Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820

Simulation Timestamp: 2023-10-16 08:56:50


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 30028.71 648.28 648.28
Net Site Energy 29495.02 636.76 636.76
Total Source Energy 93714.31 2023.18 2023.18
Net Source Energy 92024.11 1986.69 1986.69


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 56.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6149.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1809.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 263.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1203.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2594.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 804.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1778.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18496.29
Humidification 83.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.05
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 609.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 29363.03 665.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20807.50
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 56.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 6149.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1809.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 263.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1144.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 4.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2594.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 804.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1778.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18496.29
Humidification General 83.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.05
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 609.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 56.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 6149.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1809.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 263.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1203.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2594.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 804.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1778.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18496.29
Humidification Unassigned 83.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.05
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 609.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 44.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 246.33 14.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Other 342.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 633.91 14.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 44.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 246.33 14.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Other 342.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 633.91 14.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 557.235 1.90
Wind Power 0.000 0.00
Power Conversion -23.54 -0.1
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 533.690 1.82
     
Electricity Coming From Utility 28829.337 98.18
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 28829.337 98.18
     
Total On-Site and Utility Electric Sources 29363.028 100.00
Total Electricity End Uses 29363.028 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 20807.50 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 20807.50 100.00
Total Water End Uses 20807.50 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.17
Time Setpoint Not Met During Occupied Cooling 1161.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionElectricityGeneratedPropaneMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
RunPeriod RUNPERIOD 1
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Latitude [deg] 28.58
Longitude [deg] 77.20
Elevation [m] 216.00
Time Zone 5.50
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 6.0985 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.0985 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 6.0985 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.0985 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.0985 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.0985 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.0985 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.0985 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 6.0985 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.0985 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 6.0985 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.0985 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.0985 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.0985 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.0985 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.0985 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 7.5721 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 7.5721 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 7.5721 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 6.0985 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.1124 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.1124 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.0985 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.0985 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 6.0985 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.0985 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.0985 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.0985 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.0985 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.0985 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.0985 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.0985 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.0985 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.0985 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.0985 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.0985 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.0985 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.0985 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 7.5721 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 7.5721 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 7.5721 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 6.0985 18.58 484.4232  
Total 46320.38             6.1124 9.29 17.8789  
Conditioned Total 46320.38             6.1124 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 1.8799 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 07-AUG-15:20 02-JAN-06:10 - - - - - - - - - - 12-JUN-15:30
Heating 0.00 732413.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 537468.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 154097.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 52593.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 232795.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 48566.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 81944.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7280.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1885837.91 739694.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 732413.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 537468.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 154097.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3363.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 49008.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 221.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 232795.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 48566.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 81944.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 7280.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 61.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19477.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5729.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 834.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 3812.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8215.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2547.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 5631.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 264.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 660.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 92992.71 721.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 420.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 123.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 177.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 55.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 121.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 5.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2007.60 15.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 420.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 123.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 177.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 55.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 121.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 5.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2007.60 15.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.23
DATACENTER_BOT_ZN_6 DIRECT AIR 0.478704
DATACENTER_MID_ZN_6 DIRECT AIR 4.57
DATACENTER_TOP_ZN_6 DIRECT AIR 0.462284
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.85 0.325310 0.277000 1.62 0.867493 0.500000 0.001171 0.000348 1.62 12.80 0.008000
CORE_MID VAV BOX COMPONENT 55.94 0.340030 0.289000 16.17 0.906747 0.500000 0.001120 0.008441 16.17 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.73 0.331994 0.282000 1.62 0.885318 0.500000 0.001148 0.001489 2.08 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.29 0.184809 0.157000 0.202884 0.492824 0.500000 0.002062 0.000151 0.209982 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.02 0.150469 0.128000 0.130923 0.401252 0.500000 0.002532 0.000110 0.153484 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.30 0.183110 0.156000 0.203466 0.488294 0.500000 0.002081 0.000201 0.280510 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.34 0.114732 0.098000 0.131460 0.305953 0.500000 0.003321 0.000073 0.131460 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 12.99 0.183835 0.156000 2.03 0.490227 0.500000 0.002073 0.003555 4.97 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 10.82       0.379327 0.500000 0.002678 0.002349 3.28 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 12.99 0.183896 0.156000 2.03 0.490390 0.500000 0.002072 0.003555 4.97 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 11.90 0.129367 0.110000 1.31 0.344978 0.500000 0.002945 0.002154 3.01 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.46 0.163435 0.139000 0.203114 0.435827 0.500000 0.002331 0.000441 0.616053 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.13 0.136464 0.116000 0.130825 0.363905 0.500000 0.002792 0.000289 0.404318 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.46 0.163841 0.139000 0.202616 0.436909 0.500000 0.002325 0.000441 0.616059 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.29 0.118955 0.101000 0.130675 0.317214 0.500000 0.003203 0.000275 0.384213 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 15895.82 0.000348 443.65
CORE_MID VAV BOX REHEAT COIL 385891.27 0.008441 12933.89
CORE_TOP VAV BOX REHEAT COIL 68090.67 0.001489 2652.23
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6894.62 0.000151 268.75
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5036.28 0.000110 196.23
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9195.50 0.000201 358.06
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3348.23 0.000073 114.89
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 162503.79 0.003555 6318.67
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 107364.33 0.002349 4174.49
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 162504.86 0.003555 6318.71
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 98464.27 0.002154 3829.01
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 20140.35 0.000441 782.86
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 13217.65 0.000289 513.76
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 20140.54 0.000441 782.86
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 12561.74 0.000275 488.30
VAV_BOT WITH REHEAT HEATING COIL 20359.49 0.000445 470.72
VAV_MID WITH REHEAT HEATING COIL 77376.41 0.001693 1834.95
VAV_TOP WITH REHEAT HEATING COIL 8430.75 0.000184 200.13
CAV_BAS HEATING COIL 238062.16 0.005208 7778.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.40 2.29 10.81 2.29 9.88 9.88 0.300000 0.231557 9.88
VAV_MID WITH REHEAT 52.32 22.84 104.63 27.01 94.67 94.67 0.300000 0.285261 94.67
VAV_TOP WITH REHEAT 5.53 2.28 11.07 4.10 10.93 10.93 0.300000 0.374811 10.93
CAV_BAS 5.23 5.23 5.23 5.23 5.23 5.23 1.00 1.00 5.23
AIRLOOP DATACENTER BASEMENT 21.85 21.85 21.85 21.85 21.85 21.85 1.00 0.999989 21.85
AIRLOOP DATACENTER BOT 0.478704 0.478704 0.478704 0.478704 0.478704 0.478704 1.00 1.00 0.478704
AIRLOOP DATACENTER MID 4.57 4.57 4.57 4.57 4.57 4.57 1.00 1.00 4.57
AIRLOOP DATACENTER TOP 0.462284 0.462284 0.462284 0.462284 0.462284 0.462284 1.00 1.00 0.462284
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.88  
VAV_MID WITH REHEAT_OA_CONTROLLER 94.67  
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.93  
CAV_BAS_OA_CONTROLLER 5.23 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.85 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.478704 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.57 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.462284 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 27.70 6.67 10.99 0.007711 0.007000 218315.70 0.006244 9.88
VAV_MID WITH REHEAT COOLING COIL 27.96 6.67 10.99 0.007767 0.007000 2136229.56 0.061096 94.67
VAV_TOP WITH REHEAT COOLING COIL 27.33 6.67 11.00 0.007665 0.007000 235019.64 0.006722 10.93
CAV_BAS COOLING COIL 28.27 6.67 11.38 0.007950 0.007000 120546.62 0.003448 5.23
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.88
VAV_MID WITH REHEAT FAN 94.67
VAV_TOP WITH REHEAT FAN 10.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.006244 0.000076
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000445  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.061096 0.000008
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.001693  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.006722 0.000071
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000184  
CAV_BAS_COOLC_CONTROLLER 0.003448 0.000138
CAV_BAS_HEATC_CONTROLLER 0.005208  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.23
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.85 450094.94 280281.16 0.011023
AIRLOOP DATACENTER BOT COOLING COIL 0.478704 9846.57 6123.69 0.000241
AIRLOOP DATACENTER MID COOLING COIL 4.57 94174.85 58518.00 0.002306
AIRLOOP DATACENTER TOP COOLING COIL 0.462284 9515.62 5915.75 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.85 21.85 21.85 21.85 450094.94 450094.94 13450.69 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.478704 0.478704 0.478704 0.478704 9846.57 9846.57 621.37 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.57 4.57 4.57 4.57 94174.85 94174.85 6213.66 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.462284 0.462284 0.462284 0.462284 9515.62 9515.62 621.37 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.85
AIRLOOP DATACENTER BOT SUPPLY FAN 0.478704
AIRLOOP DATACENTER MID SUPPLY FAN 4.57
AIRLOOP DATACENTER TOP SUPPLY FAN 0.462284
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.85 450094.94 0.011023
AIRLOOP DATACENTER BOT HEATING COIL 0.478704 9846.57 0.000241
AIRLOOP DATACENTER MID HEATING COIL 4.57 94174.85 0.002306
AIRLOOP DATACENTER TOP HEATING COIL 0.462284 9515.62 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 13450.69
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 621.37
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6213.66
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 621.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000048 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.077509 12529.53  
HEATSYS1 PUMP 0.031401 9363.01 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.077509 9.30
HEATSYS1 0.031401 3.77
COOLSYS1_SUPPLY 0.077509 9.30
SINGLE WATER PLANT LOOP 0.013803 1.66
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.077509 0.077509 325343.52 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1435478.73 1435478.73 0.031401
CENTRAL BOILER 568578.07 557591.35 0.013803
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.038754 4337.31
COOLSYS1 CHILLER2 PUMP 0.038754 4337.31
PLANT CIRC PUMP 0.013803 3485.68
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.077509 0.039152 1372316.40 1378826.07 0.067787
COOLSYS1 CHILLER2 0.077509 0.039152 1372316.40 1378826.07 0.067787
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013803 139666.47 57394.61 69833.23 7004.20 21223.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.135573 16.27
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.135573 33232.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 51.53 1635942.04 10.31 204492.76
TOWERWATERSYS COOLTOWER 2 51.53 1635942.04 10.31 204492.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.070873
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 25.10 19.60 14.50 13.40 17.00 22.40 29.10 33.00 33.60 31.70 30.00 28.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 28.58 77.20 5.50 216.00 98757 1.1738


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.84 20.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 6.099 4.842 0.000 0.000 0.000 0.000 10.940 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.169 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.169 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.169 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.169 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.169 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.169 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 6.099 8.070 0.000 0.000 0.000 0.000 14.168 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 7.572 215.299 0.000 0.000 0.000 0.000 222.871 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 7.572 215.299 0.000 0.000 0.000 0.000 222.871 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 7.572 215.299 0.000 0.000 0.000 0.000 222.871 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 6.099 484.423 0.000 0.000 0.000 0.000 490.522 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 16950.429 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16950.429
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 15222.677 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 15222.677
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 15222.677 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 15222.677
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 15222.677 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 15222.677
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 1911.359 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1911.359
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1231.752 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1231.752
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 1911.401 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1911.401
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1231.752 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1231.752
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 1911.359 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1911.359
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1231.752 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1231.752
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 1911.401 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1911.401
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1231.752 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1231.752
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 1911.359 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1911.359
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1231.752 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1231.752
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 1911.401 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1911.401
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1231.752 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1231.752
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 4779.296 6.099 113.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4779.296
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 274.132 7.572 140.681 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 274.132
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 274.132 7.572 140.681 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 274.132
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 274.132 7.572 140.681 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 274.132


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.2994E-01
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.2994E-01
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.2994E-01
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
47 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
48 1 -21.915918 0.11588205 -6.3286394 0.20197014
49 0 21.365777 0.10835518 5.5011278  
50 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
51 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
52 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
53 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
54 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
55 4 19.715055 0.51780401E-02 12.415669 -0.24584718
56 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
57 2 168.49726 0.99923307E-02 62.094262 -2.4465849
58 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
59 0 57.057407 0.91053392E-05 16.929182  
60 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
61 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
62 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
63 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
64 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
65 4 19.715055 0.51780401E-02 12.415669 -0.24584718
66 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
67 2 168.49726 0.99923307E-02 62.094262 -2.4465849
68 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
69 0 57.057407 0.91053392E-05 16.929182  
70 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
71 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
72 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
73 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
74 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
75 4 19.715055 0.51780401E-02 12.415669 -0.24584718
76 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
77 2 168.49726 0.99923307E-02 62.094262 -2.4465849
78 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
79 0 57.057407 0.91053392E-05 16.929182  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.504_SHGC_EAST_0.229 35 1 VerySmooth 2.865 2.865 1.000 0.230    
2 WINDOW_U_0.504_SHGC_SOUTH_0.229 36 1 VerySmooth 2.865 2.865 1.000 0.230    
3 WINDOW_U_0.504_SHGC_WEST_0.229 37 1 VerySmooth 2.865 2.865 1.000 0.230    
4 WINDOW_U_0.504_SHGC_NORTH_0.229 38 1 VerySmooth 2.865 2.865 1.000 0.230    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   1.91956E-002 0.14029 0.63148 0.63148 0.25190 0.16103 0.23774 0.00000 0.84000 0.84000 0.10739 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   1.91956E-002 0.14029 0.63148 0.63148 0.25190 0.16103 0.23774 0.00000 0.84000 0.84000 0.10739 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   1.91956E-002 0.14029 0.63148 0.63148 0.25190 0.16103 0.23774 0.00000 0.84000 0.84000 0.10739 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   1.91956E-002 0.14029 0.63148 0.63148 0.25190 0.16103 0.23774 0.00000 0.84000 0.84000 0.10739 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.486 6.0748E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.4306E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.4319E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6212E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6222E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7737E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7744E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.6123E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.6128E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.4593E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5392E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6446E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7116E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7921E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8461E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.6259E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.6600E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.5698E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.4573E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.3962E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6486E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.7735E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.4606E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8968E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.0048E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.4651E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5672E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6508E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7417E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7978E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8678E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.6263E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.6610E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.4305E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.4320E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6211E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6223E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7737E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7746E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.6122E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.6127E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5778E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.7177E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4166E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5609E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2396E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3127E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7571E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7807E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.0105E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.8837E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7658E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7088E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8360E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5461E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0167E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.1262E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5454E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6026E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3763E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.4182E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2176E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.2352E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7572E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7811E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5795E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5808E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3590E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3601E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2057E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2065E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6123E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6128E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6088E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6812E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3831E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4407E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2248E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2661E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6263E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6611E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4232E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2556E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8773E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.5976E-003
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6679E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 6.4991E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8968E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0045E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6068E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6786E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3805E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4355E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2203E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2526E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6260E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6601E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5794E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5806E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3589E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3599E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2056E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2062E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.6123E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6128E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0666E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1262E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.7967E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.8398E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.7693E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7851E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.7572E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7811E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.1848E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.5773E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.7761E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3423E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0214E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2396E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0167E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.1262E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0924E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.2024E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.8293E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.9373E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.7898E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.8541E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.7570E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7806E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.9629E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.0849E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.6005E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.3564E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.5176E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.7626E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.5538E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.7566E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.7829E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.7353E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.5105E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.5228E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.5624E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.3125E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.6430E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.7769E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0510E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.0150E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.4296E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6083E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.1934E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2154E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.5538E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.7563E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.8473E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.3098E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.3878E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0123E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6469E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8983E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6430E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.7769E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.9738E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.0958E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.6136E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.3687E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.5313E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.7720E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.5614E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.7605E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.7875E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.7397E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.5157E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.5270E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.5701E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.3174E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.6507E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.7808E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0515E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.0172E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.4303E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6102E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.1969E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2175E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.5614E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.7602E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.8499E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.3131E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.3906E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0152E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6529E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9021E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6507E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.7808E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 70699.60985 70699.60985 5.23490 5.23490 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 6.30000 6.07234E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 78951.28420 78951.28420 5.84687 5.84687 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 6.30000 6.07234E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 755485.91304 755485.91304 55.93750 55.93750 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 227226.30141 227226.30141 9.81660 10.77825 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 76653.47807 76653.47807 5.72915 5.72915 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:10:00 41.90300 9.15774E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 47714.70394 47714.70394 2.07605 2.07605 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 17289.90936 17289.90936 1.29226 1.29226 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:50:00 41.51500 9.15709E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 4834.09693 4834.09693 0.20998 0.20998 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 13685.15714 13685.15714 1.02283 1.02283 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:20:00 38.79900 9.15255E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 3530.13919 3530.13919 0.15348 0.15348 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 17450.68646 17450.68646 1.30427 1.30427 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:20:00 42.00000 9.15790E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 6442.73413 6442.73413 0.28051 0.28051 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 17947.93315 17947.93315 1.34143 1.34143 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 41.15933 9.15650E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 2058.38127 2058.38127 8.89428E-002 8.89428E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 173812.46957 173812.46957 12.99102 12.99102 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:00:00 41.41800 9.15693E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 113748.48389 113748.48389 4.96805 4.96805 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 144759.31918 144759.31918 10.81951 10.81951 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:30:00 39.04150 9.15295E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 75150.00462 75150.00462 3.28256 3.28256 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 173758.39442 173758.39442 12.98698 12.98698 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00000 9.15790E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 113749.23511 113749.23511 4.96809 4.96809 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 159172.99340 159172.99340 11.89679 11.89679 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 41.03000 9.15628E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 68927.77742 68927.77742 3.00976 3.00976 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 19550.67786 19550.67786 1.46125 1.46125 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:50:00 41.51500 9.15709E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 14094.39711 14094.39711 0.61605 0.61605 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15089.35658 15089.35658 1.12781 1.12781 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:50:00 39.52650 9.15377E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 9249.66612 9249.66612 0.40432 0.40432 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 19502.71066 19502.71066 1.45767 1.45767 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 42.00000 9.15790E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 14094.53361 14094.53361 0.61606 0.61606 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 17310.41322 17310.41322 1.29381 1.29381 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 41.03000 9.15628E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 8791.10993 8791.10993 0.38421 0.38421 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8121.36305 8121.36305 0.47870 0.47870 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 32.36467 9.14193E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 77545.36358 77545.36358 4.57082 4.57082 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 32.36467 9.14193E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7841.86771 7841.86771 0.46228 0.46228 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:50:00 40.77133 9.15585E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370656.32437 370656.32437 21.84997 21.84997 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:00:00 33.17300 9.14325E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 6.30000 6.07234E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 173476.76 9.88229 9.88229 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 13882.38 1.81074 1.81074 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1650893.74 94.67353 94.67353 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 152170.03 27.00671 27.00671 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 22:10:00
5 VAV_TOP WITH REHEAT Cooling Sensible 186893.44 10.93004 10.93004 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 15351.72 4.09670 4.09670 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 06:10:00
7 CAV_BAS Cooling Sensible 85762.05 5.23490 5.23490 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
8 CAV_BAS Heating Sensible 47704.73 1.20016 1.20016 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 371456.91 21.85020 21.85020 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 13450.69 0.33839 0.33839 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8126.40 0.47870 0.47870 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 621.37 1.56323E-002 1.56323E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 77561.25 4.57082 4.57082 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6213.66 0.15632 0.15632 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7999.05 0.46228 0.46228 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 621.37 1.56323E-002 1.56323E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.23490
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.84687
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32531
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27700
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61958
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.86749
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.17119E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.47721E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.61958
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15895.81841
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.47721E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 443.65388
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 55.93750
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34003
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28900
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.16594
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.90675
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12049E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.44138E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.16594
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 385891.26916
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.44138E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12933.89402
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.72915
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33199
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28200
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61562
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88532
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14761E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48949E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.07605
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 68090.66860
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48949E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2652.23012
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.29226
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18481
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15700
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20288
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49282
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.06159E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.50820E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20998
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6894.61686
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.50820E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 268.74847
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.02283
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15047
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12800
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13092
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40125
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53208E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.10169E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15348
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5036.28343
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.10169E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 196.22893
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30427
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18311
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15600
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20347
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48829
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.08071E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.01152E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28051
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9195.49737
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.01152E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 358.05845
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.34143
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11473
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.80000E-002
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13146
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30595
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.32077E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.32425E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13146
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3348.22566
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.32425E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 114.88660
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.99102
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18384
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15600
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02660
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49023
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.07251E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.55477E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.96805
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 162503.79331
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.55477E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6318.67153
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.81951
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37933
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.67843E-003
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.34860E-003
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.28256
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
122 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 107364.32780
123 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.34860E-003
124 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4174.48555
125 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.98698
126 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18390
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15600
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02597
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49039
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.07182E-003
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.55480E-003
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.96809
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
136 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 162504.86341
137 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.55480E-003
138 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6318.71332
139 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.89679
140 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12937
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11000
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30865
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34498
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.94511E-003
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.15391E-003
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.00976
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
150 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 98464.27144
151 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.15391E-003
152 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3829.00920
153 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.46125
154 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16344
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13900
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20311
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43583
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.33120E-003
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.40571E-004
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.61605
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
164 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20140.34748
165 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.40571E-004
166 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 782.85528
167 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12781
168 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13646
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11600
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13083
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36390
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.79194E-003
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.89136E-004
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.40432
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
178 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13217.64794
179 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.89136E-004
180 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 513.75624
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.45767
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16384
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13900
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20262
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43691
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.32543E-003
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.40575E-004
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.61606
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
192 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20140.54229
193 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.40575E-004
194 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 782.86287
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.29381
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11896
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10100
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13067
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31721
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.20289E-003
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.74788E-004
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38421
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
206 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12561.74300
207 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.74788E-004
208 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 488.29580
209 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.47870
210 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.57082
211 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46228
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.84997
213 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.40383
214 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28832
215 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.80766
216 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.28832
217 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.88229
218 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.88229
219 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
220 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.23156
221 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 52.31590
222 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.83631
223 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 104.63179
224 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 27.00671
225 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 94.67353
226 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 94.67353
227 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
228 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.28526
229 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.53484
230 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28285
231 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.06968
232 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 4.09670
233 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.93004
234 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.93004
235 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
236 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.37481
237 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.23490
238 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.23490
239 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.23490
240 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.23490
241 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.23490
242 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.23490
243 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.84997
246 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.84997
247 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.84997
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.84997
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.85020
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.85020
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
253 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.47870
254 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.47870
255 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.47870
256 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.47870
257 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.47870
258 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.47870
259 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
260 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
261 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.57082
262 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.57082
263 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.57082
264 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.57082
265 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.57082
266 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.57082
267 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
268 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
269 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46228
270 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46228
271 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46228
272 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.46228
273 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.46228
274 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.46228
275 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
276 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
277 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.88229
278 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 94.67353
279 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.93004
280 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.23490
281 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.85020
282 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.47870
283 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.57082
284 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.46228
285 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.88229
286 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.70222
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99363
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.71067E-003
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 218315.70490
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.24380E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.88229
294 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 20359.49257
295 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.45364E-004
296 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 470.71853
297 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.88229
298 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.24380E-003
299 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.62661E-005
300 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.45364E-004
301 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 94.67353
302 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.95704
303 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99381
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.76672E-003
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2136229.56016
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.10959E-002
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 94.67353
310 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 77376.41421
311 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.69261E-003
312 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1834.95231
313 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 94.67353
314 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.10959E-002
315 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.79415E-006
316 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.69261E-003
317 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.93004
318 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.33305
319 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
320 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.00308
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.66510E-003
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 235019.63963
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.72153E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.93004
326 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 8430.75207
327 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.84423E-004
328 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 200.12985
329 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.93004
330 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.72153E-003
331 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.08455E-005
332 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.84423E-004
333 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.23490
334 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
335 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 28.27444
336 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
337 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.38319
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.94981E-003
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 120546.62233
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.44762E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.23490
343 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 238062.15901
344 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.20762E-003
345 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 7778.91432
346 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.23490
347 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.44762E-003
348 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.38122E-004
349 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.20762E-003
350 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.85020
351 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
352 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.85020
353 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 450094.94150
354 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 280281.16418
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.10228E-002
356 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.85020
357 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.85020
358 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.85020
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.85020
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 450094.94150
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 450094.94150
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 13450.69260
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
364 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.85020
365 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.85020
366 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 450094.94150
367 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.10228E-002
368 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 13450.69260
369 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 4.77077E-005
370 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
371 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
373 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.47870
374 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
375 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.47870
376 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9846.56543
377 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6123.69212
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.41142E-004
379 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.47870
380 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.47870
381 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.47870
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.47870
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9846.56543
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9846.56543
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 621.36627
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
387 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.47870
388 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.47870
389 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9846.56543
390 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.41142E-004
391 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 621.36627
392 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.57082
393 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
394 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.57082
395 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 94174.85131
396 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 58517.99862
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.30634E-003
398 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.57082
399 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.57082
400 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.57082
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.57082
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 94174.85131
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 94174.85131
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6213.66275
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
406 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.57082
407 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.57082
408 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 94174.85131
409 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.30634E-003
410 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6213.66275
411 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46228
412 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
413 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46228
414 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9515.62311
415 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5915.74884
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.33037E-004
417 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46228
418 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46228
419 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46228
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46228
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9515.62311
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9515.62311
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 621.36627
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
425 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46228
426 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46228
427 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9515.62311
428 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.33037E-004
429 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 621.36627
430 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 7.75088E-002
431 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 12529.53093
432 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 7.75088E-002
433 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 9.30106
434 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 7.75088E-002
435 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 7.75088E-002
436 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 325343.52065
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 8.33000
438 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.14011E-002
439 PlantLoop HEATSYS1 Plant Loop Volume [m3] 3.76814
440 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.14011E-002
441 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 9363.01341
442 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
443 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1435478.73402
444 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1435478.73000
445 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.14011E-002
446 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 7.75088E-002
447 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 9.30106
448 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 3.87544E-002
449 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 4337.30840
450 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 3.87544E-002
451 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 4337.30840
452 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 7.75088E-002
453 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.91519E-002
454 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1372316.40348
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1378826.07000
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 6.77867E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 7.75088E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.91519E-002
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1372316.40348
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1378826.07000
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 6.77867E-002
462 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.38033E-002
463 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.65640
464 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.38033E-002
465 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3485.67778
466 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.38033E-002
467 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
468 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 57394.61230
469 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
470 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7004.19857
471 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21223.62277
472 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 568578.07455
473 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 557591.35000
474 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.38033E-002
475 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
476 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
477 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
478 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
479 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
480 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.13557
481 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 16.26880
482 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.13557
483 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 33232.63536
484 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 51.52794
485 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1635942.04278
486 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 10.30559
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 204492.75535
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 51.52794
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1635942.04278
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 10.30559
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 204492.75535
492 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.08725E-002
493 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.08725E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 22128.94
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 537510.71
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 94761.09
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 9595.14
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 7008.94
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 12797.30
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4662.95
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 226156.35
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 149418.84
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 226157.84
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 137032.56
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 28029.33
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 18395.01
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 28029.61
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 17482.18
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 25238.15
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 102767.52
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 11226.83
19 Coil:Heating:Water CAV_BAS HEATING COIL 267212.86


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 277873.37 185889.27 91984.10 0.67 70917.84 719.29
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2683139.89 1789655.10 893484.79 0.67 668647.26 6781.79
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 304211.50 204296.36 99915.14 0.67 80300.67 814.45
4 Coil:Cooling:Water CAV_BAS COOLING COIL 147521.77 98586.26 48935.51 0.67 33522.21 340.00


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.80 23.21
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.80 23.21


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_NORTH_0.229 N/A 2.865 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_NORTH_0.229 N/A 2.865 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_NORTH_0.229 N/A 2.865 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_NORTH_0.229 N/A 2.865 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_NORTH_0.229 N/A 2.865 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_EAST_0.229 N/A 2.865 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_EAST_0.229 N/A 2.865 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_EAST_0.229 N/A 2.865 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_SOUTH_0.229 N/A 2.865 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_SOUTH_0.229 N/A 2.865 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_SOUTH_0.229 N/A 2.865 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_SOUTH_0.229 N/A 2.865 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_SOUTH_0.229 N/A 2.865 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_WEST_0.229 N/A 2.865 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_WEST_0.229 N/A 2.865 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_WEST_0.229 N/A 2.865 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_NORTH_0.229 N/A 2.865 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_EAST_0.229 N/A 2.865 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_SOUTH_0.229 N/A 2.865 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_WEST_0.229 N/A 2.865 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_NORTH_0.229 N/A 2.865 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_EAST_0.229 N/A 2.865 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_SOUTH_0.229 N/A 2.865 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.504_SHGC_WEST_0.229 N/A 2.865 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 5.069 2.882   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 5.069 2.882   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.3006597706 0.1886340026 Pass Pass 0.1582228336 0.3540427437 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 4.7130330934E-003 5.2261893961E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 5.2740742325E-003 5.6834893282E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 6.0061804470E-002 5.7160186441E-002 Pass Pass 0.1468603258 0.3506466093 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.6865663731E-002 1.8203911879E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 3.6177644670E-002 3.8941233246E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 6.0983516781E-002 4.6548574907E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 4.2088204960E-002 3.5239919133E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 3.0026999451E-002 1.9509959242E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 4.0335460696E-002 3.9430903711E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 7.0276146238E-002 5.1405191911E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 4.6880182356E-002 3.6720017968E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1005245825 0.1389578567 Pass Pass 0.3607902635 1.0109781128 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 7.0974341944E-002 8.6449004633E-002 Pass Pass 0.4241420128 2.1651989051 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 8.7741460035E-002 6.6364665120E-002 Pass Pass 0.5127583843 2.5466509973 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 6.7131152911E-002 5.1216002065E-002 Pass Pass 1.2841368640 8.3966411162 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 7.3363355956E-003 4.7180395382E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 7.6378528744E-003 5.0883459850E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.7122306729E-002 5.6743915821E-002 Pass Pass 0.1519183503 0.3509712429 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 6.7369528402E-005 7.2497865697E-005 Pass Pass 4.5058913094E-003 2.6076369601E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 1.1502192527E-002 1.0874913361E-002 Pass Pass 0.1774075466 0.8612554578 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 4.0052389652E-002 1.9761221498E-002 Pass Pass 1.3315292700E-002 9.1461057158E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 3.2718862042E-004 2.1086039492E-004 Pass Pass 7.6502189480E-005 1.0043752893E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4328.10 -42.1 0.00 -5249.6 41063.30 40099.68



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 6.30 0.00 6.30 Wetbulb [C] 0.50 270.00
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 42.00 9.70 22.20 Wetbulb [C] 3.20 320.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.60 4      
Feb 21.40 43      
Mar 12.00 35      
Apr 29.10 12      
May 29.10 57      
Jun 197.10 59      
Jul 47.90 83      
Aug 0.00 0      
Sep 171.60 106      
Oct 4.80 31      
Nov 1.20 7      
Dec 33.00 13      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 2.882 5.069 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 2.882 5.069 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 2.882 5.069 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 2.882 5.069 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 2.882 5.069 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 2.882 5.069 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 2.882 5.069 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.273 0.283 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.504_SHGC_NORTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.504_SHGC_NORTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.504_SHGC_NORTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.504_SHGC_NORTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.504_SHGC_NORTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.504_SHGC_EAST_0.229   25.75 0.00 0.00 25.75 25.75 2.865 0.230 0.253             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.504_SHGC_EAST_0.229   25.75 0.00 0.00 25.75 25.75 2.865 0.230 0.253             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.504_SHGC_EAST_0.229   25.75 0.00 0.00 25.75 25.75 2.865 0.230 0.253             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.504_SHGC_SOUTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.504_SHGC_SOUTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.504_SHGC_SOUTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.504_SHGC_SOUTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.504_SHGC_SOUTH_0.229   23.18 0.00 0.00 23.18 23.18 2.865 0.230 0.253             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.504_SHGC_WEST_0.229   25.75 0.00 0.00 25.75 25.75 2.865 0.230 0.253             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.504_SHGC_WEST_0.229   25.75 0.00 0.00 25.75 25.75 2.865 0.230 0.253             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.504_SHGC_WEST_0.229   25.75 0.00 0.00 25.75 25.75 2.865 0.230 0.253             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.504_SHGC_NORTH_0.229   115.90 0.00 0.00 115.90 1158.95 2.865 0.230 0.253             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.504_SHGC_EAST_0.229   77.26 0.00 0.00 77.26 772.63 2.865 0.230 0.253             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.504_SHGC_SOUTH_0.229   115.90 0.00 0.00 115.90 1158.95 2.865 0.230 0.253             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.504_SHGC_WEST_0.229   77.26 0.00 0.00 77.26 772.63 2.865 0.230 0.253             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.504_SHGC_NORTH_0.229   115.90 0.00 0.00 115.90 115.90 2.865 0.230 0.253             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.504_SHGC_EAST_0.229   77.26 0.00 0.00 77.26 77.26 2.865 0.230 0.253             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.504_SHGC_SOUTH_0.229   115.90 0.00 0.00 115.90 115.90 2.865 0.230 0.253             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.504_SHGC_WEST_0.229   77.26 0.00 0.00 77.26 77.26 2.865 0.230 0.253             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.865 0.230 0.253                      
North Total or Average             1390.74 2.865 0.230 0.253                      
Non-North Total or Average             3245.06 2.865 0.230 0.253                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.0985 2779.43 16950.43 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.49 0.0000 Y 122.46
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.0985 2496.12 15222.68 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.49 0.0000 Y 109.97
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.0985 24961.20 152226.77 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.49 0.0000 Y 1099.74
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.0985 2496.12 15222.68 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.49 0.0000 Y 109.97
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.0985 313.41 1911.36 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.10 0.0000 Y 7.93
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.0985 201.98 1231.75 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.01 0.0000 Y 5.09
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.0985 313.42 1911.40 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.87 0.0000 Y 7.85
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.0985 201.98 1231.75 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.99 0.0000 Y 5.08
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.0985 3134.13 19113.59 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.07 0.0000 Y 79.18
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.0985 2019.75 12317.52 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.98 0.0000 Y 50.82
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.0985 3134.20 19114.01 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.85 0.0000 Y 78.40
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.0985 2019.75 12317.52 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.96 0.0000 Y 50.77
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.0985 313.41 1911.36 LightsWired LTG_SCH_OFFICE 39.68 168.00 22.07 0.0000 Y 7.92
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.0985 201.98 1231.75 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.98 0.0000 Y 5.08
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.0985 313.42 1911.40 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.85 0.0000 Y 7.84
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.0985 201.98 1231.75 LightsWired LTG_SCH_OFFICE 39.68 168.00 21.96 0.0000 Y 5.08
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 6.0985 783.68 4779.30 LightsWired LTG_SCH_OFFICE 39.68 168.00 38.66 0.0000 Y 34.68
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 7.5721 36.20 274.13 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 1.77
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 7.5721 362.03 2741.32 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 17.69
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 7.5721 36.20 274.13 LightsWired LTG_SCH_DATACENTER 35.29 168.00 34.37 0.0000 Y 1.77
Interior Lighting Total       6.1124 46320.38 283126.61               570.14


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1911.40 737.23
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1911.40 264.73
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1231.75 475.09
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1231.75 170.60
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1911.36 737.21
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1911.36 264.72
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1231.75 475.09
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1231.75 170.60
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1911.40 737.23
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1911.40 264.73
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1231.75 475.09
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1231.75 170.60
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1911.36 737.21
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1911.36 264.72
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1231.75 475.09
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1231.75 170.60
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1911.40 737.23
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1911.40 264.73
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1231.75 475.09
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1231.75 170.60
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1911.36 737.21
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1911.36 264.72
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1231.75 475.09
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1231.75 170.60


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 12952.94 AstronomicalClock -   41.75 41.75 101.52
EXTERIOR_LIGHTS_B 919.74 AstronomicalClock -   83.75 62.75 10.83
EXTERIOR_LIGHTS_C 17215.91 AstronomicalClock -   83.75 46.80 151.24
Exterior Lighting Total 31088.59           263.60



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2701764.14          
HEATSYS1 BOILER Boiler:HotWater 1435478.73 0.90        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1378826.07 6.59 1209544.65 5.87 6.80 23.21
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1378826.07 6.59 1209544.65 5.87 6.80 23.21
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 557591.35 0.90        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1635942.04          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1635942.04          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 218315.70 277873.37 185889.27 91984.10 0.67 - 70917.84 719.29
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2136229.56 2683139.89 1789655.10 893484.79 0.67 - 668647.26 6781.79
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 235019.64 304211.50 204296.36 99915.14 0.67 - 80300.67 814.45
CAV_BAS COOLING COIL Coil:Cooling:Water 120546.62 147521.77 98586.26 48935.51 0.67 - 33522.21 340.00
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   450094.94 280281.16 169813.78 0.62 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9846.57 6123.69 3722.87 0.62 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   94174.85 58518.00 35656.85 0.62 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9515.62 5915.75 3599.87 0.62 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 15895.82 22128.94 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 385891.27 537510.71 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 68090.67 94761.09 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 6894.62 9595.14 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 5036.28 7008.94 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 9195.50 12797.30 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 3348.23 4662.95 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 162503.79 226156.35 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 107364.33 149418.84 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 162504.86 226157.84 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 98464.27 137032.56 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 20140.35 28029.33 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 13217.65 18395.01 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 20140.54 28029.61 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 12561.74 17482.18 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 20359.49 25238.15 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 77376.41 102767.52 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 8430.75 11226.83 -
CAV_BAS HEATING COIL Coil:Heating:Water 238062.16 267212.86 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   450094.94 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9846.57 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   94174.85 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9515.62 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   13450.69 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   621.37 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6213.66 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   621.37 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.88 21355.10 2160.95 1.00 1.12 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 94.67 204584.46 2160.95 1.00 1.08 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.93 23493.73 2149.46 1.00 1.12 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.23 8876.58 1695.65 1.00 1.16 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 21.85 36036.38 1649.25 1.00 1.14 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 536.20 1120.11 1.00 1.63 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.57 5119.81 1120.11 1.00 1.16 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 517.81 1120.11 1.00 1.64 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.077509 12529.53 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.031401 9363.01 298174.34 0.91 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.038754 4337.31 111917.77 0.91 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.038754 4337.31 111917.77 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013803 3485.68 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.135573 33232.64 245126.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.49 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 70699.61 70699.61 25.44 5.235 5.235 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00750 34.82 0.00915 1.200 0.00
CORE_BOTTOM 78951.28 78951.28 31.63 5.847 5.847 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00740 34.82 0.00915 1.078 0.00
CORE_MID 755485.91 755485.91 302.66 55.937 55.937 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00741 34.82 0.00915 10.778 0.00
CORE_TOP 76653.48 76653.48 30.71 5.729 5.729 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:10:00 24.00 24.00 0.00740 41.90 0.00916 1.078 0.00
PERIMETER_BOT_ZN_3 17289.91 17289.91 55.17 1.292 1.292 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:50:00 24.00 24.00 0.00725 41.52 0.00916 0.135 0.00
PERIMETER_BOT_ZN_2 13685.16 13685.16 67.76 1.023 1.023 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:20:00 24.00 24.00 0.00720 38.80 0.00915 0.087 0.00
PERIMETER_BOT_ZN_1 17450.69 17450.69 55.68 1.304 1.304 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:20:00 24.00 24.00 0.00724 42.00 0.00916 0.135 0.00
PERIMETER_BOT_ZN_4 17947.93 17947.93 88.86 1.341 1.341 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 24.00 24.00 0.00715 41.16 0.00916 0.087 0.00
PERIMETER_MID_ZN_3 173812.47 173812.47 554.58 12.991 12.991 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:00:00 24.00 24.00 0.00728 41.42 0.00916 1.353 0.00
PERIMETER_MID_ZN_2 144759.32 144759.32 716.72 10.820 10.820 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:30:00 24.00 24.00 0.00722 39.04 0.00915 0.872 0.00
PERIMETER_MID_ZN_1 173758.39 173758.39 554.40 12.987 12.987 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 24.00 24.00 0.00728 42.00 0.00916 1.353 0.00
PERIMETER_MID_ZN_4 159172.99 159172.99 788.08 11.897 11.897 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 24.00 24.00 0.00720 41.03 0.00916 0.872 0.00
PERIMETER_TOP_ZN_3 19550.68 19550.68 62.38 1.461 1.461 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:50:00 24.00 24.00 0.00726 41.52 0.00916 0.135 0.00
PERIMETER_TOP_ZN_2 15089.36 15089.36 74.71 1.128 1.128 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:50:00 24.00 24.00 0.00722 39.53 0.00915 0.087 0.00
PERIMETER_TOP_ZN_1 19502.71 19502.71 62.23 1.458 1.458 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 24.00 24.00 0.00726 42.00 0.00916 0.135 0.00
PERIMETER_TOP_ZN_4 17310.41 17310.41 85.71 1.294 1.294 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 24.00 24.00 0.00719 41.03 0.00916 0.087 0.00
DATACENTER_BOT_ZN_6 8121.36 8121.36 224.33 0.479 0.479 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 27.00 27.00 0.00700 32.36 0.00914 0.016 0.00
DATACENTER_MID_ZN_6 77545.36 77545.36 2141.97 4.571 4.571 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 27.00 27.00 0.00700 32.36 0.00914 0.156 0.00
DATACENTER_TOP_ZN_6 7841.87 7841.87 216.61 0.462 0.462 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:50:00 27.00 27.00 0.00709 40.77 0.00916 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370656.32 370656.32 472.97 21.850 21.850 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:00:00 27.00 27.00 0.00704 33.17 0.00914 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 24.82 0.00607 6.30 0.00607 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 22.20 0.00607 6.30 0.00607 1.078 0.00
CORE_MID 227226.30 227226.30 91.03 9.817 10.778 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 6.30 0.00607 10.778 0.00
CORE_TOP 47714.70 47714.70 19.12 2.076 2.076 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 6.30 0.00607 1.078 0.00
PERIMETER_BOT_ZN_3 4834.10 4834.10 15.42 0.210 0.210 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 6.30 0.00607 0.135 0.00
PERIMETER_BOT_ZN_2 3530.14 3530.14 17.48 0.153 0.153 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00792 6.30 0.00607 0.087 0.00
PERIMETER_BOT_ZN_1 6442.73 6442.73 20.56 0.281 0.281 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00793 6.30 0.00607 0.135 0.00
PERIMETER_BOT_ZN_4 2058.38 2058.38 10.19 0.089 0.089 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00784 6.30 0.00607 0.087 0.00
PERIMETER_MID_ZN_3 113748.48 113748.48 362.93 4.968 4.968 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00796 6.30 0.00607 1.353 0.00
PERIMETER_MID_ZN_2 75150.00 75150.00 372.08 3.283 3.283 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00796 6.30 0.00607 0.872 0.00
PERIMETER_MID_ZN_1 113749.24 113749.24 362.93 4.968 4.968 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00796 6.30 0.00607 1.353 0.00
PERIMETER_MID_ZN_4 68927.78 68927.78 341.27 3.010 3.010 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 6.30 0.00607 0.872 0.00
PERIMETER_TOP_ZN_3 14094.40 14094.40 44.97 0.616 0.616 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00797 6.30 0.00607 0.135 0.00
PERIMETER_TOP_ZN_2 9249.67 9249.67 45.80 0.404 0.404 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00797 6.30 0.00607 0.087 0.00
PERIMETER_TOP_ZN_1 14094.53 14094.53 44.97 0.616 0.616 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00797 6.30 0.00607 0.135 0.00
PERIMETER_TOP_ZN_4 8791.11 8791.11 43.53 0.384 0.384 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00796 6.30 0.00607 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 26.92 0.00700 6.30 0.00607 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 24.60 0.00661 6.30 0.00607 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 23.76 0.00614 6.30 0.00607 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00700 6.30 0.00607 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.88 9.88 1.81 1.81 9.8823 2.2883 9.8823 0.2316 0.3000
VAV_MID WITH REHEAT 94.67 94.67 27.01 27.01 94.6735 27.0067 94.6735 0.2853 0.3000
VAV_TOP WITH REHEAT 10.93 10.93 4.10 4.10 10.9300 4.0967 10.9300 0.3748 0.3000
CAV_BAS 5.23 5.23 1.20 1.20 5.2349 5.2349 5.2349 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.85 21.85 0.34 0.34 21.8502 21.8500 21.8502 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.48 0.48 0.02 0.02 0.4787 0.4787 0.4787 1.0000 1.0000
AIRLOOP DATACENTER MID 4.57 4.57 0.16 0.16 4.5708 4.5708 4.5708 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.46 0.46 0.02 0.02 0.4623 0.4623 0.4623 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 15895.818 15895.818 1.619582 0.00034772 443.654   1/21 00:10:00   1/21 00:10:00 15895.82 15895.82 1.619582 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 0.00 0.00 15923.10 15923.10
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 385891.269 385891.269 16.165937 0.00844138 12933.894 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 385891.27 385891.27 16.165937 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 227226.30 0.00 386845.19 386845.19
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 68090.669 68090.669 2.076052 0.00148949 2652.230 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 68090.67 68090.67 2.076052 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 47714.70 0.00 68235.62 68235.62
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 6894.617 6894.617 0.209982 0.00015082 268.748 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6894.62 6894.62 0.209982 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00790352 49.8127 4834.10 0.00 6909.29 6909.29
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 5036.283 5036.283 0.153484 0.00011017 196.229 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5036.28 5036.28 0.153484 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00791529 49.8859 3530.14 0.00 5047.00 5047.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 9195.497 9195.497 0.280510 0.00020115 358.058 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9195.50 9195.50 0.280510 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00793473 50.0068 6442.73 0.00 9215.07 9215.07
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 3348.226 3348.226 0.131460 0.00007324 114.887 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3348.23 3348.23 0.131460 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00783945 49.4139 2058.38 0.00 3356.21 3356.21
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 162503.793 162503.793 4.968054 0.00355477 6318.672 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 162503.79 162503.79 4.968054 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00795529 50.1349 113748.48 0.00 162849.85 162849.85
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 107364.328 107364.328 3.282560 0.00234860 4174.486 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 107364.33 107364.33 3.282560 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00795616 50.1403 75150.00 0.00 107592.96 107592.96
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 162504.863 162504.863 4.968087 0.00355480 6318.713 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 162504.86 162504.86 4.968087 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00795529 50.1349 113749.24 0.00 162850.92 162850.92
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 98464.271 98464.271 3.009756 0.00215391 3829.009 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 98464.27 98464.27 3.009756 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00794681 50.0821 68927.78 0.00 98673.95 98673.95
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 20140.347 20140.347 0.616053 0.00044057 782.855 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20140.35 20140.35 0.616053 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00796696 50.2074 14094.40 0.00 20183.24 20183.24
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 13217.648 13217.648 0.404318 0.00028914 513.756 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13217.65 13217.65 0.404318 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00796694 50.2073 9249.67 0.00 13245.80 13245.80
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 20140.542 20140.542 0.616059 0.00044057 782.863 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20140.54 20140.54 0.616059 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00796696 50.2074 14094.53 0.00 20183.44 20183.44
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 12561.743 12561.743 0.384213 0.00027479 488.296 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12561.74 12561.74 0.384213 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00796245 50.1794 8791.11 0.00 12588.50 12588.50
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 218315.705 -999.000 9.882291 0.00624380 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 218315.70 199901.80 9.882291 27.70 16.75 0.00771067 10.99 9.55 0.00700000 42.00 0.00915790 22.26 20.5469 24.00 0.00733580 38.5670 132050.41 0.00 222777.76 214078.05
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 20359.493 20359.493 2.964687 0.00044536 470.719 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20359.49 20359.49 2.964687 6.98 6.91 0.00630674 12.80 11.37 0.00800000 6.30 0.00607234 6.30 68.4895 21.43 0.00720369 44.2627 16865.35 0.00 21999.34 21999.34
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2136229.560 -999.000 94.673532 0.06109589 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 2136229.56 1945377.52 94.673532 27.96 16.88 0.00776672 10.99 9.55 0.00700000 42.00 0.00915790 22.26 21.4484 24.00 0.00737457 38.7687 1235521.82 0.00 2179190.24 2079989.09
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 77376.414 77376.414 28.402060 0.00169261 1834.952 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 22:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 77376.41 77376.41 28.402060 10.49 8.90 0.00661594 12.80 11.37 0.00800000 6.30 0.00607234 6.30 71.4948 20.23 0.00796993 52.6522 309872.88 0.00 89572.19 89572.19
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 235019.640 -999.000 10.930038 0.00672153 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 235019.64 216038.31 10.930038 27.33 16.58 0.00766510 11.00 9.55 0.00700000 41.90 0.00915774 22.24 18.5772 24.00 0.00732350 38.5033 145875.65 0.00 239984.98 231896.69
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 8430.752 8430.752 3.279011 0.00018442 200.130 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 06:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8430.75 8430.75 3.279011 10.62 9.14 0.00678212 12.80 11.37 0.00800000 6.30 0.00607234 6.30 61.9242 19.48 0.00791021 54.7582 39144.30 0.00 9785.35 9785.35
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 120546.622 -999.000 5.234902 0.00344762 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 12:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 120546.62 107667.04 5.234902 28.27 17.14 0.00794981 11.38 9.72 0.00700000 40.74 0.00915579 21.91 22.9261 24.00 0.00753611 39.6078 64236.36 0.00 122924.16 115927.85
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 238062.159 238062.159 5.234902 0.00520762 7778.914 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 238062.16 238062.16 5.234902 1.44 1.44 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 22.9261 24.82 0.00607234 30.4449 0.00 0.00 192205.02 192205.02
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 450094.941 280281.164 21.850204 0.01102280 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00 404281.19 400564.20 -999.0 28.66 16.55 0.00707508 12.80 10.34 0.00700000 42.00 0.00915790 22.26 -999.0000 27.00 0.00704228 30.9985 370194.87 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9846.565 6123.692 0.478704 0.00024114 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 8842.82 8670.12 -999.0 28.44 16.54 0.00715943 12.80 10.34 0.00700000 41.03 0.00915628 21.99 -999.0000 27.00 0.00709070 31.2074 7969.42 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 94174.851 58517.999 4.570817 0.00230634 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:50:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 84601.44 82873.14 -999.0 28.45 16.55 0.00716703 12.80 10.34 0.00700000 40.77 0.00915585 21.92 -999.0000 27.00 0.00709512 31.2269 75991.87 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9515.623 5915.749 0.462284 0.00023304 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:50:00 8546.78 8377.28 -999.0 28.45 16.54 0.00716201 12.80 10.34 0.00700000 41.03 0.00915628 21.99 -999.0000 27.00 0.00709219 31.2140 7840.43 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 450094.941 450094.941 21.850204 0.01102280 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 450094.94 450094.94 21.850204 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 1.5487 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9846.565 9846.565 0.478704 0.00024114 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9846.57 9846.57 0.478704 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.2656 26.92 0.00700000 30.9571 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 94174.851 94174.851 4.570817 0.00230634 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 94174.85 94174.85 4.570817 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.4200 24.60 0.00661303 33.5823 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9515.623 9515.623 0.462284 0.00023304 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9515.62 9515.62 0.462284 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3815 23.76 0.00614020 32.8135 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 13450.693 13450.693 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 13450.69 13450.69 21.850204 0.10 0.10 0.00698563 40.00 20.89 0.00800000 6.30 0.00607234 6.30 1.5487 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 621.366 621.366 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 621.37 621.37 0.478704 0.21 0.21 0.00696971 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.2656 26.92 0.00700000 30.9571 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6213.663 6213.663 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6213.66 6213.66 4.570817 0.22 0.22 0.00659454 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.4200 24.60 0.00661303 33.5823 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 621.366 621.366 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 621.37 621.37 0.462284 0.21 0.21 0.00613791 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3815 23.76 0.00614020 32.8135 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 15895.818 15895.818 1.619582 0.00034772 443.654 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 1.0855 1.107353   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 15895.82 15895.82 1.0000 1.90104186 1.619582 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.34768600 60.00 48.89 11.11 0.000 15895.82 6.30 0.00607234 6.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.4125 0.00 0.00 15923.10 15923.10 1.90104186 12.80 11.60 0.00800000 33059.8 21.01 14.86 0.00800000 41435.8
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 385891.269 385891.269 16.165937 0.00844138 12933.894 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 26.3521 26.882409 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 385891.27 385891.27 1.0000 18.97534216 16.165937 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 8.44052113 60.00 48.89 11.11 0.000 385891.27 6.30 0.00607234 6.30 0.00000000 0.0000 20.88 0.00800000 21.00 0.00800000 50.4125 227226.30 0.00 386845.19 386845.19 18.97534216 12.80 11.60 0.00800000 33059.8 32.79 18.95 0.00800000 53446.6
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 68090.669 68090.669 2.076052 0.00148949 2652.230 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 4.6498 4.743412 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 68090.67 68090.67 1.0000 2.43683973 2.076052 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.48933332 60.00 48.89 11.11 0.000 68090.67 6.30 0.00607234 6.30 0.00000000 0.0000 20.92 0.00800000 21.00 0.00800000 50.4125 47714.70 0.00 68235.62 68235.62 2.43683973 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61061.5
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 6894.617 6894.617 0.209982 0.00015082 268.748 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 0.4708 0.480301 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6894.62 6894.62 1.0000 0.24647386 0.209982 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.15080455 60.00 48.89 11.11 0.000 6894.62 6.30 0.00607234 6.30 0.00000000 0.0000 20.86 0.00790352 21.00 0.00790352 49.8127 4834.10 0.00 6909.29 6909.29 0.24647386 12.80 11.60 0.00800000 33059.8 40.29 21.27 0.00800000 61092.4
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 5036.283 5036.283 0.153484 0.00011017 196.229 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 0.3439 0.350843 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5036.28 5036.28 1.0000 0.18015705 0.153484 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.11015760 60.00 48.89 11.11 0.000 5036.28 6.30 0.00607234 6.30 0.00000000 0.0000 20.86 0.00791529 21.00 0.00791529 49.8859 3530.14 0.00 5047.00 5047.00 0.18015705 12.80 11.60 0.00800000 33059.8 40.27 21.26 0.00800000 61074.3
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 9195.497 9195.497 0.280510 0.00020115 358.058 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 0.6279 0.640588 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9195.50 9195.50 1.0000 0.32925859 0.280510 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.20113124 60.00 48.89 11.11 0.000 9195.50 6.30 0.00607234 6.30 0.00000000 0.0000 20.92 0.00793473 21.00 0.00793473 50.0068 6442.73 0.00 9215.07 9215.07 0.32925859 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61047.2
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 3348.226 3348.226 0.131460 0.00007324 114.887 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 0.2286 0.233248 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3348.23 3348.23 1.0000 0.15430576 0.131460 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.07323506 60.00 48.89 11.11 0.000 3348.23 6.30 0.00607234 6.30 0.00000000 0.0000 20.82 0.00783945 21.00 0.00783945 49.4139 2058.38 0.00 3356.21 3356.21 0.15430576 12.80 11.60 0.00800000 33059.8 34.13 19.38 0.00800000 54810.2
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 162503.793 162503.793 4.968054 0.00355477 6318.672 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 11.0972 11.320529 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 162503.79 162503.79 1.0000 5.83142984 4.968054 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 3.55441237 60.00 48.89 11.11 0.000 162503.79 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00795529 21.00 0.00795529 50.1349 113748.48 0.00 162849.85 162849.85 5.83142984 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.1
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 107364.328 107364.328 3.282560 0.00234860 4174.486 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 7.3318 7.479339 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 107364.33 107364.33 1.0000 3.85302131 3.282560 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 2.34835807 60.00 48.89 11.11 0.000 107364.33 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00795616 21.00 0.00795616 50.1403 75150.00 0.00 107592.96 107592.96 3.85302131 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60984.1
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 162504.863 162504.863 4.968087 0.00355480 6318.713 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 11.0973 11.320604 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 162504.86 162504.86 1.0000 5.83146798 4.968087 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 3.55443578 60.00 48.89 11.11 0.000 162504.86 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00795529 21.00 0.00795529 50.1349 113749.24 0.00 162850.92 162850.92 5.83146798 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.1
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 98464.271 98464.271 3.009756 0.00215391 3829.009 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 6.7240 6.859333 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 98464.27 98464.27 1.0000 3.53280786 3.009756 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 2.15368895 60.00 48.89 11.11 0.000 98464.27 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00794681 21.00 0.00794681 50.0821 68927.78 0.00 98673.95 98673.95 3.53280786 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60990.6
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 20140.347 20140.347 0.616053 0.00044057 782.855 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 1.3754 1.403040 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20140.35 20140.35 1.0000 0.72311415 0.616053 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.44052572 60.00 48.89 11.11 0.000 20140.35 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00796696 21.00 0.00796696 50.2074 14094.40 0.00 20183.24 20183.24 0.72311415 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.4
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 13217.648 13217.648 0.404318 0.00028914 513.756 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 0.9026 0.920783 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13217.65 13217.65 1.0000 0.47458282 0.404318 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.28910692 60.00 48.89 11.11 0.000 13217.65 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00796694 21.00 0.00796694 50.2073 9249.67 0.00 13245.80 13245.80 0.47458282 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.2
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 20140.542 20140.542 0.616059 0.00044057 782.863 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 1.3754 1.403054 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20140.54 20140.54 1.0000 0.72312113 0.616059 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.44052998 60.00 48.89 11.11 0.000 20140.54 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00796696 21.00 0.00796696 50.2074 14094.53 0.00 20183.44 20183.44 0.72312113 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 12561.743 12561.743 0.384213 0.00027479 488.296 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 0.8578 0.875091 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12561.74 12561.74 1.0000 0.45098397 0.384213 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.27476045 60.00 48.89 11.11 0.000 12561.74 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00796245 21.00 0.00796245 50.1794 8791.11 0.00 12588.50 12588.50 0.45098397 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60973.2
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 218315.705 -999.000 9.882291 0.00624380 -999.000 -999.0000 1.00000 1.00000 1019.1738 1004.8586 1.1738 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.882291 11.59968968   4197.9300 999.8980 77.50093990 15.00 6.67 8.33 2710111.53 8.0556 8.055599 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 Sensible 218315.70 199901.80 1.0000 11.59968968 9.882291 27.70 16.75 0.00771067 47517.3 10.99 9.55 0.00700000 28696.5 6.24316459 6.67 15.00 8.33 21355.105 196960.60 42.00 0.00915790 22.26 2.03050000 20.5469 24.00 0.00733580 24.00 0.00733580 38.5670 132050.41 0.00 222777.76 214078.05 11.59968968 27.70 17.02 0.00771067 47517.3 9.59 9.58 0.00741291 28311.8
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 20359.493 20359.493 2.964687 0.00044536 470.719 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.882291 11.59968968   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 1.3903 1.418307 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20359.49 20359.49 1.0000 3.47990690 2.964687 6.98 6.91 0.00630674 22866.1 12.80 11.37 0.00800000 33059.8 0.44531903 60.00 48.89 11.11 0.000 20359.49 6.30 0.00607234 6.30 2.03050000 68.4895 8.45 0.00681622 21.43 0.00720369 44.2627 16865.35 0.00 21999.34 21999.34 3.47990690 2.80 2.80 0.00630674 18619.2 9.02 8.08 0.00630674 24941.0
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2136229.560 -999.000 94.673532 0.06109589 -999.000 -999.0000 1.00000 1.00000 1019.2779 1004.8586 1.1738 VAV_MID WITH REHEAT FAN Fan:VariableVolume 94.673532 111.12641513   4197.9300 999.8980 77.50093990 15.00 6.67 8.33 2710111.53 78.8244 78.824415 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 2136229.56 1945377.52 1.0000 111.12641513 94.673532 27.96 16.88 0.00776672 47920.1 10.99 9.55 0.00700000 28696.7 61.08966259 6.67 15.00 8.33 204584.461 1931645.10 42.00 0.00915790 22.26 20.30600000 21.4484 24.00 0.00737457 24.00 0.00737457 38.7687 1235521.82 0.00 2179190.24 2079989.09 111.12641513 27.96 17.15 0.00776672 47920.1 9.59 9.58 0.00741230 28310.1
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 77376.414 77376.414 28.402060 0.00169261 1834.952 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_MID WITH REHEAT FAN Fan:VariableVolume 94.673532 111.12641513   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 5.2839 5.390286 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 22:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 77376.41 77376.41 1.0000 33.33792454 28.402060 10.49 8.90 0.00661594 27216.1 12.80 11.37 0.00800000 33059.8 1.69243855 60.00 48.89 11.11 0.000 77376.41 6.30 0.00607234 6.30 20.30600000 71.4948 21.00 0.00797935 20.23 0.00796993 52.6522 309872.88 0.00 89572.19 89572.19 33.33792454 2.80 2.80 0.00661594 19394.1 5.44 5.44 0.00661594 22080.9
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 235019.640 -999.000 10.930038 0.00672153 -999.000 -999.0000 1.00000 1.00000 1019.0890 1004.8586 1.1738 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.930038 12.82952005   4197.9300 999.8980 77.50093990 15.00 6.67 8.33 2710111.53 8.6720 8.671955 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 Sensible 235019.64 216038.31 1.0000 12.82952005 10.930038 27.33 16.58 0.00766510 47024.8 11.00 9.55 0.00700000 28706.1 6.72084628 6.67 15.00 8.33 23493.730 211525.91 41.90 0.00915774 22.24 2.03050000 18.5772 24.00 0.00732350 24.00 0.00732350 38.5033 145875.65 0.00 239984.98 231896.69 12.82952005 27.33 16.85 0.00766510 47024.8 9.60 9.59 0.00741480 28319.1
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 8430.752 8430.752 3.279011 0.00018442 200.130 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.930038 12.82952005   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 0.5757 0.587313 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 06:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8430.75 8430.75 1.0000 3.84885601 3.279011 10.62 9.14 0.00678212 27767.1 12.80 11.37 0.00800000 33059.8 0.18440412 60.00 48.89 11.11 0.000 8430.75 6.30 0.00607234 6.30 2.03050000 61.9242 17.65 0.00793645 19.48 0.00791021 54.7582 39144.30 0.00 9785.35 9785.35 3.84885601 2.80 2.80 0.00678212 19810.5 5.30 5.30 0.00678212 22352.9
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 120546.622 -999.000 5.234902 0.00344762 -999.000 -999.0000 1.00000 1.00000 1019.6183 1004.8586 1.1738 CAV_BAS FAN Fan:ConstantVolume 5.234902 6.14465200   4197.9300 999.8980 77.50093990 15.00 6.67 8.33 2710111.53 4.4480 4.448032 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 12:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 120546.62 107667.04 1.0000 6.14465200 5.234902 28.27 17.14 0.00794981 48711.1 11.38 9.72 0.00700000 29093.0 3.44726645 6.67 15.00 8.33 8876.585 111670.04 40.74 0.00915579 21.91 1.20015641 22.9261 24.00 0.00753611 24.00 0.00753611 39.6078 64236.36 0.00 122924.16 115927.85 6.14465200 28.27 17.41 0.00794981 48711.1 9.77 9.75 0.00749782 28706.1
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 238062.159 238062.159 5.234902 0.00520762 7778.914 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 CAV_BAS FAN Fan:ConstantVolume 5.234902 6.14465200   4197.9300 999.8980 31.39793395 48.89 60.00 11.11 1464368.31 16.2570 16.584165 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 238062.16 238062.16 1.0000 6.14465200 5.234902 1.44 1.44 0.00607234 16654.2 40.00 20.89 0.00800000 60796.0 5.20708511 60.00 48.89 11.11 0.000 238062.16 6.30 0.00607234 6.30 1.20015641 22.9261 0.00 0.00607234 24.82 0.00607234 30.4449 0.00 0.00 192205.02 192205.02 6.14465200 12.80 9.56 0.00607234 28193.0 43.58 20.85 0.00607234 59473.1
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 450094.941 280281.164 21.850204 0.01102280 -999.000 -999.0000 -999.00000 -999.00000 1017.9922 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00 Sensible 404281.19 400564.20 0.8982 -999.0 -999.0 28.66 16.55 0.00707508 46870.3 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 404281.19 42.00 0.00915790 22.26 0.33839277 -999.0000 27.00 0.00704228 27.00 0.00704228 30.9985 370194.87 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9846.565 6123.692 0.478704 0.00024114 -999.000 -999.0000 -999.00000 -999.00000 1018.1490 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 Sensible 8842.82 8670.12 0.8981 -999.0 -999.0 28.44 16.54 0.00715943 46858.8 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8842.82 41.03 0.00915628 21.99 0.01563234 -999.0000 27.00 0.00709070 27.00 0.00709070 31.2074 7969.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 94174.851 58517.999 4.570817 0.00230634 -999.000 -999.0000 -999.00000 -999.00000 1018.1632 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:50:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:50:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 Sensible 84601.44 82873.14 0.8983 -999.0 -999.0 28.45 16.55 0.00716703 46892.1 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 84601.44 40.77 0.00915585 21.92 0.15632344 -999.0000 27.00 0.00709512 27.00 0.00709512 31.2269 75991.87 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9515.623 5915.749 0.462284 0.00023304 -999.000 -999.0000 -999.00000 -999.00000 1018.1538 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:50:00 Sensible 8546.78 8377.28 0.8982 -999.0 -999.0 28.45 16.54 0.00716201 46873.2 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8546.78 41.03 0.00915628 21.99 0.01563234 -999.0000 27.00 0.00709219 27.00 0.00709219 31.2140 7840.43 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 450094.941 450094.941 21.850204 0.01102280 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 450094.94 450094.94 1.0000 25.64745175 21.850204 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 450094.94 6.30 0.00607234 6.30 0.33839277 1.5487 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9846.565 9846.565 0.478704 0.00024114 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9846.57 9846.57 1.0000 0.56189565 0.478704 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9846.57 6.30 0.00607234 6.30 0.01563234 3.2656 0.00 0.00700000 26.92 0.00700000 30.9571 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 94174.851 94174.851 4.570817 0.00230634 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 94174.85 94174.85 1.0000 5.36515879 4.570817 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 94174.85 6.30 0.00607234 6.30 0.15632344 3.4200 0.00 0.00661303 24.60 0.00661303 33.5823 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9515.623 9515.623 0.462284 0.00023304 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9515.62 9515.62 1.0000 0.54262233 0.462284 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9515.62 6.30 0.00607234 6.30 0.01563234 3.3815 0.00 0.00614020 23.76 0.00614020 32.8135 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 13450.693 13450.693 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.850204 25.64745175   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 13450.69 13450.69 1.0000 25.64745175 21.850204 0.10 0.10 0.00698563 17570.0 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 13450.69 6.30 0.00607234 6.30 0.33839277 1.5487 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 621.366 621.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.478704 0.56189565   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 621.37 621.37 1.0000 0.56189565 0.478704 0.21 0.21 0.00696971 17640.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 621.37 6.30 0.00607234 6.30 0.01563234 3.2656 0.00 0.00700000 26.92 0.00700000 30.9571 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6213.663 6213.663 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.570817 5.36515879   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6213.66 6213.66 1.0000 5.36515879 4.570817 0.22 0.22 0.00659454 16711.7 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6213.66 6.30 0.00607234 6.30 0.15632344 3.4200 0.00 0.00661303 24.60 0.00661303 33.5823 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 621.366 621.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.462284 0.54262233   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 621.37 621.37 1.0000 0.54262233 0.462284 0.21 0.21 0.00613791 15567.0 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 621.37 6.30 0.00607234 6.30 0.01563234 3.3815 0.00 0.00614020 23.76 0.00614020 32.8135 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 5212.67 1746.17 1743.00
CORE_BOTTOM 5219.83 35.50 17.33
CORE_MID 4425.67 608.33 28.83
CORE_TOP 4146.17 1244.83 54.50
PERIMETER_BOT_ZN_3 4371.50 1199.00 270.33
PERIMETER_BOT_ZN_2 4635.00 1045.50 370.00
PERIMETER_BOT_ZN_1 5128.83 848.00 440.33
PERIMETER_BOT_ZN_4 5327.50 969.00 769.33
PERIMETER_MID_ZN_3 3957.67 1986.00 404.83
PERIMETER_MID_ZN_2 3627.00 1491.33 493.17
PERIMETER_MID_ZN_1 4918.33 1106.50 508.17
PERIMETER_MID_ZN_4 4417.00 1625.50 559.33
PERIMETER_TOP_ZN_3 4045.83 2204.67 635.33
PERIMETER_TOP_ZN_2 4328.83 1865.67 627.33
PERIMETER_TOP_ZN_1 4767.17 1376.83 608.83
PERIMETER_TOP_ZN_4 4378.17 1866.67 684.67
DATACENTER_BOT_ZN_6 5943.00 1210.50 1210.50
DATACENTER_MID_ZN_6 5934.67 368.00 368.00
DATACENTER_TOP_ZN_6 5867.17 633.33 603.17
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 74.50 0.00 6.00
CORE_BOTTOM 0.00 9.83 0.00 0.67
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.67 2.17 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 119.67 0.00 46.00
PERIMETER_BOT_ZN_2 0.00 147.83 0.00 77.17
PERIMETER_BOT_ZN_1 0.00 191.50 0.00 96.83
PERIMETER_BOT_ZN_4 0.00 463.67 0.00 152.33
PERIMETER_MID_ZN_3 0.17 100.67 0.00 40.67
PERIMETER_MID_ZN_2 0.17 168.67 0.00 80.00
PERIMETER_MID_ZN_1 0.00 174.67 0.00 92.17
PERIMETER_MID_ZN_4 0.00 248.00 0.00 82.50
PERIMETER_TOP_ZN_3 2.83 135.17 0.17 51.00
PERIMETER_TOP_ZN_2 2.00 199.67 0.00 84.50
PERIMETER_TOP_ZN_1 0.50 194.50 0.00 89.00
PERIMETER_TOP_ZN_4 0.50 266.50 0.00 87.50
DATACENTER_BOT_ZN_6 0.00 494.17 0.00 382.50
DATACENTER_MID_ZN_6 0.00 360.17 0.00 301.33
DATACENTER_TOP_ZN_6 0.00 353.50 0.00 289.00
DATACENTER_BASEMENT_ZN_6 0.00 1292.33 0.00 924.17
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 3.17 1890.33 0.17 1161.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.531 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.488 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.462 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.448 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.614 0.017 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 0.741 0.017 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 0.862 0.017 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 1.124 0.017 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.661 0.039 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 0.841 0.042 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 0.999 0.039 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 0.931 0.041 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.642 0.049 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 0.843 0.051 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 0.949 0.049 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 0.880 0.051 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.665 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.613 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 60.99 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.86 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.79 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.20 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1010.73 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 23250801.09 0.00 23250801.09 0.00 23250801.09 37848132.68 3378.57 5381.43 0.00 599.70
CORE_BOTTOM 23931718.07 0.00 23931718.07 0.00 23931718.07 33990283.35 6772.40 781.93 1205.67 1261.69
CORE_MID 0.22E+09 0.00 0.22E+09 0.00 0.22E+09 0.34E+09 6830.97 1040.96 888.07 898.68
CORE_TOP 20940632.95 0.00 20940632.95 0.00 20940632.95 33990283.35 7115.30 1244.71 399.99 898.36
PERIMETER_BOT_ZN_3 3670594.02 0.00 3670594.02 135485.55 3806079.58 4267819.30 5134.02 636.11 2989.88 1261.69
PERIMETER_BOT_ZN_2 2769580.99 0.00 2769580.99 90323.64 2859904.63 2750345.05 4263.53 752.67 3743.80 1261.69
PERIMETER_BOT_ZN_1 4928008.65 0.00 4928008.65 135485.55 5063494.20 4267912.63 3392.48 789.84 4577.68 1261.69
PERIMETER_BOT_ZN_4 4309393.27 0.00 4309393.27 90323.64 4399716.91 2750345.05 2498.86 693.35 5567.79 1261.69
PERIMETER_MID_ZN_3 37341382.62 0.00 37341382.62 317743.67 37659126.28 42678193.03 4868.14 927.14 2964.72 898.68
PERIMETER_MID_ZN_2 29975747.15 0.00 29975747.15 211828.97 30187576.11 27503450.52 3828.30 1066.37 3865.33 1727.60
PERIMETER_MID_ZN_1 54400479.17 0.00 54400479.17 317743.67 54718222.84 42679126.28 3484.80 806.49 4468.71 898.68
PERIMETER_MID_ZN_4 33732027.16 0.00 33732027.16 211828.97 33943856.13 27503450.52 3483.95 1016.79 4259.26 898.68
PERIMETER_TOP_ZN_3 3666406.55 0.00 3666406.55 394502.81 4060909.36 4267819.30 4434.85 1258.90 3066.26 898.36
PERIMETER_TOP_ZN_2 3027163.52 0.00 3027163.52 263001.69 3290165.21 2750345.05 3577.20 1239.40 3943.39 898.36
PERIMETER_TOP_ZN_1 5217903.67 0.00 5217903.67 394502.81 5612406.48 4267912.63 3332.98 1035.47 4391.55 898.36
PERIMETER_TOP_ZN_4 3230320.65 0.00 3230320.65 263001.69 3493322.34 2750345.05 3431.44 1153.68 4174.89 898.36
DATACENTER_BOT_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_MID_ZN_6 4929815.99 0.00 4929815.99 0.00 4929815.99 4929815.99 0.00 8760.00 0.00 2817.00
DATACENTER_TOP_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_BASEMENT_ZN_6 10671554.30 0.00 10671554.30 0.00 10671554.30 10671554.30 0.00 8760.00 0.00 2817.00
Total Facility 0.39E+10 0.00 0.39E+10 12358080.11 0.39E+10 0.50E+10 8657.03 8760.00 6126.11 3645.92


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 0.9656 0.0000 0.9656 0.0000 0.9656 1.2002 1161.27 4781.73 0.00
CORE_BOTTOM 0.8986 0.0000 0.8986 0.0000 0.8986 1.0778 4462.01 301.21 1179.77
CORE_MID 8.4955 0.0000 8.4955 0.0000 8.4955 10.7782 4421.78 639.66 881.55
CORE_TOP 0.8250 0.0000 0.8250 0.0000 0.8250 1.0778 4675.40 881.59 386.00
PERIMETER_BOT_ZN_3 0.1415 0.0000 0.1415 0.0039 0.1453 0.1353 2831.59 276.88 2834.53
PERIMETER_BOT_ZN_2 0.1100 0.0000 0.1100 0.0026 0.1126 0.0872 2032.88 315.19 3594.93
PERIMETER_BOT_ZN_1 0.1990 0.0000 0.1990 0.0039 0.2029 0.1353 1280.46 297.43 4365.11
PERIMETER_BOT_ZN_4 0.1670 0.0000 0.1670 0.0026 0.1695 0.0872 879.70 242.32 4820.98
PERIMETER_MID_ZN_3 1.5238 0.0000 1.5238 0.0091 1.5329 1.3533 2500.00 606.39 2836.60
PERIMETER_MID_ZN_2 1.2480 0.0000 1.2480 0.0062 1.2542 0.8721 1394.37 595.97 3043.65
PERIMETER_MID_ZN_1 2.3080 0.0000 2.3080 0.0091 2.3170 1.3533 1158.64 504.06 4280.30
PERIMETER_MID_ZN_4 1.3812 0.0000 1.3812 0.0060 1.3873 0.8721 1458.26 602.86 3881.88
PERIMETER_TOP_ZN_3 0.1480 0.0000 0.1480 0.0113 0.1593 0.1353 2218.24 849.48 2875.28
PERIMETER_TOP_ZN_2 0.1253 0.0000 0.1253 0.0075 0.1328 0.0872 1414.63 837.77 3690.60
PERIMETER_TOP_ZN_1 0.2193 0.0000 0.2193 0.0113 0.2305 0.1353 1048.16 747.41 4147.43
PERIMETER_TOP_ZN_4 0.1307 0.0000 0.1307 0.0075 0.1382 0.0872 1353.61 827.96 3761.43
DATACENTER_BOT_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_MID_ZN_6 0.1563 0.0000 0.1563 0.0000 0.1563 0.1563 0.00 5943.00 0.00
DATACENTER_TOP_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_BASEMENT_ZN_6 0.3384 0.0000 0.3384 0.0000 0.3384 0.3384 0.00 5943.00 0.00
Total Facility 155.4279 0.0000 155.4279 0.3545 155.7825 158.4706 5856.15 5943.00 5196.88


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 54572612.23 0.00 54572612.23 48026705.38 2270.79 3.15 6486.07 1261.69
VAV_MID WITH REHEAT 0.51E+09 0.00 0.51E+09 0.48E+09 2759.54 1.75 5998.71 898.68
VAV_TOP WITH REHEAT 49713370.53 0.00 49713370.53 48026705.38 2783.02 1.76 5975.22 898.36
CAV_BAS 32034309.85 0.00 32034309.85 37848132.68 3378.57 0.00 5381.43 599.70
AIRLOOP DATACENTER BASEMENT 14702971.99 0.00 14702971.99 10671554.30 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER BOT 679216.39 0.00 679216.39 492981.60 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER MID 6792163.95 0.00 6792163.95 4929815.99 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER TOP 679216.39 0.00 679216.39 492981.60 0.00 0.00 8760.00 2817.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 2.0888 0.0000 2.0888 1.5229 684.56 1.80 5256.64
VAV_MID WITH REHEAT 20.6048 0.0000 20.6048 15.2292 819.24 0.94 5122.82
VAV_TOP WITH REHEAT 1.9953 0.0000 1.9953 1.5229 840.11 0.94 5101.95
CAV_BAS 1.3304 0.0000 1.3304 1.2002 1161.27 0.00 4781.73
AIRLOOP DATACENTER BASEMENT 0.4662 0.0000 0.4662 0.3384 0.00 0.00 5943.00
AIRLOOP DATACENTER BOT 0.0215 0.0000 0.0215 0.0156 0.00 0.00 5943.00
AIRLOOP DATACENTER MID 0.2154 0.0000 0.2154 0.1563 0.00 0.00 5943.00
AIRLOOP DATACENTER TOP 0.0215 0.0000 0.0215 0.0156 0.00 0.00 5943.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 621.07 0.00 0.00 0.00 0.00 5931.13 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 728.82 0.00 0.00 0.00 0.00 5317.93 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 356.16 0.00 0.00 0.00 0.00 5668.78 0.00 0.00 0.00
CAV_BAS 0.00 5381.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.5835 0.0000 0.0000 0.0000 0.0000 2.3198 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 26.3490 0.0000 0.0000 0.0000 0.0000 23.4027 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.4985 0.0000 0.0000 0.0000 0.0000 2.3024 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6538 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4662 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2154 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1519
Defaulted Fields 1187
Fields with Defaults 3885
Autosized Fields 333
Autosizable Fields 411
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 29363.03 328248.80 01-JAN-04:00 1885837.91 07-AUG-15:20
Electricity:Building 16485.48 215816.90 07-MAY-17:10 949844.51 29-DEC-17:00
Electricity:Zone:BASEMENT 546.85 14054.16 01-JAN-00:10 24196.91 02-JAN-08:10
Electricity:SpaceType:GENERAL 16485.48 215816.90 07-MAY-17:10 949844.51 29-DEC-17:00
InteriorLights:Electricity 1809.08 8560.74 01-JAN-09:20 173230.55 11-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 122.46 596.61 01-JAN-00:10 10739.37 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 1809.08 8560.74 01-JAN-09:20 173230.55 11-OCT-07:10
LightsWired:InteriorLights:Electricity 1809.08 8560.74 01-JAN-09:20 173230.55 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 122.46 596.61 01-JAN-00:10 10739.37 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 1809.08 8560.74 01-JAN-09:20 173230.55 11-OCT-07:10
Electricity:Zone:CORE_BOTTOM 399.59 4989.04 01-JAN-00:10 26851.34 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 109.97 535.80 01-JAN-00:10 9644.71 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 109.97 535.80 01-JAN-00:10 9644.71 02-JAN-08:10
Electricity:Zone:CORE_MID 3995.87 49890.19 01-JAN-00:10 268512.72 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1099.74 5358.02 01-JAN-00:10 96447.09 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1099.74 5358.02 01-JAN-00:10 96447.09 02-JAN-08:10
Electricity:Zone:CORE_TOP 399.59 4989.02 01-JAN-00:10 26851.27 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 109.97 535.80 01-JAN-00:10 9644.71 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 109.97 535.80 01-JAN-00:10 9644.71 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 44.30 591.18 12-MAR-17:10 3228.25 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 7.93 32.01 01-JAN-09:20 1067.70 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 7.93 32.01 01-JAN-09:20 1067.70 11-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 28.52 380.98 23-APR-17:10 2078.24 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.09 20.63 01-JAN-07:50 685.90 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.09 20.63 01-JAN-07:50 685.90 27-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_1 44.21 591.19 12-MAR-17:10 3222.30 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 7.85 32.01 01-JAN-08:00 1061.72 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 7.85 32.01 01-JAN-08:00 1061.72 11-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 28.52 380.98 12-MAR-17:10 2084.05 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.08 20.63 01-JAN-09:20 691.71 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.08 20.63 01-JAN-09:20 691.71 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 442.83 5911.80 12-MAR-17:10 32266.12 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 79.18 320.10 01-JAN-09:10 10660.60 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 79.18 320.10 01-JAN-09:10 10660.60 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 285.17 3809.79 23-APR-17:10 20758.13 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 50.82 206.28 01-JAN-07:50 6834.71 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 50.82 206.28 01-JAN-07:50 6834.71 27-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_1 442.06 5911.90 12-MAR-17:10 32206.31 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 78.40 320.10 01-JAN-08:00 10600.46 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 78.40 320.10 01-JAN-08:00 10600.46 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 285.12 3809.77 12-MAR-17:10 20817.25 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 50.77 206.28 01-JAN-09:10 6893.92 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 50.77 206.28 01-JAN-09:10 6893.92 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 44.28 591.18 12-MAR-17:10 3226.31 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 7.92 32.01 01-JAN-09:10 1065.76 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 7.92 32.01 01-JAN-09:10 1065.76 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 28.52 380.98 23-APR-17:10 2075.65 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.08 20.63 01-JAN-07:50 683.31 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.08 20.63 01-JAN-07:50 683.31 27-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_1 44.21 591.19 12-MAR-17:10 3220.32 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 7.84 32.01 01-JAN-08:00 1059.74 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 7.84 32.01 01-JAN-08:00 1059.74 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 28.51 380.98 12-MAR-17:10 2081.54 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.08 20.63 01-JAN-09:10 689.20 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.08 20.63 01-JAN-09:10 689.20 11-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7529.54 95076.35 01-JAN-00:10 382660.56 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 34.68 168.22 01-JAN-00:10 3028.04 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 34.68 168.22 01-JAN-00:10 3028.04 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 155.65 1957.19 01-JAN-00:10 7948.87 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 1.77 8.58 01-JAN-00:10 154.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 1.77 8.58 01-JAN-00:10 154.45 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1556.49 19571.87 01-JAN-00:10 79488.71 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 17.69 85.81 01-JAN-00:10 1544.49 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 17.69 85.81 01-JAN-00:10 1544.49 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 155.65 1957.19 01-JAN-00:10 7948.87 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 1.77 8.58 01-JAN-00:10 154.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 1.77 8.58 01-JAN-00:10 154.45 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 5755.29 7431.34 05-JAN-05:50 522220.10 22-JUN-15:40
HeatRejection:Electricity 1778.17 3845.97 05-JAN-07:00 81944.93 17-MAY-22:00
General:HeatRejection:Electricity 1778.17 3845.97 05-JAN-07:00 81944.93 17-MAY-22:00
ElectricityProduced:Facility 533.69 -0.00 16-JAN-17:30 89148.19 04-JUN-12:20
ElectricityProduced:Plant 533.69 -0.00 16-JAN-17:30 89148.19 04-JUN-12:20
Photovoltaic:ElectricityProduced 557.23 0.00 01-JAN-00:10 92858.80 04-JUN-12:20
PowerConversion:ElectricityProduced -23.54 -3710.62 04-JUN-12:20 0.00 01-JAN-00:10
Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
DCtoACInverter Ancillary:Cogeneration:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 5709.32 75853.93 01-JAN-13:20 421386.96 07-JUL-14:30
ExteriorEquipment:Electricity 1203.73 17814.45 01-JAN-00:10 73702.49 11-OCT-07:20
Transformer:ExteriorEquipment:Electricity 54.39 979.82 01-JAN-00:10 3373.89 11-OCT-07:20
ElectricityPurchased:Facility 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
ElectricityPurchased:Plant 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
Cogeneration:ElectricityPurchased 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
General:Cogeneration:ElectricityPurchased 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
ElectricityNet:Plant 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
Cogeneration:ElectricityNet 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
General:Cogeneration:ElectricityNet 28829.34 307294.31 08-JAN-10:30 1841797.10 07-AUG-16:00
Fans:Electricity 2594.14 42210.20 03-APR-21:10 257692.66 05-JUL-15:40
General:Fans:Electricity 2594.14 42210.20 03-APR-21:10 257692.66 05-JUL-15:40
ExteriorLights:Electricity 263.60 0.00 01-JAN-07:20 31088.59 01-JAN-06:10
General:ExteriorLights:Electricity 263.60 0.00 01-JAN-07:20 31088.59 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1144.44 16803.04 01-JAN-00:10 70012.65 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 4.90 31.59 01-JAN-00:10 315.94 01-JAN-07:10
Cooling:Electricity 6149.99 27268.83 03-JAN-05:50 543998.76 28-AUG-14:30
General:Cooling:Electricity 6149.99 27268.83 03-JAN-05:50 543998.76 28-AUG-14:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 83.46 0.00 12-JAN-13:10 28549.56 22-DEC-06:00
General:Humidifier:Electricity 83.46 0.00 12-JAN-13:10 28549.56 22-DEC-06:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 804.47 3485.68 15-APR-03:40 51292.27 23-OCT-13:50
General:Pumps:Electricity 804.47 3485.68 15-APR-03:40 51292.27 23-OCT-13:50
WIRED_LTG_ELECTRICITY 50.84 0.00 01-JAN-00:10 4867.78 11-OCT-07:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 665.68 7280.88 02-APR-15:00 739694.38 02-JAN-06:10
NaturalGas:Plant 665.68 7280.88 02-APR-15:00 739694.38 02-JAN-06:10
Heating:NaturalGas 56.57 0.00 01-JAN-00:10 732413.50 02-JAN-06:10
Boiler:Heating:NaturalGas 56.57 0.00 01-JAN-00:10 732413.50 02-JAN-06:10
WaterSystems:NaturalGas 609.11 7280.88 02-JAN-05:20 74436.05 20-JAN-12:30
Water Heater:WaterSystems:NaturalGas 609.11 7280.88 02-JAN-05:20 74436.05 20-JAN-12:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 35102.33 150349.90 03-JAN-05:50 3170585.43 28-AUG-14:30
PlantLoopCoolingDemand:HVAC 35102.33 150349.90 03-JAN-05:50 3170585.43 28-AUG-14:30
CoolingCoils:PlantLoopCoolingDemand 35102.33 150349.90 03-JAN-05:50 3170585.43 28-AUG-14:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 20807.50 0.00 11-MAR-00:30 0.00 12-JUN-15:30
Water:HVAC 31.05 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Humidifier:Water 31.05 0.00 12-JAN-13:10 0.00 22-DEC-06:00
General:Humidifier:Water 31.05 0.00 12-JAN-13:10 0.00 22-DEC-06:00
MainsWater:Facility 20807.50 0.00 11-MAR-00:30 0.00 12-JUN-15:30
MainsWater:HVAC 31.05 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Humidifier:MainsWater 31.05 0.00 12-JAN-13:10 0.00 22-DEC-06:00
General:Humidifier:MainsWater 31.05 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Water:Plant 20776.46 0.00 01-JAN-00:10 0.00 12-JUN-15:30
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 20776.46 0.00 01-JAN-00:10 0.00 12-JUN-15:30
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 18496.29 0.00 01-JAN-00:10 0.00 12-JUN-15:30
General:HeatRejection:Water 18496.29 0.00 01-JAN-00:10 0.00 12-JUN-15:30
HeatRejection:MainsWater 18496.29 0.00 01-JAN-00:10 0.00 12-JUN-15:30
General:HeatRejection:MainsWater 18496.29 0.00 01-JAN-00:10 0.00 12-JUN-15:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 124529.80 213882.31 03-JAN-05:50 12511926.71 22-JUN-15:40
EnergyTransfer:Building 22612.29 89846.31 03-JAN-02:30 1719505.21 07-AUG-15:20
EnergyTransfer:Zone:BASEMENT 702.78 0.00 01-JAN-00:10 76649.75 13-NOV-06:20
Heating:EnergyTransfer 42.41 0.00 03-JAN-22:10 438596.01 02-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.26 0.00 01-JAN-00:10 33031.73 10-JUN-16:10
General:Heating:EnergyTransfer 42.41 0.00 03-JAN-22:10 438596.01 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.26 0.00 01-JAN-00:10 33031.73 10-JUN-16:10
Cooling:EnergyTransfer 22569.88 89469.30 03-JAN-05:50 1719505.21 07-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 698.52 0.00 01-JAN-00:10 76649.75 13-NOV-06:20
General:Cooling:EnergyTransfer 22569.88 89469.30 03-JAN-05:50 1719505.21 07-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 698.52 0.00 01-JAN-00:10 76649.75 13-NOV-06:20
EnergyTransfer:Zone:CORE_BOTTOM 703.48 0.00 01-JAN-00:10 60398.55 07-AUG-07:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 703.48 0.00 01-JAN-00:10 60398.55 07-AUG-07:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 703.48 0.00 01-JAN-00:10 60398.55 07-AUG-07:20
EnergyTransfer:Zone:CORE_MID 5316.70 0.00 01-JAN-00:10 426311.18 30-MAY-10:00
Heating:EnergyTransfer:Zone:CORE_MID 0.04 0.00 01-JAN-00:10 62987.17 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.04 0.00 01-JAN-00:10 62987.17 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 5316.66 0.00 01-JAN-00:10 426311.18 30-MAY-10:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 5316.66 0.00 01-JAN-00:10 426311.18 30-MAY-10:00
EnergyTransfer:Zone:CORE_TOP 545.87 0.00 01-JAN-00:10 66240.33 02-JAN-05:20
Heating:EnergyTransfer:Zone:CORE_TOP 0.62 0.00 01-JAN-00:10 66240.33 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.62 0.00 01-JAN-00:10 66240.33 02-JAN-05:20
Cooling:EnergyTransfer:Zone:CORE_TOP 545.25 0.00 01-JAN-00:10 55409.30 12-JUN-05:10
General:Cooling:EnergyTransfer:Zone:CORE_TOP 545.25 0.00 01-JAN-00:10 55409.30 12-JUN-05:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 119.83 0.00 01-JAN-00:10 14534.53 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 119.83 0.00 01-JAN-00:10 14534.53 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 119.83 0.00 01-JAN-00:10 14534.53 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 92.75 0.00 01-JAN-00:10 13998.79 12-JUN-09:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 92.75 0.00 01-JAN-00:10 13998.79 12-JUN-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 92.75 0.00 01-JAN-00:10 13998.79 12-JUN-09:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 161.79 0.00 01-JAN-00:10 18444.60 02-OCT-13:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 1338.64 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 1338.64 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 161.79 0.00 01-JAN-00:10 18444.60 02-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 161.79 0.00 01-JAN-00:10 18444.60 02-OCT-13:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 140.06 0.00 01-JAN-00:10 18271.84 27-APR-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 140.06 0.00 01-JAN-00:10 18271.84 27-APR-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 140.06 0.00 01-JAN-00:10 18271.84 27-APR-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1025.87 0.00 01-JAN-00:10 143856.02 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 3.97 0.00 01-JAN-00:10 82894.54 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 3.97 0.00 01-JAN-00:10 82894.54 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1021.90 0.00 01-JAN-00:10 143856.02 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1021.90 0.00 01-JAN-00:10 143856.02 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 867.01 0.00 01-JAN-00:10 148450.15 12-JUN-10:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.26 0.00 01-JAN-00:10 50339.62 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.26 0.00 01-JAN-00:10 50339.62 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 865.75 0.00 01-JAN-00:10 148450.15 12-JUN-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 865.75 0.00 01-JAN-00:10 148450.15 12-JUN-10:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1490.07 0.00 01-JAN-00:10 185846.82 02-OCT-13:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.57 0.00 01-JAN-00:10 53608.64 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.57 0.00 01-JAN-00:10 53608.64 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1489.50 0.00 01-JAN-00:10 185846.82 02-OCT-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1489.50 0.00 01-JAN-00:10 185846.82 02-OCT-13:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 950.78 0.00 01-JAN-00:10 160737.12 06-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.67 0.00 01-JAN-00:10 38759.67 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.67 0.00 01-JAN-00:10 38759.67 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 950.11 0.00 01-JAN-00:10 160737.12 06-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 950.11 0.00 01-JAN-00:10 160737.12 06-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 108.50 0.00 01-JAN-00:10 16306.48 02-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.21 0.00 01-JAN-00:10 16306.48 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.21 0.00 01-JAN-00:10 16306.48 02-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 106.29 0.00 01-JAN-00:10 15857.38 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 106.29 0.00 01-JAN-00:10 15857.38 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 92.59 0.00 01-JAN-00:10 15297.07 12-JUN-09:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.82 0.00 01-JAN-00:10 10279.67 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.82 0.00 01-JAN-00:10 10279.67 02-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 91.77 0.00 01-JAN-00:10 15297.07 12-JUN-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 91.77 0.00 01-JAN-00:10 15297.07 12-JUN-09:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 150.92 0.00 01-JAN-00:10 20312.88 02-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.64 0.00 01-JAN-00:10 13497.37 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.64 0.00 01-JAN-00:10 13497.37 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 150.28 0.00 01-JAN-00:10 20312.88 02-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 150.28 0.00 01-JAN-00:10 20312.88 02-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 98.01 0.00 01-JAN-00:10 17293.33 06-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.59 0.00 01-JAN-00:10 9066.54 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.59 0.00 01-JAN-00:10 9066.54 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 97.41 0.00 01-JAN-00:10 17293.33 06-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 97.41 0.00 01-JAN-00:10 17293.33 06-JUN-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 126.62 0.00 01-JAN-00:10 19674.19 05-JUL-05:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.80 0.00 01-JAN-00:10 4157.43 24-DEC-11:00
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.80 0.00 01-JAN-00:10 4157.43 24-DEC-11:00
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 125.82 0.00 01-JAN-00:10 19674.19 05-JUL-05:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 125.82 0.00 01-JAN-00:10 19674.19 05-JUL-05:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 1007.13 0.00 01-JAN-00:10 143255.86 12-JUN-14:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 18.22 0.00 01-JAN-00:10 43792.23 03-JAN-15:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 18.22 0.00 01-JAN-00:10 43792.23 03-JAN-15:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 988.91 0.00 01-JAN-00:10 143255.86 12-JUN-14:20
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 988.91 0.00 01-JAN-00:10 143255.86 12-JUN-14:20
EnergyTransfer:Zone:TOPFLOOR_PLENUM 167.91 0.00 01-JAN-00:10 33454.17 12-JUN-13:50
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 7.41 0.00 01-JAN-00:10 21617.17 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 7.41 0.00 01-JAN-00:10 21617.17 02-JAN-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 160.50 0.00 01-JAN-00:10 33454.17 12-JUN-13:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 160.50 0.00 01-JAN-00:10 33454.17 12-JUN-13:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.08 995.64 03-JAN-08:00 7851.08 17-APR-01:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.08 995.64 03-JAN-08:00 7851.08 17-APR-01:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.08 995.64 03-JAN-08:00 7851.08 17-APR-01:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1308.03 10.52 03-JAN-02:30 73298.52 16-APR-21:00
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.19 0.00 01-JAN-15:30 2747.50 01-JAN-13:20
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.19 0.00 01-JAN-15:30 2747.50 01-JAN-13:20
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1307.84 0.00 01-JAN-00:10 73298.52 16-APR-21:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1307.84 0.00 01-JAN-00:10 73298.52 16-APR-21:00
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 128.29 0.19 21-JAN-04:10 7512.13 16-APR-21:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.15 0.00 02-JAN-14:00 346.77 01-JAN-14:20
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.15 0.00 02-JAN-14:00 346.77 01-JAN-14:20
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 128.14 0.00 01-JAN-00:10 7512.13 16-APR-21:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 128.14 0.00 01-JAN-00:10 7512.13 16-APR-21:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7165.22 88067.66 08-JAN-06:00 369082.22 15-AUG-24:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7165.22 88067.66 08-JAN-06:00 369082.22 15-AUG-24:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7165.22 88067.66 08-JAN-06:00 369082.22 15-AUG-24:00
PlantLoopHeatingDemand:Facility 343.28 0.00 01-JAN-00:10 627157.58 02-JAN-06:10
PlantLoopHeatingDemand:Plant 293.17 0.00 01-JAN-00:10 40156.20 18-JAN-12:20
WaterSystems:PlantLoopHeatingDemand 293.17 0.00 01-JAN-00:10 40156.20 18-JAN-12:20
General:WaterSystems:PlantLoopHeatingDemand 293.17 0.00 01-JAN-00:10 40156.20 18-JAN-12:20
EnergyTransfer:HVAC 32175.10 123081.08 03-JAN-05:50 2998908.24 28-AUG-14:30
HeatingCoils:EnergyTransfer 50.10 0.00 01-JAN-00:10 622328.09 02-JAN-06:10
PlantLoopHeatingDemand:HVAC 50.10 0.00 01-JAN-00:10 622328.09 02-JAN-06:10
HeatingCoils:PlantLoopHeatingDemand 50.10 0.00 01-JAN-00:10 622328.09 02-JAN-06:10
CoolingCoils:EnergyTransfer 32125.00 123081.08 03-JAN-05:50 2998908.24 28-AUG-14:30
EnergyTransfer:Plant 69742.40 0.00 01-JAN-00:10 8181653.64 22-JUN-15:40
LoopToLoop:EnergyTransfer 22194.39 0.00 01-JAN-00:10 2589266.82 22-JUN-15:40
WaterSystems:EnergyTransfer 293.17 0.00 01-JAN-00:10 40156.20 18-JAN-12:20
WaterUse:WaterSystems:EnergyTransfer 293.17 0.00 01-JAN-00:10 40156.20 18-JAN-12:20
Boilers:EnergyTransfer 49.33 0.00 01-JAN-00:10 620565.01 02-JAN-06:10
Chillers:EnergyTransfer 22016.42 0.00 01-JAN-00:10 2590713.46 22-JUN-15:40
HeatRejection:EnergyTransfer 25189.08 0.00 01-JAN-00:10 2982062.49 22-JUN-15:40
General:HeatRejection:EnergyTransfer 25189.08 0.00 01-JAN-00:10 2982062.49 22-JUN-15:40
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.257 -698.518 0.000 0.000 92.677 122.456 424.397 0.000 0.000 0.000 54.731 0.000 0.000 0.000 0.000 -0.007
CORE_BOTTOM 0.000 0.000 0.000 -703.482 0.000 0.000 83.413 109.974 289.614 0.000 0.000 0.000 220.481 0.000 0.000 0.000 0.000 -0.003
CORE_MID 0.000 0.000 0.038 -5316.650 0.000 0.000 836.782 1099.740 2896.128 0.000 0.000 0.000 483.962 0.000 0.000 0.000 0.000 -0.006
CORE_TOP 0.000 0.000 0.619 -545.251 0.000 0.000 84.505 109.974 289.613 0.000 0.000 0.000 60.541 0.000 0.000 0.000 0.000 -0.008
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -119.826 0.000 0.000 10.531 7.931 36.365 51.870 0.000 0.610 40.470 0.000 -27.602 0.000 -0.349 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -92.752 0.000 0.000 6.762 5.088 23.435 61.175 0.000 0.404 13.124 0.000 -16.999 0.000 -0.238 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.001 -161.791 0.000 0.000 10.480 7.848 36.366 110.169 0.000 0.600 23.852 0.000 -27.137 0.000 -0.387 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -140.064 0.000 0.000 6.739 5.085 23.435 59.672 0.000 0.381 66.616 0.000 -21.576 0.000 -0.287 0.000
PERIMETER_MID_ZN_3 0.000 0.000 3.970 -1021.892 0.000 0.000 107.236 79.177 363.654 534.366 0.000 14.061 172.839 0.000 -246.449 0.000 -6.961 -0.001
PERIMETER_MID_ZN_2 0.000 0.000 1.263 -865.739 0.000 0.000 49.887 50.821 234.352 609.491 0.000 8.972 78.835 0.000 -162.602 0.000 -5.278 -0.001
PERIMETER_MID_ZN_1 0.000 0.000 0.568 -1489.483 0.000 0.000 105.101 78.396 363.660 1102.895 0.000 13.670 99.396 0.000 -265.317 0.000 -8.885 -0.007
PERIMETER_MID_ZN_4 0.000 0.000 0.668 -950.106 0.000 0.000 68.333 50.773 234.351 616.034 0.000 8.920 158.744 0.000 -182.223 0.000 -5.493 -0.006
PERIMETER_TOP_ZN_3 0.000 0.000 2.208 -106.287 0.000 0.000 10.817 7.917 36.365 53.117 0.000 1.701 18.088 0.000 -23.141 0.000 -0.786 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 0.819 -91.766 0.000 0.000 6.852 5.082 23.435 61.081 0.000 1.098 9.368 0.000 -15.370 0.000 -0.599 -0.002
PERIMETER_TOP_ZN_1 0.000 0.000 0.638 -150.282 0.000 0.000 10.568 7.839 36.366 109.906 0.000 1.654 9.577 0.000 -25.229 0.000 -1.036 -0.001
PERIMETER_TOP_ZN_4 0.000 0.000 0.592 -97.413 0.000 0.000 6.882 5.077 23.435 61.316 0.000 1.084 17.009 0.000 -17.343 0.000 -0.639 -0.000
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -142.085 0.000 0.000 0.941 1.769 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -14.506
DATACENTER_MID_ZN_6 0.000 0.000 0.190 -1307.840 0.000 0.000 9.432 17.689 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -258.276
DATACENTER_TOP_ZN_6 0.000 0.000 0.153 -128.135 0.000 0.000 0.944 1.769 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -28.611
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7165.233 0.000 0.000 19.441 34.679 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -383.744
GROUNDFLOOR_PLENUM 0.802 -125.822 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.106 124.705 0.000 0.000 0.000 -0.791 -0.000
MIDFLOOR_PLENUM 18.217 -988.907 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 20.146 963.792 0.000 0.000 0.000 -13.249 -0.000
TOPFLOOR_PLENUM 7.408 -160.497 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.075 152.343 0.000 0.000 0.000 -1.330 -0.000
Total Facility 26.427 -1275.226 15.982 -21294.596 0.000 0.000 1528.320 1809.081 14676.396 3431.091 0.000 76.482 2768.475 0.000 -1030.988 0.000 -46.308 -685.179


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 23-JAN-05:11 0.00 0.00 0.00 -102603.94 0.00 0.00 0.00 598.35 13457.54 0.00 0.00 0.00 88548.05 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 30-OCT-04:13 0.00 0.00 0.00 -94851.34 0.00 0.00 0.00 537.36 5937.65 0.00 0.00 0.00 88376.34 0.00 -0.00 0.00 0.00 0.00
CORE_MID 17-OCT-04:13 0.00 0.00 0.00 -837591.09 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 772841.26 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 03-JUL-05:04 0.00 0.00 0.00 -85760.28 0.00 0.00 796.51 537.36 7647.36 0.00 0.00 0.00 76779.04 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 04-JUL-17:01 0.00 0.00 0.00 -23634.26 0.00 0.00 0.00 32.01 559.17 6227.80 0.00 113.38 16701.90 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 30-APR-09:41 0.00 0.00 0.00 -19282.63 0.00 0.00 20.73 20.63 464.11 12660.93 0.00 16.84 6099.38 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 12-NOV-13:31 0.00 0.00 0.00 -24956.58 0.00 0.00 32.77 32.01 720.19 17305.18 0.00 0.00 6883.96 0.00 -0.00 0.00 -17.53 0.00
PERIMETER_BOT_ZN_4 30-APR-16:21 0.00 0.00 0.00 -28492.81 0.00 0.00 13.57 20.63 464.11 13700.40 0.00 112.34 14181.77 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 30-APR-16:21 0.00 0.00 0.00 -225406.95 0.00 0.00 401.00 320.10 7201.84 45849.45 0.00 5838.73 165795.83 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 30-APR-09:41 0.00 0.00 0.00 -209131.05 0.00 0.00 197.13 206.28 4641.14 125422.87 0.00 323.31 78340.33 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 29-OCT-13:01 0.00 0.00 0.00 -252820.76 0.00 0.00 321.45 320.10 7201.95 183271.37 0.00 0.00 61708.74 0.00 -0.00 0.00 -2.86 0.00
PERIMETER_MID_ZN_4 30-APR-16:21 0.00 0.00 0.00 -245006.35 0.00 0.00 159.31 206.28 4641.11 137378.33 0.00 2799.50 99821.82 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 28-MAY-16:41 0.00 0.00 0.00 -25745.54 0.00 0.00 33.05 32.01 720.18 6173.45 0.00 1395.76 17391.09 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 29-MAY-09:22 0.00 0.00 0.00 -20626.64 0.00 0.00 16.79 20.63 464.11 12612.81 0.00 723.80 6788.49 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 09-OCT-13:31 0.00 0.00 0.00 -28707.12 0.00 0.00 29.73 32.01 720.19 15728.69 0.00 39.36 12157.14 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 28-MAY-16:01 0.00 0.00 0.00 -25036.85 0.00 0.00 12.64 20.63 464.11 15035.86 0.00 902.52 8601.09 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 17-APR-01:13 0.00 0.00 0.00 -7852.79 0.00 0.00 0.00 8.58 7794.42 0.00 0.00 0.00 49.79 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 16-APR-21:02 0.00 0.00 0.00 -73441.66 0.00 0.00 0.00 85.81 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4588.37
DATACENTER_TOP_ZN_6 16-APR-21:32 0.00 0.00 0.00 -7515.37 0.00 0.00 0.00 8.58 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -287.63
DATACENTER_BASEMENT_ZN_6 15-AUG-23:57 0.00 0.00 0.00 -369283.97 0.00 0.00 0.00 168.22 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10516.77
GROUNDFLOOR_PLENUM 30-MAY-05:15 0.00 -22720.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.90 22701.44 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 12-JUN-05:15 0.00 -188344.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 985.30 187359.32 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 12-JUN-13:50 0.00 -33456.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 363.94 33092.17 0.00 -0.00 0.00 0.00 0.00
Total Facility 07-AUG-05:01 0.00 -115972.47 0.00 -2192748.27 0.00 0.00 15278.87 10251.90 616289.16 8906.37 0.00 1062.30 1657077.53 0.00 -145.38 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 10-JUN-16:01 0.00 0.00 34970.92 0.00 0.00 0.00 520.12 596.61 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -49545.21
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 02-JAN-06:03 0.00 0.00 251923.09 0.00 0.00 0.00 11358.47 5373.60 76473.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -345128.77
CORE_TOP 02-JAN-05:11 0.00 0.00 72305.61 0.00 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -78780.59
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 02-JAN-06:03 0.00 0.00 4432.55 0.00 0.00 0.00 141.38 67.47 960.26 0.00 0.00 0.00 0.00 0.00 -4187.27 0.00 0.00 -1414.39
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 02-JAN-05:11 0.00 0.00 160061.72 0.00 0.00 0.00 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 -34308.64 0.00 0.00 -133883.40
PERIMETER_MID_ZN_2 02-JAN-05:11 0.00 0.00 115683.37 0.00 0.00 0.00 0.00 434.81 4804.68 0.00 0.00 0.00 0.00 0.00 -23323.60 0.00 0.00 -97599.26
PERIMETER_MID_ZN_1 02-JAN-05:11 0.00 0.00 149676.97 0.00 0.00 0.00 0.00 674.72 7455.72 0.00 0.00 0.00 0.00 0.00 -37701.61 0.00 0.00 -120105.82
PERIMETER_MID_ZN_4 02-JAN-05:11 0.00 0.00 107225.16 0.00 0.00 0.00 0.00 434.81 4804.65 0.00 0.00 0.00 0.00 0.00 -24876.69 0.00 0.00 -87587.93
PERIMETER_TOP_ZN_3 02-JAN-05:11 0.00 0.00 20177.02 0.00 0.00 0.00 0.00 67.47 745.56 0.00 0.00 0.00 0.00 0.00 -2763.54 0.00 0.00 -18226.51
PERIMETER_TOP_ZN_2 02-JAN-05:11 0.00 0.00 14387.73 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -1864.51 0.00 0.00 -13047.17
PERIMETER_TOP_ZN_1 02-JAN-05:11 0.00 0.00 20083.72 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -2917.17 0.00 0.00 -17979.60
PERIMETER_TOP_ZN_4 02-JAN-05:11 0.00 0.00 14903.12 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -1952.21 0.00 0.00 -13474.85
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 01-JAN-13:20 0.00 0.00 2747.68 0.00 0.00 0.00 53.49 85.81 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -22373.03
DATACENTER_TOP_ZN_6 01-JAN-14:15 0.00 0.00 350.63 0.00 0.00 0.00 6.87 8.58 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2314.69
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 11-DEC-05:12 11614.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -11614.04
MIDFLOOR_PLENUM 04-JUN-15:41 73269.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8751.94 0.00 0.00 -0.00 0.00 0.00 -82021.69
TOPFLOOR_PLENUM 02-JAN-06:03 23405.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -23405.04
Total Facility 02-JAN-06:03 -230107.19 258479.62 861160.46 -258479.62 0.00 0.00 20445.03 10251.90 261414.96 0.00 0.00 0.00 0.00 0.00 -151572.83 0.00 0.00 -771592.33



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.8077 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.8823 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 104.6318 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 94.6735 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.0697 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.9300 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.2349 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.2349 0.2293 1.0000 Not calculated 1.2002 0.2293    
AIRLOOP DATACENTER BASEMENT 21.8500 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.8502 0.0155 1.0000 Not calculated 0.3384 0.0155    
AIRLOOP DATACENTER BOT 0.4787 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4787 0.0327 1.0000 Not calculated 0.0156 0.0327    
AIRLOOP DATACENTER MID 4.5708 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5708 0.0342 1.0000 Not calculated 0.1563 0.0342    
AIRLOOP DATACENTER TOP 0.4623 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4623 0.0338 1.0000 Not calculated 0.0156 0.0338    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.4038 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2883 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 52.3159 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.8363 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.5348 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2828 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.2349 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.2349 1.0000 1.0000 Not calculated 1.2002 0.2293    
AIRLOOP DATACENTER BASEMENT 21.8500 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.8500 1.0000 1.0000 Not calculated 0.3384 0.0155    
AIRLOOP DATACENTER BOT 0.4787 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4787 1.0000 1.0000 Not calculated 0.0156 0.0327    
AIRLOOP DATACENTER MID 4.5708 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5708 1.0000 1.0000 Not calculated 0.1563 0.0342    
AIRLOOP DATACENTER TOP 0.4623 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4623 1.0000 1.0000 Not calculated 0.0156 0.0338    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.2349 5.2349 5.2349 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.8469 5.8469 1.6196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 55.9375 55.9375 16.1659 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7291 5.7291 1.6156 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2923 1.2923 0.2029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0228 1.0228 0.1309 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3043 1.3043 0.2035 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3414 1.3414 0.1315 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.9910 12.9910 2.0266 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.8195 10.8195 1.3092 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.9870 12.9870 2.0260 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.8968 11.8968 1.3086 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4613 1.4613 0.2031 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1278 1.1278 0.1308 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4577 1.4577 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2938 1.2938 0.1307 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4787 0.4787 0.4787 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5708 4.5708 4.5708 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4623 0.4623 0.4623 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.8500 21.8500 21.8500 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.8077 9.8823 10.8077 2.2883 0.0000 1.0000
VAV_MID WITH REHEAT 104.6318 94.6735 104.6318 22.8363 0.0000 1.0000
VAV_TOP WITH REHEAT 11.0697 10.9300 11.0697 2.2828 0.0000 1.0000
CAV_BAS 5.2349 5.2349 5.2349 5.2349 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.8500 21.8502 21.8500 21.8500 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4787 0.4787 0.4787 0.4787 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5708 4.5708 4.5708 4.5708 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4623 0.4623 0.4623 0.4623 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.2349 5.2349 5.2349 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9234 2.9234 1.6196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 27.9687 27.9687 16.1659 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8646 2.8646 1.6156 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6461 0.6461 0.2029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5114 0.5114 0.1309 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6521 0.6521 0.2035 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6707 0.6707 0.1315 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.4955 6.4955 2.0266 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4098 5.4098 1.3092 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.4935 6.4935 2.0260 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9484 5.9484 1.3086 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7306 0.7306 0.2031 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5639 0.5639 0.1308 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7288 0.7288 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6469 0.6469 0.1307 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4787 0.4787 0.4787 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5708 4.5708 4.5708 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4623 0.4623 0.4623 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.8500 21.8500 21.8500 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.4038 2.2883 2.2883 2.2883 0.0000 1.0000
VAV_MID WITH REHEAT 52.3159 22.8363 22.8363 22.8363 0.0000 1.0000
VAV_TOP WITH REHEAT 5.5348 2.2828 2.2828 2.2828 0.0000 1.0000
CAV_BAS 5.2349 5.2349 5.2349 5.2349 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.8500 21.8500 21.8500 21.8500 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4787 0.4787 0.4787 0.4787 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5708 4.5708 4.5708 4.5708 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4623 0.4623 0.4623 0.4623 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.17
Number of hours cooling loads not met 1161.83
Number of hours not met 1162.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 56.57 732413.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 6149.99 543998.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 1809.08 173230.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 263.60 31088.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.39 3373.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1144.44 70012.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 4.90 315.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2594.14 257692.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 804.47 51292.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1778.17 81944.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 83.46 28549.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 609.11 74436.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- DCtoACInverter Ancillary 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 29363.03
Natural Gas 0.00 665.68
Additional 0.00 0.00
Total 14676.40 30028.71


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 557.23
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 39.06
Space Heating 0.00
Space Cooling 132.77
Fans (All) 56.00
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 633.91
Subtotal 633.91


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.22
Service Water Heating 13.15
Miscellaneous (All) 14.37
Subtotal 14.37


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.02
Space Heating 0.19
Space Cooling 20.48
Fans (All) 8.64
Service Water Heating 2.03
Receptacle Equipment 48.87
Miscellaneous 13.76


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
PV_SCH 8760. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2069. 8760.
LTG_SCH_DATACENTER 1840. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 947. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7552.17 1207.83 0.00 0.00 0.00
CORE_BOTTOM 8697.17 62.83 0.00 0.00 0.00
CORE_MID 8759.67 0.33 0.00 0.00 0.00
CORE_TOP 8752.00 8.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8470.33 289.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8382.83 377.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8307.67 452.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7157.50 1602.50 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8375.83 384.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8113.50 646.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8033.50 726.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7706.67 1053.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8259.33 500.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8051.17 708.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 7977.50 782.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7694.83 1065.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6631.33 2128.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6686.50 2073.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6697.33 2062.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7283.50 1476.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8390.83 369.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8658.17 101.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 7919.83 840.17 0.00 0.00 0.00
Min 6631.33 0.33 0.00 0.00 0.00
Max 8759.67 2128.67 0.00 0.00 0.00
Average 7937.36 822.64 0.00 0.00 0.00
Sum 182559.17 18920.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 365334.17 3281.83 0.00 0.00 0.00
CORE_BOTTOM 330710.00 103.00 0.00 0.00 0.00
CORE_MID 330811.00 2.00 0.00 0.00 0.00
CORE_TOP 330780.00 33.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1499.17 768.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1493.67 774.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1492.50 775.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 82043.17 21351.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 365334.17 21351.83 0.00 0.00 0.00
Average 79157.07 1177.84 0.00 0.00 0.00
Sum 1820612.67 27090.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 5289.83 3470.17 0.00 0.00 0.00
CORE_BOTTOM 7139.33 1620.67 0.00 0.00 0.00
CORE_MID 7749.50 1010.50 0.00 0.00 0.00
CORE_TOP 7431.67 1328.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 6789.50 1970.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 6745.17 2014.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 6497.00 2263.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 6176.67 2583.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 6809.83 1950.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 6640.67 2119.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 6495.50 2264.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 6541.33 2218.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 6809.00 1951.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 6674.83 2085.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 6544.83 2215.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 6583.17 2176.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7421.83 1338.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7451.50 1308.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7442.50 1317.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7541.17 1218.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 5021.50 3738.50 0.00 0.00 0.00
MIDFLOOR_PLENUM 4718.33 4041.67 0.00 0.00 0.00
TOPFLOOR_PLENUM 4487.50 4272.50 0.00 0.00 0.00
Min 4487.50 1010.50 0.00 0.00 0.00
Max 7749.50 4272.50 0.00 0.00 0.00
Average 6565.31 2194.69 0.00 0.00 0.00
Sum 151002.17 50477.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 320524.17 48091.83 0.00 0.00 0.00
CORE_BOTTOM 327677.17 3135.83 0.00 0.00 0.00
CORE_MID 328919.00 1894.00 0.00 0.00 0.00
CORE_TOP 328185.00 2628.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38919.50 5.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18349.17 4.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38919.83 5.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24905.50 3.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38914.17 10.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24902.33 6.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38917.17 7.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24903.83 5.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1768.83 499.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1763.50 504.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1769.50 498.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 87365.00 16030.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 328919.00 48091.83 0.00 0.00 0.00
Average 77146.59 3188.32 0.00 0.00 0.00
Sum 1774371.67 73331.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:56:50

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.504025E+11 102604.11 23-JAN-05:11 6.33 5.49 0.566692E+10 7499.24 04-JAN-10:39 6.33 5.49
February 0.462001E+11 100320.84 21-FEB-05:11 11.87 10.80 0.513957E+10 7499.25 02-FEB-10:20 11.87 10.80
March 0.542780E+11 97884.50 06-MAR-05:12 15.13 13.89 0.613333E+10 7499.20 27-MAR-09:20 23.77 16.23
April 0.529602E+11 98320.06 30-APR-19:37 32.00 17.30 0.545128E+10 7499.21 04-APR-09:20 32.00 17.30
May 0.559944E+11 94568.73 29-MAY-09:20 34.40 21.35 0.590275E+10 7499.05 05-MAY-09:20 34.40 21.35
June 0.588711E+11 91092.95 04-JUN-22:58 33.80 20.76 0.588385E+10 7499.06 07-JUN-09:20 37.90 20.70
July 0.633598E+11 85111.30 04-JUL-19:39 40.00 24.33 0.547615E+10 7498.93 27-JUL-13:20 30.70 26.49
August 0.725480E+11 81907.29 29-AUG-03:02 27.75 24.39 0.613957E+10 7498.92 16-AUG-13:20 27.75 24.39
September 0.616567E+11 81649.01 26-SEP-03:02 25.65 21.91 0.545466E+10 7498.93 08-SEP-13:20 25.65 21.91
October 0.641569E+11 94943.73 29-OCT-13:47 29.27 17.86 0.567315E+10 7499.06 24-OCT-09:20 29.27 17.86
November 0.610831E+11 100819.02 24-NOV-05:12 10.47 9.34 0.561679E+10 7499.13 16-NOV-10:20 10.47 9.34
December 0.570113E+11 98897.67 18-DEC-05:12 11.27 8.23 0.547264E+10 7499.13 13-DEC-10:20 11.27 8.23
                     
Annual Sum or Average 0.698522E+12         0.680107E+11        
Minimum of Months 0.462001E+11 81649.01   6.33 5.49 0.513957E+10 7498.92   6.33 5.49
Maximum of Months 0.725480E+11 102604.11   40.00 24.39 0.613957E+10 7499.25   37.90 26.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.369041E+11 87913.53 02-JAN-05:11 6.47 6.24 0.507540E+10 6734.82 04-JAN-10:39 14.27 11.27
February 0.407295E+11 93854.92 21-FEB-05:11 11.87 10.80 0.460519E+10 6734.82 02-FEB-10:39 11.87 10.80
March 0.590180E+11 91173.97 06-MAR-05:13 15.13 13.89 0.549851E+10 6734.82 27-MAR-09:20 23.77 16.23
April 0.681119E+11 86521.39 03-APR-05:05 22.60 18.05 0.488034E+10 6734.81 04-APR-09:20 27.13 18.13
May 0.651332E+11 83015.70 30-MAY-05:03 30.25 21.57 0.528268E+10 6734.69 08-MAY-13:20 30.25 21.57
June 0.664179E+11 84465.80 12-JUN-05:05 34.12 19.12 0.526720E+10 6734.75 05-JUN-13:20 34.12 19.12
July 0.688445E+11 85807.67 31-JUL-05:05 29.03 26.75 0.489618E+10 6734.68 18-JUL-09:20 29.03 26.75
August 0.773782E+11 86081.98 28-AUG-05:06 29.10 27.38 0.549839E+10 6735.55 07-AUG-09:09 29.10 27.38
September 0.586763E+11 85830.49 05-SEP-05:04 26.20 25.15 0.487988E+10 6734.68 05-SEP-09:20 26.90 25.33
October 0.605992E+11 94880.30 30-OCT-04:13 16.40 14.90 0.507784E+10 6734.76 24-OCT-09:20 16.40 14.90
November 0.537398E+11 94797.09 20-NOV-05:11 12.73 11.55 0.503176E+10 6734.78 16-NOV-10:20 12.73 11.55
December 0.479298E+11 93928.67 26-DEC-05:12 10.17 8.84 0.490196E+10 6734.79 18-DEC-10:20 10.17 8.84
                     
Annual Sum or Average 0.703482E+12         0.608953E+11        
Minimum of Months 0.369041E+11 83015.70   6.47 6.24 0.460519E+10 6734.68   10.17 8.84
Maximum of Months 0.773782E+11 94880.30   34.12 27.38 0.549851E+10 6735.55   34.12 27.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.252598E+11 75038.83 27-JAN-06:02 11.07 9.85 0.494340E+10 6734.75 06-JAN-10:20 11.07 9.85
February 0.292596E+11 80386.35 27-FEB-05:12 11.13 10.43 0.457560E+10 6734.80 02-FEB-10:39 11.13 10.43
March 0.439520E+11 82428.36 08-MAR-05:12 15.77 13.75 0.549361E+10 6734.81 27-MAR-09:20 23.77 16.23
April 0.502458E+11 81064.16 11-APR-04:12 18.13 13.57 0.487406E+10 6734.81 04-APR-09:20 18.13 13.57
May 0.570509E+11 71098.18 30-MAY-05:02 30.25 21.57 0.527778E+10 6734.80 01-MAY-09:20 30.25 21.57
June 0.550967E+11 73949.88 12-JUN-05:02 34.12 19.12 0.526418E+10 6734.76 05-JUN-13:20 34.12 19.12
July 0.535299E+11 71016.28 19-JUL-05:03 26.00 25.06 0.488901E+10 6734.73 06-JUL-09:20 26.00 25.06
August 0.545220E+11 73759.70 21-AUG-05:03 25.50 25.24 0.549288E+10 6734.71 21-AUG-13:20 29.43 27.58
September 0.481491E+11 71335.14 29-SEP-03:02 24.60 20.85 0.487771E+10 6734.71 11-SEP-13:20 24.60 20.85
October 0.471579E+11 83780.46 17-OCT-04:13 19.77 16.14 0.507372E+10 6734.77 17-OCT-09:20 26.63 18.34
November 0.384223E+11 82249.60 10-NOV-05:12 16.83 15.16 0.501814E+10 6734.77 06-NOV-10:20 16.83 15.16
December 0.290201E+11 77227.17 01-DEC-06:03 11.02 8.79 0.485015E+10 6734.75 26-DEC-10:30 17.55 12.17
                     
Annual Sum or Average 0.531666E+12         0.606302E+11        
Minimum of Months 0.252598E+11 71016.28   11.02 8.79 0.457560E+10 6734.71   11.07 9.85
Maximum of Months 0.570509E+11 83780.46   34.12 25.24 0.549361E+10 6734.81   34.12 27.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.198285E+11 28605.63 26-JAN-16:40 19.13 12.86 0.456310E+10 6734.68 13-JAN-14:20 19.13 12.86
February 0.246227E+11 76497.51 23-FEB-06:02 15.05 13.57 0.444326E+10 6734.73 15-FEB-10:20 15.05 13.57
March 0.424478E+11 83415.55 14-MAR-04:12 20.77 16.48 0.547585E+10 6734.81 27-MAR-09:20 23.77 16.23
April 0.549073E+11 82952.85 10-APR-04:12 18.47 13.25 0.487772E+10 6734.80 04-APR-09:20 18.47 13.25
May 0.654691E+11 84041.82 30-MAY-05:03 30.25 21.57 0.528529E+10 6734.69 08-MAY-13:20 30.25 21.57
June 0.639613E+11 85382.66 12-JUN-05:05 34.12 19.12 0.526946E+10 6734.75 05-JUN-13:20 34.12 19.12
July 0.606619E+11 85781.44 03-JUL-05:04 29.37 24.69 0.489628E+10 6734.68 18-JUL-09:20 27.40 26.41
August 0.604707E+11 84485.06 07-AUG-05:04 29.53 24.79 0.549675E+10 6734.68 16-AUG-09:20 25.07 24.43
September 0.516252E+11 77587.33 05-SEP-05:02 26.20 25.15 0.488110E+10 6734.68 05-SEP-09:20 26.90 25.33
October 0.464993E+11 83280.55 12-OCT-04:12 21.00 20.42 0.506960E+10 6734.75 17-OCT-09:20 26.63 18.34
November 0.328091E+11 78279.98 01-NOV-05:02 15.60 12.04 0.496189E+10 6734.75 06-NOV-10:20 23.67 17.41
December 0.219509E+11 30271.07 01-DEC-16:30 21.75 14.01 0.458332E+10 6734.72 29-DEC-10:20 18.10 13.45
                     
Annual Sum or Average 0.545254E+12         0.598036E+11        
Minimum of Months 0.198285E+11 28605.63   15.05 12.04 0.444326E+10 6734.68   15.05 12.86
Maximum of Months 0.654691E+11 85781.44   34.12 25.15 0.549675E+10 6734.81   34.12 26.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.280232E+10 4214.76 26-JAN-14:10 22.35 13.84 0.600946E+09 845.62 13-JAN-14:20 22.35 13.84
February 0.389394E+10 6373.12 23-FEB-14:30 26.10 14.00 0.566009E+09 845.62 07-FEB-10:20 26.10 14.00
March 0.808296E+10 13808.15 12-MAR-16:01 31.18 19.88 0.689165E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.128314E+11 22628.60 30-APR-16:21 37.45 18.00 0.614223E+09 845.63 04-APR-09:20 37.45 18.00
May 0.152670E+11 21819.36 29-MAY-16:21 41.10 21.45 0.665790E+09 845.62 08-MAY-13:20 41.10 21.45
June 0.160084E+11 23106.86 04-JUN-16:51 41.80 22.62 0.663450E+09 845.63 05-JUN-13:20 42.30 22.45
July 0.153604E+11 23644.70 04-JUL-17:01 39.95 24.24 0.617341E+09 845.61 11-JUL-13:20 32.03 26.25
August 0.157763E+11 21548.46 27-AUG-15:01 35.43 29.15 0.692028E+09 845.85 07-AUG-09:09 35.43 29.15
September 0.111379E+11 16482.10 18-SEP-05:02 26.72 24.18 0.614182E+09 845.62 08-SEP-13:20 26.72 24.18
October 0.920555E+10 15797.72 15-OCT-15:21 32.35 19.26 0.637808E+09 845.62 23-OCT-09:20 24.30 16.37
November 0.573342E+10 7027.11 06-NOV-14:10 28.82 18.31 0.628244E+09 845.63 06-NOV-14:00 28.40 18.16
December 0.372733E+10 5153.03 26-DEC-14:10 22.68 14.39 0.599632E+09 845.62 29-DEC-14:20 19.70 14.83
                     
Annual Sum or Average 0.119827E+12         0.758882E+10        
Minimum of Months 0.280232E+10 4214.76   22.35 13.84 0.566009E+09 845.61   19.70 13.84
Maximum of Months 0.160084E+11 23644.70   41.80 29.15 0.692028E+09 845.85   42.30 29.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.241455E+10 4223.94 26-JAN-10:20 18.10 12.94 0.401715E+09 544.95 04-JAN-10:50 18.10 12.94
February 0.351226E+10 8359.43 20-FEB-10:43 21.85 12.76 0.368410E+09 544.96 02-FEB-10:00 21.85 12.76
March 0.703142E+10 16451.20 12-MAR-15:21 31.40 19.75 0.444721E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.107040E+11 19282.05 30-APR-09:41 30.90 15.93 0.396118E+09 545.40 28-APR-09:09 30.90 15.93
May 0.128537E+11 18281.15 29-MAY-09:02 34.05 21.14 0.429382E+09 545.46 04-MAY-09:09 34.05 21.14
June 0.118971E+11 18124.85 04-JUN-16:11 42.13 22.34 0.427702E+09 555.87 12-JUN-09:39 39.50 22.03
July 0.105147E+11 18794.43 04-JUL-15:41 39.65 24.77 0.397834E+09 545.07 07-JUL-09:00 36.90 24.55
August 0.101062E+11 16731.22 06-AUG-16:21 36.15 26.34 0.445798E+09 545.24 07-AUG-09:09 32.20 25.23
September 0.844967E+10 17210.96 24-SEP-10:23 31.85 25.28 0.395927E+09 544.95 08-SEP-13:20 31.85 25.28
October 0.759802E+10 17360.56 01-OCT-08:43 26.82 18.67 0.411563E+09 544.95 16-OCT-09:20 26.87 17.49
November 0.479428E+10 9055.59 05-NOV-10:32 24.63 16.65 0.405811E+09 544.96 06-NOV-14:00 28.40 18.16
December 0.287617E+10 4808.40 01-DEC-10:00 18.30 11.37 0.390104E+09 544.95 18-DEC-10:20 20.37 13.79
                     
Annual Sum or Average 0.927520E+11         0.491508E+10        
Minimum of Months 0.241455E+10 4223.94   18.10 11.37 0.368410E+09 544.95   18.10 12.76
Maximum of Months 0.128537E+11 19282.05   42.13 26.34 0.445798E+09 555.87   39.50 25.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.701415E+10 15547.10 08-JAN-13:03 20.47 12.25 0.623547E+09 845.64 04-JAN-10:50 20.47 12.25
February 0.836901E+10 23942.36 20-FEB-14:02 26.38 13.56 0.572648E+09 846.10 07-FEB-14:50 26.38 13.56
March 0.133239E+11 23749.35 12-MAR-13:22 30.95 19.20 0.690889E+09 846.08 08-MAR-14:50 30.95 19.20
April 0.161280E+11 24147.44 30-APR-15:01 37.88 18.24 0.614813E+09 845.96 06-APR-13:00 37.88 18.24
May 0.161180E+11 22196.66 29-MAY-15:41 41.30 21.63 0.665919E+09 845.90 08-MAY-13:00 41.30 21.63
June 0.159259E+11 23235.66 04-JUN-16:11 42.13 22.34 0.663453E+09 845.81 05-JUN-13:00 42.70 22.44
July 0.154450E+11 23836.59 04-JUL-16:21 39.80 24.49 0.617357E+09 845.80 06-JUL-13:00 39.90 25.44
August 0.165025E+11 22041.82 06-AUG-13:42 35.80 26.36 0.692128E+09 845.87 07-AUG-09:09 32.20 25.23
September 0.139752E+11 22460.72 17-SEP-11:43 32.98 25.91 0.614714E+09 849.71 28-SEP-13:39 35.37 22.75
October 0.162253E+11 24618.35 15-OCT-12:41 32.60 18.71 0.640933E+09 893.47 02-OCT-13:39 32.60 18.71
November 0.137958E+11 24952.97 12-NOV-13:31 28.03 16.05 0.632716E+09 860.51 13-NOV-14:09 28.20 15.99
December 0.896945E+10 22487.73 24-DEC-13:32 23.70 13.53 0.610666E+09 846.16 04-DEC-14:00 23.70 13.53
                     
Annual Sum or Average 0.161792E+12         0.763978E+10        
Minimum of Months 0.701415E+10 15547.10   20.47 12.25 0.572648E+09 845.64   20.47 12.25
Maximum of Months 0.165025E+11 24952.97   42.13 26.36 0.692128E+09 893.47   42.70 25.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.348828E+10 7103.82 31-JAN-15:50 21.15 11.24 0.403970E+09 544.95 13-JAN-10:20 21.15 11.24
February 0.538911E+10 23016.32 20-FEB-15:22 25.95 14.09 0.372518E+09 544.95 02-FEB-10:39 25.95 14.09
March 0.111682E+11 25003.12 12-MAR-16:01 31.18 19.88 0.446304E+09 544.97 30-MAR-13:50 32.05 19.26
April 0.176896E+11 28490.78 30-APR-16:21 37.45 18.00 0.397094E+09 544.96 04-APR-09:20 37.45 18.00
May 0.152554E+11 24519.03 28-MAY-16:21 42.00 19.52 0.429720E+09 544.95 08-MAY-13:20 42.00 19.52
June 0.163502E+11 27406.68 04-JUN-16:11 42.13 22.34 0.428205E+09 544.96 05-JUN-13:20 42.30 22.45
July 0.155788E+11 27327.96 04-JUL-16:21 39.80 24.49 0.398553E+09 544.95 11-JUL-09:20 28.23 25.15
August 0.184519E+11 24332.11 06-AUG-16:21 36.15 26.34 0.446830E+09 545.27 07-AUG-09:09 32.20 25.23
September 0.109236E+11 22607.28 24-SEP-15:42 34.85 25.19 0.396618E+09 544.95 08-SEP-13:20 34.85 25.19
October 0.107753E+11 24867.32 22-OCT-15:01 30.90 17.64 0.412559E+09 544.95 24-OCT-09:20 24.07 16.08
November 0.847225E+10 23801.33 12-NOV-14:52 28.20 15.74 0.408205E+09 544.97 06-NOV-14:00 28.20 15.74
December 0.652173E+10 18209.53 24-DEC-15:32 23.13 13.76 0.397198E+09 544.95 18-DEC-10:20 23.13 13.76
                     
Annual Sum or Average 0.140064E+12         0.493777E+10        
Minimum of Months 0.348828E+10 7103.82   21.15 11.24 0.372518E+09 544.95   21.15 11.24
Maximum of Months 0.184519E+11 28490.78   42.13 26.34 0.446830E+09 545.27   42.30 25.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.181609E+10 2506.93 26-JAN-15:00 21.60 13.66 0.528688E+09 845.61 26-JAN-14:20 21.60 13.66
February 0.262688E+10 5175.22 24-FEB-15:00 26.40 17.38 0.532586E+09 845.62 24-FEB-14:20 26.40 17.38
March 0.602181E+10 11914.05 11-MAR-06:02 23.80 17.15 0.682722E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.106922E+11 22538.99 30-APR-16:21 37.45 18.00 0.613865E+09 845.63 04-APR-09:20 37.45 18.00
May 0.151360E+11 22346.06 28-MAY-16:41 41.80 19.54 0.665888E+09 845.65 04-MAY-09:30 41.80 19.54
June 0.152823E+11 22288.06 11-JUN-16:21 43.25 23.12 0.663552E+09 845.65 12-JUN-09:30 39.25 21.97
July 0.139260E+11 22135.88 02-JUL-17:01 40.18 26.57 0.617450E+09 845.64 07-JUL-09:39 36.50 24.41
August 0.130612E+11 21484.73 27-AUG-14:51 35.50 29.14 0.692038E+09 845.62 21-AUG-13:20 35.50 29.14
September 0.101043E+11 21440.57 17-SEP-13:22 34.20 26.12 0.614330E+09 845.62 08-SEP-13:20 34.20 26.12
October 0.746154E+10 16738.76 01-OCT-15:11 35.83 20.00 0.636361E+09 845.62 16-OCT-09:20 26.87 17.49
November 0.390397E+10 5775.81 09-NOV-14:30 29.30 17.79 0.612242E+09 845.62 06-NOV-10:20 29.30 17.79
December 0.215788E+10 2419.33 03-DEC-15:02 23.32 14.21 0.536055E+09 845.62 29-DEC-14:20 19.70 14.83
                     
Annual Sum or Average 0.102190E+12         0.739578E+10        
Minimum of Months 0.181609E+10 2419.33   21.60 13.66 0.528688E+09 845.61   19.70 13.66
Maximum of Months 0.152823E+11 22538.99   43.25 29.14 0.692038E+09 845.65   41.80 29.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.136421E+10 5007.87 26-JAN-11:05 19.98 13.28 0.277538E+09 548.49 05-JAN-11:09 19.98 13.28
February 0.259626E+10 7877.91 22-FEB-11:05 23.90 14.68 0.265988E+09 548.49 15-FEB-11:09 23.90 14.68
March 0.629480E+10 18003.77 12-MAR-15:21 31.40 19.75 0.327278E+09 548.50 27-MAR-10:09 25.97 17.24
April 0.105405E+11 20912.73 30-APR-09:41 30.90 15.93 0.293173E+09 548.57 28-APR-10:09 30.90 15.93
May 0.132978E+11 19621.46 29-MAY-09:22 34.75 21.56 0.317540E+09 548.83 03-MAY-10:09 34.75 21.56
June 0.120032E+11 19028.20 11-JUN-10:22 37.75 25.19 0.315855E+09 548.84 05-JUN-10:09 37.75 25.19
July 0.102670E+11 18852.76 04-JUL-10:32 36.00 24.99 0.294912E+09 548.60 07-JUL-10:09 37.08 24.60
August 0.951589E+10 17891.69 27-AUG-14:11 35.57 29.07 0.329254E+09 548.48 21-AUG-12:09 35.57 29.07
September 0.811187E+10 18538.82 17-SEP-10:42 31.67 25.57 0.292968E+09 548.49 14-SEP-12:09 31.67 25.57
October 0.703023E+10 19460.07 01-OCT-10:32 31.23 19.64 0.304431E+09 548.50 10-OCT-14:09 31.67 20.72
November 0.386670E+10 8335.95 01-NOV-10:05 23.77 15.01 0.297640E+09 548.50 06-NOV-15:09 28.20 18.14
December 0.168618E+10 5371.59 01-DEC-11:05 20.45 12.21 0.276482E+09 548.49 18-DEC-11:09 21.85 14.75
                     
Annual Sum or Average 0.865746E+11         0.359306E+10        
Minimum of Months 0.136421E+10 5007.87   19.98 12.21 0.265988E+09 548.48   19.98 13.28
Maximum of Months 0.132978E+11 20912.73   37.75 29.07 0.329254E+09 548.84   37.75 29.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.629606E+10 16961.52 08-JAN-13:13 20.83 12.43 0.610427E+09 845.82 12-JAN-14:20 23.40 14.05
February 0.758580E+10 24085.60 20-FEB-14:32 26.33 13.84 0.565160E+09 846.44 23-FEB-14:20 26.20 13.97
March 0.120060E+11 23972.15 12-MAR-13:22 30.95 19.20 0.689540E+09 848.09 30-MAR-13:50 32.05 19.26
April 0.143865E+11 24044.12 30-APR-15:01 37.88 18.24 0.614795E+09 846.57 07-APR-13:20 37.88 18.24
May 0.159615E+11 22419.06 28-MAY-16:01 42.20 19.49 0.666033E+09 846.79 30-MAY-13:20 39.27 24.02
June 0.151349E+11 22174.11 11-JUN-16:21 43.25 23.12 0.663563E+09 846.77 06-JUN-13:20 43.25 23.12
July 0.140489E+11 22086.74 02-JUL-16:21 40.35 26.46 0.617485E+09 846.82 05-JUL-13:20 37.90 25.56
August 0.140012E+11 21850.69 27-AUG-14:11 35.57 29.07 0.692226E+09 846.76 08-AUG-13:20 35.57 29.07
September 0.133333E+11 23515.02 17-SEP-13:22 34.20 26.12 0.615130E+09 866.24 28-SEP-13:50 35.43 22.76
October 0.156235E+11 25278.69 29-OCT-13:01 29.13 18.04 0.641950E+09 904.79 02-OCT-13:50 29.13 18.04
November 0.130455E+11 24423.32 11-NOV-14:42 28.45 17.08 0.631476E+09 869.25 01-NOV-13:50 28.45 17.08
December 0.752673E+10 22383.14 24-DEC-14:13 24.33 13.93 0.601848E+09 845.95 01-DEC-14:20 24.33 13.93
                     
Annual Sum or Average 0.148950E+12         0.760963E+10        
Minimum of Months 0.629606E+10 16961.52   20.83 12.43 0.565160E+09 845.82   23.40 13.93
Maximum of Months 0.159615E+11 25278.69   43.25 29.07 0.692226E+09 904.79   43.25 29.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.187867E+10 4911.72 31-JAN-16:10 20.95 11.21 0.366006E+09 544.95 13-JAN-14:20 20.95 11.21
February 0.287653E+10 12874.03 20-FEB-15:52 25.60 14.15 0.355729E+09 544.95 24-FEB-14:20 26.07 17.12
March 0.679995E+10 21719.23 12-MAR-16:01 31.18 19.88 0.443985E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.113870E+11 24499.21 30-APR-16:21 37.45 18.00 0.396504E+09 544.96 04-APR-09:20 37.45 18.00
May 0.138053E+11 23142.21 14-MAY-15:51 36.20 21.41 0.429631E+09 544.97 04-MAY-09:30 36.20 21.41
June 0.134073E+11 22259.90 11-JUN-16:21 43.25 23.12 0.428017E+09 544.97 12-JUN-09:30 39.25 21.97
July 0.111370E+11 21956.15 02-JUL-16:21 40.35 26.46 0.398272E+09 544.96 07-JUL-09:39 36.50 24.41
August 0.106136E+11 20659.16 06-AUG-16:21 36.15 26.34 0.446374E+09 544.95 21-AUG-13:20 29.43 27.58
September 0.885042E+10 21645.31 17-SEP-17:21 35.00 26.58 0.396435E+09 544.95 08-SEP-13:20 35.00 26.58
October 0.751083E+10 21745.64 15-OCT-15:21 32.35 19.26 0.411716E+09 544.95 17-OCT-09:20 26.63 18.34
November 0.447945E+10 19954.41 11-NOV-15:22 28.00 17.36 0.402602E+09 544.95 06-NOV-10:20 28.00 17.36
December 0.226537E+10 5655.82 01-DEC-15:30 22.85 13.56 0.368277E+09 544.95 29-DEC-14:20 19.70 14.83
                     
Annual Sum or Average 0.950115E+11         0.484355E+10        
Minimum of Months 0.187867E+10 4911.72   20.95 11.21 0.355729E+09 544.95   19.70 11.21
Maximum of Months 0.138053E+11 24499.21   43.25 26.58 0.446374E+09 544.97   39.25 27.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135558E+10 2402.50 26-JAN-15:00 21.60 13.66 0.507723E+09 845.61 26-JAN-14:20 21.60 13.66
February 0.231324E+10 5414.81 23-FEB-14:50 25.90 14.07 0.513655E+09 845.62 24-FEB-14:20 26.07 17.12
March 0.599334E+10 10673.39 11-MAR-06:02 23.80 17.15 0.675029E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.113714E+11 24785.03 16-APR-15:21 39.50 22.49 0.613806E+09 845.63 28-APR-13:20 37.93 20.83
May 0.164856E+11 25745.27 28-MAY-16:41 41.80 19.54 0.666076E+09 845.62 08-MAY-13:20 41.80 19.54
June 0.165691E+11 25589.20 11-JUN-15:41 43.37 23.26 0.663659E+09 845.63 05-JUN-13:20 43.37 23.26
July 0.149987E+11 25457.16 02-JUL-17:01 40.18 26.57 0.617645E+09 845.61 10-JUL-09:20 33.27 26.53
August 0.139138E+11 24805.63 13-AUG-15:31 34.80 28.33 0.692122E+09 845.61 28-AUG-09:20 31.07 27.59
September 0.105799E+11 25285.20 17-SEP-14:51 34.20 26.01 0.614474E+09 845.61 08-SEP-13:20 34.20 26.01
October 0.749985E+10 23983.24 09-OCT-15:31 32.47 20.08 0.633929E+09 845.62 16-OCT-09:20 26.87 17.49
November 0.354083E+10 6245.16 09-NOV-14:40 29.27 17.76 0.596006E+09 845.62 15-NOV-14:20 26.37 17.60
December 0.166653E+10 2231.52 28-DEC-16:00 23.80 15.20 0.508000E+09 845.58 28-DEC-14:00 23.80 15.20
                     
Annual Sum or Average 0.106288E+12         0.730212E+10        
Minimum of Months 0.135558E+10 2231.52   21.60 13.66 0.507723E+09 845.58   21.60 13.66
Maximum of Months 0.165691E+11 25745.27   43.37 28.33 0.692122E+09 845.63   43.37 27.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131972E+10 2753.09 26-JAN-14:30 22.05 13.77 0.360109E+09 544.95 13-JAN-14:20 22.05 13.77
February 0.246055E+10 5979.74 23-FEB-10:40 22.80 14.32 0.354679E+09 544.95 15-FEB-14:20 22.80 14.32
March 0.642933E+10 18873.31 12-MAR-10:13 26.67 17.47 0.442780E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.112383E+11 20215.49 16-APR-10:02 35.32 21.70 0.396413E+09 545.23 28-APR-09:50 33.47 18.33
May 0.144648E+11 20629.98 29-MAY-09:22 34.75 21.56 0.429619E+09 545.19 26-MAY-09:00 34.75 21.56
June 0.131234E+11 20044.34 11-JUN-10:22 37.75 25.19 0.427910E+09 550.72 12-JUN-09:50 39.75 22.08
July 0.112333E+11 19816.63 04-JUL-10:32 36.00 24.99 0.398221E+09 545.10 10-JUL-09:50 34.12 26.58
August 0.103722E+11 19137.79 13-AUG-15:31 34.80 28.33 0.446201E+09 544.94 28-AUG-09:20 31.07 27.59
September 0.868363E+10 19898.65 17-SEP-14:51 34.20 26.01 0.396253E+09 544.95 08-SEP-13:20 34.20 26.01
October 0.724931E+10 20344.71 01-OCT-10:32 31.23 19.64 0.410890E+09 544.95 17-OCT-09:20 26.63 18.34
November 0.370138E+10 6262.71 09-NOV-10:20 25.33 18.04 0.399944E+09 544.95 15-NOV-14:20 26.37 17.60
December 0.149141E+10 2825.66 01-DEC-14:40 23.43 13.26 0.362141E+09 544.95 28-DEC-14:20 24.57 15.33
                     
Annual Sum or Average 0.917673E+11         0.482516E+10        
Minimum of Months 0.131972E+10 2753.09   22.05 13.26 0.354679E+09 544.94   22.05 13.77
Maximum of Months 0.144648E+11 20629.98   37.75 28.33 0.446201E+09 550.72   39.75 27.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.516666E+10 12948.55 12-JAN-14:30 23.45 14.09 0.591465E+09 845.64 12-JAN-14:20 23.45 14.09
February 0.680513E+10 25503.83 19-FEB-14:52 26.00 14.24 0.553180E+09 845.92 22-FEB-14:00 27.10 16.20
March 0.118035E+11 25653.50 05-MAR-13:52 28.80 17.22 0.685870E+09 846.05 08-MAR-14:50 29.22 16.87
April 0.150779E+11 25787.49 16-APR-15:21 39.50 22.49 0.614773E+09 845.94 21-APR-13:00 35.00 19.79
May 0.173123E+11 25789.22 28-MAY-16:01 42.20 19.49 0.666187E+09 845.87 03-MAY-13:00 42.20 19.49
June 0.164177E+11 25506.80 11-JUN-15:41 43.37 23.26 0.663659E+09 845.80 12-JUN-13:50 43.80 22.37
July 0.151182E+11 25359.77 02-JUL-16:21 40.35 26.46 0.617671E+09 845.63 10-JUL-09:20 33.27 26.53
August 0.148687E+11 25106.43 13-AUG-14:51 34.80 28.33 0.692285E+09 845.80 07-AUG-13:00 34.80 28.33
September 0.138161E+11 27186.79 17-SEP-14:51 34.20 26.01 0.615040E+09 845.82 26-SEP-13:00 35.70 22.91
October 0.155519E+11 28708.14 09-OCT-13:31 32.57 19.69 0.639579E+09 879.62 02-OCT-13:50 32.57 19.69
November 0.122001E+11 28126.64 05-NOV-13:41 29.32 17.20 0.625995E+09 846.01 15-NOV-14:00 26.50 17.83
December 0.614596E+10 24453.37 03-DEC-14:43 23.75 14.22 0.586421E+09 845.78 01-DEC-14:39 23.75 14.22
                     
Annual Sum or Average 0.150284E+12         0.755213E+10        
Minimum of Months 0.516666E+10 12948.55   23.45 14.09 0.553180E+09 845.63   23.45 14.09
Maximum of Months 0.173123E+11 28708.14   43.37 28.33 0.692285E+09 879.62   43.80 28.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158648E+10 4798.38 12-JAN-15:50 23.35 14.44 0.352964E+09 544.95 13-JAN-14:20 21.30 15.27
February 0.264365E+10 9483.90 20-FEB-16:12 25.27 14.30 0.345268E+09 544.95 24-FEB-14:20 26.07 17.12
March 0.672409E+10 20977.04 12-MAR-16:12 31.07 19.87 0.441239E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.118243E+11 24107.05 30-APR-16:31 37.33 17.93 0.396538E+09 544.96 04-APR-09:20 37.33 17.93
May 0.146817E+11 25036.54 28-MAY-16:01 42.20 19.49 0.429687E+09 544.95 08-MAY-13:20 42.20 19.49
June 0.142382E+11 24636.34 18-JUN-16:01 33.12 23.22 0.428038E+09 544.96 05-JUN-13:20 33.12 23.22
July 0.118174E+11 24274.00 02-JUL-16:21 40.35 26.46 0.398347E+09 544.94 10-JUL-09:20 33.27 26.53
August 0.111785E+11 23149.71 13-AUG-16:11 34.73 28.34 0.446389E+09 544.94 28-AUG-09:20 31.07 27.59
September 0.915960E+10 24098.46 17-SEP-14:51 34.20 26.01 0.396471E+09 544.95 08-SEP-13:20 34.20 26.01
October 0.749687E+10 24073.34 09-OCT-15:31 32.47 20.08 0.411081E+09 544.95 16-OCT-09:20 26.87 17.49
November 0.418858E+10 21821.17 05-NOV-15:42 28.08 17.72 0.395848E+09 544.96 06-NOV-14:00 28.40 18.16
December 0.187423E+10 5484.32 28-DEC-15:40 24.03 15.27 0.353216E+09 544.95 29-DEC-14:20 19.70 14.83
                     
Annual Sum or Average 0.974136E+11         0.479509E+10        
Minimum of Months 0.158648E+10 4798.38   23.35 14.30 0.345268E+09 544.94   19.70 14.83
Maximum of Months 0.146817E+11 25036.54   42.20 28.34 0.446389E+09 544.96   42.20 27.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138005E+10 2707.86 12-JAN-17:00 22.30 14.53 0.00 0.00 01-JAN-00:10 22.30 14.53
February 0.354211E+10 9030.83 21-FEB-06:15 11.70 10.89 0.00 0.00 01-FEB-00:10 11.70 10.89
March 0.874579E+10 10087.49 13-MAR-16:00 32.50 18.65 0.00 0.00 01-MAR-00:10 32.50 18.65
April 0.142533E+11 18717.63 17-APR-05:15 24.33 18.88 0.00 0.00 01-APR-00:10 24.33 18.88
May 0.165972E+11 22722.75 30-MAY-05:15 30.30 21.64 0.00 0.00 01-MAY-00:10 30.30 21.64
June 0.164680E+11 21586.04 12-JUN-05:15 34.23 19.16 0.00 0.00 01-JUN-00:10 34.23 19.16
July 0.156297E+11 22400.86 05-JUL-05:25 32.70 24.64 0.00 0.00 01-JUL-00:10 32.70 24.64
August 0.162986E+11 20652.55 07-AUG-05:13 29.57 24.74 0.00 0.00 01-AUG-00:10 29.57 24.74
September 0.114998E+11 18500.98 18-SEP-05:15 26.73 24.13 0.00 0.00 01-SEP-00:10 26.73 24.13
October 0.108012E+11 15005.93 10-OCT-05:15 19.90 18.09 0.00 0.00 01-OCT-00:10 19.90 18.09
November 0.714649E+10 11462.81 13-NOV-06:13 15.27 12.05 0.00 0.00 01-NOV-00:10 15.27 12.05
December 0.345977E+10 6529.34 26-DEC-06:08 10.17 8.52 0.00 0.00 01-DEC-00:10 10.17 8.52
                     
Annual Sum or Average 0.125822E+12         0.00        
Minimum of Months 0.138005E+10 2707.86   10.17 8.52 0.00 0.00   10.17 8.52
Maximum of Months 0.165972E+11 22722.75   34.23 24.74 0.00 0.00   34.23 24.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.500007E+09 2878.52 04-JAN-06:02 5.65 5.27 0.00 0.00 01-JAN-00:10 5.65 5.27
February 0.173581E+10 4511.99 22-FEB-16:50 25.83 15.78 0.00 0.00 01-FEB-00:10 25.83 15.78
March 0.624416E+10 8709.17 13-MAR-16:00 32.50 18.65 0.00 0.00 01-MAR-00:10 32.50 18.65
April 0.113646E+11 14658.25 17-APR-05:03 24.22 18.83 0.00 0.00 01-APR-00:10 24.22 18.83
May 0.151404E+11 17979.24 30-MAY-05:15 30.30 21.64 0.00 0.00 01-MAY-00:10 30.30 21.64
June 0.146465E+11 18838.43 12-JUN-05:15 34.23 19.16 0.00 0.00 01-JUN-00:10 34.23 19.16
July 0.130400E+11 18669.49 05-JUL-05:13 32.63 24.69 0.00 0.00 01-JUL-00:10 32.63 24.69
August 0.122508E+11 15278.21 07-AUG-05:13 29.57 24.74 0.00 0.00 01-AUG-00:10 29.57 24.74
September 0.986353E+10 13366.07 25-SEP-05:02 25.93 23.09 0.00 0.00 01-SEP-00:10 25.93 23.09
October 0.865555E+10 11851.00 10-OCT-05:15 19.90 18.09 0.00 0.00 01-OCT-00:10 19.90 18.09
November 0.441287E+10 6586.91 13-NOV-06:13 15.27 12.05 0.00 0.00 01-NOV-00:10 15.27 12.05
December 0.103701E+10 2706.32 01-DEC-06:10 11.02 8.79 0.00 0.00 01-DEC-00:10 11.02 8.79
                     
Annual Sum or Average 0.988912E+11         0.00        
Minimum of Months 0.500007E+09 2706.32   5.65 5.27 0.00 0.00   5.65 5.27
Maximum of Months 0.151404E+11 18838.43   34.23 24.74 0.00 0.00   34.23 24.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.911314E+09 5088.20 12-JAN-15:00 23.60 14.20 0.00 0.00 01-JAN-00:10 23.60 14.20
February 0.310881E+10 12664.08 22-FEB-15:05 27.00 16.16 0.00 0.00 01-FEB-00:10 27.00 16.16
March 0.100528E+11 21680.57 28-MAR-15:40 35.53 18.66 0.00 0.00 01-MAR-00:10 35.53 18.66
April 0.195513E+11 27383.96 28-APR-15:00 39.20 20.99 0.00 0.00 01-APR-00:10 39.20 20.99
May 0.262372E+11 31466.25 01-MAY-14:30 44.00 22.05 0.00 0.00 01-MAY-00:10 44.00 22.05
June 0.260827E+11 33454.17 12-JUN-13:50 43.80 22.37 0.00 0.00 01-JUN-00:10 43.80 22.37
July 0.211623E+11 29567.99 07-JUL-14:00 40.30 24.54 0.00 0.00 01-JUL-00:10 40.30 24.54
August 0.192145E+11 26300.67 07-AUG-14:40 37.27 26.48 0.00 0.00 01-AUG-00:10 37.27 26.48
September 0.147827E+11 22161.58 26-SEP-15:00 36.10 22.69 0.00 0.00 01-SEP-00:10 36.10 22.69
October 0.122193E+11 21493.64 02-OCT-14:20 36.40 21.05 0.00 0.00 01-OCT-00:10 36.40 21.05
November 0.582452E+10 13964.12 09-NOV-14:40 29.27 17.76 0.00 0.00 01-NOV-00:10 29.27 17.76
December 0.135161E+10 6869.94 01-DEC-14:40 23.43 13.26 0.00 0.00 01-DEC-00:10 23.43 13.26
                     
Annual Sum or Average 0.160499E+12         0.00        
Minimum of Months 0.911314E+09 5088.20   23.43 13.26 0.00 0.00   23.43 13.26
Maximum of Months 0.262372E+11 33454.17   44.00 26.48 0.00 0.00   44.00 26.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.362045E+10 1753.49 12-JAN-17:00 22.30 14.53 95236165.29 126.84 13-JAN-14:00 21.50 15.25
February 0.826261E+10 3960.89 20-FEB-17:37 23.53 14.36 86404044.24 126.84 10-FEB-14:00 23.53 14.36
March 0.145525E+11 7219.29 31-MAR-24:00 23.70 16.75 0.103242E+09 126.84 29-MAR-09:09 23.70 16.75
April 0.192107E+11 7852.83 17-APR-01:13 26.33 20.03 93970587.89 141.39 27-APR-13:00 39.60 19.54
May 0.480772E+10 3512.70 31-MAY-24:00 28.10 22.60 99238731.69 126.85 30-MAY-13:09 28.10 22.60
June 0.951775E+10 5458.70 30-JUN-23:57 33.10 24.67 98979988.99 126.88 27-JUN-09:09 33.10 24.67
July 0.148917E+11 7347.14 31-JUL-24:00 29.40 26.34 91895176.46 126.85 18-JUL-13:09 29.40 26.34
August 0.196968E+11 7642.14 21-AUG-03:15 25.83 25.23 0.109899E+09 147.87 07-AUG-13:00 25.83 25.23
September 0.450395E+10 3518.47 30-SEP-24:00 26.60 21.92 91605539.91 126.85 27-SEP-13:09 26.60 21.92
October 0.967392E+10 5363.90 31-OCT-24:00 17.80 15.13 95244767.16 126.86 13-OCT-09:09 17.80 15.13
November 0.140722E+11 5887.15 12-NOV-16:25 26.95 15.49 94305428.29 126.84 06-NOV-10:09 26.95 15.49
December 0.192744E+11 7548.01 24-DEC-17:10 20.40 13.19 91882646.58 126.83 11-DEC-10:00 20.40 13.19
                     
Annual Sum or Average 0.142085E+12         0.115190E+10        
Minimum of Months 0.362045E+10 1753.49   17.80 13.19 86404044.24 126.83   17.80 13.19
Maximum of Months 0.196968E+11 7852.83   33.10 26.34 0.109899E+09 147.87   39.60 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.206167E+10 1570.13 12-JAN-17:00 22.30 14.53 95208087.25 126.84 27-JAN-14:00 16.30 12.13
February 0.716688E+10 3540.66 20-FEB-17:37 23.53 14.36 86403741.83 126.84 10-FEB-14:00 23.53 14.36
March 0.136885E+11 6953.88 31-MAR-24:00 23.70 16.75 0.103242E+09 126.84 29-MAR-09:09 23.70 16.75
April 0.181734E+11 7344.24 16-APR-21:02 28.32 20.05 93602031.73 139.51 26-APR-13:00 38.80 22.02
May 0.449754E+10 3386.94 31-MAY-24:00 28.10 22.60 99237086.62 126.85 09-MAY-13:00 28.10 22.60
June 0.903076E+10 5258.48 30-JUN-23:57 33.10 24.67 98979332.35 126.87 27-JUN-09:09 33.10 24.67
July 0.141183E+11 7010.52 31-JUL-24:00 29.40 26.34 91895285.24 126.85 18-JUL-09:00 29.40 26.34
August 0.185848E+11 7210.26 20-AUG-17:33 26.43 25.55 0.108231E+09 143.59 07-AUG-13:00 26.43 25.55
September 0.413303E+10 3391.14 30-SEP-24:00 26.60 21.92 91605150.04 126.82 12-SEP-09:09 26.60 21.92
October 0.905730E+10 5070.49 31-OCT-24:00 17.80 15.13 95244155.17 126.86 13-OCT-09:09 17.80 15.13
November 0.129710E+11 5388.86 12-NOV-16:42 26.58 15.37 94305250.26 126.83 10-NOV-10:09 26.58 15.37
December 0.173008E+11 7079.40 01-DEC-17:00 21.20 14.26 91882716.63 126.83 11-DEC-10:09 8.92 8.81
                     
Annual Sum or Average 0.130784E+12         0.114984E+10        
Minimum of Months 0.206167E+10 1570.13   17.80 14.26 86403741.83 126.82   8.92 8.81
Maximum of Months 0.185848E+11 7344.24   33.10 26.34 0.108231E+09 143.59   38.80 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.110040E+10 1593.09 12-JAN-17:00 22.30 14.53 94540509.83 127.04 05-JAN-10:09 22.30 14.53
February 0.651320E+10 3562.24 22-FEB-17:00 25.70 15.75 86403755.38 126.84 10-FEB-14:00 25.70 15.75
March 0.135094E+11 6906.73 31-MAR-24:00 23.70 16.75 0.103242E+09 126.84 29-MAR-09:09 23.70 16.75
April 0.182510E+11 7515.39 16-APR-21:32 28.07 20.03 93759654.00 141.11 26-APR-13:00 38.80 22.02
May 0.470863E+10 3331.42 31-MAY-24:00 28.10 22.60 99238499.10 126.85 30-MAY-13:09 28.10 22.60
June 0.922232E+10 5324.76 30-JUN-23:57 33.10 24.67 98979721.63 126.87 28-JUN-13:09 33.10 24.67
July 0.143185E+11 7056.25 31-JUL-23:57 29.40 26.34 91895619.13 126.85 18-JUL-09:00 29.40 26.34
August 0.187252E+11 7331.85 20-AUG-17:55 26.30 25.51 0.108035E+09 145.06 07-AUG-13:00 26.30 25.51
September 0.421912E+10 3412.80 30-SEP-23:33 26.60 22.02 91605373.13 126.82 12-SEP-09:09 26.60 22.02
October 0.897374E+10 4935.21 31-OCT-24:00 17.80 15.13 95244322.65 126.86 13-OCT-09:09 17.80 15.13
November 0.124656E+11 5441.45 05-NOV-16:35 26.83 17.97 94305390.61 126.83 10-NOV-10:09 23.57 17.22
December 0.161280E+11 7079.88 01-DEC-17:00 21.20 14.26 91882959.00 126.83 11-DEC-10:09 8.92 8.81
                     
Annual Sum or Average 0.128135E+12         0.114913E+10        
Minimum of Months 0.110040E+10 1593.09   17.80 14.26 86403755.38 126.82   8.92 8.81
Maximum of Months 0.187252E+11 7515.39   33.10 26.34 0.108035E+09 145.06   38.80 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.239221E+12 91541.22 26-JAN-17:00 18.60 12.70 0.206235E+10 2748.30 26-JAN-10:09 18.60 12.70
February 0.436198E+12 183179.02 21-FEB-17:00 25.40 15.70 0.187100E+10 2749.20 09-FEB-14:09 25.40 15.70
March 0.728227E+12 358314.53 31-MAR-24:00 23.70 16.75 0.223524E+10 2749.98 21-MAR-09:09 23.70 16.75
April 0.933600E+12 368764.31 30-APR-05:07 22.73 16.14 0.240366E+10 4002.04 28-APR-13:00 22.73 16.14
May 0.241542E+12 175825.70 31-MAY-24:00 28.10 22.60 0.214879E+10 2747.25 24-MAY-09:09 28.10 22.60
June 0.471075E+12 268030.50 30-JUN-23:53 33.10 24.67 0.214273E+10 2746.92 27-JUN-09:09 33.10 24.67
July 0.734324E+12 356669.18 31-JUL-23:13 29.40 26.34 0.198925E+10 2746.01 18-JUL-09:09 29.40 26.34
August 0.966167E+12 369293.06 15-AUG-23:57 23.40 22.91 0.293549E+10 4088.86 07-AUG-13:00 23.40 22.91
September 0.238326E+12 177465.32 30-SEP-24:00 26.60 21.92 0.198362E+10 2747.28 01-SEP-09:09 26.60 21.92
October 0.489450E+12 269021.50 31-OCT-24:00 17.80 15.13 0.206190E+10 2746.44 13-OCT-09:09 17.80 15.13
November 0.709853E+12 276424.23 13-NOV-17:00 26.40 16.65 0.204190E+10 2749.54 28-NOV-10:09 18.13 13.76
December 0.977242E+12 367512.73 18-DEC-17:00 20.00 14.42 0.199034E+10 2807.37 28-DEC-14:00 24.50 15.39
                     
Annual Sum or Average 0.716522E+13         0.258663E+11        
Minimum of Months 0.238326E+12 91541.22   17.80 12.70 0.187100E+10 2746.01   17.80 12.70
Maximum of Months 0.977242E+12 369293.06   33.10 26.34 0.293549E+10 4088.86   33.10 26.34



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2484902.46 2097.48 14-JAN-17:03 20.55
February 44958720.13 9025.91 20-FEB-14:23 26.35
March 0.116732E+09 15750.69 11-MAR-17:01 29.70
April 0.436462E+09 29774.59 15-APR-16:01 39.58
May 0.580601E+09 33126.06 27-MAY-16:01 42.00
June 0.585313E+09 34970.42 10-JUN-16:01 43.12
July 0.760084E+09 28569.55 02-JUL-17:03 40.18
August 0.468205E+09 24428.91 05-AUG-16:01 35.70
September 0.648316E+09 22762.12 30-SEP-16:01 34.78
October 0.464714E+09 22615.21 01-OCT-14:33 35.97
November 0.134192E+09 14632.07 04-NOV-16:02 29.18
December 14412191.08 6633.06 25-DEC-14:07 24.43
         
Annual Sum or Average 0.425648E+10      
Minimum of Months 2484902.46 2097.48   20.55
Maximum of Months 0.760084E+09 34970.42   43.12



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3779229.97 25194.87 02-JAN-06:03 6.45
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 3779229.97      
Minimum of Months 0.00 0.00   6.45
Maximum of Months 3779229.97 25194.87   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.616955E+09 72305.53 02-JAN-05:11 6.47
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 1607774.08 13398.12 23-DEC-06:02 5.43
         
Annual Sum or Average 0.618562E+09      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 0.616955E+09 72305.53   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1003232.16 4432.80 02-JAN-06:03 6.45
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 1003232.16      
Minimum of Months 0.00 0.00   6.45
Maximum of Months 1003232.16 4432.80   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.323617E+09 16007.62 02-JAN-05:11 6.47
February 21672064.74 13316.86 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 51725315.87 14325.35 23-DEC-06:02 5.43
         
Annual Sum or Average 0.397014E+09      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 0.323617E+09 16007.62   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108297E+09 11569.74 02-JAN-05:11 6.47
February 4199530.10 9644.56 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 13812066.34 9474.03 23-DEC-06:02 5.43
         
Annual Sum or Average 0.126309E+09      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 0.108297E+09 11569.74   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 50884670.62 14969.30 02-JAN-05:11 6.47
February 5811972.71 12825.99 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 75722.99 82.85 23-DEC-07:10 6.25
         
Annual Sum or Average 56772366.32      
Minimum of Months 0.00 0.00   6.25
Maximum of Months 50884670.62 14969.30   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 59084140.01 10723.98 02-JAN-05:11 6.47
February 2518808.13 5390.92 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 5198136.52 5941.17 23-DEC-06:02 5.43
         
Annual Sum or Average 66801084.66      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 59084140.01 10723.98   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.133976E+10 20177.02 02-JAN-05:11 6.47
February 0.241989E+09 17573.02 11-FEB-05:12 9.07
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 17162383.51 10294.38 27-NOV-06:03 9.55
December 0.609169E+09 18376.92 22-DEC-05:11 11.37
         
Annual Sum or Average 0.220808E+10      
Minimum of Months 0.00 0.00   6.47
Maximum of Months 0.133976E+10 20177.02   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.522355E+09 14387.74 02-JAN-05:11 6.47
February 82186449.38 12459.55 11-FEB-05:12 9.07
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 1097450.28 872.54 27-NOV-06:03 9.55
December 0.213833E+09 12839.01 22-DEC-05:11 11.37
         
Annual Sum or Average 0.819472E+09      
Minimum of Months 0.00 0.00   6.47
Maximum of Months 0.522355E+09 14387.74   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.442069E+09 20083.74 02-JAN-05:11 6.47
February 79758686.07 17529.60 11-FEB-05:12 9.07
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.115739E+09 16578.75 30-DEC-06:02 10.48
         
Annual Sum or Average 0.637566E+09      
Minimum of Months 0.00 0.00   6.47
Maximum of Months 0.442069E+09 20083.74   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.411909E+09 14903.14 02-JAN-05:11 6.47
February 56187574.30 11799.67 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.124031E+09 12621.47 22-DEC-05:11 11.37
         
Annual Sum or Average 0.592127E+09      
Minimum of Months 0.00 0.00   6.47
Maximum of Months 0.411909E+09 14903.14   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 96405719.33 11078.31 02-JAN-05:11 6.47
February 94916597.13 9165.64 11-FEB-06:02 9.30
March 67915788.02 8316.60 20-MAR-04:12 15.40
April 49252980.99 7161.03 02-APR-15:41 33.88
May 27790204.79 6933.02 14-MAY-15:21 36.15
June 28771369.51 7621.11 04-JUN-14:51 42.30
July 36615238.18 5531.32 30-JUL-14:22 34.60
August 43336745.40 6386.53 27-AUG-14:22 35.55
September 29559484.43 5918.41 08-SEP-03:02 25.00
October 56386801.95 6698.16 15-OCT-14:41 32.65
November 93262406.41 8816.84 27-NOV-05:12 9.77
December 0.177717E+09 11613.13 11-DEC-05:12 10.13
         
Annual Sum or Average 0.801930E+09      
Minimum of Months 27790204.79 5531.32   6.47
Maximum of Months 0.177717E+09 11613.13   42.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105868E+10 6807.73 12-JAN-06:02 12.75
February 0.175120E+09 6909.46 10-FEB-06:02 12.33
March 42301575.11 6628.75 26-MAR-15:01 30.33
April 32892160.60 7169.11 02-APR-15:11 33.83
May 32365990.71 6660.47 14-MAY-16:31 35.87
June 28098161.45 7327.13 04-JUN-15:41 42.30
July 39049842.82 5547.71 30-JUL-14:22 34.60
August 29224700.15 6343.51 27-AUG-14:11 35.57
September 27255056.52 6710.75 11-SEP-03:02 26.07
October 45785108.30 6615.63 01-OCT-13:51 35.90
November 54084058.95 5414.99 28-NOV-06:02 15.22
December 0.256816E+09 6583.35 13-DEC-06:02 11.83
         
Annual Sum or Average 0.182167E+10      
Minimum of Months 27255056.52 5414.99   11.83
Maximum of Months 0.105868E+10 7327.13   42.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268289E+10 23405.28 02-JAN-06:03 6.45
February 0.125015E+10 14244.73 24-FEB-06:03 15.00
March 0.456952E+09 15016.42 03-MAR-06:02 14.12
April 52169386.78 12422.46 24-APR-04:11 22.17
May 6312944.25 6268.63 25-MAY-03:02 26.60
June 4674150.51 4718.45 21-JUN-03:02 28.25
July 4446837.25 6478.27 19-JUL-04:03 24.72
August 7627083.69 5349.35 21-AUG-03:02 25.87
September 18357553.83 8703.34 11-SEP-03:02 26.07
October 0.203370E+09 13269.80 31-OCT-05:03 15.53
November 0.783572E+09 14639.25 07-NOV-06:03 14.48
December 0.193734E+10 9673.53 23-DEC-06:02 5.43
         
Annual Sum or Average 0.740786E+10      
Minimum of Months 4446837.25 4718.45   5.43
Maximum of Months 0.268289E+10 23405.28   28.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 18950387.15 274.75 01-JAN-13:20 15.40
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 18950387.15      
Minimum of Months 0.00 0.00   9.73
Maximum of Months 18950387.15 274.75   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152926E+09 350.62 01-JAN-14:15 16.23
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.152926E+09      
Minimum of Months 0.00 0.00   9.73
Maximum of Months 0.152926E+09 350.62   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:05 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:05 28.05
July 0.00 0.00 01-JUL-00:03 32.95
August 0.00 0.00 01-AUG-00:05 29.32
September 0.00 0.00 01-SEP-00:05 28.43
October 0.00 0.00 01-OCT-00:05 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.102175E+11 10739.37 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.926817E+10 10739.37 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.110123E+11 10739.37 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.983736E+10 10739.37 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.106149E+11 10739.37 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.105634E+11 10739.37 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.988891E+10 10739.37 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.110123E+11 10739.37 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.983736E+10 10739.37 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.102175E+11 10739.37 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.100973E+11 10739.37 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.988891E+10 10739.37 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.122456E+12     0.424397E+12    
Minimum of Months 0.926817E+10 10739.37   0.325565E+11 13457.54  
Maximum of Months 0.110123E+11 10739.37   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.917607E+10 9644.71 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.832347E+10 9644.71 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.988979E+10 9644.71 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.883464E+10 9644.71 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.953293E+10 9644.71 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.948664E+10 9644.71 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.888093E+10 9644.71 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.988979E+10 9644.71 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.883464E+10 9644.71 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.917607E+10 9644.71 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.906805E+10 9644.71 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.888093E+10 9644.71 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.109974E+12     0.289614E+12    
Minimum of Months 0.832347E+10 9644.71   0.220609E+11 17206.63  
Maximum of Months 0.988979E+10 9644.71   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.917607E+10 9644.71 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.832347E+10 9644.71 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.988979E+10 9644.71 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.883464E+10 9644.71 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.953293E+10 9644.71 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.948664E+10 9644.71 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.888093E+10 9644.71 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.988979E+10 9644.71 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.883464E+10 9644.71 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.917607E+10 9644.71 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.906805E+10 9644.71 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.888093E+10 9644.71 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.109974E+12     0.289613E+12    
Minimum of Months 0.832347E+10 9644.71   0.220609E+11 17206.56  
Maximum of Months 0.988979E+10 9644.71   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.917607E+10 9644.71 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.832347E+10 9644.71 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.988979E+10 9644.71 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.883464E+10 9644.71 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.953293E+10 9644.71 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.948664E+10 9644.71 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.888093E+10 9644.71 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.988979E+10 9644.71 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.883464E+10 9644.71 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.917607E+10 9644.71 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.906805E+10 9644.71 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.888093E+10 9644.71 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.109974E+12     0.289613E+12    
Minimum of Months 0.832347E+10 9644.71   0.220609E+11 17206.56  
Maximum of Months 0.988979E+10 9644.71   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.701781E+09 994.68 18-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.619375E+09 972.28 10-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.701167E+09 981.82 14-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.614835E+09 634.50 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.649121E+09 675.21 24-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.646066E+09 673.98 23-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.618672E+09 941.22 26-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.694254E+09 974.63 16-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.633049E+09 1008.11 08-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.673643E+09 1067.70 11-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.689090E+09 1039.27 27-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.689654E+09 1050.24 29-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.793071E+10     0.363654E+11    
Minimum of Months 0.614835E+09 634.50   0.277008E+10 2160.55  
Maximum of Months 0.701781E+09 1067.70   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.446003E+09 633.72 17-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.396063E+09 630.23 09-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.449783E+09 549.42 14-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.395787E+09 371.32 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.420298E+09 421.11 24-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.418053E+09 421.38 23-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.399218E+09 582.94 26-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.446748E+09 606.34 16-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.406421E+09 629.92 08-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.429956E+09 675.84 11-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.441015E+09 685.90 27-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.438783E+09 682.45 29-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.508813E+10     0.234352E+11    
Minimum of Months 0.395787E+09 371.32   0.178515E+10 1392.34  
Maximum of Months 0.449783E+09 685.90   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.677118E+09 952.00 18-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.606722E+09 938.17 10-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.697072E+09 968.94 14-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.616125E+09 641.06 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.654267E+09 779.22 24-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.651046E+09 787.60 23-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.623151E+09 956.70 26-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.695991E+09 981.51 16-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.631287E+09 1006.10 08-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.664987E+09 1061.72 11-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.668514E+09 917.55 27-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.661365E+09 995.87 29-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.784764E+10     0.363660E+11    
Minimum of Months 0.606722E+09 641.06   0.277013E+10 2160.58  
Maximum of Months 0.697072E+09 1061.72   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.442887E+09 646.41 18-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.393378E+09 634.69 10-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.451653E+09 655.81 14-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.396806E+09 508.34 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.420999E+09 535.15 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.418605E+09 536.33 23-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.401582E+09 625.39 26-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.450295E+09 641.86 16-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.408421E+09 658.53 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.434059E+09 691.71 11-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.434075E+09 613.81 03-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.431826E+09 624.41 29-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.508459E+10     0.234351E+11    
Minimum of Months 0.393378E+09 508.34   0.178514E+10 1392.33  
Maximum of Months 0.451653E+09 691.71   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.699814E+09 991.98 18-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.618060E+09 969.34 10-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.700242E+09 978.93 14-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.614434E+09 627.88 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.648781E+09 671.28 24-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.645214E+09 669.99 23-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.617958E+09 938.04 26-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.693377E+09 971.87 16-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.632116E+09 1005.76 08-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.672517E+09 1066.06 11-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.687515E+09 1036.85 27-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.687661E+09 1048.25 29-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.791769E+10     0.363654E+11    
Minimum of Months 0.614434E+09 627.88   0.277008E+10 2160.55  
Maximum of Months 0.700242E+09 1066.06   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.445223E+09 629.89 17-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.395424E+09 626.29 09-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.449438E+09 544.27 14-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.395603E+09 371.32 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.420015E+09 418.31 24-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.417669E+09 418.64 23-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.398721E+09 578.29 26-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.446095E+09 602.50 16-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.405964E+09 626.68 08-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.429466E+09 673.35 11-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.440394E+09 683.47 27-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.438053E+09 679.91 29-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.508206E+10     0.234352E+11    
Minimum of Months 0.395424E+09 371.32   0.178515E+10 1392.34  
Maximum of Months 0.449438E+09 683.47   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.676830E+09 949.12 18-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.606229E+09 934.98 10-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.696501E+09 965.94 14-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.615720E+09 634.90 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.653804E+09 773.57 24-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.650348E+09 781.98 23-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.622180E+09 953.65 26-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.695029E+09 978.80 16-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.630630E+09 1003.73 08-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.664013E+09 1060.05 11-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.667166E+09 913.69 27-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.661116E+09 993.32 29-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.783957E+10     0.363660E+11    
Minimum of Months 0.606229E+09 634.90   0.277013E+10 2160.58  
Maximum of Months 0.696501E+09 1060.05   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.442139E+09 642.93 18-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.392761E+09 630.87 10-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.451082E+09 652.48 14-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.396471E+09 501.57 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.420511E+09 528.64 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.418030E+09 529.85 23-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.400785E+09 621.31 26-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.449404E+09 638.21 16-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.407781E+09 655.33 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.433320E+09 689.39 11-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.433675E+09 609.88 03-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.431316E+09 620.67 29-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.507728E+10     0.234351E+11    
Minimum of Months 0.392761E+09 501.57   0.178514E+10 1392.33  
Maximum of Months 0.451082E+09 689.39   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.699754E+09 991.54 18-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.617940E+09 968.85 10-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.700214E+09 978.49 14-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.614423E+09 627.66 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.648766E+09 671.12 24-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.645185E+09 669.82 23-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.617923E+09 937.48 26-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.693320E+09 971.38 16-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.632048E+09 1005.34 08-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.672481E+09 1065.76 11-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.687418E+09 1036.56 27-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.687616E+09 1047.93 29-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.791709E+10     0.363654E+11    
Minimum of Months 0.614423E+09 627.66   0.277008E+10 2160.55  
Maximum of Months 0.700214E+09 1065.76   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.445208E+09 629.61 17-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.395403E+09 625.98 09-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.449426E+09 543.93 14-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.395597E+09 371.32 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.420000E+09 418.18 24-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.417654E+09 418.51 23-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.398698E+09 577.91 26-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.446048E+09 602.16 16-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.405939E+09 626.39 08-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.429440E+09 673.14 11-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.440376E+09 683.31 27-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.438034E+09 679.72 29-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.508182E+10     0.234352E+11    
Minimum of Months 0.395403E+09 371.32   0.178515E+10 1392.34  
Maximum of Months 0.449426E+09 683.31   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.676823E+09 948.62 18-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.606209E+09 934.44 10-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.696451E+09 965.48 14-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.615695E+09 634.69 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.653774E+09 772.70 24-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.650317E+09 781.13 23-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.622125E+09 953.12 26-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.694982E+09 978.33 16-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.630593E+09 1003.30 08-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.663994E+09 1059.74 11-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.667155E+09 913.29 27-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.661109E+09 992.95 29-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.783923E+10     0.363660E+11    
Minimum of Months 0.606209E+09 634.69   0.277013E+10 2160.58  
Maximum of Months 0.696451E+09 1059.74   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.442127E+09 642.66 18-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.392733E+09 630.57 10-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.451056E+09 652.24 14-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.396427E+09 501.24 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.420498E+09 528.14 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.417975E+09 529.35 23-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.400757E+09 620.99 26-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.449322E+09 637.92 16-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.407746E+09 655.07 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.433300E+09 689.20 11-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.433664E+09 609.64 03-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.431268E+09 620.43 29-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.507687E+10     0.234351E+11    
Minimum of Months 0.392733E+09 501.24   0.178514E+10 1392.33  
Maximum of Months 0.451056E+09 689.20   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147592E+09 154.45 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.133877E+09 154.45 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.159083E+09 154.45 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.142093E+09 154.45 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.153337E+09 154.45 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.152596E+09 154.45 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.142835E+09 154.45 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.159083E+09 154.45 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.142093E+09 154.45 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.147592E+09 154.45 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.145862E+09 154.45 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.142835E+09 154.45 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.176888E+10     0.153881E+12    
Minimum of Months 0.133877E+09 154.45   0.505780E+10 1948.61  
Maximum of Months 0.159083E+09 154.45   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147592E+09 154.45 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.133877E+09 154.45 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.159083E+09 154.45 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.142093E+09 154.45 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.153337E+09 154.45 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.152596E+09 154.45 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.142835E+09 154.45 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.159083E+09 154.45 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.142093E+09 154.45 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.147592E+09 154.45 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.145862E+09 154.45 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.142835E+09 154.45 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.176888E+10     0.153881E+12    
Minimum of Months 0.133877E+09 154.45   0.505780E+10 1948.61  
Maximum of Months 0.159083E+09 154.45   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147592E+09 154.45 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.133877E+09 154.45 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.159083E+09 154.45 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.142093E+09 154.45 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.153337E+09 154.45 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.152596E+09 154.45 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.142835E+09 154.45 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.159083E+09 154.45 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.142093E+09 154.45 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.147592E+09 154.45 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.145862E+09 154.45 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.142835E+09 154.45 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.176888E+10     0.153881E+12    
Minimum of Months 0.133877E+09 154.45   0.505780E+10 1948.61  
Maximum of Months 0.159083E+09 154.45   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.289359E+10 3028.04 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.262470E+10 3028.04 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.311888E+10 3028.04 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.278579E+10 3028.04 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.300623E+10 3028.04 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.299170E+10 3028.04 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.280033E+10 3028.04 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.311888E+10 3028.04 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.278579E+10 3028.04 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.289359E+10 3028.04 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.285968E+10 3028.04 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.280033E+10 3028.04 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.346795E+11     0.749486E+13    
Minimum of Months 0.262470E+10 3028.04   0.246344E+12 94908.13  
Maximum of Months 0.311888E+10 3028.04   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.102175E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.926817E+10 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.110123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.983736E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.106149E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.105634E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.988891E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.110123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.983736E+10 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.102175E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.100973E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.988891E+10 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.122456E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.926817E+10 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.110123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.917607E+10 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.832347E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.988979E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.883464E+10 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.953293E+10 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.948664E+10 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.888093E+10 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.988979E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.883464E+10 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.917607E+10 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.906805E+10 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.888093E+10 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.109974E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.832347E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.988979E+10 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.917607E+10 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.832347E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.988979E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.883464E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.953293E+10 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.948664E+10 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.888093E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.988979E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.883464E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.917607E+10 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.906805E+10 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.888093E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.109974E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.832347E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.988979E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.917607E+10 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.832347E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.988979E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.883464E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.953293E+10 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.948664E+10 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.888093E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.988979E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.883464E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.917607E+10 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.906805E+10 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.888093E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.109974E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.832347E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.988979E+10 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.701781E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 86646176.32
February 0.136985E+10 0.619375E+09 0.277008E+10 0.00 0.00 0.00 0.00 1233088.31 92527240.14
March 0.163685E+10 0.701167E+09 0.318369E+10 0.00 0.00 0.00 0.00 17160278.20 57018481.30
April 0.145243E+10 0.614835E+09 0.295462E+10 0.00 0.00 0.00 0.00 68340656.31 4078822.36
May 0.157338E+10 0.649121E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.150898E+09 1286562.48
June 0.156900E+10 0.646066E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.101970E+09 608566.32
July 0.145680E+10 0.618672E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.128147E+09 244450.68
August 0.163685E+10 0.694254E+09 0.318369E+10 0.00 0.00 0.00 0.00 72195158.52 522537.32
September 0.145243E+10 0.633049E+09 0.295328E+10 0.00 0.00 0.00 0.00 42934721.29 1125206.03
October 0.150991E+10 0.673643E+09 0.306046E+10 0.00 0.00 0.00 0.00 22159425.17 4821508.19
November 0.149516E+10 0.689090E+09 0.299314E+10 0.00 0.00 0.00 0.00 4576777.91 19834954.26
December 0.145680E+10 0.689654E+09 0.300922E+10 0.00 0.00 0.00 0.00 62659.82 80137383.14
                   
Annual Sum or Average 0.181194E+11 0.793071E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.609678E+09 0.348852E+09
Minimum of Months 0.136985E+10 0.614835E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 244450.68
Maximum of Months 0.163685E+10 0.701781E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.150898E+09 92527240.14



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.446003E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 59354210.91
February 0.882782E+09 0.396063E+09 0.178515E+10 0.00 0.00 0.00 0.00 615236.40 63880890.26
March 0.105485E+10 0.449783E+09 0.205169E+10 0.00 0.00 0.00 0.00 10594516.54 38601371.68
April 0.936002E+09 0.395787E+09 0.190407E+10 0.00 0.00 0.00 0.00 44757713.07 2781328.41
May 0.101394E+10 0.420298E+09 0.201177E+10 0.00 0.00 0.00 0.00 98986456.28 889621.18
June 0.101113E+10 0.418053E+09 0.197572E+10 0.00 0.00 0.00 0.00 67899066.61 365077.17
July 0.938820E+09 0.399218E+09 0.193969E+10 0.00 0.00 0.00 0.00 86308074.99 117797.57
August 0.105485E+10 0.446748E+09 0.205169E+10 0.00 0.00 0.00 0.00 49353647.02 264454.56
September 0.936002E+09 0.406421E+09 0.190321E+10 0.00 0.00 0.00 0.00 28416508.11 613460.66
October 0.973041E+09 0.429956E+09 0.197228E+10 0.00 0.00 0.00 0.00 14128964.27 3376241.23
November 0.963541E+09 0.441015E+09 0.192889E+10 0.00 0.00 0.00 0.00 2770241.89 13824064.51
December 0.938820E+09 0.438783E+09 0.193926E+10 0.00 0.00 0.00 0.00 13231.28 53795590.91
                   
Annual Sum or Average 0.116768E+11 0.508813E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.403844E+09 0.237864E+09
Minimum of Months 0.882782E+09 0.395787E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 117797.57
Maximum of Months 0.105485E+10 0.449783E+09 0.205169E+10 0.00 0.00 0.00 0.00 98986456.28 63880890.26



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.677118E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 93587202.00
February 0.136988E+10 0.606722E+09 0.277013E+10 0.00 0.00 0.00 0.00 871812.76 0.103174E+09
March 0.163688E+10 0.697072E+09 0.318374E+10 0.00 0.00 0.00 0.00 15134886.61 63968418.92
April 0.145246E+10 0.616125E+09 0.295467E+10 0.00 0.00 0.00 0.00 66510360.17 4764594.77
May 0.157341E+10 0.654267E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.149971E+09 1317628.63
June 0.156904E+10 0.651046E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.101933E+09 619786.03
July 0.145684E+10 0.623151E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.128071E+09 237233.05
August 0.163688E+10 0.695991E+09 0.318374E+10 0.00 0.00 0.00 0.00 71863647.08 549157.34
September 0.145246E+10 0.631287E+09 0.295333E+10 0.00 0.00 0.00 0.00 41646912.08 1118081.76
October 0.150994E+10 0.664987E+09 0.306051E+10 0.00 0.00 0.00 0.00 20274473.74 5569540.03
November 0.149520E+10 0.668514E+09 0.299318E+10 0.00 0.00 0.00 0.00 3712151.09 23085922.41
December 0.145684E+10 0.661365E+09 0.300927E+10 0.00 0.00 0.00 0.00 17223.94 89352593.72
                   
Annual Sum or Average 0.181198E+11 0.784764E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.600007E+09 0.387344E+09
Minimum of Months 0.136988E+10 0.606722E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 237233.05
Maximum of Months 0.163688E+10 0.697072E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.149971E+09 0.103174E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.442887E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 65237896.09
February 0.882782E+09 0.393378E+09 0.178514E+10 0.00 0.00 0.00 0.00 581743.41 74240248.53
March 0.105485E+10 0.451653E+09 0.205168E+10 0.00 0.00 0.00 0.00 9933736.39 51210616.16
April 0.936002E+09 0.396806E+09 0.190406E+10 0.00 0.00 0.00 0.00 42902077.22 5477081.40
May 0.101394E+10 0.420999E+09 0.201175E+10 0.00 0.00 0.00 0.00 95952293.50 1390249.28
June 0.101113E+10 0.418605E+09 0.197570E+10 0.00 0.00 0.00 0.00 64847965.39 860624.08
July 0.938820E+09 0.401582E+09 0.193968E+10 0.00 0.00 0.00 0.00 79797339.55 417657.28
August 0.105485E+10 0.450295E+09 0.205168E+10 0.00 0.00 0.00 0.00 44344508.65 836519.81
September 0.936002E+09 0.408421E+09 0.190319E+10 0.00 0.00 0.00 0.00 26436804.47 1614493.62
October 0.973041E+09 0.434059E+09 0.197226E+10 0.00 0.00 0.00 0.00 13660549.08 4313549.39
November 0.963541E+09 0.434075E+09 0.192888E+10 0.00 0.00 0.00 0.00 2511512.74 16353406.37
December 0.938820E+09 0.431826E+09 0.193924E+10 0.00 0.00 0.00 0.00 11544.08 64909558.66
                   
Annual Sum or Average 0.116768E+11 0.508459E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.380980E+09 0.286862E+09
Minimum of Months 0.882782E+09 0.393378E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 417657.28
Maximum of Months 0.105485E+10 0.451653E+09 0.205168E+10 0.00 0.00 0.00 0.00 95952293.50 74240248.53



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.699814E+09 0.305979E+10 0.00 0.00 0.00 0.00 248572.96 0.162873E+09
February 0.136985E+10 0.618060E+09 0.277008E+10 0.00 0.00 0.00 0.00 5589571.47 0.183880E+09
March 0.163685E+10 0.700242E+09 0.318369E+10 0.00 0.00 0.00 0.00 41723184.38 0.126652E+09
April 0.145243E+10 0.614434E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.160437E+09 11407599.23
May 0.157338E+10 0.648781E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.345358E+09 3159055.21
June 0.156900E+10 0.645214E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.233379E+09 2196876.48
July 0.145680E+10 0.617958E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.289039E+09 948669.67
August 0.163685E+10 0.693377E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.165482E+09 2084618.76
September 0.145243E+10 0.632116E+09 0.295328E+10 0.00 0.00 0.00 0.00 96987116.14 2955896.53
October 0.150991E+10 0.672517E+09 0.306046E+10 0.00 0.00 0.00 0.00 52504374.92 11088414.65
November 0.149516E+10 0.687515E+09 0.299314E+10 0.00 0.00 0.00 0.00 13353598.50 39481206.03
December 0.145680E+10 0.687661E+09 0.300922E+10 0.00 0.00 0.00 0.00 1948163.92 0.149374E+09
                   
Annual Sum or Average 0.181194E+11 0.791769E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.140605E+10 0.696102E+09
Minimum of Months 0.136985E+10 0.614434E+09 0.277008E+10 0.00 0.00 0.00 0.00 248572.96 948669.67
Maximum of Months 0.163685E+10 0.700242E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.345358E+09 0.183880E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.445223E+09 0.197184E+10 0.00 0.00 0.00 0.00 1830.17 0.122658E+09
February 0.649041E+09 0.395424E+09 0.178515E+10 0.00 0.00 0.00 0.00 1182573.72 0.139901E+09
March 0.773965E+09 0.449438E+09 0.205169E+10 0.00 0.00 0.00 0.00 22883050.49 95299133.23
April 0.688021E+09 0.395603E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.100910E+09 9838767.82
May 0.744847E+09 0.420015E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.223661E+09 2475170.31
June 0.742030E+09 0.417669E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.152646E+09 1603132.40
July 0.690839E+09 0.398721E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.188967E+09 660095.43
August 0.773965E+09 0.446095E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.107024E+09 1517567.50
September 0.688021E+09 0.405964E+09 0.190321E+10 0.00 0.00 0.00 0.00 61921674.91 2103966.49
October 0.715730E+09 0.429466E+09 0.197228E+10 0.00 0.00 0.00 0.00 31673251.11 8573911.91
November 0.708685E+09 0.440394E+09 0.192889E+10 0.00 0.00 0.00 0.00 6019738.45 30751023.07
December 0.690839E+09 0.438053E+09 0.193926E+10 0.00 0.00 0.00 0.00 297469.23 0.112463E+09
                   
Annual Sum or Average 0.858171E+10 0.508206E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.897188E+09 0.527844E+09
Minimum of Months 0.649041E+09 0.395424E+09 0.178515E+10 0.00 0.00 0.00 0.00 1830.17 660095.43
Maximum of Months 0.773965E+09 0.449438E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.223661E+09 0.139901E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.676830E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.208748E+09
February 0.136988E+10 0.606229E+09 0.277013E+10 0.00 0.00 0.00 0.00 1854101.87 0.233794E+09
March 0.163688E+10 0.696501E+09 0.318374E+10 0.00 0.00 0.00 0.00 34087256.04 0.153347E+09
April 0.145246E+10 0.615720E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.153929E+09 13976224.67
May 0.157341E+10 0.653804E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.343502E+09 3261375.94
June 0.156904E+10 0.650348E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.233426E+09 2157580.99
July 0.145684E+10 0.622180E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.288757E+09 947070.87
August 0.163688E+10 0.695029E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.163536E+09 2202662.26
September 0.145246E+10 0.630630E+09 0.295333E+10 0.00 0.00 0.00 0.00 93455888.98 3298001.79
October 0.150994E+10 0.664013E+09 0.306051E+10 0.00 0.00 0.00 0.00 46137977.69 13780196.75
November 0.149520E+10 0.667166E+09 0.299318E+10 0.00 0.00 0.00 0.00 8277972.91 53177985.58
December 0.145684E+10 0.661116E+09 0.300927E+10 0.00 0.00 0.00 0.00 29249.43 0.199788E+09
                   
Annual Sum or Average 0.181198E+11 0.783957E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.136699E+10 0.888478E+09
Minimum of Months 0.136988E+10 0.606229E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 947070.87
Maximum of Months 0.163688E+10 0.696501E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.343502E+09 0.233794E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.442139E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.125642E+09
February 0.882782E+09 0.392761E+09 0.178514E+10 0.00 0.00 0.00 0.00 1375855.16 0.143352E+09
March 0.105485E+10 0.451082E+09 0.205168E+10 0.00 0.00 0.00 0.00 23842243.54 0.103715E+09
April 0.936002E+09 0.396471E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.100966E+09 11303452.74
May 0.101394E+10 0.420511E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.222391E+09 3097422.83
June 0.101113E+10 0.418030E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.151152E+09 1976126.25
July 0.938820E+09 0.400785E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.186631E+09 834142.89
August 0.105485E+10 0.449404E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.105606E+09 1883088.87
September 0.936002E+09 0.407781E+09 0.190319E+10 0.00 0.00 0.00 0.00 61230867.45 2829019.74
October 0.973041E+09 0.433320E+09 0.197226E+10 0.00 0.00 0.00 0.00 32249068.03 8599283.05
November 0.963541E+09 0.433675E+09 0.192888E+10 0.00 0.00 0.00 0.00 6462033.16 30743588.67
December 0.938820E+09 0.431316E+09 0.193924E+10 0.00 0.00 0.00 0.00 132215.55 0.115371E+09
                   
Annual Sum or Average 0.116768E+11 0.507728E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.892038E+09 0.549346E+09
Minimum of Months 0.882782E+09 0.392761E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 834142.89
Maximum of Months 0.105485E+10 0.451082E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.222391E+09 0.143352E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.699754E+09 0.305979E+10 0.00 0.00 0.00 0.00 566388.33 0.176061E+09
February 0.136985E+10 0.617940E+09 0.277008E+10 0.00 0.00 0.00 0.00 8079403.64 0.207889E+09
March 0.163685E+10 0.700214E+09 0.318369E+10 0.00 0.00 0.00 0.00 48924002.97 0.151926E+09
April 0.145243E+10 0.614423E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.192612E+09 14931790.87
May 0.157338E+10 0.648766E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.418361E+09 4507375.82
June 0.156900E+10 0.645185E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.283396E+09 3094341.47
July 0.145680E+10 0.617923E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.349558E+09 1209991.44
August 0.163685E+10 0.693320E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.199207E+09 2742491.46
September 0.145243E+10 0.632048E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.115876E+09 4068230.60
October 0.150991E+10 0.672481E+09 0.306046E+10 0.00 0.00 0.00 0.00 63090751.44 13282307.53
November 0.149516E+10 0.687418E+09 0.299314E+10 0.00 0.00 0.00 0.00 17122171.98 44170553.85
December 0.145680E+10 0.687616E+09 0.300922E+10 0.00 0.00 0.00 0.00 3977555.97 0.162240E+09
                   
Annual Sum or Average 0.181194E+11 0.791709E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.170077E+10 0.786123E+09
Minimum of Months 0.136985E+10 0.614423E+09 0.277008E+10 0.00 0.00 0.00 0.00 566388.33 1209991.44
Maximum of Months 0.163685E+10 0.700214E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.418361E+09 0.207889E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.445208E+09 0.197184E+10 0.00 0.00 0.00 0.00 74973.73 0.132429E+09
February 0.882782E+09 0.395403E+09 0.178515E+10 0.00 0.00 0.00 0.00 1708092.92 0.159143E+09
March 0.105485E+10 0.449426E+09 0.205169E+10 0.00 0.00 0.00 0.00 28003018.22 0.114794E+09
April 0.936002E+09 0.395597E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.123753E+09 12726399.32
May 0.101394E+10 0.420000E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.273165E+09 3400890.00
June 0.101113E+10 0.417654E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.187003E+09 2223295.49
July 0.938820E+09 0.398698E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.230644E+09 854438.43
August 0.105485E+10 0.446048E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.130611E+09 1959760.59
September 0.936002E+09 0.405939E+09 0.190321E+10 0.00 0.00 0.00 0.00 75477484.51 2866737.10
October 0.973041E+09 0.429440E+09 0.197228E+10 0.00 0.00 0.00 0.00 38942773.04 10306000.97
November 0.963541E+09 0.440376E+09 0.192889E+10 0.00 0.00 0.00 0.00 7789519.44 34853817.74
December 0.938820E+09 0.438034E+09 0.193926E+10 0.00 0.00 0.00 0.00 939591.40 0.123060E+09
                   
Annual Sum or Average 0.116768E+11 0.508182E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.109811E+10 0.598617E+09
Minimum of Months 0.882782E+09 0.395403E+09 0.178515E+10 0.00 0.00 0.00 0.00 74973.73 854438.43
Maximum of Months 0.105485E+10 0.449426E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.273165E+09 0.159143E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.676823E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.235883E+09
February 0.136988E+10 0.606209E+09 0.277013E+10 0.00 0.00 0.00 0.00 2076721.70 0.272827E+09
March 0.163688E+10 0.696451E+09 0.318374E+10 0.00 0.00 0.00 0.00 40805815.44 0.185405E+09
April 0.145246E+10 0.615695E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.186679E+09 18191749.24
May 0.157341E+10 0.653774E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.416293E+09 4621930.85
June 0.156904E+10 0.650317E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.283430E+09 3047116.77
July 0.145684E+10 0.622125E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.349261E+09 1215606.37
August 0.163688E+10 0.694982E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.197206E+09 2887025.33
September 0.145246E+10 0.630593E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.112294E+09 4568338.40
October 0.150994E+10 0.663994E+09 0.306051E+10 0.00 0.00 0.00 0.00 56144408.15 16707481.32
November 0.149520E+10 0.667155E+09 0.299318E+10 0.00 0.00 0.00 0.00 9882213.52 62806099.46
December 0.145684E+10 0.661109E+09 0.300927E+10 0.00 0.00 0.00 0.00 24851.41 0.227703E+09
                   
Annual Sum or Average 0.181198E+11 0.783923E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.165410E+10 0.103586E+10
Minimum of Months 0.136988E+10 0.606209E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 1215606.37
Maximum of Months 0.163688E+10 0.696451E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.416293E+09 0.272827E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.442127E+09 0.197183E+10 0.00 0.00 0.00 0.00 3487.95 0.141864E+09
February 0.882782E+09 0.392733E+09 0.178514E+10 0.00 0.00 0.00 0.00 1656412.08 0.166624E+09
March 0.105485E+10 0.451056E+09 0.205168E+10 0.00 0.00 0.00 0.00 28553042.52 0.125571E+09
April 0.936002E+09 0.396427E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.122742E+09 14529952.05
May 0.101394E+10 0.420498E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.270852E+09 4125323.18
June 0.101113E+10 0.417975E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.184431E+09 2625553.11
July 0.938820E+09 0.400757E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.226792E+09 1114697.54
August 0.105485E+10 0.449322E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.127897E+09 2424825.45
September 0.936002E+09 0.407746E+09 0.190319E+10 0.00 0.00 0.00 0.00 73850457.38 3835568.56
October 0.973041E+09 0.433300E+09 0.197226E+10 0.00 0.00 0.00 0.00 39174706.79 10421244.69
November 0.963541E+09 0.433664E+09 0.192888E+10 0.00 0.00 0.00 0.00 7997949.58 35599802.44
December 0.938820E+09 0.431268E+09 0.193924E+10 0.00 0.00 0.00 0.00 471690.39 0.130594E+09
                   
Annual Sum or Average 0.116768E+11 0.507687E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.108442E+10 0.639330E+09
Minimum of Months 0.882782E+09 0.392733E+09 0.178514E+10 0.00 0.00 0.00 0.00 3487.95 1114697.54
Maximum of Months 0.105485E+10 0.451056E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.270852E+09 0.166624E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.147592E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.133877E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.159083E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.142093E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.153337E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.152596E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.142835E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.159083E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.142093E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.147592E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.145862E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.142835E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.176888E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.133877E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.159083E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.147592E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.133877E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.159083E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.142093E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.153337E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.152596E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.142835E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.159083E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.142093E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.147592E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.145862E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.142835E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.176888E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.133877E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.159083E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.147592E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.133877E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.159083E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.142093E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.153337E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.152596E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.142835E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.159083E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.142093E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.147592E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.145862E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.142835E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.176888E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.133877E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.159083E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.289359E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.262470E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.311888E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.278579E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.300623E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.299170E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.280033E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.311888E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.278579E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.289359E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.285968E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.280033E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.346795E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.262470E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.311888E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.191985E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1031625.82 0.207750E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28056174.00 0.132990E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124069E+09 11868096.31
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.278218E+09 3393931.52
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.189878E+09 1750303.67
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.235446E+09 764384.59
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.128161E+09 1404640.27
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76189750.52 2175254.09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38764494.25 11788537.59
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6403029.75 45948702.61
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1036.86 0.179613E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110622E+10 0.791431E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 764384.59
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.278218E+09 0.207750E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.314317E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2904242.33 0.348382E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52214112.38 0.232593E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.228524E+09 21556914.56
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.502493E+09 5903425.83
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.342198E+09 3395563.55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.428597E+09 1470472.81
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.236698E+09 2641894.05
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.136915E+09 3736819.89
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70434468.18 21110806.68
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13101610.33 77331847.15
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 569530.36 0.292440E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.201465E+10 0.132488E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1470472.81
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.502493E+09 0.348382E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.305702E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 512257.14 0.357893E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41225594.46 0.246655E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.224481E+09 22420577.14
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.532280E+09 7083634.23
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.367515E+09 3618632.55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.448635E+09 1295729.45
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.246963E+09 4438293.70
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.138026E+09 4589317.88
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65594301.92 20337880.02
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9181321.42 75593828.18
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 759053.68 0.279896E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.207517E+10 0.132952E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1295729.45
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.532280E+09 0.357893E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 10739.37 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 10739.37 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 10739.37 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 10739.37 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 10739.37 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 10739.37 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 10739.37 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 10739.37 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 10739.37 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 10739.37 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 10739.37 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 10739.37 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   10739.37   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   10739.37   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9644.71 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9644.71 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9644.71 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9644.71 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9644.71 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9644.71 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9644.71 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9644.71 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9644.71 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9644.71 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9644.71 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9644.71 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9644.71   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9644.71   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9644.71 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9644.71 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9644.71 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9644.71 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9644.71 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9644.71 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9644.71 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9644.71 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9644.71 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9644.71 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9644.71 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9644.71 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9644.71   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9644.71   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 9644.71 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 9644.71 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 9644.71 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 9644.71 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 9644.71 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 9644.71 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 9644.71 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 9644.71 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 9644.71 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 9644.71 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 9644.71 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 9644.71 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   9644.71   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   9644.71   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 994.68 18-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 222.38 15-JAN-17:00
February 2010.79 01-FEB-10:09 972.28 10-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 39.51 19-FEB-15:10 299.30 09-FEB-22:10
March 2010.79 01-MAR-10:09 981.82 14-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 171.41 26-MAR-15:00 650.43 24-MAR-24:00
April 2010.79 03-APR-09:09 634.50 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 332.82 15-APR-17:04 98.82 22-APR-18:30
May 2010.79 01-MAY-09:09 675.21 24-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 603.16 28-MAY-14:23 47.34 15-MAY-03:20
June 2010.79 01-JUN-09:09 673.98 23-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 271.67 17-JUN-20:40 47.85 18-JUN-04:30
July 2010.79 03-JUL-09:09 941.22 26-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 295.67 02-JUL-11:44 37.55 19-JUL-02:30
August 2010.79 01-AUG-09:09 974.63 16-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 193.23 06-AUG-13:43 46.79 15-AUG-23:50
September 2010.79 01-SEP-09:09 1008.11 08-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 162.58 24-SEP-14:26 25.52 08-SEP-22:10
October 2010.79 02-OCT-09:09 1067.70 11-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 178.63 15-OCT-12:50 93.63 12-OCT-03:00
November 2010.79 01-NOV-09:09 1039.27 27-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 51.73 12-NOV-13:56 157.28 28-NOV-05:00
December 2010.79 01-DEC-10:09 1050.24 29-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 13.67 24-DEC-14:00 341.81 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   634.50   2160.55   0.00 0.00 0.00 0.00 0.00   25.52  
Maximum of Months 2010.79   1067.70   2160.55   0.00 0.00 0.00 0.00 603.16   650.43  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 633.72 17-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 144.77 15-JAN-17:00
February 1295.83 01-FEB-10:09 630.23 09-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 9.75 19-FEB-15:10 192.46 09-FEB-22:10
March 1295.83 01-MAR-10:09 549.42 14-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 110.62 26-MAR-14:35 435.41 24-MAR-24:00
April 1295.83 03-APR-09:09 371.32 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 221.56 15-APR-17:04 64.11 22-APR-18:30
May 1295.83 01-MAY-09:09 421.11 24-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 398.30 28-MAY-14:43 33.88 15-MAY-03:20
June 1295.83 01-JUN-09:09 421.38 23-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 181.12 17-JUN-20:40 29.15 18-JUN-04:30
July 1295.83 03-JUL-09:09 582.94 26-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 196.65 02-JUL-11:44 21.19 19-JUL-02:30
August 1295.83 01-AUG-09:09 606.34 16-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 130.00 06-AUG-13:43 26.85 15-AUG-23:50
September 1295.83 01-SEP-09:09 629.92 08-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 108.61 24-SEP-14:24 15.09 08-SEP-22:20
October 1295.83 02-OCT-09:09 675.84 11-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 123.77 15-OCT-12:44 58.68 12-OCT-03:00
November 1295.83 01-NOV-09:09 685.90 27-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 29.25 12-NOV-14:20 102.77 28-NOV-05:00
December 1295.83 01-DEC-10:09 682.45 29-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 2.45 24-DEC-15:00 215.10 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   371.32   1392.34   0.00 0.00 0.00 0.00 0.00   15.09  
Maximum of Months 1295.83   685.90   1392.34   0.00 0.00 0.00 0.00 398.30   435.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 952.00 18-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 245.64 22-JAN-14:10
February 2010.83 01-FEB-10:09 938.17 10-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 12.62 21-FEB-15:00 294.96 09-FEB-22:10
March 2010.83 01-MAR-10:09 968.94 14-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 149.46 26-MAR-14:35 727.56 24-MAR-23:00
April 2010.83 03-APR-09:09 641.06 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 332.00 15-APR-17:04 106.03 22-APR-18:30
May 2010.83 01-MAY-09:09 779.22 24-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 597.46 28-MAY-14:44 50.64 15-MAY-03:20
June 2010.83 01-JUN-09:09 787.60 23-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 272.34 03-JUN-17:10 48.72 18-JUN-04:30
July 2010.83 03-JUL-09:09 956.70 26-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 295.42 02-JUL-11:44 37.00 19-JUL-02:30
August 2010.83 01-AUG-09:09 981.51 16-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 188.74 06-AUG-14:00 48.06 15-AUG-23:50
September 2010.83 01-SEP-09:09 1006.10 08-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 156.77 24-SEP-14:50 24.97 08-SEP-22:10
October 2010.83 02-OCT-09:09 1061.72 11-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 164.79 15-OCT-13:00 93.31 12-OCT-03:00
November 2010.83 01-NOV-09:09 917.55 27-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 36.35 12-NOV-14:55 166.67 28-NOV-05:00
December 2010.83 01-DEC-10:09 995.87 29-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 2.91 28-DEC-14:00 409.53 31-DEC-15:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   641.06   2160.58   0.00 0.00 0.00 0.00 0.00   24.97  
Maximum of Months 2010.83   1061.72   2160.58   0.00 0.00 0.00 0.00 597.46   727.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 646.41 18-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 160.72 15-JAN-17:00
February 1295.83 01-FEB-10:09 634.69 10-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 8.43 21-FEB-15:00 225.61 09-FEB-22:10
March 1295.83 01-MAR-10:09 655.81 14-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 95.74 26-MAR-15:00 599.94 24-MAR-24:00
April 1295.83 03-APR-09:09 508.34 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 220.39 15-APR-17:10 111.50 22-APR-18:00
May 1295.83 01-MAY-09:09 535.15 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 398.31 28-MAY-14:43 49.68 15-MAY-02:40
June 1295.83 01-JUN-09:09 536.33 23-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 182.05 17-JUN-20:25 48.18 18-JUN-04:30
July 1295.83 03-JUL-09:09 625.39 26-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 197.09 02-JUL-11:44 40.29 19-JUL-02:30
August 1295.83 01-AUG-09:09 641.86 16-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 125.82 06-AUG-14:00 51.87 15-AUG-23:50
September 1295.83 01-SEP-09:09 658.53 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 107.64 24-SEP-14:24 25.01 08-SEP-22:10
October 1295.83 02-OCT-09:09 691.71 11-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 122.85 15-OCT-12:04 77.60 12-OCT-03:00
November 1295.83 01-NOV-09:09 613.81 03-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 23.61 12-NOV-12:54 126.50 28-NOV-05:00
December 1295.83 01-DEC-10:09 624.41 29-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 1.95 28-DEC-14:00 274.37 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   508.34   1392.33   0.00 0.00 0.00 0.00 0.00   25.01  
Maximum of Months 1295.83   691.71   1392.33   0.00 0.00 0.00 0.00 398.31   599.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 991.98 18-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 38.39 08-JAN-14:53 430.68 15-JAN-17:00
February 2010.79 01-FEB-10:09 969.34 10-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 159.48 19-FEB-15:00 618.24 09-FEB-22:10
March 2010.79 01-MAR-10:09 978.93 14-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 454.89 26-MAR-14:50 1271.35 24-MAR-24:00
April 2010.79 03-APR-09:09 627.88 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 782.15 15-APR-17:07 212.88 22-APR-17:53
May 2010.79 01-MAY-09:09 671.28 24-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 1395.74 28-MAY-14:53 108.66 15-MAY-02:40
June 2010.79 01-JUN-09:09 669.99 23-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 629.89 03-JUN-17:10 115.27 18-JUN-04:43
July 2010.79 03-JUL-09:09 938.04 26-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 686.15 02-JUL-11:44 98.08 19-JUL-03:00
August 2010.79 01-AUG-09:09 971.87 16-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 448.74 06-AUG-13:45 130.21 15-AUG-23:53
September 2010.79 01-SEP-09:09 1005.76 08-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 379.84 24-SEP-14:54 51.07 08-SEP-22:10
October 2010.79 02-OCT-09:09 1066.06 11-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 435.27 15-OCT-11:51 193.51 12-OCT-03:00
November 2010.79 01-NOV-09:09 1036.85 27-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 178.03 12-NOV-14:00 305.46 28-NOV-05:00
December 2010.79 01-DEC-10:09 1048.25 29-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 150.88 24-DEC-13:57 653.93 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   627.88   2160.55   0.00 0.00 0.00 0.00 38.39   51.07  
Maximum of Months 2010.79   1066.06   2160.55   0.00 0.00 0.00 0.00 1395.74   1271.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 629.89 17-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 2.02 08-JAN-14:53 286.96 15-JAN-17:00
February 1239.33 01-FEB-08:09 626.29 09-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 30.88 19-FEB-15:00 411.75 09-FEB-22:10
March 1239.33 01-MAR-08:09 544.27 14-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 238.32 26-MAR-15:04 927.56 24-MAR-24:00
April 1239.33 03-APR-07:10 371.32 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 521.78 15-APR-17:06 176.54 22-APR-17:53
May 1239.33 01-MAY-07:10 418.31 24-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 930.49 28-MAY-14:53 87.79 15-MAY-02:40
June 1239.33 01-JUN-07:10 418.64 23-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 421.43 03-JUN-17:08 79.37 18-JUN-04:43
July 1239.33 03-JUL-07:10 578.29 26-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 454.42 02-JUL-11:44 65.24 19-JUL-03:00
August 1239.33 01-AUG-07:10 602.50 16-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 300.99 06-AUG-13:43 91.03 15-AUG-23:53
September 1239.33 01-SEP-07:10 626.68 08-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 254.43 24-SEP-14:54 34.41 08-SEP-22:10
October 1239.33 02-OCT-07:10 673.35 11-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 277.16 15-OCT-12:44 130.37 12-OCT-03:00
November 1239.33 01-NOV-07:10 683.47 27-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 70.48 12-NOV-14:00 215.42 28-NOV-05:00
December 1239.33 01-DEC-08:09 679.91 29-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 46.28 24-DEC-14:00 438.39 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   371.32   1392.34   0.00 0.00 0.00 0.00 2.02   34.41  
Maximum of Months 1239.33   683.47   1392.34   0.00 0.00 0.00 0.00 930.49   927.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 949.12 18-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 588.72 22-JAN-14:10
February 2010.83 01-FEB-10:09 934.98 10-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 28.20 21-FEB-15:00 647.78 18-FEB-05:55
March 2010.83 01-MAR-10:09 965.94 14-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 322.37 26-MAR-15:04 1510.14 24-MAR-24:00
April 2010.83 03-APR-09:09 634.90 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 782.58 15-APR-17:06 248.38 22-APR-17:53
May 2010.83 01-MAY-09:09 773.57 24-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 1395.74 28-MAY-14:53 117.86 15-MAY-02:40
June 2010.83 01-JUN-09:09 781.98 23-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 630.62 03-JUN-17:02 114.37 18-JUN-04:43
July 2010.83 03-JUL-09:09 953.65 26-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 685.69 02-JUL-11:44 97.74 19-JUL-03:00
August 2010.83 01-AUG-09:09 978.80 16-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 437.40 06-AUG-14:00 134.61 15-AUG-23:53
September 2010.83 01-SEP-09:09 1003.73 08-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 368.29 24-SEP-14:54 51.83 08-SEP-22:10
October 2010.83 02-OCT-09:09 1060.05 11-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 379.45 15-OCT-13:00 200.38 12-OCT-03:00
November 2010.83 01-NOV-09:09 913.69 27-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 69.56 13-NOV-14:00 366.74 29-NOV-24:00
December 2010.83 01-DEC-10:09 993.32 29-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 5.59 28-DEC-14:00 935.26 31-DEC-14:30
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   634.90   2160.58   0.00 0.00 0.00 0.00 0.00   51.83  
Maximum of Months 2010.83   1060.05   2160.58   0.00 0.00 0.00 0.00 1395.74   1510.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 642.93 18-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 303.95 15-JAN-17:00
February 1295.83 01-FEB-10:09 630.87 10-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 20.91 19-FEB-13:22 431.28 09-FEB-22:10
March 1295.83 01-MAR-10:09 652.48 14-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 233.35 26-MAR-15:03 1030.31 24-MAR-24:00
April 1295.83 03-APR-09:09 501.57 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 512.24 15-APR-17:06 173.03 22-APR-17:53
May 1295.83 01-MAY-09:09 528.64 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 930.49 28-MAY-14:56 113.90 15-MAY-02:40
June 1295.83 01-JUN-09:09 529.85 23-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 420.95 17-JUN-20:27 93.93 18-JUN-03:45
July 1295.83 03-JUL-09:09 621.31 26-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 458.05 02-JUL-11:44 70.43 19-JUL-03:00
August 1295.83 01-AUG-09:09 638.21 16-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 299.97 06-AUG-13:43 98.29 15-AUG-23:53
September 1295.83 01-SEP-09:09 655.33 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 248.57 24-SEP-14:13 37.96 08-SEP-22:10
October 1295.83 02-OCT-09:09 689.39 11-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 277.28 15-OCT-12:44 136.84 12-OCT-03:00
November 1295.83 01-NOV-09:09 609.88 03-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 68.91 12-NOV-12:51 227.11 28-NOV-05:00
December 1295.83 01-DEC-10:09 620.67 29-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 30.01 24-DEC-13:53 460.68 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   501.57   1392.33   0.00 0.00 0.00 0.00 0.00   37.96  
Maximum of Months 1295.83   689.39   1392.33   0.00 0.00 0.00 0.00 930.49   1030.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 991.54 18-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 69.93 08-JAN-14:53 463.96 15-JAN-17:00
February 2010.79 01-FEB-10:09 968.85 10-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 203.16 19-FEB-15:00 711.82 09-FEB-22:10
March 2010.79 01-MAR-10:09 978.49 14-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 510.17 26-MAR-14:30 1490.69 24-MAR-23:00
April 2010.79 03-APR-09:09 627.66 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 961.89 15-APR-17:06 249.48 22-APR-17:53
May 2010.79 01-MAY-09:09 671.12 24-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 1722.07 28-MAY-14:44 182.21 15-MAY-02:55
June 2010.79 01-JUN-09:09 669.82 23-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 778.47 03-JUN-17:08 154.53 18-JUN-03:45
July 2010.79 03-JUL-09:09 937.48 26-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 846.77 02-JUL-11:44 116.41 19-JUL-03:00
August 2010.79 01-AUG-09:09 971.38 16-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 554.47 06-AUG-13:43 165.16 15-AUG-24:00
September 2010.79 01-SEP-09:09 1005.34 08-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 466.36 24-SEP-14:15 61.83 08-SEP-22:10
October 2010.79 02-OCT-09:09 1065.76 11-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 536.50 15-OCT-11:51 226.20 12-OCT-03:00
November 2010.79 01-NOV-09:09 1036.56 27-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 209.25 12-NOV-14:00 344.15 29-NOV-24:00
December 2010.79 01-DEC-10:09 1047.93 29-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 245.58 24-DEC-13:53 738.20 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   627.66   2160.55   0.00 0.00 0.00 0.00 69.93   61.83  
Maximum of Months 2010.79   1065.76   2160.55   0.00 0.00 0.00 0.00 1722.07   1490.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 629.61 17-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 17.79 08-JAN-14:53 308.88 15-JAN-17:00
February 1295.83 01-FEB-10:09 625.98 09-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 45.74 19-FEB-15:00 473.01 09-FEB-22:10
March 1295.83 01-MAR-10:09 543.93 14-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 283.57 26-MAR-14:48 1093.85 24-MAR-23:00
April 1295.83 03-APR-09:09 371.32 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 641.81 15-APR-17:06 203.70 22-APR-17:53
May 1295.83 01-MAY-09:09 418.18 24-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 1149.25 28-MAY-14:44 136.95 15-MAY-02:55
June 1295.83 01-JUN-09:09 418.51 23-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 518.71 03-JUN-17:07 105.87 18-JUN-03:45
July 1295.83 03-JUL-09:09 577.91 26-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 551.70 02-JUL-11:44 77.06 19-JUL-03:00
August 1295.83 01-AUG-09:09 602.16 16-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 365.70 06-AUG-13:43 114.61 15-AUG-24:00
September 1295.83 01-SEP-09:09 626.39 08-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 312.49 24-SEP-14:13 41.14 08-SEP-22:10
October 1295.83 02-OCT-09:09 673.14 11-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 326.13 15-OCT-12:56 151.97 12-OCT-03:00
November 1295.83 01-NOV-09:09 683.31 27-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 80.60 12-NOV-14:10 244.50 29-NOV-24:00
December 1295.83 01-DEC-10:09 679.72 29-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 98.29 24-DEC-13:53 495.48 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   371.32   1392.34   0.00 0.00 0.00 0.00 17.79   41.14  
Maximum of Months 1295.83   683.31   1392.34   0.00 0.00 0.00 0.00 1149.25   1093.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 948.62 18-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 680.09 22-JAN-14:50
February 2010.83 01-FEB-10:09 934.44 10-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 33.26 21-FEB-15:00 732.56 18-FEB-05:55
March 2010.83 01-MAR-10:09 965.48 14-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 402.75 26-MAR-14:45 1793.34 24-MAR-23:00
April 2010.83 03-APR-09:09 634.69 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 960.14 15-APR-17:06 291.57 22-APR-17:53
May 2010.83 01-MAY-09:09 772.70 24-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 1726.14 28-MAY-14:44 191.97 15-MAY-02:55
June 2010.83 01-JUN-09:09 781.13 23-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 777.86 03-JUN-17:08 153.44 18-JUN-03:45
July 2010.83 03-JUL-09:09 953.12 26-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 846.16 02-JUL-11:44 115.97 19-JUL-03:00
August 2010.83 01-AUG-09:09 978.33 16-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 536.56 06-AUG-14:00 170.28 15-AUG-24:00
September 2010.83 01-SEP-09:09 1003.30 08-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 454.74 24-SEP-14:54 62.76 08-SEP-22:10
October 2010.83 02-OCT-09:09 1059.74 11-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 462.40 15-OCT-13:00 234.57 12-OCT-03:00
November 2010.83 01-NOV-09:09 913.29 27-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 89.34 13-NOV-14:00 433.13 29-NOV-24:00
December 2010.83 01-DEC-10:09 992.95 29-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 5.41 28-DEC-14:00 1101.76 31-DEC-14:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   634.69   2160.58   0.00 0.00 0.00 0.00 0.00   62.76  
Maximum of Months 2010.83   1059.74   2160.58   0.00 0.00 0.00 0.00 1726.14   1793.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 642.66 18-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 3.00 08-JAN-13:53 339.96 15-JAN-17:00
February 1295.83 01-FEB-10:09 630.57 10-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 37.30 19-FEB-13:22 502.53 09-FEB-22:10
March 1295.83 01-MAR-10:09 652.24 14-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 269.61 26-MAR-14:45 1222.72 24-MAR-23:00
April 1295.83 03-APR-09:09 501.24 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 629.50 15-APR-17:10 204.20 22-APR-17:53
May 1295.83 01-MAY-09:09 528.14 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 1147.07 28-MAY-14:57 160.22 15-MAY-02:55
June 1295.83 01-JUN-09:09 529.35 23-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 518.96 17-JUN-20:25 124.73 18-JUN-02:65
July 1295.83 03-JUL-09:09 620.99 26-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 565.16 02-JUL-11:44 84.06 19-JUL-03:00
August 1295.83 01-AUG-09:09 637.92 16-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 367.55 06-AUG-13:43 123.72 15-AUG-24:00
September 1295.83 01-SEP-09:09 655.07 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 305.65 24-SEP-14:13 46.11 08-SEP-22:10
October 1295.83 02-OCT-09:09 689.20 11-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 322.28 15-OCT-11:51 161.15 12-OCT-03:00
November 1295.83 01-NOV-09:09 609.64 03-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 89.86 12-NOV-12:41 266.68 29-NOV-24:00
December 1295.83 01-DEC-10:09 620.43 29-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 63.33 24-DEC-13:53 530.01 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   501.24   1392.33   0.00 0.00 0.00 0.00 3.00   46.11  
Maximum of Months 1295.83   689.20   1392.33   0.00 0.00 0.00 0.00 1147.07   1222.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 154.45 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 154.45 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 154.45 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 154.45 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 154.45 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 154.45 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 154.45 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 154.45 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 154.45 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 154.45 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 154.45 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 154.45 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   154.45   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   154.45   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 154.45 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 154.45 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 154.45 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 154.45 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 154.45 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 154.45 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 154.45 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 154.45 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 154.45 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 154.45 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 154.45 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 154.45 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   154.45   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   154.45   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 154.45 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 154.45 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 154.45 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 154.45 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 154.45 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 154.45 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 154.45 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 154.45 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 154.45 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 154.45 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 154.45 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 154.45 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   154.45   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   154.45   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 3028.04 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 3028.04 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 3028.04 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 3028.04 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 3028.04 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 3028.04 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 3028.04 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 3028.04 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 3028.04 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 3028.04 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 3028.04 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 3028.04 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   3028.04   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   3028.04   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 467.72 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.95 19-FEB-14:52 678.10 09-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 335.75 26-MAR-15:00 1461.98 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 672.46 15-APR-17:01 212.26 22-APR-18:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1178.30 28-MAY-14:50 99.31 15-MAY-03:20
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 546.59 03-JUN-17:02 102.00 18-JUN-04:35
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 563.44 02-JUL-11:31 79.96 19-JUL-02:45
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 364.79 06-AUG-14:10 94.81 15-AUG-23:57
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 320.96 24-SEP-14:10 41.45 19-SEP-04:55
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 351.92 15-OCT-12:30 187.06 12-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.15 12-NOV-14:00 351.50 28-NOV-05:14
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.73 28-DEC-14:00 738.59 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   41.45  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1178.30   1461.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 773.56 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.46 19-FEB-14:52 1172.10 09-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 665.38 26-MAR-14:52 2476.16 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1228.40 15-APR-17:01 373.21 22-APR-18:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2131.11 28-MAY-15:00 162.79 13-MAY-04:12
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 988.26 03-JUN-17:02 183.91 18-JUN-04:43
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1042.97 02-JUL-12:00 149.23 19-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 697.25 06-AUG-14:10 173.59 15-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 583.80 24-SEP-14:00 74.00 19-SEP-04:55
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 652.77 15-OCT-12:30 325.24 12-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 176.97 12-NOV-14:00 577.32 28-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.99 24-DEC-14:10 1236.32 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   74.00  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2131.11   2476.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 756.75 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.61 24-FEB-15:00 1203.36 09-FEB-22:05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 437.06 26-MAR-15:00 2491.17 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1248.34 15-APR-17:01 308.70 22-APR-18:35
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2076.77 28-MAY-15:00 214.93 15-MAY-03:02
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1040.21 03-JUN-17:10 199.20 18-JUN-04:43
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 971.99 02-JUL-11:30 144.25 19-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 648.20 06-AUG-08:52 234.73 15-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 501.70 24-SEP-14:00 70.19 19-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 581.12 15-OCT-11:51 330.84 12-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 105.11 12-NOV-14:10 540.59 28-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119.61 24-DEC-13:53 1178.41 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   70.19  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2076.77   2491.17  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 102604.11 23-JAN-05:11 0.00 5385.15 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
February 100320.84 21-FEB-05:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
March 97884.50 06-MAR-05:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
April 98320.06 30-APR-19:37 0.00 4176.30 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
May 94568.73 29-MAY-09:20 8976.13 5966.14 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
June 91092.95 04-JUN-22:58 0.00 2983.07 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 85111.30 04-JUL-19:39 0.00 4176.30 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
August 81907.29 29-AUG-03:02 0.00 3579.69 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
September 81649.01 26-SEP-03:02 0.00 2983.07 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 94943.73 29-OCT-13:47 6283.29 4176.30 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
November 100819.02 24-NOV-05:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
December 98897.67 18-DEC-05:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 81649.01   0.00 2983.07 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 102604.11   8976.13 5966.14 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 87913.53 02-JAN-05:11 0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
February 93854.92 21-FEB-05:11 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
March 91173.97 06-MAR-05:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
April 86521.39 03-APR-05:05 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
May 83015.70 30-MAY-05:03 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
June 84465.80 12-JUN-05:05 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
July 85807.67 31-JUL-05:05 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
August 86081.98 28-AUG-05:06 11285.67 3761.52 53531.73 0.00 0.00 0.00 0.00 0.00 0.00
September 85830.49 05-SEP-05:04 8061.19 2686.80 38236.95 0.00 0.00 0.00 0.00 0.00 0.00
October 94880.30 30-OCT-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
November 94797.09 20-NOV-05:11 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
December 93928.67 26-DEC-05:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 83015.70   0.00 2686.80 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 94880.30   11285.67 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 75038.83 27-JAN-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
February 80386.35 27-FEB-05:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
March 82428.36 08-MAR-05:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
April 81064.16 11-APR-04:12 0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
May 71098.18 30-MAY-05:02 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
June 73949.88 12-JUN-05:02 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
July 71016.28 19-JUL-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
August 73759.70 21-AUG-05:03 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
September 71335.14 29-SEP-03:02 0.00 2679.01 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
October 83780.46 17-OCT-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
November 82249.60 10-NOV-05:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
December 77227.17 01-DEC-06:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 71016.28   0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 83780.46   9673.43 3761.52 45884.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 28605.63 26-JAN-16:40 15316.26 9644.71 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 76497.51 23-FEB-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 83415.55 14-MAR-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
April 82952.85 10-APR-04:12 0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
May 84041.82 30-MAY-05:03 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
June 85382.66 12-JUN-05:05 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
July 85781.44 03-JUL-05:04 11285.67 3761.52 53531.53 0.00 0.00 0.00 0.00 0.00 0.00
August 84485.06 07-AUG-05:04 11285.67 3761.52 53531.53 0.00 0.00 0.00 0.00 0.00 0.00
September 77587.33 05-SEP-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
October 83280.55 12-OCT-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
November 78279.98 01-NOV-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 30271.07 01-DEC-16:30 15316.26 9644.71 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 28605.63   0.00 2149.44 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 85781.44   15316.26 9644.71 53531.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4214.76 26-JAN-14:10 4021.58 1152.38 4321.10 0.00 0.00 0.00 0.00 0.00 9.00
February 6373.12 23-FEB-14:30 2010.79 576.19 2160.55 0.00 0.00 0.00 0.00 5.79 0.00
March 13808.15 12-MAR-16:01 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 58.94 0.00
April 22628.60 30-APR-16:21 1012.16 320.10 7201.84 0.00 0.00 0.00 0.00 248.87 0.00
May 21819.36 29-MAY-16:21 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 180.12 0.00
June 23106.86 04-JUN-16:51 1012.16 320.10 7201.84 0.00 0.00 0.00 0.00 196.30 0.00
July 23644.70 04-JUL-17:01 0.00 320.10 5591.71 0.00 0.00 0.00 0.00 113.38 0.00
August 21548.46 27-AUG-15:01 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 77.50 0.00
September 16482.10 18-SEP-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 3.02 0.00
October 15797.72 15-OCT-15:21 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 122.76 0.00
November 7027.11 06-NOV-14:10 4021.58 1152.38 4321.10 0.00 0.00 0.00 0.00 3.30 0.00
December 5153.03 26-DEC-14:10 4021.58 1152.38 4321.10 0.00 0.00 0.00 0.00 0.00 1.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4214.76   0.00 224.07 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23644.70   4021.58 1152.38 7201.84 0.00 0.00 0.00 0.00 248.87 9.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4223.94 26-JAN-10:20 1295.83 371.32 1392.34 0.00 0.00 0.00 0.00 0.00 15.32
February 8359.43 20-FEB-10:43 195.68 61.88 1392.34 0.00 0.00 0.00 0.00 0.00 31.65
March 16451.20 12-MAR-15:21 456.59 144.40 3248.80 0.00 0.00 0.00 0.00 28.25 0.00
April 19282.05 30-APR-09:41 521.82 165.03 3712.91 0.00 0.00 0.00 0.00 16.84 0.00
May 18281.15 29-MAY-09:02 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 262.57 0.00
June 18124.85 04-JUN-16:11 652.28 206.28 4641.14 0.00 0.00 0.00 0.00 143.37 0.00
July 18794.43 04-JUL-15:41 652.28 206.28 4641.14 0.00 0.00 0.00 0.00 73.40 0.00
August 16731.22 06-AUG-16:21 456.59 144.40 3248.80 0.00 0.00 0.00 0.00 99.94 0.00
September 17210.96 24-SEP-10:23 260.91 82.51 1856.46 0.00 0.00 0.00 0.00 33.10 0.00
October 17360.56 01-OCT-08:43 260.91 82.51 1856.46 0.00 0.00 0.00 0.00 0.00 0.45
November 9055.59 05-NOV-10:32 260.91 82.51 1856.46 0.00 0.00 0.00 0.00 0.00 8.44
December 4808.40 01-DEC-10:00 1239.33 371.32 1392.34 0.00 0.00 0.00 0.00 0.00 6.72
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4223.94   195.68 61.88 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19282.05   1295.83 371.32 4641.14 0.00 0.00 0.00 0.00 262.57 31.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15547.10 08-JAN-13:03 303.66 96.03 2160.58 0.00 0.00 0.00 0.00 0.00 51.37
February 23942.36 20-FEB-14:02 607.31 192.06 4321.17 0.00 0.00 0.00 0.00 0.00 9.20
March 23749.35 12-MAR-13:22 607.31 192.06 4321.17 0.00 0.00 0.00 0.00 13.14 0.00
April 24147.44 30-APR-15:01 1012.19 320.10 7201.95 0.00 0.00 0.00 0.00 227.29 0.00
May 22196.66 29-MAY-15:41 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 243.36 0.00
June 23235.66 04-JUN-16:11 1012.19 320.10 7201.95 0.00 0.00 0.00 0.00 213.88 0.00
July 23836.59 04-JUL-16:21 1012.19 320.10 7201.95 0.00 0.00 0.00 0.00 112.27 0.00
August 22041.82 06-AUG-13:42 607.31 192.06 4321.17 0.00 0.00 0.00 0.00 177.64 0.00
September 22460.72 17-SEP-11:43 404.87 128.04 2880.78 0.00 0.00 0.00 0.00 84.85 0.00
October 24618.35 15-OCT-12:41 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 105.12 0.00
November 24952.97 12-NOV-13:31 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 0.00 17.53
December 22487.73 24-DEC-13:32 404.87 128.04 2880.78 0.00 0.00 0.00 0.00 0.00 80.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15547.10   303.66 96.03 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24952.97   1012.19 320.10 7201.95 0.00 0.00 0.00 0.00 243.36 80.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7103.82 31-JAN-15:50 1239.33 371.32 1392.33 0.00 0.00 0.00 0.00 0.00 8.09
February 23016.32 20-FEB-15:22 326.14 103.14 2320.55 0.00 0.00 0.00 0.00 0.00 5.25
March 25003.12 12-MAR-16:01 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 22.55 0.00
April 28490.78 30-APR-16:21 652.28 206.28 4641.11 0.00 0.00 0.00 0.00 112.34 0.00
May 24519.03 28-MAY-16:21 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 321.71 0.00
June 27406.68 04-JUN-16:11 652.28 206.28 4641.11 0.00 0.00 0.00 0.00 120.68 0.00
July 27327.96 04-JUL-16:21 652.28 206.28 4641.11 0.00 0.00 0.00 0.00 63.57 0.00
August 24332.11 06-AUG-16:21 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 83.98 0.00
September 22607.28 24-SEP-15:42 326.14 103.14 2320.55 0.00 0.00 0.00 0.00 83.17 0.00
October 24867.32 22-OCT-15:01 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 15.24 0.00
November 23801.33 12-NOV-14:52 391.37 123.77 2784.67 0.00 0.00 0.00 0.00 5.76 0.00
December 18209.53 24-DEC-15:32 260.91 82.51 1856.44 0.00 0.00 0.00 0.00 0.00 42.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7103.82   260.91 82.51 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28490.78   1239.33 371.32 4641.11 0.00 0.00 0.00 0.00 321.71 42.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2506.93 26-JAN-15:00 2010.79 576.19 2160.55 0.00 0.00 0.00 0.00 0.00 28.75
February 5175.22 24-FEB-15:00 2010.79 576.19 2160.55 0.00 0.00 0.00 0.00 24.00 0.00
March 11914.05 11-MAR-06:02 1012.16 672.75 4801.23 0.00 0.00 0.00 0.00 0.00 2.60
April 22538.99 30-APR-16:21 1012.16 320.10 7201.84 0.00 0.00 0.00 0.00 583.87 0.00
May 22346.06 28-MAY-16:41 809.73 256.08 5761.47 0.00 0.00 0.00 0.00 1158.34 0.00
June 22288.06 11-JUN-16:21 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 249.52 0.00
July 22135.88 02-JUL-17:01 0.00 224.07 3914.20 0.00 0.00 0.00 0.00 398.52 0.00
August 21484.73 27-AUG-14:51 809.73 256.08 5761.47 0.00 0.00 0.00 0.00 184.26 0.00
September 21440.57 17-SEP-13:22 607.30 192.06 4321.10 0.00 0.00 0.00 0.00 309.19 0.00
October 16738.76 01-OCT-15:11 809.73 256.08 5761.47 0.00 0.00 0.00 0.00 168.36 0.00
November 5775.81 09-NOV-14:30 2010.79 576.19 2160.55 0.00 0.00 0.00 0.00 17.61 0.00
December 2419.33 03-DEC-15:02 404.87 128.04 2880.74 0.00 0.00 0.00 0.00 2.48 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2419.33   0.00 128.04 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22538.99   2010.79 672.75 7201.84 0.00 0.00 0.00 0.00 1158.34 28.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5007.87 26-JAN-11:05 2478.65 742.64 2784.68 0.00 0.00 0.00 0.00 0.00 35.46
February 7877.91 22-FEB-11:05 2478.65 742.64 2784.68 0.00 0.00 0.00 0.00 0.00 1.09
March 18003.77 12-MAR-15:21 456.59 144.40 3248.80 0.00 0.00 0.00 0.00 62.45 0.00
April 20912.73 30-APR-09:41 521.82 165.03 3712.91 0.00 0.00 0.00 0.00 32.33 0.00
May 19621.46 29-MAY-09:22 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 603.51 0.00
June 19028.20 11-JUN-10:22 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 137.94 0.00
July 18852.76 04-JUL-10:32 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 195.83 0.00
August 17891.69 27-AUG-14:11 521.82 165.03 3712.91 0.00 0.00 0.00 0.00 129.69 0.00
September 18538.82 17-SEP-10:42 326.14 103.14 2320.57 0.00 0.00 0.00 0.00 83.81 0.00
October 19460.07 01-OCT-10:32 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 41.31 0.00
November 8335.95 01-NOV-10:05 2478.65 742.64 2784.68 0.00 0.00 0.00 0.00 0.00 1.52
December 5371.59 01-DEC-11:05 2478.65 742.64 2784.68 0.00 0.00 0.00 0.00 0.00 10.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5007.87   326.14 103.14 2320.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20912.73   2478.65 742.64 3712.91 0.00 0.00 0.00 0.00 603.51 35.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16961.52 08-JAN-13:13 303.66 96.03 2160.58 0.00 0.00 0.00 0.00 0.00 120.71
February 24085.60 20-FEB-14:32 607.31 192.06 4321.17 0.00 0.00 0.00 0.00 0.00 24.41
March 23972.15 12-MAR-13:22 607.31 192.06 4321.17 0.00 0.00 0.00 0.00 27.68 0.00
April 24044.12 30-APR-15:01 1012.19 320.10 7201.95 0.00 0.00 0.00 0.00 524.94 0.00
May 22419.06 28-MAY-16:01 809.75 256.08 5761.56 0.00 0.00 0.00 0.00 1245.25 0.00
June 22174.11 11-JUN-16:21 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 250.60 0.00
July 22086.74 02-JUL-16:21 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 414.83 0.00
August 21850.69 27-AUG-14:11 809.75 256.08 5761.56 0.00 0.00 0.00 0.00 189.12 0.00
September 23515.02 17-SEP-13:22 607.31 192.06 4321.17 0.00 0.00 0.00 0.00 251.66 0.00
October 25278.69 29-OCT-13:01 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 0.00 0.29
November 24423.32 11-NOV-14:42 607.31 192.06 4321.17 0.00 0.00 0.00 0.00 0.00 5.05
December 22383.14 24-DEC-14:13 404.87 128.04 2880.78 0.00 0.00 0.00 0.00 0.00 147.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16961.52   303.66 96.03 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25278.69   1012.19 320.10 7201.95 0.00 0.00 0.00 0.00 1245.25 147.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4911.72 31-JAN-16:10 1239.33 371.32 1392.33 0.00 0.00 0.00 0.00 0.00 20.60
February 12874.03 20-FEB-15:52 391.37 123.77 2784.67 0.00 0.00 0.00 0.00 0.00 13.70
March 21719.23 12-MAR-16:01 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 57.81 0.00
April 24499.21 30-APR-16:21 652.28 206.28 4641.11 0.00 0.00 0.00 0.00 279.95 0.00
May 23142.21 14-MAY-15:51 521.82 165.03 3712.89 0.00 0.00 0.00 0.00 69.36 0.00
June 22259.90 11-JUN-16:21 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 152.77 0.00
July 21956.15 02-JUL-16:21 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 250.97 0.00
August 20659.16 06-AUG-16:21 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 206.75 0.00
September 21645.31 17-SEP-17:21 0.00 144.40 2522.44 0.00 0.00 0.00 0.00 71.28 0.00
October 21745.64 15-OCT-15:21 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 134.57 0.00
November 19954.41 11-NOV-15:22 391.37 123.77 2784.67 0.00 0.00 0.00 0.00 11.27 0.00
December 5655.82 01-DEC-15:30 1239.33 371.32 1392.33 0.00 0.00 0.00 0.00 0.00 3.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4911.72   0.00 123.77 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24499.21   1239.33 371.32 4641.11 0.00 0.00 0.00 0.00 279.95 20.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2402.50 26-JAN-15:00 2010.79 576.19 2160.55 0.00 0.00 0.00 0.00 0.00 37.24
February 5414.81 23-FEB-14:50 2010.79 576.19 2160.55 0.00 0.00 0.00 0.00 14.07 0.00
March 10673.39 11-MAR-06:02 1012.16 672.75 4801.23 0.00 0.00 0.00 0.00 0.00 3.86
April 24785.03 16-APR-15:21 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 150.17 0.00
May 25745.27 28-MAY-16:41 809.73 256.08 5761.47 0.00 0.00 0.00 0.00 1395.76 0.00
June 25589.20 11-JUN-15:41 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 324.51 0.00
July 25457.16 02-JUL-17:01 0.00 224.07 3914.20 0.00 0.00 0.00 0.00 480.40 0.00
August 24805.63 13-AUG-15:31 910.95 288.09 6481.66 0.00 0.00 0.00 0.00 300.64 0.00
September 25285.20 17-SEP-14:51 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 353.02 0.00
October 23983.24 09-OCT-15:31 708.51 224.07 5041.29 0.00 0.00 0.00 0.00 89.56 0.00
November 6245.16 09-NOV-14:40 2010.79 576.19 2160.55 0.00 0.00 0.00 0.00 20.84 0.00
December 2231.52 28-DEC-16:00 1923.11 611.47 2160.55 0.00 0.00 0.00 0.00 0.00 4.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2231.52   0.00 224.07 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25745.27   2010.79 672.75 6481.66 0.00 0.00 0.00 0.00 1395.76 37.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2753.09 26-JAN-14:30 1295.83 371.32 1392.34 0.00 0.00 0.00 0.00 0.00 22.01
February 5979.74 23-FEB-10:40 1295.83 371.32 1392.34 0.00 0.00 0.00 0.00 0.00 6.55
March 18873.31 12-MAR-10:13 260.91 82.51 1856.46 0.00 0.00 0.00 0.00 0.00 5.57
April 20215.49 16-APR-10:02 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 51.51 0.00
May 20629.98 29-MAY-09:22 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 723.80 0.00
June 20044.34 11-JUN-10:22 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 166.98 0.00
July 19816.63 04-JUL-10:32 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 237.17 0.00
August 19137.79 13-AUG-15:31 587.05 185.65 4177.03 0.00 0.00 0.00 0.00 200.51 0.00
September 19898.65 17-SEP-14:51 456.59 144.40 3248.80 0.00 0.00 0.00 0.00 224.98 0.00
October 20344.71 01-OCT-10:32 391.37 123.77 2784.68 0.00 0.00 0.00 0.00 49.26 0.00
November 6262.71 09-NOV-10:20 1295.83 371.32 1392.34 0.00 0.00 0.00 0.00 1.87 0.00
December 2825.66 01-DEC-14:40 1295.83 371.32 1392.34 0.00 0.00 0.00 0.00 0.00 2.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2753.09   260.91 82.51 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20629.98   1295.83 371.32 4177.03 0.00 0.00 0.00 0.00 723.80 22.01



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12948.55 12-JAN-14:30 2010.83 576.20 2160.58 0.00 0.00 0.00 0.00 0.00 14.97
February 25503.83 19-FEB-14:52 506.09 160.05 3600.97 0.00 0.00 0.00 0.00 0.00 138.94
March 25653.50 05-MAR-13:52 506.09 160.05 3600.97 0.00 0.00 0.00 0.00 14.56 0.00
April 25787.49 16-APR-15:21 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 142.68 0.00
May 25789.22 28-MAY-16:01 809.75 256.08 5761.56 0.00 0.00 0.00 0.00 1500.85 0.00
June 25506.80 11-JUN-15:41 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 324.74 0.00
July 25359.77 02-JUL-16:21 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 499.94 0.00
August 25106.43 13-AUG-14:51 910.97 288.09 6481.75 0.00 0.00 0.00 0.00 292.03 0.00
September 27186.79 17-SEP-14:51 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 292.10 0.00
October 28708.14 09-OCT-13:31 809.75 256.08 5761.56 0.00 0.00 0.00 0.00 39.36 0.00
November 28126.64 05-NOV-13:41 708.53 224.07 5041.36 0.00 0.00 0.00 0.00 2.07 0.00
December 24453.37 03-DEC-14:43 404.87 128.04 2880.78 0.00 0.00 0.00 0.00 0.00 27.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12948.55   404.87 128.04 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28708.14   2010.83 576.20 6481.75 0.00 0.00 0.00 0.00 1500.85 138.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4798.38 12-JAN-15:50 1239.33 371.32 1392.33 0.00 0.00 0.00 0.00 0.00 9.42
February 9483.90 20-FEB-16:12 260.91 82.51 1856.44 0.00 0.00 0.00 0.00 0.00 25.59
March 20977.04 12-MAR-16:12 326.14 103.14 2320.55 0.00 0.00 0.00 0.00 107.31 0.00
April 24107.05 30-APR-16:31 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 424.29 0.00
May 25036.54 28-MAY-16:01 521.82 165.03 3712.89 0.00 0.00 0.00 0.00 902.52 0.00
June 24636.34 18-JUN-16:01 521.82 165.03 3712.89 0.00 0.00 0.00 0.00 44.88 0.00
July 24274.00 02-JUL-16:21 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 303.41 0.00
August 23149.71 13-AUG-16:11 587.05 185.65 4177.00 0.00 0.00 0.00 0.00 177.68 0.00
September 24098.46 17-SEP-14:51 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 195.48 0.00
October 24073.34 09-OCT-15:31 456.59 144.40 3248.78 0.00 0.00 0.00 0.00 39.72 0.00
November 21821.17 05-NOV-15:42 391.37 123.77 2784.67 0.00 0.00 0.00 0.00 3.86 0.00
December 5484.32 28-DEC-15:40 1239.33 371.32 1392.33 0.00 0.00 0.00 0.00 0.00 1.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4798.38   260.91 82.51 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25036.54   1239.33 371.32 4177.00 0.00 0.00 0.00 0.00 902.52 25.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2707.86 12-JAN-17:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.68
February 9030.83 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.12
March 10087.49 13-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.50 0.00
April 18717.63 17-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.19
May 22722.75 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.90 0.00
June 21586.04 12-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.82 0.00
July 22400.86 05-JUL-05:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.13 0.00
August 20652.55 07-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.66 0.00
September 18500.98 18-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.70 0.00
October 15005.93 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 11462.81 13-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.13
December 6529.34 26-DEC-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2707.86   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22722.75   0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.13 24.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2878.52 04-JAN-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 4511.99 22-FEB-16:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.11 0.00
March 8709.17 13-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.00 0.00
April 14658.25 17-APR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
May 17979.24 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.48 0.00
June 18838.43 12-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.53 0.00
July 18669.49 05-JUL-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96.26 0.00
August 15278.21 07-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.13 0.00
September 13366.07 25-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
October 11851.00 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 6586.91 13-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.46
December 2706.32 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.74
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2706.32   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18838.43   0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.53 86.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5088.20 12-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.87
February 12664.08 22-FEB-15:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.21 0.00
March 21680.57 28-MAR-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 27383.96 28-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 258.71 0.00
May 31466.25 01-MAY-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 331.65 0.00
June 33454.17 12-JUN-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 363.94 0.00
July 29567.99 07-JUL-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 251.96 0.00
August 26300.67 07-AUG-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 236.78 0.00
September 22161.58 26-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 105.67 0.00
October 21493.64 02-OCT-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.85 0.00
November 13964.12 09-NOV-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.08 0.00
December 6869.94 01-DEC-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.33
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5088.20   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33454.17   0.00 0.00 0.00 0.00 0.00 0.00 0.00 363.94 44.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1753.49 12-JAN-17:00 222.14 154.45 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3960.89 20-FEB-17:37 35.07 25.74 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
March 7219.29 31-MAR-24:00 0.00 8.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7852.83 17-APR-01:13 0.00 25.74 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3512.70 31-MAY-24:00 0.00 8.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5458.70 30-JUN-23:57 0.00 25.74 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7347.14 31-JUL-24:00 0.00 25.74 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7642.14 21-AUG-03:15 0.00 17.16 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 3518.47 30-SEP-24:00 0.00 17.16 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
October 5363.90 31-OCT-24:00 0.00 8.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5887.15 12-NOV-16:25 46.77 34.32 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
December 7548.01 24-DEC-17:10 23.38 17.16 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1753.49   0.00 8.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7852.83   222.14 154.45 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1570.13 12-JAN-17:00 222.14 154.45 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3540.66 20-FEB-17:37 35.07 25.74 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
March 6953.88 31-MAR-24:00 0.00 8.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7344.24 16-APR-21:02 0.00 42.90 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3386.94 31-MAY-24:00 0.00 8.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5258.48 30-JUN-23:57 0.00 25.74 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7010.52 31-JUL-24:00 0.00 25.74 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7210.26 20-AUG-17:33 0.00 34.32 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3391.14 30-SEP-24:00 0.00 17.16 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
October 5070.49 31-OCT-24:00 0.00 8.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5388.86 12-NOV-16:42 46.77 34.32 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
December 7079.40 01-DEC-17:00 222.14 154.45 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1570.13   0.00 8.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7344.24   222.14 154.45 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1593.09 12-JAN-17:00 222.14 154.45 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3562.24 22-FEB-17:00 222.14 154.45 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6906.73 31-MAR-24:00 0.00 8.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7515.39 16-APR-21:32 0.00 51.49 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
May 3331.42 31-MAY-24:00 0.00 8.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5324.76 30-JUN-23:57 0.00 25.74 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7056.25 31-JUL-23:57 0.00 25.74 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7331.85 20-AUG-17:55 0.00 17.16 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 3412.80 30-SEP-23:33 0.00 25.74 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
October 4935.21 31-OCT-24:00 0.00 8.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5441.45 05-NOV-16:35 46.77 34.32 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
December 7079.88 01-DEC-17:00 222.14 154.45 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1593.09   0.00 8.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7515.39   222.14 154.45 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91541.22 26-JAN-17:00 4808.68 3028.04 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183179.02 21-FEB-17:00 4808.68 3028.04 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358314.53 31-MAR-24:00 0.00 168.22 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 368764.31 30-APR-05:07 759.27 504.66 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
May 175825.70 31-MAY-24:00 0.00 168.22 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 268030.50 30-JUN-23:53 0.00 504.66 854173.17 0.00 0.00 0.00 0.00 0.00 0.00
July 356669.18 31-JUL-23:13 0.00 504.66 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 369293.06 15-AUG-23:57 0.00 504.66 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
September 177465.32 30-SEP-24:00 0.00 336.44 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
October 269021.50 31-OCT-24:00 0.00 168.22 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276424.23 13-NOV-17:00 4808.68 3028.04 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 367512.73 18-DEC-17:00 4808.68 3028.04 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91541.22   0.00 168.22 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369293.06   4808.68 3028.04 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.145425E+13 927747.24 12-JAN-16:10 0.973858E+11 739694.38 02-JAN-06:10
February 0.175655E+13 1188621.91 22-FEB-16:10 0.581531E+11 330521.40 11-FEB-06:10
March 0.253547E+13 1507839.97 28-MAR-15:00 0.575208E+11 71410.65 08-MAR-12:00
April 0.303968E+13 1765426.42 18-APR-15:09 0.500092E+11 66069.58 05-APR-11:20
May 0.212829E+13 1371307.23 30-MAY-14:20 0.489772E+11 61420.54 01-MAY-11:39
June 0.258782E+13 1590176.68 22-JUN-15:09 0.451610E+11 54614.85 01-JUN-11:30
July 0.307487E+13 1777723.48 05-JUL-15:00 0.434894E+11 49233.88 03-JUL-11:50
August 0.349516E+13 1885837.91 07-AUG-15:20 0.465326E+11 53564.77 31-AUG-11:50
September 0.201446E+13 1360406.26 14-SEP-15:30 0.459685E+11 60223.48 29-SEP-11:00
October 0.221866E+13 1382016.10 03-OCT-15:09 0.510096E+11 67076.48 31-OCT-11:20
November 0.236721E+13 1438647.82 08-NOV-15:00 0.535229E+11 71303.47 27-NOV-12:39
December 0.269061E+13 1394709.76 28-DEC-16:10 0.679495E+11 333856.47 23-DEC-06:10
             
Annual Sum or Average 0.293630E+14     0.665680E+12    
Minimum of Months 0.145425E+13 927747.24   0.434894E+11 49233.88  
Maximum of Months 0.349516E+13 1885837.91   0.973858E+11 739694.38  



Table of Contents

Report: EnergyConsumptionElectricityGeneratedPropaneMonthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ELECTRICITYPRODUCED:FACILITY [J] ELECTRICITYPRODUCED:FACILITY {Maximum} [W] ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} PROPANE:FACILITY [] PROPANE:FACILITY []
January 0.320515E+11 60354.50 31-JAN-12:30 0.00 0.00
February 0.356849E+11 67944.63 18-FEB-12:30 0.00 0.00
March 0.501755E+11 75618.56 26-MAR-12:30 0.00 0.00
April 0.597093E+11 83815.98 30-APR-11:00 0.00 0.00
May 0.636003E+11 87424.13 28-MAY-12:30 0.00 0.00
June 0.577043E+11 89148.19 04-JUN-12:20 0.00 0.00
July 0.446053E+11 74441.63 04-JUL-12:30 0.00 0.00
August 0.393228E+11 69163.57 06-AUG-12:30 0.00 0.00
September 0.387884E+11 68167.98 27-SEP-12:20 0.00 0.00
October 0.438730E+11 69338.35 03-OCT-12:30 0.00 0.00
November 0.370976E+11 62028.59 02-NOV-11:00 0.00 0.00
December 0.310773E+11 53765.37 02-DEC-12:20 0.00 0.00
           
Annual Sum or Average 0.533690E+12     0.00 0.00
Minimum of Months 0.310773E+11 53765.37   0.00 0.00
Maximum of Months 0.636003E+11 89148.19   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY [J]
January 0.152167E+12 0.274203E+11 0.766053E+12 0.102197E+12 0.159285E+12 0.404889E+11 0.00 0.137255E+12 0.574427E+11 0.119379E+11 0.00 0.00 0.00
February 0.137534E+12 0.229887E+11 0.978954E+12 0.923139E+11 0.155864E+12 0.389546E+11 0.00 0.227067E+12 0.896863E+11 0.131913E+11 0.00 0.00 0.00
March 0.162287E+12 0.228184E+11 0.141687E+13 0.102366E+12 0.206777E+12 0.547964E+11 0.00 0.434955E+12 0.127561E+12 0.703766E+10 0.00 0.00 0.00
April 0.144612E+12 0.196012E+11 0.165903E+13 0.988851E+11 0.239642E+12 0.731250E+11 0.00 0.658737E+12 0.145133E+12 0.919973E+09 0.00 0.00 0.00
May 0.155575E+12 0.180629E+11 0.774844E+12 0.102281E+12 0.269464E+12 0.848960E+11 0.00 0.537719E+12 0.185436E+12 15792028.04 0.00 0.00 0.00
June 0.154803E+12 0.163664E+11 0.106252E+13 0.990426E+11 0.265955E+12 0.885280E+11 0.00 0.705470E+12 0.195136E+12 0.00 0.00 0.00 0.00
July 0.145453E+12 0.176424E+11 0.139340E+13 0.102123E+12 0.254439E+12 0.936521E+11 0.00 0.860087E+12 0.208067E+12 0.00 0.00 0.00 0.00
August 0.162128E+12 0.193388E+11 0.173200E+13 0.102366E+12 0.257854E+12 0.957879E+11 0.00 0.917805E+12 0.207880E+12 0.00 0.00 0.00 0.00
September 0.145264E+12 0.209058E+11 0.740713E+12 0.988844E+11 0.223852E+12 0.807124E+11 0.00 0.513259E+12 0.190864E+12 0.00 0.00 0.00 0.00
October 0.151390E+12 0.242493E+11 0.108340E+13 0.102198E+12 0.213450E+12 0.634858E+11 0.00 0.431496E+12 0.147617E+12 0.137246E+10 0.00 0.00 0.00
November 0.150273E+12 0.259058E+11 0.135889E+13 0.989488E+11 0.181752E+12 0.472441E+11 0.00 0.374794E+12 0.115432E+12 0.139649E+11 0.00 0.00 0.00
December 0.147596E+12 0.282970E+11 0.170972E+13 0.102123E+12 0.165807E+12 0.427941E+11 0.00 0.351349E+12 0.107913E+12 0.350155E+11 0.00 0.00 0.00
                           
Annual Sum or Average 0.180908E+13 0.263597E+12 0.146764E+14 0.120373E+13 0.259414E+13 0.804465E+12 0.00 0.614999E+13 0.177817E+13 0.834554E+11 0.00 0.00 0.00
Minimum of Months 0.137534E+12 0.163664E+11 0.740713E+12 0.923139E+11 0.155864E+12 0.389546E+11 0.00 0.137255E+12 0.574427E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.162287E+12 0.282970E+11 0.173200E+13 0.102366E+12 0.269464E+12 0.957879E+11 0.00 0.917805E+12 0.208067E+12 0.350155E+11 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.389634E+11 0.00 0.584225E+11 0.00 0.00
February 0.00 0.00 0.588770E+10 0.00 0.522654E+11 0.00 0.00
March 0.00 0.00 769615.68 0.00 0.575201E+11 0.00 0.00
April 0.00 0.00 0.00 0.00 0.500092E+11 0.00 0.00
May 0.00 0.00 4853.84 0.00 0.489772E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.451610E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.434894E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.465326E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.459685E+11 0.00 0.00
October 0.00 0.00 0.00 0.00 0.510096E+11 0.00 0.00
November 0.00 0.00 0.223821E+09 0.00 0.532991E+11 0.00 0.00
December 0.00 0.00 0.114987E+11 0.00 0.564508E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.565744E+11 0.00 0.609105E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.434894E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.389634E+11 0.00 0.584225E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 169526.52 18-JAN-08:09 31088.59 01-JAN-06:10 423497.50 02-JAN-08:09 73700.54 18-JAN-08:20 100113.33 12-JAN-15:30 30076.50 02-JAN-06:10 0.00 01-JAN-00:10
February 168725.87 10-FEB-08:09 31088.59 01-FEB-06:10 541788.89 01-FEB-08:09 73700.12 10-FEB-08:20 139242.57 22-FEB-15:50 26465.25 02-FEB-06:00 0.00 01-FEB-00:10
March 169069.63 14-MAR-07:10 31088.59 01-MAR-06:10 660080.29 01-MAR-08:09 73700.30 14-MAR-07:19 178439.33 13-MAR-15:00 47571.30 24-MAR-15:50 0.00 01-MAR-00:10
April 157004.02 03-APR-07:10 31088.59 01-APR-05:10 778371.69 03-APR-07:10 73693.96 03-APR-07:19 215783.79 17-APR-15:20 49073.97 28-APR-08:30 0.00 01-APR-00:10
May 160076.05 24-MAY-07:10 31088.59 01-MAY-05:10 423497.50 01-MAY-07:10 73695.58 24-MAY-07:19 249960.72 30-MAY-14:20 48877.67 30-MAY-15:30 0.00 01-MAY-00:10
June 160180.02 23-JUN-07:10 31088.59 01-JUN-05:10 541788.89 01-JUN-07:10 73695.63 23-JUN-07:19 247297.52 13-JUN-14:20 48990.85 13-JUN-15:30 0.00 01-JUN-00:10
July 168465.95 26-JUL-07:10 31088.59 01-JUL-05:10 660080.29 03-JUL-07:10 73699.98 26-JUL-07:19 257692.66 05-JUL-15:39 50178.28 05-JUL-05:10 0.00 01-JUL-00:10
August 169665.36 16-AUG-07:10 31088.59 01-AUG-05:10 778371.69 01-AUG-07:10 73700.61 16-AUG-07:19 232795.15 07-AUG-15:20 49079.47 25-AUG-05:10 0.00 01-AUG-00:10
September 170865.07 08-SEP-07:10 31088.59 01-SEP-05:10 423497.50 01-SEP-07:10 73701.24 08-SEP-07:19 203361.80 25-SEP-15:00 48007.84 14-SEP-14:30 0.00 01-SEP-00:10
October 173230.55 11-OCT-07:10 31088.59 01-OCT-05:10 541788.89 02-OCT-07:10 73702.49 11-OCT-07:19 184857.67 10-OCT-15:20 51292.27 23-OCT-13:50 0.00 01-OCT-00:10
November 169663.27 27-NOV-16:00 31088.59 01-NOV-05:10 660080.29 01-NOV-07:10 73696.31 03-NOV-07:19 147444.45 13-NOV-16:10 48853.82 13-NOV-14:39 0.00 01-NOV-00:10
December 171472.83 29-DEC-16:00 31088.59 01-DEC-06:10 778371.69 01-DEC-08:09 73695.66 29-DEC-08:20 115975.31 01-DEC-15:30 27213.63 23-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 157004.02   31088.59   423497.50   73693.96   100113.33   26465.25   0.00  
Maximum of Months 173230.55   31088.59   778371.69   73702.49   257692.66   51292.27   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY {Maximum} [W] COGENERATION:ELECTRICITY {TIMESTAMP}
January 133971.83 25-JAN-14:09 44716.36 12-JAN-15:50 7507.81 21-JAN-17:40 0.00 0.00 0.00 01-JAN-00:10
February 236674.73 22-FEB-15:30 47861.78 24-FEB-15:39 11117.36 04-FEB-05:00 0.00 0.00 0.00 01-FEB-00:10
March 352881.33 28-MAR-12:50 81944.93 06-MAR-16:19 13972.83 01-MAR-05:00 0.00 0.00 0.00 01-MAR-00:10
April 452153.11 18-APR-15:50 81944.93 01-APR-14:30 9630.04 15-APR-11:09 0.00 0.00 0.00 01-APR-00:10
May 408317.71 30-MAY-15:09 81944.93 01-MAY-06:30 2109.98 28-MAY-14:00 0.00 0.00 0.00 01-MAY-00:10
June 513297.33 22-JUN-15:39 81944.93 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 01-JUN-00:10
July 524573.86 05-JUL-15:00 81944.93 01-JUL-00:30 0.00 01-JUL-00:10 0.00 0.00 0.00 01-JUL-00:10
August 543998.76 28-AUG-14:30 81944.93 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 01-AUG-00:10
September 408118.82 14-SEP-15:30 81944.93 01-SEP-00:40 0.00 01-SEP-00:10 0.00 0.00 0.00 01-SEP-00:10
October 364296.10 03-OCT-14:00 81944.93 02-OCT-07:49 7288.97 31-OCT-04:00 0.00 0.00 0.00 01-OCT-00:10
November 343368.44 01-NOV-14:30 81944.93 06-NOV-11:00 15157.45 30-NOV-22:00 0.00 0.00 0.00 01-NOV-00:10
December 240106.77 28-DEC-15:09 45326.42 28-DEC-14:00 28549.56 22-DEC-05:00 0.00 0.00 0.00 01-DEC-00:10
                     
Annual Sum or Average             0.00 0.00    
Minimum of Months 133971.83   44716.36   0.00   0.00 0.00 0.00  
Maximum of Months 543998.76   81944.93   28549.56   0.00 0.00 0.00  



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 927747.24 12-JAN-16:10 154946.42 423497.50 0.00 52593.86 96730.63 24781.12 0.00 130506.43 44691.28
February 1188621.91 22-FEB-16:10 154097.63 541788.89 0.00 52593.86 136880.05 25540.88 0.00 231029.53 46691.07
March 1507839.97 28-MAR-15:00 154097.63 660080.29 0.00 52593.86 162684.79 46951.07 0.00 349487.40 81944.93
April 1765426.42 18-APR-15:09 154097.63 778371.69 0.00 52593.86 203202.86 47486.75 0.00 447728.70 81944.93
May 1371307.23 30-MAY-14:20 154097.63 423497.50 0.00 24462.42 249960.72 48162.32 0.00 389181.71 81944.93
June 1590176.68 22-JUN-15:09 154097.63 541788.89 0.00 52593.86 205640.06 48709.90 0.00 505401.41 81944.93
July 1777723.48 05-JUL-15:00 154097.63 660080.29 0.00 52593.86 255729.02 48703.89 0.00 524573.86 81944.93
August 1885837.91 07-AUG-15:20 154097.63 778371.69 0.00 52593.86 232795.15 48566.18 0.00 537468.48 81944.93
September 1360406.26 14-SEP-15:30 154097.63 423497.50 0.00 52593.86 192150.16 48003.37 0.00 408118.82 81944.93
October 1382016.10 03-OCT-15:09 154097.63 541788.89 0.00 52593.86 140594.01 47859.05 0.00 363137.72 81944.93
November 1438647.82 08-NOV-15:00 154884.42 660080.29 0.00 24462.42 136469.23 46624.13 0.00 334182.39 81944.93
December 1394709.76 28-DEC-16:10 155058.91 778371.69 0.00 52594.24 105342.39 24825.27 0.00 233373.14 45144.12
                       
Annual Sum or Average                      
Minimum of Months 927747.24   154097.63 423497.50 0.00 24462.42 96730.63 24781.12 0.00 130506.43 44691.28
Maximum of Months 1885837.91   155058.91 778371.69 0.00 52594.24 255729.02 48709.90 0.00 537468.48 81944.93



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 732413.50 02-JAN-06:10 0.00 74436.05 20-JAN-12:30 0.00
February 0.00 0.00 302384.50 11-FEB-06:10 0.00 74216.81 01-FEB-12:30 0.00
March 0.00 0.00 266.81 01-MAR-06:40 0.00 71410.65 08-MAR-12:00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 66069.58 05-APR-11:20 0.00
May 0.00 0.00 8.09 16-MAY-15:39 0.00 61420.54 01-MAY-11:39 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 54614.85 01-JUN-11:30 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 49233.88 03-JUL-11:50 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 53564.77 31-AUG-11:50 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 60223.48 29-SEP-11:00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 67076.48 31-OCT-11:20 0.00
November 0.00 0.00 34440.29 27-NOV-06:30 0.00 71303.47 27-NOV-12:39 0.00
December 0.00 0.00 326575.59 23-DEC-06:10 0.00 73927.44 27-DEC-12:00 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 49233.88   0.00
Maximum of Months 0.00 0.00 732413.50   0.00 74436.05   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.33 26.43 0.50 26.51
February 0.00 0.00 0.00 0.00 2.83 26.26 0.00 26.26
March 0.00 0.00 0.00 0.00 0.83 25.86 0.00 25.86
April 0.00 0.00 0.00 0.00 1.83 26.35 0.00 26.35
May 0.00 0.00 0.00 0.00 4.17 26.21 0.17 26.25
June 0.00 0.00 0.00 0.00 4.50 26.16 0.17 26.11
July 0.00 0.00 0.00 0.00 8.17 26.21 0.83 26.31
August 0.00 0.00 0.00 0.00 10.33 25.78 0.67 25.75
September 0.00 0.00 0.00 0.00 11.83 26.54 1.33 26.56
October 0.00 0.00 0.00 0.00 9.00 26.98 0.67 26.96
November 0.00 0.00 0.00 0.00 8.33 26.95 0.83 26.94
December 0.00 0.00 0.00 0.00 7.33 27.02 0.83 27.05
                 
Annual Sum or Average 0.00   0.00   74.50 26.47 6.00 26.49
Minimum of Months 0.00 0.00 0.00 0.00 0.83 25.78 0.00 25.75
Maximum of Months 0.00 0.00 0.00 0.00 11.83 27.02 1.33 27.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.17 25.80 0.00 25.80
May 0.00 0.00 0.00 0.00 0.83 25.69 0.00 25.69
June 0.00 0.00 0.00 0.00 1.00 25.67 0.00 25.67
July 0.00 0.00 0.00 0.00 2.17 25.65 0.17 25.57
August 0.00 0.00 0.00 0.00 3.00 25.62 0.50 25.48
September 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
October 0.00 0.00 0.00 0.00 0.67 25.61 0.00 25.61
November 0.00 0.00 0.00 0.00 0.50 25.68 0.00 25.68
December 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
                 
Annual Sum or Average 0.00   0.00   9.83 25.66 0.67 25.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.00 25.80 0.50 25.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 18.90 0.00 18.90 0.00 18.90 0.00 18.90
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.67 25.93 0.00 25.93
June 0.00 0.00 0.00 0.00 0.50 25.69 0.00 25.69
July 0.00 0.00 0.00 0.00 0.83 25.95 0.00 25.95
August 0.00 0.00 0.00 0.00 0.17 25.69 0.00 25.69
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.67 18.90 0.00 18.90 2.17 24.22 0.00 24.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 18.90 0.00 18.90 0.83 25.95 0.00 25.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 12.67 27.05 6.00 27.21
May 0.00 0.00 0.00 0.00 22.83 27.19 9.50 27.33
June 0.00 0.00 0.00 0.00 22.67 26.97 6.50 27.12
July 0.00 0.00 0.00 0.00 31.33 27.22 12.50 27.35
August 0.00 0.00 0.00 0.00 24.83 27.00 8.17 27.16
September 0.00 0.00 0.00 0.00 4.50 26.87 2.50 27.06
October 0.00 0.00 0.00 0.00 0.83 27.31 0.83 27.31
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   119.67 27.09 46.00 27.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 31.33 27.31 12.50 27.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 27.38 0.33 27.38
March 0.00 0.00 0.00 0.00 4.17 27.49 4.17 27.49
April 0.00 0.00 0.00 0.00 19.00 27.48 12.17 27.62
May 0.00 0.00 0.00 0.00 30.50 27.48 13.00 27.69
June 0.00 0.00 0.00 0.00 25.67 27.14 9.83 27.31
July 0.00 0.00 0.00 0.00 29.67 27.43 13.50 27.59
August 0.00 0.00 0.00 0.00 18.50 27.18 8.50 27.36
September 0.00 0.00 0.00 0.00 8.83 27.26 5.17 27.41
October 0.00 0.00 0.00 0.00 10.50 27.55 9.83 27.57
November 0.00 0.00 0.00 0.00 0.67 27.33 0.67 27.33
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   147.83 27.36 77.17 27.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 30.50 27.55 13.50 27.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.17 27.45 1.17 27.45
February 0.00 0.00 0.00 0.00 5.17 27.80 5.17 27.80
March 0.00 0.00 0.00 0.00 7.83 27.72 6.50 27.77
April 0.00 0.00 0.00 0.00 21.83 27.32 10.33 27.48
May 0.00 0.00 0.00 0.00 26.33 27.26 10.17 27.41
June 0.00 0.00 0.00 0.00 22.50 26.99 6.83 27.14
July 0.00 0.00 0.00 0.00 31.67 27.24 12.83 27.37
August 0.00 0.00 0.00 0.00 25.50 27.07 8.33 27.25
September 0.00 0.00 0.00 0.00 11.67 27.12 5.00 27.34
October 0.00 0.00 0.00 0.00 20.00 27.69 13.17 27.80
November 0.00 0.00 0.00 0.00 12.00 28.00 11.50 28.02
December 0.00 0.00 0.00 0.00 5.83 27.61 5.83 27.61
                 
Annual Sum or Average 0.00   0.00   191.50 27.33 96.83 27.50
Minimum of Months 0.00 0.00 0.00 0.00 1.17 26.99 1.17 27.14
Maximum of Months 0.00 0.00 0.00 0.00 31.67 28.00 13.17 28.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 3.67 27.74 3.67 27.74
March 0.00 0.00 0.00 0.00 18.67 27.38 7.67 27.53
April 0.00 0.00 0.00 0.00 77.50 27.83 23.50 27.91
May 0.00 0.00 0.00 0.00 64.50 27.59 19.00 27.70
June 0.00 0.00 0.00 0.00 65.83 27.62 18.17 27.70
July 0.00 0.00 0.00 0.00 79.83 27.74 24.00 27.82
August 0.00 0.00 0.00 0.00 79.67 27.82 21.83 27.87
September 0.00 0.00 0.00 0.00 31.17 27.08 10.50 27.24
October 0.00 0.00 0.00 0.00 27.33 27.47 11.50 27.63
November 0.00 0.00 0.00 0.00 11.00 27.54 8.00 27.67
December 0.00 0.00 0.00 0.00 4.50 27.55 4.50 27.55
                 
Annual Sum or Average 0.00   0.00   463.67 27.65 152.33 27.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 79.83 27.83 24.00 27.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.17 0.00 19.17 0.00 19.17 0.00 19.17
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 6.67 27.20 3.83 27.33
May 0.00 0.00 0.00 0.00 25.50 27.26 9.83 27.39
June 0.00 0.00 0.00 0.00 21.83 27.01 6.00 27.16
July 0.00 0.00 0.00 0.00 27.33 27.21 11.50 27.35
August 0.00 0.00 0.00 0.00 14.00 26.85 6.17 27.06
September 0.00 0.00 0.00 0.00 4.50 27.12 2.50 27.24
October 0.00 0.00 0.00 0.00 0.83 27.33 0.83 27.33
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.17 0.00 19.17 100.67 27.11 40.67 27.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.17 0.00 19.17 27.33 27.33 11.50 27.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.26 0.00 19.26 0.00 19.26 0.00 19.26
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 5.17 27.54 4.83 27.55
April 0.00 0.00 0.00 0.00 20.33 27.60 12.33 27.74
May 0.00 0.00 0.00 0.00 35.67 27.54 13.33 27.77
June 0.00 0.00 0.00 0.00 33.33 27.26 10.67 27.41
July 0.00 0.00 0.00 0.00 33.67 27.43 14.83 27.60
August 0.00 0.00 0.00 0.00 19.67 27.12 8.50 27.34
September 0.00 0.00 0.00 0.00 10.17 27.28 5.67 27.45
October 0.00 0.00 0.00 0.00 10.67 27.68 9.83 27.69
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.26 0.00 19.26 168.67 27.41 80.00 27.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.26 0.00 19.26 35.67 27.68 14.83 27.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.00 27.56 1.00 27.56
February 0.00 0.00 0.00 0.00 4.83 27.86 4.83 27.86
March 0.00 0.00 0.00 0.00 7.33 27.80 6.17 27.83
April 0.00 0.00 0.00 0.00 16.33 27.45 8.83 27.59
May 0.00 0.00 0.00 0.00 27.67 27.29 10.00 27.44
June 0.00 0.00 0.00 0.00 21.33 27.01 6.33 27.16
July 0.00 0.00 0.00 0.00 27.83 27.22 11.67 27.37
August 0.00 0.00 0.00 0.00 16.83 27.03 7.17 27.24
September 0.00 0.00 0.00 0.00 12.83 27.12 5.33 27.34
October 0.00 0.00 0.00 0.00 22.50 27.47 15.17 27.52
November 0.00 0.00 0.00 0.00 11.83 28.06 11.33 28.07
December 0.00 0.00 0.00 0.00 4.33 27.64 4.33 27.64
                 
Annual Sum or Average 0.00   0.00   174.67 27.35 92.17 27.50
Minimum of Months 0.00 0.00 0.00 0.00 1.00 27.01 1.00 27.16
Maximum of Months 0.00 0.00 0.00 0.00 27.83 28.06 15.17 28.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.17 27.48 1.17 27.48
March 0.00 0.00 0.00 0.00 5.17 27.76 3.50 27.81
April 0.00 0.00 0.00 0.00 30.67 27.49 10.33 27.63
May 0.00 0.00 0.00 0.00 54.50 27.58 16.00 27.70
June 0.00 0.00 0.00 0.00 46.00 27.48 11.83 27.59
July 0.00 0.00 0.00 0.00 50.17 27.49 15.83 27.61
August 0.00 0.00 0.00 0.00 29.33 27.18 8.83 27.36
September 0.00 0.00 0.00 0.00 17.67 27.09 6.33 27.27
October 0.00 0.00 0.00 0.00 11.00 27.74 6.33 27.89
November 0.00 0.00 0.00 0.00 2.33 27.54 2.33 27.54
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   248.00 27.46 82.50 27.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 54.50 27.76 16.00 27.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 18.74 0.17 18.48 0.00 18.48 0.00 18.48
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 10.83 27.41 5.83 27.51
May 0.00 0.00 0.00 0.00 30.83 27.49 10.83 27.62
June 0.00 0.00 0.00 0.00 30.00 27.24 8.00 27.38
July 0.00 0.00 0.00 0.00 33.83 27.40 13.17 27.54
August 0.00 0.00 0.00 0.00 19.83 27.12 7.33 27.29
September 0.00 0.00 0.00 0.00 7.67 27.31 4.17 27.42
October 0.00 0.00 0.00 0.00 2.17 27.47 1.67 27.48
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 19.34 0.00 19.34 0.00 19.34 0.00 19.34
                 
Annual Sum or Average 2.83 18.88 0.17 18.67 135.17 27.15 51.00 27.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.34 0.17 19.34 33.83 27.49 13.17 27.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 19.10 0.00 19.10 0.00 19.10 0.00 19.10
February 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
March 0.00 0.00 0.00 0.00 5.67 27.55 5.00 27.56
April 0.00 0.00 0.00 0.00 23.00 27.72 12.67 27.86
May 0.00 0.00 0.00 0.00 40.33 27.69 13.83 27.91
June 0.00 0.00 0.00 0.00 40.00 27.41 11.50 27.55
July 0.00 0.00 0.00 0.00 42.83 27.57 16.17 27.72
August 0.00 0.00 0.00 0.00 23.67 27.28 8.83 27.48
September 0.00 0.00 0.00 0.00 12.33 27.43 6.83 27.58
October 0.00 0.00 0.00 0.00 11.83 27.74 9.67 27.77
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.39 0.00 19.39 0.00 19.39 0.00 19.39
                 
Annual Sum or Average 2.00 19.18 0.00 19.18 199.67 27.46 84.50 27.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 19.44 0.00 19.44 42.83 27.74 16.17 27.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 18.81 0.00 18.81 0.17 20.92 0.17 22.19
February 0.00 0.00 0.00 0.00 4.00 27.82 4.00 27.82
March 0.00 0.00 0.00 0.00 7.17 27.90 5.83 27.93
April 0.00 0.00 0.00 0.00 19.83 27.58 9.17 27.73
May 0.00 0.00 0.00 0.00 33.00 27.48 11.00 27.64
June 0.00 0.00 0.00 0.00 28.83 27.23 7.83 27.37
July 0.00 0.00 0.00 0.00 34.67 27.41 13.17 27.55
August 0.00 0.00 0.00 0.00 21.33 27.23 7.67 27.41
September 0.00 0.00 0.00 0.00 14.83 27.33 6.67 27.52
October 0.00 0.00 0.00 0.00 18.17 28.17 11.50 28.32
November 0.00 0.00 0.00 0.00 10.67 28.03 10.17 28.05
December 0.00 0.00 0.00 0.00 1.83 27.56 1.83 27.56
                 
Annual Sum or Average 0.50 18.81 0.00 18.81 194.50 27.50 89.00 27.67
Minimum of Months 0.00 0.00 0.00 0.00 0.17 20.92 0.17 22.19
Maximum of Months 0.50 18.81 0.00 18.81 34.67 28.17 13.17 28.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 18.85 0.00 18.85 0.00 18.85 0.00 18.85
February 0.00 0.00 0.00 0.00 1.00 27.51 1.00 27.51
March 0.00 0.00 0.00 0.00 5.50 27.86 3.67 27.91
April 0.00 0.00 0.00 0.00 32.00 27.63 10.67 27.78
May 0.00 0.00 0.00 0.00 57.00 27.69 16.17 27.83
June 0.00 0.00 0.00 0.00 51.17 27.58 13.33 27.70
July 0.00 0.00 0.00 0.00 53.83 27.60 16.33 27.74
August 0.00 0.00 0.00 0.00 31.67 27.37 9.50 27.53
September 0.00 0.00 0.00 0.00 20.67 27.22 8.00 27.39
October 0.00 0.00 0.00 0.00 11.50 27.96 6.67 28.08
November 0.00 0.00 0.00 0.00 2.17 27.61 2.17 27.61
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 18.85 0.00 18.85 266.50 27.57 87.50 27.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 18.85 0.00 18.85 57.00 27.96 16.33 28.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 131.17 28.20 110.33 28.20
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 363.00 28.15 272.17 28.16
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   494.17 28.17 382.50 28.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 363.00 28.20 272.17 28.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 108.67 28.13 95.33 28.12
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 251.50 28.03 206.00 28.03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   360.17 28.06 301.33 28.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 251.50 28.13 206.00 28.12



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 116.50 28.27 99.17 28.25
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 237.00 28.15 189.83 28.14
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   353.50 28.19 289.00 28.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 237.00 28.27 189.83 28.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 548.17 29.49 410.17 29.59
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 28.32 0.00 28.32
August 0.00 0.00 0.00 0.00 743.17 30.27 514.00 30.35
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1292.33 29.94 924.17 30.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 743.17 30.27 514.00 30.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 24.25 250.17 25.05 0.17 25.05
February 12.00 26.63 341.17 24.74 12.00 24.80
March 35.33 25.02 422.33 24.55 35.33 24.58
April 40.67 24.17 402.17 24.59 40.67 24.56
May 289.67 24.45 487.33 24.50 289.67 24.49
June 355.50 24.54 496.00 24.50 355.50 24.51
July 338.00 24.93 497.00 24.75 338.00 24.81
August 249.67 25.01 514.00 24.66 249.67 24.74
September 311.00 24.89 485.00 24.70 311.00 24.75
October 110.50 25.15 501.50 24.72 110.50 24.78
November 0.50 27.34 463.50 24.66 0.50 24.66
December 1.17 24.00 352.50 24.83 0.00 24.83
             
Annual Sum or Average 1746.17 24.78 5212.67 24.66 1743.00 24.68
Minimum of Months 0.50 24.00 250.17 24.50 0.00 24.49
Maximum of Months 355.50 27.34 514.00 25.05 355.50 25.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 25.33 24.77 193.50 24.78 12.83 24.84
February 4.17 25.81 337.17 24.43 3.33 24.45
March 0.83 26.52 452.33 24.30 0.83 24.31
April 0.00 0.00 448.00 24.28 0.00 24.28
May 0.00 0.00 496.83 24.21 0.00 24.21
June 0.00 0.00 496.00 24.20 0.00 24.20
July 0.00 0.00 497.00 24.28 0.00 24.28
August 0.00 0.00 514.00 24.25 0.00 24.25
September 0.33 26.51 485.00 24.26 0.33 24.26
October 0.00 0.00 502.00 24.35 0.00 24.35
November 0.00 0.00 466.17 24.44 0.00 24.44
December 4.83 24.01 331.83 24.55 0.00 24.55
             
Annual Sum or Average 35.50 24.85 5219.83 24.33 17.33 24.34
Minimum of Months 0.00 0.00 193.50 24.20 0.00 24.20
Maximum of Months 25.33 26.52 514.00 24.78 12.83 24.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 289.33 23.22 66.67 23.33 13.83 23.27
February 108.83 23.65 189.00 24.05 8.67 24.09
March 7.50 24.30 377.50 24.26 2.33 24.27
April 0.50 23.94 401.67 24.19 0.00 24.19
May 0.00 0.00 489.17 24.13 0.00 24.13
June 1.17 26.25 496.00 24.15 1.17 24.16
July 0.00 0.00 497.00 24.16 0.00 24.16
August 0.00 0.00 514.00 24.17 0.00 24.17
September 2.83 25.85 485.00 24.24 2.83 24.25
October 0.00 0.00 492.83 24.29 0.00 24.29
November 13.17 23.67 353.50 24.27 0.00 24.27
December 185.00 23.47 63.33 23.71 0.00 23.71
             
Annual Sum or Average 608.33 23.41 4425.67 24.11 28.83 24.11
Minimum of Months 0.00 0.00 63.33 23.33 0.00 23.27
Maximum of Months 289.33 26.25 514.00 24.29 13.83 24.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 450.17 22.28 29.67 22.15 24.00 22.02
February 233.33 22.95 111.50 23.33 8.67 23.37
March 39.50 23.57 350.33 24.14 3.50 24.15
April 0.17 26.64 419.33 24.27 0.17 24.27
May 3.67 26.55 502.83 24.27 3.67 24.29
June 2.83 26.38 496.00 24.25 2.83 24.27
July 0.50 26.56 497.00 24.28 0.50 24.29
August 0.00 0.00 514.00 24.23 0.00 24.23
September 2.33 25.94 484.17 24.30 2.33 24.31
October 0.50 24.00 482.67 24.27 0.50 24.27
November 114.17 23.20 235.67 23.84 0.00 23.84
December 397.67 22.63 23.00 22.64 8.33 22.60
             
Annual Sum or Average 1244.83 22.68 4146.17 23.86 54.50 23.84
Minimum of Months 0.00 0.00 23.00 22.15 0.00 22.02
Maximum of Months 450.17 26.64 514.00 24.30 24.00 24.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 394.50 22.86 16.83 22.90 0.00 22.90
February 176.50 23.15 148.67 23.63 0.00 23.63
March 21.17 23.52 388.33 24.24 0.17 24.24
April 21.50 26.94 459.17 24.59 21.50 24.69
May 43.17 26.88 508.00 24.70 43.17 24.86
June 45.67 26.72 496.00 24.65 45.67 24.81
July 71.17 26.82 497.00 24.88 71.17 25.09
August 41.33 26.85 514.00 24.63 41.33 24.78
September 37.67 26.49 485.00 24.60 37.67 24.72
October 9.67 26.75 492.50 24.44 9.67 24.48
November 53.33 23.48 322.17 24.17 0.00 24.17
December 283.33 23.20 43.83 23.33 0.00 23.33
             
Annual Sum or Average 1199.00 23.91 4371.50 24.32 270.33 24.43
Minimum of Months 9.67 22.86 16.83 22.90 0.00 22.90
Maximum of Months 394.50 26.94 514.00 24.88 71.17 25.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 269.83 22.97 48.50 23.15 0.00 23.15
February 109.83 23.06 218.67 23.94 0.33 23.94
March 34.17 24.88 428.83 24.40 14.17 24.47
April 43.33 27.01 466.50 24.73 43.33 24.91
May 57.00 27.03 508.00 24.81 57.00 25.02
June 53.83 26.79 496.00 24.70 53.83 24.89
July 70.33 26.89 497.00 24.88 70.33 25.10
August 38.17 26.90 514.00 24.58 38.17 24.73
September 44.00 26.55 485.00 24.65 44.00 24.79
October 43.17 26.86 494.33 24.68 43.17 24.84
November 49.83 23.78 370.83 24.34 5.67 24.37
December 232.00 23.11 107.33 23.52 0.00 23.52
             
Annual Sum or Average 1045.50 24.41 4635.00 24.46 370.00 24.61
Minimum of Months 34.17 22.97 48.50 23.15 0.00 23.15
Maximum of Months 269.83 27.03 514.00 24.88 70.33 25.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 196.67 22.97 196.67 23.66 1.00 23.67
February 95.33 23.55 303.50 24.27 14.00 24.37
March 38.50 25.85 447.00 24.54 25.50 24.66
April 40.50 26.98 471.83 24.73 40.50 24.89
May 44.33 26.93 508.00 24.72 44.33 24.89
June 45.50 26.73 496.00 24.65 45.50 24.81
July 69.50 26.84 497.00 24.87 69.50 25.09
August 42.67 26.89 514.00 24.64 42.67 24.80
September 48.00 26.64 485.00 24.70 48.00 24.86
October 52.50 27.08 502.00 24.84 52.50 25.04
November 57.67 26.19 433.00 24.79 43.67 24.97
December 116.83 23.58 274.83 24.26 13.17 24.35
             
Annual Sum or Average 848.00 25.05 5128.83 24.59 440.33 24.75
Minimum of Months 38.50 22.97 196.67 23.66 1.00 23.67
Maximum of Months 196.67 27.08 514.00 24.87 69.50 25.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 164.67 23.33 167.17 23.86 0.00 23.86
February 38.50 24.77 340.67 24.57 14.00 24.65
March 39.33 26.98 499.83 24.72 39.33 24.87
April 104.17 26.86 485.00 25.06 104.17 25.33
May 98.83 26.95 508.00 25.01 98.83 25.28
June 92.00 26.91 496.00 24.94 92.00 25.21
July 116.83 26.97 497.00 25.15 116.83 25.44
August 99.17 26.99 514.00 24.98 99.17 25.26
September 81.67 26.84 485.00 24.93 81.67 25.17
October 73.00 26.95 502.00 24.96 73.00 25.18
November 37.33 26.98 469.17 24.82 37.33 24.97
December 23.50 25.57 363.67 24.72 13.00 24.79
             
Annual Sum or Average 969.00 26.20 5327.50 24.86 769.33 25.09
Minimum of Months 23.50 23.33 167.17 23.86 0.00 23.86
Maximum of Months 164.67 26.99 514.00 25.15 116.83 25.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.50 21.64 46.00 21.51 46.00 21.39
February 337.83 22.48 47.33 22.66 1.83 22.65
March 104.50 23.27 296.67 23.97 0.00 23.97
April 15.67 26.60 435.00 24.54 14.17 24.61
May 45.00 26.87 508.00 24.72 45.00 24.88
June 57.50 26.62 496.00 24.70 57.50 24.88
July 95.50 26.58 497.00 24.93 95.50 25.16
August 57.83 26.52 514.00 24.67 57.83 24.84
September 55.33 26.30 485.00 24.66 55.33 24.81
October 21.00 24.07 467.67 24.34 5.50 24.36
November 211.33 22.92 138.83 23.38 0.00 23.38
December 488.00 22.06 26.17 21.97 26.17 21.89
             
Annual Sum or Average 1986.00 22.95 3957.67 23.89 404.83 23.99
Minimum of Months 15.67 21.64 26.17 21.51 0.00 21.39
Maximum of Months 496.50 26.87 514.00 24.93 95.50 25.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 389.50 22.28 20.50 22.20 17.33 22.12
February 172.33 22.70 117.00 23.39 0.00 23.39
March 51.00 24.34 324.33 24.47 15.83 24.57
April 47.33 27.03 388.67 24.96 47.33 25.16
May 67.67 27.02 430.00 25.02 67.67 25.26
June 68.83 26.79 418.00 24.92 68.83 25.15
July 102.50 26.71 422.00 25.15 102.50 25.40
August 60.50 26.70 433.00 24.84 60.50 25.05
September 64.50 26.47 410.00 24.88 64.50 25.07
October 48.00 26.55 409.50 24.83 44.17 25.01
November 95.67 23.17 246.67 24.11 1.17 24.12
December 323.50 22.53 7.33 22.53 3.33 22.50
             
Annual Sum or Average 1491.33 23.89 3627.00 24.39 493.17 24.58
Minimum of Months 47.33 22.28 7.33 22.20 0.00 22.12
Maximum of Months 389.50 27.03 433.00 25.15 102.50 25.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 247.33 22.50 165.33 23.19 6.33 23.16
February 131.83 23.09 256.50 24.02 14.17 24.13
March 57.83 24.83 416.00 24.49 23.50 24.60
April 33.50 27.00 459.50 24.72 33.50 24.86
May 46.33 26.91 508.00 24.74 46.33 24.91
June 55.67 26.62 496.00 24.69 55.67 24.87
July 94.50 26.58 497.00 24.93 94.50 25.16
August 59.00 26.61 514.00 24.69 59.00 24.87
September 66.17 26.50 485.00 24.78 66.17 24.97
October 54.67 27.08 497.17 24.89 54.67 25.09
November 78.67 25.31 407.17 24.70 42.83 24.90
December 181.00 22.99 216.67 23.86 11.50 23.93
             
Annual Sum or Average 1106.50 24.53 4918.33 24.53 508.17 24.70
Minimum of Months 33.50 22.50 165.33 23.19 6.33 23.16
Maximum of Months 247.33 27.08 514.00 24.93 94.50 25.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 406.67 22.21 37.00 22.24 14.83 22.18
February 204.67 22.71 153.67 23.43 1.33 23.44
March 49.17 24.48 392.50 24.41 14.83 24.50
April 51.50 27.00 477.17 24.83 51.50 25.02
May 89.50 26.94 508.00 24.97 89.50 25.22
June 86.17 26.83 496.00 24.89 86.17 25.14
July 107.83 26.82 497.00 25.06 107.83 25.33
August 72.50 26.84 514.00 24.81 72.50 25.04
September 75.83 26.66 485.00 24.86 75.83 25.07
October 32.67 26.91 489.83 24.69 32.67 24.82
November 94.33 23.50 305.17 24.16 8.67 24.22
December 354.67 22.60 61.67 22.81 3.67 22.79
             
Annual Sum or Average 1625.50 23.97 4417.00 24.37 559.33 24.57
Minimum of Months 32.67 22.21 37.00 22.24 1.33 22.18
Maximum of Months 406.67 27.00 514.00 25.06 107.83 25.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.50 21.11 134.67 20.84 134.67 20.67
February 366.50 22.09 60.33 22.14 26.00 22.03
March 138.67 22.98 283.33 23.82 1.67 23.83
April 30.67 26.03 433.83 24.59 22.50 24.70
May 56.67 26.88 508.00 24.78 56.67 24.97
June 65.17 26.67 496.00 24.75 65.17 24.95
July 104.67 26.59 497.00 24.97 104.67 25.21
August 64.83 26.53 514.00 24.70 64.83 24.88
September 60.00 26.34 485.00 24.70 60.00 24.86
October 47.33 24.03 435.00 24.33 14.33 24.38
November 279.17 22.55 117.33 22.97 3.50 22.94
December 492.50 21.47 81.33 21.24 81.33 21.06
             
Annual Sum or Average 2204.67 22.66 4045.83 23.65 635.33 23.68
Minimum of Months 30.67 21.11 60.33 20.84 1.67 20.67
Maximum of Months 498.50 26.88 514.00 24.97 134.67 25.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 473.17 21.77 72.00 21.51 70.33 21.30
February 238.67 22.44 139.00 22.98 10.67 22.91
March 71.50 23.69 386.17 24.27 13.00 24.35
April 55.67 26.86 462.33 24.84 53.17 25.04
May 75.50 27.02 508.00 24.92 75.50 25.16
June 73.83 26.80 496.00 24.82 73.83 25.05
July 108.17 26.72 497.00 25.03 108.17 25.29
August 67.67 26.67 514.00 24.75 67.67 24.95
September 69.67 26.48 485.00 24.78 69.67 24.97
October 61.33 25.79 473.33 24.66 44.50 24.83
November 138.50 22.72 256.67 23.74 1.50 23.73
December 432.00 22.13 39.33 21.96 39.33 21.82
             
Annual Sum or Average 1865.67 23.42 4328.83 24.10 627.33 24.22
Minimum of Months 55.67 21.77 39.33 21.51 1.50 21.30
Maximum of Months 473.17 27.02 514.00 25.03 108.17 25.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 299.00 21.92 166.33 22.32 49.50 22.09
February 172.17 22.55 226.50 23.58 17.50 23.61
March 83.00 24.13 386.50 24.37 23.50 24.49
April 43.33 26.69 454.33 24.75 39.33 24.91
May 59.17 26.90 508.00 24.80 59.17 25.00
June 65.17 26.66 496.00 24.74 65.17 24.94
July 104.33 26.59 497.00 24.97 104.33 25.21
August 66.00 26.59 514.00 24.72 66.00 24.91
September 70.00 26.51 485.00 24.80 70.00 25.00
October 62.83 26.60 482.83 24.85 55.33 25.05
November 111.00 24.24 364.83 24.47 37.83 24.67
December 240.83 22.35 185.83 23.12 21.17 23.04
             
Annual Sum or Average 1376.83 24.01 4767.17 24.36 608.83 24.51
Minimum of Months 43.33 21.92 166.33 22.32 17.50 22.09
Maximum of Months 299.00 26.90 514.00 24.97 104.33 25.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 428.00 21.71 92.67 21.52 76.50 21.32
February 246.83 22.34 135.67 22.97 10.00 22.93
March 85.50 23.84 370.50 24.29 15.83 24.38
April 54.67 26.96 467.17 24.86 53.83 25.06
May 92.00 26.97 508.00 24.99 92.00 25.25
June 88.50 26.82 496.00 24.90 88.50 25.15
July 112.17 26.82 497.00 25.08 112.17 25.35
August 77.83 26.82 514.00 24.83 77.83 25.06
September 79.83 26.65 485.00 24.88 79.83 25.09
October 47.83 25.93 475.17 24.65 35.50 24.79
November 162.33 23.06 260.83 23.86 8.33 23.92
December 391.17 22.08 76.17 22.12 34.33 21.98
             
Annual Sum or Average 1866.67 23.58 4378.17 24.17 684.67 24.32
Minimum of Months 47.83 21.71 76.17 21.52 8.33 21.32
Maximum of Months 428.00 26.97 514.00 25.08 112.17 25.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 22.67 27.00 514.00 27.00 22.67 27.00
April 324.17 27.47 485.00 27.38 324.17 27.41
May 23.83 27.00 508.00 27.00 23.83 27.00
June 96.83 27.00 496.00 27.00 96.83 27.00
July 213.00 27.00 497.00 27.00 213.00 27.00
August 472.17 27.75 514.00 27.72 472.17 27.73
September 13.83 27.00 485.00 27.00 13.83 27.00
October 21.33 27.00 502.00 27.00 21.33 27.00
November 17.17 27.00 489.00 27.00 17.17 27.00
December 5.50 27.00 497.00 27.00 5.50 27.00
             
Annual Sum or Average 1210.50 27.42 5943.00 27.14 1210.50 27.18
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 472.17 27.75 514.00 27.72 472.17 27.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 493.67 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.17 27.00 514.00 27.00 0.17 27.00
April 111.33 28.00 485.00 27.40 111.33 27.49
May 5.67 27.00 508.00 27.00 5.67 27.00
June 7.33 27.00 496.00 27.00 7.33 27.00
July 15.00 27.00 497.00 27.00 15.00 27.00
August 223.83 27.99 514.00 27.65 223.83 27.73
September 2.83 27.00 485.00 27.00 2.83 27.00
October 1.83 27.00 502.00 27.00 1.83 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 368.00 27.90 5934.67 27.11 368.00 27.16
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 223.83 28.00 514.00 27.65 223.83 27.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 34.50 24.68 435.67 26.78 4.33 26.74
February 0.00 0.00 454.00 27.00 0.00 27.00
March 2.83 27.00 514.00 27.00 2.83 27.00
April 144.50 27.94 485.00 27.44 144.50 27.53
May 53.67 27.00 508.00 27.00 53.67 27.00
June 73.50 27.00 496.00 27.00 73.50 27.00
July 67.33 27.00 497.00 27.00 67.33 27.00
August 231.00 28.02 514.00 27.66 231.00 27.74
September 12.50 27.00 485.00 27.00 12.50 27.00
October 13.50 27.00 502.00 27.00 13.50 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 487.50 27.00 0.00 27.00
             
Annual Sum or Average 633.33 27.46 5867.17 27.10 603.17 27.14
Minimum of Months 0.00 0.00 435.67 26.78 0.00 26.74
Maximum of Months 231.00 28.02 514.00 27.66 231.00 27.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.01 454.00 27.01 454.00 27.01
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 29.32 485.00 29.32 485.00 29.32
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 30.46 514.00 30.46 514.00 30.46
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5943.00 27.49 5943.00 27.49 5943.00 27.49
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 30.46 514.00 30.46 514.00 30.46



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00070 28.75272 0.82814 19.49948
February 454.00000 27.00094 29.00837 0.88768 21.66786
March 514.00000 27.00062 30.53726 0.95999 24.49246
April 485.00000 27.31617 31.97276 1.09701 30.60261
May 508.00000 27.00059 36.89159 0.32604 7.25448
June 496.00000 27.00250 36.54377 0.36910 7.87473
July 497.00000 27.00172 35.68128 0.40299 8.43563
August 514.00000 27.69159 34.10332 0.62389 13.88136
September 485.00000 27.00005 39.76765 0.32869 7.28034
October 502.00000 27.00168 32.57582 0.96140 24.54844
November 489.00000 27.00066 29.78156 0.95200 24.17334
December 497.00000 27.00021 27.64487 0.93523 23.50475
           
Annual Sum or Average 5943.00000 27.08642 32.79135 0.72123 17.72386
Minimum of Months 454.00000 27.00005 27.64487 0.32604 7.25448
Maximum of Months 514.00000 27.69159 39.76765 1.09701 30.60261



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.98868 29.43994 0.73537 16.49010
February 454.00000 27.00090 29.11334 0.80316 18.66376
March 514.00000 27.00059 30.53998 0.88566 21.59931
April 485.00000 27.25920 32.01878 0.99703 26.20726
May 508.00000 27.00043 37.08694 0.28273 6.70320
June 496.00000 27.00244 36.67815 0.30188 6.93420
July 497.00000 27.00173 35.79726 0.30616 6.99237
August 514.00000 27.49558 34.31834 0.42740 9.33439
September 485.00000 27.00001 40.28471 0.27931 6.65087
October 502.00000 27.00161 32.66929 0.90507 22.32710
November 489.00000 27.00063 29.79603 0.85995 20.65050
December 497.00000 27.00022 27.63185 0.79359 18.34498
           
Annual Sum or Average 5943.00000 27.06377 32.96781 0.62974 15.03130
Minimum of Months 454.00000 26.98868 27.63185 0.27931 6.65087
Maximum of Months 514.00000 27.49558 40.28471 0.99703 26.20726



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.79763 30.72163 0.64946 14.74092
February 454.00000 27.00089 29.25535 0.76996 17.64169
March 514.00000 27.00060 30.57891 0.88070 21.46589
April 485.00000 27.29236 32.00722 1.01693 27.16324
May 508.00000 27.00057 37.01506 0.31411 7.16125
June 496.00000 27.00247 36.65097 0.33350 7.41539
July 497.00000 27.00176 35.79096 0.33398 7.42375
August 514.00000 27.49411 34.33053 0.44744 9.95338
September 485.00000 27.00004 40.20491 0.29393 6.86569
October 502.00000 27.00162 32.72002 0.90513 22.36874
November 489.00000 27.00065 29.85649 0.83511 19.82832
December 497.00000 27.00024 27.68329 0.73601 16.57596
           
Annual Sum or Average 5943.00000 27.05024 33.08851 0.62486 14.84633
Minimum of Months 454.00000 26.79763 27.68329 0.29393 6.86569
Maximum of Months 514.00000 27.49411 40.20491 1.01693 27.16324



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00498 30.03116 1.06392 28.89036
February 454.00000 27.00582 30.18843 1.21673 36.07381
March 514.00000 27.00310 30.99648 1.36320 43.56386
April 485.00000 29.32322 31.13249 1.97388 73.96455
May 508.00000 27.00338 34.95356 0.53955 11.15868
June 496.00000 27.00310 35.05482 0.76784 17.43744
July 497.00000 27.00168 34.44745 0.98427 25.47393
August 514.00000 30.46419 31.85826 2.18938 82.98118
September 485.00000 27.00396 35.52220 0.61177 12.90903
October 502.00000 27.00277 31.97651 1.28512 39.50975
November 489.00000 27.00431 30.62145 1.40324 45.68640
December 497.00000 27.00608 30.04603 1.51236 51.57243
           
Annual Sum or Average 5943.00000 27.49245 32.24617 1.24409 39.17928
Minimum of Months 454.00000 27.00168 30.03116 0.53955 11.15868
Maximum of Months 514.00000 30.46419 35.52220 2.18938 82.98118



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.53197 39.91959 0.48943 10.59825
February 454.00000 24.50623 44.50412 0.51808 11.12782
March 514.00000 24.41858 48.27742 0.52938 11.32305
April 485.00000 24.52765 47.49935 0.55108 11.93433
May 508.00000 24.50675 58.76408 -0.2246 7.07139
June 496.00000 24.47817 62.31974 -0.1949 7.00369
July 497.00000 24.63341 62.80120 -0.1271 7.28441
August 514.00000 24.49128 61.64941 -0.1611 7.15819
September 485.00000 24.57153 63.26187 -0.1440 7.25030
October 502.00000 24.62072 55.87744 0.65318 14.69409
November 489.00000 24.61945 47.13455 0.58637 12.89236
December 497.00000 24.59433 40.00635 0.51909 11.26765
           
Annual Sum or Average 5943.00000 24.54130 52.73826 0.24673 9.95180
Minimum of Months 454.00000 24.41858 39.91959 -0.2246 7.00369
Maximum of Months 514.00000 24.63341 63.26187 0.65318 14.69409



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.31380 42.73313 0.44805 9.75431
February 454.00000 24.31717 45.30990 0.48915 10.28034
March 514.00000 24.26492 49.00983 0.52770 11.04521
April 485.00000 24.26431 48.64407 0.54755 11.48839
May 508.00000 24.20895 54.52695 -0.2993 7.08311
June 496.00000 24.19900 56.26090 -0.2812 6.84153
July 497.00000 24.27598 56.46001 -0.2487 6.61173
August 514.00000 24.24968 56.26798 -0.2404 6.53725
September 485.00000 24.25649 57.17863 -0.2751 6.89561
October 502.00000 24.34624 54.36230 0.59166 12.60087
November 489.00000 24.41556 48.01183 0.55573 11.83167
December 497.00000 24.38326 40.71636 0.48007 10.14186
           
Annual Sum or Average 5943.00000 24.29079 50.83778 0.18829 9.24567
Minimum of Months 454.00000 24.19900 40.71636 -0.2993 6.53725
Maximum of Months 514.00000 24.41556 57.17863 0.59166 12.60087



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.59347 44.63893 0.24397 6.73703
February 454.00000 24.00931 46.14741 0.38444 8.43273
March 514.00000 24.19011 49.13220 0.47998 10.00735
April 485.00000 24.16240 49.21782 0.49010 10.14205
May 508.00000 24.13046 54.99352 -0.3491 7.64551
June 496.00000 24.14988 56.94417 -0.3287 7.40661
July 497.00000 24.16036 57.72177 -0.3265 7.35811
August 514.00000 24.16866 57.98138 -0.3229 7.35373
September 485.00000 24.22628 57.68728 -0.3151 7.35124
October 502.00000 24.28020 54.83736 0.55189 11.57926
November 489.00000 24.19919 48.53279 0.46948 9.81700
December 497.00000 23.86132 42.36652 0.31331 7.33982
           
Annual Sum or Average 5943.00000 24.09465 51.73327 0.10471 8.42909
Minimum of Months 454.00000 23.59347 42.36652 -0.3491 6.73703
Maximum of Months 514.00000 24.28020 57.98138 0.55189 11.57926



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.45832 46.42256 -0.0486 7.27985
February 454.00000 23.46113 48.06029 0.24435 7.30088
March 514.00000 24.10026 49.75424 0.45958 9.67862
April 485.00000 24.22910 49.27130 0.52252 10.92937
May 508.00000 24.25514 54.57775 -0.2754 7.00959
June 496.00000 24.24083 56.50864 -0.2641 6.85824
July 497.00000 24.28089 57.25825 -0.2592 6.80893
August 514.00000 24.23197 57.78929 -0.2781 6.93098
September 485.00000 24.28799 57.68791 -0.2784 7.05548
October 502.00000 24.25529 55.51137 0.55046 11.53648
November 489.00000 23.86835 50.11964 0.38202 8.49047
December 497.00000 22.89642 45.37223 0.06810 6.43838
           
Annual Sum or Average 5943.00000 23.88338 52.39987 0.06655 8.02939
Minimum of Months 454.00000 22.45832 45.37223 -0.2784 6.43838
Maximum of Months 514.00000 24.28799 57.78929 0.55046 11.53648



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.09660 44.25550 0.11710 6.15418
February 454.00000 23.73492 46.23591 0.31524 7.75246
March 514.00000 24.19544 48.31685 0.49816 10.50856
April 485.00000 24.45101 47.08742 0.62696 13.86540
May 508.00000 24.51696 52.51997 -0.0922 6.42880
June 496.00000 24.46411 54.48452 -0.0756 6.23884
July 497.00000 24.59665 54.96846 -0.0414 6.74636
August 514.00000 24.44625 55.07203 -0.0917 6.38334
September 485.00000 24.44985 56.07513 -0.1557 6.53777
October 502.00000 24.38393 53.39976 0.60097 12.97089
November 489.00000 24.12576 48.27472 0.45043 9.54898
December 497.00000 23.56680 42.50063 0.23723 6.78404
           
Annual Sum or Average 5943.00000 24.17183 50.30165 0.19760 8.32117
Minimum of Months 454.00000 23.09660 42.50063 -0.1557 6.15418
Maximum of Months 514.00000 24.59665 56.07513 0.62696 13.86540



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.46683 42.88970 0.21725 6.76991
February 454.00000 23.95467 45.33151 0.39356 9.06351
March 514.00000 24.28099 47.77490 0.55900 12.17757
April 485.00000 24.50034 46.70277 0.69057 15.88668
May 508.00000 24.56473 52.17908 0.00484 6.73214
June 496.00000 24.47618 54.32237 -0.0292 6.34391
July 497.00000 24.59028 54.95596 -0.0260 6.96330
August 514.00000 24.41194 55.17991 -0.1022 6.45926
September 485.00000 24.47288 55.84230 -0.1104 6.44980
October 502.00000 24.48142 52.77989 0.65989 14.87204
November 489.00000 24.25218 47.59507 0.50745 11.02322
December 497.00000 23.67495 42.00024 0.27687 7.38525
           
Annual Sum or Average 5943.00000 24.26246 49.83541 0.25172 9.16704
Minimum of Months 454.00000 23.46683 42.00024 -0.1104 6.34391
Maximum of Months 514.00000 24.59028 55.84230 0.69057 15.88668



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.73797 41.58213 0.32373 8.57143
February 454.00000 24.14506 44.50633 0.48154 11.14693
March 514.00000 24.35818 47.42890 0.60761 13.48553
April 485.00000 24.51723 46.73971 0.68579 15.68440
May 508.00000 24.52875 52.44889 -0.0740 6.47528
June 496.00000 24.46230 54.49175 -0.0778 6.27285
July 497.00000 24.59627 54.96622 -0.0403 6.77241
August 514.00000 24.45546 55.00719 -0.0763 6.42630
September 485.00000 24.51005 55.69871 -0.0817 6.50953
October 502.00000 24.60792 52.19323 0.74645 17.73236
November 489.00000 24.51539 46.31687 0.65564 15.12807
December 497.00000 24.14879 40.22898 0.44792 10.49048
           
Annual Sum or Average 5943.00000 24.38300 49.34356 0.29766 10.37220
Minimum of Months 454.00000 23.73797 40.22898 -0.0817 6.27285
Maximum of Months 514.00000 24.60792 55.69871 0.74645 17.73236



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.92576 41.33909 0.34393 8.14659
February 454.00000 24.38645 43.80206 0.53525 11.74804
March 514.00000 24.52694 46.88651 0.69279 15.91772
April 485.00000 24.67514 46.12898 0.84255 21.04036
May 508.00000 24.63285 51.96733 0.07741 7.23900
June 496.00000 24.57988 53.89044 0.10815 7.16493
July 497.00000 24.72059 54.24665 0.13344 7.88942
August 514.00000 24.58993 54.25185 0.14131 7.47639
September 485.00000 24.60818 55.25079 -0.0007 6.75664
October 502.00000 24.66544 52.07572 0.76165 18.17234
November 489.00000 24.62019 46.10477 0.66745 15.23425
December 497.00000 24.49831 39.17516 0.53944 11.79785
           
Annual Sum or Average 5943.00000 24.53624 48.80357 0.40195 11.52905
Minimum of Months 454.00000 23.92576 39.17516 -0.0007 6.75664
Maximum of Months 514.00000 24.72059 55.25079 0.84255 21.04036



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.66919 47.11388 -0.2435 7.59759
February 454.00000 22.86609 48.24328 0.08881 6.63836
March 514.00000 23.98208 48.63768 0.42019 9.24645
April 485.00000 24.41690 47.15482 0.59145 12.89482
May 508.00000 24.52932 52.68886 -0.0933 6.51507
June 496.00000 24.47978 55.25304 -0.0780 6.34415
July 497.00000 24.61506 56.46567 -0.0511 6.85733
August 514.00000 24.45612 56.87397 -0.1227 6.53194
September 485.00000 24.47318 57.20578 -0.1599 6.75339
October 502.00000 24.29752 53.83367 0.55923 11.94845
November 489.00000 23.53601 49.80864 0.28536 7.44072
December 497.00000 22.09819 45.77666 -0.1301 6.65710
           
Annual Sum or Average 5943.00000 23.79167 51.61843 0.08824 7.95506
Minimum of Months 454.00000 21.66919 45.77666 -0.2435 6.34415
Maximum of Months 514.00000 24.61506 57.20578 0.59145 12.89482



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.43218 44.81272 -0.0541 6.64732
February 385.00000 23.54636 45.49062 0.26753 7.94536
March 433.00000 24.31190 46.68872 0.53891 12.01063
April 410.00000 24.66595 45.64175 0.71036 16.71701
May 430.00000 24.70466 51.84336 0.04357 7.28275
June 418.00000 24.61714 54.63635 0.01208 6.76141
July 422.00000 24.76869 55.93048 0.02631 7.52898
August 433.00000 24.58359 56.34222 -0.0591 6.79719
September 410.00000 24.62876 56.70626 -0.0714 6.84458
October 427.00000 24.59296 52.48352 0.66645 15.28672
November 417.00000 24.07288 47.40933 0.43586 9.92305
December 422.00000 22.87863 43.36970 0.06229 6.49280
           
Annual Sum or Average 5034.00000 24.15300 50.14689 0.21397 9.18589
Minimum of Months 385.00000 22.43218 43.36970 -0.0714 6.49280
Maximum of Months 433.00000 24.76869 56.70626 0.71036 16.71701



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.37632 41.85204 0.22443 8.30938
February 454.00000 23.93203 44.47861 0.41567 10.50292
March 514.00000 24.30847 47.08445 0.57912 12.95321
April 485.00000 24.52252 46.66460 0.66655 15.14837
May 508.00000 24.54146 52.61197 -0.0751 6.54037
June 496.00000 24.47781 55.26062 -0.0814 6.36174
July 497.00000 24.61641 56.44726 -0.0483 6.87886
August 514.00000 24.47547 56.70973 -0.0996 6.57001
September 485.00000 24.54707 56.68791 -0.0745 6.75274
October 502.00000 24.63953 52.12437 0.74748 17.88882
November 489.00000 24.42784 45.93392 0.62218 14.47512
December 497.00000 23.84241 40.43166 0.35436 9.67303
           
Annual Sum or Average 5943.00000 24.31097 49.73789 0.26721 10.15638
Minimum of Months 454.00000 23.37632 40.43166 -0.0996 6.36174
Maximum of Months 514.00000 24.63953 56.70973 0.74748 17.88882



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.55658 44.51285 -0.0156 6.81398
February 454.00000 23.53814 45.97350 0.27462 8.23004
March 514.00000 24.27015 47.39457 0.54913 12.10815
April 485.00000 24.58805 46.49697 0.71930 16.89462
May 508.00000 24.61852 52.26016 0.03392 7.20339
June 496.00000 24.55193 54.84595 0.03472 6.91061
July 497.00000 24.67947 56.00861 0.02374 7.43230
August 514.00000 24.52635 56.37566 -0.0437 6.76777
September 485.00000 24.57635 56.60076 -0.0604 6.89660
October 502.00000 24.52371 52.80584 0.66837 15.21183
November 489.00000 24.08353 47.61327 0.45669 10.21869
December 497.00000 23.02914 43.00886 0.10701 6.79903
           
Annual Sum or Average 5943.00000 24.13238 50.36389 0.22791 9.28677
Minimum of Months 454.00000 22.55658 43.00886 -0.0604 6.76777
Maximum of Months 514.00000 24.67947 56.60076 0.71930 16.89462



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.13027 47.99144 -0.4007 10.66162
February 454.00000 22.45423 49.29937 -0.0207 7.22515
March 514.00000 23.84109 49.28096 0.38953 9.18457
April 485.00000 24.42676 47.54643 0.60937 13.52057
May 508.00000 24.54917 52.79379 -0.0586 6.70904
June 496.00000 24.49277 55.34391 -0.0453 6.49468
July 497.00000 24.63242 56.63464 -0.0207 7.13168
August 514.00000 24.46518 57.09925 -0.0997 6.62373
September 485.00000 24.49201 57.57492 -0.1390 6.86381
October 502.00000 24.22989 54.61489 0.54891 11.93503
November 489.00000 23.17388 51.14886 0.19517 7.26564
December 497.00000 21.48752 47.13403 -0.2990 8.90230
           
Annual Sum or Average 5943.00000 23.62327 52.23090 0.05493 8.54568
Minimum of Months 454.00000 21.13027 47.13403 -0.4007 6.49468
Maximum of Months 514.00000 24.63242 57.57492 0.60937 13.52057



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.89349 46.11209 -0.2013 8.51831
February 454.00000 23.23643 46.73558 0.18918 7.77235
March 514.00000 24.17306 47.78838 0.52360 11.83998
April 485.00000 24.56126 46.85919 0.72235 17.02360
May 508.00000 24.60554 52.39161 0.06145 7.29141
June 496.00000 24.52401 55.01397 0.02919 6.76092
July 497.00000 24.66101 56.35141 0.03037 7.54070
August 514.00000 24.49309 56.78839 -0.0540 6.73256
September 485.00000 24.53990 57.13621 -0.0687 6.82121
October 502.00000 24.45113 53.43862 0.65302 14.91815
November 489.00000 23.79980 48.61310 0.37396 9.25833
December 497.00000 22.37330 44.86177 -0.0764 7.32948
           
Annual Sum or Average 5943.00000 23.94758 51.04480 0.18118 9.31853
Minimum of Months 454.00000 21.89349 44.86177 -0.2013 6.73256
Maximum of Months 514.00000 24.66101 57.13621 0.72235 17.02360



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.84438 42.83403 0.06855 8.98308
February 454.00000 23.61282 45.36830 0.32472 10.05336
March 514.00000 24.20575 47.66749 0.55556 12.76992
April 485.00000 24.52272 47.11761 0.68190 15.73511
May 508.00000 24.55941 52.73191 -0.0413 6.77239
June 496.00000 24.49073 55.35337 -0.0487 6.51014
July 497.00000 24.63349 56.62175 -0.0181 7.16134
August 514.00000 24.48172 56.95231 -0.0777 6.68801
September 485.00000 24.55700 57.09722 -0.0568 6.94633
October 502.00000 24.57935 52.90901 0.73815 17.72986
November 489.00000 24.22612 46.86939 0.56379 13.62018
December 497.00000 23.37000 41.57557 0.21506 9.13889
           
Annual Sum or Average 5943.00000 24.17699 50.30208 0.24056 10.16438
Minimum of Months 454.00000 22.84438 41.57557 -0.0777 6.51014
Maximum of Months 514.00000 24.63349 57.09722 0.73815 17.72986



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.04528 45.34427 -0.1593 8.62434
February 454.00000 23.18742 46.89506 0.18249 8.21614
March 514.00000 24.16856 47.96092 0.52668 11.96869
April 485.00000 24.58730 46.95067 0.73368 17.47003
May 508.00000 24.62589 52.42058 0.06205 7.55673
June 496.00000 24.55560 54.98269 0.06235 7.19657
July 497.00000 24.68633 56.21842 0.04891 7.74835
August 514.00000 24.52694 56.63835 -0.0248 6.91778
September 485.00000 24.58300 57.00446 -0.0442 7.06685
October 502.00000 24.46886 53.55041 0.66070 15.13141
November 489.00000 23.81902 48.71131 0.38914 9.69616
December 497.00000 22.49789 44.20571 -0.0363 7.54772
           
Annual Sum or Average 5943.00000 23.98483 50.94219 0.19956 9.59371
Minimum of Months 454.00000 22.04528 44.20571 -0.1593 6.91778
Maximum of Months 514.00000 24.68633 57.00446 0.73368 17.47003



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.529598E+11 94718.97 25-JAN-14:05 406.86 0.286804E+12 0.00 0.339764E+12 2.73 7.51 25-JAN-14:05 0.00 0.00
February 0.804879E+11 155255.69 22-FEB-15:30 401.29 0.509359E+12 0.00 0.589847E+12 3.39 7.95 21-FEB-16:00 0.00 0.00
March 0.152377E+12 177192.13 10-MAR-13:30 553.39 0.108038E+13 0.00 0.123276E+13 4.80 7.95 14-MAR-05:05 0.00 0.00
April 0.206353E+12 182755.31 18-APR-17:10 674.33 0.149409E+13 0.00 0.170044E+13 6.28 7.95 07-APR-13:05 0.00 0.00
May 0.260528E+12 191165.86 25-MAY-07:00 684.34 0.187218E+13 0.00 0.213271E+13 6.45 7.94 06-MAY-05:03 0.00 0.00
June 0.284540E+12 198447.02 17-JUN-18:22 673.24 0.198800E+13 0.00 0.227254E+13 6.36 8.08 12-JUN-05:03 0.00 0.00
July 0.312425E+12 205038.53 16-JUL-15:02 693.38 0.212544E+13 0.00 0.243787E+13 6.14 7.92 05-JUL-05:03 0.00 0.00
August 0.304178E+12 205362.58 10-AUG-05:03 706.47 0.206454E+13 0.00 0.236872E+13 6.17 7.88 29-AUG-05:03 0.00 0.00
September 0.251034E+12 199201.36 17-SEP-20:23 632.57 0.174245E+13 0.00 0.199349E+13 5.83 7.86 29-SEP-03:04 0.00 0.00
October 0.181766E+12 182356.67 06-OCT-08:40 587.97 0.131437E+13 0.00 0.149614E+13 5.29 7.95 02-OCT-04:13 0.00 0.00
November 0.127008E+12 175223.60 07-NOV-15:50 478.75 0.877910E+12 0.00 0.100492E+13 4.15 7.95 13-NOV-17:00 0.00 0.00
December 0.684686E+11 104607.57 01-DEC-15:05 440.74 0.399371E+12 0.00 0.467839E+12 3.13 7.68 01-DEC-15:05 0.00 0.00
                         
Annual Sum or Average 0.228213E+13     6933.33 0.157549E+14 0.00 0.180370E+14 5.07     0.00 0.00
Minimum of Months 0.529598E+11 94718.97   401.29 0.286804E+12 0.00 0.339764E+12 2.73 7.51   0.00 0.00
Maximum of Months 0.312425E+12 205362.58   706.47 0.212544E+13 0.00 0.243787E+13 6.45 8.08   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.133303E+11 121217.32 30-MAR-12:05 38.42 0.995076E+11 0.00 0.112838E+12 0.38 7.83 07-MAR-15:05 0.00 0.00
April 0.560143E+11 136856.24 18-APR-14:05 150.75 0.417147E+12 0.00 0.473161E+12 1.55 7.91 10-APR-13:05 0.00 0.00
May 0.118991E+12 189222.71 22-MAY-05:03 285.73 0.861344E+12 0.00 0.980334E+12 2.77 7.82 06-MAY-17:43 0.00 0.00
June 0.158107E+12 198447.02 17-JUN-18:22 345.29 0.110961E+13 0.00 0.126772E+13 3.36 8.08 12-JUN-05:03 0.00 0.00
July 0.184084E+12 205038.53 16-JUL-15:02 384.51 0.126330E+13 0.00 0.144739E+13 3.54 7.92 05-JUL-05:03 0.00 0.00
August 0.191563E+12 205362.58 10-AUG-05:03 401.80 0.131264E+13 0.00 0.150421E+13 3.69 7.88 29-AUG-05:03 0.00 0.00
September 0.122260E+12 196271.99 05-SEP-05:04 288.46 0.855665E+12 0.00 0.977925E+12 2.79 7.59 29-SEP-05:06 0.00 0.00
October 0.403804E+11 153656.45 12-OCT-05:03 108.55 0.299216E+12 0.00 0.339596E+12 1.08 7.84 23-OCT-12:05 0.00 0.00
November 0.580408E+10 122721.95 09-NOV-11:05 17.75 0.430792E+11 0.00 0.488833E+11 0.18 7.85 09-NOV-11:05 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.890534E+12     2021.26 0.626152E+13 0.00 0.715205E+13 1.62     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.191563E+12 205362.58   401.80 0.131264E+13 0.00 0.150421E+13 3.69 8.08   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.572791E+11 744.00 43776.24 02-JAN-13:40 203847.37 12-JAN-17:00 22.44 19.04 14.70
February 0.889821E+11 672.00 43776.24 01-FEB-10:15 362734.30 24-FEB-16:20 27.71 21.34 14.70
March 0.117202E+12 744.00 43776.24 01-MAR-00:10 628601.64 31-MAR-24:00 36.47 27.03 14.70
April 0.113468E+12 720.00 43776.24 01-APR-00:05 694330.50 16-APR-17:11 47.93 35.42 14.70
May 0.117250E+12 744.00 43776.24 01-MAY-00:05 367509.23 31-MAY-23:20 39.61 35.17 14.70
June 0.113468E+12 720.00 43776.24 01-JUN-00:05 537923.21 30-JUN-23:53 44.91 37.37 14.70
July 0.117250E+12 744.00 43776.24 01-JUL-00:03 666354.28 31-JUL-24:00 47.43 36.94 14.70
August 0.117250E+12 744.00 43776.24 01-AUG-00:05 697551.40 25-AUG-14:05 49.45 36.53 14.70
September 0.113468E+12 720.00 43776.24 01-SEP-00:05 365954.99 30-SEP-23:20 35.44 30.96 14.70
October 0.117250E+12 744.00 43776.24 01-OCT-00:05 473835.22 31-OCT-23:40 35.43 28.50 14.70
November 0.111369E+12 720.00 43776.24 01-NOV-00:10 527912.73 08-NOV-16:20 33.74 24.39 14.70
December 0.107610E+12 744.00 43776.24 01-DEC-07:05 646006.31 28-DEC-16:30 33.07 21.31 14.70
                   
Annual Sum or Average 0.129185E+13 8760.00         37.86 29.54 14.70
Minimum of Months 0.572791E+11 672.00 43776.24   203847.37   22.44 19.04 14.70
Maximum of Months 0.117250E+12 744.00 43776.24   697551.40   49.45 37.37 14.70



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.163598E+09 229.60 940.12 12-JAN-15:50 802964.60 25-JAN-14:10 21.62 21.14 29.23
February 0.704219E+09 313.58 4085.54 24-FEB-15:40 1397100.02 22-FEB-15:40 22.20 21.30 36.98
March 0.831755E+10 486.59 19084.35 06-MAR-11:30 1564514.65 24-MAR-15:10 23.04 21.35 47.76
April 0.229010E+11 614.39 19084.35 01-APR-09:00 1548713.37 10-APR-10:30 24.14 21.73 60.55
May 0.426703E+11 684.09 19084.35 01-MAY-04:00 1528329.71 06-MAY-09:00 26.98 24.13 58.18
June 0.459596E+11 673.24 19084.35 01-JUN-00:05 1508050.56 22-JUN-15:40 29.25 26.12 54.97
July 0.476377E+11 693.38 19084.35 01-JUL-00:03 1529208.87 05-JUL-05:04 31.10 27.85 51.93
August 0.485369E+11 706.47 19084.35 01-AUG-00:05 1488191.17 10-AUG-05:03 30.72 27.56 54.56
September 0.433599E+11 632.57 19084.35 01-SEP-00:05 1383232.74 12-SEP-05:04 29.20 26.47 49.62
October 0.226000E+11 550.46 19084.35 01-OCT-00:05 1501471.13 24-OCT-16:10 23.98 21.95 51.64
November 0.390606E+10 427.05 19084.35 06-NOV-10:40 1544558.69 14-NOV-13:50 22.74 21.33 43.27
December 0.303371E+09 281.45 1550.17 28-DEC-15:00 916035.83 01-DEC-15:05 21.80 21.14 33.89
                   
Annual Sum or Average 0.287060E+12 6292.86         25.58 23.52 47.76
Minimum of Months 0.163598E+09 229.60 940.12   802964.60   21.62 21.14 29.23
Maximum of Months 0.485369E+11 706.47 19084.35   1564514.65   31.10 27.85 60.55



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 21.62 21.62 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 22.20 22.20 0.00
March 0.204157E+10 31.58 19084.35 06-MAR-15:05 1280147.35 08-MAR-14:05 23.04 22.89 2.80
April 0.876375E+10 140.56 19084.35 01-APR-14:30 1320211.57 11-APR-13:40 24.14 23.44 12.80
May 0.255157E+11 371.39 19084.35 01-MAY-05:15 1358877.52 30-MAY-15:20 26.98 25.18 29.77
June 0.357087E+11 519.75 19084.35 01-JUN-05:05 1508050.56 22-JUN-15:40 29.25 26.55 40.58
July 0.431788E+11 628.48 19084.35 01-JUL-00:03 1529208.87 05-JUL-05:04 31.10 27.93 46.04
August 0.420927E+11 612.67 19084.35 01-AUG-00:05 1488191.17 10-AUG-05:03 30.72 27.66 46.05
September 0.340364E+11 495.41 19084.35 01-SEP-00:05 1383232.74 12-SEP-05:04 29.20 26.75 36.76
October 0.776703E+10 114.61 19084.35 02-OCT-07:50 1305654.90 24-OCT-15:40 23.98 23.43 9.60
November 0.156514E+09 3.92 19084.35 06-NOV-12:00 1312732.23 13-NOV-14:50 22.74 22.72 0.37
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 21.80 21.80 0.00
                   
Annual Sum or Average 0.199261E+12 2918.37         25.58 24.36 18.84
Minimum of Months 0.00 0.00 0.00   0.00   21.62 21.62 0.00
Maximum of Months 0.431788E+11 628.48 19084.35   1529208.87   31.10 27.93 46.05



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.338219E+11 0.00 203.40 1288499.06 02-JAN-06:03 0.00 37.14 42.78 0.19 0.00 0.01 0.90 02-JAN-06:03
February 0.517748E+10 0.00 64.85 1010040.54 11-FEB-06:02 0.00 32.78 35.16 0.03 0.00 0.00 0.70 11-FEB-06:02
March 703167.38 0.00 1.50 243.77 01-MAR-06:40 0.00 29.85 29.91 0.00 0.00 0.00 0.00 01-MAR-06:40
April 0.00 0.00 0.00 0.00 01-APR-00:05 0.00 29.84 29.84 0.00 0.00 0.00 0.00 01-APR-00:05
May 4434.97 0.00 0.17 7.39 16-MAY-15:40 0.00 29.84 29.85 0.00 0.00 0.00 0.00 16-MAY-15:40
June 0.00 0.00 0.00 0.00 01-JUN-00:05 0.00 29.84 29.84 0.00 0.00 0.00 0.00 01-JUN-00:05
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 29.84 29.84 0.00 0.00 0.00 0.00 01-JUL-00:03
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 29.84 29.84 0.00 0.00 0.00 0.00 01-AUG-00:05
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 29.84 29.84 0.00 0.00 0.00 0.00 01-SEP-00:05
October 0.00 0.00 0.00 0.00 01-OCT-00:05 0.00 29.84 29.84 0.00 0.00 0.00 0.00 01-OCT-00:05
November 0.203808E+09 0.00 13.79 41480.05 27-NOV-06:03 0.00 30.13 30.70 0.00 0.00 0.00 0.03 27-NOV-06:03
December 0.101292E+11 0.00 130.48 739319.10 23-DEC-06:02 0.00 33.12 37.46 0.05 0.00 0.00 0.52 23-DEC-06:02
                           
Annual Sum or Average 0.493331E+11 0.00 414.19     0.00 30.99 32.07 0.02 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 29.84 29.84 0.00 0.00 0.00 0.00  
Maximum of Months 0.338219E+11 0.00 203.40 1288499.06   0.00 37.14 42.78 0.19 0.00 0.01 0.90  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 22.44 22.44 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 27.71 27.71 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 36.47 36.47 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:05 0.00 47.93 47.93 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 39.61 39.61 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:05 0.00 44.91 44.91 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 47.43 47.43 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 49.45 49.45 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 35.44 35.44 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:05 0.00 35.43 35.43 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 33.74 33.74 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 33.07 33.07 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 37.86 37.86 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 22.44 22.44 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 49.45 49.45 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.319171E+11 0.00 351.83 0.318815E+11 0.00 0.00 0.00 0.00 73958.44 18-JAN-06:03 67265.49 12-JAN-15:00 0.00 0.00 0.00
February 0.535232E+11 0.00 381.49 0.534108E+11 0.00 0.00 0.00 0.00 137160.96 25-FEB-06:03 100015.68 21-FEB-16:00 0.00 0.00 0.00
March 0.113546E+12 0.00 538.56 0.111699E+12 0.00 0.00 0.00 0.00 194319.48 11-MAR-06:02 152991.44 11-MAR-06:02 0.00 0.00 0.00
April 0.178601E+12 0.00 626.87 0.171774E+12 0.00 0.00 0.00 0.00 245068.71 17-APR-04:22 183165.67 28-APR-05:03 0.00 0.00 0.00
May 0.225418E+12 0.00 641.15 0.191315E+12 0.00 0.00 0.00 0.00 277978.66 22-MAY-05:03 194857.25 30-MAY-05:02 0.00 0.00 0.00
June 0.264286E+12 0.00 626.27 0.196026E+12 0.00 0.00 0.00 0.00 286576.64 27-JUN-05:02 204141.75 12-JUN-05:03 0.00 0.00 0.00
July 0.299831E+12 0.00 648.60 0.185347E+12 0.00 0.00 0.00 0.00 298880.24 05-JUL-03:02 197349.41 05-JUL-04:23 0.00 0.00 0.00
August 0.320001E+12 0.00 660.21 0.194748E+12 0.00 0.00 0.00 0.00 306899.58 28-AUG-03:01 188775.59 07-AUG-05:01 0.00 0.00 0.00
September 0.225567E+12 0.00 579.83 0.141613E+12 0.00 0.00 0.00 0.00 289637.10 05-SEP-05:02 178054.56 18-SEP-05:02 0.00 0.00 0.00
October 0.145588E+12 0.00 551.78 0.128889E+12 0.00 0.00 0.00 0.00 242752.28 12-OCT-04:12 158714.39 16-OCT-04:12 0.00 0.00 0.00
November 0.906330E+11 0.00 453.97 0.894293E+11 0.00 0.00 0.00 0.00 161053.19 09-NOV-05:12 111402.40 13-NOV-14:50 0.00 0.00 0.00
December 0.523929E+11 0.00 417.34 0.523929E+11 0.00 0.00 0.00 0.00 87492.58 04-DEC-15:00 87492.58 04-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.200130E+13 0.00 6477.90 0.154853E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.319171E+11 0.00 351.83 0.318815E+11 0.00 0.00 0.00 0.00 73958.44   67265.49   0.00 0.00 0.00
Maximum of Months 0.320001E+12 0.00 660.21 0.196026E+12 0.00 0.00 0.00 0.00 306899.58   204141.75   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.190234E+12 0.00 319.06 0.190234E+12 0.00 0.00 0.00 0.00 536456.62 12-JAN-15:05 536456.62 12-JAN-15:05 0.00 0.00 0.00
February 0.364762E+12 0.00 355.28 0.363986E+12 0.00 0.00 0.00 0.00 1051129.01 25-FEB-06:03 820189.83 22-FEB-15:05 0.00 0.00 0.00
March 0.867741E+12 0.00 469.76 0.854324E+12 0.00 0.00 0.00 0.00 1917282.37 11-MAR-06:02 1491729.53 29-MAR-04:12 0.00 0.00 0.00
April 0.144133E+13 0.00 554.71 0.138734E+13 0.00 0.00 0.00 0.00 2057354.63 25-APR-04:12 1582673.37 29-APR-05:02 0.00 0.00 0.00
May 0.213674E+13 0.00 630.56 0.180099E+13 0.00 0.00 0.00 0.00 2640639.76 25-MAY-05:02 1833607.44 30-MAY-05:02 0.00 0.00 0.00
June 0.242474E+13 0.00 596.78 0.176700E+13 0.00 0.00 0.00 0.00 2809311.89 27-JUN-05:02 1931725.55 12-JUN-05:03 0.00 0.00 0.00
July 0.265104E+13 0.00 601.26 0.156345E+13 0.00 0.00 0.00 0.00 3007147.97 25-JUL-05:02 1793971.01 05-JUL-05:01 0.00 0.00 0.00
August 0.260706E+13 0.00 585.14 0.147463E+13 0.00 0.00 0.00 0.00 2952591.47 11-AUG-05:03 1734176.81 07-AUG-05:01 0.00 0.00 0.00
September 0.201337E+13 0.00 525.22 0.123587E+13 0.00 0.00 0.00 0.00 2836960.22 05-SEP-05:02 1643818.40 05-SEP-05:02 0.00 0.00 0.00
October 0.121258E+13 0.00 485.00 0.106738E+13 0.00 0.00 0.00 0.00 2223005.63 12-OCT-05:03 1533460.99 03-OCT-04:12 0.00 0.00 0.00
November 0.651527E+12 0.00 426.14 0.643823E+12 0.00 0.00 0.00 0.00 1348747.46 09-NOV-06:03 943506.72 08-NOV-15:05 0.00 0.00 0.00
December 0.268472E+12 0.00 362.37 0.268472E+12 0.00 0.00 0.00 0.00 645776.19 29-DEC-06:03 645776.19 29-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.168296E+14 0.00 5911.30 0.126175E+14 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.190234E+12 0.00 319.06 0.190234E+12 0.00 0.00 0.00 0.00 536456.62   536456.62   0.00 0.00 0.00
Maximum of Months 0.265104E+13 0.00 630.56 0.180099E+13 0.00 0.00 0.00 0.00 3007147.97   1931725.55   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.157661E+11 0.00 293.09 0.157661E+11 0.00 0.00 0.00 0.00 50800.94 12-JAN-15:30 50800.94 12-JAN-15:30 0.00 0.00 0.00
February 0.330138E+11 0.00 337.42 0.329426E+11 0.00 0.00 0.00 0.00 91055.18 22-FEB-15:00 91055.18 22-FEB-15:00 0.00 0.00 0.00
March 0.882760E+11 0.00 460.04 0.870255E+11 0.00 0.00 0.00 0.00 189356.31 11-MAR-06:02 146405.23 29-MAR-04:12 0.00 0.00 0.00
April 0.157509E+12 0.00 548.99 0.152060E+12 0.00 0.00 0.00 0.00 230541.51 27-APR-05:02 182672.68 16-APR-14:42 0.00 0.00 0.00
May 0.235545E+12 0.00 631.29 0.201650E+12 0.00 0.00 0.00 0.00 283380.33 25-MAY-05:02 226709.25 29-MAY-16:41 0.00 0.00 0.00
June 0.264787E+12 0.00 599.20 0.198853E+12 0.00 0.00 0.00 0.00 313817.73 27-JUN-05:02 224698.36 12-JUN-05:03 0.00 0.00 0.00
July 0.282471E+12 0.00 606.07 0.173241E+12 0.00 0.00 0.00 0.00 338593.66 25-JUL-05:02 212275.68 03-JUL-03:02 0.00 0.00 0.00
August 0.275267E+12 0.00 589.51 0.161626E+12 0.00 0.00 0.00 0.00 320525.43 16-AUG-05:02 201808.94 07-AUG-05:01 0.00 0.00 0.00
September 0.209929E+12 0.00 524.72 0.132446E+12 0.00 0.00 0.00 0.00 316591.02 05-SEP-05:02 187634.79 18-SEP-04:12 0.00 0.00 0.00
October 0.122548E+12 0.00 477.78 0.108896E+12 0.00 0.00 0.00 0.00 222902.23 06-OCT-04:12 164039.97 01-OCT-15:11 0.00 0.00 0.00
November 0.599211E+11 0.00 407.28 0.595199E+11 0.00 0.00 0.00 0.00 114000.00 09-NOV-06:03 105183.84 09-NOV-14:50 0.00 0.00 0.00
December 0.206692E+11 0.00 329.23 0.206692E+11 0.00 0.00 0.00 0.00 60388.16 01-DEC-15:00 60388.16 01-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.176570E+13 0.00 5804.62 0.134470E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.157661E+11 0.00 293.09 0.157661E+11 0.00 0.00 0.00 0.00 50800.94   50800.94   0.00 0.00 0.00
Maximum of Months 0.282471E+12 0.00 631.29 0.201650E+12 0.00 0.00 0.00 0.00 338593.66   226709.25   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.440289E+11 0.00 388.88 0.439491E+11 0.00 0.00 0.00 0.00 116951.15 18-JAN-05:13 86046.90 12-JAN-06:02 0.00 0.00 0.00
February 0.474030E+11 0.00 362.21 0.472764E+11 0.00 0.00 0.00 0.00 130333.11 25-FEB-05:12 92996.89 20-FEB-12:48 0.00 0.00 0.00
March 0.678125E+11 0.00 426.66 0.675578E+11 0.00 0.00 0.00 0.00 135673.05 20-MAR-04:12 97827.55 27-MAR-04:12 0.00 0.00 0.00
April 0.818129E+11 0.00 414.53 0.798180E+11 0.00 0.00 0.00 0.00 156480.62 27-APR-03:02 122639.57 30-APR-16:27 0.00 0.00 0.00
May 0.105525E+12 0.00 453.38 0.937693E+11 0.00 0.00 0.00 0.00 185790.19 22-MAY-03:02 122398.61 29-MAY-13:59 0.00 0.00 0.00
June 0.125198E+12 0.00 454.12 0.977406E+11 0.00 0.00 0.00 0.00 199669.37 25-JUN-19:27 121339.40 04-JUN-17:27 0.00 0.00 0.00
July 0.146851E+12 0.00 465.69 0.971864E+11 0.00 0.00 0.00 0.00 213117.75 23-JUL-23:50 114548.41 04-JUL-19:39 0.00 0.00 0.00
August 0.164941E+12 0.00 503.91 0.105388E+12 0.00 0.00 0.00 0.00 223867.90 27-AUG-10:48 100140.05 06-AUG-15:36 0.00 0.00 0.00
September 0.127329E+12 0.00 457.86 0.885290E+11 0.00 0.00 0.00 0.00 209764.21 17-SEP-21:27 100592.84 24-SEP-12:07 0.00 0.00 0.00
October 0.905265E+11 0.00 451.95 0.838899E+11 0.00 0.00 0.00 0.00 168455.69 01-OCT-11:41 114335.80 01-OCT-15:50 0.00 0.00 0.00
November 0.683667E+11 0.00 413.20 0.680050E+11 0.00 0.00 0.00 0.00 138856.76 09-NOV-05:12 112169.20 05-NOV-13:46 0.00 0.00 0.00
December 0.527948E+11 0.00 395.19 0.527349E+11 0.00 0.00 0.00 0.00 109200.79 30-DEC-05:13 92096.41 29-DEC-05:12 0.00 0.00 0.00
                               
Annual Sum or Average 0.112259E+13 0.00 5187.58 0.925845E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.440289E+11 0.00 362.21 0.439491E+11 0.00 0.00 0.00 0.00 109200.79   86046.90   0.00 0.00 0.00
Maximum of Months 0.164941E+12 0.00 503.91 0.105388E+12 0.00 0.00 0.00 0.00 223867.90   122639.57   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.335268E+12 0.759286E+11 744.00 0.321697E+12 0.135711E+11 0.00 0.35 12-JAN-16:00 0.32 22-JAN-06:00 130508.74 17-JAN-16:20 126069.58 12-JAN-15:00 6775.85 17-JAN-16:20 35610.32 12-JAN-15:00 0.00
February 0.531318E+12 0.123285E+12 672.00 0.514330E+12 0.169876E+11 0.00 0.60 22-FEB-15:00 0.53 01-FEB-00:10 224178.32 24-FEB-17:00 218882.23 22-FEB-15:00 10311.54 27-FEB-08:65 67286.91 22-FEB-15:00 0.00
March 0.834477E+12 0.221005E+12 744.00 0.820158E+12 0.143199E+11 0.00 0.98 31-MAR-24:00 0.74 01-MAR-02:00 395281.95 31-MAR-23:03 393034.98 31-MAR-24:00 13905.05 05-MAR-06:00 118230.99 28-MAR-15:30 0.00
April 0.103342E+13 0.320861E+12 720.00 0.102706E+13 0.636840E+10 0.00 1.00 01-APR-08:70 0.42 30-APR-23:17 409066.44 25-APR-04:53 403642.46 30-APR-04:57 9076.48 11-APR-05:00 150749.01 15-APR-15:00 0.00
May 0.361731E+12 0.129374E+12 744.00 0.344718E+12 0.170129E+11 0.00 0.60 31-MAY-23:05 0.35 28-MAY-05:00 225823.51 31-MAY-23:05 212390.25 31-MAY-24:00 15181.71 22-MAY-23:10 68924.82 31-MAY-23:15 0.00
June 0.597570E+12 0.213573E+12 720.00 0.571696E+12 0.258745E+11 0.00 0.85 30-JUN-24:00 0.58 18-JUN-05:00 317953.23 30-JUN-23:03 306662.47 30-JUN-23:53 18683.65 28-JUN-13:10 110907.45 30-JUN-23:13 0.00
July 0.873059E+12 0.294996E+12 744.00 0.836318E+12 0.367406E+11 0.00 1.00 31-JUL-23:03 0.80 19-JUL-03:00 401001.85 31-JUL-24:00 389506.85 31-JUL-24:00 19584.55 18-JUL-08:30 136492.57 07-JUL-15:00 0.00
August 0.109826E+13 0.339841E+12 744.00 0.106262E+13 0.356351E+11 0.00 1.00 01-AUG-00:05 0.45 31-AUG-23:17 420506.11 10-AUG-14:00 404099.30 15-AUG-23:53 20794.05 25-AUG-16:00 144371.72 07-AUG-15:00 0.00
September 0.365274E+12 0.115021E+12 720.00 0.333871E+12 0.314029E+11 0.00 0.60 30-SEP-23:05 0.36 27-SEP-05:00 227444.94 30-SEP-23:05 213418.48 30-SEP-24:00 18076.57 12-SEP-16:00 66547.96 30-SEP-23:15 0.00
October 0.600609E+12 0.172019E+12 744.00 0.584074E+12 0.165348E+11 0.00 0.76 31-OCT-23:30 0.55 31-OCT-05:00 310344.57 31-OCT-24:00 301701.76 31-OCT-24:00 11651.76 06-OCT-09:10 88288.72 02-OCT-15:00 0.00
November 0.816197E+12 0.199744E+12 720.00 0.796345E+12 0.198517E+11 0.00 0.84 08-NOV-15:00 0.75 26-NOV-06:00 320839.21 24-NOV-08:25 313156.51 08-NOV-15:00 14602.93 23-NOV-08:00 102841.07 08-NOV-15:00 0.00
December 0.109737E+13 0.234890E+12 744.00 0.106223E+13 0.351347E+11 0.00 1.00 03-DEC-13:52 0.93 01-DEC-00:10 421149.57 22-DEC-06:15 402377.68 28-DEC-16:50 25566.72 22-DEC-06:03 113041.11 28-DEC-14:10 0.00
                                       
Annual Sum or Average 0.854455E+13 0.244054E+13 8760.00 0.827512E+13 0.269434E+12 0.00                         0.00
Minimum of Months 0.335268E+12 0.759286E+11 672.00 0.321697E+12 0.636840E+10 0.00 0.35   0.32   130508.74   126069.58   6775.85   35610.32   0.00
Maximum of Months 0.109826E+13 0.339841E+12 744.00 0.106262E+13 0.367406E+11 0.00 1.00   0.93   421149.57   404099.30   25566.72   150749.01   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.453401E+10 0.105022E+10 744.00 0.437769E+10 0.156320E+09 0.00 0.29 12-JAN-17:00 0.15 03-JAN-08:00 2336.35 12-JAN-17:00 2202.75 12-JAN-17:00 250.22 17-JAN-16:20 614.51 12-JAN-16:00 0.00
February 0.934998E+10 0.218060E+10 672.00 0.910825E+10 0.241721E+09 0.00 0.56 20-FEB-17:03 0.39 01-FEB-07:00 4436.29 20-FEB-17:15 4436.29 20-FEB-17:15 267.28 15-FEB-17:00 1287.22 22-FEB-15:00 0.00
March 0.161103E+11 0.423556E+10 744.00 0.157589E+11 0.351402E+09 0.00 0.90 31-MAR-24:00 0.62 01-MAR-07:00 7802.50 31-MAR-24:00 7694.76 31-MAR-24:00 343.90 10-MAR-17:10 2369.60 28-MAR-16:00 0.00
April 0.210210E+11 0.659091E+10 720.00 0.206940E+11 0.326996E+09 0.00 1.00 01-APR-15:10 0.40 30-APR-23:05 8640.74 17-APR-01:13 8380.17 17-APR-01:13 389.80 26-APR-08:00 3177.03 15-APR-15:00 0.00
May 0.723299E+10 0.251669E+10 744.00 0.655128E+10 0.681713E+09 0.00 0.56 31-MAY-23:05 0.28 13-MAY-07:00 4656.70 31-MAY-23:05 4073.29 31-MAY-24:00 651.05 22-MAY-23:10 1389.27 01-MAY-15:50 0.00
June 0.123428E+11 0.427659E+10 720.00 0.112404E+11 0.110240E+10 0.00 0.81 30-JUN-23:13 0.53 01-JUN-06:00 6602.69 30-JUN-23:03 6114.72 30-JUN-23:57 817.80 28-JUN-13:40 2254.00 11-JUN-16:10 0.00
July 0.182133E+11 0.596533E+10 744.00 0.165809E+11 0.163234E+10 0.00 1.00 31-JUL-23:03 0.74 19-JUL-03:00 8670.85 31-JUL-23:03 7934.80 31-JUL-24:00 850.31 18-JUL-08:20 2940.68 02-JUL-16:50 0.00
August 0.229890E+11 0.715650E+10 744.00 0.212699E+11 0.171907E+10 0.00 1.00 01-AUG-00:05 0.39 31-AUG-23:05 8835.60 10-AUG-14:00 8162.96 20-AUG-18:50 875.00 21-AUG-14:00 3046.97 07-AUG-15:00 0.00
September 0.727660E+10 0.220132E+10 720.00 0.599135E+10 0.128525E+10 0.00 0.55 30-SEP-23:05 0.30 27-SEP-06:50 4652.66 30-SEP-23:05 4050.75 30-SEP-24:00 731.23 12-SEP-16:00 1309.90 30-SEP-23:15 0.00
October 0.116569E+11 0.328329E+10 744.00 0.110190E+11 0.637909E+09 0.00 0.68 31-OCT-23:20 0.46 28-OCT-07:00 5954.14 31-OCT-23:10 5729.16 31-OCT-24:00 500.00 06-OCT-09:50 1771.57 02-OCT-15:10 0.00
November 0.154365E+11 0.377033E+10 720.00 0.151068E+11 0.329666E+09 0.00 0.78 05-NOV-16:12 0.62 25-NOV-08:00 6485.14 05-NOV-16:50 6422.34 12-NOV-16:25 290.12 08-NOV-20:00 2017.92 08-NOV-15:00 0.00
December 0.202750E+11 0.438525E+10 744.00 0.200876E+11 0.187450E+09 0.00 0.94 25-DEC-14:13 0.78 23-DEC-08:00 8100.90 28-DEC-17:00 7962.93 24-DEC-16:47 261.07 29-DEC-17:10 2236.30 25-DEC-14:03 0.00
                                       
Annual Sum or Average 0.166438E+12 0.476126E+11 8760.00 0.157786E+12 0.865223E+10 0.00                         0.00
Minimum of Months 0.453401E+10 0.105022E+10 672.00 0.437769E+10 0.156320E+09 0.00 0.29   0.15   2336.35   2202.75   250.22   614.51   0.00
Maximum of Months 0.229890E+11 0.715650E+10 744.00 0.212699E+11 0.171907E+10 0.00 1.00   0.78   8835.60   8380.17   875.00   3177.03   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.287218E+11 0.687761E+10 716.83 0.273559E+11 0.136591E+10 0.00 0.28 12-JAN-17:00 0.00 01-JAN-00:10 21263.00 12-JAN-17:00 19951.89 12-JAN-17:00 2413.02 17-JAN-16:20 5594.05 12-JAN-17:00 0.00
February 0.819238E+11 0.193119E+11 672.00 0.795393E+11 0.238452E+10 0.00 0.54 22-FEB-17:00 0.32 11-FEB-07:40 41589.04 22-FEB-17:00 39995.68 22-FEB-17:00 2657.34 15-FEB-17:00 12129.91 22-FEB-15:00 0.00
March 0.151806E+12 0.400290E+11 744.00 0.148301E+12 0.350488E+10 0.00 0.91 31-MAR-24:00 0.60 01-MAR-07:00 75136.07 31-MAR-24:00 74051.39 31-MAR-24:00 3423.10 10-MAR-17:10 22672.33 28-MAR-16:00 0.00
April 0.199249E+12 0.626214E+11 720.00 0.195966E+12 0.328295E+10 0.00 1.00 01-APR-15:10 0.34 30-APR-24:00 81476.98 16-APR-20:53 78903.66 16-APR-21:02 3902.08 26-APR-08:00 30380.55 15-APR-15:00 0.00
May 0.685033E+11 0.238439E+11 744.00 0.617602E+11 0.674314E+10 0.00 0.56 31-MAY-23:05 0.27 13-MAY-07:00 44993.49 31-MAY-23:05 39233.74 31-MAY-24:00 6409.41 31-MAY-23:05 13176.83 28-MAY-16:51 0.00
June 0.117874E+12 0.408175E+11 720.00 0.106906E+12 0.109677E+11 0.00 0.81 30-JUN-23:13 0.53 24-JUN-13:20 63822.80 30-JUN-23:03 58902.85 30-JUN-23:57 8153.87 28-JUN-13:40 21536.11 30-JUN-23:13 0.00
July 0.173703E+12 0.568563E+11 744.00 0.157426E+12 0.162771E+11 0.00 1.00 31-JUL-23:03 0.74 19-JUL-03:00 83032.81 31-JUL-23:03 75735.44 31-JUL-24:00 8479.89 18-JUL-08:20 27779.31 02-JUL-16:50 0.00
August 0.218286E+12 0.681942E+11 744.00 0.201048E+12 0.172377E+11 0.00 1.00 01-AUG-00:05 0.34 31-AUG-23:13 84266.38 10-AUG-14:00 77211.56 20-AUG-17:33 8731.91 21-AUG-14:00 29131.46 07-AUG-15:00 0.00
September 0.682600E+11 0.206446E+11 720.00 0.555738E+11 0.126863E+11 0.00 0.56 30-SEP-23:05 0.28 08-SEP-21:20 45177.29 30-SEP-23:05 38991.99 30-SEP-24:00 7225.30 12-SEP-16:00 12657.12 30-SEP-23:15 0.00
October 0.109706E+12 0.309600E+11 744.00 0.103375E+12 0.633123E+10 0.00 0.67 31-OCT-23:20 0.44 31-OCT-06:00 56392.60 31-OCT-23:10 54115.69 31-OCT-24:00 4979.05 06-OCT-10:05 16880.94 02-OCT-15:10 0.00
November 0.142714E+12 0.350554E+11 720.00 0.139429E+12 0.328478E+10 0.00 0.78 08-NOV-16:20 0.58 26-NOV-07:00 61589.23 08-NOV-17:00 58986.96 12-NOV-16:25 2866.01 08-NOV-20:00 19204.40 08-NOV-15:00 0.00
December 0.182368E+12 0.398312E+11 744.00 0.180491E+12 0.187745E+10 0.00 0.92 28-DEC-16:30 0.71 24-DEC-06:50 76581.55 28-DEC-17:00 74903.88 28-DEC-17:00 2599.93 29-DEC-17:10 20945.15 28-DEC-15:00 0.00
                                       
Annual Sum or Average 0.154311E+13 0.445043E+12 8732.83 0.145717E+13 0.859437E+11 0.00                         0.00
Minimum of Months 0.287218E+11 0.687761E+10 672.00 0.273559E+11 0.136591E+10 0.00 0.28   0.00   21263.00   19951.89   2413.02   5594.05   0.00
Maximum of Months 0.218286E+12 0.681942E+11 744.00 0.201048E+12 0.172377E+11 0.00 1.00   0.74   84266.38   78903.66   8731.91   30380.55   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.177393E+10 0.439057E+09 573.19 0.166683E+10 0.107103E+09 0.00 0.28 12-JAN-17:00 0.00 01-JAN-00:10 2157.38 12-JAN-17:00 2023.99 12-JAN-17:00 256.93 17-JAN-15:30 567.28 12-JAN-17:00 0.00
February 0.754898E+10 0.180180E+10 672.00 0.731431E+10 0.234667E+09 0.00 0.54 22-FEB-17:00 0.22 11-FEB-05:55 4216.00 22-FEB-17:00 4056.51 22-FEB-17:00 265.92 15-FEB-17:00 1234.22 22-FEB-15:00 0.00
March 0.150159E+11 0.397765E+10 744.00 0.146666E+11 0.349307E+09 0.00 0.90 31-MAR-24:00 0.54 01-MAR-07:50 7471.75 31-MAR-24:00 7363.80 31-MAR-24:00 342.54 10-MAR-17:10 2307.49 28-MAR-16:00 0.00
April 0.200146E+11 0.629641E+10 720.00 0.196877E+11 0.326913E+09 0.00 1.00 01-APR-14:50 0.36 30-APR-24:00 8307.59 16-APR-20:53 8053.77 16-APR-21:12 389.89 26-APR-08:00 3070.28 15-APR-15:00 0.00
May 0.708036E+10 0.246591E+10 744.00 0.640281E+10 0.677553E+09 0.00 0.55 31-MAY-23:05 0.26 13-MAY-07:00 4448.99 31-MAY-23:05 3873.69 31-MAY-24:00 643.58 31-MAY-23:05 1511.84 28-MAY-16:51 0.00
June 0.119956E+11 0.415604E+10 720.00 0.108972E+11 0.109831E+10 0.00 0.81 30-JUN-23:13 0.52 24-JUN-13:40 6447.59 30-JUN-23:03 5962.38 30-JUN-23:57 817.93 28-JUN-13:10 2341.81 11-JUN-16:50 0.00
July 0.175867E+11 0.575921E+10 744.00 0.159584E+11 0.162835E+10 0.00 1.00 31-JUL-23:03 0.73 19-JUL-03:00 8389.52 31-JUL-23:03 7626.00 31-JUL-23:57 847.19 18-JUL-08:20 2954.22 02-JUL-16:50 0.00
August 0.219831E+11 0.687154E+10 744.00 0.202604E+11 0.172272E+10 0.00 1.00 01-AUG-09:00 0.34 31-AUG-23:13 8510.15 20-AUG-16:54 7845.30 20-AUG-17:33 873.37 21-AUG-14:00 2943.96 07-AUG-15:00 0.00
September 0.693031E+10 0.209865E+10 720.00 0.565863E+10 0.127167E+10 0.00 0.56 30-SEP-23:05 0.28 27-SEP-07:00 4545.56 30-SEP-23:05 3927.32 30-SEP-23:33 722.31 12-SEP-16:00 1275.59 30-SEP-23:15 0.00
October 0.109010E+11 0.308845E+10 744.00 0.102695E+11 0.631509E+09 0.00 0.66 01-OCT-16:55 0.40 31-OCT-07:00 5530.47 31-OCT-23:10 5282.84 31-OCT-23:50 500.00 06-OCT-10:05 1772.37 01-OCT-16:02 0.00
November 0.137791E+11 0.341270E+10 720.00 0.134526E+11 0.326514E+09 0.00 0.78 08-NOV-16:20 0.49 26-NOV-07:40 6210.26 08-NOV-16:50 5957.35 05-NOV-16:24 285.71 08-NOV-20:00 1938.56 08-NOV-15:00 0.00
December 0.170781E+11 0.377332E+10 744.00 0.168919E+11 0.186191E+09 0.00 0.91 28-DEC-16:30 0.58 31-DEC-08:70 7686.38 28-DEC-17:00 7518.84 28-DEC-17:00 258.97 29-DEC-17:10 2103.64 28-DEC-15:00 0.00
                                       
Annual Sum or Average 0.151688E+12 0.441408E+11 8589.19 0.143127E+12 0.856081E+10 0.00                         0.00
Minimum of Months 0.177393E+10 0.439057E+09 573.19 0.166683E+10 0.107103E+09 0.00 0.28   0.00   2157.38   2023.99   256.93   567.28   0.00
Maximum of Months 0.219831E+11 0.687154E+10 744.00 0.202604E+11 0.172272E+10 0.00 1.00   0.73   8510.15   8053.77   873.37   3070.28   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.64 0.00 105.64 56.47 464.13 0.00 0.00 0.00
February 125.27 0.00 125.27 119.38 358.65 0.00 0.00 0.00
March 150.95 0.00 150.95 238.86 210.17 0.00 0.00 0.00
April 163.80 0.56 163.24 417.72 73.84 0.00 0.00 0.00
May 181.47 5.09 176.38 589.18 12.29 0.00 0.00 0.00
June 187.85 6.96 180.90 639.08 8.96 0.00 0.00 0.00
July 185.27 2.93 182.33 563.64 2.12 0.00 0.00 0.00
August 170.08 0.53 169.55 470.23 8.75 0.00 0.00 0.00
September 151.55 0.01 151.54 372.50 28.46 0.00 0.00 0.00
October 131.29 0.00 131.29 267.68 161.13 0.00 0.00 0.00
November 111.20 0.00 111.20 139.77 321.55 0.00 0.00 0.00
December 103.05 0.00 103.05 60.95 459.67 0.00 0.00 0.00
                 
Annual Sum or Average 147.40 1.35 146.05 328.96 175.05 0.00 0.00 0.00
Minimum of Months 103.05 0.00 103.05 56.47 2.12 0.00 0.00 0.00
Maximum of Months 187.85 6.96 182.33 639.08 464.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.64 0.00 105.64 56.47 464.13 0.00 0.00 0.00
February 125.27 0.00 125.27 119.38 358.65 0.00 0.00 0.00
March 150.95 0.00 150.95 238.86 210.17 0.00 0.00 0.00
April 163.80 0.56 163.24 417.72 73.84 0.00 0.00 0.00
May 181.47 5.09 176.38 589.18 12.29 0.00 0.00 0.00
June 187.85 6.96 180.90 639.08 8.96 0.00 0.00 0.00
July 185.27 2.93 182.33 563.64 2.12 0.00 0.00 0.00
August 170.08 0.53 169.55 470.23 8.75 0.00 0.00 0.00
September 151.55 0.01 151.54 372.50 28.46 0.00 0.00 0.00
October 131.29 0.00 131.29 267.68 161.13 0.00 0.00 0.00
November 111.20 0.00 111.20 139.77 321.55 0.00 0.00 0.00
December 103.05 0.00 103.05 60.95 459.67 0.00 0.00 0.00
                 
Annual Sum or Average 147.40 1.35 146.05 328.96 175.05 0.00 0.00 0.00
Minimum of Months 103.05 0.00 103.05 56.47 2.12 0.00 0.00 0.00
Maximum of Months 187.85 6.96 182.33 639.08 464.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.64 0.00 105.64 56.47 464.13 0.00 0.00 0.00
February 125.27 0.00 125.27 119.38 358.65 0.00 0.00 0.00
March 150.95 0.00 150.95 238.86 210.17 0.00 0.00 0.00
April 163.80 0.56 163.24 417.72 73.84 0.00 0.00 0.00
May 181.47 5.09 176.38 589.18 12.29 0.00 0.00 0.00
June 187.85 6.96 180.90 639.08 8.96 0.00 0.00 0.00
July 185.27 2.93 182.33 563.64 2.12 0.00 0.00 0.00
August 170.08 0.53 169.55 470.23 8.75 0.00 0.00 0.00
September 151.55 0.01 151.54 372.50 28.46 0.00 0.00 0.00
October 131.29 0.00 131.29 267.68 161.13 0.00 0.00 0.00
November 111.20 0.00 111.20 139.77 321.55 0.00 0.00 0.00
December 103.05 0.00 103.05 60.95 459.67 0.00 0.00 0.00
                 
Annual Sum or Average 147.40 1.35 146.05 328.96 175.05 0.00 0.00 0.00
Minimum of Months 103.05 0.00 103.05 56.47 2.12 0.00 0.00 0.00
Maximum of Months 187.85 6.96 182.33 639.08 464.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.64 0.00 105.64 56.47 464.13 0.00 0.00 0.00
February 125.27 0.00 125.27 119.38 358.65 0.00 0.00 0.00
March 150.95 0.00 150.95 238.86 210.17 0.00 0.00 0.00
April 163.80 0.56 163.24 417.72 73.84 0.00 0.00 0.00
May 181.47 5.09 176.38 589.18 12.29 0.00 0.00 0.00
June 187.85 6.96 180.90 639.08 8.96 0.00 0.00 0.00
July 185.27 2.93 182.33 563.64 2.12 0.00 0.00 0.00
August 170.08 0.53 169.55 470.23 8.75 0.00 0.00 0.00
September 151.55 0.01 151.54 372.50 28.46 0.00 0.00 0.00
October 131.29 0.00 131.29 267.68 161.13 0.00 0.00 0.00
November 111.20 0.00 111.20 139.77 321.55 0.00 0.00 0.00
December 103.05 0.00 103.05 60.95 459.67 0.00 0.00 0.00
                 
Annual Sum or Average 147.40 1.35 146.05 328.96 175.05 0.00 0.00 0.00
Minimum of Months 103.05 0.00 103.05 56.47 2.12 0.00 0.00 0.00
Maximum of Months 187.85 6.96 182.33 639.08 464.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 105.64 0.00 105.64 56.47 464.11 0.00 0.00 0.00
February 125.27 0.00 125.27 119.37 358.63 0.00 0.00 0.00
March 150.95 0.00 150.95 238.85 210.16 0.00 0.00 0.00
April 163.79 0.56 163.23 417.70 73.84 0.00 0.00 0.00
May 181.47 5.09 176.37 589.16 12.29 0.00 0.00 0.00
June 187.85 6.96 180.89 639.06 8.96 0.00 0.00 0.00
July 185.26 2.93 182.33 563.61 2.12 0.00 0.00 0.00
August 170.07 0.53 169.54 470.21 8.75 0.00 0.00 0.00
September 151.54 0.01 151.53 372.48 28.46 0.00 0.00 0.00
October 131.28 0.00 131.28 267.67 161.13 0.00 0.00 0.00
November 111.20 0.00 111.20 139.76 321.54 0.00 0.00 0.00
December 103.05 0.00 103.05 60.94 459.65 0.00 0.00 0.00
                 
Annual Sum or Average 147.39 1.35 146.05 328.95 175.04 0.00 0.00 0.00
Minimum of Months 103.05 0.00 103.05 56.47 2.12 0.00 0.00 0.00
Maximum of Months 187.85 6.96 182.33 639.06 464.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 251.44 100.93 150.52 257.04 470.04 0.00 0.00 0.00
February 305.47 126.11 179.36 405.46 367.57 0.00 0.00 0.00
March 372.64 153.81 218.83 632.45 218.52 0.00 0.00 0.00
April 443.35 206.71 236.64 951.65 78.69 0.00 0.00 0.00
May 436.38 193.47 242.91 1086.60 14.02 0.00 0.00 0.00
June 355.15 117.84 237.31 985.28 9.41 0.00 0.00 0.00
July 298.50 63.03 235.46 806.47 1.60 0.00 0.00 0.00
August 268.96 46.81 222.15 682.50 6.92 0.00 0.00 0.00
September 287.35 80.14 207.22 635.74 31.05 0.00 0.00 0.00
October 314.33 126.97 187.36 609.72 173.36 0.00 0.00 0.00
November 278.70 119.63 159.07 425.85 331.16 0.00 0.00 0.00
December 243.01 96.28 146.73 270.68 463.35 0.00 0.00 0.00
                 
Annual Sum or Average 321.19 119.13 202.06 646.62 179.68 0.00 0.00 0.00
Minimum of Months 243.01 46.81 146.73 257.04 1.60 0.00 0.00 0.00
Maximum of Months 443.35 206.71 242.91 1086.60 470.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 251.44 100.93 150.52 257.04 470.04 0.00 0.00 0.00
February 305.47 126.11 179.36 405.46 367.57 0.00 0.00 0.00
March 372.64 153.81 218.83 632.45 218.52 0.00 0.00 0.00
April 443.35 206.71 236.64 951.65 78.69 0.00 0.00 0.00
May 436.38 193.47 242.91 1086.60 14.02 0.00 0.00 0.00
June 355.15 117.84 237.31 985.28 9.41 0.00 0.00 0.00
July 298.50 63.03 235.46 806.47 1.60 0.00 0.00 0.00
August 268.96 46.81 222.15 682.50 6.92 0.00 0.00 0.00
September 287.35 80.14 207.22 635.74 31.05 0.00 0.00 0.00
October 314.33 126.97 187.36 609.72 173.36 0.00 0.00 0.00
November 278.70 119.63 159.07 425.85 331.16 0.00 0.00 0.00
December 243.01 96.28 146.73 270.68 463.35 0.00 0.00 0.00
                 
Annual Sum or Average 321.19 119.13 202.06 646.62 179.68 0.00 0.00 0.00
Minimum of Months 243.01 46.81 146.73 257.04 1.60 0.00 0.00 0.00
Maximum of Months 443.35 206.71 242.91 1086.60 470.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 251.44 100.92 150.52 257.04 470.04 0.00 0.00 0.00
February 305.47 126.11 179.36 405.45 367.56 0.00 0.00 0.00
March 372.64 153.81 218.83 632.43 218.51 0.00 0.00 0.00
April 443.34 206.71 236.63 951.63 78.69 0.00 0.00 0.00
May 436.37 193.46 242.91 1086.58 14.02 0.00 0.00 0.00
June 355.15 117.84 237.31 985.26 9.41 0.00 0.00 0.00
July 298.49 63.03 235.46 806.46 1.60 0.00 0.00 0.00
August 268.95 46.80 222.15 682.48 6.92 0.00 0.00 0.00
September 287.35 80.13 207.21 635.73 31.05 0.00 0.00 0.00
October 314.32 126.97 187.36 609.71 173.36 0.00 0.00 0.00
November 278.69 119.63 159.07 425.85 331.15 0.00 0.00 0.00
December 243.01 96.28 146.73 270.67 463.34 0.00 0.00 0.00
                 
Annual Sum or Average 321.18 119.12 202.06 646.61 179.68 0.00 0.00 0.00
Minimum of Months 243.01 46.80 146.73 257.04 1.60 0.00 0.00 0.00
Maximum of Months 443.34 206.71 242.91 1086.58 470.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 480.45 291.93 188.52 684.77 428.61 1.50 0.00 0.00
February 456.84 253.74 203.10 710.99 350.08 0.00 0.00 0.00
March 390.61 172.53 218.08 715.96 217.98 0.00 0.00 0.00
April 274.36 77.43 196.93 672.95 80.83 0.00 0.00 0.00
May 197.30 14.61 182.70 630.40 12.60 0.00 0.00 0.00
June 180.48 3.08 177.40 623.97 9.01 0.00 0.00 0.00
July 188.26 2.59 185.67 572.33 1.94 0.00 0.00 0.00
August 199.70 10.67 189.04 534.97 8.93 0.00 0.00 0.00
September 267.72 69.49 198.23 608.84 32.76 0.00 0.00 0.00
October 460.58 257.19 203.40 898.89 174.39 0.00 0.00 0.00
November 575.29 380.26 195.04 976.18 325.31 0.00 0.00 0.00
December 513.44 321.73 191.70 758.05 432.30 0.00 0.00 0.00
                 
Annual Sum or Average 348.13 154.03 194.10 698.69 172.11 1.50 0.00 0.00
Minimum of Months 180.48 2.59 177.40 534.97 1.94 0.00 0.00 0.00
Maximum of Months 575.29 380.26 218.08 976.18 432.30 1.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 480.45 291.93 188.52 684.77 428.61 1.50 0.00 0.00
February 456.84 253.74 203.10 710.99 350.08 0.00 0.00 0.00
March 390.61 172.53 218.08 715.96 217.98 0.00 0.00 0.00
April 274.36 77.43 196.93 672.95 80.83 0.00 0.00 0.00
May 197.30 14.61 182.70 630.40 12.60 0.00 0.00 0.00
June 180.48 3.08 177.40 623.97 9.01 0.00 0.00 0.00
July 188.26 2.59 185.67 572.33 1.94 0.00 0.00 0.00
August 199.70 10.67 189.04 534.97 8.93 0.00 0.00 0.00
September 267.72 69.49 198.23 608.84 32.76 0.00 0.00 0.00
October 460.58 257.19 203.40 898.89 174.39 0.00 0.00 0.00
November 575.29 380.26 195.04 976.17 325.31 0.00 0.00 0.00
December 513.44 321.73 191.70 758.04 432.30 0.00 0.00 0.00
                 
Annual Sum or Average 348.13 154.03 194.10 698.69 172.11 1.50 0.00 0.00
Minimum of Months 180.48 2.59 177.40 534.97 1.94 0.00 0.00 0.00
Maximum of Months 575.29 380.26 218.08 976.17 432.30 1.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 480.45 291.93 188.52 684.77 428.61 1.50 0.00 0.00
February 456.84 253.74 203.10 710.99 350.08 0.00 0.00 0.00
March 390.61 172.53 218.08 715.96 217.98 0.00 0.00 0.00
April 274.36 77.43 196.93 672.95 80.83 0.00 0.00 0.00
May 197.30 14.61 182.70 630.40 12.60 0.00 0.00 0.00
June 180.48 3.08 177.40 623.97 9.01 0.00 0.00 0.00
July 188.26 2.59 185.67 572.33 1.94 0.00 0.00 0.00
August 199.70 10.67 189.04 534.97 8.93 0.00 0.00 0.00
September 267.72 69.49 198.23 608.84 32.76 0.00 0.00 0.00
October 460.58 257.19 203.40 898.89 174.39 0.00 0.00 0.00
November 575.29 380.26 195.04 976.18 325.31 0.00 0.00 0.00
December 513.44 321.73 191.70 758.05 432.30 0.00 0.00 0.00
                 
Annual Sum or Average 348.13 154.03 194.10 698.69 172.11 1.50 0.00 0.00
Minimum of Months 180.48 2.59 177.40 534.97 1.94 0.00 0.00 0.00
Maximum of Months 575.29 380.26 218.08 976.18 432.30 1.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 480.45 291.93 188.52 684.77 428.61 1.50 0.00 0.00
February 456.84 253.74 203.10 710.99 350.08 0.00 0.00 0.00
March 390.61 172.53 218.08 715.96 217.98 0.00 0.00 0.00
April 274.36 77.43 196.93 672.95 80.83 0.00 0.00 0.00
May 197.30 14.61 182.70 630.40 12.60 0.00 0.00 0.00
June 180.48 3.08 177.40 623.97 9.01 0.00 0.00 0.00
July 188.26 2.59 185.67 572.33 1.94 0.00 0.00 0.00
August 199.70 10.67 189.04 534.97 8.93 0.00 0.00 0.00
September 267.72 69.49 198.23 608.84 32.76 0.00 0.00 0.00
October 460.58 257.19 203.40 898.89 174.39 0.00 0.00 0.00
November 575.29 380.26 195.04 976.17 325.31 0.00 0.00 0.00
December 513.44 321.73 191.70 758.04 432.30 0.00 0.00 0.00
                 
Annual Sum or Average 348.13 154.03 194.10 698.69 172.11 1.50 0.00 0.00
Minimum of Months 180.48 2.59 177.40 534.97 1.94 0.00 0.00 0.00
Maximum of Months 575.29 380.26 218.08 976.17 432.30 1.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 480.43 291.92 188.51 684.74 428.60 1.50 0.00 0.00
February 456.82 253.73 203.09 710.96 350.06 0.00 0.00 0.00
March 390.59 172.52 218.07 715.93 217.97 0.00 0.00 0.00
April 274.35 77.43 196.92 672.93 80.82 0.00 0.00 0.00
May 197.30 14.61 182.69 630.38 12.60 0.00 0.00 0.00
June 180.48 3.08 177.40 623.95 9.01 0.00 0.00 0.00
July 188.25 2.59 185.66 572.31 1.94 0.00 0.00 0.00
August 199.70 10.67 189.03 534.95 8.93 0.00 0.00 0.00
September 267.71 69.48 198.22 608.82 32.76 0.00 0.00 0.00
October 460.57 257.18 203.39 898.86 174.38 0.00 0.00 0.00
November 575.27 380.24 195.03 976.14 325.29 0.00 0.00 0.00
December 513.41 321.72 191.69 758.02 432.28 0.00 0.00 0.00
                 
Annual Sum or Average 348.12 154.02 194.09 698.66 172.10 1.50 0.00 0.00
Minimum of Months 180.48 2.59 177.40 534.95 1.94 0.00 0.00 0.00
Maximum of Months 575.27 380.24 218.07 976.14 432.28 1.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 246.00 95.73 150.26 279.24 550.69 0.00 0.00 0.00
February 281.30 103.67 177.64 378.54 447.69 0.00 0.00 0.00
March 364.78 145.82 218.96 613.80 283.96 0.00 0.00 0.00
April 443.39 207.93 235.46 922.17 124.78 0.00 0.00 0.00
May 419.85 178.09 241.76 1038.09 24.89 0.00 0.00 0.00
June 394.35 153.18 241.17 1023.99 18.41 0.00 0.00 0.00
July 292.63 56.92 235.71 746.68 9.07 0.00 0.00 0.00
August 268.75 47.76 220.98 628.26 29.63 0.00 0.00 0.00
September 295.42 86.73 208.70 635.83 52.24 0.00 0.00 0.00
October 307.49 122.44 185.05 592.86 218.18 0.00 0.00 0.00
November 278.18 118.56 159.62 434.36 412.20 0.00 0.00 0.00
December 238.04 90.77 147.27 266.45 576.41 0.00 0.00 0.00
                 
Annual Sum or Average 319.12 117.14 201.98 630.73 228.06 0.00 0.00 0.00
Minimum of Months 238.04 47.76 147.27 266.45 9.07 0.00 0.00 0.00
Maximum of Months 443.39 207.93 241.76 1038.09 576.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 246.00 95.73 150.26 279.24 550.69 0.00 0.00 0.00
February 281.30 103.67 177.64 378.54 447.69 0.00 0.00 0.00
March 364.78 145.82 218.96 613.80 283.96 0.00 0.00 0.00
April 443.39 207.93 235.46 922.17 124.78 0.00 0.00 0.00
May 419.85 178.09 241.76 1038.09 24.89 0.00 0.00 0.00
June 394.35 153.18 241.17 1023.99 18.41 0.00 0.00 0.00
July 292.63 56.92 235.71 746.68 9.07 0.00 0.00 0.00
August 268.75 47.76 220.98 628.26 29.63 0.00 0.00 0.00
September 295.42 86.73 208.70 635.83 52.24 0.00 0.00 0.00
October 307.49 122.44 185.05 592.86 218.18 0.00 0.00 0.00
November 278.18 118.56 159.62 434.36 412.20 0.00 0.00 0.00
December 238.04 90.77 147.27 266.45 576.41 0.00 0.00 0.00
                 
Annual Sum or Average 319.12 117.14 201.98 630.73 228.06 0.00 0.00 0.00
Minimum of Months 238.04 47.76 147.27 266.45 9.07 0.00 0.00 0.00
Maximum of Months 443.39 207.93 241.76 1038.09 576.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 245.99 95.73 150.26 279.24 550.68 0.00 0.00 0.00
February 281.30 103.67 177.63 378.54 447.68 0.00 0.00 0.00
March 364.77 145.81 218.96 613.79 283.96 0.00 0.00 0.00
April 443.38 207.93 235.45 922.16 124.78 0.00 0.00 0.00
May 419.84 178.09 241.75 1038.07 24.89 0.00 0.00 0.00
June 394.34 153.17 241.17 1023.97 18.41 0.00 0.00 0.00
July 292.62 56.91 235.71 746.67 9.07 0.00 0.00 0.00
August 268.74 47.76 220.98 628.25 29.63 0.00 0.00 0.00
September 295.42 86.73 208.69 635.82 52.24 0.00 0.00 0.00
October 307.48 122.44 185.04 592.84 218.18 0.00 0.00 0.00
November 278.17 118.55 159.62 434.35 412.20 0.00 0.00 0.00
December 238.03 90.77 147.26 266.45 576.40 0.00 0.00 0.00
                 
Annual Sum or Average 319.12 117.14 201.97 630.72 228.06 0.00 0.00 0.00
Minimum of Months 238.03 47.76 147.26 266.45 9.07 0.00 0.00 0.00
Maximum of Months 443.38 207.93 241.75 1038.07 576.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 528.19 0.00 528.19 378.48 1992.23 0.00 0.00 0.00
February 626.35 0.00 626.35 670.48 1593.38 0.00 0.00 0.00
March 754.75 0.00 754.75 1229.40 985.37 0.00 0.00 0.00
April 818.97 2.78 816.19 2139.83 346.87 0.00 0.00 0.00
May 907.36 25.46 881.90 2967.13 63.50 0.00 0.00 0.00
June 939.26 34.79 904.47 3218.55 47.99 0.00 0.00 0.00
July 926.33 14.67 911.66 2849.76 12.55 0.00 0.00 0.00
August 850.39 2.65 847.74 2405.83 41.01 0.00 0.00 0.00
September 757.72 0.05 757.67 1875.39 143.65 0.00 0.00 0.00
October 656.43 0.00 656.43 1368.21 776.59 0.00 0.00 0.00
November 556.01 0.00 556.01 760.27 1454.98 0.00 0.00 0.00
December 515.26 0.00 515.26 410.36 1961.74 0.00 0.00 0.00
                 
Annual Sum or Average 736.98 6.73 730.25 1694.46 781.49 0.00 0.00 0.00
Minimum of Months 515.26 0.00 515.26 378.48 12.55 0.00 0.00 0.00
Maximum of Months 939.26 34.79 911.66 3218.55 1992.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 754.32 302.78 451.55 817.64 1269.18 0.00 0.00 0.00
February 916.41 378.34 538.07 1227.04 1039.95 0.00 0.00 0.00
March 1117.92 461.44 656.48 1879.70 657.30 0.00 0.00 0.00
April 1330.04 620.13 709.91 2829.79 253.16 0.00 0.00 0.00
May 1309.12 580.39 728.73 3231.40 48.47 0.00 0.00 0.00
June 1065.45 353.52 711.94 2927.40 34.76 0.00 0.00 0.00
July 895.49 189.10 706.38 2393.10 8.02 0.00 0.00 0.00
August 806.87 140.41 666.46 2024.39 29.72 0.00 0.00 0.00
September 862.05 240.40 621.64 1885.68 106.82 0.00 0.00 0.00
October 942.98 380.90 562.08 1814.00 531.24 0.00 0.00 0.00
November 836.09 358.89 477.20 1281.87 957.73 0.00 0.00 0.00
December 729.03 288.85 440.19 850.41 1278.80 0.00 0.00 0.00
                 
Annual Sum or Average 963.55 357.37 606.18 1932.68 515.61 0.00 0.00 0.00
Minimum of Months 729.03 140.41 440.19 817.64 8.02 0.00 0.00 0.00
Maximum of Months 1330.04 620.13 728.73 3231.40 1278.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2402.22 1459.65 942.57 3420.95 2060.45 0.00 0.00 0.00
February 2284.16 1268.69 1015.47 3538.62 1699.69 0.00 0.00 0.00
March 1953.02 862.63 1090.39 3564.67 1078.04 0.00 0.00 0.00
April 1371.80 387.17 984.64 3378.06 398.41 0.00 0.00 0.00
May 986.51 73.03 913.48 3170.06 64.06 0.00 0.00 0.00
June 902.40 15.40 887.00 3144.36 47.65 0.00 0.00 0.00
July 941.29 12.95 928.34 2893.61 11.12 0.00 0.00 0.00
August 998.51 53.33 945.18 2715.97 43.26 0.00 0.00 0.00
September 1338.58 347.43 991.15 3034.46 173.38 0.00 0.00 0.00
October 2302.89 1285.93 1016.97 4471.27 887.24 0.00 0.00 0.00
November 2876.44 1901.26 975.17 4858.09 1602.88 0.00 0.00 0.00
December 2567.15 1608.65 958.50 3794.69 2075.80 0.00 0.00 0.00
                 
Annual Sum or Average 1740.64 770.14 970.49 3497.26 841.31 0.00 0.00 0.00
Minimum of Months 902.40 12.95 887.00 2715.97 11.12 0.00 0.00 0.00
Maximum of Months 2876.44 1901.26 1090.39 4858.09 2075.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 737.99 287.20 450.79 900.18 1421.03 0.00 0.00 0.00
February 843.91 311.00 532.90 1190.28 1158.21 0.00 0.00 0.00
March 1094.33 437.44 656.89 1883.22 741.23 0.00 0.00 0.00
April 1330.15 623.79 706.36 2836.50 298.29 0.00 0.00 0.00
May 1259.53 534.27 725.26 3143.70 64.43 0.00 0.00 0.00
June 1183.03 459.52 723.51 3129.51 43.82 0.00 0.00 0.00
July 877.87 170.75 707.12 2328.55 12.91 0.00 0.00 0.00
August 806.23 143.29 662.94 2006.47 38.32 0.00 0.00 0.00
September 886.26 260.18 626.08 1931.46 130.91 0.00 0.00 0.00
October 922.46 367.32 555.14 1810.46 588.40 0.00 0.00 0.00
November 834.52 355.67 478.85 1358.68 1065.94 0.00 0.00 0.00
December 714.10 272.30 441.80 894.86 1401.68 0.00 0.00 0.00
                 
Annual Sum or Average 957.36 351.43 605.93 1953.43 577.83 0.00 0.00 0.00
Minimum of Months 714.10 143.29 441.80 894.86 12.91 0.00 0.00 0.00
Maximum of Months 1330.15 623.79 725.26 3143.70 1421.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 528.19 0.00 528.19 425.81 1809.15 0.00 0.00 0.00
February 626.35 0.00 626.35 704.41 1483.74 0.00 0.00 0.00
March 754.75 0.00 754.75 1226.15 952.42 0.00 0.00 0.00
April 818.97 2.78 816.19 2106.07 352.87 0.00 0.00 0.00
May 907.36 25.46 881.90 2918.34 71.53 0.00 0.00 0.00
June 939.26 34.79 904.47 3166.23 52.25 0.00 0.00 0.00
July 926.33 14.67 911.66 2792.85 13.39 0.00 0.00 0.00
August 850.39 2.65 847.74 2360.49 44.43 0.00 0.00 0.00
September 757.72 0.05 757.67 1844.74 154.04 0.00 0.00 0.00
October 656.43 0.00 656.43 1356.29 761.31 0.00 0.00 0.00
November 556.01 0.00 556.01 786.47 1366.01 0.00 0.00 0.00
December 515.26 0.00 515.26 466.92 1784.25 0.00 0.00 0.00
                 
Annual Sum or Average 736.98 6.73 730.25 1684.33 733.78 0.00 0.00 0.00
Minimum of Months 515.26 0.00 515.26 425.81 13.39 0.00 0.00 0.00
Maximum of Months 939.26 34.79 911.66 3166.23 1809.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 754.32 302.78 451.55 876.91 1153.94 0.00 0.00 0.00
February 916.41 378.34 538.07 1259.90 977.46 0.00 0.00 0.00
March 1117.92 461.44 656.48 1883.80 639.87 0.00 0.00 0.00
April 1330.04 620.13 709.91 2815.18 256.15 0.00 0.00 0.00
May 1309.12 580.39 728.73 3206.94 53.16 0.00 0.00 0.00
June 1065.45 353.52 711.94 2901.61 37.28 0.00 0.00 0.00
July 895.49 189.10 706.38 2364.41 8.37 0.00 0.00 0.00
August 806.87 140.41 666.46 2003.71 31.87 0.00 0.00 0.00
September 862.05 240.40 621.64 1873.55 112.88 0.00 0.00 0.00
October 942.98 380.90 562.08 1813.71 522.20 0.00 0.00 0.00
November 836.09 358.89 477.20 1306.27 909.47 0.00 0.00 0.00
December 729.03 288.85 440.19 907.79 1172.83 0.00 0.00 0.00
                 
Annual Sum or Average 963.55 357.37 606.18 1936.85 487.37 0.00 0.00 0.00
Minimum of Months 729.03 140.41 440.19 876.91 8.37 0.00 0.00 0.00
Maximum of Months 1330.04 620.13 728.73 3206.94 1172.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2402.22 1459.65 942.57 3479.63 1891.40 0.00 0.00 0.00
February 2284.16 1268.69 1015.47 3562.98 1604.02 0.00 0.00 0.00
March 1953.02 862.63 1090.39 3553.67 1048.28 0.00 0.00 0.00
April 1371.80 387.17 984.64 3343.95 403.54 0.00 0.00 0.00
May 986.51 73.03 913.48 3121.41 71.68 0.00 0.00 0.00
June 902.40 15.40 887.00 3091.70 52.07 0.00 0.00 0.00
July 941.29 12.95 928.34 2836.51 11.83 0.00 0.00 0.00
August 998.51 53.33 945.18 2671.37 46.91 0.00 0.00 0.00
September 1338.58 347.43 991.15 3003.33 183.66 0.00 0.00 0.00
October 2302.89 1285.93 1016.97 4456.15 872.17 0.00 0.00 0.00
November 2876.44 1901.26 975.17 4868.53 1531.56 0.00 0.00 0.00
December 2567.15 1608.65 958.50 3851.21 1927.58 0.00 0.00 0.00
                 
Annual Sum or Average 1740.64 770.14 970.49 3485.09 800.01 0.00 0.00 0.00
Minimum of Months 902.40 12.95 887.00 2671.37 11.83 0.00 0.00 0.00
Maximum of Months 2876.44 1901.26 1090.39 4868.53 1927.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 737.99 287.20 450.79 924.86 1312.43 0.00 0.00 0.00
February 843.91 311.00 532.90 1202.34 1094.43 0.00 0.00 0.00
March 1094.33 437.44 656.89 1874.42 720.67 0.00 0.00 0.00
April 1330.15 623.79 706.36 2814.00 300.29 0.00 0.00 0.00
May 1259.53 534.27 725.26 3114.85 68.80 0.00 0.00 0.00
June 1183.03 459.52 723.51 3097.64 46.18 0.00 0.00 0.00
July 877.87 170.75 707.12 2295.16 13.75 0.00 0.00 0.00
August 806.23 143.29 662.94 1980.14 41.42 0.00 0.00 0.00
September 886.26 260.18 626.08 1912.48 136.85 0.00 0.00 0.00
October 922.46 367.32 555.14 1800.63 577.89 0.00 0.00 0.00
November 834.52 355.67 478.85 1366.11 1015.20 0.00 0.00 0.00
December 714.10 272.30 441.80 922.87 1301.37 0.00 0.00 0.00
                 
Annual Sum or Average 957.36 351.43 605.93 1944.31 549.93 0.00 0.00 0.00
Minimum of Months 714.10 143.29 441.80 922.87 13.75 0.00 0.00 0.00
Maximum of Months 1330.15 623.79 725.26 3114.85 1312.43 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282947E+09 0.00 0.282947E+09 0.151246E+09 0.124314E+10
February 0.303056E+09 0.00 0.303056E+09 0.288796E+09 0.867645E+09
March 0.404311E+09 0.00 0.404311E+09 0.639756E+09 0.562925E+09
April 0.424558E+09 1439819.52 0.423118E+09 0.108272E+10 0.191401E+09
May 0.486059E+09 13639734.17 0.472420E+09 0.157807E+10 32907128.36
June 0.486918E+09 18035552.38 0.468883E+09 0.165650E+10 23222445.81
July 0.496220E+09 7857944.09 0.488362E+09 0.150964E+10 5676202.21
August 0.455544E+09 1419727.41 0.454125E+09 0.125947E+10 23434920.39
September 0.392809E+09 27582.24 0.392782E+09 0.965515E+09 73778355.91
October 0.351643E+09 0.00 0.351643E+09 0.716957E+09 0.431583E+09
November 0.288237E+09 0.00 0.288237E+09 0.362277E+09 0.833460E+09
December 0.276020E+09 0.00 0.276020E+09 0.163237E+09 0.123119E+10
           
Annual Sum or Average 0.464832E+10 42420359.81 0.460590E+10 0.103742E+11 0.552036E+10
Minimum of Months 0.276020E+09 0.00 0.276020E+09 0.151246E+09 5676202.21
Maximum of Months 0.496220E+09 18035552.38 0.488362E+09 0.165650E+10 0.124314E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282947E+09 0.00 0.282947E+09 0.151245E+09 0.124314E+10
February 0.303056E+09 0.00 0.303056E+09 0.288796E+09 0.867644E+09
March 0.404311E+09 0.00 0.404311E+09 0.639756E+09 0.562924E+09
April 0.424558E+09 1439817.79 0.423118E+09 0.108272E+10 0.191401E+09
May 0.486059E+09 13639717.81 0.472419E+09 0.157806E+10 32907065.88
June 0.486918E+09 18035530.74 0.468882E+09 0.165650E+10 23222423.47
July 0.496220E+09 7857934.66 0.488362E+09 0.150964E+10 5676188.97
August 0.455544E+09 1419725.71 0.454124E+09 0.125947E+10 23434883.73
September 0.392809E+09 27582.20 0.392781E+09 0.965515E+09 73778254.10
October 0.351643E+09 0.00 0.351643E+09 0.716957E+09 0.431583E+09
November 0.288237E+09 0.00 0.288237E+09 0.362276E+09 0.833460E+09
December 0.276019E+09 0.00 0.276019E+09 0.163237E+09 0.123119E+10
           
Annual Sum or Average 0.464832E+10 42420308.91 0.460590E+10 0.103742E+11 0.552036E+10
Minimum of Months 0.276019E+09 0.00 0.276019E+09 0.151245E+09 5676188.97
Maximum of Months 0.496220E+09 18035530.74 0.488362E+09 0.165650E+10 0.124314E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282947E+09 0.00 0.282947E+09 0.151246E+09 0.124314E+10
February 0.303056E+09 0.00 0.303056E+09 0.288796E+09 0.867645E+09
March 0.404311E+09 0.00 0.404311E+09 0.639756E+09 0.562925E+09
April 0.424558E+09 1439819.52 0.423118E+09 0.108272E+10 0.191401E+09
May 0.486059E+09 13639734.17 0.472420E+09 0.157807E+10 32907128.36
June 0.486918E+09 18035552.38 0.468883E+09 0.165650E+10 23222445.81
July 0.496220E+09 7857944.09 0.488362E+09 0.150964E+10 5676202.21
August 0.455544E+09 1419727.41 0.454125E+09 0.125947E+10 23434920.39
September 0.392809E+09 27582.24 0.392782E+09 0.965515E+09 73778355.91
October 0.351643E+09 0.00 0.351643E+09 0.716957E+09 0.431583E+09
November 0.288237E+09 0.00 0.288237E+09 0.362277E+09 0.833460E+09
December 0.276020E+09 0.00 0.276020E+09 0.163237E+09 0.123119E+10
           
Annual Sum or Average 0.464832E+10 42420359.81 0.460590E+10 0.103742E+11 0.552036E+10
Minimum of Months 0.276020E+09 0.00 0.276020E+09 0.151246E+09 5676202.21
Maximum of Months 0.496220E+09 18035552.38 0.488362E+09 0.165650E+10 0.124314E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282947E+09 0.00 0.282947E+09 0.151245E+09 0.124314E+10
February 0.303056E+09 0.00 0.303056E+09 0.288796E+09 0.867644E+09
March 0.404311E+09 0.00 0.404311E+09 0.639756E+09 0.562924E+09
April 0.424558E+09 1439817.79 0.423118E+09 0.108272E+10 0.191401E+09
May 0.486059E+09 13639717.81 0.472419E+09 0.157806E+10 32907065.88
June 0.486918E+09 18035530.74 0.468882E+09 0.165650E+10 23222423.47
July 0.496220E+09 7857934.66 0.488362E+09 0.150964E+10 5676188.97
August 0.455544E+09 1419725.71 0.454124E+09 0.125947E+10 23434883.73
September 0.392809E+09 27582.20 0.392781E+09 0.965515E+09 73778254.10
October 0.351643E+09 0.00 0.351643E+09 0.716957E+09 0.431583E+09
November 0.288237E+09 0.00 0.288237E+09 0.362276E+09 0.833460E+09
December 0.276019E+09 0.00 0.276019E+09 0.163237E+09 0.123119E+10
           
Annual Sum or Average 0.464832E+10 42420308.91 0.460590E+10 0.103742E+11 0.552036E+10
Minimum of Months 0.276019E+09 0.00 0.276019E+09 0.151245E+09 5676188.97
Maximum of Months 0.496220E+09 18035530.74 0.488362E+09 0.165650E+10 0.124314E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282935E+09 0.00 0.282935E+09 0.151240E+09 0.124309E+10
February 0.303044E+09 0.00 0.303044E+09 0.288785E+09 0.867610E+09
March 0.404295E+09 0.00 0.404295E+09 0.639730E+09 0.562902E+09
April 0.424541E+09 1439761.49 0.423101E+09 0.108267E+10 0.191394E+09
May 0.486040E+09 13639184.43 0.472401E+09 0.157800E+10 32905802.06
June 0.486899E+09 18034825.47 0.468864E+09 0.165644E+10 23221509.84
July 0.496200E+09 7857627.38 0.488342E+09 0.150958E+10 5675973.43
August 0.455526E+09 1419670.19 0.454106E+09 0.125942E+10 23433975.85
September 0.392793E+09 27581.12 0.392766E+09 0.965476E+09 73775382.31
October 0.351629E+09 0.00 0.351629E+09 0.716928E+09 0.431566E+09
November 0.288226E+09 0.00 0.288226E+09 0.362262E+09 0.833427E+09
December 0.276008E+09 0.00 0.276008E+09 0.163231E+09 0.123114E+10
           
Annual Sum or Average 0.464814E+10 42418650.09 0.460572E+10 0.103738E+11 0.552013E+10
Minimum of Months 0.276008E+09 0.00 0.276008E+09 0.151240E+09 5675973.43
Maximum of Months 0.496200E+09 18034825.47 0.488342E+09 0.165644E+10 0.124309E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.673468E+09 0.270321E+09 0.403147E+09 0.688466E+09 0.125897E+10
February 0.739000E+09 0.305094E+09 0.433906E+09 0.980880E+09 0.889222E+09
March 0.998091E+09 0.411977E+09 0.586114E+09 0.169394E+10 0.585274E+09
April 0.114916E+10 0.535799E+09 0.613365E+09 0.246667E+10 0.203967E+09
May 0.116880E+10 0.518180E+09 0.650615E+09 0.291036E+10 37563141.90
June 0.920561E+09 0.305441E+09 0.615119E+09 0.255383E+10 24397605.88
July 0.799498E+09 0.168833E+09 0.630665E+09 0.216005E+10 4283196.51
August 0.720381E+09 0.125363E+09 0.595018E+09 0.182800E+10 18546528.01
September 0.744818E+09 0.207711E+09 0.537106E+09 0.164784E+10 80485247.77
October 0.841901E+09 0.340072E+09 0.501828E+09 0.163307E+10 0.464324E+09
November 0.722388E+09 0.310081E+09 0.412306E+09 0.110381E+10 0.858361E+09
December 0.650888E+09 0.257886E+09 0.393003E+09 0.724978E+09 0.124103E+10
           
Annual Sum or Average 0.101290E+11 0.375676E+10 0.637219E+10 0.203919E+11 0.566642E+10
Minimum of Months 0.650888E+09 0.125363E+09 0.393003E+09 0.688466E+09 4283196.51
Maximum of Months 0.116880E+10 0.535799E+09 0.650615E+09 0.291036E+10 0.125897E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.673468E+09 0.270321E+09 0.403147E+09 0.688466E+09 0.125897E+10
February 0.739000E+09 0.305094E+09 0.433906E+09 0.980880E+09 0.889222E+09
March 0.998091E+09 0.411977E+09 0.586114E+09 0.169394E+10 0.585274E+09
April 0.114916E+10 0.535799E+09 0.613365E+09 0.246667E+10 0.203967E+09
May 0.116880E+10 0.518180E+09 0.650615E+09 0.291036E+10 37563141.90
June 0.920561E+09 0.305441E+09 0.615119E+09 0.255383E+10 24397605.88
July 0.799498E+09 0.168833E+09 0.630665E+09 0.216005E+10 4283196.51
August 0.720381E+09 0.125363E+09 0.595018E+09 0.182800E+10 18546528.01
September 0.744818E+09 0.207711E+09 0.537106E+09 0.164784E+10 80485247.77
October 0.841901E+09 0.340072E+09 0.501828E+09 0.163307E+10 0.464324E+09
November 0.722388E+09 0.310081E+09 0.412306E+09 0.110381E+10 0.858361E+09
December 0.650888E+09 0.257886E+09 0.393003E+09 0.724978E+09 0.124103E+10
           
Annual Sum or Average 0.101290E+11 0.375676E+10 0.637219E+10 0.203919E+11 0.566642E+10
Minimum of Months 0.650888E+09 0.125363E+09 0.393003E+09 0.688466E+09 4283196.51
Maximum of Months 0.116880E+10 0.535799E+09 0.650615E+09 0.291036E+10 0.125897E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.673456E+09 0.270316E+09 0.403140E+09 0.688454E+09 0.125894E+10
February 0.738986E+09 0.305088E+09 0.433898E+09 0.980862E+09 0.889206E+09
March 0.998073E+09 0.411970E+09 0.586103E+09 0.169391E+10 0.585263E+09
April 0.114914E+10 0.535789E+09 0.613354E+09 0.246662E+10 0.203964E+09
May 0.116877E+10 0.518171E+09 0.650603E+09 0.291030E+10 37562455.54
June 0.920544E+09 0.305436E+09 0.615108E+09 0.255379E+10 24397160.08
July 0.799483E+09 0.168830E+09 0.630654E+09 0.216001E+10 4283118.25
August 0.720368E+09 0.125361E+09 0.595007E+09 0.182797E+10 18546189.12
September 0.744804E+09 0.207707E+09 0.537097E+09 0.164781E+10 80483777.13
October 0.841885E+09 0.340066E+09 0.501819E+09 0.163304E+10 0.464316E+09
November 0.722374E+09 0.310076E+09 0.412299E+09 0.110379E+10 0.858345E+09
December 0.650876E+09 0.257881E+09 0.392995E+09 0.724965E+09 0.124101E+10
           
Annual Sum or Average 0.101288E+11 0.375669E+10 0.637208E+10 0.203915E+11 0.566632E+10
Minimum of Months 0.650876E+09 0.125361E+09 0.392995E+09 0.688454E+09 4283118.25
Maximum of Months 0.116877E+10 0.535789E+09 0.650603E+09 0.291030E+10 0.125894E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.128684E+10 0.781916E+09 0.504922E+09 0.183409E+10 0.114800E+10
February 0.110518E+10 0.613850E+09 0.491333E+09 0.172002E+10 0.846911E+09
March 0.104620E+10 0.462100E+09 0.584105E+09 0.191762E+10 0.583844E+09
April 0.711152E+09 0.200709E+09 0.510443E+09 0.174430E+10 0.209504E+09
May 0.528459E+09 39120360.68 0.489339E+09 0.168847E+10 33736811.76
June 0.467811E+09 7983059.50 0.459828E+09 0.161733E+10 23347699.36
July 0.504237E+09 6935363.78 0.497301E+09 0.153293E+10 5197986.14
August 0.534888E+09 28567075.68 0.506321E+09 0.143287E+10 23912493.56
September 0.693930E+09 0.180111E+09 0.513819E+09 0.157812E+10 84918230.16
October 0.123363E+10 0.688853E+09 0.544776E+09 0.240760E+10 0.467088E+09
November 0.149116E+10 0.985627E+09 0.505536E+09 0.253025E+10 0.843194E+09
December 0.137519E+10 0.861730E+09 0.513456E+09 0.203035E+10 0.115786E+10
           
Annual Sum or Average 0.109787E+11 0.485750E+10 0.612118E+10 0.220340E+11 0.542752E+10
Minimum of Months 0.467811E+09 6935363.78 0.459828E+09 0.143287E+10 5197986.14
Maximum of Months 0.149116E+10 0.985627E+09 0.584105E+09 0.253025E+10 0.115786E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.128684E+10 0.781915E+09 0.504922E+09 0.183409E+10 0.114800E+10
February 0.110518E+10 0.613849E+09 0.491333E+09 0.172002E+10 0.846911E+09
March 0.104620E+10 0.462099E+09 0.584104E+09 0.191762E+10 0.583844E+09
April 0.711152E+09 0.200709E+09 0.510443E+09 0.174430E+10 0.209504E+09
May 0.528459E+09 39120313.74 0.489339E+09 0.168847E+10 33736750.22
June 0.467810E+09 7983049.92 0.459827E+09 0.161733E+10 23347678.59
July 0.504236E+09 6935355.45 0.497301E+09 0.153293E+10 5197974.36
August 0.534888E+09 28567041.40 0.506321E+09 0.143287E+10 23912457.05
September 0.693929E+09 0.180111E+09 0.513819E+09 0.157812E+10 84918120.79
October 0.123363E+10 0.688853E+09 0.544775E+09 0.240759E+10 0.467087E+09
November 0.149116E+10 0.985626E+09 0.505535E+09 0.253024E+10 0.843194E+09
December 0.137518E+10 0.861729E+09 0.513456E+09 0.203035E+10 0.115786E+10
           
Annual Sum or Average 0.109787E+11 0.485750E+10 0.612117E+10 0.220339E+11 0.542752E+10
Minimum of Months 0.467810E+09 6935355.45 0.459827E+09 0.143287E+10 5197974.36
Maximum of Months 0.149116E+10 0.985626E+09 0.584104E+09 0.253024E+10 0.115786E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.128684E+10 0.781916E+09 0.504922E+09 0.183409E+10 0.114800E+10
February 0.110518E+10 0.613850E+09 0.491333E+09 0.172002E+10 0.846911E+09
March 0.104620E+10 0.462100E+09 0.584105E+09 0.191762E+10 0.583844E+09
April 0.711152E+09 0.200709E+09 0.510443E+09 0.174430E+10 0.209504E+09
May 0.528459E+09 39120360.68 0.489339E+09 0.168847E+10 33736811.76
June 0.467811E+09 7983059.50 0.459828E+09 0.161733E+10 23347699.36
July 0.504237E+09 6935363.78 0.497301E+09 0.153293E+10 5197986.14
August 0.534888E+09 28567075.68 0.506321E+09 0.143287E+10 23912493.56
September 0.693930E+09 0.180111E+09 0.513819E+09 0.157812E+10 84918230.16
October 0.123363E+10 0.688853E+09 0.544776E+09 0.240760E+10 0.467088E+09
November 0.149116E+10 0.985627E+09 0.505536E+09 0.253025E+10 0.843194E+09
December 0.137519E+10 0.861730E+09 0.513456E+09 0.203035E+10 0.115786E+10
           
Annual Sum or Average 0.109787E+11 0.485750E+10 0.612118E+10 0.220340E+11 0.542752E+10
Minimum of Months 0.467811E+09 6935363.78 0.459828E+09 0.143287E+10 5197986.14
Maximum of Months 0.149116E+10 0.985627E+09 0.584105E+09 0.253025E+10 0.115786E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.128684E+10 0.781915E+09 0.504922E+09 0.183409E+10 0.114800E+10
February 0.110518E+10 0.613849E+09 0.491333E+09 0.172002E+10 0.846911E+09
March 0.104620E+10 0.462099E+09 0.584104E+09 0.191762E+10 0.583844E+09
April 0.711152E+09 0.200709E+09 0.510443E+09 0.174430E+10 0.209504E+09
May 0.528459E+09 39120313.74 0.489339E+09 0.168847E+10 33736750.22
June 0.467810E+09 7983049.92 0.459827E+09 0.161733E+10 23347678.59
July 0.504236E+09 6935355.45 0.497301E+09 0.153293E+10 5197974.36
August 0.534888E+09 28567041.40 0.506321E+09 0.143287E+10 23912457.05
September 0.693929E+09 0.180111E+09 0.513819E+09 0.157812E+10 84918120.79
October 0.123363E+10 0.688853E+09 0.544775E+09 0.240759E+10 0.467087E+09
November 0.149116E+10 0.985626E+09 0.505535E+09 0.253024E+10 0.843194E+09
December 0.137518E+10 0.861729E+09 0.513456E+09 0.203035E+10 0.115786E+10
           
Annual Sum or Average 0.109787E+11 0.485750E+10 0.612117E+10 0.220339E+11 0.542752E+10
Minimum of Months 0.467810E+09 6935355.45 0.459827E+09 0.143287E+10 5197974.36
Maximum of Months 0.149116E+10 0.985626E+09 0.584104E+09 0.253024E+10 0.115786E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.128679E+10 0.781885E+09 0.504902E+09 0.183402E+10 0.114795E+10
February 0.110514E+10 0.613825E+09 0.491313E+09 0.171995E+10 0.846877E+09
March 0.104616E+10 0.462081E+09 0.584081E+09 0.191755E+10 0.583821E+09
April 0.711124E+09 0.200701E+09 0.510423E+09 0.174423E+10 0.209496E+09
May 0.528438E+09 39118783.96 0.489319E+09 0.168841E+10 33735452.02
June 0.467792E+09 7982737.74 0.459809E+09 0.161727E+10 23346758.34
July 0.504216E+09 6935084.25 0.497281E+09 0.153286E+10 5197776.64
August 0.534867E+09 28565924.30 0.506301E+09 0.143281E+10 23911529.78
September 0.693902E+09 0.180104E+09 0.513798E+09 0.157806E+10 84914807.59
October 0.123358E+10 0.688826E+09 0.544754E+09 0.240750E+10 0.467069E+09
November 0.149110E+10 0.985587E+09 0.505515E+09 0.253014E+10 0.843160E+09
December 0.137513E+10 0.861695E+09 0.513436E+09 0.203027E+10 0.115782E+10
           
Annual Sum or Average 0.109782E+11 0.485731E+10 0.612093E+10 0.220331E+11 0.542730E+10
Minimum of Months 0.467792E+09 6935084.25 0.459809E+09 0.143281E+10 5197776.64
Maximum of Months 0.149110E+10 0.985587E+09 0.584081E+09 0.253014E+10 0.115782E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.658880E+09 0.256411E+09 0.402469E+09 0.747928E+09 0.147497E+10
February 0.680533E+09 0.250795E+09 0.429738E+09 0.915772E+09 0.108304E+10
March 0.977029E+09 0.390553E+09 0.586476E+09 0.164400E+10 0.760563E+09
April 0.114926E+10 0.538959E+09 0.610301E+09 0.239027E+10 0.323433E+09
May 0.112452E+10 0.476997E+09 0.647519E+09 0.278041E+10 66655785.29
June 0.102215E+10 0.397030E+09 0.625119E+09 0.265418E+10 47728368.75
July 0.783770E+09 0.152444E+09 0.631326E+09 0.199990E+10 24297524.05
August 0.719810E+09 0.127932E+09 0.591878E+09 0.168274E+10 79365866.19
September 0.765736E+09 0.224798E+09 0.540938E+09 0.164807E+10 0.135417E+09
October 0.823580E+09 0.327948E+09 0.495632E+09 0.158790E+10 0.584375E+09
November 0.721030E+09 0.307299E+09 0.413731E+09 0.112586E+10 0.106843E+10
December 0.637556E+09 0.243115E+09 0.394442E+09 0.713661E+09 0.154386E+10
           
Annual Sum or Average 0.100638E+11 0.369428E+10 0.636957E+10 0.198907E+11 0.719214E+10
Minimum of Months 0.637556E+09 0.127932E+09 0.394442E+09 0.713661E+09 24297524.05
Maximum of Months 0.114926E+10 0.538959E+09 0.647519E+09 0.278041E+10 0.154386E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.658880E+09 0.256411E+09 0.402469E+09 0.747928E+09 0.147497E+10
February 0.680533E+09 0.250795E+09 0.429738E+09 0.915772E+09 0.108304E+10
March 0.977029E+09 0.390553E+09 0.586476E+09 0.164400E+10 0.760563E+09
April 0.114926E+10 0.538959E+09 0.610301E+09 0.239027E+10 0.323433E+09
May 0.112452E+10 0.476997E+09 0.647519E+09 0.278041E+10 66655785.29
June 0.102215E+10 0.397030E+09 0.625119E+09 0.265418E+10 47728368.75
July 0.783770E+09 0.152444E+09 0.631326E+09 0.199990E+10 24297524.05
August 0.719810E+09 0.127932E+09 0.591878E+09 0.168274E+10 79365866.19
September 0.765736E+09 0.224798E+09 0.540938E+09 0.164807E+10 0.135417E+09
October 0.823580E+09 0.327948E+09 0.495632E+09 0.158790E+10 0.584375E+09
November 0.721030E+09 0.307299E+09 0.413731E+09 0.112586E+10 0.106843E+10
December 0.637556E+09 0.243115E+09 0.394442E+09 0.713661E+09 0.154386E+10
           
Annual Sum or Average 0.100638E+11 0.369428E+10 0.636957E+10 0.198907E+11 0.719214E+10
Minimum of Months 0.637556E+09 0.127932E+09 0.394442E+09 0.713661E+09 24297524.05
Maximum of Months 0.114926E+10 0.538959E+09 0.647519E+09 0.278041E+10 0.154386E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.658868E+09 0.256406E+09 0.402462E+09 0.747915E+09 0.147494E+10
February 0.680520E+09 0.250790E+09 0.429730E+09 0.915755E+09 0.108302E+10
March 0.977011E+09 0.390546E+09 0.586465E+09 0.164397E+10 0.760549E+09
April 0.114924E+10 0.538949E+09 0.610290E+09 0.239023E+10 0.323427E+09
May 0.112450E+10 0.476988E+09 0.647507E+09 0.278036E+10 66654567.35
June 0.102213E+10 0.397023E+09 0.625107E+09 0.265414E+10 47727496.65
July 0.783756E+09 0.152441E+09 0.631315E+09 0.199987E+10 24297080.08
August 0.719797E+09 0.127930E+09 0.591867E+09 0.168271E+10 79364416.00
September 0.765722E+09 0.224794E+09 0.540928E+09 0.164804E+10 0.135415E+09
October 0.823565E+09 0.327942E+09 0.495623E+09 0.158788E+10 0.584364E+09
November 0.721017E+09 0.307293E+09 0.413724E+09 0.112584E+10 0.106841E+10
December 0.637545E+09 0.243110E+09 0.394434E+09 0.713648E+09 0.154383E+10
           
Annual Sum or Average 0.100637E+11 0.369421E+10 0.636945E+10 0.198904E+11 0.719201E+10
Minimum of Months 0.637545E+09 0.127930E+09 0.394434E+09 0.713648E+09 24297080.08
Maximum of Months 0.114924E+10 0.538949E+09 0.647507E+09 0.278036E+10 0.154383E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141472E+10 0.00 0.141472E+10 0.101373E+10 0.533599E+10
February 0.151526E+10 0.00 0.151526E+10 0.162202E+10 0.385470E+10
March 0.202153E+10 0.00 0.202153E+10 0.329284E+10 0.263921E+10
April 0.212276E+10 7199010.56 0.211556E+10 0.554645E+10 0.899094E+09
May 0.243027E+10 68197846.21 0.236207E+10 0.794716E+10 0.170085E+09
June 0.243456E+10 90176671.47 0.234438E+10 0.834247E+10 0.124402E+09
July 0.248107E+10 39289245.38 0.244178E+10 0.763280E+10 33603827.93
August 0.227769E+10 7098551.23 0.227060E+10 0.644378E+10 0.109829E+09
September 0.196402E+10 137909.51 0.196388E+10 0.486101E+10 0.372350E+09
October 0.175819E+10 0.00 0.175819E+10 0.366462E+10 0.208002E+10
November 0.144117E+10 0.00 0.144117E+10 0.197062E+10 0.377131E+10
December 0.138008E+10 0.00 0.138008E+10 0.109910E+10 0.525433E+10
           
Annual Sum or Average 0.232413E+11 0.212099E+09 0.230292E+11 0.534366E+11 0.246449E+11
Minimum of Months 0.138008E+10 0.00 0.138008E+10 0.101373E+10 33603827.93
Maximum of Months 0.248107E+10 90176671.47 0.244178E+10 0.834247E+10 0.533599E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.202038E+10 0.810954E+09 0.120943E+10 0.218998E+10 0.339937E+10
February 0.221698E+10 0.915271E+09 0.130170E+10 0.296846E+10 0.251584E+10
March 0.299424E+10 0.123592E+10 0.175832E+10 0.503458E+10 0.176050E+10
April 0.344746E+10 0.160738E+10 0.184008E+10 0.733482E+10 0.656200E+09
May 0.350635E+10 0.155453E+10 0.195183E+10 0.865499E+10 0.129815E+09
June 0.276165E+10 0.916315E+09 0.184534E+10 0.758781E+10 90102618.27
July 0.239847E+10 0.506493E+09 0.189198E+10 0.640969E+10 21473762.64
August 0.216112E+10 0.376086E+09 0.178503E+10 0.542212E+10 79607128.96
September 0.223443E+10 0.623127E+09 0.161130E+10 0.488767E+10 0.276886E+09
October 0.252568E+10 0.102021E+10 0.150547E+10 0.485861E+10 0.142289E+10
November 0.216714E+10 0.930235E+09 0.123691E+10 0.332260E+10 0.248243E+10
December 0.195264E+10 0.773649E+09 0.117900E+10 0.227773E+10 0.342513E+10
           
Annual Sum or Average 0.303865E+11 0.112702E+11 0.191164E+11 0.609491E+11 0.162602E+11
Minimum of Months 0.195264E+10 0.376086E+09 0.117900E+10 0.218998E+10 21473762.64
Maximum of Months 0.350635E+10 0.160738E+10 0.195183E+10 0.865499E+10 0.342513E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.643411E+10 0.390953E+10 0.252458E+10 0.916267E+10 0.551871E+10
February 0.552585E+10 0.306921E+10 0.245664E+10 0.856063E+10 0.411189E+10
March 0.523096E+10 0.231047E+10 0.292049E+10 0.954762E+10 0.288743E+10
April 0.355572E+10 0.100353E+10 0.255218E+10 0.875594E+10 0.103267E+10
May 0.264227E+10 0.195599E+09 0.244667E+10 0.849069E+10 0.171567E+09
June 0.233902E+10 39914814.84 0.229911E+10 0.815019E+10 0.123516E+09
July 0.252115E+10 34676399.57 0.248648E+10 0.775023E+10 29770997.50
August 0.267441E+10 0.142834E+09 0.253158E+10 0.727447E+10 0.115869E+09
September 0.346961E+10 0.900544E+09 0.256906E+10 0.786531E+10 0.449404E+09
October 0.616807E+10 0.344423E+10 0.272385E+10 0.119759E+11 0.237639E+10
November 0.745572E+10 0.492808E+10 0.252765E+10 0.125922E+11 0.415467E+10
December 0.687585E+10 0.430860E+10 0.256725E+10 0.101637E+11 0.555982E+10
           
Annual Sum or Average 0.548927E+11 0.242872E+11 0.306055E+11 0.110289E+12 0.265317E+11
Minimum of Months 0.233902E+10 34676399.57 0.229911E+10 0.727447E+10 29770997.50
Maximum of Months 0.745572E+10 0.492808E+10 0.292049E+10 0.125922E+11 0.555982E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.197662E+10 0.769225E+09 0.120739E+10 0.241104E+10 0.380608E+10
February 0.204158E+10 0.752376E+09 0.128920E+10 0.287952E+10 0.280194E+10
March 0.293106E+10 0.117165E+10 0.175941E+10 0.504401E+10 0.198532E+10
April 0.344774E+10 0.161686E+10 0.183088E+10 0.735220E+10 0.773156E+09
May 0.337351E+10 0.143098E+10 0.194254E+10 0.842009E+10 0.172564E+09
June 0.306642E+10 0.119108E+10 0.187534E+10 0.811170E+10 0.113583E+09
July 0.235129E+10 0.457326E+09 0.189396E+10 0.623678E+10 34576970.35
August 0.215941E+10 0.383793E+09 0.177562E+10 0.537414E+10 0.102639E+09
September 0.229718E+10 0.674388E+09 0.162280E+10 0.500634E+10 0.339308E+09
October 0.247072E+10 0.983835E+09 0.148688E+10 0.484913E+10 0.157598E+10
November 0.216307E+10 0.921886E+09 0.124118E+10 0.352171E+10 0.276292E+10
December 0.191265E+10 0.729337E+09 0.118331E+10 0.239679E+10 0.375426E+10
           
Annual Sum or Average 0.301912E+11 0.110827E+11 0.191085E+11 0.616034E+11 0.182223E+11
Minimum of Months 0.191265E+10 0.383793E+09 0.118331E+10 0.239679E+10 34576970.35
Maximum of Months 0.344774E+10 0.161686E+10 0.194254E+10 0.842009E+10 0.380608E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141472E+10 0.00 0.141472E+10 0.114050E+10 0.484563E+10
February 0.151526E+10 0.00 0.151526E+10 0.170411E+10 0.358946E+10
March 0.202153E+10 0.00 0.202153E+10 0.328411E+10 0.255095E+10
April 0.212276E+10 7199010.56 0.211556E+10 0.545894E+10 0.914640E+09
May 0.243027E+10 68197846.21 0.236207E+10 0.781649E+10 0.191579E+09
June 0.243456E+10 90176671.47 0.234438E+10 0.820686E+10 0.135431E+09
July 0.248107E+10 39289245.38 0.244178E+10 0.748037E+10 35874315.92
August 0.227769E+10 7098551.23 0.227060E+10 0.632233E+10 0.118990E+09
September 0.196402E+10 137909.51 0.196388E+10 0.478156E+10 0.399279E+09
October 0.175819E+10 0.00 0.175819E+10 0.363269E+10 0.203908E+10
November 0.144117E+10 0.00 0.144117E+10 0.203853E+10 0.354069E+10
December 0.138008E+10 0.00 0.138008E+10 0.125060E+10 0.477894E+10
           
Annual Sum or Average 0.232413E+11 0.212099E+09 0.230292E+11 0.531171E+11 0.231405E+11
Minimum of Months 0.138008E+10 0.00 0.138008E+10 0.114050E+10 35874315.92
Maximum of Months 0.248107E+10 90176671.47 0.244178E+10 0.820686E+10 0.484563E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.202038E+10 0.810954E+09 0.120943E+10 0.234871E+10 0.309072E+10
February 0.221698E+10 0.915271E+09 0.130170E+10 0.304796E+10 0.236467E+10
March 0.299424E+10 0.123592E+10 0.175832E+10 0.504556E+10 0.171382E+10
April 0.344746E+10 0.160738E+10 0.184008E+10 0.729695E+10 0.663934E+09
May 0.350635E+10 0.155453E+10 0.195183E+10 0.858947E+10 0.142378E+09
June 0.276165E+10 0.916315E+09 0.184534E+10 0.752098E+10 96621058.28
July 0.239847E+10 0.506493E+09 0.189198E+10 0.633285E+10 22429952.30
August 0.216112E+10 0.376086E+09 0.178503E+10 0.536674E+10 85360891.59
September 0.223443E+10 0.623127E+09 0.161130E+10 0.485625E+10 0.292590E+09
October 0.252568E+10 0.102021E+10 0.150547E+10 0.485785E+10 0.139866E+10
November 0.216714E+10 0.930235E+09 0.123691E+10 0.338586E+10 0.235734E+10
December 0.195264E+10 0.773649E+09 0.117900E+10 0.243141E+10 0.314131E+10
           
Annual Sum or Average 0.303865E+11 0.112702E+11 0.191164E+11 0.610806E+11 0.153698E+11
Minimum of Months 0.195264E+10 0.376086E+09 0.117900E+10 0.234871E+10 22429952.30
Maximum of Months 0.350635E+10 0.160738E+10 0.195183E+10 0.858947E+10 0.314131E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.643411E+10 0.390953E+10 0.252458E+10 0.931985E+10 0.506592E+10
February 0.552585E+10 0.306921E+10 0.245664E+10 0.861956E+10 0.388045E+10
March 0.523096E+10 0.231047E+10 0.292049E+10 0.951814E+10 0.280770E+10
April 0.355572E+10 0.100353E+10 0.255218E+10 0.866753E+10 0.104598E+10
May 0.264227E+10 0.195599E+09 0.244667E+10 0.836040E+10 0.191986E+09
June 0.233902E+10 39914814.84 0.229911E+10 0.801369E+10 0.134974E+09
July 0.252115E+10 34676399.57 0.248648E+10 0.759731E+10 31696750.64
August 0.267441E+10 0.142834E+09 0.253158E+10 0.715498E+10 0.125637E+09
September 0.346961E+10 0.900544E+09 0.256906E+10 0.778462E+10 0.476048E+09
October 0.616807E+10 0.344423E+10 0.272385E+10 0.119353E+11 0.233601E+10
November 0.745572E+10 0.492808E+10 0.252765E+10 0.126192E+11 0.396981E+10
December 0.687585E+10 0.430860E+10 0.256725E+10 0.103151E+11 0.516284E+10
           
Annual Sum or Average 0.548927E+11 0.242872E+11 0.306055E+11 0.109906E+12 0.252291E+11
Minimum of Months 0.233902E+10 34676399.57 0.229911E+10 0.715498E+10 31696750.64
Maximum of Months 0.745572E+10 0.492808E+10 0.292049E+10 0.126192E+11 0.516284E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.197662E+10 0.769225E+09 0.120739E+10 0.247715E+10 0.351522E+10
February 0.204158E+10 0.752376E+09 0.128920E+10 0.290870E+10 0.264765E+10
March 0.293106E+10 0.117165E+10 0.175941E+10 0.502045E+10 0.193023E+10
April 0.344774E+10 0.161686E+10 0.183088E+10 0.729388E+10 0.778342E+09
May 0.337351E+10 0.143098E+10 0.194254E+10 0.834281E+10 0.184272E+09
June 0.306642E+10 0.119108E+10 0.187534E+10 0.802910E+10 0.119694E+09
July 0.235129E+10 0.457326E+09 0.189396E+10 0.614734E+10 36839387.80
August 0.215941E+10 0.383793E+09 0.177562E+10 0.530361E+10 0.110951E+09
September 0.229718E+10 0.674388E+09 0.162280E+10 0.495715E+10 0.354725E+09
October 0.247072E+10 0.983835E+09 0.148688E+10 0.482281E+10 0.154781E+10
November 0.216307E+10 0.921886E+09 0.124118E+10 0.354095E+10 0.263140E+10
December 0.191265E+10 0.729337E+09 0.118331E+10 0.247182E+10 0.348558E+10
           
Annual Sum or Average 0.301912E+11 0.110827E+11 0.191085E+11 0.613158E+11 0.173427E+11
Minimum of Months 0.191265E+10 0.383793E+09 0.118331E+10 0.247182E+10 36839387.80
Maximum of Months 0.344774E+10 0.161686E+10 0.194254E+10 0.834281E+10 0.351522E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 282.34 2320.65 528.20 0.00 528.20 0.00 0.00
February 596.88 1793.23 626.35 0.00 626.35 0.00 0.00
March 1194.28 1050.85 754.76 0.00 754.76 0.00 0.00
April 2088.56 369.21 818.97 2.78 816.19 0.00 0.00
May 2945.89 61.43 907.36 25.46 881.90 0.00 0.00
June 3195.39 44.80 939.26 34.79 904.47 0.00 0.00
July 2818.16 10.60 926.33 14.67 911.66 0.00 0.00
August 2351.14 43.75 850.40 2.65 847.75 0.00 0.00
September 1862.48 142.32 757.73 0.05 757.67 0.00 0.00
October 1338.39 805.67 656.44 0.00 656.44 0.00 0.00
November 698.83 1607.74 556.01 0.00 556.01 0.00 0.00
December 304.73 2298.35 515.27 0.00 515.27 0.00 0.00
               
Annual Sum or Average 1644.80 875.24 736.98 6.73 730.26 0.00 0.00
Minimum of Months 282.34 10.60 515.27 0.00 515.27 0.00 0.00
Maximum of Months 3195.39 2320.65 939.26 34.79 911.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 771.13 1410.12 754.33 302.78 451.55 0.00 0.00
February 1216.36 1102.70 916.41 378.34 538.07 0.00 0.00
March 1897.33 655.54 1117.93 461.44 656.49 0.00 0.00
April 2854.92 236.07 1330.04 620.13 709.91 0.00 0.00
May 3259.79 42.07 1309.13 580.40 728.73 0.00 0.00
June 2955.81 28.24 1065.46 353.52 711.94 0.00 0.00
July 2419.40 4.80 895.49 189.10 706.39 0.00 0.00
August 2047.48 20.77 806.87 140.41 666.46 0.00 0.00
September 1907.21 93.15 862.05 240.41 621.65 0.00 0.00
October 1829.14 520.07 942.98 380.90 562.08 0.00 0.00
November 1277.55 993.47 836.09 358.89 477.20 0.00 0.00
December 812.02 1390.04 729.04 288.85 440.19 0.00 0.00
               
Annual Sum or Average 1939.86 539.04 963.55 357.38 606.18 0.00 0.00
Minimum of Months 771.13 4.80 729.04 140.41 440.19 0.00 0.00
Maximum of Months 3259.79 1410.12 1330.04 620.13 728.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3423.83 2143.05 2402.23 1459.66 942.57 0.00 0.00
February 3554.91 1750.38 2284.17 1268.69 1015.48 0.00 0.00
March 3579.76 1089.90 1953.02 862.63 1090.39 0.00 0.00
April 3364.75 404.13 1371.81 387.17 984.64 0.00 0.00
May 3152.00 62.98 986.51 73.03 913.48 0.00 0.00
June 3119.83 45.04 902.40 15.40 887.01 0.00 0.00
July 2861.62 9.70 941.29 12.95 928.35 0.00 0.00
August 2674.84 44.64 998.51 53.33 945.19 0.00 0.00
September 3044.20 163.81 1338.59 347.43 991.15 0.00 0.00
October 4494.43 871.95 2302.90 1285.93 1016.97 0.00 0.00
November 4880.84 1626.52 2876.45 1901.27 975.18 0.00 0.00
December 3790.20 2161.47 2567.16 1608.65 958.51 0.00 0.00
               
Annual Sum or Average 3493.43 860.52 1740.64 770.15 970.50 0.00 0.00
Minimum of Months 2674.84 9.70 902.40 12.95 887.01 0.00 0.00
Maximum of Months 4880.84 2161.47 2876.45 1901.27 1090.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 837.73 1652.06 737.99 287.20 450.79 0.00 0.00
February 1135.62 1343.05 843.91 311.00 532.91 0.00 0.00
March 1841.39 851.88 1094.34 437.44 656.89 0.00 0.00
April 2766.50 374.34 1330.15 623.79 706.36 0.00 0.00
May 3114.24 74.66 1259.53 534.27 725.26 0.00 0.00
June 3071.95 55.24 1183.04 459.52 723.51 0.00 0.00
July 2240.02 27.21 877.87 170.75 707.13 0.00 0.00
August 1884.78 88.89 806.23 143.29 662.94 0.00 0.00
September 1907.47 156.73 886.26 260.18 626.08 0.00 0.00
October 1778.56 654.54 922.46 367.32 555.14 0.00 0.00
November 1303.08 1236.60 834.52 355.67 478.85 0.00 0.00
December 799.35 1729.23 714.10 272.30 441.80 0.00 0.00
               
Annual Sum or Average 1892.18 684.18 957.36 351.43 605.93 0.00 0.00
Minimum of Months 799.35 27.21 714.10 143.29 441.80 0.00 0.00
Maximum of Months 3114.24 1729.23 1330.15 623.79 725.26 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 378.48 1992.23 528.19 0.00 528.19 0.00 0.00
February 670.48 1593.38 626.35 0.00 626.35 0.00 0.00
March 1229.40 985.37 754.75 0.00 754.75 0.00 0.00
April 2139.83 346.87 818.97 2.78 816.19 0.00 0.00
May 2967.13 63.50 907.36 25.46 881.90 0.00 0.00
June 3218.55 47.99 939.26 34.79 904.47 0.00 0.00
July 2849.76 12.55 926.33 14.67 911.66 0.00 0.00
August 2405.83 41.01 850.39 2.65 847.74 0.00 0.00
September 1875.39 143.65 757.72 0.05 757.67 0.00 0.00
October 1368.21 776.59 656.43 0.00 656.43 0.00 0.00
November 760.27 1454.98 556.01 0.00 556.01 0.00 0.00
December 410.36 1961.74 515.26 0.00 515.26 0.00 0.00
               
Annual Sum or Average 1694.46 781.49 736.98 6.73 730.25 0.00 0.00
Minimum of Months 378.48 12.55 515.26 0.00 515.26 0.00 0.00
Maximum of Months 3218.55 1992.23 939.26 34.79 911.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 817.64 1269.18 754.32 302.78 451.55 0.00 0.00
February 1227.04 1039.95 916.41 378.34 538.07 0.00 0.00
March 1879.70 657.30 1117.92 461.44 656.48 0.00 0.00
April 2829.79 253.16 1330.04 620.13 709.91 0.00 0.00
May 3231.40 48.47 1309.12 580.39 728.73 0.00 0.00
June 2927.40 34.76 1065.45 353.52 711.94 0.00 0.00
July 2393.10 8.02 895.49 189.10 706.38 0.00 0.00
August 2024.39 29.72 806.87 140.41 666.46 0.00 0.00
September 1885.68 106.82 862.05 240.40 621.64 0.00 0.00
October 1814.00 531.24 942.98 380.90 562.08 0.00 0.00
November 1281.87 957.73 836.09 358.89 477.20 0.00 0.00
December 850.41 1278.80 729.03 288.85 440.19 0.00 0.00
               
Annual Sum or Average 1932.68 515.61 963.55 357.37 606.18 0.00 0.00
Minimum of Months 817.64 8.02 729.03 140.41 440.19 0.00 0.00
Maximum of Months 3231.40 1278.80 1330.04 620.13 728.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3420.95 2060.45 2402.22 1459.65 942.57 0.00 0.00
February 3538.62 1699.69 2284.16 1268.69 1015.47 0.00 0.00
March 3564.67 1078.04 1953.02 862.63 1090.39 0.00 0.00
April 3378.06 398.41 1371.80 387.17 984.64 0.00 0.00
May 3170.06 64.06 986.51 73.03 913.48 0.00 0.00
June 3144.36 47.65 902.40 15.40 887.00 0.00 0.00
July 2893.61 11.12 941.29 12.95 928.34 0.00 0.00
August 2715.97 43.26 998.51 53.33 945.18 0.00 0.00
September 3034.46 173.38 1338.58 347.43 991.15 0.00 0.00
October 4471.27 887.24 2302.89 1285.93 1016.97 0.00 0.00
November 4858.09 1602.88 2876.44 1901.26 975.17 0.00 0.00
December 3794.69 2075.80 2567.15 1608.65 958.50 0.00 0.00
               
Annual Sum or Average 3497.26 841.31 1740.64 770.14 970.49 0.00 0.00
Minimum of Months 2715.97 11.12 902.40 12.95 887.00 0.00 0.00
Maximum of Months 4858.09 2075.80 2876.44 1901.26 1090.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 900.18 1421.03 737.99 287.20 450.79 0.00 0.00
February 1190.28 1158.21 843.91 311.00 532.90 0.00 0.00
March 1883.22 741.23 1094.33 437.44 656.89 0.00 0.00
April 2836.50 298.29 1330.15 623.79 706.36 0.00 0.00
May 3143.70 64.43 1259.53 534.27 725.26 0.00 0.00
June 3129.51 43.82 1183.03 459.52 723.51 0.00 0.00
July 2328.55 12.91 877.87 170.75 707.12 0.00 0.00
August 2006.47 38.32 806.23 143.29 662.94 0.00 0.00
September 1931.46 130.91 886.26 260.18 626.08 0.00 0.00
October 1810.46 588.40 922.46 367.32 555.14 0.00 0.00
November 1358.68 1065.94 834.52 355.67 478.85 0.00 0.00
December 894.86 1401.68 714.10 272.30 441.80 0.00 0.00
               
Annual Sum or Average 1953.43 577.83 957.36 351.43 605.93 0.00 0.00
Minimum of Months 894.86 12.91 714.10 143.29 441.80 0.00 0.00
Maximum of Months 3143.70 1421.03 1330.15 623.79 725.26 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 425.81 1809.15 528.19 0.00 528.19 0.00 0.00
February 704.41 1483.74 626.35 0.00 626.35 0.00 0.00
March 1226.15 952.42 754.75 0.00 754.75 0.00 0.00
April 2106.07 352.87 818.97 2.78 816.19 0.00 0.00
May 2918.34 71.53 907.36 25.46 881.90 0.00 0.00
June 3166.23 52.25 939.26 34.79 904.47 0.00 0.00
July 2792.85 13.39 926.33 14.67 911.66 0.00 0.00
August 2360.49 44.43 850.39 2.65 847.74 0.00 0.00
September 1844.74 154.04 757.72 0.05 757.67 0.00 0.00
October 1356.29 761.31 656.43 0.00 656.43 0.00 0.00
November 786.47 1366.01 556.01 0.00 556.01 0.00 0.00
December 466.92 1784.25 515.26 0.00 515.26 0.00 0.00
               
Annual Sum or Average 1684.33 733.78 736.98 6.73 730.25 0.00 0.00
Minimum of Months 425.81 13.39 515.26 0.00 515.26 0.00 0.00
Maximum of Months 3166.23 1809.15 939.26 34.79 911.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 876.91 1153.94 754.32 302.78 451.55 0.00 0.00
February 1259.90 977.46 916.41 378.34 538.07 0.00 0.00
March 1883.80 639.87 1117.92 461.44 656.48 0.00 0.00
April 2815.18 256.15 1330.04 620.13 709.91 0.00 0.00
May 3206.94 53.16 1309.12 580.39 728.73 0.00 0.00
June 2901.61 37.28 1065.45 353.52 711.94 0.00 0.00
July 2364.41 8.37 895.49 189.10 706.38 0.00 0.00
August 2003.71 31.87 806.87 140.41 666.46 0.00 0.00
September 1873.55 112.88 862.05 240.40 621.64 0.00 0.00
October 1813.71 522.20 942.98 380.90 562.08 0.00 0.00
November 1306.27 909.47 836.09 358.89 477.20 0.00 0.00
December 907.79 1172.83 729.03 288.85 440.19 0.00 0.00
               
Annual Sum or Average 1936.85 487.37 963.55 357.37 606.18 0.00 0.00
Minimum of Months 876.91 8.37 729.03 140.41 440.19 0.00 0.00
Maximum of Months 3206.94 1172.83 1330.04 620.13 728.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3479.63 1891.40 2402.22 1459.65 942.57 0.00 0.00
February 3562.98 1604.02 2284.16 1268.69 1015.47 0.00 0.00
March 3553.67 1048.28 1953.02 862.63 1090.39 0.00 0.00
April 3343.95 403.54 1371.80 387.17 984.64 0.00 0.00
May 3121.41 71.68 986.51 73.03 913.48 0.00 0.00
June 3091.70 52.07 902.40 15.40 887.00 0.00 0.00
July 2836.51 11.83 941.29 12.95 928.34 0.00 0.00
August 2671.37 46.91 998.51 53.33 945.18 0.00 0.00
September 3003.33 183.66 1338.58 347.43 991.15 0.00 0.00
October 4456.15 872.17 2302.89 1285.93 1016.97 0.00 0.00
November 4868.53 1531.56 2876.44 1901.26 975.17 0.00 0.00
December 3851.21 1927.58 2567.15 1608.65 958.50 0.00 0.00
               
Annual Sum or Average 3485.09 800.01 1740.64 770.14 970.49 0.00 0.00
Minimum of Months 2671.37 11.83 902.40 12.95 887.00 0.00 0.00
Maximum of Months 4868.53 1927.58 2876.44 1901.26 1090.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 924.86 1312.43 737.99 287.20 450.79 0.00 0.00
February 1202.34 1094.43 843.91 311.00 532.90 0.00 0.00
March 1874.42 720.67 1094.33 437.44 656.89 0.00 0.00
April 2814.00 300.29 1330.15 623.79 706.36 0.00 0.00
May 3114.85 68.80 1259.53 534.27 725.26 0.00 0.00
June 3097.64 46.18 1183.03 459.52 723.51 0.00 0.00
July 2295.16 13.75 877.87 170.75 707.12 0.00 0.00
August 1980.14 41.42 806.23 143.29 662.94 0.00 0.00
September 1912.48 136.85 886.26 260.18 626.08 0.00 0.00
October 1800.63 577.89 922.46 367.32 555.14 0.00 0.00
November 1366.11 1015.20 834.52 355.67 478.85 0.00 0.00
December 922.87 1301.37 714.10 272.30 441.80 0.00 0.00
               
Annual Sum or Average 1944.31 549.93 957.36 351.43 605.93 0.00 0.00
Minimum of Months 922.87 13.75 714.10 143.29 441.80 0.00 0.00
Maximum of Months 3114.85 1312.43 1330.15 623.79 725.26 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.756222E+09 0.621563E+10 0.141472E+10 0.00 0.141472E+10 0.00 0.00
February 0.144397E+10 0.433819E+10 0.151527E+10 0.00 0.151527E+10 0.00 0.00
March 0.319875E+10 0.281460E+10 0.202154E+10 0.00 0.202154E+10 0.00 0.00
April 0.541354E+10 0.956998E+09 0.212277E+10 7199036.12 0.211557E+10 0.00 0.00
May 0.789026E+10 0.164534E+09 0.243028E+10 68198088.39 0.236208E+10 0.00 0.00
June 0.828244E+10 0.116111E+09 0.243457E+10 90176991.69 0.234439E+10 0.00 0.00
July 0.754816E+10 28380755.79 0.248108E+10 39289384.90 0.244179E+10 0.00 0.00
August 0.629729E+10 0.117174E+09 0.227770E+10 7098576.44 0.227060E+10 0.00 0.00
September 0.482754E+10 0.368889E+09 0.196403E+10 137910.00 0.196389E+10 0.00 0.00
October 0.358476E+10 0.215790E+10 0.175820E+10 0.00 0.175820E+10 0.00 0.00
November 0.181137E+10 0.416727E+10 0.144117E+10 0.00 0.144117E+10 0.00 0.00
December 0.816180E+09 0.615589E+10 0.138009E+10 0.00 0.138009E+10 0.00 0.00
               
Annual Sum or Average 0.518705E+11 0.276016E+11 0.232414E+11 0.212100E+09 0.230293E+11 0.00 0.00
Minimum of Months 0.756222E+09 28380755.79 0.138009E+10 0.00 0.138009E+10 0.00 0.00
Maximum of Months 0.828244E+10 0.621563E+10 0.248108E+10 90176991.69 0.244179E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.206539E+10 0.377687E+10 0.202039E+10 0.810957E+09 0.120943E+10 0.00 0.00
February 0.294262E+10 0.266765E+10 0.221699E+10 0.915275E+09 0.130171E+10 0.00 0.00
March 0.508180E+10 0.175581E+10 0.299425E+10 0.123592E+10 0.175833E+10 0.00 0.00
April 0.739996E+10 0.611898E+09 0.344747E+10 0.160739E+10 0.184008E+10 0.00 0.00
May 0.873101E+10 0.112689E+09 0.350637E+10 0.155453E+10 0.195183E+10 0.00 0.00
June 0.766145E+10 73192371.83 0.276167E+10 0.916318E+09 0.184535E+10 0.00 0.00
July 0.648012E+10 12849511.27 0.239848E+10 0.506495E+09 0.189198E+10 0.00 0.00
August 0.548396E+10 55639245.13 0.216113E+10 0.376087E+09 0.178504E+10 0.00 0.00
September 0.494348E+10 0.241454E+09 0.223444E+10 0.623130E+09 0.161131E+10 0.00 0.00
October 0.489918E+10 0.139296E+10 0.252569E+10 0.102021E+10 0.150548E+10 0.00 0.00
November 0.331141E+10 0.257507E+10 0.216715E+10 0.930239E+09 0.123691E+10 0.00 0.00
December 0.217492E+10 0.372308E+10 0.195265E+10 0.773652E+09 0.117900E+10 0.00 0.00
               
Annual Sum or Average 0.611753E+11 0.169992E+11 0.303867E+11 0.112702E+11 0.191165E+11 0.00 0.00
Minimum of Months 0.206539E+10 12849511.27 0.195265E+10 0.376087E+09 0.117900E+10 0.00 0.00
Maximum of Months 0.873101E+10 0.377687E+10 0.350637E+10 0.160739E+10 0.195183E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.917039E+10 0.573994E+10 0.643414E+10 0.390955E+10 0.252459E+10 0.00 0.00
February 0.860004E+10 0.423452E+10 0.552587E+10 0.306922E+10 0.245665E+10 0.00 0.00
March 0.958803E+10 0.291920E+10 0.523098E+10 0.231048E+10 0.292050E+10 0.00 0.00
April 0.872142E+10 0.104751E+10 0.355573E+10 0.100354E+10 0.255219E+10 0.00 0.00
May 0.844231E+10 0.168683E+09 0.264228E+10 0.195600E+09 0.244667E+10 0.00 0.00
June 0.808659E+10 0.116738E+09 0.233903E+10 39914956.58 0.229912E+10 0.00 0.00
July 0.766457E+10 25989697.63 0.252116E+10 34676522.71 0.248649E+10 0.00 0.00
August 0.716429E+10 0.119561E+09 0.267442E+10 0.142834E+09 0.253159E+10 0.00 0.00
September 0.789056E+10 0.424588E+09 0.346962E+10 0.900548E+09 0.256907E+10 0.00 0.00
October 0.120379E+11 0.233542E+10 0.616809E+10 0.344424E+10 0.272386E+10 0.00 0.00
November 0.126511E+11 0.421594E+10 0.745575E+10 0.492809E+10 0.252766E+10 0.00 0.00
December 0.101517E+11 0.578928E+10 0.687587E+10 0.430861E+10 0.256726E+10 0.00 0.00
               
Annual Sum or Average 0.110169E+12 0.271374E+11 0.548929E+11 0.242873E+11 0.306056E+11 0.00 0.00
Minimum of Months 0.716429E+10 25989697.63 0.233903E+10 34676522.71 0.229912E+10 0.00 0.00
Maximum of Months 0.126511E+11 0.578928E+10 0.745575E+10 0.492809E+10 0.292050E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.224377E+10 0.442488E+10 0.197663E+10 0.769228E+09 0.120740E+10 0.00 0.00
February 0.274730E+10 0.324910E+10 0.204159E+10 0.752379E+09 0.128921E+10 0.00 0.00
March 0.493197E+10 0.228167E+10 0.293107E+10 0.117165E+10 0.175942E+10 0.00 0.00
April 0.717078E+10 0.970292E+09 0.344776E+10 0.161687E+10 0.183089E+10 0.00 0.00
May 0.834119E+10 0.199966E+09 0.337353E+10 0.143098E+10 0.194255E+10 0.00 0.00
June 0.796250E+10 0.143184E+09 0.306643E+10 0.119108E+10 0.187535E+10 0.00 0.00
July 0.599968E+10 72892128.17 0.235130E+10 0.457328E+09 0.189397E+10 0.00 0.00
August 0.504820E+10 0.238096E+09 0.215942E+10 0.383794E+09 0.177562E+10 0.00 0.00
September 0.494417E+10 0.406250E+09 0.229719E+10 0.674391E+09 0.162280E+10 0.00 0.00
October 0.476369E+10 0.175311E+10 0.247073E+10 0.983839E+09 0.148689E+10 0.00 0.00
November 0.337757E+10 0.320527E+10 0.216308E+10 0.921890E+09 0.124119E+10 0.00 0.00
December 0.214097E+10 0.463156E+10 0.191266E+10 0.729340E+09 0.118332E+10 0.00 0.00
               
Annual Sum or Average 0.596718E+11 0.215763E+11 0.301914E+11 0.110828E+11 0.191086E+11 0.00 0.00
Minimum of Months 0.214097E+10 72892128.17 0.191266E+10 0.383794E+09 0.118332E+10 0.00 0.00
Maximum of Months 0.834119E+10 0.463156E+10 0.344776E+10 0.161687E+10 0.194255E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.101373E+10 0.533599E+10 0.141472E+10 0.00 0.141472E+10 0.00 0.00
February 0.162202E+10 0.385470E+10 0.151526E+10 0.00 0.151526E+10 0.00 0.00
March 0.329284E+10 0.263921E+10 0.202153E+10 0.00 0.202153E+10 0.00 0.00
April 0.554645E+10 0.899094E+09 0.212276E+10 7199010.56 0.211556E+10 0.00 0.00
May 0.794716E+10 0.170085E+09 0.243027E+10 68197846.21 0.236207E+10 0.00 0.00
June 0.834247E+10 0.124402E+09 0.243456E+10 90176671.47 0.234438E+10 0.00 0.00
July 0.763280E+10 33603827.93 0.248107E+10 39289245.38 0.244178E+10 0.00 0.00
August 0.644378E+10 0.109829E+09 0.227769E+10 7098551.23 0.227060E+10 0.00 0.00
September 0.486101E+10 0.372350E+09 0.196402E+10 137909.51 0.196388E+10 0.00 0.00
October 0.366462E+10 0.208002E+10 0.175819E+10 0.00 0.175819E+10 0.00 0.00
November 0.197062E+10 0.377131E+10 0.144117E+10 0.00 0.144117E+10 0.00 0.00
December 0.109910E+10 0.525433E+10 0.138008E+10 0.00 0.138008E+10 0.00 0.00
               
Annual Sum or Average 0.534366E+11 0.246449E+11 0.232413E+11 0.212099E+09 0.230292E+11 0.00 0.00
Minimum of Months 0.101373E+10 33603827.93 0.138008E+10 0.00 0.138008E+10 0.00 0.00
Maximum of Months 0.834247E+10 0.533599E+10 0.248107E+10 90176671.47 0.244178E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.218998E+10 0.339937E+10 0.202038E+10 0.810954E+09 0.120943E+10 0.00 0.00
February 0.296846E+10 0.251584E+10 0.221698E+10 0.915271E+09 0.130170E+10 0.00 0.00
March 0.503458E+10 0.176050E+10 0.299424E+10 0.123592E+10 0.175832E+10 0.00 0.00
April 0.733482E+10 0.656200E+09 0.344746E+10 0.160738E+10 0.184008E+10 0.00 0.00
May 0.865499E+10 0.129815E+09 0.350635E+10 0.155453E+10 0.195183E+10 0.00 0.00
June 0.758781E+10 90102618.27 0.276165E+10 0.916315E+09 0.184534E+10 0.00 0.00
July 0.640969E+10 21473762.64 0.239847E+10 0.506493E+09 0.189198E+10 0.00 0.00
August 0.542212E+10 79607128.96 0.216112E+10 0.376086E+09 0.178503E+10 0.00 0.00
September 0.488767E+10 0.276886E+09 0.223443E+10 0.623127E+09 0.161130E+10 0.00 0.00
October 0.485861E+10 0.142289E+10 0.252568E+10 0.102021E+10 0.150547E+10 0.00 0.00
November 0.332260E+10 0.248243E+10 0.216714E+10 0.930235E+09 0.123691E+10 0.00 0.00
December 0.227773E+10 0.342513E+10 0.195264E+10 0.773649E+09 0.117900E+10 0.00 0.00
               
Annual Sum or Average 0.609491E+11 0.162602E+11 0.303865E+11 0.112702E+11 0.191164E+11 0.00 0.00
Minimum of Months 0.218998E+10 21473762.64 0.195264E+10 0.376086E+09 0.117900E+10 0.00 0.00
Maximum of Months 0.865499E+10 0.342513E+10 0.350635E+10 0.160738E+10 0.195183E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.916267E+10 0.551871E+10 0.643411E+10 0.390953E+10 0.252458E+10 0.00 0.00
February 0.856063E+10 0.411189E+10 0.552585E+10 0.306921E+10 0.245664E+10 0.00 0.00
March 0.954762E+10 0.288743E+10 0.523096E+10 0.231047E+10 0.292049E+10 0.00 0.00
April 0.875594E+10 0.103267E+10 0.355572E+10 0.100353E+10 0.255218E+10 0.00 0.00
May 0.849069E+10 0.171567E+09 0.264227E+10 0.195599E+09 0.244667E+10 0.00 0.00
June 0.815019E+10 0.123516E+09 0.233902E+10 39914814.84 0.229911E+10 0.00 0.00
July 0.775023E+10 29770997.50 0.252115E+10 34676399.57 0.248648E+10 0.00 0.00
August 0.727447E+10 0.115869E+09 0.267441E+10 0.142834E+09 0.253158E+10 0.00 0.00
September 0.786531E+10 0.449404E+09 0.346961E+10 0.900544E+09 0.256906E+10 0.00 0.00
October 0.119759E+11 0.237639E+10 0.616807E+10 0.344423E+10 0.272385E+10 0.00 0.00
November 0.125922E+11 0.415467E+10 0.745572E+10 0.492808E+10 0.252765E+10 0.00 0.00
December 0.101637E+11 0.555982E+10 0.687585E+10 0.430860E+10 0.256725E+10 0.00 0.00
               
Annual Sum or Average 0.110289E+12 0.265317E+11 0.548927E+11 0.242872E+11 0.306055E+11 0.00 0.00
Minimum of Months 0.727447E+10 29770997.50 0.233902E+10 34676399.57 0.229911E+10 0.00 0.00
Maximum of Months 0.125922E+11 0.555982E+10 0.745572E+10 0.492808E+10 0.292049E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.241104E+10 0.380608E+10 0.197662E+10 0.769225E+09 0.120739E+10 0.00 0.00
February 0.287952E+10 0.280194E+10 0.204158E+10 0.752376E+09 0.128920E+10 0.00 0.00
March 0.504401E+10 0.198532E+10 0.293106E+10 0.117165E+10 0.175941E+10 0.00 0.00
April 0.735220E+10 0.773156E+09 0.344774E+10 0.161686E+10 0.183088E+10 0.00 0.00
May 0.842009E+10 0.172564E+09 0.337351E+10 0.143098E+10 0.194254E+10 0.00 0.00
June 0.811170E+10 0.113583E+09 0.306642E+10 0.119108E+10 0.187534E+10 0.00 0.00
July 0.623678E+10 34576970.35 0.235129E+10 0.457326E+09 0.189396E+10 0.00 0.00
August 0.537414E+10 0.102639E+09 0.215941E+10 0.383793E+09 0.177562E+10 0.00 0.00
September 0.500634E+10 0.339308E+09 0.229718E+10 0.674388E+09 0.162280E+10 0.00 0.00
October 0.484913E+10 0.157598E+10 0.247072E+10 0.983835E+09 0.148688E+10 0.00 0.00
November 0.352171E+10 0.276292E+10 0.216307E+10 0.921886E+09 0.124118E+10 0.00 0.00
December 0.239679E+10 0.375426E+10 0.191265E+10 0.729337E+09 0.118331E+10 0.00 0.00
               
Annual Sum or Average 0.616034E+11 0.182223E+11 0.301912E+11 0.110827E+11 0.191085E+11 0.00 0.00
Minimum of Months 0.239679E+10 34576970.35 0.191265E+10 0.383793E+09 0.118331E+10 0.00 0.00
Maximum of Months 0.842009E+10 0.380608E+10 0.344774E+10 0.161686E+10 0.194254E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.114050E+10 0.484563E+10 0.141472E+10 0.00 0.141472E+10 0.00 0.00
February 0.170411E+10 0.358946E+10 0.151526E+10 0.00 0.151526E+10 0.00 0.00
March 0.328411E+10 0.255095E+10 0.202153E+10 0.00 0.202153E+10 0.00 0.00
April 0.545894E+10 0.914640E+09 0.212276E+10 7199010.56 0.211556E+10 0.00 0.00
May 0.781649E+10 0.191579E+09 0.243027E+10 68197846.21 0.236207E+10 0.00 0.00
June 0.820686E+10 0.135431E+09 0.243456E+10 90176671.47 0.234438E+10 0.00 0.00
July 0.748037E+10 35874315.92 0.248107E+10 39289245.38 0.244178E+10 0.00 0.00
August 0.632233E+10 0.118990E+09 0.227769E+10 7098551.23 0.227060E+10 0.00 0.00
September 0.478156E+10 0.399279E+09 0.196402E+10 137909.51 0.196388E+10 0.00 0.00
October 0.363269E+10 0.203908E+10 0.175819E+10 0.00 0.175819E+10 0.00 0.00
November 0.203853E+10 0.354069E+10 0.144117E+10 0.00 0.144117E+10 0.00 0.00
December 0.125060E+10 0.477894E+10 0.138008E+10 0.00 0.138008E+10 0.00 0.00
               
Annual Sum or Average 0.531171E+11 0.231405E+11 0.232413E+11 0.212099E+09 0.230292E+11 0.00 0.00
Minimum of Months 0.114050E+10 35874315.92 0.138008E+10 0.00 0.138008E+10 0.00 0.00
Maximum of Months 0.820686E+10 0.484563E+10 0.248107E+10 90176671.47 0.244178E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.234871E+10 0.309072E+10 0.202038E+10 0.810954E+09 0.120943E+10 0.00 0.00
February 0.304796E+10 0.236467E+10 0.221698E+10 0.915271E+09 0.130170E+10 0.00 0.00
March 0.504556E+10 0.171382E+10 0.299424E+10 0.123592E+10 0.175832E+10 0.00 0.00
April 0.729695E+10 0.663934E+09 0.344746E+10 0.160738E+10 0.184008E+10 0.00 0.00
May 0.858947E+10 0.142378E+09 0.350635E+10 0.155453E+10 0.195183E+10 0.00 0.00
June 0.752098E+10 96621058.28 0.276165E+10 0.916315E+09 0.184534E+10 0.00 0.00
July 0.633285E+10 22429952.30 0.239847E+10 0.506493E+09 0.189198E+10 0.00 0.00
August 0.536674E+10 85360891.59 0.216112E+10 0.376086E+09 0.178503E+10 0.00 0.00
September 0.485625E+10 0.292590E+09 0.223443E+10 0.623127E+09 0.161130E+10 0.00 0.00
October 0.485785E+10 0.139866E+10 0.252568E+10 0.102021E+10 0.150547E+10 0.00 0.00
November 0.338586E+10 0.235734E+10 0.216714E+10 0.930235E+09 0.123691E+10 0.00 0.00
December 0.243141E+10 0.314131E+10 0.195264E+10 0.773649E+09 0.117900E+10 0.00 0.00
               
Annual Sum or Average 0.610806E+11 0.153698E+11 0.303865E+11 0.112702E+11 0.191164E+11 0.00 0.00
Minimum of Months 0.234871E+10 22429952.30 0.195264E+10 0.376086E+09 0.117900E+10 0.00 0.00
Maximum of Months 0.858947E+10 0.314131E+10 0.350635E+10 0.160738E+10 0.195183E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.931985E+10 0.506592E+10 0.643411E+10 0.390953E+10 0.252458E+10 0.00 0.00
February 0.861956E+10 0.388045E+10 0.552585E+10 0.306921E+10 0.245664E+10 0.00 0.00
March 0.951814E+10 0.280770E+10 0.523096E+10 0.231047E+10 0.292049E+10 0.00 0.00
April 0.866753E+10 0.104598E+10 0.355572E+10 0.100353E+10 0.255218E+10 0.00 0.00
May 0.836040E+10 0.191986E+09 0.264227E+10 0.195599E+09 0.244667E+10 0.00 0.00
June 0.801369E+10 0.134974E+09 0.233902E+10 39914814.84 0.229911E+10 0.00 0.00
July 0.759731E+10 31696750.64 0.252115E+10 34676399.57 0.248648E+10 0.00 0.00
August 0.715498E+10 0.125637E+09 0.267441E+10 0.142834E+09 0.253158E+10 0.00 0.00
September 0.778462E+10 0.476048E+09 0.346961E+10 0.900544E+09 0.256906E+10 0.00 0.00
October 0.119353E+11 0.233601E+10 0.616807E+10 0.344423E+10 0.272385E+10 0.00 0.00
November 0.126192E+11 0.396981E+10 0.745572E+10 0.492808E+10 0.252765E+10 0.00 0.00
December 0.103151E+11 0.516284E+10 0.687585E+10 0.430860E+10 0.256725E+10 0.00 0.00
               
Annual Sum or Average 0.109906E+12 0.252291E+11 0.548927E+11 0.242872E+11 0.306055E+11 0.00 0.00
Minimum of Months 0.715498E+10 31696750.64 0.233902E+10 34676399.57 0.229911E+10 0.00 0.00
Maximum of Months 0.126192E+11 0.516284E+10 0.745572E+10 0.492808E+10 0.292049E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.247715E+10 0.351522E+10 0.197662E+10 0.769225E+09 0.120739E+10 0.00 0.00
February 0.290870E+10 0.264765E+10 0.204158E+10 0.752376E+09 0.128920E+10 0.00 0.00
March 0.502045E+10 0.193023E+10 0.293106E+10 0.117165E+10 0.175941E+10 0.00 0.00
April 0.729388E+10 0.778342E+09 0.344774E+10 0.161686E+10 0.183088E+10 0.00 0.00
May 0.834281E+10 0.184272E+09 0.337351E+10 0.143098E+10 0.194254E+10 0.00 0.00
June 0.802910E+10 0.119694E+09 0.306642E+10 0.119108E+10 0.187534E+10 0.00 0.00
July 0.614734E+10 36839387.80 0.235129E+10 0.457326E+09 0.189396E+10 0.00 0.00
August 0.530361E+10 0.110951E+09 0.215941E+10 0.383793E+09 0.177562E+10 0.00 0.00
September 0.495715E+10 0.354725E+09 0.229718E+10 0.674388E+09 0.162280E+10 0.00 0.00
October 0.482281E+10 0.154781E+10 0.247072E+10 0.983835E+09 0.148688E+10 0.00 0.00
November 0.354095E+10 0.263140E+10 0.216307E+10 0.921886E+09 0.124118E+10 0.00 0.00
December 0.247182E+10 0.348558E+10 0.191265E+10 0.729337E+09 0.118331E+10 0.00 0.00
               
Annual Sum or Average 0.613158E+11 0.173427E+11 0.301912E+11 0.110827E+11 0.191085E+11 0.00 0.00
Minimum of Months 0.247182E+10 36839387.80 0.191265E+10 0.383793E+09 0.118331E+10 0.00 0.00
Maximum of Months 0.834281E+10 0.351522E+10 0.344774E+10 0.161686E+10 0.194254E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.39 10.38 7.87 1.20 0.38 63.33 149.51 0.00
February 16.97 12.78 9.69 1.81 4.63 75.94 163.32 0.01
March 22.37 15.60 11.23 1.86 10.07 92.70 193.23 0.00
April 29.13 18.33 11.93 1.64 16.17 89.20 259.84 0.01
May 32.98 21.97 16.72 2.17 21.14 97.31 248.85 0.02
June 33.59 24.39 20.62 1.55 23.45 107.22 203.36 0.06
July 31.67 26.29 24.51 2.27 24.88 132.35 83.14 0.02
August 30.03 26.31 25.11 1.75 23.81 127.44 60.46 0.00
September 28.75 24.70 23.21 1.33 20.22 105.62 105.60 0.08
October 25.09 18.74 15.36 0.77 12.83 75.09 190.08 0.00
November 19.63 14.46 10.99 0.66 5.78 58.54 201.10 0.00
December 14.52 10.88 7.89 0.97 0.94 60.91 153.60 0.01
                 
Annual Sum or Average 24.88 18.77 15.46 1.50 13.74 90.59 167.44 0.02
Minimum of Months 13.39 10.38 7.87 0.66 0.38 58.54 60.46 0.00
Maximum of Months 33.59 26.31 25.11 2.27 24.88 132.35 259.84 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.60 12-JAN-14:00 14.20 7.40 3.80 8.15 163.00 476.00
February 27.10 22-FEB-14:00 16.20 9.10 1.50 15.39 225.00 451.00
March 35.60 28-MAR-14:00 18.50 7.70 0.00 19.52 182.00 699.00
April 40.30 15-APR-14:00 20.67 10.00 6.70 28.43 201.00 649.50
May 44.50 03-MAY-14:00 20.64 5.30 2.80 28.91 150.00 809.00
June 44.60 07-JUN-15:00 21.53 9.10 3.10 28.43 167.00 640.50
July 40.40 02-JUL-15:00 26.36 21.60 2.10 29.87 200.00 545.50
August 37.30 07-AUG-14:00 26.58 22.90 3.00 29.87 311.00 370.00
September 37.50 17-SEP-19:00 27.68 24.60 0.20 28.59 0.00 0.00
October 36.40 02-OCT-14:20 21.05 13.00 1.80 21.61 187.33 678.83
November 30.30 04-NOV-13:00 17.17 8.90 1.10 14.84 155.00 710.00
December 24.60 28-DEC-13:00 15.30 8.90 2.80 10.88 181.50 535.00
                 
Annual Sum or Average                
Minimum of Months 23.60   14.20 5.30 0.00 8.15 0.00 0.00
Maximum of Months 44.60   27.68 24.60 6.70 29.87 311.00 809.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 4.80 05-JAN-06:00 4.73 4.60 0.00 -10.2 0.00 0.00
February 6.90 02-FEB-05:00 6.67 6.50 0.00 -7.8 0.00 0.00
March 13.30 01-MAR-03:00 10.56 8.30 0.80 -1.4 0.00 0.00
April 17.40 11-APR-04:00 13.58 10.90 0.00 3.06 0.00 0.00
May 22.70 13-MAY-04:00 20.32 19.30 2.10 20.40 0.00 0.00
June 23.30 18-JUN-04:00 21.80 21.20 2.70 17.75 0.00 0.00
July 23.20 19-JUL-02:00 23.20 23.20 2.30 15.39 0.00 0.00
August 23.40 15-AUG-23:00 22.91 22.80 2.40 21.78 0.00 0.00
September 23.00 27-SEP-04:00 20.74 19.70 0.00 10.30 0.00 0.00
October 15.50 31-OCT-04:00 14.07 13.20 0.00 1.80 0.00 0.00
November 9.50 27-NOV-05:00 8.75 8.10 0.00 -5.0 0.00 0.00
December 5.00 21-DEC-04:00 4.08 3.00 0.00 -10.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 4.80   4.08 3.00 0.00 -10.5 0.00 0.00
Maximum of Months 23.40   23.20 23.20 2.70 21.78 0.00 0.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.62 17-JAN-14:00 18.20 14.10 1.00 11.07 198.00 56.50
February 18.14 25-FEB-16:00 21.20 16.60 5.90 10.88 107.50 156.50
March 21.38 10-MAR-18:49 29.25 17.73 2.10 21.44 0.00 0.00
April 23.42 18-APR-13:00 37.10 17.80 5.70 23.49 233.50 671.50
May 27.40 22-MAY-22:00 29.40 26.80 0.00 20.40 0.00 0.00
June 28.92 28-JUN-12:00 34.40 27.50 1.00 25.49 332.50 501.50
July 29.18 01-JUL-16:00 37.20 26.80 2.30 25.66 196.00 196.00
August 29.17 27-AUG-15:00 35.10 27.40 1.30 29.55 256.00 129.00
September 28.10 14-SEP-16:00 33.70 26.40 1.40 26.48 122.50 108.50
October 23.06 06-OCT-10:00 28.60 20.80 1.30 20.22 327.00 348.50
November 18.93 08-NOV-17:10 27.55 14.47 0.17 16.67 28.00 65.33
December 15.64 29-DEC-19:00 16.80 14.90 4.80 13.54 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 15.62   16.80 14.10 0.00 10.88 0.00 0.00
Maximum of Months 29.18   37.20 27.50 5.90 29.55 332.50 671.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.10 17-JAN-13:00 17.80 15.48 0.90 9.72 260.50 81.50
February 16.60 25-FEB-16:00 21.20 18.14 5.90 10.88 107.50 156.50
March 18.30 10-MAR-19:00 27.70 21.26 2.10 21.44 0.00 0.00
April 19.30 26-APR-23:10 28.53 22.04 0.00 15.61 0.00 0.00
May 26.80 22-MAY-22:00 29.40 27.40 0.00 20.40 0.00 0.00
June 27.50 28-JUN-12:00 34.40 28.92 1.00 25.49 332.50 501.50
July 27.30 18-JUL-06:19 29.10 27.70 1.17 26.48 20.00 0.00
August 28.80 12-AUG-07:00 29.10 28.83 2.90 26.81 113.00 6.50
September 26.50 12-SEP-14:00 30.50 27.38 0.90 25.99 260.00 20.00
October 21.10 06-OCT-08:00 25.50 22.41 0.30 17.21 239.00 159.00
November 16.30 08-NOV-21:19 20.10 17.59 0.00 10.95 0.00 0.00
December 14.90 29-DEC-20:10 16.72 15.59 4.73 13.13 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 14.10   16.72 15.48 0.00 9.72 0.00 0.00
Maximum of Months 28.80   34.40 28.92 5.90 26.81 332.50 501.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.92 27.26 0.00
February 18.00 13.00 16.00 21.74 33.91 0.00
March 18.00 13.00 16.00 24.21 44.04 0.00
April 18.00 13.00 16.00 27.79 55.91 0.00
May 18.00 13.00 16.00 31.48 58.43 0.00
June 18.00 13.00 16.00 34.27 54.82 0.00
July 18.00 13.00 16.00 35.42 39.75 0.00
August 18.00 13.00 16.00 34.60 34.68 0.00
September 18.00 13.00 16.00 32.04 35.55 0.00
October 18.00 13.00 16.00 28.44 39.44 0.00
November 18.00 13.00 16.00 24.77 33.85 0.00
December 18.00 13.00 16.00 22.02 26.79 0.00
             
Annual Sum or Average 18.00 13.00 16.00 28.18 40.37 0.00
Minimum of Months 18.00 13.00 16.00 20.92 26.79 0.00
Maximum of Months 18.00 13.00 16.00 35.42 58.43 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.312957E+11 -0.302736E+11 0.00 0.00 744.00 0.00 -0.102208E+10 58.97 0.00 0.00
February 0.278521E+11 -0.269281E+11 0.00 0.00 672.00 0.00 -923944526.0 58.98 0.00 0.00
March 0.305700E+11 -0.295444E+11 0.00 0.00 744.00 0.00 -0.102560E+10 58.98 0.00 0.00
April 0.250274E+11 -0.240388E+11 0.00 0.00 720.00 0.00 -988593009.5 58.97 0.00 0.00
May 0.236951E+11 -0.226723E+11 0.00 0.00 744.00 0.00 -0.102282E+10 58.97 0.00 0.00
June 0.211365E+11 -0.201463E+11 0.00 0.00 720.00 0.00 -990271949.1 58.96 0.00 0.00
July 0.192801E+11 -0.182625E+11 0.00 0.00 744.00 0.00 -0.101764E+10 58.96 0.00 0.00
August 0.217342E+11 -0.207123E+11 0.00 0.00 744.00 0.00 -0.102190E+10 58.97 0.00 0.00
September 0.217861E+11 -0.207995E+11 0.00 0.00 720.00 0.00 -986605901.5 58.96 0.00 0.00
October 0.253256E+11 -0.243081E+11 0.00 0.00 744.00 0.00 -0.101756E+10 58.98 0.00 0.00
November 0.276753E+11 -0.266901E+11 0.00 0.00 720.00 0.00 -985146990.4 58.97 0.00 0.00
December 0.297110E+11 -0.286922E+11 0.00 0.00 744.00 0.00 -0.101876E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.305089E+12 -0.293068E+12 0.00 0.00 8760.00 0.00 -0.120209E+11 58.97 0.00 0.00
Minimum of Months 0.192801E+11 -0.302736E+11 0.00 0.00 672.00 0.00 -0.102560E+10 58.96 0.00 0.00
Maximum of Months 0.312957E+11 -0.182625E+11 0.00 0.00 744.00 0.00 -923944526.0 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.51 0.48 01-JAN-07:00 5587.00 35.39 298.33 287.33 1241.27 25.72 289.83 266.00
February 303.83 0.51 0.48 01-FEB-08:09 3361.53 29.30 203.33 271.17 1099.85 21.65 213.67 243.83
March 364.50 0.51 0.48 01-MAR-07:49 1746.34 20.45 79.17 323.67 946.86 21.50 247.50 291.33
April 379.83 0.53 0.48 01-APR-07:30 1185.67 18.87 9.67 328.83 700.32 20.16 180.17 296.17
May 406.00 0.52 0.48 01-MAY-07:10 1006.26 18.69 0.00 349.83 590.02 20.07 144.67 309.67
June 386.67 0.52 0.48 01-JUN-07:30 995.79 18.34 0.00 334.33 570.38 19.69 136.17 292.00
July 379.83 0.51 0.48 01-JUL-06:00 1113.23 18.84 0.33 333.17 578.71 20.10 146.33 281.33
August 372.50 0.52 0.48 01-AUG-07:10 1250.72 18.83 18.50 321.67 627.42 20.07 172.33 271.00
September 344.33 0.52 0.48 01-SEP-07:19 1523.47 19.57 66.67 302.17 788.20 20.88 210.50 263.00
October 347.33 0.52 0.48 01-OCT-07:10 2574.74 21.53 109.17 305.33 1062.27 21.12 226.50 278.33
November 317.83 0.51 0.48 01-NOV-07:19 7555.70 36.61 310.50 287.83 1296.96 23.62 260.83 265.00
December 315.50 0.50 0.48 01-DEC-07:30 5899.83 36.71 308.83 286.00 1459.62 27.89 308.67 278.67
                         
Annual Sum or Average 4237.50 0.52     2656.38 23.86 1404.50 3731.33 889.30 21.71 2537.17 3336.33
Minimum of Months 303.83 0.50 0.48   995.79 18.34 0.00 271.17 570.38 19.69 136.17 243.83
Maximum of Months 406.00 0.53 0.48   7555.70 36.71 310.50 349.83 1459.62 27.89 308.67 309.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.53 0.48 01-JAN-07:49 1654.05 23.82 107.17 267.67 872.87 23.89 165.83 223.67
February 303.83 0.52 0.48 01-FEB-07:49 2049.04 23.96 100.33 257.50 1081.03 24.07 154.83 219.83
March 364.50 0.51 0.48 01-MAR-07:30 1971.01 23.44 101.50 319.17 1019.94 23.69 165.17 287.17
April 379.83 0.52 0.48 01-APR-06:49 2387.77 22.87 110.33 328.00 1256.65 23.21 118.00 300.00
May 406.00 0.51 0.48 01-MAY-06:10 2476.59 23.26 128.50 357.33 965.45 22.42 123.50 323.50
June 386.67 0.52 0.48 01-JUN-06:00 1978.26 21.99 108.00 337.83 831.36 21.50 124.83 299.67
July 379.83 0.51 0.48 01-JUL-06:10 1637.28 21.95 102.00 337.50 731.31 21.54 125.50 286.67
August 372.50 0.52 0.48 01-AUG-06:30 1499.77 21.42 98.33 322.83 692.23 21.07 133.50 267.83
September 344.33 0.52 0.48 01-SEP-06:49 1674.99 22.42 90.50 298.00 848.32 22.83 152.17 257.67
October 347.33 0.52 0.48 01-OCT-06:49 1842.26 23.15 102.67 297.50 932.82 23.23 161.67 265.00
November 317.83 0.52 0.48 01-NOV-07:10 1663.43 23.57 94.83 268.67 846.23 23.55 154.50 238.83
December 315.50 0.52 0.48 01-DEC-07:30 1729.72 24.45 112.50 262.33 919.78 24.44 169.17 226.83
                         
Annual Sum or Average 4237.50 0.52     1892.20 22.97 1256.67 3654.33 915.77 22.88 1748.67 3196.67
Minimum of Months 303.83 0.51 0.48   1499.77 21.42 90.50 257.50 692.23 21.07 118.00 219.83
Maximum of Months 406.00 0.53 0.48   2476.59 24.45 128.50 357.33 1256.65 24.44 169.17 323.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.55 0.48 01-JAN-09:20 554.70 16.48 0.00 248.17 340.77 18.00 0.00 167.50
February 303.83 0.53 0.48 01-FEB-08:50 639.90 17.35 0.00 249.00 392.01 18.81 0.00 183.33
March 364.50 0.52 0.48 01-MAR-08:20 756.72 18.45 0.00 313.67 462.82 19.83 0.33 262.83
April 379.83 0.52 0.48 01-APR-07:19 817.80 18.47 0.00 332.67 508.17 19.78 48.83 298.50
May 406.00 0.51 0.48 01-MAY-06:30 970.86 19.17 6.17 365.50 570.02 20.49 149.67 336.33
June 386.67 0.51 0.48 01-JUN-07:19 1072.99 20.78 64.00 348.33 599.84 20.33 170.67 311.17
July 379.83 0.51 0.48 01-JUL-06:40 1086.46 20.41 40.33 345.00 568.04 20.99 144.17 297.17
August 372.50 0.52 0.48 01-AUG-06:00 971.60 18.52 0.00 325.67 507.87 19.72 90.17 271.33
September 344.33 0.52 0.48 01-SEP-07:30 848.14 18.39 0.00 299.17 471.66 19.64 35.33 245.17
October 347.33 0.53 0.48 01-OCT-07:40 671.39 17.30 0.00 288.50 420.34 18.78 0.00 235.50
November 317.83 0.54 0.48 01-NOV-08:09 572.50 16.88 0.00 252.50 371.70 18.55 0.00 191.67
December 315.50 0.54 0.48 01-DEC-08:39 546.82 16.57 0.00 243.33 338.97 18.16 0.00 165.00
                         
Annual Sum or Average 4237.50 0.52     807.41 18.33 110.50 3611.50 469.96 19.50 639.17 2965.50
Minimum of Months 303.83 0.51 0.48   546.82 16.48 0.00 243.33 338.97 18.00 0.00 165.00
Maximum of Months 406.00 0.55 0.48   1086.46 20.78 64.00 365.50 599.84 20.99 170.67 336.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.53 0.48 01-JAN-09:20 1657.27 23.60 104.33 266.50 860.01 23.62 165.83 223.50
February 303.83 0.52 0.48 01-FEB-09:09 1962.25 23.60 103.67 262.00 788.60 22.39 150.00 223.17
March 364.50 0.51 0.48 01-MAR-08:30 1923.06 23.35 101.17 319.83 990.90 23.59 174.83 288.67
April 379.83 0.52 0.48 01-APR-07:00 2188.74 21.13 84.50 332.00 1142.84 21.60 90.50 302.17
May 406.00 0.52 0.48 01-MAY-07:19 2100.92 17.39 0.00 352.00 1089.87 19.52 80.67 322.17
June 386.67 0.52 0.48 01-JUN-07:00 2089.78 17.41 0.00 337.67 865.07 19.36 87.83 302.50
July 379.83 0.51 0.48 01-JUL-07:30 1585.75 18.11 3.67 336.17 722.72 19.68 97.00 287.67
August 372.50 0.52 0.48 01-AUG-07:40 1479.98 19.38 54.17 321.83 736.93 19.55 97.17 272.50
September 344.33 0.52 0.48 01-SEP-08:09 1644.12 21.62 81.00 301.33 827.96 21.98 150.83 257.67
October 347.33 0.53 0.48 01-OCT-07:00 1954.50 23.25 105.00 293.67 986.71 23.34 149.83 263.33
November 317.83 0.52 0.48 01-NOV-08:20 1713.61 23.69 97.17 270.00 862.85 23.66 155.83 240.33
December 315.50 0.52 0.48 01-DEC-08:39 1510.17 23.76 101.00 268.83 781.18 23.73 170.00 231.67
                         
Annual Sum or Average 4237.50 0.52     1826.18 21.16 835.67 3661.83 892.98 21.71 1570.33 3215.33
Minimum of Months 303.83 0.51 0.48   1479.98 17.39 0.00 262.00 722.72 19.36 80.67 223.17
Maximum of Months 406.00 0.53 0.48   2188.74 23.76 105.00 352.00 1142.84 23.73 174.83 322.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.51 0.48 01-JAN-07:00 5621.98 34.87 296.67 287.33 1323.48 21.54 84.50 268.33
February 303.83 0.51 0.48 01-FEB-08:09 3400.83 26.56 195.33 271.33 1177.88 16.80 0.00 246.83
March 364.50 0.51 0.48 01-MAR-07:49 1780.18 14.28 7.50 323.67 1013.47 17.40 0.00 294.67
April 379.83 0.52 0.48 01-APR-07:19 1213.00 13.17 0.00 329.17 749.46 16.56 0.00 299.67
May 406.00 0.52 0.48 01-MAY-07:10 1025.74 12.79 0.00 350.17 629.34 16.24 0.00 315.17
June 386.67 0.52 0.48 01-JUN-07:30 1012.82 12.35 0.00 334.67 607.46 15.73 0.00 296.17
July 379.83 0.51 0.48 01-JUL-06:00 1125.18 12.41 0.00 333.83 614.53 15.74 0.00 287.00
August 372.50 0.52 0.48 01-AUG-07:10 1260.65 12.37 0.00 322.00 665.37 15.63 0.00 277.00
September 344.33 0.51 0.48 01-SEP-07:19 1541.26 13.13 0.00 302.67 838.23 16.51 0.00 267.50
October 347.33 0.52 0.48 01-OCT-07:10 2623.77 15.66 42.67 307.67 1141.33 16.87 10.00 282.00
November 317.83 0.50 0.48 01-NOV-07:19 7610.53 36.19 310.33 288.00 1400.77 20.73 74.33 272.67
December 315.50 0.50 0.48 01-DEC-07:30 5935.37 36.29 308.00 286.50 1547.51 24.15 123.17 279.67
                         
Annual Sum or Average 4237.50 0.51     2684.78 19.26 1160.50 3737.00 949.80 17.66 292.00 3386.67
Minimum of Months 303.83 0.50 0.48   1012.82 12.35 0.00 271.33 607.46 15.63 0.00 246.83
Maximum of Months 406.00 0.52 0.48   7610.53 36.29 310.33 350.17 1547.51 24.15 123.17 315.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.53 0.48 01-JAN-07:49 1680.21 21.38 106.83 269.00 910.14 22.03 77.33 228.33
February 303.83 0.52 0.48 01-FEB-07:49 2085.42 21.32 100.00 258.67 1124.62 22.06 74.00 226.33
March 364.50 0.51 0.48 01-MAR-07:30 2019.42 20.47 101.50 320.17 1070.72 21.36 70.67 291.17
April 379.83 0.52 0.48 01-APR-06:49 2415.04 19.97 110.17 328.83 1311.20 20.89 81.17 303.67
May 406.00 0.51 0.48 01-MAY-06:10 2495.02 19.31 117.00 357.50 1020.01 19.76 66.50 327.33
June 386.67 0.52 0.48 01-JUN-06:00 2006.53 18.92 107.17 338.83 878.60 18.86 51.33 304.00
July 379.83 0.51 0.48 01-JUL-06:10 1658.37 18.33 96.33 338.83 776.08 18.92 48.17 294.17
August 372.50 0.52 0.48 01-AUG-06:30 1520.80 18.31 97.67 324.00 788.56 19.50 69.00 274.83
September 344.33 0.52 0.48 01-SEP-06:49 1707.75 19.41 90.00 298.50 889.48 20.50 64.50 263.33
October 347.33 0.52 0.48 01-OCT-06:49 1881.16 20.26 100.83 298.17 978.22 21.14 72.17 268.00
November 317.83 0.52 0.48 01-NOV-06:00 1687.61 20.02 87.83 269.67 888.77 21.58 64.83 242.50
December 315.50 0.52 0.48 01-DEC-07:30 1754.95 22.08 112.50 263.83 956.81 22.70 81.67 231.83
                         
Annual Sum or Average 4237.50 0.52     1921.01 19.90 1227.83 3666.00 966.00 20.68 821.33 3255.50
Minimum of Months 303.83 0.51 0.48   1520.80 18.31 87.83 258.67 776.08 18.86 48.17 226.33
Maximum of Months 406.00 0.53 0.48   2495.02 22.08 117.00 357.50 1311.20 22.70 81.67 327.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.55 0.48 01-JAN-09:09 563.11 10.87 0.00 248.83 362.60 14.39 0.00 179.50
February 303.83 0.53 0.48 01-FEB-08:50 650.48 11.78 0.00 249.17 417.37 15.28 0.00 193.17
March 364.50 0.51 0.48 01-MAR-08:09 770.61 13.10 0.00 314.67 493.14 16.57 0.00 270.33
April 379.83 0.52 0.48 01-APR-07:19 835.40 13.26 0.00 332.83 542.33 16.67 0.00 304.83
May 406.00 0.51 0.48 01-MAY-06:30 990.58 13.32 1.17 365.83 607.96 16.86 1.17 339.33
June 386.67 0.51 0.48 01-JUN-07:19 1092.44 15.58 39.17 348.33 641.54 18.75 40.50 317.50
July 379.83 0.50 0.48 01-JUL-06:30 1100.51 14.66 29.17 345.17 603.84 17.82 29.67 303.17
August 372.50 0.52 0.48 01-AUG-06:00 983.79 12.28 0.00 325.67 539.16 15.55 0.00 279.00
September 344.33 0.52 0.48 01-SEP-07:30 860.48 12.56 0.00 299.33 501.37 15.88 0.00 252.50
October 347.33 0.53 0.48 01-OCT-07:30 683.34 11.88 0.00 289.00 447.84 15.32 0.00 242.00
November 317.83 0.53 0.48 01-NOV-08:09 582.02 11.29 0.00 253.33 395.97 14.95 0.00 203.33
December 315.50 0.54 0.48 01-DEC-08:30 554.92 10.92 0.00 244.50 360.64 14.52 0.00 178.00
                         
Annual Sum or Average 4237.50 0.52     820.86 12.73 69.50 3616.67 500.59 16.14 71.33 3062.67
Minimum of Months 303.83 0.50 0.48   554.92 10.87 0.00 244.50 360.64 14.39 0.00 178.00
Maximum of Months 406.00 0.55 0.48   1100.51 15.58 39.17 365.83 641.54 18.75 40.50 339.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.53 0.48 01-JAN-09:09 1683.35 21.17 104.00 267.50 897.15 21.75 74.33 227.33
February 303.83 0.52 0.48 01-FEB-08:00 1994.86 21.06 103.17 263.00 829.67 20.10 48.00 228.17
March 364.50 0.51 0.48 01-MAR-08:20 1969.55 20.39 101.17 320.00 1040.65 21.25 69.33 292.17
April 379.83 0.52 0.48 01-APR-07:49 2215.82 17.89 84.50 332.50 1196.61 18.98 54.67 305.33
May 406.00 0.51 0.48 01-MAY-07:19 2125.59 12.79 0.00 352.83 1143.43 16.23 0.00 326.67
June 386.67 0.52 0.48 01-JUN-07:49 2120.42 12.88 0.00 338.00 916.29 16.11 0.00 306.83
July 379.83 0.51 0.48 01-JUL-07:19 1607.93 13.62 3.50 337.17 762.81 16.49 0.00 293.33
August 372.50 0.52 0.48 01-AUG-07:40 1501.09 15.64 52.17 323.00 774.40 16.45 4.67 277.83
September 344.33 0.51 0.48 01-SEP-08:09 1676.84 18.44 80.17 302.33 869.67 19.48 52.00 263.00
October 347.33 0.53 0.48 01-OCT-07:49 1994.05 20.60 104.67 294.50 1031.45 21.29 74.17 267.33
November 317.83 0.52 0.48 01-NOV-08:20 1742.92 20.93 95.83 270.50 905.10 21.73 67.17 244.67
December 315.50 0.52 0.48 01-DEC-08:30 1524.19 20.16 90.17 269.17 817.76 21.90 70.00 236.50
                         
Annual Sum or Average 4237.50 0.52     1855.06 17.72 819.33 3670.50 937.47 19.15 514.33 3269.17
Minimum of Months 303.83 0.51 0.48   1501.09 12.79 0.00 263.00 762.81 16.11 0.00 227.33
Maximum of Months 406.00 0.53 0.48   2215.82 21.17 104.67 352.83 1196.61 21.90 74.33 326.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.51 0.48 01-JAN-07:00 5624.00 34.86 296.67 287.33 1325.45 21.53 84.50 268.33
February 303.83 0.51 0.48 01-FEB-08:09 3403.50 26.55 195.33 271.33 1179.69 16.78 0.00 246.83
March 364.50 0.51 0.48 01-MAR-07:49 1782.61 14.25 7.50 323.67 1014.98 17.39 0.00 294.83
April 379.83 0.52 0.48 01-APR-07:19 1214.45 13.14 0.00 329.17 750.44 16.55 0.00 299.67
May 406.00 0.52 0.48 01-MAY-07:10 1026.96 12.76 0.00 350.17 630.18 16.22 0.00 315.17
June 386.67 0.52 0.48 01-JUN-07:30 1014.13 12.32 0.00 334.67 608.33 15.71 0.00 296.17
July 379.83 0.51 0.48 01-JUL-06:00 1127.12 12.38 0.00 333.83 615.60 15.72 0.00 287.33
August 372.50 0.52 0.48 01-AUG-07:10 1262.97 12.35 0.00 322.33 666.63 15.61 0.00 277.33
September 344.33 0.51 0.48 01-SEP-07:19 1543.85 13.11 0.00 302.67 839.72 16.50 0.00 267.67
October 347.33 0.52 0.48 01-OCT-07:10 2626.21 15.64 42.67 307.67 1142.95 16.85 10.00 282.17
November 317.83 0.50 0.48 01-NOV-07:19 7612.61 36.19 310.33 288.00 1402.62 20.72 74.33 272.67
December 315.50 0.50 0.48 01-DEC-07:30 5937.38 36.28 308.00 286.50 1549.59 24.14 123.17 279.67
                         
Annual Sum or Average 4237.50 0.51     2686.79 19.24 1160.50 3737.33 951.21 17.65 292.00 3387.83
Minimum of Months 303.83 0.50 0.48   1014.13 12.32 0.00 271.33 608.33 15.61 0.00 246.83
Maximum of Months 406.00 0.52 0.48   7612.61 36.28 310.33 350.17 1549.59 24.14 123.17 315.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.53 0.48 01-JAN-07:49 1681.15 21.35 106.83 269.00 911.10 22.02 77.33 228.50
February 303.83 0.52 0.48 01-FEB-07:49 2086.60 21.29 100.00 258.67 1125.72 22.05 74.00 226.33
March 364.50 0.51 0.48 01-MAR-07:30 2020.70 20.44 101.50 320.17 1071.92 21.34 70.67 291.17
April 379.83 0.52 0.48 01-APR-06:49 2416.28 19.95 110.17 328.83 1312.36 20.87 81.17 304.00
May 406.00 0.51 0.48 01-MAY-06:10 2496.37 19.28 117.00 357.83 1021.17 19.75 66.50 327.33
June 386.67 0.52 0.48 01-JUN-06:00 2008.17 18.89 107.17 338.83 879.79 18.84 51.33 304.00
July 379.83 0.51 0.48 01-JUL-06:10 1660.51 18.31 96.33 338.83 777.38 18.91 48.17 294.33
August 372.50 0.52 0.48 01-AUG-06:30 1522.99 18.28 97.50 324.17 789.87 19.49 69.00 275.17
September 344.33 0.52 0.48 01-SEP-06:49 1709.62 19.39 90.00 298.50 890.79 20.48 64.50 263.33
October 347.33 0.52 0.48 01-OCT-06:49 1882.26 20.23 100.83 298.17 979.31 21.13 72.17 268.00
November 317.83 0.52 0.48 01-NOV-06:00 1688.45 19.99 87.83 269.67 889.71 21.57 64.83 242.83
December 315.50 0.52 0.48 01-DEC-07:30 1755.86 22.05 112.50 264.00 957.76 22.69 81.67 232.50
                         
Annual Sum or Average 4237.50 0.52     1922.43 19.88 1227.67 3666.67 967.15 20.67 821.33 3257.50
Minimum of Months 303.83 0.51 0.48   1522.99 18.28 87.83 258.67 777.38 18.84 48.17 226.33
Maximum of Months 406.00 0.53 0.48   2496.37 22.05 117.00 357.83 1312.36 22.69 81.67 327.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.55 0.48 01-JAN-09:09 563.55 10.84 0.00 249.00 363.04 14.37 0.00 179.83
February 303.83 0.53 0.48 01-FEB-08:50 651.03 11.75 0.00 249.33 417.89 15.27 0.00 193.33
March 364.50 0.51 0.48 01-MAR-08:09 771.28 13.07 0.00 314.83 493.75 16.56 0.00 270.50
April 379.83 0.52 0.48 01-APR-07:19 836.09 13.23 0.00 332.83 542.96 16.65 0.00 304.83
May 406.00 0.51 0.48 01-MAY-06:30 991.60 13.29 1.17 365.83 608.75 16.84 1.17 339.67
June 386.67 0.51 0.48 01-JUN-07:19 1093.78 15.55 39.17 348.33 642.47 18.74 40.50 317.83
July 379.83 0.50 0.48 01-JUL-06:30 1102.28 14.64 29.17 345.33 604.89 17.80 29.67 303.17
August 372.50 0.52 0.48 01-AUG-06:00 985.40 12.26 0.00 325.67 540.12 15.54 0.00 279.33
September 344.33 0.52 0.48 01-SEP-07:19 861.62 12.53 0.00 299.33 502.16 15.87 0.00 252.50
October 347.33 0.53 0.48 01-OCT-07:30 683.85 11.85 0.00 289.17 448.37 15.31 0.00 242.17
November 317.83 0.53 0.48 01-NOV-08:09 582.32 11.25 0.00 253.33 396.38 14.93 0.00 204.17
December 315.50 0.54 0.48 01-DEC-08:30 555.32 10.89 0.00 244.67 361.08 14.51 0.00 178.33
                         
Annual Sum or Average 4237.50 0.52     821.76 12.70 69.50 3617.67 501.28 16.12 71.33 3065.67
Minimum of Months 303.83 0.50 0.48   555.32 10.84 0.00 244.67 361.08 14.37 0.00 178.33
Maximum of Months 406.00 0.55 0.48   1102.28 15.55 39.17 365.83 642.47 18.74 40.50 339.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.53 0.48 01-JAN-09:09 1684.31 21.14 104.00 267.83 898.11 21.74 74.33 227.33
February 303.83 0.52 0.48 01-FEB-08:00 1996.07 21.04 103.17 263.00 830.75 20.08 48.00 228.33
March 364.50 0.51 0.48 01-MAR-08:20 1970.84 20.36 101.17 320.00 1041.84 21.24 69.33 292.33
April 379.83 0.52 0.48 01-APR-07:49 2217.04 17.86 84.50 332.50 1197.74 18.97 54.67 305.50
May 406.00 0.51 0.48 01-MAY-07:19 2126.96 12.76 0.00 352.83 1144.61 16.21 0.00 326.67
June 386.67 0.52 0.48 01-JUN-07:49 2122.05 12.84 0.00 338.00 917.51 16.10 0.00 306.83
July 379.83 0.51 0.48 01-JUL-07:19 1610.11 13.58 3.50 337.17 764.11 16.47 0.00 293.50
August 372.50 0.52 0.48 01-AUG-07:40 1503.29 15.61 52.00 323.00 775.71 16.44 4.67 278.00
September 344.33 0.51 0.48 01-SEP-07:00 1678.75 18.41 80.17 302.33 870.98 19.47 52.00 263.00
October 347.33 0.53 0.48 01-OCT-07:49 1995.21 20.57 104.67 294.67 1032.53 21.27 74.17 267.33
November 317.83 0.52 0.48 01-NOV-08:20 1743.76 20.90 95.83 270.50 906.03 21.72 67.17 244.67
December 315.50 0.52 0.48 01-DEC-08:30 1525.13 20.13 90.17 269.33 818.70 21.89 70.00 236.67
                         
Annual Sum or Average 4237.50 0.52     1856.49 17.69 819.17 3671.17 938.61 19.13 514.33 3270.17
Minimum of Months 303.83 0.51 0.48   1503.29 12.76 0.00 263.00 764.11 16.10 0.00 227.33
Maximum of Months 406.00 0.53 0.48   2217.04 21.14 104.67 352.83 1197.74 21.89 74.33 326.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.895018E+09 11050.65 05-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.149356E+09 6808.21 02-FEB-06:50 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 161387.26 523.37 27-NOV-05:35 0.00 0.00 0.00 0.00 0.00
December 0.193873E+09 10119.61 23-DEC-05:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.123841E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.895018E+09 11050.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7681942.04 6357.59 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 7681942.04     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7681942.04 6357.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.121305E+11 88882.92 02-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.215618E+10 68713.46 02-FEB-06:50 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 6624.69 11.04 16-MAY-15:40 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 60615545.40 17377.49 27-NOV-06:08 0.00 0.00 0.00 0.00 0.00
December 0.370594E+10 73821.37 21-DEC-08:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180533E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121305E+11 88882.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.394112E+09 352605.57 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.394112E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.394112E+09 352605.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.698805E+10 184617.13 02-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.968783E+09 170281.16 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.224496E+10 181100.19 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102018E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.698805E+10 184617.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.231050E+10 137565.87 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.240329E+09 126653.61 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.456376E+09 122849.39 23-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.300720E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.231050E+10 137565.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.135261E+10 182610.43 03-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.195608E+09 163748.33 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.165170E+09 16052.70 23-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.171339E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135261E+10 182610.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.191081E+10 135903.20 02-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.151619E+09 68890.53 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.345872E+09 75593.19 23-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.240830E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.191081E+10 135903.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.213236E+10 10530.85 02-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.518429E+09 9306.68 02-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 49568158.69 5229.60 27-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.934884E+09 9542.16 23-DEC-05:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.363524E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.213236E+10 10530.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.161427E+10 80812.60 02-JAN-05:17 0.00 0.00 0.00 0.00 0.00
February 3986759.50 1564.06 11-FEB-08:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.124983E+09 26330.10 23-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.174324E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.161427E+10 80812.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.219945E+10 22049.35 23-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.475630E+09 21338.32 02-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 977814.97 334.22 01-MAR-06:40 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 60137453.23 13227.98 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.111843E+10 22125.59 21-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.385463E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.219945E+10 22125.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.831877E+09 15820.03 03-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.167216E+09 15355.11 02-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 11787356.28 1725.36 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.394608E+09 15924.22 21-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140549E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.831877E+09 15924.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.792625E+09 21951.79 03-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.178017E+09 21307.57 02-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.300983E+09 21687.45 23-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127162E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.792625E+09 21951.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.735222E+09 16593.45 03-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.132105E+09 15928.18 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 2684120.89 380.42 27-NOV-06:40 0.00 0.00 0.00 0.00 0.00
December 0.299620E+09 16601.82 23-DEC-05:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116963E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.735222E+09 16601.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 98.09 0.82 23-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 98.09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 98.09 0.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.319171E+11 0.318815E+11 73958.44 18-JAN-06:03 59796.37 0.37
February 0.00 0.00 0.535232E+11 0.534108E+11 137160.96 25-FEB-06:03 93924.98 0.52
March 0.00 0.00 0.113546E+12 0.111699E+12 194319.48 11-MAR-06:02 152991.44 0.72
April 0.00 0.00 0.178601E+12 0.171774E+12 245068.71 17-APR-04:22 176904.82 0.82
May 0.00 0.00 0.225418E+12 0.191315E+12 277978.66 22-MAY-05:03 179286.96 0.86
June 0.00 0.00 0.264286E+12 0.196026E+12 286576.64 27-JUN-05:02 171392.50 0.87
July 0.00 0.00 0.299831E+12 0.185347E+12 298880.24 05-JUL-03:02 196938.05 0.87
August 0.00 0.00 0.320001E+12 0.194748E+12 306899.58 28-AUG-03:01 185963.01 0.89
September 0.00 0.00 0.225567E+12 0.141613E+12 289637.10 05-SEP-05:02 174105.54 0.81
October 0.00 0.00 0.145588E+12 0.128889E+12 242752.28 12-OCT-04:12 151486.91 0.74
November 0.00 0.00 0.906330E+11 0.894293E+11 161053.19 09-NOV-05:12 108738.92 0.62
December 0.00 0.00 0.523929E+11 0.523929E+11 87492.58 04-DEC-15:00 87492.58 0.47
                 
Annual Sum or Average 0.00 0.00 0.200130E+13 0.154853E+13       0.71
Minimum of Months 0.00 0.00 0.319171E+11 0.318815E+11 73958.44   59796.37 0.37
Maximum of Months 0.00 0.00 0.320001E+12 0.196026E+12 306899.58   196938.05 0.89



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.190234E+12 0.190234E+12 536456.62 12-JAN-15:05 536456.62 0.32
February 0.00 0.00 0.364762E+12 0.363986E+12 1051129.01 25-FEB-06:03 717028.64 0.48
March 0.00 0.00 0.867741E+12 0.854324E+12 1917282.37 11-MAR-06:02 1454307.28 0.62
April 0.00 0.00 0.144133E+13 0.138734E+13 2057354.63 25-APR-04:12 1486146.25 0.72
May 0.00 0.00 0.213674E+13 0.180099E+13 2640639.76 25-MAY-05:02 1618088.55 0.84
June 0.00 0.00 0.242474E+13 0.176700E+13 2809311.89 27-JUN-05:02 1631535.73 0.83
July 0.00 0.00 0.265104E+13 0.156345E+13 3007147.97 25-JUL-05:02 1607736.08 0.81
August 0.00 0.00 0.260706E+13 0.147463E+13 2952591.47 11-AUG-05:03 1583253.84 0.79
September 0.00 0.00 0.201337E+13 0.123587E+13 2836960.22 05-SEP-05:02 1643818.40 0.73
October 0.00 0.00 0.121258E+13 0.106738E+13 2223005.63 12-OCT-05:03 1293005.61 0.65
November 0.00 0.00 0.651527E+12 0.643823E+12 1348747.46 09-NOV-06:03 888581.72 0.58
December 0.00 0.00 0.268472E+12 0.268472E+12 645776.19 29-DEC-06:03 645776.19 0.40
                 
Annual Sum or Average 0.00 0.00 0.168296E+14 0.126175E+14       0.65
Minimum of Months 0.00 0.00 0.190234E+12 0.190234E+12 536456.62   536456.62 0.32
Maximum of Months 0.00 0.00 0.265104E+13 0.180099E+13 3007147.97   1643818.40 0.84



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.157661E+11 0.157661E+11 50800.94 12-JAN-15:30 50800.94 0.30
February 0.00 0.00 0.330138E+11 0.329426E+11 91055.18 22-FEB-15:00 91055.18 0.46
March 0.00 0.00 0.882760E+11 0.870255E+11 189356.31 11-MAR-06:02 141965.90 0.60
April 0.00 0.00 0.157509E+12 0.152060E+12 230541.51 27-APR-05:02 180685.61 0.71
May 0.00 0.00 0.235545E+12 0.201650E+12 283380.33 25-MAY-05:02 176593.15 0.84
June 0.00 0.00 0.264787E+12 0.198853E+12 313817.73 27-JUN-05:02 186200.28 0.83
July 0.00 0.00 0.282471E+12 0.173241E+12 338593.66 25-JUL-05:02 181336.42 0.81
August 0.00 0.00 0.275267E+12 0.161626E+12 320525.43 16-AUG-05:02 181116.75 0.79
September 0.00 0.00 0.209929E+12 0.132446E+12 316591.02 05-SEP-05:02 187505.38 0.73
October 0.00 0.00 0.122548E+12 0.108896E+12 222902.23 06-OCT-04:12 153514.04 0.64
November 0.00 0.00 0.599211E+11 0.595199E+11 114000.00 09-NOV-06:03 73304.59 0.55
December 0.00 0.00 0.206692E+11 0.206692E+11 60388.16 01-DEC-15:00 60388.16 0.37
                 
Annual Sum or Average 0.00 0.00 0.176570E+13 0.134470E+13       0.64
Minimum of Months 0.00 0.00 0.157661E+11 0.157661E+11 50800.94   50800.94 0.30
Maximum of Months 0.00 0.00 0.282471E+12 0.201650E+12 338593.66   187505.38 0.84



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.440289E+11 0.439491E+11 116951.15 18-JAN-05:13 84598.81 0.46
February 0.00 0.00 0.474030E+11 0.472764E+11 130333.11 25-FEB-05:12 85711.75 0.52
March 0.00 0.00 0.678125E+11 0.675578E+11 135673.05 20-MAR-04:12 86694.41 0.56
April 0.00 0.00 0.818129E+11 0.798180E+11 156480.62 27-APR-03:02 94254.40 0.53
May 0.00 0.00 0.105525E+12 0.937693E+11 185790.19 22-MAY-03:02 87514.86 0.61
June 0.00 0.00 0.125198E+12 0.977406E+11 199669.37 25-JUN-19:27 90646.77 0.63
July 0.00 0.00 0.146851E+12 0.971864E+11 213117.75 23-JUL-23:50 84498.02 0.63
August 0.00 0.00 0.164941E+12 0.105388E+12 223867.90 27-AUG-10:48 86750.25 0.68
September 0.00 0.00 0.127329E+12 0.885290E+11 209764.21 17-SEP-21:27 94111.96 0.64
October 0.00 0.00 0.905265E+11 0.838899E+11 168455.69 01-OCT-11:41 105640.55 0.61
November 0.00 0.00 0.683667E+11 0.680050E+11 138856.76 09-NOV-05:12 85369.01 0.57
December 0.00 0.00 0.527948E+11 0.527349E+11 109200.79 30-DEC-05:13 81629.30 0.46
                 
Annual Sum or Average 0.00 0.00 0.112259E+13 0.925845E+12       0.57
Minimum of Months 0.00 0.00 0.440289E+11 0.439491E+11 109200.79   81629.30 0.46
Maximum of Months 0.00 0.00 0.164941E+12 0.105388E+12 223867.90   105640.55 0.68



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.335268E+12 0.321697E+12 130508.74 17-JAN-16:20 123732.89 0.00
February 0.00 0.00 0.531318E+12 0.514330E+12 224178.32 24-FEB-17:00 218140.63 0.00
March 0.00 0.00 0.834477E+12 0.820158E+12 395281.95 31-MAR-23:03 392157.57 0.00
April 0.00 0.00 0.103342E+13 0.102706E+13 409066.44 25-APR-04:53 401465.92 0.00
May 0.00 0.00 0.361731E+12 0.344718E+12 225823.51 31-MAY-23:05 211801.11 0.00
June 0.00 0.00 0.597570E+12 0.571696E+12 317953.23 30-JUN-23:03 305984.61 0.00
July 0.00 0.00 0.873059E+12 0.836318E+12 401001.85 31-JUL-24:00 389506.85 0.00
August 0.00 0.00 0.109826E+13 0.106262E+13 420506.11 10-AUG-14:00 400784.64 0.00
September 0.00 0.00 0.365274E+12 0.333871E+12 227444.94 30-SEP-23:05 212762.59 0.00
October 0.00 0.00 0.600609E+12 0.584074E+12 310344.57 31-OCT-24:00 301701.76 0.00
November 0.00 0.00 0.816197E+12 0.796345E+12 320839.21 24-NOV-08:25 306852.50 0.00
December 0.00 0.00 0.109737E+13 0.106223E+13 421149.57 22-DEC-06:15 395642.80 0.00
                 
Annual Sum or Average 0.00 0.00 0.854455E+13 0.827512E+13       0.00
Minimum of Months 0.00 0.00 0.335268E+12 0.321697E+12 130508.74   123732.89 0.00
Maximum of Months 0.00 0.00 0.109826E+13 0.106262E+13 421149.57   401465.92 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.453401E+10 0.437769E+10 2336.35 12-JAN-17:00 2202.75 0.00
February 0.00 0.00 0.934998E+10 0.910825E+10 4436.29 20-FEB-17:15 4436.29 0.00
March 0.00 0.00 0.161103E+11 0.157589E+11 7802.50 31-MAR-24:00 7694.76 0.00
April 0.00 0.00 0.210210E+11 0.206940E+11 8640.74 17-APR-01:13 8380.17 0.00
May 0.00 0.00 0.723299E+10 0.655128E+10 4656.70 31-MAY-23:05 4031.62 0.00
June 0.00 0.00 0.123428E+11 0.112404E+11 6602.69 30-JUN-23:03 6079.39 0.00
July 0.00 0.00 0.182133E+11 0.165809E+11 8670.85 31-JUL-23:03 7858.67 0.00
August 0.00 0.00 0.229890E+11 0.212699E+11 8835.60 10-AUG-14:00 8000.51 0.00
September 0.00 0.00 0.727660E+10 0.599135E+10 4652.66 30-SEP-23:05 4019.11 0.00
October 0.00 0.00 0.116569E+11 0.110190E+11 5954.14 31-OCT-23:10 5693.44 0.00
November 0.00 0.00 0.154365E+11 0.151068E+11 6485.14 05-NOV-16:50 6342.29 0.00
December 0.00 0.00 0.202750E+11 0.200876E+11 8100.90 28-DEC-17:00 7932.44 0.00
                 
Annual Sum or Average 0.00 0.00 0.166438E+12 0.157786E+12       0.00
Minimum of Months 0.00 0.00 0.453401E+10 0.437769E+10 2336.35   2202.75 0.00
Maximum of Months 0.00 0.00 0.229890E+11 0.212699E+11 8835.60   8380.17 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.287218E+11 0.273559E+11 21263.00 12-JAN-17:00 19951.89 0.00
February 0.00 0.00 0.819238E+11 0.795393E+11 41589.04 22-FEB-17:00 39995.68 0.00
March 0.00 0.00 0.151806E+12 0.148301E+12 75136.07 31-MAR-24:00 74051.39 0.00
April 0.00 0.00 0.199249E+12 0.195966E+12 81476.98 16-APR-20:53 78833.18 0.00
May 0.00 0.00 0.685033E+11 0.617602E+11 44993.49 31-MAY-23:05 38584.08 0.00
June 0.00 0.00 0.117874E+12 0.106906E+12 63822.80 30-JUN-23:03 58545.60 0.00
July 0.00 0.00 0.173703E+12 0.157426E+12 83032.81 31-JUL-23:03 74883.03 0.00
August 0.00 0.00 0.218286E+12 0.201048E+12 84266.38 10-AUG-14:00 75953.24 0.00
September 0.00 0.00 0.682600E+11 0.555738E+11 45177.29 30-SEP-23:05 38730.37 0.00
October 0.00 0.00 0.109706E+12 0.103375E+12 56392.60 31-OCT-23:10 53719.98 0.00
November 0.00 0.00 0.142714E+12 0.139429E+12 61589.23 08-NOV-17:00 58831.99 0.00
December 0.00 0.00 0.182368E+12 0.180491E+12 76581.55 28-DEC-17:00 74903.88 0.00
                 
Annual Sum or Average 0.00 0.00 0.154311E+13 0.145717E+13       0.00
Minimum of Months 0.00 0.00 0.287218E+11 0.273559E+11 21263.00   19951.89 0.00
Maximum of Months 0.00 0.00 0.218286E+12 0.201048E+12 84266.38   78833.18 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.177393E+10 0.166683E+10 2157.38 12-JAN-17:00 2023.99 0.00
February 0.00 0.00 0.754898E+10 0.731431E+10 4216.00 22-FEB-17:00 4056.51 0.00
March 0.00 0.00 0.150159E+11 0.146666E+11 7471.75 31-MAR-24:00 7363.80 0.00
April 0.00 0.00 0.200146E+11 0.196877E+11 8307.59 16-APR-20:53 8046.43 0.00
May 0.00 0.00 0.708036E+10 0.640281E+10 4448.99 31-MAY-23:05 3805.41 0.00
June 0.00 0.00 0.119956E+11 0.108972E+11 6447.59 30-JUN-23:03 5920.60 0.00
July 0.00 0.00 0.175867E+11 0.159584E+11 8389.52 31-JUL-23:03 7570.37 0.00
August 0.00 0.00 0.219831E+11 0.202604E+11 8510.15 20-AUG-16:54 7839.71 0.00
September 0.00 0.00 0.693031E+10 0.565863E+10 4545.56 30-SEP-23:05 3908.75 0.00
October 0.00 0.00 0.109010E+11 0.102695E+11 5530.47 31-OCT-23:10 5262.42 0.00
November 0.00 0.00 0.137791E+11 0.134526E+11 6210.26 08-NOV-16:50 5943.03 0.00
December 0.00 0.00 0.170781E+11 0.168919E+11 7686.38 28-DEC-17:00 7518.84 0.00
                 
Annual Sum or Average 0.00 0.00 0.151688E+12 0.143127E+12       0.00
Minimum of Months 0.00 0.00 0.177393E+10 0.166683E+10 2157.38   2023.99 0.00
Maximum of Months 0.00 0.00 0.219831E+11 0.202604E+11 8510.15   8046.43 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 12627.65 1288499.06 02-JAN-06:03
February 0.00 0.00 01-FEB-00:10 2140.16 1010040.54 11-FEB-06:02
March 0.00 0.00 01-MAR-00:10 0.26 243.77 01-MAR-06:40
April 0.00 0.00 01-APR-00:05 0.00 0.00 01-APR-00:05
May 0.00 0.00 01-MAY-00:05 0.00 7.39 16-MAY-15:40
June 0.00 0.00 01-JUN-00:05 0.00 0.00 01-JUN-00:05
July 0.00 0.00 01-JUL-00:03 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:05 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:05 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:05 0.00 0.00 01-OCT-00:05
November 0.00 0.00 01-NOV-00:10 78.63 41480.05 27-NOV-06:03
December 0.00 0.00 01-DEC-00:10 3781.81 739319.10 23-DEC-06:02
             
Annual Sum or Average 0.00     1564.34    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   12627.65 1288499.06  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 107080.31 711194.87 25-JAN-14:05 0.00 0.00 01-JAN-00:10
February 210548.54 1233548.16 22-FEB-15:30 0.00 0.00 01-FEB-00:10
March 447965.62 1874783.57 30-MAR-12:05 0.00 0.00 01-MAR-00:10
April 756316.71 2064478.88 10-APR-13:05 0.00 0.00 01-APR-00:05
May 1042067.40 2936654.86 07-MAY-15:01 0.00 0.00 01-MAY-00:05
June 1215550.43 3572072.58 10-JUN-17:42 0.00 0.00 01-JUN-00:05
July 1289720.98 3816790.47 05-JUL-05:03 0.00 0.00 01-JUL-00:03
August 1280536.12 3735344.26 29-AUG-05:03 0.00 0.00 01-AUG-00:05
September 1029887.66 3317374.01 12-SEP-05:02 0.00 0.00 01-SEP-00:05
October 624195.50 2400745.67 12-OCT-05:03 0.00 0.00 01-OCT-00:05
November 361141.91 1925512.04 09-NOV-11:05 0.00 0.00 01-NOV-00:10
December 149107.97 803290.15 01-DEC-15:05 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 712173.02     0.00    
Minimum of Months 107080.31 711194.87   0.00 0.00  
Maximum of Months 1289720.98 3816790.47   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 104993.66 792341.96 25-JAN-14:05 0.00 0.00 01-JAN-00:10
February 208434.10 1416517.87 25-FEB-06:03 0.00 0.00 01-FEB-00:10
March 445643.80 3469070.37 11-MAR-06:02 0.00 0.00 01-MAR-00:10
April 752494.84 3876691.17 26-APR-05:02 0.00 0.00 01-APR-00:05
May 1036812.75 4196496.99 24-MAY-05:02 0.00 0.00 01-MAY-00:05
June 1210545.16 4353360.12 14-JUN-03:12 0.00 0.00 01-JUN-00:05
July 1282358.39 4613684.32 02-JUL-19:02 0.00 0.00 01-JUL-00:03
August 1275624.05 4646094.24 07-AUG-03:01 0.00 0.00 01-AUG-00:05
September 1024433.69 4341492.53 09-SEP-05:03 0.00 0.00 01-SEP-00:05
October 621988.09 3971558.54 04-OCT-05:02 0.00 0.00 01-OCT-00:05
November 358905.75 2016055.48 13-NOV-14:40 0.00 0.00 01-NOV-00:10
December 146888.59 928259.39 01-DEC-06:03 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 708414.05     0.00    
Minimum of Months 104993.66 792341.96   0.00 0.00  
Maximum of Months 1282358.39 4646094.24   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 210136.47 567196.02 12-JAN-15:00 0.00 0.00 01-JAN-00:10
February 482627.44 993815.52 22-FEB-15:00 0.00 0.00 01-FEB-00:10
March 941036.42 1724021.97 28-MAR-15:20 0.00 0.00 01-MAR-00:10
April 1551416.45 2182048.03 15-APR-15:00 0.00 0.00 01-APR-00:05
May 1106715.59 1758143.05 01-MAY-15:00 0.00 0.00 01-MAY-00:05
June 1389230.55 2032189.40 08-JUN-16:00 0.00 0.00 01-JUN-00:05
July 1523850.65 2049854.76 02-JUL-16:10 0.00 0.00 01-JUL-00:03
August 1632462.93 2044784.96 07-AUG-15:00 0.00 0.00 01-AUG-00:05
September 885994.73 1383538.69 17-SEP-20:00 0.00 0.00 01-SEP-00:05
October 886350.37 1548640.37 02-OCT-15:00 0.00 0.00 01-OCT-00:05
November 797827.65 1391037.94 08-NOV-15:00 0.00 0.00 01-NOV-00:10
December 761886.97 1286420.62 28-DEC-14:20 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 1016940.47     0.00    
Minimum of Months 210136.47 567196.02   0.00 0.00  
Maximum of Months 1632462.93 2182048.03   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 12726.83 41925.33 17-JAN-12:50
February 0.00 0.00 01-FEB-00:10 12555.06 41684.72 01-FEB-12:50
March 0.00 0.00 01-MAR-00:10 12449.31 39948.99 01-MAR-12:10
April 0.00 0.00 01-APR-00:05 10696.37 36257.81 03-APR-11:50
May 0.00 0.00 01-MAY-00:05 9895.56 32605.57 01-MAY-11:30
June 0.00 0.00 01-JUN-00:05 9207.39 28960.37 01-JUN-11:20
July 0.00 0.00 01-JUL-00:03 8252.91 26816.19 03-JUL-11:40
August 0.00 0.00 01-AUG-00:05 9171.40 28568.77 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 9457.62 31748.73 29-SEP-11:50
October 0.00 0.00 01-OCT-00:05 10503.62 35909.65 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 11719.75 39406.78 30-NOV-12:50
December 0.00 0.00 01-DEC-00:10 12136.03 41505.26 29-DEC-12:30
             
Annual Sum or Average 0.00     10721.04    
Minimum of Months 0.00 0.00   8252.91 26816.19  
Maximum of Months 0.00 0.00   12726.83 41925.33  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 120325.73 802964.60 25-JAN-14:10 4728.12 139193.94 04-JAN-07:40
February 244609.50 1397100.02 22-FEB-15:40 1774.62 126871.27 03-FEB-06:40
March 561159.24 2800336.28 10-MAR-17:00 486.97 57843.10 19-MAR-23:55
April 1130464.16 4913064.53 18-APR-14:05 555.64 66922.25 11-APR-03:00
May 2347528.72 6560909.26 17-MAY-15:40 0.00 0.00 01-MAY-00:05
June 3432823.20 7573858.79 22-JUN-15:40 0.00 0.00 01-JUN-00:05
July 4199729.64 7515947.03 08-JUL-05:05 0.00 0.00 01-JUL-00:03
August 4225748.51 7386168.22 28-AUG-14:40 0.00 0.00 01-AUG-00:05
September 3051709.30 7087701.71 14-SEP-15:30 0.00 0.00 01-SEP-00:05
October 961309.57 4507009.89 04-OCT-12:10 104.11 27548.28 23-OCT-03:40
November 425744.38 2638828.86 09-NOV-14:05 451.75 98592.41 26-NOV-21:00
December 169158.68 916035.83 01-DEC-15:05 2910.60 141154.54 20-DEC-06:40
             
Annual Sum or Average 1748507.01     917.90    
Minimum of Months 120325.73 802964.60   0.00 0.00  
Maximum of Months 4225748.51 7573858.79   4728.12 141154.54  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.134409E+11 0.80 8876.58 01-JAN-00:15 1.42
February 0.121994E+11 0.80 8876.58 01-FEB-05:13 1.42
March 0.138972E+11 0.83 8876.58 01-MAR-05:12 1.42
April 0.135117E+11 0.83 8876.58 01-APR-04:12 1.42
May 0.146625E+11 0.87 8876.58 01-MAY-00:23 1.42
June 0.147020E+11 0.90 8876.58 01-JUN-03:02 1.41
July 0.151172E+11 0.89 8876.58 01-JUL-03:03 1.41
August 0.162755E+11 0.96 8876.58 01-AUG-03:02 1.41
September 0.150080E+11 0.92 8876.58 01-SEP-03:03 1.41
October 0.150344E+11 0.89 8876.58 01-OCT-11:41 1.41
November 0.142891E+11 0.88 8876.58 01-NOV-04:12 1.42
December 0.138293E+11 0.82 8876.58 01-DEC-05:12 1.42
           
Annual Sum or Average 0.171967E+12 0.87      
Minimum of Months 0.121994E+11 0.80 8876.58   1.41
Maximum of Months 0.162755E+11 0.96 8876.58   1.42



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.391407E+10 0.32 7961.21 26-JAN-06:02 0.98
February 0.522690E+10 0.39 11964.52 23-FEB-06:02 1.25
March 0.946609E+10 0.54 21346.56 11-MAR-06:02 1.80
April 0.134989E+11 0.72 21346.56 03-APR-04:21 1.80
May 0.132022E+11 0.70 21346.56 01-MAY-03:02 1.81
June 0.141782E+11 0.74 21346.56 02-JUN-05:02 1.80
July 0.140997E+11 0.73 21346.56 01-JUL-05:03 1.80
August 0.170835E+11 0.80 21346.56 01-AUG-05:02 1.80
September 0.100720E+11 0.61 21346.56 02-SEP-05:02 1.80
October 0.944320E+10 0.55 21346.56 02-OCT-04:12 1.80
November 0.754624E+10 0.46 14416.12 06-NOV-05:12 1.41
December 0.600676E+10 0.39 10123.04 28-DEC-06:02 1.13
           
Annual Sum or Average 0.123738E+12 0.58      
Minimum of Months 0.391407E+10 0.32 7961.21   0.98
Maximum of Months 0.170835E+11 0.80 21346.56   1.81



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.262364E+11 0.29 85161.69 21-JAN-06:02 1.05
February 0.333258E+11 0.33 73006.11 01-FEB-06:02 0.96
March 0.642926E+11 0.43 204502.63 11-MAR-06:02 1.80
April 0.932548E+11 0.58 204502.63 05-APR-05:02 1.81
May 0.115764E+12 0.66 204502.63 01-MAY-05:03 1.80
June 0.114869E+12 0.66 204502.63 05-JUN-05:02 1.80
July 0.101255E+12 0.60 204502.63 03-JUL-05:01 1.80
August 0.100944E+12 0.59 204502.63 01-AUG-05:02 1.80
September 0.810168E+11 0.52 204502.63 05-SEP-05:02 1.80
October 0.692302E+11 0.45 204502.63 02-OCT-04:12 1.80
November 0.464012E+11 0.37 100549.81 01-NOV-05:02 1.15
December 0.302479E+11 0.30 83391.59 21-DEC-06:03 1.04
           
Annual Sum or Average 0.876838E+12 0.48      
Minimum of Months 0.262364E+11 0.29 73006.11   0.96
Maximum of Months 0.115764E+12 0.66 204502.63   1.81



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.263776E+10 0.32 4445.26 02-JAN-05:11 0.67
February 0.299692E+10 0.33 6901.90 22-FEB-15:30 0.85
March 0.606505E+10 0.40 18040.99 29-MAR-04:12 1.51
April 0.996811E+10 0.57 23484.33 26-APR-05:02 1.79
May 0.127795E+11 0.66 23484.33 16-MAY-05:02 1.79
June 0.127965E+11 0.66 23484.33 12-JUN-04:22 1.79
July 0.109110E+11 0.60 23484.33 13-JUL-05:02 1.79
August 0.104954E+11 0.58 23484.33 12-AUG-05:02 1.79
September 0.834671E+10 0.51 23484.33 18-SEP-04:12 1.79
October 0.668655E+10 0.43 23484.33 02-OCT-04:12 1.79
November 0.410701E+10 0.35 8217.32 09-NOV-15:50 0.94
December 0.266713E+10 0.31 4133.73 01-DEC-15:00 0.65
           
Annual Sum or Average 0.904577E+11 0.48      
Minimum of Months 0.263776E+10 0.31 4133.73   0.65
Maximum of Months 0.127965E+11 0.66 23484.33   1.79



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.965198E+11 1.38 36036.38 01-JAN-00:10 1.38
February 0.871792E+11 1.38 36036.38 01-FEB-00:10 1.38
March 0.965198E+11 1.38 36036.38 01-MAR-00:10 1.38
April 0.934063E+11 1.38 36036.38 01-APR-00:05 1.38
May 0.965198E+11 1.38 36036.38 01-MAY-00:05 1.38
June 0.934063E+11 1.38 36036.38 01-JUN-00:05 1.38
July 0.965198E+11 1.38 36036.38 01-JUL-00:03 1.38
August 0.965198E+11 1.38 36036.38 01-AUG-00:05 1.38
September 0.934063E+11 1.38 36036.38 01-SEP-00:05 1.38
October 0.965198E+11 1.38 36036.38 01-OCT-00:05 1.38
November 0.934063E+11 1.38 36036.38 01-NOV-00:10 1.38
December 0.965198E+11 1.38 36036.38 01-DEC-00:10 1.38
           
Annual Sum or Average 0.113644E+13 1.38      
Minimum of Months 0.871792E+11 1.38 36036.38   1.38
Maximum of Months 0.965198E+11 1.38 36036.38   1.38



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.143616E+10 0.94 536.20 01-JAN-00:10 0.94
February 0.129718E+10 0.94 536.20 01-FEB-00:10 0.94
March 0.143616E+10 0.94 536.20 01-MAR-00:10 0.94
April 0.138983E+10 0.94 536.20 01-APR-00:05 0.94
May 0.143616E+10 0.93 536.20 01-MAY-00:05 0.94
June 0.138983E+10 0.93 536.20 01-JUN-00:05 0.94
July 0.143616E+10 0.93 536.20 01-JUL-00:03 0.94
August 0.143616E+10 0.93 536.20 01-AUG-00:05 0.94
September 0.138983E+10 0.93 536.20 01-SEP-00:05 0.93
October 0.143616E+10 0.94 536.20 01-OCT-00:05 0.94
November 0.138983E+10 0.94 536.20 01-NOV-00:10 0.94
December 0.143616E+10 0.94 536.20 01-DEC-00:10 0.94
           
Annual Sum or Average 0.169096E+11 0.94      
Minimum of Months 0.129718E+10 0.93 536.20   0.93
Maximum of Months 0.143616E+10 0.94 536.20   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137129E+11 0.94 5119.81 01-JAN-00:10 0.94
February 0.123858E+11 0.94 5119.81 01-FEB-00:10 0.94
March 0.137129E+11 0.94 5119.81 01-MAR-00:10 0.94
April 0.132705E+11 0.94 5119.81 01-APR-00:05 0.94
May 0.137129E+11 0.93 5119.81 01-MAY-00:05 0.94
June 0.132705E+11 0.93 5119.81 01-JUN-00:05 0.94
July 0.137129E+11 0.93 5119.81 01-JUL-00:03 0.94
August 0.137129E+11 0.93 5119.81 01-AUG-00:05 0.94
September 0.132705E+11 0.93 5119.81 01-SEP-00:05 0.93
October 0.137129E+11 0.94 5119.81 01-OCT-00:05 0.94
November 0.132705E+11 0.94 5119.81 01-NOV-00:10 0.94
December 0.137129E+11 0.94 5119.81 01-DEC-00:10 0.94
           
Annual Sum or Average 0.161458E+12 0.94      
Minimum of Months 0.123858E+11 0.93 5119.81   0.93
Maximum of Months 0.137129E+11 0.94 5119.81   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138690E+10 0.94 517.81 01-JAN-00:10 0.94
February 0.125268E+10 0.94 517.81 01-FEB-00:10 0.94
March 0.138690E+10 0.94 517.81 01-MAR-00:10 0.94
April 0.134216E+10 0.94 517.81 01-APR-00:05 0.94
May 0.138690E+10 0.93 517.81 01-MAY-00:05 0.94
June 0.134216E+10 0.93 517.81 01-JUN-00:05 0.94
July 0.138690E+10 0.93 517.81 01-JUL-00:03 0.94
August 0.138690E+10 0.93 517.81 01-AUG-00:05 0.94
September 0.134216E+10 0.93 517.81 01-SEP-00:05 0.93
October 0.138690E+10 0.94 517.81 01-OCT-00:05 0.94
November 0.134216E+10 0.94 517.81 01-NOV-00:10 0.94
December 0.138690E+10 0.94 517.81 01-DEC-00:10 0.94
           
Annual Sum or Average 0.163296E+11 0.94      
Minimum of Months 0.125268E+10 0.93 517.81   0.93
Maximum of Months 0.138690E+10 0.94 517.81   0.94



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.427807E+09 0.388876E+09 7909.13 02-JAN-06:03 7189.40 7189.40 47.17 24.02
February 61563294.60 55961034.79 6503.88 11-FEB-06:02 5912.02 5912.02 40.06 12.12
March 5430.02 4935.89 1.88 01-MAR-06:40 1.71 1.71 29.88 0.00
April 0.00 0.00 0.00 01-APR-00:05 0.00 0.00 29.84 0.00
May 34.23 31.11 0.06 16-MAY-15:40 0.05 0.05 29.84 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00 0.00 29.84 0.00
July 0.00 0.00 0.00 01-JUL-00:03 0.00 0.00 29.84 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00 0.00 29.84 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00 0.00 29.84 0.00
October 0.00 0.00 0.00 01-OCT-00:05 0.00 0.00 29.84 0.00
November 1628381.01 1480198.34 315.94 27-NOV-06:03 287.19 287.19 29.91 0.33
December 0.117360E+09 0.106680E+09 5839.73 23-DEC-06:02 5308.31 5308.31 41.52 9.57
                 
Annual Sum or Average 0.608363E+09 0.553002E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 29.84 0.00
Maximum of Months 0.427807E+09 0.388876E+09 7909.13   7189.40 7189.40 47.17 24.02



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 88089692.40 80073530.39 778.26 12-JAN-06:02 707.44 707.44 6.70 23.88
February 0.240341E+09 0.218470E+09 1582.56 25-FEB-06:03 1438.55 1438.55 6.71 32.86
March 0.726114E+09 0.660038E+09 12328.52 11-MAR-06:02 11206.62 11206.62 9.73 76.82
April 0.139780E+10 0.127060E+10 12603.46 15-APR-05:02 11456.54 11456.54 9.49 77.50
May 0.197331E+10 0.179374E+10 12603.46 01-MAY-05:01 11456.54 11456.54 9.13 77.50
June 0.229497E+10 0.208613E+10 12603.46 02-JUN-05:02 11456.54 11456.54 10.04 77.50
July 0.242078E+10 0.220049E+10 12603.46 02-JUL-18:22 11456.54 11456.54 10.44 77.50
August 0.247274E+10 0.224772E+10 12603.46 01-AUG-05:02 11456.54 11456.54 10.49 77.50
September 0.173349E+10 0.157574E+10 12603.46 02-SEP-05:02 11456.54 11456.54 10.45 77.50
October 0.112442E+10 0.102210E+10 12603.46 02-OCT-04:12 11456.54 11456.54 9.63 77.50
November 0.635871E+09 0.578006E+09 3565.47 13-NOV-14:40 3241.02 3241.02 9.05 46.52
December 0.157200E+09 0.142895E+09 1071.40 01-DEC-06:03 973.90 973.90 6.70 27.63
                 
Annual Sum or Average 0.152651E+11 0.138760E+11            
Minimum of Months 88089692.40 80073530.39 778.26   707.44 707.44 6.70 23.88
Maximum of Months 0.247274E+10 0.224772E+10 12603.46   11456.54 11456.54 10.49 77.50



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.635281E+10 0.577470E+10 4337.31 01-JAN-00:15 3942.61 3942.61 6.80 38.75
February 0.626585E+10 0.569566E+10 4337.31 01-FEB-05:13 3942.61 3942.61 7.07 38.75
March 0.864079E+10 0.785447E+10 4337.31 01-MAR-05:12 3942.61 3942.61 7.86 38.75
April 0.105292E+11 0.957109E+10 4337.31 01-APR-00:20 3942.61 3942.61 6.87 38.75
May 0.106855E+11 0.971309E+10 4337.31 01-MAY-00:05 3942.61 3942.61 9.82 38.75
June 0.105122E+11 0.955561E+10 4337.31 01-JUN-00:05 3942.61 3942.61 7.06 38.75
July 0.108266E+11 0.984142E+10 4337.31 01-JUL-00:03 3942.61 3942.61 9.65 38.75
August 0.110310E+11 0.100272E+11 4337.31 01-AUG-00:05 3942.61 3942.61 13.13 38.75
September 0.987714E+10 0.897832E+10 4337.31 01-SEP-00:05 3942.61 3942.61 9.09 38.75
October 0.918078E+10 0.834533E+10 4337.31 01-OCT-00:05 3942.61 3942.61 7.25 38.75
November 0.747535E+10 0.679509E+10 4337.31 01-NOV-04:12 3942.61 3942.61 10.78 38.75
December 0.688184E+10 0.625559E+10 4337.31 01-DEC-05:12 3942.61 3942.61 7.76 38.75
                 
Annual Sum or Average 0.108259E+12 0.984076E+11            
Minimum of Months 0.626585E+10 0.569566E+10 4337.31   3942.61 3942.61 6.80 38.75
Maximum of Months 0.110310E+11 0.100272E+11 4337.31   3942.61 3942.61 13.13 38.75



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00 6.80 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 6.81 0.00
March 0.746885E+09 0.678918E+09 4337.31 06-MAR-13:30 3942.61 3942.61 15.17 19.38
April 0.271815E+10 0.247080E+10 4337.31 03-APR-08:20 3942.61 3942.61 15.11 19.38
May 0.484351E+10 0.440275E+10 4337.31 01-MAY-05:15 3942.61 3942.61 15.35 19.38
June 0.573888E+10 0.521664E+10 4337.31 01-JUN-05:05 3942.61 3942.61 15.95 19.38
July 0.647061E+10 0.588178E+10 4337.31 01-JUL-05:03 3942.61 3942.61 16.14 19.38
August 0.661902E+10 0.601669E+10 4337.31 01-AUG-05:04 3942.61 3942.61 16.72 19.38
September 0.495494E+10 0.450404E+10 4337.31 01-SEP-05:03 3942.61 3942.61 14.39 38.75
October 0.212823E+10 0.193456E+10 4337.31 02-OCT-07:50 3942.61 3942.61 15.28 19.38
November 0.360430E+09 0.327631E+09 4337.31 01-NOV-13:30 3942.61 3942.61 15.37 19.38
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 7.36 0.00
                 
Annual Sum or Average 0.345807E+11 0.314338E+11            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.80 0.00
Maximum of Months 0.661902E+10 0.601669E+10 4337.31   3942.61 3942.61 16.72 38.75



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.933604E+10 0.848646E+10 3485.68 01-JAN-00:10 3168.48 3168.48 21.37 14.70
February 0.843255E+10 0.766519E+10 3485.68 01-FEB-00:10 3168.48 3168.48 24.03 14.70
March 0.933604E+10 0.848646E+10 3485.68 01-MAR-00:10 3168.48 3168.48 28.23 14.70
April 0.903488E+10 0.821270E+10 3485.68 01-APR-00:05 3168.48 3168.48 41.80 14.70
May 0.933604E+10 0.848646E+10 3485.68 01-MAY-00:05 3168.48 3168.48 37.62 14.70
June 0.903488E+10 0.821270E+10 3485.68 01-JUN-00:05 3168.48 3168.48 38.60 14.70
July 0.933604E+10 0.848646E+10 3485.68 01-JUL-00:03 3168.48 3168.48 48.46 14.70
August 0.933604E+10 0.848646E+10 3485.68 01-AUG-00:05 3168.48 3168.48 48.47 14.70
September 0.903488E+10 0.821270E+10 3485.68 01-SEP-00:05 3168.48 3168.48 36.04 14.70
October 0.933604E+10 0.848646E+10 3485.68 01-OCT-00:05 3168.48 3168.48 37.03 14.70
November 0.903488E+10 0.821270E+10 3485.68 01-NOV-00:10 3168.48 3168.48 31.41 14.70
December 0.933604E+10 0.848646E+10 3485.68 01-DEC-00:10 3168.48 3168.48 29.62 14.70
                 
Annual Sum or Average 0.109924E+12 0.999212E+11            
Minimum of Months 0.843255E+10 0.766519E+10 3485.68   3168.48 3168.48 21.37 14.70
Maximum of Months 0.933604E+10 0.848646E+10 3485.68   3168.48 3168.48 48.47 14.70



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 56.33 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:02 16.86 16.86 56.63 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:02 16.86 16.86 56.50 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:03 16.86 16.86 56.91 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:01 16.86 16.86 57.82 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 56.69 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 58.03 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 56.98 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 58.04 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:05 16.86 16.86 57.14 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:02 16.86 16.86 56.52 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:03 16.86 16.86 56.24 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 56.24 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 58.04 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.241712E+11 0.219716E+11 16527.53 25-JAN-14:10 15023.53 15023.53 23.95 67.51
February 0.238523E+11 0.216817E+11 16554.69 22-FEB-15:40 15048.21 15048.21 26.05 67.51
March 0.352337E+11 0.320274E+11 33109.73 10-MAR-17:00 30096.75 30096.75 26.06 135.02
April 0.493356E+11 0.448461E+11 33186.11 17-APR-10:30 30166.17 30166.17 28.91 135.02
May 0.579448E+11 0.526718E+11 33186.11 01-MAY-14:40 30166.17 30166.17 28.91 135.02
June 0.608378E+11 0.553015E+11 33186.11 05-JUN-13:50 30166.17 30166.17 28.82 135.02
July 0.644851E+11 0.586169E+11 33186.11 01-JUL-06:30 30166.17 30166.17 29.08 135.02
August 0.662162E+11 0.601905E+11 33186.11 01-AUG-05:04 30166.17 30166.17 28.90 135.02
September 0.550027E+11 0.499975E+11 33186.11 01-SEP-05:03 30166.17 30166.17 32.27 135.02
October 0.416034E+11 0.378175E+11 33186.11 04-OCT-10:50 30166.17 30166.17 28.93 135.02
November 0.296267E+11 0.269307E+11 33101.79 09-NOV-14:05 30089.53 30089.53 25.78 135.02
December 0.261887E+11 0.238055E+11 16532.30 01-DEC-15:05 15027.86 15027.86 24.35 67.51
                 
Annual Sum or Average 0.534498E+12 0.485859E+12            
Minimum of Months 0.238523E+11 0.216817E+11 16527.53   15023.53 15023.53 23.95 67.51
Maximum of Months 0.662162E+11 0.601905E+11 33186.11   30166.17 30166.17 32.27 135.02



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 47.86 47.86 12627.65 1288499.06 02-JAN-06:03
February 0.00 0.00 01-FEB-00:10 42.26 42.26 2140.16 1010040.54 11-FEB-06:02
March 0.00 0.00 01-MAR-00:10 29.88 29.88 0.26 243.77 01-MAR-06:40
April 0.00 0.00 01-APR-00:05 29.84 29.84 0.00 0.00 01-APR-00:05
May 0.00 0.00 01-MAY-00:05 29.84 29.84 0.00 7.39 16-MAY-15:40
June 0.00 0.00 01-JUN-00:05 29.84 29.84 0.00 0.00 01-JUN-00:05
July 0.00 0.00 01-JUL-00:03 29.84 29.84 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:05 29.84 29.84 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:05 29.84 29.84 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:05 29.84 29.84 0.00 0.00 01-OCT-00:05
November 0.00 0.00 01-NOV-00:10 29.84 29.84 78.63 41480.05 27-NOV-06:03
December 0.00 0.00 01-DEC-00:10 32.46 32.46 3781.81 739319.10 23-DEC-06:02
                 
Annual Sum or Average 0.00         1564.34    
Minimum of Months 0.00 0.00   29.84 29.84 0.00 0.00  
Maximum of Months 0.00 0.00   47.86 47.86 12627.65 1288499.06  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 107080.31 711194.87 25-JAN-14:05 11.08 6.70 0.00 0.00 01-JAN-00:10
February 210548.54 1233548.16 22-FEB-15:30 14.30 6.70 0.00 0.00 01-FEB-00:10
March 447965.62 1874783.57 30-MAR-12:05 12.48 6.70 0.00 0.00 01-MAR-00:10
April 756316.71 2064478.88 10-APR-13:05 13.06 6.70 0.00 0.00 01-APR-00:05
May 1042067.40 2936654.86 07-MAY-15:01 15.76 7.25 0.00 0.00 01-MAY-00:05
June 1215550.43 3572072.58 10-JUN-17:42 17.72 9.21 0.00 0.00 01-JUN-00:05
July 1289720.98 3816790.47 05-JUL-05:03 18.48 9.97 0.00 0.00 01-JUL-00:03
August 1280536.12 3735344.26 29-AUG-05:03 18.22 9.72 0.00 0.00 01-AUG-00:05
September 1029887.66 3317374.01 12-SEP-05:02 16.93 8.43 0.00 0.00 01-SEP-00:05
October 624195.50 2400745.67 12-OCT-05:03 14.10 6.70 0.00 0.00 01-OCT-00:05
November 361141.91 1925512.04 09-NOV-11:05 12.63 6.70 0.00 0.00 01-NOV-00:10
December 149107.97 803290.15 01-DEC-15:05 11.65 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 712173.02         0.00    
Minimum of Months 107080.31 711194.87   11.08 6.70 0.00 0.00  
Maximum of Months 1289720.98 3816790.47   18.48 9.97 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 104993.66 792341.96 25-JAN-14:05 17.88 6.70 0.00 0.00 01-JAN-00:10
February 208434.10 1416517.87 25-FEB-06:03 17.00 6.70 0.00 0.00 01-FEB-00:10
March 445643.80 3469070.37 11-MAR-06:02 17.50 12.03 0.00 0.00 01-MAR-00:10
April 752494.84 3876691.17 26-APR-05:02 18.66 12.66 0.00 0.00 01-APR-00:05
May 1036812.75 4196496.99 24-MAY-05:02 19.65 13.15 0.00 0.00 01-MAY-00:05
June 1210545.16 4353360.12 14-JUN-03:12 20.60 13.38 0.00 0.00 01-JUN-00:05
July 1282358.39 4613684.32 02-JUL-19:02 20.94 13.79 0.00 0.00 01-JUL-00:03
August 1275624.05 4646094.24 07-AUG-03:01 21.04 13.84 0.00 0.00 01-AUG-00:05
September 1024433.69 4341492.53 09-SEP-05:03 20.10 13.38 0.00 0.00 01-SEP-00:05
October 621988.09 3971558.54 04-OCT-05:02 18.95 12.81 0.00 0.00 01-OCT-00:05
November 358905.75 2016055.48 13-NOV-14:40 17.06 8.97 0.00 0.00 01-NOV-00:10
December 146888.59 928259.39 01-DEC-06:03 14.73 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 708414.05         0.00    
Minimum of Months 104993.66 792341.96   14.73 6.70 0.00 0.00  
Maximum of Months 1282358.39 4646094.24   21.04 13.84 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 210136.47 567196.02 12-JAN-15:00 29.35 25.49 0.00 0.00 01-JAN-00:10
February 482627.44 993815.52 22-FEB-15:00 37.50 30.54 0.00 0.00 01-FEB-00:10
March 941036.42 1724021.97 28-MAR-15:20 51.15 40.79 0.00 0.00 01-MAR-00:10
April 1551416.45 2182048.03 15-APR-15:00 59.55 46.81 0.00 0.00 01-APR-00:05
May 1106715.59 1758143.05 01-MAY-15:00 51.78 46.74 0.00 0.00 01-MAY-00:05
June 1389230.55 2032189.40 08-JUN-16:00 56.82 48.72 0.00 0.00 01-JUN-00:05
July 1523850.65 2049854.76 02-JUL-16:10 57.14 46.04 0.00 0.00 01-JUL-00:03
August 1632462.93 2044784.96 07-AUG-15:00 57.05 43.96 0.00 0.00 01-AUG-00:05
September 885994.73 1383538.69 17-SEP-20:00 44.83 39.94 0.00 0.00 01-SEP-00:05
October 886350.37 1548640.37 02-OCT-15:00 47.90 40.24 0.00 0.00 01-OCT-00:05
November 797827.65 1391037.94 08-NOV-15:00 44.97 34.92 0.00 0.00 01-NOV-00:10
December 761886.97 1286420.62 28-DEC-14:20 43.01 30.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 1016940.47         0.00    
Minimum of Months 210136.47 567196.02   29.35 25.49 0.00 0.00  
Maximum of Months 1632462.93 2182048.03   59.55 48.72 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 58.07 58.07 12726.83 41925.33 17-JAN-12:50
February 0.00 0.00 01-FEB-00:10 57.09 57.09 12555.06 41684.72 01-FEB-12:50
March 0.00 0.00 01-MAR-00:10 57.02 57.02 12449.31 39948.99 01-MAR-12:10
April 0.00 0.00 01-APR-00:05 57.31 57.31 10696.37 36257.81 03-APR-11:50
May 0.00 0.00 01-MAY-00:05 58.60 58.60 9895.56 32605.57 01-MAY-11:30
June 0.00 0.00 01-JUN-00:05 57.02 57.02 9207.39 28960.37 01-JUN-11:20
July 0.00 0.00 01-JUL-00:03 58.33 58.33 8252.91 26816.19 03-JUL-11:40
August 0.00 0.00 01-AUG-00:05 57.20 57.20 9171.40 28568.77 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 58.33 58.33 9457.62 31748.73 29-SEP-11:50
October 0.00 0.00 01-OCT-00:05 57.57 57.57 10503.62 35909.65 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 57.05 57.05 11719.75 39406.78 30-NOV-12:50
December 0.00 0.00 01-DEC-00:10 56.92 56.92 12136.03 41505.26 29-DEC-12:30
                 
Annual Sum or Average 0.00         10721.04    
Minimum of Months 0.00 0.00   56.92 56.92 8252.91 26816.19  
Maximum of Months 0.00 0.00   58.60 58.60 12726.83 41925.33  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 120325.73 802964.60 25-JAN-14:10 23.95 21.10 4728.12 139193.94 04-JAN-07:40
February 244609.50 1397100.02 22-FEB-15:40 26.05 21.10 1774.62 126871.27 03-FEB-06:40
March 561159.24 2800336.28 10-MAR-17:00 26.06 23.15 486.97 57843.10 19-MAR-23:55
April 1130464.16 4913064.53 18-APR-14:05 29.81 25.76 555.64 66922.25 11-APR-03:00
May 2347528.72 6560909.26 17-MAY-15:40 32.72 28.03 0.00 0.00 01-MAY-00:05
June 3432823.20 7573858.79 22-JUN-15:40 34.52 29.18 0.00 0.00 01-JUN-00:05
July 4199729.64 7515947.03 08-JUL-05:05 34.42 29.14 0.00 0.00 01-JUL-00:03
August 4225748.51 7386168.22 28-AUG-14:40 34.19 29.07 0.00 0.00 01-AUG-00:05
September 3051709.30 7087701.71 14-SEP-15:30 33.66 28.91 0.00 0.00 01-SEP-00:05
October 961309.57 4507009.89 04-OCT-12:10 29.09 25.24 104.11 27548.28 23-OCT-03:40
November 425744.38 2638828.86 09-NOV-14:05 25.78 21.41 451.75 98592.41 26-NOV-21:00
December 169158.68 916035.83 01-DEC-15:05 24.35 21.10 2910.60 141154.54 20-DEC-06:40
                 
Annual Sum or Average 1748507.01         917.90    
Minimum of Months 120325.73 802964.60   23.95 21.10 0.00 0.00  
Maximum of Months 4225748.51 7573858.79   34.52 29.18 4728.12 141154.54  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.902700E+09 0.00 0.319171E+11 0.391407E+10 0.00 0.00
February 0.149356E+09 0.00 0.535232E+11 0.522690E+10 0.00 0.00
March 0.00 0.00 0.113546E+12 0.946609E+10 0.00 0.00
April 0.00 0.00 0.178601E+12 0.134989E+11 0.00 0.00
May 0.00 0.00 0.225418E+12 0.132022E+11 0.00 0.00
June 0.00 0.00 0.264286E+12 0.141782E+11 0.00 0.00
July 0.00 0.00 0.299831E+12 0.140997E+11 0.00 0.00
August 0.00 0.00 0.320001E+12 0.170835E+11 0.00 0.00
September 0.00 0.00 0.225567E+12 0.100720E+11 0.00 0.00
October 0.00 0.00 0.145588E+12 0.944320E+10 0.00 0.00
November 161387.26 0.00 0.906330E+11 0.754624E+10 0.00 0.00
December 0.193873E+09 0.00 0.523929E+11 0.600676E+10 0.00 0.00
             
Annual Sum or Average 0.124609E+10 0.00 0.200130E+13 0.123738E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.319171E+11 0.391407E+10 0.00 0.00
Maximum of Months 0.902700E+09 0.00 0.320001E+12 0.170835E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.250866E+11 0.00 0.190234E+12 0.262364E+11 0.00 0.00
February 0.371252E+10 0.00 0.364762E+12 0.333258E+11 0.00 0.00
March 0.00 0.00 0.867741E+12 0.642926E+11 0.00 0.00
April 0.00 0.00 0.144133E+13 0.932548E+11 0.00 0.00
May 6624.69 0.00 0.213674E+13 0.115764E+12 0.00 0.00
June 0.00 0.00 0.242474E+13 0.114869E+12 0.00 0.00
July 0.00 0.00 0.265104E+13 0.101255E+12 0.00 0.00
August 0.00 0.00 0.260706E+13 0.100944E+12 0.00 0.00
September 0.00 0.00 0.201337E+13 0.810168E+11 0.00 0.00
October 0.00 0.00 0.121258E+13 0.692302E+11 0.00 0.00
November 60615545.40 0.00 0.651527E+12 0.464012E+11 0.00 0.00
December 0.691832E+10 0.00 0.268472E+12 0.302479E+11 0.00 0.00
             
Annual Sum or Average 0.357781E+11 0.00 0.168296E+14 0.876838E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.190234E+12 0.262364E+11 0.00 0.00
Maximum of Months 0.250866E+11 0.00 0.265104E+13 0.115764E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.830580E+10 0.00 0.157661E+11 0.263776E+10 0.00 0.00
February 0.147538E+10 0.00 0.330138E+11 0.299692E+10 0.00 0.00
March 977814.97 0.00 0.882760E+11 0.606505E+10 0.00 0.00
April 0.00 0.00 0.157509E+12 0.996811E+10 0.00 0.00
May 0.00 0.00 0.235545E+12 0.127795E+11 0.00 0.00
June 0.00 0.00 0.264787E+12 0.127965E+11 0.00 0.00
July 0.00 0.00 0.282471E+12 0.109110E+11 0.00 0.00
August 0.00 0.00 0.275267E+12 0.104954E+11 0.00 0.00
September 0.00 0.00 0.209929E+12 0.834671E+10 0.00 0.00
October 0.00 0.00 0.122548E+12 0.668655E+10 0.00 0.00
November 0.124177E+09 0.00 0.599211E+11 0.410701E+10 0.00 0.00
December 0.317351E+10 0.00 0.206692E+11 0.266713E+10 0.00 0.00
             
Annual Sum or Average 0.130798E+11 0.00 0.176570E+13 0.904577E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.157661E+11 0.263776E+10 0.00 0.00
Maximum of Months 0.830580E+10 0.00 0.282471E+12 0.127965E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 98.09 0.00 0.440289E+11 0.134409E+11 0.00 0.00
February 0.00 0.00 0.474030E+11 0.121994E+11 0.00 0.00
March 0.00 0.00 0.678125E+11 0.138972E+11 0.00 0.00
April 0.00 0.00 0.818129E+11 0.135117E+11 0.00 0.00
May 0.00 0.00 0.105525E+12 0.146625E+11 0.00 0.00
June 0.00 0.00 0.125198E+12 0.147020E+11 0.00 0.00
July 0.00 0.00 0.146851E+12 0.151172E+11 0.00 0.00
August 0.00 0.00 0.164941E+12 0.162755E+11 0.00 0.00
September 0.00 0.00 0.127329E+12 0.150080E+11 0.00 0.00
October 0.00 0.00 0.905265E+11 0.150344E+11 0.00 0.00
November 0.00 0.00 0.683667E+11 0.142891E+11 0.00 0.00
December 0.00 0.00 0.527948E+11 0.138293E+11 0.00 0.00
             
Annual Sum or Average 98.09 0.00 0.112259E+13 0.171967E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.440289E+11 0.121994E+11 0.00 0.00
Maximum of Months 98.09 0.00 0.164941E+12 0.162755E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.411197E+12 0.184386E+12 0.00 4.44
February 0.00 0.00 0.654603E+12 0.223656E+12 0.00 4.91
March 0.00 0.00 0.105548E+13 0.324563E+12 0.00 2.62
April 0.00 0.00 0.135428E+13 0.415187E+12 0.00 0.34
May 0.00 0.00 0.491105E+12 0.225910E+12 0.00 0.01
June 0.00 0.00 0.811143E+12 0.306979E+12 0.00 0.00
July 0.00 0.00 0.116806E+13 0.391516E+12 0.00 0.00
August 0.00 0.00 0.143810E+13 0.436361E+12 0.00 0.00
September 0.00 0.00 0.480294E+12 0.208427E+12 0.00 0.00
October 0.00 0.00 0.772628E+12 0.269911E+12 0.00 0.51
November 0.00 0.00 0.101594E+13 0.307115E+12 0.00 5.19
December 0.00 0.00 0.133226E+13 0.366425E+12 0.00 13.03
             
Annual Sum or Average 0.00 0.00 0.109851E+14 0.366044E+13 0.00 31.05
Minimum of Months 0.00 0.00 0.411197E+12 0.184386E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.143810E+13 0.436361E+12 0.00 13.03



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.558423E+10 0.248638E+10 0.00 0.00
February 0.00 0.00 0.115306E+11 0.347777E+10 0.00 0.00
March 0.00 0.00 0.203459E+11 0.567172E+10 0.00 0.00
April 0.00 0.00 0.276119E+11 0.798074E+10 0.00 0.00
May 0.00 0.00 0.974968E+10 0.395284E+10 0.00 0.00
June 0.00 0.00 0.166194E+11 0.566642E+10 0.00 0.00
July 0.00 0.00 0.241786E+11 0.740149E+10 0.00 0.00
August 0.00 0.00 0.301455E+11 0.859265E+10 0.00 0.00
September 0.00 0.00 0.947791E+10 0.359115E+10 0.00 0.00
October 0.00 0.00 0.149402E+11 0.471945E+10 0.00 0.00
November 0.00 0.00 0.192068E+11 0.516016E+10 0.00 0.00
December 0.00 0.00 0.246603E+11 0.582141E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.214051E+12 0.645222E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.558423E+10 0.248638E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.301455E+11 0.859265E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.355994E+11 0.205905E+11 0.00 0.00
February 0.00 0.00 0.101236E+12 0.316977E+11 0.00 0.00
March 0.00 0.00 0.191835E+12 0.537419E+11 0.00 0.00
April 0.00 0.00 0.261871E+12 0.758920E+11 0.00 0.00
May 0.00 0.00 0.923472E+11 0.375568E+11 0.00 0.00
June 0.00 0.00 0.158691E+12 0.540881E+11 0.00 0.00
July 0.00 0.00 0.230559E+12 0.705692E+11 0.00 0.00
August 0.00 0.00 0.286480E+12 0.819071E+11 0.00 0.00
September 0.00 0.00 0.889046E+11 0.339151E+11 0.00 0.00
October 0.00 0.00 0.140666E+12 0.446729E+11 0.00 0.00
November 0.00 0.00 0.177769E+12 0.483260E+11 0.00 0.00
December 0.00 0.00 0.222199E+12 0.535441E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.198816E+13 0.606501E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.355994E+11 0.205905E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.286480E+12 0.819071E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.221299E+10 0.182595E+10 0.00 0.00
February 0.00 0.00 0.935078E+10 0.305448E+10 0.00 0.00
March 0.00 0.00 0.189936E+11 0.536455E+10 0.00 0.00
April 0.00 0.00 0.263110E+11 0.763857E+10 0.00 0.00
May 0.00 0.00 0.954627E+10 0.385281E+10 0.00 0.00
June 0.00 0.00 0.161516E+11 0.549820E+10 0.00 0.00
July 0.00 0.00 0.233459E+11 0.714611E+10 0.00 0.00
August 0.00 0.00 0.288547E+11 0.825843E+10 0.00 0.00
September 0.00 0.00 0.902896E+10 0.344081E+10 0.00 0.00
October 0.00 0.00 0.139895E+11 0.447535E+10 0.00 0.00
November 0.00 0.00 0.171918E+11 0.475486E+10 0.00 0.00
December 0.00 0.00 0.208515E+11 0.516022E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.195829E+12 0.604704E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.221299E+10 0.182595E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.288547E+11 0.825843E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.391407E+10 0.319171E+11 0.902700E+09 0.00 0.00 0.00 0.00 0.00
February 0.522690E+10 0.535232E+11 0.149356E+09 0.00 0.00 0.00 0.00 0.00
March 0.946609E+10 0.113546E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134989E+11 0.178601E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132022E+11 0.225418E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141782E+11 0.264286E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140997E+11 0.299831E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170835E+11 0.320001E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.100720E+11 0.225567E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.944320E+10 0.145588E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.754624E+10 0.906330E+11 161387.26 0.00 0.00 0.00 0.00 0.00
December 0.600676E+10 0.523929E+11 0.193873E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.123738E+12 0.200130E+13 0.124609E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.391407E+10 0.319171E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170835E+11 0.320001E+12 0.902700E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.262364E+11 0.190234E+12 0.250866E+11 0.00 0.00 0.00 0.00 0.00
February 0.333258E+11 0.364762E+12 0.371252E+10 0.00 0.00 0.00 0.00 0.00
March 0.642926E+11 0.867741E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.932548E+11 0.144133E+13 0.00 0.00 0.00 0.00 0.00 0.00
May 0.115764E+12 0.213674E+13 6624.69 0.00 0.00 0.00 0.00 0.00
June 0.114869E+12 0.242474E+13 0.00 0.00 0.00 0.00 0.00 0.00
July 0.101255E+12 0.265104E+13 0.00 0.00 0.00 0.00 0.00 0.00
August 0.100944E+12 0.260706E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.810168E+11 0.201337E+13 0.00 0.00 0.00 0.00 0.00 0.00
October 0.692302E+11 0.121258E+13 0.00 0.00 0.00 0.00 0.00 0.00
November 0.464012E+11 0.651527E+12 60615545.40 0.00 0.00 0.00 0.00 0.00
December 0.302479E+11 0.268472E+12 0.691832E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.876838E+12 0.168296E+14 0.357781E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.262364E+11 0.190234E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.115764E+12 0.265104E+13 0.250866E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.263776E+10 0.157661E+11 0.830580E+10 0.00 0.00 0.00 0.00 0.00
February 0.299692E+10 0.330138E+11 0.147538E+10 0.00 0.00 0.00 0.00 0.00
March 0.606505E+10 0.882760E+11 977814.97 0.00 0.00 0.00 0.00 0.00
April 0.996811E+10 0.157509E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.127795E+11 0.235545E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.127965E+11 0.264787E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109110E+11 0.282471E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.104954E+11 0.275267E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.834671E+10 0.209929E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.668655E+10 0.122548E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.410701E+10 0.599211E+11 0.124177E+09 0.00 0.00 0.00 0.00 0.00
December 0.266713E+10 0.206692E+11 0.317351E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.904577E+11 0.176570E+13 0.130798E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.263776E+10 0.157661E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127965E+11 0.282471E+12 0.830580E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.134409E+11 0.440289E+11 98.09 0.00 0.00 0.00 0.00 0.00
February 0.121994E+11 0.474030E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138972E+11 0.678125E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135117E+11 0.818129E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.146625E+11 0.105525E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.147020E+11 0.125198E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.151172E+11 0.146851E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.162755E+11 0.164941E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.150080E+11 0.127329E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.150344E+11 0.905265E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142891E+11 0.683667E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138293E+11 0.527948E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.171967E+12 0.112259E+13 98.09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121994E+11 0.440289E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162755E+11 0.164941E+12 98.09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.965198E+11 0.335268E+12 0.00 0.00 0.00 0.118844E+11 0.00 0.00
February 0.871792E+11 0.531318E+12 0.00 0.00 0.00 0.131322E+11 0.00 0.00
March 0.965198E+11 0.834477E+12 0.00 0.00 0.00 0.700612E+10 0.00 0.00
April 0.934063E+11 0.103342E+13 0.00 0.00 0.00 0.915851E+09 0.00 0.00
May 0.965198E+11 0.361731E+12 0.00 0.00 0.00 15721260.28 0.00 0.00
June 0.934063E+11 0.597570E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.965198E+11 0.873059E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.965198E+11 0.109826E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.934063E+11 0.365274E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.965198E+11 0.600609E+12 0.00 0.00 0.00 0.136631E+10 0.00 0.00
November 0.934063E+11 0.816197E+12 0.00 0.00 0.00 0.139023E+11 0.00 0.00
December 0.965198E+11 0.109737E+13 0.00 0.00 0.00 0.348585E+11 0.00 0.00
                 
Annual Sum or Average 0.113644E+13 0.854455E+13 0.00 0.00 0.00 0.830815E+11 0.00 0.00
Minimum of Months 0.871792E+11 0.335268E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.965198E+11 0.109826E+13 0.00 0.00 0.00 0.348585E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.143616E+10 0.453401E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129718E+10 0.934998E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143616E+10 0.161103E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138983E+10 0.210210E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143616E+10 0.723299E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138983E+10 0.123428E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143616E+10 0.182133E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143616E+10 0.229890E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.138983E+10 0.727660E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143616E+10 0.116569E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138983E+10 0.154365E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143616E+10 0.202750E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169096E+11 0.166438E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129718E+10 0.453401E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143616E+10 0.229890E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.137129E+11 0.287218E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.123858E+11 0.819238E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137129E+11 0.151806E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132705E+11 0.199249E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137129E+11 0.685033E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132705E+11 0.117874E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137129E+11 0.173703E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137129E+11 0.218286E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132705E+11 0.682600E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137129E+11 0.109706E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132705E+11 0.142714E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137129E+11 0.182368E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161458E+12 0.154311E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.123858E+11 0.287218E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137129E+11 0.218286E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.138690E+10 0.177393E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125268E+10 0.754898E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138690E+10 0.150159E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134216E+10 0.200146E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138690E+10 0.708036E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134216E+10 0.119956E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138690E+10 0.175867E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138690E+10 0.219831E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134216E+10 0.693031E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138690E+10 0.109010E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134216E+10 0.137791E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138690E+10 0.170781E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163296E+11 0.151688E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125268E+10 0.177393E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138690E+10 0.219831E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.391407E+10 0.902700E+09 0.319171E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.522690E+10 0.149356E+09 0.535232E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.946609E+10 0.00 0.113546E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134989E+11 0.00 0.178601E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132022E+11 0.00 0.225418E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141782E+11 0.00 0.264286E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140997E+11 0.00 0.299831E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170835E+11 0.00 0.320001E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.100720E+11 0.00 0.225567E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.944320E+10 0.00 0.145588E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.754624E+10 161387.26 0.906330E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.600676E+10 0.193873E+09 0.523929E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.123738E+12 0.124609E+10 0.200130E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.391407E+10 0.00 0.319171E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170835E+11 0.902700E+09 0.320001E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.262364E+11 0.250866E+11 0.190234E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.333258E+11 0.371252E+10 0.364762E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.642926E+11 0.00 0.867741E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.932548E+11 0.00 0.144133E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.115764E+12 6624.69 0.213674E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.114869E+12 0.00 0.242474E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.101255E+12 0.00 0.265104E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.100944E+12 0.00 0.260706E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.810168E+11 0.00 0.201337E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.692302E+11 0.00 0.121258E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.464012E+11 60615545.40 0.651527E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.302479E+11 0.691832E+10 0.268472E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.876838E+12 0.357781E+11 0.168296E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.262364E+11 0.00 0.190234E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.115764E+12 0.250866E+11 0.265104E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.263776E+10 0.830580E+10 0.157661E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.299692E+10 0.147538E+10 0.330138E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.606505E+10 977814.97 0.882760E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.996811E+10 0.00 0.157509E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.127795E+11 0.00 0.235545E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.127965E+11 0.00 0.264787E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.109110E+11 0.00 0.282471E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.104954E+11 0.00 0.275267E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.834671E+10 0.00 0.209929E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.668655E+10 0.00 0.122548E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.410701E+10 0.124177E+09 0.599211E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.266713E+10 0.317351E+10 0.206692E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.904577E+11 0.130798E+11 0.176570E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.263776E+10 0.00 0.157661E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127965E+11 0.830580E+10 0.282471E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.134409E+11 98.09 0.440289E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121994E+11 0.00 0.474030E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138972E+11 0.00 0.678125E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135117E+11 0.00 0.818129E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.146625E+11 0.00 0.105525E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.147020E+11 0.00 0.125198E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.151172E+11 0.00 0.146851E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.162755E+11 0.00 0.164941E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.150080E+11 0.00 0.127329E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.150344E+11 0.00 0.905265E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142891E+11 0.00 0.683667E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138293E+11 0.00 0.527948E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.171967E+12 98.09 0.112259E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121994E+11 0.00 0.440289E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162755E+11 98.09 0.164941E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.965198E+11 0.00 0.411197E+12 0.00 0.759286E+11 0.00 0.00 0.00 0.119379E+11 0.00 0.00 0.00
February 0.871792E+11 0.00 0.654603E+12 0.00 0.123285E+12 0.00 0.00 0.00 0.131913E+11 0.00 0.00 0.00
March 0.965198E+11 0.00 0.105548E+13 0.00 0.221005E+12 0.00 0.00 0.00 0.703766E+10 0.00 0.00 0.00
April 0.934063E+11 0.00 0.135428E+13 0.00 0.320861E+12 0.00 0.00 0.00 0.919973E+09 0.00 0.00 0.00
May 0.965198E+11 0.00 0.491105E+12 0.00 0.129374E+12 0.00 0.00 0.00 15792028.04 0.00 0.00 0.00
June 0.934063E+11 0.00 0.811143E+12 0.00 0.213573E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.965198E+11 0.00 0.116806E+13 0.00 0.294996E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.965198E+11 0.00 0.143810E+13 0.00 0.339841E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.934063E+11 0.00 0.480294E+12 0.00 0.115021E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.965198E+11 0.00 0.772628E+12 0.00 0.172019E+12 0.00 0.00 0.00 0.137246E+10 0.00 0.00 0.00
November 0.934063E+11 0.00 0.101594E+13 0.00 0.199744E+12 0.00 0.00 0.00 0.139649E+11 0.00 0.00 0.00
December 0.965198E+11 0.00 0.133226E+13 0.00 0.234890E+12 0.00 0.00 0.00 0.350155E+11 0.00 0.00 0.00
                         
Annual Sum or Average 0.113644E+13 0.00 0.109851E+14 0.00 0.244054E+13 0.00 0.00 0.00 0.834554E+11 0.00 0.00 0.00
Minimum of Months 0.871792E+11 0.00 0.411197E+12 0.00 0.759286E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.965198E+11 0.00 0.143810E+13 0.00 0.339841E+12 0.00 0.00 0.00 0.350155E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.143616E+10 0.00 0.558423E+10 0.00 0.105022E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129718E+10 0.00 0.115306E+11 0.00 0.218060E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143616E+10 0.00 0.203459E+11 0.00 0.423556E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138983E+10 0.00 0.276119E+11 0.00 0.659091E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143616E+10 0.00 0.974968E+10 0.00 0.251669E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138983E+10 0.00 0.166194E+11 0.00 0.427659E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143616E+10 0.00 0.241786E+11 0.00 0.596533E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143616E+10 0.00 0.301455E+11 0.00 0.715650E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.138983E+10 0.00 0.947791E+10 0.00 0.220132E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143616E+10 0.00 0.149402E+11 0.00 0.328329E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138983E+10 0.00 0.192068E+11 0.00 0.377033E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143616E+10 0.00 0.246603E+11 0.00 0.438525E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.169096E+11 0.00 0.214051E+12 0.00 0.476126E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129718E+10 0.00 0.558423E+10 0.00 0.105022E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143616E+10 0.00 0.301455E+11 0.00 0.715650E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.137129E+11 0.00 0.355994E+11 0.00 0.687761E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.123858E+11 0.00 0.101236E+12 0.00 0.193119E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137129E+11 0.00 0.191835E+12 0.00 0.400290E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132705E+11 0.00 0.261871E+12 0.00 0.626214E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137129E+11 0.00 0.923472E+11 0.00 0.238439E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132705E+11 0.00 0.158691E+12 0.00 0.408175E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137129E+11 0.00 0.230559E+12 0.00 0.568563E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137129E+11 0.00 0.286480E+12 0.00 0.681942E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132705E+11 0.00 0.889046E+11 0.00 0.206446E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137129E+11 0.00 0.140666E+12 0.00 0.309600E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132705E+11 0.00 0.177769E+12 0.00 0.350554E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137129E+11 0.00 0.222199E+12 0.00 0.398312E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.161458E+12 0.00 0.198816E+13 0.00 0.445043E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.123858E+11 0.00 0.355994E+11 0.00 0.687761E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137129E+11 0.00 0.286480E+12 0.00 0.681942E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.138690E+10 0.00 0.221299E+10 0.00 0.439057E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125268E+10 0.00 0.935078E+10 0.00 0.180180E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138690E+10 0.00 0.189936E+11 0.00 0.397765E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134216E+10 0.00 0.263110E+11 0.00 0.629641E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138690E+10 0.00 0.954627E+10 0.00 0.246591E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134216E+10 0.00 0.161516E+11 0.00 0.415604E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138690E+10 0.00 0.233459E+11 0.00 0.575921E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138690E+10 0.00 0.288547E+11 0.00 0.687154E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134216E+10 0.00 0.902896E+10 0.00 0.209865E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138690E+10 0.00 0.139895E+11 0.00 0.308845E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134216E+10 0.00 0.171918E+11 0.00 0.341270E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138690E+10 0.00 0.208515E+11 0.00 0.377332E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.163296E+11 0.00 0.195829E+12 0.00 0.441408E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125268E+10 0.00 0.221299E+10 0.00 0.439057E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138690E+10 0.00 0.288547E+11 0.00 0.687154E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.155315E+10 0.00 0.00 0.106020E+09 0.00 0.00 0.241774E+11 0.00 0.37
February 0.674785E+09 0.00 0.00 98320064.89 0.00 0.00 0.154585E+11 0.00 0.37
March 0.161051E+09 0.149743E+10 0.00 89129788.14 27319790.93 0.00 0.779154E+10 0.00 0.38
April 29737731.51 0.107458E+11 0.00 21971816.41 0.277563E+09 0.00 0.491954E+09 0.00 0.39
May 3789360.25 0.295750E+11 0.00 3215226.95 0.531141E+09 0.00 45677107.21 0.00 0.41
June 0.00 0.461083E+11 0.00 189782.73 0.862448E+09 0.00 90412.72 0.00 0.43
July 0.00 0.636415E+11 0.00 0.00 0.157757E+10 0.00 0.00 0.00 0.43
August 0.00 0.711519E+11 0.00 0.00 0.117067E+10 0.00 0.00 0.00 0.46
September 0.00 0.457752E+11 0.00 0.00 0.104968E+10 0.00 0.00 0.00 0.43
October 0.240643E+09 0.864800E+10 0.00 56484461.98 0.128237E+09 0.00 0.256715E+10 0.00 0.42
November 0.105727E+10 0.232349E+09 0.00 0.129842E+09 22561878.12 0.00 0.121298E+11 0.00 0.41
December 0.113434E+10 0.00 0.00 0.121210E+09 0.00 0.00 0.226910E+11 0.00 0.38
                   
Annual Sum or Average 0.485476E+10 0.277375E+12 0.00 0.626384E+09 0.564720E+10 0.00 0.853532E+11 0.00 0.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.37
Maximum of Months 0.155315E+10 0.711519E+11 0.00 0.129842E+09 0.157757E+10 0.00 0.241774E+11 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109142E+10 0.00 0.00 69526039.33 0.00 0.00 0.246667E+11 0.00 0.37
February 0.110872E+10 0.00 0.00 77617307.52 1368158.18 0.00 0.164013E+11 0.00 0.38
March 0.165288E+10 0.104389E+10 0.00 85354273.23 0.359776E+09 0.00 0.873985E+10 0.00 0.40
April 0.809848E+09 0.646478E+10 0.00 25952340.91 0.351851E+10 0.00 0.818737E+09 0.00 0.44
May 28614291.41 0.220657E+11 0.00 734169.34 0.106807E+11 0.00 16836660.56 0.00 0.43
June 0.00 0.337057E+11 0.00 0.00 0.191766E+11 0.00 0.00 0.00 0.43
July 0.00 0.438227E+11 0.00 0.00 0.317855E+11 0.00 0.00 0.00 0.45
August 0.00 0.501080E+11 0.00 0.00 0.283227E+11 0.00 0.00 0.00 0.45
September 0.00 0.336898E+11 0.00 0.00 0.197200E+11 0.00 0.00 0.00 0.42
October 0.712429E+09 0.709576E+10 0.00 34308560.45 0.180288E+10 0.00 0.245997E+10 0.00 0.40
November 0.144654E+10 0.155123E+09 0.00 96385886.57 73982751.53 0.00 0.125314E+11 0.00 0.38
December 0.145186E+10 0.00 0.00 94248808.73 0.00 0.00 0.240139E+11 0.00 0.40
                   
Annual Sum or Average 0.830231E+10 0.198151E+12 0.00 0.484127E+09 0.115442E+12 0.00 0.896487E+11 0.00 0.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.37
Maximum of Months 0.165288E+10 0.501080E+11 0.00 96385886.57 0.317855E+11 0.00 0.246667E+11 0.00 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103859E+12 0.00 0.00 0.260397E+09 0.00 37416143.13 0.102239E+12 0.00 0.32
February 0.286548E+11 0.00 0.00 0.453572E+09 83586523.10 0.00 0.116377E+12 0.00 0.35
March 0.610182E+10 0.104227E+11 0.00 0.649286E+09 0.357973E+10 0.00 0.796301E+11 0.00 0.35
April 0.247693E+10 0.611295E+11 0.00 0.187727E+09 0.361934E+11 0.00 0.662005E+10 0.00 0.39
May 0.275044E+09 0.212133E+12 0.00 4426429.88 0.103550E+12 0.00 0.120946E+09 0.00 0.42
June 0.00 0.321288E+12 0.00 0.00 0.171500E+12 0.00 0.00 0.00 0.41
July 0.00 0.408409E+12 0.00 0.00 0.274456E+12 0.00 0.00 0.00 0.41
August 0.00 0.465458E+12 0.00 0.00 0.215582E+12 0.00 0.00 0.00 0.40
September 0.00 0.326205E+12 0.00 0.00 0.145014E+12 0.00 0.00 0.00 0.37
October 0.248750E+10 0.685997E+11 0.00 0.269561E+09 0.142805E+11 0.00 0.231796E+11 0.00 0.35
November 0.103253E+11 0.140381E+10 0.00 0.637997E+09 0.106456E+10 0.00 0.103647E+12 0.00 0.35
December 0.576678E+11 0.00 0.00 0.389678E+09 40668642.08 0.00 0.137436E+12 0.00 0.34
                   
Annual Sum or Average 0.211848E+12 0.187505E+13 0.00 0.285264E+10 0.965345E+12 37416143.13 0.569249E+12 0.00 0.37
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.32
Maximum of Months 0.103859E+12 0.465458E+12 0.00 0.649286E+09 0.274456E+12 37416143.13 0.137436E+12 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.141806E+11 0.00 0.00 8264180.38 0.00 0.477230E+09 0.352479E+10 0.00 0.31
February 0.624919E+10 0.00 0.00 26144870.84 1824941.16 0.00 0.626512E+10 0.00 0.32
March 0.125773E+10 0.752130E+09 0.00 54613769.00 0.220270E+09 0.00 0.645816E+10 0.00 0.34
April 0.233099E+09 0.545418E+10 0.00 23192122.73 0.314671E+10 0.00 0.706111E+09 0.00 0.38
May 21849611.70 0.209007E+11 0.00 450902.31 0.929613E+10 0.00 12090861.73 0.00 0.42
June 0.00 0.321315E+11 0.00 0.00 0.160721E+11 0.00 0.00 0.00 0.41
July 0.00 0.411018E+11 0.00 0.00 0.262967E+11 0.00 0.00 0.00 0.41
August 0.00 0.465317E+11 0.00 0.00 0.208722E+11 0.00 0.00 0.00 0.40
September 0.00 0.322663E+11 0.00 0.00 0.140112E+11 0.00 0.00 0.00 0.37
October 0.346661E+09 0.613368E+10 0.00 22864923.57 0.117279E+10 0.00 0.172398E+10 0.00 0.34
November 0.330445E+10 41515360.25 0.00 43956610.61 68255678.76 0.00 0.617211E+10 0.00 0.32
December 0.112101E+11 0.00 0.00 14107258.37 985896.79 1911961.25 0.498653E+10 0.00 0.31
                   
Annual Sum or Average 0.368037E+11 0.185314E+12 0.00 0.193595E+09 0.911591E+11 0.479142E+09 0.298489E+11 0.00 0.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.141806E+11 0.465317E+11 0.00 54613769.00 0.262967E+11 0.477230E+09 0.645816E+10 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.185509E+10 0.00 0.00 1702278.71 0.00 0.00 0.458486E+09 0.00 0.26
February 0.863945E+09 0.00 0.00 4815297.74 171388.43 0.00 0.749472E+09 0.00 0.29
March 0.340476E+09 0.208541E+09 0.00 9059614.59 41554136.20 0.00 0.802189E+09 0.00 0.42
April 0.105268E+09 0.166349E+10 0.00 4216142.96 0.316210E+09 0.00 0.109669E+09 0.00 0.60
May 2893426.76 0.644127E+10 0.00 274700.89 0.845338E+09 0.00 5047956.49 0.00 0.72
June 0.00 0.101347E+11 0.00 0.00 0.145745E+10 0.00 0.00 0.00 0.75
July 0.00 0.132802E+11 0.00 0.00 0.211245E+10 0.00 0.00 0.00 0.71
August 0.00 0.124911E+11 0.00 0.00 0.245886E+10 0.00 0.00 0.00 0.68
September 0.00 0.739832E+10 0.00 0.00 0.211308E+10 0.00 0.00 0.00 0.59
October 0.113934E+09 0.129436E+10 0.00 3195986.56 0.206008E+09 0.00 0.209594E+09 0.00 0.45
November 0.483831E+09 24094540.72 0.00 7618190.34 9267778.84 0.00 0.762529E+09 0.00 0.31
December 0.133388E+10 0.00 0.00 3875709.54 0.00 0.00 0.710939E+09 0.00 0.26
                   
Annual Sum or Average 0.509932E+10 0.529361E+11 0.00 34757921.34 0.956038E+10 0.00 0.380793E+10 0.00 0.51
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.26
Maximum of Months 0.185509E+10 0.132802E+11 0.00 9059614.59 0.245886E+10 0.00 0.802189E+09 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.907315E+09 0.00 0.00 2936872.92 0.00 0.00 0.865189E+09 0.00 0.32
February 0.440944E+09 0.00 0.00 5486227.60 110598.17 0.00 0.931144E+09 0.00 0.38
March 0.212924E+09 0.170949E+09 0.00 8817402.67 20947726.96 0.00 0.768840E+09 0.00 0.54
April 61712274.94 0.140021E+10 0.00 4252648.01 0.185615E+09 0.00 0.114764E+09 0.00 0.75
May 1792709.21 0.543386E+10 0.00 205066.30 0.462376E+09 0.00 3659867.90 0.00 0.92
June 0.00 0.743384E+10 0.00 0.00 0.902815E+09 0.00 0.00 0.00 0.84
July 0.00 0.891693E+10 0.00 0.00 0.148716E+10 0.00 0.00 0.00 0.75
August 0.00 0.768967E+10 0.00 0.00 0.177191E+10 0.00 0.00 0.00 0.67
September 0.00 0.560327E+10 0.00 0.00 0.130039E+10 0.00 0.00 0.00 0.67
October 67686701.65 0.104628E+10 0.00 3458178.16 0.109988E+09 0.00 0.202329E+09 0.00 0.56
November 0.293199E+09 18225389.00 0.00 7153526.60 5980563.76 0.00 0.721530E+09 0.00 0.39
December 0.795885E+09 0.00 0.00 3685291.47 0.00 0.00 0.705023E+09 0.00 0.30
                   
Annual Sum or Average 0.278146E+10 0.377132E+11 0.00 35995213.75 0.624729E+10 0.00 0.431248E+10 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.907315E+09 0.891693E+10 0.00 8817402.67 0.177191E+10 0.00 0.931144E+09 0.00 0.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103635E+10 0.00 0.00 11525427.79 0.00 6134907.89 0.310062E+10 0.00 0.53
February 0.592477E+09 338654.02 0.00 15759260.96 20512.51 0.00 0.215188E+10 0.00 0.56
March 0.268988E+09 0.400703E+09 0.00 16417688.30 18131064.07 0.00 0.139218E+10 0.00 0.65
April 98895308.29 0.228057E+10 0.00 5712414.74 0.222126E+09 0.00 0.139734E+09 0.00 0.74
May 2901731.66 0.689993E+10 0.00 291269.10 0.784415E+09 0.00 5164476.33 0.00 0.76
June 0.00 0.101012E+11 0.00 0.00 0.145127E+10 0.00 0.00 0.00 0.74
July 0.00 0.133675E+11 0.00 0.00 0.211826E+10 0.00 0.00 0.00 0.72
August 0.00 0.132399E+11 0.00 0.00 0.237579E+10 0.00 0.00 0.00 0.70
September 0.00 0.973584E+10 0.00 0.00 0.171239E+10 0.00 0.00 0.00 0.71
October 83251551.58 0.240167E+10 0.00 8831958.91 0.104155E+09 0.00 0.378906E+09 0.00 0.76
November 0.262296E+09 75764482.41 0.00 27621309.01 2426274.72 0.00 0.215219E+10 0.00 0.69
December 0.718566E+09 0.00 0.00 16430676.44 0.00 0.00 0.303563E+10 0.00 0.55
                   
Annual Sum or Average 0.306372E+10 0.585035E+11 0.00 0.102590E+09 0.878899E+10 6134907.89 0.123563E+11 0.00 0.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.103635E+10 0.133675E+11 0.00 27621309.01 0.237579E+10 6134907.89 0.310062E+10 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.612671E+09 0.00 0.00 5238971.06 0.00 0.00 0.154081E+10 0.00 0.42
February 0.183980E+09 349638.50 0.00 10095999.41 6093.28 0.00 0.167700E+10 0.00 0.58
March 73551429.47 0.354119E+09 0.00 15937132.65 2812681.07 0.00 0.150143E+10 0.00 0.89
April 8767680.99 0.281685E+10 0.00 8977633.16 17203781.88 0.00 0.262814E+09 0.00 1.32
May 158765.95 0.723359E+10 0.00 407723.02 0.141855E+09 0.00 7328959.87 0.00 1.13
June 0.00 0.117413E+11 0.00 0.00 0.272063E+09 0.00 0.00 0.00 1.21
July 0.00 0.157869E+11 0.00 0.00 0.253324E+09 0.00 0.00 0.00 1.16
August 0.00 0.180027E+11 0.00 0.00 0.177597E+09 0.00 0.00 0.00 1.28
September 0.00 0.869990E+10 0.00 0.00 0.522269E+09 0.00 0.00 0.00 0.89
October 38619296.92 0.169181E+10 0.00 5973314.54 35645387.20 0.00 0.340891E+09 0.00 0.81
November 77545694.76 49736787.28 0.00 16210250.01 685227.00 0.00 0.169917E+10 0.00 0.71
December 0.124302E+09 0.00 0.00 12628276.35 0.00 0.00 0.290209E+10 0.00 0.65
                   
Annual Sum or Average 0.111960E+10 0.663773E+11 0.00 75469300.20 0.142346E+10 0.00 0.993154E+10 0.00 0.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.612671E+09 0.180027E+11 0.00 16210250.01 0.522269E+09 0.00 0.290209E+10 0.00 1.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.177225E+11 0.00 0.00 967350.35 0.00 0.566667E+10 0.312639E+09 0.00 0.29
February 0.112764E+11 0.00 0.00 17449952.95 10478596.57 0.972313E+09 0.275609E+10 0.00 0.29
March 0.368369E+10 0.222773E+10 0.00 59771799.54 0.434667E+09 0.00 0.566017E+10 0.00 0.37
April 0.330844E+09 0.180026E+11 0.00 29678154.94 0.358446E+10 0.00 0.920472E+09 0.00 0.60
May 24482610.62 0.716125E+11 0.00 2541013.35 0.733648E+10 0.00 54136566.72 0.00 0.78
June 0.00 0.113123E+12 0.00 0.00 0.111536E+11 0.00 0.00 0.00 0.80
July 0.00 0.145393E+12 0.00 0.00 0.164319E+11 0.00 0.00 0.00 0.76
August 0.00 0.135938E+12 0.00 0.00 0.173151E+11 0.00 0.00 0.00 0.70
September 0.00 0.792946E+11 0.00 0.00 0.145607E+11 0.00 0.00 0.00 0.58
October 0.119465E+10 0.131721E+11 0.00 21158931.08 0.166031E+10 0.00 0.134274E+10 0.00 0.41
November 0.811537E+10 0.200829E+09 0.00 36511256.84 0.129896E+09 0.00 0.321988E+10 0.00 0.30
December 0.184697E+11 0.00 0.00 2047882.96 5098313.43 0.137962E+10 0.693093E+09 0.00 0.28
                   
Annual Sum or Average 0.608176E+11 0.578964E+12 0.00 0.170126E+09 0.726227E+11 0.801860E+10 0.149592E+11 0.00 0.51
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.184697E+11 0.145393E+12 0.00 59771799.54 0.173151E+11 0.566667E+10 0.566017E+10 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.871291E+10 0.00 0.00 9415675.11 0.00 0.205653E+10 0.321754E+10 0.00 0.26
February 0.484366E+10 0.00 0.00 36746135.58 6769059.55 0.142617E+09 0.709340E+10 0.00 0.37
March 0.148616E+10 0.216060E+10 0.00 79341614.81 0.183493E+09 0.00 0.813081E+10 0.00 0.58
April 0.118134E+09 0.182633E+11 0.00 39791270.38 0.157486E+10 0.00 0.124946E+10 0.00 0.88
May 11682217.09 0.629547E+11 0.00 2205748.51 0.304328E+10 0.00 45021592.63 0.00 1.03
June 0.00 0.886070E+11 0.00 0.00 0.535098E+10 0.00 0.00 0.00 0.95
July 0.00 0.109476E+12 0.00 0.00 0.780571E+10 0.00 0.00 0.00 0.85
August 0.00 0.100161E+12 0.00 0.00 0.902482E+10 0.00 0.00 0.00 0.78
September 0.00 0.643057E+11 0.00 0.00 0.742072E+10 0.00 0.00 0.00 0.70
October 0.470620E+09 0.118760E+11 0.00 30349323.91 0.692572E+09 0.00 0.207655E+10 0.00 0.58
November 0.350694E+10 0.193378E+09 0.00 54307731.87 83564854.97 0.00 0.641545E+10 0.00 0.42
December 0.860015E+10 0.00 0.00 15377940.09 3293455.09 0.346337E+09 0.389838E+10 0.00 0.27
                   
Annual Sum or Average 0.277503E+11 0.457998E+12 0.00 0.267535E+09 0.351900E+11 0.254549E+10 0.321266E+11 0.00 0.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.26
Maximum of Months 0.871291E+10 0.109476E+12 0.00 79341614.81 0.902482E+10 0.205653E+10 0.813081E+10 0.00 1.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111840E+11 0.00 0.00 0.100956E+09 0.00 0.104658E+10 0.305152E+11 0.00 0.61
February 0.646452E+10 22968983.55 0.00 0.142446E+09 1115026.58 0.162446E+09 0.218482E+11 0.00 0.66
March 0.218296E+10 0.489433E+10 0.00 0.145874E+09 0.116956E+09 0.00 0.140505E+11 0.00 0.70
April 0.295993E+09 0.262386E+11 0.00 44587209.61 0.247831E+10 0.00 0.125397E+10 0.00 0.78
May 23545730.67 0.765217E+11 0.00 2711693.20 0.655265E+10 0.00 56259444.94 0.00 0.82
June 0.00 0.112123E+12 0.00 0.00 0.111243E+11 0.00 0.00 0.00 0.79
July 0.00 0.147284E+12 0.00 0.00 0.159233E+11 0.00 0.00 0.00 0.76
August 0.00 0.148822E+12 0.00 0.00 0.149499E+11 0.00 0.00 0.00 0.75
September 0.00 0.108836E+12 0.00 0.00 0.989960E+10 0.00 0.00 0.00 0.75
October 0.295897E+09 0.278793E+11 0.00 70863459.36 0.460629E+09 0.00 0.414606E+10 0.00 0.84
November 0.318917E+10 0.100539E+10 0.00 0.262804E+09 26564779.77 0.00 0.230502E+11 0.00 0.86
December 0.886299E+10 7681641.45 0.00 0.133916E+09 279659.39 38539562.85 0.314919E+11 0.00 0.66
                   
Annual Sum or Average 0.324991E+11 0.653635E+12 0.00 0.904159E+09 0.615336E+11 0.124757E+10 0.126412E+12 0.00 0.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
Maximum of Months 0.111840E+11 0.148822E+12 0.00 0.262804E+09 0.159233E+11 0.104658E+10 0.314919E+11 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.108793E+11 0.00 0.00 15319621.56 0.00 0.178726E+10 0.434812E+10 0.00 0.34
February 0.585299E+10 10894683.62 0.00 38469690.40 983218.11 0.112829E+09 0.606884E+10 0.00 0.41
March 0.137903E+10 0.307584E+10 0.00 79870769.82 0.101214E+09 0.00 0.785689E+10 0.00 0.63
April 0.136730E+09 0.228548E+11 0.00 35785617.29 0.690706E+09 0.00 0.102218E+10 0.00 0.98
May 2389727.73 0.715484E+11 0.00 3218030.54 0.138475E+10 0.00 60685586.48 0.00 1.11
June 0.00 0.106668E+12 0.00 0.00 0.262650E+10 0.00 0.00 0.00 1.10
July 0.00 0.125553E+12 0.00 0.00 0.494177E+10 0.00 0.00 0.00 0.94
August 0.00 0.119907E+12 0.00 0.00 0.610320E+10 0.00 0.00 0.00 0.89
September 0.00 0.764147E+11 0.00 0.00 0.507049E+10 0.00 0.00 0.00 0.79
October 0.336176E+09 0.143262E+11 0.00 26182639.53 0.494739E+09 0.00 0.183993E+10 0.00 0.63
November 0.322997E+10 0.389945E+09 0.00 63400334.49 44850481.65 0.00 0.625573E+10 0.00 0.47
December 0.101341E+11 0.00 0.00 21543351.95 3292162.75 0.264370E+09 0.483802E+10 0.00 0.35
                   
Annual Sum or Average 0.319506E+11 0.540748E+12 0.00 0.283790E+09 0.214625E+11 0.216446E+10 0.322904E+11 0.00 0.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.108793E+11 0.125553E+12 0.00 79870769.82 0.610320E+10 0.178726E+10 0.785689E+10 0.00 1.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.135935E+10 0.00 0.00 65248.92 0.00 0.948863E+09 24586801.99 0.00 0.31
February 0.101224E+10 0.00 0.00 1466464.61 229430.12 0.231641E+09 0.220357E+09 0.00 0.30
March 0.360271E+09 0.151646E+09 0.00 5976796.45 25852642.49 0.00 0.565014E+09 0.00 0.36
April 30683553.14 0.149813E+10 0.00 4162775.18 0.295500E+09 0.00 0.115769E+09 0.00 0.57
May 2007795.80 0.654421E+10 0.00 216353.70 0.596627E+09 0.00 4540921.18 0.00 0.75
June 0.00 0.104708E+11 0.00 0.00 0.947815E+09 0.00 0.00 0.00 0.76
July 0.00 0.139035E+11 0.00 0.00 0.139218E+10 0.00 0.00 0.00 0.73
August 0.00 0.130574E+11 0.00 0.00 0.154263E+10 0.00 0.00 0.00 0.68
September 0.00 0.765275E+10 0.00 0.00 0.126781E+10 0.00 0.00 0.00 0.57
October 0.124535E+09 0.112733E+10 0.00 2344891.53 0.141349E+09 0.00 0.114766E+09 0.00 0.40
November 0.766533E+09 6449741.07 0.00 3397428.22 8295344.23 35413340.14 0.273681E+09 0.00 0.30
December 0.135359E+10 0.00 0.00 98037.75 123946.15 0.592585E+09 28562998.00 0.00 0.29
                   
Annual Sum or Average 0.500922E+10 0.544122E+11 0.00 17727996.35 0.621842E+10 0.180850E+10 0.134728E+10 0.00 0.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.135935E+10 0.139035E+11 0.00 5976796.45 0.154263E+10 0.948863E+09 0.565014E+09 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.935265E+09 0.00 0.00 520552.89 0.00 0.370710E+09 0.202518E+09 0.00 0.32
February 0.455681E+09 0.00 0.00 3309829.33 147775.31 95163901.19 0.674802E+09 0.00 0.39
March 0.133502E+09 0.143550E+09 0.00 8366761.16 10735584.14 0.00 0.877473E+09 0.00 0.59
April 9741350.32 0.153504E+10 0.00 5133852.94 0.134534E+09 0.00 0.149528E+09 0.00 0.87
May 679924.18 0.577985E+10 0.00 189385.21 0.251347E+09 0.00 3956531.26 0.00 1.01
June 0.00 0.831263E+10 0.00 0.00 0.461846E+09 0.00 0.00 0.00 0.92
July 0.00 0.105770E+11 0.00 0.00 0.721061E+09 0.00 0.00 0.00 0.84
August 0.00 0.985302E+10 0.00 0.00 0.840594E+09 0.00 0.00 0.00 0.78
September 0.00 0.637908E+10 0.00 0.00 0.639775E+09 0.00 0.00 0.00 0.70
October 54669825.88 0.104986E+10 0.00 3588802.68 65493508.27 0.00 0.196975E+09 0.00 0.59
November 0.328806E+09 7370212.54 0.00 5394257.88 5262426.59 7588436.91 0.635334E+09 0.00 0.43
December 0.797661E+09 0.00 0.00 868518.43 79833.37 0.240666E+09 0.263864E+09 0.00 0.31
                   
Annual Sum or Average 0.271601E+10 0.436374E+11 0.00 27371960.52 0.313088E+10 0.714128E+09 0.300445E+10 0.00 0.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.935265E+09 0.105770E+11 0.00 8366761.16 0.840594E+09 0.370710E+09 0.877473E+09 0.00 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.913048E+09 0.00 0.00 7824719.25 0.00 0.429814E+09 0.254121E+10 0.00 0.57
February 0.584331E+09 456975.25 0.00 12587235.60 0.00 0.107043E+09 0.211323E+10 0.00 0.63
March 0.212686E+09 0.300306E+09 0.00 14960639.46 8980314.17 0.00 0.145958E+10 0.00 0.67
April 26014242.50 0.209140E+10 0.00 6213502.83 0.213061E+09 0.00 0.165025E+09 0.00 0.74
May 1825126.76 0.693237E+10 0.00 231873.87 0.524803E+09 0.00 4801686.98 0.00 0.79
June 0.00 0.103609E+11 0.00 0.00 0.958223E+09 0.00 0.00 0.00 0.76
July 0.00 0.140263E+11 0.00 0.00 0.137397E+10 0.00 0.00 0.00 0.74
August 0.00 0.141310E+11 0.00 0.00 0.139571E+10 0.00 0.00 0.00 0.72
September 0.00 0.102433E+11 0.00 0.00 0.832856E+09 0.00 0.00 0.00 0.72
October 55049026.96 0.224122E+10 0.00 10268439.69 47558834.88 0.00 0.392360E+09 0.00 0.81
November 0.315798E+09 41366141.00 0.00 26590053.50 2349835.10 0.00 0.235257E+10 0.00 0.84
December 0.812969E+09 159849.51 0.00 10358522.13 15529.29 0.190414E+09 0.266870E+10 0.00 0.62
                   
Annual Sum or Average 0.292172E+10 0.603687E+11 0.00 89034986.33 0.535753E+10 0.727271E+09 0.116975E+11 0.00 0.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
Maximum of Months 0.913048E+09 0.141310E+11 0.00 26590053.50 0.139571E+10 0.429814E+09 0.266870E+10 0.00 0.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.839167E+09 0.00 0.00 1250097.95 0.00 0.377683E+09 0.424973E+09 0.00 0.35
February 0.523740E+09 254523.06 0.00 3509266.81 0.00 82763664.47 0.589277E+09 0.00 0.41
March 0.147030E+09 0.197986E+09 0.00 8030698.75 5713176.41 0.00 0.784955E+09 0.00 0.60
April 11035905.49 0.179887E+10 0.00 4957909.62 61652663.48 0.00 0.127374E+09 0.00 0.92
May 170647.07 0.624166E+10 0.00 255787.92 0.132795E+09 0.00 5021967.27 0.00 1.04
June 0.00 0.953236E+10 0.00 0.00 0.249259E+09 0.00 0.00 0.00 1.02
July 0.00 0.116490E+11 0.00 0.00 0.485796E+09 0.00 0.00 0.00 0.90
August 0.00 0.112468E+11 0.00 0.00 0.581799E+09 0.00 0.00 0.00 0.86
September 0.00 0.715743E+10 0.00 0.00 0.447169E+09 0.00 0.00 0.00 0.75
October 51993255.35 0.117848E+10 0.00 3463639.93 42332598.90 0.00 0.149471E+09 0.00 0.61
November 0.338565E+09 16385147.20 0.00 6363797.76 3328704.77 0.00 0.587426E+09 0.00 0.45
December 0.792785E+09 0.00 0.00 1673310.24 79741.35 0.209841E+09 0.447484E+09 0.00 0.35
                   
Annual Sum or Average 0.270449E+10 0.490192E+11 0.00 29504508.98 0.200993E+10 0.670288E+09 0.311598E+10 0.00 0.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 0.839167E+09 0.116490E+11 0.00 8030698.75 0.581799E+09 0.377683E+09 0.784955E+09 0.00 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 7217699.91 0.00 0.00 0.613417E+09 0.00 0.58
February 0.00 6913659.63 0.00 15932584.43 0.00 0.00 0.295136E+09 0.00 0.59
March 0.00 0.115937E+09 0.00 15509329.86 0.00 0.00 0.100415E+09 0.00 0.59
April 0.00 0.343554E+09 0.00 6867988.07 0.00 0.00 8404546.33 0.00 0.59
May 0.00 0.856115E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.129828E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.00 0.177028E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.174998E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
September 0.00 0.126201E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.421765E+09 0.00 1563144.72 0.00 0.00 4885051.59 0.00 0.59
November 0.00 42833246.36 0.00 22098034.42 0.00 0.00 0.153349E+09 0.00 0.59
December 0.00 44704.49 0.00 41149930.67 0.00 0.00 0.489608E+09 0.00 0.58
                   
Annual Sum or Average 0.00 0.786771E+10 0.00 0.110339E+09 0.00 0.00 0.166521E+10 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.00 0.177028E+10 0.00 41149930.67 0.00 0.00 0.613417E+09 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.451942E+09 0.00 0.00 39754709.32 0.00 0.00 0.591056E+10 0.00 0.58
February 0.00 66195913.86 0.00 0.137820E+09 0.00 0.00 0.299700E+10 0.00 0.59
March 0.00 0.115781E+10 0.00 0.145284E+09 0.00 0.00 0.101261E+10 0.00 0.59
April 0.00 0.347568E+10 0.00 65460650.60 0.00 0.00 85451214.10 0.00 0.59
May 0.00 0.850565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.129443E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.00 0.176677E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.176792E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.59
September 0.00 0.124725E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.419248E+10 0.00 14740238.99 0.00 0.00 51671517.64 0.00 0.59
November 0.00 0.426473E+09 0.00 0.202499E+09 0.00 0.00 0.155448E+10 0.00 0.59
December 0.00 425631.23 0.00 0.368460E+09 0.00 0.00 0.493407E+10 0.00 0.58
                   
Annual Sum or Average 0.451942E+09 0.785885E+11 0.00 0.974019E+09 0.00 0.00 0.165458E+11 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.451942E+09 0.176792E+11 0.00 0.368460E+09 0.00 0.00 0.591056E+10 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.282093E+09 0.00 0.00 2054120.31 0.00 0.00 0.372873E+09 0.00 0.58
February 0.00 6423524.43 0.00 12453882.68 0.00 0.00 0.304662E+09 0.00 0.59
March 0.00 0.115295E+09 0.00 14231234.41 0.00 0.00 0.102326E+09 0.00 0.59
April 0.00 0.344419E+09 0.00 6574721.15 0.00 0.00 8638582.54 0.00 0.59
May 0.00 0.852815E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.129532E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.00 0.176717E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.176642E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
September 0.00 0.124972E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.417898E+09 0.00 1423788.65 0.00 0.00 5526721.84 0.00 0.59
November 0.00 42268818.23 0.00 19233144.00 0.00 0.00 0.158055E+09 0.00 0.59
December 0.00 37272.10 0.00 34270128.73 0.00 0.00 0.497571E+09 0.00 0.58
                   
Annual Sum or Average 0.282093E+09 0.785779E+10 0.00 90241019.93 0.00 0.00 0.144965E+10 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.282093E+09 0.176717E+10 0.00 34270128.73 0.00 0.00 0.497571E+09 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.480466E+09 0.00 0.00 0.140113E+11 0.00 0.66
February 0.00 0.162532E+09 0.00 0.836488E+09 0.00 0.00 0.678687E+10 0.00 0.66
March 0.00 0.247934E+10 0.00 0.750532E+09 0.00 0.00 0.214908E+10 0.00 0.66
April 0.00 0.462521E+10 0.00 0.600077E+09 0.00 0.00 0.400559E+09 0.00 0.67
May 0.00 0.196937E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
June 0.00 0.289951E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
July 0.00 0.390635E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
August 0.00 0.329698E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.68
September 0.00 0.298922E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
October 0.00 0.950343E+10 0.00 75915142.47 0.00 0.00 0.101164E+09 0.00 0.66
November 0.00 0.897460E+09 0.00 0.108531E+10 0.00 0.00 0.340143E+10 0.00 0.66
December 0.00 0.00 0.00 0.204788E+10 0.00 0.00 0.112031E+11 0.00 0.66
                   
Annual Sum or Average 0.00 0.168282E+12 0.00 0.587667E+10 0.00 0.00 0.380536E+11 0.00 0.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.66
Maximum of Months 0.00 0.390635E+11 0.00 0.204788E+10 0.00 0.00 0.140113E+11 0.00 0.68



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:56:50

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.281542E+12 0.279952E+10 0.00 0.792432E+12 0.892357E+12
February 0.322700E+12 0.338674E+10 0.00 0.536184E+12 0.149598E+13
March 0.429021E+12 0.207460E+10 0.00 0.259180E+12 0.283193E+13
April 0.458178E+12 -0.147822E+10 0.00 -0.252953E+12 0.408133E+13
May 0.491476E+12 -0.709054E+10 0.00 -0.904592E+12 0.395887E+13
June 0.459540E+12 -0.813907E+10 0.00 -0.141785E+13 0.480524E+13
July 0.369454E+12 -0.175167E+11 0.00 -0.195058E+13 0.562036E+13
August 0.309981E+12 -0.122152E+11 0.00 -0.196096E+13 0.595056E+13
September 0.338693E+12 -0.704853E+10 0.00 -0.142644E+13 0.380367E+13
October 0.324931E+12 -586211590.8 0.00 -0.135941E+12 0.296859E+13
November 0.286702E+12 0.868134E+09 0.00 0.447520E+12 0.242133E+13
December 0.255879E+12 0.283907E+10 0.00 0.764140E+12 0.223299E+13
           
Annual Sum or Average 0.432810E+13 -0.421064E+11 0.00 -0.524985E+13 0.410632E+14
Minimum of Months 0.255879E+12 -0.175167E+11 0.00 -0.196096E+13 0.892357E+12
Maximum of Months 0.491476E+12 0.338674E+10 0.00 0.792432E+12 0.595056E+13