Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:56:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31321.12 | 676.18 | 676.18 |
Net Site Energy | 30756.03 | 663.98 | 663.98 |
Total Source Energy | 97992.77 | 2115.54 | 2115.54 |
Net Source Energy | 96203.13 | 2076.91 | 2076.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6575.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1951.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 259.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1203.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2748.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 932.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2290.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18717.51 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 107.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 576.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30744.44 | 576.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20997.68 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6575.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1951.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 259.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 4.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2748.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 932.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2290.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18717.51 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 107.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 576.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6575.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1951.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 259.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1203.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2748.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 932.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2290.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18717.51 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 107.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 576.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 47.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 270.85 | 12.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Other | 345.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 663.73 | 12.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 47.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 270.85 | 12.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Other | 345.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 663.73 | 12.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 589.444 | 1.92 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -24.35 | -0.1 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 565.090 | 1.84 |
Electricity Coming From Utility | 30179.352 | 98.16 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30179.352 | 98.16 |
Total On-Site and Utility Electric Sources | 30744.442 | 100.00 |
Total Electricity End Uses | 30744.442 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 7085.21 | 100.00 |
Air to Air Heat Recovery for Heating | 0.00 | 0.00 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 7085.21 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 20997.68 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 20997.68 | 100.00 |
Total Water End Uses | 20997.68 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1678.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.4195 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.4195 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.4195 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.4195 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.4195 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.4195 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.4195 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.4195 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.4195 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.4195 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.4195 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.4195 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.4195 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.4195 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.4195 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.4195 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9707 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9707 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9707 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.4195 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.4341 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.4341 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.4195 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.4195 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.4195 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.4195 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.4195 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.4195 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.4195 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.4195 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.4195 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.4195 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.4195 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.4195 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.4195 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.4195 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.4195 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.4195 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 7.9707 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 7.9707 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 7.9707 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.4195 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.4341 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.4341 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.9789 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-AUG-15:09 | 10-JAN-12:20 | - | - | - | - | - | - | - | - | - | - | 21-MAR-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 412432.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167324.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 52600.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 206865.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 50914.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83172.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 61877.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1756202.51 | 61877.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 412432.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 167324.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3370.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 49008.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 221.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 206865.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 50914.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 83172.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 61877.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20823.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6179.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 822.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3812.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8703.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2952.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 7252.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 340.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 625.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 97367.65 | 625.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 449.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 156.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 7.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2102.05 | 13.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 449.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 156.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 7.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2102.05 | 13.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.19 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.460528 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.39 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.447486 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.28 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.51 | 0.345371 | 0.294000 | 1.62 | 0.920988 | 0.500000 | 0.001103 | 0.000356 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 51.88 | 0.366598 | 0.312000 | 16.19 | 0.977594 | 0.500000 | 0.001039 | 0.004190 | 16.19 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.14 | 0.369868 | 0.314000 | 1.61 | 0.986316 | 0.500000 | 0.001030 | 0.000601 | 1.61 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.02 | 0.233971 | 0.199000 | 0.203125 | 0.623921 | 0.500000 | 0.001628 | 0.000045 | 0.203125 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.985699 | 0.156138 | 0.133000 | 0.131098 | 0.416368 | 0.500000 | 0.002440 | 0.000029 | 0.131098 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.987219 | 0.241918 | 0.206000 | 0.203367 | 0.645114 | 0.500000 | 0.001575 | 0.000045 | 0.203367 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.32 | 0.116851 | 0.099000 | 0.130393 | 0.311603 | 0.500000 | 0.003261 | 0.000029 | 0.130393 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.89 | 0.241473 | 0.205000 | 2.03 | 0.643929 | 0.500000 | 0.001578 | 0.000854 | 2.03 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.26 | 0.400170 | 0.500000 | 0.002539 | 0.000419 | 0.656382 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.51 | 0.251032 | 0.213000 | 2.03 | 0.669419 | 0.500000 | 0.001518 | 0.000880 | 2.03 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.58 | 0.132862 | 0.113000 | 1.31 | 0.354299 | 0.500000 | 0.002868 | 0.000388 | 1.31 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.10 | 0.216364 | 0.184000 | 0.203098 | 0.576970 | 0.500000 | 0.001761 | 0.000104 | 0.203098 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.04 | 0.148345 | 0.126000 | 0.130722 | 0.395587 | 0.500000 | 0.002568 | 0.000068 | 0.130722 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.07 | 0.223906 | 0.190000 | 0.202661 | 0.597082 | 0.500000 | 0.001702 | 0.000107 | 0.202661 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.23 | 0.124958 | 0.106000 | 0.130555 | 0.333222 | 0.500000 | 0.003049 | 0.000052 | 0.130555 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16294.99 | 0.000356 | 454.79 |
CORE_MID VAV BOX REHEAT COIL | 191521.15 | 0.004190 | 5498.75 |
CORE_TOP VAV BOX REHEAT COIL | 27494.35 | 0.000601 | 840.99 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2044.26 | 0.000045 | 57.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1319.37 | 0.000029 | 36.82 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 2046.69 | 0.000045 | 57.12 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1312.28 | 0.000029 | 36.63 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 39027.81 | 0.000854 | 1223.60 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 19158.20 | 0.000419 | 689.55 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 40235.92 | 0.000880 | 1270.50 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 17716.09 | 0.000388 | 523.23 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 4750.95 | 0.000104 | 156.88 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 3125.89 | 0.000068 | 103.95 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 4879.62 | 0.000107 | 162.65 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 2372.12 | 0.000052 | 73.46 |
VAV_BOT WITH REHEAT HEATING COIL | 41870.19 | 0.000916 | 918.16 |
VAV_MID WITH REHEAT HEATING COIL | 392323.71 | 0.008582 | 8603.14 |
VAV_TOP WITH REHEAT HEATING COIL | 42658.28 | 0.000933 | 935.44 |
CAV_BAS HEATING COIL | 221964.70 | 0.004855 | 7524.46 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.91 | 2.29 | 9.82 | 2.29 | 9.02 | 9.02 | 0.300000 | 0.253688 | 9.02 |
VAV_MID WITH REHEAT | 46.56 | 22.86 | 93.13 | 22.86 | 84.47 | 84.47 | 0.300000 | 0.270652 | 84.47 |
VAV_TOP WITH REHEAT | 4.79 | 2.28 | 9.58 | 2.28 | 9.19 | 9.19 | 0.300000 | 0.248420 | 9.19 |
CAV_BAS | 5.19 | 5.19 | 5.19 | 5.19 | 5.19 | 5.19 | 1.00 | 1.00 | 5.19 |
AIRLOOP DATACENTER BASEMENT | 21.28 | 21.28 | 21.28 | 21.28 | 21.28 | 21.28 | 1.00 | 0.999989 | 21.28 |
AIRLOOP DATACENTER BOT | 0.460528 | 0.460528 | 0.460528 | 0.460528 | 0.460555 | 0.460555 | 1.00 | 0.999941 | 0.460555 |
AIRLOOP DATACENTER MID | 4.39 | 4.39 | 4.39 | 4.39 | 4.39 | 4.39 | 1.00 | 1.00 | 4.39 |
AIRLOOP DATACENTER TOP | 0.447486 | 0.447486 | 0.447486 | 0.447486 | 0.447486 | 0.447486 | 1.00 | 1.00 | 0.447486 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.02 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 84.47 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.19 | |
CAV_BAS_OA_CONTROLLER | 5.19 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.28 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.460555 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.39 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.447486 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.60 | 6.67 | 11.05 | 0.010838 | 0.008500 | 236920.65 | 0.006776 | 9.02 |
VAV_MID WITH REHEAT COOLING COIL | 26.86 | 6.67 | 11.05 | 0.011132 | 0.008500 | 2322918.00 | 0.066435 | 84.47 |
VAV_TOP WITH REHEAT COOLING COIL | 26.48 | 6.67 | 11.05 | 0.010834 | 0.008500 | 239946.93 | 0.006862 | 9.19 |
CAV_BAS COOLING COIL | 26.33 | 6.67 | 11.43 | 0.011064 | 0.008500 | 135862.32 | 0.003886 | 5.19 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.02 |
VAV_MID WITH REHEAT FAN | 84.47 |
VAV_TOP WITH REHEAT FAN | 9.19 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006776 | 0.000070 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000916 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.066435 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.008582 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006862 | 0.000069 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000933 | |
CAV_BAS_COOLC_CONTROLLER | 0.003886 | 0.000123 |
CAV_BAS_HEATC_CONTROLLER | 0.004855 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.19 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.28 | 434384.07 | 312075.60 | 0.010638 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.460555 | 9465.45 | 6772.23 | 0.000232 |
AIRLOOP DATACENTER MID COOLING COIL | 4.39 | 90489.36 | 64642.65 | 0.002216 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.447486 | 9212.92 | 6585.51 | 0.000226 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.28 | 21.28 | 21.28 | 21.28 | 434384.07 | 434384.07 | 8144.41 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.460555 | 0.460555 | 0.460555 | 0.460555 | 9465.45 | 9465.45 | 376.24 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.39 | 4.39 | 4.39 | 4.39 | 90489.36 | 90489.36 | 3762.38 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.447486 | 0.447486 | 0.447486 | 0.447486 | 9212.92 | 9212.92 | 376.24 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.28 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.460555 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.39 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.447486 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.28 | 434384.07 | 0.010638 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.460555 | 9465.45 | 0.000232 |
AIRLOOP DATACENTER MID HEATING COIL | 4.39 | 90489.36 | 0.002216 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.447486 | 9212.92 | 0.000226 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 8144.41 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 376.24 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 3762.38 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 376.24 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000000 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.083959 | 13572.24 | |
HEATSYS1 PUMP | 0.023453 | 6992.96 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.083959 | 10.08 |
HEATSYS1 | 0.023453 | 2.81 |
COOLSYS1_SUPPLY | 0.083959 | 10.08 |
SINGLE WATER PLANT LOOP | 0.013312 | 1.60 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.083959 | 0.083959 | 352418.72 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1072116.55 | 1072116.55 | 0.023453 |
CENTRAL BOILER | 548321.68 | 537763.98 | 0.013312 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.041980 | 4698.26 |
COOLSYS1 CHILLER2 PUMP | 0.041980 | 4698.26 |
PLANT CIRC PUMP | 0.013312 | 3361.50 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.083959 | 0.042335 | 1483901.52 | 1490939.78 | 0.072860 |
COOLSYS1 CHILLER2 | 0.083959 | 0.042335 | 1483901.52 | 1490939.78 | 0.072860 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013312 | 139666.47 | 59200.55 | 69833.23 | 7004.20 | 21407.97 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.145719 | 17.49 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.145719 | 35719.72 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 51.87 | 1768957.19 | 10.37 | 221119.65 |
TOWERWATERSYS COOLTOWER 2 | 51.87 | 1768957.19 | 10.37 | 221119.65 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.076635 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.420 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.261 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.490 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.490 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.490 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.490 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.490 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.490 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.420 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.489 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.971 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.270 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.971 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.270 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 7.971 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.270 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.420 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.843 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 17842.557 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17842.557 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16023.870 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16023.870 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16023.870 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16023.870 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16023.870 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16023.870 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2011.957 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2011.957 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1296.581 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1296.581 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2012.001 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2012.001 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1296.581 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1296.581 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2011.957 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2011.957 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1296.581 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1296.581 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2012.001 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2012.001 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1296.581 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1296.581 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2011.957 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2011.957 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1296.581 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1296.581 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2012.001 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2012.001 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1296.581 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1296.581 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5030.838 | 6.420 | 119.267 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5030.838 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 288.560 | 7.971 | 148.085 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 288.560 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 288.560 | 7.971 | 148.085 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 288.560 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 288.560 | 7.971 | 148.085 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 288.560 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6127E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6139E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6413E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6423E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2654E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2661E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5431E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6407E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7191E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6645E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7310E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2819E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3291E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5556E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5883E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7086E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2411E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8686E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1855E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9557E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7140E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7703E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6101E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6401E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7157E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6637E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7269E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2810E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3256E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5560E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5892E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6126E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6137E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6412E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6421E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2653E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2659E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5430E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9302E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0084E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6997E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7716E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5395E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5858E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6379E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6605E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0206E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4515E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6574E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2413E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6049E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0428E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8851E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0771E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9174E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9663E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6842E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7203E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5263E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5403E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6380E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6608E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4521E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4532E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2709E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2717E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1028E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1033E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4777E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5427E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2911E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3418E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1155E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1437E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5560E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5893E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1772E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0910E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7232E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.5104E-003 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4122E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.4719E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7703E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6072E-003 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4776E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5418E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2913E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3418E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1162E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1461E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5557E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5883E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4520E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4532E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2708E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2717E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1028E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1033E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0334E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0819E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8199E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8560E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6490E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6635E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6381E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6609E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2146E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5200E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8809E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3195E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8182E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1187E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8851E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0771E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0468E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1284E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8361E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9118E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6624E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7103E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6379E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6604E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3580E-002 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4810E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.4342E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4305E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.6411E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7719E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.3990E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6803E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6533E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1426E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2465E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8776E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1767E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6405E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4843E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6997E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7637E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7873E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2457E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4558E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8890E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0611E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3990E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6800E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8742E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2392E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5015E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9886E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4178E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7458E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4843E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6997E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3678E-002 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4877E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.4456E-002 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4376E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.6532E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7784E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.4063E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6840E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6566E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1458E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2500E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8804E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1825E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6437E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4917E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7034E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7648E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7894E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2469E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4575E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8921E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0629E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4063E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6837E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8780E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2426E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5056E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9917E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4242E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7492E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4917E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7034E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72089.80273 | 72089.80273 | 5.19124 | 5.19124 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 20.10000 | 1.47983E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 76479.57154 | 76479.57154 | 5.50725 | 5.50725 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 720709.08544 | 720709.08544 | 51.88367 | 51.88367 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 28512.31108 | 28512.31108 | 1.21289 | 10.77825 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 71434.17607 | 71434.17607 | 5.14249 | 5.14249 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 11243.55942 | 11243.55942 | 0.47278 | 1.07782 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14041.39355 | 14041.39355 | 1.02073 | 1.02073 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.13533 | 00:10:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 | |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13559.55505 | 13559.55505 | 0.98570 | 0.98570 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:10:00 | 30.76583 | 1.71497E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13580.41079 | 13580.41079 | 0.98722 | 0.98722 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.13533 | 00:10:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 | |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18118.60409 | 18118.60409 | 1.31710 | 1.31710 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 136039.50107 | 136039.50107 | 9.89014 | 9.89014 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 34.86000 | 1.71575E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 18465.42796 | 18465.42796 | 0.77711 | 1.35332 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 141072.19018 | 141072.19018 | 10.25597 | 10.25597 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 12501.22231 | 12501.22231 | 0.52592 | 0.87213 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 130862.14752 | 130862.14752 | 9.51375 | 9.51375 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 19687.12658 | 19687.12658 | 0.82782 | 1.35335 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 159337.43416 | 159337.43416 | 11.58381 | 11.58381 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71567E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 4412.66636 | 4412.66636 | 0.18781 | 0.87213 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15182.25723 | 15182.25723 | 1.10379 | 1.10379 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 2693.48186 | 2693.48186 | 0.11563 | 0.13533 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14270.18496 | 14270.18496 | 1.03748 | 1.03748 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 31.48833 | 1.71511E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 1801.68856 | 1801.68856 | 7.73419E-002 | 8.72129E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14671.18569 | 14671.18569 | 1.06664 | 1.06664 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 2827.02009 | 2827.02009 | 0.12135 | 0.13533 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16941.02294 | 16941.02294 | 1.23165 | 1.23165 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 1046.48576 | 1046.48576 | 4.42415E-002 | 8.72129E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8033.36806 | 8033.36806 | 0.46053 | 0.46053 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 26.75667 | 1.71421E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76568.82888 | 76568.82888 | 4.38999 | 4.38999 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:50:00 | 33.30167 | 1.71545E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7804.93616 | 7804.93616 | 0.44749 | 0.44749 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 33.44333 | 1.71548E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371156.48160 | 371156.48160 | 21.27925 | 21.27925 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:00:00 | 27.46500 | 1.71434E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 20.10000 | 1.47983E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 145988.34 | 9.01547 | 9.01547 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1353310.83 | 84.47496 | 84.47496 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 151510.74 | 9.18516 | 9.18516 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
7 | CAV_BAS | Cooling | Sensible | 78006.51 | 5.19124 | 5.19124 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 28885.26 | 1.20016 | 1.20016 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368308.14 | 21.27947 | 21.27947 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 8144.41 | 0.33839 | 0.33839 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8030.55 | 0.46055 | 0.46055 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 376.24 | 1.56323E-002 | 1.56323E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76586.62 | 4.38999 | 4.38999 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 3762.38 | 0.15632 | 0.15632 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7806.10 | 0.44749 | 0.44749 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 376.24 | 1.56323E-002 | 1.56323E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.19124 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.50725 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34537 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61913 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92099 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10316E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.56453E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61913 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16294.98847 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.56453E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 454.79476 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 51.88367 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36660 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18771 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97759 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03929E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.18953E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18771 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 191521.14512 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.18953E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5498.75244 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.14249 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36987 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61474 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98632 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03010E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.01440E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61474 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27494.35207 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.01440E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 840.98676 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02073 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23397 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20313 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62392 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62841E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.47182E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20313 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2044.25580 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.47182E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 57.05538 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98570 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15614 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13300 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13110 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41637 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44015E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.88613E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13110 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1319.37257 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.88613E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.82382 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98722 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24192 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20600 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20337 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64511 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57492E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.47714E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20337 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2046.69176 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.47714E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 57.12337 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31710 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11685 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.90000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13039 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31160 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26056E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.87062E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13039 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1312.28173 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.87062E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.62591 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.89014 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24147 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02748 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64393 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57781E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.53734E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.02748 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39027.80642 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.53734E-004 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1223.59549 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.25597 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40017 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53892E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.19086E-004 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65638 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19158.19985 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.19086E-004 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 689.54738 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.51375 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25103 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02643 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66942 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51773E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.80162E-004 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.02643 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40235.92056 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.80162E-004 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1270.50015 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.58381 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13286 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30897 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35430 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86763E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.87540E-004 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30897 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17716.08507 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.87540E-004 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 523.22648 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10379 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21636 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18400 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20310 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57697 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76092E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03927E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20310 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4750.95114 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03927E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 156.88315 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03748 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14835 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13072 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39559 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56834E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.83790E-005 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13072 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3125.89285 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.83790E-005 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 103.95392 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06664 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22391 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19000 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20266 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59708 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70161E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06742E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20266 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4879.61972 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06742E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 162.64507 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23165 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12496 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13056 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33322 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04902E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.18902E-005 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13056 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2372.12182 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.18902E-005 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 73.46120 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46053 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.38999 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44749 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.27925 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.90900 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28712 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.81801 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28712 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.01547 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.01547 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.25369 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 46.56367 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.86335 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 93.12734 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.86335 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 84.47496 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 84.47496 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27065 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.79102 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28178 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.58205 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28178 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.18516 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.18516 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.24842 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.19124 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.19124 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.19124 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.19124 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.19124 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.19124 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.27925 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.27925 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.27925 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.27925 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.27947 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.27947 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46053 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46053 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46053 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46053 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46055 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46055 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 0.99994 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.38999 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.38999 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.38999 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.38999 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.38999 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.38999 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44749 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44749 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44749 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44749 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44749 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44749 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.01547 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 84.47496 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.18516 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.19124 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.27947 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46055 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.38999 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44749 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.01547 |
286 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.59851 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04836 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08380E-002 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 236920.65376 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.77590E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.01547 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 41870.18784 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.15912E-004 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 918.15806 |
298 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.01547 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.77590E-003 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.02771E-005 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.15912E-004 |
302 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 84.47496 |
303 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.85522 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04929 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11323E-002 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2322918.00413 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.64352E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 84.47496 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 392323.70742 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.58209E-003 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8603.14202 |
315 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 84.47496 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.64352E-002 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.16775E-006 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.58209E-003 |
319 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.18516 |
320 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.48215 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04835 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08340E-002 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 239946.92522 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.86245E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.18516 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 42658.27710 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.33151E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 935.43981 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.18516 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.86245E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.93907E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.33151E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.19124 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.32584 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42608 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.10637E-002 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 135862.32451 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.88565E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.19124 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 221964.69657 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.85548E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7524.45648 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.19124 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.88565E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.22551E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.85548E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.27947 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.27947 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 434384.07413 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 312075.60452 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06380E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.27947 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.27947 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.27947 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.27947 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 434384.07413 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 434384.07413 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8144.40695 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.27947 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.27947 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 434384.07413 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06380E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8144.40695 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 0.00000 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46055 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46055 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9465.44536 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6772.22711 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31808E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46055 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46055 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46055 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46055 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9465.44536 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9465.44536 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 376.23786 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46055 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46055 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9465.44536 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31808E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 376.23786 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.38999 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.38999 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 90489.36418 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64642.64874 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21608E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.38999 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.38999 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.38999 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.38999 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90489.36418 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90489.36418 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 3762.37861 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.38999 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.38999 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 90489.36418 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21608E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 3762.37861 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44749 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44749 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9212.91677 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6585.50916 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25624E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44749 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44749 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44749 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44749 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9212.91677 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9212.91677 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 376.23786 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44749 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44749 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9212.91677 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25624E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 376.23786 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.39592E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13572.24265 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.39592E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.07510 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.39592E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.39592E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 352418.71640 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.34526E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.81431 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.34526E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6992.95743 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1072116.55387 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1072116.55000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.34526E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.39592E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.07510 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.19796E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4698.26065 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.19796E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4698.26065 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.39592E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.23354E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1483901.51864 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1490939.78500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.28597E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.39592E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.23354E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1483901.51864 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1490939.78500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.28597E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.33115E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.59739 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.33115E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3361.49562 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.33115E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59200.55464 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21407.97215 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 548321.68213 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 537763.98000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.33115E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14572 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.48634 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14572 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 35719.72296 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 51.86772 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1768957.19000 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.37354 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 221119.64875 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 51.86772 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1768957.19000 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.37354 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 221119.64875 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.66350E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.66350E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22683.86 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 266565.73 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 38321.26 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2845.76 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1836.67 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 2849.15 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1826.80 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 54382.91 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 26672.05 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 56063.64 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 24687.66 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 6617.70 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4353.97 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 6796.61 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 3305.71 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 45948.69 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 430539.27 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 46813.54 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 262839.53 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 243114.31 | 167437.23 | 75677.08 | 0.69 | 36071.55 | 365.86 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2319990.70 | 1586925.26 | 733065.44 | 0.68 | 340894.32 | 3457.54 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 247193.00 | 170382.18 | 76810.82 | 0.69 | 36771.82 | 372.96 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 138524.60 | 95713.31 | 42811.29 | 0.69 | 20077.13 | 203.63 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.13 | 24.34 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.13 | 24.34 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1950557004 | 0.1864925789 | Pass | Pass | 0.7994628316 | 0.8819989236 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.3281407125 | 0.1907169708 | Pass | Pass | 0.3486178115 | 0.4735003817 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2241216586 | 0.2157736824 | Pass | Pass | 0.2357993381 | 0.4224184570 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2065193193 | 0.2211069122 | Pass | Pass | 0.2483989325 | 0.4475323720 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3451983759 | 0.2114994518 | Pass | Pass | 0.3486867115 | 0.4741572622 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3568686939 | 0.2169981182 | Pass | Pass | 0.3491186260 | 0.4739121695 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3807087417 | 0.2392015699 | Pass | Pass | 0.3667582258 | 0.4773952441 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4106079296 | 0.2964111945 | Pass | Pass | 0.4398436690 | 0.5947358932 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2335297283 | 0.2326655123 | Pass | Pass | 0.2471359544 | 0.4399862375 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2494946924 | 0.2696256699 | Pass | Pass | 0.3063222574 | 0.5439840869 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2632278582 | 0.2833411963 | Pass | Pass | 0.3202767629 | 0.5472696917 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2609490190 | 0.2740650538 | Pass | Pass | 0.2954563523 | 0.5122377338 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2341921080 | 0.2538919151 | Pass | Pass | 0.2383014099 | 0.4248165675 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2571288880 | 0.2917652448 | Pass | Pass | 0.2617402731 | 0.4550819107 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2685851351 | 0.3081546436 | Pass | Pass | 0.2773839131 | 0.4771897142 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2597593559 | 0.2966547812 | Pass | Pass | 0.2646261453 | 0.4590514680 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6661215634E-002 | 3.6454542257E-002 | Pass | Pass | 0.4651943243 | 0.8733232991 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.7829793786E-002 | 4.5556547045E-002 | Pass | Pass | 0.3167844040 | 0.8456933849 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.2725015436E-002 | 5.4403343434E-002 | Pass | Pass | 0.2783492988 | 0.5416287253 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1567672834E-005 | 1.3291906824E-005 | Pass | Pass | 1.3788193308E-003 | 9.2326231546E-004 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.3106127419E-006 | 4.7880963135E-006 | Pass | Pass | 1.0173471439E-003 | 8.1875044566E-004 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.1868332920E-006 | 4.8413533720E-006 | Pass | Pass | 1.4199670344E-003 | 1.2389993303E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.3236257578E-004 | 2.7773293569E-004 | Pass | Pass | 4.4853918934E-005 | 1.1214661985E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5700.80 | -185.8 | 0.00 | -17153.8 | 46628.86 | 34990.05 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.4195 | 2779.43 | 17842.56 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.31 | 0.0000 | Y | 131.65 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.4195 | 2496.12 | 16023.87 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.31 | 0.0000 | Y | 118.23 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.4195 | 24961.20 | 160238.70 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.31 | 0.0000 | Y | 1182.31 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.4195 | 2496.12 | 16023.87 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.31 | 0.0000 | Y | 118.23 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.4195 | 313.41 | 2011.96 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.17 | 0.0000 | Y | 8.37 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.4195 | 201.98 | 1296.58 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.25 | 0.0000 | Y | 5.41 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.4195 | 313.42 | 2012.00 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.11 | 0.0000 | Y | 8.35 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.4195 | 201.98 | 1296.58 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.06 | 0.0000 | Y | 5.37 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.4195 | 3134.13 | 20119.57 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.15 | 0.0000 | Y | 83.64 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.4195 | 2019.75 | 12965.81 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.22 | 0.0000 | Y | 54.09 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.4195 | 3134.20 | 20120.01 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.09 | 0.0000 | Y | 83.43 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.4195 | 2019.75 | 12965.81 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.04 | 0.0000 | Y | 53.64 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.4195 | 313.41 | 2011.96 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.15 | 0.0000 | Y | 8.36 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.4195 | 201.98 | 1296.58 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.22 | 0.0000 | Y | 5.41 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.4195 | 313.42 | 2012.00 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.09 | 0.0000 | Y | 8.34 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.4195 | 201.98 | 1296.58 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 22.04 | 0.0000 | Y | 5.36 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.4195 | 783.68 | 5030.84 | LightsWired | LTG_SCH_OFFICE | 40.71 | 168.00 | 39.66 | 0.0000 | Y | 37.45 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 7.9707 | 36.20 | 288.56 | LightsWired | LTG_SCH_DATACENTER | 52.86 | 168.00 | 51.50 | 0.0000 | Y | 2.79 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 7.9707 | 362.03 | 2885.60 | LightsWired | LTG_SCH_DATACENTER | 52.86 | 168.00 | 51.50 | 0.0000 | Y | 27.89 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 7.9707 | 36.20 | 288.56 | LightsWired | LTG_SCH_DATACENTER | 52.86 | 168.00 | 51.50 | 0.0000 | Y | 2.79 |
Interior Lighting Total | 6.4341 | 46320.38 | 298028.01 | 614.63 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2012.00 | 776.03 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2012.00 | 278.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1296.58 | 500.09 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1296.58 | 179.58 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2011.96 | 776.01 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2011.96 | 278.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1296.58 | 500.09 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1296.58 | 179.58 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2012.00 | 776.03 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2012.00 | 278.66 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1296.58 | 500.09 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1296.58 | 179.58 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2011.96 | 776.01 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2011.96 | 278.66 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1296.58 | 500.09 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1296.58 | 179.58 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2012.00 | 776.03 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2012.00 | 278.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1296.58 | 500.09 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1296.58 | 179.58 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2011.96 | 776.01 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2011.96 | 278.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1296.58 | 500.09 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1296.58 | 179.58 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12952.94 | AstronomicalClock | - | 41.93 | 41.93 | 101.94 | |
EXTERIOR_LIGHTS_B | 919.74 | AstronomicalClock | - | 83.83 | 62.88 | 10.86 | |
EXTERIOR_LIGHTS_C | 17215.91 | AstronomicalClock | - | 83.83 | 45.49 | 147.00 | |
Exterior Lighting Total | 31088.59 | 259.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2926605.85 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1072116.55 | 0.90 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1490939.78 | 6.91 | 1310286.45 | 6.16 | 7.13 | 24.34 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1490939.78 | 6.91 | 1310286.45 | 6.16 | 7.13 | 24.34 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 537763.98 | 0.90 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1768957.19 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1768957.19 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 236920.65 | 243114.31 | 167437.23 | 75677.08 | 0.69 | - | 36071.55 | 365.86 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2322918.00 | 2319990.70 | 1586925.26 | 733065.44 | 0.68 | - | 340894.32 | 3457.54 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 239946.93 | 247193.00 | 170382.18 | 76810.82 | 0.69 | - | 36771.82 | 372.96 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 135862.32 | 138524.60 | 95713.31 | 42811.29 | 0.69 | - | 20077.13 | 203.63 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 434384.07 | 312075.60 | 122308.47 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9465.45 | 6772.23 | 2693.22 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90489.36 | 64642.65 | 25846.72 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9212.92 | 6585.51 | 2627.41 | 0.71 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16294.99 | 22683.86 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 191521.15 | 266565.73 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 27494.35 | 38321.26 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 2044.26 | 2845.76 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 1319.37 | 1836.67 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2046.69 | 2849.15 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 1312.28 | 1826.80 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 39027.81 | 54382.91 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19158.20 | 26672.05 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40235.92 | 56063.64 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17716.09 | 24687.66 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 4750.95 | 6617.70 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3125.89 | 4353.97 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4879.62 | 6796.61 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2372.12 | 3305.71 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 41870.19 | 45948.69 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 392323.71 | 430539.27 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 42658.28 | 46813.54 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 221964.70 | 262839.53 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 434384.07 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9465.45 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 90489.36 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9212.92 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 8144.41 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 376.24 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 3762.38 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 376.24 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.02 | 19481.95 | 2160.95 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 84.47 | 182545.90 | 2160.95 | 1.00 | 1.08 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.19 | 19848.64 | 2160.95 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.19 | 8802.55 | 1695.65 | 1.00 | 1.16 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.28 | 35280.79 | 1657.97 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 515.87 | 1120.11 | 1.00 | 1.64 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.39 | 4917.26 | 1120.11 | 1.00 | 1.16 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 501.23 | 1120.11 | 1.00 | 1.66 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.083959 | 13572.24 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.023453 | 6992.96 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041980 | 4698.26 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041980 | 4698.26 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013312 | 3361.50 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.145719 | 35719.72 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72089.80 | 72089.80 | 25.94 | 5.191 | 5.191 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00899 | 28.91 | 0.01715 | 1.200 | 0.00 |
CORE_BOTTOM | 76479.57 | 76479.57 | 30.64 | 5.507 | 5.507 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.91 | 0.01715 | 1.078 | 0.00 |
CORE_MID | 720709.09 | 720709.09 | 288.73 | 51.884 | 51.884 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.91 | 0.01715 | 10.778 | 0.00 |
CORE_TOP | 71434.18 | 71434.18 | 28.62 | 5.142 | 5.142 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 28.91 | 0.01715 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14041.39 | 14041.39 | 44.80 | 1.021 | 1.021 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00895 | 34.95 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13559.56 | 13559.56 | 67.13 | 0.986 | 0.986 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:10:00 | 24.00 | 24.00 | 0.00881 | 30.77 | 0.01715 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13580.41 | 13580.41 | 43.33 | 0.987 | 0.987 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00897 | 35.20 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18118.60 | 18118.60 | 89.71 | 1.317 | 1.317 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00873 | 34.58 | 0.01716 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 136039.50 | 136039.50 | 434.06 | 9.890 | 9.890 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 24.00 | 24.00 | 0.00921 | 34.86 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 141072.19 | 141072.19 | 698.46 | 10.256 | 10.256 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00896 | 31.25 | 0.01715 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 130862.15 | 130862.15 | 417.53 | 9.514 | 9.514 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00923 | 35.20 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 159337.43 | 159337.43 | 788.90 | 11.584 | 11.584 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 24.00 | 24.00 | 0.00891 | 34.46 | 0.01716 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15182.26 | 15182.26 | 48.44 | 1.104 | 1.104 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00922 | 34.95 | 0.01716 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14270.18 | 14270.18 | 70.65 | 1.037 | 1.037 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 24.00 | 24.00 | 0.00902 | 31.49 | 0.01715 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14671.19 | 14671.19 | 46.81 | 1.067 | 1.067 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 24.00 | 24.00 | 0.00925 | 35.20 | 0.01716 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16941.02 | 16941.02 | 83.88 | 1.232 | 1.232 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00894 | 34.58 | 0.01716 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8033.37 | 8033.37 | 221.90 | 0.461 | 0.461 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.76 | 0.01714 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76568.83 | 76568.83 | 2115.00 | 4.390 | 4.390 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:50:00 | 27.00 | 27.00 | 0.00859 | 33.30 | 0.01715 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7804.94 | 7804.94 | 215.59 | 0.447 | 0.447 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 27.00 | 27.00 | 0.00859 | 33.44 | 0.01715 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371156.48 | 371156.48 | 473.61 | 21.279 | 21.279 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 27.47 | 0.01714 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.70 | 0.00850 | 20.10 | 0.01480 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 25.27 | 0.01480 | 20.10 | 0.01480 | 1.078 | 0.00 | |
CORE_MID | 28512.31 | 28512.31 | 11.42 | 1.213 | 10.778 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00832 | 20.10 | 0.01480 | 10.778 | 0.00 |
CORE_TOP | 11243.56 | 11243.56 | 4.50 | 0.473 | 1.078 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.000 | 0.135 | 00:10:00 | 15.60 | 23.69 | 0.01480 | 20.10 | 0.01480 | 0.135 | 0.00 | |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 23.46 | 0.01480 | 20.10 | 0.01480 | 0.087 | 0.00 | |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.135 | 00:10:00 | 15.60 | 22.59 | 0.01480 | 20.10 | 0.01480 | 0.135 | 0.00 | |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 24.26 | 0.01480 | 20.10 | 0.01480 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 18465.43 | 18465.43 | 58.92 | 0.777 | 1.353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01209 | 20.10 | 0.01480 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 12501.22 | 12501.22 | 61.89 | 0.526 | 0.872 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01209 | 20.10 | 0.01480 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 19687.13 | 19687.13 | 62.81 | 0.828 | 1.353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01201 | 20.10 | 0.01480 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 4412.67 | 4412.67 | 21.85 | 0.188 | 0.872 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01334 | 20.10 | 0.01480 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 2693.48 | 2693.48 | 8.59 | 0.116 | 0.135 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.01141 | 20.10 | 0.01480 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 1801.69 | 1801.69 | 8.92 | 0.077 | 0.087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.01138 | 20.10 | 0.01480 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 2827.02 | 2827.02 | 9.02 | 0.121 | 0.135 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.01129 | 20.10 | 0.01480 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 1046.49 | 1046.49 | 5.18 | 0.044 | 0.087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01273 | 20.10 | 0.01480 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 20.10 | 0.01480 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 26.34 | 0.00850 | 20.10 | 0.01480 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 25.99 | 0.00850 | 20.10 | 0.01480 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 20.10 | 0.01480 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.02 | 9.02 | 0.00 | 0.00 | 9.0155 | 2.2871 | 9.0155 | 0.2537 | 0.3000 |
VAV_MID WITH REHEAT | 84.47 | 84.47 | 0.00 | 0.00 | 84.4750 | 22.8633 | 84.4750 | 0.2707 | 0.3000 |
VAV_TOP WITH REHEAT | 9.19 | 9.19 | 0.00 | 0.00 | 9.1852 | 2.2818 | 9.1852 | 0.2484 | 0.3000 |
CAV_BAS | 5.19 | 5.19 | 1.20 | 1.20 | 5.1912 | 5.1912 | 5.1912 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.28 | 21.28 | 0.34 | 0.34 | 21.2795 | 21.2792 | 21.2795 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4606 | 0.4605 | 0.4606 | 0.9999 | 1.0000 |
AIRLOOP DATACENTER MID | 4.39 | 4.39 | 0.16 | 0.16 | 4.3900 | 4.3900 | 4.3900 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4475 | 0.4475 | 0.4475 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16294.988 | 16294.988 | 1.619133 | 0.00035645 | 454.795 | 12/21 00:10:00 | 12/21 00:10:00 | 16294.99 | 16294.99 | 1.619133 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16322.96 | 16322.96 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 191521.145 | 191521.145 | 16.187706 | 0.00418953 | 5498.752 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 191521.15 | 191521.15 | 16.187706 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00831862 | 53.7243 | 28512.31 | 0.00 | 191838.06 | 191838.06 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27494.352 | 27494.352 | 1.614741 | 0.00060144 | 840.987 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27494.35 | 27494.35 | 1.614741 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11243.56 | 0.00 | 27569.85 | 27569.85 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 2044.256 | 2044.256 | 0.203125 | 0.00004472 | 57.055 | 12/21 00:10:00 | 12/21 00:10:00 | 2044.26 | 2044.26 | 0.203125 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2047.76 | 2047.76 | ||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 1319.373 | 1319.373 | 0.131098 | 0.00002886 | 36.824 | 12/21 00:10:00 | 12/21 00:10:00 | 1319.37 | 1319.37 | 0.131098 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1321.64 | 1321.64 | ||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 2046.692 | 2046.692 | 0.203367 | 0.00004477 | 57.123 | 12/21 00:10:00 | 12/21 00:10:00 | 2046.69 | 2046.69 | 0.203367 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2050.20 | 2050.20 | ||
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 1312.282 | 1312.282 | 0.130393 | 0.00002871 | 36.626 | 12/21 00:10:00 | 12/21 00:10:00 | 1312.28 | 1312.28 | 0.130393 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1314.53 | 1314.53 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 39027.806 | 39027.806 | 2.027478 | 0.00085373 | 1223.595 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39027.81 | 39027.81 | 2.027478 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01209456 | 77.6351 | 18465.43 | 0.00 | 39130.07 | 39130.07 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 19158.200 | 19158.200 | 0.656382 | 0.00041909 | 689.547 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19158.20 | 19158.20 | 0.656382 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01208980 | 77.6045 | 12501.22 | 0.00 | 19202.37 | 19202.37 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 40235.921 | 40235.921 | 2.026429 | 0.00088016 | 1270.500 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 40235.92 | 40235.92 | 2.026429 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01200727 | 77.0848 | 19687.13 | 0.00 | 40340.76 | 40340.76 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 17716.085 | 17716.085 | 1.308971 | 0.00038754 | 523.226 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17716.09 | 17716.09 | 1.308971 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01333981 | 85.4666 | 4412.67 | 0.00 | 17757.83 | 17757.83 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 4750.951 | 4750.951 | 0.203098 | 0.00010393 | 156.883 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 4750.95 | 4750.95 | 0.203098 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01141376 | 73.3399 | 2693.48 | 0.00 | 4762.73 | 4762.73 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 3125.893 | 3125.893 | 0.130722 | 0.00006838 | 103.954 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3125.89 | 3125.89 | 0.130722 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01137902 | 73.1203 | 1801.69 | 0.00 | 3133.63 | 3133.63 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 4879.620 | 4879.620 | 0.202661 | 0.00010674 | 162.645 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 4879.62 | 4879.62 | 0.202661 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01129144 | 72.5677 | 2827.02 | 0.00 | 4891.69 | 4891.69 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 2372.122 | 2372.122 | 0.130555 | 0.00005189 | 73.461 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2372.12 | 2372.12 | 0.130555 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01273470 | 81.6607 | 1046.49 | 0.00 | 2378.41 | 2378.41 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 236920.654 | -999.000 | 9.015470 | 0.00677590 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 236920.65 | 170532.24 | 9.015470 | 26.60 | 19.16 | 0.01083805 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 22.5224 | 24.00 | 0.00892763 | 48.0072 | 120340.79 | 0.00 | 237238.45 | 168404.83 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 41870.188 | 41870.188 | 2.704641 | 0.00091591 | 918.158 | unknown | unknown | unknown | 41870.19 | 41870.19 | 2.704641 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 75.0747 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 40007.43 | 40007.43 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2322918.004 | -999.000 | 84.474963 | 0.06643516 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 2322918.00 | 1623277.70 | 84.474963 | 26.86 | 19.47 | 0.01113230 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 24.0379 | 24.00 | 0.00906906 | 48.7582 | 1095135.65 | 0.00 | 2326001.63 | 1606121.40 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 392323.707 | 392323.707 | 25.342489 | 0.00858209 | 8603.142 | unknown | unknown | unknown | 392323.71 | 392323.71 | 25.342489 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 80.1263 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 374869.63 | 374869.63 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 239946.925 | -999.000 | 9.185161 | 0.00686245 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 239946.93 | 172421.84 | 9.185161 | 26.48 | 19.12 | 0.01083398 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 22.1063 | 24.00 | 0.00903182 | 48.5612 | 126158.34 | 0.00 | 240270.86 | 170267.86 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 42658.277 | 42658.277 | 2.755548 | 0.00093315 | 935.440 | unknown | unknown | unknown | 42658.28 | 42658.28 | 2.755548 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 73.6877 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 40760.45 | 40760.45 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 135862.325 | -999.000 | 5.191239 | 0.00388565 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 11:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 135862.32 | 94698.32 | 5.191239 | 26.33 | 19.25 | 0.01106369 | 11.43 | 11.43 | 0.00850000 | 33.25 | 0.01715442 | 25.34 | 23.1189 | 24.00 | 0.00901517 | 48.4706 | 71176.98 | 0.00 | 136022.81 | 94190.03 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 221964.697 | 221964.697 | 5.191239 | 0.00485548 | 7524.456 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 221964.70 | 221964.70 | 5.191239 | 4.65 | 4.65 | 0.00995610 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 23.1189 | 26.70 | 0.00850000 | 38.9515 | 0.00 | 0.00 | 189602.21 | 189602.21 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434384.074 | 312075.605 | 21.279470 | 0.01063804 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:10:00 | 407199.57 | 396679.33 | -999.0 | 28.53 | 18.09 | 0.00867952 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | -999.0000 | 27.00 | 0.00854234 | 38.4645 | 370683.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9465.445 | 6772.227 | 0.460555 | 0.00023181 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 8882.89 | 8400.04 | -999.0 | 28.16 | 18.13 | 0.00888080 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00859009 | 38.6744 | 8032.92 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90489.364 | 64642.649 | 4.389990 | 0.00221608 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:50:00 | 84962.78 | 80134.67 | -999.0 | 28.17 | 18.15 | 0.00889939 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00859450 | 38.6943 | 76551.83 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9212.917 | 6585.509 | 0.447486 | 0.00022562 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 8648.49 | 8165.66 | -999.0 | 28.17 | 18.14 | 0.00889186 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00859276 | 38.6864 | 7804.94 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434384.074 | 434384.074 | 21.279470 | 0.01063804 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 434384.07 | 434384.07 | 21.279470 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 1.5902 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9465.445 | 9465.445 | 0.460555 | 0.00023181 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9465.45 | 9465.45 | 0.460555 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.3942 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90489.364 | 90489.364 | 4.389990 | 0.00221608 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 90489.36 | 90489.36 | 4.389990 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.5609 | 26.34 | 0.00850000 | 39.7802 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9212.917 | 9212.917 | 0.447486 | 0.00022562 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9212.92 | 9212.92 | 0.447486 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4934 | 25.99 | 0.00850487 | 40.6485 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 8144.407 | 8144.407 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8144.41 | 8144.41 | 21.279470 | 0.32 | 0.32 | 0.00860016 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 1.5902 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 376.24 | 376.24 | 0.460555 | 0.68 | 0.68 | 0.00871378 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.3942 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 3762.379 | 3762.379 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3762.38 | 3762.38 | 4.389990 | 0.72 | 0.72 | 0.00872428 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.5609 | 26.34 | 0.00850000 | 39.7802 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 376.24 | 376.24 | 0.447486 | 0.70 | 0.70 | 0.00872473 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4934 | 25.99 | 0.00850487 | 40.6485 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16294.988 | 16294.988 | 1.619133 | 0.00035645 | 454.795 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 1.4899 | 1.519890 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 16294.99 | 16294.99 | 1.0000 | 1.94878014 | 1.619133 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.35641696 | 60.00 | 48.89 | 11.11 | 0.000 | 16294.99 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16322.96 | 16322.96 | 1.94878014 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 191521.145 | 191521.145 | 16.187706 | 0.00418953 | 5498.752 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 17.5114 | 17.863836 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 191521.15 | 191521.15 | 1.0000 | 19.48344118 | 16.187706 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 4.18910300 | 60.00 | 48.89 | 11.11 | 0.000 | 191521.15 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.88 | 0.00831862 | 21.00 | 0.00831862 | 53.7243 | 28512.31 | 0.00 | 191838.06 | 191838.06 | 19.48344118 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 22.46 | 15.39 | 0.00800000 | 42906.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 27494.352 | 27494.352 | 1.614741 | 0.00060144 | 840.987 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 2.5139 | 2.564493 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 27494.35 | 27494.35 | 1.0000 | 1.94349453 | 1.614741 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.60137836 | 60.00 | 48.89 | 11.11 | 0.000 | 27494.35 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.71 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11243.56 | 0.00 | 27569.85 | 27569.85 | 1.94349453 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.71 | 16.92 | 0.00800000 | 47245.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2044.256 | 2044.256 | 0.203125 | 0.00004472 | 57.055 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.1869 | 0.190675 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 2044.26 | 2044.26 | 1.0000 | 0.24448039 | 0.203125 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.04471359 | 60.00 | 48.89 | 11.11 | 0.000 | 2044.26 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2047.76 | 2047.76 | 0.24448039 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1319.373 | 1319.373 | 0.131098 | 0.00002886 | 36.824 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.1206 | 0.123062 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 1319.37 | 1319.37 | 1.0000 | 0.15778882 | 0.131098 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02885837 | 60.00 | 48.89 | 11.11 | 0.000 | 1319.37 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1321.64 | 1321.64 | 0.15778882 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2046.692 | 2046.692 | 0.203367 | 0.00004477 | 57.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.1871 | 0.190902 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 2046.69 | 2046.69 | 1.0000 | 0.24477171 | 0.203367 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.04476687 | 60.00 | 48.89 | 11.11 | 0.000 | 2046.69 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2050.20 | 2050.20 | 0.24477171 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1312.282 | 1312.282 | 0.130393 | 0.00002871 | 36.626 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.1200 | 0.122401 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 1312.28 | 1312.28 | 1.0000 | 0.15694080 | 0.130393 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02870327 | 60.00 | 48.89 | 11.11 | 0.000 | 1312.28 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1314.53 | 1314.53 | 0.15694080 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.01 | 14.86 | 0.00800000 | 41435.8 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39027.806 | 39027.806 | 2.027478 | 0.00085373 | 1223.595 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 3.5684 | 3.640258 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 39027.81 | 39027.81 | 1.0000 | 2.44026250 | 2.027478 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.85364726 | 60.00 | 48.89 | 11.11 | 0.000 | 39027.81 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.66 | 0.01209456 | 21.00 | 0.01209456 | 77.6351 | 18465.43 | 0.00 | 39130.07 | 39130.07 | 2.44026250 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.53 | 17.54 | 0.00800000 | 49095.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19158.200 | 19158.200 | 0.656382 | 0.00041909 | 689.547 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 1.7517 | 1.786951 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19158.20 | 19158.20 | 1.0000 | 0.79001791 | 0.656382 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.41904340 | 60.00 | 48.89 | 11.11 | 0.000 | 19158.20 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.64 | 0.01208980 | 21.00 | 0.01208980 | 77.6045 | 12501.22 | 0.00 | 19202.37 | 19202.37 | 0.79001791 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.64 | 20.17 | 0.00800000 | 57366.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40235.921 | 40235.921 | 2.026429 | 0.00088016 | 1270.500 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 3.6789 | 3.752943 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 40235.92 | 40235.92 | 1.0000 | 2.43900013 | 2.026429 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.88007209 | 60.00 | 48.89 | 11.11 | 0.000 | 40235.92 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.64 | 0.01200727 | 21.00 | 0.01200727 | 77.0848 | 19687.13 | 0.00 | 40340.76 | 40340.76 | 2.43900013 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.02 | 17.71 | 0.00800000 | 49599.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17716.085 | 17716.085 | 1.308971 | 0.00038754 | 523.226 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 1.6198 | 1.652440 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17716.09 | 17716.09 | 1.0000 | 1.57547035 | 1.308971 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.38750032 | 60.00 | 48.89 | 11.11 | 0.000 | 17716.09 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.88 | 0.01333981 | 21.00 | 0.01333981 | 85.4666 | 4412.67 | 0.00 | 17757.83 | 17757.83 | 1.57547035 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.85 | 15.90 | 0.00800000 | 44331.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4750.951 | 4750.951 | 0.203098 | 0.00010393 | 156.883 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.4344 | 0.443138 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 4750.95 | 4750.95 | 1.0000 | 0.24444729 | 0.203098 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10391659 | 60.00 | 48.89 | 11.11 | 0.000 | 4750.95 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.01141376 | 21.00 | 0.01141376 | 73.3399 | 2693.48 | 0.00 | 4762.73 | 4762.73 | 0.24444729 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.91 | 18.67 | 0.00800000 | 52543.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3125.893 | 3125.893 | 0.130722 | 0.00006838 | 103.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.2858 | 0.291563 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 3125.89 | 3125.89 | 1.0000 | 0.15733689 | 0.130722 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06837202 | 60.00 | 48.89 | 11.11 | 0.000 | 3125.89 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.01137902 | 21.00 | 0.01137902 | 73.1203 | 1801.69 | 0.00 | 3133.63 | 3133.63 | 0.15733689 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.33 | 18.81 | 0.00800000 | 52976.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4879.620 | 4879.620 | 0.202661 | 0.00010674 | 162.645 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.4462 | 0.455139 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 4879.62 | 4879.62 | 1.0000 | 0.24392163 | 0.202661 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10673093 | 60.00 | 48.89 | 11.11 | 0.000 | 4879.62 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.01129144 | 21.00 | 0.01129144 | 72.5677 | 2827.02 | 0.00 | 4891.69 | 4891.69 | 0.24392163 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.47 | 18.85 | 0.00800000 | 53114.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2372.122 | 2372.122 | 0.130555 | 0.00005189 | 73.461 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 0.2169 | 0.221256 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2372.12 | 2372.12 | 1.0000 | 0.15713535 | 0.130555 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05188494 | 60.00 | 48.89 | 11.11 | 0.000 | 2372.12 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.72 | 0.01273470 | 21.00 | 0.01273470 | 81.6607 | 1046.49 | 0.00 | 2378.41 | 2378.41 | 0.15713535 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.64 | 17.24 | 0.00800000 | 48195.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 236920.654 | -999.000 | 9.015470 | 0.00677590 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9874 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.015470 | 10.85097432 | 4197.9300 | 999.8980 | 83.95059384 | 15.00 | 6.67 | 8.33 | 2935647.91 | 8.0705 | 8.070472 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 236920.65 | 170532.24 | 1.0000 | 10.85097432 | 9.015470 | 26.60 | 19.16 | 0.01083805 | 54368.4 | 11.05 | 11.05 | 0.00850000 | 32534.4 | 6.77520949 | 6.67 | 15.00 | 8.33 | 19481.950 | 217438.70 | 35.20 | 0.01715815 | 25.83 | 2.03050000 | 22.5224 | 24.00 | 0.00892763 | 24.00 | 0.00892763 | 48.0072 | 120340.79 | 0.00 | 237238.45 | 168404.83 | 10.85097432 | 26.60 | 19.17 | 0.01083805 | 54368.4 | 11.46 | 11.36 | 0.00832300 | 32505.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 41870.188 | 41870.188 | 2.704641 | 0.00091591 | 918.158 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.015470 | 10.85097432 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 3.8283 | 3.905376 | unknown | unknown | unknown | unknown | unknown | Sensible | 41870.19 | 41870.19 | 1.0000 | 3.25529230 | 2.704641 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.91581809 | 60.00 | 48.89 | 11.11 | 0.000 | 41870.19 | 0.00 | 0.00000000 | -6.26 | 2.03050000 | 75.0747 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 40007.43 | 40007.43 | 3.25529230 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 15.03 | 3.22 | 0.00000000 | 15128.6 | ||
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2322918.004 | -999.000 | 84.474963 | 0.06643516 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5344 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.474963 | 101.67364165 | 4197.9300 | 999.8980 | 83.95059384 | 15.00 | 6.67 | 8.33 | 2935647.91 | 79.1279 | 79.127950 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 2322918.00 | 1623277.70 | 1.0000 | 101.67364165 | 84.474963 | 26.86 | 19.47 | 0.01113230 | 55382.2 | 11.05 | 11.05 | 0.00850000 | 32535.4 | 66.42838379 | 6.67 | 15.00 | 8.33 | 182545.897 | 2140372.11 | 35.20 | 0.01715815 | 25.83 | 20.30600000 | 24.0379 | 24.00 | 0.00906906 | 24.00 | 0.00906906 | 48.7582 | 1095135.65 | 0.00 | 2326001.63 | 1606121.40 | 101.67364165 | 26.86 | 19.48 | 0.01113230 | 55382.2 | 11.45 | 11.36 | 0.00832513 | 32505.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 392323.707 | 392323.707 | 25.342489 | 0.00858209 | 8603.142 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.474963 | 101.67364165 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 35.8715 | 36.593382 | unknown | unknown | unknown | unknown | unknown | Sensible | 392323.71 | 392323.71 | 1.0000 | 30.50209250 | 25.342489 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 8.58121654 | 60.00 | 48.89 | 11.11 | 0.000 | 392323.71 | 0.00 | 0.00000000 | -6.26 | 20.30600000 | 80.1263 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 374869.63 | 374869.63 | 30.50209250 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 15.03 | 3.22 | 0.00000000 | 15128.6 | ||
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 239946.925 | -999.000 | 9.185161 | 0.00686245 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9798 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.185161 | 11.05521358 | 4197.9300 | 999.8980 | 83.95059384 | 15.00 | 6.67 | 8.33 | 2935647.91 | 8.1736 | 8.173559 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | Sensible | 239946.93 | 172421.84 | 1.0000 | 11.05521358 | 9.185161 | 26.48 | 19.12 | 0.01083398 | 54238.8 | 11.05 | 11.05 | 0.00850000 | 32534.4 | 6.86175165 | 6.67 | 15.00 | 8.33 | 19848.644 | 220098.28 | 35.20 | 0.01715815 | 25.83 | 2.03050000 | 22.1063 | 24.00 | 0.00903182 | 24.00 | 0.00903182 | 48.5612 | 126158.34 | 0.00 | 240270.86 | 170267.86 | 11.05521358 | 26.48 | 19.13 | 0.01083398 | 54238.8 | 11.46 | 11.36 | 0.00832346 | 32505.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 42658.277 | 42658.277 | 2.755548 | 0.00093315 | 935.440 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.185161 | 11.05521358 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 3.9004 | 3.978884 | unknown | unknown | unknown | unknown | unknown | Sensible | 42658.28 | 42658.28 | 1.0000 | 3.31656407 | 2.755548 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.93305581 | 60.00 | 48.89 | 11.11 | 0.000 | 42658.28 | 0.00 | 0.00000000 | -6.26 | 2.03050000 | 73.6877 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 40760.45 | 40760.45 | 3.31656407 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 15.03 | 3.22 | 0.00000000 | 15128.6 | ||
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 135862.325 | -999.000 | 5.191239 | 0.00388565 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4069 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.191239 | 6.24814926 | 4197.9300 | 999.8980 | 83.95059384 | 15.00 | 6.67 | 8.33 | 2935647.91 | 4.6280 | 4.628018 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 11:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 135862.32 | 94698.32 | 1.0000 | 6.24814926 | 5.191239 | 26.33 | 19.25 | 0.01106369 | 54664.3 | 11.43 | 11.43 | 0.00850000 | 32919.9 | 3.88524891 | 6.67 | 15.00 | 8.33 | 8802.547 | 127059.78 | 33.25 | 0.01715442 | 25.34 | 1.20015641 | 23.1189 | 24.00 | 0.00901517 | 24.00 | 0.00901517 | 48.4706 | 71176.98 | 0.00 | 136022.81 | 94190.03 | 6.24814926 | 26.33 | 19.26 | 0.01106369 | 54664.3 | 11.62 | 11.52 | 0.00840954 | 32894.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 221964.697 | 221964.697 | 5.191239 | 0.00485548 | 7524.456 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.191239 | 6.24814926 | 4197.9300 | 999.8980 | 23.45018700 | 48.89 | 60.00 | 11.11 | 1093693.33 | 20.2950 | 20.703411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 221964.70 | 221964.70 | 1.0000 | 6.24814926 | 5.191239 | 4.65 | 4.65 | 0.00995610 | 29655.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 4.85498860 | 60.00 | 48.89 | 11.11 | 0.000 | 221964.70 | 20.10 | 0.01479830 | 20.10 | 1.20015641 | 23.1189 | 0.00 | 0.00850000 | 26.70 | 0.00850000 | 38.9515 | 0.00 | 0.00 | 189602.21 | 189602.21 | 6.24814926 | 12.80 | 12.80 | 0.00995610 | 37998.5 | 42.45 | 23.23 | 0.00995610 | 68343.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 434384.074 | 312075.605 | 21.279470 | 0.01063804 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9748 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:10:00 | Sensible | 407199.57 | 396679.33 | 0.9374 | -999.0 | -999.0 | 28.53 | 18.09 | 0.00867952 | 50834.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 407199.57 | 35.20 | 0.01715815 | 25.83 | 0.33839277 | -999.0000 | 27.00 | 0.00854234 | 27.00 | 0.00854234 | 38.4645 | 370683.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9465.445 | 6772.227 | 0.460555 | 0.00023181 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3490 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | Sensible | 8882.89 | 8400.04 | 0.9385 | -999.0 | -999.0 | 28.16 | 18.13 | 0.00888080 | 50975.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8882.89 | 33.44 | 0.01715480 | 25.39 | 0.01563234 | -999.0000 | 27.00 | 0.00859009 | 27.00 | 0.00859009 | 38.6744 | 8032.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90489.364 | 64642.649 | 4.389990 | 0.00221608 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3835 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:50:00 | Sensible | 84962.78 | 80134.67 | 0.9389 | -999.0 | -999.0 | 28.17 | 18.15 | 0.00889939 | 51034.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84962.78 | 33.44 | 0.01715480 | 25.39 | 0.15632344 | -999.0000 | 27.00 | 0.00859450 | 27.00 | 0.00859450 | 38.6943 | 76551.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9212.917 | 6585.509 | 0.447486 | 0.00022562 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3695 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | Sensible | 8648.49 | 8165.66 | 0.9387 | -999.0 | -999.0 | 28.17 | 18.14 | 0.00889186 | 51010.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8648.49 | 33.44 | 0.01715480 | 25.39 | 0.01563234 | -999.0000 | 27.00 | 0.00859276 | 27.00 | 0.00859276 | 38.6864 | 7804.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 434384.074 | 434384.074 | 21.279470 | 0.01063804 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 434384.07 | 434384.07 | 1.0000 | 25.61186312 | 21.279470 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 434384.07 | 20.10 | 0.01479830 | 20.10 | 0.33839277 | 1.5902 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9465.445 | 9465.445 | 0.460555 | 0.00023181 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9465.45 | 9465.45 | 1.0000 | 0.55432159 | 0.460555 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9465.45 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.3942 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90489.364 | 90489.364 | 4.389990 | 0.00221608 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 90489.36 | 90489.36 | 1.0000 | 5.28377053 | 4.389990 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90489.36 | 20.10 | 0.01479830 | 20.10 | 0.15632344 | 3.5609 | 0.00 | 0.00850000 | 26.34 | 0.00850000 | 39.7802 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9212.917 | 9212.917 | 0.447486 | 0.00022562 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9212.92 | 9212.92 | 1.0000 | 0.53859145 | 0.447486 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9212.92 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.4934 | 0.00 | 0.00850487 | 25.99 | 0.00850487 | 40.6485 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8144.407 | 8144.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.279470 | 25.61186312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8144.41 | 8144.41 | 1.0000 | 25.61186312 | 21.279470 | 0.32 | 0.32 | 0.00860016 | 21834.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8144.41 | 20.10 | 0.01479830 | 20.10 | 0.33839277 | 1.5902 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.460555 | 0.55432159 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 376.24 | 376.24 | 1.0000 | 0.55432159 | 0.460555 | 0.68 | 0.68 | 0.00871378 | 22489.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 376.24 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.3942 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3762.379 | 3762.379 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.389990 | 5.28377053 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 3762.38 | 3762.38 | 1.0000 | 5.28377053 | 4.389990 | 0.72 | 0.72 | 0.00872428 | 22549.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3762.38 | 20.10 | 0.01479830 | 20.10 | 0.15632344 | 3.5609 | 0.00 | 0.00850000 | 26.34 | 0.00850000 | 39.7802 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.447486 | 0.53859145 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 376.24 | 376.24 | 1.0000 | 0.53859145 | 0.447486 | 0.70 | 0.70 | 0.00872473 | 22537.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 376.24 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.4934 | 0.00 | 0.00850487 | 25.99 | 0.00850487 | 40.6485 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5943.00 | 2985.50 | 2985.50 |
CORE_BOTTOM | 5943.00 | 0.00 | 0.00 |
CORE_MID | 5924.33 | 0.33 | 0.33 |
CORE_TOP | 5943.00 | 0.83 | 0.83 |
PERIMETER_BOT_ZN_3 | 5943.00 | 432.83 | 432.83 |
PERIMETER_BOT_ZN_2 | 5943.00 | 585.83 | 585.83 |
PERIMETER_BOT_ZN_1 | 5943.00 | 520.17 | 520.17 |
PERIMETER_BOT_ZN_4 | 5943.00 | 1120.50 | 1120.50 |
PERIMETER_MID_ZN_3 | 5942.00 | 800.17 | 800.17 |
PERIMETER_MID_ZN_2 | 5034.00 | 883.50 | 883.50 |
PERIMETER_MID_ZN_1 | 5943.00 | 878.67 | 878.67 |
PERIMETER_MID_ZN_4 | 5943.00 | 951.33 | 951.33 |
PERIMETER_TOP_ZN_3 | 5939.00 | 957.00 | 955.67 |
PERIMETER_TOP_ZN_2 | 5943.00 | 980.83 | 980.83 |
PERIMETER_TOP_ZN_1 | 5943.00 | 976.67 | 976.67 |
PERIMETER_TOP_ZN_4 | 5943.00 | 1025.67 | 1025.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 3271.17 | 3271.17 |
DATACENTER_MID_ZN_6 | 5943.00 | 709.17 | 709.17 |
DATACENTER_TOP_ZN_6 | 5943.00 | 1227.00 | 1227.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 126.50 | 0.00 | 7.33 |
CORE_BOTTOM | 0.00 | 8.17 | 0.00 | 0.33 |
CORE_MID | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 100.67 | 0.00 | 62.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 146.17 | 0.00 | 118.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 190.17 | 0.00 | 148.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 590.50 | 0.00 | 196.50 |
PERIMETER_MID_ZN_3 | 0.00 | 74.50 | 0.00 | 52.67 |
PERIMETER_MID_ZN_2 | 0.00 | 162.33 | 0.00 | 132.17 |
PERIMETER_MID_ZN_1 | 0.00 | 203.33 | 0.00 | 179.83 |
PERIMETER_MID_ZN_4 | 0.00 | 230.67 | 0.00 | 102.50 |
PERIMETER_TOP_ZN_3 | 0.00 | 119.67 | 0.00 | 83.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 190.00 | 0.00 | 140.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 183.00 | 0.00 | 139.83 |
PERIMETER_TOP_ZN_4 | 0.00 | 252.50 | 0.00 | 113.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 316.00 | 0.00 | 291.00 |
DATACENTER_MID_ZN_6 | 0.00 | 242.00 | 0.00 | 230.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 191.33 | 0.00 | 175.83 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1783.00 | 0.00 | 1336.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2587.17 | 0.00 | 1678.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.533 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.465 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.439 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.439 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.730 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.828 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.809 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.209 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.776 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.952 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.881 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.039 | 0.069 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.748 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.956 | 0.085 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.851 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.988 | 0.085 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.665 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.580 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.580 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.580 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.653 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 24132762.89 | 0.00 | 24132762.89 | 0.00 | 24132762.89 | 37848132.68 | 3174.44 | 5585.56 | 0.00 | 788.49 |
CORE_BOTTOM | 25358570.82 | 0.00 | 25358570.82 | 0.00 | 25358570.82 | 33990283.35 | 7295.11 | 1434.08 | 30.81 | 1856.89 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 7769.49 | 939.91 | 50.61 | 1000.29 |
CORE_TOP | 21129024.78 | 0.00 | 21129024.78 | 0.00 | 21129024.78 | 33990283.35 | 7815.31 | 901.38 | 43.32 | 1018.89 |
PERIMETER_BOT_ZN_3 | 4521213.69 | 0.00 | 4521213.69 | 257322.26 | 4778535.95 | 4267819.30 | 2650.27 | 1416.04 | 4693.69 | 1856.89 |
PERIMETER_BOT_ZN_2 | 3217654.49 | 0.00 | 3217654.49 | 171548.06 | 3389202.55 | 2750345.05 | 2539.28 | 1463.05 | 4757.67 | 1856.89 |
PERIMETER_BOT_ZN_1 | 4918294.44 | 0.00 | 4918294.44 | 257322.26 | 5175616.70 | 4267912.63 | 2429.03 | 1446.07 | 4884.90 | 1856.89 |
PERIMETER_BOT_ZN_4 | 4780581.82 | 0.00 | 4780581.82 | 171548.06 | 4952129.87 | 2750345.05 | 1533.82 | 1192.35 | 6033.84 | 1856.89 |
PERIMETER_MID_ZN_3 | 43351554.68 | 0.00 | 43351554.68 | 603476.85 | 43955031.53 | 42678193.03 | 3210.70 | 908.09 | 4641.21 | 1000.29 |
PERIMETER_MID_ZN_2 | 33762725.58 | 0.00 | 33762725.58 | 402317.62 | 34165043.20 | 27503450.52 | 2901.52 | 954.04 | 4904.44 | 1909.29 |
PERIMETER_MID_ZN_1 | 48656931.35 | 0.00 | 48656931.35 | 603476.85 | 49260408.20 | 42679126.28 | 3011.56 | 884.09 | 4864.35 | 1000.29 |
PERIMETER_MID_ZN_4 | 37229505.22 | 0.00 | 37229505.22 | 402317.62 | 37631822.85 | 27503450.52 | 2736.77 | 829.12 | 5194.11 | 1000.29 |
PERIMETER_TOP_ZN_3 | 4218680.98 | 0.00 | 4218680.98 | 749261.02 | 4967942.01 | 4267819.30 | 3104.44 | 940.06 | 4715.50 | 1018.89 |
PERIMETER_TOP_ZN_2 | 3390989.76 | 0.00 | 3390989.76 | 499507.01 | 3890496.77 | 2750345.05 | 2870.04 | 890.65 | 4999.30 | 1018.89 |
PERIMETER_TOP_ZN_1 | 4735252.79 | 0.00 | 4735252.79 | 749261.02 | 5484513.81 | 4267912.63 | 2956.97 | 884.47 | 4918.56 | 1018.89 |
PERIMETER_TOP_ZN_4 | 3577517.99 | 0.00 | 3577517.99 | 499507.01 | 4077025.00 | 2750345.05 | 2717.58 | 812.43 | 5229.99 | 1018.89 |
DATACENTER_BOT_ZN_6 | 492952.64 | 0.00 | 492952.64 | 0.00 | 492952.64 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.39E+10 | 0.00 | 0.39E+10 | 23471166.19 | 0.39E+10 | 0.50E+10 | 8665.61 | 8760.00 | 6471.58 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9687 | 0.0000 | 0.9687 | 0.0000 | 0.9687 | 1.2002 | 1145.93 | 4797.07 | 0.00 |
CORE_BOTTOM | 0.8563 | 0.0000 | 0.8563 | 0.0000 | 0.8563 | 1.0778 | 5531.70 | 388.35 | 22.95 |
CORE_MID | 8.0829 | 0.0000 | 8.0829 | 0.0000 | 8.0829 | 10.7782 | 5648.30 | 252.73 | 41.96 |
CORE_TOP | 0.8082 | 0.0000 | 0.8082 | 0.0000 | 0.8082 | 1.0778 | 5663.61 | 243.15 | 36.23 |
PERIMETER_BOT_ZN_3 | 0.1686 | 0.0000 | 0.1686 | 0.0065 | 0.1751 | 0.1353 | 960.98 | 392.89 | 4589.13 |
PERIMETER_BOT_ZN_2 | 0.1232 | 0.0000 | 0.1232 | 0.0043 | 0.1276 | 0.0872 | 857.19 | 397.44 | 4688.37 |
PERIMETER_BOT_ZN_1 | 0.1868 | 0.0000 | 0.1868 | 0.0065 | 0.1933 | 0.1353 | 797.54 | 388.59 | 4756.87 |
PERIMETER_BOT_ZN_4 | 0.1799 | 0.0000 | 0.1799 | 0.0043 | 0.1842 | 0.0872 | 525.92 | 313.79 | 5103.29 |
PERIMETER_MID_ZN_3 | 1.7917 | 0.0000 | 1.7917 | 0.0153 | 1.8069 | 1.3533 | 1139.15 | 246.63 | 4557.22 |
PERIMETER_MID_ZN_2 | 1.4162 | 0.0000 | 1.4162 | 0.0108 | 1.4270 | 0.8721 | 873.13 | 235.96 | 3924.92 |
PERIMETER_MID_ZN_1 | 2.0358 | 0.0000 | 2.0358 | 0.0153 | 2.0511 | 1.3533 | 960.11 | 231.10 | 4751.79 |
PERIMETER_MID_ZN_4 | 1.5460 | 0.0000 | 1.5460 | 0.0102 | 1.5562 | 0.8721 | 879.05 | 229.26 | 4834.70 |
PERIMETER_TOP_ZN_3 | 0.1728 | 0.0000 | 0.1728 | 0.0190 | 0.1918 | 0.1353 | 1079.30 | 260.02 | 4603.68 |
PERIMETER_TOP_ZN_2 | 0.1423 | 0.0000 | 0.1423 | 0.0127 | 0.1549 | 0.0872 | 875.68 | 224.92 | 4842.40 |
PERIMETER_TOP_ZN_1 | 0.1965 | 0.0000 | 0.1965 | 0.0190 | 0.2155 | 0.1353 | 934.18 | 232.33 | 4776.49 |
PERIMETER_TOP_ZN_4 | 0.1470 | 0.0000 | 0.1470 | 0.0127 | 0.1597 | 0.0872 | 875.46 | 222.79 | 4844.75 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 154.6087 | 0.0000 | 154.6087 | 0.6010 | 155.2097 | 158.4706 | 5919.70 | 5943.00 | 5334.77 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 61996504.23 | 0.00 | 61996504.23 | 48026705.38 | 1464.74 | 3.45 | 7291.80 | 1856.89 |
VAV_MID WITH REHEAT | 0.54E+09 | 0.00 | 0.54E+09 | 0.48E+09 | 2580.87 | 2.74 | 6176.39 | 1000.29 |
VAV_TOP WITH REHEAT | 53674274.66 | 0.00 | 53674274.66 | 48026705.38 | 2572.23 | 3.17 | 6184.60 | 1018.89 |
CAV_BAS | 34959706.87 | 0.00 | 34959706.87 | 37848132.68 | 3174.44 | 0.00 | 5585.56 | 788.49 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1943 | 0.0000 | 2.1943 | 1.5229 | 487.09 | 2.53 | 5453.38 |
VAV_MID WITH REHEAT | 21.5540 | 0.0000 | 21.5540 | 15.2292 | 747.35 | 2.16 | 5193.49 |
VAV_TOP WITH REHEAT | 2.1249 | 0.0000 | 2.1249 | 1.5229 | 754.07 | 2.38 | 5186.55 |
CAV_BAS | 1.4034 | 0.0000 | 1.4034 | 1.2002 | 1145.93 | 0.00 | 4797.07 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 177.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7167.37 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 374.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5847.66 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 181.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6057.41 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5585.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 1.9362 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3870 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 25.7552 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.4565 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.0353 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4295 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7386 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1525 |
Defaulted Fields | 1187 |
Fields with Defaults | 3945 |
Autosized Fields | 336 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30744.44 | 367427.04 | 28-JAN-05:00 | 1756202.51 | 28-AUG-15:10 |
Electricity:Building | 16627.54 | 216079.56 | 29-MAY-17:20 | 962631.91 | 18-DEC-17:00 |
Electricity:Zone:BASEMENT | 556.05 | 14055.89 | 01-JAN-00:10 | 25054.50 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16627.54 | 216079.56 | 29-MAY-17:20 | 962631.91 | 18-DEC-17:00 |
InteriorLights:Electricity | 1951.14 | 8822.18 | 04-JUL-17:20 | 184260.23 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 131.65 | 598.35 | 01-JAN-00:10 | 11596.96 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1951.14 | 8822.18 | 04-JUL-17:20 | 184260.23 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity | 1951.14 | 8822.18 | 04-JUL-17:20 | 184260.23 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 131.65 | 598.35 | 01-JAN-00:10 | 11596.96 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1951.14 | 8822.18 | 04-JUL-17:20 | 184260.23 | 18-DEC-17:00 |
Electricity:Zone:CORE_BOTTOM | 407.84 | 4990.59 | 01-JAN-00:10 | 27621.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 118.23 | 537.36 | 01-JAN-00:10 | 10414.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 118.23 | 537.36 | 01-JAN-00:10 | 10414.88 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4078.44 | 49905.77 | 01-JAN-00:10 | 276214.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1182.31 | 5373.60 | 01-JAN-00:10 | 104148.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1182.31 | 5373.60 | 01-JAN-00:10 | 104148.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 407.84 | 4990.58 | 01-JAN-00:10 | 27621.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 118.23 | 537.36 | 01-JAN-00:10 | 10414.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 118.23 | 537.36 | 01-JAN-00:10 | 10414.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 44.74 | 593.74 | 02-APR-17:10 | 3251.44 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.37 | 34.57 | 01-JAN-08:10 | 1090.89 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.37 | 34.57 | 01-JAN-08:10 | 1090.89 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 28.85 | 384.73 | 04-JUL-17:10 | 2106.37 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.41 | 22.28 | 01-JAN-07:10 | 714.03 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.41 | 22.28 | 01-JAN-07:10 | 714.03 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 44.72 | 595.98 | 26-MAR-17:10 | 3196.34 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.35 | 34.57 | 01-JAN-07:40 | 1035.75 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.35 | 34.57 | 01-JAN-07:40 | 1035.75 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 28.80 | 382.62 | 12-MAR-17:10 | 2026.02 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.37 | 22.28 | 01-JAN-08:30 | 633.69 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.37 | 22.28 | 01-JAN-08:30 | 633.69 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 447.30 | 5937.36 | 02-APR-17:10 | 32487.81 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 83.64 | 345.66 | 01-JAN-08:10 | 10882.30 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 83.64 | 345.66 | 01-JAN-08:10 | 10882.30 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 288.44 | 3845.23 | 04-JUL-17:10 | 21030.10 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 54.09 | 222.75 | 01-JAN-07:10 | 7106.68 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 54.09 | 222.75 | 01-JAN-07:10 | 7106.68 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 447.09 | 5937.46 | 12-MAR-17:10 | 31892.66 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 83.43 | 345.66 | 01-JAN-07:30 | 10286.81 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 83.43 | 345.66 | 01-JAN-07:30 | 10286.81 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 288.00 | 3826.24 | 12-MAR-17:10 | 20210.44 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 53.64 | 222.75 | 01-JAN-08:20 | 6287.11 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 53.64 | 222.75 | 01-JAN-08:20 | 6287.11 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 44.73 | 593.74 | 02-APR-17:10 | 3248.36 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.36 | 34.57 | 01-JAN-08:10 | 1087.80 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.36 | 34.57 | 01-JAN-08:10 | 1087.80 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 28.84 | 384.52 | 04-JUL-17:10 | 2102.75 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.41 | 22.28 | 01-JAN-07:10 | 710.41 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.41 | 22.28 | 01-JAN-07:10 | 710.41 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 44.71 | 593.75 | 12-MAR-17:10 | 3188.78 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.34 | 34.57 | 01-JAN-07:30 | 1028.20 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.34 | 34.57 | 01-JAN-07:30 | 1028.20 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 28.80 | 382.62 | 12-MAR-17:10 | 2020.72 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.36 | 22.28 | 01-JAN-08:20 | 628.39 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.36 | 22.28 | 01-JAN-08:20 | 628.39 | 18-DEC-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7532.31 | 95089.78 | 01-JAN-00:10 | 382902.37 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 37.45 | 181.65 | 01-JAN-00:10 | 3269.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 37.45 | 181.65 | 01-JAN-00:10 | 3269.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.67 | 1962.14 | 01-JAN-00:10 | 8037.98 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.79 | 13.53 | 01-JAN-00:10 | 243.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.79 | 13.53 | 01-JAN-00:10 | 243.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1566.70 | 19621.38 | 01-JAN-00:10 | 80379.85 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 27.89 | 135.32 | 01-JAN-00:10 | 2435.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 27.89 | 135.32 | 01-JAN-00:10 | 2435.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.67 | 1962.14 | 01-JAN-00:10 | 8037.98 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.79 | 13.53 | 01-JAN-00:10 | 243.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.79 | 13.53 | 01-JAN-00:10 | 243.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6877.69 | 47137.74 | 01-JAN-00:10 | 417921.51 | 02-JAN-06:10 |
HeatRejection:Electricity | 2290.11 | 43776.24 | 03-APR-21:10 | 83172.35 | 02-JAN-05:30 |
General:HeatRejection:Electricity | 2290.11 | 43776.24 | 03-APR-21:10 | 83172.35 | 02-JAN-05:30 |
ElectricityProduced:Facility | 565.09 | -0.00 | 01-JAN-17:30 | 81932.75 | 19-MAR-11:30 |
ElectricityProduced:Plant | 565.09 | -0.00 | 01-JAN-17:30 | 81932.75 | 19-MAR-11:30 |
Photovoltaic:ElectricityProduced | 589.44 | 0.00 | 01-JAN-00:10 | 85273.03 | 19-MAR-11:30 |
PowerConversion:ElectricityProduced | -24.35 | -3340.28 | 19-MAR-11:30 | 0.00 | 01-JAN-00:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 5830.08 | 75296.69 | 23-JAN-05:50 | 379097.09 | 24-APR-15:20 |
ExteriorEquipment:Electricity | 1203.79 | 17814.45 | 01-JAN-00:10 | 73700.66 | 23-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.45 | 979.82 | 01-JAN-00:10 | 3379.13 | 18-DEC-17:00 |
ElectricityPurchased:Facility | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
ElectricityPurchased:Plant | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
Cogeneration:ElectricityPurchased | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
ElectricityNet:Plant | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
Cogeneration:ElectricityNet | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
General:Cogeneration:ElectricityNet | 30179.35 | 367427.04 | 28-JAN-05:00 | 1713648.18 | 28-AUG-15:50 |
Fans:Electricity | 2748.25 | 41215.16 | 01-JAN-00:10 | 216794.36 | 24-APR-15:20 |
General:Fans:Electricity | 2748.25 | 41215.16 | 01-JAN-00:10 | 216794.36 | 24-APR-15:20 |
ExteriorLights:Electricity | 259.80 | 0.00 | 01-JAN-06:20 | 31088.59 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 259.80 | 0.00 | 01-JAN-06:20 | 31088.59 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1144.44 | 16803.04 | 01-JAN-00:10 | 70012.65 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 4.90 | 31.59 | 01-JAN-00:10 | 315.94 | 01-JAN-07:10 |
HeatRecovery:Electricity | 107.44 | 0.00 | 01-JAN-00:10 | 4520.72 | 01-JAN-06:50 |
General:HeatRecovery:Electricity | 107.44 | 0.00 | 01-JAN-00:10 | 4520.72 | 01-JAN-06:50 |
Cooling:Electricity | 6575.25 | 32977.26 | 23-JAN-05:50 | 423883.54 | 23-AUG-12:10 |
General:Cooling:Electricity | 6575.25 | 32977.26 | 23-JAN-05:50 | 423883.54 | 23-AUG-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Humidifier:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 932.26 | 3361.50 | 01-JAN-00:10 | 62089.00 | 26-DEC-13:30 |
General:Pumps:Electricity | 932.26 | 3361.50 | 01-JAN-00:10 | 62089.00 | 26-DEC-13:30 |
WIRED_LTG_ELECTRICITY | 54.83 | 0.00 | 01-JAN-00:10 | 5177.71 | 18-DEC-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 576.68 | 7280.88 | 18-MAR-16:10 | 61877.34 | 10-JAN-12:20 |
NaturalGas:Plant | 576.68 | 7280.88 | 18-MAR-16:10 | 61877.34 | 10-JAN-12:20 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:NaturalGas | 576.68 | 7280.88 | 18-MAR-16:10 | 61877.34 | 10-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 576.68 | 7280.88 | 18-MAR-16:10 | 61877.34 | 10-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 39028.18 | 184081.09 | 24-JAN-05:50 | 2559244.22 | 28-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 39028.18 | 184081.09 | 24-JAN-05:50 | 2559244.22 | 28-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 39028.18 | 184081.09 | 24-JAN-05:50 | 2559244.22 | 28-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 20997.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
Water:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Humidifier:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 20997.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
MainsWater:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Humidifier:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water:Plant | 20997.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 20997.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 18717.51 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
General:HeatRejection:Water | 18717.51 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
HeatRejection:MainsWater | 18717.51 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
General:HeatRejection:MainsWater | 18717.51 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 150976.84 | 258659.53 | 24-JAN-05:50 | 10538375.17 | 28-AUG-14:30 |
EnergyTransfer:Building | 24546.38 | 106030.26 | 25-MAY-21:20 | 1611632.64 | 26-DEC-15:10 |
EnergyTransfer:Zone:BASEMENT | 746.49 | 0.00 | 01-JAN-00:10 | 72245.85 | 26-DEC-08:30 |
Heating:EnergyTransfer | 10.12 | 0.00 | 01-JAN-00:10 | 21564.02 | 06-MAY-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 5.92 | 0.00 | 01-JAN-00:10 | 21564.02 | 06-MAY-16:10 |
General:Heating:EnergyTransfer | 10.12 | 0.00 | 01-JAN-00:10 | 21564.02 | 06-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 5.92 | 0.00 | 01-JAN-00:10 | 21564.02 | 06-MAY-16:10 |
Cooling:EnergyTransfer | 24536.25 | 106030.26 | 25-MAY-21:20 | 1611632.64 | 26-DEC-15:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 740.57 | 0.00 | 01-JAN-00:10 | 72245.85 | 26-DEC-08:30 |
General:Cooling:EnergyTransfer | 24536.25 | 106030.26 | 25-MAY-21:20 | 1611632.64 | 26-DEC-15:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 740.57 | 0.00 | 01-JAN-00:10 | 72245.85 | 26-DEC-08:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 782.01 | 0.00 | 01-JAN-00:10 | 55665.15 | 26-DEC-08:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 782.01 | 0.00 | 01-JAN-00:10 | 55665.15 | 26-DEC-08:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 782.01 | 0.00 | 01-JAN-00:10 | 55665.15 | 26-DEC-08:40 |
EnergyTransfer:Zone:CORE_MID | 5959.45 | 0.00 | 01-JAN-00:10 | 512908.69 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5959.45 | 0.00 | 01-JAN-00:10 | 512908.69 | 02-JAN-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5959.45 | 0.00 | 01-JAN-00:10 | 512908.69 | 02-JAN-06:10 |
EnergyTransfer:Zone:CORE_TOP | 639.82 | 0.00 | 01-JAN-00:10 | 51222.68 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 639.82 | 0.00 | 01-JAN-00:10 | 51222.68 | 02-JAN-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 639.82 | 0.00 | 01-JAN-00:10 | 51222.68 | 02-JAN-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 152.12 | 0.00 | 01-JAN-00:10 | 14215.41 | 12-JUN-15:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 152.12 | 0.00 | 01-JAN-00:10 | 14215.41 | 12-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 152.12 | 0.00 | 01-JAN-00:10 | 14215.41 | 12-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 110.06 | 0.00 | 01-JAN-00:10 | 11509.29 | 20-MAR-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 110.06 | 0.00 | 01-JAN-00:10 | 11509.29 | 20-MAR-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 110.06 | 0.00 | 01-JAN-00:10 | 11509.29 | 20-MAR-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 167.39 | 0.00 | 01-JAN-00:10 | 15410.87 | 26-DEC-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 167.39 | 0.00 | 01-JAN-00:10 | 15410.87 | 26-DEC-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 167.39 | 0.00 | 01-JAN-00:10 | 15410.87 | 26-DEC-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 161.40 | 0.00 | 01-JAN-00:10 | 16458.34 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 161.40 | 0.00 | 01-JAN-00:10 | 16458.34 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 161.40 | 0.00 | 01-JAN-00:10 | 16458.34 | 18-APR-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1310.69 | 0.00 | 01-JAN-00:10 | 138012.57 | 12-JUN-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1310.69 | 0.00 | 01-JAN-00:10 | 138012.57 | 12-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1310.69 | 0.00 | 01-JAN-00:10 | 138012.57 | 12-JUN-15:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1036.87 | 0.00 | 01-JAN-00:10 | 117794.91 | 05-MAY-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1036.87 | 0.00 | 01-JAN-00:10 | 117794.91 | 05-MAY-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1036.87 | 0.00 | 01-JAN-00:10 | 117794.91 | 05-MAY-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1486.43 | 0.00 | 01-JAN-00:10 | 147162.92 | 07-DEC-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1486.43 | 0.00 | 01-JAN-00:10 | 147162.92 | 07-DEC-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1486.43 | 0.00 | 01-JAN-00:10 | 147162.92 | 07-DEC-14:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1123.01 | 0.00 | 01-JAN-00:10 | 132159.25 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1123.01 | 0.00 | 01-JAN-00:10 | 132159.25 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1123.01 | 0.00 | 01-JAN-00:10 | 132159.25 | 18-APR-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 136.99 | 0.00 | 01-JAN-00:10 | 15178.20 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 136.99 | 0.00 | 01-JAN-00:10 | 15178.20 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 136.99 | 0.00 | 01-JAN-00:10 | 15178.20 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 110.71 | 0.00 | 01-JAN-00:10 | 11984.64 | 05-MAY-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 110.71 | 0.00 | 01-JAN-00:10 | 11984.64 | 05-MAY-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 110.71 | 0.00 | 01-JAN-00:10 | 11984.64 | 05-MAY-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 154.80 | 0.00 | 01-JAN-00:10 | 16077.81 | 26-DEC-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 154.80 | 0.00 | 01-JAN-00:10 | 16077.81 | 26-DEC-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 154.80 | 0.00 | 01-JAN-00:10 | 16077.81 | 26-DEC-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 116.05 | 0.00 | 01-JAN-00:10 | 13827.59 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 116.05 | 0.00 | 01-JAN-00:10 | 13827.59 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 116.05 | 0.00 | 01-JAN-00:10 | 13827.59 | 18-APR-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 146.96 | 0.00 | 01-JAN-00:10 | 13797.56 | 01-MAY-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.43 | 0.00 | 01-JAN-00:10 | 1759.82 | 17-SEP-07:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.43 | 0.00 | 01-JAN-00:10 | 1759.82 | 17-SEP-07:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 146.53 | 0.00 | 01-JAN-00:10 | 13797.56 | 01-MAY-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 146.53 | 0.00 | 01-JAN-00:10 | 13797.56 | 01-MAY-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1191.25 | 0.00 | 01-JAN-00:10 | 107059.89 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.53 | 0.00 | 01-JAN-00:10 | 16745.50 | 20-AUG-14:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.53 | 0.00 | 01-JAN-00:10 | 16745.50 | 20-AUG-14:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1187.72 | 0.00 | 01-JAN-00:10 | 107059.89 | 02-JAN-06:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1187.72 | 0.00 | 01-JAN-00:10 | 107059.89 | 02-JAN-06:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 178.24 | 0.00 | 01-JAN-00:10 | 20966.43 | 11-APR-14:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.23 | 0.00 | 01-JAN-00:10 | 2291.96 | 23-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.23 | 0.00 | 01-JAN-00:10 | 2291.96 | 23-JAN-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 178.01 | 0.00 | 01-JAN-00:10 | 20966.43 | 11-APR-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 178.01 | 0.00 | 01-JAN-00:10 | 20966.43 | 11-APR-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.57 | 1476.35 | 25-MAY-21:20 | 7781.51 | 09-APR-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.57 | 1476.35 | 25-MAY-21:20 | 7781.51 | 09-APR-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.57 | 1476.35 | 25-MAY-21:20 | 7781.51 | 09-APR-17:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1367.94 | 13020.47 | 16-SEP-07:00 | 73880.80 | 24-DEC-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1367.94 | 13020.47 | 16-SEP-07:00 | 73880.80 | 24-DEC-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1367.94 | 13020.47 | 16-SEP-07:00 | 73880.80 | 24-DEC-17:30 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.82 | 1242.83 | 16-SEP-07:00 | 7553.45 | 24-DEC-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.82 | 1242.83 | 16-SEP-07:00 | 7553.45 | 24-DEC-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.82 | 1242.83 | 16-SEP-07:00 | 7553.45 | 24-DEC-17:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7185.30 | 89532.21 | 07-JAN-20:00 | 369336.37 | 23-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7185.30 | 89532.21 | 07-JAN-20:00 | 369336.37 | 23-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7185.30 | 89532.21 | 07-JAN-20:00 | 369336.37 | 23-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 267.17 | 0.00 | 01-JAN-00:10 | 30856.84 | 10-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 267.17 | 0.00 | 01-JAN-00:10 | 30856.84 | 10-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 267.17 | 0.00 | 01-JAN-00:10 | 30856.84 | 10-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 267.17 | 0.00 | 01-JAN-00:10 | 30856.84 | 10-JAN-12:30 |
EnergyTransfer:HVAC | 43193.46 | 150582.65 | 24-JAN-05:50 | 2979523.96 | 28-AUG-15:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 36108.25 | 150582.65 | 24-JAN-05:50 | 2408309.19 | 28-AUG-14:30 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 27-DEC-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 7085.21 | 0.00 | 01-JAN-00:10 | 775263.11 | 30-SEP-11:00 |
EnergyTransfer:Plant | 83237.00 | 0.00 | 01-JAN-00:10 | 6841180.91 | 02-JAN-06:10 |
LoopToLoop:EnergyTransfer | 26618.17 | 0.00 | 01-JAN-00:10 | 2225589.67 | 02-JAN-06:10 |
WaterSystems:EnergyTransfer | 267.17 | 0.00 | 01-JAN-00:10 | 30856.84 | 10-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 267.17 | 0.00 | 01-JAN-00:10 | 30856.84 | 10-JAN-12:30 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Chillers:EnergyTransfer | 26348.17 | 0.00 | 01-JAN-00:10 | 2163612.60 | 02-JAN-06:10 |
HeatRejection:EnergyTransfer | 30003.49 | 0.00 | 01-JAN-00:10 | 2448250.91 | 02-JAN-06:10 |
General:HeatRejection:EnergyTransfer | 30003.49 | 0.00 | 01-JAN-00:10 | 2448250.91 | 02-JAN-06:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 5.922 | -740.553 | 0.000 | 0.000 | 92.651 | 131.650 | 424.397 | 0.000 | 0.000 | 0.000 | 85.933 | 0.000 | 0.000 | 0.000 | 0.000 | -0.017 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -782.012 | 0.000 | 0.000 | 83.441 | 118.231 | 289.614 | 0.000 | 0.000 | 0.000 | 290.725 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5959.440 | 0.000 | 0.000 | 834.671 | 1182.311 | 2896.128 | 0.000 | 0.000 | 0.000 | 1046.330 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -639.816 | 0.000 | 0.000 | 83.422 | 118.231 | 289.613 | 0.000 | 0.000 | 0.000 | 148.551 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -152.124 | 0.000 | 0.000 | 10.458 | 8.371 | 36.365 | 66.099 | 0.000 | 0.821 | 37.259 | 0.000 | -7.149 | 0.000 | -0.101 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -110.058 | 0.000 | 0.000 | 6.738 | 5.414 | 23.435 | 66.354 | 0.000 | 0.551 | 11.940 | 0.000 | -4.311 | 0.000 | -0.064 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -167.385 | 0.000 | 0.000 | 10.432 | 8.352 | 36.366 | 84.983 | 0.000 | 0.815 | 33.884 | 0.000 | -7.327 | 0.000 | -0.119 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -161.396 | 0.000 | 0.000 | 6.728 | 5.369 | 23.435 | 64.265 | 0.000 | 0.484 | 68.967 | 0.000 | -7.713 | 0.000 | -0.139 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1310.665 | 0.000 | 0.000 | 104.556 | 83.642 | 363.654 | 663.938 | 0.000 | 18.347 | 151.044 | 0.000 | -71.223 | 0.000 | -3.294 | -0.004 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -1036.842 | 0.000 | 0.000 | 49.268 | 54.087 | 234.352 | 654.707 | 0.000 | 11.629 | 84.495 | 0.000 | -49.174 | 0.000 | -2.523 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1486.398 | 0.000 | 0.000 | 104.179 | 83.435 | 363.660 | 850.107 | 0.000 | 18.163 | 145.460 | 0.000 | -74.671 | 0.000 | -3.935 | -0.007 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -1122.993 | 0.000 | 0.000 | 67.315 | 53.645 | 234.351 | 654.337 | 0.000 | 11.282 | 165.687 | 0.000 | -60.506 | 0.000 | -3.118 | -0.011 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -136.991 | 0.000 | 0.000 | 10.455 | 8.364 | 36.365 | 65.478 | 0.000 | 2.166 | 22.059 | 0.000 | -7.460 | 0.000 | -0.437 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -110.703 | 0.000 | 0.000 | 6.733 | 5.408 | 23.435 | 65.091 | 0.000 | 1.404 | 14.048 | 0.000 | -5.087 | 0.000 | -0.330 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -154.796 | 0.000 | 0.000 | 10.435 | 8.343 | 36.366 | 84.088 | 0.000 | 2.153 | 21.668 | 0.000 | -7.743 | 0.000 | -0.514 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -116.046 | 0.000 | 0.000 | 6.731 | 5.364 | 23.435 | 64.821 | 0.000 | 1.352 | 20.959 | 0.000 | -6.213 | 0.000 | -0.404 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -144.567 | 0.000 | 0.000 | 0.942 | 2.789 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -13.045 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1367.945 | 0.000 | 0.000 | 9.433 | 27.895 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -208.188 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -137.825 | 0.000 | 0.000 | 0.945 | 2.789 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.790 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7185.313 | 0.000 | 0.000 | 19.395 | 37.449 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -366.388 |
GROUNDFLOOR_PLENUM | 0.434 | -146.529 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.420 | 144.953 | 0.000 | 0.000 | 0.000 | -0.279 | 0.000 |
MIDFLOOR_PLENUM | 3.534 | -1187.710 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25.732 | 1163.723 | 0.000 | 0.000 | 0.000 | -5.279 | 0.000 |
TOPFLOOR_PLENUM | 0.234 | -178.008 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.467 | 175.961 | 0.000 | 0.000 | 0.000 | -0.654 | 0.000 |
Total Facility | 4.203 | -1512.247 | 5.922 | -23023.867 | 0.000 | 0.000 | 1518.929 | 1951.141 | 14676.396 | 3384.268 | 0.000 | 98.786 | 3833.648 | 0.000 | -308.577 | 0.000 | -21.189 | -607.466 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-JAN-05:53 | 0.00 | 0.00 | 0.00 | -81581.33 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 67525.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-05:13 | 0.00 | 0.00 | 0.00 | -87987.45 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 81512.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:15 | 0.00 | 0.00 | 0.00 | -818135.16 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 753385.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:13 | 0.00 | 0.00 | 0.00 | -84502.93 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 78027.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 19-MAR-14:21 | 0.00 | 0.00 | 0.00 | -18170.30 | 0.00 | 0.00 | 40.96 | 34.57 | 720.18 | 5077.28 | 0.00 | 354.99 | 11942.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 19-MAR-09:42 | 0.00 | 0.00 | 0.00 | -18159.92 | 0.00 | 0.00 | 22.89 | 22.28 | 464.11 | 10280.19 | 0.00 | 89.33 | 7281.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-JAN-15:31 | 0.00 | 0.00 | 0.00 | -19114.73 | 0.00 | 0.00 | 34.32 | 34.57 | 720.19 | 9844.21 | 0.00 | 31.31 | 8450.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 | -26349.32 | 0.00 | 0.00 | 18.44 | 22.28 | 464.11 | 11417.00 | 0.00 | 126.30 | 14301.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUN-16:11 | 0.00 | 0.00 | 0.00 | -187654.37 | 0.00 | 0.00 | 364.77 | 345.66 | 7201.84 | 62428.81 | 0.00 | 2534.99 | 114778.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 19-MAR-09:12 | 0.00 | 0.00 | 0.00 | -192717.19 | 0.00 | 0.00 | 223.10 | 222.75 | 4641.14 | 110265.53 | 0.00 | 1507.02 | 75857.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 16-JAN-14:21 | 0.00 | 0.00 | 0.00 | -188091.86 | 0.00 | 0.00 | 328.57 | 345.66 | 7201.95 | 126269.42 | 0.00 | 402.35 | 53543.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 23-APR-15:31 | 0.00 | 0.00 | 0.00 | -230458.33 | 0.00 | 0.00 | 194.98 | 222.75 | 4641.11 | 122172.26 | 0.00 | 1788.17 | 101439.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 07-MAY-14:11 | 0.00 | 0.00 | 0.00 | -21026.18 | 0.00 | 0.00 | 35.63 | 34.57 | 720.18 | 6520.41 | 0.00 | 673.94 | 13041.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 26-MAR-09:42 | 0.00 | 0.00 | 0.00 | -19579.18 | 0.00 | 0.00 | 21.64 | 22.28 | 464.11 | 9546.47 | 0.00 | 219.05 | 9305.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 31-DEC-13:51 | 0.00 | 0.00 | 0.00 | -21116.87 | 0.00 | 0.00 | 32.30 | 34.57 | 720.19 | 11886.62 | 0.00 | 105.31 | 8337.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-APR-15:31 | 0.00 | 0.00 | 0.00 | -25019.00 | 0.00 | 0.00 | 18.23 | 22.28 | 464.11 | 12071.61 | 0.00 | 199.27 | 12243.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 09-APR-17:33 | 0.00 | 0.00 | 0.00 | -7791.69 | 0.00 | 0.00 | 0.00 | 13.53 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16.26 |
DATACENTER_MID_ZN_6 | 24-DEC-17:30 | 0.00 | 0.00 | 0.00 | -73908.59 | 0.00 | 0.00 | 50.89 | 135.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4221.84 |
DATACENTER_TOP_ZN_6 | 24-DEC-17:30 | 0.00 | 0.00 | 0.00 | -7556.95 | 0.00 | 0.00 | 5.02 | 13.53 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -256.02 |
DATACENTER_BASEMENT_ZN_6 | 23-AUG-21:02 | 0.00 | 0.00 | 0.00 | -369641.86 | 0.00 | 0.00 | 108.35 | 363.31 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10462.31 |
GROUNDFLOOR_PLENUM | 08-MAY-05:15 | 0.00 | -17238.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 17233.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 02-JAN-06:15 | 0.00 | -141638.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141638.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-DEC-13:05 | 0.00 | -21555.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.14 | 21475.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-DEC-06:02 | 0.00 | -110899.56 | 0.00 | -1887071.09 | 0.00 | 0.00 | 16358.51 | 10397.58 | 616289.16 | 19077.50 | 0.00 | 0.00 | 1348709.62 | 0.00 | -12333.78 | 0.00 | -527.94 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-MAY-16:01 | 0.00 | 0.00 | 23147.00 | 0.00 | 0.00 | 0.00 | 520.12 | 644.26 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37768.92 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 23-OCT-04:12 | 7196.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -110.14 | -7085.94 |
MIDFLOOR_PLENUM | 23-APR-14:51 | 60638.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8355.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -68993.93 |
TOPFLOOR_PLENUM | 23-JAN-05:12 | 9939.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -271.57 | -9667.67 |
Total Facility | 21-AUG-03:02 | -1445948.48 | 1509260.84 | 0.00 | -1509260.84 | 0.00 | 0.00 | 0.00 | 10053.57 | 587299.42 | 0.00 | 0.00 | 0.00 | 877513.02 | 0.00 | -27252.20 | 0.00 | -1665.33 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.8180 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.0155 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 93.1273 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 84.4750 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.5820 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.1852 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.1912 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.1912 | 0.2312 | 1.0000 | Not calculated | 1.2002 | 0.2312 | ||
AIRLOOP DATACENTER BASEMENT | 21.2792 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2795 | 0.0159 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4605 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4606 | 0.0339 | 1.0000 | Not calculated | 0.0156 | 0.0339 | ||
AIRLOOP DATACENTER MID | 4.3900 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3900 | 0.0356 | 1.0000 | Not calculated | 0.1563 | 0.0356 | ||
AIRLOOP DATACENTER TOP | 0.4475 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4475 | 0.0349 | 1.0000 | Not calculated | 0.0156 | 0.0349 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.9090 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2871 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 46.5637 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8633 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.7910 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2818 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.1912 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.1912 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2312 | ||
AIRLOOP DATACENTER BASEMENT | 21.2792 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2792 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4605 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4605 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0339 | ||
AIRLOOP DATACENTER MID | 4.3900 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3900 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0356 | ||
AIRLOOP DATACENTER TOP | 0.4475 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4475 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0349 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1912 | 5.1912 | 5.1912 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5073 | 5.5073 | 1.6191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 51.8837 | 51.8837 | 16.1877 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1425 | 5.1425 | 1.6147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0207 | 1.0207 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9857 | 0.9857 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9872 | 0.9872 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3171 | 1.3171 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8901 | 9.8901 | 2.0275 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.2560 | 10.2560 | 1.3128 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5138 | 9.5138 | 2.0264 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.5838 | 11.5838 | 1.3090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1038 | 1.1038 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0375 | 1.0375 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0666 | 1.0666 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2317 | 1.2317 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4605 | 0.4605 | 0.4605 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3900 | 4.3900 | 4.3900 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4475 | 0.4475 | 0.4475 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2792 | 21.2792 | 21.2792 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.8180 | 9.0155 | 9.8180 | 2.2871 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 93.1273 | 84.4750 | 93.1273 | 22.8633 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.5820 | 9.1852 | 9.5820 | 2.2818 | 0.0000 | 1.0000 |
CAV_BAS | 5.1912 | 5.1912 | 5.1912 | 5.1912 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2792 | 21.2795 | 21.2792 | 21.2792 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4605 | 0.4606 | 0.4605 | 0.4605 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3900 | 4.3900 | 4.3900 | 4.3900 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4475 | 0.4475 | 0.4475 | 0.4475 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1912 | 5.1912 | 5.1912 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7536 | 2.7536 | 1.6191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.9418 | 25.9418 | 16.1877 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5712 | 2.5712 | 1.6147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5104 | 0.5104 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4928 | 0.4928 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4936 | 0.4936 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6586 | 0.6586 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9451 | 4.9451 | 2.0275 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1280 | 5.1280 | 1.3128 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7569 | 4.7569 | 2.0264 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7919 | 5.7919 | 1.3090 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5519 | 0.5519 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5187 | 0.5187 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5333 | 0.5333 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6158 | 0.6158 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4605 | 0.4605 | 0.4605 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3900 | 4.3900 | 4.3900 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4475 | 0.4475 | 0.4475 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2792 | 21.2792 | 21.2792 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.9090 | 2.2871 | 2.2871 | 2.2871 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 46.5637 | 22.8633 | 22.8633 | 22.8633 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.7910 | 2.2818 | 2.2818 | 2.2818 | 0.0000 | 1.0000 |
CAV_BAS | 5.1912 | 5.1912 | 5.1912 | 5.1912 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2792 | 21.2792 | 21.2792 | 21.2792 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4605 | 0.4605 | 0.4605 | 0.4605 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3900 | 4.3900 | 4.3900 | 4.3900 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4475 | 0.4475 | 0.4475 | 0.4475 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 46320.38 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1678.67 |
Number of hours not met | 1678.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6575.25 | 423883.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1951.14 | 184260.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 259.80 | 31088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.45 | 3379.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1144.44 | 70012.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 4.90 | 315.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2748.25 | 216794.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 932.26 | 62089.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2290.11 | 83172.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 107.44 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 576.68 | 61877.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30744.44 |
Natural Gas | 0.00 | 576.68 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31321.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 589.44 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 42.12 |
Space Heating | 0.00 |
Space Cooling | 141.95 |
Fans (All) | 59.33 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 663.73 |
Subtotal | 663.73 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 12.45 |
Miscellaneous (All) | 12.45 |
Subtotal | 12.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.23 |
Space Heating | 0.00 |
Space Cooling | 20.99 |
Fans (All) | 8.77 |
Service Water Heating | 1.84 |
Receptacle Equipment | 46.86 |
Miscellaneous | 15.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2123. | 8760. |
LTG_SCH_DATACENTER | 2757. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1001. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6656.17 | 2103.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8416.67 | 343.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8299.50 | 460.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8263.67 | 496.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6498.83 | 2261.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7948.33 | 811.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7459.17 | 1300.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7423.67 | 1336.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6526.83 | 2233.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7756.50 | 1003.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7330.33 | 1429.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7337.17 | 1422.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6505.67 | 2254.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8.33 | 8751.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 9.17 | 8750.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8.17 | 8751.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8551.67 | 208.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7969.83 | 790.17 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 5.67 | 0.00 | 0.00 | 0.00 |
Max | 8754.33 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 6431.78 | 2328.22 | 0.00 | 0.00 | 0.00 |
Sum | 147931.00 | 53549.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 363082.50 | 5533.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330808.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330808.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330799.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 363082.50 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 75302.02 | 5032.89 | 0.00 | 0.00 | 0.00 |
Sum | 1731946.50 | 115756.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 2703.50 | 6056.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 6503.33 | 2256.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 6533.00 | 2227.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 5791.17 | 2968.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 4837.17 | 3922.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 4997.33 | 3762.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 4716.00 | 4044.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 4666.33 | 4093.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 4590.17 | 4169.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 4583.67 | 4176.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 4567.50 | 4192.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 4581.17 | 4178.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 4546.67 | 4213.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 4554.33 | 4205.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 4533.00 | 4227.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 4560.83 | 4199.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 195.00 | 8565.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 198.50 | 8561.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 186.50 | 8573.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 162.00 | 8598.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3183.50 | 5576.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1908.17 | 6851.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 945.83 | 7814.17 | 0.00 | 0.00 | 0.00 |
Min | 162.00 | 2227.00 | 0.00 | 0.00 | 0.00 |
Max | 6533.00 | 8598.00 | 0.00 | 0.00 | 0.00 |
Average | 3654.12 | 5105.88 | 0.00 | 0.00 | 0.00 |
Sum | 84044.67 | 117435.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 315007.50 | 53608.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 325958.00 | 4855.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 327055.00 | 3758.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 324925.00 | 5888.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38924.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38921.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38868.17 | 56.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18308.00 | 46.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38869.17 | 55.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24881.00 | 28.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38829.67 | 95.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24838.17 | 70.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38834.33 | 90.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24861.50 | 47.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2.17 | 2265.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2.17 | 2265.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2.17 | 2265.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 300.00 | 103095.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 327055.00 | 103095.00 | 0.00 | 0.00 | 0.00 |
Average | 72574.17 | 7760.75 | 0.00 | 0.00 | 0.00 |
Sum | 1669205.83 | 178497.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:56:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.619378E+11 | 81619.49 | 23-JAN-05:53 | 18.70 | 16.92 | 0.567264E+10 | 7499.12 | 25-JAN-14:09 | 30.00 | 22.37 |
February | 0.552199E+11 | 80752.92 | 20-FEB-21:00 | 28.40 | 21.22 | 0.514469E+10 | 7498.99 | 24-FEB-14:39 | 34.00 | 21.29 |
March | 0.638736E+11 | 77207.40 | 14-MAR-03:02 | 25.18 | 22.85 | 0.613795E+10 | 7498.95 | 24-MAR-09:20 | 30.53 | 25.08 |
April | 0.616904E+11 | 77109.56 | 04-APR-03:02 | 26.42 | 24.16 | 0.545496E+10 | 7498.94 | 21-APR-09:20 | 27.90 | 25.74 |
May | 0.628065E+11 | 72014.69 | 27-MAY-03:02 | 24.07 | 24.05 | 0.590562E+10 | 7498.96 | 26-MAY-09:20 | 24.07 | 24.05 |
June | 0.622781E+11 | 73442.14 | 26-JUN-04:23 | 24.00 | 23.75 | 0.588502E+10 | 7498.95 | 01-JUN-09:20 | 24.00 | 23.75 |
July | 0.625703E+11 | 77561.95 | 04-JUL-14:28 | 32.05 | 24.85 | 0.547600E+10 | 7498.95 | 12-JUL-13:20 | 28.17 | 24.56 |
August | 0.680430E+11 | 75041.62 | 29-AUG-03:02 | 25.87 | 25.72 | 0.613936E+10 | 7498.94 | 25-AUG-13:20 | 25.87 | 25.72 |
September | 0.588339E+11 | 73290.35 | 13-SEP-03:02 | 24.92 | 24.22 | 0.545411E+10 | 7498.96 | 08-SEP-09:20 | 24.92 | 24.22 |
October | 0.605351E+11 | 75306.92 | 11-OCT-03:02 | 24.00 | 23.26 | 0.567303E+10 | 7498.96 | 26-OCT-13:20 | 28.07 | 25.80 |
November | 0.606926E+11 | 77780.71 | 25-NOV-04:03 | 24.33 | 20.07 | 0.561759E+10 | 7498.95 | 30-NOV-10:20 | 28.27 | 25.60 |
December | 0.620853E+11 | 81157.60 | 21-DEC-05:12 | 18.00 | 17.36 | 0.547564E+10 | 7499.11 | 21-DEC-14:00 | 30.00 | 22.37 |
Annual Sum or Average | 0.740566E+12 | 0.680366E+11 | ||||||||
Minimum of Months | 0.552199E+11 | 72014.69 | 18.00 | 16.92 | 0.514469E+10 | 7498.94 | 24.00 | 21.29 | ||
Maximum of Months | 0.680430E+11 | 81619.49 | 32.05 | 25.72 | 0.613936E+10 | 7499.12 | 34.00 | 25.80 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.593534E+11 | 88012.10 | 02-JAN-05:13 | 23.27 | 23.03 | 0.507738E+10 | 6734.77 | 18-JAN-14:30 | 32.60 | 23.44 |
February | 0.588199E+11 | 75978.25 | 13-FEB-05:53 | 24.00 | 22.62 | 0.460149E+10 | 6734.67 | 08-FEB-10:20 | 24.00 | 22.62 |
March | 0.699755E+11 | 75805.03 | 06-MAR-06:05 | 24.03 | 21.85 | 0.549434E+10 | 6734.69 | 03-MAR-10:20 | 24.03 | 21.85 |
April | 0.702268E+11 | 76654.18 | 10-APR-04:23 | 25.10 | 23.69 | 0.487964E+10 | 6737.93 | 03-APR-09:09 | 25.10 | 23.69 |
May | 0.630712E+11 | 81281.73 | 09-MAY-05:04 | 24.00 | 24.00 | 0.528426E+10 | 6734.68 | 17-MAY-09:20 | 24.40 | 24.40 |
June | 0.655456E+11 | 72499.56 | 19-JUN-04:23 | 27.00 | 26.27 | 0.526710E+10 | 6734.71 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.667356E+11 | 78929.27 | 18-JUL-05:04 | 24.25 | 23.50 | 0.489442E+10 | 6734.68 | 03-JUL-13:20 | 24.25 | 23.50 |
August | 0.735566E+11 | 75771.29 | 14-AUG-03:02 | 26.90 | 26.09 | 0.549571E+10 | 6734.69 | 03-AUG-09:20 | 26.90 | 26.09 |
September | 0.577328E+11 | 81049.11 | 25-SEP-05:04 | 26.00 | 26.00 | 0.487982E+10 | 6734.68 | 22-SEP-09:20 | 26.00 | 26.00 |
October | 0.624574E+11 | 83517.35 | 12-OCT-03:02 | 24.00 | 24.00 | 0.507345E+10 | 6734.71 | 31-OCT-13:20 | 27.90 | 25.30 |
November | 0.651958E+11 | 79264.48 | 13-NOV-06:04 | 25.13 | 24.29 | 0.502369E+10 | 6734.73 | 09-NOV-14:00 | 25.13 | 24.29 |
December | 0.693419E+11 | 81755.89 | 26-DEC-05:23 | 22.00 | 21.65 | 0.489596E+10 | 6734.75 | 15-DEC-14:39 | 22.00 | 21.65 |
Annual Sum or Average | 0.782012E+12 | 0.608673E+11 | ||||||||
Minimum of Months | 0.577328E+11 | 72499.56 | 22.00 | 21.65 | 0.460149E+10 | 6734.67 | 22.00 | 21.65 | ||
Maximum of Months | 0.735566E+11 | 88012.10 | 27.00 | 26.27 | 0.549571E+10 | 6737.93 | 34.13 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496615E+11 | 81836.86 | 02-JAN-05:15 | 23.27 | 23.03 | 0.507361E+10 | 6734.75 | 31-JAN-14:30 | 32.50 | 22.41 |
February | 0.460758E+11 | 69558.27 | 09-FEB-04:02 | 23.92 | 20.70 | 0.460065E+10 | 6734.70 | 08-FEB-10:20 | 23.92 | 20.70 |
March | 0.533206E+11 | 67067.13 | 03-MAR-05:12 | 22.67 | 20.14 | 0.549271E+10 | 6734.72 | 03-MAR-10:20 | 29.67 | 21.73 |
April | 0.502661E+11 | 61474.26 | 14-APR-05:02 | 25.08 | 24.26 | 0.487299E+10 | 6734.72 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.525671E+11 | 67750.01 | 26-MAY-04:03 | 24.00 | 23.90 | 0.528084E+10 | 6734.73 | 05-MAY-09:20 | 24.00 | 23.90 |
June | 0.524955E+11 | 64092.61 | 27-JUN-05:02 | 23.00 | 23.00 | 0.526542E+10 | 6734.74 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.492937E+11 | 67548.88 | 01-JUL-05:04 | 25.88 | 24.54 | 0.489335E+10 | 6734.72 | 03-JUL-13:20 | 23.60 | 22.70 |
August | 0.511047E+11 | 67359.74 | 21-AUG-05:03 | 24.00 | 24.00 | 0.549531E+10 | 6734.72 | 17-AUG-13:20 | 24.00 | 24.00 |
September | 0.476206E+11 | 70558.67 | 16-SEP-04:12 | 23.67 | 23.18 | 0.487607E+10 | 6734.71 | 14-SEP-13:20 | 23.67 | 23.18 |
October | 0.481831E+11 | 77386.15 | 31-OCT-05:04 | 23.08 | 23.08 | 0.507176E+10 | 6734.74 | 31-OCT-13:20 | 27.90 | 25.30 |
November | 0.476822E+11 | 77121.28 | 09-NOV-06:04 | 24.20 | 23.43 | 0.502381E+10 | 6734.77 | 08-NOV-14:20 | 24.20 | 23.43 |
December | 0.476742E+11 | 79363.58 | 21-DEC-05:12 | 18.00 | 17.36 | 0.489482E+10 | 6734.76 | 15-DEC-14:20 | 18.00 | 17.36 |
Annual Sum or Average | 0.595945E+12 | 0.608413E+11 | ||||||||
Minimum of Months | 0.460758E+11 | 61474.26 | 18.00 | 17.36 | 0.460065E+10 | 6734.70 | 18.00 | 17.36 | ||
Maximum of Months | 0.533206E+11 | 81836.86 | 25.88 | 24.54 | 0.549531E+10 | 6734.77 | 34.13 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516259E+11 | 84524.47 | 02-JAN-05:13 | 23.27 | 23.03 | 0.507680E+10 | 6734.77 | 18-JAN-14:30 | 32.60 | 23.44 |
February | 0.489445E+11 | 73499.10 | 22-FEB-04:02 | 24.25 | 22.54 | 0.460432E+10 | 6734.66 | 23-FEB-10:20 | 24.73 | 20.87 |
March | 0.579531E+11 | 70792.44 | 03-MAR-05:12 | 22.67 | 20.14 | 0.549658E+10 | 6734.69 | 03-MAR-10:20 | 29.67 | 21.73 |
April | 0.555606E+11 | 73550.02 | 15-APR-04:03 | 25.58 | 24.31 | 0.487765E+10 | 6734.69 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.575886E+11 | 76069.42 | 15-MAY-05:04 | 26.00 | 26.00 | 0.528529E+10 | 6734.68 | 17-MAY-09:20 | 24.40 | 24.40 |
June | 0.576013E+11 | 67337.18 | 19-JUN-04:23 | 27.00 | 26.27 | 0.526897E+10 | 6734.72 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.533642E+11 | 69315.72 | 07-JUL-03:02 | 24.12 | 23.50 | 0.489777E+10 | 6734.68 | 03-JUL-13:20 | 24.12 | 23.50 |
August | 0.547169E+11 | 75032.53 | 31-AUG-04:03 | 24.33 | 23.50 | 0.549769E+10 | 6734.68 | 17-AUG-13:20 | 24.33 | 23.50 |
September | 0.516774E+11 | 71669.17 | 16-SEP-04:12 | 23.67 | 23.18 | 0.488022E+10 | 6734.68 | 14-SEP-13:20 | 23.67 | 23.18 |
October | 0.510861E+11 | 74216.61 | 18-OCT-03:02 | 24.55 | 24.13 | 0.507598E+10 | 6734.72 | 13-OCT-13:20 | 24.55 | 24.13 |
November | 0.502658E+11 | 76610.68 | 25-NOV-05:12 | 20.17 | 18.71 | 0.502759E+10 | 6734.76 | 16-NOV-14:20 | 20.17 | 18.71 |
December | 0.494331E+11 | 76932.57 | 14-DEC-06:04 | 21.23 | 20.50 | 0.489796E+10 | 6734.74 | 15-DEC-14:39 | 31.00 | 21.64 |
Annual Sum or Average | 0.639818E+12 | 0.608868E+11 | ||||||||
Minimum of Months | 0.489445E+11 | 67337.18 | 20.17 | 18.71 | 0.460432E+10 | 6734.66 | 20.17 | 18.71 | ||
Maximum of Months | 0.579531E+11 | 84524.47 | 27.00 | 26.27 | 0.549769E+10 | 6734.77 | 34.13 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104106E+11 | 17235.27 | 16-JAN-15:31 | 31.53 | 21.99 | 0.638534E+09 | 845.66 | 18-JAN-14:30 | 32.60 | 23.44 |
February | 0.106905E+11 | 18003.20 | 20-FEB-15:41 | 33.08 | 24.34 | 0.579143E+09 | 845.61 | 07-FEB-14:20 | 33.08 | 24.34 |
March | 0.132637E+11 | 18175.46 | 19-MAR-14:21 | 35.50 | 24.18 | 0.691265E+09 | 845.61 | 03-MAR-14:20 | 35.50 | 24.18 |
April | 0.139052E+11 | 17639.77 | 02-APR-15:01 | 34.75 | 27.18 | 0.614469E+09 | 846.15 | 03-APR-09:09 | 29.67 | 25.81 |
May | 0.143150E+11 | 17825.20 | 07-MAY-12:23 | 34.75 | 26.13 | 0.665786E+09 | 846.02 | 01-MAY-13:09 | 34.75 | 26.13 |
June | 0.160318E+11 | 18043.87 | 25-JUN-16:12 | 30.80 | 27.63 | 0.663540E+09 | 847.93 | 12-JUN-13:00 | 30.80 | 27.63 |
July | 0.140394E+11 | 17680.30 | 04-JUL-15:22 | 31.75 | 25.05 | 0.616809E+09 | 845.70 | 10-JUL-13:00 | 28.00 | 26.07 |
August | 0.143123E+11 | 17652.44 | 13-AUG-15:02 | 33.38 | 28.31 | 0.691385E+09 | 846.20 | 28-AUG-09:50 | 30.92 | 26.75 |
September | 0.111956E+11 | 17845.52 | 04-SEP-15:21 | 32.50 | 27.16 | 0.614247E+09 | 845.61 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.111163E+11 | 17443.72 | 09-OCT-13:52 | 29.10 | 26.09 | 0.638561E+09 | 845.62 | 31-OCT-13:20 | 27.90 | 25.30 |
November | 0.113492E+11 | 14863.11 | 12-NOV-13:32 | 29.63 | 26.54 | 0.632122E+09 | 845.63 | 09-NOV-14:00 | 29.63 | 26.54 |
December | 0.114951E+11 | 17430.79 | 25-DEC-13:22 | 30.50 | 23.89 | 0.615913E+09 | 845.63 | 06-DEC-14:39 | 30.50 | 23.89 |
Annual Sum or Average | 0.152125E+12 | 0.766177E+10 | ||||||||
Minimum of Months | 0.104106E+11 | 14863.11 | 29.10 | 21.99 | 0.579143E+09 | 845.61 | 27.00 | 23.44 | ||
Maximum of Months | 0.160318E+11 | 18175.46 | 35.50 | 28.31 | 0.691385E+09 | 847.93 | 35.50 | 27.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.841161E+10 | 17023.98 | 16-JAN-09:32 | 26.87 | 21.25 | 0.411927E+09 | 544.98 | 18-JAN-14:30 | 32.60 | 23.44 |
February | 0.864624E+10 | 17644.30 | 20-FEB-09:02 | 28.23 | 23.56 | 0.373528E+09 | 544.95 | 07-FEB-14:20 | 28.23 | 23.56 |
March | 0.106084E+11 | 18168.58 | 19-MAR-09:42 | 31.92 | 23.48 | 0.445706E+09 | 545.25 | 29-MAR-09:00 | 32.40 | 24.38 |
April | 0.104007E+11 | 17534.36 | 02-APR-09:02 | 29.27 | 25.31 | 0.396077E+09 | 545.51 | 12-APR-09:00 | 31.60 | 25.20 |
May | 0.990013E+10 | 17588.29 | 28-MAY-08:42 | 30.83 | 27.85 | 0.429068E+09 | 545.25 | 05-MAY-09:00 | 30.83 | 27.85 |
June | 0.102793E+11 | 15949.04 | 11-JUN-09:42 | 32.75 | 28.40 | 0.427409E+09 | 544.95 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.885607E+10 | 13460.07 | 30-JUL-11:43 | 30.92 | 24.48 | 0.397300E+09 | 544.95 | 11-JUL-13:20 | 30.92 | 24.48 |
August | 0.966522E+10 | 17017.70 | 13-AUG-08:23 | 30.00 | 27.70 | 0.445401E+09 | 545.47 | 28-AUG-09:50 | 30.92 | 26.75 |
September | 0.863307E+10 | 17459.24 | 04-SEP-10:02 | 30.17 | 27.22 | 0.396147E+09 | 545.46 | 05-SEP-09:00 | 31.20 | 26.93 |
October | 0.818526E+10 | 16952.67 | 09-OCT-08:32 | 28.33 | 25.91 | 0.411676E+09 | 544.95 | 31-OCT-13:20 | 27.90 | 25.30 |
November | 0.820105E+10 | 12460.58 | 05-NOV-11:02 | 30.58 | 23.10 | 0.407510E+09 | 544.96 | 09-NOV-14:00 | 27.50 | 24.88 |
December | 0.827251E+10 | 16645.54 | 25-DEC-13:22 | 30.50 | 23.89 | 0.397041E+09 | 544.96 | 29-DEC-10:39 | 29.67 | 24.10 |
Annual Sum or Average | 0.110059E+12 | 0.493879E+10 | ||||||||
Minimum of Months | 0.818526E+10 | 12460.58 | 26.87 | 21.25 | 0.373528E+09 | 544.95 | 27.50 | 23.44 | ||
Maximum of Months | 0.106084E+11 | 18168.58 | 32.75 | 28.40 | 0.445706E+09 | 545.51 | 34.17 | 27.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157741E+11 | 19122.39 | 16-JAN-15:31 | 31.53 | 21.99 | 0.646370E+09 | 914.71 | 04-JAN-14:09 | 31.53 | 21.99 |
February | 0.147446E+11 | 18906.29 | 20-FEB-14:21 | 33.00 | 24.27 | 0.583823E+09 | 909.87 | 21-FEB-14:20 | 34.67 | 21.94 |
March | 0.153027E+11 | 18400.11 | 19-MAR-14:21 | 35.50 | 24.18 | 0.691696E+09 | 845.84 | 21-MAR-09:50 | 32.17 | 23.59 |
April | 0.135203E+11 | 17088.69 | 02-APR-15:01 | 34.75 | 27.18 | 0.614366E+09 | 846.19 | 03-APR-13:00 | 32.10 | 25.45 |
May | 0.127409E+11 | 16777.09 | 07-MAY-12:23 | 34.75 | 26.13 | 0.665332E+09 | 845.64 | 01-MAY-13:09 | 34.75 | 26.13 |
June | 0.130604E+11 | 16802.25 | 11-JUN-15:02 | 34.92 | 28.15 | 0.662918E+09 | 845.64 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.122753E+11 | 16437.75 | 02-JUL-16:22 | 28.40 | 23.64 | 0.616379E+09 | 845.63 | 11-JUL-13:20 | 26.07 | 23.52 |
August | 0.133692E+11 | 16874.37 | 13-AUG-15:02 | 33.38 | 28.31 | 0.691154E+09 | 845.63 | 25-AUG-13:20 | 27.67 | 25.56 |
September | 0.117418E+11 | 17430.14 | 04-SEP-15:21 | 32.50 | 27.16 | 0.614377E+09 | 846.04 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.130915E+11 | 17963.44 | 08-OCT-13:52 | 32.50 | 26.17 | 0.639158E+09 | 845.91 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.150341E+11 | 17874.20 | 05-NOV-11:02 | 30.58 | 23.10 | 0.634626E+09 | 873.90 | 29-NOV-14:09 | 30.08 | 24.77 |
December | 0.167310E+11 | 19005.43 | 03-DEC-13:22 | 31.25 | 24.26 | 0.627683E+09 | 999.80 | 26-DEC-13:20 | 31.80 | 23.02 |
Annual Sum or Average | 0.167386E+12 | 0.768788E+10 | ||||||||
Minimum of Months | 0.117418E+11 | 16437.75 | 28.40 | 21.99 | 0.583823E+09 | 845.63 | 26.07 | 21.94 | ||
Maximum of Months | 0.167310E+11 | 19122.39 | 35.50 | 28.31 | 0.691696E+09 | 999.80 | 34.75 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106616E+11 | 24985.71 | 16-JAN-15:31 | 31.53 | 21.99 | 0.412520E+09 | 544.99 | 18-JAN-14:30 | 32.60 | 23.44 |
February | 0.118298E+11 | 25764.48 | 20-FEB-15:41 | 33.08 | 24.34 | 0.374232E+09 | 544.95 | 15-FEB-14:00 | 33.08 | 24.34 |
March | 0.157809E+11 | 26360.59 | 26-MAR-15:01 | 33.90 | 25.32 | 0.446589E+09 | 544.95 | 03-MAR-10:20 | 33.90 | 25.32 |
April | 0.176188E+11 | 25058.64 | 02-APR-15:41 | 33.75 | 27.23 | 0.397046E+09 | 545.41 | 03-APR-09:09 | 29.67 | 25.81 |
May | 0.122796E+11 | 22374.00 | 14-MAY-15:12 | 34.93 | 27.04 | 0.429563E+09 | 544.95 | 01-MAY-13:09 | 34.93 | 27.04 |
June | 0.137892E+11 | 24076.14 | 25-JUN-16:12 | 30.80 | 27.63 | 0.428070E+09 | 544.95 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.134931E+11 | 23728.95 | 04-JUL-16:02 | 31.17 | 25.29 | 0.398369E+09 | 544.95 | 11-JUL-13:20 | 26.07 | 23.52 |
August | 0.165232E+11 | 24142.82 | 27-AUG-15:42 | 32.83 | 25.58 | 0.446594E+09 | 544.95 | 25-AUG-13:20 | 32.83 | 25.58 |
September | 0.108440E+11 | 25487.57 | 04-SEP-16:41 | 32.17 | 26.80 | 0.396646E+09 | 544.95 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.116041E+11 | 24242.18 | 15-OCT-15:42 | 29.42 | 25.55 | 0.412613E+09 | 544.95 | 31-OCT-13:20 | 27.90 | 25.30 |
November | 0.126204E+11 | 22802.73 | 19-NOV-14:42 | 31.58 | 24.91 | 0.408628E+09 | 544.96 | 09-NOV-14:50 | 31.58 | 24.91 |
December | 0.143516E+11 | 24002.02 | 03-DEC-13:22 | 31.25 | 24.26 | 0.398429E+09 | 544.97 | 06-DEC-14:39 | 31.33 | 23.09 |
Annual Sum or Average | 0.161396E+12 | 0.494930E+10 | ||||||||
Minimum of Months | 0.106616E+11 | 22374.00 | 29.42 | 21.99 | 0.374232E+09 | 544.95 | 26.07 | 23.09 | ||
Maximum of Months | 0.176188E+11 | 26360.59 | 34.93 | 27.63 | 0.446594E+09 | 545.41 | 34.93 | 27.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.923635E+10 | 14046.65 | 02-JAN-05:13 | 23.27 | 23.03 | 0.638336E+09 | 845.64 | 26-JAN-14:39 | 31.83 | 22.91 |
February | 0.921008E+10 | 16890.63 | 26-FEB-15:31 | 34.40 | 24.93 | 0.579362E+09 | 845.61 | 08-FEB-10:20 | 34.40 | 24.93 |
March | 0.113681E+11 | 17152.53 | 19-MAR-15:51 | 34.70 | 25.24 | 0.691461E+09 | 845.62 | 03-MAR-14:20 | 34.70 | 25.24 |
April | 0.115457E+11 | 17387.08 | 23-APR-15:31 | 33.30 | 24.65 | 0.614407E+09 | 845.62 | 20-APR-13:20 | 33.30 | 24.65 |
May | 0.136402E+11 | 18365.73 | 07-MAY-14:11 | 34.00 | 26.77 | 0.665989E+09 | 846.59 | 12-MAY-13:20 | 32.60 | 27.63 |
June | 0.150746E+11 | 18764.92 | 18-JUN-16:11 | 32.47 | 27.57 | 0.664009E+09 | 849.27 | 16-JUN-13:00 | 32.47 | 27.57 |
July | 0.121298E+11 | 18212.65 | 04-JUL-15:51 | 31.50 | 25.29 | 0.617247E+09 | 846.58 | 10-JUL-13:20 | 28.67 | 25.83 |
August | 0.115747E+11 | 17593.61 | 13-AUG-16:01 | 29.92 | 26.72 | 0.691730E+09 | 846.64 | 15-AUG-13:20 | 29.93 | 27.33 |
September | 0.101585E+11 | 16228.86 | 03-SEP-12:32 | 31.33 | 27.32 | 0.614202E+09 | 845.61 | 14-SEP-09:20 | 30.27 | 26.50 |
October | 0.938812E+10 | 16935.78 | 08-OCT-14:02 | 32.33 | 26.14 | 0.638772E+09 | 845.62 | 13-OCT-13:20 | 31.60 | 26.55 |
November | 0.914909E+10 | 16908.00 | 19-NOV-14:31 | 31.67 | 24.89 | 0.632334E+09 | 845.63 | 09-NOV-14:00 | 31.67 | 24.89 |
December | 0.859384E+10 | 16776.21 | 31-DEC-14:31 | 32.00 | 24.04 | 0.615876E+09 | 845.62 | 15-DEC-14:20 | 32.00 | 24.04 |
Annual Sum or Average | 0.131069E+12 | 0.766372E+10 | ||||||||
Minimum of Months | 0.859384E+10 | 14046.65 | 23.27 | 23.03 | 0.579362E+09 | 845.61 | 28.67 | 22.91 | ||
Maximum of Months | 0.150746E+11 | 18764.92 | 34.70 | 27.57 | 0.691730E+09 | 849.27 | 34.70 | 27.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.793860E+10 | 17765.74 | 16-JAN-11:02 | 29.63 | 21.29 | 0.304941E+09 | 548.50 | 27-JAN-13:09 | 30.92 | 24.07 |
February | 0.821045E+10 | 17626.85 | 19-FEB-10:02 | 29.08 | 24.05 | 0.276571E+09 | 548.50 | 03-FEB-13:09 | 29.08 | 24.05 |
March | 0.101193E+11 | 19279.25 | 19-MAR-09:12 | 31.07 | 23.07 | 0.329197E+09 | 548.49 | 06-MAR-15:09 | 31.07 | 23.07 |
April | 0.998247E+10 | 18619.72 | 16-APR-09:32 | 30.30 | 25.66 | 0.293211E+09 | 548.48 | 25-APR-12:09 | 32.07 | 26.12 |
May | 0.973610E+10 | 18671.43 | 07-MAY-14:11 | 34.00 | 26.77 | 0.317270E+09 | 548.49 | 30-MAY-14:09 | 27.67 | 26.06 |
June | 0.100500E+11 | 18926.80 | 18-JUN-08:52 | 31.00 | 27.23 | 0.315729E+09 | 548.49 | 30-JUN-10:09 | 31.00 | 27.90 |
July | 0.820457E+10 | 17863.99 | 04-JUL-15:51 | 31.50 | 25.29 | 0.294595E+09 | 548.48 | 11-JUL-12:09 | 25.27 | 24.13 |
August | 0.892365E+10 | 18566.32 | 27-AUG-08:52 | 31.00 | 28.65 | 0.329065E+09 | 548.48 | 25-AUG-14:09 | 31.00 | 28.65 |
September | 0.825437E+10 | 18642.93 | 03-SEP-09:12 | 30.23 | 27.05 | 0.293083E+09 | 548.48 | 06-SEP-10:09 | 31.25 | 27.63 |
October | 0.753382E+10 | 18491.63 | 08-OCT-09:22 | 30.00 | 26.31 | 0.304954E+09 | 548.49 | 13-OCT-14:09 | 30.33 | 26.59 |
November | 0.742949E+10 | 17699.65 | 23-NOV-09:02 | 28.57 | 23.85 | 0.301918E+09 | 548.50 | 16-NOV-13:09 | 28.57 | 23.85 |
December | 0.730382E+10 | 17879.32 | 31-DEC-10:32 | 30.93 | 24.98 | 0.294348E+09 | 548.50 | 27-DEC-11:09 | 30.93 | 24.98 |
Annual Sum or Average | 0.103687E+12 | 0.365488E+10 | ||||||||
Minimum of Months | 0.730382E+10 | 17626.85 | 28.57 | 21.29 | 0.276571E+09 | 548.48 | 25.27 | 23.07 | ||
Maximum of Months | 0.101193E+11 | 19279.25 | 34.00 | 28.65 | 0.329197E+09 | 548.50 | 32.07 | 28.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151940E+11 | 18803.74 | 16-JAN-14:21 | 31.75 | 21.82 | 0.651970E+09 | 950.07 | 04-JAN-14:20 | 31.75 | 21.82 |
February | 0.136689E+11 | 17430.22 | 26-FEB-12:12 | 32.83 | 24.74 | 0.586786E+09 | 918.02 | 21-FEB-14:20 | 32.83 | 24.74 |
March | 0.135737E+11 | 16992.54 | 19-MAR-14:31 | 35.33 | 24.25 | 0.692035E+09 | 846.53 | 07-MAR-14:20 | 35.33 | 24.25 |
April | 0.112904E+11 | 16632.85 | 23-APR-15:31 | 33.30 | 24.65 | 0.614326E+09 | 846.62 | 11-APR-13:20 | 33.30 | 24.65 |
May | 0.118773E+11 | 17129.35 | 07-MAY-14:11 | 34.00 | 26.77 | 0.665472E+09 | 845.63 | 09-MAY-13:20 | 33.93 | 26.91 |
June | 0.117885E+11 | 16990.55 | 18-JUN-16:11 | 32.47 | 27.57 | 0.663133E+09 | 845.64 | 30-JUN-13:20 | 24.60 | 24.14 |
July | 0.102741E+11 | 16745.95 | 04-JUL-15:51 | 31.50 | 25.29 | 0.616696E+09 | 845.63 | 11-JUL-13:20 | 26.07 | 23.52 |
August | 0.107017E+11 | 16578.27 | 13-AUG-16:01 | 29.92 | 26.72 | 0.691460E+09 | 845.63 | 25-AUG-13:20 | 27.67 | 25.56 |
September | 0.107523E+11 | 16371.22 | 24-SEP-13:02 | 31.75 | 27.09 | 0.614392E+09 | 846.62 | 08-SEP-13:20 | 31.75 | 27.09 |
October | 0.116145E+11 | 17511.19 | 29-OCT-11:42 | 31.50 | 26.00 | 0.639478E+09 | 846.53 | 18-OCT-13:20 | 31.50 | 26.00 |
November | 0.133313E+11 | 18158.43 | 19-NOV-14:31 | 31.67 | 24.89 | 0.636032E+09 | 889.43 | 29-NOV-14:20 | 30.07 | 24.78 |
December | 0.145761E+11 | 18556.53 | 31-DEC-13:51 | 32.00 | 24.04 | 0.630091E+09 | 957.32 | 07-DEC-14:20 | 32.00 | 24.04 |
Annual Sum or Average | 0.148643E+12 | 0.770187E+10 | ||||||||
Minimum of Months | 0.102741E+11 | 16371.22 | 29.92 | 21.82 | 0.586786E+09 | 845.63 | 24.60 | 21.82 | ||
Maximum of Months | 0.151940E+11 | 18803.74 | 35.33 | 27.57 | 0.692035E+09 | 957.32 | 35.33 | 27.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860655E+10 | 22075.93 | 16-JAN-15:41 | 31.42 | 22.04 | 0.412145E+09 | 544.98 | 18-JAN-14:30 | 32.60 | 23.44 |
February | 0.881507E+10 | 21012.06 | 26-FEB-15:31 | 34.40 | 24.93 | 0.374024E+09 | 544.94 | 24-FEB-14:20 | 34.40 | 24.93 |
March | 0.111746E+11 | 21813.23 | 05-MAR-16:21 | 29.10 | 23.70 | 0.446381E+09 | 544.95 | 03-MAR-10:20 | 29.10 | 23.70 |
April | 0.109623E+11 | 23051.57 | 23-APR-15:31 | 33.30 | 24.65 | 0.396648E+09 | 544.95 | 24-APR-09:20 | 30.43 | 25.56 |
May | 0.102853E+11 | 21980.99 | 07-MAY-14:11 | 34.00 | 26.77 | 0.429385E+09 | 544.95 | 05-MAY-09:20 | 34.00 | 26.77 |
June | 0.106354E+11 | 22767.64 | 18-JUN-16:11 | 32.47 | 27.57 | 0.427894E+09 | 544.95 | 30-JUN-13:20 | 24.60 | 24.14 |
July | 0.891726E+10 | 22667.20 | 04-JUL-15:51 | 31.50 | 25.29 | 0.398040E+09 | 544.95 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.966964E+10 | 22238.01 | 27-AUG-16:51 | 32.00 | 26.80 | 0.446211E+09 | 544.95 | 25-AUG-13:20 | 32.00 | 26.80 |
September | 0.871471E+10 | 20474.18 | 10-SEP-14:52 | 32.00 | 26.80 | 0.396361E+09 | 544.95 | 14-SEP-09:20 | 30.27 | 26.50 |
October | 0.819718E+10 | 21057.29 | 08-OCT-14:42 | 31.67 | 26.03 | 0.412286E+09 | 544.95 | 13-OCT-13:20 | 31.60 | 26.55 |
November | 0.815992E+10 | 21598.76 | 19-NOV-15:11 | 31.03 | 25.23 | 0.408174E+09 | 544.96 | 09-NOV-14:50 | 31.03 | 25.23 |
December | 0.816266E+10 | 21270.78 | 25-DEC-16:52 | 29.00 | 23.94 | 0.397751E+09 | 544.95 | 15-DEC-14:39 | 29.00 | 23.94 |
Annual Sum or Average | 0.112301E+12 | 0.494530E+10 | ||||||||
Minimum of Months | 0.815992E+10 | 20474.18 | 29.00 | 22.04 | 0.374024E+09 | 544.94 | 24.60 | 23.44 | ||
Maximum of Months | 0.111746E+11 | 23051.57 | 34.40 | 27.57 | 0.446381E+09 | 544.98 | 34.40 | 26.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.947899E+10 | 18540.30 | 29-JAN-17:32 | 30.33 | 23.02 | 0.638365E+09 | 845.66 | 18-JAN-14:30 | 30.33 | 23.02 |
February | 0.961242E+10 | 19049.79 | 05-FEB-14:32 | 32.00 | 25.37 | 0.579453E+09 | 845.61 | 14-FEB-10:20 | 28.93 | 24.10 |
March | 0.120094E+11 | 20281.94 | 26-MAR-15:01 | 33.90 | 25.32 | 0.691606E+09 | 845.61 | 03-MAR-10:20 | 33.90 | 25.32 |
April | 0.123038E+11 | 19977.92 | 23-APR-15:31 | 33.30 | 24.65 | 0.614554E+09 | 845.61 | 20-APR-13:20 | 33.30 | 24.65 |
May | 0.143734E+11 | 21027.21 | 07-MAY-14:11 | 34.00 | 26.77 | 0.666005E+09 | 846.07 | 01-MAY-13:09 | 34.00 | 26.77 |
June | 0.157235E+11 | 19821.13 | 18-JUN-15:02 | 33.20 | 27.18 | 0.663823E+09 | 845.87 | 15-JUN-09:30 | 33.20 | 27.18 |
July | 0.126826E+11 | 20730.13 | 04-JUL-15:51 | 31.50 | 25.29 | 0.617297E+09 | 845.72 | 19-JUL-13:30 | 31.35 | 25.16 |
August | 0.120462E+11 | 20044.02 | 27-AUG-16:51 | 32.00 | 26.80 | 0.691728E+09 | 845.78 | 09-AUG-13:39 | 32.00 | 26.80 |
September | 0.106896E+11 | 19961.46 | 04-SEP-16:11 | 32.67 | 26.80 | 0.614336E+09 | 845.61 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.976718E+10 | 19131.04 | 29-OCT-14:22 | 29.75 | 25.67 | 0.638855E+09 | 845.62 | 13-OCT-13:20 | 29.75 | 25.67 |
November | 0.948174E+10 | 19287.04 | 19-NOV-14:31 | 31.67 | 24.89 | 0.632442E+09 | 845.62 | 09-NOV-14:50 | 31.67 | 24.89 |
December | 0.882519E+10 | 19192.35 | 31-DEC-14:31 | 32.00 | 24.04 | 0.615827E+09 | 845.62 | 06-DEC-14:30 | 32.00 | 24.04 |
Annual Sum or Average | 0.136994E+12 | 0.766429E+10 | ||||||||
Minimum of Months | 0.882519E+10 | 18540.30 | 29.75 | 23.02 | 0.579453E+09 | 845.61 | 28.93 | 23.02 | ||
Maximum of Months | 0.157235E+11 | 21027.21 | 34.00 | 27.18 | 0.691728E+09 | 846.07 | 34.00 | 27.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.832601E+10 | 17906.65 | 16-JAN-09:53 | 27.90 | 21.48 | 0.412040E+09 | 544.98 | 18-JAN-14:30 | 32.60 | 23.44 |
February | 0.870479E+10 | 17930.56 | 05-FEB-14:32 | 32.00 | 25.37 | 0.373893E+09 | 544.95 | 15-FEB-14:00 | 29.00 | 24.59 |
March | 0.108303E+11 | 19583.74 | 26-MAR-09:42 | 32.50 | 25.17 | 0.446158E+09 | 545.22 | 17-MAR-09:00 | 32.50 | 25.17 |
April | 0.107527E+11 | 18970.45 | 23-APR-15:31 | 33.30 | 24.65 | 0.396473E+09 | 545.35 | 12-APR-09:00 | 33.30 | 24.65 |
May | 0.104852E+11 | 19439.51 | 07-MAY-14:11 | 34.00 | 26.77 | 0.429311E+09 | 545.23 | 05-MAY-09:00 | 34.00 | 26.77 |
June | 0.107331E+11 | 18036.16 | 11-JUN-09:42 | 32.75 | 28.40 | 0.427784E+09 | 544.95 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.882782E+10 | 18523.94 | 04-JUL-15:51 | 31.50 | 25.29 | 0.397855E+09 | 544.94 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.952188E+10 | 18881.91 | 27-AUG-08:52 | 31.00 | 28.65 | 0.445977E+09 | 545.36 | 28-AUG-09:00 | 30.90 | 26.65 |
September | 0.887556E+10 | 18880.17 | 04-SEP-16:11 | 32.67 | 26.80 | 0.396342E+09 | 545.40 | 05-SEP-09:00 | 31.20 | 26.93 |
October | 0.804859E+10 | 18086.69 | 08-OCT-08:13 | 28.50 | 25.63 | 0.412086E+09 | 544.95 | 13-OCT-13:20 | 31.60 | 26.55 |
November | 0.790719E+10 | 18050.43 | 19-NOV-14:31 | 31.67 | 24.89 | 0.408015E+09 | 544.95 | 09-NOV-14:50 | 31.67 | 24.89 |
December | 0.769248E+10 | 18334.69 | 31-DEC-14:31 | 32.00 | 24.04 | 0.397560E+09 | 544.96 | 29-DEC-10:39 | 32.00 | 24.04 |
Annual Sum or Average | 0.110706E+12 | 0.494350E+10 | ||||||||
Minimum of Months | 0.769248E+10 | 17906.65 | 27.90 | 21.48 | 0.373893E+09 | 544.94 | 26.00 | 23.44 | ||
Maximum of Months | 0.108303E+11 | 19583.74 | 34.00 | 28.65 | 0.446158E+09 | 545.40 | 34.13 | 26.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155027E+11 | 19873.82 | 29-JAN-11:32 | 29.67 | 23.29 | 0.645612E+09 | 923.66 | 04-JAN-14:20 | 29.67 | 23.29 |
February | 0.141365E+11 | 19652.75 | 05-FEB-14:32 | 32.00 | 25.37 | 0.583166E+09 | 897.73 | 21-FEB-14:30 | 34.50 | 21.90 |
March | 0.142122E+11 | 20271.81 | 26-MAR-15:01 | 33.90 | 25.32 | 0.692083E+09 | 845.84 | 06-MAR-14:00 | 33.90 | 25.32 |
April | 0.120380E+11 | 19209.70 | 23-APR-15:31 | 33.30 | 24.65 | 0.614473E+09 | 846.23 | 03-APR-13:00 | 33.30 | 24.65 |
May | 0.125878E+11 | 19746.38 | 07-MAY-14:11 | 34.00 | 26.77 | 0.665592E+09 | 845.63 | 01-MAY-13:09 | 34.00 | 26.77 |
June | 0.124380E+11 | 18463.85 | 18-JUN-15:02 | 33.20 | 27.18 | 0.663249E+09 | 845.64 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.108076E+11 | 19191.01 | 04-JUL-15:51 | 31.50 | 25.29 | 0.616829E+09 | 845.63 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.111606E+11 | 19045.37 | 27-AUG-16:51 | 32.00 | 26.80 | 0.691504E+09 | 845.63 | 25-AUG-13:20 | 32.00 | 26.80 |
September | 0.112804E+11 | 19419.14 | 04-SEP-16:11 | 32.67 | 26.80 | 0.614491E+09 | 845.87 | 11-SEP-13:30 | 29.85 | 25.77 |
October | 0.120051E+11 | 19826.53 | 29-OCT-11:42 | 31.50 | 26.00 | 0.639477E+09 | 845.80 | 20-OCT-13:00 | 31.50 | 26.00 |
November | 0.137235E+11 | 20696.35 | 19-NOV-14:31 | 31.67 | 24.89 | 0.634042E+09 | 866.20 | 29-NOV-14:20 | 30.07 | 24.78 |
December | 0.149075E+11 | 21121.62 | 31-DEC-13:51 | 32.00 | 24.04 | 0.624147E+09 | 948.72 | 26-DEC-13:20 | 32.00 | 24.04 |
Annual Sum or Average | 0.154800E+12 | 0.768466E+10 | ||||||||
Minimum of Months | 0.108076E+11 | 18463.85 | 29.67 | 23.29 | 0.583166E+09 | 845.63 | 26.00 | 21.90 | ||
Maximum of Months | 0.155027E+11 | 21121.62 | 34.00 | 27.18 | 0.692083E+09 | 948.72 | 34.50 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.872859E+10 | 22678.72 | 29-JAN-17:32 | 30.33 | 23.02 | 0.412129E+09 | 544.99 | 18-JAN-14:30 | 30.33 | 23.02 |
February | 0.906795E+10 | 22109.79 | 26-FEB-15:42 | 34.25 | 25.06 | 0.374033E+09 | 544.95 | 15-FEB-14:00 | 34.25 | 25.06 |
March | 0.116092E+11 | 24754.57 | 26-MAR-15:01 | 33.90 | 25.32 | 0.446407E+09 | 544.95 | 03-MAR-10:20 | 33.90 | 25.32 |
April | 0.114766E+11 | 25025.15 | 23-APR-15:31 | 33.30 | 24.65 | 0.396662E+09 | 544.94 | 20-APR-13:20 | 33.30 | 24.65 |
May | 0.107460E+11 | 23865.09 | 07-MAY-14:11 | 34.00 | 26.77 | 0.429395E+09 | 544.94 | 01-MAY-13:09 | 34.00 | 26.77 |
June | 0.110230E+11 | 22194.45 | 18-JUN-15:42 | 34.00 | 28.01 | 0.427916E+09 | 544.95 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.926070E+10 | 24460.66 | 04-JUL-15:51 | 31.50 | 25.29 | 0.398049E+09 | 544.94 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.995471E+10 | 24088.36 | 27-AUG-16:51 | 32.00 | 26.80 | 0.446188E+09 | 544.94 | 25-AUG-13:20 | 32.00 | 26.80 |
September | 0.905914E+10 | 24547.28 | 04-SEP-16:11 | 32.67 | 26.80 | 0.396382E+09 | 544.94 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.844555E+10 | 22644.11 | 15-OCT-15:52 | 29.40 | 25.43 | 0.412286E+09 | 544.95 | 13-OCT-13:20 | 29.40 | 25.43 |
November | 0.837721E+10 | 23318.16 | 19-NOV-15:11 | 31.03 | 25.23 | 0.408164E+09 | 544.96 | 09-NOV-14:50 | 31.03 | 25.23 |
December | 0.829864E+10 | 23029.86 | 24-DEC-16:31 | 29.67 | 23.46 | 0.397708E+09 | 544.96 | 06-DEC-14:39 | 29.67 | 23.46 |
Annual Sum or Average | 0.116047E+12 | 0.494532E+10 | ||||||||
Minimum of Months | 0.829864E+10 | 22109.79 | 29.40 | 23.02 | 0.374033E+09 | 544.94 | 26.00 | 23.02 | ||
Maximum of Months | 0.116092E+11 | 25025.15 | 34.25 | 28.01 | 0.446407E+09 | 544.99 | 34.25 | 26.91 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111889E+11 | 15839.83 | 02-JAN-06:10 | 23.28 | 23.00 | 0.00 | 0.00 | 01-JAN-00:10 | 23.28 | 23.00 |
February | 0.112167E+11 | 16386.47 | 21-FEB-06:15 | 24.67 | 21.61 | 0.00 | 0.00 | 01-FEB-00:10 | 24.67 | 21.61 |
March | 0.136933E+11 | 15122.72 | 27-MAR-05:15 | 26.00 | 24.56 | 0.00 | 0.00 | 01-MAR-00:10 | 26.00 | 24.56 |
April | 0.138867E+11 | 16132.72 | 17-APR-05:25 | 26.85 | 25.18 | 0.00 | 0.00 | 01-APR-00:10 | 26.85 | 25.18 |
May | 0.128702E+11 | 17240.93 | 08-MAY-05:15 | 27.00 | 26.74 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 26.74 |
June | 0.136702E+11 | 16165.75 | 19-JUN-05:15 | 27.00 | 26.21 | 0.00 | 0.00 | 01-JUN-00:10 | 27.00 | 26.21 |
July | 0.122145E+11 | 15094.54 | 10-JUL-05:13 | 25.10 | 23.55 | 0.00 | 0.00 | 01-JUL-00:10 | 25.10 | 23.55 |
August | 0.132146E+11 | 16080.99 | 14-AUG-05:25 | 26.00 | 26.00 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 26.00 |
September | 0.108186E+11 | 16431.78 | 05-SEP-05:15 | 26.67 | 26.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.67 | 26.15 |
October | 0.107073E+11 | 14944.51 | 10-OCT-05:13 | 24.00 | 23.51 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 23.51 |
November | 0.112970E+11 | 14910.92 | 13-NOV-06:15 | 25.27 | 24.33 | 0.00 | 0.00 | 01-NOV-00:10 | 25.27 | 24.33 |
December | 0.117509E+11 | 15225.94 | 26-DEC-06:15 | 22.33 | 21.42 | 0.00 | 0.00 | 01-DEC-00:10 | 22.33 | 21.42 |
Annual Sum or Average | 0.146529E+12 | 0.00 | ||||||||
Minimum of Months | 0.107073E+11 | 14910.92 | 22.33 | 21.42 | 0.00 | 0.00 | 22.33 | 21.42 | ||
Maximum of Months | 0.138867E+11 | 17240.93 | 27.00 | 26.74 | 0.00 | 0.00 | 27.00 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.959088E+10 | 14166.95 | 02-JAN-06:15 | 23.37 | 23.04 | 0.00 | 0.00 | 01-JAN-00:10 | 23.37 | 23.04 |
February | 0.941766E+10 | 12581.80 | 06-FEB-06:15 | 23.90 | 22.57 | 0.00 | 0.00 | 01-FEB-00:10 | 23.90 | 22.57 |
March | 0.110842E+11 | 10340.26 | 20-MAR-05:02 | 25.67 | 22.37 | 0.00 | 0.00 | 01-MAR-00:10 | 25.67 | 22.37 |
April | 0.106051E+11 | 9510.67 | 03-APR-05:01 | 27.00 | 24.88 | 0.00 | 0.00 | 01-APR-00:10 | 27.00 | 24.88 |
May | 0.111135E+11 | 12569.58 | 08-MAY-05:02 | 27.00 | 26.87 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 26.87 |
June | 0.116159E+11 | 12562.85 | 19-JUN-05:02 | 27.00 | 26.21 | 0.00 | 0.00 | 01-JUN-00:10 | 27.00 | 26.21 |
July | 0.964919E+10 | 10266.28 | 31-JUL-05:03 | 24.15 | 23.23 | 0.00 | 0.00 | 01-JUL-00:10 | 24.15 | 23.23 |
August | 0.992400E+10 | 11327.75 | 28-AUG-05:13 | 25.00 | 25.00 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 25.00 |
September | 0.923706E+10 | 10728.08 | 05-SEP-05:15 | 26.67 | 26.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.67 | 26.15 |
October | 0.871873E+10 | 13770.79 | 10-OCT-05:13 | 24.00 | 23.51 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 23.51 |
November | 0.897102E+10 | 12141.05 | 13-NOV-06:15 | 25.27 | 24.33 | 0.00 | 0.00 | 01-NOV-00:10 | 25.27 | 24.33 |
December | 0.884479E+10 | 11200.72 | 18-DEC-06:15 | 23.13 | 23.13 | 0.00 | 0.00 | 01-DEC-00:10 | 23.13 | 23.13 |
Annual Sum or Average | 0.118772E+12 | 0.00 | ||||||||
Minimum of Months | 0.871873E+10 | 9510.67 | 23.13 | 22.37 | 0.00 | 0.00 | 23.13 | 22.37 | ||
Maximum of Months | 0.116159E+11 | 14166.95 | 27.00 | 26.87 | 0.00 | 0.00 | 27.00 | 26.87 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134029E+11 | 18234.28 | 31-JAN-15:10 | 32.02 | 22.35 | 0.00 | 0.00 | 01-JAN-00:10 | 32.02 | 22.35 |
February | 0.138517E+11 | 18709.99 | 21-FEB-14:40 | 34.33 | 21.86 | 0.00 | 0.00 | 01-FEB-00:10 | 34.33 | 21.86 |
March | 0.174467E+11 | 20144.85 | 29-MAR-14:20 | 35.33 | 23.94 | 0.00 | 0.00 | 01-MAR-00:10 | 35.33 | 23.94 |
April | 0.172827E+11 | 20966.43 | 11-APR-14:20 | 34.87 | 26.08 | 0.00 | 0.00 | 01-APR-00:10 | 34.87 | 26.08 |
May | 0.171086E+11 | 20885.86 | 05-MAY-13:40 | 36.13 | 27.07 | 0.00 | 0.00 | 01-MAY-00:10 | 36.13 | 27.07 |
June | 0.178126E+11 | 19728.86 | 16-JUN-14:20 | 34.67 | 27.41 | 0.00 | 0.00 | 01-JUN-00:10 | 34.67 | 27.41 |
July | 0.144616E+11 | 18322.89 | 14-JUL-14:00 | 32.00 | 24.80 | 0.00 | 0.00 | 01-JUL-00:10 | 32.00 | 24.80 |
August | 0.148142E+11 | 19705.92 | 14-AUG-14:00 | 33.00 | 27.70 | 0.00 | 0.00 | 01-AUG-00:10 | 33.00 | 27.70 |
September | 0.141209E+11 | 19839.27 | 06-SEP-14:30 | 33.50 | 26.76 | 0.00 | 0.00 | 01-SEP-00:10 | 33.50 | 26.76 |
October | 0.124521E+11 | 17392.46 | 04-OCT-14:20 | 32.83 | 26.21 | 0.00 | 0.00 | 01-OCT-00:10 | 32.83 | 26.21 |
November | 0.127626E+11 | 16046.60 | 22-NOV-13:05 | 31.50 | 24.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.50 | 24.57 |
December | 0.124939E+11 | 21555.34 | 26-DEC-13:05 | 32.00 | 23.12 | 0.00 | 0.00 | 01-DEC-00:10 | 32.00 | 23.12 |
Annual Sum or Average | 0.178010E+12 | 0.00 | ||||||||
Minimum of Months | 0.124521E+11 | 16046.60 | 31.50 | 21.86 | 0.00 | 0.00 | 31.50 | 21.86 | ||
Maximum of Months | 0.178126E+11 | 21555.34 | 36.13 | 27.70 | 0.00 | 0.00 | 36.13 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470407E+10 | 2331.28 | 16-JAN-17:44 | 27.83 | 21.78 | 95233031.81 | 126.85 | 23-JAN-14:00 | 30.50 | 21.05 |
February | 0.878989E+10 | 4133.87 | 20-FEB-17:30 | 30.00 | 23.63 | 86418180.49 | 126.87 | 16-FEB-10:09 | 30.00 | 23.63 |
March | 0.148000E+11 | 7284.05 | 31-MAR-24:00 | 27.60 | 24.97 | 0.103253E+09 | 126.85 | 15-MAR-09:09 | 27.60 | 24.97 |
April | 0.192485E+11 | 7791.76 | 09-APR-17:33 | 25.67 | 23.83 | 95379405.68 | 140.00 | 18-APR-13:00 | 34.50 | 26.94 |
May | 0.472134E+10 | 3517.54 | 31-MAY-23:55 | 24.10 | 23.98 | 99234443.39 | 126.82 | 01-MAY-13:09 | 24.10 | 23.98 |
June | 0.945470E+10 | 5347.11 | 30-JUN-24:00 | 25.40 | 24.37 | 98994026.48 | 126.88 | 02-JUN-09:09 | 25.40 | 24.37 |
July | 0.147659E+11 | 7280.91 | 31-JUL-24:00 | 25.60 | 24.83 | 91899086.44 | 126.86 | 11-JUL-09:09 | 25.60 | 24.83 |
August | 0.197892E+11 | 7750.46 | 28-AUG-01:32 | 26.13 | 24.55 | 0.106585E+09 | 140.77 | 14-AUG-13:00 | 26.13 | 24.55 |
September | 0.451560E+10 | 3492.31 | 30-SEP-24:00 | 26.30 | 25.39 | 91606297.46 | 126.82 | 25-SEP-13:09 | 26.30 | 25.39 |
October | 0.967583E+10 | 5348.18 | 31-OCT-24:00 | 25.30 | 24.41 | 95264171.07 | 126.88 | 30-OCT-13:09 | 25.30 | 24.41 |
November | 0.142601E+11 | 5930.48 | 19-NOV-17:02 | 29.42 | 25.42 | 94318702.98 | 126.86 | 09-NOV-10:09 | 29.42 | 25.42 |
December | 0.198416E+11 | 7783.96 | 25-DEC-19:52 | 26.00 | 23.88 | 92589482.03 | 132.80 | 08-DEC-14:00 | 26.00 | 23.88 |
Annual Sum or Average | 0.144567E+12 | 0.115077E+10 | ||||||||
Minimum of Months | 0.451560E+10 | 2331.28 | 24.10 | 21.78 | 86418180.49 | 126.82 | 24.10 | 21.05 | ||
Maximum of Months | 0.198416E+11 | 7791.76 | 30.00 | 25.42 | 0.106585E+09 | 140.77 | 34.50 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436129E+10 | 2164.57 | 16-JAN-17:33 | 28.07 | 21.84 | 95230661.23 | 126.84 | 24-JAN-14:00 | 30.70 | 20.80 |
February | 0.835386E+10 | 3842.62 | 20-FEB-17:30 | 30.00 | 23.63 | 86415459.19 | 126.86 | 14-FEB-14:00 | 30.00 | 23.63 |
March | 0.140898E+11 | 6997.73 | 31-MAR-23:55 | 27.60 | 24.97 | 0.103249E+09 | 126.84 | 15-MAR-09:09 | 27.60 | 24.97 |
April | 0.181647E+11 | 7262.18 | 09-APR-15:53 | 26.50 | 24.49 | 94799656.64 | 138.52 | 18-APR-13:00 | 34.50 | 26.94 |
May | 0.436690E+10 | 3441.49 | 31-MAY-23:55 | 24.10 | 23.98 | 99233187.84 | 126.82 | 03-MAY-13:00 | 24.10 | 23.98 |
June | 0.896260E+10 | 5110.37 | 30-JUN-24:00 | 25.40 | 24.37 | 98990328.24 | 126.88 | 19-JUN-13:00 | 25.40 | 24.37 |
July | 0.140379E+11 | 7007.99 | 31-JUL-24:00 | 25.60 | 24.83 | 91895571.72 | 126.85 | 03-JUL-13:09 | 25.60 | 24.83 |
August | 0.187289E+11 | 7275.37 | 13-AUG-17:40 | 28.00 | 26.50 | 0.106200E+09 | 138.83 | 14-AUG-13:00 | 33.00 | 27.70 |
September | 0.415429E+10 | 3377.35 | 30-SEP-23:50 | 26.28 | 25.37 | 91605160.78 | 126.82 | 25-SEP-09:09 | 26.28 | 25.37 |
October | 0.914659E+10 | 5129.97 | 31-OCT-24:00 | 25.30 | 24.41 | 95260291.69 | 126.87 | 30-OCT-13:09 | 25.30 | 24.41 |
November | 0.135790E+11 | 5615.12 | 19-NOV-17:00 | 29.50 | 25.36 | 94315207.33 | 126.85 | 13-NOV-10:09 | 29.50 | 25.36 |
December | 0.188487E+11 | 7390.94 | 24-DEC-17:30 | 28.00 | 23.37 | 92517272.56 | 132.80 | 08-DEC-14:00 | 28.00 | 23.37 |
Annual Sum or Average | 0.136794E+12 | 0.114971E+10 | ||||||||
Minimum of Months | 0.415429E+10 | 2164.57 | 24.10 | 21.84 | 86415459.19 | 126.82 | 24.10 | 20.80 | ||
Maximum of Months | 0.188487E+11 | 7390.94 | 30.00 | 26.50 | 0.106200E+09 | 138.83 | 34.50 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439914E+10 | 2394.48 | 16-JAN-17:33 | 28.07 | 21.84 | 95231033.69 | 126.85 | 23-JAN-14:00 | 30.50 | 21.05 |
February | 0.841601E+10 | 4123.57 | 20-FEB-17:30 | 30.00 | 23.63 | 86415902.31 | 126.86 | 14-FEB-14:09 | 30.00 | 23.63 |
March | 0.141887E+11 | 7008.50 | 31-MAR-23:55 | 27.60 | 24.97 | 0.103250E+09 | 126.84 | 15-MAR-09:09 | 27.60 | 24.97 |
April | 0.183084E+11 | 7443.16 | 23-APR-17:50 | 30.75 | 24.93 | 94040736.49 | 137.65 | 18-APR-13:00 | 30.75 | 24.93 |
May | 0.448760E+10 | 3439.98 | 31-MAY-23:55 | 24.10 | 23.98 | 99233189.56 | 126.82 | 03-MAY-13:00 | 24.10 | 23.98 |
June | 0.907014E+10 | 5058.42 | 30-JUN-24:00 | 25.40 | 24.37 | 98991417.40 | 126.88 | 02-JUN-13:09 | 25.40 | 24.37 |
July | 0.141353E+11 | 6999.53 | 31-JUL-24:00 | 25.60 | 24.83 | 91896363.60 | 126.85 | 03-JUL-13:09 | 25.60 | 24.83 |
August | 0.188284E+11 | 7456.99 | 13-AUG-17:30 | 28.00 | 26.50 | 0.105268E+09 | 137.83 | 14-AUG-13:00 | 33.00 | 27.70 |
September | 0.425538E+10 | 3407.16 | 30-SEP-23:50 | 26.28 | 25.37 | 91605162.39 | 126.82 | 25-SEP-13:00 | 26.28 | 25.37 |
October | 0.921515E+10 | 5113.97 | 31-OCT-24:00 | 25.30 | 24.41 | 95261281.38 | 126.87 | 25-OCT-13:00 | 25.30 | 24.41 |
November | 0.136331E+11 | 5869.98 | 19-NOV-17:00 | 29.50 | 25.36 | 94315989.12 | 126.85 | 13-NOV-10:09 | 29.50 | 25.36 |
December | 0.188876E+11 | 7557.03 | 24-DEC-17:30 | 28.00 | 23.37 | 92161085.62 | 131.17 | 08-DEC-14:00 | 28.00 | 23.37 |
Annual Sum or Average | 0.137825E+12 | 0.114767E+10 | ||||||||
Minimum of Months | 0.425538E+10 | 2394.48 | 24.10 | 21.84 | 86415902.31 | 126.82 | 24.10 | 21.05 | ||
Maximum of Months | 0.188876E+11 | 7557.03 | 30.75 | 26.50 | 0.105268E+09 | 137.83 | 33.00 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243346E+12 | 93189.77 | 17-JAN-17:00 | 28.50 | 21.82 | 0.206231E+10 | 2747.12 | 11-JAN-10:09 | 28.50 | 21.82 |
February | 0.440291E+12 | 184718.70 | 21-FEB-17:00 | 31.30 | 23.84 | 0.187073E+10 | 2746.46 | 16-FEB-10:09 | 31.30 | 23.84 |
March | 0.733141E+12 | 358272.74 | 31-MAR-23:20 | 27.47 | 24.84 | 0.223503E+10 | 2745.82 | 15-MAR-09:09 | 27.47 | 24.84 |
April | 0.937331E+12 | 367781.35 | 21-APR-23:57 | 24.00 | 23.26 | 0.244049E+10 | 3688.84 | 11-APR-13:00 | 24.00 | 23.26 |
May | 0.244553E+12 | 177168.47 | 31-MAY-23:55 | 24.10 | 23.98 | 0.214854E+10 | 2747.09 | 30-MAY-13:09 | 24.10 | 23.98 |
June | 0.472833E+12 | 268511.54 | 30-JUN-24:00 | 25.40 | 24.37 | 0.214306E+10 | 2746.85 | 02-JUN-09:09 | 25.40 | 24.37 |
July | 0.733941E+12 | 359971.17 | 31-JUL-24:00 | 25.60 | 24.83 | 0.198926E+10 | 2745.95 | 03-JUL-13:09 | 25.60 | 24.83 |
August | 0.971186E+12 | 369649.97 | 23-AUG-21:02 | 23.22 | 23.00 | 0.268210E+10 | 3674.54 | 14-AUG-13:50 | 23.22 | 23.00 |
September | 0.236689E+12 | 176753.23 | 30-SEP-24:00 | 26.30 | 25.39 | 0.198362E+10 | 2747.22 | 01-SEP-09:09 | 26.30 | 25.39 |
October | 0.487722E+12 | 268406.78 | 31-OCT-24:00 | 25.30 | 24.41 | 0.206230E+10 | 2746.73 | 30-OCT-13:09 | 25.30 | 24.41 |
November | 0.709529E+12 | 276275.89 | 20-NOV-17:00 | 30.00 | 25.17 | 0.204164E+10 | 2745.92 | 13-NOV-10:09 | 30.00 | 25.17 |
December | 0.974744E+12 | 369558.87 | 26-DEC-22:13 | 22.87 | 19.75 | 0.225295E+10 | 3443.79 | 08-DEC-14:00 | 22.87 | 19.75 |
Annual Sum or Average | 0.718530E+13 | 0.259120E+11 | ||||||||
Minimum of Months | 0.236689E+12 | 93189.77 | 22.87 | 19.75 | 0.187073E+10 | 2745.82 | 22.87 | 19.75 | ||
Maximum of Months | 0.974744E+12 | 369649.97 | 31.30 | 25.39 | 0.268210E+10 | 3688.84 | 31.30 | 25.39 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488589E+09 | 18124.65 | 08-JAN-15:03 | 32.45 |
February | 0.513527E+09 | 18626.19 | 20-FEB-15:40 | 33.07 |
March | 0.451465E+09 | 20660.60 | 19-MAR-14:10 | 35.83 |
April | 0.590630E+09 | 22288.49 | 01-APR-16:01 | 33.92 |
May | 0.554346E+09 | 23144.86 | 06-MAY-16:01 | 34.58 |
June | 0.451178E+09 | 22181.27 | 10-JUN-16:01 | 33.83 |
July | 0.562772E+09 | 20818.73 | 15-JUL-16:01 | 33.17 |
August | 0.408512E+09 | 19968.03 | 13-AUG-13:53 | 34.00 |
September | 0.575340E+09 | 19492.96 | 02-SEP-16:01 | 32.08 |
October | 0.532590E+09 | 16094.77 | 14-OCT-16:02 | 30.00 |
November | 0.394028E+09 | 15848.45 | 04-NOV-16:01 | 29.60 |
December | 0.398298E+09 | 17357.28 | 24-DEC-14:13 | 32.00 |
Annual Sum or Average | 0.592128E+10 | |||
Minimum of Months | 0.394028E+09 | 15848.45 | 29.60 | |
Maximum of Months | 0.590630E+09 | 23144.86 | 35.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36309954.64 | 4923.32 | 08-JAN-15:12 | 32.30 |
February | 29555178.84 | 5755.83 | 26-FEB-14:41 | 35.00 |
March | 31885261.25 | 6000.98 | 26-MAR-14:21 | 34.50 |
April | 44918612.78 | 6557.59 | 23-APR-15:42 | 33.25 |
May | 30270990.07 | 6052.52 | 18-MAY-03:02 | 25.67 |
June | 28418873.90 | 4969.65 | 25-JUN-15:32 | 30.47 |
July | 34917281.82 | 4958.45 | 04-JUL-16:02 | 31.17 |
August | 38676621.11 | 5728.69 | 06-AUG-13:42 | 31.88 |
September | 32975088.75 | 5325.75 | 19-SEP-03:02 | 24.65 |
October | 42125753.37 | 7196.18 | 23-OCT-04:12 | 22.57 |
November | 37366116.82 | 4959.64 | 19-NOV-14:42 | 31.58 |
December | 47003380.70 | 6071.39 | 03-DEC-13:22 | 31.25 |
Annual Sum or Average | 0.434423E+09 | |||
Minimum of Months | 28418873.90 | 4923.32 | 22.57 | |
Maximum of Months | 47003380.70 | 7196.18 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30898943.08 | 4188.85 | 29-JAN-15:21 | 32.15 |
February | 28423711.93 | 5516.07 | 26-FEB-14:51 | 35.00 |
March | 28676140.40 | 5711.91 | 19-MAR-14:31 | 35.33 |
April | 27549373.57 | 6063.77 | 23-APR-14:51 | 33.50 |
May | 30325252.67 | 5119.94 | 14-MAY-15:01 | 34.97 |
June | 25829351.10 | 4772.49 | 18-JUN-14:11 | 35.00 |
July | 28877144.33 | 4928.68 | 04-JUL-15:11 | 31.83 |
August | 27415884.81 | 5760.36 | 21-AUG-03:02 | 24.03 |
September | 28543741.76 | 5667.95 | 18-SEP-03:02 | 25.50 |
October | 32488347.95 | 4503.42 | 08-OCT-14:02 | 32.33 |
November | 31089746.65 | 4863.53 | 19-NOV-13:12 | 32.27 |
December | 33278117.72 | 5013.17 | 18-DEC-05:12 | 23.00 |
Annual Sum or Average | 0.353396E+09 | |||
Minimum of Months | 25829351.10 | 4188.85 | 23.00 | |
Maximum of Months | 33278117.72 | 6063.77 | 35.33 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36703657.22 | 9939.44 | 23-JAN-05:12 | 18.90 |
February | 25069315.87 | 8441.27 | 13-FEB-05:02 | 23.92 |
March | 17345507.46 | 6800.27 | 02-MAR-05:12 | 23.00 |
April | 8623644.22 | 7540.97 | 10-APR-03:02 | 25.03 |
May | 12340743.28 | 5840.97 | 22-MAY-03:02 | 27.00 |
June | 8573073.84 | 4309.03 | 23-JUN-03:02 | 24.40 |
July | 15053244.61 | 6507.74 | 18-JUL-04:12 | 23.93 |
August | 17992371.78 | 5838.99 | 21-AUG-03:02 | 24.03 |
September | 16165497.99 | 6119.61 | 18-SEP-03:02 | 25.50 |
October | 19899523.38 | 6704.98 | 02-OCT-03:02 | 24.00 |
November | 23524966.95 | 7938.65 | 27-NOV-05:12 | 22.00 |
December | 33148061.03 | 8307.51 | 21-DEC-05:12 | 18.00 |
Annual Sum or Average | 0.234440E+09 | |||
Minimum of Months | 8573073.84 | 4309.03 | 18.00 | |
Maximum of Months | 36703657.22 | 9939.44 | 27.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109836E+11 | 11596.96 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.996323E+10 | 11596.96 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.118431E+11 | 11596.96 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.105743E+11 | 11596.96 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.114134E+11 | 11596.96 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.113597E+11 | 11596.96 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.106280E+11 | 11596.96 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.118430E+11 | 11596.96 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.105743E+11 | 11596.96 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.109837E+11 | 11596.96 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.108560E+11 | 11596.96 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.106280E+11 | 11596.96 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.131650E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.996323E+10 | 11596.96 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.118431E+11 | 11596.96 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986407E+10 | 10414.88 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.894768E+10 | 10414.88 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.106359E+11 | 10414.88 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.949645E+10 | 10414.88 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.102500E+11 | 10414.88 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.102018E+11 | 10414.88 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.954466E+10 | 10414.88 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.106359E+11 | 10414.88 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.949645E+10 | 10414.88 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.986410E+10 | 10414.88 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.974941E+10 | 10414.88 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.954468E+10 | 10414.88 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.118231E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.894768E+10 | 10414.88 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.106359E+11 | 10414.88 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986407E+10 | 10414.88 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.894768E+10 | 10414.88 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.106359E+11 | 10414.88 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.949645E+10 | 10414.88 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.102500E+11 | 10414.88 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.102018E+11 | 10414.88 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.954466E+10 | 10414.88 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.106359E+11 | 10414.88 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.949645E+10 | 10414.88 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.986410E+10 | 10414.88 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.974941E+10 | 10414.88 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.954468E+10 | 10414.88 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.118231E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.894768E+10 | 10414.88 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.106359E+11 | 10414.88 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986407E+10 | 10414.88 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.894768E+10 | 10414.88 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.106359E+11 | 10414.88 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.949645E+10 | 10414.88 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.102500E+11 | 10414.88 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.102018E+11 | 10414.88 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.954466E+10 | 10414.88 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.106359E+11 | 10414.88 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.949645E+10 | 10414.88 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.986410E+10 | 10414.88 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.974941E+10 | 10414.88 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.954468E+10 | 10414.88 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.118231E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.894768E+10 | 10414.88 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.106359E+11 | 10414.88 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.722699E+09 | 1002.51 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.648249E+09 | 726.49 | 01-FEB-17:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.748377E+09 | 727.23 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.656900E+09 | 670.89 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.707917E+09 | 682.19 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.697570E+09 | 661.62 | 20-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.658523E+09 | 668.57 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.733611E+09 | 675.74 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.668852E+09 | 675.84 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.701115E+09 | 711.01 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.718959E+09 | 1067.47 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.708709E+09 | 1090.89 | 18-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.837148E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.648249E+09 | 661.62 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.748377E+09 | 1090.89 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.465843E+09 | 673.47 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.418401E+09 | 562.73 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.482861E+09 | 565.42 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.425346E+09 | 427.61 | 13-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.458999E+09 | 438.46 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.453272E+09 | 400.97 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.427915E+09 | 434.41 | 17-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.475036E+09 | 426.97 | 24-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.431701E+09 | 438.62 | 22-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.452174E+09 | 465.44 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.465705E+09 | 710.27 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.457222E+09 | 714.03 | 18-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.541447E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.418401E+09 | 400.97 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.482861E+09 | 714.03 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.711404E+09 | 861.80 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.642271E+09 | 726.51 | 01-FEB-17:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.746746E+09 | 726.51 | 01-MAR-17:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.660112E+09 | 680.69 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.714098E+09 | 702.12 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.705221E+09 | 693.93 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.666398E+09 | 697.16 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.738288E+09 | 692.93 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.669120E+09 | 676.54 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.695993E+09 | 690.86 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.707005E+09 | 986.17 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.695031E+09 | 1035.75 | 18-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.835169E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.642271E+09 | 676.54 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.746746E+09 | 1035.75 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.458120E+09 | 468.18 | 02-JAN-17:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.412897E+09 | 468.18 | 01-FEB-17:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.479836E+09 | 468.18 | 01-MAR-17:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.423966E+09 | 456.39 | 21-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.458036E+09 | 462.80 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.451491E+09 | 457.40 | 20-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.427355E+09 | 459.79 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.474629E+09 | 460.47 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.431000E+09 | 457.08 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.449610E+09 | 466.09 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.454587E+09 | 568.12 | 09-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.447510E+09 | 633.69 | 18-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.536904E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.412897E+09 | 456.39 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.479836E+09 | 633.69 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721755E+09 | 998.30 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.647736E+09 | 726.49 | 01-FEB-17:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.747887E+09 | 726.49 | 01-MAR-17:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.656543E+09 | 663.34 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.707557E+09 | 675.33 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.697304E+09 | 622.20 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.658140E+09 | 660.89 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.733151E+09 | 668.48 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.668313E+09 | 668.56 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.700263E+09 | 705.64 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.717986E+09 | 1064.24 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.707609E+09 | 1088.23 | 18-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.836424E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.647736E+09 | 622.20 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.747887E+09 | 1088.23 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.465290E+09 | 669.00 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.418007E+09 | 555.07 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.482423E+09 | 557.99 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.424987E+09 | 400.97 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.458555E+09 | 433.96 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.452939E+09 | 400.97 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.427553E+09 | 429.68 | 17-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.474652E+09 | 400.97 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.431310E+09 | 434.10 | 22-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.451638E+09 | 462.52 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.464895E+09 | 706.81 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.456460E+09 | 710.67 | 18-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.540871E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.418007E+09 | 400.97 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.482423E+09 | 710.67 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710063E+09 | 842.75 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.642013E+09 | 726.51 | 01-FEB-17:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.746284E+09 | 726.51 | 01-MAR-17:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.659623E+09 | 673.63 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.713256E+09 | 696.25 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.704629E+09 | 687.55 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.665630E+09 | 690.98 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.737587E+09 | 686.55 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.668490E+09 | 669.28 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.695398E+09 | 684.48 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.706507E+09 | 982.47 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.693998E+09 | 1028.68 | 18-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.834348E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.642013E+09 | 669.28 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.746284E+09 | 1028.68 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457822E+09 | 468.18 | 02-JAN-17:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.412665E+09 | 468.18 | 01-FEB-17:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.479636E+09 | 468.18 | 01-MAR-17:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.423656E+09 | 452.92 | 21-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.457588E+09 | 459.71 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.451122E+09 | 454.00 | 20-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.426828E+09 | 456.53 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.474102E+09 | 457.24 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.430549E+09 | 453.64 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.449144E+09 | 463.19 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.454220E+09 | 561.67 | 09-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.447149E+09 | 628.71 | 18-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.536448E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.412665E+09 | 452.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.479636E+09 | 628.71 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721727E+09 | 997.74 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.647722E+09 | 726.49 | 01-FEB-17:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.747847E+09 | 726.49 | 01-MAR-17:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.656512E+09 | 663.04 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.707521E+09 | 675.06 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.697289E+09 | 622.20 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.658127E+09 | 660.58 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.733124E+09 | 668.19 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.668275E+09 | 668.27 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.700197E+09 | 705.43 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.717946E+09 | 1063.81 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.707578E+09 | 1087.80 | 18-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.836386E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.647722E+09 | 622.20 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.747847E+09 | 1087.80 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.465276E+09 | 668.68 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.417985E+09 | 554.61 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.482412E+09 | 557.46 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.424957E+09 | 400.97 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.458499E+09 | 433.80 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.452930E+09 | 400.97 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.427528E+09 | 429.50 | 17-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.474641E+09 | 400.97 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.431299E+09 | 433.94 | 22-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.451618E+09 | 462.41 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.464874E+09 | 706.57 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.456403E+09 | 710.41 | 18-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.540842E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.417985E+09 | 400.97 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.482412E+09 | 710.41 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710057E+09 | 842.05 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.642005E+09 | 726.51 | 01-FEB-17:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.746268E+09 | 726.51 | 01-MAR-17:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.659608E+09 | 673.35 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.713210E+09 | 696.02 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.704581E+09 | 687.31 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.665587E+09 | 690.74 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.737561E+09 | 686.31 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.668452E+09 | 669.00 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.695381E+09 | 684.22 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.706492E+09 | 981.95 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.693983E+09 | 1028.20 | 18-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.834319E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.642005E+09 | 669.00 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.746268E+09 | 1028.20 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457803E+09 | 468.18 | 02-JAN-17:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.412652E+09 | 468.18 | 01-FEB-17:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.479615E+09 | 468.18 | 01-MAR-17:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.423648E+09 | 452.79 | 21-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.457575E+09 | 459.60 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.451113E+09 | 453.87 | 20-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.426797E+09 | 456.41 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.474085E+09 | 457.11 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.430538E+09 | 453.52 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.449131E+09 | 463.08 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.454213E+09 | 561.30 | 09-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.447138E+09 | 628.39 | 18-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.536431E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.412652E+09 | 452.79 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.479615E+09 | 628.39 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232749E+09 | 243.56 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.211120E+09 | 243.56 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.250870E+09 | 243.56 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.224078E+09 | 243.56 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.241809E+09 | 243.56 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.240640E+09 | 243.56 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.225247E+09 | 243.56 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.250870E+09 | 243.56 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.224078E+09 | 243.56 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.232749E+09 | 243.56 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.230021E+09 | 243.56 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.225247E+09 | 243.56 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.278948E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.211120E+09 | 243.56 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.250870E+09 | 243.56 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232749E+09 | 243.56 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.211120E+09 | 243.56 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.250870E+09 | 243.56 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.224078E+09 | 243.56 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.241809E+09 | 243.56 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.240640E+09 | 243.56 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.225247E+09 | 243.56 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.250870E+09 | 243.56 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.224078E+09 | 243.56 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.232749E+09 | 243.56 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.230021E+09 | 243.56 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.225247E+09 | 243.56 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.278948E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.211120E+09 | 243.56 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.250870E+09 | 243.56 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232749E+09 | 243.56 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.211120E+09 | 243.56 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.250870E+09 | 243.56 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.224078E+09 | 243.56 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.241809E+09 | 243.56 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.240640E+09 | 243.56 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.225247E+09 | 243.56 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.250870E+09 | 243.56 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.224078E+09 | 243.56 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.232749E+09 | 243.56 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.230021E+09 | 243.56 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.225247E+09 | 243.56 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.278948E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.211120E+09 | 243.56 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.250870E+09 | 243.56 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.312466E+10 | 3269.85 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.283429E+10 | 3269.85 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.336793E+10 | 3269.85 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.300825E+10 | 3269.85 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.324629E+10 | 3269.85 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.323060E+10 | 3269.85 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.302394E+10 | 3269.85 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.336793E+10 | 3269.85 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.300825E+10 | 3269.85 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.312466E+10 | 3269.85 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.308803E+10 | 3269.85 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.302394E+10 | 3269.85 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.374488E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.283429E+10 | 3269.85 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.336793E+10 | 3269.85 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.109836E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.996323E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.118431E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.105743E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.114134E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.113597E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.106280E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.118430E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.105743E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.109837E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.108560E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.106280E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.131650E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.996323E+10 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.118431E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.986407E+10 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.894768E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.106359E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.949645E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.102500E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.102018E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.954466E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.106359E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.949645E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.986410E+10 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.974941E+10 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.954468E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.118231E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.894768E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.106359E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.986407E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.894768E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.106359E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.949645E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.102500E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.102018E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.954466E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.106359E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.949645E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.986410E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.974941E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.954468E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.118231E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.894768E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.106359E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.986407E+10 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.894768E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.106359E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.949645E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.102500E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.102018E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.954466E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.106359E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.949645E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.986410E+10 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.974941E+10 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.954468E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.118231E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.894768E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.106359E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.722699E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39625123.48 | 25161621.20 |
February | 0.136985E+10 | 0.648249E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58145465.64 | 3514955.75 |
March | 0.163685E+10 | 0.748377E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104891E+09 | 5126441.60 |
April | 0.145243E+10 | 0.656900E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103124E+09 | 791079.79 |
May | 0.157338E+10 | 0.707917E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113139E+09 | 4949559.24 |
June | 0.156900E+10 | 0.697570E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101417E+09 | 4941339.34 |
July | 0.145680E+10 | 0.658523E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60261666.76 | 3519721.65 |
August | 0.163685E+10 | 0.733611E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73916339.11 | 6074949.44 |
September | 0.145243E+10 | 0.668852E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56078793.53 | 5421796.55 |
October | 0.150991E+10 | 0.701115E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45042967.73 | 7656897.64 |
November | 0.149516E+10 | 0.718959E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34465827.11 | 9750180.16 |
December | 0.145680E+10 | 0.708709E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31315082.45 | 24166648.58 |
Annual Sum or Average | 0.181194E+11 | 0.837148E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821421E+09 | 0.101075E+09 |
Minimum of Months | 0.136985E+10 | 0.648249E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31315082.45 | 791079.79 |
Maximum of Months | 0.163685E+10 | 0.748377E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113139E+09 | 25161621.20 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.465843E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25455574.51 | 17765571.03 |
February | 0.882782E+09 | 0.418401E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37785875.11 | 2682042.68 |
March | 0.105485E+10 | 0.482861E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68588833.40 | 3341673.63 |
April | 0.936002E+09 | 0.425346E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70146979.08 | 388730.07 |
May | 0.101394E+10 | 0.458999E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76299674.53 | 2942841.35 |
June | 0.101113E+10 | 0.453272E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70416992.56 | 2776037.38 |
July | 0.938820E+09 | 0.427915E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41842810.88 | 1726305.79 |
August | 0.105485E+10 | 0.475036E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51749827.94 | 2586643.08 |
September | 0.936002E+09 | 0.431701E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36321862.40 | 3747321.25 |
October | 0.973041E+09 | 0.452174E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29459992.00 | 4903014.21 |
November | 0.963541E+09 | 0.465705E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22669827.54 | 6017278.53 |
December | 0.938820E+09 | 0.457222E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20721617.32 | 14946798.65 |
Annual Sum or Average | 0.116768E+11 | 0.541447E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551460E+09 | 63824257.64 |
Minimum of Months | 0.882782E+09 | 0.418401E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20721617.32 | 388730.07 |
Maximum of Months | 0.105485E+10 | 0.482861E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76299674.53 | 17765571.03 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.711404E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35737866.28 | 32078760.43 |
February | 0.136988E+10 | 0.642271E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53472364.16 | 5935580.35 |
March | 0.163688E+10 | 0.746746E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99777118.79 | 6412291.28 |
April | 0.145246E+10 | 0.660112E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104432E+09 | 728807.55 |
May | 0.157341E+10 | 0.714098E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117086E+09 | 4451307.02 |
June | 0.156904E+10 | 0.705221E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107705E+09 | 4199280.15 |
July | 0.145684E+10 | 0.666398E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63154832.68 | 2831728.66 |
August | 0.163688E+10 | 0.738288E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76252082.23 | 5340091.80 |
September | 0.145246E+10 | 0.669120E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55166136.53 | 5587603.82 |
October | 0.150994E+10 | 0.695993E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42178352.33 | 9239914.79 |
November | 0.149520E+10 | 0.707005E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31614592.12 | 12689217.94 |
December | 0.145684E+10 | 0.695031E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28150835.76 | 29596130.20 |
Annual Sum or Average | 0.181198E+11 | 0.835169E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814726E+09 | 0.119091E+09 |
Minimum of Months | 0.136988E+10 | 0.642271E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28150835.76 | 728807.55 |
Maximum of Months | 0.163688E+10 | 0.746746E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117086E+09 | 32078760.43 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.458120E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23974909.02 | 24870201.77 |
February | 0.882782E+09 | 0.412897E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34233375.04 | 7949861.72 |
March | 0.105485E+10 | 0.479836E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58542286.95 | 12792751.47 |
April | 0.936002E+09 | 0.423966E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57388111.56 | 3043400.53 |
May | 0.101394E+10 | 0.458036E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69547214.79 | 5352654.77 |
June | 0.101113E+10 | 0.451491E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61753752.68 | 5541402.17 |
July | 0.938820E+09 | 0.427355E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36641493.95 | 5787089.38 |
August | 0.105485E+10 | 0.474629E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43786707.59 | 13390440.31 |
September | 0.936002E+09 | 0.431000E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33081204.86 | 6967665.40 |
October | 0.973041E+09 | 0.449610E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26106449.66 | 11036821.58 |
November | 0.963541E+09 | 0.454587E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20222362.65 | 14189339.83 |
December | 0.938820E+09 | 0.447510E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18776755.21 | 27988006.36 |
Annual Sum or Average | 0.116768E+11 | 0.536904E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484055E+09 | 0.138910E+09 |
Minimum of Months | 0.882782E+09 | 0.412897E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18776755.21 | 3043400.53 |
Maximum of Months | 0.105485E+10 | 0.479836E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69547214.79 | 27988006.36 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.721755E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90693908.56 | 64590911.22 |
February | 0.136985E+10 | 0.647736E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129904E+09 | 17274108.05 |
March | 0.163685E+10 | 0.747887E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234667E+09 | 21885919.87 |
April | 0.145243E+10 | 0.656543E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236887E+09 | 3929985.82 |
May | 0.157338E+10 | 0.707557E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249341E+09 | 15108838.55 |
June | 0.156900E+10 | 0.697304E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222380E+09 | 17928297.10 |
July | 0.145680E+10 | 0.658140E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133029E+09 | 15341451.46 |
August | 0.163685E+10 | 0.733151E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163629E+09 | 27483415.62 |
September | 0.145243E+10 | 0.668313E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125314E+09 | 15228788.28 |
October | 0.150991E+10 | 0.700263E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98778098.38 | 25472124.42 |
November | 0.149516E+10 | 0.717986E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77351138.27 | 34725113.57 |
December | 0.145680E+10 | 0.707609E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72748732.38 | 70460302.87 |
Annual Sum or Average | 0.181194E+11 | 0.836424E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183472E+10 | 0.329429E+09 |
Minimum of Months | 0.136985E+10 | 0.647736E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72748732.38 | 3929985.82 |
Maximum of Months | 0.163685E+10 | 0.747887E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249341E+09 | 70460302.87 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.465290E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55767404.76 | 49785695.40 |
February | 0.649041E+09 | 0.418007E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81004243.56 | 15593592.04 |
March | 0.773965E+09 | 0.482423E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143301E+09 | 19368851.26 |
April | 0.688021E+09 | 0.424987E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147190E+09 | 3480285.90 |
May | 0.744847E+09 | 0.458555E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163688E+09 | 10205231.42 |
June | 0.742030E+09 | 0.452939E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149223E+09 | 11512665.95 |
July | 0.690839E+09 | 0.427553E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87428893.06 | 10106067.88 |
August | 0.773965E+09 | 0.474652E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104807E+09 | 19987475.07 |
September | 0.688021E+09 | 0.431310E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77407324.02 | 12478649.46 |
October | 0.715730E+09 | 0.451638E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61382201.20 | 20351380.29 |
November | 0.708685E+09 | 0.464895E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47598009.41 | 27063193.43 |
December | 0.690839E+09 | 0.456460E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44126036.83 | 52328441.74 |
Annual Sum or Average | 0.858171E+10 | 0.540871E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116292E+10 | 0.252262E+09 |
Minimum of Months | 0.649041E+09 | 0.418007E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44126036.83 | 3480285.90 |
Maximum of Months | 0.773965E+09 | 0.482423E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163688E+09 | 52328441.74 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.710063E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79608214.40 | 86688052.09 |
February | 0.136988E+10 | 0.642013E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118527E+09 | 26833753.14 |
March | 0.163688E+10 | 0.746284E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221054E+09 | 27796475.33 |
April | 0.145246E+10 | 0.659623E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239316E+09 | 3769747.60 |
May | 0.157341E+10 | 0.713256E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259563E+09 | 13289952.45 |
June | 0.156904E+10 | 0.704629E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239809E+09 | 14665053.61 |
July | 0.145684E+10 | 0.665630E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140404E+09 | 11750911.42 |
August | 0.163688E+10 | 0.737587E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169636E+09 | 24694557.60 |
September | 0.145246E+10 | 0.668490E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123124E+09 | 16145491.93 |
October | 0.150994E+10 | 0.695398E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92577841.40 | 32008161.10 |
November | 0.149520E+10 | 0.706507E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69770433.13 | 45818960.87 |
December | 0.145684E+10 | 0.693998E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62938693.23 | 90078408.84 |
Annual Sum or Average | 0.181198E+11 | 0.834348E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181633E+10 | 0.393540E+09 |
Minimum of Months | 0.136988E+10 | 0.642013E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62938693.23 | 3769747.60 |
Maximum of Months | 0.163688E+10 | 0.746284E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259563E+09 | 90078408.84 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.457822E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55360087.55 | 56839176.22 |
February | 0.882782E+09 | 0.412665E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79511023.92 | 20493705.30 |
March | 0.105485E+10 | 0.479636E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136520E+09 | 29720721.94 |
April | 0.936002E+09 | 0.423656E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137136E+09 | 5367920.80 |
May | 0.101394E+10 | 0.457588E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159327E+09 | 12505695.25 |
June | 0.101113E+10 | 0.451122E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143921E+09 | 13788639.66 |
July | 0.938820E+09 | 0.426828E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85539633.97 | 13442195.54 |
August | 0.105485E+10 | 0.474102E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102807E+09 | 27232615.97 |
September | 0.936002E+09 | 0.430549E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76288762.21 | 15227466.96 |
October | 0.973041E+09 | 0.449144E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60490327.73 | 25337752.51 |
November | 0.963541E+09 | 0.454220E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47351646.83 | 32001926.61 |
December | 0.938820E+09 | 0.447149E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43917809.78 | 59854072.24 |
Annual Sum or Average | 0.116768E+11 | 0.536448E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112817E+10 | 0.311812E+09 |
Minimum of Months | 0.882782E+09 | 0.412665E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43917809.78 | 5367920.80 |
Maximum of Months | 0.105485E+10 | 0.479636E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159327E+09 | 59854072.24 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.721727E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106210E+09 | 83087715.31 |
February | 0.136985E+10 | 0.647722E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153328E+09 | 23952782.63 |
March | 0.163685E+10 | 0.747847E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273884E+09 | 30424783.51 |
April | 0.145243E+10 | 0.656512E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278087E+09 | 5788106.15 |
May | 0.157338E+10 | 0.707521E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297930E+09 | 20249266.94 |
June | 0.156900E+10 | 0.697289E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266116E+09 | 24000434.38 |
July | 0.145680E+10 | 0.658127E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157601E+09 | 21416103.45 |
August | 0.163685E+10 | 0.733124E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194163E+09 | 37052438.15 |
September | 0.145243E+10 | 0.668275E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147179E+09 | 21409171.15 |
October | 0.150991E+10 | 0.700197E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116159E+09 | 35194258.41 |
November | 0.149516E+10 | 0.717946E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90580465.95 | 45891595.87 |
December | 0.145680E+10 | 0.707578E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84497710.26 | 88569833.61 |
Annual Sum or Average | 0.181194E+11 | 0.836386E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216573E+10 | 0.437036E+09 |
Minimum of Months | 0.136985E+10 | 0.647722E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84497710.26 | 5788106.15 |
Maximum of Months | 0.163685E+10 | 0.747847E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297930E+09 | 88569833.61 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.465276E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67812288.44 | 63309006.81 |
February | 0.882782E+09 | 0.417985E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98210046.82 | 21019317.04 |
March | 0.105485E+10 | 0.482412E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171727E+09 | 26447572.62 |
April | 0.936002E+09 | 0.424957E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176189E+09 | 4953639.03 |
May | 0.101394E+10 | 0.458499E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197943E+09 | 13545151.49 |
June | 0.101113E+10 | 0.452930E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180073E+09 | 15334797.43 |
July | 0.938820E+09 | 0.427528E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105388E+09 | 14042476.60 |
August | 0.105485E+10 | 0.474641E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127019E+09 | 26497994.73 |
September | 0.936002E+09 | 0.431299E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93466892.31 | 16866444.07 |
October | 0.973041E+09 | 0.451618E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74256895.43 | 27085093.61 |
November | 0.963541E+09 | 0.464874E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57769005.18 | 35142122.29 |
December | 0.938820E+09 | 0.456403E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53727611.37 | 65573322.46 |
Annual Sum or Average | 0.116768E+11 | 0.540842E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140358E+10 | 0.329817E+09 |
Minimum of Months | 0.882782E+09 | 0.417985E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53727611.37 | 4953639.03 |
Maximum of Months | 0.105485E+10 | 0.482412E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197943E+09 | 65573322.46 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.710057E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97044219.41 | 0.109610E+09 |
February | 0.136988E+10 | 0.642005E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143233E+09 | 35780384.92 |
March | 0.163688E+10 | 0.746268E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261152E+09 | 38389683.32 |
April | 0.145246E+10 | 0.659608E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280676E+09 | 5563465.74 |
May | 0.157341E+10 | 0.713210E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307937E+09 | 17823472.58 |
June | 0.156904E+10 | 0.704581E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283995E+09 | 19989827.95 |
July | 0.145684E+10 | 0.665587E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164530E+09 | 17034137.95 |
August | 0.163688E+10 | 0.737561E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199813E+09 | 33279210.12 |
September | 0.145246E+10 | 0.668452E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144991E+09 | 22553463.89 |
October | 0.150994E+10 | 0.695381E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109903E+09 | 42549715.48 |
November | 0.149520E+10 | 0.706492E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83596208.65 | 59120104.38 |
December | 0.145684E+10 | 0.693983E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76380230.70 | 0.112130E+09 |
Annual Sum or Average | 0.181198E+11 | 0.834319E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215325E+10 | 0.513823E+09 |
Minimum of Months | 0.136988E+10 | 0.642005E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76380230.70 | 5563465.74 |
Maximum of Months | 0.163688E+10 | 0.746268E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307937E+09 | 0.112130E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.457803E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66512775.85 | 72026338.68 |
February | 0.882782E+09 | 0.412652E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95653107.95 | 27004941.89 |
March | 0.105485E+10 | 0.479615E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163557E+09 | 39857079.87 |
April | 0.936002E+09 | 0.423648E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163692E+09 | 7655502.27 |
May | 0.101394E+10 | 0.457575E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191714E+09 | 16523269.30 |
June | 0.101113E+10 | 0.451113E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172800E+09 | 18229067.03 |
July | 0.938820E+09 | 0.426797E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102378E+09 | 18028153.75 |
August | 0.105485E+10 | 0.474085E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123376E+09 | 35672503.76 |
September | 0.936002E+09 | 0.430538E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91172472.77 | 20424261.68 |
October | 0.973041E+09 | 0.449131E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72098787.30 | 32923695.02 |
November | 0.963541E+09 | 0.454213E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56583638.71 | 41145632.55 |
December | 0.938820E+09 | 0.447138E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52600239.38 | 74682377.39 |
Annual Sum or Average | 0.116768E+11 | 0.536431E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135214E+10 | 0.404173E+09 |
Minimum of Months | 0.882782E+09 | 0.412652E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52600239.38 | 7655502.27 |
Maximum of Months | 0.105485E+10 | 0.479615E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191714E+09 | 74682377.39 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.232749E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.211120E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.250870E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.224078E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.241809E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.240640E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.225247E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.250870E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.224078E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.232749E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.230021E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.225247E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.278948E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.211120E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.250870E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.232749E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.211120E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.250870E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.224078E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.241809E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.240640E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.225247E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.250870E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.224078E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.232749E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.230021E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.225247E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.278948E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.211120E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.250870E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.232749E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.211120E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.250870E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.224078E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.241809E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.240640E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.225247E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.250870E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.224078E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.232749E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.230021E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.225247E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.278948E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.211120E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.250870E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.312466E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.283429E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.336793E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.300825E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.324629E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.323060E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.302394E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.336793E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.300825E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.312466E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.308803E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.302394E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.374488E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.283429E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.336793E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62885427.23 | 63251283.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96989182.09 | 14037157.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172263E+09 | 19486974.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179655E+09 | 2975353.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204590E+09 | 10933334.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181885E+09 | 11758292.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112219E+09 | 9671086.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126745E+09 | 18169709.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97488177.71 | 11486101.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77416143.29 | 21255224.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56574270.71 | 29847196.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50921086.47 | 65775624.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141963E+10 | 0.278647E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50921086.47 | 2975353.54 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204590E+09 | 65775624.20 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112808E+09 | 0.115163E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173386E+09 | 29632112.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312641E+09 | 38318675.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337864E+09 | 5294364.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368620E+09 | 20476065.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326635E+09 | 22978548.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202422E+09 | 18295564.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232351E+09 | 34853110.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175893E+09 | 20584260.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138033E+09 | 39922894.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100928E+09 | 58193643.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91595859.50 | 0.124170E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257318E+10 | 0.527882E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91595859.50 | 5294364.72 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368620E+09 | 0.124170E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106920E+09 | 0.133399E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164262E+09 | 35121716.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301848E+09 | 45359406.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333542E+09 | 6811881.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374830E+09 | 25735642.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327447E+09 | 32747418.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178469E+09 | 29826667.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226313E+09 | 45091654.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160994E+09 | 31671173.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119906E+09 | 55820876.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91003873.11 | 71046055.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81752826.84 | 0.141203E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246729E+10 | 0.653835E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81752826.84 | 6811881.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374830E+09 | 0.141203E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11596.96 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11596.96 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11596.96 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11596.96 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11596.96 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11596.96 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11596.96 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11596.96 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11596.96 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11596.96 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11596.96 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11596.96 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11596.96 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11596.96 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10414.88 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10414.88 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10414.88 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10414.88 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10414.88 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10414.88 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10414.88 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10414.88 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10414.88 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10414.88 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10414.88 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10414.88 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10414.88 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10414.88 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10414.88 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10414.88 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10414.88 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10414.88 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10414.88 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10414.88 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10414.88 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10414.88 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10414.88 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10414.88 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10414.88 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10414.88 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10414.88 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10414.88 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10414.88 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10414.88 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10414.88 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10414.88 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10414.88 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10414.88 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10414.88 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10414.88 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10414.88 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10414.88 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10414.88 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10414.88 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10414.88 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10414.88 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1002.51 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 15-JAN-13:00 | 444.80 | 07-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 726.49 | 01-FEB-17:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 264.75 | 20-FEB-15:52 | 46.93 | 20-FEB-07:00 |
March | 2010.79 | 01-MAR-10:09 | 727.23 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 492.82 | 19-MAR-16:00 | 86.78 | 14-MAR-21:50 |
April | 2010.79 | 03-APR-09:09 | 670.89 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.57 | 30-APR-15:45 | 39.19 | 09-APR-16:20 |
May | 2010.79 | 01-MAY-09:09 | 682.19 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.51 | 07-MAY-14:50 | 172.37 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 661.62 | 20-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.78 | 18-JUN-14:30 | 128.21 | 20-JUN-22:55 |
July | 2010.79 | 03-JUL-09:09 | 668.57 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.81 | 04-JUL-14:04 | 82.35 | 02-JUL-13:40 |
August | 2010.79 | 01-AUG-09:09 | 675.74 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.09 | 06-AUG-12:28 | 138.59 | 20-AUG-10:50 |
September | 2010.79 | 01-SEP-09:09 | 675.84 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.36 | 10-SEP-14:52 | 101.94 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 711.01 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.50 | 29-OCT-12:52 | 63.47 | 23-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1067.47 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.71 | 11-NOV-15:55 | 78.91 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1090.89 | 18-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.98 | 24-DEC-14:52 | 145.10 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 661.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 112.98 | 39.19 | |||||
Maximum of Months | 2010.79 | 1090.89 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 492.82 | 444.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 673.47 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.98 | 15-JAN-12:56 | 295.23 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 562.73 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.46 | 20-FEB-16:00 | 51.66 | 20-FEB-07:00 |
March | 1295.83 | 01-MAR-10:09 | 565.42 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 329.39 | 19-MAR-15:44 | 57.64 | 14-MAR-21:50 |
April | 1295.83 | 03-APR-09:09 | 427.61 | 13-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.52 | 02-APR-15:44 | 28.51 | 09-APR-16:20 |
May | 1295.83 | 01-MAY-09:09 | 438.46 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.42 | 07-MAY-15:04 | 112.37 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 400.97 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.08 | 18-JUN-14:24 | 72.97 | 20-JUN-23:20 |
July | 1295.83 | 03-JUL-09:09 | 434.41 | 17-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.85 | 04-JUL-14:06 | 49.30 | 02-JUL-13:40 |
August | 1295.83 | 01-AUG-09:09 | 426.97 | 24-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.09 | 06-AUG-12:28 | 87.30 | 20-AUG-10:50 |
September | 1295.83 | 01-SEP-09:09 | 438.62 | 22-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.23 | 10-SEP-15:00 | 65.31 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 465.44 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.29 | 29-OCT-13:15 | 44.01 | 09-OCT-17:10 |
November | 1295.83 | 01-NOV-09:09 | 710.27 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.84 | 11-NOV-15:42 | 50.44 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 714.03 | 18-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.46 | 31-DEC-12:48 | 92.12 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 400.97 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 75.46 | 28.51 | |||||
Maximum of Months | 1295.83 | 714.03 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 329.39 | 295.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 861.80 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.97 | 15-JAN-12:56 | 491.74 | 07-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 726.51 | 01-FEB-17:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 264.69 | 20-FEB-16:00 | 58.78 | 20-FEB-07:00 |
March | 2010.83 | 01-MAR-10:09 | 726.51 | 01-MAR-17:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 492.82 | 19-MAR-16:00 | 90.61 | 14-MAR-21:50 |
April | 2010.83 | 03-APR-09:09 | 680.69 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.70 | 30-APR-15:45 | 34.81 | 09-APR-16:20 |
May | 2010.83 | 01-MAY-09:09 | 702.12 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.98 | 07-MAY-14:41 | 165.28 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 693.93 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.25 | 18-JUN-14:24 | 113.06 | 20-JUN-23:20 |
July | 2010.83 | 03-JUL-09:09 | 697.16 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.21 | 04-JUL-14:06 | 68.84 | 02-JUL-13:40 |
August | 2010.83 | 01-AUG-09:09 | 692.93 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.26 | 06-AUG-12:28 | 135.79 | 20-AUG-10:50 |
September | 2010.83 | 01-SEP-09:09 | 676.54 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.35 | 10-SEP-14:52 | 102.41 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 690.86 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 29-OCT-13:00 | 77.05 | 29-OCT-17:10 |
November | 2010.83 | 01-NOV-09:09 | 986.17 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.42 | 11-NOV-15:34 | 82.80 | 25-NOV-05:00 |
December | 2010.83 | 01-DEC-10:09 | 1035.75 | 18-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 | 31-DEC-13:00 | 152.87 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 676.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 | 34.81 | |||||
Maximum of Months | 2010.83 | 1035.75 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 492.82 | 491.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 468.18 | 02-JAN-17:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.88 | 15-JAN-12:56 | 382.82 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 468.18 | 01-FEB-17:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.46 | 20-FEB-16:00 | 49.43 | 20-FEB-07:00 |
March | 1295.83 | 01-MAR-10:09 | 468.18 | 01-MAR-17:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.55 | 19-MAR-16:00 | 87.69 | 14-MAR-21:50 |
April | 1295.83 | 03-APR-09:09 | 456.39 | 21-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.95 | 02-APR-15:44 | 70.43 | 09-APR-16:20 |
May | 1295.83 | 01-MAY-09:09 | 462.80 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.34 | 07-MAY-14:50 | 140.13 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 457.40 | 20-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.39 | 18-JUN-14:24 | 124.54 | 20-JUN-22:55 |
July | 1295.83 | 03-JUL-09:09 | 459.79 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.99 | 04-JUL-14:04 | 76.47 | 02-JUL-13:40 |
August | 1295.83 | 01-AUG-09:09 | 460.47 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.14 | 06-AUG-12:25 | 141.96 | 20-AUG-10:50 |
September | 1295.83 | 01-SEP-09:09 | 457.08 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.23 | 10-SEP-15:00 | 90.50 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 466.09 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.91 | 29-OCT-13:15 | 69.21 | 29-OCT-17:10 |
November | 1295.83 | 01-NOV-09:09 | 568.12 | 09-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.92 | 11-NOV-15:34 | 72.46 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 633.69 | 18-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 | 31-DEC-12:45 | 127.59 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 456.39 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 | 49.43 | |||||
Maximum of Months | 1295.83 | 633.69 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 328.55 | 382.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 998.30 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.12 | 15-JAN-13:00 | 927.18 | 07-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 726.49 | 01-FEB-17:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.62 | 20-FEB-15:55 | 107.31 | 26-FEB-06:45 |
March | 2010.79 | 01-MAR-10:09 | 726.49 | 01-MAR-17:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.91 | 19-MAR-15:53 | 198.03 | 14-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 663.34 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 564.37 | 02-APR-15:55 | 89.98 | 22-APR-02:55 |
May | 2010.79 | 01-MAY-09:09 | 675.33 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 824.51 | 07-MAY-14:54 | 377.40 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 622.20 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.90 | 18-JUN-14:14 | 484.53 | 20-JUN-22:55 |
July | 2010.79 | 03-JUL-09:09 | 660.89 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.02 | 04-JUL-13:53 | 198.49 | 02-JUL-13:50 |
August | 2010.79 | 01-AUG-09:09 | 668.48 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 673.91 | 06-AUG-12:47 | 379.40 | 20-AUG-10:55 |
September | 2010.79 | 01-SEP-09:09 | 668.56 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 808.15 | 10-SEP-14:55 | 214.04 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 705.64 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.27 | 29-OCT-13:06 | 170.83 | 22-OCT-17:55 |
November | 2010.79 | 01-NOV-09:09 | 1064.24 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.49 | 11-NOV-16:00 | 186.06 | 26-NOV-10:00 |
December | 2010.79 | 01-DEC-10:09 | 1088.23 | 18-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 264.27 | 31-DEC-12:55 | 342.38 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 622.20 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 264.27 | 89.98 | |||||
Maximum of Months | 2010.79 | 1088.23 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.91 | 927.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 669.00 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.04 | 15-JAN-12:56 | 657.52 | 07-JAN-05:00 |
February | 1239.33 | 01-FEB-08:09 | 555.07 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 434.58 | 20-FEB-15:55 | 116.10 | 20-FEB-07:10 |
March | 1239.33 | 01-MAR-08:09 | 557.99 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 763.26 | 19-MAR-15:53 | 148.58 | 14-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 400.97 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.77 | 30-APR-15:23 | 83.92 | 09-APR-16:00 |
May | 1239.33 | 01-MAY-07:10 | 433.96 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.84 | 07-MAY-14:53 | 257.16 | 08-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 400.97 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.85 | 18-JUN-14:13 | 316.35 | 20-JUN-22:55 |
July | 1239.33 | 03-JUL-07:10 | 429.68 | 17-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.10 | 04-JUL-13:55 | 132.25 | 02-JUL-13:50 |
August | 1239.33 | 01-AUG-07:10 | 400.97 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.14 | 06-AUG-13:28 | 275.94 | 20-AUG-10:43 |
September | 1239.33 | 01-SEP-07:10 | 434.10 | 22-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 542.30 | 10-SEP-14:53 | 149.25 | 15-SEP-22:00 |
October | 1239.33 | 02-OCT-07:10 | 462.52 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.40 | 29-OCT-13:04 | 116.94 | 22-OCT-17:55 |
November | 1239.33 | 01-NOV-07:10 | 706.81 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.71 | 11-NOV-15:58 | 143.04 | 26-NOV-10:00 |
December | 1239.33 | 01-DEC-08:09 | 710.67 | 18-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.88 | 24-DEC-15:05 | 234.02 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 400.97 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 180.88 | 83.92 | |||||
Maximum of Months | 1239.33 | 710.67 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 763.26 | 657.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 842.75 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 304.99 | 15-JAN-12:56 | 1075.83 | 07-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 726.51 | 01-FEB-17:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 623.97 | 20-FEB-15:55 | 125.35 | 19-FEB-06:53 |
March | 2010.83 | 01-MAR-10:09 | 726.51 | 01-MAR-17:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1161.40 | 19-MAR-15:53 | 212.34 | 14-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 673.63 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.18 | 02-APR-15:55 | 86.67 | 22-APR-02:55 |
May | 2010.83 | 01-MAY-09:09 | 696.25 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.09 | 07-MAY-14:54 | 362.67 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 687.55 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 748.89 | 18-JUN-14:14 | 441.07 | 20-JUN-22:55 |
July | 2010.83 | 03-JUL-09:09 | 690.98 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 659.98 | 04-JUL-13:55 | 149.96 | 02-JUL-13:50 |
August | 2010.83 | 01-AUG-09:09 | 686.55 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 684.64 | 06-AUG-12:23 | 374.29 | 20-AUG-10:55 |
September | 2010.83 | 01-SEP-09:09 | 669.28 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 788.44 | 10-SEP-14:55 | 218.55 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 684.48 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 650.22 | 29-OCT-13:08 | 199.55 | 29-OCT-17:00 |
November | 2010.83 | 01-NOV-09:09 | 982.47 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.62 | 11-NOV-15:55 | 221.62 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 1028.68 | 18-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 253.74 | 31-DEC-13:00 | 372.31 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 669.28 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 253.74 | 86.67 | |||||
Maximum of Months | 2010.83 | 1028.68 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1161.40 | 1075.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 468.18 | 02-JAN-17:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.28 | 15-JAN-12:56 | 700.63 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 468.18 | 01-FEB-17:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.46 | 19-FEB-14:52 | 94.15 | 11-FEB-22:00 |
March | 1295.83 | 01-MAR-10:09 | 468.18 | 01-MAR-17:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 774.85 | 19-MAR-15:53 | 154.87 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 452.92 | 21-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.67 | 02-APR-15:40 | 117.53 | 09-APR-16:00 |
May | 1295.83 | 01-MAY-09:09 | 459.71 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.41 | 07-MAY-15:00 | 272.82 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 454.00 | 20-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.58 | 18-JUN-14:16 | 345.29 | 20-JUN-22:55 |
July | 1295.83 | 03-JUL-09:09 | 456.53 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.66 | 04-JUL-13:53 | 147.57 | 02-JUL-13:50 |
August | 1295.83 | 01-AUG-09:09 | 457.24 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 457.69 | 06-AUG-12:10 | 265.37 | 20-AUG-10:43 |
September | 1295.83 | 01-SEP-09:09 | 453.64 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 505.89 | 10-SEP-15:00 | 162.31 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 463.19 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 460.90 | 29-OCT-13:04 | 152.88 | 29-OCT-17:00 |
November | 1295.83 | 01-NOV-09:09 | 561.67 | 09-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.50 | 11-NOV-15:55 | 141.18 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 628.71 | 18-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 172.00 | 31-DEC-12:35 | 248.09 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 452.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 172.00 | 94.15 | |||||
Maximum of Months | 1295.83 | 628.71 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 774.85 | 700.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 997.74 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 367.38 | 15-JAN-12:42 | 1080.25 | 07-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 726.49 | 01-FEB-17:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 783.51 | 20-FEB-15:55 | 138.66 | 26-FEB-07:00 |
March | 2010.79 | 01-MAR-10:09 | 726.49 | 01-MAR-17:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.86 | 19-MAR-15:51 | 249.59 | 14-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 663.04 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 671.29 | 02-APR-15:44 | 118.14 | 09-APR-16:00 |
May | 2010.79 | 01-MAY-09:09 | 675.06 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.94 | 07-MAY-14:54 | 473.86 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 622.20 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 910.43 | 18-JUN-14:02 | 625.73 | 20-JUN-22:55 |
July | 2010.79 | 03-JUL-09:09 | 660.58 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 752.33 | 04-JUL-13:57 | 292.65 | 02-JUL-13:50 |
August | 2010.79 | 01-AUG-09:09 | 668.19 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 824.94 | 06-AUG-12:10 | 463.61 | 20-AUG-10:55 |
September | 2010.79 | 01-SEP-09:09 | 668.27 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 964.06 | 10-SEP-14:55 | 265.24 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 705.43 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 844.00 | 29-OCT-13:06 | 217.97 | 22-OCT-17:55 |
November | 2010.79 | 01-NOV-09:09 | 1063.81 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.25 | 11-NOV-16:00 | 232.31 | 26-NOV-10:00 |
December | 2010.79 | 01-DEC-10:09 | 1087.80 | 18-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 314.35 | 31-DEC-12:35 | 407.26 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 622.20 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 314.35 | 118.14 | |||||
Maximum of Months | 2010.79 | 1087.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.86 | 1080.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 668.68 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 243.70 | 15-JAN-13:08 | 762.95 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 554.61 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.68 | 20-FEB-15:55 | 148.10 | 20-FEB-07:10 |
March | 1295.83 | 01-MAR-10:09 | 557.46 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 901.68 | 19-MAR-15:50 | 184.68 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 400.97 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.69 | 30-APR-15:23 | 125.83 | 09-APR-16:00 |
May | 1295.83 | 01-MAY-09:09 | 433.80 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 660.79 | 07-MAY-14:56 | 320.88 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 400.97 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 635.64 | 18-JUN-14:24 | 406.66 | 20-JUN-22:55 |
July | 1295.83 | 03-JUL-09:09 | 429.50 | 17-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 542.49 | 04-JUL-13:55 | 194.27 | 02-JUL-13:50 |
August | 1295.83 | 01-AUG-09:09 | 400.97 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.50 | 06-AUG-13:28 | 335.61 | 20-AUG-10:43 |
September | 1295.83 | 01-SEP-09:09 | 433.94 | 22-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 667.99 | 10-SEP-14:53 | 189.11 | 03-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 462.41 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 567.85 | 29-OCT-13:04 | 166.65 | 29-OCT-17:00 |
November | 1295.83 | 01-NOV-09:09 | 706.57 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.33 | 19-NOV-13:54 | 178.04 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 710.41 | 18-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 213.19 | 31-DEC-12:35 | 278.09 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 400.97 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 213.19 | 125.83 | |||||
Maximum of Months | 1295.83 | 710.41 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 901.68 | 762.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 842.05 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 329.25 | 15-JAN-13:05 | 1249.85 | 07-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 726.51 | 01-FEB-17:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 766.75 | 20-FEB-15:55 | 161.17 | 26-FEB-07:00 |
March | 2010.83 | 01-MAR-10:09 | 726.51 | 01-MAR-17:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.53 | 19-MAR-15:50 | 266.53 | 14-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 673.35 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 673.02 | 02-APR-15:44 | 113.58 | 09-APR-16:00 |
May | 2010.83 | 01-MAY-09:09 | 696.02 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.39 | 07-MAY-14:54 | 456.84 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 687.31 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 926.08 | 18-JUN-14:24 | 573.41 | 20-JUN-22:55 |
July | 2010.83 | 03-JUL-09:09 | 690.74 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 793.54 | 04-JUL-13:55 | 240.08 | 02-JUL-13:50 |
August | 2010.83 | 01-AUG-09:09 | 686.31 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 813.49 | 06-AUG-12:50 | 457.30 | 20-AUG-10:55 |
September | 2010.83 | 01-SEP-09:09 | 669.00 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 932.52 | 10-SEP-14:55 | 270.79 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 684.22 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 789.46 | 29-OCT-13:06 | 294.37 | 29-OCT-17:00 |
November | 2010.83 | 01-NOV-09:09 | 981.95 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.65 | 11-NOV-15:55 | 276.97 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 1028.20 | 18-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 308.43 | 31-DEC-13:00 | 444.29 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 669.00 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 308.43 | 113.58 | |||||
Maximum of Months | 2010.83 | 1028.20 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.53 | 1249.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 468.18 | 02-JAN-17:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.12 | 15-JAN-13:05 | 820.25 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 468.18 | 01-FEB-17:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 505.66 | 19-FEB-14:52 | 112.37 | 11-FEB-22:30 |
March | 1295.83 | 01-MAR-10:09 | 468.18 | 01-MAR-17:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 901.69 | 19-MAR-15:50 | 193.49 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 452.79 | 21-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.33 | 02-APR-15:44 | 166.32 | 09-APR-16:00 |
May | 1295.83 | 01-MAY-09:09 | 459.60 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.10 | 07-MAY-14:54 | 339.82 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 453.87 | 20-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 618.23 | 18-JUN-14:24 | 442.88 | 20-JUN-22:55 |
July | 1295.83 | 03-JUL-09:09 | 456.41 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 542.35 | 04-JUL-13:53 | 211.29 | 02-JUL-13:50 |
August | 1295.83 | 01-AUG-09:09 | 457.11 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 560.76 | 06-AUG-12:10 | 324.88 | 20-AUG-10:55 |
September | 1295.83 | 01-SEP-09:09 | 453.52 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.92 | 10-SEP-15:00 | 201.11 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 463.08 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.42 | 29-OCT-13:04 | 218.88 | 29-OCT-17:00 |
November | 1295.83 | 01-NOV-09:09 | 561.30 | 09-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.12 | 11-NOV-15:55 | 176.35 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 628.39 | 18-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.72 | 31-DEC-12:35 | 296.79 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 452.79 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 211.72 | 112.37 | |||||
Maximum of Months | 1295.83 | 628.39 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 901.69 | 820.25 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 243.56 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 243.56 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 243.56 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 243.56 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 243.56 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 243.56 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 243.56 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 243.56 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 243.56 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 243.56 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 243.56 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 243.56 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 243.56 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 243.56 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 243.56 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 243.56 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 243.56 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 243.56 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 243.56 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 243.56 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 243.56 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 243.56 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 243.56 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 243.56 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 243.56 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 243.56 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 243.56 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 243.56 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 243.56 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 243.56 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 243.56 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 243.56 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 243.56 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 243.56 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 243.56 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 243.56 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 243.56 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 243.56 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 243.56 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 243.56 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 243.56 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 243.56 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3269.85 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3269.85 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3269.85 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3269.85 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3269.85 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3269.85 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3269.85 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3269.85 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3269.85 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3269.85 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3269.85 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3269.85 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3269.85 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3269.85 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.95 | 15-JAN-13:00 | 978.69 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.08 | 19-FEB-14:52 | 98.79 | 20-FEB-07:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 977.44 | 19-MAR-16:00 | 173.63 | 14-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.82 | 23-APR-14:51 | 63.50 | 22-APR-03:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.66 | 07-MAY-14:51 | 322.14 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.71 | 18-JUN-14:10 | 296.69 | 20-JUN-22:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.74 | 04-JUL-13:52 | 101.03 | 19-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.36 | 06-AUG-12:52 | 251.24 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.67 | 10-SEP-15:00 | 187.58 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.09 | 29-OCT-13:00 | 126.47 | 23-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.44 | 11-NOV-16:00 | 169.63 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.16 | 24-DEC-15:00 | 327.39 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.16 | 63.50 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 977.44 | 978.69 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.68 | 15-JAN-13:00 | 1723.53 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.85 | 19-FEB-15:00 | 170.00 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1800.52 | 19-MAR-16:00 | 310.04 | 03-MAR-05:12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.23 | 30-APR-15:50 | 126.86 | 22-APR-03:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.24 | 07-MAY-15:00 | 558.33 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.14 | 18-JUN-14:20 | 583.95 | 20-JUN-22:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.99 | 04-JUL-14:00 | 184.97 | 19-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.00 | 06-AUG-13:00 | 466.39 | 20-AUG-10:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.67 | 10-SEP-15:00 | 335.90 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.40 | 29-OCT-12:52 | 237.12 | 22-OCT-17:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.36 | 11-NOV-16:00 | 302.96 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.29 | 31-DEC-13:00 | 595.42 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.29 | 126.86 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1800.52 | 1723.53 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.56 | 15-JAN-12:52 | 1748.83 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 863.33 | 19-FEB-15:00 | 234.22 | 05-FEB-17:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1555.53 | 19-MAR-15:51 | 343.46 | 03-MAR-05:15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.67 | 02-APR-15:30 | 148.22 | 22-APR-03:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.22 | 21-MAY-12:00 | 647.81 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.38 | 18-JUN-14:10 | 836.41 | 20-JUN-22:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.42 | 04-JUL-14:00 | 411.90 | 02-JUL-13:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1242.51 | 06-AUG-12:32 | 600.92 | 20-AUG-10:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 888.36 | 10-SEP-15:00 | 388.17 | 03-SEP-16:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.71 | 29-OCT-12:52 | 403.11 | 29-OCT-17:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.75 | 11-NOV-16:00 | 340.30 | 25-NOV-04:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.40 | 24-DEC-15:00 | 626.68 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.40 | 148.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1555.53 | 1748.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81619.49 | 23-JAN-05:53 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80752.92 | 20-FEB-21:00 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77207.40 | 14-MAR-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77109.56 | 04-APR-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72014.69 | 27-MAY-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73442.14 | 26-JUN-04:23 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77561.95 | 04-JUL-14:28 | 5385.68 | 3865.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75041.62 | 29-AUG-03:02 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73290.35 | 13-SEP-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75306.92 | 11-OCT-03:02 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77780.71 | 25-NOV-04:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81157.60 | 21-DEC-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 72014.69 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81619.49 | 5385.68 | 3865.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88012.10 | 02-JAN-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 75978.25 | 13-FEB-05:53 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75805.03 | 06-MAR-06:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76654.18 | 10-APR-04:23 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81281.73 | 09-MAY-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72499.56 | 19-JUN-04:23 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78929.27 | 18-JUL-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75771.29 | 14-AUG-03:02 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81049.11 | 25-SEP-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83517.35 | 12-OCT-03:02 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79264.48 | 13-NOV-06:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81755.89 | 26-DEC-05:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 72499.56 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88012.10 | 9673.43 | 3761.52 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81836.86 | 02-JAN-05:15 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69558.27 | 09-FEB-04:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67067.13 | 03-MAR-05:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61474.26 | 14-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67750.01 | 26-MAY-04:03 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64092.61 | 27-JUN-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67548.88 | 01-JUL-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 67359.74 | 21-AUG-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70558.67 | 16-SEP-04:12 | 0.00 | 2686.80 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77386.15 | 31-OCT-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77121.28 | 09-NOV-06:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79363.58 | 21-DEC-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 61474.26 | 0.00 | 2149.44 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81836.86 | 8061.19 | 3224.16 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84524.47 | 02-JAN-05:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73499.10 | 22-FEB-04:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70792.44 | 03-MAR-05:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73550.02 | 15-APR-04:03 | 0.00 | 2149.44 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76069.42 | 15-MAY-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67337.18 | 19-JUN-04:23 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69315.72 | 07-JUL-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75032.53 | 31-AUG-04:03 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71669.17 | 16-SEP-04:12 | 0.00 | 2686.80 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74216.61 | 18-OCT-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76610.68 | 25-NOV-05:12 | 0.00 | 3224.16 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76932.57 | 14-DEC-06:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 67337.18 | 0.00 | 2149.44 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84524.47 | 8061.19 | 3224.16 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17235.27 | 16-JAN-15:31 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 54.55 | 0.00 |
February | 18003.20 | 20-FEB-15:41 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 210.19 | 0.00 |
March | 18175.46 | 19-MAR-14:21 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 354.99 | 0.00 |
April | 17639.77 | 02-APR-15:01 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 218.78 | 0.00 |
May | 17825.20 | 07-MAY-12:23 | 404.87 | 138.26 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 128.61 | 0.00 |
June | 18043.87 | 25-JUN-16:12 | 607.30 | 207.39 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.56 | 0.00 |
July | 17680.30 | 04-JUL-15:22 | 607.30 | 207.39 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.23 | 0.00 |
August | 17652.44 | 13-AUG-15:02 | 607.30 | 207.39 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.67 | 0.00 |
September | 17845.52 | 04-SEP-15:21 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 144.05 | 0.00 |
October | 17443.72 | 09-OCT-13:52 | 506.08 | 172.83 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 | 0.00 |
November | 14863.11 | 12-NOV-13:32 | 404.87 | 138.26 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 67.35 | 0.00 |
December | 17430.79 | 25-DEC-13:22 | 607.30 | 207.39 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14863.11 | 404.87 | 138.26 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 | |
Maximum of Months | 18175.46 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 354.99 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17023.98 | 16-JAN-09:32 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
February | 17644.30 | 20-FEB-09:02 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 0.00 |
March | 18168.58 | 19-MAR-09:42 | 391.37 | 133.65 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 89.33 | 0.00 |
April | 17534.36 | 02-APR-09:02 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 | 0.00 |
May | 17588.29 | 28-MAY-08:42 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 47.39 | 0.00 |
June | 15949.04 | 11-JUN-09:42 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 159.08 | 0.00 |
July | 13460.07 | 30-JUL-11:43 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 108.80 | 0.00 |
August | 17017.70 | 13-AUG-08:23 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 56.44 | 0.00 |
September | 17459.24 | 04-SEP-10:02 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 0.00 |
October | 16952.67 | 09-OCT-08:32 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 0.00 |
November | 12460.58 | 05-NOV-11:02 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 69.21 | 0.00 |
December | 16645.54 | 25-DEC-13:22 | 391.37 | 133.65 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12460.58 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18168.58 | 391.37 | 133.65 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 159.08 | 0.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19122.39 | 16-JAN-15:31 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 | 0.00 |
February | 18906.29 | 20-FEB-14:21 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 78.67 | 0.00 |
March | 18400.11 | 19-MAR-14:21 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 325.05 | 0.00 |
April | 17088.69 | 02-APR-15:01 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 218.13 | 0.00 |
May | 16777.09 | 07-MAY-12:23 | 404.87 | 138.27 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 135.19 | 0.00 |
June | 16802.25 | 11-JUN-15:02 | 607.31 | 207.40 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 267.32 | 0.00 |
July | 16437.75 | 02-JUL-16:22 | 506.09 | 172.83 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 | 0.00 |
August | 16874.37 | 13-AUG-15:02 | 607.31 | 207.40 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 193.62 | 0.00 |
September | 17430.14 | 04-SEP-15:21 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 140.15 | 0.00 |
October | 17963.44 | 08-OCT-13:52 | 607.31 | 207.40 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 0.00 |
November | 17874.20 | 05-NOV-11:02 | 404.87 | 138.27 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 80.21 | 0.00 |
December | 19005.43 | 03-DEC-13:22 | 607.31 | 207.40 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16437.75 | 404.87 | 138.27 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 0.00 | |
Maximum of Months | 19122.39 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 325.05 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24985.71 | 16-JAN-15:31 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 0.00 |
February | 25764.48 | 20-FEB-15:41 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 | 0.00 |
March | 26360.59 | 26-MAR-15:01 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 126.30 | 0.00 |
April | 25058.64 | 02-APR-15:41 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 116.07 | 0.00 |
May | 22374.00 | 14-MAY-15:12 | 326.14 | 111.38 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 72.59 | 0.00 |
June | 24076.14 | 25-JUN-16:12 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 0.00 |
July | 23728.95 | 04-JUL-16:02 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 102.08 | 0.00 |
August | 24142.82 | 27-AUG-15:42 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 113.29 | 0.00 |
September | 25487.57 | 04-SEP-16:41 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 | 0.00 |
October | 24242.18 | 15-OCT-15:42 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 0.00 |
November | 22802.73 | 19-NOV-14:42 | 326.14 | 111.38 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 | 0.00 |
December | 24002.02 | 03-DEC-13:22 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22374.00 | 326.14 | 111.38 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 0.00 | |
Maximum of Months | 26360.59 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 126.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14046.65 | 02-JAN-05:13 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 |
February | 16890.63 | 26-FEB-15:31 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 559.73 | 0.00 |
March | 17152.53 | 19-MAR-15:51 | 910.95 | 311.09 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.40 | 0.00 |
April | 17387.08 | 23-APR-15:31 | 910.95 | 311.09 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 397.72 | 0.00 |
May | 18365.73 | 07-MAY-14:11 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 589.82 | 0.00 |
June | 18764.92 | 18-JUN-16:11 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 253.50 | 0.00 |
July | 18212.65 | 04-JUL-15:51 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 339.71 | 0.00 |
August | 17593.61 | 13-AUG-16:01 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 191.48 | 0.00 |
September | 16228.86 | 03-SEP-12:32 | 404.87 | 138.26 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 267.63 | 0.00 |
October | 16935.78 | 08-OCT-14:02 | 607.30 | 207.39 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.95 | 0.00 |
November | 16908.00 | 19-NOV-14:31 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 210.86 | 0.00 |
December | 16776.21 | 31-DEC-14:31 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 162.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14046.65 | 0.00 | 138.26 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18764.92 | 910.95 | 404.83 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.40 | 15.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17765.74 | 16-JAN-11:02 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 | 0.00 |
February | 17626.85 | 19-FEB-10:02 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 86.28 | 0.00 |
March | 19279.25 | 19-MAR-09:12 | 391.37 | 133.65 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 150.70 | 0.00 |
April | 18619.72 | 16-APR-09:32 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 90.04 | 0.00 |
May | 18671.43 | 07-MAY-14:11 | 456.59 | 155.93 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 413.10 | 0.00 |
June | 18926.80 | 18-JUN-08:52 | 391.37 | 133.65 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 159.19 | 0.00 |
July | 17863.99 | 04-JUL-15:51 | 521.82 | 178.20 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 280.93 | 0.00 |
August | 18566.32 | 27-AUG-08:52 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 73.05 | 0.00 |
September | 18642.93 | 03-SEP-09:12 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 0.00 |
October | 18491.63 | 08-OCT-09:22 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 45.04 | 0.00 |
November | 17699.65 | 23-NOV-09:02 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 | 0.00 |
December | 17879.32 | 31-DEC-10:32 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 96.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17626.85 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 | 0.00 | |
Maximum of Months | 19279.25 | 521.82 | 178.20 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 413.10 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18803.74 | 16-JAN-14:21 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 0.00 |
February | 17430.22 | 26-FEB-12:12 | 506.09 | 172.83 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 135.60 | 0.00 |
March | 16992.54 | 19-MAR-14:31 | 910.97 | 311.10 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 821.99 | 0.00 |
April | 16632.85 | 23-APR-15:31 | 910.97 | 311.10 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 403.21 | 0.00 |
May | 17129.35 | 07-MAY-14:11 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 637.08 | 0.00 |
June | 16990.55 | 18-JUN-16:11 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 312.94 | 0.00 |
July | 16745.95 | 04-JUL-15:51 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 407.08 | 0.00 |
August | 16578.27 | 13-AUG-16:01 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 216.97 | 0.00 |
September | 16371.22 | 24-SEP-13:02 | 404.87 | 138.27 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 441.62 | 0.00 |
October | 17511.19 | 29-OCT-11:42 | 506.09 | 172.83 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 384.77 | 0.00 |
November | 18158.43 | 19-NOV-14:31 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 135.94 | 0.00 |
December | 18556.53 | 31-DEC-13:51 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 94.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16371.22 | 404.87 | 138.27 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 0.00 | |
Maximum of Months | 18803.74 | 910.97 | 311.10 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 821.99 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22075.93 | 16-JAN-15:41 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 | 0.00 |
February | 21012.06 | 26-FEB-15:31 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 329.23 | 0.00 |
March | 21813.23 | 05-MAR-16:21 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 | 0.00 |
April | 23051.57 | 23-APR-15:31 | 587.05 | 200.48 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.82 | 0.00 |
May | 21980.99 | 07-MAY-14:11 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 370.58 | 0.00 |
June | 22767.64 | 18-JUN-16:11 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 144.85 | 0.00 |
July | 22667.20 | 04-JUL-15:51 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 163.05 | 0.00 |
August | 22238.01 | 27-AUG-16:51 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 102.99 | 0.00 |
September | 20474.18 | 10-SEP-14:52 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 438.41 | 0.00 |
October | 21057.29 | 08-OCT-14:42 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 99.76 | 0.00 |
November | 21598.76 | 19-NOV-15:11 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 86.68 | 0.00 |
December | 21270.78 | 25-DEC-16:52 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20474.18 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 0.00 | |
Maximum of Months | 23051.57 | 587.05 | 200.48 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.41 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18540.30 | 29-JAN-17:32 | 607.30 | 409.31 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.25 | 0.00 |
February | 19049.79 | 05-FEB-14:32 | 506.08 | 172.83 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 355.70 | 0.00 |
March | 20281.94 | 26-MAR-15:01 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 691.58 | 0.00 |
April | 19977.92 | 23-APR-15:31 | 910.95 | 311.09 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 452.45 | 0.00 |
May | 21027.21 | 07-MAY-14:11 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 673.94 | 0.00 |
June | 19821.13 | 18-JUN-15:02 | 607.30 | 207.39 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 705.21 | 0.00 |
July | 20730.13 | 04-JUL-15:51 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 375.06 | 0.00 |
August | 20044.02 | 27-AUG-16:51 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 239.32 | 0.00 |
September | 19961.46 | 04-SEP-16:11 | 809.73 | 276.53 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 | 0.00 |
October | 19131.04 | 29-OCT-14:22 | 506.08 | 172.83 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 464.40 | 0.00 |
November | 19287.04 | 19-NOV-14:31 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 239.66 | 0.00 |
December | 19192.35 | 31-DEC-14:31 | 708.51 | 241.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 185.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18540.30 | 506.08 | 172.83 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 185.46 | 0.00 | |
Maximum of Months | 21027.21 | 910.95 | 409.31 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 705.21 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17906.65 | 16-JAN-09:53 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 |
February | 17930.56 | 05-FEB-14:32 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 0.00 |
March | 19583.74 | 26-MAR-09:42 | 391.37 | 133.65 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 219.05 | 0.00 |
April | 18970.45 | 23-APR-15:31 | 587.05 | 200.48 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 292.77 | 0.00 |
May | 19439.51 | 07-MAY-14:11 | 456.59 | 155.93 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 470.54 | 0.00 |
June | 18036.16 | 11-JUN-09:42 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 433.87 | 0.00 |
July | 18523.94 | 04-JUL-15:51 | 521.82 | 178.20 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 312.87 | 0.00 |
August | 18881.91 | 27-AUG-08:52 | 326.14 | 111.38 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 85.81 | 0.00 |
September | 18880.17 | 04-SEP-16:11 | 521.82 | 178.20 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 247.90 | 0.00 |
October | 18086.69 | 08-OCT-08:13 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 | 0.00 |
November | 18050.43 | 19-NOV-14:31 | 456.59 | 155.93 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 161.87 | 0.00 |
December | 18334.69 | 31-DEC-14:31 | 456.59 | 155.93 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 117.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17906.65 | 260.91 | 89.10 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 | |
Maximum of Months | 19583.74 | 587.05 | 200.48 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 470.54 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19873.82 | 29-JAN-11:32 | 506.09 | 172.83 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 68.15 | 0.00 |
February | 19652.75 | 05-FEB-14:32 | 506.09 | 172.83 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 283.23 | 0.00 |
March | 20271.81 | 26-MAR-15:01 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 629.80 | 0.00 |
April | 19209.70 | 23-APR-15:31 | 910.97 | 311.10 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 458.71 | 0.00 |
May | 19746.38 | 07-MAY-14:11 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 729.54 | 0.00 |
June | 18463.85 | 18-JUN-15:02 | 607.31 | 207.40 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 774.73 | 0.00 |
July | 19191.01 | 04-JUL-15:51 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 456.00 | 0.00 |
August | 19045.37 | 27-AUG-16:51 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 254.47 | 0.00 |
September | 19419.14 | 04-SEP-16:11 | 809.75 | 276.53 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 371.85 | 0.00 |
October | 19826.53 | 29-OCT-11:42 | 506.09 | 172.83 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 443.73 | 0.00 |
November | 20696.35 | 19-NOV-14:31 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 149.55 | 0.00 |
December | 21121.62 | 31-DEC-13:51 | 708.53 | 241.97 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 105.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18463.85 | 506.09 | 172.83 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 68.15 | 0.00 | |
Maximum of Months | 21121.62 | 910.97 | 311.10 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 774.73 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22678.72 | 29-JAN-17:32 | 391.37 | 196.99 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 82.84 | 0.00 |
February | 22109.79 | 26-FEB-15:42 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 417.14 | 0.00 |
March | 24754.57 | 26-MAR-15:01 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 348.65 | 0.00 |
April | 25025.15 | 23-APR-15:31 | 587.05 | 200.48 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.27 | 0.00 |
May | 23865.09 | 07-MAY-14:11 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 426.66 | 0.00 |
June | 22194.45 | 18-JUN-15:42 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 368.91 | 0.00 |
July | 24460.66 | 04-JUL-15:51 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 176.35 | 0.00 |
August | 24088.36 | 27-AUG-16:51 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 113.31 | 0.00 |
September | 24547.28 | 04-SEP-16:11 | 521.82 | 178.20 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 172.01 | 0.00 |
October | 22644.11 | 15-OCT-15:52 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 | 0.00 |
November | 23318.16 | 19-NOV-15:11 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 95.09 | 0.00 |
December | 23029.86 | 24-DEC-16:31 | 456.59 | 155.93 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22109.79 | 391.37 | 133.65 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 0.00 | |
Maximum of Months | 25025.15 | 587.05 | 200.48 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.66 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15839.83 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16386.47 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15122.72 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
April | 16132.72 | 17-APR-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
May | 17240.93 | 08-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
June | 16165.75 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 0.00 |
July | 15094.54 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 |
August | 16080.99 | 14-AUG-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 0.00 |
September | 16431.78 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 0.00 |
October | 14944.51 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 |
November | 14910.92 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
December | 15225.94 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14910.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17240.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 25.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14166.95 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12581.80 | 06-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10340.26 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
April | 9510.67 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 0.00 |
May | 12569.58 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
June | 12562.85 | 19-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 0.00 |
July | 10266.28 | 31-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 |
August | 11327.75 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
September | 10728.08 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 0.00 |
October | 13770.79 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 |
November | 12141.05 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
December | 11200.72 | 18-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9510.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14166.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 25.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18234.28 | 31-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.90 | 0.00 |
February | 18709.99 | 21-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.40 | 0.00 |
March | 20144.85 | 29-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.39 | 0.00 |
April | 20966.43 | 11-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.18 | 0.00 |
May | 20885.86 | 05-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.83 | 0.00 |
June | 19728.86 | 16-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.98 | 0.00 |
July | 18322.89 | 14-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.97 | 0.00 |
August | 19705.92 | 14-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.12 | 0.00 |
September | 19839.27 | 06-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.10 | 0.00 |
October | 17392.46 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.39 | 0.00 |
November | 16046.60 | 22-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.34 | 0.00 |
December | 21555.34 | 26-DEC-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16046.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.34 | 0.00 | |
Maximum of Months | 21555.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.98 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2331.28 | 16-JAN-17:44 | 58.46 | 67.66 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4133.87 | 20-FEB-17:30 | 23.38 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7284.05 | 31-MAR-24:00 | 0.00 | 27.06 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7791.76 | 09-APR-17:33 | 0.00 | 54.13 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3517.54 | 31-MAY-23:55 | 0.00 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5347.11 | 30-JUN-24:00 | 0.00 | 27.06 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7280.91 | 31-JUL-24:00 | 0.00 | 13.53 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7750.46 | 28-AUG-01:32 | 0.00 | 54.13 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3492.31 | 30-SEP-24:00 | 0.00 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5348.18 | 31-OCT-24:00 | 0.00 | 27.06 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5930.48 | 19-NOV-17:02 | 70.15 | 81.19 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7783.96 | 25-DEC-19:52 | 0.00 | 67.66 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2331.28 | 0.00 | 13.53 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7791.76 | 70.15 | 81.19 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2164.57 | 16-JAN-17:33 | 70.15 | 81.19 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3842.62 | 20-FEB-17:30 | 23.38 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6997.73 | 31-MAR-23:55 | 0.00 | 27.06 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7262.18 | 09-APR-15:53 | 35.07 | 40.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3441.49 | 31-MAY-23:55 | 0.00 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5110.37 | 30-JUN-24:00 | 0.00 | 27.06 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7007.99 | 31-JUL-24:00 | 0.00 | 13.53 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7275.37 | 13-AUG-17:40 | 0.00 | 94.72 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3377.35 | 30-SEP-23:50 | 0.00 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5129.97 | 31-OCT-24:00 | 0.00 | 27.06 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5615.12 | 19-NOV-17:00 | 11.69 | 13.53 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7390.94 | 24-DEC-17:30 | 58.46 | 67.66 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2164.57 | 0.00 | 13.53 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7390.94 | 70.15 | 94.72 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2394.48 | 16-JAN-17:33 | 70.15 | 81.19 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4123.57 | 20-FEB-17:30 | 23.38 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7008.50 | 31-MAR-23:55 | 0.00 | 27.06 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7443.16 | 23-APR-17:50 | 0.00 | 81.19 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3439.98 | 31-MAY-23:55 | 0.00 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5058.42 | 30-JUN-24:00 | 0.00 | 27.06 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6999.53 | 31-JUL-24:00 | 0.00 | 13.53 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7456.99 | 13-AUG-17:30 | 0.00 | 81.19 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3407.16 | 30-SEP-23:50 | 0.00 | 27.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5113.97 | 31-OCT-24:00 | 0.00 | 27.06 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5869.98 | 19-NOV-17:00 | 11.69 | 13.53 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7557.03 | 24-DEC-17:30 | 58.46 | 67.66 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2394.48 | 0.00 | 13.53 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7557.03 | 70.15 | 81.19 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93189.77 | 17-JAN-17:00 | 4808.68 | 3269.85 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184718.70 | 21-FEB-17:00 | 4808.68 | 3269.85 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358272.74 | 31-MAR-23:20 | 0.00 | 363.31 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367781.35 | 21-APR-23:57 | 0.00 | 544.96 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177168.47 | 31-MAY-23:55 | 0.00 | 363.31 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268511.54 | 30-JUN-24:00 | 0.00 | 363.31 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359971.17 | 31-JUL-24:00 | 0.00 | 181.65 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369649.97 | 23-AUG-21:02 | 1518.53 | 2179.83 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176753.23 | 30-SEP-24:00 | 0.00 | 363.31 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268406.78 | 31-OCT-24:00 | 0.00 | 363.31 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276275.89 | 20-NOV-17:00 | 4808.68 | 3269.85 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369558.87 | 26-DEC-22:13 | 1518.53 | 2179.83 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93189.77 | 0.00 | 181.65 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369649.97 | 4808.68 | 3269.85 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.190353E+13 | 1257857.35 | 02-JAN-16:19 | 0.497096E+11 | 61877.34 | 10-JAN-12:20 |
February | 0.212404E+13 | 1401994.31 | 06-FEB-08:00 | 0.448894E+11 | 61593.52 | 09-FEB-12:20 |
March | 0.284918E+13 | 1560314.12 | 08-MAR-16:49 | 0.510403E+11 | 61070.17 | 02-MAR-12:20 |
April | 0.315452E+13 | 1751565.01 | 28-APR-15:20 | 0.469390E+11 | 59601.96 | 10-APR-11:20 |
May | 0.209806E+13 | 1291919.35 | 30-MAY-07:10 | 0.487984E+11 | 58668.16 | 02-MAY-11:20 |
June | 0.245237E+13 | 1427827.95 | 12-JUN-07:19 | 0.474596E+11 | 57370.26 | 07-JUN-11:00 |
July | 0.278051E+13 | 1549484.23 | 20-JUL-15:20 | 0.466481E+11 | 56981.09 | 28-JUL-11:20 |
August | 0.327749E+13 | 1756202.51 | 28-AUG-15:09 | 0.493216E+11 | 57675.81 | 31-AUG-11:39 |
September | 0.194866E+13 | 1288330.22 | 12-SEP-15:20 | 0.464563E+11 | 58774.04 | 26-SEP-11:50 |
October | 0.238180E+13 | 1392506.42 | 20-OCT-15:50 | 0.485541E+11 | 60187.40 | 30-OCT-11:30 |
November | 0.268433E+13 | 1575101.52 | 13-NOV-08:30 | 0.479533E+11 | 61274.56 | 30-NOV-12:30 |
December | 0.308996E+13 | 1689731.25 | 11-DEC-16:40 | 0.489087E+11 | 61821.09 | 29-DEC-12:50 |
Annual Sum or Average | 0.307444E+14 | 0.576678E+12 | ||||
Minimum of Months | 0.190353E+13 | 1257857.35 | 0.448894E+11 | 56981.09 | ||
Maximum of Months | 0.327749E+13 | 1756202.51 | 0.510403E+11 | 61877.34 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.439859E+11 | 70508.32 | 28-JAN-12:30 | 0.00 | 0.00 |
February | 0.451334E+11 | 78961.40 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.566632E+11 | 81932.75 | 19-MAR-11:30 | 0.00 | 0.00 |
April | 0.554334E+11 | 76453.78 | 13-APR-11:30 | 0.00 | 0.00 |
May | 0.491669E+11 | 76527.87 | 05-MAY-10:00 | 0.00 | 0.00 |
June | 0.510728E+11 | 69276.34 | 17-JUN-12:20 | 0.00 | 0.00 |
July | 0.458488E+11 | 70680.21 | 13-JUL-11:00 | 0.00 | 0.00 |
August | 0.499064E+11 | 74249.23 | 27-AUG-11:30 | 0.00 | 0.00 |
September | 0.446267E+11 | 70343.06 | 14-SEP-11:30 | 0.00 | 0.00 |
October | 0.426795E+11 | 68550.46 | 04-OCT-12:30 | 0.00 | 0.00 |
November | 0.395054E+11 | 64065.86 | 02-NOV-11:39 | 0.00 | 0.00 |
December | 0.410678E+11 | 66009.24 | 27-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.565090E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.395054E+11 | 64065.86 | 0.00 | 0.00 | |
Maximum of Months | 0.566632E+11 | 81932.75 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.163532E+12 | 0.240254E+11 | 0.766053E+12 | 0.102202E+12 | 0.215621E+12 | 0.704440E+11 | 0.00 | 0.377678E+12 | 0.175749E+12 | 0.00 | 0.822756E+10 | 0.00 | 0.00 |
February | 0.148150E+12 | 0.210860E+11 | 0.978954E+12 | 0.923185E+11 | 0.201035E+12 | 0.706848E+11 | 0.00 | 0.437918E+12 | 0.165771E+12 | 0.00 | 0.812240E+10 | 0.00 | 0.00 |
March | 0.175329E+12 | 0.220295E+11 | 0.141687E+13 | 0.102372E+12 | 0.245428E+12 | 0.808206E+11 | 0.00 | 0.604418E+12 | 0.192245E+12 | 0.00 | 0.966233E+10 | 0.00 | 0.00 |
April | 0.156208E+12 | 0.203658E+11 | 0.165903E+13 | 0.988902E+11 | 0.244834E+12 | 0.800111E+11 | 0.00 | 0.689053E+12 | 0.196596E+12 | 0.00 | 0.953683E+10 | 0.00 | 0.00 |
May | 0.168607E+12 | 0.203508E+11 | 0.774844E+12 | 0.102287E+12 | 0.246795E+12 | 0.811689E+11 | 0.00 | 0.490285E+12 | 0.204358E+12 | 0.00 | 0.936238E+10 | 0.00 | 0.00 |
June | 0.167573E+12 | 0.193706E+11 | 0.106252E+13 | 0.990481E+11 | 0.239032E+12 | 0.835258E+11 | 0.00 | 0.572403E+12 | 0.199559E+12 | 0.00 | 0.933948E+10 | 0.00 | 0.00 |
July | 0.157031E+12 | 0.203616E+11 | 0.139340E+13 | 0.102128E+12 | 0.233607E+12 | 0.785118E+11 | 0.00 | 0.590962E+12 | 0.195242E+12 | 0.00 | 0.926583E+10 | 0.00 | 0.00 |
August | 0.174888E+12 | 0.207671E+11 | 0.173200E+13 | 0.102371E+12 | 0.247439E+12 | 0.840752E+11 | 0.00 | 0.703389E+12 | 0.203244E+12 | 0.00 | 0.931438E+10 | 0.00 | 0.00 |
September | 0.156615E+12 | 0.210373E+11 | 0.740713E+12 | 0.988894E+11 | 0.226194E+12 | 0.735246E+11 | 0.00 | 0.431565E+12 | 0.191482E+12 | 0.00 | 0.864181E+10 | 0.00 | 0.00 |
October | 0.162830E+12 | 0.228130E+11 | 0.108340E+13 | 0.102203E+12 | 0.223716E+12 | 0.760142E+11 | 0.00 | 0.506067E+12 | 0.195969E+12 | 0.00 | 0.878855E+10 | 0.00 | 0.00 |
November | 0.161823E+12 | 0.232726E+11 | 0.135889E+13 | 0.989539E+11 | 0.212722E+12 | 0.764595E+11 | 0.00 | 0.557194E+12 | 0.186498E+12 | 0.00 | 0.851308E+10 | 0.00 | 0.00 |
December | 0.158557E+12 | 0.243184E+11 | 0.170972E+13 | 0.102128E+12 | 0.211828E+12 | 0.770188E+11 | 0.00 | 0.614322E+12 | 0.183396E+12 | 0.00 | 0.866722E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.195114E+13 | 0.259798E+12 | 0.146764E+14 | 0.120379E+13 | 0.274825E+13 | 0.932259E+12 | 0.00 | 0.657525E+13 | 0.229011E+13 | 0.00 | 0.107442E+12 | 0.00 | 0.00 |
Minimum of Months | 0.148150E+12 | 0.193706E+11 | 0.740713E+12 | 0.923185E+11 | 0.201035E+12 | 0.704440E+11 | 0.00 | 0.377678E+12 | 0.165771E+12 | 0.00 | 0.812240E+10 | 0.00 | 0.00 |
Maximum of Months | 0.175329E+12 | 0.243184E+11 | 0.173200E+13 | 0.102372E+12 | 0.247439E+12 | 0.840752E+11 | 0.00 | 0.703389E+12 | 0.204358E+12 | 0.00 | 0.966233E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.497096E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.448894E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.510403E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.469390E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.487984E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.474596E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.466481E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.493216E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.464563E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.485541E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.479533E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.489087E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.576678E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.448894E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.510403E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 178307.81 | 02-JAN-16:00 | 31088.59 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 73699.56 | 02-JAN-08:20 | 185146.82 | 02-JAN-09:00 | 61748.35 | 18-JAN-14:20 | 0.00 | 01-JAN-00:10 |
February | 170738.26 | 07-FEB-16:00 | 31088.59 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 73699.54 | 08-FEB-08:20 | 175737.47 | 21-FEB-08:09 | 61640.97 | 28-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 171454.43 | 01-MAR-16:00 | 31088.59 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 73700.27 | 28-MAR-07:19 | 192805.42 | 10-MAR-16:00 | 51323.56 | 20-MAR-12:09 | 0.00 | 01-MAR-00:10 |
April | 169075.76 | 21-APR-07:10 | 31088.59 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 73700.30 | 21-APR-07:19 | 216794.36 | 24-APR-15:20 | 51284.06 | 14-APR-13:50 | 0.00 | 01-APR-00:10 |
May | 169570.51 | 17-MAY-07:10 | 31088.59 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 73700.56 | 17-MAY-07:19 | 192829.22 | 03-MAY-15:39 | 51802.18 | 01-MAY-14:09 | 0.00 | 01-MAY-00:10 |
June | 168793.70 | 20-JUN-07:10 | 31088.59 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 73700.15 | 20-JUN-07:19 | 180892.72 | 01-JUN-15:20 | 52637.25 | 13-JUN-15:30 | 0.00 | 01-JUN-00:10 |
July | 169297.11 | 11-JUL-07:10 | 31088.59 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 73700.42 | 11-JUL-07:19 | 191300.13 | 31-JUL-15:09 | 51290.11 | 07-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 169343.22 | 21-AUG-07:10 | 31088.59 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 73700.44 | 21-AUG-07:19 | 211827.74 | 28-AUG-15:00 | 51212.29 | 18-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 169094.86 | 21-SEP-07:10 | 31088.59 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 73700.31 | 21-SEP-07:19 | 207435.82 | 12-SEP-15:20 | 51374.76 | 18-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 169763.51 | 23-OCT-07:10 | 31088.59 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 73700.66 | 23-OCT-07:19 | 179663.32 | 10-OCT-15:00 | 52143.76 | 20-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 182481.83 | 09-NOV-16:00 | 31088.59 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 73700.00 | 03-NOV-07:19 | 181663.41 | 13-NOV-08:09 | 57512.99 | 06-NOV-13:09 | 0.00 | 01-NOV-00:10 |
December | 184260.23 | 18-DEC-16:00 | 31088.59 | 01-DEC-17:30 | 778371.69 | 01-DEC-08:09 | 73699.40 | 18-DEC-08:20 | 177408.72 | 26-DEC-13:09 | 62089.00 | 26-DEC-13:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 168793.70 | 31088.59 | 423497.50 | 73699.40 | 175737.47 | 51212.29 | 0.00 | |||||||
Maximum of Months | 184260.23 | 31088.59 | 778371.69 | 73700.66 | 216794.36 | 62089.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 325164.09 | 02-JAN-06:10 | 83172.35 | 01-JAN-20:30 | 0.00 | 01-JAN-00:10 | 4520.72 | 01-JAN-06:49 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 348582.50 | 28-FEB-13:09 | 83172.35 | 01-FEB-08:39 | 0.00 | 01-FEB-00:10 | 4520.72 | 01-FEB-04:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 392526.35 | 09-MAR-13:09 | 83172.35 | 01-MAR-04:19 | 0.00 | 01-MAR-00:10 | 4520.72 | 01-MAR-04:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 420054.58 | 28-APR-12:09 | 83172.35 | 01-APR-00:49 | 0.00 | 01-APR-00:10 | 4520.72 | 01-APR-00:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 334363.80 | 01-MAY-14:09 | 83172.35 | 01-MAY-00:20 | 0.00 | 01-MAY-00:10 | 4520.72 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 373438.14 | 13-JUN-15:30 | 83172.35 | 01-JUN-03:39 | 0.00 | 01-JUN-00:10 | 4520.72 | 01-JUN-03:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 389004.75 | 05-JUL-12:09 | 83172.35 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 | 4520.72 | 01-JUL-04:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 423883.54 | 23-AUG-12:09 | 83172.35 | 01-AUG-03:20 | 0.00 | 01-AUG-00:10 | 4520.72 | 01-AUG-03:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 335063.68 | 11-SEP-12:09 | 83172.35 | 01-SEP-03:20 | 0.00 | 01-SEP-00:10 | 4520.72 | 01-SEP-03:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 361974.00 | 06-OCT-12:09 | 83172.35 | 01-OCT-06:19 | 0.00 | 01-OCT-00:10 | 4520.72 | 01-OCT-06:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 376953.96 | 17-NOV-13:09 | 83172.35 | 01-NOV-03:30 | 0.00 | 01-NOV-00:10 | 4520.72 | 01-NOV-03:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 421929.39 | 11-DEC-13:09 | 83172.35 | 01-DEC-07:40 | 0.00 | 01-DEC-00:10 | 4520.72 | 01-DEC-05:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 325164.09 | 83172.35 | 0.00 | 4520.72 | 0.00 | 0.00 | |||||
Maximum of Months | 423883.54 | 83172.35 | 0.00 | 4520.72 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1257857.35 | 02-JAN-16:19 | 168877.93 | 423497.50 | 0.00 | 52601.45 | 183742.82 | 50020.37 | 0.00 | 291424.22 | 83172.35 |
February | 1401994.31 | 06-FEB-08:00 | 167324.41 | 541788.89 | 0.00 | 73699.38 | 170600.54 | 49995.75 | 0.00 | 310892.27 | 83172.35 |
March | 1560314.12 | 08-MAR-16:49 | 167687.16 | 660080.29 | 0.00 | 52600.82 | 191353.76 | 49965.62 | 0.00 | 350933.41 | 83172.35 |
April | 1751565.01 | 28-APR-15:20 | 167324.41 | 778371.69 | 0.00 | 52600.80 | 213216.44 | 50574.88 | 0.00 | 401783.73 | 83172.35 |
May | 1291919.35 | 30-MAY-07:10 | 167324.41 | 423497.50 | 0.00 | 73641.20 | 179316.86 | 50869.39 | 0.00 | 309576.92 | 83172.35 |
June | 1427827.95 | 12-JUN-07:19 | 167324.41 | 541788.89 | 0.00 | 73699.38 | 161292.16 | 50279.34 | 0.00 | 345750.70 | 83172.35 |
July | 1549484.23 | 20-JUL-15:20 | 167324.41 | 660080.29 | 0.00 | 52600.80 | 171087.80 | 50345.20 | 0.00 | 360352.67 | 83172.35 |
August | 1756202.51 | 28-AUG-15:09 | 167324.41 | 778371.69 | 0.00 | 52600.80 | 206865.36 | 50914.28 | 0.00 | 412432.90 | 83172.35 |
September | 1288330.22 | 12-SEP-15:20 | 167324.41 | 423497.50 | 0.00 | 52600.80 | 207435.82 | 50374.20 | 0.00 | 299404.43 | 83172.35 |
October | 1392506.42 | 20-OCT-15:50 | 167350.23 | 541788.89 | 0.00 | 52600.80 | 166577.42 | 49981.14 | 0.00 | 326514.87 | 83172.35 |
November | 1575101.52 | 13-NOV-08:30 | 167324.41 | 660080.29 | 0.00 | 73699.38 | 167317.09 | 50468.77 | 0.00 | 368518.51 | 83172.35 |
December | 1689731.25 | 11-DEC-16:40 | 174986.77 | 778371.69 | 0.00 | 52603.93 | 163507.92 | 49973.14 | 0.00 | 382594.73 | 83172.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1257857.35 | 167324.41 | 423497.50 | 0.00 | 52600.80 | 161292.16 | 49965.62 | 0.00 | 291424.22 | 83172.35 | |
Maximum of Months | 1756202.51 | 174986.77 | 778371.69 | 0.00 | 73699.38 | 213216.44 | 50914.28 | 0.00 | 412432.90 | 83172.35 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 61877.34 | 10-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 61593.52 | 09-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 61070.17 | 02-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 59601.96 | 10-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 58668.16 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 57370.26 | 07-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 56981.09 | 28-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 57675.81 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 58774.04 | 26-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 60187.40 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 61274.56 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 61821.09 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56981.09 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 61877.34 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.86 | 0.50 | 26.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.91 | 0.00 | 26.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.48 | 0.17 | 26.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.11 | 0.33 | 26.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.55 | 0.17 | 26.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.34 | 0.83 | 26.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.11 | 0.50 | 26.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.31 | 0.50 | 26.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.65 | 0.50 | 26.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 26.75 | 1.00 | 26.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.76 | 2.33 | 26.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.90 | 0.50 | 26.82 |
Annual Sum or Average | 0.00 | 0.00 | 126.50 | 26.59 | 7.33 | 26.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.11 | 0.00 | 26.02 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 26.91 | 2.33 | 26.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.72 | 0.00 | 25.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.58 | 0.00 | 25.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.55 | 0.17 | 25.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.64 | 0.00 | 25.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.57 | 0.00 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.55 | 0.17 | 25.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.84 | 0.00 | 25.84 |
Annual Sum or Average | 0.00 | 0.00 | 8.17 | 25.62 | 0.33 | 25.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.55 | 0.00 | 25.45 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.84 | 0.17 | 25.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.10 | 4.50 | 27.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.08 | 5.17 | 27.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 26.93 | 8.50 | 27.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.23 | 9.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.14 | 8.83 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.17 | 10.17 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.89 | 5.50 | 27.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.99 | 4.17 | 27.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.92 | 2.67 | 27.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.75 | 2.00 | 26.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.80 | 2.17 | 27.01 |
Annual Sum or Average | 0.00 | 0.00 | 100.67 | 27.05 | 62.67 | 27.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.23 | 10.17 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.31 | 10.00 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.41 | 11.67 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.53 | 9.83 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.51 | 12.33 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.41 | 11.00 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.37 | 9.50 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.20 | 10.17 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.38 | 7.00 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.46 | 10.33 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.40 | 9.00 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.29 | 8.33 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.34 | 9.67 | 27.40 |
Annual Sum or Average | 0.00 | 0.00 | 146.17 | 27.39 | 118.83 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.20 | 7.00 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.53 | 12.33 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 26.29 | 25.67 | 26.25 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 26.94 | 15.00 | 26.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.24 | 7.67 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.94 | 7.67 | 27.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.96 | 4.67 | 27.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.90 | 4.67 | 27.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.97 | 6.00 | 27.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.83 | 4.50 | 27.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.09 | 5.83 | 27.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.38 | 9.67 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.39 | 11.00 | 27.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 25.87 | 46.33 | 25.81 |
Annual Sum or Average | 0.00 | 0.00 | 190.17 | 26.63 | 148.67 | 26.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25.87 | 4.50 | 25.81 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 27.39 | 46.33 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.25 | 11.50 | 27.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.32 | 13.50 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 | 27.45 | 17.17 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 79.33 | 27.77 | 22.33 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 27.25 | 13.00 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 27.35 | 15.00 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 27.42 | 19.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 27.55 | 18.00 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.13 | 10.83 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 27.20 | 15.33 | 27.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 27.35 | 18.00 | 27.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 | 27.58 | 22.17 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 590.50 | 27.44 | 196.50 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.13 | 10.83 | 27.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 79.33 | 27.77 | 22.33 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.37 | 4.17 | 27.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.43 | 3.33 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.26 | 5.17 | 27.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.22 | 10.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.16 | 8.67 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.33 | 9.33 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.27 | 4.17 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.25 | 4.17 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.33 | 3.33 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Annual Sum or Average | 0.00 | 0.00 | 74.50 | 27.25 | 52.67 | 27.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.43 | 10.00 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.45 | 11.17 | 27.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.59 | 12.83 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.76 | 10.00 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.57 | 12.17 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.47 | 12.17 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.29 | 10.17 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.41 | 12.83 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.61 | 7.50 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.46 | 10.50 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.57 | 10.83 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.50 | 10.67 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.57 | 11.33 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 162.33 | 27.51 | 132.17 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.29 | 7.50 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.76 | 12.83 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 52.00 | 25.74 | 48.00 | 25.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 26.21 | 23.67 | 26.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.55 | 7.17 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.26 | 4.83 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.07 | 5.50 | 27.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.18 | 4.50 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.33 | 3.83 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.44 | 2.67 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.24 | 5.50 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.53 | 9.67 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.58 | 10.83 | 27.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 25.73 | 53.67 | 25.68 |
Annual Sum or Average | 0.00 | 0.00 | 203.33 | 26.34 | 179.83 | 26.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.73 | 2.67 | 25.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 27.58 | 53.67 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.61 | 7.67 | 27.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.40 | 9.17 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.21 | 7.67 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.22 | 9.83 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.30 | 9.83 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.16 | 8.17 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.21 | 10.83 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.11 | 6.33 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.18 | 7.83 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.25 | 8.83 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.32 | 8.67 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.70 | 7.67 | 27.83 |
Annual Sum or Average | 0.00 | 0.00 | 230.67 | 27.27 | 102.50 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.11 | 6.33 | 27.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.70 | 10.83 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.24 | 2.83 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.50 | 7.67 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.46 | 6.17 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.33 | 7.50 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.34 | 10.33 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.32 | 8.83 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.45 | 10.83 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.43 | 5.17 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.39 | 6.17 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.42 | 7.17 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.40 | 5.83 | 27.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.36 | 4.50 | 27.36 |
Annual Sum or Average | 0.00 | 0.00 | 119.67 | 27.38 | 83.00 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.24 | 2.83 | 27.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.50 | 10.83 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.53 | 12.17 | 27.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.66 | 13.00 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.80 | 10.33 | 27.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.63 | 12.67 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.54 | 12.33 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.41 | 10.17 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.50 | 13.33 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.68 | 7.83 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.57 | 12.17 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.61 | 12.00 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.57 | 11.67 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.64 | 12.67 | 27.64 |
Annual Sum or Average | 0.00 | 0.00 | 190.00 | 27.59 | 140.33 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.41 | 7.83 | 27.55 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.80 | 13.33 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 26.57 | 23.33 | 26.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.41 | 12.67 | 27.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.64 | 7.50 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.40 | 7.17 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.23 | 7.67 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.32 | 7.00 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.36 | 8.50 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.30 | 4.17 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.46 | 6.83 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.61 | 10.33 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.66 | 11.33 | 27.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 26.20 | 33.33 | 26.13 |
Annual Sum or Average | 0.00 | 0.00 | 183.00 | 27.05 | 139.83 | 27.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.20 | 4.17 | 26.13 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 27.66 | 33.33 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.76 | 8.17 | 27.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.62 | 9.33 | 27.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.36 | 8.67 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 27.34 | 11.17 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 27.43 | 10.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.27 | 8.17 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.33 | 12.17 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.27 | 6.83 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.33 | 9.00 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.40 | 10.83 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.46 | 9.50 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.78 | 8.67 | 27.91 |
Annual Sum or Average | 0.00 | 0.00 | 252.50 | 27.41 | 113.00 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.27 | 6.83 | 27.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 27.78 | 12.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 173.33 | 27.92 | 156.67 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 126.17 | 27.91 | 118.50 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.67 | 15.83 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 316.00 | 27.90 | 291.00 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 173.33 | 27.92 | 156.67 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 134.17 | 27.84 | 125.83 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 102.00 | 27.84 | 98.50 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.60 | 5.83 | 27.60 |
Annual Sum or Average | 0.00 | 0.00 | 242.00 | 27.83 | 230.17 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 134.17 | 27.84 | 125.83 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 | 27.86 | 99.50 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 27.87 | 67.33 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.66 | 9.00 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 191.33 | 27.85 | 175.83 | 27.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 | 27.87 | 99.50 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.57 | 0.00 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 706.33 | 29.14 | 482.50 | 29.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 656.67 | 28.89 | 485.17 | 28.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 419.83 | 28.57 | 369.17 | 28.60 |
Annual Sum or Average | 0.00 | 0.00 | 1783.00 | 28.91 | 1336.83 | 28.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 706.33 | 29.14 | 485.17 | 29.26 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 253.83 | 25.20 | 502.00 | 24.81 | 253.83 | 24.91 |
February | 231.67 | 25.14 | 454.00 | 24.77 | 231.67 | 24.86 |
March | 260.50 | 24.94 | 514.00 | 24.63 | 260.50 | 24.71 |
April | 233.50 | 25.14 | 485.00 | 24.76 | 233.50 | 24.85 |
May | 271.00 | 25.02 | 508.00 | 24.71 | 271.00 | 24.79 |
June | 252.50 | 24.97 | 496.00 | 24.65 | 252.50 | 24.73 |
July | 247.50 | 25.27 | 497.00 | 24.85 | 247.50 | 24.95 |
August | 223.83 | 25.08 | 514.00 | 24.67 | 223.83 | 24.76 |
September | 270.00 | 25.01 | 485.00 | 24.72 | 270.00 | 24.80 |
October | 273.17 | 25.13 | 502.00 | 24.79 | 273.17 | 24.88 |
November | 238.17 | 25.27 | 489.00 | 24.84 | 238.17 | 24.94 |
December | 229.83 | 25.31 | 497.00 | 24.84 | 229.83 | 24.96 |
Annual Sum or Average | 2985.50 | 25.12 | 5943.00 | 24.75 | 2985.50 | 24.84 |
Minimum of Months | 223.83 | 24.94 | 454.00 | 24.63 | 223.83 | 24.71 |
Maximum of Months | 273.17 | 25.31 | 514.00 | 24.85 | 273.17 | 24.96 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 24.34 | 0.00 | 24.34 |
February | 0.00 | 0.00 | 454.00 | 24.25 | 0.00 | 24.25 |
March | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
April | 0.00 | 0.00 | 485.00 | 24.25 | 0.00 | 24.25 |
May | 0.00 | 0.00 | 508.00 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 496.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 514.00 | 24.21 | 0.00 | 24.21 |
September | 0.00 | 0.00 | 485.00 | 24.26 | 0.00 | 24.26 |
October | 0.00 | 0.00 | 502.00 | 24.27 | 0.00 | 24.27 |
November | 0.00 | 0.00 | 489.00 | 24.27 | 0.00 | 24.27 |
December | 0.00 | 0.00 | 497.00 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 0.00 | 5943.00 | 24.25 | 0.00 | 24.25 | |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.19 | 0.00 | 24.19 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.34 | 0.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 27.17 | 494.00 | 24.30 | 0.33 | 24.30 |
February | 0.00 | 0.00 | 454.00 | 24.24 | 0.00 | 24.24 |
March | 0.00 | 0.00 | 514.00 | 24.17 | 0.00 | 24.17 |
April | 0.00 | 0.00 | 485.00 | 24.14 | 0.00 | 24.14 |
May | 0.00 | 0.00 | 508.00 | 24.18 | 0.00 | 24.18 |
June | 0.00 | 0.00 | 496.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 514.00 | 24.21 | 0.00 | 24.21 |
September | 0.00 | 0.00 | 485.00 | 24.20 | 0.00 | 24.20 |
October | 0.00 | 0.00 | 498.67 | 24.25 | 0.00 | 24.25 |
November | 0.00 | 0.00 | 486.83 | 24.28 | 0.00 | 24.28 |
December | 0.00 | 0.00 | 491.83 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 0.33 | 27.17 | 5924.33 | 24.22 | 0.33 | 24.22 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.14 | 0.00 | 24.14 |
Maximum of Months | 0.33 | 27.17 | 514.00 | 24.30 | 0.33 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 27.11 | 502.00 | 24.34 | 0.83 | 24.34 |
February | 0.00 | 0.00 | 454.00 | 24.30 | 0.00 | 24.30 |
March | 0.00 | 0.00 | 514.00 | 24.23 | 0.00 | 24.23 |
April | 0.00 | 0.00 | 485.00 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 508.00 | 24.26 | 0.00 | 24.26 |
June | 0.00 | 0.00 | 496.00 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 497.00 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 514.00 | 24.25 | 0.00 | 24.25 |
September | 0.00 | 0.00 | 485.00 | 24.27 | 0.00 | 24.27 |
October | 0.00 | 0.00 | 502.00 | 24.32 | 0.00 | 24.32 |
November | 0.00 | 0.00 | 489.00 | 24.34 | 0.00 | 24.34 |
December | 0.00 | 0.00 | 497.00 | 24.32 | 0.00 | 24.32 |
Annual Sum or Average | 0.83 | 27.11 | 5943.00 | 24.28 | 0.83 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.22 | 0.00 | 24.22 |
Maximum of Months | 0.83 | 27.11 | 514.00 | 24.34 | 0.83 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.50 | 26.51 | 502.00 | 24.57 | 27.50 | 24.67 |
February | 32.83 | 26.73 | 454.00 | 24.59 | 32.83 | 24.73 |
March | 27.67 | 26.80 | 514.00 | 24.49 | 27.67 | 24.60 |
April | 42.00 | 26.81 | 485.00 | 24.67 | 42.00 | 24.83 |
May | 51.83 | 26.79 | 508.00 | 24.72 | 51.83 | 24.90 |
June | 41.00 | 26.90 | 496.00 | 24.65 | 41.00 | 24.81 |
July | 51.00 | 26.81 | 497.00 | 24.75 | 51.00 | 24.92 |
August | 31.00 | 26.74 | 514.00 | 24.51 | 31.00 | 24.63 |
September | 37.33 | 26.60 | 485.00 | 24.62 | 37.33 | 24.75 |
October | 33.00 | 26.67 | 502.00 | 24.60 | 33.00 | 24.72 |
November | 29.17 | 26.69 | 489.00 | 24.57 | 29.17 | 24.69 |
December | 28.50 | 26.70 | 497.00 | 24.54 | 28.50 | 24.66 |
Annual Sum or Average | 432.83 | 26.74 | 5943.00 | 24.61 | 432.83 | 24.74 |
Minimum of Months | 27.50 | 26.51 | 454.00 | 24.49 | 27.50 | 24.60 |
Maximum of Months | 51.83 | 26.90 | 514.00 | 24.75 | 51.83 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.00 | 26.73 | 502.00 | 24.79 | 63.00 | 24.98 |
February | 52.33 | 26.83 | 454.00 | 24.74 | 52.33 | 24.94 |
March | 40.83 | 26.93 | 514.00 | 24.59 | 40.83 | 24.75 |
April | 52.00 | 26.92 | 485.00 | 24.73 | 52.00 | 24.92 |
May | 53.83 | 26.87 | 508.00 | 24.74 | 53.83 | 24.92 |
June | 40.50 | 26.89 | 496.00 | 24.62 | 40.50 | 24.78 |
July | 52.00 | 26.77 | 497.00 | 24.71 | 52.00 | 24.89 |
August | 33.50 | 26.78 | 514.00 | 24.49 | 33.50 | 24.63 |
September | 54.67 | 26.80 | 485.00 | 24.75 | 54.67 | 24.94 |
October | 47.67 | 26.77 | 502.00 | 24.69 | 47.67 | 24.86 |
November | 46.50 | 26.77 | 489.00 | 24.67 | 46.50 | 24.84 |
December | 49.00 | 26.76 | 497.00 | 24.66 | 49.00 | 24.83 |
Annual Sum or Average | 585.83 | 26.82 | 5943.00 | 24.68 | 585.83 | 24.86 |
Minimum of Months | 33.50 | 26.73 | 454.00 | 24.49 | 33.50 | 24.63 |
Maximum of Months | 63.00 | 26.93 | 514.00 | 24.79 | 63.00 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.33 | 26.91 | 502.00 | 24.92 | 64.33 | 25.13 |
February | 46.50 | 26.95 | 454.00 | 24.80 | 46.50 | 24.98 |
March | 33.67 | 26.92 | 514.00 | 24.56 | 33.67 | 24.70 |
April | 38.17 | 26.81 | 485.00 | 24.64 | 38.17 | 24.78 |
May | 38.17 | 26.67 | 508.00 | 24.61 | 38.17 | 24.75 |
June | 31.67 | 26.74 | 496.00 | 24.54 | 31.67 | 24.66 |
July | 41.83 | 26.72 | 497.00 | 24.65 | 41.83 | 24.80 |
August | 27.83 | 26.64 | 514.00 | 24.46 | 27.83 | 24.57 |
September | 39.17 | 26.64 | 485.00 | 24.64 | 39.17 | 24.78 |
October | 47.50 | 26.84 | 502.00 | 24.73 | 47.50 | 24.90 |
November | 52.83 | 26.90 | 489.00 | 24.79 | 52.83 | 24.98 |
December | 58.50 | 26.98 | 497.00 | 24.89 | 58.50 | 25.09 |
Annual Sum or Average | 520.17 | 26.83 | 5943.00 | 24.69 | 520.17 | 24.85 |
Minimum of Months | 27.83 | 26.64 | 454.00 | 24.46 | 27.83 | 24.57 |
Maximum of Months | 64.33 | 26.98 | 514.00 | 24.92 | 64.33 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 78.00 | 26.92 | 502.00 | 24.96 | 78.00 | 25.19 |
February | 84.67 | 26.90 | 454.00 | 25.00 | 84.67 | 25.26 |
March | 94.83 | 26.91 | 514.00 | 24.93 | 94.83 | 25.20 |
April | 106.50 | 26.99 | 485.00 | 25.09 | 106.50 | 25.38 |
May | 83.83 | 26.89 | 508.00 | 24.93 | 83.83 | 25.17 |
June | 85.33 | 26.91 | 496.00 | 24.91 | 85.33 | 25.16 |
July | 110.17 | 26.89 | 497.00 | 25.09 | 110.17 | 25.37 |
August | 95.17 | 26.91 | 514.00 | 24.93 | 95.17 | 25.20 |
September | 78.67 | 26.88 | 485.00 | 24.93 | 78.67 | 25.17 |
October | 90.83 | 26.88 | 502.00 | 25.00 | 90.83 | 25.25 |
November | 99.00 | 26.90 | 489.00 | 25.06 | 99.00 | 25.32 |
December | 113.50 | 26.92 | 497.00 | 25.11 | 113.50 | 25.40 |
Annual Sum or Average | 1120.50 | 26.91 | 5943.00 | 25.00 | 1120.50 | 25.26 |
Minimum of Months | 78.00 | 26.88 | 454.00 | 24.91 | 78.00 | 25.16 |
Maximum of Months | 113.50 | 26.99 | 514.00 | 25.11 | 113.50 | 25.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.67 | 25.88 | 502.00 | 24.56 | 41.67 | 24.65 |
February | 57.17 | 26.32 | 454.00 | 24.68 | 57.17 | 24.85 |
March | 56.17 | 26.10 | 514.00 | 24.56 | 56.17 | 24.70 |
April | 70.67 | 26.27 | 485.00 | 24.70 | 70.67 | 24.88 |
May | 91.83 | 26.42 | 508.00 | 24.83 | 91.83 | 25.04 |
June | 71.83 | 26.61 | 496.00 | 24.77 | 71.83 | 24.98 |
July | 69.00 | 26.66 | 497.00 | 24.85 | 69.00 | 25.04 |
August | 74.33 | 26.06 | 514.00 | 24.63 | 74.33 | 24.79 |
September | 71.00 | 26.13 | 485.00 | 24.67 | 71.00 | 24.84 |
October | 79.67 | 26.15 | 502.00 | 24.72 | 79.67 | 24.90 |
November | 71.17 | 26.13 | 489.00 | 24.69 | 71.17 | 24.85 |
December | 45.67 | 25.94 | 496.00 | 24.57 | 45.67 | 24.67 |
Annual Sum or Average | 800.17 | 26.25 | 5942.00 | 24.69 | 800.17 | 24.85 |
Minimum of Months | 41.67 | 25.88 | 454.00 | 24.56 | 41.67 | 24.65 |
Maximum of Months | 91.83 | 26.66 | 514.00 | 24.85 | 91.83 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.67 | 26.63 | 427.00 | 24.98 | 76.67 | 25.20 |
February | 65.00 | 26.81 | 385.00 | 24.99 | 65.00 | 25.22 |
March | 58.00 | 26.72 | 433.00 | 24.83 | 58.00 | 25.03 |
April | 73.33 | 26.72 | 410.00 | 24.98 | 73.33 | 25.21 |
May | 91.33 | 26.52 | 430.00 | 24.99 | 91.33 | 25.22 |
June | 72.00 | 26.60 | 418.00 | 24.89 | 72.00 | 25.11 |
July | 72.67 | 26.73 | 422.00 | 25.01 | 72.67 | 25.23 |
August | 73.17 | 26.29 | 433.00 | 24.80 | 73.17 | 24.99 |
September | 73.83 | 26.63 | 410.00 | 24.95 | 73.83 | 25.18 |
October | 83.00 | 26.51 | 427.00 | 24.97 | 83.00 | 25.19 |
November | 75.00 | 26.62 | 417.00 | 24.97 | 75.00 | 25.19 |
December | 69.50 | 26.70 | 422.00 | 24.95 | 69.50 | 25.17 |
Annual Sum or Average | 883.50 | 26.62 | 5034.00 | 24.94 | 883.50 | 25.16 |
Minimum of Months | 58.00 | 26.29 | 385.00 | 24.80 | 58.00 | 24.99 |
Maximum of Months | 91.33 | 26.81 | 433.00 | 25.01 | 91.33 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.00 | 26.83 | 502.00 | 25.02 | 80.00 | 25.24 |
February | 64.17 | 26.80 | 454.00 | 24.92 | 64.17 | 25.13 |
March | 57.17 | 26.46 | 514.00 | 24.65 | 57.17 | 24.82 |
April | 70.67 | 26.21 | 485.00 | 24.68 | 70.67 | 24.86 |
May | 89.50 | 26.14 | 508.00 | 24.73 | 89.50 | 24.91 |
June | 72.17 | 26.17 | 496.00 | 24.65 | 72.17 | 24.82 |
July | 64.17 | 26.43 | 497.00 | 24.75 | 64.17 | 24.92 |
August | 75.33 | 25.88 | 514.00 | 24.58 | 75.33 | 24.73 |
September | 71.00 | 26.20 | 485.00 | 24.70 | 71.00 | 24.87 |
October | 81.33 | 26.49 | 502.00 | 24.84 | 81.33 | 25.04 |
November | 75.17 | 26.75 | 489.00 | 24.92 | 75.17 | 25.14 |
December | 78.00 | 26.83 | 497.00 | 25.02 | 78.00 | 25.23 |
Annual Sum or Average | 878.67 | 26.43 | 5943.00 | 24.79 | 878.67 | 24.98 |
Minimum of Months | 57.17 | 25.88 | 454.00 | 24.58 | 57.17 | 24.73 |
Maximum of Months | 89.50 | 26.83 | 514.00 | 25.02 | 89.50 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.33 | 26.59 | 502.00 | 24.84 | 70.33 | 25.03 |
February | 70.83 | 26.76 | 454.00 | 24.90 | 70.83 | 25.12 |
March | 71.83 | 26.82 | 514.00 | 24.81 | 71.83 | 25.03 |
April | 86.33 | 26.78 | 485.00 | 24.93 | 86.33 | 25.18 |
May | 93.67 | 26.63 | 508.00 | 24.90 | 93.67 | 25.13 |
June | 78.50 | 26.75 | 496.00 | 24.83 | 78.50 | 25.06 |
July | 84.17 | 26.81 | 497.00 | 24.96 | 84.17 | 25.19 |
August | 78.00 | 26.54 | 514.00 | 24.77 | 78.00 | 24.98 |
September | 80.83 | 26.58 | 485.00 | 24.85 | 80.83 | 25.06 |
October | 86.33 | 26.63 | 502.00 | 24.91 | 86.33 | 25.13 |
November | 78.83 | 26.64 | 489.00 | 24.89 | 78.83 | 25.10 |
December | 71.67 | 26.65 | 497.00 | 24.85 | 71.67 | 25.05 |
Annual Sum or Average | 951.33 | 26.68 | 5943.00 | 24.87 | 951.33 | 25.09 |
Minimum of Months | 70.33 | 26.54 | 454.00 | 24.77 | 70.33 | 24.98 |
Maximum of Months | 93.67 | 26.82 | 514.00 | 24.96 | 93.67 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.17 | 25.97 | 500.17 | 24.65 | 71.17 | 24.80 |
February | 66.50 | 26.34 | 454.00 | 24.72 | 66.50 | 24.91 |
March | 69.83 | 26.09 | 514.00 | 24.61 | 69.83 | 24.77 |
April | 83.83 | 26.26 | 485.00 | 24.76 | 83.83 | 24.95 |
May | 99.00 | 26.36 | 508.00 | 24.84 | 99.00 | 25.05 |
June | 79.67 | 26.56 | 496.00 | 24.79 | 79.67 | 25.01 |
July | 78.50 | 26.66 | 497.00 | 24.88 | 78.50 | 25.10 |
August | 84.00 | 25.99 | 514.00 | 24.64 | 84.00 | 24.81 |
September | 79.50 | 26.17 | 485.00 | 24.71 | 79.50 | 24.89 |
October | 89.83 | 26.14 | 502.00 | 24.75 | 89.83 | 24.94 |
November | 83.67 | 26.14 | 489.00 | 24.73 | 83.67 | 24.91 |
December | 71.50 | 25.97 | 494.83 | 24.64 | 70.17 | 24.79 |
Annual Sum or Average | 957.00 | 26.22 | 5939.00 | 24.73 | 955.67 | 24.91 |
Minimum of Months | 66.50 | 25.97 | 454.00 | 24.61 | 66.50 | 24.77 |
Maximum of Months | 99.00 | 26.66 | 514.00 | 24.88 | 99.00 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.00 | 26.54 | 502.00 | 24.85 | 83.00 | 25.06 |
February | 68.83 | 26.79 | 454.00 | 24.87 | 68.83 | 25.09 |
March | 70.00 | 26.60 | 514.00 | 24.74 | 70.00 | 24.94 |
April | 85.00 | 26.64 | 485.00 | 24.88 | 85.00 | 25.11 |
May | 98.00 | 26.47 | 508.00 | 24.87 | 98.00 | 25.09 |
June | 80.50 | 26.55 | 496.00 | 24.79 | 80.50 | 25.01 |
July | 80.50 | 26.71 | 497.00 | 24.90 | 80.50 | 25.12 |
August | 83.00 | 26.20 | 514.00 | 24.70 | 83.00 | 24.88 |
September | 81.00 | 26.57 | 485.00 | 24.84 | 81.00 | 25.06 |
October | 91.17 | 26.43 | 502.00 | 24.86 | 91.17 | 25.07 |
November | 82.00 | 26.57 | 489.00 | 24.86 | 82.00 | 25.07 |
December | 77.83 | 26.59 | 497.00 | 24.83 | 77.83 | 25.04 |
Annual Sum or Average | 980.83 | 26.55 | 5943.00 | 24.83 | 980.83 | 25.04 |
Minimum of Months | 68.83 | 26.20 | 454.00 | 24.70 | 68.83 | 24.88 |
Maximum of Months | 98.00 | 26.79 | 514.00 | 24.90 | 98.00 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.67 | 26.73 | 502.00 | 24.97 | 84.67 | 25.20 |
February | 69.00 | 26.78 | 454.00 | 24.91 | 69.00 | 25.13 |
March | 69.17 | 26.38 | 514.00 | 24.69 | 69.17 | 24.86 |
April | 84.00 | 26.19 | 485.00 | 24.74 | 84.00 | 24.92 |
May | 98.00 | 26.14 | 508.00 | 24.76 | 98.00 | 24.95 |
June | 81.67 | 26.16 | 496.00 | 24.68 | 81.67 | 24.87 |
July | 73.50 | 26.46 | 497.00 | 24.79 | 73.50 | 24.98 |
August | 85.17 | 25.81 | 514.00 | 24.60 | 85.17 | 24.75 |
September | 79.17 | 26.23 | 485.00 | 24.73 | 79.17 | 24.92 |
October | 90.17 | 26.41 | 502.00 | 24.85 | 90.17 | 25.06 |
November | 82.33 | 26.70 | 489.00 | 24.92 | 82.33 | 25.14 |
December | 79.83 | 26.77 | 497.00 | 24.97 | 79.83 | 25.19 |
Annual Sum or Average | 976.67 | 26.38 | 5943.00 | 24.80 | 976.67 | 25.00 |
Minimum of Months | 69.00 | 25.81 | 454.00 | 24.60 | 69.00 | 24.75 |
Maximum of Months | 98.00 | 26.78 | 514.00 | 24.97 | 98.00 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.00 | 26.52 | 502.00 | 24.85 | 80.00 | 25.05 |
February | 76.00 | 26.75 | 454.00 | 24.92 | 76.00 | 25.15 |
March | 78.17 | 26.80 | 514.00 | 24.83 | 78.17 | 25.06 |
April | 92.50 | 26.79 | 485.00 | 24.96 | 92.50 | 25.21 |
May | 99.00 | 26.56 | 508.00 | 24.90 | 99.00 | 25.13 |
June | 82.83 | 26.72 | 496.00 | 24.85 | 82.83 | 25.08 |
July | 90.17 | 26.79 | 497.00 | 24.98 | 90.17 | 25.22 |
August | 84.83 | 26.45 | 514.00 | 24.77 | 84.83 | 24.98 |
September | 86.67 | 26.56 | 485.00 | 24.87 | 86.67 | 25.09 |
October | 93.67 | 26.56 | 502.00 | 24.92 | 93.67 | 25.14 |
November | 85.33 | 26.59 | 489.00 | 24.90 | 85.33 | 25.12 |
December | 76.50 | 26.58 | 497.00 | 24.85 | 76.50 | 25.05 |
Annual Sum or Average | 1025.67 | 26.64 | 5943.00 | 24.88 | 1025.67 | 25.11 |
Minimum of Months | 76.00 | 26.45 | 454.00 | 24.77 | 76.00 | 24.98 |
Maximum of Months | 99.00 | 26.80 | 514.00 | 24.98 | 99.00 | 25.22 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.17 | 27.00 | 502.00 | 27.00 | 77.17 | 27.00 |
February | 145.33 | 27.00 | 454.00 | 27.00 | 145.33 | 27.00 |
March | 325.83 | 27.00 | 514.00 | 27.00 | 325.83 | 27.00 |
April | 482.00 | 27.37 | 485.00 | 27.37 | 482.00 | 27.37 |
May | 185.67 | 27.00 | 508.00 | 27.00 | 185.67 | 27.00 |
June | 249.17 | 27.00 | 496.00 | 27.00 | 249.17 | 27.00 |
July | 303.00 | 27.00 | 497.00 | 27.00 | 303.00 | 27.00 |
August | 498.00 | 27.29 | 514.00 | 27.28 | 498.00 | 27.29 |
September | 117.50 | 27.00 | 485.00 | 27.00 | 117.50 | 27.00 |
October | 156.33 | 27.00 | 502.00 | 27.00 | 156.33 | 27.00 |
November | 284.83 | 27.00 | 489.00 | 27.00 | 284.83 | 27.00 |
December | 446.33 | 27.08 | 497.00 | 27.08 | 446.33 | 27.08 |
Annual Sum or Average | 3271.17 | 27.11 | 5943.00 | 27.08 | 3271.17 | 27.09 |
Minimum of Months | 77.17 | 27.00 | 454.00 | 27.00 | 77.17 | 27.00 |
Maximum of Months | 498.00 | 27.37 | 514.00 | 27.37 | 498.00 | 27.37 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.83 | 27.00 | 502.00 | 27.00 | 17.83 | 27.00 |
February | 26.00 | 27.00 | 454.00 | 27.00 | 26.00 | 27.00 |
March | 43.50 | 27.00 | 514.00 | 27.00 | 43.50 | 27.00 |
April | 207.33 | 27.65 | 485.00 | 27.40 | 207.33 | 27.46 |
May | 29.50 | 27.00 | 508.00 | 27.00 | 29.50 | 27.00 |
June | 40.33 | 27.00 | 496.00 | 27.00 | 40.33 | 27.00 |
July | 17.17 | 27.00 | 497.00 | 27.00 | 17.17 | 27.00 |
August | 176.83 | 27.63 | 514.00 | 27.34 | 176.83 | 27.40 |
September | 18.67 | 27.00 | 485.00 | 27.00 | 18.67 | 27.00 |
October | 17.00 | 27.00 | 502.00 | 27.00 | 17.00 | 27.00 |
November | 29.50 | 27.00 | 489.00 | 27.00 | 29.50 | 27.00 |
December | 85.50 | 27.30 | 497.00 | 27.09 | 85.50 | 27.12 |
Annual Sum or Average | 709.17 | 27.38 | 5943.00 | 27.09 | 709.17 | 27.11 |
Minimum of Months | 17.00 | 27.00 | 454.00 | 27.00 | 17.00 | 27.00 |
Maximum of Months | 207.33 | 27.65 | 514.00 | 27.40 | 207.33 | 27.46 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.83 | 27.00 | 502.00 | 27.00 | 53.83 | 27.00 |
February | 80.67 | 27.00 | 454.00 | 27.00 | 80.67 | 27.00 |
March | 118.00 | 27.00 | 514.00 | 27.00 | 118.00 | 27.00 |
April | 207.50 | 27.55 | 485.00 | 27.33 | 207.50 | 27.38 |
May | 114.33 | 27.00 | 508.00 | 27.00 | 114.33 | 27.00 |
June | 108.33 | 27.00 | 496.00 | 27.00 | 108.33 | 27.00 |
July | 76.83 | 27.00 | 497.00 | 27.00 | 76.83 | 27.00 |
August | 167.67 | 27.51 | 514.00 | 27.25 | 167.67 | 27.30 |
September | 64.00 | 27.00 | 485.00 | 27.00 | 64.00 | 27.00 |
October | 57.17 | 27.00 | 502.00 | 27.00 | 57.17 | 27.00 |
November | 74.00 | 27.00 | 489.00 | 27.00 | 74.00 | 27.00 |
December | 104.67 | 27.18 | 497.00 | 27.06 | 104.67 | 27.08 |
Annual Sum or Average | 1227.00 | 27.18 | 5943.00 | 27.06 | 1227.00 | 27.08 |
Minimum of Months | 53.83 | 27.00 | 454.00 | 27.00 | 53.83 | 27.00 |
Maximum of Months | 207.50 | 27.55 | 514.00 | 27.33 | 207.50 | 27.38 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.41 | 485.00 | 29.41 | 485.00 | 29.41 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 29.00 | 514.00 | 29.00 | 514.00 | 29.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 28.26 | 497.00 | 28.26 | 497.00 | 28.26 |
Annual Sum or Average | 5943.00 | 27.48 | 5943.00 | 27.48 | 5943.00 | 27.48 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 29.41 | 514.00 | 29.41 | 514.00 | 29.41 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00039 | 43.40333 | 1.02871 | 27.36517 |
February | 454.00000 | 27.00275 | 41.10142 | 1.04298 | 27.98772 |
March | 514.00000 | 27.00189 | 40.39864 | 1.06868 | 29.11904 |
April | 485.00000 | 27.36985 | 40.03381 | 1.18062 | 34.45161 |
May | 508.00000 | 27.00014 | 47.42612 | 0.40193 | 8.40485 |
June | 496.00000 | 27.00410 | 43.40414 | 0.41815 | 8.68642 |
July | 497.00000 | 27.00221 | 40.44546 | 0.43079 | 8.90858 |
August | 514.00000 | 27.28055 | 40.00958 | 0.55266 | 11.76218 |
September | 485.00000 | 27.00014 | 46.74948 | 0.38862 | 8.18330 |
October | 502.00000 | 27.00385 | 42.43543 | 1.04592 | 28.11091 |
November | 489.00000 | 27.00223 | 40.37024 | 1.06365 | 28.89477 |
December | 497.00000 | 27.07482 | 39.13344 | 1.10302 | 30.71167 |
Annual Sum or Average | 5943.00000 | 27.06217 | 42.08035 | 0.80825 | 20.97345 |
Minimum of Months | 454.00000 | 27.00014 | 39.13344 | 0.38862 | 8.18330 |
Maximum of Months | 514.00000 | 27.36985 | 47.42612 | 1.18062 | 34.45161 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00010 | 43.68879 | 0.99636 | 25.98935 |
February | 454.00000 | 27.00241 | 41.18765 | 0.99586 | 25.97074 |
March | 514.00000 | 27.00146 | 40.42825 | 1.00436 | 26.32526 |
April | 485.00000 | 27.29372 | 40.12098 | 1.07157 | 29.36901 |
May | 508.00000 | 27.00001 | 47.90053 | 0.35496 | 7.65677 |
June | 496.00000 | 27.00370 | 43.57972 | 0.34860 | 7.56887 |
July | 497.00000 | 27.00176 | 40.49329 | 0.33590 | 7.38558 |
August | 514.00000 | 27.23473 | 40.08027 | 0.41022 | 8.79705 |
September | 485.00000 | 27.00001 | 47.24393 | 0.34018 | 7.44378 |
October | 502.00000 | 27.00344 | 42.60643 | 0.99659 | 25.99648 |
November | 489.00000 | 27.00177 | 40.41526 | 0.99887 | 26.09442 |
December | 497.00000 | 27.05678 | 39.14215 | 1.01428 | 26.78056 |
Annual Sum or Average | 5943.00000 | 27.05023 | 42.24527 | 0.73651 | 18.70759 |
Minimum of Months | 454.00000 | 27.00001 | 39.14215 | 0.33590 | 7.38558 |
Maximum of Months | 514.00000 | 27.29372 | 47.90053 | 1.07157 | 29.36901 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00014 | 43.67181 | 1.00388 | 26.32352 |
February | 454.00000 | 27.00246 | 41.19809 | 1.00664 | 26.44869 |
March | 514.00000 | 27.00150 | 40.45303 | 1.01756 | 26.90887 |
April | 485.00000 | 27.23919 | 40.18674 | 1.07783 | 29.68130 |
May | 508.00000 | 27.00001 | 47.76405 | 0.37300 | 7.97209 |
June | 496.00000 | 27.00381 | 43.56367 | 0.36784 | 7.89880 |
July | 497.00000 | 27.00184 | 40.52176 | 0.35313 | 7.67471 |
August | 514.00000 | 27.17132 | 40.16036 | 0.40876 | 8.82029 |
September | 485.00000 | 27.00001 | 47.11561 | 0.35609 | 7.71515 |
October | 502.00000 | 27.00353 | 42.61437 | 1.00604 | 26.41378 |
November | 489.00000 | 27.00185 | 40.44892 | 1.00819 | 26.50794 |
December | 497.00000 | 27.03917 | 39.19632 | 1.01865 | 26.99270 |
Annual Sum or Average | 5943.00000 | 27.03887 | 42.24594 | 0.74731 | 19.03813 |
Minimum of Months | 454.00000 | 27.00001 | 39.19632 | 0.35313 | 7.67471 |
Maximum of Months | 514.00000 | 27.23919 | 47.76405 | 1.07783 | 29.68130 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00463 | 40.84705 | 1.20170 | 35.33483 |
February | 454.00000 | 27.00301 | 40.04501 | 1.33887 | 42.28755 |
March | 514.00000 | 27.00144 | 39.95101 | 1.47528 | 49.56017 |
April | 485.00000 | 29.41157 | 38.43568 | 2.10794 | 80.85612 |
May | 508.00000 | 27.00271 | 43.06537 | 0.65119 | 13.96206 |
June | 496.00000 | 27.00483 | 41.32994 | 0.84164 | 19.95747 |
July | 497.00000 | 27.00175 | 39.80047 | 1.02386 | 27.14398 |
August | 514.00000 | 28.99753 | 38.50034 | 1.78546 | 65.61653 |
September | 485.00000 | 27.00453 | 42.49331 | 0.64817 | 13.86286 |
October | 502.00000 | 27.00451 | 40.57666 | 1.34277 | 42.49061 |
November | 489.00000 | 27.00179 | 39.71576 | 1.47633 | 49.61721 |
December | 497.00000 | 28.25711 | 38.34754 | 1.85228 | 69.33987 |
Annual Sum or Average | 5943.00000 | 27.47712 | 40.26033 | 1.31205 | 42.50603 |
Minimum of Months | 454.00000 | 27.00144 | 38.34754 | 0.64817 | 13.86286 |
Maximum of Months | 514.00000 | 29.41157 | 43.06537 | 2.10794 | 80.85612 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.60954 | 62.54508 | 0.69568 | 16.13324 |
February | 454.00000 | 24.58487 | 62.74285 | 0.68845 | 15.84716 |
March | 514.00000 | 24.47818 | 62.89564 | 0.66615 | 15.01470 |
April | 485.00000 | 24.57008 | 62.79735 | 0.69121 | 16.01694 |
May | 508.00000 | 24.54344 | 63.93572 | -0.1545 | 7.20758 |
June | 496.00000 | 24.49336 | 63.54749 | -0.1696 | 7.11885 |
July | 497.00000 | 24.63441 | 62.08741 | -0.1364 | 7.16171 |
August | 514.00000 | 24.48992 | 62.52211 | -0.1694 | 7.11098 |
September | 485.00000 | 24.56235 | 64.31526 | -0.1478 | 7.23741 |
October | 502.00000 | 24.61302 | 63.94179 | 0.70321 | 16.47963 |
November | 489.00000 | 24.62531 | 62.45883 | 0.69811 | 16.23645 |
December | 497.00000 | 24.62802 | 62.44087 | 0.70171 | 16.39857 |
Annual Sum or Average | 5943.00000 | 24.56875 | 63.02000 | 0.33542 | 12.29324 |
Minimum of Months | 454.00000 | 24.47818 | 62.08741 | -0.1696 | 7.11098 |
Maximum of Months | 514.00000 | 24.63441 | 64.31526 | 0.70321 | 16.47963 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33819 | 54.67196 | 0.59130 | 12.61485 |
February | 454.00000 | 24.24727 | 54.88679 | 0.57625 | 12.11386 |
March | 514.00000 | 24.19250 | 55.78406 | 0.57512 | 12.02917 |
April | 485.00000 | 24.25233 | 55.49850 | 0.59685 | 12.62468 |
May | 508.00000 | 24.23290 | 56.29768 | -0.2846 | 6.93874 |
June | 496.00000 | 24.19903 | 55.51194 | -0.2908 | 6.96281 |
July | 497.00000 | 24.24620 | 56.11507 | -0.2703 | 6.75805 |
August | 514.00000 | 24.21192 | 55.99031 | -0.2691 | 6.73418 |
September | 485.00000 | 24.26112 | 56.85486 | -0.2792 | 6.93430 |
October | 502.00000 | 24.27018 | 56.28829 | 0.58587 | 12.35048 |
November | 489.00000 | 24.26871 | 55.06446 | 0.58587 | 12.35449 |
December | 497.00000 | 24.27016 | 54.43551 | 0.58810 | 12.43235 |
Annual Sum or Average | 5943.00000 | 24.24897 | 55.62298 | 0.22203 | 10.04882 |
Minimum of Months | 454.00000 | 24.19250 | 54.43551 | -0.2908 | 6.73418 |
Maximum of Months | 514.00000 | 24.33819 | 56.85486 | 0.59685 | 12.62468 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.28483 | 54.95159 | 0.56190 | 11.85332 |
February | 454.00000 | 24.23695 | 55.21648 | 0.55278 | 11.54849 |
March | 514.00000 | 24.16839 | 56.66419 | 0.54377 | 11.27678 |
April | 485.00000 | 24.13965 | 57.34353 | 0.53973 | 11.15753 |
May | 508.00000 | 24.18338 | 56.81817 | -0.3287 | 7.42621 |
June | 496.00000 | 24.17291 | 56.05875 | -0.3319 | 7.49394 |
July | 497.00000 | 24.23655 | 57.02750 | -0.3152 | 7.32969 |
August | 514.00000 | 24.21284 | 57.33788 | -0.3206 | 7.41480 |
September | 485.00000 | 24.19809 | 57.43493 | -0.3252 | 7.41466 |
October | 502.00000 | 24.24717 | 56.93360 | 0.55929 | 11.70284 |
November | 489.00000 | 24.27981 | 55.70229 | 0.56240 | 11.82378 |
December | 497.00000 | 24.26640 | 55.34261 | 0.55792 | 11.70637 |
Annual Sum or Average | 5943.00000 | 24.21876 | 56.41164 | 0.18452 | 9.82929 |
Minimum of Months | 454.00000 | 24.13965 | 54.95159 | -0.3319 | 7.32969 |
Maximum of Months | 514.00000 | 24.28483 | 57.43493 | 0.56240 | 11.85332 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33107 | 55.35970 | 0.58368 | 12.41024 |
February | 454.00000 | 24.30423 | 55.41327 | 0.58119 | 12.31230 |
March | 514.00000 | 24.23338 | 56.56620 | 0.57314 | 12.03906 |
April | 485.00000 | 24.22391 | 56.88284 | 0.57394 | 12.04048 |
May | 508.00000 | 24.25650 | 56.58676 | -0.2842 | 7.02767 |
June | 496.00000 | 24.23108 | 56.07473 | -0.2900 | 7.07135 |
July | 497.00000 | 24.31323 | 56.81751 | -0.2736 | 6.98041 |
August | 514.00000 | 24.25225 | 57.19062 | -0.2925 | 7.10946 |
September | 485.00000 | 24.27101 | 57.16755 | -0.2845 | 7.05905 |
October | 502.00000 | 24.31551 | 56.94276 | 0.58490 | 12.40222 |
November | 489.00000 | 24.34373 | 55.98613 | 0.58852 | 12.52935 |
December | 497.00000 | 24.31610 | 55.72981 | 0.57960 | 12.27672 |
Annual Sum or Average | 5943.00000 | 24.28237 | 56.40102 | 0.21651 | 10.08352 |
Minimum of Months | 454.00000 | 24.22391 | 55.35970 | -0.2925 | 6.98041 |
Maximum of Months | 514.00000 | 24.34373 | 57.19062 | 0.58852 | 12.52935 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46786 | 53.79318 | 0.64636 | 14.32911 |
February | 454.00000 | 24.43973 | 53.61675 | 0.65285 | 14.52535 |
March | 514.00000 | 24.36403 | 54.81235 | 0.65694 | 14.51900 |
April | 485.00000 | 24.48119 | 54.52417 | 0.70357 | 16.04224 |
May | 508.00000 | 24.51254 | 55.14448 | -0.0889 | 6.59032 |
June | 496.00000 | 24.46622 | 54.18194 | -0.0726 | 6.43094 |
July | 497.00000 | 24.53352 | 54.69905 | -0.0876 | 6.55478 |
August | 514.00000 | 24.37585 | 55.39086 | -0.1417 | 6.39967 |
September | 485.00000 | 24.46314 | 56.05099 | -0.1499 | 6.58529 |
October | 502.00000 | 24.46452 | 55.49406 | 0.66229 | 14.79406 |
November | 489.00000 | 24.44628 | 54.08642 | 0.65425 | 14.53255 |
December | 497.00000 | 24.42060 | 53.42378 | 0.64187 | 14.18495 |
Annual Sum or Average | 5943.00000 | 24.45264 | 54.61056 | 0.33670 | 11.25569 |
Minimum of Months | 454.00000 | 24.36403 | 53.42378 | -0.1499 | 6.39967 |
Maximum of Months | 514.00000 | 24.53352 | 56.05099 | 0.70357 | 16.04224 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54680 | 53.15608 | 0.69975 | 16.03818 |
February | 454.00000 | 24.50044 | 53.07760 | 0.70727 | 16.26172 |
March | 514.00000 | 24.40233 | 54.38623 | 0.70672 | 16.13807 |
April | 485.00000 | 24.49088 | 54.29396 | 0.73735 | 17.20861 |
May | 508.00000 | 24.51141 | 55.05140 | -0.0709 | 6.74044 |
June | 496.00000 | 24.43638 | 54.26272 | -0.0842 | 6.42366 |
July | 497.00000 | 24.49725 | 54.83731 | -0.1049 | 6.57474 |
August | 514.00000 | 24.34458 | 55.43235 | -0.1375 | 6.47448 |
September | 485.00000 | 24.51656 | 55.60119 | -0.0902 | 6.74898 |
October | 502.00000 | 24.49249 | 55.19440 | 0.69029 | 15.73216 |
November | 489.00000 | 24.47131 | 53.80219 | 0.67969 | 15.36865 |
December | 497.00000 | 24.44826 | 53.09430 | 0.66798 | 15.04993 |
Annual Sum or Average | 5943.00000 | 24.47082 | 54.36089 | 0.36341 | 12.02201 |
Minimum of Months | 454.00000 | 24.34458 | 53.07760 | -0.1375 | 6.42366 |
Maximum of Months | 514.00000 | 24.54680 | 55.60119 | 0.73735 | 17.20861 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.67015 | 52.67306 | 0.76488 | 18.22693 |
February | 454.00000 | 24.57859 | 52.78893 | 0.74422 | 17.44260 |
March | 514.00000 | 24.40933 | 54.47996 | 0.69346 | 15.67747 |
April | 485.00000 | 24.46564 | 54.61742 | 0.69463 | 15.74840 |
May | 508.00000 | 24.46008 | 55.49902 | -0.1356 | 6.52310 |
June | 496.00000 | 24.39940 | 54.71016 | -0.1502 | 6.47058 |
July | 497.00000 | 24.48017 | 55.03905 | -0.1395 | 6.60680 |
August | 514.00000 | 24.34700 | 55.59988 | -0.1688 | 6.43966 |
September | 485.00000 | 24.47681 | 55.94314 | -0.1347 | 6.56961 |
October | 502.00000 | 24.53140 | 55.03415 | 0.70443 | 16.19921 |
November | 489.00000 | 24.56488 | 53.31297 | 0.73260 | 17.08820 |
December | 497.00000 | 24.64732 | 52.28815 | 0.76561 | 18.26346 |
Annual Sum or Average | 5943.00000 | 24.50145 | 54.34621 | 0.36056 | 12.55815 |
Minimum of Months | 454.00000 | 24.34700 | 52.28815 | -0.1688 | 6.43966 |
Maximum of Months | 514.00000 | 24.67015 | 55.94314 | 0.76561 | 18.26346 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.65559 | 52.71844 | 0.76771 | 18.37109 |
February | 454.00000 | 24.64646 | 52.45717 | 0.80293 | 19.53677 |
March | 514.00000 | 24.56523 | 53.57758 | 0.82879 | 20.35806 |
April | 485.00000 | 24.67287 | 53.32837 | 0.89458 | 22.89332 |
May | 508.00000 | 24.60296 | 54.52138 | 0.01688 | 6.90580 |
June | 496.00000 | 24.56423 | 53.59800 | 0.04358 | 6.89419 |
July | 497.00000 | 24.69320 | 53.86869 | 0.07483 | 7.22815 |
August | 514.00000 | 24.56664 | 54.14111 | 0.09232 | 7.03037 |
September | 485.00000 | 24.61468 | 55.10328 | 0.00009 | 6.86316 |
October | 502.00000 | 24.66535 | 54.27231 | 0.79190 | 19.17658 |
November | 489.00000 | 24.68378 | 52.73497 | 0.81053 | 19.81838 |
December | 497.00000 | 24.70250 | 51.88746 | 0.83534 | 20.75757 |
Annual Sum or Average | 5943.00000 | 24.63554 | 53.52706 | 0.49364 | 14.59800 |
Minimum of Months | 454.00000 | 24.56423 | 51.88746 | 0.00009 | 6.86316 |
Maximum of Months | 514.00000 | 24.70250 | 55.10328 | 0.89458 | 22.89332 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45041 | 54.90351 | 0.63582 | 14.05272 |
February | 454.00000 | 24.47601 | 54.73524 | 0.65309 | 14.63527 |
March | 514.00000 | 24.39096 | 56.51002 | 0.65316 | 14.47255 |
April | 485.00000 | 24.47430 | 57.10125 | 0.68945 | 15.63548 |
May | 508.00000 | 24.54020 | 56.69363 | -0.0814 | 6.83468 |
June | 496.00000 | 24.50696 | 55.68943 | -0.0629 | 6.69473 |
July | 497.00000 | 24.59507 | 56.25021 | -0.0861 | 6.85720 |
August | 514.00000 | 24.42375 | 58.42440 | -0.1490 | 6.70641 |
September | 485.00000 | 24.45635 | 57.75419 | -0.1571 | 6.71779 |
October | 502.00000 | 24.49600 | 57.61551 | 0.66641 | 15.10119 |
November | 489.00000 | 24.48131 | 55.94832 | 0.65235 | 14.60713 |
December | 497.00000 | 24.43792 | 55.41079 | 0.62933 | 13.88809 |
Annual Sum or Average | 5943.00000 | 24.47719 | 56.43481 | 0.33383 | 11.31632 |
Minimum of Months | 454.00000 | 24.39096 | 54.73524 | -0.1571 | 6.69473 |
Maximum of Months | 514.00000 | 24.59507 | 58.42440 | 0.68945 | 15.63548 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.68056 | 54.26529 | 0.72843 | 17.11681 |
February | 385.00000 | 24.68225 | 54.09898 | 0.75003 | 17.87954 |
March | 433.00000 | 24.57157 | 55.60886 | 0.74362 | 17.53699 |
April | 410.00000 | 24.66449 | 56.09199 | 0.77757 | 18.75811 |
May | 430.00000 | 24.66036 | 56.38459 | -0.0252 | 7.28446 |
June | 418.00000 | 24.59622 | 55.76106 | -0.0332 | 6.92202 |
July | 422.00000 | 24.71327 | 55.97971 | -0.0457 | 7.09135 |
August | 433.00000 | 24.54835 | 57.90937 | -0.0771 | 6.89758 |
September | 410.00000 | 24.64996 | 56.80184 | -0.0509 | 7.19202 |
October | 427.00000 | 24.67214 | 56.87742 | 0.73284 | 17.42117 |
November | 417.00000 | 24.67384 | 55.41504 | 0.72734 | 17.15038 |
December | 422.00000 | 24.66040 | 54.67084 | 0.71696 | 16.81797 |
Annual Sum or Average | 5034.00000 | 24.64719 | 55.83671 | 0.40943 | 13.13433 |
Minimum of Months | 385.00000 | 24.54835 | 54.09898 | -0.0771 | 6.89758 |
Maximum of Months | 433.00000 | 24.71327 | 57.90937 | 0.77757 | 18.75811 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.73778 | 53.16525 | 0.78080 | 18.85871 |
February | 454.00000 | 24.65569 | 53.48727 | 0.75936 | 18.06965 |
March | 514.00000 | 24.44918 | 55.96142 | 0.69512 | 15.81323 |
April | 485.00000 | 24.46101 | 57.20238 | 0.68303 | 15.42315 |
May | 508.00000 | 24.48340 | 57.25362 | -0.1317 | 6.70712 |
June | 496.00000 | 24.42779 | 56.57986 | -0.1487 | 6.67647 |
July | 497.00000 | 24.52946 | 56.79956 | -0.1439 | 6.84804 |
August | 514.00000 | 24.39220 | 58.76304 | -0.1754 | 6.71993 |
September | 485.00000 | 24.47572 | 57.57120 | -0.1390 | 6.69433 |
October | 502.00000 | 24.57234 | 56.82965 | 0.71326 | 16.67032 |
November | 489.00000 | 24.63830 | 54.63346 | 0.74461 | 17.66280 |
December | 497.00000 | 24.73157 | 53.51647 | 0.77709 | 18.80020 |
Annual Sum or Average | 5943.00000 | 24.54497 | 56.00294 | 0.36411 | 12.86408 |
Minimum of Months | 454.00000 | 24.39220 | 53.16525 | -0.1754 | 6.67647 |
Maximum of Months | 514.00000 | 24.73778 | 58.76304 | 0.78080 | 18.85871 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.59293 | 53.92489 | 0.72230 | 16.90537 |
February | 454.00000 | 24.60962 | 53.75860 | 0.74655 | 17.71744 |
March | 514.00000 | 24.52849 | 55.39713 | 0.75629 | 17.94623 |
April | 485.00000 | 24.60490 | 56.04642 | 0.78598 | 19.01396 |
May | 508.00000 | 24.57947 | 56.33980 | -0.0329 | 7.06831 |
June | 496.00000 | 24.52988 | 55.57819 | -0.0350 | 6.91261 |
July | 497.00000 | 24.64451 | 55.94173 | -0.0420 | 7.08881 |
August | 514.00000 | 24.50121 | 57.65242 | -0.0656 | 6.84346 |
September | 485.00000 | 24.55983 | 56.91310 | -0.0621 | 6.94066 |
October | 502.00000 | 24.61031 | 56.60730 | 0.73476 | 17.42897 |
November | 489.00000 | 24.60719 | 54.95511 | 0.72787 | 17.11896 |
December | 497.00000 | 24.59074 | 54.29111 | 0.71924 | 16.84060 |
Annual Sum or Average | 5943.00000 | 24.57933 | 55.63395 | 0.40971 | 13.10666 |
Minimum of Months | 454.00000 | 24.50121 | 53.75860 | -0.0656 | 6.84346 |
Maximum of Months | 514.00000 | 24.64451 | 57.65242 | 0.78598 | 19.01396 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45882 | 55.75650 | 0.64975 | 14.51458 |
February | 454.00000 | 24.48708 | 55.42700 | 0.66959 | 15.18976 |
March | 514.00000 | 24.40784 | 56.95806 | 0.67151 | 15.09585 |
April | 485.00000 | 24.49613 | 57.25289 | 0.70920 | 16.34180 |
May | 508.00000 | 24.54296 | 57.14738 | -0.0613 | 6.97610 |
June | 496.00000 | 24.50955 | 56.32495 | -0.0418 | 6.81944 |
July | 497.00000 | 24.60373 | 56.53661 | -0.0681 | 7.01578 |
August | 514.00000 | 24.42466 | 58.87766 | -0.1339 | 6.76128 |
September | 485.00000 | 24.47446 | 58.05023 | -0.1350 | 6.84332 |
October | 502.00000 | 24.50668 | 58.14929 | 0.68006 | 15.60404 |
November | 489.00000 | 24.49421 | 56.77247 | 0.66836 | 15.15901 |
December | 497.00000 | 24.44211 | 56.25296 | 0.64186 | 14.33586 |
Annual Sum or Average | 5943.00000 | 24.48704 | 56.97330 | 0.35108 | 11.68532 |
Minimum of Months | 454.00000 | 24.40784 | 55.42700 | -0.1350 | 6.76128 |
Maximum of Months | 514.00000 | 24.60373 | 58.87766 | 0.70920 | 16.34180 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.57293 | 54.66844 | 0.72210 | 16.85065 |
February | 454.00000 | 24.57923 | 54.41836 | 0.74675 | 17.71494 |
March | 514.00000 | 24.48449 | 55.98564 | 0.74827 | 17.63254 |
April | 485.00000 | 24.56902 | 56.32547 | 0.78158 | 18.83755 |
May | 508.00000 | 24.55822 | 56.78207 | -0.0245 | 7.17725 |
June | 496.00000 | 24.50582 | 56.17842 | -0.0272 | 6.80176 |
July | 497.00000 | 24.60918 | 56.35660 | -0.0484 | 7.02130 |
August | 514.00000 | 24.45780 | 58.22141 | -0.0762 | 6.77100 |
September | 485.00000 | 24.55336 | 57.13682 | -0.0513 | 7.11974 |
October | 502.00000 | 24.57170 | 57.32733 | 0.72991 | 17.27716 |
November | 489.00000 | 24.57176 | 55.83844 | 0.72289 | 16.96129 |
December | 497.00000 | 24.55459 | 55.11082 | 0.70973 | 16.53991 |
Annual Sum or Average | 5943.00000 | 24.54833 | 56.21295 | 0.40783 | 13.01214 |
Minimum of Months | 454.00000 | 24.45780 | 54.41836 | -0.0762 | 6.77100 |
Maximum of Months | 514.00000 | 24.60918 | 58.22141 | 0.78158 | 18.83755 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.67790 | 54.18054 | 0.78016 | 18.87571 |
February | 454.00000 | 24.62459 | 54.30815 | 0.76631 | 18.36752 |
March | 514.00000 | 24.45722 | 56.45733 | 0.71092 | 16.37742 |
April | 485.00000 | 24.48408 | 57.35355 | 0.70302 | 16.13403 |
May | 508.00000 | 24.49568 | 57.69435 | -0.1082 | 6.82323 |
June | 496.00000 | 24.44088 | 57.17668 | -0.1238 | 6.72247 |
July | 497.00000 | 24.54626 | 57.06067 | -0.1230 | 6.97226 |
August | 514.00000 | 24.39721 | 59.22155 | -0.1589 | 6.76163 |
September | 485.00000 | 24.49135 | 57.88214 | -0.1179 | 6.83950 |
October | 502.00000 | 24.57418 | 57.40982 | 0.72475 | 17.12041 |
November | 489.00000 | 24.61888 | 55.53593 | 0.75342 | 18.01388 |
December | 497.00000 | 24.67486 | 54.49477 | 0.77656 | 18.82919 |
Annual Sum or Average | 5943.00000 | 24.53919 | 56.58607 | 0.37822 | 13.10402 |
Minimum of Months | 454.00000 | 24.39721 | 54.18054 | -0.1589 | 6.72247 |
Maximum of Months | 514.00000 | 24.67790 | 59.22155 | 0.78016 | 18.87571 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58659 | 54.81011 | 0.73242 | 17.25893 |
February | 454.00000 | 24.60980 | 54.49538 | 0.75953 | 18.19598 |
March | 514.00000 | 24.53238 | 55.88404 | 0.77035 | 18.48099 |
April | 485.00000 | 24.61297 | 56.24826 | 0.80102 | 19.61046 |
May | 508.00000 | 24.57849 | 56.81036 | -0.0153 | 7.23681 |
June | 496.00000 | 24.53278 | 56.21554 | -0.0150 | 7.05995 |
July | 497.00000 | 24.64640 | 56.25453 | -0.0271 | 7.25595 |
August | 514.00000 | 24.49699 | 58.11373 | -0.0537 | 6.94845 |
September | 485.00000 | 24.56486 | 57.25929 | -0.0455 | 7.12303 |
October | 502.00000 | 24.60930 | 57.18754 | 0.74509 | 17.83703 |
November | 489.00000 | 24.60358 | 55.81580 | 0.73966 | 17.54645 |
December | 497.00000 | 24.58234 | 55.15808 | 0.72839 | 17.17685 |
Annual Sum or Average | 5943.00000 | 24.57908 | 56.20365 | 0.42341 | 13.43042 |
Minimum of Months | 454.00000 | 24.49699 | 54.49538 | -0.0537 | 6.94845 |
Maximum of Months | 514.00000 | 24.64640 | 58.11373 | 0.80102 | 19.61046 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.206460E+12 | 199552.55 | 27-JAN-13:05 | 585.89 | 0.153300E+13 | 0.00 | 0.173946E+13 | 5.52 | 8.33 | 23-JAN-05:13 | 0.00 | 0.00 |
February | 0.199240E+12 | 200415.26 | 01-FEB-17:00 | 605.87 | 0.146415E+13 | 0.00 | 0.166339E+13 | 6.14 | 8.30 | 24-FEB-05:14 | 0.00 | 0.00 |
March | 0.245779E+12 | 204113.10 | 27-MAR-16:50 | 696.41 | 0.179348E+13 | 0.00 | 0.203926E+13 | 6.41 | 8.29 | 04-MAR-06:04 | 0.00 | 0.00 |
April | 0.257327E+12 | 208583.64 | 11-APR-17:20 | 687.62 | 0.182731E+13 | 0.00 | 0.208464E+13 | 6.41 | 7.92 | 10-APR-03:04 | 0.00 | 0.00 |
May | 0.272877E+12 | 209654.82 | 10-MAY-16:20 | 656.66 | 0.192673E+13 | 0.00 | 0.219960E+13 | 5.97 | 7.87 | 11-MAY-03:04 | 0.00 | 0.00 |
June | 0.266060E+12 | 209583.57 | 05-JUN-16:10 | 663.13 | 0.187648E+13 | 0.00 | 0.214254E+13 | 6.17 | 7.99 | 27-JUN-04:13 | 0.00 | 0.00 |
July | 0.246448E+12 | 204153.99 | 26-JUL-16:50 | 687.19 | 0.178585E+13 | 0.00 | 0.203230E+13 | 6.22 | 8.09 | 20-JUL-04:13 | 0.00 | 0.00 |
August | 0.256899E+12 | 209111.59 | 22-AUG-11:30 | 694.05 | 0.182053E+13 | 0.00 | 0.207743E+13 | 6.14 | 7.96 | 30-AUG-04:14 | 0.00 | 0.00 |
September | 0.243844E+12 | 209416.09 | 14-SEP-11:30 | 613.00 | 0.173574E+13 | 0.00 | 0.197959E+13 | 5.77 | 7.93 | 29-SEP-03:04 | 0.00 | 0.00 |
October | 0.240602E+12 | 208307.04 | 05-OCT-11:40 | 644.92 | 0.172289E+13 | 0.00 | 0.196349E+13 | 5.81 | 8.36 | 23-OCT-04:15 | 0.00 | 0.00 |
November | 0.221899E+12 | 207502.26 | 04-NOV-13:30 | 649.02 | 0.160786E+13 | 0.00 | 0.182976E+13 | 6.00 | 8.29 | 25-NOV-06:05 | 0.00 | 0.00 |
December | 0.216504E+12 | 202699.46 | 30-DEC-13:20 | 680.03 | 0.159101E+13 | 0.00 | 0.180752E+13 | 6.07 | 8.32 | 15-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.287394E+13 | 7863.77 | 0.206850E+14 | 0.00 | 0.235590E+14 | 6.05 | 0.00 | 0.00 | ||||
Minimum of Months | 0.199240E+12 | 199552.55 | 585.89 | 0.146415E+13 | 0.00 | 0.166339E+13 | 5.52 | 7.87 | 0.00 | 0.00 | ||
Maximum of Months | 0.272877E+12 | 209654.82 | 696.41 | 0.192673E+13 | 0.00 | 0.219960E+13 | 6.41 | 8.36 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.523598E+11 | 195672.44 | 02-JAN-06:03 | 137.81 | 0.390392E+12 | 0.00 | 0.442752E+12 | 1.38 | 8.15 | 02-JAN-05:13 | 0.00 | 0.00 |
February | 0.524615E+11 | 188760.09 | 06-FEB-06:03 | 135.34 | 0.389970E+12 | 0.00 | 0.442432E+12 | 1.50 | 8.06 | 21-FEB-10:05 | 0.00 | 0.00 |
March | 0.622575E+11 | 173444.53 | 15-MAR-05:02 | 159.06 | 0.458504E+12 | 0.00 | 0.520761E+12 | 1.57 | 8.05 | 10-MAR-06:02 | 0.00 | 0.00 |
April | 0.667176E+11 | 160544.40 | 14-APR-05:04 | 163.63 | 0.480954E+12 | 0.00 | 0.547672E+12 | 1.64 | 7.73 | 14-APR-05:02 | 0.00 | 0.00 |
May | 0.836276E+11 | 207643.89 | 30-MAY-05:03 | 197.82 | 0.596236E+12 | 0.00 | 0.679863E+12 | 1.89 | 7.72 | 24-MAY-05:02 | 0.00 | 0.00 |
June | 0.938783E+11 | 192007.46 | 28-JUN-05:02 | 218.81 | 0.669482E+12 | 0.00 | 0.763360E+12 | 2.16 | 7.82 | 21-JUN-04:16 | 0.00 | 0.00 |
July | 0.559283E+11 | 173821.49 | 01-JUL-05:04 | 142.08 | 0.408038E+12 | 0.00 | 0.463966E+12 | 1.39 | 7.84 | 14-JUL-05:06 | 0.00 | 0.00 |
August | 0.814274E+11 | 199001.64 | 21-AUG-05:03 | 197.37 | 0.580890E+12 | 0.00 | 0.662317E+12 | 1.89 | 7.79 | 05-AUG-05:03 | 0.00 | 0.00 |
September | 0.649407E+11 | 202414.03 | 18-SEP-05:02 | 159.18 | 0.463763E+12 | 0.00 | 0.528703E+12 | 1.58 | 7.77 | 13-SEP-05:02 | 0.00 | 0.00 |
October | 0.603230E+11 | 196434.96 | 26-OCT-05:02 | 149.96 | 0.433426E+12 | 0.00 | 0.493749E+12 | 1.45 | 8.36 | 23-OCT-04:15 | 0.00 | 0.00 |
November | 0.605563E+11 | 194595.16 | 13-NOV-06:04 | 153.56 | 0.441642E+12 | 0.00 | 0.502198E+12 | 1.55 | 7.98 | 24-NOV-06:06 | 0.00 | 0.00 |
December | 0.469070E+11 | 194470.34 | 04-DEC-06:03 | 123.48 | 0.349842E+12 | 0.00 | 0.396749E+12 | 1.23 | 8.23 | 14-DEC-06:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.781385E+12 | 1938.10 | 0.566314E+13 | 0.00 | 0.644452E+13 | 1.60 | 0.00 | 0.00 | ||||
Minimum of Months | 0.469070E+11 | 160544.40 | 123.48 | 0.349842E+12 | 0.00 | 0.396749E+12 | 1.23 | 7.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.938783E+11 | 207643.89 | 218.81 | 0.669482E+12 | 0.00 | 0.763360E+12 | 2.16 | 8.36 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.117250E+12 | 744.00 | 43776.24 | 01-JAN-00:05 | 239258.53 | 11-JAN-15:05 | 32.56 | 28.28 | 14.18 |
February | 0.105903E+12 | 672.00 | 43776.24 | 01-FEB-00:03 | 405137.85 | 26-FEB-16:01 | 37.93 | 30.69 | 14.18 |
March | 0.117250E+12 | 744.00 | 43776.24 | 01-MAR-00:05 | 644132.95 | 31-MAR-24:00 | 43.08 | 32.87 | 14.18 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:10 | 691791.87 | 09-APR-15:32 | 47.99 | 34.99 | 14.18 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:03 | 354624.73 | 31-MAY-23:20 | 35.60 | 31.02 | 14.18 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:05 | 498177.66 | 30-JUN-23:17 | 39.70 | 32.18 | 14.18 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 641963.24 | 31-JUL-24:00 | 41.97 | 31.78 | 14.18 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:03 | 689909.03 | 13-AUG-15:31 | 46.34 | 33.36 | 14.18 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:10 | 362337.39 | 30-SEP-23:15 | 34.02 | 29.54 | 14.18 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 496885.07 | 31-OCT-23:20 | 37.46 | 30.13 | 14.18 |
November | 0.113468E+12 | 720.00 | 43776.24 | 01-NOV-00:05 | 548310.23 | 11-NOV-16:02 | 41.34 | 31.19 | 14.18 |
December | 0.117250E+12 | 744.00 | 43776.24 | 01-DEC-00:05 | 672176.31 | 31-DEC-16:22 | 44.48 | 31.68 | 14.18 |
Annual Sum or Average | 0.138053E+13 | 8760.00 | 40.22 | 31.48 | 14.18 | ||||
Minimum of Months | 0.105903E+12 | 672.00 | 43776.24 | 239258.53 | 32.56 | 28.28 | 14.18 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 691791.87 | 47.99 | 34.99 | 14.18 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.395754E+11 | 584.31 | 19698.05 | 01-JAN-00:15 | 1600756.11 | 23-JAN-08:50 | 26.20 | 24.04 | 50.98 |
February | 0.416448E+11 | 605.37 | 19698.05 | 01-FEB-00:03 | 1598940.51 | 24-FEB-08:50 | 26.51 | 24.22 | 59.09 |
March | 0.487925E+11 | 696.41 | 19698.05 | 01-MAR-00:05 | 1306759.20 | 03-MAR-08:20 | 27.53 | 24.99 | 57.87 |
April | 0.487611E+11 | 687.62 | 19698.05 | 01-APR-00:10 | 1278737.61 | 18-APR-12:05 | 29.27 | 26.59 | 53.25 |
May | 0.465654E+11 | 656.66 | 19698.05 | 01-MAY-00:03 | 1494202.51 | 31-MAY-05:04 | 30.41 | 27.68 | 45.99 |
June | 0.470247E+11 | 663.13 | 19698.05 | 01-JUN-00:15 | 1316445.63 | 28-JUN-05:04 | 30.15 | 27.40 | 50.32 |
July | 0.487304E+11 | 687.19 | 19698.05 | 01-JUL-01:05 | 1273566.51 | 03-JUL-12:05 | 28.10 | 25.57 | 54.02 |
August | 0.492172E+11 | 694.05 | 19698.05 | 01-AUG-00:15 | 1315271.64 | 21-AUG-05:05 | 29.35 | 26.77 | 52.26 |
September | 0.434697E+11 | 613.00 | 19698.05 | 01-SEP-00:10 | 1528507.72 | 18-SEP-05:04 | 29.56 | 27.02 | 45.42 |
October | 0.457332E+11 | 644.92 | 19698.05 | 01-OCT-00:05 | 1337850.46 | 26-OCT-05:04 | 28.88 | 26.44 | 47.82 |
November | 0.453751E+11 | 649.02 | 19698.05 | 01-NOV-00:05 | 1331557.92 | 27-NOV-06:20 | 27.69 | 25.34 | 53.81 |
December | 0.443267E+11 | 674.82 | 19698.05 | 01-DEC-00:25 | 1586339.07 | 20-DEC-09:00 | 26.39 | 24.15 | 57.38 |
Annual Sum or Average | 0.549216E+12 | 7856.48 | 28.34 | 25.86 | 52.31 | ||||
Minimum of Months | 0.395754E+11 | 584.31 | 19698.05 | 1273566.51 | 26.20 | 24.04 | 45.42 | ||
Maximum of Months | 0.492172E+11 | 696.41 | 19698.05 | 1600756.11 | 30.41 | 27.68 | 59.09 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.189231E+11 | 266.85 | 19698.05 | 01-JAN-20:25 | 1564056.57 | 02-JAN-06:05 | 26.20 | 24.94 | 19.87 |
February | 0.182227E+11 | 256.97 | 19698.05 | 01-FEB-08:40 | 1384732.20 | 24-FEB-15:03 | 26.51 | 25.17 | 21.42 |
March | 0.262019E+11 | 369.49 | 19698.05 | 01-MAR-04:08 | 1209695.97 | 15-MAR-05:04 | 27.53 | 25.74 | 25.99 |
April | 0.343668E+11 | 484.63 | 19698.05 | 01-APR-00:40 | 1278737.61 | 18-APR-12:05 | 29.27 | 26.95 | 32.79 |
May | 0.405418E+11 | 571.71 | 19698.05 | 01-MAY-00:07 | 1494202.51 | 31-MAY-05:04 | 30.41 | 27.77 | 37.71 |
June | 0.390662E+11 | 550.90 | 19698.05 | 01-JUN-03:28 | 1316445.63 | 28-JUN-05:04 | 30.15 | 27.54 | 39.01 |
July | 0.292608E+11 | 412.63 | 19698.05 | 01-JUL-04:08 | 1273566.51 | 03-JUL-12:05 | 28.10 | 26.09 | 27.25 |
August | 0.367770E+11 | 518.62 | 19698.05 | 01-AUG-03:05 | 1315271.64 | 21-AUG-05:05 | 29.35 | 26.95 | 35.15 |
September | 0.345439E+11 | 487.13 | 19698.05 | 01-SEP-03:06 | 1528507.72 | 18-SEP-05:04 | 29.56 | 27.22 | 32.74 |
October | 0.329858E+11 | 465.16 | 19698.05 | 01-OCT-06:13 | 1337850.46 | 26-OCT-05:04 | 28.88 | 26.70 | 30.29 |
November | 0.276549E+11 | 389.98 | 19698.05 | 01-NOV-03:17 | 1305546.38 | 15-NOV-06:03 | 27.69 | 25.80 | 27.70 |
December | 0.218191E+11 | 307.69 | 19698.05 | 01-DEC-06:04 | 1365079.52 | 07-DEC-13:03 | 26.39 | 24.91 | 21.20 |
Annual Sum or Average | 0.360364E+12 | 5081.78 | 28.34 | 26.32 | 29.28 | ||||
Minimum of Months | 0.182227E+11 | 256.97 | 19698.05 | 1209695.97 | 26.20 | 24.91 | 19.87 | ||
Maximum of Months | 0.405418E+11 | 571.71 | 19698.05 | 1564056.57 | 30.41 | 27.77 | 39.01 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 32.56 | 32.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 37.93 | 37.93 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 43.08 | 43.08 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 47.99 | 47.99 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 35.60 | 35.60 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 39.70 | 39.70 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 41.97 | 41.97 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 46.34 | 46.34 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 34.02 | 34.02 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 37.46 | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 41.34 | 41.34 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 44.48 | 44.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 | 40.22 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 32.56 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 | 47.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.164597E+12 | 0.00 | 542.86 | 0.125407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 253726.17 | 02-JAN-05:12 | 156546.35 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.167133E+12 | 0.00 | 564.73 | 0.126960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 248283.38 | 16-FEB-06:03 | 161527.88 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 |
March | 0.202867E+12 | 0.00 | 654.29 | 0.155677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257446.16 | 13-MAR-04:02 | 161020.49 | 20-MAR-04:23 | 0.00 | 0.00 | 0.00 |
April | 0.213207E+12 | 0.00 | 634.19 | 0.159876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262627.78 | 03-APR-03:02 | 164193.02 | 03-APR-04:22 | 0.00 | 0.00 | 0.00 |
May | 0.207023E+12 | 0.00 | 606.18 | 0.142264E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263670.32 | 15-MAY-04:33 | 166493.26 | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.216901E+12 | 0.00 | 620.42 | 0.149187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 248722.08 | 10-JUN-05:02 | 160880.32 | 19-JUN-04:23 | 0.00 | 0.00 | 0.00 |
July | 0.202006E+12 | 0.00 | 640.37 | 0.142191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251569.31 | 10-JUL-04:23 | 156849.84 | 03-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.232225E+12 | 0.00 | 656.82 | 0.158956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260260.13 | 14-AUG-04:23 | 164408.18 | 14-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.183468E+12 | 0.00 | 564.19 | 0.124606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 258209.45 | 21-SEP-05:02 | 162720.36 | 05-SEP-04:03 | 0.00 | 0.00 | 0.00 |
October | 0.193836E+12 | 0.00 | 602.88 | 0.129757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 253364.03 | 26-OCT-05:02 | 152835.32 | 10-OCT-03:12 | 0.00 | 0.00 | 0.00 |
November | 0.194056E+12 | 0.00 | 611.99 | 0.135021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 250696.40 | 13-NOV-06:02 | 154067.13 | 20-NOV-05:23 | 0.00 | 0.00 | 0.00 |
December | 0.194296E+12 | 0.00 | 645.51 | 0.140685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 245326.00 | 30-DEC-06:03 | 153300.45 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237162E+13 | 0.00 | 7344.43 | 0.169059E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.164597E+12 | 0.00 | 542.86 | 0.124606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 245326.00 | 152835.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.232225E+12 | 0.00 | 656.82 | 0.159876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263670.32 | 166493.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144400E+13 | 0.00 | 487.83 | 0.108894E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2571985.06 | 02-JAN-05:12 | 1442332.98 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.138569E+13 | 0.00 | 467.28 | 0.105031E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2479961.66 | 16-FEB-06:03 | 1428567.41 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.166297E+13 | 0.00 | 564.43 | 0.124741E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2456575.85 | 15-MAR-05:02 | 1408539.63 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.169000E+13 | 0.00 | 561.09 | 0.119815E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2479989.09 | 14-APR-05:02 | 1401947.04 | 14-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.187849E+13 | 0.00 | 558.27 | 0.124531E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2638846.33 | 22-MAY-05:02 | 1476908.39 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.190242E+13 | 0.00 | 548.67 | 0.126379E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2536721.60 | 10-JUN-05:02 | 1440720.25 | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.159659E+13 | 0.00 | 531.17 | 0.110003E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2475821.88 | 27-JUL-05:02 | 1428616.32 | 24-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.175502E+13 | 0.00 | 530.37 | 0.115210E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2590097.16 | 05-AUG-05:03 | 1406120.42 | 12-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.161537E+13 | 0.00 | 512.56 | 0.106727E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2521765.12 | 27-SEP-05:03 | 1482967.83 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.158222E+13 | 0.00 | 505.74 | 0.104118E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2521864.98 | 26-OCT-05:02 | 1405729.24 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.149806E+13 | 0.00 | 478.56 | 0.104208E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2470639.93 | 13-NOV-06:02 | 1430866.38 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.141488E+13 | 0.00 | 475.96 | 0.103229E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2471566.20 | 30-DEC-06:03 | 1394713.96 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194257E+14 | 0.00 | 6221.93 | 0.135289E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.138569E+13 | 0.00 | 467.28 | 0.103229E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2456575.85 | 1394713.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.190242E+13 | 0.00 | 564.43 | 0.126379E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2638846.33 | 1482967.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.151412E+12 | 0.00 | 485.94 | 0.116014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 276042.06 | 02-JAN-05:12 | 151096.87 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.147904E+12 | 0.00 | 465.25 | 0.114388E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262535.79 | 16-FEB-06:03 | 147724.08 | 16-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.180994E+12 | 0.00 | 562.39 | 0.138915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259276.19 | 15-MAR-05:02 | 147826.15 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.185598E+12 | 0.00 | 562.70 | 0.135208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261121.04 | 14-APR-05:02 | 148741.02 | 14-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.203793E+12 | 0.00 | 561.38 | 0.138879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281609.19 | 22-MAY-05:02 | 160086.22 | 30-MAY-04:03 | 0.00 | 0.00 | 0.00 |
June | 0.205693E+12 | 0.00 | 552.51 | 0.140803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271715.03 | 10-JUN-05:02 | 156730.89 | 19-JUN-04:23 | 0.00 | 0.00 | 0.00 |
July | 0.171899E+12 | 0.00 | 536.49 | 0.121229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261571.39 | 27-JUL-05:02 | 153450.33 | 03-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.187109E+12 | 0.00 | 529.79 | 0.125754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 269894.56 | 12-AUG-05:02 | 147968.66 | 12-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.173723E+12 | 0.00 | 516.25 | 0.117988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271026.96 | 21-SEP-05:02 | 158138.05 | 05-SEP-04:12 | 0.00 | 0.00 | 0.00 |
October | 0.167211E+12 | 0.00 | 511.43 | 0.112493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 266670.63 | 26-OCT-05:02 | 148720.08 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.158435E+12 | 0.00 | 478.73 | 0.112371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259087.35 | 13-NOV-06:02 | 150153.75 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.148596E+12 | 0.00 | 476.22 | 0.109956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 254936.26 | 18-DEC-06:02 | 148550.15 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208237E+13 | 0.00 | 6239.09 | 0.148400E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.147904E+12 | 0.00 | 465.25 | 0.109956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 254936.26 | 147724.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.205693E+12 | 0.00 | 562.70 | 0.140803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281609.19 | 160086.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.110559E+12 | 0.00 | 457.15 | 0.843706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178847.95 | 02-JAN-05:12 | 96422.49 | 15-JAN-16:50 | 0.00 | 0.00 | 0.00 |
February | 0.101612E+12 | 0.00 | 409.92 | 0.772907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180549.55 | 05-FEB-17:17 | 100459.01 | 26-FEB-16:09 | 0.00 | 0.00 | 0.00 |
March | 0.124816E+12 | 0.00 | 470.99 | 0.916782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187187.13 | 27-MAR-00:53 | 100264.08 | 19-MAR-14:11 | 0.00 | 0.00 | 0.00 |
April | 0.134740E+12 | 0.00 | 449.22 | 0.897075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200493.79 | 30-APR-16:40 | 95000.91 | 23-APR-14:46 | 0.00 | 0.00 | 0.00 |
May | 0.151794E+12 | 0.00 | 473.47 | 0.919224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206407.01 | 29-MAY-07:23 | 91491.21 | 07-MAY-14:48 | 0.00 | 0.00 | 0.00 |
June | 0.150431E+12 | 0.00 | 456.67 | 0.908182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207026.04 | 11-JUN-16:11 | 95270.46 | 18-JUN-14:08 | 0.00 | 0.00 | 0.00 |
July | 0.126569E+12 | 0.00 | 453.52 | 0.855538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184937.98 | 02-JUL-16:18 | 96365.93 | 04-JUL-14:28 | 0.00 | 0.00 | 0.00 |
August | 0.155493E+12 | 0.00 | 483.88 | 0.941780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211158.84 | 13-AUG-13:52 | 89796.46 | 27-AUG-16:09 | 0.00 | 0.00 | 0.00 |
September | 0.133773E+12 | 0.00 | 443.65 | 0.827132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205611.46 | 04-SEP-11:13 | 87423.36 | 24-SEP-15:27 | 0.00 | 0.00 | 0.00 |
October | 0.131669E+12 | 0.00 | 451.98 | 0.827978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204625.10 | 09-OCT-11:52 | 88678.15 | 08-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.122770E+12 | 0.00 | 441.14 | 0.823343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 201875.27 | 12-NOV-14:42 | 89797.11 | 05-NOV-14:52 | 0.00 | 0.00 | 0.00 |
December | 0.112872E+12 | 0.00 | 444.79 | 0.831961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192872.79 | 10-DEC-21:27 | 94372.17 | 24-DEC-15:08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155710E+13 | 0.00 | 5436.36 | 0.103656E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.101612E+12 | 0.00 | 409.92 | 0.772907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178847.95 | 87423.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.155493E+12 | 0.00 | 483.88 | 0.941780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211158.84 | 100459.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.358908E+12 | 0.979433E+11 | 744.00 | 0.337364E+12 | 0.215440E+11 | 0.00 | 0.40 | 03-JAN-15:00 | 0.33 | 23-JAN-06:00 | 141836.22 | 11-JAN-17:00 | 130934.60 | 05-JAN-15:00 | 12653.63 | 11-JAN-17:10 | 46129.81 | 04-JAN-13:50 | 0.00 |
February | 0.547228E+12 | 0.152024E+12 | 672.00 | 0.526326E+12 | 0.209015E+11 | 0.00 | 0.65 | 28-FEB-15:00 | 0.56 | 01-FEB-07:00 | 235242.02 | 15-FEB-14:40 | 223158.02 | 21-FEB-14:05 | 14898.94 | 15-FEB-15:00 | 78214.11 | 28-FEB-15:00 | 0.00 |
March | 0.854154E+12 | 0.241217E+12 | 744.00 | 0.829344E+12 | 0.248104E+11 | 0.00 | 1.00 | 31-MAR-23:03 | 0.78 | 03-MAR-06:00 | 401314.32 | 31-MAR-24:00 | 392357.66 | 31-MAR-24:00 | 15106.77 | 14-MAR-11:00 | 110860.32 | 21-MAR-13:10 | 0.00 |
April | 0.105619E+13 | 0.294671E+12 | 720.00 | 0.102896E+13 | 0.272309E+11 | 0.00 | 1.00 | 01-APR-00:10 | 0.43 | 30-APR-23:17 | 422621.44 | 14-APR-16:00 | 404757.41 | 14-APR-16:00 | 19053.37 | 20-APR-16:00 | 127459.94 | 01-APR-14:00 | 0.00 |
May | 0.377096E+12 | 0.109368E+12 | 744.00 | 0.341648E+12 | 0.354478E+11 | 0.00 | 0.58 | 31-MAY-23:05 | 0.36 | 10-MAY-21:10 | 227862.55 | 31-MAY-23:05 | 211339.92 | 31-MAY-23:55 | 17871.36 | 03-MAY-14:00 | 56358.97 | 31-MAY-23:15 | 0.00 |
June | 0.602660E+12 | 0.172726E+12 | 720.00 | 0.566637E+12 | 0.360227E+11 | 0.00 | 0.80 | 30-JUN-23:05 | 0.57 | 01-JUN-02:00 | 318824.12 | 30-JUN-23:05 | 303222.27 | 30-JUN-24:00 | 18686.58 | 15-JUN-10:20 | 81981.35 | 13-JUN-15:00 | 0.00 |
July | 0.857738E+12 | 0.234928E+12 | 744.00 | 0.828970E+12 | 0.287679E+11 | 0.00 | 1.00 | 31-JUL-23:10 | 0.79 | 13-JUL-05:00 | 406059.45 | 31-JUL-23:10 | 394319.63 | 31-JUL-23:30 | 17338.61 | 17-JUL-15:50 | 105653.31 | 31-JUL-24:00 | 0.00 |
August | 0.109782E+13 | 0.295125E+12 | 744.00 | 0.106458E+13 | 0.332354E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.42 | 31-AUG-24:00 | 426182.78 | 07-AUG-15:00 | 405522.53 | 23-AUG-20:00 | 23634.10 | 07-AUG-15:00 | 124579.27 | 13-AUG-15:00 | 0.00 |
September | 0.360908E+12 | 0.100789E+12 | 720.00 | 0.329052E+12 | 0.318557E+11 | 0.00 | 0.59 | 30-SEP-23:05 | 0.36 | 16-SEP-20:00 | 229759.93 | 30-SEP-23:05 | 211856.99 | 30-SEP-24:00 | 18598.85 | 30-SEP-23:05 | 60477.69 | 30-SEP-23:15 | 0.00 |
October | 0.615438E+12 | 0.167341E+12 | 744.00 | 0.582386E+12 | 0.330516E+11 | 0.00 | 0.80 | 31-OCT-23:15 | 0.58 | 23-OCT-05:00 | 317076.85 | 31-OCT-23:05 | 303075.43 | 31-OCT-23:55 | 17038.68 | 06-OCT-10:00 | 81487.45 | 31-OCT-23:15 | 0.00 |
November | 0.829028E+12 | 0.223664E+12 | 720.00 | 0.800879E+12 | 0.281487E+11 | 0.00 | 0.86 | 13-NOV-14:00 | 0.77 | 25-NOV-05:20 | 328737.22 | 14-NOV-16:10 | 313596.57 | 13-NOV-14:00 | 16289.76 | 14-NOV-16:10 | 104222.24 | 18-NOV-13:00 | 0.00 |
December | 0.108976E+13 | 0.284623E+12 | 744.00 | 0.106719E+13 | 0.225667E+11 | 0.00 | 1.00 | 01-DEC-08:70 | 0.95 | 21-DEC-06:00 | 416524.27 | 05-DEC-21:00 | 403818.44 | 26-DEC-22:03 | 15841.58 | 29-DEC-20:00 | 122114.22 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.864693E+13 | 0.237442E+13 | 8760.00 | 0.830334E+13 | 0.343583E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.358908E+12 | 0.979433E+11 | 672.00 | 0.329052E+12 | 0.209015E+11 | 0.00 | 0.40 | 0.33 | 141836.22 | 130934.60 | 12653.63 | 46129.81 | 0.00 | ||||||
Maximum of Months | 0.109782E+13 | 0.295125E+12 | 744.00 | 0.106719E+13 | 0.360227E+11 | 0.00 | 1.00 | 0.95 | 426182.78 | 405522.53 | 23634.10 | 127459.94 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.693816E+10 | 0.184177E+10 | 744.00 | 0.606384E+10 | 0.874322E+09 | 0.00 | 0.39 | 16-JAN-17:32 | 0.26 | 24-JAN-07:50 | 3122.71 | 16-JAN-17:32 | 2868.17 | 16-JAN-17:33 | 512.74 | 10-JAN-10:05 | 923.61 | 05-JAN-15:00 | 0.00 |
February | 0.109618E+11 | 0.297189E+10 | 672.00 | 0.100698E+11 | 0.892024E+09 | 0.00 | 0.63 | 20-FEB-16:00 | 0.49 | 01-FEB-07:30 | 5063.51 | 20-FEB-17:12 | 4711.44 | 20-FEB-17:30 | 588.63 | 15-FEB-15:00 | 1592.38 | 28-FEB-15:00 | 0.00 |
March | 0.173627E+11 | 0.479122E+10 | 744.00 | 0.162617E+11 | 0.110108E+10 | 0.00 | 0.96 | 31-MAR-24:00 | 0.71 | 03-MAR-06:00 | 8384.72 | 31-MAR-23:03 | 7816.88 | 31-MAR-24:00 | 615.38 | 14-MAR-11:00 | 2250.13 | 19-MAR-14:02 | 0.00 |
April | 0.220232E+11 | 0.613758E+10 | 720.00 | 0.206941E+11 | 0.132915E+10 | 0.00 | 1.00 | 01-APR-10:10 | 0.40 | 30-APR-23:05 | 8833.54 | 09-APR-15:57 | 8295.55 | 09-APR-17:33 | 736.11 | 20-APR-16:00 | 2680.68 | 01-APR-14:00 | 0.00 |
May | 0.769713E+10 | 0.214272E+10 | 744.00 | 0.622164E+10 | 0.147548E+10 | 0.00 | 0.55 | 31-MAY-23:05 | 0.29 | 25-MAY-21:20 | 4727.31 | 31-MAY-23:05 | 3982.05 | 31-MAY-23:55 | 777.73 | 31-MAY-23:05 | 1119.09 | 31-MAY-23:15 | 0.00 |
June | 0.124598E+11 | 0.345336E+10 | 720.00 | 0.109005E+11 | 0.155934E+10 | 0.00 | 0.75 | 30-JUN-23:05 | 0.52 | 21-JUN-06:00 | 6535.89 | 30-JUN-23:05 | 5836.90 | 30-JUN-24:00 | 823.79 | 15-JUN-10:10 | 1709.98 | 13-JUN-15:00 | 0.00 |
July | 0.174509E+11 | 0.466395E+10 | 744.00 | 0.161731E+11 | 0.127781E+10 | 0.00 | 0.95 | 31-JUL-23:20 | 0.72 | 19-JUL-21:20 | 8368.51 | 31-JUL-23:10 | 7774.94 | 31-JUL-24:00 | 724.34 | 10-JUL-15:00 | 2119.47 | 31-JUL-24:00 | 0.00 |
August | 0.227921E+11 | 0.609362E+10 | 744.00 | 0.212045E+11 | 0.158760E+10 | 0.00 | 1.00 | 01-AUG-08:20 | 0.36 | 31-AUG-23:13 | 8975.13 | 07-AUG-15:00 | 8258.64 | 28-AUG-01:32 | 886.73 | 15-AUG-14:00 | 2622.36 | 13-AUG-15:00 | 0.00 |
September | 0.721062E+10 | 0.193817E+10 | 720.00 | 0.589417E+10 | 0.131645E+10 | 0.00 | 0.56 | 30-SEP-23:05 | 0.29 | 15-SEP-21:20 | 4795.08 | 30-SEP-23:05 | 3999.86 | 30-SEP-24:00 | 823.46 | 30-SEP-23:05 | 1207.28 | 30-SEP-23:15 | 0.00 |
October | 0.124874E+11 | 0.329395E+10 | 744.00 | 0.110652E+11 | 0.142211E+10 | 0.00 | 0.75 | 31-OCT-23:05 | 0.52 | 30-OCT-21:20 | 6481.11 | 31-OCT-23:05 | 5835.99 | 31-OCT-24:00 | 704.05 | 16-OCT-10:50 | 1614.99 | 31-OCT-23:15 | 0.00 |
November | 0.168423E+11 | 0.443544E+10 | 720.00 | 0.155935E+11 | 0.124886E+10 | 0.00 | 0.84 | 11-NOV-15:02 | 0.70 | 25-NOV-07:10 | 6998.12 | 20-NOV-17:00 | 6498.95 | 19-NOV-17:02 | 715.22 | 14-NOV-16:50 | 2055.11 | 11-NOV-14:22 | 0.00 |
December | 0.222548E+11 | 0.576947E+10 | 744.00 | 0.211786E+11 | 0.107623E+10 | 0.00 | 1.00 | 01-DEC-14:05 | 0.87 | 21-DEC-07:00 | 8803.74 | 25-DEC-18:03 | 8312.22 | 03-DEC-17:10 | 699.21 | 18-DEC-17:00 | 2568.72 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.176481E+12 | 0.475331E+11 | 8760.00 | 0.161321E+12 | 0.151605E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.693816E+10 | 0.184177E+10 | 672.00 | 0.589417E+10 | 0.874322E+09 | 0.00 | 0.39 | 0.26 | 3122.71 | 2868.17 | 512.74 | 923.61 | 0.00 | ||||||
Maximum of Months | 0.227921E+11 | 0.613758E+10 | 744.00 | 0.212045E+11 | 0.158760E+10 | 0.00 | 1.00 | 0.87 | 8975.13 | 8312.22 | 886.73 | 2680.68 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.652001E+11 | 0.173200E+11 | 744.00 | 0.565592E+11 | 0.864086E+10 | 0.00 | 0.39 | 16-JAN-17:22 | 0.25 | 24-JAN-07:00 | 29315.70 | 16-JAN-17:32 | 26793.60 | 16-JAN-17:33 | 5085.94 | 10-JAN-10:05 | 8822.66 | 05-JAN-15:00 | 0.00 |
February | 0.104632E+12 | 0.283565E+11 | 672.00 | 0.957482E+11 | 0.888405E+10 | 0.00 | 0.63 | 26-FEB-16:00 | 0.49 | 24-FEB-07:00 | 48132.01 | 13-FEB-17:00 | 43957.88 | 20-FEB-17:30 | 5861.61 | 14-FEB-17:00 | 15240.62 | 28-FEB-15:00 | 0.00 |
March | 0.165850E+12 | 0.457554E+11 | 744.00 | 0.154859E+12 | 0.109914E+11 | 0.00 | 0.97 | 31-MAR-23:15 | 0.71 | 04-MAR-07:00 | 80987.68 | 31-MAR-23:03 | 75060.13 | 31-MAR-24:00 | 6160.85 | 31-MAR-23:03 | 21493.33 | 31-MAR-24:00 | 0.00 |
April | 0.208806E+12 | 0.583078E+11 | 720.00 | 0.195500E+12 | 0.133054E+11 | 0.00 | 1.00 | 01-APR-10:00 | 0.35 | 30-APR-23:17 | 84014.59 | 20-APR-16:00 | 78133.63 | 23-APR-18:00 | 7326.36 | 20-APR-16:00 | 25628.03 | 01-APR-14:00 | 0.00 |
May | 0.726226E+11 | 0.202039E+11 | 744.00 | 0.580203E+11 | 0.146023E+11 | 0.00 | 0.56 | 31-MAY-23:05 | 0.28 | 25-MAY-21:20 | 46242.00 | 31-MAY-23:05 | 38816.26 | 31-MAY-23:55 | 8012.04 | 31-MAY-23:05 | 10914.63 | 31-MAY-23:15 | 0.00 |
June | 0.118980E+12 | 0.329487E+11 | 720.00 | 0.103452E+12 | 0.155286E+11 | 0.00 | 0.75 | 30-JUN-23:05 | 0.52 | 30-JUN-21:05 | 62597.30 | 30-JUN-23:05 | 55757.10 | 30-JUN-24:00 | 8218.48 | 15-JUN-10:10 | 16357.31 | 13-JUN-15:00 | 0.00 |
July | 0.166548E+12 | 0.445037E+11 | 744.00 | 0.153795E+12 | 0.127530E+11 | 0.00 | 0.96 | 31-JUL-23:10 | 0.72 | 19-JUL-21:20 | 80765.01 | 31-JUL-23:10 | 74774.85 | 31-JUL-24:00 | 7221.23 | 10-JUL-15:00 | 20409.33 | 31-JUL-24:00 | 0.00 |
August | 0.216686E+12 | 0.579950E+11 | 744.00 | 0.200807E+12 | 0.158799E+11 | 0.00 | 1.00 | 01-AUG-08:00 | 0.32 | 31-AUG-23:13 | 85729.93 | 07-AUG-15:00 | 77805.92 | 13-AUG-17:40 | 8781.54 | 15-AUG-14:00 | 25059.11 | 13-AUG-15:00 | 0.00 |
September | 0.677081E+11 | 0.181975E+11 | 720.00 | 0.546981E+11 | 0.130101E+11 | 0.00 | 0.57 | 30-SEP-23:05 | 0.28 | 15-SEP-21:20 | 46753.02 | 30-SEP-23:05 | 38603.00 | 30-SEP-23:50 | 8391.99 | 30-SEP-23:05 | 11708.40 | 30-SEP-23:15 | 0.00 |
October | 0.118861E+12 | 0.313433E+11 | 744.00 | 0.104707E+12 | 0.141540E+11 | 0.00 | 0.75 | 31-OCT-23:05 | 0.51 | 30-OCT-21:20 | 62233.57 | 31-OCT-23:05 | 55933.30 | 31-OCT-24:00 | 7013.47 | 16-OCT-10:50 | 15482.04 | 31-OCT-23:15 | 0.00 |
November | 0.160955E+12 | 0.423732E+11 | 720.00 | 0.148490E+12 | 0.124652E+11 | 0.00 | 0.83 | 20-NOV-17:00 | 0.69 | 25-NOV-07:20 | 66804.19 | 20-NOV-17:00 | 61600.28 | 19-NOV-17:00 | 7140.72 | 14-NOV-16:50 | 19581.53 | 18-NOV-13:00 | 0.00 |
December | 0.211973E+12 | 0.549884E+11 | 744.00 | 0.201205E+12 | 0.107682E+11 | 0.00 | 1.00 | 01-DEC-14:00 | 0.86 | 21-DEC-07:00 | 83773.17 | 25-DEC-18:03 | 79022.61 | 24-DEC-17:30 | 6987.70 | 18-DEC-17:00 | 24557.41 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.167882E+13 | 0.452293E+12 | 8760.00 | 0.152784E+13 | 0.150983E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.652001E+11 | 0.173200E+11 | 672.00 | 0.546981E+11 | 0.864086E+10 | 0.00 | 0.39 | 0.25 | 29315.70 | 26793.60 | 5085.94 | 8822.66 | 0.00 | ||||||
Maximum of Months | 0.216686E+12 | 0.583078E+11 | 744.00 | 0.201205E+12 | 0.158799E+11 | 0.00 | 1.00 | 0.86 | 85729.93 | 79022.61 | 8781.54 | 25628.03 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.658385E+10 | 0.175284E+10 | 744.00 | 0.571930E+10 | 0.864554E+09 | 0.00 | 0.41 | 16-JAN-17:32 | 0.23 | 24-JAN-07:00 | 3176.07 | 16-JAN-17:32 | 2918.82 | 16-JAN-17:33 | 512.52 | 10-JAN-12:00 | 915.28 | 29-JAN-17:12 | 0.00 |
February | 0.105482E+11 | 0.286375E+10 | 672.00 | 0.965996E+10 | 0.888211E+09 | 0.00 | 0.65 | 26-FEB-16:00 | 0.48 | 24-FEB-07:20 | 5048.70 | 20-FEB-16:52 | 4686.28 | 20-FEB-17:30 | 586.98 | 15-FEB-15:00 | 1592.88 | 26-FEB-15:11 | 0.00 |
March | 0.167087E+11 | 0.461771E+10 | 744.00 | 0.156102E+11 | 0.109849E+10 | 0.00 | 0.96 | 31-MAR-23:15 | 0.69 | 04-MAR-07:00 | 8116.39 | 31-MAR-23:03 | 7526.28 | 31-MAR-24:00 | 615.01 | 31-MAR-23:03 | 2226.66 | 19-MAR-15:41 | 0.00 |
April | 0.210505E+11 | 0.589145E+10 | 720.00 | 0.197200E+11 | 0.133051E+10 | 0.00 | 1.00 | 01-APR-11:00 | 0.36 | 30-APR-23:17 | 8532.77 | 09-APR-15:57 | 8002.43 | 23-APR-18:00 | 740.02 | 20-APR-16:00 | 2609.02 | 01-APR-14:00 | 0.00 |
May | 0.741314E+10 | 0.206543E+10 | 744.00 | 0.594826E+10 | 0.146488E+10 | 0.00 | 0.55 | 31-MAY-23:05 | 0.27 | 25-MAY-21:13 | 4626.79 | 31-MAY-23:05 | 3889.62 | 31-MAY-23:55 | 799.59 | 31-MAY-23:05 | 1094.43 | 31-MAY-23:15 | 0.00 |
June | 0.120310E+11 | 0.333619E+10 | 720.00 | 0.104774E+11 | 0.155363E+10 | 0.00 | 0.74 | 30-JUN-23:05 | 0.50 | 30-JUN-21:05 | 6216.33 | 30-JUN-23:05 | 5533.26 | 30-JUN-24:00 | 823.21 | 15-JUN-10:10 | 1672.29 | 11-JUN-15:30 | 0.00 |
July | 0.167770E+11 | 0.449034E+10 | 744.00 | 0.155024E+11 | 0.127462E+10 | 0.00 | 0.94 | 31-JUL-23:20 | 0.70 | 22-JUL-07:00 | 8072.26 | 31-JUL-23:10 | 7478.51 | 31-JUL-24:00 | 721.97 | 10-JUL-15:00 | 2046.22 | 31-JUL-24:00 | 0.00 |
August | 0.217958E+11 | 0.584936E+10 | 744.00 | 0.202078E+11 | 0.158799E+10 | 0.00 | 1.00 | 01-AUG-09:00 | 0.32 | 31-AUG-23:13 | 8657.11 | 07-AUG-14:50 | 7967.55 | 13-AUG-17:30 | 886.33 | 15-AUG-14:00 | 2552.03 | 13-AUG-15:00 | 0.00 |
September | 0.690058E+10 | 0.185681E+10 | 720.00 | 0.559558E+10 | 0.130500E+10 | 0.00 | 0.57 | 30-SEP-23:05 | 0.26 | 16-SEP-06:40 | 4701.22 | 30-SEP-23:05 | 3899.61 | 30-SEP-23:50 | 829.02 | 30-SEP-23:05 | 1180.63 | 30-SEP-23:15 | 0.00 |
October | 0.119800E+11 | 0.316389E+10 | 744.00 | 0.105647E+11 | 0.141532E+10 | 0.00 | 0.74 | 31-OCT-23:05 | 0.49 | 31-OCT-06:00 | 6213.75 | 31-OCT-23:05 | 5586.83 | 31-OCT-24:00 | 703.42 | 16-OCT-10:50 | 1549.61 | 31-OCT-23:15 | 0.00 |
November | 0.161732E+11 | 0.426602E+10 | 720.00 | 0.149277E+11 | 0.124555E+10 | 0.00 | 0.85 | 19-NOV-16:42 | 0.67 | 25-NOV-07:20 | 6920.90 | 19-NOV-16:44 | 6424.45 | 19-NOV-17:00 | 713.42 | 14-NOV-16:50 | 2016.21 | 11-NOV-14:41 | 0.00 |
December | 0.212610E+11 | 0.553014E+10 | 744.00 | 0.201853E+11 | 0.107564E+10 | 0.00 | 1.00 | 01-DEC-14:30 | 0.83 | 21-DEC-07:00 | 8543.46 | 25-DEC-18:03 | 8074.68 | 24-DEC-17:30 | 697.57 | 18-DEC-17:00 | 2499.74 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.169223E+12 | 0.456839E+11 | 8760.00 | 0.154119E+12 | 0.151044E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.658385E+10 | 0.175284E+10 | 672.00 | 0.559558E+10 | 0.864554E+09 | 0.00 | 0.41 | 0.23 | 3176.07 | 2918.82 | 512.52 | 915.28 | 0.00 | ||||||
Maximum of Months | 0.217958E+11 | 0.589145E+10 | 744.00 | 0.202078E+11 | 0.158799E+10 | 0.00 | 1.00 | 0.83 | 8657.11 | 8074.68 | 886.33 | 2609.02 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.73 | 0.00 | 141.73 | 318.67 | 79.51 | 0.00 | 0.00 | 0.00 |
February | 151.19 | 0.00 | 151.19 | 357.61 | 59.01 | 0.00 | 0.00 | 0.00 |
March | 155.16 | 0.00 | 155.16 | 389.03 | 40.72 | 0.00 | 0.00 | 0.00 |
April | 168.86 | 2.39 | 166.47 | 432.47 | 20.28 | 0.00 | 0.00 | 0.00 |
May | 216.46 | 23.06 | 193.40 | 559.91 | 21.93 | 0.00 | 0.00 | 0.00 |
June | 264.41 | 53.44 | 210.98 | 665.16 | 25.08 | 0.00 | 0.00 | 0.00 |
July | 227.37 | 23.83 | 203.54 | 521.03 | 44.33 | 0.00 | 0.00 | 0.00 |
August | 187.20 | 7.98 | 179.22 | 432.15 | 36.27 | 0.00 | 0.00 | 0.00 |
September | 159.38 | 0.08 | 159.30 | 383.50 | 32.91 | 0.00 | 0.00 | 0.00 |
October | 153.57 | 0.00 | 153.57 | 341.13 | 42.11 | 0.00 | 0.00 | 0.00 |
November | 145.31 | 0.00 | 145.31 | 324.20 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 303.75 | 88.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.80 | 9.26 | 166.54 | 419.20 | 45.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 303.75 | 20.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 264.41 | 53.44 | 210.98 | 665.16 | 88.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.73 | 0.00 | 141.73 | 318.67 | 79.51 | 0.00 | 0.00 | 0.00 |
February | 151.19 | 0.00 | 151.19 | 357.61 | 59.01 | 0.00 | 0.00 | 0.00 |
March | 155.16 | 0.00 | 155.16 | 389.03 | 40.72 | 0.00 | 0.00 | 0.00 |
April | 168.86 | 2.39 | 166.47 | 432.47 | 20.28 | 0.00 | 0.00 | 0.00 |
May | 216.46 | 23.06 | 193.40 | 559.90 | 21.93 | 0.00 | 0.00 | 0.00 |
June | 264.41 | 53.44 | 210.97 | 665.16 | 25.08 | 0.00 | 0.00 | 0.00 |
July | 227.37 | 23.83 | 203.54 | 521.03 | 44.33 | 0.00 | 0.00 | 0.00 |
August | 187.20 | 7.98 | 179.22 | 432.15 | 36.27 | 0.00 | 0.00 | 0.00 |
September | 159.38 | 0.08 | 159.30 | 383.50 | 32.91 | 0.00 | 0.00 | 0.00 |
October | 153.57 | 0.00 | 153.57 | 341.13 | 42.11 | 0.00 | 0.00 | 0.00 |
November | 145.31 | 0.00 | 145.31 | 324.20 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 303.75 | 88.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.80 | 9.26 | 166.54 | 419.20 | 45.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 303.75 | 20.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 264.41 | 53.44 | 210.97 | 665.16 | 88.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.73 | 0.00 | 141.73 | 318.67 | 79.51 | 0.00 | 0.00 | 0.00 |
February | 151.19 | 0.00 | 151.19 | 357.61 | 59.01 | 0.00 | 0.00 | 0.00 |
March | 155.16 | 0.00 | 155.16 | 389.03 | 40.72 | 0.00 | 0.00 | 0.00 |
April | 168.86 | 2.39 | 166.47 | 432.47 | 20.28 | 0.00 | 0.00 | 0.00 |
May | 216.46 | 23.06 | 193.40 | 559.91 | 21.93 | 0.00 | 0.00 | 0.00 |
June | 264.41 | 53.44 | 210.98 | 665.16 | 25.08 | 0.00 | 0.00 | 0.00 |
July | 227.37 | 23.83 | 203.54 | 521.03 | 44.33 | 0.00 | 0.00 | 0.00 |
August | 187.20 | 7.98 | 179.22 | 432.15 | 36.27 | 0.00 | 0.00 | 0.00 |
September | 159.38 | 0.08 | 159.30 | 383.50 | 32.91 | 0.00 | 0.00 | 0.00 |
October | 153.57 | 0.00 | 153.57 | 341.13 | 42.11 | 0.00 | 0.00 | 0.00 |
November | 145.31 | 0.00 | 145.31 | 324.20 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 303.75 | 88.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.80 | 9.26 | 166.54 | 419.20 | 45.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 303.75 | 20.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 264.41 | 53.44 | 210.98 | 665.16 | 88.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.73 | 0.00 | 141.73 | 318.67 | 79.51 | 0.00 | 0.00 | 0.00 |
February | 151.19 | 0.00 | 151.19 | 357.61 | 59.01 | 0.00 | 0.00 | 0.00 |
March | 155.16 | 0.00 | 155.16 | 389.03 | 40.72 | 0.00 | 0.00 | 0.00 |
April | 168.86 | 2.39 | 166.47 | 432.47 | 20.28 | 0.00 | 0.00 | 0.00 |
May | 216.46 | 23.06 | 193.40 | 559.90 | 21.93 | 0.00 | 0.00 | 0.00 |
June | 264.41 | 53.44 | 210.97 | 665.16 | 25.08 | 0.00 | 0.00 | 0.00 |
July | 227.37 | 23.83 | 203.54 | 521.03 | 44.33 | 0.00 | 0.00 | 0.00 |
August | 187.20 | 7.98 | 179.22 | 432.15 | 36.27 | 0.00 | 0.00 | 0.00 |
September | 159.38 | 0.08 | 159.30 | 383.50 | 32.91 | 0.00 | 0.00 | 0.00 |
October | 153.57 | 0.00 | 153.57 | 341.13 | 42.11 | 0.00 | 0.00 | 0.00 |
November | 145.31 | 0.00 | 145.31 | 324.20 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 137.69 | 0.00 | 137.69 | 303.75 | 88.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.80 | 9.26 | 166.54 | 419.20 | 45.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.69 | 0.00 | 137.69 | 303.75 | 20.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 264.41 | 53.44 | 210.97 | 665.16 | 88.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.72 | 0.00 | 141.72 | 318.66 | 79.50 | 0.00 | 0.00 | 0.00 |
February | 151.18 | 0.00 | 151.18 | 357.59 | 59.00 | 0.00 | 0.00 | 0.00 |
March | 155.16 | 0.00 | 155.16 | 389.01 | 40.72 | 0.00 | 0.00 | 0.00 |
April | 168.85 | 2.39 | 166.46 | 432.45 | 20.28 | 0.00 | 0.00 | 0.00 |
May | 216.45 | 23.06 | 193.39 | 559.88 | 21.93 | 0.00 | 0.00 | 0.00 |
June | 264.40 | 53.43 | 210.97 | 665.13 | 25.08 | 0.00 | 0.00 | 0.00 |
July | 227.36 | 23.83 | 203.53 | 521.01 | 44.33 | 0.00 | 0.00 | 0.00 |
August | 187.19 | 7.98 | 179.21 | 432.13 | 36.27 | 0.00 | 0.00 | 0.00 |
September | 159.37 | 0.08 | 159.30 | 383.49 | 32.91 | 0.00 | 0.00 | 0.00 |
October | 153.56 | 0.00 | 153.56 | 341.12 | 42.11 | 0.00 | 0.00 | 0.00 |
November | 145.30 | 0.00 | 145.30 | 324.19 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 137.68 | 0.00 | 137.68 | 303.74 | 88.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.79 | 9.26 | 166.54 | 419.18 | 45.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.68 | 0.00 | 137.68 | 303.74 | 20.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 264.40 | 53.43 | 210.97 | 665.13 | 88.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 303.66 | 102.34 | 201.32 | 632.55 | 84.39 | 0.00 | 0.00 | 0.00 |
February | 344.35 | 126.25 | 218.09 | 736.47 | 60.49 | 0.00 | 0.00 | 0.00 |
March | 375.40 | 147.01 | 228.40 | 824.06 | 39.92 | 0.00 | 0.00 | 0.00 |
April | 379.40 | 144.95 | 234.45 | 853.28 | 16.49 | 0.00 | 0.00 | 0.00 |
May | 326.13 | 98.72 | 227.41 | 765.54 | 22.16 | 0.00 | 0.00 | 0.00 |
June | 347.36 | 114.40 | 232.96 | 805.93 | 23.19 | 0.00 | 0.00 | 0.00 |
July | 296.69 | 66.47 | 230.22 | 646.95 | 42.58 | 0.00 | 0.00 | 0.00 |
August | 326.51 | 95.98 | 230.53 | 700.61 | 32.83 | 0.00 | 0.00 | 0.00 |
September | 306.64 | 83.56 | 223.08 | 675.72 | 36.58 | 0.00 | 0.00 | 0.00 |
October | 287.39 | 73.52 | 213.86 | 603.58 | 44.49 | 0.00 | 0.00 | 0.00 |
November | 278.13 | 76.86 | 201.27 | 587.11 | 55.31 | 0.00 | 0.00 | 0.00 |
December | 284.62 | 91.34 | 193.28 | 591.67 | 88.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.10 | 101.55 | 219.55 | 701.36 | 45.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.13 | 66.47 | 193.28 | 587.11 | 16.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.40 | 147.01 | 234.45 | 853.28 | 88.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 303.66 | 102.34 | 201.32 | 632.55 | 84.39 | 0.00 | 0.00 | 0.00 |
February | 344.35 | 126.25 | 218.09 | 736.47 | 60.49 | 0.00 | 0.00 | 0.00 |
March | 375.40 | 147.01 | 228.40 | 824.06 | 39.92 | 0.00 | 0.00 | 0.00 |
April | 379.40 | 144.95 | 234.45 | 853.28 | 16.49 | 0.00 | 0.00 | 0.00 |
May | 326.13 | 98.72 | 227.41 | 765.54 | 22.16 | 0.00 | 0.00 | 0.00 |
June | 347.36 | 114.40 | 232.96 | 805.93 | 23.19 | 0.00 | 0.00 | 0.00 |
July | 296.69 | 66.47 | 230.22 | 646.95 | 42.58 | 0.00 | 0.00 | 0.00 |
August | 326.51 | 95.98 | 230.53 | 700.61 | 32.83 | 0.00 | 0.00 | 0.00 |
September | 306.64 | 83.56 | 223.08 | 675.72 | 36.58 | 0.00 | 0.00 | 0.00 |
October | 287.39 | 73.52 | 213.86 | 603.58 | 44.49 | 0.00 | 0.00 | 0.00 |
November | 278.13 | 76.86 | 201.27 | 587.11 | 55.31 | 0.00 | 0.00 | 0.00 |
December | 284.62 | 91.34 | 193.28 | 591.67 | 88.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.10 | 101.55 | 219.55 | 701.36 | 45.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.13 | 66.47 | 193.28 | 587.11 | 16.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.40 | 147.01 | 234.45 | 853.28 | 88.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 303.65 | 102.34 | 201.31 | 632.54 | 84.39 | 0.00 | 0.00 | 0.00 |
February | 344.34 | 126.25 | 218.09 | 736.45 | 60.49 | 0.00 | 0.00 | 0.00 |
March | 375.40 | 147.00 | 228.39 | 824.05 | 39.92 | 0.00 | 0.00 | 0.00 |
April | 379.39 | 144.94 | 234.45 | 853.27 | 16.49 | 0.00 | 0.00 | 0.00 |
May | 326.12 | 98.72 | 227.41 | 765.53 | 22.16 | 0.00 | 0.00 | 0.00 |
June | 347.35 | 114.40 | 232.95 | 805.91 | 23.19 | 0.00 | 0.00 | 0.00 |
July | 296.68 | 66.46 | 230.22 | 646.94 | 42.58 | 0.00 | 0.00 | 0.00 |
August | 326.51 | 95.98 | 230.53 | 700.59 | 32.83 | 0.00 | 0.00 | 0.00 |
September | 306.63 | 83.56 | 223.07 | 675.71 | 36.58 | 0.00 | 0.00 | 0.00 |
October | 287.38 | 73.52 | 213.86 | 603.57 | 44.49 | 0.00 | 0.00 | 0.00 |
November | 278.13 | 76.86 | 201.27 | 587.10 | 55.30 | 0.00 | 0.00 | 0.00 |
December | 284.62 | 91.34 | 193.28 | 591.66 | 88.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.09 | 101.55 | 219.54 | 701.35 | 45.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.13 | 66.46 | 193.28 | 587.10 | 16.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.39 | 147.00 | 234.45 | 853.27 | 88.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 375.25 | 156.56 | 218.69 | 788.33 | 86.06 | 0.00 | 0.00 | 0.00 |
February | 318.64 | 103.89 | 214.75 | 720.98 | 63.46 | 0.00 | 0.00 | 0.00 |
March | 217.46 | 29.20 | 188.25 | 543.93 | 41.49 | 0.00 | 0.00 | 0.00 |
April | 162.12 | 0.07 | 162.05 | 420.06 | 17.50 | 0.00 | 0.00 | 0.00 |
May | 162.23 | 0.00 | 162.23 | 437.85 | 19.31 | 0.00 | 0.00 | 0.00 |
June | 161.65 | 0.00 | 161.65 | 434.52 | 20.64 | 0.00 | 0.00 | 0.00 |
July | 166.52 | 0.00 | 166.52 | 386.05 | 40.59 | 0.00 | 0.00 | 0.00 |
August | 162.11 | 0.25 | 161.86 | 375.93 | 32.88 | 0.00 | 0.00 | 0.00 |
September | 179.47 | 5.86 | 173.61 | 429.54 | 33.61 | 0.00 | 0.00 | 0.00 |
October | 234.80 | 37.44 | 197.36 | 515.80 | 46.26 | 0.00 | 0.00 | 0.00 |
November | 305.32 | 93.15 | 212.17 | 651.69 | 60.03 | 0.00 | 0.00 | 0.00 |
December | 375.06 | 159.57 | 215.49 | 773.36 | 95.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.73 | 48.64 | 186.08 | 538.96 | 46.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.65 | 0.00 | 161.65 | 375.93 | 17.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.25 | 159.57 | 218.69 | 788.33 | 95.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 375.25 | 156.56 | 218.69 | 788.33 | 86.06 | 0.00 | 0.00 | 0.00 |
February | 318.64 | 103.89 | 214.75 | 720.98 | 63.46 | 0.00 | 0.00 | 0.00 |
March | 217.46 | 29.20 | 188.25 | 543.93 | 41.49 | 0.00 | 0.00 | 0.00 |
April | 162.12 | 0.07 | 162.05 | 420.06 | 17.50 | 0.00 | 0.00 | 0.00 |
May | 162.23 | 0.00 | 162.23 | 437.85 | 19.31 | 0.00 | 0.00 | 0.00 |
June | 161.65 | 0.00 | 161.65 | 434.52 | 20.64 | 0.00 | 0.00 | 0.00 |
July | 166.52 | 0.00 | 166.52 | 386.05 | 40.59 | 0.00 | 0.00 | 0.00 |
August | 162.11 | 0.25 | 161.86 | 375.93 | 32.88 | 0.00 | 0.00 | 0.00 |
September | 179.47 | 5.86 | 173.61 | 429.54 | 33.61 | 0.00 | 0.00 | 0.00 |
October | 234.80 | 37.44 | 197.36 | 515.80 | 46.26 | 0.00 | 0.00 | 0.00 |
November | 305.32 | 93.15 | 212.17 | 651.69 | 60.03 | 0.00 | 0.00 | 0.00 |
December | 375.06 | 159.57 | 215.48 | 773.35 | 95.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.73 | 48.64 | 186.08 | 538.96 | 46.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.65 | 0.00 | 161.65 | 375.93 | 17.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.25 | 159.57 | 218.69 | 788.33 | 95.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 375.25 | 156.56 | 218.69 | 788.33 | 86.06 | 0.00 | 0.00 | 0.00 |
February | 318.64 | 103.89 | 214.75 | 720.98 | 63.46 | 0.00 | 0.00 | 0.00 |
March | 217.46 | 29.20 | 188.25 | 543.93 | 41.49 | 0.00 | 0.00 | 0.00 |
April | 162.12 | 0.07 | 162.05 | 420.06 | 17.50 | 0.00 | 0.00 | 0.00 |
May | 162.23 | 0.00 | 162.23 | 437.85 | 19.31 | 0.00 | 0.00 | 0.00 |
June | 161.65 | 0.00 | 161.65 | 434.52 | 20.64 | 0.00 | 0.00 | 0.00 |
July | 166.52 | 0.00 | 166.52 | 386.05 | 40.59 | 0.00 | 0.00 | 0.00 |
August | 162.11 | 0.25 | 161.86 | 375.93 | 32.88 | 0.00 | 0.00 | 0.00 |
September | 179.47 | 5.86 | 173.61 | 429.54 | 33.61 | 0.00 | 0.00 | 0.00 |
October | 234.80 | 37.44 | 197.36 | 515.80 | 46.26 | 0.00 | 0.00 | 0.00 |
November | 305.32 | 93.15 | 212.17 | 651.69 | 60.03 | 0.00 | 0.00 | 0.00 |
December | 375.06 | 159.57 | 215.49 | 773.36 | 95.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.73 | 48.64 | 186.08 | 538.96 | 46.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.65 | 0.00 | 161.65 | 375.93 | 17.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.25 | 159.57 | 218.69 | 788.33 | 95.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 375.25 | 156.56 | 218.69 | 788.33 | 86.06 | 0.00 | 0.00 | 0.00 |
February | 318.64 | 103.89 | 214.75 | 720.98 | 63.46 | 0.00 | 0.00 | 0.00 |
March | 217.46 | 29.20 | 188.25 | 543.93 | 41.49 | 0.00 | 0.00 | 0.00 |
April | 162.12 | 0.07 | 162.05 | 420.06 | 17.50 | 0.00 | 0.00 | 0.00 |
May | 162.23 | 0.00 | 162.23 | 437.85 | 19.31 | 0.00 | 0.00 | 0.00 |
June | 161.65 | 0.00 | 161.65 | 434.52 | 20.64 | 0.00 | 0.00 | 0.00 |
July | 166.52 | 0.00 | 166.52 | 386.05 | 40.59 | 0.00 | 0.00 | 0.00 |
August | 162.11 | 0.25 | 161.86 | 375.93 | 32.88 | 0.00 | 0.00 | 0.00 |
September | 179.47 | 5.86 | 173.61 | 429.54 | 33.61 | 0.00 | 0.00 | 0.00 |
October | 234.80 | 37.44 | 197.36 | 515.80 | 46.26 | 0.00 | 0.00 | 0.00 |
November | 305.32 | 93.15 | 212.17 | 651.69 | 60.03 | 0.00 | 0.00 | 0.00 |
December | 375.06 | 159.57 | 215.48 | 773.35 | 95.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.73 | 48.64 | 186.08 | 538.96 | 46.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.65 | 0.00 | 161.65 | 375.93 | 17.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.25 | 159.57 | 218.69 | 788.33 | 95.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 375.23 | 156.55 | 218.68 | 788.30 | 86.06 | 0.00 | 0.00 | 0.00 |
February | 318.63 | 103.89 | 214.74 | 720.95 | 63.46 | 0.00 | 0.00 | 0.00 |
March | 217.45 | 29.20 | 188.24 | 543.91 | 41.49 | 0.00 | 0.00 | 0.00 |
April | 162.12 | 0.07 | 162.04 | 420.04 | 17.50 | 0.00 | 0.00 | 0.00 |
May | 162.23 | 0.00 | 162.23 | 437.83 | 19.31 | 0.00 | 0.00 | 0.00 |
June | 161.64 | 0.00 | 161.64 | 434.51 | 20.64 | 0.00 | 0.00 | 0.00 |
July | 166.52 | 0.00 | 166.52 | 386.04 | 40.59 | 0.00 | 0.00 | 0.00 |
August | 162.11 | 0.25 | 161.86 | 375.92 | 32.88 | 0.00 | 0.00 | 0.00 |
September | 179.46 | 5.86 | 173.60 | 429.52 | 33.61 | 0.00 | 0.00 | 0.00 |
October | 234.79 | 37.44 | 197.35 | 515.78 | 46.26 | 0.00 | 0.00 | 0.00 |
November | 305.30 | 93.14 | 212.16 | 651.66 | 60.02 | 0.00 | 0.00 | 0.00 |
December | 375.04 | 159.56 | 215.48 | 773.32 | 95.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.72 | 48.64 | 186.07 | 538.94 | 46.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.64 | 0.00 | 161.64 | 375.92 | 17.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.23 | 159.56 | 218.68 | 788.30 | 95.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.67 | 108.19 | 199.48 | 637.07 | 115.39 | 0.00 | 0.00 | 0.00 |
February | 337.91 | 119.58 | 218.33 | 713.42 | 98.55 | 0.00 | 0.00 | 0.00 |
March | 378.77 | 149.61 | 229.16 | 812.83 | 83.41 | 0.00 | 0.00 | 0.00 |
April | 380.65 | 145.79 | 234.85 | 813.61 | 59.85 | 0.00 | 0.00 | 0.00 |
May | 323.89 | 95.95 | 227.93 | 737.47 | 37.96 | 0.00 | 0.00 | 0.00 |
June | 350.97 | 120.97 | 230.00 | 784.27 | 46.90 | 0.00 | 0.00 | 0.00 |
July | 299.22 | 70.56 | 228.66 | 624.97 | 77.63 | 0.00 | 0.00 | 0.00 |
August | 325.31 | 96.34 | 228.97 | 659.80 | 79.04 | 0.00 | 0.00 | 0.00 |
September | 304.70 | 84.51 | 220.19 | 653.49 | 57.89 | 0.00 | 0.00 | 0.00 |
October | 286.18 | 73.77 | 212.41 | 580.18 | 77.38 | 0.00 | 0.00 | 0.00 |
November | 279.08 | 76.11 | 202.97 | 565.72 | 95.87 | 0.00 | 0.00 | 0.00 |
December | 285.62 | 93.43 | 192.19 | 575.03 | 147.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.45 | 102.72 | 218.73 | 679.28 | 81.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.08 | 70.56 | 192.19 | 565.72 | 37.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 380.65 | 149.61 | 234.85 | 813.61 | 147.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.67 | 108.19 | 199.48 | 637.07 | 115.39 | 0.00 | 0.00 | 0.00 |
February | 337.91 | 119.58 | 218.33 | 713.42 | 98.55 | 0.00 | 0.00 | 0.00 |
March | 378.77 | 149.61 | 229.16 | 812.83 | 83.41 | 0.00 | 0.00 | 0.00 |
April | 380.65 | 145.79 | 234.85 | 813.61 | 59.85 | 0.00 | 0.00 | 0.00 |
May | 323.89 | 95.95 | 227.93 | 737.47 | 37.96 | 0.00 | 0.00 | 0.00 |
June | 350.97 | 120.97 | 230.00 | 784.27 | 46.90 | 0.00 | 0.00 | 0.00 |
July | 299.22 | 70.56 | 228.66 | 624.97 | 77.63 | 0.00 | 0.00 | 0.00 |
August | 325.31 | 96.34 | 228.97 | 659.80 | 79.04 | 0.00 | 0.00 | 0.00 |
September | 304.70 | 84.51 | 220.19 | 653.49 | 57.89 | 0.00 | 0.00 | 0.00 |
October | 286.18 | 73.77 | 212.41 | 580.18 | 77.38 | 0.00 | 0.00 | 0.00 |
November | 279.08 | 76.11 | 202.97 | 565.72 | 95.87 | 0.00 | 0.00 | 0.00 |
December | 285.62 | 93.43 | 192.19 | 575.03 | 147.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.45 | 102.72 | 218.73 | 679.28 | 81.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.08 | 70.56 | 192.19 | 565.72 | 37.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 380.65 | 149.61 | 234.85 | 813.61 | 147.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.66 | 108.18 | 199.48 | 637.06 | 115.38 | 0.00 | 0.00 | 0.00 |
February | 337.90 | 119.58 | 218.33 | 713.40 | 98.55 | 0.00 | 0.00 | 0.00 |
March | 378.77 | 149.60 | 229.16 | 812.82 | 83.40 | 0.00 | 0.00 | 0.00 |
April | 380.64 | 145.79 | 234.85 | 813.60 | 59.85 | 0.00 | 0.00 | 0.00 |
May | 323.88 | 95.95 | 227.93 | 737.46 | 37.96 | 0.00 | 0.00 | 0.00 |
June | 350.97 | 120.97 | 230.00 | 784.25 | 46.90 | 0.00 | 0.00 | 0.00 |
July | 299.22 | 70.56 | 228.65 | 624.96 | 77.63 | 0.00 | 0.00 | 0.00 |
August | 325.31 | 96.34 | 228.97 | 659.79 | 79.04 | 0.00 | 0.00 | 0.00 |
September | 304.70 | 84.51 | 220.19 | 653.48 | 57.89 | 0.00 | 0.00 | 0.00 |
October | 286.17 | 73.77 | 212.40 | 580.17 | 77.38 | 0.00 | 0.00 | 0.00 |
November | 279.08 | 76.11 | 202.96 | 565.71 | 95.87 | 0.00 | 0.00 | 0.00 |
December | 285.61 | 93.43 | 192.18 | 575.02 | 147.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.45 | 102.72 | 218.73 | 679.27 | 81.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.08 | 70.56 | 192.18 | 565.71 | 37.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 380.64 | 149.60 | 234.85 | 813.60 | 147.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 708.64 | 0.00 | 708.64 | 1603.09 | 392.80 | 0.00 | 0.00 | 0.00 |
February | 755.92 | 0.00 | 755.92 | 1797.92 | 304.80 | 0.00 | 0.00 | 0.00 |
March | 775.81 | 0.00 | 775.81 | 1966.02 | 195.27 | 0.00 | 0.00 | 0.00 |
April | 844.29 | 11.97 | 832.32 | 2201.55 | 80.40 | 0.00 | 0.00 | 0.00 |
May | 1082.27 | 115.29 | 966.98 | 2791.72 | 116.50 | 0.00 | 0.00 | 0.00 |
June | 1322.04 | 267.17 | 1054.86 | 3314.22 | 139.31 | 0.00 | 0.00 | 0.00 |
July | 1136.83 | 119.16 | 1017.67 | 2599.92 | 229.34 | 0.00 | 0.00 | 0.00 |
August | 935.98 | 39.91 | 896.07 | 2178.38 | 171.89 | 0.00 | 0.00 | 0.00 |
September | 796.88 | 0.38 | 796.50 | 1921.23 | 164.79 | 0.00 | 0.00 | 0.00 |
October | 767.83 | 0.00 | 767.83 | 1710.01 | 212.36 | 0.00 | 0.00 | 0.00 |
November | 726.53 | 0.00 | 726.53 | 1631.57 | 267.68 | 0.00 | 0.00 | 0.00 |
December | 688.43 | 0.00 | 688.43 | 1539.52 | 434.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 878.98 | 46.28 | 832.70 | 2105.33 | 225.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.43 | 0.00 | 688.43 | 1539.52 | 80.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1322.04 | 267.17 | 1054.86 | 3314.22 | 434.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 910.96 | 307.02 | 603.94 | 1874.70 | 265.41 | 0.00 | 0.00 | 0.00 |
February | 1033.03 | 378.76 | 654.27 | 2181.47 | 206.08 | 0.00 | 0.00 | 0.00 |
March | 1126.20 | 441.01 | 685.18 | 2442.31 | 135.50 | 0.00 | 0.00 | 0.00 |
April | 1138.19 | 434.84 | 703.36 | 2532.28 | 59.23 | 0.00 | 0.00 | 0.00 |
May | 978.38 | 296.15 | 682.23 | 2267.67 | 78.22 | 0.00 | 0.00 | 0.00 |
June | 1042.06 | 343.20 | 698.86 | 2385.95 | 88.28 | 0.00 | 0.00 | 0.00 |
July | 890.06 | 199.40 | 690.66 | 1912.45 | 150.75 | 0.00 | 0.00 | 0.00 |
August | 979.53 | 287.94 | 691.59 | 2073.69 | 120.63 | 0.00 | 0.00 | 0.00 |
September | 919.90 | 250.68 | 669.22 | 2001.16 | 123.81 | 0.00 | 0.00 | 0.00 |
October | 862.15 | 220.57 | 641.58 | 1782.10 | 154.93 | 0.00 | 0.00 | 0.00 |
November | 834.39 | 230.58 | 603.81 | 1732.93 | 191.94 | 0.00 | 0.00 | 0.00 |
December | 853.86 | 274.01 | 579.85 | 1747.45 | 296.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.28 | 304.64 | 658.64 | 2076.06 | 155.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 834.39 | 199.40 | 579.85 | 1732.93 | 59.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1138.19 | 441.01 | 703.36 | 2532.28 | 296.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1876.22 | 782.78 | 1093.44 | 3908.18 | 445.12 | 0.00 | 0.00 | 0.00 |
February | 1593.19 | 519.44 | 1073.75 | 3582.81 | 336.89 | 0.00 | 0.00 | 0.00 |
March | 1087.26 | 146.02 | 941.24 | 2726.88 | 202.57 | 0.00 | 0.00 | 0.00 |
April | 810.61 | 0.36 | 810.24 | 2147.27 | 68.92 | 0.00 | 0.00 | 0.00 |
May | 811.16 | 0.00 | 811.16 | 2200.29 | 99.69 | 0.00 | 0.00 | 0.00 |
June | 808.24 | 0.00 | 808.24 | 2189.23 | 107.37 | 0.00 | 0.00 | 0.00 |
July | 832.61 | 0.00 | 832.61 | 1940.98 | 203.18 | 0.00 | 0.00 | 0.00 |
August | 810.55 | 1.25 | 809.30 | 1904.01 | 152.42 | 0.00 | 0.00 | 0.00 |
September | 897.34 | 29.31 | 868.03 | 2147.04 | 169.79 | 0.00 | 0.00 | 0.00 |
October | 1173.98 | 187.18 | 986.80 | 2566.75 | 241.88 | 0.00 | 0.00 | 0.00 |
November | 1526.56 | 465.73 | 1060.83 | 3241.09 | 316.47 | 0.00 | 0.00 | 0.00 |
December | 1875.26 | 797.85 | 1077.41 | 3845.26 | 497.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1173.62 | 243.22 | 930.40 | 2695.67 | 236.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 808.24 | 0.00 | 808.24 | 1904.01 | 68.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1876.22 | 797.85 | 1093.44 | 3908.18 | 497.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 923.00 | 324.56 | 598.44 | 1925.54 | 316.31 | 0.00 | 0.00 | 0.00 |
February | 1013.72 | 358.73 | 654.99 | 2163.56 | 257.39 | 0.00 | 0.00 | 0.00 |
March | 1136.30 | 448.82 | 687.49 | 2475.89 | 193.66 | 0.00 | 0.00 | 0.00 |
April | 1141.92 | 437.37 | 704.55 | 2514.98 | 101.37 | 0.00 | 0.00 | 0.00 |
May | 971.65 | 287.86 | 683.80 | 2231.67 | 92.38 | 0.00 | 0.00 | 0.00 |
June | 1052.91 | 362.91 | 689.99 | 2385.04 | 106.58 | 0.00 | 0.00 | 0.00 |
July | 897.66 | 211.69 | 685.97 | 1915.99 | 177.51 | 0.00 | 0.00 | 0.00 |
August | 975.93 | 289.02 | 686.92 | 2044.75 | 147.79 | 0.00 | 0.00 | 0.00 |
September | 914.10 | 253.53 | 660.57 | 1975.64 | 146.09 | 0.00 | 0.00 | 0.00 |
October | 858.52 | 221.31 | 637.21 | 1768.19 | 186.19 | 0.00 | 0.00 | 0.00 |
November | 837.23 | 228.34 | 608.89 | 1738.40 | 225.89 | 0.00 | 0.00 | 0.00 |
December | 856.84 | 280.29 | 576.55 | 1777.76 | 351.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 964.35 | 308.16 | 656.19 | 2074.89 | 191.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 837.23 | 211.69 | 576.55 | 1738.40 | 92.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1141.92 | 448.82 | 704.55 | 2514.98 | 351.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 708.64 | 0.00 | 708.64 | 1581.06 | 399.91 | 0.00 | 0.00 | 0.00 |
February | 755.92 | 0.00 | 755.92 | 1772.46 | 314.26 | 0.00 | 0.00 | 0.00 |
March | 775.81 | 0.00 | 775.81 | 1937.71 | 208.72 | 0.00 | 0.00 | 0.00 |
April | 844.29 | 11.97 | 832.32 | 2163.89 | 92.46 | 0.00 | 0.00 | 0.00 |
May | 1082.27 | 115.29 | 966.98 | 2754.19 | 125.55 | 0.00 | 0.00 | 0.00 |
June | 1322.04 | 267.17 | 1054.86 | 3280.37 | 151.14 | 0.00 | 0.00 | 0.00 |
July | 1136.83 | 119.16 | 1017.67 | 2566.85 | 242.09 | 0.00 | 0.00 | 0.00 |
August | 935.98 | 39.91 | 896.07 | 2151.24 | 181.93 | 0.00 | 0.00 | 0.00 |
September | 796.88 | 0.38 | 796.50 | 1890.18 | 178.90 | 0.00 | 0.00 | 0.00 |
October | 767.83 | 0.00 | 767.83 | 1683.51 | 224.98 | 0.00 | 0.00 | 0.00 |
November | 726.53 | 0.00 | 726.53 | 1606.47 | 277.95 | 0.00 | 0.00 | 0.00 |
December | 688.43 | 0.00 | 688.43 | 1518.81 | 440.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 878.98 | 46.28 | 832.70 | 2076.30 | 236.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.43 | 0.00 | 688.43 | 1518.81 | 92.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1322.04 | 267.17 | 1054.86 | 3280.37 | 440.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 910.96 | 307.02 | 603.94 | 1866.92 | 267.99 | 0.00 | 0.00 | 0.00 |
February | 1033.03 | 378.76 | 654.27 | 2170.80 | 209.76 | 0.00 | 0.00 | 0.00 |
March | 1126.20 | 441.01 | 685.18 | 2428.88 | 141.49 | 0.00 | 0.00 | 0.00 |
April | 1138.19 | 434.84 | 703.36 | 2514.59 | 65.54 | 0.00 | 0.00 | 0.00 |
May | 978.38 | 296.15 | 682.23 | 2250.36 | 83.02 | 0.00 | 0.00 | 0.00 |
June | 1042.06 | 343.20 | 698.86 | 2371.66 | 95.43 | 0.00 | 0.00 | 0.00 |
July | 890.06 | 199.40 | 690.66 | 1899.05 | 158.45 | 0.00 | 0.00 | 0.00 |
August | 979.53 | 287.94 | 691.59 | 2063.56 | 126.18 | 0.00 | 0.00 | 0.00 |
September | 919.90 | 250.68 | 669.22 | 1988.74 | 131.43 | 0.00 | 0.00 | 0.00 |
October | 862.15 | 220.57 | 641.58 | 1771.57 | 161.47 | 0.00 | 0.00 | 0.00 |
November | 834.39 | 230.58 | 603.81 | 1723.22 | 196.65 | 0.00 | 0.00 | 0.00 |
December | 853.86 | 274.01 | 579.85 | 1740.16 | 297.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.28 | 304.64 | 658.64 | 2064.01 | 161.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 834.39 | 199.40 | 579.85 | 1723.22 | 65.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1138.19 | 441.01 | 703.36 | 2514.59 | 297.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1876.22 | 782.78 | 1093.44 | 3889.93 | 448.02 | 0.00 | 0.00 | 0.00 |
February | 1593.19 | 519.44 | 1073.75 | 3558.84 | 342.70 | 0.00 | 0.00 | 0.00 |
March | 1087.26 | 146.02 | 941.24 | 2696.41 | 213.38 | 0.00 | 0.00 | 0.00 |
April | 810.61 | 0.36 | 810.24 | 2107.73 | 78.92 | 0.00 | 0.00 | 0.00 |
May | 811.16 | 0.00 | 811.16 | 2160.52 | 107.36 | 0.00 | 0.00 | 0.00 |
June | 808.24 | 0.00 | 808.24 | 2153.46 | 117.92 | 0.00 | 0.00 | 0.00 |
July | 832.61 | 0.00 | 832.61 | 1908.10 | 217.19 | 0.00 | 0.00 | 0.00 |
August | 810.55 | 1.25 | 809.30 | 1875.79 | 162.27 | 0.00 | 0.00 | 0.00 |
September | 897.34 | 29.31 | 868.03 | 2115.13 | 183.39 | 0.00 | 0.00 | 0.00 |
October | 1173.98 | 187.18 | 986.80 | 2538.63 | 252.85 | 0.00 | 0.00 | 0.00 |
November | 1526.56 | 465.73 | 1060.83 | 3216.72 | 323.72 | 0.00 | 0.00 | 0.00 |
December | 1875.26 | 797.85 | 1077.41 | 3827.52 | 499.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1173.62 | 243.22 | 930.40 | 2666.42 | 245.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 808.24 | 0.00 | 808.24 | 1875.79 | 78.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1876.22 | 797.85 | 1093.44 | 3889.93 | 499.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 923.00 | 324.56 | 598.44 | 1910.39 | 318.85 | 0.00 | 0.00 | 0.00 |
February | 1013.72 | 358.73 | 654.99 | 2145.92 | 261.42 | 0.00 | 0.00 | 0.00 |
March | 1136.30 | 448.82 | 687.49 | 2456.12 | 199.67 | 0.00 | 0.00 | 0.00 |
April | 1141.92 | 437.37 | 704.55 | 2492.09 | 108.32 | 0.00 | 0.00 | 0.00 |
May | 971.65 | 287.86 | 683.80 | 2208.19 | 97.87 | 0.00 | 0.00 | 0.00 |
June | 1052.91 | 362.91 | 689.99 | 2362.07 | 113.18 | 0.00 | 0.00 | 0.00 |
July | 897.66 | 211.69 | 685.97 | 1894.56 | 184.12 | 0.00 | 0.00 | 0.00 |
August | 975.93 | 289.02 | 686.92 | 2025.08 | 152.92 | 0.00 | 0.00 | 0.00 |
September | 914.10 | 253.53 | 660.57 | 1954.57 | 153.09 | 0.00 | 0.00 | 0.00 |
October | 858.52 | 221.31 | 637.21 | 1750.30 | 192.14 | 0.00 | 0.00 | 0.00 |
November | 837.23 | 228.34 | 608.89 | 1721.62 | 230.20 | 0.00 | 0.00 | 0.00 |
December | 856.84 | 280.29 | 576.55 | 1763.24 | 352.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 964.35 | 308.16 | 656.19 | 2055.45 | 197.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 837.23 | 211.69 | 576.55 | 1721.62 | 97.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1141.92 | 448.82 | 704.55 | 2492.09 | 352.88 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.379608E+09 | 0.00 | 0.379608E+09 | 0.853529E+09 | 0.212954E+09 |
February | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.865120E+09 | 0.142751E+09 |
March | 0.415590E+09 | 0.00 | 0.415590E+09 | 0.104197E+10 | 0.109065E+09 |
April | 0.437683E+09 | 6202790.48 | 0.431480E+09 | 0.112095E+10 | 52565193.62 |
May | 0.579759E+09 | 61761782.36 | 0.517998E+09 | 0.149965E+10 | 58730946.09 |
June | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 64999058.40 |
July | 0.608982E+09 | 63832181.51 | 0.545150E+09 | 0.139552E+10 | 0.118742E+09 |
August | 0.501391E+09 | 21379683.24 | 0.480011E+09 | 0.115747E+10 | 97146464.49 |
September | 0.413109E+09 | 197818.84 | 0.412911E+09 | 0.994038E+09 | 85297628.04 |
October | 0.411315E+09 | 0.00 | 0.411315E+09 | 0.913693E+09 | 0.112785E+09 |
November | 0.376640E+09 | 0.00 | 0.376640E+09 | 0.840336E+09 | 0.138654E+09 |
December | 0.368784E+09 | 0.00 | 0.368784E+09 | 0.813558E+09 | 0.236084E+09 |
Annual Sum or Average | 0.554396E+10 | 0.291878E+09 | 0.525208E+10 | 0.132199E+11 | 0.142977E+10 |
Minimum of Months | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.813558E+09 | 52565193.62 |
Maximum of Months | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 0.236084E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.379608E+09 | 0.00 | 0.379608E+09 | 0.853528E+09 | 0.212954E+09 |
February | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.865120E+09 | 0.142750E+09 |
March | 0.415590E+09 | 0.00 | 0.415590E+09 | 0.104197E+10 | 0.109065E+09 |
April | 0.437683E+09 | 6202783.04 | 0.431480E+09 | 0.112095E+10 | 52565104.86 |
May | 0.579759E+09 | 61761708.25 | 0.517997E+09 | 0.149965E+10 | 58730884.24 |
June | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 64998996.08 |
July | 0.608981E+09 | 63832104.92 | 0.545149E+09 | 0.139552E+10 | 0.118742E+09 |
August | 0.501390E+09 | 21379657.58 | 0.480010E+09 | 0.115747E+10 | 97146374.02 |
September | 0.413109E+09 | 197818.60 | 0.412911E+09 | 0.994038E+09 | 85297553.23 |
October | 0.411315E+09 | 0.00 | 0.411315E+09 | 0.913693E+09 | 0.112785E+09 |
November | 0.376639E+09 | 0.00 | 0.376639E+09 | 0.840335E+09 | 0.138654E+09 |
December | 0.368784E+09 | 0.00 | 0.368784E+09 | 0.813558E+09 | 0.236084E+09 |
Annual Sum or Average | 0.554396E+10 | 0.291878E+09 | 0.525208E+10 | 0.132199E+11 | 0.142977E+10 |
Minimum of Months | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.813558E+09 | 52565104.86 |
Maximum of Months | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 0.236084E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.379608E+09 | 0.00 | 0.379608E+09 | 0.853529E+09 | 0.212954E+09 |
February | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.865120E+09 | 0.142751E+09 |
March | 0.415590E+09 | 0.00 | 0.415590E+09 | 0.104197E+10 | 0.109065E+09 |
April | 0.437683E+09 | 6202790.48 | 0.431480E+09 | 0.112095E+10 | 52565193.62 |
May | 0.579759E+09 | 61761782.36 | 0.517998E+09 | 0.149965E+10 | 58730946.09 |
June | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 64999058.40 |
July | 0.608982E+09 | 63832181.51 | 0.545150E+09 | 0.139552E+10 | 0.118742E+09 |
August | 0.501391E+09 | 21379683.24 | 0.480011E+09 | 0.115747E+10 | 97146464.49 |
September | 0.413109E+09 | 197818.84 | 0.412911E+09 | 0.994038E+09 | 85297628.04 |
October | 0.411315E+09 | 0.00 | 0.411315E+09 | 0.913693E+09 | 0.112785E+09 |
November | 0.376640E+09 | 0.00 | 0.376640E+09 | 0.840336E+09 | 0.138654E+09 |
December | 0.368784E+09 | 0.00 | 0.368784E+09 | 0.813558E+09 | 0.236084E+09 |
Annual Sum or Average | 0.554396E+10 | 0.291878E+09 | 0.525208E+10 | 0.132199E+11 | 0.142977E+10 |
Minimum of Months | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.813558E+09 | 52565193.62 |
Maximum of Months | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 0.236084E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.379608E+09 | 0.00 | 0.379608E+09 | 0.853528E+09 | 0.212954E+09 |
February | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.865120E+09 | 0.142750E+09 |
March | 0.415590E+09 | 0.00 | 0.415590E+09 | 0.104197E+10 | 0.109065E+09 |
April | 0.437683E+09 | 6202783.04 | 0.431480E+09 | 0.112095E+10 | 52565104.86 |
May | 0.579759E+09 | 61761708.25 | 0.517997E+09 | 0.149965E+10 | 58730884.24 |
June | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 64998996.08 |
July | 0.608981E+09 | 63832104.92 | 0.545149E+09 | 0.139552E+10 | 0.118742E+09 |
August | 0.501390E+09 | 21379657.58 | 0.480010E+09 | 0.115747E+10 | 97146374.02 |
September | 0.413109E+09 | 197818.60 | 0.412911E+09 | 0.994038E+09 | 85297553.23 |
October | 0.411315E+09 | 0.00 | 0.411315E+09 | 0.913693E+09 | 0.112785E+09 |
November | 0.376639E+09 | 0.00 | 0.376639E+09 | 0.840335E+09 | 0.138654E+09 |
December | 0.368784E+09 | 0.00 | 0.368784E+09 | 0.813558E+09 | 0.236084E+09 |
Annual Sum or Average | 0.554396E+10 | 0.291878E+09 | 0.525208E+10 | 0.132199E+11 | 0.142977E+10 |
Minimum of Months | 0.365750E+09 | 0.00 | 0.365750E+09 | 0.813558E+09 | 52565104.86 |
Maximum of Months | 0.685351E+09 | 0.138504E+09 | 0.546847E+09 | 0.172410E+10 | 0.236084E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.379593E+09 | 0.00 | 0.379593E+09 | 0.853494E+09 | 0.212946E+09 |
February | 0.365736E+09 | 0.00 | 0.365736E+09 | 0.865085E+09 | 0.142745E+09 |
March | 0.415573E+09 | 0.00 | 0.415573E+09 | 0.104193E+10 | 0.109060E+09 |
April | 0.437666E+09 | 6202540.48 | 0.431463E+09 | 0.112091E+10 | 52563075.02 |
May | 0.579736E+09 | 61759293.09 | 0.517977E+09 | 0.149959E+10 | 58728578.97 |
June | 0.685324E+09 | 0.138498E+09 | 0.546825E+09 | 0.172403E+10 | 64996438.65 |
July | 0.608957E+09 | 63829608.80 | 0.545128E+09 | 0.139546E+10 | 0.118737E+09 |
August | 0.501370E+09 | 21378821.54 | 0.479992E+09 | 0.115743E+10 | 97142549.06 |
September | 0.413092E+09 | 197810.87 | 0.412894E+09 | 0.993998E+09 | 85294190.17 |
October | 0.411298E+09 | 0.00 | 0.411298E+09 | 0.913656E+09 | 0.112780E+09 |
November | 0.376625E+09 | 0.00 | 0.376625E+09 | 0.840302E+09 | 0.138649E+09 |
December | 0.368770E+09 | 0.00 | 0.368770E+09 | 0.813525E+09 | 0.236074E+09 |
Annual Sum or Average | 0.554374E+10 | 0.291866E+09 | 0.525187E+10 | 0.132194E+11 | 0.142972E+10 |
Minimum of Months | 0.365736E+09 | 0.00 | 0.365736E+09 | 0.813525E+09 | 52563075.02 |
Maximum of Months | 0.685324E+09 | 0.138498E+09 | 0.546825E+09 | 0.172403E+10 | 0.236074E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.813317E+09 | 0.274111E+09 | 0.539206E+09 | 0.169421E+10 | 0.226026E+09 |
February | 0.833043E+09 | 0.305435E+09 | 0.527608E+09 | 0.178166E+10 | 0.146336E+09 |
March | 0.100548E+10 | 0.393741E+09 | 0.611738E+09 | 0.220717E+10 | 0.106918E+09 |
April | 0.983409E+09 | 0.375704E+09 | 0.607706E+09 | 0.221171E+10 | 42737522.41 |
May | 0.873505E+09 | 0.264409E+09 | 0.609097E+09 | 0.205042E+10 | 59362864.99 |
June | 0.900346E+09 | 0.296526E+09 | 0.603820E+09 | 0.208897E+10 | 60097084.06 |
July | 0.794653E+09 | 0.178022E+09 | 0.616631E+09 | 0.173280E+10 | 0.114045E+09 |
August | 0.874531E+09 | 0.257075E+09 | 0.617456E+09 | 0.187651E+10 | 87929953.09 |
September | 0.794799E+09 | 0.216586E+09 | 0.578213E+09 | 0.175148E+10 | 94815411.65 |
October | 0.769734E+09 | 0.196925E+09 | 0.572808E+09 | 0.161663E+10 | 0.119157E+09 |
November | 0.720917E+09 | 0.199222E+09 | 0.521694E+09 | 0.152180E+10 | 0.143352E+09 |
December | 0.762334E+09 | 0.244640E+09 | 0.517694E+09 | 0.158473E+10 | 0.236158E+09 |
Annual Sum or Average | 0.101261E+11 | 0.320240E+10 | 0.692367E+10 | 0.221181E+11 | 0.143693E+10 |
Minimum of Months | 0.720917E+09 | 0.178022E+09 | 0.517694E+09 | 0.152180E+10 | 42737522.41 |
Maximum of Months | 0.100548E+10 | 0.393741E+09 | 0.617456E+09 | 0.221171E+10 | 0.236158E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.813317E+09 | 0.274111E+09 | 0.539206E+09 | 0.169421E+10 | 0.226026E+09 |
February | 0.833043E+09 | 0.305435E+09 | 0.527608E+09 | 0.178166E+10 | 0.146336E+09 |
March | 0.100548E+10 | 0.393741E+09 | 0.611738E+09 | 0.220717E+10 | 0.106918E+09 |
April | 0.983409E+09 | 0.375704E+09 | 0.607706E+09 | 0.221171E+10 | 42737522.41 |
May | 0.873505E+09 | 0.264409E+09 | 0.609097E+09 | 0.205042E+10 | 59362864.99 |
June | 0.900346E+09 | 0.296526E+09 | 0.603820E+09 | 0.208897E+10 | 60097084.06 |
July | 0.794653E+09 | 0.178022E+09 | 0.616631E+09 | 0.173280E+10 | 0.114045E+09 |
August | 0.874531E+09 | 0.257075E+09 | 0.617456E+09 | 0.187651E+10 | 87929953.09 |
September | 0.794799E+09 | 0.216586E+09 | 0.578213E+09 | 0.175148E+10 | 94815411.65 |
October | 0.769734E+09 | 0.196925E+09 | 0.572808E+09 | 0.161663E+10 | 0.119157E+09 |
November | 0.720917E+09 | 0.199222E+09 | 0.521694E+09 | 0.152180E+10 | 0.143352E+09 |
December | 0.762334E+09 | 0.244640E+09 | 0.517694E+09 | 0.158473E+10 | 0.236158E+09 |
Annual Sum or Average | 0.101261E+11 | 0.320240E+10 | 0.692367E+10 | 0.221181E+11 | 0.143693E+10 |
Minimum of Months | 0.720917E+09 | 0.178022E+09 | 0.517694E+09 | 0.152180E+10 | 42737522.41 |
Maximum of Months | 0.100548E+10 | 0.393741E+09 | 0.617456E+09 | 0.221171E+10 | 0.236158E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.813302E+09 | 0.274106E+09 | 0.539196E+09 | 0.169418E+10 | 0.226022E+09 |
February | 0.833027E+09 | 0.305429E+09 | 0.527598E+09 | 0.178163E+10 | 0.146333E+09 |
March | 0.100546E+10 | 0.393734E+09 | 0.611727E+09 | 0.220713E+10 | 0.106916E+09 |
April | 0.983392E+09 | 0.375697E+09 | 0.607695E+09 | 0.221167E+10 | 42736741.50 |
May | 0.873489E+09 | 0.264404E+09 | 0.609086E+09 | 0.205038E+10 | 59361780.30 |
June | 0.900329E+09 | 0.296521E+09 | 0.603808E+09 | 0.208893E+10 | 60095985.96 |
July | 0.794639E+09 | 0.178019E+09 | 0.616620E+09 | 0.173276E+10 | 0.114042E+09 |
August | 0.874515E+09 | 0.257070E+09 | 0.617445E+09 | 0.187647E+10 | 87928346.41 |
September | 0.794784E+09 | 0.216582E+09 | 0.578202E+09 | 0.175145E+10 | 94813679.17 |
October | 0.769720E+09 | 0.196922E+09 | 0.572798E+09 | 0.161660E+10 | 0.119154E+09 |
November | 0.720904E+09 | 0.199219E+09 | 0.521685E+09 | 0.152177E+10 | 0.143349E+09 |
December | 0.762320E+09 | 0.244636E+09 | 0.517684E+09 | 0.158470E+10 | 0.236154E+09 |
Annual Sum or Average | 0.101259E+11 | 0.320234E+10 | 0.692354E+10 | 0.221177E+11 | 0.143691E+10 |
Minimum of Months | 0.720904E+09 | 0.178019E+09 | 0.517684E+09 | 0.152177E+10 | 42736741.50 |
Maximum of Months | 0.100546E+10 | 0.393734E+09 | 0.617445E+09 | 0.221167E+10 | 0.236154E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100507E+10 | 0.419325E+09 | 0.585740E+09 | 0.211146E+10 | 0.230502E+09 |
February | 0.770860E+09 | 0.251329E+09 | 0.519530E+09 | 0.174420E+10 | 0.153526E+09 |
March | 0.582432E+09 | 78221056.82 | 0.504211E+09 | 0.145687E+10 | 0.111135E+09 |
April | 0.420224E+09 | 188641.62 | 0.420035E+09 | 0.108879E+10 | 45351742.10 |
May | 0.434528E+09 | 0.00 | 0.434528E+09 | 0.117274E+10 | 51709429.01 |
June | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.112628E+10 | 53490300.16 |
July | 0.446018E+09 | 0.00 | 0.446018E+09 | 0.103401E+10 | 0.108713E+09 |
August | 0.434202E+09 | 671067.61 | 0.433530E+09 | 0.100690E+10 | 88066854.86 |
September | 0.465186E+09 | 15193314.60 | 0.449993E+09 | 0.111336E+10 | 87121627.29 |
October | 0.628886E+09 | 0.100271E+09 | 0.528615E+09 | 0.138152E+10 | 0.123912E+09 |
November | 0.791379E+09 | 0.241439E+09 | 0.549940E+09 | 0.168918E+10 | 0.155590E+09 |
December | 0.100455E+10 | 0.427395E+09 | 0.577156E+09 | 0.207135E+10 | 0.256325E+09 |
Annual Sum or Average | 0.740233E+10 | 0.153403E+10 | 0.586829E+10 | 0.169967E+11 | 0.146544E+10 |
Minimum of Months | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.100690E+10 | 45351742.10 |
Maximum of Months | 0.100507E+10 | 0.427395E+09 | 0.585740E+09 | 0.211146E+10 | 0.256325E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100506E+10 | 0.419324E+09 | 0.585740E+09 | 0.211146E+10 | 0.230501E+09 |
February | 0.770859E+09 | 0.251329E+09 | 0.519530E+09 | 0.174420E+10 | 0.153526E+09 |
March | 0.582432E+09 | 78220962.97 | 0.504211E+09 | 0.145687E+10 | 0.111135E+09 |
April | 0.420223E+09 | 188641.40 | 0.420035E+09 | 0.108879E+10 | 45351665.11 |
May | 0.434527E+09 | 0.00 | 0.434527E+09 | 0.117274E+10 | 51709376.76 |
June | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.112628E+10 | 53490252.10 |
July | 0.446017E+09 | 0.00 | 0.446017E+09 | 0.103401E+10 | 0.108712E+09 |
August | 0.434201E+09 | 671066.81 | 0.433530E+09 | 0.100690E+10 | 88066772.96 |
September | 0.465186E+09 | 15193296.37 | 0.449992E+09 | 0.111336E+10 | 87121552.48 |
October | 0.628885E+09 | 0.100271E+09 | 0.528614E+09 | 0.138152E+10 | 0.123912E+09 |
November | 0.791378E+09 | 0.241439E+09 | 0.549939E+09 | 0.168918E+10 | 0.155590E+09 |
December | 0.100455E+10 | 0.427395E+09 | 0.577155E+09 | 0.207135E+10 | 0.256325E+09 |
Annual Sum or Average | 0.740232E+10 | 0.153403E+10 | 0.586829E+10 | 0.169966E+11 | 0.146544E+10 |
Minimum of Months | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.100690E+10 | 45351665.11 |
Maximum of Months | 0.100506E+10 | 0.427395E+09 | 0.585740E+09 | 0.211146E+10 | 0.256325E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100507E+10 | 0.419325E+09 | 0.585740E+09 | 0.211146E+10 | 0.230502E+09 |
February | 0.770860E+09 | 0.251329E+09 | 0.519530E+09 | 0.174420E+10 | 0.153526E+09 |
March | 0.582432E+09 | 78221056.82 | 0.504211E+09 | 0.145687E+10 | 0.111135E+09 |
April | 0.420224E+09 | 188641.62 | 0.420035E+09 | 0.108879E+10 | 45351742.10 |
May | 0.434528E+09 | 0.00 | 0.434528E+09 | 0.117274E+10 | 51709429.01 |
June | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.112628E+10 | 53490300.16 |
July | 0.446018E+09 | 0.00 | 0.446018E+09 | 0.103401E+10 | 0.108713E+09 |
August | 0.434202E+09 | 671067.61 | 0.433530E+09 | 0.100690E+10 | 88066854.86 |
September | 0.465186E+09 | 15193314.60 | 0.449993E+09 | 0.111336E+10 | 87121627.29 |
October | 0.628886E+09 | 0.100271E+09 | 0.528615E+09 | 0.138152E+10 | 0.123912E+09 |
November | 0.791379E+09 | 0.241439E+09 | 0.549940E+09 | 0.168918E+10 | 0.155590E+09 |
December | 0.100455E+10 | 0.427395E+09 | 0.577156E+09 | 0.207135E+10 | 0.256325E+09 |
Annual Sum or Average | 0.740233E+10 | 0.153403E+10 | 0.586829E+10 | 0.169967E+11 | 0.146544E+10 |
Minimum of Months | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.100690E+10 | 45351742.10 |
Maximum of Months | 0.100507E+10 | 0.427395E+09 | 0.585740E+09 | 0.211146E+10 | 0.256325E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100506E+10 | 0.419324E+09 | 0.585740E+09 | 0.211146E+10 | 0.230501E+09 |
February | 0.770859E+09 | 0.251329E+09 | 0.519530E+09 | 0.174420E+10 | 0.153526E+09 |
March | 0.582432E+09 | 78220962.97 | 0.504211E+09 | 0.145687E+10 | 0.111135E+09 |
April | 0.420223E+09 | 188641.40 | 0.420035E+09 | 0.108879E+10 | 45351665.11 |
May | 0.434527E+09 | 0.00 | 0.434527E+09 | 0.117274E+10 | 51709376.76 |
June | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.112628E+10 | 53490252.10 |
July | 0.446017E+09 | 0.00 | 0.446017E+09 | 0.103401E+10 | 0.108712E+09 |
August | 0.434201E+09 | 671066.81 | 0.433530E+09 | 0.100690E+10 | 88066772.96 |
September | 0.465186E+09 | 15193296.37 | 0.449992E+09 | 0.111336E+10 | 87121552.48 |
October | 0.628885E+09 | 0.100271E+09 | 0.528614E+09 | 0.138152E+10 | 0.123912E+09 |
November | 0.791378E+09 | 0.241439E+09 | 0.549939E+09 | 0.168918E+10 | 0.155590E+09 |
December | 0.100455E+10 | 0.427395E+09 | 0.577155E+09 | 0.207135E+10 | 0.256325E+09 |
Annual Sum or Average | 0.740232E+10 | 0.153403E+10 | 0.586829E+10 | 0.169966E+11 | 0.146544E+10 |
Minimum of Months | 0.418997E+09 | 0.00 | 0.418997E+09 | 0.100690E+10 | 45351665.11 |
Maximum of Months | 0.100506E+10 | 0.427395E+09 | 0.585740E+09 | 0.211146E+10 | 0.256325E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100502E+10 | 0.419308E+09 | 0.585717E+09 | 0.211138E+10 | 0.230492E+09 |
February | 0.770829E+09 | 0.251319E+09 | 0.519509E+09 | 0.174413E+10 | 0.153520E+09 |
March | 0.582409E+09 | 78217904.17 | 0.504191E+09 | 0.145681E+10 | 0.111131E+09 |
April | 0.420207E+09 | 188634.02 | 0.420018E+09 | 0.108875E+10 | 45349914.22 |
May | 0.434510E+09 | 0.00 | 0.434510E+09 | 0.117269E+10 | 51707344.89 |
June | 0.418980E+09 | 0.00 | 0.418980E+09 | 0.112624E+10 | 53488144.26 |
July | 0.446000E+09 | 0.00 | 0.446000E+09 | 0.103396E+10 | 0.108708E+09 |
August | 0.434184E+09 | 671040.57 | 0.433513E+09 | 0.100686E+10 | 88063305.38 |
September | 0.465167E+09 | 15192702.24 | 0.449974E+09 | 0.111331E+10 | 87118115.91 |
October | 0.628860E+09 | 0.100267E+09 | 0.528593E+09 | 0.138146E+10 | 0.123907E+09 |
November | 0.791347E+09 | 0.241429E+09 | 0.549918E+09 | 0.168911E+10 | 0.155584E+09 |
December | 0.100451E+10 | 0.427378E+09 | 0.577132E+09 | 0.207127E+10 | 0.256315E+09 |
Annual Sum or Average | 0.740203E+10 | 0.153397E+10 | 0.586806E+10 | 0.169960E+11 | 0.146538E+10 |
Minimum of Months | 0.418980E+09 | 0.00 | 0.418980E+09 | 0.100686E+10 | 45349914.22 |
Maximum of Months | 0.100502E+10 | 0.427378E+09 | 0.585717E+09 | 0.211138E+10 | 0.256315E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.824064E+09 | 0.289767E+09 | 0.534296E+09 | 0.170633E+10 | 0.309048E+09 |
February | 0.817472E+09 | 0.289284E+09 | 0.528188E+09 | 0.172590E+10 | 0.238410E+09 |
March | 0.101450E+10 | 0.400709E+09 | 0.613794E+09 | 0.217708E+10 | 0.223396E+09 |
April | 0.986632E+09 | 0.377895E+09 | 0.608737E+09 | 0.210889E+10 | 0.155144E+09 |
May | 0.867499E+09 | 0.257000E+09 | 0.610499E+09 | 0.197525E+10 | 0.101672E+09 |
June | 0.909720E+09 | 0.313559E+09 | 0.596161E+09 | 0.203282E+10 | 0.121559E+09 |
July | 0.801436E+09 | 0.188997E+09 | 0.612439E+09 | 0.167392E+10 | 0.207935E+09 |
August | 0.871321E+09 | 0.258036E+09 | 0.613285E+09 | 0.176721E+10 | 0.211703E+09 |
September | 0.789794E+09 | 0.219054E+09 | 0.570740E+09 | 0.169385E+10 | 0.150051E+09 |
October | 0.766497E+09 | 0.197586E+09 | 0.568911E+09 | 0.155396E+10 | 0.207262E+09 |
November | 0.723377E+09 | 0.197287E+09 | 0.526090E+09 | 0.146636E+10 | 0.248501E+09 |
December | 0.764997E+09 | 0.250244E+09 | 0.514753E+09 | 0.154017E+10 | 0.396308E+09 |
Annual Sum or Average | 0.101373E+11 | 0.323942E+10 | 0.689789E+10 | 0.214217E+11 | 0.257099E+10 |
Minimum of Months | 0.723377E+09 | 0.188997E+09 | 0.514753E+09 | 0.146636E+10 | 0.101672E+09 |
Maximum of Months | 0.101450E+10 | 0.400709E+09 | 0.613794E+09 | 0.217708E+10 | 0.396308E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.824064E+09 | 0.289767E+09 | 0.534296E+09 | 0.170633E+10 | 0.309048E+09 |
February | 0.817472E+09 | 0.289284E+09 | 0.528188E+09 | 0.172590E+10 | 0.238410E+09 |
March | 0.101450E+10 | 0.400709E+09 | 0.613794E+09 | 0.217708E+10 | 0.223396E+09 |
April | 0.986632E+09 | 0.377895E+09 | 0.608737E+09 | 0.210889E+10 | 0.155144E+09 |
May | 0.867499E+09 | 0.257000E+09 | 0.610499E+09 | 0.197525E+10 | 0.101672E+09 |
June | 0.909720E+09 | 0.313559E+09 | 0.596161E+09 | 0.203282E+10 | 0.121559E+09 |
July | 0.801436E+09 | 0.188997E+09 | 0.612439E+09 | 0.167392E+10 | 0.207935E+09 |
August | 0.871321E+09 | 0.258036E+09 | 0.613285E+09 | 0.176721E+10 | 0.211703E+09 |
September | 0.789794E+09 | 0.219054E+09 | 0.570740E+09 | 0.169385E+10 | 0.150051E+09 |
October | 0.766497E+09 | 0.197586E+09 | 0.568911E+09 | 0.155396E+10 | 0.207262E+09 |
November | 0.723377E+09 | 0.197287E+09 | 0.526090E+09 | 0.146636E+10 | 0.248501E+09 |
December | 0.764997E+09 | 0.250244E+09 | 0.514753E+09 | 0.154017E+10 | 0.396308E+09 |
Annual Sum or Average | 0.101373E+11 | 0.323942E+10 | 0.689789E+10 | 0.214217E+11 | 0.257099E+10 |
Minimum of Months | 0.723377E+09 | 0.188997E+09 | 0.514753E+09 | 0.146636E+10 | 0.101672E+09 |
Maximum of Months | 0.101450E+10 | 0.400709E+09 | 0.613794E+09 | 0.217708E+10 | 0.396308E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.824049E+09 | 0.289762E+09 | 0.534286E+09 | 0.170629E+10 | 0.309042E+09 |
February | 0.817458E+09 | 0.289279E+09 | 0.528178E+09 | 0.172587E+10 | 0.238406E+09 |
March | 0.101448E+10 | 0.400702E+09 | 0.613783E+09 | 0.217704E+10 | 0.223392E+09 |
April | 0.986614E+09 | 0.377888E+09 | 0.608726E+09 | 0.210885E+10 | 0.155141E+09 |
May | 0.867483E+09 | 0.256995E+09 | 0.610488E+09 | 0.197521E+10 | 0.101670E+09 |
June | 0.909703E+09 | 0.313553E+09 | 0.596150E+09 | 0.203278E+10 | 0.121557E+09 |
July | 0.801421E+09 | 0.188994E+09 | 0.612427E+09 | 0.167389E+10 | 0.207931E+09 |
August | 0.871305E+09 | 0.258031E+09 | 0.613274E+09 | 0.176717E+10 | 0.211699E+09 |
September | 0.789779E+09 | 0.219050E+09 | 0.570729E+09 | 0.169382E+10 | 0.150048E+09 |
October | 0.766483E+09 | 0.197583E+09 | 0.568900E+09 | 0.155393E+10 | 0.207258E+09 |
November | 0.723364E+09 | 0.197283E+09 | 0.526080E+09 | 0.146633E+10 | 0.248497E+09 |
December | 0.764983E+09 | 0.250240E+09 | 0.514743E+09 | 0.154014E+10 | 0.396301E+09 |
Annual Sum or Average | 0.101371E+11 | 0.323936E+10 | 0.689777E+10 | 0.214213E+11 | 0.257094E+10 |
Minimum of Months | 0.723364E+09 | 0.188994E+09 | 0.514743E+09 | 0.146633E+10 | 0.101670E+09 |
Maximum of Months | 0.101448E+10 | 0.400702E+09 | 0.613783E+09 | 0.217704E+10 | 0.396301E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189802E+10 | 0.00 | 0.189802E+10 | 0.429370E+10 | 0.105206E+10 |
February | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.434953E+10 | 0.737361E+09 |
March | 0.207793E+10 | 0.00 | 0.207793E+10 | 0.526579E+10 | 0.523016E+09 |
April | 0.218839E+10 | 31013577.40 | 0.215738E+10 | 0.570642E+10 | 0.208399E+09 |
May | 0.289876E+10 | 0.308805E+09 | 0.258996E+10 | 0.747735E+10 | 0.312047E+09 |
June | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.859045E+10 | 0.361097E+09 |
July | 0.304487E+10 | 0.319157E+09 | 0.272572E+10 | 0.696362E+10 | 0.614265E+09 |
August | 0.250692E+10 | 0.106897E+09 | 0.240003E+10 | 0.583456E+10 | 0.460389E+09 |
September | 0.206552E+10 | 989082.24 | 0.206453E+10 | 0.497983E+10 | 0.427141E+09 |
October | 0.205655E+10 | 0.00 | 0.205655E+10 | 0.458008E+10 | 0.568786E+09 |
November | 0.188318E+10 | 0.00 | 0.188318E+10 | 0.422902E+10 | 0.693822E+09 |
December | 0.184390E+10 | 0.00 | 0.184390E+10 | 0.412345E+10 | 0.116390E+10 |
Annual Sum or Average | 0.277195E+11 | 0.145937E+10 | 0.262601E+11 | 0.663938E+11 | 0.712229E+10 |
Minimum of Months | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.412345E+10 | 0.208399E+09 |
Maximum of Months | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.859045E+10 | 0.116390E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.243992E+10 | 0.822325E+09 | 0.161760E+10 | 0.502119E+10 | 0.710865E+09 |
February | 0.249910E+10 | 0.916294E+09 | 0.158281E+10 | 0.527742E+10 | 0.498555E+09 |
March | 0.301641E+10 | 0.118121E+10 | 0.183520E+10 | 0.654148E+10 | 0.362926E+09 |
April | 0.295020E+10 | 0.112710E+10 | 0.182310E+10 | 0.656366E+10 | 0.153526E+09 |
May | 0.262049E+10 | 0.793218E+09 | 0.182727E+10 | 0.607374E+10 | 0.209504E+09 |
June | 0.270101E+10 | 0.889570E+09 | 0.181144E+10 | 0.618439E+10 | 0.228826E+09 |
July | 0.238394E+10 | 0.534060E+09 | 0.184988E+10 | 0.512230E+10 | 0.403759E+09 |
August | 0.262357E+10 | 0.771217E+09 | 0.185235E+10 | 0.555418E+10 | 0.323097E+09 |
September | 0.238437E+10 | 0.649752E+09 | 0.173462E+10 | 0.518701E+10 | 0.320924E+09 |
October | 0.230918E+10 | 0.590770E+09 | 0.171841E+10 | 0.477317E+10 | 0.414966E+09 |
November | 0.216273E+10 | 0.597661E+09 | 0.156507E+10 | 0.449176E+10 | 0.497501E+09 |
December | 0.228698E+10 | 0.733913E+09 | 0.155306E+10 | 0.468038E+10 | 0.792984E+09 |
Annual Sum or Average | 0.303779E+11 | 0.960709E+10 | 0.207708E+11 | 0.654707E+11 | 0.491743E+10 |
Minimum of Months | 0.216273E+10 | 0.534060E+09 | 0.155306E+10 | 0.449176E+10 | 0.153526E+09 |
Maximum of Months | 0.301641E+10 | 0.118121E+10 | 0.185235E+10 | 0.656366E+10 | 0.792984E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.502526E+10 | 0.209660E+10 | 0.292867E+10 | 0.104677E+11 | 0.119221E+10 |
February | 0.385425E+10 | 0.125663E+10 | 0.259762E+10 | 0.866753E+10 | 0.815005E+09 |
March | 0.291213E+10 | 0.391101E+09 | 0.252102E+10 | 0.730368E+10 | 0.542570E+09 |
April | 0.210109E+10 | 943196.70 | 0.210015E+10 | 0.556573E+10 | 0.178647E+09 |
May | 0.217261E+10 | 0.00 | 0.217261E+10 | 0.589327E+10 | 0.267019E+09 |
June | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.567449E+10 | 0.278312E+09 |
July | 0.223006E+10 | 0.00 | 0.223006E+10 | 0.519871E+10 | 0.544188E+09 |
August | 0.217098E+10 | 3355297.50 | 0.216763E+10 | 0.509970E+10 | 0.408241E+09 |
September | 0.232590E+10 | 75965654.42 | 0.224994E+10 | 0.556513E+10 | 0.440095E+09 |
October | 0.314439E+10 | 0.501348E+09 | 0.264304E+10 | 0.687478E+10 | 0.647863E+09 |
November | 0.395685E+10 | 0.120718E+10 | 0.274967E+10 | 0.840091E+10 | 0.820282E+09 |
December | 0.502269E+10 | 0.213695E+10 | 0.288574E+10 | 0.102992E+11 | 0.133267E+10 |
Annual Sum or Average | 0.370112E+11 | 0.767007E+10 | 0.293411E+11 | 0.850107E+11 | 0.746710E+10 |
Minimum of Months | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.509970E+10 | 0.178647E+09 |
Maximum of Months | 0.502526E+10 | 0.213695E+10 | 0.292867E+10 | 0.104677E+11 | 0.133267E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247217E+10 | 0.869293E+09 | 0.160287E+10 | 0.515736E+10 | 0.847217E+09 |
February | 0.245239E+10 | 0.867845E+09 | 0.158455E+10 | 0.523409E+10 | 0.622672E+09 |
March | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.663144E+10 | 0.518698E+09 |
April | 0.295987E+10 | 0.113367E+10 | 0.182619E+10 | 0.651882E+10 | 0.262740E+09 |
May | 0.260247E+10 | 0.770992E+09 | 0.183148E+10 | 0.597730E+10 | 0.247424E+09 |
June | 0.272913E+10 | 0.940668E+09 | 0.178846E+10 | 0.618203E+10 | 0.276252E+09 |
July | 0.240428E+10 | 0.566985E+09 | 0.183730E+10 | 0.513178E+10 | 0.475440E+09 |
August | 0.261394E+10 | 0.774100E+09 | 0.183984E+10 | 0.547665E+10 | 0.395829E+09 |
September | 0.236936E+10 | 0.657155E+09 | 0.171220E+10 | 0.512087E+10 | 0.378654E+09 |
October | 0.229947E+10 | 0.592753E+09 | 0.170671E+10 | 0.473593E+10 | 0.498698E+09 |
November | 0.217011E+10 | 0.591854E+09 | 0.157825E+10 | 0.450593E+10 | 0.585494E+09 |
December | 0.229497E+10 | 0.750726E+09 | 0.154424E+10 | 0.476155E+10 | 0.941498E+09 |
Annual Sum or Average | 0.304116E+11 | 0.971816E+10 | 0.206935E+11 | 0.654337E+11 | 0.605062E+10 |
Minimum of Months | 0.217011E+10 | 0.566985E+09 | 0.154424E+10 | 0.450593E+10 | 0.247424E+09 |
Maximum of Months | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.663144E+10 | 0.941498E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189802E+10 | 0.00 | 0.189802E+10 | 0.423472E+10 | 0.107113E+10 |
February | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.428793E+10 | 0.760264E+09 |
March | 0.207793E+10 | 0.00 | 0.207793E+10 | 0.518995E+10 | 0.559025E+09 |
April | 0.218839E+10 | 31013577.40 | 0.215738E+10 | 0.560881E+10 | 0.239655E+09 |
May | 0.289876E+10 | 0.308805E+09 | 0.258996E+10 | 0.737683E+10 | 0.336278E+09 |
June | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.850271E+10 | 0.391748E+09 |
July | 0.304487E+10 | 0.319157E+09 | 0.272572E+10 | 0.687504E+10 | 0.648412E+09 |
August | 0.250692E+10 | 0.106897E+09 | 0.240003E+10 | 0.576187E+10 | 0.487279E+09 |
September | 0.206552E+10 | 989082.24 | 0.206453E+10 | 0.489936E+10 | 0.463716E+09 |
October | 0.205655E+10 | 0.00 | 0.205655E+10 | 0.450911E+10 | 0.602579E+09 |
November | 0.188318E+10 | 0.00 | 0.188318E+10 | 0.416397E+10 | 0.720449E+09 |
December | 0.184390E+10 | 0.00 | 0.184390E+10 | 0.406798E+10 | 0.117906E+10 |
Annual Sum or Average | 0.277195E+11 | 0.145937E+10 | 0.262601E+11 | 0.654783E+11 | 0.745959E+10 |
Minimum of Months | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.406798E+10 | 0.239655E+09 |
Maximum of Months | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.850271E+10 | 0.117906E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.243992E+10 | 0.822325E+09 | 0.161760E+10 | 0.500037E+10 | 0.717779E+09 |
February | 0.249910E+10 | 0.916294E+09 | 0.158281E+10 | 0.525160E+10 | 0.507449E+09 |
March | 0.301641E+10 | 0.118121E+10 | 0.183520E+10 | 0.650551E+10 | 0.378959E+09 |
April | 0.295020E+10 | 0.112710E+10 | 0.182310E+10 | 0.651781E+10 | 0.169887E+09 |
May | 0.262049E+10 | 0.793218E+09 | 0.182727E+10 | 0.602738E+10 | 0.222360E+09 |
June | 0.270101E+10 | 0.889570E+09 | 0.181144E+10 | 0.614734E+10 | 0.247353E+09 |
July | 0.238394E+10 | 0.534060E+09 | 0.184988E+10 | 0.508643E+10 | 0.424390E+09 |
August | 0.262357E+10 | 0.771217E+09 | 0.185235E+10 | 0.552703E+10 | 0.337948E+09 |
September | 0.238437E+10 | 0.649752E+09 | 0.173462E+10 | 0.515483E+10 | 0.340671E+09 |
October | 0.230918E+10 | 0.590770E+09 | 0.171841E+10 | 0.474497E+10 | 0.432488E+09 |
November | 0.216273E+10 | 0.597661E+09 | 0.156507E+10 | 0.446657E+10 | 0.509728E+09 |
December | 0.228698E+10 | 0.733913E+09 | 0.155306E+10 | 0.466084E+10 | 0.797563E+09 |
Annual Sum or Average | 0.303779E+11 | 0.960709E+10 | 0.207708E+11 | 0.650907E+11 | 0.508657E+10 |
Minimum of Months | 0.216273E+10 | 0.534060E+09 | 0.155306E+10 | 0.446657E+10 | 0.169887E+09 |
Maximum of Months | 0.301641E+10 | 0.118121E+10 | 0.185235E+10 | 0.651781E+10 | 0.797563E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.502526E+10 | 0.209660E+10 | 0.292867E+10 | 0.104188E+11 | 0.119999E+10 |
February | 0.385425E+10 | 0.125663E+10 | 0.259762E+10 | 0.860955E+10 | 0.829058E+09 |
March | 0.291213E+10 | 0.391101E+09 | 0.252102E+10 | 0.722206E+10 | 0.571515E+09 |
April | 0.210109E+10 | 943196.70 | 0.210015E+10 | 0.546324E+10 | 0.204561E+09 |
May | 0.217261E+10 | 0.00 | 0.217261E+10 | 0.578674E+10 | 0.287541E+09 |
June | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.558178E+10 | 0.305640E+09 |
July | 0.223006E+10 | 0.00 | 0.223006E+10 | 0.511064E+10 | 0.581733E+09 |
August | 0.217098E+10 | 3355297.50 | 0.216763E+10 | 0.502411E+10 | 0.434611E+09 |
September | 0.232590E+10 | 75965654.42 | 0.224994E+10 | 0.548241E+10 | 0.475338E+09 |
October | 0.314439E+10 | 0.501348E+09 | 0.264304E+10 | 0.679945E+10 | 0.677245E+09 |
November | 0.395685E+10 | 0.120718E+10 | 0.274967E+10 | 0.833774E+10 | 0.839090E+09 |
December | 0.502269E+10 | 0.213695E+10 | 0.288574E+10 | 0.102516E+11 | 0.133709E+10 |
Annual Sum or Average | 0.370112E+11 | 0.767007E+10 | 0.293411E+11 | 0.840881E+11 | 0.774341E+10 |
Minimum of Months | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.502411E+10 | 0.204561E+09 |
Maximum of Months | 0.502526E+10 | 0.213695E+10 | 0.292867E+10 | 0.104188E+11 | 0.133709E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247217E+10 | 0.869293E+09 | 0.160287E+10 | 0.511678E+10 | 0.854006E+09 |
February | 0.245239E+10 | 0.867845E+09 | 0.158455E+10 | 0.519142E+10 | 0.632418E+09 |
March | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.657847E+10 | 0.534801E+09 |
April | 0.295987E+10 | 0.113367E+10 | 0.182619E+10 | 0.645949E+10 | 0.280762E+09 |
May | 0.260247E+10 | 0.770992E+09 | 0.183148E+10 | 0.591441E+10 | 0.262129E+09 |
June | 0.272913E+10 | 0.940668E+09 | 0.178846E+10 | 0.612249E+10 | 0.293353E+09 |
July | 0.240428E+10 | 0.566985E+09 | 0.183730E+10 | 0.507439E+10 | 0.493141E+09 |
August | 0.261394E+10 | 0.774100E+09 | 0.183984E+10 | 0.542397E+10 | 0.409585E+09 |
September | 0.236936E+10 | 0.657155E+09 | 0.171220E+10 | 0.506625E+10 | 0.396802E+09 |
October | 0.229947E+10 | 0.592753E+09 | 0.170671E+10 | 0.468800E+10 | 0.514637E+09 |
November | 0.217011E+10 | 0.591854E+09 | 0.157825E+10 | 0.446243E+10 | 0.596674E+09 |
December | 0.229497E+10 | 0.750726E+09 | 0.154424E+10 | 0.472265E+10 | 0.945167E+09 |
Annual Sum or Average | 0.304116E+11 | 0.971816E+10 | 0.206935E+11 | 0.648208E+11 | 0.621347E+10 |
Minimum of Months | 0.217011E+10 | 0.566985E+09 | 0.154424E+10 | 0.446243E+10 | 0.262129E+09 |
Maximum of Months | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.657847E+10 | 0.945167E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1593.34 | 397.54 | 708.64 | 0.00 | 708.64 | 0.00 | 0.00 |
February | 1788.01 | 295.03 | 755.93 | 0.00 | 755.93 | 0.00 | 0.00 |
March | 1945.11 | 203.60 | 775.81 | 0.00 | 775.81 | 0.00 | 0.00 |
April | 2162.32 | 101.40 | 844.29 | 11.97 | 832.32 | 0.00 | 0.00 |
May | 2799.50 | 109.64 | 1082.28 | 115.30 | 966.98 | 0.00 | 0.00 |
June | 3325.78 | 125.38 | 1322.04 | 267.17 | 1054.87 | 0.00 | 0.00 |
July | 2605.11 | 221.66 | 1136.83 | 119.16 | 1017.67 | 0.00 | 0.00 |
August | 2160.74 | 181.35 | 935.98 | 39.91 | 896.07 | 0.00 | 0.00 |
September | 1917.50 | 164.54 | 796.89 | 0.38 | 796.50 | 0.00 | 0.00 |
October | 1705.66 | 210.54 | 767.83 | 0.00 | 767.83 | 0.00 | 0.00 |
November | 1621.00 | 267.46 | 726.54 | 0.00 | 726.54 | 0.00 | 0.00 |
December | 1518.73 | 440.71 | 688.44 | 0.00 | 688.44 | 0.00 | 0.00 |
Annual Sum or Average | 2095.99 | 226.69 | 878.98 | 46.28 | 832.71 | 0.00 | 0.00 |
Minimum of Months | 1518.73 | 101.40 | 688.44 | 0.00 | 688.44 | 0.00 | 0.00 |
Maximum of Months | 3325.78 | 440.71 | 1322.04 | 267.17 | 1054.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1897.63 | 253.16 | 910.97 | 307.02 | 603.95 | 0.00 | 0.00 |
February | 2209.39 | 181.47 | 1033.03 | 378.76 | 654.27 | 0.00 | 0.00 |
March | 2472.17 | 119.75 | 1126.20 | 441.02 | 685.19 | 0.00 | 0.00 |
April | 2559.84 | 49.46 | 1138.20 | 434.84 | 703.36 | 0.00 | 0.00 |
May | 2296.61 | 66.49 | 978.38 | 296.15 | 682.23 | 0.00 | 0.00 |
June | 2417.77 | 69.56 | 1042.06 | 343.20 | 698.86 | 0.00 | 0.00 |
July | 1940.84 | 127.74 | 890.06 | 199.40 | 690.67 | 0.00 | 0.00 |
August | 2101.81 | 98.49 | 979.53 | 287.94 | 691.59 | 0.00 | 0.00 |
September | 2027.16 | 109.74 | 919.90 | 250.68 | 669.22 | 0.00 | 0.00 |
October | 1810.73 | 133.46 | 862.15 | 220.57 | 641.58 | 0.00 | 0.00 |
November | 1761.33 | 165.92 | 834.39 | 230.58 | 603.81 | 0.00 | 0.00 |
December | 1775.00 | 264.51 | 853.86 | 274.01 | 579.85 | 0.00 | 0.00 |
Annual Sum or Average | 2104.07 | 136.69 | 963.28 | 304.64 | 658.64 | 0.00 | 0.00 |
Minimum of Months | 1761.33 | 49.46 | 834.39 | 199.40 | 579.85 | 0.00 | 0.00 |
Maximum of Months | 2559.84 | 264.51 | 1138.20 | 441.02 | 703.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3941.61 | 430.29 | 1876.23 | 782.78 | 1093.44 | 0.00 | 0.00 |
February | 3604.87 | 317.30 | 1593.20 | 519.44 | 1073.76 | 0.00 | 0.00 |
March | 2719.65 | 207.46 | 1087.27 | 146.02 | 941.25 | 0.00 | 0.00 |
April | 2100.28 | 87.48 | 810.61 | 0.36 | 810.25 | 0.00 | 0.00 |
May | 2189.23 | 96.53 | 811.16 | 0.00 | 811.16 | 0.00 | 0.00 |
June | 2172.60 | 103.18 | 808.24 | 0.00 | 808.24 | 0.00 | 0.00 |
July | 1930.25 | 202.94 | 832.61 | 0.00 | 832.61 | 0.00 | 0.00 |
August | 1879.66 | 164.40 | 810.55 | 1.25 | 809.30 | 0.00 | 0.00 |
September | 2147.66 | 168.06 | 897.34 | 29.31 | 868.03 | 0.00 | 0.00 |
October | 2578.98 | 231.32 | 1173.99 | 187.18 | 986.80 | 0.00 | 0.00 |
November | 3258.42 | 300.13 | 1526.57 | 465.74 | 1060.83 | 0.00 | 0.00 |
December | 3866.74 | 478.50 | 1875.27 | 797.85 | 1077.42 | 0.00 | 0.00 |
Annual Sum or Average | 2694.78 | 232.34 | 1173.62 | 243.22 | 930.40 | 0.00 | 0.00 |
Minimum of Months | 1879.66 | 87.48 | 808.24 | 0.00 | 808.24 | 0.00 | 0.00 |
Maximum of Months | 3941.61 | 478.50 | 1876.23 | 797.85 | 1093.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1911.20 | 346.15 | 923.00 | 324.56 | 598.45 | 0.00 | 0.00 |
February | 2140.24 | 295.65 | 1013.72 | 358.73 | 654.99 | 0.00 | 0.00 |
March | 2438.47 | 250.22 | 1136.31 | 448.82 | 687.49 | 0.00 | 0.00 |
April | 2440.83 | 179.56 | 1141.93 | 437.38 | 704.55 | 0.00 | 0.00 |
May | 2212.41 | 113.88 | 971.66 | 287.86 | 683.80 | 0.00 | 0.00 |
June | 2352.78 | 140.69 | 1052.91 | 362.91 | 690.00 | 0.00 | 0.00 |
July | 1874.90 | 232.90 | 897.66 | 211.69 | 685.97 | 0.00 | 0.00 |
August | 1979.39 | 237.12 | 975.94 | 289.02 | 686.92 | 0.00 | 0.00 |
September | 1960.46 | 173.67 | 914.11 | 253.53 | 660.57 | 0.00 | 0.00 |
October | 1740.53 | 232.15 | 858.53 | 221.31 | 637.22 | 0.00 | 0.00 |
November | 1697.16 | 287.62 | 837.24 | 228.34 | 608.90 | 0.00 | 0.00 |
December | 1725.09 | 443.89 | 856.85 | 280.29 | 576.56 | 0.00 | 0.00 |
Annual Sum or Average | 2037.82 | 244.58 | 964.35 | 308.16 | 656.19 | 0.00 | 0.00 |
Minimum of Months | 1697.16 | 113.88 | 837.24 | 211.69 | 576.56 | 0.00 | 0.00 |
Maximum of Months | 2440.83 | 443.89 | 1141.93 | 448.82 | 704.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1603.09 | 392.80 | 708.64 | 0.00 | 708.64 | 0.00 | 0.00 |
February | 1797.92 | 304.80 | 755.92 | 0.00 | 755.92 | 0.00 | 0.00 |
March | 1966.02 | 195.27 | 775.81 | 0.00 | 775.81 | 0.00 | 0.00 |
April | 2201.55 | 80.40 | 844.29 | 11.97 | 832.32 | 0.00 | 0.00 |
May | 2791.72 | 116.50 | 1082.27 | 115.29 | 966.98 | 0.00 | 0.00 |
June | 3314.22 | 139.31 | 1322.04 | 267.17 | 1054.86 | 0.00 | 0.00 |
July | 2599.92 | 229.34 | 1136.83 | 119.16 | 1017.67 | 0.00 | 0.00 |
August | 2178.38 | 171.89 | 935.98 | 39.91 | 896.07 | 0.00 | 0.00 |
September | 1921.23 | 164.79 | 796.88 | 0.38 | 796.50 | 0.00 | 0.00 |
October | 1710.01 | 212.36 | 767.83 | 0.00 | 767.83 | 0.00 | 0.00 |
November | 1631.57 | 267.68 | 726.53 | 0.00 | 726.53 | 0.00 | 0.00 |
December | 1539.52 | 434.55 | 688.43 | 0.00 | 688.43 | 0.00 | 0.00 |
Annual Sum or Average | 2105.33 | 225.85 | 878.98 | 46.28 | 832.70 | 0.00 | 0.00 |
Minimum of Months | 1539.52 | 80.40 | 688.43 | 0.00 | 688.43 | 0.00 | 0.00 |
Maximum of Months | 3314.22 | 434.55 | 1322.04 | 267.17 | 1054.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1874.70 | 265.41 | 910.96 | 307.02 | 603.94 | 0.00 | 0.00 |
February | 2181.47 | 206.08 | 1033.03 | 378.76 | 654.27 | 0.00 | 0.00 |
March | 2442.31 | 135.50 | 1126.20 | 441.01 | 685.18 | 0.00 | 0.00 |
April | 2532.28 | 59.23 | 1138.19 | 434.84 | 703.36 | 0.00 | 0.00 |
May | 2267.67 | 78.22 | 978.38 | 296.15 | 682.23 | 0.00 | 0.00 |
June | 2385.95 | 88.28 | 1042.06 | 343.20 | 698.86 | 0.00 | 0.00 |
July | 1912.45 | 150.75 | 890.06 | 199.40 | 690.66 | 0.00 | 0.00 |
August | 2073.69 | 120.63 | 979.53 | 287.94 | 691.59 | 0.00 | 0.00 |
September | 2001.16 | 123.81 | 919.90 | 250.68 | 669.22 | 0.00 | 0.00 |
October | 1782.10 | 154.93 | 862.15 | 220.57 | 641.58 | 0.00 | 0.00 |
November | 1732.93 | 191.94 | 834.39 | 230.58 | 603.81 | 0.00 | 0.00 |
December | 1747.45 | 296.07 | 853.86 | 274.01 | 579.85 | 0.00 | 0.00 |
Annual Sum or Average | 2076.06 | 155.93 | 963.28 | 304.64 | 658.64 | 0.00 | 0.00 |
Minimum of Months | 1732.93 | 59.23 | 834.39 | 199.40 | 579.85 | 0.00 | 0.00 |
Maximum of Months | 2532.28 | 296.07 | 1138.19 | 441.01 | 703.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3908.18 | 445.12 | 1876.22 | 782.78 | 1093.44 | 0.00 | 0.00 |
February | 3582.81 | 336.89 | 1593.19 | 519.44 | 1073.75 | 0.00 | 0.00 |
March | 2726.88 | 202.57 | 1087.26 | 146.02 | 941.24 | 0.00 | 0.00 |
April | 2147.27 | 68.92 | 810.61 | 0.36 | 810.24 | 0.00 | 0.00 |
May | 2200.29 | 99.69 | 811.16 | 0.00 | 811.16 | 0.00 | 0.00 |
June | 2189.23 | 107.37 | 808.24 | 0.00 | 808.24 | 0.00 | 0.00 |
July | 1940.98 | 203.18 | 832.61 | 0.00 | 832.61 | 0.00 | 0.00 |
August | 1904.01 | 152.42 | 810.55 | 1.25 | 809.30 | 0.00 | 0.00 |
September | 2147.04 | 169.79 | 897.34 | 29.31 | 868.03 | 0.00 | 0.00 |
October | 2566.75 | 241.88 | 1173.98 | 187.18 | 986.80 | 0.00 | 0.00 |
November | 3241.09 | 316.47 | 1526.56 | 465.73 | 1060.83 | 0.00 | 0.00 |
December | 3845.26 | 497.56 | 1875.26 | 797.85 | 1077.41 | 0.00 | 0.00 |
Annual Sum or Average | 2695.67 | 236.78 | 1173.62 | 243.22 | 930.40 | 0.00 | 0.00 |
Minimum of Months | 1904.01 | 68.92 | 808.24 | 0.00 | 808.24 | 0.00 | 0.00 |
Maximum of Months | 3908.18 | 497.56 | 1876.22 | 797.85 | 1093.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1925.54 | 316.31 | 923.00 | 324.56 | 598.44 | 0.00 | 0.00 |
February | 2163.56 | 257.39 | 1013.72 | 358.73 | 654.99 | 0.00 | 0.00 |
March | 2475.89 | 193.66 | 1136.30 | 448.82 | 687.49 | 0.00 | 0.00 |
April | 2514.98 | 101.37 | 1141.92 | 437.37 | 704.55 | 0.00 | 0.00 |
May | 2231.67 | 92.38 | 971.65 | 287.86 | 683.80 | 0.00 | 0.00 |
June | 2385.04 | 106.58 | 1052.91 | 362.91 | 689.99 | 0.00 | 0.00 |
July | 1915.99 | 177.51 | 897.66 | 211.69 | 685.97 | 0.00 | 0.00 |
August | 2044.75 | 147.79 | 975.93 | 289.02 | 686.92 | 0.00 | 0.00 |
September | 1975.64 | 146.09 | 914.10 | 253.53 | 660.57 | 0.00 | 0.00 |
October | 1768.19 | 186.19 | 858.52 | 221.31 | 637.21 | 0.00 | 0.00 |
November | 1738.40 | 225.89 | 837.23 | 228.34 | 608.89 | 0.00 | 0.00 |
December | 1777.76 | 351.51 | 856.84 | 280.29 | 576.55 | 0.00 | 0.00 |
Annual Sum or Average | 2074.89 | 191.86 | 964.35 | 308.16 | 656.19 | 0.00 | 0.00 |
Minimum of Months | 1738.40 | 92.38 | 837.23 | 211.69 | 576.55 | 0.00 | 0.00 |
Maximum of Months | 2514.98 | 351.51 | 1141.92 | 448.82 | 704.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1581.06 | 399.91 | 708.64 | 0.00 | 708.64 | 0.00 | 0.00 |
February | 1772.46 | 314.26 | 755.92 | 0.00 | 755.92 | 0.00 | 0.00 |
March | 1937.71 | 208.72 | 775.81 | 0.00 | 775.81 | 0.00 | 0.00 |
April | 2163.89 | 92.46 | 844.29 | 11.97 | 832.32 | 0.00 | 0.00 |
May | 2754.19 | 125.55 | 1082.27 | 115.29 | 966.98 | 0.00 | 0.00 |
June | 3280.37 | 151.14 | 1322.04 | 267.17 | 1054.86 | 0.00 | 0.00 |
July | 2566.85 | 242.09 | 1136.83 | 119.16 | 1017.67 | 0.00 | 0.00 |
August | 2151.24 | 181.93 | 935.98 | 39.91 | 896.07 | 0.00 | 0.00 |
September | 1890.18 | 178.90 | 796.88 | 0.38 | 796.50 | 0.00 | 0.00 |
October | 1683.51 | 224.98 | 767.83 | 0.00 | 767.83 | 0.00 | 0.00 |
November | 1606.47 | 277.95 | 726.53 | 0.00 | 726.53 | 0.00 | 0.00 |
December | 1518.81 | 440.21 | 688.43 | 0.00 | 688.43 | 0.00 | 0.00 |
Annual Sum or Average | 2076.30 | 236.54 | 878.98 | 46.28 | 832.70 | 0.00 | 0.00 |
Minimum of Months | 1518.81 | 92.46 | 688.43 | 0.00 | 688.43 | 0.00 | 0.00 |
Maximum of Months | 3280.37 | 440.21 | 1322.04 | 267.17 | 1054.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1866.92 | 267.99 | 910.96 | 307.02 | 603.94 | 0.00 | 0.00 |
February | 2170.80 | 209.76 | 1033.03 | 378.76 | 654.27 | 0.00 | 0.00 |
March | 2428.88 | 141.49 | 1126.20 | 441.01 | 685.18 | 0.00 | 0.00 |
April | 2514.59 | 65.54 | 1138.19 | 434.84 | 703.36 | 0.00 | 0.00 |
May | 2250.36 | 83.02 | 978.38 | 296.15 | 682.23 | 0.00 | 0.00 |
June | 2371.66 | 95.43 | 1042.06 | 343.20 | 698.86 | 0.00 | 0.00 |
July | 1899.05 | 158.45 | 890.06 | 199.40 | 690.66 | 0.00 | 0.00 |
August | 2063.56 | 126.18 | 979.53 | 287.94 | 691.59 | 0.00 | 0.00 |
September | 1988.74 | 131.43 | 919.90 | 250.68 | 669.22 | 0.00 | 0.00 |
October | 1771.57 | 161.47 | 862.15 | 220.57 | 641.58 | 0.00 | 0.00 |
November | 1723.22 | 196.65 | 834.39 | 230.58 | 603.81 | 0.00 | 0.00 |
December | 1740.16 | 297.78 | 853.86 | 274.01 | 579.85 | 0.00 | 0.00 |
Annual Sum or Average | 2064.01 | 161.29 | 963.28 | 304.64 | 658.64 | 0.00 | 0.00 |
Minimum of Months | 1723.22 | 65.54 | 834.39 | 199.40 | 579.85 | 0.00 | 0.00 |
Maximum of Months | 2514.59 | 297.78 | 1138.19 | 441.01 | 703.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3889.93 | 448.02 | 1876.22 | 782.78 | 1093.44 | 0.00 | 0.00 |
February | 3558.84 | 342.70 | 1593.19 | 519.44 | 1073.75 | 0.00 | 0.00 |
March | 2696.41 | 213.38 | 1087.26 | 146.02 | 941.24 | 0.00 | 0.00 |
April | 2107.73 | 78.92 | 810.61 | 0.36 | 810.24 | 0.00 | 0.00 |
May | 2160.52 | 107.36 | 811.16 | 0.00 | 811.16 | 0.00 | 0.00 |
June | 2153.46 | 117.92 | 808.24 | 0.00 | 808.24 | 0.00 | 0.00 |
July | 1908.10 | 217.19 | 832.61 | 0.00 | 832.61 | 0.00 | 0.00 |
August | 1875.79 | 162.27 | 810.55 | 1.25 | 809.30 | 0.00 | 0.00 |
September | 2115.13 | 183.39 | 897.34 | 29.31 | 868.03 | 0.00 | 0.00 |
October | 2538.63 | 252.85 | 1173.98 | 187.18 | 986.80 | 0.00 | 0.00 |
November | 3216.72 | 323.72 | 1526.56 | 465.73 | 1060.83 | 0.00 | 0.00 |
December | 3827.52 | 499.21 | 1875.26 | 797.85 | 1077.41 | 0.00 | 0.00 |
Annual Sum or Average | 2666.42 | 245.54 | 1173.62 | 243.22 | 930.40 | 0.00 | 0.00 |
Minimum of Months | 1875.79 | 78.92 | 808.24 | 0.00 | 808.24 | 0.00 | 0.00 |
Maximum of Months | 3889.93 | 499.21 | 1876.22 | 797.85 | 1093.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1910.39 | 318.85 | 923.00 | 324.56 | 598.44 | 0.00 | 0.00 |
February | 2145.92 | 261.42 | 1013.72 | 358.73 | 654.99 | 0.00 | 0.00 |
March | 2456.12 | 199.67 | 1136.30 | 448.82 | 687.49 | 0.00 | 0.00 |
April | 2492.09 | 108.32 | 1141.92 | 437.37 | 704.55 | 0.00 | 0.00 |
May | 2208.19 | 97.87 | 971.65 | 287.86 | 683.80 | 0.00 | 0.00 |
June | 2362.07 | 113.18 | 1052.91 | 362.91 | 689.99 | 0.00 | 0.00 |
July | 1894.56 | 184.12 | 897.66 | 211.69 | 685.97 | 0.00 | 0.00 |
August | 2025.08 | 152.92 | 975.93 | 289.02 | 686.92 | 0.00 | 0.00 |
September | 1954.57 | 153.09 | 914.10 | 253.53 | 660.57 | 0.00 | 0.00 |
October | 1750.30 | 192.14 | 858.52 | 221.31 | 637.21 | 0.00 | 0.00 |
November | 1721.62 | 230.20 | 837.23 | 228.34 | 608.89 | 0.00 | 0.00 |
December | 1763.24 | 352.88 | 856.84 | 280.29 | 576.55 | 0.00 | 0.00 |
Annual Sum or Average | 2055.45 | 197.03 | 964.35 | 308.16 | 656.19 | 0.00 | 0.00 |
Minimum of Months | 1721.62 | 97.87 | 837.23 | 211.69 | 576.55 | 0.00 | 0.00 |
Maximum of Months | 2492.09 | 352.88 | 1141.92 | 448.82 | 704.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.426761E+10 | 0.106476E+10 | 0.189803E+10 | 0.00 | 0.189803E+10 | 0.00 | 0.00 |
February | 0.432556E+10 | 0.713747E+09 | 0.182874E+10 | 0.00 | 0.182874E+10 | 0.00 | 0.00 |
March | 0.520980E+10 | 0.545319E+09 | 0.207793E+10 | 0.00 | 0.207793E+10 | 0.00 | 0.00 |
April | 0.560472E+10 | 0.262824E+09 | 0.218840E+10 | 31013687.53 | 0.215738E+10 | 0.00 | 0.00 |
May | 0.749819E+10 | 0.293652E+09 | 0.289877E+10 | 0.308806E+09 | 0.258997E+10 | 0.00 | 0.00 |
June | 0.862042E+10 | 0.324993E+09 | 0.342673E+10 | 0.692514E+09 | 0.273421E+10 | 0.00 | 0.00 |
July | 0.697753E+10 | 0.593705E+09 | 0.304488E+10 | 0.319158E+09 | 0.272573E+10 | 0.00 | 0.00 |
August | 0.578732E+10 | 0.485728E+09 | 0.250693E+10 | 0.106898E+09 | 0.240003E+10 | 0.00 | 0.00 |
September | 0.497015E+10 | 0.426485E+09 | 0.206553E+10 | 989085.75 | 0.206454E+10 | 0.00 | 0.00 |
October | 0.456843E+10 | 0.563919E+09 | 0.205656E+10 | 0.00 | 0.205656E+10 | 0.00 | 0.00 |
November | 0.420164E+10 | 0.693266E+09 | 0.188318E+10 | 0.00 | 0.188318E+10 | 0.00 | 0.00 |
December | 0.406776E+10 | 0.118041E+10 | 0.184391E+10 | 0.00 | 0.184391E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.660991E+11 | 0.714881E+10 | 0.277196E+11 | 0.145938E+10 | 0.262602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.406776E+10 | 0.262824E+09 | 0.182874E+10 | 0.00 | 0.182874E+10 | 0.00 | 0.00 |
Maximum of Months | 0.862042E+10 | 0.118041E+10 | 0.342673E+10 | 0.692514E+09 | 0.273421E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.508261E+10 | 0.678074E+09 | 0.243993E+10 | 0.822328E+09 | 0.161761E+10 | 0.00 | 0.00 |
February | 0.534496E+10 | 0.439005E+09 | 0.249911E+10 | 0.916298E+09 | 0.158281E+10 | 0.00 | 0.00 |
March | 0.662147E+10 | 0.320751E+09 | 0.301642E+10 | 0.118121E+10 | 0.183520E+10 | 0.00 | 0.00 |
April | 0.663510E+10 | 0.128212E+09 | 0.295021E+10 | 0.112710E+10 | 0.182311E+10 | 0.00 | 0.00 |
May | 0.615123E+10 | 0.178088E+09 | 0.262050E+10 | 0.793221E+09 | 0.182728E+10 | 0.00 | 0.00 |
June | 0.626687E+10 | 0.180290E+09 | 0.270102E+10 | 0.889573E+09 | 0.181145E+10 | 0.00 | 0.00 |
July | 0.519835E+10 | 0.342132E+09 | 0.238395E+10 | 0.534063E+09 | 0.184988E+10 | 0.00 | 0.00 |
August | 0.562948E+10 | 0.263788E+09 | 0.262358E+10 | 0.771220E+09 | 0.185236E+10 | 0.00 | 0.00 |
September | 0.525440E+10 | 0.284445E+09 | 0.238438E+10 | 0.649754E+09 | 0.173463E+10 | 0.00 | 0.00 |
October | 0.484985E+10 | 0.357467E+09 | 0.230919E+10 | 0.590772E+09 | 0.171841E+10 | 0.00 | 0.00 |
November | 0.456536E+10 | 0.430053E+09 | 0.216274E+10 | 0.597664E+09 | 0.156507E+10 | 0.00 | 0.00 |
December | 0.475416E+10 | 0.708470E+09 | 0.228699E+10 | 0.733916E+09 | 0.155307E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.663538E+11 | 0.431077E+10 | 0.303780E+11 | 0.960713E+10 | 0.207709E+11 | 0.00 | 0.00 |
Minimum of Months | 0.456536E+10 | 0.128212E+09 | 0.216274E+10 | 0.534063E+09 | 0.155307E+10 | 0.00 | 0.00 |
Maximum of Months | 0.663510E+10 | 0.708470E+09 | 0.301642E+10 | 0.118121E+10 | 0.185236E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105572E+11 | 0.115250E+10 | 0.502528E+10 | 0.209661E+10 | 0.292868E+10 | 0.00 | 0.00 |
February | 0.872091E+10 | 0.767624E+09 | 0.385427E+10 | 0.125664E+10 | 0.259763E+10 | 0.00 | 0.00 |
March | 0.728430E+10 | 0.555671E+09 | 0.291214E+10 | 0.391102E+09 | 0.252103E+10 | 0.00 | 0.00 |
April | 0.544391E+10 | 0.226757E+09 | 0.210110E+10 | 943200.05 | 0.210016E+10 | 0.00 | 0.00 |
May | 0.586363E+10 | 0.258545E+09 | 0.217262E+10 | 0.00 | 0.217262E+10 | 0.00 | 0.00 |
June | 0.563138E+10 | 0.267449E+09 | 0.209497E+10 | 0.00 | 0.209497E+10 | 0.00 | 0.00 |
July | 0.516999E+10 | 0.543558E+09 | 0.223007E+10 | 0.00 | 0.223007E+10 | 0.00 | 0.00 |
August | 0.503447E+10 | 0.440331E+09 | 0.217099E+10 | 3355309.41 | 0.216763E+10 | 0.00 | 0.00 |
September | 0.556673E+10 | 0.435604E+09 | 0.232591E+10 | 75965924.18 | 0.224994E+10 | 0.00 | 0.00 |
October | 0.690753E+10 | 0.619555E+09 | 0.314440E+10 | 0.501350E+09 | 0.264305E+10 | 0.00 | 0.00 |
November | 0.844581E+10 | 0.777944E+09 | 0.395686E+10 | 0.120719E+10 | 0.274968E+10 | 0.00 | 0.00 |
December | 0.103567E+11 | 0.128161E+10 | 0.502271E+10 | 0.213696E+10 | 0.288575E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.849826E+11 | 0.732715E+10 | 0.370113E+11 | 0.767010E+10 | 0.293412E+11 | 0.00 | 0.00 |
Minimum of Months | 0.503447E+10 | 0.226757E+09 | 0.209497E+10 | 0.00 | 0.209497E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105572E+11 | 0.128161E+10 | 0.502528E+10 | 0.213696E+10 | 0.292868E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.511895E+10 | 0.927139E+09 | 0.247218E+10 | 0.869297E+09 | 0.160288E+10 | 0.00 | 0.00 |
February | 0.517767E+10 | 0.715227E+09 | 0.245240E+10 | 0.867848E+09 | 0.158455E+10 | 0.00 | 0.00 |
March | 0.653121E+10 | 0.670184E+09 | 0.304349E+10 | 0.120212E+10 | 0.184137E+10 | 0.00 | 0.00 |
April | 0.632663E+10 | 0.465428E+09 | 0.295988E+10 | 0.113368E+10 | 0.182620E+10 | 0.00 | 0.00 |
May | 0.592571E+10 | 0.305013E+09 | 0.260248E+10 | 0.770996E+09 | 0.183149E+10 | 0.00 | 0.00 |
June | 0.609841E+10 | 0.364676E+09 | 0.272914E+10 | 0.940671E+09 | 0.178847E+10 | 0.00 | 0.00 |
July | 0.502173E+10 | 0.623801E+09 | 0.240429E+10 | 0.566987E+09 | 0.183730E+10 | 0.00 | 0.00 |
August | 0.530159E+10 | 0.635104E+09 | 0.261395E+10 | 0.774103E+09 | 0.183984E+10 | 0.00 | 0.00 |
September | 0.508152E+10 | 0.450150E+09 | 0.236937E+10 | 0.657158E+09 | 0.171221E+10 | 0.00 | 0.00 |
October | 0.466184E+10 | 0.621782E+09 | 0.229948E+10 | 0.592755E+09 | 0.170672E+10 | 0.00 | 0.00 |
November | 0.439905E+10 | 0.745500E+09 | 0.217012E+10 | 0.591857E+09 | 0.157826E+10 | 0.00 | 0.00 |
December | 0.462048E+10 | 0.118892E+10 | 0.229498E+10 | 0.750729E+09 | 0.154425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.642648E+11 | 0.771292E+10 | 0.304117E+11 | 0.971820E+10 | 0.206935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.439905E+10 | 0.305013E+09 | 0.217012E+10 | 0.566987E+09 | 0.154425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.653121E+10 | 0.118892E+10 | 0.304349E+10 | 0.120212E+10 | 0.184137E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.429370E+10 | 0.105206E+10 | 0.189802E+10 | 0.00 | 0.189802E+10 | 0.00 | 0.00 |
February | 0.434953E+10 | 0.737361E+09 | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.00 | 0.00 |
March | 0.526579E+10 | 0.523016E+09 | 0.207793E+10 | 0.00 | 0.207793E+10 | 0.00 | 0.00 |
April | 0.570642E+10 | 0.208399E+09 | 0.218839E+10 | 31013577.40 | 0.215738E+10 | 0.00 | 0.00 |
May | 0.747735E+10 | 0.312047E+09 | 0.289876E+10 | 0.308805E+09 | 0.258996E+10 | 0.00 | 0.00 |
June | 0.859045E+10 | 0.361097E+09 | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.00 | 0.00 |
July | 0.696362E+10 | 0.614265E+09 | 0.304487E+10 | 0.319157E+09 | 0.272572E+10 | 0.00 | 0.00 |
August | 0.583456E+10 | 0.460389E+09 | 0.250692E+10 | 0.106897E+09 | 0.240003E+10 | 0.00 | 0.00 |
September | 0.497983E+10 | 0.427141E+09 | 0.206552E+10 | 989082.24 | 0.206453E+10 | 0.00 | 0.00 |
October | 0.458008E+10 | 0.568786E+09 | 0.205655E+10 | 0.00 | 0.205655E+10 | 0.00 | 0.00 |
November | 0.422902E+10 | 0.693822E+09 | 0.188318E+10 | 0.00 | 0.188318E+10 | 0.00 | 0.00 |
December | 0.412345E+10 | 0.116390E+10 | 0.184390E+10 | 0.00 | 0.184390E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.663938E+11 | 0.712229E+10 | 0.277195E+11 | 0.145937E+10 | 0.262601E+11 | 0.00 | 0.00 |
Minimum of Months | 0.412345E+10 | 0.208399E+09 | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.00 | 0.00 |
Maximum of Months | 0.859045E+10 | 0.116390E+10 | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.502119E+10 | 0.710865E+09 | 0.243992E+10 | 0.822325E+09 | 0.161760E+10 | 0.00 | 0.00 |
February | 0.527742E+10 | 0.498555E+09 | 0.249910E+10 | 0.916294E+09 | 0.158281E+10 | 0.00 | 0.00 |
March | 0.654148E+10 | 0.362926E+09 | 0.301641E+10 | 0.118121E+10 | 0.183520E+10 | 0.00 | 0.00 |
April | 0.656366E+10 | 0.153526E+09 | 0.295020E+10 | 0.112710E+10 | 0.182310E+10 | 0.00 | 0.00 |
May | 0.607374E+10 | 0.209504E+09 | 0.262049E+10 | 0.793218E+09 | 0.182727E+10 | 0.00 | 0.00 |
June | 0.618439E+10 | 0.228826E+09 | 0.270101E+10 | 0.889570E+09 | 0.181144E+10 | 0.00 | 0.00 |
July | 0.512230E+10 | 0.403759E+09 | 0.238394E+10 | 0.534060E+09 | 0.184988E+10 | 0.00 | 0.00 |
August | 0.555418E+10 | 0.323097E+09 | 0.262357E+10 | 0.771217E+09 | 0.185235E+10 | 0.00 | 0.00 |
September | 0.518701E+10 | 0.320924E+09 | 0.238437E+10 | 0.649752E+09 | 0.173462E+10 | 0.00 | 0.00 |
October | 0.477317E+10 | 0.414966E+09 | 0.230918E+10 | 0.590770E+09 | 0.171841E+10 | 0.00 | 0.00 |
November | 0.449176E+10 | 0.497501E+09 | 0.216273E+10 | 0.597661E+09 | 0.156507E+10 | 0.00 | 0.00 |
December | 0.468038E+10 | 0.792984E+09 | 0.228698E+10 | 0.733913E+09 | 0.155306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.654707E+11 | 0.491743E+10 | 0.303779E+11 | 0.960709E+10 | 0.207708E+11 | 0.00 | 0.00 |
Minimum of Months | 0.449176E+10 | 0.153526E+09 | 0.216273E+10 | 0.534060E+09 | 0.155306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656366E+10 | 0.792984E+09 | 0.301641E+10 | 0.118121E+10 | 0.185235E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104677E+11 | 0.119221E+10 | 0.502526E+10 | 0.209660E+10 | 0.292867E+10 | 0.00 | 0.00 |
February | 0.866753E+10 | 0.815005E+09 | 0.385425E+10 | 0.125663E+10 | 0.259762E+10 | 0.00 | 0.00 |
March | 0.730368E+10 | 0.542570E+09 | 0.291213E+10 | 0.391101E+09 | 0.252102E+10 | 0.00 | 0.00 |
April | 0.556573E+10 | 0.178647E+09 | 0.210109E+10 | 943196.70 | 0.210015E+10 | 0.00 | 0.00 |
May | 0.589327E+10 | 0.267019E+09 | 0.217261E+10 | 0.00 | 0.217261E+10 | 0.00 | 0.00 |
June | 0.567449E+10 | 0.278312E+09 | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.00 | 0.00 |
July | 0.519871E+10 | 0.544188E+09 | 0.223006E+10 | 0.00 | 0.223006E+10 | 0.00 | 0.00 |
August | 0.509970E+10 | 0.408241E+09 | 0.217098E+10 | 3355297.50 | 0.216763E+10 | 0.00 | 0.00 |
September | 0.556513E+10 | 0.440095E+09 | 0.232590E+10 | 75965654.42 | 0.224994E+10 | 0.00 | 0.00 |
October | 0.687478E+10 | 0.647863E+09 | 0.314439E+10 | 0.501348E+09 | 0.264304E+10 | 0.00 | 0.00 |
November | 0.840091E+10 | 0.820282E+09 | 0.395685E+10 | 0.120718E+10 | 0.274967E+10 | 0.00 | 0.00 |
December | 0.102992E+11 | 0.133267E+10 | 0.502269E+10 | 0.213695E+10 | 0.288574E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.850107E+11 | 0.746710E+10 | 0.370112E+11 | 0.767007E+10 | 0.293411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.509970E+10 | 0.178647E+09 | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104677E+11 | 0.133267E+10 | 0.502526E+10 | 0.213695E+10 | 0.292867E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.515736E+10 | 0.847217E+09 | 0.247217E+10 | 0.869293E+09 | 0.160287E+10 | 0.00 | 0.00 |
February | 0.523409E+10 | 0.622672E+09 | 0.245239E+10 | 0.867845E+09 | 0.158455E+10 | 0.00 | 0.00 |
March | 0.663144E+10 | 0.518698E+09 | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.00 | 0.00 |
April | 0.651882E+10 | 0.262740E+09 | 0.295987E+10 | 0.113367E+10 | 0.182619E+10 | 0.00 | 0.00 |
May | 0.597730E+10 | 0.247424E+09 | 0.260247E+10 | 0.770992E+09 | 0.183148E+10 | 0.00 | 0.00 |
June | 0.618203E+10 | 0.276252E+09 | 0.272913E+10 | 0.940668E+09 | 0.178846E+10 | 0.00 | 0.00 |
July | 0.513178E+10 | 0.475440E+09 | 0.240428E+10 | 0.566985E+09 | 0.183730E+10 | 0.00 | 0.00 |
August | 0.547665E+10 | 0.395829E+09 | 0.261394E+10 | 0.774100E+09 | 0.183984E+10 | 0.00 | 0.00 |
September | 0.512087E+10 | 0.378654E+09 | 0.236936E+10 | 0.657155E+09 | 0.171220E+10 | 0.00 | 0.00 |
October | 0.473593E+10 | 0.498698E+09 | 0.229947E+10 | 0.592753E+09 | 0.170671E+10 | 0.00 | 0.00 |
November | 0.450593E+10 | 0.585494E+09 | 0.217011E+10 | 0.591854E+09 | 0.157825E+10 | 0.00 | 0.00 |
December | 0.476155E+10 | 0.941498E+09 | 0.229497E+10 | 0.750726E+09 | 0.154424E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.654337E+11 | 0.605062E+10 | 0.304116E+11 | 0.971816E+10 | 0.206935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.450593E+10 | 0.247424E+09 | 0.217011E+10 | 0.566985E+09 | 0.154424E+10 | 0.00 | 0.00 |
Maximum of Months | 0.663144E+10 | 0.941498E+09 | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.423472E+10 | 0.107113E+10 | 0.189802E+10 | 0.00 | 0.189802E+10 | 0.00 | 0.00 |
February | 0.428793E+10 | 0.760264E+09 | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.00 | 0.00 |
March | 0.518995E+10 | 0.559025E+09 | 0.207793E+10 | 0.00 | 0.207793E+10 | 0.00 | 0.00 |
April | 0.560881E+10 | 0.239655E+09 | 0.218839E+10 | 31013577.40 | 0.215738E+10 | 0.00 | 0.00 |
May | 0.737683E+10 | 0.336278E+09 | 0.289876E+10 | 0.308805E+09 | 0.258996E+10 | 0.00 | 0.00 |
June | 0.850271E+10 | 0.391748E+09 | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.00 | 0.00 |
July | 0.687504E+10 | 0.648412E+09 | 0.304487E+10 | 0.319157E+09 | 0.272572E+10 | 0.00 | 0.00 |
August | 0.576187E+10 | 0.487279E+09 | 0.250692E+10 | 0.106897E+09 | 0.240003E+10 | 0.00 | 0.00 |
September | 0.489936E+10 | 0.463716E+09 | 0.206552E+10 | 989082.24 | 0.206453E+10 | 0.00 | 0.00 |
October | 0.450911E+10 | 0.602579E+09 | 0.205655E+10 | 0.00 | 0.205655E+10 | 0.00 | 0.00 |
November | 0.416397E+10 | 0.720449E+09 | 0.188318E+10 | 0.00 | 0.188318E+10 | 0.00 | 0.00 |
December | 0.406798E+10 | 0.117906E+10 | 0.184390E+10 | 0.00 | 0.184390E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.654783E+11 | 0.745959E+10 | 0.277195E+11 | 0.145937E+10 | 0.262601E+11 | 0.00 | 0.00 |
Minimum of Months | 0.406798E+10 | 0.239655E+09 | 0.182873E+10 | 0.00 | 0.182873E+10 | 0.00 | 0.00 |
Maximum of Months | 0.850271E+10 | 0.117906E+10 | 0.342671E+10 | 0.692512E+09 | 0.273420E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.500037E+10 | 0.717779E+09 | 0.243992E+10 | 0.822325E+09 | 0.161760E+10 | 0.00 | 0.00 |
February | 0.525160E+10 | 0.507449E+09 | 0.249910E+10 | 0.916294E+09 | 0.158281E+10 | 0.00 | 0.00 |
March | 0.650551E+10 | 0.378959E+09 | 0.301641E+10 | 0.118121E+10 | 0.183520E+10 | 0.00 | 0.00 |
April | 0.651781E+10 | 0.169887E+09 | 0.295020E+10 | 0.112710E+10 | 0.182310E+10 | 0.00 | 0.00 |
May | 0.602738E+10 | 0.222360E+09 | 0.262049E+10 | 0.793218E+09 | 0.182727E+10 | 0.00 | 0.00 |
June | 0.614734E+10 | 0.247353E+09 | 0.270101E+10 | 0.889570E+09 | 0.181144E+10 | 0.00 | 0.00 |
July | 0.508643E+10 | 0.424390E+09 | 0.238394E+10 | 0.534060E+09 | 0.184988E+10 | 0.00 | 0.00 |
August | 0.552703E+10 | 0.337948E+09 | 0.262357E+10 | 0.771217E+09 | 0.185235E+10 | 0.00 | 0.00 |
September | 0.515483E+10 | 0.340671E+09 | 0.238437E+10 | 0.649752E+09 | 0.173462E+10 | 0.00 | 0.00 |
October | 0.474497E+10 | 0.432488E+09 | 0.230918E+10 | 0.590770E+09 | 0.171841E+10 | 0.00 | 0.00 |
November | 0.446657E+10 | 0.509728E+09 | 0.216273E+10 | 0.597661E+09 | 0.156507E+10 | 0.00 | 0.00 |
December | 0.466084E+10 | 0.797563E+09 | 0.228698E+10 | 0.733913E+09 | 0.155306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650907E+11 | 0.508657E+10 | 0.303779E+11 | 0.960709E+10 | 0.207708E+11 | 0.00 | 0.00 |
Minimum of Months | 0.446657E+10 | 0.169887E+09 | 0.216273E+10 | 0.534060E+09 | 0.155306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.651781E+10 | 0.797563E+09 | 0.301641E+10 | 0.118121E+10 | 0.185235E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104188E+11 | 0.119999E+10 | 0.502526E+10 | 0.209660E+10 | 0.292867E+10 | 0.00 | 0.00 |
February | 0.860955E+10 | 0.829058E+09 | 0.385425E+10 | 0.125663E+10 | 0.259762E+10 | 0.00 | 0.00 |
March | 0.722206E+10 | 0.571515E+09 | 0.291213E+10 | 0.391101E+09 | 0.252102E+10 | 0.00 | 0.00 |
April | 0.546324E+10 | 0.204561E+09 | 0.210109E+10 | 943196.70 | 0.210015E+10 | 0.00 | 0.00 |
May | 0.578674E+10 | 0.287541E+09 | 0.217261E+10 | 0.00 | 0.217261E+10 | 0.00 | 0.00 |
June | 0.558178E+10 | 0.305640E+09 | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.00 | 0.00 |
July | 0.511064E+10 | 0.581733E+09 | 0.223006E+10 | 0.00 | 0.223006E+10 | 0.00 | 0.00 |
August | 0.502411E+10 | 0.434611E+09 | 0.217098E+10 | 3355297.50 | 0.216763E+10 | 0.00 | 0.00 |
September | 0.548241E+10 | 0.475338E+09 | 0.232590E+10 | 75965654.42 | 0.224994E+10 | 0.00 | 0.00 |
October | 0.679945E+10 | 0.677245E+09 | 0.314439E+10 | 0.501348E+09 | 0.264304E+10 | 0.00 | 0.00 |
November | 0.833774E+10 | 0.839090E+09 | 0.395685E+10 | 0.120718E+10 | 0.274967E+10 | 0.00 | 0.00 |
December | 0.102516E+11 | 0.133709E+10 | 0.502269E+10 | 0.213695E+10 | 0.288574E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.840881E+11 | 0.774341E+10 | 0.370112E+11 | 0.767007E+10 | 0.293411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.502411E+10 | 0.204561E+09 | 0.209496E+10 | 0.00 | 0.209496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104188E+11 | 0.133709E+10 | 0.502526E+10 | 0.213695E+10 | 0.292867E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.511678E+10 | 0.854006E+09 | 0.247217E+10 | 0.869293E+09 | 0.160287E+10 | 0.00 | 0.00 |
February | 0.519142E+10 | 0.632418E+09 | 0.245239E+10 | 0.867845E+09 | 0.158455E+10 | 0.00 | 0.00 |
March | 0.657847E+10 | 0.534801E+09 | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.00 | 0.00 |
April | 0.645949E+10 | 0.280762E+09 | 0.295987E+10 | 0.113367E+10 | 0.182619E+10 | 0.00 | 0.00 |
May | 0.591441E+10 | 0.262129E+09 | 0.260247E+10 | 0.770992E+09 | 0.183148E+10 | 0.00 | 0.00 |
June | 0.612249E+10 | 0.293353E+09 | 0.272913E+10 | 0.940668E+09 | 0.178846E+10 | 0.00 | 0.00 |
July | 0.507439E+10 | 0.493141E+09 | 0.240428E+10 | 0.566985E+09 | 0.183730E+10 | 0.00 | 0.00 |
August | 0.542397E+10 | 0.409585E+09 | 0.261394E+10 | 0.774100E+09 | 0.183984E+10 | 0.00 | 0.00 |
September | 0.506625E+10 | 0.396802E+09 | 0.236936E+10 | 0.657155E+09 | 0.171220E+10 | 0.00 | 0.00 |
October | 0.468800E+10 | 0.514637E+09 | 0.229947E+10 | 0.592753E+09 | 0.170671E+10 | 0.00 | 0.00 |
November | 0.446243E+10 | 0.596674E+09 | 0.217011E+10 | 0.591854E+09 | 0.157825E+10 | 0.00 | 0.00 |
December | 0.472265E+10 | 0.945167E+09 | 0.229497E+10 | 0.750726E+09 | 0.154424E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.648208E+11 | 0.621347E+10 | 0.304116E+11 | 0.971816E+10 | 0.206935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.446243E+10 | 0.262129E+09 | 0.217011E+10 | 0.566985E+09 | 0.154424E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657847E+10 | 0.945167E+09 | 0.304348E+10 | 0.120212E+10 | 0.184136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.242870E+11 | -0.232687E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101833E+10 | 58.97 | 0.00 | 0.00 |
February | 0.219313E+11 | -0.210105E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -920767767.3 | 58.97 | 0.00 | 0.00 |
March | 0.253501E+11 | -0.243268E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102324E+10 | 58.97 | 0.00 | 0.00 |
April | 0.225624E+11 | -0.215756E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986790904.1 | 58.97 | 0.00 | 0.00 |
May | 0.235593E+11 | -0.225379E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102138E+10 | 58.98 | 0.00 | 0.00 |
June | 0.229839E+11 | -0.219944E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989475879.6 | 58.96 | 0.00 | 0.00 |
July | 0.218195E+11 | -0.208019E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101759E+10 | 58.97 | 0.00 | 0.00 |
August | 0.239759E+11 | -0.229536E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102232E+10 | 58.96 | 0.00 | 0.00 |
September | 0.221679E+11 | -0.211805E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987457028.1 | 58.97 | 0.00 | 0.00 |
October | 0.233630E+11 | -0.223440E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101894E+10 | 58.97 | 0.00 | 0.00 |
November | 0.233799E+11 | -0.223943E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985590581.9 | 58.97 | 0.00 | 0.00 |
December | 0.236349E+11 | -0.226178E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101712E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.279015E+12 | -0.267006E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120090E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.218195E+11 | -0.243268E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102324E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.253501E+11 | -0.208019E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -920767767.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:40 | 2239.14 | 26.26 | 214.00 | 323.33 | 1031.51 | 22.27 | 284.67 | 299.50 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:00 | 1777.18 | 20.65 | 103.33 | 294.50 | 923.64 | 21.97 | 254.67 | 272.83 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-07:40 | 1357.17 | 20.35 | 57.83 | 327.00 | 746.29 | 21.64 | 267.50 | 299.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1120.25 | 19.99 | 0.00 | 325.00 | 629.78 | 21.33 | 225.00 | 287.33 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:49 | 957.46 | 18.97 | 0.00 | 331.33 | 528.59 | 20.26 | 103.83 | 283.67 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-07:30 | 938.04 | 19.12 | 0.00 | 324.33 | 534.40 | 20.48 | 123.67 | 278.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:10 | 903.89 | 18.57 | 0.00 | 328.00 | 487.92 | 19.81 | 38.33 | 276.83 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:00 | 1068.86 | 19.46 | 1.00 | 330.50 | 579.83 | 20.75 | 155.67 | 287.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1202.15 | 19.32 | 9.67 | 314.50 | 626.05 | 20.57 | 179.67 | 275.83 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-06:30 | 1547.22 | 20.75 | 83.50 | 324.83 | 777.03 | 21.73 | 248.33 | 286.50 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-06:00 | 1945.70 | 24.76 | 195.67 | 313.33 | 943.10 | 23.38 | 285.00 | 284.83 |
December | 349.33 | 0.50 | 0.48 | 01-DEC-06:40 | 2247.09 | 26.28 | 207.17 | 320.67 | 1067.98 | 24.02 | 305.50 | 300.00 |
Annual Sum or Average | 4292.33 | 0.51 | 1425.98 | 21.14 | 872.17 | 3857.33 | 732.57 | 21.48 | 2471.83 | 3432.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 903.89 | 18.57 | 0.00 | 294.50 | 487.92 | 19.81 | 38.33 | 272.83 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2247.09 | 26.28 | 214.00 | 331.33 | 1067.98 | 24.02 | 305.50 | 300.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:10 | 1893.73 | 23.72 | 108.50 | 310.83 | 984.29 | 23.98 | 194.00 | 275.50 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:40 | 2104.37 | 23.87 | 99.17 | 288.33 | 1095.67 | 24.14 | 162.00 | 260.67 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2379.45 | 23.97 | 112.33 | 325.17 | 983.30 | 23.07 | 155.00 | 297.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:10 | 1982.24 | 23.24 | 90.50 | 330.00 | 1033.32 | 23.72 | 155.83 | 300.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-05:49 | 1707.61 | 22.69 | 98.00 | 339.33 | 876.22 | 23.15 | 152.50 | 301.33 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-06:40 | 1828.39 | 22.94 | 93.17 | 336.00 | 946.26 | 23.42 | 172.67 | 303.00 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:10 | 1517.80 | 22.31 | 95.67 | 338.67 | 768.47 | 22.73 | 156.83 | 296.00 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1732.80 | 22.76 | 91.00 | 337.83 | 888.86 | 23.22 | 160.83 | 303.00 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:10 | 1627.54 | 22.21 | 90.67 | 315.50 | 829.63 | 22.63 | 151.00 | 277.83 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-05:00 | 1631.05 | 22.61 | 91.50 | 317.83 | 824.78 | 22.97 | 164.00 | 280.67 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-06:30 | 1636.05 | 22.56 | 84.83 | 299.33 | 812.89 | 22.71 | 173.33 | 262.33 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:30 | 1840.48 | 23.78 | 112.50 | 303.67 | 837.19 | 23.00 | 191.50 | 270.33 |
Annual Sum or Average | 4292.33 | 0.51 | 1819.75 | 23.04 | 1167.83 | 3842.50 | 904.79 | 23.22 | 1989.50 | 3428.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1517.80 | 22.21 | 84.83 | 288.33 | 768.47 | 22.63 | 151.00 | 260.67 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2379.45 | 23.97 | 112.50 | 339.33 | 1095.67 | 24.14 | 194.00 | 303.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:09 | 768.83 | 18.11 | 0.00 | 300.00 | 450.09 | 19.48 | 0.00 | 244.00 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:30 | 846.73 | 18.60 | 0.00 | 281.00 | 497.57 | 19.95 | 6.67 | 242.00 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 966.72 | 19.47 | 0.00 | 324.50 | 566.65 | 20.80 | 143.83 | 290.33 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:40 | 1174.76 | 20.44 | 14.33 | 333.67 | 657.74 | 21.74 | 243.50 | 303.00 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1352.65 | 20.35 | 78.33 | 349.83 | 701.23 | 21.58 | 238.33 | 317.33 |
June | 370.50 | 0.49 | 0.48 | 01-JUN-07:10 | 1615.88 | 24.33 | 189.67 | 348.67 | 812.90 | 23.29 | 319.50 | 323.00 |
July | 383.17 | 0.50 | 0.48 | 01-JUL-06:40 | 1397.32 | 23.84 | 137.00 | 352.00 | 692.78 | 23.37 | 280.00 | 319.50 |
August | 369.33 | 0.49 | 0.48 | 01-AUG-06:19 | 1259.03 | 20.23 | 48.33 | 343.67 | 667.20 | 21.50 | 224.67 | 308.00 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:40 | 1024.74 | 19.02 | 0.00 | 315.33 | 549.53 | 20.25 | 116.00 | 274.00 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 907.28 | 18.84 | 0.00 | 311.83 | 494.46 | 20.07 | 60.50 | 261.17 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:30 | 814.21 | 18.48 | 0.00 | 289.33 | 455.25 | 19.75 | 0.67 | 237.33 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:19 | 747.58 | 17.89 | 0.00 | 293.50 | 432.42 | 19.24 | 0.00 | 236.00 |
Annual Sum or Average | 4292.33 | 0.51 | 1082.47 | 20.03 | 467.67 | 3843.33 | 585.41 | 20.96 | 1633.67 | 3355.67 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 747.58 | 17.89 | 0.00 | 281.00 | 432.42 | 19.24 | 0.00 | 236.00 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1615.88 | 24.33 | 189.67 | 352.00 | 812.90 | 23.37 | 319.50 | 323.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-08:30 | 1953.88 | 23.93 | 109.33 | 310.17 | 1012.94 | 24.14 | 195.17 | 277.17 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:49 | 2188.47 | 23.84 | 102.33 | 284.50 | 915.12 | 22.84 | 156.83 | 257.50 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-08:09 | 2433.57 | 23.69 | 112.67 | 333.00 | 1001.16 | 22.77 | 158.67 | 301.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 2359.31 | 18.69 | 0.00 | 329.17 | 990.11 | 20.84 | 128.17 | 299.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:00 | 1889.08 | 18.40 | 0.00 | 337.67 | 833.90 | 20.30 | 124.67 | 299.67 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:49 | 2092.13 | 18.80 | 0.00 | 334.83 | 915.13 | 20.81 | 142.00 | 301.67 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-07:30 | 1529.74 | 18.21 | 0.00 | 337.83 | 767.90 | 19.99 | 112.33 | 295.83 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-07:10 | 1973.71 | 18.91 | 8.50 | 335.50 | 865.77 | 20.50 | 121.67 | 299.33 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1776.25 | 21.33 | 87.00 | 311.67 | 800.90 | 20.22 | 112.83 | 277.50 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-07:49 | 1695.88 | 23.19 | 103.67 | 316.17 | 862.79 | 23.54 | 169.17 | 281.00 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:49 | 1683.04 | 23.38 | 95.83 | 302.00 | 856.41 | 23.65 | 182.33 | 266.67 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-07:30 | 1752.82 | 23.39 | 102.83 | 308.00 | 908.50 | 23.64 | 197.00 | 272.50 |
Annual Sum or Average | 4292.33 | 0.51 | 1941.81 | 21.23 | 722.17 | 3840.50 | 893.07 | 21.89 | 1800.83 | 3429.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1529.74 | 18.21 | 0.00 | 284.50 | 767.90 | 19.99 | 112.33 | 257.50 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2433.57 | 23.93 | 112.67 | 337.83 | 1012.94 | 24.14 | 197.00 | 301.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:30 | 2265.22 | 22.10 | 147.33 | 323.83 | 1152.85 | 21.84 | 88.50 | 312.83 |
February | 321.17 | 0.50 | 0.48 | 01-FEB-06:00 | 1803.36 | 14.30 | 0.00 | 294.50 | 984.46 | 17.85 | 0.00 | 275.83 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-07:30 | 1378.77 | 14.64 | 0.00 | 327.50 | 794.64 | 18.06 | 0.00 | 302.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1137.48 | 14.45 | 0.00 | 325.50 | 670.05 | 17.88 | 0.00 | 292.33 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:49 | 971.07 | 13.13 | 0.00 | 332.17 | 562.13 | 16.48 | 0.00 | 287.50 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-07:30 | 952.34 | 13.47 | 0.00 | 324.67 | 568.51 | 16.90 | 0.00 | 283.33 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:00 | 916.66 | 12.53 | 0.00 | 328.50 | 518.68 | 15.88 | 0.00 | 283.00 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:49 | 1083.17 | 13.65 | 0.00 | 331.00 | 616.30 | 17.00 | 0.00 | 290.00 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:40 | 1215.50 | 13.32 | 0.00 | 314.83 | 664.79 | 16.61 | 0.00 | 279.83 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-06:30 | 1561.00 | 14.65 | 15.00 | 325.00 | 824.59 | 17.52 | 4.50 | 290.00 |
November | 337.67 | 0.49 | 0.48 | 01-NOV-06:00 | 1961.75 | 20.20 | 114.17 | 313.50 | 1002.00 | 19.54 | 39.83 | 288.50 |
December | 349.33 | 0.50 | 0.48 | 01-DEC-06:40 | 2271.07 | 22.15 | 148.50 | 320.83 | 1150.94 | 21.73 | 87.50 | 305.67 |
Annual Sum or Average | 4292.33 | 0.50 | 1443.60 | 15.64 | 425.00 | 3861.83 | 784.80 | 18.06 | 220.33 | 3491.50 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 916.66 | 12.53 | 0.00 | 294.50 | 518.68 | 15.88 | 0.00 | 275.83 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2271.07 | 22.15 | 148.50 | 332.17 | 1152.85 | 21.84 | 88.50 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:10 | 1930.06 | 20.98 | 108.50 | 312.50 | 1028.53 | 21.85 | 77.50 | 279.50 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:40 | 2156.07 | 21.08 | 99.00 | 289.00 | 1144.25 | 21.94 | 71.17 | 264.33 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2405.57 | 21.10 | 112.17 | 325.33 | 1036.34 | 20.47 | 52.17 | 300.67 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:10 | 1989.52 | 19.24 | 84.17 | 329.83 | 1086.89 | 21.18 | 60.50 | 302.83 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-05:49 | 1747.44 | 19.50 | 98.00 | 340.50 | 920.11 | 20.67 | 67.33 | 305.83 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-06:40 | 1881.61 | 19.74 | 92.67 | 336.17 | 992.82 | 20.97 | 63.17 | 306.67 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:10 | 1550.16 | 18.16 | 86.67 | 338.33 | 808.38 | 20.23 | 64.67 | 300.50 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1753.52 | 18.82 | 86.00 | 338.33 | 934.96 | 20.69 | 60.33 | 307.17 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:10 | 1637.35 | 18.23 | 83.67 | 316.50 | 871.78 | 20.16 | 60.67 | 282.00 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-05:00 | 1660.00 | 18.78 | 86.17 | 318.83 | 867.24 | 20.50 | 60.50 | 284.83 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-06:30 | 1672.31 | 19.45 | 84.50 | 299.83 | 853.89 | 20.27 | 51.33 | 267.00 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:30 | 1871.70 | 21.07 | 112.50 | 304.00 | 878.98 | 20.67 | 56.00 | 273.67 |
Annual Sum or Average | 4292.33 | 0.50 | 1850.77 | 19.65 | 1134.00 | 3849.17 | 950.04 | 20.79 | 745.33 | 3475.00 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 1550.16 | 18.16 | 83.67 | 289.00 | 808.38 | 20.16 | 51.33 | 264.33 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2405.57 | 21.10 | 112.50 | 340.50 | 1144.25 | 21.94 | 77.50 | 307.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:09 | 781.28 | 12.59 | 0.00 | 300.83 | 478.90 | 16.01 | 0.00 | 252.50 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:30 | 861.27 | 13.19 | 0.00 | 281.17 | 529.69 | 16.59 | 0.00 | 247.83 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 983.69 | 14.14 | 0.00 | 325.17 | 603.44 | 17.55 | 0.00 | 294.83 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:40 | 1193.58 | 14.88 | 0.00 | 333.83 | 699.74 | 18.35 | 0.00 | 307.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1369.95 | 14.17 | 3.83 | 350.17 | 745.07 | 17.50 | 1.17 | 320.50 |
June | 370.50 | 0.49 | 0.48 | 01-JUN-06:00 | 1637.49 | 19.86 | 112.17 | 348.67 | 864.30 | 19.57 | 33.17 | 328.33 |
July | 383.17 | 0.50 | 0.48 | 01-JUL-06:30 | 1412.07 | 19.29 | 115.50 | 352.33 | 735.18 | 19.82 | 59.17 | 322.83 |
August | 369.33 | 0.49 | 0.48 | 01-AUG-06:10 | 1275.37 | 14.26 | 0.00 | 344.00 | 708.77 | 17.67 | 0.00 | 312.83 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:40 | 1038.45 | 13.19 | 0.00 | 315.50 | 583.94 | 16.47 | 0.00 | 280.17 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 920.38 | 12.97 | 0.00 | 312.17 | 525.53 | 16.31 | 0.00 | 267.67 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:19 | 826.78 | 12.70 | 0.00 | 290.00 | 484.03 | 16.07 | 0.00 | 244.17 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:10 | 759.18 | 12.27 | 0.00 | 294.17 | 459.94 | 15.66 | 0.00 | 243.83 |
Annual Sum or Average | 4292.33 | 0.51 | 1097.84 | 14.53 | 231.50 | 3848.00 | 622.37 | 17.34 | 93.50 | 3422.67 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 759.18 | 12.27 | 0.00 | 281.17 | 459.94 | 15.66 | 0.00 | 243.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1637.49 | 19.86 | 115.50 | 352.33 | 864.30 | 19.82 | 59.17 | 328.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-08:20 | 1990.94 | 21.19 | 109.33 | 311.50 | 1057.59 | 22.01 | 77.50 | 281.33 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:40 | 2238.46 | 21.10 | 102.33 | 285.33 | 963.29 | 20.35 | 46.67 | 260.50 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-08:09 | 2459.24 | 20.88 | 112.67 | 333.33 | 1054.21 | 20.18 | 50.67 | 305.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 2375.43 | 14.19 | 0.00 | 329.67 | 1042.88 | 17.63 | 0.00 | 302.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:00 | 1928.62 | 13.95 | 0.00 | 339.33 | 877.74 | 17.14 | 0.00 | 304.83 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:40 | 2144.35 | 14.41 | 0.00 | 335.33 | 961.60 | 17.69 | 0.00 | 306.17 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-07:19 | 1563.14 | 13.74 | 0.00 | 338.00 | 808.03 | 16.84 | 0.00 | 301.17 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-07:10 | 1999.70 | 14.57 | 8.50 | 336.17 | 911.30 | 17.33 | 0.00 | 304.67 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1793.96 | 18.04 | 87.00 | 312.00 | 842.93 | 17.12 | 7.67 | 282.67 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-07:40 | 1730.81 | 20.16 | 103.33 | 316.67 | 905.27 | 21.20 | 72.67 | 284.83 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:40 | 1719.93 | 20.41 | 95.83 | 302.83 | 897.80 | 21.36 | 66.00 | 270.67 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-07:19 | 1784.50 | 20.61 | 102.83 | 308.67 | 951.59 | 21.48 | 71.83 | 277.33 |
Annual Sum or Average | 4292.33 | 0.50 | 1975.14 | 17.66 | 721.83 | 3848.83 | 938.35 | 19.13 | 393.00 | 3481.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1563.14 | 13.74 | 0.00 | 285.33 | 808.03 | 16.84 | 0.00 | 260.50 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2459.24 | 21.19 | 112.67 | 339.33 | 1057.59 | 22.01 | 77.50 | 306.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:30 | 2268.30 | 22.08 | 147.17 | 323.83 | 1154.75 | 21.83 | 88.50 | 312.83 |
February | 321.17 | 0.50 | 0.48 | 01-FEB-06:00 | 1806.09 | 14.27 | 0.00 | 294.50 | 986.10 | 17.83 | 0.00 | 276.00 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-07:30 | 1380.70 | 14.61 | 0.00 | 327.50 | 795.88 | 18.05 | 0.00 | 302.83 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1138.95 | 14.42 | 0.00 | 325.50 | 671.04 | 17.86 | 0.00 | 292.33 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:49 | 972.45 | 13.10 | 0.00 | 332.17 | 563.00 | 16.47 | 0.00 | 287.83 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-07:30 | 953.51 | 13.44 | 0.00 | 324.67 | 569.33 | 16.88 | 0.00 | 283.83 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:00 | 918.08 | 12.50 | 0.00 | 328.67 | 519.52 | 15.86 | 0.00 | 283.00 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:49 | 1084.78 | 13.62 | 0.00 | 331.50 | 617.28 | 16.99 | 0.00 | 290.17 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:40 | 1217.52 | 13.29 | 0.00 | 314.83 | 665.95 | 16.60 | 0.00 | 280.17 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-06:30 | 1563.72 | 14.62 | 15.00 | 325.00 | 826.12 | 17.51 | 4.50 | 290.17 |
November | 337.67 | 0.49 | 0.48 | 01-NOV-06:00 | 1964.93 | 20.18 | 114.17 | 313.50 | 1003.87 | 19.52 | 39.83 | 288.50 |
December | 349.33 | 0.50 | 0.48 | 01-DEC-06:40 | 2274.20 | 22.13 | 148.50 | 320.83 | 1152.89 | 21.72 | 87.50 | 305.67 |
Annual Sum or Average | 4292.33 | 0.50 | 1445.72 | 15.61 | 424.83 | 3862.50 | 786.10 | 18.05 | 220.33 | 3493.33 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 918.08 | 12.50 | 0.00 | 294.50 | 519.52 | 15.86 | 0.00 | 276.00 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2274.20 | 22.13 | 148.50 | 332.17 | 1154.75 | 21.83 | 88.50 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:10 | 1931.70 | 20.96 | 108.50 | 312.67 | 1029.87 | 21.84 | 77.50 | 279.50 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:40 | 2157.92 | 21.05 | 99.00 | 289.00 | 1145.63 | 21.92 | 71.17 | 264.33 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2407.33 | 21.08 | 112.17 | 325.33 | 1037.74 | 20.45 | 52.17 | 300.67 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:10 | 1991.34 | 19.21 | 84.17 | 329.83 | 1088.31 | 21.17 | 60.50 | 303.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-05:49 | 1749.42 | 19.47 | 98.00 | 340.50 | 921.45 | 20.66 | 67.33 | 306.33 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-06:40 | 1883.60 | 19.71 | 92.67 | 336.17 | 994.24 | 20.95 | 63.17 | 306.83 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:10 | 1552.26 | 18.13 | 86.67 | 338.33 | 809.68 | 20.22 | 64.67 | 300.67 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1755.65 | 18.79 | 86.00 | 338.33 | 936.37 | 20.67 | 60.33 | 307.33 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:10 | 1639.44 | 18.21 | 83.67 | 316.50 | 873.13 | 20.14 | 60.67 | 282.00 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-05:00 | 1662.14 | 18.75 | 86.17 | 318.83 | 868.62 | 20.49 | 60.50 | 285.00 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-06:30 | 1674.26 | 19.42 | 84.33 | 300.00 | 855.25 | 20.25 | 51.33 | 267.00 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:30 | 1873.36 | 21.04 | 112.50 | 304.33 | 880.27 | 20.66 | 56.00 | 273.67 |
Annual Sum or Average | 4292.33 | 0.50 | 1852.70 | 19.63 | 1133.83 | 3849.83 | 951.41 | 20.77 | 745.33 | 3476.50 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 1552.26 | 18.13 | 83.67 | 289.00 | 809.68 | 20.14 | 51.33 | 264.33 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2407.33 | 21.08 | 112.50 | 340.50 | 1145.63 | 21.92 | 77.50 | 307.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:09 | 782.12 | 12.56 | 0.00 | 300.83 | 479.56 | 15.99 | 0.00 | 252.50 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:30 | 862.19 | 13.16 | 0.00 | 281.17 | 530.41 | 16.58 | 0.00 | 248.00 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 984.75 | 14.11 | 0.00 | 325.17 | 604.26 | 17.53 | 0.00 | 295.17 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:40 | 1195.11 | 14.85 | 0.00 | 334.17 | 700.78 | 18.34 | 0.00 | 307.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1372.09 | 14.14 | 3.83 | 350.17 | 746.34 | 17.49 | 1.17 | 320.83 |
June | 370.50 | 0.49 | 0.48 | 01-JUN-06:00 | 1639.85 | 19.84 | 112.17 | 348.83 | 865.75 | 19.56 | 33.17 | 328.33 |
July | 383.17 | 0.50 | 0.48 | 01-JUL-06:30 | 1414.42 | 19.27 | 115.50 | 352.33 | 736.50 | 19.81 | 59.17 | 323.00 |
August | 369.33 | 0.49 | 0.48 | 01-AUG-06:10 | 1277.36 | 14.23 | 0.00 | 344.00 | 709.97 | 17.65 | 0.00 | 313.00 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-06:40 | 1040.03 | 13.16 | 0.00 | 315.50 | 584.91 | 16.46 | 0.00 | 280.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 921.71 | 12.94 | 0.00 | 312.17 | 526.38 | 16.29 | 0.00 | 267.83 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:19 | 827.86 | 12.67 | 0.00 | 290.17 | 484.78 | 16.05 | 0.00 | 244.17 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:10 | 760.03 | 12.24 | 0.00 | 294.17 | 460.59 | 15.65 | 0.00 | 244.00 |
Annual Sum or Average | 4292.33 | 0.51 | 1099.36 | 14.50 | 231.50 | 3848.67 | 623.35 | 17.32 | 93.50 | 3424.67 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 760.03 | 12.24 | 0.00 | 281.17 | 460.59 | 15.65 | 0.00 | 244.00 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1639.85 | 19.84 | 115.50 | 352.33 | 865.75 | 19.81 | 59.17 | 328.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-08:20 | 1992.57 | 21.17 | 109.33 | 311.50 | 1058.91 | 22.00 | 77.50 | 281.33 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:40 | 2240.28 | 21.08 | 102.33 | 285.50 | 964.67 | 20.33 | 46.67 | 260.50 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-08:09 | 2461.00 | 20.85 | 112.67 | 333.33 | 1055.61 | 20.17 | 50.67 | 305.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 2377.25 | 14.15 | 0.00 | 329.67 | 1044.30 | 17.61 | 0.00 | 302.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:00 | 1930.67 | 13.92 | 0.00 | 339.33 | 879.09 | 17.12 | 0.00 | 304.83 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:40 | 2146.28 | 14.37 | 0.00 | 335.33 | 962.98 | 17.68 | 0.00 | 306.17 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-07:19 | 1565.20 | 13.71 | 0.00 | 338.00 | 809.31 | 16.83 | 0.00 | 301.50 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-07:10 | 2001.79 | 14.54 | 8.50 | 336.17 | 912.70 | 17.31 | 0.00 | 304.67 |
September | 357.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1796.02 | 18.01 | 87.00 | 312.00 | 844.26 | 17.10 | 7.67 | 282.67 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-07:40 | 1732.93 | 20.14 | 103.33 | 316.67 | 906.65 | 21.18 | 72.67 | 285.17 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:40 | 1721.84 | 20.38 | 95.83 | 303.00 | 899.17 | 21.35 | 66.00 | 270.83 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-07:19 | 1786.12 | 20.58 | 102.83 | 308.83 | 952.88 | 21.46 | 71.83 | 277.50 |
Annual Sum or Average | 4292.33 | 0.50 | 1977.05 | 17.63 | 721.83 | 3849.33 | 939.71 | 19.12 | 393.00 | 3483.00 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1565.20 | 13.71 | 0.00 | 285.50 | 809.31 | 16.83 | 0.00 | 260.50 | |
Maximum of Months | 383.17 | 0.51 | 0.48 | 2461.00 | 21.17 | 112.67 | 339.33 | 1058.91 | 22.00 | 77.50 | 306.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.164597E+12 | 0.125407E+12 | 253726.17 | 02-JAN-05:12 | 156546.35 | 0.73 |
February | 0.00 | 0.00 | 0.167133E+12 | 0.126960E+12 | 248283.38 | 16-FEB-06:03 | 150553.62 | 0.84 |
March | 0.00 | 0.00 | 0.202867E+12 | 0.155677E+12 | 257446.16 | 13-MAR-04:02 | 157889.04 | 0.88 |
April | 0.00 | 0.00 | 0.213207E+12 | 0.159876E+12 | 262627.78 | 03-APR-03:02 | 161679.92 | 0.88 |
May | 0.00 | 0.00 | 0.207023E+12 | 0.142264E+12 | 263670.32 | 15-MAY-04:33 | 154797.33 | 0.81 |
June | 0.00 | 0.00 | 0.216901E+12 | 0.149187E+12 | 248722.08 | 10-JUN-05:02 | 152240.42 | 0.86 |
July | 0.00 | 0.00 | 0.202006E+12 | 0.142191E+12 | 251569.31 | 10-JUL-04:23 | 156656.70 | 0.86 |
August | 0.00 | 0.00 | 0.232225E+12 | 0.158956E+12 | 260260.13 | 14-AUG-04:23 | 157169.26 | 0.88 |
September | 0.00 | 0.00 | 0.183468E+12 | 0.124606E+12 | 258209.45 | 21-SEP-05:02 | 147120.03 | 0.78 |
October | 0.00 | 0.00 | 0.193836E+12 | 0.129757E+12 | 253364.03 | 26-OCT-05:02 | 147173.38 | 0.81 |
November | 0.00 | 0.00 | 0.194056E+12 | 0.135021E+12 | 250696.40 | 13-NOV-06:02 | 154055.67 | 0.85 |
December | 0.00 | 0.00 | 0.194296E+12 | 0.140685E+12 | 245326.00 | 30-DEC-06:03 | 145821.03 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.237162E+13 | 0.169059E+13 | 0.84 | |||
Minimum of Months | 0.00 | 0.00 | 0.164597E+12 | 0.124606E+12 | 245326.00 | 145821.03 | 0.73 | |
Maximum of Months | 0.00 | 0.00 | 0.232225E+12 | 0.159876E+12 | 263670.32 | 161679.92 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144400E+13 | 0.108894E+13 | 2571985.06 | 02-JAN-05:12 | 1442332.98 | 0.66 |
February | 0.00 | 0.00 | 0.138569E+13 | 0.105031E+13 | 2479961.66 | 16-FEB-06:03 | 1406116.77 | 0.70 |
March | 0.00 | 0.00 | 0.166297E+13 | 0.124741E+13 | 2456575.85 | 15-MAR-05:02 | 1345189.67 | 0.76 |
April | 0.00 | 0.00 | 0.169000E+13 | 0.119815E+13 | 2479989.09 | 14-APR-05:02 | 1401947.04 | 0.78 |
May | 0.00 | 0.00 | 0.187849E+13 | 0.124531E+13 | 2638846.33 | 22-MAY-05:02 | 1377472.03 | 0.75 |
June | 0.00 | 0.00 | 0.190242E+13 | 0.126379E+13 | 2536721.60 | 10-JUN-05:02 | 1413381.62 | 0.76 |
July | 0.00 | 0.00 | 0.159659E+13 | 0.110003E+13 | 2475821.88 | 27-JUL-05:02 | 1404500.76 | 0.71 |
August | 0.00 | 0.00 | 0.175502E+13 | 0.115210E+13 | 2590097.16 | 05-AUG-05:03 | 1317589.44 | 0.71 |
September | 0.00 | 0.00 | 0.161537E+13 | 0.106727E+13 | 2521765.12 | 27-SEP-05:03 | 1393295.79 | 0.71 |
October | 0.00 | 0.00 | 0.158222E+13 | 0.104118E+13 | 2521864.98 | 26-OCT-05:02 | 1358020.29 | 0.68 |
November | 0.00 | 0.00 | 0.149806E+13 | 0.104208E+13 | 2470639.93 | 13-NOV-06:02 | 1430866.38 | 0.66 |
December | 0.00 | 0.00 | 0.141488E+13 | 0.103229E+13 | 2471566.20 | 30-DEC-06:03 | 1371867.65 | 0.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.194257E+14 | 0.135289E+14 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.138569E+13 | 0.103229E+13 | 2456575.85 | 1317589.44 | 0.64 | |
Maximum of Months | 0.00 | 0.00 | 0.190242E+13 | 0.126379E+13 | 2638846.33 | 1442332.98 | 0.78 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.151412E+12 | 0.116014E+12 | 276042.06 | 02-JAN-05:12 | 151096.87 | 0.65 |
February | 0.00 | 0.00 | 0.147904E+12 | 0.114388E+12 | 262535.79 | 16-FEB-06:03 | 147724.08 | 0.69 |
March | 0.00 | 0.00 | 0.180994E+12 | 0.138915E+12 | 259276.19 | 15-MAR-05:02 | 140413.99 | 0.76 |
April | 0.00 | 0.00 | 0.185598E+12 | 0.135208E+12 | 261121.04 | 14-APR-05:02 | 148741.02 | 0.78 |
May | 0.00 | 0.00 | 0.203793E+12 | 0.138879E+12 | 281609.19 | 22-MAY-05:02 | 144857.35 | 0.75 |
June | 0.00 | 0.00 | 0.205693E+12 | 0.140803E+12 | 271715.03 | 10-JUN-05:02 | 148974.46 | 0.77 |
July | 0.00 | 0.00 | 0.171899E+12 | 0.121229E+12 | 261571.39 | 27-JUL-05:02 | 148818.64 | 0.72 |
August | 0.00 | 0.00 | 0.187109E+12 | 0.125754E+12 | 269894.56 | 12-AUG-05:02 | 147968.66 | 0.71 |
September | 0.00 | 0.00 | 0.173723E+12 | 0.117988E+12 | 271026.96 | 21-SEP-05:02 | 141471.22 | 0.72 |
October | 0.00 | 0.00 | 0.167211E+12 | 0.112493E+12 | 266670.63 | 26-OCT-05:02 | 142253.22 | 0.69 |
November | 0.00 | 0.00 | 0.158435E+12 | 0.112371E+12 | 259087.35 | 13-NOV-06:02 | 150153.75 | 0.66 |
December | 0.00 | 0.00 | 0.148596E+12 | 0.109956E+12 | 254936.26 | 18-DEC-06:02 | 148173.27 | 0.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.208237E+13 | 0.148400E+13 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.147904E+12 | 0.109956E+12 | 254936.26 | 140413.99 | 0.64 | |
Maximum of Months | 0.00 | 0.00 | 0.205693E+12 | 0.140803E+12 | 281609.19 | 151096.87 | 0.78 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.110559E+12 | 0.843706E+11 | 178847.95 | 02-JAN-05:12 | 77031.85 | 0.61 |
February | 0.00 | 0.00 | 0.101612E+12 | 0.772907E+11 | 180549.55 | 05-FEB-17:17 | 87418.10 | 0.61 |
March | 0.00 | 0.00 | 0.124816E+12 | 0.916782E+11 | 187187.13 | 27-MAR-00:53 | 83204.19 | 0.63 |
April | 0.00 | 0.00 | 0.134740E+12 | 0.897075E+11 | 200493.79 | 30-APR-16:40 | 86117.75 | 0.62 |
May | 0.00 | 0.00 | 0.151794E+12 | 0.919224E+11 | 206407.01 | 29-MAY-07:23 | 79557.82 | 0.64 |
June | 0.00 | 0.00 | 0.150431E+12 | 0.908182E+11 | 207026.04 | 11-JUN-16:11 | 87481.41 | 0.63 |
July | 0.00 | 0.00 | 0.126569E+12 | 0.855538E+11 | 184937.98 | 02-JUL-16:18 | 86110.11 | 0.61 |
August | 0.00 | 0.00 | 0.155493E+12 | 0.941780E+11 | 211158.84 | 13-AUG-13:52 | 84970.48 | 0.65 |
September | 0.00 | 0.00 | 0.133773E+12 | 0.827132E+11 | 205611.46 | 04-SEP-11:13 | 81370.34 | 0.62 |
October | 0.00 | 0.00 | 0.131669E+12 | 0.827978E+11 | 204625.10 | 09-OCT-11:52 | 85063.93 | 0.61 |
November | 0.00 | 0.00 | 0.122770E+12 | 0.823343E+11 | 201875.27 | 12-NOV-14:42 | 83817.70 | 0.61 |
December | 0.00 | 0.00 | 0.112872E+12 | 0.831961E+11 | 192872.79 | 10-DEC-21:27 | 82187.08 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.155710E+13 | 0.103656E+13 | 0.62 | |||
Minimum of Months | 0.00 | 0.00 | 0.101612E+12 | 0.772907E+11 | 178847.95 | 77031.85 | 0.60 | |
Maximum of Months | 0.00 | 0.00 | 0.155493E+12 | 0.941780E+11 | 211158.84 | 87481.41 | 0.65 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.358908E+12 | 0.337364E+12 | 141836.22 | 11-JAN-17:00 | 129263.07 | 0.00 |
February | 0.00 | 0.00 | 0.547228E+12 | 0.526326E+12 | 235242.02 | 15-FEB-14:40 | 220877.11 | 0.00 |
March | 0.00 | 0.00 | 0.854154E+12 | 0.829344E+12 | 401314.32 | 31-MAR-24:00 | 392357.66 | 0.00 |
April | 0.00 | 0.00 | 0.105619E+13 | 0.102896E+13 | 422621.44 | 14-APR-16:00 | 404757.41 | 0.00 |
May | 0.00 | 0.00 | 0.377096E+12 | 0.341648E+12 | 227862.55 | 31-MAY-23:05 | 210632.04 | 0.00 |
June | 0.00 | 0.00 | 0.602660E+12 | 0.566637E+12 | 318824.12 | 30-JUN-23:05 | 302436.58 | 0.00 |
July | 0.00 | 0.00 | 0.857738E+12 | 0.828970E+12 | 406059.45 | 31-JUL-23:10 | 392667.62 | 0.00 |
August | 0.00 | 0.00 | 0.109782E+13 | 0.106458E+13 | 426182.78 | 07-AUG-15:00 | 402548.68 | 0.00 |
September | 0.00 | 0.00 | 0.360908E+12 | 0.329052E+12 | 229759.93 | 30-SEP-23:05 | 211161.09 | 0.00 |
October | 0.00 | 0.00 | 0.615438E+12 | 0.582386E+12 | 317076.85 | 31-OCT-23:05 | 302342.43 | 0.00 |
November | 0.00 | 0.00 | 0.829028E+12 | 0.800879E+12 | 328737.22 | 14-NOV-16:10 | 312447.47 | 0.00 |
December | 0.00 | 0.00 | 0.108976E+13 | 0.106719E+13 | 416524.27 | 05-DEC-21:00 | 401807.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.864693E+13 | 0.830334E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.358908E+12 | 0.329052E+12 | 141836.22 | 129263.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109782E+13 | 0.106719E+13 | 426182.78 | 404757.41 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.693816E+10 | 0.606384E+10 | 3122.71 | 16-JAN-17:32 | 2868.11 | 0.00 |
February | 0.00 | 0.00 | 0.109618E+11 | 0.100698E+11 | 5063.51 | 20-FEB-17:12 | 4709.39 | 0.00 |
March | 0.00 | 0.00 | 0.173627E+11 | 0.162617E+11 | 8384.72 | 31-MAR-23:03 | 7774.54 | 0.00 |
April | 0.00 | 0.00 | 0.220232E+11 | 0.206941E+11 | 8833.54 | 09-APR-15:57 | 8232.64 | 0.00 |
May | 0.00 | 0.00 | 0.769713E+10 | 0.622164E+10 | 4727.31 | 31-MAY-23:05 | 3949.58 | 0.00 |
June | 0.00 | 0.00 | 0.124598E+11 | 0.109005E+11 | 6535.89 | 30-JUN-23:05 | 5807.63 | 0.00 |
July | 0.00 | 0.00 | 0.174509E+11 | 0.161731E+11 | 8368.51 | 31-JUL-23:10 | 7727.89 | 0.00 |
August | 0.00 | 0.00 | 0.227921E+11 | 0.212045E+11 | 8975.13 | 07-AUG-15:00 | 8101.70 | 0.00 |
September | 0.00 | 0.00 | 0.721062E+10 | 0.589417E+10 | 4795.08 | 30-SEP-23:05 | 3971.61 | 0.00 |
October | 0.00 | 0.00 | 0.124874E+11 | 0.110652E+11 | 6481.11 | 31-OCT-23:05 | 5805.15 | 0.00 |
November | 0.00 | 0.00 | 0.168423E+11 | 0.155935E+11 | 6998.12 | 20-NOV-17:00 | 6430.75 | 0.00 |
December | 0.00 | 0.00 | 0.222548E+11 | 0.211786E+11 | 8803.74 | 25-DEC-18:03 | 8279.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.176481E+12 | 0.161321E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.693816E+10 | 0.589417E+10 | 3122.71 | 2868.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.227921E+11 | 0.212045E+11 | 8975.13 | 8279.47 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.652001E+11 | 0.565592E+11 | 29315.70 | 16-JAN-17:32 | 26793.04 | 0.00 |
February | 0.00 | 0.00 | 0.104632E+12 | 0.957482E+11 | 48132.01 | 13-FEB-17:00 | 42636.62 | 0.00 |
March | 0.00 | 0.00 | 0.165850E+12 | 0.154859E+12 | 80987.68 | 31-MAR-23:03 | 74826.82 | 0.00 |
April | 0.00 | 0.00 | 0.208806E+12 | 0.195500E+12 | 84014.59 | 20-APR-16:00 | 76688.24 | 0.00 |
May | 0.00 | 0.00 | 0.726226E+11 | 0.580203E+11 | 46242.00 | 31-MAY-23:05 | 38229.97 | 0.00 |
June | 0.00 | 0.00 | 0.118980E+12 | 0.103452E+12 | 62597.30 | 30-JUN-23:05 | 55201.18 | 0.00 |
July | 0.00 | 0.00 | 0.166548E+12 | 0.153795E+12 | 80765.01 | 31-JUL-23:10 | 74274.78 | 0.00 |
August | 0.00 | 0.00 | 0.216686E+12 | 0.200807E+12 | 85729.93 | 07-AUG-15:00 | 77077.69 | 0.00 |
September | 0.00 | 0.00 | 0.677081E+11 | 0.546981E+11 | 46753.02 | 30-SEP-23:05 | 38361.02 | 0.00 |
October | 0.00 | 0.00 | 0.118861E+12 | 0.104707E+12 | 62233.57 | 31-OCT-23:05 | 55334.81 | 0.00 |
November | 0.00 | 0.00 | 0.160955E+12 | 0.148490E+12 | 66804.19 | 20-NOV-17:00 | 61149.15 | 0.00 |
December | 0.00 | 0.00 | 0.211973E+12 | 0.201205E+12 | 83773.17 | 25-DEC-18:03 | 78512.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167882E+13 | 0.152784E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.652001E+11 | 0.546981E+11 | 29315.70 | 26793.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216686E+12 | 0.201205E+12 | 85729.93 | 78512.64 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.658385E+10 | 0.571930E+10 | 3176.07 | 16-JAN-17:32 | 2918.75 | 0.00 |
February | 0.00 | 0.00 | 0.105482E+11 | 0.965996E+10 | 5048.70 | 20-FEB-16:52 | 4677.68 | 0.00 |
March | 0.00 | 0.00 | 0.167087E+11 | 0.156102E+11 | 8116.39 | 31-MAR-23:03 | 7501.38 | 0.00 |
April | 0.00 | 0.00 | 0.210505E+11 | 0.197200E+11 | 8532.77 | 09-APR-15:57 | 7920.03 | 0.00 |
May | 0.00 | 0.00 | 0.741314E+10 | 0.594826E+10 | 4626.79 | 31-MAY-23:05 | 3827.20 | 0.00 |
June | 0.00 | 0.00 | 0.120310E+11 | 0.104774E+11 | 6216.33 | 30-JUN-23:05 | 5475.83 | 0.00 |
July | 0.00 | 0.00 | 0.167770E+11 | 0.155024E+11 | 8072.26 | 31-JUL-23:10 | 7423.95 | 0.00 |
August | 0.00 | 0.00 | 0.217958E+11 | 0.202078E+11 | 8657.11 | 07-AUG-14:50 | 7787.79 | 0.00 |
September | 0.00 | 0.00 | 0.690058E+10 | 0.559558E+10 | 4701.22 | 30-SEP-23:05 | 3872.19 | 0.00 |
October | 0.00 | 0.00 | 0.119800E+11 | 0.105647E+11 | 6213.75 | 31-OCT-23:05 | 5524.63 | 0.00 |
November | 0.00 | 0.00 | 0.161732E+11 | 0.149277E+11 | 6920.90 | 19-NOV-16:44 | 6423.29 | 0.00 |
December | 0.00 | 0.00 | 0.212610E+11 | 0.201853E+11 | 8543.46 | 25-DEC-18:03 | 8016.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169223E+12 | 0.154119E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.658385E+10 | 0.559558E+10 | 3176.07 | 2918.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217958E+11 | 0.202078E+11 | 8657.11 | 8016.22 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 732838.86 | 3366508.84 | 02-JAN-05:13 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 777392.33 | 2916877.64 | 06-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 855455.78 | 2707091.22 | 15-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 905200.78 | 2452039.53 | 14-APR-05:04 | 0.00 | 0.00 | 01-APR-00:10 |
May | 963001.37 | 3346908.33 | 22-MAY-05:04 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1007706.06 | 2783887.12 | 28-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 833903.89 | 2687611.51 | 18-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 919978.04 | 2974869.70 | 21-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 861045.31 | 3113951.33 | 18-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 824964.87 | 3517122.40 | 23-OCT-04:15 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 806383.93 | 3203786.00 | 13-NOV-06:04 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 742072.16 | 3186067.02 | 18-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 852645.84 | 0.00 | ||||
Minimum of Months | 732838.86 | 2452039.53 | 0.00 | 0.00 | ||
Maximum of Months | 1007706.06 | 3517122.40 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 753783.88 | 4104826.29 | 02-JAN-05:12 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 787844.35 | 4129490.53 | 06-FEB-05:12 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 854894.82 | 4088758.09 | 25-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 903926.13 | 4155498.32 | 10-APR-03:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 961443.05 | 4181401.07 | 16-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1005895.06 | 4037172.55 | 13-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 833790.40 | 4062374.21 | 28-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 916603.88 | 4132456.66 | 07-AUG-03:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 860724.67 | 4097682.06 | 19-SEP-04:12 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 824158.06 | 4419026.60 | 23-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 809516.14 | 4027812.32 | 06-NOV-05:12 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 765369.80 | 3980119.13 | 11-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 856637.98 | 0.00 | ||||
Minimum of Months | 753783.88 | 3980119.13 | 0.00 | 0.00 | ||
Maximum of Months | 1005895.06 | 4419026.60 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 708636.48 | 1124821.64 | 04-JAN-13:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 980923.89 | 1409663.94 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1244617.96 | 1699225.07 | 21-MAR-13:10 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 1498220.85 | 1832624.55 | 01-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 862339.61 | 1308860.60 | 06-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1071401.38 | 1484438.74 | 13-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1187392.76 | 1526509.61 | 21-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1412917.12 | 1768833.12 | 13-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 782227.03 | 1135632.80 | 06-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 956780.62 | 1303949.47 | 04-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1155158.23 | 1565328.44 | 18-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1316946.88 | 1702900.20 | 08-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1098779.91 | 0.00 | ||||
Minimum of Months | 708636.48 | 1124821.64 | 0.00 | 0.00 | ||
Maximum of Months | 1498220.85 | 1832624.55 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 10117.63 | 32719.37 | 17-JAN-12:53 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 10112.61 | 32582.79 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 10509.53 | 32246.73 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9752.05 | 31589.77 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 9845.99 | 31019.35 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9919.13 | 30373.45 | 02-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9202.38 | 30111.21 | 24-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10000.07 | 30470.93 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 9604.42 | 31090.15 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 9773.89 | 31793.31 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10070.36 | 32335.62 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9875.89 | 32690.98 | 26-DEC-12:25 |
Annual Sum or Average | 0.00 | 9897.59 | ||||
Minimum of Months | 0.00 | 0.00 | 9202.38 | 30111.21 | ||
Maximum of Months | 0.00 | 0.00 | 10509.53 | 32719.37 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1796027.31 | 6323073.51 | 12-JAN-13:05 | 0.45 | 4050.82 | 23-JAN-01:55 |
February | 2036568.99 | 6343108.54 | 07-FEB-13:05 | 0.33 | 2659.86 | 10-FEB-01:20 |
March | 2411158.18 | 6126363.37 | 27-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 3050945.73 | 7118913.47 | 10-APR-12:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 3385901.61 | 7237339.64 | 01-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3549442.68 | 6890576.18 | 28-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 2525788.97 | 6586939.84 | 27-JUL-12:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 3209937.21 | 7083745.93 | 22-AUG-12:05 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2945415.41 | 7062012.08 | 07-SEP-12:05 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 2720936.03 | 6843833.65 | 06-OCT-12:05 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 2462755.54 | 6582025.34 | 17-NOV-13:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1923846.40 | 6380458.01 | 12-DEC-13:05 | 5.01 | 8557.06 | 21-DEC-03:50 |
Annual Sum or Average | 2669759.40 | 0.49 | ||||
Minimum of Months | 1796027.31 | 6126363.37 | 0.00 | 0.00 | ||
Maximum of Months | 3549442.68 | 7237339.64 | 5.01 | 8557.06 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151002E+11 | 0.88 | 8802.55 | 01-JAN-00:15 | 1.37 |
February | 0.134121E+11 | 0.86 | 8802.55 | 01-FEB-04:02 | 1.38 |
March | 0.152222E+11 | 0.89 | 8802.55 | 01-MAR-04:02 | 1.38 |
April | 0.145434E+11 | 0.87 | 8802.55 | 01-APR-03:03 | 1.38 |
May | 0.153095E+11 | 0.89 | 8802.55 | 01-MAY-00:03 | 1.36 |
June | 0.147916E+11 | 0.89 | 8802.55 | 01-JUN-03:22 | 1.38 |
July | 0.147216E+11 | 0.86 | 8802.55 | 01-JUL-03:03 | 1.38 |
August | 0.156084E+11 | 0.91 | 8802.55 | 01-AUG-03:02 | 1.38 |
September | 0.145305E+11 | 0.87 | 8802.55 | 01-SEP-03:02 | 1.38 |
October | 0.148109E+11 | 0.86 | 8802.55 | 01-OCT-15:40 | 1.36 |
November | 0.143906E+11 | 0.87 | 8802.55 | 01-NOV-03:03 | 1.38 |
December | 0.145606E+11 | 0.85 | 8802.55 | 01-DEC-05:12 | 1.38 |
Annual Sum or Average | 0.177002E+12 | 0.87 | |||
Minimum of Months | 0.134121E+11 | 0.85 | 8802.55 | 1.36 | |
Maximum of Months | 0.156084E+11 | 0.91 | 8802.55 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.885461E+10 | 0.53 | 19474.16 | 02-JAN-05:53 | 1.75 |
February | 0.902731E+10 | 0.61 | 19474.16 | 01-FEB-05:12 | 1.75 |
March | 0.129758E+11 | 0.71 | 19474.16 | 03-MAR-06:02 | 1.76 |
April | 0.150498E+11 | 0.77 | 19474.16 | 03-APR-03:02 | 1.76 |
May | 0.117340E+11 | 0.65 | 19474.16 | 01-MAY-04:03 | 1.75 |
June | 0.118697E+11 | 0.68 | 19474.16 | 12-JUN-05:03 | 1.75 |
July | 0.122156E+11 | 0.68 | 19474.16 | 01-JUL-05:02 | 1.76 |
August | 0.150115E+11 | 0.76 | 19474.16 | 01-AUG-05:03 | 1.75 |
September | 0.103218E+11 | 0.60 | 19474.16 | 01-SEP-05:02 | 1.75 |
October | 0.104491E+11 | 0.61 | 19474.16 | 03-OCT-05:02 | 1.75 |
November | 0.102025E+11 | 0.63 | 19474.16 | 02-NOV-05:02 | 1.75 |
December | 0.105059E+11 | 0.64 | 19474.16 | 01-DEC-06:02 | 1.75 |
Annual Sum or Average | 0.138218E+12 | 0.66 | |||
Minimum of Months | 0.885461E+10 | 0.53 | 19474.16 | 1.75 | |
Maximum of Months | 0.150498E+11 | 0.77 | 19474.16 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.734847E+11 | 0.47 | 182472.88 | 02-JAN-05:12 | 1.76 |
February | 0.710865E+11 | 0.51 | 182472.88 | 01-FEB-04:02 | 1.75 |
March | 0.960016E+11 | 0.58 | 182472.88 | 01-MAR-04:02 | 1.75 |
April | 0.974687E+11 | 0.60 | 182472.88 | 01-APR-05:02 | 1.75 |
May | 0.983646E+11 | 0.59 | 182472.88 | 01-MAY-05:02 | 1.76 |
June | 0.947623E+11 | 0.59 | 182472.88 | 01-JUN-03:22 | 1.75 |
July | 0.868428E+11 | 0.54 | 182472.88 | 01-JUL-05:02 | 1.76 |
August | 0.961961E+11 | 0.56 | 182472.88 | 01-AUG-03:02 | 1.75 |
September | 0.852340E+11 | 0.54 | 182472.88 | 01-SEP-05:02 | 1.75 |
October | 0.795775E+11 | 0.50 | 182472.88 | 02-OCT-03:02 | 1.75 |
November | 0.733203E+11 | 0.48 | 182472.88 | 01-NOV-05:02 | 1.75 |
December | 0.690741E+11 | 0.45 | 182472.88 | 01-DEC-06:02 | 1.75 |
Annual Sum or Average | 0.102141E+13 | 0.54 | |||
Minimum of Months | 0.690741E+11 | 0.45 | 182472.88 | 1.75 | |
Maximum of Months | 0.983646E+11 | 0.60 | 182472.88 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.779073E+10 | 0.47 | 19840.70 | 02-JAN-05:12 | 1.76 |
February | 0.780106E+10 | 0.51 | 19840.70 | 01-FEB-05:12 | 1.75 |
March | 0.108379E+11 | 0.59 | 19840.70 | 01-MAR-04:02 | 1.75 |
April | 0.109425E+11 | 0.61 | 19840.70 | 01-APR-05:02 | 1.75 |
May | 0.109963E+11 | 0.60 | 19840.70 | 01-MAY-04:03 | 1.75 |
June | 0.107790E+11 | 0.61 | 19840.70 | 02-JUN-03:02 | 1.75 |
July | 0.943595E+10 | 0.54 | 19840.70 | 01-JUL-05:02 | 1.76 |
August | 0.102320E+11 | 0.56 | 19840.70 | 01-AUG-05:03 | 1.75 |
September | 0.927832E+10 | 0.54 | 19840.70 | 02-SEP-05:03 | 1.76 |
October | 0.848818E+10 | 0.50 | 19840.70 | 02-OCT-03:02 | 1.75 |
November | 0.797900E+10 | 0.49 | 19840.70 | 01-NOV-05:02 | 1.75 |
December | 0.729671E+10 | 0.45 | 19840.70 | 01-DEC-06:02 | 1.75 |
Annual Sum or Average | 0.111858E+12 | 0.54 | |||
Minimum of Months | 0.729671E+10 | 0.45 | 19840.70 | 1.75 | |
Maximum of Months | 0.109963E+11 | 0.61 | 19840.70 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.944961E+11 | 1.35 | 35280.79 | 01-JAN-00:05 | 1.35 |
February | 0.853513E+11 | 1.35 | 35280.79 | 01-FEB-00:03 | 1.35 |
March | 0.944961E+11 | 1.35 | 35280.79 | 01-MAR-00:05 | 1.35 |
April | 0.914478E+11 | 1.35 | 35280.79 | 01-APR-00:10 | 1.35 |
May | 0.944961E+11 | 1.35 | 35280.79 | 01-MAY-00:03 | 1.35 |
June | 0.914478E+11 | 1.35 | 35280.79 | 01-JUN-00:05 | 1.35 |
July | 0.944961E+11 | 1.35 | 35280.79 | 01-JUL-00:10 | 1.35 |
August | 0.944961E+11 | 1.35 | 35280.79 | 01-AUG-00:03 | 1.35 |
September | 0.914478E+11 | 1.35 | 35280.79 | 01-SEP-00:10 | 1.35 |
October | 0.944961E+11 | 1.35 | 35280.79 | 01-OCT-00:05 | 1.35 |
November | 0.914478E+11 | 1.35 | 35280.79 | 01-NOV-00:05 | 1.35 |
December | 0.944961E+11 | 1.35 | 35280.79 | 01-DEC-00:05 | 1.35 |
Annual Sum or Average | 0.111261E+13 | 1.35 | |||
Minimum of Months | 0.853513E+11 | 1.35 | 35280.79 | 1.35 | |
Maximum of Months | 0.944961E+11 | 1.35 | 35280.79 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138171E+10 | 0.91 | 515.87 | 01-JAN-00:05 | 0.91 |
February | 0.124800E+10 | 0.91 | 515.87 | 01-FEB-00:03 | 0.91 |
March | 0.138171E+10 | 0.91 | 515.87 | 01-MAR-00:05 | 0.91 |
April | 0.133714E+10 | 0.91 | 515.87 | 01-APR-00:10 | 0.91 |
May | 0.138171E+10 | 0.91 | 515.87 | 01-MAY-00:03 | 0.91 |
June | 0.133714E+10 | 0.91 | 515.87 | 01-JUN-00:05 | 0.91 |
July | 0.138171E+10 | 0.91 | 515.87 | 01-JUL-00:10 | 0.91 |
August | 0.138171E+10 | 0.91 | 515.87 | 01-AUG-00:03 | 0.91 |
September | 0.133714E+10 | 0.91 | 515.87 | 01-SEP-00:10 | 0.91 |
October | 0.138171E+10 | 0.91 | 515.87 | 01-OCT-00:05 | 0.91 |
November | 0.133714E+10 | 0.91 | 515.87 | 01-NOV-00:05 | 0.91 |
December | 0.138171E+10 | 0.91 | 515.87 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.162685E+11 | 0.91 | |||
Minimum of Months | 0.124800E+10 | 0.91 | 515.87 | 0.91 | |
Maximum of Months | 0.138171E+10 | 0.91 | 515.87 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131704E+11 | 0.91 | 4917.26 | 01-JAN-00:10 | 0.91 |
February | 0.118958E+11 | 0.91 | 4917.26 | 01-FEB-00:03 | 0.91 |
March | 0.131704E+11 | 0.91 | 4917.26 | 01-MAR-00:05 | 0.91 |
April | 0.127455E+11 | 0.91 | 4917.26 | 01-APR-00:10 | 0.91 |
May | 0.131704E+11 | 0.91 | 4917.26 | 01-MAY-00:03 | 0.91 |
June | 0.127455E+11 | 0.91 | 4917.26 | 01-JUN-00:05 | 0.91 |
July | 0.131704E+11 | 0.91 | 4917.26 | 01-JUL-00:10 | 0.91 |
August | 0.131704E+11 | 0.91 | 4917.26 | 01-AUG-00:03 | 0.91 |
September | 0.127455E+11 | 0.91 | 4917.26 | 01-SEP-00:10 | 0.91 |
October | 0.131704E+11 | 0.91 | 4917.26 | 01-OCT-00:05 | 0.91 |
November | 0.127455E+11 | 0.91 | 4917.26 | 01-NOV-00:05 | 0.91 |
December | 0.131704E+11 | 0.91 | 4917.26 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.155071E+12 | 0.91 | |||
Minimum of Months | 0.118958E+11 | 0.91 | 4917.26 | 0.91 | |
Maximum of Months | 0.131704E+11 | 0.91 | 4917.26 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134250E+10 | 0.91 | 501.23 | 01-JAN-00:05 | 0.91 |
February | 0.121258E+10 | 0.91 | 501.23 | 01-FEB-00:03 | 0.91 |
March | 0.134250E+10 | 0.91 | 501.23 | 01-MAR-00:05 | 0.91 |
April | 0.129919E+10 | 0.91 | 501.23 | 01-APR-00:10 | 0.91 |
May | 0.134250E+10 | 0.91 | 501.23 | 01-MAY-00:03 | 0.91 |
June | 0.129919E+10 | 0.91 | 501.23 | 01-JUN-00:05 | 0.91 |
July | 0.134250E+10 | 0.91 | 501.23 | 01-JUL-00:10 | 0.91 |
August | 0.134250E+10 | 0.91 | 501.23 | 01-AUG-00:03 | 0.91 |
September | 0.129919E+10 | 0.91 | 501.23 | 01-SEP-00:10 | 0.91 |
October | 0.134250E+10 | 0.91 | 501.23 | 01-OCT-00:05 | 0.91 |
November | 0.129919E+10 | 0.91 | 501.23 | 01-NOV-00:05 | 0.91 |
December | 0.134250E+10 | 0.91 | 501.23 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.158069E+11 | 0.91 | |||
Minimum of Months | 0.121258E+10 | 0.91 | 501.23 | 0.91 | |
Maximum of Months | 0.134250E+10 | 0.91 | 501.23 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 60.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 60.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 60.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 60.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 60.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 60.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 60.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 60.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 60.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 60.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 60.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 60.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 0.00 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.221341E+10 | 0.201199E+10 | 13652.32 | 02-JAN-05:12 | 12409.96 | 12409.96 | 6.72 | 83.95 |
February | 0.190580E+10 | 0.173237E+10 | 13652.32 | 01-FEB-05:12 | 12409.96 | 12409.96 | 9.62 | 83.95 |
March | 0.178288E+10 | 0.162064E+10 | 13652.32 | 01-MAR-06:02 | 12409.96 | 12409.96 | 9.90 | 83.95 |
April | 0.170069E+10 | 0.154593E+10 | 13652.32 | 01-APR-05:02 | 12409.96 | 12409.96 | 9.91 | 83.95 |
May | 0.207502E+10 | 0.188619E+10 | 13652.32 | 01-MAY-04:03 | 12409.96 | 12409.96 | 10.17 | 83.95 |
June | 0.237862E+10 | 0.216217E+10 | 13652.32 | 01-JUN-05:03 | 12409.96 | 12409.96 | 10.74 | 83.95 |
July | 0.161743E+10 | 0.147024E+10 | 13652.32 | 01-JUL-05:02 | 12409.96 | 12409.96 | 6.73 | 83.95 |
August | 0.188124E+10 | 0.171004E+10 | 13652.32 | 01-AUG-05:03 | 12409.96 | 12409.96 | 10.41 | 83.95 |
September | 0.161683E+10 | 0.146970E+10 | 13652.32 | 01-SEP-05:02 | 12409.96 | 12409.96 | 9.93 | 83.95 |
October | 0.166022E+10 | 0.150914E+10 | 13652.32 | 02-OCT-05:02 | 12409.96 | 12409.96 | 6.72 | 83.95 |
November | 0.188252E+10 | 0.171121E+10 | 13652.32 | 01-NOV-05:02 | 12409.96 | 12409.96 | 9.92 | 83.95 |
December | 0.225170E+10 | 0.204680E+10 | 13652.32 | 01-DEC-05:12 | 12409.96 | 12409.96 | 9.52 | 83.95 |
Annual Sum or Average | 0.229664E+11 | 0.208764E+11 | ||||||
Minimum of Months | 0.161683E+10 | 0.146970E+10 | 13652.32 | 12409.96 | 12409.96 | 6.72 | 83.95 | |
Maximum of Months | 0.237862E+10 | 0.216217E+10 | 13652.32 | 12409.96 | 12409.96 | 10.74 | 83.95 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.990957E+10 | 0.900780E+10 | 4698.26 | 01-JAN-00:15 | 4270.72 | 4270.72 | 7.20 | 41.98 |
February | 0.102475E+11 | 0.931495E+10 | 4698.26 | 01-FEB-00:03 | 4270.72 | 4270.72 | 8.25 | 41.98 |
March | 0.117788E+11 | 0.107069E+11 | 4698.26 | 01-MAR-00:05 | 4270.72 | 4270.72 | 8.26 | 41.98 |
April | 0.116302E+11 | 0.105719E+11 | 4698.26 | 01-APR-00:10 | 4270.72 | 4270.72 | 7.00 | 41.98 |
May | 0.111065E+11 | 0.100958E+11 | 4698.26 | 01-MAY-00:03 | 4270.72 | 4270.72 | 9.75 | 41.98 |
June | 0.112161E+11 | 0.101954E+11 | 4698.26 | 01-JUN-00:15 | 4270.72 | 4270.72 | 7.10 | 41.98 |
July | 0.116229E+11 | 0.105652E+11 | 4698.26 | 01-JUL-01:05 | 4270.72 | 4270.72 | 7.10 | 41.98 |
August | 0.117390E+11 | 0.106707E+11 | 4698.26 | 01-AUG-00:15 | 4270.72 | 4270.72 | 7.13 | 41.98 |
September | 0.103681E+11 | 0.942462E+10 | 4698.26 | 01-SEP-00:10 | 4270.72 | 4270.72 | 7.01 | 41.98 |
October | 0.109080E+11 | 0.991537E+10 | 4698.26 | 01-OCT-00:05 | 4270.72 | 4270.72 | 7.09 | 41.98 |
November | 0.109773E+11 | 0.997836E+10 | 4698.26 | 01-NOV-00:05 | 4270.72 | 4270.72 | 7.10 | 41.98 |
December | 0.115019E+11 | 0.104552E+11 | 4698.26 | 01-DEC-00:25 | 4270.72 | 4270.72 | 7.08 | 41.98 |
Annual Sum or Average | 0.133006E+12 | 0.120902E+12 | ||||||
Minimum of Months | 0.990957E+10 | 0.900780E+10 | 4698.26 | 4270.72 | 4270.72 | 7.00 | 41.98 | |
Maximum of Months | 0.117788E+11 | 0.107069E+11 | 4698.26 | 4270.72 | 4270.72 | 9.75 | 41.98 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.262690E+10 | 0.238785E+10 | 4698.26 | 02-JAN-05:12 | 4270.72 | 4270.72 | 12.73 | 41.98 |
February | 0.249496E+10 | 0.226792E+10 | 4698.26 | 01-FEB-08:50 | 4270.72 | 4270.72 | 15.24 | 20.99 |
March | 0.299749E+10 | 0.272472E+10 | 4698.26 | 01-MAR-08:20 | 4270.72 | 4270.72 | 15.12 | 20.99 |
April | 0.306919E+10 | 0.278989E+10 | 4698.26 | 03-APR-07:10 | 4270.72 | 4270.72 | 15.50 | 20.99 |
May | 0.378285E+10 | 0.343861E+10 | 4698.26 | 01-MAY-05:02 | 4270.72 | 4270.72 | 14.60 | 41.98 |
June | 0.421011E+10 | 0.382699E+10 | 4698.26 | 01-JUN-04:43 | 4270.72 | 4270.72 | 15.36 | 20.99 |
July | 0.270047E+10 | 0.245472E+10 | 4698.26 | 01-JUL-05:02 | 4270.72 | 4270.72 | 14.13 | 41.98 |
August | 0.382518E+10 | 0.347709E+10 | 4698.26 | 01-AUG-05:05 | 4270.72 | 4270.72 | 16.27 | 20.99 |
September | 0.294186E+10 | 0.267415E+10 | 4698.26 | 01-SEP-07:10 | 4270.72 | 4270.72 | 15.29 | 20.99 |
October | 0.293904E+10 | 0.267159E+10 | 4698.26 | 02-OCT-05:02 | 4270.72 | 4270.72 | 12.87 | 41.98 |
November | 0.290456E+10 | 0.264024E+10 | 4698.26 | 01-NOV-05:04 | 4270.72 | 4270.72 | 15.87 | 20.99 |
December | 0.241909E+10 | 0.219896E+10 | 4698.26 | 01-DEC-06:04 | 4270.72 | 4270.72 | 15.70 | 20.99 |
Annual Sum or Average | 0.369117E+11 | 0.335527E+11 | ||||||
Minimum of Months | 0.241909E+10 | 0.219896E+10 | 4698.26 | 4270.72 | 4270.72 | 12.73 | 20.99 | |
Maximum of Months | 0.421011E+10 | 0.382699E+10 | 4698.26 | 4270.72 | 4270.72 | 16.27 | 41.98 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.900343E+10 | 0.818412E+10 | 3361.50 | 01-JAN-00:05 | 3055.60 | 3055.60 | 31.20 | 14.18 |
February | 0.813213E+10 | 0.739211E+10 | 3361.50 | 01-FEB-00:03 | 3055.60 | 3055.60 | 34.78 | 14.18 |
March | 0.900343E+10 | 0.818412E+10 | 3361.50 | 01-MAR-00:05 | 3055.60 | 3055.60 | 39.02 | 14.18 |
April | 0.871300E+10 | 0.792011E+10 | 3361.50 | 01-APR-00:10 | 3055.60 | 3055.60 | 46.06 | 14.18 |
May | 0.900343E+10 | 0.818412E+10 | 3361.50 | 01-MAY-00:03 | 3055.60 | 3055.60 | 35.87 | 14.18 |
June | 0.871300E+10 | 0.792011E+10 | 3361.50 | 01-JUN-00:05 | 3055.60 | 3055.60 | 34.20 | 14.18 |
July | 0.900343E+10 | 0.818412E+10 | 3361.50 | 01-JUL-00:10 | 3055.60 | 3055.60 | 39.70 | 14.18 |
August | 0.900343E+10 | 0.818412E+10 | 3361.50 | 01-AUG-00:03 | 3055.60 | 3055.60 | 44.07 | 14.18 |
September | 0.871300E+10 | 0.792011E+10 | 3361.50 | 01-SEP-00:10 | 3055.60 | 3055.60 | 33.50 | 14.18 |
October | 0.900343E+10 | 0.818412E+10 | 3361.50 | 01-OCT-00:05 | 3055.60 | 3055.60 | 36.60 | 14.18 |
November | 0.871300E+10 | 0.792011E+10 | 3361.50 | 01-NOV-00:05 | 3055.60 | 3055.60 | 39.53 | 14.18 |
December | 0.900343E+10 | 0.818412E+10 | 3361.50 | 01-DEC-00:05 | 3055.60 | 3055.60 | 40.77 | 14.18 |
Annual Sum or Average | 0.106008E+12 | 0.963614E+11 | ||||||
Minimum of Months | 0.813213E+10 | 0.739211E+10 | 3361.50 | 3055.60 | 3055.60 | 31.20 | 14.18 | |
Maximum of Months | 0.900343E+10 | 0.818412E+10 | 3361.50 | 3055.60 | 3055.60 | 46.06 | 14.18 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.91 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 57.82 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 57.07 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.54 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.81 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.16 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.89 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.66 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.16 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 56.53 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.11 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 56.59 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.53 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.82 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.465777E+11 | 0.423392E+11 | 35669.72 | 02-JAN-05:15 | 32423.77 | 32423.77 | 29.88 | 145.13 |
February | 0.478025E+11 | 0.434525E+11 | 35669.72 | 01-FEB-15:10 | 32423.77 | 32423.77 | 28.82 | 145.13 |
March | 0.551451E+11 | 0.501269E+11 | 35669.72 | 01-MAR-12:20 | 32423.77 | 32423.77 | 28.91 | 145.13 |
April | 0.547888E+11 | 0.498030E+11 | 35669.72 | 03-APR-07:10 | 32423.77 | 32423.77 | 30.12 | 145.13 |
May | 0.550882E+11 | 0.500752E+11 | 35669.72 | 01-MAY-05:02 | 32423.77 | 32423.77 | 32.21 | 145.13 |
June | 0.568988E+11 | 0.517210E+11 | 35669.72 | 01-JUN-04:43 | 32423.77 | 32423.77 | 29.00 | 145.13 |
July | 0.534547E+11 | 0.485903E+11 | 35669.72 | 01-JUL-05:04 | 32423.77 | 32423.77 | 30.40 | 145.13 |
August | 0.575135E+11 | 0.522798E+11 | 35669.72 | 01-AUG-05:05 | 32423.77 | 32423.77 | 29.04 | 145.13 |
September | 0.497755E+11 | 0.452460E+11 | 35669.72 | 01-SEP-07:10 | 32423.77 | 32423.77 | 30.97 | 145.13 |
October | 0.513906E+11 | 0.467141E+11 | 35669.72 | 02-OCT-07:20 | 32423.77 | 32423.77 | 28.90 | 145.13 |
November | 0.518728E+11 | 0.471524E+11 | 35669.72 | 01-NOV-08:70 | 32423.77 | 32423.77 | 29.55 | 145.13 |
December | 0.517298E+11 | 0.470223E+11 | 35669.72 | 01-DEC-08:40 | 32423.77 | 32423.77 | 29.26 | 145.13 |
Annual Sum or Average | 0.632038E+12 | 0.574523E+12 | ||||||
Minimum of Months | 0.465777E+11 | 0.423392E+11 | 35669.72 | 32423.77 | 32423.77 | 28.82 | 145.13 | |
Maximum of Months | 0.575135E+11 | 0.522798E+11 | 35669.72 | 32423.77 | 32423.77 | 32.21 | 145.13 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 60.00 | 60.00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 60.00 | 60.00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 60.00 | 60.00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 60.00 | 60.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 60.00 | 60.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 60.00 | 60.00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 60.00 | 60.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 60.00 | 60.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 60.00 | 60.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 60.00 | 60.00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 60.00 | 60.00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 60.00 | 60.00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 732838.86 | 3366508.84 | 02-JAN-05:13 | 16.28 | 7.80 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 777392.33 | 2916877.64 | 06-FEB-06:03 | 15.00 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 855455.78 | 2707091.22 | 15-MAR-05:02 | 14.40 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 905200.78 | 2452039.53 | 14-APR-05:04 | 13.68 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 963001.37 | 3346908.33 | 22-MAY-05:04 | 16.23 | 7.74 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1007706.06 | 2783887.12 | 28-JUN-05:02 | 14.62 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 833903.89 | 2687611.51 | 18-JUL-05:02 | 14.35 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 919978.04 | 2974869.70 | 21-AUG-05:03 | 15.17 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 861045.31 | 3113951.33 | 18-SEP-05:02 | 15.56 | 7.08 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 824964.87 | 3517122.40 | 23-OCT-04:15 | 16.71 | 8.22 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 806383.93 | 3203786.00 | 13-NOV-06:04 | 15.82 | 7.33 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 742072.16 | 3186067.02 | 18-DEC-06:03 | 15.77 | 7.28 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 852645.84 | 0.00 | ||||||
Minimum of Months | 732838.86 | 2452039.53 | 13.68 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1007706.06 | 3517122.40 | 16.71 | 8.22 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 753783.88 | 4104826.29 | 02-JAN-05:12 | 18.39 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 787844.35 | 4129490.53 | 06-FEB-05:12 | 18.46 | 12.56 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 854894.82 | 4088758.09 | 25-MAR-05:02 | 18.35 | 12.50 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 903926.13 | 4155498.32 | 10-APR-03:02 | 18.72 | 12.60 | 0.00 | 0.00 | 01-APR-00:10 |
May | 961443.05 | 4181401.07 | 16-MAY-05:02 | 18.61 | 12.64 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1005895.06 | 4037172.55 | 13-JUN-05:02 | 18.20 | 12.43 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 833790.40 | 4062374.21 | 28-JUL-05:03 | 18.27 | 12.47 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 916603.88 | 4132456.66 | 07-AUG-03:02 | 18.47 | 12.57 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 860724.67 | 4097682.06 | 19-SEP-04:12 | 18.37 | 12.52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 824158.06 | 4419026.60 | 23-OCT-04:12 | 19.29 | 12.97 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 809516.14 | 4027812.32 | 06-NOV-05:12 | 18.17 | 12.42 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 765369.80 | 3980119.13 | 11-DEC-06:02 | 18.04 | 12.35 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 856637.98 | 0.00 | ||||||
Minimum of Months | 753783.88 | 3980119.13 | 18.04 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1005895.06 | 4419026.60 | 19.29 | 12.97 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 708636.48 | 1124821.64 | 04-JAN-13:20 | 40.75 | 36.12 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 980923.89 | 1409663.94 | 28-FEB-15:00 | 46.28 | 38.49 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1244617.96 | 1699225.07 | 21-MAR-13:10 | 51.85 | 41.16 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 1498220.85 | 1832624.55 | 01-APR-14:00 | 54.40 | 41.40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 862339.61 | 1308860.60 | 06-MAY-13:00 | 44.33 | 39.68 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1071401.38 | 1484438.74 | 13-JUN-15:00 | 47.73 | 39.63 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1187392.76 | 1526509.61 | 21-JUL-15:00 | 48.54 | 37.82 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1412917.12 | 1768833.12 | 13-AUG-15:00 | 53.18 | 39.98 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 782227.03 | 1135632.80 | 06-SEP-14:00 | 40.97 | 36.14 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 956780.62 | 1303949.47 | 04-OCT-14:00 | 44.24 | 36.47 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1155158.23 | 1565328.44 | 18-NOV-13:00 | 49.28 | 38.95 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1316946.88 | 1702900.20 | 08-DEC-15:00 | 51.92 | 38.89 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1098779.91 | 0.00 | ||||||
Minimum of Months | 708636.48 | 1124821.64 | 40.75 | 36.12 | 0.00 | 0.00 | ||
Maximum of Months | 1498220.85 | 1832624.55 | 54.40 | 41.40 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.40 | 58.40 | 10117.63 | 32719.37 | 17-JAN-12:53 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 58.21 | 58.21 | 10112.61 | 32582.79 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 57.37 | 57.37 | 10509.53 | 32246.73 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.85 | 56.85 | 9752.05 | 31589.77 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.18 | 57.18 | 9845.99 | 31019.35 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.50 | 57.50 | 9919.13 | 30373.45 | 02-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.18 | 57.18 | 9202.38 | 30111.21 | 24-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.96 | 57.96 | 10000.07 | 30470.93 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.46 | 57.46 | 9604.42 | 31090.15 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 56.92 | 56.92 | 9773.89 | 31793.31 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 57.41 | 57.41 | 10070.36 | 32335.62 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 56.88 | 56.88 | 9875.89 | 32690.98 | 26-DEC-12:25 |
Annual Sum or Average | 0.00 | 9897.59 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.85 | 56.85 | 9202.38 | 30111.21 | ||
Maximum of Months | 0.00 | 0.00 | 58.40 | 58.40 | 10509.53 | 32719.37 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1796027.31 | 6323073.51 | 12-JAN-13:05 | 31.52 | 27.47 | 0.45 | 4050.82 | 23-JAN-01:55 |
February | 2036568.99 | 6343108.54 | 07-FEB-13:05 | 31.56 | 27.49 | 0.33 | 2659.86 | 10-FEB-01:20 |
March | 2411158.18 | 6126363.37 | 27-MAR-13:00 | 31.20 | 27.85 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 3050945.73 | 7118913.47 | 10-APR-12:05 | 32.84 | 28.63 | 0.00 | 0.00 | 01-APR-00:10 |
May | 3385901.61 | 7237339.64 | 01-MAY-05:03 | 33.03 | 28.59 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3549442.68 | 6890576.18 | 28-JUN-05:04 | 32.46 | 28.12 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 2525788.97 | 6586939.84 | 27-JUL-12:05 | 31.96 | 27.81 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 3209937.21 | 7083745.93 | 22-AUG-12:05 | 32.78 | 28.61 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2945415.41 | 7062012.08 | 07-SEP-12:05 | 32.74 | 28.60 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 2720936.03 | 6843833.65 | 06-OCT-12:05 | 32.38 | 28.43 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 2462755.54 | 6582025.34 | 17-NOV-13:05 | 31.95 | 27.77 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1923846.40 | 6380458.01 | 12-DEC-13:05 | 31.62 | 27.56 | 5.01 | 8557.06 | 21-DEC-03:50 |
Annual Sum or Average | 2669759.40 | 0.49 | ||||||
Minimum of Months | 1796027.31 | 6126363.37 | 31.20 | 27.47 | 0.00 | 0.00 | ||
Maximum of Months | 3549442.68 | 7237339.64 | 33.03 | 28.63 | 5.01 | 8557.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.164597E+12 | 0.885461E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.167133E+12 | 0.902731E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.202867E+12 | 0.129758E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.213207E+12 | 0.150498E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.207023E+12 | 0.117340E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.216901E+12 | 0.118697E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202006E+12 | 0.122156E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.232225E+12 | 0.150115E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.183468E+12 | 0.103218E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.193836E+12 | 0.104491E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.194056E+12 | 0.102025E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.194296E+12 | 0.105059E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.237162E+13 | 0.138218E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.164597E+12 | 0.885461E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.232225E+12 | 0.150498E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.144400E+13 | 0.734847E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.138569E+13 | 0.710865E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166297E+13 | 0.960016E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.169000E+13 | 0.974687E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.187849E+13 | 0.983646E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.190242E+13 | 0.947623E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.159659E+13 | 0.868428E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.175502E+13 | 0.961961E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.161537E+13 | 0.852340E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.158222E+13 | 0.795775E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149806E+13 | 0.733203E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.141488E+13 | 0.690741E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.194257E+14 | 0.102141E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.138569E+13 | 0.690741E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.190242E+13 | 0.983646E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.151412E+12 | 0.779073E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.147904E+12 | 0.780106E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.180994E+12 | 0.108379E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.185598E+12 | 0.109425E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.203793E+12 | 0.109963E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.205693E+12 | 0.107790E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.171899E+12 | 0.943595E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.187109E+12 | 0.102320E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.173723E+12 | 0.927832E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.167211E+12 | 0.848818E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.158435E+12 | 0.797900E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.148596E+12 | 0.729671E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208237E+13 | 0.111858E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.147904E+12 | 0.729671E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.205693E+12 | 0.109963E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.110559E+12 | 0.151002E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.101612E+12 | 0.134121E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.124816E+12 | 0.152222E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.134740E+12 | 0.145434E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.151794E+12 | 0.153095E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.150431E+12 | 0.147916E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.126569E+12 | 0.147216E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.155493E+12 | 0.156084E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.133773E+12 | 0.145305E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131669E+12 | 0.148109E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.122770E+12 | 0.143906E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.112872E+12 | 0.145606E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155710E+13 | 0.177002E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.101612E+12 | 0.134121E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.155493E+12 | 0.156084E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.456851E+12 | 0.192439E+12 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.699252E+12 | 0.237375E+12 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.109537E+13 | 0.335713E+12 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.135086E+13 | 0.386119E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.486463E+12 | 0.203864E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.775386E+12 | 0.264173E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109267E+13 | 0.329424E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.139294E+13 | 0.389621E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.461696E+12 | 0.192236E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.782779E+12 | 0.261837E+12 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.105269E+13 | 0.315112E+12 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.137438E+13 | 0.379120E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110213E+14 | 0.348703E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.456851E+12 | 0.192236E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.139294E+13 | 0.389621E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.877994E+10 | 0.322348E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.139337E+11 | 0.421988E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.221540E+11 | 0.617293E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.281608E+11 | 0.747472E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.983985E+10 | 0.352443E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159132E+11 | 0.479050E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.221149E+11 | 0.604566E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.288857E+11 | 0.747533E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.914880E+10 | 0.327531E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.157813E+11 | 0.467566E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.212778E+11 | 0.577258E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.280243E+11 | 0.715117E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.224014E+12 | 0.638017E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.877994E+10 | 0.322348E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.288857E+11 | 0.747533E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.825201E+11 | 0.304904E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.132989E+12 | 0.402524E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.211606E+12 | 0.589258E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.267114E+12 | 0.710533E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.928265E+11 | 0.333743E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151929E+12 | 0.456943E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211052E+12 | 0.576741E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.274681E+12 | 0.711654E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.859056E+11 | 0.309430E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.150204E+12 | 0.445137E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.203328E+12 | 0.551187E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.266962E+12 | 0.681588E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.213112E+13 | 0.607364E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.825201E+11 | 0.304904E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.274681E+12 | 0.711654E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.833669E+10 | 0.309534E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.134119E+11 | 0.407633E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.213264E+11 | 0.596021E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.269420E+11 | 0.719064E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.947857E+10 | 0.340793E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.153672E+11 | 0.463538E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212673E+11 | 0.583284E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276452E+11 | 0.719186E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.875739E+10 | 0.315600E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.151439E+11 | 0.450639E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.204392E+11 | 0.556521E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.267911E+11 | 0.687264E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214907E+12 | 0.614908E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.833669E+10 | 0.309534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.276452E+11 | 0.719186E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.885461E+10 | 0.164597E+12 | 0.00 | 0.00 | 0.291597E+11 | 0.00 | 0.00 | 0.00 |
February | 0.902731E+10 | 0.167133E+12 | 0.00 | 0.00 | 0.324298E+11 | 0.00 | 0.00 | 0.00 |
March | 0.129758E+11 | 0.202867E+12 | 0.00 | 0.00 | 0.470846E+11 | 0.00 | 0.00 | 0.00 |
April | 0.150498E+11 | 0.213207E+12 | 0.00 | 0.00 | 0.673556E+11 | 0.00 | 0.00 | 0.00 |
May | 0.117340E+11 | 0.207023E+12 | 0.00 | 0.00 | 0.755533E+11 | 0.00 | 0.00 | 0.00 |
June | 0.118697E+11 | 0.216901E+12 | 0.00 | 0.00 | 0.772283E+11 | 0.00 | 0.00 | 0.00 |
July | 0.122156E+11 | 0.202006E+12 | 0.00 | 0.00 | 0.427702E+11 | 0.00 | 0.00 | 0.00 |
August | 0.150115E+11 | 0.232225E+12 | 0.00 | 0.00 | 0.656407E+11 | 0.00 | 0.00 | 0.00 |
September | 0.103218E+11 | 0.183468E+12 | 0.00 | 0.00 | 0.558418E+11 | 0.00 | 0.00 | 0.00 |
October | 0.104491E+11 | 0.193836E+12 | 0.00 | 0.00 | 0.492666E+11 | 0.00 | 0.00 | 0.00 |
November | 0.102025E+11 | 0.194056E+12 | 0.00 | 0.00 | 0.412854E+11 | 0.00 | 0.00 | 0.00 |
December | 0.105059E+11 | 0.194296E+12 | 0.00 | 0.00 | 0.318126E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138218E+12 | 0.237162E+13 | 0.00 | 0.00 | 0.615429E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.885461E+10 | 0.164597E+12 | 0.00 | 0.00 | 0.291597E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150498E+11 | 0.232225E+12 | 0.00 | 0.00 | 0.772283E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.734847E+11 | 0.144400E+13 | 0.00 | 0.00 | 0.296754E+12 | 0.00 | 0.00 | 0.00 |
February | 0.710865E+11 | 0.138569E+13 | 0.00 | 0.00 | 0.319324E+12 | 0.00 | 0.00 | 0.00 |
March | 0.960016E+11 | 0.166297E+13 | 0.00 | 0.00 | 0.449450E+12 | 0.00 | 0.00 | 0.00 |
April | 0.974687E+11 | 0.169000E+13 | 0.00 | 0.00 | 0.623966E+12 | 0.00 | 0.00 | 0.00 |
May | 0.983646E+11 | 0.187849E+13 | 0.00 | 0.00 | 0.727442E+12 | 0.00 | 0.00 | 0.00 |
June | 0.947623E+11 | 0.190242E+13 | 0.00 | 0.00 | 0.736872E+12 | 0.00 | 0.00 | 0.00 |
July | 0.868428E+11 | 0.159659E+13 | 0.00 | 0.00 | 0.404814E+12 | 0.00 | 0.00 | 0.00 |
August | 0.961961E+11 | 0.175502E+13 | 0.00 | 0.00 | 0.610275E+12 | 0.00 | 0.00 | 0.00 |
September | 0.852340E+11 | 0.161537E+13 | 0.00 | 0.00 | 0.544609E+12 | 0.00 | 0.00 | 0.00 |
October | 0.795775E+11 | 0.158222E+13 | 0.00 | 0.00 | 0.470945E+12 | 0.00 | 0.00 | 0.00 |
November | 0.733203E+11 | 0.149806E+13 | 0.00 | 0.00 | 0.403669E+12 | 0.00 | 0.00 | 0.00 |
December | 0.690741E+11 | 0.141488E+13 | 0.00 | 0.00 | 0.315995E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102141E+13 | 0.194257E+14 | 0.00 | 0.00 | 0.590411E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.690741E+11 | 0.138569E+13 | 0.00 | 0.00 | 0.296754E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983646E+11 | 0.190242E+13 | 0.00 | 0.00 | 0.736872E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.779073E+10 | 0.151412E+12 | 0.00 | 0.00 | 0.276657E+11 | 0.00 | 0.00 | 0.00 |
February | 0.780106E+10 | 0.147904E+12 | 0.00 | 0.00 | 0.299355E+11 | 0.00 | 0.00 | 0.00 |
March | 0.108379E+11 | 0.180994E+12 | 0.00 | 0.00 | 0.425716E+11 | 0.00 | 0.00 | 0.00 |
April | 0.109425E+11 | 0.185598E+12 | 0.00 | 0.00 | 0.600780E+11 | 0.00 | 0.00 | 0.00 |
May | 0.109963E+11 | 0.203793E+12 | 0.00 | 0.00 | 0.701431E+11 | 0.00 | 0.00 | 0.00 |
June | 0.107790E+11 | 0.205693E+12 | 0.00 | 0.00 | 0.706107E+11 | 0.00 | 0.00 | 0.00 |
July | 0.943595E+10 | 0.171899E+12 | 0.00 | 0.00 | 0.389523E+11 | 0.00 | 0.00 | 0.00 |
August | 0.102320E+11 | 0.187109E+12 | 0.00 | 0.00 | 0.589967E+11 | 0.00 | 0.00 | 0.00 |
September | 0.927832E+10 | 0.173723E+12 | 0.00 | 0.00 | 0.529808E+11 | 0.00 | 0.00 | 0.00 |
October | 0.848818E+10 | 0.167211E+12 | 0.00 | 0.00 | 0.460852E+11 | 0.00 | 0.00 | 0.00 |
November | 0.797900E+10 | 0.158435E+12 | 0.00 | 0.00 | 0.383514E+11 | 0.00 | 0.00 | 0.00 |
December | 0.729671E+10 | 0.148596E+12 | 0.00 | 0.00 | 0.292993E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111858E+12 | 0.208237E+13 | 0.00 | 0.00 | 0.565670E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.729671E+10 | 0.147904E+12 | 0.00 | 0.00 | 0.276657E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109963E+11 | 0.205693E+12 | 0.00 | 0.00 | 0.706107E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151002E+11 | 0.110559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134121E+11 | 0.101612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152222E+11 | 0.124816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145434E+11 | 0.134740E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153095E+11 | 0.151794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147916E+11 | 0.150431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147216E+11 | 0.126569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156084E+11 | 0.155493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145305E+11 | 0.133773E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148109E+11 | 0.131669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143906E+11 | 0.122770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145606E+11 | 0.112872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177002E+12 | 0.155710E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134121E+11 | 0.101612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156084E+11 | 0.155493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.944961E+11 | 0.358908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.853513E+11 | 0.547228E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944961E+11 | 0.854154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914478E+11 | 0.105619E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.944961E+11 | 0.377096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.914478E+11 | 0.602660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.944961E+11 | 0.857738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944961E+11 | 0.109782E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.914478E+11 | 0.360908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944961E+11 | 0.615438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914478E+11 | 0.829028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944961E+11 | 0.108976E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111261E+13 | 0.864693E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.853513E+11 | 0.358908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944961E+11 | 0.109782E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138171E+10 | 0.693816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124800E+10 | 0.109618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138171E+10 | 0.173627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133714E+10 | 0.220232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138171E+10 | 0.769713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133714E+10 | 0.124598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138171E+10 | 0.174509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138171E+10 | 0.227921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133714E+10 | 0.721062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138171E+10 | 0.124874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133714E+10 | 0.168423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138171E+10 | 0.222548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162685E+11 | 0.176481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124800E+10 | 0.693816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138171E+10 | 0.227921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131704E+11 | 0.652001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118958E+11 | 0.104632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131704E+11 | 0.165850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127455E+11 | 0.208806E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131704E+11 | 0.726226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127455E+11 | 0.118980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131704E+11 | 0.166548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131704E+11 | 0.216686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127455E+11 | 0.677081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131704E+11 | 0.118861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127455E+11 | 0.160955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131704E+11 | 0.211973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155071E+12 | 0.167882E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118958E+11 | 0.652001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131704E+11 | 0.216686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134250E+10 | 0.658385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121258E+10 | 0.105482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134250E+10 | 0.167087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129919E+10 | 0.210505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134250E+10 | 0.741314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129919E+10 | 0.120310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134250E+10 | 0.167770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134250E+10 | 0.217958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129919E+10 | 0.690058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134250E+10 | 0.119800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129919E+10 | 0.161732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134250E+10 | 0.212610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158069E+11 | 0.169223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121258E+10 | 0.658385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134250E+10 | 0.217958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.885461E+10 | 0.00 | 0.164597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902731E+10 | 0.00 | 0.167133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129758E+11 | 0.00 | 0.202867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150498E+11 | 0.00 | 0.213207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117340E+11 | 0.00 | 0.207023E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118697E+11 | 0.00 | 0.216901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122156E+11 | 0.00 | 0.202006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150115E+11 | 0.00 | 0.232225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103218E+11 | 0.00 | 0.183468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104491E+11 | 0.00 | 0.193836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102025E+11 | 0.00 | 0.194056E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105059E+11 | 0.00 | 0.194296E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138218E+12 | 0.00 | 0.237162E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.885461E+10 | 0.00 | 0.164597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150498E+11 | 0.00 | 0.232225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.734847E+11 | 0.00 | 0.144400E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710865E+11 | 0.00 | 0.138569E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.960016E+11 | 0.00 | 0.166297E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.974687E+11 | 0.00 | 0.169000E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.983646E+11 | 0.00 | 0.187849E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.947623E+11 | 0.00 | 0.190242E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.868428E+11 | 0.00 | 0.159659E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.961961E+11 | 0.00 | 0.175502E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852340E+11 | 0.00 | 0.161537E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.795775E+11 | 0.00 | 0.158222E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733203E+11 | 0.00 | 0.149806E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.690741E+11 | 0.00 | 0.141488E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102141E+13 | 0.00 | 0.194257E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.690741E+11 | 0.00 | 0.138569E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983646E+11 | 0.00 | 0.190242E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.779073E+10 | 0.00 | 0.151412E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.780106E+10 | 0.00 | 0.147904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108379E+11 | 0.00 | 0.180994E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109425E+11 | 0.00 | 0.185598E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109963E+11 | 0.00 | 0.203793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107790E+11 | 0.00 | 0.205693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.943595E+10 | 0.00 | 0.171899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102320E+11 | 0.00 | 0.187109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927832E+10 | 0.00 | 0.173723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848818E+10 | 0.00 | 0.167211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.797900E+10 | 0.00 | 0.158435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729671E+10 | 0.00 | 0.148596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111858E+12 | 0.00 | 0.208237E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.729671E+10 | 0.00 | 0.147904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109963E+11 | 0.00 | 0.205693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151002E+11 | 0.00 | 0.110559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134121E+11 | 0.00 | 0.101612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152222E+11 | 0.00 | 0.124816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145434E+11 | 0.00 | 0.134740E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153095E+11 | 0.00 | 0.151794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147916E+11 | 0.00 | 0.150431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147216E+11 | 0.00 | 0.126569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156084E+11 | 0.00 | 0.155493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145305E+11 | 0.00 | 0.133773E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148109E+11 | 0.00 | 0.131669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143906E+11 | 0.00 | 0.122770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145606E+11 | 0.00 | 0.112872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177002E+12 | 0.00 | 0.155710E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134121E+11 | 0.00 | 0.101612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156084E+11 | 0.00 | 0.155493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.944961E+11 | 0.00 | 0.456851E+12 | 0.00 | 0.979433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.853513E+11 | 0.00 | 0.699252E+12 | 0.00 | 0.152024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944961E+11 | 0.00 | 0.109537E+13 | 0.00 | 0.241217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914478E+11 | 0.00 | 0.135086E+13 | 0.00 | 0.294671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.944961E+11 | 0.00 | 0.486463E+12 | 0.00 | 0.109368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.914478E+11 | 0.00 | 0.775386E+12 | 0.00 | 0.172726E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.944961E+11 | 0.00 | 0.109267E+13 | 0.00 | 0.234928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944961E+11 | 0.00 | 0.139294E+13 | 0.00 | 0.295125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.914478E+11 | 0.00 | 0.461696E+12 | 0.00 | 0.100789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944961E+11 | 0.00 | 0.782779E+12 | 0.00 | 0.167341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914478E+11 | 0.00 | 0.105269E+13 | 0.00 | 0.223664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944961E+11 | 0.00 | 0.137438E+13 | 0.00 | 0.284623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111261E+13 | 0.00 | 0.110213E+14 | 0.00 | 0.237442E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.853513E+11 | 0.00 | 0.456851E+12 | 0.00 | 0.979433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944961E+11 | 0.00 | 0.139294E+13 | 0.00 | 0.295125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138171E+10 | 0.00 | 0.877994E+10 | 0.00 | 0.184177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124800E+10 | 0.00 | 0.139337E+11 | 0.00 | 0.297189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138171E+10 | 0.00 | 0.221540E+11 | 0.00 | 0.479122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133714E+10 | 0.00 | 0.281608E+11 | 0.00 | 0.613758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138171E+10 | 0.00 | 0.983985E+10 | 0.00 | 0.214272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133714E+10 | 0.00 | 0.159132E+11 | 0.00 | 0.345336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138171E+10 | 0.00 | 0.221149E+11 | 0.00 | 0.466395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138171E+10 | 0.00 | 0.288857E+11 | 0.00 | 0.609362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133714E+10 | 0.00 | 0.914880E+10 | 0.00 | 0.193817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138171E+10 | 0.00 | 0.157813E+11 | 0.00 | 0.329395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133714E+10 | 0.00 | 0.212778E+11 | 0.00 | 0.443544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138171E+10 | 0.00 | 0.280243E+11 | 0.00 | 0.576947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162685E+11 | 0.00 | 0.224014E+12 | 0.00 | 0.475331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124800E+10 | 0.00 | 0.877994E+10 | 0.00 | 0.184177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138171E+10 | 0.00 | 0.288857E+11 | 0.00 | 0.613758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.131704E+11 | 0.00 | 0.825201E+11 | 0.00 | 0.173200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118958E+11 | 0.00 | 0.132989E+12 | 0.00 | 0.283565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131704E+11 | 0.00 | 0.211606E+12 | 0.00 | 0.457554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127455E+11 | 0.00 | 0.267114E+12 | 0.00 | 0.583078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131704E+11 | 0.00 | 0.928265E+11 | 0.00 | 0.202039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127455E+11 | 0.00 | 0.151929E+12 | 0.00 | 0.329487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131704E+11 | 0.00 | 0.211052E+12 | 0.00 | 0.445037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131704E+11 | 0.00 | 0.274681E+12 | 0.00 | 0.579950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127455E+11 | 0.00 | 0.859056E+11 | 0.00 | 0.181975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131704E+11 | 0.00 | 0.150204E+12 | 0.00 | 0.313433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127455E+11 | 0.00 | 0.203328E+12 | 0.00 | 0.423732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131704E+11 | 0.00 | 0.266962E+12 | 0.00 | 0.549884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155071E+12 | 0.00 | 0.213112E+13 | 0.00 | 0.452293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118958E+11 | 0.00 | 0.825201E+11 | 0.00 | 0.173200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131704E+11 | 0.00 | 0.274681E+12 | 0.00 | 0.583078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134250E+10 | 0.00 | 0.833669E+10 | 0.00 | 0.175284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121258E+10 | 0.00 | 0.134119E+11 | 0.00 | 0.286375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134250E+10 | 0.00 | 0.213264E+11 | 0.00 | 0.461771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129919E+10 | 0.00 | 0.269420E+11 | 0.00 | 0.589145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134250E+10 | 0.00 | 0.947857E+10 | 0.00 | 0.206543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129919E+10 | 0.00 | 0.153672E+11 | 0.00 | 0.333619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134250E+10 | 0.00 | 0.212673E+11 | 0.00 | 0.449034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134250E+10 | 0.00 | 0.276452E+11 | 0.00 | 0.584936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129919E+10 | 0.00 | 0.875739E+10 | 0.00 | 0.185681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134250E+10 | 0.00 | 0.151439E+11 | 0.00 | 0.316389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129919E+10 | 0.00 | 0.204392E+11 | 0.00 | 0.426602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134250E+10 | 0.00 | 0.267911E+11 | 0.00 | 0.553014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158069E+11 | 0.00 | 0.214907E+12 | 0.00 | 0.456839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121258E+10 | 0.00 | 0.833669E+10 | 0.00 | 0.175284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134250E+10 | 0.00 | 0.276452E+11 | 0.00 | 0.589145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146281E+09 | 0.287042E+11 | 0.00 | 15198393.51 | 0.459966E+09 | 0.00 | 0.488370E+09 | 0.00 | 0.42 |
February | 2564198.73 | 0.283540E+11 | 0.00 | 3779564.34 | 0.468260E+09 | 0.00 | 63000302.82 | 0.00 | 0.42 |
March | 4197.01 | 0.400996E+11 | 0.00 | 414352.78 | 0.630397E+09 | 0.00 | 831624.98 | 0.00 | 0.43 |
April | 0.00 | 0.538457E+11 | 0.00 | 0.00 | 0.110586E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
May | 0.00 | 0.681112E+11 | 0.00 | 0.00 | 0.135138E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 207587.96 | 0.680619E+11 | 0.00 | 474123.64 | 0.122026E+10 | 0.00 | 2338564.28 | 0.00 | 0.43 |
July | 0.00 | 0.440586E+11 | 0.00 | 708860.55 | 0.878347E+09 | 0.00 | 6576921.54 | 0.00 | 0.41 |
August | 0.00 | 0.662984E+11 | 0.00 | 0.00 | 0.994831E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.554768E+11 | 0.00 | 0.00 | 0.118725E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 660446.06 | 0.512033E+11 | 0.00 | 567573.18 | 0.100678E+10 | 0.00 | 3866627.16 | 0.00 | 0.42 |
November | 18761827.39 | 0.426133E+11 | 0.00 | 5240537.11 | 0.644145E+09 | 0.00 | 96445555.70 | 0.00 | 0.42 |
December | 15300434.91 | 0.314092E+11 | 0.00 | 8036289.37 | 0.588790E+09 | 0.00 | 0.133297E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.183780E+09 | 0.578236E+12 | 0.00 | 34419694.48 | 0.105363E+11 | 0.00 | 0.794727E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.283540E+11 | 0.00 | 0.00 | 0.459966E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.146281E+09 | 0.681112E+11 | 0.00 | 15198393.51 | 0.135138E+10 | 0.00 | 0.488370E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22398020.88 | 0.110719E+11 | 0.00 | 5085017.08 | 0.610067E+10 | 0.00 | 0.122686E+09 | 0.00 | 0.38 |
February | 7768766.86 | 0.102107E+11 | 0.00 | 268218.71 | 0.884178E+10 | 0.00 | 4260600.43 | 0.00 | 0.44 |
March | 0.00 | 0.130910E+11 | 0.00 | 0.00 | 0.939528E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.00 | 0.157817E+11 | 0.00 | 0.00 | 0.111520E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
May | 0.00 | 0.209445E+11 | 0.00 | 0.00 | 0.118782E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.208320E+11 | 0.00 | 0.00 | 0.131968E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.165063E+11 | 0.00 | 0.00 | 0.145867E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.219070E+11 | 0.00 | 0.00 | 0.157840E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.189737E+11 | 0.00 | 0.00 | 0.113021E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.00 | 0.189222E+11 | 0.00 | 0.00 | 0.144604E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 583665.15 | 0.155839E+11 | 0.00 | 203615.72 | 0.144146E+11 | 0.00 | 221113.73 | 0.00 | 0.45 |
December | 61638047.08 | 0.122125E+11 | 0.00 | 1420258.45 | 0.130938E+11 | 0.00 | 34514848.41 | 0.00 | 0.46 |
Annual Sum or Average | 92388499.97 | 0.196037E+12 | 0.00 | 6977109.97 | 0.144206E+12 | 0.00 | 0.161683E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.102107E+11 | 0.00 | 0.00 | 0.610067E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 61638047.08 | 0.219070E+11 | 0.00 | 5085017.08 | 0.157840E+11 | 0.00 | 0.122686E+09 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184761E+09 | 0.107725E+12 | 0.00 | 44812576.34 | 0.318869E+11 | 0.00 | 0.154680E+10 | 0.00 | 0.34 |
February | 0.00 | 0.991596E+11 | 0.00 | 3598528.30 | 0.379977E+11 | 0.00 | 84025182.00 | 0.00 | 0.35 |
March | 0.00 | 0.121535E+12 | 0.00 | 0.00 | 0.499411E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 0.00 | 0.142798E+12 | 0.00 | 0.00 | 0.773691E+11 | 0.00 | 0.00 | 0.00 | 0.40 |
May | 0.00 | 0.199997E+12 | 0.00 | 0.00 | 0.823075E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.200263E+12 | 0.00 | 0.00 | 0.797345E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.154289E+12 | 0.00 | 0.00 | 0.749928E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.203211E+12 | 0.00 | 0.00 | 0.649627E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.181553E+12 | 0.00 | 0.00 | 0.741088E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.181485E+12 | 0.00 | 0.00 | 0.690033E+11 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 26821046.89 | 0.150535E+12 | 0.00 | 4318656.20 | 0.514971E+11 | 0.00 | 14237354.30 | 0.00 | 0.34 |
December | 0.128507E+09 | 0.117428E+12 | 0.00 | 19445032.80 | 0.416347E+11 | 0.00 | 0.486008E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.340089E+09 | 0.185998E+13 | 0.00 | 72174793.65 | 0.735436E+12 | 0.00 | 0.213107E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.991596E+11 | 0.00 | 0.00 | 0.318869E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.184761E+09 | 0.203211E+12 | 0.00 | 44812576.34 | 0.823075E+11 | 0.00 | 0.154680E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17930260.61 | 0.102301E+11 | 0.00 | 3367267.82 | 0.322345E+10 | 0.00 | 0.120380E+09 | 0.00 | 0.33 |
February | 0.00 | 0.950892E+10 | 0.00 | 272373.41 | 0.370553E+10 | 0.00 | 5734894.76 | 0.00 | 0.35 |
March | 0.00 | 0.117805E+11 | 0.00 | 0.00 | 0.478928E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 0.00 | 0.142130E+11 | 0.00 | 0.00 | 0.749237E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
May | 0.00 | 0.198398E+11 | 0.00 | 0.00 | 0.820441E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.198062E+11 | 0.00 | 0.00 | 0.799109E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.149140E+11 | 0.00 | 0.00 | 0.786035E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.198910E+11 | 0.00 | 0.00 | 0.659219E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.177304E+11 | 0.00 | 0.00 | 0.752400E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.173604E+11 | 0.00 | 0.00 | 0.723140E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 2890327.50 | 0.144499E+11 | 0.00 | 394620.79 | 0.537770E+10 | 0.00 | 1632978.91 | 0.00 | 0.34 |
December | 17945763.86 | 0.111942E+11 | 0.00 | 1159212.61 | 0.449426E+10 | 0.00 | 23905715.10 | 0.00 | 0.33 |
Annual Sum or Average | 38766351.98 | 0.180918E+12 | 0.00 | 5193474.63 | 0.744860E+11 | 0.00 | 0.151653E+09 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.950892E+10 | 0.00 | 0.00 | 0.322345E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 17945763.86 | 0.198910E+11 | 0.00 | 3367267.82 | 0.820441E+10 | 0.00 | 0.120380E+09 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3954746.41 | 0.208704E+10 | 0.00 | 383270.24 | 0.714797E+09 | 0.00 | 12021410.12 | 0.00 | 0.50 |
February | 974615.40 | 0.207702E+10 | 0.00 | 37795.68 | 0.103476E+10 | 0.00 | 591083.13 | 0.00 | 0.58 |
March | 0.00 | 0.278892E+10 | 0.00 | 0.00 | 0.105325E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 0.00 | 0.373080E+10 | 0.00 | 0.00 | 0.113252E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
May | 0.00 | 0.565877E+10 | 0.00 | 0.00 | 0.104371E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 0.00 | 0.621892E+10 | 0.00 | 0.00 | 0.121561E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.414549E+10 | 0.00 | 0.00 | 0.146866E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
August | 0.00 | 0.484062E+10 | 0.00 | 0.00 | 0.173805E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.414215E+10 | 0.00 | 0.00 | 0.120615E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.367470E+10 | 0.00 | 0.00 | 0.167132E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 107461.18 | 0.297741E+10 | 0.00 | 8294.46 | 0.170743E+10 | 0.00 | 6579.04 | 0.00 | 0.58 |
December | 9187592.76 | 0.220391E+10 | 0.00 | 85809.62 | 0.160029E+10 | 0.00 | 1981646.47 | 0.00 | 0.56 |
Annual Sum or Average | 14224415.75 | 0.445458E+11 | 0.00 | 515170.01 | 0.155865E+11 | 0.00 | 14600718.77 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.207702E+10 | 0.00 | 0.00 | 0.714797E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 9187592.76 | 0.621892E+10 | 0.00 | 383270.24 | 0.173805E+10 | 0.00 | 12021410.12 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2642350.97 | 0.173921E+10 | 0.00 | 359550.31 | 0.426589E+09 | 0.00 | 12290753.20 | 0.00 | 0.62 |
February | 629021.49 | 0.175106E+10 | 0.00 | 55975.98 | 0.623091E+09 | 0.00 | 849069.45 | 0.00 | 0.71 |
March | 0.00 | 0.225294E+10 | 0.00 | 0.00 | 0.669881E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
April | 0.00 | 0.281873E+10 | 0.00 | 0.00 | 0.728941E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
May | 0.00 | 0.389056E+10 | 0.00 | 0.00 | 0.699041E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
June | 0.00 | 0.387365E+10 | 0.00 | 0.00 | 0.861293E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
July | 0.00 | 0.246716E+10 | 0.00 | 0.00 | 0.104200E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.318329E+10 | 0.00 | 0.00 | 0.118296E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.332113E+10 | 0.00 | 0.00 | 0.687155E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.00 | 0.275167E+10 | 0.00 | 0.00 | 0.104600E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 70268.56 | 0.219517E+10 | 0.00 | 2227.97 | 0.107486E+10 | 0.00 | 1502.10 | 0.00 | 0.63 |
December | 5841922.89 | 0.164966E+10 | 0.00 | 64901.46 | 0.999166E+09 | 0.00 | 1880919.68 | 0.00 | 0.62 |
Annual Sum or Average | 9183563.91 | 0.318942E+11 | 0.00 | 482655.72 | 0.100410E+11 | 0.00 | 15022244.43 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.164966E+10 | 0.00 | 0.00 | 0.426589E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 5841922.89 | 0.389056E+10 | 0.00 | 359550.31 | 0.118296E+10 | 0.00 | 12290753.20 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2803061.42 | 0.343866E+10 | 0.00 | 645496.66 | 0.481008E+09 | 0.00 | 18995808.21 | 0.00 | 0.74 |
February | 975776.77 | 0.312338E+10 | 0.00 | 56289.79 | 0.886218E+09 | 0.00 | 868373.13 | 0.00 | 0.77 |
March | 0.00 | 0.334266E+10 | 0.00 | 0.00 | 0.971547E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
April | 0.00 | 0.357789E+10 | 0.00 | 0.00 | 0.116439E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.00 | 0.478959E+10 | 0.00 | 0.00 | 0.124497E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
June | 0.00 | 0.478462E+10 | 0.00 | 0.00 | 0.140411E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 0.00 | 0.343291E+10 | 0.00 | 0.00 | 0.161749E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.438688E+10 | 0.00 | 0.00 | 0.182683E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.440539E+10 | 0.00 | 0.00 | 0.116522E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.459841E+10 | 0.00 | 0.00 | 0.149475E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
November | 107589.23 | 0.433876E+10 | 0.00 | 15066.78 | 0.147617E+10 | 0.00 | 8221.79 | 0.00 | 0.73 |
December | 8622133.82 | 0.378108E+10 | 0.00 | 169584.87 | 0.124332E+10 | 0.00 | 3721986.28 | 0.00 | 0.77 |
Annual Sum or Average | 12508561.24 | 0.480002E+11 | 0.00 | 886438.09 | 0.149760E+11 | 0.00 | 23594389.41 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.312338E+10 | 0.00 | 0.00 | 0.481008E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 8622133.82 | 0.478959E+10 | 0.00 | 645496.66 | 0.182683E+10 | 0.00 | 18995808.21 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1539535.12 | 0.248989E+10 | 0.00 | 522287.22 | 0.254936E+09 | 0.00 | 14822618.75 | 0.00 | 0.79 |
February | 462413.44 | 0.302457E+10 | 0.00 | 50432.37 | 0.262743E+09 | 0.00 | 1059433.55 | 0.00 | 0.98 |
March | 0.00 | 0.440697E+10 | 0.00 | 0.00 | 98314224.65 | 0.00 | 0.00 | 0.00 | 1.15 |
April | 0.00 | 0.622210E+10 | 0.00 | 0.00 | 55248706.36 | 0.00 | 0.00 | 0.00 | 1.31 |
May | 0.00 | 0.544945E+10 | 0.00 | 0.00 | 0.345346E+09 | 0.00 | 0.00 | 0.00 | 0.93 |
June | 0.00 | 0.621028E+10 | 0.00 | 0.00 | 0.266930E+09 | 0.00 | 0.00 | 0.00 | 1.05 |
July | 0.00 | 0.528494E+10 | 0.00 | 0.00 | 0.192295E+09 | 0.00 | 0.00 | 0.00 | 1.03 |
August | 0.00 | 0.749107E+10 | 0.00 | 0.00 | 0.136102E+09 | 0.00 | 0.00 | 0.00 | 1.19 |
September | 0.00 | 0.477291E+10 | 0.00 | 0.00 | 0.369067E+09 | 0.00 | 0.00 | 0.00 | 0.88 |
October | 0.00 | 0.505045E+10 | 0.00 | 0.00 | 0.412798E+09 | 0.00 | 0.00 | 0.00 | 0.91 |
November | 15178.26 | 0.474762E+10 | 0.00 | 50392.35 | 0.275796E+09 | 0.00 | 89509.07 | 0.00 | 0.97 |
December | 2718389.22 | 0.440402E+10 | 0.00 | 383491.37 | 86936455.14 | 0.00 | 9858075.51 | 0.00 | 1.05 |
Annual Sum or Average | 4735516.04 | 0.595543E+11 | 0.00 | 1006603.31 | 0.275651E+10 | 0.00 | 25829636.88 | 0.00 | 1.02 |
Minimum of Months | 0.00 | 0.248989E+10 | 0.00 | 0.00 | 55248706.36 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 2718389.22 | 0.749107E+10 | 0.00 | 522287.22 | 0.412798E+09 | 0.00 | 14822618.75 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 55224900.44 | 0.212542E+11 | 0.00 | 2578812.18 | 0.367090E+10 | 0.00 | 0.118932E+09 | 0.00 | 0.48 |
February | 0.00 | 0.217178E+11 | 0.00 | 492039.64 | 0.406327E+10 | 0.00 | 11328042.87 | 0.00 | 0.53 |
March | 0.00 | 0.288814E+11 | 0.00 | 0.00 | 0.526472E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.391794E+11 | 0.00 | 0.00 | 0.778935E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
May | 0.00 | 0.619393E+11 | 0.00 | 0.00 | 0.552716E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
June | 0.00 | 0.700314E+11 | 0.00 | 0.00 | 0.491654E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.00 | 0.449102E+11 | 0.00 | 0.00 | 0.553318E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.513050E+11 | 0.00 | 0.00 | 0.604273E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.430181E+11 | 0.00 | 0.00 | 0.758803E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.377280E+11 | 0.00 | 0.00 | 0.735613E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 4080422.78 | 0.305726E+11 | 0.00 | 227075.25 | 0.570221E+10 | 0.00 | 712724.55 | 0.00 | 0.50 |
December | 38732357.76 | 0.221659E+11 | 0.00 | 547503.49 | 0.508901E+10 | 0.00 | 22354630.78 | 0.00 | 0.46 |
Annual Sum or Average | 98037680.97 | 0.472703E+12 | 0.00 | 3845430.56 | 0.685432E+11 | 0.00 | 0.153327E+09 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.212542E+11 | 0.00 | 0.00 | 0.367090E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 55224900.44 | 0.700314E+11 | 0.00 | 2578812.18 | 0.778935E+10 | 0.00 | 0.118932E+09 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28490773.66 | 0.188509E+11 | 0.00 | 3360267.37 | 0.179684E+10 | 0.00 | 0.169180E+09 | 0.00 | 0.63 |
February | 0.00 | 0.201836E+11 | 0.00 | 783960.06 | 0.185321E+10 | 0.00 | 18199304.99 | 0.00 | 0.72 |
March | 0.00 | 0.265548E+11 | 0.00 | 0.00 | 0.259979E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
April | 0.00 | 0.357859E+11 | 0.00 | 0.00 | 0.383521E+10 | 0.00 | 0.00 | 0.00 | 0.87 |
May | 0.00 | 0.443160E+11 | 0.00 | 0.00 | 0.335755E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.00 | 0.458568E+11 | 0.00 | 0.00 | 0.353676E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.300116E+11 | 0.00 | 0.00 | 0.369429E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.398126E+11 | 0.00 | 0.00 | 0.341221E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.367719E+11 | 0.00 | 0.00 | 0.333490E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 0.00 | 0.314554E+11 | 0.00 | 0.00 | 0.370952E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
November | 2451897.14 | 0.259659E+11 | 0.00 | 280198.09 | 0.276289E+10 | 0.00 | 1043389.79 | 0.00 | 0.62 |
December | 20073827.02 | 0.200860E+11 | 0.00 | 798248.82 | 0.243856E+10 | 0.00 | 33112057.80 | 0.00 | 0.59 |
Annual Sum or Average | 51016497.81 | 0.375651E+12 | 0.00 | 5222674.33 | 0.363317E+11 | 0.00 | 0.221535E+09 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.188509E+11 | 0.00 | 0.00 | 0.179684E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 28490773.66 | 0.458568E+11 | 0.00 | 3360267.37 | 0.383521E+10 | 0.00 | 0.169180E+09 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26183754.23 | 0.367736E+11 | 0.00 | 6024106.55 | 0.178597E+10 | 0.00 | 0.256961E+09 | 0.00 | 0.77 |
February | 0.00 | 0.344636E+11 | 0.00 | 768963.02 | 0.244623E+10 | 0.00 | 17833638.34 | 0.00 | 0.76 |
March | 0.00 | 0.356750E+11 | 0.00 | 0.00 | 0.437846E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
April | 0.00 | 0.379666E+11 | 0.00 | 0.00 | 0.800207E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
May | 0.00 | 0.513634E+11 | 0.00 | 0.00 | 0.768356E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.00 | 0.515728E+11 | 0.00 | 0.00 | 0.750528E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 0.00 | 0.359866E+11 | 0.00 | 0.00 | 0.743404E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.463522E+11 | 0.00 | 0.00 | 0.679162E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.462016E+11 | 0.00 | 0.00 | 0.712860E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.00 | 0.494378E+11 | 0.00 | 0.00 | 0.527236E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 3784836.64 | 0.480461E+11 | 0.00 | 469327.69 | 0.307939E+10 | 0.00 | 1635231.92 | 0.00 | 0.71 |
December | 29128068.37 | 0.418114E+11 | 0.00 | 1732821.52 | 0.199082E+10 | 0.00 | 52332989.82 | 0.00 | 0.75 |
Annual Sum or Average | 59096659.24 | 0.515651E+12 | 0.00 | 8995218.78 | 0.634984E+11 | 0.00 | 0.328763E+09 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 0.344636E+11 | 0.00 | 0.00 | 0.178597E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 29128068.37 | 0.515728E+11 | 0.00 | 6024106.55 | 0.800207E+10 | 0.00 | 0.256961E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19858927.51 | 0.212038E+11 | 0.00 | 3057973.12 | 0.136851E+10 | 0.00 | 0.132287E+09 | 0.00 | 0.68 |
February | 0.00 | 0.230003E+11 | 0.00 | 455357.42 | 0.139987E+10 | 0.00 | 10732296.78 | 0.00 | 0.78 |
March | 0.00 | 0.320906E+11 | 0.00 | 0.00 | 0.149777E+10 | 0.00 | 0.00 | 0.00 | 0.92 |
April | 0.00 | 0.422693E+11 | 0.00 | 0.00 | 0.234385E+10 | 0.00 | 0.00 | 0.00 | 0.98 |
May | 0.00 | 0.487662E+11 | 0.00 | 0.00 | 0.242476E+10 | 0.00 | 0.00 | 0.00 | 0.86 |
June | 0.00 | 0.509744E+11 | 0.00 | 0.00 | 0.243807E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
July | 0.00 | 0.352004E+11 | 0.00 | 0.00 | 0.231093E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
August | 0.00 | 0.459476E+11 | 0.00 | 0.00 | 0.225244E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.406946E+11 | 0.00 | 0.00 | 0.251754E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
October | 0.00 | 0.365710E+11 | 0.00 | 0.00 | 0.253265E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
November | 2634382.61 | 0.302055E+11 | 0.00 | 270082.98 | 0.201669E+10 | 0.00 | 923761.55 | 0.00 | 0.68 |
December | 19843003.27 | 0.236714E+11 | 0.00 | 933110.31 | 0.167912E+10 | 0.00 | 27337424.51 | 0.00 | 0.67 |
Annual Sum or Average | 42336313.39 | 0.430595E+12 | 0.00 | 4716523.82 | 0.247822E+11 | 0.00 | 0.171280E+09 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.212038E+11 | 0.00 | 0.00 | 0.136851E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 19858927.51 | 0.509744E+11 | 0.00 | 3057973.12 | 0.253265E+10 | 0.00 | 0.132287E+09 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5773306.91 | 0.196964E+10 | 0.00 | 162070.01 | 0.373076E+09 | 0.00 | 8918064.05 | 0.00 | 0.46 |
February | 0.00 | 0.205384E+10 | 0.00 | 36752.88 | 0.376119E+09 | 0.00 | 760009.32 | 0.00 | 0.52 |
March | 0.00 | 0.270648E+10 | 0.00 | 0.00 | 0.487223E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.378149E+10 | 0.00 | 0.00 | 0.688695E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
May | 0.00 | 0.591555E+10 | 0.00 | 0.00 | 0.515511E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
June | 0.00 | 0.656082E+10 | 0.00 | 0.00 | 0.478153E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.427316E+10 | 0.00 | 0.00 | 0.549309E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.489821E+10 | 0.00 | 0.00 | 0.575450E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.411500E+10 | 0.00 | 0.00 | 0.726686E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.359414E+10 | 0.00 | 0.00 | 0.732301E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 439913.84 | 0.292090E+10 | 0.00 | 14754.60 | 0.563353E+09 | 0.00 | 88685.42 | 0.00 | 0.49 |
December | 4381115.61 | 0.209895E+10 | 0.00 | 30737.38 | 0.521356E+09 | 0.00 | 498048.19 | 0.00 | 0.45 |
Annual Sum or Average | 10594336.36 | 0.448882E+11 | 0.00 | 244314.87 | 0.658723E+10 | 0.00 | 10264806.97 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.196964E+10 | 0.00 | 0.00 | 0.373076E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 5773306.91 | 0.656082E+10 | 0.00 | 162070.01 | 0.732301E+09 | 0.00 | 8918064.05 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2990004.81 | 0.181436E+10 | 0.00 | 270134.52 | 0.184355E+09 | 0.00 | 13733202.05 | 0.00 | 0.63 |
February | 0.00 | 0.195891E+10 | 0.00 | 63391.79 | 0.171038E+09 | 0.00 | 1292287.40 | 0.00 | 0.72 |
March | 0.00 | 0.255192E+10 | 0.00 | 0.00 | 0.239122E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
April | 0.00 | 0.350200E+10 | 0.00 | 0.00 | 0.350961E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
May | 0.00 | 0.435724E+10 | 0.00 | 0.00 | 0.316196E+09 | 0.00 | 0.00 | 0.00 | 0.79 |
June | 0.00 | 0.444977E+10 | 0.00 | 0.00 | 0.344798E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
July | 0.00 | 0.293957E+10 | 0.00 | 0.00 | 0.373952E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.394169E+10 | 0.00 | 0.00 | 0.326752E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.363389E+10 | 0.00 | 0.00 | 0.320323E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 0.00 | 0.310220E+10 | 0.00 | 0.00 | 0.371939E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
November | 283147.65 | 0.256096E+10 | 0.00 | 21144.55 | 0.278437E+09 | 0.00 | 100840.74 | 0.00 | 0.63 |
December | 1573546.47 | 0.199212E+10 | 0.00 | 52105.38 | 0.242322E+09 | 0.00 | 2056357.28 | 0.00 | 0.61 |
Annual Sum or Average | 4846698.93 | 0.368046E+11 | 0.00 | 406776.24 | 0.352019E+10 | 0.00 | 17182687.47 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.181436E+10 | 0.00 | 0.00 | 0.171038E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 2990004.81 | 0.444977E+10 | 0.00 | 270134.52 | 0.373952E+09 | 0.00 | 13733202.05 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2729631.97 | 0.342977E+10 | 0.00 | 462681.69 | 0.177355E+09 | 0.00 | 20614858.12 | 0.00 | 0.75 |
February | 0.00 | 0.321615E+10 | 0.00 | 60076.58 | 0.226478E+09 | 0.00 | 1235697.69 | 0.00 | 0.74 |
March | 0.00 | 0.330937E+10 | 0.00 | 0.00 | 0.395948E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.00 | 0.366402E+10 | 0.00 | 0.00 | 0.709581E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
May | 0.00 | 0.495892E+10 | 0.00 | 0.00 | 0.704883E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
June | 0.00 | 0.490080E+10 | 0.00 | 0.00 | 0.716311E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.344306E+10 | 0.00 | 0.00 | 0.729117E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.442991E+10 | 0.00 | 0.00 | 0.653083E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.442144E+10 | 0.00 | 0.00 | 0.658811E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 0.00 | 0.468519E+10 | 0.00 | 0.00 | 0.521235E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 438967.84 | 0.456505E+10 | 0.00 | 35256.04 | 0.320403E+09 | 0.00 | 154607.55 | 0.00 | 0.69 |
December | 2435329.23 | 0.397850E+10 | 0.00 | 108760.70 | 0.216551E+09 | 0.00 | 3087449.53 | 0.00 | 0.74 |
Annual Sum or Average | 5603929.03 | 0.490022E+11 | 0.00 | 666775.01 | 0.602976E+10 | 0.00 | 25092612.88 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.321615E+10 | 0.00 | 0.00 | 0.177355E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 2729631.97 | 0.495892E+10 | 0.00 | 462681.69 | 0.729117E+09 | 0.00 | 20614858.12 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2319822.39 | 0.196121E+10 | 0.00 | 228371.16 | 0.134063E+09 | 0.00 | 9592219.29 | 0.00 | 0.66 |
February | 0.00 | 0.213409E+10 | 0.00 | 35675.34 | 0.126322E+09 | 0.00 | 747665.89 | 0.00 | 0.75 |
March | 0.00 | 0.294185E+10 | 0.00 | 0.00 | 0.138736E+09 | 0.00 | 0.00 | 0.00 | 0.88 |
April | 0.00 | 0.395057E+10 | 0.00 | 0.00 | 0.210440E+09 | 0.00 | 0.00 | 0.00 | 0.93 |
May | 0.00 | 0.457198E+10 | 0.00 | 0.00 | 0.256018E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
June | 0.00 | 0.474288E+10 | 0.00 | 0.00 | 0.231665E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.330943E+10 | 0.00 | 0.00 | 0.251003E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.432575E+10 | 0.00 | 0.00 | 0.222943E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.382860E+10 | 0.00 | 0.00 | 0.253446E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
October | 0.00 | 0.345342E+10 | 0.00 | 0.00 | 0.255987E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
November | 282784.95 | 0.286304E+10 | 0.00 | 22851.23 | 0.204409E+09 | 0.00 | 98308.52 | 0.00 | 0.67 |
December | 1680892.42 | 0.224155E+10 | 0.00 | 59918.22 | 0.173779E+09 | 0.00 | 1733021.51 | 0.00 | 0.65 |
Annual Sum or Average | 4283499.76 | 0.403244E+11 | 0.00 | 346815.96 | 0.245881E+10 | 0.00 | 12171215.21 | 0.00 | 0.76 |
Minimum of Months | 0.00 | 0.196121E+10 | 0.00 | 0.00 | 0.126322E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 2319822.39 | 0.474288E+10 | 0.00 | 228371.16 | 0.256018E+09 | 0.00 | 9592219.29 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.727632E+09 | 0.00 | 100741.71 | 0.00 | 0.00 | 170993.29 | 0.00 | 0.59 |
February | 0.00 | 0.804574E+09 | 0.00 | 7146.57 | 0.00 | 0.00 | 17940.23 | 0.00 | 0.59 |
March | 0.00 | 0.105253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.134256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.147292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.153534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.118572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.151525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.124360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.129792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.112529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.937002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.142403E+11 | 0.00 | 107888.27 | 0.00 | 0.00 | 188933.52 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.727632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.153534E+10 | 0.00 | 100741.71 | 0.00 | 0.00 | 170993.29 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.719642E+10 | 0.00 | 1005490.09 | 0.00 | 0.00 | 2196867.71 | 0.00 | 0.59 |
February | 0.00 | 0.802614E+10 | 0.00 | 68212.17 | 0.00 | 0.00 | 184327.02 | 0.00 | 0.59 |
March | 0.00 | 0.105178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.134821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.145914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.153067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.118448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.151848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.122991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.129332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.112425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.938572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.142011E+12 | 0.00 | 1073702.26 | 0.00 | 0.00 | 2381194.73 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.719642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.153067E+11 | 0.00 | 1005490.09 | 0.00 | 0.00 | 2196867.71 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.719923E+09 | 0.00 | 101772.95 | 0.00 | 0.00 | 261964.46 | 0.00 | 0.59 |
February | 0.00 | 0.802193E+09 | 0.00 | 6975.03 | 0.00 | 0.00 | 18921.12 | 0.00 | 0.59 |
March | 0.00 | 0.105099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.135050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.146331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.153108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.118364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.152157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.129300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.112318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.938363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.142112E+11 | 0.00 | 108747.98 | 0.00 | 0.00 | 280885.57 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.719923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.153108E+10 | 0.00 | 101772.95 | 0.00 | 0.00 | 261964.46 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.173028E+11 | 0.00 | 1717779.35 | 0.00 | 0.00 | 53596.51 | 0.00 | 0.66 |
February | 0.00 | 0.179783E+11 | 0.00 | 362576.16 | 0.00 | 0.00 | 141672.20 | 0.00 | 0.66 |
March | 0.00 | 0.230327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
April | 0.00 | 0.252524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
May | 0.00 | 0.345850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 0.00 | 0.344420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.260241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.296788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.293999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.00 | 0.291927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
November | 0.00 | 0.247100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
December | 0.00 | 0.183203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.309919E+12 | 0.00 | 2080355.51 | 0.00 | 0.00 | 195268.71 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.173028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.345850E+11 | 0.00 | 1717779.35 | 0.00 | 0.00 | 141672.20 | 0.00 | 0.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:56:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.410099E+12 | -0.763356E+10 | 0.00 | -0.882907E+12 | 0.296218E+13 |
February | 0.400395E+12 | -0.912979E+10 | 0.00 | -0.923820E+12 | 0.318752E+13 |
March | 0.532805E+12 | -0.175116E+11 | 0.00 | -0.118924E+13 | 0.416937E+13 |
April | 0.534818E+12 | -0.203131E+11 | 0.00 | -0.160332E+13 | 0.457255E+13 |
May | 0.529789E+12 | -0.252628E+11 | 0.00 | -0.198660E+13 | 0.373841E+13 |
June | 0.544728E+12 | -0.243644E+11 | 0.00 | -0.196295E+13 | 0.412588E+13 |
July | 0.448962E+12 | -0.130408E+11 | 0.00 | -0.134798E+13 | 0.410263E+13 |
August | 0.572224E+12 | -0.215086E+11 | 0.00 | -0.177066E+13 | 0.474470E+13 |
September | 0.449521E+12 | -0.149505E+11 | 0.00 | -0.163922E+13 | 0.331630E+13 |
October | 0.495550E+12 | -0.141339E+11 | 0.00 | -0.154556E+13 | 0.367718E+13 |
November | 0.397503E+12 | -0.100715E+11 | 0.00 | -0.129080E+13 | 0.388104E+13 |
December | 0.384402E+12 | -0.787702E+10 | 0.00 | -0.101066E+13 | 0.415103E+13 |
Annual Sum or Average | 0.570080E+13 | -0.185798E+12 | 0.00 | -0.171537E+14 | 0.466288E+14 |
Minimum of Months | 0.384402E+12 | -0.252628E+11 | 0.00 | -0.198660E+13 | 0.296218E+13 |
Maximum of Months | 0.572224E+12 | -0.763356E+10 | 0.00 | -0.882907E+12 | 0.474470E+13 |