Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2023-10-16 08:56:55


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 27473.70 593.12 593.12
Net Site Energy 26931.00 581.41 581.41
Total Source Energy 85526.36 1846.41 1846.41
Net Source Energy 83807.63 1809.30 1809.30


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 67.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4290.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1712.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 264.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1203.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2028.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 645.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1551.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11173.78
Humidification 338.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125.96
Heat Recovery 50.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 644.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 26761.82 711.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13579.90
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 67.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 4290.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1712.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 264.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1144.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 4.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2028.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 645.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1551.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11173.78
Humidification General 338.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125.96
Heat Recovery General 50.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 644.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 67.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 4290.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1712.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 264.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1203.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2028.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 645.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1551.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11173.78
Humidification Unassigned 338.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125.96
Heat Recovery Unassigned 50.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 644.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 42.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 191.16 15.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Other 343.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 577.75 15.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 42.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 191.16 15.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Other 343.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 577.75 15.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 566.520 2.12
Wind Power 0.000 0.00
Power Conversion -23.82 -0.1
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 542.701 2.03
     
Electricity Coming From Utility 26219.119 97.97
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 26219.119 97.97
     
Total On-Site and Utility Electric Sources 26761.820 100.00
Total Electricity End Uses 26761.820 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 2689.18 99.32
Air to Air Heat Recovery for Heating 18.50 0.68
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2707.67 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 13579.90 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 13579.90 100.00
Total Water End Uses 13579.90 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1.83
Time Setpoint Not Met During Occupied Cooling 800.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionElectricityGeneratedPropaneMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
RunPeriod RUNPERIOD 1
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [m] 8.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 5.7776 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.7776 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 5.7776 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.7776 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 5.7776 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 5.7776 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 7.1736 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 7.1736 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 7.1736 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 5.7776 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 5.7907 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 5.7907 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.7776 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 5.7776 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 5.7776 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 5.7776 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 5.7776 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 5.7776 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 5.7776 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 5.7776 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 5.7776 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 5.7776 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 5.7776 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 5.7776 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 5.7776 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 5.7776 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 5.7776 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 5.7776 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 7.1736 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 7.1736 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 7.1736 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 5.7776 18.58 484.4232  
Total 46320.38             5.7907 9.29 17.8789  
Conditioned Total 46320.38             5.7907 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 1.7810 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 03-AUG-15:30 06-FEB-06:10 - - - - - - - - - - 30-AUG-15:00
Heating 0.00 459264.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 386512.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 145987.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 52589.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 131212.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 47613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 81663.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4520.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 28158.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1628470.72 487423.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 459264.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 386512.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 145987.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3359.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 49008.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 221.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 131212.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 47613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 81663.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 4520.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 28158.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 72.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 13587.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5422.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 837.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 3812.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6422.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2045.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 4914.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 1072.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 160.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 699.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 84754.68 771.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 293.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 117.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 138.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 44.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 106.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 23.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1829.75 16.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 293.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 117.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 138.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 44.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 106.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 23.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1829.75 16.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.01
DATACENTER_BOT_ZN_6 DIRECT AIR 0.461005
DATACENTER_MID_ZN_6 DIRECT AIR 4.40
DATACENTER_TOP_ZN_6 DIRECT AIR 0.448267
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.25 0.362370 0.308000 1.62 0.966319 0.500000 0.001051 0.000356 1.62 12.80 0.008000
CORE_MID VAV BOX COMPONENT 48.98 0.388321 0.330000 16.16 1.00 0.500000 0.000981 0.007470 16.16 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 4.85 0.392283 0.333000 1.61 1.00 0.500000 0.000971 0.001299 1.76 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.893749 0.267212 0.227000 0.202881 0.712566 0.500000 0.001426 0.000109 0.202881 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.01 0.151940 0.129000 0.130669 0.405172 0.500000 0.002508 0.000077 0.130669 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.12 0.212603 0.181000 0.203325 0.566940 0.500000 0.001792 0.000145 0.203325 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.29 0.119591 0.102000 0.131267 0.318910 0.500000 0.003186 0.000047 0.131267 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.40 0.284273 0.242000 2.03 0.758061 0.500000 0.001340 0.003189 4.35 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 10.56       0.388467 0.500000 0.002615 0.002128 2.90 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 10.79 0.221316 0.188000 2.03 0.590175 0.500000 0.001722 0.003168 4.32 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 11.21 0.137258 0.117000 1.31 0.366021 0.500000 0.002776 0.001884 2.57 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.962940 0.248012 0.211000 0.203180 0.661365 0.500000 0.001536 0.000421 0.573847 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.07 0.143393 0.122000 0.130944 0.382381 0.500000 0.002657 0.000278 0.378953 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.19 0.199985 0.170000 0.203017 0.533294 0.500000 0.001905 0.000419 0.571197 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.20 0.127907 0.109000 0.131155 0.341085 0.500000 0.002979 0.000259 0.353943 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 16264.35 0.000356 453.94
CORE_MID VAV BOX REHEAT COIL 341488.44 0.007470 10952.26
CORE_TOP VAV BOX REHEAT COIL 59375.28 0.001299 2314.26
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4993.32 0.000109 167.70
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 3507.79 0.000077 121.70
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 6612.92 0.000145 252.30
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2142.61 0.000047 65.06
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 145764.75 0.003189 5668.51
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 97272.91 0.002128 3782.56
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 144832.07 0.003168 5632.29
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 86146.19 0.001884 3350.47
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 19231.19 0.000421 747.54
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 12699.03 0.000278 493.61
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 19142.58 0.000419 744.10
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11862.62 0.000259 461.14
VAV_BOT WITH REHEAT HEATING COIL 23877.66 0.000522 545.16
VAV_MID WITH REHEAT HEATING COIL 170146.35 0.003722 3929.58
VAV_TOP WITH REHEAT HEATING COIL 14410.06 0.000315 336.08
CAV_BAS HEATING COIL 235688.33 0.005156 7677.65
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 4.78 2.28 9.57 2.28 8.46 8.46 0.300000 0.270092 8.46
VAV_MID WITH REHEAT 44.98 22.85 89.95 24.91 78.17 78.17 0.300000 0.318719 78.17
VAV_TOP WITH REHEAT 4.64 2.28 9.28 3.64 8.69 8.69 0.300000 0.419054 8.69
CAV_BAS 5.01 5.01 5.01 5.01 5.01 5.01 1.00 1.00 5.01
AIRLOOP DATACENTER BASEMENT 21.26 21.26 21.26 21.26 21.26 21.26 1.00 0.999991 21.26
AIRLOOP DATACENTER BOT 0.461005 0.461005 0.461005 0.461005 0.461005 0.461005 1.00 1.00 0.461005
AIRLOOP DATACENTER MID 4.40 4.40 4.40 4.40 4.40 4.40 1.00 1.00 4.40
AIRLOOP DATACENTER TOP 0.448267 0.448267 0.448267 0.448267 0.448267 0.448267 1.00 1.00 0.448267
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 8.46  
VAV_MID WITH REHEAT_OA_CONTROLLER 78.17  
VAV_TOP WITH REHEAT_OA_CONTROLLER 8.69  
CAV_BAS_OA_CONTROLLER 5.01 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.26 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.461005 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.40 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.448267 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.03
VAV_MID WITH REHEAT OA HEAT RECOVERY 20.31
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.44 6.67 11.05 0.010806 0.008500 219741.72 0.006285 8.46
VAV_MID WITH REHEAT COOLING COIL 26.72 6.67 11.05 0.011115 0.008500 2131844.07 0.060970 78.17
VAV_TOP WITH REHEAT COOLING COIL 26.30 6.67 11.05 0.010769 0.008500 223281.80 0.006386 8.69
CAV_BAS COOLING COIL 25.09 6.67 11.42 0.010810 0.008500 119601.09 0.003421 5.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 8.46
VAV_MID WITH REHEAT FAN 78.17
VAV_TOP WITH REHEAT FAN 8.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.006285 0.000076
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000522  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.060970 0.000008
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.003722  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.006386 0.000075
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000315  
CAV_BAS_COOLC_CONTROLLER 0.003421 0.000139
CAV_BAS_HEATC_CONTROLLER 0.005156  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.26 432910.51 311283.87 0.010602
AIRLOOP DATACENTER BOT COOLING COIL 0.461005 9410.66 6753.82 0.000230
AIRLOOP DATACENTER MID COOLING COIL 4.40 89955.59 64470.36 0.002203
AIRLOOP DATACENTER TOP COOLING COIL 0.448267 9167.81 6573.01 0.000225
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.26 21.26 21.26 21.26 432910.51 432910.51 14482.89 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.461005 0.461005 0.461005 0.461005 9410.66 9410.66 669.05 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.40 4.40 4.40 4.40 89955.59 89955.59 6690.49 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.448267 0.448267 0.448267 0.448267 9167.81 9167.81 669.05 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.26
AIRLOOP DATACENTER BOT SUPPLY FAN 0.461005
AIRLOOP DATACENTER MID SUPPLY FAN 4.40
AIRLOOP DATACENTER TOP SUPPLY FAN 0.448267
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.26 432910.51 0.010602
AIRLOOP DATACENTER BOT HEATING COIL 0.461005 9410.66 0.000230
AIRLOOP DATACENTER MID HEATING COIL 4.40 89955.59 0.002203
AIRLOOP DATACENTER TOP HEATING COIL 0.448267 9167.81 0.000225
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 14482.89
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 669.05
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6690.49
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 669.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000080 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.077061 12457.21  
HEATSYS1 PUMP 0.030963 9232.43 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.077061 9.25
HEATSYS1 0.030963 3.72
COOLSYS1_SUPPLY 0.077061 9.25
SINGLE WATER PLANT LOOP 0.013260 1.59
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.077061 0.077061 323465.63 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1415458.45 1415458.45 0.030963
CENTRAL BOILER 546195.96 535638.85 0.013260
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.038531 4312.27
COOLSYS1 CHILLER2 PUMP 0.038531 4312.27
PLANT CIRC PUMP 0.013260 3348.46
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.077061 0.038863 1362188.39 1368648.74 0.067286
COOLSYS1 CHILLER2 0.077061 0.038863 1362188.39 1368648.74 0.067286
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013260 139666.47 59408.87 69833.23 7004.20 21428.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.134573 16.15
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.134573 32987.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 49.90 1623881.23 9.98 202985.15
TOWERWATERSYS COOLTOWER 2 49.90 1623881.23 9.98 202985.15
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.070350
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 24.20 18.90 15.70 13.60 15.50 17.10 21.20 26.90 27.60 27.90 27.40 26.20


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tampa-MacDill AFB FL USA TMY3 WMO#=747880 27.85 -82.52 -5.00 8.00 101229 1.2032


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.85 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 5.778 4.842 0.000 0.000 0.000 0.000 10.619 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.847 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.847 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.847 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 5.778 8.070 0.000 0.000 0.000 0.000 13.848 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 7.174 215.299 0.000 0.000 0.000 0.000 222.473 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 7.174 215.299 0.000 0.000 0.000 0.000 222.473 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 7.174 215.299 0.000 0.000 0.000 0.000 222.473 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 5.778 484.423 0.000 0.000 0.000 0.000 490.201 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 16058.301 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16058.301
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 14421.483 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14421.483
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 14421.483 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14421.483
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 14421.483 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14421.483
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 1810.761 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.761
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 1810.801 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.801
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 1810.761 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.761
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 1810.801 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.801
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 1810.761 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.761
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 1810.801 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1810.801
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1166.923 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1166.923
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 4527.754 5.778 107.340 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4527.754
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 259.704 7.174 133.277 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 259.704
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 259.704 7.174 133.277 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 259.704
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 259.704 7.174 133.277 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 259.704


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.452 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.400 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.662 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5215
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5467
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4343
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.81534556E-15 0.47534309E-16 -0.12491808E-09 -0.15651055E-17
51 8 0.18376575E-07 0.18892299E-12 0.33997552E-03 -0.20894799E-09
52 7 -0.11109444E-01 0.10222184E-07 -0.21454547E-01 0.12631841E-03
53 6 0.37458360 0.36213810E-05 0.44579641 -0.43850983E-02
54 5 -4.8902522 0.13734403E-03 -4.2389002 0.59460182E-01
55 4 31.674104 0.11393769E-02 20.648451 -0.40448134
56 3 -108.39803 0.25142476E-02 -54.058051 1.4743366
57 2 194.32686 0.14299560E-02 76.440274 -2.8561868
58 1 -170.12819 0.15421596E-03 -54.840647 2.7274244
59 0 57.057407 0.88766417E-06 15.629571  
60 9 0.15527634E-14 0.48972640E-16 -0.12737755E-09 -0.48559044E-17
61 8 0.18724477E-07 0.18300980E-12 0.34384059E-03 -0.21290374E-09
62 7 -0.11225506E-01 0.98577958E-08 -0.21621905E-01 0.12763808E-03
63 6 0.37773826 0.34860306E-05 0.44850155 -0.44222837E-02
64 5 -4.9210508 0.13200769E-03 -4.2597582 0.59842059E-01
65 4 31.810414 0.10936068E-02 20.730162 -0.40629104
66 3 -108.68827 0.24103335E-02 -54.219675 1.4785295
67 2 194.61479 0.13693941E-02 76.588171 -2.8607587
68 1 -170.23464 0.14753937E-03 -54.883028 2.7292902
69 0 57.057407 0.84836289E-06 15.622061  
70 9 0.10580992E-14 0.52916478E-16 -0.11479962E-09 -0.26242945E-17
71 8 0.16943687E-07 0.21219816E-12 0.32378363E-03 -0.19265555E-09
72 7 -0.10622292E-01 0.11706466E-07 -0.20751735E-01 0.12077931E-03
73 6 0.36134106 0.41796623E-05 0.43441658 -0.42290030E-02
74 5 -4.7609497 0.15957712E-03 -4.1510514 0.57856955E-01
75 4 31.101728 0.13316855E-02 20.304070 -0.39688243
76 3 -107.17897 0.29539374E-02 -53.376774 1.4567269
77 2 193.11717 0.16877407E-02 75.817308 -2.8369794
78 1 -169.68078 0.18278585E-03 -54.662957 2.7195831
79 0 57.057407 0.10570564E-05 15.661738  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.455_SHGC_EAST_0.249 35 1 VerySmooth 2.586 2.586 1.000 0.250    
2 WINDOW_U_0.455_SHGC_SOUTH_0.249 36 1 VerySmooth 2.586 2.586 1.000 0.250    
3 WINDOW_U_0.455_SHGC_WEST_0.249 37 1 VerySmooth 2.586 2.586 1.000 0.250    
4 WINDOW_U_0.455_SHGC_NORTH_0.249 38 1 VerySmooth 2.586 2.586 1.000 0.250    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.486 6.0748E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6847E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6860E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.8818E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8829E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9924E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9931E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7516E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7521E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7154E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8001E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.9067E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.9772E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0116E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0681E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7664E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8035E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.1920E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6854E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1006
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8760E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.2933E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6417E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1496E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.0924E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7233E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8383E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.9152E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.0185E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0194E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0976E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7668E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8046E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6846E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6862E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.8817E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8831E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9923E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9934E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7515E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7521E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.9759E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.1286E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8196E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9773E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5901E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6698E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9952E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0209E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.5185E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1055E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2851E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9265E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.3008E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7275E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2799E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.2243E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.9415E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.0029E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7769E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8221E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5667E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5861E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9953E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0213E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7132E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7146E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4753E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4765E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3125E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3134E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7516E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7522E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7456E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8245E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5020E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5652E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3339E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3802E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7668E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8046E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6290E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3597E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0389E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0404E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8205E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 7.0923E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1496E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0921E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7429E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8213E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4984E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5582E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3278E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3618E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7664E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8035E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7131E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7144E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4752E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4762E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3124E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3130E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7515E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7521E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2773E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3420E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9736E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0203E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9448E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.9618E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9954E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0213E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3704E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.6802E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9096E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4183E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.1697E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3027E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2799E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2243E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3031E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4167E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0063E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1165E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9664E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0342E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9952E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0208E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.8268E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.4412E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1055
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.7165E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.1592E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.0480E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.8633E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.9092E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.3778E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.0518E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1188E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.8366E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1059E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.5769E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9603E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9312E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.3109E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.1835E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.6391E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.7446E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3925E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3248E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.8633E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9088E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.0772E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.4619E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.5589E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.1293E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.8349E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0028E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.9603E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.9312E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.8394E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.4529E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1057
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.7296E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.1744E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.0581E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.8716E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.9134E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.3832E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.0568E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1250E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.8414E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1147E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.5824E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9686E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9354E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.3115E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.1860E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.6399E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.7466E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3963E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3272E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.8716E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9131E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.0799E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.4654E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.5618E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.1323E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.8411E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0068E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.9686E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9354E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 69579.95808 69579.95808 5.01159 5.01159 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 4.60000 5.25715E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 72878.93664 72878.93664 5.24891 5.24891 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 680307.28509 680307.28509 48.98126 48.98126 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 178873.28890 178873.28890 7.48994 10.77825 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 67345.89878 67345.89878 4.84865 4.84865 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 41625.15625 41625.15625 1.76435 1.76435 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12290.45537 12290.45537 0.89375 0.89375 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 33.90000 1.65364E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 2956.16406 2956.16406 0.12440 0.13533 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 13929.54397 13929.54397 1.01294 1.01294 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 30.22650 1.65295E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 2195.48401 2195.48401 9.25703E-002 9.25703E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15447.79565 15447.79565 1.12334 1.12334 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 33.76833 1.65361E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 4570.13840 4570.13840 0.19350 0.19350 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 17697.50656 17697.50656 1.28693 1.28693 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 825.57409 825.57409 3.50739E-002 8.72129E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 115521.18973 115521.18973 8.40110 8.40110 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 33.90000 1.65364E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 102071.53484 102071.53484 4.34665 4.34665 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 145277.19753 145277.19753 10.56496 10.56496 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 30.67417 1.65303E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 68112.18998 68112.18998 2.90087 2.90087 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 148387.26493 148387.26493 10.79119 10.79119 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 33.83417 1.65363E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 101419.45529 101419.45529 4.31877 4.31877 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 154186.37661 154186.37661 11.21284 11.21284 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 32.66233 1.65340E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 60332.62421 60332.62421 2.56836 2.56836 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13240.83711 13240.83711 0.96294 0.96294 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 33.82100 1.65362E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 13461.41067 13461.41067 0.57385 0.57385 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 14758.57010 14758.57010 1.07331 1.07331 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 30.89800 1.65307E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 8888.80223 8888.80223 0.37895 0.37895 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 16421.04825 16421.04825 1.19422 1.19422 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 33.90000 1.65364E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 13399.47505 13399.47505 0.57120 0.57120 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 16545.49841 16545.49841 1.20326 1.20326 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 8304.14824 8304.14824 0.35394 0.35394 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8037.91551 8037.91551 0.46101 0.46101 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 76632.48465 76632.48465 4.39521 4.39521 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7815.78906 7815.78906 0.44827 0.44827 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370704.02631 370704.02631 21.26087 21.26087 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 26.71100 1.65229E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 4.60000 5.25715E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 135848.58 8.45934 8.45934 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 15727.81 1.58644 1.58644 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1242389.73 78.16574 78.16574 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 201288.10 24.91290 24.91290 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 141445.17 8.69169 8.69169 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 19839.11 3.64229 3.64229 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00
7 CAV_BAS Cooling Sensible 74266.08 5.01159 5.01159 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CAV_BAS Heating Sensible 51365.55 1.20016 1.20016 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 367336.59 21.26107 21.26107 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 14482.89 0.33839 0.33839 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 7993.30 0.46101 0.46101 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 669.05 1.56323E-002 1.56323E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 76244.26 4.39521 4.39521 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6690.49 0.15632 0.15632 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7775.52 0.44827 0.44827 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 669.05 1.56323E-002 1.56323E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.01159
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.24891
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36237
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61666
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.96632
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.05141E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.55783E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.61666
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16264.34832
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.55783E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 453.93959
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 48.98126
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38832
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33000
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.16382
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.81148E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.47007E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.16382
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 341488.44435
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.47007E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 10952.25502
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.84865
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.39228
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33300
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61460
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.71237E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.29884E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.76435
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 59375.27514
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.29884E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2314.26439
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.89375
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26721
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22700
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20288
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71257
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.42583E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.09229E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20288
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4993.32313
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.09229E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 167.69943
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.01294
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15194
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12900
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13067
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40517
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.50757E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.67330E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13067
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3507.78936
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.67330E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 121.69949
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12334
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21260
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.18100
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20333
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56694
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.79208E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.44658E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20333
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6612.92475
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.44658E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 252.30492
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.28693
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11959
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10200
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13127
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31891
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.18586E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.68696E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13127
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2142.60933
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.68696E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 65.05808
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.40110
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28427
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24200
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03307
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75806
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.34026E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.18861E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.34665
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 145764.74658
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.18861E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5668.50787
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.56496
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38847
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.61541E-003
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.12785E-003
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.90087
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
122 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 97272.91006
123 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.12785E-003
124 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3782.56465
125 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.79119
126 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22132
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.18800
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02874
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59017
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.72152E-003
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.16821E-003
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.31877
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
136 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 144832.07362
137 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.16821E-003
138 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5632.29418
139 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.21284
140 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13726
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11700
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.31190
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36602
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.77580E-003
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.88445E-003
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.56836
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
150 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 86146.19400
151 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.88445E-003
152 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3350.47037
153 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.96294
154 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24801
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21100
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20318
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66137
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.53622E-003
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.20683E-004
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.57385
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
164 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19231.18650
165 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.20683E-004
166 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 747.54290
167 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.07331
168 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14339
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12200
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13094
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38238
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.65704E-003
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.77792E-004
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37895
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
178 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12699.03161
179 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.77792E-004
180 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 493.61041
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.19422
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19999
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.17000
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20302
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53329
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.90514E-003
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.18744E-004
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.57120
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
192 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19142.57844
193 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.18744E-004
194 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 744.10398
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.20326
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12791
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10900
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13116
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34108
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.97873E-003
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.59495E-004
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35394
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
206 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11862.61716
207 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.59495E-004
208 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 461.14155
209 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46101
210 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.39521
211 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.44827
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.26087
213 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.78293
214 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28480
215 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.56586
216 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.28480
217 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.45934
218 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.45934
219 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
220 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.27009
221 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 44.97568
222 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.84758
223 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 89.95135
224 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 24.91290
225 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 78.16574
226 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 78.16574
227 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
228 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.31872
229 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.64119
230 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28290
231 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.28237
232 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.64229
233 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.69169
234 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.69169
235 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
236 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.41905
237 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.01159
238 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.01159
239 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.01159
240 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.01159
241 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.01159
242 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.01159
243 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.26087
246 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.26087
247 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.26087
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.26087
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.26107
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.26107
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
253 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46101
254 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46101
255 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46101
256 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.46101
257 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.46101
258 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.46101
259 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
260 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
261 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.39521
262 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.39521
263 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.39521
264 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.39521
265 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.39521
266 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.39521
267 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
268 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
269 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.44827
270 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.44827
271 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.44827
272 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.44827
273 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.44827
274 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.44827
275 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
276 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
277 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.45934
278 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 78.16574
279 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.69169
280 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.01159
281 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.26107
282 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.46101
283 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.39521
284 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.44827
285 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.45934
286 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.03050
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.43894
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04763
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.08061E-002
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 219741.71708
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.28459E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.45934
295 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 23877.65950
296 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.22324E-004
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 545.15698
298 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.45934
299 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.28459E-003
300 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.57712E-005
301 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.22324E-004
302 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 78.16574
303 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 20.30600
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.72230
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04862
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.11154E-002
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2131844.06773
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.09705E-002
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 78.16574
312 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 170146.34531
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.72196E-003
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3929.58049
315 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 78.16574
316 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.09705E-002
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.81018E-006
318 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.72196E-003
319 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.69169
320 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.03050
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.29960
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04751
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.07685E-002
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 223281.79897
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.38583E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.69169
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 14410.05568
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.15220E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 336.08450
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.69169
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.38583E-003
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.45699E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.15220E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.01159
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.09278
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.42496
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.08101E-002
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 119601.09011
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.42058E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.01159
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 235688.33338
347 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.15569E-003
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 7677.65215
349 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.01159
350 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.42058E-003
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.39214E-004
352 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.15569E-003
353 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.26107
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.26107
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 432910.50933
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 311283.87307
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.06020E-002
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.26107
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.26107
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.26107
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.26107
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 432910.50933
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 432910.50933
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 14482.88751
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
367 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.26107
368 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.26107
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 432910.50933
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.06020E-002
371 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 14482.88751
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 7.98784E-005
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
376 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46101
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46101
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9410.65657
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6753.81825
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.30466E-004
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46101
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46101
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46101
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46101
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9410.65657
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9410.65657
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.04940
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46101
391 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46101
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9410.65657
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.30466E-004
394 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.04940
395 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.39521
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.39521
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 89955.58797
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 64470.35503
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.20301E-003
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.39521
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.39521
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.39521
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.39521
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 89955.58797
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 89955.58797
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6690.49404
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
409 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.39521
410 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.39521
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 89955.58797
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.20301E-003
413 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6690.49404
414 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.44827
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.44827
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9167.81324
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6573.00875
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.24519E-004
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.44827
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.44827
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.44827
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.44827
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9167.81324
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9167.81324
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.04940
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
428 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.44827
429 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.44827
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9167.81324
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.24519E-004
432 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.04940
433 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 7.70615E-002
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 12457.21006
435 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 7.70615E-002
436 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 9.24738
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 7.70615E-002
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 7.70615E-002
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 323465.62712
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 8.33000
441 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.09632E-002
442 PlantLoop HEATSYS1 Plant Loop Volume [m3] 3.71558
443 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.09632E-002
444 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 9232.42964
445 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
446 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1415458.44624
447 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1415458.45000
448 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.09632E-002
449 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 7.70615E-002
450 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 9.24738
451 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 3.85307E-002
452 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 4312.27332
453 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 3.85307E-002
454 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 4312.27332
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 7.70615E-002
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.88630E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1362188.39373
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1368648.73500
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 6.72863E-002
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 7.70615E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.88630E-002
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1362188.39373
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1368648.73500
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 6.72863E-002
465 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.32599E-002
466 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.59119
467 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.32599E-002
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3348.46382
469 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.32599E-002
470 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
471 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 59408.86576
472 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
473 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7004.19857
474 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21428.39722
475 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 546195.95699
476 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 535638.85000
477 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.32599E-002
478 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
479 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
480 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
482 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
483 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.13457
484 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 16.14872
485 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.13457
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 32987.33999
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 49.89902
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1623881.23333
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 9.97980
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 202985.15417
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 49.89902
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1623881.23333
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 9.97980
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 202985.15417
495 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.03500E-002
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.03500E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 22641.21
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 475777.46
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 82623.97
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6954.76
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4884.61
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9203.41
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2986.51
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 202841.48
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 135361.84
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 201543.59
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 119878.18
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 26761.54
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 17671.59
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 26638.23
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 16507.66
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 28542.78
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 210220.62
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 18297.99
19 Coil:Heating:Water CAV_BAS HEATING COIL 263141.24


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 227181.20 156643.00 70538.20 0.69 33863.39 343.46
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2140936.27 1465293.11 675643.15 0.68 315642.63 3201.42
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 232447.38 160535.62 71911.76 0.69 34782.14 352.78
4 Coil:Cooling:Water CAV_BAS COOLING COIL 129160.56 90444.41 38716.15 0.70 19326.46 196.02


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.80 23.21
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.80 23.21


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2062150862 0.2045242813 Pass Pass 0.6903209525 0.6698616097 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.2268131950 0.2454809854 Pass Pass 0.2456524943 0.4298035093 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 0.1489488211 0.1979885214 Pass Pass 0.2101226406 0.4059826448 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.1294061398 0.1915938219 Pass Pass 0.2021045376 0.4001507662 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.1916320922 0.2088710204 Pass Pass 0.2448478581 0.4288006160 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.2650807081 0.3243621900 Pass Pass 0.2584364502 0.4422923565 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.4214655507 0.5916622276 Pass Pass 0.2716686247 0.4604852213 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.2772749753 0.3871329540 Pass Pass 0.2635250320 0.4618078656 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1354837136 0.1825093347 Pass Pass 0.2097839782 0.4048457179 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1863863296 0.2143306997 Pass Pass 0.2099018211 0.4064953317 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.3862944234 0.6388230730 Pass Pass 0.2244814218 0.4164633016 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1946849405 0.3001732031 Pass Pass 0.2139155751 0.4092015438 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1269756527 0.1685991667 Pass Pass 0.2015841346 0.3994391884 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.1726423570 0.1945740047 Pass Pass 0.2206734701 0.4421786278 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.3705802531 0.6213418348 Pass Pass 0.2485149218 0.4800692624 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1837957131 0.3065478421 Pass Pass 0.2115919599 0.4139387188 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.5793523121E-002 4.4113560054E-002 Pass Pass 0.2572071566 0.4141134757 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.4663841509E-002 3.9370865316E-002 Pass Pass 0.2292753661 0.4127331609 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.6745987978E-002 7.0154025508E-002 Pass Pass 0.3180098741 1.0161074396 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 1.0821657501E-005 1.8405177376E-005 Pass Pass 3.3431930516E-003 4.5451741177E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 1.0183300872E-005 1.7681559951E-005 Pass Pass 4.9298052253E-003 5.5109787832E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 1.0076726795E-005 1.8080486856E-005 Pass Pass 7.5672828905E-003 5.3524390241E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.4742683405E-004 2.4379604983E-004 Pass Pass 6.3129202607E-005 1.1179500889E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5694.90 -54.0 0.00 4642.90 29380.26 39664.12



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 4.60 0.00 4.60 Wetbulb [C] 2.50 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 33.90 7.90 25.10 Wetbulb [C] 3.10 270.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 66.00 12      
Feb 66.00 22      
Mar 126.00 32      
Apr 206.00 19      
May 144.00 46      
Jun 99.00 30      
Jul 192.00 52      
Aug 240.00 34      
Sep 310.00 44      
Oct 34.00 10      
Nov 63.00 12      
Dec 35.00 24      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.158 1.400 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.158 1.400 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.158 1.400 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.158 1.400 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.455_SHGC_NORTH_0.249   115.90 0.00 0.00 115.90 1158.95 2.586 0.250 0.275             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.455_SHGC_EAST_0.249   77.26 0.00 0.00 77.26 772.63 2.586 0.250 0.275             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.455_SHGC_SOUTH_0.249   115.90 0.00 0.00 115.90 1158.95 2.586 0.250 0.275             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.455_SHGC_WEST_0.249   77.26 0.00 0.00 77.26 772.63 2.586 0.250 0.275             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.455_SHGC_NORTH_0.249   115.90 0.00 0.00 115.90 115.90 2.586 0.250 0.275             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.455_SHGC_EAST_0.249   77.26 0.00 0.00 77.26 77.26 2.586 0.250 0.275             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.455_SHGC_SOUTH_0.249   115.90 0.00 0.00 115.90 115.90 2.586 0.250 0.275             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.455_SHGC_WEST_0.249   77.26 0.00 0.00 77.26 77.26 2.586 0.250 0.275             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.586 0.250 0.275                      
North Total or Average             1390.74 2.586 0.250 0.275                      
Non-North Total or Average             3245.06 2.586 0.250 0.275                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.7776 2779.43 16058.30 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 116.04
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 5.7776 2496.12 14421.48 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 104.21
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 5.7776 24961.20 144214.83 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 1042.11
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 5.7776 2496.12 14421.48 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.50 0.0000 Y 104.21
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 5.7776 313.41 1810.76 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.95 0.0000 Y 7.46
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.85 0.0000 Y 4.79
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 5.7776 313.42 1810.80 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.71 0.0000 Y 7.38
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.83 0.0000 Y 4.78
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 5.7776 3134.13 18107.61 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.91 0.0000 Y 74.48
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 5.7776 2019.75 11669.23 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.82 0.0000 Y 47.80
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 5.7776 3134.20 18108.01 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.69 0.0000 Y 73.74
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 5.7776 2019.75 11669.23 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.80 0.0000 Y 47.76
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 5.7776 313.41 1810.76 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.91 0.0000 Y 7.45
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.82 0.0000 Y 4.78
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 5.7776 313.42 1810.80 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.69 0.0000 Y 7.37
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 5.7776 201.98 1166.92 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.80 0.0000 Y 4.78
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 5.7776 783.68 4527.75 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.66 0.0000 Y 32.85
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 7.1736 36.20 259.70 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 1.68
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 7.1736 362.03 2597.04 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 16.76
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 7.1736 36.20 259.70 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 1.68
Interior Lighting Total       5.7907 46320.38 268225.21               539.72


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.80 698.43
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.80 250.80
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.76 698.41
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.76 250.79
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.80 698.43
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.80 250.80
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.76 698.41
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.76 250.79
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.80 698.43
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.80 250.80
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1810.76 698.41
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1810.76 250.79
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1166.92 450.08
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1166.92 161.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 12952.94 AstronomicalClock -   41.73 41.73 101.45
EXTERIOR_LIGHTS_B 919.74 AstronomicalClock -   83.73 62.73 10.83
EXTERIOR_LIGHTS_C 17215.91 AstronomicalClock -   83.73 47.05 152.06
Exterior Lighting Total 31088.59           264.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2686169.47          
HEATSYS1 BOILER Boiler:HotWater 1415458.45 0.90        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1368648.74 6.59 1200617.12 5.87 6.80 23.21
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1368648.74 6.59 1200617.12 5.87 6.80 23.21
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 535638.85 0.90        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1623881.23          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1623881.23          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 219741.72 227181.20 156643.00 70538.20 0.69 - 33863.39 343.46
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2131844.07 2140936.27 1465293.11 675643.15 0.68 - 315642.63 3201.42
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 223281.80 232447.38 160535.62 71911.76 0.69 - 34782.14 352.78
CAV_BAS COOLING COIL Coil:Cooling:Water 119601.09 129160.56 90444.41 38716.15 0.70 - 19326.46 196.02
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   432910.51 311283.87 121626.64 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9410.66 6753.82 2656.84 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   89955.59 64470.36 25485.23 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9167.81 6573.01 2594.80 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 16264.35 22641.21 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 341488.44 475777.46 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 59375.28 82623.97 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 4993.32 6954.76 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 3507.79 4884.61 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 6612.92 9203.41 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 2142.61 2986.51 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 145764.75 202841.48 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 97272.91 135361.84 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 144832.07 201543.59 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 86146.19 119878.18 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 19231.19 26761.54 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 12699.03 17671.59 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 19142.58 26638.23 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11862.62 16507.66 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 23877.66 28542.78 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 170146.35 210220.62 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 14410.06 18297.99 -
CAV_BAS HEATING COIL Coil:Heating:Water 235688.33 263141.24 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   432910.51 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9410.66 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   89955.59 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9167.81 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   14482.89 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   669.05 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6690.49 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   669.05 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.46 18280.19 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 78.17 168911.99 2160.95 1.00 1.08 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.69 18782.28 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.01 8497.92 1695.65 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.26 35250.28 1657.97 1.00 1.13 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 516.38 1120.11 1.00 1.64 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.40 4923.11 1120.11 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 502.11 1120.11 1.00 1.66 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.077061 12457.21 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.030963 9232.43 298174.34 0.91 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.038531 4312.27 111917.77 0.91 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.038531 4312.27 111917.77 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013260 3348.46 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.134573 32987.34 245126.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.49 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 69579.96 69579.96 25.03 5.012 5.012 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00901 28.05 0.01653 1.200 0.00
CORE_BOTTOM 72878.94 72878.94 29.20 5.249 5.249 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00893 28.05 0.01653 1.078 0.00
CORE_MID 680307.29 680307.29 272.55 48.981 48.981 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00896 28.05 0.01653 10.778 0.00
CORE_TOP 67345.90 67345.90 26.98 4.849 4.849 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00896 28.05 0.01653 1.078 0.00
PERIMETER_BOT_ZN_3 12290.46 12290.46 39.21 0.894 0.894 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 24.00 24.00 0.00896 33.90 0.01654 0.135 0.00
PERIMETER_BOT_ZN_2 13929.54 13929.54 68.97 1.013 1.013 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 24.00 24.00 0.00877 30.23 0.01653 0.087 0.00
PERIMETER_BOT_ZN_1 15447.80 15447.80 49.29 1.123 1.123 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 24.00 0.00886 33.77 0.01654 0.135 0.00
PERIMETER_BOT_ZN_4 17697.51 17697.51 87.62 1.287 1.287 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00871 32.79 0.01653 0.087 0.00
PERIMETER_MID_ZN_3 115521.19 115521.19 368.59 8.401 8.401 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00918 33.90 0.01654 1.353 0.00
PERIMETER_MID_ZN_2 145277.20 145277.20 719.28 10.565 10.565 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 24.00 24.00 0.00887 30.67 0.01653 0.872 0.00
PERIMETER_MID_ZN_1 148387.26 148387.26 473.45 10.791 10.791 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00904 33.83 0.01654 1.353 0.00
PERIMETER_MID_ZN_4 154186.38 154186.38 763.39 11.213 11.213 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00884 32.66 0.01653 0.872 0.00
PERIMETER_TOP_ZN_3 13240.84 13240.84 42.25 0.963 0.963 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00917 33.82 0.01654 0.135 0.00
PERIMETER_TOP_ZN_2 14758.57 14758.57 73.07 1.073 1.073 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 24.00 24.00 0.00891 30.90 0.01653 0.087 0.00
PERIMETER_TOP_ZN_1 16421.05 16421.05 52.39 1.194 1.194 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00905 33.90 0.01654 0.135 0.00
PERIMETER_TOP_ZN_4 16545.50 16545.50 81.92 1.203 1.203 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00886 32.79 0.01653 0.087 0.00
DATACENTER_BOT_ZN_6 8037.92 8037.92 222.03 0.461 0.461 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.016 0.00
DATACENTER_MID_ZN_6 76632.48 76632.48 2116.76 4.395 4.395 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.156 0.00
DATACENTER_TOP_ZN_6 7815.79 7815.79 215.89 0.448 0.448 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370704.03 370704.03 473.03 21.261 21.261 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 27.00 27.00 0.00854 26.71 0.01652 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.44 0.00526 4.60 0.00526 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 23.06 0.00526 4.60 0.00526 1.078 0.00
CORE_MID 178873.29 178873.29 71.66 7.490 10.778 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 10.778 0.00
CORE_TOP 41625.16 41625.16 16.68 1.764 1.764 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 1.078 0.00
PERIMETER_BOT_ZN_3 2956.16 2956.16 9.43 0.124 0.135 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00701 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_2 2195.48 2195.48 10.87 0.093 0.093 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00712 4.60 0.00526 0.087 0.00
PERIMETER_BOT_ZN_1 4570.14 4570.14 14.58 0.193 0.193 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00733 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_4 825.57 825.57 4.09 0.035 0.087 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00656 4.60 0.00526 0.087 0.00
PERIMETER_MID_ZN_3 102071.53 102071.53 325.68 4.347 4.347 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00763 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_2 68112.19 68112.19 337.23 2.901 2.901 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00764 4.60 0.00526 0.872 0.00
PERIMETER_MID_ZN_1 101419.46 101419.46 323.59 4.319 4.319 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00762 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_4 60332.62 60332.62 298.71 2.568 2.568 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00755 4.60 0.00526 0.872 0.00
PERIMETER_TOP_ZN_3 13461.41 13461.41 42.95 0.574 0.574 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_2 8888.80 8888.80 44.01 0.379 0.379 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 4.60 0.00526 0.087 0.00
PERIMETER_TOP_ZN_1 13399.48 13399.48 42.75 0.571 0.571 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00774 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_4 8304.15 8304.15 41.11 0.354 0.354 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00771 4.60 0.00526 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 24.97 0.00801 4.60 0.00526 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 24.09 0.00553 4.60 0.00526 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 8.46 8.46 1.59 1.59 8.4593 2.2848 8.4593 0.2701 0.3000
VAV_MID WITH REHEAT 78.17 78.17 24.91 24.91 78.1657 24.9129 78.1657 0.3187 0.3000
VAV_TOP WITH REHEAT 8.69 8.69 3.64 3.64 8.6917 3.6423 8.6917 0.4191 0.3000
CAV_BAS 5.01 5.01 1.20 1.20 5.0116 5.0116 5.0116 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.26 21.26 0.34 0.34 21.2611 21.2609 21.2611 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.46 0.46 0.02 0.02 0.4610 0.4610 0.4610 1.0000 1.0000
AIRLOOP DATACENTER MID 4.40 4.40 0.16 0.16 4.3952 4.3952 4.3952 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.45 0.45 0.02 0.02 0.4483 0.4483 0.4483 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 16264.348 16264.348 1.616663 0.00035578 453.940   1/21 00:10:00   1/21 00:10:00 16264.35 16264.35 1.616663 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 0.00 0.00 16292.26 16292.26
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 341488.444 341488.444 16.163817 0.00747007 10952.255 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 341488.44 341488.44 16.163817 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 178873.29 0.00 342371.31 342371.31
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 59375.275 59375.275 1.764348 0.00129884 2314.264 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 59375.28 59375.28 1.764348 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 41625.16 0.00 59501.65 59501.65
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 4993.323 4993.323 0.202881 0.00010923 167.699 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4993.32 4993.32 0.202881 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00701233 45.3685 2956.16 0.00 5005.67 5005.67
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 3507.789 3507.789 0.130669 0.00007673 121.699 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3507.79 3507.79 0.130669 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00711975 46.0560 2195.48 0.00 3516.14 3516.14
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 6612.925 6612.925 0.203325 0.00014466 252.305 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6612.92 6612.92 0.203325 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00733049 47.4033 4570.14 0.00 6627.34 6627.34
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 2142.609 2142.609 0.131267 0.00004687 65.058 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2142.61 2142.61 0.131267 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00655722 42.4538 825.57 0.00 2148.53 2148.53
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 145764.747 145764.747 4.346652 0.00318861 5668.508 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 145764.75 145764.75 4.346652 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00762834 49.3064 102071.53 0.00 146075.15 146075.15
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 97272.910 97272.910 2.900868 0.00212785 3782.565 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 97272.91 97272.91 2.900868 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00764147 49.3903 68112.19 0.00 97480.05 97480.05
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 144832.074 144832.074 4.318773 0.00316821 5632.294 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 144832.07 144832.07 4.318773 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00762426 49.2804 101419.46 0.00 145140.49 145140.49
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 86146.194 86146.194 2.568360 0.00188445 3350.470 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 86146.19 86146.19 2.568360 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00755344 48.8286 60332.62 0.00 86329.63 86329.63
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 19231.187 19231.187 0.573847 0.00042068 747.543 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19231.19 19231.19 0.573847 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00774524 50.0521 13461.41 0.00 19272.14 19272.14
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 12699.032 12699.032 0.378953 0.00027779 493.610 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12699.03 12699.03 0.378953 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00774823 50.0712 8888.80 0.00 12726.08 12726.08
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 19142.578 19142.578 0.571197 0.00041874 744.104 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19142.58 19142.58 0.571197 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00774325 50.0395 13399.48 0.00 19183.35 19183.35
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 11862.617 11862.617 0.353943 0.00025950 461.142 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11862.62 11862.62 0.353943 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00771023 49.8290 8304.15 0.00 11887.88 11887.88
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 219741.717 -999.000 8.459342 0.00628459 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 219741.72 158323.34 8.459342 26.44 19.08 0.01080614 11.05 11.05 0.00850000 33.90 0.01653638 25.13 24.0030 24.00 0.00893188 48.0124 113293.42 0.00 220088.75 156323.13
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 23877.660 23877.660 2.537803 0.00052232 545.157 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23877.66 23877.66 2.537803 5.02 4.97 0.00537364 12.80 11.59 0.00800000 4.60 0.00525715 4.60 80.0102 22.01 0.00618518 37.6578 10547.36 0.00 24877.50 24877.50
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2131844.068 -999.000 78.165735 0.06097047 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 2131844.07 1488927.20 78.165735 26.72 19.41 0.01111536 11.05 11.05 0.00850000 33.90 0.01653638 25.13 25.9781 24.00 0.00905797 48.6815 1014993.87 0.00 2135157.79 1473109.93
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 170146.345 170146.345 23.449721 0.00372196 3929.580 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 170146.35 170146.35 23.449721 6.80 6.16 0.00560538 12.80 11.59 0.00800000 4.60 0.00525715 4.60 86.5938 21.00 0.00778325 50.2931 317305.64 0.00 183229.05 183229.05
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 223281.799 -999.000 8.691689 0.00638583 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 223281.80 161193.83 8.691689 26.30 19.01 0.01076852 11.05 11.05 0.00850000 33.82 0.01653623 25.11 23.3614 24.00 0.00900366 48.3940 119173.84 0.00 223637.32 159117.86
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 14410.056 14410.056 2.607507 0.00031522 336.084 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14410.06 14410.06 2.607507 8.23 7.14 0.00582862 12.80 11.59 0.00800000 4.60 0.00525715 4.60 77.8713 20.26 0.00780385 52.7922 39251.06 0.00 15948.68 15948.68
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 119601.090 -999.000 5.011589 0.00342058 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 119601.09 83818.70 5.011589 25.09 18.65 0.01081008 11.42 11.42 0.00850000 28.55 0.01652632 23.72 23.9476 24.00 0.00900322 48.3901 68718.32 0.00 119785.18 83293.03
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 235688.333 235688.333 5.011589 0.00515569 7677.652 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 235688.33 235688.33 5.011589 1.10 1.10 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 23.9476 25.44 0.00525715 26.0830 0.00 0.00 189179.92 189179.92
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 432910.509 311283.873 21.261066 0.01060195 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 405616.00 395683.06 -999.0 28.51 18.07 0.00866978 12.80 12.09 0.00850000 33.90 0.01653638 25.13 -999.0000 27.00 0.00854239 38.4511 370237.69 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9410.657 6753.818 0.461005 0.00023047 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8820.41 8364.79 -999.0 28.09 18.09 0.00885932 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00859004 38.6604 8037.92 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 89955.588 64470.355 4.395207 0.00220301 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 84350.72 79796.12 -999.0 28.10 18.10 0.00887670 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00859441 38.6801 76632.48 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9167.813 6573.009 0.448267 0.00022452 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8595.56 8139.92 -999.0 28.10 18.10 0.00886951 12.80 12.09 0.00850000 31.41 0.01653169 24.48 -999.0000 27.00 0.00859255 38.6717 7812.93 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 432910.509 432910.509 21.261066 0.01060195 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 432910.51 432910.51 21.261066 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 1.5916 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9410.657 9410.657 0.461005 0.00023047 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9410.66 9410.66 0.461005 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.3909 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 89955.588 89955.588 4.395207 0.00220301 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 89955.59 89955.59 4.395207 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5567 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9167.813 9167.813 0.448267 0.00022452 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9167.81 9167.81 0.448267 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4873 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 14482.888 14482.888 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 14482.89 14482.89 21.261066 0.07 0.07 0.00844839 40.00 21.17 0.00800000 4.60 0.00525715 4.60 1.5916 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 669.049 669.049 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.05 669.05 0.461005 0.16 0.16 0.00839004 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.3909 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6690.494 6690.494 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6690.49 6690.49 4.395207 0.16 0.16 0.00791660 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5567 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 669.049 669.049 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.05 669.05 0.448267 0.16 0.16 0.00551913 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4873 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 16264.348 16264.348 1.616663 0.00035578 453.940 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 1.1264 1.149052   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 16264.35 16264.35 1.0000 1.94511577 1.616663 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.35574678 60.00 48.89 11.11 0.000 16264.35 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6744 0.00 0.00 16292.26 16292.26 1.94511577 12.80 11.60 0.00800000 33059.8 21.01 14.86 0.00800000 41435.8
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 341488.444 341488.444 16.163817 0.00747007 10952.255 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 23.6497 24.125642 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 341488.44 341488.44 1.0000 19.44776985 16.163817 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 7.46930718 60.00 48.89 11.11 0.000 341488.44 4.60 0.00525715 4.60 0.00000000 0.0000 20.58 0.00800000 21.00 0.00800000 51.6744 178873.29 0.00 342371.31 342371.31 19.44776985 12.80 11.60 0.00800000 33059.8 30.06 18.06 0.00800000 50664.5
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 59375.275 59375.275 1.764348 0.00129884 2314.264 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 4.1120 4.194773 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 59375.28 59375.28 1.0000 2.12280477 1.764348 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.29870330 60.00 48.89 11.11 0.000 59375.28 4.60 0.00525715 4.60 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 51.6744 41625.16 0.00 59501.65 59501.65 2.12280477 12.80 11.60 0.00800000 33059.8 40.29 21.27 0.00800000 61089.6
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 4993.323 4993.323 0.202881 0.00010923 167.699 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 0.3458 0.352771 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4993.32 4993.32 1.0000 0.24409968 0.202881 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.10921794 60.00 48.89 11.11 0.000 4993.32 4.60 0.00525715 4.60 0.00000000 0.0000 20.83 0.00701233 21.00 0.00701233 45.3685 2956.16 0.00 5005.67 5005.67 0.24409968 12.80 11.60 0.00800000 33059.8 32.91 18.99 0.00800000 53566.5
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 3507.789 3507.789 0.130669 0.00007673 121.699 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 0.2429 0.247820 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3507.79 3507.79 1.0000 0.15721620 0.130669 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.07672516 60.00 48.89 11.11 0.000 3507.79 4.60 0.00525715 4.60 0.00000000 0.0000 20.87 0.00711975 21.00 0.00711975 46.0560 2195.48 0.00 3516.14 3516.14 0.15721620 12.80 11.60 0.00800000 33059.8 34.73 19.57 0.00800000 55424.9
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 6612.925 6612.925 0.203325 0.00014466 252.305 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 0.4580 0.467193 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6612.92 6612.92 1.0000 0.24463411 0.203325 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.14464316 60.00 48.89 11.11 0.000 6612.92 4.60 0.00525715 4.60 0.00000000 0.0000 20.87 0.00733049 21.00 0.00733049 47.4033 4570.14 0.00 6627.34 6627.34 0.24463411 12.80 11.60 0.00800000 33059.8 39.37 20.99 0.00800000 60150.7
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 2142.609 2142.609 0.131267 0.00004687 65.058 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 0.1484 0.151372 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2142.61 2142.61 1.0000 0.15793565 0.131267 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.04686486 60.00 48.89 11.11 0.000 2142.61 4.60 0.00525715 4.60 0.00000000 0.0000 20.93 0.00655722 21.00 0.00655722 42.4538 825.57 0.00 2148.53 2148.53 0.15793565 12.80 11.60 0.00800000 33059.8 26.14 16.72 0.00800000 46663.7
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 145764.747 145764.747 4.346652 0.00318861 5668.508 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 10.0949 10.298059 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 145764.75 145764.75 1.0000 5.22974729 4.346652 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 3.18828261 60.00 48.89 11.11 0.000 145764.75 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00762834 21.00 0.00762834 49.3064 102071.53 0.00 146075.15 146075.15 5.22974729 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.4
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 97272.910 97272.910 2.900868 0.00212785 3782.565 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 6.7366 6.872184 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 97272.91 97272.91 1.0000 3.49022778 2.900868 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 2.12763055 60.00 48.89 11.11 0.000 97272.91 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00764147 21.00 0.00764147 49.3903 68112.19 0.00 97480.05 97480.05 3.49022778 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60989.3
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 144832.074 144832.074 4.318773 0.00316821 5632.294 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 10.0303 10.232167 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 144832.07 144832.07 1.0000 5.19620487 4.318773 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 3.16788244 60.00 48.89 11.11 0.000 144832.07 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00762426 21.00 0.00762426 49.2804 101419.46 0.00 145140.49 145140.49 5.19620487 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.8
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 86146.194 86146.194 2.568360 0.00188445 3350.470 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 5.9660 6.086098 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 86146.19 86146.19 1.0000 3.09016607 2.568360 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.88425815 60.00 48.89 11.11 0.000 86146.19 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00755344 21.00 0.00755344 48.8286 60332.62 0.00 86329.63 86329.63 3.09016607 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60996.7
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 19231.187 19231.187 0.573847 0.00042068 747.543 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 1.3319 1.358654 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19231.19 19231.19 1.0000 0.69043371 0.573847 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.42063983 60.00 48.89 11.11 0.000 19231.19 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00774524 21.00 0.00774524 50.0521 13461.41 0.00 19272.14 19272.14 0.69043371 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.9
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 12699.032 12699.032 0.378953 0.00027779 493.610 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 0.8795 0.897167 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12699.03 12699.03 1.0000 0.45594428 0.378953 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.27776333 60.00 48.89 11.11 0.000 12699.03 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00774823 21.00 0.00774823 50.0712 8888.80 0.00 12726.08 12726.08 0.45594428 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 19142.578 19142.578 0.571197 0.00041874 744.104 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 1.3257 1.352394 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19142.58 19142.58 1.0000 0.68724482 0.571197 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.41870172 60.00 48.89 11.11 0.000 19142.58 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00774325 21.00 0.00774325 50.0395 13399.48 0.00 19183.35 19183.35 0.68724482 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60973.2
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 11862.617 11862.617 0.353943 0.00025950 461.142 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 0.8215 0.838076 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11862.62 11862.62 1.0000 0.42585306 0.353943 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.25946861 60.00 48.89 11.11 0.000 11862.62 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00771023 21.00 0.00771023 49.8290 8304.15 0.00 11887.88 11887.88 0.42585306 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60975.3
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 219741.717 -999.000 8.459342 0.00628459 -999.000 -999.0000 1.00000 1.00000 1024.9281 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.459342 10.17800048   4197.9300 999.8980 77.05360192 15.00 6.67 8.33 2694468.67 8.1553 8.155289 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 219741.72 158323.34 1.0000 10.17800048 8.459342 26.44 19.08 0.01080614 54123.5 11.05 11.05 0.00850000 32533.7 6.28394420 6.67 15.00 8.33 18280.188 201461.53 33.90 0.01653638 25.13 2.03050000 24.0030 24.00 0.00893188 24.00 0.00893188 48.0124 113293.42 0.00 220088.75 156323.13 10.17800048 26.44 19.09 0.01080614 54123.5 11.45 11.36 0.00832222 32499.6
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 23877.660 23877.660 2.537803 0.00052232 545.157 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.459342 10.17800048   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 1.6536 1.686921 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23877.66 23877.66 1.0000 3.05340014 2.537803 5.02 4.97 0.00537364 18531.4 12.80 11.59 0.00800000 33059.8 0.52227118 60.00 48.89 11.11 0.000 23877.66 4.60 0.00525715 4.60 2.03050000 80.0102 6.69 0.00583992 22.01 0.00618518 37.6578 10547.36 0.00 24877.50 24877.50 3.05340014 2.80 2.80 0.00537364 16280.7 10.83 7.86 0.00537364 24428.2
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2131844.068 -999.000 78.165735 0.06097047 -999.000 -999.0000 1.00000 1.00000 1025.5029 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 78.165735 94.04642517   4197.9300 999.8980 77.05360192 15.00 6.67 8.33 2694468.67 79.1193 79.119275 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 2131844.07 1488927.20 1.0000 94.04642517 78.165735 26.72 19.41 0.01111536 55202.7 11.05 11.05 0.00850000 32534.7 60.96425085 6.67 15.00 8.33 168911.991 1962932.08 33.90 0.01653638 25.13 20.30600000 25.9781 24.00 0.00905797 24.00 0.00905797 48.6815 1014993.87 0.00 2135157.79 1473109.93 94.04642517 26.72 19.42 0.01111536 55202.7 11.45 11.36 0.00832434 32499.4
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 170146.345 170146.345 23.449721 0.00372196 3929.580 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 78.165735 94.04642517   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 11.7834 12.020582 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 170146.35 170146.35 1.0000 28.21392755 23.449721 6.80 6.16 0.00560538 20921.1 12.80 11.59 0.00800000 33059.8 3.72157635 60.00 48.89 11.11 0.000 170146.35 4.60 0.00525715 4.60 20.30600000 86.5938 21.00 0.00785472 21.00 0.00778325 50.2931 317305.64 0.00 183229.05 183229.05 28.21392755 2.80 2.80 0.00560538 16861.5 9.20 7.35 0.00560538 23355.7
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 223281.799 -999.000 8.691689 0.00638583 -999.000 -999.0000 1.00000 1.00000 1024.8581 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.691689 10.45755211   4197.9300 999.8980 77.05360192 15.00 6.67 8.33 2694468.67 8.2867 8.286673 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 Sensible 223281.80 161193.83 1.0000 10.45755211 8.691689 26.30 19.01 0.01076852 53884.8 11.05 11.05 0.00850000 32533.5 6.38517977 6.67 15.00 8.33 18782.276 204499.52 33.82 0.01653623 25.11 2.03050000 23.3614 24.00 0.00900366 24.00 0.00900366 48.3940 119173.84 0.00 223637.32 159117.86 10.45755211 26.30 19.02 0.01076852 53884.8 11.45 11.36 0.00832241 32499.5
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 14410.056 14410.056 2.607507 0.00031522 336.084 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.691689 10.45755211   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 0.9980 1.018049 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 14410.06 14410.06 1.0000 3.13726563 2.607507 8.23 7.14 0.00582862 22935.0 12.80 11.59 0.00800000 33059.8 0.31518821 60.00 48.89 11.11 0.000 14410.06 4.60 0.00525715 4.60 2.03050000 77.8713 21.00 0.00783966 20.26 0.00780385 52.7922 39251.06 0.00 15948.68 15948.68 3.13726563 2.80 2.80 0.00582862 17420.9 7.81 6.94 0.00582862 22504.6
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 119601.090 -999.000 5.011589 0.00342058 -999.000 -999.0000 1.00000 1.00000 1024.9354 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.011589 6.02977761   4197.9300 999.8980 77.05360192 15.00 6.67 8.33 2694468.67 4.4388 4.438763 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 119601.09 83818.70 1.0000 6.02977761 5.011589 25.09 18.65 0.01081008 52753.8 11.42 11.42 0.00850000 32918.8 3.42022710 6.67 15.00 8.33 8497.922 111103.17 28.55 0.01652632 23.72 1.20015641 23.9476 24.00 0.00900322 24.00 0.00900322 48.3901 68718.32 0.00 119785.18 83293.03 6.02977761 25.09 18.66 0.01081008 52753.8 11.62 11.52 0.00841091 32888.2
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 235688.333 235688.333 5.011589 0.00515569 7677.652 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.011589 6.02977761   4197.9300 999.8980 30.96003428 48.89 60.00 11.11 1443945.11 16.3225 16.651025 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 235688.33 235688.33 1.0000 6.02977761 5.011589 1.10 1.10 0.00525715 14265.5 40.00 21.17 0.00800000 60796.0 5.15516291 60.00 48.89 11.11 0.000 235688.33 4.60 0.00525715 4.60 1.20015641 23.9476 0.00 0.00525715 25.44 0.00525715 26.0830 0.00 0.00 189179.92 189179.92 6.02977761 12.80 8.65 0.00525715 26134.9 43.72 20.28 0.00525715 57509.1
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 432910.509 311283.873 21.261066 0.01060195 -999.000 -999.0000 -999.00000 -999.00000 1020.9567 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 Sensible 405616.00 395683.06 0.9370 -999.0 -999.0 28.51 18.07 0.00866978 50789.1 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 405616.00 33.90 0.01653638 25.13 0.33839277 -999.0000 27.00 0.00854239 27.00 0.00854239 38.4511 370237.69 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9410.657 6753.818 0.461005 0.00023047 -999.000 -999.0000 -999.00000 -999.00000 1021.3090 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8820.41 8364.79 0.9373 -999.0 -999.0 28.09 18.09 0.00885932 50843.5 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8820.41 31.21 0.01653132 24.43 0.01563234 -999.0000 27.00 0.00859004 27.00 0.00859004 38.6604 8037.92 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 89955.588 64470.355 4.395207 0.00220301 -999.000 -999.0000 -999.00000 -999.00000 1021.3413 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 84350.72 79796.12 0.9377 -999.0 -999.0 28.10 18.10 0.00887670 50894.9 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 84350.72 31.21 0.01653132 24.43 0.15632344 -999.0000 27.00 0.00859441 27.00 0.00859441 38.6801 76632.48 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9167.813 6573.009 0.448267 0.00022452 -999.000 -999.0000 -999.00000 -999.00000 1021.3280 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8595.56 8139.92 0.9376 -999.0 -999.0 28.10 18.10 0.00886951 50880.7 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8595.56 31.41 0.01653169 24.48 0.01563234 -999.0000 27.00 0.00859255 27.00 0.00859255 38.6717 7812.93 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 432910.509 432910.509 21.261066 0.01060195 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 432910.51 432910.51 1.0000 25.58061117 21.261066 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 432910.51 4.60 0.00525715 4.60 0.33839277 1.5916 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9410.657 9410.657 0.461005 0.00023047 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9410.66 9410.66 1.0000 0.55466648 0.461005 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9410.66 4.60 0.00525715 4.60 0.01563234 3.3909 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 89955.588 89955.588 4.395207 0.00220301 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 89955.59 89955.59 1.0000 5.28816788 4.395207 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 89955.59 4.60 0.00525715 4.60 0.15632344 3.5567 0.00 0.00801468 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9167.813 9167.813 0.448267 0.00022452 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9167.81 9167.81 1.0000 0.53934038 0.448267 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9167.81 4.60 0.00525715 4.60 0.01563234 3.4873 0.00 0.00552860 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 14482.888 14482.888 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.261066 25.58061117   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 14482.89 14482.89 1.0000 25.58061117 21.261066 0.07 0.07 0.00844839 21203.6 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 14482.89 4.60 0.00525715 4.60 0.33839277 1.5916 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.049 669.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.461005 0.55466648   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.05 669.05 1.0000 0.55466648 0.461005 0.16 0.16 0.00839004 21142.2 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.05 4.60 0.00525715 4.60 0.01563234 3.3909 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6690.494 6690.494 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.395207 5.28816788   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6690.49 6690.49 1.0000 5.28816788 4.395207 0.16 0.16 0.00791660 19965.8 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6690.49 4.60 0.00525715 4.60 0.15632344 3.5567 0.00 0.00801468 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.049 669.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.448267 0.53934038   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.05 669.05 1.0000 0.53934038 0.448267 0.16 0.16 0.00551913 13965.9 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.05 4.60 0.00525715 4.60 0.01563234 3.4873 0.00 0.00552860 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.46 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 78.17 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.69 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 5.01 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialEnthalpy 0.34 21.26 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 4892.17 2512.00 2393.33
CORE_BOTTOM 4712.17 235.00 0.00
CORE_MID 2660.00 1476.00 0.00
CORE_TOP 3090.00 1860.83 49.67
PERIMETER_BOT_ZN_3 4123.50 1236.50 51.67
PERIMETER_BOT_ZN_2 4238.50 1231.00 242.33
PERIMETER_BOT_ZN_1 4704.17 930.17 269.00
PERIMETER_BOT_ZN_4 5105.17 831.17 512.67
PERIMETER_MID_ZN_3 3561.00 2307.50 362.00
PERIMETER_MID_ZN_2 3326.17 1727.67 462.17
PERIMETER_MID_ZN_1 4419.50 1384.83 433.83
PERIMETER_MID_ZN_4 4239.83 1671.67 433.83
PERIMETER_TOP_ZN_3 3825.83 2539.67 772.17
PERIMETER_TOP_ZN_2 4074.00 2117.50 662.83
PERIMETER_TOP_ZN_1 4355.33 1672.67 601.67
PERIMETER_TOP_ZN_4 4231.50 1938.50 640.00
DATACENTER_BOT_ZN_6 5943.00 1088.17 1088.17
DATACENTER_MID_ZN_6 5936.50 80.33 80.33
DATACENTER_TOP_ZN_6 5860.67 263.33 243.00
DATACENTER_BASEMENT_ZN_6 5943.00 5936.67 5936.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 71.83 0.00 2.33
CORE_BOTTOM 0.00 0.17 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 2.83 0.00 1.00
PERIMETER_BOT_ZN_2 0.00 49.00 0.00 48.33
PERIMETER_BOT_ZN_1 0.00 76.17 0.00 72.50
PERIMETER_BOT_ZN_4 0.00 238.17 0.00 97.33
PERIMETER_MID_ZN_3 0.33 0.50 0.00 0.50
PERIMETER_MID_ZN_2 0.00 60.33 0.00 58.50
PERIMETER_MID_ZN_1 0.00 88.17 0.00 86.33
PERIMETER_MID_ZN_4 0.00 67.50 0.00 40.83
PERIMETER_TOP_ZN_3 8.67 24.67 1.83 19.50
PERIMETER_TOP_ZN_2 5.67 74.83 0.33 65.83
PERIMETER_TOP_ZN_1 2.67 81.83 0.17 74.67
PERIMETER_TOP_ZN_4 2.33 84.17 0.00 49.33
DATACENTER_BOT_ZN_6 0.00 34.33 0.00 34.33
DATACENTER_MID_ZN_6 0.00 26.83 0.00 26.83
DATACENTER_TOP_ZN_6 0.00 16.00 0.00 16.00
DATACENTER_BASEMENT_ZN_6 0.00 633.33 0.00 552.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 8.83 1083.83 1.83 800.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.22 149.60 6779.02 0.930 0.000 0.000 0.000
CORE_BOTTOM 55.88 134.35 6849.35 0.562 0.000 0.000 0.000
CORE_MID 55.88 134.35 6849.35 0.488 0.000 0.000 0.000
CORE_TOP 55.88 134.35 6849.35 0.476 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.02 16.87 860.00 0.627 0.034 0.000 0.000
PERIMETER_BOT_ZN_2 4.52 10.87 554.22 0.776 0.035 0.000 0.000
PERIMETER_BOT_ZN_1 7.02 16.87 860.02 0.915 0.034 0.000 0.000
PERIMETER_BOT_ZN_4 4.52 10.87 554.22 1.216 0.035 0.000 0.000
PERIMETER_MID_ZN_3 7.02 16.87 860.00 0.595 0.079 0.000 0.000
PERIMETER_MID_ZN_2 3.95 10.87 554.22 0.729 0.087 0.000 0.000
PERIMETER_MID_ZN_1 7.02 16.87 860.02 0.893 0.079 0.000 0.000
PERIMETER_MID_ZN_4 4.52 10.87 554.22 0.846 0.082 0.000 0.000
PERIMETER_TOP_ZN_3 7.02 16.87 860.00 0.591 0.098 0.000 0.000
PERIMETER_TOP_ZN_2 4.52 10.87 554.22 0.777 0.101 0.000 0.000
PERIMETER_TOP_ZN_1 7.02 16.87 860.02 0.860 0.098 0.000 0.000
PERIMETER_TOP_ZN_4 4.52 10.87 554.22 0.822 0.101 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.54 42.18 1911.37 11.824 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.22 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.95 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.54 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.22 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.95 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.54 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1031.21 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 38012388.04 0.00 38012388.04 0.00 38012388.04 37848132.68 4161.85 2793.80 1804.36 166.75
CORE_BOTTOM 23111782.05 0.00 23111782.05 0.00 23111782.05 33990283.35 6770.76 101.36 1887.88 112.49
CORE_MID 0.20E+09 0.00 0.20E+09 0.00 0.20E+09 0.34E+09 6726.36 301.63 1732.01 16.64
CORE_TOP 19173554.20 0.00 19173554.20 0.00 19173554.20 33990283.35 6803.26 340.71 1616.03 42.28
PERIMETER_BOT_ZN_3 3220940.10 0.00 3220940.10 328931.10 3549871.19 4267819.30 4470.16 116.54 4173.30 112.49
PERIMETER_BOT_ZN_2 2555739.04 0.00 2555739.04 219287.25 2775026.29 2750345.05 4421.79 85.57 4252.65 112.49
PERIMETER_BOT_ZN_1 4665652.31 0.00 4665652.31 328931.10 4994583.41 4267912.63 4194.97 55.83 4509.20 112.49
PERIMETER_BOT_ZN_4 3993026.52 0.00 3993026.52 219287.25 4212313.77 2750345.05 4097.63 8.88 4653.49 112.49
PERIMETER_MID_ZN_3 29942300.42 0.00 29942300.42 771421.61 30713722.03 42678193.03 4656.95 253.43 3849.62 16.64
PERIMETER_MID_ZN_2 24308021.96 0.00 24308021.96 514280.72 24822302.68 27503450.52 4584.58 157.68 4017.73 830.33
PERIMETER_MID_ZN_1 44875292.25 0.00 44875292.25 771421.61 45646713.87 42679126.28 4289.62 184.81 4285.57 16.64
PERIMETER_MID_ZN_4 27375612.53 0.00 27375612.53 514280.72 27889893.26 27503450.52 4286.39 40.04 4433.57 16.64
PERIMETER_TOP_ZN_3 2987664.38 0.00 2987664.38 957784.80 3945449.18 4267819.30 4623.42 273.69 3862.89 42.28
PERIMETER_TOP_ZN_2 2524046.73 0.00 2524046.73 638522.76 3162569.49 2750345.05 4314.60 173.58 4271.82 42.28
PERIMETER_TOP_ZN_1 4331275.02 0.00 4331275.02 957784.80 5289059.81 4267912.63 4310.10 179.17 4270.73 42.28
PERIMETER_TOP_ZN_4 2668587.02 0.00 2668587.02 638522.76 3307109.78 2750345.05 4316.48 73.03 4370.49 42.28
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.19E+09 0.00 0.19E+09 0.00 0.19E+09 10671554.30 2699.81 2876.00 3184.19 1095.83
Total Facility 0.35E+10 0.00 0.35E+10 30003098.57 0.36E+10 0.50E+10 7588.50 4354.12 6115.65 1950.84


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.7139 0.0000 1.7139 0.0000 1.7139 1.2002 1452.92 2792.74 1697.34
CORE_BOTTOM 1.0481 0.0000 1.0481 0.0000 1.0481 1.0778 4061.57 101.05 1780.38
CORE_MID 9.0987 0.0000 9.0987 0.0000 9.0987 10.7782 3921.44 301.41 1720.15
CORE_TOP 0.8897 0.0000 0.8897 0.0000 0.8897 1.0778 3999.68 340.11 1603.21
PERIMETER_BOT_ZN_3 0.1469 0.0000 0.1469 0.0079 0.1548 0.1353 1760.40 116.16 4066.45
PERIMETER_BOT_ZN_2 0.1171 0.0000 0.1171 0.0053 0.1224 0.0872 1712.02 85.05 4145.93
PERIMETER_BOT_ZN_1 0.2144 0.0000 0.2144 0.0079 0.2223 0.1353 1485.21 55.61 4402.18
PERIMETER_BOT_ZN_4 0.1835 0.0000 0.1835 0.0053 0.1887 0.0872 1387.95 8.71 4546.34
PERIMETER_MID_ZN_3 1.3946 0.0000 1.3946 0.0185 1.4131 1.3533 1852.79 253.26 3836.95
PERIMETER_MID_ZN_2 1.1002 0.0000 1.1002 0.0131 1.1133 0.8721 1512.37 151.38 3370.25
PERIMETER_MID_ZN_1 2.0926 0.0000 2.0926 0.0185 2.1111 1.3533 1484.73 184.58 4273.69
PERIMETER_MID_ZN_4 1.2758 0.0000 1.2758 0.0123 1.2881 0.8721 1481.53 39.82 4421.65
PERIMETER_TOP_ZN_3 0.1387 0.0000 0.1387 0.0229 0.1616 0.1353 1827.10 273.15 3842.74
PERIMETER_TOP_ZN_2 0.1173 0.0000 0.1173 0.0153 0.1326 0.0872 1516.76 173.12 4253.12
PERIMETER_TOP_ZN_1 0.2016 0.0000 0.2016 0.0229 0.2245 0.1353 1509.28 178.65 4255.07
PERIMETER_TOP_ZN_4 0.1241 0.0000 0.1241 0.0153 0.1394 0.0872 1515.10 72.54 4355.35
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 6.1071 0.0000 6.1071 0.0000 6.1071 0.3384 978.64 2876.00 2088.36
Total Facility 161.7859 0.0000 161.7859 0.7263 162.5123 158.4706 4771.50 4351.57 4981.40


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 54353238.83 0.00 54353238.83 48026705.38 4065.56 0.00 4694.44 112.49
VAV_MID WITH REHEAT 0.47E+09 0.00 0.47E+09 0.48E+09 4216.43 0.83 4542.74 16.64
VAV_TOP WITH REHEAT 45867664.74 0.00 45867664.74 48026705.38 4229.79 1.40 4528.81 42.28
CAV_BAS 55027135.14 0.00 55027135.14 37848132.68 4139.73 0.96 4619.31 166.75
AIRLOOP DATACENTER BASEMENT 0.28E+09 0.00 0.28E+09 10671554.30 2699.81 0.00 6060.19 1095.83
AIRLOOP DATACENTER BOT 353645.50 0.00 353645.50 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3536455.01 0.00 3536455.01 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 353645.50 0.00 353645.50 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 2.4754 0.0000 2.4754 1.5229 1361.05 0.00 4581.95
VAV_MID WITH REHEAT 21.7065 0.0000 21.7065 15.2292 1416.07 0.33 4526.60
VAV_TOP WITH REHEAT 2.1299 0.0000 2.1299 1.5229 1441.19 1.26 4500.56
CAV_BAS 2.4811 0.0000 2.4811 1.2002 1447.30 0.25 4495.45
AIRLOOP DATACENTER BASEMENT 8.8407 0.0000 8.8407 0.3384 978.64 0.00 4964.36
AIRLOOP DATACENTER BOT 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1653 0.0000 0.1653 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 114.45 1634.20 0.00 0.00 0.00 2945.79 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 266.91 1341.50 0.00 0.00 0.00 2935.49 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 102.62 1410.58 0.00 0.00 0.00 3042.49 0.00 0.00 0.00
CAV_BAS 0.00 2792.33 1873.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 2876.00 3184.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.7320 4.7091 0.0000 0.0000 0.0000 2.4567 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 28.3843 36.7535 0.0000 0.0000 0.0000 24.7882 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.7126 3.6046 0.0000 0.0000 0.0000 2.4491 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.7376 5.7960 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4900 24.4881 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2263 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1528
Defaulted Fields 1187
Fields with Defaults 3933
Autosized Fields 336
Autosizable Fields 414
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 26761.82 292329.59 15-JAN-05:00 1628470.72 03-AUG-15:30
Electricity:Building 16388.50 215366.33 14-MAY-17:10 942265.72 12-DEC-08:10
Electricity:Zone:BASEMENT 540.44 14022.76 01-JAN-00:10 23631.68 02-JAN-08:10
Electricity:SpaceType:GENERAL 16388.50 215366.33 14-MAY-17:10 942265.72 12-DEC-08:10
InteriorLights:Electricity 1712.11 8110.17 01-JAN-08:50 164275.09 25-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 116.04 565.21 01-JAN-00:10 10174.14 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 1712.11 8110.17 01-JAN-08:50 164275.09 25-OCT-07:10
LightsWired:InteriorLights:Electricity 1712.11 8110.17 01-JAN-08:50 164275.09 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 116.04 565.21 01-JAN-00:10 10174.14 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 1712.11 8110.17 01-JAN-08:50 164275.09 25-OCT-07:10
Electricity:Zone:CORE_BOTTOM 393.83 4960.84 01-JAN-00:10 26343.72 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
Electricity:Zone:CORE_MID 3938.24 49608.19 01-JAN-00:10 263436.56 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1042.12 5076.02 01-JAN-00:10 91370.93 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1042.12 5076.02 01-JAN-00:10 91370.93 02-JAN-08:10
Electricity:Zone:CORE_TOP 393.82 4960.82 01-JAN-00:10 26343.66 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 104.21 507.60 01-JAN-00:10 9137.09 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 43.83 589.50 26-MAR-17:10 3177.78 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 7.46 30.32 01-JAN-08:50 1017.23 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 7.46 30.32 01-JAN-08:50 1017.23 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 28.22 379.89 26-MAR-17:10 2031.40 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.79 19.54 01-JAN-07:50 639.05 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.79 19.54 01-JAN-07:50 639.05 12-DEC-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 43.75 589.50 12-MAR-17:10 3169.66 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 7.38 30.33 01-JAN-07:50 1009.08 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 7.38 30.33 01-JAN-07:50 1009.08 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 28.22 379.89 26-FEB-18:10 2054.08 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.78 19.54 01-JAN-08:50 661.75 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.78 19.54 01-JAN-08:50 661.75 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 438.13 5894.96 12-MAR-17:10 31762.48 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 74.48 303.25 01-JAN-08:50 10156.96 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 74.48 303.25 01-JAN-08:50 10156.96 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 282.15 3798.93 26-MAR-17:10 20289.56 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 47.80 195.42 01-JAN-07:50 6366.14 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 47.80 195.42 01-JAN-07:50 6366.14 12-DEC-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 437.40 5895.05 12-MAR-17:10 31680.82 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 73.74 303.26 01-JAN-07:50 10074.98 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 73.74 303.26 01-JAN-07:50 10074.98 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 282.11 3798.91 26-FEB-18:10 20520.50 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 47.76 195.42 01-JAN-08:50 6597.18 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 47.76 195.42 01-JAN-08:50 6597.18 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 43.81 589.50 12-MAR-17:10 3175.98 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 7.45 30.32 01-JAN-08:50 1015.43 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 7.45 30.32 01-JAN-08:50 1015.43 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 28.21 379.89 26-MAR-17:10 2028.75 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.78 19.54 01-JAN-07:50 636.41 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.78 19.54 01-JAN-07:50 636.41 12-DEC-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 43.74 589.50 12-MAR-17:10 3167.81 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 7.37 30.33 01-JAN-07:50 1007.22 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 7.37 30.33 01-JAN-07:50 1007.22 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 28.21 379.89 26-FEB-18:10 2051.89 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.78 19.54 01-JAN-08:50 659.56 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.78 19.54 01-JAN-08:50 659.56 25-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7527.71 95067.50 01-JAN-00:10 382501.19 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 32.85 159.37 01-JAN-00:10 2868.67 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 32.85 159.37 01-JAN-00:10 2868.67 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 155.56 1956.73 01-JAN-00:10 7940.74 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1555.56 19567.35 01-JAN-00:10 79407.42 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 16.76 81.29 01-JAN-00:10 1463.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 16.76 81.29 01-JAN-00:10 1463.20 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 155.56 1956.73 01-JAN-00:10 7940.74 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 1.68 8.13 01-JAN-00:10 146.32 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 4389.50 3744.32 10-JAN-05:00 378949.82 05-JUL-12:10
HeatRejection:Electricity 1551.85 244.67 05-JAN-08:00 81663.54 02-JAN-11:30
General:HeatRejection:Electricity 1551.85 244.67 05-JAN-08:00 81663.54 02-JAN-11:30
ElectricityProduced:Facility 542.70 -0.00 20-DEC-17:30 86329.64 10-APR-12:30
ElectricityProduced:Plant 542.70 -0.00 20-DEC-17:30 86329.64 10-APR-12:30
Photovoltaic:ElectricityProduced 566.52 0.00 01-JAN-00:10 89893.10 10-APR-12:30
PowerConversion:ElectricityProduced -23.82 -3563.46 10-APR-12:30 0.00 01-JAN-00:10
Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
DCtoACInverter Ancillary:Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 4570.14 45577.39 15-JAN-06:00 389944.97 18-APR-14:20
ExteriorEquipment:Electricity 1203.69 17814.45 01-JAN-00:10 73697.78 25-OCT-07:20
Transformer:ExteriorEquipment:Electricity 54.35 979.82 01-JAN-00:10 3369.18 25-OCT-07:20
ElectricityPurchased:Facility 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
ElectricityPurchased:Plant 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
Cogeneration:ElectricityPurchased 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
General:Cogeneration:ElectricityPurchased 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
ElectricityNet:Plant 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
Cogeneration:ElectricityNet 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
General:Cogeneration:ElectricityNet 26219.12 279944.38 15-JAN-10:10 1580520.21 30-AUG-16:00
Fans:Electricity 2028.07 41191.87 01-JAN-04:50 255581.86 03-MAY-12:30
General:Fans:Electricity 2028.07 41191.87 01-JAN-04:50 255581.86 03-MAY-12:30
ExteriorLights:Electricity 264.34 0.00 01-JAN-07:30 31088.59 01-JAN-06:10
General:ExteriorLights:Electricity 264.34 0.00 01-JAN-07:30 31088.59 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1144.44 16803.04 01-JAN-00:10 70012.65 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 4.90 31.59 01-JAN-00:10 315.94 01-JAN-07:10
HeatRecovery:Electricity 50.61 0.00 01-JAN-00:10 4520.72 02-JAN-10:10
General:HeatRecovery:Electricity 50.61 0.00 01-JAN-00:10 4520.72 02-JAN-10:10
Cooling:Electricity 4290.25 2318.74 10-JAN-07:10 395912.86 10-AUG-12:10
General:Cooling:Electricity 4290.25 2318.74 10-JAN-07:10 395912.86 10-AUG-12:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 338.60 0.00 01-JAN-00:10 100000.00 04-FEB-17:10
General:Humidifier:Electricity 338.60 0.00 01-JAN-00:10 100000.00 04-FEB-17:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 645.91 3348.46 01-JAN-00:20 57493.23 23-OCT-09:30
General:Pumps:Electricity 645.91 3348.46 01-JAN-00:20 57493.23 23-OCT-09:30
WIRED_LTG_ELECTRICITY 48.11 0.00 01-JAN-00:10 4616.13 25-OCT-07:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 711.88 7280.88 29-APR-16:10 487423.11 06-FEB-06:10
NaturalGas:Plant 711.88 7280.88 29-APR-16:10 487423.11 06-FEB-06:10
Heating:NaturalGas 67.00 0.00 01-JAN-00:10 463207.59 06-FEB-05:20
Boiler:Heating:NaturalGas 67.00 0.00 01-JAN-00:10 463207.59 06-FEB-05:20
WaterSystems:NaturalGas 644.88 7280.88 23-JAN-05:20 74963.99 27-JAN-12:30
Water Heater:WaterSystems:NaturalGas 644.88 7280.88 23-JAN-05:20 74963.99 27-JAN-12:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 24230.16 7740.17 11-JAN-07:10 2298996.09 07-AUG-14:40
PlantLoopCoolingDemand:HVAC 24230.16 7740.17 11-JAN-07:10 2298996.09 07-AUG-14:40
CoolingCoils:PlantLoopCoolingDemand 24230.16 7740.17 11-JAN-07:10 2298996.09 07-AUG-14:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 13579.90 0.00 01-JAN-00:10 0.00 30-AUG-16:00
Water:HVAC 125.96 0.00 01-JAN-00:10 0.00 13-FEB-05:20
Humidifier:Water 125.96 0.00 01-JAN-00:10 0.00 13-FEB-05:20
General:Humidifier:Water 125.96 0.00 01-JAN-00:10 0.00 13-FEB-05:20
MainsWater:Facility 13579.90 0.00 01-JAN-00:10 0.00 30-AUG-16:00
MainsWater:HVAC 125.96 0.00 01-JAN-00:10 0.00 13-FEB-05:20
Humidifier:MainsWater 125.96 0.00 01-JAN-00:10 0.00 13-FEB-05:20
General:Humidifier:MainsWater 125.96 0.00 01-JAN-00:10 0.00 13-FEB-05:20
Water:Plant 13453.94 0.00 01-JAN-00:10 0.00 30-AUG-16:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 13453.94 0.00 01-JAN-00:10 0.00 30-AUG-16:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 11173.78 0.00 01-JAN-00:10 0.00 30-AUG-16:00
General:HeatRejection:Water 11173.78 0.00 01-JAN-00:10 0.00 30-AUG-16:00
HeatRejection:MainsWater 11173.78 0.00 01-JAN-00:10 0.00 30-AUG-16:00
General:HeatRejection:MainsWater 11173.78 0.00 01-JAN-00:10 0.00 30-AUG-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 93508.47 102164.61 10-JAN-05:40 9078055.15 06-OCT-14:10
EnergyTransfer:Building 20150.36 91472.38 10-JAN-05:40 1508089.36 30-AUG-16:00
EnergyTransfer:Zone:BASEMENT 645.27 0.00 01-JAN-00:10 73609.86 26-DEC-06:10
Heating:EnergyTransfer 38.69 0.00 01-JAN-00:10 260580.87 06-FEB-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.13 0.00 01-JAN-00:10 23297.97 22-JUL-16:10
General:Heating:EnergyTransfer 38.69 0.00 01-JAN-00:10 260580.87 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.13 0.00 01-JAN-00:10 23297.97 22-JUL-16:10
Cooling:EnergyTransfer 20111.67 90968.41 10-JAN-05:40 1508089.36 30-AUG-16:00
Cooling:EnergyTransfer:Zone:BASEMENT 641.14 0.00 01-JAN-00:10 73609.86 26-DEC-06:10
General:Cooling:EnergyTransfer 20111.67 90968.41 10-JAN-05:40 1508089.36 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 641.14 0.00 01-JAN-00:10 73609.86 26-DEC-06:10
EnergyTransfer:Zone:CORE_BOTTOM 667.13 0.00 01-JAN-00:10 51428.08 02-JAN-06:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 667.13 0.00 01-JAN-00:10 51428.08 02-JAN-06:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 667.13 0.00 01-JAN-00:10 51428.08 02-JAN-06:10
EnergyTransfer:Zone:CORE_MID 4875.37 0.00 01-JAN-00:10 412029.20 14-APR-05:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 4875.37 0.00 01-JAN-00:10 412029.20 14-APR-05:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 4875.37 0.00 01-JAN-00:10 412029.20 14-APR-05:10
EnergyTransfer:Zone:CORE_TOP 496.34 0.00 01-JAN-00:10 49653.73 03-MAY-12:40
Heating:EnergyTransfer:Zone:CORE_TOP 0.52 0.00 01-JAN-00:10 47188.79 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.52 0.00 01-JAN-00:10 47188.79 06-FEB-05:20
Cooling:EnergyTransfer:Zone:CORE_TOP 495.82 0.00 01-JAN-00:10 49653.73 03-MAY-12:40
General:Cooling:EnergyTransfer:Zone:CORE_TOP 495.82 0.00 01-JAN-00:10 49653.73 03-MAY-12:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 99.89 0.00 01-JAN-00:10 11244.43 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 99.89 0.00 01-JAN-00:10 11244.43 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 99.89 0.00 01-JAN-00:10 11244.43 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 78.07 0.00 01-JAN-00:10 11496.63 12-JUN-08:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 281.36 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 281.36 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 78.07 0.00 01-JAN-00:10 11496.63 12-JUN-08:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 78.07 0.00 01-JAN-00:10 11496.63 12-JUN-08:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 132.43 0.00 01-JAN-00:10 17250.63 06-NOV-13:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 46.31 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 46.31 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 132.43 0.00 01-JAN-00:10 17250.63 06-NOV-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 132.43 0.00 01-JAN-00:10 17250.63 06-NOV-13:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 118.40 0.00 01-JAN-00:10 16563.04 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 118.40 0.00 01-JAN-00:10 16563.04 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 118.40 0.00 01-JAN-00:10 16563.04 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 769.10 0.00 01-JAN-00:10 99383.41 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 5.58 0.00 01-JAN-00:10 66990.99 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 5.58 0.00 01-JAN-00:10 66990.99 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 763.51 0.00 01-JAN-00:10 99383.41 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 763.51 0.00 01-JAN-00:10 99383.41 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 666.51 0.00 01-JAN-00:10 120704.12 20-JUL-10:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.28 0.00 01-JAN-00:10 35915.53 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.28 0.00 01-JAN-00:10 35915.53 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 664.24 0.00 01-JAN-00:10 120704.12 20-JUL-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 664.24 0.00 01-JAN-00:10 120704.12 20-JUL-10:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1129.83 0.00 01-JAN-00:10 168068.16 06-NOV-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.21 0.00 01-JAN-00:10 39170.74 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.21 0.00 01-JAN-00:10 39170.74 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1128.61 0.00 01-JAN-00:10 168068.16 06-NOV-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1128.61 0.00 01-JAN-00:10 168068.16 06-NOV-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 730.57 0.00 01-JAN-00:10 136245.33 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.05 0.00 01-JAN-00:10 26778.08 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.05 0.00 01-JAN-00:10 26778.08 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 729.53 0.00 01-JAN-00:10 136245.33 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 729.53 0.00 01-JAN-00:10 136245.33 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 81.84 0.00 01-JAN-00:10 12962.10 06-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 3.28 0.00 01-JAN-00:10 12962.10 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 3.28 0.00 01-JAN-00:10 12962.10 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 78.56 0.00 01-JAN-00:10 10951.03 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 78.56 0.00 01-JAN-00:10 10951.03 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 72.54 0.00 01-JAN-00:10 12288.46 03-MAY-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.41 0.00 01-JAN-00:10 10082.83 06-FEB-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.41 0.00 01-JAN-00:10 10082.83 06-FEB-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 71.14 0.00 01-JAN-00:10 12288.46 03-MAY-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 71.14 0.00 01-JAN-00:10 12288.46 03-MAY-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 114.92 0.00 01-JAN-00:10 18114.15 06-NOV-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 1.35 0.00 01-JAN-00:10 13231.71 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 1.35 0.00 01-JAN-00:10 13231.71 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 113.57 0.00 01-JAN-00:10 18114.15 06-NOV-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 113.57 0.00 01-JAN-00:10 18114.15 06-NOV-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 75.71 0.00 01-JAN-00:10 14402.58 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.93 0.00 01-JAN-00:10 8000.75 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.93 0.00 01-JAN-00:10 8000.75 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 74.78 0.00 01-JAN-00:10 14402.58 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 74.78 0.00 01-JAN-00:10 14402.58 30-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 74.69 0.00 01-JAN-00:10 8655.57 23-OCT-09:30
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.74 0.00 01-JAN-00:10 2964.94 31-DEC-10:40
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.74 0.00 01-JAN-00:10 2964.94 31-DEC-10:40
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 73.95 0.00 01-JAN-00:10 8655.57 23-OCT-09:30
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 73.95 0.00 01-JAN-00:10 8655.57 23-OCT-09:30
EnergyTransfer:Zone:MIDFLOOR_PLENUM 523.70 0.00 01-JAN-00:10 69985.07 03-MAY-12:30
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 10.32 0.00 01-JAN-00:10 25075.15 24-DEC-11:30
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 10.32 0.00 01-JAN-00:10 25075.15 24-DEC-11:30
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 513.37 0.00 01-JAN-00:10 69985.07 03-MAY-12:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 513.37 0.00 01-JAN-00:10 69985.07 03-MAY-12:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 93.30 0.00 01-JAN-00:10 21132.46 08-MAY-13:40
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.72 0.00 01-JAN-00:10 15918.58 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.72 0.00 01-JAN-00:10 15918.58 06-FEB-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 87.58 0.00 01-JAN-00:10 21132.46 08-MAY-13:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 87.58 0.00 01-JAN-00:10 21132.46 08-MAY-13:40
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.58 952.60 10-JAN-08:00 7989.48 16-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.58 952.60 10-JAN-08:00 7989.48 16-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.58 952.60 10-JAN-08:00 7989.48 16-APR-18:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1280.42 1448.14 10-JAN-06:20 74843.34 16-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1280.42 1448.14 10-JAN-06:20 74843.34 16-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1280.42 1448.14 10-JAN-06:20 74843.34 16-APR-18:20
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 125.03 3.43 09-JAN-21:50 7684.29 23-APR-18:00
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.18 0.00 01-JAN-00:10 524.49 10-JAN-04:20
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.18 0.00 01-JAN-00:10 524.49 10-JAN-04:20
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 124.85 0.00 04-JAN-02:50 7684.29 23-APR-18:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 124.85 0.00 04-JAN-02:50 7684.29 23-APR-18:00
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.74 87805.49 22-JAN-06:00 369239.30 03-AUG-21:10
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.74 87805.49 22-JAN-06:00 369239.30 03-AUG-21:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.74 87805.49 22-JAN-06:00 369239.30 03-AUG-21:10
PlantLoopHeatingDemand:Facility 383.04 0.00 01-JAN-00:10 384146.15 06-FEB-06:10
PlantLoopHeatingDemand:Plant 321.87 0.00 01-JAN-00:10 40642.48 24-JAN-12:10
WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40642.48 24-JAN-12:10
General:WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40642.48 24-JAN-12:10
EnergyTransfer:HVAC 24900.50 10160.14 11-JAN-05:50 2612479.20 07-AUG-13:00
HeatingCoils:EnergyTransfer 61.18 0.00 01-JAN-00:10 379229.26 06-FEB-06:10
PlantLoopHeatingDemand:HVAC 61.18 0.00 01-JAN-00:10 379229.26 06-FEB-06:10
HeatingCoils:PlantLoopHeatingDemand 61.18 0.00 01-JAN-00:10 379229.26 06-FEB-06:10
CoolingCoils:EnergyTransfer 22131.66 5414.70 11-JAN-07:10 2164922.47 07-AUG-14:40
HeatRecoveryForHeating:EnergyTransfer 18.50 0.00 01-JAN-00:10 180581.29 20-DEC-08:00
HeatRecoveryForCooling:EnergyTransfer 2689.18 0.00 01-JAN-00:10 689518.00 22-JUL-16:00
EnergyTransfer:Plant 48457.60 0.00 01-JAN-00:10 5467494.07 26-MAY-15:00
LoopToLoop:EnergyTransfer 15296.08 0.00 01-JAN-00:10 1676769.28 06-OCT-14:10
WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40642.48 24-JAN-12:10
WaterUse:WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40642.48 24-JAN-12:10
Boilers:EnergyTransfer 60.36 0.00 01-JAN-00:10 405708.31 06-FEB-05:20
Chillers:EnergyTransfer 15293.77 0.00 01-JAN-00:10 1784506.26 10-MAY-16:00
HeatRejection:EnergyTransfer 17485.52 0.00 01-JAN-00:10 2031682.67 10-MAY-16:00
General:HeatRejection:EnergyTransfer 17485.52 0.00 01-JAN-00:10 2031682.67 10-MAY-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.130 -641.143 0.000 0.000 92.699 116.039 424.397 0.000 0.000 0.000 3.878 0.000 0.000 0.000 0.000 -0.011
CORE_BOTTOM 0.000 0.000 0.000 -667.126 0.000 0.000 83.505 104.212 289.614 0.000 0.000 0.000 189.795 0.000 0.000 0.000 0.000 -0.002
CORE_MID 0.000 0.000 0.000 -4875.360 0.000 0.000 842.106 1042.115 2896.128 0.000 0.000 0.000 95.011 0.000 0.000 0.000 0.000 -0.016
CORE_TOP 0.000 0.000 0.517 -495.822 0.000 0.000 85.618 104.212 289.613 0.000 0.000 0.000 15.863 0.000 0.000 0.000 0.000 -0.006
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -99.890 0.000 0.000 10.576 7.461 36.365 41.236 0.000 0.401 35.619 0.000 -29.993 0.000 -1.776 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -78.068 0.000 0.000 6.784 4.786 23.435 60.025 0.000 0.260 2.318 0.000 -18.346 0.000 -1.194 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -132.424 0.000 0.000 10.507 7.381 36.366 103.629 0.000 0.381 4.473 0.000 -28.422 0.000 -1.890 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -118.395 0.000 0.000 6.744 4.783 23.435 57.179 0.000 0.217 51.059 0.000 -23.557 0.000 -1.465 -0.000
PERIMETER_MID_ZN_3 0.000 0.000 5.582 -763.492 0.000 0.000 108.395 74.476 363.654 424.949 0.000 8.953 78.021 0.000 -264.507 0.000 -36.032 0.000
PERIMETER_MID_ZN_2 0.000 0.000 2.277 -664.219 0.000 0.000 50.185 47.799 234.352 595.966 0.000 5.201 0.003 0.000 -174.446 0.000 -26.525 -70.588
PERIMETER_MID_ZN_1 0.000 0.000 1.214 -1128.588 0.000 0.000 105.623 73.744 363.660 1033.887 0.000 8.218 0.043 0.000 -273.636 0.000 -42.956 -141.167
PERIMETER_MID_ZN_4 0.000 0.000 1.048 -729.507 0.000 0.000 68.732 47.760 234.351 585.488 0.000 5.154 10.621 0.000 -195.370 0.000 -28.277 -0.001
PERIMETER_TOP_ZN_3 0.000 0.000 3.282 -78.556 0.000 0.000 10.945 7.447 36.365 42.304 0.000 1.032 6.416 0.000 -25.072 0.000 -4.165 0.000
PERIMETER_TOP_ZN_2 0.000 0.000 1.405 -71.135 0.000 0.000 6.904 4.780 23.435 59.736 0.000 0.623 0.000 0.000 -16.571 0.000 -3.061 -6.116
PERIMETER_TOP_ZN_1 0.000 0.000 1.348 -113.565 0.000 0.000 10.642 7.374 36.366 103.109 0.000 0.955 0.001 0.000 -26.231 0.000 -5.042 -14.956
PERIMETER_TOP_ZN_4 0.000 0.000 0.928 -74.776 0.000 0.000 6.932 4.776 23.435 58.322 0.000 0.612 1.837 0.000 -18.736 0.000 -3.330 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -140.577 0.000 0.000 0.949 1.676 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -15.928
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1280.423 0.000 0.000 9.489 16.758 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -284.630
DATACENTER_TOP_ZN_6 0.000 0.000 0.178 -124.850 0.000 0.000 0.950 1.676 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -31.834
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7158.757 0.000 0.000 20.112 32.854 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -389.067
GROUNDFLOOR_PLENUM 0.736 -73.953 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.690 76.514 0.000 0.000 0.000 -3.987 0.000
MIDFLOOR_PLENUM 10.325 -513.365 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 12.862 556.190 0.000 0.000 0.000 -66.011 0.000
TOPFLOOR_PLENUM 5.722 -87.576 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.087 87.568 0.000 0.000 0.000 -6.801 -0.001
Total Facility 16.783 -674.894 21.911 -19436.674 0.000 0.000 1538.395 1712.108 14676.396 3165.829 0.000 46.646 1215.231 0.000 -1094.887 0.000 -232.511 -954.323


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 20-MAR-04:12 0.00 0.00 0.00 -102199.42 0.00 0.00 0.00 598.35 13457.54 0.00 0.00 0.00 88143.53 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 02-OCT-04:13 0.00 0.00 0.00 -87349.75 0.00 0.00 0.00 537.36 5937.65 0.00 0.00 0.00 80874.74 0.00 -0.00 0.00 0.00 0.00
CORE_MID 08-NOV-05:11 0.00 0.00 0.00 -728985.65 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 664235.82 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 31-MAY-04:13 0.00 0.00 0.00 -73315.61 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 66840.62 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 02-JUL-15:32 0.00 0.00 0.00 -15188.97 0.00 0.00 42.97 30.32 720.18 5853.27 0.00 66.76 8475.46 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24-SEP-09:32 0.00 0.00 0.00 -18969.61 0.00 0.00 22.55 19.54 464.11 12670.05 0.00 10.71 5782.64 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 01-JAN-13:31 0.00 0.00 0.00 -22904.73 0.00 0.00 30.83 30.33 720.19 21889.98 0.00 0.00 284.69 0.00 -0.00 0.00 -51.30 0.00
PERIMETER_BOT_ZN_4 10-DEC-15:01 0.00 0.00 0.00 -24521.08 0.00 0.00 21.16 19.54 464.11 10422.50 0.00 0.00 13601.32 0.00 -0.00 0.00 -7.55 0.00
PERIMETER_MID_ZN_3 10-SEP-14:31 0.00 0.00 0.00 -144445.80 0.00 0.00 427.14 303.25 7201.84 53352.37 0.00 2803.29 80357.91 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 03-SEP-08:52 0.00 0.00 0.00 -201114.70 0.00 0.00 219.57 195.42 4641.14 141072.08 0.00 283.64 54702.85 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 10-DEC-13:51 0.00 0.00 0.00 -222756.27 0.00 0.00 305.86 303.26 7201.95 208928.25 0.00 0.00 7183.54 0.00 -0.00 0.00 -1166.58 0.00
PERIMETER_MID_ZN_4 11-JUN-17:21 0.00 0.00 0.00 -218973.48 0.00 0.00 0.00 195.42 3603.49 111482.61 0.00 1012.65 102679.31 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 10-SEP-14:31 0.00 0.00 0.00 -17237.41 0.00 0.00 39.87 30.32 720.18 5131.84 0.00 322.22 10992.97 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 29-MAY-10:01 0.00 0.00 0.00 -21184.17 0.00 0.00 20.13 19.54 464.11 10496.08 0.00 0.00 10185.55 0.00 -0.00 0.00 -1.24 0.00
PERIMETER_TOP_ZN_1 01-JAN-14:01 0.00 0.00 0.00 -24851.36 0.00 0.00 29.48 30.33 720.19 20614.96 0.00 0.00 3593.21 0.00 -0.00 0.00 -136.81 0.00
PERIMETER_TOP_ZN_4 03-SEP-15:31 0.00 0.00 0.00 -23912.68 0.00 0.00 18.83 19.54 464.11 13891.72 0.00 162.22 9356.25 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 16-APR-18:12 0.00 0.00 0.00 -7989.44 0.00 0.00 0.00 8.13 7794.42 0.00 0.00 0.00 186.89 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 16-APR-18:12 0.00 0.00 0.00 -74842.96 0.00 0.00 0.00 81.29 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3182.55
DATACENTER_TOP_ZN_6 23-APR-17:52 0.00 0.00 0.00 -7684.29 0.00 0.00 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -118.26
DATACENTER_BASEMENT_ZN_6 09-AUG-21:14 0.00 0.00 0.00 -370265.48 0.00 0.00 114.52 318.73 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -9800.30
GROUNDFLOOR_PLENUM 02-JAN-06:03 0.00 -11431.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11477.49 0.00 -0.00 0.00 -46.28 0.00
MIDFLOOR_PLENUM 25-SEP-05:02 0.00 -81663.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82207.48 0.00 -0.00 0.00 -543.60 0.00
TOPFLOOR_PLENUM 08-MAY-13:40 0.00 -21131.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 217.13 20914.79 0.00 -0.00 0.00 0.00 0.00
Total Facility 31-AUG-05:02 0.00 -61664.79 0.00 -1714285.07 0.00 0.00 16325.63 10223.35 616289.16 0.00 0.00 0.05 1170875.52 0.00 -37753.60 0.00 -10.24 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-JUL-16:01 0.00 0.00 24888.72 0.00 0.00 0.00 520.12 565.21 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -39431.60
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 06-FEB-05:11 0.00 0.00 56949.36 0.00 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -63424.35
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 21-DEC-06:01 0.00 0.00 1969.51 0.00 0.00 0.00 90.46 43.48 618.82 0.00 0.00 0.00 975.87 0.00 -3629.95 0.00 -68.19 0.00
PERIMETER_BOT_ZN_1 06-FEB-06:04 0.00 0.00 231.56 0.00 0.00 0.00 138.94 67.47 960.26 0.00 0.00 0.00 3273.65 0.00 -4618.86 0.00 -53.03 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 06-FEB-05:11 0.00 0.00 110630.55 0.00 0.00 0.00 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 -40279.84 0.00 -4435.35 -74045.68
PERIMETER_MID_ZN_2 06-FEB-05:11 0.00 0.00 96424.40 0.00 0.00 0.00 0.00 434.81 4804.68 0.00 0.00 0.00 0.00 0.00 -27782.50 0.00 -3077.67 -70803.72
PERIMETER_MID_ZN_1 21-JAN-06:02 0.00 0.00 116740.83 0.00 0.00 0.00 1462.99 1274.72 9602.60 0.00 0.00 0.00 0.00 0.00 -52476.56 0.00 -3493.07 -73111.51
PERIMETER_MID_ZN_4 10-JAN-05:01 0.00 0.00 82828.85 0.00 0.00 0.00 0.00 821.46 4804.65 0.00 0.00 0.00 0.00 0.00 -33185.16 0.00 -5899.93 -49369.86
PERIMETER_TOP_ZN_3 05-FEB-07:43 0.00 0.00 14465.58 0.00 0.00 0.00 88.55 51.84 720.18 0.00 0.00 0.00 0.00 0.00 -4495.42 0.00 -2205.70 -8625.04
PERIMETER_TOP_ZN_2 06-FEB-05:11 0.00 0.00 13397.98 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -2215.84 0.00 -317.81 -11388.27
PERIMETER_TOP_ZN_1 06-FEB-05:11 0.00 0.00 17126.94 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -3437.61 0.00 -482.37 -14020.01
PERIMETER_TOP_ZN_4 06-FEB-05:11 0.00 0.00 13091.30 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -2406.89 0.00 -333.16 -10875.20
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 05-JAN-04:45 0.00 0.00 527.04 0.00 0.00 0.00 0.00 8.13 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2483.77
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-05:12 9386.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -784.26 -8602.45
MIDFLOOR_PLENUM 10-SEP-15:51 79571.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4871.15 0.00 0.00 -0.00 0.00 0.00 -84442.96
TOPFLOOR_PLENUM 06-FEB-06:13 17815.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -185.17 -17630.62
Total Facility 06-FEB-06:02 -565912.05 550866.40 476315.66 -550866.40 0.00 0.00 19725.81 10223.35 379706.36 0.00 0.00 0.00 0.00 0.00 -174634.14 0.00 -7044.46 -138380.53



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 9.5659 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.4593 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 89.9514 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 78.1657 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 9.2824 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.6917 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.0116 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.0116 0.2395 1.0000 Not calculated 1.2002 0.2395    
AIRLOOP DATACENTER BASEMENT 21.2609 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.2611 0.0159 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4610 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4610 0.0339 1.0000 Not calculated 0.0156 0.0339    
AIRLOOP DATACENTER MID 4.3952 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.3952 0.0356 1.0000 Not calculated 0.1563 0.0356    
AIRLOOP DATACENTER TOP 0.4483 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4483 0.0349 1.0000 Not calculated 0.0156 0.0349    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 4.7829 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2848 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 44.9757 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.8476 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 4.6412 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2829 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.0116 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.0116 1.0000 1.0000 Not calculated 1.2002 0.2395    
AIRLOOP DATACENTER BASEMENT 21.2609 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.2609 1.0000 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4610 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4610 1.0000 1.0000 Not calculated 0.0156 0.0339    
AIRLOOP DATACENTER MID 4.3952 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.3952 1.0000 1.0000 Not calculated 0.1563 0.0356    
AIRLOOP DATACENTER TOP 0.4483 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4483 1.0000 1.0000 Not calculated 0.0156 0.0349    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.0116 5.0116 5.0116 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2489 5.2489 1.6167 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 48.9813 48.9813 16.1638 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8486 4.8486 1.6146 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8937 0.8937 0.2029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0129 1.0129 0.1307 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1233 1.1233 0.2033 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2869 1.2869 0.1313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.4011 8.4011 2.0331 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.5650 10.5650 1.3101 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.7912 10.7912 2.0287 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.2128 11.2128 1.3119 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9629 0.9629 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0733 1.0733 0.1309 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1942 1.1942 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2033 1.2033 0.1312 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4610 0.4610 0.4610 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.3952 4.3952 4.3952 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4483 0.4483 0.4483 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.2609 21.2609 21.2609 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 9.5659 8.4593 9.5659 2.2848 0.0000 1.0000
VAV_MID WITH REHEAT 89.9514 78.1657 89.9514 22.8476 0.0000 1.0000
VAV_TOP WITH REHEAT 9.2824 8.6917 9.2824 2.2829 0.0000 1.0000
CAV_BAS 5.0116 5.0116 5.0116 5.0116 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.2609 21.2611 21.2609 21.2609 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4610 0.4610 0.4610 0.4610 0.0156 1.0000
AIRLOOP DATACENTER MID 4.3952 4.3952 4.3952 4.3952 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4483 0.4483 0.4483 0.4483 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.0116 5.0116 5.0116 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6245 2.6245 1.6167 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 24.4906 24.4906 16.1638 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4243 2.4243 1.6146 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4469 0.4469 0.2029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5065 0.5065 0.1307 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5617 0.5617 0.2033 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6435 0.6435 0.1313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.2005 4.2005 2.0331 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2825 5.2825 1.3101 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3956 5.3956 2.0287 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.6064 5.6064 1.3119 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4815 0.4815 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5367 0.5367 0.1309 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5971 0.5971 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6016 0.6016 0.1312 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4610 0.4610 0.4610 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.3952 4.3952 4.3952 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4483 0.4483 0.4483 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.2609 21.2609 21.2609 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 4.7829 2.2848 2.2848 2.2848 0.0000 1.0000
VAV_MID WITH REHEAT 44.9757 22.8476 22.8476 22.8476 0.0000 1.0000
VAV_TOP WITH REHEAT 4.6412 2.2829 2.2829 2.2829 0.0000 1.0000
CAV_BAS 5.0116 5.0116 5.0116 5.0116 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.2609 21.2609 21.2609 21.2609 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4610 0.4610 0.4610 0.4610 0.0156 1.0000
AIRLOOP DATACENTER MID 4.3952 4.3952 4.3952 4.3952 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4483 0.4483 0.4483 0.4483 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1.83
Number of hours cooling loads not met 800.83
Number of hours not met 802.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 67.00 463207.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 4290.25 395912.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 1712.11 164275.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 264.34 31088.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.35 3369.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1144.44 70012.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 4.90 315.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2028.07 255581.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 645.91 57493.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1551.85 81663.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 338.60 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 50.61 4520.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 644.88 74963.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 26761.82
Natural Gas 0.00 711.88
Additional 0.00 0.00
Total 14676.40 27473.70


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 566.52
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 36.96
Space Heating 0.00
Space Cooling 92.62
Fans (All) 43.78
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 577.75
Subtotal 577.75


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.45
Service Water Heating 13.92
Miscellaneous (All) 15.37
Subtotal 15.37


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.23
Space Heating 0.24
Space Cooling 15.62
Fans (All) 7.38
Service Water Heating 2.35
Receptacle Equipment 53.42
Miscellaneous 14.76


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
PV_SCH 8760. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2069. 8760.
LTG_SCH_DATACENTER 1840. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 970. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7575.00 1185.00 0.00 0.00 0.00
CORE_BOTTOM 8737.67 22.33 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8729.00 31.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8601.17 158.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8583.17 176.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7375.83 1384.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8698.50 61.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8443.00 317.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8463.83 296.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7977.50 782.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8595.33 164.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8334.50 425.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8368.83 391.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7904.33 855.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 3575.17 5184.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 3647.17 5112.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 3600.17 5159.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 2183.83 6576.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8496.33 263.67 0.00 0.00 0.00
Min 2183.83 0.00 0.00 0.00 0.00
Max 8760.00 6576.17 0.00 0.00 0.00
Average 7518.71 1241.29 0.00 0.00 0.00
Sum 172930.33 28549.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 365089.17 3526.83 0.00 0.00 0.00
CORE_BOTTOM 330771.00 42.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 544.00 1724.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 539.50 1728.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 531.00 1737.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 25094.50 78300.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 365089.17 78300.50 0.00 0.00 0.00
Average 76549.75 3785.17 0.00 0.00 0.00
Sum 1760644.17 87058.83 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 3721.17 5038.83 0.00 0.00 0.00
CORE_BOTTOM 8515.50 244.50 0.00 0.00 0.00
CORE_MID 8755.50 4.50 0.00 0.00 0.00
CORE_TOP 8742.67 17.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8010.50 749.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 7927.50 832.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7811.00 949.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 6339.33 2420.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 6962.33 1797.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 6780.83 1979.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 6709.33 2050.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 6559.00 2201.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 6857.17 1902.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 6719.00 2041.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 6639.83 2120.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 6532.50 2227.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 5782.83 2977.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 5767.17 2992.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 5735.83 3024.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 4404.33 4355.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8493.33 266.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 7832.17 927.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 7350.67 1409.33 0.00 0.00 0.00
Min 3721.17 4.50 0.00 0.00 0.00
Max 8755.50 5038.83 0.00 0.00 0.00
Average 6910.85 1849.15 0.00 0.00 0.00
Sum 158949.50 42530.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 244406.00 124210.00 0.00 0.00 0.00
CORE_BOTTOM 330484.00 329.00 0.00 0.00 0.00
CORE_MID 330786.00 27.00 0.00 0.00 0.00
CORE_TOP 330744.00 69.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38924.67 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24908.67 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38924.67 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38901.83 23.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18332.00 22.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38903.67 21.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24892.83 16.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38894.33 30.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24879.83 29.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38896.50 28.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24884.83 24.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 744.50 1523.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 732.67 1535.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 719.33 1548.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 30859.17 72535.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 330786.00 124210.00 0.00 0.00 0.00
Average 71553.41 8781.50 0.00 0.00 0.00
Sum 1645728.50 201974.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:55

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.510023E+11 100389.24 09-JAN-05:11 7.67 5.62 0.566603E+10 7499.38 12-JAN-10:09 18.17 17.41
February 0.445611E+11 101761.78 13-FEB-05:11 5.53 1.73 0.513857E+10 7499.16 09-FEB-14:20 5.53 1.73
March 0.514577E+11 102273.27 20-MAR-04:12 12.27 8.01 0.613158E+10 7499.55 23-MAR-09:20 16.97 14.65
April 0.475629E+11 101596.78 17-APR-04:11 12.83 10.47 0.544749E+10 7499.32 13-APR-09:20 12.83 10.47
May 0.513999E+11 74422.79 29-MAY-18:50 28.48 23.49 0.590069E+10 7502.27 08-MAY-09:20 28.48 23.49
June 0.513594E+11 76867.29 12-JUN-03:02 23.90 21.55 0.587992E+10 7498.98 23-JUN-09:20 29.80 25.86
July 0.534806E+11 73797.60 25-JUL-03:02 25.10 23.49 0.547173E+10 7498.97 14-JUL-09:20 25.10 23.49
August 0.627445E+11 78181.38 28-AUG-03:02 26.27 23.76 0.613838E+10 7543.13 07-AUG-09:09 26.27 23.76
September 0.559182E+11 76867.75 05-SEP-04:23 22.75 22.75 0.545323E+10 7508.81 05-SEP-09:30 27.15 25.12
October 0.590223E+11 97383.83 17-OCT-04:12 17.33 12.72 0.567205E+10 7691.40 23-OCT-09:39 25.67 23.79
November 0.572719E+11 98018.34 14-NOV-05:12 15.50 12.19 0.561605E+10 7545.06 06-NOV-10:00 15.50 12.19
December 0.553592E+11 100547.99 26-DEC-05:12 6.97 3.20 0.547244E+10 7499.61 08-DEC-10:00 6.97 3.20
                     
Annual Sum or Average 0.641140E+12         0.679881E+11        
Minimum of Months 0.445611E+11 73797.60   5.53 1.73 0.513857E+10 7498.97   5.53 1.73
Maximum of Months 0.627445E+11 102273.27   28.48 23.76 0.613838E+10 7691.40   29.80 25.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.430957E+11 84197.76 02-JAN-05:14 16.67 15.63 0.505357E+10 6734.83 11-JAN-10:09 14.67 12.06
February 0.414654E+11 86975.84 27-FEB-05:13 17.77 17.77 0.459398E+10 6734.72 07-FEB-10:20 17.77 17.77
March 0.523219E+11 82946.94 30-MAR-04:13 20.83 19.79 0.549235E+10 6734.96 23-MAR-09:09 20.83 19.79
April 0.584344E+11 82662.20 04-APR-04:13 16.67 14.88 0.487526E+10 6734.84 10-APR-13:00 20.50 10.92
May 0.547623E+11 81174.35 16-MAY-04:13 23.30 22.20 0.528101E+10 6734.91 02-MAY-13:09 23.30 22.20
June 0.600887E+11 84051.95 01-JUN-04:13 21.50 20.44 0.526226E+10 6734.69 02-JUN-09:39 29.03 24.19
July 0.654121E+11 73687.97 24-JUL-05:03 27.02 24.85 0.488697E+10 6734.61 24-JUL-09:20 30.37 25.95
August 0.726654E+11 75624.07 07-AUG-05:03 24.17 23.42 0.548943E+10 6734.83 15-AUG-09:20 26.10 22.41
September 0.539228E+11 83872.84 22-SEP-04:13 21.70 20.03 0.487610E+10 6734.69 22-SEP-13:00 30.00 22.00
October 0.583462E+11 87354.71 02-OCT-04:13 18.03 15.02 0.507251E+10 6780.52 23-OCT-09:39 25.67 23.79
November 0.532584E+11 86186.58 13-NOV-05:11 9.93 8.14 0.502534E+10 6734.78 13-NOV-10:20 16.83 13.24
December 0.533520E+11 85415.91 26-DEC-05:12 6.97 3.20 0.489480E+10 6734.80 14-DEC-14:50 6.97 3.20
                     
Annual Sum or Average 0.667125E+12         0.608036E+11        
Minimum of Months 0.414654E+11 73687.97   6.97 3.20 0.459398E+10 6734.61   6.97 3.20
Maximum of Months 0.726654E+11 87354.71   27.02 24.85 0.549235E+10 6780.52   30.37 25.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.324436E+11 71078.18 02-JAN-05:12 16.67 15.63 0.488542E+10 6734.80 05-JAN-14:20 14.33 9.84
February 0.302851E+11 72117.45 27-FEB-06:04 17.70 17.70 0.447224E+10 6734.67 14-FEB-14:20 17.70 17.70
March 0.370245E+11 71138.87 29-MAR-05:02 17.10 16.79 0.539349E+10 6734.85 23-MAR-09:39 17.10 16.79
April 0.385160E+11 71652.15 14-APR-05:04 18.80 18.80 0.484400E+10 6734.77 03-APR-09:20 18.80 18.80
May 0.467854E+11 70176.17 17-MAY-04:12 22.20 20.38 0.526185E+10 6734.99 02-MAY-13:09 22.20 20.38
June 0.469736E+11 72613.14 07-JUN-04:12 21.10 18.59 0.524500E+10 6734.64 13-JUN-13:20 33.17 21.40
July 0.472117E+11 69603.24 12-JUL-04:12 23.50 23.01 0.486818E+10 6734.63 12-JUL-13:20 25.03 23.05
August 0.487305E+11 71846.21 17-AUG-04:12 21.93 21.62 0.547414E+10 6734.71 15-AUG-09:20 21.93 21.62
September 0.444175E+11 71237.92 28-SEP-04:12 22.20 20.76 0.485210E+10 6734.70 22-SEP-13:00 22.20 20.76
October 0.440336E+11 72628.96 17-OCT-04:12 17.33 12.72 0.504822E+10 6734.96 23-OCT-09:39 25.67 23.79
November 0.371631E+11 72900.24 08-NOV-05:11 19.80 19.09 0.497486E+10 6735.06 27-NOV-14:09 25.82 17.52
December 0.339522E+11 71060.55 14-DEC-05:12 20.00 20.00 0.477839E+10 6734.75 15-DEC-14:09 29.00 22.01
                     
Annual Sum or Average 0.487537E+12         0.600979E+11        
Minimum of Months 0.302851E+11 69603.24   16.67 12.72 0.447224E+10 6734.63   14.33 9.84
Maximum of Months 0.487305E+11 72900.24   23.50 23.01 0.547414E+10 6735.06   33.17 23.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.278935E+11 68060.47 02-JAN-06:03 16.00 15.39 0.447474E+10 6734.62 20-JAN-10:20 14.67 14.08
February 0.278380E+11 67175.00 03-FEB-06:02 18.90 18.50 0.422506E+10 6734.63 03-FEB-10:20 14.80 13.72
March 0.343515E+11 70037.88 27-MAR-04:12 19.97 18.72 0.516035E+10 6734.62 29-MAR-09:20 21.63 19.76
April 0.386155E+11 71987.21 26-APR-05:04 21.00 20.56 0.480483E+10 6734.69 27-APR-13:00 28.80 22.60
May 0.514586E+11 73320.11 31-MAY-04:13 23.17 21.09 0.527195E+10 6831.36 08-MAY-13:50 23.17 21.09
June 0.527005E+11 71597.80 07-JUN-04:12 21.10 18.59 0.525765E+10 6734.66 06-JUN-13:50 21.10 18.59
July 0.528277E+11 70927.33 12-JUL-04:12 23.50 23.01 0.488287E+10 6734.61 13-JUL-09:20 24.63 23.37
August 0.538400E+11 70329.09 26-AUG-04:02 23.85 23.13 0.548458E+10 6734.67 15-AUG-09:20 23.85 23.13
September 0.472555E+11 72365.21 28-SEP-05:04 22.28 21.10 0.485769E+10 6734.68 22-SEP-13:00 22.28 21.10
October 0.455150E+11 71072.37 02-OCT-04:11 18.03 15.02 0.502867E+10 6734.96 23-OCT-09:39 25.67 23.79
November 0.338955E+11 69603.10 03-NOV-04:12 22.50 22.14 0.481229E+10 6734.70 06-NOV-10:20 24.37 20.12
December 0.296327E+11 67472.98 15-DEC-06:03 21.00 21.00 0.442967E+10 6734.73 15-DEC-14:09 29.00 22.01
                     
Annual Sum or Average 0.495824E+12         0.586903E+11        
Minimum of Months 0.278380E+11 67175.00   16.00 15.02 0.422506E+10 6734.61   14.67 13.72
Maximum of Months 0.538400E+11 73320.11   23.85 23.13 0.548458E+10 6831.36   29.00 23.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.438395E+10 8168.35 02-JAN-06:03 16.00 15.39 0.595705E+09 845.61 27-JAN-14:20 19.33 12.72
February 0.456822E+10 7277.06 27-FEB-05:11 17.77 17.77 0.558250E+09 845.62 28-FEB-14:09 25.00 20.38
March 0.611022E+10 8959.58 27-MAR-05:03 19.82 18.59 0.675363E+09 845.62 24-MAR-09:20 19.82 18.59
April 0.827059E+10 8901.00 26-APR-14:30 28.00 22.41 0.610406E+09 845.65 27-APR-13:00 28.80 22.60
May 0.101105E+11 13839.86 07-MAY-14:42 32.98 23.21 0.664592E+09 857.39 08-MAY-13:50 32.70 22.56
June 0.115666E+11 11852.75 01-JUN-04:12 21.50 20.44 0.662247E+09 845.63 02-JUN-09:39 29.03 24.19
July 0.121249E+11 15188.76 02-JUL-15:32 29.07 24.97 0.615716E+09 845.61 14-JUL-13:20 26.67 25.30
August 0.128887E+11 13978.52 13-AUG-16:22 30.50 26.21 0.690551E+09 845.64 15-AUG-09:20 26.10 22.41
September 0.905055E+10 11970.26 06-SEP-03:02 24.70 23.43 0.613512E+09 845.63 28-SEP-13:39 28.80 23.39
October 0.897254E+10 14901.05 08-OCT-13:01 32.17 26.14 0.636301E+09 852.30 23-OCT-09:39 25.67 23.79
November 0.626031E+10 10947.35 02-NOV-05:02 23.38 22.55 0.624880E+09 845.63 13-NOV-10:20 16.83 13.24
December 0.558392E+10 7328.47 11-DEC-13:30 26.00 22.83 0.595664E+09 845.64 14-DEC-14:50 27.83 23.02
                     
Annual Sum or Average 0.998910E+11         0.754319E+10        
Minimum of Months 0.438395E+10 7277.06   16.00 15.39 0.558250E+09 845.61   16.83 12.72
Maximum of Months 0.128887E+11 15188.76   32.98 26.21 0.690551E+09 857.39   32.70 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.352042E+10 16181.85 01-JAN-10:52 22.00 17.44 0.400380E+09 544.96 11-JAN-10:09 14.67 12.06
February 0.378282E+10 11893.63 26-FEB-11:13 25.37 20.01 0.367075E+09 544.96 09-FEB-10:00 25.37 20.01
March 0.526355E+10 17576.05 26-MAR-09:32 24.77 20.03 0.438103E+09 544.97 23-MAR-09:09 24.77 20.03
April 0.673098E+10 17524.62 23-APR-07:53 22.20 19.24 0.393544E+09 544.97 03-APR-09:09 22.20 19.24
May 0.844666E+10 18963.41 14-MAY-08:42 27.93 23.47 0.428722E+09 545.00 02-MAY-13:09 27.93 23.47
June 0.898236E+10 17436.51 04-JUN-09:22 28.90 24.82 0.426979E+09 544.97 02-JUN-09:39 28.90 24.82
July 0.909243E+10 17601.14 09-JUL-09:02 30.68 26.13 0.397035E+09 544.94 14-JUL-13:20 26.67 25.30
August 0.920673E+10 16092.80 06-AUG-09:42 29.83 26.91 0.445001E+09 544.97 15-AUG-09:20 26.10 22.41
September 0.706659E+10 18968.24 24-SEP-09:32 29.03 25.00 0.395804E+09 544.96 21-SEP-13:50 29.03 25.00
October 0.710177E+10 17718.60 15-OCT-08:43 23.00 19.57 0.410613E+09 550.32 23-OCT-09:39 25.67 23.79
November 0.491142E+10 17395.89 11-NOV-09:23 24.40 21.68 0.404558E+09 544.98 06-NOV-10:00 24.40 21.68
December 0.396353E+10 14330.37 10-DEC-10:22 25.00 20.24 0.385431E+09 544.96 14-DEC-14:50 27.83 23.02
                     
Annual Sum or Average 0.780693E+11         0.489324E+10        
Minimum of Months 0.352042E+10 11893.63   22.00 17.44 0.367075E+09 544.94   14.67 12.06
Maximum of Months 0.920673E+10 18968.24   30.68 26.91 0.445001E+09 550.32   29.03 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.918409E+10 22906.72 01-JAN-13:31 25.67 18.12 0.625544E+09 892.85 19-JAN-14:09 25.00 21.54
February 0.877568E+10 21347.51 26-FEB-13:52 26.60 19.72 0.571256E+09 899.94 27-FEB-14:09 25.60 20.00
March 0.883988E+10 20079.33 05-MAR-13:23 27.70 18.32 0.677026E+09 845.68 23-MAR-09:09 16.78 14.63
April 0.977160E+10 14629.76 23-APR-12:33 27.20 20.85 0.610476E+09 845.69 27-APR-13:00 28.80 22.60
May 0.103271E+11 18741.38 07-MAY-14:42 32.98 23.21 0.664609E+09 850.01 08-MAY-13:50 32.70 22.56
June 0.111878E+11 13924.72 26-JUN-05:02 25.00 23.50 0.662127E+09 845.65 02-JUN-09:39 25.00 23.50
July 0.120374E+11 18904.83 02-JUL-15:32 29.07 24.97 0.615701E+09 845.63 14-JUL-13:20 26.67 25.30
August 0.140327E+11 19040.09 27-AUG-12:23 32.00 23.77 0.690791E+09 845.65 15-AUG-09:20 32.00 23.77
September 0.112016E+11 20106.27 03-SEP-13:02 31.28 23.99 0.614252E+09 845.66 21-SEP-13:50 26.78 22.76
October 0.139340E+11 21499.87 15-OCT-13:22 29.50 22.51 0.639542E+09 886.69 03-OCT-13:50 29.50 22.51
November 0.119777E+11 22188.74 11-NOV-13:21 26.35 22.79 0.633139E+09 922.46 06-NOV-14:09 26.35 22.79
December 0.111555E+11 22407.76 10-DEC-12:21 27.00 20.56 0.608348E+09 916.69 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.132425E+12         0.761281E+10        
Minimum of Months 0.877568E+10 13924.72   25.00 18.12 0.571256E+09 845.63   16.78 14.63
Maximum of Months 0.140327E+11 22906.72   32.98 24.97 0.690791E+09 922.46   32.70 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.495244E+10 23457.23 01-JAN-15:31 25.00 18.55 0.403478E+09 544.96 05-JAN-14:50 14.83 10.49
February 0.605585E+10 22725.05 26-FEB-15:12 25.90 20.05 0.371548E+09 544.97 28-FEB-14:09 25.00 20.38
March 0.852925E+10 21167.69 26-MAR-15:32 25.33 20.03 0.445376E+09 544.97 23-MAR-09:09 25.33 20.03
April 0.117870E+11 23485.85 23-APR-16:32 27.37 21.80 0.396559E+09 545.00 27-APR-13:00 28.80 22.60
May 0.994680E+10 23471.22 28-MAY-16:31 32.03 24.85 0.429259E+09 545.00 08-MAY-13:50 32.03 24.85
June 0.119351E+11 23512.99 04-JUN-16:02 29.50 24.64 0.427914E+09 544.97 02-JUN-09:39 29.50 24.64
July 0.130435E+11 23627.09 30-JUL-16:52 27.20 24.74 0.398220E+09 544.94 14-JUL-13:20 27.20 24.74
August 0.156917E+11 22793.51 06-AUG-16:22 25.00 22.52 0.446504E+09 544.97 15-AUG-09:20 26.10 22.41
September 0.921654E+10 24307.61 24-SEP-16:11 30.13 25.90 0.396455E+09 544.96 21-SEP-13:50 30.13 25.90
October 0.103700E+11 22925.95 08-OCT-15:41 31.00 25.31 0.412314E+09 550.37 23-OCT-09:39 25.67 23.79
November 0.849376E+10 23528.68 05-NOV-14:52 27.20 20.06 0.407933E+09 544.97 06-NOV-10:00 25.50 20.23
December 0.837407E+10 24523.34 10-DEC-15:01 27.83 20.05 0.397479E+09 545.00 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.118396E+12         0.493304E+10        
Minimum of Months 0.495244E+10 21167.69   25.00 18.55 0.371548E+09 544.94   14.83 10.49
Maximum of Months 0.156917E+11 24523.34   32.03 25.90 0.446504E+09 550.37   32.03 25.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288310E+10 4908.68 02-JAN-13:30 26.00 18.64 0.536347E+09 845.61 02-JAN-14:20 26.33 18.48
February 0.316136E+10 5193.86 28-FEB-15:00 25.00 20.38 0.513454E+09 845.60 27-FEB-10:20 25.00 20.38
March 0.415596E+10 6738.93 30-MAR-13:30 28.55 22.55 0.627796E+09 845.62 24-MAR-13:20 28.55 22.55
April 0.549160E+10 8633.09 29-APR-05:03 23.20 21.68 0.598390E+09 845.62 12-APR-13:20 23.20 21.68
May 0.905657E+10 11275.05 30-MAY-05:02 25.50 24.21 0.664271E+09 845.68 02-MAY-13:09 25.50 24.21
June 0.985411E+10 14326.72 11-JUN-17:21 32.75 21.65 0.662320E+09 845.61 13-JUN-13:20 33.17 21.40
July 0.973111E+10 14116.80 04-JUL-16:42 30.68 26.02 0.616040E+09 845.61 14-JUL-13:20 26.67 25.30
August 0.960643E+10 12963.88 21-AUG-03:02 26.27 23.88 0.690797E+09 845.61 25-AUG-13:20 27.90 24.42
September 0.772593E+10 14442.94 10-SEP-14:31 35.67 27.27 0.612395E+09 845.61 22-SEP-13:00 30.00 22.00
October 0.700295E+10 9930.41 10-OCT-04:11 22.00 19.99 0.630475E+09 845.66 23-OCT-09:39 25.67 23.79
November 0.432752E+10 9699.76 03-NOV-05:02 22.28 21.91 0.593729E+09 845.62 17-NOV-14:20 23.10 14.77
December 0.335475E+10 5619.61 15-DEC-14:05 29.00 22.01 0.533889E+09 845.62 15-DEC-14:09 29.00 22.01
                     
Annual Sum or Average 0.763514E+11         0.727990E+10        
Minimum of Months 0.288310E+10 4908.68   22.00 18.64 0.513454E+09 845.60   23.10 14.77
Maximum of Months 0.985411E+10 14442.94   35.67 27.27 0.690797E+09 845.68   33.17 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.224378E+10 8515.06 19-JAN-11:05 24.92 21.49 0.281325E+09 548.49 24-JAN-13:09 17.00 10.00
February 0.272143E+10 9231.37 27-FEB-11:05 22.80 19.34 0.261939E+09 548.50 09-FEB-11:09 22.80 19.34
March 0.401961E+10 17836.15 26-MAR-10:13 26.07 20.20 0.314505E+09 548.52 15-MAR-12:09 26.07 20.20
April 0.552332E+10 18533.61 23-APR-09:32 25.53 20.92 0.289451E+09 548.51 10-APR-14:09 25.53 20.92
May 0.812307E+10 20106.58 14-MAY-09:22 28.60 23.59 0.316789E+09 548.48 03-MAY-12:09 28.60 23.59
June 0.845312E+10 18828.40 11-JUN-08:62 25.47 21.10 0.315302E+09 548.49 08-JUN-14:09 25.47 21.10
July 0.831720E+10 18585.88 23-JUL-09:42 30.82 26.39 0.294417E+09 548.49 05-JUL-12:09 30.82 26.39
August 0.809374E+10 18309.57 06-AUG-08:32 28.67 26.43 0.328767E+09 548.48 30-AUG-12:09 31.18 24.70
September 0.652789E+10 20105.30 03-SEP-08:52 29.90 24.25 0.292448E+09 548.48 01-SEP-10:09 29.90 24.25
October 0.619988E+10 19702.04 09-OCT-09:12 27.73 22.40 0.302334E+09 548.51 17-OCT-12:09 21.17 14.63
November 0.371824E+10 15424.61 11-NOV-10:52 26.10 21.82 0.294739E+09 548.49 13-NOV-11:09 18.77 14.38
December 0.248238E+10 10207.59 10-DEC-11:12 26.33 20.64 0.271204E+09 548.49 01-DEC-11:09 26.33 20.64
                     
Annual Sum or Average 0.664237E+11         0.356322E+10        
Minimum of Months 0.224378E+10 8515.06   22.80 19.34 0.261939E+09 548.48   17.00 10.00
Maximum of Months 0.845312E+10 20106.58   30.82 26.43 0.328767E+09 548.52   31.18 26.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.842714E+10 20323.28 01-JAN-13:42 25.83 18.00 0.616634E+09 927.44 19-JAN-14:39 25.00 21.54
February 0.784745E+10 19568.68 26-FEB-11:32 25.73 19.91 0.562848E+09 912.43 27-FEB-14:20 25.70 20.08
March 0.716647E+10 19280.86 05-MAR-13:53 27.70 18.31 0.659938E+09 845.67 24-MAR-13:30 24.40 16.03
April 0.726048E+10 12629.96 23-APR-13:33 27.53 21.02 0.603926E+09 845.67 10-APR-13:00 27.53 21.02
May 0.931773E+10 13108.03 03-MAY-04:12 23.13 21.53 0.664311E+09 845.72 02-MAY-13:09 23.13 21.53
June 0.943405E+10 13785.27 26-JUN-05:02 25.00 23.50 0.662090E+09 845.63 13-JUN-13:20 25.00 23.50
July 0.964969E+10 17241.91 09-JUL-14:12 29.07 25.40 0.615930E+09 845.62 14-JUL-13:20 26.67 25.30
August 0.108875E+11 16842.12 06-AUG-12:32 31.00 25.63 0.691132E+09 845.63 25-AUG-13:20 27.90 24.42
September 0.102406E+11 20133.70 10-SEP-14:31 35.67 27.27 0.613750E+09 845.64 21-SEP-13:50 26.78 22.76
October 0.125704E+11 20776.04 01-OCT-13:42 27.87 18.52 0.639780E+09 908.05 13-OCT-13:50 32.87 23.24
November 0.107024E+11 21812.98 11-NOV-13:31 26.27 22.81 0.631069E+09 954.74 06-NOV-14:09 26.27 22.81
December 0.935755E+10 22277.23 10-DEC-13:51 27.00 20.22 0.596008E+09 927.07 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.112861E+12         0.755742E+10        
Minimum of Months 0.716647E+10 12629.96   23.13 18.00 0.562848E+09 845.62   23.13 16.03
Maximum of Months 0.125704E+11 22277.23   35.67 27.27 0.691132E+09 954.74   32.87 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.306063E+10 14119.22 01-JAN-17:03 23.33 19.19 0.371761E+09 544.95 24-JAN-14:39 17.00 10.58
February 0.347971E+10 20154.00 26-FEB-17:32 23.67 19.48 0.349853E+09 544.95 14-FEB-14:50 23.67 19.48
March 0.439509E+10 16030.07 05-MAR-16:32 26.10 18.81 0.421619E+09 544.95 24-MAR-13:20 24.03 15.88
April 0.618519E+10 20821.61 16-APR-16:52 19.40 13.58 0.392736E+09 544.96 12-APR-13:20 19.40 13.58
May 0.799723E+10 20437.72 29-MAY-16:12 32.07 23.52 0.428731E+09 545.00 02-MAY-13:09 32.07 23.52
June 0.864065E+10 21899.98 11-JUN-17:21 32.75 21.65 0.427496E+09 544.95 13-JUN-13:20 33.17 21.40
July 0.835280E+10 19729.66 16-JUL-15:52 31.70 25.48 0.397751E+09 544.94 14-JUL-13:20 31.70 25.48
August 0.881735E+10 17528.24 07-AUG-03:02 26.67 24.75 0.445977E+09 544.94 15-AUG-09:20 26.10 22.41
September 0.709189E+10 21837.94 03-SEP-15:31 32.37 24.62 0.395867E+09 544.94 21-SEP-13:50 26.78 22.76
October 0.695101E+10 20927.79 09-OCT-16:31 28.00 21.42 0.409802E+09 544.99 23-OCT-09:39 25.67 23.79
November 0.440247E+10 19972.98 11-NOV-15:32 26.27 22.90 0.395779E+09 545.01 27-NOV-14:09 25.82 17.52
December 0.357863E+10 19941.82 10-DEC-15:52 27.00 20.22 0.366285E+09 544.96 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.729526E+11         0.480366E+10        
Minimum of Months 0.306063E+10 14119.22   19.40 13.58 0.349853E+09 544.94   17.00 10.58
Maximum of Months 0.881735E+10 21899.98   32.75 25.48 0.445977E+09 545.01   33.17 25.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.220744E+10 5117.66 31-JAN-15:00 25.00 21.54 0.518356E+09 845.60 02-JAN-14:20 25.00 21.54
February 0.278850E+10 5572.84 22-FEB-14:30 25.55 20.41 0.498114E+09 845.60 28-FEB-14:09 25.00 20.38
March 0.386878E+10 7208.56 30-MAR-13:30 28.55 22.55 0.607542E+09 845.61 24-MAR-13:20 28.55 22.55
April 0.560764E+10 8901.26 28-APR-15:00 33.30 23.06 0.590322E+09 845.64 27-APR-13:00 33.30 23.06
May 0.982291E+10 16588.55 29-MAY-14:42 32.70 23.12 0.664539E+09 868.45 08-MAY-13:50 32.70 23.12
June 0.108268E+11 17046.92 11-JUN-17:21 32.75 21.65 0.662580E+09 845.62 13-JUN-13:20 33.17 21.40
July 0.107154E+11 16579.98 04-JUL-16:42 30.68 26.02 0.616383E+09 845.61 14-JUL-13:20 26.67 25.30
August 0.104734E+11 16307.81 20-AUG-14:12 33.67 24.98 0.690930E+09 845.60 25-AUG-13:20 27.90 24.42
September 0.821823E+10 17234.90 10-SEP-14:31 35.67 27.27 0.612229E+09 845.62 21-SEP-13:50 26.78 22.76
October 0.729467E+10 16837.32 08-OCT-13:01 32.17 26.14 0.625953E+09 845.66 23-OCT-09:39 25.67 23.79
November 0.398788E+10 9477.66 03-NOV-05:02 22.28 21.91 0.573701E+09 845.61 06-NOV-10:20 24.37 20.12
December 0.274729E+10 6165.33 15-DEC-15:00 29.00 21.56 0.513544E+09 845.62 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.785589E+11         0.717419E+10        
Minimum of Months 0.220744E+10 5117.66   22.28 20.41 0.498114E+09 845.60   24.37 20.12
Maximum of Months 0.108268E+11 17234.90   35.67 27.27 0.690930E+09 868.45   33.30 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213782E+10 6983.78 19-JAN-10:20 23.57 21.08 0.364610E+09 544.94 02-JAN-14:20 23.57 21.08
February 0.267506E+10 7499.19 27-FEB-10:30 21.90 19.28 0.346647E+09 544.95 09-FEB-10:00 21.90 19.28
March 0.400745E+10 11706.57 26-MAR-09:13 24.03 19.81 0.419056E+09 544.98 23-MAR-09:09 24.03 19.81
April 0.582951E+10 18817.68 23-APR-09:32 25.53 20.92 0.390837E+09 544.97 27-APR-13:00 28.80 22.60
May 0.896815E+10 21185.53 29-MAY-10:01 29.08 23.08 0.428896E+09 548.16 02-MAY-13:09 29.08 23.08
June 0.942541E+10 19139.94 11-JUN-08:62 25.47 21.10 0.427404E+09 544.95 13-JUN-13:20 33.17 21.40
July 0.929889E+10 19032.38 23-JUL-09:42 30.82 26.39 0.397746E+09 544.94 14-JUL-13:20 30.82 26.39
August 0.901478E+10 18687.05 06-AUG-08:32 28.67 26.43 0.445729E+09 544.94 25-AUG-13:20 27.90 24.42
September 0.716806E+10 20484.99 03-SEP-08:52 29.90 24.25 0.395580E+09 544.95 21-SEP-13:50 26.78 22.76
October 0.667783E+10 20097.43 09-OCT-09:12 27.73 22.40 0.407765E+09 545.00 23-OCT-09:39 25.67 23.79
November 0.358544E+10 11558.52 11-NOV-09:43 24.40 21.68 0.395029E+09 544.95 24-NOV-10:20 20.87 16.31
December 0.234875E+10 6975.23 10-DEC-10:43 25.67 20.42 0.353121E+09 544.95 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.711372E+11         0.477242E+10        
Minimum of Months 0.213782E+10 6975.23   21.90 19.28 0.346647E+09 544.94   20.87 16.31
Maximum of Months 0.942541E+10 21185.53   30.82 26.43 0.445729E+09 548.16   33.17 26.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.715397E+10 24854.72 01-JAN-14:01 25.83 18.00 0.602394E+09 900.32 19-JAN-14:39 25.00 21.54
February 0.719884E+10 23011.79 26-FEB-14:02 26.52 19.79 0.550982E+09 887.31 27-FEB-14:09 25.60 20.00
March 0.674925E+10 21161.47 05-MAR-13:53 27.70 18.31 0.643126E+09 845.63 15-MAR-13:20 22.20 16.14
April 0.739959E+10 16370.41 23-APR-13:33 27.53 21.02 0.597161E+09 845.68 27-APR-13:00 28.80 22.60
May 0.101015E+11 20502.38 29-MAY-14:42 32.70 23.12 0.664474E+09 863.74 08-MAY-13:50 32.70 23.12
June 0.103970E+11 20445.16 11-JUN-16:01 32.38 21.26 0.662283E+09 845.64 13-JUN-13:20 33.17 21.40
July 0.106316E+11 20187.94 09-JUL-14:12 29.07 25.40 0.616225E+09 845.62 14-JUL-13:20 26.67 25.30
August 0.118087E+11 20419.67 27-AUG-12:23 32.00 23.77 0.691209E+09 845.62 25-AUG-13:20 32.00 23.77
September 0.108489E+11 23019.05 10-SEP-14:31 35.67 27.27 0.613496E+09 845.66 21-SEP-13:50 26.78 22.76
October 0.129887E+11 23663.83 08-OCT-13:01 32.17 26.14 0.635799E+09 891.24 13-OCT-13:50 32.87 23.24
November 0.998826E+10 23124.18 05-NOV-13:42 27.20 20.74 0.621516E+09 927.17 06-NOV-14:09 28.30 21.03
December 0.830212E+10 22493.87 10-DEC-14:02 27.17 20.19 0.579086E+09 907.30 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.113568E+12         0.747775E+10        
Minimum of Months 0.674925E+10 16370.41   25.83 18.00 0.550982E+09 845.62   22.20 16.14
Maximum of Months 0.129887E+11 24854.72   35.67 27.27 0.691209E+09 927.17   33.17 25.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.263006E+10 21034.49 01-JAN-15:21 25.00 18.55 0.360710E+09 544.94 02-JAN-14:20 26.33 18.48
February 0.325481E+10 22035.62 26-FEB-16:42 24.58 19.86 0.341429E+09 544.94 28-FEB-14:09 25.00 20.38
March 0.422058E+10 18307.64 26-MAR-15:13 24.57 19.90 0.409655E+09 544.95 15-MAR-13:20 24.57 19.90
April 0.630117E+10 21535.74 23-APR-16:52 27.20 21.71 0.389052E+09 544.97 27-APR-13:00 28.80 22.60
May 0.854712E+10 22325.15 29-MAY-16:41 30.97 23.75 0.428842E+09 547.91 02-MAY-13:09 30.97 23.75
June 0.933077E+10 23905.70 11-JUN-17:21 32.75 21.65 0.427552E+09 544.95 13-JUN-13:20 33.17 21.40
July 0.905185E+10 21168.61 16-JUL-15:52 31.70 25.48 0.397833E+09 544.94 14-JUL-13:20 31.70 25.48
August 0.943262E+10 20390.21 20-AUG-16:51 30.00 24.17 0.446035E+09 544.94 25-AUG-13:20 27.90 24.42
September 0.748067E+10 23909.97 03-SEP-15:31 32.37 24.62 0.395788E+09 544.95 21-SEP-13:50 26.78 22.76
October 0.719906E+10 22853.09 01-OCT-15:51 27.70 18.29 0.407876E+09 544.98 23-OCT-09:39 25.67 23.79
November 0.415397E+10 21120.67 05-NOV-15:42 27.20 19.63 0.386524E+09 544.95 21-NOV-14:00 22.20 15.14
December 0.317538E+10 16690.96 10-DEC-15:22 27.50 20.13 0.353458E+09 544.97 15-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.747781E+11         0.474475E+10        
Minimum of Months 0.263006E+10 16690.96   24.57 18.29 0.341429E+09 544.94   22.20 15.14
Maximum of Months 0.943262E+10 23909.97   32.75 25.48 0.446035E+09 547.91   33.17 25.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.306823E+10 11431.37 02-JAN-06:03 16.00 15.39 0.00 0.00 01-JAN-00:10 16.00 15.39
February 0.338077E+10 7259.44 27-FEB-16:50 24.58 20.33 0.00 0.00 01-FEB-00:10 24.58 20.33
March 0.448508E+10 6378.88 27-MAR-05:03 19.82 18.59 0.00 0.00 01-MAR-00:10 19.82 18.59
April 0.593307E+10 6508.12 24-APR-05:03 20.08 20.03 0.00 0.00 01-APR-00:10 20.08 20.03
May 0.728347E+10 9311.33 30-MAY-05:02 25.50 24.21 0.00 0.00 01-MAY-00:10 25.50 24.21
June 0.786206E+10 8859.71 26-JUN-05:02 25.00 23.50 0.00 0.00 01-JUN-00:10 25.00 23.50
July 0.843312E+10 10723.15 05-JUL-05:02 26.10 24.88 0.00 0.00 01-JUL-00:10 26.10 24.88
August 0.936954E+10 10014.19 21-AUG-05:15 26.00 23.88 0.00 0.00 01-AUG-00:10 26.00 23.88
September 0.698553E+10 10755.25 11-SEP-05:02 25.42 23.91 0.00 0.00 01-SEP-00:10 25.42 23.91
October 0.733811E+10 9638.47 10-OCT-05:03 21.98 20.05 0.00 0.00 01-OCT-00:10 21.98 20.05
November 0.541317E+10 8061.94 06-NOV-06:03 18.80 17.70 0.00 0.00 01-NOV-00:10 18.80 17.70
December 0.440118E+10 6586.65 26-DEC-06:13 5.90 2.19 0.00 0.00 01-DEC-00:10 5.90 2.19
                     
Annual Sum or Average 0.739533E+11         0.00        
Minimum of Months 0.306823E+10 6378.88   5.90 2.19 0.00 0.00   5.90 2.19
Maximum of Months 0.936954E+10 11431.37   26.10 24.88 0.00 0.00   26.10 24.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158076E+10 6879.02 05-JAN-06:01 0.17 0.10 0.00 0.00 01-JAN-00:10 0.17 0.10
February 0.176936E+10 6252.11 17-FEB-06:02 1.52 -1.3 0.00 0.00 01-FEB-00:10 1.52 -1.3
March 0.241563E+10 4351.55 11-MAR-06:02 6.60 5.25 0.00 0.00 01-MAR-00:10 6.60 5.25
April 0.365836E+10 5273.75 28-APR-05:03 22.80 21.69 0.00 0.00 01-APR-00:10 22.80 21.69
May 0.614524E+10 6998.51 03-MAY-12:30 31.15 21.48 0.00 0.00 01-MAY-00:10 31.15 21.48
June 0.639174E+10 6683.54 27-JUN-05:02 24.50 23.30 0.00 0.00 01-JUN-00:10 24.50 23.30
July 0.650860E+10 7066.13 01-JUL-05:02 24.50 23.30 0.00 0.00 01-JUL-00:10 24.50 23.30
August 0.665929E+10 5918.43 30-AUG-16:00 36.30 23.74 0.00 0.00 01-AUG-00:10 36.30 23.74
September 0.557282E+10 8166.78 25-SEP-05:02 23.38 22.59 0.00 0.00 01-SEP-00:10 23.38 22.59
October 0.546781E+10 7914.22 16-OCT-05:02 22.17 20.62 0.00 0.00 01-OCT-00:10 22.17 20.62
November 0.299768E+10 4710.32 06-NOV-16:20 27.73 20.09 0.00 0.00 01-NOV-00:10 27.73 20.09
December 0.217011E+10 5982.38 20-DEC-06:02 2.83 1.61 0.00 0.00 01-DEC-00:10 2.83 1.61
                     
Annual Sum or Average 0.513374E+11         0.00        
Minimum of Months 0.158076E+10 4351.55   0.17 -1.3 0.00 0.00   0.17 -1.3
Maximum of Months 0.665929E+10 8166.78   36.30 23.74 0.00 0.00   36.30 23.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.177700E+10 8976.59 19-JAN-16:00 25.00 20.82 0.00 0.00 01-JAN-00:10 25.00 20.82
February 0.273427E+10 11082.53 27-FEB-15:30 25.80 20.48 0.00 0.00 01-FEB-00:10 25.80 20.48
March 0.383976E+10 10702.72 06-MAR-14:40 26.27 21.25 0.00 0.00 01-MAR-00:10 26.27 21.25
April 0.679426E+10 15593.71 28-APR-15:00 33.30 23.06 0.00 0.00 01-APR-00:10 33.30 23.06
May 0.113609E+11 21132.46 08-MAY-13:40 32.60 22.45 0.00 0.00 01-MAY-00:10 32.60 22.45
June 0.125753E+11 19580.76 08-JUN-14:30 31.65 22.58 0.00 0.00 01-JUN-00:10 31.65 22.58
July 0.120811E+11 17655.94 07-JUL-14:40 34.63 24.19 0.00 0.00 01-JUL-00:10 34.63 24.19
August 0.121463E+11 16962.02 03-AUG-15:00 35.00 24.85 0.00 0.00 01-AUG-00:10 35.00 24.85
September 0.921566E+10 15626.96 01-SEP-14:00 32.20 22.62 0.00 0.00 01-SEP-00:10 32.20 22.62
October 0.873654E+10 15416.72 05-OCT-15:20 33.33 23.87 0.00 0.00 01-OCT-00:10 33.33 23.87
November 0.388663E+10 12059.36 02-NOV-14:20 29.40 24.36 0.00 0.00 01-NOV-00:10 29.40 24.36
December 0.242941E+10 10819.25 15-DEC-14:50 29.00 21.65 0.00 0.00 01-DEC-00:10 29.00 21.65
                     
Annual Sum or Average 0.875772E+11         0.00        
Minimum of Months 0.177700E+10 8976.59   25.00 20.48 0.00 0.00   25.00 20.48
Maximum of Months 0.125753E+11 21132.46   35.00 24.85 0.00 0.00   35.00 24.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.381441E+10 2153.84 01-JAN-17:12 22.67 19.00 95231661.64 126.84 02-JAN-10:00 24.00 19.35
February 0.823335E+10 4198.55 26-FEB-17:54 23.30 19.29 86405106.17 126.85 24-FEB-14:00 23.30 19.29
March 0.142992E+11 7164.26 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 07-MAR-14:00 20.70 19.78
April 0.188816E+11 7989.48 16-APR-18:20 18.07 13.19 91642358.55 128.20 28-APR-13:00 32.70 23.02
May 0.449422E+10 3450.02 31-MAY-24:00 23.00 21.40 99235360.36 126.85 12-MAY-13:00 23.00 21.40
June 0.922292E+10 5326.41 30-JUN-24:00 25.10 23.16 98979906.40 126.86 01-JUN-13:09 25.10 23.16
July 0.145957E+11 7201.91 31-JUL-23:55 25.20 23.65 91894572.22 126.85 31-JUL-13:00 25.20 23.65
August 0.196852E+11 7780.83 06-AUG-18:00 25.00 23.59 0.104659E+09 135.22 28-AUG-13:00 33.00 25.67
September 0.437582E+10 3472.55 30-SEP-24:00 22.30 21.22 91605768.38 126.82 05-SEP-13:09 22.30 21.22
October 0.956305E+10 5327.92 31-OCT-24:00 21.60 20.90 95247478.84 126.87 24-OCT-09:09 21.60 20.90
November 0.140133E+11 6014.84 12-NOV-17:10 14.53 8.53 94306907.27 126.85 29-NOV-10:00 22.70 21.98
December 0.193979E+11 7881.62 10-DEC-16:53 25.00 19.63 91882342.29 126.83 28-DEC-14:09 19.17 19.17
                     
Annual Sum or Average 0.140577E+12         0.114433E+10        
Minimum of Months 0.381441E+10 2153.84   14.53 8.53 86405106.17 126.82   19.17 19.17
Maximum of Months 0.196852E+11 7989.48   25.20 23.65 0.104659E+09 135.22   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.239880E+10 1795.43 01-JAN-17:25 22.00 18.79 95230990.10 126.84 02-JAN-14:09 26.17 18.43
February 0.688831E+10 3840.77 26-FEB-17:54 23.30 19.29 86404719.73 126.85 24-FEB-14:00 23.30 19.29
March 0.128311E+11 6688.59 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 07-MAR-14:00 20.70 19.78
April 0.177654E+11 7484.34 16-APR-18:20 18.07 13.19 91644552.47 128.48 28-APR-13:00 32.70 23.02
May 0.407633E+10 3224.12 31-MAY-24:00 23.00 21.40 99233646.70 126.82 26-MAY-13:09 23.00 21.40
June 0.869887E+10 5143.36 30-JUN-24:00 25.10 23.16 98978968.51 126.86 19-JUN-09:09 25.10 23.16
July 0.138528E+11 6895.06 31-JUL-24:00 25.20 23.65 91893857.10 126.85 14-JUL-13:00 25.20 23.65
August 0.186458E+11 7255.41 06-AUG-17:40 25.33 23.69 0.104451E+09 133.63 28-AUG-13:00 33.00 25.67
September 0.388522E+10 3201.26 30-SEP-24:00 22.30 21.22 91605380.76 126.82 05-SEP-13:09 22.30 21.22
October 0.882342E+10 4919.07 31-OCT-24:00 21.60 20.90 95246779.25 126.87 24-OCT-09:09 21.60 20.90
November 0.126999E+11 5574.67 06-NOV-17:00 26.60 19.72 94306534.22 126.84 01-NOV-09:00 26.60 19.72
December 0.174762E+11 7293.24 15-DEC-17:00 28.00 21.24 91882381.84 126.83 28-DEC-14:09 19.17 19.17
                     
Annual Sum or Average 0.128042E+12         0.114412E+10        
Minimum of Months 0.239880E+10 1795.43   18.07 13.19 86404719.73 126.82   19.17 18.43
Maximum of Months 0.186458E+11 7484.34   28.00 23.69 0.104451E+09 133.63   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.149766E+10 1873.38 01-JAN-17:12 22.67 19.00 94926405.92 127.12 09-JAN-10:39 10.33 6.44
February 0.608554E+10 3889.11 26-FEB-17:43 23.48 19.39 86405000.01 126.85 24-FEB-14:00 23.48 19.39
March 0.122436E+11 6592.86 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 07-MAR-14:00 20.70 19.78
April 0.176336E+11 7684.29 23-APR-17:53 25.50 21.28 91633878.37 127.40 28-APR-13:00 32.70 23.02
May 0.422583E+10 3196.11 31-MAY-24:00 23.00 21.40 99235005.07 126.85 03-MAY-13:00 23.00 21.40
June 0.886252E+10 5179.29 30-JUN-24:00 25.10 23.16 98980118.78 126.86 01-JUN-13:09 25.10 23.16
July 0.140244E+11 6886.20 31-JUL-24:00 25.20 23.65 91894688.17 126.85 12-JUL-13:09 25.20 23.65
August 0.187938E+11 7529.91 06-AUG-17:40 25.33 23.69 0.104040E+09 132.78 28-AUG-13:00 33.00 25.67
September 0.398845E+10 3226.95 30-SEP-24:00 22.30 21.22 91605403.01 126.82 05-SEP-13:09 22.30 21.22
October 0.876641E+10 4850.49 31-OCT-24:00 21.60 20.90 95247428.42 126.87 06-OCT-13:00 21.60 20.90
November 0.121525E+11 5634.82 06-NOV-17:00 26.60 19.72 94306819.65 126.85 01-NOV-09:00 26.60 19.72
December 0.165758E+11 7357.72 15-DEC-17:00 28.00 21.24 91882707.05 126.83 28-DEC-14:09 19.17 19.17
                     
Annual Sum or Average 0.124850E+12         0.114340E+10        
Minimum of Months 0.149766E+10 1873.38   20.70 19.00 86405000.01 126.82   10.33 6.44
Maximum of Months 0.187938E+11 7684.29   28.00 23.69 0.104040E+09 132.78   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.239468E+12 92414.33 02-JAN-14:40 26.67 18.58 0.206150E+10 2746.60 19-JAN-14:00 25.00 21.54
February 0.435721E+12 182989.29 27-FEB-17:00 24.40 20.28 0.187039E+10 2747.66 10-FEB-10:30 24.40 20.28
March 0.727335E+12 358132.21 31-MAR-24:00 20.70 19.78 0.223521E+10 2749.13 16-MAR-13:00 20.70 19.78
April 0.939332E+12 367507.40 18-APR-16:05 27.75 17.06 0.204232E+10 3328.67 28-APR-13:00 32.70 23.02
May 0.239656E+12 175300.28 31-MAY-24:00 23.00 21.40 0.214895E+10 2747.11 26-MAY-09:09 23.00 21.40
June 0.467970E+12 266915.32 30-JUN-24:00 25.10 23.16 0.214274E+10 2746.54 01-JUN-13:09 25.10 23.16
July 0.730091E+12 359206.29 31-JUL-23:55 25.20 23.65 0.198923E+10 2745.90 12-JUL-13:09 25.20 23.65
August 0.971271E+12 370273.17 09-AUG-21:14 23.27 22.90 0.260155E+10 3580.64 28-AUG-13:00 33.00 25.67
September 0.235752E+12 176353.33 30-SEP-24:00 22.30 21.22 0.198389E+10 2747.09 18-SEP-13:00 22.30 21.22
October 0.487433E+12 268263.94 31-OCT-24:00 21.60 20.90 0.206196E+10 2747.60 30-OCT-09:50 21.60 20.90
November 0.708416E+12 275826.39 06-NOV-17:00 26.60 19.72 0.204207E+10 2750.52 20-NOV-10:09 20.18 16.15
December 0.976300E+12 367285.59 26-DEC-17:00 12.70 5.60 0.201532E+10 3137.15 13-DEC-14:00 12.70 5.60
                     
Annual Sum or Average 0.715874E+13         0.251951E+11        
Minimum of Months 0.235752E+12 92414.33   12.70 5.60 0.187039E+10 2745.90   12.70 5.60
Maximum of Months 0.976300E+12 370273.17   27.75 23.65 0.260155E+10 3580.64   33.00 25.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213079E+09 10197.59 06-JAN-05:15 11.33
February 0.198242E+09 10977.80 25-FEB-17:02 26.55
March 0.121702E+09 10195.01 15-MAR-04:15 9.87
April 0.159995E+09 16377.62 22-APR-16:01 30.08
May 0.298958E+09 18309.83 27-MAY-16:02 31.60
June 0.322241E+09 21599.03 10-JUN-16:01 33.72
July 0.386526E+09 24886.91 22-JUL-16:01 35.92
August 0.407463E+09 19265.77 19-AUG-16:02 32.63
September 0.516467E+09 24565.58 09-SEP-16:01 35.73
October 0.511804E+09 18512.29 07-OCT-16:01 31.58
November 0.502777E+09 12019.02 12-NOV-08:43 8.12
December 0.490471E+09 11989.64 25-DEC-09:53 12.00
         
Annual Sum or Average 0.412973E+10      
Minimum of Months 0.121702E+09 10195.01   8.12
Maximum of Months 0.516467E+09 24886.91   35.92



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.123463E+09 49534.88 10-JAN-06:02 3.00
February 0.306635E+09 56949.33 06-FEB-05:11 2.97
March 31895001.19 49490.01 13-MAR-05:02 6.68
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 54638561.19 49515.16 21-DEC-06:01 0.83
         
Annual Sum or Average 0.516631E+09      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 0.306635E+09 56949.33   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 12397.59 144.64 05-JAN-06:04 0.17
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 168814.96 1969.51 21-DEC-06:01 0.83
         
Annual Sum or Average 181212.55      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 168814.96 1969.51   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10796.21 125.96 05-JAN-06:06 0.17
February 27786.91 231.56 06-FEB-06:04 2.88
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 38583.12      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 27786.91 231.56   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.249155E+09 10753.19 10-JAN-05:01 1.33
February 0.117167E+09 11063.11 06-FEB-05:11 2.97
March 59347724.04 10158.00 13-MAR-05:02 6.68
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 327337.35 2240.63 16-NOV-06:02 9.40
December 0.132234E+09 10730.64 21-DEC-05:01 0.17
         
Annual Sum or Average 0.558232E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.249155E+09 11063.11   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 94387644.73 9388.93 10-JAN-05:01 1.33
February 43365039.40 9642.54 06-FEB-05:11 2.97
March 23594342.07 8808.72 09-MAR-06:02 1.10
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 66331594.04 9397.82 21-DEC-05:01 0.17
         
Annual Sum or Average 0.227679E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 94387644.73 9642.54   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42696624.17 11674.16 21-JAN-06:02 1.00
February 17241039.93 11445.05 06-FEB-06:02 2.88
March 18697758.49 11402.67 11-MAR-06:02 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 42811701.97 11556.44 21-DEC-06:01 0.83
         
Annual Sum or Average 0.121447E+09      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 42811701.97 11674.16   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 52299256.06 8282.78 10-JAN-05:01 1.33
February 19522247.04 8245.13 06-FEB-05:11 2.97
March 5892436.39 7535.40 11-MAR-06:02 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 27051874.29 7859.15 21-DEC-06:01 0.83
         
Annual Sum or Average 0.104766E+09      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 52299256.06 8282.78   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124326E+10 13662.00 23-JAN-05:11 7.67
February 0.715932E+09 14465.74 05-FEB-07:43 -3.4
March 0.437296E+09 12917.07 13-MAR-04:11 7.00
April 321400.74 1547.46 03-APR-05:03 12.28
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 3301330.59 5911.62 28-OCT-05:03 10.00
November 90327978.90 11838.68 16-NOV-05:12 9.27
December 0.791982E+09 13330.15 21-DEC-04:02 1.67
         
Annual Sum or Average 0.328242E+10      
Minimum of Months 0.00 0.00   -3.4
Maximum of Months 0.124326E+10 14465.74   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.505638E+09 12611.10 23-JAN-05:11 7.67
February 0.266326E+09 13397.98 06-FEB-05:11 2.97
March 0.218413E+09 11903.19 10-MAR-05:11 5.77
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 1055665.78 2580.99 28-OCT-05:03 10.00
November 25145665.97 10458.94 16-NOV-06:02 9.40
December 0.388544E+09 12417.36 20-DEC-05:11 4.33
         
Annual Sum or Average 0.140512E+10      
Minimum of Months 0.00 0.00   2.97
Maximum of Months 0.505638E+09 13397.98   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.466791E+09 15724.09 10-JAN-05:01 1.33
February 0.279231E+09 17126.95 06-FEB-05:11 2.97
March 0.274102E+09 15328.08 11-MAR-05:11 7.13
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 7397802.13 13840.18 16-NOV-06:02 9.40
December 0.320788E+09 15991.28 20-DEC-05:11 4.33
         
Annual Sum or Average 0.134831E+10      
Minimum of Months 0.00 0.00   1.33
Maximum of Months 0.466791E+09 17126.95   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.385104E+09 11998.08 10-JAN-05:01 1.33
February 0.206489E+09 13091.31 06-FEB-05:11 2.97
March 0.120570E+09 11250.19 10-MAR-05:11 5.77
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 7661590.64 10072.19 16-NOV-06:02 9.40
December 0.208516E+09 11922.83 20-DEC-05:11 4.33
         
Annual Sum or Average 0.928341E+09      
Minimum of Months 0.00 0.00   1.33
Maximum of Months 0.385104E+09 13091.31   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 63804380.99 8879.19 09-JAN-05:11 7.67
February 64467120.48 8831.42 21-FEB-05:12 17.27
March 66380050.01 8819.59 13-MAR-04:11 7.00
April 71235334.80 9176.42 03-APR-04:12 12.43
May 39260254.26 6137.27 28-MAY-14:32 33.13
June 35876702.68 6256.00 07-JUN-04:12 21.10
July 41961593.05 6777.38 02-JUL-15:32 29.07
August 34747591.91 6929.54 06-AUG-15:02 30.67
September 46694898.33 6757.27 29-SEP-04:12 23.80
October 69387999.70 8404.62 30-OCT-04:12 16.67
November 82777301.35 8905.12 27-NOV-05:12 14.33
December 0.119054E+09 9386.51 26-DEC-05:12 6.97
         
Annual Sum or Average 0.735647E+09      
Minimum of Months 34747591.91 6137.27   6.97
Maximum of Months 0.119054E+09 9386.51   33.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.309415E+09 5719.58 16-JAN-16:03 24.67
February 0.191206E+09 5811.85 26-FEB-16:52 24.40
March 0.112267E+09 5267.36 20-MAR-05:02 12.10
April 26668759.11 4361.19 10-APR-05:02 12.20
May 28311814.12 5965.54 22-MAY-03:02 26.10
June 22263167.80 5721.23 11-JUN-16:01 32.38
July 29892221.17 5029.66 09-JUL-14:12 29.07
August 21472603.77 4459.92 23-AUG-03:02 26.48
September 39213966.83 7957.14 10-SEP-15:51 34.30
October 45516224.95 5715.51 29-OCT-16:22 23.50
November 53735155.15 5738.77 11-NOV-14:51 26.60
December 0.152506E+09 6746.87 10-DEC-15:11 27.67
         
Annual Sum or Average 0.103247E+10      
Minimum of Months 21472603.77 4361.19   12.10
Maximum of Months 0.309415E+09 7957.14   34.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.167735E+10 12230.17 10-JAN-06:02 3.00
February 0.106115E+10 17815.77 06-FEB-06:13 3.07
March 0.915331E+09 13235.78 08-MAR-06:02 11.00
April 0.184463E+09 9568.65 21-APR-05:02 18.30
May 28763481.26 7937.25 16-MAY-04:11 23.30
June 24039865.67 7454.53 07-JUN-04:12 21.10
July 18419366.82 6219.50 10-JUL-03:02 25.60
August 19103450.25 6099.11 17-AUG-04:12 21.93
September 25002678.25 7738.66 08-SEP-05:02 24.58
October 0.106884E+09 11851.71 18-OCT-05:02 15.17
November 0.388325E+09 10431.26 06-NOV-06:03 18.80
December 0.127328E+10 13038.38 21-DEC-06:03 0.83
         
Annual Sum or Average 0.572211E+10      
Minimum of Months 18419366.82 6099.11   0.83
Maximum of Months 0.167735E+10 17815.77   25.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.177733E+09 527.04 05-JAN-04:45 1.00
February 536620.06 359.36 05-FEB-09:45 0.82
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.178269E+09      
Minimum of Months 0.00 0.00   0.82
Maximum of Months 0.177733E+09 527.04   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.968216E+10 10174.14 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.878253E+10 10174.14 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.104353E+11 10174.14 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.932187E+10 10174.14 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.100587E+11 10174.14 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.100099E+11 10174.14 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.937071E+10 10174.14 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.104353E+11 10174.14 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.932187E+10 10174.14 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.968216E+10 10174.14 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.956821E+10 10174.14 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.937071E+10 10174.14 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.116039E+12     0.424397E+12    
Minimum of Months 0.878253E+10 10174.14   0.325565E+11 13457.54  
Maximum of Months 0.104353E+11 10174.14   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.869526E+10 9137.09 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.788732E+10 9137.09 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.937162E+10 9137.09 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.837170E+10 9137.09 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.903344E+10 9137.09 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.898958E+10 9137.09 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.841555E+10 9137.09 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.937162E+10 9137.09 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.837170E+10 9137.09 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.869526E+10 9137.09 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.859292E+10 9137.09 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.841555E+10 9137.09 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.104212E+12     0.289614E+12    
Minimum of Months 0.788732E+10 9137.09   0.220609E+11 17206.63  
Maximum of Months 0.937162E+10 9137.09   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.869526E+10 9137.09 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.788732E+10 9137.09 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.937162E+10 9137.09 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.837170E+10 9137.09 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.903344E+10 9137.09 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.898958E+10 9137.09 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.841555E+10 9137.09 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.937162E+10 9137.09 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.837170E+10 9137.09 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.869526E+10 9137.09 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.859292E+10 9137.09 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.841555E+10 9137.09 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.104212E+12     0.289613E+12    
Minimum of Months 0.788732E+10 9137.09   0.220609E+11 17206.56  
Maximum of Months 0.937162E+10 9137.09   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.869526E+10 9137.09 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.788732E+10 9137.09 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.937162E+10 9137.09 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.837170E+10 9137.09 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.903344E+10 9137.09 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.898958E+10 9137.09 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.841555E+10 9137.09 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.937162E+10 9137.09 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.837170E+10 9137.09 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.869526E+10 9137.09 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.859292E+10 9137.09 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.841555E+10 9137.09 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.104212E+12     0.289613E+12    
Minimum of Months 0.788732E+10 9137.09   0.220609E+11 17206.56  
Maximum of Months 0.937162E+10 9137.09   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.664968E+09 931.91 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.582070E+09 966.94 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.669166E+09 884.16 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.585341E+09 911.52 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.611318E+09 633.47 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.600969E+09 545.86 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.569095E+09 614.12 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.643095E+09 636.61 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.592374E+09 881.55 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.630880E+09 1017.23 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.654186E+09 972.76 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.657998E+09 1008.39 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.746146E+10     0.363654E+11    
Minimum of Months 0.569095E+09 545.86   0.277008E+10 2160.55  
Maximum of Months 0.669166E+09 1017.23   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.421632E+09 559.07 31-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.371000E+09 596.94 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.427704E+09 521.53 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.376432E+09 560.54 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.396067E+09 396.42 30-MAY-15:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.390235E+09 351.77 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.368669E+09 351.77 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.414822E+09 393.46 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.380730E+09 517.96 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.403613E+09 638.09 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.416522E+09 635.00 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.418287E+09 639.05 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.478571E+10     0.234352E+11    
Minimum of Months 0.368669E+09 351.77   0.178515E+10 1392.34  
Maximum of Months 0.427704E+09 639.05   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.639397E+09 900.67 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.568375E+09 947.39 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.663304E+09 873.47 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.586845E+09 915.69 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.616885E+09 638.12 23-MAY-07:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.607661E+09 594.92 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.574045E+09 627.82 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.645744E+09 642.27 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.590925E+09 878.36 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.623797E+09 1009.08 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.632431E+09 941.76 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.631727E+09 996.90 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.738114E+10     0.363660E+11    
Minimum of Months 0.568375E+09 594.92   0.277013E+10 2160.58  
Maximum of Months 0.663304E+09 1009.08   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.418287E+09 610.15 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.370477E+09 628.91 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.430478E+09 594.28 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.378493E+09 603.80 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.396849E+09 493.50 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.389823E+09 402.05 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.369330E+09 412.08 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.416566E+09 538.63 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.383350E+09 594.97 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.405140E+09 661.75 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.411929E+09 642.01 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.412200E+09 650.56 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.478292E+10     0.234351E+11    
Minimum of Months 0.369330E+09 402.05   0.178514E+10 1392.33  
Maximum of Months 0.430478E+09 661.75   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.662709E+09 929.22 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.580637E+09 964.77 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.667836E+09 880.98 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.584690E+09 908.75 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.610808E+09 629.38 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.600154E+09 545.86 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.568752E+09 609.00 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.642612E+09 632.75 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.591506E+09 878.25 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.629940E+09 1015.70 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.652202E+09 970.46 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.655760E+09 1006.81 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.744761E+10     0.363654E+11    
Minimum of Months 0.568752E+09 545.86   0.277008E+10 2160.55  
Maximum of Months 0.667836E+09 1015.70   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.420825E+09 554.83 31-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.370357E+09 593.51 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.427254E+09 517.36 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.376102E+09 556.92 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.395720E+09 393.40 23-MAY-07:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.389980E+09 351.77 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.368305E+09 351.77 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.414527E+09 390.64 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.380313E+09 514.09 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.403213E+09 635.82 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.415832E+09 632.29 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.417458E+09 636.61 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.477989E+10     0.234352E+11    
Minimum of Months 0.368305E+09 351.77   0.178515E+10 1392.34  
Maximum of Months 0.427254E+09 636.61   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.639091E+09 897.79 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.568114E+09 945.10 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.662588E+09 870.22 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.586270E+09 912.93 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.616241E+09 634.26 23-MAY-07:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.607062E+09 588.56 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.573522E+09 623.37 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.645201E+09 638.68 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.590352E+09 875.03 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.623305E+09 1007.50 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.631540E+09 939.58 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.631143E+09 995.27 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.737443E+10     0.363660E+11    
Minimum of Months 0.568114E+09 588.56   0.277013E+10 2160.58  
Maximum of Months 0.662588E+09 1007.50   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.417688E+09 606.77 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.369936E+09 626.03 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.429752E+09 590.44 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.377953E+09 600.23 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.396323E+09 486.52 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.389439E+09 399.09 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.368830E+09 409.72 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.416018E+09 533.48 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.382685E+09 591.15 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.404588E+09 659.72 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.411300E+09 639.49 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.411480E+09 648.25 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.477599E+10     0.234351E+11    
Minimum of Months 0.368830E+09 399.09   0.178514E+10 1392.33  
Maximum of Months 0.429752E+09 659.72   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.662584E+09 928.78 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.580604E+09 964.40 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.667805E+09 880.47 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.584672E+09 908.27 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.610774E+09 629.21 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.600119E+09 545.86 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.568736E+09 608.79 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.642593E+09 632.59 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.591463E+09 877.73 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.629910E+09 1015.43 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.652117E+09 970.14 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.655711E+09 1006.51 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.744709E+10     0.363654E+11    
Minimum of Months 0.568736E+09 545.86   0.277008E+10 2160.55  
Maximum of Months 0.667805E+09 1015.43   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.420812E+09 554.50 31-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.370334E+09 593.24 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.427241E+09 516.98 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.376092E+09 556.58 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.395693E+09 393.26 23-MAY-07:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.389958E+09 351.77 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.368277E+09 351.77 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.414513E+09 390.50 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.380295E+09 513.70 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.403201E+09 635.63 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.415791E+09 632.08 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.417428E+09 636.41 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.477964E+10     0.234352E+11    
Minimum of Months 0.368277E+09 351.77   0.178515E+10 1392.34  
Maximum of Months 0.427241E+09 636.41   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.639084E+09 897.30 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.568102E+09 944.70 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.662566E+09 869.70 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.586251E+09 912.46 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.616217E+09 634.10 23-MAY-07:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.607005E+09 588.32 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.573497E+09 623.20 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.645173E+09 638.54 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.590332E+09 874.51 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.623279E+09 1007.22 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.631527E+09 939.19 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.631126E+09 994.96 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.737416E+10     0.363660E+11    
Minimum of Months 0.568102E+09 588.32   0.277013E+10 2160.58  
Maximum of Months 0.662566E+09 1007.22   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.417651E+09 606.51 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.369924E+09 625.80 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.429736E+09 590.15 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.377928E+09 599.95 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.396307E+09 486.10 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.389429E+09 398.99 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.368797E+09 409.63 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.415992E+09 533.21 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.382663E+09 590.85 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.404567E+09 659.56 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.411287E+09 639.30 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.411461E+09 648.06 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.477574E+10     0.234351E+11    
Minimum of Months 0.368797E+09 398.99   0.178514E+10 1392.33  
Maximum of Months 0.429736E+09 659.56   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.139824E+09 146.32 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.126830E+09 146.32 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.150710E+09 146.32 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.134615E+09 146.32 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.145267E+09 146.32 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.144564E+09 146.32 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.135317E+09 146.32 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.150710E+09 146.32 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.134615E+09 146.32 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.139824E+09 146.32 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.138185E+09 146.32 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.135317E+09 146.32 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.167578E+10     0.153881E+12    
Minimum of Months 0.126830E+09 146.32   0.505780E+10 1948.61  
Maximum of Months 0.150710E+09 146.32   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.139824E+09 146.32 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.126830E+09 146.32 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.150710E+09 146.32 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.134615E+09 146.32 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.145267E+09 146.32 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.144564E+09 146.32 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.135317E+09 146.32 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.150710E+09 146.32 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.134615E+09 146.32 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.139824E+09 146.32 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.138185E+09 146.32 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.135317E+09 146.32 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.167578E+10     0.153881E+12    
Minimum of Months 0.126830E+09 146.32   0.505780E+10 1948.61  
Maximum of Months 0.150710E+09 146.32   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.139824E+09 146.32 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.126830E+09 146.32 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.150710E+09 146.32 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.134615E+09 146.32 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.145267E+09 146.32 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.144564E+09 146.32 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.135317E+09 146.32 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.150710E+09 146.32 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.134615E+09 146.32 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.139824E+09 146.32 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.138185E+09 146.32 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.135317E+09 146.32 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.167578E+10     0.153881E+12    
Minimum of Months 0.126830E+09 146.32   0.505780E+10 1948.61  
Maximum of Months 0.150710E+09 146.32   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.274130E+10 2868.67 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.248656E+10 2868.67 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.295472E+10 2868.67 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.263917E+10 2868.67 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.284801E+10 2868.67 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.283424E+10 2868.67 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.265294E+10 2868.67 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.295472E+10 2868.67 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.263917E+10 2868.67 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.274130E+10 2868.67 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.270917E+10 2868.67 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.265294E+10 2868.67 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.328542E+11     0.749486E+13    
Minimum of Months 0.248656E+10 2868.67   0.246344E+12 94908.13  
Maximum of Months 0.295472E+10 2868.67   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.968216E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.878253E+10 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.104353E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.932187E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.100587E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.100099E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.937071E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.104353E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.932187E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.968216E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.956821E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.937071E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.116039E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.878253E+10 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.104353E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.869526E+10 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.937162E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.837170E+10 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.903344E+10 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.898958E+10 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.841555E+10 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.937162E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.837170E+10 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.869526E+10 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.859292E+10 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.841555E+10 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.104212E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.937162E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.869526E+10 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.837170E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.903344E+10 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.898958E+10 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.841555E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.837170E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.869526E+10 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.859292E+10 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.841555E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.104212E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.869526E+10 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.837170E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.903344E+10 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.898958E+10 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.841555E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.837170E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.869526E+10 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.859292E+10 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.841555E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.104212E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.788732E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.937162E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.664968E+09 0.305979E+10 0.00 0.00 0.00 0.00 1017678.85 0.366520E+09
February 0.136985E+10 0.582070E+09 0.277008E+10 0.00 0.00 0.00 0.00 1955978.84 0.285251E+09
March 0.163685E+10 0.669166E+09 0.318369E+10 0.00 0.00 0.00 0.00 5989378.11 0.298898E+09
April 0.145243E+10 0.585341E+09 0.295462E+10 0.00 0.00 0.00 0.00 12926596.54 0.124626E+09
May 0.157338E+10 0.611318E+09 0.312174E+10 0.00 0.00 0.00 0.00 55196529.58 18111891.91
June 0.156900E+10 0.600969E+09 0.306580E+10 0.00 0.00 0.00 0.00 52355288.17 11019401.04
July 0.145680E+10 0.569095E+09 0.300989E+10 0.00 0.00 0.00 0.00 76858743.32 1616113.15
August 0.163685E+10 0.643095E+09 0.318369E+10 0.00 0.00 0.00 0.00 73325234.28 9333660.43
September 0.145243E+10 0.592374E+09 0.295328E+10 0.00 0.00 0.00 0.00 62536722.16 30968487.71
October 0.150991E+10 0.630880E+09 0.306046E+10 0.00 0.00 0.00 0.00 50501593.55 0.104901E+09
November 0.149516E+10 0.654186E+09 0.299314E+10 0.00 0.00 0.00 0.00 5239227.71 0.190293E+09
December 0.145680E+10 0.657998E+09 0.300922E+10 0.00 0.00 0.00 0.00 3380708.72 0.334836E+09
                   
Annual Sum or Average 0.181194E+11 0.746146E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.401284E+09 0.177637E+10
Minimum of Months 0.136985E+10 0.569095E+09 0.277008E+10 0.00 0.00 0.00 0.00 1017678.85 1616113.15
Maximum of Months 0.163685E+10 0.669166E+09 0.318369E+10 0.00 0.00 0.00 0.00 76858743.32 0.366520E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.421632E+09 0.197184E+10 0.00 0.00 0.00 0.00 530162.73 0.252445E+09
February 0.882782E+09 0.371000E+09 0.178515E+10 0.00 0.00 0.00 0.00 1111995.45 0.194692E+09
March 0.105485E+10 0.427704E+09 0.205169E+10 0.00 0.00 0.00 0.00 3353399.07 0.199822E+09
April 0.936002E+09 0.376432E+09 0.190407E+10 0.00 0.00 0.00 0.00 8311668.47 82609729.80
May 0.101394E+10 0.396067E+09 0.201177E+10 0.00 0.00 0.00 0.00 35052840.37 12354876.77
June 0.101113E+10 0.390235E+09 0.197572E+10 0.00 0.00 0.00 0.00 34590155.34 6887753.31
July 0.938820E+09 0.368669E+09 0.193969E+10 0.00 0.00 0.00 0.00 51241512.61 1017315.57
August 0.105485E+10 0.414822E+09 0.205169E+10 0.00 0.00 0.00 0.00 50647392.85 4691669.00
September 0.936002E+09 0.380730E+09 0.190321E+10 0.00 0.00 0.00 0.00 39009136.84 20630850.82
October 0.973041E+09 0.403613E+09 0.197228E+10 0.00 0.00 0.00 0.00 31279623.46 70376181.39
November 0.963541E+09 0.416522E+09 0.192889E+10 0.00 0.00 0.00 0.00 3102183.00 0.128399E+09
December 0.938820E+09 0.418287E+09 0.193926E+10 0.00 0.00 0.00 0.00 2045118.04 0.219742E+09
                   
Annual Sum or Average 0.116768E+11 0.478571E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.260275E+09 0.119367E+10
Minimum of Months 0.882782E+09 0.368669E+09 0.178515E+10 0.00 0.00 0.00 0.00 530162.73 1017315.57
Maximum of Months 0.105485E+10 0.427704E+09 0.205169E+10 0.00 0.00 0.00 0.00 51241512.61 0.252445E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.639397E+09 0.305983E+10 0.00 0.00 0.00 0.00 572682.71 0.395615E+09
February 0.136988E+10 0.568375E+09 0.277013E+10 0.00 0.00 0.00 0.00 1473897.49 0.303534E+09
March 0.163688E+10 0.663304E+09 0.318374E+10 0.00 0.00 0.00 0.00 4586439.13 0.304101E+09
April 0.145246E+10 0.586845E+09 0.295467E+10 0.00 0.00 0.00 0.00 11691947.03 0.128504E+09
May 0.157341E+10 0.616885E+09 0.312179E+10 0.00 0.00 0.00 0.00 55112730.10 17924776.37
June 0.156904E+10 0.607661E+09 0.306585E+10 0.00 0.00 0.00 0.00 53035104.78 10656145.03
July 0.145684E+10 0.574045E+09 0.300994E+10 0.00 0.00 0.00 0.00 76723355.69 1667860.10
August 0.163688E+10 0.645744E+09 0.318374E+10 0.00 0.00 0.00 0.00 71505916.18 9962694.90
September 0.145246E+10 0.590925E+09 0.295333E+10 0.00 0.00 0.00 0.00 57385499.50 33931949.58
October 0.150994E+10 0.623797E+09 0.306051E+10 0.00 0.00 0.00 0.00 41939220.86 0.120163E+09
November 0.149520E+10 0.632431E+09 0.299318E+10 0.00 0.00 0.00 0.00 3935777.96 0.207800E+09
December 0.145684E+10 0.631727E+09 0.300927E+10 0.00 0.00 0.00 0.00 2551605.33 0.356048E+09
                   
Annual Sum or Average 0.181198E+11 0.738114E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.380514E+09 0.188991E+10
Minimum of Months 0.136988E+10 0.568375E+09 0.277013E+10 0.00 0.00 0.00 0.00 572682.71 1667860.10
Maximum of Months 0.163688E+10 0.663304E+09 0.318374E+10 0.00 0.00 0.00 0.00 76723355.69 0.395615E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.418287E+09 0.197183E+10 0.00 0.00 0.00 0.00 441447.90 0.274619E+09
February 0.882782E+09 0.370477E+09 0.178514E+10 0.00 0.00 0.00 0.00 1010356.95 0.219033E+09
March 0.105485E+10 0.430478E+09 0.205168E+10 0.00 0.00 0.00 0.00 3062232.83 0.237069E+09
April 0.936002E+09 0.378493E+09 0.190406E+10 0.00 0.00 0.00 0.00 6822950.17 0.112922E+09
May 0.101394E+10 0.396849E+09 0.201175E+10 0.00 0.00 0.00 0.00 31959522.91 21476617.73
June 0.101113E+10 0.389823E+09 0.197570E+10 0.00 0.00 0.00 0.00 29092643.09 15465915.85
July 0.938820E+09 0.369330E+09 0.193968E+10 0.00 0.00 0.00 0.00 38816561.88 7237325.10
August 0.105485E+10 0.416566E+09 0.205168E+10 0.00 0.00 0.00 0.00 39257147.42 21483590.54
September 0.936002E+09 0.383350E+09 0.190319E+10 0.00 0.00 0.00 0.00 35124402.49 32320448.47
October 0.973041E+09 0.405140E+09 0.197226E+10 0.00 0.00 0.00 0.00 27284271.39 97701412.51
November 0.963541E+09 0.411929E+09 0.192888E+10 0.00 0.00 0.00 0.00 2747347.70 0.154507E+09
December 0.938820E+09 0.412200E+09 0.193924E+10 0.00 0.00 0.00 0.00 1775951.06 0.271164E+09
                   
Annual Sum or Average 0.116768E+11 0.478292E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.217395E+09 0.146500E+10
Minimum of Months 0.882782E+09 0.369330E+09 0.178514E+10 0.00 0.00 0.00 0.00 441447.90 7237325.10
Maximum of Months 0.105485E+10 0.430478E+09 0.205168E+10 0.00 0.00 0.00 0.00 39257147.42 0.274619E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.662709E+09 0.305979E+10 0.00 0.00 0.00 0.00 5672474.40 0.721986E+09
February 0.136985E+10 0.580637E+09 0.277008E+10 0.00 0.00 0.00 0.00 6764732.34 0.556178E+09
March 0.163685E+10 0.667836E+09 0.318369E+10 0.00 0.00 0.00 0.00 18333120.25 0.599993E+09
April 0.145243E+10 0.584690E+09 0.295462E+10 0.00 0.00 0.00 0.00 29968170.85 0.270234E+09
May 0.157338E+10 0.610808E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.123380E+09 43734540.92
June 0.156900E+10 0.600154E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.112381E+09 34085559.77
July 0.145680E+10 0.568752E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.158406E+09 12572914.99
August 0.163685E+10 0.642612E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.154390E+09 43517296.18
September 0.145243E+10 0.591506E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.143172E+09 68312547.65
October 0.150991E+10 0.629940E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.116356E+09 0.228093E+09
November 0.149516E+10 0.652202E+09 0.299314E+10 0.00 0.00 0.00 0.00 15675970.14 0.375910E+09
December 0.145680E+10 0.655760E+09 0.300922E+10 0.00 0.00 0.00 0.00 10796287.88 0.648536E+09
                   
Annual Sum or Average 0.181194E+11 0.744761E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.895297E+09 0.360315E+10
Minimum of Months 0.136985E+10 0.568752E+09 0.277008E+10 0.00 0.00 0.00 0.00 5672474.40 12572914.99
Maximum of Months 0.163685E+10 0.667836E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.158406E+09 0.721986E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.420825E+09 0.197184E+10 0.00 0.00 0.00 0.00 1321654.53 0.528862E+09
February 0.649041E+09 0.370357E+09 0.178515E+10 0.00 0.00 0.00 0.00 2419560.47 0.408122E+09
March 0.773965E+09 0.427254E+09 0.205169E+10 0.00 0.00 0.00 0.00 6918912.07 0.437004E+09
April 0.688021E+09 0.376102E+09 0.190407E+10 0.00 0.00 0.00 0.00 16577179.39 0.203022E+09
May 0.744847E+09 0.395720E+09 0.201177E+10 0.00 0.00 0.00 0.00 73457914.87 34847198.96
June 0.742030E+09 0.389980E+09 0.197572E+10 0.00 0.00 0.00 0.00 69795559.27 25807124.42
July 0.690839E+09 0.368305E+09 0.193969E+10 0.00 0.00 0.00 0.00 95539581.71 11563599.41
August 0.773965E+09 0.414527E+09 0.205169E+10 0.00 0.00 0.00 0.00 95040955.71 33031064.94
September 0.688021E+09 0.380313E+09 0.190321E+10 0.00 0.00 0.00 0.00 83407068.88 52365264.99
October 0.715730E+09 0.403213E+09 0.197228E+10 0.00 0.00 0.00 0.00 64975772.10 0.171167E+09
November 0.708685E+09 0.415832E+09 0.192889E+10 0.00 0.00 0.00 0.00 6414359.75 0.281037E+09
December 0.690839E+09 0.417458E+09 0.193926E+10 0.00 0.00 0.00 0.00 4202210.66 0.465716E+09
                   
Annual Sum or Average 0.858171E+10 0.477989E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.520071E+09 0.265254E+10
Minimum of Months 0.649041E+09 0.368305E+09 0.178515E+10 0.00 0.00 0.00 0.00 1321654.53 11563599.41
Maximum of Months 0.773965E+09 0.427254E+09 0.205169E+10 0.00 0.00 0.00 0.00 95539581.71 0.528862E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.639091E+09 0.305983E+10 0.00 0.00 0.00 0.00 1001078.36 0.887429E+09
February 0.136988E+10 0.568114E+09 0.277013E+10 0.00 0.00 0.00 0.00 3103848.22 0.672916E+09
March 0.163688E+10 0.662588E+09 0.318374E+10 0.00 0.00 0.00 0.00 10128293.32 0.664419E+09
April 0.145246E+10 0.586270E+09 0.295467E+10 0.00 0.00 0.00 0.00 26294904.78 0.297290E+09
May 0.157341E+10 0.616241E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.123120E+09 44364647.33
June 0.156904E+10 0.607062E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.115106E+09 32455738.56
July 0.145684E+10 0.573522E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.159753E+09 12379377.95
August 0.163688E+10 0.645201E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.149776E+09 46557321.67
September 0.145246E+10 0.590352E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.127663E+09 81368599.19
October 0.150994E+10 0.623305E+09 0.306051E+10 0.00 0.00 0.00 0.00 91760258.93 0.295240E+09
November 0.149520E+10 0.631540E+09 0.299318E+10 0.00 0.00 0.00 0.00 8524404.13 0.468752E+09
December 0.145684E+10 0.631143E+09 0.300927E+10 0.00 0.00 0.00 0.00 5525931.59 0.792428E+09
                   
Annual Sum or Average 0.181198E+11 0.737443E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.821757E+09 0.429560E+10
Minimum of Months 0.136988E+10 0.568114E+09 0.277013E+10 0.00 0.00 0.00 0.00 1001078.36 12379377.95
Maximum of Months 0.163688E+10 0.662588E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.159753E+09 0.887429E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.417688E+09 0.197183E+10 0.00 0.00 0.00 0.00 1489433.05 0.547138E+09
February 0.882782E+09 0.369936E+09 0.178514E+10 0.00 0.00 0.00 0.00 2662210.62 0.421821E+09
March 0.105485E+10 0.429752E+09 0.205168E+10 0.00 0.00 0.00 0.00 8544853.04 0.451440E+09
April 0.936002E+09 0.377953E+09 0.190406E+10 0.00 0.00 0.00 0.00 15811264.96 0.223137E+09
May 0.101394E+10 0.396323E+09 0.201175E+10 0.00 0.00 0.00 0.00 75143142.73 42077901.01
June 0.101113E+10 0.389439E+09 0.197570E+10 0.00 0.00 0.00 0.00 67747905.51 33480398.56
July 0.938820E+09 0.368830E+09 0.193968E+10 0.00 0.00 0.00 0.00 92078845.64 17483313.04
August 0.105485E+10 0.416018E+09 0.205168E+10 0.00 0.00 0.00 0.00 92958774.41 44613359.05
September 0.936002E+09 0.382685E+09 0.190319E+10 0.00 0.00 0.00 0.00 81695695.90 63616690.03
October 0.973041E+09 0.404588E+09 0.197226E+10 0.00 0.00 0.00 0.00 65293309.07 0.195228E+09
November 0.963541E+09 0.411300E+09 0.192888E+10 0.00 0.00 0.00 0.00 7196301.02 0.290983E+09
December 0.938820E+09 0.411480E+09 0.193924E+10 0.00 0.00 0.00 0.00 4783287.51 0.496635E+09
                   
Annual Sum or Average 0.116768E+11 0.477599E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.515405E+09 0.282765E+10
Minimum of Months 0.882782E+09 0.368830E+09 0.178514E+10 0.00 0.00 0.00 0.00 1489433.05 17483313.04
Maximum of Months 0.105485E+10 0.429752E+09 0.205168E+10 0.00 0.00 0.00 0.00 92958774.41 0.547138E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.662584E+09 0.305979E+10 0.00 0.00 0.00 0.00 8578720.40 0.811669E+09
February 0.136985E+10 0.580604E+09 0.277008E+10 0.00 0.00 0.00 0.00 8696212.69 0.623213E+09
March 0.163685E+10 0.667805E+09 0.318369E+10 0.00 0.00 0.00 0.00 21518704.73 0.692690E+09
April 0.145243E+10 0.584672E+09 0.295462E+10 0.00 0.00 0.00 0.00 33556241.63 0.325608E+09
May 0.157338E+10 0.610774E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.142281E+09 61591494.12
June 0.156900E+10 0.600119E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.130225E+09 47752732.92
July 0.145680E+10 0.568736E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.179630E+09 20223538.56
August 0.163685E+10 0.642593E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.179353E+09 60485317.32
September 0.145243E+10 0.591463E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.162411E+09 91055199.89
October 0.150991E+10 0.629910E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.131341E+09 0.272089E+09
November 0.149516E+10 0.652117E+09 0.299314E+10 0.00 0.00 0.00 0.00 20147134.63 0.424369E+09
December 0.145680E+10 0.655711E+09 0.300922E+10 0.00 0.00 0.00 0.00 14676828.70 0.734186E+09
                   
Annual Sum or Average 0.181194E+11 0.744709E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.103241E+10 0.416493E+10
Minimum of Months 0.136985E+10 0.568736E+09 0.277008E+10 0.00 0.00 0.00 0.00 8578720.40 20223538.56
Maximum of Months 0.163685E+10 0.667805E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.179630E+09 0.811669E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.420812E+09 0.197184E+10 0.00 0.00 0.00 0.00 2219598.40 0.589618E+09
February 0.882782E+09 0.370334E+09 0.178515E+10 0.00 0.00 0.00 0.00 3220725.91 0.454103E+09
March 0.105485E+10 0.427241E+09 0.205169E+10 0.00 0.00 0.00 0.00 8626522.46 0.506801E+09
April 0.936002E+09 0.376092E+09 0.190407E+10 0.00 0.00 0.00 0.00 19930711.26 0.245751E+09
May 0.101394E+10 0.395693E+09 0.201177E+10 0.00 0.00 0.00 0.00 88067589.50 47873476.49
June 0.101113E+10 0.389958E+09 0.197572E+10 0.00 0.00 0.00 0.00 83619796.78 35434792.44
July 0.938820E+09 0.368277E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.112522E+09 17314325.05
August 0.105485E+10 0.414513E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.114020E+09 44914884.49
September 0.936002E+09 0.380295E+09 0.190321E+10 0.00 0.00 0.00 0.00 99366346.33 68554008.76
October 0.973041E+09 0.403201E+09 0.197228E+10 0.00 0.00 0.00 0.00 77580366.77 0.204533E+09
November 0.963541E+09 0.415791E+09 0.192889E+10 0.00 0.00 0.00 0.00 8102101.59 0.321764E+09
December 0.938820E+09 0.417428E+09 0.193926E+10 0.00 0.00 0.00 0.00 5729348.03 0.524203E+09
                   
Annual Sum or Average 0.116768E+11 0.477964E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.623005E+09 0.306086E+10
Minimum of Months 0.882782E+09 0.368277E+09 0.178515E+10 0.00 0.00 0.00 0.00 2219598.40 17314325.05
Maximum of Months 0.105485E+10 0.427241E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.114020E+09 0.589618E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.639084E+09 0.305983E+10 0.00 0.00 0.00 0.00 1230957.17 0.102150E+10
February 0.136988E+10 0.568102E+09 0.277013E+10 0.00 0.00 0.00 0.00 3705614.66 0.763299E+09
March 0.163688E+10 0.662566E+09 0.318374E+10 0.00 0.00 0.00 0.00 11712300.15 0.773976E+09
April 0.145246E+10 0.586251E+09 0.295467E+10 0.00 0.00 0.00 0.00 30138777.03 0.360046E+09
May 0.157341E+10 0.616217E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.142347E+09 62378965.26
June 0.156904E+10 0.607005E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.132962E+09 45650885.17
July 0.145684E+10 0.573497E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.181750E+09 19864674.75
August 0.163688E+10 0.645173E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.175612E+09 64411570.39
September 0.145246E+10 0.590332E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.149655E+09 0.107346E+09
October 0.150994E+10 0.623279E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.108920E+09 0.359012E+09
November 0.149520E+10 0.631527E+09 0.299318E+10 0.00 0.00 0.00 0.00 10519788.35 0.549958E+09
December 0.145684E+10 0.631126E+09 0.300927E+10 0.00 0.00 0.00 0.00 6771825.34 0.914847E+09
                   
Annual Sum or Average 0.181198E+11 0.737416E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.955325E+09 0.504229E+10
Minimum of Months 0.136988E+10 0.568102E+09 0.277013E+10 0.00 0.00 0.00 0.00 1230957.17 19864674.75
Maximum of Months 0.163688E+10 0.662566E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.181750E+09 0.102150E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.417651E+09 0.197183E+10 0.00 0.00 0.00 0.00 1966642.11 0.630485E+09
February 0.882782E+09 0.369924E+09 0.178514E+10 0.00 0.00 0.00 0.00 3153906.03 0.482657E+09
March 0.105485E+10 0.429736E+09 0.205168E+10 0.00 0.00 0.00 0.00 10178122.71 0.529854E+09
April 0.936002E+09 0.377928E+09 0.190406E+10 0.00 0.00 0.00 0.00 18634823.54 0.270763E+09
May 0.101394E+10 0.396307E+09 0.201175E+10 0.00 0.00 0.00 0.00 88716823.79 56644607.09
June 0.101113E+10 0.389429E+09 0.197570E+10 0.00 0.00 0.00 0.00 80945033.52 44585006.96
July 0.938820E+09 0.368797E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.108687E+09 24324889.56
August 0.105485E+10 0.415992E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.110859E+09 59370071.70
September 0.936002E+09 0.382663E+09 0.190319E+10 0.00 0.00 0.00 0.00 97007590.88 82131368.73
October 0.973041E+09 0.404567E+09 0.197226E+10 0.00 0.00 0.00 0.00 76772389.65 0.236318E+09
November 0.963541E+09 0.411287E+09 0.192888E+10 0.00 0.00 0.00 0.00 8845660.45 0.338583E+09
December 0.938820E+09 0.411461E+09 0.193924E+10 0.00 0.00 0.00 0.00 6052310.87 0.574080E+09
                   
Annual Sum or Average 0.116768E+11 0.477574E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.611820E+09 0.332980E+10
Minimum of Months 0.882782E+09 0.368797E+09 0.178514E+10 0.00 0.00 0.00 0.00 1966642.11 24324889.56
Maximum of Months 0.105485E+10 0.429736E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.110859E+09 0.630485E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.139824E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.126830E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.150710E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.134615E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.145267E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.144564E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.135317E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.150710E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.134615E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.139824E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.138185E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.135317E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.167578E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.126830E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.150710E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.139824E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.126830E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.150710E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.134615E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.145267E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.144564E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.135317E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.150710E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.134615E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.139824E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.138185E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.135317E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.167578E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.126830E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.150710E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.139824E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.126830E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.150710E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.134615E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.145267E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.144564E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.135317E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.150710E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.134615E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.139824E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.138185E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.135317E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.167578E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.126830E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.150710E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.274130E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.248656E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.295472E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.263917E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.284801E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.283424E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.265294E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.295472E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.263917E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.274130E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.270917E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.265294E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.328542E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.248656E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.295472E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 801688.05 0.821786E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2116564.36 0.636444E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8479388.39 0.657571E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20015053.92 0.283203E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 97668743.31 34546197.64
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91400264.80 26412422.75
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.138982E+09 6574843.51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124768E+09 32881054.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109971E+09 66702625.68
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84123513.55 0.244763E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7075426.32 0.428436E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4639267.51 0.747607E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.690042E+09 0.398693E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 801688.05 6574843.51
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.138982E+09 0.821786E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3465029.88 0.135427E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6001163.51 0.104942E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21314865.30 0.108916E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38329841.90 0.479379E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.181665E+09 56995619.79
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.165556E+09 47109209.06
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.251660E+09 13024303.67
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.227215E+09 64488031.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.208353E+09 0.107369E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.157009E+09 0.412988E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15265212.27 0.710497E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10328007.20 0.121638E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.128616E+10 0.660108E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3465029.88 13024303.67
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.251660E+09 0.135427E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1777910.39 0.134047E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2082895.63 0.103848E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11081623.04 0.113949E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23199055.79 0.542005E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.153394E+09 75505008.75
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.144612E+09 59572690.17
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.215418E+09 22652887.48
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.207677E+09 82503762.10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.188444E+09 0.127262E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120685E+09 0.444235E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10738213.39 0.716736E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7842796.58 0.121215E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108695E+10 0.680106E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1777910.39 22652887.48
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.215418E+09 0.134047E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 10174.14 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 10174.14 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 10174.14 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 10174.14 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 10174.14 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 10174.14 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 10174.14 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 10174.14 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 10174.14 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 10174.14 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 10174.14 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 10174.14 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   10174.14   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   10174.14   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9137.09 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9137.09 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9137.09 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9137.09 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9137.09 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9137.09 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9137.09 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9137.09 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9137.09 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9137.09 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9137.09 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9137.09 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9137.09   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9137.09   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9137.09 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9137.09 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9137.09 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9137.09 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9137.09 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9137.09 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9137.09 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9137.09 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9137.09 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9137.09 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9137.09 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9137.09 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9137.09 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9137.09 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9137.09 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9137.09 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9137.09 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9137.09 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9137.09 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9137.09 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9137.09 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9137.09 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9137.09 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9137.09 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9137.09   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 931.91 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 51.07 16-JAN-15:00 693.91 09-JAN-05:00
February 2010.79 01-FEB-10:09 966.94 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 49.90 02-FEB-13:00 969.27 05-FEB-08:00
March 2010.79 01-MAR-10:09 884.16 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 102.78 05-MAR-12:50 831.60 20-MAR-22:00
April 2010.79 03-APR-09:09 911.52 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 155.47 29-APR-17:01 505.17 01-APR-21:00
May 2010.79 01-MAY-09:09 633.47 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 218.74 07-MAY-13:52 114.02 14-MAY-12:00
June 2010.79 01-JUN-09:09 545.86 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 267.65 10-JUN-17:02 149.16 06-JUN-22:00
July 2010.79 03-JUL-09:09 614.12 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 241.90 22-JUL-18:50 70.62 30-JUL-10:53
August 2010.79 01-AUG-09:09 636.61 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 333.24 20-AUG-14:00 152.93 25-AUG-23:40
September 2010.79 01-SEP-09:09 881.55 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 329.95 09-SEP-22:53 196.86 05-SEP-02:50
October 2010.79 02-OCT-09:09 1017.23 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 360.88 09-OCT-13:51 410.05 29-OCT-02:00
November 2010.79 01-NOV-09:09 972.76 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 65.83 05-NOV-13:00 593.62 12-NOV-08:00
December 2010.79 01-DEC-10:09 1008.39 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 58.69 10-DEC-14:51 897.15 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   545.86   2160.55   0.00 0.00 0.00 0.00 49.90   70.62  
Maximum of Months 2010.79   1017.23   2160.55   0.00 0.00 0.00 0.00 360.88   969.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 559.07 31-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 23.15 16-JAN-15:00 472.20 22-JAN-08:00
February 1295.83 01-FEB-10:09 596.94 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 33.27 02-FEB-13:00 709.36 05-FEB-10:00
March 1295.83 01-MAR-10:09 521.53 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 53.34 26-MAR-14:00 547.03 20-MAR-22:00
April 1295.83 03-APR-09:09 560.54 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 102.66 29-APR-17:01 325.27 01-APR-21:00
May 1295.83 01-MAY-09:09 396.42 30-MAY-15:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 146.27 21-MAY-14:00 102.08 14-MAY-12:00
June 1295.83 01-JUN-09:09 351.77 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 183.85 10-JUN-17:02 93.22 06-JUN-22:00
July 1295.83 03-JUL-09:09 351.77 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 164.18 22-JUL-18:50 68.93 30-JUL-10:53
August 1295.83 01-AUG-09:09 393.46 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 221.33 20-AUG-14:00 93.57 25-AUG-23:40
September 1295.83 01-SEP-09:09 517.96 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 219.65 09-SEP-22:53 132.29 05-SEP-02:50
October 1295.83 02-OCT-09:09 638.09 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 234.84 09-OCT-14:06 269.67 29-OCT-02:00
November 1295.83 01-NOV-09:09 635.00 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 33.17 05-NOV-13:00 461.24 12-NOV-08:10
December 1295.83 01-DEC-10:09 639.05 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 33.29 10-DEC-14:51 578.10 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   351.77   1392.34   0.00 0.00 0.00 0.00 23.15   68.93  
Maximum of Months 1295.83   639.05   1392.34   0.00 0.00 0.00 0.00 234.84   709.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 900.67 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 15.22 19-JAN-12:10 690.21 26-JAN-03:00
February 2010.83 01-FEB-10:09 947.39 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 49.90 02-FEB-13:00 969.65 05-FEB-10:00
March 2010.83 01-MAR-10:09 873.47 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 69.61 26-MAR-13:55 836.42 20-MAR-22:00
April 2010.83 03-APR-09:09 915.69 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 138.22 29-APR-17:01 507.94 01-APR-21:00
May 2010.83 01-MAY-09:09 638.12 23-MAY-07:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 215.90 21-MAY-14:00 121.43 14-MAY-12:00
June 2010.83 01-JUN-09:09 594.92 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 278.08 10-JUN-17:02 146.96 06-JUN-22:00
July 2010.83 03-JUL-09:09 627.82 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 248.12 22-JUL-18:50 79.40 30-JUL-10:53
August 2010.83 01-AUG-09:09 642.27 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 327.48 20-AUG-14:00 155.08 25-AUG-23:40
September 2010.83 01-SEP-09:09 878.36 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 317.30 09-SEP-22:53 207.25 05-SEP-02:50
October 2010.83 02-OCT-09:09 1009.08 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 328.50 09-OCT-13:44 423.44 29-OCT-02:00
November 2010.83 01-NOV-09:09 941.76 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 34.92 28-NOV-13:00 652.40 12-NOV-08:10
December 2010.83 01-DEC-10:09 996.90 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 36.29 13-DEC-14:00 873.58 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   594.92   2160.58   0.00 0.00 0.00 0.00 15.22   79.40  
Maximum of Months 2010.83   1009.08   2160.58   0.00 0.00 0.00 0.00 328.50   969.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 610.15 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 12.22 19-JAN-12:05 490.02 26-JAN-03:00
February 1295.83 01-FEB-10:09 628.91 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 33.27 02-FEB-13:00 687.29 05-FEB-08:00
March 1295.83 01-MAR-10:09 594.28 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 47.56 26-MAR-13:35 621.37 20-MAR-22:00
April 1295.83 03-APR-09:09 603.80 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 55.47 29-APR-17:10 421.73 01-APR-21:00
May 1295.83 01-MAY-09:09 493.50 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 142.75 21-MAY-13:50 93.36 14-MAY-12:00
June 1295.83 01-JUN-09:09 402.05 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 159.96 10-JUN-17:07 140.17 06-JUN-22:00
July 1295.83 03-JUL-09:09 412.08 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 147.00 02-JUL-11:38 80.87 31-JUL-02:10
August 1295.83 01-AUG-09:09 538.63 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 209.29 20-AUG-14:00 160.64 25-AUG-23:40
September 1295.83 01-SEP-09:09 594.97 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 195.74 09-SEP-17:07 158.21 05-SEP-02:50
October 1295.83 02-OCT-09:09 661.75 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 225.47 09-OCT-14:04 321.34 29-OCT-02:00
November 1295.83 01-NOV-09:09 642.01 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 25.82 07-NOV-13:00 438.40 12-NOV-08:00
December 1295.83 01-DEC-10:09 650.56 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 24.20 13-DEC-14:00 687.52 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   402.05   1392.33   0.00 0.00 0.00 0.00 12.22   80.87  
Maximum of Months 1295.83   661.75   1392.33   0.00 0.00 0.00 0.00 225.47   687.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 929.22 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 194.02 16-JAN-15:00 1402.99 21-JAN-05:53
February 2010.79 01-FEB-10:09 964.77 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 213.23 20-FEB-14:53 1928.45 05-FEB-07:55
March 2010.79 01-MAR-10:09 880.98 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 333.72 05-MAR-12:40 1711.55 20-MAR-22:00
April 2010.79 03-APR-09:09 908.75 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 395.13 29-APR-17:01 1000.03 01-APR-17:53
May 2010.79 01-MAY-09:09 629.38 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 518.40 07-MAY-14:00 251.01 14-MAY-12:00
June 2010.79 01-JUN-09:09 545.86 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 633.24 10-JUN-17:02 300.82 06-JUN-21:20
July 2010.79 03-JUL-09:09 609.00 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 568.42 22-JUL-18:50 199.95 30-JUL-11:00
August 2010.79 01-AUG-09:09 632.75 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 770.85 20-AUG-14:00 432.86 25-AUG-23:55
September 2010.79 01-SEP-09:09 878.25 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 765.71 09-SEP-22:53 425.11 05-SEP-02:53
October 2010.79 02-OCT-09:09 1015.70 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 860.82 09-OCT-14:00 801.20 29-OCT-02:00
November 2010.79 01-NOV-09:09 970.46 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 205.99 05-NOV-13:00 1217.13 12-NOV-06:55
December 2010.79 01-DEC-10:09 1006.81 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 189.34 10-DEC-15:00 1734.97 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   545.86   2160.55   0.00 0.00 0.00 0.00 189.34   199.95  
Maximum of Months 2010.79   1015.70   2160.55   0.00 0.00 0.00 0.00 860.82   1928.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 554.83 31-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 80.85 16-JAN-15:00 936.53 21-JAN-05:53
February 1239.33 01-FEB-08:09 593.51 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 90.50 20-FEB-14:53 1443.95 05-FEB-10:00
March 1239.33 01-MAR-08:09 517.36 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 119.76 26-MAR-14:00 1174.13 20-MAR-22:00
April 1239.33 03-APR-07:10 556.92 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 226.27 29-APR-17:01 705.01 01-APR-17:53
May 1239.33 01-MAY-07:10 393.40 23-MAY-07:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 319.49 21-MAY-13:50 262.29 14-MAY-12:00
June 1239.33 01-JUN-07:10 351.77 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 415.49 10-JUN-17:02 217.17 11-JUN-08:00
July 1239.33 03-JUL-07:10 351.77 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 351.31 22-JUL-18:50 262.67 30-JUL-11:00
August 1239.33 01-AUG-07:10 390.64 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 498.42 20-AUG-14:00 298.48 25-AUG-23:55
September 1239.33 01-SEP-07:10 514.09 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 495.63 09-SEP-22:53 305.25 05-SEP-02:53
October 1239.33 02-OCT-07:10 635.82 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 584.26 09-OCT-13:54 558.80 29-OCT-02:00
November 1239.33 01-NOV-07:10 632.29 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 73.38 05-NOV-13:00 1005.25 12-NOV-08:50
December 1239.33 01-DEC-08:09 636.61 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 82.52 10-DEC-15:00 1171.15 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   351.77   1392.34   0.00 0.00 0.00 0.00 73.38   217.17  
Maximum of Months 1239.33   636.61   1392.34   0.00 0.00 0.00 0.00 584.26   1443.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 897.79 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 28.84 19-JAN-12:00 1637.01 22-JAN-16:55
February 2010.83 01-FEB-10:09 945.10 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 114.06 02-FEB-13:00 2058.38 05-FEB-10:00
March 2010.83 01-MAR-10:09 870.22 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 157.87 26-MAR-13:55 1796.36 20-MAR-22:00
April 2010.83 03-APR-09:09 912.93 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 340.84 29-APR-17:01 1079.12 01-APR-17:53
May 2010.83 01-MAY-09:09 634.26 23-MAY-07:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 495.09 07-MAY-13:52 271.76 14-MAY-12:00
June 2010.83 01-JUN-09:09 588.56 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 658.66 10-JUN-17:02 299.70 06-JUN-21:20
July 2010.83 03-JUL-09:09 623.37 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 587.47 22-JUL-18:50 213.77 30-JUL-11:00
August 2010.83 01-AUG-09:09 638.68 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 761.90 20-AUG-14:00 444.19 25-AUG-23:55
September 2010.83 01-SEP-09:09 875.03 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 729.40 09-SEP-22:53 462.17 05-SEP-02:53
October 2010.83 02-OCT-09:09 1007.50 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 780.91 09-OCT-13:57 926.36 29-OCT-02:00
November 2010.83 01-NOV-09:09 939.58 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 79.83 28-NOV-13:00 1428.53 12-NOV-08:50
December 2010.83 01-DEC-10:09 995.27 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 83.26 13-DEC-14:00 1813.58 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   588.56   2160.58   0.00 0.00 0.00 0.00 28.84   213.77  
Maximum of Months 2010.83   1007.50   2160.58   0.00 0.00 0.00 0.00 780.91   2058.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 606.77 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 56.61 16-JAN-13:40 984.64 22-JAN-16:55
February 1295.83 01-FEB-10:09 626.03 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 76.05 02-FEB-13:00 1323.90 05-FEB-07:55
March 1295.83 01-MAR-10:09 590.44 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 170.78 05-MAR-12:40 1230.72 20-MAR-22:00
April 1295.83 03-APR-09:09 600.23 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 126.51 23-APR-14:54 814.52 01-APR-17:53
May 1295.83 01-MAY-09:09 486.52 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 327.29 21-MAY-13:50 182.92 06-MAY-19:55
June 1295.83 01-JUN-09:09 399.09 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 367.06 10-JUN-17:07 240.24 06-JUN-21:20
July 1295.83 03-JUL-09:09 409.72 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 329.46 02-JUL-11:28 172.01 30-JUL-11:00
August 1295.83 01-AUG-09:09 533.48 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 495.79 20-AUG-14:00 332.02 25-AUG-23:55
September 1295.83 01-SEP-09:09 591.15 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 444.84 09-SEP-17:07 327.56 05-SEP-02:53
October 1295.83 02-OCT-09:09 659.72 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 559.29 09-OCT-13:53 608.28 29-OCT-02:00
November 1295.83 01-NOV-09:09 639.49 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 94.43 05-NOV-12:52 861.40 12-NOV-06:55
December 1295.83 01-DEC-10:09 648.25 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 85.17 10-DEC-10:52 1215.25 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   399.09   1392.33   0.00 0.00 0.00 0.00 56.61   172.01  
Maximum of Months 1295.83   659.72   1392.33   0.00 0.00 0.00 0.00 559.29   1323.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 928.78 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 260.10 15-JAN-14:00 1790.94 21-JAN-06:00
February 2010.79 01-FEB-10:09 964.40 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 291.35 20-FEB-15:00 2289.85 05-FEB-08:00
March 2010.79 01-MAR-10:09 880.47 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 411.29 05-MAR-13:00 1998.75 20-MAR-22:00
April 2010.79 03-APR-09:09 908.27 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 419.17 29-APR-17:01 1227.13 01-APR-17:53
May 2010.79 01-MAY-09:09 629.21 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 597.52 07-MAY-13:52 259.22 14-MAY-11:53
June 2010.79 01-JUN-09:09 545.86 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 714.48 10-JUN-17:02 387.92 06-JUN-21:20
July 2010.79 03-JUL-09:09 608.79 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 612.90 02-JUL-11:48 320.87 30-JUL-11:00
August 2010.79 01-AUG-09:09 632.59 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 887.00 20-AUG-14:00 528.95 25-AUG-23:55
September 2010.79 01-SEP-09:09 877.73 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 890.07 09-SEP-17:02 565.48 05-SEP-02:53
October 2010.79 02-OCT-09:09 1015.43 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 1029.61 09-OCT-13:54 857.03 29-OCT-02:00
November 2010.79 01-NOV-09:09 970.14 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 245.38 05-NOV-12:52 1424.83 12-NOV-06:55
December 2010.79 01-DEC-10:09 1006.51 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 227.04 10-DEC-11:10 1861.38 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   545.86   2160.55   0.00 0.00 0.00 0.00 227.04   259.22  
Maximum of Months 2010.79   1015.43   2160.55   0.00 0.00 0.00 0.00 1029.61   2289.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 554.50 31-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 109.92 16-JAN-15:00 1193.96 21-JAN-06:00
February 1295.83 01-FEB-10:09 593.24 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 134.72 20-FEB-15:00 1526.76 05-FEB-07:55
March 1295.83 01-MAR-10:09 516.98 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 163.32 26-MAR-14:00 1381.54 20-MAR-21:25
April 1295.83 03-APR-09:09 556.58 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 237.37 29-APR-17:01 864.49 01-APR-17:53
May 1295.83 01-MAY-09:09 393.26 23-MAY-07:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 386.47 07-MAY-13:52 275.30 14-MAY-12:10
June 1295.83 01-JUN-09:09 351.77 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 471.59 10-JUN-17:02 278.20 11-JUN-08:00
July 1295.83 03-JUL-09:09 351.77 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 427.38 02-JUL-11:48 354.21 30-JUL-11:00
August 1295.83 01-AUG-09:09 390.50 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 591.32 20-AUG-14:00 363.67 25-AUG-23:55
September 1295.83 01-SEP-09:09 513.70 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 579.51 09-SEP-17:02 398.80 05-SEP-02:53
October 1295.83 02-OCT-09:09 635.63 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 722.49 09-OCT-13:54 600.09 29-OCT-02:00
November 1295.83 01-NOV-09:09 632.08 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 82.51 05-NOV-13:10 1171.05 12-NOV-08:50
December 1295.83 01-DEC-10:09 636.41 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 91.51 10-DEC-15:00 1250.20 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   351.77   1392.34   0.00 0.00 0.00 0.00 82.51   275.30  
Maximum of Months 1295.83   636.41   1392.34   0.00 0.00 0.00 0.00 722.49   1526.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 897.30 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 42.82 19-JAN-12:05 1899.72 22-JAN-16:55
February 2010.83 01-FEB-10:09 944.70 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 137.94 02-FEB-13:00 2290.11 05-FEB-07:55
March 2010.83 01-MAR-10:09 869.70 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 193.22 26-MAR-13:58 2116.33 20-MAR-21:25
April 2010.83 03-APR-09:09 912.46 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 352.18 29-APR-17:01 1329.72 01-APR-17:53
May 2010.83 01-MAY-09:09 634.10 23-MAY-07:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 579.72 07-MAY-13:52 278.28 14-MAY-11:53
June 2010.83 01-JUN-09:09 588.32 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 745.23 10-JUN-17:02 387.54 06-JUN-21:20
July 2010.83 03-JUL-09:09 623.20 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 619.55 02-JUL-11:48 335.97 30-JUL-11:00
August 2010.83 01-AUG-09:09 638.54 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 886.99 20-AUG-14:00 543.21 25-AUG-23:55
September 2010.83 01-SEP-09:09 874.51 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 835.52 09-SEP-22:53 605.00 05-SEP-02:53
October 2010.83 02-OCT-09:09 1007.22 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 944.37 09-OCT-13:57 1025.65 29-OCT-02:00
November 2010.83 01-NOV-09:09 939.19 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 97.59 07-NOV-13:00 1764.01 12-NOV-10:53
December 2010.83 01-DEC-10:09 994.96 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 101.07 13-DEC-14:00 1939.09 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   588.32   2160.58   0.00 0.00 0.00 0.00 42.82   278.28  
Maximum of Months 2010.83   1007.22   2160.58   0.00 0.00 0.00 0.00 944.37   2290.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 606.51 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 78.76 16-JAN-12:50 1194.01 21-JAN-06:00
February 1295.83 01-FEB-10:09 625.80 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 91.96 02-FEB-13:00 1526.64 05-FEB-07:55
March 1295.83 01-MAR-10:09 590.15 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 207.38 05-MAR-12:40 1455.41 20-MAR-21:25
April 1295.83 03-APR-09:09 599.95 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 151.63 23-APR-14:54 999.73 01-APR-17:53
May 1295.83 01-MAY-09:09 486.10 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 386.48 07-MAY-13:52 260.37 06-MAY-19:55
June 1295.83 01-JUN-09:09 398.99 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 438.32 10-JUN-17:07 307.21 06-JUN-21:20
July 1295.83 03-JUL-09:09 409.63 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 423.62 02-JUL-11:48 254.47 30-JUL-11:00
August 1295.83 01-AUG-09:09 533.21 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 591.35 20-AUG-14:00 406.63 25-AUG-23:55
September 1295.83 01-SEP-09:09 590.85 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 544.62 09-SEP-17:10 420.67 05-SEP-02:53
October 1295.83 02-OCT-09:09 659.56 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 670.68 09-OCT-13:53 679.64 29-OCT-02:00
November 1295.83 01-NOV-09:09 639.30 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 111.06 11-NOV-11:50 1015.28 12-NOV-06:55
December 1295.83 01-DEC-10:09 648.06 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 106.26 10-DEC-11:30 1332.37 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   398.99   1392.33   0.00 0.00 0.00 0.00 78.76   254.47  
Maximum of Months 1295.83   659.56   1392.33   0.00 0.00 0.00 0.00 670.68   1526.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 146.32 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 146.32 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 146.32 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 146.32 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 146.32 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 146.32 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 146.32 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 146.32 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 146.32 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 146.32 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 146.32 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 146.32 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   146.32   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   146.32   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 146.32 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 146.32 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 146.32 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 146.32 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 146.32 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 146.32 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 146.32 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 146.32 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 146.32 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 146.32 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 146.32 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 146.32 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   146.32   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   146.32   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 146.32 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 146.32 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 146.32 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 146.32 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 146.32 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 146.32 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 146.32 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 146.32 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 146.32 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 146.32 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 146.32 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 146.32 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   146.32   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   146.32   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 2868.67 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 2868.67 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 2868.67 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 2868.67 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 2868.67 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 2868.67 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 2868.67 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 2868.67 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 2868.67 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 2868.67 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 2868.67 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 2868.67 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   2868.67   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   2868.67   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68.42 16-JAN-15:00 1511.05 26-JAN-03:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.30 02-FEB-13:00 2182.52 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 188.83 26-MAR-14:00 1840.75 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 296.48 29-APR-17:01 1073.82 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 479.72 21-MAY-14:00 174.87 14-MAY-12:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 579.44 10-JUN-17:02 281.78 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 496.46 22-JUL-18:53 112.44 31-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 690.12 20-AUG-14:00 390.65 25-AUG-23:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 656.56 09-SEP-17:02 375.17 05-SEP-02:57
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 749.23 09-OCT-13:51 903.16 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.97 05-NOV-13:00 1280.14 12-NOV-08:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 92.41 10-DEC-14:51 2018.14 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68.42   112.44  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 749.23   2182.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 214.91 16-JAN-15:00 2601.76 21-JAN-05:53
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 225.42 20-FEB-14:53 3732.14 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 430.05 05-MAR-13:00 3142.45 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 579.09 29-APR-17:01 1784.38 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 889.75 21-MAY-14:00 290.59 14-MAY-12:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1071.42 10-JUN-17:02 479.39 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 943.99 22-JUL-18:53 204.40 31-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1270.89 20-AUG-14:00 721.64 25-AUG-23:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1207.02 09-SEP-17:02 599.26 05-SEP-02:53
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1376.03 09-OCT-14:00 1521.96 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 220.61 05-NOV-13:00 2188.96 12-NOV-08:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.25 10-DEC-15:00 3400.77 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 214.91   204.40  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1376.03   3732.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 187.39 16-JAN-15:00 2571.53 21-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130.78 02-FEB-13:00 3368.91 05-FEB-08:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 313.81 05-MAR-12:55 3290.77 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 384.45 29-APR-17:01 1997.56 01-APR-17:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 693.90 07-MAY-14:00 583.47 14-MAY-11:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 968.72 10-JUN-17:02 504.58 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 729.14 02-JUL-10:53 569.49 30-JUL-11:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1150.37 20-AUG-14:00 788.33 25-AUG-23:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1323.45 09-SEP-22:53 789.72 05-SEP-02:53
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 947.95 08-OCT-14:00 1411.41 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 150.09 05-NOV-12:52 2259.37 12-NOV-06:55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 136.87 10-DEC-15:00 3133.40 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130.78   504.58  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1323.45   3368.91  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 100389.24 09-JAN-05:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
February 101761.78 13-FEB-05:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
March 102273.27 20-MAR-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
April 101596.78 17-APR-04:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
May 74422.79 29-MAY-18:50 0.00 2826.07 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 76867.29 12-JUN-03:02 0.00 2826.07 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 73797.60 25-JUL-03:02 0.00 2826.07 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 78181.38 28-AUG-03:02 0.00 3391.28 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
September 76867.75 05-SEP-04:23 0.00 1795.05 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
October 97383.83 17-OCT-04:12 0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 98018.34 14-NOV-05:12 0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
December 100547.99 26-DEC-05:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 73797.60   0.00 1795.05 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 102273.27   0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 84197.76 02-JAN-05:14 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
February 86975.84 27-FEB-05:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
March 82946.94 30-MAR-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
April 82662.20 04-APR-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
May 81174.35 16-MAY-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
June 84051.95 01-JUN-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
July 73687.97 24-JUL-05:03 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
August 75624.07 07-AUG-05:03 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
September 83872.84 22-SEP-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 87354.71 02-OCT-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
November 86186.58 13-NOV-05:11 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
December 85415.91 26-DEC-05:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 73687.97   0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 87354.71   9673.43 3761.52 45884.34 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 71078.18 02-JAN-05:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
February 72117.45 27-FEB-06:04 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 71138.87 29-MAR-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 71652.15 14-APR-05:04 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 70176.17 17-MAY-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
June 72613.14 07-JUN-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 69603.24 12-JUL-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 71846.21 17-AUG-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 71237.92 28-SEP-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
October 72628.96 17-OCT-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
November 72900.24 08-NOV-05:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
December 71060.55 14-DEC-05:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 69603.24   0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 72900.24   8061.19 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 68060.47 02-JAN-06:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
February 67175.00 03-FEB-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 70037.88 27-MAR-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
April 71987.21 26-APR-05:04 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 73320.11 31-MAY-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
June 71597.80 07-JUN-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 70927.33 12-JUL-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 70329.09 26-AUG-04:02 0.00 2538.01 22266.09 0.00 0.00 0.00 0.00 0.00 0.00
September 72365.21 28-SEP-05:04 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
October 71072.37 02-OCT-04:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
November 69603.10 03-NOV-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
December 67472.98 15-DEC-06:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 67175.00   0.00 2149.44 22266.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73320.11   8061.19 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8168.35 02-JAN-06:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 18.75
February 7277.06 27-FEB-05:11 0.00 472.30 5218.93 0.00 0.00 0.00 0.00 0.00 0.00
March 8959.58 27-MAR-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 22.36
April 8901.00 26-APR-14:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 30.69 0.00
May 13839.86 07-MAY-14:42 506.08 151.62 3600.92 0.00 0.00 0.00 0.00 124.56 0.00
June 11852.75 01-JUN-04:12 0.00 404.83 4473.37 0.00 0.00 0.00 0.00 0.00 0.00
July 15188.76 02-JUL-15:32 607.30 181.95 4321.10 0.00 0.00 0.00 0.00 66.76 0.00
August 13978.52 13-AUG-16:22 506.08 151.62 3600.92 0.00 0.00 0.00 0.00 47.77 0.00
September 11970.26 06-SEP-03:02 0.00 318.67 3727.80 0.00 0.00 0.00 0.00 0.00 26.14
October 14901.05 08-OCT-13:01 708.51 212.27 5041.29 0.00 0.00 0.00 0.00 254.39 0.00
November 10947.35 02-NOV-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 1.89
December 7328.47 11-DEC-13:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 10.15 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7277.06   0.00 151.62 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15188.76   1923.11 545.86 5218.93 0.00 0.00 0.00 0.00 254.39 26.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16181.85 01-JAN-10:52 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 82.99
February 11893.63 26-FEB-11:13 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 9.98
March 17576.05 26-MAR-09:32 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 30.35
April 17524.62 23-APR-07:53 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 68.40
May 18963.41 14-MAY-08:42 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 1.38
June 17436.51 04-JUN-09:22 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 30.02 0.00
July 17601.14 09-JUL-09:02 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 55.88 0.00
August 16092.80 06-AUG-09:42 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 32.39 0.00
September 18968.24 24-SEP-09:32 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 10.71 0.00
October 17718.60 15-OCT-08:43 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 105.23
November 17395.89 11-NOV-09:23 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 29.78
December 14330.37 10-DEC-10:22 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 32.34
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11893.63   260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18968.24   391.37 117.25 2784.68 0.00 0.00 0.00 0.00 55.88 105.23



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22906.72 01-JAN-13:31 809.75 242.60 5761.56 0.00 0.00 0.00 0.00 0.00 51.30
February 21347.51 26-FEB-13:52 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 37.86
March 20079.33 05-MAR-13:23 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 7.35 0.00
April 14629.76 23-APR-12:33 303.66 90.98 2160.58 0.00 0.00 0.00 0.00 10.62 0.00
May 18741.38 07-MAY-14:42 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 123.02 0.00
June 13924.72 26-JUN-05:02 1012.19 337.36 4801.30 0.00 0.00 0.00 0.00 0.14 0.00
July 18904.83 02-JUL-15:32 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 71.06 0.00
August 19040.09 27-AUG-12:23 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 113.39 0.00
September 20106.27 03-SEP-13:02 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 66.33 0.00
October 21499.87 15-OCT-13:22 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 33.48 0.00
November 22188.74 11-NOV-13:21 708.53 212.28 5041.36 0.00 0.00 0.00 0.00 0.00 81.54
December 22407.76 10-DEC-12:21 708.53 212.28 5041.36 0.00 0.00 0.00 0.00 0.00 39.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13924.72   303.66 90.98 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22906.72   1012.19 337.36 5761.56 0.00 0.00 0.00 0.00 123.02 81.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 23457.23 01-JAN-15:31 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 0.00 22.57
February 22725.05 26-FEB-15:12 326.14 97.71 2320.55 0.00 0.00 0.00 0.00 0.00 18.84
March 21167.69 26-MAR-15:32 326.14 97.71 2320.55 0.00 0.00 0.00 0.00 0.00 37.50
April 23485.85 23-APR-16:32 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 7.05
May 23471.22 28-MAY-16:31 587.05 175.88 4177.00 0.00 0.00 0.00 0.00 69.49 0.00
June 23512.99 04-JUN-16:02 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 18.84 0.00
July 23627.09 30-JUL-16:52 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 11.00
August 22793.51 06-AUG-16:22 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 36.86
September 24307.61 24-SEP-16:11 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 27.39 0.00
October 22925.95 08-OCT-15:41 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 132.33 0.00
November 23528.68 05-NOV-14:52 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 2.86
December 24523.34 10-DEC-15:01 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 0.00 7.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 21167.69   326.14 97.71 2320.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24523.34   587.05 175.88 4177.00 0.00 0.00 0.00 0.00 132.33 37.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4908.68 02-JAN-13:30 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 16.18 0.00
February 5193.86 28-FEB-15:00 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 24.58 0.00
March 6738.93 30-MAR-13:30 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 50.32 0.00
April 8633.09 29-APR-05:03 809.73 509.88 3840.98 0.00 0.00 0.00 0.00 0.00 13.02
May 11275.05 30-MAY-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 0.00
June 14326.72 11-JUN-17:21 0.00 242.60 4473.37 0.00 0.00 0.00 0.00 237.61 0.00
July 14116.80 04-JUL-16:42 506.08 151.62 3600.92 0.00 0.00 0.00 0.00 284.66 0.00
August 12963.88 21-AUG-03:02 0.00 382.41 4473.37 0.00 0.00 0.00 0.00 16.25 0.00
September 14442.94 10-SEP-14:31 708.51 212.27 5041.29 0.00 0.00 0.00 0.00 280.33 0.00
October 9930.41 10-OCT-04:11 0.00 472.30 5218.93 0.00 0.00 0.00 0.00 0.00 285.44
November 9699.76 03-NOV-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 0.00
December 5619.61 15-DEC-14:05 4021.58 1091.73 4321.10 0.00 0.00 0.00 0.00 44.33 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4908.68   0.00 151.62 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14442.94   4021.58 1091.73 5218.93 0.00 0.00 0.00 0.00 284.66 285.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8515.06 19-JAN-11:05 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 10.60 0.00
February 9231.37 27-FEB-11:05 2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 0.00 14.91
March 17836.15 26-MAR-10:13 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 35.08
April 18533.61 23-APR-09:32 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 56.21
May 20106.58 14-MAY-09:22 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 6.80 0.00
June 18828.40 11-JUN-08:62 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 110.52
July 18585.88 23-JUL-09:42 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 6.53 0.00
August 18309.57 06-AUG-08:32 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 51.82 0.00
September 20105.30 03-SEP-08:52 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 28.36 0.00
October 19702.04 09-OCT-09:12 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 44.15
November 15424.61 11-NOV-10:52 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 26.06
December 10207.59 10-DEC-11:12 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 19.66
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8515.06   260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20106.58   2478.65 703.55 2784.68 0.00 0.00 0.00 0.00 51.82 110.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20323.28 01-JAN-13:42 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 0.00 67.57
February 19568.68 26-FEB-11:32 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 0.00 66.74
March 19280.86 05-MAR-13:53 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 11.95 0.00
April 12629.96 23-APR-13:33 303.66 90.98 2160.58 0.00 0.00 0.00 0.00 58.14 0.00
May 13108.03 03-MAY-04:12 0.00 404.83 4473.43 0.00 0.00 0.00 0.00 0.00 52.90
June 13785.27 26-JUN-05:02 1012.19 337.36 4801.30 0.00 0.00 0.00 0.00 0.29 0.00
July 17241.91 09-JUL-14:12 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 168.75 0.00
August 16842.12 06-AUG-12:32 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 268.90 0.00
September 20133.70 10-SEP-14:31 708.53 212.28 5041.36 0.00 0.00 0.00 0.00 239.45 0.00
October 20776.04 01-OCT-13:42 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 42.69
November 21812.98 11-NOV-13:31 708.53 212.28 5041.36 0.00 0.00 0.00 0.00 0.00 218.22
December 22277.23 10-DEC-13:51 809.75 242.60 5761.56 0.00 0.00 0.00 0.00 0.00 116.66
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12629.96   0.00 90.98 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22277.23   1012.19 404.83 5761.56 0.00 0.00 0.00 0.00 268.90 218.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14119.22 01-JAN-17:03 260.91 78.17 1856.44 0.00 0.00 0.00 0.00 0.00 47.56
February 20154.00 26-FEB-17:32 326.14 97.71 2320.55 0.00 0.00 0.00 0.00 0.00 97.63
March 16030.07 05-MAR-16:32 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 28.66
April 20821.61 16-APR-16:52 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 506.39
May 20437.72 29-MAY-16:12 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 120.18 0.00
June 21899.98 11-JUN-17:21 0.00 156.34 2882.79 0.00 0.00 0.00 0.00 101.27 0.00
July 19729.66 16-JUL-15:52 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 246.12 0.00
August 17528.24 07-AUG-03:02 0.00 246.44 2882.79 0.00 0.00 0.00 0.00 44.49 0.00
September 21837.94 03-SEP-15:31 521.82 156.34 3712.89 0.00 0.00 0.00 0.00 150.34 0.00
October 20927.79 09-OCT-16:31 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 0.00 35.15
November 19972.98 11-NOV-15:32 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 46.00
December 19941.82 10-DEC-15:52 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 15.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 14119.22   0.00 78.17 1856.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21899.98   521.82 246.44 3712.89 0.00 0.00 0.00 0.00 246.12 506.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5117.66 31-JAN-15:00 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 25.21 0.00
February 5572.84 22-FEB-14:30 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 13.81 0.00
March 7208.56 30-MAR-13:30 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 60.95 0.00
April 8901.26 28-APR-15:00 1923.11 545.86 2160.55 0.00 0.00 0.00 0.00 188.11 0.00
May 16588.55 29-MAY-14:42 607.30 181.95 4321.10 0.00 0.00 0.00 0.00 150.64 0.00
June 17046.92 11-JUN-17:21 0.00 242.60 4473.37 0.00 0.00 0.00 0.00 258.28 0.00
July 16579.98 04-JUL-16:42 506.08 151.62 3600.92 0.00 0.00 0.00 0.00 307.86 0.00
August 16307.81 20-AUG-14:12 607.30 181.95 4321.10 0.00 0.00 0.00 0.00 732.71 0.00
September 17234.90 10-SEP-14:31 708.51 212.27 5041.29 0.00 0.00 0.00 0.00 322.22 0.00
October 16837.32 08-OCT-13:01 708.51 212.27 5041.29 0.00 0.00 0.00 0.00 632.36 0.00
November 9477.66 03-NOV-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 0.00
December 6165.33 15-DEC-15:00 2010.79 545.86 2160.55 0.00 0.00 0.00 0.00 64.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5117.66   0.00 151.62 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17234.90   2010.79 545.86 5041.29 0.00 0.00 0.00 0.00 732.71 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6983.78 19-JAN-10:20 1295.83 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 11.53
February 7499.19 27-FEB-10:30 1295.83 351.77 1392.34 0.00 0.00 0.00 0.00 0.00 16.66
March 11706.57 26-MAR-09:13 195.68 58.63 1392.34 0.00 0.00 0.00 0.00 0.00 91.04
April 18817.68 23-APR-09:32 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 73.24
May 21185.53 29-MAY-10:01 456.59 136.80 3248.80 0.00 0.00 0.00 0.00 0.00 1.24
June 19139.94 11-JUN-08:62 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 0.00 143.85
July 19032.38 23-JUL-09:42 326.14 97.71 2320.57 0.00 0.00 0.00 0.00 7.64 0.00
August 18687.05 06-AUG-08:32 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 58.74 0.00
September 20484.99 03-SEP-08:52 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 32.05 0.00
October 20097.43 09-OCT-09:12 391.37 117.25 2784.68 0.00 0.00 0.00 0.00 0.00 72.51
November 11558.52 11-NOV-09:43 195.68 58.63 1392.34 0.00 0.00 0.00 0.00 0.00 90.43
December 6975.23 10-DEC-10:43 260.91 78.17 1856.46 0.00 0.00 0.00 0.00 0.00 70.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6975.23   195.68 58.63 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21185.53   1295.83 351.77 3248.80 0.00 0.00 0.00 0.00 58.74 143.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 24854.72 01-JAN-14:01 809.75 242.60 5761.56 0.00 0.00 0.00 0.00 0.00 136.81
February 23011.79 26-FEB-14:02 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 135.88
March 21161.47 05-MAR-13:53 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 16.54 0.00
April 16370.41 23-APR-13:33 303.66 90.98 2160.58 0.00 0.00 0.00 0.00 56.48 0.00
May 20502.38 29-MAY-14:42 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 151.92 0.00
June 20445.16 11-JUN-16:01 809.75 242.60 5761.56 0.00 0.00 0.00 0.00 162.63 0.00
July 20187.94 09-JUL-14:12 506.09 151.63 3600.97 0.00 0.00 0.00 0.00 180.05 0.00
August 20419.67 27-AUG-12:23 404.87 121.30 2880.78 0.00 0.00 0.00 0.00 307.77 0.00
September 23019.05 10-SEP-14:31 708.53 212.28 5041.36 0.00 0.00 0.00 0.00 274.77 0.00
October 23663.83 08-OCT-13:01 708.53 212.28 5041.36 0.00 0.00 0.00 0.00 366.31 0.00
November 23124.18 05-NOV-13:42 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 91.07
December 22493.87 10-DEC-14:02 607.31 181.95 4321.17 0.00 0.00 0.00 0.00 0.00 63.74
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16370.41   303.66 90.98 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24854.72   809.75 242.60 5761.56 0.00 0.00 0.00 0.00 366.31 136.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21034.49 01-JAN-15:21 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 0.00 58.62
February 22035.62 26-FEB-16:42 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 119.59
March 18307.64 26-MAR-15:13 260.91 78.17 1856.44 0.00 0.00 0.00 0.00 0.00 165.80
April 21535.74 23-APR-16:52 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 0.00 29.50
May 22325.15 29-MAY-16:41 521.82 156.34 3712.89 0.00 0.00 0.00 0.00 111.08 0.00
June 23905.70 11-JUN-17:21 0.00 156.34 2882.79 0.00 0.00 0.00 0.00 110.23 0.00
July 21168.61 16-JUL-15:52 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 285.19 0.00
August 20390.21 20-AUG-16:51 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 157.81 0.00
September 23909.97 03-SEP-15:31 521.82 156.34 3712.89 0.00 0.00 0.00 0.00 162.22 0.00
October 22853.09 01-OCT-15:51 456.59 136.80 3248.78 0.00 0.00 0.00 0.00 0.00 41.44
November 21120.67 05-NOV-15:42 326.14 97.71 2320.55 0.00 0.00 0.00 0.00 0.00 6.56
December 16690.96 10-DEC-15:22 391.37 117.25 2784.67 0.00 0.00 0.00 0.00 18.87 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16690.96   0.00 78.17 1856.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23909.97   521.82 156.34 3712.89 0.00 0.00 0.00 0.00 285.19 165.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11431.37 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.28
February 7259.44 27-FEB-16:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.71
March 6378.88 27-MAR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.79
April 6508.12 24-APR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.08
May 9311.33 30-MAY-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 8859.71 26-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10
July 10723.15 05-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.93 0.00
August 10014.19 21-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.64 0.00
September 10755.25 11-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
October 9638.47 10-OCT-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.60
November 8061.94 06-NOV-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.04
December 6586.65 26-DEC-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 274.93
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6378.88   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11431.37   0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.93 274.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6879.02 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 320.07
February 6252.11 17-FEB-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 287.47
March 4351.55 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 474.04
April 5273.75 28-APR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.93
May 6998.51 03-MAY-12:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71.23 0.00
June 6683.54 27-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.43
July 7066.13 01-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.71
August 5918.43 30-AUG-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 167.67 0.00
September 8166.78 25-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.36
October 7914.22 16-OCT-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.22
November 4710.32 06-NOV-16:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.89 0.00
December 5982.38 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 571.39
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4351.55   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8166.78   0.00 0.00 0.00 0.00 0.00 0.00 0.00 167.67 571.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8976.59 19-JAN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.19
February 11082.53 27-FEB-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.47
March 10702.72 06-MAR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.32 0.00
April 15593.71 28-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 217.30 0.00
May 21132.46 08-MAY-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 217.13 0.00
June 19580.76 08-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 297.72 0.00
July 17655.94 07-JUL-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 116.46 0.00
August 16962.02 03-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 299.52 0.00
September 15626.96 01-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.43 0.00
October 15416.72 05-OCT-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.13 0.00
November 12059.36 02-NOV-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.56 0.00
December 10819.25 15-DEC-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.03 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 8976.59   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21132.46   0.00 0.00 0.00 0.00 0.00 0.00 0.00 299.52 31.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2153.84 01-JAN-17:12 46.77 32.52 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
February 4198.55 26-FEB-17:54 58.46 40.65 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
March 7164.26 31-MAR-24:00 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7989.48 16-APR-18:20 0.00 32.52 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3450.02 31-MAY-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5326.41 30-JUN-24:00 0.00 16.26 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7201.91 31-JUL-23:55 0.00 16.26 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7780.83 06-AUG-18:00 0.00 32.52 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3472.55 30-SEP-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5327.92 31-OCT-24:00 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6014.84 12-NOV-17:10 23.38 16.26 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
December 7881.62 10-DEC-16:53 70.15 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2153.84   0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7989.48   70.15 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1795.43 01-JAN-17:25 46.77 32.52 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
February 3840.77 26-FEB-17:54 58.46 40.65 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
March 6688.59 31-MAR-24:00 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7484.34 16-APR-18:20 0.00 32.52 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3224.12 31-MAY-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5143.36 30-JUN-24:00 0.00 16.26 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 6895.06 31-JUL-24:00 0.00 16.26 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7255.41 06-AUG-17:40 0.00 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3201.26 30-SEP-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4919.07 31-OCT-24:00 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5574.67 06-NOV-17:00 222.14 146.32 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7293.24 15-DEC-17:00 222.14 146.32 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1795.43   0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7484.34   222.14 146.32 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1873.38 01-JAN-17:12 46.77 32.52 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
February 3889.11 26-FEB-17:43 70.15 48.78 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
March 6592.86 31-MAR-24:00 0.00 8.13 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7684.29 23-APR-17:53 0.00 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
May 3196.11 31-MAY-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5179.29 30-JUN-24:00 0.00 16.26 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 6886.20 31-JUL-24:00 0.00 16.26 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7529.91 06-AUG-17:40 0.00 48.78 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3226.95 30-SEP-24:00 0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4850.49 31-OCT-24:00 0.00 8.13 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5634.82 06-NOV-17:00 222.14 146.32 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7357.72 15-DEC-17:00 222.14 146.32 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1873.38   0.00 8.13 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7684.29   222.14 146.32 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92414.33 02-JAN-14:40 5027.92 2868.67 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 182989.29 27-FEB-17:00 4808.68 2868.67 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358132.21 31-MAR-24:00 0.00 159.37 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 367507.40 18-APR-16:05 3037.06 3187.40 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
May 175300.28 31-MAY-24:00 0.00 159.37 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 266915.32 30-JUN-24:00 0.00 318.73 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
July 359206.29 31-JUL-23:55 0.00 318.73 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
August 370273.17 09-AUG-21:14 1265.44 1593.66 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
September 176353.33 30-SEP-24:00 0.00 159.37 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268263.94 31-OCT-24:00 0.00 159.37 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 275826.39 06-NOV-17:00 4808.68 2868.67 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 367285.59 26-DEC-17:00 4808.68 2868.67 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92414.33   0.00 159.37 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 370273.17   5027.92 3187.40 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.140157E+13 1137367.16 19-JAN-16:40 0.844033E+11 420754.96 23-JAN-06:10
February 0.166272E+13 1295279.61 27-FEB-16:49 0.659341E+11 487423.11 06-FEB-06:10
March 0.229342E+13 1435753.91 29-MAR-15:30 0.702644E+11 399917.86 11-MAR-06:10
April 0.271439E+13 1604210.16 28-APR-15:00 0.534248E+11 118006.72 18-APR-14:20
May 0.184330E+13 1248950.56 03-MAY-12:30 0.536083E+11 67295.98 09-MAY-11:20
June 0.222282E+13 1313000.21 28-JUN-15:09 0.506235E+11 64098.75 06-JUN-11:39
July 0.268546E+13 1479149.93 18-JUL-15:30 0.488411E+11 61920.46 03-JUL-11:39
August 0.313650E+13 1628470.72 03-AUG-15:30 0.518580E+11 62569.74 25-AUG-11:20
September 0.178182E+13 1154546.03 01-SEP-15:09 0.497641E+11 64999.44 19-SEP-11:00
October 0.215743E+13 1321211.05 06-OCT-15:09 0.536614E+11 69169.43 25-OCT-11:30
November 0.225740E+13 1436772.08 02-NOV-15:09 0.555800E+11 107843.87 16-NOV-06:10
December 0.260499E+13 1569295.52 14-DEC-16:10 0.739192E+11 444098.91 21-DEC-07:10
             
Annual Sum or Average 0.267618E+14     0.711882E+12    
Minimum of Months 0.140157E+13 1137367.16   0.488411E+11 61920.46  
Maximum of Months 0.313650E+13 1628470.72   0.844033E+11 487423.11  



Table of Contents

Report: EnergyConsumptionElectricityGeneratedPropaneMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ELECTRICITYPRODUCED:FACILITY [J] ELECTRICITYPRODUCED:FACILITY {Maximum} [W] ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} PROPANE:FACILITY [] PROPANE:FACILITY []
January 0.348992E+11 62801.03 23-JAN-12:50 0.00 0.00
February 0.389133E+11 72705.70 13-FEB-12:30 0.00 0.00
March 0.458785E+11 84375.12 22-MAR-12:30 0.00 0.00
April 0.547081E+11 86329.64 10-APR-12:30 0.00 0.00
May 0.530214E+11 83915.95 15-MAY-12:30 0.00 0.00
June 0.562117E+11 84613.62 09-JUN-12:30 0.00 0.00
July 0.546688E+11 79965.54 06-JUL-12:39 0.00 0.00
August 0.516110E+11 80137.75 03-AUG-12:30 0.00 0.00
September 0.433131E+11 74836.43 03-SEP-12:30 0.00 0.00
October 0.429860E+11 71885.92 01-OCT-12:30 0.00 0.00
November 0.348223E+11 64831.49 15-NOV-12:20 0.00 0.00
December 0.316676E+11 57802.88 26-DEC-12:30 0.00 0.00
           
Annual Sum or Average 0.542701E+12     0.00 0.00
Minimum of Months 0.316676E+11 57802.88   0.00 0.00
Maximum of Months 0.562117E+11 86329.64   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY [J]
January 0.144132E+12 0.273830E+11 0.766053E+12 0.102194E+12 0.155049E+12 0.314002E+11 0.00 0.840496E+11 0.410433E+11 0.482065E+11 0.206055E+10 0.00 0.00
February 0.130110E+12 0.228767E+11 0.978954E+12 0.923108E+11 0.142223E+12 0.342773E+11 0.00 0.145159E+12 0.584184E+11 0.559137E+11 0.247811E+10 0.00 0.00
March 0.153910E+12 0.228740E+11 0.141687E+13 0.102362E+12 0.160456E+12 0.417905E+11 0.00 0.233590E+12 0.845625E+11 0.744739E+11 0.252693E+10 0.00 0.00
April 0.137139E+12 0.198050E+11 0.165903E+13 0.988820E+11 0.161678E+12 0.533269E+11 0.00 0.430654E+12 0.130007E+12 0.199018E+11 0.396739E+10 0.00 0.00
May 0.147282E+12 0.183091E+11 0.774844E+12 0.102278E+12 0.181976E+12 0.615864E+11 0.00 0.375555E+12 0.175379E+12 0.00 0.608670E+10 0.00 0.00
June 0.146295E+12 0.166074E+11 0.106252E+13 0.990391E+11 0.180470E+12 0.668417E+11 0.00 0.469603E+12 0.175359E+12 0.00 0.608670E+10 0.00 0.00
July 0.137189E+12 0.178700E+11 0.139340E+13 0.102120E+12 0.182986E+12 0.730666E+11 0.00 0.583960E+12 0.189092E+12 0.00 0.577748E+10 0.00 0.00
August 0.153080E+12 0.195477E+11 0.173200E+13 0.102362E+12 0.189495E+12 0.760738E+11 0.00 0.668553E+12 0.189054E+12 1328817.66 0.633082E+10 0.00 0.00
September 0.137377E+12 0.210774E+11 0.740713E+12 0.988812E+11 0.173386E+12 0.612057E+11 0.00 0.370280E+12 0.173126E+12 0.00 0.577748E+10 0.00 0.00
October 0.143179E+12 0.242140E+11 0.108340E+13 0.102194E+12 0.180843E+12 0.608732E+11 0.00 0.389720E+12 0.152274E+12 0.159977E+11 0.473591E+10 0.00 0.00
November 0.142385E+12 0.257752E+11 0.135889E+13 0.989455E+11 0.160573E+12 0.460388E+11 0.00 0.275286E+12 0.999375E+11 0.471324E+11 0.243079E+10 0.00 0.00
December 0.140028E+12 0.279985E+11 0.170972E+13 0.102120E+12 0.158937E+12 0.394242E+11 0.00 0.263840E+12 0.835968E+11 0.769723E+11 0.235349E+10 0.00 0.00
                           
Annual Sum or Average 0.171211E+13 0.264338E+12 0.146764E+14 0.120369E+13 0.202807E+13 0.645906E+12 0.00 0.429025E+13 0.155185E+13 0.338600E+12 0.506124E+11 0.00 0.00
Minimum of Months 0.130110E+12 0.166074E+11 0.740713E+12 0.923108E+11 0.142223E+12 0.314002E+11 0.00 0.840496E+11 0.410433E+11 0.00 0.206055E+10 0.00 0.00
Maximum of Months 0.153910E+12 0.279985E+11 0.173200E+13 0.102362E+12 0.189495E+12 0.760738E+11 0.00 0.668553E+12 0.189092E+12 0.769723E+11 0.633082E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.255229E+11 0.00 0.588805E+11 0.00 0.00
February 0.00 0.00 0.128096E+11 0.00 0.531245E+11 0.00 0.00
March 0.00 0.00 0.106280E+11 0.00 0.596364E+11 0.00 0.00
April 0.00 0.00 0.239679E+09 0.00 0.531851E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.536083E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.506235E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.488411E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.518580E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.497641E+11 0.00 0.00
October 0.00 0.00 42109672.15 0.00 0.536192E+11 0.00 0.00
November 0.00 0.00 0.898335E+09 0.00 0.546816E+11 0.00 0.00
December 0.00 0.00 0.168595E+11 0.00 0.570597E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.670001E+11 0.00 0.644882E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.488411E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.255229E+11 0.00 0.596364E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 160318.72 31-JAN-08:09 31088.59 01-JAN-06:10 423497.50 02-JAN-08:09 73695.70 31-JAN-08:20 131021.01 19-JAN-16:40 57103.63 19-JAN-16:40 0.00 01-JAN-00:10
February 162006.23 01-FEB-08:09 31088.59 01-FEB-06:10 541788.89 01-FEB-08:09 73696.59 01-FEB-08:20 143288.51 27-FEB-16:49 57350.74 27-FEB-16:49 0.00 01-FEB-00:10
March 158764.49 27-MAR-07:10 31088.59 01-MAR-06:10 660080.29 01-MAR-08:09 73694.89 27-MAR-07:19 113688.48 07-MAR-06:10 50276.81 07-MAR-11:50 0.00 01-MAR-00:10
April 160200.83 14-APR-07:10 31088.59 01-APR-05:10 778371.69 03-APR-07:10 73695.64 14-APR-07:19 145236.34 18-APR-14:20 50702.25 27-APR-10:50 0.00 01-APR-00:10
May 150024.83 23-MAY-07:30 31088.59 01-MAY-05:10 423497.50 01-MAY-07:10 73690.30 23-MAY-07:40 255581.86 03-MAY-12:30 57427.71 08-MAY-13:39 0.00 01-MAY-00:10
June 147076.19 16-JUN-07:10 31088.59 01-JUN-05:10 541788.89 01-JUN-07:10 73688.76 16-JUN-07:19 165597.38 08-JUN-14:30 57261.45 01-JUN-14:30 0.00 01-JUN-00:10
July 148381.65 14-JUL-07:10 31088.59 01-JUL-05:10 660080.29 03-JUL-07:10 73689.44 14-JUL-07:19 126749.37 07-JUL-15:00 50441.00 24-JUL-07:30 0.00 01-JUL-00:10
August 150535.37 21-AUG-07:10 31088.59 01-AUG-05:10 778371.69 01-AUG-07:10 73690.57 21-AUG-07:19 144054.57 15-AUG-10:30 57456.38 15-AUG-10:30 0.00 01-AUG-00:10
September 158758.58 26-SEP-07:10 31088.59 01-SEP-05:10 423497.50 01-SEP-07:10 73694.88 26-SEP-07:19 126906.44 01-SEP-14:00 57490.94 25-SEP-10:39 0.00 01-SEP-00:10
October 164275.09 25-OCT-07:10 31088.59 01-OCT-05:10 541788.89 02-OCT-07:10 73697.78 25-OCT-07:19 135550.30 11-OCT-15:30 57493.23 23-OCT-09:30 0.00 01-OCT-00:10
November 161990.68 21-NOV-16:00 31088.59 01-NOV-05:10 660080.29 01-NOV-07:10 73696.41 01-NOV-07:19 132518.81 06-NOV-16:19 57254.33 29-NOV-16:10 0.00 01-NOV-00:10
December 163894.04 12-DEC-08:09 31088.59 01-DEC-06:10 778371.69 01-DEC-08:09 73697.58 12-DEC-08:20 124324.51 15-DEC-15:30 50666.79 12-DEC-13:39 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 147076.19   31088.59   423497.50   73688.76   113688.48   50276.81   0.00  
Maximum of Months 164275.09   31088.59   778371.69   73697.78   255581.86   57493.23   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY {Maximum} [W] COGENERATION:ELECTRICITY {TIMESTAMP}
January 264276.26 19-JAN-11:00 81663.54 02-JAN-11:30 100000.00 06-JAN-12:00 4520.72 02-JAN-10:09 0.00 0.00 01-JAN-00:10
February 301723.40 24-FEB-10:39 81663.54 01-FEB-13:50 100000.00 04-FEB-17:10 4520.72 01-FEB-11:50 0.00 0.00 01-FEB-00:10
March 349223.40 30-MAR-12:00 81663.54 06-MAR-09:39 100000.00 03-MAR-22:10 4520.72 04-MAR-15:20 0.00 0.00 01-MAR-00:10
April 381769.27 28-APR-11:50 81663.54 04-APR-15:39 100000.00 10-APR-04:19 4520.72 01-APR-06:10 0.00 0.00 01-APR-00:10
May 303897.87 10-MAY-15:00 81663.54 01-MAY-06:19 0.00 01-MAY-00:10 4520.72 01-MAY-06:10 0.00 0.00 01-MAY-00:10
June 329057.00 16-JUN-16:00 81663.54 01-JUN-06:49 0.00 01-JUN-00:10 4520.72 01-JUN-06:10 0.00 0.00 01-JUN-00:10
July 379739.99 05-JUL-12:09 81663.54 01-JUL-06:30 0.00 01-JUL-00:10 4520.72 01-JUL-06:10 0.00 0.00 01-JUL-00:10
August 395912.86 10-AUG-12:09 81663.54 01-AUG-06:19 1230.55 20-AUG-14:09 4520.72 01-AUG-06:10 0.00 0.00 01-AUG-00:10
September 300121.13 01-SEP-12:09 81663.54 01-SEP-06:19 0.00 01-SEP-00:10 4520.72 01-SEP-06:10 0.00 0.00 01-SEP-00:10
October 338325.47 06-OCT-14:09 81663.54 02-OCT-09:39 100000.00 27-OCT-04:30 4520.72 02-OCT-08:50 0.00 0.00 01-OCT-00:10
November 346315.36 02-NOV-13:20 81663.54 01-NOV-06:19 100000.00 09-NOV-05:30 4520.72 01-NOV-06:10 0.00 0.00 01-NOV-00:10
December 377967.77 14-DEC-15:09 81663.54 08-DEC-15:50 100000.00 06-DEC-05:30 4520.72 02-DEC-13:30 0.00 0.00 01-DEC-00:10
                       
Annual Sum or Average                 0.00    
Minimum of Months 264276.26   81663.54   0.00   4520.72   0.00 0.00  
Maximum of Months 395912.86   81663.54   100000.00   4520.72   0.00 0.00  



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1137367.16 19-JAN-16:40 146044.91 423497.50 0.00 52589.61 131021.01 57103.63 0.00 240926.25 81663.54
February 1295279.61 27-FEB-16:49 145987.23 541788.89 0.00 52589.61 143288.51 57350.74 0.00 268090.37 81663.54
March 1435753.91 29-MAR-15:30 145987.23 660080.29 0.00 52589.61 101330.87 48399.70 0.00 341181.96 81663.54
April 1604210.16 28-APR-15:00 145987.23 778371.69 0.00 52589.61 119889.50 47343.40 0.00 373844.49 81663.54
May 1248950.56 03-MAY-12:30 145987.23 423497.50 0.00 24458.17 255581.86 57045.66 0.00 256195.89 81663.54
June 1313000.21 28-JUN-15:09 145987.23 541788.89 0.00 52589.61 119965.66 47395.35 0.00 319089.22 81663.54
July 1479149.93 18-JUL-15:30 145987.23 660080.29 0.00 52589.61 124667.48 47505.09 0.00 362135.98 81663.54
August 1628470.72 03-AUG-15:30 145987.23 778371.69 0.00 52589.61 131212.37 47613.48 0.00 386512.09 81663.54
September 1154546.03 01-SEP-15:09 145987.23 423497.50 0.00 52589.61 125457.29 47425.35 0.00 273404.80 81663.54
October 1321211.05 06-OCT-15:09 145987.23 541788.89 0.00 52589.61 123587.45 47749.30 0.00 323324.31 81663.54
November 1436772.08 02-NOV-15:09 145987.23 660080.29 0.00 52589.61 118477.80 47155.39 0.00 326297.52 81663.54
December 1569295.52 14-DEC-16:10 146638.83 778371.69 0.00 52589.61 105980.95 47022.27 0.00 352507.91 81663.54
                       
Annual Sum or Average                      
Minimum of Months 1137367.16   145987.23 423497.50 0.00 24458.17 101330.87 47022.27 0.00 240926.25 81663.54
Maximum of Months 1628470.72   146638.83 778371.69 0.00 52589.61 255581.86 57350.74 0.00 386512.09 81663.54



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 410819.46 10-JAN-06:10 0.00 74963.99 27-JAN-12:30 0.00
February 0.00 0.00 463207.59 06-FEB-05:19 0.00 74904.20 01-FEB-12:39 0.00
March 0.00 0.00 374870.31 11-MAR-06:10 0.00 73556.25 07-MAR-12:50 0.00
April 0.00 0.00 85194.95 18-APR-14:20 0.00 71224.17 04-APR-11:00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 67295.98 09-MAY-11:20 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 64098.75 06-JUN-11:39 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 61920.46 03-JUL-11:39 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 62569.74 25-AUG-11:20 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 64999.44 19-SEP-11:00 0.00
October 0.00 0.00 6469.01 28-OCT-05:10 0.00 69169.43 25-OCT-11:30 0.00
November 0.00 0.00 79767.41 16-NOV-06:10 0.00 72693.89 29-NOV-12:20 0.00
December 0.00 0.00 436818.03 21-DEC-07:10 0.00 73987.51 18-DEC-12:30 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 61920.46   0.00
Maximum of Months 0.00 0.00 463207.59   0.00 74963.99   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.00 26.83 0.17 26.84
February 0.00 0.00 0.00 0.00 3.67 26.96 0.00 26.96
March 0.00 0.00 0.00 0.00 2.17 25.81 0.00 25.81
April 0.00 0.00 0.00 0.00 1.00 25.65 0.00 25.65
May 0.00 0.00 0.00 0.00 3.00 25.85 0.00 25.85
June 0.00 0.00 0.00 0.00 2.67 25.82 0.17 25.75
July 0.00 0.00 0.00 0.00 3.83 26.16 0.00 26.16
August 0.00 0.00 0.00 0.00 7.17 26.40 0.00 26.40
September 0.00 0.00 0.00 0.00 8.67 26.72 0.50 26.71
October 0.00 0.00 0.00 0.00 11.33 26.99 0.17 26.96
November 0.00 0.00 0.00 0.00 12.33 27.21 0.50 27.21
December 0.00 0.00 0.00 0.00 11.00 27.30 0.83 27.31
                 
Annual Sum or Average 0.00   0.00   71.83 26.78 2.33 26.78
Minimum of Months 0.00 0.00 0.00 0.00 1.00 25.65 0.00 25.65
Maximum of Months 0.00 0.00 0.00 0.00 12.33 27.30 0.83 27.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.58 0.00 25.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.33 19.17 0.00 19.17 0.00 19.17 0.00 19.17
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 19.17 0.00 19.17 0.00 19.17 0.00 19.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 19.17 0.00 19.17 0.00 19.17 0.00 19.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.17 26.37 0.50 26.65
August 0.00 0.00 0.00 0.00 1.67 26.15 0.50 26.42
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.83 26.24 1.00 26.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 26.37 0.50 26.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.17 27.50 1.17 27.50
February 0.00 0.00 0.00 0.00 0.50 27.56 0.50 27.56
March 0.00 0.00 0.00 0.00 1.67 27.59 1.67 27.59
April 0.00 0.00 0.00 0.00 2.17 27.73 2.17 27.73
May 0.00 0.00 0.00 0.00 8.50 27.82 8.50 27.82
June 0.00 0.00 0.00 0.00 4.17 27.67 4.17 27.67
July 0.00 0.00 0.00 0.00 8.17 27.61 7.67 27.65
August 0.00 0.00 0.00 0.00 5.17 27.52 5.17 27.52
September 0.00 0.00 0.00 0.00 9.33 27.69 9.17 27.71
October 0.00 0.00 0.00 0.00 6.00 27.66 6.00 27.66
November 0.00 0.00 0.00 0.00 1.83 27.47 1.83 27.47
December 0.00 0.00 0.00 0.00 0.33 27.46 0.33 27.46
                 
Annual Sum or Average 0.00   0.00   49.00 27.66 48.33 27.67
Minimum of Months 0.00 0.00 0.00 0.00 0.33 27.46 0.33 27.46
Maximum of Months 0.00 0.00 0.00 0.00 9.33 27.82 9.17 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 9.33 27.46 9.33 27.46
February 0.00 0.00 0.00 0.00 5.33 27.43 5.33 27.43
March 0.00 0.00 0.00 0.00 2.67 27.62 2.67 27.62
April 0.00 0.00 0.00 0.00 0.83 27.43 0.83 27.43
May 0.00 0.00 0.00 0.00 0.17 27.35 0.17 27.35
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.67 26.66 1.00 26.92
August 0.00 0.00 0.00 0.00 5.67 27.10 4.50 27.26
September 0.00 0.00 0.00 0.00 8.17 27.72 7.67 27.74
October 0.00 0.00 0.00 0.00 12.33 27.80 11.00 27.86
November 0.00 0.00 0.00 0.00 16.67 26.69 16.67 26.69
December 0.00 0.00 0.00 0.00 13.33 26.84 13.33 26.84
                 
Annual Sum or Average 0.00   0.00   76.17 27.22 72.50 27.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 16.67 27.80 16.67 27.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.17 27.75 3.17 27.75
February 0.00 0.00 0.00 0.00 4.33 27.59 3.50 27.72
March 0.00 0.00 0.00 0.00 6.83 27.46 3.83 27.67
April 0.00 0.00 0.00 0.00 19.83 27.44 8.00 27.60
May 0.00 0.00 0.00 0.00 15.17 27.03 6.17 27.28
June 0.00 0.00 0.00 0.00 27.50 27.10 9.33 27.28
July 0.00 0.00 0.00 0.00 45.00 27.34 15.17 27.49
August 0.00 0.00 0.00 0.00 52.83 27.43 15.00 27.53
September 0.00 0.00 0.00 0.00 18.00 27.28 8.17 27.50
October 0.00 0.00 0.00 0.00 22.50 27.29 10.00 27.50
November 0.00 0.00 0.00 0.00 11.83 27.39 7.50 27.59
December 0.00 0.00 0.00 0.00 11.17 27.55 7.50 27.70
                 
Annual Sum or Average 0.00   0.00   238.17 27.34 97.33 27.51
Minimum of Months 0.00 0.00 0.00 0.00 3.17 27.03 3.17 27.28
Maximum of Months 0.00 0.00 0.00 0.00 52.83 27.75 15.17 27.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 19.30 0.00 19.30 0.00 19.30 0.00 19.30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.50 27.29 0.50 27.29
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.43 0.00 19.43 0.00 19.43 0.00 19.43
                 
Annual Sum or Average 0.33 19.37 0.00 19.37 0.50 24.12 0.50 25.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.43 0.00 19.43 0.50 27.29 0.50 27.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 27.41 0.33 27.41
March 0.00 0.00 0.00 0.00 1.33 27.54 1.33 27.54
April 0.00 0.00 0.00 0.00 2.17 27.84 2.17 27.84
May 0.00 0.00 0.00 0.00 9.50 27.90 9.00 27.92
June 0.00 0.00 0.00 0.00 7.67 27.71 7.50 27.71
July 0.00 0.00 0.00 0.00 13.33 27.73 12.83 27.74
August 0.00 0.00 0.00 0.00 7.33 27.66 7.00 27.67
September 0.00 0.00 0.00 0.00 10.33 27.81 10.00 27.82
October 0.00 0.00 0.00 0.00 7.67 27.67 7.67 27.67
November 0.00 0.00 0.00 0.00 0.67 27.64 0.67 27.64
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   60.33 27.75 58.50 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.33 27.90 12.83 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 11.00 26.93 11.00 26.93
February 0.00 0.00 0.00 0.00 7.00 26.61 7.00 26.61
March 0.00 0.00 0.00 0.00 2.00 27.62 2.00 27.62
April 0.00 0.00 0.00 0.00 0.33 27.35 0.33 27.35
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 27.29 0.50 27.29
August 0.00 0.00 0.00 0.00 2.83 27.38 2.83 27.38
September 0.00 0.00 0.00 0.00 8.33 27.78 7.67 27.79
October 0.00 0.00 0.00 0.00 17.33 26.82 16.33 26.80
November 0.00 0.00 0.00 0.00 21.83 26.31 21.67 26.31
December 0.00 0.00 0.00 0.00 17.00 26.33 17.00 26.33
                 
Annual Sum or Average 0.00   0.00   88.17 26.73 86.33 26.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 21.83 27.78 21.67 27.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.00 27.59 1.00 27.59
February 0.00 0.00 0.00 0.00 0.83 28.03 0.67 28.07
March 0.00 0.00 0.00 0.00 1.83 27.72 1.67 27.74
April 0.00 0.00 0.00 0.00 5.33 27.83 3.50 27.84
May 0.00 0.00 0.00 0.00 6.83 27.84 3.67 27.94
June 0.00 0.00 0.00 0.00 8.67 27.60 3.83 27.76
July 0.00 0.00 0.00 0.00 14.83 27.43 8.00 27.56
August 0.00 0.00 0.00 0.00 8.33 27.32 4.33 27.49
September 0.00 0.00 0.00 0.00 9.33 27.79 5.67 27.90
October 0.00 0.00 0.00 0.00 7.00 27.86 5.17 27.93
November 0.00 0.00 0.00 0.00 2.33 27.64 2.17 27.64
December 0.00 0.00 0.00 0.00 1.17 27.61 1.17 27.61
                 
Annual Sum or Average 0.00   0.00   67.50 27.64 40.83 27.74
Minimum of Months 0.00 0.00 0.00 0.00 0.83 27.32 0.67 27.49
Maximum of Months 0.00 0.00 0.00 0.00 14.83 28.03 8.00 28.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.67 18.89 0.00 18.89 0.00 18.89 0.00 18.89
February 3.67 17.58 1.67 17.38 0.00 17.38 0.00 17.38
March 0.67 19.14 0.00 19.14 0.00 19.14 0.00 19.14
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 3.33 27.35 2.33 27.39
June 0.00 0.00 0.00 0.00 3.83 27.49 2.67 27.48
July 0.00 0.00 0.00 0.00 8.50 27.45 6.50 27.46
August 0.00 0.00 0.00 0.00 4.17 27.44 3.67 27.44
September 0.00 0.00 0.00 0.00 2.67 27.53 2.17 27.54
October 0.00 0.00 0.00 0.00 2.17 27.45 2.17 27.45
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.67 18.97 0.17 19.10 0.00 19.10 0.00 19.10
                 
Annual Sum or Average 8.67 18.37 1.83 18.18 24.67 24.68 19.50 25.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.67 19.14 1.67 19.14 8.50 27.53 6.50 27.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 19.05 0.00 19.05 0.00 19.05 0.00 19.05
February 1.83 17.93 0.33 17.46 0.00 17.46 0.00 17.46
March 0.67 19.23 0.00 19.23 1.00 24.23 1.00 25.48
April 0.00 0.00 0.00 0.00 2.50 27.86 2.50 27.86
May 0.00 0.00 0.00 0.00 11.33 27.97 9.67 28.02
June 0.00 0.00 0.00 0.00 9.83 27.82 8.33 27.85
July 0.00 0.00 0.00 0.00 16.67 27.82 14.17 27.86
August 0.00 0.00 0.00 0.00 10.33 27.70 8.67 27.75
September 0.00 0.00 0.00 0.00 13.17 27.89 11.83 27.91
October 0.00 0.00 0.00 0.00 9.33 27.72 9.00 27.73
November 0.00 0.00 0.00 0.00 0.67 27.46 0.67 27.46
December 1.17 19.01 0.00 19.01 0.00 19.01 0.00 19.01
                 
Annual Sum or Average 5.67 18.70 0.33 18.49 74.83 27.13 65.83 27.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.46 0.00 17.46
Maximum of Months 2.00 19.23 0.33 19.23 16.67 27.97 14.17 28.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 19.14 0.00 19.14 8.17 26.26 8.17 26.67
February 0.67 17.87 0.17 17.30 2.67 25.19 2.67 26.26
March 0.50 19.33 0.00 19.33 2.17 26.10 2.17 26.80
April 0.00 0.00 0.00 0.00 1.17 27.50 1.17 27.50
May 0.00 0.00 0.00 0.00 4.50 27.42 3.67 27.46
June 0.00 0.00 0.00 0.00 3.33 27.44 2.67 27.44
July 0.00 0.00 0.00 0.00 8.33 27.46 7.33 27.46
August 0.00 0.00 0.00 0.00 6.50 27.59 5.50 27.60
September 0.00 0.00 0.00 0.00 10.67 27.90 8.67 27.94
October 0.00 0.00 0.00 0.00 12.67 27.84 11.00 27.86
November 0.00 0.00 0.00 0.00 14.67 26.62 14.67 26.62
December 0.50 18.85 0.00 18.85 7.00 27.02 7.00 27.30
                 
Annual Sum or Average 2.67 18.80 0.17 18.58 81.83 27.13 74.67 27.27
Minimum of Months 0.00 0.00 0.00 0.00 1.17 25.19 1.17 26.26
Maximum of Months 1.00 19.33 0.17 19.33 14.67 27.90 14.67 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 19.15 0.00 19.15 0.83 22.70 0.83 24.16
February 0.50 19.02 0.00 19.02 0.83 24.68 0.83 25.99
March 0.17 19.41 0.00 19.41 2.00 27.15 1.67 27.45
April 0.00 0.00 0.00 0.00 5.33 27.92 3.33 27.94
May 0.00 0.00 0.00 0.00 9.33 27.82 5.17 27.93
June 0.00 0.00 0.00 0.00 11.67 27.65 5.67 27.78
July 0.00 0.00 0.00 0.00 18.83 27.55 9.67 27.68
August 0.00 0.00 0.00 0.00 11.17 27.43 6.17 27.59
September 0.00 0.00 0.00 0.00 12.67 27.89 7.17 27.98
October 0.00 0.00 0.00 0.00 8.67 27.92 6.00 28.00
November 0.00 0.00 0.00 0.00 1.67 27.77 1.67 27.77
December 0.50 18.91 0.00 18.91 1.17 25.05 1.17 26.13
                 
Annual Sum or Average 2.33 19.09 0.00 19.09 84.17 27.48 49.33 27.67
Minimum of Months 0.00 0.00 0.00 0.00 0.83 22.70 0.83 24.16
Maximum of Months 1.17 19.41 0.00 19.41 18.83 27.92 9.67 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.59 0.67 27.59
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 33.67 27.74 33.67 27.74
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   34.33 27.73 34.33 27.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 33.67 27.74 33.67 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.60 0.67 27.60
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 26.17 27.71 26.17 27.71
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   26.83 27.70 26.83 27.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 26.17 27.71 26.17 27.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 16.00 27.69 16.00 27.69
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   16.00 27.69 16.00 27.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 16.00 27.69 16.00 27.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 98.50 28.19 97.17 28.19
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 495.33 28.86 415.33 28.93
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 39.50 28.01 39.50 28.01
                 
Annual Sum or Average 0.00   0.00   633.33 28.70 552.00 28.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 495.33 28.86 415.33 28.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 86.67 24.31 228.00 24.87 43.17 24.84
February 126.33 24.38 301.33 24.60 97.83 24.58
March 148.17 24.38 302.67 24.55 113.83 24.54
April 242.00 24.51 428.83 24.53 240.83 24.52
May 418.83 24.58 508.00 24.53 418.83 24.54
June 401.67 24.50 496.00 24.46 401.67 24.47
July 293.83 24.97 497.00 24.72 293.83 24.79
August 219.17 25.10 514.00 24.66 219.17 24.76
September 241.33 25.09 485.00 24.73 241.33 24.82
October 179.00 25.38 452.33 24.87 179.00 24.98
November 80.50 25.27 373.50 24.87 80.50 24.93
December 74.50 24.89 305.50 24.93 63.33 24.95
             
Annual Sum or Average 2512.00 24.76 4892.17 24.66 2393.33 24.70
Minimum of Months 74.50 24.31 228.00 24.46 43.17 24.47
Maximum of Months 418.83 25.38 514.00 24.93 418.83 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 127.00 23.62 183.67 24.15 0.00 24.15
February 56.17 23.73 257.83 24.25 0.00 24.25
March 36.00 23.74 303.67 24.30 0.00 24.30
April 0.00 0.00 421.00 24.22 0.00 24.22
May 0.00 0.00 483.50 24.23 0.00 24.23
June 0.00 0.00 479.83 24.14 0.00 24.14
July 0.00 0.00 491.33 24.14 0.00 24.14
August 0.00 0.00 514.00 24.11 0.00 24.11
September 0.00 0.00 464.50 24.23 0.00 24.23
October 0.33 23.94 446.33 24.30 0.00 24.30
November 1.17 23.92 372.33 24.39 0.00 24.39
December 14.33 23.78 294.17 24.44 0.00 24.44
             
Annual Sum or Average 235.00 23.67 4712.17 24.23 0.00 24.23
Minimum of Months 0.00 0.00 183.67 24.11 0.00 24.11
Maximum of Months 127.00 23.94 514.00 24.44 0.00 24.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 364.33 23.15 65.00 23.31 0.00 23.31
February 246.00 23.14 112.33 23.46 0.00 23.46
March 247.33 23.24 140.50 23.60 0.00 23.60
April 76.83 23.36 228.50 24.09 0.00 24.09
May 17.33 23.26 322.50 24.19 0.00 24.19
June 15.00 23.27 300.50 24.17 0.00 24.17
July 22.33 23.28 293.83 24.18 0.00 24.18
August 11.50 23.27 329.67 24.20 0.00 24.20
September 28.33 23.25 288.83 24.13 0.00 24.13
October 40.17 23.33 295.67 24.17 0.00 24.17
November 148.83 23.33 176.00 23.83 0.00 23.83
December 258.00 23.13 106.67 23.47 0.00 23.47
             
Annual Sum or Average 1476.00 23.20 2660.00 23.87 0.00 23.87
Minimum of Months 11.50 23.13 65.00 23.31 0.00 23.31
Maximum of Months 364.33 23.36 329.67 24.20 0.00 24.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 412.67 22.02 65.33 22.20 14.17 22.16
February 323.67 22.28 99.50 22.51 18.00 22.39
March 311.50 22.61 128.33 23.00 7.67 22.95
April 108.50 23.22 240.50 23.95 0.00 23.95
May 2.33 23.29 414.67 24.25 0.00 24.25
June 0.00 0.00 421.50 24.22 0.00 24.22
July 1.17 23.35 418.00 24.26 0.00 24.26
August 0.00 0.00 424.33 24.25 0.00 24.25
September 1.50 23.34 352.67 24.24 0.00 24.24
October 63.83 22.98 326.33 24.09 0.00 24.09
November 264.00 22.87 120.83 23.27 0.00 23.27
December 371.67 22.32 78.00 22.56 9.83 22.51
             
Annual Sum or Average 1860.83 22.45 3090.00 23.53 49.67 23.49
Minimum of Months 0.00 0.00 65.33 22.20 0.00 22.16
Maximum of Months 412.67 23.35 424.33 24.26 18.00 24.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 340.67 22.58 103.00 22.97 0.00 22.97
February 219.83 22.79 145.17 23.31 4.33 23.27
March 205.67 23.09 199.17 23.66 0.00 23.66
April 33.17 23.54 355.50 24.14 0.00 24.14
May 9.50 26.03 507.83 24.42 9.50 24.45
June 1.67 26.84 495.83 24.33 1.67 24.34
July 11.17 26.78 496.33 24.46 11.17 24.51
August 9.33 26.79 514.00 24.32 9.33 24.37
September 10.83 25.95 481.50 24.42 10.83 24.45
October 37.17 23.83 421.83 24.34 4.83 24.36
November 133.50 23.42 238.00 23.94 0.00 23.94
December 224.00 23.00 165.33 23.51 0.00 23.51
             
Annual Sum or Average 1236.50 23.07 4123.50 24.03 51.67 24.04
Minimum of Months 1.67 22.58 103.00 22.97 0.00 22.97
Maximum of Months 340.67 26.84 514.00 24.46 11.17 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 271.00 22.87 136.33 23.44 4.50 23.47
February 177.83 22.97 180.67 23.65 3.83 23.65
March 175.83 23.06 230.17 23.82 6.67 23.87
April 50.33 23.89 352.33 24.24 7.67 24.29
May 43.67 26.76 506.33 24.65 43.67 24.80
June 22.00 26.87 494.00 24.47 22.00 24.57
July 42.00 26.83 493.67 24.64 42.00 24.80
August 23.33 26.83 505.67 24.40 23.33 24.50
September 47.33 26.77 477.67 24.68 47.33 24.85
October 58.00 25.25 425.17 24.56 32.33 24.70
November 108.17 23.54 271.00 24.18 6.83 24.22
December 211.50 22.87 165.50 23.53 2.17 23.55
             
Annual Sum or Average 1231.00 23.69 4238.50 24.24 242.33 24.35
Minimum of Months 22.00 22.87 136.33 23.44 2.17 23.47
Maximum of Months 271.00 26.87 506.33 24.68 47.33 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 199.50 23.32 220.00 24.01 26.50 24.19
February 129.67 23.30 258.83 24.05 18.33 24.12
March 164.00 23.10 255.83 23.89 10.67 23.96
April 39.33 23.77 364.33 24.25 3.83 24.27
May 13.50 26.21 507.67 24.43 13.50 24.48
June 2.17 26.88 494.00 24.32 2.17 24.33
July 16.17 26.76 495.50 24.48 16.17 24.55
August 21.17 26.80 514.00 24.40 21.17 24.49
September 43.67 26.68 481.83 24.65 43.67 24.81
October 63.67 25.99 453.17 24.73 46.00 24.91
November 81.33 24.97 372.67 24.66 35.67 24.84
December 156.00 23.76 286.33 24.33 31.33 24.51
             
Annual Sum or Average 930.17 24.05 4704.17 24.37 269.00 24.48
Minimum of Months 2.17 23.10 220.00 23.89 2.17 23.96
Maximum of Months 199.50 26.88 514.00 24.73 46.00 24.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 195.50 23.51 217.33 24.07 12.17 24.15
February 81.67 24.02 313.50 24.43 12.50 24.50
March 54.83 24.80 365.33 24.60 18.00 24.70
April 45.50 26.95 467.50 24.84 45.50 25.01
May 45.67 26.83 508.00 24.75 45.67 24.91
June 49.50 26.92 496.00 24.75 49.50 24.93
July 81.17 26.91 497.00 24.99 81.17 25.22
August 76.83 26.91 514.00 24.86 76.83 25.09
September 56.17 26.86 485.00 24.82 56.17 25.01
October 55.33 26.77 471.17 24.88 52.00 25.07
November 34.33 26.62 423.00 24.79 29.83 24.93
December 54.67 25.75 347.33 24.94 33.33 25.10
             
Annual Sum or Average 831.17 25.58 5105.17 24.75 512.67 24.92
Minimum of Months 34.33 23.51 217.33 24.07 12.17 24.15
Maximum of Months 195.50 26.95 514.00 24.99 81.17 25.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 444.33 21.62 97.83 21.66 63.83 21.56
February 361.83 21.92 96.33 21.98 44.33 21.81
March 359.17 22.29 108.00 22.54 20.83 22.45
April 168.17 23.22 235.83 23.80 11.33 23.85
May 30.00 25.58 506.67 24.42 30.00 24.49
June 13.83 25.98 492.83 24.40 13.67 24.44
July 41.83 26.19 490.00 24.60 41.83 24.72
August 27.67 25.71 508.83 24.41 27.67 24.47
September 42.33 25.27 448.50 24.43 42.00 24.49
October 116.00 23.68 374.50 24.18 34.67 24.27
November 301.17 22.52 114.00 22.95 2.50 22.96
December 401.17 21.91 87.67 22.12 29.33 22.06
             
Annual Sum or Average 2307.50 22.44 3561.00 23.48 362.00 23.48
Minimum of Months 13.83 21.62 87.67 21.66 2.50 21.56
Maximum of Months 444.33 26.19 508.83 24.60 63.83 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 328.00 22.23 83.33 22.51 25.67 22.45
February 237.17 22.37 105.33 22.74 21.83 22.64
March 212.50 22.54 156.67 23.26 16.83 23.24
April 87.67 23.91 270.17 24.35 22.67 24.47
May 62.00 26.56 430.00 24.82 62.00 25.02
June 44.00 26.71 416.00 24.73 44.00 24.91
July 69.83 26.77 418.50 24.98 69.83 25.21
August 50.67 26.49 430.50 24.71 50.67 24.88
September 66.50 26.40 398.33 24.82 66.50 25.02
October 99.67 24.80 340.17 24.64 52.67 24.84
November 181.83 23.03 172.00 23.74 7.17 23.79
December 287.83 22.32 105.17 22.72 22.33 22.69
             
Annual Sum or Average 1727.67 23.36 3326.17 24.09 462.17 24.22
Minimum of Months 44.00 22.23 83.33 22.51 7.17 22.45
Maximum of Months 328.00 26.77 430.50 24.98 69.83 25.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 238.83 22.90 210.83 23.65 38.50 23.78
February 178.83 22.81 222.00 23.66 22.17 23.69
March 223.50 22.60 209.50 23.36 18.67 23.37
April 110.17 23.45 300.00 24.11 14.67 24.17
May 32.50 25.62 506.67 24.44 32.50 24.50
June 14.00 25.75 491.00 24.37 13.50 24.41
July 44.33 26.15 487.00 24.60 44.33 24.72
August 41.50 26.10 511.00 24.50 41.50 24.61
September 67.17 26.20 471.00 24.67 67.17 24.84
October 90.50 25.52 440.83 24.74 62.33 24.94
November 134.00 24.16 323.33 24.49 39.33 24.68
December 209.50 23.09 246.33 23.92 39.17 24.08
             
Annual Sum or Average 1384.83 23.66 4419.50 24.25 433.83 24.36
Minimum of Months 14.00 22.60 209.50 23.36 13.50 23.37
Maximum of Months 238.83 26.20 511.00 24.74 67.17 24.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 335.00 22.17 126.50 22.63 27.33 22.60
February 229.33 22.31 177.50 22.99 20.67 22.89
March 228.00 22.64 219.67 23.39 18.17 23.39
April 73.33 24.42 368.33 24.44 25.50 24.56
May 48.83 26.32 508.00 24.63 48.83 24.77
June 36.00 26.76 495.00 24.62 36.00 24.76
July 68.83 26.68 497.00 24.85 68.83 25.05
August 45.00 26.57 514.00 24.64 45.00 24.78
September 64.67 26.29 481.67 24.70 64.67 24.87
October 86.83 25.04 430.83 24.59 51.67 24.75
November 181.83 23.13 242.00 23.83 11.50 23.90
December 274.00 22.36 179.33 23.10 15.67 23.11
             
Annual Sum or Average 1671.67 23.32 4239.83 24.10 433.83 24.21
Minimum of Months 36.00 22.17 126.50 22.63 11.50 22.60
Maximum of Months 335.00 26.76 514.00 24.85 68.83 25.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 454.33 21.21 194.33 21.15 160.83 20.99
February 378.50 21.54 143.83 21.51 92.50 21.27
March 372.17 21.89 149.83 22.07 62.50 21.89
April 187.50 22.93 233.00 23.65 11.50 23.70
May 49.00 25.94 505.50 24.53 49.00 24.64
June 32.00 26.20 491.67 24.51 30.50 24.61
July 59.83 26.42 487.83 24.73 59.83 24.89
August 49.83 26.03 505.17 24.52 49.83 24.65
September 69.50 25.53 445.17 24.54 66.50 24.67
October 135.33 23.50 371.33 24.12 46.83 24.21
November 338.33 22.09 128.83 22.47 27.33 22.39
December 413.33 21.48 169.33 21.55 115.00 21.40
             
Annual Sum or Average 2539.67 22.26 3825.83 23.24 772.17 23.17
Minimum of Months 32.00 21.21 128.83 21.15 11.50 20.99
Maximum of Months 454.33 26.42 505.50 24.73 160.83 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 411.67 21.78 151.33 21.86 88.50 21.67
February 297.00 21.95 145.17 22.20 47.83 21.97
March 259.50 22.16 223.67 22.86 46.67 22.73
April 108.67 23.50 328.67 24.17 22.83 24.27
May 66.17 26.56 507.00 24.73 66.17 24.92
June 51.17 26.63 492.67 24.66 49.83 24.84
July 71.00 26.83 492.17 24.88 71.00 25.10
August 57.33 26.45 510.50 24.64 57.33 24.80
September 75.67 26.26 465.17 24.73 75.00 24.92
October 127.17 24.42 403.50 24.48 60.33 24.67
November 232.00 22.65 194.50 23.35 16.00 23.34
December 360.17 21.88 159.67 22.21 61.33 22.07
             
Annual Sum or Average 2117.50 22.93 4074.00 23.78 662.83 23.82
Minimum of Months 51.17 21.78 145.17 21.86 16.00 21.67
Maximum of Months 411.67 26.83 510.50 24.88 88.50 25.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 273.83 22.34 204.17 22.97 68.17 22.94
February 213.33 22.26 218.50 23.04 42.33 22.92
March 261.00 22.26 222.50 22.89 48.83 22.78
April 139.50 23.16 289.67 23.97 17.17 24.05
May 50.67 25.93 502.00 24.53 50.67 24.65
June 31.50 26.06 489.67 24.48 29.50 24.57
July 60.17 26.34 486.00 24.71 59.50 24.87
August 52.67 26.18 508.50 24.56 52.67 24.70
September 74.50 26.10 461.33 24.70 73.67 24.87
October 100.50 25.08 432.00 24.66 62.83 24.87
November 170.67 23.46 293.33 24.17 36.67 24.34
December 244.33 22.49 247.67 23.32 59.67 23.32
             
Annual Sum or Average 1672.67 23.30 4355.33 24.04 601.67 24.12
Minimum of Months 31.50 22.26 204.17 22.89 17.17 22.78
Maximum of Months 273.83 26.34 508.50 24.71 73.67 24.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 364.17 21.77 165.17 22.04 81.83 21.90
February 263.33 21.93 181.67 22.42 53.17 22.22
March 261.50 22.25 225.50 22.92 44.00 22.82
April 107.00 23.84 346.00 24.30 26.33 24.43
May 58.67 26.34 508.00 24.68 58.67 24.83
June 47.17 26.73 493.00 24.68 47.17 24.85
July 74.17 26.72 495.83 24.89 74.17 25.10
August 56.50 26.56 513.83 24.68 56.50 24.85
September 75.17 26.21 478.00 24.72 75.17 24.90
October 101.00 24.66 421.17 24.53 55.17 24.70
November 222.83 22.65 211.67 23.46 14.67 23.52
December 307.00 21.91 191.67 22.52 53.17 22.42
             
Annual Sum or Average 1938.50 23.01 4231.50 23.87 640.00 23.93
Minimum of Months 47.17 21.77 165.17 22.04 14.67 21.90
Maximum of Months 364.17 26.73 513.83 24.89 81.83 25.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 27.00 502.00 27.00 4.00 27.00
February 8.83 27.00 454.00 27.00 8.83 27.00
March 18.00 27.00 514.00 27.00 18.00 27.00
April 180.00 27.01 485.00 27.00 180.00 27.01
May 2.33 27.00 508.00 27.00 2.33 27.00
June 38.33 27.00 496.00 27.00 38.33 27.00
July 178.83 27.00 497.00 27.00 178.83 27.00
August 427.17 27.13 514.00 27.12 427.17 27.12
September 14.50 27.00 485.00 27.00 14.50 27.00
October 53.50 27.00 502.00 27.00 53.50 27.00
November 52.83 27.00 489.00 27.00 52.83 27.00
December 109.83 27.00 497.00 27.00 109.83 27.00
             
Annual Sum or Average 1088.17 27.05 5943.00 27.02 1088.17 27.02
Minimum of Months 2.33 27.00 454.00 27.00 2.33 27.00
Maximum of Months 427.17 27.13 514.00 27.12 427.17 27.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.33 27.00 447.50 27.00 0.33 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 4.67 27.28 485.00 27.01 4.67 27.01
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 0.00 0.00 497.00 27.00 0.00 27.00
August 72.50 27.50 514.00 27.14 72.50 27.18
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.50 27.00 502.00 27.00 0.50 27.00
November 1.00 27.00 489.00 27.00 1.00 27.00
December 1.33 27.00 497.00 27.00 1.33 27.00
             
Annual Sum or Average 80.33 27.46 5936.50 27.01 80.33 27.02
Minimum of Months 0.00 0.00 447.50 27.00 0.00 27.00
Maximum of Months 72.50 27.50 514.00 27.14 72.50 27.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.33 25.99 459.83 26.97 0.00 26.97
February 8.17 27.01 429.50 27.00 1.17 27.00
March 0.33 27.00 506.17 27.00 0.33 27.00
April 29.00 27.04 485.00 27.00 29.00 27.01
May 6.00 27.00 508.00 27.00 6.00 27.00
June 17.67 27.00 496.00 27.00 17.67 27.00
July 46.17 27.00 497.00 27.00 46.17 27.00
August 105.00 27.28 514.00 27.10 105.00 27.13
September 10.83 27.00 485.00 27.00 10.83 27.00
October 19.17 27.00 502.00 27.00 19.17 27.00
November 2.33 27.00 489.00 27.00 2.33 27.00
December 5.33 27.00 489.17 27.00 5.33 27.00
             
Annual Sum or Average 263.33 27.07 5860.67 27.01 243.00 27.01
Minimum of Months 0.33 25.99 429.50 26.97 0.00 26.97
Maximum of Months 105.00 27.28 514.00 27.10 105.00 27.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 495.67 27.00 502.00 27.00 495.67 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.27 485.00 27.27 485.00 27.27
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.66 514.00 28.66 514.00 28.66
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.10 497.00 27.10 497.00 27.10
             
Annual Sum or Average 5936.67 27.18 5943.00 27.18 5936.67 27.18
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 28.66 514.00 28.66 514.00 28.66



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00016 32.39973 0.87215 21.19393
February 454.00000 27.00088 33.55156 0.92594 23.22518
March 514.00000 27.00052 33.86258 0.96452 24.72001
April 485.00000 27.00329 36.53116 1.03694 27.73110
May 508.00000 27.00030 42.35146 0.32872 7.28020
June 496.00000 27.00216 40.66373 0.36186 7.75542
July 497.00000 27.00135 39.88758 0.40361 8.42422
August 514.00000 27.10931 39.18812 0.48120 9.97181
September 485.00000 27.00019 42.76276 0.33489 7.37288
October 502.00000 27.00169 38.48460 1.00118 26.21543
November 489.00000 27.00063 35.41219 0.99356 25.89871
December 497.00000 27.00015 33.44707 0.99621 26.03701
           
Annual Sum or Average 5943.00000 27.01039 37.40023 0.72308 17.92655
Minimum of Months 454.00000 27.00015 32.39973 0.32872 7.28020
Maximum of Months 514.00000 27.10931 42.76276 1.03694 27.73110



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00010 32.56580 0.78399 18.16256
February 454.00000 27.00085 33.60476 0.82608 19.61705
March 514.00000 27.00050 33.84823 0.85690 20.63408
April 485.00000 27.00345 36.49595 0.93847 23.65535
May 508.00000 27.00015 42.61186 0.27641 6.62882
June 496.00000 27.00209 40.75352 0.28889 6.77069
July 497.00000 27.00129 39.91963 0.30530 6.97123
August 514.00000 27.09135 39.20621 0.34551 7.61055
September 485.00000 27.00011 43.13409 0.27417 6.61126
October 502.00000 27.00163 38.56298 0.93798 23.65529
November 489.00000 27.00060 35.39974 0.88887 21.77052
December 497.00000 27.00015 33.40577 0.85349 20.53849
           
Annual Sum or Average 5943.00000 27.00880 37.48065 0.62930 15.16735
Minimum of Months 454.00000 27.00010 32.56580 0.27417 6.61126
Maximum of Months 514.00000 27.09135 43.13409 0.93847 23.65535



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.95331 32.72327 0.72488 16.54577
February 454.00000 27.00108 33.66466 0.78803 18.50874
March 514.00000 27.00052 33.87928 0.82977 19.80851
April 485.00000 27.00265 36.52396 0.93690 23.65230
May 508.00000 27.00026 42.49314 0.29772 6.92205
June 496.00000 27.00220 40.72136 0.31592 7.15338
July 497.00000 27.00137 39.92282 0.33346 7.39034
August 514.00000 27.06189 39.24306 0.36245 7.88900
September 485.00000 27.00012 43.04143 0.28959 6.83731
October 502.00000 27.00169 38.56560 0.94053 23.82590
November 489.00000 27.00062 35.43738 0.86101 20.83167
December 497.00000 27.00018 33.44287 0.80771 19.07284
           
Annual Sum or Average 5943.00000 27.00229 37.49298 0.62217 14.82364
Minimum of Months 454.00000 26.95331 32.72327 0.28959 6.83731
Maximum of Months 514.00000 27.06189 43.04143 0.94053 23.82590



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00034 36.93628 1.12348 31.72195
February 454.00000 27.00097 37.84081 1.27479 39.05221
March 514.00000 27.00245 34.45412 1.38338 44.65581
April 485.00000 27.27271 36.06971 1.58315 55.38025
May 508.00000 27.00394 40.24686 0.55397 11.46088
June 496.00000 27.00277 39.73511 0.76515 17.34589
July 497.00000 27.00133 39.47584 0.97885 25.24857
August 514.00000 28.66117 37.84920 1.64998 58.74331
September 485.00000 27.00441 40.29959 0.61537 12.98952
October 502.00000 27.00249 38.34598 1.32108 41.37309
November 489.00000 27.00405 35.42983 1.43163 47.22017
December 497.00000 27.10167 32.86869 1.55126 53.67751
           
Annual Sum or Average 5943.00000 27.17633 37.45732 1.18624 36.59305
Minimum of Months 454.00000 27.00034 32.86869 0.55397 11.46088
Maximum of Months 514.00000 28.66117 40.29959 1.64998 58.74331



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.51544 38.29537 0.47637 10.59705
February 454.00000 24.48703 46.71570 0.52591 11.55301
March 514.00000 24.38753 45.70718 0.49810 10.91769
April 485.00000 24.47232 57.60872 0.60087 13.24922
May 508.00000 24.48104 66.10830 -0.1916 6.95353
June 496.00000 24.42447 65.52763 -0.2111 6.84088
July 497.00000 24.57626 64.62722 -0.1612 6.99811
August 514.00000 24.47716 62.66835 -0.1878 6.99356
September 485.00000 24.55143 63.38262 -0.1666 7.08611
October 502.00000 24.60307 57.71676 0.65379 15.09767
November 489.00000 24.60364 48.13331 0.58322 13.02480
December 497.00000 24.58750 43.26585 0.53967 12.11155
           
Annual Sum or Average 5943.00000 24.51355 55.02905 0.24357 10.09674
Minimum of Months 454.00000 24.38753 38.29537 -0.2111 6.84088
Maximum of Months 514.00000 24.60364 66.10830 0.65379 15.09767



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.12214 38.30103 0.38871 8.61914
February 454.00000 24.19880 41.98012 0.43895 9.42291
March 514.00000 24.20247 41.13675 0.44263 9.40016
April 485.00000 24.18857 46.62821 0.49048 10.18362
May 508.00000 24.20471 49.84191 -0.3613 8.00752
June 496.00000 24.12938 49.80148 -0.3781 8.11722
July 497.00000 24.13401 49.51692 -0.3693 7.94400
August 514.00000 24.11203 49.44988 -0.3612 7.78882
September 485.00000 24.21235 49.66022 -0.3563 7.94090
October 502.00000 24.26412 47.13223 0.51229 10.71122
November 489.00000 24.30823 43.57697 0.49589 10.44391
December 497.00000 24.27924 40.26391 0.46091 9.78738
           
Annual Sum or Average 5943.00000 24.19595 45.62668 0.11366 9.02253
Minimum of Months 454.00000 24.11203 38.30103 -0.3781 7.78882
Maximum of Months 514.00000 24.30823 49.84191 0.51229 10.71122



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.39302 40.91440 0.19722 6.48173
February 454.00000 23.53607 44.52589 0.26102 7.14961
March 514.00000 23.67593 43.71122 0.29646 7.39595
April 485.00000 23.96988 48.30803 0.41169 8.80301
May 508.00000 24.03025 50.69882 -0.4369 9.30100
June 496.00000 24.00623 50.66511 -0.4435 9.38996
July 497.00000 24.00305 50.62136 -0.4468 9.49909
August 514.00000 24.03488 50.68692 -0.4339 9.22557
September 485.00000 23.97942 50.80394 -0.4547 9.63246
October 502.00000 24.04441 48.38884 0.44149 9.33141
November 489.00000 23.86159 45.93706 0.36536 8.12223
December 497.00000 23.58313 43.37301 0.26818 7.22760
           
Annual Sum or Average 5943.00000 23.84500 47.40001 -0.0007 8.46980
Minimum of Months 454.00000 23.39302 40.91440 -0.4547 6.48173
Maximum of Months 514.00000 24.04441 50.80394 0.44149 9.63246



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.36949 43.17232 -0.0553 7.08437
February 454.00000 22.76614 46.15132 0.07298 7.75841
March 514.00000 23.17955 44.97695 0.17436 7.40745
April 485.00000 23.90458 48.72557 0.40013 8.77523
May 508.00000 24.15427 50.11299 -0.3787 8.31258
June 496.00000 24.15627 49.92828 -0.3738 8.18421
July 497.00000 24.17754 49.85239 -0.3705 8.18091
August 514.00000 24.16183 50.08528 -0.3745 8.23707
September 485.00000 24.08726 50.42093 -0.4075 8.77717
October 502.00000 24.02413 48.45144 0.44141 9.66661
November 489.00000 23.38829 47.41470 0.24866 7.22465
December 497.00000 22.73884 45.39297 0.05883 7.06414
           
Annual Sum or Average 5943.00000 23.59770 47.89507 -0.0489 8.05608
Minimum of Months 454.00000 22.36949 43.17232 -0.4075 7.06414
Maximum of Months 514.00000 24.17754 50.42093 0.44141 9.66661



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.07226 40.07486 0.11807 7.07124
February 454.00000 23.44915 42.47953 0.23738 7.78215
March 514.00000 23.72255 41.45903 0.30693 8.10137
April 485.00000 24.10461 46.10317 0.46561 9.79150
May 508.00000 24.38569 49.51502 -0.2501 7.10253
June 496.00000 24.32469 48.49996 -0.2518 6.89762
July 497.00000 24.41034 48.57480 -0.2188 6.90163
August 514.00000 24.27709 48.70582 -0.2569 7.00475
September 485.00000 24.37805 49.92748 -0.2666 7.35823
October 502.00000 24.28274 47.40037 0.52902 11.48369
November 489.00000 23.93996 43.92399 0.38442 8.67021
December 497.00000 23.60905 41.49486 0.27174 7.68354
           
Annual Sum or Average 5943.00000 23.99954 45.69593 0.08703 7.98380
Minimum of Months 454.00000 23.07226 40.07486 -0.2666 6.89762
Maximum of Months 514.00000 24.41034 49.92748 0.52902 11.48369



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.50806 38.79752 0.23508 8.12613
February 454.00000 23.71101 41.59566 0.31957 8.71136
March 514.00000 23.81046 40.78095 0.35753 9.34829
April 485.00000 24.13678 45.63197 0.50574 10.95827
May 508.00000 24.46251 48.82932 -0.1689 7.17823
June 496.00000 24.36459 48.11306 -0.1937 6.82721
July 497.00000 24.45276 48.21538 -0.1659 7.07768
August 514.00000 24.27736 48.56292 -0.2294 7.08078
September 485.00000 24.45964 49.23421 -0.2009 7.58382
October 502.00000 24.35873 46.80176 0.57467 12.91912
November 489.00000 24.08369 43.24837 0.43942 9.96361
December 497.00000 23.62074 41.33007 0.28627 8.26199
           
Annual Sum or Average 5943.00000 24.10593 45.11358 0.14439 8.66330
Minimum of Months 454.00000 23.50806 38.79752 -0.2294 6.82721
Maximum of Months 514.00000 24.46251 49.23421 0.57467 12.91912



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.84269 37.32728 0.36266 10.34981
February 454.00000 23.97140 40.41892 0.42137 10.80021
March 514.00000 23.84639 40.51380 0.37216 9.68361
April 485.00000 24.17420 45.69001 0.50295 10.77831
May 508.00000 24.38492 49.50026 -0.2465 7.12085
June 496.00000 24.31012 48.60829 -0.2648 7.04780
July 497.00000 24.40495 48.59883 -0.2227 6.99586
August 514.00000 24.30205 48.49250 -0.2274 6.88871
September 485.00000 24.46475 49.25189 -0.1934 7.34687
October 502.00000 24.48579 46.09996 0.64304 14.88507
November 489.00000 24.39528 41.96543 0.57093 13.19104
December 497.00000 24.09835 39.46905 0.46233 11.81077
           
Annual Sum or Average 5943.00000 24.22394 44.68676 0.17876 9.72413
Minimum of Months 454.00000 23.84269 37.32728 -0.2648 6.88871
Maximum of Months 514.00000 24.48579 49.50026 0.64304 14.88507



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.99458 37.27449 0.37537 9.52654
February 454.00000 24.30525 39.63893 0.50580 11.70111
March 514.00000 24.40179 38.86349 0.55458 12.51278
April 485.00000 24.60787 43.94700 0.71062 16.59445
May 508.00000 24.56304 48.37036 -0.0966 6.88306
June 496.00000 24.53518 47.33786 -0.0603 6.70935
July 497.00000 24.67325 47.09197 0.00397 7.07865
August 514.00000 24.54944 47.05150 0.01458 6.67076
September 485.00000 24.58226 48.46452 -0.0994 7.20118
October 502.00000 24.61840 45.54406 0.69616 16.31354
November 489.00000 24.56368 41.45235 0.62207 14.08974
December 497.00000 24.56981 38.17326 0.58994 13.61195
           
Annual Sum or Average 5943.00000 24.49762 43.62268 0.31582 10.71560
Minimum of Months 454.00000 23.99458 37.27449 -0.0994 6.67076
Maximum of Months 514.00000 24.67325 48.46452 0.71062 16.59445



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.88137 43.57127 -0.1795 8.06392
February 454.00000 22.32673 45.73508 -0.0412 8.23938
March 514.00000 22.79471 44.57002 0.07413 7.50887
April 485.00000 23.77370 48.88798 0.37097 8.72865
May 508.00000 24.35496 51.66145 -0.2653 7.26423
June 496.00000 24.35062 50.21715 -0.2560 7.11030
July 497.00000 24.46083 51.27661 -0.2170 7.23896
August 514.00000 24.33383 51.71714 -0.2657 7.29927
September 485.00000 24.29881 53.00596 -0.2980 7.75716
October 502.00000 24.06530 50.70034 0.47586 10.92021
November 489.00000 23.08128 47.34412 0.16982 7.16975
December 497.00000 22.30566 45.97066 -0.0490 7.61699
           
Annual Sum or Average 5943.00000 23.51013 48.73517 -0.0411 7.90578
Minimum of Months 454.00000 21.88137 43.57127 -0.2980 7.11030
Maximum of Months 514.00000 24.46083 53.00596 0.47586 10.92021



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.69906 41.53748 0.02742 7.83906
February 385.00000 23.04352 43.28386 0.14214 8.25900
March 433.00000 23.39238 42.14417 0.23747 9.03749
April 410.00000 24.16319 47.03947 0.49521 11.28912
May 430.00000 24.57122 50.41416 -0.1391 7.51144
June 418.00000 24.52157 49.25563 -0.1524 7.13826
July 422.00000 24.67769 50.10513 -0.0996 7.67035
August 433.00000 24.50032 50.77667 -0.1686 7.26860
September 410.00000 24.53710 51.64162 -0.1817 8.08240
October 427.00000 24.35589 49.29624 0.57138 13.58855
November 417.00000 23.72992 44.84322 0.33793 8.99056
December 422.00000 22.90242 44.23234 0.10102 8.10380
           
Annual Sum or Average 5034.00000 23.92902 47.06421 0.09670 8.73096
Minimum of Months 385.00000 22.69906 41.53748 -0.1817 7.13826
Maximum of Months 433.00000 24.67769 51.64162 0.57138 13.58855



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.57724 38.61690 0.29745 10.26566
February 454.00000 23.67719 41.53831 0.34554 10.55011
March 514.00000 23.46952 42.13671 0.27254 9.18933
April 485.00000 24.01412 47.73718 0.45163 10.19417
May 508.00000 24.35976 51.61565 -0.2590 7.26716
June 496.00000 24.32663 50.42669 -0.2727 7.24909
July 497.00000 24.44784 51.35913 -0.2231 7.29473
August 514.00000 24.36919 51.31955 -0.2298 7.13640
September 485.00000 24.43299 51.74803 -0.2040 7.61618
October 502.00000 24.45758 48.19015 0.63938 15.15461
November 489.00000 24.22357 43.16526 0.52371 12.69934
December 497.00000 23.76645 41.38417 0.37611 11.56065
           
Annual Sum or Average 5943.00000 24.09515 46.63570 0.14043 9.66659
Minimum of Months 454.00000 23.46952 38.61690 -0.2727 7.13640
Maximum of Months 514.00000 24.45758 51.74803 0.63938 15.15461



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.83207 40.88200 0.07221 8.17701
February 454.00000 23.22441 42.93237 0.20328 9.29363
March 514.00000 23.47556 42.32240 0.26928 9.09336
April 485.00000 24.24714 46.87727 0.53724 12.13381
May 508.00000 24.47078 50.73220 -0.1667 7.07290
June 496.00000 24.46849 49.38880 -0.1523 7.02587
July 497.00000 24.59403 50.22039 -0.1142 7.34424
August 514.00000 24.46696 50.45447 -0.1480 6.95270
September 485.00000 24.47846 51.55600 -0.1770 7.56400
October 502.00000 24.36013 48.91771 0.59290 13.72969
November 489.00000 23.78730 44.83870 0.36826 9.38193
December 497.00000 23.18769 43.29960 0.18922 8.70188
           
Annual Sum or Average 5943.00000 23.97035 46.89089 0.12121 8.86053
Minimum of Months 454.00000 22.83207 40.88200 -0.1770 6.95270
Maximum of Months 514.00000 24.59403 51.55600 0.59290 13.72969



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.47238 44.77691 -0.3064 10.33886
February 454.00000 21.93970 46.86633 -0.1496 10.00701
March 514.00000 22.47598 45.35956 -0.0119 8.65907
April 485.00000 23.64086 49.42511 0.34487 8.88389
May 508.00000 24.38709 51.82967 -0.2336 7.22001
June 496.00000 24.38763 50.23397 -0.2197 7.06276
July 497.00000 24.50598 51.26819 -0.1784 7.32904
August 514.00000 24.36134 51.92887 -0.2344 7.27335
September 485.00000 24.32526 53.40294 -0.2726 7.90037
October 502.00000 23.99051 51.26330 0.46631 11.43751
November 489.00000 22.67952 48.43603 0.06857 7.64403
December 497.00000 21.89702 47.24721 -0.1689 9.14703
           
Annual Sum or Average 5943.00000 23.34821 49.34549 -0.0750 8.56503
Minimum of Months 454.00000 21.47238 44.77691 -0.3064 7.06276
Maximum of Months 514.00000 24.50598 53.40294 0.46631 11.43751



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.21143 42.91778 -0.1053 8.86756
February 454.00000 22.67782 44.69373 0.05138 9.28510
March 514.00000 23.15707 43.07537 0.18082 9.61609
April 485.00000 24.03323 47.45045 0.48329 11.28337
May 508.00000 24.49386 50.52610 -0.1243 7.33515
June 496.00000 24.45403 49.33567 -0.1280 6.95755
July 497.00000 24.59057 50.08994 -0.0830 7.53622
August 514.00000 24.42936 50.86577 -0.1496 7.09481
September 485.00000 24.45065 51.87613 -0.1764 8.00834
October 502.00000 24.22107 49.57924 0.55872 13.64192
November 489.00000 23.45798 45.97238 0.27278 8.68285
December 497.00000 22.49945 45.54036 -0.0095 8.84641
           
Annual Sum or Average 5943.00000 23.72972 47.67459 0.06337 8.92249
Minimum of Months 454.00000 22.21143 42.91778 -0.1764 6.95755
Maximum of Months 514.00000 24.59057 51.87613 0.55872 13.64192



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.17788 39.86196 0.17649 10.40925
February 454.00000 23.29237 42.60277 0.23994 10.82584
March 514.00000 23.16875 42.97308 0.19160 9.75633
April 485.00000 23.88442 48.30273 0.42693 10.28065
May 508.00000 24.38535 51.80173 -0.2291 7.23718
June 496.00000 24.36338 50.44159 -0.2365 7.17897
July 497.00000 24.48926 51.35605 -0.1856 7.37013
August 514.00000 24.38813 51.55232 -0.2008 7.14067
September 485.00000 24.43322 52.19882 -0.1856 7.81528
October 502.00000 24.37868 48.73051 0.62947 15.33263
November 489.00000 23.96921 43.91939 0.45353 12.03823
December 497.00000 23.38886 42.58391 0.26608 11.39710
           
Annual Sum or Average 5943.00000 23.94662 47.22252 0.11003 9.71735
Minimum of Months 454.00000 23.16875 39.86196 -0.2365 7.14067
Maximum of Months 514.00000 24.48926 52.19882 0.62947 15.33263



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.41873 42.06886 -0.0455 9.26158
February 454.00000 22.85768 43.98966 0.10634 10.14089
March 514.00000 23.16969 43.12878 0.19098 9.62202
April 485.00000 24.12690 47.42183 0.51482 12.10403
May 508.00000 24.48692 50.96880 -0.1408 7.14926
June 496.00000 24.48167 49.49161 -0.1242 7.09851
July 497.00000 24.60858 50.31983 -0.0860 7.50364
August 514.00000 24.47646 50.72102 -0.1231 7.02082
September 485.00000 24.47788 52.02982 -0.1600 7.74020
October 502.00000 24.29033 49.45881 0.58492 14.01835
November 489.00000 23.47074 45.71446 0.28844 9.22965
December 497.00000 22.78313 44.50183 0.07882 9.26480
           
Annual Sum or Average 5943.00000 23.80985 47.50324 0.08925 9.16528
Minimum of Months 454.00000 22.41873 42.06886 -0.1600 7.02082
Maximum of Months 514.00000 24.60858 52.02982 0.58492 14.01835



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.605366E+11 180605.42 31-JAN-15:00 285.80 0.398754E+12 0.00 0.459291E+12 2.22 7.93 20-JAN-06:04 0.00 0.00
February 0.820175E+11 182713.76 24-FEB-16:20 326.18 0.557632E+12 0.00 0.639650E+12 2.97 7.93 03-FEB-06:04 0.00 0.00
March 0.977547E+11 186962.31 07-MAR-12:30 409.89 0.664887E+12 0.00 0.762642E+12 3.32 7.93 28-MAR-05:04 0.00 0.00
April 0.148096E+12 187755.82 27-APR-11:20 549.60 0.105468E+13 0.00 0.120277E+13 4.83 7.95 18-APR-13:40 0.00 0.00
May 0.210828E+12 197647.32 24-MAY-11:10 540.60 0.150527E+13 0.00 0.171610E+13 4.98 7.89 13-MAY-04:13 0.00 0.00
June 0.213231E+12 203463.34 24-JUN-10:00 596.88 0.149815E+13 0.00 0.171138E+13 5.45 7.92 08-JUN-05:04 0.00 0.00
July 0.221354E+12 205427.64 22-JUL-11:20 658.73 0.152089E+13 0.00 0.174225E+13 5.60 7.71 12-JUL-15:10 0.00 0.00
August 0.224907E+12 200291.36 10-AUG-17:20 679.36 0.156487E+13 0.00 0.178978E+13 5.79 7.82 16-AUG-04:13 0.00 0.00
September 0.206450E+12 197643.95 08-SEP-08:00 534.81 0.146120E+13 0.00 0.166765E+13 5.02 7.92 22-SEP-05:04 0.00 0.00
October 0.178691E+12 204877.40 14-OCT-11:00 549.58 0.125333E+13 0.00 0.143202E+13 4.79 7.95 26-OCT-15:00 0.00 0.00
November 0.115489E+12 192887.50 01-NOV-12:00 450.99 0.787722E+12 0.00 0.903211E+12 3.85 7.92 08-NOV-06:04 0.00 0.00
December 0.836780E+11 188640.02 13-DEC-11:30 376.17 0.569175E+12 0.00 0.652853E+12 2.98 7.88 16-DEC-06:05 0.00 0.00
                         
Annual Sum or Average 0.184303E+13     5958.57 0.128366E+14 0.00 0.146796E+14 4.32     0.00 0.00
Minimum of Months 0.605366E+11 180605.42   285.80 0.398754E+12 0.00 0.459291E+12 2.22 7.71   0.00 0.00
Maximum of Months 0.224907E+12 205427.64   679.36 0.156487E+13 0.00 0.178978E+13 5.79 7.95   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.173825E+10 110084.60 19-JAN-11:05 5.83 0.127127E+11 0.00 0.144510E+11 0.05 7.50 19-JAN-10:05 0.00 0.00
February 0.333279E+10 140187.00 27-FEB-16:13 12.19 0.245353E+11 0.00 0.278681E+11 0.12 7.67 27-FEB-16:13 0.00 0.00
March 0.531534E+10 115449.70 30-MAR-13:00 17.75 0.387701E+11 0.00 0.440854E+11 0.16 7.66 17-MAR-16:00 0.00 0.00
April 0.923889E+10 155642.44 27-APR-15:23 29.75 0.668469E+11 0.00 0.760858E+11 0.29 7.75 20-APR-15:03 0.00 0.00
May 0.428665E+11 162062.56 10-MAY-15:53 122.12 0.305034E+12 0.00 0.347900E+12 1.15 7.52 12-MAY-12:05 0.00 0.00
June 0.512908E+11 156616.03 12-JUN-15:13 142.53 0.360010E+12 0.00 0.411301E+12 1.37 7.62 12-JUN-11:00 0.00 0.00
July 0.607825E+11 138879.71 05-JUL-12:05 163.00 0.421862E+12 0.00 0.482644E+12 1.51 7.44 12-JUL-15:30 0.00 0.00
August 0.668206E+11 136882.00 22-AUG-12:05 180.67 0.467096E+12 0.00 0.533916E+12 1.69 7.46 15-AUG-10:05 0.00 0.00
September 0.472370E+11 150427.51 22-SEP-14:03 131.28 0.333773E+12 0.00 0.381010E+12 1.28 7.57 13-SEP-04:15 0.00 0.00
October 0.412091E+11 142098.89 18-OCT-15:03 112.94 0.291157E+12 0.00 0.332366E+12 1.06 7.80 02-OCT-10:43 0.00 0.00
November 0.123894E+11 139790.72 06-NOV-10:23 34.67 0.884285E+11 0.00 0.100818E+12 0.34 7.74 06-NOV-09:43 0.00 0.00
December 0.649604E+10 152898.45 15-DEC-13:53 18.92 0.469957E+11 0.00 0.534918E+11 0.18 7.52 11-DEC-17:00 0.00 0.00
                         
Annual Sum or Average 0.348717E+12     971.64 0.245722E+13 0.00 0.280594E+13 0.77     0.00 0.00
Minimum of Months 0.173825E+10 110084.60   5.83 0.127127E+11 0.00 0.144510E+11 0.05 7.44   0.00 0.00
Maximum of Months 0.668206E+11 162062.56   180.67 0.467096E+12 0.00 0.533916E+12 1.69 7.80   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.352858E+11 744.00 43776.24 01-JAN-08:43 275331.83 31-JAN-13:00 20.13 19.29 14.12
February 0.504049E+11 672.00 43776.24 01-FEB-00:10 421877.81 24-FEB-10:30 22.83 20.21 14.12
March 0.732820E+11 744.00 43776.24 01-MAR-00:10 604837.54 31-MAR-24:00 26.92 21.83 14.12
April 0.107161E+12 720.00 43776.24 01-APR-00:10 681836.41 28-APR-17:20 36.90 26.20 14.12
May 0.117250E+12 744.00 43776.24 01-MAY-00:03 331361.79 31-MAY-23:40 32.87 28.70 14.12
June 0.113468E+12 720.00 43776.24 01-JUN-00:10 479456.68 30-JUN-23:55 37.89 30.73 14.12
July 0.117250E+12 744.00 43776.24 01-JUL-00:10 626134.36 31-JUL-23:33 42.51 32.38 14.12
August 0.117250E+12 744.00 43776.24 01-AUG-00:10 691090.32 06-AUG-15:31 46.03 33.13 14.12
September 0.113468E+12 720.00 43776.24 01-SEP-00:10 330798.55 30-SEP-23:50 32.24 28.04 14.12
October 0.107934E+12 744.00 43776.24 01-OCT-00:10 467693.82 31-OCT-24:00 33.12 27.13 14.12
November 0.836272E+11 720.00 43776.24 01-NOV-00:10 531439.10 01-NOV-14:05 28.73 22.90 14.12
December 0.717103E+11 744.00 43776.24 01-DEC-09:50 664223.09 13-DEC-17:10 28.90 22.02 14.12
                   
Annual Sum or Average 0.110809E+13 8760.00         32.48 26.09 14.12
Minimum of Months 0.352858E+11 672.00 43776.24   275331.83   20.13 19.29 14.12
Maximum of Months 0.117250E+12 744.00 43776.24   691090.32   46.03 33.13 14.12



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.479709E+10 201.99 18943.65 02-JAN-10:20 1448397.94 02-JAN-11:20 21.96 21.33 22.25
February 0.616463E+10 267.45 18943.65 01-FEB-13:00 1426086.80 27-FEB-10:20 22.51 21.55 29.53
March 0.858101E+10 325.18 18943.65 06-MAR-08:30 1425666.21 31-MAR-10:50 22.56 21.53 32.42
April 0.177225E+11 472.79 18943.65 01-APR-04:12 1467532.20 05-APR-10:40 23.55 21.87 46.35
May 0.367080E+11 540.60 18943.65 01-MAY-01:05 1282035.31 17-MAY-04:14 27.18 24.91 40.14
June 0.398424E+11 596.88 18943.65 01-JUN-04:12 1436606.02 07-JUN-04:13 27.26 24.92 47.19
July 0.449235E+11 658.73 18943.65 01-JUL-00:10 1172817.00 12-JUL-12:05 28.10 25.78 49.01
August 0.454753E+11 677.52 18943.65 01-AUG-00:10 1230426.70 16-AUG-17:20 27.52 25.14 51.99
September 0.364588E+11 534.81 18943.65 01-SEP-00:10 1288067.34 22-SEP-07:30 27.81 25.53 40.16
October 0.285151E+11 527.90 18943.65 02-OCT-09:00 1437026.06 02-OCT-12:00 25.62 23.71 43.43
November 0.116275E+11 389.16 18943.65 01-NOV-03:43 1428092.28 06-NOV-09:00 23.21 21.94 38.42
December 0.873243E+10 285.41 18943.65 08-DEC-11:00 1465941.74 08-DEC-16:30 22.39 21.50 28.98
                   
Annual Sum or Average 0.289548E+12 5478.42         24.99 23.32 39.19
Minimum of Months 0.479709E+10 201.99 18943.65   1172817.00   21.96 21.33 22.25
Maximum of Months 0.454753E+11 677.52 18943.65   1467532.20   28.10 25.78 51.99



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.960443E+09 14.08 18943.65 02-JAN-11:30 1038970.94 31-JAN-15:05 21.96 21.88 0.90
February 0.184890E+10 27.11 18943.65 01-FEB-13:50 1129684.72 27-FEB-15:05 22.51 22.33 1.87
March 0.269947E+10 39.58 18943.65 06-MAR-09:40 1078515.52 07-MAR-13:05 22.56 22.34 2.60
April 0.512331E+10 75.12 18943.65 04-APR-15:40 1151454.19 25-APR-14:05 23.55 23.13 4.85
May 0.214204E+11 314.10 18943.65 01-MAY-05:06 1173137.52 10-MAY-15:53 27.18 25.56 19.74
June 0.220482E+11 323.30 18943.65 01-JUN-06:50 1157650.47 08-JUN-14:05 27.26 25.57 21.72
July 0.269178E+11 394.71 18943.65 01-JUL-05:06 1172817.00 12-JUL-12:05 28.10 26.21 25.23
August 0.263285E+11 386.06 18943.65 01-AUG-06:20 1154193.48 22-AUG-12:05 27.52 25.63 25.59
September 0.231992E+11 340.18 18943.65 01-SEP-05:08 1173802.42 01-SEP-12:05 27.81 26.07 22.04
October 0.158257E+11 232.06 18943.65 02-OCT-09:40 1185291.21 03-OCT-15:43 25.62 24.49 15.57
November 0.468287E+10 68.67 18943.65 01-NOV-06:20 1094641.92 06-NOV-13:05 23.21 22.85 4.82
December 0.315412E+10 46.25 18943.65 08-DEC-15:50 1150883.87 15-DEC-13:53 22.39 22.14 2.95
                   
Annual Sum or Average 0.154209E+12 2261.22         24.99 24.03 12.40
Minimum of Months 0.960443E+09 14.08 18943.65   1038970.94   21.96 21.88 0.90
Maximum of Months 0.269178E+11 394.71 18943.65   1185291.21   28.10 26.21 25.59



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.229603E+11 0.00 213.14 1164287.24 09-JAN-06:02 0.00 29.65 38.29 0.08 0.00 0.01 0.82 09-JAN-06:02
February 0.114890E+11 0.00 118.17 1053750.78 17-FEB-06:02 0.00 26.69 32.03 0.05 0.00 0.00 0.74 17-FEB-06:02
March 0.963574E+10 0.00 93.83 1204389.09 11-MAR-06:02 0.00 27.25 31.19 0.03 0.00 0.00 0.85 11-MAR-06:02
April 0.217796E+09 0.00 10.21 77297.97 18-APR-14:20 0.00 33.03 33.47 0.00 0.00 0.00 0.05 18-APR-14:20
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 39.42 39.42 0.00 0.00 0.00 0.00 01-MAY-00:03
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 39.42 39.42 0.00 0.00 0.00 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 39.42 39.42 0.00 0.00 0.00 0.00 01-JUL-00:10
August 0.00 0.00 0.00 0.00 01-AUG-00:10 0.00 39.42 39.42 0.00 0.00 0.00 0.00 01-AUG-00:10
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 39.42 39.42 0.00 0.00 0.00 0.00 01-SEP-00:10
October 37483238.36 0.00 6.75 16441.45 28-OCT-05:03 0.00 39.07 39.27 0.00 0.00 0.00 0.01 28-OCT-05:03
November 0.819410E+09 0.00 43.58 211962.11 16-NOV-06:02 0.00 31.49 33.32 0.00 0.00 0.00 0.15 16-NOV-06:02
December 0.151990E+11 0.00 159.29 1213618.47 20-DEC-05:11 0.00 27.33 33.95 0.05 0.00 0.00 0.86 20-DEC-05:11
                           
Annual Sum or Average 0.603588E+11 0.00 644.97     0.00 34.35 36.59 0.02 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 26.69 31.19 0.00 0.00 0.00 0.00  
Maximum of Months 0.229603E+11 0.00 213.14 1213618.47   0.00 39.42 39.42 0.08 0.00 0.01 0.86  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 20.13 20.13 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 22.83 22.83 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 26.92 26.92 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 36.90 36.90 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 32.87 32.87 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 37.89 37.89 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 42.51 42.51 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:10 0.00 46.03 46.03 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 32.24 32.24 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 33.12 33.12 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 28.73 28.73 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 28.90 28.90 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 32.48 32.48 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 20.13 20.13 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 46.03 46.03 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.389122E+11 0.00 270.89 0.292565E+11 0.00 0.00 0.00 0.00 132707.43 30-JAN-06:02 108360.00 19-JAN-06:03 0.00 0.00 0.00
February 0.554933E+11 0.00 316.93 0.405615E+11 0.00 0.00 0.00 0.00 151496.21 28-FEB-05:12 141705.55 27-FEB-05:11 0.00 0.00 0.00
March 0.694834E+11 0.00 403.42 0.548985E+11 0.00 0.00 0.00 0.00 155185.81 28-MAR-04:12 133662.05 27-MAR-05:03 0.00 0.00 0.00
April 0.113392E+12 0.00 539.42 0.901505E+11 0.00 0.00 0.00 0.00 151446.33 01-APR-04:12 129226.91 27-APR-05:02 0.00 0.00 0.00
May 0.142564E+12 0.00 513.61 0.109169E+12 0.00 0.00 0.00 0.00 176689.16 22-MAY-05:02 143786.38 31-MAY-04:11 0.00 0.00 0.00
June 0.154722E+12 0.00 574.55 0.121502E+12 0.00 0.00 0.00 0.00 171250.04 07-JUN-04:12 140975.66 12-JUN-05:02 0.00 0.00 0.00
July 0.168254E+12 0.00 626.05 0.130387E+12 0.00 0.00 0.00 0.00 164096.97 24-JUL-05:03 145552.63 24-JUL-05:02 0.00 0.00 0.00
August 0.185142E+12 0.00 655.42 0.145190E+12 0.00 0.00 0.00 0.00 176546.98 07-AUG-05:02 148808.83 21-AUG-05:02 0.00 0.00 0.00
September 0.143539E+12 0.00 504.28 0.103867E+12 0.00 0.00 0.00 0.00 194757.12 06-SEP-03:02 142409.50 06-SEP-03:02 0.00 0.00 0.00
October 0.134782E+12 0.00 525.20 0.105470E+12 0.00 0.00 0.00 0.00 178077.97 21-OCT-04:11 144805.62 10-OCT-04:11 0.00 0.00 0.00
November 0.847191E+11 0.00 435.50 0.682199E+11 0.00 0.00 0.00 0.00 173699.87 08-NOV-05:11 138388.80 08-NOV-05:11 0.00 0.00 0.00
December 0.633503E+11 0.00 361.54 0.498403E+11 0.00 0.00 0.00 0.00 141176.64 11-DEC-06:03 128658.57 11-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.135435E+13 0.00 5726.80 0.104851E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.389122E+11 0.00 270.89 0.292565E+11 0.00 0.00 0.00 0.00 132707.43   108360.00   0.00 0.00 0.00
Maximum of Months 0.185142E+12 0.00 655.42 0.145190E+12 0.00 0.00 0.00 0.00 194757.12   148808.83   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.308391E+12 0.00 264.49 0.225246E+12 0.00 0.00 0.00 0.00 1086610.00 19-JAN-06:03 826674.22 19-JAN-06:03 0.00 0.00 0.00
February 0.436165E+12 0.00 300.19 0.304722E+12 0.00 0.00 0.00 0.00 1300453.40 27-FEB-06:02 1179700.80 27-FEB-06:02 0.00 0.00 0.00
March 0.518457E+12 0.00 363.22 0.387582E+12 0.00 0.00 0.00 0.00 1585560.07 07-MAR-06:02 1157412.51 07-MAR-06:02 0.00 0.00 0.00
April 0.818957E+12 0.00 413.54 0.609615E+12 0.00 0.00 0.00 0.00 1571671.91 29-APR-04:11 1257316.61 28-APR-04:12 0.00 0.00 0.00
May 0.129612E+13 0.00 479.96 0.950414E+12 0.00 0.00 0.00 0.00 2012289.33 24-MAY-05:02 1289933.92 22-MAY-05:02 0.00 0.00 0.00
June 0.132443E+13 0.00 486.59 0.983251E+12 0.00 0.00 0.00 0.00 1669297.10 09-JUN-04:12 1282046.96 16-JUN-05:02 0.00 0.00 0.00
July 0.137971E+13 0.00 502.13 0.980776E+12 0.00 0.00 0.00 0.00 1632799.65 29-JUL-05:02 1281498.94 07-JUL-05:02 0.00 0.00 0.00
August 0.142465E+13 0.00 501.26 0.101288E+13 0.00 0.00 0.00 0.00 1830270.31 16-AUG-04:12 1265232.28 31-AUG-05:02 0.00 0.00 0.00
September 0.128209E+13 0.00 465.78 0.871973E+12 0.00 0.00 0.00 0.00 2158839.05 05-SEP-04:11 1296756.61 01-SEP-05:02 0.00 0.00 0.00
October 0.112227E+13 0.00 450.41 0.824566E+12 0.00 0.00 0.00 0.00 1825929.02 21-OCT-04:11 1290285.76 10-OCT-04:11 0.00 0.00 0.00
November 0.643854E+12 0.00 391.87 0.495761E+12 0.00 0.00 0.00 0.00 1556379.23 02-NOV-05:02 1263701.95 03-NOV-05:02 0.00 0.00 0.00
December 0.450324E+12 0.00 301.79 0.329179E+12 0.00 0.00 0.00 0.00 1323950.75 16-DEC-06:03 1030499.51 11-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.110054E+14 0.00 4921.23 0.797597E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.308391E+12 0.00 264.49 0.225246E+12 0.00 0.00 0.00 0.00 1086610.00   826674.22   0.00 0.00 0.00
Maximum of Months 0.142465E+13 0.00 502.13 0.101288E+13 0.00 0.00 0.00 0.00 2158839.05   1296756.61   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.303282E+11 0.00 253.19 0.215849E+11 0.00 0.00 0.00 0.00 123310.99 19-JAN-15:00 83205.69 19-JAN-15:50 0.00 0.00 0.00
February 0.440308E+11 0.00 295.21 0.305756E+11 0.00 0.00 0.00 0.00 122032.23 27-FEB-16:00 90350.17 28-FEB-06:03 0.00 0.00 0.00
March 0.534965E+11 0.00 360.99 0.396660E+11 0.00 0.00 0.00 0.00 144840.10 07-MAR-06:02 104574.28 27-MAR-05:03 0.00 0.00 0.00
April 0.866360E+11 0.00 408.23 0.652177E+11 0.00 0.00 0.00 0.00 159578.45 26-APR-05:02 119870.28 26-APR-05:02 0.00 0.00 0.00
May 0.143674E+12 0.00 485.19 0.107950E+12 0.00 0.00 0.00 0.00 234436.44 24-MAY-05:02 147051.59 22-MAY-05:02 0.00 0.00 0.00
June 0.149056E+12 0.00 495.98 0.113927E+12 0.00 0.00 0.00 0.00 182076.64 19-JUN-05:02 139550.10 16-JUN-05:02 0.00 0.00 0.00
July 0.154574E+12 0.00 515.05 0.112965E+12 0.00 0.00 0.00 0.00 201930.60 27-JUL-03:02 146936.65 20-JUL-03:02 0.00 0.00 0.00
August 0.157917E+12 0.00 509.03 0.115222E+12 0.00 0.00 0.00 0.00 212218.32 23-AUG-03:02 147498.35 03-AUG-03:02 0.00 0.00 0.00
September 0.138163E+12 0.00 469.81 0.957260E+11 0.00 0.00 0.00 0.00 240696.43 05-SEP-04:11 140509.56 07-SEP-05:02 0.00 0.00 0.00
October 0.120021E+12 0.00 451.34 0.893688E+11 0.00 0.00 0.00 0.00 206501.13 06-OCT-03:02 147080.15 06-OCT-03:02 0.00 0.00 0.00
November 0.626074E+11 0.00 386.54 0.478871E+11 0.00 0.00 0.00 0.00 166848.53 01-NOV-05:02 128779.38 03-NOV-05:02 0.00 0.00 0.00
December 0.433980E+11 0.00 297.68 0.314509E+11 0.00 0.00 0.00 0.00 134246.73 15-DEC-06:03 94824.36 15-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.118390E+13 0.00 4928.24 0.871540E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.303282E+11 0.00 253.19 0.215849E+11 0.00 0.00 0.00 0.00 122032.23   83205.69   0.00 0.00 0.00
Maximum of Months 0.157917E+12 0.00 515.05 0.115222E+12 0.00 0.00 0.00 0.00 240696.43   147498.35   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.203163E+11 0.00 145.35 0.158448E+11 0.00 0.00 0.00 0.00 120528.60 01-JAN-16:12 97241.30 30-JAN-05:15 0.00 0.00 0.00
February 0.237956E+11 0.00 190.53 0.193774E+11 0.00 0.00 0.00 0.00 117803.38 03-FEB-05:12 101361.26 21-FEB-05:12 0.00 0.00 0.00
March 0.325190E+11 0.00 238.29 0.276503E+11 0.00 0.00 0.00 0.00 140960.90 07-MAR-05:11 93505.33 06-MAR-05:11 0.00 0.00 0.00
April 0.512819E+11 0.00 349.58 0.446918E+11 0.00 0.00 0.00 0.00 138277.68 26-APR-04:12 84763.60 24-APR-04:53 0.00 0.00 0.00
May 0.953758E+11 0.00 424.13 0.731138E+11 0.00 0.00 0.00 0.00 164826.03 29-MAY-11:20 86157.34 29-MAY-18:50 0.00 0.00 0.00
June 0.100442E+12 0.00 421.62 0.746899E+11 0.00 0.00 0.00 0.00 162971.22 19-JUN-03:02 88911.18 12-JUN-03:02 0.00 0.00 0.00
July 0.109203E+12 0.00 414.74 0.760260E+11 0.00 0.00 0.00 0.00 167486.31 03-JUL-03:02 85832.43 05-JUL-03:02 0.00 0.00 0.00
August 0.121463E+12 0.00 464.88 0.871028E+11 0.00 0.00 0.00 0.00 164242.89 06-AUG-17:20 89674.88 28-AUG-03:02 0.00 0.00 0.00
September 0.103109E+12 0.00 428.58 0.741632E+11 0.00 0.00 0.00 0.00 160914.75 24-SEP-16:01 90860.05 05-SEP-04:23 0.00 0.00 0.00
October 0.887705E+11 0.00 404.00 0.674879E+11 0.00 0.00 0.00 0.00 170718.78 15-OCT-15:38 91473.68 09-OCT-17:08 0.00 0.00 0.00
November 0.489548E+11 0.00 303.77 0.403978E+11 0.00 0.00 0.00 0.00 142478.22 01-NOV-04:15 88879.35 05-NOV-15:18 0.00 0.00 0.00
December 0.317500E+11 0.00 204.59 0.256639E+11 0.00 0.00 0.00 0.00 141806.98 15-DEC-05:12 84824.61 12-DEC-05:14 0.00 0.00 0.00
                               
Annual Sum or Average 0.826981E+12 0.00 3990.06 0.626210E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.203163E+11 0.00 145.35 0.158448E+11 0.00 0.00 0.00 0.00 117803.38   84763.60   0.00 0.00 0.00
Maximum of Months 0.121463E+12 0.00 464.88 0.871028E+11 0.00 0.00 0.00 0.00 170718.78   101361.26   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.382904E+11 0.118644E+11 534.03 0.341162E+11 0.417421E+10 0.00 0.49 31-JAN-12:50 0.01 28-JAN-10:07 206710.47 31-JAN-12:50 127695.78 02-JAN-15:00 81442.71 31-JAN-12:50 50169.67 31-JAN-12:50 0.00
February 0.147440E+12 0.383266E+11 494.56 0.137605E+12 0.983564E+10 0.00 0.72 24-FEB-10:30 0.00 03-FEB-20:20 310688.50 24-FEB-10:30 217821.93 24-FEB-13:05 112095.02 24-FEB-10:20 72270.11 24-FEB-10:30 0.00
March 0.360646E+12 0.926839E+11 699.18 0.334091E+12 0.265546E+11 0.00 0.95 31-MAR-24:00 0.01 11-MAR-17:13 393382.55 31-MAR-24:00 393382.55 31-MAR-24:00 169281.52 29-MAR-08:40 96482.29 30-MAR-13:00 0.00
April 0.853578E+12 0.217778E+12 719.83 0.778393E+12 0.751856E+11 0.00 1.00 04-APR-12:10 0.01 11-APR-06:50 428399.79 05-APR-07:15 403299.07 28-APR-21:02 220465.81 05-APR-07:10 127990.90 28-APR-15:00 0.00
May 0.347644E+12 0.101274E+12 744.00 0.334917E+12 0.127271E+11 0.00 0.56 31-MAY-23:20 0.34 07-MAY-01:00 212295.34 31-MAY-23:10 210555.14 31-MAY-24:00 14625.84 23-MAY-16:00 54896.44 31-MAY-23:20 0.00
June 0.574680E+12 0.168227E+12 720.00 0.560727E+12 0.139532E+11 0.00 0.78 30-JUN-23:55 0.55 01-JUN-05:00 302399.82 30-JUN-23:03 302165.61 30-JUN-24:00 17666.92 29-JUN-15:00 82416.44 30-JUN-23:20 0.00
July 0.840727E+12 0.246595E+12 744.00 0.825771E+12 0.149566E+11 0.00 0.99 31-JUL-23:23 0.78 01-JUL-04:10 394456.57 31-JUL-23:55 394456.57 31-JUL-23:55 16547.80 12-JUL-12:50 116091.94 21-JUL-16:00 0.00
August 0.107906E+13 0.306089E+12 744.00 0.106521E+13 0.138474E+11 0.00 1.00 01-AUG-06:40 0.39 31-AUG-24:00 423562.46 07-AUG-14:00 409616.88 06-AUG-15:54 89469.74 20-AUG-04:10 134496.65 30-AUG-16:00 0.00
September 0.340724E+12 0.972231E+11 720.00 0.327114E+12 0.136103E+11 0.00 0.55 30-SEP-23:20 0.34 22-SEP-06:10 212878.39 30-SEP-24:00 211605.14 30-SEP-24:00 14011.68 18-SEP-10:40 54317.16 30-SEP-23:20 0.00
October 0.485368E+12 0.136100E+12 708.31 0.470419E+12 0.149497E+11 0.00 0.76 31-OCT-24:00 0.01 18-OCT-04:12 303514.43 31-OCT-24:00 303514.43 31-OCT-24:00 80873.59 31-OCT-11:00 79184.37 05-OCT-15:00 0.00
November 0.417925E+12 0.108799E+12 679.49 0.381085E+12 0.368399E+11 0.00 0.86 28-NOV-09:00 0.01 26-NOV-09:40 358650.74 28-NOV-09:00 311604.57 03-NOV-14:00 132715.05 28-NOV-08:50 99154.86 02-NOV-13:00 0.00
December 0.499357E+12 0.124975E+12 718.97 0.447798E+12 0.515592E+11 0.00 1.00 08-DEC-11:20 0.01 19-DEC-21:30 431788.40 28-DEC-09:50 402932.62 13-DEC-18:00 235944.04 28-DEC-09:40 120444.25 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.598544E+13 0.164994E+13 8226.37 0.569724E+13 0.288193E+12 0.00                         0.00
Minimum of Months 0.382904E+11 0.118644E+11 494.56 0.341162E+11 0.417421E+10 0.00 0.49   0.00   206710.47   127695.78   14011.68   50169.67   0.00
Maximum of Months 0.107906E+13 0.306089E+12 744.00 0.106521E+13 0.751856E+11 0.00 1.00   0.78   431788.40   409616.88   235944.04   134496.65   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.500004E+10 0.113324E+10 744.00 0.489472E+10 0.105316E+09 0.00 0.34 01-JAN-17:03 0.14 05-JAN-07:55 2718.81 19-JAN-17:00 2670.29 01-JAN-17:17 398.64 31-JAN-17:00 704.22 02-JAN-15:00 0.00
February 0.945244E+10 0.206303E+10 672.00 0.926618E+10 0.186265E+09 0.00 0.57 26-FEB-17:42 0.39 17-FEB-07:20 4714.93 26-FEB-17:54 4714.93 26-FEB-17:54 393.39 24-FEB-17:00 1259.06 02-FEB-13:20 0.00
March 0.156588E+11 0.344335E+10 744.00 0.154535E+11 0.205244E+09 0.00 0.88 31-MAR-24:00 0.60 11-MAR-08:00 7680.64 31-MAR-24:00 7680.64 31-MAR-24:00 480.70 07-MAR-15:00 1901.42 30-MAR-13:00 0.00
April 0.204232E+11 0.487265E+10 720.00 0.201307E+11 0.292502E+09 0.00 1.00 28-APR-12:50 0.31 30-APR-23:55 8597.65 28-APR-17:20 8505.87 16-APR-18:15 551.99 28-APR-17:30 2685.94 28-APR-15:00 0.00
May 0.642048E+10 0.183532E+10 744.00 0.591644E+10 0.504039E+09 0.00 0.50 31-MAY-23:20 0.26 02-MAY-06:10 4057.69 31-MAY-23:10 3966.77 31-MAY-24:00 548.16 23-MAY-16:00 1030.77 31-MAY-23:20 0.00
June 0.112072E+11 0.321944E+10 720.00 0.106254E+11 0.581839E+09 0.00 0.71 30-JUN-23:55 0.48 01-JUN-06:10 5863.84 30-JUN-23:03 5842.81 30-JUN-24:00 682.70 29-JUN-15:00 1604.00 29-JUN-14:00 0.00
July 0.166897E+11 0.480878E+10 744.00 0.160371E+11 0.652530E+09 0.00 0.91 31-JUL-23:55 0.70 15-JUL-06:00 7719.89 31-JUL-24:00 7718.29 31-JUL-23:55 666.06 12-JUL-10:00 2358.40 21-JUL-16:00 0.00
August 0.217761E+11 0.616973E+10 744.00 0.211186E+11 0.657475E+09 0.00 1.00 01-AUG-10:30 0.33 31-AUG-24:00 8784.00 07-AUG-13:40 8297.21 06-AUG-17:55 739.52 07-AUG-13:40 2822.42 30-AUG-16:00 0.00
September 0.625484E+10 0.175008E+10 720.00 0.571383E+10 0.541003E+09 0.00 0.49 30-SEP-24:00 0.26 07-SEP-21:00 4019.99 30-SEP-24:00 3989.00 30-SEP-24:00 583.00 18-SEP-14:30 1018.31 09-SEP-17:00 0.00
October 0.113695E+11 0.299231E+10 744.00 0.109175E+11 0.451968E+09 0.00 0.69 31-OCT-24:00 0.43 28-OCT-07:00 5854.39 31-OCT-24:00 5844.30 31-OCT-24:00 685.11 24-OCT-14:05 1584.22 05-OCT-15:00 0.00
November 0.154616E+11 0.348474E+10 720.00 0.152084E+11 0.253215E+09 0.00 0.80 02-NOV-16:00 0.62 15-NOV-07:10 6709.07 07-NOV-16:40 6531.26 12-NOV-17:10 560.58 01-NOV-11:00 1971.43 01-NOV-14:00 0.00
December 0.207200E+11 0.441960E+10 744.00 0.205395E+11 0.180522E+09 0.00 1.00 15-DEC-17:00 0.78 20-DEC-07:40 8667.17 14-DEC-17:00 8398.00 10-DEC-16:53 565.40 12-DEC-15:00 2503.83 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.160434E+12 0.401923E+11 8760.00 0.155822E+12 0.461192E+10 0.00                         0.00
Minimum of Months 0.500004E+10 0.113324E+10 672.00 0.489472E+10 0.105316E+09 0.00 0.34   0.14   2718.81   2670.29   393.39   704.22   0.00
Maximum of Months 0.217761E+11 0.616973E+10 744.00 0.211186E+11 0.657475E+09 0.00 1.00   0.78   8784.00   8505.87   739.52   2822.42   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.351623E+11 0.818706E+10 744.00 0.341466E+11 0.101574E+10 0.00 0.33 19-JAN-17:00 0.04 10-JAN-07:10 25419.11 19-JAN-17:00 22879.44 01-JAN-17:30 3960.36 31-JAN-17:00 6533.83 19-JAN-17:00 0.00
February 0.804711E+11 0.177921E+11 672.00 0.786294E+11 0.184173E+10 0.00 0.56 27-FEB-17:00 0.28 06-FEB-07:10 44065.51 27-FEB-17:00 43330.78 26-FEB-17:54 3906.76 24-FEB-17:00 11780.61 24-FEB-14:00 0.00
March 0.141251E+12 0.313525E+11 744.00 0.139210E+12 0.204062E+10 0.00 0.86 31-MAR-24:00 0.50 13-MAR-06:55 71809.06 31-MAR-24:00 71809.06 31-MAR-24:00 4788.74 07-MAR-15:00 18105.63 30-MAR-13:00 0.00
April 0.192445E+12 0.460661E+11 720.00 0.189521E+12 0.292361E+10 0.00 1.00 28-APR-12:40 0.29 30-APR-23:55 82229.22 28-APR-17:20 79766.64 16-APR-18:15 5464.84 28-APR-17:30 25675.68 28-APR-15:00 0.00
May 0.593120E+11 0.169985E+11 744.00 0.543394E+11 0.497263E+10 0.00 0.49 31-MAY-23:20 0.25 02-MAY-06:10 38224.32 31-MAY-23:10 37168.52 31-MAY-24:00 5406.61 23-MAY-16:00 9712.46 31-MAY-23:20 0.00
June 0.106174E+12 0.305255E+11 720.00 0.100389E+12 0.578503E+10 0.00 0.71 30-JUN-23:55 0.46 07-JUN-06:10 56528.30 30-JUN-23:55 56356.97 30-JUN-24:00 6774.08 29-JUN-15:00 15367.98 29-JUN-14:00 0.00
July 0.158805E+12 0.457789E+11 744.00 0.152298E+12 0.650734E+10 0.00 0.91 31-JUL-23:55 0.69 11-JUL-21:20 73901.90 31-JUL-24:00 73873.71 31-JUL-24:00 6651.09 12-JUL-10:00 22609.51 21-JUL-16:00 0.00
August 0.206729E+12 0.586400E+11 744.00 0.200154E+12 0.657500E+10 0.00 1.00 01-AUG-09:50 0.29 31-AUG-24:00 83611.52 14-AUG-16:00 77558.79 03-AUG-18:00 7310.00 07-AUG-13:40 26977.47 30-AUG-16:00 0.00
September 0.569287E+11 0.159823E+11 720.00 0.516073E+11 0.532134E+10 0.00 0.48 30-SEP-23:50 0.24 28-SEP-06:10 37263.99 30-SEP-24:00 36936.72 30-SEP-24:00 5799.86 18-SEP-14:30 9454.69 09-SEP-17:00 0.00
October 0.105621E+12 0.279284E+11 744.00 0.101134E+12 0.448671E+10 0.00 0.67 31-OCT-24:00 0.38 28-OCT-07:00 54238.24 31-OCT-24:00 54113.87 31-OCT-24:00 6829.33 24-OCT-14:05 15093.69 05-OCT-15:00 0.00
November 0.140840E+12 0.320116E+11 720.00 0.138326E+12 0.251448E+10 0.00 0.80 02-NOV-16:00 0.56 15-NOV-07:40 64109.61 07-NOV-16:50 60609.65 06-NOV-17:00 5600.04 01-NOV-11:00 18807.20 01-NOV-14:00 0.00
December 0.187339E+12 0.403770E+11 744.00 0.185534E+12 0.180496E+10 0.00 1.00 15-DEC-17:00 0.70 20-DEC-07:10 82357.51 14-DEC-17:00 78069.53 15-DEC-17:00 5644.47 12-DEC-15:00 23843.12 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.147108E+13 0.371640E+12 8760.00 0.142529E+13 0.457892E+11 0.00                         0.00
Minimum of Months 0.351623E+11 0.818706E+10 672.00 0.341466E+11 0.101574E+10 0.00 0.33   0.04   25419.11   22879.44   3906.76   6533.83   0.00
Maximum of Months 0.206729E+12 0.586400E+11 744.00 0.200154E+12 0.657500E+10 0.00 1.00   0.70   83611.52   79766.64   7310.00   26977.47   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.246367E+10 0.589996E+09 671.56 0.236381E+10 99854633.74 0.00 0.33 19-JAN-17:00 0.00 04-JAN-07:10 2623.37 19-JAN-17:00 2375.56 01-JAN-17:17 398.81 31-JAN-17:00 674.55 19-JAN-16:50 0.00
February 0.726646E+10 0.162665E+10 671.75 0.708331E+10 0.183146E+09 0.00 0.55 27-FEB-17:00 0.00 05-FEB-09:45 4480.53 27-FEB-17:00 4391.22 26-FEB-17:43 391.59 24-FEB-17:00 1200.76 24-FEB-14:00 0.00
March 0.135633E+11 0.304002E+10 744.00 0.133598E+11 0.203456E+09 0.00 0.84 31-MAR-24:00 0.37 12-MAR-07:50 7094.97 31-MAR-24:00 7094.97 31-MAR-24:00 479.18 07-MAR-15:00 1834.66 30-MAR-13:00 0.00
April 0.191377E+11 0.460336E+10 720.00 0.188458E+11 0.291870E+09 0.00 1.00 28-APR-13:30 0.28 30-APR-23:55 8335.05 28-APR-17:20 8186.40 23-APR-17:58 543.72 28-APR-17:30 2616.39 28-APR-15:00 0.00
May 0.610987E+10 0.175227E+10 744.00 0.560978E+10 0.500092E+09 0.00 0.48 31-MAY-23:20 0.24 02-MAY-06:10 3810.97 31-MAY-23:10 3698.66 31-MAY-24:00 547.78 23-MAY-16:00 970.16 31-MAY-23:20 0.00
June 0.108075E+11 0.310972E+10 720.00 0.102280E+11 0.579555E+09 0.00 0.71 30-JUN-23:55 0.44 07-JUN-06:10 5698.59 30-JUN-23:55 5681.43 30-JUN-24:00 680.96 29-JUN-15:00 1574.43 29-JUN-14:00 0.00
July 0.160785E+11 0.464053E+10 744.00 0.154276E+11 0.650880E+09 0.00 0.89 31-JUL-23:55 0.67 15-JUL-06:00 7391.30 31-JUL-24:00 7388.31 31-JUL-24:00 666.76 12-JUL-10:00 2302.68 21-JUL-16:00 0.00
August 0.208483E+11 0.592667E+10 744.00 0.201905E+11 0.657728E+09 0.00 1.00 01-AUG-11:40 0.29 31-AUG-24:00 8486.67 09-AUG-17:00 8032.02 06-AUG-17:35 726.60 09-AUG-17:00 2749.09 30-AUG-16:00 0.00
September 0.582362E+10 0.163764E+10 720.00 0.528939E+10 0.534230E+09 0.00 0.47 30-SEP-23:30 0.23 28-SEP-06:20 3761.03 30-SEP-24:00 3729.16 30-SEP-24:00 580.59 18-SEP-14:30 1008.55 09-SEP-17:00 0.00
October 0.105314E+11 0.279878E+10 744.00 0.100826E+11 0.448776E+09 0.00 0.65 31-OCT-24:00 0.30 28-OCT-07:00 5365.55 31-OCT-24:00 5352.61 31-OCT-24:00 684.25 24-OCT-14:05 1544.06 05-OCT-15:00 0.00
November 0.135610E+11 0.311217E+10 720.00 0.133106E+11 0.250436E+09 0.00 0.79 02-NOV-16:00 0.47 16-NOV-07:05 6470.34 07-NOV-16:40 6130.94 06-NOV-17:00 560.64 01-NOV-11:00 1905.02 01-NOV-14:00 0.00
December 0.178591E+11 0.389457E+10 744.00 0.176792E+11 0.179844E+09 0.00 0.99 15-DEC-17:00 0.60 20-DEC-07:10 8297.11 14-DEC-17:00 7881.24 15-DEC-17:00 564.60 12-DEC-15:00 2403.17 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.144050E+12 0.367324E+11 8687.31 0.139471E+12 0.457987E+10 0.00                         0.00
Minimum of Months 0.246367E+10 0.589996E+09 671.56 0.236381E+10 99854633.74 0.00 0.33   0.00   2623.37   2375.56   391.59   674.55   0.00
Maximum of Months 0.208483E+11 0.592667E+10 744.00 0.201905E+11 0.657728E+09 0.00 1.00   0.67   8486.67   8186.40   726.60   2749.09   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.80 432.01 0.00 0.00 0.00
February 130.31 0.00 130.31 99.60 367.45 0.00 0.00 0.00
March 151.17 0.00 151.17 147.68 312.37 0.00 0.00 0.00
April 178.41 0.73 177.68 240.78 187.05 0.00 0.00 0.00
May 202.09 7.39 194.70 409.22 50.45 0.00 0.00 0.00
June 229.82 15.91 213.90 484.22 40.08 0.00 0.00 0.00
July 223.02 8.50 214.53 465.21 25.46 0.00 0.00 0.00
August 199.72 1.57 198.15 417.77 37.87 0.00 0.00 0.00
September 172.51 0.01 172.50 333.74 60.40 0.00 0.00 0.00
October 149.91 0.00 149.91 266.69 116.84 0.00 0.00 0.00
November 113.81 0.00 113.81 115.13 281.39 0.00 0.00 0.00
December 102.68 0.00 102.68 75.80 382.16 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 261.52 190.21 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.80 25.46 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 484.22 432.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.80 432.01 0.00 0.00 0.00
February 130.31 0.00 130.31 99.60 367.45 0.00 0.00 0.00
March 151.17 0.00 151.17 147.68 312.37 0.00 0.00 0.00
April 178.41 0.73 177.68 240.78 187.05 0.00 0.00 0.00
May 202.09 7.39 194.70 409.22 50.45 0.00 0.00 0.00
June 229.82 15.91 213.90 484.22 40.08 0.00 0.00 0.00
July 223.02 8.50 214.53 465.21 25.46 0.00 0.00 0.00
August 199.72 1.57 198.15 417.77 37.87 0.00 0.00 0.00
September 172.51 0.01 172.50 333.74 60.40 0.00 0.00 0.00
October 149.91 0.00 149.91 266.69 116.84 0.00 0.00 0.00
November 113.81 0.00 113.81 115.13 281.39 0.00 0.00 0.00
December 102.68 0.00 102.68 75.80 382.16 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 261.52 190.21 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.80 25.46 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 484.22 432.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.80 432.01 0.00 0.00 0.00
February 130.31 0.00 130.31 99.60 367.45 0.00 0.00 0.00
March 151.17 0.00 151.17 147.68 312.37 0.00 0.00 0.00
April 178.41 0.73 177.68 240.78 187.05 0.00 0.00 0.00
May 202.09 7.39 194.70 409.22 50.45 0.00 0.00 0.00
June 229.82 15.91 213.90 484.22 40.08 0.00 0.00 0.00
July 223.02 8.50 214.53 465.21 25.46 0.00 0.00 0.00
August 199.72 1.57 198.15 417.77 37.87 0.00 0.00 0.00
September 172.51 0.01 172.50 333.74 60.40 0.00 0.00 0.00
October 149.91 0.00 149.91 266.69 116.84 0.00 0.00 0.00
November 113.81 0.00 113.81 115.13 281.39 0.00 0.00 0.00
December 102.68 0.00 102.68 75.80 382.16 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 261.52 190.21 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.80 25.46 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 484.22 432.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.80 432.01 0.00 0.00 0.00
February 130.31 0.00 130.31 99.60 367.45 0.00 0.00 0.00
March 151.17 0.00 151.17 147.68 312.37 0.00 0.00 0.00
April 178.41 0.73 177.68 240.78 187.05 0.00 0.00 0.00
May 202.09 7.39 194.70 409.22 50.45 0.00 0.00 0.00
June 229.82 15.91 213.90 484.22 40.08 0.00 0.00 0.00
July 223.02 8.50 214.53 465.21 25.46 0.00 0.00 0.00
August 199.72 1.57 198.15 417.77 37.87 0.00 0.00 0.00
September 172.51 0.01 172.50 333.74 60.40 0.00 0.00 0.00
October 149.91 0.00 149.91 266.69 116.84 0.00 0.00 0.00
November 113.81 0.00 113.81 115.13 281.39 0.00 0.00 0.00
December 102.68 0.00 102.68 75.80 382.16 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 261.52 190.21 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.80 25.46 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 484.22 432.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.79 432.00 0.00 0.00 0.00
February 130.30 0.00 130.30 99.60 367.43 0.00 0.00 0.00
March 151.16 0.00 151.16 147.67 312.35 0.00 0.00 0.00
April 178.41 0.73 177.67 240.77 187.05 0.00 0.00 0.00
May 202.08 7.39 194.69 409.21 50.45 0.00 0.00 0.00
June 229.81 15.91 213.90 484.20 40.08 0.00 0.00 0.00
July 223.01 8.50 214.52 465.19 25.45 0.00 0.00 0.00
August 199.71 1.57 198.14 417.75 37.87 0.00 0.00 0.00
September 172.51 0.01 172.49 333.73 60.39 0.00 0.00 0.00
October 149.91 0.00 149.91 266.68 116.83 0.00 0.00 0.00
November 113.80 0.00 113.80 115.13 281.38 0.00 0.00 0.00
December 102.68 0.00 102.68 75.80 382.14 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 261.51 190.21 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.79 25.45 0.00 0.00 0.00
Maximum of Months 229.81 15.91 214.52 484.20 432.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 315.85 160.83 155.02 363.79 440.72 0.00 0.00 0.00
February 351.71 169.80 181.91 431.58 372.02 0.00 0.00 0.00
March 413.73 199.53 214.20 556.08 316.23 0.00 0.00 0.00
April 454.02 205.34 248.68 700.23 193.95 0.00 0.00 0.00
May 467.97 202.92 265.05 865.87 55.62 0.00 0.00 0.00
June 474.60 188.21 286.39 909.86 42.10 0.00 0.00 0.00
July 457.58 167.45 290.13 879.11 24.52 0.00 0.00 0.00
August 421.65 144.97 276.68 811.23 36.04 0.00 0.00 0.00
September 373.50 128.41 245.09 682.76 65.51 0.00 0.00 0.00
October 369.10 155.76 213.34 640.78 122.21 0.00 0.00 0.00
November 326.78 166.70 160.08 449.25 283.41 0.00 0.00 0.00
December 257.29 116.55 140.74 310.02 385.74 0.00 0.00 0.00
                 
Annual Sum or Average 390.45 167.13 223.32 634.47 193.92 0.00 0.00 0.00
Minimum of Months 257.29 116.55 140.74 310.02 24.52 0.00 0.00 0.00
Maximum of Months 474.60 205.34 290.13 909.86 440.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 315.85 160.83 155.02 363.79 440.72 0.00 0.00 0.00
February 351.71 169.80 181.91 431.58 372.02 0.00 0.00 0.00
March 413.73 199.53 214.20 556.08 316.23 0.00 0.00 0.00
April 454.02 205.34 248.68 700.23 193.95 0.00 0.00 0.00
May 467.97 202.92 265.05 865.87 55.62 0.00 0.00 0.00
June 474.60 188.21 286.39 909.86 42.10 0.00 0.00 0.00
July 457.58 167.45 290.13 879.11 24.52 0.00 0.00 0.00
August 421.65 144.97 276.68 811.23 36.04 0.00 0.00 0.00
September 373.50 128.41 245.09 682.76 65.51 0.00 0.00 0.00
October 369.10 155.76 213.34 640.78 122.21 0.00 0.00 0.00
November 326.78 166.70 160.08 449.25 283.41 0.00 0.00 0.00
December 257.29 116.55 140.74 310.02 385.74 0.00 0.00 0.00
                 
Annual Sum or Average 390.45 167.13 223.32 634.47 193.92 0.00 0.00 0.00
Minimum of Months 257.29 116.55 140.74 310.02 24.52 0.00 0.00 0.00
Maximum of Months 474.60 205.34 290.13 909.86 440.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 315.84 160.83 155.01 363.78 440.71 0.00 0.00 0.00
February 351.70 169.79 181.91 431.57 372.01 0.00 0.00 0.00
March 413.72 199.52 214.19 556.07 316.22 0.00 0.00 0.00
April 454.01 205.33 248.67 700.22 193.95 0.00 0.00 0.00
May 467.96 202.92 265.04 865.86 55.62 0.00 0.00 0.00
June 474.59 188.21 286.38 909.84 42.10 0.00 0.00 0.00
July 457.57 167.45 290.13 879.10 24.52 0.00 0.00 0.00
August 421.64 144.96 276.68 811.22 36.04 0.00 0.00 0.00
September 373.49 128.41 245.09 682.74 65.51 0.00 0.00 0.00
October 369.09 155.75 213.33 640.77 122.21 0.00 0.00 0.00
November 326.77 166.70 160.07 449.24 283.41 0.00 0.00 0.00
December 257.28 116.54 140.74 310.01 385.73 0.00 0.00 0.00
                 
Annual Sum or Average 390.44 167.13 223.31 634.46 193.91 0.00 0.00 0.00
Minimum of Months 257.28 116.54 140.74 310.01 24.52 0.00 0.00 0.00
Maximum of Months 474.59 205.33 290.13 909.84 440.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 907.88 388.08 0.00 0.00 0.00
February 579.04 374.80 204.24 840.13 335.95 0.00 0.00 0.00
March 369.67 166.83 202.84 550.27 297.36 0.00 0.00 0.00
April 273.99 64.20 209.79 451.05 190.91 0.00 0.00 0.00
May 209.35 8.90 200.45 428.93 51.96 0.00 0.00 0.00
June 206.80 1.93 204.88 436.95 41.54 0.00 0.00 0.00
July 216.49 3.98 212.51 453.66 25.25 0.00 0.00 0.00
August 254.69 30.57 224.12 534.89 40.54 0.00 0.00 0.00
September 305.58 80.53 225.05 595.21 64.46 0.00 0.00 0.00
October 474.12 246.97 227.15 848.51 121.77 0.00 0.00 0.00
November 603.34 415.41 187.94 930.13 264.50 0.00 0.00 0.00
December 623.84 448.01 175.83 919.70 350.66 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 657.21 180.25 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.93 25.25 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 930.13 388.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 907.88 388.08 0.00 0.00 0.00
February 579.04 374.80 204.24 840.13 335.95 0.00 0.00 0.00
March 369.67 166.83 202.84 550.27 297.36 0.00 0.00 0.00
April 273.99 64.20 209.79 451.05 190.91 0.00 0.00 0.00
May 209.35 8.90 200.45 428.93 51.96 0.00 0.00 0.00
June 206.80 1.93 204.88 436.95 41.54 0.00 0.00 0.00
July 216.49 3.98 212.51 453.66 25.25 0.00 0.00 0.00
August 254.69 30.57 224.12 534.89 40.54 0.00 0.00 0.00
September 305.58 80.53 225.05 595.21 64.46 0.00 0.00 0.00
October 474.12 246.97 227.15 848.51 121.77 0.00 0.00 0.00
November 603.34 415.41 187.93 930.13 264.50 0.00 0.00 0.00
December 623.84 448.01 175.83 919.70 350.66 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 657.21 180.25 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.93 25.25 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 930.13 388.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 907.88 388.08 0.00 0.00 0.00
February 579.04 374.80 204.24 840.13 335.95 0.00 0.00 0.00
March 369.67 166.83 202.84 550.27 297.36 0.00 0.00 0.00
April 273.99 64.20 209.79 451.05 190.91 0.00 0.00 0.00
May 209.35 8.90 200.45 428.93 51.96 0.00 0.00 0.00
June 206.80 1.93 204.88 436.95 41.54 0.00 0.00 0.00
July 216.49 3.98 212.51 453.66 25.25 0.00 0.00 0.00
August 254.69 30.57 224.12 534.89 40.54 0.00 0.00 0.00
September 305.58 80.53 225.05 595.21 64.46 0.00 0.00 0.00
October 474.12 246.97 227.15 848.51 121.77 0.00 0.00 0.00
November 603.34 415.41 187.94 930.13 264.50 0.00 0.00 0.00
December 623.84 448.01 175.83 919.70 350.66 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 657.21 180.25 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.93 25.25 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 930.13 388.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 907.88 388.08 0.00 0.00 0.00
February 579.04 374.80 204.24 840.13 335.95 0.00 0.00 0.00
March 369.67 166.83 202.84 550.27 297.36 0.00 0.00 0.00
April 273.99 64.20 209.79 451.05 190.91 0.00 0.00 0.00
May 209.35 8.90 200.45 428.93 51.96 0.00 0.00 0.00
June 206.80 1.93 204.88 436.95 41.54 0.00 0.00 0.00
July 216.49 3.98 212.51 453.66 25.25 0.00 0.00 0.00
August 254.69 30.57 224.12 534.89 40.54 0.00 0.00 0.00
September 305.58 80.53 225.05 595.21 64.46 0.00 0.00 0.00
October 474.12 246.97 227.15 848.51 121.77 0.00 0.00 0.00
November 603.34 415.41 187.93 930.13 264.50 0.00 0.00 0.00
December 623.84 448.01 175.83 919.70 350.66 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 657.21 180.25 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.93 25.25 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 930.13 388.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.42 455.31 183.12 907.85 388.06 0.00 0.00 0.00
February 579.01 374.79 204.23 840.10 335.93 0.00 0.00 0.00
March 369.65 166.83 202.83 550.24 297.35 0.00 0.00 0.00
April 273.98 64.20 209.78 451.04 190.90 0.00 0.00 0.00
May 209.34 8.90 200.45 428.92 51.96 0.00 0.00 0.00
June 206.80 1.93 204.87 436.93 41.53 0.00 0.00 0.00
July 216.48 3.98 212.50 453.65 25.25 0.00 0.00 0.00
August 254.68 30.57 224.11 534.87 40.54 0.00 0.00 0.00
September 305.57 80.53 225.04 595.18 64.46 0.00 0.00 0.00
October 474.10 246.96 227.14 848.48 121.76 0.00 0.00 0.00
November 603.32 415.39 187.93 930.09 264.49 0.00 0.00 0.00
December 623.82 447.99 175.83 919.67 350.65 0.00 0.00 0.00
                 
Annual Sum or Average 395.30 190.50 204.80 657.19 180.25 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.92 25.25 0.00 0.00 0.00
Maximum of Months 638.42 455.31 227.14 930.09 388.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 335.96 181.67 154.29 410.81 501.82 0.00 0.00 0.00
February 380.38 192.52 187.85 481.66 444.55 0.00 0.00 0.00
March 374.90 165.96 208.94 492.31 394.75 0.00 0.00 0.00
April 465.64 214.20 251.43 701.12 263.10 0.00 0.00 0.00
May 387.23 126.14 261.09 723.28 80.25 0.00 0.00 0.00
June 430.17 150.84 279.33 816.08 74.15 0.00 0.00 0.00
July 392.66 108.92 283.75 738.89 58.83 0.00 0.00 0.00
August 397.03 121.54 275.50 743.00 83.98 0.00 0.00 0.00
September 365.60 125.42 240.18 661.79 92.09 0.00 0.00 0.00
October 374.30 161.73 212.57 644.53 165.98 0.00 0.00 0.00
November 320.82 161.23 159.59 445.64 359.95 0.00 0.00 0.00
December 308.60 164.11 144.49 388.27 480.80 0.00 0.00 0.00
                 
Annual Sum or Average 377.56 155.82 221.74 604.38 249.00 0.00 0.00 0.00
Minimum of Months 308.60 108.92 144.49 388.27 58.83 0.00 0.00 0.00
Maximum of Months 465.64 214.20 283.75 816.08 501.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 335.96 181.67 154.29 410.81 501.82 0.00 0.00 0.00
February 380.38 192.52 187.85 481.66 444.55 0.00 0.00 0.00
March 374.90 165.96 208.94 492.31 394.75 0.00 0.00 0.00
April 465.64 214.20 251.43 701.12 263.10 0.00 0.00 0.00
May 387.23 126.14 261.09 723.28 80.25 0.00 0.00 0.00
June 430.17 150.84 279.33 816.08 74.15 0.00 0.00 0.00
July 392.66 108.92 283.75 738.89 58.83 0.00 0.00 0.00
August 397.03 121.54 275.50 743.00 83.98 0.00 0.00 0.00
September 365.60 125.42 240.18 661.79 92.09 0.00 0.00 0.00
October 374.30 161.73 212.57 644.53 165.98 0.00 0.00 0.00
November 320.82 161.23 159.59 445.64 359.95 0.00 0.00 0.00
December 308.60 164.11 144.49 388.27 480.80 0.00 0.00 0.00
                 
Annual Sum or Average 377.56 155.82 221.74 604.38 249.00 0.00 0.00 0.00
Minimum of Months 308.60 108.92 144.49 388.27 58.83 0.00 0.00 0.00
Maximum of Months 465.64 214.20 283.75 816.08 501.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 335.95 181.66 154.29 410.80 501.81 0.00 0.00 0.00
February 380.37 192.52 187.85 481.65 444.54 0.00 0.00 0.00
March 374.89 165.96 208.94 492.30 394.74 0.00 0.00 0.00
April 465.63 214.20 251.43 701.11 263.10 0.00 0.00 0.00
May 387.22 126.14 261.08 723.26 80.25 0.00 0.00 0.00
June 430.16 150.83 279.33 816.06 74.15 0.00 0.00 0.00
July 392.66 108.92 283.74 738.87 58.82 0.00 0.00 0.00
August 397.03 121.53 275.49 742.98 83.98 0.00 0.00 0.00
September 365.59 125.42 240.18 661.78 92.09 0.00 0.00 0.00
October 374.29 161.73 212.56 644.52 165.98 0.00 0.00 0.00
November 320.81 161.23 159.59 445.63 359.95 0.00 0.00 0.00
December 308.59 164.11 144.49 388.26 480.79 0.00 0.00 0.00
                 
Annual Sum or Average 377.55 155.81 221.74 604.37 249.00 0.00 0.00 0.00
Minimum of Months 308.59 108.92 144.49 388.26 58.82 0.00 0.00 0.00
Maximum of Months 465.63 214.20 283.74 816.06 501.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.27 0.00 552.27 426.25 1894.16 0.00 0.00 0.00
February 651.54 0.00 651.54 569.91 1589.08 0.00 0.00 0.00
March 755.84 0.00 755.84 805.49 1367.53 0.00 0.00 0.00
April 892.06 3.66 888.40 1242.64 858.75 0.00 0.00 0.00
May 1010.43 36.96 973.47 2054.63 239.98 0.00 0.00 0.00
June 1149.07 79.56 1069.51 2427.07 205.66 0.00 0.00 0.00
July 1115.10 42.48 1072.62 2337.27 132.99 0.00 0.00 0.00
August 998.59 7.85 990.74 2113.25 189.07 0.00 0.00 0.00
September 862.56 0.07 862.49 1684.07 273.70 0.00 0.00 0.00
October 749.55 0.00 749.55 1361.38 530.26 0.00 0.00 0.00
November 569.03 0.00 569.03 639.24 1213.15 0.00 0.00 0.00
December 513.39 0.00 513.39 453.06 1617.30 0.00 0.00 0.00
                 
Annual Sum or Average 819.11 14.26 804.85 1347.51 838.75 0.00 0.00 0.00
Minimum of Months 513.39 0.00 513.39 426.25 132.99 0.00 0.00 0.00
Maximum of Months 1149.07 79.56 1072.62 2427.07 1894.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 947.54 482.49 465.05 1108.57 1211.86 0.00 0.00 0.00
February 1055.12 509.38 545.73 1308.20 1024.41 0.00 0.00 0.00
March 1241.16 598.58 642.58 1663.65 889.08 0.00 0.00 0.00
April 1362.03 616.01 746.02 2075.46 583.35 0.00 0.00 0.00
May 1403.89 608.75 795.14 2565.57 171.84 0.00 0.00 0.00
June 1423.78 564.63 859.15 2696.54 146.60 0.00 0.00 0.00
July 1372.73 502.34 870.38 2601.39 96.53 0.00 0.00 0.00
August 1264.93 434.89 830.03 2401.46 135.94 0.00 0.00 0.00
September 1120.49 385.22 735.27 2025.27 194.69 0.00 0.00 0.00
October 1107.28 467.27 640.01 1900.45 361.42 0.00 0.00 0.00
November 980.33 500.11 480.23 1347.79 793.96 0.00 0.00 0.00
December 771.86 349.63 422.22 945.79 1057.96 0.00 0.00 0.00
                 
Annual Sum or Average 1171.32 501.38 669.94 1889.79 553.17 0.00 0.00 0.00
Minimum of Months 771.86 349.63 422.22 945.79 96.53 0.00 0.00 0.00
Maximum of Months 1423.78 616.01 870.38 2696.54 1211.86 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3192.21 2276.60 915.61 4505.70 1882.40 0.00 0.00 0.00
February 2895.15 1873.98 1021.17 4178.29 1613.71 0.00 0.00 0.00
March 1848.33 834.15 1014.17 2749.25 1402.35 0.00 0.00 0.00
April 1369.96 321.01 1048.94 2260.19 914.82 0.00 0.00 0.00
May 1046.75 44.49 1002.26 2149.73 249.07 0.00 0.00 0.00
June 1034.01 9.64 1024.37 2195.02 209.95 0.00 0.00 0.00
July 1082.44 19.90 1062.54 2283.20 129.34 0.00 0.00 0.00
August 1273.43 152.85 1120.58 2686.07 204.83 0.00 0.00 0.00
September 1527.90 402.67 1125.23 2965.51 308.36 0.00 0.00 0.00
October 2370.55 1234.83 1135.72 4214.63 600.67 0.00 0.00 0.00
November 3016.68 2077.02 939.66 4626.07 1274.39 0.00 0.00 0.00
December 3119.17 2240.02 879.15 4580.24 1670.00 0.00 0.00 0.00
                 
Annual Sum or Average 1976.55 952.52 1024.03 3278.43 867.69 0.00 0.00 0.00
Minimum of Months 1034.01 9.64 879.15 2149.73 129.34 0.00 0.00 0.00
Maximum of Months 3192.21 2276.60 1135.72 4626.07 1882.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1007.86 544.99 462.86 1275.14 1318.24 0.00 0.00 0.00
February 1141.12 577.56 563.55 1496.61 1132.02 0.00 0.00 0.00
March 1124.69 497.87 626.82 1528.76 980.95 0.00 0.00 0.00
April 1396.89 642.60 754.30 2153.72 659.35 0.00 0.00 0.00
May 1161.68 378.42 783.26 2187.45 206.53 0.00 0.00 0.00
June 1290.49 452.51 837.99 2475.84 183.76 0.00 0.00 0.00
July 1177.98 326.75 851.23 2263.62 127.15 0.00 0.00 0.00
August 1191.09 364.61 826.48 2291.23 173.66 0.00 0.00 0.00
September 1096.79 376.25 720.54 2002.28 230.75 0.00 0.00 0.00
October 1122.89 485.19 637.70 1965.12 419.12 0.00 0.00 0.00
November 962.45 483.69 478.76 1390.89 888.35 0.00 0.00 0.00
December 925.79 492.32 433.47 1232.58 1147.25 0.00 0.00 0.00
                 
Annual Sum or Average 1132.66 467.45 665.21 1856.57 619.51 0.00 0.00 0.00
Minimum of Months 925.79 326.75 433.47 1232.58 127.15 0.00 0.00 0.00
Maximum of Months 1396.89 642.60 851.23 2475.84 1318.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.27 0.00 552.27 460.09 1745.53 0.00 0.00 0.00
February 651.54 0.00 651.54 598.97 1467.39 0.00 0.00 0.00
March 755.84 0.00 755.84 823.95 1284.59 0.00 0.00 0.00
April 892.06 3.66 888.40 1237.41 837.14 0.00 0.00 0.00
May 1010.43 36.96 973.47 2020.13 256.80 0.00 0.00 0.00
June 1149.07 79.56 1069.51 2387.33 223.08 0.00 0.00 0.00
July 1115.10 42.48 1072.62 2292.50 149.54 0.00 0.00 0.00
August 998.59 7.85 990.74 2077.03 204.17 0.00 0.00 0.00
September 862.56 0.07 862.49 1651.45 285.72 0.00 0.00 0.00
October 749.55 0.00 749.55 1347.16 520.58 0.00 0.00 0.00
November 569.03 0.00 569.03 665.74 1120.86 0.00 0.00 0.00
December 513.39 0.00 513.39 482.53 1486.95 0.00 0.00 0.00
                 
Annual Sum or Average 819.11 14.26 804.85 1341.46 795.03 0.00 0.00 0.00
Minimum of Months 513.39 0.00 513.39 460.09 149.54 0.00 0.00 0.00
Maximum of Months 1149.07 79.56 1072.62 2387.33 1745.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 947.54 482.49 465.05 1152.36 1112.22 0.00 0.00 0.00
February 1055.12 509.38 545.73 1342.68 946.39 0.00 0.00 0.00
March 1241.16 598.58 642.58 1681.32 839.76 0.00 0.00 0.00
April 1362.03 616.01 746.02 2075.18 571.61 0.00 0.00 0.00
May 1403.89 608.75 795.14 2547.91 181.63 0.00 0.00 0.00
June 1423.78 564.63 859.15 2677.55 157.47 0.00 0.00 0.00
July 1372.73 502.34 870.38 2579.88 106.82 0.00 0.00 0.00
August 1264.93 434.89 830.03 2384.46 145.22 0.00 0.00 0.00
September 1120.49 385.22 735.27 2011.20 201.15 0.00 0.00 0.00
October 1107.28 467.27 640.01 1895.74 355.00 0.00 0.00 0.00
November 980.33 500.11 480.23 1369.65 742.99 0.00 0.00 0.00
December 771.86 349.63 422.22 977.07 972.35 0.00 0.00 0.00
                 
Annual Sum or Average 1171.32 501.38 669.94 1894.20 525.48 0.00 0.00 0.00
Minimum of Months 771.86 349.63 422.22 977.07 106.82 0.00 0.00 0.00
Maximum of Months 1423.78 616.01 870.38 2677.55 1112.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3192.21 2276.60 915.61 4539.59 1755.73 0.00 0.00 0.00
February 2895.15 1873.98 1021.17 4208.30 1506.92 0.00 0.00 0.00
March 1848.33 834.15 1014.17 2761.64 1326.70 0.00 0.00 0.00
April 1369.96 321.01 1048.94 2249.58 894.12 0.00 0.00 0.00
May 1046.75 44.49 1002.26 2115.36 266.09 0.00 0.00 0.00
June 1034.01 9.64 1024.37 2156.77 228.58 0.00 0.00 0.00
July 1082.44 19.90 1062.54 2236.97 145.01 0.00 0.00 0.00
August 1273.43 152.85 1120.58 2649.05 220.41 0.00 0.00 0.00
September 1527.90 402.67 1125.23 2933.91 320.01 0.00 0.00 0.00
October 2370.55 1234.83 1135.72 4194.57 593.56 0.00 0.00 0.00
November 3016.68 2077.02 939.66 4639.58 1209.15 0.00 0.00 0.00
December 3119.17 2240.02 879.15 4604.95 1558.71 0.00 0.00 0.00
                 
Annual Sum or Average 1976.55 952.52 1024.03 3269.57 831.79 0.00 0.00 0.00
Minimum of Months 1034.01 9.64 879.15 2115.36 145.01 0.00 0.00 0.00
Maximum of Months 3192.21 2276.60 1135.72 4639.58 1755.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1007.86 544.99 462.86 1291.18 1234.20 0.00 0.00 0.00
February 1141.12 577.56 563.55 1508.06 1061.91 0.00 0.00 0.00
March 1124.69 497.87 626.82 1532.84 931.77 0.00 0.00 0.00
April 1396.89 642.60 754.30 2142.92 644.25 0.00 0.00 0.00
May 1161.68 378.42 783.26 2165.47 215.33 0.00 0.00 0.00
June 1290.49 452.51 837.99 2451.28 192.91 0.00 0.00 0.00
July 1177.98 326.75 851.23 2237.36 135.74 0.00 0.00 0.00
August 1191.09 364.61 826.48 2268.31 182.66 0.00 0.00 0.00
September 1096.79 376.25 720.54 1983.03 236.61 0.00 0.00 0.00
October 1122.89 485.19 637.70 1953.16 413.19 0.00 0.00 0.00
November 962.45 483.69 478.76 1399.11 838.82 0.00 0.00 0.00
December 925.79 492.32 433.47 1245.47 1072.29 0.00 0.00 0.00
                 
Annual Sum or Average 1132.66 467.45 665.21 1849.38 594.11 0.00 0.00 0.00
Minimum of Months 925.79 326.75 433.47 1245.47 135.74 0.00 0.00 0.00
Maximum of Months 1396.89 642.60 851.23 2451.28 1234.20 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.189622E+09 0.115710E+10
February 0.315245E+09 0.00 0.315245E+09 0.240959E+09 0.888928E+09
March 0.404895E+09 0.00 0.404895E+09 0.395548E+09 0.836640E+09
April 0.462450E+09 1898057.14 0.460552E+09 0.624113E+09 0.484842E+09
May 0.541273E+09 19798542.17 0.521475E+09 0.109607E+10 0.135129E+09
June 0.595687E+09 41246703.62 0.554440E+09 0.125510E+10 0.103889E+09
July 0.597345E+09 22757759.15 0.574588E+09 0.124602E+10 68180344.45
August 0.534933E+09 4207320.32 0.530726E+09 0.111894E+10 0.101429E+09
September 0.447157E+09 34439.89 0.447123E+09 0.865056E+09 0.156550E+09
October 0.401523E+09 0.00 0.401523E+09 0.714306E+09 0.312931E+09
November 0.294987E+09 0.00 0.294987E+09 0.298418E+09 0.729366E+09
December 0.275018E+09 0.00 0.275018E+09 0.203019E+09 0.102357E+10
           
Annual Sum or Average 0.516636E+10 89942822.29 0.507641E+10 0.824717E+10 0.599856E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.189622E+09 68180344.45
Maximum of Months 0.597345E+09 41246703.62 0.574588E+09 0.125510E+10 0.115710E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.189622E+09 0.115710E+10
February 0.315244E+09 0.00 0.315244E+09 0.240959E+09 0.888928E+09
March 0.404895E+09 0.00 0.404895E+09 0.395547E+09 0.836640E+09
April 0.462450E+09 1898054.86 0.460552E+09 0.624113E+09 0.484842E+09
May 0.541273E+09 19798518.42 0.521474E+09 0.109607E+10 0.135129E+09
June 0.595687E+09 41246654.13 0.554440E+09 0.125510E+10 0.103889E+09
July 0.597345E+09 22757731.84 0.574587E+09 0.124602E+10 68180259.89
August 0.534933E+09 4207315.27 0.530726E+09 0.111894E+10 0.101429E+09
September 0.447157E+09 34439.85 0.447122E+09 0.865056E+09 0.156550E+09
October 0.401523E+09 0.00 0.401523E+09 0.714305E+09 0.312931E+09
November 0.294987E+09 0.00 0.294987E+09 0.298417E+09 0.729366E+09
December 0.275018E+09 0.00 0.275018E+09 0.203019E+09 0.102357E+10
           
Annual Sum or Average 0.516635E+10 89942714.37 0.507641E+10 0.824717E+10 0.599856E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.189622E+09 68180259.89
Maximum of Months 0.597345E+09 41246654.13 0.574587E+09 0.125510E+10 0.115710E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.189622E+09 0.115710E+10
February 0.315245E+09 0.00 0.315245E+09 0.240959E+09 0.888928E+09
March 0.404895E+09 0.00 0.404895E+09 0.395548E+09 0.836640E+09
April 0.462450E+09 1898057.14 0.460552E+09 0.624113E+09 0.484842E+09
May 0.541273E+09 19798542.17 0.521475E+09 0.109607E+10 0.135129E+09
June 0.595687E+09 41246703.62 0.554440E+09 0.125510E+10 0.103889E+09
July 0.597345E+09 22757759.15 0.574588E+09 0.124602E+10 68180344.45
August 0.534933E+09 4207320.32 0.530726E+09 0.111894E+10 0.101429E+09
September 0.447157E+09 34439.89 0.447123E+09 0.865056E+09 0.156550E+09
October 0.401523E+09 0.00 0.401523E+09 0.714306E+09 0.312931E+09
November 0.294987E+09 0.00 0.294987E+09 0.298418E+09 0.729366E+09
December 0.275018E+09 0.00 0.275018E+09 0.203019E+09 0.102357E+10
           
Annual Sum or Average 0.516636E+10 89942822.29 0.507641E+10 0.824717E+10 0.599856E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.189622E+09 68180344.45
Maximum of Months 0.597345E+09 41246703.62 0.574588E+09 0.125510E+10 0.115710E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.189622E+09 0.115710E+10
February 0.315244E+09 0.00 0.315244E+09 0.240959E+09 0.888928E+09
March 0.404895E+09 0.00 0.404895E+09 0.395547E+09 0.836640E+09
April 0.462450E+09 1898054.86 0.460552E+09 0.624113E+09 0.484842E+09
May 0.541273E+09 19798518.42 0.521474E+09 0.109607E+10 0.135129E+09
June 0.595687E+09 41246654.13 0.554440E+09 0.125510E+10 0.103889E+09
July 0.597345E+09 22757731.84 0.574587E+09 0.124602E+10 68180259.89
August 0.534933E+09 4207315.27 0.530726E+09 0.111894E+10 0.101429E+09
September 0.447157E+09 34439.85 0.447122E+09 0.865056E+09 0.156550E+09
October 0.401523E+09 0.00 0.401523E+09 0.714305E+09 0.312931E+09
November 0.294987E+09 0.00 0.294987E+09 0.298417E+09 0.729366E+09
December 0.275018E+09 0.00 0.275018E+09 0.203019E+09 0.102357E+10
           
Annual Sum or Average 0.516635E+10 89942714.37 0.507641E+10 0.824717E+10 0.599856E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.189622E+09 68180259.89
Maximum of Months 0.597345E+09 41246654.13 0.574587E+09 0.125510E+10 0.115710E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295829E+09 0.00 0.295829E+09 0.189615E+09 0.115706E+10
February 0.315232E+09 0.00 0.315232E+09 0.240950E+09 0.888892E+09
March 0.404879E+09 0.00 0.404879E+09 0.395532E+09 0.836607E+09
April 0.462432E+09 1897980.64 0.460534E+09 0.624088E+09 0.484823E+09
May 0.541251E+09 19797744.20 0.521454E+09 0.109602E+10 0.135123E+09
June 0.595663E+09 41245041.19 0.554418E+09 0.125505E+10 0.103885E+09
July 0.597321E+09 22756841.91 0.574564E+09 0.124597E+10 68177596.48
August 0.534912E+09 4207150.75 0.530705E+09 0.111890E+10 0.101425E+09
September 0.447139E+09 34438.50 0.447104E+09 0.865021E+09 0.156543E+09
October 0.401507E+09 0.00 0.401507E+09 0.714277E+09 0.312919E+09
November 0.294975E+09 0.00 0.294975E+09 0.298406E+09 0.729337E+09
December 0.275007E+09 0.00 0.275007E+09 0.203011E+09 0.102353E+10
           
Annual Sum or Average 0.516615E+10 89939197.20 0.507621E+10 0.824684E+10 0.599832E+10
Minimum of Months 0.275007E+09 0.00 0.275007E+09 0.189615E+09 68177596.48
Maximum of Months 0.597321E+09 41245041.19 0.574564E+09 0.125505E+10 0.115706E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.845971E+09 0.430772E+09 0.415200E+09 0.974370E+09 0.118043E+10
February 0.850854E+09 0.410770E+09 0.440084E+09 0.104407E+10 0.899987E+09
March 0.110812E+10 0.534417E+09 0.573705E+09 0.148940E+10 0.846987E+09
April 0.117681E+10 0.532238E+09 0.644570E+09 0.181500E+10 0.502724E+09
May 0.125340E+10 0.543500E+09 0.709904E+09 0.231915E+10 0.148982E+09
June 0.123016E+10 0.487847E+09 0.742311E+09 0.235835E+10 0.109125E+09
July 0.122558E+10 0.448497E+09 0.777086E+09 0.235462E+10 65665630.31
August 0.112934E+10 0.388275E+09 0.741062E+09 0.217280E+10 96537488.49
September 0.968114E+09 0.332835E+09 0.635280E+09 0.176970E+10 0.169798E+09
October 0.988586E+09 0.417180E+09 0.571406E+09 0.171628E+10 0.327324E+09
November 0.847016E+09 0.432096E+09 0.414920E+09 0.116445E+10 0.734608E+09
December 0.689122E+09 0.312157E+09 0.376965E+09 0.830356E+09 0.103316E+10
           
Annual Sum or Average 0.123131E+11 0.527058E+10 0.704249E+10 0.200085E+11 0.611533E+10
Minimum of Months 0.689122E+09 0.312157E+09 0.376965E+09 0.830356E+09 65665630.31
Maximum of Months 0.125340E+10 0.543500E+09 0.777086E+09 0.235835E+10 0.118043E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.845971E+09 0.430772E+09 0.415200E+09 0.974370E+09 0.118043E+10
February 0.850854E+09 0.410770E+09 0.440084E+09 0.104407E+10 0.899987E+09
March 0.110812E+10 0.534417E+09 0.573705E+09 0.148940E+10 0.846987E+09
April 0.117681E+10 0.532238E+09 0.644570E+09 0.181500E+10 0.502724E+09
May 0.125340E+10 0.543500E+09 0.709904E+09 0.231915E+10 0.148982E+09
June 0.123016E+10 0.487847E+09 0.742311E+09 0.235835E+10 0.109125E+09
July 0.122558E+10 0.448497E+09 0.777086E+09 0.235462E+10 65665630.31
August 0.112934E+10 0.388275E+09 0.741062E+09 0.217280E+10 96537488.49
September 0.968114E+09 0.332835E+09 0.635280E+09 0.176970E+10 0.169798E+09
October 0.988586E+09 0.417180E+09 0.571406E+09 0.171628E+10 0.327324E+09
November 0.847016E+09 0.432096E+09 0.414920E+09 0.116445E+10 0.734608E+09
December 0.689122E+09 0.312157E+09 0.376965E+09 0.830356E+09 0.103316E+10
           
Annual Sum or Average 0.123131E+11 0.527058E+10 0.704249E+10 0.200085E+11 0.611533E+10
Minimum of Months 0.689122E+09 0.312157E+09 0.376965E+09 0.830356E+09 65665630.31
Maximum of Months 0.125340E+10 0.543500E+09 0.777086E+09 0.235835E+10 0.118043E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.845956E+09 0.430764E+09 0.415192E+09 0.974353E+09 0.118040E+10
February 0.850839E+09 0.410762E+09 0.440076E+09 0.104405E+10 0.899970E+09
March 0.110810E+10 0.534407E+09 0.573695E+09 0.148938E+10 0.846972E+09
April 0.117679E+10 0.532228E+09 0.644558E+09 0.181497E+10 0.502714E+09
May 0.125338E+10 0.543490E+09 0.709891E+09 0.231911E+10 0.148979E+09
June 0.123014E+10 0.487838E+09 0.742298E+09 0.235831E+10 0.109123E+09
July 0.122556E+10 0.448489E+09 0.777071E+09 0.235457E+10 65664430.46
August 0.112932E+10 0.388268E+09 0.741048E+09 0.217276E+10 96535724.54
September 0.968097E+09 0.332828E+09 0.635268E+09 0.176967E+10 0.169795E+09
October 0.988568E+09 0.417173E+09 0.571395E+09 0.171624E+10 0.327318E+09
November 0.847001E+09 0.432088E+09 0.414912E+09 0.116442E+10 0.734594E+09
December 0.689109E+09 0.312151E+09 0.376958E+09 0.830341E+09 0.103314E+10
           
Annual Sum or Average 0.123128E+11 0.527049E+10 0.704236E+10 0.200082E+11 0.611522E+10
Minimum of Months 0.689109E+09 0.312151E+09 0.376958E+09 0.830341E+09 65664430.46
Maximum of Months 0.125338E+10 0.543490E+09 0.777071E+09 0.235831E+10 0.118040E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.243167E+10 0.103943E+10
February 0.140081E+10 0.906719E+09 0.494088E+09 0.203244E+10 0.812719E+09
March 0.990124E+09 0.446844E+09 0.543280E+09 0.147383E+10 0.796452E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116913E+10 0.494838E+09
May 0.560728E+09 23830137.60 0.536897E+09 0.114886E+10 0.139165E+09
June 0.536035E+09 4996364.11 0.531039E+09 0.113258E+10 0.107659E+09
July 0.579847E+09 10657518.52 0.569189E+09 0.121510E+10 67635935.68
August 0.682159E+09 81879609.18 0.600279E+09 0.143265E+10 0.108587E+09
September 0.792074E+09 0.208745E+09 0.583329E+09 0.154278E+10 0.167084E+09
October 0.126987E+10 0.661484E+09 0.608389E+09 0.227265E+10 0.326140E+09
November 0.156387E+10 0.107674E+10 0.487128E+09 0.241089E+10 0.685593E+09
December 0.167090E+10 0.119995E+10 0.470949E+09 0.246333E+10 0.939217E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207259E+11 0.568452E+10
Minimum of Months 0.536035E+09 4996364.11 0.470949E+09 0.113258E+10 67635935.68
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246333E+10 0.103943E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.243167E+10 0.103943E+10
February 0.140081E+10 0.906718E+09 0.494088E+09 0.203244E+10 0.812719E+09
March 0.990123E+09 0.446843E+09 0.543279E+09 0.147383E+10 0.796452E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116913E+10 0.494838E+09
May 0.560727E+09 23830109.01 0.536897E+09 0.114886E+10 0.139165E+09
June 0.536035E+09 4996358.11 0.531038E+09 0.113258E+10 0.107659E+09
July 0.579846E+09 10657505.73 0.569189E+09 0.121510E+10 67635853.96
August 0.682158E+09 81879510.93 0.600279E+09 0.143265E+10 0.108587E+09
September 0.792073E+09 0.208745E+09 0.583328E+09 0.154278E+10 0.167084E+09
October 0.126987E+10 0.661483E+09 0.608389E+09 0.227265E+10 0.326140E+09
November 0.156386E+10 0.107674E+10 0.487127E+09 0.241089E+10 0.685593E+09
December 0.167090E+10 0.119995E+10 0.470948E+09 0.246333E+10 0.939217E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207259E+11 0.568451E+10
Minimum of Months 0.536035E+09 4996358.11 0.470948E+09 0.113258E+10 67635853.96
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246333E+10 0.103943E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.243167E+10 0.103943E+10
February 0.140081E+10 0.906719E+09 0.494088E+09 0.203244E+10 0.812719E+09
March 0.990124E+09 0.446844E+09 0.543280E+09 0.147383E+10 0.796452E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116913E+10 0.494838E+09
May 0.560728E+09 23830137.60 0.536897E+09 0.114886E+10 0.139165E+09
June 0.536035E+09 4996364.11 0.531039E+09 0.113258E+10 0.107659E+09
July 0.579847E+09 10657518.52 0.569189E+09 0.121510E+10 67635935.68
August 0.682159E+09 81879609.18 0.600279E+09 0.143265E+10 0.108587E+09
September 0.792074E+09 0.208745E+09 0.583329E+09 0.154278E+10 0.167084E+09
October 0.126987E+10 0.661484E+09 0.608389E+09 0.227265E+10 0.326140E+09
November 0.156387E+10 0.107674E+10 0.487128E+09 0.241089E+10 0.685593E+09
December 0.167090E+10 0.119995E+10 0.470949E+09 0.246333E+10 0.939217E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207259E+11 0.568452E+10
Minimum of Months 0.536035E+09 4996364.11 0.470949E+09 0.113258E+10 67635935.68
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246333E+10 0.103943E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.243167E+10 0.103943E+10
February 0.140081E+10 0.906718E+09 0.494088E+09 0.203244E+10 0.812719E+09
March 0.990123E+09 0.446843E+09 0.543279E+09 0.147383E+10 0.796452E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116913E+10 0.494838E+09
May 0.560727E+09 23830109.01 0.536897E+09 0.114886E+10 0.139165E+09
June 0.536035E+09 4996358.11 0.531038E+09 0.113258E+10 0.107659E+09
July 0.579846E+09 10657505.73 0.569189E+09 0.121510E+10 67635853.96
August 0.682158E+09 81879510.93 0.600279E+09 0.143265E+10 0.108587E+09
September 0.792073E+09 0.208745E+09 0.583328E+09 0.154278E+10 0.167084E+09
October 0.126987E+10 0.661483E+09 0.608389E+09 0.227265E+10 0.326140E+09
November 0.156386E+10 0.107674E+10 0.487127E+09 0.241089E+10 0.685593E+09
December 0.167090E+10 0.119995E+10 0.470948E+09 0.246333E+10 0.939217E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207259E+11 0.568451E+10
Minimum of Months 0.536035E+09 4996358.11 0.470948E+09 0.113258E+10 67635853.96
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246333E+10 0.103943E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170995E+10 0.121949E+10 0.490460E+09 0.243157E+10 0.103938E+10
February 0.140075E+10 0.906682E+09 0.494068E+09 0.203236E+10 0.812686E+09
March 0.990084E+09 0.446826E+09 0.543258E+09 0.147377E+10 0.796420E+09
April 0.710166E+09 0.166409E+09 0.543756E+09 0.116909E+10 0.494818E+09
May 0.560705E+09 23829177.14 0.536876E+09 0.114881E+10 0.139160E+09
June 0.536013E+09 4996162.73 0.531017E+09 0.113253E+10 0.107655E+09
July 0.579823E+09 10657088.97 0.569166E+09 0.121505E+10 67633209.66
August 0.682131E+09 81876309.07 0.600255E+09 0.143259E+10 0.108582E+09
September 0.792042E+09 0.208737E+09 0.583305E+09 0.154271E+10 0.167077E+09
October 0.126982E+10 0.661457E+09 0.608365E+09 0.227256E+10 0.326127E+09
November 0.156380E+10 0.107669E+10 0.487108E+09 0.241079E+10 0.685565E+09
December 0.167083E+10 0.119990E+10 0.470930E+09 0.246323E+10 0.939179E+09
           
Annual Sum or Average 0.124661E+11 0.600756E+10 0.645856E+10 0.207251E+11 0.568429E+10
Minimum of Months 0.536013E+09 4996162.73 0.470930E+09 0.113253E+10 67633209.66
Maximum of Months 0.170995E+10 0.121949E+10 0.608365E+09 0.246323E+10 0.103938E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.899823E+09 0.486575E+09 0.413249E+09 0.110030E+10 0.134408E+10
February 0.920207E+09 0.465752E+09 0.454455E+09 0.116522E+10 0.107545E+10
March 0.100413E+10 0.444504E+09 0.559628E+09 0.131859E+10 0.105730E+10
April 0.120693E+10 0.555209E+09 0.651718E+09 0.181730E+10 0.681964E+09
May 0.103716E+10 0.337857E+09 0.699303E+09 0.193722E+10 0.214947E+09
June 0.111500E+10 0.390971E+09 0.724027E+09 0.211527E+10 0.192199E+09
July 0.105171E+10 0.291728E+09 0.759983E+09 0.197903E+10 0.157557E+09
August 0.106341E+10 0.325525E+09 0.737888E+09 0.199004E+10 0.224932E+09
September 0.947636E+09 0.325084E+09 0.622551E+09 0.171537E+10 0.238702E+09
October 0.100252E+10 0.433179E+09 0.569344E+09 0.172630E+10 0.444564E+09
November 0.831563E+09 0.417910E+09 0.413653E+09 0.115510E+10 0.932997E+09
December 0.826555E+09 0.439551E+09 0.387004E+09 0.103993E+10 0.128776E+10
           
Annual Sum or Average 0.119066E+11 0.491384E+10 0.699280E+10 0.190597E+11 0.785246E+10
Minimum of Months 0.826555E+09 0.291728E+09 0.387004E+09 0.103993E+10 0.157557E+09
Maximum of Months 0.120693E+10 0.555209E+09 0.759983E+09 0.211527E+10 0.134408E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.899823E+09 0.486575E+09 0.413249E+09 0.110030E+10 0.134408E+10
February 0.920207E+09 0.465752E+09 0.454455E+09 0.116522E+10 0.107545E+10
March 0.100413E+10 0.444504E+09 0.559628E+09 0.131859E+10 0.105730E+10
April 0.120693E+10 0.555209E+09 0.651718E+09 0.181730E+10 0.681964E+09
May 0.103716E+10 0.337857E+09 0.699303E+09 0.193722E+10 0.214947E+09
June 0.111500E+10 0.390971E+09 0.724027E+09 0.211527E+10 0.192199E+09
July 0.105171E+10 0.291728E+09 0.759983E+09 0.197903E+10 0.157557E+09
August 0.106341E+10 0.325525E+09 0.737888E+09 0.199004E+10 0.224932E+09
September 0.947636E+09 0.325084E+09 0.622551E+09 0.171537E+10 0.238702E+09
October 0.100252E+10 0.433179E+09 0.569344E+09 0.172630E+10 0.444564E+09
November 0.831563E+09 0.417910E+09 0.413653E+09 0.115510E+10 0.932997E+09
December 0.826555E+09 0.439551E+09 0.387004E+09 0.103993E+10 0.128776E+10
           
Annual Sum or Average 0.119066E+11 0.491384E+10 0.699280E+10 0.190597E+11 0.785246E+10
Minimum of Months 0.826555E+09 0.291728E+09 0.387004E+09 0.103993E+10 0.157557E+09
Maximum of Months 0.120693E+10 0.555209E+09 0.759983E+09 0.211527E+10 0.134408E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.899807E+09 0.486566E+09 0.413241E+09 0.110028E+10 0.134406E+10
February 0.920190E+09 0.465743E+09 0.454447E+09 0.116520E+10 0.107543E+10
March 0.100411E+10 0.444496E+09 0.559617E+09 0.131857E+10 0.105728E+10
April 0.120690E+10 0.555199E+09 0.651706E+09 0.181727E+10 0.681951E+09
May 0.103714E+10 0.337850E+09 0.699290E+09 0.193718E+10 0.214943E+09
June 0.111498E+10 0.390964E+09 0.724014E+09 0.211524E+10 0.192195E+09
July 0.105169E+10 0.291723E+09 0.759969E+09 0.197900E+10 0.157555E+09
August 0.106339E+10 0.325519E+09 0.737874E+09 0.199000E+10 0.224928E+09
September 0.947618E+09 0.325078E+09 0.622540E+09 0.171534E+10 0.238698E+09
October 0.100250E+10 0.433171E+09 0.569333E+09 0.172627E+10 0.444556E+09
November 0.831548E+09 0.417903E+09 0.413645E+09 0.115508E+10 0.932980E+09
December 0.826540E+09 0.439543E+09 0.386997E+09 0.103992E+10 0.128774E+10
           
Annual Sum or Average 0.119064E+11 0.491376E+10 0.699267E+10 0.190593E+11 0.785232E+10
Minimum of Months 0.826540E+09 0.291723E+09 0.386997E+09 0.103992E+10 0.157555E+09
Maximum of Months 0.120690E+10 0.555199E+09 0.759969E+09 0.211524E+10 0.134406E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147919E+10 0.00 0.147919E+10 0.114167E+10 0.507331E+10
February 0.157620E+10 0.00 0.157620E+10 0.137872E+10 0.384430E+10
March 0.202445E+10 0.00 0.202445E+10 0.215744E+10 0.366280E+10
April 0.231222E+10 9490170.94 0.230273E+10 0.322092E+10 0.222589E+10
May 0.270633E+10 98991513.86 0.260734E+10 0.550312E+10 0.642760E+09
June 0.297840E+10 0.206231E+09 0.277217E+10 0.629096E+10 0.533076E+09
July 0.298669E+10 0.113787E+09 0.287290E+10 0.626015E+10 0.356202E+09
August 0.267463E+10 21036347.24 0.265360E+10 0.566013E+10 0.506396E+09
September 0.223576E+10 172197.38 0.223559E+10 0.436511E+10 0.709430E+09
October 0.200759E+10 0.00 0.200759E+10 0.364633E+10 0.142026E+10
November 0.147492E+10 0.00 0.147492E+10 0.165692E+10 0.314448E+10
December 0.137507E+10 0.00 0.137507E+10 0.121348E+10 0.433177E+10
           
Annual Sum or Average 0.258315E+11 0.449709E+09 0.253818E+11 0.424949E+11 0.264507E+11
Minimum of Months 0.137507E+10 0.00 0.137507E+10 0.114167E+10 0.356202E+09
Maximum of Months 0.298669E+10 0.206231E+09 0.287290E+10 0.629096E+10 0.507331E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253789E+10 0.129230E+10 0.124559E+10 0.296918E+10 0.324585E+10
February 0.255254E+10 0.123230E+10 0.132024E+10 0.316481E+10 0.247824E+10
March 0.332433E+10 0.160323E+10 0.172110E+10 0.445592E+10 0.238132E+10
April 0.353039E+10 0.159670E+10 0.193369E+10 0.537959E+10 0.151204E+10
May 0.376017E+10 0.163048E+10 0.212969E+10 0.687161E+10 0.460263E+09
June 0.369044E+10 0.146352E+10 0.222691E+10 0.698944E+10 0.379984E+09
July 0.367671E+10 0.134548E+10 0.233123E+10 0.696757E+10 0.258555E+09
August 0.338798E+10 0.116481E+10 0.222316E+10 0.643207E+10 0.364094E+09
September 0.290431E+10 0.998493E+09 0.190582E+10 0.524950E+10 0.504639E+09
October 0.296573E+10 0.125153E+10 0.171420E+10 0.509016E+10 0.968039E+09
November 0.254102E+10 0.129628E+10 0.124475E+10 0.349348E+10 0.205795E+10
December 0.206734E+10 0.936461E+09 0.113088E+10 0.253321E+10 0.283365E+10
           
Annual Sum or Average 0.369388E+11 0.158116E+11 0.211273E+11 0.595966E+11 0.174446E+11
Minimum of Months 0.206734E+10 0.936461E+09 0.113088E+10 0.253321E+10 0.258555E+09
Maximum of Months 0.376017E+10 0.163048E+10 0.233123E+10 0.698944E+10 0.324585E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.855001E+10 0.609764E+10 0.245237E+10 0.120681E+11 0.504183E+10
February 0.700395E+10 0.453354E+10 0.247041E+10 0.101081E+11 0.390389E+10
March 0.495056E+10 0.223419E+10 0.271637E+10 0.736360E+10 0.375605E+10
April 0.355093E+10 0.832070E+09 0.271886E+10 0.585840E+10 0.237122E+10
May 0.280360E+10 0.119149E+09 0.268445E+10 0.575782E+10 0.667114E+09
June 0.268014E+10 24981518.47 0.265516E+10 0.568948E+10 0.544190E+09
July 0.289920E+10 53286948.24 0.284591E+10 0.611533E+10 0.346433E+09
August 0.341075E+10 0.409393E+09 0.300136E+10 0.719438E+10 0.548604E+09
September 0.396032E+10 0.104371E+10 0.291661E+10 0.768660E+10 0.799264E+09
October 0.634929E+10 0.330738E+10 0.304191E+10 0.112885E+11 0.160884E+10
November 0.781924E+10 0.538363E+10 0.243561E+10 0.119908E+11 0.330321E+10
December 0.835440E+10 0.599968E+10 0.235471E+10 0.122677E+11 0.447293E+10
           
Annual Sum or Average 0.623324E+11 0.300386E+11 0.322937E+11 0.103389E+12 0.273636E+11
Minimum of Months 0.268014E+10 24981518.47 0.235471E+10 0.568948E+10 0.346433E+09
Maximum of Months 0.855001E+10 0.609764E+10 0.304191E+10 0.122677E+11 0.504183E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.269944E+10 0.145971E+10 0.123973E+10 0.341535E+10 0.353078E+10
February 0.276059E+10 0.139724E+10 0.136335E+10 0.362060E+10 0.273858E+10
March 0.301236E+10 0.133350E+10 0.167887E+10 0.409463E+10 0.262737E+10
April 0.362074E+10 0.166561E+10 0.195513E+10 0.558244E+10 0.170903E+10
May 0.311145E+10 0.101356E+10 0.209789E+10 0.585886E+10 0.553168E+09
June 0.334496E+10 0.117290E+10 0.217206E+10 0.641739E+10 0.476306E+09
July 0.315510E+10 0.875176E+09 0.227992E+10 0.606288E+10 0.340561E+09
August 0.319021E+10 0.976566E+09 0.221364E+10 0.613684E+10 0.465121E+09
September 0.284288E+10 0.975243E+09 0.186763E+10 0.518990E+10 0.598098E+09
October 0.300754E+10 0.129952E+10 0.170801E+10 0.526337E+10 0.112257E+10
November 0.249466E+10 0.125372E+10 0.124095E+10 0.360519E+10 0.230261E+10
December 0.247964E+10 0.131864E+10 0.116100E+10 0.330135E+10 0.307279E+10
           
Annual Sum or Average 0.357196E+11 0.147414E+11 0.209782E+11 0.585488E+11 0.195370E+11
Minimum of Months 0.247964E+10 0.875176E+09 0.116100E+10 0.330135E+10 0.340561E+09
Maximum of Months 0.362074E+10 0.166561E+10 0.227992E+10 0.641739E+10 0.353078E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147919E+10 0.00 0.147919E+10 0.123230E+10 0.467524E+10
February 0.157620E+10 0.00 0.157620E+10 0.144902E+10 0.354992E+10
March 0.202445E+10 0.00 0.202445E+10 0.220686E+10 0.344065E+10
April 0.231222E+10 9490170.94 0.230273E+10 0.320738E+10 0.216988E+10
May 0.270633E+10 98991513.86 0.260734E+10 0.541072E+10 0.687823E+09
June 0.297840E+10 0.206231E+09 0.277217E+10 0.618795E+10 0.578213E+09
July 0.298669E+10 0.113787E+09 0.287290E+10 0.614024E+10 0.400533E+09
August 0.267463E+10 21036347.24 0.265360E+10 0.556312E+10 0.546841E+09
September 0.223576E+10 172197.38 0.223559E+10 0.428056E+10 0.740596E+09
October 0.200759E+10 0.00 0.200759E+10 0.360823E+10 0.139433E+10
November 0.147492E+10 0.00 0.147492E+10 0.172559E+10 0.290526E+10
December 0.137507E+10 0.00 0.137507E+10 0.129240E+10 0.398265E+10
           
Annual Sum or Average 0.258315E+11 0.449709E+09 0.253818E+11 0.423044E+11 0.250719E+11
Minimum of Months 0.137507E+10 0.00 0.137507E+10 0.123230E+10 0.400533E+09
Maximum of Months 0.298669E+10 0.206231E+09 0.287290E+10 0.618795E+10 0.467524E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253789E+10 0.129230E+10 0.124559E+10 0.308648E+10 0.297896E+10
February 0.255254E+10 0.123230E+10 0.132024E+10 0.324820E+10 0.228951E+10
March 0.332433E+10 0.160323E+10 0.172110E+10 0.450326E+10 0.224922E+10
April 0.353039E+10 0.159670E+10 0.193369E+10 0.537886E+10 0.148161E+10
May 0.376017E+10 0.163048E+10 0.212969E+10 0.682433E+10 0.486471E+09
June 0.369044E+10 0.146352E+10 0.222691E+10 0.694020E+10 0.408172E+09
July 0.367671E+10 0.134548E+10 0.233123E+10 0.690996E+10 0.286118E+09
August 0.338798E+10 0.116481E+10 0.222316E+10 0.638654E+10 0.388967E+09
September 0.290431E+10 0.998493E+09 0.190582E+10 0.521304E+10 0.521389E+09
October 0.296573E+10 0.125153E+10 0.171420E+10 0.507755E+10 0.950820E+09
November 0.254102E+10 0.129628E+10 0.124475E+10 0.355013E+10 0.192583E+10
December 0.206734E+10 0.936461E+09 0.113088E+10 0.261698E+10 0.260434E+10
           
Annual Sum or Average 0.369388E+11 0.158116E+11 0.211273E+11 0.597355E+11 0.165714E+11
Minimum of Months 0.206734E+10 0.936461E+09 0.113088E+10 0.261698E+10 0.286118E+09
Maximum of Months 0.376017E+10 0.163048E+10 0.233123E+10 0.694020E+10 0.297896E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.855001E+10 0.609764E+10 0.245237E+10 0.121588E+11 0.470256E+10
February 0.700395E+10 0.453354E+10 0.247041E+10 0.101807E+11 0.364555E+10
March 0.495056E+10 0.223419E+10 0.271637E+10 0.739677E+10 0.355342E+10
April 0.355093E+10 0.832070E+09 0.271886E+10 0.583090E+10 0.231756E+10
May 0.280360E+10 0.119149E+09 0.268445E+10 0.566579E+10 0.712682E+09
June 0.268014E+10 24981518.47 0.265516E+10 0.559033E+10 0.592471E+09
July 0.289920E+10 53286948.24 0.284591E+10 0.599151E+10 0.388382E+09
August 0.341075E+10 0.409393E+09 0.300136E+10 0.709521E+10 0.590339E+09
September 0.396032E+10 0.104371E+10 0.291661E+10 0.760469E+10 0.829462E+09
October 0.634929E+10 0.330738E+10 0.304191E+10 0.112347E+11 0.158980E+10
November 0.781924E+10 0.538363E+10 0.243561E+10 0.120258E+11 0.313412E+10
December 0.835440E+10 0.599968E+10 0.235471E+10 0.123339E+11 0.417484E+10
           
Annual Sum or Average 0.623324E+11 0.300386E+11 0.322937E+11 0.103109E+12 0.262312E+11
Minimum of Months 0.268014E+10 24981518.47 0.235471E+10 0.559033E+10 0.388382E+09
Maximum of Months 0.855001E+10 0.609764E+10 0.304191E+10 0.123339E+11 0.470256E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.269944E+10 0.145971E+10 0.123973E+10 0.345831E+10 0.330568E+10
February 0.276059E+10 0.139724E+10 0.136335E+10 0.364830E+10 0.256896E+10
March 0.301236E+10 0.133350E+10 0.167887E+10 0.410557E+10 0.249566E+10
April 0.362074E+10 0.166561E+10 0.195513E+10 0.555444E+10 0.166990E+10
May 0.311145E+10 0.101356E+10 0.209789E+10 0.579999E+10 0.576728E+09
June 0.334496E+10 0.117290E+10 0.217206E+10 0.635373E+10 0.500011E+09
July 0.315510E+10 0.875176E+09 0.227992E+10 0.599255E+10 0.363563E+09
August 0.319021E+10 0.976566E+09 0.221364E+10 0.607545E+10 0.489245E+09
September 0.284288E+10 0.975243E+09 0.186763E+10 0.514002E+10 0.613306E+09
October 0.300754E+10 0.129952E+10 0.170801E+10 0.523134E+10 0.110668E+10
November 0.249466E+10 0.125372E+10 0.124095E+10 0.362648E+10 0.217422E+10
December 0.247964E+10 0.131864E+10 0.116100E+10 0.333585E+10 0.287202E+10
           
Annual Sum or Average 0.357196E+11 0.147414E+11 0.209782E+11 0.583220E+11 0.187360E+11
Minimum of Months 0.247964E+10 0.875176E+09 0.116100E+10 0.333585E+10 0.363563E+09
Maximum of Months 0.362074E+10 0.166561E+10 0.227992E+10 0.635373E+10 0.330568E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 353.98 2160.05 552.27 0.00 552.27 0.00 0.00
February 498.01 1837.22 651.54 0.00 651.54 0.00 0.00
March 738.40 1561.82 755.85 0.00 755.85 0.00 0.00
April 1203.91 935.26 892.06 3.66 888.40 0.00 0.00
May 2046.10 252.25 1010.43 36.96 973.47 0.00 0.00
June 2421.09 200.40 1149.08 79.56 1069.51 0.00 0.00
July 2326.03 127.28 1115.11 42.48 1072.62 0.00 0.00
August 2088.81 189.35 998.60 7.85 990.74 0.00 0.00
September 1668.69 301.98 862.56 0.07 862.50 0.00 0.00
October 1333.45 584.17 749.55 0.00 749.55 0.00 0.00
November 575.65 1406.94 569.03 0.00 569.03 0.00 0.00
December 378.99 1910.78 513.40 0.00 513.40 0.00 0.00
               
Annual Sum or Average 1307.57 951.06 819.11 14.26 804.85 0.00 0.00
Minimum of Months 353.98 127.28 513.40 0.00 513.40 0.00 0.00
Maximum of Months 2421.09 2160.05 1149.08 79.56 1072.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1091.36 1322.15 947.54 482.49 465.05 0.00 0.00
February 1294.72 1116.05 1055.12 509.38 545.74 0.00 0.00
March 1668.23 948.68 1241.17 598.58 642.59 0.00 0.00
April 2100.69 581.85 1362.04 616.01 746.03 0.00 0.00
May 2597.60 166.87 1403.89 608.76 795.14 0.00 0.00
June 2729.55 126.30 1423.79 564.63 859.15 0.00 0.00
July 2637.32 73.55 1372.73 502.35 870.39 0.00 0.00
August 2433.68 108.13 1264.93 434.89 830.04 0.00 0.00
September 2048.26 196.52 1120.50 385.22 735.27 0.00 0.00
October 1922.34 366.62 1107.28 467.27 640.01 0.00 0.00
November 1347.73 850.24 980.34 500.11 480.23 0.00 0.00
December 930.05 1157.21 771.86 349.64 422.23 0.00 0.00
               
Annual Sum or Average 1903.39 581.74 1171.33 501.38 669.94 0.00 0.00
Minimum of Months 930.05 73.55 771.86 349.64 422.23 0.00 0.00
Maximum of Months 2729.55 1322.15 1423.79 616.01 870.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4539.37 1940.37 3192.22 2276.61 915.61 0.00 0.00
February 4200.62 1679.71 2895.16 1873.99 1021.17 0.00 0.00
March 2751.31 1486.79 1848.33 834.16 1014.18 0.00 0.00
April 2255.25 954.54 1369.96 321.02 1048.95 0.00 0.00
May 2144.65 259.79 1046.75 44.49 1002.26 0.00 0.00
June 2184.74 207.67 1034.01 9.64 1024.37 0.00 0.00
July 2268.31 126.26 1082.44 19.90 1062.55 0.00 0.00
August 2674.43 202.71 1273.43 152.85 1120.58 0.00 0.00
September 2976.01 322.30 1527.91 402.67 1125.24 0.00 0.00
October 4242.52 608.83 2370.56 1234.84 1135.72 0.00 0.00
November 4650.60 1322.51 3016.69 2077.02 939.67 0.00 0.00
December 4598.47 1753.30 3119.19 2240.03 879.15 0.00 0.00
               
Annual Sum or Average 3286.04 901.27 1976.55 952.52 1024.03 0.00 0.00
Minimum of Months 2144.65 126.26 1034.01 9.64 879.15 0.00 0.00
Maximum of Months 4650.60 1940.37 3192.22 2276.61 1135.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1232.41 1505.46 1007.86 545.00 462.87 0.00 0.00
February 1444.96 1333.64 1141.12 577.57 563.56 0.00 0.00
March 1476.91 1184.24 1124.69 497.87 626.82 0.00 0.00
April 2103.35 789.31 1396.90 642.60 754.30 0.00 0.00
May 2169.81 240.75 1161.69 378.42 783.26 0.00 0.00
June 2448.22 222.45 1290.50 452.51 837.99 0.00 0.00
July 2216.64 176.47 1177.98 326.75 851.23 0.00 0.00
August 2228.97 251.94 1191.09 364.61 826.48 0.00 0.00
September 1985.37 276.27 1096.79 376.25 720.54 0.00 0.00
October 1933.57 497.94 1122.89 485.19 637.70 0.00 0.00
November 1336.92 1079.85 962.45 483.69 478.76 0.00 0.00
December 1164.79 1442.38 925.80 492.33 433.47 0.00 0.00
               
Annual Sum or Average 1813.13 747.00 1132.66 467.45 665.22 0.00 0.00
Minimum of Months 1164.79 176.47 925.80 326.75 433.47 0.00 0.00
Maximum of Months 2448.22 1505.46 1396.90 642.60 851.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 426.25 1894.16 552.27 0.00 552.27 0.00 0.00
February 569.91 1589.08 651.54 0.00 651.54 0.00 0.00
March 805.49 1367.53 755.84 0.00 755.84 0.00 0.00
April 1242.64 858.75 892.06 3.66 888.40 0.00 0.00
May 2054.63 239.98 1010.43 36.96 973.47 0.00 0.00
June 2427.07 205.66 1149.07 79.56 1069.51 0.00 0.00
July 2337.27 132.99 1115.10 42.48 1072.62 0.00 0.00
August 2113.25 189.07 998.59 7.85 990.74 0.00 0.00
September 1684.07 273.70 862.56 0.07 862.49 0.00 0.00
October 1361.38 530.26 749.55 0.00 749.55 0.00 0.00
November 639.24 1213.15 569.03 0.00 569.03 0.00 0.00
December 453.06 1617.30 513.39 0.00 513.39 0.00 0.00
               
Annual Sum or Average 1347.51 838.75 819.11 14.26 804.85 0.00 0.00
Minimum of Months 426.25 132.99 513.39 0.00 513.39 0.00 0.00
Maximum of Months 2427.07 1894.16 1149.07 79.56 1072.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1108.57 1211.86 947.54 482.49 465.05 0.00 0.00
February 1308.20 1024.41 1055.12 509.38 545.73 0.00 0.00
March 1663.65 889.08 1241.16 598.58 642.58 0.00 0.00
April 2075.46 583.35 1362.03 616.01 746.02 0.00 0.00
May 2565.57 171.84 1403.89 608.75 795.14 0.00 0.00
June 2696.54 146.60 1423.78 564.63 859.15 0.00 0.00
July 2601.39 96.53 1372.73 502.34 870.38 0.00 0.00
August 2401.46 135.94 1264.93 434.89 830.03 0.00 0.00
September 2025.27 194.69 1120.49 385.22 735.27 0.00 0.00
October 1900.45 361.42 1107.28 467.27 640.01 0.00 0.00
November 1347.79 793.96 980.33 500.11 480.23 0.00 0.00
December 945.79 1057.96 771.86 349.63 422.22 0.00 0.00
               
Annual Sum or Average 1889.79 553.17 1171.32 501.38 669.94 0.00 0.00
Minimum of Months 945.79 96.53 771.86 349.63 422.22 0.00 0.00
Maximum of Months 2696.54 1211.86 1423.78 616.01 870.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4505.70 1882.40 3192.21 2276.60 915.61 0.00 0.00
February 4178.29 1613.71 2895.15 1873.98 1021.17 0.00 0.00
March 2749.25 1402.35 1848.33 834.15 1014.17 0.00 0.00
April 2260.19 914.82 1369.96 321.01 1048.94 0.00 0.00
May 2149.73 249.07 1046.75 44.49 1002.26 0.00 0.00
June 2195.02 209.95 1034.01 9.64 1024.37 0.00 0.00
July 2283.20 129.34 1082.44 19.90 1062.54 0.00 0.00
August 2686.07 204.83 1273.43 152.85 1120.58 0.00 0.00
September 2965.51 308.36 1527.90 402.67 1125.23 0.00 0.00
October 4214.63 600.67 2370.55 1234.83 1135.72 0.00 0.00
November 4626.07 1274.39 3016.68 2077.02 939.66 0.00 0.00
December 4580.24 1670.00 3119.17 2240.02 879.15 0.00 0.00
               
Annual Sum or Average 3278.43 867.69 1976.55 952.52 1024.03 0.00 0.00
Minimum of Months 2149.73 129.34 1034.01 9.64 879.15 0.00 0.00
Maximum of Months 4626.07 1882.40 3192.21 2276.60 1135.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1275.14 1318.24 1007.86 544.99 462.86 0.00 0.00
February 1496.61 1132.02 1141.12 577.56 563.55 0.00 0.00
March 1528.76 980.95 1124.69 497.87 626.82 0.00 0.00
April 2153.72 659.35 1396.89 642.60 754.30 0.00 0.00
May 2187.45 206.53 1161.68 378.42 783.26 0.00 0.00
June 2475.84 183.76 1290.49 452.51 837.99 0.00 0.00
July 2263.62 127.15 1177.98 326.75 851.23 0.00 0.00
August 2291.23 173.66 1191.09 364.61 826.48 0.00 0.00
September 2002.28 230.75 1096.79 376.25 720.54 0.00 0.00
October 1965.12 419.12 1122.89 485.19 637.70 0.00 0.00
November 1390.89 888.35 962.45 483.69 478.76 0.00 0.00
December 1232.58 1147.25 925.79 492.32 433.47 0.00 0.00
               
Annual Sum or Average 1856.57 619.51 1132.66 467.45 665.21 0.00 0.00
Minimum of Months 1232.58 127.15 925.79 326.75 433.47 0.00 0.00
Maximum of Months 2475.84 1318.24 1396.89 642.60 851.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 460.09 1745.53 552.27 0.00 552.27 0.00 0.00
February 598.97 1467.39 651.54 0.00 651.54 0.00 0.00
March 823.95 1284.59 755.84 0.00 755.84 0.00 0.00
April 1237.41 837.14 892.06 3.66 888.40 0.00 0.00
May 2020.13 256.80 1010.43 36.96 973.47 0.00 0.00
June 2387.33 223.08 1149.07 79.56 1069.51 0.00 0.00
July 2292.50 149.54 1115.10 42.48 1072.62 0.00 0.00
August 2077.03 204.17 998.59 7.85 990.74 0.00 0.00
September 1651.45 285.72 862.56 0.07 862.49 0.00 0.00
October 1347.16 520.58 749.55 0.00 749.55 0.00 0.00
November 665.74 1120.86 569.03 0.00 569.03 0.00 0.00
December 482.53 1486.95 513.39 0.00 513.39 0.00 0.00
               
Annual Sum or Average 1341.46 795.03 819.11 14.26 804.85 0.00 0.00
Minimum of Months 460.09 149.54 513.39 0.00 513.39 0.00 0.00
Maximum of Months 2387.33 1745.53 1149.07 79.56 1072.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1152.36 1112.22 947.54 482.49 465.05 0.00 0.00
February 1342.68 946.39 1055.12 509.38 545.73 0.00 0.00
March 1681.32 839.76 1241.16 598.58 642.58 0.00 0.00
April 2075.18 571.61 1362.03 616.01 746.02 0.00 0.00
May 2547.91 181.63 1403.89 608.75 795.14 0.00 0.00
June 2677.55 157.47 1423.78 564.63 859.15 0.00 0.00
July 2579.88 106.82 1372.73 502.34 870.38 0.00 0.00
August 2384.46 145.22 1264.93 434.89 830.03 0.00 0.00
September 2011.20 201.15 1120.49 385.22 735.27 0.00 0.00
October 1895.74 355.00 1107.28 467.27 640.01 0.00 0.00
November 1369.65 742.99 980.33 500.11 480.23 0.00 0.00
December 977.07 972.35 771.86 349.63 422.22 0.00 0.00
               
Annual Sum or Average 1894.20 525.48 1171.32 501.38 669.94 0.00 0.00
Minimum of Months 977.07 106.82 771.86 349.63 422.22 0.00 0.00
Maximum of Months 2677.55 1112.22 1423.78 616.01 870.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4539.59 1755.73 3192.21 2276.60 915.61 0.00 0.00
February 4208.30 1506.92 2895.15 1873.98 1021.17 0.00 0.00
March 2761.64 1326.70 1848.33 834.15 1014.17 0.00 0.00
April 2249.58 894.12 1369.96 321.01 1048.94 0.00 0.00
May 2115.36 266.09 1046.75 44.49 1002.26 0.00 0.00
June 2156.77 228.58 1034.01 9.64 1024.37 0.00 0.00
July 2236.97 145.01 1082.44 19.90 1062.54 0.00 0.00
August 2649.05 220.41 1273.43 152.85 1120.58 0.00 0.00
September 2933.91 320.01 1527.90 402.67 1125.23 0.00 0.00
October 4194.57 593.56 2370.55 1234.83 1135.72 0.00 0.00
November 4639.58 1209.15 3016.68 2077.02 939.66 0.00 0.00
December 4604.95 1558.71 3119.17 2240.02 879.15 0.00 0.00
               
Annual Sum or Average 3269.57 831.79 1976.55 952.52 1024.03 0.00 0.00
Minimum of Months 2115.36 145.01 1034.01 9.64 879.15 0.00 0.00
Maximum of Months 4639.58 1755.73 3192.21 2276.60 1135.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1291.18 1234.20 1007.86 544.99 462.86 0.00 0.00
February 1508.06 1061.91 1141.12 577.56 563.55 0.00 0.00
March 1532.84 931.77 1124.69 497.87 626.82 0.00 0.00
April 2142.92 644.25 1396.89 642.60 754.30 0.00 0.00
May 2165.47 215.33 1161.68 378.42 783.26 0.00 0.00
June 2451.28 192.91 1290.49 452.51 837.99 0.00 0.00
July 2237.36 135.74 1177.98 326.75 851.23 0.00 0.00
August 2268.31 182.66 1191.09 364.61 826.48 0.00 0.00
September 1983.03 236.61 1096.79 376.25 720.54 0.00 0.00
October 1953.16 413.19 1122.89 485.19 637.70 0.00 0.00
November 1399.11 838.82 962.45 483.69 478.76 0.00 0.00
December 1245.47 1072.29 925.79 492.32 433.47 0.00 0.00
               
Annual Sum or Average 1849.38 594.11 1132.66 467.45 665.21 0.00 0.00
Minimum of Months 1245.47 135.74 925.79 326.75 433.47 0.00 0.00
Maximum of Months 2451.28 1234.20 1396.89 642.60 851.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.948103E+09 0.578547E+10 0.147919E+10 0.00 0.147919E+10 0.00 0.00
February 0.120479E+10 0.444460E+10 0.157621E+10 0.00 0.157621E+10 0.00 0.00
March 0.197772E+10 0.418317E+10 0.202446E+10 0.00 0.202446E+10 0.00 0.00
April 0.312054E+10 0.242419E+10 0.231223E+10 9490204.64 0.230274E+10 0.00 0.00
May 0.548029E+10 0.675637E+09 0.270634E+10 98991865.38 0.260735E+10 0.00 0.00
June 0.627547E+10 0.519439E+09 0.297841E+10 0.206232E+09 0.277218E+10 0.00 0.00
July 0.623004E+10 0.340899E+09 0.298670E+10 0.113788E+09 0.287291E+10 0.00 0.00
August 0.559468E+10 0.507142E+09 0.267464E+10 21036421.94 0.265361E+10 0.00 0.00
September 0.432524E+10 0.782742E+09 0.223577E+10 172197.99 0.223559E+10 0.00 0.00
October 0.357150E+10 0.156464E+10 0.200760E+10 0.00 0.200760E+10 0.00 0.00
November 0.149208E+10 0.364680E+10 0.147492E+10 0.00 0.147492E+10 0.00 0.00
December 0.101509E+10 0.511783E+10 0.137508E+10 0.00 0.137508E+10 0.00 0.00
               
Annual Sum or Average 0.412355E+11 0.299926E+11 0.258316E+11 0.449710E+09 0.253818E+11 0.00 0.00
Minimum of Months 0.948103E+09 0.340899E+09 0.137508E+10 0.00 0.137508E+10 0.00 0.00
Maximum of Months 0.627547E+10 0.578547E+10 0.298670E+10 0.206232E+09 0.287291E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.292309E+10 0.354126E+10 0.253790E+10 0.129231E+10 0.124559E+10 0.00 0.00
February 0.313218E+10 0.269994E+10 0.255255E+10 0.123230E+10 0.132024E+10 0.00 0.00
March 0.446819E+10 0.254095E+10 0.332435E+10 0.160324E+10 0.172110E+10 0.00 0.00
April 0.544498E+10 0.150816E+10 0.353040E+10 0.159670E+10 0.193370E+10 0.00 0.00
May 0.695740E+10 0.446943E+09 0.376019E+10 0.163049E+10 0.212970E+10 0.00 0.00
June 0.707500E+10 0.327373E+09 0.369045E+10 0.146353E+10 0.222692E+10 0.00 0.00
July 0.706380E+10 0.196996E+09 0.367673E+10 0.134548E+10 0.233124E+10 0.00 0.00
August 0.651837E+10 0.289611E+09 0.338799E+10 0.116482E+10 0.222317E+10 0.00 0.00
September 0.530908E+10 0.509392E+09 0.290433E+10 0.998497E+09 0.190583E+10 0.00 0.00
October 0.514880E+10 0.981967E+09 0.296574E+10 0.125153E+10 0.171421E+10 0.00 0.00
November 0.349332E+10 0.220381E+10 0.254103E+10 0.129628E+10 0.124475E+10 0.00 0.00
December 0.249105E+10 0.309947E+10 0.206735E+10 0.936465E+09 0.113089E+10 0.00 0.00
               
Annual Sum or Average 0.600253E+11 0.183459E+11 0.369390E+11 0.158117E+11 0.211273E+11 0.00 0.00
Minimum of Months 0.249105E+10 0.196996E+09 0.206735E+10 0.936465E+09 0.113089E+10 0.00 0.00
Maximum of Months 0.707500E+10 0.354126E+10 0.376019E+10 0.163049E+10 0.233124E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121583E+11 0.519709E+10 0.855004E+10 0.609766E+10 0.245238E+10 0.00 0.00
February 0.101621E+11 0.406356E+10 0.700398E+10 0.453355E+10 0.247042E+10 0.00 0.00
March 0.736910E+10 0.398223E+10 0.495058E+10 0.223420E+10 0.271638E+10 0.00 0.00
April 0.584562E+10 0.247417E+10 0.355094E+10 0.832073E+09 0.271887E+10 0.00 0.00
May 0.574423E+10 0.695820E+09 0.280361E+10 0.119150E+09 0.268446E+10 0.00 0.00
June 0.566284E+10 0.538292E+09 0.268015E+10 24981607.18 0.265517E+10 0.00 0.00
July 0.607543E+10 0.338177E+09 0.289921E+10 53287137.46 0.284592E+10 0.00 0.00
August 0.716320E+10 0.542929E+09 0.341077E+10 0.409395E+09 0.300137E+10 0.00 0.00
September 0.771382E+10 0.835412E+09 0.396034E+10 0.104372E+10 0.291662E+10 0.00 0.00
October 0.113632E+11 0.163069E+10 0.634931E+10 0.330739E+10 0.304192E+10 0.00 0.00
November 0.120544E+11 0.342794E+10 0.781926E+10 0.538364E+10 0.243562E+10 0.00 0.00
December 0.123166E+11 0.469605E+10 0.835443E+10 0.599970E+10 0.235472E+10 0.00 0.00
               
Annual Sum or Average 0.103629E+12 0.284223E+11 0.623326E+11 0.300388E+11 0.322939E+11 0.00 0.00
Minimum of Months 0.566284E+10 0.338177E+09 0.268015E+10 24981607.18 0.235472E+10 0.00 0.00
Maximum of Months 0.123166E+11 0.519709E+10 0.855004E+10 0.609766E+10 0.304192E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.330088E+10 0.403222E+10 0.269945E+10 0.145972E+10 0.123974E+10 0.00 0.00
February 0.349565E+10 0.322634E+10 0.276060E+10 0.139725E+10 0.136336E+10 0.00 0.00
March 0.395575E+10 0.317187E+10 0.301238E+10 0.133350E+10 0.167887E+10 0.00 0.00
April 0.545188E+10 0.204588E+10 0.362076E+10 0.166562E+10 0.195514E+10 0.00 0.00
May 0.581162E+10 0.644837E+09 0.311146E+10 0.101356E+10 0.209789E+10 0.00 0.00
June 0.634578E+10 0.576593E+09 0.334497E+10 0.117291E+10 0.217207E+10 0.00 0.00
July 0.593706E+10 0.472669E+09 0.315511E+10 0.875179E+09 0.227993E+10 0.00 0.00
August 0.597008E+10 0.674792E+09 0.319022E+10 0.976570E+09 0.221365E+10 0.00 0.00
September 0.514607E+10 0.716102E+09 0.284289E+10 0.975247E+09 0.186764E+10 0.00 0.00
October 0.517887E+10 0.133368E+10 0.300755E+10 0.129953E+10 0.170802E+10 0.00 0.00
November 0.346529E+10 0.279897E+10 0.249467E+10 0.125372E+10 0.124095E+10 0.00 0.00
December 0.311979E+10 0.386327E+10 0.247965E+10 0.131864E+10 0.116101E+10 0.00 0.00
               
Annual Sum or Average 0.571787E+11 0.235572E+11 0.357197E+11 0.147414E+11 0.209783E+11 0.00 0.00
Minimum of Months 0.311979E+10 0.472669E+09 0.247965E+10 0.875179E+09 0.116101E+10 0.00 0.00
Maximum of Months 0.634578E+10 0.403222E+10 0.362076E+10 0.166562E+10 0.227993E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.114167E+10 0.507331E+10 0.147919E+10 0.00 0.147919E+10 0.00 0.00
February 0.137872E+10 0.384430E+10 0.157620E+10 0.00 0.157620E+10 0.00 0.00
March 0.215744E+10 0.366280E+10 0.202445E+10 0.00 0.202445E+10 0.00 0.00
April 0.322092E+10 0.222589E+10 0.231222E+10 9490170.94 0.230273E+10 0.00 0.00
May 0.550312E+10 0.642760E+09 0.270633E+10 98991513.86 0.260734E+10 0.00 0.00
June 0.629096E+10 0.533076E+09 0.297840E+10 0.206231E+09 0.277217E+10 0.00 0.00
July 0.626015E+10 0.356202E+09 0.298669E+10 0.113787E+09 0.287290E+10 0.00 0.00
August 0.566013E+10 0.506396E+09 0.267463E+10 21036347.24 0.265360E+10 0.00 0.00
September 0.436511E+10 0.709430E+09 0.223576E+10 172197.38 0.223559E+10 0.00 0.00
October 0.364633E+10 0.142026E+10 0.200759E+10 0.00 0.200759E+10 0.00 0.00
November 0.165692E+10 0.314448E+10 0.147492E+10 0.00 0.147492E+10 0.00 0.00
December 0.121348E+10 0.433177E+10 0.137507E+10 0.00 0.137507E+10 0.00 0.00
               
Annual Sum or Average 0.424949E+11 0.264507E+11 0.258315E+11 0.449709E+09 0.253818E+11 0.00 0.00
Minimum of Months 0.114167E+10 0.356202E+09 0.137507E+10 0.00 0.137507E+10 0.00 0.00
Maximum of Months 0.629096E+10 0.507331E+10 0.298669E+10 0.206231E+09 0.287290E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.296918E+10 0.324585E+10 0.253789E+10 0.129230E+10 0.124559E+10 0.00 0.00
February 0.316481E+10 0.247824E+10 0.255254E+10 0.123230E+10 0.132024E+10 0.00 0.00
March 0.445592E+10 0.238132E+10 0.332433E+10 0.160323E+10 0.172110E+10 0.00 0.00
April 0.537959E+10 0.151204E+10 0.353039E+10 0.159670E+10 0.193369E+10 0.00 0.00
May 0.687161E+10 0.460263E+09 0.376017E+10 0.163048E+10 0.212969E+10 0.00 0.00
June 0.698944E+10 0.379984E+09 0.369044E+10 0.146352E+10 0.222691E+10 0.00 0.00
July 0.696757E+10 0.258555E+09 0.367671E+10 0.134548E+10 0.233123E+10 0.00 0.00
August 0.643207E+10 0.364094E+09 0.338798E+10 0.116481E+10 0.222316E+10 0.00 0.00
September 0.524950E+10 0.504639E+09 0.290431E+10 0.998493E+09 0.190582E+10 0.00 0.00
October 0.509016E+10 0.968039E+09 0.296573E+10 0.125153E+10 0.171420E+10 0.00 0.00
November 0.349348E+10 0.205795E+10 0.254102E+10 0.129628E+10 0.124475E+10 0.00 0.00
December 0.253321E+10 0.283365E+10 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
               
Annual Sum or Average 0.595966E+11 0.174446E+11 0.369388E+11 0.158116E+11 0.211273E+11 0.00 0.00
Minimum of Months 0.253321E+10 0.258555E+09 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
Maximum of Months 0.698944E+10 0.324585E+10 0.376017E+10 0.163048E+10 0.233123E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.120681E+11 0.504183E+10 0.855001E+10 0.609764E+10 0.245237E+10 0.00 0.00
February 0.101081E+11 0.390389E+10 0.700395E+10 0.453354E+10 0.247041E+10 0.00 0.00
March 0.736360E+10 0.375605E+10 0.495056E+10 0.223419E+10 0.271637E+10 0.00 0.00
April 0.585840E+10 0.237122E+10 0.355093E+10 0.832070E+09 0.271886E+10 0.00 0.00
May 0.575782E+10 0.667114E+09 0.280360E+10 0.119149E+09 0.268445E+10 0.00 0.00
June 0.568948E+10 0.544190E+09 0.268014E+10 24981518.47 0.265516E+10 0.00 0.00
July 0.611533E+10 0.346433E+09 0.289920E+10 53286948.24 0.284591E+10 0.00 0.00
August 0.719438E+10 0.548604E+09 0.341075E+10 0.409393E+09 0.300136E+10 0.00 0.00
September 0.768660E+10 0.799264E+09 0.396032E+10 0.104371E+10 0.291661E+10 0.00 0.00
October 0.112885E+11 0.160884E+10 0.634929E+10 0.330738E+10 0.304191E+10 0.00 0.00
November 0.119908E+11 0.330321E+10 0.781924E+10 0.538363E+10 0.243561E+10 0.00 0.00
December 0.122677E+11 0.447293E+10 0.835440E+10 0.599968E+10 0.235471E+10 0.00 0.00
               
Annual Sum or Average 0.103389E+12 0.273636E+11 0.623324E+11 0.300386E+11 0.322937E+11 0.00 0.00
Minimum of Months 0.568948E+10 0.346433E+09 0.268014E+10 24981518.47 0.235471E+10 0.00 0.00
Maximum of Months 0.122677E+11 0.504183E+10 0.855001E+10 0.609764E+10 0.304191E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.341535E+10 0.353078E+10 0.269944E+10 0.145971E+10 0.123973E+10 0.00 0.00
February 0.362060E+10 0.273858E+10 0.276059E+10 0.139724E+10 0.136335E+10 0.00 0.00
March 0.409463E+10 0.262737E+10 0.301236E+10 0.133350E+10 0.167887E+10 0.00 0.00
April 0.558244E+10 0.170903E+10 0.362074E+10 0.166561E+10 0.195513E+10 0.00 0.00
May 0.585886E+10 0.553168E+09 0.311145E+10 0.101356E+10 0.209789E+10 0.00 0.00
June 0.641739E+10 0.476306E+09 0.334496E+10 0.117290E+10 0.217206E+10 0.00 0.00
July 0.606288E+10 0.340561E+09 0.315510E+10 0.875176E+09 0.227992E+10 0.00 0.00
August 0.613684E+10 0.465121E+09 0.319021E+10 0.976566E+09 0.221364E+10 0.00 0.00
September 0.518990E+10 0.598098E+09 0.284288E+10 0.975243E+09 0.186763E+10 0.00 0.00
October 0.526337E+10 0.112257E+10 0.300754E+10 0.129952E+10 0.170801E+10 0.00 0.00
November 0.360519E+10 0.230261E+10 0.249466E+10 0.125372E+10 0.124095E+10 0.00 0.00
December 0.330135E+10 0.307279E+10 0.247964E+10 0.131864E+10 0.116100E+10 0.00 0.00
               
Annual Sum or Average 0.585488E+11 0.195370E+11 0.357196E+11 0.147414E+11 0.209782E+11 0.00 0.00
Minimum of Months 0.330135E+10 0.340561E+09 0.247964E+10 0.875176E+09 0.116100E+10 0.00 0.00
Maximum of Months 0.641739E+10 0.353078E+10 0.362074E+10 0.166561E+10 0.227992E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.123230E+10 0.467524E+10 0.147919E+10 0.00 0.147919E+10 0.00 0.00
February 0.144902E+10 0.354992E+10 0.157620E+10 0.00 0.157620E+10 0.00 0.00
March 0.220686E+10 0.344065E+10 0.202445E+10 0.00 0.202445E+10 0.00 0.00
April 0.320738E+10 0.216988E+10 0.231222E+10 9490170.94 0.230273E+10 0.00 0.00
May 0.541072E+10 0.687823E+09 0.270633E+10 98991513.86 0.260734E+10 0.00 0.00
June 0.618795E+10 0.578213E+09 0.297840E+10 0.206231E+09 0.277217E+10 0.00 0.00
July 0.614024E+10 0.400533E+09 0.298669E+10 0.113787E+09 0.287290E+10 0.00 0.00
August 0.556312E+10 0.546841E+09 0.267463E+10 21036347.24 0.265360E+10 0.00 0.00
September 0.428056E+10 0.740596E+09 0.223576E+10 172197.38 0.223559E+10 0.00 0.00
October 0.360823E+10 0.139433E+10 0.200759E+10 0.00 0.200759E+10 0.00 0.00
November 0.172559E+10 0.290526E+10 0.147492E+10 0.00 0.147492E+10 0.00 0.00
December 0.129240E+10 0.398265E+10 0.137507E+10 0.00 0.137507E+10 0.00 0.00
               
Annual Sum or Average 0.423044E+11 0.250719E+11 0.258315E+11 0.449709E+09 0.253818E+11 0.00 0.00
Minimum of Months 0.123230E+10 0.400533E+09 0.137507E+10 0.00 0.137507E+10 0.00 0.00
Maximum of Months 0.618795E+10 0.467524E+10 0.298669E+10 0.206231E+09 0.287290E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.308648E+10 0.297896E+10 0.253789E+10 0.129230E+10 0.124559E+10 0.00 0.00
February 0.324820E+10 0.228951E+10 0.255254E+10 0.123230E+10 0.132024E+10 0.00 0.00
March 0.450326E+10 0.224922E+10 0.332433E+10 0.160323E+10 0.172110E+10 0.00 0.00
April 0.537886E+10 0.148161E+10 0.353039E+10 0.159670E+10 0.193369E+10 0.00 0.00
May 0.682433E+10 0.486471E+09 0.376017E+10 0.163048E+10 0.212969E+10 0.00 0.00
June 0.694020E+10 0.408172E+09 0.369044E+10 0.146352E+10 0.222691E+10 0.00 0.00
July 0.690996E+10 0.286118E+09 0.367671E+10 0.134548E+10 0.233123E+10 0.00 0.00
August 0.638654E+10 0.388967E+09 0.338798E+10 0.116481E+10 0.222316E+10 0.00 0.00
September 0.521304E+10 0.521389E+09 0.290431E+10 0.998493E+09 0.190582E+10 0.00 0.00
October 0.507755E+10 0.950820E+09 0.296573E+10 0.125153E+10 0.171420E+10 0.00 0.00
November 0.355013E+10 0.192583E+10 0.254102E+10 0.129628E+10 0.124475E+10 0.00 0.00
December 0.261698E+10 0.260434E+10 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
               
Annual Sum or Average 0.597355E+11 0.165714E+11 0.369388E+11 0.158116E+11 0.211273E+11 0.00 0.00
Minimum of Months 0.261698E+10 0.286118E+09 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
Maximum of Months 0.694020E+10 0.297896E+10 0.376017E+10 0.163048E+10 0.233123E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121588E+11 0.470256E+10 0.855001E+10 0.609764E+10 0.245237E+10 0.00 0.00
February 0.101807E+11 0.364555E+10 0.700395E+10 0.453354E+10 0.247041E+10 0.00 0.00
March 0.739677E+10 0.355342E+10 0.495056E+10 0.223419E+10 0.271637E+10 0.00 0.00
April 0.583090E+10 0.231756E+10 0.355093E+10 0.832070E+09 0.271886E+10 0.00 0.00
May 0.566579E+10 0.712682E+09 0.280360E+10 0.119149E+09 0.268445E+10 0.00 0.00
June 0.559033E+10 0.592471E+09 0.268014E+10 24981518.47 0.265516E+10 0.00 0.00
July 0.599151E+10 0.388382E+09 0.289920E+10 53286948.24 0.284591E+10 0.00 0.00
August 0.709521E+10 0.590339E+09 0.341075E+10 0.409393E+09 0.300136E+10 0.00 0.00
September 0.760469E+10 0.829462E+09 0.396032E+10 0.104371E+10 0.291661E+10 0.00 0.00
October 0.112347E+11 0.158980E+10 0.634929E+10 0.330738E+10 0.304191E+10 0.00 0.00
November 0.120258E+11 0.313412E+10 0.781924E+10 0.538363E+10 0.243561E+10 0.00 0.00
December 0.123339E+11 0.417484E+10 0.835440E+10 0.599968E+10 0.235471E+10 0.00 0.00
               
Annual Sum or Average 0.103109E+12 0.262312E+11 0.623324E+11 0.300386E+11 0.322937E+11 0.00 0.00
Minimum of Months 0.559033E+10 0.388382E+09 0.268014E+10 24981518.47 0.235471E+10 0.00 0.00
Maximum of Months 0.123339E+11 0.470256E+10 0.855001E+10 0.609764E+10 0.304191E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.345831E+10 0.330568E+10 0.269944E+10 0.145971E+10 0.123973E+10 0.00 0.00
February 0.364830E+10 0.256896E+10 0.276059E+10 0.139724E+10 0.136335E+10 0.00 0.00
March 0.410557E+10 0.249566E+10 0.301236E+10 0.133350E+10 0.167887E+10 0.00 0.00
April 0.555444E+10 0.166990E+10 0.362074E+10 0.166561E+10 0.195513E+10 0.00 0.00
May 0.579999E+10 0.576728E+09 0.311145E+10 0.101356E+10 0.209789E+10 0.00 0.00
June 0.635373E+10 0.500011E+09 0.334496E+10 0.117290E+10 0.217206E+10 0.00 0.00
July 0.599255E+10 0.363563E+09 0.315510E+10 0.875176E+09 0.227992E+10 0.00 0.00
August 0.607545E+10 0.489245E+09 0.319021E+10 0.976566E+09 0.221364E+10 0.00 0.00
September 0.514002E+10 0.613306E+09 0.284288E+10 0.975243E+09 0.186763E+10 0.00 0.00
October 0.523134E+10 0.110668E+10 0.300754E+10 0.129952E+10 0.170801E+10 0.00 0.00
November 0.362648E+10 0.217422E+10 0.249466E+10 0.125372E+10 0.124095E+10 0.00 0.00
December 0.333585E+10 0.287202E+10 0.247964E+10 0.131864E+10 0.116100E+10 0.00 0.00
               
Annual Sum or Average 0.583220E+11 0.187360E+11 0.357196E+11 0.147414E+11 0.209782E+11 0.00 0.00
Minimum of Months 0.333585E+10 0.363563E+09 0.247964E+10 0.875176E+09 0.116100E+10 0.00 0.00
Maximum of Months 0.635373E+10 0.330568E+10 0.362074E+10 0.166561E+10 0.227992E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.57 11.02 8.64 3.24 3.13 48.31 209.17 0.01
February 15.49 12.82 10.40 2.82 4.36 58.07 218.23 0.02
March 17.07 13.58 10.72 3.68 7.24 76.61 186.08 0.03
April 21.23 17.54 15.23 2.65 11.47 90.28 216.86 0.02
May 26.90 22.82 21.10 3.11 19.64 106.10 173.47 0.04
June 27.61 23.37 21.62 2.44 19.77 115.40 187.69 0.03
July 27.94 24.58 23.34 2.53 20.70 123.49 154.05 0.05
August 27.43 23.90 22.52 3.20 20.40 118.51 145.78 0.03
September 26.23 23.37 22.24 3.39 19.02 101.73 135.58 0.05
October 24.23 20.47 18.40 4.11 16.60 78.24 178.15 0.01
November 18.91 15.31 12.62 2.63 7.99 49.56 205.43 0.01
December 15.68 12.88 10.53 3.17 6.01 45.08 191.18 0.02
                 
Annual Sum or Average 21.89 18.50 16.48 3.09 13.08 84.44 183.16 0.03
Minimum of Months 13.57 11.02 8.64 2.44 3.13 45.08 135.58 0.01
Maximum of Months 27.94 24.58 23.34 4.11 20.70 123.49 218.23 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 27.00 02-JAN-14:00 18.67 14.00 1.50 17.75 146.50 0.00
February 28.30 02-FEB-12:00 20.78 17.20 6.60 17.93 127.50 748.50
March 30.00 26-MAR-13:00 19.88 14.40 3.00 19.52 288.50 548.00
April 33.30 28-APR-14:00 23.06 18.80 4.10 23.15 150.50 762.50
May 33.90 07-MAY-13:00 23.76 19.40 4.10 23.15 287.50 507.50
June 35.00 14-JUN-13:00 23.95 19.40 2.10 24.16 194.50 712.50
July 36.10 21-JUL-15:00 25.96 22.20 1.50 26.65 216.00 245.00
August 36.30 30-AUG-15:00 23.74 18.50 2.40 25.33 116.00 698.50
September 36.40 09-SEP-16:00 26.65 23.40 4.40 26.48 114.00 401.50
October 34.00 05-OCT-14:00 24.05 20.00 2.60 29.55 169.50 606.00
November 30.00 01-NOV-13:00 25.01 23.30 2.00 26.48 216.50 118.00
December 30.00 13-DEC-14:00 21.84 18.00 3.10 20.92 101.50 682.50
                 
Annual Sum or Average                
Minimum of Months 27.00   18.67 14.00 1.50 17.75 101.50 0.00
Maximum of Months 36.40   26.65 23.40 6.60 29.55 288.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.00 05-JAN-05:00 -0.0 -0.0 2.10 -16.0 0.00 0.00
February -3.4 05-FEB-07:10 -5.4 -9.4 4.68 -21.3 0.00 0.00
March 1.10 09-MAR-05:00 -2.1 -7.3 3.60 -14.4 0.00 0.00
April 8.30 11-APR-05:00 6.95 5.50 0.00 -6.9 0.00 0.00
May 21.10 07-MAY-00:00 19.58 18.90 0.00 11.46 0.00 0.00
June 20.60 07-JUN-01:00 18.00 16.70 3.60 10.50 0.00 0.00
July 22.20 11-JUL-19:00 21.37 21.10 2.10 20.22 0.00 0.00
August 20.20 25-AUG-23:00 20.20 20.20 5.30 11.84 0.00 0.00
September 19.20 07-SEP-17:00 19.20 19.20 2.50 16.85 35.00 7.00
October 10.00 28-OCT-04:00 5.56 0.00 3.60 -0.1 0.00 0.00
November 7.20 12-NOV-07:49 4.12 0.18 4.60 -9.0 36.00 517.00
December 0.00 21-DEC-04:00 -0.9 -2.0 2.10 -16.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -3.4   -5.4 -9.4 0.00 -21.3 0.00 0.00
Maximum of Months 22.20   21.37 21.10 5.30 20.22 36.00 517.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 22.11 31-JAN-12:00 25.00 21.00 5.70 20.92 336.50 96.00
February 21.49 24-FEB-12:00 27.70 18.80 4.10 17.75 165.00 746.50
March 22.77 30-MAR-12:00 29.40 20.00 2.50 27.14 340.00 0.00
April 25.55 28-APR-15:00 32.20 23.30 3.60 22.47 156.00 575.50
May 25.84 27-MAY-13:00 31.70 23.90 3.10 22.13 168.50 735.50
June 26.52 29-JUN-16:00 29.40 25.60 1.50 26.32 164.00 36.00
July 27.17 22-JUL-10:00 32.20 25.60 2.10 21.96 191.00 719.50
August 27.24 07-AUG-12:00 31.00 26.00 3.10 27.95 473.00 200.00
September 27.79 10-SEP-12:00 35.00 25.50 2.90 24.66 239.50 662.00
October 28.18 07-OCT-07:00 29.00 28.00 2.60 21.09 95.00 500.50
November 25.01 01-NOV-13:00 30.00 23.30 2.00 26.48 216.50 118.00
December 24.12 12-DEC-13:00 27.00 23.00 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 21.49   25.00 18.80 1.50 17.75 95.00 0.00
Maximum of Months 28.18   35.00 28.00 5.70 27.95 473.00 746.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 31-JAN-12:00 25.00 22.11 5.70 20.92 336.50 96.00
February 20.20 02-FEB-22:00 21.50 20.56 4.80 14.65 0.00 0.00
March 21.10 07-MAR-08:00 23.30 21.69 2.00 13.91 126.00 566.50
April 23.30 28-APR-15:00 32.20 25.55 3.60 22.47 156.00 575.50
May 24.40 26-MAY-08:20 27.07 25.09 3.10 23.71 252.67 47.33
June 25.60 29-JUN-14:00 27.20 26.00 5.10 24.16 335.00 238.00
July 25.60 02-JUL-05:00 26.10 25.71 2.60 19.52 30.50 8.50
August 26.60 09-AUG-18:00 26.60 26.60 1.90 19.52 26.00 23.00
September 25.50 10-SEP-12:00 35.00 27.79 2.90 24.66 239.50 662.00
October 28.00 07-OCT-07:00 29.00 28.18 2.60 21.09 95.00 500.50
November 23.80 01-NOV-10:00 26.10 24.39 2.00 22.64 228.50 113.00
December 23.00 12-DEC-13:00 27.00 24.12 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 20.20   21.50 20.56 1.90 13.91 0.00 0.00
Maximum of Months 28.00   35.00 28.18 5.70 24.66 336.50 662.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.46 29.60 0.00
February 18.00 13.00 16.00 20.78 36.65 0.00
March 18.00 13.00 16.00 22.23 38.94 0.00
April 18.00 13.00 16.00 24.49 49.11 0.00
May 18.00 13.00 16.00 26.95 46.95 0.00
June 18.00 13.00 16.00 28.93 51.71 0.00
July 18.00 13.00 16.00 29.89 48.43 0.00
August 18.00 13.00 16.00 29.58 45.50 0.00
September 18.00 13.00 16.00 28.08 39.22 0.00
October 18.00 13.00 16.00 25.80 37.51 0.00
November 18.00 13.00 16.00 23.35 31.26 0.00
December 18.00 13.00 16.00 21.40 27.18 0.00
             
Annual Sum or Average 18.00 13.00 16.00 25.18 40.17 0.00
Minimum of Months 18.00 13.00 16.00 20.46 27.18 0.00
Maximum of Months 18.00 13.00 16.00 29.89 51.71 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.316654E+11 -0.306424E+11 0.00 0.00 744.00 0.00 -0.102298E+10 58.98 0.00 0.00
February 0.285447E+11 -0.276197E+11 0.00 0.00 672.00 0.00 -925033711.4 58.98 0.00 0.00
March 0.322693E+11 -0.312421E+11 0.00 0.00 744.00 0.00 -0.102719E+10 58.97 0.00 0.00
April 0.275772E+11 -0.265862E+11 0.00 0.00 720.00 0.00 -991009905.9 58.97 0.00 0.00
May 0.274213E+11 -0.263973E+11 0.00 0.00 744.00 0.00 -0.102402E+10 58.97 0.00 0.00
June 0.255250E+11 -0.245324E+11 0.00 0.00 720.00 0.00 -992650969.0 58.97 0.00 0.00
July 0.235918E+11 -0.225716E+11 0.00 0.00 744.00 0.00 -0.102011E+10 58.97 0.00 0.00
August 0.260128E+11 -0.249897E+11 0.00 0.00 744.00 0.00 -0.102314E+10 58.97 0.00 0.00
September 0.248319E+11 -0.238443E+11 0.00 0.00 720.00 0.00 -987542950.6 58.97 0.00 0.00
October 0.274241E+11 -0.264052E+11 0.00 0.00 744.00 0.00 -0.101887E+10 58.97 0.00 0.00
November 0.287894E+11 -0.278037E+11 0.00 0.00 720.00 0.00 -985687268.6 58.97 0.00 0.00
December 0.301990E+11 -0.291796E+11 0.00 0.00 744.00 0.00 -0.101939E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.333852E+12 -0.321814E+12 0.00 0.00 8760.00 0.00 -0.120376E+11 58.97 0.00 0.00
Minimum of Months 0.235918E+11 -0.312421E+11 0.00 0.00 672.00 0.00 -0.102719E+10 58.97 0.00 0.00
Maximum of Months 0.322693E+11 -0.225716E+11 0.00 0.00 744.00 0.00 -925033711.4 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.50 0.48 01-JAN-07:49 7755.15 36.97 300.33 296.17 1434.31 25.98 217.00 278.67
February 295.50 0.50 0.48 01-FEB-11:39 3369.40 28.26 173.67 279.67 1244.31 23.23 186.33 266.33
March 296.00 0.50 0.48 02-MAR-12:39 1582.52 20.02 56.00 319.67 923.77 21.35 174.17 281.00
April 347.33 0.52 0.48 01-APR-07:49 1258.74 19.22 29.50 323.33 725.51 20.52 172.33 284.33
May 353.67 0.51 0.48 01-MAY-07:19 1125.05 19.46 8.50 349.50 632.91 20.81 166.17 299.83
June 394.00 0.51 0.48 01-JUN-06:00 1068.89 19.10 2.50 350.33 605.06 20.47 166.17 303.67
July 390.00 0.51 0.48 01-JUL-06:49 1178.73 19.47 15.00 360.00 647.27 20.81 195.00 313.33
August 380.83 0.51 0.48 01-AUG-07:10 1368.33 19.76 42.67 346.67 736.37 21.08 240.83 307.67
September 342.17 0.51 0.48 01-SEP-07:19 1609.71 20.05 88.00 317.50 851.55 21.28 225.33 281.83
October 330.00 0.50 0.48 01-OCT-07:10 2775.33 23.94 167.83 314.17 1154.73 22.37 237.67 283.33
November 308.00 0.50 0.48 01-NOV-07:00 7827.42 36.40 297.33 288.67 1366.65 24.17 202.00 270.67
December 282.83 0.50 0.48 01-DEC-07:49 7905.21 37.74 279.33 284.33 1821.31 27.87 206.83 267.17
                         
Annual Sum or Average 4027.67 0.51     3028.53 24.45 1460.67 3830.00 977.62 22.31 2389.83 3437.83
Minimum of Months 282.83 0.50 0.48   1068.89 19.10 2.50 279.67 605.06 20.47 166.17 266.33
Maximum of Months 394.00 0.52 0.48   7905.21 37.74 300.33 360.00 1821.31 27.87 240.83 313.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.53 0.48 01-JAN-07:49 1992.23 23.66 104.50 271.00 1073.98 23.73 125.50 222.83
February 295.50 0.51 0.48 01-FEB-11:39 2205.56 23.74 91.00 261.50 1169.87 23.89 114.00 228.00
March 296.00 0.50 0.48 02-MAR-12:39 2297.05 23.70 86.33 315.33 1213.61 23.84 122.67 276.17
April 347.33 0.51 0.48 01-APR-07:10 2350.89 22.79 96.00 326.33 1247.80 23.15 121.83 293.33
May 353.67 0.50 0.48 01-MAY-06:40 2660.08 24.08 112.00 359.83 1066.29 23.06 127.67 314.83
June 394.00 0.50 0.48 01-JUN-06:10 2392.43 23.70 122.83 358.83 1009.20 22.95 145.33 320.83
July 390.00 0.50 0.48 01-JUL-06:19 2303.45 23.16 112.83 365.17 990.92 22.42 158.50 318.00
August 380.83 0.51 0.48 01-AUG-06:49 2122.09 23.07 106.17 347.17 1104.79 23.47 171.50 308.00
September 342.17 0.51 0.48 01-SEP-06:49 2027.04 23.20 101.17 314.17 1035.72 23.49 171.17 278.33
October 330.00 0.50 0.48 01-OCT-06:49 2109.35 23.42 93.17 303.00 1078.59 23.56 160.67 269.83
November 308.00 0.51 0.48 01-NOV-07:49 1752.12 22.80 86.00 266.83 897.81 22.84 124.00 230.50
December 282.83 0.52 0.48 01-DEC-07:40 1885.48 23.39 91.50 257.50 1004.69 23.42 111.00 208.00
                         
Annual Sum or Average 4027.67 0.51     2188.11 23.39 1203.50 3746.67 1072.92 23.29 1653.83 3268.67
Minimum of Months 282.83 0.50 0.48   1752.12 22.79 86.00 257.50 897.81 22.42 111.00 208.00
Maximum of Months 394.00 0.53 0.48   2660.08 24.08 122.83 365.17 1247.80 23.89 171.50 320.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.55 0.48 01-JAN-08:50 544.72 16.25 0.00 251.67 352.43 17.93 0.00 164.00
February 295.50 0.53 0.48 01-FEB-11:50 629.09 17.42 0.00 248.17 408.48 19.01 2.83 184.17
March 296.00 0.51 0.48 02-MAR-12:39 735.30 18.42 0.00 306.33 462.02 19.81 11.00 236.67
April 347.33 0.51 0.48 01-APR-07:49 875.26 18.83 0.00 326.50 532.86 20.12 79.67 284.83
May 353.67 0.49 0.48 01-MAY-06:00 1074.01 21.05 56.50 370.33 618.05 22.22 188.50 330.67
June 394.00 0.50 0.48 01-JUN-06:30 1242.28 22.16 108.17 374.00 654.87 21.35 217.33 338.17
July 390.00 0.49 0.48 01-JUL-06:40 1214.98 20.86 80.83 376.50 659.51 22.13 241.67 340.17
August 380.83 0.50 0.48 01-AUG-07:10 1066.39 19.59 11.33 353.17 598.95 20.89 175.83 317.50
September 342.17 0.51 0.48 01-SEP-07:19 893.27 18.81 0.17 315.50 513.67 20.10 75.50 264.83
October 330.00 0.51 0.48 01-OCT-07:30 771.07 18.58 0.00 296.50 471.76 20.03 13.83 244.17
November 308.00 0.53 0.48 01-NOV-09:50 559.79 16.86 0.00 242.83 364.10 18.51 0.00 169.00
December 282.83 0.54 0.48 01-DEC-08:39 545.21 16.51 0.00 242.83 354.44 18.24 0.00 148.50
                         
Annual Sum or Average 4027.67 0.51     871.71 18.95 257.00 3704.33 510.62 20.16 1006.17 3022.67
Minimum of Months 282.83 0.49 0.48   544.72 16.25 0.00 242.83 352.43 17.93 0.00 148.50
Maximum of Months 394.00 0.55 0.48   1242.28 22.16 108.17 376.50 659.51 22.22 241.67 340.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.52 0.48 01-JAN-08:50 2280.62 24.58 112.67 275.83 1263.44 24.48 128.00 230.00
February 295.50 0.51 0.48 01-FEB-11:39 2036.90 23.84 89.33 266.00 1073.39 23.83 128.83 234.17
March 296.00 0.51 0.48 02-MAR-12:39 2184.74 23.22 81.00 311.67 1146.46 23.53 115.17 269.00
April 347.33 0.51 0.48 01-APR-08:20 2468.66 21.70 82.83 327.00 1295.37 22.11 108.67 293.67
May 353.67 0.50 0.48 01-MAY-07:40 2045.61 18.24 1.17 356.33 904.53 20.35 102.50 317.50
June 394.00 0.51 0.48 01-JUN-07:19 2165.45 18.10 0.67 359.00 922.97 20.14 103.67 318.00
July 390.00 0.50 0.48 01-JUL-07:10 2003.70 18.58 6.50 365.83 890.49 20.40 122.33 322.33
August 380.83 0.51 0.48 01-AUG-07:40 2069.13 20.52 59.17 349.17 947.33 20.62 137.50 309.67
September 342.17 0.51 0.48 01-SEP-07:40 1919.80 21.94 82.33 314.67 983.40 22.33 153.00 278.17
October 330.00 0.50 0.48 01-OCT-07:49 2455.72 24.58 110.67 309.33 1014.45 23.45 166.67 273.00
November 308.00 0.52 0.48 01-NOV-09:50 1978.57 23.73 96.67 266.50 1063.11 23.78 124.83 231.33
December 282.83 0.51 0.48 01-DEC-08:39 2124.31 25.20 106.67 271.00 1147.23 24.95 124.33 219.00
                         
Annual Sum or Average 4027.67 0.51     2142.81 21.78 829.67 3772.33 1045.16 22.32 1515.50 3295.83
Minimum of Months 282.83 0.50 0.48   1919.80 18.10 0.67 266.00 890.49 20.14 102.50 219.00
Maximum of Months 394.00 0.52 0.48   2468.66 25.20 112.67 365.83 1295.37 24.95 166.67 322.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.50 0.48 01-JAN-07:49 7818.77 36.47 297.33 296.17 1535.46 21.75 92.17 281.67
February 295.50 0.50 0.48 01-FEB-11:39 3425.14 24.68 165.33 280.00 1336.98 18.93 36.50 268.00
March 296.00 0.50 0.48 02-MAR-12:39 1621.49 13.81 0.00 319.83 991.74 17.38 0.00 286.00
April 347.33 0.52 0.48 01-APR-07:49 1284.11 13.39 0.00 323.83 775.30 16.80 0.00 289.67
May 353.67 0.50 0.48 01-MAY-07:19 1142.90 13.60 0.00 350.00 673.87 17.05 0.00 305.50
June 394.00 0.51 0.48 01-JUN-06:49 1085.60 13.25 0.00 350.67 644.09 16.68 0.00 308.17
July 390.00 0.50 0.48 01-JUL-06:49 1195.27 13.48 0.00 360.00 688.40 16.89 0.00 318.83
August 380.83 0.51 0.48 01-AUG-07:10 1386.82 13.75 0.00 346.83 783.48 17.12 0.00 312.50
September 342.17 0.51 0.48 01-SEP-07:10 1629.69 13.91 3.67 318.17 906.66 17.13 0.00 286.67
October 330.00 0.49 0.48 01-OCT-07:10 2814.82 18.77 80.67 314.50 1241.50 18.27 10.50 287.83
November 308.00 0.50 0.48 01-NOV-07:00 7883.76 35.88 296.00 289.00 1496.85 21.56 90.83 276.33
December 282.83 0.50 0.48 01-DEC-07:49 7967.38 37.33 279.33 284.33 1927.93 23.98 110.83 268.50
                         
Annual Sum or Average 4027.67 0.50     3062.68 19.94 1122.33 3833.33 1046.51 18.44 340.83 3489.67
Minimum of Months 282.83 0.49 0.48   1085.60 13.25 0.00 280.00 644.09 16.68 0.00 268.00
Maximum of Months 394.00 0.52 0.48   7967.38 37.33 297.33 360.00 1927.93 23.98 110.83 318.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.53 0.48 01-JAN-07:49 2025.64 21.16 100.17 272.67 1118.26 21.82 72.33 229.67
February 295.50 0.51 0.48 01-FEB-11:39 2247.37 20.99 89.67 262.67 1218.85 21.80 64.33 231.67
March 296.00 0.50 0.48 02-MAR-12:39 2322.08 19.46 74.33 316.00 1274.62 21.39 56.50 282.17
April 347.33 0.51 0.48 01-APR-07:10 2380.85 19.75 95.67 327.17 1303.95 20.73 68.00 296.67
May 353.67 0.50 0.48 01-MAY-06:40 2679.10 20.41 106.00 361.17 1125.28 20.39 55.00 320.50
June 394.00 0.50 0.48 01-JUN-06:10 2420.29 19.85 114.00 359.50 1064.00 20.35 62.67 326.67
July 390.00 0.50 0.48 01-JUL-06:19 2333.56 20.10 112.33 366.33 1045.23 19.74 53.67 323.50
August 380.83 0.51 0.48 01-AUG-06:49 2144.89 20.01 105.17 347.67 1156.72 21.11 75.50 312.50
September 342.17 0.51 0.48 01-SEP-06:49 2063.30 20.20 96.00 314.67 1085.54 21.13 67.50 282.17
October 330.00 0.50 0.48 01-OCT-06:49 2156.18 20.45 87.67 303.17 1130.67 21.24 57.00 273.17
November 308.00 0.51 0.48 01-NOV-07:49 1786.71 19.96 84.00 267.83 942.70 20.65 55.50 234.17
December 282.83 0.52 0.48 01-DEC-07:40 1915.03 20.90 89.17 258.50 1045.95 21.56 61.67 213.67
                         
Annual Sum or Average 4027.67 0.51     2219.26 20.25 1154.17 3757.33 1124.75 20.94 749.67 3326.50
Minimum of Months 282.83 0.50 0.48   1786.71 19.46 74.33 258.50 942.70 19.74 53.67 213.67
Maximum of Months 394.00 0.53 0.48   2679.10 21.16 114.00 366.33 1303.95 21.82 75.50 326.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.54 0.48 01-JAN-08:50 554.53 10.76 0.00 252.67 375.65 14.39 0.00 179.67
February 295.50 0.52 0.48 01-FEB-11:50 641.40 11.98 0.00 249.33 435.66 15.61 0.00 193.83
March 296.00 0.51 0.48 02-MAR-12:39 750.69 13.17 0.00 307.67 492.99 16.68 0.00 248.83
April 347.33 0.51 0.48 01-APR-07:49 893.47 13.44 0.00 327.33 568.46 16.87 0.00 291.50
May 353.67 0.49 0.48 01-MAY-06:00 1093.61 15.68 27.17 370.67 658.39 19.00 27.50 336.00
June 394.00 0.49 0.48 01-JUN-06:19 1263.02 17.19 58.00 374.33 707.06 20.31 59.33 348.67
July 390.00 0.49 0.48 01-JUL-06:40 1234.24 15.30 23.50 376.67 701.51 18.62 24.50 343.33
August 380.83 0.50 0.48 01-AUG-06:00 1083.71 13.86 0.00 353.33 637.21 17.27 0.00 322.00
September 342.17 0.51 0.48 01-SEP-07:19 908.54 13.25 0.00 316.00 546.69 16.60 0.00 271.17
October 330.00 0.51 0.48 01-OCT-07:30 784.88 13.18 0.00 297.33 502.55 16.68 0.00 252.33
November 308.00 0.53 0.48 01-NOV-09:39 570.14 11.28 0.00 244.33 388.17 14.97 0.00 180.50
December 282.83 0.53 0.48 01-DEC-08:30 554.52 10.91 0.00 243.67 377.66 14.62 0.00 162.33
                         
Annual Sum or Average 4027.67 0.51     887.19 13.51 108.67 3713.33 544.86 16.96 111.33 3130.17
Minimum of Months 282.83 0.49 0.48   554.52 10.76 0.00 243.67 375.65 14.39 0.00 162.33
Maximum of Months 394.00 0.54 0.48   1263.02 17.19 58.00 376.67 707.06 20.31 59.33 348.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.52 0.48 01-JAN-08:50 2314.52 22.16 109.33 276.83 1309.65 22.68 81.83 237.00
February 295.50 0.51 0.48 01-FEB-11:39 2056.29 19.85 79.17 266.83 1126.49 21.64 60.17 237.67
March 296.00 0.51 0.48 02-MAR-12:39 2235.47 20.17 81.00 313.33 1200.28 21.13 56.67 276.50
April 347.33 0.51 0.48 01-APR-08:09 2497.62 18.40 82.00 327.67 1352.65 19.42 53.00 297.83
May 353.67 0.50 0.48 01-MAY-07:40 2069.90 13.72 0.00 357.33 955.03 17.13 0.00 320.67
June 394.00 0.50 0.48 01-JUN-07:10 2193.28 13.62 0.00 359.17 973.97 16.95 0.00 324.00
July 390.00 0.50 0.48 01-JUL-07:10 2026.98 14.18 3.67 366.67 939.37 17.25 0.00 327.33
August 380.83 0.51 0.48 01-AUG-07:40 2092.83 16.85 59.00 350.67 997.72 17.53 5.50 316.50
September 342.17 0.51 0.48 01-SEP-07:40 1954.55 18.73 80.50 315.67 1032.02 19.80 51.67 282.83
October 330.00 0.50 0.48 01-OCT-07:40 2502.37 21.91 108.83 310.17 1066.59 21.07 53.50 276.83
November 308.00 0.51 0.48 01-NOV-09:39 2013.78 21.06 95.17 268.17 1108.33 21.76 66.67 236.00
December 282.83 0.51 0.48 01-DEC-08:30 2159.94 22.85 103.00 271.50 1194.42 23.17 74.00 226.00
                         
Annual Sum or Average 4027.67 0.51     2174.37 18.32 801.67 3784.00 1095.57 19.74 503.00 3359.17
Minimum of Months 282.83 0.50 0.48   1954.55 13.62 0.00 266.83 939.37 16.95 0.00 226.00
Maximum of Months 394.00 0.52 0.48   2502.37 22.85 109.33 366.67 1352.65 23.17 81.83 327.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.50 0.48 01-JAN-07:49 7820.39 36.46 297.33 296.17 1537.13 21.74 92.17 281.67
February 295.50 0.50 0.48 01-FEB-11:39 3427.36 24.66 165.33 280.00 1338.57 18.92 36.50 268.00
March 296.00 0.50 0.48 02-MAR-12:39 1623.59 13.78 0.00 320.33 993.08 17.37 0.00 286.00
April 347.33 0.52 0.48 01-APR-07:49 1285.78 13.36 0.00 323.83 776.38 16.79 0.00 289.83
May 353.67 0.50 0.48 01-MAY-07:19 1144.44 13.57 0.00 350.33 674.86 17.04 0.00 305.67
June 394.00 0.51 0.48 01-JUN-06:49 1087.04 13.22 0.00 350.67 645.02 16.67 0.00 308.17
July 390.00 0.50 0.48 01-JUL-06:49 1197.01 13.45 0.00 360.17 689.47 16.87 0.00 318.83
August 380.83 0.51 0.48 01-AUG-07:10 1388.97 13.72 0.00 346.83 784.75 17.11 0.00 312.50
September 342.17 0.51 0.48 01-SEP-07:10 1632.29 13.88 3.67 318.17 908.20 17.12 0.00 286.67
October 330.00 0.49 0.48 01-OCT-07:10 2817.67 18.74 80.67 314.67 1243.35 18.26 10.50 288.00
November 308.00 0.50 0.48 01-NOV-07:00 7885.67 35.88 296.00 289.00 1498.51 21.55 90.83 276.50
December 282.83 0.50 0.48 01-DEC-07:49 7968.96 37.33 279.33 284.33 1929.71 23.97 110.83 268.50
                         
Annual Sum or Average 4027.67 0.50     3064.63 19.92 1122.33 3834.50 1047.88 18.43 340.83 3490.33
Minimum of Months 282.83 0.49 0.48   1087.04 13.22 0.00 280.00 645.02 16.67 0.00 268.00
Maximum of Months 394.00 0.52 0.48   7968.96 37.33 297.33 360.17 1929.71 23.97 110.83 318.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.53 0.48 01-JAN-07:49 2026.36 21.14 100.17 272.67 1119.11 21.81 72.33 229.67
February 295.50 0.51 0.48 01-FEB-11:39 2248.17 20.97 89.67 262.67 1219.82 21.79 64.33 231.83
March 296.00 0.50 0.48 02-MAR-12:39 2323.21 19.43 74.33 316.17 1275.78 21.37 56.50 282.17
April 347.33 0.51 0.48 01-APR-07:10 2382.24 19.72 95.67 327.17 1305.15 20.72 68.00 297.00
May 353.67 0.50 0.48 01-MAY-06:40 2680.73 20.38 106.00 361.17 1126.63 20.38 55.00 320.83
June 394.00 0.50 0.48 01-JUN-06:10 2422.08 19.82 114.00 359.50 1065.36 20.33 62.67 326.83
July 390.00 0.50 0.48 01-JUL-06:19 2335.59 20.07 112.33 366.67 1046.70 19.73 53.67 323.67
August 380.83 0.51 0.48 01-AUG-06:49 2146.90 19.98 105.17 347.67 1158.18 21.09 75.50 312.67
September 342.17 0.51 0.48 01-SEP-06:49 2065.24 20.18 96.00 314.67 1086.96 21.12 67.50 282.17
October 330.00 0.50 0.48 01-OCT-06:49 2157.53 20.42 87.67 303.17 1131.94 21.22 57.00 273.17
November 308.00 0.51 0.48 01-NOV-07:49 1787.48 19.93 84.00 267.83 943.59 20.63 55.50 234.33
December 282.83 0.52 0.48 01-DEC-07:40 1915.74 20.88 89.17 258.50 1046.79 21.55 61.67 213.67
                         
Annual Sum or Average 4027.67 0.51     2220.67 20.22 1154.17 3757.83 1125.96 20.93 749.67 3328.00
Minimum of Months 282.83 0.50 0.48   1787.48 19.43 74.33 258.50 943.59 19.73 53.67 213.67
Maximum of Months 394.00 0.53 0.48   2680.73 21.14 114.00 366.67 1305.15 21.81 75.50 326.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.54 0.48 01-JAN-08:50 554.85 10.72 0.00 252.67 376.05 14.37 0.00 179.83
February 295.50 0.52 0.48 01-FEB-11:50 641.78 11.95 0.00 249.67 436.11 15.59 0.00 194.00
March 296.00 0.51 0.48 02-MAR-12:39 751.28 13.14 0.00 307.83 493.55 16.66 0.00 249.00
April 347.33 0.51 0.48 01-APR-07:49 894.31 13.41 0.00 327.33 569.17 16.85 0.00 291.83
May 353.67 0.49 0.48 01-MAY-06:00 1094.90 15.65 27.17 370.83 659.33 18.98 27.50 336.00
June 394.00 0.49 0.48 01-JUN-06:19 1264.52 17.16 58.00 374.33 708.10 20.30 59.33 348.67
July 390.00 0.49 0.48 01-JUL-06:40 1235.87 15.27 23.50 376.67 702.59 18.60 24.50 343.50
August 380.83 0.50 0.48 01-AUG-06:00 1085.11 13.83 0.00 353.33 638.17 17.25 0.00 322.00
September 342.17 0.51 0.48 01-SEP-07:19 909.61 13.22 0.00 316.00 547.48 16.58 0.00 271.33
October 330.00 0.51 0.48 01-OCT-07:30 785.55 13.15 0.00 297.33 503.17 16.67 0.00 252.33
November 308.00 0.53 0.48 01-NOV-09:39 570.46 11.24 0.00 244.33 388.57 14.95 0.00 181.17
December 282.83 0.53 0.48 01-DEC-08:30 554.82 10.88 0.00 243.83 378.05 14.60 0.00 162.33
                         
Annual Sum or Average 4027.67 0.51     888.10 13.48 108.67 3714.17 545.58 16.95 111.33 3132.00
Minimum of Months 282.83 0.49 0.48   554.82 10.72 0.00 243.83 376.05 14.37 0.00 162.33
Maximum of Months 394.00 0.54 0.48   1264.52 17.16 58.00 376.67 708.10 20.30 59.33 348.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.52 0.48 01-JAN-08:50 2315.23 22.13 109.33 276.83 1310.50 22.67 81.83 237.33
February 295.50 0.51 0.48 01-FEB-11:39 2057.17 19.82 79.17 266.83 1127.49 21.62 60.17 237.67
March 296.00 0.51 0.48 02-MAR-12:39 2236.62 20.14 81.00 313.33 1201.37 21.12 56.67 276.83
April 347.33 0.51 0.48 01-APR-08:09 2499.05 18.37 82.00 327.67 1353.89 19.40 53.00 297.83
May 353.67 0.50 0.48 01-MAY-07:40 2071.62 13.69 0.00 357.33 1137.83 17.11 0.00 320.83
June 394.00 0.50 0.48 01-JUN-07:10 2195.02 13.58 0.00 359.17 975.26 16.94 0.00 324.17
July 390.00 0.50 0.48 01-JUL-07:10 2029.01 14.14 3.67 366.83 948.38 17.24 0.00 327.50
August 380.83 0.51 0.48 01-AUG-07:40 2094.90 16.82 59.00 350.67 1125.48 17.52 5.50 316.67
September 342.17 0.51 0.48 01-SEP-07:40 1956.38 18.71 80.50 315.67 1033.37 19.78 51.67 282.83
October 330.00 0.50 0.48 01-OCT-07:40 2503.78 21.88 108.83 310.17 1067.87 21.06 53.50 277.00
November 308.00 0.51 0.48 01-NOV-09:39 2014.51 21.03 95.17 268.17 1109.21 21.74 66.67 236.17
December 282.83 0.51 0.48 01-DEC-08:30 2160.65 22.82 103.00 271.50 1195.27 23.16 74.00 226.00
                         
Annual Sum or Average 4027.67 0.51     2175.78 18.29 801.67 3784.17 1125.37 19.72 503.00 3360.83
Minimum of Months 282.83 0.50 0.48   1956.38 13.58 0.00 266.83 948.38 16.94 0.00 226.00
Maximum of Months 394.00 0.52 0.48   2503.78 22.82 109.33 366.83 1353.89 23.16 81.83 327.50



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 42550292.76 11142.12 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 15820188.31 10529.94 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 13572752.88 10681.55 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 13748102.89 5068.05 18-APR-14:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 58268.81 100.87 18-NOV-13:05 0.00 0.00 0.00 0.00 0.00
December 21077994.80 12167.68 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.106828E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 42550292.76 12167.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 16341503.97 1701.81 05-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 1570688.51 454.73 06-FEB-06:40 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 3981116.31 1069.70 21-DEC-06:09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 21893308.79     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 16341503.97 1701.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 10225748.42 1524.95 05-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 2774405.17 536.60 17-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 142339.56 179.40 09-MAR-06:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 12143397.41 3210.37 21-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 25285890.56     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 12143397.41 3210.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 22253865.13 2155.63 05-JAN-06:06 0.00 0.00 0.00 0.00 0.00
February 9518535.63 2259.13 06-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 235258.83 117.41 11-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 15176007.95 1744.34 20-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 47183667.53     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 22253865.13 2259.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.609042E+09 119063.55 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.350759E+09 114056.33 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.517475E+09 113159.59 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 52089634.06 14741.43 18-APR-15:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 6813311.22 16304.69 15-NOV-10:05 0.00 0.00 0.00 0.00 0.00
December 0.356574E+09 133562.85 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.189275E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.609042E+09 133562.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.892601E+10 139703.91 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.419053E+10 139664.81 06-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.282691E+10 139501.02 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.349651E+09 41547.31 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.550374E+10 139666.12 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.217968E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.892601E+10 139703.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.279479E+10 135835.29 14-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.115811E+10 135823.88 06-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.112711E+10 135787.43 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 31641153.16 12097.70 16-NOV-06:06 0.00 0.00 0.00 0.00 0.00
December 0.219829E+10 135703.96 20-DEC-05:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.730995E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.279479E+10 135835.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.205388E+10 165448.35 09-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.964711E+09 165200.11 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.153585E+10 165383.97 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.144193E+10 165324.20 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.599638E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205388E+10 165448.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.225033E+10 130444.52 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.957014E+09 130383.73 06-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.742397E+09 130366.49 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2660324.74 2132.32 16-NOV-06:50 0.00 0.00 0.00 0.00 0.00
December 0.114547E+10 130336.91 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.509787E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.225033E+10 130444.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 67030316.12 14564.73 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 26245917.05 14112.27 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 19178156.80 14003.45 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 3592899.00 5988.17 18-APR-15:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 792877.58 1136.65 15-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 38533665.95 14976.84 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155374E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 67030316.12 14976.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.144142E+10 71491.10 09-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.108504E+10 71771.19 06-FEB-05:45 0.00 0.00 0.00 0.00 0.00
March 0.634456E+09 71470.68 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 3006217.66 1618.86 16-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.883672E+09 71658.63 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.404760E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144142E+10 71771.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.255447E+10 16115.67 09-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.138537E+10 16103.93 18-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.938687E+09 16111.88 13-MAR-05:04 0.00 0.00 0.00 0.00 0.00
April 29721977.26 3585.53 03-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 33747236.30 8456.21 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.300470E+09 16014.23 24-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.173816E+10 16061.85 29-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.698063E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.255447E+10 16115.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.953166E+09 15610.70 11-JAN-05:12 0.00 0.00 0.00 0.00 0.00
February 0.508090E+09 15606.52 18-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.438043E+09 15604.59 11-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 5528400.07 881.23 11-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 10844821.33 3887.53 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 88255840.76 15581.60 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.794735E+09 15596.18 05-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.279866E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.953166E+09 15610.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.871295E+09 19717.30 09-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.517584E+09 19689.75 06-FEB-05:16 0.00 0.00 0.00 0.00 0.00
March 0.607464E+09 19707.80 11-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 11308889.23 1235.63 11-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 10808796.14 1647.78 28-OCT-06:40 0.00 0.00 0.00 0.00 0.00
November 55415033.84 19656.38 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.693036E+09 19694.62 20-DEC-05:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.276691E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.871295E+09 19717.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.823847E+09 16017.11 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.423826E+09 16002.68 06-FEB-05:15 0.00 0.00 0.00 0.00 0.00
March 0.306934E+09 15995.04 11-MAR-05:11 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 5983386.10 739.90 28-OCT-06:40 0.00 0.00 0.00 0.00 0.00
November 53695946.11 15991.46 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.516871E+09 16012.93 20-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.213116E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.823847E+09 16017.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 80.37 0.67 27-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 261.28 0.75 14-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 79.87 0.67 07-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 421.52     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 261.28 0.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.389122E+11 0.292565E+11 132707.43 30-JAN-06:02 54684.77 0.27
February 0.00 0.00 0.554933E+11 0.405615E+11 151496.21 28-FEB-05:12 135794.50 0.42
March 0.00 0.00 0.694834E+11 0.548985E+11 155185.81 28-MAR-04:12 120169.68 0.42
April 0.00 0.00 0.113392E+12 0.901505E+11 151446.33 01-APR-04:12 117278.69 0.69
May 0.00 0.00 0.142564E+12 0.109169E+12 176689.16 22-MAY-05:02 142221.01 0.69
June 0.00 0.00 0.154722E+12 0.121502E+12 171250.04 07-JUN-04:12 136429.65 0.80
July 0.00 0.00 0.168254E+12 0.130387E+12 164096.97 24-JUL-05:03 143586.24 0.84
August 0.00 0.00 0.185142E+12 0.145190E+12 176546.98 07-AUG-05:02 147426.02 0.88
September 0.00 0.00 0.143539E+12 0.103867E+12 194757.12 06-SEP-03:02 142409.50 0.70
October 0.00 0.00 0.134782E+12 0.105470E+12 178077.97 21-OCT-04:11 134166.47 0.66
November 0.00 0.00 0.847191E+11 0.682199E+11 173699.87 08-NOV-05:11 138388.80 0.52
December 0.00 0.00 0.633503E+11 0.498403E+11 141176.64 11-DEC-06:03 128658.57 0.39
                 
Annual Sum or Average 0.00 0.00 0.135435E+13 0.104851E+13       0.61
Minimum of Months 0.00 0.00 0.389122E+11 0.292565E+11 132707.43   54684.77 0.27
Maximum of Months 0.00 0.00 0.185142E+12 0.145190E+12 194757.12   147426.02 0.88



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.308391E+12 0.225246E+12 1086610.00 19-JAN-06:03 826674.22 0.26
February 0.00 0.00 0.436165E+12 0.304722E+12 1300453.40 27-FEB-06:02 1179700.80 0.40
March 0.00 0.00 0.518457E+12 0.387582E+12 1585560.07 07-MAR-06:02 1157412.51 0.38
April 0.00 0.00 0.818957E+12 0.609615E+12 1571671.91 29-APR-04:11 1243013.26 0.52
May 0.00 0.00 0.129612E+13 0.950414E+12 2012289.33 24-MAY-05:02 1266858.69 0.65
June 0.00 0.00 0.132443E+13 0.983251E+12 1669297.10 09-JUN-04:12 1260871.41 0.68
July 0.00 0.00 0.137971E+13 0.980776E+12 1632799.65 29-JUL-05:02 1249838.02 0.67
August 0.00 0.00 0.142465E+13 0.101288E+13 1830270.31 16-AUG-04:12 1149573.81 0.67
September 0.00 0.00 0.128209E+13 0.871973E+12 2158839.05 05-SEP-04:11 1102728.41 0.65
October 0.00 0.00 0.112227E+13 0.824566E+12 1825929.02 21-OCT-04:11 1098504.77 0.56
November 0.00 0.00 0.643854E+12 0.495761E+12 1556379.23 02-NOV-05:02 1218098.88 0.46
December 0.00 0.00 0.450324E+12 0.329179E+12 1323950.75 16-DEC-06:03 1003734.96 0.32
                 
Annual Sum or Average 0.00 0.00 0.110054E+14 0.797597E+13       0.52
Minimum of Months 0.00 0.00 0.308391E+12 0.225246E+12 1086610.00   826674.22 0.26
Maximum of Months 0.00 0.00 0.142465E+13 0.101288E+13 2158839.05   1266858.69 0.68



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.303282E+11 0.215849E+11 123310.99 19-JAN-15:00 81786.28 0.26
February 0.00 0.00 0.440308E+11 0.305756E+11 122032.23 27-FEB-16:00 89455.23 0.40
March 0.00 0.00 0.534965E+11 0.396660E+11 144840.10 07-MAR-06:02 97073.18 0.37
April 0.00 0.00 0.866360E+11 0.652177E+11 159578.45 26-APR-05:02 119870.28 0.52
May 0.00 0.00 0.143674E+12 0.107950E+12 234436.44 24-MAY-05:02 140492.74 0.65
June 0.00 0.00 0.149056E+12 0.113927E+12 182076.64 19-JUN-05:02 136347.45 0.69
July 0.00 0.00 0.154574E+12 0.112965E+12 201930.60 27-JUL-03:02 143823.48 0.69
August 0.00 0.00 0.157917E+12 0.115222E+12 212218.32 23-AUG-03:02 143992.28 0.68
September 0.00 0.00 0.138163E+12 0.957260E+11 240696.43 05-SEP-04:11 119511.59 0.65
October 0.00 0.00 0.120021E+12 0.893688E+11 206501.13 06-OCT-03:02 147080.15 0.56
November 0.00 0.00 0.626074E+11 0.478871E+11 166848.53 01-NOV-05:02 120202.71 0.45
December 0.00 0.00 0.433980E+11 0.314509E+11 134246.73 15-DEC-06:03 94824.36 0.31
                 
Annual Sum or Average 0.00 0.00 0.118390E+13 0.871540E+12       0.52
Minimum of Months 0.00 0.00 0.303282E+11 0.215849E+11 122032.23   81786.28 0.26
Maximum of Months 0.00 0.00 0.157917E+12 0.115222E+12 240696.43   147080.15 0.69



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.203163E+11 0.158448E+11 120528.60 01-JAN-16:12 96396.40 0.18
February 0.00 0.00 0.237956E+11 0.193774E+11 117803.38 03-FEB-05:12 44151.29 0.28
March 0.00 0.00 0.325190E+11 0.276503E+11 140960.90 07-MAR-05:11 84096.90 0.26
April 0.00 0.00 0.512819E+11 0.446918E+11 138277.68 26-APR-04:12 50604.74 0.44
May 0.00 0.00 0.953758E+11 0.731138E+11 164826.03 29-MAY-11:20 82262.49 0.57
June 0.00 0.00 0.100442E+12 0.746899E+11 162971.22 19-JUN-03:02 80763.06 0.59
July 0.00 0.00 0.109203E+12 0.760260E+11 167486.31 03-JUL-03:02 79318.49 0.56
August 0.00 0.00 0.121463E+12 0.871028E+11 164242.89 06-AUG-17:20 82522.41 0.62
September 0.00 0.00 0.103109E+12 0.741632E+11 160914.75 24-SEP-16:01 82930.90 0.60
October 0.00 0.00 0.887705E+11 0.674879E+11 170718.78 15-OCT-15:38 79958.62 0.51
November 0.00 0.00 0.489548E+11 0.403978E+11 142478.22 01-NOV-04:15 84860.74 0.38
December 0.00 0.00 0.317500E+11 0.256639E+11 141806.98 15-DEC-05:12 84158.09 0.24
                 
Annual Sum or Average 0.00 0.00 0.826981E+12 0.626210E+12       0.44
Minimum of Months 0.00 0.00 0.203163E+11 0.158448E+11 117803.38   44151.29 0.18
Maximum of Months 0.00 0.00 0.121463E+12 0.871028E+11 170718.78   96396.40 0.62



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.382904E+11 0.341162E+11 206710.47 31-JAN-12:50 125267.76 0.00
February 0.00 0.00 0.147440E+12 0.137605E+12 310688.50 24-FEB-10:30 215849.15 0.00
March 0.00 0.00 0.360646E+12 0.334091E+12 393382.55 31-MAR-24:00 393382.55 0.00
April 0.00 0.00 0.853578E+12 0.778393E+12 428399.79 05-APR-07:15 396349.65 0.00
May 0.00 0.00 0.347644E+12 0.334917E+12 212295.34 31-MAY-23:10 209953.86 0.00
June 0.00 0.00 0.574680E+12 0.560727E+12 302399.82 30-JUN-23:03 301477.89 0.00
July 0.00 0.00 0.840727E+12 0.825771E+12 394456.57 31-JUL-23:55 394456.57 0.00
August 0.00 0.00 0.107906E+13 0.106521E+13 423562.46 07-AUG-14:00 402875.99 0.00
September 0.00 0.00 0.340724E+12 0.327114E+12 212878.39 30-SEP-24:00 211605.14 0.00
October 0.00 0.00 0.485368E+12 0.470419E+12 303514.43 31-OCT-24:00 303514.43 0.00
November 0.00 0.00 0.417925E+12 0.381085E+12 358650.74 28-NOV-09:00 308171.33 0.00
December 0.00 0.00 0.499357E+12 0.447798E+12 431788.40 28-DEC-09:50 397906.84 0.00
                 
Annual Sum or Average 0.00 0.00 0.598544E+13 0.569724E+13       0.00
Minimum of Months 0.00 0.00 0.382904E+11 0.341162E+11 206710.47   125267.76 0.00
Maximum of Months 0.00 0.00 0.107906E+13 0.106521E+13 431788.40   402875.99 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.500004E+10 0.489472E+10 2718.81 19-JAN-17:00 2362.07 0.00
February 0.00 0.00 0.945244E+10 0.926618E+10 4714.93 26-FEB-17:54 4714.93 0.00
March 0.00 0.00 0.156588E+11 0.154535E+11 7680.64 31-MAR-24:00 7680.64 0.00
April 0.00 0.00 0.204232E+11 0.201307E+11 8597.65 28-APR-17:20 8064.96 0.00
May 0.00 0.00 0.642048E+10 0.591644E+10 4057.69 31-MAY-23:10 3909.74 0.00
June 0.00 0.00 0.112072E+11 0.106254E+11 5863.84 30-JUN-23:03 5814.96 0.00
July 0.00 0.00 0.166897E+11 0.160371E+11 7719.89 31-JUL-24:00 7718.29 0.00
August 0.00 0.00 0.217761E+11 0.211186E+11 8784.00 07-AUG-13:40 8044.48 0.00
September 0.00 0.00 0.625484E+10 0.571383E+10 4019.99 30-SEP-24:00 3989.00 0.00
October 0.00 0.00 0.113695E+11 0.109175E+11 5854.39 31-OCT-24:00 5844.30 0.00
November 0.00 0.00 0.154616E+11 0.152084E+11 6709.07 07-NOV-16:40 6174.56 0.00
December 0.00 0.00 0.207200E+11 0.205395E+11 8667.17 14-DEC-17:00 8198.33 0.00
                 
Annual Sum or Average 0.00 0.00 0.160434E+12 0.155822E+12       0.00
Minimum of Months 0.00 0.00 0.500004E+10 0.489472E+10 2718.81   2362.07 0.00
Maximum of Months 0.00 0.00 0.217761E+11 0.211186E+11 8784.00   8198.33 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.351623E+11 0.341466E+11 25419.11 19-JAN-17:00 21866.79 0.00
February 0.00 0.00 0.804711E+11 0.786294E+11 44065.51 27-FEB-17:00 40554.82 0.00
March 0.00 0.00 0.141251E+12 0.139210E+12 71809.06 31-MAR-24:00 71809.06 0.00
April 0.00 0.00 0.192445E+12 0.189521E+12 82229.22 28-APR-17:20 76953.75 0.00
May 0.00 0.00 0.593120E+11 0.543394E+11 38224.32 31-MAY-23:10 36595.73 0.00
June 0.00 0.00 0.106174E+12 0.100389E+12 56528.30 30-JUN-23:55 56356.65 0.00
July 0.00 0.00 0.158805E+12 0.152298E+12 73901.90 31-JUL-24:00 73873.71 0.00
August 0.00 0.00 0.206729E+12 0.200154E+12 83611.52 14-AUG-16:00 76992.10 0.00
September 0.00 0.00 0.569287E+11 0.516073E+11 37263.99 30-SEP-24:00 36936.72 0.00
October 0.00 0.00 0.105621E+12 0.101134E+12 54238.24 31-OCT-24:00 54113.87 0.00
November 0.00 0.00 0.140840E+12 0.138326E+12 64109.61 07-NOV-16:50 58799.48 0.00
December 0.00 0.00 0.187339E+12 0.185534E+12 82357.51 14-DEC-17:00 77679.41 0.00
                 
Annual Sum or Average 0.00 0.00 0.147108E+13 0.142529E+13       0.00
Minimum of Months 0.00 0.00 0.351623E+11 0.341466E+11 25419.11   21866.79 0.00
Maximum of Months 0.00 0.00 0.206729E+12 0.200154E+12 83611.52   77679.41 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.246367E+10 0.236381E+10 2623.37 19-JAN-17:00 2267.31 0.00
February 0.00 0.00 0.726646E+10 0.708331E+10 4480.53 27-FEB-17:00 4128.91 0.00
March 0.00 0.00 0.135633E+11 0.133598E+11 7094.97 31-MAR-24:00 7094.97 0.00
April 0.00 0.00 0.191377E+11 0.188458E+11 8335.05 28-APR-17:20 7803.90 0.00
May 0.00 0.00 0.610987E+10 0.560978E+10 3810.97 31-MAY-23:10 3649.70 0.00
June 0.00 0.00 0.108075E+11 0.102280E+11 5698.59 30-JUN-23:55 5681.40 0.00
July 0.00 0.00 0.160785E+11 0.154276E+11 7391.30 31-JUL-24:00 7388.31 0.00
August 0.00 0.00 0.208483E+11 0.201905E+11 8486.67 09-AUG-17:00 7760.07 0.00
September 0.00 0.00 0.582362E+10 0.528939E+10 3761.03 30-SEP-24:00 3729.16 0.00
October 0.00 0.00 0.105314E+11 0.100826E+11 5365.55 31-OCT-24:00 5352.61 0.00
November 0.00 0.00 0.135610E+11 0.133106E+11 6470.34 07-NOV-16:40 5937.40 0.00
December 0.00 0.00 0.178591E+11 0.176792E+11 8297.11 14-DEC-17:00 7829.23 0.00
                 
Annual Sum or Average 0.00 0.00 0.144050E+12 0.139471E+12       0.00
Minimum of Months 0.00 0.00 0.246367E+10 0.236381E+10 2623.37   2267.31 0.00
Maximum of Months 0.00 0.00 0.208483E+11 0.201905E+11 8486.67   7829.23 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 6.44 25927.45 03-JAN-06:02 8572.41 1164287.24 09-JAN-06:02
February 0.00 0.00 01-FEB-00:10 4749.09 1053750.78 17-FEB-06:02
March 0.00 0.00 01-MAR-00:10 3597.57 1204389.09 11-MAR-06:02
April 0.00 0.00 01-APR-00:10 84.03 77297.97 18-APR-14:20
May 0.00 0.00 01-MAY-00:03 0.00 0.00 01-MAY-00:03
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 13.99 16441.45 28-OCT-05:03
November 0.00 0.00 01-NOV-00:10 316.13 211962.11 16-NOV-06:02
December 0.00 0.00 01-DEC-00:10 5674.67 1213618.47 20-DEC-05:11
             
Annual Sum or Average 0.55     1913.96    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 6.44 25927.45   8572.41 1213618.47  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 155415.61 1647444.04 19-JAN-11:05 0.00 0.00 01-JAN-00:05
February 246911.76 2149587.64 27-FEB-16:13 0.00 0.00 01-FEB-00:10
March 267252.40 1739370.42 29-MAR-15:30 0.00 0.00 01-MAR-00:10
April 441450.73 2358139.95 27-APR-15:43 0.00 0.00 01-APR-00:10
May 689550.16 2375306.43 10-MAY-15:53 0.00 0.00 01-MAY-00:03
June 729226.94 2366601.31 12-JUN-15:13 0.00 0.00 01-JUN-00:10
July 732255.39 1898447.88 05-JUL-12:05 0.00 0.00 01-JUL-00:10
August 765211.80 1890540.71 22-AUG-12:05 0.00 0.00 01-AUG-00:10
September 701565.61 2259829.37 22-SEP-14:03 0.00 0.00 01-SEP-00:10
October 585483.75 2155621.31 18-OCT-15:23 0.00 0.00 01-OCT-00:10
November 341124.03 2156864.77 06-NOV-10:23 0.00 0.00 01-NOV-00:10
December 234147.69 2282359.68 15-DEC-13:53 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 492118.82     0.00    
Minimum of Months 155415.61 1647444.04   0.00 0.00  
Maximum of Months 765211.80 2375306.43   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 156058.93 2940493.59 19-JAN-16:40 0.00 0.00 01-JAN-00:05
February 252609.81 2891095.84 27-FEB-16:50 0.00 0.00 01-FEB-00:10
March 268570.88 2993786.35 07-MAR-06:02 0.00 0.00 01-MAR-00:10
April 447767.42 2872550.23 29-APR-05:03 0.00 0.00 01-APR-00:10
May 721235.73 3347722.94 22-MAY-03:02 0.00 0.00 01-MAY-00:03
June 751672.02 3070520.94 08-JUN-05:02 0.00 0.00 01-JUN-00:10
July 738940.52 2935279.82 28-JUL-05:03 0.00 0.00 01-JUL-00:10
August 774729.78 3186751.68 26-AUG-05:02 0.00 0.00 01-AUG-00:10
September 721580.27 3466056.12 05-SEP-04:11 0.00 0.00 01-SEP-00:10
October 603218.57 3190567.08 21-OCT-05:03 0.00 0.00 01-OCT-00:10
November 347198.99 3071952.52 01-NOV-05:02 0.00 0.00 01-NOV-00:10
December 239924.81 2720740.29 14-DEC-13:30 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 503295.05     0.00    
Minimum of Months 156058.93 2720740.29   0.00 0.00  
Maximum of Months 774729.78 3466056.12   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 88504.30 741087.86 02-JAN-15:00 0.00 0.00 01-JAN-00:05
February 222623.58 1007467.46 02-FEB-13:05 0.00 0.00 01-FEB-00:10
March 426437.92 1301755.61 26-MAR-14:00 0.00 0.00 01-MAR-00:10
April 927026.05 1713091.31 28-APR-15:00 0.00 0.00 01-APR-00:10
May 721789.62 1081890.85 18-MAY-16:00 0.00 0.00 01-MAY-00:03
June 975042.31 1393306.28 14-JUN-14:00 0.00 0.00 01-JUN-00:10
July 1210588.40 1696436.49 21-JUL-16:00 0.00 0.00 01-JUL-00:10
August 1391459.26 1862941.62 30-AUG-16:10 0.00 0.00 01-AUG-00:10
September 689728.83 1245663.26 09-SEP-17:00 0.00 0.00 01-SEP-00:10
October 736031.95 1345475.24 05-OCT-15:00 0.00 0.00 01-OCT-00:10
November 516883.38 1345271.70 02-NOV-13:00 0.00 0.00 01-NOV-00:10
December 525932.07 1534746.33 13-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 705799.80     0.00    
Minimum of Months 88504.30 741087.86   0.00 0.00  
Maximum of Months 1391459.26 1862941.62   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 12860.29 42455.45 20-JAN-12:10
February 0.00 0.00 01-FEB-00:10 12838.17 42389.67 01-FEB-12:10
March 0.00 0.00 01-MAR-00:10 13080.93 41428.83 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 11678.42 39124.16 03-APR-11:20
May 0.00 0.00 01-MAY-00:03 11278.54 36812.07 01-MAY-11:10
June 0.00 0.00 01-JUN-00:10 10889.39 34304.54 01-JUN-11:50
July 0.00 0.00 01-JUL-00:10 9856.44 32638.70 03-JUL-11:30
August 0.00 0.00 01-AUG-00:10 10755.60 33324.48 31-AUG-11:30
September 0.00 0.00 01-SEP-00:10 10627.69 35276.17 28-SEP-11:10
October 0.00 0.00 01-OCT-00:10 11283.71 37983.60 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 12147.09 40383.69 30-NOV-12:50
December 0.00 0.00 01-DEC-00:10 12315.54 41971.21 28-DEC-12:15
             
Annual Sum or Average 0.00     11627.70    
Minimum of Months 0.00 0.00   9856.44 32638.70  
Maximum of Months 0.00 0.00   13080.93 42455.45  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 216004.53 3685892.62 31-JAN-15:05 1514.07 137258.57 09-JAN-18:30
February 338884.50 3568314.30 24-FEB-13:05 1034.47 153597.34 17-FEB-12:50
March 403296.82 4251035.70 28-MAR-12:05 1742.95 126159.02 09-MAR-08:00
April 726316.42 5047230.40 28-APR-16:00 884.30 103820.54 03-APR-06:20
May 1706898.91 5968741.97 26-MAY-10:05 0.00 0.00 01-MAY-00:03
June 1996074.53 6050985.62 23-JUN-10:05 0.00 0.00 01-JUN-00:10
July 2356342.13 6428734.21 05-JUL-12:05 0.00 0.00 01-JUL-00:10
August 2289078.55 6198678.52 22-AUG-12:05 3.03 13530.86 20-AUG-04:50
September 1891687.94 5944327.10 01-SEP-12:05 0.00 0.00 01-SEP-00:10
October 1426420.45 5990228.93 06-OCT-14:05 293.44 108377.47 28-OCT-09:00
November 605448.27 5427698.26 01-NOV-14:05 766.81 130170.93 15-NOV-10:30
December 384964.95 4945556.40 12-DEC-14:05 1858.03 172934.60 26-DEC-09:10
             
Annual Sum or Average 1200952.81     674.67    
Minimum of Months 216004.53 3568314.30   0.00 0.00  
Maximum of Months 2356342.13 6428734.21   1858.03 172934.60  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.131757E+11 0.80 8497.92 01-JAN-00:13 1.37
February 0.113966E+11 0.77 8497.92 01-FEB-05:12 1.38
March 0.132440E+11 0.80 8497.92 01-MAR-05:12 1.38
April 0.121248E+11 0.76 8497.92 01-APR-04:12 1.38
May 0.132025E+11 0.80 8497.92 01-MAY-03:02 1.38
June 0.130953E+11 0.82 8497.92 01-JUN-04:12 1.38
July 0.129134E+11 0.78 8497.92 01-JUL-03:55 1.37
August 0.145093E+11 0.88 8497.92 01-AUG-03:03 1.38
September 0.135144E+11 0.84 8497.92 01-SEP-04:12 1.38
October 0.138340E+11 0.84 8497.92 01-OCT-16:02 1.38
November 0.132427E+11 0.83 8497.92 01-NOV-04:15 1.38
December 0.133320E+11 0.81 8497.92 01-DEC-05:12 1.38
           
Annual Sum or Average 0.157585E+12 0.81      
Minimum of Months 0.113966E+11 0.76 8497.92   1.37
Maximum of Months 0.145093E+11 0.88 8497.92   1.38



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.345896E+10 0.32 17688.74 02-JAN-06:03 1.72
February 0.363917E+10 0.35 18272.88 27-FEB-05:11 1.76
March 0.454453E+10 0.38 17152.25 27-MAR-05:03 1.69
April 0.548427E+10 0.46 16132.23 27-APR-05:02 1.62
May 0.553935E+10 0.43 18272.88 01-MAY-05:02 1.76
June 0.615410E+10 0.50 18272.88 01-JUN-14:30 1.75
July 0.665993E+10 0.52 18272.88 01-JUL-05:02 1.76
August 0.794075E+10 0.58 18272.88 01-AUG-05:02 1.76
September 0.529625E+10 0.43 18272.88 02-SEP-05:02 1.76
October 0.611159E+10 0.46 18272.88 02-OCT-04:11 1.76
November 0.512788E+10 0.41 18272.88 01-NOV-05:02 1.76
December 0.473504E+10 0.39 14905.21 11-DEC-06:03 1.54
           
Annual Sum or Average 0.646918E+11 0.44      
Minimum of Months 0.345896E+10 0.32 14905.21   1.54
Maximum of Months 0.794075E+10 0.58 18272.88   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.256211E+11 0.29 122260.21 21-JAN-06:02 1.44
February 0.250590E+11 0.30 150395.35 27-FEB-06:02 1.63
March 0.294774E+11 0.32 168844.43 07-MAR-06:02 1.76
April 0.338811E+11 0.33 168844.43 15-APR-05:02 1.76
May 0.476289E+11 0.40 168844.43 03-MAY-12:30 1.76
June 0.489041E+11 0.42 168844.43 03-JUN-05:02 1.76
July 0.477314E+11 0.41 168844.43 07-JUL-05:02 1.76
August 0.510673E+11 0.42 168844.43 01-AUG-05:02 1.76
September 0.432731E+11 0.39 168844.43 01-SEP-04:12 1.76
October 0.458851E+11 0.38 168844.43 03-OCT-05:03 1.76
November 0.324815E+11 0.33 168844.43 01-NOV-05:02 1.76
December 0.279184E+11 0.30 111332.26 11-DEC-06:03 1.35
           
Annual Sum or Average 0.458928E+12 0.36      
Minimum of Months 0.250590E+11 0.29 111332.26   1.35
Maximum of Months 0.510673E+11 0.42 168844.43   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.246492E+10 0.29 8973.13 02-JAN-06:03 1.11
February 0.247665E+10 0.30 8898.74 27-FEB-06:02 1.10
March 0.286172E+10 0.31 10716.99 27-MAR-05:03 1.23
April 0.341813E+10 0.32 14919.09 26-APR-05:02 1.52
May 0.527734E+10 0.40 18774.76 02-MAY-13:00 1.76
June 0.554736E+10 0.43 18774.76 08-JUN-14:30 1.75
July 0.535312E+10 0.42 18774.76 05-JUL-05:02 1.76
August 0.564949E+10 0.43 18774.76 03-AUG-03:02 1.76
September 0.453244E+10 0.39 18774.76 01-SEP-04:12 1.76
October 0.468393E+10 0.37 18774.76 06-OCT-05:02 1.76
November 0.295175E+10 0.31 17251.58 03-NOV-05:02 1.67
December 0.262336E+10 0.29 8428.01 15-DEC-06:03 1.07
           
Annual Sum or Average 0.478402E+11 0.36      
Minimum of Months 0.246492E+10 0.29 8428.01   1.07
Maximum of Months 0.564949E+10 0.43 18774.76   1.76



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.944143E+11 1.35 35250.28 01-JAN-00:05 1.34
February 0.852775E+11 1.35 35250.28 01-FEB-00:10 1.35
March 0.944143E+11 1.35 35250.28 01-MAR-00:10 1.35
April 0.913687E+11 1.35 35250.28 01-APR-00:10 1.35
May 0.944143E+11 1.35 35250.28 01-MAY-00:03 1.35
June 0.913687E+11 1.35 35250.28 01-JUN-00:10 1.35
July 0.944143E+11 1.35 35250.28 01-JUL-00:10 1.35
August 0.944143E+11 1.35 35250.28 01-AUG-00:10 1.35
September 0.913687E+11 1.35 35250.28 01-SEP-00:10 1.35
October 0.944143E+11 1.35 35250.28 01-OCT-00:10 1.35
November 0.913687E+11 1.35 35250.28 01-NOV-00:10 1.35
December 0.944143E+11 1.35 35250.28 01-DEC-00:20 1.35
           
Annual Sum or Average 0.111165E+13 1.35      
Minimum of Months 0.852775E+11 1.35 35250.28   1.34
Maximum of Months 0.944143E+11 1.35 35250.28   1.35



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138306E+10 0.91 516.38 01-JAN-00:05 0.91
February 0.124922E+10 0.91 516.38 01-FEB-00:10 0.91
March 0.138306E+10 0.91 516.38 01-MAR-00:10 0.91
April 0.133845E+10 0.91 516.38 01-APR-00:10 0.91
May 0.138306E+10 0.91 516.38 01-MAY-00:03 0.91
June 0.133845E+10 0.91 516.38 01-JUN-00:10 0.91
July 0.138306E+10 0.91 516.38 01-JUL-00:10 0.91
August 0.138306E+10 0.91 516.38 01-AUG-00:10 0.91
September 0.133845E+10 0.91 516.38 01-SEP-00:10 0.91
October 0.138306E+10 0.91 516.38 01-OCT-00:10 0.91
November 0.133845E+10 0.91 516.38 01-NOV-00:10 0.91
December 0.138306E+10 0.91 516.38 01-DEC-00:10 0.91
           
Annual Sum or Average 0.162844E+11 0.91      
Minimum of Months 0.124922E+10 0.91 516.38   0.91
Maximum of Months 0.138306E+10 0.91 516.38   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.131860E+11 0.91 4923.11 01-JAN-00:10 0.91
February 0.119100E+11 0.91 4923.11 01-FEB-00:10 0.91
March 0.131860E+11 0.91 4923.11 01-MAR-00:10 0.91
April 0.127607E+11 0.91 4923.11 01-APR-00:20 0.91
May 0.131860E+11 0.91 4923.11 01-MAY-00:03 0.91
June 0.127607E+11 0.91 4923.11 01-JUN-00:10 0.91
July 0.131860E+11 0.91 4923.11 01-JUL-00:10 0.91
August 0.131860E+11 0.91 4923.11 01-AUG-00:10 0.91
September 0.127607E+11 0.91 4923.11 01-SEP-00:10 0.91
October 0.131860E+11 0.91 4923.11 01-OCT-00:10 0.91
November 0.127607E+11 0.91 4923.11 01-NOV-00:10 0.91
December 0.131860E+11 0.91 4923.11 01-DEC-00:10 0.91
           
Annual Sum or Average 0.155255E+12 0.91      
Minimum of Months 0.119100E+11 0.91 4923.11   0.91
Maximum of Months 0.131860E+11 0.91 4923.11   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.134485E+10 0.91 502.11 01-JAN-00:05 0.91
February 0.121470E+10 0.91 502.11 01-FEB-00:10 0.91
March 0.134485E+10 0.91 502.11 01-MAR-00:10 0.91
April 0.130146E+10 0.91 502.11 01-APR-00:10 0.91
May 0.134485E+10 0.91 502.11 01-MAY-00:03 0.91
June 0.130146E+10 0.91 502.11 01-JUN-00:10 0.91
July 0.134485E+10 0.91 502.11 01-JUL-00:10 0.91
August 0.134485E+10 0.91 502.11 01-AUG-00:10 0.91
September 0.130146E+10 0.91 502.11 01-SEP-00:10 0.91
October 0.134485E+10 0.91 502.11 01-OCT-00:10 0.91
November 0.130146E+10 0.91 502.11 01-NOV-00:10 0.91
December 0.134485E+10 0.91 502.11 01-DEC-00:10 0.91
           
Annual Sum or Average 0.158345E+11 0.91      
Minimum of Months 0.121470E+10 0.91 502.11   0.91
Maximum of Months 0.134485E+10 0.91 502.11   0.91



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.195199E+09 0.177436E+09 6559.61 09-JAN-06:02 5962.68 5962.68 38.05 12.69
February 0.100646E+09 91486907.96 6556.47 06-FEB-06:02 5959.83 5959.83 44.51 12.64
March 75734217.24 68842403.47 6554.23 11-MAR-06:02 5957.80 5957.80 37.25 12.67
April 1774969.12 1613446.93 624.88 18-APR-14:20 568.01 568.01 32.08 0.66
May 0.00 0.00 0.00 01-MAY-00:03 0.00 0.00 39.42 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 39.42 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 39.42 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 39.42 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 39.42 0.00
October 398396.11 362142.06 185.20 28-OCT-05:03 168.35 168.35 39.46 0.19
November 6377733.06 5797359.35 1499.87 16-NOV-06:02 1363.38 1363.38 29.64 1.67
December 0.125685E+09 0.114248E+09 6564.39 21-DEC-06:01 5967.03 5967.03 41.84 12.70
                 
Annual Sum or Average 0.505815E+09 0.459786E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 29.64 0.00
Maximum of Months 0.195199E+09 0.177436E+09 6564.39   5967.03 5967.03 44.51 12.70



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.332919E+09 0.302624E+09 12211.70 19-JAN-16:40 11100.43 11100.43 11.51 76.25
February 0.645774E+09 0.587009E+09 12456.02 27-FEB-16:50 11322.52 11322.52 10.98 76.85
March 0.643381E+09 0.584833E+09 12530.71 07-MAR-06:04 11390.41 11390.41 10.89 77.05
April 0.117683E+10 0.106974E+10 12030.88 25-APR-14:00 10936.07 10936.07 12.34 75.80
May 0.265781E+10 0.241595E+10 12530.71 03-MAY-04:13 11390.41 11390.41 10.54 77.05
June 0.254924E+10 0.231726E+10 12530.71 03-JUN-05:02 11390.41 11390.41 9.37 77.05
July 0.231362E+10 0.210308E+10 12530.71 24-JUL-14:30 11390.41 11390.41 12.50 77.05
August 0.254880E+10 0.231686E+10 12530.71 01-AUG-05:02 11390.41 11390.41 9.38 77.05
September 0.237870E+10 0.216224E+10 12530.71 06-SEP-05:02 11390.41 11390.41 9.46 77.05
October 0.207977E+10 0.189051E+10 12530.71 06-OCT-05:02 11390.41 11390.41 9.37 77.05
November 0.916653E+09 0.833237E+09 12530.71 01-NOV-05:02 11390.41 11390.41 9.42 77.05
December 0.670206E+09 0.609217E+09 12262.47 14-DEC-13:30 11146.58 11146.58 11.56 76.37
                 
Annual Sum or Average 0.189137E+11 0.171925E+11            
Minimum of Months 0.332919E+09 0.302624E+09 12030.88   10936.07 10936.07 9.37 75.80
Maximum of Months 0.265781E+10 0.241595E+10 12530.71   11390.41 11390.41 12.50 77.05



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.443677E+10 0.403302E+10 4312.27 01-JAN-04:03 3919.86 3919.86 6.93 38.53
February 0.506364E+10 0.460285E+10 4312.27 01-FEB-05:12 3919.86 3919.86 9.50 38.53
March 0.636315E+10 0.578410E+10 4312.27 01-MAR-05:12 3919.86 3919.86 10.14 38.53
April 0.853209E+10 0.775567E+10 4312.27 01-APR-04:12 3919.86 3919.86 9.64 38.53
May 0.839233E+10 0.762863E+10 4312.27 01-MAY-00:10 3919.86 3919.86 6.95 38.53
June 0.926608E+10 0.842287E+10 4312.27 01-JUN-04:12 3919.86 3919.86 13.03 38.53
July 0.102263E+11 0.929567E+10 4312.27 01-JUL-00:10 3919.86 3919.86 6.97 38.53
August 0.105464E+11 0.958671E+10 4312.27 01-AUG-00:10 3919.86 3919.86 6.98 38.53
September 0.830242E+10 0.754690E+10 4312.27 01-SEP-00:10 3919.86 3919.86 6.96 38.53
October 0.853175E+10 0.775536E+10 4312.27 01-OCT-07:30 3919.86 3919.86 8.23 38.53
November 0.700128E+10 0.636416E+10 4312.27 01-NOV-03:43 3919.86 3919.86 8.70 38.53
December 0.583972E+10 0.530831E+10 4312.27 01-DEC-05:12 3919.86 3919.86 7.19 38.53
                 
Annual Sum or Average 0.925019E+11 0.840842E+11            
Minimum of Months 0.443677E+10 0.403302E+10 4312.27   3919.86 3919.86 6.93 38.53
Maximum of Months 0.105464E+11 0.958671E+10 4312.27   3919.86 3919.86 13.03 38.53



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.111257E+09 0.101132E+09 4312.27 18-JAN-14:50 3919.86 3919.86 15.50 19.26
February 0.256580E+09 0.233231E+09 4312.27 01-FEB-16:20 3919.86 3919.86 15.33 19.26
March 0.316952E+09 0.288109E+09 4312.27 06-MAR-09:40 3919.86 3919.86 15.45 19.26
April 0.561027E+09 0.509973E+09 4312.27 05-APR-14:50 3919.86 3919.86 15.35 19.26
May 0.207300E+10 0.188435E+10 4312.27 01-MAY-07:50 3919.86 3919.86 15.51 19.26
June 0.235752E+10 0.214299E+10 4312.27 01-JUN-08:00 3919.86 3919.86 15.33 19.26
July 0.261065E+10 0.237308E+10 4312.27 03-JUL-07:50 3919.86 3919.86 15.68 19.26
August 0.287068E+10 0.260945E+10 4312.27 01-AUG-08:00 3919.86 3919.86 15.50 19.26
September 0.214534E+10 0.195012E+10 4312.27 01-SEP-07:30 3919.86 3919.86 15.55 19.26
October 0.188662E+10 0.171494E+10 4312.27 02-OCT-09:40 3919.86 3919.86 15.38 19.26
November 0.585607E+09 0.532317E+09 4312.27 01-NOV-07:40 3919.86 3919.86 15.47 19.26
December 0.357056E+09 0.324564E+09 4312.27 11-DEC-09:50 3919.86 3919.86 15.37 19.26
                 
Annual Sum or Average 0.161323E+11 0.146643E+11            
Minimum of Months 0.111257E+09 0.101132E+09 4312.27   3919.86 3919.86 15.33 19.26
Maximum of Months 0.287068E+10 0.260945E+10 4312.27   3919.86 3919.86 15.68 19.26



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.896853E+10 0.815239E+10 3348.46 01-JAN-00:05 3043.75 3043.75 18.98 14.12
February 0.810060E+10 0.736345E+10 3348.46 01-FEB-00:10 3043.75 3043.75 26.84 14.12
March 0.896853E+10 0.815239E+10 3348.46 01-MAR-00:10 3043.75 3043.75 30.18 14.12
April 0.867922E+10 0.788941E+10 3348.46 01-APR-00:10 3043.75 3043.75 38.15 14.12
May 0.896853E+10 0.815239E+10 3348.46 01-MAY-00:03 3043.75 3043.75 28.39 14.12
June 0.867922E+10 0.788941E+10 3348.46 01-JUN-00:10 3043.75 3043.75 32.50 14.12
July 0.896853E+10 0.815239E+10 3348.46 01-JUL-00:10 3043.75 3043.75 38.89 14.12
August 0.896853E+10 0.815239E+10 3348.46 01-AUG-00:10 3043.75 3043.75 43.13 14.12
September 0.867922E+10 0.788941E+10 3348.46 01-SEP-00:10 3043.75 3043.75 31.24 14.12
October 0.896853E+10 0.815239E+10 3348.46 01-OCT-00:10 3043.75 3043.75 31.73 14.12
November 0.867922E+10 0.788941E+10 3348.46 01-NOV-00:10 3043.75 3043.75 35.14 14.12
December 0.896853E+10 0.815239E+10 3348.46 01-DEC-00:10 3043.75 3043.75 22.56 14.12
                 
Annual Sum or Average 0.105597E+12 0.959878E+11            
Minimum of Months 0.810060E+10 0.736345E+10 3348.46   3043.75 3043.75 18.98 14.12
Maximum of Months 0.896853E+10 0.815239E+10 3348.46   3043.75 3043.75 43.13 14.12



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 55.98 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:03 16.86 16.86 56.17 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:03 16.86 16.86 56.70 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:03 16.86 16.86 56.38 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:02 16.86 16.86 56.55 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 57.65 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:02 16.86 16.86 57.91 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 57.02 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:02 16.86 16.86 56.87 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.99 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:02 16.86 16.86 56.26 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:03 16.86 16.86 56.00 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.98 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.91 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.172427E+11 0.156736E+11 32909.98 31-JAN-15:05 29915.17 29915.17 27.68 134.03
February 0.200081E+11 0.181874E+11 32904.18 24-FEB-13:05 29909.90 29909.90 27.47 134.03
March 0.253099E+11 0.230067E+11 32937.87 28-MAR-12:05 29940.52 29940.52 28.69 134.03
April 0.342667E+11 0.311484E+11 32941.16 25-APR-14:05 29943.51 29943.51 29.18 134.03
May 0.393818E+11 0.357981E+11 32941.16 01-MAY-09:30 29943.51 29943.51 28.88 134.03
June 0.438804E+11 0.398873E+11 32941.16 01-JUN-09:05 29943.51 29943.51 28.88 134.03
July 0.488347E+11 0.443907E+11 32941.16 03-JUL-07:50 29943.51 29943.51 29.48 134.03
August 0.510265E+11 0.463831E+11 32941.16 01-AUG-08:30 29943.51 29943.51 29.43 134.03
September 0.395907E+11 0.359880E+11 32941.16 01-SEP-07:40 29943.51 29943.51 28.81 134.03
October 0.392933E+11 0.357176E+11 32941.16 04-OCT-09:05 29943.51 29943.51 29.23 134.03
November 0.287405E+11 0.261251E+11 32941.16 01-NOV-10:05 29943.51 29943.51 29.53 134.03
December 0.233501E+11 0.212253E+11 32941.16 12-DEC-14:05 29943.51 29943.51 29.93 134.03
                 
Annual Sum or Average 0.410925E+12 0.373531E+12            
Minimum of Months 0.172427E+11 0.156736E+11 32904.18   29909.90 29909.90 27.47 134.03
Maximum of Months 0.510265E+11 0.463831E+11 32941.16   29943.51 29943.51 29.93 134.03



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 6.44 25927.45 03-JAN-06:02 59.75 59.75 8572.41 1164287.24 09-JAN-06:02
February 0.00 0.00 01-FEB-00:10 25.30 25.30 4749.09 1053750.78 17-FEB-06:02
March 0.00 0.00 01-MAR-00:10 25.01 25.01 3597.57 1204389.09 11-MAR-06:02
April 0.00 0.00 01-APR-00:10 26.08 26.08 84.03 77297.97 18-APR-14:20
May 0.00 0.00 01-MAY-00:03 39.42 39.42 0.00 0.00 01-MAY-00:03
June 0.00 0.00 01-JUN-00:10 39.42 39.42 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 39.42 39.42 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 39.42 39.42 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 39.42 39.42 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 39.42 39.42 13.99 16441.45 28-OCT-05:03
November 0.00 0.00 01-NOV-00:10 36.39 36.39 316.13 211962.11 16-NOV-06:02
December 0.00 0.00 01-DEC-00:10 27.87 27.87 5674.67 1213618.47 20-DEC-05:11
                 
Annual Sum or Average 0.55         1913.96    
Minimum of Months 0.00 0.00   25.01 25.01 0.00 0.00  
Maximum of Months 6.44 25927.45   59.75 59.75 8572.41 1213618.47  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 155415.61 1647444.04 19-JAN-11:05 11.80 6.70 0.00 0.00 01-JAN-00:05
February 246911.76 2149587.64 27-FEB-16:13 13.36 6.70 0.00 0.00 01-FEB-00:10
March 267252.40 1739370.42 29-MAR-15:30 12.09 6.70 0.00 0.00 01-MAR-00:10
April 441450.73 2358139.95 27-APR-15:43 14.01 6.70 0.00 0.00 01-APR-00:10
May 689550.16 2375306.43 10-MAY-15:53 14.06 6.70 0.00 0.00 01-MAY-00:03
June 729226.94 2366601.31 12-JUN-15:13 14.04 6.70 0.00 0.00 01-JUN-00:10
July 732255.39 1898447.88 05-JUL-12:05 12.58 6.70 0.00 0.00 01-JUL-00:10
August 765211.80 1890540.71 22-AUG-12:05 12.56 6.70 0.00 0.00 01-AUG-00:10
September 701565.61 2259829.37 22-SEP-14:03 13.71 6.70 0.00 0.00 01-SEP-00:10
October 585483.75 2155621.31 18-OCT-15:23 13.38 6.70 0.00 0.00 01-OCT-00:10
November 341124.03 2156864.77 06-NOV-10:23 13.39 6.70 0.00 0.00 01-NOV-00:10
December 234147.69 2282359.68 15-DEC-13:53 13.78 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 492118.82         0.00    
Minimum of Months 155415.61 1647444.04   11.80 6.70 0.00 0.00  
Maximum of Months 765211.80 2375306.43   14.06 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 156058.93 2940493.59 19-JAN-16:40 15.92 11.57 0.00 0.00 01-JAN-00:05
February 252609.81 2891095.84 27-FEB-16:50 15.69 11.17 0.00 0.00 01-FEB-00:10
March 268570.88 2993786.35 07-MAR-06:02 16.06 11.33 0.00 0.00 01-MAR-00:10
April 447767.42 2872550.23 29-APR-05:03 15.85 11.14 0.00 0.00 01-APR-00:10
May 721235.73 3347722.94 22-MAY-03:02 17.09 11.88 0.00 0.00 01-MAY-00:03
June 751672.02 3070520.94 08-JUN-05:02 16.22 11.45 0.00 0.00 01-JUN-00:10
July 738940.52 2935279.82 28-JUL-05:03 15.80 11.24 0.00 0.00 01-JUL-00:10
August 774729.78 3186751.68 26-AUG-05:02 16.59 11.63 0.00 0.00 01-AUG-00:10
September 721580.27 3466056.12 05-SEP-04:11 17.95 12.05 0.00 0.00 01-SEP-00:10
October 603218.57 3190567.08 21-OCT-05:03 16.60 11.63 0.00 0.00 01-OCT-00:10
November 347198.99 3071952.52 01-NOV-05:02 16.23 11.45 0.00 0.00 01-NOV-00:10
December 239924.81 2720740.29 14-DEC-13:30 15.21 11.54 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 503295.05         0.00    
Minimum of Months 156058.93 2720740.29   15.21 11.14 0.00 0.00  
Maximum of Months 774729.78 3466056.12   17.95 12.05 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 88504.30 741087.86 02-JAN-15:00 33.27 28.89 0.00 0.00 01-JAN-00:05
February 222623.58 1007467.46 02-FEB-13:05 38.54 31.34 0.00 0.00 01-FEB-00:10
March 426437.92 1301755.61 26-MAR-14:00 44.29 34.37 0.00 0.00 01-MAR-00:10
April 927026.05 1713091.31 28-APR-15:00 52.24 39.15 0.00 0.00 01-APR-00:10
May 721789.62 1081890.85 18-MAY-16:00 40.00 35.34 0.00 0.00 01-MAY-00:03
June 975042.31 1393306.28 14-JUN-14:00 46.07 38.39 0.00 0.00 01-JUN-00:10
July 1210588.40 1696436.49 21-JUL-16:00 51.92 40.98 0.00 0.00 01-JUL-00:10
August 1391459.26 1862941.62 30-AUG-16:10 55.12 41.96 0.00 0.00 01-AUG-00:10
September 689728.83 1245663.26 09-SEP-17:00 43.20 38.48 0.00 0.00 01-SEP-00:10
October 736031.95 1345475.24 05-OCT-15:00 45.14 37.41 0.00 0.00 01-OCT-00:10
November 516883.38 1345271.70 02-NOV-13:00 45.14 34.63 0.00 0.00 01-NOV-00:10
December 525932.07 1534746.33 13-DEC-15:00 48.81 35.78 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 705799.80         0.00    
Minimum of Months 88504.30 741087.86   33.27 28.89 0.00 0.00  
Maximum of Months 1391459.26 1862941.62   55.12 41.96 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.27 57.27 12860.29 42455.45 20-JAN-12:10
February 0.00 0.00 01-FEB-00:10 56.69 56.69 12838.17 42389.67 01-FEB-12:10
March 0.00 0.00 01-MAR-00:10 57.29 57.29 13080.93 41428.83 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 56.85 56.85 11678.42 39124.16 03-APR-11:20
May 0.00 0.00 01-MAY-00:03 57.15 57.15 11278.54 36812.07 01-MAY-11:10
June 0.00 0.00 01-JUN-00:10 57.93 57.93 10889.39 34304.54 01-JUN-11:50
July 0.00 0.00 01-JUL-00:10 58.10 58.10 9856.44 32638.70 03-JUL-11:30
August 0.00 0.00 01-AUG-00:10 57.32 57.32 10755.60 33324.48 31-AUG-11:30
September 0.00 0.00 01-SEP-00:10 57.18 57.18 10627.69 35276.17 28-SEP-11:10
October 0.00 0.00 01-OCT-00:10 57.74 57.74 11283.71 37983.60 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 56.70 56.70 12147.09 40383.69 30-NOV-12:50
December 0.00 0.00 01-DEC-00:10 56.49 56.49 12315.54 41971.21 28-DEC-12:15
                 
Annual Sum or Average 0.00         11627.70    
Minimum of Months 0.00 0.00   56.49 56.49 9856.44 32638.70  
Maximum of Months 0.00 0.00   58.10 58.10 13080.93 42455.45  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 216004.53 3685892.62 31-JAN-15:05 27.68 23.97 1514.07 137258.57 09-JAN-18:30
February 338884.50 3568314.30 24-FEB-13:05 27.47 23.85 1034.47 153597.34 17-FEB-12:50
March 403296.82 4251035.70 28-MAR-12:05 28.69 24.85 1742.95 126159.02 09-MAR-08:00
April 726316.42 5047230.40 28-APR-16:00 30.11 27.05 884.30 103820.54 03-APR-06:20
May 1706898.91 5968741.97 26-MAY-10:05 31.75 27.77 0.00 0.00 01-MAY-00:03
June 1996074.53 6050985.62 23-JUN-10:05 31.90 27.95 0.00 0.00 01-JUN-00:10
July 2356342.13 6428734.21 05-JUL-12:05 32.58 28.44 0.00 0.00 01-JUL-00:10
August 2289078.55 6198678.52 22-AUG-12:05 32.16 28.04 3.03 13530.86 20-AUG-04:50
September 1891687.94 5944327.10 01-SEP-12:05 31.71 27.52 0.00 0.00 01-SEP-00:10
October 1426420.45 5990228.93 06-OCT-14:05 31.79 28.29 293.44 108377.47 28-OCT-09:00
November 605448.27 5427698.26 01-NOV-14:05 30.79 26.94 766.81 130170.93 15-NOV-10:30
December 384964.95 4945556.40 12-DEC-14:05 29.93 26.17 1858.03 172934.60 26-DEC-09:10
                 
Annual Sum or Average 1200952.81         674.67    
Minimum of Months 216004.53 3568314.30   27.47 23.85 0.00 0.00  
Maximum of Months 2356342.13 6428734.21   32.58 28.44 1858.03 172934.60  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 91371410.27 0.00 0.389122E+11 0.345896E+10 0.00 0.00
February 29683817.63 0.00 0.554933E+11 0.363917E+10 0.00 0.00
March 13950351.28 0.00 0.694834E+11 0.454453E+10 0.00 0.00
April 13748102.89 0.00 0.113392E+12 0.548427E+10 0.00 0.00
May 0.00 0.00 0.142564E+12 0.553935E+10 0.00 0.00
June 0.00 0.00 0.154722E+12 0.615410E+10 0.00 0.00
July 0.00 0.00 0.168254E+12 0.665993E+10 0.00 0.00
August 0.00 0.00 0.185142E+12 0.794075E+10 0.00 0.00
September 0.00 0.00 0.143539E+12 0.529625E+10 0.00 0.00
October 0.00 0.00 0.134782E+12 0.611159E+10 0.00 0.00
November 58268.81 0.00 0.847191E+11 0.512788E+10 0.00 0.00
December 52378516.45 0.00 0.633503E+11 0.473504E+10 0.00 0.00
             
Annual Sum or Average 0.201190E+09 0.00 0.135435E+13 0.646918E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.389122E+11 0.345896E+10 0.00 0.00
Maximum of Months 91371410.27 0.00 0.185142E+12 0.794075E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.166341E+11 0.00 0.308391E+12 0.256211E+11 0.00 0.00
February 0.762112E+10 0.00 0.436165E+12 0.250590E+11 0.00 0.00
March 0.674975E+10 0.00 0.518457E+12 0.294774E+11 0.00 0.00
April 52089634.06 0.00 0.818957E+12 0.338811E+11 0.00 0.00
May 0.00 0.00 0.129612E+13 0.476289E+11 0.00 0.00
June 0.00 0.00 0.132443E+13 0.489041E+11 0.00 0.00
July 0.00 0.00 0.137971E+13 0.477314E+11 0.00 0.00
August 0.00 0.00 0.142465E+13 0.510673E+11 0.00 0.00
September 0.00 0.00 0.128209E+13 0.432731E+11 0.00 0.00
October 0.00 0.00 0.112227E+13 0.458851E+11 0.00 0.00
November 0.390766E+09 0.00 0.643854E+12 0.324815E+11 0.00 0.00
December 0.106460E+11 0.00 0.450324E+12 0.279184E+11 0.00 0.00
             
Annual Sum or Average 0.420938E+11 0.00 0.110054E+14 0.458928E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.308391E+12 0.250590E+11 0.00 0.00
Maximum of Months 0.166341E+11 0.00 0.142465E+13 0.510673E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.671123E+10 0.00 0.303282E+11 0.246492E+10 0.00 0.00
February 0.394616E+10 0.00 0.440308E+11 0.247665E+10 0.00 0.00
March 0.294476E+10 0.00 0.534965E+11 0.286172E+10 0.00 0.00
April 50152165.55 0.00 0.866360E+11 0.341813E+10 0.00 0.00
May 0.00 0.00 0.143674E+12 0.527734E+10 0.00 0.00
June 0.00 0.00 0.149056E+12 0.554736E+10 0.00 0.00
July 0.00 0.00 0.154574E+12 0.535312E+10 0.00 0.00
August 0.00 0.00 0.157917E+12 0.564949E+10 0.00 0.00
September 0.00 0.00 0.138163E+12 0.453244E+10 0.00 0.00
October 61384239.87 0.00 0.120021E+12 0.468393E+10 0.00 0.00
November 0.501636E+09 0.00 0.626074E+11 0.295175E+10 0.00 0.00
December 0.466501E+10 0.00 0.433980E+11 0.262336E+10 0.00 0.00
             
Annual Sum or Average 0.188803E+11 0.00 0.118390E+13 0.478402E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.303282E+11 0.246492E+10 0.00 0.00
Maximum of Months 0.671123E+10 0.00 0.157917E+12 0.564949E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.203163E+11 0.131757E+11 0.00 0.00
February 0.00 0.00 0.237956E+11 0.113966E+11 0.00 0.00
March 0.00 0.00 0.325190E+11 0.132440E+11 0.00 0.00
April 0.00 0.00 0.512819E+11 0.121248E+11 0.00 0.00
May 0.00 0.00 0.953758E+11 0.132025E+11 0.00 0.00
June 0.00 0.00 0.100442E+12 0.130953E+11 0.00 0.00
July 0.00 0.00 0.109203E+12 0.129134E+11 0.00 0.00
August 0.00 0.00 0.121463E+12 0.145093E+11 0.00 0.00
September 0.00 0.00 0.103109E+12 0.135144E+11 0.00 0.00
October 80.37 0.00 0.887705E+11 0.138340E+11 0.00 0.00
November 261.28 0.00 0.489548E+11 0.132427E+11 0.00 0.00
December 79.87 0.00 0.317500E+11 0.133320E+11 0.00 0.00
             
Annual Sum or Average 421.52 0.00 0.826981E+12 0.157585E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.203163E+11 0.113966E+11 0.00 0.00
Maximum of Months 261.28 0.00 0.121463E+12 0.145093E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.501548E+11 0.154485E+12 0.00 17.93
February 0.00 0.00 0.185767E+12 0.179518E+12 0.00 20.80
March 0.00 0.00 0.453330E+12 0.261572E+12 0.00 27.70
April 0.00 0.00 0.107136E+13 0.329048E+12 0.00 7.40
May 0.00 0.00 0.448919E+12 0.195689E+12 0.00 0.00
June 0.00 0.00 0.742908E+12 0.259596E+12 0.00 0.00
July 0.00 0.00 0.108732E+13 0.341010E+12 0.00 0.00
August 0.00 0.00 0.138515E+13 0.400504E+12 0.00 0.00
September 0.00 0.00 0.437947E+12 0.188592E+12 0.00 0.00
October 0.00 0.00 0.621469E+12 0.246512E+12 0.00 5.95
November 0.00 0.00 0.526723E+12 0.247300E+12 0.00 17.53
December 0.00 0.00 0.624332E+12 0.296362E+12 0.00 28.63
             
Annual Sum or Average 0.00 0.00 0.763537E+13 0.310019E+13 0.00 125.96
Minimum of Months 0.00 0.00 0.501548E+11 0.154485E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.138515E+13 0.400504E+12 0.00 28.63



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.613328E+10 0.251630E+10 0.00 0.00
February 0.00 0.00 0.115155E+11 0.331225E+10 0.00 0.00
March 0.00 0.00 0.191021E+11 0.482641E+10 0.00 0.00
April 0.00 0.00 0.252959E+11 0.621109E+10 0.00 0.00
May 0.00 0.00 0.825580E+10 0.321838E+10 0.00 0.00
June 0.00 0.00 0.144267E+11 0.455788E+10 0.00 0.00
July 0.00 0.00 0.214984E+11 0.619184E+10 0.00 0.00
August 0.00 0.00 0.279458E+11 0.755279E+10 0.00 0.00
September 0.00 0.00 0.800491E+10 0.308853E+10 0.00 0.00
October 0.00 0.00 0.143618E+11 0.437537E+10 0.00 0.00
November 0.00 0.00 0.189464E+11 0.482319E+10 0.00 0.00
December 0.00 0.00 0.251396E+11 0.580267E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.200626E+12 0.564767E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.613328E+10 0.251630E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.279458E+11 0.755279E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.433494E+11 0.213731E+11 0.00 0.00
February 0.00 0.00 0.982632E+11 0.297021E+11 0.00 0.00
March 0.00 0.00 0.172604E+12 0.445385E+11 0.00 0.00
April 0.00 0.00 0.238511E+12 0.588268E+11 0.00 0.00
May 0.00 0.00 0.763105E+11 0.301846E+11 0.00 0.00
June 0.00 0.00 0.136700E+12 0.432862E+11 0.00 0.00
July 0.00 0.00 0.204584E+12 0.589649E+11 0.00 0.00
August 0.00 0.00 0.265369E+12 0.718260E+11 0.00 0.00
September 0.00 0.00 0.729110E+11 0.287430E+11 0.00 0.00
October 0.00 0.00 0.133549E+12 0.411145E+11 0.00 0.00
November 0.00 0.00 0.172852E+12 0.447722E+11 0.00 0.00
December 0.00 0.00 0.227716E+12 0.535630E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.184272E+13 0.526895E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.433494E+11 0.213731E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.265369E+12 0.718260E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.305367E+10 0.193484E+10 0.00 0.00
February 0.00 0.00 0.889310E+10 0.284135E+10 0.00 0.00
March 0.00 0.00 0.166033E+11 0.438486E+10 0.00 0.00
April 0.00 0.00 0.237410E+11 0.590482E+10 0.00 0.00
May 0.00 0.00 0.786214E+10 0.309711E+10 0.00 0.00
June 0.00 0.00 0.139173E+11 0.441118E+10 0.00 0.00
July 0.00 0.00 0.207190E+11 0.598537E+10 0.00 0.00
August 0.00 0.00 0.267749E+11 0.727152E+10 0.00 0.00
September 0.00 0.00 0.746126E+10 0.293910E+10 0.00 0.00
October 0.00 0.00 0.133302E+11 0.414363E+10 0.00 0.00
November 0.00 0.00 0.166732E+11 0.441363E+10 0.00 0.00
December 0.00 0.00 0.217536E+11 0.523942E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.180783E+12 0.525668E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.305367E+10 0.193484E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.267749E+11 0.727152E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.345896E+10 0.389122E+11 91371410.27 0.386326E+09 0.789578E+09 0.00 0.00 0.00
February 0.363917E+10 0.554933E+11 29683817.63 0.132152E+09 0.134728E+10 0.00 0.00 0.00
March 0.454453E+10 0.694834E+11 13950351.28 78596446.47 0.259508E+10 0.00 0.00 0.00
April 0.548427E+10 0.113392E+12 13748102.89 0.00 0.733585E+10 0.00 0.00 0.00
May 0.553935E+10 0.142564E+12 0.00 0.00 0.309942E+11 0.00 0.00 0.00
June 0.615410E+10 0.154722E+12 0.00 0.00 0.379873E+11 0.00 0.00 0.00
July 0.665993E+10 0.168254E+12 0.00 0.00 0.415012E+11 0.00 0.00 0.00
August 0.794075E+10 0.185142E+12 0.00 0.00 0.404826E+11 0.00 0.00 0.00
September 0.529625E+10 0.143539E+12 0.00 0.00 0.270041E+11 0.00 0.00 0.00
October 0.611159E+10 0.134782E+12 0.00 0.00 0.229330E+11 0.00 0.00 0.00
November 0.512788E+10 0.847191E+11 58268.81 0.00 0.542459E+10 0.00 0.00 0.00
December 0.473504E+10 0.633503E+11 52378516.45 0.217240E+09 0.301986E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.646918E+11 0.135435E+13 0.201190E+09 0.814314E+09 0.221415E+12 0.00 0.00 0.00
Minimum of Months 0.345896E+10 0.389122E+11 0.00 0.00 0.789578E+09 0.00 0.00 0.00
Maximum of Months 0.794075E+10 0.185142E+12 91371410.27 0.386326E+09 0.415012E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.256211E+11 0.308391E+12 0.166341E+11 0.615686E+10 0.972959E+10 0.00 0.00 0.00
February 0.250590E+11 0.436165E+12 0.762112E+10 0.273490E+10 0.161120E+11 0.00 0.00 0.00
March 0.294774E+11 0.518457E+12 0.674975E+10 0.170043E+10 0.304610E+11 0.00 0.00 0.00
April 0.338811E+11 0.818957E+12 52089634.06 17980834.19 0.733600E+11 0.00 0.00 0.00
May 0.476289E+11 0.129612E+13 0.00 0.00 0.312719E+12 0.00 0.00 0.00
June 0.489041E+11 0.132443E+13 0.00 0.00 0.382447E+12 0.00 0.00 0.00
July 0.477314E+11 0.137971E+13 0.00 0.00 0.419472E+12 0.00 0.00 0.00
August 0.510673E+11 0.142465E+13 0.00 0.00 0.411574E+12 0.00 0.00 0.00
September 0.432731E+11 0.128209E+13 0.00 0.00 0.275513E+12 0.00 0.00 0.00
October 0.458851E+11 0.112227E+13 0.00 0.00 0.232576E+12 0.00 0.00 0.00
November 0.324815E+11 0.643854E+12 0.390766E+09 5087996.78 0.600954E+11 0.00 0.00 0.00
December 0.279184E+11 0.450324E+12 0.106460E+11 0.456138E+10 0.322830E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.458928E+12 0.110054E+14 0.420938E+11 0.151766E+11 0.225634E+13 0.00 0.00 0.00
Minimum of Months 0.250590E+11 0.308391E+12 0.00 0.00 0.972959E+10 0.00 0.00 0.00
Maximum of Months 0.510673E+11 0.142465E+13 0.166341E+11 0.615686E+10 0.419472E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.246492E+10 0.303282E+11 0.671123E+10 0.101392E+10 0.268089E+09 0.00 0.00 0.00
February 0.247665E+10 0.440308E+11 0.394616E+10 0.470814E+09 0.760532E+09 0.00 0.00 0.00
March 0.286172E+10 0.534965E+11 0.294476E+10 0.296831E+09 0.194530E+10 0.00 0.00 0.00
April 0.341813E+10 0.866360E+11 50152165.55 0.00 0.617322E+10 0.00 0.00 0.00
May 0.527734E+10 0.143674E+12 0.00 0.00 0.297913E+11 0.00 0.00 0.00
June 0.554736E+10 0.149056E+12 0.00 0.00 0.364207E+11 0.00 0.00 0.00
July 0.535312E+10 0.154574E+12 0.00 0.00 0.399118E+11 0.00 0.00 0.00
August 0.564949E+10 0.157917E+12 0.00 0.00 0.391881E+11 0.00 0.00 0.00
September 0.453244E+10 0.138163E+12 0.00 0.00 0.262538E+11 0.00 0.00 0.00
October 0.468393E+10 0.120021E+12 61384239.87 0.00 0.223347E+11 0.00 0.00 0.00
November 0.295175E+10 0.626074E+11 0.501636E+09 2604559.76 0.553273E+10 0.00 0.00 0.00
December 0.262336E+10 0.433980E+11 0.466501E+10 0.721659E+09 0.283982E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.478402E+11 0.118390E+13 0.188803E+11 0.250583E+10 0.211420E+12 0.00 0.00 0.00
Minimum of Months 0.246492E+10 0.303282E+11 0.00 0.00 0.268089E+09 0.00 0.00 0.00
Maximum of Months 0.564949E+10 0.157917E+12 0.671123E+10 0.101392E+10 0.399118E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.131757E+11 0.203163E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.113966E+11 0.237956E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.132440E+11 0.325190E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.121248E+11 0.512819E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132025E+11 0.953758E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130953E+11 0.100442E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129134E+11 0.109203E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145093E+11 0.121463E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135144E+11 0.103109E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138340E+11 0.887705E+11 80.37 0.00 0.00 0.00 0.00 0.00
November 0.132427E+11 0.489548E+11 261.28 0.00 0.00 0.00 0.00 0.00
December 0.133320E+11 0.317500E+11 79.87 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.157585E+12 0.826981E+12 421.52 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.113966E+11 0.203163E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145093E+11 0.121463E+12 261.28 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.944143E+11 0.382904E+11 0.00 0.00 0.00 0.479905E+11 0.00 0.00
February 0.852775E+11 0.147440E+12 0.00 0.00 0.00 0.556631E+11 0.00 0.00
March 0.944143E+11 0.360646E+12 0.00 0.00 0.00 0.741402E+11 0.00 0.00
April 0.913687E+11 0.853578E+12 0.00 0.00 0.00 0.198127E+11 0.00 0.00
May 0.944143E+11 0.347644E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.913687E+11 0.574680E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.944143E+11 0.840727E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.944143E+11 0.107906E+13 0.00 0.00 0.00 1322862.92 0.00 0.00
September 0.913687E+11 0.340724E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.944143E+11 0.485368E+12 0.00 0.00 0.00 0.159260E+11 0.00 0.00
November 0.913687E+11 0.417925E+12 0.00 0.00 0.00 0.469212E+11 0.00 0.00
December 0.944143E+11 0.499357E+12 0.00 0.00 0.00 0.766274E+11 0.00 0.00
                 
Annual Sum or Average 0.111165E+13 0.598544E+13 0.00 0.00 0.00 0.337082E+12 0.00 0.00
Minimum of Months 0.852775E+11 0.382904E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.944143E+11 0.107906E+13 0.00 0.00 0.00 0.766274E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.138306E+10 0.500004E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124922E+10 0.945244E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138306E+10 0.156588E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133845E+10 0.204232E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138306E+10 0.642048E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133845E+10 0.112072E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138306E+10 0.166897E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138306E+10 0.217761E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133845E+10 0.625484E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138306E+10 0.113695E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133845E+10 0.154616E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138306E+10 0.207200E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.162844E+11 0.160434E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124922E+10 0.500004E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138306E+10 0.217761E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.131860E+11 0.351623E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119100E+11 0.804711E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.131860E+11 0.141251E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.127607E+11 0.192445E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.131860E+11 0.593120E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.127607E+11 0.106174E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.131860E+11 0.158805E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.131860E+11 0.206729E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.127607E+11 0.569287E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.131860E+11 0.105621E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.127607E+11 0.140840E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.131860E+11 0.187339E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155255E+12 0.147108E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119100E+11 0.351623E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131860E+11 0.206729E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.134485E+10 0.246367E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121470E+10 0.726646E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.134485E+10 0.135633E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.130146E+10 0.191377E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.134485E+10 0.610987E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130146E+10 0.108075E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.134485E+10 0.160785E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.134485E+10 0.208483E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.130146E+10 0.582362E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.134485E+10 0.105314E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.130146E+10 0.135610E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.134485E+10 0.178591E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.158345E+11 0.144050E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121470E+10 0.246367E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134485E+10 0.208483E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.345896E+10 91371410.27 0.389122E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.363917E+10 29683817.63 0.554933E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.454453E+10 13950351.28 0.694834E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.548427E+10 13748102.89 0.113392E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.553935E+10 0.00 0.142564E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.615410E+10 0.00 0.154722E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.665993E+10 0.00 0.168254E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.794075E+10 0.00 0.185142E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.529625E+10 0.00 0.143539E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.611159E+10 0.00 0.134782E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.512788E+10 58268.81 0.847191E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.473504E+10 52378516.45 0.633503E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.646918E+11 0.201190E+09 0.135435E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.345896E+10 0.00 0.389122E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.794075E+10 91371410.27 0.185142E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.256211E+11 0.166341E+11 0.308391E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.250590E+11 0.762112E+10 0.436165E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.294774E+11 0.674975E+10 0.518457E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.338811E+11 52089634.06 0.818957E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.476289E+11 0.00 0.129612E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.489041E+11 0.00 0.132443E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.477314E+11 0.00 0.137971E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.510673E+11 0.00 0.142465E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.432731E+11 0.00 0.128209E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.458851E+11 0.00 0.112227E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.324815E+11 0.390766E+09 0.643854E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.279184E+11 0.106460E+11 0.450324E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.458928E+12 0.420938E+11 0.110054E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.250590E+11 0.00 0.308391E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.510673E+11 0.166341E+11 0.142465E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.246492E+10 0.671123E+10 0.303282E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.247665E+10 0.394616E+10 0.440308E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.286172E+10 0.294476E+10 0.534965E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.341813E+10 50152165.55 0.866360E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.527734E+10 0.00 0.143674E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.554736E+10 0.00 0.149056E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.535312E+10 0.00 0.154574E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.564949E+10 0.00 0.157917E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453244E+10 0.00 0.138163E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.468393E+10 61384239.87 0.120021E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.295175E+10 0.501636E+09 0.626074E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.262336E+10 0.466501E+10 0.433980E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.478402E+11 0.188803E+11 0.118390E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.246492E+10 0.00 0.303282E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.564949E+10 0.671123E+10 0.157917E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.131757E+11 0.00 0.203163E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.113966E+11 0.00 0.237956E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.132440E+11 0.00 0.325190E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.121248E+11 0.00 0.512819E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132025E+11 0.00 0.953758E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130953E+11 0.00 0.100442E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129134E+11 0.00 0.109203E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145093E+11 0.00 0.121463E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135144E+11 0.00 0.103109E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138340E+11 80.37 0.887705E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132427E+11 261.28 0.489548E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.133320E+11 79.87 0.317500E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.157585E+12 421.52 0.826981E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.113966E+11 0.00 0.203163E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145093E+11 261.28 0.121463E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.944143E+11 0.00 0.501548E+11 0.00 0.118644E+11 0.00 0.00 0.00 0.482065E+11 0.00 0.00 0.00
February 0.852775E+11 0.00 0.185767E+12 0.00 0.383266E+11 0.00 0.00 0.00 0.559137E+11 0.00 0.00 0.00
March 0.944143E+11 0.00 0.453330E+12 0.00 0.926839E+11 0.00 0.00 0.00 0.744739E+11 0.00 0.00 0.00
April 0.913687E+11 0.00 0.107136E+13 0.00 0.217778E+12 0.00 0.00 0.00 0.199018E+11 0.00 0.00 0.00
May 0.944143E+11 0.00 0.448919E+12 0.00 0.101274E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.913687E+11 0.00 0.742908E+12 0.00 0.168227E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.944143E+11 0.00 0.108732E+13 0.00 0.246595E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.944143E+11 0.00 0.138515E+13 0.00 0.306089E+12 0.00 0.00 0.00 1328817.66 0.00 0.00 0.00
September 0.913687E+11 0.00 0.437947E+12 0.00 0.972231E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.944143E+11 0.00 0.621469E+12 0.00 0.136100E+12 0.00 0.00 0.00 0.159977E+11 0.00 0.00 0.00
November 0.913687E+11 0.00 0.526723E+12 0.00 0.108799E+12 0.00 0.00 0.00 0.471324E+11 0.00 0.00 0.00
December 0.944143E+11 0.00 0.624332E+12 0.00 0.124975E+12 0.00 0.00 0.00 0.769723E+11 0.00 0.00 0.00
                         
Annual Sum or Average 0.111165E+13 0.00 0.763537E+13 0.00 0.164994E+13 0.00 0.00 0.00 0.338600E+12 0.00 0.00 0.00
Minimum of Months 0.852775E+11 0.00 0.501548E+11 0.00 0.118644E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.944143E+11 0.00 0.138515E+13 0.00 0.306089E+12 0.00 0.00 0.00 0.769723E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.138306E+10 0.00 0.613328E+10 0.00 0.113324E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124922E+10 0.00 0.115155E+11 0.00 0.206303E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138306E+10 0.00 0.191021E+11 0.00 0.344335E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133845E+10 0.00 0.252959E+11 0.00 0.487265E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138306E+10 0.00 0.825580E+10 0.00 0.183532E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133845E+10 0.00 0.144267E+11 0.00 0.321944E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138306E+10 0.00 0.214984E+11 0.00 0.480878E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138306E+10 0.00 0.279458E+11 0.00 0.616973E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133845E+10 0.00 0.800491E+10 0.00 0.175008E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138306E+10 0.00 0.143618E+11 0.00 0.299231E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133845E+10 0.00 0.189464E+11 0.00 0.348474E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138306E+10 0.00 0.251396E+11 0.00 0.441960E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.162844E+11 0.00 0.200626E+12 0.00 0.401923E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124922E+10 0.00 0.613328E+10 0.00 0.113324E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138306E+10 0.00 0.279458E+11 0.00 0.616973E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.131860E+11 0.00 0.433494E+11 0.00 0.818706E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119100E+11 0.00 0.982632E+11 0.00 0.177921E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.131860E+11 0.00 0.172604E+12 0.00 0.313525E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.127607E+11 0.00 0.238511E+12 0.00 0.460661E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.131860E+11 0.00 0.763105E+11 0.00 0.169985E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.127607E+11 0.00 0.136700E+12 0.00 0.305255E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.131860E+11 0.00 0.204584E+12 0.00 0.457789E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.131860E+11 0.00 0.265369E+12 0.00 0.586400E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.127607E+11 0.00 0.729110E+11 0.00 0.159823E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.131860E+11 0.00 0.133549E+12 0.00 0.279284E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.127607E+11 0.00 0.172852E+12 0.00 0.320116E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.131860E+11 0.00 0.227716E+12 0.00 0.403770E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.155255E+12 0.00 0.184272E+13 0.00 0.371640E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119100E+11 0.00 0.433494E+11 0.00 0.818706E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131860E+11 0.00 0.265369E+12 0.00 0.586400E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.134485E+10 0.00 0.305367E+10 0.00 0.589996E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121470E+10 0.00 0.889310E+10 0.00 0.162665E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.134485E+10 0.00 0.166033E+11 0.00 0.304002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.130146E+10 0.00 0.237410E+11 0.00 0.460336E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.134485E+10 0.00 0.786214E+10 0.00 0.175227E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130146E+10 0.00 0.139173E+11 0.00 0.310972E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.134485E+10 0.00 0.207190E+11 0.00 0.464053E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.134485E+10 0.00 0.267749E+11 0.00 0.592667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.130146E+10 0.00 0.746126E+10 0.00 0.163764E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.134485E+10 0.00 0.133302E+11 0.00 0.279878E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.130146E+10 0.00 0.166732E+11 0.00 0.311217E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.134485E+10 0.00 0.217536E+11 0.00 0.389457E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.158345E+11 0.00 0.180783E+12 0.00 0.367324E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121470E+10 0.00 0.305367E+10 0.00 0.589996E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134485E+10 0.00 0.267749E+11 0.00 0.592667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.278126E+09 0.138008E+10 0.00 0.103891E+09 0.00 0.00 0.504310E+11 0.00 0.87
February 0.207358E+09 0.137261E+10 0.00 81118419.90 4333917.25 0.00 0.383351E+11 0.00 0.97
March 0.119261E+09 0.293867E+10 0.00 88541877.73 5579004.37 0.00 0.411031E+11 0.00 0.97
April 0.136435E+09 0.509566E+10 0.00 59864775.18 72116959.85 0.00 0.187607E+11 0.00 0.87
May 0.00 0.250156E+11 0.00 1252492.73 0.144868E+09 0.00 6257107.62 0.00 0.33
June 2642122.16 0.304291E+11 0.00 2063613.49 0.207405E+09 0.00 88282348.33 0.00 0.35
July 0.00 0.374439E+11 0.00 0.00 0.401138E+09 0.00 0.00 0.00 0.31
August 0.00 0.382943E+11 0.00 243525.09 0.229350E+09 0.00 23024107.59 0.00 0.35
September 38932.55 0.285555E+11 0.00 1540556.53 0.289238E+09 0.00 0.103184E+09 0.00 0.34
October 92194253.89 0.215812E+11 0.00 38164411.92 0.229906E+09 0.00 0.110898E+11 0.00 0.63
November 0.198188E+09 0.636098E+10 0.00 92150712.80 7684014.13 0.00 0.330678E+11 0.00 1.02
December 0.303146E+09 0.397671E+10 0.00 98106306.57 11548314.92 0.00 0.456600E+11 0.00 0.87
                   
Annual Sum or Average 0.133739E+10 0.202444E+12 0.00 0.566938E+09 0.160317E+10 0.00 0.238668E+12 0.00 0.65
Minimum of Months 0.00 0.137261E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.303146E+09 0.382943E+11 0.00 0.103891E+09 0.401138E+09 0.00 0.504310E+11 0.00 1.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.331334E+10 0.216799E+10 0.00 52980958.94 0.00 0.00 0.274935E+11 0.00 0.48
February 0.218286E+10 0.251918E+10 0.00 45041773.99 38453681.61 0.00 0.174113E+11 0.00 0.48
March 0.188129E+10 0.391879E+10 0.00 64028606.53 84251367.34 0.00 0.240264E+11 0.00 0.54
April 0.252364E+10 0.628254E+10 0.00 34363966.95 81447912.09 0.00 0.681554E+10 0.00 0.48
May 0.00 0.133330E+11 0.00 0.00 0.143634E+09 0.00 0.00 0.00 0.26
June 0.00 0.137733E+11 0.00 0.00 0.147551E+09 0.00 0.00 0.00 0.27
July 0.00 0.158082E+11 0.00 0.00 0.253020E+09 0.00 0.00 0.00 0.24
August 3729338.07 0.165282E+11 0.00 0.00 0.160481E+09 0.00 0.00 0.00 0.27
September 0.00 0.162519E+11 0.00 0.00 0.284737E+09 0.00 0.00 0.00 0.26
October 0.428058E+09 0.105745E+11 0.00 20475087.33 0.176487E+09 0.00 0.544054E+10 0.00 0.35
November 0.235766E+10 0.506368E+10 0.00 59715223.67 48495853.95 0.00 0.167325E+11 0.00 0.55
December 0.264316E+10 0.433178E+10 0.00 67742139.85 79244220.45 0.00 0.280454E+11 0.00 0.53
                   
Annual Sum or Average 0.153337E+11 0.110553E+12 0.00 0.344348E+09 0.149781E+10 0.00 0.125965E+12 0.00 0.39
Minimum of Months 0.00 0.216799E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Maximum of Months 0.331334E+10 0.165282E+11 0.00 67742139.85 0.284737E+09 0.00 0.280454E+11 0.00 0.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.137501E+12 0.147353E+11 0.00 0.145599E+09 0.649543E+10 0.00 0.972734E+11 0.00 0.38
February 0.797423E+11 0.193492E+11 0.00 0.140188E+09 0.558424E+10 0.00 0.599281E+11 0.00 0.39
March 0.760434E+11 0.277415E+11 0.00 0.246102E+09 0.954273E+10 0.00 0.108057E+12 0.00 0.43
April 0.190404E+11 0.530366E+11 0.00 0.171810E+09 0.946925E+10 0.00 0.374336E+11 0.00 0.38
May 0.00 0.124413E+12 0.00 0.00 0.768651E+10 0.00 0.00 0.00 0.26
June 0.00 0.130463E+12 0.00 682600.71 0.721449E+10 0.00 0.00 0.00 0.27
July 0.00 0.147184E+12 0.00 0.00 0.119656E+11 0.00 0.00 0.00 0.25
August 0.00 0.155375E+12 0.00 0.00 0.725555E+10 0.00 0.00 0.00 0.27
September 0.00 0.147422E+12 0.00 0.00 0.132138E+11 0.00 0.00 0.00 0.26
October 0.103345E+11 0.962385E+11 0.00 0.114403E+09 0.810907E+10 0.00 0.358751E+11 0.00 0.32
November 0.523581E+11 0.420105E+11 0.00 0.258350E+09 0.510974E+10 0.00 0.753669E+11 0.00 0.41
December 0.104229E+12 0.351821E+11 0.00 0.184422E+09 0.702190E+10 0.00 0.903655E+11 0.00 0.38
                   
Annual Sum or Average 0.479250E+12 0.993150E+12 0.00 0.126156E+10 0.986683E+11 0.00 0.504299E+12 0.00 0.33
Minimum of Months 0.00 0.147353E+11 0.00 0.00 0.510974E+10 0.00 0.00 0.00 0.25
Maximum of Months 0.137501E+12 0.155375E+12 0.00 0.258350E+09 0.132138E+11 0.00 0.108057E+12 0.00 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.179900E+11 0.148530E+10 0.00 3340849.49 0.851250E+09 0.227116E+09 0.205106E+10 0.00 0.38
February 0.101349E+11 0.194358E+10 0.00 4617685.32 0.807287E+09 0.156524E+09 0.221711E+10 0.00 0.37
March 0.112458E+11 0.303327E+10 0.00 9440020.08 0.984611E+09 64703123.29 0.477005E+10 0.00 0.41
April 0.243013E+10 0.552244E+10 0.00 12106834.66 0.765952E+09 0.00 0.279083E+10 0.00 0.36
May 0.00 0.126251E+11 0.00 0.00 0.288498E+09 0.00 0.00 0.00 0.26
June 0.00 0.133054E+11 0.00 0.00 0.143713E+09 0.00 0.00 0.00 0.27
July 0.00 0.153909E+11 0.00 0.00 0.382464E+09 0.00 0.00 0.00 0.25
August 0.00 0.157726E+11 0.00 0.00 0.235273E+09 0.00 0.00 0.00 0.27
September 0.00 0.151516E+11 0.00 0.00 0.687665E+09 0.00 0.00 0.00 0.26
October 0.139828E+10 0.971577E+10 0.00 8236588.95 0.430486E+09 0.00 0.253266E+10 0.00 0.31
November 0.708161E+10 0.370565E+10 0.00 11009898.82 0.107846E+10 0.00 0.400638E+10 0.00 0.40
December 0.152414E+11 0.282634E+10 0.00 2245379.83 0.134608E+10 0.112736E+09 0.119773E+10 0.00 0.37
                   
Annual Sum or Average 0.655221E+11 0.100478E+12 0.00 50997257.15 0.800174E+10 0.561079E+09 0.195658E+11 0.00 0.33
Minimum of Months 0.00 0.148530E+10 0.00 0.00 0.143713E+09 0.00 0.00 0.00 0.25
Maximum of Months 0.179900E+11 0.157726E+11 0.00 12106834.66 0.134608E+10 0.227116E+09 0.477005E+10 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.259137E+10 0.273348E+09 0.00 898726.95 8358989.42 0.00 0.554289E+09 0.00 0.40
February 0.142030E+10 0.334583E+09 0.00 1615962.84 6661036.36 0.00 0.600002E+09 0.00 0.42
March 0.140439E+10 0.576949E+09 0.00 3149689.26 10886070.15 0.00 0.120754E+10 0.00 0.49
April 0.510685E+09 0.100051E+10 0.00 2717736.89 10598477.31 0.00 0.530702E+09 0.00 0.52
May 0.00 0.257785E+10 0.00 0.00 18025213.15 0.00 0.00 0.00 0.41
June 0.00 0.294916E+10 0.00 0.00 18516742.35 0.00 0.00 0.00 0.45
July 0.00 0.332161E+10 0.00 0.00 31752453.57 0.00 0.00 0.00 0.41
August 468008.25 0.319692E+10 0.00 0.00 20139408.99 0.00 0.00 0.00 0.41
September 0.00 0.280441E+10 0.00 0.00 35732743.60 0.00 0.00 0.00 0.37
October 0.219285E+09 0.183201E+10 0.00 1556762.49 22147996.51 0.00 0.436409E+09 0.00 0.42
November 0.967399E+09 0.708396E+09 0.00 3447661.56 6085921.79 0.00 0.977262E+09 0.00 0.49
December 0.193304E+10 0.566110E+09 0.00 2068654.26 11618608.16 0.00 0.914036E+09 0.00 0.43
                   
Annual Sum or Average 0.904693E+10 0.201419E+11 0.00 15455194.26 0.200524E+09 0.00 0.522024E+10 0.00 0.44
Minimum of Months 0.00 0.273348E+09 0.00 0.00 6085921.79 0.00 0.00 0.00 0.37
Maximum of Months 0.259137E+10 0.332161E+10 0.00 3447661.56 35732743.60 0.00 0.120754E+10 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109146E+10 0.202576E+09 0.00 2901371.30 9986497.59 167798.55 0.137815E+10 0.00 0.49
February 0.690589E+09 0.273294E+09 0.00 2667517.13 4177037.53 0.00 0.957263E+09 0.00 0.53
March 0.777800E+09 0.463976E+09 0.00 4005343.35 11044352.45 0.00 0.144501E+10 0.00 0.66
April 0.311370E+09 0.810340E+09 0.00 2897401.94 12524015.42 0.00 0.675704E+09 0.00 0.68
May 0.00 0.213448E+10 0.00 0.00 11609419.40 0.00 0.00 0.00 0.53
June 0.00 0.231510E+10 0.00 0.00 11925996.43 0.00 0.00 0.00 0.55
July 0.00 0.255833E+10 0.00 0.00 20450662.48 0.00 0.00 0.00 0.48
August 301428.01 0.230211E+10 0.00 0.00 12971100.17 0.00 0.00 0.00 0.47
September 0.00 0.216745E+10 0.00 0.00 23014230.30 0.00 0.00 0.00 0.44
October 0.131883E+09 0.145399E+10 0.00 1637861.72 14264762.25 0.00 0.388942E+09 0.00 0.51
November 0.538460E+09 0.520143E+09 0.00 3727987.90 8361842.89 0.00 0.109418E+10 0.00 0.61
December 0.118915E+10 0.355254E+09 0.00 2483849.95 19001967.47 165843.42 0.962970E+09 0.00 0.50
                   
Annual Sum or Average 0.473101E+10 0.155570E+11 0.00 20321333.29 0.159332E+09 333641.97 0.690222E+10 0.00 0.54
Minimum of Months 0.00 0.202576E+09 0.00 0.00 4177037.53 0.00 0.00 0.00 0.44
Maximum of Months 0.118915E+10 0.255833E+10 0.00 4005343.35 23014230.30 167798.55 0.144501E+10 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.132387E+10 0.449024E+09 0.00 11729126.08 4555675.48 251591.26 0.486124E+10 0.00 0.83
February 0.855198E+09 0.670817E+09 0.00 7434530.75 4808523.95 359245.62 0.266733E+10 0.00 0.77
March 0.123240E+10 0.794037E+09 0.00 6602279.80 11340093.87 0.00 0.230513E+10 0.00 0.72
April 0.516548E+09 0.118498E+10 0.00 3329160.85 10645534.55 0.00 0.637030E+09 0.00 0.62
May 0.00 0.259674E+10 0.00 0.00 18064677.17 0.00 0.00 0.00 0.42
June 0.00 0.281197E+10 0.00 0.00 18557282.51 0.00 0.00 0.00 0.43
July 0.00 0.327109E+10 0.00 0.00 31821971.72 0.00 0.00 0.00 0.40
August 469032.90 0.347900E+10 0.00 0.00 20183501.78 0.00 0.00 0.00 0.45
September 0.00 0.344450E+10 0.00 0.00 35810976.11 0.00 0.00 0.00 0.46
October 0.165058E+09 0.272666E+10 0.00 3382213.02 18837691.38 0.00 0.755477E+09 0.00 0.65
November 0.493676E+09 0.116971E+10 0.00 13565523.80 6099246.18 0.00 0.317088E+10 0.00 0.96
December 0.115696E+10 0.942643E+09 0.00 12926278.40 9966419.17 0.00 0.416339E+10 0.00 0.89
                   
Annual Sum or Average 0.574418E+10 0.235412E+11 0.00 58969112.69 0.190692E+09 610836.88 0.185605E+11 0.00 0.63
Minimum of Months 0.00 0.449024E+09 0.00 0.00 4555675.48 0.00 0.00 0.00 0.40
Maximum of Months 0.132387E+10 0.347900E+10 0.00 13565523.80 35810976.11 359245.62 0.486124E+10 0.00 0.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.837195E+09 0.331406E+09 0.00 4888699.22 0.00 0.00 0.221541E+10 0.00 0.67
February 0.289817E+09 0.470666E+09 0.00 5841487.51 1203395.71 0.00 0.197069E+10 0.00 0.82
March 0.164371E+09 0.764935E+09 0.00 9465192.95 1779770.77 0.00 0.329612E+10 0.00 1.08
April 0.107404E+09 0.152915E+10 0.00 8389677.34 1144500.00 0.00 0.131518E+10 0.00 1.18
May 0.00 0.257561E+10 0.00 0.00 7023051.86 0.00 0.00 0.00 0.64
June 0.00 0.309564E+10 0.00 0.00 2440331.05 0.00 0.00 0.00 0.75
July 0.00 0.369633E+10 0.00 0.00 2859992.97 0.00 0.00 0.00 0.70
August 138373.11 0.404983E+10 0.00 6923.56 2326074.78 0.00 196662.74 0.00 0.81
September 0.00 0.294449E+10 0.00 0.00 10809607.16 0.00 0.00 0.00 0.59
October 32861360.64 0.212948E+10 0.00 2974651.93 10545376.39 0.00 0.733147E+09 0.00 0.77
November 0.160390E+09 0.948527E+09 0.00 9455550.95 282855.07 0.00 0.236922E+10 0.00 1.05
December 0.178585E+09 0.845958E+09 0.00 10092701.48 2983944.23 0.00 0.370696E+10 0.00 1.01
                   
Annual Sum or Average 0.177076E+10 0.233820E+11 0.00 51114884.94 43398899.99 0.00 0.156069E+11 0.00 0.84
Minimum of Months 0.00 0.331406E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
Maximum of Months 0.837195E+09 0.404983E+10 0.00 10092701.48 10809607.16 0.00 0.370696E+10 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.235917E+11 0.145505E+10 0.00 182325.36 0.125237E+10 0.500413E+10 65513268.39 0.00 0.38
February 0.144055E+11 0.209719E+10 0.00 1177972.75 0.110473E+10 0.188935E+10 0.752006E+09 0.00 0.38
March 0.181449E+11 0.401967E+10 0.00 4330635.37 0.111058E+10 0.180990E+10 0.155103E+10 0.00 0.41
April 0.466391E+10 0.838371E+10 0.00 11683973.27 0.100498E+10 0.00 0.193699E+10 0.00 0.41
May 0.00 0.254728E+11 0.00 0.00 0.180602E+09 0.00 0.00 0.00 0.42
June 28332.72 0.298852E+11 0.00 0.00 0.229031E+09 0.00 0.00 0.00 0.47
July 0.00 0.343453E+11 0.00 0.00 0.322854E+09 0.00 0.00 0.00 0.43
August 0.00 0.325498E+11 0.00 0.00 0.205161E+09 0.00 0.00 0.00 0.44
September 0.00 0.269374E+11 0.00 0.00 0.583964E+09 0.00 0.00 0.00 0.37
October 0.310856E+10 0.173391E+11 0.00 8142858.70 0.530967E+09 0.00 0.225402E+10 0.00 0.38
November 0.128394E+11 0.530238E+10 0.00 7857387.58 0.110876E+10 11065106.97 0.195245E+10 0.00 0.40
December 0.205229E+11 0.358899E+10 0.00 656236.77 0.178484E+10 0.288376E+10 0.173179E+09 0.00 0.36
                   
Annual Sum or Average 0.972770E+11 0.191377E+12 0.00 34031389.80 0.941883E+10 0.115982E+11 0.868519E+10 0.00 0.41
Minimum of Months 0.00 0.145505E+10 0.00 0.00 0.180602E+09 0.00 0.00 0.00 0.36
Maximum of Months 0.235917E+11 0.343453E+11 0.00 11683973.27 0.178484E+10 0.500413E+10 0.225402E+10 0.00 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100719E+11 0.154979E+10 0.00 9179005.97 0.485234E+09 0.184472E+10 0.500500E+10 0.00 0.35
February 0.611949E+10 0.259262E+10 0.00 12151584.05 0.271797E+09 0.617565E+09 0.409768E+10 0.00 0.42
March 0.709667E+10 0.456010E+10 0.00 24296567.76 0.318391E+09 0.713317E+09 0.805574E+10 0.00 0.55
April 0.187361E+10 0.891095E+10 0.00 23744084.14 0.211711E+09 0.00 0.545174E+10 0.00 0.63
May 0.00 0.224972E+11 0.00 0.00 0.116375E+09 0.00 0.00 0.00 0.57
June 18256.88 0.254226E+11 0.00 0.00 0.131514E+09 0.00 0.00 0.00 0.62
July 0.00 0.294115E+11 0.00 0.00 0.208039E+09 0.00 0.00 0.00 0.57
August 0.00 0.272647E+11 0.00 0.00 0.132200E+09 0.00 0.00 0.00 0.57
September 0.00 0.222391E+11 0.00 0.00 0.258391E+09 0.00 0.00 0.00 0.47
October 0.145917E+10 0.153799E+11 0.00 12174539.02 0.229297E+09 0.00 0.272782E+10 0.00 0.51
November 0.537437E+10 0.499698E+10 0.00 22178265.73 0.388396E+09 0.00 0.598278E+10 0.00 0.49
December 0.946793E+10 0.311199E+10 0.00 9763215.18 0.626211E+09 0.126523E+10 0.333569E+10 0.00 0.36
                   
Annual Sum or Average 0.414632E+11 0.167938E+12 0.00 0.113487E+09 0.337756E+10 0.444084E+10 0.346565E+11 0.00 0.51
Minimum of Months 0.00 0.154979E+10 0.00 0.00 0.116375E+09 0.00 0.00 0.00 0.35
Maximum of Months 0.100719E+11 0.294115E+11 0.00 24296567.76 0.626211E+09 0.184472E+10 0.805574E+10 0.00 0.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.122103E+11 0.474108E+10 0.00 0.103764E+09 0.329958E+09 0.120977E+10 0.411711E+11 0.00 0.78
February 0.805554E+10 0.764586E+10 0.00 62115239.28 0.107812E+09 0.443262E+09 0.206179E+11 0.00 0.74
March 0.127657E+11 0.741049E+10 0.00 47853416.54 0.463322E+09 0.909282E+09 0.154812E+11 0.00 0.65
April 0.386745E+10 0.112101E+11 0.00 23835099.22 0.564864E+09 0.00 0.416930E+10 0.00 0.53
May 0.00 0.258952E+11 0.00 0.00 0.180218E+09 0.00 0.00 0.00 0.43
June 28272.48 0.283038E+11 0.00 0.00 0.228545E+09 0.00 0.00 0.00 0.45
July 0.00 0.338797E+11 0.00 0.00 0.322168E+09 0.00 0.00 0.00 0.43
August 0.00 0.366419E+11 0.00 0.00 0.204725E+09 0.00 0.00 0.00 0.50
September 0.00 0.352448E+11 0.00 0.00 0.434337E+09 0.00 0.00 0.00 0.49
October 0.204512E+10 0.290165E+11 0.00 27365934.12 0.186953E+09 0.00 0.584306E+10 0.00 0.67
November 0.512787E+10 0.121184E+11 0.00 0.127277E+09 0.206472E+09 0.00 0.247988E+11 0.00 0.87
December 0.116062E+11 0.989876E+10 0.00 0.108691E+09 0.372990E+09 0.906985E+09 0.295985E+11 0.00 0.78
                   
Annual Sum or Average 0.556783E+11 0.242007E+12 0.00 0.500902E+09 0.360236E+10 0.346930E+10 0.141680E+12 0.00 0.61
Minimum of Months 0.00 0.474108E+10 0.00 0.00 0.107812E+09 0.00 0.00 0.00 0.43
Maximum of Months 0.127657E+11 0.366419E+11 0.00 0.127277E+09 0.564864E+09 0.120977E+10 0.411711E+11 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128243E+11 0.252833E+10 0.00 14609541.38 0.185623E+09 0.139306E+10 0.717104E+10 0.00 0.47
February 0.758853E+10 0.356455E+10 0.00 14878979.79 0.137325E+09 0.413856E+09 0.520316E+10 0.00 0.52
March 0.910817E+10 0.471605E+10 0.00 26102083.25 0.137197E+09 0.355225E+09 0.890036E+10 0.00 0.62
April 0.167046E+10 0.104064E+11 0.00 31507661.14 0.109145E+09 0.00 0.448127E+10 0.00 0.70
May 0.00 0.223877E+11 0.00 0.00 76840449.15 0.00 0.00 0.00 0.58
June 0.00 0.259989E+11 0.00 33484.26 37833236.90 0.00 0.00 0.00 0.65
July 0.00 0.298653E+11 0.00 0.00 64456788.75 0.00 0.00 0.00 0.58
August 0.00 0.305120E+11 0.00 0.00 63120763.01 0.00 0.00 0.00 0.64
September 0.00 0.247663E+11 0.00 0.00 0.127673E+09 0.00 0.00 0.00 0.52
October 0.144049E+10 0.169485E+11 0.00 12702806.34 0.105453E+09 0.00 0.303233E+10 0.00 0.58
November 0.606305E+10 0.615642E+10 0.00 25938581.53 25475545.41 0.00 0.577575E+10 0.00 0.55
December 0.121870E+11 0.497817E+10 0.00 14483236.76 0.207484E+09 0.612102E+09 0.411763E+10 0.00 0.47
                   
Annual Sum or Average 0.508820E+11 0.182829E+12 0.00 0.140256E+09 0.127763E+10 0.277425E+10 0.386815E+11 0.00 0.58
Minimum of Months 0.00 0.252833E+10 0.00 0.00 25475545.41 0.00 0.00 0.00 0.47
Maximum of Months 0.128243E+11 0.305120E+11 0.00 31507661.14 0.207484E+09 0.139306E+10 0.890036E+10 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.153755E+10 0.154571E+09 0.00 14144.00 0.149562E+09 0.106695E+10 3964973.90 0.00 0.38
February 0.100488E+10 0.216688E+09 0.00 66961.59 0.142692E+09 0.532342E+09 53780070.92 0.00 0.38
March 0.150547E+10 0.430018E+09 0.00 354585.64 0.127489E+09 0.372410E+09 0.124478E+09 0.00 0.42
April 0.432691E+09 0.826354E+09 0.00 1148382.84 0.127639E+09 2161696.90 0.218746E+09 0.00 0.41
May 0.00 0.247817E+10 0.00 0.00 18252978.29 0.00 0.00 0.00 0.41
June 0.00 0.288789E+10 0.00 0.00 22752665.71 0.00 0.00 0.00 0.46
July 0.00 0.336211E+10 0.00 0.00 37057661.83 0.00 0.00 0.00 0.42
August 0.00 0.317042E+10 0.00 0.00 35427720.29 0.00 0.00 0.00 0.43
September 0.00 0.261191E+10 0.00 0.00 0.117036E+09 0.00 0.00 0.00 0.37
October 0.277465E+09 0.167405E+10 0.00 712592.86 65974312.69 17422206.79 0.186321E+09 0.00 0.38
November 0.110200E+10 0.490681E+09 1342361.91 481211.49 0.156994E+09 0.106911E+09 0.157462E+09 8857.44 0.40
December 0.135374E+10 0.322810E+09 591530.72 28807.49 0.215471E+09 0.754235E+09 13655102.29 9217.47 0.37
                   
Annual Sum or Average 0.721380E+10 0.186257E+11 1933892.62 2806685.91 0.121635E+10 0.285243E+10 0.758407E+09 18074.92 0.40
Minimum of Months 0.00 0.154571E+09 0.00 0.00 18252978.29 0.00 0.00 0.00 0.37
Maximum of Months 0.153755E+10 0.336211E+10 1342361.91 1148382.84 0.215471E+09 0.106695E+10 0.218746E+09 9217.47 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.119616E+10 0.190089E+09 0.00 172595.22 59922983.09 0.358785E+09 0.126588E+09 0.00 0.40
February 0.649737E+09 0.291959E+09 0.00 742030.16 46961940.67 0.168912E+09 0.247971E+09 0.00 0.45
March 0.687687E+09 0.527179E+09 0.00 2019143.94 39228308.66 0.185962E+09 0.659601E+09 0.00 0.57
April 0.168276E+09 0.929583E+09 0.00 2358565.93 37892794.65 0.00 0.566381E+09 0.00 0.65
May 0.00 0.224102E+10 0.00 0.00 11763518.50 0.00 0.00 0.00 0.58
June 0.00 0.252128E+10 0.00 0.00 13807433.57 0.00 0.00 0.00 0.63
July 0.00 0.296996E+10 0.00 0.00 22729461.77 0.00 0.00 0.00 0.58
August 0.00 0.274266E+10 0.00 0.00 21826044.01 0.00 0.00 0.00 0.58
September 0.00 0.228575E+10 0.00 0.00 36820698.05 0.00 0.00 0.00 0.49
October 0.127283E+09 0.155572E+10 0.00 1118120.36 27102554.13 10277485.00 0.248576E+09 0.00 0.53
November 0.516561E+09 0.513037E+09 182923.76 1631297.36 62394386.56 27320161.93 0.471045E+09 315.02 0.50
December 0.938546E+09 0.309188E+09 0.00 441992.57 95393552.20 0.320760E+09 0.134702E+09 0.00 0.40
                   
Annual Sum or Average 0.428425E+10 0.170774E+11 182923.76 8483745.54 0.475844E+09 0.107202E+10 0.245486E+10 315.02 0.53
Minimum of Months 0.00 0.190089E+09 0.00 0.00 11763518.50 0.00 0.00 0.00 0.40
Maximum of Months 0.119616E+10 0.296996E+10 182923.76 2358565.93 95393552.20 0.358785E+09 0.659601E+09 315.02 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.996061E+09 0.544124E+09 0.00 7738205.63 46641890.92 0.344881E+09 0.305832E+10 0.00 0.70
February 0.669993E+09 0.813559E+09 0.00 4689733.92 30406313.51 0.172889E+09 0.167909E+10 0.00 0.68
March 0.104076E+10 0.796372E+09 0.00 4077950.64 64618107.88 0.271938E+09 0.140889E+10 0.00 0.62
April 0.347045E+09 0.108484E+10 0.00 2381962.46 93035525.34 0.00 0.476908E+09 0.00 0.53
May 0.00 0.251511E+10 0.00 0.00 18238287.29 0.00 0.00 0.00 0.42
June 0.00 0.273493E+10 0.00 0.00 29099348.46 0.00 0.00 0.00 0.44
July 0.00 0.330518E+10 0.00 0.00 45044352.46 0.00 0.00 0.00 0.42
August 0.00 0.353296E+10 0.00 0.00 35399206.10 0.00 0.00 0.00 0.49
September 0.00 0.342696E+10 0.00 0.00 65916373.75 0.00 0.00 0.00 0.47
October 0.190556E+09 0.276902E+10 0.00 2503799.77 22050890.35 0.00 0.530579E+09 0.00 0.65
November 0.489406E+09 0.118009E+10 0.00 10174716.22 51838491.54 16434506.10 0.230077E+10 0.00 0.86
December 0.917867E+09 0.928839E+09 0.00 8480335.35 76394728.36 0.298894E+09 0.232122E+10 0.00 0.75
                   
Annual Sum or Average 0.465169E+10 0.236320E+11 0.00 40046704.00 0.578684E+09 0.110504E+10 0.117758E+11 0.00 0.59
Minimum of Months 0.00 0.544124E+09 0.00 0.00 18238287.29 0.00 0.00 0.00 0.42
Maximum of Months 0.104076E+10 0.353296E+10 0.00 10174716.22 93035525.34 0.344881E+09 0.305832E+10 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100554E+10 0.273799E+09 0.00 1040683.67 34315827.22 0.331407E+09 0.516062E+09 0.00 0.46
February 0.591595E+09 0.370816E+09 0.00 1170872.37 34917261.45 0.152684E+09 0.457965E+09 0.00 0.51
March 0.761131E+09 0.491105E+09 0.00 2361452.46 33637266.58 0.130951E+09 0.865984E+09 0.00 0.61
April 0.165529E+09 0.101819E+10 0.00 3008673.62 22724898.79 0.00 0.489493E+09 0.00 0.68
May 0.00 0.212953E+10 0.00 0.00 6858173.53 0.00 0.00 0.00 0.56
June 0.00 0.244624E+10 0.00 0.00 4575514.16 0.00 0.00 0.00 0.62
July 0.00 0.286784E+10 0.00 0.00 5615519.24 0.00 0.00 0.00 0.55
August 0.00 0.291915E+10 0.00 0.00 7571380.27 0.00 0.00 0.00 0.62
September 0.00 0.241502E+10 0.00 0.00 15110996.33 0.00 0.00 0.00 0.51
October 0.134346E+09 0.161472E+10 0.00 1162426.75 13194995.20 0.00 0.277117E+09 0.00 0.57
November 0.555527E+09 0.588459E+09 0.00 2091253.94 26015229.81 21424928.14 0.575954E+09 0.00 0.57
December 0.920806E+09 0.463170E+09 232662.58 1124364.99 46087970.14 0.227516E+09 0.369356E+09 802.74 0.48
                   
Annual Sum or Average 0.413447E+10 0.175980E+11 232662.58 11959727.81 0.250625E+09 0.863984E+09 0.355193E+10 802.74 0.56
Minimum of Months 0.00 0.273799E+09 0.00 0.00 4575514.16 0.00 0.00 0.00 0.46
Maximum of Months 0.100554E+10 0.291915E+10 232662.58 3008673.62 46087970.14 0.331407E+09 0.865984E+09 802.74 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 30983105.82 0.00 2869269.68 0.00 0.00 0.326060E+09 0.00 0.28
February 0.00 48505141.51 0.00 4874561.50 0.00 0.00 0.174295E+09 0.00 0.29
March 0.00 83354432.08 0.00 9328562.03 0.00 0.00 0.218732E+09 0.00 0.31
April 0.00 0.159563E+09 0.00 5193842.58 0.00 0.00 49767031.09 0.00 0.29
May 0.00 0.419999E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.518933E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.601516E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.606859E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.425161E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.348101E+09 0.00 1650267.42 0.00 0.00 44681357.65 0.00 0.28
November 0.00 0.123863E+09 0.00 7382482.06 0.00 0.00 0.123885E+09 0.00 0.28
December 0.00 90559953.86 0.00 12252749.18 0.00 0.00 0.238931E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.345740E+10 0.00 43551734.44 0.00 0.00 0.117635E+10 0.00 0.29
Minimum of Months 0.00 30983105.82 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.606859E+09 0.00 12252749.18 0.00 0.00 0.326060E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.288631E+09 0.00 18552228.89 0.00 0.00 0.327919E+10 0.00 0.28
February 0.00 0.476778E+09 0.00 41124985.93 0.00 0.00 0.175270E+10 0.00 0.29
March 0.00 0.830614E+09 0.00 83588511.04 0.00 0.00 0.219364E+10 0.00 0.31
April 0.00 0.159687E+10 0.00 48723371.65 0.00 0.00 0.498911E+09 0.00 0.29
May 0.00 0.415389E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.517159E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.600650E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.607670E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.418905E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.346453E+10 0.00 14916666.35 0.00 0.00 0.447485E+09 0.00 0.28
November 0.00 0.123538E+10 0.00 67063013.88 0.00 0.00 0.124311E+10 0.00 0.28
December 0.00 0.905075E+09 0.00 0.110203E+09 0.00 0.00 0.239662E+10 0.00 0.28
                   
Annual Sum or Average 0.00 0.343956E+11 0.00 0.384171E+09 0.00 0.00 0.118117E+11 0.00 0.29
Minimum of Months 0.00 0.288631E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.607670E+10 0.00 0.110203E+09 0.00 0.00 0.327919E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 73918065.87 28487667.51 0.00 1117397.74 0.00 0.00 0.254753E+09 0.00 0.28
February 0.00 47402806.33 0.00 3658636.20 0.00 0.00 0.176330E+09 0.00 0.29
March 0.00 82907161.24 0.00 7886856.72 0.00 0.00 0.220185E+09 0.00 0.31
April 0.00 0.159463E+09 0.00 4798667.41 0.00 0.00 50091015.71 0.00 0.29
May 0.00 0.417541E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.517788E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.600669E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.609521E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.420576E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.346570E+09 0.00 1416678.57 0.00 0.00 44920194.79 0.00 0.28
November 0.00 0.123306E+09 0.00 6378102.41 0.00 0.00 0.124962E+09 0.00 0.28
December 0.00 90281077.89 0.00 10343956.78 0.00 0.00 0.240682E+09 0.00 0.28
                   
Annual Sum or Average 73918065.87 0.344451E+10 0.00 35600295.83 0.00 0.00 0.111192E+10 0.00 0.29
Minimum of Months 0.00 28487667.51 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 73918065.87 0.609521E+09 0.00 10343956.78 0.00 0.00 0.254753E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.423039E+09 0.00 0.522740E+09 0.00 0.00 0.345920E+12 0.00 15.61
February 0.00 0.885337E+09 0.00 0.740973E+09 0.00 0.00 0.431602E+12 0.00 21.44
March 0.00 0.177769E+10 0.00 0.109099E+10 0.00 0.00 0.538634E+12 0.00 25.12
April 0.00 0.308551E+10 0.00 0.108268E+10 0.00 0.00 0.201126E+12 0.00 17.33
May 0.00 0.994340E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.33
June 0.00 0.116470E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.34
July 0.00 0.132558E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.31
August 0.00 0.112746E+11 0.00 4024830.50 0.00 0.00 77861455.53 0.00 0.40
September 0.00 0.101565E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.33
October 0.00 0.779559E+10 0.00 0.267179E+09 0.00 0.00 0.123253E+12 0.00 8.36
November 0.00 0.270032E+10 0.00 0.114000E+10 0.00 0.00 0.432973E+12 0.00 25.18
December 0.00 0.182445E+10 0.00 0.171273E+10 0.00 0.00 0.650157E+12 0.00 27.11
                   
Annual Sum or Average 0.00 0.747693E+11 0.00 0.656131E+10 0.00 0.00 0.272374E+13 0.00 11.75
Minimum of Months 0.00 0.423039E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.00 0.132558E+11 0.00 0.171273E+10 0.00 0.00 0.650157E+12 0.00 27.11



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:56:55

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.400076E+12 0.939272E+10 0.00 0.178873E+13 0.644120E+12
February 0.430415E+12 0.722136E+10 0.00 0.143866E+13 0.105544E+13
March 0.494733E+12 0.641207E+10 0.00 0.161315E+13 0.159003E+13
April 0.554660E+12 -382918631.3 0.00 0.560390E+12 0.282085E+13
May 0.553913E+12 -0.134217E+11 0.00 -0.688243E+12 0.281283E+13
June 0.551801E+12 -0.108468E+11 0.00 -0.800599E+12 0.324665E+13
July 0.570055E+12 -0.183162E+11 0.00 -0.904147E+12 0.380245E+13
August 0.525011E+12 -0.175923E+11 0.00 -0.893690E+12 0.427833E+13
September 0.452611E+12 -0.168134E+11 0.00 -0.698747E+12 0.278364E+13
October 0.454583E+12 -0.104715E+11 0.00 -0.504640E+11 0.274201E+13
November 0.348252E+12 0.327180E+10 0.00 0.134112E+13 0.187721E+13
December 0.358796E+12 0.759176E+10 0.00 0.193662E+13 0.172669E+13
           
Annual Sum or Average 0.569490E+13 -0.539551E+11 0.00 0.464277E+13 0.293802E+14
Minimum of Months 0.348252E+12 -0.183162E+11 0.00 -0.904147E+12 0.644120E+12
Maximum of Months 0.570055E+12 0.939272E+10 0.00 0.193662E+13 0.427833E+13