23.79 | 494.50 | 24.24 | 91.67 | 24.24 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.85 | 220.50 | 20.54 | 220.50 | 20.37 |
February | 454.00 | 21.15 | 208.67 | 20.89 | 208.67 | 20.76 |
March | 502.50 | 22.20 | 48.33 | 22.06 | 48.17 | 21.95 |
April | 372.00 | 22.67 | 39.83 | 22.68 | 14.67 | 22.60 |
May | 174.33 | 23.44 | 146.00 | 23.80 | 0.00 | 23.80 |
June | 12.50 | 23.64 | 413.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 495.33 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 455.00 | 24.27 | 0.00 | 24.27 |
September | 74.33 | 23.34 | 309.33 | 24.05 | 0.00 | 24.05 |
October | 272.33 | 22.94 | 157.17 | 23.30 | 7.17 | 23.27 |
November | 473.17 | 21.99 | 82.67 | 21.74 | 81.83 | 21.55 |
December | 497.00 | 21.16 | 170.50 | 20.87 | 170.50 | 20.70 |
Annual Sum or Average | 3334.17 | 21.88 | 2746.33 | 22.44 | 751.50 | 22.18 |
Minimum of Months | 0.00 | 0.00 | 39.83 | 20.54 | 0.00 | 20.37 |
Maximum of Months | 502.50 | 23.64 | 495.33 | 24.29 | 220.50 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.46 | 160.83 | 21.22 | 160.83 | 21.08 |
February | 454.00 | 21.73 | 113.17 | 21.52 | 113.17 | 21.37 |
March | 465.67 | 22.91 | 11.33 | 22.92 | 3.00 | 22.91 |
April | 277.17 | 23.37 | 69.67 | 23.57 | 0.00 | 23.57 |
May | 76.17 | 23.71 | 209.17 | 24.20 | 1.00 | 24.21 |
June | 11.67 | 25.82 | 451.33 | 24.36 | 10.33 | 24.40 |
July | 28.33 | 26.64 | 497.00 | 24.55 | 28.33 | 24.65 |
August | 10.50 | 26.77 | 481.67 | 24.35 | 10.50 | 24.40 |
September | 47.50 | 23.82 | 342.67 | 24.28 | 3.00 | 24.29 |
October | 192.83 | 23.46 | 220.33 | 23.83 | 0.00 | 23.83 |
November | 412.33 | 22.93 | 15.33 | 22.93 | 6.50 | 22.90 |
December | 497.00 | 22.41 | 12.00 | 22.37 | 12.00 | 22.33 |
Annual Sum or Average | 2975.17 | 22.58 | 2584.50 | 23.19 | 348.67 | 23.09 |
Minimum of Months | 10.50 | 21.46 | 11.33 | 21.22 | 0.00 | 21.08 |
Maximum of Months | 502.00 | 26.77 | 497.00 | 24.55 | 160.83 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 21.65 | 131.17 | 21.39 | 131.17 | 21.22 |
February | 438.33 | 22.08 | 85.17 | 21.89 | 81.67 | 21.73 |
March | 397.33 | 22.77 | 36.33 | 22.85 | 7.83 | 22.82 |
April | 252.67 | 23.23 | 122.50 | 23.68 | 8.33 | 23.75 |
May | 88.67 | 24.57 | 291.33 | 24.52 | 24.83 | 24.67 |
June | 26.50 | 26.48 | 470.33 | 24.46 | 24.67 | 24.57 |
July | 50.83 | 26.83 | 497.00 | 24.68 | 50.83 | 24.86 |
August | 25.17 | 26.87 | 487.50 | 24.43 | 24.67 | 24.55 |
September | 62.50 | 25.11 | 383.17 | 24.55 | 28.50 | 24.68 |
October | 151.83 | 23.54 | 256.83 | 24.03 | 6.50 | 24.08 |
November | 372.50 | 22.81 | 26.50 | 22.86 | 8.00 | 22.82 |
December | 482.00 | 22.29 | 20.67 | 22.25 | 18.67 | 22.19 |
Annual Sum or Average | 2845.00 | 22.73 | 2808.50 | 23.39 | 415.67 | 23.38 |
Minimum of Months | 25.17 | 21.65 | 20.67 | 21.39 | 6.50 | 21.22 |
Maximum of Months | 496.67 | 26.87 | 497.00 | 24.68 | 131.17 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 432.00 | 21.56 | 143.33 | 21.37 | 126.00 | 21.17 |
February | 357.50 | 22.06 | 102.67 | 22.02 | 77.83 | 21.83 |
March | 352.67 | 22.74 | 84.17 | 22.91 | 15.50 | 22.85 |
April | 242.67 | 23.15 | 118.83 | 23.62 | 8.17 | 23.69 |
May | 110.17 | 23.88 | 258.17 | 24.26 | 12.33 | 24.35 |
June | 25.50 | 25.93 | 460.50 | 24.42 | 20.17 | 24.51 |
July | 41.67 | 26.85 | 497.00 | 24.64 | 41.67 | 24.80 |
August | 24.00 | 27.03 | 493.50 | 24.49 | 24.00 | 24.60 |
September | 58.00 | 25.31 | 406.17 | 24.58 | 29.50 | 24.72 |
October | 124.50 | 24.12 | 325.33 | 24.40 | 23.50 | 24.53 |
November | 301.50 | 22.74 | 97.17 | 23.05 | 11.50 | 22.99 |
December | 391.00 | 22.31 | 64.33 | 22.44 | 32.67 | 22.40 |
Annual Sum or Average | 2461.17 | 22.73 | 3051.17 | 23.50 | 422.83 | 23.46 |
Minimum of Months | 24.00 | 21.56 | 64.33 | 21.37 | 8.17 | 21.17 |
Maximum of Months | 432.00 | 27.03 | 497.00 | 24.64 | 126.00 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.50 | 22.35 | 64.17 | 22.18 | 60.17 | 22.02 |
February | 382.50 | 23.00 | 31.67 | 23.00 | 17.83 | 22.92 |
March | 164.00 | 23.93 | 127.00 | 24.24 | 5.00 | 24.28 |
April | 44.83 | 25.55 | 273.00 | 24.93 | 22.50 | 25.07 |
May | 32.33 | 26.34 | 380.17 | 24.70 | 25.50 | 24.83 |
June | 50.83 | 26.95 | 481.33 | 24.78 | 50.83 | 24.97 |
July | 103.67 | 26.86 | 497.00 | 25.07 | 103.67 | 25.33 |
August | 98.00 | 26.52 | 514.00 | 24.88 | 98.00 | 25.10 |
September | 27.67 | 27.01 | 424.17 | 24.70 | 27.67 | 24.84 |
October | 64.17 | 24.85 | 338.50 | 24.64 | 18.83 | 24.74 |
November | 162.50 | 23.77 | 120.00 | 24.24 | 1.17 | 24.26 |
December | 295.00 | 23.90 | 37.67 | 24.12 | 1.00 | 24.13 |
Annual Sum or Average | 1884.00 | 23.87 | 3288.67 | 24.30 | 432.17 | 24.41 |
Minimum of Months | 27.67 | 22.35 | 31.67 | 22.18 | 1.00 | 22.02 |
Maximum of Months | 458.50 | 27.01 | 514.00 | 25.07 | 103.67 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.09 | 397.00 | 19.98 | 397.00 | 19.93 |
February | 454.00 | 20.29 | 380.00 | 20.21 | 380.00 | 20.18 |
March | 510.17 | 21.20 | 171.33 | 20.99 | 169.67 | 20.86 |
April | 408.50 | 22.10 | 56.33 | 22.04 | 37.17 | 21.92 |
May | 208.67 | 23.22 | 136.67 | 23.65 | 0.00 | 23.65 |
June | 44.67 | 25.01 | 428.50 | 24.34 | 33.00 | 24.41 |
July | 79.83 | 25.89 | 497.00 | 24.65 | 79.83 | 24.80 |
August | 44.17 | 25.68 | 468.83 | 24.45 | 40.67 | 24.55 |
September | 130.50 | 23.36 | 280.50 | 23.95 | 14.33 | 23.97 |
October | 328.83 | 22.46 | 124.83 | 22.75 | 18.33 | 22.66 |
November | 489.00 | 21.22 | 162.00 | 20.93 | 162.00 | 20.75 |
December | 497.00 | 20.38 | 407.33 | 20.31 | 407.33 | 20.28 |
Annual Sum or Average | 3697.33 | 21.43 | 3510.33 | 21.92 | 1739.33 | 21.67 |
Minimum of Months | 44.17 | 20.09 | 56.33 | 19.98 | 0.00 | 19.93 |
Maximum of Months | 510.17 | 25.89 | 497.00 | 24.65 | 407.33 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.11 | 316.00 | 19.90 | 316.00 | 19.82 |
February | 385.00 | 20.65 | 255.67 | 20.40 | 255.67 | 20.29 |
March | 396.17 | 21.61 | 108.50 | 21.34 | 103.50 | 21.14 |
April | 279.67 | 22.38 | 85.00 | 22.79 | 17.17 | 22.77 |
May | 147.67 | 23.88 | 199.00 | 24.32 | 26.50 | 24.52 |
June | 50.67 | 26.02 | 390.00 | 24.61 | 45.33 | 24.77 |
July | 91.50 | 26.40 | 422.00 | 24.96 | 91.50 | 25.18 |
August | 51.67 | 26.50 | 409.83 | 24.73 | 51.17 | 24.91 |
September | 100.67 | 24.50 | 290.50 | 24.52 | 40.67 | 24.69 |
October | 208.00 | 22.83 | 156.33 | 23.39 | 12.83 | 23.37 |
November | 388.67 | 21.46 | 114.33 | 21.13 | 112.00 | 20.91 |
December | 422.00 | 20.62 | 274.33 | 20.40 | 274.33 | 20.30 |
Annual Sum or Average | 2948.67 | 21.79 | 3021.50 | 22.34 | 1346.67 | 22.14 |
Minimum of Months | 50.67 | 20.11 | 85.00 | 19.90 | 12.83 | 19.82 |
Maximum of Months | 427.00 | 26.50 | 422.00 | 24.96 | 316.00 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 445.83 | 20.66 | 256.67 | 20.39 | 242.83 | 20.20 |
February | 378.00 | 21.29 | 204.50 | 21.10 | 183.17 | 20.89 |
March | 386.00 | 21.78 | 140.33 | 21.84 | 80.67 | 21.65 |
April | 317.33 | 22.35 | 113.83 | 22.73 | 24.33 | 22.66 |
May | 182.83 | 23.38 | 211.83 | 23.93 | 12.67 | 24.03 |
June | 51.33 | 25.06 | 441.83 | 24.39 | 34.17 | 24.48 |
July | 87.17 | 26.13 | 497.00 | 24.74 | 87.17 | 24.92 |
August | 51.67 | 26.39 | 485.83 | 24.62 | 50.50 | 24.77 |
September | 92.00 | 24.63 | 378.00 | 24.49 | 40.33 | 24.64 |
October | 175.33 | 23.61 | 299.83 | 24.16 | 32.67 | 24.30 |
November | 354.67 | 21.83 | 141.17 | 21.92 | 71.33 | 21.68 |
December | 422.00 | 21.32 | 215.67 | 21.16 | 194.17 | 20.97 |
Annual Sum or Average | 2944.17 | 22.11 | 3386.50 | 22.81 | 1054.00 | 22.64 |
Minimum of Months | 51.33 | 20.66 | 113.83 | 20.39 | 12.67 | 20.20 |
Maximum of Months | 445.83 | 26.39 | 497.00 | 24.74 | 242.83 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.67 | 20.49 | 309.33 | 20.24 | 309.33 | 20.13 |
February | 442.17 | 20.85 | 271.17 | 20.59 | 271.17 | 20.48 |
March | 431.00 | 21.79 | 113.83 | 21.76 | 82.33 | 21.60 |
April | 313.17 | 22.54 | 102.83 | 22.90 | 19.33 | 22.89 |
May | 135.00 | 23.84 | 255.33 | 24.23 | 20.33 | 24.36 |
June | 48.33 | 26.12 | 462.83 | 24.58 | 42.67 | 24.72 |
July | 89.67 | 26.52 | 497.00 | 24.89 | 89.67 | 25.10 |
August | 52.33 | 26.67 | 498.67 | 24.69 | 52.33 | 24.86 |
September | 84.50 | 24.26 | 358.83 | 24.36 | 27.33 | 24.47 |
October | 206.17 | 22.90 | 235.33 | 23.59 | 8.17 | 23.59 |
November | 446.83 | 21.56 | 119.83 | 21.30 | 113.67 | 21.10 |
December | 495.50 | 20.92 | 262.00 | 20.69 | 262.00 | 20.58 |
Annual Sum or Average | 3244.33 | 21.87 | 3487.00 | 22.53 | 1298.33 | 22.33 |
Minimum of Months | 48.33 | 20.49 | 102.83 | 20.24 | 8.17 | 20.13 |
Maximum of Months | 499.67 | 26.67 | 498.67 | 24.89 | 309.33 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.86 | 443.83 | 19.79 | 443.83 | 19.77 |
February | 454.00 | 20.00 | 424.00 | 19.96 | 424.00 | 19.95 |
March | 513.17 | 20.77 | 273.83 | 20.53 | 273.83 | 20.41 |
April | 416.17 | 21.55 | 133.50 | 21.37 | 109.83 | 21.16 |
May | 256.50 | 22.87 | 129.00 | 23.36 | 5.67 | 23.39 |
June | 59.67 | 24.67 | 415.67 | 24.31 | 38.33 | 24.39 |
July | 95.17 | 25.91 | 497.00 | 24.70 | 95.17 | 24.87 |
August | 57.67 | 25.36 | 458.33 | 24.46 | 44.67 | 24.58 |
September | 167.67 | 23.00 | 260.17 | 23.74 | 18.17 | 23.76 |
October | 374.17 | 21.85 | 157.17 | 21.90 | 77.33 | 21.65 |
November | 489.00 | 20.58 | 270.67 | 20.30 | 270.67 | 20.17 |
December | 497.00 | 19.96 | 470.67 | 19.93 | 470.67 | 19.92 |
Annual Sum or Average | 3882.17 | 21.11 | 3933.83 | 21.55 | 2272.17 | 21.29 |
Minimum of Months | 57.67 | 19.86 | 129.00 | 19.79 | 5.67 | 19.77 |
Maximum of Months | 513.17 | 25.91 | 497.00 | 24.70 | 470.67 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 403.67 | 19.84 | 403.67 | 19.78 |
February | 454.00 | 20.32 | 356.17 | 20.15 | 356.17 | 20.09 |
March | 479.83 | 21.28 | 175.00 | 20.88 | 175.00 | 20.64 |
April | 332.83 | 21.89 | 158.83 | 22.11 | 75.67 | 21.89 |
May | 194.17 | 23.39 | 238.50 | 24.02 | 28.00 | 24.20 |
June | 60.50 | 25.70 | 460.67 | 24.50 | 52.00 | 24.64 |
July | 99.83 | 26.29 | 497.00 | 24.84 | 99.83 | 25.05 |
August | 57.67 | 26.33 | 487.67 | 24.62 | 54.83 | 24.79 |
September | 140.50 | 23.95 | 337.17 | 24.27 | 44.50 | 24.42 |
October | 269.67 | 22.29 | 191.00 | 22.83 | 31.00 | 22.69 |
November | 476.17 | 20.96 | 207.17 | 20.58 | 206.00 | 20.36 |
December | 497.00 | 20.15 | 398.00 | 20.02 | 398.00 | 19.97 |
Annual Sum or Average | 3564.17 | 21.43 | 3910.83 | 21.99 | 1924.67 | 21.74 |
Minimum of Months | 57.67 | 19.99 | 158.83 | 19.84 | 28.00 | 19.78 |
Maximum of Months | 502.00 | 26.33 | 497.00 | 24.84 | 403.67 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.83 | 20.37 | 301.67 | 20.06 | 295.67 | 19.90 |
February | 395.00 | 20.83 | 262.67 | 20.58 | 249.17 | 20.40 |
March | 401.17 | 21.21 | 208.67 | 21.11 | 160.67 | 20.87 |
April | 333.67 | 21.77 | 158.67 | 21.99 | 79.33 | 21.78 |
May | 225.33 | 22.99 | 201.50 | 23.66 | 17.83 | 23.77 |
June | 68.17 | 24.70 | 428.17 | 24.35 | 41.67 | 24.45 |
July | 97.33 | 26.03 | 497.00 | 24.75 | 97.33 | 24.93 |
August | 58.17 | 26.07 | 481.17 | 24.60 | 51.83 | 24.76 |
September | 120.67 | 23.98 | 352.00 | 24.31 | 41.50 | 24.45 |
October | 204.33 | 22.68 | 286.50 | 23.52 | 39.50 | 23.49 |
November | 392.67 | 21.23 | 190.00 | 21.05 | 148.50 | 20.78 |
December | 439.33 | 20.70 | 293.00 | 20.45 | 280.67 | 20.27 |
Annual Sum or Average | 3195.67 | 21.67 | 3661.00 | 22.30 | 1503.67 | 22.06 |
Minimum of Months | 58.17 | 20.37 | 158.67 | 20.06 | 17.83 | 19.90 |
Maximum of Months | 459.83 | 26.07 | 497.00 | 24.75 | 295.67 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.83 | 20.20 | 358.00 | 19.97 | 358.00 | 19.88 |
February | 444.50 | 20.50 | 320.50 | 20.27 | 320.50 | 20.18 |
March | 440.67 | 21.26 | 192.00 | 21.09 | 165.67 | 20.89 |
April | 339.50 | 22.01 | 141.67 | 22.23 | 63.17 | 22.08 |
May | 181.67 | 23.37 | 235.17 | 23.97 | 22.50 | 24.13 |
June | 59.17 | 25.69 | 457.00 | 24.54 | 48.33 | 24.69 |
July | 99.33 | 26.40 | 497.00 | 24.90 | 99.33 | 25.11 |
August | 56.17 | 26.57 | 495.67 | 24.69 | 55.83 | 24.86 |
September | 116.83 | 23.74 | 331.83 | 24.20 | 30.83 | 24.31 |
October | 257.33 | 22.29 | 228.00 | 22.90 | 40.00 | 22.75 |
November | 464.33 | 20.99 | 199.17 | 20.66 | 197.33 | 20.47 |
December | 497.00 | 20.45 | 369.17 | 20.26 | 369.17 | 20.18 |
Annual Sum or Average | 3456.33 | 21.51 | 3825.17 | 22.12 | 1770.67 | 21.88 |
Minimum of Months | 56.17 | 20.20 | 141.67 | 19.97 | 22.50 | 19.88 |
Maximum of Months | 499.83 | 26.57 | 497.00 | 24.90 | 369.17 | 25.11 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 468.33 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 6.17 | 27.00 | 514.00 | 27.00 | 6.17 | 27.00 |
April | 62.83 | 27.00 | 485.00 | 27.00 | 62.83 | 27.00 |
May | 2.17 | 27.00 | 508.00 | 27.00 | 2.17 | 27.00 |
June | 60.33 | 27.00 | 496.00 | 27.00 | 60.33 | 27.00 |
July | 214.17 | 27.00 | 497.00 | 27.00 | 214.17 | 27.00 |
August | 411.33 | 27.05 | 514.00 | 27.04 | 411.33 | 27.04 |
September | 24.17 | 27.00 | 485.00 | 27.00 | 24.17 | 27.00 |
October | 29.83 | 27.00 | 502.00 | 27.00 | 29.83 | 27.00 |
November | 5.17 | 27.00 | 489.00 | 27.00 | 5.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 816.17 | 27.02 | 5909.33 | 27.01 | 816.17 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 411.33 | 27.05 | 514.00 | 27.04 | 411.33 | 27.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.17 | 25.10 | 271.50 | 26.33 | 12.33 | 26.21 |
February | 0.00 | 0.00 | 264.50 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 497.17 | 27.00 | 0.67 | 27.00 |
April | 3.00 | 27.00 | 485.00 | 27.00 | 3.00 | 27.00 |
May | 1.00 | 27.00 | 508.00 | 27.00 | 1.00 | 27.00 |
June | 5.83 | 27.00 | 496.00 | 27.00 | 5.83 | 27.00 |
July | 30.17 | 27.00 | 497.00 | 27.00 | 30.17 | 27.00 |
August | 90.00 | 27.13 | 514.00 | 27.04 | 90.00 | 27.05 |
September | 8.67 | 27.00 | 485.00 | 27.00 | 8.67 | 27.00 |
October | 5.83 | 27.00 | 502.00 | 27.00 | 5.83 | 27.00 |
November | 0.00 | 0.00 | 446.17 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 438.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 244.33 | 26.28 | 5404.50 | 26.96 | 157.50 | 26.95 |
Minimum of Months | 0.00 | 0.00 | 264.50 | 26.33 | 0.00 | 26.21 |
Maximum of Months | 99.17 | 27.13 | 514.00 | 27.04 | 90.00 | 27.05 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 208.83 | 24.71 | 195.67 | 25.36 | 40.00 | 25.09 |
February | 49.83 | 27.00 | 158.17 | 27.00 | 0.00 | 27.00 |
March | 0.17 | 27.00 | 432.17 | 27.00 | 0.17 | 27.00 |
April | 8.00 | 27.00 | 468.83 | 27.00 | 8.00 | 27.00 |
May | 2.83 | 27.00 | 508.00 | 27.00 | 2.83 | 27.00 |
June | 29.33 | 27.00 | 496.00 | 27.00 | 29.33 | 27.00 |
July | 89.50 | 27.00 | 497.00 | 27.00 | 89.50 | 27.00 |
August | 140.17 | 27.06 | 514.00 | 27.03 | 140.17 | 27.03 |
September | 16.33 | 27.00 | 485.00 | 27.00 | 16.33 | 27.00 |
October | 9.00 | 27.00 | 473.50 | 27.00 | 9.00 | 27.00 |
November | 7.33 | 27.00 | 392.17 | 27.00 | 0.00 | 27.00 |
December | 22.33 | 27.00 | 262.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 583.67 | 26.20 | 4883.33 | 26.88 | 335.33 | 26.86 |
Minimum of Months | 0.17 | 24.71 | 158.17 | 25.36 | 0.00 | 25.09 |
Maximum of Months | 208.83 | 27.06 | 514.00 | 27.03 | 140.17 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.83 | 27.00 | 502.00 | 27.00 | 92.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 501.83 | 27.00 | 508.00 | 27.00 | 501.83 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.01 | 514.00 | 28.01 | 514.00 | 28.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5527.67 | 27.10 | 5943.00 | 27.09 | 5527.67 | 27.09 |
Minimum of Months | 92.83 | 27.00 | 454.00 | 27.00 | 92.83 | 27.00 |
Maximum of Months | 514.00 | 28.01 | 514.00 | 28.01 | 514.00 | 28.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99981 | 20.80641 | 0.69335 | 15.29884 |
February | 454.00000 | 27.00000 | 17.44616 | 0.72687 | 16.23106 |
March | 514.00000 | 27.00003 | 24.55654 | 0.86665 | 20.96070 |
April | 485.00000 | 27.00003 | 29.71344 | 0.96112 | 24.60493 |
May | 508.00000 | 27.00036 | 34.20367 | 0.24557 | 6.33379 |
June | 496.00000 | 27.00135 | 38.01178 | 0.35145 | 7.62964 |
July | 497.00000 | 27.00110 | 39.18449 | 0.41376 | 8.62253 |
August | 514.00000 | 27.03718 | 38.39345 | 0.47252 | 9.77632 |
September | 485.00000 | 27.00055 | 37.56152 | 0.28848 | 6.84099 |
October | 502.00000 | 27.00066 | 31.58432 | 0.93145 | 23.46165 |
November | 489.00000 | 27.00006 | 27.04930 | 0.88172 | 21.53464 |
December | 497.00000 | 26.99999 | 20.19834 | 0.83856 | 19.89197 |
Annual Sum or Average | 5943.00000 | 27.00355 | 29.98066 | 0.63817 | 15.07332 |
Minimum of Months | 454.00000 | 26.99981 | 17.44616 | 0.24557 | 6.33379 |
Maximum of Months | 514.00000 | 27.03718 | 39.18449 | 0.96112 | 24.60493 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.57299 | 20.99019 | 0.46425 | 10.96958 |
February | 454.00000 | 27.00000 | 17.44353 | 0.56335 | 11.80980 |
March | 514.00000 | 27.00003 | 24.54167 | 0.71708 | 16.01822 |
April | 485.00000 | 27.00003 | 29.67880 | 0.82133 | 19.41026 |
May | 508.00000 | 27.00024 | 34.27786 | 0.17361 | 5.76252 |
June | 496.00000 | 27.00131 | 38.05981 | 0.27345 | 6.63361 |
July | 497.00000 | 27.00108 | 39.20723 | 0.32144 | 7.21338 |
August | 514.00000 | 27.02531 | 38.39407 | 0.35281 | 7.70756 |
September | 485.00000 | 27.00039 | 37.69593 | 0.22087 | 6.16987 |
October | 502.00000 | 27.00065 | 31.59419 | 0.84630 | 20.33385 |
November | 489.00000 | 27.00006 | 27.02915 | 0.71804 | 16.10595 |
December | 497.00000 | 26.99999 | 20.18521 | 0.62391 | 13.27655 |
Annual Sum or Average | 5943.00000 | 26.96644 | 30.01322 | 0.50712 | 11.77088 |
Minimum of Months | 454.00000 | 26.57299 | 17.44353 | 0.17361 | 5.76252 |
Maximum of Months | 514.00000 | 27.02531 | 39.20723 | 0.84630 | 20.33385 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.95637 | 21.43446 | 0.30069 | 9.72835 |
February | 454.00000 | 26.99973 | 17.44171 | 0.50163 | 10.50434 |
March | 514.00000 | 27.00004 | 24.55557 | 0.65894 | 14.44470 |
April | 485.00000 | 27.00004 | 29.69522 | 0.77922 | 18.14897 |
May | 508.00000 | 27.00024 | 34.34463 | 0.15701 | 5.80152 |
June | 496.00000 | 27.00135 | 38.06241 | 0.28241 | 6.80861 |
July | 497.00000 | 27.00113 | 39.21337 | 0.34148 | 7.55089 |
August | 514.00000 | 27.01651 | 38.41108 | 0.36457 | 7.94000 |
September | 485.00000 | 27.00039 | 37.72128 | 0.20928 | 6.19045 |
October | 502.00000 | 27.00066 | 31.64009 | 0.80646 | 19.11833 |
November | 489.00000 | 27.00006 | 27.05082 | 0.64718 | 14.14723 |
December | 497.00000 | 27.00000 | 20.19085 | 0.54744 | 11.46002 |
Annual Sum or Average | 5943.00000 | 26.91358 | 30.06926 | 0.46561 | 10.97947 |
Minimum of Months | 454.00000 | 25.95637 | 17.44171 | 0.15701 | 5.80152 |
Maximum of Months | 514.00000 | 27.01651 | 39.21337 | 0.80646 | 19.11833 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99995 | 30.41630 | 1.00111 | 26.19046 |
February | 454.00000 | 27.00020 | 29.34153 | 1.16666 | 33.64087 |
March | 514.00000 | 27.00054 | 27.92221 | 1.32336 | 41.49253 |
April | 485.00000 | 27.00402 | 28.79259 | 1.47433 | 49.51839 |
May | 508.00000 | 27.00000 | 36.42989 | 0.50753 | 10.49360 |
June | 496.00000 | 27.00229 | 39.95414 | 0.78109 | 17.93565 |
July | 497.00000 | 27.00125 | 38.83047 | 0.98411 | 25.46733 |
August | 514.00000 | 28.01325 | 36.85256 | 1.45925 | 48.79515 |
September | 485.00000 | 27.00085 | 40.63870 | 0.60611 | 12.87264 |
October | 502.00000 | 27.00100 | 37.82866 | 1.31158 | 40.95188 |
November | 489.00000 | 27.00027 | 29.46747 | 1.36434 | 43.63446 |
December | 497.00000 | 27.00014 | 23.83470 | 1.43558 | 47.42351 |
Annual Sum or Average | 5943.00000 | 27.08850 | 33.38823 | 1.11811 | 33.22173 |
Minimum of Months | 454.00000 | 26.99995 | 23.83470 | 0.50753 | 10.49360 |
Maximum of Months | 514.00000 | 28.01325 | 40.63870 | 1.47433 | 49.51839 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04765 | 22.48446 | 0.22449 | 6.63796 |
February | 454.00000 | 24.14637 | 18.08625 | 0.22373 | 6.61147 |
March | 514.00000 | 24.31766 | 25.46046 | 0.32825 | 7.61180 |
April | 485.00000 | 24.43377 | 31.51707 | 0.40258 | 8.90458 |
May | 508.00000 | 24.43966 | 40.85560 | -0.3963 | 9.09275 |
June | 496.00000 | 24.42211 | 56.42590 | -0.2738 | 7.51458 |
July | 497.00000 | 24.57066 | 62.47203 | -0.1785 | 7.02489 |
August | 514.00000 | 24.46054 | 56.45819 | -0.2428 | 7.42195 |
September | 485.00000 | 24.52146 | 50.07353 | -0.2776 | 7.89911 |
October | 502.00000 | 24.56876 | 41.00662 | 0.51886 | 11.47565 |
November | 489.00000 | 24.52917 | 27.66160 | 0.40513 | 9.08590 |
December | 497.00000 | 24.47753 | 20.10054 | 0.32994 | 7.74510 |
Annual Sum or Average | 5943.00000 | 24.41252 | 37.87116 | 0.08675 | 8.09386 |
Minimum of Months | 454.00000 | 24.04765 | 18.08625 | -0.3963 | 6.61147 |
Maximum of Months | 514.00000 | 24.57066 | 62.47203 | 0.51886 | 11.47565 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78795 | 27.96619 | 0.18349 | 6.07025 |
February | 454.00000 | 24.04392 | 21.60288 | 0.21381 | 6.16200 |
March | 514.00000 | 24.24868 | 27.55279 | 0.33256 | 7.57040 |
April | 485.00000 | 24.28238 | 32.98664 | 0.39894 | 8.64781 |
May | 508.00000 | 24.25316 | 41.96873 | -0.4232 | 9.20629 |
June | 496.00000 | 24.23559 | 52.70620 | -0.3268 | 7.56212 |
July | 497.00000 | 24.22093 | 56.61628 | -0.2932 | 6.98277 |
August | 514.00000 | 24.18468 | 52.56849 | -0.3189 | 7.32495 |
September | 485.00000 | 24.30916 | 48.67065 | -0.3440 | 8.01088 |
October | 502.00000 | 24.34650 | 40.68457 | 0.47110 | 10.12460 |
November | 489.00000 | 24.38601 | 29.97598 | 0.38321 | 8.52531 |
December | 497.00000 | 24.30218 | 22.96726 | 0.30792 | 7.20282 |
Annual Sum or Average | 5943.00000 | 24.21728 | 38.15080 | 0.04659 | 7.79232 |
Minimum of Months | 454.00000 | 23.78795 | 21.60288 | -0.4232 | 6.07025 |
Maximum of Months | 514.00000 | 24.38601 | 56.61628 | 0.47110 | 10.12460 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.82713 | 29.55264 | -0.3186 | 9.41401 |
February | 454.00000 | 22.38252 | 24.43074 | -0.2059 | 6.75452 |
March | 514.00000 | 23.36718 | 31.16411 | 0.09235 | 5.72250 |
April | 485.00000 | 23.72356 | 35.79611 | 0.23187 | 6.61778 |
May | 508.00000 | 24.06526 | 42.95675 | -0.5136 | 10.90489 |
June | 496.00000 | 24.18043 | 53.44795 | -0.3785 | 8.29790 |
July | 497.00000 | 24.21076 | 57.44759 | -0.3339 | 7.57170 |
August | 514.00000 | 24.21578 | 53.39929 | -0.3558 | 7.98034 |
September | 485.00000 | 24.17319 | 49.45689 | -0.4180 | 9.06950 |
October | 502.00000 | 24.03671 | 42.35216 | 0.37142 | 8.39261 |
November | 489.00000 | 23.38066 | 34.29125 | 0.11677 | 6.41895 |
December | 497.00000 | 22.70151 | 27.74582 | -0.1030 | 5.87939 |
Annual Sum or Average | 5943.00000 | 23.53021 | 40.28989 | -0.1517 | 7.76318 |
Minimum of Months | 454.00000 | 21.82713 | 24.43074 | -0.5136 | 5.72250 |
Maximum of Months | 514.00000 | 24.21578 | 57.44759 | 0.37142 | 10.90489 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.85271 | 31.09285 | -0.5714 | 14.88334 |
February | 454.00000 | 21.14665 | 25.87549 | -0.5254 | 12.70951 |
March | 514.00000 | 22.24238 | 33.40251 | -0.1879 | 7.26025 |
April | 485.00000 | 22.99723 | 37.70733 | 0.05097 | 6.87256 |
May | 508.00000 | 23.88393 | 43.71279 | -0.5778 | 12.85333 |
June | 496.00000 | 24.18133 | 53.43414 | -0.3653 | 8.16604 |
July | 497.00000 | 24.29033 | 57.04930 | -0.2891 | 7.12759 |
August | 514.00000 | 24.23843 | 53.23299 | -0.3324 | 7.71144 |
September | 485.00000 | 24.03858 | 49.98474 | -0.4636 | 10.23969 |
October | 502.00000 | 23.41974 | 44.05136 | 0.21469 | 7.71862 |
November | 489.00000 | 22.05450 | 37.11643 | -0.2179 | 8.34395 |
December | 497.00000 | 21.15836 | 30.16268 | -0.4933 | 11.90182 |
Annual Sum or Average | 5943.00000 | 22.88886 | 41.51689 | -0.3122 | 9.62962 |
Minimum of Months | 454.00000 | 20.85271 | 25.87549 | -0.5778 | 6.87256 |
Maximum of Months | 514.00000 | 24.29033 | 57.04930 | 0.21469 | 14.88334 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.45513 | 27.41161 | -0.3966 | 9.83564 |
February | 454.00000 | 21.72964 | 21.96385 | -0.3576 | 8.94916 |
March | 514.00000 | 23.01961 | 28.57243 | 0.01198 | 6.08222 |
April | 485.00000 | 23.70345 | 33.21681 | 0.23444 | 6.96040 |
May | 508.00000 | 24.12957 | 41.24688 | -0.4652 | 10.34170 |
June | 496.00000 | 24.29932 | 51.96064 | -0.2652 | 7.09475 |
July | 497.00000 | 24.42568 | 55.73319 | -0.1676 | 6.54566 |
August | 514.00000 | 24.28233 | 51.59815 | -0.2447 | 6.93091 |
September | 485.00000 | 24.21505 | 48.37344 | -0.3776 | 8.79079 |
October | 502.00000 | 23.86856 | 40.61928 | 0.33092 | 8.22588 |
November | 489.00000 | 23.11458 | 31.12477 | 0.04948 | 6.35678 |
December | 497.00000 | 22.40607 | 24.39175 | -0.1721 | 6.44181 |
Annual Sum or Average | 5943.00000 | 23.39898 | 38.14068 | -0.1509 | 7.70548 |
Minimum of Months | 454.00000 | 21.45513 | 21.96385 | -0.4652 | 6.08222 |
Maximum of Months | 514.00000 | 24.42568 | 55.73319 | 0.33092 | 10.34170 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.67278 | 27.22891 | -0.3413 | 9.31861 |
February | 454.00000 | 22.16889 | 21.57798 | -0.2478 | 8.16579 |
March | 514.00000 | 23.07568 | 28.12313 | 0.05026 | 6.58805 |
April | 485.00000 | 23.71046 | 32.92222 | 0.27054 | 8.23603 |
May | 508.00000 | 24.24257 | 40.77896 | -0.3578 | 9.80159 |
June | 496.00000 | 24.33497 | 51.68394 | -0.2044 | 7.09342 |
July | 497.00000 | 24.45781 | 55.40812 | -0.1063 | 6.95735 |
August | 514.00000 | 24.29028 | 51.27375 | -0.1691 | 6.81844 |
September | 485.00000 | 24.33697 | 47.72874 | -0.2759 | 8.50638 |
October | 502.00000 | 24.00517 | 39.98343 | 0.39869 | 9.62478 |
November | 489.00000 | 23.13267 | 30.96033 | 0.06615 | 6.67655 |
December | 497.00000 | 22.35663 | 24.45315 | -0.1782 | 6.97334 |
Annual Sum or Average | 5943.00000 | 23.49119 | 37.79982 | -0.0908 | 7.89396 |
Minimum of Months | 454.00000 | 21.67278 | 21.57798 | -0.3578 | 6.58805 |
Maximum of Months | 514.00000 | 24.45781 | 55.40812 | 0.39869 | 9.80159 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.93416 | 26.49102 | -0.2627 | 9.97712 |
February | 454.00000 | 22.56926 | 20.57404 | -0.1276 | 8.78707 |
March | 514.00000 | 23.16293 | 27.57797 | 0.09557 | 7.20866 |
April | 485.00000 | 23.68350 | 32.89395 | 0.26480 | 8.31138 |
May | 508.00000 | 24.12351 | 41.19460 | -0.4363 | 10.63586 |
June | 496.00000 | 24.31682 | 51.80369 | -0.2366 | 7.12884 |
July | 497.00000 | 24.45859 | 55.41900 | -0.1211 | 6.73978 |
August | 514.00000 | 24.34847 | 51.05383 | -0.1367 | 6.61596 |
September | 485.00000 | 24.37137 | 47.51986 | -0.2218 | 8.11506 |
October | 502.00000 | 24.22844 | 39.13530 | 0.51412 | 12.32110 |
November | 489.00000 | 23.32238 | 30.14329 | 0.14201 | 7.65320 |
December | 497.00000 | 22.72905 | 23.46574 | -0.0624 | 7.89525 |
Annual Sum or Average | 5943.00000 | 23.61102 | 37.40026 | -0.0493 | 8.44871 |
Minimum of Months | 454.00000 | 21.93416 | 20.57404 | -0.4363 | 6.61596 |
Maximum of Months | 514.00000 | 24.45859 | 55.41900 | 0.51412 | 12.32110 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.50774 | 25.66952 | -0.1333 | 7.38540 |
February | 454.00000 | 23.22300 | 19.75664 | 0.01992 | 6.65292 |
March | 514.00000 | 24.16729 | 25.58615 | 0.35632 | 8.38756 |
April | 485.00000 | 24.48404 | 30.84756 | 0.52915 | 12.03629 |
May | 508.00000 | 24.42749 | 40.09205 | -0.2494 | 7.94818 |
June | 496.00000 | 24.53790 | 50.72866 | -0.0297 | 6.89311 |
July | 497.00000 | 24.69065 | 54.24363 | 0.09214 | 7.55826 |
August | 514.00000 | 24.56309 | 50.19078 | 0.08021 | 7.00661 |
September | 485.00000 | 24.48914 | 47.09959 | -0.1673 | 7.39370 |
October | 502.00000 | 24.44429 | 38.72530 | 0.55862 | 12.64651 |
November | 489.00000 | 24.18072 | 28.31323 | 0.34443 | 8.24824 |
December | 497.00000 | 24.13165 | 21.13179 | 0.26615 | 7.01514 |
Annual Sum or Average | 5943.00000 | 24.15978 | 36.15756 | 0.13924 | 8.26950 |
Minimum of Months | 454.00000 | 22.50774 | 19.75664 | -0.2494 | 6.65292 |
Maximum of Months | 514.00000 | 24.69065 | 54.24363 | 0.55862 | 12.64651 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.09097 | 29.16101 | -0.8019 | 21.15908 |
February | 454.00000 | 20.29100 | 23.45939 | -0.7699 | 19.47105 |
March | 514.00000 | 21.22399 | 31.83729 | -0.4327 | 10.51038 |
April | 485.00000 | 22.39921 | 36.53291 | -0.0902 | 7.41852 |
May | 508.00000 | 23.75450 | 42.60250 | -0.6098 | 14.30452 |
June | 496.00000 | 24.22549 | 53.43392 | -0.3087 | 7.70075 |
July | 497.00000 | 24.45011 | 58.01289 | -0.1745 | 6.80216 |
August | 514.00000 | 24.30190 | 53.20665 | -0.2696 | 7.35384 |
September | 485.00000 | 23.92685 | 49.78449 | -0.4919 | 11.34536 |
October | 502.00000 | 22.96491 | 43.14130 | 0.10646 | 7.52778 |
November | 489.00000 | 21.21771 | 35.22305 | -0.4197 | 11.17354 |
December | 497.00000 | 20.37946 | 27.92125 | -0.7051 | 16.84456 |
Annual Sum or Average | 5943.00000 | 22.45221 | 40.48485 | -0.4118 | 11.74927 |
Minimum of Months | 454.00000 | 20.09097 | 23.45939 | -0.8019 | 6.80216 |
Maximum of Months | 514.00000 | 24.45011 | 58.01289 | 0.10646 | 21.15908 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.10973 | 28.34802 | -0.7797 | 21.08327 |
February | 385.00000 | 20.64526 | 22.36569 | -0.6583 | 16.85877 |
March | 433.00000 | 21.82352 | 30.16130 | -0.2698 | 9.37399 |
April | 410.00000 | 22.99433 | 34.53197 | 0.08142 | 8.36973 |
May | 430.00000 | 24.07080 | 41.26380 | -0.4318 | 12.40589 |
June | 418.00000 | 24.40206 | 52.51043 | -0.1946 | 7.56604 |
July | 422.00000 | 24.64667 | 57.02953 | -0.0457 | 7.58512 |
August | 433.00000 | 24.47690 | 52.35046 | -0.1203 | 7.10722 |
September | 410.00000 | 24.26193 | 48.49142 | -0.3193 | 9.92237 |
October | 427.00000 | 23.49916 | 40.87382 | 0.25917 | 8.74482 |
November | 417.00000 | 21.63316 | 33.85883 | -0.3078 | 10.24438 |
December | 422.00000 | 20.62268 | 27.02736 | -0.6316 | 15.34920 |
Annual Sum or Average | 5034.00000 | 22.77866 | 39.17752 | -0.2828 | 11.18607 |
Minimum of Months | 385.00000 | 20.10973 | 22.36569 | -0.7797 | 7.10722 |
Maximum of Months | 433.00000 | 24.64667 | 57.02953 | 0.25917 | 21.08327 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.05591 | 27.66151 | -0.5036 | 16.01607 |
February | 454.00000 | 21.81160 | 21.52822 | -0.3281 | 12.48725 |
March | 514.00000 | 22.35626 | 29.39091 | -0.1006 | 8.78869 |
April | 485.00000 | 22.99935 | 34.73451 | 0.09492 | 8.41386 |
May | 508.00000 | 23.87402 | 42.06133 | -0.5268 | 13.26956 |
June | 496.00000 | 24.26067 | 53.13526 | -0.2677 | 7.68921 |
July | 497.00000 | 24.49127 | 57.50462 | -0.1207 | 6.98329 |
August | 514.00000 | 24.40153 | 52.36631 | -0.1366 | 6.87868 |
September | 485.00000 | 24.27466 | 48.19265 | -0.2541 | 9.10604 |
October | 502.00000 | 23.99229 | 39.90167 | 0.46097 | 12.15155 |
November | 489.00000 | 22.47390 | 32.49103 | -0.0611 | 9.13940 |
December | 497.00000 | 21.77196 | 25.83625 | -0.3118 | 11.75969 |
Annual Sum or Average | 5943.00000 | 23.15698 | 38.86323 | -0.1707 | 10.21349 |
Minimum of Months | 454.00000 | 21.05591 | 21.52822 | -0.5268 | 6.87868 |
Maximum of Months | 514.00000 | 24.49127 | 57.50462 | 0.46097 | 16.01607 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.51109 | 28.51262 | -0.6672 | 17.60312 |
February | 454.00000 | 20.93302 | 22.62701 | -0.5765 | 15.08454 |
March | 514.00000 | 22.17410 | 29.85525 | -0.1691 | 8.46450 |
April | 485.00000 | 23.10301 | 34.66147 | 0.12172 | 8.30076 |
May | 508.00000 | 24.06145 | 41.56251 | -0.4250 | 11.29270 |
June | 496.00000 | 24.38588 | 52.47750 | -0.1534 | 7.25341 |
July | 497.00000 | 24.59517 | 56.91126 | -0.0290 | 7.36275 |
August | 514.00000 | 24.46557 | 52.19301 | -0.0798 | 6.85858 |
September | 485.00000 | 24.20083 | 48.56805 | -0.3177 | 9.26414 |
October | 502.00000 | 23.63857 | 41.06044 | 0.31522 | 9.42184 |
November | 489.00000 | 21.76774 | 34.01667 | -0.2699 | 9.46585 |
December | 497.00000 | 20.93034 | 27.09344 | -0.5438 | 13.04239 |
Annual Sum or Average | 5943.00000 | 22.91285 | 39.25030 | -0.2305 | 10.24979 |
Minimum of Months | 454.00000 | 20.51109 | 22.62701 | -0.6672 | 6.85858 |
Maximum of Months | 514.00000 | 24.59517 | 56.91126 | 0.31522 | 17.60312 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86353 | 29.42743 | -0.8961 | 25.02943 |
February | 454.00000 | 19.99579 | 24.00793 | -0.8884 | 24.19932 |
March | 514.00000 | 20.77431 | 32.77749 | -0.5732 | 14.37016 |
April | 485.00000 | 21.89819 | 37.56948 | -0.2248 | 9.59898 |
May | 508.00000 | 23.49548 | 43.35843 | -0.6960 | 18.06236 |
June | 496.00000 | 24.18850 | 53.71157 | -0.3093 | 8.04830 |
July | 497.00000 | 24.46953 | 58.17230 | -0.1490 | 6.93069 |
August | 514.00000 | 24.29106 | 53.40306 | -0.2583 | 7.49960 |
September | 485.00000 | 23.74405 | 50.48093 | -0.5510 | 13.66997 |
October | 502.00000 | 22.37122 | 44.44636 | -0.0433 | 9.13860 |
November | 489.00000 | 20.57516 | 36.72110 | -0.6087 | 15.92268 |
December | 497.00000 | 19.96281 | 29.08687 | -0.8563 | 22.99985 |
Annual Sum or Average | 5943.00000 | 22.15335 | 41.22109 | -0.5019 | 14.55404 |
Minimum of Months | 454.00000 | 19.86353 | 24.00793 | -0.8961 | 6.93069 |
Maximum of Months | 514.00000 | 24.46953 | 58.17230 | -0.0433 | 25.02943 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.99334 | 29.28409 | -0.8370 | 23.33510 |
February | 454.00000 | 20.31550 | 23.65663 | -0.7690 | 20.39742 |
March | 514.00000 | 21.45609 | 31.62408 | -0.3796 | 12.08864 |
April | 485.00000 | 22.63982 | 35.57442 | -0.0132 | 9.39291 |
May | 508.00000 | 23.84848 | 42.08361 | -0.4946 | 14.50352 |
June | 496.00000 | 24.30645 | 52.90897 | -0.1966 | 7.56232 |
July | 497.00000 | 24.55133 | 57.17201 | -0.0391 | 7.46801 |
August | 514.00000 | 24.39172 | 52.43764 | -0.1098 | 6.96570 |
September | 485.00000 | 24.07780 | 49.05582 | -0.3644 | 11.00202 |
October | 502.00000 | 23.11256 | 42.21340 | 0.16707 | 9.26131 |
November | 489.00000 | 21.04186 | 35.80296 | -0.4753 | 13.97866 |
December | 497.00000 | 20.15391 | 28.80042 | -0.7822 | 20.57102 |
Annual Sum or Average | 5943.00000 | 22.50803 | 40.17205 | -0.3549 | 12.98990 |
Minimum of Months | 454.00000 | 19.99334 | 23.65663 | -0.8370 | 6.96570 |
Maximum of Months | 514.00000 | 24.55133 | 57.17201 | 0.16707 | 23.33510 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.68171 | 28.19124 | -0.6262 | 19.60060 |
February | 454.00000 | 21.28003 | 22.32348 | -0.4914 | 16.27374 |
March | 514.00000 | 21.83510 | 30.51587 | -0.2532 | 11.57347 |
April | 485.00000 | 22.53221 | 35.77727 | -0.0325 | 9.80336 |
May | 508.00000 | 23.62848 | 42.80970 | -0.6091 | 16.79294 |
June | 496.00000 | 24.21247 | 53.46260 | -0.2717 | 8.11635 |
July | 497.00000 | 24.49577 | 57.74995 | -0.0996 | 7.16942 |
August | 514.00000 | 24.38191 | 52.60838 | -0.1282 | 7.08046 |
September | 485.00000 | 24.11487 | 48.84543 | -0.3066 | 10.66861 |
October | 502.00000 | 23.59862 | 40.78921 | 0.35080 | 11.77966 |
November | 489.00000 | 21.78285 | 34.10587 | -0.2568 | 11.83853 |
December | 497.00000 | 21.13583 | 27.30709 | -0.5049 | 16.39599 |
Annual Sum or Average | 5943.00000 | 22.81888 | 39.66798 | -0.2679 | 12.23553 |
Minimum of Months | 454.00000 | 20.68171 | 22.32348 | -0.6262 | 7.08046 |
Maximum of Months | 514.00000 | 24.49577 | 57.74995 | 0.35080 | 19.60060 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.21226 | 28.89128 | -0.7718 | 21.34521 |
February | 454.00000 | 20.57224 | 23.22940 | -0.6966 | 18.98560 |
March | 514.00000 | 21.66135 | 30.87563 | -0.3113 | 11.01970 |
April | 485.00000 | 22.63515 | 35.65497 | 0.00042 | 9.47261 |
May | 508.00000 | 23.84924 | 42.22348 | -0.4955 | 14.10914 |
June | 496.00000 | 24.34791 | 52.76968 | -0.1551 | 7.57871 |
July | 497.00000 | 24.59392 | 57.15275 | -0.0109 | 7.59616 |
August | 514.00000 | 24.45341 | 52.38517 | -0.0701 | 7.01323 |
September | 485.00000 | 24.05558 | 49.16519 | -0.3648 | 10.85721 |
October | 502.00000 | 23.17735 | 42.04744 | 0.19683 | 9.78315 |
November | 489.00000 | 21.14038 | 35.42292 | -0.4439 | 12.89154 |
December | 497.00000 | 20.44543 | 28.27099 | -0.6964 | 17.87972 |
Annual Sum or Average | 5943.00000 | 22.61207 | 39.96162 | -0.3155 | 12.32824 |
Minimum of Months | 454.00000 | 20.21226 | 23.22940 | -0.7718 | 7.01323 |
Maximum of Months | 514.00000 | 24.59392 | 57.15275 | 0.19683 | 21.34521 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.163177E+09 | 11600.01 | 24-JAN-06:02 | 31.47 | 0.733416E+09 | 0.00 | 0.896594E+09 | 0.19 | 4.51 | 26-JAN-07:30 | 0.00 | 0.00 |
February | 0.411591E+09 | 7638.54 | 24-FEB-15:50 | 51.97 | 0.185004E+10 | 0.00 | 0.226163E+10 | 0.35 | 4.51 | 15-FEB-06:30 | 0.00 | 0.00 |
March | 0.536304E+10 | 74665.99 | 27-MAR-16:00 | 127.88 | 0.261112E+11 | 0.00 | 0.314743E+11 | 0.78 | 7.10 | 27-MAR-16:00 | 0.00 | 0.00 |
April | 0.207838E+11 | 156401.90 | 07-APR-15:00 | 168.22 | 0.122954E+12 | 0.00 | 0.143738E+12 | 1.19 | 7.88 | 07-APR-12:30 | 0.00 | 0.00 |
May | 0.561992E+11 | 165542.58 | 31-MAY-09:10 | 332.47 | 0.350604E+12 | 0.00 | 0.406804E+12 | 2.47 | 7.93 | 30-MAY-14:40 | 0.00 | 0.00 |
June | 0.147674E+12 | 174879.93 | 07-JUN-11:50 | 512.19 | 0.104799E+13 | 0.00 | 0.119566E+13 | 4.67 | 7.94 | 12-JUN-05:05 | 0.00 | 0.00 |
July | 0.183678E+12 | 181427.89 | 21-JUL-16:10 | 648.74 | 0.129373E+13 | 0.00 | 0.147741E+13 | 5.57 | 7.92 | 05-JUL-04:13 | 0.00 | 0.00 |
August | 0.176842E+12 | 180450.75 | 17-AUG-17:00 | 669.53 | 0.124971E+13 | 0.00 | 0.142655E+13 | 5.67 | 7.95 | 30-AUG-10:20 | 0.00 | 0.00 |
September | 0.108327E+12 | 173546.78 | 13-SEP-15:10 | 432.22 | 0.748873E+12 | 0.00 | 0.857200E+12 | 3.76 | 7.95 | 28-SEP-14:00 | 0.00 | 0.00 |
October | 0.570103E+11 | 168782.18 | 05-OCT-11:30 | 287.76 | 0.373777E+12 | 0.00 | 0.430787E+12 | 2.22 | 7.91 | 03-OCT-10:40 | 0.00 | 0.00 |
November | 0.697570E+10 | 80239.59 | 03-NOV-15:10 | 112.30 | 0.350145E+11 | 0.00 | 0.419902E+11 | 0.72 | 7.29 | 03-NOV-15:10 | 0.00 | 0.00 |
December | 0.109369E+10 | 9173.35 | 20-DEC-10:30 | 89.52 | 0.491583E+10 | 0.00 | 0.600952E+10 | 0.54 | 4.51 | 21-DEC-12:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764521E+12 | 3464.25 | 0.525627E+13 | 0.00 | 0.602079E+13 | 2.36 | 0.00 | 0.00 | ||||
Minimum of Months | 0.163177E+09 | 7638.54 | 31.47 | 0.733416E+09 | 0.00 | 0.896594E+09 | 0.19 | 4.51 | 0.00 | 0.00 | ||
Maximum of Months | 0.183678E+12 | 181427.89 | 669.53 | 0.129373E+13 | 0.00 | 0.147741E+13 | 5.67 | 7.95 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.405316E+10 | 131698.56 | 30-MAY-09:07 | 11.83 | 0.302606E+11 | 0.00 | 0.343138E+11 | 0.12 | 7.85 | 30-MAY-14:07 | 0.00 | 0.00 |
June | 0.294463E+11 | 136811.28 | 22-JUN-13:25 | 84.78 | 0.214147E+12 | 0.00 | 0.243593E+12 | 0.85 | 7.84 | 01-JUN-14:55 | 0.00 | 0.00 |
July | 0.578264E+11 | 172915.82 | 24-JUL-05:05 | 158.54 | 0.411834E+12 | 0.00 | 0.469661E+12 | 1.52 | 7.77 | 11-JUL-15:55 | 0.00 | 0.00 |
August | 0.594116E+11 | 156645.77 | 22-AUG-12:03 | 161.40 | 0.425483E+12 | 0.00 | 0.484895E+12 | 1.55 | 7.86 | 30-AUG-13:25 | 0.00 | 0.00 |
September | 0.175285E+11 | 145310.80 | 01-SEP-13:12 | 50.17 | 0.127631E+12 | 0.00 | 0.145160E+12 | 0.51 | 7.74 | 01-SEP-13:50 | 0.00 | 0.00 |
October | 0.569973E+10 | 143748.78 | 03-OCT-12:43 | 17.96 | 0.423170E+11 | 0.00 | 0.480168E+11 | 0.18 | 7.73 | 03-OCT-12:23 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.173966E+12 | 484.68 | 0.125167E+13 | 0.00 | 0.142564E+13 | 0.40 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.594116E+11 | 172915.82 | 161.40 | 0.425483E+12 | 0.00 | 0.484895E+12 | 1.55 | 7.86 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.775485E+09 | 744.00 | 2503.25 | 12-JAN-15:40 | 53797.32 | 12-JAN-15:50 | 18.56 | 18.33 | 14.04 |
February | 0.230961E+10 | 672.00 | 2884.26 | 01-FEB-12:30 | 78963.08 | 01-FEB-12:30 | 19.19 | 18.33 | 14.04 |
March | 0.777088E+10 | 744.00 | 43776.24 | 27-MAR-12:05 | 378062.73 | 27-MAR-16:00 | 20.00 | 18.37 | 14.04 |
April | 0.344067E+11 | 720.00 | 43776.24 | 06-APR-08:35 | 622871.67 | 09-APR-10:47 | 22.54 | 19.00 | 14.03 |
May | 0.403258E+11 | 744.00 | 43776.24 | 05-MAY-11:30 | 322765.12 | 31-MAY-23:20 | 20.16 | 19.32 | 14.06 |
June | 0.103981E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 463807.17 | 30-JUN-24:00 | 29.02 | 24.03 | 14.06 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 621011.44 | 31-JUL-24:00 | 39.26 | 29.32 | 14.06 |
August | 0.117224E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 677105.99 | 04-AUG-21:02 | 42.31 | 30.08 | 14.06 |
September | 0.829231E+11 | 720.00 | 43776.24 | 01-SEP-00:03 | 331523.89 | 01-SEP-13:40 | 23.11 | 21.51 | 14.06 |
October | 0.392992E+11 | 744.00 | 43776.24 | 02-OCT-09:05 | 399466.43 | 25-OCT-10:20 | 20.58 | 19.02 | 14.05 |
November | 0.935287E+10 | 720.00 | 43776.24 | 03-NOV-13:00 | 197264.08 | 01-NOV-21:03 | 19.92 | 18.34 | 14.03 |
December | 0.650422E+10 | 744.00 | 5944.50 | 17-DEC-14:58 | 150257.27 | 04-DEC-17:50 | 20.36 | 18.33 | 14.04 |
Annual Sum or Average | 0.562123E+12 | 8760.00 | 24.64 | 21.19 | 14.05 | ||||
Minimum of Months | 0.775485E+09 | 672.00 | 2503.25 | 53797.32 | 18.56 | 18.33 | 14.03 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 677105.99 | 42.31 | 30.08 | 14.06 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 246333.79 | 30-JAN-08:37 | 21.00 | 20.99 | 0.26 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 247244.45 | 02-FEB-15:30 | 20.89 | 20.89 | 0.31 |
March | 31257375.95 | 10.56 | 2185.93 | 27-MAR-16:00 | 610297.27 | 27-MAR-16:00 | 21.05 | 21.00 | 3.97 |
April | 0.434694E+09 | 89.95 | 17899.53 | 07-APR-12:40 | 1379998.14 | 07-APR-15:00 | 21.31 | 21.09 | 11.25 |
May | 0.232598E+10 | 249.68 | 17899.53 | 18-MAY-10:00 | 1382752.69 | 30-MAY-08:50 | 21.77 | 21.17 | 25.63 |
June | 0.213645E+11 | 481.87 | 17899.53 | 01-JUN-09:30 | 1434440.73 | 01-JUN-16:00 | 24.20 | 22.43 | 42.19 |
July | 0.383824E+11 | 644.01 | 17899.53 | 01-JUL-04:12 | 1335637.33 | 11-JUL-11:20 | 26.01 | 23.90 | 50.68 |
August | 0.291890E+11 | 608.09 | 17899.53 | 01-AUG-00:05 | 1389147.83 | 22-AUG-16:40 | 25.11 | 23.05 | 51.79 |
September | 0.109510E+11 | 376.70 | 17899.53 | 01-SEP-04:12 | 1333813.64 | 01-SEP-16:20 | 23.35 | 22.08 | 35.44 |
October | 0.438444E+10 | 228.84 | 17899.53 | 02-OCT-12:50 | 1348820.24 | 13-OCT-14:00 | 22.02 | 21.40 | 22.17 |
November | 17563411.45 | 32.64 | 652.95 | 10-NOV-10:05 | 653200.74 | 03-NOV-15:10 | 21.18 | 21.11 | 4.95 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 247379.14 | 21-DEC-13:40 | 20.94 | 20.93 | 0.93 |
Annual Sum or Average | 0.107081E+12 | 2722.35 | 22.41 | 21.68 | 20.94 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 246333.79 | 20.89 | 20.89 | 0.26 | ||
Maximum of Months | 0.383824E+11 | 644.01 | 17899.53 | 1434440.73 | 26.01 | 23.90 | 51.79 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.00 | 21.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.89 | 20.89 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.05 | 21.05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.31 | 21.31 | 0.00 |
May | 0.801899E+09 | 12.44 | 17899.53 | 30-MAY-09:07 | 1073902.31 | 30-MAY-09:07 | 21.77 | 21.71 | 1.04 |
June | 0.827989E+10 | 128.49 | 17899.53 | 01-JUN-10:00 | 1105228.94 | 22-JUN-13:25 | 24.20 | 23.55 | 9.41 |
July | 0.171655E+11 | 266.39 | 17899.53 | 01-JUL-10:05 | 1195046.26 | 24-JUL-05:05 | 26.01 | 24.73 | 18.21 |
August | 0.146597E+11 | 230.81 | 17899.53 | 01-AUG-05:04 | 1305390.15 | 30-AUG-16:00 | 25.11 | 23.99 | 16.53 |
September | 0.469827E+10 | 72.91 | 17899.53 | 01-SEP-07:10 | 1252045.99 | 01-SEP-13:12 | 23.35 | 22.98 | 5.43 |
October | 0.124312E+10 | 19.29 | 17899.53 | 03-OCT-10:30 | 1061426.32 | 03-OCT-12:43 | 22.02 | 21.93 | 1.56 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.18 | 21.18 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.94 | 20.94 | 0.00 |
Annual Sum or Average | 0.468483E+11 | 730.33 | 22.41 | 22.11 | 4.39 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 20.89 | 0.00 | ||
Maximum of Months | 0.171655E+11 | 266.39 | 17899.53 | 1305390.15 | 26.01 | 24.73 | 18.21 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.254405E+12 | 0.00 | 540.52 | 2144040.66 | 03-JAN-05:21 | 0.00 | 34.79 | 52.54 | 1.22 | 0.00 | 0.04 | 0.86 | 03-JAN-05:21 |
February | 0.172436E+12 | 0.00 | 470.10 | 1769755.45 | 22-FEB-05:01 | 0.00 | 34.78 | 51.76 | 0.89 | 0.00 | 0.03 | 0.71 | 22-FEB-05:01 |
March | 0.520183E+11 | 0.00 | 348.28 | 1854835.06 | 11-MAR-05:11 | 0.00 | 31.24 | 43.85 | 0.21 | 0.00 | 0.01 | 0.74 | 11-MAR-05:11 |
April | 0.139904E+11 | 0.00 | 177.68 | 1765651.39 | 22-APR-04:11 | 0.00 | 30.28 | 37.39 | 0.05 | 0.00 | 0.00 | 0.71 | 22-APR-04:11 |
May | 0.856202E+09 | 0.00 | 16.24 | 167211.72 | 30-MAY-14:03 | 0.00 | 30.62 | 31.25 | 0.00 | 0.00 | 0.00 | 0.07 | 30-MAY-14:03 |
June | 0.121439E+10 | 0.00 | 16.14 | 188488.59 | 01-JUN-14:50 | 0.00 | 42.89 | 43.28 | 0.01 | 0.00 | 0.00 | 0.08 | 01-JUN-14:50 |
July | 0.516751E+09 | 0.00 | 8.56 | 93417.32 | 11-JUL-15:37 | 0.00 | 40.18 | 40.41 | 0.00 | 0.00 | 0.00 | 0.04 | 11-JUL-15:37 |
August | 0.137373E+10 | 0.00 | 21.14 | 151745.24 | 24-AUG-17:07 | 0.00 | 40.79 | 41.26 | 0.01 | 0.00 | 0.00 | 0.06 | 24-AUG-17:07 |
September | 0.263373E+09 | 0.00 | 7.25 | 78050.04 | 01-SEP-16:40 | 0.00 | 43.39 | 43.57 | 0.00 | 0.00 | 0.00 | 0.03 | 01-SEP-16:40 |
October | 0.227764E+10 | 0.00 | 75.24 | 648764.01 | 28-OCT-05:03 | 0.00 | 35.51 | 38.21 | 0.01 | 0.00 | 0.00 | 0.26 | 28-OCT-05:03 |
November | 0.548075E+11 | 0.00 | 309.54 | 1930614.37 | 15-NOV-05:11 | 0.00 | 32.01 | 43.49 | 0.23 | 0.00 | 0.01 | 0.77 | 15-NOV-05:11 |
December | 0.122057E+12 | 0.00 | 468.29 | 1797337.17 | 21-DEC-05:01 | 0.00 | 32.43 | 49.19 | 0.50 | 0.00 | 0.02 | 0.72 | 21-DEC-05:01 |
Annual Sum or Average | 0.676216E+12 | 0.00 | 2458.96 | 0.00 | 35.73 | 42.95 | 0.26 | 0.00 | 0.01 | ||||
Minimum of Months | 0.263373E+09 | 0.00 | 7.25 | 78050.04 | 0.00 | 30.28 | 31.25 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.254405E+12 | 0.00 | 540.52 | 2144040.66 | 0.00 | 43.39 | 52.54 | 1.22 | 0.00 | 0.04 | 0.86 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 18.56 | 18.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.19 | 19.19 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.00 | 20.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22.54 | 22.54 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.16 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.02 | 29.02 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 39.26 | 39.26 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 42.31 | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 23.11 | 23.11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 20.58 | 20.58 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.92 | 19.92 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.36 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 18.56 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.31 | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.403654E+09 | 0.00 | 26.97 | 0.403654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18566.92 | 19-JAN-14:20 | 18566.92 | 19-JAN-14:20 | 0.00 | 0.00 | 0.00 |
February | 0.100775E+10 | 0.00 | 44.11 | 0.100775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22513.91 | 24-FEB-15:30 | 22513.91 | 24-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.504468E+10 | 0.00 | 106.17 | 0.500858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65940.16 | 27-MAR-16:00 | 65940.16 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.124807E+11 | 0.00 | 132.45 | 0.124745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112942.92 | 07-APR-14:40 | 112942.92 | 07-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.339305E+11 | 0.00 | 312.88 | 0.305482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161336.07 | 30-MAY-13:40 | 161336.07 | 30-MAY-13:40 | 0.00 | 0.00 | 0.00 |
June | 0.113738E+12 | 0.00 | 498.30 | 0.928109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193725.30 | 15-JUN-04:12 | 161995.70 | 22-JUN-15:35 | 0.00 | 0.00 | 0.00 |
July | 0.157088E+12 | 0.00 | 618.38 | 0.129881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 216533.67 | 10-JUL-04:02 | 170575.38 | 11-JUL-15:37 | 0.00 | 0.00 | 0.00 |
August | 0.161205E+12 | 0.00 | 650.12 | 0.141764E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 199908.94 | 14-AUG-04:21 | 188198.12 | 22-AUG-14:15 | 0.00 | 0.00 | 0.00 |
September | 0.758084E+11 | 0.00 | 415.05 | 0.647915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186120.37 | 22-SEP-04:12 | 156252.23 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.383038E+11 | 0.00 | 260.84 | 0.293040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144532.71 | 06-OCT-04:12 | 96413.01 | 04-OCT-14:40 | 0.00 | 0.00 | 0.00 |
November | 0.318571E+10 | 0.00 | 86.72 | 0.310331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53392.06 | 10-NOV-06:03 | 38511.45 | 01-NOV-10:30 | 0.00 | 0.00 | 0.00 |
December | 0.341458E+10 | 0.00 | 83.67 | 0.341458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32698.20 | 18-DEC-14:30 | 32698.20 | 18-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.605610E+12 | 0.00 | 3235.66 | 0.514511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.403654E+09 | 0.00 | 26.97 | 0.403654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18566.92 | 18566.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.161205E+12 | 0.00 | 650.12 | 0.141764E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 216533.67 | 188198.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 48935580.64 | 0.00 | 15.26 | 48935580.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5395.14 | 27-JAN-15:10 | 5395.14 | 27-JAN-15:10 | 0.00 | 0.00 | 0.00 |
February | 0.166581E+09 | 0.00 | 31.97 | 0.166581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12094.64 | 24-FEB-15:50 | 12094.64 | 24-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.180189E+11 | 0.00 | 89.12 | 0.180171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 400604.51 | 27-MAR-16:00 | 400604.51 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.950080E+11 | 0.00 | 140.60 | 0.949873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 910674.62 | 07-APR-15:10 | 910674.62 | 07-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.295081E+12 | 0.00 | 309.75 | 0.266756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1574223.25 | 30-MAY-14:07 | 1574223.25 | 30-MAY-14:07 | 0.00 | 0.00 | 0.00 |
June | 0.946767E+12 | 0.00 | 449.19 | 0.746803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1895877.86 | 27-JUN-04:11 | 1568237.89 | 22-JUN-15:40 | 0.00 | 0.00 | 0.00 |
July | 0.126326E+13 | 0.00 | 477.37 | 0.980807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2262304.43 | 24-JUL-05:03 | 1455535.60 | 11-JUL-14:05 | 0.00 | 0.00 | 0.00 |
August | 0.123954E+13 | 0.00 | 480.00 | 0.105131E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1834573.17 | 24-AUG-16:30 | 1834573.17 | 24-AUG-16:30 | 0.00 | 0.00 | 0.00 |
September | 0.659382E+12 | 0.00 | 398.22 | 0.552146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1767629.56 | 01-SEP-14:55 | 1767629.56 | 01-SEP-14:55 | 0.00 | 0.00 | 0.00 |
October | 0.320611E+12 | 0.00 | 261.45 | 0.247857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1161306.82 | 06-OCT-05:03 | 862743.68 | 04-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.296448E+11 | 0.00 | 86.11 | 0.292617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 448000.62 | 03-NOV-14:05 | 448000.62 | 03-NOV-14:05 | 0.00 | 0.00 | 0.00 |
December | 0.274703E+09 | 0.00 | 55.68 | 0.274703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12041.75 | 21-DEC-14:30 | 12041.75 | 21-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486780E+13 | 0.00 | 2794.74 | 0.398843E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 48935580.64 | 0.00 | 15.26 | 48935580.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5395.14 | 5395.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.126326E+13 | 0.00 | 480.00 | 0.105131E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2262304.43 | 1834573.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9540862.98 | 0.00 | 14.39 | 9540862.98 | 0.00 | 0.00 | 0.00 | 0.00 | 831.20 | 15-JAN-10:50 | 831.20 | 15-JAN-10:50 | 0.00 | 0.00 | 0.00 |
February | 18098289.14 | 0.00 | 28.18 | 18098289.14 | 0.00 | 0.00 | 0.00 | 0.00 | 537.57 | 02-FEB-10:50 | 537.57 | 02-FEB-10:50 | 0.00 | 0.00 | 0.00 |
March | 0.802188E+09 | 0.00 | 79.85 | 0.802188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33585.30 | 27-MAR-16:00 | 33585.30 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.829779E+10 | 0.00 | 119.71 | 0.829779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103273.10 | 07-APR-14:50 | 103273.10 | 07-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.302314E+11 | 0.00 | 299.69 | 0.275812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179370.34 | 30-MAY-14:03 | 179370.34 | 30-MAY-14:03 | 0.00 | 0.00 | 0.00 |
June | 0.102440E+12 | 0.00 | 446.27 | 0.822836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 197961.09 | 19-JUN-04:12 | 168784.01 | 23-JUN-10:10 | 0.00 | 0.00 | 0.00 |
July | 0.141254E+12 | 0.00 | 479.97 | 0.111603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243092.52 | 24-JUL-05:03 | 161527.77 | 11-JUL-14:05 | 0.00 | 0.00 | 0.00 |
August | 0.136729E+12 | 0.00 | 481.21 | 0.117397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 220209.22 | 05-AUG-03:02 | 189910.32 | 22-AUG-14:10 | 0.00 | 0.00 | 0.00 |
September | 0.672082E+11 | 0.00 | 393.01 | 0.564136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 175095.08 | 01-SEP-04:12 | 171897.15 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 |
October | 0.272795E+11 | 0.00 | 240.57 | 0.206831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123605.28 | 04-OCT-14:50 | 96636.71 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 |
November | 0.634438E+09 | 0.00 | 55.03 | 0.604780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16307.27 | 03-NOV-14:00 | 16307.27 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 27716048.84 | 0.00 | 54.53 | 27716048.84 | 0.00 | 0.00 | 0.00 | 0.00 | 508.05 | 21-DEC-11:30 | 508.05 | 21-DEC-11:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514933E+12 | 0.00 | 2692.40 | 0.425721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9540862.98 | 0.00 | 14.39 | 9540862.98 | 0.00 | 0.00 | 0.00 | 0.00 | 508.05 | 508.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.141254E+12 | 0.00 | 481.21 | 0.117397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243092.52 | 189910.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7265902.43 | 0.00 | 0.43 | 3177209.47 | 0.00 | 0.00 | 0.00 | 0.00 | 33492.33 | 24-JAN-06:02 | 14678.81 | 24-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 5257.73 | 0.00 | 0.17 | 5257.73 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 16-FEB-20:40 | 8.76 | 16-FEB-20:40 | 0.00 | 0.00 | 0.00 |
March | 0.562617E+09 | 0.00 | 7.70 | 0.562617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37672.28 | 27-MAR-16:00 | 37672.28 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.511323E+10 | 0.00 | 69.33 | 0.507299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60349.68 | 10-APR-05:02 | 58769.20 | 07-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.146669E+11 | 0.00 | 186.77 | 0.139727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89838.07 | 30-MAY-10:55 | 89838.07 | 30-MAY-10:55 | 0.00 | 0.00 | 0.00 |
June | 0.617354E+11 | 0.00 | 384.08 | 0.507924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130084.31 | 19-JUN-04:53 | 91924.93 | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.895414E+11 | 0.00 | 400.98 | 0.689404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141999.74 | 10-JUL-03:02 | 80803.69 | 18-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.906345E+11 | 0.00 | 440.33 | 0.748252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132210.95 | 13-AUG-16:11 | 99901.30 | 13-AUG-16:11 | 0.00 | 0.00 | 0.00 |
September | 0.471375E+11 | 0.00 | 340.48 | 0.406731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123297.79 | 08-SEP-04:53 | 91819.16 | 04-SEP-17:22 | 0.00 | 0.00 | 0.00 |
October | 0.184637E+11 | 0.00 | 187.44 | 0.152495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101015.46 | 06-OCT-04:12 | 55939.11 | 04-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.154824E+09 | 0.00 | 7.69 | 0.136132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68041.85 | 10-NOV-06:03 | 27420.70 | 10-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 9637.81 | 0.00 | 0.17 | 9637.81 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 | 06-DEC-19:20 | 16.06 | 06-DEC-19:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328017E+12 | 0.00 | 2025.56 | 0.270228E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5257.73 | 0.00 | 0.17 | 5257.73 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 8.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.906345E+11 | 0.00 | 440.33 | 0.748252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141999.74 | 99901.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.546816E+10 | 0.346858E+10 | 705.14 | 0.546803E+10 | 126118.61 | 0.00 | 0.02 | 20-JAN-05:55 | 0.01 | 24-JAN-05:45 | 3594.78 | 20-JAN-05:55 | 3594.78 | 20-JAN-05:55 | 26.56 | 18-JAN-18:40 | 1883.38 | 17-JAN-16:30 | 0.00 |
February | 0.106241E+11 | 0.462115E+10 | 672.00 | 0.106093E+11 | 14788161.32 | 0.00 | 0.03 | 01-FEB-12:20 | 0.01 | 28-FEB-16:00 | 5159.00 | 20-FEB-13:43 | 5159.00 | 20-FEB-13:43 | 89.57 | 28-FEB-18:20 | 2715.51 | 13-FEB-14:20 | 0.00 |
March | 0.158226E+11 | 0.626854E+10 | 696.72 | 0.141304E+11 | 0.169217E+10 | 0.00 | 0.62 | 27-MAR-16:00 | 0.01 | 26-MAR-12:27 | 232489.05 | 27-MAR-16:00 | 183676.77 | 27-MAR-16:00 | 82610.93 | 27-MAR-13:00 | 59560.45 | 27-MAR-16:00 | 0.00 |
April | 0.143051E+12 | 0.378667E+11 | 673.61 | 0.116409E+12 | 0.266415E+11 | 0.00 | 1.00 | 07-APR-12:40 | 0.01 | 16-APR-01:10 | 408567.38 | 09-APR-10:43 | 398579.97 | 09-APR-10:57 | 137082.18 | 09-APR-10:33 | 110819.25 | 07-APR-13:00 | 0.00 |
May | 0.221344E+11 | 0.828677E+10 | 449.94 | 0.215059E+11 | 0.628529E+09 | 0.00 | 0.54 | 31-MAY-23:20 | 0.01 | 27-MAY-05:55 | 212115.18 | 31-MAY-23:10 | 210545.46 | 31-MAY-23:20 | 34085.75 | 31-MAY-09:05 | 59873.14 | 30-MAY-13:50 | 0.00 |
June | 0.372607E+12 | 0.980952E+11 | 655.40 | 0.351047E+12 | 0.215595E+11 | 0.00 | 0.76 | 30-JUN-24:00 | 0.01 | 08-JUN-21:35 | 325784.11 | 21-JUN-14:40 | 302319.31 | 30-JUN-24:00 | 130440.68 | 21-JUN-14:30 | 84654.32 | 22-JUN-15:55 | 0.00 |
July | 0.832456E+12 | 0.225357E+12 | 744.00 | 0.819576E+12 | 0.128797E+11 | 0.00 | 0.98 | 31-JUL-24:00 | 0.42 | 11-JUL-05:00 | 394706.24 | 31-JUL-24:00 | 394706.24 | 31-JUL-24:00 | 84791.60 | 11-JUL-19:50 | 108086.16 | 07-JUL-12:00 | 0.00 |
August | 0.101709E+13 | 0.274490E+12 | 744.00 | 0.973885E+12 | 0.432039E+11 | 0.00 | 1.00 | 01-AUG-06:40 | 0.38 | 08-AUG-04:53 | 417681.56 | 31-AUG-05:40 | 404450.68 | 13-AUG-23:55 | 184209.98 | 31-AUG-05:30 | 128378.82 | 24-AUG-15:41 | 0.00 |
September | 0.922796E+11 | 0.266083E+11 | 464.10 | 0.873915E+11 | 0.488806E+10 | 0.00 | 0.65 | 01-SEP-13:40 | 0.01 | 30-SEP-07:05 | 237261.89 | 01-SEP-13:40 | 237261.89 | 01-SEP-13:40 | 81187.46 | 13-SEP-11:00 | 74306.64 | 01-SEP-13:40 | 0.00 |
October | 0.447646E+11 | 0.134976E+11 | 535.77 | 0.327189E+11 | 0.120458E+11 | 0.00 | 0.68 | 25-OCT-10:20 | 0.01 | 23-OCT-05:04 | 277684.39 | 25-OCT-10:20 | 218250.16 | 04-OCT-13:10 | 88465.81 | 25-OCT-10:05 | 68598.16 | 25-OCT-10:20 | 0.00 |
November | 0.134506E+11 | 0.563834E+10 | 624.35 | 0.127128E+11 | 0.737834E+09 | 0.00 | 0.25 | 04-NOV-13:00 | 0.01 | 03-NOV-21:10 | 81361.60 | 04-NOV-13:00 | 76510.05 | 03-NOV-14:00 | 28074.59 | 10-NOV-08:00 | 20525.80 | 04-NOV-13:00 | 0.00 |
December | 0.147888E+11 | 0.641379E+10 | 740.33 | 0.144936E+11 | 0.295153E+09 | 0.00 | 0.09 | 17-DEC-12:00 | 0.01 | 25-DEC-07:40 | 21518.65 | 17-DEC-12:02 | 21518.65 | 17-DEC-12:02 | 711.89 | 26-DEC-03:55 | 7355.17 | 17-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.258453E+13 | 0.710612E+12 | 7705.35 | 0.245995E+13 | 0.124587E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.546816E+10 | 0.346858E+10 | 449.94 | 0.546803E+10 | 126118.61 | 0.00 | 0.02 | 0.01 | 3594.78 | 3594.78 | 26.56 | 1883.38 | 0.00 | ||||||
Maximum of Months | 0.101709E+13 | 0.274490E+12 | 744.00 | 0.973885E+12 | 0.432039E+11 | 0.00 | 1.00 | 0.42 | 417681.56 | 404450.68 | 184209.98 | 128378.82 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.315822E+10 | 0.753331E+09 | 742.62 | 0.315285E+10 | 5369000.58 | 0.00 | 0.30 | 29-JAN-16:40 | 0.00 | 01-JAN-01:45 | 2288.62 | 29-JAN-16:40 | 2288.62 | 29-JAN-16:40 | 98.58 | 24-JAN-15:20 | 507.34 | 29-JAN-16:40 | 0.00 |
February | 0.794025E+10 | 0.177260E+10 | 672.00 | 0.794025E+10 | 0.00 | 0.00 | 0.54 | 20-FEB-16:13 | 0.28 | 06-FEB-07:05 | 4330.86 | 20-FEB-16:20 | 4330.86 | 20-FEB-16:20 | 0.00 | 05-FEB-13:28 | 928.50 | 20-FEB-16:13 | 0.00 |
March | 0.148669E+11 | 0.304170E+10 | 744.00 | 0.148555E+11 | 11403008.39 | 0.00 | 0.82 | 31-MAR-24:00 | 0.58 | 01-MAR-07:03 | 7460.20 | 31-MAR-24:00 | 7460.20 | 31-MAR-24:00 | 234.00 | 27-MAR-15:00 | 1479.36 | 27-MAR-17:00 | 0.00 |
April | 0.197219E+11 | 0.387252E+10 | 720.00 | 0.196963E+11 | 25542324.15 | 0.00 | 0.97 | 23-APR-17:47 | 0.30 | 30-APR-24:00 | 8839.55 | 23-APR-17:47 | 8839.55 | 23-APR-17:47 | 247.66 | 27-APR-16:00 | 2211.41 | 07-APR-17:00 | 0.00 |
May | 0.554745E+10 | 0.124131E+10 | 744.00 | 0.545269E+10 | 94764304.37 | 0.00 | 0.48 | 31-MAY-23:20 | 0.19 | 04-MAY-07:00 | 4090.23 | 31-MAY-23:40 | 4012.49 | 31-MAY-24:00 | 276.85 | 18-MAY-15:30 | 908.66 | 31-MAY-23:20 | 0.00 |
June | 0.108938E+11 | 0.261995E+10 | 720.00 | 0.105698E+11 | 0.323995E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.44 | 02-JUN-06:20 | 5857.45 | 30-JUN-24:00 | 5838.94 | 30-JUN-24:00 | 531.04 | 15-JUN-14:00 | 1658.91 | 19-JUN-12:05 | 0.00 |
July | 0.165809E+11 | 0.441239E+10 | 744.00 | 0.160995E+11 | 0.481388E+09 | 0.00 | 0.90 | 31-JUL-24:00 | 0.68 | 11-JUL-06:10 | 7749.12 | 31-JUL-24:00 | 7749.12 | 31-JUL-24:00 | 614.61 | 20-JUL-15:00 | 2145.35 | 10-JUL-15:00 | 0.00 |
August | 0.215845E+11 | 0.568120E+10 | 744.00 | 0.212095E+11 | 0.375047E+09 | 0.00 | 1.00 | 01-AUG-12:40 | 0.32 | 31-AUG-24:00 | 8821.95 | 31-AUG-18:00 | 8554.29 | 13-AUG-18:35 | 612.26 | 03-AUG-15:00 | 2719.94 | 24-AUG-15:43 | 0.00 |
September | 0.573117E+10 | 0.135506E+10 | 720.00 | 0.552832E+10 | 0.202841E+09 | 0.00 | 0.46 | 30-SEP-24:00 | 0.20 | 30-SEP-06:45 | 3901.18 | 30-SEP-24:00 | 3901.18 | 30-SEP-24:00 | 445.40 | 07-SEP-15:00 | 843.83 | 14-SEP-14:00 | 0.00 |
October | 0.106727E+11 | 0.224957E+10 | 744.00 | 0.105239E+11 | 0.148792E+09 | 0.00 | 0.64 | 31-OCT-24:00 | 0.41 | 28-OCT-06:55 | 5646.76 | 31-OCT-24:00 | 5645.98 | 31-OCT-24:00 | 350.47 | 24-OCT-16:00 | 1181.47 | 04-OCT-16:00 | 0.00 |
November | 0.144264E+11 | 0.291385E+10 | 720.00 | 0.144087E+11 | 17698871.26 | 0.00 | 0.74 | 23-NOV-15:55 | 0.59 | 01-NOV-06:20 | 6092.93 | 03-NOV-16:00 | 6092.93 | 03-NOV-16:00 | 265.94 | 10-NOV-10:20 | 1259.84 | 23-NOV-15:55 | 0.00 |
December | 0.196656E+11 | 0.395817E+10 | 744.00 | 0.196656E+11 | 0.00 | 0.00 | 0.97 | 03-DEC-15:45 | 0.80 | 04-DEC-22:00 | 8263.37 | 17-DEC-16:00 | 8263.37 | 17-DEC-16:00 | 0.00 | 03-DEC-17:50 | 1654.81 | 03-DEC-15:45 | 0.00 |
Annual Sum or Average | 0.150790E+12 | 0.338717E+11 | 8758.62 | 0.149103E+12 | 0.168684E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.315822E+10 | 0.753331E+09 | 672.00 | 0.315285E+10 | 0.00 | 0.00 | 0.30 | 0.00 | 2288.62 | 2288.62 | 0.00 | 507.34 | 0.00 | ||||||
Maximum of Months | 0.215845E+11 | 0.568120E+10 | 744.00 | 0.212095E+11 | 0.481388E+09 | 0.00 | 1.00 | 0.80 | 8839.55 | 8839.55 | 614.61 | 2719.94 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.647414E+10 | 0.171920E+10 | 440.44 | 0.644125E+10 | 32885735.89 | 0.00 | 0.23 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 | 16549.83 | 20-JAN-16:30 | 16549.83 | 20-JAN-16:30 | 746.92 | 24-JAN-15:20 | 3819.46 | 17-JAN-16:30 | 0.00 |
February | 0.521583E+11 | 0.120203E+11 | 672.00 | 0.521583E+11 | -0.0 | 0.00 | 0.48 | 22-FEB-17:00 | 0.10 | 06-FEB-07:05 | 36125.71 | 22-FEB-17:00 | 36125.71 | 22-FEB-17:00 | 0.00 | 05-FEB-22:27 | 7919.59 | 22-FEB-17:00 | 0.00 |
March | 0.124285E+12 | 0.258233E+11 | 744.00 | 0.124170E+12 | 0.114847E+09 | 0.00 | 0.76 | 31-MAR-23:40 | 0.46 | 01-MAR-07:03 | 65334.34 | 31-MAR-23:40 | 65334.34 | 31-MAR-23:40 | 2306.31 | 27-MAR-15:00 | 13838.82 | 27-MAR-17:00 | 0.00 |
April | 0.177455E+12 | 0.351693E+11 | 720.00 | 0.177198E+12 | 0.256929E+09 | 0.00 | 0.95 | 12-APR-17:40 | 0.21 | 30-APR-24:00 | 81641.17 | 09-APR-17:32 | 81394.20 | 09-APR-17:34 | 2448.53 | 27-APR-16:00 | 21091.06 | 07-APR-17:00 | 0.00 |
May | 0.479674E+11 | 0.108407E+11 | 744.00 | 0.470367E+11 | 0.930747E+09 | 0.00 | 0.48 | 31-MAY-23:20 | 0.13 | 01-MAY-06:05 | 38916.75 | 31-MAY-23:40 | 38101.91 | 31-MAY-24:00 | 2728.61 | 18-MAY-15:30 | 8657.69 | 31-MAY-23:20 | 0.00 |
June | 0.102168E+12 | 0.246507E+11 | 720.00 | 0.989524E+11 | 0.321558E+10 | 0.00 | 0.67 | 30-JUN-24:00 | 0.42 | 07-JUN-06:10 | 55217.76 | 30-JUN-24:00 | 55030.26 | 30-JUN-24:00 | 5268.39 | 15-JUN-14:00 | 15824.46 | 19-JUN-12:05 | 0.00 |
July | 0.158045E+12 | 0.420917E+11 | 744.00 | 0.153247E+12 | 0.479814E+10 | 0.00 | 0.90 | 31-JUL-24:00 | 0.67 | 01-JUL-06:10 | 74357.92 | 31-JUL-24:00 | 74357.92 | 31-JUL-24:00 | 6127.54 | 20-JUL-15:00 | 20572.83 | 07-JUL-12:10 | 0.00 |
August | 0.205564E+12 | 0.541733E+11 | 744.00 | 0.201813E+12 | 0.375111E+10 | 0.00 | 1.00 | 01-AUG-12:50 | 0.29 | 31-AUG-24:00 | 84596.51 | 31-AUG-18:00 | 81394.97 | 10-AUG-18:10 | 6133.66 | 03-AUG-15:00 | 26085.57 | 24-AUG-15:43 | 0.00 |
September | 0.507926E+11 | 0.121145E+11 | 720.00 | 0.487981E+11 | 0.199447E+10 | 0.00 | 0.44 | 30-SEP-23:30 | 0.16 | 30-SEP-06:55 | 35737.27 | 30-SEP-23:30 | 35737.27 | 30-SEP-23:30 | 4414.47 | 07-SEP-15:00 | 8008.71 | 14-SEP-14:00 | 0.00 |
October | 0.939635E+11 | 0.199743E+11 | 744.00 | 0.924888E+11 | 0.147463E+10 | 0.00 | 0.58 | 31-OCT-23:50 | 0.34 | 28-OCT-06:55 | 49279.84 | 31-OCT-23:50 | 49253.43 | 31-OCT-23:50 | 3485.22 | 24-OCT-16:00 | 11262.06 | 04-OCT-16:00 | 0.00 |
November | 0.117863E+12 | 0.242049E+11 | 720.00 | 0.117686E+12 | 0.176741E+09 | 0.00 | 0.68 | 03-NOV-16:00 | 0.44 | 24-NOV-07:10 | 57264.85 | 03-NOV-16:00 | 57264.85 | 03-NOV-16:00 | 2639.31 | 10-NOV-10:20 | 11245.66 | 03-NOV-16:00 | 0.00 |
December | 0.160258E+12 | 0.329636E+11 | 744.00 | 0.160258E+12 | 0.00 | 0.00 | 0.88 | 21-DEC-16:10 | 0.60 | 31-DEC-23:54 | 71395.46 | 08-DEC-16:10 | 71395.46 | 08-DEC-16:10 | 0.00 | 13-DEC-19:30 | 14349.44 | 21-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.129700E+13 | 0.295746E+12 | 8456.44 | 0.128025E+13 | 0.167461E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.647414E+10 | 0.171920E+10 | 440.44 | 0.644125E+10 | -0.0 | 0.00 | 0.23 | 0.00 | 16549.83 | 16549.83 | 0.00 | 3819.46 | 0.00 | ||||||
Maximum of Months | 0.205564E+12 | 0.541733E+11 | 744.00 | 0.201813E+12 | 0.479814E+10 | 0.00 | 1.00 | 0.67 | 84596.51 | 81394.97 | 6133.66 | 26085.57 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.231906E+09 | 62442100.71 | 170.30 | 0.229866E+09 | 2039200.99 | 0.00 | 0.22 | 19-JAN-16:30 | 0.00 | 01-JAN-00:01 | 1631.64 | 19-JAN-16:30 | 1631.64 | 19-JAN-16:30 | 60.80 | 24-JAN-15:20 | 370.42 | 19-JAN-16:30 | 0.00 |
February | 0.374316E+10 | 0.882057E+09 | 655.44 | 0.374316E+10 | 0.00 | 0.00 | 0.46 | 02-FEB-16:50 | 0.00 | 05-FEB-03:05 | 3509.06 | 22-FEB-17:00 | 3509.06 | 22-FEB-17:00 | 0.00 | 24-FEB-08:15 | 774.92 | 02-FEB-16:50 | 0.00 |
March | 0.110981E+11 | 0.233441E+10 | 744.00 | 0.110869E+11 | 11244556.53 | 0.00 | 0.71 | 27-MAR-17:10 | 0.34 | 13-MAR-03:23 | 6071.42 | 27-MAR-17:20 | 5971.35 | 31-MAR-23:20 | 231.22 | 27-MAR-15:00 | 1384.93 | 27-MAR-17:00 | 0.00 |
April | 0.168667E+11 | 0.337324E+10 | 720.00 | 0.168412E+11 | 25525255.94 | 0.00 | 0.94 | 12-APR-17:40 | 0.12 | 30-APR-24:00 | 8278.77 | 09-APR-17:23 | 8249.14 | 09-APR-17:25 | 245.19 | 27-APR-16:00 | 2136.70 | 07-APR-17:00 | 0.00 |
May | 0.448424E+10 | 0.102308E+10 | 743.88 | 0.439208E+10 | 92157544.06 | 0.00 | 0.47 | 31-MAY-23:20 | 0.00 | 01-MAY-04:05 | 3852.00 | 31-MAY-23:30 | 3767.00 | 31-MAY-24:00 | 273.54 | 18-MAY-15:30 | 859.58 | 31-MAY-23:20 | 0.00 |
June | 0.102260E+11 | 0.247528E+10 | 720.00 | 0.990440E+10 | 0.321654E+09 | 0.00 | 0.65 | 30-JUN-24:00 | 0.37 | 03-JUN-06:10 | 5456.20 | 30-JUN-24:00 | 5437.07 | 30-JUN-24:00 | 529.03 | 15-JUN-14:00 | 1622.19 | 19-JUN-12:05 | 0.00 |
July | 0.159292E+11 | 0.424946E+10 | 744.00 | 0.154494E+11 | 0.479791E+09 | 0.00 | 0.88 | 31-JUL-24:00 | 0.65 | 01-JUL-06:10 | 7438.49 | 31-JUL-24:00 | 7438.49 | 31-JUL-24:00 | 613.54 | 20-JUL-15:00 | 2088.12 | 07-JUL-12:10 | 0.00 |
August | 0.206280E+11 | 0.545126E+10 | 744.00 | 0.202529E+11 | 0.375056E+09 | 0.00 | 1.00 | 01-AUG-13:30 | 0.28 | 31-AUG-24:00 | 8594.69 | 31-AUG-17:50 | 8344.69 | 13-AUG-18:33 | 616.75 | 03-AUG-15:00 | 2656.21 | 24-AUG-15:43 | 0.00 |
September | 0.487870E+10 | 0.117353E+10 | 720.00 | 0.467944E+10 | 0.199260E+09 | 0.00 | 0.41 | 10-SEP-17:21 | 0.11 | 30-SEP-06:55 | 3286.72 | 30-SEP-23:20 | 3286.72 | 30-SEP-23:20 | 444.94 | 07-SEP-15:00 | 831.12 | 14-SEP-14:00 | 0.00 |
October | 0.856651E+10 | 0.183746E+10 | 744.00 | 0.841969E+10 | 0.146823E+09 | 0.00 | 0.56 | 04-OCT-16:30 | 0.24 | 28-OCT-06:10 | 4632.78 | 04-OCT-16:30 | 4487.23 | 15-OCT-16:32 | 348.81 | 24-OCT-16:00 | 1142.52 | 04-OCT-16:00 | 0.00 |
November | 0.102240E+11 | 0.212923E+10 | 720.00 | 0.102065E+11 | 17432997.20 | 0.00 | 0.67 | 03-NOV-16:00 | 0.28 | 24-NOV-04:27 | 5711.45 | 03-NOV-16:00 | 5711.45 | 03-NOV-16:00 | 263.44 | 10-NOV-10:20 | 1124.53 | 03-NOV-16:00 | 0.00 |
December | 0.141679E+11 | 0.296222E+10 | 744.00 | 0.141679E+11 | -0.0 | 0.00 | 0.84 | 21-DEC-16:10 | 0.45 | 31-DEC-23:42 | 6975.46 | 08-DEC-16:10 | 6975.46 | 08-DEC-16:10 | 0.00 | 26-DEC-03:10 | 1403.24 | 21-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.121044E+12 | 0.279537E+11 | 8169.62 | 0.119374E+12 | 0.167098E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.231906E+09 | 62442100.71 | 170.30 | 0.229866E+09 | -0.0 | 0.00 | 0.22 | 0.00 | 1631.64 | 1631.64 | 0.00 | 370.42 | 0.00 | ||||||
Maximum of Months | 0.206280E+11 | 0.545126E+10 | 744.00 | 0.202529E+11 | 0.479791E+09 | 0.00 | 1.00 | 0.65 | 8594.69 | 8344.69 | 616.75 | 2656.21 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 3.21 | 707.16 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.56 | 730.56 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 64.62 | 504.92 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 151.72 | 360.38 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.99 | 206.84 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 460.89 | 110.27 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 513.12 | 58.30 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 447.15 | 80.41 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 254.61 | 172.42 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 144.57 | 326.41 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 30.35 | 527.80 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.45 | 695.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 201.74 | 371.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.45 | 58.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 513.12 | 730.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 3.21 | 707.16 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.56 | 730.56 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 64.62 | 504.92 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 151.72 | 360.38 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.99 | 206.84 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 460.89 | 110.27 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 513.12 | 58.30 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 447.15 | 80.41 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 254.61 | 172.42 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 144.57 | 326.41 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 30.35 | 527.80 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.45 | 695.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 201.74 | 371.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.45 | 58.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 513.12 | 730.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 3.21 | 707.16 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.56 | 730.56 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 64.62 | 504.92 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 151.72 | 360.38 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.99 | 206.84 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 460.89 | 110.27 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 513.12 | 58.30 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 447.15 | 80.41 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 254.61 | 172.42 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 144.57 | 326.41 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 30.35 | 527.80 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.45 | 695.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 201.74 | 371.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.45 | 58.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 513.12 | 730.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 3.21 | 707.16 | 0.00 | 0.00 | 0.00 |
February | 159.28 | 0.00 | 159.28 | 9.56 | 730.56 | 0.00 | 0.00 | 0.00 |
March | 220.88 | 0.00 | 220.88 | 64.62 | 504.92 | 0.00 | 0.00 | 0.00 |
April | 265.31 | 0.75 | 264.55 | 151.72 | 360.38 | 0.00 | 0.00 | 0.00 |
May | 351.98 | 11.73 | 340.25 | 323.99 | 206.84 | 0.00 | 0.00 | 0.00 |
June | 373.27 | 20.06 | 353.21 | 460.89 | 110.27 | 0.00 | 0.00 | 0.00 |
July | 360.73 | 13.05 | 347.68 | 513.12 | 58.30 | 0.00 | 0.00 | 0.00 |
August | 319.59 | 3.80 | 315.79 | 447.15 | 80.41 | 0.00 | 0.00 | 0.00 |
September | 240.92 | 0.05 | 240.87 | 254.61 | 172.42 | 0.00 | 0.00 | 0.00 |
October | 208.50 | 0.00 | 208.50 | 144.57 | 326.41 | 0.00 | 0.00 | 0.00 |
November | 146.24 | 0.00 | 146.24 | 30.35 | 527.80 | 0.00 | 0.00 | 0.00 |
December | 101.53 | 0.00 | 101.53 | 1.45 | 695.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.18 | 4.14 | 235.04 | 201.74 | 371.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.53 | 0.00 | 101.53 | 1.45 | 58.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.27 | 20.06 | 353.21 | 513.12 | 730.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.39 | 0.00 | 116.39 | 3.21 | 707.13 | 0.00 | 0.00 | 0.00 |
February | 159.27 | 0.00 | 159.27 | 9.56 | 730.53 | 0.00 | 0.00 | 0.00 |
March | 220.87 | 0.00 | 220.87 | 64.62 | 504.90 | 0.00 | 0.00 | 0.00 |
April | 265.30 | 0.75 | 264.54 | 151.71 | 360.37 | 0.00 | 0.00 | 0.00 |
May | 351.97 | 11.73 | 340.24 | 323.98 | 206.83 | 0.00 | 0.00 | 0.00 |
June | 373.26 | 20.06 | 353.20 | 460.87 | 110.27 | 0.00 | 0.00 | 0.00 |
July | 360.72 | 13.04 | 347.67 | 513.10 | 58.29 | 0.00 | 0.00 | 0.00 |
August | 319.58 | 3.80 | 315.77 | 447.13 | 80.41 | 0.00 | 0.00 | 0.00 |
September | 240.91 | 0.05 | 240.86 | 254.60 | 172.41 | 0.00 | 0.00 | 0.00 |
October | 208.49 | 0.00 | 208.49 | 144.56 | 326.39 | 0.00 | 0.00 | 0.00 |
November | 146.23 | 0.00 | 146.23 | 30.35 | 527.78 | 0.00 | 0.00 | 0.00 |
December | 101.52 | 0.00 | 101.52 | 1.45 | 694.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.17 | 4.14 | 235.03 | 201.73 | 371.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.52 | 0.00 | 101.52 | 1.45 | 58.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.26 | 20.06 | 353.20 | 513.10 | 730.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.15 | 108.31 | 161.84 | 156.14 | 727.83 | 0.00 | 0.00 | 0.00 |
February | 418.94 | 195.44 | 223.50 | 279.68 | 727.46 | 0.00 | 0.00 | 0.00 |
March | 534.44 | 227.30 | 307.14 | 454.04 | 527.93 | 0.00 | 0.00 | 0.00 |
April | 641.36 | 280.94 | 360.43 | 638.95 | 374.21 | 0.00 | 0.00 | 0.00 |
May | 777.84 | 310.87 | 466.97 | 898.76 | 232.41 | 0.00 | 0.00 | 0.00 |
June | 720.89 | 260.96 | 459.93 | 944.09 | 122.21 | 0.00 | 0.00 | 0.00 |
July | 724.05 | 261.29 | 462.76 | 1029.61 | 61.79 | 0.00 | 0.00 | 0.00 |
August | 815.29 | 367.62 | 447.68 | 1152.92 | 84.37 | 0.00 | 0.00 | 0.00 |
September | 608.05 | 272.81 | 335.24 | 758.03 | 183.81 | 0.00 | 0.00 | 0.00 |
October | 551.24 | 249.84 | 301.40 | 605.21 | 345.39 | 0.00 | 0.00 | 0.00 |
November | 340.90 | 130.91 | 209.99 | 259.06 | 537.07 | 0.00 | 0.00 | 0.00 |
December | 265.58 | 124.70 | 140.88 | 167.86 | 693.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.61 | 232.84 | 323.77 | 614.34 | 382.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.58 | 108.31 | 140.88 | 156.14 | 61.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 815.29 | 367.62 | 466.97 | 1152.92 | 727.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.15 | 108.31 | 161.84 | 156.14 | 727.83 | 0.00 | 0.00 | 0.00 |
February | 418.94 | 195.44 | 223.50 | 279.68 | 727.46 | 0.00 | 0.00 | 0.00 |
March | 534.44 | 227.30 | 307.14 | 454.04 | 527.93 | 0.00 | 0.00 | 0.00 |
April | 641.36 | 280.94 | 360.43 | 638.95 | 374.21 | 0.00 | 0.00 | 0.00 |
May | 777.84 | 310.87 | 466.97 | 898.76 | 232.41 | 0.00 | 0.00 | 0.00 |
June | 720.89 | 260.96 | 459.93 | 944.09 | 122.21 | 0.00 | 0.00 | 0.00 |
July | 724.05 | 261.29 | 462.76 | 1029.61 | 61.79 | 0.00 | 0.00 | 0.00 |
August | 815.29 | 367.62 | 447.68 | 1152.92 | 84.37 | 0.00 | 0.00 | 0.00 |
September | 608.05 | 272.81 | 335.24 | 758.03 | 183.81 | 0.00 | 0.00 | 0.00 |
October | 551.24 | 249.84 | 301.40 | 605.21 | 345.39 | 0.00 | 0.00 | 0.00 |
November | 340.90 | 130.91 | 209.99 | 259.06 | 537.07 | 0.00 | 0.00 | 0.00 |
December | 265.58 | 124.70 | 140.88 | 167.86 | 693.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.61 | 232.84 | 323.77 | 614.34 | 382.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.58 | 108.31 | 140.88 | 156.14 | 61.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 815.29 | 367.62 | 466.97 | 1152.92 | 727.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.14 | 108.31 | 161.84 | 156.13 | 727.82 | 0.00 | 0.00 | 0.00 |
February | 418.93 | 195.43 | 223.50 | 279.68 | 727.44 | 0.00 | 0.00 | 0.00 |
March | 534.43 | 227.30 | 307.13 | 454.03 | 527.92 | 0.00 | 0.00 | 0.00 |
April | 641.35 | 280.93 | 360.42 | 638.94 | 374.20 | 0.00 | 0.00 | 0.00 |
May | 777.82 | 310.86 | 466.96 | 898.74 | 232.40 | 0.00 | 0.00 | 0.00 |
June | 720.88 | 260.95 | 459.92 | 944.08 | 122.20 | 0.00 | 0.00 | 0.00 |
July | 724.03 | 261.29 | 462.75 | 1029.59 | 61.79 | 0.00 | 0.00 | 0.00 |
August | 815.28 | 367.61 | 447.67 | 1152.90 | 84.37 | 0.00 | 0.00 | 0.00 |
September | 608.04 | 272.80 | 335.24 | 758.01 | 183.81 | 0.00 | 0.00 | 0.00 |
October | 551.23 | 249.84 | 301.40 | 605.20 | 345.39 | 0.00 | 0.00 | 0.00 |
November | 340.89 | 130.91 | 209.99 | 259.05 | 537.06 | 0.00 | 0.00 | 0.00 |
December | 265.58 | 124.70 | 140.88 | 167.86 | 693.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.60 | 232.84 | 323.76 | 614.33 | 382.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.58 | 108.31 | 140.88 | 156.13 | 61.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 815.28 | 367.61 | 466.96 | 1152.90 | 727.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 586.31 | 610.23 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 787.15 | 618.14 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.68 | 318.83 | 754.18 | 469.05 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 602.04 | 355.28 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 565.30 | 219.29 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 616.01 | 117.62 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 716.65 | 60.78 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 963.86 | 86.62 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 927.20 | 175.08 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1182.33 | 317.36 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 694.23 | 466.86 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 659.93 | 580.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 754.82 | 338.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 565.30 | 60.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1182.33 | 618.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 586.31 | 610.23 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 787.15 | 618.14 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.67 | 318.83 | 754.17 | 469.05 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 602.04 | 355.28 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 565.30 | 219.29 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 616.01 | 117.62 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 716.65 | 60.78 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 963.86 | 86.62 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 927.20 | 175.08 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1182.33 | 317.36 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 694.23 | 466.86 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 659.93 | 580.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 754.82 | 338.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 565.30 | 60.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1182.33 | 618.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 586.31 | 610.23 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 787.15 | 618.14 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.68 | 318.83 | 754.18 | 469.05 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 602.04 | 355.28 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 565.30 | 219.29 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 616.01 | 117.62 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 716.65 | 60.78 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 963.86 | 86.62 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 927.20 | 175.08 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1182.33 | 317.36 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 694.23 | 466.86 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 659.93 | 580.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 754.82 | 338.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 565.30 | 60.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1182.33 | 618.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.13 | 394.28 | 207.85 | 586.31 | 610.23 | 0.00 | 0.00 | 0.00 |
February | 794.19 | 525.69 | 268.50 | 787.15 | 618.14 | 0.00 | 0.00 | 0.00 |
March | 716.51 | 397.67 | 318.83 | 754.17 | 469.05 | 0.00 | 0.00 | 0.00 |
April | 555.99 | 219.85 | 336.13 | 602.04 | 355.28 | 0.00 | 0.00 | 0.00 |
May | 487.24 | 101.63 | 385.61 | 565.30 | 219.29 | 0.00 | 0.00 | 0.00 |
June | 457.26 | 69.90 | 387.36 | 616.01 | 117.62 | 0.00 | 0.00 | 0.00 |
July | 479.30 | 83.25 | 396.05 | 716.65 | 60.78 | 0.00 | 0.00 | 0.00 |
August | 640.05 | 237.41 | 402.65 | 963.86 | 86.62 | 0.00 | 0.00 | 0.00 |
September | 694.47 | 359.21 | 335.26 | 927.20 | 175.08 | 0.00 | 0.00 | 0.00 |
October | 951.36 | 596.57 | 354.79 | 1182.33 | 317.36 | 0.00 | 0.00 | 0.00 |
November | 659.69 | 396.17 | 263.51 | 694.23 | 466.86 | 0.00 | 0.00 | 0.00 |
December | 652.62 | 463.32 | 189.30 | 659.93 | 580.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.18 | 319.37 | 320.80 | 754.82 | 338.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.26 | 69.90 | 189.30 | 565.30 | 60.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.36 | 596.57 | 402.65 | 1182.33 | 618.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.11 | 394.26 | 207.84 | 586.29 | 610.20 | 0.00 | 0.00 | 0.00 |
February | 794.16 | 525.67 | 268.49 | 787.12 | 618.11 | 0.00 | 0.00 | 0.00 |
March | 716.48 | 397.66 | 318.82 | 754.15 | 469.03 | 0.00 | 0.00 | 0.00 |
April | 555.96 | 219.84 | 336.12 | 602.02 | 355.26 | 0.00 | 0.00 | 0.00 |
May | 487.22 | 101.63 | 385.59 | 565.28 | 219.28 | 0.00 | 0.00 | 0.00 |
June | 457.24 | 69.89 | 387.35 | 615.99 | 117.62 | 0.00 | 0.00 | 0.00 |
July | 479.28 | 83.25 | 396.03 | 716.62 | 60.78 | 0.00 | 0.00 | 0.00 |
August | 640.03 | 237.40 | 402.63 | 963.82 | 86.61 | 0.00 | 0.00 | 0.00 |
September | 694.44 | 359.19 | 335.25 | 927.16 | 175.07 | 0.00 | 0.00 | 0.00 |
October | 951.33 | 596.55 | 354.78 | 1182.29 | 317.35 | 0.00 | 0.00 | 0.00 |
November | 659.66 | 396.16 | 263.50 | 694.20 | 466.84 | 0.00 | 0.00 | 0.00 |
December | 652.59 | 463.30 | 189.30 | 659.91 | 580.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 640.15 | 319.36 | 320.79 | 754.79 | 338.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.24 | 69.89 | 189.30 | 565.28 | 60.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 951.33 | 596.55 | 402.63 | 1182.29 | 618.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 266.70 | 109.24 | 157.46 | 152.31 | 790.15 | 0.00 | 0.00 | 0.00 |
February | 393.28 | 172.73 | 220.55 | 252.20 | 821.66 | 0.00 | 0.00 | 0.00 |
March | 580.73 | 268.11 | 312.62 | 495.64 | 593.03 | 0.00 | 0.00 | 0.00 |
April | 634.71 | 271.58 | 363.13 | 616.56 | 451.83 | 0.00 | 0.00 | 0.00 |
May | 739.37 | 280.78 | 458.59 | 844.44 | 262.56 | 0.00 | 0.00 | 0.00 |
June | 809.22 | 326.38 | 482.84 | 1051.03 | 154.82 | 0.00 | 0.00 | 0.00 |
July | 757.88 | 285.39 | 472.48 | 1053.91 | 94.83 | 0.00 | 0.00 | 0.00 |
August | 838.42 | 388.13 | 450.29 | 1165.61 | 128.84 | 0.00 | 0.00 | 0.00 |
September | 595.21 | 260.11 | 335.10 | 739.88 | 214.94 | 0.00 | 0.00 | 0.00 |
October | 590.11 | 286.95 | 303.15 | 648.03 | 395.01 | 0.00 | 0.00 | 0.00 |
November | 277.11 | 80.09 | 197.02 | 164.56 | 626.33 | 0.00 | 0.00 | 0.00 |
December | 246.49 | 106.65 | 139.83 | 136.70 | 816.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.94 | 236.89 | 325.06 | 612.65 | 443.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.49 | 80.09 | 139.83 | 136.70 | 94.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.42 | 388.13 | 482.84 | 1165.61 | 821.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 266.70 | 109.24 | 157.46 | 152.31 | 790.15 | 0.00 | 0.00 | 0.00 |
February | 393.28 | 172.73 | 220.55 | 252.20 | 821.66 | 0.00 | 0.00 | 0.00 |
March | 580.73 | 268.11 | 312.62 | 495.64 | 593.03 | 0.00 | 0.00 | 0.00 |
April | 634.71 | 271.58 | 363.13 | 616.56 | 451.83 | 0.00 | 0.00 | 0.00 |
May | 739.37 | 280.78 | 458.59 | 844.44 | 262.56 | 0.00 | 0.00 | 0.00 |
June | 809.22 | 326.38 | 482.84 | 1051.03 | 154.82 | 0.00 | 0.00 | 0.00 |
July | 757.88 | 285.39 | 472.48 | 1053.91 | 94.83 | 0.00 | 0.00 | 0.00 |
August | 838.42 | 388.13 | 450.29 | 1165.61 | 128.84 | 0.00 | 0.00 | 0.00 |
September | 595.21 | 260.11 | 335.10 | 739.88 | 214.94 | 0.00 | 0.00 | 0.00 |
October | 590.11 | 286.95 | 303.15 | 648.03 | 395.01 | 0.00 | 0.00 | 0.00 |
November | 277.11 | 80.09 | 197.02 | 164.56 | 626.33 | 0.00 | 0.00 | 0.00 |
December | 246.49 | 106.65 | 139.83 | 136.70 | 816.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.94 | 236.89 | 325.06 | 612.65 | 443.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.49 | 80.09 | 139.83 | 136.70 | 94.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.42 | 388.13 | 482.84 | 1165.61 | 821.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 266.69 | 109.24 | 157.45 | 152.31 | 790.13 | 0.00 | 0.00 | 0.00 |
February | 393.27 | 172.73 | 220.55 | 252.19 | 821.65 | 0.00 | 0.00 | 0.00 |
March | 580.72 | 268.10 | 312.62 | 495.63 | 593.01 | 0.00 | 0.00 | 0.00 |
April | 634.70 | 271.57 | 363.13 | 616.55 | 451.82 | 0.00 | 0.00 | 0.00 |
May | 739.36 | 280.78 | 458.58 | 844.42 | 262.56 | 0.00 | 0.00 | 0.00 |
June | 809.20 | 326.37 | 482.83 | 1051.01 | 154.82 | 0.00 | 0.00 | 0.00 |
July | 757.86 | 285.39 | 472.47 | 1053.89 | 94.83 | 0.00 | 0.00 | 0.00 |
August | 838.40 | 388.12 | 450.28 | 1165.59 | 128.83 | 0.00 | 0.00 | 0.00 |
September | 595.20 | 260.10 | 335.10 | 739.86 | 214.94 | 0.00 | 0.00 | 0.00 |
October | 590.09 | 286.95 | 303.15 | 648.02 | 395.00 | 0.00 | 0.00 | 0.00 |
November | 277.11 | 80.09 | 197.02 | 164.55 | 626.32 | 0.00 | 0.00 | 0.00 |
December | 246.48 | 106.65 | 139.83 | 136.70 | 816.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.93 | 236.88 | 325.05 | 612.64 | 443.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.48 | 80.09 | 139.83 | 136.70 | 94.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.40 | 388.12 | 482.83 | 1165.59 | 821.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 581.96 | 0.00 | 581.96 | 40.70 | 3113.47 | 0.00 | 0.00 | 0.00 |
February | 796.39 | 0.00 | 796.39 | 78.12 | 3251.19 | 0.00 | 0.00 | 0.00 |
March | 1104.39 | 0.00 | 1104.39 | 402.10 | 2185.48 | 0.00 | 0.00 | 0.00 |
April | 1326.53 | 3.77 | 1322.76 | 839.96 | 1565.10 | 0.00 | 0.00 | 0.00 |
May | 1759.88 | 58.64 | 1701.24 | 1645.07 | 971.42 | 0.00 | 0.00 | 0.00 |
June | 1866.33 | 100.29 | 1766.05 | 2311.81 | 524.90 | 0.00 | 0.00 | 0.00 |
July | 1803.63 | 65.23 | 1738.40 | 2569.63 | 290.01 | 0.00 | 0.00 | 0.00 |
August | 1597.93 | 19.02 | 1578.91 | 2253.02 | 393.03 | 0.00 | 0.00 | 0.00 |
September | 1204.57 | 0.23 | 1204.35 | 1293.43 | 798.87 | 0.00 | 0.00 | 0.00 |
October | 1042.47 | 0.00 | 1042.47 | 775.20 | 1461.58 | 0.00 | 0.00 | 0.00 |
November | 731.19 | 0.00 | 731.19 | 208.01 | 2230.55 | 0.00 | 0.00 | 0.00 |
December | 507.63 | 0.00 | 507.63 | 24.49 | 2933.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1195.87 | 20.71 | 1175.16 | 1043.29 | 1633.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 507.63 | 0.00 | 507.63 | 24.49 | 290.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1866.33 | 100.29 | 1766.05 | 2569.63 | 3251.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 810.43 | 324.92 | 485.51 | 499.54 | 1938.20 | 0.00 | 0.00 | 0.00 |
February | 1256.81 | 586.30 | 670.51 | 872.51 | 1974.99 | 0.00 | 0.00 | 0.00 |
March | 1603.29 | 681.89 | 921.40 | 1377.75 | 1434.39 | 0.00 | 0.00 | 0.00 |
April | 1924.06 | 842.80 | 1081.26 | 1925.13 | 1035.22 | 0.00 | 0.00 | 0.00 |
May | 2333.49 | 932.60 | 1400.88 | 2674.06 | 672.53 | 0.00 | 0.00 | 0.00 |
June | 2162.65 | 782.86 | 1379.78 | 2805.50 | 364.83 | 0.00 | 0.00 | 0.00 |
July | 2172.12 | 783.86 | 1388.25 | 3057.80 | 202.25 | 0.00 | 0.00 | 0.00 |
August | 2445.85 | 1102.84 | 1343.02 | 3425.73 | 272.52 | 0.00 | 0.00 | 0.00 |
September | 1824.13 | 818.42 | 1005.72 | 2256.19 | 532.35 | 0.00 | 0.00 | 0.00 |
October | 1653.71 | 749.52 | 904.19 | 1815.52 | 972.17 | 0.00 | 0.00 | 0.00 |
November | 1022.69 | 392.72 | 629.97 | 807.94 | 1424.13 | 0.00 | 0.00 | 0.00 |
December | 796.74 | 374.10 | 422.64 | 531.50 | 1820.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.81 | 698.53 | 971.29 | 1844.14 | 1048.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 796.74 | 324.92 | 422.64 | 499.54 | 202.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2445.85 | 1102.84 | 1400.88 | 3425.73 | 1974.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3010.62 | 1971.37 | 1039.25 | 2945.92 | 2844.03 | 0.00 | 0.00 | 0.00 |
February | 3970.90 | 2628.41 | 1342.49 | 3936.53 | 2928.63 | 0.00 | 0.00 | 0.00 |
March | 3582.50 | 1988.35 | 1594.15 | 3766.59 | 2195.32 | 0.00 | 0.00 | 0.00 |
April | 2779.90 | 1099.25 | 1680.64 | 3018.38 | 1652.25 | 0.00 | 0.00 | 0.00 |
May | 2436.17 | 508.15 | 1928.02 | 2813.73 | 1057.18 | 0.00 | 0.00 | 0.00 |
June | 2286.27 | 349.48 | 1936.79 | 3067.59 | 567.36 | 0.00 | 0.00 | 0.00 |
July | 2396.47 | 416.27 | 1980.20 | 3571.34 | 303.55 | 0.00 | 0.00 | 0.00 |
August | 3200.22 | 1187.01 | 2013.20 | 4802.15 | 432.19 | 0.00 | 0.00 | 0.00 |
September | 3472.30 | 1796.02 | 1676.29 | 4606.71 | 851.67 | 0.00 | 0.00 | 0.00 |
October | 4756.76 | 2982.83 | 1773.93 | 5870.47 | 1538.22 | 0.00 | 0.00 | 0.00 |
November | 3298.41 | 1980.85 | 1317.56 | 3481.96 | 2168.15 | 0.00 | 0.00 | 0.00 |
December | 3263.06 | 2316.55 | 946.51 | 3314.27 | 2677.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3200.85 | 1596.85 | 1604.00 | 3767.34 | 1593.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2286.27 | 349.48 | 946.51 | 2813.73 | 303.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4756.76 | 2982.83 | 2013.20 | 5870.47 | 2928.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 800.08 | 327.71 | 472.36 | 490.77 | 2034.61 | 0.00 | 0.00 | 0.00 |
February | 1179.83 | 518.19 | 661.64 | 801.39 | 2112.48 | 0.00 | 0.00 | 0.00 |
March | 1742.16 | 804.31 | 937.85 | 1548.47 | 1480.36 | 0.00 | 0.00 | 0.00 |
April | 1904.10 | 814.72 | 1089.39 | 1918.05 | 1114.11 | 0.00 | 0.00 | 0.00 |
May | 2218.09 | 842.34 | 1375.74 | 2547.97 | 722.07 | 0.00 | 0.00 | 0.00 |
June | 2427.63 | 979.13 | 1448.50 | 3167.32 | 408.78 | 0.00 | 0.00 | 0.00 |
July | 2273.60 | 856.17 | 1417.44 | 3188.39 | 237.68 | 0.00 | 0.00 | 0.00 |
August | 2515.23 | 1164.38 | 1350.84 | 3535.12 | 319.03 | 0.00 | 0.00 | 0.00 |
September | 1785.61 | 780.31 | 1005.30 | 2234.79 | 579.05 | 0.00 | 0.00 | 0.00 |
October | 1770.30 | 860.85 | 909.45 | 1979.51 | 1039.30 | 0.00 | 0.00 | 0.00 |
November | 831.33 | 240.26 | 591.07 | 552.18 | 1501.88 | 0.00 | 0.00 | 0.00 |
December | 739.45 | 319.96 | 419.49 | 459.90 | 1931.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1685.81 | 710.66 | 975.16 | 1876.34 | 1117.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 739.45 | 240.26 | 419.49 | 459.90 | 237.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2515.23 | 1164.38 | 1448.50 | 3535.12 | 2112.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 581.96 | 0.00 | 581.96 | 46.77 | 2997.27 | 0.00 | 0.00 | 0.00 |
February | 796.39 | 0.00 | 796.39 | 90.65 | 3097.51 | 0.00 | 0.00 | 0.00 |
March | 1104.39 | 0.00 | 1104.39 | 430.20 | 2037.25 | 0.00 | 0.00 | 0.00 |
April | 1326.53 | 3.77 | 1322.76 | 876.32 | 1453.06 | 0.00 | 0.00 | 0.00 |
May | 1759.88 | 58.64 | 1701.24 | 1656.82 | 932.30 | 0.00 | 0.00 | 0.00 |
June | 1866.33 | 100.29 | 1766.05 | 2293.97 | 519.89 | 0.00 | 0.00 | 0.00 |
July | 1803.63 | 65.23 | 1738.40 | 2541.26 | 298.08 | 0.00 | 0.00 | 0.00 |
August | 1597.93 | 19.02 | 1578.91 | 2233.47 | 393.99 | 0.00 | 0.00 | 0.00 |
September | 1204.57 | 0.23 | 1204.35 | 1295.68 | 765.97 | 0.00 | 0.00 | 0.00 |
October | 1042.47 | 0.00 | 1042.47 | 815.76 | 1347.09 | 0.00 | 0.00 | 0.00 |
November | 731.19 | 0.00 | 731.19 | 245.33 | 2038.69 | 0.00 | 0.00 | 0.00 |
December | 507.63 | 0.00 | 507.63 | 36.38 | 2730.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1195.87 | 20.71 | 1175.16 | 1053.31 | 1542.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 507.63 | 0.00 | 507.63 | 36.38 | 298.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1866.33 | 100.29 | 1766.05 | 2541.26 | 3097.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 810.43 | 324.92 | 485.51 | 510.86 | 1865.74 | 0.00 | 0.00 | 0.00 |
February | 1256.81 | 586.30 | 670.51 | 898.02 | 1875.34 | 0.00 | 0.00 | 0.00 |
March | 1603.29 | 681.89 | 921.40 | 1406.09 | 1334.38 | 0.00 | 0.00 | 0.00 |
April | 1924.06 | 842.80 | 1081.26 | 1951.58 | 966.89 | 0.00 | 0.00 | 0.00 |
May | 2333.49 | 932.60 | 1400.88 | 2682.01 | 647.91 | 0.00 | 0.00 | 0.00 |
June | 2162.65 | 782.86 | 1379.78 | 2798.18 | 361.15 | 0.00 | 0.00 | 0.00 |
July | 2172.12 | 783.86 | 1388.25 | 3044.96 | 206.78 | 0.00 | 0.00 | 0.00 |
August | 2445.85 | 1102.84 | 1343.02 | 3416.34 | 272.54 | 0.00 | 0.00 | 0.00 |
September | 1824.13 | 818.42 | 1005.72 | 2260.27 | 512.58 | 0.00 | 0.00 | 0.00 |
October | 1653.71 | 749.52 | 904.19 | 1841.92 | 903.71 | 0.00 | 0.00 | 0.00 |
November | 1022.69 | 392.72 | 629.97 | 846.57 | 1299.48 | 0.00 | 0.00 | 0.00 |
December | 796.74 | 374.10 | 422.64 | 556.05 | 1687.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.81 | 698.53 | 971.29 | 1857.67 | 989.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 796.74 | 324.92 | 422.64 | 510.86 | 206.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2445.85 | 1102.84 | 1400.88 | 3416.34 | 1875.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3010.62 | 1971.37 | 1039.25 | 2964.57 | 2717.13 | 0.00 | 0.00 | 0.00 |
February | 3970.90 | 2628.41 | 1342.49 | 3972.44 | 2770.51 | 0.00 | 0.00 | 0.00 |
March | 3582.50 | 1988.35 | 1594.15 | 3794.75 | 2046.38 | 0.00 | 0.00 | 0.00 |
April | 2779.90 | 1099.25 | 1680.64 | 3046.22 | 1542.44 | 0.00 | 0.00 | 0.00 |
May | 2436.17 | 508.15 | 1928.02 | 2817.24 | 1015.51 | 0.00 | 0.00 | 0.00 |
June | 2286.27 | 349.48 | 1936.79 | 3047.50 | 561.94 | 0.00 | 0.00 | 0.00 |
July | 2396.47 | 416.27 | 1980.20 | 3541.67 | 311.36 | 0.00 | 0.00 | 0.00 |
August | 3200.22 | 1187.01 | 2013.20 | 4777.74 | 432.55 | 0.00 | 0.00 | 0.00 |
September | 3472.30 | 1796.02 | 1676.29 | 4601.68 | 821.91 | 0.00 | 0.00 | 0.00 |
October | 4756.76 | 2982.83 | 1773.93 | 5889.67 | 1442.41 | 0.00 | 0.00 | 0.00 |
November | 3298.41 | 1980.85 | 1317.56 | 3532.11 | 1987.49 | 0.00 | 0.00 | 0.00 |
December | 3263.06 | 2316.55 | 946.51 | 3358.17 | 2480.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3200.85 | 1596.85 | 1604.00 | 3779.49 | 1503.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2286.27 | 349.48 | 946.51 | 2817.24 | 311.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4756.76 | 2982.83 | 2013.20 | 5889.67 | 2770.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 800.08 | 327.71 | 472.36 | 497.09 | 1954.36 | 0.00 | 0.00 | 0.00 |
February | 1179.83 | 518.19 | 661.64 | 809.97 | 2020.67 | 0.00 | 0.00 | 0.00 |
March | 1742.16 | 804.31 | 937.85 | 1564.51 | 1391.31 | 0.00 | 0.00 | 0.00 |
April | 1904.10 | 814.72 | 1089.39 | 1933.54 | 1046.98 | 0.00 | 0.00 | 0.00 |
May | 2218.09 | 842.34 | 1375.74 | 2547.09 | 696.36 | 0.00 | 0.00 | 0.00 |
June | 2427.63 | 979.13 | 1448.50 | 3151.38 | 403.96 | 0.00 | 0.00 | 0.00 |
July | 2273.60 | 856.17 | 1417.44 | 3168.46 | 240.42 | 0.00 | 0.00 | 0.00 |
August | 2515.23 | 1164.38 | 1350.84 | 3518.96 | 318.30 | 0.00 | 0.00 | 0.00 |
September | 1785.61 | 780.31 | 1005.30 | 2231.33 | 560.00 | 0.00 | 0.00 | 0.00 |
October | 1770.30 | 860.85 | 909.45 | 1995.39 | 976.00 | 0.00 | 0.00 | 0.00 |
November | 831.33 | 240.26 | 591.07 | 575.88 | 1391.84 | 0.00 | 0.00 | 0.00 |
December | 739.45 | 319.96 | 419.49 | 472.59 | 1810.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1685.81 | 710.66 | 975.16 | 1879.81 | 1062.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 739.45 | 240.26 | 419.49 | 472.59 | 240.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2515.23 | 1164.38 | 1448.50 | 3518.96 | 2020.67 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311750E+09 | 0.00 | 0.311750E+09 | 8585236.30 | 0.189406E+10 |
February | 0.385331E+09 | 0.00 | 0.385331E+09 | 23125890.47 | 0.176737E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.173088E+09 | 0.135239E+10 |
April | 0.687681E+09 | 1955975.73 | 0.685725E+09 | 0.393253E+09 | 0.934107E+09 |
May | 0.942744E+09 | 31412772.00 | 0.911332E+09 | 0.867781E+09 | 0.554003E+09 |
June | 0.967518E+09 | 51988794.86 | 0.915529E+09 | 0.119463E+10 | 0.285824E+09 |
July | 0.966180E+09 | 34940286.43 | 0.931239E+09 | 0.137435E+10 | 0.156141E+09 |
August | 0.855989E+09 | 10187475.72 | 0.845802E+09 | 0.119765E+10 | 0.215381E+09 |
September | 0.624458E+09 | 116935.68 | 0.624341E+09 | 0.659950E+09 | 0.446907E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.387205E+09 | 0.874247E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 78664989.43 | 0.136806E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880091.72 | 0.186155E+10 |
Annual Sum or Average | 0.754268E+10 | 0.130602E+09 | 0.741208E+10 | 0.636216E+10 | 0.117100E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880091.72 | 0.156141E+09 |
Maximum of Months | 0.967518E+09 | 51988794.86 | 0.931239E+09 | 0.137435E+10 | 0.189406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311749E+09 | 0.00 | 0.311749E+09 | 8585172.73 | 0.189406E+10 |
February | 0.385330E+09 | 0.00 | 0.385330E+09 | 23125804.77 | 0.176737E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.173088E+09 | 0.135239E+10 |
April | 0.687680E+09 | 1955973.39 | 0.685724E+09 | 0.393253E+09 | 0.934107E+09 |
May | 0.942744E+09 | 31412734.31 | 0.911331E+09 | 0.867780E+09 | 0.554003E+09 |
June | 0.967517E+09 | 51988732.48 | 0.915528E+09 | 0.119463E+10 | 0.285824E+09 |
July | 0.966179E+09 | 34940244.51 | 0.931239E+09 | 0.137434E+10 | 0.156141E+09 |
August | 0.855988E+09 | 10187463.49 | 0.845801E+09 | 0.119765E+10 | 0.215381E+09 |
September | 0.624458E+09 | 116935.54 | 0.624341E+09 | 0.659949E+09 | 0.446907E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.387205E+09 | 0.874247E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 78664796.41 | 0.136806E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880063.27 | 0.186155E+10 |
Annual Sum or Average | 0.754267E+10 | 0.130602E+09 | 0.741207E+10 | 0.636215E+10 | 0.117100E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880063.27 | 0.156141E+09 |
Maximum of Months | 0.967517E+09 | 51988732.48 | 0.931239E+09 | 0.137434E+10 | 0.189406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311750E+09 | 0.00 | 0.311750E+09 | 8585236.30 | 0.189406E+10 |
February | 0.385331E+09 | 0.00 | 0.385331E+09 | 23125890.47 | 0.176737E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.173088E+09 | 0.135239E+10 |
April | 0.687681E+09 | 1955975.73 | 0.685725E+09 | 0.393253E+09 | 0.934107E+09 |
May | 0.942744E+09 | 31412772.00 | 0.911332E+09 | 0.867781E+09 | 0.554003E+09 |
June | 0.967518E+09 | 51988794.86 | 0.915529E+09 | 0.119463E+10 | 0.285824E+09 |
July | 0.966180E+09 | 34940286.43 | 0.931239E+09 | 0.137435E+10 | 0.156141E+09 |
August | 0.855989E+09 | 10187475.72 | 0.845802E+09 | 0.119765E+10 | 0.215381E+09 |
September | 0.624458E+09 | 116935.68 | 0.624341E+09 | 0.659950E+09 | 0.446907E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.387205E+09 | 0.874247E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 78664989.43 | 0.136806E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880091.72 | 0.186155E+10 |
Annual Sum or Average | 0.754268E+10 | 0.130602E+09 | 0.741208E+10 | 0.636216E+10 | 0.117100E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880091.72 | 0.156141E+09 |
Maximum of Months | 0.967518E+09 | 51988794.86 | 0.931239E+09 | 0.137435E+10 | 0.189406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311749E+09 | 0.00 | 0.311749E+09 | 8585172.73 | 0.189406E+10 |
February | 0.385330E+09 | 0.00 | 0.385330E+09 | 23125804.77 | 0.176737E+10 |
March | 0.591609E+09 | 0.00 | 0.591609E+09 | 0.173088E+09 | 0.135239E+10 |
April | 0.687680E+09 | 1955973.39 | 0.685724E+09 | 0.393253E+09 | 0.934107E+09 |
May | 0.942744E+09 | 31412734.31 | 0.911331E+09 | 0.867780E+09 | 0.554003E+09 |
June | 0.967517E+09 | 51988732.48 | 0.915528E+09 | 0.119463E+10 | 0.285824E+09 |
July | 0.966179E+09 | 34940244.51 | 0.931239E+09 | 0.137434E+10 | 0.156141E+09 |
August | 0.855988E+09 | 10187463.49 | 0.845801E+09 | 0.119765E+10 | 0.215381E+09 |
September | 0.624458E+09 | 116935.54 | 0.624341E+09 | 0.659949E+09 | 0.446907E+09 |
October | 0.558438E+09 | 0.00 | 0.558438E+09 | 0.387205E+09 | 0.874247E+09 |
November | 0.379055E+09 | 0.00 | 0.379055E+09 | 78664796.41 | 0.136806E+10 |
December | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880063.27 | 0.186155E+10 |
Annual Sum or Average | 0.754267E+10 | 0.130602E+09 | 0.741207E+10 | 0.636215E+10 | 0.117100E+11 |
Minimum of Months | 0.271928E+09 | 0.00 | 0.271928E+09 | 3880063.27 | 0.156141E+09 |
Maximum of Months | 0.967517E+09 | 51988732.48 | 0.931239E+09 | 0.137434E+10 | 0.189406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311737E+09 | 0.00 | 0.311737E+09 | 8584890.28 | 0.189399E+10 |
February | 0.385315E+09 | 0.00 | 0.385315E+09 | 23124958.39 | 0.176730E+10 |
March | 0.591585E+09 | 0.00 | 0.591585E+09 | 0.173081E+09 | 0.135233E+10 |
April | 0.687653E+09 | 1955896.90 | 0.685697E+09 | 0.393238E+09 | 0.934070E+09 |
May | 0.942706E+09 | 31411505.93 | 0.911295E+09 | 0.867746E+09 | 0.553980E+09 |
June | 0.967479E+09 | 51986699.49 | 0.915492E+09 | 0.119458E+10 | 0.285812E+09 |
July | 0.966141E+09 | 34938878.18 | 0.931202E+09 | 0.137429E+10 | 0.156134E+09 |
August | 0.855955E+09 | 10187065.12 | 0.845768E+09 | 0.119760E+10 | 0.215373E+09 |
September | 0.624433E+09 | 116930.97 | 0.624316E+09 | 0.659923E+09 | 0.446889E+09 |
October | 0.558415E+09 | 0.00 | 0.558415E+09 | 0.387190E+09 | 0.874211E+09 |
November | 0.379040E+09 | 0.00 | 0.379040E+09 | 78661818.88 | 0.136800E+10 |
December | 0.271917E+09 | 0.00 | 0.271917E+09 | 3879935.34 | 0.186147E+10 |
Annual Sum or Average | 0.754238E+10 | 0.130597E+09 | 0.741178E+10 | 0.636190E+10 | 0.117096E+11 |
Minimum of Months | 0.271917E+09 | 0.00 | 0.271917E+09 | 3879935.34 | 0.156134E+09 |
Maximum of Months | 0.967479E+09 | 51986699.49 | 0.931202E+09 | 0.137429E+10 | 0.189399E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723562E+09 | 0.290090E+09 | 0.433472E+09 | 0.418197E+09 | 0.194943E+10 |
February | 0.101350E+10 | 0.472798E+09 | 0.540701E+09 | 0.676611E+09 | 0.175986E+10 |
March | 0.143144E+10 | 0.608800E+09 | 0.822636E+09 | 0.121609E+10 | 0.141400E+10 |
April | 0.166241E+10 | 0.728186E+09 | 0.934222E+09 | 0.165617E+10 | 0.969947E+09 |
May | 0.208336E+10 | 0.832635E+09 | 0.125072E+10 | 0.240723E+10 | 0.622479E+09 |
June | 0.186855E+10 | 0.676401E+09 | 0.119215E+10 | 0.244709E+10 | 0.316759E+09 |
July | 0.193928E+10 | 0.699840E+09 | 0.123944E+10 | 0.275770E+10 | 0.165497E+09 |
August | 0.218368E+10 | 0.984622E+09 | 0.119906E+10 | 0.308798E+10 | 0.225977E+09 |
September | 0.157607E+10 | 0.707119E+09 | 0.868947E+09 | 0.196481E+10 | 0.476440E+09 |
October | 0.147645E+10 | 0.669176E+09 | 0.807272E+09 | 0.162100E+10 | 0.925105E+09 |
November | 0.883615E+09 | 0.339317E+09 | 0.544298E+09 | 0.671471E+09 | 0.139208E+10 |
December | 0.711333E+09 | 0.333998E+09 | 0.377334E+09 | 0.449598E+09 | 0.185740E+10 |
Annual Sum or Average | 0.175532E+11 | 0.734298E+10 | 0.102103E+11 | 0.193740E+11 | 0.120750E+11 |
Minimum of Months | 0.711333E+09 | 0.290090E+09 | 0.377334E+09 | 0.418197E+09 | 0.165497E+09 |
Maximum of Months | 0.218368E+10 | 0.984622E+09 | 0.125072E+10 | 0.308798E+10 | 0.194943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723562E+09 | 0.290090E+09 | 0.433472E+09 | 0.418197E+09 | 0.194943E+10 |
February | 0.101350E+10 | 0.472798E+09 | 0.540701E+09 | 0.676611E+09 | 0.175986E+10 |
March | 0.143144E+10 | 0.608800E+09 | 0.822636E+09 | 0.121609E+10 | 0.141400E+10 |
April | 0.166241E+10 | 0.728186E+09 | 0.934222E+09 | 0.165617E+10 | 0.969947E+09 |
May | 0.208336E+10 | 0.832635E+09 | 0.125072E+10 | 0.240723E+10 | 0.622479E+09 |
June | 0.186855E+10 | 0.676401E+09 | 0.119215E+10 | 0.244709E+10 | 0.316759E+09 |
July | 0.193928E+10 | 0.699840E+09 | 0.123944E+10 | 0.275770E+10 | 0.165497E+09 |
August | 0.218368E+10 | 0.984622E+09 | 0.119906E+10 | 0.308798E+10 | 0.225977E+09 |
September | 0.157607E+10 | 0.707119E+09 | 0.868947E+09 | 0.196481E+10 | 0.476440E+09 |
October | 0.147645E+10 | 0.669176E+09 | 0.807272E+09 | 0.162100E+10 | 0.925105E+09 |
November | 0.883615E+09 | 0.339317E+09 | 0.544298E+09 | 0.671471E+09 | 0.139208E+10 |
December | 0.711333E+09 | 0.333998E+09 | 0.377334E+09 | 0.449598E+09 | 0.185740E+10 |
Annual Sum or Average | 0.175532E+11 | 0.734298E+10 | 0.102103E+11 | 0.193740E+11 | 0.120750E+11 |
Minimum of Months | 0.711333E+09 | 0.290090E+09 | 0.377334E+09 | 0.418197E+09 | 0.165497E+09 |
Maximum of Months | 0.218368E+10 | 0.984622E+09 | 0.125072E+10 | 0.308798E+10 | 0.194943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723549E+09 | 0.290085E+09 | 0.433464E+09 | 0.418190E+09 | 0.194939E+10 |
February | 0.101348E+10 | 0.472789E+09 | 0.540691E+09 | 0.676599E+09 | 0.175983E+10 |
March | 0.143141E+10 | 0.608788E+09 | 0.822621E+09 | 0.121607E+10 | 0.141397E+10 |
April | 0.166238E+10 | 0.728173E+09 | 0.934205E+09 | 0.165614E+10 | 0.969930E+09 |
May | 0.208332E+10 | 0.832620E+09 | 0.125070E+10 | 0.240719E+10 | 0.622468E+09 |
June | 0.186851E+10 | 0.676388E+09 | 0.119212E+10 | 0.244705E+10 | 0.316753E+09 |
July | 0.193925E+10 | 0.699827E+09 | 0.123942E+10 | 0.275765E+10 | 0.165494E+09 |
August | 0.218364E+10 | 0.984604E+09 | 0.119904E+10 | 0.308792E+10 | 0.225973E+09 |
September | 0.157604E+10 | 0.707106E+09 | 0.868931E+09 | 0.196477E+10 | 0.476431E+09 |
October | 0.147642E+10 | 0.669164E+09 | 0.807257E+09 | 0.162097E+10 | 0.925088E+09 |
November | 0.883599E+09 | 0.339311E+09 | 0.544288E+09 | 0.671459E+09 | 0.139205E+10 |
December | 0.711320E+09 | 0.333992E+09 | 0.377327E+09 | 0.449590E+09 | 0.185737E+10 |
Annual Sum or Average | 0.175529E+11 | 0.734285E+10 | 0.102101E+11 | 0.193736E+11 | 0.120748E+11 |
Minimum of Months | 0.711320E+09 | 0.290085E+09 | 0.377327E+09 | 0.418190E+09 | 0.165494E+09 |
Maximum of Months | 0.218364E+10 | 0.984604E+09 | 0.125070E+10 | 0.308792E+10 | 0.194939E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556710E+09 | 0.157038E+10 | 0.163444E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649557E+09 | 0.190427E+10 | 0.149540E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853966E+09 | 0.201999E+10 | 0.125630E+10 |
April | 0.144112E+10 | 0.569860E+09 | 0.871255E+09 | 0.156049E+10 | 0.920882E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151411E+10 | 0.587334E+09 |
June | 0.118522E+10 | 0.181173E+09 | 0.100404E+10 | 0.159670E+10 | 0.304877E+09 |
July | 0.128376E+10 | 0.222988E+09 | 0.106077E+10 | 0.191948E+10 | 0.162806E+09 |
August | 0.171431E+10 | 0.635868E+09 | 0.107845E+10 | 0.258160E+10 | 0.231991E+09 |
September | 0.180006E+10 | 0.931067E+09 | 0.868997E+09 | 0.240330E+10 | 0.453811E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950270E+09 | 0.316676E+10 | 0.850022E+09 |
November | 0.170991E+10 | 0.102689E+10 | 0.683029E+09 | 0.179945E+10 | 0.121010E+10 |
December | 0.174798E+10 | 0.124095E+10 | 0.507030E+09 | 0.176757E+10 | 0.155506E+10 |
Annual Sum or Average | 0.201887E+11 | 0.100718E+11 | 0.101169E+11 | 0.238041E+11 | 0.106630E+11 |
Minimum of Months | 0.118522E+10 | 0.181173E+09 | 0.507030E+09 | 0.151411E+10 | 0.162806E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316676E+10 | 0.163444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556709E+09 | 0.157038E+10 | 0.163444E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649556E+09 | 0.190427E+10 | 0.149540E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853965E+09 | 0.201998E+10 | 0.125630E+10 |
April | 0.144111E+10 | 0.569860E+09 | 0.871254E+09 | 0.156049E+10 | 0.920882E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151411E+10 | 0.587334E+09 |
June | 0.118522E+10 | 0.181172E+09 | 0.100404E+10 | 0.159670E+10 | 0.304877E+09 |
July | 0.128375E+10 | 0.222988E+09 | 0.106077E+10 | 0.191948E+10 | 0.162806E+09 |
August | 0.171431E+10 | 0.635867E+09 | 0.107845E+10 | 0.258160E+10 | 0.231991E+09 |
September | 0.180006E+10 | 0.931066E+09 | 0.868996E+09 | 0.240330E+10 | 0.453811E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950269E+09 | 0.316676E+10 | 0.850022E+09 |
November | 0.170991E+10 | 0.102688E+10 | 0.683029E+09 | 0.179945E+10 | 0.121010E+10 |
December | 0.174797E+10 | 0.124095E+10 | 0.507029E+09 | 0.176757E+10 | 0.155506E+10 |
Annual Sum or Average | 0.201886E+11 | 0.100718E+11 | 0.101169E+11 | 0.238041E+11 | 0.106630E+11 |
Minimum of Months | 0.118522E+10 | 0.181172E+09 | 0.507029E+09 | 0.151411E+10 | 0.162806E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316676E+10 | 0.163444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556710E+09 | 0.157038E+10 | 0.163444E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649557E+09 | 0.190427E+10 | 0.149540E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853966E+09 | 0.201999E+10 | 0.125630E+10 |
April | 0.144112E+10 | 0.569860E+09 | 0.871255E+09 | 0.156049E+10 | 0.920882E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151411E+10 | 0.587334E+09 |
June | 0.118522E+10 | 0.181173E+09 | 0.100404E+10 | 0.159670E+10 | 0.304877E+09 |
July | 0.128376E+10 | 0.222988E+09 | 0.106077E+10 | 0.191948E+10 | 0.162806E+09 |
August | 0.171431E+10 | 0.635868E+09 | 0.107845E+10 | 0.258160E+10 | 0.231991E+09 |
September | 0.180006E+10 | 0.931067E+09 | 0.868997E+09 | 0.240330E+10 | 0.453811E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950270E+09 | 0.316676E+10 | 0.850022E+09 |
November | 0.170991E+10 | 0.102689E+10 | 0.683029E+09 | 0.179945E+10 | 0.121010E+10 |
December | 0.174798E+10 | 0.124095E+10 | 0.507030E+09 | 0.176757E+10 | 0.155506E+10 |
Annual Sum or Average | 0.201887E+11 | 0.100718E+11 | 0.101169E+11 | 0.238041E+11 | 0.106630E+11 |
Minimum of Months | 0.118522E+10 | 0.181173E+09 | 0.507030E+09 | 0.151411E+10 | 0.162806E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316676E+10 | 0.163444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161275E+10 | 0.105604E+10 | 0.556709E+09 | 0.157038E+10 | 0.163444E+10 |
February | 0.192130E+10 | 0.127175E+10 | 0.649556E+09 | 0.190427E+10 | 0.149540E+10 |
March | 0.191910E+10 | 0.106513E+10 | 0.853965E+09 | 0.201998E+10 | 0.125630E+10 |
April | 0.144111E+10 | 0.569860E+09 | 0.871254E+09 | 0.156049E+10 | 0.920882E+09 |
May | 0.130502E+10 | 0.272207E+09 | 0.103281E+10 | 0.151411E+10 | 0.587334E+09 |
June | 0.118522E+10 | 0.181172E+09 | 0.100404E+10 | 0.159670E+10 | 0.304877E+09 |
July | 0.128375E+10 | 0.222988E+09 | 0.106077E+10 | 0.191948E+10 | 0.162806E+09 |
August | 0.171431E+10 | 0.635867E+09 | 0.107845E+10 | 0.258160E+10 | 0.231991E+09 |
September | 0.180006E+10 | 0.931066E+09 | 0.868996E+09 | 0.240330E+10 | 0.453811E+09 |
October | 0.254813E+10 | 0.159786E+10 | 0.950269E+09 | 0.316676E+10 | 0.850022E+09 |
November | 0.170991E+10 | 0.102688E+10 | 0.683029E+09 | 0.179945E+10 | 0.121010E+10 |
December | 0.174797E+10 | 0.124095E+10 | 0.507029E+09 | 0.176757E+10 | 0.155506E+10 |
Annual Sum or Average | 0.201886E+11 | 0.100718E+11 | 0.101169E+11 | 0.238041E+11 | 0.106630E+11 |
Minimum of Months | 0.118522E+10 | 0.181172E+09 | 0.507029E+09 | 0.151411E+10 | 0.162806E+09 |
Maximum of Months | 0.254813E+10 | 0.159786E+10 | 0.107845E+10 | 0.316676E+10 | 0.163444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161268E+10 | 0.105600E+10 | 0.556687E+09 | 0.157032E+10 | 0.163437E+10 |
February | 0.192123E+10 | 0.127170E+10 | 0.649531E+09 | 0.190419E+10 | 0.149533E+10 |
March | 0.191902E+10 | 0.106509E+10 | 0.853931E+09 | 0.201990E+10 | 0.125625E+10 |
April | 0.144106E+10 | 0.569837E+09 | 0.871220E+09 | 0.156043E+10 | 0.920844E+09 |
May | 0.130497E+10 | 0.272196E+09 | 0.103277E+10 | 0.151405E+10 | 0.587310E+09 |
June | 0.118517E+10 | 0.181165E+09 | 0.100400E+10 | 0.159663E+10 | 0.304865E+09 |
July | 0.128370E+10 | 0.222979E+09 | 0.106073E+10 | 0.191941E+10 | 0.162800E+09 |
August | 0.171425E+10 | 0.635842E+09 | 0.107840E+10 | 0.258150E+10 | 0.231981E+09 |
September | 0.179999E+10 | 0.931029E+09 | 0.868962E+09 | 0.240321E+10 | 0.453793E+09 |
October | 0.254803E+10 | 0.159780E+10 | 0.950232E+09 | 0.316663E+10 | 0.849987E+09 |
November | 0.170985E+10 | 0.102684E+10 | 0.683002E+09 | 0.179938E+10 | 0.121005E+10 |
December | 0.174791E+10 | 0.124090E+10 | 0.507010E+09 | 0.176750E+10 | 0.155500E+10 |
Annual Sum or Average | 0.201878E+11 | 0.100714E+11 | 0.101165E+11 | 0.238031E+11 | 0.106626E+11 |
Minimum of Months | 0.118517E+10 | 0.181165E+09 | 0.507010E+09 | 0.151405E+10 | 0.162800E+09 |
Maximum of Months | 0.254803E+10 | 0.159780E+10 | 0.107840E+10 | 0.316663E+10 | 0.163437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.714317E+09 | 0.292586E+09 | 0.421730E+09 | 0.407941E+09 | 0.211633E+10 |
February | 0.951424E+09 | 0.417869E+09 | 0.533555E+09 | 0.610116E+09 | 0.198777E+10 |
March | 0.155542E+10 | 0.718094E+09 | 0.837324E+09 | 0.132752E+10 | 0.158836E+10 |
April | 0.164516E+10 | 0.703923E+09 | 0.941239E+09 | 0.159811E+10 | 0.117114E+10 |
May | 0.198033E+10 | 0.752052E+09 | 0.122828E+10 | 0.226175E+10 | 0.703243E+09 |
June | 0.209749E+10 | 0.845979E+09 | 0.125151E+10 | 0.272426E+10 | 0.401303E+09 |
July | 0.202990E+10 | 0.764396E+09 | 0.126550E+10 | 0.282280E+10 | 0.253985E+09 |
August | 0.224562E+10 | 0.103957E+10 | 0.120604E+10 | 0.312198E+10 | 0.345077E+09 |
September | 0.154278E+10 | 0.674193E+09 | 0.868590E+09 | 0.191776E+10 | 0.557131E+09 |
October | 0.158054E+10 | 0.768578E+09 | 0.811961E+09 | 0.173569E+10 | 0.105800E+10 |
November | 0.718273E+09 | 0.207586E+09 | 0.510687E+09 | 0.426528E+09 | 0.162344E+10 |
December | 0.660186E+09 | 0.285664E+09 | 0.374521E+09 | 0.366144E+09 | 0.218737E+10 |
Annual Sum or Average | 0.177214E+11 | 0.747049E+10 | 0.102509E+11 | 0.193206E+11 | 0.139932E+11 |
Minimum of Months | 0.660186E+09 | 0.207586E+09 | 0.374521E+09 | 0.366144E+09 | 0.253985E+09 |
Maximum of Months | 0.224562E+10 | 0.103957E+10 | 0.126550E+10 | 0.312198E+10 | 0.218737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.714317E+09 | 0.292586E+09 | 0.421730E+09 | 0.407941E+09 | 0.211633E+10 |
February | 0.951424E+09 | 0.417869E+09 | 0.533555E+09 | 0.610116E+09 | 0.198777E+10 |
March | 0.155542E+10 | 0.718094E+09 | 0.837324E+09 | 0.132752E+10 | 0.158836E+10 |
April | 0.164516E+10 | 0.703923E+09 | 0.941239E+09 | 0.159811E+10 | 0.117114E+10 |
May | 0.198033E+10 | 0.752052E+09 | 0.122828E+10 | 0.226175E+10 | 0.703243E+09 |
June | 0.209749E+10 | 0.845979E+09 | 0.125151E+10 | 0.272426E+10 | 0.401303E+09 |
July | 0.202990E+10 | 0.764396E+09 | 0.126550E+10 | 0.282280E+10 | 0.253985E+09 |
August | 0.224562E+10 | 0.103957E+10 | 0.120604E+10 | 0.312198E+10 | 0.345077E+09 |
September | 0.154278E+10 | 0.674193E+09 | 0.868590E+09 | 0.191776E+10 | 0.557131E+09 |
October | 0.158054E+10 | 0.768578E+09 | 0.811961E+09 | 0.173569E+10 | 0.105800E+10 |
November | 0.718273E+09 | 0.207586E+09 | 0.510687E+09 | 0.426528E+09 | 0.162344E+10 |
December | 0.660186E+09 | 0.285664E+09 | 0.374521E+09 | 0.366144E+09 | 0.218737E+10 |
Annual Sum or Average | 0.177214E+11 | 0.747049E+10 | 0.102509E+11 | 0.193206E+11 | 0.139932E+11 |
Minimum of Months | 0.660186E+09 | 0.207586E+09 | 0.374521E+09 | 0.366144E+09 | 0.253985E+09 |
Maximum of Months | 0.224562E+10 | 0.103957E+10 | 0.126550E+10 | 0.312198E+10 | 0.218737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.714304E+09 | 0.292581E+09 | 0.421723E+09 | 0.407934E+09 | 0.211629E+10 |
February | 0.951407E+09 | 0.417862E+09 | 0.533545E+09 | 0.610104E+09 | 0.198773E+10 |
March | 0.155539E+10 | 0.718081E+09 | 0.837309E+09 | 0.132749E+10 | 0.158833E+10 |
April | 0.164513E+10 | 0.703910E+09 | 0.941222E+09 | 0.159808E+10 | 0.117112E+10 |
May | 0.198029E+10 | 0.752038E+09 | 0.122825E+10 | 0.226170E+10 | 0.703230E+09 |
June | 0.209745E+10 | 0.845964E+09 | 0.125149E+10 | 0.272421E+10 | 0.401296E+09 |
July | 0.202986E+10 | 0.764382E+09 | 0.126548E+10 | 0.282275E+10 | 0.253980E+09 |
August | 0.224558E+10 | 0.103955E+10 | 0.120602E+10 | 0.312192E+10 | 0.345070E+09 |
September | 0.154275E+10 | 0.674180E+09 | 0.868575E+09 | 0.191772E+10 | 0.557120E+09 |
October | 0.158051E+10 | 0.768564E+09 | 0.811947E+09 | 0.173565E+10 | 0.105798E+10 |
November | 0.718260E+09 | 0.207582E+09 | 0.510678E+09 | 0.426520E+09 | 0.162341E+10 |
December | 0.660173E+09 | 0.285659E+09 | 0.374514E+09 | 0.366137E+09 | 0.218733E+10 |
Annual Sum or Average | 0.177211E+11 | 0.747036E+10 | 0.102508E+11 | 0.193202E+11 | 0.139929E+11 |
Minimum of Months | 0.660173E+09 | 0.207582E+09 | 0.374514E+09 | 0.366137E+09 | 0.253980E+09 |
Maximum of Months | 0.224558E+10 | 0.103955E+10 | 0.126548E+10 | 0.312192E+10 | 0.218733E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.109024E+09 | 0.833911E+10 |
February | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.188978E+09 | 0.786529E+10 |
March | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.107698E+10 | 0.585359E+10 |
April | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.217718E+10 | 0.405674E+10 |
May | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.440615E+10 | 0.260185E+10 |
June | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.599222E+10 | 0.136053E+10 |
July | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.688250E+10 | 0.776770E+09 |
August | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.603450E+10 | 0.105270E+10 |
September | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.335257E+10 | 0.207067E+10 |
October | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.207629E+10 | 0.391470E+10 |
November | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.539149E+09 | 0.578159E+10 |
December | 0.135963E+10 | 0.00 | 0.135963E+10 | 65598719.69 | 0.785601E+10 |
Annual Sum or Average | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.329011E+11 | 0.515295E+11 |
Minimum of Months | 0.135963E+10 | 0.00 | 0.135963E+10 | 65598719.69 | 0.776770E+09 |
Maximum of Months | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.688250E+10 | 0.833911E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.133796E+10 | 0.519127E+10 |
February | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.211077E+10 | 0.477789E+10 |
March | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.369018E+10 | 0.384186E+10 |
April | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.498994E+10 | 0.268329E+10 |
May | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.716221E+10 | 0.180130E+10 |
June | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.727186E+10 | 0.945651E+09 |
July | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.819000E+10 | 0.541715E+09 |
August | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.917547E+10 | 0.729906E+09 |
September | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.584804E+10 | 0.137984E+10 |
October | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.486268E+10 | 0.260387E+10 |
November | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.209419E+10 | 0.369135E+10 |
December | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.142358E+10 | 0.487708E+10 |
Annual Sum or Average | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.581569E+11 | 0.330650E+11 |
Minimum of Months | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.133796E+10 | 0.541715E+09 |
Maximum of Months | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.917547E+10 | 0.519127E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.789036E+10 | 0.761744E+10 |
February | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.952326E+10 | 0.708494E+10 |
March | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.100884E+11 | 0.587995E+10 |
April | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.782365E+10 | 0.428263E+10 |
May | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.753630E+10 | 0.283155E+10 |
June | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.795120E+10 | 0.147059E+10 |
July | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.956547E+10 | 0.813023E+09 |
August | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.128621E+11 | 0.115758E+10 |
September | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.119406E+11 | 0.220752E+10 |
October | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.157235E+11 | 0.411997E+10 |
November | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.902525E+10 | 0.561984E+10 |
December | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.887693E+10 | 0.717036E+10 |
Annual Sum or Average | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.118807E+12 | 0.502554E+11 |
Minimum of Months | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.753630E+10 | 0.813023E+09 |
Maximum of Months | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.157235E+11 | 0.761744E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.131449E+10 | 0.544951E+10 |
February | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.193873E+10 | 0.511051E+10 |
March | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.414742E+10 | 0.396500E+10 |
April | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.497159E+10 | 0.288778E+10 |
May | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.682448E+10 | 0.193398E+10 |
June | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.820970E+10 | 0.105955E+10 |
July | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.853978E+10 | 0.636603E+09 |
August | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.946847E+10 | 0.854484E+09 |
September | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.579258E+10 | 0.150091E+10 |
October | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.530191E+10 | 0.278367E+10 |
November | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.143124E+10 | 0.389286E+10 |
December | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.123178E+10 | 0.517215E+10 |
Annual Sum or Average | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.591722E+11 | 0.352470E+11 |
Minimum of Months | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.123178E+10 | 0.636603E+09 |
Maximum of Months | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.946847E+10 | 0.544951E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.125271E+09 | 0.802788E+10 |
February | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.219290E+09 | 0.749350E+10 |
March | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.115225E+10 | 0.545658E+10 |
April | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.227143E+10 | 0.376632E+10 |
May | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.443764E+10 | 0.249706E+10 |
June | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.594597E+10 | 0.134757E+10 |
July | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.680651E+10 | 0.798385E+09 |
August | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.598212E+10 | 0.105528E+10 |
September | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.335841E+10 | 0.198539E+10 |
October | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.218493E+10 | 0.360805E+10 |
November | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.635893E+09 | 0.528429E+10 |
December | 0.135963E+10 | 0.00 | 0.135963E+10 | 97449072.22 | 0.731295E+10 |
Annual Sum or Average | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.332172E+11 | 0.486333E+11 |
Minimum of Months | 0.135963E+10 | 0.00 | 0.135963E+10 | 97449072.22 | 0.798385E+09 |
Maximum of Months | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.680651E+10 | 0.802788E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.136830E+10 | 0.499719E+10 |
February | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.217250E+10 | 0.453683E+10 |
March | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.376607E+10 | 0.357401E+10 |
April | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.505851E+10 | 0.250617E+10 |
May | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.718349E+10 | 0.173535E+10 |
June | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.725288E+10 | 0.936105E+09 |
July | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.815562E+10 | 0.553834E+09 |
August | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.915033E+10 | 0.729982E+09 |
September | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.585861E+10 | 0.132861E+10 |
October | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.493340E+10 | 0.242051E+10 |
November | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.219432E+10 | 0.336826E+10 |
December | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.148934E+10 | 0.452042E+10 |
Annual Sum or Average | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.585834E+11 | 0.312073E+11 |
Minimum of Months | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.136830E+10 | 0.553834E+09 |
Maximum of Months | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.915033E+10 | 0.499719E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.794030E+10 | 0.727757E+10 |
February | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.961012E+10 | 0.670241E+10 |
March | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.101639E+11 | 0.548103E+10 |
April | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.789579E+10 | 0.399801E+10 |
May | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.754571E+10 | 0.271993E+10 |
June | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.789913E+10 | 0.145655E+10 |
July | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.948602E+10 | 0.833958E+09 |
August | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.127967E+11 | 0.115855E+10 |
September | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.119276E+11 | 0.213038E+10 |
October | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.157749E+11 | 0.386336E+10 |
November | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.915524E+10 | 0.515158E+10 |
December | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.899453E+10 | 0.664322E+10 |
Annual Sum or Average | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.119190E+12 | 0.474165E+11 |
Minimum of Months | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.754571E+10 | 0.833958E+09 |
Maximum of Months | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.157749E+11 | 0.727757E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.133140E+10 | 0.523455E+10 |
February | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.195948E+10 | 0.488840E+10 |
March | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.419038E+10 | 0.372648E+10 |
April | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.501175E+10 | 0.271377E+10 |
May | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.682213E+10 | 0.186513E+10 |
June | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.816838E+10 | 0.104707E+10 |
July | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.848641E+10 | 0.643933E+09 |
August | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.942519E+10 | 0.852525E+09 |
September | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.578362E+10 | 0.145152E+10 |
October | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.534446E+10 | 0.261412E+10 |
November | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.149269E+10 | 0.360765E+10 |
December | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.126578E+10 | 0.484850E+10 |
Annual Sum or Average | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.592817E+11 | 0.334936E+11 |
Minimum of Months | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.126578E+10 | 0.643933E+09 |
Maximum of Months | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.942519E+10 | 0.523455E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.03 | 3535.78 | 581.96 | 0.00 | 581.96 | 0.00 | 0.00 |
February | 47.80 | 3652.77 | 796.39 | 0.00 | 796.39 | 0.00 | 0.00 |
March | 323.12 | 2524.59 | 1104.40 | 0.00 | 1104.40 | 0.00 | 0.00 |
April | 758.58 | 1801.89 | 1326.53 | 3.77 | 1322.76 | 0.00 | 0.00 |
May | 1619.95 | 1034.20 | 1759.89 | 58.64 | 1701.25 | 0.00 | 0.00 |
June | 2304.43 | 551.35 | 1866.34 | 100.29 | 1766.05 | 0.00 | 0.00 |
July | 2565.59 | 291.48 | 1803.64 | 65.23 | 1738.41 | 0.00 | 0.00 |
August | 2235.74 | 402.07 | 1597.94 | 19.02 | 1578.92 | 0.00 | 0.00 |
September | 1273.04 | 862.08 | 1204.58 | 0.23 | 1204.35 | 0.00 | 0.00 |
October | 722.82 | 1632.02 | 1042.48 | 0.00 | 1042.48 | 0.00 | 0.00 |
November | 151.74 | 2638.98 | 731.20 | 0.00 | 731.20 | 0.00 | 0.00 |
December | 7.24 | 3475.08 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Annual Sum or Average | 1008.71 | 1856.60 | 1195.87 | 20.71 | 1175.17 | 0.00 | 0.00 |
Minimum of Months | 7.24 | 291.48 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Maximum of Months | 2565.59 | 3652.77 | 1866.34 | 100.29 | 1766.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 468.41 | 2183.49 | 810.44 | 324.92 | 485.52 | 0.00 | 0.00 |
February | 839.05 | 2182.36 | 1256.81 | 586.30 | 670.51 | 0.00 | 0.00 |
March | 1362.10 | 1583.77 | 1603.30 | 681.90 | 921.41 | 0.00 | 0.00 |
April | 1916.85 | 1122.62 | 1924.07 | 842.80 | 1081.27 | 0.00 | 0.00 |
May | 2696.26 | 697.22 | 2333.50 | 932.61 | 1400.89 | 0.00 | 0.00 |
June | 2832.27 | 366.62 | 2162.66 | 782.87 | 1379.79 | 0.00 | 0.00 |
July | 3088.81 | 185.37 | 2172.12 | 783.87 | 1388.26 | 0.00 | 0.00 |
August | 3458.73 | 253.11 | 2445.86 | 1102.84 | 1343.02 | 0.00 | 0.00 |
September | 2274.07 | 551.43 | 1824.14 | 818.42 | 1005.72 | 0.00 | 0.00 |
October | 1815.63 | 1036.18 | 1653.72 | 749.52 | 904.20 | 0.00 | 0.00 |
November | 777.16 | 1611.19 | 1022.70 | 392.73 | 629.97 | 0.00 | 0.00 |
December | 503.58 | 2080.41 | 796.74 | 374.10 | 422.64 | 0.00 | 0.00 |
Annual Sum or Average | 1843.02 | 1148.68 | 1669.82 | 698.53 | 971.29 | 0.00 | 0.00 |
Minimum of Months | 468.41 | 185.37 | 796.74 | 324.92 | 422.64 | 0.00 | 0.00 |
Maximum of Months | 3458.73 | 2183.49 | 2445.86 | 1102.84 | 1400.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2931.54 | 3051.12 | 3010.63 | 1971.38 | 1039.25 | 0.00 | 0.00 |
February | 3935.71 | 3090.66 | 3970.92 | 2628.42 | 1342.49 | 0.00 | 0.00 |
March | 3770.85 | 2345.22 | 3582.52 | 1988.36 | 1594.16 | 0.00 | 0.00 |
April | 3010.18 | 1776.38 | 2779.91 | 1099.26 | 1680.65 | 0.00 | 0.00 |
May | 2826.49 | 1096.42 | 2436.18 | 508.15 | 1928.03 | 0.00 | 0.00 |
June | 3080.02 | 588.11 | 2286.28 | 349.48 | 1936.80 | 0.00 | 0.00 |
July | 3583.24 | 303.92 | 2396.48 | 416.27 | 1980.21 | 0.00 | 0.00 |
August | 4819.26 | 433.07 | 3200.23 | 1187.02 | 2013.21 | 0.00 | 0.00 |
September | 4635.96 | 875.40 | 3472.32 | 1796.02 | 1676.29 | 0.00 | 0.00 |
October | 5911.61 | 1586.80 | 4756.78 | 2982.84 | 1773.94 | 0.00 | 0.00 |
November | 3471.13 | 2334.28 | 3298.42 | 1980.86 | 1317.56 | 0.00 | 0.00 |
December | 3299.64 | 2902.94 | 3263.07 | 2316.56 | 946.51 | 0.00 | 0.00 |
Annual Sum or Average | 3774.08 | 1690.60 | 3200.86 | 1596.86 | 1604.01 | 0.00 | 0.00 |
Minimum of Months | 2826.49 | 303.92 | 2286.28 | 349.48 | 946.51 | 0.00 | 0.00 |
Maximum of Months | 5911.61 | 3090.66 | 4756.78 | 2982.84 | 2013.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 456.92 | 2370.43 | 800.08 | 327.72 | 472.37 | 0.00 | 0.00 |
February | 756.59 | 2464.98 | 1179.83 | 518.19 | 661.65 | 0.00 | 0.00 |
March | 1486.91 | 1779.07 | 1742.17 | 804.31 | 937.86 | 0.00 | 0.00 |
April | 1849.66 | 1355.48 | 1904.11 | 814.72 | 1089.39 | 0.00 | 0.00 |
May | 2533.30 | 787.68 | 2218.10 | 842.35 | 1375.75 | 0.00 | 0.00 |
June | 3153.06 | 464.47 | 2427.64 | 979.14 | 1448.50 | 0.00 | 0.00 |
July | 3161.72 | 284.48 | 2273.61 | 856.17 | 1417.44 | 0.00 | 0.00 |
August | 3496.82 | 386.51 | 2515.24 | 1164.39 | 1350.85 | 0.00 | 0.00 |
September | 2219.61 | 644.82 | 1785.62 | 780.31 | 1005.31 | 0.00 | 0.00 |
October | 1944.08 | 1185.03 | 1770.31 | 860.86 | 909.45 | 0.00 | 0.00 |
November | 493.66 | 1878.97 | 831.33 | 240.26 | 591.07 | 0.00 | 0.00 |
December | 410.10 | 2450.00 | 739.45 | 319.96 | 419.49 | 0.00 | 0.00 |
Annual Sum or Average | 1837.94 | 1331.15 | 1685.82 | 710.66 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 410.10 | 284.48 | 739.45 | 240.26 | 419.49 | 0.00 | 0.00 |
Maximum of Months | 3496.82 | 2464.98 | 2515.24 | 1164.39 | 1448.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.70 | 3113.47 | 581.96 | 0.00 | 581.96 | 0.00 | 0.00 |
February | 78.12 | 3251.19 | 796.39 | 0.00 | 796.39 | 0.00 | 0.00 |
March | 402.10 | 2185.48 | 1104.39 | 0.00 | 1104.39 | 0.00 | 0.00 |
April | 839.96 | 1565.10 | 1326.53 | 3.77 | 1322.76 | 0.00 | 0.00 |
May | 1645.07 | 971.42 | 1759.88 | 58.64 | 1701.24 | 0.00 | 0.00 |
June | 2311.81 | 524.90 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
July | 2569.63 | 290.01 | 1803.63 | 65.23 | 1738.40 | 0.00 | 0.00 |
August | 2253.02 | 393.03 | 1597.93 | 19.02 | 1578.91 | 0.00 | 0.00 |
September | 1293.43 | 798.87 | 1204.57 | 0.23 | 1204.35 | 0.00 | 0.00 |
October | 775.20 | 1461.58 | 1042.47 | 0.00 | 1042.47 | 0.00 | 0.00 |
November | 208.01 | 2230.55 | 731.19 | 0.00 | 731.19 | 0.00 | 0.00 |
December | 24.49 | 2933.10 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Annual Sum or Average | 1043.29 | 1633.99 | 1195.87 | 20.71 | 1175.16 | 0.00 | 0.00 |
Minimum of Months | 24.49 | 290.01 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Maximum of Months | 2569.63 | 3251.19 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 499.54 | 1938.20 | 810.43 | 324.92 | 485.51 | 0.00 | 0.00 |
February | 872.51 | 1974.99 | 1256.81 | 586.30 | 670.51 | 0.00 | 0.00 |
March | 1377.75 | 1434.39 | 1603.29 | 681.89 | 921.40 | 0.00 | 0.00 |
April | 1925.13 | 1035.22 | 1924.06 | 842.80 | 1081.26 | 0.00 | 0.00 |
May | 2674.06 | 672.53 | 2333.49 | 932.60 | 1400.88 | 0.00 | 0.00 |
June | 2805.50 | 364.83 | 2162.65 | 782.86 | 1379.78 | 0.00 | 0.00 |
July | 3057.80 | 202.25 | 2172.12 | 783.86 | 1388.25 | 0.00 | 0.00 |
August | 3425.73 | 272.52 | 2445.85 | 1102.84 | 1343.02 | 0.00 | 0.00 |
September | 2256.19 | 532.35 | 1824.13 | 818.42 | 1005.72 | 0.00 | 0.00 |
October | 1815.52 | 972.17 | 1653.71 | 749.52 | 904.19 | 0.00 | 0.00 |
November | 807.94 | 1424.13 | 1022.69 | 392.72 | 629.97 | 0.00 | 0.00 |
December | 531.50 | 1820.89 | 796.74 | 374.10 | 422.64 | 0.00 | 0.00 |
Annual Sum or Average | 1844.14 | 1048.49 | 1669.81 | 698.53 | 971.29 | 0.00 | 0.00 |
Minimum of Months | 499.54 | 202.25 | 796.74 | 324.92 | 422.64 | 0.00 | 0.00 |
Maximum of Months | 3425.73 | 1974.99 | 2445.85 | 1102.84 | 1400.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2945.92 | 2844.03 | 3010.62 | 1971.37 | 1039.25 | 0.00 | 0.00 |
February | 3936.53 | 2928.63 | 3970.90 | 2628.41 | 1342.49 | 0.00 | 0.00 |
March | 3766.59 | 2195.32 | 3582.50 | 1988.35 | 1594.15 | 0.00 | 0.00 |
April | 3018.38 | 1652.25 | 2779.90 | 1099.25 | 1680.64 | 0.00 | 0.00 |
May | 2813.73 | 1057.18 | 2436.17 | 508.15 | 1928.02 | 0.00 | 0.00 |
June | 3067.59 | 567.36 | 2286.27 | 349.48 | 1936.79 | 0.00 | 0.00 |
July | 3571.34 | 303.55 | 2396.47 | 416.27 | 1980.20 | 0.00 | 0.00 |
August | 4802.15 | 432.19 | 3200.22 | 1187.01 | 2013.20 | 0.00 | 0.00 |
September | 4606.71 | 851.67 | 3472.30 | 1796.02 | 1676.29 | 0.00 | 0.00 |
October | 5870.47 | 1538.22 | 4756.76 | 2982.83 | 1773.93 | 0.00 | 0.00 |
November | 3481.96 | 2168.15 | 3298.41 | 1980.85 | 1317.56 | 0.00 | 0.00 |
December | 3314.27 | 2677.10 | 3263.06 | 2316.55 | 946.51 | 0.00 | 0.00 |
Annual Sum or Average | 3767.34 | 1593.59 | 3200.85 | 1596.85 | 1604.00 | 0.00 | 0.00 |
Minimum of Months | 2813.73 | 303.55 | 2286.27 | 349.48 | 946.51 | 0.00 | 0.00 |
Maximum of Months | 5870.47 | 2928.63 | 4756.76 | 2982.83 | 2013.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 490.77 | 2034.61 | 800.08 | 327.71 | 472.36 | 0.00 | 0.00 |
February | 801.39 | 2112.48 | 1179.83 | 518.19 | 661.64 | 0.00 | 0.00 |
March | 1548.47 | 1480.36 | 1742.16 | 804.31 | 937.85 | 0.00 | 0.00 |
April | 1918.05 | 1114.11 | 1904.10 | 814.72 | 1089.39 | 0.00 | 0.00 |
May | 2547.97 | 722.07 | 2218.09 | 842.34 | 1375.74 | 0.00 | 0.00 |
June | 3167.32 | 408.78 | 2427.63 | 979.13 | 1448.50 | 0.00 | 0.00 |
July | 3188.39 | 237.68 | 2273.60 | 856.17 | 1417.44 | 0.00 | 0.00 |
August | 3535.12 | 319.03 | 2515.23 | 1164.38 | 1350.84 | 0.00 | 0.00 |
September | 2234.79 | 579.05 | 1785.61 | 780.31 | 1005.30 | 0.00 | 0.00 |
October | 1979.51 | 1039.30 | 1770.30 | 860.85 | 909.45 | 0.00 | 0.00 |
November | 552.18 | 1501.88 | 831.33 | 240.26 | 591.07 | 0.00 | 0.00 |
December | 459.90 | 1931.06 | 739.45 | 319.96 | 419.49 | 0.00 | 0.00 |
Annual Sum or Average | 1876.34 | 1117.68 | 1685.81 | 710.66 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 459.90 | 237.68 | 739.45 | 240.26 | 419.49 | 0.00 | 0.00 |
Maximum of Months | 3535.12 | 2112.48 | 2515.23 | 1164.38 | 1448.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.77 | 2997.27 | 581.96 | 0.00 | 581.96 | 0.00 | 0.00 |
February | 90.65 | 3097.51 | 796.39 | 0.00 | 796.39 | 0.00 | 0.00 |
March | 430.20 | 2037.25 | 1104.39 | 0.00 | 1104.39 | 0.00 | 0.00 |
April | 876.32 | 1453.06 | 1326.53 | 3.77 | 1322.76 | 0.00 | 0.00 |
May | 1656.82 | 932.30 | 1759.88 | 58.64 | 1701.24 | 0.00 | 0.00 |
June | 2293.97 | 519.89 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
July | 2541.26 | 298.08 | 1803.63 | 65.23 | 1738.40 | 0.00 | 0.00 |
August | 2233.47 | 393.99 | 1597.93 | 19.02 | 1578.91 | 0.00 | 0.00 |
September | 1295.68 | 765.97 | 1204.57 | 0.23 | 1204.35 | 0.00 | 0.00 |
October | 815.76 | 1347.09 | 1042.47 | 0.00 | 1042.47 | 0.00 | 0.00 |
November | 245.33 | 2038.69 | 731.19 | 0.00 | 731.19 | 0.00 | 0.00 |
December | 36.38 | 2730.34 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Annual Sum or Average | 1053.31 | 1542.15 | 1195.87 | 20.71 | 1175.16 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 298.08 | 507.63 | 0.00 | 507.63 | 0.00 | 0.00 |
Maximum of Months | 2541.26 | 3097.51 | 1866.33 | 100.29 | 1766.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 510.86 | 1865.74 | 810.43 | 324.92 | 485.51 | 0.00 | 0.00 |
February | 898.02 | 1875.34 | 1256.81 | 586.30 | 670.51 | 0.00 | 0.00 |
March | 1406.09 | 1334.38 | 1603.29 | 681.89 | 921.40 | 0.00 | 0.00 |
April | 1951.58 | 966.89 | 1924.06 | 842.80 | 1081.26 | 0.00 | 0.00 |
May | 2682.01 | 647.91 | 2333.49 | 932.60 | 1400.88 | 0.00 | 0.00 |
June | 2798.18 | 361.15 | 2162.65 | 782.86 | 1379.78 | 0.00 | 0.00 |
July | 3044.96 | 206.78 | 2172.12 | 783.86 | 1388.25 | 0.00 | 0.00 |
August | 3416.34 | 272.54 | 2445.85 | 1102.84 | 1343.02 | 0.00 | 0.00 |
September | 2260.27 | 512.58 | 1824.13 | 818.42 | 1005.72 | 0.00 | 0.00 |
October | 1841.92 | 903.71 | 1653.71 | 749.52 | 904.19 | 0.00 | 0.00 |
November | 846.57 | 1299.48 | 1022.69 | 392.72 | 629.97 | 0.00 | 0.00 |
December | 556.05 | 1687.73 | 796.74 | 374.10 | 422.64 | 0.00 | 0.00 |
Annual Sum or Average | 1857.67 | 989.58 | 1669.81 | 698.53 | 971.29 | 0.00 | 0.00 |
Minimum of Months | 510.86 | 206.78 | 796.74 | 324.92 | 422.64 | 0.00 | 0.00 |
Maximum of Months | 3416.34 | 1875.34 | 2445.85 | 1102.84 | 1400.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2964.57 | 2717.13 | 3010.62 | 1971.37 | 1039.25 | 0.00 | 0.00 |
February | 3972.44 | 2770.51 | 3970.90 | 2628.41 | 1342.49 | 0.00 | 0.00 |
March | 3794.75 | 2046.38 | 3582.50 | 1988.35 | 1594.15 | 0.00 | 0.00 |
April | 3046.22 | 1542.44 | 2779.90 | 1099.25 | 1680.64 | 0.00 | 0.00 |
May | 2817.24 | 1015.51 | 2436.17 | 508.15 | 1928.02 | 0.00 | 0.00 |
June | 3047.50 | 561.94 | 2286.27 | 349.48 | 1936.79 | 0.00 | 0.00 |
July | 3541.67 | 311.36 | 2396.47 | 416.27 | 1980.20 | 0.00 | 0.00 |
August | 4777.74 | 432.55 | 3200.22 | 1187.01 | 2013.20 | 0.00 | 0.00 |
September | 4601.68 | 821.91 | 3472.30 | 1796.02 | 1676.29 | 0.00 | 0.00 |
October | 5889.67 | 1442.41 | 4756.76 | 2982.83 | 1773.93 | 0.00 | 0.00 |
November | 3532.11 | 1987.49 | 3298.41 | 1980.85 | 1317.56 | 0.00 | 0.00 |
December | 3358.17 | 2480.29 | 3263.06 | 2316.55 | 946.51 | 0.00 | 0.00 |
Annual Sum or Average | 3779.49 | 1503.57 | 3200.85 | 1596.85 | 1604.00 | 0.00 | 0.00 |
Minimum of Months | 2817.24 | 311.36 | 2286.27 | 349.48 | 946.51 | 0.00 | 0.00 |
Maximum of Months | 5889.67 | 2770.51 | 4756.76 | 2982.83 | 2013.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 497.09 | 1954.36 | 800.08 | 327.71 | 472.36 | 0.00 | 0.00 |
February | 809.97 | 2020.67 | 1179.83 | 518.19 | 661.64 | 0.00 | 0.00 |
March | 1564.51 | 1391.31 | 1742.16 | 804.31 | 937.85 | 0.00 | 0.00 |
April | 1933.54 | 1046.98 | 1904.10 | 814.72 | 1089.39 | 0.00 | 0.00 |
May | 2547.09 | 696.36 | 2218.09 | 842.34 | 1375.74 | 0.00 | 0.00 |
June | 3151.38 | 403.96 | 2427.63 | 979.13 | 1448.50 | 0.00 | 0.00 |
July | 3168.46 | 240.42 | 2273.60 | 856.17 | 1417.44 | 0.00 | 0.00 |
August | 3518.96 | 318.30 | 2515.23 | 1164.38 | 1350.84 | 0.00 | 0.00 |
September | 2231.33 | 560.00 | 1785.61 | 780.31 | 1005.30 | 0.00 | 0.00 |
October | 1995.39 | 976.00 | 1770.30 | 860.85 | 909.45 | 0.00 | 0.00 |
November | 575.88 | 1391.84 | 831.33 | 240.26 | 591.07 | 0.00 | 0.00 |
December | 472.59 | 1810.22 | 739.45 | 319.96 | 419.49 | 0.00 | 0.00 |
Annual Sum or Average | 1879.81 | 1062.08 | 1685.81 | 710.66 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 472.59 | 240.42 | 739.45 | 240.26 | 419.49 | 0.00 | 0.00 |
Maximum of Months | 3518.96 | 2020.67 | 2515.23 | 1164.38 | 1448.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 42925708.33 | 0.947024E+10 | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.00 | 0.00 |
February | 0.115628E+09 | 0.883678E+10 | 0.192664E+10 | 0.00 | 0.192664E+10 | 0.00 | 0.00 |
March | 0.865434E+09 | 0.676187E+10 | 0.295802E+10 | 0.00 | 0.295802E+10 | 0.00 | 0.00 |
April | 0.196625E+10 | 0.467050E+10 | 0.343837E+10 | 9779795.14 | 0.342859E+10 | 0.00 | 0.00 |
May | 0.433887E+10 | 0.276999E+10 | 0.471368E+10 | 0.157063E+09 | 0.455662E+10 | 0.00 | 0.00 |
June | 0.597309E+10 | 0.142911E+10 | 0.483755E+10 | 0.259942E+09 | 0.457761E+10 | 0.00 | 0.00 |
July | 0.687167E+10 | 0.780697E+09 | 0.483086E+10 | 0.174700E+09 | 0.465616E+10 | 0.00 | 0.00 |
August | 0.598821E+10 | 0.107690E+10 | 0.427991E+10 | 50936943.54 | 0.422897E+10 | 0.00 | 0.00 |
September | 0.329972E+10 | 0.223452E+10 | 0.312227E+10 | 584673.41 | 0.312168E+10 | 0.00 | 0.00 |
October | 0.193601E+10 | 0.437120E+10 | 0.279217E+10 | 0.00 | 0.279217E+10 | 0.00 | 0.00 |
November | 0.393321E+09 | 0.684024E+10 | 0.189526E+10 | 0.00 | 0.189526E+10 | 0.00 | 0.00 |
December | 19400245.31 | 0.930766E+10 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.318105E+11 | 0.585497E+11 | 0.377131E+11 | 0.653006E+09 | 0.370601E+11 | 0.00 | 0.00 |
Minimum of Months | 19400245.31 | 0.780697E+09 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.687167E+10 | 0.947024E+10 | 0.483755E+10 | 0.259942E+09 | 0.465616E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125458E+10 | 0.584826E+10 | 0.217067E+10 | 0.870265E+09 | 0.130041E+10 | 0.00 | 0.00 |
February | 0.202982E+10 | 0.527956E+10 | 0.304048E+10 | 0.141839E+10 | 0.162209E+10 | 0.00 | 0.00 |
March | 0.364824E+10 | 0.424196E+10 | 0.429428E+10 | 0.182639E+10 | 0.246789E+10 | 0.00 | 0.00 |
April | 0.496847E+10 | 0.290982E+10 | 0.498720E+10 | 0.218455E+10 | 0.280265E+10 | 0.00 | 0.00 |
May | 0.722166E+10 | 0.186743E+10 | 0.625004E+10 | 0.249789E+10 | 0.375215E+10 | 0.00 | 0.00 |
June | 0.734123E+10 | 0.950270E+09 | 0.560561E+10 | 0.202919E+10 | 0.357642E+10 | 0.00 | 0.00 |
July | 0.827306E+10 | 0.496488E+09 | 0.581782E+10 | 0.209951E+10 | 0.371831E+10 | 0.00 | 0.00 |
August | 0.926388E+10 | 0.677927E+09 | 0.655100E+10 | 0.295385E+10 | 0.359716E+10 | 0.00 | 0.00 |
September | 0.589439E+10 | 0.142931E+10 | 0.472817E+10 | 0.212134E+10 | 0.260682E+10 | 0.00 | 0.00 |
October | 0.486298E+10 | 0.277530E+10 | 0.442932E+10 | 0.200752E+10 | 0.242180E+10 | 0.00 | 0.00 |
November | 0.201440E+10 | 0.417621E+10 | 0.265083E+10 | 0.101795E+10 | 0.163288E+10 | 0.00 | 0.00 |
December | 0.134879E+10 | 0.557217E+10 | 0.213398E+10 | 0.100199E+10 | 0.113200E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.581215E+11 | 0.362247E+11 | 0.526594E+11 | 0.220288E+11 | 0.306306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125458E+10 | 0.496488E+09 | 0.213398E+10 | 0.870265E+09 | 0.113200E+10 | 0.00 | 0.00 |
Maximum of Months | 0.926388E+10 | 0.584826E+10 | 0.655100E+10 | 0.295385E+10 | 0.375215E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785183E+10 | 0.817213E+10 | 0.806367E+10 | 0.528014E+10 | 0.278353E+10 | 0.00 | 0.00 |
February | 0.952126E+10 | 0.747692E+10 | 0.960644E+10 | 0.635868E+10 | 0.324776E+10 | 0.00 | 0.00 |
March | 0.100998E+11 | 0.628144E+10 | 0.959541E+10 | 0.532562E+10 | 0.426979E+10 | 0.00 | 0.00 |
April | 0.780239E+10 | 0.460437E+10 | 0.720552E+10 | 0.284928E+10 | 0.435624E+10 | 0.00 | 0.00 |
May | 0.757048E+10 | 0.293665E+10 | 0.652505E+10 | 0.136102E+10 | 0.516403E+10 | 0.00 | 0.00 |
June | 0.798342E+10 | 0.152437E+10 | 0.592603E+10 | 0.905855E+09 | 0.502018E+10 | 0.00 | 0.00 |
July | 0.959734E+10 | 0.814024E+09 | 0.641873E+10 | 0.111493E+10 | 0.530380E+10 | 0.00 | 0.00 |
August | 0.129079E+11 | 0.115994E+10 | 0.857150E+10 | 0.317931E+10 | 0.539219E+10 | 0.00 | 0.00 |
September | 0.120164E+11 | 0.226904E+10 | 0.900024E+10 | 0.465529E+10 | 0.434495E+10 | 0.00 | 0.00 |
October | 0.158337E+11 | 0.425007E+10 | 0.127406E+11 | 0.798924E+10 | 0.475131E+10 | 0.00 | 0.00 |
November | 0.899716E+10 | 0.605047E+10 | 0.854950E+10 | 0.513438E+10 | 0.341512E+10 | 0.00 | 0.00 |
December | 0.883776E+10 | 0.777524E+10 | 0.873981E+10 | 0.620468E+10 | 0.253513E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.119019E+12 | 0.533147E+11 | 0.100942E+12 | 0.503584E+11 | 0.505840E+11 | 0.00 | 0.00 |
Minimum of Months | 0.757048E+10 | 0.814024E+09 | 0.592603E+10 | 0.905855E+09 | 0.253513E+10 | 0.00 | 0.00 |
Maximum of Months | 0.158337E+11 | 0.817213E+10 | 0.127406E+11 | 0.798924E+10 | 0.539219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122382E+10 | 0.634896E+10 | 0.214294E+10 | 0.877754E+09 | 0.126518E+10 | 0.00 | 0.00 |
February | 0.183034E+10 | 0.596328E+10 | 0.285425E+10 | 0.125360E+10 | 0.160065E+10 | 0.00 | 0.00 |
March | 0.398253E+10 | 0.476505E+10 | 0.466623E+10 | 0.215427E+10 | 0.251196E+10 | 0.00 | 0.00 |
April | 0.479431E+10 | 0.351340E+10 | 0.493545E+10 | 0.211175E+10 | 0.282370E+10 | 0.00 | 0.00 |
May | 0.678520E+10 | 0.210972E+10 | 0.594095E+10 | 0.225614E+10 | 0.368481E+10 | 0.00 | 0.00 |
June | 0.817274E+10 | 0.120390E+10 | 0.629244E+10 | 0.253792E+10 | 0.375452E+10 | 0.00 | 0.00 |
July | 0.846834E+10 | 0.761951E+09 | 0.608965E+10 | 0.229317E+10 | 0.379647E+10 | 0.00 | 0.00 |
August | 0.936587E+10 | 0.103522E+10 | 0.673681E+10 | 0.311870E+10 | 0.361811E+10 | 0.00 | 0.00 |
September | 0.575324E+10 | 0.167138E+10 | 0.462832E+10 | 0.202257E+10 | 0.260576E+10 | 0.00 | 0.00 |
October | 0.520703E+10 | 0.317397E+10 | 0.474159E+10 | 0.230572E+10 | 0.243587E+10 | 0.00 | 0.00 |
November | 0.127958E+10 | 0.487029E+10 | 0.215481E+10 | 0.622754E+09 | 0.153205E+10 | 0.00 | 0.00 |
December | 0.109842E+10 | 0.656207E+10 | 0.198054E+10 | 0.856988E+09 | 0.112356E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579614E+11 | 0.419792E+11 | 0.531640E+11 | 0.224113E+11 | 0.307526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109842E+10 | 0.761951E+09 | 0.198054E+10 | 0.622754E+09 | 0.112356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.936587E+10 | 0.656207E+10 | 0.673681E+10 | 0.311870E+10 | 0.379647E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109024E+09 | 0.833911E+10 | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.00 | 0.00 |
February | 0.188978E+09 | 0.786529E+10 | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.00 | 0.00 |
March | 0.107698E+10 | 0.585359E+10 | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.00 | 0.00 |
April | 0.217718E+10 | 0.405674E+10 | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.00 | 0.00 |
May | 0.440615E+10 | 0.260185E+10 | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.00 | 0.00 |
June | 0.599222E+10 | 0.136053E+10 | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.00 | 0.00 |
July | 0.688250E+10 | 0.776770E+09 | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.00 | 0.00 |
August | 0.603450E+10 | 0.105270E+10 | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.00 | 0.00 |
September | 0.335257E+10 | 0.207067E+10 | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.00 | 0.00 |
October | 0.207629E+10 | 0.391470E+10 | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.00 | 0.00 |
November | 0.539149E+09 | 0.578159E+10 | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.00 | 0.00 |
December | 65598719.69 | 0.785601E+10 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.329011E+11 | 0.515295E+11 | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.00 | 0.00 |
Minimum of Months | 65598719.69 | 0.776770E+09 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.688250E+10 | 0.833911E+10 | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133796E+10 | 0.519127E+10 | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.00 | 0.00 |
February | 0.211077E+10 | 0.477789E+10 | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.00 | 0.00 |
March | 0.369018E+10 | 0.384186E+10 | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.00 | 0.00 |
April | 0.498994E+10 | 0.268329E+10 | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.00 | 0.00 |
May | 0.716221E+10 | 0.180130E+10 | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.00 | 0.00 |
June | 0.727186E+10 | 0.945651E+09 | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.00 | 0.00 |
July | 0.819000E+10 | 0.541715E+09 | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.00 | 0.00 |
August | 0.917547E+10 | 0.729906E+09 | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.00 | 0.00 |
September | 0.584804E+10 | 0.137984E+10 | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.00 | 0.00 |
October | 0.486268E+10 | 0.260387E+10 | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.00 | 0.00 |
November | 0.209419E+10 | 0.369135E+10 | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.00 | 0.00 |
December | 0.142358E+10 | 0.487708E+10 | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.581569E+11 | 0.330650E+11 | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133796E+10 | 0.541715E+09 | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.00 | 0.00 |
Maximum of Months | 0.917547E+10 | 0.519127E+10 | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.789036E+10 | 0.761744E+10 | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.00 | 0.00 |
February | 0.952326E+10 | 0.708494E+10 | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.00 | 0.00 |
March | 0.100884E+11 | 0.587995E+10 | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.00 | 0.00 |
April | 0.782365E+10 | 0.428263E+10 | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.00 | 0.00 |
May | 0.753630E+10 | 0.283155E+10 | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.00 | 0.00 |
June | 0.795120E+10 | 0.147059E+10 | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.00 | 0.00 |
July | 0.956547E+10 | 0.813023E+09 | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.00 | 0.00 |
August | 0.128621E+11 | 0.115758E+10 | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.00 | 0.00 |
September | 0.119406E+11 | 0.220752E+10 | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.00 | 0.00 |
October | 0.157235E+11 | 0.411997E+10 | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.00 | 0.00 |
November | 0.902525E+10 | 0.561984E+10 | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.00 | 0.00 |
December | 0.887693E+10 | 0.717036E+10 | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118807E+12 | 0.502554E+11 | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.00 | 0.00 |
Minimum of Months | 0.753630E+10 | 0.813023E+09 | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.157235E+11 | 0.761744E+10 | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131449E+10 | 0.544951E+10 | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.00 | 0.00 |
February | 0.193873E+10 | 0.511051E+10 | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.00 | 0.00 |
March | 0.414742E+10 | 0.396500E+10 | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.00 | 0.00 |
April | 0.497159E+10 | 0.288778E+10 | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.00 | 0.00 |
May | 0.682448E+10 | 0.193398E+10 | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.00 | 0.00 |
June | 0.820970E+10 | 0.105955E+10 | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.00 | 0.00 |
July | 0.853978E+10 | 0.636603E+09 | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.00 | 0.00 |
August | 0.946847E+10 | 0.854484E+09 | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.00 | 0.00 |
September | 0.579258E+10 | 0.150091E+10 | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.00 | 0.00 |
October | 0.530191E+10 | 0.278367E+10 | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.00 | 0.00 |
November | 0.143124E+10 | 0.389286E+10 | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.00 | 0.00 |
December | 0.123178E+10 | 0.517215E+10 | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.591722E+11 | 0.352470E+11 | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123178E+10 | 0.636603E+09 | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.946847E+10 | 0.544951E+10 | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125271E+09 | 0.802788E+10 | 0.155873E+10 | 0.00 | 0.155873E+10 | 0.00 | 0.00 |
February | 0.219290E+09 | 0.749350E+10 | 0.192663E+10 | 0.00 | 0.192663E+10 | 0.00 | 0.00 |
March | 0.115225E+10 | 0.545658E+10 | 0.295801E+10 | 0.00 | 0.295801E+10 | 0.00 | 0.00 |
April | 0.227143E+10 | 0.376632E+10 | 0.343836E+10 | 9779760.41 | 0.342858E+10 | 0.00 | 0.00 |
May | 0.443764E+10 | 0.249706E+10 | 0.471366E+10 | 0.157062E+09 | 0.455660E+10 | 0.00 | 0.00 |
June | 0.594597E+10 | 0.134757E+10 | 0.483753E+10 | 0.259941E+09 | 0.457759E+10 | 0.00 | 0.00 |
July | 0.680651E+10 | 0.798385E+09 | 0.483084E+10 | 0.174699E+09 | 0.465614E+10 | 0.00 | 0.00 |
August | 0.598212E+10 | 0.105528E+10 | 0.427989E+10 | 50936762.66 | 0.422896E+10 | 0.00 | 0.00 |
September | 0.335841E+10 | 0.198539E+10 | 0.312225E+10 | 584671.33 | 0.312167E+10 | 0.00 | 0.00 |
October | 0.218493E+10 | 0.360805E+10 | 0.279216E+10 | 0.00 | 0.279216E+10 | 0.00 | 0.00 |
November | 0.635893E+09 | 0.528429E+10 | 0.189525E+10 | 0.00 | 0.189525E+10 | 0.00 | 0.00 |
December | 97449072.22 | 0.731295E+10 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.332172E+11 | 0.486333E+11 | 0.377129E+11 | 0.653003E+09 | 0.370599E+11 | 0.00 | 0.00 |
Minimum of Months | 97449072.22 | 0.798385E+09 | 0.135963E+10 | 0.00 | 0.135963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.680651E+10 | 0.802788E+10 | 0.483753E+10 | 0.259941E+09 | 0.465614E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136830E+10 | 0.499719E+10 | 0.217066E+10 | 0.870261E+09 | 0.130040E+10 | 0.00 | 0.00 |
February | 0.217250E+10 | 0.453683E+10 | 0.304047E+10 | 0.141838E+10 | 0.162209E+10 | 0.00 | 0.00 |
March | 0.376607E+10 | 0.357401E+10 | 0.429426E+10 | 0.182638E+10 | 0.246788E+10 | 0.00 | 0.00 |
April | 0.505851E+10 | 0.250617E+10 | 0.498717E+10 | 0.218454E+10 | 0.280264E+10 | 0.00 | 0.00 |
May | 0.718349E+10 | 0.173535E+10 | 0.625001E+10 | 0.249788E+10 | 0.375213E+10 | 0.00 | 0.00 |
June | 0.725288E+10 | 0.936105E+09 | 0.560558E+10 | 0.202918E+10 | 0.357640E+10 | 0.00 | 0.00 |
July | 0.815562E+10 | 0.553834E+09 | 0.581779E+10 | 0.209950E+10 | 0.371830E+10 | 0.00 | 0.00 |
August | 0.915033E+10 | 0.729982E+09 | 0.655098E+10 | 0.295384E+10 | 0.359714E+10 | 0.00 | 0.00 |
September | 0.585861E+10 | 0.132861E+10 | 0.472815E+10 | 0.212134E+10 | 0.260681E+10 | 0.00 | 0.00 |
October | 0.493340E+10 | 0.242051E+10 | 0.442930E+10 | 0.200751E+10 | 0.242179E+10 | 0.00 | 0.00 |
November | 0.219432E+10 | 0.336826E+10 | 0.265082E+10 | 0.101794E+10 | 0.163288E+10 | 0.00 | 0.00 |
December | 0.148934E+10 | 0.452042E+10 | 0.213398E+10 | 0.100198E+10 | 0.113199E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.585834E+11 | 0.312073E+11 | 0.526592E+11 | 0.220287E+11 | 0.306305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.136830E+10 | 0.553834E+09 | 0.213398E+10 | 0.870261E+09 | 0.113199E+10 | 0.00 | 0.00 |
Maximum of Months | 0.915033E+10 | 0.499719E+10 | 0.655098E+10 | 0.295384E+10 | 0.375213E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.794030E+10 | 0.727757E+10 | 0.806364E+10 | 0.528012E+10 | 0.278352E+10 | 0.00 | 0.00 |
February | 0.961012E+10 | 0.670241E+10 | 0.960641E+10 | 0.635866E+10 | 0.324775E+10 | 0.00 | 0.00 |
March | 0.101639E+11 | 0.548103E+10 | 0.959538E+10 | 0.532560E+10 | 0.426978E+10 | 0.00 | 0.00 |
April | 0.789579E+10 | 0.399801E+10 | 0.720549E+10 | 0.284927E+10 | 0.435622E+10 | 0.00 | 0.00 |
May | 0.754571E+10 | 0.271993E+10 | 0.652503E+10 | 0.136102E+10 | 0.516401E+10 | 0.00 | 0.00 |
June | 0.789913E+10 | 0.145655E+10 | 0.592601E+10 | 0.905852E+09 | 0.502016E+10 | 0.00 | 0.00 |
July | 0.948602E+10 | 0.833958E+09 | 0.641870E+10 | 0.111493E+10 | 0.530378E+10 | 0.00 | 0.00 |
August | 0.127967E+11 | 0.115855E+10 | 0.857147E+10 | 0.317930E+10 | 0.539217E+10 | 0.00 | 0.00 |
September | 0.119276E+11 | 0.213038E+10 | 0.900021E+10 | 0.465528E+10 | 0.434493E+10 | 0.00 | 0.00 |
October | 0.157749E+11 | 0.386336E+10 | 0.127405E+11 | 0.798922E+10 | 0.475129E+10 | 0.00 | 0.00 |
November | 0.915524E+10 | 0.515158E+10 | 0.854947E+10 | 0.513436E+10 | 0.341510E+10 | 0.00 | 0.00 |
December | 0.899453E+10 | 0.664322E+10 | 0.873978E+10 | 0.620466E+10 | 0.253512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.119190E+12 | 0.474165E+11 | 0.100942E+12 | 0.503583E+11 | 0.505838E+11 | 0.00 | 0.00 |
Minimum of Months | 0.754571E+10 | 0.833958E+09 | 0.592601E+10 | 0.905852E+09 | 0.253512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.157749E+11 | 0.727757E+10 | 0.127405E+11 | 0.798922E+10 | 0.539217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133140E+10 | 0.523455E+10 | 0.214293E+10 | 0.877750E+09 | 0.126518E+10 | 0.00 | 0.00 |
February | 0.195948E+10 | 0.488840E+10 | 0.285424E+10 | 0.125359E+10 | 0.160065E+10 | 0.00 | 0.00 |
March | 0.419038E+10 | 0.372648E+10 | 0.466621E+10 | 0.215426E+10 | 0.251195E+10 | 0.00 | 0.00 |
April | 0.501175E+10 | 0.271377E+10 | 0.493543E+10 | 0.211175E+10 | 0.282369E+10 | 0.00 | 0.00 |
May | 0.682213E+10 | 0.186513E+10 | 0.594092E+10 | 0.225613E+10 | 0.368479E+10 | 0.00 | 0.00 |
June | 0.816838E+10 | 0.104707E+10 | 0.629242E+10 | 0.253791E+10 | 0.375450E+10 | 0.00 | 0.00 |
July | 0.848641E+10 | 0.643933E+09 | 0.608962E+10 | 0.229317E+10 | 0.379646E+10 | 0.00 | 0.00 |
August | 0.942519E+10 | 0.852525E+09 | 0.673678E+10 | 0.311869E+10 | 0.361809E+10 | 0.00 | 0.00 |
September | 0.578362E+10 | 0.145152E+10 | 0.462830E+10 | 0.202256E+10 | 0.260574E+10 | 0.00 | 0.00 |
October | 0.534446E+10 | 0.261412E+10 | 0.474157E+10 | 0.230571E+10 | 0.243586E+10 | 0.00 | 0.00 |
November | 0.149269E+10 | 0.360765E+10 | 0.215480E+10 | 0.622752E+09 | 0.153205E+10 | 0.00 | 0.00 |
December | 0.126578E+10 | 0.484850E+10 | 0.198054E+10 | 0.856984E+09 | 0.112355E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.592817E+11 | 0.334936E+11 | 0.531638E+11 | 0.224112E+11 | 0.307525E+11 | 0.00 | 0.00 |
Minimum of Months | 0.126578E+10 | 0.643933E+09 | 0.198054E+10 | 0.622752E+09 | 0.112355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.942519E+10 | 0.523455E+10 | 0.673678E+10 | 0.311869E+10 | 0.379646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.399942E+11 | -0.389533E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104087E+10 | 58.97 | 0.00 | 0.00 |
February | 0.366884E+11 | -0.357525E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -935885599.3 | 58.97 | 0.00 | 0.00 |
March | 0.421347E+11 | -0.411037E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103096E+10 | 58.97 | 0.00 | 0.00 |
April | 0.363464E+11 | -0.353534E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992949668.9 | 58.98 | 0.00 | 0.00 |
May | 0.361698E+11 | -0.351436E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102621E+10 | 58.98 | 0.00 | 0.00 |
June | 0.332974E+11 | -0.323049E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992518593.8 | 58.98 | 0.00 | 0.00 |
July | 0.301098E+11 | -0.290898E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102003E+10 | 58.98 | 0.00 | 0.00 |
August | 0.324346E+11 | -0.314108E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102385E+10 | 58.98 | 0.00 | 0.00 |
September | 0.303824E+11 | -0.293940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988348621.3 | 58.97 | 0.00 | 0.00 |
October | 0.333557E+11 | -0.323362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101958E+10 | 58.97 | 0.00 | 0.00 |
November | 0.352088E+11 | -0.342195E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989265835.1 | 58.97 | 0.00 | 0.00 |
December | 0.374251E+11 | -0.364004E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102476E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.423547E+12 | -0.411462E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120852E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.301098E+11 | -0.411037E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.104087E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.421347E+11 | -0.290898E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -935885599.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6516.47 | 36.94 | 196.67 | 243.33 | 3351.63 | 33.73 | 200.17 | 196.83 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9267.66 | 37.81 | 211.17 | 259.50 | 2106.72 | 28.00 | 209.83 | 235.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3550.10 | 24.99 | 164.33 | 318.17 | 1572.98 | 22.61 | 217.50 | 285.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2114.75 | 20.62 | 97.83 | 341.17 | 1229.54 | 22.02 | 226.83 | 299.50 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1854.56 | 20.47 | 144.50 | 391.50 | 1028.75 | 21.84 | 278.17 | 348.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1773.70 | 20.45 | 129.67 | 384.33 | 998.65 | 21.87 | 268.33 | 341.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1951.98 | 20.72 | 163.17 | 391.50 | 1074.71 | 22.14 | 288.00 | 346.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2156.42 | 20.70 | 180.83 | 371.67 | 1230.92 | 22.09 | 298.00 | 340.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3832.95 | 22.85 | 156.33 | 325.00 | 1454.32 | 22.36 | 230.00 | 290.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10144.17 | 36.46 | 284.33 | 306.50 | 2014.31 | 24.31 | 271.67 | 288.17 |
November | 240.83 | 0.49 | 0.48 | 01-NOV-06:00 | 6467.15 | 36.72 | 236.67 | 257.50 | 2232.23 | 29.50 | 233.00 | 235.00 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6094.53 | 37.97 | 207.83 | 245.00 | 5368.24 | 39.14 | 212.67 | 214.50 |
Annual Sum or Average | 3472.67 | 0.50 | 4242.72 | 26.71 | 2173.33 | 3835.17 | 1780.89 | 24.89 | 2934.17 | 3421.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1773.70 | 20.45 | 97.83 | 243.33 | 998.65 | 21.84 | 200.17 | 196.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10144.17 | 37.97 | 284.33 | 391.50 | 5368.24 | 39.14 | 298.00 | 348.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2071.63 | 24.91 | 90.67 | 224.67 | 1130.67 | 24.88 | 121.00 | 160.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2855.67 | 25.87 | 96.00 | 247.17 | 1633.20 | 25.86 | 138.33 | 209.00 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:49 | 2969.68 | 23.64 | 94.00 | 314.67 | 1645.84 | 24.09 | 160.50 | 263.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3922.37 | 25.77 | 97.17 | 343.50 | 1567.53 | 24.60 | 171.67 | 305.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3232.23 | 23.57 | 103.33 | 397.67 | 1738.76 | 24.15 | 225.33 | 357.33 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2905.62 | 23.59 | 95.00 | 389.50 | 1607.09 | 24.40 | 220.33 | 355.33 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:49 | 2993.76 | 23.98 | 116.33 | 397.83 | 1612.03 | 24.62 | 258.00 | 360.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3974.05 | 25.41 | 143.17 | 374.83 | 1647.60 | 24.54 | 241.50 | 348.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3469.64 | 25.26 | 105.50 | 323.33 | 1502.20 | 24.40 | 179.67 | 287.83 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3074.77 | 25.37 | 142.17 | 295.50 | 1614.08 | 25.50 | 208.00 | 267.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2097.39 | 24.97 | 117.33 | 246.33 | 1073.19 | 24.74 | 153.00 | 202.50 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-07:30 | 1929.46 | 25.24 | 94.33 | 225.33 | 1106.63 | 25.18 | 113.00 | 161.17 |
Annual Sum or Average | 3472.67 | 0.50 | 3045.94 | 24.71 | 1295.00 | 3780.33 | 1525.14 | 24.69 | 2190.33 | 3279.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1929.46 | 23.57 | 90.67 | 224.67 | 1073.19 | 24.09 | 113.00 | 160.83 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 3974.05 | 25.87 | 143.17 | 397.83 | 1738.76 | 25.86 | 258.00 | 360.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-08:39 | 663.49 | 17.27 | 0.00 | 209.83 | 398.73 | 18.87 | 3.00 | 122.00 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 725.15 | 18.20 | 0.00 | 232.83 | 461.49 | 19.88 | 6.83 | 167.17 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 955.78 | 18.94 | 0.17 | 308.83 | 587.34 | 20.39 | 90.67 | 240.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1076.64 | 19.87 | 9.50 | 344.83 | 664.44 | 21.28 | 126.33 | 296.50 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1374.85 | 20.67 | 101.00 | 404.33 | 782.43 | 21.93 | 266.83 | 363.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1548.41 | 23.69 | 165.83 | 402.67 | 853.92 | 23.41 | 294.50 | 370.67 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1528.31 | 22.47 | 154.83 | 408.67 | 845.59 | 22.27 | 289.33 | 368.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1264.17 | 20.26 | 66.00 | 378.50 | 753.77 | 21.65 | 271.83 | 350.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 988.01 | 19.48 | 0.83 | 321.50 | 615.01 | 20.95 | 117.17 | 271.17 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 899.09 | 19.17 | 0.00 | 290.83 | 569.51 | 20.79 | 136.17 | 246.67 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:19 | 738.13 | 17.96 | 0.00 | 235.33 | 435.17 | 19.47 | 15.33 | 157.83 |
December | 211.17 | 0.55 | 0.48 | 01-DEC-08:39 | 537.50 | 16.36 | 0.00 | 200.83 | 332.30 | 18.09 | 0.17 | 94.33 |
Annual Sum or Average | 3472.67 | 0.51 | 1090.56 | 19.89 | 498.17 | 3739.00 | 642.83 | 21.03 | 1618.17 | 3049.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 537.50 | 16.36 | 0.00 | 200.83 | 332.30 | 18.09 | 0.17 | 94.33 | |
Maximum of Months | 389.17 | 0.55 | 0.48 | 1548.41 | 23.69 | 165.83 | 408.67 | 853.92 | 23.41 | 294.50 | 370.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:39 | 2006.30 | 25.13 | 89.67 | 231.50 | 1119.28 | 25.10 | 118.83 | 164.67 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-08:39 | 2268.45 | 24.81 | 93.17 | 247.00 | 1193.03 | 24.83 | 130.67 | 207.83 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3228.49 | 25.77 | 117.00 | 319.33 | 1805.64 | 26.00 | 182.83 | 275.17 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3698.33 | 24.31 | 83.00 | 342.33 | 1515.01 | 23.40 | 163.83 | 302.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3470.34 | 21.99 | 75.00 | 396.33 | 1531.87 | 21.31 | 209.00 | 360.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:49 | 3365.67 | 19.39 | 19.67 | 393.67 | 1809.63 | 21.52 | 209.50 | 354.83 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-05:49 | 3172.12 | 21.51 | 64.17 | 399.17 | 1687.44 | 21.60 | 236.00 | 359.00 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 4047.55 | 22.91 | 106.33 | 374.33 | 1753.72 | 21.68 | 220.83 | 347.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:30 | 3285.42 | 24.88 | 107.00 | 324.33 | 1706.96 | 24.97 | 179.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 3536.98 | 27.18 | 160.33 | 305.00 | 1496.52 | 25.80 | 223.33 | 278.17 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-07:30 | 1738.14 | 24.69 | 110.50 | 247.17 | 923.05 | 24.77 | 155.83 | 206.00 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-08:39 | 1628.67 | 24.74 | 90.33 | 224.00 | 894.55 | 24.52 | 117.00 | 165.83 |
Annual Sum or Average | 3472.67 | 0.50 | 3090.74 | 23.66 | 1116.17 | 3804.17 | 1507.17 | 23.50 | 2147.00 | 3308.17 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1628.67 | 19.39 | 19.67 | 224.00 | 894.55 | 21.31 | 117.00 | 164.67 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4047.55 | 27.18 | 160.33 | 399.17 | 1809.63 | 26.00 | 236.00 | 360.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6565.12 | 36.52 | 196.17 | 243.50 | 3470.15 | 31.82 | 144.00 | 199.50 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9332.01 | 37.32 | 210.00 | 259.83 | 2239.50 | 24.09 | 80.00 | 237.83 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3653.81 | 20.19 | 90.67 | 320.50 | 1688.13 | 18.23 | 22.67 | 289.33 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2161.66 | 14.43 | 0.00 | 341.17 | 1318.38 | 17.96 | 1.17 | 304.00 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1883.11 | 14.50 | 0.00 | 391.50 | 1097.06 | 17.89 | 0.00 | 353.67 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1801.20 | 14.49 | 0.00 | 384.67 | 1064.62 | 17.95 | 0.00 | 344.83 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1978.94 | 14.66 | 0.00 | 391.83 | 1144.83 | 18.11 | 0.00 | 350.83 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2197.90 | 14.74 | 0.00 | 371.83 | 1316.84 | 18.19 | 3.83 | 343.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3893.23 | 17.10 | 29.50 | 326.00 | 1561.48 | 18.04 | 4.67 | 293.33 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10219.96 | 35.69 | 283.50 | 307.67 | 2239.27 | 20.15 | 27.00 | 291.83 |
November | 240.83 | 0.49 | 0.48 | 01-NOV-06:49 | 6501.37 | 36.31 | 236.17 | 258.17 | 2778.68 | 29.03 | 144.17 | 238.67 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6153.49 | 37.56 | 207.67 | 245.50 | 5485.28 | 38.83 | 207.83 | 218.33 |
Annual Sum or Average | 3472.67 | 0.50 | 4292.17 | 22.66 | 1253.67 | 3842.17 | 1916.37 | 21.43 | 635.33 | 3465.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1801.20 | 14.43 | 0.00 | 243.50 | 1064.62 | 17.89 | 0.00 | 199.50 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10219.96 | 37.56 | 283.50 | 391.83 | 5485.28 | 38.83 | 207.83 | 353.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2103.61 | 22.61 | 72.83 | 226.17 | 1175.88 | 23.15 | 68.33 | 164.67 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2898.17 | 23.51 | 80.67 | 248.83 | 1690.74 | 24.07 | 60.00 | 213.33 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:49 | 3031.30 | 20.75 | 71.50 | 315.17 | 1716.12 | 21.86 | 51.67 | 271.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3982.58 | 23.07 | 92.67 | 344.67 | 1646.72 | 22.13 | 50.17 | 308.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3272.76 | 20.46 | 99.50 | 398.00 | 1815.56 | 21.69 | 72.83 | 361.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2949.83 | 20.40 | 88.50 | 390.33 | 1681.26 | 21.97 | 68.83 | 358.17 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:49 | 3030.83 | 20.33 | 89.67 | 399.00 | 1688.55 | 22.18 | 70.00 | 363.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 4022.65 | 22.54 | 128.17 | 375.17 | 1727.62 | 22.08 | 70.50 | 351.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3509.49 | 21.50 | 82.67 | 324.17 | 1577.27 | 21.98 | 48.50 | 292.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3120.89 | 22.48 | 91.17 | 296.33 | 1683.68 | 23.50 | 74.00 | 272.50 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2116.32 | 21.45 | 73.33 | 247.17 | 1123.19 | 22.81 | 75.00 | 206.33 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-07:30 | 1958.74 | 23.02 | 82.83 | 226.00 | 1146.82 | 23.59 | 79.00 | 166.83 |
Annual Sum or Average | 3472.67 | 0.50 | 3088.42 | 21.69 | 1053.50 | 3791.00 | 1593.79 | 22.47 | 788.83 | 3330.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1958.74 | 20.33 | 71.50 | 226.00 | 1123.19 | 21.69 | 48.50 | 164.67 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4022.65 | 23.51 | 128.17 | 399.00 | 1815.56 | 24.07 | 79.00 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-08:30 | 671.65 | 11.60 | 0.00 | 210.17 | 423.72 | 15.13 | 0.00 | 132.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 736.57 | 12.67 | 0.00 | 233.67 | 491.33 | 16.37 | 0.00 | 177.17 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 972.29 | 13.62 | 0.00 | 309.00 | 625.65 | 17.07 | 0.00 | 250.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1098.08 | 14.57 | 0.00 | 345.17 | 708.64 | 18.08 | 0.00 | 303.00 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 1398.39 | 15.04 | 3.17 | 404.50 | 833.96 | 18.46 | 10.83 | 369.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-04:00 | 1575.90 | 19.17 | 73.00 | 402.67 | 918.42 | 21.16 | 51.83 | 375.67 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1554.29 | 17.45 | 41.33 | 408.83 | 908.77 | 20.65 | 46.17 | 376.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1287.99 | 14.98 | 0.00 | 378.50 | 803.56 | 18.44 | 3.50 | 354.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 1006.59 | 14.22 | 0.00 | 321.67 | 655.54 | 17.73 | 0.00 | 277.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 913.08 | 13.93 | 0.00 | 291.17 | 606.32 | 17.48 | 0.00 | 252.00 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:19 | 747.59 | 12.16 | 0.00 | 235.67 | 462.39 | 15.68 | 0.00 | 166.50 |
December | 211.17 | 0.55 | 0.48 | 01-DEC-08:30 | 543.95 | 10.49 | 0.00 | 201.33 | 353.15 | 14.19 | 0.00 | 103.33 |
Annual Sum or Average | 3472.67 | 0.50 | 1109.18 | 14.57 | 117.50 | 3742.33 | 686.49 | 17.90 | 112.33 | 3136.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 543.95 | 10.49 | 0.00 | 201.33 | 353.15 | 14.19 | 0.00 | 103.33 | |
Maximum of Months | 389.17 | 0.55 | 0.48 | 1575.90 | 19.17 | 73.00 | 408.83 | 918.42 | 21.16 | 51.83 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:30 | 2037.12 | 22.87 | 73.33 | 232.33 | 1162.98 | 23.43 | 65.83 | 170.00 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-08:39 | 2279.05 | 20.90 | 57.00 | 247.83 | 1250.27 | 22.84 | 45.17 | 213.00 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:19 | 3292.31 | 23.14 | 95.83 | 320.83 | 1878.74 | 24.00 | 74.83 | 283.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3756.97 | 21.31 | 76.83 | 343.17 | 1593.57 | 20.73 | 37.00 | 306.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3510.82 | 18.43 | 69.17 | 397.33 | 1606.29 | 18.04 | 0.00 | 364.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:49 | 3402.51 | 14.80 | 1.83 | 394.17 | 1893.52 | 18.18 | 0.00 | 360.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-05:49 | 3209.65 | 17.66 | 49.00 | 399.83 | 1766.88 | 18.33 | 0.00 | 362.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 4102.31 | 19.58 | 86.33 | 374.50 | 1835.50 | 18.51 | 8.50 | 351.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:30 | 3333.55 | 21.79 | 85.33 | 324.83 | 1780.67 | 22.70 | 61.67 | 291.17 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 3574.67 | 23.93 | 111.83 | 305.17 | 1568.63 | 23.75 | 70.67 | 282.00 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-07:19 | 1764.67 | 22.04 | 79.67 | 248.33 | 965.30 | 22.95 | 70.67 | 212.17 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-08:30 | 1622.90 | 20.94 | 68.50 | 224.33 | 933.34 | 22.88 | 67.00 | 171.50 |
Annual Sum or Average | 3472.67 | 0.50 | 3129.55 | 20.27 | 854.67 | 3812.67 | 1576.61 | 20.94 | 501.33 | 3369.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1622.90 | 14.80 | 1.83 | 224.33 | 933.34 | 18.04 | 0.00 | 170.00 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4102.31 | 23.93 | 111.83 | 399.83 | 1893.52 | 24.00 | 74.83 | 364.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6566.78 | 36.52 | 196.17 | 243.50 | 3472.65 | 31.81 | 144.00 | 199.67 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9334.04 | 37.31 | 210.00 | 260.00 | 2242.05 | 24.08 | 80.00 | 238.00 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3657.09 | 20.16 | 90.67 | 320.50 | 1690.50 | 18.21 | 22.00 | 289.33 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2164.50 | 14.40 | 0.00 | 341.17 | 1320.20 | 17.95 | 1.17 | 304.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1885.82 | 14.47 | 0.00 | 391.67 | 1098.74 | 17.88 | 0.00 | 354.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1803.67 | 14.46 | 0.00 | 384.67 | 1066.18 | 17.94 | 0.00 | 344.83 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1981.83 | 14.63 | 0.00 | 391.83 | 1146.60 | 18.10 | 0.00 | 350.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:00 | 2200.87 | 14.71 | 0.00 | 371.83 | 1318.72 | 18.17 | 3.67 | 343.67 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3896.46 | 17.07 | 29.50 | 326.00 | 1563.63 | 18.03 | 4.67 | 293.50 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10223.06 | 35.68 | 283.50 | 307.67 | 2242.25 | 20.13 | 26.83 | 291.83 |
November | 240.83 | 0.49 | 0.48 | 01-NOV-06:49 | 6503.38 | 36.30 | 236.17 | 258.33 | 2781.45 | 29.02 | 144.17 | 238.67 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6154.29 | 37.55 | 207.67 | 245.67 | 5487.32 | 38.82 | 207.83 | 218.33 |
Annual Sum or Average | 3472.67 | 0.50 | 4294.76 | 22.64 | 1253.67 | 3842.83 | 1918.49 | 21.42 | 634.33 | 3467.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1803.67 | 14.40 | 0.00 | 243.50 | 1066.18 | 17.88 | 0.00 | 199.67 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10223.06 | 37.55 | 283.50 | 391.83 | 5487.32 | 38.82 | 207.83 | 354.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2104.60 | 22.59 | 72.83 | 226.17 | 1177.02 | 23.13 | 68.00 | 164.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2899.11 | 23.49 | 80.67 | 249.00 | 1691.96 | 24.06 | 59.83 | 213.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:49 | 3032.66 | 20.72 | 71.50 | 315.17 | 1717.70 | 21.85 | 51.67 | 271.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3984.28 | 23.05 | 92.67 | 344.67 | 1648.33 | 22.11 | 50.17 | 308.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3275.05 | 20.44 | 99.50 | 398.00 | 1817.46 | 21.68 | 72.83 | 361.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2951.96 | 20.37 | 88.50 | 390.33 | 1683.00 | 21.96 | 68.83 | 358.17 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:49 | 3033.33 | 20.30 | 89.67 | 399.17 | 1690.49 | 22.16 | 70.00 | 363.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 4024.76 | 22.51 | 128.17 | 375.17 | 1729.47 | 22.07 | 70.50 | 351.50 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3511.07 | 21.47 | 82.67 | 324.17 | 1578.83 | 21.97 | 48.50 | 292.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3122.13 | 22.46 | 91.17 | 296.50 | 1685.27 | 23.49 | 73.50 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2117.60 | 21.42 | 73.33 | 247.33 | 1124.52 | 22.79 | 74.00 | 206.50 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-07:30 | 1959.40 | 23.00 | 82.83 | 226.00 | 1147.69 | 23.57 | 78.67 | 166.83 |
Annual Sum or Average | 3472.67 | 0.50 | 3090.10 | 21.67 | 1053.50 | 3791.67 | 1595.39 | 22.46 | 786.50 | 3331.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1959.40 | 20.30 | 71.50 | 226.00 | 1124.52 | 21.68 | 48.50 | 164.83 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4024.76 | 23.49 | 128.17 | 399.17 | 1817.46 | 24.06 | 78.67 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-08:30 | 672.22 | 11.57 | 0.00 | 210.17 | 424.27 | 15.11 | 0.00 | 132.17 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 737.01 | 12.64 | 0.00 | 233.83 | 491.88 | 16.35 | 0.00 | 177.50 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 973.10 | 13.59 | 0.00 | 309.00 | 626.42 | 17.05 | 0.00 | 251.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1098.97 | 14.54 | 0.00 | 345.17 | 709.49 | 18.06 | 0.00 | 303.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 1399.89 | 15.01 | 3.17 | 404.50 | 835.14 | 18.44 | 10.33 | 369.17 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-04:00 | 1577.44 | 19.14 | 73.00 | 402.83 | 919.65 | 21.15 | 51.83 | 375.83 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1555.91 | 17.42 | 41.33 | 409.00 | 910.04 | 20.64 | 46.17 | 376.50 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1289.09 | 14.95 | 0.00 | 378.50 | 804.57 | 18.42 | 3.50 | 354.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 1007.37 | 14.19 | 0.00 | 321.83 | 656.32 | 17.71 | 0.00 | 277.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 913.63 | 13.90 | 0.00 | 291.33 | 607.01 | 17.47 | 0.00 | 252.00 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:19 | 748.31 | 12.13 | 0.00 | 235.83 | 463.03 | 15.66 | 0.00 | 166.67 |
December | 211.17 | 0.55 | 0.48 | 01-DEC-08:30 | 544.32 | 10.46 | 0.00 | 201.50 | 353.58 | 14.17 | 0.00 | 103.33 |
Annual Sum or Average | 3472.67 | 0.50 | 1110.16 | 14.54 | 117.50 | 3743.50 | 687.37 | 17.89 | 111.83 | 3138.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 544.32 | 10.46 | 0.00 | 201.50 | 353.58 | 14.17 | 0.00 | 103.33 | |
Maximum of Months | 389.17 | 0.55 | 0.48 | 1577.44 | 19.14 | 73.00 | 409.00 | 919.65 | 21.15 | 51.83 | 376.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:30 | 2038.06 | 22.84 | 73.33 | 232.50 | 1164.06 | 23.42 | 65.50 | 170.17 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-08:39 | 2280.00 | 20.87 | 57.00 | 247.83 | 1251.45 | 22.83 | 45.17 | 213.00 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:19 | 3293.72 | 23.12 | 95.83 | 320.83 | 1880.37 | 23.99 | 74.83 | 283.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3728.70 | 21.29 | 76.83 | 343.33 | 1595.22 | 20.72 | 37.00 | 306.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3513.10 | 18.40 | 69.17 | 397.33 | 1608.14 | 18.02 | 0.00 | 364.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:49 | 3405.00 | 14.76 | 1.83 | 394.17 | 1895.56 | 18.16 | 0.00 | 360.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-05:49 | 3212.24 | 17.63 | 49.00 | 400.17 | 1768.90 | 18.32 | 0.00 | 362.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 4104.43 | 19.55 | 86.33 | 374.50 | 1837.36 | 18.50 | 8.50 | 351.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:30 | 3335.17 | 21.76 | 85.17 | 325.00 | 1782.28 | 22.69 | 61.50 | 291.33 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 3576.05 | 23.91 | 111.83 | 305.17 | 1570.20 | 23.74 | 70.33 | 282.00 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-07:19 | 1765.94 | 22.02 | 79.67 | 248.33 | 966.51 | 22.94 | 70.33 | 212.33 |
December | 211.17 | 0.52 | 0.48 | 01-DEC-08:30 | 1623.60 | 20.91 | 68.50 | 224.33 | 934.19 | 22.87 | 66.83 | 171.50 |
Annual Sum or Average | 3472.67 | 0.50 | 3129.04 | 20.24 | 854.50 | 3813.50 | 1578.23 | 20.93 | 500.00 | 3370.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1623.60 | 14.76 | 1.83 | 224.33 | 934.19 | 18.02 | 0.00 | 170.17 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 4104.43 | 23.91 | 111.83 | 400.17 | 1895.56 | 23.99 | 74.83 | 364.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254732E+09 | 22533.81 | 26-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285757E+09 | 39136.01 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354956E+09 | 30006.84 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103843E+09 | 15984.18 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23963964.96 | 10401.25 | 30-MAY-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117145E+09 | 14963.35 | 22-JUN-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 61901400.22 | 11360.77 | 11-JUL-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120258E+09 | 16541.27 | 24-AUG-17:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7131794.00 | 5470.32 | 01-SEP-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34273687.68 | 13076.06 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219147E+09 | 30450.65 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430391E+09 | 31514.98 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7131794.00 | 5470.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.430391E+09 | 39136.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.805874E+09 | 15084.33 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.551931E+09 | 15094.40 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3575204.64 | 1368.23 | 17-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9461307.87 | 10062.52 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3387708.22 | 2242.39 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.805874E+09 | 15094.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.513434E+09 | 14342.26 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328682E+09 | 14374.27 | 28-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23306589.34 | 14420.84 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15864012.14 | 14419.89 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50821978.54 | 14431.38 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.513434E+09 | 14431.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.896833E+09 | 19682.26 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.534073E+09 | 19836.49 | 22-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 61611629.98 | 19844.69 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 47432338.45 | 19855.34 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126010E+09 | 19855.31 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.896833E+09 | 19855.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115771E+09 | 13111.88 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36328177.59 | 13100.40 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115771E+09 | 13111.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.930544E+10 | 283598.17 | 31-JAN-10:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844255E+10 | 462862.06 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.480132E+10 | 310308.22 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213149E+10 | 199627.88 | 14-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.568753E+09 | 150175.83 | 30-MAY-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.914922E+09 | 156120.61 | 01-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.479800E+09 | 111990.89 | 11-JUL-15:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111665E+10 | 207347.31 | 24-AUG-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236389E+09 | 73604.86 | 01-SEP-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.530624E+09 | 135769.86 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316541E+10 | 325795.49 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.421429E+10 | 313572.56 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.236389E+09 | 73604.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.930544E+10 | 462862.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264428E+11 | 545415.29 | 17-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440928E+10 | 544480.26 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214178E+09 | 115139.79 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82732949.49 | 25180.78 | 26-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264428E+11 | 545415.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.674222E+11 | 135627.70 | 24-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.536345E+11 | 134929.83 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158436E+11 | 134921.46 | 10-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324541E+10 | 146733.13 | 12-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.561582E+09 | 146459.36 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163261E+11 | 143316.95 | 01-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378905E+11 | 134944.26 | 30-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194924E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.674222E+11 | 146733.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354926E+11 | 185586.35 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241402E+11 | 185375.74 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.663236E+10 | 185283.25 | 11-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153427E+10 | 184988.24 | 21-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174861E+09 | 92215.60 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.748233E+10 | 185646.63 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183564E+11 | 185527.89 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354926E+11 | 185646.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.403940E+11 | 202874.21 | 23-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252625E+11 | 202070.64 | 28-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784442E+10 | 201724.72 | 11-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224776E+10 | 211691.54 | 14-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53139265.43 | 36570.29 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723957E+10 | 202897.45 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196109E+11 | 202921.70 | 30-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.403940E+11 | 211691.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316062E+11 | 188155.65 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221903E+11 | 187953.35 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464068E+10 | 187557.98 | 13-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.869002E+09 | 136501.72 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75785317.37 | 41110.32 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.640962E+10 | 187643.37 | 20-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147158E+11 | 187835.50 | 30-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316062E+11 | 188155.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196243E+10 | 28767.38 | 26-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145614E+10 | 47731.13 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344227E+09 | 36051.63 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122351E+09 | 19752.96 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27641892.97 | 14422.76 | 30-MAY-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70440341.43 | 12162.91 | 01-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 54866763.24 | 8067.77 | 11-JUL-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77189816.06 | 14395.86 | 30-AUG-14:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17355766.72 | 9365.52 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67260978.97 | 16660.46 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259296E+09 | 37763.64 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489448E+09 | 37522.70 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.494864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17355766.72 | 8067.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196243E+10 | 47731.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102690E+11 | 74931.98 | 23-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.762641E+10 | 74893.43 | 21-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194847E+10 | 74567.26 | 20-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.423194E+09 | 74872.69 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41535218.42 | 8978.39 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317617E+10 | 74958.83 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.575456E+10 | 74918.22 | 26-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102690E+11 | 74958.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107292E+11 | 15585.16 | 24-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.942556E+10 | 15499.78 | 28-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395192E+10 | 15459.35 | 17-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126183E+10 | 15459.31 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55708863.85 | 15411.23 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 763321.17 | 288.97 | 30-SEP-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439967E+09 | 15408.98 | 10-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416334E+10 | 15540.18 | 27-NOV-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794540E+10 | 15534.11 | 30-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107292E+11 | 15585.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.615408E+10 | 19271.46 | 24-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483335E+10 | 19202.86 | 22-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184952E+10 | 19257.79 | 06-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659849E+09 | 19212.99 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22894618.44 | 11506.97 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180977E+09 | 19057.08 | 28-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210783E+10 | 19262.47 | 27-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.428974E+10 | 19262.67 | 26-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.615408E+10 | 19271.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.716979E+10 | 22174.97 | 23-JAN-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.543131E+10 | 22199.16 | 28-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240766E+10 | 22133.74 | 17-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.997704E+09 | 22098.18 | 22-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57559846.07 | 18749.43 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174979E+09 | 21856.54 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230460E+10 | 22205.69 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479317E+10 | 22135.93 | 28-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.716979E+10 | 22205.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.536873E+10 | 21017.67 | 23-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418915E+10 | 20967.32 | 07-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136981E+10 | 20971.17 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.433543E+09 | 20929.38 | 22-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13410769.77 | 10858.90 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121702E+09 | 14951.54 | 28-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171548E+10 | 21030.13 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331919E+10 | 20975.87 | 02-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.536873E+10 | 21030.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 334.22 | 0.88 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 402.37 | 0.91 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 508.18 | 0.75 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1244.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 508.18 | 0.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.403654E+09 | 0.403654E+09 | 18566.92 | 19-JAN-14:20 | 18566.92 | 0.00 |
February | 0.00 | 0.00 | 0.100775E+10 | 0.100775E+10 | 22513.91 | 24-FEB-15:30 | 22513.91 | 0.00 |
March | 0.00 | 0.00 | 0.504468E+10 | 0.500858E+10 | 65940.16 | 27-MAR-16:00 | 65940.16 | 0.03 |
April | 0.00 | 0.00 | 0.124807E+11 | 0.124745E+11 | 112942.92 | 07-APR-14:40 | 112942.92 | 0.13 |
May | 0.00 | 0.00 | 0.339305E+11 | 0.305482E+11 | 161336.07 | 30-MAY-13:40 | 161336.07 | 0.29 |
June | 0.00 | 0.00 | 0.113738E+12 | 0.928109E+11 | 193725.30 | 15-JUN-04:12 | 136243.50 | 0.65 |
July | 0.00 | 0.00 | 0.157088E+12 | 0.129881E+12 | 216533.67 | 10-JUL-04:02 | 152519.09 | 0.83 |
August | 0.00 | 0.00 | 0.161205E+12 | 0.141764E+12 | 199908.94 | 14-AUG-04:21 | 149122.75 | 0.85 |
September | 0.00 | 0.00 | 0.758084E+11 | 0.647915E+11 | 186120.37 | 22-SEP-04:12 | 121723.80 | 0.53 |
October | 0.00 | 0.00 | 0.383038E+11 | 0.293040E+11 | 144532.71 | 06-OCT-04:12 | 61393.09 | 0.29 |
November | 0.00 | 0.00 | 0.318571E+10 | 0.310331E+10 | 53392.06 | 10-NOV-06:03 | 20727.16 | 0.02 |
December | 0.00 | 0.00 | 0.341458E+10 | 0.341458E+10 | 32698.20 | 18-DEC-14:30 | 32698.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.605610E+12 | 0.514511E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.403654E+09 | 0.403654E+09 | 18566.92 | 18566.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161205E+12 | 0.141764E+12 | 216533.67 | 161336.07 | 0.85 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 48935580.64 | 48935580.64 | 5395.14 | 27-JAN-15:10 | 5395.14 | 0.00 |
February | 0.00 | 0.00 | 0.166581E+09 | 0.166581E+09 | 12094.64 | 24-FEB-15:50 | 12094.64 | 0.00 |
March | 0.00 | 0.00 | 0.180189E+11 | 0.180171E+11 | 400604.51 | 27-MAR-16:00 | 400604.51 | 0.02 |
April | 0.00 | 0.00 | 0.950080E+11 | 0.949873E+11 | 910674.62 | 07-APR-15:10 | 910674.62 | 0.11 |
May | 0.00 | 0.00 | 0.295081E+12 | 0.266756E+12 | 1574223.25 | 30-MAY-14:07 | 1574223.25 | 0.29 |
June | 0.00 | 0.00 | 0.946767E+12 | 0.746803E+12 | 1895877.86 | 27-JUN-04:11 | 1146432.61 | 0.59 |
July | 0.00 | 0.00 | 0.126326E+13 | 0.980807E+12 | 2262304.43 | 24-JUL-05:03 | 1127832.01 | 0.64 |
August | 0.00 | 0.00 | 0.123954E+13 | 0.105131E+13 | 1834573.17 | 24-AUG-16:30 | 1834573.17 | 0.62 |
September | 0.00 | 0.00 | 0.659382E+12 | 0.552146E+12 | 1767629.56 | 01-SEP-14:55 | 1767629.56 | 0.50 |
October | 0.00 | 0.00 | 0.320611E+12 | 0.247857E+12 | 1161306.82 | 06-OCT-05:03 | 498350.19 | 0.28 |
November | 0.00 | 0.00 | 0.296448E+11 | 0.292617E+11 | 448000.62 | 03-NOV-14:05 | 448000.62 | 0.03 |
December | 0.00 | 0.00 | 0.274703E+09 | 0.274703E+09 | 12041.75 | 21-DEC-14:30 | 12041.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.486780E+13 | 0.398843E+13 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 48935580.64 | 48935580.64 | 5395.14 | 5395.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126326E+13 | 0.105131E+13 | 2262304.43 | 1834573.17 | 0.64 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9540862.98 | 9540862.98 | 831.20 | 15-JAN-10:50 | 831.20 | 0.00 |
February | 0.00 | 0.00 | 18098289.14 | 18098289.14 | 537.57 | 02-FEB-10:50 | 537.57 | 0.00 |
March | 0.00 | 0.00 | 0.802188E+09 | 0.802188E+09 | 33585.30 | 27-MAR-16:00 | 33585.30 | 0.03 |
April | 0.00 | 0.00 | 0.829779E+10 | 0.829779E+10 | 103273.10 | 07-APR-14:50 | 103273.10 | 0.11 |
May | 0.00 | 0.00 | 0.302314E+11 | 0.275812E+11 | 179370.34 | 30-MAY-14:03 | 179370.34 | 0.28 |
June | 0.00 | 0.00 | 0.102440E+12 | 0.822836E+11 | 197961.09 | 19-JUN-04:12 | 128067.34 | 0.59 |
July | 0.00 | 0.00 | 0.141254E+12 | 0.111603E+12 | 243092.52 | 24-JUL-05:03 | 139167.91 | 0.65 |
August | 0.00 | 0.00 | 0.136729E+12 | 0.117397E+12 | 220209.22 | 05-AUG-03:02 | 142976.50 | 0.62 |
September | 0.00 | 0.00 | 0.672082E+11 | 0.564136E+11 | 175095.08 | 01-SEP-04:12 | 116366.84 | 0.50 |
October | 0.00 | 0.00 | 0.272795E+11 | 0.206831E+11 | 123605.28 | 04-OCT-14:50 | 96636.71 | 0.28 |
November | 0.00 | 0.00 | 0.634438E+09 | 0.604780E+09 | 16307.27 | 03-NOV-14:00 | 16307.27 | 0.02 |
December | 0.00 | 0.00 | 27716048.84 | 27716048.84 | 508.05 | 21-DEC-11:30 | 508.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.514933E+12 | 0.425721E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 9540862.98 | 9540862.98 | 508.05 | 508.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141254E+12 | 0.117397E+12 | 243092.52 | 179370.34 | 0.65 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7265902.43 | 3177209.47 | 33492.33 | 24-JAN-06:02 | 14678.81 | 0.00 |
February | 0.00 | 0.00 | 5257.73 | 5257.73 | 8.76 | 16-FEB-20:40 | 8.76 | 0.00 |
March | 0.00 | 0.00 | 0.562617E+09 | 0.562617E+09 | 37672.28 | 27-MAR-16:00 | 37672.28 | 0.01 |
April | 0.00 | 0.00 | 0.511323E+10 | 0.507299E+10 | 60349.68 | 10-APR-05:02 | 32953.78 | 0.07 |
May | 0.00 | 0.00 | 0.146669E+11 | 0.139727E+11 | 89838.07 | 30-MAY-10:55 | 89838.07 | 0.17 |
June | 0.00 | 0.00 | 0.617354E+11 | 0.507924E+11 | 130084.31 | 19-JUN-04:53 | 75001.92 | 0.51 |
July | 0.00 | 0.00 | 0.895414E+11 | 0.689404E+11 | 141999.74 | 10-JUL-03:02 | 72705.06 | 0.54 |
August | 0.00 | 0.00 | 0.906345E+11 | 0.748252E+11 | 132210.95 | 13-AUG-16:11 | 99901.30 | 0.57 |
September | 0.00 | 0.00 | 0.471375E+11 | 0.406731E+11 | 123297.79 | 08-SEP-04:53 | 75331.47 | 0.44 |
October | 0.00 | 0.00 | 0.184637E+11 | 0.152495E+11 | 101015.46 | 06-OCT-04:12 | 42910.52 | 0.23 |
November | 0.00 | 0.00 | 0.154824E+09 | 0.136132E+09 | 68041.85 | 10-NOV-06:03 | 27420.70 | 0.00 |
December | 0.00 | 0.00 | 9637.81 | 9637.81 | 16.06 | 06-DEC-19:20 | 16.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.328017E+12 | 0.270228E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 5257.73 | 5257.73 | 8.76 | 8.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.906345E+11 | 0.748252E+11 | 141999.74 | 99901.30 | 0.57 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.546816E+10 | 0.546803E+10 | 3594.78 | 20-JAN-05:55 | 3594.78 | 0.00 |
February | 0.00 | 0.00 | 0.106241E+11 | 0.106093E+11 | 5159.00 | 20-FEB-13:43 | 5159.00 | 0.00 |
March | 0.00 | 0.00 | 0.158226E+11 | 0.141304E+11 | 232489.05 | 27-MAR-16:00 | 183676.77 | 0.00 |
April | 0.00 | 0.00 | 0.143051E+12 | 0.116409E+12 | 408567.38 | 09-APR-10:43 | 398543.83 | 0.00 |
May | 0.00 | 0.00 | 0.221344E+11 | 0.215059E+11 | 212115.18 | 31-MAY-23:10 | 210196.86 | 0.00 |
June | 0.00 | 0.00 | 0.372607E+12 | 0.351047E+12 | 325784.11 | 21-JUN-14:40 | 215967.79 | 0.00 |
July | 0.00 | 0.00 | 0.832456E+12 | 0.819576E+12 | 394706.24 | 31-JUL-24:00 | 394706.24 | 0.00 |
August | 0.00 | 0.00 | 0.101709E+13 | 0.973885E+12 | 417681.56 | 31-AUG-05:40 | 400747.15 | 0.00 |
September | 0.00 | 0.00 | 0.922796E+11 | 0.873915E+11 | 237261.89 | 01-SEP-13:40 | 237261.89 | 0.00 |
October | 0.00 | 0.00 | 0.447646E+11 | 0.327189E+11 | 277684.39 | 25-OCT-10:20 | 217539.27 | 0.00 |
November | 0.00 | 0.00 | 0.134506E+11 | 0.127128E+11 | 81361.60 | 04-NOV-13:00 | 68208.11 | 0.00 |
December | 0.00 | 0.00 | 0.147888E+11 | 0.144936E+11 | 21518.65 | 17-DEC-12:02 | 21518.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.258453E+13 | 0.245995E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.546816E+10 | 0.546803E+10 | 3594.78 | 3594.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101709E+13 | 0.973885E+12 | 417681.56 | 400747.15 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.315822E+10 | 0.315285E+10 | 2288.62 | 29-JAN-16:40 | 2288.62 | 0.00 |
February | 0.00 | 0.00 | 0.794025E+10 | 0.794025E+10 | 4330.86 | 20-FEB-16:20 | 4330.86 | 0.00 |
March | 0.00 | 0.00 | 0.148669E+11 | 0.148555E+11 | 7460.20 | 31-MAR-24:00 | 7460.20 | 0.00 |
April | 0.00 | 0.00 | 0.197219E+11 | 0.196963E+11 | 8839.55 | 23-APR-17:47 | 8839.55 | 0.00 |
May | 0.00 | 0.00 | 0.554745E+10 | 0.545269E+10 | 4090.23 | 31-MAY-23:40 | 3999.61 | 0.00 |
June | 0.00 | 0.00 | 0.108938E+11 | 0.105698E+11 | 5857.45 | 30-JUN-24:00 | 5838.94 | 0.00 |
July | 0.00 | 0.00 | 0.165809E+11 | 0.160995E+11 | 7749.12 | 31-JUL-24:00 | 7749.12 | 0.00 |
August | 0.00 | 0.00 | 0.215845E+11 | 0.212095E+11 | 8821.95 | 31-AUG-18:00 | 8477.48 | 0.00 |
September | 0.00 | 0.00 | 0.573117E+10 | 0.552832E+10 | 3901.18 | 30-SEP-24:00 | 3901.18 | 0.00 |
October | 0.00 | 0.00 | 0.106727E+11 | 0.105239E+11 | 5646.76 | 31-OCT-24:00 | 5645.98 | 0.00 |
November | 0.00 | 0.00 | 0.144264E+11 | 0.144087E+11 | 6092.93 | 03-NOV-16:00 | 6092.93 | 0.00 |
December | 0.00 | 0.00 | 0.196656E+11 | 0.196656E+11 | 8263.37 | 17-DEC-16:00 | 8263.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150790E+12 | 0.149103E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.315822E+10 | 0.315285E+10 | 2288.62 | 2288.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215845E+11 | 0.212095E+11 | 8839.55 | 8839.55 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.647414E+10 | 0.644125E+10 | 16549.83 | 20-JAN-16:30 | 16549.83 | 0.00 |
February | 0.00 | 0.00 | 0.521583E+11 | 0.521583E+11 | 36125.71 | 22-FEB-17:00 | 36125.71 | 0.00 |
March | 0.00 | 0.00 | 0.124285E+12 | 0.124170E+12 | 65334.34 | 31-MAR-23:40 | 65334.34 | 0.00 |
April | 0.00 | 0.00 | 0.177455E+12 | 0.177198E+12 | 81641.17 | 09-APR-17:32 | 81394.19 | 0.00 |
May | 0.00 | 0.00 | 0.479674E+11 | 0.470367E+11 | 38916.75 | 31-MAY-23:40 | 38001.38 | 0.00 |
June | 0.00 | 0.00 | 0.102168E+12 | 0.989524E+11 | 55217.76 | 30-JUN-24:00 | 55030.26 | 0.00 |
July | 0.00 | 0.00 | 0.158045E+12 | 0.153247E+12 | 74357.92 | 31-JUL-24:00 | 74357.92 | 0.00 |
August | 0.00 | 0.00 | 0.205564E+12 | 0.201813E+12 | 84596.51 | 31-AUG-18:00 | 81144.27 | 0.00 |
September | 0.00 | 0.00 | 0.507926E+11 | 0.487981E+11 | 35737.27 | 30-SEP-23:30 | 35737.27 | 0.00 |
October | 0.00 | 0.00 | 0.939635E+11 | 0.924888E+11 | 49279.84 | 31-OCT-23:50 | 49253.43 | 0.00 |
November | 0.00 | 0.00 | 0.117863E+12 | 0.117686E+12 | 57264.85 | 03-NOV-16:00 | 57264.85 | 0.00 |
December | 0.00 | 0.00 | 0.160258E+12 | 0.160258E+12 | 71395.46 | 08-DEC-16:10 | 71395.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129700E+13 | 0.128025E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.647414E+10 | 0.644125E+10 | 16549.83 | 16549.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205564E+12 | 0.201813E+12 | 84596.51 | 81394.19 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.231906E+09 | 0.229866E+09 | 1631.64 | 19-JAN-16:30 | 1631.64 | 0.00 |
February | 0.00 | 0.00 | 0.374316E+10 | 0.374316E+10 | 3509.06 | 22-FEB-17:00 | 3509.06 | 0.00 |
March | 0.00 | 0.00 | 0.110981E+11 | 0.110869E+11 | 6071.42 | 27-MAR-17:20 | 5948.69 | 0.00 |
April | 0.00 | 0.00 | 0.168667E+11 | 0.168412E+11 | 8278.77 | 09-APR-17:23 | 8249.14 | 0.00 |
May | 0.00 | 0.00 | 0.448424E+10 | 0.439208E+10 | 3852.00 | 31-MAY-23:30 | 3753.28 | 0.00 |
June | 0.00 | 0.00 | 0.102260E+11 | 0.990440E+10 | 5456.20 | 30-JUN-24:00 | 5437.07 | 0.00 |
July | 0.00 | 0.00 | 0.159292E+11 | 0.154494E+11 | 7438.49 | 31-JUL-24:00 | 7438.49 | 0.00 |
August | 0.00 | 0.00 | 0.206280E+11 | 0.202529E+11 | 8594.69 | 31-AUG-17:50 | 8247.21 | 0.00 |
September | 0.00 | 0.00 | 0.487870E+10 | 0.467944E+10 | 3286.72 | 30-SEP-23:20 | 3286.72 | 0.00 |
October | 0.00 | 0.00 | 0.856651E+10 | 0.841969E+10 | 4632.78 | 04-OCT-16:30 | 4339.68 | 0.00 |
November | 0.00 | 0.00 | 0.102240E+11 | 0.102065E+11 | 5711.45 | 03-NOV-16:00 | 5711.45 | 0.00 |
December | 0.00 | 0.00 | 0.141679E+11 | 0.141679E+11 | 6975.46 | 08-DEC-16:10 | 6975.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121044E+12 | 0.119374E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.231906E+09 | 0.229866E+09 | 1631.64 | 1631.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206280E+11 | 0.202529E+11 | 8594.69 | 8249.14 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.16 | 48188.11 | 31-JAN-11:00 | 94983.89 | 2144040.66 | 03-JAN-05:21 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 71278.02 | 1769755.45 | 22-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 19421.40 | 1854835.06 | 11-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5397.55 | 1765651.39 | 22-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 319.67 | 167211.72 | 30-MAY-14:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 468.52 | 188488.59 | 01-JUN-14:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 192.93 | 93417.32 | 11-JUL-15:37 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 512.89 | 151745.24 | 24-AUG-17:07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 101.61 | 78050.04 | 01-SEP-16:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 850.38 | 648764.01 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21144.87 | 1930614.37 | 15-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 45570.85 | 1797337.17 | 21-DEC-05:01 |
Annual Sum or Average | 1.37 | 21442.67 | ||||
Minimum of Months | 0.00 | 0.00 | 101.61 | 78050.04 | ||
Maximum of Months | 16.16 | 48188.11 | 94983.89 | 2144040.66 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 273.83 | 52133.36 | 24-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 764.73 | 34270.59 | 24-FEB-15:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9748.81 | 530180.16 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 47436.02 | 1217922.83 | 07-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 142975.88 | 2055056.64 | 30-MAY-09:07 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 499091.12 | 2135319.96 | 22-JUN-13:25 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 648978.44 | 2721222.15 | 24-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 634662.61 | 2401945.95 | 22-AUG-12:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 341873.80 | 2229407.79 | 01-SEP-13:12 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 157862.67 | 2206131.47 | 03-OCT-12:43 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 13508.69 | 584703.60 | 03-NOV-15:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1835.36 | 41195.72 | 20-DEC-10:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 209767.58 | 0.00 | ||||
Minimum of Months | 273.83 | 34270.59 | 0.00 | 0.00 | ||
Maximum of Months | 648978.44 | 2721222.15 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117.48 | 91171.97 | 24-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 478.59 | 33092.31 | 24-FEB-15:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9116.72 | 534789.65 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46780.94 | 1389617.44 | 07-APR-14:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 141817.18 | 2024454.84 | 30-MAY-14:07 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 499053.41 | 3472678.05 | 27-JUN-04:11 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 648939.23 | 3507083.97 | 28-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 635484.17 | 3419515.33 | 17-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 341830.18 | 3434936.67 | 14-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 160369.30 | 2624722.31 | 04-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 12937.51 | 611184.78 | 03-NOV-15:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1390.22 | 37604.96 | 20-DEC-10:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 209714.31 | 0.00 | ||||
Minimum of Months | 117.48 | 33092.31 | 0.00 | 0.00 | ||
Maximum of Months | 648939.23 | 3507083.97 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10938.26 | 53797.32 | 12-JAN-15:50 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 41817.03 | 78963.08 | 01-FEB-12:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 81209.64 | 730021.72 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 205919.31 | 1302271.24 | 07-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 89420.17 | 966125.64 | 30-MAY-13:55 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 527491.21 | 1479699.56 | 19-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1039550.47 | 1547016.33 | 07-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1195553.54 | 1733875.23 | 24-AUG-15:42 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 234684.50 | 1100841.88 | 01-SEP-13:40 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 109905.22 | 863187.27 | 04-OCT-13:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76968.53 | 230267.26 | 04-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 98481.63 | 150257.27 | 04-DEC-17:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312053.73 | 0.00 | ||||
Minimum of Months | 10938.26 | 53797.32 | 0.00 | 0.00 | ||
Maximum of Months | 1195553.54 | 1733875.23 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 15951.29 | 53759.63 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16183.26 | 53879.71 | 06-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16751.03 | 53447.32 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15050.60 | 51229.75 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14533.25 | 48327.77 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13875.85 | 44828.67 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12278.62 | 41916.16 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13141.77 | 40963.63 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 12759.42 | 42849.13 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13490.37 | 46119.10 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14617.05 | 49506.74 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15004.21 | 52217.08 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14459.96 | ||||
Minimum of Months | 0.00 | 0.00 | 12278.62 | 40963.63 | ||
Maximum of Months | 0.00 | 0.00 | 16751.03 | 53879.71 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19.41 | 19446.88 | 20-JAN-14:25 | 1769.86 | 141426.30 | 07-JAN-11:10 |
February | 48.10 | 29161.27 | 22-FEB-15:40 | 3406.43 | 161409.06 | 28-FEB-05:01 |
March | 7950.62 | 610297.27 | 27-MAR-16:00 | 4582.31 | 146417.26 | 17-MAR-06:50 |
April | 54758.08 | 1685866.33 | 07-APR-15:00 | 1459.96 | 113883.68 | 21-APR-09:30 |
May | 183783.25 | 2941893.98 | 31-MAY-12:30 | 896.69 | 85792.66 | 01-MAY-15:50 |
June | 933617.23 | 5186306.99 | 19-JUN-08:40 | 230.60 | 68770.21 | 09-JUN-06:00 |
July | 1661041.11 | 5717996.33 | 20-JUL-14:30 | 4.45 | 10068.97 | 11-JUL-03:00 |
August | 1446717.30 | 6013527.51 | 03-AUG-14:05 | 479.00 | 51447.51 | 24-AUG-22:40 |
September | 585643.58 | 4743966.59 | 07-SEP-14:05 | 481.79 | 69403.54 | 29-SEP-18:40 |
October | 213684.48 | 3308791.39 | 03-OCT-12:43 | 1076.22 | 134618.44 | 31-OCT-07:30 |
November | 14101.49 | 653200.74 | 03-NOV-15:10 | 3345.42 | 144573.26 | 24-NOV-14:50 |
December | 155.59 | 47773.53 | 18-DEC-14:40 | 5187.61 | 149547.30 | 15-DEC-14:30 |
Annual Sum or Average | 428928.39 | 1903.54 | ||||
Minimum of Months | 19.41 | 19446.88 | 4.45 | 10068.97 | ||
Maximum of Months | 1661041.11 | 6013527.51 | 5187.61 | 161409.06 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114986E+11 | 0.73 | 8170.07 | 02-JAN-06:01 | 1.39 |
February | 0.106072E+11 | 0.75 | 8170.07 | 01-FEB-06:02 | 1.40 |
March | 0.127838E+11 | 0.81 | 8170.07 | 01-MAR-05:11 | 1.39 |
April | 0.116448E+11 | 0.76 | 8170.07 | 01-APR-04:11 | 1.39 |
May | 0.124938E+11 | 0.79 | 8170.07 | 01-MAY-04:12 | 1.39 |
June | 0.122845E+11 | 0.80 | 8170.07 | 01-JUN-04:12 | 1.38 |
July | 0.122053E+11 | 0.77 | 8170.07 | 01-JUL-04:12 | 1.38 |
August | 0.135617E+11 | 0.85 | 8170.07 | 01-AUG-03:02 | 1.38 |
September | 0.125735E+11 | 0.82 | 8170.07 | 01-SEP-04:12 | 1.38 |
October | 0.126920E+11 | 0.80 | 8170.07 | 01-OCT-23:50 | 1.38 |
November | 0.120937E+11 | 0.79 | 8170.07 | 01-NOV-04:12 | 1.39 |
December | 0.117903E+11 | 0.75 | 8170.07 | 01-DEC-05:11 | 1.39 |
Annual Sum or Average | 0.146229E+12 | 0.79 | |||
Minimum of Months | 0.106072E+11 | 0.73 | 8170.07 | 1.38 | |
Maximum of Months | 0.135617E+11 | 0.85 | 8170.07 | 1.40 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.258404E+10 | 0.28 | 10434.61 | 30-JAN-06:01 | 1.21 |
February | 0.277096E+10 | 0.30 | 10434.61 | 03-FEB-06:01 | 1.21 |
March | 0.502301E+10 | 0.37 | 9980.81 | 04-MAR-06:02 | 1.17 |
April | 0.683909E+10 | 0.45 | 15546.42 | 10-APR-14:40 | 1.55 |
May | 0.700119E+10 | 0.44 | 19228.61 | 30-MAY-04:12 | 1.76 |
June | 0.100488E+11 | 0.57 | 19228.61 | 01-JUN-15:43 | 1.76 |
July | 0.118836E+11 | 0.66 | 19228.61 | 03-JUL-05:03 | 1.75 |
August | 0.138080E+11 | 0.73 | 19228.61 | 01-AUG-05:02 | 1.75 |
September | 0.752607E+10 | 0.46 | 19228.61 | 02-SEP-04:12 | 1.76 |
October | 0.708458E+10 | 0.43 | 13255.45 | 16-OCT-15:10 | 1.39 |
November | 0.454683E+10 | 0.34 | 10690.96 | 06-NOV-14:30 | 1.22 |
December | 0.399422E+10 | 0.32 | 9456.78 | 07-DEC-06:01 | 1.14 |
Annual Sum or Average | 0.831104E+11 | 0.45 | |||
Minimum of Months | 0.258404E+10 | 0.28 | 9456.78 | 1.14 | |
Maximum of Months | 0.138080E+11 | 0.73 | 19228.61 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.256726E+11 | 0.32 | 46016.72 | 02-JAN-04:01 | 0.78 |
February | 0.230564E+11 | 0.32 | 46016.72 | 06-FEB-05:01 | 0.78 |
March | 0.270938E+11 | 0.31 | 85692.69 | 29-MAR-05:03 | 1.11 |
April | 0.340851E+11 | 0.33 | 108178.63 | 07-APR-15:10 | 1.28 |
May | 0.520924E+11 | 0.39 | 180291.17 | 30-MAY-05:03 | 1.76 |
June | 0.755601E+11 | 0.48 | 180291.17 | 01-JUN-14:40 | 1.76 |
July | 0.866692E+11 | 0.51 | 180291.17 | 03-JUL-04:12 | 1.75 |
August | 0.956056E+11 | 0.54 | 180291.17 | 02-AUG-05:03 | 1.75 |
September | 0.577781E+11 | 0.41 | 180291.17 | 01-SEP-04:12 | 1.75 |
October | 0.439169E+11 | 0.35 | 97399.71 | 05-OCT-15:50 | 1.19 |
November | 0.242368E+11 | 0.28 | 79504.72 | 01-NOV-05:03 | 1.06 |
December | 0.227039E+11 | 0.29 | 31250.28 | 06-DEC-05:01 | 0.64 |
Annual Sum or Average | 0.568471E+12 | 0.38 | |||
Minimum of Months | 0.227039E+11 | 0.28 | 31250.28 | 0.64 | |
Maximum of Months | 0.956056E+11 | 0.54 | 180291.17 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.310322E+10 | 0.38 | 4513.13 | 01-JAN-00:42 | 0.73 |
February | 0.268850E+10 | 0.36 | 4513.13 | 03-FEB-06:01 | 0.73 |
March | 0.270650E+10 | 0.32 | 4513.13 | 13-MAR-04:01 | 0.73 |
April | 0.316120E+10 | 0.32 | 11238.56 | 07-APR-14:50 | 1.23 |
May | 0.491989E+10 | 0.37 | 19955.60 | 30-MAY-13:25 | 1.76 |
June | 0.783764E+10 | 0.47 | 19955.60 | 01-JUN-15:43 | 1.76 |
July | 0.945807E+10 | 0.51 | 19955.60 | 05-JUL-04:12 | 1.76 |
August | 0.102405E+11 | 0.53 | 19955.60 | 02-AUG-05:03 | 1.75 |
September | 0.549316E+10 | 0.38 | 16849.68 | 07-SEP-05:03 | 1.57 |
October | 0.373607E+10 | 0.32 | 10550.29 | 04-OCT-16:00 | 1.17 |
November | 0.240108E+10 | 0.30 | 4513.13 | 20-NOV-05:01 | 0.73 |
December | 0.264847E+10 | 0.33 | 4513.13 | 02-DEC-05:11 | 0.73 |
Annual Sum or Average | 0.583943E+11 | 0.38 | |||
Minimum of Months | 0.240108E+10 | 0.30 | 4513.13 | 0.73 | |
Maximum of Months | 0.102405E+11 | 0.53 | 19955.60 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.942726E+11 | 1.36 | 35197.36 | 01-JAN-00:03 | 1.36 |
February | 0.851495E+11 | 1.36 | 35197.36 | 01-FEB-00:10 | 1.36 |
March | 0.942726E+11 | 1.36 | 35197.36 | 01-MAR-00:10 | 1.36 |
April | 0.912316E+11 | 1.36 | 35197.36 | 01-APR-00:10 | 1.36 |
May | 0.942726E+11 | 1.35 | 35197.36 | 01-MAY-00:10 | 1.35 |
June | 0.912316E+11 | 1.35 | 35197.36 | 01-JUN-00:10 | 1.34 |
July | 0.942726E+11 | 1.35 | 35197.36 | 01-JUL-00:10 | 1.35 |
August | 0.942726E+11 | 1.35 | 35197.36 | 01-AUG-00:05 | 1.35 |
September | 0.912316E+11 | 1.35 | 35197.36 | 01-SEP-00:03 | 1.35 |
October | 0.942726E+11 | 1.35 | 35197.36 | 01-OCT-00:10 | 1.35 |
November | 0.912316E+11 | 1.36 | 35197.36 | 01-NOV-00:10 | 1.35 |
December | 0.942726E+11 | 1.36 | 35197.36 | 01-DEC-00:10 | 1.36 |
Annual Sum or Average | 0.110998E+13 | 1.35 | |||
Minimum of Months | 0.851495E+11 | 1.35 | 35197.36 | 1.34 | |
Maximum of Months | 0.942726E+11 | 1.36 | 35197.36 | 1.36 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140754E+10 | 0.92 | 525.52 | 01-JAN-00:01 | 0.92 |
February | 0.127133E+10 | 0.92 | 525.52 | 01-FEB-00:10 | 0.92 |
March | 0.140754E+10 | 0.92 | 525.52 | 01-MAR-00:10 | 0.92 |
April | 0.136214E+10 | 0.92 | 525.52 | 01-APR-00:10 | 0.91 |
May | 0.140754E+10 | 0.91 | 525.52 | 01-MAY-00:10 | 0.91 |
June | 0.136214E+10 | 0.91 | 525.52 | 01-JUN-00:10 | 0.91 |
July | 0.140754E+10 | 0.91 | 525.52 | 01-JUL-00:10 | 0.91 |
August | 0.140754E+10 | 0.91 | 525.52 | 01-AUG-00:05 | 0.91 |
September | 0.136214E+10 | 0.91 | 525.52 | 01-SEP-00:03 | 0.91 |
October | 0.140754E+10 | 0.91 | 525.52 | 01-OCT-00:10 | 0.91 |
November | 0.136214E+10 | 0.92 | 525.52 | 01-NOV-00:10 | 0.91 |
December | 0.140754E+10 | 0.92 | 525.52 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.165727E+11 | 0.92 | |||
Minimum of Months | 0.127133E+10 | 0.91 | 525.52 | 0.91 | |
Maximum of Months | 0.140754E+10 | 0.92 | 525.52 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134761E+11 | 0.92 | 5031.40 | 01-JAN-00:01 | 0.92 |
February | 0.121720E+11 | 0.92 | 5031.40 | 01-FEB-00:10 | 0.92 |
March | 0.134761E+11 | 0.92 | 5031.40 | 01-MAR-00:10 | 0.92 |
April | 0.130414E+11 | 0.92 | 5031.40 | 01-APR-00:10 | 0.91 |
May | 0.134761E+11 | 0.91 | 5031.40 | 01-MAY-00:10 | 0.91 |
June | 0.130414E+11 | 0.91 | 5031.40 | 01-JUN-00:10 | 0.91 |
July | 0.134761E+11 | 0.91 | 5031.40 | 01-JUL-00:10 | 0.91 |
August | 0.134761E+11 | 0.91 | 5031.40 | 01-AUG-00:05 | 0.91 |
September | 0.130414E+11 | 0.91 | 5031.40 | 01-SEP-00:03 | 0.91 |
October | 0.134761E+11 | 0.91 | 5031.40 | 01-OCT-00:10 | 0.91 |
November | 0.130414E+11 | 0.92 | 5031.40 | 01-NOV-00:10 | 0.91 |
December | 0.134761E+11 | 0.92 | 5031.40 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.158670E+12 | 0.92 | |||
Minimum of Months | 0.121720E+11 | 0.91 | 5031.40 | 0.91 | |
Maximum of Months | 0.134761E+11 | 0.92 | 5031.40 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137307E+10 | 0.92 | 512.65 | 01-JAN-00:01 | 0.92 |
February | 0.124019E+10 | 0.92 | 512.65 | 01-FEB-00:10 | 0.92 |
March | 0.137307E+10 | 0.92 | 512.65 | 01-MAR-00:10 | 0.92 |
April | 0.132878E+10 | 0.92 | 512.65 | 01-APR-00:10 | 0.91 |
May | 0.137307E+10 | 0.91 | 512.65 | 01-MAY-00:10 | 0.91 |
June | 0.132878E+10 | 0.91 | 512.65 | 01-JUN-00:10 | 0.91 |
July | 0.137307E+10 | 0.91 | 512.65 | 01-JUL-00:10 | 0.91 |
August | 0.137307E+10 | 0.91 | 512.65 | 01-AUG-00:05 | 0.91 |
September | 0.132878E+10 | 0.91 | 512.65 | 01-SEP-00:03 | 0.91 |
October | 0.137307E+10 | 0.91 | 512.65 | 01-OCT-00:10 | 0.91 |
November | 0.132878E+10 | 0.92 | 512.65 | 01-NOV-00:10 | 0.91 |
December | 0.137307E+10 | 0.92 | 512.65 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.161668E+11 | 0.92 | |||
Minimum of Months | 0.124019E+10 | 0.91 | 512.65 | 0.91 | |
Maximum of Months | 0.137307E+10 | 0.92 | 512.65 | 0.92 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 94325492.45 | 85741872.63 | 3169.93 | 02-JAN-05:21 | 2881.47 | 2881.47 | 47.23 | 27.63 |
February | 46896583.82 | 42628994.69 | 3159.65 | 06-FEB-06:02 | 2872.12 | 2872.12 | 46.82 | 27.59 |
March | 9101755.67 | 8273495.90 | 1066.60 | 17-MAR-05:01 | 969.54 | 969.54 | 44.57 | 17.08 |
April | 1714397.58 | 1558387.40 | 737.74 | 03-APR-05:02 | 670.60 | 670.60 | 40.32 | 14.41 |
May | 61397.62 | 55810.44 | 16.03 | 30-MAY-14:03 | 14.57 | 14.57 | 35.16 | 1.61 |
June | 133423.66 | 121282.11 | 20.13 | 01-JUN-14:50 | 18.29 | 18.29 | 36.14 | 1.89 |
July | 44366.44 | 40329.09 | 9.47 | 11-JUL-15:37 | 8.61 | 8.61 | 39.46 | 1.09 |
August | 178059.13 | 161855.75 | 25.35 | 24-AUG-17:10 | 23.05 | 23.05 | 43.58 | 2.21 |
September | 25883.99 | 23528.55 | 8.57 | 01-SEP-16:40 | 7.79 | 7.79 | 41.45 | 1.01 |
October | 180972.94 | 164504.40 | 135.52 | 28-OCT-05:03 | 123.19 | 123.19 | 34.60 | 6.11 |
November | 10152390.13 | 9228522.63 | 1090.13 | 22-NOV-06:01 | 990.93 | 990.93 | 45.07 | 17.25 |
December | 21243973.76 | 19310772.15 | 1065.72 | 02-DEC-06:01 | 968.74 | 968.74 | 44.88 | 17.07 |
Annual Sum or Average | 0.184059E+09 | 0.167309E+09 | ||||||
Minimum of Months | 25883.99 | 23528.55 | 8.57 | 7.79 | 7.79 | 34.60 | 1.01 | |
Maximum of Months | 94325492.45 | 85741872.63 | 3169.93 | 2881.47 | 2881.47 | 47.23 | 27.63 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 43006.47 | 39092.88 | 14.57 | 24-JAN-06:02 | 13.24 | 13.24 | 6.70 | 2.54 |
February | 107379.44 | 97607.91 | 3.12 | 24-FEB-15:50 | 2.83 | 2.83 | 6.70 | 0.77 |
March | 4878234.63 | 4434315.28 | 244.51 | 27-MAR-16:00 | 222.26 | 222.26 | 6.70 | 13.24 |
April | 68184603.59 | 61979804.66 | 3034.90 | 07-APR-14:50 | 2758.72 | 2758.72 | 7.74 | 41.91 |
May | 0.249669E+09 | 0.226949E+09 | 7227.12 | 30-MAY-14:07 | 6569.46 | 6569.46 | 6.72 | 59.83 |
June | 0.996970E+09 | 0.906246E+09 | 11828.47 | 14-JUN-05:03 | 10752.08 | 10752.08 | 9.72 | 72.74 |
July | 0.136893E+10 | 0.124435E+10 | 11828.47 | 01-JUL-05:03 | 10752.08 | 10752.08 | 10.05 | 72.74 |
August | 0.163725E+10 | 0.148826E+10 | 11828.47 | 01-AUG-05:02 | 10752.08 | 10752.08 | 9.83 | 72.74 |
September | 0.721704E+09 | 0.656029E+09 | 11828.47 | 05-SEP-04:12 | 10752.08 | 10752.08 | 9.25 | 72.74 |
October | 0.404614E+09 | 0.367794E+09 | 11514.72 | 04-OCT-13:30 | 10466.88 | 10466.88 | 11.64 | 71.94 |
November | 8602034.02 | 7819248.92 | 464.24 | 10-NOV-06:03 | 422.00 | 422.00 | 6.70 | 18.12 |
December | 324322.04 | 294808.74 | 3.70 | 18-DEC-11:20 | 3.36 | 3.36 | 6.70 | 0.89 |
Annual Sum or Average | 0.546127E+10 | 0.496429E+10 | ||||||
Minimum of Months | 43006.47 | 39092.88 | 3.12 | 2.83 | 2.83 | 6.70 | 0.77 | |
Maximum of Months | 0.163725E+10 | 0.148826E+10 | 11828.47 | 10752.08 | 10752.08 | 11.64 | 72.74 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.461179E+09 | 0.419212E+09 | 4070.61 | 04-JAN-07:05 | 3700.18 | 3700.18 | 6.72 | 36.37 |
February | 0.761583E+09 | 0.692279E+09 | 4070.61 | 01-FEB-13:40 | 3700.18 | 3700.18 | 6.72 | 36.37 |
March | 0.187395E+10 | 0.170342E+10 | 4070.61 | 01-MAR-07:03 | 3700.18 | 3700.18 | 6.72 | 36.37 |
April | 0.246507E+10 | 0.224075E+10 | 4070.61 | 01-APR-08:30 | 3700.18 | 3700.18 | 6.72 | 36.37 |
May | 0.487207E+10 | 0.442871E+10 | 4070.61 | 01-MAY-09:20 | 3700.18 | 3700.18 | 6.73 | 36.37 |
June | 0.750574E+10 | 0.682272E+10 | 4070.61 | 01-JUN-04:12 | 3700.18 | 3700.18 | 9.88 | 36.37 |
July | 0.950671E+10 | 0.864160E+10 | 4070.61 | 01-JUL-04:12 | 3700.18 | 3700.18 | 11.90 | 36.37 |
August | 0.981138E+10 | 0.891854E+10 | 4070.61 | 01-AUG-00:05 | 3700.18 | 3700.18 | 6.93 | 36.37 |
September | 0.633382E+10 | 0.575744E+10 | 4070.61 | 01-SEP-00:15 | 3700.18 | 3700.18 | 6.92 | 36.37 |
October | 0.421682E+10 | 0.383309E+10 | 4070.61 | 02-OCT-04:12 | 3700.18 | 3700.18 | 7.13 | 36.37 |
November | 0.164565E+10 | 0.149590E+10 | 4070.61 | 01-NOV-07:13 | 3700.18 | 3700.18 | 6.80 | 36.37 |
December | 0.131181E+10 | 0.119244E+10 | 4070.61 | 01-DEC-09:00 | 3700.18 | 3700.18 | 6.73 | 36.37 |
Annual Sum or Average | 0.507658E+11 | 0.461461E+11 | ||||||
Minimum of Months | 0.461179E+09 | 0.419212E+09 | 4070.61 | 3700.18 | 3700.18 | 6.72 | 36.37 | |
Maximum of Months | 0.981138E+10 | 0.891854E+10 | 4070.61 | 3700.18 | 3700.18 | 11.90 | 36.37 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
May | 0.188062E+09 | 0.170948E+09 | 4070.61 | 30-MAY-09:00 | 3700.18 | 3700.18 | 15.05 | 18.18 |
June | 0.147926E+10 | 0.134465E+10 | 4070.61 | 01-JUN-10:00 | 3700.18 | 3700.18 | 15.52 | 18.18 |
July | 0.257490E+10 | 0.234059E+10 | 4070.61 | 03-JUL-07:20 | 3700.18 | 3700.18 | 15.99 | 18.18 |
August | 0.254063E+10 | 0.230943E+10 | 4070.61 | 01-AUG-05:04 | 3700.18 | 3700.18 | 15.45 | 18.18 |
September | 0.809644E+09 | 0.735966E+09 | 4070.61 | 01-SEP-07:20 | 3700.18 | 3700.18 | 15.57 | 18.18 |
October | 0.299800E+09 | 0.272518E+09 | 4070.61 | 03-OCT-10:20 | 3700.18 | 3700.18 | 15.24 | 18.18 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.83 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.789229E+10 | 0.717410E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.257490E+10 | 0.234059E+10 | 4070.61 | 3700.18 | 3700.18 | 15.99 | 18.18 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.892467E+10 | 0.811253E+10 | 3332.09 | 01-JAN-00:01 | 3028.87 | 3028.87 | 18.49 | 14.06 |
February | 0.806100E+10 | 0.732745E+10 | 3332.09 | 01-FEB-00:10 | 3028.87 | 3028.87 | 19.19 | 14.06 |
March | 0.892467E+10 | 0.811253E+10 | 3332.09 | 01-MAR-00:10 | 3028.87 | 3028.87 | 19.69 | 14.06 |
April | 0.863678E+10 | 0.785083E+10 | 3332.09 | 01-APR-00:10 | 3028.87 | 3028.87 | 20.45 | 14.06 |
May | 0.892467E+10 | 0.811253E+10 | 3332.09 | 01-MAY-00:10 | 3028.87 | 3028.87 | 18.89 | 14.06 |
June | 0.863678E+10 | 0.785083E+10 | 3332.09 | 01-JUN-00:10 | 3028.87 | 3028.87 | 20.16 | 14.06 |
July | 0.892467E+10 | 0.811253E+10 | 3332.09 | 01-JUL-00:10 | 3028.87 | 3028.87 | 33.40 | 14.06 |
August | 0.892467E+10 | 0.811253E+10 | 3332.09 | 01-AUG-00:05 | 3028.87 | 3028.87 | 41.77 | 14.06 |
September | 0.863678E+10 | 0.785083E+10 | 3332.09 | 01-SEP-00:03 | 3028.87 | 3028.87 | 29.69 | 14.06 |
October | 0.892467E+10 | 0.811253E+10 | 3332.09 | 01-OCT-00:10 | 3028.87 | 3028.87 | 19.45 | 14.06 |
November | 0.863678E+10 | 0.785083E+10 | 3332.09 | 01-NOV-00:10 | 3028.87 | 3028.87 | 19.88 | 14.06 |
December | 0.892467E+10 | 0.811253E+10 | 3332.09 | 01-DEC-00:10 | 3028.87 | 3028.87 | 20.36 | 14.06 |
Annual Sum or Average | 0.105081E+12 | 0.955185E+11 | ||||||
Minimum of Months | 0.806100E+10 | 0.732745E+10 | 3332.09 | 3028.87 | 3028.87 | 18.49 | 14.06 | |
Maximum of Months | 0.892467E+10 | 0.811253E+10 | 3332.09 | 3028.87 | 3028.87 | 41.77 | 14.06 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:02 | 16.86 | 16.86 | 56.04 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.33 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.64 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.41 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.66 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 55.80 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.01 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.82 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.19 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 55.91 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 55.91 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 55.66 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.64 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.19 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.175243E+10 | 0.159296E+10 | 15470.45 | 20-JAN-14:25 | 14062.64 | 14062.64 | 21.17 | 63.32 |
February | 0.289392E+10 | 0.263058E+10 | 15470.86 | 22-FEB-15:40 | 14063.01 | 14063.01 | 21.21 | 63.32 |
March | 0.712200E+10 | 0.647390E+10 | 15495.30 | 27-MAR-16:00 | 14085.23 | 14085.23 | 23.41 | 63.32 |
April | 0.937390E+10 | 0.852088E+10 | 15545.30 | 07-APR-15:00 | 14130.68 | 14130.68 | 27.47 | 63.32 |
May | 0.192139E+11 | 0.174654E+11 | 31069.44 | 31-MAY-12:30 | 28242.12 | 28242.12 | 26.66 | 126.64 |
June | 0.335085E+11 | 0.304592E+11 | 31125.55 | 15-JUN-09:05 | 28293.13 | 28293.13 | 29.37 | 126.64 |
July | 0.453602E+11 | 0.412324E+11 | 31125.55 | 03-JUL-14:05 | 28293.13 | 28293.13 | 29.09 | 126.64 |
August | 0.466094E+11 | 0.423679E+11 | 31125.55 | 01-AUG-09:50 | 28293.13 | 28293.13 | 28.98 | 126.64 |
September | 0.269677E+11 | 0.245137E+11 | 31125.55 | 07-SEP-12:20 | 28293.13 | 28293.13 | 28.84 | 126.64 |
October | 0.170962E+11 | 0.155405E+11 | 31087.51 | 03-OCT-12:43 | 28258.55 | 28258.55 | 27.35 | 126.64 |
November | 0.625519E+10 | 0.568597E+10 | 15497.11 | 03-NOV-15:10 | 14086.87 | 14086.87 | 23.57 | 63.32 |
December | 0.498474E+10 | 0.453113E+10 | 15471.64 | 18-DEC-14:40 | 14063.72 | 14063.72 | 21.28 | 63.32 |
Annual Sum or Average | 0.221138E+12 | 0.201015E+12 | ||||||
Minimum of Months | 0.175243E+10 | 0.159296E+10 | 15470.45 | 14062.64 | 14062.64 | 21.17 | 63.32 | |
Maximum of Months | 0.466094E+11 | 0.423679E+11 | 31125.55 | 28293.13 | 28293.13 | 29.37 | 126.64 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.16 | 48188.11 | 31-JAN-11:00 | 55.80 | 55.80 | 94983.89 | 2144040.66 | 03-JAN-05:21 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 36.82 | 36.82 | 71278.02 | 1769755.45 | 22-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 30.01 | 30.01 | 19421.40 | 1854835.06 | 11-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30.86 | 30.86 | 5397.55 | 1765651.39 | 22-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 29.30 | 29.30 | 319.67 | 167211.72 | 30-MAY-14:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 35.68 | 35.68 | 468.52 | 188488.59 | 01-JUN-14:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 43.95 | 43.95 | 192.93 | 93417.32 | 11-JUL-15:37 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 38.18 | 38.18 | 512.89 | 151745.24 | 24-AUG-17:07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 42.67 | 42.67 | 101.61 | 78050.04 | 01-SEP-16:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 42.81 | 42.81 | 850.38 | 648764.01 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29.95 | 29.95 | 21144.87 | 1930614.37 | 15-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 31.92 | 31.92 | 45570.85 | 1797337.17 | 21-DEC-05:01 |
Annual Sum or Average | 1.37 | 21442.67 | ||||||
Minimum of Months | 0.00 | 0.00 | 29.30 | 29.30 | 101.61 | 78050.04 | ||
Maximum of Months | 16.16 | 48188.11 | 55.80 | 55.80 | 94983.89 | 2144040.66 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 273.83 | 52133.36 | 24-JAN-06:02 | 7.04 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 764.73 | 34270.59 | 24-FEB-15:50 | 6.92 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9748.81 | 530180.16 | 27-MAR-16:00 | 10.18 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 47436.02 | 1217922.83 | 07-APR-15:00 | 14.70 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 142975.88 | 2055056.64 | 30-MAY-09:07 | 13.45 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 499091.12 | 2135319.96 | 22-JUN-13:25 | 13.71 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 648978.44 | 2721222.15 | 24-JUL-05:03 | 15.64 | 7.14 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 634662.61 | 2401945.95 | 22-AUG-12:03 | 14.59 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 341873.80 | 2229407.79 | 01-SEP-13:12 | 14.02 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 157862.67 | 2206131.47 | 03-OCT-12:43 | 13.95 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 13508.69 | 584703.60 | 03-NOV-15:10 | 10.54 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1835.36 | 41195.72 | 20-DEC-10:30 | 6.97 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 209767.58 | 0.00 | ||||||
Minimum of Months | 273.83 | 34270.59 | 6.92 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 648978.44 | 2721222.15 | 15.64 | 7.14 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117.48 | 91171.97 | 24-JAN-06:02 | 15.29 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 478.59 | 33092.31 | 24-FEB-15:50 | 16.93 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9116.72 | 534789.65 | 27-MAR-16:00 | 16.35 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46780.94 | 1389617.44 | 07-APR-14:50 | 14.62 | 7.73 | 0.00 | 0.00 | 01-APR-00:10 |
May | 141817.18 | 2024454.84 | 30-MAY-14:07 | 14.78 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 499053.41 | 3472678.05 | 27-JUN-04:11 | 18.12 | 12.39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 648939.23 | 3507083.97 | 28-JUL-05:03 | 18.23 | 12.45 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 635484.17 | 3419515.33 | 17-AUG-05:02 | 17.94 | 12.30 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 341830.18 | 3434936.67 | 14-SEP-05:03 | 17.99 | 12.33 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 160369.30 | 2624722.31 | 04-OCT-13:30 | 15.42 | 11.63 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 12937.51 | 611184.78 | 03-NOV-15:10 | 15.58 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1390.22 | 37604.96 | 20-DEC-10:30 | 17.49 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 209714.31 | 0.00 | ||||||
Minimum of Months | 117.48 | 33092.31 | 14.62 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 648939.23 | 3507083.97 | 18.23 | 12.45 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10938.26 | 53797.32 | 12-JAN-15:50 | 19.43 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 41817.03 | 78963.08 | 01-FEB-12:30 | 19.95 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 81209.64 | 730021.72 | 27-MAR-16:00 | 33.12 | 25.46 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 205919.31 | 1302271.24 | 07-APR-13:00 | 44.43 | 32.06 | 0.00 | 0.00 | 01-APR-00:10 |
May | 89420.17 | 966125.64 | 30-MAY-13:55 | 37.82 | 31.93 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 527491.21 | 1479699.56 | 19-JUN-12:00 | 47.89 | 40.10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1039550.47 | 1547016.33 | 07-JUL-12:00 | 49.19 | 38.55 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1195553.54 | 1733875.23 | 24-AUG-15:42 | 52.81 | 39.67 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 234684.50 | 1100841.88 | 01-SEP-13:40 | 40.48 | 33.81 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 109905.22 | 863187.27 | 04-OCT-13:10 | 35.77 | 28.16 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76968.53 | 230267.26 | 04-NOV-13:00 | 23.04 | 19.35 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 98481.63 | 150257.27 | 04-DEC-17:50 | 21.41 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312053.73 | 0.00 | ||||||
Minimum of Months | 10938.26 | 53797.32 | 19.43 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1195553.54 | 1733875.23 | 52.81 | 40.10 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.13 | 57.13 | 15951.29 | 53759.63 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.90 | 56.90 | 16183.26 | 53879.71 | 06-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.27 | 56.27 | 16751.03 | 53447.32 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.95 | 56.95 | 15050.60 | 51229.75 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.52 | 57.52 | 14533.25 | 48327.77 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.29 | 56.29 | 13875.85 | 44828.67 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.52 | 56.52 | 12278.62 | 41916.16 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.23 | 57.23 | 13141.77 | 40963.63 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.73 | 57.73 | 12759.42 | 42849.13 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.45 | 56.45 | 13490.37 | 46119.10 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.49 | 56.49 | 14617.05 | 49506.74 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.22 | 56.22 | 15004.21 | 52217.08 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14459.96 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.22 | 56.22 | 12278.62 | 40963.63 | ||
Maximum of Months | 0.00 | 0.00 | 57.73 | 57.73 | 16751.03 | 53879.71 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19.41 | 19446.88 | 20-JAN-14:25 | 21.17 | 20.40 | 1769.86 | 141426.30 | 07-JAN-11:10 |
February | 48.10 | 29161.27 | 22-FEB-15:40 | 21.21 | 20.28 | 3406.43 | 161409.06 | 28-FEB-05:01 |
March | 7950.62 | 610297.27 | 27-MAR-16:00 | 23.41 | 21.10 | 4582.31 | 146417.26 | 17-MAR-06:50 |
April | 54758.08 | 1685866.33 | 07-APR-15:00 | 27.47 | 22.26 | 1459.96 | 113883.68 | 21-APR-09:30 |
May | 183783.25 | 2941893.98 | 31-MAY-12:30 | 26.66 | 23.54 | 896.69 | 85792.66 | 01-MAY-15:50 |
June | 933617.23 | 5186306.99 | 19-JUN-08:40 | 30.90 | 27.45 | 230.60 | 68770.21 | 09-JUN-06:00 |
July | 1661041.11 | 5717996.33 | 20-JUL-14:30 | 31.90 | 28.20 | 4.45 | 10068.97 | 11-JUL-03:00 |
August | 1446717.30 | 6013527.51 | 03-AUG-14:05 | 32.46 | 28.66 | 479.00 | 51447.51 | 24-AUG-22:40 |
September | 585643.58 | 4743966.59 | 07-SEP-14:05 | 30.06 | 26.54 | 481.79 | 69403.54 | 29-SEP-18:40 |
October | 213684.48 | 3308791.39 | 03-OCT-12:43 | 27.35 | 23.34 | 1076.22 | 134618.44 | 31-OCT-07:30 |
November | 14101.49 | 653200.74 | 03-NOV-15:10 | 23.57 | 21.10 | 3345.42 | 144573.26 | 24-NOV-14:50 |
December | 155.59 | 47773.53 | 18-DEC-14:40 | 21.28 | 20.47 | 5187.61 | 149547.30 | 15-DEC-14:30 |
Annual Sum or Average | 428928.39 | 1903.54 | ||||||
Minimum of Months | 19.41 | 19446.88 | 21.17 | 20.28 | 4.45 | 10068.97 | ||
Maximum of Months | 1661041.11 | 6013527.51 | 32.46 | 28.66 | 5187.61 | 161409.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.258664E+10 | 0.00 | 0.403654E+09 | 0.258404E+10 | 0.00 | 0.00 |
February | 0.173677E+10 | 0.00 | 0.100775E+10 | 0.277096E+10 | 0.00 | 0.00 |
March | 0.443449E+09 | 0.00 | 0.504468E+10 | 0.502301E+10 | 0.00 | 0.00 |
April | 0.103843E+09 | 0.00 | 0.124807E+11 | 0.683909E+10 | 0.00 | 0.00 |
May | 23963964.96 | 0.00 | 0.339305E+11 | 0.700119E+10 | 0.00 | 0.00 |
June | 0.117145E+09 | 0.00 | 0.113738E+12 | 0.100488E+11 | 0.00 | 0.00 |
July | 61901400.22 | 0.00 | 0.157088E+12 | 0.118836E+11 | 0.00 | 0.00 |
August | 0.120258E+09 | 0.00 | 0.161205E+12 | 0.138080E+11 | 0.00 | 0.00 |
September | 7131794.00 | 0.00 | 0.758084E+11 | 0.752607E+10 | 0.00 | 0.00 |
October | 34273687.68 | 0.00 | 0.383038E+11 | 0.708458E+10 | 0.00 | 0.00 |
November | 0.291905E+09 | 0.00 | 0.318571E+10 | 0.454683E+10 | 0.00 | 0.00 |
December | 0.610610E+09 | 0.00 | 0.341458E+10 | 0.399422E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.613790E+10 | 0.00 | 0.605610E+12 | 0.831104E+11 | 0.00 | 0.00 |
Minimum of Months | 7131794.00 | 0.00 | 0.403654E+09 | 0.258404E+10 | 0.00 | 0.00 |
Maximum of Months | 0.258664E+10 | 0.00 | 0.161205E+12 | 0.138080E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.210663E+12 | 0.00 | 48935580.64 | 0.256726E+11 | 0.00 | 0.00 |
February | 0.138079E+12 | 0.00 | 0.166581E+09 | 0.230564E+11 | 0.00 | 0.00 |
March | 0.397624E+11 | 0.00 | 0.180189E+11 | 0.270938E+11 | 0.00 | 0.00 |
April | 0.100279E+11 | 0.00 | 0.950080E+11 | 0.340851E+11 | 0.00 | 0.00 |
May | 0.568753E+09 | 0.00 | 0.295081E+12 | 0.520924E+11 | 0.00 | 0.00 |
June | 0.914922E+09 | 0.00 | 0.946767E+12 | 0.755601E+11 | 0.00 | 0.00 |
July | 0.479800E+09 | 0.00 | 0.126326E+13 | 0.866692E+11 | 0.00 | 0.00 |
August | 0.111665E+10 | 0.00 | 0.123954E+13 | 0.956056E+11 | 0.00 | 0.00 |
September | 0.236389E+09 | 0.00 | 0.659382E+12 | 0.577781E+11 | 0.00 | 0.00 |
October | 0.139599E+10 | 0.00 | 0.320611E+12 | 0.439169E+11 | 0.00 | 0.00 |
November | 0.408372E+11 | 0.00 | 0.296448E+11 | 0.242368E+11 | 0.00 | 0.00 |
December | 0.948706E+11 | 0.00 | 0.274703E+09 | 0.227039E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.538953E+12 | 0.00 | 0.486780E+13 | 0.568471E+12 | 0.00 | 0.00 |
Minimum of Months | 0.236389E+09 | 0.00 | 48935580.64 | 0.227039E+11 | 0.00 | 0.00 |
Maximum of Months | 0.210663E+12 | 0.00 | 0.126326E+13 | 0.956056E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.416532E+11 | 0.00 | 9540862.98 | 0.310322E+10 | 0.00 | 0.00 |
February | 0.329619E+11 | 0.00 | 18098289.14 | 0.268850E+10 | 0.00 | 0.00 |
March | 0.118716E+11 | 0.00 | 0.802188E+09 | 0.270650E+10 | 0.00 | 0.00 |
April | 0.389848E+10 | 0.00 | 0.829779E+10 | 0.316120E+10 | 0.00 | 0.00 |
May | 0.177216E+09 | 0.00 | 0.302314E+11 | 0.491989E+10 | 0.00 | 0.00 |
June | 70440341.43 | 0.00 | 0.102440E+12 | 0.783764E+10 | 0.00 | 0.00 |
July | 54866763.24 | 0.00 | 0.141254E+12 | 0.945807E+10 | 0.00 | 0.00 |
August | 77189816.06 | 0.00 | 0.136729E+12 | 0.102405E+11 | 0.00 | 0.00 |
September | 18119087.90 | 0.00 | 0.672082E+11 | 0.549316E+10 | 0.00 | 0.00 |
October | 0.102642E+10 | 0.00 | 0.272795E+11 | 0.373607E+10 | 0.00 | 0.00 |
November | 0.137267E+11 | 0.00 | 0.634438E+09 | 0.240108E+10 | 0.00 | 0.00 |
December | 0.265915E+11 | 0.00 | 27716048.84 | 0.264847E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.132128E+12 | 0.00 | 0.514933E+12 | 0.583943E+11 | 0.00 | 0.00 |
Minimum of Months | 18119087.90 | 0.00 | 9540862.98 | 0.240108E+10 | 0.00 | 0.00 |
Maximum of Months | 0.416532E+11 | 0.00 | 0.141254E+12 | 0.102405E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 7265902.43 | 0.114986E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 5257.73 | 0.106072E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.562617E+09 | 0.127838E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.511323E+10 | 0.116448E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.146669E+11 | 0.124938E+11 | 0.00 | 0.00 |
June | 334.22 | 0.00 | 0.617354E+11 | 0.122845E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.895414E+11 | 0.122053E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.906345E+11 | 0.135617E+11 | 0.00 | 0.00 |
September | 402.37 | 0.00 | 0.471375E+11 | 0.125735E+11 | 0.00 | 0.00 |
October | 508.18 | 0.00 | 0.184637E+11 | 0.126920E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.154824E+09 | 0.120937E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 9637.81 | 0.117903E+11 | 0.00 | 0.00 |
Annual Sum or Average | 1244.77 | 0.00 | 0.328017E+12 | 0.146229E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5257.73 | 0.106072E+11 | 0.00 | 0.00 |
Maximum of Months | 508.18 | 0.00 | 0.906345E+11 | 0.135617E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.893673E+10 | 0.209806E+12 | 0.00 | 41.69 |
February | 0.00 | 0.00 | 0.152453E+11 | 0.296921E+12 | 0.00 | 77.06 |
March | 0.00 | 0.00 | 0.220911E+11 | 0.295949E+12 | 0.00 | 72.69 |
April | 0.00 | 0.00 | 0.180917E+12 | 0.262636E+12 | 0.00 | 49.68 |
May | 0.00 | 0.00 | 0.304212E+11 | 0.148813E+12 | 0.00 | 17.21 |
June | 0.00 | 0.00 | 0.470702E+12 | 0.205418E+12 | 0.00 | 5.99 |
July | 0.00 | 0.00 | 0.105781E+13 | 0.319629E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.129158E+13 | 0.378066E+12 | 0.00 | 3.46 |
September | 0.00 | 0.00 | 0.118888E+12 | 0.132896E+12 | 0.00 | 5.60 |
October | 0.00 | 0.00 | 0.582622E+11 | 0.199809E+12 | 0.00 | 34.24 |
November | 0.00 | 0.00 | 0.190890E+11 | 0.276464E+12 | 0.00 | 66.81 |
December | 0.00 | 0.00 | 0.212026E+11 | 0.355559E+12 | 0.00 | 94.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.329515E+13 | 0.308197E+13 | 0.00 | 469.23 |
Minimum of Months | 0.00 | 0.00 | 0.893673E+10 | 0.132896E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.129158E+13 | 0.378066E+12 | 0.00 | 94.81 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.391155E+10 | 0.216088E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.971286E+10 | 0.304393E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.179086E+11 | 0.444925E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.235944E+11 | 0.523466E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.678876E+10 | 0.264885E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135138E+11 | 0.398209E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.209933E+11 | 0.581993E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272657E+11 | 0.708875E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.708622E+10 | 0.271720E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129223E+11 | 0.365712E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.173402E+11 | 0.427599E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.236238E+11 | 0.536571E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184661E+12 | 0.504444E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.391155E+10 | 0.216088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272657E+11 | 0.708875E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.819334E+10 | 0.151953E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.641786E+11 | 0.241923E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.150108E+12 | 0.392994E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.212625E+12 | 0.482107E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.588082E+11 | 0.243168E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126819E+12 | 0.376921E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200137E+12 | 0.555678E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259737E+12 | 0.676494E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.629071E+11 | 0.251559E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113938E+12 | 0.334504E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.142068E+12 | 0.372463E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.193222E+12 | 0.464397E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159274E+13 | 0.454416E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.819334E+10 | 0.151953E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259737E+12 | 0.676494E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.294348E+09 | 0.143551E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.462522E+10 | 0.212225E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.134325E+11 | 0.370748E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.202400E+11 | 0.470201E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.550733E+10 | 0.239615E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127013E+11 | 0.380405E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201787E+11 | 0.562253E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260792E+11 | 0.682433E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.605223E+10 | 0.250231E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104040E+11 | 0.321052E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.123532E+11 | 0.345800E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.171302E+11 | 0.433529E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148998E+12 | 0.441204E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.294348E+09 | 0.143551E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260792E+11 | 0.682433E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.258404E+10 | 0.403654E+09 | 0.258664E+10 | 0.244730E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277096E+10 | 0.100775E+10 | 0.173677E+10 | 0.228138E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.502301E+10 | 0.504468E+10 | 0.443449E+09 | 0.847931E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.683909E+10 | 0.124807E+11 | 0.103843E+09 | 0.160120E+10 | 12516167.16 | 0.00 | 0.00 | 0.00 |
May | 0.700119E+10 | 0.339305E+11 | 23963964.96 | 2001972.79 | 0.235756E+09 | 0.00 | 0.00 | 0.00 |
June | 0.100488E+11 | 0.113738E+12 | 0.117145E+09 | 0.00 | 0.398162E+10 | 0.00 | 0.00 | 0.00 |
July | 0.118836E+11 | 0.157088E+12 | 61901400.22 | 0.00 | 0.164062E+11 | 0.00 | 0.00 | 0.00 |
August | 0.138080E+11 | 0.161205E+12 | 0.120258E+09 | 0.00 | 0.162647E+11 | 0.00 | 0.00 | 0.00 |
September | 0.752607E+10 | 0.758084E+11 | 7131794.00 | 0.00 | 0.223328E+10 | 0.00 | 0.00 | 0.00 |
October | 0.708458E+10 | 0.383038E+11 | 34273687.68 | 0.269945E+09 | 28220818.57 | 0.00 | 0.00 | 0.00 |
November | 0.454683E+10 | 0.318571E+10 | 0.291905E+09 | 0.487563E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399422E+10 | 0.341458E+10 | 0.610610E+09 | 0.115728E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.831104E+11 | 0.605610E+12 | 0.613790E+10 | 0.740877E+11 | 0.391624E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258404E+10 | 0.403654E+09 | 7131794.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138080E+11 | 0.161205E+12 | 0.258664E+10 | 0.244730E+11 | 0.164062E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.256726E+11 | 48935580.64 | 0.210663E+12 | 0.282008E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230564E+11 | 0.166581E+09 | 0.138079E+12 | 0.272752E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270938E+11 | 0.180189E+11 | 0.397624E+11 | 0.152229E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340851E+11 | 0.950080E+11 | 0.100279E+11 | 0.372873E+11 | 0.144231E+09 | 0.00 | 0.00 | 0.00 |
May | 0.520924E+11 | 0.295081E+12 | 0.568753E+09 | 0.523122E+09 | 0.241799E+10 | 0.00 | 0.00 | 0.00 |
June | 0.755601E+11 | 0.946767E+12 | 0.914922E+09 | 0.00 | 0.405041E+11 | 0.00 | 0.00 | 0.00 |
July | 0.866692E+11 | 0.126326E+13 | 0.479800E+09 | 0.00 | 0.165794E+12 | 0.00 | 0.00 | 0.00 |
August | 0.956056E+11 | 0.123954E+13 | 0.111665E+10 | 0.00 | 0.165692E+12 | 0.00 | 0.00 | 0.00 |
September | 0.577781E+11 | 0.659382E+12 | 0.236389E+09 | 22115843.46 | 0.229772E+11 | 0.00 | 0.00 | 0.00 |
October | 0.439169E+11 | 0.320611E+12 | 0.139599E+10 | 0.588783E+10 | 0.328465E+09 | 0.00 | 0.00 | 0.00 |
November | 0.242368E+11 | 0.296448E+11 | 0.408372E+11 | 0.977326E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227039E+11 | 0.274703E+09 | 0.948706E+11 | 0.215119E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.568471E+12 | 0.486780E+13 | 0.538953E+12 | 0.106356E+13 | 0.397858E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227039E+11 | 48935580.64 | 0.236389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956056E+11 | 0.126326E+13 | 0.210663E+12 | 0.282008E+12 | 0.165794E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.310322E+10 | 9540862.98 | 0.416532E+11 | 0.292643E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268850E+10 | 18098289.14 | 0.329619E+11 | 0.289117E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270650E+10 | 0.802188E+09 | 0.118716E+11 | 0.170964E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316120E+10 | 0.829779E+10 | 0.389848E+10 | 0.507403E+10 | 2497563.54 | 0.00 | 0.00 | 0.00 |
May | 0.491989E+10 | 0.302314E+11 | 0.177216E+09 | 0.101269E+09 | 0.159896E+09 | 0.00 | 0.00 | 0.00 |
June | 0.783764E+10 | 0.102440E+12 | 70440341.43 | 0.00 | 0.330670E+10 | 0.00 | 0.00 | 0.00 |
July | 0.945807E+10 | 0.141254E+12 | 54866763.24 | 0.00 | 0.146922E+11 | 0.00 | 0.00 | 0.00 |
August | 0.102405E+11 | 0.136729E+12 | 77189816.06 | 0.00 | 0.149907E+11 | 0.00 | 0.00 | 0.00 |
September | 0.549316E+10 | 0.672082E+11 | 18119087.90 | 1690848.87 | 0.181227E+10 | 0.00 | 0.00 | 0.00 |
October | 0.373607E+10 | 0.272795E+11 | 0.102642E+10 | 0.104812E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240108E+10 | 0.634438E+09 | 0.137267E+11 | 0.117285E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264847E+10 | 27716048.84 | 0.265915E+11 | 0.244257E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.583943E+11 | 0.514933E+12 | 0.132128E+12 | 0.117652E+12 | 0.349642E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.240108E+10 | 9540862.98 | 18119087.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102405E+11 | 0.141254E+12 | 0.416532E+11 | 0.292643E+11 | 0.149907E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114986E+11 | 7265902.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106072E+11 | 5257.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127838E+11 | 0.562617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116448E+11 | 0.511323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124938E+11 | 0.146669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122845E+11 | 0.617354E+11 | 334.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122053E+11 | 0.895414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135617E+11 | 0.906345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125735E+11 | 0.471375E+11 | 402.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126920E+11 | 0.184637E+11 | 508.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120937E+11 | 0.154824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117903E+11 | 9637.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146229E+12 | 0.328017E+12 | 1244.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106072E+11 | 5257.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135617E+11 | 0.906345E+11 | 508.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.942726E+11 | 0.546816E+10 | 0.00 | 0.00 | 0.00 | 0.111563E+12 | 0.00 | 0.00 |
February | 0.851495E+11 | 0.106241E+11 | 0.00 | 0.00 | 0.00 | 0.206222E+12 | 0.00 | 0.00 |
March | 0.942726E+11 | 0.158226E+11 | 0.00 | 0.00 | 0.00 | 0.194532E+12 | 0.00 | 0.00 |
April | 0.912316E+11 | 0.143051E+12 | 0.00 | 0.00 | 0.00 | 0.132939E+12 | 0.00 | 0.00 |
May | 0.942726E+11 | 0.221344E+11 | 0.00 | 0.00 | 0.00 | 0.460461E+11 | 0.00 | 0.00 |
June | 0.912316E+11 | 0.372607E+12 | 0.00 | 0.00 | 0.00 | 0.160196E+11 | 0.00 | 0.00 |
July | 0.942726E+11 | 0.832456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.942726E+11 | 0.101709E+13 | 0.00 | 0.00 | 0.00 | 0.926179E+10 | 0.00 | 0.00 |
September | 0.912316E+11 | 0.922796E+11 | 0.00 | 0.00 | 0.00 | 0.149886E+11 | 0.00 | 0.00 |
October | 0.942726E+11 | 0.447646E+11 | 0.00 | 0.00 | 0.00 | 0.916267E+11 | 0.00 | 0.00 |
November | 0.912316E+11 | 0.134506E+11 | 0.00 | 0.00 | 0.00 | 0.178789E+12 | 0.00 | 0.00 |
December | 0.942726E+11 | 0.147888E+11 | 0.00 | 0.00 | 0.00 | 0.253731E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.110998E+13 | 0.258453E+13 | 0.00 | 0.00 | 0.00 | 0.125572E+13 | 0.00 | 0.00 |
Minimum of Months | 0.851495E+11 | 0.546816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942726E+11 | 0.101709E+13 | 0.00 | 0.00 | 0.00 | 0.253731E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140754E+10 | 0.315822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127133E+10 | 0.794025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140754E+10 | 0.148669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136214E+10 | 0.197219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140754E+10 | 0.554745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136214E+10 | 0.108938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140754E+10 | 0.165809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140754E+10 | 0.215845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136214E+10 | 0.573117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140754E+10 | 0.106727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136214E+10 | 0.144264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140754E+10 | 0.196656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165727E+11 | 0.150790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127133E+10 | 0.315822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140754E+10 | 0.215845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134761E+11 | 0.647414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121720E+11 | 0.521583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134761E+11 | 0.124285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130414E+11 | 0.177455E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134761E+11 | 0.479674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130414E+11 | 0.102168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134761E+11 | 0.158045E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134761E+11 | 0.205564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130414E+11 | 0.507926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134761E+11 | 0.939635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130414E+11 | 0.117863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134761E+11 | 0.160258E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158670E+12 | 0.129700E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121720E+11 | 0.647414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134761E+11 | 0.205564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137307E+10 | 0.231906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124019E+10 | 0.374316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137307E+10 | 0.110981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132878E+10 | 0.168667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137307E+10 | 0.448424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132878E+10 | 0.102260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137307E+10 | 0.159292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137307E+10 | 0.206280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132878E+10 | 0.487870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137307E+10 | 0.856651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132878E+10 | 0.102240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137307E+10 | 0.141679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161668E+11 | 0.121044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124019E+10 | 0.231906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137307E+10 | 0.206280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.258404E+10 | 0.258664E+10 | 0.403654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277096E+10 | 0.173677E+10 | 0.100775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.502301E+10 | 0.443449E+09 | 0.504468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.683909E+10 | 0.103843E+09 | 0.124807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.700119E+10 | 23963964.96 | 0.339305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100488E+11 | 0.117145E+09 | 0.113738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118836E+11 | 61901400.22 | 0.157088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138080E+11 | 0.120258E+09 | 0.161205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.752607E+10 | 7131794.00 | 0.758084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708458E+10 | 34273687.68 | 0.383038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454683E+10 | 0.291905E+09 | 0.318571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399422E+10 | 0.610610E+09 | 0.341458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.831104E+11 | 0.613790E+10 | 0.605610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258404E+10 | 7131794.00 | 0.403654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138080E+11 | 0.258664E+10 | 0.161205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.256726E+11 | 0.210663E+12 | 48935580.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230564E+11 | 0.138079E+12 | 0.166581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270938E+11 | 0.397624E+11 | 0.180189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340851E+11 | 0.100279E+11 | 0.950080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.520924E+11 | 0.568753E+09 | 0.295081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.755601E+11 | 0.914922E+09 | 0.946767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.866692E+11 | 0.479800E+09 | 0.126326E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.956056E+11 | 0.111665E+10 | 0.123954E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577781E+11 | 0.236389E+09 | 0.659382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439169E+11 | 0.139599E+10 | 0.320611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242368E+11 | 0.408372E+11 | 0.296448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227039E+11 | 0.948706E+11 | 0.274703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.568471E+12 | 0.538953E+12 | 0.486780E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227039E+11 | 0.236389E+09 | 48935580.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956056E+11 | 0.210663E+12 | 0.126326E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.310322E+10 | 0.416532E+11 | 9540862.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268850E+10 | 0.329619E+11 | 18098289.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270650E+10 | 0.118716E+11 | 0.802188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316120E+10 | 0.389848E+10 | 0.829779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491989E+10 | 0.177216E+09 | 0.302314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.783764E+10 | 70440341.43 | 0.102440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.945807E+10 | 54866763.24 | 0.141254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102405E+11 | 77189816.06 | 0.136729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.549316E+10 | 18119087.90 | 0.672082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373607E+10 | 0.102642E+10 | 0.272795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240108E+10 | 0.137267E+11 | 0.634438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264847E+10 | 0.265915E+11 | 27716048.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.583943E+11 | 0.132128E+12 | 0.514933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.240108E+10 | 18119087.90 | 9540862.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102405E+11 | 0.416532E+11 | 0.141254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114986E+11 | 0.00 | 7265902.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106072E+11 | 0.00 | 5257.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127838E+11 | 0.00 | 0.562617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116448E+11 | 0.00 | 0.511323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124938E+11 | 0.00 | 0.146669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122845E+11 | 334.22 | 0.617354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122053E+11 | 0.00 | 0.895414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135617E+11 | 0.00 | 0.906345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125735E+11 | 402.37 | 0.471375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126920E+11 | 508.18 | 0.184637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120937E+11 | 0.00 | 0.154824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117903E+11 | 0.00 | 9637.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146229E+12 | 1244.77 | 0.328017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106072E+11 | 0.00 | 5257.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135617E+11 | 508.18 | 0.906345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.942726E+11 | 0.00 | 0.893673E+10 | 0.00 | 0.346858E+10 | 0.00 | 0.00 | 0.00 | 0.112065E+12 | 0.00 | 0.00 | 0.00 |
February | 0.851495E+11 | 0.00 | 0.152453E+11 | 0.00 | 0.462115E+10 | 0.00 | 0.00 | 0.00 | 0.207150E+12 | 0.00 | 0.00 | 0.00 |
March | 0.942726E+11 | 0.00 | 0.220911E+11 | 0.00 | 0.626854E+10 | 0.00 | 0.00 | 0.00 | 0.195408E+12 | 0.00 | 0.00 | 0.00 |
April | 0.912316E+11 | 0.00 | 0.180917E+12 | 0.00 | 0.378667E+11 | 0.00 | 0.00 | 0.00 | 0.133538E+12 | 0.00 | 0.00 | 0.00 |
May | 0.942726E+11 | 0.00 | 0.304212E+11 | 0.00 | 0.828677E+10 | 0.00 | 0.00 | 0.00 | 0.462534E+11 | 0.00 | 0.00 | 0.00 |
June | 0.912316E+11 | 0.00 | 0.470702E+12 | 0.00 | 0.980952E+11 | 0.00 | 0.00 | 0.00 | 0.160917E+11 | 0.00 | 0.00 | 0.00 |
July | 0.942726E+11 | 0.00 | 0.105781E+13 | 0.00 | 0.225357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.942726E+11 | 0.00 | 0.129158E+13 | 0.00 | 0.274490E+12 | 0.00 | 0.00 | 0.00 | 0.930348E+10 | 0.00 | 0.00 | 0.00 |
September | 0.912316E+11 | 0.00 | 0.118888E+12 | 0.00 | 0.266083E+11 | 0.00 | 0.00 | 0.00 | 0.150561E+11 | 0.00 | 0.00 | 0.00 |
October | 0.942726E+11 | 0.00 | 0.582622E+11 | 0.00 | 0.134976E+11 | 0.00 | 0.00 | 0.00 | 0.920392E+11 | 0.00 | 0.00 | 0.00 |
November | 0.912316E+11 | 0.00 | 0.190890E+11 | 0.00 | 0.563834E+10 | 0.00 | 0.00 | 0.00 | 0.179594E+12 | 0.00 | 0.00 | 0.00 |
December | 0.942726E+11 | 0.00 | 0.212026E+11 | 0.00 | 0.641379E+10 | 0.00 | 0.00 | 0.00 | 0.254873E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110998E+13 | 0.00 | 0.329515E+13 | 0.00 | 0.710612E+12 | 0.00 | 0.00 | 0.00 | 0.126137E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.851495E+11 | 0.00 | 0.893673E+10 | 0.00 | 0.346858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942726E+11 | 0.00 | 0.129158E+13 | 0.00 | 0.274490E+12 | 0.00 | 0.00 | 0.00 | 0.254873E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140754E+10 | 0.00 | 0.391155E+10 | 0.00 | 0.753331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127133E+10 | 0.00 | 0.971286E+10 | 0.00 | 0.177260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140754E+10 | 0.00 | 0.179086E+11 | 0.00 | 0.304170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136214E+10 | 0.00 | 0.235944E+11 | 0.00 | 0.387252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140754E+10 | 0.00 | 0.678876E+10 | 0.00 | 0.124131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136214E+10 | 0.00 | 0.135138E+11 | 0.00 | 0.261995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140754E+10 | 0.00 | 0.209933E+11 | 0.00 | 0.441239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140754E+10 | 0.00 | 0.272657E+11 | 0.00 | 0.568120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136214E+10 | 0.00 | 0.708622E+10 | 0.00 | 0.135506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140754E+10 | 0.00 | 0.129223E+11 | 0.00 | 0.224957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136214E+10 | 0.00 | 0.173402E+11 | 0.00 | 0.291385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140754E+10 | 0.00 | 0.236238E+11 | 0.00 | 0.395817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165727E+11 | 0.00 | 0.184661E+12 | 0.00 | 0.338717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127133E+10 | 0.00 | 0.391155E+10 | 0.00 | 0.753331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140754E+10 | 0.00 | 0.272657E+11 | 0.00 | 0.568120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134761E+11 | 0.00 | 0.819334E+10 | 0.00 | 0.171920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121720E+11 | 0.00 | 0.641786E+11 | 0.00 | 0.120203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134761E+11 | 0.00 | 0.150108E+12 | 0.00 | 0.258233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130414E+11 | 0.00 | 0.212625E+12 | 0.00 | 0.351693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134761E+11 | 0.00 | 0.588082E+11 | 0.00 | 0.108407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130414E+11 | 0.00 | 0.126819E+12 | 0.00 | 0.246507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134761E+11 | 0.00 | 0.200137E+12 | 0.00 | 0.420917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134761E+11 | 0.00 | 0.259737E+12 | 0.00 | 0.541733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130414E+11 | 0.00 | 0.629071E+11 | 0.00 | 0.121145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134761E+11 | 0.00 | 0.113938E+12 | 0.00 | 0.199743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130414E+11 | 0.00 | 0.142068E+12 | 0.00 | 0.242049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134761E+11 | 0.00 | 0.193222E+12 | 0.00 | 0.329636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158670E+12 | 0.00 | 0.159274E+13 | 0.00 | 0.295746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121720E+11 | 0.00 | 0.819334E+10 | 0.00 | 0.171920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134761E+11 | 0.00 | 0.259737E+12 | 0.00 | 0.541733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137307E+10 | 0.00 | 0.294348E+09 | 0.00 | 62442100.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124019E+10 | 0.00 | 0.462522E+10 | 0.00 | 0.882057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137307E+10 | 0.00 | 0.134325E+11 | 0.00 | 0.233441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132878E+10 | 0.00 | 0.202400E+11 | 0.00 | 0.337324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137307E+10 | 0.00 | 0.550733E+10 | 0.00 | 0.102308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132878E+10 | 0.00 | 0.127013E+11 | 0.00 | 0.247528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137307E+10 | 0.00 | 0.201787E+11 | 0.00 | 0.424946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137307E+10 | 0.00 | 0.260792E+11 | 0.00 | 0.545126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132878E+10 | 0.00 | 0.605223E+10 | 0.00 | 0.117353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137307E+10 | 0.00 | 0.104040E+11 | 0.00 | 0.183746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132878E+10 | 0.00 | 0.123532E+11 | 0.00 | 0.212923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137307E+10 | 0.00 | 0.171302E+11 | 0.00 | 0.296222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161668E+11 | 0.00 | 0.148998E+12 | 0.00 | 0.279537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124019E+10 | 0.00 | 0.294348E+09 | 0.00 | 62442100.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137307E+10 | 0.00 | 0.260792E+11 | 0.00 | 0.545126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136399E+11 | 0.00 | 0.00 | 59712723.76 | 0.00 | 0.00 | 0.420923E+11 | 0.00 | 0.40 |
February | 0.889773E+10 | 0.00 | 0.00 | 63540900.21 | 0.00 | 0.00 | 0.439130E+11 | 0.00 | 0.39 |
March | 0.495943E+09 | 0.00 | 0.00 | 0.111254E+09 | 0.00 | 0.00 | 0.651628E+11 | 0.00 | 0.61 |
April | 0.390071E+09 | 15639388.32 | 0.00 | 0.101316E+09 | 0.00 | 0.00 | 0.577567E+11 | 0.00 | 0.83 |
May | 0.184597E+09 | 0.187375E+09 | 0.00 | 96940687.48 | 0.00 | 0.00 | 0.519026E+11 | 0.00 | 1.14 |
June | 98801869.07 | 0.606562E+10 | 0.00 | 51811177.21 | 38373663.09 | 0.00 | 0.141518E+11 | 0.00 | 0.85 |
July | 33495875.68 | 0.198477E+11 | 0.00 | 10412984.68 | 0.124644E+09 | 0.00 | 0.892359E+09 | 0.00 | 0.37 |
August | 67453120.31 | 0.167018E+11 | 0.00 | 41411932.56 | 0.149371E+09 | 0.00 | 0.577241E+10 | 0.00 | 0.65 |
September | 0.224776E+09 | 0.408427E+10 | 0.00 | 80828285.22 | 4090413.40 | 0.00 | 0.280764E+11 | 0.00 | 1.01 |
October | 0.400242E+09 | 0.123153E+09 | 0.00 | 0.121571E+09 | 0.00 | 0.00 | 0.553001E+11 | 0.00 | 1.10 |
November | 0.391512E+09 | 0.00 | 0.00 | 0.123013E+09 | 0.00 | 0.00 | 0.675326E+11 | 0.00 | 0.74 |
December | 0.575452E+09 | 0.00 | 0.00 | 0.117149E+09 | 0.00 | 0.00 | 0.637209E+11 | 0.00 | 0.49 |
Annual Sum or Average | 0.254000E+11 | 0.470256E+11 | 0.00 | 0.978961E+09 | 0.316479E+09 | 0.00 | 0.496274E+12 | 0.00 | 0.72 |
Minimum of Months | 33495875.68 | 0.00 | 0.00 | 10412984.68 | 0.00 | 0.00 | 0.892359E+09 | 0.00 | 0.37 |
Maximum of Months | 0.136399E+11 | 0.198477E+11 | 0.00 | 0.123013E+09 | 0.149371E+09 | 0.00 | 0.675326E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.922047E+10 | 0.00 | 0.00 | 36781387.97 | 0.00 | 0.00 | 0.233926E+11 | 0.00 | 0.33 |
February | 0.507376E+10 | 0.00 | 0.00 | 47129242.00 | 0.00 | 0.00 | 0.280187E+11 | 0.00 | 0.35 |
March | 0.177041E+10 | 0.00 | 0.00 | 90478941.36 | 0.00 | 0.00 | 0.470394E+11 | 0.00 | 0.48 |
April | 0.424974E+10 | 3421248.77 | 0.00 | 89320126.02 | 0.00 | 0.00 | 0.473855E+11 | 0.00 | 0.71 |
May | 0.262379E+10 | 96797397.65 | 0.00 | 80502471.54 | 0.00 | 0.00 | 0.371187E+11 | 0.00 | 0.80 |
June | 0.134280E+10 | 0.440422E+10 | 0.00 | 38793706.64 | 0.100369E+09 | 0.00 | 0.867825E+10 | 0.00 | 0.58 |
July | 0.263120E+09 | 0.906898E+10 | 0.00 | 1982128.70 | 0.167704E+09 | 0.00 | 0.262108E+09 | 0.00 | 0.27 |
August | 0.246008E+10 | 0.612050E+10 | 0.00 | 29096636.65 | 0.137611E+09 | 0.00 | 0.420339E+10 | 0.00 | 0.55 |
September | 0.184814E+10 | 0.292622E+10 | 0.00 | 55684644.85 | 30470460.06 | 0.00 | 0.185489E+11 | 0.00 | 0.65 |
October | 0.302445E+10 | 0.404194E+09 | 0.00 | 86705872.64 | 0.00 | 0.00 | 0.360045E+11 | 0.00 | 0.73 |
November | 0.135268E+10 | 0.00 | 0.00 | 85790689.89 | 0.00 | 0.00 | 0.468375E+11 | 0.00 | 0.53 |
December | 0.187860E+10 | 0.00 | 0.00 | 84127943.94 | 0.00 | 0.00 | 0.430604E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.351080E+11 | 0.230243E+11 | 0.00 | 0.726394E+09 | 0.436154E+09 | 0.00 | 0.340550E+12 | 0.00 | 0.53 |
Minimum of Months | 0.263120E+09 | 0.00 | 0.00 | 1982128.70 | 0.00 | 0.00 | 0.262108E+09 | 0.00 | 0.27 |
Maximum of Months | 0.922047E+10 | 0.906898E+10 | 0.00 | 90478941.36 | 0.167704E+09 | 0.00 | 0.473855E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208556E+12 | 0.00 | 0.00 | 4750156.67 | 0.00 | 0.760488E+10 | 0.741341E+10 | 0.00 | 0.30 |
February | 0.200548E+12 | 0.00 | 0.00 | 19848384.98 | 0.00 | 0.123420E+10 | 0.240767E+11 | 0.00 | 0.30 |
March | 0.154347E+12 | 0.00 | 0.00 | 0.186073E+09 | 0.00 | 0.00 | 0.140484E+12 | 0.00 | 0.34 |
April | 0.912127E+11 | 74203314.43 | 0.00 | 0.342674E+09 | 0.00 | 0.00 | 0.210235E+12 | 0.00 | 0.44 |
May | 0.294175E+11 | 0.102617E+10 | 0.00 | 0.561989E+09 | 0.00 | 0.00 | 0.278063E+12 | 0.00 | 0.64 |
June | 0.857885E+10 | 0.412812E+11 | 0.00 | 0.306987E+09 | 0.998299E+09 | 0.00 | 0.690472E+11 | 0.00 | 0.49 |
July | 0.556684E+09 | 0.867770E+11 | 0.00 | 29537997.24 | 0.164850E+10 | 0.00 | 0.296890E+10 | 0.00 | 0.26 |
August | 0.447166E+10 | 0.575718E+11 | 0.00 | 0.268853E+09 | 0.131830E+10 | 0.00 | 0.367663E+11 | 0.00 | 0.43 |
September | 0.181519E+11 | 0.280550E+11 | 0.00 | 0.404913E+09 | 0.304138E+09 | 0.00 | 0.139961E+12 | 0.00 | 0.53 |
October | 0.419994E+11 | 0.374432E+10 | 0.00 | 0.493220E+09 | 674194.99 | 0.00 | 0.217361E+12 | 0.00 | 0.51 |
November | 0.132462E+12 | 0.00 | 0.00 | 0.208089E+09 | 0.00 | 18171003.07 | 0.140749E+12 | 0.00 | 0.34 |
December | 0.200423E+12 | 0.00 | 0.00 | 46416974.15 | 0.00 | 0.00 | 0.515792E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.109073E+13 | 0.218530E+12 | 0.00 | 0.287335E+10 | 0.426991E+10 | 0.885725E+10 | 0.131871E+13 | 0.00 | 0.41 |
Minimum of Months | 0.556684E+09 | 0.00 | 0.00 | 4750156.67 | 0.00 | 0.00 | 0.296890E+10 | 0.00 | 0.26 |
Maximum of Months | 0.208556E+12 | 0.867770E+11 | 0.00 | 0.561989E+09 | 0.164850E+10 | 0.760488E+10 | 0.278063E+12 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233083E+10 | 0.00 | 0.00 | 0.28 |
February | 0.153784E+11 | 0.00 | 0.00 | 14082.15 | 0.00 | 0.178862E+10 | 0.178025E+09 | 0.00 | 0.29 |
March | 0.195816E+11 | 0.00 | 0.00 | 4539158.32 | 0.00 | 0.484772E+09 | 0.491988E+10 | 0.00 | 0.33 |
April | 0.129030E+11 | 530044.77 | 0.00 | 20353139.84 | 0.00 | 69647011.26 | 0.138670E+11 | 0.00 | 0.43 |
May | 0.727429E+10 | 97558133.04 | 0.00 | 42872419.57 | 0.00 | 0.00 | 0.225730E+11 | 0.00 | 0.63 |
June | 0.102024E+10 | 0.398091E+10 | 0.00 | 30186175.67 | 92443619.30 | 0.00 | 0.708245E+10 | 0.00 | 0.50 |
July | 0.142759E+09 | 0.884152E+10 | 0.00 | 3193790.50 | 0.165524E+09 | 0.00 | 0.286700E+09 | 0.00 | 0.27 |
August | 0.414007E+09 | 0.571805E+10 | 0.00 | 28446726.34 | 0.138153E+09 | 0.00 | 0.367745E+10 | 0.00 | 0.46 |
September | 0.392880E+10 | 0.277760E+10 | 0.00 | 31133781.67 | 25663782.48 | 0.00 | 0.107190E+11 | 0.00 | 0.52 |
October | 0.963495E+10 | 0.254277E+09 | 0.00 | 26503541.62 | 0.00 | 0.00 | 0.129289E+11 | 0.00 | 0.48 |
November | 0.171778E+11 | 0.00 | 0.00 | 3914384.16 | 0.00 | 0.684209E+09 | 0.399720E+10 | 0.00 | 0.32 |
December | 0.176175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144130E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.121180E+12 | 0.216704E+11 | 0.00 | 0.191157E+09 | 0.421785E+09 | 0.679937E+10 | 0.802296E+11 | 0.00 | 0.40 |
Minimum of Months | 0.142759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.195816E+11 | 0.884152E+10 | 0.00 | 42872419.57 | 0.165524E+09 | 0.233083E+10 | 0.225730E+11 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551539E+09 | 0.00 | 0.00 | 0.28 |
February | 0.276617E+10 | 0.00 | 0.00 | 16672.24 | 0.00 | 0.358082E+09 | 35217229.96 | 0.00 | 0.27 |
March | 0.262906E+10 | 0.00 | 0.00 | 2362128.22 | 0.00 | 0.00 | 0.163759E+10 | 0.00 | 0.35 |
April | 0.172221E+10 | 577111.76 | 0.00 | 6000732.93 | 0.00 | 0.00 | 0.358501E+10 | 0.00 | 0.63 |
May | 0.719021E+09 | 20025933.55 | 0.00 | 9403974.95 | 0.00 | 0.00 | 0.446560E+10 | 0.00 | 0.90 |
June | 0.204890E+09 | 0.862574E+09 | 0.00 | 5543162.94 | 12628271.69 | 0.00 | 0.130825E+10 | 0.00 | 0.79 |
July | 32816305.32 | 0.181357E+10 | 0.00 | 491804.21 | 21100176.29 | 0.00 | 45361702.98 | 0.00 | 0.43 |
August | 0.326537E+09 | 0.122013E+10 | 0.00 | 4424965.76 | 17313941.58 | 0.00 | 0.583370E+09 | 0.00 | 0.73 |
September | 0.477053E+09 | 0.459704E+09 | 0.00 | 5887190.01 | 3833741.20 | 0.00 | 0.195024E+10 | 0.00 | 0.70 |
October | 0.120160E+10 | 62011879.67 | 0.00 | 6195483.60 | 0.00 | 0.00 | 0.271303E+10 | 0.00 | 0.63 |
November | 0.223602E+10 | 0.00 | 0.00 | 2346621.40 | 0.00 | 390977.65 | 0.173483E+10 | 0.00 | 0.36 |
December | 0.325171E+10 | 0.00 | 0.00 | 303982.10 | 0.00 | 254842.46 | 0.287760E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.184218E+11 | 0.443859E+10 | 0.00 | 42976718.36 | 54876130.76 | 0.910267E+09 | 0.183463E+11 | 0.00 | 0.53 |
Minimum of Months | 32816305.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.325171E+10 | 0.181357E+10 | 0.00 | 9403974.95 | 21100176.29 | 0.551539E+09 | 0.446560E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165860E+10 | 0.00 | 0.00 | 577218.44 | 0.00 | 0.346036E+09 | 0.295803E+09 | 0.00 | 0.29 |
February | 0.151204E+10 | 0.00 | 0.00 | 983011.12 | 0.00 | 0.207082E+09 | 0.492690E+09 | 0.00 | 0.29 |
March | 0.141534E+10 | 0.00 | 0.00 | 5042083.78 | 0.00 | 10532473.54 | 0.243493E+10 | 0.00 | 0.46 |
April | 0.111955E+10 | 428295.41 | 0.00 | 7351873.70 | 0.00 | 0.00 | 0.374175E+10 | 0.00 | 0.90 |
May | 0.395361E+09 | 18402293.65 | 0.00 | 12310229.65 | 0.00 | 0.00 | 0.476363E+10 | 0.00 | 1.35 |
June | 0.109278E+09 | 0.637552E+09 | 0.00 | 5637848.09 | 8093363.83 | 0.00 | 0.141953E+10 | 0.00 | 1.04 |
July | 21231690.15 | 0.137159E+10 | 0.00 | 588373.53 | 13522943.42 | 0.00 | 59520594.99 | 0.00 | 0.54 |
August | 0.201416E+09 | 0.985746E+09 | 0.00 | 4775407.74 | 11096374.23 | 0.00 | 0.697510E+09 | 0.00 | 1.01 |
September | 0.228390E+09 | 0.353096E+09 | 0.00 | 9085625.25 | 2457015.75 | 0.00 | 0.222701E+10 | 0.00 | 1.02 |
October | 0.679481E+09 | 49757599.51 | 0.00 | 7497767.94 | 0.00 | 0.00 | 0.306775E+10 | 0.00 | 0.91 |
November | 0.128707E+10 | 0.00 | 0.00 | 3006363.22 | 0.00 | 9688247.75 | 0.173243E+10 | 0.00 | 0.42 |
December | 0.188789E+10 | 0.00 | 0.00 | 1032674.42 | 0.00 | 17654461.25 | 0.532137E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.105156E+11 | 0.341657E+10 | 0.00 | 57888476.86 | 35169697.22 | 0.590993E+09 | 0.214647E+11 | 0.00 | 0.71 |
Minimum of Months | 21231690.15 | 0.00 | 0.00 | 577218.44 | 0.00 | 0.00 | 59520594.99 | 0.00 | 0.27 |
Maximum of Months | 0.188789E+10 | 0.137159E+10 | 0.00 | 12310229.65 | 13522943.42 | 0.346036E+09 | 0.476363E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200331E+10 | 0.00 | 0.00 | 5384919.79 | 0.00 | 0.526868E+09 | 0.295582E+10 | 0.00 | 0.42 |
February | 0.171635E+10 | 0.00 | 0.00 | 6995131.55 | 0.00 | 0.287532E+09 | 0.378948E+10 | 0.00 | 0.46 |
March | 0.198736E+10 | 0.00 | 0.00 | 11643300.40 | 0.00 | 38517096.25 | 0.648179E+10 | 0.00 | 0.69 |
April | 0.170915E+10 | 1227011.52 | 0.00 | 11225541.56 | 0.00 | 0.00 | 0.594541E+10 | 0.00 | 0.97 |
May | 0.866086E+09 | 25523282.25 | 0.00 | 12448353.41 | 0.00 | 0.00 | 0.525636E+10 | 0.00 | 1.10 |
June | 0.213538E+09 | 0.971920E+09 | 0.00 | 6199064.35 | 12627365.98 | 0.00 | 0.137657E+10 | 0.00 | 0.87 |
July | 32133501.99 | 0.206011E+10 | 0.00 | 891009.78 | 21098662.97 | 0.00 | 45067145.38 | 0.00 | 0.50 |
August | 0.319740E+09 | 0.163683E+10 | 0.00 | 7379334.17 | 17312699.81 | 0.00 | 0.771322E+09 | 0.00 | 1.00 |
September | 0.370692E+09 | 0.658778E+09 | 0.00 | 17965567.47 | 3833466.25 | 0.00 | 0.378259E+10 | 0.00 | 1.23 |
October | 0.647251E+09 | 0.164826E+09 | 0.00 | 21717981.19 | 0.00 | 0.00 | 0.818682E+10 | 0.00 | 1.42 |
November | 0.163094E+10 | 0.00 | 0.00 | 10015878.54 | 0.00 | 31055123.82 | 0.595420E+10 | 0.00 | 0.71 |
December | 0.221766E+10 | 0.00 | 0.00 | 8268938.95 | 0.00 | 64298181.27 | 0.400735E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.137142E+11 | 0.551921E+10 | 0.00 | 0.120135E+09 | 54872195.01 | 0.948270E+09 | 0.485528E+11 | 0.00 | 0.82 |
Minimum of Months | 32133501.99 | 0.00 | 0.00 | 891009.78 | 0.00 | 0.00 | 45067145.38 | 0.00 | 0.42 |
Maximum of Months | 0.221766E+10 | 0.206011E+10 | 0.00 | 21717981.19 | 21098662.97 | 0.526868E+09 | 0.818682E+10 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159491E+10 | 0.00 | 0.00 | 1420872.75 | 0.00 | 49901014.84 | 0.978116E+09 | 0.00 | 0.32 |
February | 0.113781E+10 | 0.00 | 0.00 | 3015295.39 | 0.00 | 20561068.31 | 0.191753E+10 | 0.00 | 0.38 |
March | 0.273314E+09 | 0.00 | 0.00 | 11732071.15 | 0.00 | 0.00 | 0.677241E+10 | 0.00 | 0.90 |
April | 0.180588E+09 | 992564.04 | 0.00 | 18265180.88 | 0.00 | 0.00 | 0.878489E+10 | 0.00 | 1.67 |
May | 0.165977E+09 | 26102985.12 | 0.00 | 14949858.76 | 0.00 | 0.00 | 0.609663E+10 | 0.00 | 1.71 |
June | 48648165.02 | 0.106137E+10 | 0.00 | 8604241.53 | 5888370.01 | 0.00 | 0.173963E+10 | 0.00 | 1.48 |
July | 10251366.72 | 0.224036E+10 | 0.00 | 1964753.87 | 4459833.69 | 0.00 | 69518887.67 | 0.00 | 0.83 |
August | 64430308.88 | 0.176056E+10 | 0.00 | 8807292.21 | 2966491.04 | 0.00 | 0.105504E+10 | 0.00 | 1.58 |
September | 0.130642E+09 | 0.551305E+09 | 0.00 | 11023877.55 | 1835621.47 | 0.00 | 0.271186E+10 | 0.00 | 1.32 |
October | 0.195441E+09 | 0.100488E+09 | 0.00 | 13537635.82 | 0.00 | 0.00 | 0.544121E+10 | 0.00 | 1.44 |
November | 0.314837E+09 | 0.00 | 0.00 | 7866994.78 | 0.00 | 0.00 | 0.491074E+10 | 0.00 | 0.75 |
December | 0.361592E+09 | 0.00 | 0.00 | 6854472.51 | 0.00 | 0.00 | 0.403610E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.447844E+10 | 0.574117E+10 | 0.00 | 0.108043E+09 | 15150316.21 | 70462083.15 | 0.445137E+11 | 0.00 | 1.07 |
Minimum of Months | 10251366.72 | 0.00 | 0.00 | 1420872.75 | 0.00 | 0.00 | 69518887.67 | 0.00 | 0.32 |
Maximum of Months | 0.159491E+10 | 0.224036E+10 | 0.00 | 18265180.88 | 5888370.01 | 49901014.84 | 0.878489E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.703277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231290E+11 | 0.00 | 0.00 | 0.31 |
February | 0.850409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217267E+11 | 0.00 | 0.00 | 0.32 |
March | 0.262770E+11 | 0.00 | 0.00 | 931247.06 | 0.00 | 0.866679E+10 | 0.545221E+09 | 0.00 | 0.32 |
April | 0.240266E+11 | 13098676.08 | 0.00 | 16043663.44 | 0.00 | 0.190060E+10 | 0.814048E+10 | 0.00 | 0.42 |
May | 0.120161E+11 | 0.230703E+09 | 0.00 | 60640638.82 | 0.00 | 0.00 | 0.270415E+11 | 0.00 | 0.70 |
June | 0.155745E+10 | 0.867509E+10 | 0.00 | 44249984.81 | 0.125098E+09 | 0.00 | 0.103047E+11 | 0.00 | 0.70 |
July | 68355679.56 | 0.189743E+11 | 0.00 | 4952648.06 | 0.206576E+09 | 0.00 | 0.490697E+09 | 0.00 | 0.45 |
August | 0.892945E+09 | 0.127810E+11 | 0.00 | 37688062.65 | 0.165198E+09 | 0.00 | 0.477629E+10 | 0.00 | 0.63 |
September | 0.778617E+10 | 0.446918E+10 | 0.00 | 37837662.21 | 48180663.08 | 0.00 | 0.111753E+11 | 0.00 | 0.58 |
October | 0.189327E+11 | 0.562677E+09 | 0.00 | 22036661.35 | 84484.42 | 0.234486E+09 | 0.816726E+10 | 0.00 | 0.45 |
November | 0.218439E+11 | 0.00 | 0.00 | 617071.89 | 0.00 | 0.904774E+10 | 0.630077E+09 | 0.00 | 0.31 |
December | 0.123524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197185E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.141290E+12 | 0.457060E+11 | 0.00 | 0.224998E+09 | 0.545138E+09 | 0.844238E+11 | 0.712715E+11 | 0.00 | 0.46 |
Minimum of Months | 68355679.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.262770E+11 | 0.189743E+11 | 0.00 | 60640638.82 | 0.206576E+09 | 0.231290E+11 | 0.270415E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.499639E+10 | 0.00 | 0.00 | 196089.41 | 0.00 | 0.112114E+11 | 0.107695E+09 | 0.00 | 0.26 |
February | 0.653793E+10 | 0.00 | 0.00 | 1259014.35 | 0.00 | 0.923848E+10 | 0.543515E+09 | 0.00 | 0.26 |
March | 0.112641E+11 | 0.00 | 0.00 | 21974991.88 | 0.00 | 0.342648E+10 | 0.107870E+11 | 0.00 | 0.36 |
April | 0.916837E+10 | 12382539.39 | 0.00 | 50818083.68 | 0.00 | 0.958818E+09 | 0.242206E+11 | 0.00 | 0.69 |
May | 0.483001E+10 | 0.224092E+09 | 0.00 | 0.108186E+09 | 0.00 | 0.00 | 0.393121E+11 | 0.00 | 1.20 |
June | 0.681701E+09 | 0.688193E+10 | 0.00 | 58197786.69 | 80960689.18 | 0.00 | 0.136890E+11 | 0.00 | 1.05 |
July | 42950308.56 | 0.160072E+11 | 0.00 | 8810283.70 | 0.133691E+09 | 0.00 | 0.746745E+09 | 0.00 | 0.63 |
August | 0.370922E+09 | 0.120538E+11 | 0.00 | 56973154.69 | 0.106912E+09 | 0.00 | 0.749511E+10 | 0.00 | 1.07 |
September | 0.293560E+10 | 0.366510E+10 | 0.00 | 79168840.84 | 29590557.13 | 0.00 | 0.180253E+11 | 0.00 | 0.92 |
October | 0.755333E+10 | 0.509925E+09 | 0.00 | 52778072.22 | 0.00 | 0.100334E+09 | 0.196900E+11 | 0.00 | 0.72 |
November | 0.995409E+10 | 0.00 | 0.00 | 9387125.69 | 0.00 | 0.392300E+10 | 0.520137E+10 | 0.00 | 0.29 |
December | 0.760107E+10 | 0.00 | 0.00 | 302315.08 | 0.00 | 0.929082E+10 | 0.201317E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.659365E+11 | 0.393544E+11 | 0.00 | 0.448052E+09 | 0.351155E+09 | 0.381493E+11 | 0.140020E+12 | 0.00 | 0.64 |
Minimum of Months | 42950308.56 | 0.00 | 0.00 | 196089.41 | 0.00 | 0.00 | 0.107695E+09 | 0.00 | 0.25 |
Maximum of Months | 0.112641E+11 | 0.160072E+11 | 0.00 | 0.108186E+09 | 0.133691E+09 | 0.112114E+11 | 0.393121E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110584E+11 | 0.00 | 0.00 | 41032813.27 | 0.00 | 0.124023E+11 | 0.197733E+11 | 0.00 | 0.43 |
February | 0.115496E+11 | 0.00 | 0.00 | 55491775.50 | 0.00 | 0.982325E+10 | 0.283027E+11 | 0.00 | 0.50 |
March | 0.178233E+11 | 0.00 | 0.00 | 92608321.66 | 0.00 | 0.430765E+10 | 0.513111E+11 | 0.00 | 0.67 |
April | 0.169836E+11 | 30576665.73 | 0.00 | 80979956.62 | 0.00 | 0.158569E+10 | 0.391486E+11 | 0.00 | 0.77 |
May | 0.110317E+11 | 0.314357E+09 | 0.00 | 0.101174E+09 | 0.00 | 0.00 | 0.419193E+11 | 0.00 | 0.98 |
June | 0.202979E+10 | 0.101433E+11 | 0.00 | 55081140.10 | 0.125336E+09 | 0.00 | 0.115314E+11 | 0.00 | 0.82 |
July | 70577824.60 | 0.222840E+11 | 0.00 | 10517062.79 | 0.206969E+09 | 0.00 | 0.487282E+09 | 0.00 | 0.54 |
August | 0.778250E+09 | 0.185472E+11 | 0.00 | 75703386.01 | 0.165512E+09 | 0.00 | 0.720721E+10 | 0.00 | 0.99 |
September | 0.455870E+10 | 0.713715E+10 | 0.00 | 0.181536E+09 | 45809551.42 | 0.00 | 0.338028E+11 | 0.00 | 1.19 |
October | 0.748399E+10 | 0.194537E+10 | 0.00 | 0.211258E+09 | 0.00 | 4322190.82 | 0.679378E+11 | 0.00 | 1.29 |
November | 0.150228E+11 | 0.00 | 0.00 | 77196068.68 | 0.00 | 0.364502E+10 | 0.406347E+11 | 0.00 | 0.59 |
December | 0.129789E+11 | 0.00 | 0.00 | 57199367.67 | 0.00 | 0.996133E+10 | 0.279450E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.111370E+12 | 0.604019E+11 | 0.00 | 0.103978E+10 | 0.543627E+09 | 0.417295E+11 | 0.370001E+12 | 0.00 | 0.77 |
Minimum of Months | 70577824.60 | 0.00 | 0.00 | 10517062.79 | 0.00 | 0.00 | 0.487282E+09 | 0.00 | 0.43 |
Maximum of Months | 0.178233E+11 | 0.222840E+11 | 0.00 | 0.211258E+09 | 0.206969E+09 | 0.124023E+11 | 0.679378E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.798764E+10 | 0.00 | 0.00 | 1709505.03 | 0.00 | 0.104347E+11 | 0.119320E+10 | 0.00 | 0.31 |
February | 0.883970E+10 | 0.00 | 0.00 | 4568001.48 | 0.00 | 0.890172E+10 | 0.316478E+10 | 0.00 | 0.34 |
March | 0.147289E+11 | 0.00 | 0.00 | 26899008.92 | 0.00 | 0.262848E+10 | 0.164946E+11 | 0.00 | 0.49 |
April | 0.103750E+11 | 31380162.11 | 0.00 | 60145674.04 | 0.00 | 0.584755E+09 | 0.270529E+11 | 0.00 | 0.80 |
May | 0.480204E+10 | 0.303324E+09 | 0.00 | 97262724.75 | 0.00 | 0.00 | 0.382277E+11 | 0.00 | 1.25 |
June | 0.770282E+09 | 0.944024E+10 | 0.00 | 55221307.53 | 59080760.51 | 0.00 | 0.109591E+11 | 0.00 | 1.15 |
July | 35753005.72 | 0.190947E+11 | 0.00 | 14504118.87 | 68753247.49 | 0.00 | 0.405580E+09 | 0.00 | 0.71 |
August | 0.392793E+09 | 0.150988E+11 | 0.00 | 48958795.62 | 69000475.28 | 0.00 | 0.506065E+10 | 0.00 | 1.16 |
September | 0.316026E+10 | 0.498913E+10 | 0.00 | 76493469.84 | 18567088.65 | 0.00 | 0.161707E+11 | 0.00 | 0.99 |
October | 0.791859E+10 | 0.965452E+09 | 0.00 | 57515300.89 | 0.00 | 5378322.68 | 0.210040E+11 | 0.00 | 0.82 |
November | 0.140586E+11 | 0.00 | 0.00 | 9010041.73 | 0.00 | 0.342350E+10 | 0.467528E+10 | 0.00 | 0.34 |
December | 0.118842E+11 | 0.00 | 0.00 | 1645364.78 | 0.00 | 0.786888E+10 | 0.124839E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.849538E+11 | 0.499230E+11 | 0.00 | 0.453933E+09 | 0.215402E+09 | 0.338474E+11 | 0.145657E+12 | 0.00 | 0.72 |
Minimum of Months | 35753005.72 | 0.00 | 0.00 | 1645364.78 | 0.00 | 0.00 | 0.405580E+09 | 0.00 | 0.30 |
Maximum of Months | 0.147289E+11 | 0.190947E+11 | 0.00 | 97262724.75 | 69000475.28 | 0.104347E+11 | 0.382277E+11 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.388907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224935E+10 | 0.00 | 0.00 | 0.32 |
February | 0.402314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209841E+10 | 0.00 | 0.00 | 0.33 |
March | 0.176107E+10 | 0.00 | 0.00 | 47691.68 | 0.00 | 0.137217E+10 | 65693064.63 | 0.00 | 0.34 |
April | 0.200388E+10 | 85777.79 | 0.00 | 1580579.37 | 0.00 | 0.479255E+09 | 0.815154E+09 | 0.00 | 0.43 |
May | 0.138624E+10 | 20681313.62 | 0.00 | 5673578.30 | 0.00 | 24294361.47 | 0.256750E+10 | 0.00 | 0.70 |
June | 0.202648E+09 | 0.798578E+09 | 0.00 | 4625134.02 | 12286640.85 | 0.00 | 0.108015E+10 | 0.00 | 0.71 |
July | 12127091.30 | 0.184241E+10 | 0.00 | 1091989.28 | 20798120.04 | 0.00 | 59263052.97 | 0.00 | 0.45 |
August | 96428332.64 | 0.120486E+10 | 0.00 | 4311529.27 | 18528903.59 | 0.00 | 0.512299E+09 | 0.00 | 0.66 |
September | 0.802687E+09 | 0.428017E+09 | 0.00 | 3393526.13 | 11649488.17 | 0.00 | 0.105030E+10 | 0.00 | 0.57 |
October | 0.179822E+10 | 37536333.58 | 0.00 | 1657987.46 | 141609.29 | 0.144985E+09 | 0.662863E+09 | 0.00 | 0.45 |
November | 0.150225E+10 | 0.00 | 0.00 | 8328.83 | 0.00 | 0.128615E+10 | 18785010.64 | 0.00 | 0.33 |
December | 0.325728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227441E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.106825E+11 | 0.433217E+10 | 0.00 | 22390344.34 | 63404761.95 | 0.992904E+10 | 0.683201E+10 | 0.00 | 0.47 |
Minimum of Months | 12127091.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.200388E+10 | 0.184241E+10 | 0.00 | 5673578.30 | 20798120.04 | 0.227441E+10 | 0.256750E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.425642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123864E+10 | 0.00 | 0.00 | 0.31 |
February | 0.576018E+09 | 0.00 | 0.00 | 2849.54 | 0.00 | 0.956554E+09 | 4435261.49 | 0.00 | 0.31 |
March | 0.103658E+10 | 0.00 | 0.00 | 1466665.65 | 0.00 | 0.572697E+09 | 0.815281E+09 | 0.00 | 0.39 |
April | 0.813398E+09 | 92053.35 | 0.00 | 4497285.67 | 0.00 | 0.255090E+09 | 0.240517E+10 | 0.00 | 0.72 |
May | 0.640594E+09 | 20531359.77 | 0.00 | 11503754.65 | 0.00 | 7749395.41 | 0.400211E+10 | 0.00 | 1.26 |
June | 61461712.81 | 0.671903E+09 | 0.00 | 6129340.85 | 7663243.85 | 0.00 | 0.149375E+10 | 0.00 | 1.11 |
July | 6613191.62 | 0.160720E+10 | 0.00 | 1350429.07 | 13414256.65 | 0.00 | 90619491.52 | 0.00 | 0.66 |
August | 31280407.42 | 0.117982E+10 | 0.00 | 6622736.06 | 11196106.12 | 0.00 | 0.819272E+09 | 0.00 | 1.16 |
September | 0.333277E+09 | 0.373771E+09 | 0.00 | 8140068.13 | 6622797.59 | 0.00 | 0.179531E+10 | 0.00 | 0.96 |
October | 0.687554E+09 | 36322170.81 | 0.00 | 4594076.34 | 0.00 | 61479285.77 | 0.183981E+10 | 0.00 | 0.73 |
November | 0.100331E+10 | 0.00 | 0.00 | 394705.69 | 0.00 | 0.579224E+09 | 0.283211E+09 | 0.00 | 0.33 |
December | 0.582951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108737E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.619869E+10 | 0.388964E+10 | 0.00 | 44701911.64 | 38896404.21 | 0.475881E+10 | 0.135490E+11 | 0.00 | 0.69 |
Minimum of Months | 6613191.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.103658E+10 | 0.160720E+10 | 0.00 | 11503754.65 | 13414256.65 | 0.123864E+10 | 0.400211E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.672674E+09 | 0.00 | 0.00 | 3117617.36 | 0.00 | 0.132535E+10 | 0.156568E+10 | 0.00 | 0.40 |
February | 0.726195E+09 | 0.00 | 0.00 | 3907434.13 | 0.00 | 0.979733E+09 | 0.213629E+10 | 0.00 | 0.45 |
March | 0.122230E+10 | 0.00 | 0.00 | 7681559.43 | 0.00 | 0.683404E+09 | 0.485220E+10 | 0.00 | 0.65 |
April | 0.137321E+10 | 264416.87 | 0.00 | 7455746.87 | 0.00 | 0.387769E+09 | 0.411859E+10 | 0.00 | 0.79 |
May | 0.122290E+10 | 27646490.40 | 0.00 | 10786975.78 | 0.00 | 25523345.21 | 0.427511E+10 | 0.00 | 0.98 |
June | 0.215683E+09 | 0.916146E+09 | 0.00 | 5869009.04 | 11863713.71 | 0.00 | 0.130865E+10 | 0.00 | 0.84 |
July | 10466916.91 | 0.213220E+10 | 0.00 | 1739736.69 | 21203815.22 | 0.00 | 71281520.84 | 0.00 | 0.53 |
August | 77632228.92 | 0.170902E+10 | 0.00 | 8891839.69 | 17274427.72 | 0.00 | 0.843646E+09 | 0.00 | 1.03 |
September | 0.511159E+09 | 0.681842E+09 | 0.00 | 18814545.39 | 5515764.86 | 0.00 | 0.352145E+10 | 0.00 | 1.21 |
October | 0.712167E+09 | 0.129274E+09 | 0.00 | 18273786.81 | 0.00 | 75277899.21 | 0.697499E+10 | 0.00 | 1.34 |
November | 0.111215E+10 | 0.00 | 0.00 | 5536179.74 | 0.00 | 0.604653E+09 | 0.339487E+10 | 0.00 | 0.59 |
December | 0.832753E+09 | 0.00 | 0.00 | 3274437.29 | 0.00 | 0.114370E+10 | 0.165385E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.868929E+10 | 0.559639E+10 | 0.00 | 95348868.22 | 55857721.51 | 0.522541E+10 | 0.347166E+11 | 0.00 | 0.77 |
Minimum of Months | 10466916.91 | 0.00 | 0.00 | 1739736.69 | 0.00 | 0.00 | 71281520.84 | 0.00 | 0.40 |
Maximum of Months | 0.137321E+10 | 0.213220E+10 | 0.00 | 18814545.39 | 21203815.22 | 0.132535E+10 | 0.697499E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.493991E+09 | 0.00 | 0.00 | 137034.99 | 0.00 | 0.107756E+10 | 0.103034E+09 | 0.00 | 0.31 |
February | 0.537564E+09 | 0.00 | 0.00 | 350155.35 | 0.00 | 0.865473E+09 | 0.259373E+09 | 0.00 | 0.33 |
March | 0.112771E+10 | 0.00 | 0.00 | 2336066.91 | 0.00 | 0.392444E+09 | 0.164235E+10 | 0.00 | 0.49 |
April | 0.939840E+09 | 86398.97 | 0.00 | 5856974.13 | 0.00 | 0.167031E+09 | 0.282237E+10 | 0.00 | 0.82 |
May | 0.580587E+09 | 25769954.92 | 0.00 | 10442339.14 | 0.00 | 5890010.15 | 0.393830E+10 | 0.00 | 1.26 |
June | 82447923.60 | 0.840743E+09 | 0.00 | 6070265.84 | 5646540.71 | 0.00 | 0.123401E+10 | 0.00 | 1.16 |
July | 4421317.18 | 0.181180E+10 | 0.00 | 2364602.91 | 6684184.20 | 0.00 | 66491027.87 | 0.00 | 0.70 |
August | 29354526.75 | 0.138142E+10 | 0.00 | 5648764.12 | 6983813.87 | 0.00 | 0.563468E+09 | 0.00 | 1.18 |
September | 0.367582E+09 | 0.475996E+09 | 0.00 | 8159016.97 | 1877093.13 | 0.00 | 0.161746E+10 | 0.00 | 1.00 |
October | 0.760360E+09 | 64845773.29 | 0.00 | 5058158.65 | 0.00 | 50491665.91 | 0.215343E+10 | 0.00 | 0.84 |
November | 0.104402E+10 | 0.00 | 0.00 | 608063.71 | 0.00 | 0.499914E+09 | 0.443074E+09 | 0.00 | 0.36 |
December | 0.635233E+09 | 0.00 | 0.00 | 82455.97 | 0.00 | 0.929940E+09 | 63086405.90 | 0.00 | 0.30 |
Annual Sum or Average | 0.660312E+10 | 0.460066E+10 | 0.00 | 47113898.69 | 21191631.90 | 0.398874E+10 | 0.149064E+11 | 0.00 | 0.73 |
Minimum of Months | 4421317.18 | 0.00 | 0.00 | 82455.97 | 0.00 | 0.00 | 63086405.90 | 0.00 | 0.30 |
Maximum of Months | 0.112771E+10 | 0.181180E+10 | 0.00 | 10442339.14 | 6983813.87 | 0.107756E+10 | 0.393830E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2871431.98 | 0.00 | 0.00 | 0.698981E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7634521.49 | 0.00 | 0.00 | 0.659886E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 15150103.67 | 0.00 | 0.00 | 0.623926E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17411415.36 | 0.00 | 0.00 | 0.423031E+09 | 0.00 | 0.29 |
May | 0.00 | 4411181.57 | 0.00 | 3802745.40 | 0.00 | 0.00 | 0.256153E+09 | 0.00 | 0.29 |
June | 0.00 | 0.147760E+09 | 0.00 | 2663181.00 | 0.00 | 0.00 | 43592794.17 | 0.00 | 0.31 |
July | 0.00 | 0.359883E+09 | 0.00 | 343466.02 | 0.00 | 0.00 | 922454.38 | 0.00 | 0.28 |
August | 0.00 | 0.283896E+09 | 0.00 | 4513970.64 | 0.00 | 0.00 | 20555035.68 | 0.00 | 0.31 |
September | 0.00 | 75323255.48 | 0.00 | 2348509.64 | 0.00 | 0.00 | 0.114552E+09 | 0.00 | 0.29 |
October | 0.00 | 12338381.52 | 0.00 | 7159067.98 | 0.00 | 0.00 | 0.237544E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12882650.50 | 0.00 | 0.00 | 0.512266E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18271313.01 | 0.00 | 0.00 | 0.638601E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.883612E+09 | 0.00 | 95052376.68 | 0.00 | 0.00 | 0.423001E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 343466.02 | 0.00 | 0.00 | 922454.38 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.359883E+09 | 0.00 | 18271313.01 | 0.00 | 0.00 | 0.698981E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.260806E+10 | 0.00 | 0.00 | 6710136.58 | 0.00 | 0.00 | 0.432762E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 53644947.46 | 0.00 | 0.00 | 0.662251E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.129465E+09 | 0.00 | 0.00 | 0.626003E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.159184E+09 | 0.00 | 0.00 | 0.424107E+10 | 0.00 | 0.29 |
May | 0.00 | 42639889.69 | 0.00 | 33268103.10 | 0.00 | 0.00 | 0.258054E+10 | 0.00 | 0.29 |
June | 0.00 | 0.146734E+10 | 0.00 | 25126509.11 | 0.00 | 0.00 | 0.436922E+09 | 0.00 | 0.31 |
July | 0.00 | 0.359259E+10 | 0.00 | 3300767.46 | 0.00 | 0.00 | 9273357.69 | 0.00 | 0.28 |
August | 0.00 | 0.284430E+10 | 0.00 | 43086995.41 | 0.00 | 0.00 | 0.206037E+09 | 0.00 | 0.31 |
September | 0.00 | 0.737089E+09 | 0.00 | 20579207.85 | 0.00 | 0.00 | 0.115562E+10 | 0.00 | 0.29 |
October | 0.00 | 0.119901E+09 | 0.00 | 64071343.71 | 0.00 | 0.00 | 0.238480E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.108486E+09 | 0.00 | 0.00 | 0.514163E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.153672E+09 | 0.00 | 0.00 | 0.641448E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.260806E+10 | 0.880386E+10 | 0.00 | 0.800594E+09 | 0.00 | 0.00 | 0.397805E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3300767.46 | 0.00 | 0.00 | 9273357.69 | 0.00 | 0.28 |
Maximum of Months | 0.260806E+10 | 0.359259E+10 | 0.00 | 0.159184E+09 | 0.00 | 0.00 | 0.662251E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.465416E+09 | 0.00 | 0.00 | 333287.39 | 0.00 | 0.00 | 0.217059E+09 | 0.00 | 0.28 |
February | 834562.64 | 0.00 | 0.00 | 4449892.41 | 0.00 | 0.00 | 0.662234E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11934857.70 | 0.00 | 0.00 | 0.627214E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15361479.18 | 0.00 | 0.00 | 0.424876E+09 | 0.00 | 0.29 |
May | 1742462.15 | 4310840.23 | 0.00 | 3142939.97 | 0.00 | 0.00 | 0.257531E+09 | 0.00 | 0.29 |
June | 0.00 | 0.146794E+09 | 0.00 | 2525509.55 | 0.00 | 0.00 | 43726422.27 | 0.00 | 0.31 |
July | 0.00 | 0.359213E+09 | 0.00 | 331122.88 | 0.00 | 0.00 | 929603.03 | 0.00 | 0.28 |
August | 0.00 | 0.284999E+09 | 0.00 | 4323130.99 | 0.00 | 0.00 | 20627056.37 | 0.00 | 0.31 |
September | 0.00 | 73885526.99 | 0.00 | 1942467.74 | 0.00 | 0.00 | 0.116098E+09 | 0.00 | 0.29 |
October | 0.00 | 11893094.98 | 0.00 | 5903179.12 | 0.00 | 0.00 | 0.239533E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9808800.77 | 0.00 | 0.00 | 0.515484E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14196677.32 | 0.00 | 0.00 | 0.642643E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.467993E+09 | 0.881095E+09 | 0.00 | 74253345.02 | 0.00 | 0.00 | 0.376796E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 331122.88 | 0.00 | 0.00 | 929603.03 | 0.00 | 0.28 |
Maximum of Months | 0.465416E+09 | 0.359213E+09 | 0.00 | 15361479.18 | 0.00 | 0.00 | 0.662234E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.672942E+09 | 0.00 | 0.00 | 0.435977E+12 | 0.00 | 7.87 |
February | 0.00 | 0.00 | 0.00 | 0.125050E+10 | 0.00 | 0.00 | 0.713821E+12 | 0.00 | 13.00 |
March | 0.00 | 0.00 | 0.00 | 0.163505E+10 | 0.00 | 0.00 | 0.100031E+13 | 0.00 | 23.65 |
April | 0.00 | 0.00 | 0.00 | 0.217499E+10 | 0.00 | 0.00 | 0.102186E+13 | 0.00 | 36.37 |
May | 0.00 | 99035756.49 | 0.00 | 0.523836E+09 | 0.00 | 0.00 | 0.358874E+12 | 0.00 | 18.60 |
June | 0.00 | 0.308863E+10 | 0.00 | 0.522873E+09 | 0.00 | 0.00 | 0.209503E+12 | 0.00 | 18.10 |
July | 0.00 | 0.797153E+10 | 0.00 | 34699172.06 | 0.00 | 0.00 | 0.372974E+10 | 0.00 | 1.07 |
August | 0.00 | 0.508591E+10 | 0.00 | 0.796110E+09 | 0.00 | 0.00 | 0.670085E+11 | 0.00 | 11.57 |
September | 0.00 | 0.133911E+10 | 0.00 | 0.453901E+09 | 0.00 | 0.00 | 0.252097E+12 | 0.00 | 20.45 |
October | 0.00 | 38650952.65 | 0.00 | 0.111628E+10 | 0.00 | 0.00 | 0.629114E+12 | 0.00 | 27.96 |
November | 0.00 | 0.00 | 0.00 | 0.159408E+10 | 0.00 | 0.00 | 0.963597E+12 | 0.00 | 26.27 |
December | 0.00 | 0.00 | 0.00 | 0.244870E+10 | 0.00 | 0.00 | 0.130688E+13 | 0.00 | 27.39 |
Annual Sum or Average | 0.00 | 0.176229E+11 | 0.00 | 0.132240E+11 | 0.00 | 0.00 | 0.696277E+13 | 0.00 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34699172.06 | 0.00 | 0.00 | 0.372974E+10 | 0.00 | 1.07 |
Maximum of Months | 0.00 | 0.797153E+10 | 0.00 | 0.244870E+10 | 0.00 | 0.00 | 0.130688E+13 | 0.00 | 36.37 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:52
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.223709E+12 | 0.447186E+11 | 0.00 | 0.185814E+13 | 0.536867E+11 |
February | 0.367280E+12 | 0.403757E+11 | 0.00 | 0.218361E+13 | 0.120304E+12 |
March | 0.625923E+12 | 0.330334E+11 | 0.00 | 0.279226E+13 | 0.261673E+12 |
April | 0.672898E+12 | 0.217658E+11 | 0.00 | 0.276350E+13 | 0.636336E+12 |
May | 0.861209E+12 | 0.125528E+11 | 0.00 | 0.206548E+13 | 0.611812E+12 |
June | 0.843641E+12 | 0.874115E+09 | 0.00 | 0.614106E+12 | 0.223802E+13 |
July | 0.825858E+12 | -0.103792E+11 | 0.00 | -0.387682E+12 | 0.348110E+13 |
August | 0.790185E+12 | -0.511129E+10 | 0.00 | 0.294003E+11 | 0.375267E+13 |
September | 0.554153E+12 | 0.493038E+10 | 0.00 | 0.119288E+13 | 0.132420E+13 |
October | 0.522977E+12 | 0.170521E+11 | 0.00 | 0.241156E+13 | 0.741695E+12 |
November | 0.254250E+12 | 0.319680E+11 | 0.00 | 0.270618E+13 | 0.258986E+12 |
December | 0.180572E+12 | 0.384252E+11 | 0.00 | 0.293537E+13 | 0.287432E+12 |
Annual Sum or Average | 0.672265E+13 | 0.230206E+12 | 0.00 | 0.211648E+14 | 0.137679E+14 |
Minimum of Months | 0.180572E+12 | -0.103792E+11 | 0.00 | -0.387682E+12 | 0.536867E+11 |
Maximum of Months | 0.861209E+12 | 0.447186E+11 | 0.00 | 0.293537E+13 | 0.375267E+13 |